Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:20:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2121.70 | 425.86 | 425.86 |
Net Site Energy | 2121.70 | 425.86 | 425.86 |
Total Source Energy | 6719.42 | 1348.69 | 1348.69 |
Net Source Energy | 6719.42 | 1348.69 | 1348.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 814.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 173.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2121.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 814.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 173.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 814.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 173.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 205.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 425.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 205.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 425.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2121.698 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2121.698 | 100.00 |
Total On-Site and Utility Electric Sources | 2121.698 | 100.00 |
Total Electricity End Uses | 2121.698 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 528.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1199.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:39 | - | - | - | - | - | - | - | - | - | - | - | 28-APR-11:20 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 116504.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2468.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 211985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 116504.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2468.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2580.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 951.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 549.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6719.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 517.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1348.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 517.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1348.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.73 | 0.274848 | 0.292000 | 0.796225 | 0.732928 | 0.500000 | 0.001386 |
CORE_MID VAV BOX COMPONENT | 2.27 | 0.330310 | 0.343000 | 0.778248 | 0.880827 | 0.500000 | 0.001153 |
CORE_TOP VAV BOX COMPONENT | 2.52 | 0.297699 | 0.322000 | 0.810634 | 0.793863 | 0.500000 | 0.001280 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.909136 | 0.173782 | 0.200000 | 0.181827 | 0.463419 | 0.500000 | 0.002192 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.721064 | 0.138714 | 0.200000 | 0.144213 | 0.369904 | 0.500000 | 0.002747 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.01 | 0.156313 | 0.200000 | 0.202148 | 0.416835 | 0.500000 | 0.002437 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.815991 | 0.122569 | 0.200000 | 0.163198 | 0.326851 | 0.500000 | 0.003108 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.791058 | 0.199722 | 0.212000 | 0.167704 | 0.532592 | 0.500000 | 0.001908 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.661312 | 0.151247 | 0.200000 | 0.132262 | 0.403327 | 0.500000 | 0.002519 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.885602 | 0.178400 | 0.200000 | 0.177120 | 0.475734 | 0.500000 | 0.002136 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.699054 | 0.143072 | 0.200000 | 0.139811 | 0.381526 | 0.500000 | 0.002663 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.786366 | 0.200914 | 0.209000 | 0.164350 | 0.535770 | 0.500000 | 0.001896 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.676426 | 0.147868 | 0.200000 | 0.135285 | 0.394315 | 0.500000 | 0.002577 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.886336 | 0.178253 | 0.200000 | 0.177267 | 0.475340 | 0.500000 | 0.002137 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.727967 | 0.137390 | 0.200000 | 0.145593 | 0.366373 | 0.500000 | 0.002773 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26580.45 |
CORE_MID VAV BOX REHEAT COIL | 25980.32 |
CORE_TOP VAV BOX REHEAT COIL | 27061.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7037.13 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4814.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7002.09 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5448.06 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5598.49 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4415.33 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5912.83 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4667.32 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5486.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4516.24 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5917.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4860.36 |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.88 | 1.41 | 5.76 | 1.41 | 5.39 | 5.39 | 0.300000 | 0.262183 | 5.39 |
PACU_VAV_MID | 2.67 | 1.40 | 5.35 | 1.40 | 4.92 | 4.92 | 0.300000 | 0.284912 | 4.92 |
PACU_VAV_TOP | 2.99 | 1.50 | 5.97 | 1.50 | 5.81 | 5.81 | 0.300000 | 0.258487 | 5.81 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.39 |
PACU_VAV_MID_OA_CONTROLLER | 4.92 |
PACU_VAV_TOP_OA_CONTROLLER | 5.81 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.39 | 129520.52 | 0.711261 | 1.80 | 43169.19 | 0.711261 |
PACU_VAV_MID COOLING COIL | 4.92 | 121004.05 | 0.704275 | 1.64 | 40330.65 | 0.704275 |
PACU_VAV_TOP COOLING COIL | 5.81 | 137372.46 | 0.716436 | 1.94 | 45786.24 | 0.716436 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.39 |
PACU_VAV_MID FAN | 4.92 |
PACU_VAV_TOP FAN | 5.81 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4542E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4882E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7144E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7426E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4687E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4900E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5694E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5839E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6568E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2174E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3085E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3336E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2899E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3868E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8227E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0568E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4554E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4962E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7159E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7512E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4702E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4970E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5692E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5837E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2028E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3634E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9332E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1584E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0136E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9772E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3172E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5628E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8407E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8536E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6327E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6422E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4643E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4678E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9989E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0039E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4834E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5151E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1127E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1381E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8415E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8592E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5692E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5837E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2596E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2649E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7679E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7780E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5867E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.7310E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8227E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0568E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4829E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5144E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1120E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1363E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8401E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8543E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5694E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5839E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4226E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0155E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0068E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7455E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2202E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6254E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3172E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5628E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3293E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3538E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0194E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0433E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9682E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9821E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9990E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0040E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0467E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0831E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.6505E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2402E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7949E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1176E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2209E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5024E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0727E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2876E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8193E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0917E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9235E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9227E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2554E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5255E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.6048E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6840E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0789E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3440E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8923E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0071E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2209E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5024E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3153E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9558E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9202E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6981E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1525E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5865E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2554E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5255E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0463E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6499E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2397E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7944E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1172E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2206E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5023E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0726E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2875E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8191E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0915E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9233E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9225E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2551E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5253E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.6049E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6839E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0789E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3439E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8922E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0070E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2206E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5023E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3153E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9557E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9201E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6980E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1523E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5863E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2551E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5253E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37831.50666 | 37831.50666 | 2.72680 | 2.72680 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 460.54308 | 460.54308 | 1.97077E-002 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31503.64818 | 31503.64818 | 2.26894 | 2.26894 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6689.82468 | 6689.82468 | 0.27965 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 34633.18463 | 34633.18463 | 2.51750 | 2.51750 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11597.79250 | 11597.79250 | 0.48950 | 0.48950 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12506.96665 | 12506.96665 | 0.90914 | 0.90914 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 4959.68103 | 4959.68103 | 0.21080 | 0.21080 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9919.68927 | 9919.68927 | 0.72106 | 0.72106 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3237.84930 | 3237.84930 | 0.13765 | 0.13765 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13904.72657 | 13904.72657 | 1.01074 | 1.01074 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 4935.14436 | 4935.14436 | 0.20975 | 0.20975 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11225.61966 | 11225.61966 | 0.81599 | 0.81599 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3252.01722 | 3252.01722 | 0.13825 | 0.13825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10882.63309 | 10882.63309 | 0.79106 | 0.79106 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2482.48386 | 2482.48386 | 0.10480 | 0.10480 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9097.73878 | 9097.73878 | 0.66131 | 0.66131 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1646.82863 | 1646.82863 | 6.95755E-002 | 6.95755E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12183.28873 | 12183.28873 | 0.88560 | 0.88560 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2471.43868 | 2471.43868 | 0.10433 | 0.10433 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9616.96887 | 9616.96887 | 0.69905 | 0.69905 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1654.09494 | 1654.09494 | 6.98872E-002 | 6.98872E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10818.02118 | 10818.02118 | 0.78637 | 0.78637 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3541.10507 | 3541.10507 | 0.15011 | 0.15011 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9305.61663 | 9305.61663 | 0.67643 | 0.67643 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2335.64896 | 2335.64896 | 9.90373E-002 | 9.90373E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12193.32508 | 12193.32508 | 0.88634 | 0.88634 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3522.73619 | 3522.73619 | 0.14932 | 0.14932 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10014.67165 | 10014.67165 | 0.72797 | 0.72797 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2345.93158 | 2345.93158 | 9.94758E-002 | 9.94758E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 100161.21 | 5.38983 | 5.38983 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 94.08 | 0.77791 | 0.77791 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 93679.98 | 4.91641 | 4.91641 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 111.59 | 0.92264 | 0.92264 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 105673.64 | 5.81081 | 5.81081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 143.43 | 1.18594 | 1.18594 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.72680 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27485 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79622 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73293 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38622E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26580.44609 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26894 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33031 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77825 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88083 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15346E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25980.32293 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.51750 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29770 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81063 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79386 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27982E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27061.46004 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90914 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17378 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18183 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46342 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19240E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7037.13248 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72106 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13871 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14421 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36990 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74666E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4814.27210 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01074 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15631 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20215 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41683 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43742E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7002.08656 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81599 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12257 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16320 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32685 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10845E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5448.06413 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79106 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19972 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16770 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53259 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90765E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5598.48981 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66131 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15125 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13226 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40333 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51905E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4415.32893 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88560 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17840 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17712 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47573 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13565E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5912.82546 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69905 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14307 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13981 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38153 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66299E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4667.32026 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78637 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20091 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16435 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53577 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89634E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5486.52528 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67643 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14787 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13529 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39431 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57662E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4516.24043 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88634 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17825 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17727 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47534 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13742E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5917.72523 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72797 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13739 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14559 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36637 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77313E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4860.35805 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88191 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41312 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.76382 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41312 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.38983 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.38983 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.26218 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.67302 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40074 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.34604 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.40074 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91641 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.91641 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.28491 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.98721 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50202 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.97443 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.50202 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.81081 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.81081 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.25849 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.38983 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.91641 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.81081 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.38983 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.38983 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 129520.52392 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71126 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.79643 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 43169.19062 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71126 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.38983 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91641 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.91641 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 121004.05436 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70427 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63864 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40330.65132 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70427 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.91641 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.81081 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.81081 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 137372.45594 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71644 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.93674 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 45786.23956 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71644 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.81081 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 129174.40 | 440761.34 | 12.46 | 3.19 | 3.57 | 3.76 | 3.91 | 10.89 | 12.18 | 12.84 | 13.33 | 6.2310 | 4.9456 | 3.3241 | 1.4176 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 120772.73 | 412093.65 | 12.51 | 3.20 | 3.58 | 3.78 | 3.92 | 10.93 | 12.23 | 12.90 | 13.37 | 5.6837 | 4.5069 | 3.0374 | 1.3007 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 136932.48 | 467233.01 | 12.42 | 3.19 | 3.56 | 3.75 | 3.90 | 10.87 | 12.14 | 12.80 | 13.31 | 6.7177 | 5.3390 | 3.5910 | 1.5215 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1439885191 | 0.2418215847 | Pass | Pass | 9.3421341649E-002 | 0.2892468874 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4632356830E-002 | 5.3586644325E-002 | Pass | Pass | 7.4684250729E-003 | 7.2619406225E-002 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.7038440261E-002 | 2.3477960764E-002 | Pass | Pass | 0.1285012711 | 0.6686463703 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2435330515E-002 | 3.4828149729E-002 | Pass | Pass | 0.5048917531 | 3.5985939444 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.8854163170E-002 | 0.1550458111 | Pass | Pass | 4.4375214934E-002 | 0.2048901382 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.7931021942E-002 | 8.6172806368E-002 | Pass | Pass | 7.8605664267E-003 | 8.8640725049E-002 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6078644323E-002 | 8.3811208012E-002 | Pass | Pass | 7.7300355628E-003 | 8.7839862396E-002 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.3237075968E-002 | 0.1037707880 | Pass | Pass | 8.2047483149E-003 | 9.0875107631E-002 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.0078191582E-002 | 0.1256428229 | Pass | Pass | 1.5300078148E-002 | 0.1417983257 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.1307927000E-002 | 0.1246107208 | Pass | Pass | 8.1979878321E-003 | 9.0846250241E-002 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1165814078 | 0.1773519263 | Pass | Pass | 9.2193373271E-002 | 0.2878021440 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1416513314 | 0.2183277336 | Pass | Pass | 9.2376435281E-002 | 0.2878802422 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1401194962 | 0.2157962826 | Pass | Pass | 9.2076623910E-002 | 0.2883310942 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1520787090 | 0.2400419085 | Pass | Pass | 9.1984461666E-002 | 0.2866078929 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.4319615014E-002 | 0.1368582808 | Pass | Pass | 4.3881661410E-002 | 0.2038773314 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.9028882970E-002 | 0.1714663660 | Pass | Pass | 4.4444055958E-002 | 0.2050006412 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1098363390 | 0.1824985567 | Pass | Pass | 5.3506694901E-002 | 0.2513094511 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1068062700 | 0.1966668126 | Pass | Pass | 4.3920724205E-002 | 0.2029693250 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2118.92 | -84.6 | 0.00 | -1104.7 | 3978.85 | 4908.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 8.71 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 5.48 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.26 | 0.0000 | Y | 8.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 5.49 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.64 | 0.0000 | Y | 8.68 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 5.48 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 8.71 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 5.48 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.26 | 0.0000 | Y | 8.55 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 5.49 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.85 | 41.85 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.85 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.85 | 46.68 | 41.32 | |
Exterior Lighting Total | 5686.19 | 50.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 129520.52 | 92122.93 | 37397.60 | 0.71 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 121004.05 | 85220.13 | 35783.93 | 0.70 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 137372.46 | 98418.57 | 38953.89 | 0.72 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 129174.4 | 3.19 | 10.89 | N/A | N/A | 12.46 | |
PACU_VAV_MID COOLING COIL | 120772.7 | 3.20 | 10.93 | N/A | N/A | 12.51 | |
PACU_VAV_TOP COOLING COIL | 136932.5 | 3.19 | 10.87 | N/A | N/A | 12.42 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 26580.45 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25980.32 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27061.46 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7037.13 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4814.27 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7002.09 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5448.06 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5598.49 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4415.33 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5912.83 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4667.32 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5486.53 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4516.24 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5917.73 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4860.36 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.39 | 11722.29 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.92 | 10762.08 | 2189.01 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.81 | 12637.87 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 129174.40 | 3.19 | 10.89 | 12.46 | 6.2310 | 3.57 | 12.18 | 4.9456 | 3.76 | 12.84 | 3.3241 | 3.91 | 13.33 | 1.4176 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120772.73 | 3.20 | 10.93 | 12.51 | 5.6837 | 3.58 | 12.23 | 4.5069 | 3.78 | 12.90 | 3.0374 | 3.92 | 13.37 | 1.3007 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 136932.48 | 3.19 | 10.87 | 12.42 | 6.7177 | 3.56 | 12.14 | 5.3390 | 3.75 | 12.80 | 3.5910 | 3.90 | 13.31 | 1.5215 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37831.51 | 37831.51 | 38.46 | 2.727 | 2.727 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 31503.65 | 31503.65 | 32.03 | 2.269 | 2.269 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 34633.18 | 34633.18 | 35.21 | 2.517 | 2.517 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00885 | 42.61 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12506.97 | 12506.97 | 60.32 | 0.909 | 0.909 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00874 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9919.69 | 9919.69 | 75.57 | 0.721 | 0.721 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00869 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13904.73 | 13904.73 | 67.06 | 1.011 | 1.011 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00871 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11225.62 | 11225.62 | 85.53 | 0.816 | 0.816 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00867 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10882.63 | 10882.63 | 52.49 | 0.791 | 0.791 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9097.74 | 9097.74 | 69.31 | 0.661 | 0.661 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00869 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12183.29 | 12183.29 | 58.76 | 0.886 | 0.886 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00873 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9616.97 | 9616.97 | 73.27 | 0.699 | 0.699 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00868 | 41.83 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10818.02 | 10818.02 | 52.18 | 0.786 | 0.786 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00877 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9305.62 | 9305.62 | 70.89 | 0.676 | 0.676 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00870 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12193.33 | 12193.33 | 58.81 | 0.886 | 0.886 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00874 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10014.67 | 10014.67 | 76.30 | 0.728 | 0.728 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00868 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 460.54 | 460.54 | 0.47 | 0.020 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00871 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6689.82 | 6689.82 | 6.80 | 0.280 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11597.79 | 11597.79 | 11.79 | 0.489 | 0.489 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 4959.68 | 4959.68 | 23.92 | 0.211 | 0.211 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3237.85 | 3237.85 | 24.67 | 0.138 | 0.138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 4935.14 | 4935.14 | 23.80 | 0.210 | 0.210 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3252.02 | 3252.02 | 24.78 | 0.138 | 0.138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2482.48 | 2482.48 | 11.97 | 0.105 | 0.105 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1646.83 | 1646.83 | 12.55 | 0.070 | 0.070 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2471.44 | 2471.44 | 11.92 | 0.104 | 0.104 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1654.09 | 1654.09 | 12.60 | 0.070 | 0.070 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3541.11 | 3541.11 | 17.08 | 0.150 | 0.150 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2335.65 | 2335.65 | 17.79 | 0.099 | 0.099 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3522.74 | 3522.74 | 16.99 | 0.149 | 0.149 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2345.93 | 2345.93 | 17.87 | 0.099 | 0.099 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.39 | 5.39 | 0.78 | 0.78 | 5.3898 | 1.4131 | 5.3898 | 0.2622 | 0.3000 |
PACU_VAV_MID | 4.92 | 4.92 | 0.92 | 0.92 | 4.9164 | 1.4007 | 4.9164 | 0.2849 | 0.3000 |
PACU_VAV_TOP | 5.81 | 5.81 | 1.19 | 1.19 | 5.8108 | 1.5020 | 5.8108 | 0.2585 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26580.446 | 26580.446 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26580.45 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00870976 | 56.2156 | 460.54 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25980.323 | 25980.323 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25980.32 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6689.82 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27061.460 | 27061.460 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27061.46 | 16340.94 | 0.489498 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11597.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7037.132 | 7037.132 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7037.13 | 7037.13 | 0.210799 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813285 | 52.5391 | 4959.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4814.272 | 4814.272 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4814.27 | 4595.04 | 0.137646 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813397 | 52.5462 | 3237.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7002.087 | 7002.087 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7002.09 | 7002.09 | 0.209749 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813374 | 52.5447 | 4935.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5448.064 | 5448.064 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5448.06 | 4615.27 | 0.138252 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813316 | 52.5410 | 3252.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5598.490 | 5598.490 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5598.49 | 3498.67 | 0.104804 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815465 | 52.6785 | 2482.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4415.329 | 4415.329 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4415.33 | 2322.65 | 0.069576 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815704 | 52.6937 | 1646.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5912.825 | 5912.825 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5912.83 | 3482.85 | 0.104330 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815517 | 52.6818 | 2471.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4667.320 | 4667.320 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4667.32 | 2333.05 | 0.069887 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815648 | 52.6901 | 1654.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5486.525 | 5486.525 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5486.53 | 5011.06 | 0.150108 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816588 | 52.7498 | 3541.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4516.240 | 4516.240 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4516.24 | 3306.17 | 0.099037 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816711 | 52.7576 | 2335.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5917.725 | 5917.725 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5917.73 | 4984.89 | 0.149324 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816678 | 52.7555 | 3522.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4860.358 | 4860.358 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4860.36 | 3320.81 | 0.099476 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816631 | 52.7525 | 2345.93 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 129520.524 | 92122.926 | 5.389833 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 120817.61 | 108876.14 | 5.389833 | 28.17 | 18.41 | 0.00922680 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 22.1745 | 24.00 | 0.00878360 | 47.2426 | 74130.57 | 0.00 | 133553.05 | 93668.45 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.616950 | 14.87 | 13.39 | 0.00896857 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 73.9151 | 21.00 | 0.00815671 | 52.6918 | 8615.16 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 121004.054 | 85220.126 | 4.916410 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 113479.53 | 101571.28 | 4.916410 | 28.58 | 18.60 | 0.00929572 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 24.3098 | 24.00 | 0.00881760 | 47.4230 | 67547.49 | 0.00 | 124771.42 | 86701.16 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.474923 | 14.22 | 13.12 | 0.00895171 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 81.0327 | 21.00 | 0.00810661 | 52.3722 | 18435.25 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 137372.456 | 98418.570 | 5.810814 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 127681.55 | 115498.51 | 5.810814 | 27.88 | 18.28 | 0.00918679 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.5680 | 24.00 | 0.00877240 | 47.1833 | 79729.53 | 0.00 | 141649.44 | 100042.97 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.743244 | 15.28 | 13.40 | 0.00881543 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 68.5601 | 21.00 | 0.00807834 | 52.1919 | 27982.48 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 26580.446 | 26580.446 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26580.45 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26580.45 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00870976 | 21.00 | 0.00870976 | 56.2156 | 460.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25980.323 | 25980.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25980.32 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25980.32 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6689.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27061.460 | 27061.460 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27061.46 | 16340.94 | 1.0000 | 0.58915674 | 0.489498 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27061.46 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11597.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7037.132 | 7037.132 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7037.13 | 7037.13 | 1.0000 | 0.25371694 | 0.210799 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7037.13 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813285 | 21.00 | 0.00813285 | 52.5391 | 4959.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4814.272 | 4814.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4814.27 | 4595.04 | 1.0000 | 0.16566956 | 0.137646 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4814.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813397 | 21.00 | 0.00813397 | 52.5462 | 3237.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7002.087 | 7002.087 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7002.09 | 7002.09 | 1.0000 | 0.25245339 | 0.209749 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7002.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813374 | 21.00 | 0.00813374 | 52.5447 | 4935.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5448.064 | 5448.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5448.06 | 4615.27 | 1.0000 | 0.16639909 | 0.138252 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5448.06 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813316 | 21.00 | 0.00813316 | 52.5410 | 3252.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5598.490 | 5598.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5598.49 | 3498.67 | 1.0000 | 0.12614120 | 0.104804 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5598.49 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815465 | 21.00 | 0.00815465 | 52.6785 | 2482.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4415.329 | 4415.329 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4415.33 | 2322.65 | 1.0000 | 0.08374077 | 0.069576 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4415.33 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815704 | 21.00 | 0.00815704 | 52.6937 | 1646.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5912.825 | 5912.825 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5912.83 | 3482.85 | 1.0000 | 0.12557081 | 0.104330 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5912.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815517 | 21.00 | 0.00815517 | 52.6818 | 2471.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4667.320 | 4667.320 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4667.32 | 2333.05 | 1.0000 | 0.08411584 | 0.069887 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4667.32 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815648 | 21.00 | 0.00815648 | 52.6901 | 1654.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5486.525 | 5486.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5486.53 | 5011.06 | 1.0000 | 0.18066875 | 0.150108 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5486.53 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816588 | 21.00 | 0.00816588 | 52.7498 | 3541.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4516.240 | 4516.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4516.24 | 3306.17 | 1.0000 | 0.11920074 | 0.099037 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4516.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816711 | 21.00 | 0.00816711 | 52.7576 | 2335.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5917.725 | 5917.725 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5917.73 | 4984.89 | 1.0000 | 0.17972528 | 0.149324 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5917.73 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816678 | 21.00 | 0.00816678 | 52.7555 | 3522.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4860.358 | 4860.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4860.36 | 3320.81 | 1.0000 | 0.11972854 | 0.099476 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4860.36 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816631 | 21.00 | 0.00816631 | 52.7525 | 2345.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 129520.524 | 92122.926 | 5.389833 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9922 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.389833 | 6.48717637 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 120817.61 | 108876.14 | 0.9328 | 6.48717637 | 5.389833 | 28.17 | 18.41 | 0.00922680 | 51864.0 | 11.03 | 11.03 | 0.00850000 | 32517.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11722.286 | 109095.33 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 22.1745 | 24.00 | 0.00878360 | 24.00 | 0.00878360 | 47.2426 | 74130.57 | 0.00 | 133553.05 | 93668.45 | 6.23098195 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.94 | 11.92 | 0.00867497 | 33888.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.389833 | 6.48717637 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.94615291 | 1.616950 | 14.87 | 13.39 | 0.00896857 | 37615.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 73.9151 | 21.00 | 0.00844468 | 21.00 | 0.00815671 | 52.6918 | 8615.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 121004.054 | 85220.126 | 4.916410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1203 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.916410 | 5.91736669 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 113479.53 | 101571.28 | 0.9378 | 5.91736669 | 4.916410 | 28.58 | 18.60 | 0.00929572 | 52455.3 | 11.02 | 11.02 | 0.00850000 | 32506.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10762.076 | 102717.45 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 24.3098 | 24.00 | 0.00881760 | 24.00 | 0.00881760 | 47.4230 | 67547.49 | 0.00 | 124771.42 | 86701.16 | 5.68367544 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.72 | 11.71 | 0.00855846 | 33369.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.916410 | 5.91736669 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.77521001 | 1.474923 | 14.22 | 13.12 | 0.00895171 | 36916.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 81.0327 | 20.73 | 0.00808985 | 21.00 | 0.00810661 | 52.3722 | 18435.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 137372.456 | 98418.570 | 5.810814 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9178 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.810814 | 6.99386634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 127681.55 | 115498.51 | 0.9295 | 6.99386634 | 5.810814 | 27.88 | 18.28 | 0.00918679 | 51462.6 | 11.03 | 11.03 | 0.00850000 | 32517.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12637.871 | 115043.68 | 42.80 | 0.01078182 | 23.86 | 1.19517000 | 20.5680 | 24.00 | 0.00877240 | 24.00 | 0.00877240 | 47.1833 | 79729.53 | 0.00 | 141649.44 | 100042.97 | 6.71766149 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.08 | 12.06 | 0.00875629 | 34236.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.810814 | 6.99386634 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.09815990 | 1.743244 | 15.28 | 13.40 | 0.00881543 | 37648.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 1.19517000 | 68.5601 | 20.90 | 0.00807834 | 21.00 | 0.00807834 | 52.1919 | 27982.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5604.50 | 0.00 | 0.00 |
CORE_MID | 4878.83 | 217.83 | 0.00 |
CORE_TOP | 4434.67 | 647.50 | 0.50 |
PERIMETER_TOP_ZN_3 | 4429.83 | 1243.17 | 308.83 |
PERIMETER_TOP_ZN_2 | 4675.00 | 1155.00 | 390.33 |
PERIMETER_TOP_ZN_1 | 4827.00 | 1040.17 | 384.33 |
PERIMETER_TOP_ZN_4 | 4494.83 | 1343.33 | 360.17 |
PERIMETER_BOT_ZN_3 | 4943.67 | 540.83 | 203.33 |
PERIMETER_BOT_ZN_2 | 5203.83 | 573.33 | 324.17 |
PERIMETER_BOT_ZN_1 | 5335.00 | 1166.33 | 941.00 |
PERIMETER_BOT_ZN_4 | 5134.00 | 614.67 | 305.17 |
PERIMETER_MID_ZN_3 | 4713.50 | 866.17 | 279.50 |
PERIMETER_MID_ZN_2 | 4069.83 | 869.50 | 361.50 |
PERIMETER_MID_ZN_1 | 5094.33 | 701.00 | 357.17 |
PERIMETER_MID_ZN_4 | 4799.33 | 963.67 | 336.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5729.17 | 2294.00 | 1199.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 76.33 | 0.00 | 52.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 97.67 | 0.00 | 76.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 95.00 | 0.00 | 73.17 |
PERIMETER_TOP_ZN_4 | 0.00 | 90.83 | 0.00 | 57.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 50.50 | 0.00 | 36.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 89.67 | 0.00 | 70.83 |
PERIMETER_BOT_ZN_1 | 0.83 | 420.17 | 0.83 | 396.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 84.00 | 0.00 | 50.83 |
PERIMETER_MID_ZN_3 | 0.00 | 58.33 | 0.00 | 43.00 |
PERIMETER_MID_ZN_2 | 0.00 | 82.33 | 0.00 | 71.00 |
PERIMETER_MID_ZN_1 | 0.00 | 82.50 | 0.00 | 68.83 |
PERIMETER_MID_ZN_4 | 0.00 | 72.00 | 0.00 | 49.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.83 | 598.17 | 0.83 | 528.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.490 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.435 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.428 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.599 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.755 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.732 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.767 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.511 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.646 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.723 | 1.236 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.643 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.598 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.713 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.731 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.761 | 0.028 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8408917.60 | 0.00 | 8408917.60 | 0.00 | 8408917.60 | 13393058.27 | 7196.12 | 105.16 | 1458.72 | 543.19 |
CORE_MID | 7366678.19 | 0.00 | 7366678.19 | 0.00 | 7366678.19 | 13393058.27 | 8440.65 | 45.85 | 273.50 | 424.43 |
CORE_TOP | 7304441.15 | 0.00 | 7304441.15 | 0.00 | 7304441.15 | 13393058.27 | 8626.23 | 25.62 | 108.15 | 464.54 |
PERIMETER_TOP_ZN_3 | 2119493.19 | 0.00 | 2119493.19 | 186056.00 | 2305549.19 | 2823374.22 | 3900.57 | 579.27 | 4280.15 | 464.54 |
PERIMETER_TOP_ZN_2 | 1684207.77 | 0.00 | 1684207.77 | 124036.59 | 1808244.35 | 1787429.43 | 3240.39 | 15.51 | 5504.10 | 464.54 |
PERIMETER_TOP_ZN_1 | 2569467.81 | 0.00 | 2569467.81 | 186056.00 | 2755523.80 | 2823374.22 | 3261.37 | 14.73 | 5483.90 | 464.54 |
PERIMETER_TOP_ZN_4 | 1730948.50 | 0.00 | 1730948.50 | 124036.59 | 1854985.08 | 1787312.18 | 3334.19 | 33.86 | 5391.95 | 464.54 |
PERIMETER_BOT_ZN_3 | 1842447.65 | 0.00 | 1842447.65 | 98926.03 | 1941373.68 | 2823374.22 | 6443.83 | 100.03 | 2216.14 | 543.19 |
PERIMETER_BOT_ZN_2 | 1472764.06 | 0.00 | 1472764.06 | 65950.29 | 1538714.35 | 1787429.43 | 3563.19 | 132.41 | 5064.40 | 543.19 |
PERIMETER_BOT_ZN_1 | 2545851.65 | 0.00 | 2545851.65 | 4077227.68 | 6623079.33 | 2823374.22 | 3780.42 | 95.70 | 4883.87 | 543.19 |
PERIMETER_BOT_ZN_4 | 1479332.35 | 0.00 | 1479332.35 | 65950.29 | 1545282.63 | 1787312.18 | 3844.55 | 102.53 | 4812.92 | 543.19 |
PERIMETER_MID_ZN_3 | 2092407.77 | 0.00 | 2092407.77 | 154878.15 | 2247285.91 | 2823374.22 | 5407.16 | 86.52 | 3266.32 | 424.43 |
PERIMETER_MID_ZN_2 | 1655132.61 | 0.00 | 1655132.61 | 103251.48 | 1758384.09 | 1787429.43 | 3342.11 | 33.57 | 5384.32 | 1333.43 |
PERIMETER_MID_ZN_1 | 2539097.09 | 0.00 | 2539097.09 | 154878.15 | 2693975.24 | 2823374.22 | 3363.26 | 43.65 | 5353.09 | 424.43 |
PERIMETER_MID_ZN_4 | 1697304.55 | 0.00 | 1697304.55 | 103251.48 | 1800556.03 | 1787312.18 | 3496.74 | 40.71 | 5222.55 | 424.43 |
Total Facility | 46508491.92 | 0.00 | 46508491.92 | 5444498.70 | 51952990.62 | 67843644.98 | 8760.00 | 1246.24 | 5952.68 | 1630.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3555 | 0.0000 | 0.3555 | 0.0000 | 0.3555 | 0.4247 | 4393.90 | 104.82 | 1444.28 |
CORE_MID | 0.3155 | 0.0000 | 0.3155 | 0.0000 | 0.3155 | 0.4247 | 5625.33 | 45.65 | 272.02 |
CORE_TOP | 0.3105 | 0.0000 | 0.3105 | 0.0000 | 0.3105 | 0.4247 | 5810.17 | 25.47 | 107.36 |
PERIMETER_TOP_ZN_3 | 0.0915 | 0.0000 | 0.0915 | 0.0049 | 0.0965 | 0.0895 | 1541.94 | 280.92 | 4120.14 |
PERIMETER_TOP_ZN_2 | 0.0730 | 0.0000 | 0.0730 | 0.0033 | 0.0763 | 0.0567 | 887.39 | 15.34 | 5040.27 |
PERIMETER_TOP_ZN_1 | 0.1119 | 0.0000 | 0.1119 | 0.0049 | 0.1169 | 0.0895 | 908.48 | 14.51 | 5020.01 |
PERIMETER_TOP_ZN_4 | 0.0742 | 0.0000 | 0.0742 | 0.0033 | 0.0775 | 0.0567 | 981.41 | 33.86 | 4927.73 |
PERIMETER_BOT_ZN_3 | 0.0780 | 0.0000 | 0.0780 | 0.0026 | 0.0806 | 0.0895 | 3670.57 | 98.13 | 2174.30 |
PERIMETER_BOT_ZN_2 | 0.0625 | 0.0000 | 0.0625 | 0.0018 | 0.0642 | 0.0567 | 1283.84 | 131.66 | 4527.50 |
PERIMETER_BOT_ZN_1 | 0.1102 | 0.0000 | 0.1102 | 0.1886 | 0.2988 | 0.0895 | 1488.87 | 85.02 | 4369.11 |
PERIMETER_BOT_ZN_4 | 0.0622 | 0.0000 | 0.0622 | 0.0018 | 0.0639 | 0.0567 | 1569.03 | 101.83 | 4272.14 |
PERIMETER_MID_ZN_3 | 0.0913 | 0.0000 | 0.0913 | 0.0041 | 0.0954 | 0.0895 | 2644.14 | 85.03 | 3213.82 |
PERIMETER_MID_ZN_2 | 0.0689 | 0.0000 | 0.0689 | 0.0029 | 0.0718 | 0.0567 | 902.64 | 23.37 | 4107.99 |
PERIMETER_MID_ZN_1 | 0.1117 | 0.0000 | 0.1117 | 0.0041 | 0.1158 | 0.0895 | 967.55 | 38.90 | 4936.55 |
PERIMETER_MID_ZN_4 | 0.0735 | 0.0000 | 0.0735 | 0.0027 | 0.0763 | 0.0567 | 1103.65 | 40.64 | 4798.71 |
Total Facility | 1.9905 | 0.0000 | 1.9905 | 0.2250 | 2.2155 | 2.1513 | 5943.00 | 932.67 | 5231.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 22815092.42 | 0.00 | 22815092.42 | 22614548.33 | 3111.38 | 0.00 | 5648.63 | 543.19 |
PACU_VAV_MID | 22237548.75 | 0.00 | 22237548.75 | 22614548.33 | 3262.39 | 0.00 | 5497.61 | 424.43 |
PACU_VAV_TOP | 22321465.65 | 0.00 | 22321465.65 | 22614548.33 | 3224.17 | 0.00 | 5535.83 | 464.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9683 | 0.0000 | 0.9683 | 0.7171 | 837.57 | 0.00 | 5105.43 |
PACU_VAV_MID | 0.9623 | 0.0000 | 0.9623 | 0.7171 | 869.82 | 0.00 | 5073.18 |
PACU_VAV_TOP | 0.9577 | 0.0000 | 0.9577 | 0.7171 | 871.71 | 0.00 | 5071.29 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.63 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5497.61 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5535.83 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1273 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1273 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1224 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
Electricity:Building | 1020.12 | 13479.36 | 29-MAY-17:20 | 74341.76 | 14-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1020.12 | 13479.36 | 29-MAY-17:20 | 74341.76 | 14-MAR-07:10 |
InteriorLights:Electricity | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.43 | 1001.61 | 29-MAY-17:20 | 32642.50 | 14-MAR-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.04 | 422.10 | 30-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.89 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.89 | 422.10 | 30-APR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.02 | 422.10 | 23-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-10:40 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-10:40 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.87 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.87 | 422.10 | 26-MAR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.88 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.48 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.48 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.04 | 422.10 | 30-APR-17:10 | 2793.69 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-11:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.89 | 269.43 | 30-APR-17:10 | 1768.58 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.48 | 22.79 | 01-JAN-08:00 | 860.01 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.89 | 422.10 | 30-APR-17:10 | 2793.68 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:10 | 1358.45 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.49 | 22.79 | 01-JAN-10:20 | 859.95 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 1015.43 | 367.92 | 01-JAN-00:10 | 142245.35 | 10-AUG-15:30 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 01-MAR-13:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 01-MAR-13:10 |
ElectricityPurchased:Facility | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
ElectricityPurchased:Plant | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
Cogeneration:ElectricityPurchased | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
ElectricityNet:Plant | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
Cogeneration:ElectricityNet | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
General:Cogeneration:ElectricityNet | 2121.70 | 13851.75 | 11-JUN-17:20 | 211985.66 | 10-AUG-15:40 |
Heating:Electricity | 0.45 | 0.00 | 01-JAN-00:10 | 6545.09 | 20-JAN-07:30 |
General:Heating:Electricity | 0.45 | 0.00 | 01-JAN-00:10 | 6545.09 | 20-JAN-07:30 |
Fans:Electricity | 173.37 | 0.00 | 01-JAN-00:10 | 26454.56 | 05-SEP-15:30 |
General:Fans:Electricity | 173.37 | 0.00 | 01-JAN-00:10 | 26454.56 | 05-SEP-15:30 |
ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 814.70 | 0.00 | 01-JAN-00:10 | 116549.45 | 10-AUG-15:30 |
General:Cooling:Electricity | 814.70 | 0.00 | 01-JAN-00:10 | 116549.45 | 10-AUG-15:30 |
Electricity:Plant | 35.59 | 0.00 | 01-JAN-00:10 | 4623.70 | 11-JAN-12:50 |
WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.85 | 11-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.85 | 11-JAN-12:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
WIRED_LTG_ELECTRICITY | 8.44 | 0.00 | 01-JAN-00:10 | 917.25 | 14-MAR-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5155.94 | 0.00 | 01-JAN-00:10 | 553657.83 | 10-AUG-16:00 |
EnergyTransfer:Building | 1958.61 | 0.00 | 01-JAN-00:10 | 194998.53 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 339.48 | 0.00 | 01-JAN-00:10 | 26282.23 | 05-SEP-07:20 |
Heating:EnergyTransfer | 2.04 | 0.00 | 01-JAN-00:10 | 6048.96 | 03-JAN-07:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.04 | 0.00 | 01-JAN-00:10 | 6048.96 | 03-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1956.58 | 0.00 | 01-JAN-00:10 | 194998.53 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 339.48 | 0.00 | 01-JAN-00:10 | 26282.23 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1956.58 | 0.00 | 01-JAN-00:10 | 194998.53 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 339.48 | 0.00 | 01-JAN-00:10 | 26282.23 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.74 | 0.00 | 01-JAN-00:10 | 14418.32 | 16-AUG-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 2717.38 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 2717.38 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.63 | 0.00 | 01-JAN-00:10 | 14418.32 | 16-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 88.63 | 0.00 | 01-JAN-00:10 | 14418.32 | 16-AUG-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 55.11 | 0.00 | 01-JAN-00:10 | 7283.71 | 05-SEP-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 1495.61 | 01-JAN-13:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.22 | 0.00 | 01-JAN-00:10 | 1495.61 | 01-JAN-13:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 54.89 | 0.00 | 01-JAN-00:10 | 7283.71 | 05-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 54.89 | 0.00 | 01-JAN-00:10 | 7283.71 | 05-SEP-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.99 | 0.00 | 01-JAN-00:10 | 7446.81 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.41 | 0.00 | 01-JAN-00:10 | 1559.84 | 16-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.41 | 0.00 | 01-JAN-00:10 | 1559.84 | 16-JAN-10:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.57 | 0.00 | 01-JAN-00:10 | 7446.81 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 62.57 | 0.00 | 01-JAN-00:10 | 7446.81 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 244.97 | 0.00 | 01-JAN-00:10 | 20819.42 | 05-SEP-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 244.97 | 0.00 | 01-JAN-00:10 | 20819.42 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 244.97 | 0.00 | 01-JAN-00:10 | 20819.42 | 05-SEP-07:50 |
EnergyTransfer:Zone:CORE_TOP | 252.99 | 0.00 | 01-JAN-00:10 | 22838.72 | 05-SEP-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 252.99 | 0.00 | 01-JAN-00:10 | 22838.72 | 05-SEP-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 252.99 | 0.00 | 01-JAN-00:10 | 22838.72 | 05-SEP-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.55 | 0.00 | 01-JAN-00:10 | 9321.72 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.55 | 0.00 | 01-JAN-00:10 | 9321.72 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.55 | 0.00 | 01-JAN-00:10 | 9321.72 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 62.90 | 0.00 | 01-JAN-00:10 | 7915.96 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 158.31 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 158.31 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 62.90 | 0.00 | 01-JAN-00:10 | 7915.96 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 62.90 | 0.00 | 01-JAN-00:10 | 7915.96 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.88 | 0.00 | 01-JAN-00:10 | 11134.98 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.88 | 0.00 | 01-JAN-00:10 | 11134.98 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.88 | 0.00 | 01-JAN-00:10 | 11134.98 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.08 | 0.00 | 01-JAN-00:10 | 8130.42 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 325.94 | 20-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 325.94 | 20-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.08 | 0.00 | 01-JAN-00:10 | 8130.42 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.08 | 0.00 | 01-JAN-00:10 | 8130.42 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.33 | 0.00 | 01-JAN-00:10 | 8941.94 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.33 | 0.00 | 01-JAN-00:10 | 8941.94 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 80.33 | 0.00 | 01-JAN-00:10 | 8941.94 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.03 | 0.00 | 01-JAN-00:10 | 7525.04 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.03 | 0.00 | 01-JAN-00:10 | 7525.04 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 64.03 | 0.00 | 01-JAN-00:10 | 7525.04 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 119.03 | 0.00 | 01-JAN-00:10 | 18582.87 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 4599.90 | 22-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 4599.90 | 22-FEB-07:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.75 | 0.00 | 01-JAN-00:10 | 18582.87 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.75 | 0.00 | 01-JAN-00:10 | 18582.87 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.35 | 0.00 | 01-JAN-00:10 | 7539.25 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.35 | 0.00 | 01-JAN-00:10 | 7539.25 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 63.35 | 0.00 | 01-JAN-00:10 | 7539.25 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.29 | 0.00 | 01-JAN-00:10 | 8412.14 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.29 | 0.00 | 01-JAN-00:10 | 8412.14 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 75.29 | 0.00 | 01-JAN-00:10 | 8412.14 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.07 | 0.00 | 01-JAN-00:10 | 7469.01 | 31-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.07 | 0.00 | 01-JAN-00:10 | 7469.01 | 31-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 59.07 | 0.00 | 01-JAN-00:10 | 7469.01 | 31-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.22 | 0.00 | 01-JAN-00:10 | 10439.99 | 02-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.22 | 0.00 | 01-JAN-00:10 | 10439.99 | 02-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 91.22 | 0.00 | 01-JAN-00:10 | 10439.99 | 02-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.59 | 0.00 | 01-JAN-00:10 | 7520.04 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.59 | 0.00 | 01-JAN-00:10 | 7520.04 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.59 | 0.00 | 01-JAN-00:10 | 7520.04 | 31-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 3164.60 | 0.00 | 01-JAN-00:10 | 368265.63 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.45 | 0.00 | 01-JAN-00:10 | 6545.09 | 20-JAN-07:30 |
CoolingCoils:EnergyTransfer | 3164.15 | 0.00 | 01-JAN-00:10 | 368265.63 | 10-AUG-16:00 |
EnergyTransfer:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -339.482 | 0.000 | 0.000 | 32.646 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.515 |
CORE_MID | 0.000 | 0.000 | 0.000 | -244.973 | 0.000 | 0.000 | 32.726 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 24.894 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -252.988 | 0.000 | 0.000 | 32.810 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 32.825 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -79.547 | 0.000 | 0.000 | 6.943 | 8.712 | 24.333 | 36.658 | 0.000 | 0.993 | 10.045 | 0.000 | -7.863 | 0.000 | -0.273 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -62.900 | 0.000 | 0.000 | 4.383 | 5.484 | 15.404 | 37.058 | 0.000 | 0.659 | 5.065 | 0.000 | -4.964 | 0.000 | -0.188 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -95.883 | 0.000 | 0.000 | 6.920 | 8.553 | 24.332 | 57.951 | 0.000 | 0.981 | 5.310 | 0.000 | -7.858 | 0.000 | -0.305 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -63.080 | 0.000 | 0.000 | 4.412 | 5.491 | 15.403 | 37.693 | 0.000 | 0.660 | 4.929 | 0.000 | -5.320 | 0.000 | -0.189 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -80.328 | 0.000 | 0.000 | 6.897 | 8.683 | 24.333 | 36.364 | 0.000 | 0.535 | 12.512 | 0.000 | -8.825 | 0.000 | -0.170 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -64.035 | 0.000 | 0.000 | 4.362 | 5.471 | 15.404 | 36.853 | 0.000 | 0.353 | 7.347 | 0.000 | -5.636 | 0.000 | -0.118 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.285 | -118.748 | 0.000 | 0.000 | 6.840 | 8.538 | 24.332 | 57.498 | 0.000 | 26.322 | 8.191 | 0.000 | -8.967 | 0.000 | -4.291 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -63.347 | 0.000 | 0.000 | 4.367 | 5.476 | 15.403 | 37.497 | 0.000 | 0.351 | 6.468 | 0.000 | -6.096 | 0.000 | -0.119 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -75.292 | 0.000 | 0.000 | 6.908 | 8.712 | 24.333 | 36.713 | 0.000 | 0.829 | 6.492 | 0.000 | -8.443 | 0.000 | -0.252 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -59.070 | 0.000 | 0.000 | 3.224 | 5.484 | 15.404 | 37.105 | 0.000 | 0.551 | 2.757 | 0.000 | -5.283 | 0.000 | -0.172 | 0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -91.221 | 0.000 | 0.000 | 6.895 | 8.553 | 24.332 | 58.043 | 0.000 | 0.819 | 1.232 | 0.000 | -8.376 | 0.000 | -0.277 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -59.592 | 0.000 | 0.000 | 4.383 | 5.491 | 15.403 | 37.736 | 0.000 | 0.549 | 1.913 | 0.000 | -5.709 | 0.000 | -0.174 | -0.000 |
TOPFLOOR_PLENUM | 1.118 | -88.627 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.362 | 86.560 | 0.000 | 0.000 | 0.000 | -0.413 | -0.000 |
MIDFLOOR_PLENUM | 0.219 | -54.895 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.309 | 53.809 | 0.000 | 0.000 | 0.000 | -0.442 | 0.000 |
FIRSTFLOOR_PLENUM | 0.413 | -62.575 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.006 | 61.529 | 0.000 | 0.000 | 0.000 | -0.373 | 0.000 |
Total Facility | 1.750 | -206.097 | 0.286 | -1750.487 | 0.000 | 0.000 | 164.714 | 300.433 | 719.689 | 507.168 | 0.000 | 37.279 | 331.879 | 0.000 | -83.341 | 0.000 | -7.757 | -15.520 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-APR-04:52 | 0.00 | 0.00 | 0.00 | -43876.40 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 38022.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-APR-04:52 | 0.00 | 0.00 | 0.00 | -35181.78 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 32527.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-SEP-04:02 | 0.00 | 0.00 | 0.00 | -38594.88 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 35941.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 20-AUG-14:32 | 0.00 | 0.00 | 0.00 | -16191.95 | 0.00 | 0.00 | 24.84 | 36.00 | 478.42 | 3499.04 | 0.00 | 270.11 | 11883.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 07-MAY-09:52 | 0.00 | 0.00 | 0.00 | -12979.76 | 0.00 | 0.00 | 15.25 | 22.79 | 302.86 | 5473.41 | 0.00 | 49.14 | 7116.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-13:32 | 0.00 | 0.00 | 0.00 | -18659.86 | 0.00 | 0.00 | 22.64 | 36.00 | 478.41 | 7906.76 | 0.00 | 110.28 | 10105.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 20-AUG-14:32 | 0.00 | 0.00 | 0.00 | -14894.43 | 0.00 | 0.00 | 14.02 | 22.79 | 302.86 | 4972.00 | 0.00 | 173.79 | 9408.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-15:41 | 0.00 | 0.00 | 0.00 | -14218.95 | 0.00 | 0.00 | 25.64 | 36.00 | 478.42 | 3325.07 | 0.00 | 135.84 | 10217.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-11:22 | 0.00 | 0.00 | 0.00 | -12091.88 | 0.00 | 0.00 | 14.69 | 22.79 | 302.86 | 3983.49 | 0.00 | 110.03 | 7658.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18582.50 | 0.00 | 0.00 | 224.54 | 647.98 | 1275.77 | 5935.39 | 0.00 | 18593.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8094.54 |
PERIMETER_BOT_ZN_4 | 04-SEP-15:41 | 0.00 | 0.00 | 0.00 | -13311.33 | 0.00 | 0.00 | 13.75 | 22.79 | 302.86 | 5770.90 | 0.00 | 84.54 | 7116.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -13871.91 | 0.00 | 0.00 | 26.02 | 36.00 | 478.42 | 2963.70 | 0.00 | 181.79 | 10185.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-09:52 | 0.00 | 0.00 | 0.00 | -12297.44 | 0.00 | 0.00 | 14.69 | 22.79 | 302.86 | 5091.41 | 0.00 | 98.46 | 6767.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:22 | 0.00 | 0.00 | 0.00 | -16323.36 | 0.00 | 0.00 | 23.58 | 36.00 | 478.41 | 8196.39 | 0.00 | 80.49 | 7508.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -13575.01 | 0.00 | 0.00 | 13.96 | 22.79 | 302.86 | 4262.56 | 0.00 | 113.15 | 8859.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:30 | 0.00 | -14418.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.90 | 14295.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -7310.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 7292.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:08 | 0.00 | -9365.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 | 9290.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:02 | 0.00 | 8466.77 | 0.00 | -236357.84 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 466.22 | 0.00 | 208.76 | 210573.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 20-JAN-07:03 | 0.00 | 0.00 | 633.23 | 0.00 | 0.00 | 0.00 | 118.56 | 286.67 | 403.81 | 82.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.57 | -1515.46 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 20-JAN-07:03 | 0.00 | 0.00 | 1303.75 | 0.00 | 0.00 | 0.00 | 119.02 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -924.68 | 0.00 | -9.56 | -1178.99 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:08 | 0.00 | 0.00 | 4607.72 | 0.00 | 0.00 | 0.00 | 171.75 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 3807.88 | 0.00 | -1153.15 | 0.00 | -8524.91 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 08-MAY-04:02 | 5190.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5192.60 |
MIDFLOOR_PLENUM | 25-AUG-04:02 | 3326.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3368.63 |
FIRSTFLOOR_PLENUM | 28-SEP-04:02 | 4803.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4828.39 |
Total Facility | 15-SEP-04:02 | -208451.49 | 219141.51 | 0.00 | -219141.51 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 66.66 | 0.00 | 315.70 | 191629.49 | 0.00 | -203.25 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7638 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3898 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3460 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9164 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9744 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.8108 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8819 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4131 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6730 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4007 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9872 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5020 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7268 | 2.7268 | 0.7962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2689 | 2.2689 | 0.7782 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5175 | 2.5175 | 0.8106 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9091 | 0.9091 | 0.1818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7211 | 0.7211 | 0.1442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0107 | 1.0107 | 0.2021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8160 | 0.8160 | 0.1632 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7911 | 0.7911 | 0.1677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6613 | 0.6613 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8856 | 0.8856 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6991 | 0.6991 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7864 | 0.7864 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6764 | 0.6764 | 0.1353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8863 | 0.8863 | 0.1773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7280 | 0.7280 | 0.1456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7638 | 5.3898 | 5.7638 | 1.4131 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3460 | 4.9164 | 5.3460 | 1.4007 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9744 | 5.8108 | 5.9744 | 1.5020 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3634 | 1.3634 | 0.7962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1345 | 1.1345 | 0.7782 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2587 | 1.2587 | 0.8106 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4546 | 0.4546 | 0.1818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3605 | 0.3605 | 0.1442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5054 | 0.5054 | 0.2021 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4080 | 0.4080 | 0.1632 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3955 | 0.3955 | 0.1677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3307 | 0.3307 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4428 | 0.4428 | 0.1771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3495 | 0.3495 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3932 | 0.3932 | 0.1644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3382 | 0.3382 | 0.1353 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4432 | 0.4432 | 0.1773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3640 | 0.3640 | 0.1456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8819 | 1.4131 | 1.4131 | 1.4131 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6730 | 1.4007 | 1.4007 | 1.4007 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9872 | 1.5020 | 1.5020 | 1.5020 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 528.00 |
Number of hours not met | 528.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.45 | 6545.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 814.70 | 116549.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.43 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.55 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 173.37 | 26454.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 35.45 | 4616.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 2121.70 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2121.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.30 |
Space Heating | 0.09 |
Space Cooling | 163.52 |
Fans (All) | 34.80 |
Service Water Heating | 7.11 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 425.86 |
Subtotal | 425.86 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.16 |
Space Heating | 0.02 |
Space Cooling | 38.40 |
Fans (All) | 8.17 |
Service Water Heating | 1.67 |
Receptacle Equipment | 33.92 |
Miscellaneous | 3.66 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7806.00 | 954.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8728.83 | 31.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7916.00 | 844.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7847.50 | 912.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7833.17 | 926.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7816.17 | 943.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8102.00 | 658.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7873.67 | 886.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7711.17 | 1048.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7784.50 | 975.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7893.83 | 866.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7805.50 | 954.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7767.83 | 992.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7720.00 | 1040.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8091.33 | 668.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8448.33 | 311.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8504.33 | 255.67 | 0.00 | 0.00 | 0.00 |
Min | 7711.17 | 31.17 | 0.00 | 0.00 | 0.00 |
Max | 8728.83 | 1048.83 | 0.00 | 0.00 | 0.00 |
Average | 8020.73 | 739.27 | 0.00 | 0.00 | 0.00 |
Sum | 144373.17 | 13306.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127995.33 | 308.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128295.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24493.33 | 415.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.67 | 415.67 | 0.00 | 0.00 | 0.00 |
Average | 34102.28 | 41.06 | 0.00 | 0.00 | 0.00 |
Sum | 613841.00 | 739.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6748.83 | 2011.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7324.17 | 1435.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7400.17 | 1359.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6642.00 | 2118.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6615.33 | 2144.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6570.83 | 2189.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6663.50 | 2096.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6585.33 | 2174.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6475.50 | 2284.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5708.00 | 3052.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6480.33 | 2279.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6509.17 | 2250.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6471.50 | 2288.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6395.83 | 2364.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6475.33 | 2284.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4731.17 | 4028.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5700.83 | 3059.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6154.67 | 2605.33 | 0.00 | 0.00 | 0.00 |
Min | 4731.17 | 1359.83 | 0.00 | 0.00 | 0.00 |
Max | 7400.17 | 4028.83 | 0.00 | 0.00 | 0.00 |
Average | 6425.14 | 2334.86 | 0.00 | 0.00 | 0.00 |
Sum | 115652.50 | 42027.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127206.33 | 1097.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127648.00 | 656.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127586.33 | 717.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24835.67 | 73.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24842.83 | 66.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24840.00 | 69.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21531.50 | 3377.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24826.50 | 82.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24830.67 | 78.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127648.00 | 3377.50 | 0.00 | 0.00 | 0.00 |
Average | 33797.88 | 345.45 | 0.00 | 0.00 | 0.00 |
Sum | 608361.83 | 6218.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238382E+11 | 39223.59 | 02-JAN-07:02 | 13.00 | 10.98 | 0.199674E+10 | 2606.69 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.220216E+11 | 41902.81 | 06-FEB-06:12 | 21.77 | 18.83 | 0.181184E+10 | 2606.76 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.266993E+11 | 43130.99 | 28-MAR-04:02 | 26.08 | 14.62 | 0.216290E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.261812E+11 | 43883.68 | 25-APR-04:52 | 24.00 | 12.96 | 0.192041E+10 | 2606.86 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.307949E+11 | 43743.56 | 04-MAY-05:03 | 24.00 | 18.14 | 0.207924E+10 | 2606.77 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.310462E+11 | 42637.57 | 07-JUN-04:02 | 24.83 | 21.13 | 0.207233E+10 | 2606.72 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.319345E+11 | 41235.05 | 29-JUL-04:03 | 29.42 | 25.46 | 0.192481E+10 | 2606.84 | 03-JUL-09:09 | 29.42 | 25.46 |
August | 0.340557E+11 | 37151.07 | 05-AUG-06:03 | 35.07 | 23.19 | 0.215974E+10 | 2606.63 | 25-AUG-13:09 | 36.58 | 27.69 |
September | 0.307285E+11 | 41999.41 | 30-SEP-04:03 | 24.52 | 21.72 | 0.191930E+10 | 2606.64 | 26-SEP-09:30 | 24.52 | 21.72 |
October | 0.303711E+11 | 42370.60 | 28-OCT-04:03 | 24.00 | 21.39 | 0.199648E+10 | 2606.61 | 27-OCT-13:09 | 24.00 | 21.39 |
November | 0.273975E+11 | 42543.71 | 25-NOV-05:03 | 25.00 | 18.54 | 0.197770E+10 | 2606.66 | 22-NOV-10:09 | 25.00 | 18.54 |
December | 0.244102E+11 | 41702.01 | 11-DEC-06:12 | 21.80 | 19.16 | 0.192703E+10 | 2606.68 | 08-DEC-10:20 | 21.80 | 19.16 |
Annual Sum or Average | 0.339479E+12 | 0.239485E+11 | ||||||||
Minimum of Months | 0.220216E+11 | 37151.07 | 13.00 | 10.98 | 0.181184E+10 | 2606.61 | 21.80 | 17.69 | ||
Maximum of Months | 0.340557E+11 | 43883.68 | 35.07 | 25.46 | 0.216290E+10 | 2606.86 | 36.58 | 27.69 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229943E+10 | 5387.03 | 31-JAN-14:10 | 23.00 | 16.33 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 16.33 |
February | 0.300648E+10 | 8183.52 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.484936E+10 | 11067.72 | 27-MAR-13:40 | 35.33 | 19.53 | 0.00 | 0.00 | 01-MAR-00:10 | 35.33 | 19.53 |
April | 0.644407E+10 | 12199.33 | 28-APR-12:40 | 38.47 | 22.15 | 0.00 | 0.00 | 01-APR-00:10 | 38.47 | 22.15 |
May | 0.101409E+11 | 12660.57 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.110123E+11 | 13248.84 | 12-JUN-13:10 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.121963E+11 | 14355.88 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.128389E+11 | 14418.32 | 16-AUG-13:30 | 44.10 | 25.63 | 0.00 | 0.00 | 01-AUG-00:10 | 44.10 | 25.63 |
September | 0.992754E+10 | 13354.44 | 05-SEP-14:00 | 40.00 | 25.05 | 0.00 | 0.00 | 01-SEP-00:10 | 40.00 | 25.05 |
October | 0.789688E+10 | 11332.70 | 04-OCT-14:00 | 36.00 | 20.88 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 20.88 |
November | 0.513784E+10 | 9383.03 | 06-NOV-14:10 | 32.83 | 20.61 | 0.00 | 0.00 | 01-NOV-00:10 | 32.83 | 20.61 |
December | 0.287681E+10 | 6913.26 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.886268E+11 | 0.00 | ||||||||
Minimum of Months | 0.229943E+10 | 5387.03 | 23.00 | 16.33 | 0.00 | 0.00 | 23.00 | 16.33 | ||
Maximum of Months | 0.128389E+11 | 14418.32 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149725E+10 | 2273.86 | 31-JAN-15:40 | 22.73 | 16.59 | 0.00 | 0.00 | 01-JAN-00:10 | 22.73 | 16.59 |
February | 0.187632E+10 | 4074.38 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.301816E+10 | 5385.62 | 27-MAR-15:20 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.387602E+10 | 5494.41 | 24-APR-14:30 | 35.00 | 18.42 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 18.42 |
May | 0.611651E+10 | 6443.25 | 30-MAY-15:20 | 38.83 | 25.75 | 0.00 | 0.00 | 01-MAY-00:10 | 38.83 | 25.75 |
June | 0.656769E+10 | 6738.57 | 19-JUN-06:15 | 28.20 | 25.08 | 0.00 | 0.00 | 01-JUN-00:10 | 28.20 | 25.08 |
July | 0.703969E+10 | 7311.31 | 05-JUL-06:15 | 30.13 | 28.32 | 0.00 | 0.00 | 01-JUL-00:10 | 30.13 | 28.32 |
August | 0.754904E+10 | 6974.28 | 21-AUG-06:15 | 30.00 | 28.39 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 28.39 |
September | 0.623286E+10 | 7283.71 | 05-SEP-15:30 | 39.05 | 25.34 | 0.00 | 0.00 | 01-SEP-00:10 | 39.05 | 25.34 |
October | 0.537624E+10 | 6309.79 | 10-OCT-15:10 | 34.85 | 19.93 | 0.00 | 0.00 | 01-OCT-00:10 | 34.85 | 19.93 |
November | 0.370651E+10 | 5373.72 | 06-NOV-15:10 | 31.90 | 21.82 | 0.00 | 0.00 | 01-NOV-00:10 | 31.90 | 21.82 |
December | 0.203840E+10 | 3465.84 | 04-DEC-15:10 | 26.87 | 21.39 | 0.00 | 0.00 | 01-DEC-00:10 | 26.87 | 21.39 |
Annual Sum or Average | 0.548947E+11 | 0.00 | ||||||||
Minimum of Months | 0.149725E+10 | 2273.86 | 22.73 | 16.59 | 0.00 | 0.00 | 22.73 | 16.59 | ||
Maximum of Months | 0.754904E+10 | 7311.31 | 39.05 | 28.39 | 0.00 | 0.00 | 39.05 | 28.39 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249459E+10 | 4043.26 | 02-JAN-07:07 | 13.00 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.98 |
February | 0.271204E+10 | 4936.14 | 06-FEB-15:50 | 31.58 | 17.52 | 0.00 | 0.00 | 01-FEB-00:10 | 31.58 | 17.52 |
March | 0.383289E+10 | 6880.68 | 27-MAR-12:08 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.444526E+10 | 6953.68 | 24-APR-12:06 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.647166E+10 | 9008.53 | 22-MAY-12:06 | 38.02 | 22.04 | 0.00 | 0.00 | 01-MAY-00:10 | 38.02 | 22.04 |
June | 0.688557E+10 | 8643.69 | 05-JUN-12:06 | 37.18 | 23.51 | 0.00 | 0.00 | 01-JUN-00:10 | 37.18 | 23.51 |
July | 0.721791E+10 | 9366.29 | 31-JUL-12:08 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.777542E+10 | 8867.79 | 07-AUG-12:09 | 36.98 | 28.67 | 0.00 | 0.00 | 01-AUG-00:10 | 36.98 | 28.67 |
September | 0.670514E+10 | 8728.86 | 25-SEP-12:09 | 38.83 | 22.60 | 0.00 | 0.00 | 01-SEP-00:10 | 38.83 | 22.60 |
October | 0.612956E+10 | 6617.36 | 10-OCT-06:10 | 25.97 | 23.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 23.91 |
November | 0.479964E+10 | 5897.87 | 13-NOV-16:20 | 29.80 | 21.47 | 0.00 | 0.00 | 01-NOV-00:10 | 29.80 | 21.47 |
December | 0.310516E+10 | 4871.77 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.625749E+11 | 0.00 | ||||||||
Minimum of Months | 0.249459E+10 | 4043.26 | 13.00 | 10.98 | 0.00 | 0.00 | 13.00 | 10.98 | ||
Maximum of Months | 0.777542E+10 | 9366.29 | 40.98 | 28.67 | 0.00 | 0.00 | 40.98 | 28.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148852E+11 | 15381.76 | 30-JAN-15:00 | 22.00 | 20.56 | 0.197949E+10 | 2606.68 | 17-JAN-10:09 | 22.00 | 20.56 |
February | 0.143794E+11 | 30674.96 | 06-FEB-06:12 | 21.77 | 18.83 | 0.179977E+10 | 2606.73 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.182621E+11 | 34589.29 | 28-MAR-04:02 | 26.08 | 14.62 | 0.215429E+10 | 2606.79 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.188699E+11 | 35186.90 | 25-APR-04:52 | 24.00 | 12.96 | 0.191489E+10 | 2606.82 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.234159E+11 | 34778.05 | 16-MAY-04:02 | 25.00 | 22.44 | 0.207576E+10 | 2606.76 | 08-MAY-13:30 | 25.00 | 22.44 |
June | 0.238876E+11 | 34397.43 | 07-JUN-04:02 | 24.83 | 21.13 | 0.206908E+10 | 2606.76 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.250550E+11 | 31425.24 | 13-JUL-04:02 | 30.58 | 20.96 | 0.192175E+10 | 2606.83 | 03-JUL-09:09 | 30.58 | 20.96 |
August | 0.264169E+11 | 31405.33 | 07-AUG-06:03 | 31.98 | 22.90 | 0.215716E+10 | 2606.58 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.230073E+11 | 34110.27 | 29-SEP-04:02 | 26.00 | 24.56 | 0.191671E+10 | 2606.64 | 26-SEP-09:00 | 26.00 | 24.56 |
October | 0.221095E+11 | 35023.14 | 31-OCT-04:02 | 24.33 | 22.73 | 0.199308E+10 | 2606.62 | 20-OCT-09:39 | 24.33 | 22.73 |
November | 0.188872E+11 | 34472.44 | 13-NOV-06:12 | 20.83 | 17.71 | 0.197225E+10 | 2606.69 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.157954E+11 | 30697.59 | 11-DEC-06:12 | 21.80 | 19.16 | 0.191407E+10 | 2606.66 | 08-DEC-10:09 | 21.80 | 19.16 |
Annual Sum or Average | 0.244971E+12 | 0.238683E+11 | ||||||||
Minimum of Months | 0.143794E+11 | 15381.76 | 20.83 | 12.96 | 0.179977E+10 | 2606.58 | 21.80 | 18.27 | ||
Maximum of Months | 0.264169E+11 | 35186.90 | 31.98 | 24.56 | 0.215716E+10 | 2606.83 | 36.42 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134783E+11 | 15105.67 | 31-JAN-15:50 | 22.67 | 16.56 | 0.194931E+10 | 2606.65 | 24-JAN-10:00 | 22.67 | 16.56 |
February | 0.136135E+11 | 18053.13 | 06-FEB-15:50 | 31.58 | 17.52 | 0.178151E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.179565E+11 | 36822.11 | 28-MAR-05:03 | 25.67 | 14.74 | 0.214331E+10 | 2606.80 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.193458E+11 | 36872.27 | 29-APR-05:03 | 25.00 | 16.37 | 0.191133E+10 | 2606.82 | 25-APR-09:09 | 25.00 | 16.37 |
May | 0.251754E+11 | 38397.50 | 09-MAY-04:02 | 26.08 | 19.67 | 0.207631E+10 | 2606.77 | 08-MAY-13:39 | 26.08 | 19.67 |
June | 0.260373E+11 | 38512.10 | 07-JUN-04:02 | 24.83 | 21.13 | 0.206973E+10 | 2606.80 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.279303E+11 | 36657.12 | 03-JUL-04:02 | 29.00 | 16.97 | 0.192300E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.292771E+11 | 35839.56 | 15-AUG-04:02 | 29.75 | 23.27 | 0.215818E+10 | 2606.57 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.246076E+11 | 38601.50 | 25-SEP-04:02 | 24.17 | 23.10 | 0.191728E+10 | 2606.65 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.225695E+11 | 38478.36 | 23-OCT-04:03 | 25.42 | 23.19 | 0.199274E+10 | 2606.69 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.183303E+11 | 37223.93 | 03-NOV-05:03 | 23.83 | 22.46 | 0.196738E+10 | 2606.68 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.146650E+11 | 16840.28 | 04-DEC-15:00 | 27.00 | 21.53 | 0.189418E+10 | 2606.66 | 01-DEC-14:09 | 27.00 | 21.53 |
Annual Sum or Average | 0.252987E+12 | 0.237843E+11 | ||||||||
Minimum of Months | 0.134783E+11 | 15105.67 | 22.67 | 14.74 | 0.178151E+10 | 2606.57 | 22.67 | 16.37 | ||
Maximum of Months | 0.292771E+11 | 38601.50 | 31.58 | 23.27 | 0.215818E+10 | 2606.83 | 36.90 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283515E+10 | 4101.23 | 23-JAN-14:10 | 27.50 | 16.66 | 0.397948E+09 | 549.50 | 23-JAN-14:00 | 25.00 | 16.89 |
February | 0.313751E+10 | 5840.75 | 06-FEB-15:00 | 32.50 | 17.28 | 0.368406E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.466726E+10 | 7965.13 | 26-MAR-14:53 | 32.60 | 18.60 | 0.447635E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.577922E+10 | 13659.86 | 30-APR-13:32 | 35.03 | 22.43 | 0.402341E+09 | 549.54 | 28-APR-13:09 | 35.03 | 22.43 |
May | 0.876940E+10 | 14359.69 | 28-MAY-13:23 | 34.85 | 23.67 | 0.438717E+09 | 549.53 | 04-MAY-13:00 | 34.85 | 23.67 |
June | 0.959265E+10 | 13928.37 | 11-JUN-15:22 | 36.70 | 27.29 | 0.437507E+09 | 549.53 | 02-JUN-13:09 | 36.70 | 27.29 |
July | 0.104813E+11 | 15951.52 | 23-JUL-13:22 | 38.10 | 26.30 | 0.407198E+09 | 549.55 | 03-JUL-09:09 | 38.10 | 26.30 |
August | 0.108685E+11 | 16197.39 | 20-AUG-14:32 | 38.17 | 26.36 | 0.456464E+09 | 549.49 | 04-AUG-13:00 | 38.17 | 26.36 |
September | 0.841624E+10 | 15589.79 | 04-SEP-15:22 | 40.85 | 24.13 | 0.405312E+09 | 549.50 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.688869E+10 | 13305.15 | 10-OCT-04:02 | 27.00 | 23.50 | 0.420711E+09 | 549.51 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.485025E+10 | 6277.36 | 06-NOV-14:10 | 32.83 | 20.61 | 0.413531E+09 | 549.50 | 09-NOV-10:20 | 30.27 | 21.02 |
December | 0.326115E+10 | 4629.33 | 11-DEC-14:10 | 26.77 | 18.23 | 0.392111E+09 | 549.50 | 01-DEC-14:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.795473E+11 | 0.498788E+10 | ||||||||
Minimum of Months | 0.283515E+10 | 4101.23 | 26.77 | 16.66 | 0.368406E+09 | 549.49 | 25.00 | 16.89 | ||
Maximum of Months | 0.108685E+11 | 16197.39 | 40.85 | 27.29 | 0.456464E+09 | 549.55 | 38.17 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234572E+10 | 3048.26 | 24-JAN-11:00 | 24.00 | 17.69 | 0.256845E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.258411E+10 | 4093.29 | 05-FEB-10:53 | 29.00 | 18.72 | 0.236038E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.378327E+10 | 7585.08 | 26-MAR-14:53 | 32.60 | 18.60 | 0.284387E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.477539E+10 | 12174.15 | 30-APR-10:53 | 34.00 | 21.75 | 0.255040E+09 | 347.91 | 25-APR-09:09 | 34.00 | 21.75 |
May | 0.697071E+10 | 12978.36 | 07-MAY-09:52 | 36.50 | 17.98 | 0.277823E+09 | 347.90 | 04-MAY-13:00 | 36.50 | 17.98 |
June | 0.732683E+10 | 12065.41 | 11-JUN-10:02 | 38.17 | 26.68 | 0.276971E+09 | 347.90 | 02-JUN-13:09 | 38.17 | 26.68 |
July | 0.794773E+10 | 12854.88 | 30-JUL-09:52 | 42.40 | 21.65 | 0.257820E+09 | 348.02 | 21-JUL-09:39 | 42.40 | 21.65 |
August | 0.841443E+10 | 12921.57 | 27-AUG-09:42 | 36.25 | 26.52 | 0.288990E+09 | 347.96 | 02-AUG-09:30 | 36.25 | 26.52 |
September | 0.667137E+10 | 12427.41 | 04-SEP-10:02 | 38.00 | 23.07 | 0.256654E+09 | 347.88 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.554170E+10 | 11956.92 | 29-OCT-13:32 | 34.37 | 18.20 | 0.266520E+09 | 347.88 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.392108E+10 | 7170.97 | 05-NOV-11:13 | 32.87 | 18.22 | 0.262449E+09 | 347.88 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.261793E+10 | 3481.36 | 04-DEC-11:00 | 26.00 | 20.51 | 0.250640E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.629003E+11 | 0.317018E+10 | ||||||||
Minimum of Months | 0.234572E+10 | 3048.26 | 24.00 | 17.69 | 0.236038E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.841443E+10 | 12978.36 | 42.40 | 26.68 | 0.288990E+09 | 348.02 | 42.40 | 26.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486937E+10 | 8828.08 | 22-JAN-15:03 | 26.00 | 16.78 | 0.407754E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.501289E+10 | 17628.57 | 05-FEB-13:32 | 31.43 | 19.44 | 0.372847E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.633316E+10 | 17327.35 | 26-MAR-14:53 | 32.60 | 18.60 | 0.448637E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.661900E+10 | 17227.05 | 30-APR-12:53 | 37.10 | 21.04 | 0.402167E+09 | 549.55 | 28-APR-13:09 | 37.10 | 21.04 |
May | 0.886934E+10 | 15795.90 | 28-MAY-13:23 | 34.85 | 23.67 | 0.438520E+09 | 549.53 | 04-MAY-13:00 | 34.85 | 23.67 |
June | 0.929181E+10 | 14268.49 | 26-JUN-04:02 | 29.33 | 25.25 | 0.437313E+09 | 549.53 | 02-JUN-13:09 | 29.33 | 25.25 |
July | 0.104626E+11 | 17651.24 | 23-JUL-13:22 | 38.10 | 26.30 | 0.407042E+09 | 549.54 | 03-JUL-09:09 | 38.10 | 26.30 |
August | 0.115359E+11 | 18201.94 | 20-AUG-14:32 | 38.17 | 26.36 | 0.456420E+09 | 549.49 | 04-AUG-13:00 | 38.17 | 26.36 |
September | 0.100912E+11 | 17634.22 | 04-SEP-15:22 | 40.85 | 24.13 | 0.405440E+09 | 549.74 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.957977E+10 | 18665.42 | 29-OCT-13:32 | 34.37 | 18.20 | 0.421246E+09 | 549.80 | 10-OCT-13:00 | 34.37 | 18.20 |
November | 0.768593E+10 | 17641.71 | 19-NOV-12:43 | 30.92 | 16.54 | 0.415306E+09 | 549.83 | 13-NOV-14:09 | 30.92 | 16.54 |
December | 0.553263E+10 | 17663.72 | 03-DEC-13:23 | 28.40 | 19.50 | 0.398304E+09 | 549.51 | 01-DEC-14:09 | 28.40 | 19.50 |
Annual Sum or Average | 0.958837E+11 | 0.501100E+10 | ||||||||
Minimum of Months | 0.486937E+10 | 8828.08 | 26.00 | 16.54 | 0.372847E+09 | 549.49 | 24.00 | 16.54 | ||
Maximum of Months | 0.115359E+11 | 18665.42 | 40.85 | 26.36 | 0.456420E+09 | 549.83 | 38.17 | 26.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249978E+10 | 3744.00 | 31-JAN-16:20 | 22.73 | 16.79 | 0.247424E+09 | 347.85 | 23-JAN-14:00 | 22.73 | 16.79 |
February | 0.274279E+10 | 6227.55 | 05-FEB-14:53 | 32.00 | 19.39 | 0.230041E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.396794E+10 | 11968.87 | 26-MAR-14:53 | 32.60 | 18.60 | 0.280843E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.467930E+10 | 12365.01 | 30-APR-14:13 | 33.00 | 24.33 | 0.253590E+09 | 347.88 | 28-APR-13:09 | 33.00 | 24.33 |
May | 0.678243E+10 | 13993.86 | 21-MAY-16:32 | 37.17 | 23.21 | 0.277503E+09 | 347.88 | 04-MAY-13:00 | 37.17 | 23.21 |
June | 0.726662E+10 | 13402.14 | 18-JUN-16:02 | 35.98 | 27.42 | 0.276840E+09 | 347.87 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.791052E+10 | 14326.69 | 30-JUL-14:32 | 42.00 | 26.25 | 0.257638E+09 | 347.88 | 03-JUL-09:09 | 42.00 | 26.25 |
August | 0.833351E+10 | 14901.39 | 20-AUG-14:32 | 38.17 | 26.36 | 0.288865E+09 | 347.85 | 04-AUG-13:00 | 38.17 | 26.36 |
September | 0.661651E+10 | 14430.90 | 04-SEP-16:02 | 40.58 | 23.84 | 0.256493E+09 | 347.85 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.549211E+10 | 13970.55 | 29-OCT-15:32 | 32.00 | 19.85 | 0.265967E+09 | 347.86 | 30-OCT-09:30 | 29.25 | 20.46 |
November | 0.397817E+10 | 10587.30 | 12-NOV-15:32 | 29.07 | 17.65 | 0.260529E+09 | 347.86 | 28-NOV-10:00 | 26.00 | 20.50 |
December | 0.281038E+10 | 4436.22 | 06-DEC-15:30 | 26.85 | 20.67 | 0.244587E+09 | 347.85 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.630801E+11 | 0.314032E+10 | ||||||||
Minimum of Months | 0.249978E+10 | 3744.00 | 22.73 | 16.79 | 0.230041E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.833351E+10 | 14901.39 | 42.00 | 27.42 | 0.288865E+09 | 347.88 | 42.00 | 27.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326983E+10 | 4200.29 | 23-JAN-14:10 | 27.50 | 16.66 | 0.414846E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.325886E+10 | 5320.26 | 06-FEB-15:00 | 32.50 | 17.28 | 0.377536E+09 | 549.51 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.438716E+10 | 6159.70 | 27-MAR-13:40 | 35.33 | 19.53 | 0.452409E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.516435E+10 | 6511.08 | 28-APR-12:30 | 39.35 | 21.60 | 0.403387E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.793254E+10 | 11084.39 | 12-MAY-04:02 | 28.67 | 19.72 | 0.438558E+09 | 549.53 | 04-MAY-13:00 | 28.67 | 19.72 |
June | 0.889799E+10 | 11198.95 | 16-JUN-04:02 | 28.83 | 20.58 | 0.437458E+09 | 549.51 | 02-JUN-13:09 | 28.83 | 20.58 |
July | 0.994020E+10 | 13979.62 | 30-JUL-15:22 | 39.35 | 29.13 | 0.407066E+09 | 549.55 | 03-JUL-09:09 | 39.35 | 29.13 |
August | 0.108904E+11 | 13787.79 | 20-AUG-14:32 | 38.17 | 26.36 | 0.456390E+09 | 549.50 | 04-AUG-13:00 | 38.17 | 26.36 |
September | 0.889604E+10 | 14224.22 | 04-SEP-15:41 | 40.75 | 24.06 | 0.405408E+09 | 549.50 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.783453E+10 | 12599.22 | 08-OCT-14:32 | 32.97 | 26.20 | 0.421278E+09 | 549.49 | 27-OCT-13:09 | 32.00 | 22.23 |
November | 0.589666E+10 | 8697.24 | 13-NOV-07:03 | 20.75 | 17.82 | 0.416247E+09 | 549.50 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.395932E+10 | 5813.72 | 11-DEC-07:03 | 21.50 | 18.56 | 0.403389E+09 | 549.50 | 08-DEC-10:09 | 21.50 | 18.56 |
Annual Sum or Average | 0.803278E+11 | 0.503397E+10 | ||||||||
Minimum of Months | 0.325886E+10 | 4200.29 | 20.75 | 16.66 | 0.377536E+09 | 549.49 | 21.50 | 16.66 | ||
Maximum of Months | 0.108904E+11 | 14224.22 | 40.75 | 29.13 | 0.456390E+09 | 549.55 | 39.35 | 29.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275449E+10 | 3402.00 | 17-JAN-11:10 | 24.17 | 16.24 | 0.263862E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.272632E+10 | 3863.22 | 06-FEB-14:10 | 32.08 | 17.23 | 0.239773E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.361568E+10 | 5724.81 | 27-MAR-10:50 | 37.50 | 18.71 | 0.286761E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.436699E+10 | 10043.13 | 30-APR-11:02 | 34.50 | 21.63 | 0.255716E+09 | 347.91 | 28-APR-13:09 | 34.50 | 21.63 |
May | 0.642633E+10 | 11337.10 | 21-MAY-11:32 | 38.20 | 22.36 | 0.277829E+09 | 348.02 | 22-MAY-09:00 | 36.70 | 22.71 |
June | 0.688148E+10 | 9876.29 | 25-JUN-09:23 | 32.15 | 27.01 | 0.277013E+09 | 347.89 | 27-JUN-13:09 | 38.33 | 27.70 |
July | 0.761378E+10 | 12094.28 | 30-JUL-11:22 | 44.00 | 23.16 | 0.257800E+09 | 347.91 | 03-JUL-09:09 | 44.00 | 23.16 |
August | 0.848168E+10 | 11599.88 | 20-AUG-09:12 | 35.60 | 25.67 | 0.289005E+09 | 347.88 | 04-AUG-13:00 | 35.60 | 25.67 |
September | 0.705710E+10 | 12056.39 | 04-SEP-10:22 | 38.00 | 23.07 | 0.256796E+09 | 347.88 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.626177E+10 | 11227.32 | 08-OCT-11:52 | 34.00 | 27.29 | 0.266917E+09 | 347.87 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.469253E+10 | 7812.73 | 05-NOV-11:13 | 32.87 | 18.22 | 0.263810E+09 | 347.88 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.315685E+10 | 4069.71 | 04-DEC-10:40 | 25.47 | 20.60 | 0.255718E+09 | 347.88 | 08-DEC-10:20 | 23.20 | 18.74 |
Annual Sum or Average | 0.640350E+11 | 0.319100E+10 | ||||||||
Minimum of Months | 0.272632E+10 | 3402.00 | 24.17 | 16.24 | 0.239773E+09 | 347.87 | 23.20 | 16.99 | ||
Maximum of Months | 0.848168E+10 | 12094.28 | 44.00 | 27.29 | 0.289005E+09 | 348.02 | 44.00 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488407E+10 | 11097.32 | 23-JAN-13:00 | 27.40 | 16.52 | 0.412040E+09 | 549.52 | 23-JAN-14:30 | 26.50 | 16.81 |
February | 0.504307E+10 | 13257.41 | 07-FEB-13:00 | 31.00 | 20.84 | 0.375957E+09 | 583.63 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.661451E+10 | 15510.25 | 27-MAR-12:00 | 37.30 | 19.38 | 0.450577E+09 | 700.34 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.738957E+10 | 16880.81 | 28-APR-12:00 | 42.00 | 19.18 | 0.404462E+09 | 776.58 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.109652E+11 | 16469.50 | 09-MAY-12:00 | 41.00 | 19.42 | 0.445670E+09 | 751.94 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.120226E+11 | 17349.44 | 12-JUN-12:00 | 43.00 | 24.56 | 0.446818E+09 | 792.90 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.134711E+11 | 18267.35 | 21-JUL-12:00 | 46.00 | 22.01 | 0.417665E+09 | 850.25 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.156797E+11 | 18582.87 | 16-AUG-12:00 | 46.00 | 25.38 | 0.471183E+09 | 863.13 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.134996E+11 | 17195.68 | 05-SEP-12:00 | 41.00 | 24.24 | 0.416454E+09 | 784.79 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.128136E+11 | 16024.98 | 04-OCT-12:00 | 38.00 | 19.81 | 0.429415E+09 | 725.21 | 04-OCT-12:09 | 37.77 | 20.04 |
November | 0.100600E+11 | 15644.59 | 19-NOV-13:02 | 31.00 | 16.80 | 0.418960E+09 | 639.29 | 06-NOV-13:09 | 31.00 | 16.80 |
December | 0.630614E+10 | 15600.91 | 25-DEC-13:53 | 27.00 | 18.66 | 0.401752E+09 | 558.93 | 04-DEC-13:09 | 27.00 | 18.66 |
Annual Sum or Average | 0.118749E+12 | 0.509095E+10 | ||||||||
Minimum of Months | 0.488407E+10 | 11097.32 | 27.00 | 16.52 | 0.375957E+09 | 549.52 | 26.50 | 16.80 | ||
Maximum of Months | 0.156797E+11 | 18582.87 | 46.00 | 25.38 | 0.471183E+09 | 863.13 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273000E+10 | 3691.87 | 31-JAN-16:30 | 22.80 | 16.92 | 0.261797E+09 | 347.86 | 17-JAN-10:09 | 22.80 | 16.92 |
February | 0.274692E+10 | 4955.78 | 06-FEB-15:30 | 31.95 | 17.43 | 0.238505E+09 | 347.86 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.371617E+10 | 6975.62 | 26-MAR-16:02 | 31.70 | 18.58 | 0.286181E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.422128E+10 | 9783.51 | 30-APR-16:23 | 31.25 | 25.60 | 0.255391E+09 | 347.88 | 28-APR-13:09 | 31.25 | 25.60 |
May | 0.621473E+10 | 11855.40 | 07-MAY-14:43 | 37.00 | 20.10 | 0.277694E+09 | 347.88 | 04-MAY-13:00 | 37.00 | 20.10 |
June | 0.680489E+10 | 10524.12 | 18-JUN-16:02 | 35.98 | 27.42 | 0.276981E+09 | 347.86 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.753025E+10 | 12769.51 | 30-JUL-15:22 | 39.35 | 29.13 | 0.257732E+09 | 347.88 | 03-JUL-09:09 | 39.35 | 29.13 |
August | 0.836708E+10 | 12536.94 | 20-AUG-14:32 | 38.17 | 26.36 | 0.288984E+09 | 347.86 | 04-AUG-13:00 | 38.17 | 26.36 |
September | 0.698215E+10 | 13317.79 | 04-SEP-15:41 | 40.75 | 24.06 | 0.256755E+09 | 347.85 | 26-SEP-09:30 | 35.45 | 21.05 |
October | 0.616661E+10 | 12154.12 | 08-OCT-15:52 | 32.80 | 26.05 | 0.266821E+09 | 347.85 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.466860E+10 | 9551.13 | 12-NOV-15:13 | 29.03 | 17.77 | 0.263661E+09 | 347.85 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.319825E+10 | 4456.39 | 04-DEC-15:30 | 26.60 | 21.10 | 0.255087E+09 | 347.86 | 08-DEC-10:09 | 22.75 | 18.50 |
Annual Sum or Average | 0.633469E+11 | 0.318559E+10 | ||||||||
Minimum of Months | 0.273000E+10 | 3691.87 | 22.80 | 16.92 | 0.238505E+09 | 347.85 | 22.75 | 16.92 | ||
Maximum of Months | 0.836708E+10 | 13317.79 | 40.75 | 29.13 | 0.288984E+09 | 347.88 | 39.35 | 29.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294888E+10 | 4042.15 | 23-JAN-14:10 | 27.50 | 16.66 | 0.409889E+09 | 549.50 | 17-JAN-10:09 | 27.50 | 16.66 |
February | 0.317249E+10 | 5500.43 | 06-FEB-15:00 | 32.50 | 17.28 | 0.375491E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.461072E+10 | 6646.33 | 27-MAR-13:40 | 35.33 | 19.53 | 0.452100E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.553335E+10 | 8119.08 | 23-APR-16:02 | 32.25 | 18.47 | 0.403631E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.812798E+10 | 11194.93 | 10-MAY-04:02 | 29.83 | 16.21 | 0.438798E+09 | 549.53 | 04-MAY-13:00 | 29.83 | 16.21 |
June | 0.883426E+10 | 11301.86 | 02-JUN-04:02 | 28.33 | 18.21 | 0.437524E+09 | 549.52 | 02-JUN-13:09 | 38.83 | 24.30 |
July | 0.947511E+10 | 13454.55 | 23-JUL-13:22 | 38.10 | 26.30 | 0.407178E+09 | 549.60 | 31-JUL-13:30 | 40.45 | 27.06 |
August | 0.987940E+10 | 13877.27 | 06-AUG-16:51 | 40.00 | 26.17 | 0.456427E+09 | 549.50 | 04-AUG-13:20 | 40.00 | 26.17 |
September | 0.783654E+10 | 13577.85 | 03-SEP-16:12 | 37.17 | 26.54 | 0.405324E+09 | 549.50 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.664578E+10 | 13393.42 | 09-OCT-15:52 | 36.80 | 18.76 | 0.420952E+09 | 549.49 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.486273E+10 | 7259.56 | 20-NOV-06:03 | 25.85 | 18.49 | 0.415304E+09 | 549.51 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.336471E+10 | 4582.11 | 11-DEC-14:10 | 26.77 | 18.23 | 0.399713E+09 | 549.50 | 01-DEC-14:09 | 26.77 | 18.23 |
Annual Sum or Average | 0.752920E+11 | 0.502233E+10 | ||||||||
Minimum of Months | 0.294888E+10 | 4042.15 | 25.85 | 16.21 | 0.375491E+09 | 549.49 | 25.67 | 16.21 | ||
Maximum of Months | 0.987940E+10 | 13877.27 | 40.00 | 26.54 | 0.456427E+09 | 549.60 | 40.45 | 27.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241927E+10 | 3171.17 | 24-JAN-11:10 | 24.00 | 18.08 | 0.192308E+09 | 338.73 | 24-JAN-11:20 | 24.00 | 18.46 |
February | 0.258021E+10 | 3766.73 | 06-FEB-14:00 | 32.00 | 17.22 | 0.175864E+09 | 338.73 | 06-FEB-16:49 | 26.90 | 20.82 |
March | 0.366608E+10 | 6721.12 | 26-MAR-11:13 | 33.33 | 16.90 | 0.210883E+09 | 338.75 | 28-MAR-10:20 | 27.33 | 20.93 |
April | 0.451593E+10 | 10148.93 | 23-APR-11:23 | 33.00 | 16.90 | 0.189079E+09 | 338.74 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.642554E+10 | 12121.23 | 07-MAY-09:52 | 36.50 | 17.98 | 0.205615E+09 | 338.96 | 08-MAY-10:39 | 39.53 | 19.24 |
June | 0.671396E+10 | 11381.16 | 25-JUN-09:23 | 32.15 | 27.01 | 0.204730E+09 | 338.74 | 15-JUN-07:19 | 32.15 | 27.01 |
July | 0.717414E+10 | 11849.19 | 30-JUL-10:12 | 43.27 | 21.89 | 0.191237E+09 | 339.13 | 31-JUL-10:30 | 40.45 | 24.31 |
August | 0.762311E+10 | 12201.70 | 13-AUG-10:42 | 39.60 | 25.04 | 0.213574E+09 | 339.17 | 30-AUG-10:50 | 42.55 | 23.86 |
September | 0.617549E+10 | 12305.53 | 04-SEP-09:52 | 38.00 | 23.07 | 0.190078E+09 | 338.73 | 19-SEP-07:19 | 29.07 | 21.35 |
October | 0.528461E+10 | 11887.23 | 09-OCT-10:32 | 35.10 | 22.00 | 0.197556E+09 | 338.74 | 04-OCT-07:19 | 35.10 | 22.00 |
November | 0.383929E+10 | 7481.87 | 05-NOV-11:42 | 33.72 | 17.44 | 0.194716E+09 | 338.75 | 06-NOV-08:20 | 24.33 | 20.27 |
December | 0.265250E+10 | 3600.84 | 04-DEC-10:00 | 24.40 | 20.71 | 0.187160E+09 | 338.73 | 20-DEC-13:20 | 24.30 | 20.76 |
Annual Sum or Average | 0.590701E+11 | 0.235280E+10 | ||||||||
Minimum of Months | 0.241927E+10 | 3171.17 | 24.00 | 16.90 | 0.175864E+09 | 338.73 | 24.00 | 18.46 | ||
Maximum of Months | 0.762311E+10 | 12305.53 | 43.27 | 27.01 | 0.213574E+09 | 339.17 | 42.55 | 27.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506183E+10 | 7739.21 | 23-JAN-13:30 | 27.70 | 16.54 | 0.415219E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.504753E+10 | 12141.92 | 05-FEB-12:23 | 31.05 | 19.28 | 0.377896E+09 | 549.53 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.621726E+10 | 15359.13 | 26-MAR-13:13 | 34.33 | 18.34 | 0.452809E+09 | 549.66 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.630623E+10 | 12641.00 | 23-APR-16:02 | 32.25 | 18.47 | 0.403753E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.819970E+10 | 12369.98 | 28-MAY-13:23 | 34.85 | 23.67 | 0.438683E+09 | 549.53 | 04-MAY-13:00 | 34.85 | 23.67 |
June | 0.852872E+10 | 12296.55 | 16-JUN-04:02 | 28.83 | 20.58 | 0.437363E+09 | 549.52 | 02-JUN-13:09 | 28.83 | 20.58 |
July | 0.942137E+10 | 15091.35 | 23-JUL-13:22 | 38.10 | 26.30 | 0.407064E+09 | 549.54 | 03-JUL-09:09 | 38.10 | 26.30 |
August | 0.104720E+11 | 15567.49 | 06-AUG-16:51 | 40.00 | 26.17 | 0.456431E+09 | 549.66 | 29-AUG-13:30 | 37.30 | 29.96 |
September | 0.941465E+10 | 15972.35 | 03-SEP-13:32 | 39.97 | 25.60 | 0.405512E+09 | 549.74 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.924066E+10 | 16327.30 | 29-OCT-13:22 | 34.55 | 17.47 | 0.421526E+09 | 549.81 | 20-OCT-13:00 | 34.55 | 17.47 |
November | 0.763570E+10 | 16008.92 | 05-NOV-11:42 | 33.72 | 17.44 | 0.416491E+09 | 549.86 | 13-NOV-14:50 | 33.00 | 18.21 |
December | 0.567524E+10 | 15629.65 | 03-DEC-12:53 | 29.80 | 17.63 | 0.403025E+09 | 549.51 | 01-DEC-14:09 | 29.80 | 17.63 |
Annual Sum or Average | 0.912209E+11 | 0.503577E+10 | ||||||||
Minimum of Months | 0.504753E+10 | 7739.21 | 27.70 | 16.54 | 0.377896E+09 | 549.51 | 24.00 | 17.47 | ||
Maximum of Months | 0.104720E+11 | 16327.30 | 40.00 | 26.30 | 0.456431E+09 | 549.86 | 38.10 | 29.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253539E+10 | 3699.68 | 31-JAN-16:20 | 22.73 | 16.79 | 0.256299E+09 | 347.85 | 24-JAN-10:00 | 22.73 | 16.79 |
February | 0.271599E+10 | 5607.53 | 05-FEB-15:43 | 32.00 | 19.00 | 0.235785E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.386259E+10 | 11409.16 | 26-MAR-15:53 | 31.80 | 18.54 | 0.284983E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.445424E+10 | 12657.26 | 23-APR-16:42 | 31.25 | 19.17 | 0.255117E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.631082E+10 | 12439.10 | 21-MAY-15:52 | 37.50 | 23.27 | 0.277680E+09 | 347.88 | 04-MAY-13:00 | 37.50 | 23.27 |
June | 0.672154E+10 | 12040.38 | 18-JUN-16:02 | 35.98 | 27.42 | 0.276896E+09 | 347.87 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.718023E+10 | 12508.71 | 23-JUL-16:02 | 38.50 | 26.05 | 0.257691E+09 | 347.88 | 03-JUL-09:09 | 38.50 | 26.05 |
August | 0.760681E+10 | 13582.31 | 06-AUG-16:51 | 40.00 | 26.17 | 0.288911E+09 | 347.85 | 04-AUG-13:50 | 40.00 | 26.17 |
September | 0.618013E+10 | 13338.02 | 03-SEP-16:12 | 37.17 | 26.54 | 0.256562E+09 | 347.85 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.528398E+10 | 13102.38 | 09-OCT-15:52 | 36.80 | 18.76 | 0.266393E+09 | 347.85 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.392224E+10 | 12312.98 | 05-NOV-15:02 | 31.90 | 20.93 | 0.262490E+09 | 347.86 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.281864E+10 | 4305.34 | 06-DEC-15:30 | 26.85 | 20.67 | 0.251010E+09 | 347.85 | 04-DEC-10:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.595926E+11 | 0.316982E+10 | ||||||||
Minimum of Months | 0.253539E+10 | 3699.68 | 22.73 | 16.79 | 0.235785E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.760681E+10 | 13582.31 | 40.00 | 27.42 | 0.288911E+09 | 347.88 | 40.00 | 27.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340329E+09 | 3538.45 | 03-JAN-06:03 | 12.93 |
February | 0.202889E+09 | 3318.98 | 13-FEB-06:03 | 13.03 |
March | 0.156733E+09 | 4764.20 | 28-MAR-05:03 | 25.67 |
April | 56935961.76 | 4714.71 | 25-APR-05:03 | 23.83 |
May | 21127867.06 | 5190.42 | 08-MAY-04:02 | 26.67 |
June | 16330492.14 | 4121.35 | 19-JUN-04:02 | 28.08 |
July | 9331654.24 | 3173.51 | 03-JUL-04:02 | 29.00 |
August | 6644350.94 | 3088.53 | 15-AUG-04:02 | 29.75 |
September | 17468334.93 | 4909.17 | 25-SEP-04:02 | 24.17 |
October | 26162309.92 | 4901.40 | 10-OCT-04:02 | 27.00 |
November | 49946228.75 | 4034.31 | 01-NOV-05:03 | 23.83 |
December | 0.214079E+09 | 3308.44 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.111798E+10 | |||
Minimum of Months | 6644350.94 | 3088.53 | 12.93 | |
Maximum of Months | 0.340329E+09 | 5190.42 | 29.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21006802.72 | 2588.65 | 01-JAN-13:23 | 22.65 |
February | 14942062.59 | 2321.58 | 26-FEB-11:30 | 22.50 |
March | 10188299.97 | 2081.07 | 02-MAR-05:03 | 29.08 |
April | 11269119.41 | 2052.17 | 17-APR-04:02 | 24.33 |
May | 15877062.55 | 2988.02 | 12-MAY-04:02 | 28.67 |
June | 18040255.09 | 2914.16 | 16-JUN-04:02 | 28.83 |
July | 28312090.77 | 3214.79 | 13-JUL-04:02 | 30.58 |
August | 26058741.92 | 3326.40 | 25-AUG-04:02 | 31.17 |
September | 18163823.58 | 3214.00 | 08-SEP-04:02 | 30.62 |
October | 18667415.67 | 2548.07 | 05-OCT-04:02 | 27.83 |
November | 16929412.93 | 2126.80 | 20-NOV-05:03 | 26.00 |
December | 19461308.34 | 2526.10 | 31-DEC-11:20 | 24.00 |
Annual Sum or Average | 0.218916E+09 | |||
Minimum of Months | 10188299.97 | 2052.17 | 22.50 | |
Maximum of Months | 28312090.77 | 3326.40 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41233298.85 | 3002.27 | 01-JAN-12:03 | 21.22 |
February | 25795288.34 | 2417.95 | 19-FEB-11:03 | 24.92 |
March | 20289527.87 | 3958.70 | 01-MAR-05:03 | 23.92 |
April | 18600111.65 | 3334.03 | 25-APR-04:52 | 24.00 |
May | 23072166.51 | 4096.77 | 23-MAY-04:02 | 31.17 |
June | 28807396.72 | 4026.42 | 28-JUN-04:02 | 29.00 |
July | 49291455.70 | 4303.34 | 13-JUL-04:02 | 30.58 |
August | 53486309.10 | 4351.97 | 31-AUG-04:02 | 28.83 |
September | 42885837.95 | 4803.11 | 28-SEP-04:02 | 27.75 |
October | 38180023.57 | 4595.97 | 13-OCT-04:02 | 25.75 |
November | 36051499.10 | 4175.98 | 03-NOV-04:02 | 24.08 |
December | 35416959.82 | 2622.85 | 17-DEC-11:33 | 21.67 |
Annual Sum or Average | 0.413110E+09 | |||
Minimum of Months | 18600111.65 | 2417.95 | 21.22 | |
Maximum of Months | 53486309.10 | 4803.11 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 140926.20 | 633.23 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 140926.20 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 140926.20 | 633.23 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 384782.80 | 1303.75 | 20-JAN-07:03 | 12.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 384782.80 | |||
Minimum of Months | 0.00 | 0.00 | 12.17 | |
Maximum of Months | 384782.80 | 1303.75 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149517E+09 | 4584.14 | 04-JAN-07:20 | 13.80 |
February | 91046577.30 | 4607.35 | 02-FEB-07:08 | 14.42 |
March | 24738499.43 | 4436.97 | 16-MAR-06:06 | 15.00 |
April | 27233.60 | 226.95 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 19821600.77 | 3830.28 | 19-DEC-07:07 | 14.92 |
Annual Sum or Average | 0.285151E+09 | |||
Minimum of Months | 0.00 | 0.00 | 13.80 | |
Maximum of Months | 0.149517E+09 | 4607.35 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787026E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.682380E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.788076E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.678723E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708602E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.698713E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.665518E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747497E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682664E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.734146E+09 | 947.97 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.763127E+09 | 1184.79 | 08-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.775536E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.871201E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.665518E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788076E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485772E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427823E+09 | 750.07 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495128E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429520E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452909E+09 | 450.21 | 18-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447766E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.424337E+09 | 490.21 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474582E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431992E+09 | 450.21 | 19-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458896E+09 | 450.21 | 02-OCT-15:50 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477595E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.477629E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548395E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.424337E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.495128E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738511E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.659399E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.778373E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679878E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719844E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.711281E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.674661E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751641E+09 | 774.31 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680242E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716166E+09 | 774.31 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.722577E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720436E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855301E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.659399E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.778373E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481316E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424537E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500668E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.435037E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.456658E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450024E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.428707E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479795E+09 | 600.10 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435543E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464360E+09 | 750.02 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.465858E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.468468E+09 | 750.02 | 11-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549097E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424537E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500668E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.781088E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.679681E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.785391E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.677181E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707980E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.697534E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.664648E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.746365E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.681454E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.731860E+09 | 947.97 | 10-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.759199E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.770176E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.868256E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664648E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.785391E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484147E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.426697E+09 | 750.07 | 09-FEB-16:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.493820E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.428823E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452169E+09 | 450.21 | 18-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447039E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.423447E+09 | 490.21 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474000E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431316E+09 | 450.21 | 25-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.457901E+09 | 450.21 | 02-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.475929E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475933E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547122E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423447E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.493820E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737862E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.658042E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.776386E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679100E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.718416E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.710191E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.673002E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.750477E+09 | 711.15 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.679205E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.715173E+09 | 774.31 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721622E+09 | 1121.62 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.718992E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853847E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.658042E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.776386E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479519E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.423402E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.499474E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.433580E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455736E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.448938E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.427582E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478537E+09 | 600.10 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434668E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463011E+09 | 750.02 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.464801E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466829E+09 | 750.02 | 14-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547608E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.423402E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.499474E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787026E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.682380E+09 | 1184.79 | 09-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.788076E+09 | 1358.45 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.678723E+09 | 1184.79 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708602E+09 | 711.15 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.698713E+09 | 711.15 | 08-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.665518E+09 | 947.97 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747497E+09 | 774.31 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682664E+09 | 774.31 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.734146E+09 | 947.97 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.763127E+09 | 1184.79 | 08-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.775536E+09 | 1358.45 | 11-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.871201E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.665518E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788076E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485772E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427823E+09 | 750.07 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495128E+09 | 860.01 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429520E+09 | 600.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452909E+09 | 450.21 | 18-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.447763E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.424329E+09 | 490.21 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474582E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431992E+09 | 450.21 | 19-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458896E+09 | 450.21 | 02-OCT-15:50 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477595E+09 | 860.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.477629E+09 | 860.01 | 11-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548394E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.424329E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.495128E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738511E+09 | 947.97 | 09-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.659399E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.778367E+09 | 1358.45 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679878E+09 | 1184.79 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719844E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.711277E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.674661E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751641E+09 | 774.31 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680242E+09 | 774.31 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716166E+09 | 774.31 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.722577E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720436E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855300E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.659399E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.778367E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481316E+09 | 750.02 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424537E+09 | 750.02 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500668E+09 | 859.95 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.435037E+09 | 750.02 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.456658E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450024E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.428707E+09 | 750.02 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479795E+09 | 600.10 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435543E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464360E+09 | 750.02 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.465858E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.468468E+09 | 750.02 | 11-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549097E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424537E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500668E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787026E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271956.60 | 69764927.72 |
February | 0.901968E+09 | 0.682380E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8250196.77 | 70984014.60 |
March | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19799523.27 | 39455374.04 |
April | 0.956342E+09 | 0.678723E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47364699.42 | 18188741.37 |
May | 0.103597E+10 | 0.708602E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114916E+09 | 2133294.41 |
June | 0.103308E+10 | 0.698713E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143071E+09 | 198206.33 |
July | 0.959235E+09 | 0.665518E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205033E+09 | 0.00 |
August | 0.107774E+10 | 0.747497E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196372E+09 | 0.00 |
September | 0.956342E+09 | 0.682664E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137705E+09 | 315113.25 |
October | 0.994195E+09 | 0.734146E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79252467.75 | 2927911.37 |
November | 0.984487E+09 | 0.763127E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33948003.89 | 18610470.12 |
December | 0.959235E+09 | 0.775536E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5748516.91 | 50863414.57 |
Annual Sum or Average | 0.119305E+11 | 0.871201E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992732E+09 | 0.273441E+09 |
Minimum of Months | 0.901968E+09 | 0.665518E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271956.60 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205033E+09 | 70984014.60 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.485772E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 567772.88 | 48527303.19 |
February | 0.571020E+09 | 0.427823E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4937695.88 | 48690550.34 |
March | 0.682301E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12929677.08 | 26982702.61 |
April | 0.605444E+09 | 0.429520E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30651317.45 | 12388141.88 |
May | 0.655854E+09 | 0.452909E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76424273.32 | 1465852.98 |
June | 0.654023E+09 | 0.447766E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95659380.48 | 136649.54 |
July | 0.607275E+09 | 0.424337E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137223E+09 | 0.00 |
August | 0.682301E+09 | 0.474582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131282E+09 | 0.00 |
September | 0.605444E+09 | 0.431992E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91507603.27 | 217289.31 |
October | 0.629407E+09 | 0.458896E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52216703.28 | 2103189.85 |
November | 0.623262E+09 | 0.477595E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21669512.31 | 13100365.15 |
December | 0.607275E+09 | 0.477629E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3554272.22 | 34725406.45 |
Annual Sum or Average | 0.755301E+10 | 0.548395E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658623E+09 | 0.188337E+09 |
Minimum of Months | 0.571020E+09 | 0.424337E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 567772.88 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137223E+09 | 48690550.34 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738511E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444663.79 | 80524801.81 |
February | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6710358.97 | 78071896.46 |
March | 0.107774E+10 | 0.778373E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18786541.83 | 42527170.72 |
April | 0.956342E+09 | 0.679878E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46159498.65 | 18558954.72 |
May | 0.103597E+10 | 0.719844E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115671E+09 | 2122288.28 |
June | 0.103308E+10 | 0.711281E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144292E+09 | 186779.75 |
July | 0.959235E+09 | 0.674661E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206548E+09 | 0.00 |
August | 0.107774E+10 | 0.751641E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196991E+09 | 0.00 |
September | 0.956342E+09 | 0.680242E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136617E+09 | 336080.97 |
October | 0.994195E+09 | 0.716166E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76221882.40 | 3446164.51 |
November | 0.984487E+09 | 0.722577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28960499.93 | 21097878.79 |
December | 0.959235E+09 | 0.720436E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4005873.45 | 58556180.99 |
Annual Sum or Average | 0.119305E+11 | 0.855301E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981408E+09 | 0.305428E+09 |
Minimum of Months | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444663.79 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.778373E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206548E+09 | 80524801.81 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481316E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 757430.90 | 48090633.78 |
February | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5361720.88 | 48608688.14 |
March | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12960625.75 | 27735881.32 |
April | 0.605404E+09 | 0.435037E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30825745.42 | 12722838.69 |
May | 0.655811E+09 | 0.456658E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76460577.11 | 1504283.50 |
June | 0.653980E+09 | 0.450024E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95365040.06 | 139737.04 |
July | 0.607235E+09 | 0.428707E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137638E+09 | 0.00 |
August | 0.682256E+09 | 0.479795E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131512E+09 | 0.00 |
September | 0.605404E+09 | 0.435543E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91309408.33 | 219029.93 |
October | 0.629366E+09 | 0.464360E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52047671.13 | 2108019.84 |
November | 0.623221E+09 | 0.465858E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21683997.29 | 12852242.92 |
December | 0.607235E+09 | 0.468468E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3611362.47 | 34828037.61 |
Annual Sum or Average | 0.755252E+10 | 0.549097E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659534E+09 | 0.188809E+09 |
Minimum of Months | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 757430.90 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137638E+09 | 48608688.14 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.781088E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 571259.71 | 44377539.84 |
February | 0.901968E+09 | 0.679681E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486215.86 | 43078729.60 |
March | 0.107774E+10 | 0.785391E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10847982.37 | 22731736.17 |
April | 0.956342E+09 | 0.677181E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26422565.91 | 9950821.56 |
May | 0.103597E+10 | 0.707980E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62626506.58 | 954564.98 |
June | 0.103308E+10 | 0.697534E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77320437.01 | 92725.39 |
July | 0.959235E+09 | 0.664648E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110376E+09 | 0.00 |
August | 0.107774E+10 | 0.746365E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105632E+09 | 0.00 |
September | 0.956342E+09 | 0.681454E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74287003.67 | 170120.86 |
October | 0.994195E+09 | 0.731860E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42310499.06 | 1969412.22 |
November | 0.984487E+09 | 0.759199E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17770155.36 | 12594195.44 |
December | 0.959235E+09 | 0.770176E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2835050.20 | 33742825.37 |
Annual Sum or Average | 0.119305E+11 | 0.868256E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535485E+09 | 0.169663E+09 |
Minimum of Months | 0.901968E+09 | 0.664648E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 571259.71 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.785391E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110376E+09 | 44377539.84 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.484147E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251180.45 | 30822089.46 |
February | 0.571020E+09 | 0.426697E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2706632.76 | 29793926.84 |
March | 0.682301E+09 | 0.493820E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7002816.14 | 15747013.18 |
April | 0.605444E+09 | 0.428823E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16784399.49 | 7031219.76 |
May | 0.655854E+09 | 0.452169E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41197054.12 | 712290.22 |
June | 0.654023E+09 | 0.447039E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51322600.76 | 72121.98 |
July | 0.607275E+09 | 0.423447E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73462866.93 | 0.00 |
August | 0.682301E+09 | 0.474000E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70277068.82 | 0.00 |
September | 0.605444E+09 | 0.431316E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49042667.89 | 127471.18 |
October | 0.629407E+09 | 0.457901E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27664385.20 | 1475653.69 |
November | 0.623262E+09 | 0.475929E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11281245.59 | 8992917.72 |
December | 0.607275E+09 | 0.475933E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1782579.77 | 23133166.12 |
Annual Sum or Average | 0.755301E+10 | 0.547122E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352775E+09 | 0.117908E+09 |
Minimum of Months | 0.571020E+09 | 0.423447E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251180.45 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.493820E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73462866.93 | 30822089.46 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737862E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21422663.82 | 0.145425E+10 |
February | 0.901968E+09 | 0.658042E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253066E+09 | 0.881768E+09 |
March | 0.107774E+10 | 0.776386E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878580E+09 | 0.564506E+09 |
April | 0.956342E+09 | 0.679100E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162546E+10 | 0.199291E+09 |
May | 0.103597E+10 | 0.718416E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335513E+10 | 33211243.65 |
June | 0.103308E+10 | 0.710191E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394458E+10 | 1189548.46 |
July | 0.959235E+09 | 0.673002E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415633E+10 | 0.00 |
August | 0.107774E+10 | 0.750477E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480581E+10 | 0.00 |
September | 0.956342E+09 | 0.679205E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334340E+10 | 2752219.54 |
October | 0.994195E+09 | 0.715173E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242966E+10 | 24158687.39 |
November | 0.984487E+09 | 0.721622E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130730E+10 | 0.294326E+09 |
December | 0.959235E+09 | 0.718992E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201639E+09 | 0.836041E+09 |
Annual Sum or Average | 0.119305E+11 | 0.853847E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263224E+11 | 0.429149E+10 |
Minimum of Months | 0.901968E+09 | 0.658042E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21422663.82 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.776386E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480581E+10 | 0.145425E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.479519E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 333727.86 | 30858398.56 |
February | 0.570983E+09 | 0.423402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2831087.29 | 30055913.07 |
March | 0.682256E+09 | 0.499474E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6887869.16 | 16420512.67 |
April | 0.605404E+09 | 0.433580E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16664142.82 | 7276328.59 |
May | 0.655811E+09 | 0.455736E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41038396.76 | 744776.70 |
June | 0.653980E+09 | 0.448938E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50876046.77 | 78800.84 |
July | 0.607235E+09 | 0.427582E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73266308.18 | 0.00 |
August | 0.682256E+09 | 0.478537E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70063823.13 | 0.00 |
September | 0.605404E+09 | 0.434668E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48713589.25 | 133492.89 |
October | 0.629366E+09 | 0.463011E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27416447.91 | 1520716.91 |
November | 0.623221E+09 | 0.464801E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11185047.22 | 9004802.33 |
December | 0.607235E+09 | 0.466829E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1756910.88 | 23400216.69 |
Annual Sum or Average | 0.755252E+10 | 0.547608E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351033E+09 | 0.119494E+09 |
Minimum of Months | 0.570983E+09 | 0.423402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 333727.86 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.499474E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73266308.18 | 30858398.56 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.787026E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009303.51 | 64887968.30 |
February | 0.901968E+09 | 0.682380E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6863794.61 | 64866099.19 |
March | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16516011.46 | 35841228.27 |
April | 0.956342E+09 | 0.678723E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39910458.03 | 16316910.83 |
May | 0.103597E+10 | 0.708602E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96326159.29 | 1874401.05 |
June | 0.103308E+10 | 0.698713E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119661E+09 | 167740.66 |
July | 0.959235E+09 | 0.665518E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170855E+09 | 0.00 |
August | 0.107774E+10 | 0.747497E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163839E+09 | 0.00 |
September | 0.956342E+09 | 0.682664E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115250E+09 | 271823.26 |
October | 0.994195E+09 | 0.734146E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66335042.68 | 2691375.21 |
November | 0.984487E+09 | 0.763127E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28211707.74 | 17536178.17 |
December | 0.959235E+09 | 0.775536E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4594971.51 | 47567310.60 |
Annual Sum or Average | 0.119305E+11 | 0.871201E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829372E+09 | 0.252021E+09 |
Minimum of Months | 0.901968E+09 | 0.665518E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009303.51 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.788076E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170855E+09 | 64887968.30 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.485772E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472333.77 | 44428797.23 |
February | 0.421807E+09 | 0.427823E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4150632.03 | 44025083.14 |
March | 0.502994E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10800764.23 | 24250015.41 |
April | 0.447140E+09 | 0.429520E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25902783.24 | 11059837.42 |
May | 0.484071E+09 | 0.452909E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64149608.79 | 1277466.04 |
June | 0.482240E+09 | 0.447763E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80098517.60 | 113969.92 |
July | 0.448971E+09 | 0.424329E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114405E+09 | 0.00 |
August | 0.502994E+09 | 0.474582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109556E+09 | 0.00 |
September | 0.447140E+09 | 0.431992E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76650968.06 | 184384.61 |
October | 0.465148E+09 | 0.458896E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43783216.97 | 1892730.93 |
November | 0.460569E+09 | 0.477595E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18072747.43 | 12169771.49 |
December | 0.448971E+09 | 0.477629E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901502.15 | 32120820.76 |
Annual Sum or Average | 0.557719E+10 | 0.548394E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550944E+09 | 0.171523E+09 |
Minimum of Months | 0.421807E+09 | 0.424329E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472333.77 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.495128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114405E+09 | 44428797.23 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738511E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362821.48 | 73139244.83 |
February | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5580622.71 | 70400077.67 |
March | 0.107774E+10 | 0.778367E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15617067.85 | 38364834.32 |
April | 0.956342E+09 | 0.679878E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38682022.01 | 16655033.69 |
May | 0.103597E+10 | 0.719844E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96851490.30 | 1869845.14 |
June | 0.103308E+10 | 0.711277E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120583E+09 | 159268.79 |
July | 0.959235E+09 | 0.674661E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171847E+09 | 0.00 |
August | 0.107774E+10 | 0.751641E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164033E+09 | 0.00 |
September | 0.956342E+09 | 0.680242E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114030E+09 | 290626.68 |
October | 0.994195E+09 | 0.716166E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63604436.98 | 3125316.00 |
November | 0.984487E+09 | 0.722577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24182165.20 | 19556985.33 |
December | 0.959235E+09 | 0.720436E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3288427.64 | 53501028.97 |
Annual Sum or Average | 0.119305E+11 | 0.855300E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818662E+09 | 0.277062E+09 |
Minimum of Months | 0.901968E+09 | 0.659399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362821.48 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.778367E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171847E+09 | 73139244.83 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481316E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 608583.40 | 44472821.87 |
February | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4405780.09 | 44334462.71 |
March | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10690311.47 | 25123022.87 |
April | 0.605404E+09 | 0.435037E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25703373.52 | 11429383.14 |
May | 0.655811E+09 | 0.456658E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63895648.38 | 1326486.95 |
June | 0.653980E+09 | 0.450024E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79520544.63 | 118041.72 |
July | 0.607235E+09 | 0.428707E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114192E+09 | 0.00 |
August | 0.682256E+09 | 0.479795E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109284E+09 | 0.00 |
September | 0.605404E+09 | 0.435543E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76087533.37 | 189270.52 |
October | 0.629366E+09 | 0.464360E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43378573.23 | 1925916.79 |
November | 0.623221E+09 | 0.465858E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17885960.62 | 12105015.23 |
December | 0.607235E+09 | 0.468468E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2868619.76 | 32536030.26 |
Annual Sum or Average | 0.755252E+10 | 0.549097E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548521E+09 | 0.173560E+09 |
Minimum of Months | 0.570983E+09 | 0.424537E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 608583.40 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.500668E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114192E+09 | 44472821.87 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537935.86 | 98656547.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7210711.90 | 95699636.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17823337.00 | 52063719.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45976778.96 | 22367874.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118227E+09 | 2191291.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148179E+09 | 217453.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213200E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202477E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141150E+09 | 336962.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77973856.53 | 3881754.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29375589.71 | 25460465.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3870669.85 | 72346333.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100600E+10 | 0.373222E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537935.86 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213200E+09 | 98656547.81 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1262099.28 | 0.114935E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10146684.30 | 0.114501E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23750731.98 | 62688938.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60368817.74 | 27676086.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152622E+09 | 2825635.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191510E+09 | 260426.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275451E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262096E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183124E+09 | 425576.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102253E+09 | 4464860.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40200169.27 | 30043279.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6034181.12 | 84333603.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130882E+10 | 0.442155E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1262099.28 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275451E+09 | 0.114935E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415836.54 | 0.111985E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8564311.45 | 0.110399E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23217434.88 | 60839168.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55227115.23 | 23157771.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156890E+09 | 1990799.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203060E+09 | 194500.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290955E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279356E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193514E+09 | 290252.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107811E+09 | 2688965.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39372255.33 | 22900929.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4083639.87 | 78386734.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136247E+10 | 0.412833E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415836.54 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290955E+09 | 0.111985E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 29-JAN-11:50 | 184.72 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.89 | 05-FEB-14:40 | 155.06 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.82 | 26-MAR-14:00 | 162.69 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.19 | 30-APR-12:58 | 106.28 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.42 | 21-MAY-12:53 | 38.14 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.85 | 11-JUN-14:46 | 27.28 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.05 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.44 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.74 | 03-SEP-15:56 | 26.71 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.75 | 09-OCT-15:26 | 52.39 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 08-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.97 | 19-NOV-13:50 | 85.12 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.22 | 10-DEC-12:00 | 121.38 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.42 | 184.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 29-JAN-11:50 | 122.97 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.58 | 05-FEB-15:00 | 103.93 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.73 | 26-MAR-14:20 | 111.64 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.05 | 30-APR-12:58 | 70.89 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 18-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.61 | 21-MAY-12:53 | 25.56 | 01-MAY-04:53 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.26 | 11-JUN-14:46 | 18.01 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 301.20 | 30-JUL-14:33 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.67 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 19-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.16 | 03-SEP-15:56 | 17.66 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 450.21 | 02-OCT-15:50 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.71 | 09-OCT-15:26 | 34.98 | 20-OCT-04:50 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.01 | 19-NOV-13:50 | 56.31 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.94 | 10-DEC-12:40 | 79.78 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 0.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 797.61 | 122.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 29-JAN-11:50 | 191.98 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 05-FEB-14:58 | 162.68 | 10-FEB-23:10 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 26-MAR-14:15 | 185.20 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.45 | 30-APR-12:58 | 107.51 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.42 | 21-MAY-12:53 | 38.44 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.28 | 11-JUN-14:46 | 27.08 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.05 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.70 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.03 | 03-SEP-15:54 | 27.02 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.94 | 09-OCT-16:06 | 53.93 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.87 | 19-NOV-14:05 | 86.62 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 | 10-DEC-13:00 | 121.40 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.42 | 191.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.42 | 29-JAN-11:50 | 123.46 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 | 05-FEB-12:23 | 104.73 | 10-FEB-23:10 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 26-MAR-13:53 | 119.01 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.52 | 30-APR-12:58 | 72.48 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 797.61 | 21-MAY-12:53 | 25.89 | 01-MAY-04:53 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.43 | 11-JUN-12:48 | 18.28 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.70 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.96 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.76 | 03-SEP-15:54 | 17.57 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.76 | 09-OCT-15:24 | 35.54 | 20-OCT-04:50 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.03 | 19-NOV-13:43 | 56.71 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 11-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 10-DEC-12:00 | 79.44 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.42 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 797.61 | 123.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 29-JAN-12:00 | 119.65 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.31 | 05-FEB-14:50 | 95.88 | 10-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 | 26-MAR-13:53 | 84.00 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 | 30-APR-12:53 | 59.97 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.09 | 21-MAY-12:57 | 17.55 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.65 | 11-JUN-14:46 | 12.40 | 07-JUN-04:45 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.70 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.59 | 13-AUG-13:52 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.66 | 03-SEP-15:44 | 15.90 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 10-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.07 | 09-OCT-15:00 | 35.35 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.43 | 19-NOV-14:00 | 55.60 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.35 | 10-DEC-11:55 | 77.42 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 649.09 | 119.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 29-JAN-12:00 | 81.97 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 09-FEB-16:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 05-FEB-15:10 | 64.82 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.51 | 26-MAR-14:10 | 56.68 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.20 | 30-APR-13:08 | 40.81 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 18-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.85 | 21-MAY-12:57 | 12.17 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.10 | 11-JUN-14:46 | 8.55 | 07-JUN-04:45 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.46 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.49 | 13-AUG-14:16 | 0.00 | 01-AUG-00:03 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 25-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 | 03-SEP-15:44 | 11.09 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 450.21 | 02-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.87 | 09-OCT-15:26 | 24.64 | 20-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 | 19-NOV-13:50 | 37.29 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 10-DEC-12:40 | 51.23 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 0.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 432.85 | 81.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.28 | 23-JAN-13:00 | 12356.21 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7405.77 | 07-FEB-13:00 | 10836.96 | 13-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15743.26 | 27-MAR-11:01 | 8796.46 | 16-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18436.22 | 28-APR-11:01 | 6696.62 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18166.17 | 09-MAY-11:01 | 4046.93 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20260.05 | 12-JUN-11:01 | 538.52 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23290.29 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22580.10 | 16-AUG-11:01 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17764.44 | 12-SEP-11:01 | 1052.24 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14169.45 | 04-OCT-11:01 | 2695.88 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1121.62 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9232.13 | 01-NOV-11:02 | 7689.67 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4964.32 | 01-DEC-12:10 | 11553.93 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.28 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23290.29 | 12356.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 29-JAN-12:00 | 82.04 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.71 | 05-FEB-14:50 | 65.88 | 10-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.43 | 26-MAR-13:53 | 60.89 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.66 | 30-APR-13:10 | 41.83 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.32 | 21-MAY-12:57 | 12.33 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.02 | 11-JUN-12:48 | 8.94 | 07-JUN-04:45 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.37 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.09 | 13-AUG-14:14 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.80 | 03-SEP-16:00 | 11.22 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.61 | 09-OCT-15:24 | 25.13 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.61 | 19-NOV-14:00 | 37.73 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 10-DEC-11:55 | 51.18 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 433.32 | 82.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 29-JAN-11:50 | 172.97 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 05-FEB-14:50 | 142.51 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.16 | 26-MAR-14:00 | 134.81 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.05 | 30-APR-13:00 | 94.13 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 998.22 | 21-MAY-12:53 | 32.71 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 08-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.23 | 11-JUN-14:46 | 23.60 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.64 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.59 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.60 | 03-SEP-16:00 | 23.32 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.51 | 09-OCT-15:14 | 48.08 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 08-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.33 | 19-NOV-14:00 | 78.69 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 11-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.20 | 10-DEC-12:40 | 110.49 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 998.22 | 172.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | 29-JAN-12:00 | 114.84 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.21 | 05-FEB-15:10 | 95.29 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 860.01 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.90 | 26-MAR-14:00 | 92.28 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 600.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.88 | 30-APR-12:53 | 62.70 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 18-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.48 | 21-MAY-12:53 | 21.89 | 01-MAY-04:53 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.17 | 11-JUN-14:46 | 15.51 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 490.21 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.70 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.33 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 805.43 | 01-SEP-07:10 | 450.21 | 19-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.36 | 03-SEP-15:35 | 15.33 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 450.21 | 02-OCT-15:50 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.18 | 09-OCT-15:14 | 32.05 | 20-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.51 | 19-NOV-14:00 | 52.00 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 11-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 10-DEC-12:35 | 72.61 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.23 | 0.00 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 665.48 | 114.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 09-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 23-JAN-13:00 | 178.81 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 | 05-FEB-15:50 | 148.50 | 10-FEB-23:20 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.06 | 26-MAR-13:58 | 152.02 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.30 | 30-APR-12:53 | 95.17 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 998.22 | 21-MAY-12:53 | 33.01 | 01-MAY-04:53 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.00 | 11-JUN-14:46 | 23.48 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.43 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.90 | 13-AUG-14:04 | 0.00 | 01-AUG-00:03 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.70 | 03-SEP-15:35 | 23.68 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.84 | 09-OCT-15:55 | 49.43 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 19-NOV-13:52 | 79.85 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.15 | 10-DEC-12:00 | 110.54 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 998.22 | 178.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 29-JAN-11:50 | 115.53 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.19 | 05-FEB-13:23 | 96.22 | 10-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 | 26-MAR-13:58 | 98.34 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.87 | 30-APR-12:53 | 64.13 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.48 | 21-MAY-12:53 | 22.22 | 01-MAY-04:53 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.91 | 11-JUN-12:48 | 15.84 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.19 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.11 | 13-AUG-14:03 | 0.00 | 01-AUG-00:03 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.98 | 03-SEP-15:35 | 15.41 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.97 | 09-OCT-15:55 | 32.51 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.44 | 19-NOV-13:52 | 52.40 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 11-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 | 10-DEC-12:35 | 72.56 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 0.00 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 665.48 | 115.53 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.97 | 29-JAN-12:00 | 255.18 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.16 | 05-FEB-14:53 | 208.99 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.22 | 26-MAR-13:53 | 187.25 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.65 | 30-APR-12:53 | 131.07 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.08 | 21-MAY-13:00 | 40.23 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.41 | 11-JUN-13:10 | 30.91 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.05 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.73 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.97 | 03-SEP-16:00 | 31.31 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.09 | 09-OCT-15:10 | 65.51 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.27 | 19-NOV-14:00 | 114.43 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.19 | 10-DEC-12:00 | 160.37 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.97 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.08 | 255.18 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.86 | 29-JAN-12:00 | 301.33 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.94 | 05-FEB-14:53 | 253.31 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.64 | 26-MAR-14:00 | 227.47 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.62 | 30-APR-13:00 | 164.92 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.12 | 21-MAY-12:53 | 53.91 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.21 | 11-JUN-13:10 | 37.92 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.50 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.84 | 13-AUG-13:52 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.70 | 03-SEP-16:00 | 40.43 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.39 | 09-OCT-15:00 | 78.05 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.18 | 19-NOV-14:00 | 140.30 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.88 | 10-DEC-12:50 | 195.36 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1620.12 | 301.33 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 29-JAN-11:50 | 266.98 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.43 | 05-FEB-15:20 | 236.48 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.12 | 02-MAR-04:00 | 289.46 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.17 | 30-APR-13:00 | 147.87 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1491.63 | 21-MAY-13:00 | 52.56 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.60 | 09-JUN-03:00 | 31.11 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.10 | 30-JUL-14:20 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.75 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.99 | 04-SEP-17:00 | 35.68 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.98 | 09-OCT-15:10 | 64.76 | 20-OCT-04:20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.66 | 19-NOV-13:52 | 117.53 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.34 | 10-DEC-12:00 | 179.10 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1491.63 | 289.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 39223.59 | 02-JAN-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41902.81 | 06-FEB-06:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43130.99 | 28-MAR-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43883.68 | 25-APR-04:52 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43743.56 | 04-MAY-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42637.57 | 07-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41235.05 | 29-JUL-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37151.07 | 05-AUG-06:03 | 1905.79 | 2147.94 | 30513.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41999.41 | 30-SEP-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42370.60 | 28-OCT-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42543.71 | 25-NOV-05:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 41702.01 | 11-DEC-06:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 37151.07 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43883.68 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5387.03 | 31-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
February | 8183.52 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 0.00 |
March | 11067.72 | 27-MAR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 0.00 |
April | 12199.33 | 28-APR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.69 | 0.00 |
May | 12660.57 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.07 | 0.00 |
June | 13248.84 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.72 | 0.00 |
July | 14355.88 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.71 | 0.00 |
August | 14418.32 | 16-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.90 | 0.00 |
September | 13354.44 | 05-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.98 | 0.00 |
October | 11332.70 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.43 | 0.00 |
November | 9383.03 | 06-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 | 0.00 |
December | 6913.26 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5387.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14418.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.69 | 14.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2273.86 | 31-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
February | 4074.38 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 0.00 |
March | 5385.62 | 27-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.35 | 0.00 |
April | 5494.41 | 24-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 0.00 |
May | 6443.25 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 0.00 |
June | 6738.57 | 19-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 0.00 |
July | 7311.31 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 0.00 |
August | 6974.28 | 21-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 |
September | 7283.71 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.01 | 0.00 |
October | 6309.79 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 0.00 |
November | 5373.72 | 06-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 | 0.00 |
December | 3465.84 | 04-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2273.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7311.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.01 | 15.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4043.26 | 02-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 |
February | 4936.14 | 06-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 0.00 |
March | 6880.68 | 27-MAR-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.91 | 0.00 |
April | 6953.68 | 24-APR-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 | 0.00 |
May | 9008.53 | 22-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | 0.00 |
June | 8643.69 | 05-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.91 | 0.00 |
July | 9366.29 | 31-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 | 0.00 |
August | 8867.79 | 07-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 | 0.00 |
September | 8728.86 | 25-SEP-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.45 | 0.00 |
October | 6617.36 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
November | 5897.87 | 13-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | 0.00 |
December | 4871.77 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4043.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9366.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.91 | 14.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15381.76 | 30-JAN-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30674.96 | 06-FEB-06:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34589.29 | 28-MAR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35186.90 | 25-APR-04:52 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34778.05 | 16-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34397.43 | 07-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31425.24 | 13-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31405.33 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34110.27 | 29-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35023.14 | 31-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34472.44 | 13-NOV-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30697.59 | 11-DEC-06:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15381.76 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35186.90 | 6198.29 | 6444.06 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15105.67 | 31-JAN-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18053.13 | 06-FEB-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36822.11 | 28-MAR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36872.27 | 29-APR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38397.50 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38512.10 | 07-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36657.12 | 03-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35839.56 | 15-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38601.50 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38478.36 | 23-OCT-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37223.93 | 03-NOV-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16840.28 | 04-DEC-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15105.67 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38601.50 | 6198.29 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4101.23 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
February | 5840.75 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 0.00 |
March | 7965.13 | 26-MAR-14:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 | 0.00 |
April | 13659.86 | 30-APR-13:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 | 0.00 |
May | 14359.69 | 28-MAY-13:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 143.66 | 0.00 |
June | 13928.37 | 11-JUN-15:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 265.90 | 0.00 |
July | 15951.52 | 23-JUL-13:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 243.41 | 0.00 |
August | 16197.39 | 20-AUG-14:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 270.11 | 0.00 |
September | 15589.79 | 04-SEP-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 269.24 | 0.00 |
October | 13305.15 | 10-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 0.00 |
November | 6277.36 | 06-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.77 | 0.00 |
December | 4629.33 | 11-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4101.23 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 0.00 | |
Maximum of Months | 16197.39 | 1306.65 | 647.98 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 270.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3048.26 | 24-JAN-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
February | 4093.29 | 05-FEB-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 0.00 |
March | 7585.08 | 26-MAR-14:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 81.60 | 0.00 |
April | 12174.15 | 30-APR-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 | 0.00 |
May | 12978.36 | 07-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.14 | 0.00 |
June | 12065.41 | 11-JUN-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 135.57 | 0.00 |
July | 12854.88 | 30-JUL-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 136.07 | 0.00 |
August | 12921.57 | 27-AUG-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 86.91 | 0.00 |
September | 12427.41 | 04-SEP-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 131.33 | 0.00 |
October | 11956.92 | 29-OCT-13:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 92.51 | 0.00 |
November | 7170.97 | 05-NOV-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37.32 | 0.00 |
December | 3481.36 | 04-DEC-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3048.26 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12978.36 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 136.07 | 0.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8828.08 | 22-JAN-15:03 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
February | 17628.57 | 05-FEB-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 119.95 | 0.00 |
March | 17327.35 | 26-MAR-14:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 115.93 | 0.00 |
April | 17227.05 | 30-APR-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 200.48 | 0.00 |
May | 15795.90 | 28-MAY-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 144.39 | 0.00 |
June | 14268.49 | 26-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 0.00 |
July | 17651.24 | 23-JUL-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 244.94 | 0.00 |
August | 18201.94 | 20-AUG-14:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 266.03 | 0.00 |
September | 17634.22 | 04-SEP-15:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 264.49 | 0.00 |
October | 18665.42 | 29-OCT-13:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 110.28 | 0.00 |
November | 17641.71 | 19-NOV-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 97.64 | 0.00 |
December | 17663.72 | 03-DEC-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8828.08 | 0.00 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18665.42 | 401.76 | 223.18 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 266.03 | 8.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3744.00 | 31-JAN-16:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
February | 6227.55 | 05-FEB-14:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 100.53 | 0.00 |
March | 11968.87 | 26-MAR-14:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 0.00 |
April | 12365.01 | 30-APR-14:13 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 107.73 | 0.00 |
May | 13993.86 | 21-MAY-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 163.54 | 0.00 |
June | 13402.14 | 18-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 141.04 | 0.00 |
July | 14326.69 | 30-JUL-14:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 284.62 | 0.00 |
August | 14901.39 | 20-AUG-14:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 173.79 | 0.00 |
September | 14430.90 | 04-SEP-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 176.37 | 0.00 |
October | 13970.55 | 29-OCT-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 77.58 | 0.00 |
November | 10587.30 | 12-NOV-15:32 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 0.00 |
December | 4436.22 | 06-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3744.00 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14901.39 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 284.62 | 5.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4200.29 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 0.00 |
February | 5320.26 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 | 0.00 |
March | 6159.70 | 27-MAR-13:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 | 0.00 |
April | 6511.08 | 28-APR-12:30 | 2544.47 | 1295.96 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 0.00 |
May | 11084.39 | 12-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
June | 11198.95 | 16-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
July | 13979.62 | 30-JUL-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 198.49 | 0.00 |
August | 13787.79 | 20-AUG-14:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 149.93 | 0.00 |
September | 14224.22 | 04-SEP-15:41 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 135.84 | 0.00 |
October | 12599.22 | 08-OCT-14:32 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 | 0.00 |
November | 8697.24 | 13-NOV-07:03 | 1071.35 | 1495.52 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
December | 5813.72 | 11-DEC-07:03 | 803.52 | 1358.47 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4200.29 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14224.22 | 2544.47 | 1495.52 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 198.49 | 4.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3402.00 | 17-JAN-11:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
February | 3863.22 | 06-FEB-14:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 0.00 |
March | 5724.81 | 27-MAR-10:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 | 0.00 |
April | 10043.13 | 30-APR-11:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 27.06 | 0.00 |
May | 11337.10 | 21-MAY-11:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 95.90 | 0.00 |
June | 9876.29 | 25-JUN-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 0.00 |
July | 12094.28 | 30-JUL-11:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 | 0.00 |
August | 11599.88 | 20-AUG-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 | 0.00 |
September | 12056.39 | 04-SEP-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 63.29 | 0.00 |
October | 11227.32 | 08-OCT-11:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 31.07 | 0.00 |
November | 7812.73 | 05-NOV-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 | 0.00 |
December | 4069.71 | 04-DEC-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3402.00 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 | |
Maximum of Months | 12094.28 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11097.32 | 23-JAN-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.28 | 0.00 |
February | 13257.41 | 07-FEB-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7405.77 | 0.00 |
March | 15510.25 | 27-MAR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12164.41 | 0.00 |
April | 16880.81 | 28-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15928.69 | 0.00 |
May | 16469.50 | 09-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15259.17 | 0.00 |
June | 17349.44 | 12-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16583.32 | 0.00 |
July | 18267.35 | 21-JUL-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18701.30 | 0.00 |
August | 18582.87 | 16-AUG-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18593.37 | 0.00 |
September | 17195.68 | 05-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14588.65 | 0.00 |
October | 16024.98 | 04-OCT-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12433.30 | 0.00 |
November | 15644.59 | 19-NOV-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 55.90 | 0.00 |
December | 15600.91 | 25-DEC-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11097.32 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18582.87 | 687.71 | 647.98 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18701.30 | 1.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3691.87 | 31-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
February | 4955.78 | 06-FEB-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
March | 6975.62 | 26-MAR-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.74 | 0.00 |
April | 9783.51 | 30-APR-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 36.79 | 0.00 |
May | 11855.40 | 07-MAY-14:43 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 | 0.00 |
June | 10524.12 | 18-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 76.36 | 0.00 |
July | 12769.51 | 30-JUL-15:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 | 0.00 |
August | 12536.94 | 20-AUG-14:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 | 0.00 |
September | 13317.79 | 04-SEP-15:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 84.54 | 0.00 |
October | 12154.12 | 08-OCT-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 0.00 |
November | 9551.13 | 12-NOV-15:13 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 0.00 |
December | 4456.39 | 04-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3691.87 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13317.79 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 | 2.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4042.15 | 23-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 0.00 |
February | 5500.43 | 06-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 0.00 |
March | 6646.33 | 27-MAR-13:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 0.00 |
April | 8119.08 | 23-APR-16:02 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 119.31 | 0.00 |
May | 11194.93 | 10-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 32.92 | 0.00 |
June | 11301.86 | 02-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
July | 13454.55 | 23-JUL-13:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 207.97 | 0.00 |
August | 13877.27 | 06-AUG-16:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 181.79 | 0.00 |
September | 13577.85 | 03-SEP-16:12 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 238.86 | 0.00 |
October | 13393.42 | 09-OCT-15:52 | 401.76 | 237.04 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 209.15 | 0.00 |
November | 7259.56 | 20-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 |
December | 4582.11 | 11-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4042.15 | 0.00 | 178.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 | |
Maximum of Months | 13877.27 | 1306.65 | 647.98 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 238.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3171.17 | 24-JAN-11:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
February | 3766.73 | 06-FEB-14:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | 0.00 |
March | 6721.12 | 26-MAR-11:13 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 0.00 |
April | 10148.93 | 23-APR-11:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 0.00 |
May | 12121.23 | 07-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 | 0.00 |
June | 11381.16 | 25-JUN-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 0.00 |
July | 11849.19 | 30-JUL-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 132.87 | 0.00 |
August | 12201.70 | 13-AUG-10:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 178.98 | 0.00 |
September | 12305.53 | 04-SEP-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 98.46 | 0.00 |
October | 11887.23 | 09-OCT-10:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 0.00 |
November | 7481.87 | 05-NOV-11:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 33.18 | 0.00 |
December | 3600.84 | 04-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3171.17 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12305.53 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 178.98 | 0.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7739.21 | 23-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 16.79 | 0.00 |
February | 12141.92 | 05-FEB-12:23 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 90.86 | 0.00 |
March | 15359.13 | 26-MAR-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 78.93 | 0.00 |
April | 12641.00 | 23-APR-16:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 118.54 | 0.00 |
May | 12369.98 | 28-MAY-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 121.11 | 0.00 |
June | 12296.55 | 16-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 0.00 |
July | 15091.35 | 23-JUL-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 209.26 | 0.00 |
August | 15567.49 | 06-AUG-16:51 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 182.78 | 0.00 |
September | 15972.35 | 03-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 184.54 | 0.00 |
October | 16327.30 | 29-OCT-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 80.49 | 0.00 |
November | 16008.92 | 05-NOV-11:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 0.00 |
December | 15629.65 | 03-DEC-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7739.21 | 0.00 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 0.00 | |
Maximum of Months | 16327.30 | 1272.23 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 209.26 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3699.68 | 31-JAN-16:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 |
February | 5607.53 | 05-FEB-15:43 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 78.83 | 0.00 |
March | 11409.16 | 26-MAR-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 0.00 |
April | 12657.26 | 23-APR-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 0.00 |
May | 12439.10 | 21-MAY-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 164.17 | 0.00 |
June | 12040.38 | 18-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 118.64 | 0.00 |
July | 12508.71 | 23-JUL-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 99.35 | 0.00 |
August | 13582.31 | 06-AUG-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 113.15 | 0.00 |
September | 13338.02 | 03-SEP-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 145.27 | 0.00 |
October | 13102.38 | 09-OCT-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 127.88 | 0.00 |
November | 12312.98 | 05-NOV-15:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 | 0.00 |
December | 4305.34 | 06-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3699.68 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13582.31 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 164.17 | 4.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.128830E+12 | 112127.87 | 30-JAN-16:00 | 0.00 | 0.00 |
February | 0.121928E+12 | 135316.75 | 06-FEB-15:09 | 0.00 | 0.00 |
March | 0.148649E+12 | 156639.38 | 27-MAR-10:00 | 0.00 | 0.00 |
April | 0.152436E+12 | 165719.64 | 28-APR-12:09 | 0.00 | 0.00 |
May | 0.194368E+12 | 187458.43 | 30-MAY-14:00 | 0.00 | 0.00 |
June | 0.211133E+12 | 193837.94 | 12-JUN-10:00 | 0.00 | 0.00 |
July | 0.231266E+12 | 200359.91 | 21-JUL-14:09 | 0.00 | 0.00 |
August | 0.250521E+12 | 211985.66 | 10-AUG-15:39 | 0.00 | 0.00 |
September | 0.207182E+12 | 191655.43 | 05-SEP-15:30 | 0.00 | 0.00 |
October | 0.185124E+12 | 168687.59 | 06-OCT-15:20 | 0.00 | 0.00 |
November | 0.155808E+12 | 157566.79 | 01-NOV-14:09 | 0.00 | 0.00 |
December | 0.134453E+12 | 128898.24 | 05-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.212170E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.121928E+12 | 112127.87 | 0.00 | 0.00 | |
Maximum of Months | 0.250521E+12 | 211985.66 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.254616E+11 | 0.507020E+10 | 0.605851E+11 | 0.225886E+10 | 0.691069E+10 | 12379742.02 | 0.225523E+09 | 0.247586E+11 | 0.00 | 0.00 | 0.00 | 0.354662E+10 | 0.00 |
February | 0.229004E+11 | 0.427755E+10 | 0.548702E+11 | 0.204962E+10 | 0.729895E+10 | 11196021.66 | 0.132710E+09 | 0.272475E+11 | 0.00 | 0.00 | 0.00 | 0.314025E+10 | 0.00 |
March | 0.271220E+11 | 0.435515E+10 | 0.627783E+11 | 0.235661E+10 | 0.102079E+11 | 12675672.10 | 49468461.74 | 0.383036E+11 | 0.00 | 0.00 | 0.00 | 0.346325E+10 | 0.00 |
April | 0.239857E+11 | 0.382924E+10 | 0.586172E+11 | 0.219345E+10 | 0.119202E+11 | 11960507.72 | 1014905.61 | 0.490311E+11 | 0.00 | 0.00 | 0.00 | 0.284636E+10 | 0.00 |
May | 0.257284E+11 | 0.363967E+10 | 0.616817E+11 | 0.230738E+10 | 0.184669E+11 | 12527707.06 | 0.00 | 0.797829E+11 | 0.00 | 0.00 | 0.00 | 0.274844E+10 | 0.00 |
June | 0.255635E+11 | 0.340476E+10 | 0.604966E+11 | 0.226958E+10 | 0.200964E+11 | 12231776.97 | 0.00 | 0.967826E+11 | 0.00 | 0.00 | 0.00 | 0.250729E+10 | 0.00 |
July | 0.239697E+11 | 0.358307E+10 | 0.597911E+11 | 0.223042E+10 | 0.208081E+11 | 12256437.81 | 0.00 | 0.118551E+12 | 0.00 | 0.00 | 0.00 | 0.231984E+10 | 0.00 |
August | 0.267986E+11 | 0.383930E+10 | 0.627783E+11 | 0.235642E+10 | 0.227106E+11 | 12675672.10 | 0.00 | 0.129382E+12 | 0.00 | 0.00 | 0.00 | 0.264318E+10 | 0.00 |
September | 0.240082E+11 | 0.401557E+10 | 0.585950E+11 | 0.219222E+10 | 0.184689E+11 | 11960507.72 | 0.00 | 0.972740E+11 | 0.00 | 0.00 | 0.00 | 0.261662E+10 | 0.00 |
October | 0.251091E+11 | 0.454821E+10 | 0.605962E+11 | 0.225944E+10 | 0.160501E+11 | 12379742.02 | 0.00 | 0.735519E+11 | 0.00 | 0.00 | 0.00 | 0.299659E+10 | 0.00 |
November | 0.250751E+11 | 0.480143E+10 | 0.591197E+11 | 0.220143E+10 | 0.122717E+11 | 12059151.09 | 0.00 | 0.491029E+11 | 0.00 | 0.00 | 0.00 | 0.322366E+10 | 0.00 |
December | 0.247109E+11 | 0.518961E+10 | 0.597800E+11 | 0.223011E+10 | 0.815750E+10 | 12256437.81 | 46234839.37 | 0.309306E+11 | 0.00 | 0.00 | 0.00 | 0.339599E+10 | 0.00 |
Annual Sum or Average | 0.300433E+12 | 0.505538E+11 | 0.719689E+12 | 0.269055E+11 | 0.173368E+12 | 0.146559E+09 | 0.454951E+09 | 0.814699E+12 | 0.00 | 0.00 | 0.00 | 0.354481E+11 | 0.00 |
Minimum of Months | 0.229004E+11 | 0.340476E+10 | 0.548702E+11 | 0.204962E+10 | 0.691069E+10 | 11196021.66 | 0.00 | 0.247586E+11 | 0.00 | 0.00 | 0.00 | 0.231984E+10 | 0.00 |
Maximum of Months | 0.271220E+11 | 0.518961E+10 | 0.627783E+11 | 0.235661E+10 | 0.227106E+11 | 12675672.10 | 0.225523E+09 | 0.129382E+12 | 0.00 | 0.00 | 0.00 | 0.354662E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29780.74 | 23-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 03-JAN-08:20 | 10474.72 | 17-JAN-15:09 | 6.85 | 01-JAN-06:10 | 6545.09 | 20-JAN-07:30 |
February | 30491.21 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:20 | 16728.84 | 06-FEB-15:50 | 6.85 | 01-FEB-06:10 | 5912.83 | 01-FEB-07:19 |
March | 32642.50 | 14-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 20910.25 | 27-MAR-15:30 | 6.85 | 27-MAR-12:09 | 4831.92 | 07-MAR-07:19 |
April | 30491.18 | 18-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 26-APR-11:09 | 22920.25 | 24-APR-14:00 | 6.85 | 28-APR-11:09 | 517.63 | 05-APR-06:00 |
May | 26300.01 | 23-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 04-MAY-12:09 | 25924.86 | 30-MAY-15:30 | 6.85 | 04-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 26426.34 | 08-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-11:09 | 25632.99 | 12-JUN-15:20 | 6.85 | 01-JUN-11:09 | 0.00 | 01-JUN-00:10 |
July | 28740.43 | 20-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-12:09 | 26224.34 | 31-JUL-15:20 | 6.85 | 03-JUL-12:09 | 0.00 | 01-JUL-00:10 |
August | 26945.64 | 29-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 03-AUG-16:10 | 24640.92 | 07-AUG-15:30 | 6.85 | 01-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 27008.81 | 06-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-16:10 | 26454.56 | 05-SEP-15:30 | 6.85 | 04-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 27939.54 | 25-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 21496.40 | 10-OCT-15:09 | 6.85 | 04-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 31087.65 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-16:10 | 18300.62 | 06-NOV-15:09 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 31791.75 | 14-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 26-DEC-08:09 | 14735.25 | 04-DEC-15:09 | 6.85 | 01-DEC-06:10 | 4203.16 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26300.01 | 5686.19 | 41699.26 | 1410.29 | 10474.72 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 26454.56 | 6.85 | 6545.09 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 31086.24 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4616.85 | 11-JAN-12:50 | 0.00 |
February | 47540.95 | 07-FEB-15:50 | 0.00 | 0.00 | 0.00 | 4608.11 | 01-FEB-12:30 | 0.00 |
March | 65838.68 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 4569.17 | 01-MAR-12:39 | 0.00 |
April | 78348.68 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 4129.79 | 03-APR-11:50 | 0.00 |
May | 91277.95 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 3543.87 | 01-MAY-11:00 | 0.00 |
June | 100101.26 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 | 3204.29 | 01-JUN-11:30 | 0.00 |
July | 106230.66 | 21-JUL-13:00 | 0.00 | 0.00 | 0.00 | 3183.52 | 31-JUL-11:39 | 0.00 |
August | 116549.45 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 3447.46 | 30-AUG-11:20 | 0.00 |
September | 98205.94 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 3831.42 | 29-SEP-11:39 | 0.00 |
October | 77394.19 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 | 4214.20 | 31-OCT-11:39 | 0.00 |
November | 69844.95 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4574.23 | 28-NOV-12:30 | 0.00 |
December | 43970.67 | 05-DEC-15:09 | 0.00 | 0.00 | 0.00 | 4612.44 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31086.24 | 0.00 | 0.00 | 0.00 | 3183.52 | 0.00 | ||
Maximum of Months | 116549.45 | 0.00 | 0.00 | 0.00 | 4616.85 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 112127.87 | 30-JAN-16:00 | 29780.74 | 41670.51 | 0.00 | 1410.29 | 7659.94 | 6.85 | 0.00 | 28057.44 | 0.00 |
February | 135316.75 | 06-FEB-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 16516.48 | 6.85 | 0.00 | 47473.35 | 0.00 |
March | 156639.38 | 27-MAR-10:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 18735.05 | 6.85 | 0.00 | 65838.68 | 0.00 |
April | 165719.64 | 28-APR-12:09 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 17956.58 | 6.85 | 0.00 | 78348.68 | 0.00 |
May | 187458.43 | 30-MAY-14:00 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 25480.29 | 6.85 | 0.00 | 91277.95 | 0.00 |
June | 193837.94 | 12-JUN-10:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 24186.31 | 6.85 | 0.00 | 98325.70 | 0.00 |
July | 200359.91 | 21-JUL-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 23585.24 | 6.85 | 0.00 | 106162.16 | 0.00 |
August | 211985.66 | 10-AUG-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 24244.38 | 6.85 | 0.00 | 116504.31 | 0.00 |
September | 191655.43 | 05-SEP-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 26454.56 | 6.85 | 0.00 | 93871.53 | 0.00 |
October | 168687.59 | 06-OCT-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 19673.75 | 6.85 | 0.00 | 77367.47 | 0.00 |
November | 157566.79 | 01-NOV-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 16477.05 | 6.85 | 0.00 | 69788.85 | 0.00 |
December | 128898.24 | 05-DEC-15:09 | 25887.39 | 41659.26 | 0.00 | 1410.29 | 13154.18 | 6.85 | 0.00 | 43970.67 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112127.87 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 7659.94 | 6.85 | 0.00 | 28057.44 | 0.00 | |
Maximum of Months | 211985.66 | 29780.74 | 41670.51 | 0.00 | 1410.29 | 26454.56 | 6.85 | 0.00 | 116504.31 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.26 | 0.00 | 26.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.27 | 0.00 | 26.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 26.24 | 0.00 | 26.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.27 | 0.00 | 26.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.41 | 1.83 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.68 | 8.33 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.72 | 7.83 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.65 | 12.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.66 | 8.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.66 | 8.17 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.51 | 5.17 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 76.33 | 27.65 | 52.00 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.72 | 12.50 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.41 | 1.33 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.63 | 7.00 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.97 | 11.33 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 28.00 | 9.00 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.94 | 14.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.93 | 9.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.95 | 11.33 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.69 | 11.83 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 97.67 | 27.89 | 76.67 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 28.00 | 14.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 1.50 | 27.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.67 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.57 | 5.50 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.72 | 7.83 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.73 | 6.67 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.70 | 11.33 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.78 | 8.00 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.96 | 9.17 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.04 | 10.83 | 28.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.80 | 8.67 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.74 | 2.00 | 27.74 |
Annual Sum or Average | 0.00 | 0.00 | 95.00 | 27.80 | 73.17 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28.04 | 11.33 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.82 | 0.83 | 27.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.80 | 4.33 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.01 | 8.00 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.98 | 7.17 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.96 | 12.00 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.99 | 8.17 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.07 | 7.83 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.95 | 6.67 | 27.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.63 | 2.33 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 90.83 | 27.96 | 57.67 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 28.07 | 12.00 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.42 | 2.83 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.44 | 6.00 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.41 | 10.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.28 | 7.17 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.45 | 7.17 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.29 | 2.67 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 50.50 | 27.38 | 36.00 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.45 | 10.17 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 2.67 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.65 | 11.00 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.67 | 8.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.68 | 13.67 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.51 | 9.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.70 | 11.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.52 | 12.33 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.31 | 1.83 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 89.67 | 27.61 | 70.83 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.70 | 13.67 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.35 | 0.83 | 20.35 | 1.00 | 22.95 | 1.00 | 24.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.38 | 2.33 | 26.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.81 | 7.50 | 25.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 25.69 | 13.67 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 25.91 | 46.33 | 25.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 26.20 | 53.33 | 26.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 | 26.54 | 60.33 | 26.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 76.00 | 26.58 | 68.33 | 26.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 26.44 | 58.00 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 26.12 | 55.50 | 26.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.19 | 26.00 | 26.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.54 | 4.50 | 27.54 |
Annual Sum or Average | 0.83 | 20.35 | 0.83 | 20.35 | 420.17 | 26.28 | 396.83 | 26.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.95 | 1.00 | 24.13 |
Maximum of Months | 0.83 | 20.35 | 0.83 | 20.35 | 76.00 | 27.54 | 68.33 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.67 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.52 | 2.67 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.79 | 5.83 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.72 | 5.67 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.66 | 10.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.51 | 8.33 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.72 | 8.00 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.69 | 6.83 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.55 | 2.67 | 27.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 84.00 | 27.65 | 50.83 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.79 | 10.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.49 | 7.17 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.53 | 6.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.48 | 11.33 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.45 | 7.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.50 | 7.33 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 2.67 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 58.33 | 27.48 | 43.00 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.53 | 11.33 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.57 | 4.83 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.78 | 11.83 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.79 | 9.33 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.82 | 14.00 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.82 | 9.00 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.81 | 11.17 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.60 | 9.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 82.33 | 27.76 | 71.00 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.82 | 14.00 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.67 | 1.33 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.48 | 3.33 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.52 | 7.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.48 | 6.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.51 | 10.17 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.59 | 7.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.80 | 9.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.89 | 11.00 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.74 | 8.50 | 27.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.63 | 2.67 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 82.50 | 27.65 | 68.83 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.89 | 11.00 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.67 | 0.67 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.71 | 3.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.95 | 6.33 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.86 | 6.17 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.87 | 10.50 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.84 | 7.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.96 | 6.83 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.85 | 5.83 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 72.00 | 27.86 | 49.17 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.96 | 10.50 | 28.00 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 379.00 | 24.65 | 0.00 | 24.65 |
February | 0.00 | 0.00 | 397.00 | 24.58 | 0.00 | 24.58 |
March | 0.00 | 0.00 | 439.00 | 24.53 | 0.00 | 24.53 |
April | 0.00 | 0.00 | 468.67 | 24.48 | 0.00 | 24.48 |
May | 0.00 | 0.00 | 501.33 | 24.46 | 0.00 | 24.46 |
June | 0.00 | 0.00 | 496.00 | 24.43 | 0.00 | 24.43 |
July | 0.00 | 0.00 | 497.00 | 24.42 | 0.00 | 24.42 |
August | 0.00 | 0.00 | 514.00 | 24.34 | 0.00 | 24.34 |
September | 0.00 | 0.00 | 485.00 | 24.44 | 0.00 | 24.44 |
October | 0.00 | 0.00 | 494.00 | 24.50 | 0.00 | 24.50 |
November | 0.00 | 0.00 | 484.00 | 24.52 | 0.00 | 24.52 |
December | 0.00 | 0.00 | 449.50 | 24.55 | 0.00 | 24.55 |
Annual Sum or Average | 0.00 | 5604.50 | 24.48 | 0.00 | 24.48 | |
Minimum of Months | 0.00 | 0.00 | 379.00 | 24.34 | 0.00 | 24.34 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.65 | 0.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.83 | 23.51 | 180.83 | 24.05 | 0.00 | 24.05 |
February | 45.83 | 23.54 | 255.33 | 24.25 | 0.00 | 24.25 |
March | 21.00 | 23.59 | 326.67 | 24.32 | 0.00 | 24.32 |
April | 4.50 | 23.74 | 407.67 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 488.83 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 496.00 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 514.00 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 485.00 | 24.35 | 0.00 | 24.35 |
October | 0.00 | 0.00 | 484.17 | 24.38 | 0.00 | 24.38 |
November | 0.33 | 23.76 | 456.50 | 24.34 | 0.00 | 24.34 |
December | 46.33 | 23.52 | 286.83 | 24.22 | 0.00 | 24.22 |
Annual Sum or Average | 217.83 | 23.53 | 4878.83 | 24.30 | 0.00 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 180.83 | 24.05 | 0.00 | 24.05 |
Maximum of Months | 99.83 | 23.76 | 514.00 | 24.38 | 0.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.33 | 23.29 | 90.50 | 23.51 | 0.00 | 23.51 |
February | 142.67 | 23.33 | 170.00 | 23.81 | 0.00 | 23.81 |
March | 83.17 | 23.42 | 263.17 | 24.07 | 0.00 | 24.07 |
April | 13.67 | 23.45 | 382.00 | 24.30 | 0.00 | 24.30 |
May | 0.00 | 0.00 | 484.67 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 496.17 | 24.37 | 0.00 | 24.37 |
August | 0.00 | 0.00 | 514.00 | 24.30 | 0.00 | 24.30 |
September | 0.50 | 26.62 | 485.00 | 24.38 | 0.50 | 24.38 |
October | 0.00 | 0.00 | 478.67 | 24.38 | 0.00 | 24.38 |
November | 9.00 | 23.50 | 391.00 | 24.28 | 0.00 | 24.28 |
December | 158.17 | 23.30 | 183.50 | 23.77 | 0.00 | 23.77 |
Annual Sum or Average | 647.50 | 23.32 | 4434.67 | 24.20 | 0.50 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 90.50 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 240.33 | 26.62 | 514.00 | 24.38 | 0.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 316.17 | 22.80 | 84.83 | 23.08 | 0.00 | 23.08 |
February | 197.83 | 22.96 | 165.83 | 23.53 | 0.00 | 23.53 |
March | 125.17 | 23.13 | 268.67 | 23.90 | 0.00 | 23.90 |
April | 41.67 | 23.88 | 388.83 | 24.38 | 9.00 | 24.42 |
May | 35.67 | 26.84 | 500.50 | 24.71 | 35.67 | 24.84 |
June | 49.50 | 26.66 | 496.00 | 24.74 | 49.50 | 24.90 |
July | 71.67 | 26.82 | 497.00 | 24.95 | 71.67 | 25.16 |
August | 49.17 | 26.77 | 514.00 | 24.74 | 49.17 | 24.90 |
September | 55.17 | 26.61 | 485.00 | 24.79 | 55.17 | 24.96 |
October | 40.83 | 26.30 | 484.50 | 24.66 | 38.33 | 24.79 |
November | 41.50 | 23.30 | 374.50 | 24.24 | 0.33 | 24.24 |
December | 218.83 | 22.95 | 170.17 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 1243.17 | 23.88 | 4429.83 | 24.35 | 308.83 | 24.47 |
Minimum of Months | 35.67 | 22.80 | 84.83 | 23.08 | 0.00 | 23.08 |
Maximum of Months | 316.17 | 26.84 | 514.00 | 24.95 | 71.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.00 | 22.76 | 138.33 | 23.30 | 0.00 | 23.30 |
February | 162.00 | 22.88 | 211.67 | 23.70 | 0.00 | 23.70 |
March | 112.33 | 23.09 | 311.50 | 24.00 | 1.50 | 24.01 |
April | 60.33 | 25.07 | 413.83 | 24.58 | 33.00 | 24.72 |
May | 49.83 | 26.93 | 503.67 | 24.79 | 49.83 | 24.97 |
June | 53.17 | 26.81 | 496.00 | 24.78 | 53.17 | 24.95 |
July | 76.17 | 26.94 | 497.00 | 24.99 | 76.17 | 25.22 |
August | 55.67 | 26.90 | 514.00 | 24.78 | 55.67 | 24.97 |
September | 62.33 | 26.81 | 485.00 | 24.86 | 62.33 | 25.06 |
October | 56.83 | 26.68 | 492.00 | 24.80 | 55.67 | 24.98 |
November | 33.50 | 23.50 | 399.00 | 24.36 | 3.00 | 24.38 |
December | 181.83 | 22.90 | 213.00 | 23.62 | 0.00 | 23.62 |
Annual Sum or Average | 1155.00 | 24.23 | 4675.00 | 24.46 | 390.33 | 24.61 |
Minimum of Months | 33.50 | 22.76 | 138.33 | 23.30 | 0.00 | 23.30 |
Maximum of Months | 251.00 | 26.94 | 514.00 | 24.99 | 76.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 212.50 | 22.89 | 212.67 | 23.71 | 0.83 | 23.72 |
February | 143.17 | 23.10 | 239.83 | 23.93 | 6.00 | 23.98 |
March | 111.33 | 23.28 | 312.17 | 24.08 | 6.17 | 24.12 |
April | 59.17 | 24.56 | 397.50 | 24.48 | 23.67 | 24.59 |
May | 34.17 | 26.83 | 494.83 | 24.69 | 34.17 | 24.82 |
June | 42.00 | 26.61 | 496.00 | 24.69 | 42.00 | 24.83 |
July | 62.50 | 26.80 | 497.00 | 24.90 | 62.50 | 25.09 |
August | 48.67 | 26.81 | 514.00 | 24.74 | 48.67 | 24.90 |
September | 58.50 | 26.74 | 485.00 | 24.84 | 58.50 | 25.02 |
October | 58.83 | 26.74 | 491.50 | 24.84 | 57.17 | 25.03 |
November | 58.17 | 25.37 | 415.50 | 24.64 | 33.50 | 24.79 |
December | 151.17 | 23.26 | 271.00 | 24.06 | 11.17 | 24.13 |
Annual Sum or Average | 1040.17 | 24.38 | 4827.00 | 24.51 | 384.33 | 24.65 |
Minimum of Months | 34.17 | 22.89 | 212.67 | 23.71 | 0.83 | 23.72 |
Maximum of Months | 212.50 | 26.83 | 514.00 | 24.90 | 62.50 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 307.83 | 22.58 | 121.00 | 23.07 | 0.00 | 23.07 |
February | 199.00 | 22.75 | 183.83 | 23.48 | 0.83 | 23.49 |
March | 141.17 | 23.00 | 287.33 | 23.88 | 3.50 | 23.91 |
April | 70.00 | 24.21 | 387.00 | 24.43 | 23.33 | 24.54 |
May | 39.00 | 26.88 | 491.00 | 24.73 | 38.67 | 24.88 |
June | 55.67 | 26.80 | 496.00 | 24.77 | 55.67 | 24.95 |
July | 70.33 | 26.91 | 497.00 | 24.93 | 70.33 | 25.15 |
August | 57.17 | 26.87 | 514.00 | 24.77 | 57.17 | 24.96 |
September | 60.33 | 26.73 | 484.67 | 24.82 | 60.33 | 25.01 |
October | 45.50 | 26.29 | 474.83 | 24.69 | 40.83 | 24.83 |
November | 67.83 | 23.58 | 368.83 | 24.27 | 9.50 | 24.32 |
December | 229.50 | 22.74 | 189.33 | 23.44 | 0.00 | 23.44 |
Annual Sum or Average | 1343.33 | 23.83 | 4494.83 | 24.35 | 360.17 | 24.49 |
Minimum of Months | 39.00 | 22.58 | 121.00 | 23.07 | 0.00 | 23.07 |
Maximum of Months | 307.83 | 26.91 | 514.00 | 24.93 | 70.33 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.83 | 23.46 | 162.67 | 23.84 | 0.00 | 23.84 |
February | 78.67 | 23.38 | 239.50 | 24.04 | 0.00 | 24.04 |
March | 62.83 | 23.44 | 314.33 | 24.13 | 0.00 | 24.13 |
April | 10.17 | 23.45 | 416.50 | 24.36 | 0.00 | 24.36 |
May | 16.17 | 26.83 | 506.83 | 24.60 | 16.17 | 24.66 |
June | 32.33 | 26.73 | 496.00 | 24.67 | 32.33 | 24.79 |
July | 53.00 | 26.80 | 497.00 | 24.86 | 53.00 | 25.03 |
August | 35.67 | 26.81 | 514.00 | 24.68 | 35.67 | 24.81 |
September | 38.83 | 26.77 | 485.00 | 24.75 | 38.83 | 24.89 |
October | 27.33 | 26.58 | 499.17 | 24.68 | 27.33 | 24.78 |
November | 0.00 | 0.00 | 477.00 | 24.44 | 0.00 | 24.44 |
December | 41.00 | 23.51 | 335.67 | 24.19 | 0.00 | 24.19 |
Annual Sum or Average | 540.83 | 24.69 | 4943.67 | 24.50 | 203.33 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 162.67 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 144.83 | 26.83 | 514.00 | 24.86 | 53.00 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.00 | 23.37 | 248.83 | 24.06 | 0.00 | 24.06 |
February | 57.83 | 23.29 | 285.83 | 24.19 | 0.00 | 24.19 |
March | 50.83 | 23.31 | 365.17 | 24.20 | 0.00 | 24.20 |
April | 16.33 | 25.04 | 447.00 | 24.49 | 7.67 | 24.53 |
May | 43.67 | 26.88 | 508.00 | 24.76 | 43.67 | 24.92 |
June | 43.00 | 26.86 | 496.00 | 24.75 | 43.00 | 24.90 |
July | 67.00 | 26.91 | 497.00 | 24.95 | 67.00 | 25.15 |
August | 50.33 | 26.92 | 514.00 | 24.76 | 50.33 | 24.94 |
September | 57.17 | 26.88 | 485.00 | 24.87 | 57.17 | 25.06 |
October | 50.83 | 26.80 | 502.00 | 24.84 | 50.83 | 25.00 |
November | 4.50 | 27.13 | 484.00 | 24.55 | 4.50 | 24.57 |
December | 32.83 | 23.43 | 371.00 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 573.33 | 25.35 | 5203.83 | 24.60 | 324.17 | 24.73 |
Minimum of Months | 4.50 | 23.29 | 248.83 | 24.06 | 0.00 | 24.06 |
Maximum of Months | 99.00 | 27.13 | 514.00 | 24.95 | 67.00 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.33 | 22.62 | 311.67 | 24.18 | 2.33 | 24.18 |
February | 58.50 | 22.94 | 336.33 | 24.24 | 10.17 | 24.26 |
March | 66.50 | 22.98 | 372.17 | 24.19 | 13.83 | 24.19 |
April | 36.83 | 23.59 | 426.33 | 24.42 | 20.00 | 24.41 |
May | 51.50 | 25.47 | 504.50 | 24.75 | 51.50 | 24.81 |
June | 123.17 | 25.31 | 496.00 | 24.85 | 123.17 | 24.93 |
July | 176.00 | 25.51 | 497.00 | 25.05 | 176.00 | 25.15 |
August | 175.83 | 25.65 | 514.00 | 25.06 | 175.83 | 25.18 |
September | 150.33 | 25.79 | 485.00 | 25.08 | 150.33 | 25.22 |
October | 122.33 | 25.79 | 502.00 | 25.03 | 122.33 | 25.16 |
November | 71.50 | 25.61 | 483.67 | 24.78 | 69.67 | 24.89 |
December | 57.50 | 23.84 | 406.33 | 24.46 | 25.83 | 24.52 |
Annual Sum or Average | 1166.33 | 24.98 | 5335.00 | 24.74 | 941.00 | 24.84 |
Minimum of Months | 36.83 | 22.62 | 311.67 | 24.18 | 2.33 | 24.18 |
Maximum of Months | 176.00 | 25.79 | 514.00 | 25.08 | 176.00 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.50 | 23.31 | 229.00 | 23.95 | 0.00 | 23.95 |
February | 70.67 | 23.24 | 282.67 | 24.11 | 0.00 | 24.11 |
March | 54.33 | 23.34 | 356.33 | 24.21 | 0.67 | 24.22 |
April | 19.83 | 24.79 | 427.67 | 24.47 | 8.17 | 24.51 |
May | 26.00 | 26.95 | 506.83 | 24.67 | 26.00 | 24.77 |
June | 47.50 | 26.88 | 496.00 | 24.77 | 47.50 | 24.94 |
July | 65.83 | 26.89 | 497.00 | 24.93 | 65.83 | 25.14 |
August | 54.33 | 26.92 | 514.00 | 24.78 | 54.33 | 24.96 |
September | 56.00 | 26.91 | 485.00 | 24.86 | 56.00 | 25.06 |
October | 37.83 | 26.79 | 502.00 | 24.77 | 37.83 | 24.90 |
November | 8.83 | 26.96 | 482.83 | 24.54 | 8.83 | 24.58 |
December | 45.00 | 23.37 | 354.67 | 24.24 | 0.00 | 24.24 |
Annual Sum or Average | 614.67 | 25.08 | 5134.00 | 24.57 | 305.17 | 24.69 |
Minimum of Months | 8.83 | 23.24 | 229.00 | 23.95 | 0.00 | 23.95 |
Maximum of Months | 128.50 | 26.96 | 514.00 | 24.93 | 65.83 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.67 | 23.25 | 118.83 | 23.54 | 0.00 | 23.54 |
February | 121.83 | 23.28 | 211.17 | 23.88 | 0.00 | 23.88 |
March | 70.50 | 23.39 | 309.17 | 24.12 | 0.00 | 24.12 |
April | 17.50 | 24.40 | 420.33 | 24.43 | 5.83 | 24.46 |
May | 32.17 | 26.80 | 506.50 | 24.69 | 32.17 | 24.81 |
June | 45.33 | 26.62 | 496.00 | 24.72 | 45.33 | 24.87 |
July | 65.83 | 26.77 | 497.00 | 24.92 | 65.83 | 25.12 |
August | 44.50 | 26.71 | 514.00 | 24.71 | 44.50 | 24.86 |
September | 52.67 | 26.59 | 485.00 | 24.78 | 52.67 | 24.94 |
October | 33.00 | 26.44 | 490.33 | 24.66 | 33.00 | 24.76 |
November | 7.00 | 23.50 | 430.33 | 24.35 | 0.17 | 24.35 |
December | 138.17 | 23.33 | 234.83 | 23.88 | 0.00 | 23.88 |
Annual Sum or Average | 866.17 | 24.38 | 4713.50 | 24.46 | 279.50 | 24.57 |
Minimum of Months | 7.00 | 23.25 | 118.83 | 23.54 | 0.00 | 23.54 |
Maximum of Months | 237.67 | 26.80 | 514.00 | 24.92 | 65.83 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.50 | 23.13 | 128.83 | 23.65 | 0.17 | 23.65 |
February | 108.83 | 23.14 | 190.00 | 23.97 | 0.00 | 23.97 |
March | 70.67 | 23.30 | 270.83 | 24.19 | 1.00 | 24.20 |
April | 35.50 | 25.61 | 363.50 | 24.69 | 23.50 | 24.81 |
May | 50.67 | 26.88 | 430.00 | 24.92 | 50.67 | 25.10 |
June | 50.33 | 26.78 | 418.00 | 24.89 | 50.33 | 25.07 |
July | 71.17 | 26.90 | 422.00 | 25.11 | 71.17 | 25.34 |
August | 49.83 | 26.85 | 433.00 | 24.88 | 49.83 | 25.06 |
September | 60.17 | 26.78 | 410.00 | 24.98 | 60.17 | 25.18 |
October | 51.83 | 26.73 | 423.17 | 24.91 | 51.83 | 25.09 |
November | 10.67 | 24.30 | 371.17 | 24.52 | 2.83 | 24.54 |
December | 118.33 | 23.19 | 209.33 | 23.94 | 0.00 | 23.94 |
Annual Sum or Average | 869.50 | 24.69 | 4069.83 | 24.63 | 361.50 | 24.78 |
Minimum of Months | 10.67 | 23.13 | 128.83 | 23.65 | 0.00 | 23.65 |
Maximum of Months | 191.50 | 26.90 | 433.00 | 25.11 | 71.17 | 25.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.00 | 23.27 | 251.33 | 24.09 | 0.83 | 24.10 |
February | 78.17 | 23.44 | 285.83 | 24.23 | 5.17 | 24.27 |
March | 59.67 | 23.60 | 351.33 | 24.27 | 4.17 | 24.30 |
April | 25.00 | 25.16 | 425.67 | 24.51 | 13.33 | 24.58 |
May | 31.83 | 26.79 | 505.83 | 24.68 | 31.83 | 24.79 |
June | 39.00 | 26.56 | 496.00 | 24.67 | 39.00 | 24.80 |
July | 59.00 | 26.74 | 497.00 | 24.88 | 59.00 | 25.06 |
August | 44.17 | 26.75 | 514.00 | 24.72 | 44.17 | 24.87 |
September | 56.00 | 26.75 | 485.00 | 24.83 | 56.00 | 25.01 |
October | 57.17 | 26.84 | 498.00 | 24.85 | 57.17 | 25.04 |
November | 36.67 | 26.64 | 458.67 | 24.70 | 33.83 | 24.84 |
December | 81.33 | 23.81 | 325.67 | 24.37 | 12.67 | 24.44 |
Annual Sum or Average | 701.00 | 25.05 | 5094.33 | 24.60 | 357.17 | 24.73 |
Minimum of Months | 25.00 | 23.27 | 251.33 | 24.09 | 0.83 | 24.10 |
Maximum of Months | 133.00 | 26.84 | 514.00 | 24.88 | 59.00 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 235.33 | 23.02 | 161.50 | 23.53 | 0.00 | 23.53 |
February | 128.33 | 23.06 | 230.33 | 23.86 | 0.33 | 23.86 |
March | 82.67 | 23.29 | 330.50 | 24.13 | 2.83 | 24.15 |
April | 38.17 | 24.95 | 417.50 | 24.51 | 19.00 | 24.60 |
May | 34.33 | 26.89 | 503.17 | 24.70 | 34.33 | 24.84 |
June | 52.50 | 26.76 | 496.00 | 24.76 | 52.50 | 24.93 |
July | 71.17 | 26.87 | 497.00 | 24.94 | 71.17 | 25.16 |
August | 55.50 | 26.82 | 514.00 | 24.77 | 55.50 | 24.95 |
September | 56.17 | 26.71 | 485.00 | 24.81 | 56.17 | 24.99 |
October | 37.67 | 26.64 | 490.67 | 24.69 | 37.33 | 24.82 |
November | 22.00 | 24.45 | 424.33 | 24.41 | 7.33 | 24.45 |
December | 149.83 | 23.10 | 249.33 | 23.84 | 0.00 | 23.84 |
Annual Sum or Average | 963.67 | 24.37 | 4799.33 | 24.48 | 336.50 | 24.60 |
Minimum of Months | 22.00 | 23.02 | 161.50 | 23.53 | 0.00 | 23.53 |
Maximum of Months | 235.33 | 26.89 | 514.00 | 24.94 | 71.17 | 25.16 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.49844 | 42.35298 | 0.52166 | 10.99888 |
February | 454.00000 | 24.50846 | 45.45282 | 0.54974 | 11.64796 |
March | 514.00000 | 24.44951 | 45.09364 | 0.54346 | 11.48289 |
April | 485.00000 | 24.46924 | 47.81137 | 0.57648 | 12.29142 |
May | 508.00000 | 24.45540 | 50.05333 | -0.2309 | 6.72655 |
June | 496.00000 | 24.42568 | 53.01931 | -0.2149 | 6.57186 |
July | 497.00000 | 24.41763 | 52.56484 | -0.2225 | 6.47992 |
August | 514.00000 | 24.33651 | 52.68710 | -0.2429 | 6.60338 |
September | 485.00000 | 24.43663 | 52.33595 | -0.2168 | 6.55595 |
October | 502.00000 | 24.49133 | 50.54223 | 0.61470 | 13.29119 |
November | 489.00000 | 24.51291 | 49.68852 | 0.60492 | 12.95798 |
December | 497.00000 | 24.49664 | 46.73158 | 0.56021 | 11.88248 |
Annual Sum or Average | 5943.00000 | 24.45747 | 49.04466 | 0.23368 | 9.76921 |
Minimum of Months | 454.00000 | 24.33651 | 42.35298 | -0.2429 | 6.47992 |
Maximum of Months | 514.00000 | 24.51291 | 53.01931 | 0.61470 | 13.29119 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06391 | 42.85007 | 0.39042 | 8.40598 |
February | 454.00000 | 24.15494 | 45.91951 | 0.44153 | 9.29204 |
March | 514.00000 | 24.20687 | 45.39139 | 0.46366 | 9.68926 |
April | 485.00000 | 24.27701 | 48.85914 | 0.51797 | 10.81777 |
May | 508.00000 | 24.33061 | 51.89702 | -0.2817 | 7.07477 |
June | 496.00000 | 24.31056 | 55.12665 | -0.2597 | 6.79875 |
July | 497.00000 | 24.31188 | 55.28116 | -0.2551 | 6.66711 |
August | 514.00000 | 24.25909 | 55.98505 | -0.2637 | 6.70787 |
September | 485.00000 | 24.34753 | 55.43354 | -0.2473 | 6.71265 |
October | 502.00000 | 24.36531 | 52.92885 | 0.58279 | 12.37779 |
November | 489.00000 | 24.32071 | 50.82284 | 0.54210 | 11.31468 |
December | 497.00000 | 24.14377 | 46.83330 | 0.44692 | 9.40976 |
Annual Sum or Average | 5943.00000 | 24.25803 | 50.63565 | 0.17021 | 8.76185 |
Minimum of Months | 454.00000 | 24.06391 | 42.85007 | -0.2817 | 6.66711 |
Maximum of Months | 514.00000 | 24.36531 | 55.98505 | 0.58279 | 12.37779 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70591 | 42.69617 | 0.29120 | 7.22139 |
February | 454.00000 | 23.89301 | 45.31463 | 0.36745 | 8.20443 |
March | 514.00000 | 24.05899 | 44.54586 | 0.42031 | 8.99151 |
April | 485.00000 | 24.23311 | 47.83269 | 0.50470 | 10.55667 |
May | 508.00000 | 24.36413 | 51.17381 | -0.2580 | 6.91248 |
June | 496.00000 | 24.34390 | 54.81497 | -0.2296 | 6.59451 |
July | 497.00000 | 24.36682 | 55.04547 | -0.2125 | 6.41171 |
August | 514.00000 | 24.30267 | 55.86431 | -0.2256 | 6.45010 |
September | 485.00000 | 24.37648 | 55.33086 | -0.2217 | 6.57770 |
October | 502.00000 | 24.36579 | 52.37320 | 0.58377 | 12.41371 |
November | 489.00000 | 24.22126 | 49.92027 | 0.50865 | 10.59092 |
December | 497.00000 | 23.85118 | 46.14197 | 0.36263 | 8.15894 |
Annual Sum or Average | 5943.00000 | 24.17518 | 50.11417 | 0.15511 | 8.25034 |
Minimum of Months | 454.00000 | 23.70591 | 42.69617 | -0.2580 | 6.41171 |
Maximum of Months | 514.00000 | 24.37648 | 55.86431 | 0.58377 | 12.41371 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.26619 | 45.10571 | 0.18997 | 6.86242 |
February | 454.00000 | 23.61352 | 47.84044 | 0.31209 | 7.99278 |
March | 514.00000 | 23.92976 | 45.89359 | 0.40396 | 9.13679 |
April | 485.00000 | 24.28781 | 48.73280 | 0.54752 | 11.90498 |
May | 508.00000 | 24.55227 | 51.09747 | -0.1186 | 6.68907 |
June | 496.00000 | 24.55165 | 54.89067 | -0.0633 | 6.48315 |
July | 497.00000 | 24.68035 | 54.67596 | -0.0041 | 6.72459 |
August | 514.00000 | 24.54713 | 55.65427 | -0.0417 | 6.37950 |
September | 485.00000 | 24.58288 | 55.76649 | -0.0754 | 6.65655 |
October | 502.00000 | 24.50499 | 53.11620 | 0.65274 | 14.60597 |
November | 489.00000 | 24.19668 | 51.11501 | 0.51843 | 11.06403 |
December | 497.00000 | 23.58033 | 48.54929 | 0.30486 | 7.87188 |
Annual Sum or Average | 5943.00000 | 24.19468 | 51.04933 | 0.21728 | 8.52465 |
Minimum of Months | 454.00000 | 23.26619 | 45.10571 | -0.1186 | 6.37950 |
Maximum of Months | 514.00000 | 24.68035 | 55.76649 | 0.65274 | 14.60597 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45189 | 44.42139 | 0.25319 | 7.54095 |
February | 454.00000 | 23.73481 | 47.29494 | 0.36335 | 8.84565 |
March | 514.00000 | 23.98318 | 45.56152 | 0.44309 | 10.02395 |
April | 485.00000 | 24.36299 | 48.30454 | 0.60049 | 13.46898 |
May | 508.00000 | 24.57778 | 50.88584 | -0.0532 | 6.74317 |
June | 496.00000 | 24.55696 | 54.74816 | -0.0131 | 6.56950 |
July | 497.00000 | 24.68937 | 54.54384 | 0.04782 | 7.02498 |
August | 514.00000 | 24.55198 | 55.51034 | 0.01537 | 6.48722 |
September | 485.00000 | 24.60824 | 55.48820 | -0.0119 | 6.83045 |
October | 502.00000 | 24.56268 | 52.70239 | 0.70136 | 16.19839 |
November | 489.00000 | 24.28444 | 50.73464 | 0.56740 | 12.36630 |
December | 497.00000 | 23.67992 | 48.10697 | 0.34809 | 8.50582 |
Annual Sum or Average | 5943.00000 | 24.25668 | 50.70675 | 0.27022 | 9.20663 |
Minimum of Months | 454.00000 | 23.45189 | 44.42139 | -0.0532 | 6.48722 |
Maximum of Months | 514.00000 | 24.68937 | 55.51034 | 0.70136 | 16.19839 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.74615 | 42.97127 | 0.34246 | 9.21093 |
February | 454.00000 | 23.89864 | 46.33735 | 0.42037 | 10.14220 |
March | 514.00000 | 24.03449 | 45.14733 | 0.46128 | 10.49258 |
April | 485.00000 | 24.31229 | 48.44729 | 0.57054 | 12.63776 |
May | 508.00000 | 24.52958 | 51.10666 | -0.1246 | 6.71402 |
June | 496.00000 | 24.52416 | 54.96888 | -0.0825 | 6.46896 |
July | 497.00000 | 24.65502 | 54.71790 | -0.0149 | 6.65893 |
August | 514.00000 | 24.54127 | 55.57598 | -0.0278 | 6.39685 |
September | 485.00000 | 24.60730 | 55.43869 | -0.0209 | 6.82168 |
October | 502.00000 | 24.59478 | 52.41591 | 0.72676 | 17.07899 |
November | 489.00000 | 24.41133 | 49.94702 | 0.62753 | 14.23681 |
December | 497.00000 | 23.97852 | 46.65204 | 0.44361 | 10.65303 |
Annual Sum or Average | 5943.00000 | 24.32174 | 50.32975 | 0.27473 | 9.77726 |
Minimum of Months | 454.00000 | 23.74615 | 42.97127 | -0.1246 | 6.39685 |
Maximum of Months | 514.00000 | 24.65502 | 55.57598 | 0.72676 | 17.07899 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19355 | 44.80941 | 0.19773 | 7.41924 |
February | 454.00000 | 23.54058 | 47.61973 | 0.32345 | 8.59193 |
March | 514.00000 | 23.87721 | 45.69147 | 0.42351 | 9.90288 |
April | 485.00000 | 24.25628 | 48.57642 | 0.57146 | 12.83061 |
May | 508.00000 | 24.53413 | 51.03561 | -0.0805 | 6.88187 |
June | 496.00000 | 24.54024 | 54.83379 | -0.0257 | 6.66727 |
July | 497.00000 | 24.65598 | 54.64672 | 0.02902 | 6.94236 |
August | 514.00000 | 24.53768 | 55.60720 | 0.00257 | 6.55133 |
September | 485.00000 | 24.58349 | 55.58521 | -0.0274 | 6.87571 |
October | 502.00000 | 24.49089 | 52.98145 | 0.68144 | 15.59857 |
November | 489.00000 | 24.16050 | 50.97522 | 0.53999 | 11.89396 |
December | 497.00000 | 23.49654 | 48.35851 | 0.31114 | 8.38510 |
Annual Sum or Average | 5943.00000 | 24.15937 | 50.90702 | 0.24407 | 9.03711 |
Minimum of Months | 454.00000 | 23.19355 | 44.80941 | -0.0805 | 6.55133 |
Maximum of Months | 514.00000 | 24.65598 | 55.60720 | 0.68144 | 15.59857 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93498 | 45.36324 | 0.37018 | 8.18145 |
February | 454.00000 | 24.03201 | 48.50428 | 0.42457 | 9.08873 |
March | 514.00000 | 24.10530 | 47.28442 | 0.45030 | 9.53308 |
April | 485.00000 | 24.31090 | 49.43573 | 0.54272 | 11.46267 |
May | 508.00000 | 24.52371 | 50.43732 | -0.1599 | 6.49567 |
June | 496.00000 | 24.54092 | 53.28718 | -0.0999 | 6.30894 |
July | 497.00000 | 24.65731 | 52.29759 | -0.0450 | 6.39396 |
August | 514.00000 | 24.53196 | 52.42377 | -0.0695 | 6.21274 |
September | 485.00000 | 24.58825 | 52.48452 | -0.0860 | 6.40407 |
October | 502.00000 | 24.57524 | 50.99119 | 0.67209 | 15.04740 |
November | 489.00000 | 24.42563 | 50.67641 | 0.59613 | 12.68028 |
December | 497.00000 | 24.15365 | 49.03379 | 0.47013 | 9.88748 |
Annual Sum or Average | 5943.00000 | 24.36679 | 50.18800 | 0.25328 | 8.96306 |
Minimum of Months | 454.00000 | 23.93498 | 45.36324 | -0.1599 | 6.21274 |
Maximum of Months | 514.00000 | 24.65731 | 53.28718 | 0.67209 | 15.04740 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.05375 | 44.82070 | 0.42177 | 9.14598 |
February | 454.00000 | 24.12961 | 48.02721 | 0.47243 | 10.11778 |
March | 514.00000 | 24.16599 | 46.92839 | 0.49148 | 10.50370 |
April | 485.00000 | 24.41294 | 48.92993 | 0.60168 | 13.12260 |
May | 508.00000 | 24.57720 | 50.13826 | -0.0847 | 6.42182 |
June | 496.00000 | 24.56281 | 53.10466 | -0.0433 | 6.30807 |
July | 497.00000 | 24.67982 | 52.13464 | 0.01231 | 6.58539 |
August | 514.00000 | 24.54951 | 52.26031 | -0.0062 | 6.24584 |
September | 485.00000 | 24.62776 | 52.21379 | -0.0157 | 6.51109 |
October | 502.00000 | 24.63933 | 50.63258 | 0.72429 | 16.74645 |
November | 489.00000 | 24.51770 | 50.35469 | 0.64786 | 14.20100 |
December | 497.00000 | 24.21869 | 48.74155 | 0.50773 | 10.75648 |
Annual Sum or Average | 5943.00000 | 24.42930 | 49.86180 | 0.30863 | 9.70509 |
Minimum of Months | 454.00000 | 24.05375 | 44.82070 | -0.0847 | 6.24584 |
Maximum of Months | 514.00000 | 24.67982 | 53.10466 | 0.72429 | 16.74645 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13818 | 44.36684 | 0.48035 | 10.88265 |
February | 454.00000 | 24.18803 | 48.18411 | 0.51943 | 11.52032 |
March | 514.00000 | 24.16420 | 47.10118 | 0.50558 | 11.08092 |
April | 485.00000 | 24.37480 | 50.00753 | 0.58073 | 12.62203 |
May | 508.00000 | 24.66840 | 51.85056 | -0.1084 | 6.38530 |
June | 496.00000 | 24.73534 | 56.47754 | -0.0352 | 6.29674 |
July | 497.00000 | 24.89174 | 57.01380 | 0.05061 | 6.65800 |
August | 514.00000 | 24.85184 | 57.94809 | 0.07810 | 6.84798 |
September | 485.00000 | 24.86490 | 56.44245 | 0.07501 | 6.85530 |
October | 502.00000 | 24.84620 | 53.16292 | 0.80838 | 19.55825 |
November | 489.00000 | 24.64128 | 52.07677 | 0.72878 | 16.82712 |
December | 497.00000 | 24.32557 | 48.89002 | 0.57862 | 12.95361 |
Annual Sum or Average | 5943.00000 | 24.55963 | 51.97910 | 0.35292 | 10.68751 |
Minimum of Months | 454.00000 | 24.13818 | 44.36684 | -0.1084 | 6.29674 |
Maximum of Months | 514.00000 | 24.89174 | 57.94809 | 0.80838 | 19.55825 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.97554 | 44.97594 | 0.40187 | 8.87882 |
February | 454.00000 | 24.08018 | 48.11352 | 0.46089 | 9.93051 |
March | 514.00000 | 24.16137 | 46.87570 | 0.49282 | 10.55601 |
April | 485.00000 | 24.36830 | 49.12144 | 0.58648 | 12.71829 |
May | 508.00000 | 24.55040 | 50.29401 | -0.1053 | 6.45299 |
June | 496.00000 | 24.56371 | 53.17209 | -0.0488 | 6.35836 |
July | 497.00000 | 24.66992 | 52.20299 | 0.00179 | 6.52527 |
August | 514.00000 | 24.55201 | 52.33339 | -0.0130 | 6.29548 |
September | 485.00000 | 24.62638 | 52.29196 | -0.0229 | 6.52016 |
October | 502.00000 | 24.61938 | 50.80608 | 0.71546 | 16.43783 |
November | 489.00000 | 24.48400 | 50.44448 | 0.63868 | 13.93863 |
December | 497.00000 | 24.18752 | 48.75182 | 0.50100 | 10.66991 |
Annual Sum or Average | 5943.00000 | 24.40487 | 49.95283 | 0.29860 | 9.59172 |
Minimum of Months | 454.00000 | 23.97554 | 44.97594 | -0.1053 | 6.29548 |
Maximum of Months | 514.00000 | 24.66992 | 53.17209 | 0.71546 | 16.43783 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68647 | 45.18668 | 0.29848 | 7.40080 |
February | 454.00000 | 23.91549 | 48.13816 | 0.39035 | 8.66570 |
March | 514.00000 | 24.09940 | 46.53832 | 0.44915 | 9.59791 |
April | 485.00000 | 24.35697 | 49.50434 | 0.56334 | 12.07264 |
May | 508.00000 | 24.55623 | 51.64474 | -0.1336 | 6.58752 |
June | 496.00000 | 24.55107 | 54.98796 | -0.0863 | 6.42428 |
July | 497.00000 | 24.67746 | 54.66184 | -0.0339 | 6.57986 |
August | 514.00000 | 24.54125 | 55.54905 | -0.0709 | 6.30690 |
September | 485.00000 | 24.58048 | 55.63495 | -0.0961 | 6.55569 |
October | 502.00000 | 24.52555 | 53.44013 | 0.65316 | 14.53894 |
November | 489.00000 | 24.31114 | 51.74166 | 0.55131 | 11.62155 |
December | 497.00000 | 23.90711 | 48.93979 | 0.39184 | 8.68582 |
Annual Sum or Average | 5943.00000 | 24.31139 | 51.34311 | 0.23772 | 8.74317 |
Minimum of Months | 454.00000 | 23.68647 | 45.18668 | -0.1336 | 6.30690 |
Maximum of Months | 514.00000 | 24.67746 | 55.63495 | 0.65316 | 14.53894 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.73880 | 44.17733 | 0.32117 | 7.91330 |
February | 385.00000 | 23.96667 | 47.33533 | 0.41283 | 9.31243 |
March | 433.00000 | 24.14156 | 45.75154 | 0.46829 | 10.24476 |
April | 410.00000 | 24.49259 | 48.84631 | 0.61138 | 13.64131 |
May | 430.00000 | 24.68316 | 51.21168 | -0.0626 | 6.81887 |
June | 418.00000 | 24.65720 | 54.76534 | -0.0300 | 6.68933 |
July | 422.00000 | 24.80816 | 54.19896 | 0.03071 | 7.09063 |
August | 433.00000 | 24.65033 | 55.25198 | -0.0079 | 6.56709 |
September | 410.00000 | 24.71137 | 55.21777 | -0.0248 | 6.91496 |
October | 427.00000 | 24.67693 | 52.83396 | 0.70551 | 16.34174 |
November | 417.00000 | 24.44622 | 50.61986 | 0.59159 | 12.85512 |
December | 422.00000 | 23.93806 | 48.12343 | 0.40751 | 9.13842 |
Annual Sum or Average | 5034.00000 | 24.41133 | 50.70524 | 0.28393 | 9.45318 |
Minimum of Months | 385.00000 | 23.73880 | 44.17733 | -0.0626 | 6.56709 |
Maximum of Months | 433.00000 | 24.80816 | 55.25198 | 0.70551 | 16.34174 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07801 | 43.26992 | 0.43227 | 9.96557 |
February | 454.00000 | 24.15533 | 46.75430 | 0.48839 | 10.86826 |
March | 514.00000 | 24.19996 | 45.80891 | 0.50434 | 10.94982 |
April | 485.00000 | 24.39446 | 49.21320 | 0.58821 | 12.82773 |
May | 508.00000 | 24.53950 | 51.65650 | -0.1379 | 6.59082 |
June | 496.00000 | 24.52677 | 55.08153 | -0.1041 | 6.42013 |
July | 497.00000 | 24.65747 | 54.70759 | -0.0430 | 6.53190 |
August | 514.00000 | 24.54123 | 55.45652 | -0.0560 | 6.30473 |
September | 485.00000 | 24.61208 | 55.28978 | -0.0408 | 6.64127 |
October | 502.00000 | 24.62046 | 52.71862 | 0.72661 | 16.95689 |
November | 489.00000 | 24.50680 | 50.65099 | 0.65499 | 14.73997 |
December | 497.00000 | 24.23362 | 47.23318 | 0.51509 | 11.56497 |
Annual Sum or Average | 5943.00000 | 24.42341 | 50.67170 | 0.29154 | 10.01095 |
Minimum of Months | 454.00000 | 24.07801 | 43.26992 | -0.1379 | 6.30473 |
Maximum of Months | 514.00000 | 24.65747 | 55.45652 | 0.72661 | 16.95689 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63161 | 44.90768 | 0.30892 | 7.89584 |
February | 454.00000 | 23.87220 | 47.90449 | 0.40664 | 9.25241 |
March | 514.00000 | 24.08192 | 46.30089 | 0.47458 | 10.38382 |
April | 485.00000 | 24.35667 | 49.31918 | 0.59282 | 13.05167 |
May | 508.00000 | 24.54877 | 51.58002 | -0.0928 | 6.64919 |
June | 496.00000 | 24.54759 | 54.93425 | -0.0466 | 6.51149 |
July | 497.00000 | 24.66734 | 54.60988 | 0.00309 | 6.72358 |
August | 514.00000 | 24.54429 | 55.47589 | -0.0235 | 6.39704 |
September | 485.00000 | 24.59107 | 55.45801 | -0.0456 | 6.66389 |
October | 502.00000 | 24.53081 | 53.29163 | 0.68521 | 15.57371 |
November | 489.00000 | 24.31151 | 51.56881 | 0.57905 | 12.52308 |
December | 497.00000 | 23.85819 | 48.73806 | 0.40406 | 9.20581 |
Annual Sum or Average | 5943.00000 | 24.29765 | 51.18728 | 0.26858 | 9.22394 |
Minimum of Months | 454.00000 | 23.63161 | 44.90768 | -0.0928 | 6.39704 |
Maximum of Months | 514.00000 | 24.66734 | 55.47589 | 0.68521 | 15.57371 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.425912E+11 | 0.965534E+10 | 410.75 | 0.367553E+11 | 0.583589E+10 | 0.00 | 1.00 | 02-JAN-15:10 | 0.00 | 01-JAN-00:10 | 57077.20 | 30-JAN-12:00 | 50049.40 | 23-JAN-14:00 | 14702.12 | 30-JAN-14:40 | 12123.28 | 30-JAN-12:00 | 0.00 |
February | 0.449665E+11 | 0.102244E+11 | 369.83 | 0.381989E+11 | 0.676767E+10 | 0.00 | 1.00 | 01-FEB-15:40 | 0.00 | 01-FEB-00:10 | 75043.55 | 07-FEB-15:50 | 64943.29 | 06-FEB-15:10 | 22714.53 | 09-FEB-06:12 | 18253.53 | 07-FEB-13:03 | 0.00 |
March | 0.595050E+11 | 0.139473E+11 | 435.40 | 0.523140E+11 | 0.719098E+10 | 0.00 | 1.00 | 01-MAR-05:03 | 0.00 | 01-MAR-00:10 | 81136.70 | 28-MAR-11:40 | 74830.09 | 02-MAR-07:03 | 25797.68 | 28-MAR-11:40 | 23086.19 | 27-MAR-11:00 | 0.00 |
April | 0.707196E+11 | 0.173992E+11 | 426.99 | 0.607235E+11 | 0.999603E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 87856.90 | 10-APR-12:00 | 76891.02 | 28-APR-12:02 | 31569.87 | 10-APR-12:00 | 26577.11 | 28-APR-12:02 | 0.00 |
May | 0.105828E+12 | 0.282305E+11 | 495.14 | 0.879643E+11 | 0.178641E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:05 | 142184.47 | 31-MAY-04:02 | 97106.64 | 23-MAY-04:02 | 56349.79 | 24-MAY-04:02 | 34209.85 | 31-MAY-12:01 | 0.00 |
June | 0.127538E+12 | 0.342802E+11 | 498.05 | 0.947017E+11 | 0.328362E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 145017.10 | 20-JUN-04:02 | 96508.65 | 26-JUN-04:02 | 60569.91 | 08-JUN-04:02 | 36022.37 | 12-JUN-12:02 | 0.00 |
July | 0.153617E+12 | 0.420265E+11 | 561.01 | 0.104648E+12 | 0.489697E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 144667.71 | 06-JUL-04:02 | 98611.11 | 22-JUL-04:02 | 66239.55 | 20-JUL-06:07 | 39170.40 | 30-JUL-15:22 | 0.00 |
August | 0.170799E+12 | 0.468576E+11 | 589.11 | 0.114011E+12 | 0.567882E+11 | 0.00 | 1.00 | 01-AUG-00:17 | 0.00 | 01-AUG-00:03 | 144361.12 | 26-AUG-04:02 | 100197.74 | 05-AUG-06:03 | 67253.41 | 22-AUG-17:00 | 40678.18 | 10-AUG-15:30 | 0.00 |
September | 0.137333E+12 | 0.358642E+11 | 515.75 | 0.944766E+11 | 0.428569E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 146437.84 | 10-SEP-17:02 | 98390.64 | 05-SEP-05:03 | 71049.06 | 10-SEP-17:02 | 36519.15 | 03-SEP-14:21 | 0.00 |
October | 0.111535E+12 | 0.278010E+11 | 499.81 | 0.846106E+11 | 0.269248E+11 | 0.00 | 1.00 | 01-OCT-06:42 | 0.00 | 01-OCT-00:10 | 143490.63 | 18-OCT-04:02 | 94360.39 | 03-OCT-04:02 | 57551.80 | 07-OCT-04:03 | 31947.41 | 05-OCT-04:02 | 0.00 |
November | 0.808197E+11 | 0.189927E+11 | 436.39 | 0.655324E+11 | 0.152872E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 123764.45 | 03-NOV-04:02 | 87693.38 | 20-NOV-07:03 | 46401.74 | 03-NOV-04:02 | 26701.48 | 01-NOV-12:02 | 0.00 |
December | 0.532874E+11 | 0.119738E+11 | 410.39 | 0.444929E+11 | 0.879450E+10 | 0.00 | 1.00 | 01-DEC-10:10 | 0.00 | 01-DEC-00:10 | 78835.38 | 04-DEC-12:10 | 61480.53 | 12-DEC-07:03 | 25726.01 | 05-DEC-12:10 | 17930.02 | 04-DEC-12:10 | 0.00 |
Annual Sum or Average | 0.115854E+13 | 0.297253E+12 | 5648.63 | 0.878429E+12 | 0.280112E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.425912E+11 | 0.965534E+10 | 369.83 | 0.367553E+11 | 0.583589E+10 | 0.00 | 1.00 | 0.00 | 57077.20 | 50049.40 | 14702.12 | 12123.28 | 0.00 | ||||||
Maximum of Months | 0.170799E+12 | 0.468576E+11 | 589.11 | 0.114011E+12 | 0.567882E+11 | 0.00 | 1.00 | 0.00 | 146437.84 | 100197.74 | 71049.06 | 40678.18 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.323435E+11 | 0.752645E+10 | 404.28 | 0.261315E+11 | 0.621206E+10 | 0.00 | 1.00 | 30-JAN-14:00 | 0.00 | 01-JAN-00:10 | 43882.59 | 30-JAN-14:00 | 39981.24 | 23-JAN-14:00 | 12973.63 | 30-JAN-15:00 | 9379.12 | 23-JAN-14:00 | 0.00 |
February | 0.360283E+11 | 0.835985E+10 | 369.28 | 0.292191E+11 | 0.680918E+10 | 0.00 | 1.00 | 06-FEB-06:12 | 0.00 | 01-FEB-00:10 | 64219.70 | 07-FEB-15:50 | 56044.77 | 06-FEB-15:10 | 17022.89 | 07-FEB-16:00 | 14655.19 | 07-FEB-15:50 | 0.00 |
March | 0.498605E+11 | 0.118423E+11 | 436.40 | 0.426977E+11 | 0.716274E+10 | 0.00 | 1.00 | 01-MAR-10:30 | 0.00 | 01-MAR-00:10 | 67108.62 | 27-MAR-14:50 | 67108.62 | 27-MAR-14:50 | 15626.71 | 31-MAR-18:00 | 20913.46 | 27-MAR-11:00 | 0.00 |
April | 0.615896E+11 | 0.152269E+11 | 430.28 | 0.521890E+11 | 0.940060E+10 | 0.00 | 1.00 | 02-APR-13:33 | 0.00 | 01-APR-00:10 | 93207.95 | 30-APR-16:33 | 70184.77 | 28-APR-12:02 | 37223.98 | 30-APR-16:33 | 24260.48 | 28-APR-12:02 | 0.00 |
May | 0.928818E+11 | 0.246729E+11 | 490.89 | 0.774157E+11 | 0.154662E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 134392.17 | 30-MAY-04:02 | 89110.89 | 22-MAY-04:02 | 56378.28 | 24-MAY-04:02 | 29989.47 | 31-MAY-04:02 | 0.00 |
June | 0.112509E+12 | 0.299831E+11 | 494.79 | 0.829839E+11 | 0.295253E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 136881.03 | 20-JUN-04:02 | 86932.25 | 01-JUN-04:02 | 60485.10 | 24-JUN-05:03 | 32605.02 | 09-JUN-04:02 | 0.00 |
July | 0.134529E+12 | 0.365310E+11 | 543.89 | 0.919918E+11 | 0.425371E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 136836.51 | 06-JUL-04:02 | 92590.30 | 30-JUL-14:12 | 59229.47 | 06-JUL-04:02 | 38318.37 | 30-JUL-14:52 | 0.00 |
August | 0.144985E+12 | 0.395381E+11 | 557.32 | 0.979712E+11 | 0.470141E+11 | 0.00 | 1.00 | 01-AUG-00:07 | 0.00 | 01-AUG-00:03 | 137729.56 | 08-AUG-04:02 | 90753.81 | 07-AUG-06:03 | 61488.04 | 08-AUG-04:02 | 37675.65 | 06-AUG-16:51 | 0.00 |
September | 0.114510E+12 | 0.297102E+11 | 482.90 | 0.789160E+11 | 0.355944E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 136808.99 | 10-SEP-16:52 | 91560.37 | 04-SEP-15:11 | 65583.65 | 10-SEP-16:52 | 37391.80 | 04-SEP-13:51 | 0.00 |
October | 0.897706E+11 | 0.223457E+11 | 466.74 | 0.682960E+11 | 0.214746E+11 | 0.00 | 1.00 | 01-OCT-07:12 | 0.00 | 01-OCT-00:10 | 135311.62 | 02-OCT-04:02 | 88962.80 | 10-OCT-04:02 | 56130.95 | 07-OCT-05:03 | 29743.36 | 02-OCT-04:02 | 0.00 |
November | 0.627093E+11 | 0.148429E+11 | 416.24 | 0.498168E+11 | 0.128925E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 92628.01 | 03-NOV-05:03 | 66882.18 | 20-NOV-06:03 | 38612.37 | 03-NOV-05:03 | 21454.61 | 01-NOV-14:00 | 0.00 |
December | 0.408388E+11 | 0.939111E+10 | 404.61 | 0.320767E+11 | 0.876207E+10 | 0.00 | 1.00 | 01-DEC-11:50 | 0.00 | 01-DEC-00:10 | 61275.41 | 05-DEC-15:10 | 47467.52 | 04-DEC-13:40 | 18832.10 | 05-DEC-15:00 | 13429.32 | 05-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.972556E+12 | 0.249971E+12 | 5497.61 | 0.729705E+12 | 0.242851E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.323435E+11 | 0.752645E+10 | 369.28 | 0.261315E+11 | 0.621206E+10 | 0.00 | 1.00 | 0.00 | 43882.59 | 39981.24 | 12973.63 | 9379.12 | 0.00 | ||||||
Maximum of Months | 0.144985E+12 | 0.395381E+11 | 557.32 | 0.979712E+11 | 0.470141E+11 | 0.00 | 1.00 | 0.00 | 137729.56 | 92590.30 | 65583.65 | 38318.37 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.321071E+11 | 0.757681E+10 | 400.08 | 0.249572E+11 | 0.714987E+10 | 0.00 | 0.93 | 30-JAN-14:30 | 0.00 | 01-JAN-00:10 | 44966.27 | 30-JAN-14:30 | 42158.26 | 23-JAN-14:00 | 13730.36 | 30-JAN-15:00 | 10049.44 | 23-JAN-14:00 | 0.00 |
February | 0.368627E+11 | 0.866328E+10 | 367.99 | 0.292105E+11 | 0.765217E+10 | 0.00 | 1.00 | 05-FEB-13:32 | 0.00 | 01-FEB-00:10 | 69162.78 | 07-FEB-15:30 | 61576.27 | 06-FEB-15:00 | 16922.27 | 07-FEB-16:00 | 16050.64 | 06-FEB-15:00 | 0.00 |
March | 0.521127E+11 | 0.125140E+11 | 435.57 | 0.440024E+11 | 0.811031E+10 | 0.00 | 1.00 | 01-MAR-11:00 | 0.00 | 01-MAR-00:10 | 74997.88 | 27-MAR-13:40 | 74997.88 | 27-MAR-13:40 | 16633.73 | 31-MAR-18:00 | 22432.75 | 27-MAR-12:03 | 0.00 |
April | 0.657217E+11 | 0.164050E+11 | 431.51 | 0.553918E+11 | 0.103299E+11 | 0.00 | 1.00 | 02-APR-14:32 | 0.00 | 01-APR-00:10 | 114741.25 | 30-APR-14:13 | 90904.92 | 30-APR-13:32 | 26236.18 | 30-APR-17:33 | 28972.89 | 30-APR-14:13 | 0.00 |
May | 0.100617E+12 | 0.268795E+11 | 494.86 | 0.843596E+11 | 0.162572E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:05 | 151773.77 | 30-MAY-04:02 | 104200.45 | 12-MAY-04:02 | 59871.46 | 24-MAY-04:02 | 34039.58 | 31-MAY-04:02 | 0.00 |
June | 0.121516E+12 | 0.325193E+11 | 501.50 | 0.911172E+11 | 0.303985E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:23 | 155648.55 | 20-JUN-04:02 | 100860.84 | 26-JUN-04:02 | 71708.39 | 20-JUN-04:02 | 37687.49 | 04-JUN-15:52 | 0.00 |
July | 0.146964E+12 | 0.399935E+11 | 561.76 | 0.102589E+12 | 0.443744E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 155359.36 | 06-JUL-04:02 | 113548.25 | 30-JUL-13:52 | 65417.47 | 06-JUL-04:02 | 44014.29 | 30-JUL-14:32 | 0.00 |
August | 0.157317E+12 | 0.429859E+11 | 573.60 | 0.108663E+12 | 0.486541E+11 | 0.00 | 1.00 | 01-AUG-00:30 | 0.00 | 01-AUG-00:03 | 154666.00 | 26-AUG-04:02 | 107959.67 | 06-AUG-15:02 | 66270.96 | 08-AUG-04:02 | 42499.58 | 06-AUG-14:22 | 0.00 |
September | 0.121729E+12 | 0.316996E+11 | 489.46 | 0.853819E+11 | 0.363470E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 155277.64 | 28-SEP-04:02 | 108554.99 | 04-SEP-15:22 | 71984.35 | 28-SEP-04:02 | 42123.43 | 04-SEP-14:02 | 0.00 |
October | 0.933131E+11 | 0.234051E+11 | 463.85 | 0.713223E+11 | 0.219908E+11 | 0.00 | 1.00 | 01-OCT-08:63 | 0.00 | 01-OCT-00:10 | 152828.21 | 02-OCT-04:02 | 98535.90 | 10-OCT-04:02 | 59670.77 | 02-OCT-04:02 | 33695.25 | 02-OCT-04:02 | 0.00 |
November | 0.638194E+11 | 0.152673E+11 | 413.54 | 0.501189E+11 | 0.137004E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 99622.17 | 03-NOV-05:03 | 68878.19 | 06-NOV-14:10 | 40910.43 | 03-NOV-05:03 | 23317.18 | 01-NOV-14:00 | 0.00 |
December | 0.409716E+11 | 0.956573E+10 | 402.11 | 0.312028E+11 | 0.976881E+10 | 0.00 | 1.00 | 01-DEC-13:10 | 0.00 | 01-DEC-00:10 | 64392.30 | 05-DEC-15:00 | 49953.66 | 04-DEC-14:10 | 19021.32 | 05-DEC-15:00 | 14073.60 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.103305E+13 | 0.267475E+12 | 5535.83 | 0.778317E+12 | 0.254734E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.321071E+11 | 0.757681E+10 | 367.99 | 0.249572E+11 | 0.714987E+10 | 0.00 | 0.93 | 0.00 | 44966.27 | 42158.26 | 13730.36 | 10049.44 | 0.00 | ||||||
Maximum of Months | 0.157317E+12 | 0.429859E+11 | 573.60 | 0.108663E+12 | 0.486541E+11 | 0.00 | 1.00 | 0.00 | 155648.55 | 113548.25 | 71984.35 | 44014.29 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.97 | 0.00 | 317.97 | 374.40 | 666.26 | 0.00 | 0.00 | 0.00 |
February | 364.49 | 0.00 | 364.49 | 510.49 | 560.70 | 0.00 | 0.00 | 0.00 |
March | 418.66 | 0.00 | 418.66 | 727.40 | 429.23 | 0.00 | 0.00 | 0.00 |
April | 471.70 | 0.97 | 470.73 | 1050.06 | 272.21 | 0.00 | 0.00 | 0.00 |
May | 530.94 | 15.57 | 515.37 | 1589.95 | 70.18 | 0.00 | 0.00 | 0.00 |
June | 568.47 | 31.56 | 536.91 | 1838.64 | 17.86 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 15.03 | 506.60 | 2055.12 | 0.37 | 0.00 | 0.00 | 0.00 |
August | 485.59 | 4.02 | 481.57 | 2026.08 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 442.33 | 0.05 | 442.28 | 1522.84 | 25.74 | 0.00 | 0.00 | 0.00 |
October | 392.11 | 0.00 | 392.11 | 1092.26 | 113.32 | 0.00 | 0.00 | 0.00 |
November | 336.62 | 0.00 | 336.62 | 695.62 | 309.18 | 0.00 | 0.00 | 0.00 |
December | 296.79 | 0.00 | 296.79 | 417.85 | 544.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 429.19 | 5.62 | 423.57 | 1162.42 | 249.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.79 | 0.00 | 296.79 | 374.40 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.47 | 31.56 | 536.91 | 2055.12 | 666.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 383.47 | 116.02 | 267.45 | 536.31 | 417.94 | 0.00 | 0.00 | 0.00 |
February | 417.90 | 113.25 | 304.65 | 644.84 | 354.76 | 0.00 | 0.00 | 0.00 |
March | 461.61 | 113.77 | 347.84 | 816.50 | 273.40 | 0.00 | 0.00 | 0.00 |
April | 562.03 | 163.76 | 398.27 | 1162.55 | 175.22 | 0.00 | 0.00 | 0.00 |
May | 628.09 | 200.11 | 427.97 | 1570.62 | 44.28 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 188.11 | 427.00 | 1660.09 | 10.32 | 0.00 | 0.00 | 0.00 |
July | 574.11 | 165.52 | 408.60 | 1796.52 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 587.88 | 180.43 | 407.45 | 1855.88 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 552.68 | 170.83 | 381.85 | 1502.60 | 15.14 | 0.00 | 0.00 | 0.00 |
October | 501.50 | 163.84 | 337.66 | 1175.85 | 69.08 | 0.00 | 0.00 | 0.00 |
November | 420.26 | 133.12 | 287.14 | 818.54 | 195.24 | 0.00 | 0.00 | 0.00 |
December | 340.16 | 93.33 | 246.83 | 523.83 | 344.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 504.07 | 150.33 | 353.74 | 1175.09 | 157.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.16 | 93.33 | 246.83 | 523.83 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 628.09 | 200.11 | 427.97 | 1855.88 | 417.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1027.66 | 483.15 | 544.51 | 1635.60 | 652.76 | 0.00 | 0.00 | 0.00 |
February | 965.01 | 394.73 | 570.28 | 1630.93 | 560.63 | 0.00 | 0.00 | 0.00 |
March | 794.25 | 215.63 | 578.62 | 1499.98 | 438.17 | 0.00 | 0.00 | 0.00 |
April | 624.34 | 66.19 | 558.15 | 1398.55 | 277.63 | 0.00 | 0.00 | 0.00 |
May | 528.87 | 8.10 | 520.77 | 1587.01 | 69.98 | 0.00 | 0.00 | 0.00 |
June | 498.07 | 0.62 | 497.46 | 1688.33 | 14.03 | 0.00 | 0.00 | 0.00 |
July | 498.06 | 4.23 | 493.83 | 1996.56 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 577.71 | 40.93 | 536.78 | 2236.93 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 761.72 | 174.57 | 587.15 | 2207.31 | 25.46 | 0.00 | 0.00 | 0.00 |
October | 997.24 | 396.46 | 600.78 | 2291.19 | 113.15 | 0.00 | 0.00 | 0.00 |
November | 1100.16 | 530.36 | 569.80 | 2129.88 | 311.78 | 0.00 | 0.00 | 0.00 |
December | 1021.28 | 504.48 | 516.80 | 1731.35 | 544.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 781.77 | 234.10 | 547.67 | 1837.60 | 249.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 498.06 | 0.62 | 493.83 | 1398.55 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1100.16 | 530.36 | 600.78 | 2291.19 | 652.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.07 | 108.01 | 268.06 | 552.31 | 442.95 | 0.00 | 0.00 | 0.00 |
February | 429.43 | 122.46 | 306.97 | 689.53 | 373.82 | 0.00 | 0.00 | 0.00 |
March | 508.67 | 150.59 | 358.08 | 917.05 | 291.13 | 0.00 | 0.00 | 0.00 |
April | 555.89 | 156.18 | 399.72 | 1157.09 | 190.04 | 0.00 | 0.00 | 0.00 |
May | 605.08 | 181.13 | 423.96 | 1534.67 | 51.31 | 0.00 | 0.00 | 0.00 |
June | 625.30 | 197.11 | 428.19 | 1686.07 | 11.74 | 0.00 | 0.00 | 0.00 |
July | 573.65 | 164.11 | 409.54 | 1794.26 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 588.50 | 178.93 | 409.57 | 1848.01 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 559.82 | 175.88 | 383.94 | 1515.52 | 18.66 | 0.00 | 0.00 | 0.00 |
October | 497.51 | 160.71 | 336.80 | 1176.45 | 80.04 | 0.00 | 0.00 | 0.00 |
November | 427.55 | 139.82 | 287.73 | 853.38 | 211.46 | 0.00 | 0.00 | 0.00 |
December | 357.93 | 108.19 | 249.73 | 583.52 | 365.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 509.07 | 153.70 | 355.37 | 1195.24 | 168.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.93 | 108.01 | 249.73 | 552.31 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 625.30 | 197.11 | 428.19 | 1848.01 | 442.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.05 | 255.55 | 0.00 | 0.00 | 0.00 |
February | 121.49 | 0.00 | 121.49 | 166.32 | 208.10 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.39 | 152.23 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.90 | 354.11 | 92.12 | 0.00 | 0.00 | 0.00 |
May | 176.97 | 5.19 | 171.78 | 534.01 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 189.48 | 10.52 | 178.96 | 614.11 | 5.77 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 684.28 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 669.75 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.20 | 10.32 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.66 | 44.90 | 0.00 | 0.00 | 0.00 |
November | 112.20 | 0.00 | 112.20 | 224.30 | 121.20 | 0.00 | 0.00 | 0.00 |
December | 98.92 | 0.00 | 98.92 | 130.94 | 213.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.18 | 384.35 | 93.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.92 | 0.00 | 98.92 | 117.05 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.48 | 10.52 | 178.96 | 684.28 | 255.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.06 | 255.56 | 0.00 | 0.00 | 0.00 |
February | 121.50 | 0.00 | 121.50 | 166.32 | 208.11 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.40 | 152.24 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.91 | 354.13 | 92.12 | 0.00 | 0.00 | 0.00 |
May | 176.98 | 5.19 | 171.79 | 534.04 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 189.49 | 10.52 | 178.97 | 614.15 | 5.77 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 684.32 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 669.79 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.22 | 10.32 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.68 | 44.90 | 0.00 | 0.00 | 0.00 |
November | 112.21 | 0.00 | 112.21 | 224.32 | 121.20 | 0.00 | 0.00 | 0.00 |
December | 98.93 | 0.00 | 98.93 | 130.94 | 213.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.19 | 384.37 | 93.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.93 | 0.00 | 98.93 | 117.06 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.49 | 10.52 | 178.97 | 684.32 | 255.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.99 | 0.00 | 105.99 | 117.06 | 255.56 | 0.00 | 0.00 | 0.00 |
February | 121.50 | 0.00 | 121.50 | 166.32 | 208.11 | 0.00 | 0.00 | 0.00 |
March | 139.55 | 0.00 | 139.55 | 243.40 | 152.24 | 0.00 | 0.00 | 0.00 |
April | 157.23 | 0.32 | 156.91 | 354.13 | 92.12 | 0.00 | 0.00 | 0.00 |
May | 176.98 | 5.19 | 171.79 | 534.04 | 22.33 | 0.00 | 0.00 | 0.00 |
June | 189.49 | 10.52 | 178.97 | 614.15 | 5.77 | 0.00 | 0.00 | 0.00 |
July | 173.87 | 5.01 | 168.86 | 684.32 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 161.86 | 1.34 | 160.52 | 669.79 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 147.44 | 0.02 | 147.42 | 501.22 | 10.32 | 0.00 | 0.00 | 0.00 |
October | 130.70 | 0.00 | 130.70 | 356.68 | 44.90 | 0.00 | 0.00 | 0.00 |
November | 112.21 | 0.00 | 112.21 | 224.32 | 121.20 | 0.00 | 0.00 | 0.00 |
December | 98.93 | 0.00 | 98.93 | 130.94 | 213.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.06 | 1.87 | 141.19 | 384.37 | 93.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.93 | 0.00 | 98.93 | 117.06 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.49 | 10.52 | 178.97 | 684.32 | 255.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 368.88 | 111.60 | 257.28 | 497.51 | 462.60 | 0.00 | 0.00 | 0.00 |
February | 402.00 | 108.94 | 293.05 | 612.05 | 382.07 | 0.00 | 0.00 | 0.00 |
March | 444.05 | 109.44 | 334.61 | 787.57 | 282.93 | 0.00 | 0.00 | 0.00 |
April | 540.65 | 157.53 | 383.12 | 1127.53 | 175.94 | 0.00 | 0.00 | 0.00 |
May | 604.19 | 192.50 | 411.69 | 1518.91 | 43.45 | 0.00 | 0.00 | 0.00 |
June | 591.71 | 180.95 | 410.76 | 1599.54 | 10.83 | 0.00 | 0.00 | 0.00 |
July | 552.27 | 159.22 | 393.05 | 1725.91 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 565.51 | 173.56 | 391.95 | 1773.69 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 531.65 | 164.33 | 367.32 | 1433.63 | 19.14 | 0.00 | 0.00 | 0.00 |
October | 482.42 | 157.61 | 324.81 | 1119.35 | 83.61 | 0.00 | 0.00 | 0.00 |
November | 404.27 | 128.05 | 276.22 | 773.51 | 224.66 | 0.00 | 0.00 | 0.00 |
December | 327.22 | 89.77 | 237.44 | 485.19 | 389.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.89 | 144.60 | 340.28 | 1124.15 | 171.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.22 | 89.77 | 237.44 | 485.19 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 604.19 | 192.50 | 411.69 | 1773.69 | 462.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.59 | 4.41 | 10.17 | 19.67 | 18.29 | 0.00 | 0.00 | 0.00 |
February | 15.89 | 4.31 | 11.59 | 24.20 | 15.11 | 0.00 | 0.00 | 0.00 |
March | 17.56 | 4.33 | 13.23 | 31.14 | 11.19 | 0.00 | 0.00 | 0.00 |
April | 21.38 | 6.23 | 15.15 | 44.58 | 6.96 | 0.00 | 0.00 | 0.00 |
May | 23.89 | 7.61 | 16.28 | 60.06 | 1.72 | 0.00 | 0.00 | 0.00 |
June | 23.40 | 7.15 | 16.24 | 63.24 | 0.43 | 0.00 | 0.00 | 0.00 |
July | 21.84 | 6.30 | 15.54 | 68.24 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.36 | 6.86 | 15.50 | 70.13 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21.02 | 6.50 | 14.52 | 56.68 | 0.76 | 0.00 | 0.00 | 0.00 |
October | 19.07 | 6.23 | 12.84 | 44.26 | 3.31 | 0.00 | 0.00 | 0.00 |
November | 15.98 | 5.06 | 10.92 | 30.58 | 8.88 | 0.00 | 0.00 | 0.00 |
December | 12.94 | 3.55 | 9.39 | 19.18 | 15.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.17 | 5.72 | 13.45 | 44.45 | 6.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.94 | 3.55 | 9.39 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.89 | 7.61 | 16.28 | 70.13 | 18.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.55 | 161.05 | 181.50 | 541.11 | 251.22 | 0.00 | 0.00 | 0.00 |
February | 321.67 | 131.57 | 190.09 | 543.54 | 210.84 | 0.00 | 0.00 | 0.00 |
March | 264.75 | 71.88 | 192.87 | 502.63 | 157.43 | 0.00 | 0.00 | 0.00 |
April | 208.11 | 22.06 | 186.05 | 470.09 | 95.56 | 0.00 | 0.00 | 0.00 |
May | 176.29 | 2.70 | 173.59 | 528.88 | 23.25 | 0.00 | 0.00 | 0.00 |
June | 166.02 | 0.21 | 165.82 | 557.39 | 5.09 | 0.00 | 0.00 | 0.00 |
July | 166.02 | 1.41 | 164.61 | 657.78 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 192.57 | 13.64 | 178.92 | 730.60 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 253.90 | 58.19 | 195.71 | 723.40 | 11.54 | 0.00 | 0.00 | 0.00 |
October | 332.41 | 132.15 | 200.26 | 754.85 | 49.33 | 0.00 | 0.00 | 0.00 |
November | 366.71 | 176.78 | 189.93 | 704.98 | 126.50 | 0.00 | 0.00 | 0.00 |
December | 340.42 | 168.16 | 172.26 | 572.50 | 213.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.59 | 78.03 | 182.55 | 607.76 | 94.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.02 | 0.21 | 164.61 | 470.09 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.71 | 176.78 | 200.26 | 754.85 | 251.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.55 | 161.05 | 181.50 | 541.11 | 251.22 | 0.00 | 0.00 | 0.00 |
February | 321.67 | 131.57 | 190.09 | 543.54 | 210.84 | 0.00 | 0.00 | 0.00 |
March | 264.75 | 71.88 | 192.87 | 502.63 | 157.43 | 0.00 | 0.00 | 0.00 |
April | 208.11 | 22.06 | 186.05 | 470.09 | 95.56 | 0.00 | 0.00 | 0.00 |
May | 176.29 | 2.70 | 173.59 | 528.88 | 23.25 | 0.00 | 0.00 | 0.00 |
June | 166.02 | 0.21 | 165.82 | 557.39 | 5.09 | 0.00 | 0.00 | 0.00 |
July | 166.02 | 1.41 | 164.61 | 657.78 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 192.57 | 13.64 | 178.92 | 730.60 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 253.90 | 58.19 | 195.71 | 723.40 | 11.54 | 0.00 | 0.00 | 0.00 |
October | 332.41 | 132.15 | 200.26 | 754.85 | 49.33 | 0.00 | 0.00 | 0.00 |
November | 366.71 | 176.78 | 189.93 | 704.98 | 126.50 | 0.00 | 0.00 | 0.00 |
December | 340.42 | 168.16 | 172.26 | 572.50 | 213.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.59 | 78.03 | 182.55 | 607.76 | 94.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.02 | 0.21 | 164.61 | 470.09 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.71 | 176.78 | 200.26 | 754.85 | 251.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.52 | 161.04 | 181.49 | 541.08 | 251.21 | 0.00 | 0.00 | 0.00 |
February | 321.65 | 131.57 | 190.08 | 543.50 | 210.83 | 0.00 | 0.00 | 0.00 |
March | 264.73 | 71.87 | 192.86 | 502.60 | 157.42 | 0.00 | 0.00 | 0.00 |
April | 208.10 | 22.06 | 186.04 | 470.06 | 95.55 | 0.00 | 0.00 | 0.00 |
May | 176.28 | 2.70 | 173.58 | 528.85 | 23.24 | 0.00 | 0.00 | 0.00 |
June | 166.01 | 0.21 | 165.81 | 557.36 | 5.09 | 0.00 | 0.00 | 0.00 |
July | 166.01 | 1.41 | 164.60 | 657.73 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 192.56 | 13.64 | 178.91 | 730.55 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 253.89 | 58.19 | 195.70 | 723.36 | 11.54 | 0.00 | 0.00 | 0.00 |
October | 332.39 | 132.14 | 200.24 | 754.81 | 49.33 | 0.00 | 0.00 | 0.00 |
November | 366.69 | 176.77 | 189.92 | 704.94 | 126.49 | 0.00 | 0.00 | 0.00 |
December | 340.40 | 168.15 | 172.25 | 572.47 | 213.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.57 | 78.03 | 182.54 | 607.73 | 94.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 166.01 | 0.21 | 164.60 | 470.06 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 366.69 | 176.77 | 200.24 | 754.81 | 251.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 361.76 | 103.90 | 257.86 | 516.87 | 496.17 | 0.00 | 0.00 | 0.00 |
February | 413.09 | 117.80 | 295.29 | 656.97 | 406.94 | 0.00 | 0.00 | 0.00 |
March | 489.32 | 144.86 | 344.45 | 885.85 | 304.68 | 0.00 | 0.00 | 0.00 |
April | 534.74 | 150.23 | 384.51 | 1122.59 | 191.84 | 0.00 | 0.00 | 0.00 |
May | 582.06 | 174.23 | 407.83 | 1483.40 | 50.73 | 0.00 | 0.00 | 0.00 |
June | 601.51 | 189.61 | 411.90 | 1621.49 | 12.86 | 0.00 | 0.00 | 0.00 |
July | 551.82 | 157.87 | 393.96 | 1721.03 | 0.34 | 0.00 | 0.00 | 0.00 |
August | 566.11 | 172.12 | 393.99 | 1764.80 | 0.12 | 0.00 | 0.00 | 0.00 |
September | 538.52 | 169.19 | 369.33 | 1445.52 | 23.26 | 0.00 | 0.00 | 0.00 |
October | 478.58 | 154.59 | 323.99 | 1119.45 | 95.39 | 0.00 | 0.00 | 0.00 |
November | 411.28 | 134.50 | 276.78 | 808.43 | 244.87 | 0.00 | 0.00 | 0.00 |
December | 344.31 | 104.08 | 240.23 | 545.70 | 417.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.70 | 147.85 | 341.85 | 1143.80 | 185.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.31 | 103.90 | 240.23 | 516.87 | 0.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.51 | 189.61 | 411.90 | 1764.80 | 496.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.30 | 4.11 | 10.20 | 20.44 | 19.62 | 0.00 | 0.00 | 0.00 |
February | 16.33 | 4.66 | 11.68 | 25.98 | 16.09 | 0.00 | 0.00 | 0.00 |
March | 19.35 | 5.73 | 13.62 | 35.03 | 12.05 | 0.00 | 0.00 | 0.00 |
April | 21.14 | 5.94 | 15.20 | 44.39 | 7.59 | 0.00 | 0.00 | 0.00 |
May | 23.01 | 6.89 | 16.13 | 58.65 | 2.01 | 0.00 | 0.00 | 0.00 |
June | 23.78 | 7.50 | 16.29 | 64.11 | 0.51 | 0.00 | 0.00 | 0.00 |
July | 21.82 | 6.24 | 15.58 | 68.05 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.38 | 6.81 | 15.58 | 69.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21.29 | 6.69 | 14.60 | 57.15 | 0.92 | 0.00 | 0.00 | 0.00 |
October | 18.92 | 6.11 | 12.81 | 44.26 | 3.77 | 0.00 | 0.00 | 0.00 |
November | 16.26 | 5.32 | 10.94 | 31.96 | 9.68 | 0.00 | 0.00 | 0.00 |
December | 13.61 | 4.12 | 9.50 | 21.58 | 16.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.36 | 5.85 | 13.52 | 45.22 | 7.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.61 | 4.11 | 9.50 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.78 | 7.50 | 16.29 | 69.78 | 19.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.97 | 0.00 | 317.97 | 359.42 | 725.97 | 0.00 | 0.00 | 0.00 |
February | 364.49 | 0.00 | 364.49 | 500.58 | 604.85 | 0.00 | 0.00 | 0.00 |
March | 418.66 | 0.00 | 418.66 | 724.56 | 457.33 | 0.00 | 0.00 | 0.00 |
April | 471.70 | 0.97 | 470.73 | 1054.04 | 284.58 | 0.00 | 0.00 | 0.00 |
May | 530.94 | 15.57 | 515.37 | 1600.33 | 71.41 | 0.00 | 0.00 | 0.00 |
June | 568.47 | 31.56 | 536.91 | 1849.77 | 17.65 | 0.00 | 0.00 | 0.00 |
July | 521.63 | 15.03 | 506.60 | 2068.54 | 0.40 | 0.00 | 0.00 | 0.00 |
August | 485.59 | 4.02 | 481.57 | 2038.07 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 442.33 | 0.05 | 442.28 | 1531.24 | 26.46 | 0.00 | 0.00 | 0.00 |
October | 392.11 | 0.00 | 392.11 | 1096.00 | 119.23 | 0.00 | 0.00 | 0.00 |
November | 336.62 | 0.00 | 336.62 | 692.30 | 331.85 | 0.00 | 0.00 | 0.00 |
December | 296.79 | 0.00 | 296.79 | 405.89 | 592.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 429.19 | 5.62 | 423.57 | 1164.15 | 267.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 296.79 | 0.00 | 296.79 | 359.42 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.47 | 31.56 | 536.91 | 2068.54 | 725.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 383.47 | 116.02 | 267.45 | 523.86 | 449.74 | 0.00 | 0.00 | 0.00 |
February | 417.90 | 113.25 | 304.65 | 637.34 | 378.85 | 0.00 | 0.00 | 0.00 |
March | 461.61 | 113.77 | 347.84 | 814.34 | 289.16 | 0.00 | 0.00 | 0.00 |
April | 562.03 | 163.76 | 398.27 | 1165.94 | 182.24 | 0.00 | 0.00 | 0.00 |
May | 628.09 | 200.11 | 427.97 | 1579.08 | 45.06 | 0.00 | 0.00 | 0.00 |
June | 615.11 | 188.11 | 427.00 | 1668.95 | 10.20 | 0.00 | 0.00 | 0.00 |
July | 574.11 | 165.52 | 408.60 | 1806.60 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 587.88 | 180.43 | 407.45 | 1865.01 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 552.68 | 170.83 | 381.85 | 1509.83 | 15.57 | 0.00 | 0.00 | 0.00 |
October | 501.50 | 163.84 | 337.66 | 1179.87 | 72.53 | 0.00 | 0.00 | 0.00 |
November | 420.26 | 133.12 | 287.14 | 816.48 | 208.14 | 0.00 | 0.00 | 0.00 |
December | 340.16 | 93.33 | 246.83 | 514.22 | 370.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 504.07 | 150.33 | 353.74 | 1176.59 | 167.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.16 | 93.33 | 246.83 | 514.22 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 628.09 | 200.11 | 427.97 | 1865.01 | 449.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1027.66 | 483.15 | 544.51 | 1621.96 | 702.89 | 0.00 | 0.00 | 0.00 |
February | 965.01 | 394.73 | 570.28 | 1624.06 | 600.21 | 0.00 | 0.00 | 0.00 |
March | 794.25 | 215.63 | 578.62 | 1499.28 | 465.40 | 0.00 | 0.00 | 0.00 |
April | 624.34 | 66.19 | 558.15 | 1403.34 | 290.80 | 0.00 | 0.00 | 0.00 |
May | 528.87 | 8.10 | 520.77 | 1597.30 | 72.03 | 0.00 | 0.00 | 0.00 |
June | 498.07 | 0.62 | 497.46 | 1698.14 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 498.06 | 4.23 | 493.83 | 2008.90 | 0.17 | 0.00 | 0.00 | 0.00 |
August | 577.71 | 40.93 | 536.78 | 2248.36 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 761.72 | 174.57 | 587.15 | 2217.26 | 26.36 | 0.00 | 0.00 | 0.00 |
October | 997.24 | 396.46 | 600.78 | 2298.31 | 118.97 | 0.00 | 0.00 | 0.00 |
November | 1100.16 | 530.36 | 569.80 | 2129.82 | 331.37 | 0.00 | 0.00 | 0.00 |
December | 1021.28 | 504.48 | 516.80 | 1721.47 | 584.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 781.77 | 234.10 | 547.67 | 1840.53 | 265.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 498.06 | 0.62 | 493.83 | 1403.34 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1100.16 | 530.36 | 600.78 | 2298.31 | 702.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.07 | 108.01 | 268.06 | 542.51 | 481.81 | 0.00 | 0.00 | 0.00 |
February | 429.43 | 122.46 | 306.97 | 683.24 | 403.00 | 0.00 | 0.00 | 0.00 |
March | 508.67 | 150.59 | 358.08 | 915.72 | 310.11 | 0.00 | 0.00 | 0.00 |
April | 555.89 | 156.18 | 399.72 | 1160.33 | 198.93 | 0.00 | 0.00 | 0.00 |
May | 605.08 | 181.13 | 423.96 | 1542.23 | 52.56 | 0.00 | 0.00 | 0.00 |
June | 625.30 | 197.11 | 428.19 | 1693.40 | 11.85 | 0.00 | 0.00 | 0.00 |
July | 573.65 | 164.11 | 409.54 | 1802.23 | 0.20 | 0.00 | 0.00 | 0.00 |
August | 588.50 | 178.93 | 409.57 | 1855.56 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 559.82 | 175.88 | 383.94 | 1521.55 | 19.18 | 0.00 | 0.00 | 0.00 |
October | 497.51 | 160.71 | 336.80 | 1179.76 | 84.18 | 0.00 | 0.00 | 0.00 |
November | 427.55 | 139.82 | 287.73 | 851.76 | 227.03 | 0.00 | 0.00 | 0.00 |
December | 357.93 | 108.19 | 249.73 | 575.52 | 396.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 509.07 | 153.70 | 355.37 | 1196.61 | 181.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 357.93 | 108.01 | 249.73 | 542.51 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 625.30 | 197.11 | 428.19 | 1855.56 | 481.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.100280E+10 | 0.178451E+10 |
February | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.123498E+10 | 0.135644E+10 |
March | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.194828E+10 | 0.114965E+10 |
April | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.272177E+10 | 0.705560E+09 |
May | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.425853E+10 | 0.187958E+09 |
June | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.476575E+10 | 46299194.22 |
July | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.550443E+10 | 991082.96 |
August | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.542665E+10 | 224219.01 |
September | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.394720E+10 | 66714314.55 |
October | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.292552E+10 | 0.303520E+09 |
November | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.180304E+10 | 0.801395E+09 |
December | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.111917E+10 | 0.145944E+10 |
Annual Sum or Average | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.366581E+11 | 0.786270E+10 |
Minimum of Months | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.100280E+10 | 224219.01 |
Maximum of Months | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.550443E+10 | 0.178451E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.143644E+10 | 0.111941E+10 |
February | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.156000E+10 | 0.858242E+09 |
March | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.218691E+10 | 0.732281E+09 |
April | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.301332E+10 | 0.454162E+09 |
May | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.420674E+10 | 0.118605E+09 |
June | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.430296E+10 | 26759657.21 |
July | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.481179E+10 | 389019.18 |
August | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.497078E+10 | 86172.08 |
September | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.389475E+10 | 39241293.75 |
October | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.314941E+10 | 0.185031E+09 |
November | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.212165E+10 | 0.506054E+09 |
December | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.140303E+10 | 0.923349E+09 |
Annual Sum or Average | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.370578E+11 | 0.496361E+10 |
Minimum of Months | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.140303E+10 | 86172.08 |
Maximum of Months | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.497078E+10 | 0.111941E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.438078E+10 | 0.174836E+10 |
February | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.394555E+10 | 0.135626E+10 |
March | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.401756E+10 | 0.117359E+10 |
April | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.362505E+10 | 0.719621E+09 |
May | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.425064E+10 | 0.187435E+09 |
June | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.437614E+10 | 36371276.88 |
July | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.534758E+10 | 316359.86 |
August | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.599139E+10 | 129637.78 |
September | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.572136E+10 | 65991562.32 |
October | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.613673E+10 | 0.303053E+09 |
November | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.552066E+10 | 0.808145E+09 |
December | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.463723E+10 | 0.145852E+10 |
Annual Sum or Average | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.579507E+11 | 0.785779E+10 |
Minimum of Months | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.362505E+10 | 129637.78 |
Maximum of Months | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.613673E+10 | 0.174836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.147930E+10 | 0.118640E+10 |
February | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.166810E+10 | 0.904341E+09 |
March | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.245623E+10 | 0.779753E+09 |
April | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.299918E+10 | 0.492583E+09 |
May | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.411047E+10 | 0.137419E+09 |
June | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.437030E+10 | 30436538.15 |
July | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.480574E+10 | 392388.75 |
August | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.494970E+10 | 241618.97 |
September | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.392824E+10 | 48359166.06 |
October | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.315100E+10 | 0.214384E+09 |
November | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.221196E+10 | 0.548107E+09 |
December | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.156289E+10 | 0.977790E+09 |
Annual Sum or Average | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.376931E+11 | 0.532021E+10 |
Minimum of Months | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.147930E+10 | 241618.97 |
Maximum of Months | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.494970E+10 | 0.118640E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283873E+09 | 0.00 | 0.283873E+09 | 0.313516E+09 | 0.684466E+09 |
February | 0.293910E+09 | 0.00 | 0.293910E+09 | 0.402356E+09 | 0.503425E+09 |
March | 0.373766E+09 | 0.00 | 0.373766E+09 | 0.651896E+09 | 0.407728E+09 |
April | 0.407528E+09 | 839690.24 | 0.406688E+09 | 0.917860E+09 | 0.238766E+09 |
May | 0.473999E+09 | 13902104.80 | 0.460097E+09 | 0.143030E+10 | 59818922.34 |
June | 0.491135E+09 | 27266316.28 | 0.463868E+09 | 0.159178E+10 | 14955765.37 |
July | 0.465686E+09 | 13417543.97 | 0.452269E+09 | 0.183277E+10 | 403809.26 |
August | 0.433514E+09 | 3585590.35 | 0.429928E+09 | 0.179386E+10 | 90437.67 |
September | 0.382153E+09 | 43791.23 | 0.382109E+09 | 0.129910E+10 | 26754869.08 |
October | 0.350063E+09 | 0.00 | 0.350063E+09 | 0.955287E+09 | 0.120270E+09 |
November | 0.290827E+09 | 0.00 | 0.290827E+09 | 0.581399E+09 | 0.314142E+09 |
December | 0.264959E+09 | 0.00 | 0.264959E+09 | 0.350707E+09 | 0.570836E+09 |
Annual Sum or Average | 0.451141E+10 | 59055036.89 | 0.445236E+10 | 0.121208E+11 | 0.294166E+10 |
Minimum of Months | 0.264959E+09 | 0.00 | 0.264959E+09 | 0.313516E+09 | 90437.67 |
Maximum of Months | 0.491135E+09 | 27266316.28 | 0.463868E+09 | 0.183277E+10 | 0.684466E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283884E+09 | 0.00 | 0.283884E+09 | 0.313527E+09 | 0.684504E+09 |
February | 0.293921E+09 | 0.00 | 0.293921E+09 | 0.402372E+09 | 0.503452E+09 |
March | 0.373780E+09 | 0.00 | 0.373780E+09 | 0.651925E+09 | 0.407749E+09 |
April | 0.407544E+09 | 839712.81 | 0.406704E+09 | 0.917904E+09 | 0.238776E+09 |
May | 0.474018E+09 | 13902478.50 | 0.460115E+09 | 0.143037E+10 | 59820177.01 |
June | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.159187E+10 | 14955411.13 |
July | 0.465704E+09 | 13417904.64 | 0.452287E+09 | 0.183288E+10 | 403750.91 |
August | 0.433531E+09 | 3585686.74 | 0.429946E+09 | 0.179397E+10 | 90415.15 |
September | 0.382168E+09 | 43792.41 | 0.382124E+09 | 0.129917E+10 | 26755096.44 |
October | 0.350076E+09 | 0.00 | 0.350076E+09 | 0.955338E+09 | 0.120273E+09 |
November | 0.290838E+09 | 0.00 | 0.290838E+09 | 0.581427E+09 | 0.314156E+09 |
December | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.350721E+09 | 0.570866E+09 |
Annual Sum or Average | 0.451159E+10 | 59056624.30 | 0.445253E+10 | 0.121215E+11 | 0.294180E+10 |
Minimum of Months | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.313527E+09 | 90415.15 |
Maximum of Months | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.183288E+10 | 0.684504E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283884E+09 | 0.00 | 0.283884E+09 | 0.313527E+09 | 0.684504E+09 |
February | 0.293921E+09 | 0.00 | 0.293921E+09 | 0.402372E+09 | 0.503452E+09 |
March | 0.373780E+09 | 0.00 | 0.373780E+09 | 0.651925E+09 | 0.407749E+09 |
April | 0.407544E+09 | 839712.81 | 0.406704E+09 | 0.917904E+09 | 0.238776E+09 |
May | 0.474018E+09 | 13902478.50 | 0.460115E+09 | 0.143037E+10 | 59820177.01 |
June | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.159187E+10 | 14955411.13 |
July | 0.465704E+09 | 13417904.64 | 0.452287E+09 | 0.183288E+10 | 403750.91 |
August | 0.433531E+09 | 3585686.74 | 0.429946E+09 | 0.179397E+10 | 90415.15 |
September | 0.382168E+09 | 43792.41 | 0.382124E+09 | 0.129917E+10 | 26755096.44 |
October | 0.350076E+09 | 0.00 | 0.350076E+09 | 0.955338E+09 | 0.120273E+09 |
November | 0.290838E+09 | 0.00 | 0.290838E+09 | 0.581427E+09 | 0.314156E+09 |
December | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.350721E+09 | 0.570866E+09 |
Annual Sum or Average | 0.451159E+10 | 59056624.30 | 0.445253E+10 | 0.121215E+11 | 0.294180E+10 |
Minimum of Months | 0.264969E+09 | 0.00 | 0.264969E+09 | 0.313527E+09 | 90415.15 |
Maximum of Months | 0.491154E+09 | 27267049.21 | 0.463887E+09 | 0.183288E+10 | 0.684504E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.988016E+09 | 0.298922E+09 | 0.689094E+09 | 0.133253E+10 | 0.123902E+10 |
February | 0.972513E+09 | 0.263555E+09 | 0.708958E+09 | 0.148068E+10 | 0.924295E+09 |
March | 0.118934E+10 | 0.293127E+09 | 0.896211E+09 | 0.210943E+10 | 0.757793E+09 |
April | 0.140136E+10 | 0.408307E+09 | 0.993048E+09 | 0.292256E+10 | 0.456031E+09 |
May | 0.161825E+10 | 0.515582E+09 | 0.110267E+10 | 0.406826E+10 | 0.116370E+09 |
June | 0.153371E+10 | 0.469023E+09 | 0.106469E+10 | 0.414601E+10 | 28068596.09 |
July | 0.147920E+10 | 0.426447E+09 | 0.105275E+10 | 0.462267E+10 | 718195.77 |
August | 0.151467E+10 | 0.464871E+09 | 0.104980E+10 | 0.475066E+10 | 182110.11 |
September | 0.137803E+10 | 0.425931E+09 | 0.952101E+09 | 0.371598E+10 | 49609335.52 |
October | 0.129211E+10 | 0.422130E+09 | 0.869977E+09 | 0.299808E+10 | 0.223929E+09 |
November | 0.104786E+10 | 0.331908E+09 | 0.715954E+09 | 0.200493E+10 | 0.582323E+09 |
December | 0.876414E+09 | 0.240452E+09 | 0.635962E+09 | 0.129954E+10 | 0.104368E+10 |
Annual Sum or Average | 0.152915E+11 | 0.456025E+10 | 0.107312E+11 | 0.354513E+11 | 0.542201E+10 |
Minimum of Months | 0.876414E+09 | 0.240452E+09 | 0.635962E+09 | 0.129954E+10 | 182110.11 |
Maximum of Months | 0.161825E+10 | 0.515582E+09 | 0.110267E+10 | 0.475066E+10 | 0.123902E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 39065258.48 | 11819103.90 | 27246154.59 | 52687071.75 | 48989552.31 |
February | 38452275.37 | 10420713.04 | 28031562.33 | 58544869.04 | 36545783.03 |
March | 47025345.96 | 11589972.09 | 35435373.87 | 83405081.67 | 29962453.94 |
April | 55408338.03 | 16144095.39 | 39264242.64 | 0.115555E+09 | 18031050.25 |
May | 63984314.02 | 20385644.58 | 43598669.44 | 0.160855E+09 | 4601182.28 |
June | 60641450.18 | 18544738.24 | 42096711.94 | 0.163929E+09 | 1109807.02 |
July | 58486056.92 | 16861338.40 | 41624718.52 | 0.182776E+09 | 28396.81 |
August | 59888712.98 | 18380572.30 | 41508140.68 | 0.187837E+09 | 7200.47 |
September | 54486149.10 | 16840947.48 | 37645201.62 | 0.146926E+09 | 1961508.46 |
October | 51088757.59 | 16690654.48 | 34398103.11 | 0.118541E+09 | 8853967.97 |
November | 41431482.81 | 13123324.59 | 28308158.22 | 79273287.43 | 23024510.77 |
December | 34652617.29 | 9507238.85 | 25145378.45 | 51382466.18 | 41266143.63 |
Annual Sum or Average | 0.604611E+09 | 0.180308E+09 | 0.424302E+09 | 0.140171E+10 | 0.214382E+09 |
Minimum of Months | 34652617.29 | 9507238.85 | 25145378.45 | 51382466.18 | 7200.47 |
Maximum of Months | 63984314.02 | 20385644.58 | 43598669.44 | 0.187837E+09 | 48989552.31 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917476E+09 | 0.431346E+09 | 0.486131E+09 | 0.144931E+10 | 0.672876E+09 |
February | 0.778174E+09 | 0.318306E+09 | 0.459868E+09 | 0.131493E+10 | 0.510062E+09 |
March | 0.709096E+09 | 0.192515E+09 | 0.516581E+09 | 0.134624E+10 | 0.421670E+09 |
April | 0.539423E+09 | 57188570.39 | 0.482235E+09 | 0.121847E+10 | 0.247681E+09 |
May | 0.472171E+09 | 7230741.31 | 0.464940E+09 | 0.141655E+10 | 62259661.39 |
June | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.144476E+10 | 13186027.72 |
July | 0.444665E+09 | 3778245.47 | 0.440887E+09 | 0.176179E+10 | 233832.00 |
August | 0.515775E+09 | 36544326.84 | 0.479230E+09 | 0.195683E+10 | 121872.39 |
September | 0.658116E+09 | 0.150825E+09 | 0.507290E+09 | 0.187506E+10 | 29912850.87 |
October | 0.890320E+09 | 0.353951E+09 | 0.536369E+09 | 0.202180E+10 | 0.132135E+09 |
November | 0.950519E+09 | 0.458219E+09 | 0.492300E+09 | 0.182732E+10 | 0.327888E+09 |
December | 0.911781E+09 | 0.450391E+09 | 0.461390E+09 | 0.153339E+10 | 0.571170E+09 |
Annual Sum or Average | 0.821785E+10 | 0.246083E+10 | 0.575702E+10 | 0.191665E+11 | 0.298920E+10 |
Minimum of Months | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.121847E+10 | 121872.39 |
Maximum of Months | 0.950519E+09 | 0.458219E+09 | 0.536369E+09 | 0.202180E+10 | 0.672876E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917476E+09 | 0.431346E+09 | 0.486131E+09 | 0.144931E+10 | 0.672876E+09 |
February | 0.778174E+09 | 0.318306E+09 | 0.459868E+09 | 0.131493E+10 | 0.510062E+09 |
March | 0.709096E+09 | 0.192515E+09 | 0.516581E+09 | 0.134624E+10 | 0.421670E+09 |
April | 0.539423E+09 | 57188570.39 | 0.482235E+09 | 0.121847E+10 | 0.247681E+09 |
May | 0.472171E+09 | 7230741.31 | 0.464940E+09 | 0.141655E+10 | 62259661.39 |
June | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.144476E+10 | 13186027.72 |
July | 0.444665E+09 | 3778245.47 | 0.440887E+09 | 0.176179E+10 | 233832.00 |
August | 0.515775E+09 | 36544326.84 | 0.479230E+09 | 0.195683E+10 | 121872.39 |
September | 0.658116E+09 | 0.150825E+09 | 0.507290E+09 | 0.187506E+10 | 29912850.87 |
October | 0.890320E+09 | 0.353951E+09 | 0.536369E+09 | 0.202180E+10 | 0.132135E+09 |
November | 0.950519E+09 | 0.458219E+09 | 0.492300E+09 | 0.182732E+10 | 0.327888E+09 |
December | 0.911781E+09 | 0.450391E+09 | 0.461390E+09 | 0.153339E+10 | 0.571170E+09 |
Annual Sum or Average | 0.821785E+10 | 0.246083E+10 | 0.575702E+10 | 0.191665E+11 | 0.298920E+10 |
Minimum of Months | 0.430333E+09 | 532545.65 | 0.429800E+09 | 0.121847E+10 | 121872.39 |
Maximum of Months | 0.950519E+09 | 0.458219E+09 | 0.536369E+09 | 0.202180E+10 | 0.672876E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.917418E+09 | 0.431318E+09 | 0.486100E+09 | 0.144922E+10 | 0.672834E+09 |
February | 0.778125E+09 | 0.318286E+09 | 0.459839E+09 | 0.131485E+10 | 0.510029E+09 |
March | 0.709051E+09 | 0.192502E+09 | 0.516549E+09 | 0.134616E+10 | 0.421643E+09 |
April | 0.539389E+09 | 57184956.40 | 0.482204E+09 | 0.121839E+10 | 0.247665E+09 |
May | 0.472141E+09 | 7230284.37 | 0.464911E+09 | 0.141646E+10 | 62255726.93 |
June | 0.430305E+09 | 532512.00 | 0.429773E+09 | 0.144467E+10 | 13185194.44 |
July | 0.444637E+09 | 3778006.70 | 0.440859E+09 | 0.176168E+10 | 233817.22 |
August | 0.515742E+09 | 36542017.44 | 0.479200E+09 | 0.195671E+10 | 121864.69 |
September | 0.658074E+09 | 0.150816E+09 | 0.507258E+09 | 0.187494E+10 | 29910960.55 |
October | 0.890264E+09 | 0.353928E+09 | 0.536335E+09 | 0.202167E+10 | 0.132127E+09 |
November | 0.950458E+09 | 0.458190E+09 | 0.492268E+09 | 0.182721E+10 | 0.327867E+09 |
December | 0.911724E+09 | 0.450362E+09 | 0.461361E+09 | 0.153330E+10 | 0.571134E+09 |
Annual Sum or Average | 0.821733E+10 | 0.246067E+10 | 0.575666E+10 | 0.191652E+11 | 0.298901E+10 |
Minimum of Months | 0.430305E+09 | 532512.00 | 0.429773E+09 | 0.121839E+10 | 121864.69 |
Maximum of Months | 0.950458E+09 | 0.458190E+09 | 0.536335E+09 | 0.202167E+10 | 0.672834E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.968932E+09 | 0.278284E+09 | 0.690647E+09 | 0.138440E+10 | 0.132893E+10 |
February | 0.999348E+09 | 0.284973E+09 | 0.714375E+09 | 0.158935E+10 | 0.984478E+09 |
March | 0.131059E+10 | 0.388002E+09 | 0.922587E+09 | 0.237267E+10 | 0.816053E+09 |
April | 0.138605E+10 | 0.389404E+09 | 0.996644E+09 | 0.290975E+10 | 0.497239E+09 |
May | 0.155900E+10 | 0.466668E+09 | 0.109233E+10 | 0.397313E+10 | 0.135875E+09 |
June | 0.155912E+10 | 0.491475E+09 | 0.106765E+10 | 0.420290E+10 | 33336690.48 |
July | 0.147800E+10 | 0.422826E+09 | 0.105518E+10 | 0.460960E+10 | 914759.50 |
August | 0.151627E+10 | 0.461009E+09 | 0.105526E+10 | 0.472685E+10 | 319665.55 |
September | 0.139583E+10 | 0.438529E+09 | 0.957304E+09 | 0.374680E+10 | 60296744.97 |
October | 0.128184E+10 | 0.414067E+09 | 0.867769E+09 | 0.299834E+10 | 0.255493E+09 |
November | 0.106604E+10 | 0.348630E+09 | 0.717415E+09 | 0.209546E+10 | 0.634691E+09 |
December | 0.922194E+09 | 0.278762E+09 | 0.643432E+09 | 0.146161E+10 | 0.111691E+10 |
Annual Sum or Average | 0.154432E+11 | 0.466263E+10 | 0.107806E+11 | 0.360709E+11 | 0.586454E+10 |
Minimum of Months | 0.922194E+09 | 0.278284E+09 | 0.643432E+09 | 0.138440E+10 | 319665.55 |
Maximum of Months | 0.155912E+10 | 0.491475E+09 | 0.109233E+10 | 0.472685E+10 | 0.132893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38310577.77 | 11003077.04 | 27307500.73 | 54737628.44 | 52544719.13 |
February | 39513211.75 | 11267528.36 | 28245683.39 | 62841165.13 | 38925358.51 |
March | 51819367.10 | 15341183.56 | 36478183.54 | 93813132.11 | 32265963.55 |
April | 54802937.33 | 15396622.59 | 39406314.74 | 0.115049E+09 | 19660356.06 |
May | 61641163.83 | 18451589.80 | 43189574.02 | 0.157094E+09 | 5372363.41 |
June | 61646131.46 | 19432416.19 | 42213715.27 | 0.166179E+09 | 1318093.42 |
July | 58438824.35 | 16718109.48 | 41720714.87 | 0.182259E+09 | 36167.84 |
August | 59951733.09 | 18227802.62 | 41723930.47 | 0.186895E+09 | 12639.03 |
September | 55189856.52 | 17338991.81 | 37850864.72 | 0.148145E+09 | 2384067.67 |
October | 50682477.21 | 16371773.25 | 34310703.96 | 0.118551E+09 | 10101933.10 |
November | 42150315.10 | 13784453.03 | 28365862.07 | 82852247.23 | 25095076.42 |
December | 36462607.41 | 11021956.80 | 25440650.61 | 57790712.53 | 44161467.18 |
Annual Sum or Average | 0.610609E+09 | 0.184356E+09 | 0.426254E+09 | 0.142621E+10 | 0.231878E+09 |
Minimum of Months | 36462607.41 | 11003077.04 | 25440650.61 | 54737628.44 | 12639.03 |
Maximum of Months | 61646131.46 | 19432416.19 | 43189574.02 | 0.186895E+09 | 52544719.13 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.962658E+09 | 0.194443E+10 |
February | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.121101E+10 | 0.146326E+10 |
March | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.194067E+10 | 0.122490E+10 |
April | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.273207E+10 | 0.737621E+09 |
May | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.428634E+10 | 0.191272E+09 |
June | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.479461E+10 | 45745114.17 |
July | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.554039E+10 | 1081293.56 |
August | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.545876E+10 | 193357.92 |
September | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.396897E+10 | 68591767.14 |
October | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.293553E+10 | 0.319340E+09 |
November | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.179445E+10 | 0.860145E+09 |
December | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.108715E+10 | 0.158669E+10 |
Annual Sum or Average | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.367126E+11 | 0.844327E+10 |
Minimum of Months | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.962658E+09 | 193357.92 |
Maximum of Months | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.554039E+10 | 0.194443E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.140312E+10 | 0.120458E+10 |
February | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.154185E+10 | 0.916523E+09 |
March | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.218114E+10 | 0.774499E+09 |
April | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.302210E+10 | 0.472367E+09 |
May | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.422940E+10 | 0.120680E+09 |
June | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.432592E+10 | 26447171.24 |
July | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.483879E+10 | 483132.55 |
August | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.499524E+10 | 75368.76 |
September | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.391349E+10 | 40351813.12 |
October | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.316016E+10 | 0.194257E+09 |
November | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.211631E+10 | 0.539491E+09 |
December | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.137728E+10 | 0.993480E+09 |
Annual Sum or Average | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.371048E+11 | 0.528323E+10 |
Minimum of Months | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.137728E+10 | 75368.76 |
Maximum of Months | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.499524E+10 | 0.120458E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.434425E+10 | 0.188262E+10 |
February | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.392893E+10 | 0.145203E+10 |
March | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.401566E+10 | 0.124653E+10 |
April | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.363745E+10 | 0.753758E+09 |
May | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.427821E+10 | 0.192917E+09 |
June | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.440159E+10 | 36838601.61 |
July | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.538065E+10 | 463140.37 |
August | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.602200E+10 | 108407.18 |
September | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.574714E+10 | 68321163.35 |
October | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.615579E+10 | 0.318644E+09 |
November | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.552050E+10 | 0.858911E+09 |
December | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.461080E+10 | 0.156514E+10 |
Annual Sum or Average | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.580430E+11 | 0.837629E+10 |
Minimum of Months | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.363745E+10 | 108407.18 |
Maximum of Months | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.615579E+10 | 0.188262E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.145305E+10 | 0.129049E+10 |
February | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.165290E+10 | 0.974929E+09 |
March | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.245266E+10 | 0.830597E+09 |
April | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.300756E+10 | 0.515621E+09 |
May | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.413070E+10 | 0.140770E+09 |
June | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.438929E+10 | 30709267.71 |
July | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.482711E+10 | 527092.80 |
August | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.496992E+10 | 220759.02 |
September | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.394386E+10 | 49722009.85 |
October | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.315988E+10 | 0.225456E+09 |
November | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.220776E+10 | 0.588464E+09 |
December | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.154148E+10 | 0.106127E+10 |
Annual Sum or Average | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.377362E+11 | 0.570878E+10 |
Minimum of Months | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.145305E+10 | 220759.02 |
Maximum of Months | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.496992E+10 | 0.129049E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 374.40 | 666.26 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 510.49 | 560.70 | 364.49 | 0.00 | 364.49 | 0.00 | 0.00 |
March | 727.40 | 429.23 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1050.06 | 272.21 | 471.70 | 0.97 | 470.73 | 0.00 | 0.00 |
May | 1589.95 | 70.18 | 530.94 | 15.57 | 515.37 | 0.00 | 0.00 |
June | 1838.64 | 17.86 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
July | 2055.12 | 0.37 | 521.63 | 15.03 | 506.60 | 0.00 | 0.00 |
August | 2026.08 | 0.08 | 485.59 | 4.02 | 481.57 | 0.00 | 0.00 |
September | 1522.84 | 25.74 | 442.33 | 0.05 | 442.28 | 0.00 | 0.00 |
October | 1092.26 | 113.32 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 695.62 | 309.18 | 336.62 | 0.00 | 336.62 | 0.00 | 0.00 |
December | 417.85 | 544.89 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Annual Sum or Average | 1162.42 | 249.32 | 429.19 | 5.62 | 423.57 | 0.00 | 0.00 |
Minimum of Months | 374.40 | 0.08 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Maximum of Months | 2055.12 | 666.26 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 536.31 | 417.94 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 644.84 | 354.76 | 417.90 | 113.25 | 304.65 | 0.00 | 0.00 |
March | 816.50 | 273.40 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1162.55 | 175.22 | 562.03 | 163.76 | 398.27 | 0.00 | 0.00 |
May | 1570.62 | 44.28 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1660.09 | 10.32 | 615.11 | 188.11 | 427.00 | 0.00 | 0.00 |
July | 1796.52 | 0.15 | 574.11 | 165.52 | 408.60 | 0.00 | 0.00 |
August | 1855.88 | 0.03 | 587.88 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1502.60 | 15.14 | 552.68 | 170.83 | 381.85 | 0.00 | 0.00 |
October | 1175.85 | 69.08 | 501.50 | 163.84 | 337.66 | 0.00 | 0.00 |
November | 818.54 | 195.24 | 420.26 | 133.12 | 287.14 | 0.00 | 0.00 |
December | 523.83 | 344.74 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1175.09 | 157.39 | 504.07 | 150.33 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 523.83 | 0.03 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1855.88 | 417.94 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1635.60 | 652.76 | 1027.66 | 483.15 | 544.51 | 0.00 | 0.00 |
February | 1630.93 | 560.63 | 965.01 | 394.73 | 570.28 | 0.00 | 0.00 |
March | 1499.98 | 438.17 | 794.25 | 215.63 | 578.62 | 0.00 | 0.00 |
April | 1398.55 | 277.63 | 624.34 | 66.19 | 558.15 | 0.00 | 0.00 |
May | 1587.01 | 69.98 | 528.87 | 8.10 | 520.77 | 0.00 | 0.00 |
June | 1688.33 | 14.03 | 498.07 | 0.62 | 497.46 | 0.00 | 0.00 |
July | 1996.56 | 0.12 | 498.06 | 4.23 | 493.83 | 0.00 | 0.00 |
August | 2236.93 | 0.05 | 577.71 | 40.93 | 536.78 | 0.00 | 0.00 |
September | 2207.31 | 25.46 | 761.72 | 174.57 | 587.15 | 0.00 | 0.00 |
October | 2291.19 | 113.15 | 997.24 | 396.46 | 600.78 | 0.00 | 0.00 |
November | 2129.88 | 311.78 | 1100.16 | 530.36 | 569.80 | 0.00 | 0.00 |
December | 1731.35 | 544.55 | 1021.28 | 504.48 | 516.80 | 0.00 | 0.00 |
Annual Sum or Average | 1837.60 | 249.17 | 781.77 | 234.10 | 547.67 | 0.00 | 0.00 |
Minimum of Months | 1398.55 | 0.05 | 498.06 | 0.62 | 493.83 | 0.00 | 0.00 |
Maximum of Months | 2291.19 | 652.76 | 1100.16 | 530.36 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 552.31 | 442.95 | 376.07 | 108.01 | 268.06 | 0.00 | 0.00 |
February | 689.53 | 373.82 | 429.43 | 122.46 | 306.97 | 0.00 | 0.00 |
March | 917.05 | 291.13 | 508.67 | 150.59 | 358.08 | 0.00 | 0.00 |
April | 1157.09 | 190.04 | 555.89 | 156.18 | 399.72 | 0.00 | 0.00 |
May | 1534.67 | 51.31 | 605.08 | 181.13 | 423.96 | 0.00 | 0.00 |
June | 1686.07 | 11.74 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1794.26 | 0.15 | 573.65 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1848.01 | 0.09 | 588.50 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1515.52 | 18.66 | 559.82 | 175.88 | 383.94 | 0.00 | 0.00 |
October | 1176.45 | 80.04 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 853.38 | 211.46 | 427.55 | 139.82 | 287.73 | 0.00 | 0.00 |
December | 583.52 | 365.07 | 357.93 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1195.24 | 168.70 | 509.07 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 552.31 | 0.09 | 357.93 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1848.01 | 442.95 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.17 | 766.68 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 498.97 | 624.31 | 364.48 | 0.00 | 364.48 | 0.00 | 0.00 |
March | 730.19 | 456.70 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1062.37 | 276.36 | 471.69 | 0.97 | 470.72 | 0.00 | 0.00 |
May | 1602.09 | 67.00 | 530.93 | 15.57 | 515.36 | 0.00 | 0.00 |
June | 1842.41 | 17.31 | 568.46 | 31.56 | 536.90 | 0.00 | 0.00 |
July | 2052.91 | 0.45 | 521.62 | 15.03 | 506.59 | 0.00 | 0.00 |
August | 2009.33 | 0.10 | 485.58 | 4.02 | 481.56 | 0.00 | 0.00 |
September | 1503.64 | 30.97 | 442.32 | 0.05 | 442.27 | 0.00 | 0.00 |
October | 1070.03 | 134.71 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 672.94 | 363.60 | 336.61 | 0.00 | 336.61 | 0.00 | 0.00 |
December | 392.83 | 639.40 | 296.78 | 0.00 | 296.78 | 0.00 | 0.00 |
Annual Sum or Average | 1153.09 | 279.85 | 429.18 | 5.62 | 423.56 | 0.00 | 0.00 |
Minimum of Months | 351.17 | 0.10 | 296.78 | 0.00 | 296.78 | 0.00 | 0.00 |
Maximum of Months | 2052.91 | 766.68 | 568.46 | 31.56 | 536.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 517.18 | 480.89 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 636.25 | 397.17 | 417.89 | 113.25 | 304.64 | 0.00 | 0.00 |
March | 818.71 | 294.11 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1172.11 | 182.89 | 562.02 | 163.75 | 398.27 | 0.00 | 0.00 |
May | 1578.97 | 45.17 | 628.08 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1662.78 | 11.26 | 615.10 | 188.10 | 427.00 | 0.00 | 0.00 |
July | 1794.15 | 0.28 | 574.10 | 165.51 | 408.59 | 0.00 | 0.00 |
August | 1843.82 | 0.07 | 587.87 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1490.32 | 19.90 | 552.67 | 170.82 | 381.85 | 0.00 | 0.00 |
October | 1163.61 | 86.91 | 501.49 | 163.84 | 337.65 | 0.00 | 0.00 |
November | 804.09 | 233.54 | 420.25 | 133.11 | 287.14 | 0.00 | 0.00 |
December | 504.38 | 405.07 | 340.15 | 93.32 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1168.60 | 178.73 | 504.06 | 150.32 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 504.38 | 0.07 | 340.15 | 93.32 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1843.82 | 480.89 | 628.08 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1623.30 | 753.65 | 1027.62 | 483.13 | 544.49 | 0.00 | 0.00 |
February | 1630.58 | 632.50 | 964.98 | 394.72 | 570.26 | 0.00 | 0.00 |
March | 1507.86 | 472.29 | 794.22 | 215.63 | 578.60 | 0.00 | 0.00 |
April | 1410.24 | 286.66 | 624.32 | 66.19 | 558.13 | 0.00 | 0.00 |
May | 1586.60 | 69.73 | 528.85 | 8.10 | 520.76 | 0.00 | 0.00 |
June | 1672.14 | 15.26 | 498.06 | 0.62 | 497.44 | 0.00 | 0.00 |
July | 1973.29 | 0.26 | 498.05 | 4.23 | 493.81 | 0.00 | 0.00 |
August | 2191.75 | 0.14 | 577.69 | 40.93 | 536.76 | 0.00 | 0.00 |
September | 2170.16 | 34.62 | 761.69 | 174.56 | 587.13 | 0.00 | 0.00 |
October | 2264.51 | 148.00 | 997.20 | 396.44 | 600.76 | 0.00 | 0.00 |
November | 2114.91 | 379.49 | 1100.11 | 530.33 | 569.78 | 0.00 | 0.00 |
December | 1717.47 | 639.74 | 1021.24 | 504.46 | 516.78 | 0.00 | 0.00 |
Annual Sum or Average | 1823.25 | 284.35 | 781.74 | 234.09 | 547.65 | 0.00 | 0.00 |
Minimum of Months | 1410.24 | 0.14 | 498.05 | 0.62 | 493.81 | 0.00 | 0.00 |
Maximum of Months | 2264.51 | 753.65 | 1100.11 | 530.33 | 600.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 537.31 | 515.78 | 376.06 | 108.01 | 268.05 | 0.00 | 0.00 |
February | 682.95 | 423.03 | 429.42 | 122.45 | 306.97 | 0.00 | 0.00 |
March | 920.88 | 316.73 | 508.66 | 150.59 | 358.07 | 0.00 | 0.00 |
April | 1166.98 | 199.42 | 555.88 | 156.17 | 399.71 | 0.00 | 0.00 |
May | 1542.05 | 52.74 | 605.08 | 181.12 | 423.95 | 0.00 | 0.00 |
June | 1685.60 | 13.37 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1789.08 | 0.36 | 573.64 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1834.58 | 0.12 | 588.49 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1502.68 | 24.18 | 559.81 | 175.88 | 383.93 | 0.00 | 0.00 |
October | 1163.71 | 99.16 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 840.40 | 254.55 | 427.54 | 139.82 | 287.72 | 0.00 | 0.00 |
December | 567.28 | 433.49 | 357.92 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1189.02 | 193.32 | 509.06 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 537.31 | 0.12 | 357.92 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1834.58 | 515.78 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.42 | 725.97 | 317.97 | 0.00 | 317.97 | 0.00 | 0.00 |
February | 500.58 | 604.85 | 364.49 | 0.00 | 364.49 | 0.00 | 0.00 |
March | 724.56 | 457.33 | 418.66 | 0.00 | 418.66 | 0.00 | 0.00 |
April | 1054.04 | 284.58 | 471.70 | 0.97 | 470.73 | 0.00 | 0.00 |
May | 1600.33 | 71.41 | 530.94 | 15.57 | 515.37 | 0.00 | 0.00 |
June | 1849.77 | 17.65 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
July | 2068.54 | 0.40 | 521.63 | 15.03 | 506.60 | 0.00 | 0.00 |
August | 2038.07 | 0.07 | 485.59 | 4.02 | 481.57 | 0.00 | 0.00 |
September | 1531.24 | 26.46 | 442.33 | 0.05 | 442.28 | 0.00 | 0.00 |
October | 1096.00 | 119.23 | 392.11 | 0.00 | 392.11 | 0.00 | 0.00 |
November | 692.30 | 331.85 | 336.62 | 0.00 | 336.62 | 0.00 | 0.00 |
December | 405.89 | 592.40 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Annual Sum or Average | 1164.15 | 267.73 | 429.19 | 5.62 | 423.57 | 0.00 | 0.00 |
Minimum of Months | 359.42 | 0.07 | 296.79 | 0.00 | 296.79 | 0.00 | 0.00 |
Maximum of Months | 2068.54 | 725.97 | 568.47 | 31.56 | 536.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 523.86 | 449.74 | 383.47 | 116.02 | 267.45 | 0.00 | 0.00 |
February | 637.34 | 378.85 | 417.90 | 113.25 | 304.65 | 0.00 | 0.00 |
March | 814.34 | 289.16 | 461.61 | 113.77 | 347.84 | 0.00 | 0.00 |
April | 1165.94 | 182.24 | 562.03 | 163.76 | 398.27 | 0.00 | 0.00 |
May | 1579.08 | 45.06 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
June | 1668.95 | 10.20 | 615.11 | 188.11 | 427.00 | 0.00 | 0.00 |
July | 1806.60 | 0.18 | 574.11 | 165.52 | 408.60 | 0.00 | 0.00 |
August | 1865.01 | 0.03 | 587.88 | 180.43 | 407.45 | 0.00 | 0.00 |
September | 1509.83 | 15.57 | 552.68 | 170.83 | 381.85 | 0.00 | 0.00 |
October | 1179.87 | 72.53 | 501.50 | 163.84 | 337.66 | 0.00 | 0.00 |
November | 816.48 | 208.14 | 420.26 | 133.12 | 287.14 | 0.00 | 0.00 |
December | 514.22 | 370.92 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Annual Sum or Average | 1176.59 | 167.53 | 504.07 | 150.33 | 353.74 | 0.00 | 0.00 |
Minimum of Months | 514.22 | 0.03 | 340.16 | 93.33 | 246.83 | 0.00 | 0.00 |
Maximum of Months | 1865.01 | 449.74 | 628.09 | 200.11 | 427.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1621.96 | 702.89 | 1027.66 | 483.15 | 544.51 | 0.00 | 0.00 |
February | 1624.06 | 600.21 | 965.01 | 394.73 | 570.28 | 0.00 | 0.00 |
March | 1499.28 | 465.40 | 794.25 | 215.63 | 578.62 | 0.00 | 0.00 |
April | 1403.34 | 290.80 | 624.34 | 66.19 | 558.15 | 0.00 | 0.00 |
May | 1597.30 | 72.03 | 528.87 | 8.10 | 520.77 | 0.00 | 0.00 |
June | 1698.14 | 14.21 | 498.07 | 0.62 | 497.46 | 0.00 | 0.00 |
July | 2008.90 | 0.17 | 498.06 | 4.23 | 493.83 | 0.00 | 0.00 |
August | 2248.36 | 0.04 | 577.71 | 40.93 | 536.78 | 0.00 | 0.00 |
September | 2217.26 | 26.36 | 761.72 | 174.57 | 587.15 | 0.00 | 0.00 |
October | 2298.31 | 118.97 | 997.24 | 396.46 | 600.78 | 0.00 | 0.00 |
November | 2129.82 | 331.37 | 1100.16 | 530.36 | 569.80 | 0.00 | 0.00 |
December | 1721.47 | 584.36 | 1021.28 | 504.48 | 516.80 | 0.00 | 0.00 |
Annual Sum or Average | 1840.53 | 265.61 | 781.77 | 234.10 | 547.67 | 0.00 | 0.00 |
Minimum of Months | 1403.34 | 0.04 | 498.06 | 0.62 | 493.83 | 0.00 | 0.00 |
Maximum of Months | 2298.31 | 702.89 | 1100.16 | 530.36 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 542.51 | 481.81 | 376.07 | 108.01 | 268.06 | 0.00 | 0.00 |
February | 683.24 | 403.00 | 429.43 | 122.46 | 306.97 | 0.00 | 0.00 |
March | 915.72 | 310.11 | 508.67 | 150.59 | 358.08 | 0.00 | 0.00 |
April | 1160.33 | 198.93 | 555.89 | 156.18 | 399.72 | 0.00 | 0.00 |
May | 1542.23 | 52.56 | 605.08 | 181.13 | 423.96 | 0.00 | 0.00 |
June | 1693.40 | 11.85 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
July | 1802.23 | 0.20 | 573.65 | 164.11 | 409.54 | 0.00 | 0.00 |
August | 1855.56 | 0.08 | 588.50 | 178.93 | 409.57 | 0.00 | 0.00 |
September | 1521.55 | 19.18 | 559.82 | 175.88 | 383.94 | 0.00 | 0.00 |
October | 1179.76 | 84.18 | 497.51 | 160.71 | 336.80 | 0.00 | 0.00 |
November | 851.76 | 227.03 | 427.55 | 139.82 | 287.73 | 0.00 | 0.00 |
December | 575.52 | 396.23 | 357.93 | 108.19 | 249.73 | 0.00 | 0.00 |
Annual Sum or Average | 1196.61 | 181.02 | 509.07 | 153.70 | 355.37 | 0.00 | 0.00 |
Minimum of Months | 542.51 | 0.08 | 357.93 | 108.01 | 249.73 | 0.00 | 0.00 |
Maximum of Months | 1855.56 | 481.81 | 625.30 | 197.11 | 428.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100280E+10 | 0.178451E+10 | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.00 | 0.00 |
February | 0.123498E+10 | 0.135644E+10 | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.00 | 0.00 |
March | 0.194828E+10 | 0.114965E+10 | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.00 | 0.00 |
April | 0.272177E+10 | 0.705560E+09 | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.00 | 0.00 |
May | 0.425853E+10 | 0.187958E+09 | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.00 | 0.00 |
June | 0.476575E+10 | 46299194.22 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
July | 0.550443E+10 | 991082.96 | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.00 | 0.00 |
August | 0.542665E+10 | 224219.01 | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.00 | 0.00 |
September | 0.394720E+10 | 66714314.55 | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.00 | 0.00 |
October | 0.292552E+10 | 0.303520E+09 | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.00 | 0.00 |
November | 0.180304E+10 | 0.801395E+09 | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.00 | 0.00 |
December | 0.111917E+10 | 0.145944E+10 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366581E+11 | 0.786270E+10 | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100280E+10 | 224219.01 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550443E+10 | 0.178451E+10 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143644E+10 | 0.111941E+10 | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.00 | 0.00 |
February | 0.156000E+10 | 0.858242E+09 | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.00 | 0.00 |
March | 0.218691E+10 | 0.732281E+09 | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.00 | 0.00 |
April | 0.301332E+10 | 0.454162E+09 | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.00 | 0.00 |
May | 0.420674E+10 | 0.118605E+09 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
June | 0.430296E+10 | 26759657.21 | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.00 | 0.00 |
July | 0.481179E+10 | 389019.18 | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.00 | 0.00 |
August | 0.497078E+10 | 86172.08 | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.00 | 0.00 |
September | 0.389475E+10 | 39241293.75 | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.00 | 0.00 |
October | 0.314941E+10 | 0.185031E+09 | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.00 | 0.00 |
November | 0.212165E+10 | 0.506054E+09 | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.00 | 0.00 |
December | 0.140303E+10 | 0.923349E+09 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.370578E+11 | 0.496361E+10 | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140303E+10 | 86172.08 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497078E+10 | 0.111941E+10 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438078E+10 | 0.174836E+10 | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.00 | 0.00 |
February | 0.394555E+10 | 0.135626E+10 | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.00 | 0.00 |
March | 0.401756E+10 | 0.117359E+10 | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.00 | 0.00 |
April | 0.362505E+10 | 0.719621E+09 | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.00 | 0.00 |
May | 0.425064E+10 | 0.187435E+09 | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.00 | 0.00 |
June | 0.437614E+10 | 36371276.88 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
July | 0.534758E+10 | 316359.86 | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.00 | 0.00 |
August | 0.599139E+10 | 129637.78 | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.00 | 0.00 |
September | 0.572136E+10 | 65991562.32 | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.00 | 0.00 |
October | 0.613673E+10 | 0.303053E+09 | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.00 | 0.00 |
November | 0.552066E+10 | 0.808145E+09 | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.00 | 0.00 |
December | 0.463723E+10 | 0.145852E+10 | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579507E+11 | 0.785779E+10 | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362505E+10 | 129637.78 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.613673E+10 | 0.174836E+10 | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147930E+10 | 0.118640E+10 | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.00 | 0.00 |
February | 0.166810E+10 | 0.904341E+09 | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.00 | 0.00 |
March | 0.245623E+10 | 0.779753E+09 | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.00 | 0.00 |
April | 0.299918E+10 | 0.492583E+09 | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.00 | 0.00 |
May | 0.411047E+10 | 0.137419E+09 | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.00 | 0.00 |
June | 0.437030E+10 | 30436538.15 | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.00 | 0.00 |
July | 0.480574E+10 | 392388.75 | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.00 | 0.00 |
August | 0.494970E+10 | 241618.97 | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.00 | 0.00 |
September | 0.392824E+10 | 48359166.06 | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.00 | 0.00 |
October | 0.315100E+10 | 0.214384E+09 | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.00 | 0.00 |
November | 0.221196E+10 | 0.548107E+09 | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.00 | 0.00 |
December | 0.156289E+10 | 0.977790E+09 | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376931E+11 | 0.532021E+10 | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147930E+10 | 241618.97 | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494970E+10 | 0.118640E+10 | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.940569E+09 | 0.205347E+10 | 0.851641E+09 | 0.00 | 0.851641E+09 | 0.00 | 0.00 |
February | 0.120710E+10 | 0.151033E+10 | 0.881752E+09 | 0.00 | 0.881752E+09 | 0.00 | 0.00 |
March | 0.195575E+10 | 0.122323E+10 | 0.112133E+10 | 0.00 | 0.112133E+10 | 0.00 | 0.00 |
April | 0.275367E+10 | 0.716318E+09 | 0.122262E+10 | 2519115.86 | 0.122010E+10 | 0.00 | 0.00 |
May | 0.429104E+10 | 0.179459E+09 | 0.142203E+10 | 41707061.80 | 0.138033E+10 | 0.00 | 0.00 |
June | 0.477551E+10 | 44866587.63 | 0.147344E+10 | 81800414.70 | 0.139164E+10 | 0.00 | 0.00 |
July | 0.549853E+10 | 1211311.08 | 0.139709E+10 | 40253353.26 | 0.135684E+10 | 0.00 | 0.00 |
August | 0.538179E+10 | 271267.97 | 0.130058E+10 | 10756963.82 | 0.128982E+10 | 0.00 | 0.00 |
September | 0.389745E+10 | 80265061.96 | 0.114649E+10 | 131376.06 | 0.114636E+10 | 0.00 | 0.00 |
October | 0.286596E+10 | 0.360817E+09 | 0.105022E+10 | 0.00 | 0.105022E+10 | 0.00 | 0.00 |
November | 0.174425E+10 | 0.942454E+09 | 0.872504E+09 | 0.00 | 0.872504E+09 | 0.00 | 0.00 |
December | 0.105215E+10 | 0.171257E+10 | 0.794897E+09 | 0.00 | 0.794897E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.363638E+11 | 0.882526E+10 | 0.135346E+11 | 0.177168E+09 | 0.133574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.940569E+09 | 271267.97 | 0.794897E+09 | 0.00 | 0.794897E+09 | 0.00 | 0.00 |
Maximum of Months | 0.549853E+10 | 0.205347E+10 | 0.147344E+10 | 81800414.70 | 0.139164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138522E+10 | 0.128800E+10 | 0.102708E+10 | 0.310741E+09 | 0.716340E+09 | 0.00 | 0.00 |
February | 0.153923E+10 | 0.960841E+09 | 0.101096E+10 | 0.273975E+09 | 0.736990E+09 | 0.00 | 0.00 |
March | 0.219284E+10 | 0.787755E+09 | 0.123636E+10 | 0.304717E+09 | 0.931646E+09 | 0.00 | 0.00 |
April | 0.303811E+10 | 0.474062E+09 | 0.145676E+10 | 0.424451E+09 | 0.103231E+10 | 0.00 | 0.00 |
May | 0.422912E+10 | 0.120972E+09 | 0.168224E+10 | 0.535968E+09 | 0.114627E+10 | 0.00 | 0.00 |
June | 0.430994E+10 | 29178403.11 | 0.159435E+10 | 0.487568E+09 | 0.110678E+10 | 0.00 | 0.00 |
July | 0.480545E+10 | 746592.58 | 0.153768E+10 | 0.443309E+09 | 0.109437E+10 | 0.00 | 0.00 |
August | 0.493850E+10 | 189310.58 | 0.157456E+10 | 0.483251E+09 | 0.109131E+10 | 0.00 | 0.00 |
September | 0.386291E+10 | 51570843.98 | 0.143252E+10 | 0.442772E+09 | 0.989746E+09 | 0.00 | 0.00 |
October | 0.311662E+10 | 0.232783E+09 | 0.134320E+10 | 0.438821E+09 | 0.904375E+09 | 0.00 | 0.00 |
November | 0.208421E+10 | 0.605347E+09 | 0.108929E+10 | 0.345031E+09 | 0.744262E+09 | 0.00 | 0.00 |
December | 0.135092E+10 | 0.108495E+10 | 0.911067E+09 | 0.249959E+09 | 0.661108E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368530E+11 | 0.563640E+10 | 0.158961E+11 | 0.474056E+10 | 0.111555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135092E+10 | 189310.58 | 0.911067E+09 | 0.249959E+09 | 0.661108E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493850E+10 | 0.128800E+10 | 0.168224E+10 | 0.535968E+09 | 0.114627E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434784E+10 | 0.201859E+10 | 0.275237E+10 | 0.129401E+10 | 0.145836E+10 | 0.00 | 0.00 |
February | 0.394471E+10 | 0.153015E+10 | 0.233447E+10 | 0.954898E+09 | 0.137958E+10 | 0.00 | 0.00 |
March | 0.403865E+10 | 0.126498E+10 | 0.212724E+10 | 0.577531E+09 | 0.154971E+10 | 0.00 | 0.00 |
April | 0.365534E+10 | 0.743027E+09 | 0.161824E+10 | 0.171562E+09 | 0.144667E+10 | 0.00 | 0.00 |
May | 0.424956E+10 | 0.186775E+09 | 0.141648E+10 | 21691766.98 | 0.139479E+10 | 0.00 | 0.00 |
June | 0.433419E+10 | 39557249.88 | 0.129097E+10 | 1597603.30 | 0.128937E+10 | 0.00 | 0.00 |
July | 0.528525E+10 | 701481.23 | 0.133397E+10 | 11334497.64 | 0.132263E+10 | 0.00 | 0.00 |
August | 0.587037E+10 | 365609.48 | 0.154729E+10 | 0.109631E+09 | 0.143766E+10 | 0.00 | 0.00 |
September | 0.562505E+10 | 89736662.29 | 0.197431E+10 | 0.452466E+09 | 0.152184E+10 | 0.00 | 0.00 |
October | 0.606528E+10 | 0.396397E+09 | 0.267090E+10 | 0.106183E+10 | 0.160907E+10 | 0.00 | 0.00 |
November | 0.548185E+10 | 0.983644E+09 | 0.285150E+10 | 0.137463E+10 | 0.147687E+10 | 0.00 | 0.00 |
December | 0.460008E+10 | 0.171347E+10 | 0.273529E+10 | 0.135114E+10 | 0.138414E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574982E+11 | 0.896740E+10 | 0.246530E+11 | 0.738232E+10 | 0.172707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365534E+10 | 365609.48 | 0.129097E+10 | 1597603.30 | 0.128937E+10 | 0.00 | 0.00 |
Maximum of Months | 0.606528E+10 | 0.201859E+10 | 0.285150E+10 | 0.137463E+10 | 0.160907E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143913E+10 | 0.138148E+10 | 0.100724E+10 | 0.289287E+09 | 0.717955E+09 | 0.00 | 0.00 |
February | 0.165219E+10 | 0.102340E+10 | 0.103886E+10 | 0.296240E+09 | 0.742621E+09 | 0.00 | 0.00 |
March | 0.246649E+10 | 0.848319E+09 | 0.136241E+10 | 0.403343E+09 | 0.959066E+09 | 0.00 | 0.00 |
April | 0.302480E+10 | 0.516900E+09 | 0.144085E+10 | 0.404800E+09 | 0.103605E+10 | 0.00 | 0.00 |
May | 0.413023E+10 | 0.141248E+09 | 0.162064E+10 | 0.485120E+09 | 0.113552E+10 | 0.00 | 0.00 |
June | 0.436908E+10 | 34654783.89 | 0.162077E+10 | 0.510907E+09 | 0.110986E+10 | 0.00 | 0.00 |
July | 0.479186E+10 | 950927.34 | 0.153644E+10 | 0.439544E+09 | 0.109690E+10 | 0.00 | 0.00 |
August | 0.491374E+10 | 332304.58 | 0.157622E+10 | 0.479236E+09 | 0.109698E+10 | 0.00 | 0.00 |
September | 0.389494E+10 | 62680812.63 | 0.145102E+10 | 0.455868E+09 | 0.995155E+09 | 0.00 | 0.00 |
October | 0.311689E+10 | 0.265595E+09 | 0.133252E+10 | 0.430439E+09 | 0.902079E+09 | 0.00 | 0.00 |
November | 0.217831E+10 | 0.659786E+09 | 0.110819E+10 | 0.362414E+09 | 0.745781E+09 | 0.00 | 0.00 |
December | 0.151940E+10 | 0.116107E+10 | 0.958656E+09 | 0.289784E+09 | 0.668872E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374971E+11 | 0.609641E+10 | 0.160538E+11 | 0.484698E+10 | 0.112068E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143913E+10 | 332304.58 | 0.958656E+09 | 0.289287E+09 | 0.668872E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491374E+10 | 0.138148E+10 | 0.162077E+10 | 0.510907E+09 | 0.113552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.962658E+09 | 0.194443E+10 | 0.851660E+09 | 0.00 | 0.851660E+09 | 0.00 | 0.00 |
February | 0.121101E+10 | 0.146326E+10 | 0.881771E+09 | 0.00 | 0.881771E+09 | 0.00 | 0.00 |
March | 0.194067E+10 | 0.122490E+10 | 0.112135E+10 | 0.00 | 0.112135E+10 | 0.00 | 0.00 |
April | 0.273207E+10 | 0.737621E+09 | 0.122264E+10 | 2519189.90 | 0.122012E+10 | 0.00 | 0.00 |
May | 0.428634E+10 | 0.191272E+09 | 0.142206E+10 | 41708287.71 | 0.138036E+10 | 0.00 | 0.00 |
June | 0.479461E+10 | 45745114.17 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
July | 0.554039E+10 | 1081293.56 | 0.139712E+10 | 40254536.45 | 0.135687E+10 | 0.00 | 0.00 |
August | 0.545876E+10 | 193357.92 | 0.130060E+10 | 10757280.01 | 0.128985E+10 | 0.00 | 0.00 |
September | 0.396897E+10 | 68591767.14 | 0.114651E+10 | 131379.92 | 0.114638E+10 | 0.00 | 0.00 |
October | 0.293553E+10 | 0.319340E+09 | 0.105024E+10 | 0.00 | 0.105024E+10 | 0.00 | 0.00 |
November | 0.179445E+10 | 0.860145E+09 | 0.872523E+09 | 0.00 | 0.872523E+09 | 0.00 | 0.00 |
December | 0.108715E+10 | 0.158669E+10 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367126E+11 | 0.844327E+10 | 0.135349E+11 | 0.177173E+09 | 0.133577E+11 | 0.00 | 0.00 |
Minimum of Months | 0.962658E+09 | 193357.92 | 0.794915E+09 | 0.00 | 0.794915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554039E+10 | 0.194443E+10 | 0.147347E+10 | 81802819.11 | 0.139167E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140312E+10 | 0.120458E+10 | 0.102710E+10 | 0.310747E+09 | 0.716350E+09 | 0.00 | 0.00 |
February | 0.154185E+10 | 0.916523E+09 | 0.101098E+10 | 0.273981E+09 | 0.737000E+09 | 0.00 | 0.00 |
March | 0.218114E+10 | 0.774499E+09 | 0.123638E+10 | 0.304723E+09 | 0.931659E+09 | 0.00 | 0.00 |
April | 0.302210E+10 | 0.472367E+09 | 0.145679E+10 | 0.424460E+09 | 0.103233E+10 | 0.00 | 0.00 |
May | 0.422940E+10 | 0.120680E+09 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
June | 0.432592E+10 | 26447171.24 | 0.159437E+10 | 0.487577E+09 | 0.110680E+10 | 0.00 | 0.00 |
July | 0.483879E+10 | 483132.55 | 0.153770E+10 | 0.443317E+09 | 0.109439E+10 | 0.00 | 0.00 |
August | 0.499524E+10 | 75368.76 | 0.157458E+10 | 0.483261E+09 | 0.109132E+10 | 0.00 | 0.00 |
September | 0.391349E+10 | 40351813.12 | 0.143254E+10 | 0.442781E+09 | 0.989759E+09 | 0.00 | 0.00 |
October | 0.316016E+10 | 0.194257E+09 | 0.134322E+10 | 0.438830E+09 | 0.904387E+09 | 0.00 | 0.00 |
November | 0.211631E+10 | 0.539491E+09 | 0.108931E+10 | 0.345038E+09 | 0.744272E+09 | 0.00 | 0.00 |
December | 0.137728E+10 | 0.993480E+09 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.371048E+11 | 0.528323E+10 | 0.158963E+11 | 0.474066E+10 | 0.111557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137728E+10 | 75368.76 | 0.911081E+09 | 0.249964E+09 | 0.661117E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499524E+10 | 0.120458E+10 | 0.168226E+10 | 0.535978E+09 | 0.114629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.434425E+10 | 0.188262E+10 | 0.275248E+10 | 0.129406E+10 | 0.145841E+10 | 0.00 | 0.00 |
February | 0.392893E+10 | 0.145203E+10 | 0.233456E+10 | 0.954937E+09 | 0.137962E+10 | 0.00 | 0.00 |
March | 0.401566E+10 | 0.124653E+10 | 0.212732E+10 | 0.577555E+09 | 0.154976E+10 | 0.00 | 0.00 |
April | 0.363745E+10 | 0.753758E+09 | 0.161829E+10 | 0.171569E+09 | 0.144672E+10 | 0.00 | 0.00 |
May | 0.427821E+10 | 0.192917E+09 | 0.141652E+10 | 21692667.17 | 0.139483E+10 | 0.00 | 0.00 |
June | 0.440159E+10 | 36838601.61 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
July | 0.538065E+10 | 463140.37 | 0.133400E+10 | 11334968.01 | 0.132267E+10 | 0.00 | 0.00 |
August | 0.602200E+10 | 108407.18 | 0.154734E+10 | 0.109635E+09 | 0.143770E+10 | 0.00 | 0.00 |
September | 0.574714E+10 | 68321163.35 | 0.197437E+10 | 0.452485E+09 | 0.152189E+10 | 0.00 | 0.00 |
October | 0.615579E+10 | 0.318644E+09 | 0.267100E+10 | 0.106187E+10 | 0.160913E+10 | 0.00 | 0.00 |
November | 0.552050E+10 | 0.858911E+09 | 0.285160E+10 | 0.137469E+10 | 0.147692E+10 | 0.00 | 0.00 |
December | 0.461080E+10 | 0.156514E+10 | 0.273539E+10 | 0.135120E+10 | 0.138419E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580430E+11 | 0.837629E+10 | 0.246539E+11 | 0.738263E+10 | 0.172713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363745E+10 | 108407.18 | 0.129101E+10 | 1597669.60 | 0.128941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.615579E+10 | 0.188262E+10 | 0.285160E+10 | 0.137469E+10 | 0.160913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145305E+10 | 0.129049E+10 | 0.100726E+10 | 0.289292E+09 | 0.717963E+09 | 0.00 | 0.00 |
February | 0.165290E+10 | 0.974929E+09 | 0.103887E+10 | 0.296245E+09 | 0.742629E+09 | 0.00 | 0.00 |
March | 0.245266E+10 | 0.830597E+09 | 0.136243E+10 | 0.403349E+09 | 0.959076E+09 | 0.00 | 0.00 |
April | 0.300756E+10 | 0.515621E+09 | 0.144087E+10 | 0.404807E+09 | 0.103606E+10 | 0.00 | 0.00 |
May | 0.413070E+10 | 0.140770E+09 | 0.162066E+10 | 0.485128E+09 | 0.113553E+10 | 0.00 | 0.00 |
June | 0.438929E+10 | 30709267.71 | 0.162079E+10 | 0.510916E+09 | 0.110987E+10 | 0.00 | 0.00 |
July | 0.482711E+10 | 527092.80 | 0.153646E+10 | 0.439551E+09 | 0.109691E+10 | 0.00 | 0.00 |
August | 0.496992E+10 | 220759.02 | 0.157624E+10 | 0.479244E+09 | 0.109700E+10 | 0.00 | 0.00 |
September | 0.394386E+10 | 49722009.85 | 0.145104E+10 | 0.455876E+09 | 0.995166E+09 | 0.00 | 0.00 |
October | 0.315988E+10 | 0.225456E+09 | 0.133253E+10 | 0.430446E+09 | 0.902089E+09 | 0.00 | 0.00 |
November | 0.220776E+10 | 0.588464E+09 | 0.110821E+10 | 0.362420E+09 | 0.745789E+09 | 0.00 | 0.00 |
December | 0.154148E+10 | 0.106127E+10 | 0.958669E+09 | 0.289789E+09 | 0.668880E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377362E+11 | 0.570878E+10 | 0.160540E+11 | 0.484706E+10 | 0.112070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145305E+10 | 220759.02 | 0.958669E+09 | 0.289292E+09 | 0.668880E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496992E+10 | 0.129049E+10 | 0.162079E+10 | 0.510916E+09 | 0.113553E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.354670E+10 | -0.331502E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231681833.7 | 60.05 | 0.00 | 0.00 |
February | 0.314020E+10 | -0.293107E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209129150.4 | 60.05 | 0.00 | 0.00 |
March | 0.346322E+10 | -0.323128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231943666.8 | 60.05 | 0.00 | 0.00 |
April | 0.284645E+10 | -0.262248E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223965056.9 | 60.05 | 0.00 | 0.00 |
May | 0.274840E+10 | -0.251643E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231969039.6 | 60.05 | 0.00 | 0.00 |
June | 0.250732E+10 | -0.228242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224898558.1 | 60.05 | 0.00 | 0.00 |
July | 0.231989E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233333458.9 | 60.05 | 0.00 | 0.00 |
August | 0.264302E+10 | -0.240878E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234241839.1 | 60.05 | 0.00 | 0.00 |
September | 0.261665E+10 | -0.239148E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225164317.3 | 60.05 | 0.00 | 0.00 |
October | 0.299659E+10 | -0.276466E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231927496.4 | 60.05 | 0.00 | 0.00 |
November | 0.322375E+10 | -0.299995E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223803473.0 | 60.05 | 0.00 | 0.00 |
December | 0.339597E+10 | -0.316457E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231394528.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.354481E+11 | -0.327147E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273345E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.231989E+10 | -0.331502E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234241839.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.354670E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209129150.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4184.40 | 34.11 | 310.83 | 292.67 | 1096.35 | 25.00 | 290.00 | 280.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2152.07 | 24.99 | 142.00 | 274.00 | 976.29 | 20.81 | 177.67 | 244.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:30 | 1580.47 | 18.41 | 5.00 | 313.33 | 828.66 | 20.38 | 146.83 | 277.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 1229.88 | 17.41 | 0.00 | 321.83 | 656.40 | 19.47 | 86.17 | 284.00 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1042.30 | 17.35 | 0.00 | 348.50 | 574.90 | 19.47 | 19.17 | 303.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 996.87 | 17.25 | 0.00 | 343.50 | 558.78 | 19.41 | 9.83 | 296.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-07:30 | 1048.58 | 17.17 | 0.00 | 344.00 | 580.68 | 19.32 | 42.50 | 303.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1233.60 | 17.67 | 0.00 | 342.67 | 666.59 | 19.79 | 135.67 | 303.33 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1549.25 | 18.40 | 0.00 | 318.17 | 824.33 | 20.55 | 188.67 | 284.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 2081.82 | 20.37 | 34.50 | 317.17 | 1000.65 | 21.45 | 232.50 | 288.00 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3519.92 | 31.75 | 256.33 | 297.67 | 1136.11 | 24.84 | 301.33 | 282.00 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4173.11 | 34.49 | 307.00 | 288.83 | 1170.91 | 26.19 | 288.00 | 275.50 |
Annual Sum or Average | 4323.33 | 0.53 | 1972.52 | 21.91 | 1055.67 | 3802.33 | 818.86 | 21.21 | 1918.33 | 3422.50 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 996.87 | 17.17 | 0.00 | 274.00 | 558.78 | 19.32 | 9.83 | 244.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 4184.40 | 34.49 | 310.83 | 348.50 | 1170.91 | 26.19 | 301.33 | 303.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1519.85 | 21.79 | 111.83 | 272.83 | 801.99 | 22.51 | 80.83 | 234.00 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1642.20 | 21.37 | 102.50 | 261.33 | 710.00 | 20.78 | 47.17 | 224.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1529.48 | 19.19 | 83.83 | 306.67 | 790.84 | 21.38 | 66.00 | 268.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1800.14 | 20.38 | 109.33 | 318.83 | 923.09 | 21.38 | 79.83 | 281.33 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 2033.08 | 20.26 | 118.83 | 355.50 | 869.57 | 20.94 | 67.83 | 319.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:10 | 1953.33 | 20.00 | 114.33 | 349.17 | 857.28 | 21.00 | 66.67 | 316.33 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1843.92 | 19.92 | 114.17 | 347.33 | 818.68 | 20.66 | 61.83 | 309.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1898.99 | 20.51 | 113.83 | 340.00 | 852.05 | 20.40 | 56.00 | 305.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1892.81 | 21.36 | 107.00 | 310.17 | 979.72 | 22.35 | 77.33 | 283.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:49 | 1760.11 | 21.27 | 104.67 | 303.83 | 915.95 | 22.32 | 76.00 | 272.83 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1511.99 | 20.50 | 84.33 | 275.33 | 789.22 | 22.27 | 63.00 | 241.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-07:19 | 1251.77 | 20.34 | 85.50 | 267.50 | 630.87 | 20.92 | 50.67 | 223.00 |
Annual Sum or Average | 4323.33 | 0.54 | 1737.44 | 20.54 | 1250.17 | 3708.50 | 833.10 | 21.38 | 793.17 | 3279.67 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1251.77 | 19.19 | 83.83 | 261.33 | 630.87 | 20.40 | 47.17 | 223.00 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 2033.08 | 21.79 | 118.83 | 355.50 | 979.72 | 22.51 | 80.83 | 319.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.57 | 0.48 | 01-JAN-10:39 | 583.95 | 15.21 | 0.00 | 258.67 | 337.79 | 17.35 | 0.00 | 173.83 |
February | 308.33 | 0.55 | 0.48 | 01-FEB-09:09 | 664.12 | 16.06 | 0.00 | 251.83 | 383.06 | 18.19 | 0.00 | 189.33 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:09 | 774.93 | 16.72 | 0.00 | 305.17 | 440.69 | 18.80 | 0.00 | 253.50 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 888.56 | 17.04 | 0.00 | 325.83 | 498.75 | 19.06 | 0.00 | 285.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1048.69 | 18.06 | 2.83 | 367.83 | 580.84 | 20.13 | 58.67 | 334.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1161.11 | 21.19 | 77.67 | 366.00 | 634.77 | 21.74 | 159.67 | 337.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:00 | 1122.40 | 19.02 | 27.00 | 357.67 | 614.73 | 21.15 | 131.83 | 327.17 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:10 | 1015.31 | 17.71 | 0.00 | 349.17 | 569.21 | 19.83 | 57.67 | 315.17 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 884.63 | 17.40 | 0.00 | 316.67 | 507.78 | 19.51 | 0.00 | 274.33 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 731.07 | 16.51 | 0.00 | 298.33 | 429.39 | 18.65 | 0.00 | 246.00 |
November | 318.83 | 0.55 | 0.48 | 01-NOV-08:20 | 632.93 | 16.13 | 0.00 | 260.50 | 373.18 | 18.35 | 0.00 | 194.83 |
December | 319.00 | 0.57 | 0.48 | 01-DEC-09:20 | 566.22 | 15.30 | 0.00 | 247.67 | 328.20 | 17.48 | 0.00 | 151.67 |
Annual Sum or Average | 4323.33 | 0.54 | 858.46 | 17.33 | 107.50 | 3705.33 | 484.58 | 19.30 | 407.83 | 3082.67 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 566.22 | 15.21 | 0.00 | 247.67 | 328.20 | 17.35 | 0.00 | 151.67 | |
Maximum of Months | 405.33 | 0.57 | 0.48 | 1161.11 | 21.19 | 77.67 | 367.83 | 634.77 | 21.74 | 159.67 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:20 | 1472.49 | 21.41 | 108.17 | 273.67 | 770.48 | 22.12 | 77.17 | 234.00 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:30 | 1441.48 | 19.80 | 76.33 | 260.33 | 731.40 | 20.69 | 48.33 | 222.67 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1643.78 | 19.44 | 85.83 | 307.67 | 844.33 | 21.41 | 65.67 | 270.50 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:39 | 1670.50 | 16.78 | 55.00 | 323.00 | 871.46 | 17.27 | 0.00 | 285.83 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-08:09 | 1755.31 | 14.44 | 0.00 | 348.83 | 908.83 | 17.58 | 0.00 | 312.50 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:00 | 1864.70 | 14.62 | 0.00 | 345.33 | 831.45 | 17.79 | 0.00 | 310.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:09 | 1785.81 | 14.65 | 3.67 | 347.00 | 813.31 | 17.57 | 0.00 | 308.17 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:09 | 1824.05 | 17.26 | 59.83 | 342.17 | 945.36 | 17.97 | 5.50 | 307.50 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1753.99 | 19.77 | 86.83 | 316.33 | 913.00 | 20.84 | 57.33 | 284.00 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1823.51 | 21.44 | 107.83 | 301.83 | 949.35 | 22.47 | 79.33 | 271.50 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1569.76 | 20.46 | 85.00 | 275.67 | 823.99 | 22.59 | 69.00 | 243.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1371.99 | 20.01 | 87.33 | 267.17 | 719.82 | 22.18 | 71.17 | 225.50 |
Annual Sum or Average | 4323.33 | 0.54 | 1677.91 | 18.12 | 755.83 | 3709.00 | 847.81 | 19.86 | 473.50 | 3275.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1371.99 | 14.44 | 0.00 | 260.33 | 719.82 | 17.27 | 0.00 | 222.67 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1864.70 | 21.44 | 108.17 | 348.83 | 949.35 | 22.59 | 79.33 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4086.59 | 33.82 | 310.17 | 292.17 | 1028.59 | 22.68 | 91.67 | 279.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2064.32 | 22.71 | 141.00 | 272.67 | 915.48 | 17.90 | 0.00 | 241.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:39 | 1512.04 | 14.51 | 5.00 | 311.67 | 782.61 | 17.73 | 0.00 | 274.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 1181.64 | 13.73 | 0.00 | 320.50 | 625.95 | 17.06 | 0.00 | 280.50 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1003.72 | 13.75 | 0.00 | 345.67 | 551.91 | 17.15 | 0.00 | 299.67 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 960.15 | 13.58 | 0.00 | 342.33 | 537.26 | 17.05 | 0.00 | 294.33 |
July | 405.00 | 0.55 | 0.48 | 01-JUL-07:30 | 1009.76 | 13.44 | 0.00 | 342.83 | 557.67 | 16.85 | 0.00 | 298.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1185.81 | 14.02 | 0.00 | 341.83 | 637.18 | 17.40 | 0.00 | 299.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1483.91 | 14.69 | 0.00 | 317.17 | 781.48 | 18.11 | 0.00 | 282.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1994.96 | 16.79 | 34.50 | 316.17 | 940.22 | 18.93 | 10.67 | 285.17 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3419.48 | 30.75 | 255.67 | 296.17 | 1064.51 | 22.45 | 76.67 | 280.50 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4073.66 | 34.24 | 306.00 | 287.50 | 1101.75 | 24.02 | 113.17 | 274.67 |
Annual Sum or Average | 4323.33 | 0.53 | 1906.79 | 19.03 | 1052.33 | 3786.67 | 775.12 | 18.77 | 292.17 | 3390.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 960.15 | 13.44 | 0.00 | 272.67 | 537.26 | 16.85 | 0.00 | 241.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 4086.59 | 34.24 | 310.17 | 345.67 | 1101.75 | 24.02 | 113.17 | 299.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-07:00 | 1477.44 | 21.34 | 111.83 | 271.17 | 770.93 | 22.29 | 80.83 | 230.17 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1598.28 | 20.91 | 102.33 | 259.50 | 677.76 | 20.56 | 47.17 | 222.17 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-07:00 | 1486.55 | 18.70 | 83.83 | 304.00 | 756.64 | 21.18 | 66.00 | 264.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:10 | 1745.70 | 19.95 | 109.33 | 316.33 | 885.84 | 21.22 | 79.83 | 278.00 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 1978.19 | 19.83 | 118.83 | 354.50 | 822.55 | 19.95 | 57.33 | 312.00 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-06:10 | 1906.78 | 19.55 | 114.33 | 347.33 | 818.23 | 20.81 | 66.33 | 312.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1794.64 | 19.48 | 114.17 | 345.50 | 778.78 | 19.69 | 52.50 | 306.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1837.56 | 20.08 | 113.83 | 338.67 | 812.55 | 20.23 | 56.17 | 303.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1838.98 | 20.74 | 105.17 | 309.00 | 939.81 | 22.18 | 77.33 | 280.50 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-06:00 | 1687.40 | 19.31 | 87.83 | 302.33 | 877.59 | 22.12 | 76.00 | 269.17 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1465.58 | 19.99 | 84.33 | 273.50 | 754.40 | 22.05 | 63.00 | 237.67 |
December | 319.00 | 0.55 | 0.48 | 01-DEC-07:19 | 1213.13 | 19.85 | 85.33 | 264.83 | 602.64 | 20.68 | 50.67 | 218.33 |
Annual Sum or Average | 4323.33 | 0.54 | 1686.47 | 19.95 | 1231.17 | 3686.67 | 795.92 | 21.03 | 773.17 | 3235.33 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1213.13 | 18.70 | 83.83 | 259.50 | 602.64 | 19.69 | 47.17 | 218.33 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1978.19 | 21.34 | 118.83 | 354.50 | 939.81 | 22.29 | 80.83 | 312.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.58 | 0.48 | 01-JAN-11:09 | 563.02 | 11.56 | 0.00 | 254.17 | 326.01 | 15.02 | 0.00 | 161.83 |
February | 308.33 | 0.56 | 0.48 | 01-FEB-09:20 | 640.55 | 12.32 | 0.00 | 250.17 | 369.77 | 15.82 | 0.00 | 183.00 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:20 | 747.66 | 13.05 | 0.00 | 303.00 | 425.11 | 16.48 | 0.00 | 246.17 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 856.88 | 13.49 | 0.00 | 324.00 | 480.37 | 16.84 | 0.00 | 281.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1010.38 | 14.42 | 2.83 | 366.50 | 558.12 | 17.86 | 1.17 | 328.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1117.74 | 18.33 | 77.33 | 363.17 | 608.57 | 19.55 | 34.17 | 333.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1080.87 | 15.56 | 26.83 | 356.33 | 589.86 | 18.88 | 27.33 | 324.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 977.84 | 14.13 | 0.00 | 347.50 | 547.30 | 17.57 | 0.00 | 310.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 852.42 | 13.96 | 0.00 | 315.33 | 489.39 | 17.37 | 0.00 | 270.83 |
October | 351.17 | 0.55 | 0.48 | 01-OCT-07:00 | 704.50 | 13.07 | 0.00 | 295.83 | 414.52 | 16.53 | 0.00 | 240.67 |
November | 318.83 | 0.56 | 0.48 | 01-NOV-08:30 | 609.74 | 12.53 | 0.00 | 257.17 | 360.27 | 16.11 | 0.00 | 185.67 |
December | 319.00 | 0.58 | 0.48 | 01-DEC-09:30 | 545.66 | 11.53 | 0.00 | 243.83 | 316.64 | 15.08 | 0.00 | 137.17 |
Annual Sum or Average | 4323.33 | 0.54 | 827.19 | 13.81 | 107.00 | 3677.00 | 466.41 | 17.04 | 62.67 | 3004.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 545.66 | 11.53 | 0.00 | 243.83 | 316.64 | 15.02 | 0.00 | 137.17 | |
Maximum of Months | 405.33 | 0.58 | 0.48 | 1117.74 | 18.33 | 77.33 | 366.50 | 608.57 | 19.55 | 34.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-10:20 | 1431.04 | 21.03 | 108.17 | 271.33 | 739.89 | 22.02 | 77.17 | 228.83 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:39 | 1395.63 | 19.38 | 76.33 | 258.83 | 697.96 | 20.57 | 48.33 | 218.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1596.77 | 19.01 | 85.83 | 306.83 | 806.38 | 21.29 | 65.83 | 266.83 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:50 | 1600.12 | 16.31 | 55.00 | 320.17 | 833.79 | 17.10 | 0.00 | 282.83 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-08:09 | 1699.56 | 13.89 | 0.00 | 347.83 | 870.84 | 17.38 | 0.00 | 309.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-08:09 | 1816.32 | 14.07 | 0.00 | 344.17 | 792.02 | 17.58 | 0.00 | 306.83 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:20 | 1734.07 | 14.10 | 3.67 | 345.33 | 775.79 | 17.36 | 0.00 | 304.83 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:20 | 1762.23 | 16.77 | 59.83 | 340.17 | 905.81 | 17.79 | 5.50 | 304.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1703.72 | 19.34 | 86.83 | 314.50 | 872.46 | 20.70 | 57.33 | 281.17 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-08:20 | 1772.59 | 21.04 | 107.83 | 300.00 | 911.28 | 22.36 | 79.33 | 269.00 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1522.63 | 20.02 | 85.00 | 273.17 | 788.90 | 22.49 | 69.00 | 240.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1330.39 | 19.58 | 87.33 | 265.00 | 689.13 | 22.07 | 71.33 | 222.67 |
Annual Sum or Average | 4323.33 | 0.54 | 1626.43 | 17.66 | 755.83 | 3687.33 | 811.03 | 19.71 | 473.83 | 3235.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1330.39 | 13.89 | 0.00 | 258.83 | 689.13 | 17.10 | 0.00 | 218.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1816.32 | 21.04 | 108.17 | 347.83 | 911.28 | 22.49 | 79.33 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4086.49 | 33.82 | 310.17 | 292.17 | 1028.50 | 22.68 | 91.67 | 279.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2064.21 | 22.71 | 141.00 | 272.67 | 915.40 | 17.90 | 0.00 | 241.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:39 | 1511.93 | 14.51 | 5.00 | 311.50 | 782.54 | 17.73 | 0.00 | 274.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 1181.56 | 13.73 | 0.00 | 320.50 | 625.90 | 17.06 | 0.00 | 280.50 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1003.67 | 13.75 | 0.00 | 345.67 | 551.86 | 17.15 | 0.00 | 299.67 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 960.10 | 13.58 | 0.00 | 342.33 | 537.22 | 17.05 | 0.00 | 294.33 |
July | 405.00 | 0.55 | 0.48 | 01-JUL-07:30 | 1009.71 | 13.44 | 0.00 | 342.83 | 557.63 | 16.85 | 0.00 | 298.00 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1185.73 | 14.02 | 0.00 | 341.83 | 637.13 | 17.40 | 0.00 | 299.83 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1483.81 | 14.69 | 0.00 | 317.17 | 781.41 | 18.11 | 0.00 | 282.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1994.84 | 16.79 | 34.50 | 316.17 | 940.13 | 18.94 | 10.67 | 285.17 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3419.37 | 30.75 | 255.67 | 296.17 | 1064.41 | 22.45 | 76.67 | 280.50 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4073.58 | 34.24 | 306.00 | 287.50 | 1101.66 | 24.02 | 113.33 | 274.67 |
Annual Sum or Average | 4323.33 | 0.53 | 1906.71 | 19.03 | 1052.33 | 3786.50 | 775.05 | 18.77 | 292.33 | 3390.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 960.10 | 13.44 | 0.00 | 272.67 | 537.22 | 16.85 | 0.00 | 241.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 4086.49 | 34.24 | 310.17 | 345.67 | 1101.66 | 24.02 | 113.33 | 299.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-07:00 | 1477.39 | 21.34 | 111.83 | 271.17 | 770.88 | 22.29 | 80.83 | 230.17 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-07:49 | 1598.23 | 20.92 | 102.33 | 259.50 | 677.71 | 20.56 | 47.17 | 222.17 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-07:00 | 1486.48 | 18.70 | 83.83 | 304.00 | 756.59 | 21.18 | 66.00 | 264.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:10 | 1745.63 | 19.95 | 109.33 | 316.33 | 885.79 | 21.22 | 79.83 | 278.00 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-06:30 | 1978.13 | 19.83 | 118.83 | 354.50 | 822.49 | 19.95 | 57.33 | 312.00 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-06:10 | 1906.71 | 19.55 | 114.33 | 347.33 | 818.17 | 20.81 | 66.33 | 312.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-06:40 | 1794.57 | 19.49 | 114.17 | 345.50 | 778.72 | 19.69 | 52.50 | 306.67 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-06:40 | 1837.49 | 20.08 | 113.83 | 338.67 | 812.49 | 20.23 | 56.17 | 303.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1838.91 | 20.74 | 105.17 | 309.00 | 939.74 | 22.18 | 77.33 | 280.50 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-06:00 | 1687.34 | 19.31 | 87.83 | 302.33 | 877.53 | 22.12 | 76.00 | 269.17 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1465.54 | 20.00 | 84.33 | 273.50 | 754.35 | 22.05 | 63.00 | 237.67 |
December | 319.00 | 0.55 | 0.48 | 01-DEC-07:19 | 1213.09 | 19.85 | 85.33 | 264.83 | 602.60 | 20.68 | 50.67 | 218.33 |
Annual Sum or Average | 4323.33 | 0.54 | 1686.41 | 19.95 | 1231.17 | 3686.67 | 795.86 | 21.03 | 773.17 | 3235.33 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1213.09 | 18.70 | 83.83 | 259.50 | 602.60 | 19.69 | 47.17 | 218.33 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1978.13 | 21.34 | 118.83 | 354.50 | 939.74 | 22.29 | 80.83 | 312.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.58 | 0.48 | 01-JAN-11:09 | 563.00 | 11.56 | 0.00 | 254.17 | 325.99 | 15.02 | 0.00 | 161.83 |
February | 308.33 | 0.56 | 0.48 | 01-FEB-09:20 | 640.53 | 12.32 | 0.00 | 250.17 | 369.74 | 15.82 | 0.00 | 183.00 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:20 | 747.62 | 13.05 | 0.00 | 303.00 | 425.08 | 16.48 | 0.00 | 246.17 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:00 | 856.84 | 13.49 | 0.00 | 324.00 | 480.33 | 16.84 | 0.00 | 281.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1010.32 | 14.42 | 2.83 | 366.50 | 558.07 | 17.86 | 1.17 | 328.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:40 | 1117.68 | 18.33 | 77.33 | 363.17 | 608.53 | 19.55 | 34.17 | 333.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1080.81 | 15.56 | 26.83 | 356.33 | 589.82 | 18.88 | 27.33 | 324.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 977.79 | 14.13 | 0.00 | 347.50 | 547.26 | 17.57 | 0.00 | 310.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 852.38 | 13.96 | 0.00 | 315.33 | 489.35 | 17.37 | 0.00 | 270.83 |
October | 351.17 | 0.55 | 0.48 | 01-OCT-07:00 | 704.48 | 13.07 | 0.00 | 295.83 | 414.49 | 16.54 | 0.00 | 240.67 |
November | 318.83 | 0.56 | 0.48 | 01-NOV-08:30 | 609.72 | 12.54 | 0.00 | 257.17 | 360.24 | 16.12 | 0.00 | 185.67 |
December | 319.00 | 0.58 | 0.48 | 01-DEC-09:30 | 545.64 | 11.53 | 0.00 | 243.83 | 316.62 | 15.08 | 0.00 | 137.17 |
Annual Sum or Average | 4323.33 | 0.54 | 827.15 | 13.81 | 107.00 | 3677.00 | 466.38 | 17.04 | 62.67 | 3004.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 545.64 | 11.53 | 0.00 | 243.83 | 316.62 | 15.02 | 0.00 | 137.17 | |
Maximum of Months | 405.33 | 0.58 | 0.48 | 1117.68 | 18.33 | 77.33 | 366.50 | 608.53 | 19.55 | 34.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-10:20 | 1431.00 | 21.03 | 108.17 | 271.33 | 739.84 | 22.02 | 77.17 | 228.83 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:39 | 1395.57 | 19.38 | 76.33 | 258.83 | 697.91 | 20.57 | 48.33 | 218.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1596.71 | 19.01 | 85.83 | 306.83 | 806.32 | 21.29 | 65.83 | 266.83 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:50 | 1600.05 | 16.31 | 55.00 | 320.17 | 833.73 | 17.10 | 0.00 | 282.83 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-08:09 | 1699.49 | 13.89 | 0.00 | 347.83 | 870.78 | 17.38 | 0.00 | 309.33 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-08:09 | 1816.25 | 14.07 | 0.00 | 344.17 | 791.96 | 17.58 | 0.00 | 306.83 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:20 | 1733.99 | 14.10 | 3.67 | 345.33 | 775.73 | 17.36 | 0.00 | 304.83 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-08:20 | 1762.15 | 16.77 | 59.83 | 340.17 | 905.74 | 17.79 | 5.50 | 304.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-08:20 | 1703.65 | 19.34 | 86.83 | 314.50 | 872.40 | 20.70 | 57.33 | 281.17 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-08:20 | 1772.54 | 21.04 | 107.83 | 300.00 | 911.22 | 22.36 | 79.33 | 269.00 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1522.58 | 20.03 | 85.00 | 273.17 | 788.85 | 22.49 | 69.00 | 240.00 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:20 | 1330.35 | 19.58 | 87.33 | 265.00 | 689.08 | 22.07 | 71.33 | 222.67 |
Annual Sum or Average | 4323.33 | 0.54 | 1626.37 | 17.66 | 755.83 | 3687.33 | 810.97 | 19.71 | 473.83 | 3235.83 | ||
Minimum of Months | 308.33 | 0.53 | 0.48 | 1330.35 | 13.89 | 0.00 | 258.83 | 689.08 | 17.10 | 0.00 | 218.83 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1816.25 | 21.04 | 108.17 | 347.83 | 911.22 | 22.49 | 79.33 | 309.33 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218833E+09 | 5912.83 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132695E+09 | 5912.83 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49468461.74 | 5912.83 | 16-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1014905.61 | 1410.25 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45861291.42 | 4989.60 | 19-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218833E+09 | 5912.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25479.73 | 169.86 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25479.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25479.73 | 169.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 577296.63 | 1584.19 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 577296.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 577296.63 | 1584.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 397610.28 | 770.44 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 397610.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 397610.28 | 770.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5689911.12 | 2379.02 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14758.76 | 122.99 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 373547.94 | 122.17 | 30-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6078217.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5689911.12 | 2379.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.425912E+11 | 0.367553E+11 | 57077.20 | 30-JAN-12:00 | 45286.33 | 0.00 |
February | 0.00 | 0.00 | 0.449665E+11 | 0.381989E+11 | 75043.55 | 07-FEB-15:50 | 57001.35 | 0.00 |
March | 0.00 | 0.00 | 0.595050E+11 | 0.523140E+11 | 81136.70 | 28-MAR-11:40 | 55339.02 | 0.00 |
April | 0.00 | 0.00 | 0.707196E+11 | 0.607235E+11 | 87856.90 | 10-APR-12:00 | 56287.02 | 0.00 |
May | 0.00 | 0.00 | 0.105828E+12 | 0.879643E+11 | 142184.47 | 31-MAY-04:02 | 91673.69 | 0.00 |
June | 0.00 | 0.00 | 0.127538E+12 | 0.947017E+11 | 145017.10 | 20-JUN-04:02 | 85953.35 | 0.00 |
July | 0.00 | 0.00 | 0.153617E+12 | 0.104648E+12 | 144667.71 | 06-JUL-04:02 | 86555.94 | 0.00 |
August | 0.00 | 0.00 | 0.170799E+12 | 0.114011E+12 | 144361.12 | 26-AUG-04:02 | 86014.91 | 0.00 |
September | 0.00 | 0.00 | 0.137333E+12 | 0.944766E+11 | 146437.84 | 10-SEP-17:02 | 75388.78 | 0.00 |
October | 0.00 | 0.00 | 0.111535E+12 | 0.846106E+11 | 143490.63 | 18-OCT-04:02 | 87429.28 | 0.00 |
November | 0.00 | 0.00 | 0.808197E+11 | 0.655324E+11 | 123764.45 | 03-NOV-04:02 | 77362.71 | 0.00 |
December | 0.00 | 0.00 | 0.532874E+11 | 0.444929E+11 | 78835.38 | 04-DEC-12:10 | 53507.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115854E+13 | 0.878429E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.425912E+11 | 0.367553E+11 | 57077.20 | 45286.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.170799E+12 | 0.114011E+12 | 146437.84 | 91673.69 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323435E+11 | 0.261315E+11 | 43882.59 | 30-JAN-14:00 | 32485.04 | 0.00 |
February | 0.00 | 0.00 | 0.360283E+11 | 0.292191E+11 | 64219.70 | 07-FEB-15:50 | 47574.96 | 0.00 |
March | 0.00 | 0.00 | 0.498605E+11 | 0.426977E+11 | 67108.62 | 27-MAR-14:50 | 67108.62 | 0.00 |
April | 0.00 | 0.00 | 0.615896E+11 | 0.521890E+11 | 93207.95 | 30-APR-16:33 | 55983.97 | 0.00 |
May | 0.00 | 0.00 | 0.928818E+11 | 0.774157E+11 | 134392.17 | 30-MAY-04:02 | 84293.35 | 0.00 |
June | 0.00 | 0.00 | 0.112509E+12 | 0.829839E+11 | 136881.03 | 20-JUN-04:02 | 77136.06 | 0.00 |
July | 0.00 | 0.00 | 0.134529E+12 | 0.919918E+11 | 136836.51 | 06-JUL-04:02 | 77607.04 | 0.00 |
August | 0.00 | 0.00 | 0.144985E+12 | 0.979712E+11 | 137729.56 | 08-AUG-04:02 | 76241.52 | 0.00 |
September | 0.00 | 0.00 | 0.114510E+12 | 0.789160E+11 | 136808.99 | 10-SEP-16:52 | 71225.34 | 0.00 |
October | 0.00 | 0.00 | 0.897706E+11 | 0.682960E+11 | 135311.62 | 02-OCT-04:02 | 82114.31 | 0.00 |
November | 0.00 | 0.00 | 0.627093E+11 | 0.498168E+11 | 92628.01 | 03-NOV-05:03 | 54015.64 | 0.00 |
December | 0.00 | 0.00 | 0.408388E+11 | 0.320767E+11 | 61275.41 | 05-DEC-15:10 | 42595.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.972556E+12 | 0.729705E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.323435E+11 | 0.261315E+11 | 43882.59 | 32485.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144985E+12 | 0.979712E+11 | 137729.56 | 84293.35 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321071E+11 | 0.249572E+11 | 44966.27 | 30-JAN-14:30 | 32025.59 | 0.00 |
February | 0.00 | 0.00 | 0.368627E+11 | 0.292105E+11 | 69162.78 | 07-FEB-15:30 | 53442.91 | 0.00 |
March | 0.00 | 0.00 | 0.521127E+11 | 0.440024E+11 | 74997.88 | 27-MAR-13:40 | 74997.88 | 0.00 |
April | 0.00 | 0.00 | 0.657217E+11 | 0.553918E+11 | 114741.25 | 30-APR-14:13 | 89217.33 | 0.00 |
May | 0.00 | 0.00 | 0.100617E+12 | 0.843596E+11 | 151773.77 | 30-MAY-04:02 | 95318.98 | 0.00 |
June | 0.00 | 0.00 | 0.121516E+12 | 0.911172E+11 | 155648.55 | 20-JUN-04:02 | 83940.16 | 0.00 |
July | 0.00 | 0.00 | 0.146964E+12 | 0.102589E+12 | 155359.36 | 06-JUL-04:02 | 89941.89 | 0.00 |
August | 0.00 | 0.00 | 0.157317E+12 | 0.108663E+12 | 154666.00 | 26-AUG-04:02 | 90634.33 | 0.00 |
September | 0.00 | 0.00 | 0.121729E+12 | 0.853819E+11 | 155277.64 | 28-SEP-04:02 | 83293.28 | 0.00 |
October | 0.00 | 0.00 | 0.933131E+11 | 0.713223E+11 | 152828.21 | 02-OCT-04:02 | 93157.44 | 0.00 |
November | 0.00 | 0.00 | 0.638194E+11 | 0.501189E+11 | 99622.17 | 03-NOV-05:03 | 58711.74 | 0.00 |
December | 0.00 | 0.00 | 0.409716E+11 | 0.312028E+11 | 64392.30 | 05-DEC-15:00 | 45370.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103305E+13 | 0.778317E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.321071E+11 | 0.249572E+11 | 44966.27 | 32025.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.157317E+12 | 0.108663E+12 | 155648.55 | 95318.98 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1228.96 | 4483.27 | 12-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1202.89 | 4436.51 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1197.58 | 4225.50 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1003.36 | 3823.28 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 931.13 | 3441.37 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 872.20 | 3086.30 | 01-JUN-11:16 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 771.00 | 2915.96 | 31-JUL-11:14 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 890.92 | 3142.36 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 914.37 | 3491.81 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1023.76 | 3927.52 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1148.72 | 4272.17 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1172.94 | 4459.60 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1028.89 | ||||
Minimum of Months | 0.00 | 0.00 | 771.00 | 2915.96 | ||
Maximum of Months | 0.00 | 0.00 | 1228.96 | 4483.27 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.308542E+10 | 0.36 | 5049.11 | 17-JAN-15:10 | 1.04 |
February | 0.310089E+10 | 0.37 | 7073.06 | 06-FEB-15:50 | 1.29 |
March | 0.409343E+10 | 0.42 | 8053.92 | 27-MAR-10:10 | 1.40 |
April | 0.461546E+10 | 0.46 | 9119.83 | 24-APR-12:20 | 1.51 |
May | 0.690718E+10 | 0.59 | 11717.60 | 12-MAY-04:02 | 1.77 |
June | 0.745287E+10 | 0.63 | 11717.60 | 01-JUN-04:02 | 1.77 |
July | 0.737746E+10 | 0.64 | 11717.60 | 05-JUL-04:02 | 1.77 |
August | 0.777099E+10 | 0.68 | 11717.60 | 01-AUG-04:03 | 1.77 |
September | 0.659991E+10 | 0.60 | 11717.60 | 01-SEP-04:02 | 1.77 |
October | 0.611052E+10 | 0.55 | 11717.60 | 02-OCT-06:03 | 1.77 |
November | 0.523535E+10 | 0.49 | 9715.25 | 20-NOV-07:03 | 1.57 |
December | 0.370675E+10 | 0.39 | 6816.30 | 04-DEC-15:20 | 1.25 |
Annual Sum or Average | 0.660562E+11 | 0.52 | |||
Minimum of Months | 0.308542E+10 | 0.36 | 5049.11 | 1.04 | |
Maximum of Months | 0.777099E+10 | 0.68 | 11717.60 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204373E+10 | 0.32 | 3196.93 | 23-JAN-13:30 | 0.85 |
February | 0.223036E+10 | 0.34 | 5489.47 | 06-FEB-15:10 | 1.17 |
March | 0.321875E+10 | 0.39 | 7611.49 | 27-MAR-14:50 | 1.43 |
April | 0.379850E+10 | 0.44 | 7401.99 | 24-APR-14:10 | 1.41 |
May | 0.592814E+10 | 0.56 | 10757.77 | 08-MAY-04:02 | 1.78 |
June | 0.644836E+10 | 0.61 | 10757.77 | 01-JUN-04:02 | 1.78 |
July | 0.677910E+10 | 0.63 | 10757.77 | 01-JUL-04:02 | 1.78 |
August | 0.757119E+10 | 0.68 | 10757.77 | 01-AUG-06:03 | 1.78 |
September | 0.609727E+10 | 0.58 | 10757.77 | 01-SEP-04:02 | 1.78 |
October | 0.519176E+10 | 0.51 | 10757.77 | 02-OCT-04:02 | 1.78 |
November | 0.378782E+10 | 0.43 | 6971.49 | 06-NOV-15:10 | 1.35 |
December | 0.239512E+10 | 0.33 | 4640.94 | 04-DEC-13:40 | 1.05 |
Annual Sum or Average | 0.554901E+11 | 0.49 | |||
Minimum of Months | 0.204373E+10 | 0.32 | 3196.93 | 0.85 | |
Maximum of Months | 0.757119E+10 | 0.68 | 10757.77 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178155E+10 | 0.29 | 2638.34 | 23-JAN-14:00 | 0.70 |
February | 0.196771E+10 | 0.31 | 4935.35 | 06-FEB-15:00 | 0.99 |
March | 0.289572E+10 | 0.35 | 7083.41 | 27-MAR-14:30 | 1.23 |
April | 0.350626E+10 | 0.39 | 7110.97 | 24-APR-14:00 | 1.23 |
May | 0.563154E+10 | 0.51 | 12462.11 | 12-MAY-04:02 | 1.75 |
June | 0.619512E+10 | 0.55 | 12632.82 | 27-JUN-04:02 | 1.76 |
July | 0.665158E+10 | 0.59 | 12632.82 | 06-JUL-04:02 | 1.76 |
August | 0.736842E+10 | 0.62 | 12632.82 | 04-AUG-04:02 | 1.77 |
September | 0.577175E+10 | 0.53 | 12632.82 | 01-SEP-04:02 | 1.77 |
October | 0.474783E+10 | 0.45 | 12632.82 | 02-OCT-04:02 | 1.77 |
November | 0.324852E+10 | 0.37 | 6325.28 | 06-NOV-14:20 | 1.14 |
December | 0.205563E+10 | 0.30 | 3819.29 | 04-DEC-14:10 | 0.85 |
Annual Sum or Average | 0.518216E+11 | 0.44 | |||
Minimum of Months | 0.178155E+10 | 0.29 | 2638.34 | 0.70 | |
Maximum of Months | 0.736842E+10 | 0.62 | 12632.82 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.66 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.88 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.93 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 58.11 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.46 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:05 | 2.06 | 2.06 | 58.47 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.63 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.58 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:10 | 2.06 | 2.06 | 58.37 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.86 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 58.12 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.95 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.88 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.86 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.66 | 58.66 | 1228.96 | 4483.27 | 12-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.32 | 58.32 | 1202.89 | 4436.51 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.39 | 58.39 | 1197.58 | 4225.50 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.54 | 58.54 | 1003.36 | 3823.28 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.97 | 58.97 | 931.13 | 3441.37 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.85 | 58.85 | 872.20 | 3086.30 | 01-JUN-11:16 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.92 | 58.92 | 771.00 | 2915.96 | 31-JUL-11:14 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.90 | 58.90 | 890.92 | 3142.36 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.82 | 58.82 | 914.37 | 3491.81 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.13 | 58.13 | 1023.76 | 3927.52 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.52 | 58.52 | 1148.72 | 4272.17 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.38 | 58.38 | 1172.94 | 4459.60 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1028.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 771.00 | 2915.96 | ||
Maximum of Months | 0.00 | 0.00 | 58.97 | 58.97 | 1228.96 | 4483.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.129596E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134580E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180902E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.220156E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.351377E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.417331E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.494040E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.546286E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.424641E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.339116E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.242281E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157264E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.363757E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129596E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.546286E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.957017E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.105902E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150611E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.190254E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.306011E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.364315E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.433101E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.471093E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.358075E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.275375E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.186307E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.117862E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.305461E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.957017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.471093E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.936505E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106310E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154097E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.199113E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.325111E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.387144E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.466451E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.503543E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.374713E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.281530E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.185158E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116217E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.319304E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.936505E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.503543E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.308542E+10 | 0.425912E+11 | 0.218833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310089E+10 | 0.449665E+11 | 0.132695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409343E+10 | 0.595050E+11 | 49468461.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461546E+10 | 0.707196E+11 | 1014905.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690718E+10 | 0.105828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745287E+10 | 0.127538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737746E+10 | 0.153617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777099E+10 | 0.170799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659991E+10 | 0.137333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611052E+10 | 0.111535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523535E+10 | 0.808197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370675E+10 | 0.532874E+11 | 45861291.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660562E+11 | 0.115854E+13 | 0.447873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308542E+10 | 0.425912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777099E+10 | 0.170799E+12 | 0.218833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204373E+10 | 0.323435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223036E+10 | 0.360283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321875E+10 | 0.498605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379850E+10 | 0.615896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592814E+10 | 0.928818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644836E+10 | 0.112509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677910E+10 | 0.134529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.757119E+10 | 0.144985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.609727E+10 | 0.114510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519176E+10 | 0.897706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378782E+10 | 0.627093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239512E+10 | 0.408388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554901E+11 | 0.972556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.204373E+10 | 0.323435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.757119E+10 | 0.144985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178155E+10 | 0.321071E+11 | 6690297.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196771E+10 | 0.368627E+11 | 14758.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289572E+10 | 0.521127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350626E+10 | 0.657217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.563154E+10 | 0.100617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619512E+10 | 0.121516E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665158E+10 | 0.146964E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.736842E+10 | 0.157317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577175E+10 | 0.121729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474783E+10 | 0.933131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324852E+10 | 0.638194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205563E+10 | 0.409716E+11 | 373547.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518216E+11 | 0.103305E+13 | 7078604.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178155E+10 | 0.321071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.736842E+10 | 0.157317E+12 | 6690297.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.308542E+10 | 0.00 | 0.00 | 0.00 | 0.965534E+10 | 0.218833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310089E+10 | 0.00 | 0.00 | 0.00 | 0.102244E+11 | 0.132695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409343E+10 | 0.00 | 0.00 | 0.00 | 0.139473E+11 | 49468461.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.461546E+10 | 0.00 | 0.00 | 0.00 | 0.173992E+11 | 1014905.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.690718E+10 | 0.00 | 0.00 | 0.00 | 0.282305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.745287E+10 | 0.00 | 0.00 | 0.00 | 0.342802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737746E+10 | 0.00 | 0.00 | 0.00 | 0.420265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.777099E+10 | 0.00 | 0.00 | 0.00 | 0.468576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.659991E+10 | 0.00 | 0.00 | 0.00 | 0.358642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.611052E+10 | 0.00 | 0.00 | 0.00 | 0.278010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.523535E+10 | 0.00 | 0.00 | 0.00 | 0.189927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370675E+10 | 0.00 | 0.00 | 0.00 | 0.119738E+11 | 45861291.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660562E+11 | 0.00 | 0.00 | 0.00 | 0.297253E+12 | 0.447873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308542E+10 | 0.00 | 0.00 | 0.00 | 0.965534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.777099E+10 | 0.00 | 0.00 | 0.00 | 0.468576E+11 | 0.218833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204373E+10 | 0.00 | 0.00 | 0.00 | 0.752645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223036E+10 | 0.00 | 0.00 | 0.00 | 0.835985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321875E+10 | 0.00 | 0.00 | 0.00 | 0.118423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379850E+10 | 0.00 | 0.00 | 0.00 | 0.152269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592814E+10 | 0.00 | 0.00 | 0.00 | 0.246729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644836E+10 | 0.00 | 0.00 | 0.00 | 0.299831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677910E+10 | 0.00 | 0.00 | 0.00 | 0.365310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.757119E+10 | 0.00 | 0.00 | 0.00 | 0.395381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.609727E+10 | 0.00 | 0.00 | 0.00 | 0.297102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519176E+10 | 0.00 | 0.00 | 0.00 | 0.223457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378782E+10 | 0.00 | 0.00 | 0.00 | 0.148429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239512E+10 | 0.00 | 0.00 | 0.00 | 0.939111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554901E+11 | 0.00 | 0.00 | 0.00 | 0.249971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.204373E+10 | 0.00 | 0.00 | 0.00 | 0.752645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.757119E+10 | 0.00 | 0.00 | 0.00 | 0.395381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178155E+10 | 0.00 | 0.00 | 0.00 | 0.757681E+10 | 6690297.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196771E+10 | 0.00 | 0.00 | 0.00 | 0.866328E+10 | 14758.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289572E+10 | 0.00 | 0.00 | 0.00 | 0.125140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.350626E+10 | 0.00 | 0.00 | 0.00 | 0.164050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.563154E+10 | 0.00 | 0.00 | 0.00 | 0.268795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619512E+10 | 0.00 | 0.00 | 0.00 | 0.325193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665158E+10 | 0.00 | 0.00 | 0.00 | 0.399935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.736842E+10 | 0.00 | 0.00 | 0.00 | 0.429859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577175E+10 | 0.00 | 0.00 | 0.00 | 0.316996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474783E+10 | 0.00 | 0.00 | 0.00 | 0.234051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324852E+10 | 0.00 | 0.00 | 0.00 | 0.152673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205563E+10 | 0.00 | 0.00 | 0.00 | 0.956573E+10 | 373547.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.518216E+11 | 0.00 | 0.00 | 0.00 | 0.267475E+12 | 7078604.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178155E+10 | 0.00 | 0.00 | 0.00 | 0.757681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.736842E+10 | 0.00 | 0.00 | 0.00 | 0.429859E+11 | 6690297.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193069E+09 | 0.339169E+09 | 0.00 | 35729425.26 | 0.155146E+09 | 0.00 | 0.347031E+10 | 0.00 | 0.40 |
February | 92174928.91 | 0.110218E+10 | 0.00 | 25054615.29 | 0.157966E+09 | 0.00 | 0.181029E+10 | 0.00 | 0.38 |
March | 94583074.87 | 0.211099E+10 | 0.00 | 23076128.75 | 0.188049E+09 | 0.00 | 0.144699E+10 | 0.00 | 0.39 |
April | 49978925.59 | 0.446907E+10 | 0.00 | 8116417.44 | 0.101234E+10 | 0.00 | 0.453267E+09 | 0.00 | 0.36 |
May | 15862069.04 | 0.904595E+10 | 0.00 | 2133893.97 | 0.269635E+10 | 0.00 | 69621427.40 | 0.00 | 0.35 |
June | 1898707.82 | 0.144803E+11 | 0.00 | 404966.23 | 0.427420E+10 | 0.00 | 8602333.87 | 0.00 | 0.36 |
July | 1941436.72 | 0.183682E+11 | 0.00 | 21250.93 | 0.901886E+10 | 0.00 | 200913.40 | 0.00 | 0.38 |
August | 0.00 | 0.208713E+11 | 0.00 | 0.00 | 0.911994E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 17790.96 | 0.159905E+11 | 0.00 | 23557.40 | 0.620022E+10 | 0.00 | 25263.29 | 0.00 | 0.36 |
October | 25237026.27 | 0.100861E+11 | 0.00 | 1511852.90 | 0.370277E+10 | 0.00 | 67143350.85 | 0.00 | 0.35 |
November | 14472391.25 | 0.531994E+10 | 0.00 | 4360778.59 | 0.853193E+09 | 0.00 | 0.118112E+09 | 0.00 | 0.34 |
December | 83889674.20 | 0.155119E+10 | 0.00 | 26509042.39 | 0.385265E+09 | 0.00 | 0.161397E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.573125E+09 | 0.103735E+12 | 0.00 | 0.126942E+09 | 0.377643E+11 | 0.00 | 0.905853E+10 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.339169E+09 | 0.00 | 0.00 | 0.155146E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.193069E+09 | 0.208713E+11 | 0.00 | 35729425.26 | 0.911994E+10 | 0.00 | 0.347031E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.678210E+09 | 0.341459E+09 | 0.00 | 14532574.24 | 0.233077E+09 | 0.00 | 0.176642E+10 | 0.00 | 0.31 |
February | 0.324120E+09 | 0.936902E+09 | 0.00 | 11129623.74 | 0.258264E+09 | 0.00 | 0.937286E+09 | 0.00 | 0.30 |
March | 0.257474E+09 | 0.185580E+10 | 0.00 | 11630566.54 | 0.230871E+09 | 0.00 | 0.809578E+09 | 0.00 | 0.32 |
April | 0.127464E+09 | 0.379248E+10 | 0.00 | 4381539.42 | 0.110403E+10 | 0.00 | 0.269443E+09 | 0.00 | 0.31 |
May | 37637783.40 | 0.788843E+10 | 0.00 | 1299962.92 | 0.265889E+10 | 0.00 | 56051683.39 | 0.00 | 0.33 |
June | 4159278.34 | 0.130010E+11 | 0.00 | 251335.06 | 0.434481E+10 | 0.00 | 8906202.00 | 0.00 | 0.34 |
July | 3687581.61 | 0.169300E+11 | 0.00 | 776.00 | 0.828012E+10 | 0.00 | 570055.97 | 0.00 | 0.36 |
August | 0.00 | 0.196092E+11 | 0.00 | 0.00 | 0.747556E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 223685.22 | 0.147438E+11 | 0.00 | 112418.84 | 0.482459E+10 | 0.00 | 1897774.04 | 0.00 | 0.33 |
October | 33747528.62 | 0.903314E+10 | 0.00 | 1075471.92 | 0.283192E+10 | 0.00 | 44176849.45 | 0.00 | 0.31 |
November | 24472327.11 | 0.492611E+10 | 0.00 | 2396293.41 | 0.698591E+09 | 0.00 | 68657835.58 | 0.00 | 0.30 |
December | 0.292771E+09 | 0.147332E+10 | 0.00 | 11417423.66 | 0.424316E+09 | 0.00 | 0.781553E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.178397E+10 | 0.945316E+11 | 0.00 | 58227985.75 | 0.333650E+11 | 0.00 | 0.474454E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.341459E+09 | 0.00 | 0.00 | 0.230871E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.678210E+09 | 0.196092E+11 | 0.00 | 14532574.24 | 0.828012E+10 | 0.00 | 0.176642E+10 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.820908E+09 | 0.349809E+09 | 0.00 | 9407365.47 | 0.351560E+09 | 0.00 | 0.985991E+09 | 0.00 | 0.29 |
February | 0.381745E+09 | 0.936589E+09 | 0.00 | 7816630.55 | 0.411100E+09 | 0.00 | 0.546505E+09 | 0.00 | 0.29 |
March | 0.302613E+09 | 0.190276E+10 | 0.00 | 7422935.78 | 0.309952E+09 | 0.00 | 0.461284E+09 | 0.00 | 0.31 |
April | 0.125833E+09 | 0.382685E+10 | 0.00 | 2491753.62 | 0.110582E+10 | 0.00 | 0.125406E+09 | 0.00 | 0.31 |
May | 36579156.59 | 0.775286E+10 | 0.00 | 980188.50 | 0.267740E+10 | 0.00 | 26329427.41 | 0.00 | 0.33 |
June | 6835326.24 | 0.127270E+11 | 0.00 | 288789.10 | 0.446404E+10 | 0.00 | 4906182.75 | 0.00 | 0.34 |
July | 1888208.66 | 0.167441E+11 | 0.00 | 0.00 | 0.877937E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.193099E+11 | 0.00 | 0.00 | 0.801865E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 302946.84 | 0.143355E+11 | 0.00 | 51317.63 | 0.512132E+10 | 0.00 | 665920.76 | 0.00 | 0.33 |
October | 40661010.77 | 0.880882E+10 | 0.00 | 910225.35 | 0.287448E+10 | 0.00 | 19001531.29 | 0.00 | 0.31 |
November | 12017351.94 | 0.504989E+10 | 0.00 | 1555649.53 | 0.741558E+09 | 0.00 | 39759215.41 | 0.00 | 0.30 |
December | 0.317098E+09 | 0.138943E+10 | 0.00 | 6715684.78 | 0.727864E+09 | 0.00 | 0.370632E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.204648E+10 | 0.931335E+11 | 0.00 | 37640540.32 | 0.355831E+11 | 0.00 | 0.258048E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.349809E+09 | 0.00 | 0.00 | 0.309952E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.820908E+09 | 0.193099E+11 | 0.00 | 9407365.47 | 0.877937E+10 | 0.00 | 0.985991E+09 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245776E+09 | 68993729.30 | 0.00 | 1546702.37 | 87402998.68 | 0.00 | 0.147512E+09 | 0.00 | 0.30 |
February | 0.104087E+09 | 0.195518E+09 | 0.00 | 1669292.82 | 0.121085E+09 | 0.00 | 0.106431E+09 | 0.00 | 0.32 |
March | 77893732.65 | 0.505230E+09 | 0.00 | 1670918.15 | 79974920.77 | 0.00 | 0.100301E+09 | 0.00 | 0.37 |
April | 35704327.34 | 0.122475E+10 | 0.00 | 585916.53 | 0.227557E+09 | 0.00 | 22026164.95 | 0.00 | 0.41 |
May | 6255461.86 | 0.314475E+10 | 0.00 | 276994.05 | 0.359444E+09 | 0.00 | 8767567.86 | 0.00 | 0.51 |
June | 956689.57 | 0.551813E+10 | 0.00 | 96746.06 | 0.525295E+09 | 0.00 | 1881637.29 | 0.00 | 0.56 |
July | 365511.92 | 0.769510E+10 | 0.00 | 10084.34 | 0.113308E+10 | 0.00 | 65202.39 | 0.00 | 0.60 |
August | 0.00 | 0.840466E+10 | 0.00 | 0.00 | 0.109343E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 97916.81 | 0.564511E+10 | 0.00 | 10801.92 | 0.707962E+09 | 0.00 | 120087.31 | 0.00 | 0.50 |
October | 9994227.13 | 0.285319E+10 | 0.00 | 250074.50 | 0.530381E+09 | 0.00 | 4241000.69 | 0.00 | 0.43 |
November | 2878424.64 | 0.130931E+10 | 0.00 | 409942.93 | 0.197790E+09 | 0.00 | 10360448.78 | 0.00 | 0.36 |
December | 83750030.26 | 0.315232E+09 | 0.00 | 1308138.81 | 0.168124E+09 | 0.00 | 68816633.25 | 0.00 | 0.31 |
Annual Sum or Average | 0.567759E+09 | 0.368800E+11 | 0.00 | 7835612.48 | 0.523153E+10 | 0.00 | 0.470522E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 68993729.30 | 0.00 | 0.00 | 79974920.77 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.245776E+09 | 0.840466E+10 | 0.00 | 1670918.15 | 0.113308E+10 | 0.00 | 0.147512E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167812E+09 | 69663872.45 | 0.00 | 1505607.58 | 57558141.38 | 220183.26 | 0.147279E+09 | 0.00 | 0.39 |
February | 75694861.02 | 0.159978E+09 | 0.00 | 1472672.26 | 93133961.32 | 0.00 | 94294179.24 | 0.00 | 0.42 |
March | 59749865.08 | 0.425493E+09 | 0.00 | 1393583.60 | 53435463.92 | 0.00 | 80838290.80 | 0.00 | 0.47 |
April | 28201436.06 | 0.103556E+10 | 0.00 | 538572.15 | 0.138638E+09 | 0.00 | 19034536.42 | 0.00 | 0.54 |
May | 4854769.49 | 0.241895E+10 | 0.00 | 221992.09 | 0.276138E+09 | 0.00 | 7077536.20 | 0.00 | 0.64 |
June | 835817.96 | 0.412145E+10 | 0.00 | 76516.06 | 0.435818E+09 | 0.00 | 1447852.62 | 0.00 | 0.67 |
July | 289899.00 | 0.565185E+10 | 0.00 | 8854.60 | 0.953688E+09 | 0.00 | 59410.04 | 0.00 | 0.72 |
August | 0.00 | 0.631111E+10 | 0.00 | 0.00 | 0.914650E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 100153.46 | 0.436676E+10 | 0.00 | 6085.99 | 0.566102E+09 | 0.00 | 72648.75 | 0.00 | 0.63 |
October | 4815157.70 | 0.235300E+10 | 0.00 | 323105.06 | 0.356294E+09 | 0.00 | 7649759.07 | 0.00 | 0.54 |
November | 2109836.14 | 0.107719E+10 | 0.00 | 306420.84 | 0.143258E+09 | 0.00 | 7542866.86 | 0.00 | 0.46 |
December | 58637788.59 | 0.265871E+09 | 0.00 | 1087008.27 | 0.125117E+09 | 0.00 | 61470892.62 | 0.00 | 0.39 |
Annual Sum or Average | 0.403102E+09 | 0.282569E+11 | 0.00 | 6940418.50 | 0.411383E+10 | 220183.26 | 0.426767E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 69663872.45 | 0.00 | 0.00 | 53435463.92 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.167812E+09 | 0.631111E+10 | 0.00 | 1505607.58 | 0.953688E+09 | 220183.26 | 0.147279E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214530E+09 | 0.181416E+09 | 0.00 | 4113257.20 | 57917870.71 | 0.00 | 0.368080E+09 | 0.00 | 0.47 |
February | 0.101692E+09 | 0.353503E+09 | 0.00 | 3357166.52 | 80319105.42 | 0.00 | 0.208923E+09 | 0.00 | 0.47 |
March | 83029397.82 | 0.696140E+09 | 0.00 | 2578960.34 | 64110286.76 | 0.00 | 0.150936E+09 | 0.00 | 0.48 |
April | 40124109.83 | 0.144393E+10 | 0.00 | 641263.04 | 0.211911E+09 | 0.00 | 24033884.70 | 0.00 | 0.47 |
May | 7467320.79 | 0.310406E+10 | 0.00 | 257998.09 | 0.442253E+09 | 0.00 | 8709845.12 | 0.00 | 0.52 |
June | 1355583.94 | 0.521819E+10 | 0.00 | 90760.64 | 0.677892E+09 | 0.00 | 1693545.19 | 0.00 | 0.55 |
July | 406360.55 | 0.749452E+10 | 0.00 | 8114.04 | 0.139134E+10 | 0.00 | 63392.20 | 0.00 | 0.61 |
August | 0.00 | 0.877657E+10 | 0.00 | 0.00 | 0.128711E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 140388.26 | 0.675475E+10 | 0.00 | 10450.32 | 0.718008E+09 | 0.00 | 101959.18 | 0.00 | 0.60 |
October | 6954758.37 | 0.402698E+10 | 0.00 | 767634.84 | 0.438411E+09 | 0.00 | 13250034.38 | 0.00 | 0.58 |
November | 3088651.34 | 0.209908E+10 | 0.00 | 720089.43 | 0.118888E+09 | 0.00 | 17486634.07 | 0.00 | 0.54 |
December | 74666308.52 | 0.653950E+09 | 0.00 | 3098460.25 | 0.106945E+09 | 0.00 | 0.157693E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.533454E+09 | 0.408031E+11 | 0.00 | 15644154.71 | 0.559511E+10 | 0.00 | 0.950971E+09 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.181416E+09 | 0.00 | 0.00 | 57917870.71 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.214530E+09 | 0.877657E+10 | 0.00 | 4113257.20 | 0.139134E+10 | 0.00 | 0.368080E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224389E+09 | 59657126.35 | 0.00 | 1357013.02 | 76503787.85 | 469498.01 | 0.133671E+09 | 0.00 | 0.43 |
February | 93222499.51 | 0.165563E+09 | 0.00 | 1502949.79 | 0.106614E+09 | 0.00 | 0.101385E+09 | 0.00 | 0.45 |
March | 72041876.49 | 0.427629E+09 | 0.00 | 1446229.72 | 70476187.71 | 0.00 | 94026857.34 | 0.00 | 0.50 |
April | 33154390.55 | 0.104517E+10 | 0.00 | 398694.76 | 0.171573E+09 | 0.00 | 16545917.56 | 0.00 | 0.54 |
May | 7137167.12 | 0.247989E+10 | 0.00 | 168016.76 | 0.326536E+09 | 0.00 | 5591352.46 | 0.00 | 0.63 |
June | 1361432.46 | 0.420642E+10 | 0.00 | 59111.57 | 0.494461E+09 | 0.00 | 1018799.00 | 0.00 | 0.68 |
July | 328063.79 | 0.570056E+10 | 0.00 | 5730.47 | 0.111714E+10 | 0.00 | 49234.43 | 0.00 | 0.74 |
August | 0.00 | 0.642262E+10 | 0.00 | 0.00 | 0.104947E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 151792.87 | 0.452167E+10 | 0.00 | 5756.97 | 0.624752E+09 | 0.00 | 43639.52 | 0.00 | 0.64 |
October | 9724546.23 | 0.228717E+10 | 0.00 | 148317.29 | 0.450606E+09 | 0.00 | 2514739.85 | 0.00 | 0.55 |
November | 2583518.78 | 0.104061E+10 | 0.00 | 361184.47 | 0.193361E+09 | 0.00 | 9587580.22 | 0.00 | 0.47 |
December | 73588590.59 | 0.255796E+09 | 0.00 | 1113567.59 | 0.171502E+09 | 0.00 | 66293806.02 | 0.00 | 0.43 |
Annual Sum or Average | 0.517683E+09 | 0.286127E+11 | 0.00 | 6566572.42 | 0.485300E+10 | 469498.01 | 0.430729E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 59657126.35 | 0.00 | 0.00 | 70476187.71 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.224389E+09 | 0.642262E+10 | 0.00 | 1502949.79 | 0.111714E+10 | 469498.01 | 0.133671E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209167E+09 | 49756150.54 | 0.00 | 3018112.61 | 34693055.13 | 0.00 | 0.285368E+09 | 0.00 | 0.26 |
February | 0.111556E+09 | 0.170517E+09 | 0.00 | 2357567.07 | 44503696.78 | 0.00 | 0.155145E+09 | 0.00 | 0.27 |
March | 97159659.42 | 0.380139E+09 | 0.00 | 2059847.12 | 44288076.48 | 0.00 | 0.122265E+09 | 0.00 | 0.29 |
April | 44080697.98 | 0.911816E+09 | 0.00 | 638094.34 | 0.230241E+09 | 0.00 | 32036510.11 | 0.00 | 0.32 |
May | 6489420.31 | 0.257665E+10 | 0.00 | 240726.01 | 0.440338E+09 | 0.00 | 9682403.99 | 0.00 | 0.41 |
June | 468798.20 | 0.465020E+10 | 0.00 | 53070.99 | 0.569113E+09 | 0.00 | 1535740.14 | 0.00 | 0.46 |
July | 408913.89 | 0.674866E+10 | 0.00 | 4135.99 | 0.123392E+10 | 0.00 | 32635.81 | 0.00 | 0.52 |
August | 0.00 | 0.769744E+10 | 0.00 | 0.00 | 0.132723E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 3747.21 | 0.521364E+10 | 0.00 | 4574.33 | 0.971623E+09 | 0.00 | 4899.42 | 0.00 | 0.47 |
October | 5840962.20 | 0.278723E+10 | 0.00 | 239349.70 | 0.661962E+09 | 0.00 | 11799406.00 | 0.00 | 0.41 |
November | 8353852.99 | 0.118921E+10 | 0.00 | 583365.06 | 0.184572E+09 | 0.00 | 13714411.83 | 0.00 | 0.33 |
December | 85272295.61 | 0.269491E+09 | 0.00 | 2943873.04 | 82993143.58 | 0.00 | 0.167256E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.568802E+09 | 0.326448E+11 | 0.00 | 12142716.25 | 0.582548E+10 | 0.00 | 0.798841E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 49756150.54 | 0.00 | 0.00 | 34693055.13 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.209167E+09 | 0.769744E+10 | 0.00 | 3018112.61 | 0.132723E+10 | 0.00 | 0.285368E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142193E+09 | 41996306.26 | 0.00 | 2869521.36 | 26649051.15 | 0.00 | 0.267411E+09 | 0.00 | 0.35 |
February | 79803626.79 | 0.134258E+09 | 0.00 | 2229852.60 | 32802223.32 | 0.00 | 0.143832E+09 | 0.00 | 0.35 |
March | 72374952.53 | 0.310596E+09 | 0.00 | 1823749.51 | 34219563.62 | 0.00 | 0.106062E+09 | 0.00 | 0.38 |
April | 34170745.96 | 0.788732E+09 | 0.00 | 640490.95 | 0.142928E+09 | 0.00 | 30095693.25 | 0.00 | 0.43 |
May | 4509996.11 | 0.208979E+10 | 0.00 | 214812.70 | 0.279697E+09 | 0.00 | 8439873.52 | 0.00 | 0.53 |
June | 432371.53 | 0.358070E+10 | 0.00 | 34314.34 | 0.425885E+09 | 0.00 | 1139455.36 | 0.00 | 0.56 |
July | 322495.78 | 0.512546E+10 | 0.00 | 4143.12 | 0.943746E+09 | 0.00 | 27983.13 | 0.00 | 0.64 |
August | 0.00 | 0.594461E+10 | 0.00 | 0.00 | 0.100157E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 2955.29 | 0.413956E+10 | 0.00 | 3134.86 | 0.694002E+09 | 0.00 | 4035.74 | 0.00 | 0.59 |
October | 2627527.36 | 0.231129E+10 | 0.00 | 295800.05 | 0.427391E+09 | 0.00 | 13022881.79 | 0.00 | 0.51 |
November | 6323870.44 | 0.941066E+09 | 0.00 | 503698.17 | 0.129760E+09 | 0.00 | 12085897.94 | 0.00 | 0.42 |
December | 55567546.19 | 0.209520E+09 | 0.00 | 2502314.66 | 65150686.60 | 0.00 | 0.148919E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.398329E+09 | 0.256176E+11 | 0.00 | 11121832.33 | 0.420380E+10 | 0.00 | 0.731040E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 41996306.26 | 0.00 | 0.00 | 26649051.15 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.142193E+09 | 0.594461E+10 | 0.00 | 2869521.36 | 0.100157E+10 | 0.00 | 0.267411E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192222E+09 | 0.104543E+09 | 0.00 | 5166866.24 | 24591815.18 | 51411635.12 | 0.400335E+09 | 0.00 | 0.38 |
February | 97090093.56 | 0.297297E+09 | 0.00 | 4072497.41 | 25784754.15 | 25727915.76 | 0.233374E+09 | 0.00 | 0.39 |
March | 96747406.29 | 0.625094E+09 | 0.00 | 2967282.00 | 35383118.74 | 10083603.69 | 0.160178E+09 | 0.00 | 0.42 |
April | 53877810.55 | 0.134555E+10 | 0.00 | 779960.70 | 0.208780E+09 | 47889.34 | 29480950.89 | 0.00 | 0.43 |
May | 6561340.59 | 0.339610E+10 | 0.00 | 328629.27 | 0.481242E+09 | 0.00 | 11814028.40 | 0.00 | 0.53 |
June | 495119.58 | 0.577315E+10 | 0.00 | 60581.80 | 0.678204E+09 | 0.00 | 1657778.44 | 0.00 | 0.58 |
July | 431872.98 | 0.864159E+10 | 0.00 | 4845.31 | 0.138341E+10 | 0.00 | 39787.09 | 0.00 | 0.66 |
August | 0.00 | 0.106843E+11 | 0.00 | 0.00 | 0.133755E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 3957.60 | 0.787011E+10 | 0.00 | 6008.07 | 0.832802E+09 | 0.00 | 6441.78 | 0.00 | 0.66 |
October | 3759828.60 | 0.477715E+10 | 0.00 | 566474.07 | 0.439085E+09 | 0.00 | 18009586.31 | 0.00 | 0.62 |
November | 10606650.80 | 0.218007E+10 | 0.00 | 846088.16 | 94267275.13 | 0.00 | 18126966.78 | 0.00 | 0.53 |
December | 86907304.10 | 0.528058E+09 | 0.00 | 4703585.35 | 48983454.00 | 11329057.63 | 0.248366E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.548703E+09 | 0.462231E+11 | 0.00 | 19502818.37 | 0.559008E+10 | 98600101.53 | 0.112139E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.104543E+09 | 0.00 | 0.00 | 24591815.18 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.192222E+09 | 0.106843E+11 | 0.00 | 5166866.24 | 0.138341E+10 | 51411635.12 | 0.400335E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173746E+09 | 43578251.68 | 0.00 | 2525309.69 | 27336746.30 | 0.00 | 0.241487E+09 | 0.00 | 0.35 |
February | 92946489.43 | 0.145423E+09 | 0.00 | 2069479.15 | 32106509.99 | 0.00 | 0.136973E+09 | 0.00 | 0.36 |
March | 79409460.40 | 0.333645E+09 | 0.00 | 1766785.64 | 29989433.16 | 0.00 | 0.109900E+09 | 0.00 | 0.40 |
April | 38591815.17 | 0.830556E+09 | 0.00 | 447904.64 | 0.135939E+09 | 0.00 | 21986969.80 | 0.00 | 0.42 |
May | 5659870.55 | 0.216648E+10 | 0.00 | 171734.77 | 0.294109E+09 | 0.00 | 7439262.92 | 0.00 | 0.52 |
June | 390825.28 | 0.372415E+10 | 0.00 | 38323.20 | 0.397234E+09 | 0.00 | 1273529.89 | 0.00 | 0.57 |
July | 340901.24 | 0.522074E+10 | 0.00 | 4024.06 | 0.970495E+09 | 0.00 | 33326.70 | 0.00 | 0.64 |
August | 0.00 | 0.610301E+10 | 0.00 | 0.00 | 0.100010E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 3123.96 | 0.431571E+10 | 0.00 | 3200.82 | 0.688501E+09 | 0.00 | 4379.02 | 0.00 | 0.59 |
October | 4869463.39 | 0.231381E+10 | 0.00 | 168951.26 | 0.457818E+09 | 0.00 | 8768094.10 | 0.00 | 0.51 |
November | 7156436.51 | 0.967830E+09 | 0.00 | 456196.16 | 0.123603E+09 | 0.00 | 10717619.64 | 0.00 | 0.42 |
December | 73563900.51 | 0.223196E+09 | 0.00 | 2268660.73 | 69098761.19 | 0.00 | 0.135934E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.476678E+09 | 0.263881E+11 | 0.00 | 9920570.13 | 0.422634E+10 | 0.00 | 0.674517E+09 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 43578251.68 | 0.00 | 0.00 | 27336746.30 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.173746E+09 | 0.610301E+10 | 0.00 | 2525309.69 | 0.100010E+10 | 0.00 | 0.241487E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269980E+09 | 71546942.91 | 0.00 | 2085432.70 | 50363221.97 | 0.00 | 0.212357E+09 | 0.00 | 0.29 |
February | 0.127359E+09 | 0.214789E+09 | 0.00 | 1953491.40 | 60659116.75 | 0.00 | 0.136960E+09 | 0.00 | 0.31 |
March | 98223988.65 | 0.513038E+09 | 0.00 | 2083032.44 | 49026049.45 | 0.00 | 0.130050E+09 | 0.00 | 0.36 |
April | 43867082.16 | 0.124098E+10 | 0.00 | 776114.22 | 0.210980E+09 | 0.00 | 39681628.55 | 0.00 | 0.41 |
May | 6381914.80 | 0.322372E+10 | 0.00 | 349466.88 | 0.334072E+09 | 0.00 | 14819687.36 | 0.00 | 0.51 |
June | 853989.66 | 0.564961E+10 | 0.00 | 78557.71 | 0.475901E+09 | 0.00 | 2072465.74 | 0.00 | 0.56 |
July | 634685.50 | 0.788262E+10 | 0.00 | 20310.85 | 0.935797E+09 | 0.00 | 287678.85 | 0.00 | 0.59 |
August | 0.00 | 0.854626E+10 | 0.00 | 0.00 | 0.966645E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 47237.85 | 0.571207E+10 | 0.00 | 24804.09 | 0.688384E+09 | 0.00 | 402058.82 | 0.00 | 0.50 |
October | 8664881.33 | 0.290919E+10 | 0.00 | 261508.93 | 0.504996E+09 | 0.00 | 7944943.28 | 0.00 | 0.43 |
November | 8590420.80 | 0.130014E+10 | 0.00 | 437612.38 | 0.159202E+09 | 0.00 | 12332075.44 | 0.00 | 0.36 |
December | 0.108140E+09 | 0.328534E+09 | 0.00 | 1846913.46 | 94693653.83 | 0.00 | 0.113025E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.672744E+09 | 0.375925E+11 | 0.00 | 9917245.06 | 0.453072E+10 | 0.00 | 0.669933E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 71546942.91 | 0.00 | 0.00 | 49026049.45 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.269980E+09 | 0.854626E+10 | 0.00 | 2085432.70 | 0.966645E+09 | 0.00 | 0.212357E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202475E+09 | 58613627.68 | 0.00 | 1874557.15 | 40407085.18 | 0.00 | 0.194655E+09 | 0.00 | 0.39 |
February | 98659233.84 | 0.158359E+09 | 0.00 | 1719987.36 | 57443410.81 | 0.00 | 0.119651E+09 | 0.00 | 0.41 |
March | 80267609.76 | 0.405498E+09 | 0.00 | 1678590.40 | 39645311.22 | 0.00 | 0.103680E+09 | 0.00 | 0.46 |
April | 37149300.03 | 0.101598E+10 | 0.00 | 699369.23 | 0.136328E+09 | 0.00 | 34165376.18 | 0.00 | 0.53 |
May | 5372194.07 | 0.244291E+10 | 0.00 | 267469.44 | 0.274342E+09 | 0.00 | 11828372.62 | 0.00 | 0.63 |
June | 892182.02 | 0.416887E+10 | 0.00 | 54373.11 | 0.434470E+09 | 0.00 | 1457676.22 | 0.00 | 0.67 |
July | 522442.20 | 0.573787E+10 | 0.00 | 14752.41 | 0.857168E+09 | 0.00 | 236570.92 | 0.00 | 0.71 |
August | 0.00 | 0.637640E+10 | 0.00 | 0.00 | 0.839914E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 68193.65 | 0.438094E+10 | 0.00 | 12773.88 | 0.563996E+09 | 0.00 | 295282.29 | 0.00 | 0.62 |
October | 5706321.80 | 0.234437E+10 | 0.00 | 281477.64 | 0.358759E+09 | 0.00 | 9661096.87 | 0.00 | 0.54 |
November | 6087379.25 | 0.101294E+10 | 0.00 | 352982.94 | 0.123350E+09 | 0.00 | 10230724.80 | 0.00 | 0.45 |
December | 82842153.20 | 0.256764E+09 | 0.00 | 1479540.34 | 79901228.43 | 0.00 | 95113266.74 | 0.00 | 0.38 |
Annual Sum or Average | 0.520042E+09 | 0.283595E+11 | 0.00 | 8435873.88 | 0.380572E+10 | 0.00 | 0.580974E+09 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 58613627.68 | 0.00 | 0.00 | 39645311.22 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.202475E+09 | 0.637640E+10 | 0.00 | 1874557.15 | 0.857168E+09 | 0.00 | 0.194655E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223289E+09 | 0.170027E+09 | 0.00 | 4940670.63 | 24212612.29 | 0.00 | 0.479151E+09 | 0.00 | 0.46 |
February | 0.121765E+09 | 0.362677E+09 | 0.00 | 3776772.37 | 26910303.13 | 0.00 | 0.252986E+09 | 0.00 | 0.47 |
March | 0.102171E+09 | 0.708078E+09 | 0.00 | 3022447.18 | 33496599.02 | 0.00 | 0.185334E+09 | 0.00 | 0.48 |
April | 48529150.55 | 0.147849E+10 | 0.00 | 827502.40 | 0.180319E+09 | 0.00 | 40714327.99 | 0.00 | 0.47 |
May | 7528791.52 | 0.319412E+10 | 0.00 | 334098.38 | 0.397475E+09 | 0.00 | 14533736.75 | 0.00 | 0.51 |
June | 994344.60 | 0.532664E+10 | 0.00 | 72763.54 | 0.614675E+09 | 0.00 | 2091142.51 | 0.00 | 0.54 |
July | 684567.05 | 0.765966E+10 | 0.00 | 17790.87 | 0.114999E+10 | 0.00 | 294818.17 | 0.00 | 0.59 |
August | 0.00 | 0.899432E+10 | 0.00 | 0.00 | 0.105781E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 50950.39 | 0.692373E+10 | 0.00 | 24592.91 | 0.650963E+09 | 0.00 | 432486.47 | 0.00 | 0.59 |
October | 6898263.04 | 0.415975E+10 | 0.00 | 706452.49 | 0.389338E+09 | 0.00 | 13730934.40 | 0.00 | 0.58 |
November | 8053404.79 | 0.206961E+10 | 0.00 | 773448.78 | 92995601.60 | 0.00 | 20950354.51 | 0.00 | 0.53 |
December | 97139085.60 | 0.634200E+09 | 0.00 | 3953734.81 | 53241943.06 | 0.00 | 0.227365E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.617104E+09 | 0.416813E+11 | 0.00 | 18450274.36 | 0.467143E+10 | 0.00 | 0.123758E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.170027E+09 | 0.00 | 0.00 | 24212612.29 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.223289E+09 | 0.899432E+10 | 0.00 | 4940670.63 | 0.114999E+10 | 0.00 | 0.479151E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243295E+09 | 59017260.60 | 0.00 | 1729755.12 | 46342433.61 | 0.00 | 0.185069E+09 | 0.00 | 0.41 |
February | 0.116270E+09 | 0.175369E+09 | 0.00 | 1686579.81 | 57302988.49 | 0.00 | 0.121314E+09 | 0.00 | 0.43 |
March | 91008425.99 | 0.437754E+09 | 0.00 | 1686029.49 | 39223314.33 | 0.00 | 0.113975E+09 | 0.00 | 0.49 |
April | 44337497.36 | 0.108389E+10 | 0.00 | 496199.59 | 0.141409E+09 | 0.00 | 23641065.28 | 0.00 | 0.53 |
May | 7788174.57 | 0.260599E+10 | 0.00 | 212500.32 | 0.282453E+09 | 0.00 | 9483523.36 | 0.00 | 0.64 |
June | 960162.36 | 0.439043E+10 | 0.00 | 46028.63 | 0.417723E+09 | 0.00 | 1496813.14 | 0.00 | 0.68 |
July | 562249.99 | 0.593371E+10 | 0.00 | 12453.17 | 0.899142E+09 | 0.00 | 234105.08 | 0.00 | 0.72 |
August | 0.00 | 0.664961E+10 | 0.00 | 0.00 | 0.864811E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 128880.44 | 0.466752E+10 | 0.00 | 12364.52 | 0.554130E+09 | 0.00 | 261859.83 | 0.00 | 0.63 |
October | 8267209.41 | 0.235979E+10 | 0.00 | 160109.83 | 0.407258E+09 | 0.00 | 5334163.98 | 0.00 | 0.55 |
November | 8871242.72 | 0.104647E+10 | 0.00 | 359499.30 | 0.128273E+09 | 0.00 | 9946219.80 | 0.00 | 0.46 |
December | 0.101920E+09 | 0.273515E+09 | 0.00 | 1486400.57 | 93396126.99 | 0.00 | 93913544.72 | 0.00 | 0.41 |
Annual Sum or Average | 0.623409E+09 | 0.296831E+11 | 0.00 | 7887920.34 | 0.393146E+10 | 0.00 | 0.564670E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 59017260.60 | 0.00 | 0.00 | 39223314.33 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.243295E+09 | 0.664961E+10 | 0.00 | 1729755.12 | 0.899142E+09 | 0.00 | 0.185069E+09 | 0.00 | 0.74 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147811E+12 | 0.187965E+10 | 0.00 | 0.202473E+11 | 0.131800E+12 |
February | 0.162238E+12 | 0.523213E+09 | 0.00 | 0.331036E+10 | 0.145105E+12 |
March | 0.198338E+12 | -772903616.3 | 0.00 | -0.735714E+10 | 0.199782E+12 |
April | 0.207990E+12 | -0.346495E+10 | 0.00 | -0.425629E+11 | 0.247062E+12 |
May | 0.215371E+12 | -0.805773E+10 | 0.00 | -0.984782E+11 | 0.379110E+12 |
June | 0.204941E+12 | -0.128295E+11 | 0.00 | -0.161935E+12 | 0.458345E+12 |
July | 0.201709E+12 | -0.169664E+11 | 0.00 | -0.222261E+12 | 0.553661E+12 |
August | 0.196268E+12 | -0.188895E+11 | 0.00 | -0.238294E+12 | 0.602483E+12 |
September | 0.176210E+12 | -0.137033E+11 | 0.00 | -0.186073E+12 | 0.470847E+12 |
October | 0.153816E+12 | -0.833899E+10 | 0.00 | -0.115686E+12 | 0.368171E+12 |
November | 0.126866E+12 | -0.401605E+10 | 0.00 | -0.496628E+11 | 0.256451E+12 |
December | 0.127365E+12 | 56806295.23 | 0.00 | -0.591222E+10 | 0.166028E+12 |
Annual Sum or Average | 0.211892E+13 | -0.845796E+11 | 0.00 | -0.110466E+13 | 0.397885E+13 |
Minimum of Months | 0.126866E+12 | -0.188895E+11 | 0.00 | -0.238294E+12 | 0.131800E+12 |
Maximum of Months | 0.215371E+12 | 0.187965E+10 | 0.00 | 0.202473E+11 | 0.602483E+12 |