Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2024-07-03 12:20:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1979.12 | 397.24 | 397.24 |
Net Site Energy | 1979.12 | 397.24 | 397.24 |
Total Source Energy | 6267.88 | 1258.06 | 1258.06 |
Net Source Energy | 6267.88 | 1258.06 | 1258.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 679.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 155.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1979.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 679.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 155.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 679.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 155.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 38.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 176.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 176.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1979.121 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1979.121 | 100.00 |
Total On-Site and Utility Electric Sources | 1979.121 | 100.00 |
Total Electricity End Uses | 1979.121 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 41.50 |
Time Setpoint Not Met During Occupied Cooling | 556.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1526.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 12-JUN-14:09 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 103322.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41659.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28252.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1951.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 202283.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 103322.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 28252.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 1951.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 24.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2151.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 952.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 491.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 122.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6267.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 431.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1258.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 431.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1258.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.78 | 0.269753 | 0.286000 | 0.794595 | 0.719340 | 0.500000 | 0.001412 |
CORE_MID VAV BOX COMPONENT | 2.31 | 0.324365 | 0.338000 | 0.780959 | 0.864974 | 0.500000 | 0.001175 |
CORE_TOP VAV BOX COMPONENT | 2.62 | 0.285785 | 0.312000 | 0.818202 | 0.762094 | 0.500000 | 0.001333 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.956734 | 0.165137 | 0.200000 | 0.191347 | 0.440364 | 0.500000 | 0.002307 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.732291 | 0.136587 | 0.200000 | 0.146458 | 0.364233 | 0.500000 | 0.002789 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.971895 | 0.162560 | 0.200000 | 0.194379 | 0.433495 | 0.500000 | 0.002344 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.816270 | 0.122527 | 0.200000 | 0.163254 | 0.326739 | 0.500000 | 0.003110 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.791326 | 0.199654 | 0.212000 | 0.167761 | 0.532411 | 0.500000 | 0.001908 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.643019 | 0.155550 | 0.200000 | 0.128604 | 0.414801 | 0.500000 | 0.002449 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.805464 | 0.196150 | 0.208000 | 0.167537 | 0.523066 | 0.500000 | 0.001942 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.673046 | 0.148601 | 0.200000 | 0.134609 | 0.396269 | 0.500000 | 0.002564 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.819471 | 0.192797 | 0.201000 | 0.164714 | 0.514126 | 0.500000 | 0.001976 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.679226 | 0.147259 | 0.200000 | 0.135845 | 0.392690 | 0.500000 | 0.002587 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.836225 | 0.188934 | 0.200000 | 0.167245 | 0.503825 | 0.500000 | 0.002017 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.721941 | 0.138537 | 0.200000 | 0.144388 | 0.369431 | 0.500000 | 0.002750 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25869.07 |
CORE_MID VAV BOX REHEAT COIL | 25425.12 |
CORE_TOP VAV BOX REHEAT COIL | 27865.62 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11087.34 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7215.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11080.61 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7225.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7333.68 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4858.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7333.66 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4876.06 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8626.08 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5683.78 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8615.36 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5701.43 |
PACU_VAV_BOT HEATING COIL | 5260.13 |
PACU_VAV_MID HEATING COIL | 6269.08 |
PACU_VAV_TOP HEATING COIL | 5002.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.85 | 1.39 | 5.69 | 1.39 | 5.35 | 5.35 | 0.300000 | 0.260411 | 5.35 |
PACU_VAV_MID | 2.68 | 1.39 | 5.37 | 1.39 | 4.98 | 4.98 | 0.300000 | 0.279678 | 4.98 |
PACU_VAV_TOP | 3.05 | 1.51 | 6.10 | 2.05 | 5.98 | 5.98 | 0.300000 | 0.342662 | 5.98 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.35 |
PACU_VAV_MID_OA_CONTROLLER | 4.98 |
PACU_VAV_TOP_OA_CONTROLLER | 5.98 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.35 | 119786.12 | 0.734800 | 1.78 | 39924.71 | 0.734800 |
PACU_VAV_MID COOLING COIL | 4.98 | 113410.32 | 0.729313 | 1.66 | 37799.66 | 0.729313 |
PACU_VAV_TOP COOLING COIL | 5.98 | 130697.51 | 0.743574 | 1.99 | 43561.48 | 0.743574 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.35 |
PACU_VAV_MID FAN | 4.98 |
PACU_VAV_TOP FAN | 5.98 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5025E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5418E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8753E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9078E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2046E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2299E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3474E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.0012E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1027 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2188E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4379E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8652E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5041E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5520E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8771E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9190E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2065E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2385E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9200E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7695E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6402E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5486E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7284E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3340E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4528E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4680E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2313E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2423E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0279E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0321E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8585E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8950E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4223E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4516E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1182E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1393E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6192E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4748E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0408E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1355E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8543E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.8625E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8580E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8944E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4215E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4495E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1166E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1333E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9347E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3253E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4589E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0159E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7619E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9014E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8125E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8431E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4570E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4874E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4284E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4451E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7620E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0283E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1062 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3039E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0174E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7143E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7665E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6801E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5042E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4690E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6208E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2689E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0138E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9558E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3951E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5544E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2047E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1699E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8102E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2561E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3581E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9609E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6817E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8553E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7616E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0278E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1062 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3033E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0167E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7138E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7663E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6799E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5041E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4688E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6204E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2687E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0138E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9557E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3952E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5543E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2045E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1698E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8101E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2560E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3581E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9607E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6815E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8551E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37589.17671 | 37589.17671 | 2.77830 | 2.77830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3233.24217 | 3233.24217 | 0.14051 | 0.42469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31284.24785 | 31284.24785 | 2.31053 | 2.31053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10310.02521 | 10310.02521 | 0.44563 | 0.44563 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 35183.35528 | 35183.35528 | 2.62244 | 2.62244 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19664.04722 | 19664.04722 | 0.85592 | 0.85592 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12835.96414 | 12835.96414 | 0.95673 | 0.95673 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8471.15275 | 8471.15275 | 0.34056 | 0.34056 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9824.76536 | 9824.76536 | 0.73229 | 0.73229 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5508.57282 | 5508.57282 | 0.22164 | 0.22164 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13039.37149 | 13039.37149 | 0.97189 | 0.97189 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8466.18975 | 8466.18975 | 0.34035 | 0.34035 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10951.47758 | 10951.47758 | 0.81627 | 0.81627 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5515.92461 | 5515.92461 | 0.22195 | 0.22195 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10616.76779 | 10616.76779 | 0.79133 | 0.79133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5165.90729 | 5165.90729 | 0.22526 | 0.22526 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8627.03490 | 8627.03490 | 0.64302 | 0.64302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3421.45535 | 3421.45535 | 0.14923 | 0.14923 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10806.44593 | 10806.44593 | 0.80546 | 0.80546 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5165.89468 | 5165.89468 | 0.22526 | 0.22526 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9029.90393 | 9029.90393 | 0.67305 | 0.67305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3433.73371 | 3433.73371 | 0.14977 | 0.14977 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10994.36300 | 10994.36300 | 0.81947 | 0.81947 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6071.66589 | 6071.66589 | 0.26496 | 0.26496 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9112.80336 | 9112.80336 | 0.67923 | 0.67923 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3999.99823 | 3999.99823 | 0.17458 | 0.17458 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11219.14770 | 11219.14770 | 0.83623 | 0.83623 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6064.14845 | 6064.14845 | 0.26463 | 0.26463 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9685.89428 | 9685.89428 | 0.72194 | 0.72194 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4012.36690 | 4012.36690 | 0.17513 | 0.17513 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 95967.30 | 5.34963 | 5.34963 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9002.37 | 1.17422 | 1.17422 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 90976.10 | 4.98127 | 4.98127 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9150.96 | 1.32493 | 1.32493 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 104082.99 | 5.98241 | 5.98241 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 8860.20 | 2.04994 | 2.04994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.77830 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26975 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79460 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71934 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41241E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25869.07092 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31053 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32437 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78096 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86497 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17460E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25425.12154 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.62244 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28579 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81820 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76209 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33317E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27865.61520 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95673 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16514 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19135 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44036 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30718E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11087.34037 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73229 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13659 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14646 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36423 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78942E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7215.78812 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97189 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16256 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19438 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43349 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34374E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11080.60914 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81627 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12253 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16325 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32674 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10951E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7225.75870 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79133 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19965 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16776 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53241 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90830E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7333.67537 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64302 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15555 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12860 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41480 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44937E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4858.52406 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80546 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19615 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16754 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52307 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94239E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7333.65735 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67305 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14860 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13461 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39627 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56392E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4876.06438 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81947 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19280 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16471 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51413 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97617E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8626.08427 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67923 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14726 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13585 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39269 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58729E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5683.78105 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83623 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18893 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16725 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50382 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01657E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8615.35726 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72194 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13854 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14439 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36943 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.75017E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5701.43490 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.84558 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39311 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.69116 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39311 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.34963 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.34963 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.26041 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68370 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39315 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.36739 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39315 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.98127 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.98127 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.27968 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.04982 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51364 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.09963 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04994 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.98241 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.98241 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.34266 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.34963 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.98127 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.98241 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.34963 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.34963 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 119786.12068 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73480 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.78303 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39924.71402 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73480 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 5260.12712 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.34963 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.98127 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.98127 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113410.32147 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72931 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.66026 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37799.66015 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72931 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 6269.07979 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.98127 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.98241 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.98241 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 130697.51035 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74357 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.99394 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 43561.48020 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74357 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 5002.16747 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.98241 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 119183.84 | 406672.16 | 12.35 | 3.16 | 3.54 | 3.73 | 3.89 | 10.79 | 12.07 | 12.72 | 13.27 | 6.0313 | 4.8037 | 3.2338 | 1.3470 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 112904.76 | 385247.05 | 12.39 | 3.17 | 3.55 | 3.74 | 3.90 | 10.81 | 12.11 | 12.76 | 13.30 | 5.6160 | 4.4711 | 3.0099 | 1.2601 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 129927.87 | 443332.30 | 12.29 | 3.15 | 3.52 | 3.71 | 3.88 | 10.75 | 12.01 | 12.65 | 13.23 | 6.7448 | 5.3771 | 3.6204 | 1.4949 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.3034083214E-003 | 4.8947442703E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.3125810089E-002 | 6.4354675412E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4803973478E-002 | 6.4196257730E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3052044106E-002 | 6.0597091141E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.7309171625E-003 | 5.5737519086E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.9461621832E-002 | 1.5751696369E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9306926454E-002 | 2.8204654744E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.6759517488E-002 | 3.7835973676E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.7626393088E-002 | 5.7784201096E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.9717473494E-002 | 4.7369064744E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8870484649E-002 | 1.8757756530E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.5011160641E-002 | 3.3221190062E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.5733675187E-002 | 4.0775603257E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.2059701652E-002 | 3.3646956532E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3847200593E-002 | 1.9545312012E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2133057044E-002 | 3.9069621223E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.1086932078E-002 | 4.9876000097E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.2621981947E-002 | 3.8438699021E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2479.19 | -43.8 | 0.00 | -709.1 | 3362.23 | 5088.49 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 8.75 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 5.50 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 8.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 5.50 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 8.73 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.60 | 0.0000 | Y | 5.49 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.33 | 0.0000 | Y | 8.58 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.61 | 0.0000 | Y | 5.49 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 8.75 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 5.50 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 8.59 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 5.50 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.75 | 41.75 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.75 | 62.75 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.75 | 46.80 | 41.42 | |
Exterior Lighting Total | 5686.19 | 50.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 119786.12 | 88018.84 | 31767.28 | 0.73 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113410.32 | 82711.58 | 30698.74 | 0.73 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 130697.51 | 97183.31 | 33514.20 | 0.74 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 119183.8 | 3.16 | 10.79 | N/A | N/A | 12.35 | |
PACU_VAV_MID COOLING COIL | 112904.8 | 3.17 | 10.81 | N/A | N/A | 12.39 | |
PACU_VAV_TOP COOLING COIL | 129927.9 | 3.15 | 10.75 | N/A | N/A | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25869.07 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25425.12 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 27865.62 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11087.34 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7215.79 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11080.61 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7225.76 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7333.68 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4858.52 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7333.66 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4876.06 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8626.08 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5683.78 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8615.36 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5701.43 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 5260.13 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 6269.08 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 5002.17 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.35 | 11634.85 | 2174.89 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.98 | 10904.06 | 2189.01 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.98 | 13011.08 | 2174.89 | 1.00 | 1.13 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 119183.84 | 3.16 | 10.79 | 12.35 | 6.0313 | 3.54 | 12.07 | 4.8037 | 3.73 | 12.72 | 3.2338 | 3.89 | 13.27 | 1.3470 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112904.76 | 3.17 | 10.81 | 12.39 | 5.6160 | 3.55 | 12.11 | 4.4711 | 3.74 | 12.76 | 3.0099 | 3.90 | 13.30 | 1.2601 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 129927.87 | 3.15 | 10.75 | 12.29 | 6.7448 | 3.52 | 12.01 | 5.3771 | 3.71 | 12.65 | 3.6204 | 3.88 | 13.23 | 1.4949 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37589.18 | 37589.18 | 38.22 | 2.778 | 2.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 31284.25 | 31284.25 | 31.81 | 2.311 | 2.311 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 34.82 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 35183.36 | 35183.36 | 35.77 | 2.622 | 2.622 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00884 | 41.81 | 0.00916 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12835.96 | 12835.96 | 61.91 | 0.957 | 0.957 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00870 | 41.61 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9824.77 | 9824.77 | 74.85 | 0.732 | 0.732 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00867 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13039.37 | 13039.37 | 62.89 | 0.972 | 0.972 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00870 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10951.48 | 10951.48 | 83.44 | 0.816 | 0.816 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00865 | 41.16 | 0.00916 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10616.77 | 10616.77 | 51.21 | 0.791 | 0.791 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00874 | 41.71 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8627.03 | 8627.03 | 65.72 | 0.643 | 0.643 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00869 | 39.53 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10806.45 | 10806.45 | 52.12 | 0.805 | 0.805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00874 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9029.90 | 9029.90 | 68.80 | 0.673 | 0.673 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00868 | 41.03 | 0.00916 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10994.36 | 10994.36 | 53.03 | 0.819 | 0.819 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00873 | 41.61 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9112.80 | 9112.80 | 69.42 | 0.679 | 0.679 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00868 | 39.04 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11219.15 | 11219.15 | 54.11 | 0.836 | 0.836 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00873 | 42.00 | 0.00916 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9685.89 | 9685.89 | 73.80 | 0.722 | 0.722 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00867 | 41.16 | 0.00916 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3233.24 | 3233.24 | 3.29 | 0.141 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_MID | 10310.03 | 10310.03 | 10.48 | 0.446 | 0.446 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
CORE_TOP | 19664.05 | 19664.05 | 19.99 | 0.856 | 0.856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8471.15 | 8471.15 | 40.86 | 0.341 | 0.341 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00795 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5508.57 | 5508.57 | 41.97 | 0.222 | 0.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00795 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8466.19 | 8466.19 | 40.83 | 0.340 | 0.340 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00795 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5515.92 | 5515.92 | 42.02 | 0.222 | 0.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00795 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5165.91 | 5165.91 | 24.92 | 0.225 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3421.46 | 3421.46 | 26.07 | 0.149 | 0.149 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5165.89 | 5165.89 | 24.92 | 0.225 | 0.225 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3433.73 | 3433.73 | 26.16 | 0.150 | 0.150 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6071.67 | 6071.67 | 29.28 | 0.265 | 0.265 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4000.00 | 4000.00 | 30.47 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6064.15 | 6064.15 | 29.25 | 0.265 | 0.265 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4012.37 | 4012.37 | 30.57 | 0.175 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.35 | 5.35 | 1.17 | 1.17 | 5.3496 | 1.3931 | 5.3496 | 0.2604 | 0.3000 |
PACU_VAV_MID | 4.98 | 4.98 | 1.32 | 1.32 | 4.9813 | 1.3932 | 4.9813 | 0.2797 | 0.3000 |
PACU_VAV_TOP | 5.98 | 5.98 | 2.05 | 2.05 | 5.9824 | 2.0499 | 5.9824 | 0.3427 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25869.071 | 25869.071 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25869.07 | 13826.37 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00799971 | 50.4107 | 3233.24 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25425.122 | 25425.122 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25425.12 | 14508.19 | 0.445634 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 10310.03 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27865.615 | 27865.615 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27865.62 | 27865.62 | 0.855921 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 19664.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11087.340 | 11087.340 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11087.34 | 11087.34 | 0.340559 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00795296 | 51.0663 | 8471.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7215.788 | 7215.788 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7215.79 | 7215.79 | 0.221640 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00795431 | 51.0755 | 5508.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11080.609 | 11080.609 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11080.61 | 11080.61 | 0.340352 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00795284 | 51.0655 | 8466.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7225.759 | 7225.759 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7225.76 | 7225.76 | 0.221947 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 20.70 | 0.00795459 | 51.0773 | 5515.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7333.675 | 7333.675 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7333.68 | 7333.68 | 0.225261 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797455 | 50.2544 | 5165.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4858.524 | 4858.524 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4858.52 | 4858.52 | 0.149235 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797504 | 50.2574 | 3421.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7333.657 | 7333.657 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7333.66 | 7333.66 | 0.225261 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797455 | 50.2544 | 5165.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4876.064 | 4876.064 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4876.06 | 4876.06 | 0.149773 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797518 | 50.2583 | 3433.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8626.084 | 8626.084 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8626.08 | 8626.08 | 0.264959 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797109 | 50.2330 | 6071.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5683.781 | 5683.781 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5683.78 | 5683.78 | 0.174583 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797164 | 50.2364 | 4000.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8615.357 | 8615.357 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8615.36 | 8615.36 | 0.264630 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797103 | 50.2326 | 6064.15 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5701.435 | 5701.435 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5701.43 | 5701.43 | 0.175125 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797180 | 50.2373 | 4012.37 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 119786.121 | 88018.838 | 5.349633 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 110927.38 | 105177.75 | 5.349633 | 28.02 | 17.81 | 0.00886741 | 10.99 | 10.99 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 22.3412 | 24.00 | 0.00878373 | 46.0731 | 71699.95 | 0.00 | 123515.57 | 88428.47 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 5260.127 | 5260.127 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5260.13 | 5260.13 | 1.604890 | 10.02 | 8.63 | 0.00656032 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 74.4705 | 21.00 | 0.00797871 | 50.2802 | 20420.23 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 113410.321 | 82711.581 | 4.981271 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 105350.37 | 99658.22 | 4.981271 | 28.33 | 17.93 | 0.00889078 | 10.97 | 10.97 | 0.00850000 | 42.00 | 0.00915790 | 22.26 | 23.9933 | 24.00 | 0.00880613 | 46.1890 | 66630.35 | 0.00 | 116941.26 | 83120.65 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 6269.080 | 6269.080 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6269.08 | 6269.08 | 1.494381 | 9.24 | 8.15 | 0.00645628 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 79.9776 | 21.00 | 0.00798954 | 50.3476 | 26317.82 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 130697.510 | 97183.305 | 5.982413 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 120635.61 | 114748.32 | 5.982413 | 27.58 | 17.64 | 0.00883589 | 10.99 | 10.99 | 0.00850000 | 41.90 | 0.00915774 | 22.24 | 19.9781 | 24.00 | 0.00875532 | 45.9261 | 80082.03 | 0.00 | 134766.68 | 97567.88 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 5002.167 | 5002.167 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5002.17 | 5002.17 | 1.794724 | 10.44 | 8.97 | 0.00669938 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 66.5935 | 19.60 | 0.00794933 | 54.6253 | 31512.67 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25869.071 | 25869.071 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25869.07 | 13826.37 | 1.0000 | 0.49849623 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25869.07 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.81 | 0.00799971 | 21.00 | 0.00799971 | 50.4107 | 3233.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25425.122 | 25425.122 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25425.12 | 14508.19 | 1.0000 | 0.52307857 | 0.445634 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25425.12 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.82 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 10310.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 27865.615 | 27865.615 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27865.62 | 27865.62 | 1.0000 | 1.00466754 | 0.855921 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27865.62 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 19664.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11087.340 | 11087.340 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11087.34 | 11087.34 | 1.0000 | 0.39974323 | 0.340559 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11087.34 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00795296 | 20.70 | 0.00795296 | 51.0663 | 8471.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7215.788 | 7215.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7215.79 | 7215.79 | 1.0000 | 0.26015819 | 0.221640 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7215.79 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00795431 | 20.70 | 0.00795431 | 51.0755 | 5508.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11080.609 | 11080.609 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11080.61 | 11080.61 | 1.0000 | 0.39950054 | 0.340352 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11080.61 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00795284 | 20.70 | 0.00795284 | 51.0655 | 8466.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7225.759 | 7225.759 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7225.76 | 7225.76 | 1.0000 | 0.26051767 | 0.221947 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7225.76 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 19.48 | 0.00795459 | 20.70 | 0.00795459 | 51.0773 | 5515.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7333.675 | 7333.675 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7333.68 | 7333.68 | 1.0000 | 0.26440850 | 0.225261 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7333.68 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797455 | 21.00 | 0.00797455 | 50.2544 | 5165.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4858.524 | 4858.524 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4858.52 | 4858.52 | 1.0000 | 0.17516934 | 0.149235 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4858.52 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797504 | 21.00 | 0.00797504 | 50.2574 | 3421.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7333.657 | 7333.657 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7333.66 | 7333.66 | 1.0000 | 0.26440785 | 0.225261 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7333.66 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797455 | 21.00 | 0.00797455 | 50.2544 | 5165.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4876.064 | 4876.064 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4876.06 | 4876.06 | 1.0000 | 0.17580174 | 0.149773 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4876.06 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797518 | 21.00 | 0.00797518 | 50.2583 | 3433.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8626.084 | 8626.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8626.08 | 8626.08 | 1.0000 | 0.31100504 | 0.264959 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8626.08 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797109 | 21.00 | 0.00797109 | 50.2330 | 6071.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5683.781 | 5683.781 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5683.78 | 5683.78 | 1.0000 | 0.20492318 | 0.174583 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5683.78 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797164 | 21.00 | 0.00797164 | 50.2364 | 4000.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8615.357 | 8615.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8615.36 | 8615.36 | 1.0000 | 0.31061829 | 0.264630 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8615.36 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797103 | 21.00 | 0.00797103 | 50.2326 | 6064.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5701.435 | 5701.435 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5701.43 | 5701.43 | 1.0000 | 0.20555967 | 0.175125 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5701.43 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00797180 | 21.00 | 0.00797180 | 50.2373 | 4012.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 119786.121 | 88018.838 | 5.349633 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3241 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.349633 | 6.27932095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 110927.38 | 105177.75 | 0.9260 | 6.27932095 | 5.349633 | 28.02 | 17.81 | 0.00886741 | 50799.0 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11634.854 | 99292.53 | 42.00 | 0.00915790 | 22.26 | 1.19517000 | 22.3412 | 24.00 | 0.00878373 | 24.00 | 0.00878373 | 46.0731 | 71699.95 | 0.00 | 123515.57 | 88428.47 | 6.03133524 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.31 | 12.30 | 0.00890376 | 34843.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5260.127 | 5260.127 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.349633 | 6.27932095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5260.13 | 5260.13 | 1.0000 | 1.88379628 | 1.604890 | 10.02 | 8.63 | 0.00656032 | 26598.9 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5260.13 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 74.4705 | 20.88 | 0.00798379 | 21.00 | 0.00797871 | 50.2802 | 20420.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113410.321 | 82711.581 | 4.981271 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3675 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.981271 | 5.84694297 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 105350.37 | 99658.22 | 0.9289 | 5.84694297 | 4.981271 | 28.33 | 17.93 | 0.00889078 | 51171.5 | 10.97 | 10.97 | 0.00850000 | 32458.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10904.056 | 94446.31 | 42.00 | 0.00915790 | 22.26 | 1.19517000 | 23.9933 | 24.00 | 0.00880613 | 24.00 | 0.00880613 | 46.1890 | 66630.35 | 0.00 | 116941.26 | 83120.65 | 5.61603292 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.17 | 12.16 | 0.00882351 | 34499.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6269.080 | 6269.080 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.981271 | 5.84694297 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6269.08 | 6269.08 | 1.0000 | 1.75408289 | 1.494381 | 9.24 | 8.15 | 0.00645628 | 25545.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6269.08 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 79.9776 | 21.00 | 0.00798986 | 21.00 | 0.00798954 | 50.3476 | 26317.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 130697.510 | 97183.305 | 5.982413 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2655 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.982413 | 7.02206894 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 120635.61 | 114748.32 | 0.9230 | 7.02206894 | 5.982413 | 27.58 | 17.64 | 0.00883589 | 50268.4 | 10.99 | 10.99 | 0.00850000 | 32470.4 | -999.0 | -999.00 | -999.00 | -999.00 | 13011.079 | 107624.53 | 41.90 | 0.00915774 | 22.24 | 1.19517000 | 19.9781 | 24.00 | 0.00875532 | 24.00 | 0.00875532 | 45.9261 | 80082.03 | 0.00 | 134766.68 | 97567.88 | 6.74475030 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.51 | 12.50 | 0.00902227 | 35341.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5002.167 | 5002.167 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.982413 | 7.02206894 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5002.17 | 5002.17 | 1.0000 | 2.10662068 | 1.794724 | 10.44 | 8.97 | 0.00669938 | 27372.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5002.17 | 6.30 | 0.00607234 | 6.30 | 1.19517000 | 66.5935 | 18.68 | 0.00794933 | 19.60 | 0.00794933 | 54.6253 | 31512.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4842.67 | 74.67 | 12.83 |
CORE_MID | 3999.17 | 992.83 | 5.50 |
CORE_TOP | 3741.33 | 1553.83 | 29.33 |
PERIMETER_TOP_ZN_3 | 3849.50 | 2158.17 | 456.50 |
PERIMETER_TOP_ZN_2 | 4075.83 | 1941.00 | 484.67 |
PERIMETER_TOP_ZN_1 | 4420.67 | 1540.00 | 494.17 |
PERIMETER_TOP_ZN_4 | 4010.00 | 2053.50 | 510.33 |
PERIMETER_BOT_ZN_3 | 3859.33 | 1737.67 | 202.50 |
PERIMETER_BOT_ZN_2 | 4258.50 | 1377.67 | 317.17 |
PERIMETER_BOT_ZN_1 | 4663.83 | 1945.50 | 1164.17 |
PERIMETER_BOT_ZN_4 | 4210.00 | 1539.33 | 310.33 |
PERIMETER_MID_ZN_3 | 3882.17 | 1818.67 | 305.17 |
PERIMETER_MID_ZN_2 | 3434.83 | 1533.83 | 381.17 |
PERIMETER_MID_ZN_1 | 4556.50 | 1243.17 | 402.50 |
PERIMETER_MID_ZN_4 | 4101.17 | 1746.33 | 370.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5292.83 | 3274.17 | 1526.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.33 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 62.17 | 0.17 | 38.83 |
PERIMETER_TOP_ZN_2 | 0.17 | 87.33 | 0.17 | 65.00 |
PERIMETER_TOP_ZN_1 | 0.17 | 97.50 | 0.17 | 72.17 |
PERIMETER_TOP_ZN_4 | 0.17 | 82.50 | 0.17 | 48.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 35.33 | 0.00 | 22.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 72.00 | 0.00 | 53.50 |
PERIMETER_BOT_ZN_1 | 41.33 | 453.33 | 41.33 | 432.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 76.67 | 0.00 | 40.67 |
PERIMETER_MID_ZN_3 | 0.00 | 45.83 | 0.00 | 29.83 |
PERIMETER_MID_ZN_2 | 0.00 | 70.50 | 0.00 | 58.67 |
PERIMETER_MID_ZN_1 | 0.00 | 89.33 | 0.00 | 72.33 |
PERIMETER_MID_ZN_4 | 0.00 | 67.83 | 0.00 | 40.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 41.50 | 627.83 | 41.50 | 556.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.512 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.434 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.424 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.575 | 0.015 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.741 | 0.015 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.759 | 0.015 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.761 | 0.015 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.478 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.631 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.720 | 1.236 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.632 | 0.008 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.564 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.702 | 0.013 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.771 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.758 | 0.013 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.14 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.67 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.14 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.67 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.81 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8579183.28 | 0.00 | 8579183.28 | 0.00 | 8579183.28 | 13393058.27 | 6811.46 | 101.81 | 1846.72 | 419.36 |
CORE_MID | 7240576.77 | 0.00 | 7240576.77 | 0.00 | 7240576.77 | 13393058.27 | 8428.14 | 54.04 | 277.82 | 345.51 |
CORE_TOP | 7110103.83 | 0.00 | 7110103.83 | 0.00 | 7110103.83 | 13393058.27 | 8685.87 | 16.86 | 57.27 | 369.82 |
PERIMETER_TOP_ZN_3 | 2012647.09 | 0.00 | 2012647.09 | 78254.03 | 2090901.12 | 2823374.22 | 4185.99 | 124.69 | 4449.32 | 369.82 |
PERIMETER_TOP_ZN_2 | 1631622.15 | 0.00 | 1631622.15 | 52169.04 | 1683791.19 | 1787429.43 | 3393.21 | 21.13 | 5345.67 | 369.82 |
PERIMETER_TOP_ZN_1 | 2619034.90 | 0.00 | 2619034.90 | 78254.03 | 2697288.93 | 2823374.22 | 3419.86 | 20.34 | 5319.80 | 369.82 |
PERIMETER_TOP_ZN_4 | 1694572.72 | 0.00 | 1694572.72 | 52169.04 | 1746741.76 | 1787312.18 | 3499.30 | 22.89 | 5237.81 | 369.82 |
PERIMETER_BOT_ZN_3 | 1696490.94 | 0.00 | 1696490.94 | 41607.65 | 1738098.59 | 2823374.22 | 6906.44 | 101.73 | 1751.83 | 419.36 |
PERIMETER_BOT_ZN_2 | 1408541.98 | 0.00 | 1408541.98 | 27738.27 | 1436280.25 | 1787429.43 | 3967.51 | 138.95 | 4653.54 | 419.36 |
PERIMETER_BOT_ZN_1 | 2489231.53 | 0.00 | 2489231.53 | 4055195.49 | 6544427.02 | 2823374.22 | 4968.81 | 38.67 | 3752.52 | 419.36 |
PERIMETER_BOT_ZN_4 | 1422965.22 | 0.00 | 1422965.22 | 27738.27 | 1450703.49 | 1787312.18 | 4157.76 | 130.16 | 4472.07 | 419.36 |
PERIMETER_MID_ZN_3 | 1956420.16 | 0.00 | 1956420.16 | 65140.78 | 2021560.94 | 2823374.22 | 6036.68 | 57.83 | 2665.49 | 345.51 |
PERIMETER_MID_ZN_2 | 1616721.55 | 0.00 | 1616721.55 | 43426.93 | 1660148.48 | 1787429.43 | 3472.56 | 31.58 | 5255.86 | 1254.51 |
PERIMETER_MID_ZN_1 | 2638819.23 | 0.00 | 2638819.23 | 65140.78 | 2703960.01 | 2823374.22 | 4186.81 | 682.78 | 3890.41 | 345.51 |
PERIMETER_MID_ZN_4 | 1673246.01 | 0.00 | 1673246.01 | 43426.93 | 1716672.93 | 1787312.18 | 3602.56 | 29.29 | 5128.14 | 345.51 |
Total Facility | 45790177.35 | 0.00 | 45790177.35 | 4630261.24 | 50420438.59 | 67843644.98 | 8760.00 | 1360.45 | 5712.61 | 1464.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3719 | 0.0000 | 0.3719 | 0.0000 | 0.3719 | 0.4247 | 4011.50 | 101.13 | 1830.38 |
CORE_MID | 0.3150 | 0.0000 | 0.3150 | 0.0000 | 0.3150 | 0.4247 | 5613.10 | 53.89 | 276.01 |
CORE_TOP | 0.3078 | 0.0000 | 0.3078 | 0.0000 | 0.3078 | 0.4247 | 5870.02 | 16.86 | 56.12 |
PERIMETER_TOP_ZN_3 | 0.0878 | 0.0000 | 0.0878 | 0.0022 | 0.0901 | 0.0895 | 1734.17 | 122.25 | 4086.58 |
PERIMETER_TOP_ZN_2 | 0.0716 | 0.0000 | 0.0716 | 0.0015 | 0.0731 | 0.0567 | 944.99 | 21.01 | 4977.00 |
PERIMETER_TOP_ZN_1 | 0.1161 | 0.0000 | 0.1161 | 0.0022 | 0.1183 | 0.0895 | 971.01 | 19.19 | 4952.80 |
PERIMETER_TOP_ZN_4 | 0.0737 | 0.0000 | 0.0737 | 0.0015 | 0.0752 | 0.0567 | 1051.60 | 22.82 | 4868.58 |
PERIMETER_BOT_ZN_3 | 0.0730 | 0.0000 | 0.0730 | 0.0012 | 0.0742 | 0.0895 | 4123.97 | 100.32 | 1718.71 |
PERIMETER_BOT_ZN_2 | 0.0610 | 0.0000 | 0.0610 | 0.0008 | 0.0618 | 0.0567 | 1563.12 | 137.80 | 4242.08 |
PERIMETER_BOT_ZN_1 | 0.1099 | 0.0000 | 0.1099 | 0.1888 | 0.2986 | 0.0895 | 2210.82 | 36.85 | 3695.33 |
PERIMETER_BOT_ZN_4 | 0.0611 | 0.0000 | 0.0611 | 0.0008 | 0.0619 | 0.0567 | 1755.66 | 129.06 | 4058.28 |
PERIMETER_MID_ZN_3 | 0.0861 | 0.0000 | 0.0861 | 0.0019 | 0.0880 | 0.0895 | 3264.80 | 56.45 | 2621.75 |
PERIMETER_MID_ZN_2 | 0.0679 | 0.0000 | 0.0679 | 0.0013 | 0.0691 | 0.0567 | 957.86 | 25.39 | 4050.75 |
PERIMETER_MID_ZN_1 | 0.1179 | 0.0000 | 0.1179 | 0.0019 | 0.1198 | 0.0895 | 1423.27 | 678.18 | 3841.55 |
PERIMETER_MID_ZN_4 | 0.0733 | 0.0000 | 0.0733 | 0.0012 | 0.0746 | 0.0567 | 1130.49 | 29.22 | 4783.29 |
Total Facility | 1.9941 | 0.0000 | 1.9941 | 0.2052 | 2.1993 | 2.1513 | 5943.00 | 1345.57 | 5157.11 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21488305.31 | 0.00 | 21488305.31 | 22614548.33 | 3296.97 | 0.00 | 5463.03 | 419.36 |
PACU_VAV_MID | 20839903.23 | 0.00 | 20839903.23 | 22614548.33 | 3386.86 | 0.00 | 5373.14 | 345.51 |
PACU_VAV_TOP | 20760238.54 | 0.00 | 20760238.54 | 22614548.33 | 3368.74 | 0.00 | 5391.26 | 369.82 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9325 | 0.0000 | 0.9325 | 0.7171 | 899.33 | 0.00 | 5043.67 |
PACU_VAV_MID | 0.9145 | 0.0000 | 0.9145 | 0.7171 | 915.38 | 0.00 | 5027.62 |
PACU_VAV_TOP | 0.9053 | 0.0000 | 0.9053 | 0.7171 | 921.56 | 0.00 | 5021.44 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5463.03 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.14 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5391.26 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0989 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0811 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0715 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
Electricity:Building | 1020.46 | 13470.12 | 16-JUL-17:20 | 74341.76 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1020.46 | 13470.12 | 16-JUL-17:20 | 74341.76 | 11-OCT-07:10 |
InteriorLights:Electricity | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.77 | 992.37 | 16-JUL-17:20 | 32642.50 | 11-OCT-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.09 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.90 | 267.21 | 02-JUL-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.93 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.06 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.89 | 267.21 | 29-MAY-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.91 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.58 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.58 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:40 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:40 | 859.95 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.09 | 422.10 | 02-APR-17:10 | 2793.69 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.75 | 36.00 | 01-JAN-10:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.90 | 267.21 | 02-JUL-17:10 | 1768.58 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.50 | 22.79 | 01-JAN-07:50 | 860.01 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.93 | 422.10 | 12-MAR-17:10 | 2793.68 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.59 | 36.00 | 01-JAN-08:00 | 1358.45 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:50 | 859.95 | 11-OCT-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 869.13 | 367.92 | 01-JAN-00:10 | 132985.22 | 12-JUN-14:10 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
ElectricityPurchased:Facility | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
ElectricityPurchased:Plant | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
Cogeneration:ElectricityPurchased | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
General:Cogeneration:ElectricityPurchased | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
ElectricityNet:Plant | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
Cogeneration:ElectricityNet | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
General:Cogeneration:ElectricityNet | 1979.12 | 13841.23 | 04-JUN-17:20 | 202283.51 | 12-JUN-14:10 |
Heating:Electricity | 7.69 | 0.00 | 01-JAN-00:10 | 98066.79 | 02-JAN-07:10 |
General:Heating:Electricity | 7.69 | 0.00 | 01-JAN-00:10 | 98066.79 | 02-JAN-07:10 |
Fans:Electricity | 155.28 | 0.00 | 01-JAN-00:10 | 28328.66 | 05-JUN-14:10 |
General:Fans:Electricity | 155.28 | 0.00 | 01-JAN-00:10 | 28328.66 | 05-JUN-14:10 |
ExteriorLights:Electricity | 50.64 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.64 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 679.25 | 0.00 | 01-JAN-00:10 | 107743.39 | 12-JUN-15:30 |
General:Cooling:Electricity | 679.25 | 0.00 | 01-JAN-00:10 | 107743.39 | 12-JUN-15:30 |
Electricity:Plant | 38.89 | 0.00 | 01-JAN-00:10 | 5347.92 | 24-JAN-12:50 |
WaterSystems:Electricity | 38.75 | 0.00 | 01-JAN-00:10 | 5341.07 | 24-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 38.75 | 0.00 | 01-JAN-00:10 | 5341.07 | 24-JAN-12:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-06:20 |
WIRED_LTG_ELECTRICITY | 8.45 | 0.00 | 01-JAN-00:10 | 917.25 | 11-OCT-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4527.49 | 0.00 | 01-JAN-00:10 | 524079.06 | 22-JUN-15:30 |
EnergyTransfer:Building | 1800.82 | 0.00 | 01-JAN-00:10 | 205433.97 | 12-JUN-15:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 317.63 | 0.00 | 01-JAN-00:10 | 26644.51 | 05-SEP-07:40 |
Heating:EnergyTransfer | 8.85 | 0.00 | 01-JAN-00:10 | 75043.29 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 8.85 | 0.00 | 01-JAN-00:10 | 75043.29 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1791.97 | 0.00 | 01-JAN-00:10 | 205433.97 | 12-JUN-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 317.63 | 0.00 | 01-JAN-00:10 | 26644.51 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer | 1791.97 | 0.00 | 01-JAN-00:10 | 205433.97 | 12-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 317.63 | 0.00 | 01-JAN-00:10 | 26644.51 | 05-SEP-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 90.17 | 0.00 | 01-JAN-00:10 | 17236.98 | 08-JUN-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.13 | 0.00 | 01-JAN-00:10 | 8636.92 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.13 | 0.00 | 01-JAN-00:10 | 8636.92 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 86.04 | 0.00 | 01-JAN-00:10 | 17236.98 | 08-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 86.04 | 0.00 | 01-JAN-00:10 | 17236.98 | 08-JUN-14:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 47.74 | 0.00 | 01-JAN-00:10 | 7385.10 | 12-JUN-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 2202.17 | 02-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 2202.17 | 02-JAN-10:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.56 | 0.00 | 01-JAN-00:10 | 7385.10 | 12-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 46.56 | 0.00 | 01-JAN-00:10 | 7385.10 | 12-JUN-14:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.73 | 0.00 | 01-JAN-00:10 | 7178.37 | 05-JUL-07:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.55 | 0.00 | 01-JAN-00:10 | 1938.23 | 02-JAN-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.55 | 0.00 | 01-JAN-00:10 | 1938.23 | 02-JAN-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.18 | 0.00 | 01-JAN-00:10 | 7178.37 | 05-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 53.18 | 0.00 | 01-JAN-00:10 | 7178.37 | 05-JUL-07:20 |
EnergyTransfer:Zone:CORE_MID | 225.53 | 0.00 | 01-JAN-00:10 | 21253.76 | 30-MAY-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 4739.80 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 4739.80 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 225.53 | 0.00 | 01-JAN-00:10 | 21253.76 | 30-MAY-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 225.53 | 0.00 | 01-JAN-00:10 | 21253.76 | 30-MAY-07:50 |
EnergyTransfer:Zone:CORE_TOP | 232.52 | 0.00 | 01-JAN-00:10 | 24402.65 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.12 | 0.00 | 01-JAN-00:10 | 14948.66 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.12 | 0.00 | 01-JAN-00:10 | 14948.66 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 232.41 | 0.00 | 01-JAN-00:10 | 24402.65 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 232.41 | 0.00 | 01-JAN-00:10 | 24402.65 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.67 | 0.00 | 01-JAN-00:10 | 10033.46 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.52 | 0.00 | 01-JAN-00:10 | 7771.54 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.52 | 0.00 | 01-JAN-00:10 | 7771.54 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.15 | 0.00 | 01-JAN-00:10 | 10033.46 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 70.15 | 0.00 | 01-JAN-00:10 | 10033.46 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.92 | 0.00 | 01-JAN-00:10 | 9838.43 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.22 | 0.00 | 01-JAN-00:10 | 4985.85 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.22 | 0.00 | 01-JAN-00:10 | 4985.85 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.71 | 0.00 | 01-JAN-00:10 | 9838.43 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.71 | 0.00 | 01-JAN-00:10 | 9838.43 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.04 | 0.00 | 01-JAN-00:10 | 13488.97 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7221.22 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.29 | 0.00 | 01-JAN-00:10 | 7221.22 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.75 | 0.00 | 01-JAN-00:10 | 13488.97 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 92.75 | 0.00 | 01-JAN-00:10 | 13488.97 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.63 | 0.00 | 01-JAN-00:10 | 10817.06 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.33 | 0.00 | 01-JAN-00:10 | 4907.92 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.33 | 0.00 | 01-JAN-00:10 | 4907.92 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.31 | 0.00 | 01-JAN-00:10 | 10817.06 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 58.31 | 0.00 | 01-JAN-00:10 | 10817.06 | 08-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.82 | 0.00 | 01-JAN-00:10 | 9034.01 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2132.99 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2132.99 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.80 | 0.00 | 01-JAN-00:10 | 9034.01 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.80 | 0.00 | 01-JAN-00:10 | 9034.01 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.91 | 0.00 | 01-JAN-00:10 | 8690.04 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1360.34 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1360.34 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.91 | 0.00 | 01-JAN-00:10 | 8690.04 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.91 | 0.00 | 01-JAN-00:10 | 8690.04 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 106.96 | 0.00 | 01-JAN-00:10 | 16097.04 | 12-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.31 | 0.00 | 01-JAN-00:10 | 6688.58 | 03-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.31 | 0.00 | 01-JAN-00:10 | 6688.58 | 03-JAN-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.65 | 0.00 | 01-JAN-00:10 | 16097.04 | 12-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.65 | 0.00 | 01-JAN-00:10 | 16097.04 | 12-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.57 | 0.00 | 01-JAN-00:10 | 9090.70 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1342.03 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1342.03 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.56 | 0.00 | 01-JAN-00:10 | 9090.70 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 56.56 | 0.00 | 01-JAN-00:10 | 9090.70 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.07 | 0.00 | 01-JAN-00:10 | 8988.61 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 3692.16 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 3692.16 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.01 | 0.00 | 01-JAN-00:10 | 8988.61 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 66.01 | 0.00 | 01-JAN-00:10 | 8988.61 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.50 | 0.00 | 01-JAN-00:10 | 9131.42 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2393.11 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2393.11 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.46 | 0.00 | 01-JAN-00:10 | 9131.42 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.46 | 0.00 | 01-JAN-00:10 | 9131.42 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.03 | 0.00 | 01-JAN-00:10 | 11969.82 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3224.04 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3224.04 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.00 | 0.00 | 01-JAN-00:10 | 11969.82 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.00 | 0.00 | 01-JAN-00:10 | 11969.82 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.36 | 0.00 | 01-JAN-00:10 | 9762.86 | 08-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2330.80 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2330.80 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.31 | 0.00 | 01-JAN-00:10 | 9762.86 | 08-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 55.31 | 0.00 | 01-JAN-00:10 | 9762.86 | 08-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
EnergyTransfer:HVAC | 2690.67 | 0.00 | 01-JAN-00:10 | 340795.51 | 22-JUN-15:30 |
HeatingCoils:EnergyTransfer | 7.69 | 0.00 | 01-JAN-00:10 | 98066.79 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2682.98 | 0.00 | 01-JAN-00:10 | 340795.51 | 22-JUN-15:30 |
EnergyTransfer:Plant | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterSystems:EnergyTransfer | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 36.01 | 0.00 | 01-JAN-00:10 | 5004.68 | 17-JAN-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -317.632 | 0.000 | 0.000 | 32.656 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -37.376 |
CORE_MID | 0.000 | 0.000 | 0.003 | -225.526 | 0.000 | 0.000 | 32.872 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 5.297 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.116 | -232.409 | 0.000 | 0.000 | 33.220 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 11.720 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.519 | -70.150 | 0.000 | 0.000 | 7.095 | 8.754 | 24.333 | 33.101 | 0.000 | 0.344 | 10.601 | 0.000 | -14.432 | 0.000 | -0.163 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.216 | -57.708 | 0.000 | 0.000 | 4.442 | 5.499 | 15.404 | 38.353 | 0.000 | 0.226 | 2.825 | 0.000 | -9.140 | 0.000 | -0.116 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.285 | -92.750 | 0.000 | 0.000 | 6.980 | 8.595 | 24.332 | 68.933 | 0.000 | 0.337 | 0.000 | 0.000 | -14.429 | 0.000 | -0.192 | -2.090 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.327 | -58.307 | 0.000 | 0.000 | 4.495 | 5.504 | 15.403 | 38.861 | 0.000 | 0.227 | 3.365 | 0.000 | -9.762 | 0.000 | -0.115 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.019 | -67.803 | 0.000 | 0.000 | 6.999 | 8.726 | 24.333 | 32.980 | 0.000 | 0.187 | 10.660 | 0.000 | -16.002 | 0.000 | -0.099 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -56.906 | 0.000 | 0.000 | 4.393 | 5.487 | 15.404 | 38.170 | 0.000 | 0.121 | 3.681 | 0.000 | -10.283 | 0.000 | -0.071 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.310 | -105.646 | 0.000 | 0.000 | 6.895 | 8.578 | 24.332 | 68.644 | 0.000 | 20.245 | 0.825 | 0.000 | -16.390 | 0.000 | -8.793 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.008 | -56.558 | 0.000 | 0.000 | 4.422 | 5.490 | 15.403 | 38.740 | 0.000 | 0.121 | 3.486 | 0.000 | -11.042 | 0.000 | -0.070 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.068 | -66.005 | 0.000 | 0.000 | 7.011 | 8.754 | 24.333 | 33.050 | 0.000 | 0.287 | 8.368 | 0.000 | -15.714 | 0.000 | -0.153 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.034 | -54.465 | 0.000 | 0.000 | 3.258 | 5.499 | 15.404 | 38.302 | 0.000 | 0.189 | 1.715 | 0.000 | -9.830 | 0.000 | -0.106 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.033 | -88.996 | 0.000 | 0.000 | 6.930 | 8.595 | 24.332 | 68.925 | 0.000 | 0.282 | 0.004 | 0.000 | -15.523 | 0.000 | -0.174 | -4.403 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.047 | -55.314 | 0.000 | 0.000 | 4.447 | 5.504 | 15.403 | 38.852 | 0.000 | 0.189 | 1.550 | 0.000 | -10.573 | 0.000 | -0.106 | -0.000 |
TOPFLOOR_PLENUM | 4.126 | -86.044 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.453 | 81.725 | 0.000 | 0.000 | 0.000 | -0.260 | -0.000 |
MIDFLOOR_PLENUM | 1.182 | -46.563 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.449 | 45.205 | 0.000 | 0.000 | 0.000 | -0.273 | -0.000 |
FIRSTFLOOR_PLENUM | 0.551 | -53.184 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.345 | 52.519 | 0.000 | 0.000 | 0.000 | -0.230 | -0.000 |
Total Facility | 5.858 | -185.791 | 2.990 | -1606.175 | 0.000 | 0.000 | 166.115 | 300.769 | 719.689 | 536.911 | 0.000 | 24.002 | 243.545 | 0.000 | -153.121 | 0.000 | -10.921 | -43.875 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | -43436.49 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 37582.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 29-SEP-04:02 | 0.00 | 0.00 | 0.00 | -34877.84 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 32224.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 15-MAY-04:02 | 0.00 | 0.00 | 0.00 | -39441.81 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 36788.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 | -16639.09 | 0.00 | 0.00 | 22.87 | 36.00 | 478.42 | 4323.45 | 0.00 | 57.05 | 11721.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-10:11 | 0.00 | 0.00 | 0.00 | -13755.66 | 0.00 | 0.00 | 13.03 | 22.79 | 302.86 | 6528.28 | 0.00 | 28.35 | 6860.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:01 | 0.00 | 0.00 | 0.00 | -18571.51 | 0.00 | 0.00 | 20.73 | 36.00 | 478.41 | 10442.63 | 0.00 | 6.99 | 7586.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:11 | 0.00 | 0.00 | 0.00 | -15351.89 | 0.00 | 0.00 | 9.96 | 22.79 | 302.86 | 8414.53 | 0.00 | 38.04 | 6563.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-18:32 | 0.00 | 0.00 | 0.00 | -13466.74 | 0.00 | 0.00 | 0.00 | 43.02 | 386.10 | 2553.23 | 0.00 | 37.91 | 10446.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 11-JUN-10:11 | 0.00 | 0.00 | 0.00 | -11642.34 | 0.00 | 0.00 | 14.69 | 22.79 | 302.86 | 6643.01 | 0.00 | 16.26 | 4642.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 12-JUN-17:00 | 0.00 | 0.00 | 0.00 | -16098.14 | 0.00 | 0.00 | 136.67 | 359.99 | 797.35 | 3700.92 | 0.00 | 16143.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5040.13 |
PERIMETER_BOT_ZN_4 | 01-OCT-15:21 | 0.00 | 0.00 | 0.00 | -12343.87 | 0.00 | 0.00 | 14.20 | 22.79 | 302.86 | 7670.61 | 0.00 | 11.40 | 4322.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-16:41 | 0.00 | 0.00 | 0.00 | -13606.86 | 0.00 | 0.00 | 25.38 | 36.00 | 478.42 | 4491.25 | 0.00 | 102.60 | 8473.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-09:12 | 0.00 | 0.00 | 0.00 | -12124.03 | 0.00 | 0.00 | 12.54 | 22.79 | 302.86 | 8209.55 | 0.00 | 129.60 | 3446.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 12-NOV-13:12 | 0.00 | 0.00 | 0.00 | -15700.10 | 0.00 | 0.00 | 22.63 | 36.00 | 478.41 | 11309.95 | 0.00 | 0.00 | 3859.69 | 0.00 | -0.00 | 0.00 | -6.58 | 0.00 |
PERIMETER_MID_ZN_4 | 24-SEP-15:51 | 0.00 | 0.00 | 0.00 | -13210.18 | 0.00 | 0.00 | 13.81 | 22.79 | 302.86 | 5958.06 | 0.00 | 30.59 | 6882.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-12:02 | 0.00 | -17277.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 | 17188.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUN-06:15 | 0.00 | -9262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 9226.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:09 | 0.00 | -9245.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 9206.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-MAY-04:02 | 0.00 | 10454.49 | 0.00 | -231039.33 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 415.47 | 0.00 | 448.85 | 203080.65 | 0.00 | -3.01 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:01 | 0.00 | 0.00 | 18852.57 | 0.00 | 0.00 | 0.00 | 906.80 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24933.31 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 22730.47 | 0.00 | 0.00 | 0.00 | 496.00 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26968.37 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 10235.71 | 0.00 | 0.00 | 0.00 | 111.40 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1864.51 | 0.00 | 0.00 | -9271.42 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 6562.49 | 0.00 | 0.00 | 0.00 | 70.61 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1243.32 | 0.00 | 0.00 | -5889.14 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 10010.76 | 0.00 | 0.00 | 0.00 | 110.21 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1927.07 | 0.00 | 0.00 | -8982.72 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 6470.75 | 0.00 | 0.00 | 0.00 | 70.54 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1250.95 | 0.00 | 0.00 | -5789.70 |
PERIMETER_BOT_ZN_3 | 04-JAN-07:03 | 0.00 | 0.00 | 5662.95 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2643.00 | 0.00 | 0.00 | -4303.96 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 3765.87 | 0.00 | 0.00 | 0.00 | 62.53 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1614.48 | 0.00 | 0.00 | -2713.29 |
PERIMETER_BOT_ZN_1 | 03-JAN-07:10 | 0.00 | 0.00 | 6872.55 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 9015.03 | 0.00 | -2727.97 | 0.00 | -14443.62 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-07:03 | 0.00 | 0.00 | 3513.85 | 0.00 | 0.00 | 0.00 | 122.36 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1598.67 | 0.00 | 0.00 | -2728.00 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7193.72 | 0.00 | 0.00 | 0.00 | 103.61 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2205.77 | 0.00 | 0.00 | -5880.39 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 4517.99 | 0.00 | 0.00 | 0.00 | 65.83 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1468.95 | 0.00 | 0.00 | -3614.23 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 6980.99 | 0.00 | 0.00 | 0.00 | 102.27 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2268.28 | 0.00 | 0.00 | -5603.80 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 4438.98 | 0.00 | 0.00 | 0.00 | 65.73 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1475.25 | 0.00 | 0.00 | -3528.81 |
TOPFLOOR_PLENUM | 02-JAN-06:23 | 11720.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11720.82 |
MIDFLOOR_PLENUM | 24-DEC-13:43 | 4667.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4689.48 |
FIRSTFLOOR_PLENUM | 31-AUG-04:02 | 4856.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4903.76 |
Total Facility | 02-JAN-07:01 | 5169.78 | 6779.93 | 104146.84 | -6779.93 | 0.00 | 0.00 | 4515.09 | 10880.98 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22823.36 | 0.00 | -16446.02 | -107940.16 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6912 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3496 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3674 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9813 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0996 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9824 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8456 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3931 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6837 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3932 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0498 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5136 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7783 | 2.7783 | 0.7946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3105 | 2.3105 | 0.7810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6224 | 2.6224 | 0.8182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9567 | 0.9567 | 0.1913 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7323 | 0.7323 | 0.1465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9719 | 0.9719 | 0.1944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8163 | 0.8163 | 0.1633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7913 | 0.7913 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6430 | 0.6430 | 0.1286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8055 | 0.8055 | 0.1675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6730 | 0.6730 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8195 | 0.8195 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6792 | 0.6792 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8362 | 0.8362 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7219 | 0.7219 | 0.1444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6912 | 5.3496 | 5.6912 | 1.3931 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3674 | 4.9813 | 5.3674 | 1.3932 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0996 | 5.9824 | 6.0996 | 1.5136 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3892 | 1.3892 | 0.7946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1553 | 1.1553 | 0.7810 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3112 | 1.3112 | 0.8182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4784 | 0.4784 | 0.1913 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3661 | 0.3661 | 0.1465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4859 | 0.4859 | 0.1944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4081 | 0.4081 | 0.1633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3957 | 0.3957 | 0.1678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3215 | 0.3215 | 0.1286 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4027 | 0.4027 | 0.1675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3365 | 0.3365 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4097 | 0.4097 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3396 | 0.3396 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4181 | 0.4181 | 0.1672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3610 | 0.3610 | 0.1444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8456 | 1.3931 | 1.3931 | 1.3931 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6837 | 1.3932 | 1.3932 | 1.3932 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0498 | 1.5136 | 1.5136 | 1.5136 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 41.50 |
Number of hours cooling loads not met | 556.83 |
Number of hours not met | 598.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 7.69 | 98066.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 679.25 | 107743.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.77 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.64 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 155.28 | 28328.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 38.75 | 5341.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1979.12 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1979.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.37 |
Space Heating | 1.54 |
Space Cooling | 136.34 |
Fans (All) | 31.17 |
Service Water Heating | 7.78 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 397.24 |
Subtotal | 397.24 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.20 |
Space Heating | 0.39 |
Space Cooling | 34.32 |
Fans (All) | 7.85 |
Service Water Heating | 1.96 |
Receptacle Equipment | 36.36 |
Miscellaneous | 3.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7898.33 | 861.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8709.67 | 50.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8179.83 | 580.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8117.17 | 642.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8091.17 | 668.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8030.33 | 729.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8283.67 | 476.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8073.00 | 687.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7930.17 | 829.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7941.33 | 818.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8167.67 | 592.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8108.83 | 651.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8062.67 | 697.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7966.33 | 793.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8155.50 | 604.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8547.00 | 213.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8573.50 | 186.50 | 0.00 | 0.00 | 0.00 |
Min | 7898.33 | 43.67 | 0.00 | 0.00 | 0.00 |
Max | 8716.33 | 861.67 | 0.00 | 0.00 | 0.00 |
Average | 8197.36 | 562.64 | 0.00 | 0.00 | 0.00 |
Sum | 147552.50 | 10127.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128012.33 | 291.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128290.67 | 13.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128283.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24641.17 | 267.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128290.67 | 291.67 | 0.00 | 0.00 | 0.00 |
Average | 34110.36 | 32.97 | 0.00 | 0.00 | 0.00 |
Sum | 613986.50 | 593.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7076.67 | 1683.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7472.67 | 1287.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7455.00 | 1305.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7121.17 | 1638.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7111.50 | 1648.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7071.67 | 1688.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7122.17 | 1637.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7094.67 | 1665.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7014.67 | 1745.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6229.17 | 2530.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6986.50 | 1773.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7031.33 | 1728.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7040.17 | 1719.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6963.50 | 1796.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7020.83 | 1739.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 5243.67 | 3516.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6091.67 | 2668.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6529.33 | 2230.67 | 0.00 | 0.00 | 0.00 |
Min | 5243.67 | 1287.33 | 0.00 | 0.00 | 0.00 |
Max | 7472.67 | 3516.33 | 0.00 | 0.00 | 0.00 |
Average | 6870.91 | 1889.09 | 0.00 | 0.00 | 0.00 |
Sum | 123676.33 | 34003.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127245.50 | 1058.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127651.50 | 652.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127565.00 | 739.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24869.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24869.83 | 39.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24850.33 | 58.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20758.00 | 4151.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24844.00 | 65.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24844.67 | 64.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127651.50 | 4151.00 | 0.00 | 0.00 | 0.00 |
Average | 33761.77 | 381.56 | 0.00 | 0.00 | 0.00 |
Sum | 607711.83 | 6868.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174175E+11 | 24861.51 | 27-JAN-07:03 | 10.95 | 9.87 | 0.198973E+10 | 2606.63 | 13-JAN-14:09 | 10.95 | 9.87 |
February | 0.191027E+11 | 37939.61 | 21-FEB-07:02 | 12.08 | 11.15 | 0.180917E+10 | 2606.65 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.264258E+11 | 41757.82 | 13-MAR-05:12 | 20.73 | 15.50 | 0.216182E+10 | 2606.67 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.278103E+11 | 43444.99 | 18-APR-04:02 | 24.53 | 18.88 | 0.192032E+10 | 2606.66 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.316931E+11 | 42593.58 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207876E+10 | 2606.71 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.313307E+11 | 42380.38 | 01-JUN-04:02 | 27.42 | 21.75 | 0.207186E+10 | 2606.69 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.307749E+11 | 42281.48 | 19-JUL-04:03 | 24.72 | 24.59 | 0.192607E+10 | 2606.62 | 13-JUL-13:09 | 24.72 | 24.59 |
August | 0.317149E+11 | 41773.74 | 24-AUG-04:03 | 25.48 | 24.97 | 0.216200E+10 | 2606.64 | 21-AUG-13:09 | 25.48 | 24.97 |
September | 0.288829E+11 | 42006.97 | 30-SEP-04:03 | 24.07 | 22.26 | 0.192084E+10 | 2606.63 | 11-SEP-13:09 | 24.07 | 22.26 |
October | 0.284112E+11 | 41993.63 | 11-OCT-04:02 | 24.15 | 20.56 | 0.199769E+10 | 2606.67 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.242847E+11 | 38869.53 | 13-NOV-07:02 | 16.07 | 12.01 | 0.197635E+10 | 2606.69 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.197815E+11 | 36419.15 | 04-DEC-07:02 | 8.63 | 7.96 | 0.192304E+10 | 2606.65 | 18-DEC-10:09 | 20.03 | 13.57 |
Annual Sum or Average | 0.317630E+12 | 0.239376E+11 | ||||||||
Minimum of Months | 0.174175E+11 | 24861.51 | 8.63 | 7.96 | 0.180917E+10 | 2606.62 | 10.95 | 9.87 | ||
Maximum of Months | 0.317149E+11 | 43444.99 | 27.42 | 24.97 | 0.216200E+10 | 2606.71 | 39.90 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136261E+10 | 4244.00 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.249624E+10 | 8349.28 | 22-FEB-14:50 | 27.08 | 16.22 | 0.00 | 0.00 | 01-FEB-00:10 | 27.08 | 16.22 |
March | 0.604340E+10 | 12920.93 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.101271E+11 | 15206.29 | 26-APR-15:00 | 39.30 | 22.03 | 0.00 | 0.00 | 01-APR-00:10 | 39.30 | 22.03 |
May | 0.129647E+11 | 16939.50 | 01-MAY-14:20 | 43.93 | 22.01 | 0.00 | 0.00 | 01-MAY-00:10 | 43.93 | 22.01 |
June | 0.128282E+11 | 17277.47 | 12-JUN-12:02 | 42.55 | 22.27 | 0.00 | 0.00 | 01-JUN-00:10 | 42.55 | 22.27 |
July | 0.103746E+11 | 15592.68 | 10-JUL-13:50 | 39.20 | 26.60 | 0.00 | 0.00 | 01-JUL-00:10 | 39.20 | 26.60 |
August | 0.957214E+10 | 14170.84 | 07-AUG-14:40 | 37.27 | 26.48 | 0.00 | 0.00 | 01-AUG-00:10 | 37.27 | 26.48 |
September | 0.775406E+10 | 12840.70 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.694115E+10 | 12968.44 | 02-OCT-14:20 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.397265E+10 | 8984.16 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.160724E+10 | 5564.19 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.860441E+11 | 0.00 | ||||||||
Minimum of Months | 0.136261E+10 | 4244.00 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.129647E+11 | 17277.47 | 43.93 | 26.60 | 0.00 | 0.00 | 43.93 | 26.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369587E+09 | 2294.26 | 06-JAN-07:02 | 5.62 | 5.52 | 0.00 | 0.00 | 01-JAN-00:10 | 5.62 | 5.52 |
February | 0.989511E+09 | 2779.77 | 22-FEB-15:40 | 26.70 | 16.04 | 0.00 | 0.00 | 01-FEB-00:10 | 26.70 | 16.04 |
March | 0.309227E+10 | 5358.55 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.526718E+10 | 6452.25 | 17-APR-15:10 | 34.65 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 34.65 | 21.60 |
May | 0.689436E+10 | 7219.46 | 30-MAY-06:10 | 30.62 | 21.96 | 0.00 | 0.00 | 01-MAY-00:10 | 30.62 | 21.96 |
June | 0.671367E+10 | 9263.45 | 12-JUN-06:15 | 35.03 | 19.50 | 0.00 | 0.00 | 01-JUN-00:10 | 35.03 | 19.50 |
July | 0.604191E+10 | 7148.25 | 05-JUL-12:03 | 37.65 | 25.58 | 0.00 | 0.00 | 01-JUL-00:10 | 37.65 | 25.58 |
August | 0.582231E+10 | 6775.86 | 28-AUG-06:15 | 29.17 | 27.23 | 0.00 | 0.00 | 01-AUG-00:10 | 29.17 | 27.23 |
September | 0.485505E+10 | 6901.31 | 05-SEP-06:15 | 26.23 | 25.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.23 | 25.18 |
October | 0.400024E+10 | 6220.41 | 02-OCT-16:00 | 35.90 | 21.25 | 0.00 | 0.00 | 01-OCT-00:10 | 35.90 | 21.25 |
November | 0.196322E+10 | 3644.30 | 13-NOV-15:50 | 27.70 | 16.51 | 0.00 | 0.00 | 01-NOV-00:10 | 27.70 | 16.51 |
December | 0.553346E+09 | 2560.90 | 21-DEC-07:01 | 5.68 | 4.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.68 | 4.75 |
Annual Sum or Average | 0.465627E+11 | 0.00 | ||||||||
Minimum of Months | 0.369587E+09 | 2294.26 | 5.62 | 4.75 | 0.00 | 0.00 | 5.62 | 4.75 | ||
Maximum of Months | 0.689436E+10 | 9263.45 | 37.65 | 27.23 | 0.00 | 0.00 | 37.65 | 27.23 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.797551E+09 | 2572.47 | 04-JAN-07:01 | 5.50 | 4.96 | 0.00 | 0.00 | 01-JAN-00:10 | 5.50 | 4.96 |
February | 0.168792E+10 | 3695.35 | 22-FEB-16:00 | 26.50 | 15.96 | 0.00 | 0.00 | 01-FEB-00:10 | 26.50 | 15.96 |
March | 0.378156E+10 | 5969.39 | 28-MAR-17:06 | 34.60 | 18.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.60 | 18.91 |
April | 0.544299E+10 | 7394.09 | 27-APR-12:10 | 38.00 | 21.24 | 0.00 | 0.00 | 01-APR-00:10 | 38.00 | 21.24 |
May | 0.685756E+10 | 9246.40 | 30-MAY-12:09 | 37.90 | 23.62 | 0.00 | 0.00 | 01-MAY-00:10 | 37.90 | 23.62 |
June | 0.680190E+10 | 8505.55 | 12-JUN-07:07 | 35.90 | 20.13 | 0.00 | 0.00 | 01-JUN-00:10 | 35.90 | 20.13 |
July | 0.641936E+10 | 8622.84 | 10-JUL-12:09 | 38.28 | 26.74 | 0.00 | 0.00 | 01-JUL-00:10 | 38.28 | 26.74 |
August | 0.648184E+10 | 7891.06 | 07-AUG-17:08 | 36.48 | 26.95 | 0.00 | 0.00 | 01-AUG-00:10 | 36.48 | 26.95 |
September | 0.561211E+10 | 7568.67 | 05-SEP-06:15 | 26.23 | 25.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.23 | 25.18 |
October | 0.494049E+10 | 6466.34 | 03-OCT-17:08 | 32.53 | 22.15 | 0.00 | 0.00 | 01-OCT-00:10 | 32.53 | 22.15 |
November | 0.309118E+10 | 4715.09 | 13-NOV-16:40 | 26.80 | 16.64 | 0.00 | 0.00 | 01-NOV-00:10 | 26.80 | 16.64 |
December | 0.126979E+10 | 2894.81 | 01-DEC-15:30 | 22.85 | 13.56 | 0.00 | 0.00 | 01-DEC-00:10 | 22.85 | 13.56 |
Annual Sum or Average | 0.531843E+11 | 0.00 | ||||||||
Minimum of Months | 0.797551E+09 | 2572.47 | 5.50 | 4.96 | 0.00 | 0.00 | 5.50 | 4.96 | ||
Maximum of Months | 0.685756E+10 | 9246.40 | 38.28 | 26.95 | 0.00 | 0.00 | 38.28 | 26.95 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104220E+11 | 12155.54 | 26-JAN-17:00 | 18.60 | 12.70 | 0.189493E+10 | 2606.61 | 13-JAN-14:09 | 18.60 | 12.70 |
February | 0.120169E+11 | 15037.51 | 22-FEB-17:00 | 25.70 | 15.75 | 0.178112E+10 | 2606.65 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.182864E+11 | 33975.26 | 13-MAR-05:12 | 20.73 | 15.50 | 0.215281E+10 | 2606.67 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.209514E+11 | 34815.92 | 18-APR-04:02 | 24.53 | 18.88 | 0.191608E+10 | 2606.66 | 04-APR-09:09 | 24.53 | 18.88 |
May | 0.248936E+11 | 34128.64 | 03-MAY-04:02 | 25.78 | 20.40 | 0.207552E+10 | 2606.59 | 01-MAY-09:20 | 25.78 | 20.40 |
June | 0.243128E+11 | 33909.29 | 01-JUN-04:02 | 27.42 | 21.75 | 0.206850E+10 | 2606.63 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.234275E+11 | 33515.75 | 13-JUL-04:02 | 27.87 | 26.38 | 0.192279E+10 | 2606.58 | 05-JUL-09:20 | 27.87 | 26.38 |
August | 0.234267E+11 | 34307.59 | 22-AUG-04:02 | 25.78 | 25.00 | 0.215866E+10 | 2606.57 | 21-AUG-13:39 | 25.78 | 25.00 |
September | 0.207904E+11 | 34884.69 | 29-SEP-04:02 | 24.00 | 21.14 | 0.191728E+10 | 2606.57 | 11-SEP-13:09 | 24.00 | 21.14 |
October | 0.197807E+11 | 34691.08 | 04-OCT-04:02 | 25.08 | 21.56 | 0.199190E+10 | 2606.68 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.156035E+11 | 22674.12 | 13-NOV-07:02 | 16.07 | 12.01 | 0.196291E+10 | 2606.69 | 06-NOV-10:09 | 16.07 | 12.01 |
December | 0.116135E+11 | 13708.65 | 01-DEC-17:00 | 21.20 | 14.26 | 0.187982E+10 | 2606.61 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.225525E+12 | 0.237223E+11 | ||||||||
Minimum of Months | 0.104220E+11 | 12155.54 | 16.07 | 12.01 | 0.178112E+10 | 2606.57 | 16.07 | 12.01 | ||
Maximum of Months | 0.248936E+11 | 34884.69 | 27.87 | 26.38 | 0.215866E+10 | 2606.69 | 42.20 | 26.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.930634E+10 | 11626.68 | 26-JAN-16:30 | 19.40 | 12.94 | 0.176959E+10 | 2606.59 | 12-JAN-14:09 | 19.40 | 12.94 |
February | 0.111179E+11 | 15801.51 | 23-FEB-15:00 | 25.80 | 14.10 | 0.172027E+10 | 2606.63 | 15-FEB-14:09 | 25.80 | 14.10 |
March | 0.180976E+11 | 23172.85 | 13-MAR-05:12 | 20.73 | 15.50 | 0.213728E+10 | 2606.69 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.225149E+11 | 39223.73 | 17-APR-04:02 | 24.68 | 19.16 | 0.191501E+10 | 2606.70 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.275970E+11 | 39439.42 | 15-MAY-04:02 | 24.27 | 18.74 | 0.207654E+10 | 2606.67 | 01-MAY-09:09 | 24.27 | 18.74 |
June | 0.272431E+11 | 38409.81 | 20-JUN-04:02 | 28.05 | 23.71 | 0.206943E+10 | 2606.63 | 05-JUN-13:09 | 28.05 | 23.71 |
July | 0.257577E+11 | 38785.74 | 11-JUL-04:02 | 26.73 | 24.05 | 0.192401E+10 | 2606.57 | 07-JUL-13:09 | 26.73 | 24.05 |
August | 0.251926E+11 | 39336.26 | 21-AUG-04:02 | 25.67 | 25.19 | 0.215923E+10 | 2606.57 | 21-AUG-13:50 | 29.03 | 27.63 |
September | 0.215635E+11 | 38680.95 | 25-SEP-04:02 | 26.32 | 23.72 | 0.191682E+10 | 2606.66 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.194930E+11 | 37991.43 | 02-OCT-05:12 | 21.80 | 17.53 | 0.198434E+10 | 2606.70 | 10-OCT-09:20 | 26.23 | 20.33 |
November | 0.142697E+11 | 17199.25 | 09-NOV-15:00 | 29.20 | 17.71 | 0.192842E+10 | 2606.66 | 09-NOV-10:50 | 29.20 | 17.71 |
December | 0.102547E+11 | 13082.36 | 01-DEC-16:20 | 21.93 | 13.92 | 0.177343E+10 | 2606.62 | 28-DEC-14:09 | 24.58 | 15.31 |
Annual Sum or Average | 0.232408E+12 | 0.233744E+11 | ||||||||
Minimum of Months | 0.930634E+10 | 11626.68 | 19.40 | 12.94 | 0.172027E+10 | 2606.57 | 19.40 | 12.94 | ||
Maximum of Months | 0.275970E+11 | 39439.42 | 29.20 | 25.19 | 0.215923E+10 | 2606.70 | 29.20 | 27.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161021E+10 | 2466.71 | 26-JAN-15:00 | 21.60 | 13.66 | 0.346684E+09 | 549.48 | 26-JAN-14:00 | 21.60 | 13.66 |
February | 0.230207E+10 | 4360.26 | 23-FEB-14:40 | 26.00 | 14.03 | 0.343917E+09 | 549.49 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.462421E+10 | 6703.15 | 28-MAR-15:30 | 35.55 | 18.62 | 0.442609E+09 | 549.51 | 29-MAR-09:00 | 26.40 | 19.31 |
April | 0.715677E+10 | 15799.76 | 16-APR-15:22 | 39.50 | 22.49 | 0.403722E+09 | 549.51 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.986209E+10 | 16207.32 | 21-MAY-14:32 | 33.70 | 23.70 | 0.438872E+09 | 549.51 | 01-MAY-09:09 | 33.70 | 23.70 |
June | 0.100252E+11 | 16641.39 | 11-JUN-16:51 | 43.10 | 23.03 | 0.437397E+09 | 549.50 | 05-JUN-13:09 | 43.10 | 23.03 |
July | 0.909169E+10 | 15958.25 | 04-JUL-16:42 | 39.87 | 24.34 | 0.406951E+09 | 549.48 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.847981E+10 | 15813.86 | 06-AUG-12:42 | 35.17 | 26.30 | 0.456051E+09 | 549.48 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.669164E+10 | 13015.24 | 18-SEP-04:02 | 27.28 | 24.67 | 0.404623E+09 | 549.50 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.528138E+10 | 15376.81 | 09-OCT-14:21 | 32.75 | 19.69 | 0.415336E+09 | 549.51 | 10-OCT-09:20 | 26.23 | 20.33 |
November | 0.315210E+10 | 4789.18 | 09-NOV-14:30 | 29.30 | 17.79 | 0.392727E+09 | 549.50 | 09-NOV-10:50 | 29.30 | 17.79 |
December | 0.187352E+10 | 2480.69 | 01-DEC-15:20 | 23.03 | 13.49 | 0.347129E+09 | 549.49 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.701507E+11 | 0.483601E+10 | ||||||||
Minimum of Months | 0.161021E+10 | 2466.71 | 21.60 | 13.49 | 0.343917E+09 | 549.48 | 21.60 | 13.66 | ||
Maximum of Months | 0.100252E+11 | 16641.39 | 43.10 | 26.30 | 0.456051E+09 | 549.51 | 43.10 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144563E+10 | 2095.54 | 26-JAN-14:10 | 22.35 | 13.84 | 0.232530E+09 | 347.87 | 12-JAN-14:00 | 22.35 | 13.84 |
February | 0.212021E+10 | 4152.49 | 22-FEB-10:50 | 23.10 | 14.47 | 0.227779E+09 | 347.88 | 24-FEB-10:00 | 22.30 | 15.46 |
March | 0.432786E+10 | 11586.97 | 12-MAR-10:32 | 27.43 | 17.74 | 0.284266E+09 | 347.89 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.655155E+10 | 13018.45 | 16-APR-10:02 | 35.32 | 21.70 | 0.256047E+09 | 348.06 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.826410E+10 | 13137.25 | 29-MAY-09:32 | 35.10 | 21.77 | 0.277975E+09 | 348.02 | 03-MAY-09:00 | 35.10 | 21.77 |
June | 0.771390E+10 | 13763.41 | 11-JUN-10:11 | 37.37 | 25.15 | 0.276921E+09 | 348.10 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.668763E+10 | 12818.19 | 02-JUL-08:32 | 34.30 | 25.53 | 0.257656E+09 | 347.96 | 05-JUL-09:09 | 35.53 | 25.08 |
August | 0.619810E+10 | 12822.31 | 06-AUG-09:22 | 31.65 | 24.82 | 0.288699E+09 | 347.87 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.528184E+10 | 8599.79 | 05-SEP-04:02 | 26.28 | 25.12 | 0.256114E+09 | 347.88 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.464277E+10 | 12397.71 | 09-OCT-11:42 | 31.15 | 20.28 | 0.264016E+09 | 347.89 | 19-OCT-09:39 | 28.40 | 21.52 |
November | 0.286494E+10 | 4262.27 | 09-NOV-10:30 | 25.75 | 18.10 | 0.255984E+09 | 347.88 | 09-NOV-10:50 | 26.58 | 18.19 |
December | 0.160979E+10 | 2428.75 | 01-DEC-10:40 | 19.57 | 11.89 | 0.233003E+09 | 347.87 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.577083E+11 | 0.311099E+10 | ||||||||
Minimum of Months | 0.144563E+10 | 2095.54 | 19.57 | 11.89 | 0.227779E+09 | 347.87 | 22.30 | 13.84 | ||
Maximum of Months | 0.826410E+10 | 13763.41 | 37.37 | 25.53 | 0.288699E+09 | 348.10 | 39.75 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374563E+10 | 8536.88 | 12-JAN-14:10 | 23.35 | 14.02 | 0.386914E+09 | 549.50 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.469045E+10 | 17360.70 | 20-FEB-14:22 | 26.35 | 13.75 | 0.361164E+09 | 549.72 | 22-FEB-14:50 | 27.08 | 16.22 |
March | 0.756993E+10 | 16599.11 | 05-MAR-14:13 | 28.90 | 17.37 | 0.447332E+09 | 549.82 | 09-MAR-14:00 | 30.80 | 17.74 |
April | 0.898081E+10 | 16764.19 | 16-APR-14:42 | 39.67 | 22.23 | 0.404105E+09 | 549.70 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.102801E+11 | 16654.99 | 21-MAY-14:32 | 33.70 | 23.70 | 0.438875E+09 | 549.68 | 04-MAY-13:00 | 33.70 | 23.70 |
June | 0.996629E+10 | 16819.68 | 11-JUN-16:11 | 43.30 | 23.15 | 0.437361E+09 | 549.63 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.916621E+10 | 16229.73 | 30-JUL-13:02 | 33.57 | 26.57 | 0.406936E+09 | 549.48 | 05-JUL-13:00 | 33.57 | 26.57 |
August | 0.897192E+10 | 16724.70 | 06-AUG-12:42 | 35.17 | 26.30 | 0.456108E+09 | 549.63 | 07-AUG-13:00 | 37.20 | 26.26 |
September | 0.830632E+10 | 16585.54 | 24-SEP-13:22 | 34.85 | 24.63 | 0.404884E+09 | 549.73 | 19-SEP-13:00 | 34.85 | 24.63 |
October | 0.923642E+10 | 18573.31 | 09-OCT-13:01 | 32.37 | 19.90 | 0.418231E+09 | 569.17 | 02-OCT-13:39 | 32.37 | 19.90 |
November | 0.746191E+10 | 17367.40 | 23-NOV-13:22 | 25.70 | 14.25 | 0.406811E+09 | 549.78 | 06-NOV-14:00 | 25.70 | 14.25 |
December | 0.437477E+10 | 16365.34 | 03-DEC-13:23 | 24.25 | 14.17 | 0.382051E+09 | 549.64 | 01-DEC-14:20 | 24.25 | 14.17 |
Annual Sum or Average | 0.927507E+11 | 0.495077E+10 | ||||||||
Minimum of Months | 0.374563E+10 | 8536.88 | 23.35 | 13.75 | 0.361164E+09 | 549.48 | 23.00 | 13.41 | ||
Maximum of Months | 0.102801E+11 | 18573.31 | 43.30 | 26.57 | 0.456108E+09 | 569.17 | 43.90 | 26.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155483E+10 | 3532.60 | 31-JAN-16:10 | 20.95 | 11.21 | 0.223267E+09 | 347.84 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.221686E+10 | 10343.75 | 20-FEB-16:23 | 25.10 | 14.37 | 0.215574E+09 | 347.85 | 24-FEB-14:00 | 26.40 | 17.38 |
March | 0.435823E+10 | 12102.99 | 12-MAR-15:52 | 31.30 | 19.90 | 0.277898E+09 | 347.86 | 29-MAR-09:00 | 26.40 | 19.31 |
April | 0.648876E+10 | 14572.49 | 23-APR-15:22 | 31.80 | 19.70 | 0.255252E+09 | 347.86 | 24-APR-09:09 | 28.52 | 20.32 |
May | 0.809423E+10 | 15102.39 | 28-MAY-16:31 | 41.90 | 19.53 | 0.277779E+09 | 347.86 | 01-MAY-09:09 | 41.90 | 19.53 |
June | 0.795487E+10 | 15355.07 | 11-JUN-16:11 | 43.30 | 23.15 | 0.276843E+09 | 347.85 | 07-JUN-09:09 | 43.30 | 23.15 |
July | 0.664687E+10 | 14388.98 | 02-JUL-16:32 | 40.33 | 26.50 | 0.257500E+09 | 347.84 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.617834E+10 | 13913.47 | 06-AUG-16:01 | 36.25 | 26.27 | 0.288552E+09 | 347.84 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.531487E+10 | 13778.38 | 24-SEP-15:22 | 34.95 | 25.05 | 0.255848E+09 | 347.85 | 27-SEP-09:09 | 28.62 | 20.79 |
October | 0.462974E+10 | 14410.44 | 09-OCT-14:21 | 32.75 | 19.69 | 0.261613E+09 | 347.86 | 10-OCT-09:20 | 26.23 | 20.33 |
November | 0.308590E+10 | 6124.94 | 05-NOV-15:32 | 28.27 | 17.66 | 0.246154E+09 | 347.85 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.178385E+10 | 3964.11 | 01-DEC-15:30 | 22.85 | 13.56 | 0.221107E+09 | 347.85 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.583074E+11 | 0.305739E+10 | ||||||||
Minimum of Months | 0.155483E+10 | 3532.60 | 20.95 | 11.21 | 0.215574E+09 | 347.84 | 20.95 | 11.21 | ||
Maximum of Months | 0.809423E+10 | 15355.07 | 43.30 | 26.50 | 0.288552E+09 | 347.86 | 43.30 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187314E+10 | 2189.36 | 26-JAN-14:10 | 22.35 | 13.84 | 0.369602E+09 | 549.49 | 13-JAN-14:39 | 22.35 | 13.84 |
February | 0.216387E+10 | 3505.21 | 24-FEB-15:00 | 26.40 | 17.38 | 0.357249E+09 | 549.49 | 24-FEB-10:20 | 26.40 | 17.38 |
March | 0.371534E+10 | 5137.00 | 13-MAR-15:20 | 32.77 | 18.67 | 0.447841E+09 | 549.50 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.569538E+10 | 8480.02 | 16-APR-16:42 | 38.47 | 22.85 | 0.403683E+09 | 549.50 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.831742E+10 | 13050.44 | 29-MAY-16:51 | 40.90 | 21.33 | 0.438601E+09 | 549.52 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.906529E+10 | 13362.87 | 11-JUN-16:51 | 43.10 | 23.03 | 0.437291E+09 | 549.50 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.902641E+10 | 13472.00 | 04-JUL-18:32 | 40.07 | 24.28 | 0.407002E+09 | 549.49 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.902268E+10 | 13046.61 | 06-AUG-13:22 | 35.60 | 26.34 | 0.456299E+09 | 549.50 | 21-AUG-13:09 | 29.57 | 27.56 |
September | 0.743084E+10 | 13224.40 | 24-SEP-15:51 | 34.80 | 25.26 | 0.405160E+09 | 549.49 | 11-SEP-13:09 | 34.80 | 25.26 |
October | 0.586086E+10 | 12935.56 | 01-OCT-15:21 | 35.75 | 20.04 | 0.419970E+09 | 549.50 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.345589E+10 | 4535.86 | 09-NOV-14:10 | 29.37 | 17.83 | 0.410409E+09 | 549.50 | 06-NOV-10:09 | 29.37 | 17.83 |
December | 0.217586E+10 | 2672.46 | 01-DEC-15:00 | 23.40 | 13.35 | 0.378242E+09 | 549.49 | 29-DEC-14:09 | 19.75 | 14.80 |
Annual Sum or Average | 0.678030E+11 | 0.493135E+10 | ||||||||
Minimum of Months | 0.187314E+10 | 2189.36 | 22.35 | 13.35 | 0.357249E+09 | 549.49 | 19.75 | 13.84 | ||
Maximum of Months | 0.906529E+10 | 13472.00 | 43.10 | 26.34 | 0.456299E+09 | 549.52 | 39.90 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163279E+10 | 2271.08 | 26-JAN-11:00 | 19.70 | 13.19 | 0.248798E+09 | 347.87 | 30-JAN-10:30 | 14.10 | 9.40 |
February | 0.208199E+10 | 3870.20 | 22-FEB-10:40 | 22.60 | 14.39 | 0.234264E+09 | 347.88 | 24-FEB-10:20 | 20.97 | 15.04 |
March | 0.374674E+10 | 8362.88 | 12-MAR-10:32 | 27.43 | 17.74 | 0.286205E+09 | 347.88 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.557461E+10 | 11096.28 | 16-APR-10:02 | 35.32 | 21.70 | 0.256152E+09 | 348.04 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.729161E+10 | 11304.88 | 29-MAY-09:32 | 35.10 | 21.77 | 0.277954E+09 | 347.99 | 26-MAY-09:00 | 35.10 | 21.77 |
June | 0.711424E+10 | 11649.30 | 11-JUN-10:11 | 37.37 | 25.15 | 0.276947E+09 | 350.18 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.668776E+10 | 11118.93 | 04-JUL-09:51 | 35.20 | 25.12 | 0.257737E+09 | 347.87 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.659320E+10 | 11133.55 | 06-AUG-09:22 | 31.65 | 24.82 | 0.288925E+09 | 347.87 | 21-AUG-13:39 | 29.17 | 27.62 |
September | 0.582356E+10 | 11081.92 | 24-SEP-10:32 | 32.10 | 25.28 | 0.256567E+09 | 347.87 | 11-SEP-13:09 | 32.10 | 25.28 |
October | 0.514735E+10 | 11236.96 | 01-OCT-10:02 | 30.08 | 19.42 | 0.266367E+09 | 347.88 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.326836E+10 | 4499.81 | 13-NOV-10:30 | 23.45 | 14.94 | 0.261790E+09 | 347.88 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.194364E+10 | 3014.96 | 01-DEC-10:30 | 19.25 | 11.77 | 0.248582E+09 | 347.88 | 27-DEC-10:20 | 17.47 | 12.54 |
Annual Sum or Average | 0.569059E+11 | 0.316029E+10 | ||||||||
Minimum of Months | 0.163279E+10 | 2271.08 | 19.25 | 11.77 | 0.234264E+09 | 347.87 | 14.10 | 9.40 | ||
Maximum of Months | 0.729161E+10 | 11649.30 | 37.37 | 25.28 | 0.288925E+09 | 350.18 | 39.75 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312154E+10 | 9384.09 | 08-JAN-14:13 | 22.50 | 13.35 | 0.385818E+09 | 549.51 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.406031E+10 | 14266.42 | 20-FEB-14:22 | 26.35 | 13.75 | 0.362054E+09 | 549.77 | 23-FEB-14:20 | 26.20 | 13.97 |
March | 0.711294E+10 | 13497.65 | 12-MAR-13:52 | 31.20 | 19.38 | 0.449277E+09 | 642.41 | 28-MAR-12:09 | 33.22 | 18.26 |
April | 0.950063E+10 | 14408.16 | 27-APR-16:50 | 39.30 | 18.95 | 0.411101E+09 | 729.75 | 27-APR-12:09 | 39.30 | 18.95 |
May | 0.120523E+11 | 15758.97 | 01-MAY-16:50 | 43.07 | 22.15 | 0.452346E+09 | 798.00 | 01-MAY-12:09 | 43.07 | 22.15 |
June | 0.123734E+11 | 16097.04 | 12-JUN-17:00 | 43.90 | 22.35 | 0.450238E+09 | 817.19 | 12-JUN-12:09 | 43.90 | 22.35 |
July | 0.114588E+11 | 14682.06 | 03-JUL-17:00 | 39.50 | 25.70 | 0.413826E+09 | 744.47 | 07-JUL-12:09 | 39.13 | 24.79 |
August | 0.119225E+11 | 13831.91 | 07-AUG-16:50 | 36.68 | 26.89 | 0.462174E+09 | 688.56 | 07-AUG-12:09 | 36.68 | 26.89 |
September | 0.107888E+11 | 14557.29 | 24-SEP-13:52 | 35.10 | 24.61 | 0.413372E+09 | 707.59 | 29-SEP-12:09 | 35.52 | 22.70 |
October | 0.109356E+11 | 15369.13 | 01-OCT-13:21 | 35.55 | 19.91 | 0.432782E+09 | 736.00 | 02-OCT-12:09 | 35.70 | 21.30 |
November | 0.822062E+10 | 15095.60 | 12-NOV-13:42 | 28.12 | 16.00 | 0.414437E+09 | 611.93 | 09-NOV-13:09 | 28.12 | 16.00 |
December | 0.409991E+10 | 11956.69 | 24-DEC-14:03 | 24.32 | 13.88 | 0.387652E+09 | 549.70 | 01-DEC-14:00 | 24.32 | 13.88 |
Annual Sum or Average | 0.105647E+12 | 0.503508E+10 | ||||||||
Minimum of Months | 0.312154E+10 | 9384.09 | 22.50 | 13.35 | 0.362054E+09 | 549.51 | 23.00 | 13.41 | ||
Maximum of Months | 0.123734E+11 | 16097.04 | 43.90 | 26.89 | 0.462174E+09 | 817.19 | 43.90 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172654E+10 | 2962.66 | 31-JAN-16:30 | 20.65 | 11.16 | 0.238361E+09 | 347.84 | 13-JAN-14:00 | 20.65 | 11.16 |
February | 0.204307E+10 | 6536.11 | 20-FEB-16:23 | 25.10 | 14.37 | 0.226876E+09 | 347.85 | 24-FEB-10:00 | 22.30 | 15.46 |
March | 0.364855E+10 | 8669.12 | 26-MAR-16:32 | 29.47 | 16.16 | 0.283975E+09 | 347.86 | 30-MAR-13:00 | 32.00 | 19.26 |
April | 0.544979E+10 | 11654.87 | 30-APR-16:12 | 37.57 | 18.06 | 0.256006E+09 | 347.85 | 21-APR-09:09 | 37.57 | 18.06 |
May | 0.707148E+10 | 11967.67 | 29-MAY-16:11 | 41.17 | 21.49 | 0.277867E+09 | 347.87 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.731735E+10 | 12186.64 | 11-JUN-16:11 | 43.30 | 23.15 | 0.276963E+09 | 347.85 | 20-JUN-13:09 | 33.57 | 27.49 |
July | 0.660872E+10 | 12086.60 | 09-JUL-15:22 | 36.35 | 27.39 | 0.257684E+09 | 347.85 | 13-JUL-13:09 | 34.20 | 27.70 |
August | 0.654506E+10 | 11575.33 | 06-AUG-16:01 | 36.25 | 26.27 | 0.288897E+09 | 347.85 | 21-AUG-13:39 | 29.17 | 27.62 |
September | 0.582150E+10 | 12335.03 | 24-SEP-15:51 | 34.80 | 25.26 | 0.256583E+09 | 347.85 | 11-SEP-13:09 | 34.80 | 25.26 |
October | 0.503329E+10 | 12343.90 | 01-OCT-15:21 | 35.75 | 20.04 | 0.266227E+09 | 347.86 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.327177E+10 | 10149.87 | 05-NOV-15:12 | 28.63 | 17.52 | 0.260358E+09 | 347.85 | 16-NOV-10:09 | 21.45 | 16.35 |
December | 0.202086E+10 | 3701.51 | 01-DEC-15:40 | 22.67 | 13.61 | 0.240650E+09 | 347.84 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.565580E+11 | 0.313045E+10 | ||||||||
Minimum of Months | 0.172654E+10 | 2962.66 | 20.65 | 11.16 | 0.226876E+09 | 347.84 | 20.65 | 11.16 | ||
Maximum of Months | 0.731735E+10 | 12343.90 | 43.30 | 27.39 | 0.288897E+09 | 347.87 | 39.90 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177271E+10 | 2547.86 | 26-JAN-14:40 | 21.90 | 13.73 | 0.366430E+09 | 549.49 | 13-JAN-14:09 | 21.90 | 13.73 |
February | 0.232212E+10 | 4142.07 | 23-FEB-14:30 | 26.10 | 14.00 | 0.359658E+09 | 549.50 | 24-FEB-10:09 | 20.63 | 14.93 |
March | 0.446383E+10 | 6080.22 | 13-MAR-15:20 | 32.77 | 18.67 | 0.450151E+09 | 549.50 | 29-MAR-09:09 | 24.57 | 18.84 |
April | 0.659930E+10 | 12605.00 | 16-APR-15:22 | 39.50 | 22.49 | 0.404465E+09 | 549.50 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.892785E+10 | 13560.37 | 28-MAY-16:31 | 41.90 | 19.53 | 0.438945E+09 | 549.49 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.904608E+10 | 13607.27 | 04-JUN-16:41 | 41.88 | 22.55 | 0.437411E+09 | 549.49 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.827141E+10 | 13460.46 | 04-JUL-16:42 | 39.87 | 24.34 | 0.406966E+09 | 549.49 | 05-JUL-09:20 | 35.67 | 25.11 |
August | 0.786884E+10 | 10584.46 | 04-AUG-04:02 | 28.05 | 24.13 | 0.456100E+09 | 549.49 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.638115E+10 | 13554.52 | 24-SEP-15:51 | 34.80 | 25.26 | 0.404889E+09 | 549.49 | 08-SEP-13:00 | 34.80 | 25.26 |
October | 0.515054E+10 | 9480.76 | 01-OCT-15:31 | 35.67 | 20.08 | 0.418888E+09 | 549.50 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.318630E+10 | 4466.37 | 09-NOV-14:10 | 29.37 | 17.83 | 0.406065E+09 | 549.50 | 06-NOV-10:09 | 29.37 | 17.83 |
December | 0.201514E+10 | 2593.52 | 01-DEC-15:00 | 23.40 | 13.35 | 0.369842E+09 | 549.49 | 18-DEC-14:09 | 22.68 | 15.08 |
Annual Sum or Average | 0.660053E+11 | 0.491981E+10 | ||||||||
Minimum of Months | 0.177271E+10 | 2547.86 | 21.90 | 13.35 | 0.359658E+09 | 549.49 | 20.63 | 13.73 | ||
Maximum of Months | 0.904608E+10 | 13607.27 | 41.90 | 25.26 | 0.456100E+09 | 549.50 | 42.20 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158649E+10 | 2422.71 | 26-JAN-11:10 | 19.98 | 13.28 | 0.177507E+09 | 338.72 | 27-JAN-13:30 | 16.05 | 11.86 |
February | 0.219565E+10 | 4398.16 | 22-FEB-10:00 | 20.60 | 13.92 | 0.171051E+09 | 338.72 | 15-FEB-11:20 | 20.60 | 13.92 |
March | 0.418589E+10 | 7244.16 | 26-MAR-11:03 | 27.92 | 15.71 | 0.210857E+09 | 338.73 | 16-MAR-10:20 | 27.92 | 15.71 |
April | 0.606703E+10 | 11992.66 | 16-APR-10:02 | 35.32 | 21.70 | 0.189720E+09 | 339.19 | 14-APR-10:00 | 35.32 | 21.70 |
May | 0.753076E+10 | 12123.39 | 29-MAY-09:12 | 34.40 | 21.35 | 0.205750E+09 | 339.16 | 26-MAY-10:00 | 34.40 | 21.35 |
June | 0.696404E+10 | 11681.73 | 11-JUN-10:22 | 37.75 | 25.19 | 0.204674E+09 | 339.14 | 12-JUN-10:00 | 41.40 | 22.35 |
July | 0.606914E+10 | 12057.36 | 02-JUL-09:02 | 34.63 | 25.70 | 0.191072E+09 | 339.10 | 05-JUL-10:30 | 36.60 | 25.30 |
August | 0.569139E+10 | 10971.99 | 06-AUG-12:13 | 34.77 | 26.29 | 0.213308E+09 | 338.99 | 07-AUG-10:00 | 34.40 | 26.40 |
September | 0.498955E+10 | 11709.36 | 24-SEP-10:32 | 32.10 | 25.28 | 0.189702E+09 | 338.74 | 26-SEP-07:19 | 26.03 | 19.88 |
October | 0.448029E+10 | 11927.26 | 01-OCT-10:12 | 30.47 | 19.50 | 0.196365E+09 | 338.74 | 10-OCT-07:19 | 21.97 | 18.94 |
November | 0.293224E+10 | 4414.22 | 09-NOV-10:00 | 24.50 | 17.90 | 0.191227E+09 | 338.73 | 16-NOV-11:09 | 24.57 | 17.22 |
December | 0.177239E+10 | 2992.32 | 01-DEC-10:00 | 18.30 | 11.37 | 0.177469E+09 | 338.72 | 18-DEC-11:20 | 22.00 | 14.81 |
Annual Sum or Average | 0.544649E+11 | 0.231870E+10 | ||||||||
Minimum of Months | 0.158649E+10 | 2422.71 | 18.30 | 11.37 | 0.171051E+09 | 338.72 | 16.05 | 11.86 | ||
Maximum of Months | 0.753076E+10 | 12123.39 | 37.75 | 26.29 | 0.213308E+09 | 339.19 | 41.40 | 26.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414592E+10 | 9303.59 | 08-JAN-14:13 | 22.50 | 13.35 | 0.399423E+09 | 549.58 | 12-JAN-14:09 | 23.35 | 14.02 |
February | 0.483901E+10 | 14478.02 | 20-FEB-12:32 | 25.43 | 13.32 | 0.371001E+09 | 549.71 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.737016E+10 | 14472.73 | 26-MAR-13:02 | 29.87 | 16.43 | 0.452461E+09 | 551.01 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.831744E+10 | 14215.51 | 16-APR-13:22 | 39.30 | 21.89 | 0.404877E+09 | 549.69 | 06-APR-13:00 | 39.30 | 21.89 |
May | 0.931539E+10 | 13892.89 | 29-MAY-15:12 | 41.30 | 21.81 | 0.438958E+09 | 549.68 | 18-MAY-13:00 | 41.30 | 21.81 |
June | 0.898424E+10 | 13793.89 | 11-JUN-15:42 | 43.37 | 23.26 | 0.437385E+09 | 549.71 | 06-JUN-13:30 | 43.37 | 23.26 |
July | 0.833863E+10 | 13820.41 | 30-JUL-13:02 | 33.57 | 26.57 | 0.406954E+09 | 549.63 | 10-JUL-13:30 | 33.57 | 26.57 |
August | 0.832430E+10 | 13943.76 | 06-AUG-12:13 | 34.77 | 26.29 | 0.456171E+09 | 549.61 | 07-AUG-13:50 | 37.08 | 26.29 |
September | 0.793694E+10 | 15001.63 | 24-SEP-13:52 | 35.10 | 24.61 | 0.405194E+09 | 558.83 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.897816E+10 | 15498.07 | 15-OCT-12:12 | 32.30 | 18.51 | 0.421602E+09 | 588.23 | 02-OCT-13:39 | 32.30 | 18.51 |
November | 0.761588E+10 | 15699.19 | 12-NOV-13:12 | 27.87 | 16.14 | 0.413128E+09 | 559.34 | 01-NOV-13:39 | 27.87 | 16.14 |
December | 0.483082E+10 | 14411.50 | 03-DEC-13:23 | 24.25 | 14.17 | 0.393003E+09 | 549.69 | 01-DEC-14:00 | 24.25 | 14.17 |
Annual Sum or Average | 0.889969E+11 | 0.500016E+10 | ||||||||
Minimum of Months | 0.414592E+10 | 9303.59 | 22.50 | 13.32 | 0.371001E+09 | 549.58 | 23.35 | 14.02 | ||
Maximum of Months | 0.931539E+10 | 15699.19 | 43.37 | 26.57 | 0.456171E+09 | 588.23 | 43.37 | 26.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174023E+10 | 3546.84 | 31-JAN-16:10 | 20.95 | 11.21 | 0.232495E+09 | 347.84 | 25-JAN-14:00 | 20.95 | 11.21 |
February | 0.225663E+10 | 5221.91 | 21-FEB-16:10 | 25.98 | 15.67 | 0.224636E+09 | 347.85 | 24-FEB-10:00 | 22.30 | 15.46 |
March | 0.419504E+10 | 11177.26 | 26-MAR-15:02 | 30.33 | 16.74 | 0.283603E+09 | 347.86 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.603378E+10 | 13174.34 | 02-APR-16:41 | 33.57 | 20.57 | 0.256045E+09 | 347.86 | 21-APR-09:09 | 27.48 | 18.82 |
May | 0.741614E+10 | 13103.97 | 28-MAY-16:31 | 41.90 | 19.53 | 0.277860E+09 | 347.85 | 31-MAY-13:00 | 39.90 | 22.41 |
June | 0.724902E+10 | 12972.58 | 04-JUN-16:01 | 42.22 | 22.27 | 0.276885E+09 | 347.85 | 05-JUN-13:09 | 42.20 | 22.45 |
July | 0.607507E+10 | 13051.10 | 02-JUL-16:22 | 40.35 | 26.46 | 0.257547E+09 | 347.85 | 05-JUL-09:20 | 35.67 | 25.11 |
August | 0.573969E+10 | 12234.81 | 06-AUG-16:12 | 36.20 | 26.31 | 0.288647E+09 | 347.84 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.506308E+10 | 13216.64 | 24-SEP-15:51 | 34.80 | 25.26 | 0.256233E+09 | 347.84 | 08-SEP-13:00 | 34.80 | 25.26 |
October | 0.447540E+10 | 12872.55 | 15-OCT-15:32 | 32.27 | 19.28 | 0.264719E+09 | 347.85 | 30-OCT-09:09 | 21.27 | 16.75 |
November | 0.309817E+10 | 11499.96 | 05-NOV-15:22 | 28.45 | 17.59 | 0.254956E+09 | 347.86 | 06-NOV-10:09 | 23.13 | 17.24 |
December | 0.197207E+10 | 3973.02 | 01-DEC-15:30 | 22.85 | 13.56 | 0.232082E+09 | 347.85 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.553143E+11 | 0.310571E+10 | ||||||||
Minimum of Months | 0.174023E+10 | 3546.84 | 20.95 | 11.21 | 0.224636E+09 | 347.84 | 20.95 | 11.21 | ||
Maximum of Months | 0.741614E+10 | 13216.64 | 42.22 | 26.46 | 0.288647E+09 | 347.86 | 42.20 | 27.65 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126199E+10 | 11719.20 | 02-JAN-06:23 | 6.55 |
February | 0.662671E+09 | 4793.03 | 02-FEB-06:03 | 6.92 |
March | 0.320327E+09 | 3867.36 | 01-MAR-06:03 | 13.67 |
April | 66986371.19 | 6598.19 | 17-APR-04:02 | 24.68 |
May | 24888005.05 | 5645.68 | 15-MAY-04:02 | 24.27 |
June | 12893754.74 | 5251.75 | 19-JUN-04:02 | 27.82 |
July | 11126173.20 | 3523.11 | 19-JUL-05:03 | 26.00 |
August | 13936986.59 | 5019.14 | 21-AUG-04:02 | 25.67 |
September | 22244093.35 | 5750.42 | 25-SEP-04:02 | 26.32 |
October | 0.194953E+09 | 4925.08 | 04-OCT-05:03 | 25.07 |
November | 0.527328E+09 | 4418.03 | 24-NOV-06:03 | 10.50 |
December | 0.100690E+10 | 5636.98 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.412624E+10 | |||
Minimum of Months | 11126173.20 | 3523.11 | 6.25 | |
Maximum of Months | 0.126199E+10 | 11719.20 | 27.82 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597340E+09 | 3798.08 | 08-JAN-14:13 | 22.50 |
February | 0.121071E+09 | 3694.93 | 05-FEB-13:33 | 23.07 |
March | 15982386.25 | 2866.85 | 26-MAR-15:02 | 30.33 |
April | 16504244.97 | 2583.80 | 28-APR-04:02 | 27.93 |
May | 20487618.45 | 3001.60 | 18-MAY-04:02 | 30.20 |
June | 20754497.06 | 3045.95 | 22-JUN-04:02 | 30.28 |
July | 21996473.85 | 3328.79 | 14-JUL-04:02 | 29.58 |
August | 16559129.40 | 3212.16 | 09-AUG-04:02 | 30.32 |
September | 17074224.99 | 2592.50 | 11-SEP-04:02 | 25.87 |
October | 22585301.64 | 2772.15 | 01-OCT-14:11 | 35.93 |
November | 38530222.99 | 3525.59 | 26-NOV-11:32 | 24.67 |
December | 0.272611E+09 | 4667.18 | 24-DEC-13:43 | 24.00 |
Annual Sum or Average | 0.118150E+10 | |||
Minimum of Months | 15982386.25 | 2583.80 | 22.50 | |
Maximum of Months | 0.597340E+09 | 4667.18 | 35.93 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182265E+09 | 2901.08 | 08-JAN-14:13 | 22.50 |
February | 23809682.97 | 2614.52 | 05-FEB-11:43 | 20.35 |
March | 17809545.07 | 2292.08 | 11-MAR-05:03 | 23.97 |
April | 18116131.64 | 3054.29 | 27-APR-04:02 | 29.08 |
May | 26108432.74 | 3674.78 | 18-MAY-04:02 | 30.20 |
June | 32870279.69 | 4200.86 | 22-JUN-04:02 | 30.28 |
July | 42665232.71 | 4659.68 | 12-JUL-04:02 | 29.25 |
August | 35848715.91 | 4856.85 | 31-AUG-04:02 | 28.85 |
September | 35179062.51 | 4612.77 | 12-SEP-04:02 | 26.75 |
October | 36707940.42 | 4145.50 | 11-OCT-04:02 | 24.15 |
November | 41057993.43 | 2663.85 | 26-NOV-09:43 | 21.00 |
December | 58102169.03 | 3426.30 | 24-DEC-13:23 | 23.40 |
Annual Sum or Average | 0.550541E+09 | |||
Minimum of Months | 17809545.07 | 2292.08 | 20.35 | |
Maximum of Months | 0.182265E+09 | 4856.85 | 30.28 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3452981.20 | 18852.21 | 02-JAN-07:01 | 6.78 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 3452981.20 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 3452981.20 | 18852.21 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111207E+09 | 22731.99 | 02-JAN-06:11 | 6.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 4634011.75 | 17746.08 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.115841E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 0.111207E+09 | 22731.99 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339850E+09 | 10237.29 | 02-JAN-06:11 | 6.50 |
February | 51607437.53 | 8649.41 | 13-FEB-07:03 | 10.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 4997580.79 | 8330.89 | 27-NOV-07:02 | 10.02 |
December | 0.122107E+09 | 8845.54 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.518562E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.339850E+09 | 10237.29 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142448E+09 | 6563.70 | 02-JAN-06:11 | 6.50 |
February | 19635308.11 | 5633.15 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 2664944.46 | 5487.91 | 27-NOV-07:02 | 10.02 |
December | 51418130.81 | 5707.98 | 21-DEC-06:12 | 5.33 |
Annual Sum or Average | 0.216166E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.33 | |
Maximum of Months | 0.142448E+09 | 6563.70 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194203E+09 | 10012.49 | 02-JAN-06:11 | 6.50 |
February | 27711454.70 | 8582.58 | 04-FEB-07:03 | 8.40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 1575715.29 | 5658.54 | 27-NOV-07:02 | 10.02 |
December | 61887720.12 | 8637.01 | 23-DEC-06:12 | 5.57 |
Annual Sum or Average | 0.285378E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 0.194203E+09 | 10012.49 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210028E+09 | 6472.07 | 02-JAN-06:11 | 6.50 |
February | 34860066.57 | 5597.62 | 04-FEB-07:03 | 8.40 |
March | 88218.58 | 588.12 | 01-MAR-07:03 | 14.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 3787327.44 | 5481.33 | 27-NOV-07:02 | 10.02 |
December | 78538691.80 | 5740.63 | 21-DEC-06:12 | 5.33 |
Annual Sum or Average | 0.327302E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.33 | |
Maximum of Months | 0.210028E+09 | 6472.07 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18785071.16 | 5663.14 | 04-JAN-07:03 | 5.50 |
February | 95288.44 | 706.55 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 142953.97 | 953.03 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 19023313.57 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 18785071.16 | 5663.14 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4907376.90 | 3766.27 | 02-JAN-06:11 | 6.50 |
February | 95666.97 | 637.78 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 5003043.87 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 4907376.90 | 3766.27 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482516E+09 | 6873.02 | 03-JAN-07:10 | 5.50 |
February | 0.318917E+09 | 6257.26 | 02-FEB-07:10 | 7.12 |
March | 65435178.34 | 5621.01 | 20-MAR-06:06 | 14.88 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 81179412.34 | 5551.64 | 30-NOV-07:05 | 13.90 |
December | 0.361506E+09 | 6338.92 | 21-DEC-07:10 | 5.68 |
Annual Sum or Average | 0.130955E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 0.482516E+09 | 6873.02 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7710615.02 | 3514.57 | 02-JAN-07:03 | 6.78 |
February | 232238.32 | 1034.75 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 69881.37 | 465.88 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 8012734.71 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 7710615.02 | 3514.57 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59850879.82 | 7194.95 | 02-JAN-06:11 | 6.50 |
February | 2397308.24 | 4756.99 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 5614716.73 | 6338.78 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 67862904.79 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 59850879.82 | 7194.95 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28075037.32 | 4519.18 | 02-JAN-06:11 | 6.50 |
February | 2471444.51 | 4424.98 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 3676504.90 | 4319.28 | 20-DEC-07:02 | 7.70 |
Annual Sum or Average | 34222986.74 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 28075037.32 | 4519.18 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30093925.38 | 6982.35 | 02-JAN-06:11 | 6.50 |
February | 956261.66 | 3433.59 | 11-FEB-07:03 | 9.97 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 1989634.39 | 6466.70 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 33039821.43 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 30093925.38 | 6982.35 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38949474.89 | 4440.23 | 02-JAN-06:11 | 6.50 |
February | 2851855.10 | 4326.89 | 02-FEB-07:02 | 7.12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 5252872.89 | 4295.68 | 20-DEC-07:02 | 7.70 |
Annual Sum or Average | 47054202.88 | |||
Minimum of Months | 0.00 | 0.00 | 6.50 | |
Maximum of Months | 38949474.89 | 4440.23 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.783470E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.687680E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773316E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.669866E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708885E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.708060E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.680015E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.766573E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.695482E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.743205E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.766480E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771400E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.875443E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.669866E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.783470E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484724E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.429787E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485628E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423888E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451637E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450864E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430719E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.484528E+09 | 750.07 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438298E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463349E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479239E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.476547E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549921E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423888E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485628E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738184E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664162E+09 | 1184.79 | 09-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764877E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671962E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.716769E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.715935E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.686041E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.769109E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.691699E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.725575E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.729400E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720873E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.859459E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664162E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.769109E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.480572E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425690E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489316E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426774E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453912E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.453132E+09 | 600.10 | 19-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.435553E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.490544E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.442410E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.469748E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.469596E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466855E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550410E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.425690E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490544E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.779795E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.684667E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.771302E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668943E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707953E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.706913E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.678033E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.764651E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.693547E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740540E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.762787E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.766472E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.872560E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.668943E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.779795E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.482516E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.428590E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.484757E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423282E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451166E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450398E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429605E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.483349E+09 | 750.07 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437574E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.462264E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477851E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475378E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548673E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423282E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.484757E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737320E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.662861E+09 | 1184.79 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763282E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671005E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.715590E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.714437E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.684406E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.767023E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.690078E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.724688E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.727700E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.719206E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.857759E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.662861E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.767023E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478392E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424406E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488324E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425602E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453193E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452267E+09 | 600.10 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.434503E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.489238E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.441325E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468945E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468281E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.465251E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548973E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.424406E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.489238E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.783470E+09 | 1184.79 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.687680E+09 | 1184.79 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773316E+09 | 1184.79 | 14-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.669866E+09 | 711.15 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708885E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.708060E+09 | 947.97 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.679994E+09 | 1184.79 | 18-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.766573E+09 | 1184.79 | 11-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.695378E+09 | 1184.79 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.743205E+09 | 1358.45 | 11-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.766480E+09 | 1358.45 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771400E+09 | 1358.45 | 29-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.875431E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.669866E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.783470E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.484724E+09 | 750.07 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.429787E+09 | 750.07 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485628E+09 | 710.08 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423888E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451637E+09 | 490.21 | 24-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.450864E+09 | 490.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430697E+09 | 750.07 | 18-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.484528E+09 | 750.07 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438298E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463349E+09 | 860.01 | 11-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479239E+09 | 860.01 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.476547E+09 | 860.01 | 26-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.549919E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.423888E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485628E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738184E+09 | 1184.79 | 18-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664162E+09 | 1184.79 | 09-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764877E+09 | 1184.79 | 14-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671962E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.716767E+09 | 947.97 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.715935E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.686041E+09 | 1184.79 | 18-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.769088E+09 | 1184.79 | 11-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.691699E+09 | 1184.79 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.725575E+09 | 1358.45 | 11-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.729400E+09 | 1184.79 | 27-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.720873E+09 | 1184.79 | 26-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.859456E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664162E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.769088E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.480572E+09 | 750.02 | 18-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425690E+09 | 750.02 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489316E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426774E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453912E+09 | 600.10 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.453132E+09 | 600.10 | 19-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.435553E+09 | 750.02 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.490544E+09 | 750.02 | 11-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.442410E+09 | 750.02 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.469748E+09 | 859.95 | 11-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.469596E+09 | 750.02 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.466855E+09 | 750.02 | 26-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550410E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.425690E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490544E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.783470E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46096.18 | 38934859.90 |
February | 0.901968E+09 | 0.687680E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1309846.70 | 43339459.25 |
March | 0.107774E+10 | 0.773316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10473518.63 | 29056425.12 |
April | 0.956342E+09 | 0.669866E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39940880.58 | 2557671.87 |
May | 0.103597E+10 | 0.708885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84349704.33 | 997473.72 |
June | 0.103308E+10 | 0.708060E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57016239.83 | 545827.17 |
July | 0.959235E+09 | 0.680015E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70652455.33 | 218118.70 |
August | 0.107774E+10 | 0.766573E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39829000.68 | 418038.84 |
September | 0.956342E+09 | 0.695482E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23786135.68 | 758554.91 |
October | 0.994195E+09 | 0.743205E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13224310.50 | 2360023.29 |
November | 0.984487E+09 | 0.766480E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3383560.75 | 8824448.95 |
December | 0.959235E+09 | 0.771400E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 440901.20 | 35480127.47 |
Annual Sum or Average | 0.119305E+11 | 0.875443E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344453E+09 | 0.163491E+09 |
Minimum of Months | 0.901968E+09 | 0.669866E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46096.18 | 218118.70 |
Maximum of Months | 0.107774E+10 | 0.783470E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84349704.33 | 43339459.25 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.484724E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6722.96 | 27479960.48 |
February | 0.571020E+09 | 0.429787E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519950.70 | 30994088.31 |
March | 0.682301E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6284830.72 | 20324358.25 |
April | 0.605444E+09 | 0.423888E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25753603.98 | 1897978.91 |
May | 0.655854E+09 | 0.451637E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55749051.63 | 682127.42 |
June | 0.654023E+09 | 0.450864E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37995645.94 | 369947.43 |
July | 0.607275E+09 | 0.430719E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47101906.92 | 144788.69 |
August | 0.682301E+09 | 0.484528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26435219.95 | 278805.11 |
September | 0.605444E+09 | 0.438298E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15789127.42 | 494342.82 |
October | 0.629407E+09 | 0.463349E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8232390.61 | 1711904.51 |
November | 0.623262E+09 | 0.479239E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1857187.89 | 6500632.24 |
December | 0.607275E+09 | 0.476547E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 149964.25 | 25343519.40 |
Annual Sum or Average | 0.755301E+10 | 0.549921E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225876E+09 | 0.116222E+09 |
Minimum of Months | 0.571020E+09 | 0.423888E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6722.96 | 144788.69 |
Maximum of Months | 0.682301E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55749051.63 | 30994088.31 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46315631.97 |
February | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 481415.04 | 51124891.12 |
March | 0.107774E+10 | 0.764877E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8781708.78 | 31939677.13 |
April | 0.956342E+09 | 0.671962E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38892428.09 | 2730227.21 |
May | 0.103597E+10 | 0.716769E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84361669.71 | 1012745.70 |
June | 0.103308E+10 | 0.715935E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57108195.90 | 534905.75 |
July | 0.959235E+09 | 0.686041E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70708563.73 | 217475.50 |
August | 0.107774E+10 | 0.769109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39643186.77 | 423596.52 |
September | 0.956342E+09 | 0.691699E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23292182.08 | 786463.21 |
October | 0.994195E+09 | 0.725575E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11734050.45 | 2648385.51 |
November | 0.984487E+09 | 0.729400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121625.73 | 11003014.23 |
December | 0.959235E+09 | 0.720873E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8642.17 | 43653058.26 |
Annual Sum or Average | 0.119305E+11 | 0.859459E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337134E+09 | 0.192390E+09 |
Minimum of Months | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217475.50 |
Maximum of Months | 0.107774E+10 | 0.769109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84361669.71 | 51124891.12 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.480572E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1989.98 | 27317834.92 |
February | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 507737.90 | 30293992.15 |
March | 0.682256E+09 | 0.489316E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6402501.62 | 20707523.39 |
April | 0.605404E+09 | 0.426774E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26264834.13 | 1882514.35 |
May | 0.655811E+09 | 0.453912E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56096439.04 | 721464.74 |
June | 0.653980E+09 | 0.453132E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37940480.10 | 392186.00 |
July | 0.607235E+09 | 0.435553E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47257022.68 | 142970.93 |
August | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26541073.84 | 279974.01 |
September | 0.605404E+09 | 0.442410E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15787270.35 | 497488.35 |
October | 0.629366E+09 | 0.469748E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8533431.64 | 1579843.41 |
November | 0.623221E+09 | 0.469596E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1949934.22 | 6052858.84 |
December | 0.607235E+09 | 0.466855E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150576.00 | 24691259.60 |
Annual Sum or Average | 0.755252E+10 | 0.550410E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227433E+09 | 0.114560E+09 |
Minimum of Months | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1989.98 | 142970.93 |
Maximum of Months | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56096439.04 | 30293992.15 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.779795E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8638.52 | 24423953.11 |
February | 0.901968E+09 | 0.684667E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 694175.40 | 25507682.17 |
March | 0.107774E+10 | 0.771302E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6062656.07 | 15740358.27 |
April | 0.956342E+09 | 0.668943E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22391304.52 | 1253217.42 |
May | 0.103597E+10 | 0.707953E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46098787.54 | 413922.83 |
June | 0.103308E+10 | 0.706913E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30814489.39 | 281857.99 |
July | 0.959235E+09 | 0.678033E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37846716.17 | 142940.19 |
August | 0.107774E+10 | 0.764651E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21222825.73 | 261587.42 |
September | 0.956342E+09 | 0.693547E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12592291.28 | 556701.92 |
October | 0.994195E+09 | 0.740540E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7026502.73 | 1546026.09 |
November | 0.984487E+09 | 0.762787E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1633777.89 | 5717607.31 |
December | 0.959235E+09 | 0.766472E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122003.22 | 22761444.36 |
Annual Sum or Average | 0.119305E+11 | 0.872560E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186514E+09 | 98607299.07 |
Minimum of Months | 0.901968E+09 | 0.668943E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8638.52 | 142940.19 |
Maximum of Months | 0.107774E+10 | 0.779795E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46098787.54 | 25507682.17 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.482516E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17335319.93 |
February | 0.571020E+09 | 0.428590E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266717.62 | 18391428.08 |
March | 0.682301E+09 | 0.484757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3570952.35 | 11378449.35 |
April | 0.605444E+09 | 0.423282E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14074872.88 | 1012379.42 |
May | 0.655854E+09 | 0.451166E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29961944.53 | 323791.49 |
June | 0.654023E+09 | 0.450398E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20359740.31 | 204471.94 |
July | 0.607275E+09 | 0.429605E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25073626.53 | 101044.01 |
August | 0.682301E+09 | 0.483349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14009635.52 | 181747.84 |
September | 0.605444E+09 | 0.437574E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8312030.32 | 377679.32 |
October | 0.629407E+09 | 0.462264E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4421197.77 | 1128419.29 |
November | 0.623262E+09 | 0.477851E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 924389.25 | 4135687.52 |
December | 0.607275E+09 | 0.475378E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29271.68 | 16096907.81 |
Annual Sum or Average | 0.755301E+10 | 0.548673E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121004E+09 | 70667326.01 |
Minimum of Months | 0.571020E+09 | 0.423282E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101044.01 |
Maximum of Months | 0.682301E+09 | 0.484757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29961944.53 | 18391428.08 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737320E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274472E+10 |
February | 0.901968E+09 | 0.662861E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63698189.95 | 0.156640E+10 |
March | 0.107774E+10 | 0.763282E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894816E+09 | 0.711956E+09 |
April | 0.956342E+09 | 0.671005E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239065E+10 | 95031733.37 |
May | 0.103597E+10 | 0.715590E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386350E+10 | 793693.54 |
June | 0.103308E+10 | 0.714437E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392315E+10 | 359405.32 |
July | 0.959235E+09 | 0.684406E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268635E+10 | 151559.05 |
August | 0.107774E+10 | 0.767023E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265676E+10 | 610488.88 |
September | 0.956342E+09 | 0.690078E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195879E+10 | 3737154.06 |
October | 0.994195E+09 | 0.724688E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136972E+10 | 0.318526E+09 |
November | 0.984487E+09 | 0.727700E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436706E+09 | 0.999644E+09 |
December | 0.959235E+09 | 0.719206E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 652412.83 | 0.235071E+10 |
Annual Sum or Average | 0.119305E+11 | 0.857759E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202448E+11 | 0.879264E+10 |
Minimum of Months | 0.901968E+09 | 0.662861E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151559.05 |
Maximum of Months | 0.107774E+10 | 0.767023E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392315E+10 | 0.274472E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.478392E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17204224.36 |
February | 0.570983E+09 | 0.424406E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239139.21 | 18107727.65 |
March | 0.682256E+09 | 0.488324E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3502619.45 | 11713223.84 |
April | 0.605404E+09 | 0.425602E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14153762.56 | 1039163.67 |
May | 0.655811E+09 | 0.453193E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29924886.04 | 348786.35 |
June | 0.653980E+09 | 0.452267E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20162606.01 | 230932.96 |
July | 0.607235E+09 | 0.434503E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25012131.41 | 101595.20 |
August | 0.682256E+09 | 0.489238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13972261.68 | 182708.99 |
September | 0.605404E+09 | 0.441325E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8238881.87 | 396929.01 |
October | 0.629366E+09 | 0.468945E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4455864.10 | 1089953.66 |
November | 0.623221E+09 | 0.468281E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928258.64 | 4025223.89 |
December | 0.607235E+09 | 0.465251E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19583.23 | 15869147.93 |
Annual Sum or Average | 0.755252E+10 | 0.548973E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120610E+09 | 70309617.50 |
Minimum of Months | 0.570983E+09 | 0.424406E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101595.20 |
Maximum of Months | 0.682256E+09 | 0.489238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29924886.04 | 18107727.65 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.783470E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19530.74 | 36868561.26 |
February | 0.901968E+09 | 0.687680E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 946142.51 | 40260240.23 |
March | 0.107774E+10 | 0.773316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8790960.19 | 26378002.56 |
April | 0.956342E+09 | 0.669866E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33519044.43 | 2397680.55 |
May | 0.103597E+10 | 0.708885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70328795.60 | 872683.77 |
June | 0.103308E+10 | 0.708060E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47616298.32 | 448902.18 |
July | 0.959235E+09 | 0.679994E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59035496.19 | 185165.34 |
August | 0.107774E+10 | 0.766573E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33380610.96 | 349078.55 |
September | 0.956342E+09 | 0.695378E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19780473.29 | 701112.48 |
October | 0.994195E+09 | 0.743205E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11061972.70 | 2224616.17 |
November | 0.984487E+09 | 0.766480E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2631225.45 | 8442527.28 |
December | 0.959235E+09 | 0.771400E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250540.41 | 33616164.49 |
Annual Sum or Average | 0.119305E+11 | 0.875431E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287361E+09 | 0.152745E+09 |
Minimum of Months | 0.901968E+09 | 0.669866E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19530.74 | 185165.34 |
Maximum of Months | 0.107774E+10 | 0.783470E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70328795.60 | 40260240.23 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.484724E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.20 | 25515311.68 |
February | 0.421807E+09 | 0.429787E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 412109.91 | 28167197.14 |
March | 0.502994E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5360955.75 | 18165793.97 |
April | 0.447140E+09 | 0.423888E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21730884.51 | 1745853.39 |
May | 0.484071E+09 | 0.451637E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46618161.33 | 592238.23 |
June | 0.482240E+09 | 0.450864E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31793643.02 | 302477.45 |
July | 0.448971E+09 | 0.430697E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39438725.28 | 122819.96 |
August | 0.502994E+09 | 0.484528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22176871.63 | 231519.05 |
September | 0.447140E+09 | 0.438298E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13177132.99 | 452678.30 |
October | 0.465148E+09 | 0.463349E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6963338.34 | 1580999.76 |
November | 0.460569E+09 | 0.479239E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1503231.91 | 6017246.23 |
December | 0.448971E+09 | 0.476547E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84430.61 | 23486837.72 |
Annual Sum or Average | 0.557719E+10 | 0.549919E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189261E+09 | 0.106381E+09 |
Minimum of Months | 0.421807E+09 | 0.423888E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.20 | 122819.96 |
Maximum of Months | 0.502994E+09 | 0.485628E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46618161.33 | 28167197.14 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.738184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42183558.90 |
February | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409804.14 | 46137430.78 |
March | 0.107774E+10 | 0.764877E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7369056.42 | 28639934.33 |
April | 0.956342E+09 | 0.671962E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32490520.07 | 2534905.77 |
May | 0.103597E+10 | 0.716767E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70326981.10 | 885144.98 |
June | 0.103308E+10 | 0.715935E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47698258.67 | 438574.87 |
July | 0.959235E+09 | 0.686041E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59088770.41 | 184829.11 |
August | 0.107774E+10 | 0.769088E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33194823.63 | 353700.92 |
September | 0.956342E+09 | 0.691699E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19366055.68 | 724331.35 |
October | 0.994195E+09 | 0.725575E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9794950.71 | 2450807.89 |
November | 0.984487E+09 | 0.729400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1769390.78 | 10052129.53 |
December | 0.959235E+09 | 0.720873E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7707.04 | 39724968.61 |
Annual Sum or Average | 0.119305E+11 | 0.859456E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281516E+09 | 0.174310E+09 |
Minimum of Months | 0.901968E+09 | 0.664162E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184829.11 |
Maximum of Months | 0.107774E+10 | 0.769088E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70326981.10 | 46137430.78 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.480572E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25444440.07 |
February | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358366.14 | 27862705.28 |
March | 0.682256E+09 | 0.489316E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5315883.18 | 18708440.94 |
April | 0.605404E+09 | 0.426774E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21911002.51 | 1747424.52 |
May | 0.655811E+09 | 0.453912E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46667701.51 | 633016.36 |
June | 0.653980E+09 | 0.453132E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31604140.12 | 324815.69 |
July | 0.607235E+09 | 0.435553E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39395702.59 | 122285.45 |
August | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22189726.52 | 234199.13 |
September | 0.605404E+09 | 0.442410E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13084566.16 | 462682.79 |
October | 0.629366E+09 | 0.469748E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7094888.03 | 1495063.47 |
November | 0.623221E+09 | 0.469596E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1531839.71 | 5762019.62 |
December | 0.607235E+09 | 0.466855E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64250.31 | 23070174.05 |
Annual Sum or Average | 0.755252E+10 | 0.550410E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189218E+09 | 0.105867E+09 |
Minimum of Months | 0.570983E+09 | 0.425690E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122285.45 |
Maximum of Months | 0.682256E+09 | 0.490544E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46667701.51 | 27862705.28 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56385504.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356683.02 | 60728073.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8870496.42 | 38538023.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39168530.32 | 3313135.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86849855.66 | 1064565.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58791765.09 | 551395.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73583031.32 | 238392.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40528466.30 | 396663.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22858300.89 | 760738.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11774160.87 | 3363379.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014293.83 | 13202950.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16180.18 | 51804192.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344812E+09 | 0.230347E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238392.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86849855.66 | 60728073.58 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.75 | 65076992.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 761529.43 | 72453133.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11925424.06 | 47706272.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50890279.11 | 4143102.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111852E+09 | 1411172.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76204887.25 | 723200.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95388772.91 | 276919.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52825913.49 | 473154.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30194622.87 | 803869.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15917257.34 | 4034489.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3145637.41 | 15564259.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238513.86 | 60470952.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449346E+09 | 0.273138E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.75 | 276919.03 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111852E+09 | 72453133.01 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64247199.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81864.34 | 71512939.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8731334.13 | 42977094.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49230058.67 | 2983407.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117079E+09 | 1028835.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79730057.82 | 631906.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97949216.30 | 219773.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53962291.44 | 606611.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30261998.93 | 569838.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13888242.13 | 3092594.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1673929.18 | 14122456.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5012.21 | 57629457.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452593E+09 | 0.259622E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219773.04 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117079E+09 | 71512939.38 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 08-JAN-15:00 | 104.16 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 | 19-FEB-14:55 | 146.88 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.69 | 26-MAR-14:53 | 317.51 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.20 | 15-APR-17:10 | 44.16 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.83 | 28-MAY-13:54 | 32.97 | 15-MAY-02:53 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.02 | 17-JUN-20:50 | 27.02 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.76 | 02-JUL-11:56 | 21.81 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.56 | 06-AUG-14:06 | 27.47 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.03 | 24-SEP-14:46 | 10.93 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.68 | 15-OCT-12:10 | 43.59 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 | 12-NOV-14:10 | 69.43 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 24-DEC-14:10 | 164.00 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 | 10.93 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 346.83 | 317.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 08-JAN-15:00 | 68.70 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 19-FEB-14:53 | 95.80 | 09-FEB-22:10 |
March | 827.22 | 01-MAR-10:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 | 26-MAR-14:53 | 215.48 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 15-APR-17:10 | 32.02 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.23 | 28-MAY-13:54 | 22.71 | 15-MAY-02:53 |
June | 827.22 | 01-JUN-09:09 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 17-JUN-20:50 | 17.83 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.67 | 02-JUL-11:54 | 14.41 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.89 | 06-AUG-14:06 | 18.45 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.74 | 24-SEP-14:46 | 7.00 | 08-SEP-22:20 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 15-OCT-13:08 | 28.77 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 12-NOV-14:10 | 46.48 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 24-DEC-14:10 | 108.25 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 7.00 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 232.23 | 215.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 138.85 | 22-JAN-13:53 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 | 21-FEB-15:00 | 147.39 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 26-MAR-14:45 | 337.69 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.41 | 15-APR-17:10 | 47.18 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.04 | 28-MAY-14:55 | 33.73 | 15-MAY-02:53 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.43 | 17-JUN-20:50 | 26.81 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.10 | 02-JUL-11:56 | 21.76 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.16 | 06-AUG-14:04 | 27.65 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.63 | 24-SEP-14:44 | 11.03 | 08-SEP-22:20 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 | 15-OCT-12:50 | 44.00 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 12-NOV-14:45 | 74.60 | 29-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 28-DEC-14:00 | 226.42 | 31-DEC-14:23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 345.04 | 337.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 08-JAN-14:03 | 69.50 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 19-FEB-13:32 | 95.64 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 | 26-MAR-12:53 | 225.11 | 24-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.19 | 15-APR-17:08 | 30.08 | 22-APR-18:20 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.02 | 28-MAY-15:00 | 23.80 | 15-MAY-02:53 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 19-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.34 | 17-JUN-20:50 | 18.73 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.94 | 02-JUL-11:56 | 14.32 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 | 06-AUG-08:50 | 18.60 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.05 | 24-SEP-14:04 | 7.21 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.35 | 15-OCT-11:50 | 28.77 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 12-NOV-12:50 | 46.82 | 29-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 24-DEC-13:33 | 107.62 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 7.21 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 230.02 | 225.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 08-JAN-14:40 | 64.35 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 | 19-FEB-15:10 | 86.64 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 | 26-MAR-15:00 | 174.16 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.82 | 15-APR-17:02 | 25.11 | 22-APR-18:20 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.87 | 28-MAY-14:50 | 13.68 | 15-MAY-02:40 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 17-JUN-21:00 | 14.68 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.59 | 02-JUL-11:28 | 13.53 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 06-AUG-14:06 | 15.76 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.37 | 24-SEP-13:55 | 8.59 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.92 | 15-OCT-12:12 | 27.71 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.96 | 12-NOV-13:52 | 44.92 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | 24-DEC-14:20 | 102.98 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 8.59 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.87 | 174.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 43.34 | 15-JAN-17:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.71 | 19-FEB-15:10 | 57.55 | 09-FEB-22:10 |
March | 827.22 | 01-MAR-10:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 | 26-MAR-15:00 | 123.34 | 24-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.88 | 15-APR-17:02 | 19.40 | 22-APR-18:10 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.66 | 28-MAY-14:35 | 10.95 | 15-MAY-02:40 |
June | 827.22 | 01-JUN-09:09 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 17-JUN-20:47 | 10.18 | 18-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 02-JUL-11:25 | 9.01 | 19-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 | 06-AUG-14:06 | 10.75 | 15-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 | 24-SEP-13:55 | 5.73 | 08-SEP-22:10 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 15-OCT-12:45 | 18.71 | 12-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 12-NOV-13:52 | 31.06 | 28-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 24-DEC-14:17 | 68.98 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 125.66 | 123.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18876.69 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2958.04 | 22-FEB-13:00 | 15975.57 | 02-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12435.47 | 28-MAR-16:02 | 8945.98 | 01-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16973.68 | 27-APR-16:01 | 5016.11 | 10-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21374.59 | 03-MAY-16:01 | 115.44 | 15-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21620.24 | 08-JUN-16:01 | 97.60 | 27-JUN-11:10 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17085.69 | 07-JUL-16:01 | 13.59 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14016.38 | 07-AUG-16:01 | 101.70 | 16-AUG-05:03 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12437.92 | 26-SEP-16:02 | 564.91 | 27-SEP-05:03 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11646.88 | 02-OCT-16:02 | 9030.66 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4818.40 | 09-NOV-12:03 | 14361.15 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.72 | 28-DEC-14:00 | 18463.92 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21620.24 | 18876.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 43.67 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 19-FEB-14:02 | 57.46 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 26-MAR-12:53 | 128.92 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 15-APR-17:08 | 17.94 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.71 | 28-MAY-14:55 | 11.97 | 15-MAY-02:40 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.58 | 17-JUN-20:43 | 11.14 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 | 02-JUL-11:30 | 9.04 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 06-AUG-13:26 | 10.83 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 | 24-SEP-13:55 | 5.76 | 08-SEP-22:10 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 | 15-OCT-12:12 | 18.68 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 12-NOV-13:12 | 31.10 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 24-DEC-13:43 | 68.88 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 122.71 | 128.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 08-JAN-14:40 | 96.29 | 15-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.88 | 19-FEB-15:00 | 134.17 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.12 | 26-MAR-14:50 | 287.21 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.48 | 15-APR-17:02 | 42.35 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.71 | 28-MAY-14:33 | 28.79 | 15-MAY-02:53 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.70 | 17-JUN-21:00 | 22.78 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.45 | 02-JUL-11:45 | 19.32 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.95 | 06-AUG-14:18 | 22.40 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.21 | 24-SEP-13:55 | 10.59 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.81 | 15-OCT-12:00 | 39.53 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 12-NOV-14:00 | 66.15 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 29-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 24-DEC-14:00 | 151.30 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 10.59 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 290.71 | 287.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 08-JAN-15:00 | 63.52 | 15-JAN-17:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 19-FEB-15:00 | 86.59 | 09-FEB-22:10 |
March | 805.43 | 01-MAR-08:09 | 710.08 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 26-MAR-14:50 | 193.84 | 24-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.05 | 15-APR-17:02 | 30.19 | 22-APR-18:10 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 | 28-MAY-14:35 | 19.74 | 15-MAY-02:53 |
June | 805.43 | 01-JUN-07:10 | 490.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.04 | 17-JUN-20:57 | 14.98 | 18-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 750.07 | 18-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.67 | 02-JUL-11:45 | 12.76 | 19-JUL-03:00 |
August | 805.43 | 01-AUG-07:10 | 750.07 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 | 06-AUG-14:18 | 15.04 | 15-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.81 | 24-SEP-13:55 | 6.81 | 08-SEP-22:20 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 | 15-OCT-12:15 | 26.07 | 12-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 12-NOV-14:00 | 44.06 | 28-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 26-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 | 24-DEC-13:57 | 99.58 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 6.81 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 | 193.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 18-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 117.13 | 22-JAN-13:53 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 09-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 21-FEB-15:00 | 134.55 | 09-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 14-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.19 | 26-MAR-14:25 | 302.88 | 24-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.24 | 15-APR-17:10 | 44.90 | 22-APR-18:10 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.70 | 28-MAY-14:55 | 29.42 | 15-MAY-02:53 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.95 | 17-JUN-21:00 | 22.56 | 18-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 1184.79 | 18-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.10 | 02-JUL-11:45 | 19.28 | 19-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 11-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 | 06-AUG-14:15 | 22.56 | 15-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 24-SEP-13:55 | 10.68 | 08-SEP-22:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 11-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.54 | 15-OCT-12:54 | 39.85 | 12-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 27-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | 12-NOV-14:35 | 69.13 | 28-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 26-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 28-DEC-14:00 | 192.45 | 31-DEC-14:33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 287.70 | 302.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 18-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 64.16 | 15-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 19-FEB-13:13 | 86.52 | 09-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 26-MAR-12:43 | 201.67 | 24-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.82 | 15-APR-17:08 | 28.86 | 22-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 28-MAY-14:55 | 20.78 | 15-MAY-02:53 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 19-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.06 | 17-JUN-21:00 | 15.88 | 18-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.63 | 02-JUL-11:47 | 12.73 | 19-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 11-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 | 06-AUG-09:00 | 15.18 | 15-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 24-SEP-13:55 | 6.92 | 19-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 11-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 | 15-OCT-12:00 | 26.13 | 12-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 12-NOV-12:52 | 44.34 | 28-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 26-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 24-DEC-13:53 | 99.39 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 201.67 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 139.10 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 19-FEB-14:53 | 201.94 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 | 26-MAR-15:00 | 424.01 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.41 | 15-APR-17:02 | 58.08 | 22-APR-18:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.44 | 28-MAY-15:00 | 32.04 | 15-MAY-04:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.43 | 17-JUN-21:00 | 30.95 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.05 | 02-JUL-11:50 | 24.66 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.46 | 06-AUG-13:52 | 26.01 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 | 24-SEP-14:20 | 13.12 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.05 | 15-OCT-12:30 | 54.10 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 12-NOV-14:00 | 98.79 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 24-DEC-14:00 | 221.98 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.44 | 424.01 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 08-JAN-14:55 | 162.45 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 19-FEB-14:53 | 248.56 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.86 | 26-MAR-14:53 | 531.69 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.38 | 15-APR-17:02 | 70.83 | 22-APR-18:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.76 | 28-MAY-15:00 | 44.96 | 15-MAY-04:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.37 | 03-JUN-17:02 | 40.02 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.71 | 02-JUL-12:00 | 29.98 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.21 | 06-AUG-14:00 | 32.37 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.75 | 24-SEP-14:20 | 16.42 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.01 | 15-OCT-12:00 | 65.41 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 12-NOV-13:42 | 117.71 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 24-DEC-14:20 | 268.61 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 16.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.76 | 531.69 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 161.36 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 24-FEB-16:00 | 235.16 | 09-FEB-22:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.77 | 26-MAR-15:00 | 438.26 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.22 | 15-APR-17:02 | 51.34 | 22-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.97 | 28-MAY-15:00 | 33.82 | 15-MAY-04:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.10 | 17-JUN-20:50 | 35.68 | 18-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.95 | 02-JUL-10:52 | 26.25 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.73 | 06-AUG-08:53 | 37.47 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.80 | 24-SEP-14:30 | 10.19 | 19-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 | 15-OCT-12:02 | 60.58 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 12-NOV-13:50 | 96.66 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 24-DEC-14:17 | 262.84 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.97 | 438.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 24861.51 | 27-JAN-07:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37939.61 | 21-FEB-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41757.82 | 13-MAR-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43444.99 | 18-APR-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42593.58 | 15-MAY-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42380.38 | 01-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42281.48 | 19-JUL-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41773.74 | 24-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42006.97 | 30-SEP-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41993.63 | 11-OCT-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38869.53 | 13-NOV-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36419.15 | 04-DEC-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24861.51 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43444.99 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4244.00 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
February | 8349.28 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
March | 12920.93 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15206.29 | 26-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.69 | 0.00 |
May | 16939.50 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | 0.00 |
June | 17277.47 | 12-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 | 0.00 |
July | 15592.68 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 0.00 |
August | 14170.84 | 07-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 0.00 |
September | 12840.70 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 0.00 |
October | 12968.44 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 | 0.00 |
November | 8984.16 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
December | 5564.19 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4244.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17277.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.35 | 11.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2294.26 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2779.77 | 22-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 0.00 |
March | 5358.55 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 | 0.00 |
April | 6452.25 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 | 0.00 |
May | 7219.46 | 30-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
June | 9263.45 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 0.00 |
July | 7148.25 | 05-JUL-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.47 | 0.00 |
August | 6775.86 | 28-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6901.31 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
October | 6220.41 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 |
November | 3644.30 | 13-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 0.00 |
December | 2560.90 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2294.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9263.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 | 10.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2572.47 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3695.35 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 0.00 |
March | 5969.39 | 28-MAR-17:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7394.09 | 27-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | 0.00 |
May | 9246.40 | 30-MAY-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 0.00 |
June | 8505.55 | 12-JUN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 0.00 |
July | 8622.84 | 10-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 0.00 |
August | 7891.06 | 07-AUG-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
September | 7568.67 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
October | 6466.34 | 03-OCT-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
November | 4715.09 | 13-NOV-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
December | 2894.81 | 01-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2572.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9246.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | 1.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12155.54 | 26-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15037.51 | 22-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33975.26 | 13-MAR-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34815.92 | 18-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34128.64 | 03-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33909.29 | 01-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33515.75 | 13-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34307.59 | 22-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34884.69 | 29-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34691.08 | 04-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22674.12 | 13-NOV-07:02 | 7623.17 | 12888.13 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13708.65 | 01-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12155.54 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34884.69 | 7623.17 | 12888.13 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11626.68 | 26-JAN-16:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15801.51 | 23-FEB-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23172.85 | 13-MAR-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39223.73 | 17-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39439.42 | 15-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38409.81 | 20-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38785.74 | 11-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39336.26 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38680.95 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37991.43 | 02-OCT-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17199.25 | 09-NOV-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13082.36 | 01-DEC-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11626.68 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39439.42 | 6198.29 | 6443.98 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2466.71 | 26-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
February | 4360.26 | 23-FEB-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 0.00 |
March | 6703.15 | 28-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15799.76 | 16-APR-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 0.00 |
May | 16207.32 | 21-MAY-14:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 | 0.00 |
June | 16641.39 | 11-JUN-16:51 | 602.64 | 323.98 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 | 0.00 |
July | 15958.25 | 04-JUL-16:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 0.00 |
August | 15813.86 | 06-AUG-12:42 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 0.00 |
September | 13015.24 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
October | 15376.81 | 09-OCT-14:21 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 0.00 |
November | 4789.18 | 09-NOV-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 0.00 |
December | 2480.69 | 01-DEC-15:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2466.71 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16641.39 | 1306.65 | 711.15 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 6.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2095.54 | 26-JAN-14:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
February | 4152.49 | 22-FEB-10:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
March | 11586.97 | 12-MAR-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 0.00 |
April | 13018.45 | 16-APR-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 0.00 |
May | 13137.25 | 29-MAY-09:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 0.00 |
June | 13763.41 | 11-JUN-10:11 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | 0.00 |
July | 12818.19 | 02-JUL-08:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 69.56 | 0.00 |
August | 12822.31 | 06-AUG-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 52.29 | 0.00 |
September | 8599.79 | 05-SEP-04:02 | 0.00 | 141.29 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.00 |
October | 12397.71 | 09-OCT-11:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
November | 4262.27 | 09-NOV-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 | 0.00 |
December | 2428.75 | 01-DEC-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2095.54 | 0.00 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13763.41 | 827.22 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 3.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8536.88 | 12-JAN-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
February | 17360.70 | 20-FEB-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 |
March | 16599.11 | 05-MAR-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 0.00 |
April | 16764.19 | 16-APR-14:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 0.00 |
May | 16654.99 | 21-MAY-14:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
June | 16819.68 | 11-JUN-16:11 | 602.64 | 323.98 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 0.00 |
July | 16229.73 | 30-JUL-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 0.00 |
August | 16724.70 | 06-AUG-12:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 0.00 |
September | 16585.54 | 24-SEP-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 75.05 | 0.00 |
October | 18573.31 | 09-OCT-13:01 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
November | 17367.40 | 23-NOV-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
December | 16365.34 | 03-DEC-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8536.88 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18573.31 | 1306.65 | 647.98 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 5.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3532.60 | 31-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
February | 10343.75 | 20-FEB-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
March | 12102.99 | 12-MAR-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 14572.49 | 23-APR-15:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 0.00 |
May | 15102.39 | 28-MAY-16:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 178.10 | 0.00 |
June | 15355.07 | 11-JUN-16:11 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 0.00 |
July | 14388.98 | 02-JUL-16:32 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 69.38 | 0.00 |
August | 13913.47 | 06-AUG-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 54.74 | 0.00 |
September | 13778.38 | 24-SEP-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 51.10 | 0.00 |
October | 14410.44 | 09-OCT-14:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 |
November | 6124.94 | 05-NOV-15:32 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
December | 3964.11 | 01-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3532.60 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15355.07 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 178.10 | 5.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2189.36 | 26-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
February | 3505.21 | 24-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
March | 5137.00 | 13-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 0.00 |
April | 8480.02 | 16-APR-16:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
May | 13050.44 | 29-MAY-16:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 41.58 | 0.00 |
June | 13362.87 | 11-JUN-16:51 | 602.64 | 323.98 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 0.00 |
July | 13472.00 | 04-JUL-18:32 | 0.00 | 258.10 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 | 0.00 |
August | 13046.61 | 06-AUG-13:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 0.00 |
September | 13224.40 | 24-SEP-15:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 | 0.00 |
October | 12935.56 | 01-OCT-15:21 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 0.00 |
November | 4535.86 | 09-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 | 0.00 |
December | 2672.46 | 01-DEC-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2189.36 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13472.00 | 1306.65 | 647.98 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 2.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2271.08 | 26-JAN-11:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 |
February | 3870.20 | 22-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
March | 8362.88 | 12-MAR-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 0.00 |
April | 11096.28 | 16-APR-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
May | 11304.88 | 29-MAY-09:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 88.90 | 0.00 |
June | 11649.30 | 11-JUN-10:11 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 0.00 |
July | 11118.93 | 04-JUL-09:51 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 0.00 |
August | 11133.55 | 06-AUG-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | 0.00 |
September | 11081.92 | 24-SEP-10:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | 0.00 |
October | 11236.96 | 01-OCT-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
November | 4499.81 | 13-NOV-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 3014.96 | 01-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2271.08 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11649.30 | 827.22 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.90 | 4.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9384.09 | 08-JAN-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
February | 14266.42 | 20-FEB-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
March | 13497.65 | 12-MAR-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 | 0.00 |
April | 14408.16 | 27-APR-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13173.04 | 0.00 |
May | 15758.97 | 01-MAY-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 15736.48 | 0.00 |
June | 16097.04 | 12-JUN-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 16143.34 | 0.00 |
July | 14682.06 | 03-JUL-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13216.11 | 0.00 |
August | 13831.91 | 07-AUG-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11212.87 | 0.00 |
September | 14557.29 | 24-SEP-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.45 | 0.00 |
October | 15369.13 | 01-OCT-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
November | 15095.60 | 12-NOV-13:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
December | 11956.69 | 24-DEC-14:03 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9384.09 | 200.88 | 107.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16097.04 | 468.72 | 359.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16143.34 | 16.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2962.66 | 31-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
February | 6536.11 | 20-FEB-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
March | 8669.12 | 26-MAR-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 0.00 |
April | 11654.87 | 30-APR-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 0.00 |
May | 11967.67 | 29-MAY-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 37.74 | 0.00 |
June | 12186.64 | 11-JUN-16:11 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 |
July | 12086.60 | 09-JUL-15:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 | 0.00 |
August | 11575.33 | 06-AUG-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
September | 12335.03 | 24-SEP-15:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 | 0.00 |
October | 12343.90 | 01-OCT-15:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 | 0.00 |
November | 10149.87 | 05-NOV-15:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
December | 3701.51 | 01-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2962.66 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12343.90 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 2.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2547.86 | 26-JAN-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
February | 4142.07 | 23-FEB-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
March | 6080.22 | 13-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.00 |
April | 12605.00 | 16-APR-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 | 0.00 |
May | 13560.37 | 28-MAY-16:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 249.29 | 0.00 |
June | 13607.27 | 04-JUN-16:41 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 102.60 | 0.00 |
July | 13460.46 | 04-JUL-16:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.52 | 0.00 |
August | 10584.46 | 04-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
September | 13554.52 | 24-SEP-15:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 | 0.00 |
October | 9480.76 | 01-OCT-15:31 | 535.68 | 287.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 | 0.00 |
November | 4466.37 | 09-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 | 0.00 |
December | 2593.52 | 01-DEC-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2547.86 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13607.27 | 1306.65 | 647.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 249.29 | 5.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2422.71 | 26-JAN-11:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 |
February | 4398.16 | 22-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 |
March | 7244.16 | 26-MAR-11:03 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 0.00 |
April | 11992.66 | 16-APR-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 0.00 |
May | 12123.39 | 29-MAY-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 0.00 |
June | 11681.73 | 11-JUN-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
July | 12057.36 | 02-JUL-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 | 0.00 |
August | 10971.99 | 06-AUG-12:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 | 0.00 |
September | 11709.36 | 24-SEP-10:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 0.00 |
October | 11927.26 | 01-OCT-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
November | 4414.22 | 09-NOV-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
December | 2992.32 | 01-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2422.71 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12123.39 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 7.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9303.59 | 08-JAN-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 |
February | 14478.02 | 20-FEB-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
March | 14472.73 | 26-MAR-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 42.80 | 0.00 |
April | 14215.51 | 16-APR-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 0.00 |
May | 13892.89 | 29-MAY-15:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 0.00 |
June | 13793.89 | 11-JUN-15:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 0.00 |
July | 13820.41 | 30-JUL-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 | 0.00 |
August | 13943.76 | 06-AUG-12:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 76.45 | 0.00 |
September | 15001.63 | 24-SEP-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 61.31 | 0.00 |
October | 15498.07 | 15-OCT-12:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 | 0.00 |
November | 15699.19 | 12-NOV-13:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
December | 14411.50 | 03-DEC-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9303.59 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15699.19 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 19.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3546.84 | 31-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 |
February | 5221.91 | 21-FEB-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
March | 11177.26 | 26-MAR-15:02 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 | 0.00 |
April | 13174.34 | 02-APR-16:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 | 0.00 |
May | 13103.97 | 28-MAY-16:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 151.06 | 0.00 |
June | 12972.58 | 04-JUN-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 68.47 | 0.00 |
July | 13051.10 | 02-JUL-16:22 | 423.88 | 227.88 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 | 0.00 |
August | 12234.81 | 06-AUG-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 0.00 |
September | 13216.64 | 24-SEP-15:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 30.59 | 0.00 |
October | 12872.55 | 15-OCT-15:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 | 0.00 |
November | 11499.96 | 05-NOV-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
December | 3973.02 | 01-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3546.84 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13216.64 | 805.38 | 410.20 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 151.06 | 4.11 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.118898E+12 | 143868.50 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 0.112870E+12 | 117186.18 | 22-FEB-15:30 | 0.00 | 0.00 |
March | 0.148083E+12 | 151023.80 | 28-MAR-15:00 | 0.00 | 0.00 |
April | 0.168367E+12 | 172512.72 | 26-APR-15:20 | 0.00 | 0.00 |
May | 0.209565E+12 | 197895.01 | 01-MAY-15:09 | 0.00 | 0.00 |
June | 0.215662E+12 | 202283.51 | 12-JUN-14:09 | 0.00 | 0.00 |
July | 0.207253E+12 | 193841.64 | 10-JUL-14:09 | 0.00 | 0.00 |
August | 0.209504E+12 | 189251.10 | 07-AUG-15:20 | 0.00 | 0.00 |
September | 0.180033E+12 | 171048.81 | 14-SEP-15:09 | 0.00 | 0.00 |
October | 0.158766E+12 | 162866.22 | 02-OCT-15:20 | 0.00 | 0.00 |
November | 0.132206E+12 | 124572.69 | 08-NOV-15:39 | 0.00 | 0.00 |
December | 0.117915E+12 | 105899.53 | 01-DEC-15:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.197912E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.112870E+12 | 105899.53 | 0.00 | 0.00 | |
Maximum of Months | 0.215662E+12 | 202283.51 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.254457E+11 | 0.518279E+10 | 0.605851E+11 | 0.225887E+10 | 0.481753E+10 | 12379742.02 | 0.457187E+10 | 0.120984E+11 | 0.00 | 0.00 | 0.00 | 0.392562E+10 | 0.00 |
February | 0.229394E+11 | 0.435602E+10 | 0.548702E+11 | 0.204965E+10 | 0.587288E+10 | 11196021.66 | 0.103264E+10 | 0.182418E+11 | 0.00 | 0.00 | 0.00 | 0.349620E+10 | 0.00 |
March | 0.269764E+11 | 0.436364E+10 | 0.627783E+11 | 0.235656E+10 | 0.106934E+11 | 12675672.10 | 97626849.65 | 0.369373E+11 | 0.00 | 0.00 | 0.00 | 0.386671E+10 | 0.00 |
April | 0.238945E+11 | 0.379987E+10 | 0.586172E+11 | 0.219339E+10 | 0.156363E+11 | 11960507.72 | 0.00 | 0.610444E+11 | 0.00 | 0.00 | 0.00 | 0.316921E+10 | 0.00 |
May | 0.257084E+11 | 0.355162E+10 | 0.616817E+11 | 0.230736E+10 | 0.201551E+11 | 12527707.06 | 0.00 | 0.931116E+11 | 0.00 | 0.00 | 0.00 | 0.303620E+10 | 0.00 |
June | 0.256243E+11 | 0.325331E+10 | 0.604966E+11 | 0.226965E+10 | 0.204169E+11 | 12231776.97 | 0.00 | 0.100857E+12 | 0.00 | 0.00 | 0.00 | 0.273202E+10 | 0.00 |
July | 0.240857E+11 | 0.349586E+10 | 0.597911E+11 | 0.223046E+10 | 0.182504E+11 | 12256437.81 | 0.00 | 0.968983E+11 | 0.00 | 0.00 | 0.00 | 0.248908E+10 | 0.00 |
August | 0.269680E+11 | 0.377888E+10 | 0.627783E+11 | 0.235650E+10 | 0.183081E+11 | 12675672.10 | 0.00 | 0.924880E+11 | 0.00 | 0.00 | 0.00 | 0.281335E+10 | 0.00 |
September | 0.241189E+11 | 0.401124E+10 | 0.585950E+11 | 0.219225E+10 | 0.151182E+11 | 11960507.72 | 0.00 | 0.731987E+11 | 0.00 | 0.00 | 0.00 | 0.278647E+10 | 0.00 |
October | 0.251942E+11 | 0.460280E+10 | 0.605962E+11 | 0.225947E+10 | 0.123191E+11 | 12379742.02 | 0.00 | 0.505670E+11 | 0.00 | 0.00 | 0.00 | 0.321502E+10 | 0.00 |
November | 0.251213E+11 | 0.490037E+10 | 0.591197E+11 | 0.220147E+10 | 0.826386E+10 | 12059151.09 | 0.178516E+09 | 0.289124E+11 | 0.00 | 0.00 | 0.00 | 0.349597E+10 | 0.00 |
December | 0.246925E+11 | 0.534314E+10 | 0.597800E+11 | 0.223015E+10 | 0.542884E+10 | 12256437.81 | 0.180722E+10 | 0.148987E+11 | 0.00 | 0.00 | 0.00 | 0.372213E+10 | 0.00 |
Annual Sum or Average | 0.300769E+12 | 0.506395E+11 | 0.719689E+12 | 0.269058E+11 | 0.155281E+12 | 0.146559E+09 | 0.768788E+10 | 0.679254E+12 | 0.00 | 0.00 | 0.00 | 0.387480E+11 | 0.00 |
Minimum of Months | 0.229394E+11 | 0.325331E+10 | 0.548702E+11 | 0.204965E+10 | 0.481753E+10 | 11196021.66 | 0.00 | 0.120984E+11 | 0.00 | 0.00 | 0.00 | 0.248908E+10 | 0.00 |
Maximum of Months | 0.269764E+11 | 0.534314E+10 | 0.627783E+11 | 0.235656E+10 | 0.204169E+11 | 12675672.10 | 0.457187E+10 | 0.100857E+12 | 0.00 | 0.00 | 0.00 | 0.392562E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30940.97 | 18-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:09 | 7135.78 | 12-JAN-15:09 | 6.85 | 03-JAN-06:19 | 98066.79 | 02-JAN-07:10 |
February | 30940.97 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-08:09 | 13076.68 | 22-FEB-15:00 | 6.85 | 03-FEB-08:09 | 32708.06 | 02-FEB-07:10 |
March | 30821.00 | 14-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 28-MAR-16:10 | 19272.86 | 13-MAR-15:00 | 6.85 | 01-MAR-06:10 | 6332.39 | 03-MAR-07:19 |
April | 26819.30 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 13-APR-12:09 | 23729.33 | 17-APR-15:09 | 6.85 | 02-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 28290.68 | 24-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:20 | 27217.54 | 30-MAY-14:20 | 6.85 | 02-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 28290.68 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 02-JUN-11:09 | 28328.66 | 05-JUN-14:09 | 6.85 | 02-JUN-12:09 | 0.00 | 01-JUN-00:10 |
July | 30940.97 | 18-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-16:10 | 27189.84 | 05-JUL-14:50 | 6.85 | 02-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 30940.97 | 16-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 07-AUG-11:09 | 25613.79 | 07-AUG-15:30 | 6.85 | 06-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 30940.97 | 05-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 26-SEP-16:10 | 22511.05 | 25-SEP-15:00 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 11-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 18651.88 | 02-OCT-15:00 | 6.85 | 01-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 31751.76 | 27-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 06-NOV-08:09 | 13419.45 | 01-NOV-15:00 | 6.85 | 01-NOV-05:10 | 14914.38 | 27-NOV-07:10 |
December | 31791.75 | 29-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 11-DEC-08:09 | 9864.27 | 01-DEC-15:30 | 6.85 | 21-DEC-17:10 | 43379.57 | 23-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26819.30 | 5686.19 | 41699.26 | 1410.29 | 7135.78 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 28328.66 | 6.85 | 98066.79 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 20818.37 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 5341.07 | 24-JAN-12:50 | 0.00 |
February | 33066.15 | 22-FEB-15:09 | 0.00 | 0.00 | 0.00 | 5229.53 | 01-FEB-12:50 | 0.00 |
March | 61322.54 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 | 4978.27 | 01-MAR-12:30 | 0.00 |
April | 82177.78 | 26-APR-15:30 | 0.00 | 0.00 | 0.00 | 4583.12 | 03-APR-11:00 | 0.00 |
May | 104632.55 | 01-MAY-14:00 | 0.00 | 0.00 | 0.00 | 4119.61 | 02-MAY-11:50 | 0.00 |
June | 107743.39 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 3540.31 | 01-JUN-11:20 | 0.00 |
July | 98789.37 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 3503.04 | 05-JUL-11:20 | 0.00 |
August | 92362.33 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 3533.00 | 31-AUG-11:00 | 0.00 |
September | 79816.90 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 3885.82 | 29-SEP-11:20 | 0.00 |
October | 74836.86 | 02-OCT-14:00 | 0.00 | 0.00 | 0.00 | 4572.50 | 30-OCT-11:20 | 0.00 |
November | 41290.91 | 06-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4965.12 | 30-NOV-12:20 | 0.00 |
December | 24242.56 | 01-DEC-15:09 | 0.00 | 0.00 | 0.00 | 5184.34 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 20818.37 | 0.00 | 0.00 | 0.00 | 3503.04 | 0.00 | ||
Maximum of Months | 107743.39 | 0.00 | 0.00 | 0.00 | 5341.07 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 143868.50 | 02-JAN-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3882.87 | 6.85 | 98066.79 | 217.50 | 0.00 |
February | 117186.18 | 22-FEB-15:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 12663.91 | 6.85 | 0.00 | 32885.08 | 0.00 |
March | 151023.80 | 28-MAR-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 17395.92 | 6.85 | 0.00 | 61322.54 | 0.00 |
April | 172512.72 | 26-APR-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 18921.96 | 6.85 | 0.00 | 81624.21 | 0.00 |
May | 197895.01 | 01-MAY-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 21335.31 | 6.85 | 0.00 | 104609.65 | 0.00 |
June | 202283.51 | 12-JUN-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 28252.44 | 6.85 | 0.00 | 103322.49 | 0.00 |
July | 193841.64 | 10-JUL-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 25933.74 | 6.85 | 0.00 | 97206.46 | 0.00 |
August | 189251.10 | 07-AUG-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 25605.69 | 6.85 | 0.00 | 92318.30 | 0.00 |
September | 171048.81 | 14-SEP-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 19803.69 | 6.85 | 0.00 | 79610.62 | 0.00 |
October | 162866.22 | 02-OCT-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 17096.47 | 6.85 | 0.00 | 73816.05 | 0.00 |
November | 124572.69 | 08-NOV-15:39 | 25990.55 | 41659.26 | 0.00 | 1410.29 | 12320.79 | 6.85 | 0.00 | 40617.76 | 0.00 |
December | 105899.53 | 01-DEC-15:20 | 25990.55 | 41659.26 | 0.00 | 1410.29 | 9801.64 | 6.85 | 0.00 | 24158.97 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 105899.53 | 10880.98 | 22496.85 | 0.00 | 975.80 | 3882.87 | 6.85 | 0.00 | 217.50 | 0.00 | |
Maximum of Months | 202283.51 | 25990.55 | 41670.51 | 5686.19 | 1410.29 | 28252.44 | 6.85 | 98066.79 | 104609.65 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.28 | 0.00 | 26.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.00 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.28 | 0.00 | 26.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.33 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.04 | 0.33 | 27.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.33 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.97 | 0.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.70 | 3.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.77 | 8.83 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.68 | 6.50 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.69 | 9.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.64 | 6.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.53 | 3.00 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.97 | 0.17 | 18.97 | 62.17 | 27.64 | 38.83 | 27.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.97 | 0.17 | 18.97 | 16.83 | 27.77 | 9.83 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.95 | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.94 | 10.50 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 28.11 | 12.17 | 28.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.88 | 8.67 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.94 | 12.00 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.87 | 7.33 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.81 | 4.67 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.70 | 7.33 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.95 | 0.17 | 18.95 | 87.33 | 27.89 | 65.00 | 27.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.95 | 0.17 | 18.95 | 18.33 | 28.11 | 12.17 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.16 | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.76 | 3.50 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.88 | 5.00 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.93 | 7.67 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.82 | 9.00 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.68 | 6.50 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.75 | 9.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.81 | 6.17 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.98 | 4.00 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.27 | 10.83 | 28.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.98 | 8.50 | 27.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.53 | 1.33 | 27.53 |
Annual Sum or Average | 0.17 | 19.16 | 0.17 | 19.16 | 97.50 | 27.85 | 72.17 | 27.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 0.00 | 19.16 |
Maximum of Months | 0.17 | 19.16 | 0.17 | 19.16 | 16.00 | 28.27 | 10.83 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.95 | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.61 | 0.50 | 27.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.95 | 2.50 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.24 | 6.17 | 28.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 28.21 | 8.83 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.17 | 6.50 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 28.07 | 9.33 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.04 | 5.33 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.13 | 2.83 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.17 | 5.50 | 28.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.95 | 0.17 | 18.95 | 82.50 | 28.09 | 48.67 | 28.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.95 | 0.17 | 18.95 | 18.17 | 28.24 | 9.33 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.48 | 4.17 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.50 | 3.00 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.39 | 8.50 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.32 | 4.50 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.19 | 2.17 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.33 | 27.39 | 22.67 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.50 | 8.50 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.33 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.76 | 6.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.81 | 10.83 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.60 | 6.33 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.61 | 11.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.56 | 6.67 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.54 | 4.67 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.61 | 6.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 72.00 | 27.65 | 53.50 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.81 | 11.50 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.83 | 18.78 | 18.83 | 18.78 | 0.50 | 18.89 | 0.50 | 19.00 |
February | 9.33 | 19.53 | 9.33 | 19.53 | 3.50 | 20.81 | 3.50 | 21.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 25.82 | 15.17 | 25.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 26.09 | 43.17 | 26.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 26.55 | 62.17 | 26.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 26.34 | 63.50 | 26.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.00 | 26.27 | 45.33 | 26.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 25.97 | 42.00 | 25.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 25.64 | 52.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 25.64 | 80.67 | 25.61 |
November | 0.17 | 20.39 | 0.17 | 20.39 | 21.33 | 26.16 | 21.17 | 26.20 |
December | 13.00 | 19.81 | 13.00 | 19.81 | 2.83 | 20.57 | 2.83 | 21.20 |
Annual Sum or Average | 41.33 | 19.28 | 41.33 | 19.28 | 453.33 | 25.03 | 432.00 | 25.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 18.89 | 0.50 | 19.00 |
Maximum of Months | 18.83 | 20.39 | 18.83 | 20.39 | 83.50 | 26.55 | 80.67 | 26.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.66 | 0.83 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.90 | 4.50 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.95 | 6.67 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.69 | 5.50 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.68 | 8.67 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.59 | 5.67 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.70 | 2.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.90 | 5.00 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.38 | 1.00 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 76.67 | 27.75 | 40.67 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.95 | 8.67 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 2.17 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.56 | 7.83 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.47 | 4.67 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.44 | 8.83 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.48 | 4.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.41 | 2.00 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.83 | 27.49 | 29.83 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.56 | 8.83 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.87 | 8.67 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.98 | 12.00 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.72 | 8.33 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.73 | 11.50 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.72 | 6.50 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.70 | 4.17 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.69 | 5.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 70.50 | 27.79 | 58.67 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.98 | 12.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 3.83 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.76 | 5.00 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.76 | 6.83 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.64 | 8.33 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.51 | 5.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.49 | 9.00 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.54 | 5.67 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.80 | 3.83 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.61 | 13.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.94 | 9.17 | 27.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.59 | 2.00 | 27.59 |
Annual Sum or Average | 0.00 | 0.00 | 89.33 | 27.65 | 72.33 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.94 | 13.17 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.82 | 2.33 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.10 | 5.17 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.08 | 7.33 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.01 | 5.17 | 28.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.88 | 7.67 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.95 | 4.00 | 27.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.03 | 2.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.03 | 5.00 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 67.83 | 27.99 | 40.50 | 28.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.10 | 7.67 | 28.19 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.50 | 23.84 | 123.67 | 24.62 | 12.33 | 24.59 |
February | 0.00 | 0.00 | 250.33 | 24.70 | 0.00 | 24.70 |
March | 0.00 | 0.00 | 428.83 | 24.48 | 0.00 | 24.48 |
April | 0.00 | 0.00 | 449.50 | 24.50 | 0.00 | 24.50 |
May | 0.00 | 0.00 | 505.33 | 24.44 | 0.00 | 24.44 |
June | 0.00 | 0.00 | 496.00 | 24.40 | 0.00 | 24.40 |
July | 0.00 | 0.00 | 497.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 514.00 | 24.43 | 0.00 | 24.43 |
September | 0.50 | 27.27 | 485.00 | 24.51 | 0.50 | 24.51 |
October | 0.00 | 0.00 | 502.00 | 24.52 | 0.00 | 24.52 |
November | 0.00 | 0.00 | 428.00 | 24.52 | 0.00 | 24.52 |
December | 11.67 | 23.99 | 163.00 | 24.81 | 0.00 | 24.81 |
Annual Sum or Average | 74.67 | 23.89 | 4842.67 | 24.50 | 12.83 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 123.67 | 24.40 | 0.00 | 24.40 |
Maximum of Months | 62.50 | 27.27 | 514.00 | 24.81 | 12.33 | 24.81 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.50 | 23.08 | 4.50 | 23.08 | 2.83 | 23.07 |
February | 178.83 | 23.33 | 86.17 | 23.67 | 0.00 | 23.67 |
March | 33.17 | 23.64 | 310.83 | 24.25 | 0.00 | 24.25 |
April | 0.00 | 0.00 | 416.83 | 24.36 | 0.00 | 24.36 |
May | 0.00 | 0.00 | 497.00 | 24.33 | 0.00 | 24.33 |
June | 0.00 | 0.00 | 496.00 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 514.00 | 24.32 | 0.00 | 24.32 |
September | 2.67 | 27.15 | 485.00 | 24.38 | 2.67 | 24.40 |
October | 0.00 | 0.00 | 462.33 | 24.35 | 0.00 | 24.35 |
November | 65.83 | 23.54 | 224.83 | 24.18 | 0.00 | 24.18 |
December | 313.83 | 23.32 | 4.67 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 992.83 | 23.26 | 3999.17 | 24.12 | 5.50 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 4.50 | 23.08 | 0.00 | 23.07 |
Maximum of Months | 398.50 | 27.15 | 514.00 | 24.38 | 2.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.83 | 22.31 | 17.33 | 22.21 | 17.33 | 22.13 |
February | 296.67 | 22.90 | 49.33 | 23.07 | 0.00 | 23.07 |
March | 114.83 | 23.41 | 247.50 | 23.96 | 0.00 | 23.96 |
April | 4.50 | 23.57 | 399.00 | 24.37 | 0.00 | 24.37 |
May | 1.67 | 26.61 | 505.50 | 24.38 | 1.67 | 24.39 |
June | 1.67 | 26.52 | 496.00 | 24.33 | 1.67 | 24.34 |
July | 0.50 | 26.56 | 497.00 | 24.41 | 0.50 | 24.41 |
August | 0.00 | 0.00 | 514.00 | 24.35 | 0.00 | 24.35 |
September | 1.83 | 27.14 | 482.33 | 24.38 | 1.83 | 24.39 |
October | 23.83 | 23.33 | 399.50 | 24.26 | 0.00 | 24.26 |
November | 208.67 | 23.21 | 126.50 | 23.54 | 0.00 | 23.54 |
December | 429.83 | 22.60 | 7.33 | 22.57 | 6.33 | 22.55 |
Annual Sum or Average | 1553.83 | 22.74 | 3741.33 | 23.85 | 29.33 | 23.84 |
Minimum of Months | 0.00 | 0.00 | 7.33 | 22.21 | 0.00 | 22.13 |
Maximum of Months | 469.83 | 27.14 | 514.00 | 24.41 | 17.33 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.50 | 21.49 | 83.67 | 21.25 | 83.67 | 21.07 |
February | 352.00 | 22.26 | 67.33 | 22.37 | 19.67 | 22.27 |
March | 165.00 | 22.95 | 242.33 | 23.70 | 0.50 | 23.70 |
April | 37.83 | 24.77 | 414.00 | 24.53 | 14.50 | 24.60 |
May | 43.33 | 26.87 | 508.00 | 24.75 | 43.33 | 24.90 |
June | 47.00 | 26.63 | 496.00 | 24.71 | 47.00 | 24.86 |
July | 81.67 | 26.58 | 497.00 | 24.92 | 81.67 | 25.13 |
August | 50.83 | 26.51 | 514.00 | 24.68 | 50.83 | 24.83 |
September | 45.50 | 26.44 | 482.67 | 24.66 | 45.50 | 24.80 |
October | 75.50 | 23.38 | 365.00 | 24.19 | 6.83 | 24.23 |
November | 290.00 | 22.63 | 120.67 | 23.02 | 4.17 | 22.99 |
December | 479.00 | 21.82 | 58.83 | 21.62 | 58.83 | 21.45 |
Annual Sum or Average | 2158.17 | 22.71 | 3849.50 | 23.72 | 456.50 | 23.75 |
Minimum of Months | 37.83 | 21.49 | 58.83 | 21.25 | 0.50 | 21.07 |
Maximum of Months | 490.50 | 26.87 | 514.00 | 24.92 | 83.67 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.33 | 21.87 | 56.67 | 21.64 | 56.67 | 21.46 |
February | 270.83 | 22.37 | 115.50 | 22.79 | 13.17 | 22.70 |
March | 124.00 | 23.15 | 320.83 | 24.00 | 8.17 | 24.05 |
April | 53.33 | 25.86 | 439.50 | 24.72 | 36.83 | 24.88 |
May | 55.83 | 27.03 | 507.00 | 24.84 | 55.83 | 25.04 |
June | 51.00 | 26.78 | 496.00 | 24.74 | 51.00 | 24.92 |
July | 84.33 | 26.70 | 497.00 | 24.95 | 84.33 | 25.17 |
August | 56.17 | 26.62 | 514.00 | 24.71 | 56.17 | 24.88 |
September | 48.83 | 26.55 | 481.83 | 24.69 | 48.83 | 24.84 |
October | 84.83 | 24.32 | 396.00 | 24.46 | 30.67 | 24.60 |
November | 206.83 | 22.61 | 209.17 | 23.41 | 3.17 | 23.39 |
December | 425.67 | 22.10 | 42.33 | 21.93 | 39.83 | 21.77 |
Annual Sum or Average | 1941.00 | 23.11 | 4075.83 | 23.97 | 484.67 | 24.06 |
Minimum of Months | 48.83 | 21.87 | 42.33 | 21.64 | 3.17 | 21.46 |
Maximum of Months | 479.33 | 27.03 | 514.00 | 24.95 | 84.33 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 318.17 | 21.77 | 154.17 | 22.13 | 55.50 | 21.92 |
February | 227.00 | 22.50 | 181.17 | 23.28 | 19.83 | 23.26 |
March | 131.00 | 23.49 | 314.33 | 24.12 | 18.50 | 24.23 |
April | 49.50 | 25.48 | 422.33 | 24.66 | 27.83 | 24.79 |
May | 43.00 | 26.93 | 507.67 | 24.75 | 43.00 | 24.91 |
June | 45.00 | 26.63 | 496.00 | 24.69 | 45.00 | 24.84 |
July | 78.33 | 26.59 | 497.00 | 24.91 | 78.33 | 25.11 |
August | 53.00 | 26.59 | 514.00 | 24.70 | 53.00 | 24.86 |
September | 51.17 | 26.58 | 484.00 | 24.72 | 51.17 | 24.89 |
October | 88.67 | 24.97 | 412.33 | 24.64 | 41.67 | 24.83 |
November | 184.17 | 23.34 | 261.67 | 24.06 | 27.50 | 24.23 |
December | 271.00 | 22.02 | 176.00 | 22.72 | 32.83 | 22.54 |
Annual Sum or Average | 1540.00 | 23.42 | 4420.67 | 24.18 | 494.17 | 24.27 |
Minimum of Months | 43.00 | 21.77 | 154.17 | 22.13 | 18.50 | 21.92 |
Maximum of Months | 318.17 | 26.93 | 514.00 | 24.91 | 78.33 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.83 | 21.45 | 92.50 | 21.28 | 80.67 | 21.09 |
February | 314.67 | 22.10 | 115.50 | 22.53 | 20.00 | 22.43 |
March | 172.83 | 22.99 | 272.33 | 23.80 | 9.50 | 23.86 |
April | 56.83 | 25.13 | 420.67 | 24.62 | 28.00 | 24.75 |
May | 50.33 | 27.02 | 506.00 | 24.79 | 50.33 | 24.98 |
June | 54.83 | 26.79 | 496.00 | 24.75 | 54.83 | 24.93 |
July | 79.67 | 26.64 | 497.00 | 24.91 | 79.67 | 25.12 |
August | 54.83 | 26.58 | 514.00 | 24.69 | 54.83 | 24.85 |
September | 46.33 | 26.48 | 475.00 | 24.67 | 46.33 | 24.81 |
October | 100.67 | 23.79 | 362.00 | 24.30 | 22.33 | 24.42 |
November | 272.33 | 22.53 | 167.83 | 23.17 | 7.00 | 23.18 |
December | 413.33 | 21.70 | 91.17 | 21.67 | 56.83 | 21.50 |
Annual Sum or Average | 2053.50 | 22.82 | 4010.00 | 23.81 | 510.33 | 23.87 |
Minimum of Months | 46.33 | 21.45 | 91.17 | 21.28 | 7.00 | 21.09 |
Maximum of Months | 436.83 | 27.02 | 514.00 | 24.91 | 80.67 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.33 | 22.32 | 14.83 | 22.27 | 14.83 | 22.23 |
February | 340.00 | 22.80 | 36.17 | 22.94 | 0.00 | 22.94 |
March | 145.67 | 23.27 | 223.50 | 23.80 | 0.00 | 23.80 |
April | 13.50 | 23.91 | 406.50 | 24.41 | 1.17 | 24.41 |
May | 19.00 | 26.84 | 508.00 | 24.61 | 19.00 | 24.68 |
June | 29.33 | 26.59 | 496.00 | 24.62 | 29.33 | 24.73 |
July | 64.17 | 26.65 | 497.00 | 24.88 | 64.17 | 25.06 |
August | 37.83 | 26.70 | 514.00 | 24.67 | 37.83 | 24.80 |
September | 35.17 | 26.60 | 485.00 | 24.69 | 35.17 | 24.82 |
October | 3.83 | 24.44 | 471.67 | 24.41 | 1.00 | 24.41 |
November | 140.83 | 23.37 | 206.67 | 23.84 | 0.00 | 23.84 |
December | 422.00 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 1737.67 | 23.17 | 3859.33 | 24.06 | 202.50 | 24.13 |
Minimum of Months | 3.83 | 22.32 | 0.00 | 22.27 | 0.00 | 22.23 |
Maximum of Months | 486.33 | 26.84 | 514.00 | 24.88 | 64.17 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.50 | 22.66 | 19.67 | 22.63 | 14.17 | 22.59 |
February | 213.33 | 22.88 | 121.00 | 23.40 | 0.00 | 23.40 |
March | 82.17 | 23.29 | 335.33 | 24.12 | 0.67 | 24.12 |
April | 25.00 | 26.40 | 446.67 | 24.64 | 20.67 | 24.74 |
May | 48.83 | 26.92 | 508.00 | 24.80 | 48.83 | 24.97 |
June | 45.17 | 26.72 | 496.00 | 24.72 | 45.17 | 24.87 |
July | 73.83 | 26.78 | 497.00 | 24.94 | 73.83 | 25.15 |
August | 46.17 | 26.81 | 514.00 | 24.73 | 46.17 | 24.89 |
September | 42.17 | 26.70 | 485.00 | 24.75 | 42.17 | 24.89 |
October | 26.33 | 26.79 | 487.50 | 24.64 | 25.50 | 24.75 |
November | 71.50 | 23.31 | 317.33 | 24.17 | 0.00 | 24.17 |
December | 293.67 | 22.91 | 31.00 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 1377.67 | 23.73 | 4258.50 | 24.32 | 317.17 | 24.44 |
Minimum of Months | 25.00 | 22.66 | 19.67 | 22.63 | 0.00 | 22.59 |
Maximum of Months | 409.50 | 26.92 | 514.00 | 24.94 | 73.83 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.17 | 22.34 | 129.50 | 22.76 | 26.67 | 22.63 |
February | 163.50 | 22.48 | 197.50 | 23.59 | 7.50 | 23.60 |
March | 85.67 | 23.11 | 338.67 | 24.18 | 8.00 | 24.23 |
April | 37.00 | 25.58 | 437.67 | 24.78 | 27.50 | 24.88 |
May | 97.83 | 25.88 | 508.00 | 25.01 | 97.83 | 25.13 |
June | 155.67 | 25.32 | 496.00 | 24.93 | 155.67 | 25.01 |
July | 252.33 | 25.03 | 497.00 | 24.89 | 252.33 | 24.92 |
August | 263.50 | 24.78 | 514.00 | 24.71 | 263.50 | 24.73 |
September | 201.00 | 24.99 | 485.00 | 24.83 | 201.00 | 24.87 |
October | 92.33 | 25.75 | 488.50 | 24.98 | 87.00 | 25.11 |
November | 79.50 | 24.23 | 386.00 | 24.58 | 32.00 | 24.74 |
December | 213.00 | 22.74 | 186.00 | 23.63 | 5.17 | 23.64 |
Annual Sum or Average | 1945.50 | 24.10 | 4663.83 | 24.52 | 1164.17 | 24.62 |
Minimum of Months | 37.00 | 22.34 | 129.50 | 22.76 | 5.17 | 22.63 |
Maximum of Months | 304.17 | 25.88 | 514.00 | 25.01 | 263.50 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.17 | 22.39 | 32.00 | 22.43 | 14.17 | 22.39 |
February | 272.00 | 22.77 | 103.00 | 23.21 | 0.00 | 23.21 |
March | 108.17 | 23.31 | 301.83 | 24.04 | 2.50 | 24.05 |
April | 21.33 | 26.44 | 445.33 | 24.60 | 17.83 | 24.69 |
May | 39.17 | 26.99 | 508.00 | 24.76 | 39.17 | 24.91 |
June | 47.17 | 26.83 | 496.00 | 24.75 | 47.17 | 24.91 |
July | 74.67 | 26.74 | 497.00 | 24.94 | 74.67 | 25.14 |
August | 48.00 | 26.81 | 514.00 | 24.74 | 48.00 | 24.90 |
September | 45.00 | 26.73 | 485.00 | 24.77 | 45.00 | 24.93 |
October | 21.83 | 26.83 | 483.50 | 24.61 | 20.67 | 24.70 |
November | 96.33 | 23.35 | 285.00 | 24.09 | 1.17 | 24.10 |
December | 351.50 | 22.81 | 59.33 | 23.01 | 0.00 | 23.01 |
Annual Sum or Average | 1539.33 | 23.53 | 4210.00 | 24.25 | 310.33 | 24.37 |
Minimum of Months | 21.33 | 22.39 | 32.00 | 22.43 | 0.00 | 22.39 |
Maximum of Months | 414.17 | 26.99 | 514.00 | 24.94 | 74.67 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 478.83 | 22.11 | 33.67 | 21.98 | 33.67 | 21.86 |
February | 303.00 | 22.75 | 59.17 | 22.98 | 0.00 | 22.98 |
March | 107.50 | 23.34 | 277.50 | 23.98 | 0.00 | 23.98 |
April | 9.33 | 26.22 | 429.50 | 24.54 | 7.33 | 24.58 |
May | 38.17 | 26.80 | 508.00 | 24.73 | 38.17 | 24.87 |
June | 42.83 | 26.58 | 496.00 | 24.69 | 42.83 | 24.83 |
July | 78.67 | 26.53 | 497.00 | 24.90 | 78.67 | 25.10 |
August | 47.50 | 26.44 | 514.00 | 24.66 | 47.50 | 24.80 |
September | 47.50 | 26.47 | 485.00 | 24.69 | 47.50 | 24.83 |
October | 24.33 | 23.59 | 430.17 | 24.33 | 1.50 | 24.34 |
November | 205.83 | 23.13 | 144.17 | 23.54 | 0.00 | 23.54 |
December | 435.17 | 22.42 | 8.00 | 22.38 | 8.00 | 22.34 |
Annual Sum or Average | 1818.67 | 23.14 | 3882.17 | 24.02 | 305.17 | 24.11 |
Minimum of Months | 9.33 | 22.11 | 8.00 | 21.98 | 0.00 | 21.86 |
Maximum of Months | 478.83 | 26.80 | 514.00 | 24.90 | 78.67 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.83 | 22.24 | 29.67 | 22.11 | 29.50 | 21.99 |
February | 216.67 | 22.72 | 89.67 | 23.23 | 0.00 | 23.23 |
March | 84.67 | 23.46 | 272.17 | 24.20 | 6.00 | 24.25 |
April | 37.00 | 26.55 | 373.17 | 24.86 | 32.67 | 25.01 |
May | 53.67 | 26.94 | 430.00 | 24.96 | 53.67 | 25.16 |
June | 47.67 | 26.71 | 418.00 | 24.84 | 47.67 | 25.01 |
July | 80.00 | 26.65 | 422.00 | 25.07 | 80.00 | 25.29 |
August | 51.50 | 26.59 | 433.00 | 24.80 | 51.50 | 24.97 |
September | 49.17 | 26.56 | 410.00 | 24.81 | 49.17 | 24.98 |
October | 47.00 | 25.17 | 365.33 | 24.66 | 25.33 | 24.78 |
November | 150.00 | 23.00 | 179.83 | 23.77 | 0.00 | 23.77 |
December | 327.67 | 22.45 | 12.00 | 22.46 | 5.67 | 22.42 |
Annual Sum or Average | 1533.83 | 23.51 | 3434.83 | 24.25 | 381.17 | 24.38 |
Minimum of Months | 37.00 | 22.24 | 12.00 | 22.11 | 0.00 | 21.99 |
Maximum of Months | 388.83 | 26.94 | 433.00 | 25.07 | 80.00 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.83 | 22.40 | 144.33 | 22.95 | 18.00 | 22.89 |
February | 177.33 | 23.01 | 192.67 | 23.81 | 8.50 | 23.89 |
March | 82.67 | 24.00 | 349.83 | 24.32 | 16.00 | 24.42 |
April | 26.33 | 26.79 | 440.50 | 24.69 | 24.67 | 24.81 |
May | 40.00 | 26.84 | 508.00 | 24.74 | 40.00 | 24.88 |
June | 42.00 | 26.56 | 496.00 | 24.68 | 42.00 | 24.81 |
July | 74.83 | 26.53 | 497.00 | 24.89 | 74.83 | 25.08 |
August | 48.50 | 26.53 | 514.00 | 24.68 | 48.50 | 24.83 |
September | 51.50 | 26.61 | 485.00 | 24.75 | 51.50 | 24.91 |
October | 57.17 | 26.20 | 454.67 | 24.77 | 43.67 | 24.95 |
November | 126.17 | 24.12 | 303.50 | 24.44 | 30.17 | 24.62 |
December | 231.83 | 22.69 | 171.00 | 23.52 | 4.67 | 23.53 |
Annual Sum or Average | 1243.17 | 23.96 | 4556.50 | 24.41 | 402.50 | 24.55 |
Minimum of Months | 26.33 | 22.40 | 144.33 | 22.95 | 4.67 | 22.89 |
Maximum of Months | 284.83 | 26.84 | 514.00 | 24.89 | 74.83 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 418.33 | 22.00 | 54.83 | 21.98 | 33.33 | 21.87 |
February | 275.33 | 22.58 | 109.17 | 23.09 | 0.50 | 23.10 |
March | 113.67 | 23.36 | 310.50 | 24.06 | 7.17 | 24.11 |
April | 31.00 | 26.22 | 444.83 | 24.65 | 23.83 | 24.76 |
May | 49.33 | 26.97 | 508.00 | 24.79 | 49.33 | 24.97 |
June | 50.17 | 26.77 | 496.00 | 24.74 | 50.17 | 24.91 |
July | 80.33 | 26.59 | 497.00 | 24.91 | 80.33 | 25.11 |
August | 50.00 | 26.56 | 514.00 | 24.67 | 50.00 | 24.83 |
September | 44.50 | 26.52 | 485.00 | 24.68 | 44.50 | 24.82 |
October | 51.50 | 24.75 | 427.00 | 24.48 | 21.17 | 24.59 |
November | 195.17 | 23.00 | 197.17 | 23.66 | 2.17 | 23.67 |
December | 387.00 | 22.30 | 57.67 | 22.48 | 8.17 | 22.44 |
Annual Sum or Average | 1746.33 | 23.25 | 4101.17 | 24.10 | 370.67 | 24.21 |
Minimum of Months | 31.00 | 22.00 | 54.83 | 21.98 | 0.50 | 21.87 |
Maximum of Months | 418.33 | 26.97 | 514.00 | 24.91 | 80.33 | 25.11 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.30256 | 36.88462 | 0.38718 | 8.36645 |
February | 454.00000 | 24.41268 | 39.01432 | 0.45806 | 9.65880 |
March | 514.00000 | 24.40701 | 43.40786 | 0.52074 | 10.94211 |
April | 485.00000 | 24.46618 | 44.42481 | 0.56051 | 11.88569 |
May | 508.00000 | 24.43830 | 49.92476 | -0.2325 | 6.67891 |
June | 496.00000 | 24.40171 | 52.32650 | -0.2277 | 6.62248 |
July | 497.00000 | 24.47119 | 53.58859 | -0.2024 | 6.48529 |
August | 514.00000 | 24.43105 | 53.66648 | -0.2128 | 6.59102 |
September | 485.00000 | 24.50737 | 53.26898 | -0.1964 | 6.59943 |
October | 502.00000 | 24.52095 | 48.71196 | 0.60064 | 12.89866 |
November | 489.00000 | 24.46582 | 42.35956 | 0.52265 | 10.98427 |
December | 497.00000 | 24.36659 | 36.14760 | 0.41921 | 8.85473 |
Annual Sum or Average | 5943.00000 | 24.43240 | 46.20362 | 0.19704 | 8.86933 |
Minimum of Months | 454.00000 | 24.30256 | 36.14760 | -0.2325 | 6.48529 |
Maximum of Months | 514.00000 | 24.52095 | 53.66648 | 0.60064 | 12.89866 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28829 | 39.73785 | 0.13912 | 5.99981 |
February | 454.00000 | 23.82966 | 40.52880 | 0.30420 | 7.37643 |
March | 514.00000 | 24.16378 | 44.14003 | 0.44516 | 9.36078 |
April | 485.00000 | 24.30795 | 45.84771 | 0.51737 | 10.81251 |
May | 508.00000 | 24.32400 | 52.07154 | -0.2742 | 6.93625 |
June | 496.00000 | 24.28253 | 54.95737 | -0.2686 | 6.81374 |
July | 497.00000 | 24.35307 | 56.18909 | -0.2441 | 6.65943 |
August | 514.00000 | 24.31608 | 56.52696 | -0.2565 | 6.77470 |
September | 485.00000 | 24.36972 | 55.92458 | -0.2518 | 6.86957 |
October | 502.00000 | 24.32076 | 49.68809 | 0.53652 | 11.22491 |
November | 489.00000 | 24.10459 | 42.85222 | 0.40902 | 8.72219 |
December | 497.00000 | 23.59954 | 37.93607 | 0.21808 | 6.41590 |
Annual Sum or Average | 5943.00000 | 24.10669 | 48.09699 | 0.10392 | 7.82971 |
Minimum of Months | 454.00000 | 23.28829 | 37.93607 | -0.2742 | 5.99981 |
Maximum of Months | 514.00000 | 24.36972 | 56.52696 | 0.53652 | 11.22491 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41132 | 41.03759 | -0.0772 | 6.47191 |
February | 454.00000 | 23.30119 | 40.98105 | 0.17087 | 6.63772 |
March | 514.00000 | 23.99008 | 43.35635 | 0.39705 | 8.71285 |
April | 485.00000 | 24.31105 | 45.30165 | 0.52593 | 11.06637 |
May | 508.00000 | 24.37110 | 51.75898 | -0.2335 | 6.66657 |
June | 496.00000 | 24.32753 | 54.75944 | -0.2262 | 6.51096 |
July | 497.00000 | 24.40818 | 56.15533 | -0.2044 | 6.47098 |
August | 514.00000 | 24.34710 | 56.61081 | -0.2289 | 6.59535 |
September | 485.00000 | 24.36797 | 55.88621 | -0.2430 | 6.81570 |
October | 502.00000 | 24.20673 | 49.22419 | 0.50434 | 10.59599 |
November | 489.00000 | 23.69690 | 42.91509 | 0.30080 | 7.46974 |
December | 497.00000 | 22.78315 | 39.03945 | 0.01520 | 6.13484 |
Annual Sum or Average | 5943.00000 | 23.88095 | 48.14531 | 0.05686 | 7.51417 |
Minimum of Months | 454.00000 | 22.41132 | 39.03945 | -0.2430 | 6.13484 |
Maximum of Months | 514.00000 | 24.40818 | 56.61081 | 0.52593 | 11.06637 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.54197 | 44.53930 | -0.2885 | 8.69049 |
February | 454.00000 | 22.66038 | 43.61661 | 0.02087 | 7.08342 |
March | 514.00000 | 23.76471 | 44.38332 | 0.35330 | 8.74481 |
April | 485.00000 | 24.40615 | 45.09578 | 0.58324 | 12.84226 |
May | 508.00000 | 24.56595 | 51.37930 | -0.0822 | 6.51658 |
June | 496.00000 | 24.52445 | 54.47090 | -0.0633 | 6.31446 |
July | 497.00000 | 24.64772 | 56.16515 | -0.0389 | 6.77828 |
August | 514.00000 | 24.49599 | 56.69454 | -0.1078 | 6.48878 |
September | 485.00000 | 24.48535 | 56.34322 | -0.1531 | 6.70042 |
October | 502.00000 | 24.12242 | 49.68548 | 0.49708 | 10.98910 |
November | 489.00000 | 23.19692 | 44.74729 | 0.18262 | 7.23064 |
December | 497.00000 | 21.89412 | 41.92745 | -0.1997 | 7.76607 |
Annual Sum or Average | 5943.00000 | 23.69980 | 49.13451 | 0.05831 | 8.01111 |
Minimum of Months | 454.00000 | 21.54197 | 41.92745 | -0.2885 | 6.31446 |
Maximum of Months | 514.00000 | 24.64772 | 56.69454 | 0.58324 | 12.84226 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.96264 | 43.69278 | -0.1687 | 7.69985 |
February | 454.00000 | 23.08135 | 42.44139 | 0.14577 | 7.60882 |
March | 514.00000 | 23.96053 | 43.61846 | 0.44393 | 10.47529 |
April | 485.00000 | 24.49933 | 44.73580 | 0.66856 | 15.40318 |
May | 508.00000 | 24.60043 | 51.20095 | 0.00972 | 6.86024 |
June | 496.00000 | 24.53247 | 54.38389 | -0.0082 | 6.47197 |
July | 497.00000 | 24.65722 | 56.11647 | -0.0002 | 7.04221 |
August | 514.00000 | 24.50122 | 56.67182 | -0.0746 | 6.55735 |
September | 485.00000 | 24.49046 | 56.25327 | -0.1055 | 6.64227 |
October | 502.00000 | 24.25586 | 49.15839 | 0.56999 | 13.01099 |
November | 489.00000 | 23.52094 | 43.68022 | 0.28853 | 8.43210 |
December | 497.00000 | 22.36713 | 40.94725 | -0.0713 | 7.22238 |
Annual Sum or Average | 5943.00000 | 23.87481 | 48.62752 | 0.14083 | 8.61618 |
Minimum of Months | 454.00000 | 21.96264 | 40.94725 | -0.1687 | 6.47197 |
Maximum of Months | 514.00000 | 24.65722 | 56.67182 | 0.66856 | 15.40318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.67394 | 41.03864 | 0.02308 | 8.65208 |
February | 454.00000 | 23.40332 | 41.05398 | 0.24756 | 9.42374 |
March | 514.00000 | 24.00491 | 43.23613 | 0.46732 | 11.24309 |
April | 485.00000 | 24.46557 | 44.76519 | 0.63401 | 14.41271 |
May | 508.00000 | 24.56553 | 51.34149 | -0.0713 | 6.58197 |
June | 496.00000 | 24.51849 | 54.48610 | -0.0670 | 6.33344 |
July | 497.00000 | 24.64447 | 56.16352 | -0.0379 | 6.80399 |
August | 514.00000 | 24.50528 | 56.60015 | -0.0914 | 6.54895 |
September | 485.00000 | 24.52583 | 56.01075 | -0.0929 | 6.72826 |
October | 502.00000 | 24.37155 | 48.51382 | 0.63357 | 15.03453 |
November | 489.00000 | 23.88968 | 42.04992 | 0.43154 | 11.63234 |
December | 497.00000 | 23.10327 | 38.32420 | 0.13357 | 8.96660 |
Annual Sum or Average | 5943.00000 | 24.06026 | 47.85721 | 0.18288 | 9.35197 |
Minimum of Months | 454.00000 | 22.67394 | 38.32420 | -0.0929 | 6.33344 |
Maximum of Months | 514.00000 | 24.64447 | 56.60015 | 0.63401 | 15.03453 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79320 | 43.68160 | -0.2094 | 8.69480 |
February | 454.00000 | 22.75303 | 43.03082 | 0.07117 | 7.95468 |
March | 514.00000 | 23.76323 | 44.08208 | 0.39718 | 10.08942 |
April | 485.00000 | 24.42392 | 44.94455 | 0.64411 | 14.88936 |
May | 508.00000 | 24.56837 | 51.32189 | -0.0161 | 7.05641 |
June | 496.00000 | 24.52443 | 54.44841 | -0.0057 | 6.71588 |
July | 497.00000 | 24.63142 | 56.24234 | -0.0154 | 7.04975 |
August | 514.00000 | 24.48448 | 56.77019 | -0.0835 | 6.62883 |
September | 485.00000 | 24.46869 | 56.36274 | -0.1136 | 6.84617 |
October | 502.00000 | 24.12418 | 49.52086 | 0.53733 | 12.46768 |
November | 489.00000 | 23.25171 | 44.21330 | 0.23222 | 8.42532 |
December | 497.00000 | 22.09950 | 41.09924 | -0.1299 | 8.01131 |
Annual Sum or Average | 5943.00000 | 23.74774 | 48.85962 | 0.10865 | 8.73144 |
Minimum of Months | 454.00000 | 21.79320 | 41.09924 | -0.2094 | 6.62883 |
Maximum of Months | 514.00000 | 24.63142 | 56.77019 | 0.64411 | 14.88936 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36849 | 43.59792 | -0.0717 | 6.12962 |
February | 454.00000 | 23.10905 | 44.06120 | 0.13118 | 6.42510 |
March | 514.00000 | 23.86543 | 46.06267 | 0.36545 | 8.28885 |
April | 485.00000 | 24.34444 | 45.16482 | 0.53198 | 11.26324 |
May | 508.00000 | 24.52350 | 50.06056 | -0.1532 | 6.38741 |
June | 496.00000 | 24.50513 | 52.36446 | -0.1147 | 6.19212 |
July | 497.00000 | 24.65211 | 53.55818 | -0.0597 | 6.52022 |
August | 514.00000 | 24.52611 | 53.75571 | -0.1053 | 6.33065 |
September | 485.00000 | 24.55670 | 53.67263 | -0.1278 | 6.42734 |
October | 502.00000 | 24.37676 | 49.61083 | 0.57149 | 12.14631 |
November | 489.00000 | 23.89024 | 45.02058 | 0.36529 | 8.18326 |
December | 497.00000 | 22.95180 | 41.14235 | 0.06993 | 5.92565 |
Annual Sum or Average | 5943.00000 | 23.97810 | 48.21170 | 0.11597 | 7.51963 |
Minimum of Months | 454.00000 | 22.36849 | 41.14235 | -0.1532 | 5.92565 |
Maximum of Months | 514.00000 | 24.65211 | 53.75571 | 0.57149 | 12.14631 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90261 | 42.59032 | 0.07252 | 6.16132 |
February | 454.00000 | 23.56934 | 42.60662 | 0.26696 | 7.54686 |
March | 514.00000 | 24.09194 | 44.97821 | 0.46458 | 10.18505 |
April | 485.00000 | 24.49663 | 44.49419 | 0.63169 | 14.02946 |
May | 508.00000 | 24.59577 | 49.70726 | -0.0456 | 6.39740 |
June | 496.00000 | 24.53338 | 52.19380 | -0.0513 | 6.18776 |
July | 497.00000 | 24.67138 | 53.49459 | -0.0163 | 6.70982 |
August | 514.00000 | 24.54185 | 53.71549 | -0.0675 | 6.34792 |
September | 485.00000 | 24.58028 | 53.52586 | -0.0730 | 6.31856 |
October | 502.00000 | 24.50818 | 49.04124 | 0.64648 | 14.36004 |
November | 489.00000 | 24.13165 | 44.00514 | 0.45767 | 9.91711 |
December | 497.00000 | 23.38897 | 39.87993 | 0.19240 | 6.61260 |
Annual Sum or Average | 5943.00000 | 24.17135 | 47.56450 | 0.20527 | 8.39382 |
Minimum of Months | 454.00000 | 22.90261 | 39.87993 | -0.0730 | 6.16132 |
Maximum of Months | 514.00000 | 24.67138 | 53.71549 | 0.64648 | 14.36004 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.09913 | 40.07698 | 0.17273 | 7.80145 |
February | 454.00000 | 23.67973 | 41.40725 | 0.33558 | 9.38600 |
March | 514.00000 | 24.11220 | 44.14744 | 0.48534 | 11.00445 |
April | 485.00000 | 24.62008 | 44.05798 | 0.62604 | 13.99194 |
May | 508.00000 | 24.84126 | 51.37790 | -0.0424 | 6.55692 |
June | 496.00000 | 24.81142 | 55.79433 | -0.0069 | 6.44359 |
July | 497.00000 | 24.81250 | 59.61925 | 0.03169 | 6.53218 |
August | 514.00000 | 24.67084 | 61.15617 | 0.00425 | 6.26538 |
September | 485.00000 | 24.76685 | 58.60977 | 0.02189 | 6.40495 |
October | 502.00000 | 24.78364 | 49.36910 | 0.75566 | 18.04789 |
November | 489.00000 | 24.35284 | 42.39527 | 0.57960 | 13.42533 |
December | 497.00000 | 23.69594 | 37.70034 | 0.32237 | 9.04410 |
Annual Sum or Average | 5943.00000 | 24.35772 | 48.88000 | 0.27238 | 9.56421 |
Minimum of Months | 454.00000 | 23.09913 | 37.70034 | -0.0424 | 6.26538 |
Maximum of Months | 514.00000 | 24.84126 | 61.15617 | 0.75566 | 18.04789 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.68491 | 42.77750 | 0.02403 | 6.33219 |
February | 454.00000 | 23.34496 | 43.12600 | 0.21224 | 7.32285 |
March | 514.00000 | 24.01324 | 45.28354 | 0.44169 | 9.81865 |
April | 485.00000 | 24.46673 | 44.68567 | 0.61834 | 13.66657 |
May | 508.00000 | 24.58452 | 49.83904 | -0.0638 | 6.49481 |
June | 496.00000 | 24.54692 | 52.21760 | -0.0411 | 6.33881 |
July | 497.00000 | 24.66572 | 53.57469 | -0.0251 | 6.70954 |
August | 514.00000 | 24.54262 | 53.77971 | -0.0710 | 6.39120 |
September | 485.00000 | 24.59293 | 53.59033 | -0.0707 | 6.42067 |
October | 502.00000 | 24.48131 | 49.21649 | 0.63510 | 14.04621 |
November | 489.00000 | 24.05929 | 44.22474 | 0.43982 | 9.67304 |
December | 497.00000 | 23.18631 | 40.16330 | 0.14745 | 6.47887 |
Annual Sum or Average | 5943.00000 | 24.10220 | 47.74935 | 0.18618 | 8.30504 |
Minimum of Months | 454.00000 | 22.68491 | 40.16330 | -0.0710 | 6.33219 |
Maximum of Months | 514.00000 | 24.66572 | 53.77971 | 0.63510 | 14.04621 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.19292 | 43.91277 | -0.1172 | 6.64476 |
February | 454.00000 | 23.18461 | 43.30679 | 0.15133 | 6.74417 |
March | 514.00000 | 23.99806 | 45.00739 | 0.41104 | 9.06343 |
April | 485.00000 | 24.44865 | 45.44936 | 0.58252 | 12.59905 |
May | 508.00000 | 24.57487 | 51.46906 | -0.1075 | 6.41718 |
June | 496.00000 | 24.52410 | 54.42037 | -0.0932 | 6.24430 |
July | 497.00000 | 24.64852 | 55.93944 | -0.0640 | 6.65309 |
August | 514.00000 | 24.49555 | 56.44414 | -0.1278 | 6.43551 |
September | 485.00000 | 24.51295 | 56.21324 | -0.1564 | 6.63503 |
October | 502.00000 | 24.28411 | 50.03434 | 0.53655 | 11.42533 |
November | 489.00000 | 23.67430 | 44.69095 | 0.30158 | 7.58733 |
December | 497.00000 | 22.61146 | 41.36720 | -0.0175 | 6.24475 |
Annual Sum or Average | 5943.00000 | 23.93443 | 49.07105 | 0.10728 | 7.72431 |
Minimum of Months | 454.00000 | 22.19292 | 41.36720 | -0.1564 | 6.24430 |
Maximum of Months | 514.00000 | 24.64852 | 56.44414 | 0.58252 | 12.59905 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.39632 | 43.04286 | -0.0539 | 6.48174 |
February | 385.00000 | 23.39061 | 41.87467 | 0.21796 | 7.49269 |
March | 433.00000 | 24.13388 | 43.59486 | 0.46752 | 10.52050 |
April | 410.00000 | 24.62142 | 44.16333 | 0.65830 | 15.03338 |
May | 430.00000 | 24.71144 | 50.80498 | -0.0140 | 6.87996 |
June | 418.00000 | 24.62607 | 54.02476 | -0.0350 | 6.48318 |
July | 422.00000 | 24.76886 | 55.69021 | -0.0111 | 7.07841 |
August | 433.00000 | 24.59008 | 56.26041 | -0.0878 | 6.63377 |
September | 410.00000 | 24.60497 | 56.00648 | -0.1051 | 6.68854 |
October | 427.00000 | 24.44406 | 48.95762 | 0.59384 | 13.30736 |
November | 417.00000 | 23.82792 | 43.26424 | 0.35570 | 8.69489 |
December | 422.00000 | 22.81716 | 40.14228 | 0.04377 | 6.42536 |
Annual Sum or Average | 5034.00000 | 24.08099 | 48.19704 | 0.16830 | 8.47460 |
Minimum of Months | 385.00000 | 22.39632 | 40.14228 | -0.1051 | 6.42536 |
Maximum of Months | 433.00000 | 24.76886 | 56.26041 | 0.65830 | 15.03338 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19852 | 40.28034 | 0.16586 | 7.88391 |
February | 454.00000 | 23.80124 | 40.82586 | 0.35095 | 9.53125 |
March | 514.00000 | 24.19655 | 43.86000 | 0.51477 | 11.54356 |
April | 485.00000 | 24.51564 | 45.06297 | 0.63343 | 14.13306 |
May | 508.00000 | 24.57537 | 51.42181 | -0.0968 | 6.43663 |
June | 496.00000 | 24.51878 | 54.43467 | -0.0969 | 6.26096 |
July | 497.00000 | 24.64539 | 55.93579 | -0.0631 | 6.66724 |
August | 514.00000 | 24.50657 | 56.33620 | -0.1114 | 6.46779 |
September | 485.00000 | 24.55291 | 55.85730 | -0.0979 | 6.58548 |
October | 502.00000 | 24.51371 | 48.81985 | 0.66650 | 15.42541 |
November | 489.00000 | 24.21052 | 42.17946 | 0.51678 | 12.23182 |
December | 497.00000 | 23.60753 | 37.85156 | 0.27103 | 8.74375 |
Annual Sum or Average | 5943.00000 | 24.23947 | 47.79915 | 0.21926 | 9.31359 |
Minimum of Months | 454.00000 | 23.19852 | 37.85156 | -0.1114 | 6.26096 |
Maximum of Months | 514.00000 | 24.64539 | 56.33620 | 0.66650 | 15.42541 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.34646 | 43.16358 | -0.0578 | 6.94792 |
February | 454.00000 | 23.22562 | 42.73037 | 0.19041 | 7.62482 |
March | 514.00000 | 24.01054 | 44.66381 | 0.45643 | 10.37206 |
April | 485.00000 | 24.48284 | 45.25317 | 0.64575 | 14.60144 |
May | 508.00000 | 24.58392 | 51.40083 | -0.0402 | 6.74621 |
June | 496.00000 | 24.52978 | 54.38635 | -0.0345 | 6.48050 |
July | 497.00000 | 24.63815 | 56.00588 | -0.0389 | 6.83517 |
August | 514.00000 | 24.49031 | 56.51446 | -0.1020 | 6.49674 |
September | 485.00000 | 24.51339 | 56.20213 | -0.1134 | 6.61853 |
October | 502.00000 | 24.30872 | 49.82809 | 0.58011 | 12.88522 |
November | 489.00000 | 23.70517 | 44.16665 | 0.34510 | 8.72523 |
December | 497.00000 | 22.70037 | 40.53727 | 0.02797 | 6.71260 |
Annual Sum or Average | 5943.00000 | 23.96642 | 48.79010 | 0.15392 | 8.41687 |
Minimum of Months | 454.00000 | 22.34646 | 40.53727 | -0.1134 | 6.48050 |
Maximum of Months | 514.00000 | 24.63815 | 56.51446 | 0.64575 | 14.60144 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.198780E+11 | 0.477661E+10 | 368.07 | 0.172309E+11 | 0.264708E+10 | 0.00 | 0.90 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 35996.60 | 12-JAN-15:10 | 35996.60 | 12-JAN-15:10 | 7029.25 | 17-JAN-17:08 | 7785.51 | 12-JAN-15:10 | 0.00 |
February | 0.296233E+11 | 0.683998E+10 | 366.44 | 0.265834E+11 | 0.303998E+10 | 0.00 | 1.00 | 21-FEB-11:20 | 0.00 | 01-FEB-00:10 | 51113.11 | 22-FEB-15:30 | 51113.11 | 22-FEB-15:30 | 8540.64 | 25-FEB-17:10 | 11564.75 | 22-FEB-15:10 | 0.00 |
March | 0.549596E+11 | 0.129771E+11 | 442.01 | 0.514321E+11 | 0.352746E+10 | 0.00 | 1.00 | 01-MAR-14:10 | 0.00 | 01-MAR-00:10 | 71151.60 | 29-MAR-11:10 | 69108.18 | 28-MAR-16:00 | 19539.85 | 10-MAR-17:20 | 19852.63 | 28-MAR-15:50 | 0.00 |
April | 0.779604E+11 | 0.207224E+11 | 448.66 | 0.732578E+11 | 0.470260E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 99220.30 | 27-APR-06:03 | 83277.39 | 28-APR-04:02 | 26109.10 | 26-APR-06:03 | 26773.91 | 26-APR-15:50 | 0.00 |
May | 0.113244E+12 | 0.319145E+11 | 518.16 | 0.953769E+11 | 0.178667E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:03 | 129225.70 | 19-MAY-04:02 | 97175.57 | 31-MAY-04:02 | 48869.72 | 24-MAY-04:02 | 33793.48 | 01-MAY-15:20 | 0.00 |
June | 0.128505E+12 | 0.353107E+11 | 517.23 | 0.969860E+11 | 0.315189E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 132524.30 | 27-JUN-04:02 | 99910.90 | 12-JUN-06:03 | 58373.52 | 28-JUN-12:02 | 35479.77 | 12-JUN-16:00 | 0.00 |
July | 0.139627E+12 | 0.349287E+11 | 527.38 | 0.897100E+11 | 0.499173E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:03 | 133972.69 | 20-JUL-04:02 | 89786.81 | 01-JUL-04:02 | 58502.93 | 18-JUL-06:07 | 35209.99 | 02-JUL-13:23 | 0.00 |
August | 0.142204E+12 | 0.343444E+11 | 513.68 | 0.886068E+11 | 0.535970E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 135203.92 | 27-AUG-16:52 | 88739.00 | 03-AUG-06:03 | 62109.41 | 27-AUG-14:12 | 34197.77 | 27-AUG-14:12 | 0.00 |
September | 0.114951E+12 | 0.275228E+11 | 467.49 | 0.772008E+11 | 0.377498E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 132370.42 | 06-SEP-04:02 | 89591.75 | 18-SEP-04:02 | 54226.83 | 13-SEP-06:03 | 31040.26 | 17-SEP-17:02 | 0.00 |
October | 0.789890E+11 | 0.189752E+11 | 457.86 | 0.680651E+11 | 0.109239E+11 | 0.00 | 1.00 | 01-OCT-10:02 | 0.00 | 01-OCT-00:10 | 114235.24 | 04-OCT-04:02 | 82163.47 | 02-OCT-05:12 | 35993.17 | 04-OCT-04:02 | 25440.56 | 02-OCT-15:00 | 0.00 |
November | 0.484901E+11 | 0.111017E+11 | 411.75 | 0.451458E+11 | 0.334431E+10 | 0.00 | 1.00 | 01-NOV-09:40 | 0.00 | 01-NOV-00:10 | 65628.14 | 06-NOV-11:30 | 60340.10 | 13-NOV-15:10 | 12112.35 | 06-NOV-11:30 | 15127.90 | 08-NOV-15:30 | 0.00 |
December | 0.255024E+11 | 0.600924E+10 | 395.55 | 0.230083E+11 | 0.249405E+10 | 0.00 | 1.00 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 43242.35 | 01-DEC-15:20 | 43242.35 | 01-DEC-15:20 | 6729.41 | 29-DEC-18:15 | 9080.26 | 01-DEC-15:20 | 0.00 |
Annual Sum or Average | 0.973933E+12 | 0.245423E+12 | 5434.29 | 0.752604E+12 | 0.221329E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.198780E+11 | 0.477661E+10 | 366.44 | 0.172309E+11 | 0.249405E+10 | 0.00 | 0.90 | 0.00 | 35996.60 | 35996.60 | 6729.41 | 7785.51 | 0.00 | ||||||
Maximum of Months | 0.142204E+12 | 0.353107E+11 | 527.38 | 0.969860E+11 | 0.535970E+11 | 0.00 | 1.00 | 0.00 | 135203.92 | 99910.90 | 62109.41 | 35479.77 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.145409E+11 | 0.356900E+10 | 346.39 | 0.119031E+11 | 0.263773E+10 | 0.00 | 0.77 | 12-JAN-15:20 | 0.00 | 01-JAN-00:10 | 27965.54 | 12-JAN-15:20 | 27965.54 | 12-JAN-15:20 | 6383.33 | 17-JAN-15:00 | 6280.58 | 12-JAN-15:20 | 0.00 |
February | 0.237519E+11 | 0.557886E+10 | 361.61 | 0.204808E+11 | 0.327105E+10 | 0.00 | 1.00 | 21-FEB-13:40 | 0.00 | 01-FEB-00:10 | 44203.41 | 22-FEB-15:30 | 44203.41 | 22-FEB-15:30 | 8115.37 | 25-FEB-17:00 | 10005.93 | 22-FEB-15:10 | 0.00 |
March | 0.482772E+11 | 0.114993E+11 | 446.50 | 0.446103E+11 | 0.366697E+10 | 0.00 | 1.00 | 01-MAR-15:10 | 0.00 | 01-MAR-00:10 | 66005.50 | 28-MAR-16:00 | 66005.50 | 28-MAR-16:00 | 10855.40 | 10-MAR-20:50 | 18912.82 | 28-MAR-16:00 | 0.00 |
April | 0.714256E+11 | 0.190071E+11 | 451.47 | 0.676348E+11 | 0.379083E+10 | 0.00 | 1.00 | 01-APR-12:50 | 0.00 | 01-APR-00:10 | 104322.09 | 27-APR-04:02 | 85969.30 | 17-APR-04:02 | 26300.25 | 27-APR-04:02 | 28564.17 | 16-APR-15:22 | 0.00 |
May | 0.102939E+12 | 0.289071E+11 | 520.91 | 0.877288E+11 | 0.152104E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:23 | 123433.61 | 24-MAY-05:03 | 91340.33 | 30-MAY-06:03 | 51600.92 | 24-MAY-04:02 | 32580.36 | 01-MAY-15:10 | 0.00 |
June | 0.113638E+12 | 0.310383E+11 | 511.80 | 0.863684E+11 | 0.272692E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 126469.03 | 26-JUN-04:02 | 97523.84 | 12-JUN-06:03 | 50494.00 | 27-JUN-06:03 | 36769.30 | 11-JUN-15:02 | 0.00 |
July | 0.119723E+12 | 0.297503E+11 | 508.04 | 0.762031E+11 | 0.435201E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:03 | 128167.74 | 20-JUL-04:02 | 85527.28 | 05-JUL-06:03 | 57505.46 | 27-JUL-04:02 | 35555.93 | 02-JUL-16:21 | 0.00 |
August | 0.117474E+12 | 0.281773E+11 | 490.38 | 0.720575E+11 | 0.454163E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 126699.74 | 19-AUG-05:03 | 82880.79 | 07-AUG-06:03 | 54427.83 | 19-AUG-05:03 | 29912.35 | 06-AUG-14:52 | 0.00 |
September | 0.935447E+11 | 0.222917E+11 | 443.90 | 0.618495E+11 | 0.316952E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 126552.43 | 11-SEP-04:02 | 83424.62 | 25-SEP-04:02 | 53174.27 | 11-SEP-04:02 | 31826.17 | 17-SEP-17:12 | 0.00 |
October | 0.632654E+11 | 0.153540E+11 | 438.00 | 0.541002E+11 | 0.916524E+10 | 0.00 | 1.00 | 01-OCT-08:53 | 0.00 | 01-OCT-00:10 | 86554.13 | 04-OCT-05:03 | 73182.03 | 01-OCT-14:51 | 27654.82 | 04-OCT-04:02 | 23094.42 | 02-OCT-15:00 | 0.00 |
November | 0.375308E+11 | 0.877162E+10 | 407.14 | 0.338978E+11 | 0.363296E+10 | 0.00 | 1.00 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 | 54198.85 | 06-NOV-14:00 | 50032.54 | 08-NOV-15:10 | 8619.70 | 08-NOV-19:20 | 12882.82 | 06-NOV-14:00 | 0.00 |
December | 0.183167E+11 | 0.442960E+10 | 382.50 | 0.154441E+11 | 0.287253E+10 | 0.00 | 0.89 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 33627.77 | 01-DEC-15:10 | 33627.77 | 01-DEC-15:10 | 5782.59 | 29-DEC-18:00 | 7293.12 | 01-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.824427E+12 | 0.208374E+12 | 5308.64 | 0.632279E+12 | 0.192148E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.145409E+11 | 0.356900E+10 | 346.39 | 0.119031E+11 | 0.263773E+10 | 0.00 | 0.77 | 0.00 | 27965.54 | 27965.54 | 5782.59 | 6280.58 | 0.00 | ||||||
Maximum of Months | 0.119723E+12 | 0.310383E+11 | 520.91 | 0.877288E+11 | 0.454163E+11 | 0.00 | 1.00 | 0.00 | 128167.74 | 97523.84 | 57505.46 | 36769.30 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.152365E+11 | 0.375279E+10 | 329.84 | 0.122237E+11 | 0.301280E+10 | 0.00 | 0.72 | 12-JAN-15:30 | 0.00 | 01-JAN-00:10 | 29664.36 | 12-JAN-15:30 | 29664.36 | 12-JAN-15:30 | 7051.81 | 17-JAN-15:00 | 6756.43 | 12-JAN-15:30 | 0.00 |
February | 0.245967E+11 | 0.582295E+10 | 349.10 | 0.208468E+11 | 0.374992E+10 | 0.00 | 1.00 | 20-FEB-16:23 | 0.00 | 01-FEB-00:10 | 50924.27 | 22-FEB-15:00 | 50924.27 | 22-FEB-15:00 | 8770.80 | 25-FEB-17:00 | 11597.96 | 22-FEB-15:00 | 0.00 |
March | 0.518000E+11 | 0.124609E+11 | 445.89 | 0.472314E+11 | 0.456852E+10 | 0.00 | 1.00 | 03-MAR-14:00 | 0.00 | 01-MAR-00:10 | 79206.77 | 28-MAR-16:00 | 79206.77 | 28-MAR-16:00 | 12172.81 | 10-MAR-20:20 | 22568.50 | 28-MAR-16:00 | 0.00 |
April | 0.794057E+11 | 0.213148E+11 | 454.31 | 0.751171E+11 | 0.428854E+10 | 0.00 | 1.00 | 01-APR-12:30 | 0.00 | 01-APR-00:10 | 117144.46 | 16-APR-16:42 | 107410.99 | 16-APR-14:42 | 15045.97 | 17-APR-09:40 | 35179.64 | 16-APR-15:22 | 0.00 |
May | 0.114243E+12 | 0.322900E+11 | 525.63 | 0.985535E+11 | 0.156893E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:23 | 141152.02 | 17-MAY-04:02 | 112974.99 | 29-MAY-16:11 | 54905.28 | 24-MAY-04:02 | 38846.67 | 28-MAY-15:12 | 0.00 |
June | 0.125484E+12 | 0.345083E+11 | 519.15 | 0.976808E+11 | 0.278028E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 145582.25 | 27-JUN-04:02 | 112524.98 | 11-JUN-16:11 | 59268.82 | 29-JUN-04:02 | 43648.84 | 11-JUN-15:31 | 0.00 |
July | 0.129191E+12 | 0.322193E+11 | 520.56 | 0.846503E+11 | 0.445410E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:23 | 148080.89 | 20-JUL-04:02 | 105981.97 | 04-JUL-16:02 | 66134.06 | 25-JUL-04:02 | 40999.66 | 02-JUL-15:51 | 0.00 |
August | 0.124525E+12 | 0.299663E+11 | 496.31 | 0.786269E+11 | 0.458981E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 145959.55 | 10-AUG-04:02 | 98342.82 | 06-AUG-15:21 | 57745.44 | 13-AUG-15:32 | 37842.19 | 06-AUG-15:21 | 0.00 |
September | 0.975069E+11 | 0.233842E+11 | 443.14 | 0.658051E+11 | 0.317018E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 143304.36 | 05-SEP-04:02 | 95151.46 | 05-SEP-04:02 | 58916.18 | 01-SEP-04:02 | 32488.49 | 17-SEP-15:22 | 0.00 |
October | 0.661618E+11 | 0.162378E+11 | 436.00 | 0.565918E+11 | 0.956994E+10 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 93541.55 | 09-OCT-14:21 | 93541.55 | 09-OCT-14:21 | 24245.86 | 04-OCT-05:03 | 26306.99 | 02-OCT-14:50 | 0.00 |
November | 0.381615E+11 | 0.903908E+10 | 402.77 | 0.338991E+11 | 0.426242E+10 | 0.00 | 1.00 | 01-NOV-12:05 | 0.00 | 01-NOV-00:10 | 59712.32 | 09-NOV-13:30 | 58046.89 | 09-NOV-14:50 | 9785.78 | 08-NOV-18:40 | 14284.67 | 09-NOV-13:30 | 0.00 |
December | 0.183083E+11 | 0.445988E+10 | 361.01 | 0.149478E+11 | 0.336049E+10 | 0.00 | 0.84 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 36183.57 | 01-DEC-14:50 | 36183.57 | 01-DEC-14:50 | 6321.21 | 29-DEC-17:00 | 7954.91 | 01-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.884620E+12 | 0.225456E+12 | 5283.70 | 0.686174E+12 | 0.198446E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.152365E+11 | 0.375279E+10 | 329.84 | 0.122237E+11 | 0.301280E+10 | 0.00 | 0.72 | 0.00 | 29664.36 | 29664.36 | 6321.21 | 6756.43 | 0.00 | ||||||
Maximum of Months | 0.129191E+12 | 0.345083E+11 | 525.63 | 0.985535E+11 | 0.458981E+11 | 0.00 | 1.00 | 0.00 | 148080.89 | 112974.99 | 66134.06 | 43648.84 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.18 | 0.00 | 342.18 | 235.35 | 1175.62 | 23.33 | 0.00 | 0.00 |
February | 405.77 | 0.00 | 405.77 | 416.01 | 939.44 | 0.00 | 0.00 | 0.00 |
March | 488.95 | 0.00 | 488.95 | 761.42 | 571.74 | 0.00 | 0.00 | 0.00 |
April | 530.55 | 1.80 | 528.75 | 1319.34 | 207.14 | 0.00 | 0.00 | 0.00 |
May | 587.82 | 16.50 | 571.32 | 1835.83 | 39.18 | 0.00 | 0.00 | 0.00 |
June | 608.48 | 22.54 | 585.94 | 1995.32 | 29.68 | 0.00 | 0.00 | 0.00 |
July | 600.10 | 9.50 | 590.60 | 1766.63 | 6.39 | 0.00 | 0.00 | 0.00 |
August | 550.91 | 1.72 | 549.20 | 1486.73 | 21.38 | 0.00 | 0.00 | 0.00 |
September | 490.88 | 0.03 | 490.84 | 1156.59 | 86.22 | 0.00 | 0.00 | 0.00 |
October | 425.26 | 0.00 | 425.26 | 847.13 | 446.51 | 0.00 | 0.00 | 0.00 |
November | 360.20 | 0.00 | 360.20 | 477.47 | 840.07 | 0.00 | 0.00 | 0.00 |
December | 333.80 | 0.00 | 333.80 | 260.43 | 1153.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 477.44 | 4.36 | 473.08 | 1049.61 | 457.64 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 333.80 | 0.00 | 333.80 | 235.35 | 6.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.48 | 22.54 | 590.60 | 1995.32 | 1175.62 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.68 | 196.15 | 292.53 | 533.28 | 723.40 | 21.33 | 0.00 | 0.00 |
February | 593.69 | 245.10 | 348.58 | 782.89 | 590.51 | 0.00 | 0.00 | 0.00 |
March | 724.23 | 298.94 | 425.30 | 1182.21 | 366.93 | 0.00 | 0.00 | 0.00 |
April | 861.65 | 401.75 | 459.90 | 1769.30 | 139.50 | 0.00 | 0.00 | 0.00 |
May | 848.10 | 376.00 | 472.10 | 2021.71 | 25.71 | 0.00 | 0.00 | 0.00 |
June | 690.24 | 229.02 | 461.22 | 1832.80 | 19.84 | 0.00 | 0.00 | 0.00 |
July | 580.13 | 122.51 | 457.62 | 1499.04 | 3.79 | 0.00 | 0.00 | 0.00 |
August | 522.72 | 90.97 | 431.76 | 1265.75 | 14.44 | 0.00 | 0.00 | 0.00 |
September | 558.47 | 155.74 | 402.73 | 1177.93 | 57.69 | 0.00 | 0.00 | 0.00 |
October | 610.90 | 246.76 | 364.14 | 1138.99 | 292.07 | 0.00 | 0.00 | 0.00 |
November | 541.65 | 232.50 | 309.15 | 817.54 | 534.05 | 0.00 | 0.00 | 0.00 |
December | 472.30 | 187.13 | 285.17 | 554.21 | 725.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 624.23 | 231.52 | 392.70 | 1216.16 | 289.83 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 472.30 | 90.97 | 285.17 | 533.28 | 3.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.65 | 401.75 | 472.10 | 2021.71 | 725.91 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1556.24 | 945.61 | 610.63 | 2164.05 | 1128.00 | 21.33 | 0.00 | 0.00 |
February | 1479.75 | 821.90 | 657.86 | 2225.83 | 936.21 | 0.00 | 0.00 | 0.00 |
March | 1265.23 | 558.84 | 706.39 | 2225.76 | 589.10 | 0.00 | 0.00 | 0.00 |
April | 888.70 | 250.82 | 637.88 | 2100.13 | 220.05 | 0.00 | 0.00 | 0.00 |
May | 639.09 | 47.31 | 591.78 | 1965.82 | 37.92 | 0.00 | 0.00 | 0.00 |
June | 584.60 | 9.98 | 574.63 | 1949.69 | 29.49 | 0.00 | 0.00 | 0.00 |
July | 609.80 | 8.39 | 601.41 | 1795.53 | 5.68 | 0.00 | 0.00 | 0.00 |
August | 646.87 | 34.55 | 612.32 | 1684.79 | 21.90 | 0.00 | 0.00 | 0.00 |
September | 867.18 | 225.08 | 642.10 | 1885.50 | 92.09 | 0.00 | 0.00 | 0.00 |
October | 1491.89 | 833.06 | 658.82 | 2793.84 | 468.97 | 0.00 | 0.00 | 0.00 |
November | 1863.45 | 1231.70 | 631.75 | 3049.95 | 857.47 | 0.00 | 0.00 | 0.00 |
December | 1663.08 | 1042.13 | 620.95 | 2400.80 | 1129.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1127.64 | 498.92 | 628.72 | 2185.84 | 457.54 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 584.60 | 8.39 | 574.63 | 1684.79 | 5.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1863.45 | 1231.70 | 706.39 | 3049.95 | 1129.61 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.10 | 186.06 | 292.04 | 575.97 | 782.60 | 23.33 | 0.00 | 0.00 |
February | 546.72 | 201.48 | 345.24 | 757.92 | 632.92 | 0.00 | 0.00 | 0.00 |
March | 708.95 | 283.39 | 425.56 | 1184.61 | 393.90 | 0.00 | 0.00 | 0.00 |
April | 861.72 | 404.11 | 457.61 | 1778.62 | 149.41 | 0.00 | 0.00 | 0.00 |
May | 815.97 | 346.12 | 469.85 | 1973.04 | 29.23 | 0.00 | 0.00 | 0.00 |
June | 766.41 | 297.70 | 468.72 | 1968.87 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 568.72 | 110.62 | 458.10 | 1472.29 | 4.52 | 0.00 | 0.00 | 0.00 |
August | 522.31 | 92.83 | 429.48 | 1267.28 | 14.90 | 0.00 | 0.00 | 0.00 |
September | 574.15 | 168.56 | 405.60 | 1209.22 | 61.48 | 0.00 | 0.00 | 0.00 |
October | 597.61 | 237.97 | 359.64 | 1137.49 | 308.35 | 0.00 | 0.00 | 0.00 |
November | 540.63 | 230.41 | 310.22 | 865.27 | 569.79 | 0.00 | 0.00 | 0.00 |
December | 462.62 | 176.41 | 286.21 | 579.75 | 763.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.21 | 227.67 | 392.54 | 1232.29 | 309.56 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 462.62 | 92.83 | 286.21 | 575.97 | 4.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.72 | 404.11 | 469.85 | 1973.04 | 782.60 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 69.15 | 444.64 | 24.00 | 0.00 | 0.00 |
February | 135.25 | 0.00 | 135.25 | 135.99 | 338.06 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 259.74 | 194.03 | 0.00 | 0.00 | 0.00 |
April | 176.84 | 0.60 | 176.24 | 451.23 | 64.80 | 0.00 | 0.00 | 0.00 |
May | 195.93 | 5.50 | 190.43 | 622.07 | 11.00 | 0.00 | 0.00 | 0.00 |
June | 202.82 | 7.51 | 195.31 | 670.69 | 9.35 | 0.00 | 0.00 | 0.00 |
July | 200.02 | 3.17 | 196.86 | 588.60 | 2.85 | 0.00 | 0.00 | 0.00 |
August | 183.63 | 0.57 | 183.06 | 491.52 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 380.86 | 36.08 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.07 | 166.10 | 0.00 | 0.00 | 0.00 |
November | 120.06 | 0.00 | 120.06 | 149.65 | 318.30 | 0.00 | 0.00 | 0.00 |
December | 111.26 | 0.00 | 111.26 | 73.21 | 443.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 348.59 | 169.13 | 24.00 | 0.00 | 0.00 |
Minimum of Months | 111.26 | 0.00 | 111.26 | 69.15 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.82 | 7.51 | 196.86 | 670.69 | 444.64 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 69.15 | 444.66 | 24.00 | 0.00 | 0.00 |
February | 135.26 | 0.00 | 135.26 | 136.00 | 338.08 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 259.75 | 194.03 | 0.00 | 0.00 | 0.00 |
April | 176.85 | 0.60 | 176.25 | 451.26 | 64.80 | 0.00 | 0.00 | 0.00 |
May | 195.94 | 5.50 | 190.44 | 622.11 | 11.00 | 0.00 | 0.00 | 0.00 |
June | 202.83 | 7.51 | 195.31 | 670.73 | 9.35 | 0.00 | 0.00 | 0.00 |
July | 200.03 | 3.17 | 196.86 | 588.63 | 2.85 | 0.00 | 0.00 | 0.00 |
August | 183.64 | 0.57 | 183.06 | 491.55 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 380.88 | 36.09 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.09 | 166.11 | 0.00 | 0.00 | 0.00 |
November | 120.07 | 0.00 | 120.07 | 149.66 | 318.32 | 0.00 | 0.00 | 0.00 |
December | 111.27 | 0.00 | 111.27 | 73.22 | 443.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 348.60 | 169.14 | 24.00 | 0.00 | 0.00 |
Minimum of Months | 111.27 | 0.00 | 111.27 | 69.15 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.83 | 7.51 | 196.86 | 670.73 | 444.66 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.06 | 0.00 | 114.06 | 69.15 | 444.66 | 24.00 | 0.00 | 0.00 |
February | 135.26 | 0.00 | 135.26 | 136.00 | 338.08 | 0.00 | 0.00 | 0.00 |
March | 162.98 | 0.00 | 162.98 | 259.75 | 194.03 | 0.00 | 0.00 | 0.00 |
April | 176.85 | 0.60 | 176.25 | 451.26 | 64.80 | 0.00 | 0.00 | 0.00 |
May | 195.94 | 5.50 | 190.44 | 622.11 | 11.00 | 0.00 | 0.00 | 0.00 |
June | 202.83 | 7.51 | 195.31 | 670.73 | 9.35 | 0.00 | 0.00 | 0.00 |
July | 200.03 | 3.17 | 196.86 | 588.63 | 2.85 | 0.00 | 0.00 | 0.00 |
August | 183.64 | 0.57 | 183.06 | 491.55 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 163.62 | 0.01 | 163.61 | 380.88 | 36.09 | 0.00 | 0.00 | 0.00 |
October | 141.75 | 0.00 | 141.75 | 278.09 | 166.11 | 0.00 | 0.00 | 0.00 |
November | 120.07 | 0.00 | 120.07 | 149.66 | 318.32 | 0.00 | 0.00 | 0.00 |
December | 111.27 | 0.00 | 111.27 | 73.22 | 443.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.14 | 1.45 | 157.69 | 348.60 | 169.14 | 24.00 | 0.00 | 0.00 |
Minimum of Months | 111.27 | 0.00 | 111.27 | 69.15 | 2.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.83 | 7.51 | 196.86 | 670.73 | 444.66 | 24.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 470.09 | 188.69 | 281.40 | 481.87 | 798.98 | 24.33 | 0.00 | 0.00 |
February | 571.10 | 235.77 | 335.32 | 743.83 | 623.31 | 0.00 | 0.00 | 0.00 |
March | 696.68 | 287.56 | 409.11 | 1148.66 | 368.07 | 0.00 | 0.00 | 0.00 |
April | 828.86 | 386.46 | 442.41 | 1723.31 | 133.68 | 0.00 | 0.00 | 0.00 |
May | 815.83 | 361.69 | 454.14 | 1961.52 | 23.87 | 0.00 | 0.00 | 0.00 |
June | 663.98 | 220.31 | 443.67 | 1772.30 | 19.19 | 0.00 | 0.00 | 0.00 |
July | 558.06 | 117.85 | 440.21 | 1438.90 | 5.34 | 0.00 | 0.00 | 0.00 |
August | 502.83 | 87.50 | 415.33 | 1209.38 | 19.44 | 0.00 | 0.00 | 0.00 |
September | 537.22 | 149.82 | 387.40 | 1125.27 | 72.80 | 0.00 | 0.00 | 0.00 |
October | 587.65 | 237.37 | 350.28 | 1087.92 | 319.33 | 0.00 | 0.00 | 0.00 |
November | 521.04 | 223.65 | 297.39 | 765.33 | 587.63 | 0.00 | 0.00 | 0.00 |
December | 454.33 | 180.01 | 274.32 | 496.42 | 808.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.47 | 222.71 | 377.76 | 1164.32 | 313.68 | 24.33 | 0.00 | 0.00 |
Minimum of Months | 454.33 | 87.50 | 274.32 | 481.87 | 5.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 828.86 | 386.46 | 454.14 | 1961.52 | 808.30 | 24.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.59 | 7.46 | 11.13 | 19.05 | 31.59 | 24.33 | 0.00 | 0.00 |
February | 22.58 | 9.32 | 13.26 | 29.41 | 24.65 | 0.00 | 0.00 | 0.00 |
March | 27.55 | 11.37 | 16.18 | 45.42 | 14.55 | 0.00 | 0.00 | 0.00 |
April | 32.77 | 15.28 | 17.49 | 68.14 | 5.29 | 0.00 | 0.00 | 0.00 |
May | 32.26 | 14.30 | 17.96 | 77.56 | 0.94 | 0.00 | 0.00 | 0.00 |
June | 26.25 | 8.71 | 17.54 | 70.08 | 0.76 | 0.00 | 0.00 | 0.00 |
July | 22.07 | 4.66 | 17.41 | 56.89 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 19.88 | 3.46 | 16.42 | 47.82 | 0.77 | 0.00 | 0.00 | 0.00 |
September | 21.24 | 5.92 | 15.32 | 44.49 | 2.88 | 0.00 | 0.00 | 0.00 |
October | 23.24 | 9.39 | 13.85 | 43.02 | 12.63 | 0.00 | 0.00 | 0.00 |
November | 20.60 | 8.84 | 11.76 | 30.26 | 23.23 | 0.00 | 0.00 | 0.00 |
December | 17.96 | 7.12 | 10.85 | 19.63 | 31.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.74 | 8.81 | 14.94 | 46.04 | 12.40 | 24.33 | 0.00 | 0.00 |
Minimum of Months | 17.96 | 3.46 | 10.85 | 19.05 | 0.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.77 | 15.28 | 17.96 | 77.56 | 31.96 | 24.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.74 | 315.20 | 203.54 | 716.38 | 433.66 | 21.33 | 0.00 | 0.00 |
February | 493.24 | 273.96 | 219.28 | 743.52 | 346.15 | 0.00 | 0.00 | 0.00 |
March | 421.74 | 186.28 | 235.46 | 749.05 | 207.20 | 0.00 | 0.00 | 0.00 |
April | 296.23 | 83.60 | 212.63 | 706.67 | 72.85 | 0.00 | 0.00 | 0.00 |
May | 213.03 | 15.77 | 197.26 | 655.79 | 11.62 | 0.00 | 0.00 | 0.00 |
June | 194.87 | 3.33 | 191.54 | 646.01 | 9.53 | 0.00 | 0.00 | 0.00 |
July | 203.26 | 2.80 | 200.47 | 592.49 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 215.62 | 11.52 | 204.10 | 553.34 | 10.21 | 0.00 | 0.00 | 0.00 |
September | 289.05 | 75.02 | 214.03 | 621.22 | 41.36 | 0.00 | 0.00 | 0.00 |
October | 497.29 | 277.68 | 219.61 | 924.99 | 182.64 | 0.00 | 0.00 | 0.00 |
November | 621.14 | 410.56 | 210.58 | 1011.78 | 332.63 | 0.00 | 0.00 | 0.00 |
December | 554.35 | 347.37 | 206.98 | 790.09 | 437.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.87 | 166.30 | 209.57 | 725.57 | 173.24 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 194.87 | 2.80 | 191.54 | 553.34 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.14 | 410.56 | 235.46 | 1011.78 | 437.41 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.74 | 315.20 | 203.54 | 716.38 | 433.66 | 21.33 | 0.00 | 0.00 |
February | 493.24 | 273.96 | 219.28 | 743.52 | 346.15 | 0.00 | 0.00 | 0.00 |
March | 421.74 | 186.28 | 235.46 | 749.05 | 207.20 | 0.00 | 0.00 | 0.00 |
April | 296.23 | 83.60 | 212.63 | 706.67 | 72.85 | 0.00 | 0.00 | 0.00 |
May | 213.03 | 15.77 | 197.26 | 655.79 | 11.62 | 0.00 | 0.00 | 0.00 |
June | 194.87 | 3.33 | 191.54 | 646.01 | 9.53 | 0.00 | 0.00 | 0.00 |
July | 203.26 | 2.80 | 200.47 | 592.49 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 215.62 | 11.52 | 204.10 | 553.34 | 10.21 | 0.00 | 0.00 | 0.00 |
September | 289.05 | 75.02 | 214.03 | 621.22 | 41.36 | 0.00 | 0.00 | 0.00 |
October | 497.29 | 277.68 | 219.61 | 924.99 | 182.64 | 0.00 | 0.00 | 0.00 |
November | 621.14 | 410.56 | 210.58 | 1011.78 | 332.63 | 0.00 | 0.00 | 0.00 |
December | 554.35 | 347.37 | 206.98 | 790.09 | 437.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.87 | 166.30 | 209.57 | 725.57 | 173.24 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 194.87 | 2.80 | 191.54 | 553.34 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.14 | 410.56 | 235.46 | 1011.78 | 437.41 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.70 | 315.18 | 203.53 | 716.34 | 433.63 | 21.33 | 0.00 | 0.00 |
February | 493.21 | 273.94 | 219.27 | 743.47 | 346.12 | 0.00 | 0.00 | 0.00 |
March | 421.71 | 186.26 | 235.44 | 749.00 | 207.19 | 0.00 | 0.00 | 0.00 |
April | 296.21 | 83.60 | 212.61 | 706.63 | 72.85 | 0.00 | 0.00 | 0.00 |
May | 213.02 | 15.77 | 197.25 | 655.74 | 11.62 | 0.00 | 0.00 | 0.00 |
June | 194.85 | 3.33 | 191.53 | 645.97 | 9.53 | 0.00 | 0.00 | 0.00 |
July | 203.25 | 2.80 | 200.46 | 592.45 | 2.77 | 0.00 | 0.00 | 0.00 |
August | 215.61 | 11.51 | 204.09 | 553.31 | 10.21 | 0.00 | 0.00 | 0.00 |
September | 289.04 | 75.02 | 214.02 | 621.18 | 41.36 | 0.00 | 0.00 | 0.00 |
October | 497.26 | 277.66 | 219.59 | 924.93 | 182.63 | 0.00 | 0.00 | 0.00 |
November | 621.10 | 410.53 | 210.57 | 1011.72 | 332.61 | 0.00 | 0.00 | 0.00 |
December | 554.31 | 347.35 | 206.97 | 790.04 | 437.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 375.85 | 166.29 | 209.56 | 725.53 | 173.23 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 194.85 | 2.80 | 191.53 | 553.31 | 2.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.10 | 410.53 | 235.44 | 1011.72 | 437.38 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.91 | 178.98 | 280.93 | 537.85 | 864.30 | 25.83 | 0.00 | 0.00 |
February | 525.91 | 193.81 | 332.10 | 725.53 | 670.22 | 0.00 | 0.00 | 0.00 |
March | 681.98 | 272.61 | 409.37 | 1151.83 | 398.37 | 0.00 | 0.00 | 0.00 |
April | 828.94 | 388.74 | 440.20 | 1730.82 | 145.25 | 0.00 | 0.00 | 0.00 |
May | 784.92 | 332.95 | 451.98 | 1910.22 | 27.95 | 0.00 | 0.00 | 0.00 |
June | 737.25 | 286.37 | 450.89 | 1899.01 | 21.50 | 0.00 | 0.00 | 0.00 |
July | 547.08 | 106.41 | 440.67 | 1412.33 | 6.15 | 0.00 | 0.00 | 0.00 |
August | 502.44 | 89.30 | 413.14 | 1209.17 | 20.00 | 0.00 | 0.00 | 0.00 |
September | 552.31 | 162.14 | 390.17 | 1154.92 | 78.30 | 0.00 | 0.00 | 0.00 |
October | 574.87 | 228.91 | 345.96 | 1086.67 | 339.69 | 0.00 | 0.00 | 0.00 |
November | 520.06 | 221.65 | 298.42 | 814.90 | 633.20 | 0.00 | 0.00 | 0.00 |
December | 445.02 | 169.70 | 275.33 | 531.34 | 854.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 596.62 | 219.01 | 377.61 | 1181.72 | 336.83 | 25.83 | 0.00 | 0.00 |
Minimum of Months | 445.02 | 89.30 | 275.33 | 531.34 | 6.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 828.94 | 388.74 | 451.98 | 1910.22 | 864.30 | 25.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.18 | 7.08 | 11.11 | 21.27 | 34.17 | 25.83 | 0.00 | 0.00 |
February | 20.79 | 7.66 | 13.13 | 28.69 | 26.50 | 0.00 | 0.00 | 0.00 |
March | 26.96 | 10.78 | 16.19 | 45.54 | 15.75 | 0.00 | 0.00 | 0.00 |
April | 32.78 | 15.37 | 17.40 | 68.43 | 5.74 | 0.00 | 0.00 | 0.00 |
May | 31.04 | 13.16 | 17.87 | 75.53 | 1.11 | 0.00 | 0.00 | 0.00 |
June | 29.15 | 11.32 | 17.83 | 75.09 | 0.85 | 0.00 | 0.00 | 0.00 |
July | 21.63 | 4.21 | 17.42 | 55.84 | 0.24 | 0.00 | 0.00 | 0.00 |
August | 19.87 | 3.53 | 16.34 | 47.81 | 0.79 | 0.00 | 0.00 | 0.00 |
September | 21.84 | 6.41 | 15.43 | 45.66 | 3.10 | 0.00 | 0.00 | 0.00 |
October | 22.73 | 9.05 | 13.68 | 42.97 | 13.43 | 0.00 | 0.00 | 0.00 |
November | 20.56 | 8.76 | 11.80 | 32.22 | 25.04 | 0.00 | 0.00 | 0.00 |
December | 17.60 | 6.71 | 10.89 | 21.01 | 33.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.59 | 8.66 | 14.93 | 46.72 | 13.32 | 25.83 | 0.00 | 0.00 |
Minimum of Months | 17.60 | 3.53 | 10.89 | 21.01 | 0.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.78 | 15.37 | 17.87 | 75.53 | 34.17 | 25.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 342.18 | 0.00 | 342.18 | 209.46 | 1297.89 | 23.33 | 0.00 | 0.00 |
February | 405.77 | 0.00 | 405.77 | 395.68 | 1024.38 | 0.00 | 0.00 | 0.00 |
March | 488.95 | 0.00 | 488.95 | 757.46 | 611.38 | 0.00 | 0.00 | 0.00 |
April | 530.55 | 1.80 | 528.75 | 1329.49 | 217.50 | 0.00 | 0.00 | 0.00 |
May | 587.82 | 16.50 | 571.32 | 1851.52 | 39.79 | 0.00 | 0.00 | 0.00 |
June | 608.48 | 22.54 | 585.94 | 2012.89 | 29.28 | 0.00 | 0.00 | 0.00 |
July | 600.10 | 9.50 | 590.60 | 1782.68 | 6.57 | 0.00 | 0.00 | 0.00 |
August | 550.91 | 1.72 | 549.20 | 1499.74 | 22.21 | 0.00 | 0.00 | 0.00 |
September | 490.88 | 0.03 | 490.84 | 1163.32 | 91.80 | 0.00 | 0.00 | 0.00 |
October | 425.26 | 0.00 | 425.26 | 846.35 | 476.56 | 0.00 | 0.00 | 0.00 |
November | 360.20 | 0.00 | 360.20 | 459.16 | 916.06 | 0.00 | 0.00 | 0.00 |
December | 333.80 | 0.00 | 333.80 | 230.34 | 1273.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 477.44 | 4.36 | 473.08 | 1048.02 | 498.28 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 333.80 | 0.00 | 333.80 | 209.46 | 6.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.48 | 22.54 | 590.60 | 2012.89 | 1297.89 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.68 | 196.15 | 292.53 | 507.59 | 791.13 | 23.33 | 0.00 | 0.00 |
February | 593.69 | 245.10 | 348.58 | 767.15 | 635.23 | 0.00 | 0.00 | 0.00 |
March | 724.23 | 298.94 | 425.30 | 1180.08 | 387.24 | 0.00 | 0.00 | 0.00 |
April | 861.65 | 401.75 | 459.90 | 1778.36 | 145.13 | 0.00 | 0.00 | 0.00 |
May | 848.10 | 376.00 | 472.10 | 2034.95 | 25.97 | 0.00 | 0.00 | 0.00 |
June | 690.24 | 229.02 | 461.22 | 1846.38 | 19.37 | 0.00 | 0.00 | 0.00 |
July | 580.13 | 122.51 | 457.62 | 1511.01 | 3.91 | 0.00 | 0.00 | 0.00 |
August | 522.72 | 90.97 | 431.76 | 1275.45 | 14.85 | 0.00 | 0.00 | 0.00 |
September | 558.47 | 155.74 | 402.73 | 1183.70 | 60.84 | 0.00 | 0.00 | 0.00 |
October | 610.90 | 246.76 | 364.14 | 1138.97 | 308.66 | 0.00 | 0.00 | 0.00 |
November | 541.65 | 232.50 | 309.15 | 803.98 | 574.19 | 0.00 | 0.00 | 0.00 |
December | 472.30 | 187.13 | 285.17 | 528.01 | 790.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 624.23 | 231.52 | 392.70 | 1214.55 | 311.71 | 23.33 | 0.00 | 0.00 |
Minimum of Months | 472.30 | 90.97 | 285.17 | 507.59 | 3.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.65 | 401.75 | 472.10 | 2034.95 | 791.13 | 23.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1556.24 | 945.61 | 610.63 | 2134.52 | 1232.47 | 21.33 | 0.00 | 0.00 |
February | 1479.75 | 821.90 | 657.86 | 2208.99 | 1008.99 | 0.00 | 0.00 | 0.00 |
March | 1265.23 | 558.84 | 706.39 | 2225.54 | 624.51 | 0.00 | 0.00 | 0.00 |
April | 888.70 | 250.82 | 637.88 | 2112.61 | 230.44 | 0.00 | 0.00 | 0.00 |
May | 639.09 | 47.31 | 591.78 | 1981.97 | 38.73 | 0.00 | 0.00 | 0.00 |
June | 584.60 | 9.98 | 574.63 | 1967.28 | 28.96 | 0.00 | 0.00 | 0.00 |
July | 609.80 | 8.39 | 601.41 | 1811.51 | 5.91 | 0.00 | 0.00 | 0.00 |
August | 646.87 | 34.55 | 612.32 | 1698.16 | 22.68 | 0.00 | 0.00 | 0.00 |
September | 867.18 | 225.08 | 642.10 | 1894.55 | 97.44 | 0.00 | 0.00 | 0.00 |
October | 1491.89 | 833.06 | 658.82 | 2795.60 | 495.90 | 0.00 | 0.00 | 0.00 |
November | 1863.45 | 1231.70 | 631.75 | 3037.48 | 920.85 | 0.00 | 0.00 | 0.00 |
December | 1663.08 | 1042.13 | 620.95 | 2369.99 | 1227.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1127.64 | 498.92 | 628.72 | 2185.60 | 492.23 | 21.33 | 0.00 | 0.00 |
Minimum of Months | 584.60 | 8.39 | 574.63 | 1698.16 | 5.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1863.45 | 1231.70 | 706.39 | 3037.48 | 1232.47 | 21.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 478.10 | 186.06 | 292.04 | 560.49 | 858.98 | 24.83 | 0.00 | 0.00 |
February | 546.72 | 201.48 | 345.24 | 746.37 | 686.45 | 0.00 | 0.00 | 0.00 |
March | 708.95 | 283.39 | 425.56 | 1182.97 | 419.72 | 0.00 | 0.00 | 0.00 |
April | 861.72 | 404.11 | 457.61 | 1786.51 | 156.64 | 0.00 | 0.00 | 0.00 |
May | 815.97 | 346.12 | 469.85 | 1983.91 | 29.87 | 0.00 | 0.00 | 0.00 |
June | 766.41 | 297.70 | 468.72 | 1980.75 | 21.27 | 0.00 | 0.00 | 0.00 |
July | 568.72 | 110.62 | 458.10 | 1482.55 | 4.60 | 0.00 | 0.00 | 0.00 |
August | 522.31 | 92.83 | 429.48 | 1275.77 | 15.42 | 0.00 | 0.00 | 0.00 |
September | 574.15 | 168.56 | 405.60 | 1213.91 | 65.25 | 0.00 | 0.00 | 0.00 |
October | 597.61 | 237.97 | 359.64 | 1137.31 | 328.22 | 0.00 | 0.00 | 0.00 |
November | 540.63 | 230.41 | 310.22 | 854.40 | 618.29 | 0.00 | 0.00 | 0.00 |
December | 462.62 | 176.41 | 286.21 | 561.17 | 837.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 620.21 | 227.67 | 392.54 | 1231.98 | 335.27 | 24.83 | 0.00 | 0.00 |
Minimum of Months | 462.62 | 92.83 | 286.21 | 560.49 | 4.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 861.72 | 404.11 | 469.85 | 1983.91 | 858.98 | 24.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.630372E+09 | 0.314877E+10 |
February | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.100641E+10 | 0.227269E+10 |
March | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.203940E+10 | 0.153134E+10 |
April | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.341972E+10 | 0.536917E+09 |
May | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.491709E+10 | 0.104927E+09 |
June | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.517186E+10 | 76928853.64 |
July | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.473174E+10 | 17107775.96 |
August | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.398206E+10 | 57265983.93 |
September | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.299788E+10 | 0.223481E+09 |
October | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.226894E+10 | 0.119594E+10 |
November | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.123761E+10 | 0.217745E+10 |
December | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.697525E+09 | 0.308941E+10 |
Annual Sum or Average | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.331006E+11 | 0.144322E+11 |
Minimum of Months | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.630372E+09 | 17107775.96 |
Maximum of Months | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.517186E+10 | 0.314877E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.142834E+10 | 0.193756E+10 |
February | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.189396E+10 | 0.142857E+10 |
March | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.316643E+10 | 0.982797E+09 |
April | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.458602E+10 | 0.361580E+09 |
May | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.541494E+10 | 68866849.52 |
June | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.475063E+10 | 51429199.52 |
July | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.401504E+10 | 10161375.45 |
August | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.339018E+10 | 38675920.17 |
September | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.305320E+10 | 0.149520E+09 |
October | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.305066E+10 | 0.782278E+09 |
November | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.211907E+10 | 0.138425E+10 |
December | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.148439E+10 | 0.194428E+10 |
Annual Sum or Average | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.383529E+11 | 0.913997E+10 |
Minimum of Months | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.142834E+10 | 10161375.45 |
Maximum of Months | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.541494E+10 | 0.194428E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.579620E+10 | 0.302123E+10 |
February | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.538473E+10 | 0.226489E+10 |
March | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.596148E+10 | 0.157784E+10 |
April | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.544354E+10 | 0.570365E+09 |
May | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.526526E+10 | 0.101563E+09 |
June | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.505360E+10 | 76433788.96 |
July | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.480914E+10 | 15208380.54 |
August | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.451255E+10 | 58651289.66 |
September | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.488722E+10 | 0.238708E+09 |
October | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.748302E+10 | 0.125610E+10 |
November | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.790547E+10 | 0.222256E+10 |
December | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.643031E+10 | 0.302555E+10 |
Annual Sum or Average | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.689325E+11 | 0.144291E+11 |
Minimum of Months | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.451255E+10 | 15208380.54 |
Maximum of Months | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.790547E+10 | 0.302555E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.154268E+10 | 0.209611E+10 |
February | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.183357E+10 | 0.153117E+10 |
March | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.317286E+10 | 0.105502E+10 |
April | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.461018E+10 | 0.387270E+09 |
May | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.528460E+10 | 78280349.75 |
June | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.510331E+10 | 55499773.76 |
July | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.394338E+10 | 12106283.05 |
August | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.339429E+10 | 39895263.81 |
September | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.313429E+10 | 0.159367E+09 |
October | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.304664E+10 | 0.825881E+09 |
November | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.224279E+10 | 0.147689E+10 |
December | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.155280E+10 | 0.204484E+10 |
Annual Sum or Average | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.388614E+11 | 0.976232E+10 |
Minimum of Months | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.154268E+10 | 12106283.05 |
Maximum of Months | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.528460E+10 | 0.209611E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305485E+09 | 0.00 | 0.305485E+09 | 0.185208E+09 | 0.119092E+10 |
February | 0.327197E+09 | 0.00 | 0.327197E+09 | 0.328989E+09 | 0.817847E+09 |
March | 0.436517E+09 | 0.00 | 0.436517E+09 | 0.695675E+09 | 0.519677E+09 |
April | 0.458376E+09 | 1554509.24 | 0.456822E+09 | 0.116959E+10 | 0.167953E+09 |
May | 0.524777E+09 | 14726215.66 | 0.510051E+09 | 0.166615E+10 | 29456212.00 |
June | 0.525704E+09 | 19472185.50 | 0.506232E+09 | 0.173842E+10 | 24225910.40 |
July | 0.535747E+09 | 8483873.51 | 0.527263E+09 | 0.157651E+10 | 7635735.04 |
August | 0.491831E+09 | 1532816.68 | 0.490298E+09 | 0.131649E+10 | 25644606.24 |
September | 0.424099E+09 | 29779.32 | 0.424069E+09 | 0.987189E+09 | 93529842.33 |
October | 0.379654E+09 | 0.00 | 0.379654E+09 | 0.744785E+09 | 0.444881E+09 |
November | 0.311197E+09 | 0.00 | 0.311197E+09 | 0.387904E+09 | 0.825036E+09 |
December | 0.298006E+09 | 0.00 | 0.298006E+09 | 0.196099E+09 | 0.118687E+10 |
Annual Sum or Average | 0.501859E+10 | 45799379.90 | 0.497279E+10 | 0.109930E+11 | 0.533368E+10 |
Minimum of Months | 0.298006E+09 | 0.00 | 0.298006E+09 | 0.185208E+09 | 7635735.04 |
Maximum of Months | 0.535747E+09 | 19472185.50 | 0.527263E+09 | 0.173842E+10 | 0.119092E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305497E+09 | 0.00 | 0.305497E+09 | 0.185213E+09 | 0.119099E+10 |
February | 0.327210E+09 | 0.00 | 0.327210E+09 | 0.329002E+09 | 0.817893E+09 |
March | 0.436535E+09 | 0.00 | 0.436535E+09 | 0.695708E+09 | 0.519703E+09 |
April | 0.458396E+09 | 1554551.03 | 0.456842E+09 | 0.116966E+10 | 0.167959E+09 |
May | 0.524799E+09 | 14726611.51 | 0.510072E+09 | 0.166625E+10 | 29456341.95 |
June | 0.525726E+09 | 19472708.91 | 0.506253E+09 | 0.173852E+10 | 24226745.96 |
July | 0.535767E+09 | 8484101.56 | 0.527283E+09 | 0.157659E+10 | 7635706.52 |
August | 0.491849E+09 | 1532857.88 | 0.490316E+09 | 0.131656E+10 | 25645063.25 |
September | 0.424115E+09 | 29780.12 | 0.424085E+09 | 0.987238E+09 | 93532378.68 |
October | 0.379669E+09 | 0.00 | 0.379669E+09 | 0.744823E+09 | 0.444902E+09 |
November | 0.311210E+09 | 0.00 | 0.311210E+09 | 0.387923E+09 | 0.825080E+09 |
December | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.196105E+09 | 0.118694E+10 |
Annual Sum or Average | 0.501879E+10 | 45800611.00 | 0.497299E+10 | 0.109936E+11 | 0.533396E+10 |
Minimum of Months | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.185213E+09 | 7635706.52 |
Maximum of Months | 0.535767E+09 | 19472708.91 | 0.527283E+09 | 0.173852E+10 | 0.119099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.305497E+09 | 0.00 | 0.305497E+09 | 0.185213E+09 | 0.119099E+10 |
February | 0.327210E+09 | 0.00 | 0.327210E+09 | 0.329002E+09 | 0.817893E+09 |
March | 0.436535E+09 | 0.00 | 0.436535E+09 | 0.695708E+09 | 0.519703E+09 |
April | 0.458396E+09 | 1554551.03 | 0.456842E+09 | 0.116966E+10 | 0.167959E+09 |
May | 0.524799E+09 | 14726611.51 | 0.510072E+09 | 0.166625E+10 | 29456341.95 |
June | 0.525726E+09 | 19472708.91 | 0.506253E+09 | 0.173852E+10 | 24226745.96 |
July | 0.535767E+09 | 8484101.56 | 0.527283E+09 | 0.157659E+10 | 7635706.52 |
August | 0.491849E+09 | 1532857.88 | 0.490316E+09 | 0.131656E+10 | 25645063.25 |
September | 0.424115E+09 | 29780.12 | 0.424085E+09 | 0.987238E+09 | 93532378.68 |
October | 0.379669E+09 | 0.00 | 0.379669E+09 | 0.744823E+09 | 0.444902E+09 |
November | 0.311210E+09 | 0.00 | 0.311210E+09 | 0.387923E+09 | 0.825080E+09 |
December | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.196105E+09 | 0.118694E+10 |
Annual Sum or Average | 0.501879E+10 | 45800611.00 | 0.497299E+10 | 0.109936E+11 | 0.533396E+10 |
Minimum of Months | 0.298018E+09 | 0.00 | 0.298018E+09 | 0.185213E+09 | 7635706.52 |
Maximum of Months | 0.535767E+09 | 19472708.91 | 0.527283E+09 | 0.173852E+10 | 0.119099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125908E+10 | 0.505375E+09 | 0.753705E+09 | 0.129063E+10 | 0.213999E+10 |
February | 0.138159E+10 | 0.570384E+09 | 0.811210E+09 | 0.179947E+10 | 0.150790E+10 |
March | 0.186598E+10 | 0.770207E+09 | 0.109577E+10 | 0.307658E+10 | 0.985849E+09 |
April | 0.214842E+10 | 0.100170E+10 | 0.114672E+10 | 0.446681E+10 | 0.346501E+09 |
May | 0.218512E+10 | 0.968759E+09 | 0.121636E+10 | 0.525375E+10 | 63936498.32 |
June | 0.172103E+10 | 0.571035E+09 | 0.115000E+10 | 0.459381E+10 | 49731466.41 |
July | 0.149470E+10 | 0.315639E+09 | 0.117906E+10 | 0.385396E+10 | 14299481.52 |
August | 0.134679E+10 | 0.234371E+09 | 0.111242E+10 | 0.323920E+10 | 52063311.19 |
September | 0.139247E+10 | 0.388324E+09 | 0.100415E+10 | 0.291671E+10 | 0.188691E+09 |
October | 0.157397E+10 | 0.635779E+09 | 0.938195E+09 | 0.291389E+10 | 0.855286E+09 |
November | 0.135054E+10 | 0.579710E+09 | 0.770828E+09 | 0.198373E+10 | 0.152315E+10 |
December | 0.121687E+10 | 0.482127E+09 | 0.734739E+09 | 0.132961E+10 | 0.216496E+10 |
Annual Sum or Average | 0.189366E+11 | 0.702341E+10 | 0.119132E+11 | 0.367181E+11 | 0.989236E+10 |
Minimum of Months | 0.121687E+10 | 0.234371E+09 | 0.734739E+09 | 0.129063E+10 | 14299481.52 |
Maximum of Months | 0.218512E+10 | 0.100170E+10 | 0.121636E+10 | 0.525375E+10 | 0.216496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49782875.71 | 19982077.15 | 29800798.56 | 51030305.13 | 84613172.48 |
February | 54626992.37 | 22552487.90 | 32074504.48 | 71149524.40 | 59621187.13 |
March | 73779083.82 | 30453304.59 | 43325779.23 | 0.121645E+09 | 38979600.81 |
April | 84946476.03 | 39606217.43 | 45340258.60 | 0.176614E+09 | 13700338.53 |
May | 86397680.08 | 38303848.58 | 48093831.50 | 0.207728E+09 | 2527991.58 |
June | 68048135.35 | 22578193.78 | 45469941.58 | 0.181635E+09 | 1966337.41 |
July | 59099080.80 | 12480090.13 | 46618990.67 | 0.152382E+09 | 565388.63 |
August | 53250721.51 | 9266833.39 | 43983888.12 | 0.128075E+09 | 2058536.45 |
September | 55057092.91 | 15353990.10 | 39703102.81 | 0.115324E+09 | 7460661.24 |
October | 62233497.71 | 25138116.68 | 37095381.03 | 0.115213E+09 | 33817257.99 |
November | 53399050.41 | 22921191.96 | 30477858.45 | 78434790.78 | 60223952.04 |
December | 48113780.19 | 19062880.35 | 29050899.84 | 52571586.99 | 85600649.91 |
Annual Sum or Average | 0.748734E+09 | 0.277699E+09 | 0.471035E+09 | 0.145180E+10 | 0.391135E+09 |
Minimum of Months | 48113780.19 | 9266833.39 | 29050899.84 | 51030305.13 | 565388.63 |
Maximum of Months | 86397680.08 | 39606217.43 | 48093831.50 | 0.207728E+09 | 85600649.91 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138938E+10 | 0.844223E+09 | 0.545161E+09 | 0.191876E+10 | 0.116150E+10 |
February | 0.119325E+10 | 0.662765E+09 | 0.530489E+09 | 0.179873E+10 | 0.837397E+09 |
March | 0.112958E+10 | 0.498922E+09 | 0.630655E+09 | 0.200625E+10 | 0.554971E+09 |
April | 0.767828E+09 | 0.216703E+09 | 0.551125E+09 | 0.183169E+10 | 0.188829E+09 |
May | 0.570578E+09 | 42237652.62 | 0.528340E+09 | 0.175646E+10 | 31127085.78 |
June | 0.505095E+09 | 8619186.74 | 0.496476E+09 | 0.167447E+10 | 24710777.16 |
July | 0.544422E+09 | 7488005.76 | 0.536934E+09 | 0.158691E+10 | 7430105.08 |
August | 0.577516E+09 | 30843432.88 | 0.546672E+09 | 0.148208E+10 | 27340599.84 |
September | 0.749231E+09 | 0.194463E+09 | 0.554767E+09 | 0.161020E+10 | 0.107218E+09 |
October | 0.133194E+10 | 0.743745E+09 | 0.588192E+09 | 0.247748E+10 | 0.489180E+09 |
November | 0.160999E+10 | 0.106417E+10 | 0.545824E+09 | 0.262254E+10 | 0.862169E+09 |
December | 0.148477E+10 | 0.930396E+09 | 0.554375E+09 | 0.211618E+10 | 0.117155E+10 |
Annual Sum or Average | 0.118536E+11 | 0.524457E+10 | 0.660901E+10 | 0.228817E+11 | 0.546343E+10 |
Minimum of Months | 0.505095E+09 | 7488005.76 | 0.496476E+09 | 0.148208E+10 | 7430105.08 |
Maximum of Months | 0.160999E+10 | 0.106417E+10 | 0.630655E+09 | 0.262254E+10 | 0.117155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138938E+10 | 0.844223E+09 | 0.545161E+09 | 0.191876E+10 | 0.116150E+10 |
February | 0.119325E+10 | 0.662765E+09 | 0.530489E+09 | 0.179873E+10 | 0.837397E+09 |
March | 0.112958E+10 | 0.498922E+09 | 0.630655E+09 | 0.200625E+10 | 0.554971E+09 |
April | 0.767828E+09 | 0.216703E+09 | 0.551125E+09 | 0.183169E+10 | 0.188829E+09 |
May | 0.570578E+09 | 42237652.62 | 0.528340E+09 | 0.175646E+10 | 31127085.78 |
June | 0.505095E+09 | 8619186.74 | 0.496476E+09 | 0.167447E+10 | 24710777.16 |
July | 0.544422E+09 | 7488005.76 | 0.536934E+09 | 0.158691E+10 | 7430105.08 |
August | 0.577516E+09 | 30843432.88 | 0.546672E+09 | 0.148208E+10 | 27340599.84 |
September | 0.749231E+09 | 0.194463E+09 | 0.554767E+09 | 0.161020E+10 | 0.107218E+09 |
October | 0.133194E+10 | 0.743745E+09 | 0.588192E+09 | 0.247748E+10 | 0.489180E+09 |
November | 0.160999E+10 | 0.106417E+10 | 0.545824E+09 | 0.262254E+10 | 0.862169E+09 |
December | 0.148477E+10 | 0.930396E+09 | 0.554375E+09 | 0.211618E+10 | 0.117155E+10 |
Annual Sum or Average | 0.118536E+11 | 0.524457E+10 | 0.660901E+10 | 0.228817E+11 | 0.546343E+10 |
Minimum of Months | 0.505095E+09 | 7488005.76 | 0.496476E+09 | 0.148208E+10 | 7430105.08 |
Maximum of Months | 0.160999E+10 | 0.106417E+10 | 0.630655E+09 | 0.262254E+10 | 0.117155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138930E+10 | 0.844169E+09 | 0.545126E+09 | 0.191864E+10 | 0.116143E+10 |
February | 0.119318E+10 | 0.662723E+09 | 0.530456E+09 | 0.179861E+10 | 0.837344E+09 |
March | 0.112951E+10 | 0.498891E+09 | 0.630615E+09 | 0.200612E+10 | 0.554936E+09 |
April | 0.767779E+09 | 0.216689E+09 | 0.551090E+09 | 0.183157E+10 | 0.188817E+09 |
May | 0.570542E+09 | 42234983.44 | 0.528307E+09 | 0.175635E+10 | 31125118.73 |
June | 0.505064E+09 | 8618642.05 | 0.496445E+09 | 0.167436E+10 | 24709215.58 |
July | 0.544388E+09 | 7487532.56 | 0.536900E+09 | 0.158681E+10 | 7429635.54 |
August | 0.577479E+09 | 30841483.75 | 0.546638E+09 | 0.148198E+10 | 27338872.07 |
September | 0.749183E+09 | 0.194451E+09 | 0.554732E+09 | 0.161009E+10 | 0.107211E+09 |
October | 0.133185E+10 | 0.743698E+09 | 0.588154E+09 | 0.247733E+10 | 0.489149E+09 |
November | 0.160989E+10 | 0.106410E+10 | 0.545789E+09 | 0.262237E+10 | 0.862115E+09 |
December | 0.148468E+10 | 0.930338E+09 | 0.554340E+09 | 0.211604E+10 | 0.117147E+10 |
Annual Sum or Average | 0.118528E+11 | 0.524424E+10 | 0.660859E+10 | 0.228803E+11 | 0.546308E+10 |
Minimum of Months | 0.505064E+09 | 7487532.56 | 0.496445E+09 | 0.148198E+10 | 7429635.54 |
Maximum of Months | 0.160989E+10 | 0.106410E+10 | 0.630615E+09 | 0.262237E+10 | 0.117147E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123181E+10 | 0.479372E+09 | 0.752438E+09 | 0.144059E+10 | 0.231494E+10 |
February | 0.127229E+10 | 0.468872E+09 | 0.803419E+09 | 0.175520E+10 | 0.162141E+10 |
March | 0.182661E+10 | 0.730156E+09 | 0.109645E+10 | 0.308506E+10 | 0.106699E+10 |
April | 0.214860E+10 | 0.100761E+10 | 0.114099E+10 | 0.448628E+10 | 0.376481E+09 |
May | 0.210234E+10 | 0.891767E+09 | 0.121058E+10 | 0.511634E+10 | 74865331.98 |
June | 0.191096E+10 | 0.742266E+09 | 0.116870E+10 | 0.492224E+10 | 55734690.46 |
July | 0.146530E+10 | 0.285000E+09 | 0.118030E+10 | 0.378279E+10 | 16481286.52 |
August | 0.134572E+10 | 0.239175E+09 | 0.110655E+10 | 0.323864E+10 | 53568353.94 |
September | 0.143158E+10 | 0.420271E+09 | 0.101131E+10 | 0.299354E+10 | 0.202944E+09 |
October | 0.153973E+10 | 0.613114E+09 | 0.926613E+09 | 0.291053E+10 | 0.909831E+09 |
November | 0.134800E+10 | 0.574509E+09 | 0.773495E+09 | 0.211222E+10 | 0.164125E+10 |
December | 0.119194E+10 | 0.454514E+09 | 0.737431E+09 | 0.142315E+10 | 0.228776E+10 |
Annual Sum or Average | 0.188149E+11 | 0.690662E+10 | 0.119083E+11 | 0.372666E+11 | 0.106223E+11 |
Minimum of Months | 0.119194E+10 | 0.239175E+09 | 0.737431E+09 | 0.142315E+10 | 16481286.52 |
Maximum of Months | 0.214860E+10 | 0.100761E+10 | 0.121058E+10 | 0.511634E+10 | 0.231494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48704544.42 | 18953876.96 | 29750667.45 | 56959381.51 | 91530638.99 |
February | 50305114.38 | 18538715.82 | 31766398.56 | 69398741.21 | 64108859.25 |
March | 72222168.57 | 28869617.75 | 43352550.82 | 0.121980E+09 | 42187858.63 |
April | 84953547.95 | 39839791.47 | 45113756.47 | 0.177383E+09 | 14885677.41 |
May | 83124525.94 | 35259549.00 | 47864976.95 | 0.202295E+09 | 2960093.33 |
June | 75557532.32 | 29348432.76 | 46209099.55 | 0.194621E+09 | 2203694.17 |
July | 57936481.56 | 11268615.00 | 46667866.56 | 0.149568E+09 | 651651.37 |
August | 53208563.17 | 9456740.43 | 43751822.74 | 0.128053E+09 | 2118035.81 |
September | 56603380.70 | 16617070.77 | 39986309.93 | 0.118362E+09 | 8024181.69 |
October | 60879265.82 | 24241916.18 | 36637349.64 | 0.115079E+09 | 35973863.70 |
November | 53298707.56 | 22715483.29 | 30583224.27 | 83515070.36 | 64893466.21 |
December | 47128295.36 | 17971013.27 | 29157282.09 | 56269874.47 | 90455858.02 |
Annual Sum or Average | 0.743922E+09 | 0.273081E+09 | 0.470841E+09 | 0.147348E+10 | 0.419994E+09 |
Minimum of Months | 47128295.36 | 9456740.43 | 29157282.09 | 56269874.47 | 651651.37 |
Maximum of Months | 84953547.95 | 39839791.47 | 47864976.95 | 0.202295E+09 | 91530638.99 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.561006E+09 | 0.347628E+10 |
February | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.957222E+09 | 0.247818E+10 |
March | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.202877E+10 | 0.163752E+10 |
April | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.344603E+10 | 0.563752E+09 |
May | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.495912E+10 | 0.106586E+09 |
June | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.521740E+10 | 75885214.08 |
July | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.477472E+10 | 17599790.38 |
August | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.401691E+10 | 59474434.45 |
September | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.301531E+10 | 0.237958E+09 |
October | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.226687E+10 | 0.127643E+10 |
November | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.119015E+10 | 0.237444E+10 |
December | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.616954E+09 | 0.340964E+10 |
Annual Sum or Average | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.330505E+11 | 0.157137E+11 |
Minimum of Months | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.561006E+09 | 17599790.38 |
Maximum of Months | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.521740E+10 | 0.347628E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.135953E+10 | 0.211896E+10 |
February | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.185588E+10 | 0.153676E+10 |
March | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.316071E+10 | 0.103719E+10 |
April | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.460950E+10 | 0.376175E+09 |
May | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.545041E+10 | 69566048.92 |
June | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.478580E+10 | 50205356.21 |
July | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.404708E+10 | 10460201.30 |
August | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.341615E+10 | 39772903.68 |
September | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.306815E+10 | 0.157692E+09 |
October | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.305063E+10 | 0.826721E+09 |
November | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.208390E+10 | 0.148829E+10 |
December | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.141423E+10 | 0.211827E+10 |
Annual Sum or Average | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.383020E+11 | 0.983006E+10 |
Minimum of Months | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.135953E+10 | 10460201.30 |
Maximum of Months | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.545041E+10 | 0.211896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.571710E+10 | 0.330106E+10 |
February | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.534399E+10 | 0.244094E+10 |
March | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.596087E+10 | 0.167270E+10 |
April | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.547587E+10 | 0.597290E+09 |
May | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.530851E+10 | 0.103746E+09 |
June | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.509919E+10 | 75074923.21 |
July | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.485195E+10 | 15817767.13 |
August | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.454836E+10 | 60755801.59 |
September | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.491068E+10 | 0.252572E+09 |
October | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.748773E+10 | 0.132823E+10 |
November | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.787315E+10 | 0.238685E+10 |
December | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.634779E+10 | 0.328782E+10 |
Annual Sum or Average | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.689252E+11 | 0.155228E+11 |
Minimum of Months | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.454836E+10 | 15817767.13 |
Maximum of Months | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.787315E+10 | 0.330106E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.150122E+10 | 0.230068E+10 |
February | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.180561E+10 | 0.166065E+10 |
March | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.316845E+10 | 0.112418E+10 |
April | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.463063E+10 | 0.406007E+09 |
May | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.531370E+10 | 80006460.48 |
June | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.513410E+10 | 55142749.44 |
July | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.397086E+10 | 12320954.94 |
August | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.341702E+10 | 41290796.65 |
September | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.314646E+10 | 0.169137E+09 |
October | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.304617E+10 | 0.879103E+09 |
November | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.221462E+10 | 0.160262E+10 |
December | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.150303E+10 | 0.224185E+10 |
Annual Sum or Average | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.388519E+11 | 0.105730E+11 |
Minimum of Months | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.150122E+10 | 12320954.94 |
Maximum of Months | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.531370E+10 | 0.230068E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 235.35 | 1175.62 | 342.18 | 0.00 | 342.18 | 0.00 | 0.00 |
February | 416.01 | 939.44 | 405.77 | 0.00 | 405.77 | 0.00 | 0.00 |
March | 761.42 | 571.74 | 488.95 | 0.00 | 488.95 | 0.00 | 0.00 |
April | 1319.34 | 207.14 | 530.55 | 1.80 | 528.75 | 0.00 | 0.00 |
May | 1835.83 | 39.18 | 587.82 | 16.50 | 571.32 | 0.00 | 0.00 |
June | 1995.32 | 29.68 | 608.48 | 22.54 | 585.94 | 0.00 | 0.00 |
July | 1766.63 | 6.39 | 600.10 | 9.50 | 590.60 | 0.00 | 0.00 |
August | 1486.73 | 21.38 | 550.91 | 1.72 | 549.20 | 0.00 | 0.00 |
September | 1156.59 | 86.22 | 490.88 | 0.03 | 490.84 | 0.00 | 0.00 |
October | 847.13 | 446.51 | 425.26 | 0.00 | 425.26 | 0.00 | 0.00 |
November | 477.47 | 840.07 | 360.20 | 0.00 | 360.20 | 0.00 | 0.00 |
December | 260.43 | 1153.45 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1049.61 | 457.64 | 477.44 | 4.36 | 473.08 | 0.00 | 0.00 |
Minimum of Months | 235.35 | 6.39 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 1995.32 | 1175.62 | 608.48 | 22.54 | 590.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 533.28 | 723.40 | 488.68 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 782.89 | 590.51 | 593.69 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1182.21 | 366.93 | 724.23 | 298.94 | 425.30 | 0.00 | 0.00 |
April | 1769.30 | 139.50 | 861.65 | 401.75 | 459.90 | 0.00 | 0.00 |
May | 2021.71 | 25.71 | 848.10 | 376.00 | 472.10 | 0.00 | 0.00 |
June | 1832.80 | 19.84 | 690.24 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1499.04 | 3.79 | 580.13 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1265.75 | 14.44 | 522.72 | 90.97 | 431.76 | 0.00 | 0.00 |
September | 1177.93 | 57.69 | 558.47 | 155.74 | 402.73 | 0.00 | 0.00 |
October | 1138.99 | 292.07 | 610.90 | 246.76 | 364.14 | 0.00 | 0.00 |
November | 817.54 | 534.05 | 541.65 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 554.21 | 725.91 | 472.30 | 187.13 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1216.16 | 289.83 | 624.23 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 533.28 | 3.79 | 472.30 | 90.97 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2021.71 | 725.91 | 861.65 | 401.75 | 472.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2164.05 | 1128.00 | 1556.24 | 945.61 | 610.63 | 0.00 | 0.00 |
February | 2225.83 | 936.21 | 1479.75 | 821.90 | 657.86 | 0.00 | 0.00 |
March | 2225.76 | 589.10 | 1265.23 | 558.84 | 706.39 | 0.00 | 0.00 |
April | 2100.13 | 220.05 | 888.70 | 250.82 | 637.88 | 0.00 | 0.00 |
May | 1965.82 | 37.92 | 639.09 | 47.31 | 591.78 | 0.00 | 0.00 |
June | 1949.69 | 29.49 | 584.60 | 9.98 | 574.63 | 0.00 | 0.00 |
July | 1795.53 | 5.68 | 609.80 | 8.39 | 601.41 | 0.00 | 0.00 |
August | 1684.79 | 21.90 | 646.87 | 34.55 | 612.32 | 0.00 | 0.00 |
September | 1885.50 | 92.09 | 867.18 | 225.08 | 642.10 | 0.00 | 0.00 |
October | 2793.84 | 468.97 | 1491.89 | 833.06 | 658.82 | 0.00 | 0.00 |
November | 3049.95 | 857.47 | 1863.45 | 1231.70 | 631.75 | 0.00 | 0.00 |
December | 2400.80 | 1129.61 | 1663.08 | 1042.13 | 620.95 | 0.00 | 0.00 |
Annual Sum or Average | 2185.84 | 457.54 | 1127.64 | 498.92 | 628.72 | 0.00 | 0.00 |
Minimum of Months | 1684.79 | 5.68 | 584.60 | 8.39 | 574.63 | 0.00 | 0.00 |
Maximum of Months | 3049.95 | 1129.61 | 1863.45 | 1231.70 | 706.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 575.97 | 782.60 | 478.10 | 186.06 | 292.04 | 0.00 | 0.00 |
February | 757.92 | 632.92 | 546.72 | 201.48 | 345.24 | 0.00 | 0.00 |
March | 1184.61 | 393.90 | 708.95 | 283.39 | 425.56 | 0.00 | 0.00 |
April | 1778.62 | 149.41 | 861.72 | 404.11 | 457.61 | 0.00 | 0.00 |
May | 1973.04 | 29.23 | 815.97 | 346.12 | 469.85 | 0.00 | 0.00 |
June | 1968.87 | 21.41 | 766.41 | 297.70 | 468.72 | 0.00 | 0.00 |
July | 1472.29 | 4.52 | 568.72 | 110.62 | 458.10 | 0.00 | 0.00 |
August | 1267.28 | 14.90 | 522.31 | 92.83 | 429.48 | 0.00 | 0.00 |
September | 1209.22 | 61.48 | 574.15 | 168.56 | 405.60 | 0.00 | 0.00 |
October | 1137.49 | 308.35 | 597.61 | 237.97 | 359.64 | 0.00 | 0.00 |
November | 865.27 | 569.79 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 579.75 | 763.45 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1232.29 | 309.56 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 575.97 | 4.52 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1973.04 | 782.60 | 861.72 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 207.45 | 1333.96 | 342.17 | 0.00 | 342.17 | 0.00 | 0.00 |
February | 407.98 | 1014.23 | 405.76 | 0.00 | 405.76 | 0.00 | 0.00 |
March | 779.23 | 582.09 | 488.94 | 0.00 | 488.94 | 0.00 | 0.00 |
April | 1353.75 | 194.39 | 530.54 | 1.80 | 528.74 | 0.00 | 0.00 |
May | 1866.28 | 32.99 | 587.80 | 16.49 | 571.31 | 0.00 | 0.00 |
June | 2012.14 | 28.04 | 608.47 | 22.54 | 585.93 | 0.00 | 0.00 |
July | 1765.87 | 8.55 | 600.09 | 9.50 | 590.59 | 0.00 | 0.00 |
August | 1474.62 | 28.72 | 550.90 | 1.72 | 549.18 | 0.00 | 0.00 |
September | 1142.62 | 108.25 | 490.87 | 0.03 | 490.83 | 0.00 | 0.00 |
October | 834.24 | 498.31 | 425.25 | 0.00 | 425.25 | 0.00 | 0.00 |
November | 448.98 | 954.94 | 360.19 | 0.00 | 360.19 | 0.00 | 0.00 |
December | 219.65 | 1329.44 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1045.80 | 507.41 | 477.43 | 4.36 | 473.07 | 0.00 | 0.00 |
Minimum of Months | 207.45 | 8.55 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 2012.14 | 1333.96 | 608.47 | 22.54 | 590.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 500.92 | 830.57 | 488.67 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 773.24 | 647.95 | 593.68 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1194.08 | 382.63 | 724.22 | 298.93 | 425.29 | 0.00 | 0.00 |
April | 1791.44 | 138.97 | 861.64 | 401.74 | 459.90 | 0.00 | 0.00 |
May | 2039.08 | 24.81 | 848.09 | 375.99 | 472.09 | 0.00 | 0.00 |
June | 1842.38 | 19.95 | 690.23 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1495.80 | 5.55 | 580.12 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1257.20 | 20.21 | 522.71 | 90.96 | 431.75 | 0.00 | 0.00 |
September | 1169.77 | 75.68 | 558.46 | 155.74 | 402.72 | 0.00 | 0.00 |
October | 1130.94 | 331.95 | 610.89 | 246.76 | 364.13 | 0.00 | 0.00 |
November | 795.59 | 610.87 | 541.64 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 516.05 | 840.26 | 472.29 | 187.12 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1210.36 | 326.09 | 624.22 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 500.92 | 5.55 | 472.29 | 90.96 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2039.08 | 840.26 | 861.64 | 401.74 | 472.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2149.10 | 1300.94 | 1556.18 | 945.57 | 610.61 | 0.00 | 0.00 |
February | 2230.52 | 1038.42 | 1479.70 | 821.86 | 657.83 | 0.00 | 0.00 |
March | 2247.09 | 621.59 | 1265.18 | 558.82 | 706.36 | 0.00 | 0.00 |
April | 2119.97 | 218.55 | 888.67 | 250.81 | 637.86 | 0.00 | 0.00 |
May | 1967.32 | 34.86 | 639.07 | 47.31 | 591.77 | 0.00 | 0.00 |
June | 1938.00 | 28.60 | 584.59 | 9.98 | 574.61 | 0.00 | 0.00 |
July | 1777.42 | 8.32 | 609.78 | 8.39 | 601.39 | 0.00 | 0.00 |
August | 1660.00 | 30.62 | 646.85 | 34.55 | 612.30 | 0.00 | 0.00 |
September | 1863.61 | 124.09 | 867.15 | 225.07 | 642.08 | 0.00 | 0.00 |
October | 2774.90 | 547.91 | 1491.83 | 833.03 | 658.80 | 0.00 | 0.00 |
November | 3035.28 | 997.86 | 1863.38 | 1231.65 | 631.73 | 0.00 | 0.00 |
December | 2370.22 | 1312.19 | 1663.01 | 1042.09 | 620.93 | 0.00 | 0.00 |
Annual Sum or Average | 2176.68 | 519.72 | 1127.60 | 498.90 | 628.70 | 0.00 | 0.00 |
Minimum of Months | 1660.00 | 8.32 | 584.59 | 8.39 | 574.61 | 0.00 | 0.00 |
Maximum of Months | 3035.28 | 1312.19 | 1863.38 | 1231.65 | 706.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 559.12 | 898.47 | 478.09 | 186.05 | 292.04 | 0.00 | 0.00 |
February | 754.21 | 696.72 | 546.71 | 201.48 | 345.23 | 0.00 | 0.00 |
March | 1197.37 | 414.12 | 708.94 | 283.39 | 425.55 | 0.00 | 0.00 |
April | 1799.25 | 150.99 | 861.71 | 404.11 | 457.60 | 0.00 | 0.00 |
May | 1985.75 | 29.06 | 815.96 | 346.11 | 469.85 | 0.00 | 0.00 |
June | 1974.10 | 22.35 | 766.40 | 297.69 | 468.71 | 0.00 | 0.00 |
July | 1468.17 | 6.40 | 568.71 | 110.61 | 458.10 | 0.00 | 0.00 |
August | 1256.98 | 20.79 | 522.30 | 92.83 | 429.47 | 0.00 | 0.00 |
September | 1200.58 | 81.39 | 574.15 | 168.55 | 405.59 | 0.00 | 0.00 |
October | 1129.63 | 353.12 | 597.60 | 237.96 | 359.64 | 0.00 | 0.00 |
November | 847.12 | 658.23 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 552.35 | 887.92 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1228.44 | 350.15 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 552.35 | 6.40 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1985.75 | 898.47 | 861.71 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.46 | 1297.89 | 342.18 | 0.00 | 342.18 | 0.00 | 0.00 |
February | 395.68 | 1024.38 | 405.77 | 0.00 | 405.77 | 0.00 | 0.00 |
March | 757.46 | 611.38 | 488.95 | 0.00 | 488.95 | 0.00 | 0.00 |
April | 1329.49 | 217.50 | 530.55 | 1.80 | 528.75 | 0.00 | 0.00 |
May | 1851.52 | 39.79 | 587.82 | 16.50 | 571.32 | 0.00 | 0.00 |
June | 2012.89 | 29.28 | 608.48 | 22.54 | 585.94 | 0.00 | 0.00 |
July | 1782.68 | 6.57 | 600.10 | 9.50 | 590.60 | 0.00 | 0.00 |
August | 1499.74 | 22.21 | 550.91 | 1.72 | 549.20 | 0.00 | 0.00 |
September | 1163.32 | 91.80 | 490.88 | 0.03 | 490.84 | 0.00 | 0.00 |
October | 846.35 | 476.56 | 425.26 | 0.00 | 425.26 | 0.00 | 0.00 |
November | 459.16 | 916.06 | 360.20 | 0.00 | 360.20 | 0.00 | 0.00 |
December | 230.34 | 1273.01 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Annual Sum or Average | 1048.02 | 498.28 | 477.44 | 4.36 | 473.08 | 0.00 | 0.00 |
Minimum of Months | 209.46 | 6.57 | 333.80 | 0.00 | 333.80 | 0.00 | 0.00 |
Maximum of Months | 2012.89 | 1297.89 | 608.48 | 22.54 | 590.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 507.59 | 791.13 | 488.68 | 196.15 | 292.53 | 0.00 | 0.00 |
February | 767.15 | 635.23 | 593.69 | 245.10 | 348.58 | 0.00 | 0.00 |
March | 1180.08 | 387.24 | 724.23 | 298.94 | 425.30 | 0.00 | 0.00 |
April | 1778.36 | 145.13 | 861.65 | 401.75 | 459.90 | 0.00 | 0.00 |
May | 2034.95 | 25.97 | 848.10 | 376.00 | 472.10 | 0.00 | 0.00 |
June | 1846.38 | 19.37 | 690.24 | 229.02 | 461.22 | 0.00 | 0.00 |
July | 1511.01 | 3.91 | 580.13 | 122.51 | 457.62 | 0.00 | 0.00 |
August | 1275.45 | 14.85 | 522.72 | 90.97 | 431.76 | 0.00 | 0.00 |
September | 1183.70 | 60.84 | 558.47 | 155.74 | 402.73 | 0.00 | 0.00 |
October | 1138.97 | 308.66 | 610.90 | 246.76 | 364.14 | 0.00 | 0.00 |
November | 803.98 | 574.19 | 541.65 | 232.50 | 309.15 | 0.00 | 0.00 |
December | 528.01 | 790.87 | 472.30 | 187.13 | 285.17 | 0.00 | 0.00 |
Annual Sum or Average | 1214.55 | 311.71 | 624.23 | 231.52 | 392.70 | 0.00 | 0.00 |
Minimum of Months | 507.59 | 3.91 | 472.30 | 90.97 | 285.17 | 0.00 | 0.00 |
Maximum of Months | 2034.95 | 791.13 | 861.65 | 401.75 | 472.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2134.52 | 1232.47 | 1556.24 | 945.61 | 610.63 | 0.00 | 0.00 |
February | 2208.99 | 1008.99 | 1479.75 | 821.90 | 657.86 | 0.00 | 0.00 |
March | 2225.54 | 624.51 | 1265.23 | 558.84 | 706.39 | 0.00 | 0.00 |
April | 2112.61 | 230.44 | 888.70 | 250.82 | 637.88 | 0.00 | 0.00 |
May | 1981.97 | 38.73 | 639.09 | 47.31 | 591.78 | 0.00 | 0.00 |
June | 1967.28 | 28.96 | 584.60 | 9.98 | 574.63 | 0.00 | 0.00 |
July | 1811.51 | 5.91 | 609.80 | 8.39 | 601.41 | 0.00 | 0.00 |
August | 1698.16 | 22.68 | 646.87 | 34.55 | 612.32 | 0.00 | 0.00 |
September | 1894.55 | 97.44 | 867.18 | 225.08 | 642.10 | 0.00 | 0.00 |
October | 2795.60 | 495.90 | 1491.89 | 833.06 | 658.82 | 0.00 | 0.00 |
November | 3037.48 | 920.85 | 1863.45 | 1231.70 | 631.75 | 0.00 | 0.00 |
December | 2369.99 | 1227.53 | 1663.08 | 1042.13 | 620.95 | 0.00 | 0.00 |
Annual Sum or Average | 2185.60 | 492.23 | 1127.64 | 498.92 | 628.72 | 0.00 | 0.00 |
Minimum of Months | 1698.16 | 5.91 | 584.60 | 8.39 | 574.63 | 0.00 | 0.00 |
Maximum of Months | 3037.48 | 1232.47 | 1863.45 | 1231.70 | 706.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 560.49 | 858.98 | 478.10 | 186.06 | 292.04 | 0.00 | 0.00 |
February | 746.37 | 686.45 | 546.72 | 201.48 | 345.24 | 0.00 | 0.00 |
March | 1182.97 | 419.72 | 708.95 | 283.39 | 425.56 | 0.00 | 0.00 |
April | 1786.51 | 156.64 | 861.72 | 404.11 | 457.61 | 0.00 | 0.00 |
May | 1983.91 | 29.87 | 815.97 | 346.12 | 469.85 | 0.00 | 0.00 |
June | 1980.75 | 21.27 | 766.41 | 297.70 | 468.72 | 0.00 | 0.00 |
July | 1482.55 | 4.60 | 568.72 | 110.62 | 458.10 | 0.00 | 0.00 |
August | 1275.77 | 15.42 | 522.31 | 92.83 | 429.48 | 0.00 | 0.00 |
September | 1213.91 | 65.25 | 574.15 | 168.56 | 405.60 | 0.00 | 0.00 |
October | 1137.31 | 328.22 | 597.61 | 237.97 | 359.64 | 0.00 | 0.00 |
November | 854.40 | 618.29 | 540.63 | 230.41 | 310.22 | 0.00 | 0.00 |
December | 561.17 | 837.01 | 462.62 | 176.41 | 286.21 | 0.00 | 0.00 |
Annual Sum or Average | 1231.98 | 335.27 | 620.21 | 227.67 | 392.54 | 0.00 | 0.00 |
Minimum of Months | 560.49 | 4.60 | 462.62 | 92.83 | 286.21 | 0.00 | 0.00 |
Maximum of Months | 1983.91 | 858.98 | 861.72 | 404.11 | 469.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.630372E+09 | 0.314877E+10 | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.00 | 0.00 |
February | 0.100641E+10 | 0.227269E+10 | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.00 | 0.00 |
March | 0.203940E+10 | 0.153134E+10 | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.00 | 0.00 |
April | 0.341972E+10 | 0.536917E+09 | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.00 | 0.00 |
May | 0.491709E+10 | 0.104927E+09 | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.00 | 0.00 |
June | 0.517186E+10 | 76928853.64 | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.00 | 0.00 |
July | 0.473174E+10 | 17107775.96 | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.00 | 0.00 |
August | 0.398206E+10 | 57265983.93 | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.00 | 0.00 |
September | 0.299788E+10 | 0.223481E+09 | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.00 | 0.00 |
October | 0.226894E+10 | 0.119594E+10 | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.00 | 0.00 |
November | 0.123761E+10 | 0.217745E+10 | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.00 | 0.00 |
December | 0.697525E+09 | 0.308941E+10 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331006E+11 | 0.144322E+11 | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.630372E+09 | 17107775.96 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517186E+10 | 0.314877E+10 | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142834E+10 | 0.193756E+10 | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.00 | 0.00 |
February | 0.189396E+10 | 0.142857E+10 | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.00 | 0.00 |
March | 0.316643E+10 | 0.982797E+09 | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.00 | 0.00 |
April | 0.458602E+10 | 0.361580E+09 | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.00 | 0.00 |
May | 0.541494E+10 | 68866849.52 | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.00 | 0.00 |
June | 0.475063E+10 | 51429199.52 | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.00 | 0.00 |
July | 0.401504E+10 | 10161375.45 | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.00 | 0.00 |
August | 0.339018E+10 | 38675920.17 | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.00 | 0.00 |
September | 0.305320E+10 | 0.149520E+09 | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.00 | 0.00 |
October | 0.305066E+10 | 0.782278E+09 | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.00 | 0.00 |
November | 0.211907E+10 | 0.138425E+10 | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.00 | 0.00 |
December | 0.148439E+10 | 0.194428E+10 | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383529E+11 | 0.913997E+10 | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142834E+10 | 10161375.45 | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.541494E+10 | 0.194428E+10 | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.579620E+10 | 0.302123E+10 | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.00 | 0.00 |
February | 0.538473E+10 | 0.226489E+10 | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.00 | 0.00 |
March | 0.596148E+10 | 0.157784E+10 | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.00 | 0.00 |
April | 0.544354E+10 | 0.570365E+09 | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.00 | 0.00 |
May | 0.526526E+10 | 0.101563E+09 | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.00 | 0.00 |
June | 0.505360E+10 | 76433788.96 | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.00 | 0.00 |
July | 0.480914E+10 | 15208380.54 | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.00 | 0.00 |
August | 0.451255E+10 | 58651289.66 | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.00 | 0.00 |
September | 0.488722E+10 | 0.238708E+09 | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.00 | 0.00 |
October | 0.748302E+10 | 0.125610E+10 | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.00 | 0.00 |
November | 0.790547E+10 | 0.222256E+10 | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.00 | 0.00 |
December | 0.643031E+10 | 0.302555E+10 | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.689325E+11 | 0.144291E+11 | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.451255E+10 | 15208380.54 | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.790547E+10 | 0.302555E+10 | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154268E+10 | 0.209611E+10 | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.00 | 0.00 |
February | 0.183357E+10 | 0.153117E+10 | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.00 | 0.00 |
March | 0.317286E+10 | 0.105502E+10 | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.00 | 0.00 |
April | 0.461018E+10 | 0.387270E+09 | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.00 | 0.00 |
May | 0.528460E+10 | 78280349.75 | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.00 | 0.00 |
June | 0.510331E+10 | 55499773.76 | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.00 | 0.00 |
July | 0.394338E+10 | 12106283.05 | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.00 | 0.00 |
August | 0.339429E+10 | 39895263.81 | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.00 | 0.00 |
September | 0.313429E+10 | 0.159367E+09 | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.00 | 0.00 |
October | 0.304664E+10 | 0.825881E+09 | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.00 | 0.00 |
November | 0.224279E+10 | 0.147689E+10 | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.00 | 0.00 |
December | 0.155280E+10 | 0.204484E+10 | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388614E+11 | 0.976232E+10 | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154268E+10 | 12106283.05 | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528460E+10 | 0.209611E+10 | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.555635E+09 | 0.357289E+10 | 0.916479E+09 | 0.00 | 0.916479E+09 | 0.00 | 0.00 |
February | 0.986994E+09 | 0.245363E+10 | 0.981616E+09 | 0.00 | 0.981616E+09 | 0.00 | 0.00 |
March | 0.208709E+10 | 0.155908E+10 | 0.130959E+10 | 0.00 | 0.130959E+10 | 0.00 | 0.00 |
April | 0.350891E+10 | 0.503871E+09 | 0.137517E+10 | 4663611.29 | 0.137051E+10 | 0.00 | 0.00 |
May | 0.499865E+10 | 88368895.90 | 0.157437E+10 | 44179438.68 | 0.153020E+10 | 0.00 | 0.00 |
June | 0.521546E+10 | 72679402.32 | 0.157716E+10 | 58417603.32 | 0.151874E+10 | 0.00 | 0.00 |
July | 0.472970E+10 | 22907147.99 | 0.160728E+10 | 25452076.62 | 0.158183E+10 | 0.00 | 0.00 |
August | 0.394961E+10 | 76934732.74 | 0.147553E+10 | 4598532.45 | 0.147093E+10 | 0.00 | 0.00 |
September | 0.296167E+10 | 0.280595E+09 | 0.127233E+10 | 89339.55 | 0.127224E+10 | 0.00 | 0.00 |
October | 0.223443E+10 | 0.133468E+10 | 0.113899E+10 | 0.00 | 0.113899E+10 | 0.00 | 0.00 |
November | 0.116375E+10 | 0.247520E+10 | 0.933617E+09 | 0.00 | 0.933617E+09 | 0.00 | 0.00 |
December | 0.588308E+09 | 0.356076E+10 | 0.894042E+09 | 0.00 | 0.894042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329802E+11 | 0.160016E+11 | 0.150562E+11 | 0.137401E+09 | 0.149188E+11 | 0.00 | 0.00 |
Minimum of Months | 0.555635E+09 | 22907147.99 | 0.894042E+09 | 0.00 | 0.894042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521546E+10 | 0.357289E+10 | 0.160728E+10 | 58417603.32 | 0.158183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.134166E+10 | 0.222460E+10 | 0.130886E+10 | 0.525357E+09 | 0.783505E+09 | 0.00 | 0.00 |
February | 0.187062E+10 | 0.156753E+10 | 0.143622E+10 | 0.592937E+09 | 0.843284E+09 | 0.00 | 0.00 |
March | 0.319822E+10 | 0.102483E+10 | 0.193976E+10 | 0.800661E+09 | 0.113910E+10 | 0.00 | 0.00 |
April | 0.464342E+10 | 0.360201E+09 | 0.223336E+10 | 0.104130E+10 | 0.119206E+10 | 0.00 | 0.00 |
May | 0.546147E+10 | 66464489.90 | 0.227152E+10 | 0.100706E+10 | 0.126446E+10 | 0.00 | 0.00 |
June | 0.477544E+10 | 51697803.82 | 0.178908E+10 | 0.593613E+09 | 0.119547E+10 | 0.00 | 0.00 |
July | 0.400634E+10 | 14864870.15 | 0.155380E+10 | 0.328119E+09 | 0.122568E+10 | 0.00 | 0.00 |
August | 0.336728E+10 | 54121847.65 | 0.140004E+10 | 0.243638E+09 | 0.115640E+10 | 0.00 | 0.00 |
September | 0.303204E+10 | 0.196151E+09 | 0.144753E+10 | 0.403678E+09 | 0.104385E+10 | 0.00 | 0.00 |
October | 0.302911E+10 | 0.889104E+09 | 0.163621E+10 | 0.660917E+09 | 0.975290E+09 | 0.00 | 0.00 |
November | 0.206216E+10 | 0.158337E+10 | 0.140394E+10 | 0.602631E+09 | 0.801306E+09 | 0.00 | 0.00 |
December | 0.138218E+10 | 0.225056E+10 | 0.126498E+10 | 0.501190E+09 | 0.763789E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.381700E+11 | 0.102835E+11 | 0.196853E+11 | 0.730111E+10 | 0.123842E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134166E+10 | 14864870.15 | 0.126498E+10 | 0.243638E+09 | 0.763789E+09 | 0.00 | 0.00 |
Maximum of Months | 0.546147E+10 | 0.225056E+10 | 0.227152E+10 | 0.104130E+10 | 0.126446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.575615E+10 | 0.348444E+10 | 0.416806E+10 | 0.253261E+10 | 0.163545E+10 | 0.00 | 0.00 |
February | 0.539607E+10 | 0.251214E+10 | 0.357969E+10 | 0.198825E+10 | 0.159143E+10 | 0.00 | 0.00 |
March | 0.601862E+10 | 0.166488E+10 | 0.338866E+10 | 0.149673E+10 | 0.189192E+10 | 0.00 | 0.00 |
April | 0.549495E+10 | 0.566474E+09 | 0.230343E+10 | 0.650094E+09 | 0.165334E+10 | 0.00 | 0.00 |
May | 0.526926E+10 | 93379290.30 | 0.171170E+10 | 0.126710E+09 | 0.158499E+10 | 0.00 | 0.00 |
June | 0.502330E+10 | 74130769.91 | 0.151525E+10 | 25857015.52 | 0.148940E+10 | 0.00 | 0.00 |
July | 0.476064E+10 | 22289845.71 | 0.163323E+10 | 22463544.07 | 0.161077E+10 | 0.00 | 0.00 |
August | 0.444614E+10 | 82020071.75 | 0.173251E+10 | 92528349.50 | 0.163998E+10 | 0.00 | 0.00 |
September | 0.483049E+10 | 0.321647E+09 | 0.224764E+10 | 0.583377E+09 | 0.166427E+10 | 0.00 | 0.00 |
October | 0.743230E+10 | 0.146751E+10 | 0.399572E+10 | 0.223119E+10 | 0.176454E+10 | 0.00 | 0.00 |
November | 0.786745E+10 | 0.258645E+10 | 0.482987E+10 | 0.319243E+10 | 0.163744E+10 | 0.00 | 0.00 |
December | 0.634839E+10 | 0.351457E+10 | 0.445422E+10 | 0.279113E+10 | 0.166309E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.686438E+11 | 0.163899E+11 | 0.355600E+11 | 0.157334E+11 | 0.198266E+11 | 0.00 | 0.00 |
Minimum of Months | 0.444614E+10 | 22289845.71 | 0.151525E+10 | 22463544.07 | 0.148940E+10 | 0.00 | 0.00 |
Maximum of Months | 0.786745E+10 | 0.351457E+10 | 0.482987E+10 | 0.319243E+10 | 0.189192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149755E+10 | 0.240647E+10 | 0.128051E+10 | 0.498326E+09 | 0.782189E+09 | 0.00 | 0.00 |
February | 0.182460E+10 | 0.168551E+10 | 0.132260E+10 | 0.487411E+09 | 0.835186E+09 | 0.00 | 0.00 |
March | 0.320704E+10 | 0.110918E+10 | 0.189883E+10 | 0.759026E+09 | 0.113980E+10 | 0.00 | 0.00 |
April | 0.466366E+10 | 0.391366E+09 | 0.223356E+10 | 0.104745E+10 | 0.118611E+10 | 0.00 | 0.00 |
May | 0.531864E+10 | 77825425.30 | 0.218547E+10 | 0.927027E+09 | 0.125844E+10 | 0.00 | 0.00 |
June | 0.511686E+10 | 57938384.63 | 0.198652E+10 | 0.771614E+09 | 0.121491E+10 | 0.00 | 0.00 |
July | 0.393236E+10 | 17132937.89 | 0.152324E+10 | 0.296269E+09 | 0.122697E+10 | 0.00 | 0.00 |
August | 0.336669E+10 | 55686389.76 | 0.139893E+10 | 0.248632E+09 | 0.115030E+10 | 0.00 | 0.00 |
September | 0.311190E+10 | 0.210968E+09 | 0.148819E+10 | 0.436888E+09 | 0.105130E+10 | 0.00 | 0.00 |
October | 0.302561E+10 | 0.945805E+09 | 0.160061E+10 | 0.637356E+09 | 0.963250E+09 | 0.00 | 0.00 |
November | 0.219574E+10 | 0.170614E+10 | 0.140130E+10 | 0.597224E+09 | 0.804078E+09 | 0.00 | 0.00 |
December | 0.147942E+10 | 0.237821E+10 | 0.123907E+10 | 0.472485E+09 | 0.766588E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387401E+11 | 0.110422E+11 | 0.195588E+11 | 0.717971E+10 | 0.123791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147942E+10 | 17132937.89 | 0.123907E+10 | 0.248632E+09 | 0.766588E+09 | 0.00 | 0.00 |
Maximum of Months | 0.531864E+10 | 0.240647E+10 | 0.223356E+10 | 0.104745E+10 | 0.125844E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.561006E+09 | 0.347628E+10 | 0.916498E+09 | 0.00 | 0.916498E+09 | 0.00 | 0.00 |
February | 0.957222E+09 | 0.247818E+10 | 0.981636E+09 | 0.00 | 0.981636E+09 | 0.00 | 0.00 |
March | 0.202877E+10 | 0.163752E+10 | 0.130961E+10 | 0.00 | 0.130961E+10 | 0.00 | 0.00 |
April | 0.344603E+10 | 0.563752E+09 | 0.137519E+10 | 4663748.37 | 0.137053E+10 | 0.00 | 0.00 |
May | 0.495912E+10 | 0.106586E+09 | 0.157440E+10 | 44180737.27 | 0.153022E+10 | 0.00 | 0.00 |
June | 0.521740E+10 | 75885214.08 | 0.157719E+10 | 58419320.43 | 0.151877E+10 | 0.00 | 0.00 |
July | 0.477472E+10 | 17599790.38 | 0.160732E+10 | 25452824.75 | 0.158186E+10 | 0.00 | 0.00 |
August | 0.401691E+10 | 59474434.45 | 0.147556E+10 | 4598667.62 | 0.147096E+10 | 0.00 | 0.00 |
September | 0.301531E+10 | 0.237958E+09 | 0.127236E+10 | 89342.18 | 0.127227E+10 | 0.00 | 0.00 |
October | 0.226687E+10 | 0.127643E+10 | 0.113901E+10 | 0.00 | 0.113901E+10 | 0.00 | 0.00 |
November | 0.119015E+10 | 0.237444E+10 | 0.933635E+09 | 0.00 | 0.933635E+09 | 0.00 | 0.00 |
December | 0.616954E+09 | 0.340964E+10 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330505E+11 | 0.157137E+11 | 0.150565E+11 | 0.137405E+09 | 0.149191E+11 | 0.00 | 0.00 |
Minimum of Months | 0.561006E+09 | 17599790.38 | 0.894061E+09 | 0.00 | 0.894061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521740E+10 | 0.347628E+10 | 0.160732E+10 | 58419320.43 | 0.158186E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135953E+10 | 0.211896E+10 | 0.130888E+10 | 0.525367E+09 | 0.783516E+09 | 0.00 | 0.00 |
February | 0.185588E+10 | 0.153676E+10 | 0.143624E+10 | 0.592949E+09 | 0.843295E+09 | 0.00 | 0.00 |
March | 0.316071E+10 | 0.103719E+10 | 0.193979E+10 | 0.800676E+09 | 0.113911E+10 | 0.00 | 0.00 |
April | 0.460950E+10 | 0.376175E+09 | 0.223340E+10 | 0.104132E+10 | 0.119207E+10 | 0.00 | 0.00 |
May | 0.545041E+10 | 69566048.92 | 0.227155E+10 | 0.100708E+10 | 0.126447E+10 | 0.00 | 0.00 |
June | 0.478580E+10 | 50205356.21 | 0.178911E+10 | 0.593624E+09 | 0.119548E+10 | 0.00 | 0.00 |
July | 0.404708E+10 | 10460201.30 | 0.155382E+10 | 0.328126E+09 | 0.122570E+10 | 0.00 | 0.00 |
August | 0.341615E+10 | 39772903.68 | 0.140006E+10 | 0.243643E+09 | 0.115642E+10 | 0.00 | 0.00 |
September | 0.306815E+10 | 0.157692E+09 | 0.144755E+10 | 0.403686E+09 | 0.104386E+10 | 0.00 | 0.00 |
October | 0.305063E+10 | 0.826721E+09 | 0.163623E+10 | 0.660930E+09 | 0.975302E+09 | 0.00 | 0.00 |
November | 0.208390E+10 | 0.148829E+10 | 0.140396E+10 | 0.602642E+09 | 0.801316E+09 | 0.00 | 0.00 |
December | 0.141423E+10 | 0.211827E+10 | 0.126500E+10 | 0.501200E+09 | 0.763799E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383020E+11 | 0.983006E+10 | 0.196856E+11 | 0.730125E+10 | 0.123843E+11 | 0.00 | 0.00 |
Minimum of Months | 0.135953E+10 | 10460201.30 | 0.126500E+10 | 0.243643E+09 | 0.763799E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545041E+10 | 0.211896E+10 | 0.227155E+10 | 0.104132E+10 | 0.126447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.571710E+10 | 0.330106E+10 | 0.416822E+10 | 0.253272E+10 | 0.163550E+10 | 0.00 | 0.00 |
February | 0.534399E+10 | 0.244094E+10 | 0.357982E+10 | 0.198833E+10 | 0.159149E+10 | 0.00 | 0.00 |
March | 0.596087E+10 | 0.167270E+10 | 0.338878E+10 | 0.149680E+10 | 0.189198E+10 | 0.00 | 0.00 |
April | 0.547587E+10 | 0.597290E+09 | 0.230351E+10 | 0.650121E+09 | 0.165339E+10 | 0.00 | 0.00 |
May | 0.530851E+10 | 0.103746E+09 | 0.171174E+10 | 0.126716E+09 | 0.158503E+10 | 0.00 | 0.00 |
June | 0.509919E+10 | 75074923.21 | 0.151529E+10 | 25858088.57 | 0.148944E+10 | 0.00 | 0.00 |
July | 0.485195E+10 | 15817767.13 | 0.163328E+10 | 22464476.29 | 0.161082E+10 | 0.00 | 0.00 |
August | 0.454836E+10 | 60755801.59 | 0.173257E+10 | 92532189.35 | 0.164004E+10 | 0.00 | 0.00 |
September | 0.491068E+10 | 0.252572E+09 | 0.224772E+10 | 0.583401E+09 | 0.166432E+10 | 0.00 | 0.00 |
October | 0.748773E+10 | 0.132823E+10 | 0.399587E+10 | 0.223128E+10 | 0.176459E+10 | 0.00 | 0.00 |
November | 0.787315E+10 | 0.238685E+10 | 0.483006E+10 | 0.319256E+10 | 0.163749E+10 | 0.00 | 0.00 |
December | 0.634779E+10 | 0.328782E+10 | 0.445439E+10 | 0.279125E+10 | 0.166315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.689252E+11 | 0.155228E+11 | 0.355613E+11 | 0.157340E+11 | 0.198272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454836E+10 | 15817767.13 | 0.151529E+10 | 22464476.29 | 0.148944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.787315E+10 | 0.330106E+10 | 0.483006E+10 | 0.319256E+10 | 0.189198E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150122E+10 | 0.230068E+10 | 0.128053E+10 | 0.498334E+09 | 0.782197E+09 | 0.00 | 0.00 |
February | 0.180561E+10 | 0.166065E+10 | 0.132261E+10 | 0.487419E+09 | 0.835194E+09 | 0.00 | 0.00 |
March | 0.316845E+10 | 0.112418E+10 | 0.189885E+10 | 0.759038E+09 | 0.113981E+10 | 0.00 | 0.00 |
April | 0.463063E+10 | 0.406007E+09 | 0.223358E+10 | 0.104747E+10 | 0.118612E+10 | 0.00 | 0.00 |
May | 0.531370E+10 | 80006460.48 | 0.218549E+10 | 0.927042E+09 | 0.125845E+10 | 0.00 | 0.00 |
June | 0.513410E+10 | 55142749.44 | 0.198654E+10 | 0.771627E+09 | 0.121492E+10 | 0.00 | 0.00 |
July | 0.397086E+10 | 12320954.94 | 0.152325E+10 | 0.296274E+09 | 0.122698E+10 | 0.00 | 0.00 |
August | 0.341702E+10 | 41290796.65 | 0.139895E+10 | 0.248636E+09 | 0.115031E+10 | 0.00 | 0.00 |
September | 0.314646E+10 | 0.169137E+09 | 0.148821E+10 | 0.436895E+09 | 0.105131E+10 | 0.00 | 0.00 |
October | 0.304617E+10 | 0.879103E+09 | 0.160063E+10 | 0.637367E+09 | 0.963259E+09 | 0.00 | 0.00 |
November | 0.221462E+10 | 0.160262E+10 | 0.140132E+10 | 0.597234E+09 | 0.804086E+09 | 0.00 | 0.00 |
December | 0.150303E+10 | 0.224185E+10 | 0.123909E+10 | 0.472493E+09 | 0.766596E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388519E+11 | 0.105730E+11 | 0.195591E+11 | 0.717982E+10 | 0.123792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.150122E+10 | 12320954.94 | 0.123909E+10 | 0.248636E+09 | 0.766596E+09 | 0.00 | 0.00 |
Maximum of Months | 0.531370E+10 | 0.230068E+10 | 0.223358E+10 | 0.104747E+10 | 0.125845E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.392571E+10 | -0.369108E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234627178.9 | 60.05 | 0.00 | 0.00 |
February | 0.349617E+10 | -0.328574E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -210421133.0 | 60.05 | 0.00 | 0.00 |
March | 0.386678E+10 | -0.363450E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232281060.6 | 60.05 | 0.00 | 0.00 |
April | 0.316916E+10 | -0.294508E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224076062.0 | 60.05 | 0.00 | 0.00 |
May | 0.303624E+10 | -0.280387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232365637.7 | 60.05 | 0.00 | 0.00 |
June | 0.273204E+10 | -0.250665E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225388690.3 | 60.05 | 0.00 | 0.00 |
July | 0.248904E+10 | -0.225654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232496383.3 | 60.05 | 0.00 | 0.00 |
August | 0.281335E+10 | -0.258092E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232432117.2 | 60.05 | 0.00 | 0.00 |
September | 0.278646E+10 | -0.256232E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224133724.1 | 60.05 | 0.00 | 0.00 |
October | 0.321506E+10 | -0.298370E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231353381.0 | 60.05 | 0.00 | 0.00 |
November | 0.349593E+10 | -0.327156E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224370746.6 | 60.05 | 0.00 | 0.00 |
December | 0.372213E+10 | -0.348864E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233489588.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.387481E+11 | -0.360106E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273744E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.248904E+10 | -0.369108E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234627178.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.392571E+10 | -0.225654E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -210421133.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 6081.91 | 35.36 | 298.33 | 288.50 | 1375.40 | 25.15 | 252.83 | 270.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:09 | 3645.73 | 28.75 | 198.00 | 272.83 | 1214.39 | 21.04 | 174.33 | 247.83 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:49 | 1873.39 | 19.10 | 7.50 | 326.67 | 1034.98 | 20.97 | 185.17 | 296.17 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:30 | 1254.11 | 17.59 | 0.00 | 331.33 | 750.66 | 19.71 | 117.17 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1054.85 | 17.39 | 0.00 | 352.33 | 623.52 | 19.60 | 71.17 | 315.83 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1044.49 | 17.05 | 0.00 | 337.00 | 602.40 | 19.22 | 69.50 | 297.00 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1179.81 | 17.50 | 0.00 | 336.17 | 618.67 | 19.57 | 72.00 | 289.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1331.84 | 17.49 | 0.00 | 324.83 | 675.58 | 19.53 | 116.67 | 278.50 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:30 | 1629.65 | 18.20 | 0.00 | 304.67 | 856.21 | 20.33 | 177.00 | 269.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2791.57 | 20.26 | 42.67 | 308.17 | 1172.04 | 20.77 | 170.17 | 283.17 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 8233.82 | 36.60 | 310.50 | 288.67 | 1450.08 | 24.47 | 217.00 | 274.83 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:30 | 6423.88 | 36.70 | 308.83 | 288.33 | 1617.05 | 27.38 | 277.33 | 280.83 |
Annual Sum or Average | 4237.50 | 0.53 | 2869.59 | 22.89 | 1165.83 | 3759.50 | 971.39 | 21.31 | 1900.33 | 3404.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1044.49 | 17.05 | 0.00 | 272.83 | 602.40 | 19.22 | 69.50 | 247.83 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8233.82 | 36.70 | 310.50 | 352.33 | 1617.05 | 27.38 | 277.33 | 315.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1770.82 | 22.21 | 107.00 | 271.00 | 944.84 | 22.94 | 81.50 | 228.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2200.28 | 22.21 | 100.50 | 259.67 | 1171.01 | 23.00 | 74.33 | 227.17 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:30 | 2085.66 | 20.16 | 88.33 | 320.50 | 1101.78 | 22.38 | 70.83 | 291.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-06:49 | 2567.71 | 20.92 | 110.67 | 330.83 | 1358.50 | 21.89 | 81.33 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:10 | 2652.55 | 20.27 | 116.50 | 358.50 | 1039.38 | 20.87 | 66.67 | 328.33 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2108.36 | 19.28 | 101.00 | 339.33 | 890.43 | 19.96 | 52.00 | 304.17 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:10 | 1744.74 | 19.37 | 96.50 | 341.50 | 785.76 | 19.96 | 46.17 | 295.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-06:40 | 1601.25 | 19.33 | 98.17 | 326.00 | 744.40 | 19.53 | 42.33 | 275.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1787.14 | 20.41 | 90.17 | 301.00 | 914.62 | 21.52 | 65.17 | 263.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1969.21 | 21.16 | 100.83 | 299.33 | 1004.89 | 21.92 | 70.33 | 268.67 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1772.01 | 20.93 | 88.00 | 271.00 | 906.96 | 21.69 | 59.83 | 241.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1853.80 | 22.89 | 112.50 | 264.83 | 995.96 | 23.57 | 91.67 | 232.33 |
Annual Sum or Average | 4237.50 | 0.53 | 2022.02 | 20.68 | 1210.17 | 3683.50 | 987.28 | 21.52 | 802.17 | 3259.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1601.25 | 19.28 | 88.00 | 259.67 | 744.40 | 19.53 | 42.33 | 227.17 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2652.55 | 22.89 | 116.50 | 358.50 | 1358.50 | 23.57 | 91.67 | 328.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.57 | 0.48 | 01-JAN-09:39 | 577.30 | 15.20 | 0.00 | 252.17 | 358.43 | 17.55 | 0.00 | 179.33 |
February | 303.83 | 0.55 | 0.48 | 01-FEB-09:09 | 665.98 | 16.09 | 0.00 | 252.67 | 411.81 | 18.37 | 0.00 | 194.00 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:30 | 787.65 | 17.24 | 0.00 | 317.67 | 486.03 | 19.44 | 0.00 | 271.33 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 849.38 | 17.31 | 0.00 | 333.83 | 532.13 | 19.42 | 11.83 | 306.33 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 1015.59 | 17.91 | 1.17 | 368.00 | 600.96 | 20.13 | 110.33 | 342.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1127.21 | 18.54 | 18.50 | 350.00 | 638.44 | 21.77 | 162.67 | 319.17 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1150.86 | 19.24 | 29.33 | 347.67 | 607.47 | 21.24 | 109.50 | 305.83 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 1029.30 | 17.24 | 0.00 | 329.00 | 542.25 | 19.24 | 41.83 | 281.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 892.80 | 17.15 | 0.00 | 302.00 | 500.51 | 19.21 | 1.67 | 253.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 696.69 | 16.06 | 0.00 | 291.33 | 440.31 | 18.35 | 0.00 | 243.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 591.40 | 15.58 | 0.00 | 256.17 | 388.54 | 18.08 | 0.00 | 202.83 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:09 | 568.53 | 15.28 | 0.00 | 248.00 | 356.48 | 17.70 | 0.00 | 177.33 |
Annual Sum or Average | 4237.50 | 0.54 | 845.28 | 17.00 | 49.00 | 3648.50 | 496.44 | 19.30 | 437.83 | 3076.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 568.53 | 15.20 | 0.00 | 248.00 | 356.48 | 17.55 | 0.00 | 177.33 | |
Maximum of Months | 406.00 | 0.57 | 0.48 | 1150.86 | 19.24 | 29.33 | 368.00 | 638.44 | 21.77 | 162.67 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1773.99 | 21.91 | 104.50 | 269.83 | 930.56 | 22.54 | 74.67 | 227.17 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2104.43 | 21.85 | 103.50 | 264.83 | 850.02 | 21.02 | 48.17 | 228.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:50 | 2034.70 | 20.04 | 87.83 | 321.00 | 1069.54 | 22.21 | 69.33 | 292.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2343.62 | 18.89 | 84.50 | 333.67 | 1233.89 | 20.04 | 54.67 | 306.17 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:40 | 2253.63 | 14.18 | 0.00 | 354.17 | 1174.39 | 17.53 | 0.00 | 326.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:20 | 2237.26 | 14.25 | 0.00 | 339.83 | 928.18 | 17.41 | 0.00 | 306.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1691.82 | 15.00 | 3.50 | 339.00 | 775.05 | 17.77 | 0.00 | 293.50 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:00 | 1577.68 | 16.81 | 53.17 | 324.67 | 793.36 | 17.69 | 4.83 | 279.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:30 | 1747.06 | 19.43 | 80.83 | 303.83 | 892.75 | 20.50 | 52.50 | 264.33 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2091.28 | 21.21 | 103.00 | 295.67 | 1065.30 | 22.15 | 74.50 | 267.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:30 | 1817.51 | 20.52 | 85.00 | 271.33 | 931.51 | 22.54 | 67.17 | 244.33 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:09 | 1595.36 | 20.69 | 87.67 | 269.83 | 844.25 | 22.66 | 70.17 | 236.83 |
Annual Sum or Average | 4237.50 | 0.53 | 1948.56 | 18.51 | 793.50 | 3687.67 | 962.69 | 20.19 | 516.00 | 3273.17 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 1577.68 | 14.18 | 0.00 | 264.83 | 775.05 | 17.41 | 0.00 | 227.17 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 2343.62 | 21.91 | 104.50 | 354.17 | 1233.89 | 22.66 | 74.67 | 326.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 5953.75 | 35.08 | 297.50 | 287.50 | 1279.97 | 22.68 | 85.50 | 267.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:20 | 3529.86 | 27.16 | 196.83 | 271.83 | 1129.27 | 18.12 | 0.00 | 246.00 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1783.68 | 15.41 | 7.50 | 323.67 | 970.49 | 18.57 | 0.00 | 292.83 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:40 | 1199.63 | 14.18 | 0.00 | 329.50 | 714.40 | 17.61 | 0.00 | 298.50 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1016.04 | 13.80 | 0.00 | 350.67 | 600.71 | 17.30 | 0.00 | 313.17 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1007.40 | 13.37 | 0.00 | 335.33 | 581.02 | 16.80 | 0.00 | 294.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:19 | 1136.78 | 13.51 | 0.00 | 334.33 | 592.45 | 16.88 | 0.00 | 284.50 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1281.50 | 13.49 | 0.00 | 322.67 | 644.11 | 16.77 | 0.00 | 275.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 1560.05 | 14.26 | 0.00 | 303.00 | 809.84 | 17.67 | 0.00 | 265.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2683.20 | 16.59 | 41.33 | 307.83 | 1090.43 | 18.11 | 10.00 | 281.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:30 | 8091.22 | 35.52 | 301.67 | 286.50 | 1340.60 | 21.93 | 74.33 | 272.67 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:40 | 6275.40 | 35.55 | 298.83 | 285.50 | 1513.28 | 25.19 | 123.67 | 279.67 |
Annual Sum or Average | 4237.50 | 0.53 | 2787.35 | 19.96 | 1143.67 | 3738.33 | 913.65 | 18.80 | 293.50 | 3371.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1007.40 | 13.37 | 0.00 | 271.83 | 581.02 | 16.77 | 0.00 | 246.00 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8091.22 | 35.55 | 301.67 | 350.67 | 1513.28 | 25.19 | 123.67 | 313.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1676.92 | 19.65 | 85.67 | 265.50 | 907.75 | 22.72 | 77.33 | 225.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2142.64 | 21.76 | 100.50 | 258.17 | 1128.70 | 22.80 | 74.33 | 223.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-07:30 | 2026.42 | 19.67 | 88.33 | 318.33 | 1052.38 | 22.19 | 70.83 | 288.50 |
April | 379.83 | 0.54 | 0.48 | 01-APR-06:49 | 2492.62 | 20.48 | 110.67 | 328.33 | 1306.38 | 21.73 | 81.33 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:19 | 2582.68 | 19.82 | 116.50 | 357.67 | 990.02 | 20.71 | 66.67 | 324.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2056.84 | 18.83 | 101.00 | 338.33 | 850.41 | 19.80 | 52.00 | 302.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-06:19 | 1695.94 | 18.93 | 96.33 | 340.00 | 750.27 | 19.79 | 46.17 | 290.33 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-06:40 | 1552.06 | 18.89 | 97.83 | 324.67 | 711.13 | 19.34 | 42.50 | 271.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1735.46 | 19.77 | 88.17 | 299.00 | 876.70 | 21.34 | 65.33 | 260.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1892.73 | 19.35 | 87.00 | 297.00 | 962.02 | 21.73 | 70.33 | 265.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1718.87 | 20.44 | 88.00 | 268.17 | 866.26 | 21.47 | 58.33 | 238.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1806.74 | 22.43 | 112.50 | 263.33 | 959.95 | 23.35 | 81.67 | 228.67 |
Annual Sum or Average | 4237.50 | 0.54 | 1960.93 | 19.94 | 1172.50 | 3658.50 | 945.71 | 21.33 | 786.83 | 3219.17 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1552.06 | 18.83 | 85.67 | 258.17 | 711.13 | 19.34 | 42.50 | 223.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2582.68 | 22.43 | 116.50 | 357.67 | 1306.38 | 23.35 | 81.67 | 324.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.58 | 0.48 | 01-JAN-09:00 | 555.40 | 11.71 | 0.00 | 249.17 | 346.69 | 15.30 | 0.00 | 171.50 |
February | 303.83 | 0.56 | 0.48 | 01-FEB-09:20 | 641.44 | 12.62 | 0.00 | 249.50 | 398.64 | 16.18 | 0.00 | 188.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:39 | 759.14 | 13.95 | 0.00 | 315.17 | 470.72 | 17.47 | 0.00 | 266.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:40 | 819.56 | 14.14 | 0.00 | 333.00 | 516.36 | 17.59 | 0.00 | 301.83 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 980.17 | 14.31 | 1.17 | 367.00 | 581.15 | 17.90 | 1.17 | 338.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1087.30 | 15.02 | 17.50 | 348.67 | 615.15 | 19.73 | 41.50 | 315.67 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1109.08 | 14.69 | 14.50 | 345.67 | 582.57 | 18.85 | 30.00 | 301.67 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 992.88 | 13.32 | 0.00 | 327.17 | 520.35 | 16.62 | 0.00 | 277.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:49 | 860.73 | 13.51 | 0.00 | 300.50 | 482.05 | 16.87 | 0.00 | 249.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 671.17 | 12.70 | 0.00 | 289.67 | 426.84 | 16.21 | 0.00 | 238.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 568.76 | 12.10 | 0.00 | 253.67 | 376.91 | 15.85 | 0.00 | 196.17 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:20 | 546.63 | 11.76 | 0.00 | 244.50 | 344.80 | 15.43 | 0.00 | 168.67 |
Annual Sum or Average | 4237.50 | 0.54 | 814.74 | 13.41 | 33.17 | 3623.67 | 479.36 | 17.10 | 72.67 | 3014.33 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 546.63 | 11.71 | 0.00 | 244.50 | 344.80 | 15.30 | 0.00 | 168.67 | |
Maximum of Months | 406.00 | 0.58 | 0.48 | 1109.08 | 15.02 | 17.50 | 367.00 | 615.15 | 19.73 | 41.50 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:50 | 1682.22 | 19.63 | 84.17 | 265.50 | 893.94 | 22.44 | 74.83 | 224.33 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2050.02 | 21.46 | 103.50 | 262.17 | 810.86 | 20.90 | 48.17 | 225.50 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:50 | 1975.03 | 19.60 | 87.83 | 319.83 | 1021.42 | 22.08 | 69.33 | 289.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2231.14 | 18.45 | 84.50 | 331.67 | 1180.80 | 19.89 | 54.67 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:49 | 2182.57 | 13.63 | 0.00 | 352.83 | 1127.61 | 17.33 | 0.00 | 323.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:30 | 2177.70 | 13.72 | 0.00 | 338.33 | 882.88 | 17.21 | 0.00 | 303.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1641.27 | 14.44 | 3.50 | 337.50 | 740.14 | 17.56 | 0.00 | 290.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-08:09 | 1528.92 | 16.32 | 53.00 | 322.83 | 759.83 | 17.49 | 4.83 | 275.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:39 | 1698.00 | 19.00 | 80.67 | 301.50 | 853.54 | 20.36 | 52.50 | 260.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2034.76 | 20.82 | 103.00 | 294.67 | 1023.30 | 22.04 | 74.67 | 265.00 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:39 | 1764.51 | 20.10 | 85.00 | 269.17 | 890.16 | 22.29 | 66.00 | 240.83 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:20 | 1547.18 | 20.29 | 87.67 | 268.17 | 793.94 | 21.57 | 59.33 | 231.50 |
Annual Sum or Average | 4237.50 | 0.54 | 1885.28 | 17.91 | 772.83 | 3664.17 | 920.06 | 19.95 | 504.33 | 3233.50 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1528.92 | 13.63 | 0.00 | 262.17 | 740.14 | 17.21 | 0.00 | 224.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2231.14 | 21.46 | 103.50 | 352.83 | 1180.80 | 22.44 | 74.83 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.52 | 0.48 | 01-JAN-07:00 | 5953.68 | 35.08 | 297.50 | 287.50 | 1279.87 | 22.68 | 85.50 | 267.83 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:20 | 3529.76 | 27.17 | 196.83 | 271.83 | 1129.18 | 18.12 | 0.00 | 246.00 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1783.58 | 15.41 | 7.50 | 323.67 | 970.42 | 18.58 | 0.00 | 292.83 |
April | 379.83 | 0.54 | 0.48 | 01-APR-07:40 | 1199.58 | 14.18 | 0.00 | 329.50 | 714.36 | 17.61 | 0.00 | 298.50 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1016.00 | 13.80 | 0.00 | 350.67 | 600.67 | 17.30 | 0.00 | 313.17 |
June | 386.67 | 0.54 | 0.48 | 01-JUN-07:49 | 1007.35 | 13.37 | 0.00 | 335.33 | 580.98 | 16.80 | 0.00 | 294.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:19 | 1136.69 | 13.52 | 0.00 | 334.33 | 592.40 | 16.88 | 0.00 | 284.50 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-07:19 | 1281.40 | 13.49 | 0.00 | 322.67 | 644.05 | 16.78 | 0.00 | 274.83 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-07:40 | 1559.94 | 14.27 | 0.00 | 303.00 | 809.76 | 17.68 | 0.00 | 265.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:19 | 2683.11 | 16.59 | 41.33 | 307.83 | 1090.36 | 18.11 | 10.00 | 281.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:30 | 8091.14 | 35.53 | 301.67 | 286.50 | 1340.51 | 21.93 | 74.33 | 272.67 |
December | 315.50 | 0.51 | 0.48 | 01-DEC-07:40 | 6275.34 | 35.55 | 298.83 | 285.50 | 1513.18 | 25.19 | 123.67 | 279.67 |
Annual Sum or Average | 4237.50 | 0.53 | 2787.27 | 19.96 | 1143.67 | 3738.33 | 913.58 | 18.80 | 293.50 | 3371.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1007.35 | 13.37 | 0.00 | 271.83 | 580.98 | 16.78 | 0.00 | 246.00 | |
Maximum of Months | 406.00 | 0.54 | 0.48 | 8091.14 | 35.55 | 301.67 | 350.67 | 1513.18 | 25.19 | 123.67 | 313.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1676.89 | 19.65 | 85.67 | 265.50 | 907.70 | 22.72 | 77.33 | 225.17 |
February | 303.83 | 0.54 | 0.48 | 01-FEB-07:49 | 2142.60 | 21.76 | 100.50 | 258.17 | 1128.65 | 22.80 | 74.33 | 223.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-07:30 | 2026.37 | 19.68 | 88.33 | 318.33 | 1052.32 | 22.19 | 70.83 | 288.50 |
April | 379.83 | 0.54 | 0.48 | 01-APR-06:49 | 2492.59 | 20.48 | 110.67 | 328.33 | 1306.32 | 21.73 | 81.33 | 301.00 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-06:19 | 2582.63 | 19.82 | 116.50 | 357.67 | 989.97 | 20.71 | 66.67 | 324.67 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-06:00 | 2056.78 | 18.84 | 101.00 | 338.33 | 850.35 | 19.80 | 52.00 | 302.33 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-06:19 | 1695.85 | 18.93 | 96.33 | 339.83 | 750.21 | 19.79 | 46.17 | 290.33 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-06:40 | 1551.97 | 18.89 | 97.83 | 324.67 | 711.06 | 19.34 | 42.50 | 271.00 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-06:49 | 1735.38 | 19.77 | 88.17 | 299.00 | 876.63 | 21.34 | 65.33 | 260.67 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-06:49 | 1892.70 | 19.35 | 87.00 | 297.00 | 961.97 | 21.73 | 70.33 | 265.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-07:10 | 1718.86 | 20.44 | 88.00 | 268.17 | 866.22 | 21.47 | 58.33 | 238.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-07:30 | 1806.71 | 22.43 | 112.50 | 263.33 | 959.91 | 23.35 | 81.67 | 228.67 |
Annual Sum or Average | 4237.50 | 0.54 | 1960.88 | 19.94 | 1172.50 | 3658.33 | 945.66 | 21.33 | 786.83 | 3219.17 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1551.97 | 18.84 | 85.67 | 258.17 | 711.06 | 19.34 | 42.50 | 223.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2582.63 | 22.43 | 116.50 | 357.67 | 1306.32 | 23.35 | 81.67 | 324.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.58 | 0.48 | 01-JAN-09:00 | 555.39 | 11.71 | 0.00 | 249.17 | 346.67 | 15.30 | 0.00 | 171.50 |
February | 303.83 | 0.56 | 0.48 | 01-FEB-09:20 | 641.42 | 12.62 | 0.00 | 249.50 | 398.62 | 16.18 | 0.00 | 188.33 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:39 | 759.12 | 13.95 | 0.00 | 315.17 | 470.69 | 17.47 | 0.00 | 266.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:40 | 819.54 | 14.15 | 0.00 | 333.00 | 516.34 | 17.59 | 0.00 | 301.83 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:40 | 980.13 | 14.32 | 1.17 | 367.00 | 581.11 | 17.90 | 1.17 | 338.83 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1087.25 | 15.03 | 17.50 | 348.67 | 615.10 | 19.73 | 41.50 | 315.67 |
July | 379.83 | 0.52 | 0.48 | 01-JUL-06:40 | 1109.01 | 14.69 | 14.50 | 345.67 | 582.52 | 18.85 | 30.00 | 301.50 |
August | 372.50 | 0.53 | 0.48 | 01-AUG-07:10 | 992.81 | 13.32 | 0.00 | 327.17 | 520.30 | 16.63 | 0.00 | 277.00 |
September | 344.33 | 0.54 | 0.48 | 01-SEP-07:49 | 860.68 | 13.51 | 0.00 | 300.50 | 482.02 | 16.87 | 0.00 | 249.83 |
October | 347.33 | 0.55 | 0.48 | 01-OCT-07:00 | 671.16 | 12.71 | 0.00 | 289.67 | 426.82 | 16.21 | 0.00 | 238.00 |
November | 317.83 | 0.56 | 0.48 | 01-NOV-08:30 | 568.76 | 12.11 | 0.00 | 253.67 | 376.89 | 15.85 | 0.00 | 196.17 |
December | 315.50 | 0.57 | 0.48 | 01-DEC-09:20 | 546.62 | 11.76 | 0.00 | 244.50 | 344.78 | 15.44 | 0.00 | 168.67 |
Annual Sum or Average | 4237.50 | 0.54 | 814.71 | 13.41 | 33.17 | 3623.67 | 479.33 | 17.10 | 72.67 | 3014.17 | ||
Minimum of Months | 303.83 | 0.52 | 0.48 | 546.62 | 11.71 | 0.00 | 244.50 | 344.78 | 15.30 | 0.00 | 168.67 | |
Maximum of Months | 406.00 | 0.58 | 0.48 | 1109.01 | 15.03 | 17.50 | 367.00 | 615.10 | 19.73 | 41.50 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:50 | 1682.19 | 19.63 | 84.17 | 265.50 | 893.89 | 22.44 | 74.83 | 224.33 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2049.99 | 21.46 | 103.50 | 262.17 | 810.81 | 20.90 | 48.17 | 225.50 |
March | 364.50 | 0.53 | 0.48 | 01-MAR-08:50 | 1974.99 | 19.60 | 87.83 | 319.83 | 1021.37 | 22.08 | 69.33 | 289.67 |
April | 379.83 | 0.53 | 0.48 | 01-APR-08:20 | 2231.10 | 18.45 | 84.50 | 331.67 | 1180.75 | 19.89 | 54.67 | 303.33 |
May | 406.00 | 0.53 | 0.48 | 01-MAY-07:49 | 2182.52 | 13.64 | 0.00 | 352.83 | 1127.55 | 17.34 | 0.00 | 323.50 |
June | 386.67 | 0.53 | 0.48 | 01-JUN-08:30 | 2177.63 | 13.72 | 0.00 | 338.33 | 882.82 | 17.21 | 0.00 | 303.83 |
July | 379.83 | 0.53 | 0.48 | 01-JUL-07:40 | 1641.17 | 14.44 | 3.50 | 337.50 | 740.08 | 17.56 | 0.00 | 290.17 |
August | 372.50 | 0.54 | 0.48 | 01-AUG-08:09 | 1528.82 | 16.32 | 53.00 | 322.83 | 759.76 | 17.49 | 4.83 | 275.33 |
September | 344.33 | 0.53 | 0.48 | 01-SEP-08:39 | 1697.92 | 19.00 | 80.67 | 301.50 | 853.47 | 20.36 | 52.50 | 260.50 |
October | 347.33 | 0.54 | 0.48 | 01-OCT-08:09 | 2034.73 | 20.82 | 103.00 | 294.67 | 1023.25 | 22.04 | 74.67 | 265.00 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:39 | 1764.49 | 20.10 | 85.00 | 269.17 | 890.11 | 22.29 | 66.00 | 240.83 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-09:20 | 1547.15 | 20.29 | 87.67 | 268.17 | 793.89 | 21.57 | 59.33 | 231.50 |
Annual Sum or Average | 4237.50 | 0.54 | 1885.23 | 17.92 | 772.83 | 3664.17 | 920.00 | 19.95 | 504.33 | 3233.50 | ||
Minimum of Months | 303.83 | 0.53 | 0.48 | 1528.82 | 13.64 | 0.00 | 262.17 | 740.08 | 17.21 | 0.00 | 224.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 2231.10 | 21.46 | 103.50 | 352.83 | 1180.75 | 22.44 | 74.83 | 323.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119120E+09 | 3174.21 | 03-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2104463.61 | 688.30 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16788525.79 | 2078.28 | 23-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119120E+09 | 3174.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.642120E+09 | 7333.66 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.436137E+09 | 7333.66 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96557609.11 | 7333.66 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124022E+09 | 7333.66 | 22-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.498772E+09 | 7333.66 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.642120E+09 | 7333.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 21195487.08 | 4858.52 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 278897.30 | 1465.79 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131007.31 | 607.87 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21605391.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21195487.08 | 4858.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 72890633.99 | 7333.68 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1774214.57 | 1776.44 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1314322.80 | 2031.01 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75979171.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72890633.99 | 7333.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 35942870.20 | 4876.06 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2140235.65 | 1901.08 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 979218.04 | 1330.84 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39062323.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35942870.20 | 4876.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295055E+09 | 4408.09 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14798569.87 | 1567.27 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58486794.30 | 3103.65 | 23-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295055E+09 | 4408.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 15173862.35 | 25425.12 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15173862.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15173862.35 | 25425.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70118231.83 | 8615.36 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3259639.58 | 4509.38 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5410451.90 | 8276.02 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78788323.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70118231.83 | 8615.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 79562252.34 | 5683.78 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5310491.51 | 5683.78 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11889738.30 | 5683.78 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96762482.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79562252.34 | 5683.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163303E+09 | 8626.08 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13298785.99 | 6104.08 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24205448.20 | 8626.08 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163303E+09 | 8626.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139340E+09 | 5701.43 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17528709.84 | 5701.43 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31896940.47 | 5701.43 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139340E+09 | 5701.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.599889E+09 | 5002.17 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96331726.93 | 4526.28 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2285044.84 | 1025.44 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182669E+09 | 5002.17 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.599889E+09 | 5002.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350225E+09 | 27865.62 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2063938.93 | 1435.55 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27372710.04 | 22965.81 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350225E+09 | 27865.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388953E+09 | 11080.61 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87082990.73 | 11080.61 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5451395.48 | 7259.99 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168016E+09 | 11080.61 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388953E+09 | 11080.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327500E+09 | 7215.79 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66500072.56 | 7215.79 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 128657.59 | 857.72 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7573098.01 | 7215.79 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162349E+09 | 7215.79 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327500E+09 | 7215.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.720062E+09 | 11087.34 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150325E+09 | 11087.34 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94378.97 | 629.19 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19043910.69 | 11087.34 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337763E+09 | 11087.34 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.720062E+09 | 11087.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.531421E+09 | 7225.76 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133705E+09 | 7225.76 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 846203.97 | 1638.28 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20140460.79 | 7225.76 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279179E+09 | 7225.76 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.965292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.531421E+09 | 7225.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198780E+11 | 0.172309E+11 | 35996.60 | 12-JAN-15:10 | 35996.60 | 0.00 |
February | 0.00 | 0.00 | 0.296233E+11 | 0.265834E+11 | 51113.11 | 22-FEB-15:30 | 51113.11 | 0.00 |
March | 0.00 | 0.00 | 0.549596E+11 | 0.514321E+11 | 71151.60 | 29-MAR-11:10 | 52172.69 | 0.00 |
April | 0.00 | 0.00 | 0.779604E+11 | 0.732578E+11 | 99220.30 | 27-APR-06:03 | 81969.19 | 0.00 |
May | 0.00 | 0.00 | 0.113244E+12 | 0.953769E+11 | 129225.70 | 19-MAY-04:02 | 89367.85 | 0.00 |
June | 0.00 | 0.00 | 0.128505E+12 | 0.969860E+11 | 132524.30 | 27-JUN-04:02 | 82744.94 | 0.00 |
July | 0.00 | 0.00 | 0.139627E+12 | 0.897100E+11 | 133972.69 | 20-JUL-04:02 | 78984.61 | 0.00 |
August | 0.00 | 0.00 | 0.142204E+12 | 0.886068E+11 | 135203.92 | 27-AUG-16:52 | 73647.01 | 0.00 |
September | 0.00 | 0.00 | 0.114951E+12 | 0.772008E+11 | 132370.42 | 06-SEP-04:02 | 83184.15 | 0.00 |
October | 0.00 | 0.00 | 0.789890E+11 | 0.680651E+11 | 114235.24 | 04-OCT-04:02 | 78242.08 | 0.00 |
November | 0.00 | 0.00 | 0.484901E+11 | 0.451458E+11 | 65628.14 | 06-NOV-11:30 | 53515.79 | 0.00 |
December | 0.00 | 0.00 | 0.255024E+11 | 0.230083E+11 | 43242.35 | 01-DEC-15:20 | 43242.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.973933E+12 | 0.752604E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.198780E+11 | 0.172309E+11 | 35996.60 | 35996.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142204E+12 | 0.969860E+11 | 135203.92 | 89367.85 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.145409E+11 | 0.119031E+11 | 27965.54 | 12-JAN-15:20 | 27965.54 | 0.00 |
February | 0.00 | 0.00 | 0.237519E+11 | 0.204808E+11 | 44203.41 | 22-FEB-15:30 | 44203.41 | 0.00 |
March | 0.00 | 0.00 | 0.482772E+11 | 0.446103E+11 | 66005.50 | 28-MAR-16:00 | 66005.50 | 0.00 |
April | 0.00 | 0.00 | 0.714256E+11 | 0.676348E+11 | 104322.09 | 27-APR-04:02 | 78021.84 | 0.00 |
May | 0.00 | 0.00 | 0.102939E+12 | 0.877288E+11 | 123433.61 | 24-MAY-05:03 | 72035.99 | 0.00 |
June | 0.00 | 0.00 | 0.113638E+12 | 0.863684E+11 | 126469.03 | 26-JUN-04:02 | 77512.27 | 0.00 |
July | 0.00 | 0.00 | 0.119723E+12 | 0.762031E+11 | 128167.74 | 20-JUL-04:02 | 71764.53 | 0.00 |
August | 0.00 | 0.00 | 0.117474E+12 | 0.720575E+11 | 126699.74 | 19-AUG-05:03 | 72271.91 | 0.00 |
September | 0.00 | 0.00 | 0.935447E+11 | 0.618495E+11 | 126552.43 | 11-SEP-04:02 | 73378.15 | 0.00 |
October | 0.00 | 0.00 | 0.632654E+11 | 0.541002E+11 | 86554.13 | 04-OCT-05:03 | 59132.28 | 0.00 |
November | 0.00 | 0.00 | 0.375308E+11 | 0.338978E+11 | 54198.85 | 06-NOV-14:00 | 49279.88 | 0.00 |
December | 0.00 | 0.00 | 0.183167E+11 | 0.154441E+11 | 33627.77 | 01-DEC-15:10 | 33627.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.824427E+12 | 0.632279E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.145409E+11 | 0.119031E+11 | 27965.54 | 27965.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119723E+12 | 0.877288E+11 | 128167.74 | 78021.84 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152365E+11 | 0.122237E+11 | 29664.36 | 12-JAN-15:30 | 29664.36 | 0.00 |
February | 0.00 | 0.00 | 0.245967E+11 | 0.208468E+11 | 50924.27 | 22-FEB-15:00 | 50924.27 | 0.00 |
March | 0.00 | 0.00 | 0.518000E+11 | 0.472314E+11 | 79206.77 | 28-MAR-16:00 | 79206.77 | 0.00 |
April | 0.00 | 0.00 | 0.794057E+11 | 0.751171E+11 | 117144.46 | 16-APR-16:42 | 103406.52 | 0.00 |
May | 0.00 | 0.00 | 0.114243E+12 | 0.985535E+11 | 141152.02 | 17-MAY-04:02 | 94593.73 | 0.00 |
June | 0.00 | 0.00 | 0.125484E+12 | 0.976808E+11 | 145582.25 | 27-JUN-04:02 | 89905.44 | 0.00 |
July | 0.00 | 0.00 | 0.129191E+12 | 0.846503E+11 | 148080.89 | 20-JUL-04:02 | 84213.38 | 0.00 |
August | 0.00 | 0.00 | 0.124525E+12 | 0.786269E+11 | 145959.55 | 10-AUG-04:02 | 90351.35 | 0.00 |
September | 0.00 | 0.00 | 0.975069E+11 | 0.658051E+11 | 143304.36 | 05-SEP-04:02 | 95151.46 | 0.00 |
October | 0.00 | 0.00 | 0.661618E+11 | 0.565918E+11 | 93541.55 | 09-OCT-14:21 | 93541.55 | 0.00 |
November | 0.00 | 0.00 | 0.381615E+11 | 0.338991E+11 | 59712.32 | 09-NOV-13:30 | 55718.00 | 0.00 |
December | 0.00 | 0.00 | 0.183083E+11 | 0.149478E+11 | 36183.57 | 01-DEC-14:50 | 36183.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.884620E+12 | 0.686174E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.152365E+11 | 0.122237E+11 | 29664.36 | 29664.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129191E+12 | 0.985535E+11 | 148080.89 | 103406.52 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1369.18 | 4991.52 | 17-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1349.30 | 4961.58 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1347.92 | 4749.24 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1127.65 | 4301.52 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1038.30 | 3854.11 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 958.59 | 3415.15 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 834.39 | 3149.59 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 955.10 | 3361.97 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 980.18 | 3750.13 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1105.43 | 4259.51 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1253.37 | 4684.47 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1293.77 | 4939.77 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1133.26 | ||||
Minimum of Months | 0.00 | 0.00 | 834.39 | 3149.59 | ||
Maximum of Months | 0.00 | 0.00 | 1369.18 | 4991.52 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.190065E+10 | 0.30 | 3208.06 | 27-JAN-07:03 | 0.83 |
February | 0.237601E+10 | 0.34 | 5450.40 | 21-FEB-16:20 | 1.13 |
March | 0.398359E+10 | 0.43 | 6972.54 | 13-MAR-10:30 | 1.31 |
April | 0.527034E+10 | 0.52 | 9064.10 | 28-APR-04:02 | 1.55 |
May | 0.679303E+10 | 0.61 | 11630.20 | 02-MAY-04:02 | 1.81 |
June | 0.706274E+10 | 0.65 | 11630.20 | 05-JUN-06:03 | 1.81 |
July | 0.673024E+10 | 0.61 | 11630.20 | 03-JUL-06:03 | 1.81 |
August | 0.705508E+10 | 0.62 | 11630.20 | 01-AUG-04:02 | 1.81 |
September | 0.600401E+10 | 0.56 | 11630.20 | 01-SEP-04:02 | 1.81 |
October | 0.495325E+10 | 0.49 | 9904.55 | 02-OCT-05:12 | 1.64 |
November | 0.349904E+10 | 0.40 | 6393.32 | 06-NOV-16:50 | 1.24 |
December | 0.230014E+10 | 0.32 | 4533.24 | 01-DEC-15:30 | 1.01 |
Annual Sum or Average | 0.579281E+11 | 0.49 | |||
Minimum of Months | 0.190065E+10 | 0.30 | 3208.06 | 0.83 | |
Maximum of Months | 0.706274E+10 | 0.65 | 11630.20 | 1.81 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145514E+10 | 0.28 | 2340.29 | 02-JAN-07:01 | 0.73 |
February | 0.180763E+10 | 0.32 | 4264.39 | 22-FEB-15:40 | 1.02 |
March | 0.346774E+10 | 0.42 | 6912.03 | 13-MAR-16:00 | 1.37 |
April | 0.519153E+10 | 0.53 | 10899.69 | 17-APR-04:02 | 1.82 |
May | 0.665752E+10 | 0.63 | 10899.69 | 02-MAY-04:02 | 1.82 |
June | 0.665239E+10 | 0.64 | 10899.69 | 06-JUN-06:03 | 1.82 |
July | 0.588142E+10 | 0.58 | 10899.69 | 01-JUL-04:02 | 1.82 |
August | 0.582332E+10 | 0.57 | 10899.69 | 01-AUG-04:02 | 1.82 |
September | 0.471618E+10 | 0.50 | 10899.69 | 05-SEP-04:02 | 1.82 |
October | 0.380469E+10 | 0.43 | 7272.63 | 02-OCT-09:20 | 1.41 |
November | 0.247989E+10 | 0.36 | 4915.86 | 13-NOV-16:00 | 1.11 |
December | 0.160212E+10 | 0.29 | 3027.98 | 01-DEC-15:20 | 0.84 |
Annual Sum or Average | 0.495396E+11 | 0.46 | |||
Minimum of Months | 0.145514E+10 | 0.28 | 2340.29 | 0.73 | |
Maximum of Months | 0.665752E+10 | 0.64 | 10899.69 | 1.82 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146174E+10 | 0.28 | 2494.86 | 02-JAN-06:11 | 0.68 |
February | 0.168923E+10 | 0.30 | 3857.54 | 22-FEB-15:00 | 0.86 |
March | 0.324203E+10 | 0.38 | 7238.12 | 13-MAR-15:50 | 1.25 |
April | 0.517440E+10 | 0.49 | 10284.20 | 17-APR-04:02 | 1.56 |
May | 0.670456E+10 | 0.58 | 12963.12 | 06-MAY-04:02 | 1.81 |
June | 0.670176E+10 | 0.59 | 13005.87 | 26-JUN-04:02 | 1.81 |
July | 0.563873E+10 | 0.53 | 13005.87 | 12-JUL-04:02 | 1.81 |
August | 0.542967E+10 | 0.50 | 13005.87 | 10-AUG-04:02 | 1.81 |
September | 0.439804E+10 | 0.44 | 12067.05 | 05-SEP-04:02 | 1.73 |
October | 0.356113E+10 | 0.39 | 7075.80 | 03-OCT-16:00 | 1.23 |
November | 0.228494E+10 | 0.33 | 4644.25 | 09-NOV-15:30 | 0.96 |
December | 0.152658E+10 | 0.28 | 2444.35 | 01-DEC-15:00 | 0.68 |
Annual Sum or Average | 0.478128E+11 | 0.42 | |||
Minimum of Months | 0.146174E+10 | 0.28 | 2444.35 | 0.68 | |
Maximum of Months | 0.670456E+10 | 0.59 | 13005.87 | 1.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.50 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.61 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.73 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.87 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 58.12 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.32 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 58.41 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 58.42 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.40 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.79 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.95 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.75 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.61 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.79 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.51 | 58.51 | 1369.18 | 4991.52 | 17-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.11 | 58.11 | 1349.30 | 4961.58 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.19 | 58.19 | 1347.92 | 4749.24 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.35 | 58.35 | 1127.65 | 4301.52 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.84 | 58.84 | 1038.30 | 3854.11 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.71 | 58.71 | 958.59 | 3415.15 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.80 | 58.80 | 834.39 | 3149.59 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.82 | 58.82 | 955.10 | 3361.97 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.73 | 58.73 | 980.18 | 3750.13 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.99 | 57.99 | 1105.43 | 4259.51 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.38 | 58.38 | 1253.37 | 4684.47 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.22 | 58.22 | 1293.77 | 4939.77 | 29-DEC-12:15 |
Annual Sum or Average | 0.00 | 1133.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 834.39 | 3149.59 | ||
Maximum of Months | 0.00 | 0.00 | 58.84 | 58.84 | 1369.18 | 4991.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.756852E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.965843E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.170573E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.259928E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.387075E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.423734E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.416589E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.413995E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.335268E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.239285E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.147248E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.882737E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.305424E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.756852E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.423734E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.578669E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.744069E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149671E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.241986E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.355646E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.376907E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.356317E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.340006E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.270079E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.191587E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.112515E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.616361E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.258862E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.578669E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.376907E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.813258E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.804820E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157040E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.264892E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.389946E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.412101E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.378580E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.353959E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.277822E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.197990E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113785E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.714380E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.277936E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.714380E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.412101E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.190065E+10 | 0.198780E+11 | 0.891269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237601E+10 | 0.296233E+11 | 0.442435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398359E+10 | 0.549596E+11 | 96557609.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.527034E+10 | 0.779604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679303E+10 | 0.113244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.706274E+10 | 0.128505E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673024E+10 | 0.139627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.705508E+10 | 0.142204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.600401E+10 | 0.114951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.495325E+10 | 0.789890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349904E+10 | 0.484901E+11 | 0.124022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230014E+10 | 0.255024E+11 | 0.517986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579281E+11 | 0.973933E+12 | 0.207227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190065E+10 | 0.198780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.706274E+10 | 0.142204E+12 | 0.891269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145514E+10 | 0.145409E+11 | 0.762552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180763E+10 | 0.237519E+11 | 54196196.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346774E+10 | 0.482772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519153E+10 | 0.714256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.665752E+10 | 0.102939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665239E+10 | 0.113638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.588142E+10 | 0.119723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582332E+10 | 0.117474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471618E+10 | 0.935447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380469E+10 | 0.632654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247989E+10 | 0.375308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160212E+10 | 0.183167E+11 | 0.131889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495396E+11 | 0.824427E+12 | 0.948638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145514E+10 | 0.145409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665752E+10 | 0.119723E+12 | 0.762552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146174E+10 | 0.152365E+11 | 0.291805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168923E+10 | 0.245967E+11 | 0.536009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324203E+10 | 0.518000E+11 | 1069240.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517440E+10 | 0.794057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.670456E+10 | 0.114243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.670176E+10 | 0.125484E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.563873E+10 | 0.129191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.542967E+10 | 0.124525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.439804E+10 | 0.975069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356113E+10 | 0.661618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228494E+10 | 0.381615E+11 | 54493909.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152658E+10 | 0.183083E+11 | 0.115735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478128E+11 | 0.884620E+12 | 0.466697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146174E+10 | 0.152365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.670456E+10 | 0.129191E+12 | 0.291805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.190065E+10 | 0.00 | 0.00 | 0.00 | 0.477661E+10 | 0.891269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237601E+10 | 0.00 | 0.00 | 0.00 | 0.683998E+10 | 0.442435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398359E+10 | 0.00 | 0.00 | 0.00 | 0.129771E+11 | 96557609.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.527034E+10 | 0.00 | 0.00 | 0.00 | 0.207224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.679303E+10 | 0.00 | 0.00 | 0.00 | 0.319145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.706274E+10 | 0.00 | 0.00 | 0.00 | 0.353107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.673024E+10 | 0.00 | 0.00 | 0.00 | 0.349287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.705508E+10 | 0.00 | 0.00 | 0.00 | 0.343444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.600401E+10 | 0.00 | 0.00 | 0.00 | 0.275228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.495325E+10 | 0.00 | 0.00 | 0.00 | 0.189752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349904E+10 | 0.00 | 0.00 | 0.00 | 0.111017E+11 | 0.124022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230014E+10 | 0.00 | 0.00 | 0.00 | 0.600924E+10 | 0.517986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579281E+11 | 0.00 | 0.00 | 0.00 | 0.245423E+12 | 0.207227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190065E+10 | 0.00 | 0.00 | 0.00 | 0.477661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.706274E+10 | 0.00 | 0.00 | 0.00 | 0.353107E+11 | 0.891269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145514E+10 | 0.00 | 0.00 | 0.00 | 0.356900E+10 | 0.762552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180763E+10 | 0.00 | 0.00 | 0.00 | 0.557886E+10 | 54196196.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346774E+10 | 0.00 | 0.00 | 0.00 | 0.114993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519153E+10 | 0.00 | 0.00 | 0.00 | 0.190071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.665752E+10 | 0.00 | 0.00 | 0.00 | 0.289071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.665239E+10 | 0.00 | 0.00 | 0.00 | 0.310383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.588142E+10 | 0.00 | 0.00 | 0.00 | 0.297503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582332E+10 | 0.00 | 0.00 | 0.00 | 0.281773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.471618E+10 | 0.00 | 0.00 | 0.00 | 0.222917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380469E+10 | 0.00 | 0.00 | 0.00 | 0.153540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247989E+10 | 0.00 | 0.00 | 0.00 | 0.877162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160212E+10 | 0.00 | 0.00 | 0.00 | 0.442960E+10 | 0.131889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.495396E+11 | 0.00 | 0.00 | 0.00 | 0.208374E+12 | 0.948638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145514E+10 | 0.00 | 0.00 | 0.00 | 0.356900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.665752E+10 | 0.00 | 0.00 | 0.00 | 0.310383E+11 | 0.762552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146174E+10 | 0.00 | 0.00 | 0.00 | 0.375279E+10 | 0.291805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168923E+10 | 0.00 | 0.00 | 0.00 | 0.582295E+10 | 0.536009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324203E+10 | 0.00 | 0.00 | 0.00 | 0.124609E+11 | 1069240.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.517440E+10 | 0.00 | 0.00 | 0.00 | 0.213148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.670456E+10 | 0.00 | 0.00 | 0.00 | 0.322900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.670176E+10 | 0.00 | 0.00 | 0.00 | 0.345083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.563873E+10 | 0.00 | 0.00 | 0.00 | 0.322193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.542967E+10 | 0.00 | 0.00 | 0.00 | 0.299663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.439804E+10 | 0.00 | 0.00 | 0.00 | 0.233842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.356113E+10 | 0.00 | 0.00 | 0.00 | 0.162378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228494E+10 | 0.00 | 0.00 | 0.00 | 0.903908E+10 | 54493909.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152658E+10 | 0.00 | 0.00 | 0.00 | 0.445988E+10 | 0.115735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478128E+11 | 0.00 | 0.00 | 0.00 | 0.225456E+12 | 0.466697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146174E+10 | 0.00 | 0.00 | 0.00 | 0.375279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.670456E+10 | 0.00 | 0.00 | 0.00 | 0.345083E+11 | 0.291805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950809E+09 | 217293.48 | 0.00 | 33476488.00 | 628066.05 | 0.00 | 0.709978E+10 | 0.00 | 0.38 |
February | 0.303353E+09 | 34623796.77 | 0.00 | 34462509.96 | 11930407.03 | 0.00 | 0.456870E+10 | 0.00 | 0.41 |
March | 85443750.71 | 0.877379E+09 | 0.00 | 31877352.22 | 0.210647E+09 | 0.00 | 0.232084E+10 | 0.00 | 0.41 |
April | 25168760.28 | 0.361060E+10 | 0.00 | 6818518.87 | 0.998263E+09 | 0.00 | 0.129843E+09 | 0.00 | 0.35 |
May | 725942.34 | 0.104333E+11 | 0.00 | 135242.38 | 0.252272E+10 | 0.00 | 2387258.56 | 0.00 | 0.36 |
June | 0.00 | 0.148304E+11 | 0.00 | 0.00 | 0.397545E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.180991E+11 | 0.00 | 0.00 | 0.718738E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.201865E+11 | 0.00 | 0.00 | 0.482706E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.144721E+11 | 0.00 | 0.00 | 0.345499E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 37662576.24 | 0.370426E+10 | 0.00 | 10020826.34 | 0.857657E+09 | 0.00 | 0.373016E+09 | 0.00 | 0.35 |
November | 0.162305E+09 | 0.146326E+09 | 0.00 | 39591141.24 | 0.109803E+09 | 0.00 | 0.303587E+10 | 0.00 | 0.38 |
December | 0.549153E+09 | 4323.39 | 0.00 | 37939222.27 | 8010189.66 | 0.00 | 0.719165E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.211462E+10 | 0.863948E+11 | 0.00 | 0.194321E+09 | 0.241645E+11 | 0.00 | 0.247221E+11 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 4323.39 | 0.00 | 0.00 | 628066.05 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.950809E+09 | 0.201865E+11 | 0.00 | 39591141.24 | 0.718738E+10 | 0.00 | 0.719165E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.393587E+10 | 0.00 | 0.00 | 6544963.39 | 6120491.79 | 4722753.96 | 0.193020E+10 | 0.00 | 0.29 |
February | 0.139994E+10 | 9828214.87 | 0.00 | 13800770.01 | 48788507.04 | 0.00 | 0.196992E+10 | 0.00 | 0.30 |
March | 0.255876E+09 | 0.638505E+09 | 0.00 | 18193089.86 | 0.259883E+09 | 0.00 | 0.141635E+10 | 0.00 | 0.32 |
April | 33017704.25 | 0.284816E+10 | 0.00 | 5061370.66 | 0.104348E+10 | 0.00 | 0.101149E+09 | 0.00 | 0.31 |
May | 1075896.04 | 0.899924E+10 | 0.00 | 64955.22 | 0.263140E+10 | 0.00 | 1126047.89 | 0.00 | 0.34 |
June | 0.00 | 0.131648E+11 | 0.00 | 0.00 | 0.405586E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.165674E+11 | 0.00 | 0.00 | 0.660164E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.187336E+11 | 0.00 | 0.00 | 0.417819E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.129665E+11 | 0.00 | 0.00 | 0.304212E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 67090867.51 | 0.330359E+10 | 0.00 | 4853212.85 | 0.694909E+09 | 0.00 | 0.150985E+09 | 0.00 | 0.30 |
November | 0.544699E+09 | 0.123594E+09 | 0.00 | 19330097.08 | 0.149000E+09 | 0.00 | 0.157582E+10 | 0.00 | 0.31 |
December | 0.280159E+10 | 0.00 | 0.00 | 10990018.85 | 27436915.02 | 0.00 | 0.244351E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.903915E+10 | 0.773553E+11 | 0.00 | 78838477.92 | 0.227388E+11 | 4722753.96 | 0.958907E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6120491.79 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.393587E+10 | 0.187336E+11 | 0.00 | 19330097.08 | 0.660164E+10 | 4722753.96 | 0.244351E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407897E+10 | 0.00 | 0.00 | 2736570.52 | 6148923.45 | 0.125131E+09 | 0.839295E+09 | 0.00 | 0.28 |
February | 0.161429E+10 | 9064670.70 | 0.00 | 8724999.63 | 66728794.41 | 0.00 | 0.114016E+10 | 0.00 | 0.29 |
March | 0.273036E+09 | 0.640216E+09 | 0.00 | 14162796.96 | 0.303937E+09 | 0.00 | 0.101347E+10 | 0.00 | 0.31 |
April | 19069465.41 | 0.268241E+10 | 0.00 | 5918729.07 | 0.104360E+10 | 0.00 | 0.108153E+09 | 0.00 | 0.31 |
May | 547892.35 | 0.867002E+10 | 0.00 | 2751.21 | 0.264315E+10 | 0.00 | 233612.52 | 0.00 | 0.34 |
June | 0.00 | 0.128550E+11 | 0.00 | 0.00 | 0.413971E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.161997E+11 | 0.00 | 0.00 | 0.690544E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.182700E+11 | 0.00 | 0.00 | 0.436926E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.125074E+11 | 0.00 | 0.00 | 0.317817E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 45617279.96 | 0.320298E+10 | 0.00 | 2136176.25 | 0.742516E+09 | 0.00 | 35794176.25 | 0.00 | 0.30 |
November | 0.679594E+09 | 0.137745E+09 | 0.00 | 13033212.52 | 0.167828E+09 | 0.00 | 0.857958E+09 | 0.00 | 0.29 |
December | 0.317520E+10 | 0.00 | 0.00 | 4781005.06 | 19294437.68 | 2581576.28 | 0.108409E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.988633E+10 | 0.751746E+11 | 0.00 | 51496241.24 | 0.235858E+11 | 0.127712E+09 | 0.507916E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6148923.45 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.407897E+10 | 0.182700E+11 | 0.00 | 14162796.96 | 0.690544E+10 | 0.125131E+09 | 0.114016E+10 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.834828E+09 | 0.00 | 0.00 | 166125.50 | 1438003.13 | 0.291159E+09 | 56154528.01 | 0.00 | 0.31 |
February | 0.409947E+09 | 5552812.97 | 0.00 | 1447981.45 | 12172442.63 | 56497439.37 | 0.167600E+09 | 0.00 | 0.32 |
March | 93527371.52 | 0.179366E+09 | 0.00 | 3283767.04 | 68904249.14 | 0.00 | 0.219393E+09 | 0.00 | 0.36 |
April | 4791116.63 | 0.963530E+09 | 0.00 | 1855833.63 | 0.186725E+09 | 0.00 | 32876737.53 | 0.00 | 0.44 |
May | 95354.64 | 0.349120E+10 | 0.00 | 5259.32 | 0.354288E+09 | 0.00 | 82794.19 | 0.00 | 0.54 |
June | 0.00 | 0.527462E+10 | 0.00 | 0.00 | 0.591189E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.679503E+10 | 0.00 | 0.00 | 0.918152E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.672670E+10 | 0.00 | 0.00 | 0.649164E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.408516E+10 | 0.00 | 0.00 | 0.597997E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 11379437.88 | 0.840291E+09 | 0.00 | 531299.81 | 0.211944E+09 | 0.00 | 9223107.84 | 0.00 | 0.36 |
November | 0.209103E+09 | 24050763.51 | 0.00 | 2530554.97 | 47034914.18 | 3722364.70 | 0.136323E+09 | 0.00 | 0.31 |
December | 0.766400E+09 | 0.00 | 0.00 | 361678.44 | 4512247.05 | 0.123595E+09 | 91564931.63 | 0.00 | 0.30 |
Annual Sum or Average | 0.233007E+10 | 0.283855E+11 | 0.00 | 10182500.17 | 0.364352E+10 | 0.474974E+09 | 0.713218E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1438003.13 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.834828E+09 | 0.679503E+10 | 0.00 | 3283767.04 | 0.918152E+09 | 0.291159E+09 | 0.219393E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.608317E+09 | 0.00 | 0.00 | 414481.06 | 1100658.65 | 0.145796E+09 | 0.151065E+09 | 0.00 | 0.37 |
February | 0.258055E+09 | 5125843.25 | 0.00 | 2035051.72 | 8441203.72 | 26047969.55 | 0.248170E+09 | 0.00 | 0.42 |
March | 52092757.64 | 0.177965E+09 | 0.00 | 3298050.17 | 41308815.33 | 0.00 | 0.227176E+09 | 0.00 | 0.53 |
April | 2063157.11 | 0.939981E+09 | 0.00 | 1615413.52 | 0.113766E+09 | 0.00 | 31394932.74 | 0.00 | 0.63 |
May | 72985.18 | 0.287863E+10 | 0.00 | 2449.62 | 0.259888E+09 | 0.00 | 64947.22 | 0.00 | 0.71 |
June | 0.00 | 0.397653E+10 | 0.00 | 0.00 | 0.454115E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.492962E+10 | 0.00 | 0.00 | 0.724191E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.484887E+10 | 0.00 | 0.00 | 0.487310E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.316480E+10 | 0.00 | 0.00 | 0.444645E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 7791986.73 | 0.767356E+09 | 0.00 | 467545.67 | 0.130476E+09 | 0.00 | 7977561.34 | 0.00 | 0.50 |
November | 0.128875E+09 | 35400384.51 | 0.00 | 2727927.10 | 28422734.63 | 1175919.17 | 0.163788E+09 | 0.00 | 0.43 |
December | 0.513830E+09 | 606801.17 | 0.00 | 748322.53 | 2846907.43 | 57914572.62 | 0.183779E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.157110E+10 | 0.217249E+11 | 0.00 | 11309241.39 | 0.269651E+10 | 0.230934E+09 | 0.101342E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1100658.65 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.608317E+09 | 0.492962E+10 | 0.00 | 3298050.17 | 0.724191E+09 | 0.145796E+09 | 0.248170E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558526E+09 | 1972523.25 | 0.00 | 5134390.52 | 154388.51 | 0.181717E+09 | 0.100482E+10 | 0.00 | 0.48 |
February | 0.305898E+09 | 14531373.01 | 0.00 | 6878861.15 | 8486189.04 | 32303797.44 | 0.672135E+09 | 0.00 | 0.52 |
March | 72766905.92 | 0.313308E+09 | 0.00 | 6531149.24 | 39562198.15 | 0.00 | 0.424804E+09 | 0.00 | 0.54 |
April | 4867039.77 | 0.123589E+10 | 0.00 | 2566582.97 | 0.149498E+09 | 0.00 | 45525497.57 | 0.00 | 0.53 |
May | 96865.69 | 0.361122E+10 | 0.00 | 5211.56 | 0.361044E+09 | 0.00 | 84237.31 | 0.00 | 0.56 |
June | 0.00 | 0.521329E+10 | 0.00 | 0.00 | 0.614921E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.681056E+10 | 0.00 | 0.00 | 0.958817E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.713098E+10 | 0.00 | 0.00 | 0.615996E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.502492E+10 | 0.00 | 0.00 | 0.499590E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 11191722.15 | 0.149077E+10 | 0.00 | 1142227.15 | 0.129819E+09 | 0.00 | 17933122.46 | 0.00 | 0.59 |
November | 0.139521E+09 | 0.124969E+09 | 0.00 | 9683507.83 | 14527781.30 | 503049.64 | 0.533986E+09 | 0.00 | 0.62 |
December | 0.508148E+09 | 6699095.81 | 0.00 | 6001866.75 | 1220487.51 | 61804557.58 | 0.969372E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.160101E+10 | 0.309791E+11 | 0.00 | 37943797.15 | 0.339364E+10 | 0.276328E+09 | 0.366866E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 1972523.25 | 0.00 | 0.00 | 154388.51 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.558526E+09 | 0.713098E+10 | 0.00 | 9683507.83 | 0.958817E+09 | 0.181717E+09 | 0.100482E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607506E+09 | 444418.72 | 0.00 | 889312.97 | 782462.38 | 0.234284E+09 | 0.205282E+09 | 0.00 | 0.43 |
February | 0.336772E+09 | 7187589.07 | 0.00 | 1880136.34 | 9192744.02 | 48486342.85 | 0.203586E+09 | 0.00 | 0.46 |
March | 78890716.81 | 0.174403E+09 | 0.00 | 3374929.86 | 49521165.26 | 113432.15 | 0.232960E+09 | 0.00 | 0.53 |
April | 4104926.28 | 0.891814E+09 | 0.00 | 1846467.48 | 0.136198E+09 | 0.00 | 29634731.54 | 0.00 | 0.62 |
May | 81355.04 | 0.284803E+10 | 0.00 | 2787.56 | 0.308881E+09 | 0.00 | 72338.28 | 0.00 | 0.71 |
June | 0.00 | 0.411645E+10 | 0.00 | 0.00 | 0.520838E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.489374E+10 | 0.00 | 0.00 | 0.839277E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.489466E+10 | 0.00 | 0.00 | 0.560170E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.323136E+10 | 0.00 | 0.00 | 0.491670E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 9792248.12 | 0.723412E+09 | 0.00 | 553608.80 | 0.170270E+09 | 0.00 | 10195732.50 | 0.00 | 0.50 |
November | 0.171756E+09 | 29551549.34 | 0.00 | 2812247.89 | 36429149.17 | 2861808.77 | 0.155972E+09 | 0.00 | 0.46 |
December | 0.589644E+09 | 889251.26 | 0.00 | 1036738.44 | 2960525.23 | 0.100041E+09 | 0.187088E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.179855E+10 | 0.218119E+11 | 0.00 | 12396229.33 | 0.312619E+10 | 0.385787E+09 | 0.102479E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 444418.72 | 0.00 | 0.00 | 782462.38 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.607506E+09 | 0.489466E+10 | 0.00 | 3374929.86 | 0.839277E+09 | 0.234284E+09 | 0.232960E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107081E+10 | 0.00 | 0.00 | 278716.75 | 168935.36 | 39851853.18 | 82977615.32 | 0.00 | 0.26 |
February | 0.490566E+09 | 3794372.77 | 0.00 | 1294002.66 | 3689736.14 | 351662.29 | 0.146146E+09 | 0.00 | 0.25 |
March | 0.134025E+09 | 0.143610E+09 | 0.00 | 2370421.57 | 49377842.31 | 0.00 | 0.173320E+09 | 0.00 | 0.28 |
April | 12874202.93 | 0.800802E+09 | 0.00 | 653496.69 | 0.213050E+09 | 0.00 | 10812820.55 | 0.00 | 0.33 |
May | 236413.26 | 0.288979E+10 | 0.00 | 16448.88 | 0.435852E+09 | 0.00 | 394771.66 | 0.00 | 0.43 |
June | 0.00 | 0.456659E+10 | 0.00 | 0.00 | 0.632953E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.612113E+10 | 0.00 | 0.00 | 0.949942E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.625712E+10 | 0.00 | 0.00 | 0.680286E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.388265E+10 | 0.00 | 0.00 | 0.630860E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 25746813.70 | 0.817545E+09 | 0.00 | 1028962.72 | 0.192662E+09 | 0.00 | 32687880.52 | 0.00 | 0.33 |
November | 0.218882E+09 | 25444725.18 | 0.00 | 3312913.78 | 23194059.62 | 0.00 | 0.200623E+09 | 0.00 | 0.26 |
December | 0.846750E+09 | 0.00 | 0.00 | 963150.40 | 1691913.97 | 270558.58 | 0.179852E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.279989E+10 | 0.255085E+11 | 0.00 | 9918113.46 | 0.381373E+10 | 40474074.05 | 0.826814E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 168935.36 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.107081E+10 | 0.625712E+10 | 0.00 | 3312913.78 | 0.949942E+09 | 39851853.18 | 0.200623E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.665099E+09 | 27852.50 | 0.00 | 971401.45 | 101651.32 | 13923042.82 | 0.254737E+09 | 0.00 | 0.32 |
February | 0.285351E+09 | 3146978.98 | 0.00 | 2283609.51 | 2590249.00 | 152906.08 | 0.272624E+09 | 0.00 | 0.35 |
March | 74141985.38 | 0.134644E+09 | 0.00 | 3200009.42 | 33676133.08 | 0.00 | 0.227705E+09 | 0.00 | 0.42 |
April | 7369518.15 | 0.818465E+09 | 0.00 | 904294.08 | 0.117872E+09 | 0.00 | 17640667.40 | 0.00 | 0.50 |
May | 181231.56 | 0.257508E+10 | 0.00 | 14233.10 | 0.247280E+09 | 0.00 | 302070.36 | 0.00 | 0.59 |
June | 0.00 | 0.357087E+10 | 0.00 | 0.00 | 0.439500E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.457209E+10 | 0.00 | 0.00 | 0.688161E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.456476E+10 | 0.00 | 0.00 | 0.492932E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.302854E+10 | 0.00 | 0.00 | 0.437361E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 17425580.73 | 0.718598E+09 | 0.00 | 1164797.72 | 0.114815E+09 | 0.00 | 36135497.34 | 0.00 | 0.45 |
November | 0.124613E+09 | 22739393.99 | 0.00 | 3993673.45 | 17623372.84 | 0.00 | 0.262371E+09 | 0.00 | 0.38 |
December | 0.515813E+09 | 566.58 | 0.00 | 1803447.47 | 1296434.34 | 0.00 | 0.323845E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.169000E+10 | 0.200090E+11 | 0.00 | 14335466.20 | 0.259321E+10 | 14075948.90 | 0.139536E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 566.58 | 0.00 | 0.00 | 101651.32 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.665099E+09 | 0.457209E+10 | 0.00 | 3993673.45 | 0.688161E+09 | 13923042.82 | 0.323845E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.740878E+09 | 138150.89 | 0.00 | 3437198.89 | 85853.99 | 0.292326E+09 | 0.632765E+09 | 0.00 | 0.38 |
February | 0.318457E+09 | 10210179.83 | 0.00 | 5769505.62 | 1743766.71 | 0.120964E+09 | 0.518288E+09 | 0.00 | 0.42 |
March | 93897708.24 | 0.338131E+09 | 0.00 | 5425831.93 | 20808125.41 | 19372525.13 | 0.343584E+09 | 0.00 | 0.47 |
April | 14174154.60 | 0.140127E+10 | 0.00 | 1112312.69 | 0.145598E+09 | 0.00 | 14449535.96 | 0.00 | 0.50 |
May | 148993.87 | 0.410254E+10 | 0.00 | 28868.24 | 0.387741E+09 | 0.00 | 658316.05 | 0.00 | 0.57 |
June | 0.00 | 0.598266E+10 | 0.00 | 0.00 | 0.611540E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.749816E+10 | 0.00 | 0.00 | 0.941180E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.806552E+10 | 0.00 | 0.00 | 0.623987E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.565198E+10 | 0.00 | 0.00 | 0.470578E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 29024836.80 | 0.166037E+10 | 0.00 | 1742817.89 | 78552994.12 | 0.00 | 42476954.63 | 0.00 | 0.57 |
November | 0.131194E+09 | 0.104155E+09 | 0.00 | 10815686.23 | 6289380.00 | 28628785.86 | 0.576530E+09 | 0.00 | 0.55 |
December | 0.525685E+09 | 1627179.46 | 0.00 | 5572780.78 | 591063.26 | 0.173604E+09 | 0.832455E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.185346E+10 | 0.348168E+11 | 0.00 | 33905002.26 | 0.328870E+10 | 0.634895E+09 | 0.296121E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 138150.89 | 0.00 | 0.00 | 85853.99 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.740878E+09 | 0.806552E+10 | 0.00 | 10815686.23 | 0.941180E+09 | 0.292326E+09 | 0.832455E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.783775E+09 | 29153.15 | 0.00 | 1007115.71 | 106398.23 | 20683983.45 | 0.194586E+09 | 0.00 | 0.35 |
February | 0.364384E+09 | 5092758.47 | 0.00 | 1750777.29 | 1998536.12 | 281812.14 | 0.183196E+09 | 0.00 | 0.36 |
March | 92358335.88 | 0.161376E+09 | 0.00 | 2612415.43 | 27892641.77 | 0.00 | 0.188469E+09 | 0.00 | 0.41 |
April | 9607664.86 | 0.872200E+09 | 0.00 | 557632.14 | 0.104074E+09 | 0.00 | 9077388.15 | 0.00 | 0.50 |
May | 147143.94 | 0.263136E+10 | 0.00 | 16792.45 | 0.239455E+09 | 0.00 | 364423.70 | 0.00 | 0.59 |
June | 0.00 | 0.381545E+10 | 0.00 | 0.00 | 0.409200E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.459745E+10 | 0.00 | 0.00 | 0.698914E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.464091E+10 | 0.00 | 0.00 | 0.491075E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.313645E+10 | 0.00 | 0.00 | 0.426234E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 19022023.41 | 0.751577E+09 | 0.00 | 836746.64 | 0.112743E+09 | 0.00 | 27004192.20 | 0.00 | 0.44 |
November | 0.148014E+09 | 30711134.42 | 0.00 | 3369629.59 | 16358348.46 | 0.00 | 0.210142E+09 | 0.00 | 0.38 |
December | 0.616771E+09 | 593.04 | 0.00 | 1525399.82 | 1356975.06 | 217092.42 | 0.259860E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.203408E+10 | 0.206426E+11 | 0.00 | 11676509.07 | 0.252941E+10 | 21182888.01 | 0.107270E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 593.04 | 0.00 | 0.00 | 106398.23 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.783775E+09 | 0.464091E+10 | 0.00 | 3369629.59 | 0.698914E+09 | 20683983.45 | 0.259860E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.989751E+09 | 0.00 | 0.00 | 365193.74 | 1290885.71 | 0.111854E+09 | 0.115497E+09 | 0.00 | 0.28 |
February | 0.471734E+09 | 6229756.82 | 0.00 | 1839372.78 | 6133218.45 | 1671072.55 | 0.204187E+09 | 0.00 | 0.29 |
March | 0.109028E+09 | 0.193425E+09 | 0.00 | 3475594.86 | 51674876.41 | 0.00 | 0.251904E+09 | 0.00 | 0.35 |
April | 11019584.62 | 0.105403E+10 | 0.00 | 1220989.93 | 0.176995E+09 | 0.00 | 19901933.94 | 0.00 | 0.43 |
May | 135219.22 | 0.369825E+10 | 0.00 | 27591.18 | 0.308663E+09 | 0.00 | 350932.47 | 0.00 | 0.54 |
June | 0.00 | 0.552189E+10 | 0.00 | 0.00 | 0.506139E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.695483E+10 | 0.00 | 0.00 | 0.770217E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.692199E+10 | 0.00 | 0.00 | 0.540612E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.426590E+10 | 0.00 | 0.00 | 0.510117E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 29875837.30 | 0.914781E+09 | 0.00 | 642104.32 | 0.157125E+09 | 0.00 | 12076577.03 | 0.00 | 0.36 |
November | 0.244720E+09 | 33112567.69 | 0.00 | 2810507.64 | 27568592.89 | 0.00 | 0.169902E+09 | 0.00 | 0.30 |
December | 0.887514E+09 | 0.00 | 0.00 | 815642.07 | 5786777.06 | 11745553.89 | 0.151090E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.274378E+10 | 0.295644E+11 | 0.00 | 11196996.52 | 0.306232E+10 | 0.125271E+09 | 0.924910E+09 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1290885.71 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.989751E+09 | 0.695483E+10 | 0.00 | 3475594.86 | 0.770217E+09 | 0.111854E+09 | 0.251904E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.743400E+09 | 0.00 | 0.00 | 704407.70 | 1064638.90 | 49463274.94 | 0.220304E+09 | 0.00 | 0.37 |
February | 0.315869E+09 | 4907720.71 | 0.00 | 2372193.03 | 5289321.69 | 1797865.65 | 0.303737E+09 | 0.00 | 0.42 |
March | 75032895.93 | 0.168915E+09 | 0.00 | 3622330.94 | 34891241.98 | 0.00 | 0.265074E+09 | 0.00 | 0.52 |
April | 7134236.97 | 0.990073E+09 | 0.00 | 1208787.56 | 0.112588E+09 | 0.00 | 23723039.20 | 0.00 | 0.63 |
May | 157004.15 | 0.302638E+10 | 0.00 | 14842.61 | 0.254084E+09 | 0.00 | 222301.08 | 0.00 | 0.71 |
June | 0.00 | 0.412192E+10 | 0.00 | 0.00 | 0.442499E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.500843E+10 | 0.00 | 0.00 | 0.682917E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.490718E+10 | 0.00 | 0.00 | 0.467299E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.321003E+10 | 0.00 | 0.00 | 0.446450E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 23247227.20 | 0.776206E+09 | 0.00 | 771424.91 | 0.106949E+09 | 0.00 | 14579356.66 | 0.00 | 0.49 |
November | 0.175429E+09 | 31819998.42 | 0.00 | 3006880.56 | 22149808.57 | 0.00 | 0.205150E+09 | 0.00 | 0.43 |
December | 0.620236E+09 | 862250.25 | 0.00 | 1222944.08 | 3922143.47 | 4026441.36 | 0.257471E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.196051E+10 | 0.222467E+11 | 0.00 | 12923811.38 | 0.258010E+10 | 55287581.94 | 0.129026E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1064638.90 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.743400E+09 | 0.500843E+10 | 0.00 | 3622330.94 | 0.682917E+09 | 49463274.94 | 0.303737E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.691965E+09 | 2137444.48 | 0.00 | 6139980.71 | 119202.15 | 43815840.36 | 0.119380E+10 | 0.00 | 0.50 |
February | 0.343390E+09 | 17781057.11 | 0.00 | 7056728.05 | 2666120.56 | 751122.65 | 0.739864E+09 | 0.00 | 0.52 |
March | 93741717.42 | 0.355329E+09 | 0.00 | 6550796.74 | 20552637.65 | 0.00 | 0.457600E+09 | 0.00 | 0.55 |
April | 10927109.59 | 0.140095E+10 | 0.00 | 1640843.53 | 0.126400E+09 | 0.00 | 26029937.38 | 0.00 | 0.53 |
May | 137297.35 | 0.385875E+10 | 0.00 | 27244.38 | 0.306365E+09 | 0.00 | 352927.64 | 0.00 | 0.56 |
June | 0.00 | 0.545460E+10 | 0.00 | 0.00 | 0.534897E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.696715E+10 | 0.00 | 0.00 | 0.821192E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.736504E+10 | 0.00 | 0.00 | 0.493314E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.531044E+10 | 0.00 | 0.00 | 0.416910E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 26993393.81 | 0.167141E+10 | 0.00 | 1271766.37 | 70464009.29 | 0.00 | 22319609.35 | 0.00 | 0.59 |
November | 0.168092E+09 | 0.138282E+09 | 0.00 | 9413884.11 | 7885559.49 | 0.00 | 0.586433E+09 | 0.00 | 0.62 |
December | 0.570968E+09 | 9383044.71 | 0.00 | 6941348.98 | 1524961.57 | 1521132.57 | 0.120608E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.190621E+10 | 0.325513E+11 | 0.00 | 39042592.87 | 0.280229E+10 | 46088095.58 | 0.423248E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 2137444.48 | 0.00 | 0.00 | 119202.15 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.691965E+09 | 0.736504E+10 | 0.00 | 9413884.11 | 0.821192E+09 | 43815840.36 | 0.120608E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.803103E+09 | 560603.71 | 0.00 | 1087506.92 | 570987.84 | 92029916.39 | 0.228389E+09 | 0.00 | 0.42 |
February | 0.411562E+09 | 9389294.23 | 0.00 | 2031517.18 | 3592803.12 | 4017367.32 | 0.217194E+09 | 0.00 | 0.44 |
March | 97916516.20 | 0.203168E+09 | 0.00 | 3292463.59 | 29277378.18 | 0.00 | 0.248006E+09 | 0.00 | 0.52 |
April | 10632164.33 | 0.104437E+10 | 0.00 | 1055107.38 | 0.107459E+09 | 0.00 | 14882831.38 | 0.00 | 0.63 |
May | 166877.77 | 0.313974E+10 | 0.00 | 16958.33 | 0.248821E+09 | 0.00 | 235491.19 | 0.00 | 0.72 |
June | 0.00 | 0.440788E+10 | 0.00 | 0.00 | 0.454575E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.508569E+10 | 0.00 | 0.00 | 0.707046E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.505849E+10 | 0.00 | 0.00 | 0.492674E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.337750E+10 | 0.00 | 0.00 | 0.442466E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 27071422.80 | 0.825169E+09 | 0.00 | 479718.61 | 0.107858E+09 | 0.00 | 9102450.96 | 0.00 | 0.49 |
November | 0.211009E+09 | 40431121.96 | 0.00 | 2799000.06 | 22035952.41 | 0.00 | 0.170202E+09 | 0.00 | 0.44 |
December | 0.737117E+09 | 1078772.69 | 0.00 | 1296416.26 | 4085657.01 | 13391884.29 | 0.223212E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.229858E+10 | 0.231935E+11 | 0.00 | 12058688.34 | 0.262046E+10 | 0.109439E+09 | 0.111123E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 560603.71 | 0.00 | 0.00 | 570987.84 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.803103E+09 | 0.508569E+10 | 0.00 | 3292463.59 | 0.707046E+09 | 92029916.39 | 0.248006E+09 | 0.00 | 0.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.166562E+12 | 0.352899E+10 | 0.00 | 0.655330E+11 | 0.617538E+11 |
February | 0.184641E+12 | 0.221201E+10 | 0.00 | 0.368661E+11 | 0.962137E+11 |
March | 0.243688E+12 | 0.328528E+09 | 0.00 | 0.783396E+10 | 0.191974E+12 |
April | 0.260487E+12 | -0.270181E+10 | 0.00 | -0.375686E+11 | 0.289836E+12 |
May | 0.270217E+12 | -0.759910E+10 | 0.00 | -0.102631E+12 | 0.423537E+12 |
June | 0.249187E+12 | -0.950933E+10 | 0.00 | -0.153649E+12 | 0.468483E+12 |
July | 0.207768E+12 | -0.121058E+11 | 0.00 | -0.207616E+12 | 0.485440E+12 |
August | 0.178556E+12 | -0.120694E+11 | 0.00 | -0.209601E+12 | 0.476691E+12 |
September | 0.195847E+12 | -0.790166E+10 | 0.00 | -0.156391E+12 | 0.379201E+12 |
October | 0.195803E+12 | -0.209138E+10 | 0.00 | -0.350612E+11 | 0.258983E+12 |
November | 0.174729E+12 | 0.963807E+09 | 0.00 | 0.229439E+11 | 0.153095E+12 |
December | 0.151700E+12 | 0.311653E+10 | 0.00 | 0.602132E+11 | 0.770260E+11 |
Annual Sum or Average | 0.247919E+13 | -0.438286E+11 | 0.00 | -0.709128E+12 | 0.336223E+13 |
Minimum of Months | 0.151700E+12 | -0.121058E+11 | 0.00 | -0.209601E+12 | 0.617538E+11 |
Maximum of Months | 0.270217E+12 | 0.352899E+10 | 0.00 | 0.655330E+11 | 0.485440E+12 |