Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2024-07-03 12:20:07


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1803.10 361.91 361.91
Net Site Energy 1803.10 361.91 361.91
Total Source Energy 4999.21 1003.42 1003.42
Net Source Energy 4999.21 1003.42 1003.42


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 341.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 204.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 301.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 50.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 103.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 52.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1461.67 341.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 341.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 204.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 301.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 50.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 103.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 52.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 341.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 204.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 301.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 50.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 103.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 52.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 72.73 68.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 293.38 68.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 72.73 68.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 293.38 68.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1461.667 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1461.667 100.00
     
Total On-Site and Utility Electric Sources 1461.667 100.00
Total Electricity End Uses 1461.667 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 314.17
Time Setpoint Not Met During Occupied Cooling 111.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2446.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 8.6994 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 8.6994 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 8.6994 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 8.6994 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 8.6994 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 8.6994 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 8.6994 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 8.6994 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 8.6994 18.58 8.0700  
Total 4982.19             8.6994 9.29 24.1370  
Conditioned Total 4982.19             8.6994 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 8.6994 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 19-JUN-10:00 02-JAN-07:19 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 265742.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 72133.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41666.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25851.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4374.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 171124.26 265742.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 265742.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 72133.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 53.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 25851.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4374.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 370.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 646.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 956.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 160.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 328.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 5.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 167.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4629.10 370.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 129.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 191.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 65.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 929.13 74.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 129.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 191.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 65.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 33.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 929.13 74.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 2.65 0.282315 0.291000 0.772511 0.752840 0.500000 0.001350 0.000133 0.772511 12.80 0.008000
CORE_MID VAV BOX COMPONENT 2.16 0.346597 0.351000 0.758976 0.924258 0.500000 0.001099 0.000199 0.758976 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 2.30 0.325238 0.342000 0.788079 0.867302 0.500000 0.001171 0.000324 1.10 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.718045 0.220030 0.231000 0.165868 0.586747 0.500000 0.001732 0.000154 0.526266 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.783728 0.127623 0.200000 0.156746 0.340328 0.500000 0.002985 0.000100 0.341456 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 0.971361 0.162650 0.200000 0.194272 0.433733 0.500000 0.002342 0.000153 0.521449 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.845579 0.118280 0.200000 0.169116 0.315414 0.500000 0.003221 0.000101 0.344391 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.576536 0.274036 0.283000 0.163160 0.730762 0.500000 0.001390 0.000118 0.401049 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.652549 0.153279 0.200000 0.130510 0.408743 0.500000 0.002486 0.000077 0.261865 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.792761 0.199293 0.205000 0.162516 0.531448 0.500000 0.001912 0.000116 0.396918 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.669441 0.149401 0.200000 0.133888 0.398403 0.500000 0.002550 0.000078 0.264552 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.627003 0.251979 0.255000 0.159886 0.671944 0.500000 0.001512 0.000122 0.415793 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.759505 0.131693 0.200000 0.151901 0.351183 0.500000 0.002893 0.000079 0.271048 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 0.879409 0.179657 0.200000 0.175882 0.479084 0.500000 0.002121 0.000121 0.411362 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.778764 0.128428 0.200000 0.155753 0.342475 0.500000 0.002967 0.000080 0.273700 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 15249.25 0.000133 339.82
CORE_MID VAV BOX REHEAT COIL 22701.31 0.000199 570.87
CORE_TOP VAV BOX REHEAT COIL 37087.48 0.000324 979.01
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17629.33 0.000154 464.86
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11437.87 0.000100 301.59
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17468.23 0.000153 460.62
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11536.03 0.000101 304.18
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13441.70 0.000118 354.52
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 8776.16 0.000077 231.46
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 13303.50 0.000116 350.88
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8866.07 0.000078 233.83
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 13934.52 0.000122 367.51
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 9083.09 0.000079 239.55
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 13786.31 0.000121 363.60
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 9171.78 0.000080 241.88
PACU_VAV_BOT HEATING COIL 32080.03 0.000281 521.08
PACU_VAV_MID HEATING COIL 32842.08 0.000287 528.51
PACU_VAV_TOP HEATING COIL 31977.94 0.000280 523.45
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.67 1.36 5.35 1.75 4.79 4.79 0.300000 0.364954 4.79
PACU_VAV_MID 2.60 1.40 5.21 2.01 4.48 4.48 0.300000 0.448669 4.48
PACU_VAV_TOP 2.81 1.47 5.62 2.84 5.17 5.17 0.300000 0.549141 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.79
PACU_VAV_MID_OA_CONTROLLER 4.48
PACU_VAV_TOP_OA_CONTROLLER 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.79 106396.08 0.737142 1.60 35461.81 0.737142
PACU_VAV_MID COOLING COIL 4.48 101930.72 0.729448 1.49 33973.51 0.729448
PACU_VAV_TOP COOLING COIL 5.17 112787.59 0.743874 1.72 37592.10 0.743874
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.79
PACU_VAV_MID FAN 4.48
PACU_VAV_TOP FAN 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000281
PACU_VAV_MID_HEATC_CONTROLLER 0.000287
PACU_VAV_TOP_HEATC_CONTROLLER 0.000280
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002803 0.336331
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.002803 844.07 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 320372.69 320372.69 0.002803
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 8.699 89.459 0.000 0.000 0.000 0.000 98.158 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.8668 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.8532 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.101 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.2365 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.2366 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9196
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9381
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6745
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.383
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.151
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.383
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 4.150
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
39 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
40 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
41 0 21.357363 0.71091016E-01 5.4032014  
42 7 -0.29350128E-12 0.14024199E-14 -0.85558835E-13 0.14795563E-15
43 6 0.27596652E-07 0.24107488E-09 0.63308017E-08 -0.12943591E-12
44 5 -0.18463709E-03 0.20772830E-05 -0.95040309E-04 0.62615177E-08
45 4 0.28572581 0.10171039E-02 0.97375121E-01 -0.32667087E-04
46 3 -7.1391205 0.31676816E-01 -2.3011695 0.28385744E-01
47 2 40.451560 0.11313072 15.110175 -0.32866754
48 1 -80.224209 0.51250674E-01 -29.002757 1.0717664
49 0 46.824341 0.10349526E-02 16.294583  
50 7 -0.29575366E-12 0.13916748E-14 -0.86470795E-13 0.14800413E-15
51 6 0.27759747E-07 0.23770535E-09 0.63667993E-08 -0.13030888E-12
52 5 -0.18546937E-03 0.20460315E-05 -0.95457978E-04 0.62966404E-08
53 4 0.28670590 0.10008406E-02 0.97727300E-01 -0.32804728E-04
54 3 -7.1585449 0.31143840E-01 -2.3069324 0.28480895E-01
55 2 40.515639 0.11114407 15.133849 -0.32938113
56 1 -80.273331 0.50317938E-01 -29.023991 1.0728132
57 0 46.824340 0.10154678E-02 16.294067  
58 7 -0.28281898E-12 0.14025464E-14 -0.82622143E-13 0.19904483E-15
59 6 0.24787521E-07 0.29557932E-09 0.57107416E-08 -0.11447606E-12
60 5 -0.17017937E-03 0.25981591E-05 -0.87765911E-04 0.56555961E-08
61 4 0.26851995 0.12946983E-02 0.91201294E-01 -0.30269387E-04
62 3 -6.7976835 0.40953066E-01 -2.1999024 0.26714449E-01
63 2 39.324706 0.14826279 14.693101 -0.31612152
64 1 -79.359856 0.67961194E-01 -28.628348 1.0533482
65 0 46.824347 0.13883650E-02 16.303898  
66 7 -0.18778705E-08 -0.48456698E-15 0.68415356E-14 -0.90766841E-16
67 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
68 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
69 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
70 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
71 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
72 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
73 0 0.22781756 0.11275910E-04 60.838472  
74 7 -0.17777358E-08 -0.41207670E-15 0.60771148E-14 -0.79247013E-16
75 6 0.66205355E-05 0.45347915E-08 0.31869553E-02 -0.26734852E-04
76 5 -0.47643654E-03 0.26865296E-05 -0.22355891 0.19546881E-02
77 4 0.10961386E-01 0.12229770E-03 4.8267865 -0.45238458E-01
78 3 -0.96263561E-01 0.97262436E-03 -38.005829 0.39848146
79 2 0.34182167 0.16181264E-02 116.45361 -1.4175335
80 1 -0.49337445 0.49308431E-03 -143.88945 2.0487464
81 0 0.24054552 0.11921404E-04 60.838472  
82 7 -0.18778705E-08 -0.48456747E-15 0.68415356E-14 -0.90766840E-16
83 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
84 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
85 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
86 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
87 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
88 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
89 0 0.22781756 0.11275910E-04 60.838472  
90 7 -0.17776120E-08 -0.41258204E-15 0.60425363E-14 -0.82023253E-16
91 6 0.66209765E-05 0.45351028E-08 0.31869540E-02 -0.26734841E-04
92 5 -0.47646911E-03 0.26867147E-05 -0.22355884 0.19546874E-02
93 4 0.10962140E-01 0.12230614E-03 4.8267853 -0.45238446E-01
94 3 -0.96270204E-01 0.97269154E-03 -38.005822 0.39848139
95 2 0.34184528 0.16182383E-02 116.45360 -1.4175333
96 1 -0.49340854 0.49311848E-03 -143.88944 2.0487463
97 0 0.24056214 0.11922214E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.38_SHGC_EAST_0.36 35 1 VerySmooth 2.159 2.159 1.000 0.361    
2 WINDOW_U_0.38_SHGC_SOUTH_0.36 36 1 VerySmooth 2.159 2.159 1.000 0.361    
3 WINDOW_U_0.38_SHGC_WEST_0.36 37 1 VerySmooth 2.159 2.159 1.000 0.361    
4 WINDOW_U_0.38_SHGC_NORTH_0.36 38 1 VerySmooth 2.159 2.159 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.1155E-002
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.1218E-002
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2228E-002
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2282E-002
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.8331E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.8773E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1452E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1682E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1567
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9961E-002
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1770
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.9524E-002
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1122
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6966E-002
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5786E-002
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7177E-002
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.1155E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.1221E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2228E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2285E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.8331E-003
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.8792E-003
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1449E-003
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1679E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.7615E-002
26 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9430E-002
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.2770E-002
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5953E-002
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6518E-002
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3525E-002
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3760E-002
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5338E-002
33 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1841E-004
34 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.2085E-004
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8026E-004
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8201E-004
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.6546E-004
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6606E-004
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8379E-004
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8458E-004
41 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3283E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3818E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6194E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.6620E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1611E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1916E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1449E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1679E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.0916E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3427E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1489E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7832E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9116E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2315E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5786E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7177E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3284E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3821E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6194E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.6618E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1608E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.1901E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1452E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1682E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.4706E-002
66 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8027E-002
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9164E-002
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4208E-002
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.4043E-002
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2366E-002
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3760E-002
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5339E-002
73 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.0112E-004
74 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.0805E-004
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5875E-004
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.6633E-004
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5097E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.5385E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.8380E-004
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.8460E-004
81 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1554
82 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 9.6358E-002
83 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1725
84 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1072
85 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1197
86 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.9538E-002
87 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.2201E-002
88 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.4367E-002
89 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.5407E-002
90 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.8172E-002
91 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.0836E-002
92 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4854E-002
93 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.4971E-002
94 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.2609E-002
95 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2761E-002
96 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4738E-002
97 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.6716E-002
98 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.0623E-002
99 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.6650E-002
100 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4025E-002
101 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.4285E-002
102 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.8005E-002
103 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2201E-002
104 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4367E-002
105 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2594E-002
106 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6845E-002
107 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.7350E-002
108 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3203E-002
109 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2572E-002
110 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.1506E-002
111 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.2761E-002
112 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4738E-002
113 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1554
114 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 9.6348E-002
115 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1725
116 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1072
117 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1197
118 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.9530E-002
119 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.2196E-002
120 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.4365E-002
121 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.5407E-002
122 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.8170E-002
123 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.0835E-002
124 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4851E-002
125 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.4967E-002
126 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.2606E-002
127 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2756E-002
128 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4735E-002
129 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.6717E-002
130 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.0622E-002
131 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.6651E-002
132 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4024E-002
133 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.4282E-002
134 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.8003E-002
135 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2196E-002
136 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4365E-002
137 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2593E-002
138 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6843E-002
139 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.7349E-002
140 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3201E-002
141 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2568E-002
142 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.1502E-002
143 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.2756E-002
144 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4736E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 36833.92583 36833.92583 2.65468 2.65468 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 7474.68352 7474.68352 0.31339 0.42469 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 30028.75052 30028.75052 2.16232 2.16232 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 15062.96053 15062.96053 0.63783 0.63783 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 31700.56933 31700.56933 2.30433 2.30433 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 32.10000 1.41196E-002 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 25971.82922 25971.82922 1.10449 1.10449 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 9877.78020 9877.78020 0.71805 0.71805 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 12337.64282 12337.64282 0.52627 0.52627 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 10781.40770 10781.40770 0.78373 0.78373 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 8004.54593 8004.54593 0.34146 0.34146 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 13362.56796 13362.56796 0.97136 0.97136 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 12225.01706 12225.01706 0.52145 0.52145 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 11632.29334 11632.29334 0.84558 0.84558 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 8073.17191 8073.17191 0.34439 0.34439 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7931.26626 7931.26626 0.57654 0.57654 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 9408.70458 9408.70458 0.40105 0.40105 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 8977.01761 8977.01761 0.65255 0.65255 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 28.65900 1.41134E-002 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 6142.78791 6142.78791 0.26186 0.26186 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 10905.85979 10905.85979 0.79276 0.79276 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 31.85333 1.41192E-002 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 9312.12736 9312.12736 0.39692 0.39692 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 9209.41157 9209.41157 0.66944 0.66944 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.06400 1.41178E-002 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 6205.62029 6205.62029 0.26455 0.26455 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 8625.40664 8625.40664 0.62700 0.62700 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 32.10000 1.41196E-002 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 9754.12967 9754.12967 0.41579 0.41579 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 10448.26348 10448.26348 0.75950 0.75950 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 28.23967 1.41127E-002 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 6357.98082 6357.98082 0.27105 0.27105 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 12097.70766 12097.70766 0.87941 0.87941 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 9650.53362 9650.53362 0.41136 0.41136 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 10713.21578 10713.21578 0.77876 0.77876 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 6419.97733 6419.97733 0.27370 0.27370 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 76621.92 4.79259 4.79259 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 33865.07 1.74908 1.74908 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:40:00
3 PACU_VAV_MID Cooling Sensible 72374.56 4.47933 4.47933 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 PACU_VAV_MID Heating Sensible 33660.71 2.00974 2.00974 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00
5 PACU_VAV_TOP Cooling Sensible 81689.97 5.16817 5.16817 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 33688.86 2.83806 2.83806 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.65468
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28231
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29100
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.77251
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75284
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34956E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.33407E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.77251
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15249.25167
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.33407E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 339.81994
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.16232
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34660
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35100
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75898
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.92426
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09926E-003
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98601E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75898
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22701.31231
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98601E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 570.87334
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.30433
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32524
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34200
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78808
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86730
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.17145E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.24457E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.10449
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 37087.48466
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.24457E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 979.01084
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.71805
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22003
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23100
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16587
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58675
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.73158E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54229E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52627
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17629.33218
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54229E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 464.86085
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.78373
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12762
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15675
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34033
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.98535E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00063E-004
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34146
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11437.86945
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00063E-004
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 301.59415
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.97136
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16265
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19427
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43373
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.34246E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.52820E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52145
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17468.23212
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.52820E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 460.61599
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84558
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11828
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16912
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31541
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.22117E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00922E-004
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34439
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11536.03187
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00922E-004
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 304.18062
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.57654
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27404
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28300
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16316
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73076
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.39033E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.17594E-004
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.40105
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13441.70347
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.17594E-004
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 354.52317
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.65255
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15328
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13051
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40874
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48567E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.67777E-005
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26186
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8776.15990
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.67777E-005
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 231.46305
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.79276
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19929
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20500
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16252
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53145
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.91176E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.16385E-004
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39692
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13303.50148
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.16385E-004
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 350.88128
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.66944
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14940
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13389
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39840
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55018E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.75642E-005
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26455
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8866.06692
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.75642E-005
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 233.83221
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.62700
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25198
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25500
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15989
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67194
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.51203E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21905E-004
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41579
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13934.51916
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21905E-004
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 367.50510
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.75950
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13169
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15190
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35118
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.89308E-003
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.94628E-005
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27105
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
180 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9083.08912
181 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.94628E-005
182 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.54770
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.87941
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17966
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17588
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47908
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12071E-003
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20609E-004
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41136
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
194 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13786.30796
195 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20609E-004
196 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 363.59968
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77876
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12843
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15575
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34247
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.96664E-003
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.02388E-005
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27370
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
208 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9171.78296
209 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.02388E-005
210 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 241.88477
211 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.67298
212 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.36258
213 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 5.34597
214 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.74908
215 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.79259
216 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.79259
217 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
218 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.36495
219 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.60350
220 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.40240
221 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.20701
222 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 2.00974
223 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.47933
224 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.47933
225 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
226 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.44867
227 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.81152
228 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.47408
229 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.62304
230 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.83806
231 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 5.16817
232 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 5.16817
233 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
234 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.54914
235 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.79259
236 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.47933
237 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 5.16817
238 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.79259
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.79259
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 106396.08142
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.73714
242 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.59737
243 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 35461.81394
244 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.73714
245 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 32080.02626
246 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.80650E-004
247 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 521.08017
248 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.79259
249 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.80650E-004
250 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.47933
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.47933
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 101930.72417
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.72945
254 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.49296
255 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 33973.51037
256 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.72945
257 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 32842.07598
258 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.87317E-004
259 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 528.50620
260 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.47933
261 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.87317E-004
262 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.16817
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.16817
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 112787.58863
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74387
266 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.72255
267 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 37592.10329
268 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74387
269 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 31977.94487
270 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.79757E-004
271 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 523.45137
272 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 5.16817
273 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.79757E-004
274 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.80276E-003
275 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.33633
276 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.80276E-003
277 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 844.06825
278 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
279 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 320372.69235
280 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 320372.69000
281 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.80276E-003
282 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
283 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
284 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
285 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
286 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 14451.43
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 21499.49
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 35143.87
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16702.05
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 10836.21
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 16549.45
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10929.20
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 12735.25
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 8314.87
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12604.34
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8400.04
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 13202.06
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 8605.60
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 13061.66
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8689.61
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 24029.77
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 24119.34
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 24340.11


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 105829.46 361105.11 12.28 3.16 3.52 3.70 3.87 10.77 12.00 12.64 13.21 5.5405 4.4007 2.9672 1.2326
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 101474.58 346245.65 12.33 3.17 3.53 3.72 3.88 10.81 12.05 12.70 13.25 5.1784 4.1226 2.7735 1.1587
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 112119.12 382566.33 12.24 3.15 3.50 3.69 3.86 10.74 11.96 12.59 13.18 5.9747 4.7604 3.2081 1.3207


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.237 0.224   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.237 0.224   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 6.3863824414E-002 3.6519664005E-002 Pass Pass 0.4857894698 0.4903960073 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1759109575 0.1305221562 Pass Pass 0.4917284915 0.4849861634 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.5145554683E-002 5.0263649885E-002 Pass Pass 0.4878361675 0.4778758109 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.1922162814E-002 4.8398155934E-002 Pass Pass 0.4881139767 0.4755791087 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 1.2031283144E-002 9.5346778547E-003 Pass Pass 0.4971964566 0.4898993380 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 9.6231216585E-002 0.1173222162 Pass Pass 33.8408077418 361.1053599043 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.5348207141 0.4956954337 Pass Pass 1.9132961682 9.8822805957 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.4615004992 0.5119433362 Pass Pass 3.6360282762 20.8737048300 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.4026447331 0.4409297353 Pass Pass 5.8047266461 61.1499758091 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.5254122161 0.5264184683 Pass Pass 6.8054200991 41.5646371320 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.3449903413 0.3226710161 Pass Pass 7.3802794194 33.8226771513 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2593993184 0.3112123563 Pass Pass 8.2398644967 51.4245219053 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1906982333 0.1989216610 Pass Pass 2.0276926636 13.7873111105 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.3211770585 0.3384285454 Pass Pass 3.0116810884 11.7323044177 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.3873362476 0.3647115006 Pass Pass 4.7723378466 30.4355021236 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.3294603095 0.3764050092 Pass Pass 4.1291094221 23.9325339302 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2956249070 0.3066301803 Pass Pass 1.1838304018 3.7030991327 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.3741779724 0.3917406960 Pass Pass 7.6039332208 60.0948920574 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3581.21 72.69 0.00 1583.15 1210.03 6447.10



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.228 0.237 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.228 0.237 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_NORTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_EAST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_SOUTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_WEST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.38_SHGC_EAST_0.36   41.85 0.00 0.00 41.85 41.85 2.159 0.361 0.397             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.38_SHGC_EAST_0.36   1.65 0.00 0.00 1.65 1.65 2.159 0.361 0.397             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.38_SHGC_WEST_0.36   41.85 0.00 0.00 41.85 41.85 2.159 0.361 0.397             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.38_SHGC_WEST_0.36   1.65 0.00 0.00 1.65 1.65 2.159 0.361 0.397             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_NORTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_EAST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_SOUTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_WEST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.159 0.361 0.397                      
North Total or Average             195.79 2.159 0.361 0.397                      
Non-North Total or Average             456.84 2.159 0.361 0.397                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.27 0.0000 Y 8.89
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.09 0.0000 Y 5.59
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.69 0.0000 Y 8.70
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.84 0.0000 Y 5.54
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.17 0.0000 Y 8.86
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.03 0.0000 Y 5.58
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.65 0.0000 Y 8.68
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.77 0.0000 Y 5.52
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.27 0.0000 Y 8.89
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.09 0.0000 Y 5.59
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.69 0.0000 Y 8.70
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.84 0.0000 Y 5.54
Interior Lighting Total       8.6994 4982.19 43341.88               301.88


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   42.43 42.43 4.49
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.64 63.04 4.82
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.64 46.90 41.51
Exterior Lighting Total 5686.19           50.82



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 320372.69 0.80        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   106396.08 78429.07 27967.01 0.74 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   101930.72 74353.20 27577.53 0.73 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   112787.59 83899.74 28887.85 0.74 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   105829.5 3.16 10.77 N/A N/A 12.28
PACU_VAV_MID COOLING COIL   101474.6 3.17 10.81 N/A N/A 12.33
PACU_VAV_TOP COOLING COIL   112119.1 3.15 10.74 N/A N/A 12.24
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 15249.25 14451.43 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 22701.31 21499.49 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 37087.48 35143.87 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 17629.33 16702.05 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11437.87 10836.21 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 17468.23 16549.45 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11536.03 10929.20 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13441.70 12735.25 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 8776.16 8314.87 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 13303.50 12604.34 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8866.07 8400.04 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13934.52 13202.06 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9083.09 8605.60 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 13786.31 13061.66 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9171.78 8689.61 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 32080.03 24029.77 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 32842.08 24119.34 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 31977.94 24340.11 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.79 10491.03 2189.01 1.00 1.14 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1389.42 4.48 10362.42 2313.39 1.00 1.13 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 5.17 11240.20 2174.89 1.00 1.14 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002803 844.07 301156.09 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 105829.46 3.16 10.77 12.28 5.5405 3.52 12.00 4.4007 3.70 12.64 2.9672 3.87 13.21 1.2326
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 101474.58 3.17 10.81 12.33 5.1784 3.53 12.05 4.1226 3.72 12.70 2.7735 3.88 13.25 1.1587
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 112119.12 3.15 10.74 12.24 5.9747 3.50 11.96 4.7604 3.69 12.59 3.2081 3.86 13.18 1.3207
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 36833.93 36833.93 37.45 2.655 2.655 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00883 26.62 0.01411 0.425 0.00
CORE_MID 30028.75 30028.75 30.53 2.162 2.162 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00891 26.62 0.01411 0.425 0.00
CORE_TOP 31700.57 31700.57 32.23 2.304 2.304 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00888 32.10 0.01412 0.425 0.00
PERIMETER_TOP_ZN_3 9877.78 9877.78 47.64 0.718 0.718 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00889 32.10 0.01412 0.090 0.00
PERIMETER_TOP_ZN_2 10781.41 10781.41 82.14 0.784 0.784 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00873 28.45 0.01411 0.057 0.00
PERIMETER_TOP_ZN_1 13362.57 13362.57 64.45 0.971 0.971 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00879 31.85 0.01412 0.090 0.00
PERIMETER_TOP_ZN_4 11632.29 11632.29 88.62 0.846 0.846 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00871 31.26 0.01412 0.057 0.00
PERIMETER_BOT_ZN_3 7931.27 7931.27 38.25 0.577 0.577 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00891 32.10 0.01412 0.090 0.00
PERIMETER_BOT_ZN_2 8977.02 8977.02 68.39 0.653 0.653 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00873 28.66 0.01411 0.057 0.00
PERIMETER_BOT_ZN_1 10905.86 10905.86 52.60 0.793 0.793 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00880 31.85 0.01412 0.090 0.00
PERIMETER_BOT_ZN_4 9209.41 9209.41 70.17 0.669 0.669 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00873 31.06 0.01412 0.057 0.00
PERIMETER_MID_ZN_3 8625.41 8625.41 41.60 0.627 0.627 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00892 32.10 0.01412 0.090 0.00
PERIMETER_MID_ZN_2 10448.26 10448.26 79.60 0.760 0.760 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00873 28.24 0.01411 0.057 0.00
PERIMETER_MID_ZN_1 12097.71 12097.71 58.35 0.879 0.879 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00880 31.79 0.01412 0.090 0.00
PERIMETER_MID_ZN_4 10713.22 10713.22 81.62 0.779 0.779 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00872 31.26 0.01412 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 7474.68 7474.68 7.60 0.313 0.425 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
CORE_MID 15062.96 15062.96 15.32 0.638 0.638 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
CORE_TOP 25971.83 25971.83 26.41 1.104 1.104 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 0.425 0.00
PERIMETER_TOP_ZN_3 12337.64 12337.64 59.50 0.526 0.526 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 -10.70 0.00150 0.090 0.00
PERIMETER_TOP_ZN_2 8004.55 8004.55 60.98 0.341 0.341 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 -10.70 0.00150 0.057 0.00
PERIMETER_TOP_ZN_1 12225.02 12225.02 58.96 0.521 0.521 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 -10.70 0.00150 0.090 0.00
PERIMETER_TOP_ZN_4 8073.17 8073.17 61.51 0.344 0.344 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 -10.70 0.00150 0.057 0.00
PERIMETER_BOT_ZN_3 9408.70 9408.70 45.38 0.401 0.401 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -10.70 0.00150 0.090 0.00
PERIMETER_BOT_ZN_2 6142.79 6142.79 46.80 0.262 0.262 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00767 -10.70 0.00150 0.057 0.00
PERIMETER_BOT_ZN_1 9312.13 9312.13 44.91 0.397 0.397 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 -10.70 0.00150 0.090 0.00
PERIMETER_BOT_ZN_4 6205.62 6205.62 47.28 0.265 0.265 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00768 -10.70 0.00150 0.057 0.00
PERIMETER_MID_ZN_3 9754.13 9754.13 47.04 0.416 0.416 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00758 -10.70 0.00150 0.090 0.00
PERIMETER_MID_ZN_2 6357.98 6357.98 48.44 0.271 0.271 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00757 -10.70 0.00150 0.057 0.00
PERIMETER_MID_ZN_1 9650.53 9650.53 46.54 0.411 0.411 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00757 -10.70 0.00150 0.090 0.00
PERIMETER_MID_ZN_4 6419.98 6419.98 48.91 0.274 0.274 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00758 -10.70 0.00150 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.79 4.79 1.75 1.75 4.7926 1.7491 4.7926 0.3650 0.3000
PACU_VAV_MID 4.48 4.48 2.01 2.01 4.4793 2.0097 4.4793 0.4487 0.3000
PACU_VAV_TOP 5.17 5.17 2.84 2.84 5.1682 2.8381 5.1682 0.5491 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 15249.252 15249.252 0.772511 0.00013341 339.820 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15249.25 15249.25 0.772511 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 7474.68 0.00 15301.60 15301.60
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 22701.312 22701.312 0.758976 0.00019860 570.873 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22701.31 22701.31 0.758976 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 15062.96 0.00 22771.86 22771.86
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 37087.485 37087.485 1.104494 0.00032446 979.011 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 37087.48 37087.48 1.104494 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 25971.83 0.00 37215.75 37215.75
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 17629.332 17629.332 0.526266 0.00015423 464.861 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17629.33 17629.33 0.526266 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00763734 49.3833 12337.64 0.00 17686.66 17686.66
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 11437.869 11437.869 0.341456 0.00010006 301.594 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11437.87 11437.87 0.341456 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00762954 49.3336 8004.55 0.00 11475.02 11475.02
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 17468.232 17468.232 0.521449 0.00015282 460.616 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17468.23 17468.23 0.521449 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00763350 49.3588 12225.02 0.00 17525.06 17525.06
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11536.032 11536.032 0.344391 0.00010092 304.181 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11536.03 11536.03 0.344391 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00763308 49.3562 8073.17 0.00 11573.48 11573.48
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 13441.703 13441.703 0.401049 0.00011759 354.523 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13441.70 13441.70 0.401049 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00766623 49.5668 9408.70 0.00 13486.02 13486.02
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 8776.160 8776.160 0.261865 0.00007678 231.463 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8776.16 8776.16 0.261865 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00767197 49.6034 6142.79 0.00 8805.04 8805.04
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 13303.501 13303.501 0.396918 0.00011638 350.881 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13303.50 13303.50 0.396918 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00765723 49.5094 9312.13 0.00 13347.39 13347.39
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8866.067 8866.067 0.264552 0.00007756 233.832 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8866.07 8866.07 0.264552 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00767972 49.6528 6205.62 0.00 8895.23 8895.23
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 13934.519 13934.519 0.415793 0.00012191 367.505 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13934.52 13934.52 0.415793 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00757527 48.9868 9754.13 0.00 13980.35 13980.35
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 9083.089 9083.089 0.271048 0.00007946 239.548 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9083.09 9083.09 0.271048 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00757357 48.9761 6357.98 0.00 9112.91 9112.91
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 13786.308 13786.308 0.411362 0.00012061 363.600 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13786.31 13786.31 0.411362 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00756778 48.9390 9650.53 0.00 13831.67 13831.67
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 9171.783 9171.783 0.273700 0.00008024 241.885 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9171.78 9171.78 0.273700 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00757991 49.0165 6419.98 0.00 9201.88 9201.88
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 106396.081 78429.069 4.792587 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 109038.61 84716.67 4.792587 26.02 18.44 0.01015835 11.02 11.02 0.00850000 32.10 0.01411964 23.13 24.9379 24.00 0.00884230 47.5542 65931.05 0.00 109708.64 79657.30
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 32080.026 32080.026 1.437776 0.00028065 521.080 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 32080.03 32080.03 1.437776 -5.65 -5.65 0.00251231 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 83.1263 19.60 0.00720214 50.8136 20341.80 0.00 29067.47 29067.47
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 101930.724 74353.199 4.479330 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 104815.70 80269.71 4.479330 26.16 18.59 0.01028347 10.92 10.92 0.00850000 32.10 0.01411964 23.13 26.6819 24.00 0.00888729 47.7930 61616.82 0.00 105104.26 75553.39
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 32842.076 32842.076 1.343799 0.00028732 528.506 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 32842.08 32842.08 1.343799 -7.41 -7.41 0.00216034 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 88.9396 19.64 0.00729015 51.2899 25616.80 0.00 29170.83 29170.83
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 112787.589 83899.736 5.168174 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 115268.56 90485.56 5.168174 25.87 18.32 0.01006617 11.03 11.03 0.00850000 32.10 0.01411964 23.13 23.1256 24.00 0.00884638 47.5762 71078.51 0.00 116299.14 85207.24
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 31977.945 31977.945 1.550452 0.00027976 523.451 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 31977.94 31977.94 1.550452 -4.25 -4.25 0.00286123 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 77.0853 17.60 0.00734636 58.7339 30594.88 0.00 29447.05 29447.05



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 15249.252 15249.252 0.772511 0.00013341 339.820 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 4.6659 4.759848 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15249.25 15249.25 1.0000 0.92979041 0.772511 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.13339350 60.00 32.22 27.78 0.000 15249.25 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.56 0.00800000 21.00 0.00800000 51.6928 7474.68 0.00 15301.60 15301.60 0.92979041 12.80 11.60 0.00800000 33059.8 28.94 17.68 0.00800000 49516.9
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 22701.312 22701.312 0.758976 0.00019860 570.873 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 6.9461 7.085907 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22701.31 22701.31 1.0000 0.91349977 0.758976 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.19858072 60.00 32.22 27.78 0.000 22701.31 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6928 15062.96 0.00 22771.86 22771.86 0.91349977 12.80 11.60 0.00800000 33059.8 37.25 20.35 0.00800000 57988.0
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 37087.485 37087.485 1.104494 0.00032446 979.011 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 11.3480 11.576356 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 37087.48 37087.48 1.0000 1.32936385 1.104494 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.32442440 60.00 32.22 27.78 0.000 37087.48 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 51.6928 25971.83 0.00 37215.75 37215.75 1.32936385 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61055.0
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 17629.332 17629.332 0.526266 0.00015423 464.861 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 5.3942 5.502757 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17629.33 17629.33 1.0000 0.63341075 0.526266 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.15421336 60.00 32.22 27.78 0.000 17629.33 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00763734 21.00 0.00763734 49.3833 12337.64 0.00 17686.66 17686.66 0.63341075 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 11437.869 11437.869 0.341456 0.00010006 301.594 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 3.4997 3.570176 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11437.87 11437.87 1.0000 0.41097474 0.341456 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.10005326 60.00 32.22 27.78 0.000 11437.87 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00762954 21.00 0.00762954 49.3336 8004.55 0.00 11475.02 11475.02 0.41097474 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60981.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 17468.232 17468.232 0.521449 0.00015282 460.616 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 5.3449 5.452472 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17468.23 17468.23 1.0000 0.62761322 0.521449 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.15280413 60.00 32.22 27.78 0.000 17468.23 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00763350 21.00 0.00763350 49.3588 12225.02 0.00 17525.06 17525.06 0.62761322 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.2
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11536.032 11536.032 0.344391 0.00010092 304.181 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 3.5298 3.600816 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11536.03 11536.03 1.0000 0.41450740 0.344391 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.10091194 60.00 32.22 27.78 0.000 11536.03 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00763308 21.00 0.00763308 49.3562 8073.17 0.00 11573.48 11573.48 0.41450740 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60980.9
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 13441.703 13441.703 0.401049 0.00011759 354.523 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 4.1129 4.195646 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13441.70 13441.70 1.0000 0.48270093 0.401049 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.11758189 60.00 32.22 27.78 0.000 13441.70 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00766623 21.00 0.00766623 49.5668 9408.70 0.00 13486.02 13486.02 0.48270093 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.5
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 8776.160 8776.160 0.261865 0.00007678 231.463 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 2.6853 2.739360 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8776.16 8776.16 1.0000 0.31517891 0.261865 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07676984 60.00 32.22 27.78 0.000 8776.16 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00767197 21.00 0.00767197 49.6034 6142.79 0.00 8805.04 8805.04 0.31517891 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 13303.501 13303.501 0.396918 0.00011638 350.881 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 4.0706 4.152508 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13303.50 13303.50 1.0000 0.47772857 0.396918 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.11637296 60.00 32.22 27.78 0.000 13303.50 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00765723 21.00 0.00765723 49.5094 9312.13 0.00 13347.39 13347.39 0.47772857 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60999.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8866.067 8866.067 0.264552 0.00007756 233.832 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 2.7128 2.767423 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8866.07 8866.07 1.0000 0.31841388 0.264552 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07755631 60.00 32.22 27.78 0.000 8866.07 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00767972 21.00 0.00767972 49.6528 6205.62 0.00 8895.23 8895.23 0.31841388 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60995.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 13934.519 13934.519 0.415793 0.00012191 367.505 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 4.2637 4.349472 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13934.52 13934.52 1.0000 0.50044598 0.415793 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.12189282 60.00 32.22 27.78 0.000 13934.52 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00757527 21.00 0.00757527 48.9868 9754.13 0.00 13980.35 13980.35 0.50044598 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60995.6
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 9083.089 9083.089 0.271048 0.00007946 239.548 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 2.7792 2.835163 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9083.09 9083.09 1.0000 0.32623243 0.271048 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07945472 60.00 32.22 27.78 0.000 9083.09 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00757357 21.00 0.00757357 48.9761 6357.98 0.00 9112.91 9112.91 0.32623243 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.6
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 13786.308 13786.308 0.411362 0.00012061 363.600 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 4.2183 4.303209 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13786.31 13786.31 1.0000 0.49511280 0.411362 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.12059633 60.00 32.22 27.78 0.000 13786.31 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00756778 21.00 0.00756778 48.9390 9650.53 0.00 13831.67 13831.67 0.49511280 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.2
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 9171.783 9171.783 0.273700 0.00008024 241.885 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 2.8064 2.862848 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9171.78 9171.78 1.0000 0.32942409 0.273700 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.08023057 60.00 32.22 27.78 0.000 9171.78 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00757991 21.00 0.00757991 49.0165 6419.98 0.00 9201.88 9201.88 0.32942409 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.1
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 106396.081 78429.069 4.792587 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7239 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.792587 5.76833342   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 109038.61 84716.67 1.0248 5.76833342 4.792587 26.02 18.44 0.01015835 52041.7 11.02 11.02 0.00850000 32508.9 -999.0 -999.00 -999.00 -999.00 10491.025 98547.59 32.10 0.01411964 23.13 1.19517000 24.9379 24.00 0.00884230 24.00 0.00884230 47.5542 65931.05 0.00 109708.64 79657.30 5.54052785 26.67 19.44 0.01118466 55322.4 12.59 12.57 0.00905807 35521.3
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 32080.026 32080.026 1.437776 0.00028065 521.080 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.792587 5.76833342   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 9.8158 10.013346 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:40:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 32080.03 32080.03 1.0000 1.73050003 1.437776 -5.65 -5.65 0.00251231 581.0 12.80 11.59 0.00800000 33059.8 0.28062144 60.00 32.22 27.78 0.000 32080.03 -10.70 0.00150390 -10.70 1.19517000 83.1263 19.24 0.00748011 19.60 0.00720214 50.8136 20341.80 0.00 29067.47 29067.47 1.73050003 2.80 -0.39 0.00251231 9109.8 19.44 8.59 0.00251231 25906.9
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 101930.724 74353.199 4.479330 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.9565 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.479330 5.39129943   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 104815.70 80269.71 1.0283 5.39129943 4.479330 26.16 18.59 0.01028347 52505.4 10.92 10.92 0.00850000 32406.4 -999.0 -999.00 -999.00 -999.00 10362.423 94453.27 32.10 0.01411964 23.13 1.19517000 26.6819 24.00 0.00888729 24.00 0.00888729 47.7930 61616.82 0.00 105104.26 75553.39 5.17838386 26.67 19.44 0.01118466 55322.4 12.38 12.37 0.00894724 35025.7
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 32842.076 32842.076 1.343799 0.00028732 528.506 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.479330 5.39129943   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 10.0490 10.251210 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 32842.08 32842.08 1.0000 1.61738983 1.343799 -7.41 -7.41 0.00216034 -2070.1 12.80 11.59 0.00800000 33059.8 0.28728750 60.00 32.22 27.78 0.000 32842.08 -10.70 0.00150390 -10.70 1.19517000 88.9396 19.07 0.00743903 19.64 0.00729015 51.2899 25616.80 0.00 29170.83 29170.83 1.61738983 2.80 -0.93 0.00216034 8227.7 20.68 8.76 0.00216034 26263.4
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 112787.589 83899.736 5.168174 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.5525 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 5.168174 6.22038835   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 115268.56 90485.56 1.0220 6.22038835 5.168174 25.87 18.32 0.01006617 51656.8 11.03 11.03 0.00850000 32520.3 -999.0 -999.00 -999.00 -999.00 11240.201 104028.36 32.10 0.01411964 23.13 1.19517000 23.1256 24.00 0.00884638 24.00 0.00884638 47.5762 71078.51 0.00 116299.14 85207.24 5.97473003 26.67 19.44 0.01118466 55322.4 12.71 12.70 0.00914433 35857.2
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 31977.945 31977.945 1.550452 0.00027976 523.451 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 5.168174 6.22038835   4197.9300 999.8980 2.80247416 54.44 82.22 27.78 326820.32 9.7846 9.981483 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:50:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 31977.94 31977.94 1.0000 1.86611650 1.550452 -4.25 -4.25 0.00286123 2859.3 12.80 11.59 0.00800000 33059.8 0.27972847 60.00 32.22 27.78 0.000 31977.94 -10.70 0.00150390 -10.70 1.19517000 77.0853 17.43 0.00742728 17.60 0.00734636 58.7339 30594.88 0.00 29447.05 29447.05 1.86611650 2.80 0.32 0.00286123 9984.2 18.42 8.52 0.00286123 25764.1



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialEnthalpy 0.00 4.79 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialEnthalpy 0.00 4.48 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialEnthalpy 0.00 5.17 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 2605.50 2343.33 42.67
CORE_MID 2401.50 3154.83 350.67
CORE_TOP 2860.50 3463.67 1026.67
PERIMETER_TOP_ZN_3 3734.33 3737.33 1993.83
PERIMETER_TOP_ZN_2 3707.50 3621.50 1793.33
PERIMETER_TOP_ZN_1 3512.50 3288.33 1453.83
PERIMETER_TOP_ZN_4 3664.17 3698.33 1854.33
PERIMETER_BOT_ZN_3 3453.00 3683.50 1656.00
PERIMETER_BOT_ZN_2 3427.33 3316.50 1296.00
PERIMETER_BOT_ZN_1 3289.33 3487.00 1318.00
PERIMETER_BOT_ZN_4 3502.83 3397.67 1401.50
PERIMETER_MID_ZN_3 3434.33 3506.50 1525.33
PERIMETER_MID_ZN_2 2925.50 2991.33 1274.50
PERIMETER_MID_ZN_1 3279.17 3001.50 1011.50
PERIMETER_MID_ZN_4 3449.50 3445.67 1432.67
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4972.00 4355.83 2446.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 2.67 0.33 2.67 0.00
CORE_MID 4.33 0.00 3.67 0.00
CORE_TOP 8.33 0.00 7.17 0.00
PERIMETER_TOP_ZN_3 46.83 3.50 26.17 3.17
PERIMETER_TOP_ZN_2 30.67 28.17 9.67 27.83
PERIMETER_TOP_ZN_1 24.83 27.67 10.67 27.00
PERIMETER_TOP_ZN_4 31.00 24.17 12.50 17.67
PERIMETER_BOT_ZN_3 20.33 0.00 14.50 0.00
PERIMETER_BOT_ZN_2 8.83 16.00 3.67 16.00
PERIMETER_BOT_ZN_1 302.17 30.50 299.67 30.17
PERIMETER_BOT_ZN_4 12.33 15.50 7.00 11.50
PERIMETER_MID_ZN_3 19.00 0.67 12.50 0.67
PERIMETER_MID_ZN_2 10.00 23.33 4.00 23.33
PERIMETER_MID_ZN_1 9.33 26.67 4.00 26.50
PERIMETER_MID_ZN_4 12.50 22.00 6.00 16.50
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 339.67 122.50 314.17 111.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.81 52.94 2698.04 0.824 0.000 0.000 0.000
CORE_MID 21.81 52.94 2698.04 0.607 0.000 0.000 0.000
CORE_TOP 21.81 52.94 2698.04 0.600 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.60 11.16 568.77 0.674 0.048 0.000 0.000
PERIMETER_TOP_ZN_2 2.91 7.07 360.08 1.053 0.050 0.000 0.000
PERIMETER_TOP_ZN_1 4.60 11.16 568.77 1.027 0.048 0.000 0.000
PERIMETER_TOP_ZN_4 2.91 7.06 360.05 1.105 0.050 0.000 0.000
PERIMETER_BOT_ZN_3 4.60 11.16 568.77 0.601 0.025 0.000 0.000
PERIMETER_BOT_ZN_2 2.91 7.07 360.08 0.902 0.027 0.000 0.000
PERIMETER_BOT_ZN_1 4.60 11.16 568.77 0.852 0.832 0.000 0.000
PERIMETER_BOT_ZN_4 2.91 7.06 360.05 0.898 0.027 0.000 0.000
PERIMETER_MID_ZN_3 4.60 11.16 568.77 0.670 0.040 0.000 0.000
PERIMETER_MID_ZN_2 2.55 7.07 360.08 0.968 0.045 0.000 0.000
PERIMETER_MID_ZN_1 4.60 11.16 568.77 1.017 0.040 0.000 0.000
PERIMETER_MID_ZN_4 2.91 7.06 360.05 1.068 0.042 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.81 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.81 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.81 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.91 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.91 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.91 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.91 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.55 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.60 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.91 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.81 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.81 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.81 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.91 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.91 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.91 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.91 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.55 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.60 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.91 7.06 360.05 131.25 0.0000 0.057
Total Facility   110.11 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 12983346.84 0.00 12983346.84 0.00 12983346.84 13393058.27 5623.66 344.01 2792.33 31.15
CORE_MID 9587059.67 0.00 9587059.67 0.00 9587059.67 13393058.27 6905.02 42.53 1812.45 32.18
CORE_TOP 9487165.78 0.00 9487165.78 0.00 9487165.78 13393058.27 6931.77 31.53 1796.70 46.36
PERIMETER_TOP_ZN_3 2246224.39 0.00 2246224.39 313577.76 2559802.14 2823374.22 5913.44 52.35 2794.21 46.36
PERIMETER_TOP_ZN_2 2222881.78 0.00 2222881.78 209050.58 2431932.36 1787429.43 4210.05 6.50 4543.45 46.36
PERIMETER_TOP_ZN_1 3417073.32 0.00 3417073.32 313577.76 3730651.08 2823374.22 4245.35 12.72 4501.94 46.36
PERIMETER_TOP_ZN_4 2333216.05 0.00 2333216.05 209050.58 2542266.63 1787312.18 4226.51 12.80 4520.68 46.36
PERIMETER_BOT_ZN_3 2003274.14 0.00 2003274.14 166727.58 2170001.71 2823374.22 6302.33 457.50 2000.17 31.15
PERIMETER_BOT_ZN_2 1901306.19 0.00 1901306.19 111151.05 2012457.24 1787429.43 4318.74 35.28 4405.98 31.15
PERIMETER_BOT_ZN_1 2840216.92 0.00 2840216.92 2860908.58 5701125.51 2823374.22 5506.36 242.07 3011.57 31.15
PERIMETER_BOT_ZN_4 1893716.58 0.00 1893716.58 111151.05 2004867.63 1787312.18 4356.16 47.70 4356.15 31.15
PERIMETER_MID_ZN_3 2229890.87 0.00 2229890.87 261029.36 2490920.23 2823374.22 5949.35 59.23 2751.42 32.18
PERIMETER_MID_ZN_2 2209440.02 0.00 2209440.02 174018.53 2383458.55 1787429.43 4190.15 9.16 4560.69 941.18
PERIMETER_MID_ZN_1 3383882.50 0.00 3383882.50 261029.36 3644911.86 2823374.22 4246.49 21.04 4492.47 32.18
PERIMETER_MID_ZN_4 2254158.48 0.00 2254158.48 174018.53 2428177.01 1787312.18 4203.26 14.19 4542.55 32.18
Total Facility 60992853.55 0.00 60992853.55 5165290.72 66158144.26 67843644.98 7100.27 771.08 4646.01 993.20


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.6053 0.0000 0.6053 0.0000 0.6053 0.4247 2816.83 344.01 2782.16
CORE_MID 0.4465 0.0000 0.4465 0.0000 0.4465 0.4247 4098.82 42.53 1801.65
CORE_TOP 0.4415 0.0000 0.4415 0.0000 0.4415 0.4247 4127.66 31.53 1783.81
PERIMETER_TOP_ZN_3 0.1046 0.0000 0.1046 0.0075 0.1121 0.0895 3109.33 52.35 2781.32
PERIMETER_TOP_ZN_2 0.1035 0.0000 0.1035 0.0050 0.1085 0.0567 1405.93 6.50 4530.56
PERIMETER_TOP_ZN_1 0.1592 0.0000 0.1592 0.0075 0.1667 0.0895 1441.24 12.72 4489.05
PERIMETER_TOP_ZN_4 0.1086 0.0000 0.1086 0.0050 0.1136 0.0567 1422.40 12.80 4507.80
PERIMETER_BOT_ZN_3 0.0933 0.0000 0.0933 0.0040 0.0973 0.0895 3495.49 457.50 1990.00
PERIMETER_BOT_ZN_2 0.0886 0.0000 0.0886 0.0026 0.0913 0.0567 1511.99 35.28 4395.73
PERIMETER_BOT_ZN_1 0.1324 0.0000 0.1324 0.1299 0.2623 0.0895 2699.53 242.07 3001.40
PERIMETER_BOT_ZN_4 0.0882 0.0000 0.0882 0.0026 0.0909 0.0567 1549.41 47.70 4345.89
PERIMETER_MID_ZN_3 0.1039 0.0000 0.1039 0.0062 0.1101 0.0895 3143.16 59.23 2740.61
PERIMETER_MID_ZN_2 0.0952 0.0000 0.0952 0.0044 0.0996 0.0567 1375.16 7.97 3650.86
PERIMETER_MID_ZN_1 0.1578 0.0000 0.1578 0.0062 0.1640 0.0895 1440.29 21.04 4481.67
PERIMETER_MID_ZN_4 0.1050 0.0000 0.1050 0.0041 0.1091 0.0567 1397.26 14.19 4531.55
Total Facility 2.8336 0.0000 2.8336 0.1851 3.0187 2.1513 4288.32 771.05 4626.54


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 31322311.26 0.00 31322311.26 22614548.33 4167.83 4.65 4587.53 31.15
PACU_VAV_MID 28486699.42 0.00 28486699.42 22614548.33 4165.32 3.16 4591.51 32.18
PACU_VAV_TOP 28547730.33 0.00 28547730.33 22614548.33 4198.65 1.01 4560.34 46.36


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.4600 0.0000 1.4600 0.7171 1360.99 4.65 4577.36
PACU_VAV_MID 1.3270 0.0000 1.3270 0.7171 1359.13 3.16 4580.71
PACU_VAV_TOP 1.3290 0.0000 1.3290 0.7171 1394.53 1.01 4547.46


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 0.00 2255.08 0.00 0.00 0.00 2441.48 0.00 0.00 0.00
PACU_VAV_MID 0.00 0.00 2051.35 0.00 0.00 0.00 2658.10 0.00 0.00 0.00
PACU_VAV_TOP 0.00 0.00 2065.75 0.00 0.00 0.00 2654.22 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 0.0000 2.6723 0.0000 0.0000 0.0000 1.1211 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 0.0000 2.4262 0.0000 0.0000 0.0000 1.1242 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 0.0000 2.4419 0.0000 0.0000 0.0000 1.1184 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 982
Defaulted Fields 577
Fields with Defaults 2420
Autosized Fields 193
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
Electricity:Building 1021.57 13465.67 21-MAY-17:20 74313.01 02-JAN-16:30
Electricity:Zone:CORE_BOTTOM 322.35 5243.28 01-JAN-00:10 20463.73 02-JAN-08:10
Electricity:SpaceType:GENERAL 1021.57 13465.67 21-MAY-17:20 74313.01 02-JAN-16:30
InteriorLights:Electricity 301.88 987.92 21-MAY-17:20 32642.50 02-JAN-16:30
InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 301.88 987.92 21-MAY-17:20 32642.50 02-JAN-16:30
LightsWired:InteriorLights:Electricity 301.88 987.92 21-MAY-17:20 32642.50 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 301.88 987.92 21-MAY-17:20 32642.50 02-JAN-16:30
Electricity:Zone:CORE_MID 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:CORE_TOP 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 33.23 422.10 09-APR-17:10 2793.69 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.89 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.89 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
Electricity:Zone:PERIMETER_TOP_ZN_2 21.00 267.21 14-MAY-17:10 1768.58 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.59 22.79 01-JAN-07:50 860.01 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.59 22.79 01-JAN-07:50 860.01 02-JAN-16:10
Electricity:Zone:PERIMETER_TOP_ZN_1 33.03 422.10 26-MAR-17:10 2793.68 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.70 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.70 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_4 20.94 267.21 12-MAR-17:10 1768.52 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.54 22.79 01-JAN-09:20 859.95 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.54 22.79 01-JAN-09:20 859.95 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_3 33.19 422.10 02-APR-17:10 2793.69 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.86 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.86 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
Electricity:Zone:PERIMETER_BOT_ZN_2 20.98 267.21 14-MAY-17:10 1768.58 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.58 22.79 01-JAN-07:50 860.01 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.58 22.79 01-JAN-07:50 860.01 02-JAN-16:10
Electricity:Zone:PERIMETER_BOT_ZN_1 33.02 422.10 26-MAR-17:10 2793.68 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.68 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.68 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_4 20.93 267.21 12-MAR-17:10 1768.52 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.52 22.79 01-JAN-09:10 859.95 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.52 22.79 01-JAN-09:10 859.95 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_3 33.23 422.10 09-APR-17:10 2793.69 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 8.89 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 8.89 36.00 01-JAN-09:20 1358.45 02-JAN-16:10
Electricity:Zone:PERIMETER_MID_ZN_2 21.00 267.21 14-MAY-17:10 1768.58 02-JAN-16:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.59 22.79 01-JAN-07:50 860.01 02-JAN-16:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.59 22.79 01-JAN-07:50 860.01 02-JAN-16:10
Electricity:Zone:PERIMETER_MID_ZN_1 33.03 422.10 26-MAR-17:10 2793.68 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.70 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.70 36.00 01-JAN-07:50 1358.45 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_4 20.94 267.21 12-MAR-17:10 1768.52 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.54 22.79 01-JAN-09:20 859.95 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.54 22.79 01-JAN-09:20 859.95 02-JAN-16:30
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 334.71 368.59 30-APR-17:30 99394.94 19-JUN-11:00
ExteriorEquipment:Electricity 26.90 367.92 01-JAN-00:10 1410.29 02-JAN-12:20
Transformer:ExteriorEquipment:Electricity 26.90 367.92 01-JAN-00:10 1410.29 02-JAN-12:20
ElectricityPurchased:Facility 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
ElectricityPurchased:Plant 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
Cogeneration:ElectricityPurchased 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
General:Cogeneration:ElectricityPurchased 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
ElectricityNet:Plant 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
Cogeneration:ElectricityNet 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
General:Cogeneration:ElectricityNet 1461.67 13841.23 30-APR-17:20 171124.26 19-JUN-11:00
Fans:Electricity 103.63 0.00 01-JAN-00:40 28789.94 10-JUL-15:30
General:Fans:Electricity 103.63 0.00 01-JAN-00:40 28789.94 10-JUL-15:30
ExteriorLights:Electricity 50.82 0.00 01-JAN-07:30 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 50.82 0.00 01-JAN-07:30 5686.19 01-JAN-06:10
Cooling:Electricity 204.18 0.00 01-JAN-00:10 74709.97 19-JUN-12:10
General:Cooling:Electricity 204.18 0.00 01-JAN-00:10 74709.97 19-JUN-12:10
Electricity:Plant 54.56 0.00 01-JAN-00:40 7315.13 06-FEB-12:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 52.85 0.00 01-JAN-00:10 6688.11 07-FEB-12:50
Water Heater:WaterSystems:Electricity 52.85 0.00 01-JAN-00:10 6688.11 07-FEB-12:50
Pumps:Electricity 1.71 0.00 01-JAN-00:40 840.41 02-JAN-07:10
General:Pumps:Electricity 1.71 0.00 01-JAN-00:40 840.41 02-JAN-07:10
WIRED_LTG_ELECTRICITY 8.48 0.00 01-JAN-00:10 917.25 02-JAN-16:40
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 341.43 0.00 01-JAN-00:40 265742.95 02-JAN-07:20
NaturalGas:Plant 341.43 0.00 01-JAN-00:40 265742.95 02-JAN-07:20
Heating:NaturalGas 341.43 0.00 01-JAN-00:40 265742.95 02-JAN-07:20
Boiler:Heating:NaturalGas 341.43 0.00 01-JAN-00:40 265742.95 02-JAN-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2579.06 0.00 01-JAN-00:40 564032.87 02-JAN-07:10
EnergyTransfer:Building 1166.33 0.00 01-JAN-00:40 173691.22 14-AUG-14:20
EnergyTransfer:Zone:CORE_BOTTOM 232.47 0.00 01-JAN-00:40 25803.41 05-SEP-07:50
Heating:EnergyTransfer 101.18 0.00 01-JAN-00:40 150929.91 02-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.18 0.00 01-JAN-00:10 7547.84 02-JAN-06:10
General:Heating:EnergyTransfer 101.18 0.00 01-JAN-00:40 150929.91 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.18 0.00 01-JAN-00:10 7547.84 02-JAN-06:10
Cooling:EnergyTransfer 1065.15 0.00 01-JAN-00:40 173691.22 14-AUG-14:20
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 232.29 0.00 01-JAN-00:40 25803.41 05-SEP-07:50
General:Cooling:EnergyTransfer 1065.15 0.00 01-JAN-00:40 173691.22 14-AUG-14:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 232.29 0.00 01-JAN-00:40 25803.41 05-SEP-07:50
EnergyTransfer:Zone:TOPFLOOR_PLENUM 51.69 0.00 01-JAN-00:40 13331.65 06-FEB-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 17.47 0.00 01-JAN-00:40 13331.65 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 17.47 0.00 01-JAN-00:40 13331.65 06-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 34.22 0.00 01-JAN-00:10 12459.99 19-JUN-13:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 34.22 0.00 01-JAN-00:10 12459.99 19-JUN-13:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 28.40 0.00 01-JAN-00:40 9475.25 02-JAN-08:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.45 0.00 01-JAN-00:40 9475.25 02-JAN-08:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.45 0.00 01-JAN-00:40 9475.25 02-JAN-08:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 19.95 0.00 01-JAN-00:10 5764.67 14-AUG-14:50
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 19.95 0.00 01-JAN-00:10 5764.67 14-AUG-14:50
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 30.08 0.00 01-JAN-00:40 7940.93 02-JAN-09:00
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 5.53 0.00 01-JAN-00:40 7940.93 02-JAN-09:00
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 5.53 0.00 01-JAN-00:40 7940.93 02-JAN-09:00
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 24.55 0.00 01-JAN-00:10 5946.67 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 24.55 0.00 01-JAN-00:10 5946.67 10-JUL-15:30
EnergyTransfer:Zone:CORE_MID 159.35 0.00 01-JAN-00:40 19728.86 14-AUG-09:20
Heating:EnergyTransfer:Zone:CORE_MID 0.85 0.00 01-JAN-00:20 15080.79 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.85 0.00 01-JAN-00:20 15080.79 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 158.50 0.00 01-JAN-00:40 19728.86 14-AUG-09:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 158.50 0.00 01-JAN-00:40 19728.86 14-AUG-09:20
EnergyTransfer:Zone:CORE_TOP 153.51 0.00 01-JAN-00:40 22032.16 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_TOP 4.67 0.00 01-JAN-00:40 22032.16 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 4.67 0.00 01-JAN-00:40 22032.16 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 148.85 0.00 01-JAN-00:20 21488.53 10-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 148.85 0.00 01-JAN-00:20 21488.53 10-JUL-14:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 43.55 0.00 01-JAN-00:40 8909.57 02-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 10.61 0.00 01-JAN-00:40 8909.57 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 10.61 0.00 01-JAN-00:40 8909.57 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 32.94 0.00 01-JAN-00:10 7961.54 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 32.94 0.00 01-JAN-00:10 7961.54 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 38.31 0.00 01-JAN-00:40 9422.93 26-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.50 0.00 01-JAN-00:40 6975.14 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.50 0.00 01-JAN-00:40 6975.14 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 32.81 0.00 01-JAN-00:10 9422.93 26-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 32.81 0.00 01-JAN-00:10 9422.93 26-JUN-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 60.69 0.00 01-JAN-00:40 13494.58 28-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 6.73 0.00 01-JAN-00:40 9795.54 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 6.73 0.00 01-JAN-00:40 9795.54 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.96 0.00 01-JAN-00:10 13494.58 28-SEP-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.96 0.00 01-JAN-00:10 13494.58 28-SEP-12:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 39.85 0.00 01-JAN-00:40 9902.20 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.38 0.00 01-JAN-00:40 7186.40 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.38 0.00 01-JAN-00:40 7186.40 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 33.47 0.00 01-JAN-00:10 9902.20 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 33.47 0.00 01-JAN-00:10 9902.20 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 35.24 0.00 01-JAN-00:40 6847.83 02-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.86 0.00 01-JAN-00:40 6847.83 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.86 0.00 01-JAN-00:40 6847.83 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 30.38 0.00 01-JAN-00:10 6242.67 10-JUL-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 30.38 0.00 01-JAN-00:10 6242.67 10-JUL-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 32.79 0.00 01-JAN-00:40 7564.82 22-AUG-09:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.15 0.00 01-JAN-00:40 5359.39 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.15 0.00 01-JAN-00:40 5359.39 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 30.63 0.00 01-JAN-00:10 7564.82 22-AUG-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 30.63 0.00 01-JAN-00:10 7564.82 22-AUG-09:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 57.36 0.00 01-JAN-00:40 12767.65 19-JUN-12:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.70 0.00 01-JAN-00:40 10998.97 02-JAN-07:50
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.70 0.00 01-JAN-00:40 10998.97 02-JAN-07:50
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 44.66 0.00 01-JAN-00:20 12767.65 19-JUN-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 44.66 0.00 01-JAN-00:20 12767.65 19-JUN-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 32.95 0.00 01-JAN-00:40 7873.06 21-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.53 0.00 01-JAN-00:40 5481.20 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.53 0.00 01-JAN-00:40 5481.20 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 30.43 0.00 01-JAN-00:10 7873.06 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 30.43 0.00 01-JAN-00:10 7873.06 21-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 38.88 0.00 01-JAN-00:40 7322.51 02-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.66 0.00 01-JAN-00:40 7322.51 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.66 0.00 01-JAN-00:40 7322.51 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 34.22 0.00 01-JAN-00:10 7182.60 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 34.22 0.00 01-JAN-00:10 7182.60 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 35.96 0.00 01-JAN-00:40 9241.52 26-JUN-08:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.46 0.00 01-JAN-00:40 5786.68 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.46 0.00 01-JAN-00:40 5786.68 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 33.50 0.00 01-JAN-00:10 9241.52 26-JUN-08:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 33.50 0.00 01-JAN-00:10 9241.52 26-JUN-08:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 58.36 0.00 01-JAN-00:40 12520.38 28-SEP-12:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.65 0.00 01-JAN-00:40 8163.68 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.65 0.00 01-JAN-00:40 8163.68 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 55.71 0.00 01-JAN-00:10 12520.38 28-SEP-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 55.71 0.00 01-JAN-00:10 12520.38 28-SEP-12:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 36.88 0.00 01-JAN-00:40 9428.95 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.78 0.00 01-JAN-00:40 5876.25 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.78 0.00 01-JAN-00:40 5876.25 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 34.09 0.00 01-JAN-00:10 9428.95 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 34.09 0.00 01-JAN-00:10 9428.95 15-AUG-16:00
PlantLoopHeatingDemand:Facility 283.94 0.00 01-JAN-00:40 214196.94 02-JAN-07:10
PlantLoopHeatingDemand:Plant 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
EnergyTransfer:HVAC 1130.48 0.00 01-JAN-00:40 285252.06 16-AUG-12:30
HeatingCoils:EnergyTransfer 233.88 0.00 01-JAN-00:40 212098.37 02-JAN-07:10
PlantLoopHeatingDemand:HVAC 233.88 0.00 01-JAN-00:40 212098.37 02-JAN-07:10
HeatingCoils:PlantLoopHeatingDemand 233.88 0.00 01-JAN-00:40 212098.37 02-JAN-07:10
CoolingCoils:EnergyTransfer 896.61 0.00 01-JAN-00:10 285245.64 16-AUG-12:30
EnergyTransfer:Plant 282.25 0.00 01-JAN-00:40 212712.26 02-JAN-07:20
WaterSystems:EnergyTransfer 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 50.06 0.00 01-JAN-00:10 6459.49 09-FEB-12:10
Boilers:EnergyTransfer 232.19 0.00 01-JAN-00:40 210613.69 02-JAN-07:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.185 -232.287 0.000 0.000 32.955 71.928 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -123.204
CORE_MID 0.000 0.000 0.850 -158.501 0.000 0.000 34.220 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -63.923
CORE_TOP 0.000 0.000 4.669 -148.845 0.000 0.000 34.922 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -78.100
PERIMETER_TOP_ZN_3 0.000 0.000 10.614 -32.940 0.000 0.000 7.521 8.893 24.333 18.649 0.000 0.063 0.000 0.000 -29.120 0.000 -4.183 -3.830
PERIMETER_TOP_ZN_2 0.000 0.000 5.500 -32.814 0.000 0.000 4.719 5.593 15.404 33.324 0.000 0.041 0.001 0.000 -18.374 0.000 -2.826 -10.567
PERIMETER_TOP_ZN_1 0.000 0.000 6.727 -53.960 0.000 0.000 7.316 8.700 24.332 67.848 0.000 0.061 0.001 0.000 -27.641 0.000 -4.386 -28.997
PERIMETER_TOP_ZN_4 0.000 0.000 6.385 -33.466 0.000 0.000 4.764 5.538 15.403 33.996 0.000 0.042 0.001 0.000 -18.952 0.000 -2.841 -10.869
PERIMETER_BOT_ZN_3 0.000 0.000 4.865 -30.379 0.000 0.000 7.489 8.862 24.333 18.911 0.000 0.037 0.001 0.000 -30.506 0.000 -2.362 -1.248
PERIMETER_BOT_ZN_2 0.000 0.000 2.154 -30.632 0.000 0.000 4.674 5.579 15.404 33.431 0.000 0.022 0.001 0.000 -19.615 0.000 -1.620 -9.397
PERIMETER_BOT_ZN_1 0.000 0.000 12.703 -44.659 0.000 0.000 7.456 8.683 24.332 68.522 0.000 1.992 0.004 0.000 -29.507 0.000 -31.706 -17.817
PERIMETER_BOT_ZN_4 0.000 0.000 2.529 -30.425 0.000 0.000 4.707 5.524 15.403 34.151 0.000 0.023 0.000 0.000 -20.245 0.000 -1.629 -10.037
PERIMETER_MID_ZN_3 0.000 0.000 4.658 -34.217 0.000 0.000 7.444 8.893 24.333 18.450 0.000 0.054 4.994 0.000 -30.914 0.000 -3.694 -0.000
PERIMETER_MID_ZN_2 0.000 0.000 2.461 -33.496 0.000 0.000 3.463 5.593 15.404 33.150 0.000 0.035 0.000 0.000 -19.446 0.000 -2.490 -4.674
PERIMETER_MID_ZN_1 0.000 0.000 2.650 -55.713 0.000 0.000 7.221 8.700 24.332 67.574 0.000 0.051 0.000 0.000 -29.333 0.000 -3.874 -21.609
PERIMETER_MID_ZN_4 0.000 0.000 2.783 -34.094 0.000 0.000 4.711 5.538 15.403 33.854 0.000 0.035 0.000 0.000 -20.105 0.000 -2.507 -5.620
TOPFLOOR_PLENUM 17.469 -34.217 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.062 23.129 0.000 0.000 0.000 -6.442 -0.002
MIDFLOOR_PLENUM 8.446 -19.953 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.072 17.821 0.000 0.000 0.000 -6.386 -0.000
FIRSTFLOOR_PLENUM 5.535 -24.545 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.055 24.182 0.000 0.000 0.000 -5.226 -0.000
Total Facility 31.450 -78.715 69.732 -986.429 0.000 0.000 173.582 301.881 719.689 461.859 0.000 2.645 70.135 0.000 -293.758 0.000 -82.173 -389.893


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 19-JUN-05:03 0.00 0.00 0.00 -44126.20 0.00 0.00 285.69 211.73 7410.35 0.00 0.00 0.00 36218.43 0.00 -0.00 0.00 0.00 0.00
CORE_MID 19-JUN-05:03 0.00 0.00 0.00 -35206.16 0.00 0.00 304.30 211.73 3025.92 0.00 0.00 0.00 31664.20 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-05:03 0.00 0.00 0.00 -35032.67 0.00 0.00 306.65 211.73 3025.92 0.00 0.00 0.00 31488.37 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 10-JUL-04:02 0.00 0.00 0.00 -10458.06 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 10050.59 0.00 -151.14 0.00 -0.82 0.00
PERIMETER_TOP_ZN_2 02-JUL-08:42 0.00 0.00 0.00 -13765.90 0.00 0.00 13.35 22.79 302.86 10507.81 0.00 0.00 2935.90 0.00 -0.00 0.00 -16.81 0.00
PERIMETER_TOP_ZN_1 04-SEP-12:42 0.00 0.00 0.00 -17318.37 0.00 0.00 21.12 36.00 478.41 12703.69 0.00 0.00 4101.51 0.00 -0.00 0.00 -22.36 0.00
PERIMETER_TOP_ZN_4 02-JUL-16:02 0.00 0.00 0.00 -15121.61 0.00 0.00 12.66 22.79 302.86 10563.95 0.00 0.00 4270.79 0.00 -0.00 0.00 -51.42 0.00
PERIMETER_BOT_ZN_3 10-JUL-06:03 0.00 0.00 0.00 -7817.90 0.00 0.00 145.85 237.05 637.89 1041.02 0.00 4.66 5751.42 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 10-SEP-09:12 0.00 0.00 0.00 -11581.52 0.00 0.00 16.30 22.79 302.86 9055.59 0.00 0.00 2242.70 0.00 -0.00 0.00 -58.71 0.00
PERIMETER_BOT_ZN_1 03-SEP-12:52 0.00 0.00 0.00 -14532.50 0.00 0.00 24.93 36.00 478.41 11283.26 0.00 0.00 2745.63 0.00 -0.00 0.00 -35.73 0.00
PERIMETER_BOT_ZN_4 10-SEP-16:31 0.00 0.00 0.00 -12363.99 0.00 0.00 15.01 22.79 302.86 10062.26 0.00 0.00 2008.90 0.00 -0.00 0.00 -47.83 0.00
PERIMETER_MID_ZN_3 09-JUL-14:41 0.00 0.00 0.00 -9048.86 0.00 0.00 28.41 36.00 478.42 3699.86 0.00 24.91 4781.27 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 09-JUL-09:21 0.00 0.00 0.00 -14565.26 0.00 0.00 13.78 22.79 302.86 8726.90 0.00 4.87 5494.06 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 10-SEP-13:12 0.00 0.00 0.00 -16591.85 0.00 0.00 23.27 36.00 478.41 12000.00 0.00 0.00 4146.76 0.00 -0.00 0.00 -92.59 0.00
PERIMETER_MID_ZN_4 10-SEP-15:51 0.00 0.00 0.00 -14747.28 0.00 0.00 13.67 22.79 302.86 11151.41 0.00 0.00 3325.49 0.00 -0.00 0.00 -68.93 0.00
TOPFLOOR_PLENUM 19-JUN-13:40 0.00 -12459.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.59 12397.98 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 14-AUG-14:50 0.00 -5765.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.32 5736.06 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 19-JUN-12:08 0.00 -6557.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.14 6495.45 0.00 -0.00 0.00 0.00 0.00
Total Facility 19-JUN-05:02 0.00 10843.67 0.00 -212548.90 0.00 0.00 1535.05 1072.56 19712.35 17263.51 0.00 0.00 162296.59 0.00 0.00 0.00 -174.83 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-05:02 0.00 0.00 9047.19 0.00 0.00 0.00 0.00 211.73 5642.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14900.98
CORE_MID 02-JAN-05:02 0.00 0.00 16183.53 0.00 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18837.32
CORE_TOP 02-JAN-04:42 0.00 0.00 24010.57 0.00 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -26664.36
PERIMETER_TOP_ZN_3 02-JAN-00:42 0.00 0.00 9860.22 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3175.55 0.00 -933.01 -6311.09
PERIMETER_TOP_ZN_2 02-JAN-00:42 0.00 0.00 8430.12 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2062.36 0.00 -628.97 -6092.93
PERIMETER_TOP_ZN_1 02-JAN-00:42 0.00 0.00 11441.42 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3117.94 0.00 -945.98 -7936.93
PERIMETER_TOP_ZN_4 02-JAN-00:42 0.00 0.00 8825.44 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2117.06 0.00 -628.88 -6433.64
PERIMETER_BOT_ZN_3 01-JAN-23:22 0.00 0.00 7497.82 0.00 0.00 0.00 0.00 44.64 386.10 0.00 0.00 0.00 0.00 0.00 -3162.15 0.00 -565.58 -4200.82
PERIMETER_BOT_ZN_2 02-JAN-00:42 0.00 0.00 6448.43 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2111.68 0.00 -343.56 -4347.34
PERIMETER_BOT_ZN_1 02-JAN-07:50 0.00 0.00 10998.61 0.00 0.00 0.00 255.01 216.00 637.88 206.70 0.00 0.00 7606.59 0.00 -0.00 0.00 -19920.79 0.00
PERIMETER_BOT_ZN_4 02-JAN-00:42 0.00 0.00 6607.57 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2154.56 0.00 -342.20 -4464.96
PERIMETER_MID_ZN_3 01-JAN-23:22 0.00 0.00 8074.34 0.00 0.00 0.00 0.00 44.64 386.10 0.00 0.00 0.00 0.00 0.00 -3177.31 0.00 -879.33 -4448.44
PERIMETER_MID_ZN_2 01-JAN-23:22 0.00 0.00 7216.25 0.00 0.00 0.00 0.00 28.26 244.42 0.00 0.00 0.00 0.00 0.00 -2067.05 0.00 -592.94 -4828.94
PERIMETER_MID_ZN_1 02-JAN-00:42 0.00 0.00 9454.86 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3186.84 0.00 -801.81 -6025.64
PERIMETER_MID_ZN_4 01-JAN-23:22 0.00 0.00 7360.73 0.00 0.00 0.00 0.00 28.26 244.42 0.00 0.00 0.00 0.00 0.00 -2119.30 0.00 -592.01 -4922.09
TOPFLOOR_PLENUM 02-JAN-06:10 14719.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -162.34 -14557.25
MIDFLOOR_PLENUM 02-JAN-08:15 9742.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -148.91 -9593.93
FIRSTFLOOR_PLENUM 02-JAN-12:01 8086.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -81.50 -8004.70
Total Facility 02-JAN-05:22 19476.05 0.00 144559.10 0.00 0.00 0.00 0.00 1072.56 15570.33 0.00 0.00 0.00 0.00 0.00 -32697.52 0.00 -4653.81 -143326.70



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 5.3460 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.7926 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 5.2070 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.4793 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.6230 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.1682 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.6730 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3626 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.6035 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.4024 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.8115 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.4741 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6547 2.6547 0.7725 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1623 2.1623 0.7590 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3043 2.3043 0.7881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7180 0.7180 0.1659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7837 0.7837 0.1567 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9714 0.9714 0.1943 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8456 0.8456 0.1691 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5765 0.5765 0.1632 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6525 0.6525 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7928 0.7928 0.1625 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6694 0.6694 0.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6270 0.6270 0.1599 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7595 0.7595 0.1519 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8794 0.8794 0.1759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7788 0.7788 0.1558 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 5.3460 4.7926 5.3460 1.3626 0.0000 1.0000
PACU_VAV_MID 5.2070 4.4793 5.2070 1.4024 0.0000 1.0000
PACU_VAV_TOP 5.6230 5.1682 5.6230 1.4741 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3273 1.3273 0.7725 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0812 1.0812 0.7590 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1522 1.1522 0.7881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3590 0.3590 0.1659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3919 0.3919 0.1567 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4857 0.4857 0.1943 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4228 0.4228 0.1691 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2883 0.2883 0.1632 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3263 0.3263 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3964 0.3964 0.1625 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3347 0.3347 0.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3135 0.3135 0.1599 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3798 0.3798 0.1519 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4397 0.4397 0.1759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3894 0.3894 0.1558 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.6730 1.3626 1.3626 1.3626 0.0000 1.0000
PACU_VAV_MID 2.6035 1.4024 1.4024 1.4024 0.0000 1.0000
PACU_VAV_TOP 2.8115 1.4741 1.4741 1.4741 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 314.17
Number of hours cooling loads not met 111.00
Number of hours not met 425.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 341.43 265742.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 204.18 74709.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 301.88 32642.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 50.82 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.90 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 103.63 28789.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.71 840.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 52.85 6688.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1461.67
Natural Gas 0.00 341.43
Additional 0.00 0.00
Total 719.69 1803.10


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 60.59
Space Heating 0.00
Space Cooling 40.98
Fans (All) 20.80
Service Water Heating 10.61
Receptacle Equipment 144.45
Miscellaneous (All) 293.38
Subtotal 293.38


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 68.53
Service Water Heating 0.00
Miscellaneous (All) 68.53
Subtotal 68.53


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 16.74
Space Heating 18.94
Space Cooling 11.32
Fans (All) 5.75
Service Water Heating 2.93
Receptacle Equipment 39.91
Miscellaneous 4.41


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 1574. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8395.83 364.17 0.00 0.00 0.00
CORE_MID 8743.67 16.33 0.00 0.00 0.00
CORE_TOP 8753.83 6.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8723.50 36.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8680.33 79.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8680.17 79.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8638.83 121.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8756.00 4.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8716.17 43.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8708.33 51.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8661.83 98.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8732.67 27.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8684.50 75.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8683.67 76.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8630.50 129.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8639.33 120.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8395.83 0.00 0.00 0.00 0.00
Max 8760.00 364.17 0.00 0.00 0.00
Average 8686.06 73.94 0.00 0.00 0.00
Sum 156349.17 1330.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128170.33 133.67 0.00 0.00 0.00
CORE_MID 128303.00 1.00 0.00 0.00 0.00
CORE_TOP 128300.33 3.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128303.00 133.67 0.00 0.00 0.00
Average 34135.65 7.69 0.00 0.00 0.00
Sum 614441.67 138.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 7909.17 850.83 0.00 0.00 0.00
CORE_MID 8256.00 504.00 0.00 0.00 0.00
CORE_TOP 8372.33 387.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8099.83 660.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8126.17 633.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8098.50 661.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8100.00 660.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8218.17 541.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8124.83 635.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7824.50 935.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8026.83 733.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8056.33 703.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8076.17 683.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8025.83 734.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8031.17 728.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 7589.33 1170.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8088.33 671.67 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8057.67 702.33 0.00 0.00 0.00
Min 7589.33 387.67 0.00 0.00 0.00
Max 8372.33 1170.67 0.00 0.00 0.00
Average 8060.06 699.94 0.00 0.00 0.00
Sum 145081.17 12598.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 127843.00 461.00 0.00 0.00 0.00
CORE_MID 128066.00 238.00 0.00 0.00 0.00
CORE_TOP 128137.83 166.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24823.50 85.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14006.00 10.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24871.00 38.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24858.17 50.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14001.00 15.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 23605.67 1303.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14015.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24882.50 26.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24886.67 22.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14014.00 2.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128137.83 1303.33 0.00 0.00 0.00
Average 34008.91 134.43 0.00 0.00 0.00
Sum 612160.33 2419.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:07

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.965619E+10 12200.66 27-JAN-16:30 5.00 2.53 0.183521E+10 2606.62 26-JAN-10:09 5.00 2.53
February 0.993481E+10 13132.60 24-FEB-17:00 6.70 1.42 0.174368E+10 2606.64 01-FEB-10:30 6.70 1.42
March 0.146445E+11 17601.22 29-MAR-16:00 7.20 4.88 0.214245E+10 2606.67 27-MAR-09:09 7.20 4.88
April 0.166767E+11 36452.65 10-APR-06:03 15.78 13.94 0.191200E+10 2606.67 26-APR-09:00 16.10 12.59
May 0.227141E+11 40527.48 30-MAY-05:12 18.53 14.51 0.207699E+10 2606.78 15-MAY-13:00 18.53 14.51
June 0.265993E+11 44122.38 19-JUN-05:03 24.08 22.05 0.207329E+10 2606.65 22-JUN-09:09 25.68 16.96
July 0.274597E+11 43854.10 25-JUL-05:03 23.90 23.41 0.192720E+10 2606.66 12-JUL-13:50 23.90 23.41
August 0.296390E+11 41921.71 01-AUG-04:03 23.90 20.81 0.216289E+10 2606.69 08-AUG-13:30 26.40 17.05
September 0.251232E+11 43602.31 01-SEP-05:03 24.08 21.83 0.192065E+10 2606.72 19-SEP-09:09 18.58 14.06
October 0.230841E+11 39397.01 06-OCT-05:12 19.40 18.16 0.199547E+10 2606.74 16-OCT-09:09 16.88 14.11
November 0.150225E+11 24335.57 03-NOV-06:03 8.40 6.00 0.196124E+10 2606.70 09-NOV-14:00 13.90 12.65
December 0.117327E+11 14702.61 21-DEC-16:10 2.62 -2.3 0.188803E+10 2606.64 04-DEC-10:09 2.62 -2.3
                     
Annual Sum or Average 0.232287E+12         0.236391E+11        
Minimum of Months 0.965619E+10 12200.66   2.62 -2.3 0.174368E+10 2606.62   2.62 -2.3
Maximum of Months 0.296390E+11 44122.38   24.08 23.41 0.216289E+10 2606.78   26.40 23.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8479200.36 467.96 17-JAN-14:20 10.93 5.12 0.00 0.00 01-JAN-00:10 10.93 5.12
February 42218196.73 928.43 17-FEB-13:00 6.70 1.56 0.00 0.00 01-FEB-00:10 6.70 1.56
March 0.639621E+09 3041.25 03-MAR-14:30 15.00 8.51 0.00 0.00 01-MAR-00:10 15.00 8.51
April 0.163305E+10 7520.79 07-APR-14:30 25.85 15.95 0.00 0.00 01-APR-00:10 25.85 15.95
May 0.363191E+10 11096.85 30-MAY-13:50 29.50 17.11 0.00 0.00 01-MAY-00:10 29.50 17.11
June 0.610886E+10 12459.99 19-JUN-13:40 34.60 23.77 0.00 0.00 01-JUN-00:10 34.60 23.77
July 0.746608E+10 11613.76 10-JUL-13:50 32.70 20.82 0.00 0.00 01-JUL-00:10 32.70 20.82
August 0.801329E+10 11161.93 01-AUG-14:40 30.97 22.94 0.00 0.00 01-AUG-00:10 30.97 22.94
September 0.409140E+10 9908.45 01-SEP-14:50 30.68 17.45 0.00 0.00 01-SEP-00:10 30.68 17.45
October 0.230434E+10 7051.42 04-OCT-14:50 23.98 19.09 0.00 0.00 01-OCT-00:10 23.98 19.09
November 0.270100E+09 2506.09 04-NOV-13:00 17.80 12.74 0.00 0.00 01-NOV-00:10 17.80 12.74
December 7953150.22 1189.86 17-DEC-13:20 12.20 5.06 0.00 0.00 01-DEC-00:10 12.20 5.06
                     
Annual Sum or Average 0.342173E+11         0.00        
Minimum of Months 7953150.22 467.96   6.70 1.56 0.00 0.00   6.70 1.56
Maximum of Months 0.801329E+10 12459.99   34.60 23.77 0.00 0.00   34.60 23.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 14366612.90 2142.21 05-JAN-05:01 -7.8 -9.6 0.00 0.00 01-JAN-00:10 -7.8 -9.6
February 21306093.38 1923.34 03-FEB-06:01 -7.8 -9.5 0.00 0.00 01-FEB-00:10 -7.8 -9.5
March 0.227657E+09 2524.67 16-MAR-06:02 1.20 -1.9 0.00 0.00 01-MAR-00:10 1.20 -1.9
April 0.705898E+09 2402.14 10-APR-16:00 20.00 11.13 0.00 0.00 01-APR-00:10 20.00 11.13
May 0.176308E+10 5089.64 30-MAY-14:10 29.22 16.98 0.00 0.00 01-MAY-00:10 29.22 16.98
June 0.357170E+10 5240.77 19-JUN-15:10 32.93 23.30 0.00 0.00 01-JUN-00:10 32.93 23.30
July 0.446867E+10 5626.28 10-JUL-15:10 32.93 20.87 0.00 0.00 01-JUL-00:10 32.93 20.87
August 0.487190E+10 5764.67 14-AUG-14:50 28.58 23.14 0.00 0.00 01-AUG-00:10 28.58 23.14
September 0.272003E+10 5389.19 05-SEP-15:20 25.93 21.57 0.00 0.00 01-SEP-00:10 25.93 21.57
October 0.137446E+10 3360.27 04-OCT-15:40 23.17 19.12 0.00 0.00 01-OCT-00:10 23.17 19.12
November 0.194477E+09 1669.62 18-NOV-07:03 2.88 1.89 0.00 0.00 01-NOV-00:10 2.88 1.89
December 19303094.65 1734.49 23-DEC-06:11 2.93 2.42 0.00 0.00 01-DEC-00:10 2.93 2.42
                     
Annual Sum or Average 0.199529E+11         0.00        
Minimum of Months 14366612.90 1669.62   -7.8 -9.6 0.00 0.00   -7.8 -9.6
Maximum of Months 0.487190E+10 5764.67   32.93 23.30 0.00 0.00   32.93 23.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 57056675.73 1758.98 25-JAN-06:11 3.30 0.42 0.00 0.00 01-JAN-00:10 3.30 0.42
February 75296640.37 2203.45 24-FEB-06:11 4.80 4.55 0.00 0.00 01-FEB-00:10 4.80 4.55
March 0.381794E+09 2939.92 16-MAR-06:02 1.20 -1.9 0.00 0.00 01-MAR-00:10 1.20 -1.9
April 0.100543E+10 2928.68 10-APR-15:50 20.00 11.21 0.00 0.00 01-APR-00:10 20.00 11.21
May 0.223899E+10 5297.27 30-MAY-14:10 29.22 16.98 0.00 0.00 01-MAY-00:10 29.22 16.98
June 0.403562E+10 6558.32 19-JUN-12:08 36.42 24.23 0.00 0.00 01-JUN-00:10 36.42 24.23
July 0.489686E+10 6055.16 10-JUL-12:10 31.28 20.14 0.00 0.00 01-JUL-00:10 31.28 20.14
August 0.550376E+10 5946.36 14-AUG-15:50 27.88 22.79 0.00 0.00 01-AUG-00:10 27.88 22.79
September 0.352570E+10 5583.10 05-SEP-16:00 25.60 21.66 0.00 0.00 01-SEP-00:10 25.60 21.66
October 0.230684E+10 4073.00 04-OCT-16:00 22.80 19.11 0.00 0.00 01-OCT-00:10 22.80 19.11
November 0.423593E+09 2144.33 03-NOV-06:08 8.40 6.00 0.00 0.00 01-NOV-00:10 8.40 6.00
December 94410241.11 2156.41 20-DEC-07:02 1.78 1.02 0.00 0.00 01-DEC-00:10 1.78 1.02
                     
Annual Sum or Average 0.245454E+11         0.00        
Minimum of Months 57056675.73 1758.98   1.20 -1.9 0.00 0.00   1.20 -1.9
Maximum of Months 0.550376E+10 6558.32   36.42 24.23 0.00 0.00   36.42 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.646613E+10 7205.30 20-JAN-17:00 5.60 3.19 0.159344E+10 2395.86 20-JAN-14:00 5.60 3.19
February 0.672563E+10 7211.45 02-FEB-17:00 2.80 -3.1 0.148278E+10 2409.16 02-FEB-14:00 2.80 -3.1
March 0.977127E+10 10562.61 29-MAR-16:00 7.20 4.88 0.195126E+10 2606.59 29-MAR-13:09 7.20 4.88
April 0.110930E+11 14840.05 10-APR-16:00 20.00 11.13 0.183472E+10 2606.64 07-APR-13:09 20.00 11.13
May 0.155222E+11 31832.95 30-MAY-05:12 18.53 14.51 0.205729E+10 2606.74 15-MAY-13:00 18.53 14.51
June 0.190051E+11 35205.20 19-JUN-05:03 24.08 22.05 0.206745E+10 2606.66 23-JUN-09:09 27.25 18.76
July 0.201703E+11 34919.84 25-JUL-05:03 23.90 23.41 0.192219E+10 2606.67 17-JUL-09:20 23.90 23.41
August 0.214660E+11 32980.65 07-AUG-05:12 19.40 16.84 0.215865E+10 2606.66 23-AUG-13:09 25.60 17.07
September 0.170224E+11 30740.55 01-SEP-05:02 24.08 21.83 0.191122E+10 2606.69 19-SEP-09:09 18.58 14.06
October 0.144322E+11 16176.59 05-OCT-16:00 21.70 19.15 0.197341E+10 2606.71 16-OCT-09:09 16.88 14.11
November 0.899844E+10 12192.31 03-NOV-16:00 15.00 10.26 0.179770E+10 2606.66 09-NOV-14:00 13.90 12.65
December 0.782793E+10 7405.35 21-DEC-16:20 2.43 -2.4 0.162388E+10 2480.62 21-DEC-14:00 2.43 -2.4
                     
Annual Sum or Average 0.158501E+12         0.223740E+11        
Minimum of Months 0.646613E+10 7205.30   2.43 -3.1 0.148278E+10 2395.86   2.43 -3.1
Maximum of Months 0.214660E+11 35205.20   24.08 23.41 0.215865E+10 2606.74   27.25 23.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.461068E+10 7036.89 20-JAN-16:40 6.13 3.40 0.151564E+10 2287.85 20-JAN-16:49 5.87 3.30
February 0.478622E+10 7110.39 02-FEB-17:00 2.80 -3.1 0.139687E+10 2329.48 02-FEB-14:00 2.80 -3.1
March 0.874610E+10 10111.32 29-MAR-16:00 7.20 4.88 0.183141E+10 2606.58 29-MAR-13:39 7.20 4.88
April 0.103672E+11 15582.59 10-APR-15:50 20.00 11.21 0.176254E+10 2606.64 07-APR-13:09 20.00 11.21
May 0.152960E+11 25095.91 30-MAY-05:12 18.53 14.51 0.203079E+10 2606.74 15-MAY-13:00 18.53 14.51
June 0.194690E+11 35031.03 19-JUN-05:03 24.08 22.05 0.206378E+10 2606.67 23-JUN-09:09 27.25 18.76
July 0.211403E+11 33982.43 25-JUL-05:02 23.90 23.41 0.192189E+10 2606.67 14-JUL-09:00 23.90 23.41
August 0.221768E+11 34402.80 07-AUG-05:12 19.40 16.84 0.215684E+10 2606.70 31-AUG-09:09 24.18 20.67
September 0.163905E+11 34069.10 01-SEP-05:02 24.08 21.83 0.189867E+10 2606.69 11-SEP-13:09 20.60 12.01
October 0.129160E+11 16633.01 04-OCT-15:50 22.98 19.12 0.192267E+10 2606.70 16-OCT-09:09 16.88 14.11
November 0.742614E+10 10842.23 03-NOV-16:00 15.00 10.26 0.166884E+10 2606.58 03-NOV-13:09 15.00 10.26
December 0.552024E+10 7045.79 21-DEC-16:10 2.62 -2.3 0.150223E+10 2328.24 21-DEC-14:00 2.62 -2.3
                     
Annual Sum or Average 0.148845E+12         0.216722E+11        
Minimum of Months 0.461068E+10 7036.89   2.62 -3.1 0.139687E+10 2287.85   2.62 -3.1
Maximum of Months 0.221768E+11 35031.03   24.08 23.41 0.215684E+10 2606.74   27.25 23.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154231E+09 1167.22 20-JAN-16:10 6.93 3.71 0.305106E+09 421.95 20-JAN-14:00 6.93 3.71
February 0.179814E+09 1207.09 24-FEB-15:50 7.88 1.88 0.277759E+09 428.42 24-FEB-14:00 7.88 1.88
March 0.979138E+09 1715.71 28-MAR-14:00 13.30 8.41 0.354282E+09 548.88 28-MAR-13:00 13.30 8.41
April 0.186159E+10 4151.27 07-APR-15:20 25.60 16.01 0.350990E+09 549.50 07-APR-13:09 25.60 16.01
May 0.363891E+10 8019.78 29-MAY-14:53 25.60 17.03 0.421930E+09 549.52 15-MAY-13:00 25.60 17.03
June 0.560392E+10 9657.68 19-JUN-05:02 24.08 22.05 0.435069E+09 549.67 19-JUN-13:50 34.50 23.73
July 0.652535E+10 10460.75 10-JUL-04:02 26.10 21.38 0.405937E+09 549.51 11-JUL-13:50 28.72 17.86
August 0.651859E+10 10255.00 13-AUG-15:52 30.00 20.46 0.454636E+09 549.51 29-AUG-09:09 23.77 18.41
September 0.392055E+10 6200.27 01-SEP-14:00 31.10 17.34 0.396087E+09 549.51 11-SEP-13:09 20.60 12.01
October 0.250558E+10 4274.36 04-OCT-14:00 24.40 18.95 0.388348E+09 549.50 12-OCT-13:00 20.60 17.37
November 0.867300E+09 1681.96 03-NOV-14:50 17.30 10.93 0.323853E+09 540.83 03-NOV-13:00 17.30 10.93
December 0.185653E+09 1200.33 20-DEC-14:00 10.00 5.91 0.295506E+09 429.90 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.329406E+11         0.440950E+10        
Minimum of Months 0.154231E+09 1167.22   6.93 1.88 0.277759E+09 421.95   6.93 1.88
Maximum of Months 0.652535E+10 10460.75   31.10 22.05 0.454636E+09 549.67   34.50 23.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.247023E+09 1304.21 19-JAN-10:10 7.80 4.25 0.194740E+09 298.31 19-JAN-10:20 7.80 4.36
February 0.361965E+09 1371.70 22-FEB-09:50 0.50 -3.2 0.178420E+09 309.70 22-FEB-10:09 0.87 -3.0
March 0.122081E+10 3632.33 29-MAR-09:30 6.15 3.19 0.238183E+09 347.87 29-MAR-09:50 6.52 3.33
April 0.214103E+10 6252.72 28-APR-08:50 15.82 8.80 0.231244E+09 347.89 26-APR-09:00 15.82 8.80
May 0.390013E+10 13644.17 29-MAY-08:52 26.10 16.72 0.267687E+09 348.42 30-MAY-09:00 27.80 17.82
June 0.498067E+10 12806.26 25-JUN-08:42 25.40 23.51 0.275249E+09 348.42 26-JUN-09:00 26.10 20.11
July 0.572091E+10 13765.45 02-JUL-08:42 25.40 21.60 0.257042E+09 348.97 14-JUL-09:00 30.60 21.74
August 0.632915E+10 12674.93 13-AUG-09:12 28.17 19.21 0.288048E+09 348.54 18-AUG-09:30 30.00 19.65
September 0.387742E+10 13570.24 04-SEP-08:42 23.72 18.57 0.251331E+09 348.41 06-SEP-09:39 26.33 19.45
October 0.270876E+10 5540.08 05-OCT-09:20 19.27 16.99 0.253266E+09 347.89 16-OCT-09:09 16.88 14.11
November 0.955145E+09 1999.53 02-NOV-09:40 11.83 6.09 0.209777E+09 347.87 03-NOV-09:00 13.30 8.39
December 0.370890E+09 1349.27 20-DEC-09:50 7.93 4.87 0.188549E+09 304.96 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.328139E+11         0.283354E+10        
Minimum of Months 0.247023E+09 1304.21   0.50 -3.2 0.178420E+09 298.31   0.87 -3.0
Maximum of Months 0.632915E+10 13765.45   28.17 23.51 0.288048E+09 348.97   30.60 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100619E+10 6182.74 19-JAN-13:25 9.40 3.94 0.336862E+09 549.49 30-JAN-14:20 2.80 -1.2
February 0.130285E+10 6609.01 02-FEB-13:50 5.78 -0.8 0.311836E+09 549.49 03-FEB-14:00 -1.7 -5.1
March 0.280719E+10 9111.67 03-MAR-13:25 14.70 8.33 0.392477E+09 549.50 23-MAR-13:00 5.00 1.08
April 0.337577E+10 10160.78 07-APR-12:30 26.15 15.90 0.362903E+09 549.83 07-APR-13:09 26.60 16.32
May 0.486488E+10 16740.78 29-MAY-11:32 28.53 18.30 0.420194E+09 550.10 30-MAY-13:50 29.50 17.11
June 0.649575E+10 12609.23 19-JUN-05:02 24.08 22.05 0.434301E+09 549.87 19-JUN-13:39 34.60 23.77
July 0.767274E+10 16695.77 04-JUL-12:13 28.13 19.53 0.405854E+09 550.05 10-JUL-13:00 32.80 20.89
August 0.935315E+10 16974.30 13-AUG-12:32 30.93 19.36 0.454811E+09 550.09 17-AUG-13:50 31.10 24.82
September 0.699450E+10 17318.50 04-SEP-12:42 26.10 18.22 0.398256E+09 557.72 28-SEP-13:09 22.98 13.55
October 0.642088E+10 16635.94 15-OCT-15:13 20.20 12.62 0.404577E+09 549.96 13-OCT-13:39 20.20 12.62
November 0.236895E+10 10899.84 02-NOV-13:10 15.68 8.29 0.361066E+09 549.57 02-NOV-13:50 16.02 8.62
December 0.129762E+10 6340.67 21-DEC-13:25 3.05 -1.7 0.331804E+09 549.49 14-DEC-14:09 3.05 -1.7
                     
Annual Sum or Average 0.539605E+11         0.461494E+10        
Minimum of Months 0.100619E+10 6182.74   3.05 -1.7 0.311836E+09 549.49   -1.7 -5.1
Maximum of Months 0.935315E+10 17318.50   30.93 22.05 0.454811E+09 557.72   34.60 24.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272727E+09 1619.26 19-JAN-15:50 8.40 3.05 0.196378E+09 321.65 19-JAN-15:00 8.30 2.94
February 0.359407E+09 2164.10 24-FEB-15:30 8.05 2.04 0.181095E+09 338.68 22-FEB-16:00 8.05 2.04
March 0.133618E+10 5495.08 29-MAR-16:00 7.20 4.88 0.230130E+09 347.84 01-MAR-14:00 7.20 4.88
April 0.227490E+10 10949.58 09-APR-17:12 15.73 13.56 0.218811E+09 347.85 26-APR-13:00 18.30 12.92
May 0.382816E+10 12026.20 14-MAY-16:03 13.30 9.05 0.260589E+09 347.88 15-MAY-13:00 17.80 11.36
June 0.522434E+10 15109.07 18-JUN-16:02 25.50 22.07 0.274015E+09 347.86 22-JUN-13:30 29.15 17.46
July 0.573120E+10 15121.48 02-JUL-16:02 24.90 20.78 0.256534E+09 347.87 11-JUL-13:50 28.72 17.86
August 0.636143E+10 14773.21 13-AUG-15:52 30.00 20.46 0.287200E+09 347.86 08-AUG-13:39 30.00 20.46
September 0.392286E+10 14551.77 10-SEP-16:02 23.22 12.85 0.247393E+09 347.86 11-SEP-13:09 20.60 12.01
October 0.294368E+10 10232.71 15-OCT-15:13 20.20 12.62 0.241700E+09 347.86 12-OCT-13:00 20.20 12.62
November 0.898986E+09 3622.98 03-NOV-15:30 16.10 10.65 0.204899E+09 347.85 08-NOV-14:00 13.30 11.09
December 0.312817E+09 1574.01 08-DEC-15:40 6.30 2.04 0.189938E+09 314.91 08-DEC-15:50 6.20 1.96
                     
Annual Sum or Average 0.334667E+11         0.278868E+10        
Minimum of Months 0.272727E+09 1574.01   6.30 2.04 0.181095E+09 314.91   6.20 1.96
Maximum of Months 0.636143E+10 15121.48   30.00 22.07 0.287200E+09 347.88   30.00 20.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248178E+09 1151.49 20-JAN-15:00 7.80 3.97 0.305772E+09 423.69 20-JAN-14:00 7.80 3.97
February 0.211442E+09 1161.13 24-FEB-14:10 9.22 3.12 0.278806E+09 425.88 24-FEB-14:20 9.03 2.95
March 0.102784E+10 1502.21 28-MAR-14:00 13.30 8.41 0.349383E+09 505.54 28-MAR-13:00 13.30 8.41
April 0.161890E+10 2317.43 10-APR-14:00 20.60 10.45 0.344961E+09 549.49 07-APR-13:20 20.60 10.45
May 0.277245E+10 4611.58 30-MAY-13:50 29.50 17.11 0.418124E+09 549.51 15-MAY-13:00 29.50 17.11
June 0.446181E+10 7611.72 26-JUN-06:03 21.97 17.81 0.434827E+09 549.50 05-JUN-09:09 21.97 17.81
July 0.557254E+10 7817.49 10-JUL-06:03 26.20 20.78 0.405425E+09 549.50 12-JUL-13:50 28.40 19.35
August 0.586251E+10 7036.93 14-AUG-06:03 23.48 21.76 0.454797E+09 549.50 08-AUG-13:30 23.48 21.76
September 0.392539E+10 6145.17 01-SEP-05:02 24.08 21.83 0.401057E+09 549.51 19-SEP-09:09 18.58 14.06
October 0.277202E+10 3883.70 05-OCT-14:00 23.30 18.86 0.405477E+09 549.51 16-OCT-09:09 16.88 14.11
November 0.137814E+10 1863.24 06-NOV-13:07 12.98 7.45 0.343914E+09 546.67 03-NOV-13:00 12.98 7.45
December 0.528013E+09 1250.36 20-DEC-14:00 10.00 5.91 0.299232E+09 445.94 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.303792E+11         0.444177E+10        
Minimum of Months 0.211442E+09 1151.49   7.80 3.12 0.278806E+09 423.69   7.80 2.95
Maximum of Months 0.586251E+10 7817.49   29.50 21.83 0.454797E+09 549.51   29.50 21.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.309833E+09 1094.94 27-JAN-10:10 4.50 1.48 0.196705E+09 300.40 27-JAN-10:20 4.60 1.51
February 0.392525E+09 1117.76 22-FEB-09:50 0.50 -3.2 0.180197E+09 305.08 22-FEB-10:20 1.13 -2.8
March 0.117899E+10 2342.90 29-MAR-09:30 6.15 3.19 0.239098E+09 347.87 29-MAR-09:09 6.15 3.19
April 0.178093E+10 4280.43 28-APR-09:10 16.28 8.96 0.233632E+09 347.88 26-APR-09:00 16.28 8.96
May 0.305626E+10 9317.74 29-MAY-08:52 26.10 16.72 0.268619E+09 348.17 30-MAY-09:00 27.80 17.82
June 0.417787E+10 11579.24 25-JUN-09:12 25.77 23.51 0.275743E+09 348.18 26-JUN-09:00 26.10 20.11
July 0.504328E+10 11366.36 02-JUL-09:11 25.77 21.71 0.257159E+09 348.54 14-JUL-09:00 30.60 21.74
August 0.594117E+10 9374.53 20-AUG-10:32 25.37 15.92 0.288430E+09 348.29 18-AUG-09:30 25.37 15.92
September 0.390252E+10 11580.06 10-SEP-09:12 20.57 13.59 0.254859E+09 348.09 06-SEP-09:30 20.57 13.59
October 0.294998E+10 5077.23 05-OCT-09:20 19.27 16.99 0.261916E+09 347.89 16-OCT-09:09 16.88 14.11
November 0.126683E+10 2384.94 03-NOV-09:30 13.05 8.24 0.227166E+09 347.87 01-NOV-09:09 13.05 8.24
December 0.632247E+09 1215.18 20-DEC-09:40 7.57 4.72 0.195610E+09 322.66 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.306324E+11         0.287913E+10        
Minimum of Months 0.309833E+09 1094.94   0.50 -3.2 0.180197E+09 300.40   1.13 -2.8
Maximum of Months 0.594117E+10 11580.06   26.10 23.51 0.288430E+09 348.54   30.60 21.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.429253E+09 1711.72 19-JAN-14:30 9.15 3.65 0.304034E+09 549.50 19-JAN-14:50 8.98 3.61
February 0.502282E+09 2551.24 25-FEB-13:10 2.88 -1.9 0.280360E+09 545.01 02-FEB-14:39 2.88 -1.9
March 0.132207E+10 6095.69 03-MAR-13:08 14.50 8.14 0.365017E+09 549.50 07-MAR-14:09 10.00 5.05
April 0.194318E+10 7124.65 07-APR-12:00 25.60 15.40 0.346134E+09 549.51 10-APR-13:09 20.10 10.10
May 0.303728E+10 11137.43 30-MAY-12:00 29.40 17.58 0.405532E+09 549.98 30-MAY-13:00 29.40 16.93
June 0.520617E+10 12767.65 19-JUN-12:00 36.70 24.28 0.432583E+09 631.17 19-JUN-12:09 36.42 24.23
July 0.726173E+10 12199.12 07-JUL-12:00 33.90 23.31 0.406147E+09 600.21 07-JUL-12:09 33.72 23.31
August 0.941506E+10 13623.84 13-AUG-13:12 31.30 19.70 0.456054E+09 605.24 18-AUG-12:09 32.88 20.21
September 0.675460E+10 14531.58 03-SEP-12:52 23.90 15.38 0.401256E+09 590.75 01-SEP-12:09 23.90 15.38
October 0.599953E+10 13850.81 22-OCT-13:02 22.20 16.91 0.410724E+09 565.96 04-OCT-13:20 22.20 16.91
November 0.191458E+10 10127.05 06-NOV-13:07 12.98 7.45 0.353503E+09 549.65 02-NOV-13:00 12.98 7.45
December 0.873523E+09 5361.29 17-DEC-14:37 12.20 5.44 0.313236E+09 549.51 18-DEC-14:09 7.52 2.81
                     
Annual Sum or Average 0.446593E+11         0.447458E+10        
Minimum of Months 0.429253E+09 1711.72   2.88 -1.9 0.280360E+09 545.01   2.88 -1.9
Maximum of Months 0.941506E+10 14531.58   36.70 24.28 0.456054E+09 631.17   36.42 24.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.304019E+09 1285.78 20-JAN-16:00 7.20 3.80 0.196891E+09 322.11 20-JAN-16:10 6.93 3.71
February 0.349754E+09 1356.44 22-FEB-16:30 3.85 -0.7 0.181014E+09 336.29 22-FEB-16:40 3.67 -0.7
March 0.122684E+10 3499.78 27-MAR-16:50 21.28 15.57 0.231993E+09 347.83 03-MAR-14:00 21.28 15.57
April 0.179086E+10 6429.68 09-APR-16:53 16.10 13.79 0.224378E+09 347.84 10-APR-13:09 20.10 10.10
May 0.286356E+10 7412.31 27-MAY-17:42 21.20 11.70 0.264218E+09 347.87 15-MAY-13:00 21.20 11.70
June 0.436716E+10 11865.52 25-JUN-16:32 25.77 22.57 0.275682E+09 347.85 05-JUN-09:09 25.77 22.57
July 0.502708E+10 11771.42 02-JUL-16:31 24.60 20.65 0.257025E+09 347.86 12-JUL-13:50 28.40 19.35
August 0.592457E+10 11528.78 13-AUG-15:52 30.00 20.46 0.288384E+09 347.86 08-AUG-13:30 30.00 20.46
September 0.382918E+10 12362.50 10-SEP-16:31 22.97 12.76 0.254082E+09 347.86 19-SEP-09:09 18.58 14.06
October 0.301805E+10 7373.85 15-OCT-15:13 20.20 12.62 0.259200E+09 347.86 16-OCT-09:09 16.88 14.11
November 0.118554E+10 3400.57 03-NOV-15:30 16.10 10.65 0.218925E+09 347.85 08-NOV-14:00 13.30 11.09
December 0.538609E+09 1295.53 08-DEC-15:40 6.30 2.04 0.193778E+09 324.16 08-DEC-15:50 6.20 1.96
                     
Annual Sum or Average 0.304252E+11         0.284557E+10        
Minimum of Months 0.304019E+09 1285.78   3.85 -0.7 0.181014E+09 322.11   3.67 -0.7
Maximum of Months 0.592457E+10 12362.50   30.00 22.57 0.288384E+09 347.87   30.00 22.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.297793E+09 1213.90 20-JAN-15:00 7.80 3.97 0.307310E+09 443.43 20-JAN-14:00 7.80 3.97
February 0.332543E+09 1241.24 24-FEB-15:50 7.88 1.88 0.281020E+09 447.91 24-FEB-14:00 7.88 1.88
March 0.135854E+10 1793.49 28-MAR-14:00 13.30 8.41 0.365893E+09 549.48 28-MAR-13:00 13.30 8.41
April 0.207789E+10 3699.78 07-APR-15:20 25.60 16.01 0.364120E+09 549.50 07-APR-13:09 25.60 16.01
May 0.366314E+10 8425.44 30-MAY-06:03 20.47 15.45 0.429162E+09 549.52 15-MAY-13:00 20.47 15.45
June 0.546427E+10 8783.54 26-JUN-05:12 20.97 17.23 0.435838E+09 549.71 19-JUN-13:30 20.97 17.23
July 0.623703E+10 9049.59 09-JUL-14:41 27.95 24.21 0.406029E+09 549.68 10-JUL-13:50 32.70 20.82
August 0.628569E+10 8613.52 14-AUG-06:03 23.48 21.76 0.455158E+09 549.51 08-AUG-13:30 23.48 21.76
September 0.402048E+10 8447.07 01-SEP-05:02 24.08 21.83 0.400388E+09 549.51 19-SEP-09:09 18.58 14.06
October 0.276672E+10 4141.88 05-OCT-14:00 23.30 18.86 0.402644E+09 549.51 16-OCT-09:09 16.88 14.11
November 0.122458E+10 1919.92 03-NOV-14:00 17.80 10.67 0.339298E+09 549.48 03-NOV-13:09 17.80 10.67
December 0.488957E+09 1265.19 20-DEC-14:00 10.00 5.91 0.299204E+09 455.26 20-DEC-14:09 9.72 5.77
                     
Annual Sum or Average 0.342176E+11         0.448606E+10        
Minimum of Months 0.297793E+09 1213.90   7.80 1.88 0.281020E+09 443.43   7.80 1.88
Maximum of Months 0.628569E+10 9049.59   27.95 24.21 0.455158E+09 549.71   32.70 21.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361652E+09 1381.12 19-JAN-10:00 7.80 4.14 0.144788E+09 308.84 19-JAN-09:00 7.80 4.14
February 0.503418E+09 1478.27 22-FEB-09:40 0.40 -3.3 0.133677E+09 326.18 22-FEB-09:50 0.50 -3.2
March 0.151204E+10 4332.67 29-MAR-09:00 5.60 2.98 0.178278E+09 338.72 23-MAR-10:20 5.60 2.98
April 0.234296E+10 6631.85 28-APR-08:30 15.25 8.69 0.172757E+09 338.73 26-APR-10:09 15.25 8.69
May 0.386963E+10 13628.67 28-MAY-08:22 20.00 12.65 0.199456E+09 339.33 30-MAY-07:19 23.53 16.02
June 0.479038E+10 14190.10 25-JUN-08:32 25.20 23.38 0.203521E+09 341.29 26-JUN-07:19 23.50 18.22
July 0.542883E+10 14565.82 09-JUL-09:21 29.15 25.29 0.190587E+09 342.93 17-JUL-07:19 24.63 20.35
August 0.604288E+10 13315.21 27-AUG-09:52 26.10 21.81 0.212855E+09 339.50 22-AUG-07:19 26.10 21.81
September 0.389906E+10 14089.13 10-SEP-08:32 19.63 13.49 0.186843E+09 339.03 06-SEP-08:00 19.63 13.49
October 0.293050E+10 6787.84 15-OCT-09:43 18.12 12.80 0.189497E+09 338.73 16-OCT-08:39 15.77 13.14
November 0.122796E+10 2792.37 02-NOV-09:00 11.10 5.86 0.160125E+09 338.72 03-NOV-10:09 13.58 8.52
December 0.586660E+09 1472.98 20-DEC-09:40 7.57 4.72 0.142063E+09 324.45 20-DEC-09:50 7.93 4.87
                     
Annual Sum or Average 0.334960E+11         0.211445E+10        
Minimum of Months 0.361652E+09 1381.12   0.40 -3.3 0.133677E+09 308.84   0.50 -3.2
Maximum of Months 0.604288E+10 14565.82   29.15 25.29 0.212855E+09 342.93   26.10 21.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131109E+10 6503.78 19-JAN-13:25 9.40 3.94 0.344222E+09 549.50 30-JAN-14:39 2.80 -1.1
February 0.161562E+10 7065.14 02-FEB-13:40 5.97 -0.5 0.321293E+09 549.49 03-FEB-14:00 -1.7 -5.1
March 0.326004E+10 9095.95 29-MAR-13:00 7.80 5.26 0.405295E+09 549.52 29-MAR-13:20 7.80 5.34
April 0.357739E+10 9606.40 07-APR-12:30 26.15 15.90 0.375095E+09 549.90 07-APR-13:30 26.40 16.17
May 0.478853E+10 15289.57 29-MAY-12:32 27.77 17.46 0.428684E+09 550.24 30-MAY-13:00 29.40 16.93
June 0.627785E+10 12869.61 25-JUN-14:32 26.70 22.80 0.435653E+09 549.88 19-JUN-13:30 26.70 22.80
July 0.731166E+10 15186.35 09-JUL-11:22 29.70 25.23 0.406166E+09 550.09 10-JUL-13:50 32.70 20.82
August 0.900312E+10 15832.26 27-AUG-12:32 27.97 22.65 0.455578E+09 555.32 30-AUG-13:09 27.48 15.59
September 0.704319E+10 16591.14 10-SEP-13:12 24.07 14.06 0.402270E+09 572.30 28-SEP-13:09 22.98 13.55
October 0.686635E+10 16227.42 15-OCT-12:22 20.30 13.25 0.413104E+09 563.98 04-OCT-13:09 20.30 13.25
November 0.289424E+10 11253.47 02-NOV-12:50 15.50 8.17 0.377399E+09 549.68 02-NOV-13:00 16.10 8.71
December 0.176463E+10 9368.42 17-DEC-12:53 12.20 4.95 0.344372E+09 549.49 18-DEC-14:00 6.10 2.61
                     
Annual Sum or Average 0.557137E+11         0.470913E+10        
Minimum of Months 0.131109E+10 6503.78   5.97 -0.5 0.321293E+09 549.49   -1.7 -5.1
Maximum of Months 0.900312E+10 16591.14   29.70 25.23 0.455578E+09 572.30   32.70 22.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.385306E+09 1573.23 20-JAN-16:00 7.20 3.80 0.198474E+09 334.69 20-JAN-16:10 6.93 3.71
February 0.489200E+09 2451.96 24-FEB-15:30 8.05 2.04 0.183531E+09 344.62 02-FEB-14:00 8.05 2.04
March 0.164905E+10 5538.58 29-MAR-16:00 7.20 4.88 0.235870E+09 347.84 28-MAR-13:00 7.20 4.88
April 0.242855E+10 10448.23 09-APR-17:12 15.73 13.56 0.226551E+09 347.85 26-APR-13:00 18.30 12.92
May 0.375114E+10 13405.83 28-MAY-15:02 26.23 15.49 0.267132E+09 347.87 15-MAY-13:00 26.23 15.49
June 0.505469E+10 14429.64 25-JUN-16:32 25.77 22.57 0.275369E+09 347.86 23-JUN-09:09 25.77 22.57
July 0.547012E+10 14065.07 04-JUL-16:41 25.18 18.20 0.256888E+09 347.86 17-JUL-09:20 27.97 21.33
August 0.612149E+10 13598.69 13-AUG-15:52 30.00 20.46 0.287996E+09 347.86 08-AUG-13:30 30.00 20.46
September 0.391220E+10 14743.74 10-SEP-15:51 23.30 12.88 0.251675E+09 347.86 15-SEP-13:00 22.80 15.50
October 0.311583E+10 10636.77 15-OCT-15:43 19.60 12.30 0.251401E+09 347.85 13-OCT-13:39 19.60 12.30
November 0.118571E+10 3813.80 03-NOV-15:30 16.10 10.65 0.213081E+09 347.85 08-NOV-14:00 13.30 11.09
December 0.531148E+09 1545.70 08-DEC-15:40 6.30 2.04 0.193258E+09 330.49 21-DEC-14:00 3.30 -1.8
                     
Annual Sum or Average 0.340944E+11         0.284123E+10        
Minimum of Months 0.385306E+09 1545.70   6.30 2.04 0.183531E+09 330.49   3.30 -1.8
Maximum of Months 0.612149E+10 14743.74   30.00 22.57 0.287996E+09 347.87   30.00 22.57



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.184810E+09 9047.20 02-JAN-05:02 -12.1
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.184810E+09      
Minimum of Months 0.00 0.00   -12.1
Maximum of Months 0.184810E+09 9047.20   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.482839E+10 14719.57 02-JAN-06:10 -11.7
February 0.391017E+10 14061.95 13-FEB-06:09 -9.4
March 0.177617E+10 10729.83 20-MAR-06:12 -0.6
April 0.820206E+09 7793.31 03-APR-06:02 2.38
May 0.194840E+09 3624.58 02-MAY-05:03 8.40
June 41966009.97 5093.43 19-JUN-05:02 24.08
July 18233109.23 4567.04 25-JUL-05:02 23.90
August 36661337.80 3839.40 01-AUG-05:03 23.90
September 0.137414E+09 3567.76 01-SEP-05:02 24.08
October 0.496304E+09 4308.92 19-OCT-05:03 5.37
November 0.187197E+10 11620.87 24-NOV-06:07 -4.4
December 0.333611E+10 11107.71 11-DEC-06:09 1.70
         
Annual Sum or Average 0.174684E+11      
Minimum of Months 18233109.23 3567.76   -11.7
Maximum of Months 0.482839E+10 14719.57   24.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.247497E+10 9742.75 02-JAN-08:15 -10.9
February 0.181443E+10 6894.72 06-FEB-07:20 -13.1
March 0.102163E+10 2758.71 01-MAR-11:30 13.90
April 0.364716E+09 3371.87 16-APR-12:13 20.77
May 71086189.07 3059.63 28-MAY-15:02 26.23
June 14834552.35 2628.50 19-JUN-05:02 24.08
July 21995419.22 3133.96 09-JUL-14:41 27.95
August 17485814.04 2690.14 13-AUG-10:32 29.63
September 23993713.80 3936.57 10-SEP-09:52 21.70
October 0.119290E+09 4399.77 29-OCT-13:13 12.07
November 0.975964E+09 4245.36 24-NOV-07:12 -4.2
December 0.152575E+10 5230.64 17-DEC-12:53 12.20
         
Annual Sum or Average 0.844615E+10      
Minimum of Months 14834552.35 2628.50   -13.1
Maximum of Months 0.247497E+10 9742.75   29.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190591E+10 8086.18 02-JAN-12:01 -7.0
February 0.122907E+10 3834.10 06-FEB-09:00 -12.2
March 0.553840E+09 2478.87 14-MAR-07:10 -1.4
April 0.136566E+09 2050.42 04-APR-07:08 4.87
May 20849746.16 2134.75 14-MAY-14:20 14.23
June 18980430.14 3122.17 19-JUN-05:02 24.08
July 25215891.23 3282.36 18-JUL-04:02 24.40
August 24774541.83 3697.54 22-AUG-04:02 25.92
September 29783994.35 3676.18 01-SEP-05:02 24.08
October 47523025.59 2849.74 29-OCT-10:13 10.20
November 0.500577E+09 2738.96 06-NOV-06:12 5.00
December 0.104148E+10 3388.85 03-DEC-12:53 8.30
         
Annual Sum or Average 0.553457E+10      
Minimum of Months 18980430.14 2050.42   -12.2
Maximum of Months 0.190591E+10 8086.18   25.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.655807E+09 16183.54 02-JAN-05:02 -12.1
February 0.133131E+09 12720.87 06-FEB-06:02 -12.9
March 5985400.52 10680.26 20-MAR-06:01 -0.6
April 746233.95 9949.79 03-APR-06:01 2.38
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 16409237.92 11022.06 24-NOV-07:01 -4.3
December 37523714.12 11287.25 26-DEC-06:11 6.30
         
Annual Sum or Average 0.849602E+09      
Minimum of Months 0.00 0.00   -12.9
Maximum of Months 0.655807E+09 16183.54   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.212187E+10 24010.52 02-JAN-04:42 -12.1
February 0.125374E+10 22582.26 06-FEB-05:11 -13.1
March 0.215212E+09 19538.25 20-MAR-05:01 -1.5
April 32059116.60 18043.67 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.390536E+09 20147.83 24-NOV-06:01 -4.4
December 0.656043E+09 20787.51 11-DEC-05:51 1.70
         
Annual Sum or Average 0.466946E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.212187E+10 24010.52   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.362082E+10 9860.33 02-JAN-00:42 -11.0
February 0.295658E+10 9576.31 05-FEB-23:12 -12.6
March 0.788562E+09 8535.95 20-MAR-04:02 -0.8
April 0.163255E+09 8171.15 03-APR-05:11 2.60
May 1812635.01 6796.46 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 23415652.12 6911.09 30-OCT-06:02 10.50
November 0.934409E+09 9012.48 24-NOV-05:01 -4.0
December 0.212537E+10 9275.34 31-DEC-23:13 -8.0
         
Annual Sum or Average 0.106142E+11      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.362082E+10 9860.33   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.198016E+10 8430.17 02-JAN-00:42 -11.0
February 0.145081E+10 8052.74 05-FEB-23:12 -12.6
March 0.367580E+09 7072.74 20-MAR-04:02 -0.8
April 82300133.89 6635.96 03-APR-05:11 2.60
May 611974.72 2859.33 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 13271545.67 5283.74 30-OCT-06:02 10.50
November 0.474786E+09 7557.13 24-NOV-05:01 -4.0
December 0.113018E+10 7734.12 31-DEC-23:13 -8.0
         
Annual Sum or Average 0.549970E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.198016E+10 8430.17   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240712E+10 11441.50 02-JAN-00:42 -11.0
February 0.175392E+10 10947.94 06-FEB-05:11 -13.1
March 0.516452E+09 9554.55 20-MAR-04:02 -0.8
April 0.142264E+09 9125.72 03-APR-05:11 2.60
May 2727168.04 7461.42 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 12405283.50 7501.52 28-OCT-06:03 3.90
November 0.542128E+09 10297.32 24-NOV-05:01 -4.0
December 0.134987E+10 10239.45 11-DEC-05:51 1.70
         
Annual Sum or Average 0.672688E+10      
Minimum of Months 0.00 0.00   -13.1
Maximum of Months 0.240712E+10 11441.50   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.220740E+10 8825.48 02-JAN-00:42 -11.0
February 0.174131E+10 8429.47 05-FEB-23:12 -12.6
March 0.437713E+09 7209.41 13-MAR-04:02 -0.1
April 0.105121E+09 6760.13 03-APR-05:11 2.60
May 2338512.80 5221.53 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 15590196.76 5415.78 30-OCT-06:02 10.50
November 0.584044E+09 7861.19 24-NOV-05:01 -4.0
December 0.129120E+10 7780.00 31-DEC-23:13 -8.0
         
Annual Sum or Average 0.638472E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.220740E+10 8825.48   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215145E+10 7497.86 01-JAN-23:22 -10.3
February 0.167270E+10 6977.34 06-FEB-05:01 -13.2
March 0.326359E+09 6047.65 20-MAR-05:01 -1.5
April 40093910.79 5825.09 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.154181E+09 5999.07 24-NOV-06:01 -4.4
December 0.520199E+09 5952.09 11-DEC-06:01 1.70
         
Annual Sum or Average 0.486498E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.215145E+10 7497.86   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108937E+10 6448.44 02-JAN-00:42 -11.0
February 0.650157E+09 5920.22 06-FEB-05:01 -13.2
March 0.102841E+09 4878.35 20-MAR-05:01 -1.5
April 13375782.23 4571.71 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 53760458.66 4710.86 24-NOV-06:01 -4.4
December 0.244191E+09 4796.34 11-DEC-06:01 1.70
         
Annual Sum or Average 0.215370E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.108937E+10 6448.44   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.354132E+10 10998.97 02-JAN-07:50 -11.2
February 0.284654E+10 10341.01 06-FEB-07:10 -13.2
March 0.176204E+10 8639.42 23-MAR-06:10 -4.7
April 0.865483E+09 7814.98 03-APR-06:10 2.38
May 0.268391E+09 6435.66 01-MAY-06:10 7.67
June 171186.71 877.80 02-JUN-06:08 13.98
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 2956655.57 4565.78 20-SEP-06:07 12.48
October 0.164714E+09 6213.08 27-OCT-06:10 5.68
November 0.112438E+10 8495.47 24-NOV-07:10 -4.3
December 0.212753E+10 8568.67 15-DEC-07:10 -3.6
         
Annual Sum or Average 0.127035E+11      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.354132E+10 10998.97   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122832E+10 6607.59 02-JAN-00:42 -11.0
February 0.818382E+09 6036.56 06-FEB-05:01 -13.2
March 0.105400E+09 4828.00 01-MAR-06:11 4.07
April 17936776.26 4522.51 03-APR-05:11 2.60
May 38766.27 258.44 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 78035404.06 4774.24 24-NOV-06:01 -4.4
December 0.280684E+09 4870.86 11-DEC-06:01 1.70
         
Annual Sum or Average 0.252880E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.122832E+10 6607.59   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.199293E+10 8074.42 01-JAN-23:22 -10.3
February 0.139578E+10 7501.40 13-FEB-05:01 -9.0
March 0.208944E+09 6457.93 13-MAR-05:01 -0.6
April 24355957.16 6167.19 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 133644.56 890.96 28-OCT-06:03 3.90
November 0.294794E+09 6844.32 24-NOV-05:01 -4.0
December 0.740924E+09 6710.92 11-DEC-06:01 1.70
         
Annual Sum or Average 0.465786E+10      
Minimum of Months 0.00 0.00   -10.3
Maximum of Months 0.199293E+10 8074.42   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110403E+10 7216.26 01-JAN-23:22 -10.3
February 0.667207E+09 6524.16 13-FEB-05:01 -9.0
March 0.101344E+09 5350.94 20-MAR-05:01 -1.5
April 12041234.11 4993.37 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 553174.97 2113.59 28-OCT-06:03 3.90
November 0.155703E+09 5778.46 24-NOV-05:01 -4.0
December 0.420478E+09 5686.68 11-DEC-06:01 1.70
         
Annual Sum or Average 0.246136E+10      
Minimum of Months 0.00 0.00   -10.3
Maximum of Months 0.110403E+10 7216.26   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122534E+10 9454.89 02-JAN-00:42 -11.0
February 0.705844E+09 8702.71 06-FEB-05:01 -13.2
March 0.124439E+09 7173.03 13-MAR-05:01 -0.6
April 19729682.26 6769.34 03-APR-05:11 2.60
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.139061E+09 7496.89 24-NOV-06:01 -4.4
December 0.435818E+09 7645.70 11-DEC-06:01 1.70
         
Annual Sum or Average 0.265023E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.122534E+10 9454.89   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120750E+10 7360.75 01-JAN-23:22 -10.3
February 0.801682E+09 6626.88 06-FEB-05:01 -13.2
March 0.116232E+09 5398.61 13-MAR-05:01 -0.6
April 17258602.71 4951.36 03-APR-05:11 2.60
May 31724.53 211.50 01-MAY-06:03 7.67
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:10 23.90
September 0.00 0.00 01-SEP-00:10 23.43
October 434225.73 1906.68 28-OCT-06:03 3.90
November 0.183806E+09 5830.78 24-NOV-05:01 -4.0
December 0.455840E+09 5753.38 11-DEC-06:01 1.70
         
Annual Sum or Average 0.278279E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.120750E+10 7360.75   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.250423E+12    
Minimum of Months 0.544142E+10 6443.98   0.191215E+11 14019.75  
Maximum of Months 0.648083E+10 6443.98   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.861293E+09 1358.45 02-JAN-16:10 0.204758E+10 1435.25 02-JAN-08:09
February 0.718912E+09 1358.45 01-FEB-16:49 0.185366E+10 1435.25 01-FEB-08:09
March 0.788618E+09 1184.79 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.665518E+09 774.31 18-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.700073E+09 774.31 04-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.686128E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.645027E+09 711.15 05-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.730074E+09 774.31 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.681982E+09 947.97 22-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.741925E+09 1184.79 06-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.817781E+09 1358.45 06-NOV-16:19 0.200273E+10 1435.25 01-NOV-07:10
December 0.855579E+09 1358.45 01-DEC-16:10 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.889291E+10     0.243325E+11    
Minimum of Months 0.645027E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.861293E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.533841E+09 860.01 02-JAN-16:10 0.129621E+10 908.57 02-JAN-08:09
February 0.447525E+09 860.01 01-FEB-16:40 0.117344E+10 908.57 01-FEB-08:09
March 0.497172E+09 750.07 02-MAR-16:40 0.134804E+10 908.57 01-MAR-08:09
April 0.422223E+09 450.21 05-APR-15:30 0.125169E+10 908.57 03-APR-07:10
May 0.446586E+09 490.21 19-MAY-15:50 0.132213E+10 908.57 01-MAY-07:10
June 0.438836E+09 450.21 16-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.411705E+09 450.21 24-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.464421E+09 450.21 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.430424E+09 490.21 22-SEP-15:39 0.125111E+10 908.57 01-SEP-07:10
October 0.466644E+09 750.07 06-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.510330E+09 860.01 06-NOV-16:19 0.126781E+10 908.57 01-NOV-07:10
December 0.523472E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.559318E+10     0.154036E+11    
Minimum of Months 0.411705E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.533841E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.814181E+09 1358.45 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.686012E+09 1358.45 01-FEB-16:49 0.185364E+10 1435.24 01-FEB-08:09
March 0.776147E+09 947.97 02-MAR-16:30 0.212945E+10 1435.24 01-MAR-08:09
April 0.666087E+09 774.31 18-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.704048E+09 774.31 04-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.692138E+09 774.31 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.650038E+09 711.15 05-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.733674E+09 774.31 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.677097E+09 947.97 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.724484E+09 1184.79 06-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.783316E+09 1358.45 06-NOV-16:30 0.200271E+10 1435.24 01-NOV-07:10
December 0.792354E+09 1358.45 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.869958E+10     0.243324E+11    
Minimum of Months 0.650038E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.814181E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.525304E+09 859.95 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.440532E+09 859.95 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.492411E+09 750.02 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.421696E+09 600.10 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.442276E+09 490.17 04-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.435217E+09 490.17 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.409363E+09 490.17 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.462311E+09 600.10 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.430025E+09 600.10 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.461490E+09 750.02 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.501660E+09 859.95 06-NOV-16:40 0.126780E+10 908.57 01-NOV-07:10
December 0.515862E+09 859.95 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.553815E+10     0.154035E+11    
Minimum of Months 0.409363E+09 490.17   0.117344E+10 908.57  
Maximum of Months 0.525304E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.855795E+09 1358.45 02-JAN-16:10 0.204758E+10 1435.25 02-JAN-08:09
February 0.714932E+09 1358.45 01-FEB-16:49 0.185366E+10 1435.25 01-FEB-08:09
March 0.786159E+09 1184.79 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.664468E+09 774.31 18-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.699354E+09 774.31 08-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.685265E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.644089E+09 711.15 05-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.729524E+09 774.31 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.679970E+09 947.97 26-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.739508E+09 1184.79 06-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.813095E+09 1358.45 06-NOV-16:19 0.200273E+10 1435.25 01-NOV-07:10
December 0.849423E+09 1358.45 01-DEC-16:10 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.886158E+10     0.243325E+11    
Minimum of Months 0.644089E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.855795E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.531815E+09 860.01 02-JAN-16:10 0.129621E+10 908.57 02-JAN-08:09
February 0.445928E+09 860.01 01-FEB-16:40 0.117344E+10 908.57 01-FEB-08:09
March 0.495813E+09 750.07 02-MAR-16:49 0.134804E+10 908.57 01-MAR-08:09
April 0.421406E+09 450.21 05-APR-15:39 0.125169E+10 908.57 03-APR-07:10
May 0.446103E+09 490.21 19-MAY-15:50 0.132213E+10 908.57 01-MAY-07:10
June 0.438314E+09 450.21 29-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.411209E+09 410.22 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.464108E+09 450.21 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.429663E+09 490.21 22-SEP-15:50 0.125111E+10 908.57 01-SEP-07:10
October 0.465404E+09 750.07 06-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.509030E+09 860.01 06-NOV-16:19 0.126781E+10 908.57 01-NOV-07:10
December 0.520378E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.557917E+10     0.154036E+11    
Minimum of Months 0.411209E+09 410.22   0.117344E+10 908.57  
Maximum of Months 0.531815E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.811644E+09 1358.45 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.685228E+09 1358.45 01-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.774833E+09 947.97 02-MAR-16:40 0.212945E+10 1435.24 01-MAR-08:09
April 0.664987E+09 774.31 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.703179E+09 774.31 08-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.690949E+09 711.15 16-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.649268E+09 711.15 05-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.732861E+09 774.31 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.675814E+09 947.97 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.723481E+09 1184.79 06-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.781889E+09 1358.45 06-NOV-16:40 0.200271E+10 1435.24 01-NOV-07:10
December 0.789341E+09 1358.45 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.868347E+10     0.243324E+11    
Minimum of Months 0.649268E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.811644E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.522475E+09 859.95 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.438975E+09 859.95 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.491114E+09 750.02 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.421099E+09 600.10 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.441772E+09 490.17 04-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.434646E+09 490.17 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.408784E+09 490.17 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.461693E+09 600.10 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.429196E+09 600.10 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.460716E+09 750.02 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.499806E+09 859.95 06-NOV-16:40 0.126780E+10 908.57 01-NOV-07:10
December 0.513773E+09 859.95 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.552405E+10     0.154035E+11    
Minimum of Months 0.408784E+09 490.17   0.117344E+10 908.57  
Maximum of Months 0.522475E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.861293E+09 1358.45 02-JAN-16:10 0.204758E+10 1435.25 02-JAN-08:09
February 0.718912E+09 1358.45 01-FEB-16:49 0.185366E+10 1435.25 01-FEB-08:09
March 0.788618E+09 1184.79 02-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.665518E+09 774.31 18-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.700073E+09 774.31 04-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.686128E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.645025E+09 711.15 05-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.730074E+09 774.31 16-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.681982E+09 947.97 22-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.741925E+09 1184.79 06-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.817781E+09 1358.45 06-NOV-16:19 0.200273E+10 1435.25 01-NOV-07:10
December 0.855579E+09 1358.45 01-DEC-16:10 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.889291E+10     0.243325E+11    
Minimum of Months 0.645025E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.861293E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.533841E+09 860.01 02-JAN-16:10 0.129621E+10 908.57 02-JAN-08:09
February 0.447525E+09 860.01 01-FEB-16:40 0.117344E+10 908.57 01-FEB-08:09
March 0.497172E+09 750.07 02-MAR-16:40 0.134804E+10 908.57 01-MAR-08:09
April 0.422223E+09 450.21 05-APR-15:30 0.125169E+10 908.57 03-APR-07:10
May 0.446586E+09 490.21 19-MAY-15:50 0.132213E+10 908.57 01-MAY-07:10
June 0.438836E+09 450.21 16-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.411705E+09 450.21 24-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.464454E+09 450.21 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.430424E+09 490.21 22-SEP-15:39 0.125111E+10 908.57 01-SEP-07:10
October 0.466644E+09 750.07 06-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.510330E+09 860.01 06-NOV-16:19 0.126781E+10 908.57 01-NOV-07:10
December 0.523472E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.559321E+10     0.154036E+11    
Minimum of Months 0.411705E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.533841E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.814181E+09 1358.45 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.686012E+09 1358.45 01-FEB-16:49 0.185364E+10 1435.24 01-FEB-08:09
March 0.776147E+09 947.97 02-MAR-16:30 0.212945E+10 1435.24 01-MAR-08:09
April 0.666087E+09 774.31 18-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.704048E+09 774.31 04-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.692138E+09 774.31 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.650038E+09 711.15 05-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.733674E+09 774.31 16-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.677097E+09 947.97 27-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.724484E+09 1184.79 06-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.783316E+09 1358.45 06-NOV-16:30 0.200271E+10 1435.24 01-NOV-07:10
December 0.792354E+09 1358.45 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.869958E+10     0.243324E+11    
Minimum of Months 0.650038E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.814181E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.525304E+09 859.95 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.440532E+09 859.95 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.492403E+09 750.02 16-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.421696E+09 600.10 14-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.442276E+09 490.17 04-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.435217E+09 490.17 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.409363E+09 490.17 24-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.462311E+09 600.10 16-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.430025E+09 600.10 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.461490E+09 750.02 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.501660E+09 859.95 06-NOV-16:40 0.126780E+10 908.57 01-NOV-07:10
December 0.515861E+09 859.95 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.553814E+10     0.154035E+11    
Minimum of Months 0.409363E+09 490.17   0.117344E+10 908.57  
Maximum of Months 0.525304E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.861293E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.726594E+09
February 0.901968E+09 0.718912E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.646943E+09
March 0.107774E+10 0.788618E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.525397E+09
April 0.956342E+09 0.665518E+09 0.197726E+10 0.00 0.00 0.00 0.00 285397.44 0.349657E+09
May 0.103597E+10 0.700073E+09 0.208852E+10 0.00 0.00 0.00 0.00 1387799.95 0.213606E+09
June 0.103308E+10 0.686128E+09 0.205071E+10 0.00 0.00 0.00 0.00 9332537.91 0.114060E+09
July 0.959235E+09 0.645027E+09 0.201461E+10 0.00 0.00 0.00 0.00 21825688.84 41554816.37
August 0.107774E+10 0.730074E+09 0.212947E+10 0.00 0.00 0.00 0.00 26569370.82 51311209.22
September 0.956342E+09 0.681982E+09 0.197634E+10 0.00 0.00 0.00 0.00 3290775.75 0.115530E+09
October 0.994195E+09 0.741925E+09 0.204804E+10 0.00 0.00 0.00 0.00 48860.20 0.282889E+09
November 0.984487E+09 0.817781E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.507429E+09
December 0.959235E+09 0.855579E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.607971E+09
                   
Annual Sum or Average 0.119305E+11 0.889291E+10 0.243325E+11 0.00 0.00 0.00 0.00 62740430.91 0.418294E+10
Minimum of Months 0.901968E+09 0.645027E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 41554816.37
Maximum of Months 0.107774E+10 0.861293E+09 0.212947E+10 0.00 0.00 0.00 0.00 26569370.82 0.726594E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.533841E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.484839E+09
February 0.571020E+09 0.447525E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.436066E+09
March 0.682301E+09 0.497172E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.355114E+09
April 0.605444E+09 0.422223E+09 0.125169E+10 0.00 0.00 0.00 0.00 188204.38 0.240984E+09
May 0.655854E+09 0.446586E+09 0.132213E+10 0.00 0.00 0.00 0.00 721733.80 0.144589E+09
June 0.654023E+09 0.438836E+09 0.129819E+10 0.00 0.00 0.00 0.00 6159761.96 76240583.52
July 0.607275E+09 0.411705E+09 0.127534E+10 0.00 0.00 0.00 0.00 14489932.44 27799113.55
August 0.682301E+09 0.464421E+09 0.134804E+10 0.00 0.00 0.00 0.00 17293016.26 35225785.34
September 0.605444E+09 0.430424E+09 0.125111E+10 0.00 0.00 0.00 0.00 2170972.05 80003725.59
October 0.629407E+09 0.466644E+09 0.129650E+10 0.00 0.00 0.00 0.00 32572.28 0.194122E+09
November 0.623262E+09 0.510330E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.342926E+09
December 0.607275E+09 0.523472E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.407758E+09
                   
Annual Sum or Average 0.755301E+10 0.559318E+10 0.154036E+11 0.00 0.00 0.00 0.00 41056193.17 0.282567E+10
Minimum of Months 0.571020E+09 0.411705E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 27799113.55
Maximum of Months 0.682301E+09 0.533841E+09 0.134804E+10 0.00 0.00 0.00 0.00 17293016.26 0.484839E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.814181E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.746989E+09
February 0.901968E+09 0.686012E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.680349E+09
March 0.107774E+10 0.776147E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.551008E+09
April 0.956342E+09 0.666087E+09 0.197725E+10 0.00 0.00 0.00 0.00 281651.44 0.365707E+09
May 0.103597E+10 0.704048E+09 0.208851E+10 0.00 0.00 0.00 0.00 1119159.56 0.216177E+09
June 0.103308E+10 0.692138E+09 0.205070E+10 0.00 0.00 0.00 0.00 9111735.74 0.114038E+09
July 0.959235E+09 0.650038E+09 0.201460E+10 0.00 0.00 0.00 0.00 21472444.93 42230150.43
August 0.107774E+10 0.733674E+09 0.212945E+10 0.00 0.00 0.00 0.00 25605795.25 53830283.17
September 0.956342E+09 0.677097E+09 0.197632E+10 0.00 0.00 0.00 0.00 3224030.83 0.125097E+09
October 0.994195E+09 0.724484E+09 0.204803E+10 0.00 0.00 0.00 0.00 48643.85 0.312836E+09
November 0.984487E+09 0.783316E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.536860E+09
December 0.959235E+09 0.792354E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.640617E+09
                   
Annual Sum or Average 0.119305E+11 0.869958E+10 0.243324E+11 0.00 0.00 0.00 0.00 60863461.59 0.438574E+10
Minimum of Months 0.901968E+09 0.650038E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 42230150.43
Maximum of Months 0.107774E+10 0.814181E+09 0.212945E+10 0.00 0.00 0.00 0.00 25605795.25 0.746989E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.525304E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.486936E+09
February 0.570983E+09 0.440532E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.436908E+09
March 0.682256E+09 0.492411E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.360242E+09
April 0.605404E+09 0.421696E+09 0.125169E+10 0.00 0.00 0.00 0.00 199050.73 0.240666E+09
May 0.655811E+09 0.442276E+09 0.132212E+10 0.00 0.00 0.00 0.00 1050030.57 0.145372E+09
June 0.653980E+09 0.435217E+09 0.129818E+10 0.00 0.00 0.00 0.00 6355729.43 79329581.22
July 0.607235E+09 0.409363E+09 0.127533E+10 0.00 0.00 0.00 0.00 14950535.34 30586196.89
August 0.682256E+09 0.462311E+09 0.134804E+10 0.00 0.00 0.00 0.00 17561106.34 36800178.54
September 0.605404E+09 0.430025E+09 0.125110E+10 0.00 0.00 0.00 0.00 2259600.64 79842154.90
October 0.629366E+09 0.461490E+09 0.129649E+10 0.00 0.00 0.00 0.00 32591.40 0.195634E+09
November 0.623221E+09 0.501660E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.339520E+09
December 0.607235E+09 0.515862E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.409179E+09
                   
Annual Sum or Average 0.755252E+10 0.553815E+10 0.154035E+11 0.00 0.00 0.00 0.00 42408644.45 0.284102E+10
Minimum of Months 0.570983E+09 0.409363E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 30586196.89
Maximum of Months 0.682256E+09 0.525304E+09 0.134804E+10 0.00 0.00 0.00 0.00 17561106.34 0.486936E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.855795E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.409322E+09
February 0.901968E+09 0.714932E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.362166E+09
March 0.107774E+10 0.786159E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.289978E+09
April 0.956342E+09 0.664468E+09 0.197726E+10 0.00 0.00 0.00 0.00 190853.44 0.190770E+09
May 0.103597E+10 0.699354E+09 0.208852E+10 0.00 0.00 0.00 0.00 1194609.54 0.111574E+09
June 0.103308E+10 0.685265E+09 0.205071E+10 0.00 0.00 0.00 0.00 5692511.49 58690757.59
July 0.959235E+09 0.644089E+09 0.201461E+10 0.00 0.00 0.00 0.00 13294895.62 19721001.24
August 0.107774E+10 0.729524E+09 0.212947E+10 0.00 0.00 0.00 0.00 15063995.11 26640383.03
September 0.956342E+09 0.679970E+09 0.197634E+10 0.00 0.00 0.00 0.00 1843457.22 65891264.96
October 0.994195E+09 0.739508E+09 0.204804E+10 0.00 0.00 0.00 0.00 29314.42 0.167186E+09
November 0.984487E+09 0.813095E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.304452E+09
December 0.959235E+09 0.849423E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.355873E+09
                   
Annual Sum or Average 0.119305E+11 0.886158E+10 0.243325E+11 0.00 0.00 0.00 0.00 37309636.84 0.236226E+10
Minimum of Months 0.901968E+09 0.644089E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 19721001.24
Maximum of Months 0.107774E+10 0.855795E+09 0.212947E+10 0.00 0.00 0.00 0.00 15063995.11 0.409322E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.531815E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.274018E+09
February 0.571020E+09 0.445928E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.246310E+09
March 0.682301E+09 0.495813E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.199082E+09
April 0.605444E+09 0.421406E+09 0.125169E+10 0.00 0.00 0.00 0.00 103798.30 0.134210E+09
May 0.655854E+09 0.446103E+09 0.132213E+10 0.00 0.00 0.00 0.00 415742.64 78448294.55
June 0.654023E+09 0.438314E+09 0.129819E+10 0.00 0.00 0.00 0.00 3486788.65 41222108.42
July 0.607275E+09 0.411209E+09 0.127534E+10 0.00 0.00 0.00 0.00 7975303.81 14558727.17
August 0.682301E+09 0.464108E+09 0.134804E+10 0.00 0.00 0.00 0.00 9318590.82 19741084.04
September 0.605444E+09 0.429663E+09 0.125111E+10 0.00 0.00 0.00 0.00 1166068.55 47240745.69
October 0.629407E+09 0.465404E+09 0.129650E+10 0.00 0.00 0.00 0.00 19542.13 0.116859E+09
November 0.623262E+09 0.509030E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.208205E+09
December 0.607275E+09 0.520378E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.240304E+09
                   
Annual Sum or Average 0.755301E+10 0.557917E+10 0.154036E+11 0.00 0.00 0.00 0.00 22485834.89 0.162020E+10
Minimum of Months 0.571020E+09 0.411209E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 14558727.17
Maximum of Months 0.682301E+09 0.531815E+09 0.134804E+10 0.00 0.00 0.00 0.00 9318590.82 0.274018E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.811644E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.515778E+10
February 0.901968E+09 0.685228E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.515202E+10
March 0.107774E+10 0.774833E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.465220E+10
April 0.956342E+09 0.664987E+09 0.197725E+10 0.00 0.00 0.00 0.00 10880372.69 0.275350E+10
May 0.103597E+10 0.703179E+09 0.208851E+10 0.00 0.00 0.00 0.00 44881449.53 0.166270E+10
June 0.103308E+10 0.690949E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.315898E+09 0.562284E+09
July 0.959235E+09 0.649268E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.668843E+09 76162134.09
August 0.107774E+10 0.732861E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.815291E+09 0.185655E+09
September 0.956342E+09 0.675814E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.134128E+09 0.797955E+09
October 0.994195E+09 0.723481E+09 0.204803E+10 0.00 0.00 0.00 0.00 1809478.76 0.214484E+10
November 0.984487E+09 0.781889E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.389255E+10
December 0.959235E+09 0.789341E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.466859E+10
                   
Annual Sum or Average 0.119305E+11 0.868347E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.199173E+10 0.317063E+11
Minimum of Months 0.901968E+09 0.649268E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 76162134.09
Maximum of Months 0.107774E+10 0.811644E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.815291E+09 0.515778E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.522475E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.274896E+09
February 0.570983E+09 0.438975E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.245950E+09
March 0.682256E+09 0.491114E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.202104E+09
April 0.605404E+09 0.421099E+09 0.125169E+10 0.00 0.00 0.00 0.00 111671.84 0.134505E+09
May 0.655811E+09 0.441772E+09 0.132212E+10 0.00 0.00 0.00 0.00 624357.56 79320097.71
June 0.653980E+09 0.434646E+09 0.129818E+10 0.00 0.00 0.00 0.00 3391317.60 43712944.11
July 0.607235E+09 0.408784E+09 0.127533E+10 0.00 0.00 0.00 0.00 8060976.14 16581870.26
August 0.682256E+09 0.461693E+09 0.134804E+10 0.00 0.00 0.00 0.00 9375073.08 20868912.81
September 0.605404E+09 0.429196E+09 0.125110E+10 0.00 0.00 0.00 0.00 1179816.34 47422309.31
October 0.629366E+09 0.460716E+09 0.129649E+10 0.00 0.00 0.00 0.00 19552.85 0.118572E+09
November 0.623221E+09 0.499806E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.204913E+09
December 0.607235E+09 0.513773E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.240360E+09
                   
Annual Sum or Average 0.755252E+10 0.552405E+10 0.154035E+11 0.00 0.00 0.00 0.00 22762765.40 0.162921E+10
Minimum of Months 0.570983E+09 0.408784E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 16581870.26
Maximum of Months 0.682256E+09 0.522475E+09 0.134804E+10 0.00 0.00 0.00 0.00 9375073.08 0.274896E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.861293E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.632559E+09
February 0.901968E+09 0.718912E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.564841E+09
March 0.107774E+10 0.788618E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.463902E+09
April 0.956342E+09 0.665518E+09 0.197726E+10 0.00 0.00 0.00 0.00 238548.00 0.310050E+09
May 0.103597E+10 0.700073E+09 0.208852E+10 0.00 0.00 0.00 0.00 1247854.91 0.186190E+09
June 0.103308E+10 0.686128E+09 0.205071E+10 0.00 0.00 0.00 0.00 8048590.39 98213903.66
July 0.959235E+09 0.645025E+09 0.201461E+10 0.00 0.00 0.00 0.00 18736358.62 35215170.03
August 0.107774E+10 0.730074E+09 0.212947E+10 0.00 0.00 0.00 0.00 22483695.08 44536495.22
September 0.956342E+09 0.681982E+09 0.197634E+10 0.00 0.00 0.00 0.00 2778864.44 0.102377E+09
October 0.994195E+09 0.741925E+09 0.204804E+10 0.00 0.00 0.00 0.00 43190.90 0.254610E+09
November 0.984487E+09 0.817781E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.459327E+09
December 0.959235E+09 0.855579E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.541964E+09
                   
Annual Sum or Average 0.119305E+11 0.889291E+10 0.243325E+11 0.00 0.00 0.00 0.00 53577102.34 0.369379E+10
Minimum of Months 0.901968E+09 0.645025E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 35215170.03
Maximum of Months 0.107774E+10 0.861293E+09 0.212947E+10 0.00 0.00 0.00 0.00 22483695.08 0.632559E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.533841E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.422136E+09
February 0.421807E+09 0.447525E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.381593E+09
March 0.502994E+09 0.497172E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.312760E+09
April 0.447140E+09 0.422223E+09 0.125169E+10 0.00 0.00 0.00 0.00 159388.05 0.211932E+09
May 0.484071E+09 0.446586E+09 0.132213E+10 0.00 0.00 0.00 0.00 619830.05 0.125466E+09
June 0.482240E+09 0.438836E+09 0.129819E+10 0.00 0.00 0.00 0.00 5335961.48 65640568.42
July 0.448971E+09 0.411705E+09 0.127534E+10 0.00 0.00 0.00 0.00 12327469.39 23617649.50
August 0.502994E+09 0.464454E+09 0.134804E+10 0.00 0.00 0.00 0.00 14610110.94 30507641.51
September 0.447140E+09 0.430424E+09 0.125111E+10 0.00 0.00 0.00 0.00 1819087.14 70297577.01
October 0.465148E+09 0.466644E+09 0.129650E+10 0.00 0.00 0.00 0.00 28775.66 0.173014E+09
November 0.460569E+09 0.510330E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.309444E+09
December 0.448971E+09 0.523472E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.363508E+09
                   
Annual Sum or Average 0.557719E+10 0.559321E+10 0.154036E+11 0.00 0.00 0.00 0.00 34900622.71 0.248992E+10
Minimum of Months 0.421807E+09 0.411705E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 23617649.50
Maximum of Months 0.502994E+09 0.533841E+09 0.134804E+10 0.00 0.00 0.00 0.00 14610110.94 0.422136E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.814181E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.652705E+09
February 0.901968E+09 0.686012E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.597461E+09
March 0.107774E+10 0.776147E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.485693E+09
April 0.956342E+09 0.666087E+09 0.197725E+10 0.00 0.00 0.00 0.00 238214.98 0.323278E+09
May 0.103597E+10 0.704048E+09 0.208851E+10 0.00 0.00 0.00 0.00 929104.04 0.189065E+09
June 0.103308E+10 0.692138E+09 0.205070E+10 0.00 0.00 0.00 0.00 7655038.98 98743428.66
July 0.959235E+09 0.650038E+09 0.201460E+10 0.00 0.00 0.00 0.00 17972687.37 36276450.69
August 0.107774E+10 0.733674E+09 0.212945E+10 0.00 0.00 0.00 0.00 21464495.48 46864928.20
September 0.956342E+09 0.677097E+09 0.197632E+10 0.00 0.00 0.00 0.00 2700876.13 0.110370E+09
October 0.994195E+09 0.724484E+09 0.204803E+10 0.00 0.00 0.00 0.00 35052.42 0.276842E+09
November 0.984487E+09 0.783316E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.484307E+09
December 0.959235E+09 0.792354E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.571942E+09
                   
Annual Sum or Average 0.119305E+11 0.869958E+10 0.243324E+11 0.00 0.00 0.00 0.00 50995469.39 0.387355E+10
Minimum of Months 0.901968E+09 0.650038E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 36276450.69
Maximum of Months 0.107774E+10 0.814181E+09 0.212945E+10 0.00 0.00 0.00 0.00 21464495.48 0.652705E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.525304E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.423922E+09
February 0.570983E+09 0.440532E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.381550E+09
March 0.682256E+09 0.492403E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.317205E+09
April 0.605404E+09 0.421696E+09 0.125169E+10 0.00 0.00 0.00 0.00 163354.32 0.212653E+09
May 0.655811E+09 0.442276E+09 0.132212E+10 0.00 0.00 0.00 0.00 876560.62 0.127132E+09
June 0.653980E+09 0.435217E+09 0.129818E+10 0.00 0.00 0.00 0.00 5314255.11 68721104.84
July 0.607235E+09 0.409363E+09 0.127533E+10 0.00 0.00 0.00 0.00 12488511.89 26350131.18
August 0.682256E+09 0.462311E+09 0.134804E+10 0.00 0.00 0.00 0.00 14710141.44 32043598.92
September 0.605404E+09 0.430025E+09 0.125110E+10 0.00 0.00 0.00 0.00 1873906.36 70909805.16
October 0.629366E+09 0.461490E+09 0.129649E+10 0.00 0.00 0.00 0.00 28813.69 0.175082E+09
November 0.623221E+09 0.501660E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.306770E+09
December 0.607235E+09 0.515861E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.364568E+09
                   
Annual Sum or Average 0.755252E+10 0.553814E+10 0.154035E+11 0.00 0.00 0.00 0.00 35455543.42 0.250691E+10
Minimum of Months 0.570983E+09 0.409363E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 26350131.18
Maximum of Months 0.682256E+09 0.525304E+09 0.134804E+10 0.00 0.00 0.00 0.00 14710141.44 0.423922E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.880432E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.797611E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.655445E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214484.95 0.437067E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1318375.66 0.255982E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8029298.18 0.133279E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19804950.94 45018485.37
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23634246.73 60208408.08
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2288963.78 0.146855E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2838.01 0.368586E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.664413E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.781502E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55293158.24 0.522640E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45018485.37
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23634246.73 0.880432E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107716E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.976948E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.805879E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 284708.52 0.537986E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1715746.26 0.321813E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10486319.56 0.168625E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25724940.86 56792413.64
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30834929.90 75549466.99
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2993987.60 0.180090E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7025.45 0.450172E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.796018E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.939293E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72047658.16 0.638633E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56792413.64
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30834929.90 0.107716E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108816E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.987348E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.817543E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67169.49 0.551271E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 643730.57 0.340065E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8618620.99 0.179699E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21453051.73 62908170.61
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28447127.94 75133086.31
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2572543.18 0.184022E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.451282E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.779199E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.925838E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61802243.90 0.644247E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62908170.61
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28447127.94 0.108816E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:10 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1227.84 31-JAN-01:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:49 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1322.42 06-FEB-00:55
March 1306.65 01-MAR-10:09 1184.79 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1001.64 21-MAR-21:03
April 1306.65 03-APR-09:09 774.31 18-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 16.73 07-APR-13:00 785.75 11-APR-04:00
May 1306.65 01-MAY-09:09 774.31 04-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 66.72 29-MAY-11:53 455.98 03-MAY-04:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 112.29 19-JUN-21:03 280.96 02-JUN-22:00
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 118.36 09-JUL-13:52 130.64 11-JUL-05:00
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 156.97 04-AUG-21:03 176.52 20-AUG-06:00
September 1306.65 01-SEP-09:09 947.97 22-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 44.13 14-SEP-14:00 233.80 23-SEP-04:00
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 7.42 25-OCT-11:00 651.35 17-OCT-24:00
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:19 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 996.82 23-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:10 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1313.59 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   130.64  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 156.97   1322.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 02-JAN-16:10 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 818.14 31-JAN-01:00
February 827.22 01-FEB-10:09 860.01 01-FEB-16:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 881.63 06-FEB-01:00
March 827.22 01-MAR-10:09 750.07 02-MAR-16:40 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 685.86 12-MAR-10:00
April 827.22 03-APR-09:09 450.21 05-APR-15:30 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 11.15 07-APR-13:00 522.12 11-APR-04:00
May 827.22 01-MAY-09:09 490.21 19-MAY-15:50 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 43.71 29-MAY-11:38 304.00 03-MAY-04:00
June 827.22 01-JUN-09:09 450.21 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 74.63 19-JUN-21:03 185.31 02-JUN-22:00
July 827.22 03-JUL-09:09 450.21 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 78.91 09-JUL-13:52 88.83 11-JUL-05:00
August 827.22 01-AUG-09:09 450.21 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 112.28 12-AUG-19:00 123.48 20-AUG-06:00
September 827.22 01-SEP-09:09 490.21 22-SEP-15:39 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.42 14-SEP-14:00 176.21 10-SEP-08:00
October 827.22 02-OCT-09:09 750.07 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.95 25-OCT-11:00 480.03 08-OCT-08:20
November 827.22 01-NOV-09:09 860.01 06-NOV-16:19 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 664.82 23-NOV-02:00
December 827.22 01-DEC-10:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 883.55 31-DEC-21:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 0.00   88.83  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 112.28   883.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1271.03 31-JAN-01:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:49 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1322.40 06-FEB-00:55
March 1306.65 01-MAR-10:09 947.97 02-MAR-16:30 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1028.98 12-MAR-10:00
April 1306.65 03-APR-09:09 774.31 18-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 16.69 07-APR-13:00 797.33 11-APR-04:00
May 1306.65 01-MAY-09:09 774.31 04-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 55.05 29-MAY-11:38 461.89 03-MAY-04:00
June 1306.65 01-JUN-09:09 774.31 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 112.22 19-JUN-21:03 280.06 02-JUN-22:00
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 113.53 09-JUL-13:52 129.27 02-JUL-18:40
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 157.55 12-AUG-19:00 177.60 20-AUG-06:00
September 1306.65 01-SEP-09:09 947.97 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 44.07 14-SEP-14:00 244.00 30-SEP-24:00
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 7.42 25-OCT-11:00 683.97 08-OCT-08:00
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:30 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1022.53 23-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1323.45 31-DEC-21:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   129.27  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 157.55   1323.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 820.35 31-JAN-01:00
February 827.17 01-FEB-10:09 859.95 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 881.61 06-FEB-00:55
March 827.17 01-MAR-10:09 750.02 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 670.89 21-MAR-21:03
April 827.17 03-APR-09:09 600.10 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 11.16 07-APR-13:00 530.81 11-APR-04:00
May 827.17 01-MAY-09:09 490.17 04-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 56.42 29-MAY-11:53 310.69 03-MAY-04:00
June 827.17 01-JUN-09:09 490.17 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 73.49 19-JUN-21:03 211.60 03-JUN-17:40
July 827.17 03-JUL-09:09 490.17 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 75.74 09-JUL-13:52 124.16 02-JUL-18:00
August 827.17 01-AUG-09:09 600.10 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 106.09 12-AUG-19:00 120.26 20-AUG-06:00
September 827.17 01-SEP-09:09 600.10 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.42 14-SEP-14:00 168.59 10-SEP-20:00
October 827.17 02-OCT-09:09 750.02 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.95 25-OCT-11:00 440.12 17-OCT-24:00
November 827.17 01-NOV-09:09 859.95 06-NOV-16:40 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 663.63 23-NOV-02:00
December 827.17 01-DEC-10:09 859.95 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 884.64 31-DEC-21:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   490.17   908.57   0.00 0.00 0.00 0.00 0.00   120.26  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 106.09   884.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:10 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 711.85 31-JAN-01:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:49 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 699.50 05-FEB-07:53
March 1306.65 01-MAR-10:09 1184.79 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 533.71 21-MAR-21:03
April 1306.65 03-APR-09:09 774.31 18-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 9.07 07-APR-13:00 440.57 11-APR-04:00
May 1306.65 01-MAY-09:09 774.31 08-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 52.37 29-MAY-12:00 248.20 03-MAY-04:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 61.20 19-JUN-21:03 151.00 02-JUN-22:00
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 72.82 09-JUL-13:52 71.07 11-JUL-05:00
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 84.28 04-AUG-21:03 101.56 20-AUG-06:00
September 1306.65 01-SEP-09:09 947.97 26-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 23.65 14-SEP-14:00 137.28 17-SEP-10:00
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 4.16 25-OCT-11:00 398.47 08-OCT-08:00
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:19 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 598.34 23-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:10 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 737.98 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   71.07  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 84.28   737.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 02-JAN-16:10 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 479.50 31-JAN-01:00
February 827.22 01-FEB-10:09 860.01 01-FEB-16:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 496.95 05-FEB-08:40
March 827.22 01-MAR-10:09 750.07 02-MAR-16:49 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 387.14 12-MAR-10:00
April 827.22 03-APR-09:09 450.21 05-APR-15:39 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 6.05 07-APR-13:00 300.95 11-APR-04:00
May 827.22 01-MAY-09:09 490.21 19-MAY-15:50 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 21.69 29-MAY-11:38 174.13 03-MAY-04:00
June 827.22 01-JUN-09:09 450.21 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 40.33 19-JUN-21:03 104.62 02-JUN-22:00
July 827.22 03-JUL-09:09 410.22 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 43.82 09-JUL-13:52 50.24 11-JUL-05:00
August 827.22 01-AUG-09:09 450.21 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 55.59 04-AUG-21:03 73.32 20-AUG-06:00
September 827.22 01-SEP-09:09 490.21 22-SEP-15:50 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 15.77 14-SEP-14:00 93.85 17-SEP-10:00
October 827.22 02-OCT-09:09 750.07 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 2.77 25-OCT-11:00 295.12 08-OCT-08:00
November 827.22 01-NOV-09:09 860.01 06-NOV-16:19 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 405.72 23-NOV-02:00
December 827.22 01-DEC-10:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 496.45 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   410.22   908.57   0.00 0.00 0.00 0.00 0.00   50.24  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 55.59   496.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 26297.82 31-JAN-07:01
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 28780.03 06-FEB-07:01
March 1306.65 01-MAR-10:09 947.97 02-MAR-16:40 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 21964.10 23-MAR-06:01
April 1306.65 03-APR-09:09 774.31 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 1695.29 07-APR-17:00 15281.03 03-APR-06:01
May 1306.65 01-MAY-09:09 774.31 08-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 4156.08 30-MAY-12:00 10654.74 01-MAY-06:03
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 9103.30 19-JUN-11:03 7028.42 02-JUN-06:02
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 7056.41 07-JUL-11:05 2539.63 11-JUL-06:03
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 7368.90 24-AUG-16:05 4664.26 25-AUG-06:03
September 1306.65 01-SEP-09:09 947.97 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 4420.61 14-SEP-16:10 9625.75 11-SEP-06:01
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 656.19 25-OCT-11:10 13571.42 31-OCT-06:03
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:40 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 21593.19 24-NOV-07:01
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 22154.09 22-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   2539.63  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 9103.30   28780.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 480.31 31-JAN-01:00
February 827.17 01-FEB-10:09 859.95 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 468.75 06-FEB-00:55
March 827.17 01-MAR-10:09 750.02 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 358.88 21-MAR-21:03
April 827.17 03-APR-09:09 600.10 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 6.05 07-APR-13:00 311.08 11-APR-04:00
May 827.17 01-MAY-09:09 490.17 04-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 34.19 29-MAY-12:00 175.67 03-MAY-04:00
June 827.17 01-JUN-09:09 490.17 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 39.37 19-JUN-21:03 110.60 02-JUN-22:00
July 827.17 03-JUL-09:09 490.17 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 42.36 09-JUL-13:52 58.17 02-JUL-17:50
August 827.17 01-AUG-09:09 600.10 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 55.35 04-AUG-21:03 73.19 20-AUG-06:00
September 827.17 01-SEP-09:09 600.10 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 15.77 14-SEP-14:00 96.32 30-SEP-24:00
October 827.17 02-OCT-09:09 750.02 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 2.77 25-OCT-11:00 272.87 08-OCT-08:00
November 827.17 01-NOV-09:09 859.95 06-NOV-16:40 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 401.28 23-NOV-02:00
December 827.17 01-DEC-10:09 859.95 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 498.01 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   490.17   908.57   0.00 0.00 0.00 0.00 0.00   58.17  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 55.35   498.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:10 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1093.80 31-JAN-01:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:49 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1101.68 06-FEB-01:00
March 1306.65 01-MAR-10:09 1184.79 02-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 838.74 21-MAR-21:03
April 1306.65 03-APR-09:09 774.31 18-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 14.06 07-APR-13:00 701.24 11-APR-04:00
May 1306.65 01-MAY-09:09 774.31 04-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 63.66 29-MAY-12:00 409.27 03-MAY-04:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 94.28 19-JUN-21:03 242.90 02-JUN-22:00
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 92.77 09-JUL-13:52 114.51 11-JUL-05:00
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 131.33 04-AUG-21:03 159.05 20-AUG-06:00
September 1306.65 01-SEP-09:09 947.97 22-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 36.88 14-SEP-14:00 209.22 17-SEP-10:00
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 6.34 25-OCT-11:00 589.63 08-OCT-08:00
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:19 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 900.15 23-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:10 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1083.31 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   114.51  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 131.33   1101.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 860.01 02-JAN-16:10 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 729.34 31-JAN-01:00
February 805.43 01-FEB-08:09 860.01 01-FEB-16:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 768.72 05-FEB-08:50
March 805.43 01-MAR-08:09 750.07 02-MAR-16:40 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 625.53 12-MAR-10:00
April 805.43 03-APR-07:10 450.21 05-APR-15:30 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 9.38 07-APR-13:00 465.80 11-APR-04:00
May 805.43 01-MAY-07:10 490.21 19-MAY-15:50 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 34.50 29-MAY-12:00 272.52 03-MAY-04:00
June 805.43 01-JUN-07:10 450.21 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 62.66 19-JUN-21:03 160.18 02-JUN-22:00
July 805.43 03-JUL-07:10 450.21 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 62.90 09-JUL-14:05 77.73 11-JUL-05:00
August 805.43 01-AUG-07:10 450.21 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 87.28 04-AUG-21:03 110.90 20-AUG-06:00
September 805.43 01-SEP-07:10 490.21 22-SEP-15:39 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 24.59 14-SEP-14:00 141.89 10-SEP-07:50
October 805.43 02-OCT-07:10 750.07 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.23 25-OCT-11:00 443.69 08-OCT-08:00
November 805.43 01-NOV-07:10 860.01 06-NOV-16:19 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 600.58 23-NOV-02:00
December 805.43 01-DEC-08:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 726.64 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   450.21   908.57   0.00 0.00 0.00 0.00 0.00   77.73  
Maximum of Months 805.43   860.01   908.57   0.00 0.00 0.00 0.00 87.28   768.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1131.98 31-JAN-01:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:49 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1128.96 05-FEB-10:00
March 1306.65 01-MAR-10:09 947.97 02-MAR-16:30 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 938.42 12-MAR-10:00
April 1306.65 03-APR-09:09 774.31 18-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 14.03 07-APR-13:00 710.74 11-APR-04:00
May 1306.65 01-MAY-09:09 774.31 04-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 45.46 29-MAY-11:57 414.27 03-MAY-04:00
June 1306.65 01-JUN-09:09 774.31 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 94.20 19-JUN-21:03 242.66 02-JUN-22:00
July 1306.65 03-JUL-09:09 711.15 05-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 90.56 09-JUL-13:50 112.79 11-JUL-05:00
August 1306.65 01-AUG-09:09 774.31 16-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 130.91 04-AUG-21:03 160.04 20-AUG-06:00
September 1306.65 01-SEP-09:09 947.97 27-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 36.83 14-SEP-14:00 217.25 30-SEP-24:00
October 1306.65 02-OCT-09:09 1184.79 06-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 6.32 25-OCT-11:00 637.24 08-OCT-08:00
November 1306.65 01-NOV-09:09 1358.45 06-NOV-16:30 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 924.32 23-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1145.97 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   112.79  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 130.91   1145.97  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 730.99 31-JAN-01:00
February 827.17 01-FEB-10:09 859.95 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 734.05 06-FEB-01:00
March 827.17 01-MAR-10:09 750.02 16-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 562.02 21-MAR-21:03
April 827.17 03-APR-09:09 600.10 14-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 9.38 07-APR-13:00 473.23 11-APR-04:00
May 827.17 01-MAY-09:09 490.17 04-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 51.65 29-MAY-12:00 278.36 03-MAY-04:00
June 827.17 01-JUN-09:09 490.17 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 61.75 19-JUN-21:03 174.13 03-JUN-17:40
July 827.17 03-JUL-09:09 490.17 24-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 61.32 09-JUL-14:05 95.92 02-JUL-17:40
August 827.17 01-AUG-09:09 600.10 16-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 86.86 04-AUG-21:03 108.30 20-AUG-06:00
September 827.17 01-SEP-09:09 600.10 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 24.59 14-SEP-14:00 142.62 30-SEP-24:00
October 827.17 02-OCT-09:09 750.02 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.23 25-OCT-11:00 394.83 17-OCT-24:00
November 827.17 01-NOV-09:09 859.95 06-NOV-16:40 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 599.73 23-NOV-02:00
December 827.17 01-DEC-10:09 859.95 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 731.15 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   490.17   908.57   0.00 0.00 0.00 0.00 0.00   95.92  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 86.86   734.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1580.52 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1561.79 06-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1152.21 21-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.85 07-APR-13:00 995.28 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.57 29-MAY-12:00 577.36 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.26 19-JUN-21:03 327.80 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 131.27 09-JUL-14:00 149.54 11-JUL-05:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.55 12-AUG-18:53 218.01 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.48 14-SEP-14:00 291.96 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.71 25-OCT-11:00 854.06 08-OCT-08:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1318.38 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1627.64 31-DEC-21:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   149.54  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.55   1627.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1942.62 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1893.43 06-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1440.71 21-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.62 07-APR-13:00 1254.31 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.22 29-MAY-12:00 721.72 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.46 19-JUN-21:03 418.92 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.44 09-JUL-13:52 190.27 11-JUL-05:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.07 12-AUG-18:53 273.20 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.68 14-SEP-14:00 363.00 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.59 25-OCT-11:00 1043.93 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1612.57 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1943.87 31-DEC-21:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   190.27  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.07   1943.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1878.06 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1904.80 06-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1512.81 21-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.74 08-APR-10:00 1186.29 11-APR-04:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.02 30-MAY-13:00 686.85 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.89 19-JUN-21:03 404.92 03-JUN-18:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.17 07-JUL-22:00 227.59 02-JUL-18:03
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.77 04-AUG-21:03 243.35 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.40 14-SEP-14:00 350.39 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 985.86 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1516.05 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1918.66 31-DEC-22:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   227.59  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 223.77   1918.66  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12200.66 27-JAN-16:30 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
February 13132.60 24-FEB-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
March 17601.22 29-MAR-16:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
April 36452.65 10-APR-06:03 5082.11 8592.08 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
May 40527.48 30-MAY-05:12 3176.32 3579.89 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
June 44122.38 19-JUN-05:03 3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00
July 43854.10 25-JUL-05:03 3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00
August 41921.71 01-AUG-04:03 0.00 846.94 22568.22 0.00 0.00 0.00 0.00 0.00 0.00
September 43602.31 01-SEP-05:03 3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00
October 39397.01 06-OCT-05:12 2541.06 2863.91 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
November 24335.57 03-NOV-06:03 5082.11 8592.08 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
December 14702.61 21-DEC-16:10 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12200.66   0.00 846.94 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 44122.38   6035.01 8592.08 44462.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 467.96 17-JAN-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56.74
February 928.43 17-FEB-13:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 101.65
March 3041.25 03-MAR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 144.74
April 7520.79 07-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.38 0.00
May 11096.85 30-MAY-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.73 0.00
June 12459.99 19-JUN-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.59 0.00
July 11613.76 10-JUL-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.71 0.00
August 11161.93 01-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.56 0.00
September 9908.45 01-SEP-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.44 0.00
October 7051.42 04-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.61
November 2506.09 04-NOV-13:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.45
December 1189.86 17-DEC-13:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 253.77
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 467.96   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12459.99   0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.71 253.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2142.21 05-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 895.49
February 1923.34 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 241.05
March 2524.67 16-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 166.99
April 2402.14 10-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.37
May 5089.64 30-MAY-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.78 0.00
June 5240.77 19-JUN-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.05 0.00
July 5626.28 10-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.29 0.00
August 5764.67 14-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.32 0.00
September 5389.19 05-SEP-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.93 0.00
October 3360.27 04-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.87
November 1669.62 18-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 161.76
December 1734.49 23-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 249.26
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1669.62   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5764.67   0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.29 895.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1758.98 25-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 169.82
February 2203.45 24-FEB-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.88
March 2939.92 16-MAR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.94
April 2928.68 10-APR-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.46
May 5297.27 30-MAY-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.65 0.00
June 6558.32 19-JUN-12:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.14 0.00
July 6055.16 10-JUL-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.41 0.00
August 5946.36 14-AUG-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.82 0.00
September 5583.10 05-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.93 0.00
October 4073.00 04-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.32
November 2144.33 03-NOV-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.52
December 2156.41 20-DEC-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.70
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1758.98   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6558.32   0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.14 169.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7205.30 20-JAN-17:00 12070.02 12887.96 13616.64 0.00 0.00 0.00 0.00 0.00 0.00
February 7211.45 02-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 10562.61 29-MAR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14840.05 10-APR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 31832.95 30-MAY-05:12 3176.32 3579.89 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
June 35205.20 19-JUN-05:03 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
July 34919.84 25-JUL-05:03 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
August 32980.65 07-AUG-05:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
September 30740.55 01-SEP-05:02 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
October 16176.59 05-OCT-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 12192.31 03-NOV-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7405.35 21-DEC-16:20 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7205.30   2541.06 1270.40 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35205.20   12070.02 12887.96 18155.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7036.89 20-JAN-16:40 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 7110.39 02-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 10111.32 29-MAR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 15582.59 10-APR-15:50 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 25095.91 30-MAY-05:12 3176.32 3579.89 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
June 35031.03 19-JUN-05:03 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
July 33982.43 25-JUL-05:02 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
August 34402.80 07-AUG-05:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
September 34069.10 01-SEP-05:02 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
October 16633.01 04-OCT-15:50 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 10842.23 03-NOV-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7045.79 21-DEC-16:10 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7036.89   2541.06 1270.40 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35031.03   6035.01 6443.98 18155.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1167.22 20-JAN-16:10 1272.23 1121.62 1435.25 0.00 0.00 0.00 0.00 0.00 53.17
February 1207.09 24-FEB-15:50 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 138.19
March 1715.71 28-MAR-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 83.85
April 4151.27 07-APR-15:20 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 10.60 0.00
May 8019.78 29-MAY-14:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 0.00 42.59
June 9657.68 19-JUN-05:02 803.52 267.81 3827.32 0.00 0.00 0.00 0.00 0.00 5.85
July 10460.75 10-JUL-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 0.82
August 10255.00 13-AUG-15:52 401.76 215.99 2870.49 0.00 0.00 0.00 0.00 52.97 0.00
September 6200.27 01-SEP-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 32.39 0.00
October 4274.36 04-OCT-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 1.48 0.00
November 1681.96 03-NOV-14:50 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 20.56
December 1200.33 20-DEC-14:00 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 64.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1167.22   0.00 143.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10460.75   1306.65 1121.62 3827.32 0.00 0.00 0.00 0.00 52.97 138.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1304.21 19-JAN-10:10 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 78.28
February 1371.70 22-FEB-09:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 106.21
March 3632.33 29-MAR-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 54.51
April 6252.72 28-APR-08:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 28.43
May 13644.17 29-MAY-08:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 11.11
June 12806.26 25-JUN-08:42 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 19.18
July 13765.45 02-JUL-08:42 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 16.81
August 12674.93 13-AUG-09:12 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 15.58 0.00
September 13570.24 04-SEP-08:42 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 19.74
October 5540.08 05-OCT-09:20 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 15.39
November 1999.53 02-NOV-09:40 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 77.26
December 1349.27 20-DEC-09:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 22.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1304.21   211.95 113.95 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13765.45   1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 15.58 106.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6182.74 19-JAN-13:25 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 138.40
February 6609.01 02-FEB-13:50 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 114.70
March 9111.67 03-MAR-13:25 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 92.55
April 10160.78 07-APR-12:30 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 13.27 0.00
May 16740.78 29-MAY-11:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 32.78 0.00
June 12609.23 19-JUN-05:02 803.52 267.81 3827.30 0.00 0.00 0.00 0.00 0.00 4.34
July 16695.77 04-JUL-12:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 26.70 0.00
August 16974.30 13-AUG-12:32 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 63.67 0.00
September 17318.50 04-SEP-12:42 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 22.36
October 16635.94 15-OCT-15:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 240.37
November 10899.84 02-NOV-13:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 55.81
December 6340.67 21-DEC-13:25 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 120.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6182.74   267.84 143.99 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17318.50   2544.47 1295.96 3827.30 0.00 0.00 0.00 0.00 63.67 240.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1619.26 19-JAN-15:50 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 100.63
February 2164.10 24-FEB-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 107.20
March 5495.08 29-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 77.09
April 10949.58 09-APR-17:12 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 81.48
May 12026.20 14-MAY-16:03 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 180.30
June 15109.07 18-JUN-16:02 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 35.42
July 15121.48 02-JUL-16:02 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 51.42
August 14773.21 13-AUG-15:52 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 27.74 0.00
September 14551.77 10-SEP-16:02 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 62.21
October 10232.71 15-OCT-15:13 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 156.62
November 3622.98 03-NOV-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 17.42
December 1574.01 08-DEC-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 72.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1574.01   0.00 91.15 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15121.48   805.38 410.20 1817.13 0.00 0.00 0.00 0.00 27.74 180.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1151.49 20-JAN-15:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 36.29
February 1161.13 24-FEB-14:10 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 67.84
March 1502.21 28-MAR-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 40.76
April 2317.43 10-APR-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 14.35
May 4611.58 30-MAY-13:50 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 14.00 0.00
June 7611.72 26-JUN-06:03 803.52 647.99 1913.66 0.00 0.00 0.00 0.00 0.00 4.36
July 7817.49 10-JUL-06:03 803.52 711.16 1913.66 0.00 0.00 0.00 0.00 4.66 0.00
August 7036.93 14-AUG-06:03 803.52 647.99 1913.66 0.00 0.00 0.00 0.00 0.00 0.82
September 6145.17 01-SEP-05:02 803.52 267.81 3827.32 0.00 0.00 0.00 0.00 0.00 2.49
October 3883.70 05-OCT-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 1.99
November 1863.24 06-NOV-13:07 3816.70 1943.94 4305.74 0.00 0.00 0.00 0.00 0.00 30.99
December 1250.36 20-DEC-14:00 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 35.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1151.49   803.52 267.81 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7817.49   3816.70 1943.94 4305.74 0.00 0.00 0.00 0.00 14.00 67.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1094.94 27-JAN-10:10 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 20.78
February 1117.76 22-FEB-09:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 55.95
March 2342.90 29-MAR-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 28.90
April 4280.43 28-APR-09:10 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 12.64
May 9317.74 29-MAY-08:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 4.38
June 11579.24 25-JUN-09:12 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 10.06
July 11366.36 02-JUL-09:11 296.74 159.53 2120.00 0.00 0.00 0.00 0.00 0.00 6.89
August 9374.53 20-AUG-10:32 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 9.54
September 11580.06 10-SEP-09:12 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 58.71
October 5077.23 05-OCT-09:20 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 8.10
November 2384.94 03-NOV-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 16.06
December 1215.18 20-DEC-09:40 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 12.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1094.94   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 4.38
Maximum of Months 11580.06   1610.86 820.45 2120.00 0.00 0.00 0.00 0.00 0.00 58.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1711.72 19-JAN-14:30 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 1730.47
February 2551.24 25-FEB-13:10 133.92 107.99 558.15 0.00 0.00 0.00 0.00 0.00 79.74
March 6095.69 03-MAR-13:08 6361.16 3239.90 7176.19 0.00 0.00 0.00 0.00 0.00 1105.14
April 7124.65 07-APR-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 1295.86 0.00
May 11137.43 30-MAY-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 4156.08 0.00
June 12767.65 19-JUN-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 8484.94 0.00
July 12199.12 07-JUL-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 6815.94 0.00
August 13623.84 13-AUG-13:12 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 35.58 0.00
September 14531.58 03-SEP-12:52 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 0.00 35.73
October 13850.81 22-OCT-13:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 0.00
November 10127.05 06-NOV-13:07 3816.70 1943.94 4305.71 0.00 0.00 0.00 0.00 0.00 1250.80
December 5361.29 17-DEC-14:37 200.88 107.99 1435.24 0.00 0.00 0.00 0.00 0.00 182.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1711.72   133.92 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14531.58   6361.16 3239.90 7176.19 0.00 0.00 0.00 0.00 8484.94 1730.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1285.78 20-JAN-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 19.57
February 1356.44 22-FEB-16:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 36.18
March 3499.78 27-MAR-16:50 254.33 227.89 504.76 0.00 0.00 0.00 0.00 0.00 5.48
April 6429.68 09-APR-16:53 127.16 68.36 908.57 0.00 0.00 0.00 0.00 0.00 33.36
May 7412.31 27-MAY-17:42 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 58.22
June 11865.52 25-JUN-16:32 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 15.46
July 11771.42 02-JUL-16:31 339.11 182.31 2422.85 0.00 0.00 0.00 0.00 0.00 28.28
August 11528.78 13-AUG-15:52 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 17.62 0.00
September 12362.50 10-SEP-16:31 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 0.00 47.83
October 7373.85 15-OCT-15:13 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 81.89
November 3400.57 03-NOV-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 9.20
December 1295.53 08-DEC-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 39.24
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1285.78   127.16 68.36 504.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12362.50   805.38 410.20 2422.85 0.00 0.00 0.00 0.00 17.62 81.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1213.90 20-JAN-15:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 58.76
February 1241.24 24-FEB-15:50 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 118.08
March 1793.49 28-MAR-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 69.63
April 3699.78 07-APR-15:20 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 8.97 0.00
May 8425.44 30-MAY-06:03 803.52 647.99 1913.66 0.00 0.00 0.00 0.00 0.00 7.24
June 8783.54 26-JUN-05:12 669.60 359.98 3189.44 0.00 0.00 0.00 0.00 0.00 16.94
July 9049.59 09-JUL-14:41 468.72 251.99 3348.91 0.00 0.00 0.00 0.00 24.91 0.00
August 8613.52 14-AUG-06:03 803.52 647.99 1913.66 0.00 0.00 0.00 0.00 0.00 1.56
September 8447.07 01-SEP-05:02 803.52 267.81 3827.32 0.00 0.00 0.00 0.00 0.00 4.03
October 4141.88 05-OCT-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 3.24
November 1919.92 03-NOV-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 11.47
December 1265.19 20-DEC-14:00 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 56.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1213.90   468.72 251.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9049.59   1306.65 711.15 3827.32 0.00 0.00 0.00 0.00 24.91 118.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1381.12 19-JAN-10:00 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 66.31
February 1478.27 22-FEB-09:40 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 94.34
March 4332.67 29-MAR-09:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 46.79
April 6631.85 28-APR-08:30 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 28.03
May 13628.67 28-MAY-08:22 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 91.29
June 14190.10 25-JUN-08:32 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 28.30
July 14565.82 09-JUL-09:21 296.74 159.53 2120.00 0.00 0.00 0.00 0.00 4.87 0.00
August 13315.21 27-AUG-09:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 13.26
September 14089.13 10-SEP-08:32 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 108.00
October 6787.84 15-OCT-09:43 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 121.95
November 2792.37 02-NOV-09:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 68.22
December 1472.98 20-DEC-09:40 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 20.31
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1381.12   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14565.82   1610.86 820.45 2120.00 0.00 0.00 0.00 0.00 4.87 121.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6503.78 19-JAN-13:25 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 115.01
February 7065.14 02-FEB-13:40 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 95.69
March 9095.95 29-MAR-13:00 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 92.67
April 9606.40 07-APR-12:30 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 11.17 0.00
May 15289.57 29-MAY-12:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 12.99 0.00
June 12869.61 25-JUN-14:32 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 2.38
July 15186.35 09-JUL-11:22 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 38.81 0.00
August 15832.26 27-AUG-12:32 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 6.19 0.00
September 16591.14 10-SEP-13:12 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 0.00 92.59
October 16227.42 15-OCT-12:22 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 212.80
November 11253.47 02-NOV-12:50 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 48.00
December 9368.42 17-DEC-12:53 200.88 107.99 1435.24 0.00 0.00 0.00 0.00 0.00 186.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6503.78   200.88 107.99 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16591.14   2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 38.81 212.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1573.23 20-JAN-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 31.45
February 2451.96 24-FEB-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 89.11
March 5538.58 29-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 64.07
April 10448.23 09-APR-17:12 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 67.58
May 13405.83 28-MAY-15:02 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 10.21
June 14429.64 25-JUN-16:32 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 36.40
July 14065.07 04-JUL-16:41 339.11 182.31 2422.85 0.00 0.00 0.00 0.00 0.00 26.95
August 13598.69 13-AUG-15:52 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 24.33 0.00
September 14743.74 10-SEP-15:51 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 0.00 68.93
October 10636.77 15-OCT-15:43 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 120.53
November 3813.80 03-NOV-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 14.45
December 1545.70 08-DEC-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 62.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1545.70   0.00 91.15 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14743.74   805.38 410.20 2422.85 0.00 0.00 0.00 0.00 24.33 120.53



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.104857E+12 89999.64 02-JAN-16:40 0.104356E+12 265742.95 02-JAN-07:19
February 0.936679E+11 84014.12 06-FEB-16:00 0.884276E+11 252566.09 06-FEB-07:30
March 0.107013E+12 94861.92 27-MAR-15:00 0.385722E+11 159731.49 20-MAR-06:10
April 0.101343E+12 117334.69 07-APR-15:39 0.982290E+10 120135.52 03-APR-06:10
May 0.117624E+12 162142.67 30-MAY-14:09 0.701496E+09 30993.37 01-MAY-06:10
June 0.147266E+12 171124.26 19-JUN-10:00 4680511.24 738.27 02-JUN-06:10
July 0.163805E+12 164973.54 07-JUL-14:30 5605646.12 14.04 10-JUL-16:40
August 0.173711E+12 167162.25 16-AUG-15:09 5404297.99 15.28 29-AUG-11:50
September 0.131093E+12 146285.10 07-SEP-15:20 21764476.60 4506.12 20-SEP-06:10
October 0.117186E+12 125216.37 04-OCT-15:30 0.124031E+10 51015.77 28-OCT-06:10
November 0.101641E+12 90373.31 06-NOV-16:49 0.296274E+11 184538.20 24-NOV-07:10
December 0.102460E+12 89784.10 21-DEC-16:40 0.686472E+11 167048.17 11-DEC-07:10
             
Annual Sum or Average 0.146167E+13     0.341432E+12    
Minimum of Months 0.936679E+11 84014.12   4680511.24 14.04  
Maximum of Months 0.173711E+12 171124.26   0.104356E+12 265742.95  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.261847E+11 0.583101E+10 0.605851E+11 0.225894E+10 0.453675E+10 0.491768E+09 0.00 156139.48 0.00 0.00 0.00 0.496829E+10 0.00
February 0.231953E+11 0.466989E+10 0.548702E+11 0.204961E+10 0.390953E+10 0.421682E+09 0.00 332511.22 0.00 0.00 0.00 0.455139E+10 0.00
March 0.270991E+11 0.435457E+10 0.627783E+11 0.235661E+10 0.465100E+10 0.184900E+09 0.00 0.336053E+09 0.00 0.00 0.00 0.525299E+10 0.00
April 0.238437E+11 0.349082E+10 0.586172E+11 0.219331E+10 0.541420E+10 58109987.38 0.00 0.321211E+10 0.00 0.00 0.00 0.451362E+10 0.00
May 0.255945E+11 0.313503E+10 0.616817E+11 0.230721E+10 0.838730E+10 18108206.92 0.00 0.119794E+11 0.00 0.00 0.00 0.452052E+10 0.00
June 0.253981E+11 0.283034E+10 0.604966E+11 0.226938E+10 0.135618E+11 12262404.19 0.00 0.385165E+11 0.00 0.00 0.00 0.418105E+10 0.00
July 0.237402E+11 0.300505E+10 0.597911E+11 0.223015E+10 0.167504E+11 12291508.83 0.00 0.545086E+11 0.00 0.00 0.00 0.376679E+10 0.00
August 0.266114E+11 0.336878E+10 0.627783E+11 0.235620E+10 0.186673E+11 12708252.71 0.00 0.558273E+11 0.00 0.00 0.00 0.408939E+10 0.00
September 0.239744E+11 0.386937E+10 0.585950E+11 0.219215E+10 0.110572E+11 12078791.99 0.00 0.275890E+11 0.00 0.00 0.00 0.380411E+10 0.00
October 0.251722E+11 0.483138E+10 0.605962E+11 0.225946E+10 0.824893E+10 18912668.86 0.00 0.118908E+11 0.00 0.00 0.00 0.416831E+10 0.00
November 0.256252E+11 0.542578E+10 0.591197E+11 0.220148E+10 0.441139E+10 0.145950E+09 0.00 0.315491E+09 0.00 0.00 0.00 0.439586E+10 0.00
December 0.254422E+11 0.601184E+10 0.597800E+11 0.223021E+10 0.403844E+10 0.316848E+09 0.00 26571.72 0.00 0.00 0.00 0.464013E+10 0.00
                           
Annual Sum or Average 0.301881E+12 0.508239E+11 0.719689E+12 0.269047E+11 0.103634E+12 0.170562E+10 0.00 0.204176E+12 0.00 0.00 0.00 0.528525E+11 0.00
Minimum of Months 0.231953E+11 0.283034E+10 0.548702E+11 0.204961E+10 0.390953E+10 12078791.99 0.00 26571.72 0.00 0.00 0.00 0.376679E+10 0.00
Maximum of Months 0.270991E+11 0.601184E+10 0.627783E+11 0.235661E+10 0.186673E+11 0.491768E+09 0.00 0.558273E+11 0.00 0.00 0.00 0.525299E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.104356E+12 0.00 0.00 0.00 0.00
February 0.00 0.00 0.884276E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.385722E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.982290E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 0.701496E+09 0.00 0.00 0.00 0.00
June 0.00 0.00 4680511.24 0.00 0.00 0.00 0.00
July 0.00 0.00 5605646.12 0.00 0.00 0.00 0.00
August 0.00 0.00 5404297.99 0.00 0.00 0.00 0.00
September 0.00 0.00 21764476.60 0.00 0.00 0.00 0.00
October 0.00 0.00 0.124031E+10 0.00 0.00 0.00 0.00
November 0.00 0.00 0.296274E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.686472E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.341432E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 4680511.24 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.104356E+12 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 32642.50 02-JAN-16:30 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 02-JAN-12:20 7502.33 02-JAN-07:10 840.41 02-JAN-07:10 0.00 01-JAN-00:10
February 32642.50 01-FEB-16:00 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 02-FEB-12:09 6621.04 06-FEB-07:10 810.30 06-FEB-07:30 0.00 01-FEB-00:10
March 29330.99 02-MAR-16:00 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 01-MAR-08:09 6398.62 29-MAR-15:30 661.24 20-MAR-06:10 0.00 01-MAR-00:10
April 26798.99 21-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 03-APR-16:10 14393.63 10-APR-15:20 549.74 03-APR-06:10 0.00 01-APR-00:10
May 26798.99 08-MAY-07:10 3328.83 01-MAY-18:49 41699.26 01-MAY-07:10 1410.29 01-MAY-16:10 28390.86 30-MAY-14:09 226.24 01-MAY-06:10 0.00 01-MAY-00:10
June 26546.32 29-JUN-07:10 3328.83 01-JUN-19:19 41699.26 01-JUN-07:10 1410.29 01-JUN-07:19 27494.07 19-JUN-15:09 11.86 02-JUN-06:10 0.00 01-JUN-00:10
July 26379.99 24-JUL-07:10 3328.83 01-JUL-19:30 41699.26 03-JUL-07:10 1410.29 10-JUL-12:09 28789.94 10-JUL-15:30 6.94 10-JUL-16:40 0.00 01-JUL-00:10
August 27128.78 16-AUG-07:10 5686.19 16-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-12:09 28041.00 14-AUG-14:00 6.94 29-AUG-11:50 0.00 01-AUG-00:10
September 28290.68 27-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 11-SEP-07:10 23544.40 05-SEP-15:20 31.24 20-SEP-06:10 0.00 01-SEP-00:10
October 30940.97 06-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 06-OCT-12:09 17243.19 04-OCT-15:50 257.91 31-OCT-06:10 0.00 01-OCT-00:10
November 32642.50 06-NOV-16:40 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 01-NOV-12:09 7879.50 02-NOV-14:30 690.68 24-NOV-07:10 0.00 01-NOV-00:10
December 32642.50 01-DEC-16:30 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 01-DEC-08:09 5110.74 11-DEC-07:10 677.28 11-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 26379.99   3328.83   41699.26   1410.29   5110.74   6.94   0.00  
Maximum of Months 32642.50   5686.19   41699.26   1410.29   28789.94   840.41   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 54.05 15-JAN-06:49 0.00 0.00 0.00 6685.21 31-JAN-12:00 0.00
February 186.01 06-FEB-06:40 0.00 0.00 0.00 6688.11 07-FEB-12:50 0.00
March 16181.18 27-MAR-15:00 0.00 0.00 0.00 6673.07 01-MAR-12:00 0.00
April 31374.86 07-APR-14:30 0.00 0.00 0.00 6265.00 03-APR-11:20 0.00
May 61786.61 30-MAY-14:09 0.00 0.00 0.00 5945.78 01-MAY-11:00 0.00
June 74709.97 19-JUN-12:09 0.00 0.00 0.00 5584.09 01-JUN-11:39 0.00
July 66607.34 07-JUL-14:20 0.00 0.00 0.00 5342.29 03-JUL-11:30 0.00
August 69822.83 04-AUG-14:09 0.00 0.00 0.00 5003.76 31-AUG-11:20 0.00
September 55098.38 07-SEP-13:00 0.00 0.00 0.00 5367.28 29-SEP-11:50 0.00
October 39510.36 04-OCT-14:20 0.00 0.00 0.00 5779.08 31-OCT-11:39 0.00
November 7162.13 03-NOV-13:00 0.00 0.00 0.00 6208.37 30-NOV-12:39 0.00
December 44.29 31-DEC-09:30 0.00 0.00 0.00 6494.92 27-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 44.29   0.00 0.00 0.00 5003.76   0.00
Maximum of Months 74709.97   0.00 0.00 0.00 6688.11   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 89999.64 02-JAN-16:40 32642.50 41670.51 5686.19 1410.29 2951.54 638.95 0.00 0.00 0.00
February 84014.12 06-FEB-16:00 32642.50 41670.51 0.00 1410.29 2710.75 555.85 0.00 0.00 0.00
March 94861.92 27-MAR-15:00 25681.07 41670.51 0.00 1410.29 4926.79 6.85 0.00 16181.18 0.00
April 117334.69 07-APR-15:39 25681.07 41670.51 0.00 1410.29 13088.56 6.85 0.00 30510.96 0.00
May 162142.67 30-MAY-14:09 25681.07 41659.26 0.00 1410.29 28390.86 6.85 0.00 61786.61 0.00
June 171124.26 19-JUN-10:00 25681.07 41666.76 0.00 1410.29 25851.00 6.93 0.00 72133.65 0.00
July 164973.54 07-JUL-14:30 25681.07 41659.26 0.00 1410.29 26873.16 6.93 0.00 66454.31 0.00
August 167162.25 16-AUG-15:09 25681.07 41670.51 0.00 1410.29 25716.61 6.91 0.00 68809.37 0.00
September 146285.10 07-SEP-15:20 25681.07 41670.51 0.00 1410.29 22350.69 6.91 0.00 51273.68 0.00
October 125216.37 04-OCT-15:30 25681.07 41670.51 0.00 1410.29 16575.60 6.89 0.00 35649.23 0.00
November 90373.31 06-NOV-16:49 32642.50 41670.51 5686.19 1410.29 4372.33 6.85 0.00 0.00 0.00
December 89784.10 21-DEC-16:40 32642.50 41670.51 5686.19 1410.29 3277.02 117.63 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 84014.12   25681.07 41659.26 0.00 1410.29 2710.75 6.85 0.00 0.00 0.00
Maximum of Months 171124.26   32642.50 41670.51 5686.19 1410.29 28390.86 638.95 0.00 72133.65 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 265742.95 02-JAN-07:19 0.00 0.00 0.00
February 0.00 0.00 252566.09 06-FEB-07:30 0.00 0.00 0.00
March 0.00 0.00 159731.49 20-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 120135.52 03-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 30993.37 01-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 738.27 02-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 14.04 10-JUL-16:40 0.00 0.00 0.00
August 0.00 0.00 15.28 29-AUG-11:50 0.00 0.00 0.00
September 0.00 0.00 4506.12 20-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 51015.77 28-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 184538.20 24-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 167048.17 11-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 14.04   0.00 0.00 0.00
Maximum of Months 0.00 0.00 265742.95   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.67 19.36 2.67 19.36 0.00 19.36 0.00 19.36
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 26.19 0.00 26.19
August 0.00 0.00 0.00 0.00 0.17 26.28 0.00 26.28
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.67 19.36 2.67 19.36 0.33 19.76 0.00 19.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.67 19.36 2.67 19.36 0.17 26.28 0.00 26.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.17 18.81 3.50 18.98 0.00 18.98 0.00 18.98
February 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4.33 18.84 3.67 19.00 0.00 19.00 0.00 19.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.17 19.43 3.50 19.43 0.00 19.43 0.00 19.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.33 18.65 4.33 18.87 0.00 18.87 0.00 18.87
February 2.33 19.28 2.17 19.40 0.00 19.40 0.00 19.40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.31 0.33 19.31 0.00 19.31 0.00 19.31
December 0.33 19.13 0.33 19.13 0.00 19.13 0.00 19.13
                 
Annual Sum or Average 8.33 18.87 7.17 19.05 0.00 19.05 0.00 19.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.33 19.31 4.33 19.40 0.00 19.40 0.00 19.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.17 16.73 13.33 17.16 0.00 17.16 0.00 17.16
February 17.17 17.48 9.33 18.09 0.00 18.09 0.00 18.09
March 0.83 18.49 0.50 18.83 0.00 18.83 0.00 18.83
April 0.17 19.32 0.17 19.32 0.00 19.32 0.00 19.32
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.17 27.37 2.00 27.37
August 0.00 0.00 0.00 0.00 1.33 27.45 1.17 27.46
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.33 17.92 1.17 18.40 0.00 18.40 0.00 18.40
December 3.17 17.41 1.67 18.06 0.00 18.06 0.00 18.06
                 
Annual Sum or Average 46.83 17.15 26.17 17.66 3.50 18.10 3.17 18.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23.17 19.32 13.33 19.32 2.17 27.45 2.00 27.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.50 15.86 5.67 16.25 0.00 16.25 0.00 16.25
February 10.67 16.54 3.33 17.19 0.00 17.19 0.00 17.19
March 0.50 17.16 0.00 17.16 0.00 17.16 0.00 17.16
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.83 27.90 4.83 27.90
June 0.00 0.00 0.00 0.00 3.00 27.75 3.00 27.75
July 0.00 0.00 0.00 0.00 10.33 27.83 10.17 27.83
August 0.00 0.00 0.00 0.00 5.67 27.79 5.50 27.80
September 0.00 0.00 0.00 0.00 4.33 27.94 4.33 27.94
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 17.74 0.33 18.14 0.00 18.14 0.00 18.14
December 2.00 16.09 0.33 16.50 0.00 16.50 0.00 16.50
                 
Annual Sum or Average 30.67 16.19 9.67 16.66 28.17 21.26 27.83 23.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16.50 17.74 5.67 18.14 10.33 27.94 10.17 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.67 16.36 6.00 16.86 0.00 16.86 0.00 16.86
February 8.33 17.31 4.00 17.97 0.00 17.97 0.00 17.97
March 0.17 17.23 0.00 17.23 0.00 17.23 0.00 17.23
April 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
May 0.00 0.00 0.00 0.00 3.00 27.67 3.00 27.67
June 0.00 0.00 0.00 0.00 2.50 27.52 2.50 27.52
July 0.00 0.00 0.00 0.00 8.17 27.72 8.00 27.72
August 0.00 0.00 0.00 0.00 5.33 27.95 5.00 27.97
September 0.00 0.00 0.00 0.00 5.83 28.16 5.67 28.17
October 0.00 0.00 0.00 0.00 2.67 27.83 2.67 27.83
November 0.67 18.14 0.33 18.52 0.00 18.52 0.00 18.52
December 1.00 16.65 0.33 17.21 0.00 17.21 0.00 17.21
                 
Annual Sum or Average 24.83 16.74 10.67 17.31 27.67 21.92 27.00 23.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.86 0.00 16.86
Maximum of Months 14.67 18.14 6.00 18.52 8.17 28.16 8.00 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.67 15.99 7.50 16.30 0.00 16.30 0.00 16.30
February 11.17 16.75 4.17 17.43 0.00 17.43 0.00 17.43
March 0.17 17.11 0.00 17.11 0.00 17.11 0.00 17.11
April 0.00 0.00 0.00 0.00 0.67 27.86 0.50 27.85
May 0.00 0.00 0.00 0.00 4.00 27.77 3.50 27.80
June 0.00 0.00 0.00 0.00 4.50 28.13 3.00 28.19
July 0.00 0.00 0.00 0.00 7.50 28.20 4.83 28.27
August 0.00 0.00 0.00 0.00 3.33 28.26 2.50 28.29
September 0.00 0.00 0.00 0.00 3.67 28.22 2.83 28.24
October 0.00 0.00 0.00 0.00 0.50 27.62 0.50 27.62
November 1.00 17.76 0.33 18.16 0.00 18.16 0.00 18.16
December 2.00 15.94 0.50 16.29 0.00 16.29 0.00 16.29
                 
Annual Sum or Average 31.00 16.32 12.50 16.76 24.17 20.81 17.67 22.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.29 0.00 16.29
Maximum of Months 16.67 17.76 7.50 18.16 7.50 28.26 4.83 28.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.50 17.45 10.33 17.93 0.00 17.93 0.00 17.93
February 4.83 19.26 4.17 19.43 0.00 19.43 0.00 19.43
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 20.33 17.88 14.50 18.32 0.00 18.32 0.00 18.32
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15.50 19.26 10.33 19.43 0.00 19.43 0.00 19.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.00 16.31 3.17 16.87 0.00 16.87 0.00 16.87
February 0.83 18.60 0.50 19.00 0.00 19.00 0.00 19.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.17 27.67 2.17 27.67
June 0.00 0.00 0.00 0.00 1.33 27.60 1.33 27.60
July 0.00 0.00 0.00 0.00 4.83 27.67 4.83 27.67
August 0.00 0.00 0.00 0.00 3.50 27.58 3.50 27.58
September 0.00 0.00 0.00 0.00 4.17 27.74 4.17 27.74
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 8.83 16.53 3.67 17.10 16.00 23.03 16.00 24.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.00 18.60 3.17 19.00 4.83 27.74 4.83 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 78.17 17.74 75.83 17.77 0.00 17.77 0.00 17.77
February 65.00 17.63 64.83 17.63 0.00 17.63 0.00 17.63
March 48.17 18.59 48.17 18.59 0.00 18.59 0.00 18.59
April 20.50 19.31 20.50 19.31 0.00 19.31 0.00 19.31
May 1.83 20.04 1.83 20.04 0.33 20.65 0.33 21.17
June 0.00 0.00 0.00 0.00 1.00 25.55 1.00 25.55
July 0.00 0.00 0.00 0.00 5.17 26.24 5.17 26.24
August 0.00 0.00 0.00 0.00 10.83 25.86 10.67 25.85
September 0.00 0.00 0.00 0.00 7.67 27.13 7.50 27.13
October 3.17 20.27 3.17 20.27 5.33 23.61 5.33 24.86
November 31.00 19.06 31.00 19.06 0.00 19.06 0.00 19.06
December 54.33 18.41 54.33 18.41 0.17 18.43 0.17 18.44
                 
Annual Sum or Average 302.17 18.25 299.67 18.27 30.50 18.67 30.17 19.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.63 0.00 17.63
Maximum of Months 78.17 20.27 75.83 20.27 10.83 27.13 10.67 27.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.50 16.80 5.67 17.35 0.00 17.35 0.00 17.35
February 1.83 19.20 1.33 19.54 0.00 19.54 0.00 19.54
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.39 0.33 27.39
May 0.00 0.00 0.00 0.00 0.50 27.36 0.50 27.36
June 0.00 0.00 0.00 0.00 3.17 27.69 2.33 27.70
July 0.00 0.00 0.00 0.00 5.17 27.78 3.50 27.80
August 0.00 0.00 0.00 0.00 2.67 27.86 1.83 27.88
September 0.00 0.00 0.00 0.00 3.17 27.90 2.50 27.90
October 0.00 0.00 0.00 0.00 0.50 27.47 0.50 27.47
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12.33 17.15 7.00 17.71 15.50 22.18 11.50 23.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.50 19.20 5.67 19.54 5.17 27.90 3.50 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.33 16.84 8.00 17.30 0.00 17.30 0.00 17.30
February 5.33 18.81 4.17 19.11 0.00 19.11 0.00 19.11
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 27.28 0.67 27.28
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.42 0.17 19.42 0.00 19.42 0.00 19.42
December 0.17 19.33 0.17 19.33 0.00 19.33 0.00 19.33
                 
Annual Sum or Average 19.00 17.43 12.50 17.89 0.67 18.08 0.67 18.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13.33 19.42 8.00 19.42 0.67 27.28 0.67 27.28



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.50 16.17 3.33 16.67 0.00 16.67 0.00 16.67
February 1.50 17.57 0.67 18.16 0.00 18.16 0.00 18.16
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.36 0.17 27.36
May 0.00 0.00 0.00 0.00 4.83 27.88 4.83 27.88
June 0.00 0.00 0.00 0.00 2.67 27.78 2.67 27.78
July 0.00 0.00 0.00 0.00 7.17 27.90 7.17 27.90
August 0.00 0.00 0.00 0.00 4.17 27.84 4.17 27.84
September 0.00 0.00 0.00 0.00 4.17 27.99 4.17 27.99
October 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10.00 16.38 4.00 16.90 23.33 23.76 23.33 25.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.50 17.57 3.33 18.16 7.17 27.99 7.17 27.99



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.83 16.28 3.00 16.87 0.00 16.87 0.00 16.87
February 1.50 18.71 1.00 19.06 0.00 19.06 0.00 19.06
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.50 27.56 2.50 27.56
June 0.00 0.00 0.00 0.00 1.50 27.40 1.50 27.40
July 0.00 0.00 0.00 0.00 6.33 27.62 6.33 27.62
August 0.00 0.00 0.00 0.00 4.67 27.86 4.50 27.86
September 0.00 0.00 0.00 0.00 6.17 28.03 6.17 28.03
October 0.00 0.00 0.00 0.00 5.00 27.70 5.00 27.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.50 27.34 0.50 27.34
                 
Annual Sum or Average 9.33 16.67 4.00 17.28 26.67 24.26 26.50 25.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.83 18.71 3.00 19.06 6.33 28.03 6.33 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.00 16.34 4.67 16.80 0.00 16.80 0.00 16.80
February 2.50 17.94 1.33 18.62 0.00 18.62 0.00 18.62
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.99 0.33 28.02
May 0.00 0.00 0.00 0.00 3.67 27.67 3.33 27.68
June 0.00 0.00 0.00 0.00 4.17 27.99 2.83 28.03
July 0.00 0.00 0.00 0.00 6.83 28.03 4.50 28.09
August 0.00 0.00 0.00 0.00 3.17 28.06 2.50 28.08
September 0.00 0.00 0.00 0.00 3.17 28.22 2.50 28.24
October 0.00 0.00 0.00 0.00 0.50 27.68 0.50 27.68
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 12.50 16.66 6.00 17.18 22.00 23.05 16.50 24.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.00 17.94 4.67 18.62 6.83 28.22 4.50 28.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.67 22.80 42.67 22.56 42.67 22.36
February 454.00 23.47 0.00 23.47 0.00 23.47
March 403.17 23.86 6.83 23.87 0.00 23.87
April 177.33 23.94 72.83 24.30 0.00 24.30
May 16.50 24.00 264.00 24.61 0.00 24.61
June 0.00 0.00 446.50 24.49 0.00 24.49
July 0.00 0.00 497.00 24.50 0.00 24.50
August 0.00 0.00 487.17 24.47 0.00 24.47
September 0.00 0.00 408.83 24.56 0.00 24.56
October 39.83 24.02 303.50 24.54 0.00 24.54
November 259.67 23.83 76.17 24.15 0.00 24.15
December 494.17 23.69 0.00 23.69 0.00 23.69
             
Annual Sum or Average 2343.33 23.53 2605.50 24.04 42.67 24.00
Minimum of Months 0.00 0.00 0.00 22.56 0.00 22.36
Maximum of Months 498.67 24.02 497.00 24.61 42.67 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.24 168.17 20.98 168.17 20.82
February 454.00 21.67 108.50 21.53 108.50 21.43
March 511.33 22.65 3.00 22.64 3.00 22.63
April 372.83 23.08 16.33 23.14 0.00 23.14
May 148.83 23.53 143.83 23.88 0.00 23.88
June 0.00 0.00 415.33 24.29 0.00 24.29
July 0.00 0.00 496.50 24.32 0.00 24.32
August 0.00 0.00 462.00 24.34 0.00 24.34
September 36.00 23.60 316.67 24.28 0.00 24.28
October 186.33 23.60 196.33 23.93 0.00 23.93
November 446.50 22.66 27.67 22.57 23.83 22.49
December 497.00 21.83 47.17 21.73 47.17 21.64
             
Annual Sum or Average 3154.83 22.32 2401.50 22.94 350.67 22.80
Minimum of Months 0.00 0.00 3.00 20.98 0.00 20.82
Maximum of Months 511.33 23.60 496.50 24.34 168.17 24.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.63 298.67 20.42 298.67 20.32
February 454.00 20.95 275.67 20.78 275.67 20.70
March 512.67 21.90 66.50 21.74 66.50 21.62
April 404.17 22.53 27.17 22.50 15.50 22.43
May 217.67 23.28 115.50 23.60 0.00 23.60
June 16.17 23.55 388.67 24.23 0.00 24.23
July 0.00 0.00 490.67 24.33 0.00 24.33
August 2.00 23.56 442.83 24.32 0.00 24.32
September 89.17 23.28 259.17 24.01 0.00 24.01
October 291.83 23.02 129.00 23.32 3.67 23.30
November 477.00 21.83 101.50 21.58 101.50 21.40
December 497.00 20.98 265.17 20.78 265.17 20.68
             
Annual Sum or Average 3463.67 21.75 2860.50 22.25 1026.67 21.99
Minimum of Months 0.00 0.00 27.17 20.42 0.00 20.32
Maximum of Months 512.67 23.56 490.67 24.33 298.67 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.97 437.67 19.90 437.67 19.87
February 454.00 20.14 416.83 20.10 416.83 20.08
March 513.17 20.99 248.83 20.76 248.83 20.65
April 416.67 21.77 99.33 21.65 76.33 21.46
May 250.33 22.94 126.50 23.38 7.67 23.38
June 32.50 24.15 403.50 24.29 10.83 24.32
July 42.33 26.07 496.17 24.60 42.33 24.71
August 37.67 25.19 446.83 24.44 23.17 24.52
September 148.67 23.10 247.83 23.82 5.83 23.84
October 354.00 22.25 123.67 22.41 37.17 22.26
November 489.00 20.93 226.83 20.66 226.83 20.51
December 497.00 20.17 460.33 20.13 460.33 20.12
             
Annual Sum or Average 3737.33 21.18 3734.33 21.67 1993.83 21.38
Minimum of Months 32.50 19.97 99.33 19.90 5.83 19.87
Maximum of Months 513.17 26.07 496.17 24.60 460.33 24.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.04 413.00 19.93 413.00 19.88
February 454.00 20.35 367.17 20.25 367.17 20.21
March 499.67 21.26 179.50 20.95 179.50 20.78
April 356.50 21.80 129.00 22.05 54.50 21.87
May 230.33 22.98 203.17 23.70 16.50 23.81
June 47.50 24.59 413.33 24.38 20.50 24.46
July 66.33 26.49 487.83 24.77 66.33 24.95
August 45.50 26.01 472.67 24.55 37.00 24.69
September 144.83 23.38 298.00 24.07 22.67 24.19
October 295.67 22.33 148.83 22.76 21.17 22.64
November 482.17 21.07 189.00 20.77 189.00 20.60
December 497.00 20.29 406.00 20.20 406.00 20.17
             
Annual Sum or Average 3621.50 21.35 3707.50 21.93 1793.33 21.67
Minimum of Months 45.50 20.04 129.00 19.93 16.50 19.88
Maximum of Months 502.00 26.49 487.83 24.77 413.00 24.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 486.50 20.52 323.67 20.20 323.67 20.06
February 423.17 20.94 282.33 20.66 278.83 20.51
March 423.00 21.30 189.50 21.16 160.33 20.97
April 350.17 21.79 131.83 22.02 58.83 21.83
May 240.17 22.89 174.50 23.51 11.67 23.56
June 53.83 24.25 398.67 24.31 18.83 24.38
July 58.67 26.27 489.00 24.68 57.50 24.84
August 51.17 25.69 462.83 24.55 37.00 24.69
September 126.67 23.74 322.33 24.23 27.33 24.37
October 208.83 22.57 250.67 23.41 29.17 23.35
November 408.67 21.35 174.50 21.16 145.83 20.94
December 457.50 20.82 312.67 20.59 304.83 20.45
             
Annual Sum or Average 3288.33 21.63 3512.50 22.24 1453.83 21.97
Minimum of Months 51.17 20.52 131.83 20.20 11.67 20.06
Maximum of Months 486.50 26.27 489.00 24.68 323.67 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.11 405.50 19.98 405.50 19.93
February 453.83 20.41 367.67 20.26 367.67 20.20
March 468.17 21.06 219.00 20.88 209.00 20.74
April 380.83 21.59 129.00 21.72 72.83 21.55
May 269.00 22.80 170.00 23.41 16.33 23.50
June 65.33 24.18 397.50 24.32 22.50 24.41
July 52.17 26.21 475.00 24.65 50.00 24.80
August 52.17 25.03 459.83 24.47 29.33 24.58
September 166.17 23.08 253.33 23.83 17.83 23.94
October 316.17 22.09 157.00 22.51 33.83 22.37
November 475.50 20.87 216.50 20.62 215.67 20.49
December 497.00 20.32 413.83 20.22 413.83 20.18
             
Annual Sum or Average 3698.33 21.27 3664.17 21.81 1854.33 21.55
Minimum of Months 52.17 20.11 129.00 19.98 16.33 19.93
Maximum of Months 502.00 26.21 475.00 24.65 413.83 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.29 418.67 20.22 418.67 20.19
February 454.00 20.46 413.00 20.43 413.00 20.42
March 514.00 21.05 235.17 20.91 235.17 20.83
April 466.33 21.94 43.83 21.82 43.17 21.71
May 344.67 23.04 64.17 23.21 3.17 23.22
June 26.17 24.00 379.33 24.22 5.17 24.23
July 13.83 25.72 496.67 24.42 13.83 24.46
August 12.17 25.85 462.67 24.37 11.00 24.41
September 86.33 23.44 295.17 24.08 0.17 24.08
October 279.67 23.02 131.67 23.35 0.00 23.35
November 487.33 21.74 121.17 21.49 121.17 21.33
December 497.00 20.66 391.50 20.61 391.50 20.58
             
Annual Sum or Average 3683.50 21.47 3453.00 21.95 1656.00 21.68
Minimum of Months 12.17 20.29 43.83 20.22 0.00 20.19
Maximum of Months 514.00 25.85 496.67 24.42 418.67 24.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.40 384.83 20.29 384.83 20.25
February 454.00 20.73 333.17 20.62 333.17 20.58
March 510.83 21.53 114.83 21.33 114.83 21.19
April 369.67 22.17 61.00 22.34 17.83 22.25
May 223.83 22.96 158.83 23.67 4.33 23.71
June 14.83 25.23 433.00 24.38 8.50 24.42
July 36.00 26.55 496.83 24.66 36.00 24.78
August 23.83 26.60 499.33 24.54 23.83 24.63
September 62.67 24.21 369.50 24.42 16.00 24.50
October 178.67 23.24 215.33 23.78 0.17 23.78
November 443.17 21.90 88.67 21.70 84.50 21.54
December 497.00 20.90 272.00 20.75 272.00 20.68
             
Annual Sum or Average 3316.50 21.62 3427.33 22.33 1296.00 22.08
Minimum of Months 14.83 20.40 61.00 20.29 0.17 20.25
Maximum of Months 510.83 26.60 499.33 24.66 384.83 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.33 20.22 320.50 19.94 320.50 19.82
February 445.00 20.67 268.00 20.40 263.17 20.25
March 481.50 21.26 118.83 20.99 114.17 20.79
April 396.50 21.75 79.83 21.84 39.00 21.69
May 324.83 22.60 89.50 23.01 13.83 23.01
June 95.67 23.65 394.00 24.15 65.67 24.12
July 93.67 24.61 493.83 24.50 93.67 24.51
August 60.33 25.07 490.00 24.53 57.00 24.59
September 95.67 24.07 388.00 24.43 48.33 24.50
October 130.17 23.23 313.00 24.16 14.83 24.22
November 393.00 21.67 96.67 21.64 62.00 21.44
December 471.33 20.96 237.17 20.77 225.83 20.60
             
Annual Sum or Average 3487.00 21.59 3289.33 22.28 1318.00 22.05
Minimum of Months 60.33 20.22 79.83 19.94 13.83 19.82
Maximum of Months 499.33 25.07 493.83 24.53 320.50 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.43 379.83 20.31 379.83 20.26
February 454.00 20.73 347.83 20.61 347.83 20.56
March 497.83 21.49 141.00 21.32 137.33 21.20
April 394.67 22.05 68.67 22.17 29.00 22.07
May 254.67 22.91 141.67 23.47 0.00 23.47
June 24.00 25.12 432.50 24.41 13.33 24.47
July 33.67 26.58 494.83 24.64 33.67 24.75
August 19.83 26.56 497.67 24.52 19.83 24.60
September 70.17 23.89 344.33 24.32 12.50 24.39
October 183.33 23.14 226.50 23.75 0.50 23.75
November 466.50 21.73 103.67 21.51 103.33 21.36
December 497.00 20.86 324.33 20.74 324.33 20.69
             
Annual Sum or Average 3397.67 21.59 3502.83 22.26 1401.50 22.01
Minimum of Months 19.83 20.43 68.67 20.31 0.00 20.26
Maximum of Months 502.00 26.58 497.67 24.64 379.83 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.24 388.50 20.13 388.50 20.09
February 454.00 20.48 372.67 20.41 372.67 20.38
March 512.00 21.37 145.67 21.18 145.67 21.06
April 408.33 22.23 45.50 22.23 23.50 22.13
May 196.33 23.27 135.17 23.68 0.00 23.68
June 12.67 24.85 428.00 24.33 7.83 24.35
July 26.00 25.98 497.00 24.56 26.00 24.62
August 19.17 26.16 471.00 24.45 18.00 24.52
September 102.00 23.43 290.00 24.06 5.00 24.08
October 291.33 22.79 125.67 23.15 3.00 23.13
November 485.67 21.49 146.17 21.21 146.17 21.04
December 497.00 20.54 389.00 20.46 389.00 20.43
             
Annual Sum or Average 3506.50 21.45 3434.33 22.02 1525.33 21.74
Minimum of Months 12.67 20.24 45.50 20.13 0.00 20.09
Maximum of Months 512.00 26.16 497.00 24.56 389.00 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.18 329.83 20.05 329.83 20.00
February 385.00 20.65 275.67 20.50 275.67 20.44
March 419.50 21.47 107.67 21.25 106.50 21.10
April 305.67 22.11 70.33 22.44 13.17 22.36
May 183.50 23.28 164.17 23.93 14.00 24.05
June 24.83 25.49 355.17 24.51 16.67 24.59
July 52.17 26.58 420.50 24.84 52.17 25.01
August 32.33 26.59 403.00 24.66 31.33 24.80
September 105.83 23.74 263.67 24.29 19.67 24.41
October 234.83 22.74 121.83 23.24 4.33 23.23
November 398.67 21.43 120.00 21.18 117.50 21.01
December 422.00 20.61 293.67 20.47 293.67 20.42
             
Annual Sum or Average 2991.33 21.59 2925.50 22.20 1274.50 21.96
Minimum of Months 24.83 20.18 70.33 20.05 4.33 20.00
Maximum of Months 427.00 26.59 420.50 24.84 329.83 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 478.00 20.84 270.33 20.52 268.00 20.36
February 408.67 21.34 216.83 21.08 209.33 20.91
March 412.33 21.77 108.33 21.73 77.67 21.56
April 329.50 22.26 91.33 22.60 16.17 22.51
May 189.17 23.24 189.83 23.82 5.17 23.86
June 26.33 24.94 431.50 24.37 14.50 24.43
July 49.83 26.42 496.33 24.69 49.83 24.83
August 35.50 26.56 482.67 24.59 34.17 24.72
September 82.83 24.42 361.50 24.44 27.00 24.58
October 166.67 23.28 277.17 24.01 11.17 24.09
November 379.33 21.88 123.50 21.84 79.50 21.62
December 443.33 21.27 229.83 21.07 219.00 20.90
             
Annual Sum or Average 3001.50 21.97 3279.17 22.68 1011.50 22.47
Minimum of Months 26.33 20.84 91.33 20.52 5.17 20.36
Maximum of Months 478.00 26.56 496.33 24.69 268.00 24.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.39 355.83 20.22 355.83 20.15
February 452.83 20.75 319.50 20.58 319.50 20.50
March 460.17 21.41 133.83 21.28 122.83 21.16
April 370.17 22.03 84.67 22.26 27.00 22.17
May 212.67 23.13 191.67 23.73 11.00 23.81
June 36.00 25.07 424.83 24.42 20.17 24.50
July 43.17 26.48 493.33 24.65 43.17 24.79
August 31.83 26.09 476.67 24.52 26.50 24.63
September 114.17 23.48 307.50 24.11 16.67 24.21
October 256.83 22.64 175.50 23.24 5.00 23.23
November 468.83 21.37 138.33 21.13 137.17 20.98
December 497.00 20.71 347.83 20.58 347.83 20.52
             
Annual Sum or Average 3445.67 21.55 3449.50 22.19 1432.67 21.95
Minimum of Months 31.83 20.39 84.67 20.22 5.00 20.15
Maximum of Months 502.00 26.48 493.33 24.65 355.83 24.79



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.80665 23.72292 -0.1371 7.68573
February 454.00000 23.46534 19.68350 0.00654 5.40709
March 514.00000 23.97282 26.84726 0.20867 6.16306
April 485.00000 24.23537 32.29948 0.33701 7.72515
May 508.00000 24.37630 39.70060 -0.3997 8.83763
June 496.00000 24.44127 49.03738 -0.2683 7.09170
July 497.00000 24.49827 52.37296 -0.2168 6.57440
August 514.00000 24.44980 49.21125 -0.2469 6.93871
September 485.00000 24.47822 44.94791 -0.2927 7.44086
October 502.00000 24.44829 38.44955 0.47736 10.27219
November 489.00000 24.14020 29.55774 0.27810 7.30395
December 497.00000 23.69362 22.50283 0.09128 5.38091
           
Annual Sum or Average 5943.00000 24.08758 35.81750 -0.0146 7.24885
Minimum of Months 454.00000 22.80665 19.68350 -0.3997 5.38091
Maximum of Months 514.00000 24.49827 52.37296 0.47736 10.27219



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.23541 25.75350 -0.4896 11.95648
February 454.00000 21.66987 21.62579 -0.3993 9.01871
March 514.00000 22.65653 29.62278 -0.0909 5.94634
April 485.00000 23.31902 34.90758 0.12478 6.28976
May 508.00000 23.96816 41.45117 -0.5496 11.89868
June 496.00000 24.24739 49.96142 -0.3550 7.97158
July 497.00000 24.31711 53.74684 -0.2916 7.10432
August 514.00000 24.30670 50.52695 -0.3138 7.48153
September 485.00000 24.19679 46.04267 -0.4139 9.09489
October 502.00000 23.94890 40.01500 0.33939 8.07829
November 489.00000 22.78331 32.76785 -0.0407 6.68719
December 497.00000 21.83447 25.17790 -0.3300 7.94660
           
Annual Sum or Average 5943.00000 23.21821 37.75515 -0.2337 8.28945
Minimum of Months 454.00000 21.23541 21.62579 -0.5496 5.94634
Maximum of Months 514.00000 24.31711 53.74684 0.33939 11.95648



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.62664 26.58911 -0.6586 16.45702
February 454.00000 20.94746 21.83507 -0.6002 13.81210
March 514.00000 21.90192 30.66829 -0.2774 7.91371
April 485.00000 22.77979 35.91495 -0.0061 6.71006
May 508.00000 23.74605 42.09655 -0.6216 14.15217
June 496.00000 24.18879 49.97687 -0.3677 8.20675
July 497.00000 24.32069 53.60868 -0.2793 6.94211
August 514.00000 24.28004 50.40360 -0.3153 7.51566
September 485.00000 24.01285 46.21989 -0.4803 10.64959
October 502.00000 23.43244 41.25476 0.21143 7.36395
November 489.00000 21.88043 34.35782 -0.2684 8.68989
December 497.00000 20.97702 26.03819 -0.5599 12.76861
           
Annual Sum or Average 5943.00000 22.77181 38.37054 -0.3507 10.07645
Minimum of Months 454.00000 20.62664 21.83507 -0.6586 6.71006
Maximum of Months 514.00000 24.32069 53.60868 0.21143 16.45702



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.97405 28.14739 -0.8718 23.70467
February 454.00000 20.13708 22.98423 -0.8505 22.37980
March 514.00000 20.99458 32.74786 -0.5146 12.40611
April 485.00000 22.09572 37.73291 -0.1725 8.51212
May 508.00000 23.55226 43.17048 -0.6767 16.94468
June 496.00000 24.21307 51.21084 -0.3189 7.93413
July 497.00000 24.47523 55.30794 -0.1678 6.55755
August 514.00000 24.31341 51.67634 -0.2589 7.36757
September 485.00000 23.83032 48.13660 -0.5296 12.71314
October 502.00000 22.74947 43.57043 0.05021 7.95311
November 489.00000 20.92763 36.34968 -0.5173 13.30401
December 497.00000 20.16705 27.94787 -0.8025 20.38523
           
Annual Sum or Average 5943.00000 22.30303 40.04076 -0.4667 13.28454
Minimum of Months 454.00000 19.97405 22.98423 -0.8718 6.55755
Maximum of Months 514.00000 24.47523 55.30794 0.05021 23.70467



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.03606 27.62384 -0.8375 22.59736
February 454.00000 20.34988 22.37095 -0.7699 19.59289
March 514.00000 21.33408 31.76391 -0.4051 11.12954
April 485.00000 22.46251 36.32523 -0.0518 8.70173
May 508.00000 23.63824 42.54009 -0.5708 15.77346
June 496.00000 24.22640 50.88210 -0.2501 7.78048
July 497.00000 24.51358 54.71306 -0.0870 6.84942
August 514.00000 24.35579 51.08729 -0.1508 6.91544
September 485.00000 23.93092 47.44314 -0.4264 11.88148
October 502.00000 23.03047 42.39072 0.15506 8.39389
November 489.00000 21.11221 35.57139 -0.4514 12.26609
December 497.00000 20.29202 27.35928 -0.7527 18.73373
           
Annual Sum or Average 5943.00000 22.45674 39.29819 -0.3806 12.50138
Minimum of Months 454.00000 20.03606 22.37095 -0.8375 6.84942
Maximum of Months 514.00000 24.51358 54.71306 0.15506 22.59736



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.63380 26.81324 -0.6662 19.32972
February 454.00000 21.17393 21.30998 -0.5481 15.97085
March 514.00000 21.79205 30.53661 -0.2813 10.65295
April 485.00000 22.48790 36.10317 -0.0482 9.01929
May 508.00000 23.55299 42.74358 -0.6384 16.98790
June 496.00000 24.18728 51.04570 -0.3014 8.22278
July 497.00000 24.47707 54.96626 -0.1345 6.78455
August 514.00000 24.35961 51.02333 -0.1652 7.10346
September 485.00000 24.04845 46.84250 -0.3632 10.99449
October 502.00000 23.53805 40.63074 0.31276 10.48449
November 489.00000 21.79417 34.02976 -0.2692 10.88469
December 497.00000 21.11975 26.14713 -0.5318 15.41643
           
Annual Sum or Average 5943.00000 22.77639 38.64519 -0.3015 11.79805
Minimum of Months 454.00000 20.63380 21.30998 -0.6662 6.78455
Maximum of Months 514.00000 24.47707 54.96626 0.31276 19.32972



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.11181 27.30788 -0.8289 22.41934
February 454.00000 20.40827 22.12695 -0.7702 20.37299
March 514.00000 21.32743 31.40537 -0.4090 11.61769
April 485.00000 22.15189 36.90235 -0.1206 9.24791
May 508.00000 23.40906 43.17434 -0.6501 18.07593
June 496.00000 24.16078 51.00796 -0.2618 8.35964
July 497.00000 24.43557 54.93152 -0.1149 7.02137
August 514.00000 24.30971 51.27248 -0.1677 7.26193
September 485.00000 23.74325 47.91834 -0.4872 13.37811
October 502.00000 22.81648 42.77400 0.11226 8.74467
November 489.00000 20.95326 35.65541 -0.4974 13.02768
December 497.00000 20.32425 27.11066 -0.7560 19.05837
           
Annual Sum or Average 5943.00000 22.36233 39.42523 -0.4100 13.16381
Minimum of Months 454.00000 20.11181 22.12695 -0.8289 7.02137
Maximum of Months 514.00000 24.43557 54.93152 0.11226 22.41934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.28749 27.88940 -0.7739 19.42451
February 454.00000 20.46117 23.00572 -0.7565 18.06129
March 514.00000 21.04687 32.86556 -0.4968 10.99982
April 485.00000 22.02050 38.33086 -0.1975 7.42107
May 508.00000 23.36739 44.03711 -0.7764 19.14006
June 496.00000 24.16000 51.52738 -0.3787 8.41809
July 497.00000 24.38553 54.52697 -0.2411 6.67588
August 514.00000 24.29840 50.92236 -0.2934 7.28994
September 485.00000 24.06813 47.57387 -0.4531 10.04579
October 502.00000 23.43506 42.09239 0.21625 7.26204
November 489.00000 21.74168 34.80506 -0.2908 8.68720
December 497.00000 20.66481 27.29199 -0.6363 14.02823
           
Annual Sum or Average 5943.00000 22.50955 39.69685 -0.4216 11.42610
Minimum of Months 454.00000 20.28749 23.00572 -0.7764 6.67588
Maximum of Months 514.00000 24.38553 54.52697 0.21625 19.42451



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.40171 27.80996 -0.7267 17.96934
February 454.00000 20.73110 22.76684 -0.6588 15.11910
March 514.00000 21.54514 32.09884 -0.3485 9.01491
April 485.00000 22.67077 36.52857 -0.0143 7.47433
May 508.00000 23.71260 42.70364 -0.5942 15.22360
June 496.00000 24.27633 50.89981 -0.2762 7.47667
July 497.00000 24.52353 53.76424 -0.1275 6.42848
August 514.00000 24.42447 50.11895 -0.1538 6.37893
September 485.00000 24.27509 46.68165 -0.3154 8.61400
October 502.00000 23.82114 40.63998 0.34656 8.68754
November 489.00000 22.10386 34.07412 -0.1863 8.06476
December 497.00000 20.90212 27.01377 -0.5604 12.32794
           
Annual Sum or Average 5943.00000 22.79679 38.87996 -0.2995 10.20843
Minimum of Months 454.00000 20.40171 22.76684 -0.7267 6.37893
Maximum of Months 514.00000 24.52353 53.76424 0.34656 17.96934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.24098 25.58326 -0.6969 18.32218
February 454.00000 20.76264 20.34877 -0.5764 15.14497
March 514.00000 21.43700 29.96424 -0.3263 9.69273
April 485.00000 22.22612 36.01911 -0.1006 8.07866
May 508.00000 23.20580 43.81669 -0.7763 20.46547
June 496.00000 24.13594 53.54375 -0.3423 8.40523
July 497.00000 24.47161 57.40891 -0.1571 6.32526
August 514.00000 24.42801 52.29290 -0.1510 6.45989
September 485.00000 24.29436 47.60500 -0.2619 8.43875
October 502.00000 24.08260 39.69752 0.47418 11.43104
November 489.00000 22.17627 31.82480 -0.1186 8.49045
December 497.00000 21.18527 24.37509 -0.4414 11.98796
           
Annual Sum or Average 5943.00000 22.73420 38.67957 -0.2885 11.09613
Minimum of Months 454.00000 20.24098 20.34877 -0.7763 6.32526
Maximum of Months 514.00000 24.47161 57.40891 0.47418 20.46547



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.42794 27.64659 -0.7272 18.11983
February 454.00000 20.73073 22.66671 -0.6693 15.80502
March 514.00000 21.56721 31.79924 -0.3439 9.19764
April 485.00000 22.45650 37.01854 -0.0639 7.56987
May 508.00000 23.58238 43.16962 -0.6468 16.31539
June 496.00000 24.30208 50.77013 -0.2587 7.38450
July 497.00000 24.50256 53.87829 -0.1359 6.47647
August 514.00000 24.42529 50.22634 -0.1554 6.40534
September 485.00000 24.19908 46.94461 -0.3448 8.94407
October 502.00000 23.79248 40.76919 0.34223 8.79702
November 489.00000 21.83375 34.45275 -0.2549 8.50161
December 497.00000 20.86056 26.95828 -0.5777 12.79136
           
Annual Sum or Average 5943.00000 22.73841 38.97930 -0.3177 10.49996
Minimum of Months 454.00000 20.42794 22.66671 -0.7272 6.40534
Maximum of Months 514.00000 24.50256 53.87829 0.34223 18.11983



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.24225 27.82730 -0.7700 19.68092
February 454.00000 20.48110 22.62855 -0.7288 17.56624
March 514.00000 21.38408 32.21901 -0.3944 9.60954
April 485.00000 22.51958 37.01716 -0.0613 7.14149
May 508.00000 23.79318 42.46816 -0.5986 13.78804
June 496.00000 24.27411 51.00646 -0.3058 7.48268
July 497.00000 24.48160 55.11789 -0.1791 6.47430
August 514.00000 24.34997 51.56730 -0.2559 7.10719
September 485.00000 24.02947 47.72084 -0.4607 10.48413
October 502.00000 23.28366 42.25796 0.18093 7.38515
November 489.00000 21.50962 35.30333 -0.3510 9.86198
December 497.00000 20.53882 27.36765 -0.6688 15.35453
           
Annual Sum or Average 5943.00000 22.58998 39.50058 -0.3808 10.95242
Minimum of Months 454.00000 20.24225 22.62855 -0.7700 6.47430
Maximum of Months 514.00000 24.48160 55.11789 0.18093 19.68092



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.18211 26.60200 -0.7729 19.95279
February 385.00000 20.64756 21.28392 -0.6715 16.01295
March 433.00000 21.55355 30.84591 -0.3344 9.30944
April 410.00000 22.69296 35.64103 0.00864 7.85987
May 430.00000 23.83168 41.72440 -0.5228 13.91287
June 418.00000 24.33460 50.20280 -0.2461 7.59739
July 422.00000 24.62022 54.19218 -0.0919 6.90438
August 433.00000 24.46223 50.83350 -0.1551 6.91077
September 410.00000 24.11672 46.98851 -0.3806 10.53981
October 427.00000 23.35988 41.02190 0.22804 8.05404
November 417.00000 21.54980 34.18199 -0.3268 9.72939
December 422.00000 20.61013 26.15764 -0.6420 14.79311
           
Annual Sum or Average 5034.00000 22.67610 38.41930 -0.3237 10.93819
Minimum of Months 385.00000 20.18211 21.28392 -0.7729 6.90438
Maximum of Months 433.00000 24.62022 54.19218 0.22804 19.95279



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.00292 26.44930 -0.5464 15.61698
February 454.00000 21.65110 20.88128 -0.4033 12.29732
March 514.00000 22.22914 29.92132 -0.1552 8.46492
April 485.00000 22.90864 35.38377 0.06088 7.90556
May 508.00000 23.83649 41.97807 -0.5500 13.44201
June 496.00000 24.28106 50.78977 -0.2801 7.52293
July 497.00000 24.51133 54.74069 -0.1387 6.60172
August 514.00000 24.41304 50.88411 -0.1595 6.72805
September 485.00000 24.24518 46.46985 -0.2976 9.01781
October 502.00000 23.93779 39.59352 0.41537 10.71100
November 489.00000 22.39648 32.94366 -0.1024 8.71878
December 497.00000 21.62936 25.46123 -0.3748 11.60801
           
Annual Sum or Average 5943.00000 23.09770 38.08733 -0.2102 9.87553
Minimum of Months 454.00000 21.00292 20.88128 -0.5500 6.60172
Maximum of Months 514.00000 24.51133 54.74069 0.41537 15.61698



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.38501 27.09703 -0.7263 18.61113
February 454.00000 20.76053 21.78155 -0.6479 15.95857
March 514.00000 21.68758 30.94823 -0.2957 9.23075
April 485.00000 22.54859 36.24423 -0.0154 7.97091
May 508.00000 23.70739 42.41603 -0.5577 14.27181
June 496.00000 24.26819 50.71361 -0.2373 7.52549
July 497.00000 24.48142 54.70898 -0.1159 6.71420
August 514.00000 24.37355 51.16817 -0.1585 6.78558
September 485.00000 23.99381 47.47829 -0.4059 10.67921
October 502.00000 23.33451 41.56618 0.23922 8.39275
November 489.00000 21.48260 34.74308 -0.3417 9.78889
December 497.00000 20.71074 26.57126 -0.6204 14.34405
           
Annual Sum or Average 5943.00000 22.65974 38.91266 -0.3215 10.82185
Minimum of Months 454.00000 20.38501 21.78155 -0.7263 6.71420
Maximum of Months 514.00000 24.48142 54.70898 0.23922 18.61113



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.738036E+11 0.00 463.46 211145.26 02-JAN-07:10 0.00 32.97 49.32 0.29 0.00 0.09 0.66 02-JAN-07:10
February 0.618109E+11 0.00 398.86 200587.76 06-FEB-07:30 0.00 32.58 48.28 0.27 0.00 0.08 0.63 06-FEB-07:30
March 0.246958E+11 0.00 339.97 206261.68 06-MAR-06:11 0.00 28.68 42.35 0.08 0.00 0.03 0.64 06-MAR-06:11
April 0.618166E+10 0.00 167.07 207581.85 03-APR-05:11 0.00 34.05 40.57 0.02 0.00 0.01 0.65 03-APR-05:11
May 0.423068E+09 0.00 36.83 45190.54 01-MAY-06:03 0.00 41.72 42.64 0.00 0.00 0.00 0.14 01-MAY-06:03
June 2812677.45 0.00 95.31 1229.05 02-JUN-06:08 0.00 38.17 41.07 0.00 0.00 0.00 0.00 02-JUN-06:08
July 3368631.21 0.00 171.81 8.43 10-JUL-16:40 0.00 37.39 42.61 0.00 0.00 0.00 0.00 10-JUL-16:40
August 3249335.25 0.00 162.59 9.18 29-AUG-11:50 0.00 36.40 41.54 0.00 0.00 0.00 0.00 29-AUG-11:50
September 13075727.64 0.00 65.11 12157.25 20-SEP-06:07 0.00 34.77 36.99 0.00 0.00 0.00 0.04 20-SEP-06:07
October 0.768345E+09 0.00 72.18 84439.24 28-OCT-06:03 0.00 35.92 38.32 0.00 0.00 0.00 0.26 28-OCT-06:03
November 0.193125E+11 0.00 265.63 190483.49 28-NOV-07:02 0.00 30.81 41.52 0.07 0.00 0.02 0.59 28-NOV-07:02
December 0.451710E+11 0.00 391.86 207245.41 26-DEC-06:11 0.00 29.76 45.31 0.15 0.00 0.05 0.65 26-DEC-06:11
                           
Annual Sum or Average 0.232189E+12 0.00 2630.69     0.00 34.45 42.52 0.07 0.00 0.02    
Minimum of Months 2812677.45 0.00 36.83 8.43   0.00 28.68 36.99 0.00 0.00 0.00 0.00  
Maximum of Months 0.738036E+11 0.00 463.46 211145.26   0.00 41.72 49.32 0.29 0.00 0.09 0.66  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.480296E+09 0.115264E+09 13.17 0.329552E+09 0.150744E+09 0.00 0.74 27-MAR-16:00 0.00 01-MAR-00:10 25145.19 27-MAR-16:00 21407.14 27-MAR-16:00 8262.95 27-MAR-12:55 5688.68 27-MAR-16:00 0.00
April 0.436067E+10 0.103530E+10 89.00 0.391833E+10 0.442342E+09 0.00 1.00 07-APR-12:40 0.00 01-APR-00:10 44998.31 07-APR-14:30 44998.31 07-APR-14:30 10287.89 10-APR-06:03 9955.62 07-APR-14:10 0.00
May 0.172057E+11 0.404619E+10 288.11 0.144808E+11 0.272485E+10 0.00 1.00 19-MAY-06:03 0.00 01-MAY-00:10 85699.67 30-MAY-14:10 85699.67 30-MAY-14:10 24876.25 19-MAY-06:03 20587.02 30-MAY-14:10 0.00
June 0.593883E+11 0.133045E+11 424.21 0.464830E+11 0.129053E+11 0.00 1.00 01-JUN-06:03 0.00 01-JUN-00:10 106194.62 19-JUN-06:03 83395.59 19-JUN-05:02 41634.40 27-JUN-06:03 26180.22 19-JUN-12:15 0.00
July 0.836518E+11 0.189611E+11 446.63 0.631085E+11 0.205433E+11 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 115440.44 14-JUL-06:03 86859.58 10-JUL-06:03 47460.87 28-JUL-06:03 24722.80 14-JUL-06:03 0.00
August 0.860507E+11 0.197621E+11 461.34 0.693264E+11 0.167243E+11 0.00 1.00 01-AUG-04:03 0.00 01-AUG-00:10 116417.14 17-AUG-06:03 89929.14 22-AUG-15:40 42993.89 17-AUG-06:03 25554.66 05-AUG-06:03 0.00
September 0.454007E+11 0.101092E+11 390.05 0.370196E+11 0.838111E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 115376.35 01-SEP-05:02 80401.11 01-SEP-05:02 39746.82 14-SEP-06:03 24459.95 01-SEP-05:02 0.00
October 0.201654E+11 0.447928E+10 227.75 0.141906E+11 0.597488E+10 0.00 1.00 02-OCT-12:40 0.00 01-OCT-00:10 66561.29 04-OCT-15:00 53569.83 04-OCT-15:30 37526.36 06-OCT-05:12 14092.05 04-OCT-15:00 0.00
November 0.453766E+09 0.117288E+09 24.89 0.371407E+09 82359292.96 0.00 0.37 03-NOV-14:10 0.00 01-NOV-00:10 11314.17 03-NOV-14:10 11314.17 03-NOV-14:10 4378.44 10-NOV-10:00 2822.66 03-NOV-14:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.317157E+12 0.719303E+11 2365.14 0.249228E+12 0.679293E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.860507E+11 0.197621E+11 461.34 0.693264E+11 0.205433E+11 0.00 1.00   0.00   116417.14   89929.14   47460.87   26180.22   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 60027.90 16253.76 0.02 60027.90 0.00 0.00 0.03 02-JAN-06:01 0.00 01-JAN-00:02 700.33 02-JAN-06:01 700.33 02-JAN-06:01 0.00 02-JAN-06:01 189.63 02-JAN-06:01 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.449706E+09 0.108468E+09 13.17 0.304998E+09 0.144708E+09 0.00 0.69 27-MAR-16:00 0.00 01-MAR-00:10 22303.67 27-MAR-16:00 18008.38 27-MAR-16:00 7868.36 27-MAR-13:00 5110.02 27-MAR-16:00 0.00
April 0.450032E+10 0.107006E+10 96.58 0.402596E+10 0.474353E+09 0.00 1.00 07-APR-12:10 0.00 01-APR-00:10 46458.30 07-APR-14:30 46458.30 07-APR-14:30 6383.68 09-APR-12:15 10244.51 07-APR-14:30 0.00
May 0.165630E+11 0.389414E+10 294.51 0.141352E+11 0.242783E+10 0.00 1.00 28-MAY-15:02 0.00 01-MAY-00:10 82754.46 30-MAY-14:10 82754.46 30-MAY-14:10 16651.25 18-MAY-15:00 19878.80 30-MAY-14:10 0.00
June 0.546259E+11 0.122888E+11 429.46 0.426732E+11 0.119527E+11 0.00 1.00 01-JUN-09:40 0.00 01-JUN-00:10 107167.47 19-JUN-06:03 77286.39 19-JUN-05:02 32973.97 19-JUN-06:03 23624.15 19-JUN-12:06 0.00
July 0.762030E+11 0.172787E+11 443.54 0.566184E+11 0.195846E+11 0.00 1.00 01-JUL-08:50 0.00 01-JUL-00:10 115304.64 22-JUL-05:03 79451.04 10-JUL-04:02 49645.12 22-JUL-05:03 24277.13 22-JUL-05:03 0.00
August 0.764348E+11 0.175683E+11 452.79 0.611104E+11 0.153244E+11 0.00 1.00 01-AUG-04:03 0.00 01-AUG-00:10 104777.71 03-AUG-05:03 87735.36 22-AUG-14:50 35536.92 03-AUG-05:03 22789.96 03-AUG-05:03 0.00
September 0.385929E+11 0.867246E+10 386.11 0.309400E+11 0.765286E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 104508.77 01-SEP-05:02 73650.77 01-SEP-05:02 30858.00 01-SEP-05:02 22169.95 01-SEP-05:02 0.00
October 0.167740E+11 0.376931E+10 229.64 0.118174E+11 0.495659E+10 0.00 1.00 03-OCT-10:10 0.00 01-OCT-00:10 59183.59 04-OCT-14:20 48017.97 04-OCT-15:00 22774.45 24-OCT-09:00 12618.78 04-OCT-14:20 0.00
November 0.408614E+09 0.105978E+09 25.17 0.339925E+09 68689287.49 0.00 0.32 03-NOV-14:00 0.00 01-NOV-00:10 9306.61 03-NOV-14:00 9306.61 03-NOV-14:00 3061.11 10-NOV-10:00 2349.74 03-NOV-14:00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.284552E+12 0.647562E+11 2371.00 0.221966E+12 0.625867E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.764348E+11 0.175683E+11 452.79 0.611104E+11 0.195846E+11 0.00 1.00   0.00   115304.64   87735.36   49645.12   24277.13   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 514452.69 139885.72 0.67 502690.23 11762.46 0.00 0.01 05-JAN-06:04 0.00 01-JAN-00:02 400.19 05-JAN-06:04 400.19 05-JAN-06:04 37.60 04-JAN-05:07 108.67 05-JAN-06:04 0.00
February 1227301.42 332511.22 0.83 1222621.05 4680.38 0.00 0.05 06-FEB-06:40 0.00 01-FEB-00:10 1380.29 06-FEB-06:40 1380.29 06-FEB-06:40 7.80 05-FEB-09:40 372.03 06-FEB-06:40 0.00
March 0.462149E+09 0.112321E+09 13.17 0.306395E+09 0.155754E+09 0.00 0.66 27-MAR-16:00 0.00 01-MAR-00:10 23281.53 27-MAR-16:00 18094.28 27-MAR-16:00 8338.84 27-MAR-13:00 5382.48 27-MAR-16:00 0.00
April 0.463038E+10 0.110674E+10 94.78 0.409484E+10 0.535532E+09 0.00 1.00 07-APR-12:10 0.00 01-APR-00:10 50818.60 07-APR-14:30 50818.60 07-APR-14:30 7966.68 09-APR-11:53 11206.27 07-APR-14:30 0.00
May 0.170751E+11 0.403912E+10 292.14 0.145997E+11 0.247547E+10 0.00 1.00 29-MAY-11:32 0.00 01-MAY-00:10 90306.82 30-MAY-14:00 90306.82 30-MAY-14:00 15467.98 18-MAY-15:00 21816.60 30-MAY-13:50 0.00
June 0.570648E+11 0.129232E+11 429.39 0.448740E+11 0.121908E+11 0.00 1.00 01-JUN-09:50 0.00 01-JUN-00:10 112179.76 19-JUN-05:02 84461.09 19-JUN-05:02 27718.67 19-JUN-05:02 26440.42 19-JUN-12:02 0.00
July 0.803071E+11 0.182688E+11 444.43 0.607047E+11 0.196025E+11 0.00 1.00 01-JUL-09:40 0.00 01-JUL-00:10 127937.44 22-JUL-05:03 89858.91 10-JUL-04:02 60536.10 22-JUL-05:03 26903.48 22-JUL-05:03 0.00
August 0.801762E+11 0.184968E+11 453.16 0.649410E+11 0.152352E+11 0.00 1.00 01-AUG-05:03 0.00 01-AUG-00:10 101500.32 03-AUG-05:03 95352.36 22-AUG-14:40 35897.91 03-AUG-05:03 24371.77 04-AUG-14:00 0.00
September 0.388269E+11 0.880735E+10 383.25 0.309019E+11 0.792498E+10 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 88982.47 01-SEP-14:00 88982.47 01-SEP-14:00 24793.22 14-SEP-12:20 22451.24 01-SEP-14:00 0.00
October 0.159999E+11 0.364224E+10 223.26 0.110901E+11 0.490978E+10 0.00 1.00 03-OCT-11:50 0.00 01-OCT-00:10 61376.47 04-OCT-13:50 52877.77 04-OCT-15:00 22119.42 24-OCT-09:50 13180.34 04-OCT-13:40 0.00
November 0.352766E+09 92224905.94 24.00 0.279540E+09 73225688.94 0.00 0.28 04-NOV-12:30 0.00 01-NOV-00:10 8792.09 04-NOV-12:30 7954.79 03-NOV-14:00 2707.69 10-NOV-10:00 2243.80 04-NOV-12:30 0.00
December 97798.81 26571.72 0.08 93122.71 4676.11 0.00 0.01 31-DEC-09:30 0.00 01-DEC-00:10 326.00 31-DEC-09:30 310.41 31-DEC-09:30 15.59 31-DEC-09:30 88.57 31-DEC-09:30 0.00
                                       
Annual Sum or Average 0.294897E+12 0.674893E+11 2359.16 0.231794E+12 0.631032E+11 0.00                         0.00
Minimum of Months 97798.81 26571.72 0.08 93122.71 4676.11 0.00 0.01   0.00   326.00   310.41   7.80   88.57   0.00
Maximum of Months 0.803071E+11 0.184968E+11 453.16 0.649410E+11 0.196025E+11 0.00 1.00   0.00   127937.44   95352.36   60536.10   26903.48   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 328.95 0.00 328.95 22.95 1771.10 0.00 0.00 0.00
February 450.15 0.00 450.15 44.91 1843.82 0.00 0.00 0.00
March 624.24 0.00 624.24 229.94 1226.95 0.00 0.00 0.00
April 749.80 2.13 747.67 480.34 875.67 0.00 0.00 0.00
May 994.74 33.15 961.60 934.08 550.04 0.00 0.00 0.00
June 1054.91 56.68 998.23 1304.96 305.49 0.00 0.00 0.00
July 1019.47 36.87 982.61 1451.38 172.51 0.00 0.00 0.00
August 903.20 10.75 892.45 1272.66 232.08 0.00 0.00 0.00
September 680.87 0.13 680.74 730.98 457.79 0.00 0.00 0.00
October 589.24 0.00 589.24 441.34 828.62 0.00 0.00 0.00
November 413.30 0.00 413.30 123.17 1241.62 0.00 0.00 0.00
December 286.93 0.00 286.93 15.61 1637.72 0.00 0.00 0.00
                 
Annual Sum or Average 675.95 11.70 664.24 591.36 923.38 0.00 0.00 0.00
Minimum of Months 286.93 0.00 286.93 15.61 172.51 0.00 0.00 0.00
Maximum of Months 1054.91 56.68 998.23 1451.38 1843.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 458.09 183.66 274.43 286.95 1097.30 0.00 0.00 0.00
February 710.40 331.40 379.00 504.55 1106.75 0.00 0.00 0.00
March 906.25 385.43 520.81 797.82 789.25 0.00 0.00 0.00
April 1087.56 476.38 611.17 1108.62 567.24 0.00 0.00 0.00
May 1318.98 527.14 791.84 1530.77 372.40 0.00 0.00 0.00
June 1222.42 442.51 779.91 1597.50 207.13 0.00 0.00 0.00
July 1227.77 443.07 784.70 1740.78 115.79 0.00 0.00 0.00
August 1382.50 623.37 759.13 1951.41 155.29 0.00 0.00 0.00
September 1031.07 462.60 568.47 1289.45 295.38 0.00 0.00 0.00
October 934.74 423.66 511.09 1042.96 535.56 0.00 0.00 0.00
November 578.07 221.98 356.08 473.72 778.63 0.00 0.00 0.00
December 450.35 211.46 238.89 310.15 1006.24 0.00 0.00 0.00
                 
Annual Sum or Average 943.84 394.84 549.01 1056.69 582.65 0.00 0.00 0.00
Minimum of Months 450.35 183.66 238.89 286.95 115.79 0.00 0.00 0.00
Maximum of Months 1382.50 623.37 791.84 1951.41 1106.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1701.70 1114.29 587.42 1684.20 1583.90 0.00 0.00 0.00
February 2244.49 1485.67 758.82 2256.52 1610.71 0.00 0.00 0.00
March 2024.95 1123.88 901.07 2154.88 1197.66 0.00 0.00 0.00
April 1571.29 621.34 949.96 1729.01 904.62 0.00 0.00 0.00
May 1377.00 287.22 1089.78 1604.99 589.96 0.00 0.00 0.00
June 1292.28 197.54 1094.74 1740.33 326.59 0.00 0.00 0.00
July 1354.57 235.29 1119.28 2026.77 177.04 0.00 0.00 0.00
August 1808.87 670.94 1137.93 2731.07 246.27 0.00 0.00 0.00
September 1962.66 1015.17 947.49 2625.60 471.22 0.00 0.00 0.00
October 2688.68 1686.00 1002.69 3352.72 836.25 0.00 0.00 0.00
November 1864.37 1119.64 744.73 2000.60 1170.72 0.00 0.00 0.00
December 1844.39 1309.40 535.00 1904.22 1453.51 0.00 0.00 0.00
                 
Annual Sum or Average 1809.23 902.59 906.64 2151.43 876.48 0.00 0.00 0.00
Minimum of Months 1292.28 197.54 535.00 1604.99 177.04 0.00 0.00 0.00
Maximum of Months 2688.68 1686.00 1137.93 3352.72 1610.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.24 185.24 267.00 283.59 1122.77 0.00 0.00 0.00
February 666.89 292.90 373.99 462.81 1156.40 0.00 0.00 0.00
March 984.74 454.63 530.11 895.70 787.36 0.00 0.00 0.00
April 1076.28 460.51 615.77 1111.23 584.50 0.00 0.00 0.00
May 1253.75 476.13 777.63 1464.49 386.14 0.00 0.00 0.00
June 1372.19 553.45 818.75 1808.18 220.50 0.00 0.00 0.00
July 1285.13 483.94 801.19 1821.06 124.11 0.00 0.00 0.00
August 1421.71 658.16 763.55 2018.22 168.07 0.00 0.00 0.00
September 1009.30 441.06 568.24 1279.50 309.85 0.00 0.00 0.00
October 1000.64 486.59 514.06 1140.47 552.95 0.00 0.00 0.00
November 469.90 135.80 334.09 328.09 800.44 0.00 0.00 0.00
December 417.97 180.85 237.11 270.15 1036.51 0.00 0.00 0.00
                 
Annual Sum or Average 952.89 401.69 551.20 1078.01 600.97 0.00 0.00 0.00
Minimum of Months 417.97 135.80 237.11 270.15 124.11 0.00 0.00 0.00
Maximum of Months 1421.71 658.16 818.75 2018.22 1156.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.64 0.00 109.64 7.09 614.84 0.00 0.00 0.00
February 150.04 0.00 150.04 14.80 636.19 0.00 0.00 0.00
March 208.07 0.00 208.07 80.61 418.36 0.00 0.00 0.00
April 249.92 0.71 249.21 167.19 294.95 0.00 0.00 0.00
May 331.57 11.05 320.52 324.56 178.94 0.00 0.00 0.00
June 351.62 18.89 332.73 444.38 99.27 0.00 0.00 0.00
July 339.81 12.29 327.52 492.65 54.66 0.00 0.00 0.00
August 301.05 3.58 297.47 428.74 77.63 0.00 0.00 0.00
September 226.94 0.04 226.90 243.15 163.18 0.00 0.00 0.00
October 196.40 0.00 196.40 141.10 303.70 0.00 0.00 0.00
November 137.76 0.00 137.76 35.42 460.18 0.00 0.00 0.00
December 95.64 0.00 95.64 3.91 588.94 0.00 0.00 0.00
                 
Annual Sum or Average 225.30 3.90 221.40 199.88 322.44 0.00 0.00 0.00
Minimum of Months 95.64 0.00 95.64 3.91 54.66 0.00 0.00 0.00
Maximum of Months 351.62 18.89 332.73 492.65 636.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.65 0.00 109.65 7.09 614.88 0.00 0.00 0.00
February 150.05 0.00 150.05 14.80 636.23 0.00 0.00 0.00
March 208.08 0.00 208.08 80.61 418.39 0.00 0.00 0.00
April 249.93 0.71 249.22 167.20 294.97 0.00 0.00 0.00
May 331.58 11.05 320.53 324.57 178.95 0.00 0.00 0.00
June 351.64 18.89 332.74 444.39 99.28 0.00 0.00 0.00
July 339.82 12.29 327.53 492.67 54.66 0.00 0.00 0.00
August 301.07 3.58 297.48 428.76 77.63 0.00 0.00 0.00
September 226.95 0.04 226.91 243.16 163.19 0.00 0.00 0.00
October 196.41 0.00 196.41 141.10 303.72 0.00 0.00 0.00
November 137.76 0.00 137.76 35.42 460.21 0.00 0.00 0.00
December 95.64 0.00 95.64 3.91 588.98 0.00 0.00 0.00
                 
Annual Sum or Average 225.31 3.90 221.41 199.89 322.46 0.00 0.00 0.00
Minimum of Months 95.64 0.00 95.64 3.91 54.66 0.00 0.00 0.00
Maximum of Months 351.64 18.89 332.74 492.67 636.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.65 0.00 109.65 7.09 614.88 0.00 0.00 0.00
February 150.05 0.00 150.05 14.80 636.23 0.00 0.00 0.00
March 208.08 0.00 208.08 80.61 418.39 0.00 0.00 0.00
April 249.93 0.71 249.22 167.20 294.97 0.00 0.00 0.00
May 331.58 11.05 320.53 324.57 178.95 0.00 0.00 0.00
June 351.64 18.89 332.74 444.39 99.28 0.00 0.00 0.00
July 339.82 12.29 327.53 492.67 54.66 0.00 0.00 0.00
August 301.07 3.58 297.48 428.76 77.63 0.00 0.00 0.00
September 226.95 0.04 226.91 243.16 163.19 0.00 0.00 0.00
October 196.41 0.00 196.41 141.10 303.72 0.00 0.00 0.00
November 137.76 0.00 137.76 35.42 460.21 0.00 0.00 0.00
December 95.64 0.00 95.64 3.91 588.98 0.00 0.00 0.00
                 
Annual Sum or Average 225.31 3.90 221.41 199.89 322.46 0.00 0.00 0.00
Minimum of Months 95.64 0.00 95.64 3.91 54.66 0.00 0.00 0.00
Maximum of Months 351.64 18.89 332.74 492.67 636.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 440.66 176.67 263.99 275.00 1108.03 0.00 0.00 0.00
February 683.37 318.79 364.58 484.17 1116.69 0.00 0.00 0.00
March 871.76 370.77 501.00 776.01 791.86 0.00 0.00 0.00
April 1046.18 458.26 587.92 1077.11 567.94 0.00 0.00 0.00
May 1268.79 507.08 761.71 1493.02 362.64 0.00 0.00 0.00
June 1175.90 425.67 750.24 1552.97 202.02 0.00 0.00 0.00
July 1181.05 426.21 754.84 1689.36 113.26 0.00 0.00 0.00
August 1329.89 599.65 730.25 1886.37 159.16 0.00 0.00 0.00
September 991.84 445.00 546.84 1239.91 314.16 0.00 0.00 0.00
October 899.18 407.54 491.64 991.56 580.66 0.00 0.00 0.00
November 556.07 213.54 342.53 437.18 843.61 0.00 0.00 0.00
December 433.21 203.41 229.80 290.14 1054.97 0.00 0.00 0.00
                 
Annual Sum or Average 907.93 379.81 528.12 1019.77 598.32 0.00 0.00 0.00
Minimum of Months 433.21 176.67 229.80 275.00 113.26 0.00 0.00 0.00
Maximum of Months 1329.89 599.65 761.71 1886.37 1116.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.42 6.99 10.44 10.87 43.81 0.00 0.00 0.00
February 27.02 12.60 14.42 19.14 44.15 0.00 0.00 0.00
March 34.47 14.66 19.81 30.68 31.31 0.00 0.00 0.00
April 41.36 18.12 23.25 42.59 22.46 0.00 0.00 0.00
May 50.17 20.05 30.12 59.03 14.34 0.00 0.00 0.00
June 46.49 16.83 29.66 61.40 7.99 0.00 0.00 0.00
July 46.70 16.85 29.85 66.80 4.48 0.00 0.00 0.00
August 52.58 23.71 28.87 74.59 6.29 0.00 0.00 0.00
September 39.22 17.59 21.62 49.02 12.42 0.00 0.00 0.00
October 35.55 16.11 19.44 39.21 22.96 0.00 0.00 0.00
November 21.99 8.44 13.54 17.29 33.36 0.00 0.00 0.00
December 17.13 8.04 9.09 11.47 41.71 0.00 0.00 0.00
                 
Annual Sum or Average 35.90 15.02 20.88 40.32 23.66 0.00 0.00 0.00
Minimum of Months 17.13 6.99 9.09 10.87 4.48 0.00 0.00 0.00
Maximum of Months 52.58 23.71 30.12 74.59 44.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 567.22 371.42 195.80 571.27 554.57 0.00 0.00 0.00
February 748.15 495.21 252.94 763.07 568.69 0.00 0.00 0.00
March 674.97 374.62 300.35 731.54 417.87 0.00 0.00 0.00
April 523.76 207.11 316.65 587.83 309.11 0.00 0.00 0.00
May 459.00 95.74 363.26 550.77 193.53 0.00 0.00 0.00
June 430.75 65.84 364.91 590.54 107.90 0.00 0.00 0.00
July 451.52 78.43 373.09 683.91 58.50 0.00 0.00 0.00
August 602.95 223.64 379.31 915.52 87.52 0.00 0.00 0.00
September 654.21 338.38 315.83 877.05 174.81 0.00 0.00 0.00
October 896.21 561.99 334.22 1117.03 318.87 0.00 0.00 0.00
November 621.45 373.21 248.24 664.64 438.68 0.00 0.00 0.00
December 614.79 436.46 178.33 636.37 530.54 0.00 0.00 0.00
                 
Annual Sum or Average 603.07 300.86 302.21 724.29 311.90 0.00 0.00 0.00
Minimum of Months 430.75 65.84 178.33 550.77 58.50 0.00 0.00 0.00
Maximum of Months 896.21 561.99 379.31 1117.03 568.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 567.22 371.42 195.80 571.27 554.57 0.00 0.00 0.00
February 748.15 495.21 252.94 763.07 568.69 0.00 0.00 0.00
March 674.97 374.62 300.35 731.54 417.87 0.00 0.00 0.00
April 523.76 207.11 316.65 587.83 309.11 0.00 0.00 0.00
May 459.00 95.74 363.26 550.77 193.53 0.00 0.00 0.00
June 430.75 65.84 364.91 590.54 107.90 0.00 0.00 0.00
July 451.52 78.43 373.09 683.91 58.50 0.00 0.00 0.00
August 602.95 223.64 379.31 915.52 87.52 0.00 0.00 0.00
September 654.21 338.38 315.83 877.05 174.81 0.00 0.00 0.00
October 896.21 561.99 334.22 1117.03 318.87 0.00 0.00 0.00
November 621.45 373.21 248.24 664.64 438.68 0.00 0.00 0.00
December 614.79 436.46 178.33 636.37 530.54 0.00 0.00 0.00
                 
Annual Sum or Average 603.07 300.86 302.21 724.29 311.90 0.00 0.00 0.00
Minimum of Months 430.75 65.84 178.33 550.77 58.50 0.00 0.00 0.00
Maximum of Months 896.21 561.99 379.31 1117.03 568.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 567.19 371.40 195.79 571.23 554.53 0.00 0.00 0.00
February 748.10 495.18 252.92 763.02 568.65 0.00 0.00 0.00
March 674.93 374.60 300.33 731.49 417.84 0.00 0.00 0.00
April 523.72 207.09 316.63 587.79 309.09 0.00 0.00 0.00
May 458.97 95.73 363.23 550.73 193.52 0.00 0.00 0.00
June 430.73 65.84 364.89 590.50 107.89 0.00 0.00 0.00
July 451.49 78.42 373.07 683.87 58.49 0.00 0.00 0.00
August 602.91 223.63 379.28 915.47 87.52 0.00 0.00 0.00
September 654.17 338.36 315.81 877.00 174.80 0.00 0.00 0.00
October 896.16 561.95 334.20 1116.96 318.85 0.00 0.00 0.00
November 621.41 373.18 248.22 664.59 438.65 0.00 0.00 0.00
December 614.75 436.43 178.32 636.33 530.50 0.00 0.00 0.00
                 
Annual Sum or Average 603.03 300.84 302.19 724.25 311.88 0.00 0.00 0.00
Minimum of Months 430.73 65.84 178.32 550.73 58.49 0.00 0.00 0.00
Maximum of Months 896.16 561.95 379.28 1116.96 568.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 435.03 178.19 256.84 275.16 1131.55 0.00 0.00 0.00
February 641.51 281.75 359.76 451.23 1165.01 0.00 0.00 0.00
March 947.27 437.33 509.94 872.81 794.12 0.00 0.00 0.00
April 1035.33 442.99 592.34 1080.66 587.31 0.00 0.00 0.00
May 1206.05 458.01 748.04 1427.14 377.86 0.00 0.00 0.00
June 1319.99 532.39 787.60 1755.20 218.73 0.00 0.00 0.00
July 1236.24 465.53 770.71 1766.29 123.23 0.00 0.00 0.00
August 1367.61 633.11 734.50 1949.80 173.41 0.00 0.00 0.00
September 970.90 424.28 546.62 1228.17 329.59 0.00 0.00 0.00
October 962.57 468.07 494.50 1084.01 602.32 0.00 0.00 0.00
November 452.02 130.64 321.38 302.85 861.65 0.00 0.00 0.00
December 402.06 173.97 228.09 256.63 1083.54 0.00 0.00 0.00
                 
Annual Sum or Average 916.63 386.41 530.23 1041.72 617.55 0.00 0.00 0.00
Minimum of Months 402.06 130.64 228.09 256.63 123.23 0.00 0.00 0.00
Maximum of Months 1367.61 633.11 787.60 1949.80 1165.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 17.20 7.05 10.16 10.88 44.74 0.00 0.00 0.00
February 25.36 11.14 14.22 17.84 46.06 0.00 0.00 0.00
March 37.45 17.29 20.16 34.51 31.40 0.00 0.00 0.00
April 40.94 17.52 23.42 42.73 23.22 0.00 0.00 0.00
May 47.69 18.11 29.58 56.43 14.94 0.00 0.00 0.00
June 52.19 21.05 31.14 69.40 8.65 0.00 0.00 0.00
July 48.88 18.41 30.47 69.84 4.87 0.00 0.00 0.00
August 54.07 25.03 29.04 77.09 6.86 0.00 0.00 0.00
September 38.39 16.78 21.61 48.56 13.03 0.00 0.00 0.00
October 38.06 18.51 19.55 42.86 23.82 0.00 0.00 0.00
November 17.87 5.17 12.71 11.97 34.07 0.00 0.00 0.00
December 15.90 6.88 9.02 10.15 42.84 0.00 0.00 0.00
                 
Annual Sum or Average 36.24 15.28 20.96 41.19 24.42 0.00 0.00 0.00
Minimum of Months 15.90 5.17 9.02 10.15 4.87 0.00 0.00 0.00
Maximum of Months 54.07 25.03 31.14 77.09 46.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 328.95 0.00 328.95 19.39 1856.18 0.00 0.00 0.00
February 450.15 0.00 450.15 39.56 1942.10 0.00 0.00 0.00
March 624.24 0.00 624.24 217.72 1306.96 0.00 0.00 0.00
April 749.80 2.13 747.67 465.53 936.31 0.00 0.00 0.00
May 994.74 33.15 961.60 924.79 577.23 0.00 0.00 0.00
June 1054.91 56.68 998.23 1307.05 316.42 0.00 0.00 0.00
July 1019.47 36.87 982.61 1458.47 177.03 0.00 0.00 0.00
August 903.20 10.75 892.45 1276.25 240.65 0.00 0.00 0.00
September 680.87 0.13 680.74 725.63 486.03 0.00 0.00 0.00
October 589.24 0.00 589.24 422.89 893.86 0.00 0.00 0.00
November 413.30 0.00 413.30 107.25 1346.55 0.00 0.00 0.00
December 286.93 0.00 286.93 11.61 1750.05 0.00 0.00 0.00
                 
Annual Sum or Average 675.95 11.70 664.24 585.03 980.27 0.00 0.00 0.00
Minimum of Months 286.93 0.00 286.93 11.61 177.03 0.00 0.00 0.00
Maximum of Months 1054.91 56.68 998.23 1458.47 1942.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 458.09 183.66 274.43 280.81 1150.69 0.00 0.00 0.00
February 710.40 331.40 379.00 493.26 1165.88 0.00 0.00 0.00
March 906.25 385.43 520.81 788.04 837.46 0.00 0.00 0.00
April 1087.56 476.38 611.17 1099.69 601.21 0.00 0.00 0.00
May 1318.98 527.14 791.84 1527.20 389.09 0.00 0.00 0.00
June 1222.42 442.51 779.91 1599.90 214.18 0.00 0.00 0.00
July 1227.77 443.07 784.70 1746.13 118.94 0.00 0.00 0.00
August 1382.50 623.37 759.13 1955.36 160.65 0.00 0.00 0.00
September 1031.07 462.60 568.47 1287.00 311.71 0.00 0.00 0.00
October 934.74 423.66 511.09 1032.12 572.99 0.00 0.00 0.00
November 578.07 221.98 356.08 457.98 839.32 0.00 0.00 0.00
December 450.35 211.46 238.89 300.44 1074.54 0.00 0.00 0.00
                 
Annual Sum or Average 943.84 394.84 549.01 1051.18 616.64 0.00 0.00 0.00
Minimum of Months 450.35 183.66 238.89 280.81 118.94 0.00 0.00 0.00
Maximum of Months 1382.50 623.37 791.84 1955.36 1165.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1701.70 1114.29 587.42 1671.97 1665.94 0.00 0.00 0.00
February 2244.49 1485.67 758.82 2236.61 1701.96 0.00 0.00 0.00
March 2024.95 1123.88 901.07 2141.84 1275.01 0.00 0.00 0.00
April 1571.29 621.34 949.96 1717.00 964.43 0.00 0.00 0.00
May 1377.00 287.22 1089.78 1598.80 620.86 0.00 0.00 0.00
June 1292.28 197.54 1094.74 1743.67 339.47 0.00 0.00 0.00
July 1354.57 235.29 1119.28 2034.33 182.74 0.00 0.00 0.00
August 1808.87 670.94 1137.93 2737.28 255.60 0.00 0.00 0.00
September 1962.66 1015.17 947.49 2623.40 498.09 0.00 0.00 0.00
October 2688.68 1686.00 1002.69 3341.61 893.35 0.00 0.00 0.00
November 1864.37 1119.64 744.73 1976.01 1263.47 0.00 0.00 0.00
December 1844.39 1309.40 535.00 1882.99 1554.28 0.00 0.00 0.00
                 
Annual Sum or Average 1809.23 902.59 906.64 2142.74 930.14 0.00 0.00 0.00
Minimum of Months 1292.28 197.54 535.00 1598.80 182.74 0.00 0.00 0.00
Maximum of Months 2688.68 1686.00 1137.93 3341.61 1701.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 452.24 185.24 267.00 279.63 1177.27 0.00 0.00 0.00
February 666.89 292.90 373.99 456.87 1218.73 0.00 0.00 0.00
March 984.74 454.63 530.11 887.60 837.39 0.00 0.00 0.00
April 1076.28 460.51 615.77 1102.60 623.02 0.00 0.00 0.00
May 1253.75 476.13 777.63 1459.43 406.19 0.00 0.00 0.00
June 1372.19 553.45 818.75 1810.68 229.13 0.00 0.00 0.00
July 1285.13 483.94 801.19 1826.26 128.19 0.00 0.00 0.00
August 1421.71 658.16 763.55 2021.76 174.31 0.00 0.00 0.00
September 1009.30 441.06 568.24 1275.86 328.64 0.00 0.00 0.00
October 1000.64 486.59 514.06 1129.07 594.29 0.00 0.00 0.00
November 469.90 135.80 334.09 315.62 865.41 0.00 0.00 0.00
December 417.97 180.85 237.11 263.86 1107.62 0.00 0.00 0.00
                 
Annual Sum or Average 952.89 401.69 551.20 1073.51 637.52 0.00 0.00 0.00
Minimum of Months 417.97 135.80 237.11 263.86 128.19 0.00 0.00 0.00
Maximum of Months 1421.71 658.16 818.75 2021.76 1218.73 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.881047E+09 0.00 0.881047E+09 61476148.24 0.474370E+10
February 0.108900E+10 0.00 0.108900E+10 0.108657E+09 0.446057E+10
March 0.167197E+10 0.00 0.167197E+10 0.615860E+09 0.328625E+10
April 0.194348E+10 5527855.32 0.193795E+10 0.124504E+10 0.226973E+10
May 0.266432E+10 88776796.13 0.257555E+10 0.250185E+10 0.147323E+10
June 0.273434E+10 0.146927E+09 0.258741E+10 0.338245E+10 0.791839E+09
July 0.273056E+10 98746035.06 0.263181E+10 0.388736E+10 0.462054E+09
August 0.241914E+10 28791201.70 0.239035E+10 0.340868E+10 0.621594E+09
September 0.176480E+10 330476.25 0.176447E+10 0.189470E+10 0.118660E+10
October 0.157822E+10 0.00 0.157822E+10 0.118208E+10 0.221937E+10
November 0.107126E+10 0.00 0.107126E+10 0.319256E+09 0.321827E+10
December 0.768507E+09 0.00 0.768507E+09 41805694.77 0.438648E+10
           
Annual Sum or Average 0.213166E+11 0.369100E+09 0.209475E+11 0.186492E+11 0.291197E+11
Minimum of Months 0.768507E+09 0.00 0.768507E+09 41805694.77 0.462054E+09
Maximum of Months 0.273434E+10 0.146927E+09 0.263181E+10 0.388736E+10 0.474370E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122695E+10 0.491907E+09 0.735040E+09 0.768566E+09 0.293901E+10
February 0.171860E+10 0.801726E+09 0.916869E+09 0.122061E+10 0.267745E+10
March 0.242729E+10 0.103234E+10 0.139495E+10 0.213689E+10 0.211392E+10
April 0.281895E+10 0.123479E+10 0.158416E+10 0.287355E+10 0.147029E+10
May 0.353276E+10 0.141190E+10 0.212086E+10 0.410000E+10 0.997447E+09
June 0.316850E+10 0.114698E+10 0.202153E+10 0.414072E+10 0.536872E+09
July 0.328845E+10 0.118672E+10 0.210173E+10 0.466250E+10 0.310142E+09
August 0.370288E+10 0.166963E+10 0.203325E+10 0.522665E+10 0.415931E+09
September 0.267254E+10 0.119906E+10 0.147348E+10 0.334225E+10 0.765629E+09
October 0.250362E+10 0.113473E+10 0.136889E+10 0.279348E+10 0.143445E+10
November 0.149835E+10 0.575381E+09 0.922968E+09 0.122789E+10 0.201820E+10
December 0.120621E+10 0.566362E+09 0.639847E+09 0.830716E+09 0.269512E+10
           
Annual Sum or Average 0.297651E+11 0.124515E+11 0.173136E+11 0.333238E+11 0.183745E+11
Minimum of Months 0.120621E+10 0.491907E+09 0.639847E+09 0.768566E+09 0.310142E+09
Maximum of Months 0.370288E+10 0.166963E+10 0.212086E+10 0.522665E+10 0.293901E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.455785E+10 0.298451E+10 0.157334E+10 0.451097E+10 0.424233E+10
February 0.542987E+10 0.359413E+10 0.183574E+10 0.545897E+10 0.389664E+10
March 0.542364E+10 0.301021E+10 0.241342E+10 0.577163E+10 0.320781E+10
April 0.407279E+10 0.161050E+10 0.246229E+10 0.448160E+10 0.234478E+10
May 0.368817E+10 0.769294E+09 0.291888E+10 0.429882E+10 0.158014E+10
June 0.334958E+10 0.512019E+09 0.283757E+10 0.451094E+10 0.846511E+09
July 0.362807E+10 0.630195E+09 0.299788E+10 0.542851E+10 0.474186E+09
August 0.484489E+10 0.179705E+10 0.304784E+10 0.731491E+10 0.659619E+09
September 0.508723E+10 0.263132E+10 0.245590E+10 0.680554E+10 0.122140E+10
October 0.720137E+10 0.451578E+10 0.268559E+10 0.897992E+10 0.223980E+10
November 0.483245E+10 0.290212E+10 0.193033E+10 0.518555E+10 0.303452E+10
December 0.494002E+10 0.350709E+10 0.143294E+10 0.510025E+10 0.389308E+10
           
Annual Sum or Average 0.570559E+11 0.284642E+11 0.285917E+11 0.678476E+11 0.276408E+11
Minimum of Months 0.334958E+10 0.512019E+09 0.143294E+10 0.429882E+10 0.474186E+09
Maximum of Months 0.720137E+10 0.451578E+10 0.304784E+10 0.897992E+10 0.424233E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121127E+10 0.496140E+09 0.715130E+09 0.759572E+09 0.300722E+10
February 0.161333E+10 0.708583E+09 0.904751E+09 0.111962E+10 0.279756E+10
March 0.263753E+10 0.121768E+10 0.141985E+10 0.239905E+10 0.210886E+10
April 0.278971E+10 0.119364E+10 0.159606E+10 0.288031E+10 0.151503E+10
May 0.335805E+10 0.127526E+10 0.208279E+10 0.392248E+10 0.103425E+10
June 0.355673E+10 0.143453E+10 0.212220E+10 0.468680E+10 0.571540E+09
July 0.344210E+10 0.129619E+10 0.214591E+10 0.487754E+10 0.332405E+09
August 0.380790E+10 0.176281E+10 0.204509E+10 0.540560E+10 0.450162E+09
September 0.261610E+10 0.114323E+10 0.147287E+10 0.331646E+10 0.803143E+09
October 0.268013E+10 0.130328E+10 0.137685E+10 0.305462E+10 0.148102E+10
November 0.121798E+10 0.352004E+09 0.865974E+09 0.850405E+09 0.207474E+10
December 0.111948E+10 0.484402E+09 0.635077E+09 0.723560E+09 0.277619E+10
           
Annual Sum or Average 0.300503E+11 0.126677E+11 0.173826E+11 0.339960E+11 0.189521E+11
Minimum of Months 0.111948E+10 0.352004E+09 0.635077E+09 0.723560E+09 0.332405E+09
Maximum of Months 0.380790E+10 0.176281E+10 0.214591E+10 0.540560E+10 0.300722E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293668E+09 0.00 0.293668E+09 18993033.72 0.164678E+10
February 0.362982E+09 0.00 0.362982E+09 35808730.01 0.153906E+10
March 0.557296E+09 0.00 0.557296E+09 0.215913E+09 0.112054E+10
April 0.647796E+09 1842531.26 0.645953E+09 0.433366E+09 0.764511E+09
May 0.888066E+09 29590865.31 0.858475E+09 0.869291E+09 0.479267E+09
June 0.911403E+09 48973501.17 0.862429E+09 0.115182E+10 0.257317E+09
July 0.910142E+09 32913787.73 0.877228E+09 0.131952E+10 0.146398E+09
August 0.806343E+09 9596613.18 0.796746E+09 0.114835E+10 0.207918E+09
September 0.588240E+09 110153.54 0.588130E+09 0.630242E+09 0.422958E+09
October 0.526049E+09 0.00 0.526049E+09 0.377910E+09 0.813443E+09
November 0.357071E+09 0.00 0.357071E+09 91818420.34 0.119279E+10
December 0.256157E+09 0.00 0.256157E+09 10479249.38 0.157742E+10
           
Annual Sum or Average 0.710521E+10 0.123027E+09 0.698219E+10 0.630351E+10 0.101684E+11
Minimum of Months 0.256157E+09 0.00 0.256157E+09 10479249.38 0.146398E+09
Maximum of Months 0.911403E+09 48973501.17 0.877228E+09 0.131952E+10 0.164678E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293680E+09 0.00 0.293680E+09 18991616.37 0.164689E+10
February 0.362996E+09 0.00 0.362996E+09 35807756.56 0.153916E+10
March 0.557319E+09 0.00 0.557319E+09 0.215916E+09 0.112061E+10
April 0.647822E+09 1842580.79 0.645979E+09 0.433378E+09 0.764559E+09
May 0.888101E+09 29591660.72 0.858509E+09 0.869318E+09 0.479296E+09
June 0.911439E+09 48974817.59 0.862464E+09 0.115186E+10 0.257332E+09
July 0.910178E+09 32914672.46 0.877263E+09 0.131957E+10 0.146405E+09
August 0.806376E+09 9596871.14 0.796779E+09 0.114840E+10 0.207928E+09
September 0.588264E+09 110156.50 0.588154E+09 0.630266E+09 0.422982E+09
October 0.526070E+09 0.00 0.526070E+09 0.377922E+09 0.813491E+09
November 0.357084E+09 0.00 0.357084E+09 91817892.76 0.119287E+10
December 0.256167E+09 0.00 0.256167E+09 10478595.87 0.157752E+10
           
Annual Sum or Average 0.710550E+10 0.123031E+09 0.698246E+10 0.630373E+10 0.101690E+11
Minimum of Months 0.256167E+09 0.00 0.256167E+09 10478595.87 0.146405E+09
Maximum of Months 0.911439E+09 48974817.59 0.877263E+09 0.131957E+10 0.164689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.293680E+09 0.00 0.293680E+09 18991616.37 0.164689E+10
February 0.362996E+09 0.00 0.362996E+09 35807756.56 0.153916E+10
March 0.557319E+09 0.00 0.557319E+09 0.215916E+09 0.112061E+10
April 0.647822E+09 1842580.79 0.645979E+09 0.433378E+09 0.764559E+09
May 0.888101E+09 29591660.72 0.858509E+09 0.869318E+09 0.479296E+09
June 0.911439E+09 48974817.59 0.862464E+09 0.115186E+10 0.257332E+09
July 0.910178E+09 32914672.46 0.877263E+09 0.131957E+10 0.146405E+09
August 0.806376E+09 9596871.14 0.796779E+09 0.114840E+10 0.207928E+09
September 0.588264E+09 110156.50 0.588154E+09 0.630266E+09 0.422982E+09
October 0.526070E+09 0.00 0.526070E+09 0.377922E+09 0.813491E+09
November 0.357084E+09 0.00 0.357084E+09 91817892.76 0.119287E+10
December 0.256167E+09 0.00 0.256167E+09 10478595.87 0.157752E+10
           
Annual Sum or Average 0.710550E+10 0.123031E+09 0.698246E+10 0.630373E+10 0.101690E+11
Minimum of Months 0.256167E+09 0.00 0.256167E+09 10478595.87 0.146405E+09
Maximum of Months 0.911439E+09 48974817.59 0.877263E+09 0.131957E+10 0.164689E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118026E+10 0.473188E+09 0.707073E+09 0.736571E+09 0.296774E+10
February 0.165320E+10 0.771217E+09 0.881985E+09 0.117130E+10 0.270150E+10
March 0.233493E+10 0.993059E+09 0.134187E+10 0.207847E+10 0.212091E+10
April 0.271169E+10 0.118780E+10 0.152389E+10 0.279187E+10 0.147210E+10
May 0.339834E+10 0.135817E+10 0.204016E+10 0.399890E+10 0.971284E+09
June 0.304794E+10 0.110333E+10 0.194461E+10 0.402530E+10 0.523635E+09
July 0.316333E+10 0.114156E+10 0.202177E+10 0.452478E+10 0.303360E+09
August 0.356198E+10 0.160609E+10 0.195589E+10 0.505245E+10 0.426281E+09
September 0.257085E+10 0.115344E+10 0.141742E+10 0.321384E+10 0.814313E+09
October 0.240836E+10 0.109154E+10 0.131681E+10 0.265579E+10 0.155523E+10
November 0.144134E+10 0.553486E+09 0.887850E+09 0.113318E+10 0.218663E+10
December 0.116031E+10 0.544810E+09 0.615502E+09 0.777120E+09 0.282562E+10
           
Annual Sum or Average 0.286325E+11 0.119777E+11 0.166548E+11 0.321596E+11 0.188686E+11
Minimum of Months 0.116031E+10 0.473188E+09 0.615502E+09 0.736571E+09 0.303360E+09
Maximum of Months 0.356198E+10 0.160609E+10 0.204016E+10 0.505245E+10 0.296774E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 46666451.72 18709415.56 27957036.16 29123360.73 0.117342E+09
February 65366097.52 30493216.92 34872880.60 46312064.68 0.106815E+09
March 92321124.46 39264663.74 53056460.71 82180794.48 83858940.15
April 0.107218E+09 46964536.22 60253293.01 0.110388E+09 58205391.96
May 0.134367E+09 53700993.61 80666182.91 0.158113E+09 38403706.21
June 0.120513E+09 43624602.32 76888287.41 0.159157E+09 20704045.01
July 0.125075E+09 45136317.62 79938830.90 0.178906E+09 11994574.22
August 0.140838E+09 63503417.77 77334188.60 0.199769E+09 16854772.44
September 0.101649E+09 45605790.11 56043314.57 0.127072E+09 32197218.77
October 95224190.38 43158677.19 52065513.19 0.105008E+09 61492486.80
November 56989125.52 21884333.32 35104792.20 44804921.77 86457403.45
December 45877695.07 21541286.80 24336408.28 30726620.25 0.111723E+09
           
Annual Sum or Average 0.113210E+10 0.473587E+09 0.658517E+09 0.127156E+10 0.746048E+09
Minimum of Months 45877695.07 18709415.56 24336408.28 29123360.73 11994574.22
Maximum of Months 0.140838E+09 63503417.77 80666182.91 0.199769E+09 0.117342E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151925E+10 0.994815E+09 0.524439E+09 0.153009E+10 0.148536E+10
February 0.180992E+10 0.119802E+10 0.611904E+09 0.184601E+10 0.137577E+10
March 0.180785E+10 0.100338E+10 0.804465E+09 0.195935E+10 0.111921E+10
April 0.135758E+10 0.536823E+09 0.820754E+09 0.152366E+10 0.801223E+09
May 0.122938E+10 0.256426E+09 0.972950E+09 0.147518E+10 0.518362E+09
June 0.111652E+10 0.170669E+09 0.945847E+09 0.153067E+10 0.279678E+09
July 0.120934E+10 0.210061E+09 0.999283E+09 0.183179E+10 0.156680E+09
August 0.161494E+10 0.599004E+09 0.101594E+10 0.245214E+10 0.234415E+09
September 0.169572E+10 0.877089E+09 0.818626E+09 0.227332E+10 0.453109E+09
October 0.240042E+10 0.150523E+10 0.895187E+09 0.299185E+10 0.854063E+09
November 0.161079E+10 0.967353E+09 0.643435E+09 0.172274E+10 0.113706E+10
December 0.164664E+10 0.116900E+10 0.477639E+09 0.170447E+10 0.142099E+10
           
Annual Sum or Average 0.190183E+11 0.948788E+10 0.953047E+10 0.228413E+11 0.983593E+10
Minimum of Months 0.111652E+10 0.170669E+09 0.477639E+09 0.147518E+10 0.156680E+09
Maximum of Months 0.240042E+10 0.150523E+10 0.101594E+10 0.299185E+10 0.148536E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151925E+10 0.994815E+09 0.524439E+09 0.153009E+10 0.148536E+10
February 0.180992E+10 0.119802E+10 0.611904E+09 0.184601E+10 0.137577E+10
March 0.180785E+10 0.100338E+10 0.804465E+09 0.195935E+10 0.111921E+10
April 0.135758E+10 0.536823E+09 0.820754E+09 0.152366E+10 0.801223E+09
May 0.122938E+10 0.256426E+09 0.972950E+09 0.147518E+10 0.518362E+09
June 0.111652E+10 0.170669E+09 0.945847E+09 0.153067E+10 0.279678E+09
July 0.120934E+10 0.210061E+09 0.999283E+09 0.183179E+10 0.156680E+09
August 0.161494E+10 0.599004E+09 0.101594E+10 0.245214E+10 0.234415E+09
September 0.169572E+10 0.877089E+09 0.818626E+09 0.227332E+10 0.453109E+09
October 0.240042E+10 0.150523E+10 0.895187E+09 0.299185E+10 0.854063E+09
November 0.161079E+10 0.967353E+09 0.643435E+09 0.172274E+10 0.113706E+10
December 0.164664E+10 0.116900E+10 0.477639E+09 0.170447E+10 0.142099E+10
           
Annual Sum or Average 0.190183E+11 0.948788E+10 0.953047E+10 0.228413E+11 0.983593E+10
Minimum of Months 0.111652E+10 0.170669E+09 0.477639E+09 0.147518E+10 0.156680E+09
Maximum of Months 0.240042E+10 0.150523E+10 0.101594E+10 0.299185E+10 0.148536E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.151916E+10 0.994753E+09 0.524405E+09 0.152999E+10 0.148527E+10
February 0.180981E+10 0.119794E+10 0.611866E+09 0.184590E+10 0.137568E+10
March 0.180773E+10 0.100332E+10 0.804415E+09 0.195922E+10 0.111914E+10
April 0.135749E+10 0.536790E+09 0.820702E+09 0.152356E+10 0.801172E+09
May 0.122930E+10 0.256410E+09 0.972888E+09 0.147509E+10 0.518329E+09
June 0.111645E+10 0.170659E+09 0.945788E+09 0.153058E+10 0.279661E+09
July 0.120927E+10 0.210047E+09 0.999220E+09 0.183167E+10 0.156670E+09
August 0.161484E+10 0.598966E+09 0.101587E+10 0.245198E+10 0.234401E+09
September 0.169561E+10 0.877034E+09 0.818574E+09 0.227318E+10 0.453081E+09
October 0.240026E+10 0.150513E+10 0.895130E+09 0.299166E+10 0.854009E+09
November 0.161069E+10 0.967292E+09 0.643395E+09 0.172263E+10 0.113699E+10
December 0.164654E+10 0.116893E+10 0.477608E+09 0.170436E+10 0.142090E+10
           
Annual Sum or Average 0.190171E+11 0.948728E+10 0.952986E+10 0.228398E+11 0.983530E+10
Minimum of Months 0.111645E+10 0.170659E+09 0.477608E+09 0.147509E+10 0.156670E+09
Maximum of Months 0.240026E+10 0.150513E+10 0.101587E+10 0.299166E+10 0.148527E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.116518E+10 0.477261E+09 0.687922E+09 0.736985E+09 0.303074E+10
February 0.155195E+10 0.681620E+09 0.870330E+09 0.109160E+10 0.281840E+10
March 0.253718E+10 0.117134E+10 0.136584E+10 0.233773E+10 0.212697E+10
April 0.268357E+10 0.114823E+10 0.153534E+10 0.280106E+10 0.152232E+10
May 0.323028E+10 0.122673E+10 0.200355E+10 0.382244E+10 0.101206E+10
June 0.342140E+10 0.137995E+10 0.204146E+10 0.454948E+10 0.566956E+09
July 0.331114E+10 0.124687E+10 0.206427E+10 0.473083E+10 0.330052E+09
August 0.366302E+10 0.169573E+10 0.196729E+10 0.522235E+10 0.464464E+09
September 0.251657E+10 0.109973E+10 0.141684E+10 0.318342E+10 0.854304E+09
October 0.257815E+10 0.125369E+10 0.132446E+10 0.290342E+10 0.161325E+10
November 0.117164E+10 0.338610E+09 0.833027E+09 0.784994E+09 0.223339E+10
December 0.107689E+10 0.465970E+09 0.610915E+09 0.687351E+09 0.290216E+10
           
Annual Sum or Average 0.289070E+11 0.121857E+11 0.167212E+11 0.328517E+11 0.194751E+11
Minimum of Months 0.107689E+10 0.338610E+09 0.610915E+09 0.687351E+09 0.330052E+09
Maximum of Months 0.366302E+10 0.169573E+10 0.206427E+10 0.522235E+10 0.303074E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 46070184.34 18870425.07 27199759.27 29139601.48 0.119833E+09
February 61362537.31 26950565.49 34411971.83 43160838.83 0.111437E+09
March 0.100317E+09 46313648.32 54003789.77 92431526.90 84098644.06
April 0.106105E+09 45399637.11 60705850.83 0.110751E+09 60191017.77
May 0.127722E+09 48503739.13 79218474.93 0.151135E+09 40015971.60
June 0.135279E+09 54561610.96 80717239.19 0.179882E+09 22416911.72
July 0.130919E+09 49299896.61 81619217.06 0.187052E+09 13049949.98
August 0.144832E+09 67047474.72 77784632.22 0.206487E+09 18364484.89
September 99502534.75 43482204.47 56020330.28 0.125869E+09 33778381.64
October 0.101938E+09 49569581.67 52367992.87 0.114798E+09 63786446.43
November 46325363.91 13388302.43 32937061.48 31037824.64 88306229.77
December 42578960.75 18423978.04 24154982.71 27177116.43 0.114749E+09
           
Annual Sum or Average 0.114295E+10 0.481811E+09 0.661141E+09 0.129892E+10 0.770027E+09
Minimum of Months 42578960.75 13388302.43 24154982.71 27177116.43 13049949.98
Maximum of Months 0.144832E+09 67047474.72 81619217.06 0.206487E+09 0.119833E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.881047E+09 0.00 0.881047E+09 51924469.44 0.497159E+10
February 0.108900E+10 0.00 0.108900E+10 95699420.56 0.469832E+10
March 0.167197E+10 0.00 0.167197E+10 0.583142E+09 0.350057E+10
April 0.194348E+10 5527855.32 0.193795E+10 0.120665E+10 0.242692E+10
May 0.266432E+10 88776796.13 0.257555E+10 0.247697E+10 0.154606E+10
June 0.273434E+10 0.146927E+09 0.258741E+10 0.338786E+10 0.820162E+09
July 0.273056E+10 98746035.06 0.263181E+10 0.390636E+10 0.474159E+09
August 0.241914E+10 28791201.70 0.239035E+10 0.341830E+10 0.644561E+09
September 0.176480E+10 330476.25 0.176447E+10 0.188083E+10 0.125978E+10
October 0.157822E+10 0.00 0.157822E+10 0.113268E+10 0.239412E+10
November 0.107126E+10 0.00 0.107126E+10 0.277998E+09 0.349025E+10
December 0.768507E+09 0.00 0.768507E+09 31098996.03 0.468733E+10
           
Annual Sum or Average 0.213166E+11 0.369100E+09 0.209475E+11 0.184495E+11 0.309138E+11
Minimum of Months 0.768507E+09 0.00 0.768507E+09 31098996.03 0.474159E+09
Maximum of Months 0.273434E+10 0.146927E+09 0.263181E+10 0.390636E+10 0.497159E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122695E+10 0.491907E+09 0.735040E+09 0.752117E+09 0.308200E+10
February 0.171860E+10 0.801726E+09 0.916869E+09 0.119328E+10 0.282049E+10
March 0.242729E+10 0.103234E+10 0.139495E+10 0.211069E+10 0.224305E+10
April 0.281895E+10 0.123479E+10 0.158416E+10 0.285039E+10 0.155833E+10
May 0.353276E+10 0.141190E+10 0.212086E+10 0.409045E+10 0.104215E+10
June 0.316850E+10 0.114698E+10 0.202153E+10 0.414694E+10 0.555148E+09
July 0.328845E+10 0.118672E+10 0.210173E+10 0.467684E+10 0.318565E+09
August 0.370288E+10 0.166963E+10 0.203325E+10 0.523723E+10 0.430291E+09
September 0.267254E+10 0.119906E+10 0.147348E+10 0.333589E+10 0.807948E+09
October 0.250362E+10 0.113473E+10 0.136889E+10 0.276442E+10 0.153470E+10
November 0.149835E+10 0.575381E+09 0.922968E+09 0.118709E+10 0.217552E+10
December 0.120621E+10 0.566362E+09 0.639847E+09 0.804706E+09 0.287805E+10
           
Annual Sum or Average 0.297651E+11 0.124515E+11 0.173136E+11 0.331500E+11 0.194462E+11
Minimum of Months 0.120621E+10 0.491907E+09 0.639847E+09 0.752117E+09 0.318565E+09
Maximum of Months 0.370288E+10 0.166963E+10 0.212086E+10 0.523723E+10 0.308200E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.455785E+10 0.298451E+10 0.157334E+10 0.447819E+10 0.446204E+10
February 0.542987E+10 0.359413E+10 0.183574E+10 0.541081E+10 0.411738E+10
March 0.542364E+10 0.301021E+10 0.241342E+10 0.573671E+10 0.341499E+10
April 0.407279E+10 0.161050E+10 0.246229E+10 0.445046E+10 0.249982E+10
May 0.368817E+10 0.769294E+09 0.291888E+10 0.428224E+10 0.166290E+10
June 0.334958E+10 0.512019E+09 0.283757E+10 0.451960E+10 0.879915E+09
July 0.362807E+10 0.630195E+09 0.299788E+10 0.544874E+10 0.489438E+09
August 0.484489E+10 0.179705E+10 0.304784E+10 0.733152E+10 0.684612E+09
September 0.508723E+10 0.263132E+10 0.245590E+10 0.679985E+10 0.129105E+10
October 0.720137E+10 0.451578E+10 0.268559E+10 0.895015E+10 0.239274E+10
November 0.483245E+10 0.290212E+10 0.193033E+10 0.512183E+10 0.327492E+10
December 0.494002E+10 0.350709E+10 0.143294E+10 0.504340E+10 0.416299E+10
           
Annual Sum or Average 0.570559E+11 0.284642E+11 0.285917E+11 0.675735E+11 0.293328E+11
Minimum of Months 0.334958E+10 0.512019E+09 0.143294E+10 0.428224E+10 0.489438E+09
Maximum of Months 0.720137E+10 0.451578E+10 0.304784E+10 0.895015E+10 0.446204E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121127E+10 0.496140E+09 0.715130E+09 0.748968E+09 0.315320E+10
February 0.161333E+10 0.708583E+09 0.904751E+09 0.110526E+10 0.294835E+10
March 0.263753E+10 0.121768E+10 0.141985E+10 0.237735E+10 0.224287E+10
April 0.278971E+10 0.119364E+10 0.159606E+10 0.285794E+10 0.161486E+10
May 0.335805E+10 0.127526E+10 0.208279E+10 0.390893E+10 0.108795E+10
June 0.355673E+10 0.143453E+10 0.212220E+10 0.469329E+10 0.593898E+09
July 0.344210E+10 0.129619E+10 0.214591E+10 0.489144E+10 0.343357E+09
August 0.380790E+10 0.176281E+10 0.204509E+10 0.541508E+10 0.466864E+09
September 0.261610E+10 0.114323E+10 0.147287E+10 0.330702E+10 0.851826E+09
October 0.268013E+10 0.130328E+10 0.137685E+10 0.302411E+10 0.159176E+10
November 0.121798E+10 0.352004E+09 0.865974E+09 0.818095E+09 0.224314E+10
December 0.111948E+10 0.484402E+09 0.635077E+09 0.706723E+09 0.296665E+10
           
Annual Sum or Average 0.300503E+11 0.126677E+11 0.173826E+11 0.338542E+11 0.201047E+11
Minimum of Months 0.111948E+10 0.352004E+09 0.635077E+09 0.706723E+09 0.343357E+09
Maximum of Months 0.380790E+10 0.176281E+10 0.214591E+10 0.541508E+10 0.315320E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.95 1771.10 328.95 0.00 328.95 0.00 0.00
February 44.91 1843.82 450.15 0.00 450.15 0.00 0.00
March 229.94 1226.95 624.24 0.00 624.24 0.00 0.00
April 480.34 875.67 749.80 2.13 747.67 0.00 0.00
May 934.08 550.04 994.74 33.15 961.60 0.00 0.00
June 1304.96 305.49 1054.91 56.68 998.23 0.00 0.00
July 1451.38 172.51 1019.47 36.87 982.61 0.00 0.00
August 1272.66 232.08 903.20 10.75 892.45 0.00 0.00
September 730.98 457.79 680.87 0.13 680.74 0.00 0.00
October 441.34 828.62 589.24 0.00 589.24 0.00 0.00
November 123.17 1241.62 413.30 0.00 413.30 0.00 0.00
December 15.61 1637.72 286.93 0.00 286.93 0.00 0.00
               
Annual Sum or Average 591.36 923.38 675.95 11.70 664.24 0.00 0.00
Minimum of Months 15.61 172.51 286.93 0.00 286.93 0.00 0.00
Maximum of Months 1451.38 1843.82 1054.91 56.68 998.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 286.95 1097.30 458.09 183.66 274.43 0.00 0.00
February 504.55 1106.75 710.40 331.40 379.00 0.00 0.00
March 797.82 789.25 906.25 385.43 520.81 0.00 0.00
April 1108.62 567.24 1087.56 476.38 611.17 0.00 0.00
May 1530.77 372.40 1318.98 527.14 791.84 0.00 0.00
June 1597.50 207.13 1222.42 442.51 779.91 0.00 0.00
July 1740.78 115.79 1227.77 443.07 784.70 0.00 0.00
August 1951.41 155.29 1382.50 623.37 759.13 0.00 0.00
September 1289.45 295.38 1031.07 462.60 568.47 0.00 0.00
October 1042.96 535.56 934.74 423.66 511.09 0.00 0.00
November 473.72 778.63 578.07 221.98 356.08 0.00 0.00
December 310.15 1006.24 450.35 211.46 238.89 0.00 0.00
               
Annual Sum or Average 1056.69 582.65 943.84 394.84 549.01 0.00 0.00
Minimum of Months 286.95 115.79 450.35 183.66 238.89 0.00 0.00
Maximum of Months 1951.41 1106.75 1382.50 623.37 791.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1684.20 1583.90 1701.70 1114.29 587.42 0.00 0.00
February 2256.52 1610.71 2244.49 1485.67 758.82 0.00 0.00
March 2154.88 1197.66 2024.95 1123.88 901.07 0.00 0.00
April 1729.01 904.62 1571.29 621.34 949.96 0.00 0.00
May 1604.99 589.96 1377.00 287.22 1089.78 0.00 0.00
June 1740.33 326.59 1292.28 197.54 1094.74 0.00 0.00
July 2026.77 177.04 1354.57 235.29 1119.28 0.00 0.00
August 2731.07 246.27 1808.87 670.94 1137.93 0.00 0.00
September 2625.60 471.22 1962.66 1015.17 947.49 0.00 0.00
October 3352.72 836.25 2688.68 1686.00 1002.69 0.00 0.00
November 2000.60 1170.72 1864.37 1119.64 744.73 0.00 0.00
December 1904.22 1453.51 1844.39 1309.40 535.00 0.00 0.00
               
Annual Sum or Average 2151.43 876.48 1809.23 902.59 906.64 0.00 0.00
Minimum of Months 1604.99 177.04 1292.28 197.54 535.00 0.00 0.00
Maximum of Months 3352.72 1610.71 2688.68 1686.00 1137.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 283.59 1122.77 452.24 185.24 267.00 0.00 0.00
February 462.81 1156.40 666.89 292.90 373.99 0.00 0.00
March 895.70 787.36 984.74 454.63 530.11 0.00 0.00
April 1111.23 584.50 1076.28 460.51 615.77 0.00 0.00
May 1464.49 386.14 1253.75 476.13 777.63 0.00 0.00
June 1808.18 220.50 1372.19 553.45 818.75 0.00 0.00
July 1821.06 124.11 1285.13 483.94 801.19 0.00 0.00
August 2018.22 168.07 1421.71 658.16 763.55 0.00 0.00
September 1279.50 309.85 1009.30 441.06 568.24 0.00 0.00
October 1140.47 552.95 1000.64 486.59 514.06 0.00 0.00
November 328.09 800.44 469.90 135.80 334.09 0.00 0.00
December 270.15 1036.51 417.97 180.85 237.11 0.00 0.00
               
Annual Sum or Average 1078.01 600.97 952.89 401.69 551.20 0.00 0.00
Minimum of Months 270.15 124.11 417.97 135.80 237.11 0.00 0.00
Maximum of Months 2018.22 1156.40 1421.71 658.16 818.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 21.27 1844.59 328.94 0.00 328.94 0.00 0.00
February 44.40 1908.64 450.14 0.00 450.14 0.00 0.00
March 241.84 1255.14 624.23 0.00 624.23 0.00 0.00
April 501.59 884.89 749.78 2.13 747.65 0.00 0.00
May 973.69 536.83 994.72 33.14 961.58 0.00 0.00
June 1333.16 297.83 1054.89 56.68 998.21 0.00 0.00
July 1478.00 163.98 1019.45 36.87 982.58 0.00 0.00
August 1286.27 232.89 903.19 10.75 892.44 0.00 0.00
September 729.47 489.55 680.85 0.13 680.72 0.00 0.00
October 423.30 911.15 589.23 0.00 589.23 0.00 0.00
November 106.27 1380.61 413.29 0.00 413.29 0.00 0.00
December 11.74 1766.90 286.92 0.00 286.92 0.00 0.00
               
Annual Sum or Average 599.66 967.35 675.93 11.70 664.23 0.00 0.00
Minimum of Months 11.74 163.98 286.92 0.00 286.92 0.00 0.00
Maximum of Months 1478.00 1908.64 1054.89 56.68 998.21 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 285.88 1151.84 458.08 183.65 274.43 0.00 0.00
February 503.31 1160.85 710.39 331.39 378.99 0.00 0.00
March 806.69 823.17 906.23 385.43 520.81 0.00 0.00
April 1119.70 590.39 1087.54 476.38 611.17 0.00 0.00
May 1552.05 376.97 1318.96 527.13 791.83 0.00 0.00
June 1614.37 210.01 1222.40 442.50 779.90 0.00 0.00
July 1756.16 117.74 1227.75 443.06 784.69 0.00 0.00
August 1960.95 165.45 1382.47 623.36 759.12 0.00 0.00
September 1288.93 326.59 1031.06 462.59 568.46 0.00 0.00
October 1030.76 603.62 934.73 423.65 511.08 0.00 0.00
November 454.47 876.96 578.06 221.98 356.08 0.00 0.00
December 301.62 1096.68 450.34 211.45 238.89 0.00 0.00
               
Annual Sum or Average 1060.09 621.98 943.83 394.83 549.00 0.00 0.00
Minimum of Months 285.88 117.74 450.34 183.65 238.89 0.00 0.00
Maximum of Months 1960.95 1160.85 1382.47 623.36 791.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1713.77 1663.68 1701.64 1114.24 587.40 0.00 0.00
February 2289.15 1706.03 2244.40 1485.61 758.79 0.00 0.00
March 2194.56 1253.57 2024.88 1123.84 901.04 0.00 0.00
April 1763.46 927.32 1571.24 621.31 949.93 0.00 0.00
May 1652.27 580.59 1376.96 287.21 1089.75 0.00 0.00
June 1771.58 323.69 1292.24 197.53 1094.71 0.00 0.00
July 2051.69 175.49 1354.52 235.28 1119.24 0.00 0.00
August 2746.51 262.56 1808.81 670.91 1137.90 0.00 0.00
September 2631.10 524.42 1962.59 1015.13 947.46 0.00 0.00
October 3351.01 956.59 2688.58 1685.93 1002.65 0.00 0.00
November 1993.87 1316.02 1864.30 1119.60 744.70 0.00 0.00
December 1909.08 1591.57 1844.32 1309.34 534.98 0.00 0.00
               
Annual Sum or Average 2172.83 935.67 1809.17 902.56 906.61 0.00 0.00
Minimum of Months 1652.27 175.49 1292.24 197.53 534.98 0.00 0.00
Maximum of Months 3351.01 1706.03 2688.58 1685.93 1137.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 286.04 1176.29 452.23 185.23 267.00 0.00 0.00
February 469.07 1211.08 666.88 292.89 373.98 0.00 0.00
March 907.32 825.52 984.73 454.62 530.11 0.00 0.00
April 1123.39 610.54 1076.26 460.50 615.76 0.00 0.00
May 1483.56 392.80 1253.74 476.12 777.62 0.00 0.00
June 1824.60 227.38 1372.18 553.44 818.74 0.00 0.00
July 1836.13 128.10 1285.12 483.93 801.18 0.00 0.00
August 2026.90 180.27 1421.69 658.15 763.54 0.00 0.00
September 1276.73 342.62 1009.29 441.05 568.23 0.00 0.00
October 1126.87 626.13 1000.63 486.58 514.05 0.00 0.00
November 314.83 895.72 469.89 135.80 334.09 0.00 0.00
December 266.77 1126.38 417.96 180.85 237.11 0.00 0.00
               
Annual Sum or Average 1082.91 641.97 952.88 401.68 551.19 0.00 0.00
Minimum of Months 266.77 128.10 417.96 135.80 237.11 0.00 0.00
Maximum of Months 2026.90 1211.08 1421.69 658.15 818.74 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 19.39 1856.18 328.95 0.00 328.95 0.00 0.00
February 39.56 1942.10 450.15 0.00 450.15 0.00 0.00
March 217.72 1306.96 624.24 0.00 624.24 0.00 0.00
April 465.53 936.31 749.80 2.13 747.67 0.00 0.00
May 924.79 577.23 994.74 33.15 961.60 0.00 0.00
June 1307.05 316.42 1054.91 56.68 998.23 0.00 0.00
July 1458.47 177.03 1019.47 36.87 982.61 0.00 0.00
August 1276.25 240.65 903.20 10.75 892.45 0.00 0.00
September 725.63 486.03 680.87 0.13 680.74 0.00 0.00
October 422.89 893.86 589.24 0.00 589.24 0.00 0.00
November 107.25 1346.55 413.30 0.00 413.30 0.00 0.00
December 11.61 1750.05 286.93 0.00 286.93 0.00 0.00
               
Annual Sum or Average 585.03 980.27 675.95 11.70 664.24 0.00 0.00
Minimum of Months 11.61 177.03 286.93 0.00 286.93 0.00 0.00
Maximum of Months 1458.47 1942.10 1054.91 56.68 998.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 280.81 1150.69 458.09 183.66 274.43 0.00 0.00
February 493.26 1165.88 710.40 331.40 379.00 0.00 0.00
March 788.04 837.46 906.25 385.43 520.81 0.00 0.00
April 1099.69 601.21 1087.56 476.38 611.17 0.00 0.00
May 1527.20 389.09 1318.98 527.14 791.84 0.00 0.00
June 1599.90 214.18 1222.42 442.51 779.91 0.00 0.00
July 1746.13 118.94 1227.77 443.07 784.70 0.00 0.00
August 1955.36 160.65 1382.50 623.37 759.13 0.00 0.00
September 1287.00 311.71 1031.07 462.60 568.47 0.00 0.00
October 1032.12 572.99 934.74 423.66 511.09 0.00 0.00
November 457.98 839.32 578.07 221.98 356.08 0.00 0.00
December 300.44 1074.54 450.35 211.46 238.89 0.00 0.00
               
Annual Sum or Average 1051.18 616.64 943.84 394.84 549.01 0.00 0.00
Minimum of Months 280.81 118.94 450.35 183.66 238.89 0.00 0.00
Maximum of Months 1955.36 1165.88 1382.50 623.37 791.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1671.97 1665.94 1701.70 1114.29 587.42 0.00 0.00
February 2236.61 1701.96 2244.49 1485.67 758.82 0.00 0.00
March 2141.84 1275.01 2024.95 1123.88 901.07 0.00 0.00
April 1717.00 964.43 1571.29 621.34 949.96 0.00 0.00
May 1598.80 620.86 1377.00 287.22 1089.78 0.00 0.00
June 1743.67 339.47 1292.28 197.54 1094.74 0.00 0.00
July 2034.33 182.74 1354.57 235.29 1119.28 0.00 0.00
August 2737.28 255.60 1808.87 670.94 1137.93 0.00 0.00
September 2623.40 498.09 1962.66 1015.17 947.49 0.00 0.00
October 3341.61 893.35 2688.68 1686.00 1002.69 0.00 0.00
November 1976.01 1263.47 1864.37 1119.64 744.73 0.00 0.00
December 1882.99 1554.28 1844.39 1309.40 535.00 0.00 0.00
               
Annual Sum or Average 2142.74 930.14 1809.23 902.59 906.64 0.00 0.00
Minimum of Months 1598.80 182.74 1292.28 197.54 535.00 0.00 0.00
Maximum of Months 3341.61 1701.96 2688.68 1686.00 1137.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 279.63 1177.27 452.24 185.24 267.00 0.00 0.00
February 456.87 1218.73 666.89 292.90 373.99 0.00 0.00
March 887.60 837.39 984.74 454.63 530.11 0.00 0.00
April 1102.60 623.02 1076.28 460.51 615.77 0.00 0.00
May 1459.43 406.19 1253.75 476.13 777.63 0.00 0.00
June 1810.68 229.13 1372.19 553.45 818.75 0.00 0.00
July 1826.26 128.19 1285.13 483.94 801.19 0.00 0.00
August 2021.76 174.31 1421.71 658.16 763.55 0.00 0.00
September 1275.86 328.64 1009.30 441.06 568.24 0.00 0.00
October 1129.07 594.29 1000.64 486.59 514.06 0.00 0.00
November 315.62 865.41 469.90 135.80 334.09 0.00 0.00
December 263.86 1107.62 417.97 180.85 237.11 0.00 0.00
               
Annual Sum or Average 1073.51 637.52 952.89 401.69 551.20 0.00 0.00
Minimum of Months 263.86 128.19 417.97 135.80 237.11 0.00 0.00
Maximum of Months 2021.76 1218.73 1421.71 658.16 818.75 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 61476148.24 0.474370E+10 0.881047E+09 0.00 0.881047E+09 0.00 0.00
February 0.108657E+09 0.446057E+10 0.108900E+10 0.00 0.108900E+10 0.00 0.00
March 0.615860E+09 0.328625E+10 0.167197E+10 0.00 0.167197E+10 0.00 0.00
April 0.124504E+10 0.226973E+10 0.194348E+10 5527855.32 0.193795E+10 0.00 0.00
May 0.250185E+10 0.147323E+10 0.266432E+10 88776796.13 0.257555E+10 0.00 0.00
June 0.338245E+10 0.791839E+09 0.273434E+10 0.146927E+09 0.258741E+10 0.00 0.00
July 0.388736E+10 0.462054E+09 0.273056E+10 98746035.06 0.263181E+10 0.00 0.00
August 0.340868E+10 0.621594E+09 0.241914E+10 28791201.70 0.239035E+10 0.00 0.00
September 0.189470E+10 0.118660E+10 0.176480E+10 330476.25 0.176447E+10 0.00 0.00
October 0.118208E+10 0.221937E+10 0.157822E+10 0.00 0.157822E+10 0.00 0.00
November 0.319256E+09 0.321827E+10 0.107126E+10 0.00 0.107126E+10 0.00 0.00
December 41805694.77 0.438648E+10 0.768507E+09 0.00 0.768507E+09 0.00 0.00
               
Annual Sum or Average 0.186492E+11 0.291197E+11 0.213166E+11 0.369100E+09 0.209475E+11 0.00 0.00
Minimum of Months 41805694.77 0.462054E+09 0.768507E+09 0.00 0.768507E+09 0.00 0.00
Maximum of Months 0.388736E+10 0.474370E+10 0.273434E+10 0.146927E+09 0.263181E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.768566E+09 0.293901E+10 0.122695E+10 0.491907E+09 0.735040E+09 0.00 0.00
February 0.122061E+10 0.267745E+10 0.171860E+10 0.801726E+09 0.916869E+09 0.00 0.00
March 0.213689E+10 0.211392E+10 0.242729E+10 0.103234E+10 0.139495E+10 0.00 0.00
April 0.287355E+10 0.147029E+10 0.281895E+10 0.123479E+10 0.158416E+10 0.00 0.00
May 0.410000E+10 0.997447E+09 0.353276E+10 0.141190E+10 0.212086E+10 0.00 0.00
June 0.414072E+10 0.536872E+09 0.316850E+10 0.114698E+10 0.202153E+10 0.00 0.00
July 0.466250E+10 0.310142E+09 0.328845E+10 0.118672E+10 0.210173E+10 0.00 0.00
August 0.522665E+10 0.415931E+09 0.370288E+10 0.166963E+10 0.203325E+10 0.00 0.00
September 0.334225E+10 0.765629E+09 0.267254E+10 0.119906E+10 0.147348E+10 0.00 0.00
October 0.279348E+10 0.143445E+10 0.250362E+10 0.113473E+10 0.136889E+10 0.00 0.00
November 0.122789E+10 0.201820E+10 0.149835E+10 0.575381E+09 0.922968E+09 0.00 0.00
December 0.830716E+09 0.269512E+10 0.120621E+10 0.566362E+09 0.639847E+09 0.00 0.00
               
Annual Sum or Average 0.333238E+11 0.183745E+11 0.297651E+11 0.124515E+11 0.173136E+11 0.00 0.00
Minimum of Months 0.768566E+09 0.310142E+09 0.120621E+10 0.491907E+09 0.639847E+09 0.00 0.00
Maximum of Months 0.522665E+10 0.293901E+10 0.370288E+10 0.166963E+10 0.212086E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.451097E+10 0.424233E+10 0.455785E+10 0.298451E+10 0.157334E+10 0.00 0.00
February 0.545897E+10 0.389664E+10 0.542987E+10 0.359413E+10 0.183574E+10 0.00 0.00
March 0.577163E+10 0.320781E+10 0.542364E+10 0.301021E+10 0.241342E+10 0.00 0.00
April 0.448160E+10 0.234478E+10 0.407279E+10 0.161050E+10 0.246229E+10 0.00 0.00
May 0.429882E+10 0.158014E+10 0.368817E+10 0.769294E+09 0.291888E+10 0.00 0.00
June 0.451094E+10 0.846511E+09 0.334958E+10 0.512019E+09 0.283757E+10 0.00 0.00
July 0.542851E+10 0.474186E+09 0.362807E+10 0.630195E+09 0.299788E+10 0.00 0.00
August 0.731491E+10 0.659619E+09 0.484489E+10 0.179705E+10 0.304784E+10 0.00 0.00
September 0.680554E+10 0.122140E+10 0.508723E+10 0.263132E+10 0.245590E+10 0.00 0.00
October 0.897992E+10 0.223980E+10 0.720137E+10 0.451578E+10 0.268559E+10 0.00 0.00
November 0.518555E+10 0.303452E+10 0.483245E+10 0.290212E+10 0.193033E+10 0.00 0.00
December 0.510025E+10 0.389308E+10 0.494002E+10 0.350709E+10 0.143294E+10 0.00 0.00
               
Annual Sum or Average 0.678476E+11 0.276408E+11 0.570559E+11 0.284642E+11 0.285917E+11 0.00 0.00
Minimum of Months 0.429882E+10 0.474186E+09 0.334958E+10 0.512019E+09 0.143294E+10 0.00 0.00
Maximum of Months 0.897992E+10 0.424233E+10 0.720137E+10 0.451578E+10 0.304784E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.759572E+09 0.300722E+10 0.121127E+10 0.496140E+09 0.715130E+09 0.00 0.00
February 0.111962E+10 0.279756E+10 0.161333E+10 0.708583E+09 0.904751E+09 0.00 0.00
March 0.239905E+10 0.210886E+10 0.263753E+10 0.121768E+10 0.141985E+10 0.00 0.00
April 0.288031E+10 0.151503E+10 0.278971E+10 0.119364E+10 0.159606E+10 0.00 0.00
May 0.392248E+10 0.103425E+10 0.335805E+10 0.127526E+10 0.208279E+10 0.00 0.00
June 0.468680E+10 0.571540E+09 0.355673E+10 0.143453E+10 0.212220E+10 0.00 0.00
July 0.487754E+10 0.332405E+09 0.344210E+10 0.129619E+10 0.214591E+10 0.00 0.00
August 0.540560E+10 0.450162E+09 0.380790E+10 0.176281E+10 0.204509E+10 0.00 0.00
September 0.331646E+10 0.803143E+09 0.261610E+10 0.114323E+10 0.147287E+10 0.00 0.00
October 0.305462E+10 0.148102E+10 0.268013E+10 0.130328E+10 0.137685E+10 0.00 0.00
November 0.850405E+09 0.207474E+10 0.121798E+10 0.352004E+09 0.865974E+09 0.00 0.00
December 0.723560E+09 0.277619E+10 0.111948E+10 0.484402E+09 0.635077E+09 0.00 0.00
               
Annual Sum or Average 0.339960E+11 0.189521E+11 0.300503E+11 0.126677E+11 0.173826E+11 0.00 0.00
Minimum of Months 0.723560E+09 0.332405E+09 0.111948E+10 0.352004E+09 0.635077E+09 0.00 0.00
Maximum of Months 0.540560E+10 0.300722E+10 0.380790E+10 0.176281E+10 0.214591E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 56976266.46 0.494056E+10 0.881027E+09 0.00 0.881027E+09 0.00 0.00
February 0.107424E+09 0.461739E+10 0.108897E+10 0.00 0.108897E+10 0.00 0.00
March 0.647744E+09 0.336176E+10 0.167193E+10 0.00 0.167193E+10 0.00 0.00
April 0.130012E+10 0.229363E+10 0.194344E+10 5527692.85 0.193791E+10 0.00 0.00
May 0.260793E+10 0.143786E+10 0.266427E+10 88774186.74 0.257549E+10 0.00 0.00
June 0.345555E+10 0.771981E+09 0.273428E+10 0.146923E+09 0.258736E+10 0.00 0.00
July 0.395866E+10 0.439208E+09 0.273050E+10 98743132.64 0.263176E+10 0.00 0.00
August 0.344514E+10 0.623773E+09 0.241909E+10 28790355.45 0.239030E+10 0.00 0.00
September 0.189077E+10 0.126892E+10 0.176477E+10 330466.53 0.176444E+10 0.00 0.00
October 0.113375E+10 0.244043E+10 0.157819E+10 0.00 0.157819E+10 0.00 0.00
November 0.275454E+09 0.357853E+10 0.107124E+10 0.00 0.107124E+10 0.00 0.00
December 31436441.12 0.473246E+10 0.768490E+09 0.00 0.768490E+09 0.00 0.00
               
Annual Sum or Average 0.189110E+11 0.305065E+11 0.213162E+11 0.369089E+09 0.209471E+11 0.00 0.00
Minimum of Months 31436441.12 0.439208E+09 0.768490E+09 0.00 0.768490E+09 0.00 0.00
Maximum of Months 0.395866E+10 0.494056E+10 0.273428E+10 0.146923E+09 0.263176E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.765695E+09 0.308509E+10 0.122693E+10 0.491897E+09 0.735030E+09 0.00 0.00
February 0.121761E+10 0.280832E+10 0.171857E+10 0.801710E+09 0.916858E+09 0.00 0.00
March 0.216065E+10 0.220477E+10 0.242725E+10 0.103232E+10 0.139493E+10 0.00 0.00
April 0.290226E+10 0.153030E+10 0.281891E+10 0.123476E+10 0.158414E+10 0.00 0.00
May 0.415702E+10 0.100969E+10 0.353270E+10 0.141188E+10 0.212083E+10 0.00 0.00
June 0.418445E+10 0.544339E+09 0.316846E+10 0.114695E+10 0.202150E+10 0.00 0.00
July 0.470369E+10 0.315354E+09 0.328840E+10 0.118670E+10 0.210171E+10 0.00 0.00
August 0.525222E+10 0.443136E+09 0.370282E+10 0.166960E+10 0.203323E+10 0.00 0.00
September 0.334091E+10 0.846511E+09 0.267250E+10 0.119904E+10 0.147346E+10 0.00 0.00
October 0.276080E+10 0.161672E+10 0.250358E+10 0.113470E+10 0.136888E+10 0.00 0.00
November 0.117799E+10 0.227309E+10 0.149833E+10 0.575370E+09 0.922955E+09 0.00 0.00
December 0.807846E+09 0.293734E+10 0.120619E+10 0.566351E+09 0.639839E+09 0.00 0.00
               
Annual Sum or Average 0.334311E+11 0.196147E+11 0.297646E+11 0.124513E+11 0.173134E+11 0.00 0.00
Minimum of Months 0.765695E+09 0.315354E+09 0.120619E+10 0.491897E+09 0.639839E+09 0.00 0.00
Maximum of Months 0.525222E+10 0.308509E+10 0.370282E+10 0.166960E+10 0.212083E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.459016E+10 0.445599E+10 0.455767E+10 0.298438E+10 0.157328E+10 0.00 0.00
February 0.553792E+10 0.412722E+10 0.542966E+10 0.359398E+10 0.183567E+10 0.00 0.00
March 0.587792E+10 0.335757E+10 0.542343E+10 0.301009E+10 0.241335E+10 0.00 0.00
April 0.457088E+10 0.240362E+10 0.407265E+10 0.161044E+10 0.246221E+10 0.00 0.00
May 0.442545E+10 0.155505E+10 0.368805E+10 0.769262E+09 0.291879E+10 0.00 0.00
June 0.459192E+10 0.839017E+09 0.334948E+10 0.511997E+09 0.283748E+10 0.00 0.00
July 0.549524E+10 0.470031E+09 0.362795E+10 0.630169E+09 0.299779E+10 0.00 0.00
August 0.735626E+10 0.703232E+09 0.484472E+10 0.179697E+10 0.304775E+10 0.00 0.00
September 0.681982E+10 0.135930E+10 0.508704E+10 0.263121E+10 0.245583E+10 0.00 0.00
October 0.897535E+10 0.256214E+10 0.720109E+10 0.451559E+10 0.268550E+10 0.00 0.00
November 0.516811E+10 0.341112E+10 0.483226E+10 0.290200E+10 0.193027E+10 0.00 0.00
December 0.511329E+10 0.426287E+10 0.493982E+10 0.350694E+10 0.143289E+10 0.00 0.00
               
Annual Sum or Average 0.685223E+11 0.295072E+11 0.570538E+11 0.284630E+11 0.285908E+11 0.00 0.00
Minimum of Months 0.442545E+10 0.470031E+09 0.334948E+10 0.511997E+09 0.143289E+10 0.00 0.00
Maximum of Months 0.897535E+10 0.445599E+10 0.720109E+10 0.451559E+10 0.304775E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.766125E+09 0.315058E+10 0.121125E+10 0.496132E+09 0.715122E+09 0.00 0.00
February 0.113476E+10 0.292984E+10 0.161331E+10 0.708571E+09 0.904742E+09 0.00 0.00
March 0.243017E+10 0.221107E+10 0.263749E+10 0.121766E+10 0.141984E+10 0.00 0.00
April 0.291181E+10 0.158251E+10 0.278967E+10 0.119362E+10 0.159605E+10 0.00 0.00
May 0.397357E+10 0.105208E+10 0.335801E+10 0.127524E+10 0.208277E+10 0.00 0.00
June 0.472937E+10 0.589373E+09 0.355668E+10 0.143451E+10 0.212218E+10 0.00 0.00
July 0.491788E+10 0.343102E+09 0.344206E+10 0.129617E+10 0.214589E+10 0.00 0.00
August 0.542884E+10 0.482829E+09 0.380785E+10 0.176278E+10 0.204507E+10 0.00 0.00
September 0.330929E+10 0.888082E+09 0.261607E+10 0.114321E+10 0.147286E+10 0.00 0.00
October 0.301822E+10 0.167704E+10 0.268009E+10 0.130326E+10 0.137683E+10 0.00 0.00
November 0.816032E+09 0.232170E+10 0.121796E+10 0.351999E+09 0.865964E+09 0.00 0.00
December 0.714528E+09 0.301691E+10 0.111946E+10 0.484394E+09 0.635070E+09 0.00 0.00
               
Annual Sum or Average 0.341506E+11 0.202451E+11 0.300499E+11 0.126675E+11 0.173824E+11 0.00 0.00
Minimum of Months 0.714528E+09 0.343102E+09 0.111946E+10 0.351999E+09 0.635070E+09 0.00 0.00
Maximum of Months 0.542884E+10 0.315058E+10 0.380785E+10 0.176278E+10 0.214589E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 51924469.44 0.497159E+10 0.881047E+09 0.00 0.881047E+09 0.00 0.00
February 95699420.56 0.469832E+10 0.108900E+10 0.00 0.108900E+10 0.00 0.00
March 0.583142E+09 0.350057E+10 0.167197E+10 0.00 0.167197E+10 0.00 0.00
April 0.120665E+10 0.242692E+10 0.194348E+10 5527855.32 0.193795E+10 0.00 0.00
May 0.247697E+10 0.154606E+10 0.266432E+10 88776796.13 0.257555E+10 0.00 0.00
June 0.338786E+10 0.820162E+09 0.273434E+10 0.146927E+09 0.258741E+10 0.00 0.00
July 0.390636E+10 0.474159E+09 0.273056E+10 98746035.06 0.263181E+10 0.00 0.00
August 0.341830E+10 0.644561E+09 0.241914E+10 28791201.70 0.239035E+10 0.00 0.00
September 0.188083E+10 0.125978E+10 0.176480E+10 330476.25 0.176447E+10 0.00 0.00
October 0.113268E+10 0.239412E+10 0.157822E+10 0.00 0.157822E+10 0.00 0.00
November 0.277998E+09 0.349025E+10 0.107126E+10 0.00 0.107126E+10 0.00 0.00
December 31098996.03 0.468733E+10 0.768507E+09 0.00 0.768507E+09 0.00 0.00
               
Annual Sum or Average 0.184495E+11 0.309138E+11 0.213166E+11 0.369100E+09 0.209475E+11 0.00 0.00
Minimum of Months 31098996.03 0.474159E+09 0.768507E+09 0.00 0.768507E+09 0.00 0.00
Maximum of Months 0.390636E+10 0.497159E+10 0.273434E+10 0.146927E+09 0.263181E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.752117E+09 0.308200E+10 0.122695E+10 0.491907E+09 0.735040E+09 0.00 0.00
February 0.119328E+10 0.282049E+10 0.171860E+10 0.801726E+09 0.916869E+09 0.00 0.00
March 0.211069E+10 0.224305E+10 0.242729E+10 0.103234E+10 0.139495E+10 0.00 0.00
April 0.285039E+10 0.155833E+10 0.281895E+10 0.123479E+10 0.158416E+10 0.00 0.00
May 0.409045E+10 0.104215E+10 0.353276E+10 0.141190E+10 0.212086E+10 0.00 0.00
June 0.414694E+10 0.555148E+09 0.316850E+10 0.114698E+10 0.202153E+10 0.00 0.00
July 0.467684E+10 0.318565E+09 0.328845E+10 0.118672E+10 0.210173E+10 0.00 0.00
August 0.523723E+10 0.430291E+09 0.370288E+10 0.166963E+10 0.203325E+10 0.00 0.00
September 0.333589E+10 0.807948E+09 0.267254E+10 0.119906E+10 0.147348E+10 0.00 0.00
October 0.276442E+10 0.153470E+10 0.250362E+10 0.113473E+10 0.136889E+10 0.00 0.00
November 0.118709E+10 0.217552E+10 0.149835E+10 0.575381E+09 0.922968E+09 0.00 0.00
December 0.804706E+09 0.287805E+10 0.120621E+10 0.566362E+09 0.639847E+09 0.00 0.00
               
Annual Sum or Average 0.331500E+11 0.194462E+11 0.297651E+11 0.124515E+11 0.173136E+11 0.00 0.00
Minimum of Months 0.752117E+09 0.318565E+09 0.120621E+10 0.491907E+09 0.639847E+09 0.00 0.00
Maximum of Months 0.523723E+10 0.308200E+10 0.370288E+10 0.166963E+10 0.212086E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.447819E+10 0.446204E+10 0.455785E+10 0.298451E+10 0.157334E+10 0.00 0.00
February 0.541081E+10 0.411738E+10 0.542987E+10 0.359413E+10 0.183574E+10 0.00 0.00
March 0.573671E+10 0.341499E+10 0.542364E+10 0.301021E+10 0.241342E+10 0.00 0.00
April 0.445046E+10 0.249982E+10 0.407279E+10 0.161050E+10 0.246229E+10 0.00 0.00
May 0.428224E+10 0.166290E+10 0.368817E+10 0.769294E+09 0.291888E+10 0.00 0.00
June 0.451960E+10 0.879915E+09 0.334958E+10 0.512019E+09 0.283757E+10 0.00 0.00
July 0.544874E+10 0.489438E+09 0.362807E+10 0.630195E+09 0.299788E+10 0.00 0.00
August 0.733152E+10 0.684612E+09 0.484489E+10 0.179705E+10 0.304784E+10 0.00 0.00
September 0.679985E+10 0.129105E+10 0.508723E+10 0.263132E+10 0.245590E+10 0.00 0.00
October 0.895015E+10 0.239274E+10 0.720137E+10 0.451578E+10 0.268559E+10 0.00 0.00
November 0.512183E+10 0.327492E+10 0.483245E+10 0.290212E+10 0.193033E+10 0.00 0.00
December 0.504340E+10 0.416299E+10 0.494002E+10 0.350709E+10 0.143294E+10 0.00 0.00
               
Annual Sum or Average 0.675735E+11 0.293328E+11 0.570559E+11 0.284642E+11 0.285917E+11 0.00 0.00
Minimum of Months 0.428224E+10 0.489438E+09 0.334958E+10 0.512019E+09 0.143294E+10 0.00 0.00
Maximum of Months 0.895015E+10 0.446204E+10 0.720137E+10 0.451578E+10 0.304784E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.748968E+09 0.315320E+10 0.121127E+10 0.496140E+09 0.715130E+09 0.00 0.00
February 0.110526E+10 0.294835E+10 0.161333E+10 0.708583E+09 0.904751E+09 0.00 0.00
March 0.237735E+10 0.224287E+10 0.263753E+10 0.121768E+10 0.141985E+10 0.00 0.00
April 0.285794E+10 0.161486E+10 0.278971E+10 0.119364E+10 0.159606E+10 0.00 0.00
May 0.390893E+10 0.108795E+10 0.335805E+10 0.127526E+10 0.208279E+10 0.00 0.00
June 0.469329E+10 0.593898E+09 0.355673E+10 0.143453E+10 0.212220E+10 0.00 0.00
July 0.489144E+10 0.343357E+09 0.344210E+10 0.129619E+10 0.214591E+10 0.00 0.00
August 0.541508E+10 0.466864E+09 0.380790E+10 0.176281E+10 0.204509E+10 0.00 0.00
September 0.330702E+10 0.851826E+09 0.261610E+10 0.114323E+10 0.147287E+10 0.00 0.00
October 0.302411E+10 0.159176E+10 0.268013E+10 0.130328E+10 0.137685E+10 0.00 0.00
November 0.818095E+09 0.224314E+10 0.121798E+10 0.352004E+09 0.865974E+09 0.00 0.00
December 0.706723E+09 0.296665E+10 0.111948E+10 0.484402E+09 0.635077E+09 0.00 0.00
               
Annual Sum or Average 0.338542E+11 0.201047E+11 0.300503E+11 0.126677E+11 0.173826E+11 0.00 0.00
Minimum of Months 0.706723E+09 0.343357E+09 0.111948E+10 0.352004E+09 0.635077E+09 0.00 0.00
Maximum of Months 0.541508E+10 0.315320E+10 0.380790E+10 0.176281E+10 0.214591E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.496831E+10 -0.472086E+10 0.00 0.00 744.00 0.00 -247442931.4 60.05 0.00 0.00
February 0.455146E+10 -0.433271E+10 0.00 0.00 672.00 0.00 -218749014.1 60.05 0.00 0.00
March 0.525293E+10 -0.501498E+10 0.00 0.00 744.00 0.00 -237943906.4 60.05 0.00 0.00
April 0.451368E+10 -0.428604E+10 0.00 0.00 720.00 0.00 -227641422.5 60.05 0.00 0.00
May 0.452044E+10 -0.428732E+10 0.00 0.00 744.00 0.00 -233116664.2 60.05 0.00 0.00
June 0.418108E+10 -0.395667E+10 0.00 0.00 720.00 0.00 -224409315.8 60.05 0.00 0.00
July 0.376682E+10 -0.353550E+10 0.00 0.00 744.00 0.00 -231319707.4 60.05 0.00 0.00
August 0.408938E+10 -0.385767E+10 0.00 0.00 744.00 0.00 -231712913.0 60.05 0.00 0.00
September 0.380418E+10 -0.358006E+10 0.00 0.00 720.00 0.00 -224118142.0 60.05 0.00 0.00
October 0.416827E+10 -0.393596E+10 0.00 0.00 744.00 0.00 -232308168.5 60.05 0.00 0.00
November 0.439579E+10 -0.416705E+10 0.00 0.00 720.00 0.00 -228738971.0 60.05 0.00 0.00
December 0.464019E+10 -0.439982E+10 0.00 0.00 744.00 0.00 -240365007.4 60.05 0.00 0.00
                     
Annual Sum or Average 0.528525E+11 -0.500746E+11 0.00 0.00 8760.00 0.00 -0.277787E+10 60.05 0.00 0.00
Minimum of Months 0.376682E+10 -0.501498E+10 0.00 0.00 672.00 0.00 -247442931.4 60.05 0.00 0.00
Maximum of Months 0.525293E+10 -0.353550E+10 0.00 0.00 744.00 0.00 -218749014.1 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 6520.69 36.70 196.17 241.83 3398.41 33.31 185.67 196.83
February 216.00 0.50 0.48 01-FEB-07:49 9284.94 37.55 210.00 258.50 2132.87 26.56 177.00 233.50
March 275.00 0.52 0.48 01-MAR-07:10 3285.58 21.58 57.17 318.50 1596.66 21.72 171.17 285.33
April 261.17 0.51 0.48 01-APR-14:39 2079.63 18.96 2.00 339.17 1231.31 21.19 151.67 299.17
May 372.00 0.52 0.48 01-MAY-06:10 1808.98 18.86 0.00 390.67 1017.18 21.03 225.83 347.50
June 351.83 0.51 0.48 01-JUN-05:00 1722.91 18.84 0.00 383.33 981.70 21.07 208.50 340.50
July 365.17 0.51 0.48 01-JUL-06:10 1901.43 19.10 1.17 390.67 1060.71 21.32 238.33 344.50
August 389.17 0.52 0.48 01-AUG-06:10 2112.92 19.07 8.17 370.67 1226.77 21.28 239.33 340.17
September 285.33 0.51 0.48 01-SEP-06:30 3816.36 21.31 36.67 324.00 1470.88 21.49 179.00 289.67
October 305.50 0.50 0.48 01-OCT-14:39 10157.18 36.13 283.50 307.00 2058.56 23.61 258.83 289.17
November 240.83 0.50 0.48 01-NOV-06:00 6465.51 36.32 235.17 257.17 2281.24 29.45 223.33 236.17
December 211.17 0.51 0.48 01-DEC-07:40 6080.04 36.57 198.50 243.50 5426.00 39.05 208.00 214.67
                         
Annual Sum or Average 3472.67 0.51     4199.02 25.33 1228.50 3825.00 1794.48 24.16 2466.67 3417.17
Minimum of Months 199.50 0.50 0.48   1722.91 18.84 0.00 241.83 981.70 21.03 151.67 196.83
Maximum of Months 389.17 0.52 0.48   10157.18 37.55 283.50 390.67 5426.00 39.05 258.83 347.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-07:49 1984.23 21.32 61.00 221.33 1128.54 23.70 88.67 159.17
February 216.00 0.52 0.48 01-FEB-07:40 2824.27 24.02 80.67 245.50 1630.91 24.65 92.50 207.50
March 275.00 0.53 0.48 01-MAR-06:00 2927.68 21.41 71.50 313.50 1640.11 22.58 77.83 260.67
April 261.17 0.51 0.48 01-APR-06:19 3834.32 22.29 80.67 341.33 1561.34 22.92 53.33 302.50
May 372.00 0.51 0.48 01-MAY-05:40 3187.13 21.16 99.17 396.67 1730.16 22.45 73.67 355.17
June 351.83 0.51 0.48 01-JUN-04:00 2843.04 20.47 80.67 387.50 1592.55 22.73 70.00 353.17
July 365.17 0.51 0.48 01-JUL-04:00 2937.38 21.08 89.67 396.00 1593.35 22.49 69.83 358.50
August 389.17 0.51 0.48 01-AUG-05:40 3921.38 23.18 128.17 373.17 1636.90 22.86 83.00 346.33
September 285.33 0.51 0.48 01-SEP-05:49 3407.26 22.18 82.67 320.67 1496.69 22.76 64.33 285.83
October 305.50 0.51 0.48 01-OCT-14:39 3025.40 23.07 91.17 293.67 1602.17 23.89 138.17 265.67
November 240.83 0.52 0.48 01-NOV-06:49 2048.23 22.04 73.33 244.50 1053.53 22.56 114.33 200.67
December 211.17 0.55 0.48 01-DEC-07:40 1901.11 23.21 81.17 221.67 1106.82 24.09 92.33 157.50
                         
Annual Sum or Average 3472.67 0.52     2991.42 22.04 1019.83 3755.50 1515.55 23.04 1018.00 3252.67
Minimum of Months 199.50 0.51 0.48   1901.11 20.47 61.00 221.33 1053.53 22.45 53.33 157.50
Maximum of Months 389.17 0.55 0.48   3921.38 24.02 128.17 396.67 1730.16 24.65 138.17 358.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.56 0.48 01-JAN-09:20 636.47 15.58 0.00 207.67 387.01 18.00 0.00 118.67
February 216.00 0.54 0.48 01-FEB-08:00 690.32 16.54 0.00 230.50 444.44 19.05 0.00 163.50
March 275.00 0.53 0.48 01-MAR-07:40 913.57 17.41 0.00 308.00 566.31 19.66 13.50 238.00
April 261.17 0.51 0.48 01-APR-14:39 1028.27 18.39 0.00 344.00 639.88 20.59 51.67 296.00
May 372.00 0.50 0.48 01-MAY-05:49 1325.81 19.17 8.00 403.67 761.65 21.29 169.17 363.17
June 351.83 0.50 0.48 01-JUN-05:10 1495.76 22.45 75.17 402.00 839.92 23.66 240.00 373.50
July 365.17 0.50 0.48 01-JUL-04:00 1472.15 20.29 27.00 407.50 831.57 23.23 245.67 372.00
August 389.17 0.51 0.48 01-AUG-05:00 1211.60 18.80 0.00 378.00 728.73 20.98 166.67 350.33
September 285.33 0.52 0.48 01-SEP-06:30 942.84 17.96 0.00 320.17 592.19 20.23 28.67 269.67
October 305.50 0.52 0.48 01-OCT-14:39 856.62 17.61 0.00 289.17 549.52 20.02 0.00 244.50
November 240.83 0.54 0.48 01-NOV-07:49 709.67 16.29 0.00 234.17 422.86 18.61 0.00 156.00
December 211.17 0.59 0.48 01-DEC-09:20 513.93 14.58 0.00 196.67 321.97 17.17 0.00 89.50
                         
Annual Sum or Average 3472.67 0.52     1046.62 18.30 110.17 3721.50 624.55 20.55 915.33 3034.83
Minimum of Months 199.50 0.50 0.48   513.93 14.58 0.00 196.67 321.97 17.17 0.00 89.50
Maximum of Months 389.17 0.59 0.48   1495.76 22.45 75.17 407.50 839.92 23.66 245.67 373.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-09:09 1976.07 23.25 73.33 228.83 1116.75 23.84 79.00 162.67
February 216.00 0.52 0.48 01-FEB-08:00 2203.40 21.44 57.00 244.67 1189.39 23.38 76.67 205.00
March 275.00 0.51 0.48 01-MAR-07:49 3187.72 23.69 95.83 317.83 1802.94 24.58 92.50 272.83
April 261.17 0.51 0.48 01-APR-14:39 3627.64 21.97 76.83 340.17 1507.63 21.52 40.50 299.83
May 372.00 0.51 0.48 01-MAY-06:30 3422.05 19.23 69.33 395.33 1520.91 19.01 0.00 357.50
June 351.83 0.50 0.48 01-JUN-06:10 3310.52 15.88 1.83 391.33 1792.24 19.19 2.50 351.83
July 365.17 0.50 0.48 01-JUL-06:10 3115.08 18.54 49.00 397.33 1670.19 19.31 6.50 356.17
August 389.17 0.51 0.48 01-AUG-06:30 3999.16 20.32 86.33 373.67 1744.88 19.44 20.00 346.50
September 285.33 0.51 0.48 01-SEP-07:10 3229.52 22.41 85.33 322.50 1687.85 23.14 68.67 284.67
October 305.50 0.50 0.48 01-OCT-14:39 3460.64 24.13 109.33 303.67 1469.04 23.45 119.67 276.00
November 240.83 0.52 0.48 01-NOV-07:49 1674.03 21.06 68.83 245.67 916.06 23.41 100.33 203.83
December 211.17 0.55 0.48 01-DEC-09:09 1566.14 21.17 67.50 220.17 892.97 23.27 76.33 163.00
                         
Annual Sum or Average 3472.67 0.51     3034.67 20.80 840.50 3781.17 1495.71 21.58 682.67 3279.83
Minimum of Months 199.50 0.50 0.48   1566.14 15.88 1.83 220.17 892.97 19.01 0.00 162.67
Maximum of Months 389.17 0.55 0.48   3999.16 24.13 109.33 397.33 1802.94 24.58 119.67 357.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 6344.17 36.48 196.17 238.33 3267.69 32.20 144.00 194.00
February 216.00 0.50 0.48 01-FEB-07:49 9101.11 37.28 210.00 256.83 2007.73 24.95 80.00 233.83
March 275.00 0.52 0.48 01-MAR-07:10 3162.74 18.17 45.83 318.33 1483.58 19.20 40.67 280.33
April 261.17 0.52 0.48 01-APR-14:39 1975.43 15.25 0.00 338.33 1155.71 18.83 8.17 295.17
May 372.00 0.52 0.48 01-MAY-06:10 1732.66 15.24 0.00 389.33 967.45 18.67 1.00 343.17
June 351.83 0.52 0.48 01-JUN-05:00 1653.04 15.23 0.00 380.50 937.64 18.74 0.00 336.00
July 365.17 0.51 0.48 01-JUL-06:10 1822.94 15.43 0.00 388.83 1010.61 18.92 1.83 341.17
August 389.17 0.52 0.48 01-AUG-06:19 2013.34 15.52 0.00 368.83 1157.48 19.00 19.83 336.17
September 285.33 0.51 0.48 01-SEP-06:30 3681.18 17.88 29.50 322.33 1369.26 18.98 20.50 287.17
October 305.50 0.50 0.48 01-OCT-14:39 9957.48 35.44 281.00 306.33 1913.18 20.88 46.50 287.33
November 240.83 0.51 0.48 01-NOV-06:00 6286.24 35.30 228.83 255.83 2158.10 27.60 121.17 234.33
December 211.17 0.52 0.48 01-DEC-07:40 5899.55 35.74 195.67 240.17 5293.51 38.86 208.00 212.00
                         
Annual Sum or Average 3472.67 0.51     4073.13 22.75 1187.00 3804.00 1703.99 22.03 691.67 3380.67
Minimum of Months 199.50 0.50 0.48   1653.04 15.23 0.00 238.33 937.64 18.67 0.00 194.00
Maximum of Months 389.17 0.52 0.48   9957.48 37.28 281.00 389.33 5293.51 38.86 208.00 343.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-07:49 1926.39 20.84 61.00 219.00 1084.85 23.48 82.67 156.00
February 216.00 0.52 0.48 01-FEB-07:40 2755.80 23.57 80.67 243.50 1576.58 24.45 82.83 202.67
March 275.00 0.53 0.48 01-MAR-06:00 2750.59 19.57 58.83 311.00 1577.81 22.37 68.67 253.17
April 261.17 0.51 0.48 01-APR-06:19 3743.14 21.83 80.67 338.83 1489.14 22.74 52.00 299.00
May 372.00 0.51 0.48 01-MAY-05:40 3091.89 20.71 99.17 395.83 1661.13 22.28 72.83 351.17
June 351.83 0.51 0.48 01-JUN-04:00 2759.53 19.99 80.67 385.00 1531.03 22.56 69.00 351.33
July 365.17 0.51 0.48 01-JUL-04:00 2846.26 20.59 89.17 394.50 1528.69 22.32 67.17 355.17
August 389.17 0.51 0.48 01-AUG-05:40 3778.34 21.41 111.67 371.33 1559.26 22.55 74.50 344.50
September 285.33 0.52 0.48 01-SEP-05:49 3321.46 21.70 82.67 319.67 1404.77 21.71 49.17 281.50
October 305.50 0.52 0.48 01-OCT-14:39 2940.32 22.59 91.17 291.33 1536.61 23.68 120.83 262.00
November 240.83 0.53 0.48 01-NOV-06:49 1981.68 21.38 72.00 242.33 1005.20 22.33 102.00 197.67
December 211.17 0.56 0.48 01-DEC-07:40 1762.73 20.41 64.00 215.00 1067.76 23.87 86.67 152.50
                         
Annual Sum or Average 3472.67 0.52     2891.11 21.16 971.67 3727.33 1451.12 22.77 928.33 3206.67
Minimum of Months 199.50 0.51 0.48   1762.73 19.57 58.83 215.00 1005.20 21.71 49.17 152.50
Maximum of Months 389.17 0.56 0.48   3778.34 23.57 111.67 395.83 1661.13 24.45 120.83 355.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.56 0.48 01-JAN-09:20 611.76 12.01 0.00 203.17 373.60 15.63 0.00 113.00
February 216.00 0.55 0.48 01-FEB-09:09 664.06 13.11 0.00 226.83 430.79 16.88 0.00 157.67
March 275.00 0.53 0.48 01-MAR-07:40 880.71 14.17 0.00 306.67 548.91 17.67 0.00 230.17
April 261.17 0.51 0.48 01-APR-14:39 992.14 15.17 0.00 342.50 620.83 18.72 0.00 291.50
May 372.00 0.51 0.48 01-MAY-05:00 1278.10 15.69 3.00 401.83 735.03 19.17 37.17 359.00
June 351.83 0.50 0.48 01-JUN-05:10 1438.31 18.89 62.83 398.83 810.13 21.83 77.17 371.50
July 365.17 0.50 0.48 01-JUL-04:00 1415.92 15.76 0.00 405.00 801.76 21.33 63.67 368.17
August 389.17 0.51 0.48 01-AUG-05:00 1168.62 15.60 0.00 377.67 705.56 19.11 8.33 346.67
September 285.33 0.52 0.48 01-SEP-06:40 909.11 14.78 0.00 318.17 574.47 18.33 0.00 264.00
October 305.50 0.52 0.48 01-OCT-14:39 823.40 14.42 0.00 286.67 532.15 18.04 0.00 239.83
November 240.83 0.55 0.48 01-NOV-07:49 682.75 12.62 0.00 231.17 408.08 16.21 0.00 147.33
December 211.17 0.60 0.48 01-DEC-09:20 493.39 10.89 0.00 190.83 311.02 14.70 0.00 84.50
                         
Annual Sum or Average 3472.67 0.52     1007.78 14.79 65.83 3689.33 603.84 18.52 186.33 2973.33
Minimum of Months 199.50 0.50 0.48   493.39 10.89 0.00 190.83 311.02 14.70 0.00 84.50
Maximum of Months 389.17 0.60 0.48   1438.31 18.89 62.83 405.00 810.13 21.83 77.17 371.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-09:20 1837.37 20.60 57.17 224.50 1073.79 23.71 77.33 158.50
February 216.00 0.52 0.48 01-FEB-09:09 2134.02 21.02 57.00 243.17 1103.38 22.18 66.50 200.00
March 275.00 0.51 0.48 01-MAR-07:49 3102.89 23.31 95.83 316.33 1734.52 24.40 88.83 265.50
April 261.17 0.51 0.48 01-APR-14:39 3536.36 21.54 76.83 337.83 1435.92 21.37 39.00 297.33
May 372.00 0.51 0.48 01-MAY-06:30 3335.10 18.76 69.17 393.83 1456.65 18.83 0.00 353.33
June 351.83 0.51 0.48 01-JUN-06:10 3207.76 15.35 1.83 389.83 1719.31 19.01 1.50 348.17
July 365.17 0.51 0.48 01-JUL-06:19 3017.06 18.06 49.00 395.67 1601.30 19.14 4.50 353.00
August 389.17 0.51 0.48 01-AUG-06:30 3852.83 19.87 86.33 371.17 1668.91 19.29 15.33 344.17
September 285.33 0.51 0.48 01-SEP-07:10 3145.33 22.00 85.33 321.00 1619.85 23.02 66.50 280.50
October 305.50 0.50 0.48 01-OCT-14:39 3368.04 23.75 109.33 302.33 1399.23 23.34 116.33 273.00
November 240.83 0.52 0.48 01-NOV-07:00 1624.02 20.65 68.83 243.67 876.50 23.12 95.17 198.00
December 211.17 0.55 0.48 01-DEC-09:20 1517.71 20.78 67.50 218.00 822.30 21.78 65.67 156.17
                         
Annual Sum or Average 3472.67 0.52     2940.90 20.24 824.17 3757.33 1428.28 21.27 636.67 3227.67
Minimum of Months 199.50 0.50 0.48   1517.71 15.35 1.83 218.00 822.30 18.83 0.00 156.17
Maximum of Months 389.17 0.55 0.48   3852.83 23.75 109.33 395.67 1734.52 24.40 116.33 353.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.51 0.48 01-JAN-07:49 6344.16 36.48 196.17 238.33 3267.57 32.20 144.00 194.00
February 216.00 0.50 0.48 01-FEB-07:49 9101.06 37.28 210.00 256.83 2007.62 24.95 80.00 233.83
March 275.00 0.52 0.48 01-MAR-07:10 3162.62 18.17 45.83 318.33 1483.48 19.20 40.67 280.33
April 261.17 0.52 0.48 01-APR-14:39 1975.32 15.26 0.00 338.33 1155.63 18.83 8.17 295.17
May 372.00 0.52 0.48 01-MAY-06:10 1732.56 15.25 0.00 389.33 967.38 18.68 1.00 343.17
June 351.83 0.52 0.48 01-JUN-05:00 1652.95 15.23 0.00 380.50 937.57 18.74 0.00 336.00
July 365.17 0.51 0.48 01-JUL-06:10 1822.84 15.43 0.00 388.83 1010.53 18.92 1.83 341.17
August 389.17 0.52 0.48 01-AUG-06:19 2013.23 15.52 0.00 368.83 1157.40 19.01 19.83 336.17
September 285.33 0.51 0.48 01-SEP-06:30 3681.06 17.88 29.50 322.33 1369.16 18.98 20.50 287.17
October 305.50 0.50 0.48 01-OCT-14:39 9957.39 35.45 281.00 306.33 1913.05 20.88 46.50 287.33
November 240.83 0.51 0.48 01-NOV-06:00 6286.20 35.30 228.83 255.83 2157.98 27.60 121.17 234.33
December 211.17 0.52 0.48 01-DEC-07:40 5899.56 35.74 195.67 240.17 5293.42 38.86 208.00 212.00
                         
Annual Sum or Average 3472.67 0.51     4073.04 22.75 1187.00 3804.00 1703.90 22.03 691.67 3380.67
Minimum of Months 199.50 0.50 0.48   1652.95 15.23 0.00 238.33 937.57 18.68 0.00 194.00
Maximum of Months 389.17 0.52 0.48   9957.39 37.28 281.00 389.33 5293.42 38.86 208.00 343.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.54 0.48 01-JAN-07:49 1926.36 20.84 61.00 219.00 1084.80 23.48 82.67 156.00
February 216.00 0.52 0.48 01-FEB-07:40 2755.79 23.57 80.67 243.50 1576.53 24.45 83.00 202.67
March 275.00 0.53 0.48 01-MAR-06:00 2750.56 19.57 58.83 311.00 1577.74 22.37 68.67 253.17
April 261.17 0.51 0.48 01-APR-06:19 3743.10 21.84 80.67 338.83 1489.07 22.74 52.00 299.00
May 372.00 0.51 0.48 01-MAY-05:40 3091.82 20.71 99.17 395.83 1661.04 22.28 72.83 351.17
June 351.83 0.51 0.48 01-JUN-04:00 2759.46 20.00 80.67 385.00 1530.96 22.56 69.00 351.33
July 365.17 0.51 0.48 01-JUL-04:00 2846.69 20.63 89.67 394.50 1528.60 22.32 67.17 355.17
August 389.17 0.51 0.48 01-AUG-05:40 3825.63 22.75 128.17 372.17 1559.18 22.55 74.50 344.50
September 285.33 0.52 0.48 01-SEP-05:49 3321.42 21.71 82.67 319.67 1404.70 21.71 49.17 281.50
October 305.50 0.52 0.48 01-OCT-14:39 2940.29 22.60 91.17 291.33 1536.54 23.68 120.83 262.00
November 240.83 0.53 0.48 01-NOV-06:49 1981.64 21.38 72.00 242.33 1005.14 22.33 102.00 197.67
December 211.17 0.56 0.48 01-DEC-07:40 1762.72 20.41 64.00 215.00 1067.72 23.87 86.67 152.50
                         
Annual Sum or Average 3472.67 0.52     2896.43 21.31 988.67 3728.17 1451.05 22.77 928.50 3206.67
Minimum of Months 199.50 0.51 0.48   1762.72 19.57 58.83 215.00 1005.14 21.71 49.17 152.50
Maximum of Months 389.17 0.56 0.48   3825.63 23.57 128.17 395.83 1661.04 24.45 120.83 355.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.56 0.48 01-JAN-09:20 611.75 12.01 0.00 203.17 373.58 15.63 0.00 113.00
February 216.00 0.55 0.48 01-FEB-09:09 664.06 13.11 0.00 226.83 430.77 16.88 0.00 157.67
March 275.00 0.53 0.48 01-MAR-07:40 880.69 14.17 0.00 306.67 548.87 17.67 0.00 230.17
April 261.17 0.51 0.48 01-APR-14:39 992.12 15.18 0.00 342.50 620.79 18.72 0.00 291.50
May 372.00 0.51 0.48 01-MAY-05:00 1278.05 15.69 3.00 401.83 734.98 19.18 37.17 359.00
June 351.83 0.50 0.48 01-JUN-05:10 1438.26 18.90 62.83 398.83 810.07 21.83 77.17 371.50
July 365.17 0.50 0.48 01-JUL-04:00 1415.87 15.76 0.00 405.00 801.71 21.33 63.67 368.17
August 389.17 0.51 0.48 01-AUG-05:00 1168.59 15.60 0.00 377.67 705.52 19.11 8.33 346.67
September 285.33 0.52 0.48 01-SEP-06:40 909.09 14.78 0.00 318.17 574.43 18.33 0.00 264.00
October 305.50 0.52 0.48 01-OCT-14:39 823.39 14.42 0.00 286.67 532.12 18.04 0.00 239.83
November 240.83 0.55 0.48 01-NOV-07:49 682.73 12.62 0.00 231.17 408.05 16.21 0.00 147.33
December 211.17 0.60 0.48 01-DEC-09:20 493.38 10.90 0.00 190.83 311.00 14.70 0.00 84.50
                         
Annual Sum or Average 3472.67 0.52     1007.75 14.79 65.83 3689.33 603.80 18.52 186.33 2973.33
Minimum of Months 199.50 0.50 0.48   493.38 10.90 0.00 190.83 311.00 14.70 0.00 84.50
Maximum of Months 389.17 0.60 0.48   1438.26 18.90 62.83 405.00 810.07 21.83 77.17 371.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.53 0.48 01-JAN-09:20 1837.35 20.60 57.17 224.50 1073.74 23.71 77.50 158.50
February 216.00 0.52 0.48 01-FEB-09:09 2134.01 21.02 57.00 243.17 1103.33 22.18 66.67 200.00
March 275.00 0.51 0.48 01-MAR-07:49 3102.86 23.31 95.83 316.33 1734.45 24.40 88.83 265.50
April 261.17 0.51 0.48 01-APR-14:39 3536.32 21.54 76.83 337.83 1435.84 21.37 39.00 297.33
May 372.00 0.51 0.48 01-MAY-06:30 3335.03 18.76 69.17 393.83 1456.56 18.83 0.00 353.33
June 351.83 0.51 0.48 01-JUN-06:10 3207.69 15.35 1.83 389.83 1719.22 19.01 1.50 348.17
July 365.17 0.51 0.48 01-JUL-06:19 3016.98 18.06 49.00 395.67 1601.21 19.14 4.50 353.00
August 389.17 0.51 0.48 01-AUG-06:30 3852.78 19.87 86.33 371.17 1668.83 19.29 15.33 344.17
September 285.33 0.51 0.48 01-SEP-07:10 3145.30 22.00 85.33 321.00 1619.78 23.02 66.50 280.50
October 305.50 0.50 0.48 01-OCT-14:39 3368.02 23.75 109.33 302.33 1399.17 23.34 116.33 273.00
November 240.83 0.52 0.48 01-NOV-07:00 1623.98 20.65 68.83 243.67 876.45 23.12 95.17 198.00
December 211.17 0.55 0.48 01-DEC-09:20 1517.70 20.78 67.50 218.00 822.26 21.78 65.67 156.17
                         
Annual Sum or Average 3472.67 0.52     2940.86 20.24 824.17 3757.33 1428.21 21.27 637.00 3227.67
Minimum of Months 199.50 0.50 0.48   1517.70 15.35 1.83 218.00 822.26 18.83 0.00 156.17
Maximum of Months 389.17 0.55 0.48   3852.78 23.75 109.33 395.67 1734.45 24.40 116.33 353.33



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.874547E+10 20372.08 02-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.882571E+10 23152.31 06-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.360491E+10 13197.00 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.396451E+09 6422.72 03-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 94590.61 4.86 31-MAY-15:40 0.00 0.00 0.00 0.00 0.00
June 814075.76 5.73 19-JUN-15:00 0.00 0.00 0.00 0.00 0.00
July 1555814.37 5.72 17-JUL-15:00 0.00 0.00 0.00 0.00 0.00
August 1555691.20 5.68 04-AUG-16:00 0.00 0.00 0.00 0.00 0.00
September 567253.20 5.36 06-SEP-16:00 0.00 0.00 0.00 0.00 0.00
October 11453911.27 3698.68 28-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.206307E+10 13605.83 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.562314E+10 13361.58 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.292748E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 94590.61 4.86   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.882571E+10 23152.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.637758E+09 11872.30 04-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.637758E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.637758E+09 11872.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.473108E+10 8313.43 03-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.381370E+10 8447.46 06-FEB-07:50 0.00 0.00 0.00 0.00 0.00
March 0.248944E+10 8309.15 06-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.129762E+10 8408.92 11-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.388788E+09 8370.40 12-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 1827442.53 1916.01 02-JUN-06:08 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 14911480.56 5979.45 20-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.239066E+09 8366.04 19-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.159595E+10 8351.17 03-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.300895E+10 8305.47 05-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175813E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.473108E+10 8447.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.200676E+10 6144.69 03-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.137283E+10 6227.50 06-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.399956E+09 6129.61 20-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.119124E+09 6121.09 21-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.229815E+09 6123.23 22-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.827822E+09 6129.42 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.495631E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.200676E+10 6227.50   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.342219E+10 7120.42 03-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.284014E+10 7232.49 06-FEB-07:50 0.00 0.00 0.00 0.00 0.00
March 0.972685E+09 7109.85 09-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.215714E+09 7107.02 03-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 85137.51 567.58 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.443315E+09 7104.60 20-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.146300E+10 7114.37 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.935712E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.342219E+10 7232.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.219757E+10 6254.10 03-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.163246E+10 6354.33 06-FEB-07:50 0.00 0.00 0.00 0.00 0.00
March 0.433146E+09 6240.94 10-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.125249E+09 6239.07 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 252134.71 1131.26 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.319486E+09 6234.97 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.980086E+09 6238.51 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.568825E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.219757E+10 6354.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.976887E+10 22590.84 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.982916E+10 24518.37 06-FEB-07:30 0.00 0.00 0.00 0.00 0.00
March 0.463452E+10 13989.65 23-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.766045E+09 7748.81 03-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 1622347.11 1292.72 01-MAY-06:08 0.00 0.00 0.00 0.00 0.00
June 537064.39 5.37 26-JUN-06:03 0.00 0.00 0.00 0.00 0.00
July 1216200.20 5.27 17-JUL-14:30 0.00 0.00 0.00 0.00 0.00
August 1292925.46 5.28 14-AUG-14:30 0.00 0.00 0.00 0.00 0.00
September 366496.62 5.30 05-SEP-09:10 0.00 0.00 0.00 0.00 0.00
October 85613324.71 4651.48 28-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.289830E+10 15197.50 24-NOV-07:06 0.00 0.00 0.00 0.00 0.00
December 0.702666E+10 14567.78 22-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.350142E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 366496.62 5.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.982916E+10 24518.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.193033E+10 16856.13 18-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.688746E+09 16805.12 28-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 33341881.99 16841.41 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 2733677.36 16662.49 03-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.149001E+09 16857.30 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.287263E+09 16840.05 26-DEC-07:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309141E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.193033E+10 16857.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.206606E+10 8940.29 04-JAN-07:06 0.00 0.00 0.00 0.00 0.00
February 0.133319E+10 8985.16 06-FEB-07:45 0.00 0.00 0.00 0.00 0.00
March 0.336117E+09 8917.68 10-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 96573911.16 8933.04 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 90482.97 80.72 28-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.363791E+09 8921.84 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.104863E+10 8928.39 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.524445E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.206606E+10 8985.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.215967E+10 6717.80 25-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.147777E+10 6749.22 06-FEB-07:30 0.00 0.00 0.00 0.00 0.00
March 0.417832E+09 6713.60 13-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.115408E+09 6696.65 14-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3577295.02 3108.54 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.493814E+09 6716.65 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.123587E+10 6720.67 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.590394E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.215967E+10 6749.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319131E+10 7594.31 13-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.243049E+10 7667.82 06-FEB-08:25 0.00 0.00 0.00 0.00 0.00
March 0.592579E+09 7587.32 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.107270E+09 7577.44 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1808008.83 1940.50 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.683083E+09 7589.65 25-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.170177E+10 7588.61 13-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.870831E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319131E+10 7667.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.229375E+10 6830.59 04-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.169898E+10 6919.85 06-FEB-08:04 0.00 0.00 0.00 0.00 0.00
March 0.470346E+09 6826.59 13-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.125828E+09 6838.41 03-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 271881.39 1238.21 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 4973055.77 2927.03 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.600826E+09 6829.65 21-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.136737E+10 6833.69 26-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.656235E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.229375E+10 6919.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104467E+11 24344.04 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.102811E+11 24291.37 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.494356E+10 16603.79 23-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.104003E+10 9215.69 03-APR-06:06 0.00 0.00 0.00 0.00 0.00
May 6008971.43 2871.99 01-MAY-06:08 0.00 0.00 0.00 0.00 0.00
June 586899.38 5.88 19-JUN-15:10 0.00 0.00 0.00 0.00 0.00
July 1259332.08 5.72 07-JUL-13:40 0.00 0.00 0.00 0.00 0.00
August 1350085.93 5.88 01-AUG-14:40 0.00 0.00 0.00 0.00 0.00
September 365413.77 5.44 07-SEP-15:30 0.00 0.00 0.00 0.00 0.00
October 0.182140E+09 6572.37 28-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.321479E+10 16712.72 24-NOV-07:09 0.00 0.00 0.00 0.00 0.00
December 0.755304E+10 17148.72 22-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376709E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 365413.77 5.44   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104467E+11 24344.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.528600E+10 23742.74 18-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.372908E+10 23744.02 24-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 0.769703E+09 23732.50 07-MAR-07:04 0.00 0.00 0.00 0.00 0.00
April 0.218696E+09 23693.82 03-APR-06:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.131754E+10 23734.72 28-NOV-07:04 0.00 0.00 0.00 0.00 0.00
December 0.283974E+10 23727.94 04-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.141607E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.528600E+10 23744.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.361601E+10 10568.49 23-JAN-06:25 0.00 0.00 0.00 0.00 0.00
February 0.270250E+10 10558.83 11-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.110541E+10 10556.63 01-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 0.417658E+09 10551.03 03-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 11967266.01 10526.85 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 41568824.20 10512.12 19-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.105712E+10 10558.91 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.233702E+10 10561.19 11-DEC-07:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112892E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.361601E+10 10568.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.321084E+10 7682.91 19-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.245589E+10 7679.70 16-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.947359E+09 7681.32 01-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 0.334267E+09 7676.10 03-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 3628378.56 3874.51 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 53641000.85 7651.67 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.104585E+10 7678.37 21-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.219206E+10 7682.52 30-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102435E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.321084E+10 7682.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.507379E+10 9082.67 04-JAN-06:17 0.00 0.00 0.00 0.00 0.00
February 0.425250E+10 9280.84 06-FEB-08:25 0.00 0.00 0.00 0.00 0.00
March 0.156946E+10 9082.96 20-MAR-05:17 0.00 0.00 0.00 0.00 0.00
April 0.427687E+09 9066.91 03-APR-06:04 0.00 0.00 0.00 0.00 0.00
May 6254590.81 9043.78 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 70147962.80 9033.45 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.166127E+10 9092.94 27-NOV-06:16 0.00 0.00 0.00 0.00 0.00
December 0.346407E+10 9084.60 26-DEC-06:37 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165252E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.507379E+10 9280.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354572E+10 8014.54 19-JAN-06:13 0.00 0.00 0.00 0.00 0.00
February 0.289574E+10 8204.89 06-FEB-08:25 0.00 0.00 0.00 0.00 0.00
March 0.116602E+10 8012.96 01-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 0.408176E+09 8007.79 03-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 14086578.28 7821.63 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 82311246.75 7981.92 10-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 0.132230E+10 8010.04 21-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.253251E+10 8014.15 30-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119669E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354572E+10 8204.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.480296E+09 0.329552E+09 25145.19 27-MAR-16:00 21407.14 0.00
April 0.00 0.00 0.436067E+10 0.391833E+10 44998.31 07-APR-14:30 44998.31 0.00
May 0.00 0.00 0.172057E+11 0.144808E+11 85699.67 30-MAY-14:10 85699.67 0.00
June 0.00 0.00 0.593883E+11 0.464830E+11 106194.62 19-JUN-06:03 78916.42 0.00
July 0.00 0.00 0.836518E+11 0.631085E+11 115440.44 14-JUL-06:03 77671.61 0.00
August 0.00 0.00 0.860507E+11 0.693264E+11 116417.14 17-AUG-06:03 73423.25 0.00
September 0.00 0.00 0.454007E+11 0.370196E+11 115376.35 01-SEP-05:02 80401.11 0.00
October 0.00 0.00 0.201654E+11 0.141906E+11 66561.29 04-OCT-15:00 53510.82 0.00
November 0.00 0.00 0.453766E+09 0.371407E+09 11314.17 03-NOV-14:10 11314.17 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.317157E+12 0.249228E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.860507E+11 0.693264E+11 116417.14   85699.67 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 60027.90 60027.90 700.33 02-JAN-06:01 700.33 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.449706E+09 0.304998E+09 22303.67 27-MAR-16:00 18008.38 0.00
April 0.00 0.00 0.450032E+10 0.402596E+10 46458.30 07-APR-14:30 46458.30 0.00
May 0.00 0.00 0.165630E+11 0.141352E+11 82754.46 30-MAY-14:10 82754.46 0.00
June 0.00 0.00 0.546259E+11 0.426732E+11 107167.47 19-JUN-06:03 74193.51 0.00
July 0.00 0.00 0.762030E+11 0.566184E+11 115304.64 22-JUL-05:03 65659.52 0.00
August 0.00 0.00 0.764348E+11 0.611104E+11 104777.71 03-AUG-05:03 69240.79 0.00
September 0.00 0.00 0.385929E+11 0.309400E+11 104508.77 01-SEP-05:02 73650.77 0.00
October 0.00 0.00 0.167740E+11 0.118174E+11 59183.59 04-OCT-14:20 47507.19 0.00
November 0.00 0.00 0.408614E+09 0.339925E+09 9306.61 03-NOV-14:00 9306.61 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.284552E+12 0.221966E+12       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.764348E+11 0.611104E+11 115304.64   82754.46 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 514452.69 502690.23 400.19 05-JAN-06:04 400.19 0.00
February 0.00 0.00 1227301.42 1222621.05 1380.29 06-FEB-06:40 1380.29 0.00
March 0.00 0.00 0.462149E+09 0.306395E+09 23281.53 27-MAR-16:00 18094.28 0.00
April 0.00 0.00 0.463038E+10 0.409484E+10 50818.60 07-APR-14:30 50818.60 0.00
May 0.00 0.00 0.170751E+11 0.145997E+11 90306.82 30-MAY-14:00 90306.82 0.00
June 0.00 0.00 0.570648E+11 0.448740E+11 112179.76 19-JUN-05:02 84461.09 0.00
July 0.00 0.00 0.803071E+11 0.607047E+11 127937.44 22-JUL-05:03 67401.34 0.00
August 0.00 0.00 0.801762E+11 0.649410E+11 101500.32 03-AUG-05:03 65602.41 0.00
September 0.00 0.00 0.388269E+11 0.309019E+11 88982.47 01-SEP-14:00 88982.47 0.00
October 0.00 0.00 0.159999E+11 0.110901E+11 61376.47 04-OCT-13:50 51649.16 0.00
November 0.00 0.00 0.352766E+09 0.279540E+09 8792.09 04-NOV-12:30 6902.82 0.00
December 0.00 0.00 97798.81 93122.71 326.00 31-DEC-09:30 310.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.294897E+12 0.231794E+12       0.00
Minimum of Months 0.00 0.00 97798.81 93122.71 326.00   310.41 0.00
Maximum of Months 0.00 0.00 0.803071E+11 0.649410E+11 127937.44   90306.82 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 27555.09 211145.26 02-JAN-07:10
February 0.00 0.00 01-FEB-00:10 25550.15 200587.76 06-FEB-07:30
March 0.00 0.00 01-MAR-00:10 9220.35 206261.68 06-MAR-06:11
April 0.00 0.00 01-APR-00:10 2384.90 207581.85 03-APR-05:11
May 0.00 0.00 01-MAY-00:10 157.96 45190.54 01-MAY-06:03
June 0.00 0.00 01-JUN-00:10 1.09 1229.05 02-JUN-06:08
July 0.00 0.00 01-JUL-00:10 1.26 8.43 10-JUL-16:40
August 0.00 0.00 01-AUG-00:10 1.21 9.18 29-AUG-11:50
September 0.00 0.00 01-SEP-00:10 5.04 12157.25 20-SEP-06:07
October 0.00 0.00 01-OCT-00:10 286.87 84439.24 28-OCT-06:03
November 0.00 0.00 01-NOV-00:10 7450.82 190483.49 28-NOV-07:02
December 0.00 0.00 01-DEC-00:10 16864.92 207245.41 26-DEC-06:11
             
Annual Sum or Average 0.00     7362.68    
Minimum of Months 0.00 0.00   1.09 8.43  
Maximum of Months 0.00 0.00   27555.09 211145.26  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 1753.16 6437.63 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 1781.52 6446.39 09-FEB-12:18
March 0.00 0.00 01-MAR-00:10 1862.65 6396.59 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 1644.31 6126.41 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 1591.41 5771.09 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 1517.24 5345.04 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 1311.24 4990.77 03-JUL-11:20
August 0.00 0.00 01-AUG-00:10 1431.13 4874.11 31-AUG-11:30
September 0.00 0.00 01-SEP-00:10 1372.29 5103.48 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 1460.48 5503.59 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 1598.39 5916.28 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 1633.52 6246.32 29-DEC-12:40
             
Annual Sum or Average 0.00     1578.63    
Minimum of Months 0.00 0.00   1311.24 4874.11  
Maximum of Months 0.00 0.00   1862.65 6446.39  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140053E+10 0.29 2422.67 02-JAN-05:02 0.75
February 0.119745E+10 0.28 1541.37 01-FEB-07:01 0.60
March 0.157968E+10 0.30 2188.75 29-MAR-15:30 0.70
April 0.191465E+10 0.31 4927.13 10-APR-15:20 1.12
May 0.297181E+10 0.38 9508.45 30-MAY-14:10 1.68
June 0.488775E+10 0.50 10486.83 19-JUN-05:02 1.78
July 0.611971E+10 0.56 10486.83 10-JUL-10:10 1.78
August 0.677967E+10 0.60 10486.83 03-AUG-06:03 1.78
September 0.443244E+10 0.47 10486.83 01-SEP-05:02 1.78
October 0.349257E+10 0.40 7387.61 05-OCT-16:00 1.42
November 0.166871E+10 0.29 3637.68 02-NOV-14:10 0.93
December 0.132050E+10 0.27 1592.85 22-DEC-08:06 0.61
           
Annual Sum or Average 0.377655E+11 0.39      
Minimum of Months 0.119745E+10 0.27 1541.37   0.60
Maximum of Months 0.677967E+10 0.60 10486.83   1.78



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148687E+10 0.31 2617.73 02-JAN-05:02 0.83
February 0.129545E+10 0.30 2617.73 01-FEB-07:01 0.83
March 0.156408E+10 0.31 2617.73 01-MAR-07:02 0.82
April 0.183326E+10 0.33 5134.83 10-APR-14:50 1.22
May 0.287687E+10 0.40 9857.95 30-MAY-14:10 1.83
June 0.461802E+10 0.52 10358.28 19-JUN-05:02 1.88
July 0.561883E+10 0.56 10358.28 10-JUL-04:02 1.88
August 0.628144E+10 0.60 10358.28 14-AUG-14:50 1.88
September 0.360453E+10 0.45 10358.28 01-SEP-05:02 1.88
October 0.263195E+10 0.37 6442.74 04-OCT-15:40 1.39
November 0.140332E+10 0.29 2617.73 20-NOV-07:01 0.83
December 0.134487E+10 0.29 2617.73 07-DEC-07:01 0.83
           
Annual Sum or Average 0.345595E+11 0.40      
Minimum of Months 0.129545E+10 0.29 2617.73   0.82
Maximum of Months 0.628144E+10 0.60 10358.28   1.88



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.164935E+10 0.33 2461.93 01-JAN-02:62 0.72
February 0.141664E+10 0.31 2461.93 01-FEB-06:01 0.72
March 0.150724E+10 0.29 2461.93 01-MAR-06:11 0.72
April 0.166629E+10 0.29 4657.95 07-APR-15:20 1.03
May 0.253862E+10 0.35 9211.30 30-MAY-14:00 1.56
June 0.405601E+10 0.44 11235.71 19-JUN-05:02 1.77
July 0.501190E+10 0.48 11235.71 10-JUL-04:02 1.77
August 0.560616E+10 0.51 10045.04 14-AUG-14:40 1.64
September 0.302019E+10 0.37 8209.68 01-SEP-15:10 1.45
October 0.212441E+10 0.31 5719.06 04-OCT-15:30 1.15
November 0.133937E+10 0.27 2461.93 06-NOV-07:03 0.72
December 0.137307E+10 0.28 2461.93 01-DEC-07:03 0.72
           
Annual Sum or Average 0.313092E+11 0.35      
Minimum of Months 0.133937E+10 0.27 2461.93   0.72
Maximum of Months 0.560616E+10 0.51 11235.71   1.77



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.479389E+09 0.431450E+09 834.28 02-JAN-07:10 750.85 750.85 41.14 2.68
February 0.410486E+09 0.369437E+09 811.04 06-FEB-07:30 729.93 729.93 41.60 2.61
March 0.172224E+09 0.155002E+09 695.88 20-MAR-06:01 626.29 626.29 40.66 2.01
April 46149479.66 41534531.69 685.34 03-APR-06:01 616.80 616.80 36.52 1.91
May 5580499.86 5022449.87 434.31 01-MAY-06:03 390.88 390.88 42.45 0.62
June 30627.21 27564.49 13.90 02-JUN-06:08 12.51 12.51 39.30 0.01
July 35071.02 31563.92 0.09 10-JUL-16:40 0.08 0.08 37.53 0.00
August 32580.61 29322.55 0.09 29-AUG-11:50 0.08 0.08 35.79 0.00
September 118284.27 106455.84 107.70 20-SEP-06:07 96.93 96.93 35.01 0.12
October 6532926.84 5879634.16 452.45 28-OCT-06:03 407.21 407.21 29.36 0.66
November 0.133891E+09 0.120502E+09 711.86 24-NOV-07:01 640.68 640.68 42.47 2.14
December 0.304591E+09 0.274132E+09 701.68 15-DEC-07:01 631.51 631.51 39.66 2.06
                 
Annual Sum or Average 0.155906E+10 0.140315E+10            
Minimum of Months 30627.21 27564.49 0.09   0.08 0.08 29.36 0.00
Maximum of Months 0.479389E+09 0.431450E+09 834.28   750.85 750.85 42.47 2.68



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:03 2.06 2.06 58.09 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:01 2.06 2.06 57.16 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:05 2.06 2.06 56.75 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.87 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.28 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.37 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 57.54 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.69 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:02 2.06 2.06 57.76 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.33 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.28 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:05 2.06 2.06 56.99 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.75 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.33 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 41.92 41.92 27555.09 211145.26 02-JAN-07:10
February 0.00 0.00 01-FEB-00:10 35.10 35.10 25550.15 200587.76 06-FEB-07:30
March 0.00 0.00 01-MAR-00:10 29.30 29.30 9220.35 206261.68 06-MAR-06:11
April 0.00 0.00 01-APR-00:10 22.27 22.27 2384.90 207581.85 03-APR-05:11
May 0.00 0.00 01-MAY-00:10 45.66 45.66 157.96 45190.54 01-MAY-06:03
June 0.00 0.00 01-JUN-00:10 39.32 39.32 1.09 1229.05 02-JUN-06:08
July 0.00 0.00 01-JUL-00:10 38.01 38.01 1.26 8.43 10-JUL-16:40
August 0.00 0.00 01-AUG-00:10 37.12 37.12 1.21 9.18 29-AUG-11:50
September 0.00 0.00 01-SEP-00:10 35.82 35.82 5.04 12157.25 20-SEP-06:07
October 0.00 0.00 01-OCT-00:10 31.54 31.54 286.87 84439.24 28-OCT-06:03
November 0.00 0.00 01-NOV-00:10 29.81 29.81 7450.82 190483.49 28-NOV-07:02
December 0.00 0.00 01-DEC-00:10 26.71 26.71 16864.92 207245.41 26-DEC-06:11
                 
Annual Sum or Average 0.00         7362.68    
Minimum of Months 0.00 0.00   22.27 22.27 1.09 8.43  
Maximum of Months 0.00 0.00   45.66 45.66 27555.09 211145.26  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 58.09 58.09 1753.16 6437.63 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 57.53 57.53 1781.52 6446.39 09-FEB-12:18
March 0.00 0.00 01-MAR-00:10 57.55 57.55 1862.65 6396.59 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 57.64 57.64 1644.31 6126.41 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 58.24 58.24 1591.41 5771.09 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 57.96 57.96 1517.24 5345.04 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 58.09 58.09 1311.24 4990.77 03-JUL-11:20
August 0.00 0.00 01-AUG-00:10 58.16 58.16 1431.13 4874.11 31-AUG-11:30
September 0.00 0.00 01-SEP-00:10 58.15 58.15 1372.29 5103.48 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.25 57.25 1460.48 5503.59 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 57.90 57.90 1598.39 5916.28 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 57.74 57.74 1633.52 6246.32 29-DEC-12:40
                 
Annual Sum or Average 0.00         1578.63    
Minimum of Months 0.00 0.00   57.25 57.25 1311.24 4874.11  
Maximum of Months 0.00 0.00   58.24 58.24 1862.65 6446.39  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.217408E+11 0.00 0.00 0.140053E+10 0.00 0.00
February 0.184848E+11 0.00 0.00 0.119745E+10 0.00 0.00
March 0.790013E+10 0.00 0.00 0.169494E+10 0.00 0.00
April 0.215416E+10 0.00 0.00 0.294995E+10 0.00 0.00
May 0.389220E+09 0.00 0.00 0.701800E+10 0.00 0.00
June 2641518.29 0.00 0.00 0.181923E+11 0.00 0.00
July 1555814.37 0.00 0.00 0.250808E+11 0.00 0.00
August 1555691.20 0.00 0.00 0.265418E+11 0.00 0.00
September 15478733.76 0.00 0.00 0.145416E+11 0.00 0.00
October 0.250520E+09 0.00 0.00 0.797185E+10 0.00 0.00
November 0.465163E+10 0.00 0.00 0.178600E+10 0.00 0.00
December 0.119030E+11 0.00 0.00 0.132050E+10 0.00 0.00
             
Annual Sum or Average 0.674956E+11 0.00 0.00 0.109696E+12 0.00 0.00
Minimum of Months 1555691.20 0.00 0.00 0.119745E+10 0.00 0.00
Maximum of Months 0.217408E+11 0.00 0.00 0.265418E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.214100E+11 0.00 0.00 0.148689E+10 0.00 0.00
February 0.174583E+11 0.00 0.00 0.129545E+10 0.00 0.00
March 0.648474E+10 0.00 0.00 0.167255E+10 0.00 0.00
April 0.121386E+10 0.00 0.00 0.290332E+10 0.00 0.00
May 1894228.50 0.00 0.00 0.677100E+10 0.00 0.00
June 537064.39 0.00 0.00 0.169068E+11 0.00 0.00
July 1216200.20 0.00 0.00 0.228975E+11 0.00 0.00
August 1292925.46 0.00 0.00 0.238498E+11 0.00 0.00
September 366496.62 0.00 0.00 0.122770E+11 0.00 0.00
October 96062167.30 0.00 0.00 0.640126E+10 0.00 0.00
November 0.518881E+10 0.00 0.00 0.150930E+10 0.00 0.00
December 0.126676E+11 0.00 0.00 0.134487E+10 0.00 0.00
             
Annual Sum or Average 0.645247E+11 0.00 0.00 0.993157E+11 0.00 0.00
Minimum of Months 366496.62 0.00 0.00 0.129545E+10 0.00 0.00
Maximum of Months 0.214100E+11 0.00 0.00 0.238498E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.311790E+11 0.00 0.00 0.164949E+10 0.00 0.00
February 0.263168E+11 0.00 0.00 0.141697E+10 0.00 0.00
March 0.105015E+11 0.00 0.00 0.161956E+10 0.00 0.00
April 0.284651E+10 0.00 0.00 0.277304E+10 0.00 0.00
May 41945785.08 0.00 0.00 0.657774E+10 0.00 0.00
June 586899.38 0.00 0.00 0.169792E+11 0.00 0.00
July 1259332.08 0.00 0.00 0.232807E+11 0.00 0.00
August 1350085.93 0.00 0.00 0.241030E+11 0.00 0.00
September 365413.77 0.00 0.00 0.118275E+11 0.00 0.00
October 0.429809E+09 0.00 0.00 0.576665E+10 0.00 0.00
November 0.961886E+10 0.00 0.00 0.143159E+10 0.00 0.00
December 0.209184E+11 0.00 0.00 0.137310E+10 0.00 0.00
             
Annual Sum or Average 0.101856E+12 0.00 0.00 0.987986E+11 0.00 0.00
Minimum of Months 365413.77 0.00 0.00 0.137310E+10 0.00 0.00
Maximum of Months 0.311790E+11 0.00 0.00 0.241030E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140053E+10 0.00 0.217408E+11 0.00 0.00 0.00 0.00 0.00
February 0.119745E+10 0.00 0.184848E+11 0.00 0.00 0.00 0.00 0.00
March 0.157968E+10 0.480296E+09 0.790013E+10 0.00 0.00 0.00 0.00 0.00
April 0.191465E+10 0.436067E+10 0.215416E+10 0.00 0.00 0.00 0.00 0.00
May 0.297181E+10 0.172057E+11 0.389220E+09 0.00 0.00 0.00 0.00 0.00
June 0.488775E+10 0.593883E+11 2641518.29 0.00 0.00 0.00 0.00 0.00
July 0.611971E+10 0.836518E+11 1555814.37 0.00 0.00 0.00 0.00 0.00
August 0.677967E+10 0.860507E+11 1555691.20 0.00 0.00 0.00 0.00 0.00
September 0.443244E+10 0.454007E+11 15478733.76 0.00 0.00 0.00 0.00 0.00
October 0.349257E+10 0.201654E+11 0.250520E+09 0.00 0.00 0.00 0.00 0.00
November 0.166871E+10 0.453766E+09 0.465163E+10 0.00 0.00 0.00 0.00 0.00
December 0.132050E+10 0.00 0.119030E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.377655E+11 0.317157E+12 0.674956E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119745E+10 0.00 1555691.20 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.677967E+10 0.860507E+11 0.217408E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148687E+10 60027.90 0.214100E+11 0.00 0.00 0.00 0.00 0.00
February 0.129545E+10 0.00 0.174583E+11 0.00 0.00 0.00 0.00 0.00
March 0.156408E+10 0.449706E+09 0.648474E+10 0.00 0.00 0.00 0.00 0.00
April 0.183326E+10 0.450032E+10 0.121386E+10 0.00 0.00 0.00 0.00 0.00
May 0.287687E+10 0.165630E+11 1894228.50 0.00 0.00 0.00 0.00 0.00
June 0.461802E+10 0.546259E+11 537064.39 0.00 0.00 0.00 0.00 0.00
July 0.561883E+10 0.762030E+11 1216200.20 0.00 0.00 0.00 0.00 0.00
August 0.628144E+10 0.764348E+11 1292925.46 0.00 0.00 0.00 0.00 0.00
September 0.360453E+10 0.385929E+11 366496.62 0.00 0.00 0.00 0.00 0.00
October 0.263195E+10 0.167740E+11 96062167.30 0.00 0.00 0.00 0.00 0.00
November 0.140332E+10 0.408614E+09 0.518881E+10 0.00 0.00 0.00 0.00 0.00
December 0.134487E+10 0.00 0.126676E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.345595E+11 0.284552E+12 0.645247E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129545E+10 0.00 366496.62 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.628144E+10 0.764348E+11 0.214100E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.164935E+10 514452.69 0.311790E+11 0.00 0.00 0.00 0.00 0.00
February 0.141664E+10 1227301.42 0.263168E+11 0.00 0.00 0.00 0.00 0.00
March 0.150724E+10 0.462149E+09 0.105015E+11 0.00 0.00 0.00 0.00 0.00
April 0.166629E+10 0.463038E+10 0.284651E+10 0.00 0.00 0.00 0.00 0.00
May 0.253862E+10 0.170751E+11 41945785.08 0.00 0.00 0.00 0.00 0.00
June 0.405601E+10 0.570648E+11 586899.38 0.00 0.00 0.00 0.00 0.00
July 0.501190E+10 0.803071E+11 1259332.08 0.00 0.00 0.00 0.00 0.00
August 0.560616E+10 0.801762E+11 1350085.93 0.00 0.00 0.00 0.00 0.00
September 0.302019E+10 0.388269E+11 365413.77 0.00 0.00 0.00 0.00 0.00
October 0.212441E+10 0.159999E+11 0.429809E+09 0.00 0.00 0.00 0.00 0.00
November 0.133937E+10 0.352766E+09 0.961886E+10 0.00 0.00 0.00 0.00 0.00
December 0.137307E+10 97798.81 0.209184E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.313092E+11 0.294897E+12 0.101856E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133937E+10 97798.81 365413.77 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.560616E+10 0.803071E+11 0.311790E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140053E+10 0.217408E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119745E+10 0.184848E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.157968E+10 0.790013E+10 0.00 0.00 0.115264E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.191465E+10 0.215416E+10 0.00 0.00 0.103530E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.297181E+10 0.389220E+09 0.00 0.00 0.404619E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.488775E+10 2641518.29 0.00 0.00 0.133045E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.611971E+10 1555814.37 0.00 0.00 0.189611E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.677967E+10 1555691.20 0.00 0.00 0.197621E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.443244E+10 15478733.76 0.00 0.00 0.101092E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.349257E+10 0.250520E+09 0.00 0.00 0.447928E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.166871E+10 0.465163E+10 0.00 0.00 0.117288E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132050E+10 0.119030E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.377655E+11 0.674956E+11 0.00 0.00 0.719303E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119745E+10 1555691.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.677967E+10 0.217408E+11 0.00 0.00 0.197621E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.148687E+10 0.214100E+11 0.00 0.00 16253.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129545E+10 0.174583E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.156408E+10 0.648474E+10 0.00 0.00 0.108468E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.183326E+10 0.121386E+10 0.00 0.00 0.107006E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.287687E+10 1894228.50 0.00 0.00 0.389414E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.461802E+10 537064.39 0.00 0.00 0.122888E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.561883E+10 1216200.20 0.00 0.00 0.172787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.628144E+10 1292925.46 0.00 0.00 0.175683E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.360453E+10 366496.62 0.00 0.00 0.867246E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.263195E+10 96062167.30 0.00 0.00 0.376931E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.140332E+10 0.518881E+10 0.00 0.00 0.105978E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.134487E+10 0.126676E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.345595E+11 0.645247E+11 0.00 0.00 0.647562E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129545E+10 366496.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.628144E+10 0.214100E+11 0.00 0.00 0.175683E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.164935E+10 0.311790E+11 0.00 0.00 139885.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.141664E+10 0.263168E+11 0.00 0.00 332511.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150724E+10 0.105015E+11 0.00 0.00 0.112321E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166629E+10 0.284651E+10 0.00 0.00 0.110674E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.253862E+10 41945785.08 0.00 0.00 0.403912E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.405601E+10 586899.38 0.00 0.00 0.129232E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.501190E+10 1259332.08 0.00 0.00 0.182688E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.560616E+10 1350085.93 0.00 0.00 0.184968E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.302019E+10 365413.77 0.00 0.00 0.880735E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.212441E+10 0.429809E+09 0.00 0.00 0.364224E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133937E+10 0.961886E+10 0.00 0.00 92224905.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137307E+10 0.209184E+11 0.00 0.00 26571.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.313092E+11 0.101856E+12 0.00 0.00 0.674893E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133937E+10 365413.77 0.00 0.00 26571.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.560616E+10 0.311790E+11 0.00 0.00 0.184968E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.972947E+10 0.00 0.00 5531917.37 0.00 0.618085E+09 0.462679E+10 0.00 0.29
February 0.805398E+10 0.00 0.00 8425900.62 0.00 0.00 0.684664E+10 0.00 0.30
March 0.337681E+10 0.00 0.00 26421329.15 0.00 0.00 0.145104E+11 0.00 0.43
April 0.116548E+10 7666991.92 0.00 30667376.96 0.00 0.00 0.160210E+11 0.00 0.63
May 0.740649E+09 0.113102E+09 0.00 39137898.20 0.00 0.00 0.170110E+11 0.00 0.99
June 0.195395E+09 0.339504E+10 0.00 16130861.51 41439538.38 0.00 0.362728E+10 0.00 0.66
July 6973506.67 0.823590E+10 0.00 1148624.54 0.110126E+09 0.00 0.136339E+09 0.00 0.30
August 0.101018E+09 0.640580E+10 0.00 13115853.75 89873676.45 0.00 0.154851E+10 0.00 0.55
September 0.533389E+09 0.208430E+10 0.00 27020305.70 16671035.21 0.00 0.864495E+10 0.00 0.83
October 0.100433E+10 0.180672E+09 0.00 41808714.57 0.00 0.00 0.166122E+11 0.00 0.92
November 0.257019E+10 0.00 0.00 28259294.57 0.00 0.00 0.154772E+11 0.00 0.51
December 0.576119E+10 0.00 0.00 15059204.82 0.00 0.00 0.968586E+10 0.00 0.31
                   
Annual Sum or Average 0.332389E+11 0.204225E+11 0.00 0.252727E+09 0.258111E+09 0.618085E+09 0.114748E+12 0.00 0.56
Minimum of Months 6973506.67 0.00 0.00 1148624.54 0.00 0.00 0.136339E+09 0.00 0.29
Maximum of Months 0.972947E+10 0.823590E+10 0.00 41808714.57 0.110126E+09 0.618085E+09 0.170110E+11 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128602E+11 0.00 0.00 0.00 0.00 0.105106E+10 0.00 0.00 0.27
February 0.132088E+11 0.00 0.00 0.00 0.00 0.274668E+09 0.00 0.00 0.28
March 0.117406E+11 0.00 0.00 1766792.59 0.00 10735547.33 0.219629E+10 0.00 0.34
April 0.599917E+10 4714402.48 0.00 9054173.62 0.00 646250.27 0.614210E+10 0.00 0.45
May 0.289349E+10 90905827.73 0.00 19136317.44 0.00 0.00 0.925017E+10 0.00 0.68
June 0.350309E+09 0.267459E+10 0.00 9989647.17 39889061.31 0.00 0.232065E+10 0.00 0.48
July 8160566.54 0.693069E+10 0.00 833878.56 0.105070E+09 0.00 96451623.68 0.00 0.25
August 0.156451E+09 0.552733E+10 0.00 8492488.30 88609952.61 0.00 0.104808E+10 0.00 0.43
September 0.118528E+10 0.174803E+10 0.00 13771860.69 19792863.43 0.00 0.470062E+10 0.00 0.57
October 0.288633E+10 0.153306E+09 0.00 17085690.74 3113490.41 0.00 0.785973E+10 0.00 0.58
November 0.888966E+10 0.00 0.00 4077286.13 0.00 29440546.05 0.336789E+10 0.00 0.35
December 0.129514E+11 0.00 0.00 22336.59 0.00 75448666.87 0.132886E+09 0.00 0.28
                   
Annual Sum or Average 0.731298E+11 0.171296E+11 0.00 84230471.81 0.256475E+09 0.144200E+10 0.371149E+11 0.00 0.41
Minimum of Months 8160566.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.132088E+11 0.693069E+10 0.00 19136317.44 0.105070E+09 0.105106E+10 0.925017E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100533E+11 0.00 0.00 0.00 0.00 0.299920E+10 0.00 0.00 0.27
February 0.103794E+11 0.00 0.00 0.00 0.00 0.223883E+10 0.00 0.00 0.27
March 0.120942E+11 0.00 0.00 763401.25 0.00 0.367848E+09 0.989747E+09 0.00 0.33
April 0.725684E+10 1391718.06 0.00 6780516.19 1313746.19 48376378.96 0.443519E+10 0.00 0.45
May 0.407053E+10 76386070.42 0.00 15918851.69 0.00 0.00 0.817181E+10 0.00 0.68
June 0.543662E+09 0.256433E+10 0.00 9433203.21 38659062.43 0.00 0.231058E+10 0.00 0.50
July 16521473.93 0.668295E+10 0.00 978394.02 98005191.79 0.00 85266780.65 0.00 0.25
August 0.185766E+09 0.531004E+10 0.00 8089454.04 83155232.87 0.00 0.978570E+09 0.00 0.44
September 0.181824E+10 0.171500E+10 0.00 10042113.04 32111041.11 0.00 0.365296E+10 0.00 0.55
October 0.439830E+10 98907190.43 0.00 10415887.60 7055263.51 0.00 0.512622E+10 0.00 0.54
November 0.931909E+10 0.00 0.00 1119484.11 0.00 0.632668E+09 0.132595E+10 0.00 0.33
December 0.110523E+11 0.00 0.00 0.00 0.00 0.115243E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.711881E+11 0.164490E+11 0.00 63541305.14 0.260300E+09 0.743935E+10 0.270763E+11 0.00 0.41
Minimum of Months 16521473.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.120942E+11 0.668295E+10 0.00 15918851.69 98005191.79 0.299920E+10 0.817181E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.426803E+09 0.00 0.00 0.00 0.00 0.249155E+10 0.00 0.00 0.28
February 0.513154E+09 0.00 0.00 0.00 0.00 0.229917E+10 0.00 0.00 0.28
March 0.183027E+10 0.00 0.00 42256.14 0.00 0.952560E+09 62436173.88 0.00 0.33
April 0.164063E+10 612565.40 0.00 1146494.40 0.00 0.241354E+09 0.604033E+09 0.00 0.46
May 0.101641E+10 23710071.99 0.00 3855195.68 0.00 2252446.21 0.176259E+10 0.00 0.77
June 0.118492E+09 0.789705E+09 0.00 2616561.01 9912276.18 0.00 0.613764E+09 0.00 0.66
July 3419783.38 0.214620E+10 0.00 282747.92 20186160.73 0.00 22863826.89 0.00 0.38
August 47362001.12 0.168679E+10 0.00 2159562.00 19931416.80 0.00 0.245750E+09 0.00 0.60
September 0.495495E+09 0.425460E+09 0.00 2087812.97 15911140.21 0.00 0.700538E+09 0.00 0.60
October 0.122854E+10 19877578.84 0.00 1463349.39 4520550.90 40501808.54 0.648957E+09 0.00 0.53
November 0.147267E+10 0.00 0.00 21889.62 0.00 0.899739E+09 24026922.64 0.00 0.33
December 0.681963E+09 0.00 0.00 0.00 0.00 0.192947E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.947521E+10 0.509236E+10 0.00 13675869.12 70461544.81 0.885660E+10 0.468496E+10 0.00 0.46
Minimum of Months 3419783.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.183027E+10 0.214620E+10 0.00 3855195.68 20186160.73 0.249155E+10 0.176259E+10 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.771227E+09 0.00 0.00 0.00 0.00 0.186852E+10 0.00 0.00 0.40
February 0.102215E+10 0.00 0.00 0.00 0.00 0.151615E+10 0.00 0.00 0.40
March 0.172549E+10 0.00 0.00 485480.67 0.00 0.566791E+09 0.436374E+09 0.00 0.51
April 0.127585E+10 1199133.75 0.00 2215655.32 0.00 0.188618E+09 0.120686E+10 0.00 0.79
May 0.913407E+09 24614119.35 0.00 4847653.34 0.00 441760.97 0.214547E+10 0.00 1.29
June 89488675.95 0.643520E+09 0.00 2942707.77 25939425.78 0.00 0.723770E+09 0.00 0.98
July 2124471.02 0.179365E+10 0.00 344803.08 22027533.39 0.00 34083523.54 0.00 0.53
August 31394475.91 0.153105E+10 0.00 2451377.71 17746132.07 0.00 0.313412E+09 0.00 0.94
September 0.389726E+09 0.351029E+09 0.00 2835345.93 30852665.02 0.00 0.909740E+09 0.00 0.96
October 0.885102E+09 17219389.70 0.00 2431801.21 5068067.67 21643907.08 0.109339E+10 0.00 0.90
November 0.151842E+10 0.00 0.00 126657.05 0.00 0.599674E+09 0.129784E+09 0.00 0.49
December 0.102420E+10 0.00 0.00 0.00 0.00 0.141648E+10 0.00 0.00 0.40
                   
Annual Sum or Average 0.964858E+10 0.436228E+10 0.00 18681482.08 0.101634E+09 0.617832E+10 0.699288E+10 0.00 0.72
Minimum of Months 2124471.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.172549E+10 0.179365E+10 0.00 4847653.34 30852665.02 0.186852E+10 0.214547E+10 0.00 1.29



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.105016E+10 0.00 0.00 1270141.27 0.00 0.175463E+10 0.734357E+09 0.00 0.34
February 0.119925E+10 0.00 0.00 1810452.33 0.00 0.141933E+10 0.987549E+09 0.00 0.36
March 0.172452E+10 0.00 0.00 4518032.64 0.00 0.569029E+09 0.236977E+10 0.00 0.57
April 0.147076E+10 1530190.67 0.00 4460340.54 0.00 0.233329E+09 0.225333E+10 0.00 0.77
May 0.120090E+10 29982308.52 0.00 5765989.38 12530.49 4787133.19 0.256179E+10 0.00 1.03
June 0.167960E+09 0.886018E+09 0.00 3084526.32 17792697.36 0.00 0.723467E+09 0.00 0.78
July 5723762.81 0.244614E+10 0.00 332369.44 27216904.37 0.00 22244478.13 0.00 0.43
August 52019597.46 0.221725E+10 0.00 3604750.66 24458237.83 0.00 0.378915E+09 0.00 0.86
September 0.442731E+09 0.624674E+09 0.00 6430467.50 21127157.62 0.00 0.183006E+10 0.00 1.09
October 0.777859E+09 56638344.36 0.00 8630393.35 773782.89 18714892.38 0.368489E+10 0.00 1.25
November 0.142039E+10 0.00 0.00 2944812.59 0.00 0.562759E+09 0.171253E+10 0.00 0.55
December 0.119491E+10 0.00 0.00 1558843.90 0.00 0.137798E+10 0.781111E+09 0.00 0.35
                   
Annual Sum or Average 0.107072E+11 0.626224E+10 0.00 44411119.90 91381310.56 0.594055E+10 0.180400E+11 0.00 0.70
Minimum of Months 5723762.81 0.00 0.00 332369.44 0.00 0.00 22244478.13 0.00 0.34
Maximum of Months 0.172452E+10 0.244614E+10 0.00 8630393.35 27216904.37 0.175463E+10 0.368489E+10 0.00 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.749408E+09 0.00 0.00 3646.75 0.00 0.210094E+10 14811274.66 0.00 0.44
February 0.795548E+09 0.00 0.00 86164.01 0.00 0.188835E+10 94122200.07 0.00 0.44
March 0.168980E+10 0.00 0.00 1197646.73 0.00 0.723283E+09 0.705592E+09 0.00 0.59
April 0.149637E+10 317727.59 0.00 2566904.19 281919.93 0.226020E+09 0.125042E+10 0.00 0.88
May 0.114648E+10 22784996.21 0.00 4451220.16 512047.66 5581194.24 0.189303E+10 0.00 1.30
June 0.139427E+09 0.671870E+09 0.00 2582708.66 24631170.88 0.00 0.570232E+09 0.00 0.99
July 5366571.30 0.181366E+10 0.00 213468.10 21854837.29 0.00 13702664.83 0.00 0.51
August 55609979.56 0.156859E+10 0.00 2138122.29 23749688.11 0.00 0.209868E+09 0.00 0.93
September 0.511845E+09 0.385923E+09 0.00 2700189.52 29222901.53 0.00 0.785275E+09 0.00 0.99
October 0.118289E+10 27051708.73 0.00 2304748.43 3275303.41 38328744.20 0.102883E+10 0.00 0.98
November 0.145917E+10 0.00 0.00 240733.27 0.00 0.815604E+09 0.186652E+09 0.00 0.54
December 0.855833E+09 0.00 0.00 83.54 0.00 0.177227E+10 2590393.97 0.00 0.43
                   
Annual Sum or Average 0.100878E+11 0.449019E+10 0.00 18485635.65 0.103528E+09 0.757038E+10 0.675512E+10 0.00 0.75
Minimum of Months 5366571.30 0.00 0.00 83.54 0.00 0.00 2590393.97 0.00 0.43
Maximum of Months 0.168980E+10 0.181366E+10 0.00 4451220.16 29222901.53 0.210094E+10 0.189303E+10 0.00 1.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.694461E+09 0.00 0.00 0.00 0.00 0.247324E+10 0.00 0.00 0.29
February 0.679926E+09 0.00 0.00 0.00 0.00 0.239515E+10 0.00 0.00 0.28
March 0.217444E+10 0.00 0.00 0.00 0.00 0.841451E+09 0.00 0.00 0.33
April 0.210457E+10 572498.24 0.00 268351.89 292126.45 0.121257E+09 0.179343E+09 0.00 0.40
May 0.138935E+10 20259527.12 0.00 1827549.66 0.00 0.00 0.838282E+09 0.00 0.59
June 0.115943E+09 0.605381E+09 0.00 1859365.88 10581362.86 0.00 0.438867E+09 0.00 0.50
July 2636319.08 0.167506E+10 0.00 189722.09 23259476.19 0.00 21822018.13 0.00 0.28
August 52893369.40 0.138060E+10 0.00 1822790.13 18981958.62 0.00 0.207410E+09 0.00 0.48
September 0.427203E+09 0.361462E+09 0.00 2476227.31 3525673.86 0.00 0.824075E+09 0.00 0.58
October 0.126156E+10 28241987.08 0.00 1971213.68 182625.71 0.00 0.900249E+09 0.00 0.55
November 0.215279E+10 0.00 0.00 56672.18 0.00 0.402608E+09 0.107942E+09 0.00 0.34
December 0.148690E+10 0.00 0.00 0.00 0.00 0.142558E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.125427E+11 0.407158E+10 0.00 10471892.84 56823223.69 0.765928E+10 0.351799E+10 0.00 0.41
Minimum of Months 2636319.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.217444E+10 0.167506E+10 0.00 2476227.31 23259476.19 0.247324E+10 0.900249E+09 0.00 0.59



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.941063E+09 0.00 0.00 0.00 0.00 0.155353E+10 0.00 0.00 0.36
February 0.113844E+10 0.00 0.00 0.00 0.00 0.128436E+10 0.00 0.00 0.36
March 0.191073E+10 0.00 0.00 209456.39 0.00 0.332703E+09 0.192287E+09 0.00 0.43
April 0.134472E+10 1387975.78 0.00 1583537.41 0.00 59950951.46 0.816493E+09 0.00 0.62
May 0.818728E+09 23766740.00 0.00 3478531.51 0.00 0.00 0.150515E+10 0.00 0.99
June 58954937.46 0.526270E+09 0.00 2361919.67 11666027.87 0.00 0.589094E+09 0.00 0.78
July 1310767.25 0.147054E+10 0.00 244761.64 18605003.11 0.00 30437998.97 0.00 0.41
August 34731823.94 0.131702E+10 0.00 2257161.06 15183463.13 0.00 0.281596E+09 0.00 0.80
September 0.232375E+09 0.321546E+09 0.00 3454016.77 3519721.29 0.00 0.108539E+10 0.00 0.92
October 0.672824E+09 27465749.17 0.00 3600546.50 0.00 0.00 0.152552E+10 0.00 0.90
November 0.149248E+10 0.00 0.00 571639.93 0.00 0.222241E+09 0.466473E+09 0.00 0.45
December 0.148072E+10 0.00 0.00 0.00 0.00 0.851489E+09 0.00 0.00 0.35
                   
Annual Sum or Average 0.101271E+11 0.368800E+10 0.00 17761570.87 48974215.40 0.430427E+10 0.649244E+10 0.00 0.61
Minimum of Months 1310767.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.191073E+10 0.147054E+10 0.00 3600546.50 18605003.11 0.155353E+10 0.152552E+10 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.934143E+09 0.00 0.00 25316.44 0.00 0.307428E+10 40051635.42 0.00 0.36
February 0.958341E+09 0.00 0.00 83734.82 0.00 0.284680E+10 0.102084E+09 0.00 0.36
March 0.162481E+10 0.00 0.00 657882.48 0.00 0.167102E+10 0.471535E+09 0.00 0.41
April 0.157286E+10 2761683.02 0.00 1390024.84 0.00 0.750394E+09 0.638597E+09 0.00 0.53
May 0.141259E+10 30847364.73 0.00 1978676.05 147286.90 0.198793E+09 0.841982E+09 0.00 0.67
June 0.165641E+09 0.734848E+09 0.00 1817679.31 26176075.13 645456.93 0.406010E+09 0.00 0.55
July 7893236.66 0.219884E+10 0.00 200866.67 28598077.42 0.00 15229074.82 0.00 0.36
August 69257091.99 0.220262E+10 0.00 2892935.99 22863125.03 0.00 0.273037E+09 0.00 0.74
September 0.342775E+09 0.592742E+09 0.00 6073152.63 9804145.04 8374350.59 0.164692E+10 0.00 0.97
October 0.636248E+09 76469678.29 0.00 8242536.39 79702.99 0.124112E+09 0.332668E+10 0.00 1.13
November 0.162177E+10 0.00 0.00 1621421.52 0.00 0.939522E+09 0.110834E+10 0.00 0.50
December 0.135640E+10 0.00 0.00 310855.89 0.00 0.205797E+10 0.228015E+09 0.00 0.34
                   
Annual Sum or Average 0.107027E+11 0.583913E+10 0.00 25295083.05 87668412.52 0.116719E+11 0.909848E+10 0.00 0.58
Minimum of Months 7893236.66 0.00 0.00 25316.44 0.00 0.00 15229074.82 0.00 0.34
Maximum of Months 0.162481E+10 0.220262E+10 0.00 8242536.39 28598077.42 0.307428E+10 0.332668E+10 0.00 1.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.888700E+09 0.00 0.00 787.91 0.00 0.169731E+10 3724508.34 0.00 0.37
February 0.934687E+09 0.00 0.00 17527.18 0.00 0.154354E+10 36360314.22 0.00 0.37
March 0.187144E+10 0.00 0.00 571728.85 0.00 0.346748E+09 0.328872E+09 0.00 0.45
April 0.143276E+10 800215.38 0.00 1558355.86 143943.68 77996875.70 0.759046E+09 0.00 0.64
May 0.922509E+09 22316154.94 0.00 2930089.77 0.00 290466.30 0.126752E+10 0.00 0.95
June 85910639.99 0.590030E+09 0.00 1998746.10 6756694.31 0.00 0.450800E+09 0.00 0.77
July 2163352.74 0.152217E+10 0.00 156669.54 13904189.57 0.00 15826906.67 0.00 0.40
August 39192270.88 0.138918E+10 0.00 1855042.62 14001490.89 0.00 0.189551E+09 0.00 0.76
September 0.298843E+09 0.351580E+09 0.00 2977049.41 2375227.40 0.00 0.893408E+09 0.00 0.89
October 0.749150E+09 37290532.06 0.00 3252452.76 0.00 0.00 0.140967E+10 0.00 0.91
November 0.168175E+10 0.00 0.00 323371.83 0.00 0.296636E+09 0.264194E+09 0.00 0.46
December 0.141707E+10 0.00 0.00 2185.18 0.00 0.964216E+09 11017009.30 0.00 0.36
                   
Annual Sum or Average 0.103242E+11 0.391337E+10 0.00 15644007.02 37181545.86 0.492673E+10 0.562999E+10 0.00 0.61
Minimum of Months 2163352.74 0.00 0.00 787.91 0.00 0.00 3724508.34 0.00 0.36
Maximum of Months 0.187144E+10 0.152217E+10 0.00 3252452.76 14001490.89 0.169731E+10 0.140967E+10 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.744631E+09 0.00 0.00 0.00 0.00 0.227517E+10 0.00 0.00 0.28
February 0.904751E+09 0.00 0.00 0.00 0.00 0.201017E+10 0.00 0.00 0.28
March 0.238378E+10 0.00 0.00 56335.83 0.00 0.489725E+09 59549492.49 0.00 0.33
April 0.178384E+10 1258332.86 0.00 1224347.94 0.00 50775707.97 0.673106E+09 0.00 0.45
May 0.847965E+09 28973734.46 0.00 4281052.28 0.00 0.00 0.184482E+10 0.00 0.76
June 79587406.07 0.849599E+09 0.00 2627608.66 8403022.31 0.00 0.590587E+09 0.00 0.64
July 1931592.76 0.226961E+10 0.00 232223.67 22133985.21 0.00 24424412.63 0.00 0.37
August 44236477.82 0.179342E+10 0.00 2086628.84 18666556.30 0.00 0.236176E+09 0.00 0.58
September 0.431917E+09 0.451162E+09 0.00 2509219.96 4675717.48 0.00 0.802781E+09 0.00 0.61
October 0.119922E+10 36526284.49 0.00 1950335.17 1111900.25 316376.34 0.850579E+09 0.00 0.54
November 0.187119E+10 0.00 0.00 87539.90 0.00 0.519020E+09 0.146254E+09 0.00 0.33
December 0.131838E+10 0.00 0.00 0.00 0.00 0.146637E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.116114E+11 0.543055E+10 0.00 15055292.26 54991181.54 0.681155E+10 0.522828E+10 0.00 0.46
Minimum of Months 1931592.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.238378E+10 0.226961E+10 0.00 4281052.28 22133985.21 0.227517E+10 0.184482E+10 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114163E+10 0.00 0.00 0.00 0.00 0.166607E+10 0.00 0.00 0.41
February 0.138114E+10 0.00 0.00 974.96 0.00 0.134164E+10 4433168.40 0.00 0.42
March 0.204764E+10 0.00 0.00 703146.33 0.00 0.301222E+09 0.548975E+09 0.00 0.52
April 0.147381E+10 1719482.76 0.00 2372285.99 0.00 36294540.98 0.125065E+10 0.00 0.80
May 0.866526E+09 27305073.69 0.00 5019253.97 0.00 0.00 0.211032E+10 0.00 1.25
June 70440371.49 0.684912E+09 0.00 2854583.66 11280913.71 0.00 0.695698E+09 0.00 0.93
July 1432782.49 0.185620E+10 0.00 280801.22 21172894.34 0.00 34754760.94 0.00 0.51
August 37509696.69 0.157392E+10 0.00 2371064.13 17734331.61 0.00 0.307515E+09 0.00 0.90
September 0.390073E+09 0.358946E+09 0.00 3301031.94 17176759.66 0.00 0.973440E+09 0.00 0.97
October 0.924380E+09 30656289.93 0.00 2915568.61 1554129.80 878829.99 0.127675E+10 0.00 0.91
November 0.174523E+10 0.00 0.00 331966.34 0.00 0.392949E+09 0.296425E+09 0.00 0.51
December 0.149459E+10 0.00 0.00 1022.81 0.00 0.114944E+10 1758018.63 0.00 0.41
                   
Annual Sum or Average 0.115744E+11 0.453367E+10 0.00 20151699.97 68919029.13 0.488849E+10 0.750072E+10 0.00 0.71
Minimum of Months 1432782.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.204764E+10 0.185620E+10 0.00 5019253.97 21172894.34 0.166607E+10 0.211032E+10 0.00 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.140910E+10 0.00 0.00 1719509.58 0.00 0.131229E+10 0.951790E+09 0.00 0.34
February 0.149252E+10 0.00 0.00 2318622.93 0.00 0.104285E+10 0.129410E+10 0.00 0.37
March 0.192731E+10 0.00 0.00 5186970.24 0.00 0.268004E+09 0.252027E+10 0.00 0.57
April 0.156034E+10 3296640.21 0.00 4676830.37 0.00 56157055.49 0.219096E+10 0.00 0.75
May 0.944431E+09 37853274.04 0.00 5947747.39 0.00 0.00 0.252984E+10 0.00 0.99
June 0.115861E+09 0.971643E+09 0.00 2947277.09 9300697.86 0.00 0.659382E+09 0.00 0.73
July 4555390.74 0.262485E+10 0.00 249331.76 24746639.27 0.00 21482301.80 0.00 0.43
August 49909348.86 0.240705E+10 0.00 3232102.55 20534091.08 0.00 0.324903E+09 0.00 0.81
September 0.346596E+09 0.675983E+09 0.00 7151836.10 6688875.85 0.00 0.183687E+10 0.00 1.09
October 0.697800E+09 0.100304E+09 0.00 9801292.79 0.00 0.00 0.393634E+10 0.00 1.26
November 0.153117E+10 0.00 0.00 4126884.92 0.00 0.259526E+09 0.224857E+10 0.00 0.58
December 0.154434E+10 0.00 0.00 2347682.27 0.00 0.878270E+09 0.121733E+10 0.00 0.36
                   
Annual Sum or Average 0.116239E+11 0.682098E+10 0.00 49706087.98 61270304.07 0.381709E+10 0.197318E+11 0.00 0.69
Minimum of Months 4555390.74 0.00 0.00 249331.76 0.00 0.00 21482301.80 0.00 0.34
Maximum of Months 0.192731E+10 0.262485E+10 0.00 9801292.79 24746639.27 0.131229E+10 0.393634E+10 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100771E+10 0.00 0.00 20323.60 0.00 0.185242E+10 37890401.96 0.00 0.43
February 0.114187E+10 0.00 0.00 120326.41 0.00 0.158558E+10 0.107997E+09 0.00 0.43
March 0.206365E+10 0.00 0.00 1322431.74 0.00 0.350626E+09 0.706329E+09 0.00 0.57
April 0.160879E+10 1137800.74 0.00 2576419.54 0.00 57772532.75 0.120116E+10 0.00 0.85
May 0.919224E+09 29623265.15 0.00 4508108.17 0.00 335765.95 0.188423E+10 0.00 1.23
June 0.115478E+09 0.753120E+09 0.00 2346431.63 7716685.14 0.00 0.504864E+09 0.00 0.93
July 5450627.19 0.195737E+10 0.00 173984.43 11463980.54 0.00 12839026.33 0.00 0.50
August 52529455.79 0.170567E+10 0.00 1900621.85 14017493.18 0.00 0.186983E+09 0.00 0.88
September 0.460458E+09 0.415224E+09 0.00 2873761.18 8891026.95 0.00 0.793746E+09 0.00 0.97
October 0.110660E+10 47495409.37 0.00 2658291.64 172595.59 593280.29 0.116828E+10 0.00 0.96
November 0.179195E+10 0.00 0.00 336559.68 0.00 0.472363E+09 0.265944E+09 0.00 0.53
December 0.142180E+10 0.00 0.00 12627.55 0.00 0.125347E+10 37061908.85 0.00 0.42
                   
Annual Sum or Average 0.116955E+11 0.490965E+10 0.00 18849887.42 42261781.40 0.557315E+10 0.690732E+10 0.00 0.73
Minimum of Months 5450627.19 0.00 0.00 12627.55 0.00 0.00 12839026.33 0.00 0.42
Maximum of Months 0.206365E+10 0.195737E+10 0.00 4508108.17 14017493.18 0.185242E+10 0.188423E+10 0.00 1.23



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:07

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.134751E+12 0.147697E+11 0.00 0.146331E+12 0.305530E+11
February 0.208109E+12 0.139660E+11 0.00 0.152544E+12 0.266183E+11
March 0.336262E+12 0.120639E+11 0.00 0.196772E+12 0.156046E+11
April 0.354093E+12 0.761878E+10 0.00 0.206227E+12 0.203447E+11
May 0.448598E+12 0.426410E+10 0.00 0.209052E+12 0.631017E+11
June 0.431444E+12 -0.107026E+10 0.00 0.396223E+11 0.209597E+12
July 0.423048E+12 -0.564751E+10 0.00 -0.428864E+11 0.294673E+12
August 0.410162E+12 -0.376933E+10 0.00 -0.744849E+10 0.298491E+12
September 0.292592E+12 0.712304E+09 0.00 0.104102E+12 0.150418E+12
October 0.287567E+12 0.559435E+10 0.00 0.215777E+12 0.653022E+11
November 0.145358E+12 0.111540E+11 0.00 0.198996E+12 0.118455E+11
December 0.109221E+12 0.130362E+11 0.00 0.164065E+12 0.234763E+11
           
Annual Sum or Average 0.358121E+13 0.726922E+11 0.00 0.158315E+13 0.121003E+13
Minimum of Months 0.109221E+12 -0.564751E+10 0.00 -0.428864E+11 0.118455E+11
Maximum of Months 0.448598E+12 0.147697E+11 0.00 0.215777E+12 0.298491E+12