Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:20:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1963.73 | 394.15 | 394.15 |
Net Site Energy | 1963.73 | 394.15 | 394.15 |
Total Source Energy | 5007.89 | 1005.16 | 1005.16 |
Net Source Energy | 5007.89 | 1005.16 | 1005.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 581.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1382.24 | 581.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 581.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 94.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 2.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 56.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 581.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 128.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 94.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 2.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 56.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 56.80 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.44 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 56.80 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.44 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1382.241 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1382.241 | 100.00 |
Total On-Site and Utility Electric Sources | 1382.241 | 100.00 |
Total Electricity End Uses | 1382.241 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 465.83 |
Time Setpoint Not Met During Occupied Cooling | 63.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2660.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-AUG-14:30 | 11-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 271921.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71174.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41659.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27389.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3204.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 170525.51 | 271921.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 271921.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 71174.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27389.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3204.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 630.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 954.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 298.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 9.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 180.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4377.56 | 630.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 126.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 878.64 | 126.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 126.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 878.64 | 126.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.77 | 0.271014 | 0.281000 | 0.777071 | 0.722703 | 0.500000 | 0.001406 | 0.000137 | 0.777071 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.25 | 0.333188 | 0.339000 | 0.762529 | 0.888500 | 0.500000 | 0.001143 | 0.000209 | 0.762529 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.33 | 0.322104 | 0.340000 | 0.791094 | 0.858945 | 0.500000 | 0.001183 | 0.000355 | 1.24 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.703686 | 0.224520 | 0.237000 | 0.166773 | 0.598721 | 0.500000 | 0.001697 | 0.000166 | 0.581753 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.827130 | 0.120926 | 0.200000 | 0.165426 | 0.322470 | 0.500000 | 0.003151 | 0.000108 | 0.377087 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.02 | 0.155221 | 0.200000 | 0.203570 | 0.413922 | 0.500000 | 0.002455 | 0.000166 | 0.581308 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.897247 | 0.111469 | 0.200000 | 0.179449 | 0.300000 | 0.500000 | 0.003418 | 0.000109 | 0.380619 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.556962 | 0.283667 | 0.294000 | 0.163747 | 0.756445 | 0.500000 | 0.001343 | 0.000130 | 0.453667 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.678947 | 0.147319 | 0.200000 | 0.135789 | 0.392850 | 0.500000 | 0.002586 | 0.000085 | 0.296089 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.819455 | 0.192801 | 0.200000 | 0.163891 | 0.514136 | 0.500000 | 0.001976 | 0.000130 | 0.453666 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.706289 | 0.141607 | 0.200000 | 0.141258 | 0.377618 | 0.500000 | 0.002691 | 0.000086 | 0.299245 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.618409 | 0.255481 | 0.260000 | 0.160786 | 0.681283 | 0.500000 | 0.001491 | 0.000131 | 0.457619 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.811441 | 0.123264 | 0.200000 | 0.162288 | 0.328705 | 0.500000 | 0.003091 | 0.000085 | 0.298084 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.930799 | 0.169738 | 0.200000 | 0.186160 | 0.452634 | 0.500000 | 0.002245 | 0.000131 | 0.457092 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.833416 | 0.120006 | 0.200000 | 0.166683 | 0.320017 | 0.500000 | 0.003175 | 0.000086 | 0.301287 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15617.17 | 0.000137 | 351.38 |
CORE_MID VAV BOX REHEAT COIL | 23866.36 | 0.000209 | 617.54 |
CORE_TOP VAV BOX REHEAT COIL | 40627.93 | 0.000355 | 1072.26 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19005.86 | 0.000166 | 501.14 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12318.94 | 0.000108 | 324.81 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18991.34 | 0.000166 | 500.75 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12434.17 | 0.000109 | 327.85 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14827.71 | 0.000130 | 391.05 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9676.83 | 0.000085 | 255.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14827.68 | 0.000130 | 391.05 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9779.77 | 0.000086 | 257.91 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14956.49 | 0.000131 | 394.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9741.80 | 0.000085 | 256.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14939.30 | 0.000131 | 393.98 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9846.29 | 0.000086 | 259.66 |
PACU_VAV_BOT HEATING COIL | 38464.99 | 0.000337 | 612.22 |
PACU_VAV_MID HEATING COIL | 39776.12 | 0.000348 | 626.08 |
PACU_VAV_TOP HEATING COIL | 39012.59 | 0.000341 | 624.75 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.76 | 1.38 | 5.53 | 1.93 | 4.87 | 4.87 | 0.300000 | 0.396024 | 4.87 |
PACU_VAV_MID | 2.72 | 1.44 | 5.44 | 2.23 | 4.56 | 4.56 | 0.300000 | 0.487654 | 4.56 |
PACU_VAV_TOP | 2.89 | 1.51 | 5.77 | 3.16 | 5.22 | 5.22 | 0.300000 | 0.605579 | 5.22 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.87 |
PACU_VAV_MID_OA_CONTROLLER | 4.56 |
PACU_VAV_TOP_OA_CONTROLLER | 5.22 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.87 | 101079.54 | 0.762029 | 1.62 | 33689.81 | 0.762029 |
PACU_VAV_MID COOLING COIL | 4.56 | 96487.17 | 0.754919 | 1.52 | 32159.17 | 0.754919 |
PACU_VAV_TOP COOLING COIL | 5.22 | 107027.13 | 0.766896 | 1.74 | 35672.14 | 0.766896 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.87 |
PACU_VAV_MID FAN | 4.56 |
PACU_VAV_TOP FAN | 5.22 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000337 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000348 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000341 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003138 | 0.376580 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003138 | 945.08 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 358711.32 | 358711.32 | 0.003138 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8022 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7887 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.032 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.013 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.034 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7350 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29755900E-12 | 0.81313074E-15 | -0.93602003E-13 | 0.14510957E-15 |
43 | 6 | 0.28367368E-07 | 0.22496401E-09 | 0.65009128E-08 | -0.13359594E-12 |
44 | 5 | -0.18856357E-03 | 0.19286971E-05 | -0.97009749E-04 | 0.64274374E-08 |
45 | 4 | 0.29034011 | 0.94012602E-03 | 0.99033658E-01 | -0.33316087E-04 |
46 | 3 | -7.2305496 | 0.29163423E-01 | -2.3282961 | 0.28833673E-01 |
47 | 2 | 40.753148 | 0.10379063 | 15.221555 | -0.33202618 |
48 | 1 | -80.455373 | 0.46876469E-01 | -29.102648 | 1.0766925 |
49 | 0 | 46.824339 | 0.94379271E-03 | 16.292168 | |
50 | 7 | -0.29905644E-12 | 0.21441847E-14 | -0.94350753E-13 | 0.15229914E-15 |
51 | 6 | 0.28527035E-07 | 0.22156944E-09 | 0.65361533E-08 | -0.13441220E-12 |
52 | 5 | -0.18937502E-03 | 0.18976302E-05 | -0.97416439E-04 | 0.64617957E-08 |
53 | 4 | 0.29129073 | 0.92413897E-03 | 0.99375489E-01 | -0.33450099E-04 |
54 | 3 | -7.2493786 | 0.28644335E-01 | -2.3338831 | 0.28925940E-01 |
55 | 2 | 40.815249 | 0.10187053 | 15.244478 | -0.33271782 |
56 | 1 | -80.502964 | 0.45980673E-01 | -29.123201 | 1.0777067 |
57 | 0 | 46.824339 | 0.92519179E-03 | 16.291675 | |
58 | 7 | -0.27570686E-12 | 0.13707328E-14 | -0.80264236E-13 | 0.78378346E-16 |
59 | 6 | 0.25615968E-07 | 0.28022365E-09 | 0.58936169E-08 | -0.11887149E-12 |
60 | 5 | -0.17446821E-03 | 0.24481169E-05 | -0.89927666E-04 | 0.58344893E-08 |
61 | 4 | 0.27366067 | 0.12133616E-02 | 0.93044102E-01 | -0.30982017E-04 |
62 | 3 | -6.8997845 | 0.38197916E-01 | -2.2301787 | 0.27213971E-01 |
63 | 2 | 39.661773 | 0.13771433 | 14.818013 | -0.31987377 |
64 | 1 | -79.618511 | 0.62899977E-01 | -28.740542 | 1.0588596 |
65 | 0 | 46.824345 | 0.12804488E-02 | 16.301062 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2280E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2344E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3605E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3660E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2600E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3050E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3739E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3982E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1704 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0078E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1940 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1022 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9965E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8328E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8130E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2281E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2358E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3607E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3675E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2620E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3148E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3736E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3979E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8817E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5551E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5462E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2759E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5339E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7896E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6742E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6741E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0206E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0469E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7332E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7523E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2823E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2891E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1047E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1131E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6737E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7318E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9075E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9545E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3952E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4303E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3736E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3979E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4687E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5588E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4473E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9526E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1720E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3390E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8328E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8130E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6734E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7323E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9067E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9529E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3934E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4234E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3739E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3982E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5869E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9261E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9216E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4835E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4936E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3000E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6742E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6742E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1962E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2694E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6935E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7737E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6487E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6788E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1049E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1133E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1711 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1091 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1919 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1233 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1261 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3347E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5097E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5717E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6218E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4056E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3093E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1393E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.3549E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6828E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5687E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6108E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0903E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3334E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0000E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6189E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7247E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9486E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5097E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5717E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3688E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8051E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7378E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3831E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3456E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2142E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5688E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6108E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1711 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1091 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1919 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1232 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1261 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3339E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5092E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5714E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6217E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4053E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3092E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1390E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.3544E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6824E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5682E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6105E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0905E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3333E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0001E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6187E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7244E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9484E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5092E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5714E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3688E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8049E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7377E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3829E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3452E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2139E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5683E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6105E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37420.61674 | 37420.61674 | 2.76538 | 2.76538 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7989.48740 | 7989.48740 | 0.34465 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30463.91995 | 30463.91995 | 2.24935 | 2.24935 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16381.42202 | 16381.42202 | 0.71189 | 0.71189 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31219.89098 | 31219.89098 | 2.32675 | 2.32675 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 28445.88350 | 28445.88350 | 1.24105 | 1.24105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9441.65463 | 9441.65463 | 0.70369 | 0.70369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13298.79105 | 13298.79105 | 0.58175 | 0.58175 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11098.05190 | 11098.05190 | 0.82713 | 0.82713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8619.73084 | 8619.73084 | 0.37709 | 0.37709 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13657.04500 | 13657.04500 | 1.01785 | 1.01785 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13288.63921 | 13288.63921 | 0.58131 | 0.58131 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12038.87463 | 12038.87463 | 0.89725 | 0.89725 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8700.28950 | 8700.28950 | 0.38062 | 0.38062 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7473.11940 | 7473.11940 | 0.55696 | 0.55696 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10376.45732 | 10376.45732 | 0.45367 | 0.45367 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9109.96054 | 9109.96054 | 0.67895 | 0.67895 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6771.69553 | 6771.69553 | 0.29609 | 0.29609 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10995.21963 | 10995.21963 | 0.81946 | 0.81946 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10376.44094 | 10376.44094 | 0.45367 | 0.45367 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9476.83558 | 9476.83558 | 0.70629 | 0.70629 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6843.65774 | 6843.65774 | 0.29925 | 0.29925 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8297.49928 | 8297.49928 | 0.61841 | 0.61841 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10467.35746 | 10467.35746 | 0.45762 | 0.45762 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10887.61283 | 10887.61283 | 0.81144 | 0.81144 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.44850 | 1.33584E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6817.69727 | 6817.69727 | 0.29808 | 0.29808 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12489.07225 | 12489.07225 | 0.93080 | 0.93080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10455.34020 | 10455.34020 | 0.45709 | 0.45709 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11182.46955 | 11182.46955 | 0.83342 | 0.83342 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6890.73858 | 6890.73858 | 0.30129 | 0.30129 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73169.64 | 4.86677 | 4.86677 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40992.75 | 1.92736 | 1.92736 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69112.75 | 4.56466 | 4.56466 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40500.01 | 2.22597 | 2.22597 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 77701.77 | 5.22115 | 5.22115 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40809.73 | 3.16182 | 3.16182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76538 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27101 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77707 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72270 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40583E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36626E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77707 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15617.17308 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36626E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.38307 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24935 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33319 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76253 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88850 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14350E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08793E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76253 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23866.35506 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08793E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 617.54026 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32675 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32210 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79109 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85894 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18285E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55431E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24105 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40627.93279 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55431E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1072.25645 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70369 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22452 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16677 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59872 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69695E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66272E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58175 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19005.85667 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66272E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 501.13576 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82713 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12093 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16543 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32247 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15068E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07771E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37709 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12318.93761 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07771E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.81290 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01785 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15522 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20357 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41392 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45457E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66144E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58131 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18991.33622 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66144E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 500.75314 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89725 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11147 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17945 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41799E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08780E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38062 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12434.16574 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08780E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.84905 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55696 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28367 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16375 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75645 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34312E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29719E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45367 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14827.70525 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29719E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 391.04581 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67895 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14732 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13579 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39285 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58623E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.46571E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29609 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9676.82659 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.46571E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 255.19646 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81946 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19280 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16389 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51414 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97613E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29719E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45367 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14827.68182 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29719E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 391.04519 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70629 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14161 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14126 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37762 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69055E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.55577E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29925 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9779.77126 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.55577E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 257.90895 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61841 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25548 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16079 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68128 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49130E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30846E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45762 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14956.49086 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30846E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 394.43764 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81144 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12326 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16229 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32871 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09092E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.52255E-005 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29808 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9741.80198 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.52255E-005 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 256.90724 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93080 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16974 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18616 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45263 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24464E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30696E-004 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45709 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14939.30087 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30696E-004 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.98469 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83342 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12001 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16668 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32002 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17483E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.61396E-005 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30129 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9846.28561 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61396E-005 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.66028 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76352 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38176 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.52703 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92736 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.86677 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.86677 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.39602 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.72171 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43845 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.44341 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22597 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.56466 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.56466 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.48765 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88633 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50631 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.77266 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.16182 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.22115 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.22115 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.60558 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.86677 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.56466 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.22115 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.86677 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.86677 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 101079.53632 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76203 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.62210 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33689.80946 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76203 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 38464.99104 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36509E-004 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 612.22381 |
248 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.86677 |
249 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.36509E-004 |
250 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.56466 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.56466 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96487.16683 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75492 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.52140 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32159.17271 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75492 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 39776.11809 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.47979E-004 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 626.07655 |
260 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.56466 |
261 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.47979E-004 |
262 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.22115 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.22115 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107027.12520 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76690 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74021 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35672.14083 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76690 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 39012.59295 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41299E-004 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 624.74542 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.22115 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.41299E-004 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.13816E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.37658 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.13816E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 945.07693 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 358711.32350 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 358711.32000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.13816E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14800.09 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 22601.77 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 38499.20 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18006.88 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11671.40 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17993.13 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11780.56 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14048.86 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9168.49 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14048.84 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9266.01 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14170.85 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9230.03 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14154.57 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9329.01 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 27594.68 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 27843.62 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 28362.10 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 100298.67 | 342233.26 | 12.17 | 3.13 | 3.49 | 3.67 | 3.86 | 10.66 | 11.89 | 12.51 | 13.16 | 5.4876 | 4.3822 | 2.9513 | 1.1975 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95804.42 | 326898.24 | 12.22 | 3.13 | 3.50 | 3.68 | 3.86 | 10.69 | 11.94 | 12.56 | 13.18 | 5.1469 | 4.1049 | 2.7635 | 1.1308 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 106147.72 | 362191.06 | 12.14 | 3.12 | 3.48 | 3.66 | 3.85 | 10.64 | 11.86 | 12.48 | 13.13 | 5.8872 | 4.7025 | 3.1678 | 1.2796 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.032 | 0.894 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.802 | 0.716 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.789 | 0.705 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.1242320219E-002 | 3.9267857131E-002 | Pass | Pass | 0.4617238863 | 0.4831635720 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1354404496 | 9.0640835694E-002 | Pass | Pass | 0.4951947332 | 0.4701601856 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3972637770E-002 | 3.5433010312E-002 | Pass | Pass | 0.4710521036 | 0.4559876113 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4788769881E-002 | 4.0896869196E-002 | Pass | Pass | 0.4640026058 | 0.4582683577 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.4012811537E-002 | 9.3093830376E-003 | Pass | Pass | 0.5333523396 | 0.7233739199 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.8101822254E-002 | 7.2967878814E-002 | Pass | Pass | 27.1611564015 | 50.8079733974 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3443437811 | 0.3422750009 | Pass | Pass | 27.7982109736 | 176.0717733824 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3724459254 | 0.3620981299 | Pass | Pass | 50.3035069586 | 116.7040938459 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3434073814 | 0.3426337737 | Pass | Pass | 45.4525932717 | 101.1063868516 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3739083034 | 0.3665527401 | Pass | Pass | 49.9954709191 | 119.6683463448 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2578634589 | 0.2334382964 | Pass | Pass | 19.4667188936 | 42.0383124351 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2651289400 | 0.2418251337 | Pass | Pass | 16.2700893515 | 35.0885573933 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2240923037 | 0.2150512114 | Pass | Pass | 27.5790985525 | 107.8931621170 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2664087909 | 0.2444624589 | Pass | Pass | 15.6193794213 | 33.6329040900 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2656436058 | 0.2434211962 | Pass | Pass | 29.5263983355 | 70.2956920297 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2694576755 | 0.2503205643 | Pass | Pass | 22.4745596903 | 53.2305416242 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2349043000 | 0.2294271485 | Pass | Pass | 32.3444940406 | 78.0408427338 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2710228464 | 0.2533980003 | Pass | Pass | 23.4343111173 | 56.5844682175 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3530.34 | 105.70 | 0.00 | 1831.73 | 876.81 | 6344.59 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.894 | 1.032 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.716 | 0.802 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.705 | 0.789 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.38 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.38 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.38 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 195.79 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 5.54 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 8.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.01 | 0.0000 | Y | 8.81 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 5.52 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 8.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.76 | 0.0000 | Y | 5.52 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 5.54 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 8.66 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 5.54 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.41 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.04 | 42.04 | 4.45 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.67 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.67 | 47.45 | 41.99 | |
Exterior Lighting Total | 5686.19 | 51.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 358711.32 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 101079.54 | 77025.49 | 24054.04 | 0.76 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 96487.17 | 72840.02 | 23647.15 | 0.75 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107027.13 | 82078.64 | 24948.48 | 0.77 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 100298.7 | 3.13 | 10.66 | N/A | N/A | 12.17 | |
PACU_VAV_MID COOLING COIL | 95804.4 | 3.13 | 10.69 | N/A | N/A | 12.22 | |
PACU_VAV_TOP COOLING COIL | 106147.7 | 3.12 | 10.64 | N/A | N/A | 12.14 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15617.17 | 14800.09 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 23866.36 | 22601.77 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 40627.93 | 38499.20 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19005.86 | 18006.88 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12318.94 | 11671.40 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18991.34 | 17993.13 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12434.17 | 11780.56 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14827.71 | 14048.86 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9676.83 | 9168.49 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14827.68 | 14048.84 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9779.77 | 9266.01 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14956.49 | 14170.85 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9741.80 | 9230.03 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14939.30 | 14154.57 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9846.29 | 9329.01 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 38464.99 | 27594.68 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 39776.12 | 27843.62 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 39012.59 | 28362.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.87 | 11186.09 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.56 | 10559.82 | 2313.39 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.22 | 12000.60 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003138 | 945.08 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 100298.67 | 3.13 | 10.66 | 12.17 | 5.4876 | 3.49 | 11.89 | 4.3822 | 3.67 | 12.51 | 2.9513 | 3.86 | 13.16 | 1.1975 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95804.42 | 3.13 | 10.69 | 12.22 | 5.1469 | 3.50 | 11.94 | 4.1049 | 3.68 | 12.56 | 2.7635 | 3.86 | 13.18 | 1.1308 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106147.72 | 3.12 | 10.64 | 12.14 | 5.8872 | 3.48 | 11.86 | 4.7025 | 3.66 | 12.48 | 3.1678 | 3.85 | 13.13 | 1.2796 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37420.62 | 37420.62 | 38.05 | 2.765 | 2.765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 30463.92 | 30463.92 | 30.97 | 2.249 | 2.249 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 31219.89 | 31219.89 | 31.74 | 2.327 | 2.327 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00888 | 30.21 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9441.65 | 9441.65 | 45.54 | 0.704 | 0.704 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00889 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11098.05 | 11098.05 | 84.55 | 0.827 | 0.827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00871 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13657.04 | 13657.04 | 65.87 | 1.018 | 1.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00877 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12038.87 | 12038.87 | 91.72 | 0.897 | 0.897 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7473.12 | 7473.12 | 36.04 | 0.557 | 0.557 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00892 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9109.96 | 9109.96 | 69.40 | 0.679 | 0.679 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00872 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10995.22 | 10995.22 | 53.03 | 0.819 | 0.819 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00878 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9476.84 | 9476.84 | 72.20 | 0.706 | 0.706 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00871 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8297.50 | 8297.50 | 40.02 | 0.618 | 0.618 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00892 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10887.61 | 10887.61 | 82.95 | 0.811 | 0.811 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00871 | 25.45 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12489.07 | 12489.07 | 60.24 | 0.931 | 0.931 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00878 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11182.47 | 11182.47 | 85.20 | 0.833 | 0.833 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7989.49 | 7989.49 | 8.12 | 0.345 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 16381.42 | 16381.42 | 16.66 | 0.712 | 0.712 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 28445.88 | 28445.88 | 28.92 | 1.241 | 1.241 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13298.79 | 13298.79 | 64.14 | 0.582 | 0.582 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8619.73 | 8619.73 | 65.67 | 0.377 | 0.377 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13288.64 | 13288.64 | 64.09 | 0.581 | 0.581 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8700.29 | 8700.29 | 66.29 | 0.381 | 0.381 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10376.46 | 10376.46 | 50.05 | 0.454 | 0.454 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6771.70 | 6771.70 | 51.59 | 0.296 | 0.296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10376.44 | 10376.44 | 50.05 | 0.454 | 0.454 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6843.66 | 6843.66 | 52.14 | 0.299 | 0.299 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10467.36 | 10467.36 | 50.48 | 0.458 | 0.458 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6817.70 | 6817.70 | 51.94 | 0.298 | 0.298 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10455.34 | 10455.34 | 50.43 | 0.457 | 0.457 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6890.74 | 6890.74 | 52.50 | 0.301 | 0.301 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.87 | 4.87 | 1.93 | 1.93 | 4.8668 | 1.9274 | 4.8668 | 0.3960 | 0.3000 |
PACU_VAV_MID | 4.56 | 4.56 | 2.23 | 2.23 | 4.5647 | 2.2260 | 4.5647 | 0.4877 | 0.3000 |
PACU_VAV_TOP | 5.22 | 5.22 | 3.16 | 3.16 | 5.2211 | 3.1618 | 5.2211 | 0.6056 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15617.173 | 15617.173 | 0.777071 | 0.00013663 | 351.383 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15617.17 | 15617.17 | 0.777071 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 7989.49 | 0.00 | 15670.56 | 15670.56 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23866.355 | 23866.355 | 0.762529 | 0.00020879 | 617.540 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23866.36 | 23866.36 | 0.762529 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 16381.42 | 0.00 | 23939.54 | 23939.54 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 40627.933 | 40627.933 | 1.241048 | 0.00035543 | 1072.256 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40627.93 | 40627.93 | 1.241048 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 28445.88 | 0.00 | 40766.92 | 40766.92 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19005.857 | 19005.857 | 0.581753 | 0.00016627 | 501.136 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19005.86 | 19005.86 | 0.581753 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775974 | 48.9268 | 13298.79 | 0.00 | 19067.50 | 19067.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12318.938 | 12318.938 | 0.377087 | 0.00010777 | 324.813 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12318.94 | 12318.94 | 0.377087 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775347 | 48.8879 | 8619.73 | 0.00 | 12358.85 | 12358.85 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18991.336 | 18991.336 | 0.581308 | 0.00016614 | 500.753 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18991.34 | 18991.34 | 0.581308 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775955 | 48.9256 | 13288.64 | 0.00 | 19052.93 | 19052.93 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12434.166 | 12434.166 | 0.380619 | 0.00010878 | 327.849 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12434.17 | 12434.17 | 0.380619 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775581 | 48.9024 | 8700.29 | 0.00 | 12474.44 | 12474.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14827.705 | 14827.705 | 0.453667 | 0.00012972 | 391.046 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14827.71 | 14827.71 | 0.453667 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781941 | 49.2971 | 10376.46 | 0.00 | 14876.35 | 14876.35 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9676.827 | 9676.827 | 0.296089 | 0.00008466 | 255.196 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9676.83 | 9676.83 | 0.296089 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781853 | 49.2916 | 6771.70 | 0.00 | 9708.52 | 9708.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14827.682 | 14827.682 | 0.453666 | 0.00012972 | 391.045 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14827.68 | 14827.68 | 0.453666 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00781941 | 49.2971 | 10376.44 | 0.00 | 14876.33 | 14876.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9779.771 | 9779.771 | 0.299245 | 0.00008556 | 257.909 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9779.77 | 9779.77 | 0.299245 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00782142 | 49.3096 | 6843.66 | 0.00 | 9811.79 | 9811.79 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 14956.491 | 14956.491 | 0.457619 | 0.00013085 | 394.438 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14956.49 | 14956.49 | 0.457619 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773430 | 48.7681 | 10467.36 | 0.00 | 15005.53 | 15005.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9741.802 | 9741.802 | 0.298084 | 0.00008523 | 256.907 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9741.80 | 9741.80 | 0.298084 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773057 | 48.7450 | 6817.70 | 0.00 | 9773.69 | 9773.69 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14939.301 | 14939.301 | 0.457092 | 0.00013070 | 393.985 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14939.30 | 14939.30 | 0.457092 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773391 | 48.7657 | 10455.34 | 0.00 | 14988.29 | 14988.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9846.286 | 9846.286 | 0.301287 | 0.00008614 | 259.660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9846.29 | 9846.29 | 0.301287 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00773415 | 48.7673 | 6890.74 | 0.00 | 9878.50 | 9878.50 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 101079.536 | 77025.493 | 4.866775 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 103409.09 | 82528.45 | 4.866775 | 25.55 | 17.86 | 0.00995224 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 24.5577 | 24.00 | 0.00884056 | 46.3730 | 65295.36 | 0.00 | 104226.57 | 77248.18 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 38464.991 | 38464.991 | 1.460032 | 0.00033651 | 612.224 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38464.99 | 38464.99 | 1.460032 | -9.53 | -9.53 | 0.00217105 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 81.8591 | 17.76 | 0.00773518 | 59.6735 | 20813.74 | 0.00 | 33369.43 | 33369.43 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 96487.167 | 72840.015 | 4.564658 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 98951.96 | 77951.60 | 4.564658 | 25.65 | 17.97 | 0.01005744 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 26.1831 | 24.00 | 0.00888166 | 46.5858 | 61174.62 | 0.00 | 99491.22 | 73078.11 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 39776.118 | 39776.118 | 1.369397 | 0.00034798 | 626.077 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39776.12 | 39776.12 | 1.369397 | -11.82 | -11.82 | 0.00177364 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 87.2771 | 19.60 | 0.00747686 | 51.4247 | 25217.52 | 0.00 | 33662.47 | 33662.47 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 107027.125 | 82078.642 | 5.221146 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 109292.36 | 87973.36 | 5.221146 | 25.44 | 17.77 | 0.00988116 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.8910 | 24.00 | 0.00884334 | 46.3876 | 69898.51 | 0.00 | 110359.33 | 82297.38 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 39012.593 | 39012.593 | 1.566344 | 0.00034130 | 624.745 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39012.59 | 39012.59 | 1.566344 | -8.31 | -8.31 | 0.00250762 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 76.3032 | 17.63 | 0.00752644 | 58.5406 | 28691.68 | 0.00 | 34302.75 | 34302.75 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15617.173 | 15617.173 | 0.777071 | 0.00013663 | 351.383 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 4.2678 | 4.353688 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15617.17 | 15617.17 | 1.0000 | 0.91222365 | 0.777071 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.13661191 | 60.00 | 32.22 | 27.78 | 0.000 | 15617.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 7989.49 | 0.00 | 15670.56 | 15670.56 | 0.91222365 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.65 | 17.92 | 0.00800000 | 50238.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 23866.355 | 23866.355 | 0.762529 | 0.00020879 | 617.540 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 6.5221 | 6.653360 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23866.36 | 23866.36 | 1.0000 | 0.89515184 | 0.762529 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20877199 | 60.00 | 32.22 | 27.78 | 0.000 | 23866.36 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 16381.42 | 0.00 | 23939.54 | 23939.54 | 0.89515184 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.03 | 20.89 | 0.00800000 | 59803.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 40627.933 | 40627.933 | 1.241048 | 0.00035543 | 1072.256 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 11.1026 | 11.326080 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40627.93 | 40627.93 | 1.0000 | 1.45689798 | 1.241048 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.35539462 | 60.00 | 32.22 | 27.78 | 0.000 | 40627.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 28445.88 | 0.00 | 40766.92 | 40766.92 | 1.45689798 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61041.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19005.857 | 19005.857 | 0.581753 | 0.00016627 | 501.136 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 5.1938 | 5.298371 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19005.86 | 19005.86 | 1.0000 | 0.68293435 | 0.581753 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16625456 | 60.00 | 32.22 | 27.78 | 0.000 | 19005.86 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775974 | 21.00 | 0.00775974 | 48.9268 | 13298.79 | 0.00 | 19067.50 | 19067.50 | 0.68293435 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12318.938 | 12318.938 | 0.377087 | 0.00010777 | 324.813 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 3.3665 | 3.434220 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12318.94 | 12318.94 | 1.0000 | 0.44267208 | 0.377087 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10776045 | 60.00 | 32.22 | 27.78 | 0.000 | 12318.94 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775347 | 21.00 | 0.00775347 | 48.8879 | 8619.73 | 0.00 | 12358.85 | 12358.85 | 0.44267208 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18991.336 | 18991.336 | 0.581308 | 0.00016614 | 500.753 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 5.1899 | 5.294323 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18991.34 | 18991.34 | 1.0000 | 0.68241184 | 0.581308 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16612755 | 60.00 | 32.22 | 27.78 | 0.000 | 18991.34 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775955 | 21.00 | 0.00775955 | 48.9256 | 13288.64 | 0.00 | 19052.93 | 19052.93 | 0.68241184 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12434.166 | 12434.166 | 0.380619 | 0.00010878 | 327.849 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 3.3980 | 3.466343 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12434.17 | 12434.17 | 1.0000 | 0.44681885 | 0.380619 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10876841 | 60.00 | 32.22 | 27.78 | 0.000 | 12434.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775581 | 21.00 | 0.00775581 | 48.9024 | 8700.29 | 0.00 | 12474.44 | 12474.44 | 0.44681885 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14827.705 | 14827.705 | 0.453667 | 0.00012972 | 391.046 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 4.0521 | 4.133604 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14827.71 | 14827.71 | 1.0000 | 0.53257142 | 0.453667 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.12970600 | 60.00 | 32.22 | 27.78 | 0.000 | 14827.71 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781941 | 21.00 | 0.00781941 | 49.2971 | 10376.46 | 0.00 | 14876.35 | 14876.35 | 0.53257142 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9676.827 | 9676.827 | 0.296089 | 0.00008466 | 255.196 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 2.6444 | 2.697664 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9676.83 | 9676.83 | 1.0000 | 0.34758669 | 0.296089 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08464846 | 60.00 | 32.22 | 27.78 | 0.000 | 9676.83 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781853 | 21.00 | 0.00781853 | 49.2916 | 6771.70 | 0.00 | 9708.52 | 9708.52 | 0.34758669 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14827.682 | 14827.682 | 0.453666 | 0.00012972 | 391.045 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 4.0520 | 4.133597 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14827.68 | 14827.68 | 1.0000 | 0.53257058 | 0.453666 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.12970580 | 60.00 | 32.22 | 27.78 | 0.000 | 14827.68 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781941 | 21.00 | 0.00781941 | 49.2971 | 10376.44 | 0.00 | 14876.33 | 14876.33 | 0.53257058 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9779.771 | 9779.771 | 0.299245 | 0.00008556 | 257.909 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 2.6726 | 2.726363 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9779.77 | 9779.77 | 1.0000 | 0.35129141 | 0.299245 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08554898 | 60.00 | 32.22 | 27.78 | 0.000 | 9779.77 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00782142 | 21.00 | 0.00782142 | 49.3096 | 6843.66 | 0.00 | 9811.79 | 9811.79 | 0.35129141 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14956.491 | 14956.491 | 0.457619 | 0.00013085 | 394.438 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 4.0872 | 4.169506 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14956.49 | 14956.49 | 1.0000 | 0.53721070 | 0.457619 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.13083256 | 60.00 | 32.22 | 27.78 | 0.000 | 14956.49 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773430 | 21.00 | 0.00773430 | 48.7681 | 10467.36 | 0.00 | 15005.53 | 15005.53 | 0.53721070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9741.802 | 9741.802 | 0.298084 | 0.00008523 | 256.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 2.6622 | 2.715778 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9741.80 | 9741.80 | 1.0000 | 0.34992875 | 0.298084 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08521684 | 60.00 | 32.22 | 27.78 | 0.000 | 9741.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773057 | 21.00 | 0.00773057 | 48.7450 | 6817.70 | 0.00 | 9773.69 | 9773.69 | 0.34992875 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14939.301 | 14939.301 | 0.457092 | 0.00013070 | 393.985 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 4.0826 | 4.164714 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14939.30 | 14939.30 | 1.0000 | 0.53659212 | 0.457092 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.13068219 | 60.00 | 32.22 | 27.78 | 0.000 | 14939.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773391 | 21.00 | 0.00773391 | 48.7657 | 10455.34 | 0.00 | 14988.29 | 14988.29 | 0.53659212 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9846.286 | 9846.286 | 0.301287 | 0.00008614 | 259.660 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 2.6908 | 2.744905 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9846.29 | 9846.29 | 1.0000 | 0.35368888 | 0.301287 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08613081 | 60.00 | 32.22 | 27.78 | 0.000 | 9846.29 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773415 | 21.00 | 0.00773415 | 48.7673 | 6890.74 | 0.00 | 9878.50 | 9878.50 | 0.35368888 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.7 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 101079.536 | 77025.493 | 4.866775 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3407 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.866775 | 5.71322994 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 103409.09 | 82528.45 | 1.0230 | 5.71322994 | 4.866775 | 25.55 | 17.86 | 0.00995224 | 51032.5 | 10.89 | 10.89 | 0.00850000 | 32369.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11186.094 | 92222.99 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 24.5577 | 24.00 | 0.00884056 | 24.00 | 0.00884056 | 46.3730 | 65295.36 | 0.00 | 104226.57 | 77248.18 | 5.48760055 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.89 | 12.88 | 0.00925711 | 36329.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 38464.991 | 38464.991 | 1.460032 | 0.00033651 | 612.224 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.866775 | 5.71322994 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 10.5116 | 10.723105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38464.99 | 38464.99 | 1.0000 | 1.71396898 | 1.460032 | -9.53 | -9.53 | 0.00217105 | -4188.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.33647419 | 60.00 | 32.22 | 27.78 | 0.000 | 38464.99 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 81.8591 | 21.00 | 0.00779783 | 17.76 | 0.00773518 | 59.6735 | 20813.74 | 0.00 | 33369.43 | 33369.43 | 1.71396898 | 2.80 | -0.92 | 0.00217105 | 8254.5 | 22.10 | 9.42 | 0.00217105 | 27723.6 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96487.167 | 72840.015 | 4.564658 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5363 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.564658 | 5.35856753 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 98951.96 | 77951.60 | 1.0255 | 5.35856753 | 4.564658 | 25.65 | 17.97 | 0.01005744 | 51407.2 | 10.87 | 10.87 | 0.00850000 | 32357.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10559.819 | 88392.14 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 26.1831 | 24.00 | 0.00888166 | 24.00 | 0.00888166 | 46.5858 | 61174.62 | 0.00 | 99491.22 | 73078.11 | 5.14694462 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.77 | 12.75 | 0.00917260 | 35992.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39776.118 | 39776.118 | 1.369397 | 0.00034798 | 626.077 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.564658 | 5.35856753 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 10.8699 | 11.088615 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39776.12 | 39776.12 | 1.0000 | 1.60757026 | 1.369397 | -11.82 | -11.82 | 0.00177364 | -7483.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.34794334 | 60.00 | 32.22 | 27.78 | 0.000 | 39776.12 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 87.2771 | 18.89 | 0.00760137 | 19.60 | 0.00747686 | 51.4247 | 25217.52 | 0.00 | 33662.47 | 33662.47 | 1.60757026 | 2.80 | -1.54 | 0.00177364 | 7258.5 | 23.57 | 9.64 | 0.00177364 | 28198.5 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107027.125 | 82078.642 | 5.221146 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2086 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.221146 | 6.12923527 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 109292.36 | 87973.36 | 1.0212 | 6.12923527 | 5.221146 | 25.44 | 17.77 | 0.00988116 | 50747.0 | 10.89 | 10.89 | 0.00850000 | 32369.2 | -999.0 | -999.00 | -999.00 | -999.00 | 12000.603 | 97291.75 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 22.8910 | 24.00 | 0.00884334 | 24.00 | 0.00884334 | 46.3876 | 69898.51 | 0.00 | 110359.33 | 82297.38 | 5.88717681 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.99 | 12.98 | 0.00931577 | 36576.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39012.593 | 39012.593 | 1.566344 | 0.00034130 | 624.745 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.221146 | 6.12923527 | 4197.9300 | 999.8980 | 3.13784302 | 54.44 | 82.22 | 27.78 | 365930.53 | 10.6612 | 10.875763 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39012.59 | 39012.59 | 1.0000 | 1.83877058 | 1.566344 | -8.31 | -8.31 | 0.00250762 | -2121.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.34126437 | 60.00 | 32.22 | 27.78 | 0.000 | 39012.59 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 76.3032 | 17.40 | 0.00760655 | 17.63 | 0.00752644 | 58.5406 | 28691.68 | 0.00 | 34302.75 | 34302.75 | 1.83877058 | 2.80 | -0.40 | 0.00250762 | 9098.0 | 21.28 | 9.43 | 0.00250762 | 27753.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.87 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.56 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2151.67 | 2652.50 | 72.33 |
CORE_MID | 2370.33 | 3557.33 | 862.50 |
CORE_TOP | 2875.50 | 3888.00 | 1541.33 |
PERIMETER_TOP_ZN_3 | 3580.33 | 4153.33 | 2329.67 |
PERIMETER_TOP_ZN_2 | 3747.00 | 3933.17 | 2216.83 |
PERIMETER_TOP_ZN_1 | 3440.83 | 3848.67 | 1938.17 |
PERIMETER_TOP_ZN_4 | 3653.00 | 4167.00 | 2266.50 |
PERIMETER_BOT_ZN_3 | 3239.17 | 4178.83 | 2024.33 |
PERIMETER_BOT_ZN_2 | 3508.33 | 3787.17 | 1859.83 |
PERIMETER_BOT_ZN_1 | 3301.00 | 4012.67 | 1871.17 |
PERIMETER_BOT_ZN_4 | 3448.17 | 3905.83 | 1897.67 |
PERIMETER_MID_ZN_3 | 3304.83 | 3930.00 | 1935.00 |
PERIMETER_MID_ZN_2 | 2958.67 | 3305.33 | 1667.17 |
PERIMETER_MID_ZN_1 | 3182.17 | 3542.50 | 1507.00 |
PERIMETER_MID_ZN_4 | 3447.33 | 3936.00 | 1902.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4876.83 | 4702.33 | 2660.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.50 | 0.00 | 2.50 | 0.00 |
CORE_MID | 4.83 | 0.00 | 4.33 | 0.00 |
CORE_TOP | 18.67 | 0.00 | 16.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 117.50 | 2.00 | 65.17 | 1.67 |
PERIMETER_TOP_ZN_2 | 74.50 | 15.00 | 23.83 | 14.83 |
PERIMETER_TOP_ZN_1 | 69.50 | 18.33 | 27.17 | 18.00 |
PERIMETER_TOP_ZN_4 | 76.50 | 23.83 | 25.50 | 14.17 |
PERIMETER_BOT_ZN_3 | 37.83 | 0.00 | 32.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13.33 | 6.00 | 8.17 | 6.00 |
PERIMETER_BOT_ZN_1 | 449.83 | 8.00 | 446.83 | 8.00 |
PERIMETER_BOT_ZN_4 | 14.00 | 15.50 | 8.17 | 8.67 |
PERIMETER_MID_ZN_3 | 43.50 | 0.00 | 29.83 | 0.00 |
PERIMETER_MID_ZN_2 | 22.00 | 13.67 | 8.17 | 13.67 |
PERIMETER_MID_ZN_1 | 20.67 | 17.50 | 11.83 | 17.50 |
PERIMETER_MID_ZN_4 | 22.00 | 21.67 | 8.17 | 13.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 531.00 | 79.83 | 465.83 | 63.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.968 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.709 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.707 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.795 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.305 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 1.141 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.322 | 0.054 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.694 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 1.086 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.909 | 0.843 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 1.057 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.777 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 1.184 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 1.101 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.255 | 0.045 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15320421.56 | 0.00 | 15320421.56 | 0.00 | 15320421.56 | 13393058.27 | 5677.23 | 155.12 | 2927.65 | 92.62 |
CORE_MID | 11278843.43 | 0.00 | 11278843.43 | 0.00 | 11278843.43 | 13393058.27 | 6364.08 | 27.66 | 2368.27 | 126.53 |
CORE_TOP | 11275975.86 | 0.00 | 11275975.86 | 0.00 | 11275975.86 | 13393058.27 | 6325.39 | 25.21 | 2409.40 | 82.38 |
PERIMETER_TOP_ZN_3 | 2668723.87 | 0.00 | 2668723.87 | 337696.32 | 3006420.19 | 2823374.22 | 5783.32 | 45.20 | 2931.48 | 82.38 |
PERIMETER_TOP_ZN_2 | 2770984.05 | 0.00 | 2770984.05 | 225129.53 | 2996113.58 | 1787429.43 | 4067.26 | 0.44 | 4692.31 | 82.38 |
PERIMETER_TOP_ZN_1 | 3821319.12 | 0.00 | 3821319.12 | 337696.32 | 4159015.45 | 2823374.22 | 4088.40 | 1.49 | 4670.11 | 82.38 |
PERIMETER_TOP_ZN_4 | 2821794.61 | 0.00 | 2821794.61 | 225129.53 | 3046924.14 | 1787312.18 | 4063.32 | 1.98 | 4694.70 | 82.38 |
PERIMETER_BOT_ZN_3 | 2330150.58 | 0.00 | 2330150.58 | 179550.94 | 2509701.52 | 2823374.22 | 6065.03 | 145.86 | 2549.11 | 92.62 |
PERIMETER_BOT_ZN_2 | 2303828.54 | 0.00 | 2303828.54 | 119699.90 | 2423528.44 | 1787429.43 | 4109.70 | 8.76 | 4641.54 | 92.62 |
PERIMETER_BOT_ZN_1 | 3050098.44 | 0.00 | 3050098.44 | 2914681.55 | 5964779.99 | 2823374.22 | 5268.79 | 163.11 | 3328.10 | 92.62 |
PERIMETER_BOT_ZN_4 | 2248231.44 | 0.00 | 2248231.44 | 119699.90 | 2367931.34 | 1787312.18 | 4135.19 | 13.19 | 4611.62 | 92.62 |
PERIMETER_MID_ZN_3 | 2603917.06 | 0.00 | 2603917.06 | 281105.94 | 2885023.00 | 2823374.22 | 5943.59 | 36.62 | 2779.79 | 126.53 |
PERIMETER_MID_ZN_2 | 2724864.01 | 0.00 | 2724864.01 | 187402.83 | 2912266.84 | 1787429.43 | 4049.04 | 5.55 | 4705.41 | 1035.53 |
PERIMETER_MID_ZN_1 | 3683546.09 | 0.00 | 3683546.09 | 281105.94 | 3964652.02 | 2823374.22 | 4089.74 | 2.02 | 4668.25 | 126.53 |
PERIMETER_MID_ZN_4 | 2673902.06 | 0.00 | 2673902.06 | 187402.83 | 2861304.89 | 1787312.18 | 4047.42 | 4.24 | 4708.34 | 126.53 |
Total Facility | 71576600.72 | 0.00 | 71576600.72 | 5396301.53 | 76972902.25 | 67843644.98 | 6522.52 | 330.55 | 4799.18 | 1103.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7099 | 0.0000 | 0.7099 | 0.0000 | 0.7099 | 0.4247 | 2901.36 | 155.12 | 2886.52 |
CORE_MID | 0.5208 | 0.0000 | 0.5208 | 0.0000 | 0.5208 | 0.4247 | 3590.13 | 27.66 | 2325.21 |
CORE_TOP | 0.5202 | 0.0000 | 0.5202 | 0.0000 | 0.5202 | 0.4247 | 3558.97 | 25.21 | 2358.81 |
PERIMETER_TOP_ZN_3 | 0.1233 | 0.0000 | 0.1233 | 0.0080 | 0.1313 | 0.0895 | 3016.91 | 45.20 | 2880.89 |
PERIMETER_TOP_ZN_2 | 0.1281 | 0.0000 | 0.1281 | 0.0053 | 0.1334 | 0.0567 | 1300.84 | 0.44 | 4641.72 |
PERIMETER_TOP_ZN_1 | 0.1768 | 0.0000 | 0.1768 | 0.0080 | 0.1848 | 0.0895 | 1321.99 | 1.49 | 4619.53 |
PERIMETER_TOP_ZN_4 | 0.1299 | 0.0000 | 0.1299 | 0.0053 | 0.1352 | 0.0567 | 1296.90 | 1.98 | 4644.12 |
PERIMETER_BOT_ZN_3 | 0.1076 | 0.0000 | 0.1076 | 0.0043 | 0.1119 | 0.0895 | 3289.16 | 145.86 | 2507.98 |
PERIMETER_BOT_ZN_2 | 0.1066 | 0.0000 | 0.1066 | 0.0028 | 0.1094 | 0.0567 | 1333.98 | 8.76 | 4600.26 |
PERIMETER_BOT_ZN_1 | 0.1413 | 0.0000 | 0.1413 | 0.1321 | 0.2734 | 0.0895 | 2492.92 | 163.11 | 3286.98 |
PERIMETER_BOT_ZN_4 | 0.1037 | 0.0000 | 0.1037 | 0.0028 | 0.1066 | 0.0567 | 1359.53 | 13.19 | 4570.28 |
PERIMETER_MID_ZN_3 | 0.1204 | 0.0000 | 0.1204 | 0.0067 | 0.1270 | 0.0895 | 3169.64 | 36.62 | 2736.74 |
PERIMETER_MID_ZN_2 | 0.1163 | 0.0000 | 0.1163 | 0.0047 | 0.1210 | 0.0567 | 1275.44 | 5.46 | 3753.10 |
PERIMETER_MID_ZN_1 | 0.1706 | 0.0000 | 0.1706 | 0.0067 | 0.1773 | 0.0895 | 1315.79 | 2.02 | 4625.19 |
PERIMETER_MID_ZN_4 | 0.1232 | 0.0000 | 0.1232 | 0.0044 | 0.1277 | 0.0567 | 1273.84 | 4.20 | 4664.96 |
Total Facility | 3.2986 | 0.0000 | 3.2986 | 0.1912 | 3.4899 | 2.1513 | 3729.37 | 330.41 | 4730.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 34800804.18 | 0.00 | 34800804.18 | 22614548.33 | 4079.34 | 4.95 | 4675.71 | 92.62 |
PACU_VAV_MID | 31648181.36 | 0.00 | 31648181.36 | 22614548.33 | 4060.53 | 1.25 | 4698.22 | 126.53 |
PACU_VAV_TOP | 32190773.84 | 0.00 | 32190773.84 | 22614548.33 | 4067.95 | 0.32 | 4691.73 | 82.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.6112 | 0.0000 | 1.6112 | 0.7171 | 1303.47 | 4.95 | 4634.58 |
PACU_VAV_MID | 1.4621 | 0.0000 | 1.4621 | 0.7171 | 1286.59 | 1.25 | 4655.16 |
PACU_VAV_TOP | 1.4859 | 0.0000 | 1.4859 | 0.7171 | 1301.54 | 0.32 | 4641.14 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.50 | 2879.80 | 0.00 | 0.00 | 0.00 | 1962.07 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.06 | 2717.42 | 0.00 | 0.00 | 0.00 | 2184.69 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.18 | 2737.66 | 0.00 | 0.00 | 0.00 | 2140.68 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6857 | 0.0000 | 0.0000 | 0.0000 | 1.0637 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.4500 | 0.0000 | 0.0000 | 0.0000 | 1.0731 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.4644 | 0.0000 | 0.0000 | 0.0000 | 1.0684 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 982 |
Defaulted Fields | 577 |
Fields with Defaults | 2420 |
Autosized Fields | 193 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
Electricity:Building | 1021.10 | 13465.67 | 16-APR-17:20 | 74341.76 | 11-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1021.10 | 13465.67 | 16-APR-17:20 | 74341.76 | 11-JAN-08:10 |
InteriorLights:Electricity | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.42 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.17 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.94 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.99 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.14 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-11:20 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-11:20 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.93 | 267.21 | 09-APR-17:10 | 1768.58 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.52 | 22.79 | 01-JAN-09:20 | 860.01 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.52 | 22.79 | 01-JAN-09:20 | 860.01 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.97 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.92 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.17 | 422.10 | 26-MAR-17:10 | 2793.69 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-11:30 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.94 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.54 | 22.79 | 01-JAN-09:30 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.99 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 250.18 | 368.59 | 16-APR-17:30 | 99973.76 | 15-AUG-14:30 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
ElectricityPurchased:Plant | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
Cogeneration:ElectricityPurchased | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
General:Cogeneration:ElectricityPurchased | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
ElectricityNet:Plant | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
Cogeneration:ElectricityNet | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
General:Cogeneration:ElectricityNet | 1382.24 | 13834.26 | 14-MAY-17:50 | 170525.51 | 15-AUG-14:30 |
Fans:Electricity | 94.39 | 0.00 | 01-JAN-00:40 | 29324.48 | 17-JUL-12:10 |
General:Fans:Electricity | 94.39 | 0.00 | 01-JAN-00:40 | 29324.48 | 17-JUL-12:10 |
ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.25 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 128.89 | 0.00 | 01-JAN-00:10 | 71174.16 | 15-AUG-14:30 |
General:Cooling:Electricity | 128.89 | 0.00 | 01-JAN-00:10 | 71174.16 | 15-AUG-14:30 |
Electricity:Plant | 59.70 | 0.00 | 01-JAN-00:40 | 7896.38 | 06-FEB-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 56.85 | 0.00 | 01-JAN-00:10 | 7140.62 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 56.85 | 0.00 | 01-JAN-00:10 | 7140.62 | 13-FEB-13:00 |
Pumps:Electricity | 2.85 | 0.00 | 01-JAN-00:40 | 895.67 | 11-DEC-08:00 |
General:Pumps:Electricity | 2.85 | 0.00 | 01-JAN-00:40 | 895.67 | 11-DEC-08:00 |
WIRED_LTG_ELECTRICITY | 8.47 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-17:00 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 581.49 | 0.00 | 01-JAN-00:40 | 271921.25 | 11-DEC-07:20 |
NaturalGas:Plant | 581.49 | 0.00 | 01-JAN-00:40 | 271921.25 | 11-DEC-07:20 |
Heating:NaturalGas | 581.49 | 0.00 | 01-JAN-00:40 | 271921.25 | 11-DEC-07:20 |
Boiler:Heating:NaturalGas | 581.49 | 0.00 | 01-JAN-00:40 | 271921.25 | 11-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2523.72 | 0.00 | 01-JAN-00:40 | 569025.13 | 11-DEC-07:10 |
EnergyTransfer:Building | 1077.15 | 0.00 | 01-JAN-00:40 | 160965.73 | 09-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 211.49 | 0.00 | 01-JAN-00:40 | 25308.62 | 17-JUL-08:00 |
Heating:EnergyTransfer | 182.59 | 0.00 | 01-JAN-00:40 | 146673.89 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.20 | 0.00 | 01-JAN-00:10 | 7715.73 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 182.59 | 0.00 | 01-JAN-00:40 | 146673.89 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.20 | 0.00 | 01-JAN-00:10 | 7715.73 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 894.56 | 0.00 | 01-JAN-00:40 | 160965.73 | 09-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 211.29 | 0.00 | 01-JAN-00:40 | 25308.62 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer | 894.56 | 0.00 | 01-JAN-00:40 | 160965.73 | 09-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 211.29 | 0.00 | 01-JAN-00:40 | 25308.62 | 17-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 52.07 | 0.00 | 01-JAN-00:40 | 13985.70 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.74 | 0.00 | 01-JAN-00:40 | 13985.70 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.74 | 0.00 | 01-JAN-00:40 | 13985.70 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.33 | 0.00 | 01-JAN-00:10 | 10289.49 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.33 | 0.00 | 01-JAN-00:10 | 10289.49 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.78 | 0.00 | 01-JAN-00:40 | 9312.94 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.08 | 0.00 | 01-JAN-00:40 | 9312.94 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.08 | 0.00 | 01-JAN-00:40 | 9312.94 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.69 | 0.00 | 01-JAN-00:10 | 5319.90 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.69 | 0.00 | 01-JAN-00:10 | 5319.90 | 17-JUL-12:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 26.81 | 0.00 | 01-JAN-00:40 | 7926.24 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 8.19 | 0.00 | 01-JAN-00:40 | 7926.24 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 8.19 | 0.00 | 01-JAN-00:40 | 7926.24 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.63 | 0.00 | 01-JAN-00:10 | 5695.91 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.63 | 0.00 | 01-JAN-00:10 | 5695.91 | 17-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 142.56 | 0.00 | 01-JAN-00:40 | 19419.13 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.71 | 0.00 | 01-JAN-00:20 | 14660.19 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.71 | 0.00 | 01-JAN-00:20 | 14660.19 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 140.85 | 0.00 | 01-JAN-00:10 | 19419.13 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 140.85 | 0.00 | 01-JAN-00:10 | 19419.13 | 17-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 137.38 | 0.00 | 01-JAN-00:40 | 21187.32 | 27-JUN-15:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 9.28 | 0.00 | 01-JAN-00:40 | 21076.46 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 9.28 | 0.00 | 01-JAN-00:40 | 21076.46 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 128.10 | 0.00 | 01-JAN-00:10 | 21187.32 | 27-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 128.10 | 0.00 | 01-JAN-00:10 | 21187.32 | 27-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.09 | 0.00 | 01-JAN-00:40 | 9016.74 | 11-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.05 | 0.00 | 01-JAN-00:40 | 9016.74 | 11-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.05 | 0.00 | 01-JAN-00:40 | 9016.74 | 11-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.04 | 0.00 | 01-JAN-00:10 | 7041.06 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.04 | 0.00 | 01-JAN-00:10 | 7041.06 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.89 | 0.00 | 01-JAN-00:40 | 8850.88 | 17-JUL-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.27 | 0.00 | 01-JAN-00:40 | 7358.90 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.27 | 0.00 | 01-JAN-00:40 | 7358.90 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.62 | 0.00 | 01-JAN-00:10 | 8850.88 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.62 | 0.00 | 01-JAN-00:10 | 8850.88 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 55.17 | 0.00 | 01-JAN-00:40 | 12519.72 | 21-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.95 | 0.00 | 01-JAN-00:40 | 10380.10 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.95 | 0.00 | 01-JAN-00:40 | 10380.10 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.22 | 0.00 | 01-JAN-00:10 | 12519.72 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.22 | 0.00 | 01-JAN-00:10 | 12519.72 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.95 | 0.00 | 01-JAN-00:40 | 9194.91 | 18-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.20 | 0.00 | 01-JAN-00:40 | 7589.19 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 11.20 | 0.00 | 01-JAN-00:40 | 7589.19 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.75 | 0.00 | 01-JAN-00:10 | 9194.91 | 18-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.75 | 0.00 | 01-JAN-00:10 | 9194.91 | 18-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.71 | 0.00 | 01-JAN-00:40 | 6488.24 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.41 | 0.00 | 01-JAN-00:40 | 6488.24 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.41 | 0.00 | 01-JAN-00:40 | 6488.24 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.30 | 0.00 | 01-JAN-00:10 | 5540.06 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.30 | 0.00 | 01-JAN-00:10 | 5540.06 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.27 | 0.00 | 01-JAN-00:40 | 7027.93 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 0.00 | 01-JAN-00:40 | 5401.00 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.49 | 0.00 | 01-JAN-00:40 | 5401.00 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.78 | 0.00 | 01-JAN-00:10 | 7027.93 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.78 | 0.00 | 01-JAN-00:10 | 7027.93 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 53.67 | 0.00 | 01-JAN-00:40 | 11597.43 | 07-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.15 | 0.00 | 01-JAN-00:40 | 11597.43 | 07-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 23.15 | 0.00 | 01-JAN-00:40 | 11597.43 | 07-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 30.52 | 0.00 | 01-JAN-00:10 | 11568.73 | 10-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 30.52 | 0.00 | 01-JAN-00:10 | 11568.73 | 10-AUG-11:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.29 | 0.00 | 01-JAN-00:40 | 7368.85 | 04-AUG-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.05 | 0.00 | 01-JAN-00:40 | 5499.77 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.05 | 0.00 | 01-JAN-00:40 | 5499.77 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.24 | 0.00 | 01-JAN-00:10 | 7368.85 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.24 | 0.00 | 01-JAN-00:10 | 7368.85 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.10 | 0.00 | 01-JAN-00:40 | 7248.55 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 9.43 | 0.00 | 01-JAN-00:40 | 7248.55 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 9.43 | 0.00 | 01-JAN-00:40 | 7248.55 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.68 | 0.00 | 01-JAN-00:10 | 6419.23 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.68 | 0.00 | 01-JAN-00:10 | 6419.23 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.13 | 0.00 | 01-JAN-00:40 | 8813.18 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.44 | 0.00 | 01-JAN-00:40 | 5949.47 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.44 | 0.00 | 01-JAN-00:40 | 5949.47 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.69 | 0.00 | 01-JAN-00:10 | 8813.18 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 28.69 | 0.00 | 01-JAN-00:10 | 8813.18 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.30 | 0.00 | 01-JAN-00:40 | 12423.43 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.15 | 0.00 | 01-JAN-00:40 | 8217.13 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.15 | 0.00 | 01-JAN-00:40 | 8217.13 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 44.15 | 0.00 | 01-JAN-00:10 | 12423.43 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 44.15 | 0.00 | 01-JAN-00:10 | 12423.43 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.51 | 0.00 | 01-JAN-00:40 | 8790.56 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.80 | 0.00 | 01-JAN-00:40 | 6058.18 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.80 | 0.00 | 01-JAN-00:40 | 6058.18 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.71 | 0.00 | 01-JAN-00:10 | 8790.56 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.71 | 0.00 | 01-JAN-00:10 | 8790.56 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 464.69 | 0.00 | 01-JAN-00:40 | 220024.96 | 11-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 984.81 | 0.00 | 01-JAN-00:40 | 339941.81 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 410.65 | 0.00 | 01-JAN-00:40 | 217889.51 | 11-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 410.65 | 0.00 | 01-JAN-00:40 | 217889.51 | 11-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 410.65 | 0.00 | 01-JAN-00:40 | 217889.51 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 574.15 | 0.00 | 01-JAN-00:10 | 339941.81 | 15-AUG-14:30 |
EnergyTransfer:Plant | 461.76 | 0.00 | 01-JAN-00:40 | 217384.67 | 11-DEC-07:20 |
WaterSystems:EnergyTransfer | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 54.03 | 0.00 | 01-JAN-00:10 | 6833.49 | 15-FEB-12:10 |
Boilers:EnergyTransfer | 407.73 | 0.00 | 01-JAN-00:40 | 215249.22 | 11-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.196 | -211.292 | 0.000 | 0.000 | 33.217 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -144.472 |
CORE_MID | 0.000 | 0.000 | 1.714 | -140.848 | 0.000 | 0.000 | 34.681 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.900 |
CORE_TOP | 0.000 | 0.000 | 9.281 | -128.098 | 0.000 | 0.000 | 35.405 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -103.941 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 18.047 | -26.038 | 0.000 | 0.000 | 7.620 | 8.836 | 24.333 | 16.670 | 0.000 | 0.028 | 0.001 | 0.000 | -35.537 | 0.000 | -5.330 | -8.629 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 10.271 | -27.619 | 0.000 | 0.000 | 4.790 | 5.537 | 15.404 | 30.914 | 0.000 | 0.019 | 0.000 | 0.000 | -22.322 | 0.000 | -3.584 | -13.409 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 12.949 | -42.217 | 0.000 | 0.000 | 7.482 | 8.661 | 24.332 | 57.434 | 0.000 | 0.027 | 0.001 | 0.000 | -33.571 | 0.000 | -5.499 | -29.598 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 11.198 | -27.750 | 0.000 | 0.000 | 4.846 | 5.535 | 15.403 | 31.107 | 0.000 | 0.019 | 0.000 | 0.000 | -23.184 | 0.000 | -3.599 | -13.576 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 10.414 | -23.298 | 0.000 | 0.000 | 7.596 | 8.807 | 24.333 | 17.003 | 0.000 | 0.018 | 0.001 | 0.000 | -36.722 | 0.000 | -2.964 | -5.187 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 5.490 | -24.779 | 0.000 | 0.000 | 4.751 | 5.524 | 15.404 | 31.055 | 0.000 | 0.010 | 0.001 | 0.000 | -23.405 | 0.000 | -2.018 | -12.032 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 23.152 | -30.515 | 0.000 | 0.000 | 7.669 | 8.641 | 24.332 | 58.256 | 0.000 | 0.772 | 0.000 | 0.000 | -34.874 | 0.000 | -40.565 | -16.869 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 6.049 | -24.241 | 0.000 | 0.000 | 4.791 | 5.521 | 15.403 | 31.320 | 0.000 | 0.010 | 0.001 | 0.000 | -24.295 | 0.000 | -2.025 | -12.533 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 9.429 | -27.675 | 0.000 | 0.000 | 7.537 | 8.835 | 24.333 | 16.416 | 0.000 | 0.025 | 3.151 | 0.000 | -37.392 | 0.000 | -4.658 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 5.441 | -28.686 | 0.000 | 0.000 | 3.518 | 5.537 | 15.404 | 30.713 | 0.000 | 0.016 | 0.000 | 0.000 | -23.432 | 0.000 | -3.125 | -5.385 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 6.149 | -44.147 | 0.000 | 0.000 | 7.383 | 8.661 | 24.332 | 57.093 | 0.000 | 0.023 | 0.000 | 0.000 | -35.361 | 0.000 | -4.813 | -19.320 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 5.796 | -28.711 | 0.000 | 0.000 | 4.791 | 5.535 | 15.403 | 30.939 | 0.000 | 0.016 | 0.001 | 0.000 | -24.377 | 0.000 | -3.142 | -6.251 |
TOPFLOOR_PLENUM | 26.739 | -25.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.022 | 6.725 | 0.000 | 0.000 | 0.000 | -8.161 | -0.000 |
MIDFLOOR_PLENUM | 12.085 | -14.695 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.033 | 10.553 | 0.000 | 0.000 | 0.000 | -7.976 | -0.000 |
FIRSTFLOOR_PLENUM | 8.187 | -18.626 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.025 | 16.905 | 0.000 | 0.000 | 0.000 | -6.491 | -0.000 |
Total Facility | 47.011 | -58.646 | 135.576 | -835.913 | 0.000 | 0.000 | 176.076 | 301.415 | 719.689 | 408.920 | 0.000 | 1.064 | 37.340 | 0.000 | -354.471 | 0.000 | -103.950 | -474.106 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 21-JUL-04:03 | 0.00 | 0.00 | 0.00 | -41387.23 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 35533.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -32590.12 | 0.00 | 0.00 | 332.94 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 28515.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -30802.64 | 0.00 | 0.00 | 700.11 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 24928.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:02 | 0.00 | 0.00 | 0.00 | -11352.12 | 0.00 | 0.00 | 28.56 | 36.00 | 478.42 | 3542.89 | 0.00 | 121.37 | 7144.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-08:52 | 0.00 | 0.00 | 0.00 | -14104.82 | 0.00 | 0.00 | 13.42 | 22.79 | 302.86 | 11234.36 | 0.00 | 0.00 | 2606.39 | 0.00 | -0.00 | 0.00 | -74.99 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:32 | 0.00 | 0.00 | 0.00 | -18417.23 | 0.00 | 0.00 | 23.52 | 36.00 | 478.41 | 13705.27 | 0.00 | 0.00 | 4381.92 | 0.00 | -0.00 | 0.00 | -207.89 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:12 | 0.00 | 0.00 | 0.00 | -16010.79 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 11860.97 | 0.00 | 0.00 | 3929.02 | 0.00 | -0.00 | 0.00 | -46.40 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | -5540.30 | 0.00 | 0.00 | 757.17 | 647.98 | 1435.25 | 4387.86 | 0.00 | 21.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1709.02 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:21 | 0.00 | 0.00 | 0.00 | -12178.86 | 0.00 | 0.00 | 15.55 | 22.79 | 302.86 | 10275.18 | 0.00 | 0.00 | 1603.16 | 0.00 | -0.00 | 0.00 | -40.67 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-15:02 | 0.00 | 0.00 | 0.00 | -14063.34 | 0.00 | 0.00 | 26.44 | 36.00 | 478.41 | 7297.48 | 0.00 | 54.71 | 6170.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:31 | 0.00 | 0.00 | 0.00 | -12555.33 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 9443.10 | 0.00 | 0.00 | 2866.25 | 0.00 | -0.00 | 0.00 | -21.22 | 0.00 |
PERIMETER_MID_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -7900.66 | 0.00 | 0.00 | 145.79 | 258.11 | 637.89 | 267.21 | 0.00 | 0.00 | 6602.86 | 0.00 | -0.00 | 0.00 | -11.19 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:41 | 0.00 | 0.00 | 0.00 | -15385.75 | 0.00 | 0.00 | 13.27 | 22.79 | 302.86 | 11540.26 | 0.00 | 0.00 | 3591.37 | 0.00 | -0.00 | 0.00 | -84.79 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-12:02 | 0.00 | 0.00 | 0.00 | -15935.17 | 0.00 | 0.00 | 25.38 | 36.00 | 478.41 | 13535.07 | 0.00 | 0.00 | 1979.49 | 0.00 | -0.00 | 0.00 | -119.18 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:11 | 0.00 | 0.00 | 0.00 | -15426.70 | 0.00 | 0.00 | 13.79 | 22.79 | 302.86 | 11104.31 | 0.00 | 0.00 | 4033.41 | 0.00 | -0.00 | 0.00 | -50.45 | 0.00 |
TOPFLOOR_PLENUM | 27-JUN-15:15 | 0.00 | -10937.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10938.32 | 0.00 | -0.00 | 0.00 | -1.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5319.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 5298.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5694.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 5677.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-06:03 | 0.00 | -8799.84 | 0.00 | -157908.53 | 0.00 | 0.00 | 3539.17 | 9021.99 | 22496.85 | 3024.20 | 0.00 | 0.00 | 131494.91 | 0.00 | 0.00 | 0.00 | -2868.75 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 9465.13 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15318.92 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 17315.80 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19969.59 |
CORE_TOP | 11-DEC-05:11 | 0.00 | 0.00 | 24261.89 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26915.67 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:12 | 0.00 | 0.00 | 9841.08 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3631.24 | 0.00 | -992.27 | -5777.01 |
PERIMETER_TOP_ZN_2 | 11-DEC-05:11 | 0.00 | 0.00 | 8833.48 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2548.10 | 0.00 | -171.07 | -6468.47 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:12 | 0.00 | 0.00 | 12015.87 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3648.55 | 0.00 | -1002.12 | -7924.63 |
PERIMETER_TOP_ZN_4 | 11-DEC-05:11 | 0.00 | 0.00 | 9241.24 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2495.57 | 0.00 | -171.47 | -6928.35 |
PERIMETER_BOT_ZN_3 | 06-FEB-04:12 | 0.00 | 0.00 | 7276.60 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3777.01 | 0.00 | -552.15 | -3506.88 |
PERIMETER_BOT_ZN_2 | 06-FEB-04:12 | 0.00 | 0.00 | 6504.95 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2459.81 | 0.00 | -371.65 | -4027.64 |
PERIMETER_BOT_ZN_1 | 07-FEB-07:10 | 0.00 | 0.00 | 11645.52 | 0.00 | 0.00 | 0.00 | 210.10 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 15304.69 | 0.00 | -4178.61 | 0.00 | -24072.41 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-04:12 | 0.00 | 0.00 | 6693.64 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2521.16 | 0.00 | -371.01 | -4155.62 |
PERIMETER_MID_ZN_3 | 26-DEC-04:52 | 0.00 | 0.00 | 7872.90 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3379.38 | 0.00 | -956.03 | -4096.92 |
PERIMETER_MID_ZN_2 | 13-FEB-05:11 | 0.00 | 0.00 | 7329.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1967.61 | 0.00 | -791.30 | -4924.73 |
PERIMETER_MID_ZN_1 | 26-DEC-04:52 | 0.00 | 0.00 | 9669.79 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3496.38 | 0.00 | -962.29 | -5770.56 |
PERIMETER_MID_ZN_4 | 13-FEB-05:11 | 0.00 | 0.00 | 7476.52 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2044.51 | 0.00 | -790.57 | -4995.59 |
TOPFLOOR_PLENUM | 07-FEB-06:09 | 14628.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -403.14 | -14224.86 |
MIDFLOOR_PLENUM | 02-JAN-08:10 | 9688.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -112.09 | -9576.48 |
FIRSTFLOOR_PLENUM | 02-JAN-08:50 | 7964.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -81.06 | -7883.87 |
Total Facility | 02-JAN-05:01 | 11868.27 | 0.00 | 145716.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19174.68 | 0.00 | -3825.82 | -151226.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.5270 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4434 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5647 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7727 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2211 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7635 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7217 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4384 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8863 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5063 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7654 | 2.7654 | 0.7771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2493 | 2.2493 | 0.7625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3267 | 2.3267 | 0.7911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7037 | 0.7037 | 0.1668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8271 | 0.8271 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0179 | 1.0179 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8972 | 0.8972 | 0.1794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5570 | 0.5570 | 0.1637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6789 | 0.6789 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8195 | 0.8195 | 0.1639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7063 | 0.7063 | 0.1413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6184 | 0.6184 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8114 | 0.8114 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9308 | 0.9308 | 0.1862 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8334 | 0.8334 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.5270 | 4.8668 | 5.5270 | 1.3818 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4434 | 4.5647 | 5.4434 | 1.4384 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7727 | 5.2211 | 5.7727 | 1.5063 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3827 | 1.3827 | 0.7771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1247 | 1.1247 | 0.7625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1634 | 1.1634 | 0.7911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3518 | 0.3518 | 0.1668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4136 | 0.4136 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5089 | 0.5089 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4486 | 0.4486 | 0.1794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2785 | 0.2785 | 0.1637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3395 | 0.3395 | 0.1358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4097 | 0.4097 | 0.1639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3531 | 0.3531 | 0.1413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3092 | 0.3092 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4057 | 0.4057 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4654 | 0.4654 | 0.1862 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4167 | 0.4167 | 0.1667 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7635 | 1.3818 | 1.3818 | 1.3818 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7217 | 1.4384 | 1.4384 | 1.4384 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8863 | 1.5063 | 1.5063 | 1.5063 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 465.83 |
Number of hours cooling loads not met | 63.67 |
Number of hours not met | 529.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 581.49 | 271921.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 128.89 | 71174.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.42 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.25 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 94.39 | 29324.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 2.85 | 895.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 56.85 | 7140.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1382.24 |
Natural Gas | 0.00 | 581.49 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1963.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.50 |
Space Heating | 0.00 |
Space Cooling | 25.87 |
Fans (All) | 18.95 |
Service Water Heating | 11.41 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 277.44 |
Subtotal | 277.44 |
Natural Gas [MJ/m2] | |
Space Heating | 116.71 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 116.71 |
Subtotal | 116.71 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.35 |
Space Heating | 29.61 |
Space Cooling | 6.56 |
Fans (All) | 4.81 |
Service Water Heating | 2.89 |
Receptacle Equipment | 36.65 |
Miscellaneous | 4.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8534.67 | 225.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8737.00 | 23.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8697.00 | 63.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8666.33 | 93.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8725.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.83 | 37.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8688.67 | 71.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8703.83 | 56.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8698.67 | 61.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8674.33 | 85.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8666.67 | 93.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8534.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 225.33 | 0.00 | 0.00 | 0.00 |
Average | 8708.62 | 51.38 | 0.00 | 0.00 | 0.00 |
Sum | 156755.17 | 924.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128232.00 | 72.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 72.00 | 0.00 | 0.00 | 0.00 |
Average | 34139.33 | 4.00 | 0.00 | 0.00 | 0.00 |
Sum | 614508.00 | 72.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8185.50 | 574.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8371.83 | 388.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8442.67 | 317.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8361.00 | 399.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8355.83 | 404.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8338.00 | 422.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8330.17 | 429.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8403.83 | 356.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8326.67 | 433.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8249.50 | 510.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8273.17 | 486.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8319.17 | 440.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8320.17 | 439.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8291.83 | 468.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8284.50 | 475.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8075.00 | 685.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8344.33 | 415.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8280.50 | 479.50 | 0.00 | 0.00 | 0.00 |
Min | 8075.00 | 317.33 | 0.00 | 0.00 | 0.00 |
Max | 8442.67 | 685.00 | 0.00 | 0.00 | 0.00 |
Average | 8308.54 | 451.46 | 0.00 | 0.00 | 0.00 |
Sum | 149553.67 | 8126.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127968.50 | 335.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128126.67 | 177.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128162.67 | 141.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24900.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24902.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24506.00 | 403.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24897.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24900.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128162.67 | 403.00 | 0.00 | 0.00 | 0.00 |
Average | 34082.17 | 61.17 | 0.00 | 0.00 | 0.00 |
Sum | 613479.00 | 1101.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.891571E+10 | 9631.79 | 20-JAN-17:00 | -1.1 | -3.7 | 0.177881E+10 | 2595.37 | 20-JAN-14:00 | -1.1 | -3.7 |
February | 0.869555E+10 | 9945.16 | 17-FEB-17:00 | 1.10 | 0.20 | 0.165185E+10 | 2606.56 | 17-FEB-14:50 | 1.10 | 0.20 |
March | 0.132690E+11 | 18083.50 | 16-MAR-16:00 | 15.60 | 13.95 | 0.212040E+10 | 2606.63 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.150214E+11 | 29468.46 | 24-APR-05:03 | 0.68 | -0.4 | 0.190902E+10 | 2606.67 | 21-APR-13:00 | 0.68 | -0.4 |
May | 0.209812E+11 | 40086.86 | 30-MAY-05:12 | 12.20 | 11.93 | 0.207813E+10 | 2606.67 | 05-MAY-13:09 | 12.20 | 11.93 |
June | 0.257158E+11 | 40171.18 | 27-JUN-05:12 | 21.30 | 19.75 | 0.207235E+10 | 2606.81 | 22-JUN-13:09 | 21.30 | 19.75 |
July | 0.266438E+11 | 41399.53 | 21-JUL-04:03 | 26.52 | 23.72 | 0.192753E+10 | 2606.68 | 12-JUL-09:00 | 26.52 | 23.72 |
August | 0.280485E+11 | 41225.16 | 21-AUG-05:12 | 14.40 | 13.12 | 0.216332E+10 | 2647.25 | 14-AUG-09:00 | 14.40 | 13.12 |
September | 0.234744E+11 | 39871.73 | 25-SEP-05:12 | 13.30 | 13.02 | 0.192015E+10 | 2606.79 | 12-SEP-13:09 | 13.30 | 13.02 |
October | 0.176949E+11 | 36246.31 | 13-OCT-06:02 | 10.00 | 9.62 | 0.199176E+10 | 2606.67 | 03-OCT-09:00 | 10.00 | 9.62 |
November | 0.130690E+11 | 17184.02 | 01-NOV-16:00 | 9.40 | 6.91 | 0.195773E+10 | 2606.71 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.976282E+10 | 12592.50 | 01-DEC-17:00 | 7.20 | 4.89 | 0.180631E+10 | 2606.64 | 01-DEC-10:09 | 7.20 | 4.89 |
Annual Sum or Average | 0.211292E+12 | 0.233774E+11 | ||||||||
Minimum of Months | 0.869555E+10 | 9631.79 | -1.1 | -3.7 | 0.165185E+10 | 2595.37 | -1.1 | -3.7 | ||
Maximum of Months | 0.280485E+11 | 41399.53 | 26.52 | 23.72 | 0.216332E+10 | 2647.25 | 26.52 | 23.72 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 1580096.00 | 394.68 | 22-FEB-17:20 | 12.07 | 5.77 | 0.00 | 0.00 | 01-FEB-00:10 | 12.07 | 5.77 |
March | 0.383206E+09 | 5511.77 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.106894E+10 | 4771.71 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.279529E+10 | 7240.93 | 31-MAY-14:30 | 21.70 | 14.07 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.07 |
June | 0.526046E+10 | 10936.67 | 27-JUN-15:15 | 25.77 | 22.70 | 0.00 | 0.00 | 01-JUN-00:10 | 25.77 | 22.70 |
July | 0.645009E+10 | 10289.49 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.567912E+10 | 10215.97 | 09-AUG-14:40 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.294309E+10 | 8076.89 | 21-SEP-15:20 | 26.10 | 16.82 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.82 |
October | 0.673678E+09 | 4492.63 | 11-OCT-15:00 | 22.20 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.61 |
November | 70172286.19 | 1009.72 | 04-NOV-15:20 | 18.30 | 13.65 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.65 |
December | 286720.55 | 152.59 | 16-DEC-14:30 | 5.30 | 2.77 | 0.00 | 0.00 | 01-DEC-00:10 | 5.30 | 2.77 |
Annual Sum or Average | 0.253259E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.645009E+10 | 10936.67 | 31.15 | 22.70 | 0.00 | 0.00 | 31.15 | 22.70 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8680654.33 | 2636.05 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 7276306.69 | 2298.70 | 09-FEB-05:02 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.198883E+09 | 2607.36 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.384720E+09 | 2614.52 | 11-APR-06:02 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.125317E+10 | 2548.75 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.297287E+10 | 4464.08 | 12-JUN-15:30 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
July | 0.385550E+10 | 5319.90 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.357794E+10 | 4597.99 | 14-AUG-15:50 | 27.80 | 21.19 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.19 |
September | 0.187054E+10 | 3411.76 | 18-SEP-13:00 | 18.90 | 12.42 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.42 |
October | 0.457713E+09 | 2733.95 | 24-OCT-06:02 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 98982460.22 | 2095.61 | 17-NOV-07:03 | 5.50 | 2.77 | 0.00 | 0.00 | 01-NOV-00:10 | 5.50 | 2.77 |
December | 8408431.80 | 2191.81 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.146947E+11 | 0.00 | ||||||||
Minimum of Months | 7276306.69 | 2095.61 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.385550E+10 | 5319.90 | 29.15 | 21.19 | 0.00 | 0.00 | 29.15 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45158310.69 | 2208.20 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 49645534.02 | 2008.91 | 07-FEB-05:01 | -15.7 | -16.1 | 0.00 | 0.00 | 01-FEB-00:10 | -15.7 | -16.1 |
March | 0.330800E+09 | 3267.89 | 18-MAR-06:03 | 2.12 | 1.35 | 0.00 | 0.00 | 01-MAR-00:10 | 2.12 | 1.35 |
April | 0.658765E+09 | 3106.31 | 11-APR-06:02 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.176520E+10 | 3115.45 | 30-MAY-06:07 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.344808E+10 | 4815.64 | 12-JUN-12:10 | 29.40 | 20.05 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 20.05 |
July | 0.432283E+10 | 5695.91 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.429786E+10 | 5070.61 | 14-AUG-15:40 | 27.80 | 21.36 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.36 |
September | 0.267042E+10 | 5154.05 | 18-SEP-06:06 | 10.28 | 9.20 | 0.00 | 0.00 | 01-SEP-00:10 | 10.28 | 9.20 |
October | 0.790549E+09 | 2715.67 | 13-OCT-06:06 | 10.00 | 9.62 | 0.00 | 0.00 | 01-OCT-00:10 | 10.00 | 9.62 |
November | 0.204034E+09 | 2536.87 | 03-NOV-06:02 | 1.70 | 0.39 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 0.39 |
December | 42315853.55 | 1813.96 | 15-DEC-06:11 | 2.20 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | 1.70 |
Annual Sum or Average | 0.186257E+11 | 0.00 | ||||||||
Minimum of Months | 42315853.55 | 1813.96 | -15.7 | -16.1 | 0.00 | 0.00 | -15.7 | -16.1 | ||
Maximum of Months | 0.432283E+10 | 5695.91 | 29.40 | 21.36 | 0.00 | 0.00 | 29.40 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.528139E+10 | 6420.57 | 12-JAN-16:50 | -6.6 | -8.3 | 0.153660E+10 | 2246.29 | 12-JAN-14:00 | -6.6 | -8.3 |
February | 0.523524E+10 | 6478.49 | 17-FEB-17:00 | 1.10 | 0.20 | 0.141177E+10 | 2282.71 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.919214E+10 | 12419.97 | 16-MAR-16:00 | 15.60 | 13.95 | 0.188955E+10 | 2606.62 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.988577E+10 | 11770.97 | 21-APR-16:00 | 13.30 | 8.77 | 0.180521E+10 | 2606.63 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.141079E+11 | 15145.39 | 30-MAY-16:00 | 17.80 | 14.06 | 0.205298E+10 | 2606.65 | 05-MAY-13:09 | 17.80 | 14.06 |
June | 0.181518E+11 | 29822.13 | 19-JUN-06:03 | 16.70 | 15.97 | 0.206473E+10 | 2606.79 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.192949E+11 | 32594.30 | 31-JUL-05:12 | 17.60 | 16.78 | 0.192153E+10 | 2606.66 | 12-JUL-09:00 | 17.60 | 16.78 |
August | 0.196274E+11 | 32046.39 | 21-AUG-05:12 | 14.40 | 13.12 | 0.215692E+10 | 2606.82 | 02-AUG-13:09 | 14.40 | 13.12 |
September | 0.152737E+11 | 30277.60 | 18-SEP-06:01 | 10.28 | 9.20 | 0.190703E+10 | 2606.76 | 12-SEP-13:09 | 10.28 | 9.20 |
October | 0.106002E+11 | 13336.44 | 12-OCT-16:00 | 18.30 | 14.87 | 0.190412E+10 | 2606.63 | 03-OCT-09:00 | 18.30 | 14.87 |
November | 0.821050E+10 | 8941.32 | 01-NOV-16:00 | 9.40 | 6.91 | 0.174821E+10 | 2606.58 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.598744E+10 | 6793.58 | 01-DEC-17:00 | 7.20 | 4.89 | 0.151483E+10 | 2358.17 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.140848E+12 | 0.219135E+11 | ||||||||
Minimum of Months | 0.523524E+10 | 6420.57 | -6.6 | -8.3 | 0.141177E+10 | 2246.29 | -6.6 | -8.3 | ||
Maximum of Months | 0.196274E+11 | 32594.30 | 18.30 | 16.78 | 0.215692E+10 | 2606.82 | 20.60 | 16.78 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321730E+10 | 6080.72 | 12-JAN-16:40 | -6.5 | -8.3 | 0.147575E+10 | 2114.10 | 12-JAN-14:00 | -6.5 | -8.3 |
February | 0.347131E+10 | 6234.36 | 28-FEB-17:00 | -0.6 | -3.0 | 0.135562E+10 | 2166.73 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.775274E+10 | 12478.80 | 16-MAR-16:00 | 15.60 | 13.95 | 0.178676E+10 | 2606.62 | 15-MAR-13:30 | 15.60 | 13.95 |
April | 0.908224E+10 | 12420.19 | 21-APR-16:00 | 13.30 | 8.77 | 0.171315E+10 | 2606.63 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.135118E+11 | 16485.76 | 31-MAY-16:00 | 22.20 | 14.47 | 0.201746E+10 | 2606.65 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.181946E+11 | 26927.82 | 27-JUN-15:05 | 25.68 | 22.74 | 0.205688E+10 | 2641.57 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.196875E+11 | 29228.99 | 21-JUL-04:03 | 26.52 | 23.72 | 0.191895E+10 | 2606.66 | 24-JUL-13:30 | 25.85 | 17.85 |
August | 0.194507E+11 | 30807.72 | 07-AUG-06:03 | 20.68 | 18.73 | 0.215110E+10 | 2606.83 | 02-AUG-13:09 | 20.68 | 18.73 |
September | 0.141844E+11 | 17419.42 | 18-SEP-13:10 | 18.72 | 12.47 | 0.188447E+10 | 2606.76 | 12-SEP-13:09 | 18.72 | 12.47 |
October | 0.932177E+10 | 12958.47 | 12-OCT-16:00 | 18.30 | 14.87 | 0.179100E+10 | 2606.60 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.657892E+10 | 7603.83 | 01-NOV-16:00 | 9.40 | 6.91 | 0.160538E+10 | 2502.18 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.364551E+10 | 6435.78 | 01-DEC-16:40 | 7.20 | 5.06 | 0.143232E+10 | 2226.99 | 01-DEC-14:00 | 7.20 | 5.06 |
Annual Sum or Average | 0.128099E+12 | 0.211889E+11 | ||||||||
Minimum of Months | 0.321730E+10 | 6080.72 | -6.5 | -8.3 | 0.135562E+10 | 2114.10 | -6.5 | -8.3 | ||
Maximum of Months | 0.196875E+11 | 30807.72 | 26.52 | 23.72 | 0.215110E+10 | 2641.57 | 25.85 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19260003.06 | 1007.02 | 14-JAN-17:03 | 3.22 | 2.72 | 0.304283E+09 | 406.79 | 30-JAN-14:00 | -8.9 | -10.2 |
February | 42341961.56 | 1002.64 | 18-FEB-17:03 | 0.82 | -0.6 | 0.275872E+09 | 406.79 | 21-FEB-10:00 | -10.6 | -12.0 |
March | 0.820789E+09 | 3778.25 | 15-MAR-14:40 | 25.77 | 16.18 | 0.352672E+09 | 549.50 | 15-MAR-13:30 | 25.77 | 16.18 |
April | 0.144576E+10 | 2629.34 | 21-APR-15:20 | 14.43 | 8.49 | 0.334992E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.286980E+10 | 4836.97 | 23-MAY-14:40 | 23.90 | 13.32 | 0.413332E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.485679E+10 | 8241.71 | 27-JUN-15:05 | 25.68 | 22.74 | 0.432152E+09 | 568.10 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.567670E+10 | 9540.99 | 16-JUL-16:42 | 27.77 | 20.68 | 0.404799E+09 | 549.52 | 24-JUL-13:30 | 25.85 | 17.85 |
August | 0.519573E+10 | 11352.29 | 13-AUG-15:02 | 29.90 | 23.27 | 0.451405E+09 | 549.54 | 02-AUG-13:09 | 29.90 | 23.27 |
September | 0.308020E+10 | 4801.57 | 15-SEP-14:00 | 25.60 | 21.03 | 0.387085E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.145821E+10 | 2677.54 | 12-OCT-15:20 | 18.30 | 15.11 | 0.349883E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.519953E+09 | 1445.13 | 16-NOV-16:50 | 18.12 | 13.51 | 0.310389E+09 | 486.72 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 52736469.99 | 1143.19 | 01-DEC-13:30 | 11.10 | 9.57 | 0.293489E+09 | 415.72 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.260383E+11 | 0.431035E+10 | ||||||||
Minimum of Months | 19260003.06 | 1002.64 | 0.82 | -0.6 | 0.275872E+09 | 406.79 | -10.6 | -12.0 | ||
Maximum of Months | 0.567670E+10 | 11352.29 | 29.90 | 23.27 | 0.451405E+09 | 568.10 | 29.90 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22654162.83 | 987.15 | 14-JAN-17:03 | 3.22 | 2.72 | 0.193096E+09 | 257.54 | 09-JAN-14:20 | 3.22 | 2.72 |
February | 0.149116E+09 | 1342.07 | 28-FEB-10:05 | -3.6 | -5.3 | 0.175937E+09 | 299.19 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.103980E+10 | 2902.06 | 15-MAR-14:00 | 26.10 | 16.06 | 0.229540E+09 | 347.88 | 15-MAR-13:30 | 26.10 | 16.06 |
April | 0.186309E+10 | 5495.05 | 24-APR-09:10 | 6.28 | 2.92 | 0.224171E+09 | 347.88 | 21-APR-13:00 | 6.28 | 2.92 |
May | 0.339018E+10 | 9154.84 | 21-MAY-09:13 | 16.50 | 11.82 | 0.265175E+09 | 347.88 | 26-MAY-09:00 | 18.90 | 12.57 |
June | 0.493147E+10 | 10565.95 | 18-JUN-10:32 | 25.40 | 21.05 | 0.274026E+09 | 348.40 | 12-JUN-09:00 | 25.40 | 21.05 |
July | 0.555960E+10 | 14107.06 | 04-JUL-08:52 | 21.10 | 17.14 | 0.256449E+09 | 348.32 | 03-JUL-09:50 | 21.10 | 17.14 |
August | 0.515745E+10 | 9683.87 | 13-AUG-15:02 | 29.90 | 23.27 | 0.285916E+09 | 347.92 | 04-AUG-09:09 | 29.90 | 23.27 |
September | 0.338316E+10 | 8736.81 | 04-SEP-10:32 | 18.53 | 13.52 | 0.246696E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.154829E+10 | 4252.76 | 11-OCT-09:30 | 15.85 | 11.81 | 0.228101E+09 | 347.88 | 10-OCT-09:30 | 15.85 | 11.81 |
November | 0.528705E+09 | 1543.13 | 03-NOV-09:30 | 4.75 | 2.42 | 0.197731E+09 | 329.90 | 03-NOV-09:30 | 4.75 | 2.42 |
December | 45492388.62 | 982.52 | 02-DEC-17:03 | 2.62 | 1.32 | 0.186256E+09 | 257.55 | 26-DEC-10:39 | -11.1 | -12.5 |
Annual Sum or Average | 0.276190E+11 | 0.276309E+10 | ||||||||
Minimum of Months | 22654162.83 | 982.52 | -3.6 | -5.3 | 0.175937E+09 | 257.54 | -11.1 | -12.5 | ||
Maximum of Months | 0.555960E+10 | 14107.06 | 29.90 | 23.27 | 0.285916E+09 | 348.40 | 29.90 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480603E+09 | 4429.16 | 12-JAN-13:40 | -6.5 | -9.0 | 0.318032E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.637392E+09 | 6390.96 | 28-FEB-13:50 | 0.00 | -3.0 | 0.292591E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.220537E+10 | 10203.25 | 15-MAR-13:30 | 25.55 | 15.84 | 0.386506E+09 | 549.91 | 15-MAR-13:39 | 25.73 | 15.91 |
April | 0.279489E+10 | 8328.15 | 21-APR-13:10 | 15.40 | 7.97 | 0.352940E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.440425E+10 | 8166.69 | 26-MAY-13:30 | 20.85 | 13.56 | 0.413274E+09 | 549.52 | 10-MAY-13:00 | 20.85 | 13.56 |
June | 0.608244E+10 | 10283.79 | 18-JUN-11:53 | 26.10 | 20.70 | 0.429727E+09 | 564.04 | 27-JUN-15:09 | 25.68 | 22.74 |
July | 0.716106E+10 | 17078.32 | 30-JUL-13:53 | 25.60 | 19.95 | 0.403846E+09 | 549.99 | 31-JUL-13:50 | 25.18 | 19.30 |
August | 0.750632E+10 | 17494.35 | 13-AUG-15:02 | 29.90 | 23.27 | 0.450707E+09 | 550.09 | 03-AUG-13:00 | 29.90 | 23.27 |
September | 0.591354E+10 | 18416.22 | 10-SEP-13:32 | 17.20 | 10.63 | 0.390685E+09 | 550.14 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.331518E+10 | 12314.04 | 11-OCT-12:30 | 21.95 | 13.79 | 0.376325E+09 | 549.81 | 11-OCT-13:20 | 22.20 | 14.14 |
November | 0.133894E+10 | 7883.00 | 03-NOV-12:25 | 8.35 | 4.56 | 0.332914E+09 | 549.50 | 01-NOV-13:00 | 8.35 | 4.56 |
December | 0.377556E+09 | 3952.73 | 16-DEC-13:30 | 5.60 | 3.03 | 0.300700E+09 | 549.48 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.422175E+11 | 0.444825E+10 | ||||||||
Minimum of Months | 0.377556E+09 | 3952.73 | -6.5 | -9.0 | 0.292591E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.750632E+10 | 18416.22 | 29.90 | 23.27 | 0.450707E+09 | 564.04 | 29.90 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62151535.06 | 1309.40 | 12-JAN-16:00 | -6.1 | -8.3 | 0.193236E+09 | 271.65 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.144808E+09 | 1901.87 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176555E+09 | 338.61 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.103182E+10 | 3773.47 | 15-MAR-14:20 | 25.93 | 16.12 | 0.226091E+09 | 347.85 | 15-MAR-13:39 | 25.93 | 16.12 |
April | 0.183433E+10 | 6519.80 | 24-APR-16:00 | 13.30 | 7.63 | 0.210052E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.344934E+10 | 13004.20 | 27-MAY-17:05 | 20.32 | 11.21 | 0.253279E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.510110E+10 | 15532.20 | 11-JUN-17:02 | 25.50 | 17.77 | 0.269659E+09 | 368.84 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.544416E+10 | 16010.69 | 02-JUL-17:12 | 24.63 | 16.88 | 0.254446E+09 | 347.87 | 24-JUL-13:30 | 25.85 | 17.85 |
August | 0.514849E+10 | 15728.77 | 27-AUG-15:52 | 23.30 | 19.27 | 0.282479E+09 | 347.88 | 02-AUG-13:09 | 23.30 | 19.27 |
September | 0.331875E+10 | 15773.23 | 04-SEP-16:32 | 18.30 | 12.97 | 0.238905E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.159994E+10 | 6159.93 | 11-OCT-16:00 | 21.70 | 14.52 | 0.218052E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.544455E+09 | 1772.64 | 03-NOV-15:30 | 9.45 | 5.21 | 0.197205E+09 | 335.27 | 03-NOV-15:39 | 9.27 | 5.12 |
December | 71257938.43 | 1297.19 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186298E+09 | 269.67 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.277506E+11 | 0.270626E+10 | ||||||||
Minimum of Months | 62151535.06 | 1297.19 | -6.1 | -8.3 | 0.176555E+09 | 269.67 | -6.2 | -8.3 | ||
Maximum of Months | 0.544416E+10 | 16010.69 | 25.93 | 19.27 | 0.282479E+09 | 368.84 | 25.93 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26029659.43 | 999.59 | 14-JAN-17:03 | 3.22 | 2.72 | 0.305123E+09 | 406.81 | 03-JAN-14:20 | 3.22 | 2.72 |
February | 33315281.25 | 988.31 | 18-FEB-17:03 | 0.82 | -0.6 | 0.277165E+09 | 406.78 | 21-FEB-14:09 | -9.0 | -10.5 |
March | 0.679428E+09 | 1634.69 | 15-MAR-15:30 | 25.30 | 16.10 | 0.347074E+09 | 539.74 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.128730E+10 | 1510.11 | 21-APR-15:40 | 13.87 | 8.65 | 0.324031E+09 | 511.38 | 07-APR-13:00 | 13.87 | 8.65 |
May | 0.216404E+10 | 2925.91 | 23-MAY-14:40 | 23.90 | 13.32 | 0.403669E+09 | 549.49 | 10-MAY-13:09 | 23.90 | 13.32 |
June | 0.371917E+10 | 4882.88 | 26-JUN-15:40 | 28.13 | 20.69 | 0.432375E+09 | 549.52 | 22-JUN-13:09 | 28.13 | 20.69 |
July | 0.466091E+10 | 5540.06 | 21-JUL-13:50 | 31.52 | 21.79 | 0.404595E+09 | 549.50 | 12-JUL-09:00 | 31.52 | 21.79 |
August | 0.461955E+10 | 5519.78 | 14-AUG-12:30 | 26.40 | 21.20 | 0.453326E+09 | 555.02 | 14-AUG-09:00 | 26.40 | 21.20 |
September | 0.301767E+10 | 4151.54 | 15-SEP-14:00 | 25.60 | 21.03 | 0.396177E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.186109E+10 | 2334.22 | 05-OCT-14:40 | 18.90 | 12.59 | 0.370884E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.110151E+10 | 1435.05 | 16-NOV-16:40 | 17.93 | 13.54 | 0.324038E+09 | 496.70 | 01-NOV-13:39 | 17.93 | 13.54 |
December | 0.127734E+09 | 1233.93 | 01-DEC-13:30 | 11.10 | 9.57 | 0.296164E+09 | 441.10 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.232977E+11 | 0.433462E+10 | ||||||||
Minimum of Months | 26029659.43 | 988.31 | 0.82 | -0.6 | 0.277165E+09 | 406.78 | -9.0 | -10.5 | ||
Maximum of Months | 0.466091E+10 | 5540.06 | 31.52 | 21.79 | 0.453326E+09 | 555.02 | 31.52 | 21.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31384161.39 | 823.84 | 14-JAN-17:03 | 3.22 | 2.72 | 0.193710E+09 | 257.57 | 02-JAN-14:39 | 3.22 | 2.72 |
February | 0.121803E+09 | 1011.11 | 28-FEB-09:55 | -3.9 | -5.5 | 0.176429E+09 | 282.52 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.862059E+09 | 1601.34 | 15-MAR-14:00 | 26.10 | 16.06 | 0.228121E+09 | 347.86 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.149279E+10 | 3994.63 | 24-APR-09:20 | 6.47 | 3.13 | 0.225480E+09 | 347.88 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.248344E+10 | 5224.84 | 31-MAY-09:10 | 17.88 | 13.30 | 0.266045E+09 | 347.88 | 26-MAY-09:00 | 17.88 | 13.30 |
June | 0.405863E+10 | 8863.19 | 23-JUN-06:02 | 13.90 | 11.85 | 0.275118E+09 | 347.89 | 22-JUN-13:09 | 13.90 | 11.85 |
July | 0.485917E+10 | 12179.66 | 04-JUL-09:21 | 21.65 | 17.37 | 0.256834E+09 | 347.94 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.476302E+10 | 6789.85 | 10-AUG-10:00 | 27.80 | 20.31 | 0.287540E+09 | 348.76 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.329483E+10 | 5433.17 | 21-SEP-09:20 | 19.83 | 15.19 | 0.252391E+09 | 347.89 | 12-SEP-13:09 | 19.83 | 15.19 |
October | 0.175628E+10 | 3825.24 | 11-OCT-09:30 | 15.85 | 11.81 | 0.245341E+09 | 347.88 | 03-OCT-09:00 | 15.85 | 11.81 |
November | 0.953692E+09 | 1554.21 | 03-NOV-08:35 | 3.53 | 1.63 | 0.207870E+09 | 347.87 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 0.102031E+09 | 975.06 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187561E+09 | 270.69 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.247791E+11 | 0.280244E+10 | ||||||||
Minimum of Months | 31384161.39 | 823.84 | -3.9 | -5.5 | 0.176429E+09 | 257.57 | -3.6 | -5.3 | ||
Maximum of Months | 0.485917E+10 | 12179.66 | 27.80 | 20.31 | 0.287540E+09 | 348.76 | 26.10 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82856669.47 | 1280.32 | 21-JAN-12:30 | -0.6 | -3.1 | 0.283386E+09 | 437.61 | 12-JAN-14:00 | -0.6 | -3.1 |
February | 0.107469E+09 | 1489.47 | 18-FEB-14:40 | 2.80 | 0.63 | 0.258857E+09 | 470.78 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.927504E+09 | 6388.50 | 15-MAR-13:30 | 25.55 | 15.84 | 0.348650E+09 | 549.50 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.134749E+10 | 5150.21 | 23-APR-13:35 | 16.13 | 9.68 | 0.327464E+09 | 549.51 | 21-APR-13:00 | 16.13 | 9.68 |
May | 0.234995E+10 | 5579.64 | 16-MAY-12:10 | 19.18 | 11.50 | 0.393629E+09 | 549.51 | 05-MAY-13:09 | 19.18 | 11.50 |
June | 0.422592E+10 | 11076.63 | 27-JUN-12:00 | 30.00 | 22.87 | 0.423611E+09 | 549.53 | 22-JUN-13:09 | 30.00 | 22.87 |
July | 0.608652E+10 | 11321.24 | 21-JUL-12:00 | 30.00 | 21.57 | 0.402717E+09 | 550.14 | 17-JUL-13:20 | 30.00 | 21.57 |
August | 0.667066E+10 | 14063.15 | 13-AUG-15:02 | 29.90 | 23.27 | 0.449804E+09 | 553.21 | 10-AUG-12:09 | 29.90 | 23.27 |
September | 0.502155E+10 | 13765.91 | 04-SEP-12:02 | 18.98 | 12.67 | 0.393504E+09 | 549.87 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.257294E+10 | 10397.26 | 11-OCT-12:30 | 21.95 | 13.79 | 0.375367E+09 | 549.79 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.987362E+09 | 5348.24 | 01-NOV-12:08 | 11.20 | 6.39 | 0.325606E+09 | 549.50 | 01-NOV-13:00 | 10.60 | 6.85 |
December | 0.135078E+09 | 2158.88 | 16-DEC-13:30 | 5.60 | 3.03 | 0.279196E+09 | 465.42 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.305153E+11 | 0.426179E+10 | ||||||||
Minimum of Months | 82856669.47 | 1280.32 | -0.6 | -3.1 | 0.258857E+09 | 437.61 | -0.6 | -3.1 | ||
Maximum of Months | 0.667066E+10 | 14063.15 | 30.00 | 23.27 | 0.449804E+09 | 553.21 | 30.00 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53488894.55 | 1060.17 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193763E+09 | 276.58 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.103576E+09 | 1302.93 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176680E+09 | 318.93 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.824506E+09 | 1887.79 | 15-MAR-14:20 | 25.93 | 16.12 | 0.223830E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.141780E+10 | 4023.57 | 24-APR-17:30 | 11.70 | 7.64 | 0.212770E+09 | 347.84 | 21-APR-13:00 | 11.70 | 7.64 |
May | 0.243660E+10 | 8384.58 | 07-MAY-18:03 | 13.80 | 5.19 | 0.257559E+09 | 347.84 | 23-MAY-13:09 | 22.98 | 12.85 |
June | 0.417334E+10 | 12555.30 | 11-JUN-17:31 | 25.20 | 17.61 | 0.273957E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.465232E+10 | 12164.21 | 02-JUL-18:12 | 23.53 | 16.58 | 0.256492E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.467859E+10 | 12200.52 | 13-AUG-15:02 | 29.90 | 23.27 | 0.287206E+09 | 348.78 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.308219E+10 | 11166.83 | 10-SEP-17:42 | 16.10 | 10.54 | 0.250949E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.175724E+10 | 5202.31 | 11-OCT-16:00 | 21.70 | 14.52 | 0.235543E+09 | 347.85 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.943217E+09 | 1513.65 | 03-NOV-15:30 | 9.45 | 5.21 | 0.205383E+09 | 338.68 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 0.118010E+09 | 1091.08 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187570E+09 | 281.49 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.242409E+11 | 0.276170E+10 | ||||||||
Minimum of Months | 53488894.55 | 1060.17 | -6.2 | -8.3 | 0.176680E+09 | 276.58 | -6.3 | -8.3 | ||
Maximum of Months | 0.467859E+10 | 12555.30 | 29.90 | 23.27 | 0.287206E+09 | 348.78 | 25.93 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62646169.05 | 1066.83 | 11-JAN-16:50 | 11.20 | 9.89 | 0.305364E+09 | 406.78 | 23-JAN-10:30 | -6.7 | -8.5 |
February | 0.120597E+09 | 1059.62 | 17-FEB-14:50 | 3.22 | 1.00 | 0.277297E+09 | 412.70 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.108194E+10 | 3386.34 | 15-MAR-14:40 | 25.77 | 16.18 | 0.360774E+09 | 549.49 | 16-MAR-09:00 | 13.90 | 12.34 |
April | 0.170040E+10 | 2523.14 | 21-APR-15:20 | 14.43 | 8.49 | 0.349583E+09 | 549.49 | 21-APR-13:00 | 14.43 | 8.49 |
May | 0.296830E+10 | 4604.55 | 23-MAY-14:40 | 23.90 | 13.32 | 0.424023E+09 | 549.50 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.483434E+10 | 6694.59 | 12-JUN-06:03 | 22.98 | 18.45 | 0.434608E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.554976E+10 | 7854.17 | 03-JUL-06:02 | 12.77 | 11.69 | 0.405355E+09 | 549.60 | 20-JUL-13:30 | 30.00 | 23.60 |
August | 0.518138E+10 | 7903.40 | 07-AUG-06:03 | 20.68 | 18.73 | 0.453693E+09 | 549.54 | 02-AUG-13:09 | 20.68 | 18.73 |
September | 0.325333E+10 | 4614.84 | 13-SEP-13:30 | 22.20 | 19.01 | 0.396100E+09 | 549.52 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.181783E+10 | 2810.70 | 12-OCT-14:50 | 18.30 | 15.17 | 0.368946E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.17 |
November | 0.967290E+09 | 1475.26 | 16-NOV-16:50 | 18.12 | 13.51 | 0.322384E+09 | 509.84 | 01-NOV-13:50 | 18.12 | 13.51 |
December | 0.137750E+09 | 1213.82 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295558E+09 | 441.57 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.276756E+11 | 0.439369E+10 | ||||||||
Minimum of Months | 62646169.05 | 1059.62 | 3.22 | 1.00 | 0.277297E+09 | 406.78 | -6.7 | -8.5 | ||
Maximum of Months | 0.554976E+10 | 7903.40 | 25.77 | 19.01 | 0.453693E+09 | 549.60 | 30.00 | 23.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72088146.01 | 1053.20 | 12-JAN-10:00 | -10.0 | -12.3 | 0.142529E+09 | 251.14 | 12-JAN-09:00 | -10.0 | -12.3 |
February | 0.208475E+09 | 1450.63 | 28-FEB-09:50 | -4.5 | -6.0 | 0.130296E+09 | 312.09 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.124302E+10 | 2984.23 | 14-MAR-10:30 | 20.80 | 17.14 | 0.172003E+09 | 338.72 | 21-MAR-10:20 | 2.97 | 0.65 |
April | 0.212688E+10 | 6383.26 | 24-APR-08:40 | 5.73 | 2.63 | 0.168325E+09 | 338.73 | 21-APR-14:09 | 5.73 | 2.63 |
May | 0.346881E+10 | 8028.18 | 29-MAY-09:43 | 18.12 | 14.19 | 0.197565E+09 | 338.73 | 26-MAY-10:09 | 18.12 | 14.19 |
June | 0.483569E+10 | 14089.08 | 11-JUN-08:52 | 23.30 | 16.13 | 0.202752E+09 | 338.86 | 23-JUN-08:00 | 15.60 | 11.53 |
July | 0.537752E+10 | 15386.73 | 04-JUL-08:41 | 21.10 | 17.25 | 0.190167E+09 | 341.76 | 17-JUL-07:19 | 23.50 | 20.94 |
August | 0.504585E+10 | 8546.73 | 02-AUG-08:30 | 18.85 | 14.82 | 0.211508E+09 | 339.76 | 15-AUG-14:39 | 24.23 | 21.18 |
September | 0.348120E+10 | 7803.46 | 04-SEP-08:43 | 16.05 | 12.76 | 0.184068E+09 | 338.74 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.186958E+10 | 4961.82 | 11-OCT-09:00 | 15.00 | 11.35 | 0.173460E+09 | 338.73 | 03-OCT-10:09 | 15.00 | 11.35 |
November | 0.858566E+09 | 1953.39 | 03-NOV-09:00 | 3.90 | 1.83 | 0.149211E+09 | 338.71 | 03-NOV-08:00 | 3.90 | 1.83 |
December | 98147603.63 | 1118.24 | 01-DEC-13:30 | 11.10 | 9.57 | 0.137744E+09 | 260.08 | 01-DEC-13:39 | 10.17 | 8.68 |
Annual Sum or Average | 0.286858E+11 | 0.205963E+10 | ||||||||
Minimum of Months | 72088146.01 | 1053.20 | -10.0 | -12.3 | 0.130296E+09 | 251.14 | -10.0 | -12.3 | ||
Maximum of Months | 0.537752E+10 | 15386.73 | 23.30 | 17.25 | 0.211508E+09 | 341.76 | 24.23 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639664E+09 | 5462.99 | 12-JAN-13:30 | -6.7 | -9.2 | 0.323662E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.827658E+09 | 6731.00 | 28-FEB-13:40 | 0.00 | -2.9 | 0.298580E+09 | 549.49 | 08-FEB-14:00 | 0.00 | -2.9 |
March | 0.258059E+10 | 9797.35 | 15-MAR-13:30 | 25.55 | 15.84 | 0.398647E+09 | 549.84 | 15-MAR-13:50 | 25.92 | 15.99 |
April | 0.308041E+10 | 11977.10 | 23-APR-13:32 | 16.13 | 9.68 | 0.366735E+09 | 549.52 | 21-APR-13:00 | 16.13 | 9.68 |
May | 0.446051E+10 | 7686.84 | 26-MAY-13:30 | 20.85 | 13.56 | 0.423861E+09 | 549.51 | 05-MAY-13:09 | 20.85 | 13.56 |
June | 0.596381E+10 | 12801.45 | 18-JUN-15:02 | 25.55 | 20.06 | 0.433472E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.692762E+10 | 15545.94 | 30-JUL-13:53 | 25.60 | 19.95 | 0.405291E+09 | 550.10 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.737244E+10 | 15774.36 | 13-AUG-13:13 | 30.00 | 22.88 | 0.453800E+09 | 550.06 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.606083E+10 | 15932.48 | 04-SEP-12:02 | 18.98 | 12.67 | 0.398143E+09 | 550.29 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.380164E+10 | 12423.43 | 11-OCT-12:30 | 21.95 | 13.79 | 0.392390E+09 | 550.06 | 30-OCT-13:50 | 14.72 | 8.63 |
November | 0.186790E+10 | 8819.17 | 03-NOV-12:25 | 8.35 | 4.56 | 0.347040E+09 | 549.50 | 01-NOV-13:00 | 8.35 | 4.56 |
December | 0.564541E+09 | 4571.73 | 16-DEC-13:30 | 5.60 | 3.03 | 0.305632E+09 | 549.48 | 11-DEC-14:39 | 5.60 | 3.03 |
Annual Sum or Average | 0.441476E+11 | 0.454725E+10 | ||||||||
Minimum of Months | 0.564541E+09 | 4571.73 | -6.7 | -9.2 | 0.298580E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.737244E+10 | 15932.48 | 30.00 | 22.88 | 0.453800E+09 | 550.29 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111609E+09 | 1328.99 | 12-JAN-16:00 | -6.1 | -8.3 | 0.193963E+09 | 287.91 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.214296E+09 | 1981.82 | 28-FEB-16:40 | -0.2 | -2.7 | 0.177537E+09 | 338.68 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.124835E+10 | 3600.32 | 21-MAR-16:00 | 4.40 | 1.34 | 0.230963E+09 | 347.85 | 16-MAR-13:00 | 4.40 | 1.34 |
April | 0.205387E+10 | 6493.83 | 24-APR-16:00 | 13.30 | 7.63 | 0.217908E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.345457E+10 | 12116.04 | 27-MAY-17:05 | 20.32 | 11.21 | 0.261760E+09 | 347.85 | 17-MAY-09:00 | 20.32 | 11.21 |
June | 0.499494E+10 | 15426.67 | 11-JUN-16:11 | 25.60 | 17.82 | 0.273017E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.526333E+10 | 14827.02 | 02-JUL-16:52 | 25.00 | 17.00 | 0.255954E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.503175E+10 | 13904.71 | 06-AUG-16:32 | 27.80 | 18.98 | 0.285710E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.335549E+10 | 12194.07 | 04-SEP-15:23 | 18.60 | 13.14 | 0.246678E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.192577E+10 | 6126.31 | 11-OCT-16:00 | 21.70 | 14.52 | 0.228184E+09 | 347.85 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.908916E+09 | 2128.33 | 03-NOV-15:00 | 10.00 | 5.48 | 0.202455E+09 | 347.71 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 0.148488E+09 | 1309.26 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187206E+09 | 284.66 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.287114E+11 | 0.276133E+10 | ||||||||
Minimum of Months | 0.111609E+09 | 1309.26 | -6.1 | -8.3 | 0.177537E+09 | 284.66 | -6.2 | -8.3 | ||
Maximum of Months | 0.526333E+10 | 15426.67 | 27.80 | 18.98 | 0.285710E+09 | 347.88 | 27.80 | 18.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195083E+09 | 9465.14 | 02-JAN-05:01 | -0.7 |
February | 688253.03 | 4075.64 | 06-FEB-07:01 | -14.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.195771E+09 | |||
Minimum of Months | 0.00 | 0.00 | -14.1 | |
Maximum of Months | 0.195083E+09 | 9465.14 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676597E+10 | 14124.93 | 10-JAN-06:09 | -13.0 |
February | 0.573698E+10 | 14627.99 | 07-FEB-06:09 | -16.2 |
March | 0.279007E+10 | 13993.53 | 07-MAR-06:07 | -13.3 |
April | 0.107202E+10 | 11595.20 | 17-APR-05:13 | -4.1 |
May | 0.392850E+09 | 4171.28 | 08-MAY-05:03 | 3.40 |
June | 0.137740E+09 | 3810.87 | 14-JUN-05:03 | 6.78 |
July | 76300342.08 | 3361.06 | 04-JUL-06:20 | 16.67 |
August | 0.118250E+09 | 3184.11 | 03-AUG-05:03 | 11.10 |
September | 0.310297E+09 | 5264.09 | 04-SEP-07:58 | 12.80 |
October | 0.102690E+10 | 9522.33 | 30-OCT-06:12 | -0.2 |
November | 0.224940E+10 | 11531.73 | 24-NOV-06:13 | -3.7 |
December | 0.606232E+10 | 14329.91 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.267391E+11 | |||
Minimum of Months | 76300342.08 | 3184.11 | -18.2 | |
Maximum of Months | 0.676597E+10 | 14627.99 | 16.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316111E+10 | 9688.53 | 02-JAN-08:10 | -1.1 |
February | 0.262253E+10 | 7649.10 | 06-FEB-06:10 | -13.9 |
March | 0.136240E+10 | 6398.82 | 06-MAR-07:11 | -10.5 |
April | 0.557699E+09 | 3785.17 | 23-APR-13:32 | 16.13 |
May | 87104099.90 | 2932.22 | 07-MAY-16:53 | 15.00 |
June | 19490610.91 | 3092.50 | 11-JUN-14:52 | 26.10 |
July | 23320967.74 | 2451.98 | 21-JUL-04:03 | 26.52 |
August | 15544536.72 | 3559.79 | 13-AUG-15:12 | 29.80 |
September | 28550774.64 | 4530.97 | 04-SEP-15:23 | 18.60 |
October | 0.553887E+09 | 5104.43 | 09-OCT-11:13 | 11.30 |
November | 0.104622E+10 | 5169.84 | 24-NOV-07:12 | -3.1 |
December | 0.260642E+10 | 7627.49 | 26-DEC-07:50 | -12.7 |
Annual Sum or Average | 0.120843E+11 | |||
Minimum of Months | 15544536.72 | 2451.98 | -13.9 | |
Maximum of Months | 0.316111E+10 | 9688.53 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238813E+10 | 7964.55 | 02-JAN-08:50 | -1.1 |
February | 0.187470E+10 | 4468.12 | 06-FEB-07:01 | -14.1 |
March | 0.868637E+09 | 3374.29 | 06-MAR-08:30 | -8.9 |
April | 0.234682E+09 | 4801.14 | 24-APR-05:03 | 0.68 |
May | 16807621.29 | 2273.52 | 07-MAY-15:23 | 15.00 |
June | 21415416.30 | 2015.84 | 04-JUN-14:23 | 20.00 |
July | 25115176.11 | 3165.79 | 20-JUL-04:03 | 24.82 |
August | 22417262.95 | 2380.24 | 13-AUG-15:02 | 29.90 |
September | 26173127.90 | 2789.22 | 17-SEP-14:50 | 22.70 |
October | 0.183627E+09 | 4596.50 | 24-OCT-05:03 | 0.78 |
November | 0.653246E+09 | 2507.57 | 24-NOV-08:20 | -2.4 |
December | 0.187196E+10 | 4256.89 | 11-DEC-08:23 | -14.4 |
Annual Sum or Average | 0.818691E+10 | |||
Minimum of Months | 16807621.29 | 2015.84 | -14.4 | |
Maximum of Months | 0.238813E+10 | 7964.55 | 29.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.835353E+09 | 17315.83 | 02-JAN-05:01 | -0.7 |
February | 0.469780E+09 | 14494.10 | 06-FEB-06:02 | -13.9 |
March | 49708721.01 | 13218.63 | 06-MAR-06:02 | -11.1 |
April | 3290464.83 | 11945.04 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 263526.21 | 3074.47 | 30-OCT-06:01 | -0.4 |
November | 13320701.71 | 12135.38 | 24-NOV-07:01 | -3.2 |
December | 0.342205E+09 | 14675.20 | 11-DEC-06:02 | -18.5 |
Annual Sum or Average | 0.171392E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.5 | |
Maximum of Months | 0.835353E+09 | 17315.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315500E+10 | 24200.73 | 02-JAN-05:01 | -0.7 |
February | 0.253949E+10 | 24137.28 | 06-FEB-05:01 | -14.8 |
March | 0.710836E+09 | 22850.38 | 06-MAR-05:01 | -11.1 |
April | 0.104830E+09 | 20994.93 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 75061648.13 | 20143.74 | 30-OCT-05:01 | -0.1 |
November | 0.346658E+09 | 21120.42 | 24-NOV-06:01 | -3.8 |
December | 0.234929E+10 | 24261.76 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.928117E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.315500E+10 | 24261.76 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542147E+10 | 9533.65 | 30-JAN-04:23 | -9.7 |
February | 0.449985E+10 | 9841.24 | 06-FEB-04:12 | -15.0 |
March | 0.185500E+10 | 9342.05 | 06-MAR-05:01 | -11.1 |
April | 0.315936E+09 | 8980.74 | 17-APR-04:01 | -3.4 |
May | 5132717.69 | 7013.51 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2944002.31 | 6956.04 | 30-SEP-06:03 | 7.30 |
October | 0.262426E+09 | 8497.45 | 30-OCT-04:02 | -0.5 |
November | 0.103941E+10 | 9143.52 | 24-NOV-05:01 | -3.0 |
December | 0.464494E+10 | 9815.27 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.180471E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.542147E+10 | 9841.24 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312183E+10 | 8406.80 | 30-JAN-04:23 | -9.7 |
February | 0.256908E+10 | 8786.23 | 06-FEB-04:12 | -15.0 |
March | 0.839961E+09 | 8250.95 | 06-MAR-05:01 | -11.1 |
April | 0.126659E+09 | 7840.88 | 17-APR-04:01 | -3.4 |
May | 2234645.61 | 4954.89 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2045414.40 | 5297.67 | 30-SEP-06:03 | 7.30 |
October | 0.139537E+09 | 7300.40 | 30-OCT-04:02 | -0.5 |
November | 0.599721E+09 | 8081.58 | 24-NOV-05:01 | -3.0 |
December | 0.287015E+10 | 8833.54 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.102712E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.312183E+10 | 8833.54 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388254E+10 | 11556.46 | 30-JAN-04:23 | -9.7 |
February | 0.328623E+10 | 12015.98 | 06-FEB-04:12 | -15.0 |
March | 0.108253E+10 | 11261.65 | 06-MAR-05:01 | -11.1 |
April | 0.265139E+09 | 10644.34 | 17-APR-04:01 | -3.4 |
May | 9311943.05 | 8056.25 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2686828.47 | 7933.63 | 30-SEP-06:03 | 7.30 |
October | 0.177633E+09 | 10008.87 | 30-OCT-04:02 | -0.5 |
November | 0.762240E+09 | 11079.99 | 24-NOV-05:01 | -3.0 |
December | 0.348100E+10 | 12007.37 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.129493E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.388254E+10 | 12015.98 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342120E+10 | 8810.26 | 30-JAN-04:23 | -9.7 |
February | 0.280178E+10 | 9230.83 | 06-FEB-04:12 | -15.0 |
March | 0.998771E+09 | 8608.49 | 06-MAR-05:01 | -11.1 |
April | 0.193876E+09 | 7951.69 | 17-APR-04:01 | -3.4 |
May | 7110608.60 | 5698.63 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2666366.96 | 5238.66 | 30-SEP-06:03 | 7.30 |
October | 0.164041E+09 | 7490.05 | 30-OCT-04:02 | -0.5 |
November | 0.663267E+09 | 8415.13 | 24-NOV-05:01 | -3.0 |
December | 0.294566E+10 | 9241.32 | 11-DEC-05:11 | -17.8 |
Annual Sum or Average | 0.111984E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.8 | |
Maximum of Months | 0.342120E+10 | 9241.32 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367573E+10 | 7183.21 | 02-JAN-02:63 | -1.7 |
February | 0.292679E+10 | 7276.62 | 06-FEB-04:12 | -15.0 |
March | 0.124424E+10 | 7113.51 | 06-MAR-05:01 | -11.1 |
April | 0.140267E+09 | 6300.63 | 17-APR-05:01 | -4.0 |
May | 1242863.12 | 5333.42 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 12696852.21 | 5616.10 | 17-OCT-06:01 | -2.8 |
November | 0.156105E+09 | 6128.22 | 24-NOV-06:01 | -3.8 |
December | 0.225700E+10 | 7108.70 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.104141E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.367573E+10 | 7276.62 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205162E+10 | 6368.25 | 30-JAN-05:01 | -9.5 |
February | 0.155258E+10 | 6504.96 | 06-FEB-04:12 | -15.0 |
March | 0.399983E+09 | 6090.02 | 06-MAR-05:01 | -11.1 |
April | 32437176.26 | 5339.35 | 17-APR-05:01 | -4.0 |
May | 103455.63 | 500.25 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 6458711.35 | 4552.52 | 17-OCT-06:01 | -2.8 |
November | 90179117.29 | 5237.31 | 24-NOV-06:01 | -3.8 |
December | 0.135673E+10 | 6390.89 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.549008E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.205162E+10 | 6504.96 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601877E+10 | 11222.80 | 04-JAN-08:00 | -13.3 |
February | 0.508887E+10 | 11645.80 | 07-FEB-07:10 | -16.5 |
March | 0.256656E+10 | 10820.41 | 07-MAR-07:10 | -12.9 |
April | 0.132063E+10 | 9281.28 | 17-APR-06:10 | -4.2 |
May | 0.498006E+09 | 7737.34 | 01-MAY-06:10 | 2.35 |
June | 0.104700E+09 | 6511.64 | 14-JUN-06:10 | 7.67 |
July | 2355706.94 | 3079.41 | 06-JUL-06:08 | 13.07 |
August | 16349738.98 | 4666.03 | 02-AUG-06:07 | 11.85 |
September | 0.137891E+09 | 6410.56 | 06-SEP-06:08 | 6.28 |
October | 0.725338E+09 | 8458.13 | 17-OCT-06:10 | -2.8 |
November | 0.172630E+10 | 9131.14 | 24-NOV-07:10 | -3.2 |
December | 0.494694E+10 | 11496.52 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.231527E+11 | |||
Minimum of Months | 2355706.94 | 3079.41 | -16.5 | |
Maximum of Months | 0.601877E+10 | 11645.80 | 13.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229444E+10 | 6575.15 | 30-JAN-05:01 | -9.5 |
February | 0.174001E+10 | 6693.66 | 06-FEB-04:12 | -15.0 |
March | 0.454900E+09 | 6262.15 | 06-MAR-05:01 | -11.1 |
April | 51264294.35 | 5260.35 | 17-APR-05:01 | -4.0 |
May | 730607.41 | 3208.51 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 7074872.37 | 4639.51 | 17-OCT-06:01 | -2.8 |
November | 95136272.00 | 5274.54 | 24-NOV-06:01 | -3.8 |
December | 0.140564E+10 | 6571.99 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.604920E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.229444E+10 | 6693.66 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324199E+10 | 7684.38 | 30-JAN-05:01 | -9.5 |
February | 0.253892E+10 | 7858.85 | 13-FEB-05:11 | -9.1 |
March | 0.782441E+09 | 7684.12 | 06-MAR-05:01 | -11.1 |
April | 69611921.69 | 6709.69 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 41922544.52 | 6400.18 | 30-OCT-05:01 | -0.1 |
November | 0.282336E+09 | 6889.39 | 24-NOV-05:01 | -3.0 |
December | 0.247141E+10 | 7872.94 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.942863E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.324199E+10 | 7872.94 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188074E+10 | 7091.02 | 30-JAN-05:01 | -9.5 |
February | 0.144606E+10 | 7329.69 | 13-FEB-05:11 | -9.1 |
March | 0.320666E+09 | 7014.28 | 06-MAR-05:01 | -11.1 |
April | 25471421.66 | 5835.97 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 158088.19 | 1053.92 | 30-SEP-06:03 | 7.30 |
October | 28559332.92 | 5493.30 | 30-OCT-05:01 | -0.1 |
November | 0.174852E+09 | 6140.43 | 24-NOV-05:01 | -3.0 |
December | 0.156412E+10 | 7320.60 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.544062E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.188074E+10 | 7329.69 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215660E+10 | 9390.34 | 30-JAN-05:01 | -9.5 |
February | 0.168948E+10 | 9660.64 | 13-FEB-05:11 | -9.1 |
March | 0.362668E+09 | 8914.33 | 06-MAR-05:01 | -11.1 |
April | 57527287.83 | 7777.41 | 17-APR-05:01 | -4.0 |
May | 371815.86 | 3098.47 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 28849800.72 | 7390.68 | 30-OCT-05:01 | -0.1 |
November | 0.189462E+09 | 7962.62 | 24-NOV-06:01 | -3.8 |
December | 0.166377E+10 | 9669.83 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.614873E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.215660E+10 | 9669.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203337E+10 | 7233.71 | 30-JAN-05:01 | -9.5 |
February | 0.155656E+10 | 7476.72 | 13-FEB-05:11 | -9.1 |
March | 0.384242E+09 | 7061.94 | 06-MAR-05:01 | -11.1 |
April | 42251907.57 | 5721.48 | 17-APR-05:01 | -4.0 |
May | 290414.89 | 2420.12 | 01-MAY-06:02 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 42347.24 | 282.31 | 30-SEP-06:03 | 7.30 |
October | 30341580.52 | 5480.94 | 30-OCT-05:01 | -0.1 |
November | 0.189796E+09 | 6100.35 | 24-NOV-05:01 | -3.0 |
December | 0.155885E+10 | 7465.50 | 26-DEC-04:52 | -12.2 |
Annual Sum or Average | 0.579575E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 0.203337E+10 | 7476.72 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838871E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.702291E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.775995E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.660517E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.694200E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.679334E+09 | 711.15 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638323E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.724654E+09 | 774.31 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.680801E+09 | 947.97 | 14-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.755649E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841564E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.843643E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883584E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638323E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.843643E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515874E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.439151E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487360E+09 | 600.14 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418354E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442742E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433737E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407032E+09 | 450.21 | 11-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461307E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428862E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468762E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.518058E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515679E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553692E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407032E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.518058E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790656E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.682144E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764945E+09 | 1011.14 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.661965E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.700517E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.685468E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.644308E+09 | 774.31 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.728907E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676824E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.732804E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.797400E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.794634E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866057E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.644308E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.797400E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513904E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437043E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488336E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419395E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440951E+09 | 490.17 | 10-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431460E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405988E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460047E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430711E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.473677E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516635E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.517000E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553515E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405988E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.517000E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.833996E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.699502E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773634E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.659386E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.693316E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.678838E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.637855E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.723545E+09 | 711.15 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.678831E+09 | 947.97 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.752389E+09 | 1358.45 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.837027E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.838649E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.880697E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.637855E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.838649E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513619E+09 | 860.01 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437731E+09 | 860.01 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.486368E+09 | 600.14 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.417853E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442073E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433292E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.406666E+09 | 450.21 | 17-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460826E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428024E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467774E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516103E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.514168E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552450E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.406666E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.516103E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788494E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.680470E+09 | 1184.79 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763857E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.660924E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.699030E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.684654E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.643297E+09 | 711.15 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.727559E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.675263E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.731188E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.794840E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.791833E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.864141E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.643297E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.794840E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.511425E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.435830E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487068E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418538E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440165E+09 | 490.17 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.430945E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405451E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.459138E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.429897E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.472617E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.514477E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515447E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552100E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405451E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.515447E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.838729E+09 | 1358.45 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.702291E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.775995E+09 | 1184.79 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.660517E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.694200E+09 | 774.31 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.679334E+09 | 711.15 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638323E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.724654E+09 | 774.31 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.680801E+09 | 947.97 | 14-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.755590E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841526E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.843539E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883550E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638323E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.843539E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.515808E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.439151E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487360E+09 | 600.14 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418353E+09 | 490.21 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442742E+09 | 450.21 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.433737E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407032E+09 | 450.21 | 11-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461293E+09 | 450.21 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428862E+09 | 600.14 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468762E+09 | 750.07 | 23-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.518058E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.515679E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553684E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407032E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.518058E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.790656E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.682144E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764945E+09 | 1011.14 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.661952E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.700517E+09 | 774.31 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.685468E+09 | 711.15 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.644295E+09 | 774.31 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.728907E+09 | 774.31 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676824E+09 | 947.97 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.732804E+09 | 1358.45 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.797400E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.794634E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866055E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.644295E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.797400E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513904E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437043E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488336E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419395E+09 | 600.10 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440951E+09 | 490.17 | 10-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431460E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405988E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460047E+09 | 490.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430711E+09 | 750.02 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.473677E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.516635E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.516976E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553512E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405988E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.516976E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838871E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856029E+09 |
February | 0.901968E+09 | 0.702291E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911012E+09 |
March | 0.107774E+10 | 0.775995E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207661.38 | 0.563235E+09 |
April | 0.956342E+09 | 0.660517E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459513E+09 |
May | 0.103597E+10 | 0.694200E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167150.23 | 0.282271E+09 |
June | 0.103308E+10 | 0.679334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5047720.88 | 0.164769E+09 |
July | 0.959235E+09 | 0.638323E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12144661.13 | 98025304.50 |
August | 0.107774E+10 | 0.724654E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9868920.24 | 0.112144E+09 |
September | 0.956342E+09 | 0.680801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 710229.85 | 0.163243E+09 |
October | 0.994195E+09 | 0.755649E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347654E+09 |
November | 0.984487E+09 | 0.841564E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465951E+09 |
December | 0.959235E+09 | 0.843643E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906242E+09 |
Annual Sum or Average | 0.119305E+11 | 0.883584E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28146343.72 | 0.533009E+10 |
Minimum of Months | 0.901968E+09 | 0.638323E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98025304.50 |
Maximum of Months | 0.107774E+10 | 0.843643E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12144661.13 | 0.911012E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.515874E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571875E+09 |
February | 0.571020E+09 | 0.439151E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608386E+09 |
March | 0.682301E+09 | 0.487360E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132426.93 | 0.379220E+09 |
April | 0.605444E+09 | 0.418354E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311742E+09 |
May | 0.655854E+09 | 0.442742E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133987.70 | 0.193417E+09 |
June | 0.654023E+09 | 0.433737E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3352609.10 | 0.111484E+09 |
July | 0.607275E+09 | 0.407032E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7993760.68 | 66164569.36 |
August | 0.682301E+09 | 0.461307E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6523793.86 | 75922954.62 |
September | 0.605444E+09 | 0.428862E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 500755.64 | 0.110808E+09 |
October | 0.629407E+09 | 0.468762E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237199E+09 |
November | 0.623262E+09 | 0.518058E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312602E+09 |
December | 0.607275E+09 | 0.515679E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604981E+09 |
Annual Sum or Average | 0.755301E+10 | 0.553692E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18637333.92 | 0.358380E+10 |
Minimum of Months | 0.571020E+09 | 0.407032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66164569.36 |
Maximum of Months | 0.682301E+09 | 0.518058E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7993760.68 | 0.608386E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790656E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875008E+09 |
February | 0.901968E+09 | 0.682144E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924186E+09 |
March | 0.107774E+10 | 0.764945E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 196847.21 | 0.592773E+09 |
April | 0.956342E+09 | 0.661965E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476538E+09 |
May | 0.103597E+10 | 0.700517E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90850.18 | 0.290508E+09 |
June | 0.103308E+10 | 0.685468E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4884145.83 | 0.165607E+09 |
July | 0.959235E+09 | 0.644308E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11839757.11 | 99826090.87 |
August | 0.107774E+10 | 0.728907E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9036114.57 | 0.116385E+09 |
September | 0.956342E+09 | 0.676824E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 643757.95 | 0.173259E+09 |
October | 0.994195E+09 | 0.732804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373577E+09 |
November | 0.984487E+09 | 0.797400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484965E+09 |
December | 0.959235E+09 | 0.794634E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926119E+09 |
Annual Sum or Average | 0.119305E+11 | 0.866057E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26691472.85 | 0.549875E+10 |
Minimum of Months | 0.901968E+09 | 0.644308E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99826090.87 |
Maximum of Months | 0.107774E+10 | 0.797400E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11839757.11 | 0.926119E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.513904E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571563E+09 |
February | 0.570983E+09 | 0.437043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609241E+09 |
March | 0.682256E+09 | 0.488336E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170635.82 | 0.385498E+09 |
April | 0.605404E+09 | 0.419395E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315115E+09 |
May | 0.655811E+09 | 0.440951E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61901.90 | 0.194946E+09 |
June | 0.653980E+09 | 0.431460E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3507562.55 | 0.113919E+09 |
July | 0.607235E+09 | 0.405988E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8201644.98 | 68684206.17 |
August | 0.682256E+09 | 0.460047E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6655749.37 | 78466737.10 |
September | 0.605404E+09 | 0.430711E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 423530.16 | 0.111366E+09 |
October | 0.629366E+09 | 0.473677E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234708E+09 |
November | 0.623221E+09 | 0.516635E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311005E+09 |
December | 0.607235E+09 | 0.517000E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604632E+09 |
Annual Sum or Average | 0.755252E+10 | 0.553515E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19021024.78 | 0.359914E+10 |
Minimum of Months | 0.570983E+09 | 0.405988E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68684206.17 |
Maximum of Months | 0.682256E+09 | 0.517000E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8201644.98 | 0.609241E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.833996E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476485E+09 |
February | 0.901968E+09 | 0.699502E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504268E+09 |
March | 0.107774E+10 | 0.773634E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 218292.13 | 0.309027E+09 |
April | 0.956342E+09 | 0.659386E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247320E+09 |
May | 0.103597E+10 | 0.693316E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248785.33 | 0.144337E+09 |
June | 0.103308E+10 | 0.678838E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3666182.75 | 85470028.13 |
July | 0.959235E+09 | 0.637855E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7414412.14 | 49316390.47 |
August | 0.107774E+10 | 0.723545E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6184661.42 | 59606521.67 |
September | 0.956342E+09 | 0.678831E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415323.71 | 92035555.03 |
October | 0.994195E+09 | 0.752389E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206426E+09 |
November | 0.984487E+09 | 0.837027E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274604E+09 |
December | 0.959235E+09 | 0.838649E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515261E+09 |
Annual Sum or Average | 0.119305E+11 | 0.880697E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18147657.48 | 0.296416E+10 |
Minimum of Months | 0.901968E+09 | 0.637855E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49316390.47 |
Maximum of Months | 0.107774E+10 | 0.838649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7414412.14 | 0.515261E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.513619E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319289E+09 |
February | 0.571020E+09 | 0.437731E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337390E+09 |
March | 0.682301E+09 | 0.486368E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98654.32 | 0.209894E+09 |
April | 0.605444E+09 | 0.417853E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172386E+09 |
May | 0.655854E+09 | 0.442073E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104155.78 | 0.104039E+09 |
June | 0.654023E+09 | 0.433292E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1901528.76 | 60530347.54 |
July | 0.607275E+09 | 0.406666E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4481584.19 | 35624839.66 |
August | 0.682301E+09 | 0.460826E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3624153.10 | 42428519.02 |
September | 0.605444E+09 | 0.428024E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 271968.18 | 64285817.39 |
October | 0.629407E+09 | 0.467774E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142707E+09 |
November | 0.623262E+09 | 0.516103E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185183E+09 |
December | 0.607275E+09 | 0.514168E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344092E+09 |
Annual Sum or Average | 0.755301E+10 | 0.552450E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10482044.35 | 0.201785E+10 |
Minimum of Months | 0.571020E+09 | 0.406666E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35624839.66 |
Maximum of Months | 0.682301E+09 | 0.516103E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4481584.19 | 0.344092E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.788494E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650931E+10 |
February | 0.901968E+09 | 0.680470E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599568E+10 |
March | 0.107774E+10 | 0.763857E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7637474.70 | 0.510351E+10 |
April | 0.956342E+09 | 0.660924E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346183E+10 |
May | 0.103597E+10 | 0.699030E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2320190.39 | 0.223684E+10 |
June | 0.103308E+10 | 0.684654E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125765E+09 | 0.119850E+10 |
July | 0.959235E+09 | 0.643297E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351063E+09 | 0.481111E+09 |
August | 0.107774E+10 | 0.727559E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272231E+09 | 0.846345E+09 |
September | 0.956342E+09 | 0.675263E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13324262.27 | 0.146777E+10 |
October | 0.994195E+09 | 0.731188E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319257E+10 |
November | 0.984487E+09 | 0.794840E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410711E+10 |
December | 0.959235E+09 | 0.791833E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596474E+10 |
Annual Sum or Average | 0.119305E+11 | 0.864141E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772342E+09 | 0.405653E+11 |
Minimum of Months | 0.901968E+09 | 0.643297E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481111E+09 |
Maximum of Months | 0.107774E+10 | 0.794840E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351063E+09 | 0.650931E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.511425E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318109E+09 |
February | 0.570983E+09 | 0.435830E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337610E+09 |
March | 0.682256E+09 | 0.487068E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137784.98 | 0.212845E+09 |
April | 0.605404E+09 | 0.418538E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172660E+09 |
May | 0.655811E+09 | 0.440165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35301.23 | 0.105524E+09 |
June | 0.653980E+09 | 0.430945E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894236.35 | 62860118.37 |
July | 0.607235E+09 | 0.405451E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4573219.59 | 37792010.11 |
August | 0.682256E+09 | 0.459138E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3564190.48 | 44394849.87 |
September | 0.605404E+09 | 0.429897E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227938.55 | 64985808.14 |
October | 0.629366E+09 | 0.472617E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140742E+09 |
November | 0.623221E+09 | 0.514477E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184086E+09 |
December | 0.607235E+09 | 0.515447E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343738E+09 |
Annual Sum or Average | 0.755252E+10 | 0.552100E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10432671.18 | 0.202535E+10 |
Minimum of Months | 0.570983E+09 | 0.405451E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37792010.11 |
Maximum of Months | 0.682256E+09 | 0.515447E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4573219.59 | 0.343738E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.838729E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739310E+09 |
February | 0.901968E+09 | 0.702291E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784879E+09 |
March | 0.107774E+10 | 0.775995E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177036.99 | 0.493255E+09 |
April | 0.956342E+09 | 0.660517E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404828E+09 |
May | 0.103597E+10 | 0.694200E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 218377.09 | 0.244992E+09 |
June | 0.103308E+10 | 0.679334E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4513907.27 | 0.141591E+09 |
July | 0.959235E+09 | 0.638323E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10470625.00 | 83327325.46 |
August | 0.107774E+10 | 0.724654E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8655287.74 | 96582804.65 |
September | 0.956342E+09 | 0.680801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 613494.37 | 0.144345E+09 |
October | 0.994195E+09 | 0.755590E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315048E+09 |
November | 0.984487E+09 | 0.841526E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419607E+09 |
December | 0.959235E+09 | 0.843539E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789811E+09 |
Annual Sum or Average | 0.119305E+11 | 0.883550E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24648728.46 | 0.465758E+10 |
Minimum of Months | 0.901968E+09 | 0.638323E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83327325.46 |
Maximum of Months | 0.107774E+10 | 0.843539E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10470625.00 | 0.789811E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.515808E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494434E+09 |
February | 0.421807E+09 | 0.439151E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524010E+09 |
March | 0.502994E+09 | 0.487360E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115427.26 | 0.332095E+09 |
April | 0.447140E+09 | 0.418353E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273061E+09 |
May | 0.484071E+09 | 0.442742E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167882.24 | 0.166708E+09 |
June | 0.482240E+09 | 0.433737E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2962801.13 | 95423994.92 |
July | 0.448971E+09 | 0.407032E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6889415.55 | 56135184.36 |
August | 0.502994E+09 | 0.461293E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5664642.81 | 65154231.62 |
September | 0.447140E+09 | 0.428862E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 434104.97 | 97224632.33 |
October | 0.465148E+09 | 0.468762E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213035E+09 |
November | 0.460569E+09 | 0.518058E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280262E+09 |
December | 0.448971E+09 | 0.515679E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527087E+09 |
Annual Sum or Average | 0.557719E+10 | 0.553684E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16234273.95 | 0.312463E+10 |
Minimum of Months | 0.421807E+09 | 0.407032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56135184.36 |
Maximum of Months | 0.502994E+09 | 0.518058E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6889415.55 | 0.527087E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.790656E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760080E+09 |
February | 0.901968E+09 | 0.682144E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799031E+09 |
March | 0.107774E+10 | 0.764945E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 168504.36 | 0.519919E+09 |
April | 0.956342E+09 | 0.661952E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418649E+09 |
May | 0.103597E+10 | 0.700517E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77253.52 | 0.252105E+09 |
June | 0.103308E+10 | 0.685468E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4166690.46 | 0.143052E+09 |
July | 0.959235E+09 | 0.644295E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10066326.87 | 85609969.19 |
August | 0.107774E+10 | 0.728907E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7640243.06 | 0.100677E+09 |
September | 0.956342E+09 | 0.676824E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 548166.03 | 0.152398E+09 |
October | 0.994195E+09 | 0.732804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335501E+09 |
November | 0.984487E+09 | 0.797400E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435859E+09 |
December | 0.959235E+09 | 0.794634E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810259E+09 |
Annual Sum or Average | 0.119305E+11 | 0.866055E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22667184.30 | 0.481314E+10 |
Minimum of Months | 0.901968E+09 | 0.644295E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85609969.19 |
Maximum of Months | 0.107774E+10 | 0.797400E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10066326.87 | 0.810259E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.513904E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493179E+09 |
February | 0.570983E+09 | 0.437043E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524600E+09 |
March | 0.682256E+09 | 0.488336E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137942.39 | 0.337409E+09 |
April | 0.605404E+09 | 0.419395E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276487E+09 |
May | 0.655811E+09 | 0.440951E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51508.21 | 0.169208E+09 |
June | 0.653980E+09 | 0.431460E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2930914.70 | 98439400.73 |
July | 0.607235E+09 | 0.405988E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7001333.19 | 59074605.88 |
August | 0.682256E+09 | 0.460047E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5653652.45 | 68001968.12 |
September | 0.605404E+09 | 0.430711E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349979.47 | 98551940.65 |
October | 0.629366E+09 | 0.473677E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211605E+09 |
November | 0.623221E+09 | 0.516635E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279193E+09 |
December | 0.607235E+09 | 0.516976E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526616E+09 |
Annual Sum or Average | 0.755252E+10 | 0.553512E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16125330.41 | 0.314236E+10 |
Minimum of Months | 0.570983E+09 | 0.405988E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59074605.88 |
Maximum of Months | 0.682256E+09 | 0.516976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7001333.19 | 0.526616E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102140E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108123E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234437.56 | 0.690368E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564113E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182959.41 | 0.333638E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4225429.22 | 0.192508E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10879659.38 | 0.112342E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8980971.62 | 0.133304E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467004.55 | 0.203724E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452066E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601628E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110490E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24970461.75 | 0.649123E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112342E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10879659.38 | 0.110490E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125855E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133125E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351148.44 | 0.852612E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700198E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351381.70 | 0.419916E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5791141.16 | 0.244046E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14084373.06 | 0.142056E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12155477.91 | 0.167521E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653743.13 | 0.251640E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542677E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718651E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134691E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33387265.39 | 0.797603E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142056E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14084373.06 | 0.134691E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128383E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136709E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16987.48 | 0.870288E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719471E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13232.08 | 0.449097E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3444469.57 | 0.263302E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10594769.16 | 0.156494E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7445051.24 | 0.176990E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328977.73 | 0.260339E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541930E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710171E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136195E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21843487.25 | 0.816095E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156494E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10594769.16 | 0.136709E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1605.62 | 12-JAN-05:45 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1661.29 | 13-FEB-05:50 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | 15-MAR-14:00 | 924.40 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 848.96 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.59 | 14-MAY-15:00 | 572.79 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.38 | 17-JUN-17:03 | 485.47 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.47 | 15-JUL-15:00 | 350.84 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.70 | 13-AUG-12:52 | 221.91 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 14-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 16-SEP-17:03 | 386.53 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 466.31 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 860.86 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1548.52 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.91 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 158.70 | 1661.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1070.44 | 12-JAN-05:50 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1109.17 | 13-FEB-05:46 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 15-MAR-14:00 | 621.11 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 567.35 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 14-MAY-14:50 | 417.74 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 | 17-JUN-17:20 | 325.03 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 11-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 | 15-JUL-15:00 | 232.78 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.26 | 13-AUG-13:10 | 143.43 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 16-SEP-17:03 | 254.14 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 326.23 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 569.64 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1026.01 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.43 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 117.26 | 1109.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1605.62 | 12-JAN-05:45 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1663.73 | 13-FEB-05:46 |
March | 1306.65 | 01-MAR-10:09 | 1011.14 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | 15-MAR-14:00 | 1030.61 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 850.93 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 | 10-MAY-14:00 | 623.45 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.56 | 17-JUN-17:03 | 489.33 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.47 | 15-JUL-15:00 | 352.25 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.78 | 13-AUG-13:05 | 222.00 | 20-AUG-15:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 | 16-SEP-13:00 | 387.68 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 490.41 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 871.83 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1557.48 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 154.78 | 1663.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1070.36 | 12-JAN-05:50 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1109.15 | 13-FEB-05:46 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 15-MAR-14:00 | 683.02 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 560.87 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 10-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | 10-MAY-14:00 | 427.60 | 29-MAY-14:50 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 17-JUN-17:50 | 326.87 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 16-JUL-10:10 | 237.19 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 13-AUG-13:10 | 177.18 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 16-SEP-13:00 | 252.99 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 311.21 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 567.62 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1026.72 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.18 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 1109.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 857.07 | 12-JAN-05:54 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 896.66 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 14-MAR-14:00 | 517.00 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 497.40 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 14-MAY-15:00 | 271.63 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 17-JUN-17:03 | 262.56 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.71 | 21-JUL-03:00 | 192.15 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 | 13-AUG-13:10 | 123.10 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 16-SEP-17:03 | 233.79 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 296.12 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 508.19 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 859.59 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.10 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 | 896.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 571.37 | 12-JAN-05:52 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 597.77 | 13-FEB-05:59 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 15-MAR-14:00 | 355.25 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 333.53 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 | 14-MAY-15:00 | 204.19 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 17-JUN-17:03 | 182.27 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 17-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 21-JUL-03:00 | 131.87 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 | 13-AUG-13:10 | 81.44 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 16-SEP-17:20 | 154.89 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 205.04 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.75 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 570.84 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.44 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 | 597.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 28825.32 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31014.61 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 795.60 | 15-MAR-12:00 | 29526.61 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20843.41 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.98 | 10-MAY-16:10 | 14655.52 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.87 | 27-JUN-12:00 | 11250.00 | 06-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.12 | 19-JUL-16:10 | 8091.97 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4406.00 | 10-AUG-12:00 | 9037.33 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.92 | 15-SEP-12:00 | 13350.23 | 05-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19636.39 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19818.08 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31519.01 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8091.97 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.87 | 31519.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 571.37 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 597.77 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 15-MAR-12:00 | 359.78 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 329.97 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 10-MAY-14:00 | 206.86 | 29-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 12-JUN-13:00 | 184.26 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 21-JUL-03:00 | 134.97 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 13-AUG-13:10 | 83.15 | 19-AUG-17:40 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 16-SEP-13:00 | 154.43 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 199.06 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.57 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 570.94 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.15 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 597.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1343.20 | 12-JAN-05:56 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1405.14 | 13-FEB-05:59 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 15-MAR-14:00 | 828.24 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 775.90 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.52 | 14-MAY-14:50 | 477.80 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.15 | 17-JUN-17:03 | 418.94 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.38 | 21-JUL-03:00 | 306.00 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 | 13-AUG-12:52 | 191.52 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 14-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 16-SEP-17:03 | 353.95 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 440.34 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 778.40 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1329.37 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.52 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 | 1405.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 895.47 | 12-JAN-05:56 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 936.76 | 13-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 15-MAR-14:00 | 556.87 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 490.21 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 517.77 | 16-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 14-MAY-15:10 | 346.88 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.06 | 17-JUN-17:20 | 280.39 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 11-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 | 15-JUL-15:00 | 203.12 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 13-AUG-13:20 | 123.72 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 600.14 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 16-SEP-17:03 | 232.66 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 305.97 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 513.53 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 879.87 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.72 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 101.15 | 936.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1343.22 | 12-JAN-05:56 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1405.15 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1011.14 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 15-MAR-14:00 | 906.22 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 777.88 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 10-MAY-14:00 | 520.55 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 17-JUN-17:03 | 422.13 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.41 | 15-JUL-15:00 | 307.34 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 13-AUG-13:18 | 190.98 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 | 16-SEP-13:00 | 354.76 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 460.08 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 787.91 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1338.41 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.98 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 | 1405.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 895.47 | 12-JAN-05:56 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 936.77 | 13-FEB-05:56 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 | 15-MAR-14:00 | 580.94 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 600.10 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 512.61 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 10-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 10-MAY-14:00 | 357.04 | 29-MAY-14:50 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 | 12-JUN-13:00 | 282.11 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 16-JUL-11:30 | 206.89 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.25 | 13-AUG-12:52 | 142.99 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 | 16-SEP-13:00 | 232.09 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 293.46 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 512.58 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 881.06 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.99 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 109.25 | 936.77 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1857.31 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1825.19 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 | 15-MAR-14:00 | 1203.29 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1125.49 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 | 14-MAY-15:00 | 572.93 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 | 17-JUN-17:03 | 571.59 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.28 | 21-JUL-03:00 | 418.13 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.77 | 13-AUG-12:52 | 261.55 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.48 | 16-SEP-13:00 | 505.81 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.24 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1120.94 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1859.67 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.77 | 1859.67 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2312.90 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2207.24 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 15-MAR-14:00 | 1497.13 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1372.06 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 | 14-MAY-14:53 | 711.50 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.70 | 17-JUN-17:03 | 730.91 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.41 | 21-JUL-03:00 | 529.74 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.94 | 13-AUG-13:00 | 333.36 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 | 16-SEP-17:03 | 619.98 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 749.20 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1367.97 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2301.95 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.94 | 2312.90 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2284.64 | 12-JAN-05:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2298.53 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 15-MAR-14:00 | 1400.01 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1302.24 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 | 10-MAY-15:00 | 960.34 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.99 | 17-JUN-17:03 | 741.58 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.77 | 21-JUL-02:00 | 525.90 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.60 | 13-AUG-12:52 | 340.08 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.48 | 16-SEP-13:00 | 586.27 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 700.18 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1314.17 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2470.39 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.60 | 2470.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9631.79 | 20-JAN-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9945.16 | 17-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18083.50 | 16-MAR-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29468.46 | 24-APR-05:03 | 2541.06 | 846.94 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40086.86 | 30-MAY-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40171.18 | 27-JUN-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41399.53 | 21-JUL-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41225.16 | 21-AUG-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39871.73 | 25-SEP-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36246.31 | 13-OCT-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17184.02 | 01-NOV-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12592.50 | 01-DEC-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9631.79 | 0.00 | 846.94 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41399.53 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.59 |
February | 394.68 | 22-FEB-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.60 |
March | 5511.77 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
April | 4771.71 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.72 |
May | 7240.93 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 |
June | 10936.67 | 27-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 10289.49 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 | 0.00 |
August | 10215.97 | 09-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 | 0.00 |
September | 8076.89 | 21-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
October | 4492.63 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
November | 1009.72 | 04-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
December | 152.59 | 16-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10936.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 | 440.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2636.05 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.48 |
February | 2298.70 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.51 |
March | 2607.36 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.83 |
April | 2614.52 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.87 |
May | 2548.75 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
June | 4464.08 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.40 | 0.00 |
July | 5319.90 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.00 |
August | 4597.99 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 | 0.00 |
September | 3411.76 | 18-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 |
October | 2733.95 | 24-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 |
November | 2095.61 | 17-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.14 |
December | 2191.81 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2095.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5319.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.40 | 853.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2208.20 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.36 |
February | 2008.91 | 07-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.37 |
March | 3267.89 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.31 |
April | 3106.31 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.77 |
May | 3115.45 | 30-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 |
June | 4815.64 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.64 | 0.00 |
July | 5695.91 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 0.00 |
August | 5070.61 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 0.00 |
September | 5154.05 | 18-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2715.67 | 13-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 |
November | 2536.87 | 03-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.73 |
December | 1813.96 | 15-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1813.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5695.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.64 | 1285.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6420.57 | 12-JAN-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6478.49 | 17-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12419.97 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11770.97 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15145.39 | 30-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29822.13 | 19-JUN-06:03 | 5082.11 | 8592.08 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32594.30 | 31-JUL-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32046.39 | 21-AUG-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30277.60 | 18-SEP-06:01 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13336.44 | 12-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8941.32 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6793.58 | 01-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6420.57 | 3176.32 | 3579.89 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32594.30 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6080.72 | 12-JAN-16:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6234.36 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12478.80 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12420.19 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16485.76 | 31-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26927.82 | 27-JUN-15:05 | 12070.02 | 12887.96 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29228.99 | 21-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30807.72 | 07-AUG-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17419.42 | 18-SEP-13:10 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12958.47 | 12-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7603.83 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6435.78 | 01-DEC-16:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6080.72 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30807.72 | 12070.02 | 12887.96 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1007.02 | 14-JAN-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.63 |
February | 1002.64 | 18-FEB-17:03 | 200.88 | 186.93 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.66 |
March | 3778.25 | 15-MAR-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
April | 2629.34 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.30 |
May | 4836.97 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
June | 8241.71 | 27-JUN-15:05 | 2544.47 | 1295.96 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 | 0.00 |
July | 9540.99 | 16-JUL-16:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 | 0.00 |
August | 11352.29 | 13-AUG-15:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 0.00 |
September | 4801.57 | 15-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 0.00 |
October | 2677.54 | 12-OCT-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 |
November | 1445.13 | 16-NOV-16:50 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.55 |
December | 1143.19 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1002.64 | 200.88 | 186.93 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11352.29 | 2544.47 | 1358.45 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 121.37 | 140.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 987.15 | 14-JAN-17:03 | 169.56 | 191.11 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 |
February | 1342.07 | 28-FEB-10:05 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 |
March | 2902.06 | 15-MAR-14:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
April | 5495.05 | 24-APR-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 |
May | 9154.84 | 21-MAY-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.40 |
June | 10565.95 | 18-JUN-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.62 |
July | 14107.06 | 04-JUL-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.99 |
August | 9683.87 | 13-AUG-15:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 0.00 |
September | 8736.81 | 04-SEP-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.37 |
October | 4252.76 | 11-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
November | 1543.13 | 03-NOV-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.85 |
December | 982.52 | 02-DEC-17:03 | 169.56 | 191.11 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 982.52 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14107.06 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 249.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4429.16 | 12-JAN-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.87 |
February | 6390.96 | 28-FEB-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.21 |
March | 10203.25 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.74 | 0.00 |
April | 8328.15 | 21-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.82 |
May | 8166.69 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
June | 10283.79 | 18-JUN-11:53 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 |
July | 17078.32 | 30-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 |
August | 17494.35 | 13-AUG-15:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 85.56 | 0.00 |
September | 18416.22 | 10-SEP-13:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.89 |
October | 12314.04 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 |
November | 7883.00 | 03-NOV-12:25 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.60 |
December | 3952.73 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3952.73 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18416.22 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 85.56 | 407.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1309.40 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.96 |
February | 1901.87 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.60 |
March | 3773.47 | 15-MAR-14:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 0.00 |
April | 6519.80 | 24-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 |
May | 13004.20 | 27-MAY-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.90 |
June | 15532.20 | 11-JUN-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
July | 16010.69 | 02-JUL-17:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.40 |
August | 15728.77 | 27-AUG-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.97 |
September | 15773.23 | 04-SEP-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.69 |
October | 6159.93 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
November | 1772.64 | 03-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 |
December | 1297.19 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1297.19 | 0.00 | 136.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16010.69 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | 226.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 999.59 | 14-JAN-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 |
February | 988.31 | 18-FEB-17:03 | 200.88 | 157.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 |
March | 1634.69 | 15-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
April | 1510.11 | 21-APR-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.98 |
May | 2925.91 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 4882.88 | 26-JUN-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
July | 5540.06 | 21-JUL-13:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 0.00 |
August | 5519.78 | 14-AUG-12:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 | 0.00 |
September | 4151.54 | 15-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 0.00 |
October | 2334.22 | 05-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.30 |
November | 1435.05 | 16-NOV-16:40 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 |
December | 1233.93 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 988.31 | 200.88 | 157.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5540.06 | 1306.65 | 1358.45 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 75.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 823.84 | 14-JAN-17:03 | 169.56 | 191.11 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 |
February | 1011.11 | 28-FEB-09:55 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 |
March | 1601.34 | 15-MAR-14:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 0.00 |
April | 3994.63 | 24-APR-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 |
May | 5224.84 | 31-MAY-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
June | 8863.19 | 23-JUN-06:02 | 847.82 | 683.72 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 |
July | 12179.66 | 04-JUL-09:21 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 |
August | 6789.85 | 10-AUG-10:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
September | 5433.17 | 21-SEP-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
October | 3825.24 | 11-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 |
November | 1554.21 | 03-NOV-08:35 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.98 |
December | 975.06 | 01-DEC-13:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 823.84 | 169.56 | 159.53 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12179.66 | 1610.86 | 820.45 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 54.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1280.32 | 21-JAN-12:30 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 |
February | 1489.47 | 18-FEB-14:40 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 |
March | 6388.50 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 166.25 | 0.00 |
April | 5150.21 | 23-APR-13:35 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.13 |
May | 5579.64 | 16-MAY-12:10 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.30 |
June | 11076.63 | 27-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.87 | 0.00 |
July | 11321.24 | 21-JUL-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4470.53 | 0.00 |
August | 14063.15 | 13-AUG-15:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 | 0.00 |
September | 13765.91 | 04-SEP-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.15 |
October | 10397.26 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.04 |
November | 5348.24 | 01-NOV-12:08 | 7633.40 | 3887.88 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.45 |
December | 2158.88 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1280.32 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14063.15 | 7633.40 | 3887.88 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4689.87 | 1416.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1060.17 | 12-JAN-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.82 |
February | 1302.93 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.53 |
March | 1887.79 | 15-MAR-14:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
April | 4023.57 | 24-APR-17:30 | 84.78 | 136.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 |
May | 8384.58 | 07-MAY-18:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.43 |
June | 12555.30 | 11-JUN-17:31 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 |
July | 12164.21 | 02-JUL-18:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 |
August | 12200.52 | 13-AUG-15:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 0.00 |
September | 11166.83 | 10-SEP-17:42 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.44 |
October | 5202.31 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
November | 1513.65 | 03-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 |
December | 1091.08 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1060.17 | 0.00 | 91.15 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12555.30 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 119.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1066.83 | 11-JAN-16:50 | 1272.23 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.37 |
February | 1059.62 | 17-FEB-14:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.50 |
March | 3386.34 | 15-MAR-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 0.00 |
April | 2523.14 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 |
May | 4604.55 | 23-MAY-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
June | 6694.59 | 12-JUN-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
July | 7854.17 | 03-JUL-06:02 | 1607.03 | 1295.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 |
August | 7903.40 | 07-AUG-06:03 | 803.52 | 774.33 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 |
September | 4614.84 | 13-SEP-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 |
October | 2810.70 | 12-OCT-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 |
November | 1475.26 | 16-NOV-16:50 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 |
December | 1213.82 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1059.62 | 803.52 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7903.40 | 1607.03 | 1358.45 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 118.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1053.20 | 12-JAN-10:00 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.02 |
February | 1450.63 | 28-FEB-09:50 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 |
March | 2984.23 | 14-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
April | 6383.26 | 24-APR-08:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 |
May | 8028.18 | 29-MAY-09:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.95 |
June | 14089.08 | 11-JUN-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.97 |
July | 15386.73 | 04-JUL-08:41 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 |
August | 8546.73 | 02-AUG-08:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 |
September | 7803.46 | 04-SEP-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 |
October | 4961.82 | 11-OCT-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 |
November | 1953.39 | 03-NOV-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 |
December | 1118.24 | 01-DEC-13:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1053.20 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | |
Maximum of Months | 15386.73 | 1610.86 | 820.45 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5462.99 | 12-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.14 |
February | 6731.00 | 28-FEB-13:40 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.06 |
March | 9797.35 | 15-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
April | 11977.10 | 23-APR-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.26 |
May | 7686.84 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
June | 12801.45 | 18-JUN-15:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
July | 15545.94 | 30-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 |
August | 15774.36 | 13-AUG-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 99.27 | 0.00 |
September | 15932.48 | 04-SEP-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.18 |
October | 12423.43 | 11-OCT-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
November | 8819.17 | 03-NOV-12:25 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 |
December | 4571.73 | 16-DEC-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4571.73 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15932.48 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 99.27 | 349.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1328.99 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.59 |
February | 1981.82 | 28-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.16 |
March | 3600.32 | 21-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 |
April | 6493.83 | 24-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 |
May | 12116.04 | 27-MAY-17:05 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 |
June | 15426.67 | 11-JUN-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.45 |
July | 14827.02 | 02-JUL-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 |
August | 13904.71 | 06-AUG-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 0.00 |
September | 12194.07 | 04-SEP-15:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 |
October | 6126.31 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
November | 2128.33 | 03-NOV-15:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
December | 1309.26 | 04-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1309.26 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15426.67 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 192.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.105811E+12 | 90386.98 | 02-JAN-16:49 | 0.161652E+12 | 254168.70 | 04-JAN-07:19 |
February | 0.947128E+11 | 84656.44 | 06-FEB-08:09 | 0.140213E+12 | 270414.04 | 07-FEB-07:30 |
March | 0.108759E+12 | 104921.71 | 15-MAR-14:09 | 0.697640E+11 | 235131.73 | 06-MAR-07:10 |
April | 0.984816E+11 | 87933.79 | 07-APR-14:09 | 0.178605E+11 | 174142.96 | 17-APR-06:10 |
May | 0.110583E+12 | 112752.58 | 23-MAY-14:30 | 0.160807E+10 | 81356.46 | 01-MAY-06:10 |
June | 0.133202E+12 | 160259.06 | 27-JUN-15:20 | 0.256405E+09 | 17080.81 | 14-JUN-06:10 |
July | 0.151555E+12 | 163974.51 | 05-JUL-15:00 | 16730727.75 | 2449.38 | 13-JUL-06:10 |
August | 0.150737E+12 | 170525.51 | 15-AUG-14:30 | 64603542.87 | 13313.94 | 31-AUG-06:10 |
September | 0.117837E+12 | 138476.17 | 15-SEP-10:00 | 0.470316E+09 | 24649.95 | 30-SEP-06:10 |
October | 0.104755E+12 | 103828.52 | 11-OCT-15:00 | 0.102586E+11 | 143513.26 | 30-OCT-06:10 |
November | 0.102050E+12 | 96694.03 | 16-NOV-16:49 | 0.415576E+11 | 186779.97 | 24-NOV-07:10 |
December | 0.103759E+12 | 90309.08 | 26-DEC-16:00 | 0.137769E+12 | 271921.25 | 11-DEC-07:19 |
Annual Sum or Average | 0.138224E+13 | 0.581491E+12 | ||||
Minimum of Months | 0.947128E+11 | 84656.44 | 16730727.75 | 2449.38 | ||
Maximum of Months | 0.151555E+12 | 170525.51 | 0.161652E+12 | 271921.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.259597E+11 | 0.597089E+10 | 0.605851E+11 | 0.225894E+10 | 0.504241E+10 | 0.766767E+09 | 0.00 | 240131.44 | 0.00 | 0.00 | 0.00 | 0.522657E+10 | 0.00 |
February | 0.230990E+11 | 0.474836E+10 | 0.548702E+11 | 0.204968E+10 | 0.447177E+10 | 0.662830E+09 | 0.00 | 197572.42 | 0.00 | 0.00 | 0.00 | 0.481067E+10 | 0.00 |
March | 0.269867E+11 | 0.441831E+10 | 0.627783E+11 | 0.235656E+10 | 0.489092E+10 | 0.335902E+09 | 0.00 | 0.139523E+10 | 0.00 | 0.00 | 0.00 | 0.559739E+10 | 0.00 |
April | 0.237978E+11 | 0.352418E+10 | 0.586172E+11 | 0.219326E+10 | 0.484987E+10 | 95797213.65 | 0.00 | 0.540476E+09 | 0.00 | 0.00 | 0.00 | 0.486295E+10 | 0.00 |
May | 0.255495E+11 | 0.304929E+10 | 0.616817E+11 | 0.230716E+10 | 0.734771E+10 | 23958168.91 | 0.00 | 0.569482E+10 | 0.00 | 0.00 | 0.00 | 0.492872E+10 | 0.00 |
June | 0.253320E+11 | 0.273786E+10 | 0.604966E+11 | 0.226930E+10 | 0.127173E+11 | 14412822.68 | 0.00 | 0.250281E+11 | 0.00 | 0.00 | 0.00 | 0.460665E+10 | 0.00 |
July | 0.236791E+11 | 0.290320E+10 | 0.597911E+11 | 0.223007E+10 | 0.158950E+11 | 12350893.11 | 0.00 | 0.428817E+11 | 0.00 | 0.00 | 0.00 | 0.416268E+10 | 0.00 |
August | 0.265631E+11 | 0.337878E+10 | 0.627783E+11 | 0.235614E+10 | 0.154542E+11 | 13044690.23 | 0.00 | 0.356935E+11 | 0.00 | 0.00 | 0.00 | 0.449992E+10 | 0.00 |
September | 0.239671E+11 | 0.391430E+10 | 0.585950E+11 | 0.219215E+10 | 0.955115E+10 | 15260470.49 | 0.00 | 0.154663E+11 | 0.00 | 0.00 | 0.00 | 0.413540E+10 | 0.00 |
October | 0.252797E+11 | 0.488938E+10 | 0.605962E+11 | 0.225948E+10 | 0.532691E+10 | 62130992.21 | 0.00 | 0.187082E+10 | 0.00 | 0.00 | 0.00 | 0.447046E+10 | 0.00 |
November | 0.258050E+11 | 0.553154E+10 | 0.591197E+11 | 0.220158E+10 | 0.421746E+10 | 0.195957E+09 | 0.00 | 0.318582E+09 | 0.00 | 0.00 | 0.00 | 0.465982E+10 | 0.00 |
December | 0.253967E+11 | 0.618583E+10 | 0.597800E+11 | 0.223023E+10 | 0.462404E+10 | 0.652878E+09 | 0.00 | 374070.28 | 0.00 | 0.00 | 0.00 | 0.488849E+10 | 0.00 |
Annual Sum or Average | 0.301415E+12 | 0.512519E+11 | 0.719689E+12 | 0.269046E+11 | 0.943887E+11 | 0.285129E+10 | 0.00 | 0.128890E+12 | 0.00 | 0.00 | 0.00 | 0.568497E+11 | 0.00 |
Minimum of Months | 0.230990E+11 | 0.273786E+10 | 0.548702E+11 | 0.204968E+10 | 0.421746E+10 | 12350893.11 | 0.00 | 197572.42 | 0.00 | 0.00 | 0.00 | 0.413540E+10 | 0.00 |
Maximum of Months | 0.269867E+11 | 0.618583E+10 | 0.627783E+11 | 0.235656E+10 | 0.158950E+11 | 0.766767E+09 | 0.00 | 0.428817E+11 | 0.00 | 0.00 | 0.00 | 0.559739E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.161652E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.140213E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.697640E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.178605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.160807E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.256405E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 16730727.75 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 64603542.87 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.470316E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.102586E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.415576E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.137769E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.581491E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 16730727.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.161652E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:20 | 8228.21 | 02-JAN-06:19 | 834.36 | 04-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 32139.06 | 01-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-17:10 | 7402.27 | 06-FEB-07:10 | 892.64 | 07-FEB-07:30 | 0.00 | 01-FEB-00:10 |
March | 29907.05 | 17-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 8663.31 | 15-MAR-14:09 | 819.12 | 07-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 28290.68 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-16:10 | 8581.36 | 21-APR-15:20 | 741.61 | 17-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 26798.99 | 11-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-07:10 | 15069.07 | 31-MAY-15:00 | 335.44 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 26116.88 | 19-JUN-07:10 | 3328.83 | 01-JUN-19:49 | 41699.26 | 01-JUN-07:10 | 1410.29 | 13-JUN-11:09 | 27871.11 | 27-JUN-14:00 | 135.92 | 14-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 26506.32 | 11-JUL-07:30 | 3328.83 | 01-JUL-19:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 05-JUL-07:10 | 29324.48 | 17-JUL-12:09 | 20.43 | 13-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 26735.82 | 24-AUG-07:10 | 5686.19 | 02-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 31-AUG-11:09 | 28009.54 | 09-AUG-15:30 | 75.46 | 31-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 29070.25 | 26-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 28-SEP-11:09 | 20696.96 | 21-SEP-15:00 | 160.49 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32272.70 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 11910.03 | 11-OCT-15:00 | 679.92 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 5306.96 | 24-NOV-07:10 | 761.57 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 7195.78 | 11-DEC-07:10 | 895.67 | 11-DEC-07:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26116.88 | 3328.83 | 41699.26 | 1410.29 | 5306.96 | 20.43 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 29324.48 | 895.67 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 85.89 | 09-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7127.75 | 27-JAN-12:00 | 0.00 |
February | 73.64 | 07-FEB-06:30 | 0.00 | 0.00 | 0.00 | 7140.62 | 13-FEB-12:00 | 0.00 |
March | 23591.20 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 7130.46 | 03-MAR-12:39 | 0.00 |
April | 9991.74 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 6730.19 | 03-APR-11:30 | 0.00 |
May | 27157.89 | 10-MAY-14:39 | 0.00 | 0.00 | 0.00 | 6627.00 | 01-MAY-11:50 | 0.00 |
June | 59036.79 | 27-JUN-15:20 | 0.00 | 0.00 | 0.00 | 6202.61 | 01-JUN-11:30 | 0.00 |
July | 66785.75 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 5789.97 | 03-JUL-11:30 | 0.00 |
August | 71174.16 | 15-AUG-14:30 | 0.00 | 0.00 | 0.00 | 5672.68 | 31-AUG-11:30 | 0.00 |
September | 48625.77 | 15-SEP-10:00 | 0.00 | 0.00 | 0.00 | 5788.18 | 29-SEP-11:00 | 0.00 |
October | 19382.69 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6199.89 | 31-OCT-11:39 | 0.00 |
November | 7391.40 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 6611.11 | 30-NOV-12:50 | 0.00 |
December | 105.66 | 05-DEC-05:30 | 0.00 | 0.00 | 0.00 | 6728.49 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 73.64 | 0.00 | 0.00 | 0.00 | 5672.68 | 0.00 | ||
Maximum of Months | 71174.16 | 0.00 | 0.00 | 0.00 | 7140.62 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 90386.98 | 02-JAN-16:49 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3046.47 | 561.34 | 0.00 | 0.00 | 0.00 |
February | 84656.44 | 06-FEB-08:09 | 30254.36 | 41699.26 | 0.00 | 1410.29 | 6420.99 | 866.81 | 0.00 | 0.00 | 0.00 |
March | 104921.71 | 15-MAR-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 8663.31 | 6.85 | 0.00 | 23591.20 | 0.00 |
April | 87933.79 | 07-APR-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 5630.98 | 6.85 | 0.00 | 9652.00 | 0.00 |
May | 112752.58 | 23-MAY-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14941.42 | 6.85 | 0.00 | 25505.52 | 0.00 |
June | 160259.06 | 27-JUN-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 27866.50 | 6.90 | 0.00 | 59036.79 | 0.00 |
July | 163974.51 | 05-JUL-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 24148.60 | 6.85 | 0.00 | 66785.75 | 0.00 |
August | 170525.51 | 15-AUG-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 27389.31 | 6.85 | 0.00 | 71174.16 | 0.00 |
September | 138476.17 | 15-SEP-10:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 16469.20 | 6.85 | 0.00 | 48625.77 | 0.00 |
October | 103828.52 | 11-OCT-15:00 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 11910.03 | 6.85 | 0.00 | 18245.85 | 0.00 |
November | 96694.03 | 16-NOV-16:49 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3564.47 | 6.85 | 0.00 | 6746.06 | 0.00 |
December | 90309.08 | 26-DEC-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 2894.10 | 648.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 84656.44 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 2894.10 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 170525.51 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 27866.50 | 866.81 | 0.00 | 71174.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 254168.70 | 04-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 270414.04 | 07-FEB-07:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 235131.73 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 174142.96 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 81356.46 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 17080.81 | 14-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2449.38 | 13-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 13313.94 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24649.95 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 143513.26 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 186779.97 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 271921.25 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 2449.38 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 271921.25 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.41 | 2.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.41 | 2.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.41 | 2.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.98 | 3.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 0.50 | 19.58 | 0.50 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.71 | 0.67 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
Annual Sum or Average | 4.83 | 19.14 | 4.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.71 | 3.17 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 19.02 | 5.83 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 5.83 | 19.13 | 5.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.67 | 19.53 | 0.67 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
April | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 5.00 | 19.09 | 4.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 18.67 | 19.10 | 16.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 19.53 | 5.83 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.67 | 17.23 | 23.33 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
February | 35.17 | 17.21 | 18.83 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
March | 8.67 | 17.73 | 4.67 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
April | 0.33 | 18.03 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.41 | 1.17 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 18.69 | 0.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
November | 1.67 | 18.71 | 1.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 30.50 | 17.08 | 16.67 | 17.60 | 0.00 | 17.60 | 0.00 | 17.60 |
Annual Sum or Average | 117.50 | 17.25 | 65.17 | 17.79 | 2.00 | 17.90 | 1.67 | 17.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.67 | 18.71 | 23.33 | 19.00 | 1.50 | 27.41 | 1.17 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 16.17 | 8.67 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
February | 22.50 | 16.32 | 7.67 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
March | 4.67 | 16.30 | 0.67 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
April | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.55 | 0.50 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.73 | 3.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.82 | 7.33 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.61 | 3.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 1.00 | 27.52 |
October | 0.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
November | 1.17 | 16.78 | 0.33 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
December | 19.83 | 16.20 | 6.50 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
Annual Sum or Average | 74.50 | 16.24 | 23.83 | 16.78 | 15.00 | 18.23 | 14.83 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 | 0.00 | 16.65 |
Maximum of Months | 26.00 | 17.15 | 8.67 | 17.36 | 7.50 | 27.82 | 7.33 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 16.64 | 9.67 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
February | 23.17 | 16.83 | 9.67 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
March | 3.00 | 17.04 | 0.67 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
April | 0.17 | 17.03 | 0.00 | 17.03 | 0.33 | 23.89 | 0.33 | 25.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.56 | 2.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.70 | 6.50 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.80 | 4.33 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.86 | 3.33 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 18.46 | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
December | 18.00 | 16.67 | 6.83 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
Annual Sum or Average | 69.50 | 16.74 | 27.17 | 17.36 | 18.33 | 19.01 | 18.00 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.67 | 18.46 | 9.67 | 18.81 | 6.67 | 27.86 | 6.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.67 | 15.86 | 8.67 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
February | 23.50 | 16.33 | 8.83 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
March | 4.00 | 16.55 | 0.67 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
April | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.83 | 1.67 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.07 | 3.50 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.23 | 4.17 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.10 | 2.83 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.78 | 2.00 | 27.78 |
October | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
November | 0.50 | 17.74 | 0.17 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
December | 20.50 | 16.12 | 7.17 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
Annual Sum or Average | 76.50 | 16.13 | 25.50 | 16.59 | 23.83 | 18.77 | 14.17 | 19.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 | 16.23 |
Maximum of Months | 27.67 | 17.74 | 8.83 | 18.15 | 7.83 | 28.23 | 4.17 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.17 | 19.16 | 13.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
February | 13.00 | 19.12 | 11.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 3.00 | 19.26 | 2.50 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.67 | 19.05 | 5.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 37.83 | 19.13 | 32.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.17 | 19.26 | 13.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 17.91 | 3.67 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
February | 4.17 | 18.84 | 2.83 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.45 | 1.17 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.66 | 3.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.55 | 1.00 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.75 | 1.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 13.33 | 18.35 | 8.17 | 18.83 | 6.00 | 20.74 | 6.00 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 18.84 | 3.67 | 19.23 | 3.17 | 27.66 | 3.17 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 110.83 | 17.10 | 109.67 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
February | 96.83 | 17.04 | 95.67 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
March | 58.17 | 18.10 | 58.17 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
April | 31.17 | 18.89 | 31.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
May | 7.00 | 19.49 | 7.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
June | 0.17 | 20.43 | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.54 | 3.17 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.67 | 3.17 | 27.67 |
October | 11.67 | 18.92 | 11.67 | 18.92 | 0.17 | 18.97 | 0.17 | 19.03 |
November | 45.17 | 18.91 | 45.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
December | 88.83 | 17.16 | 88.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
Annual Sum or Average | 449.83 | 17.62 | 446.83 | 17.62 | 8.00 | 17.71 | 8.00 | 17.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 | 17.05 |
Maximum of Months | 110.83 | 20.43 | 109.67 | 20.43 | 3.17 | 27.67 | 3.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 17.64 | 3.33 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
February | 4.67 | 18.81 | 3.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.45 | 0.33 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.75 | 2.33 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.95 | 2.33 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 2.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 1.50 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.84 | 1.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 14.00 | 18.24 | 8.17 | 18.78 | 15.50 | 22.48 | 8.67 | 23.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 18.84 | 3.33 | 19.25 | 4.83 | 27.95 | 2.33 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.83 | 18.38 | 10.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
February | 15.33 | 18.22 | 10.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
March | 2.50 | 19.02 | 2.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.83 | 18.19 | 7.33 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
Annual Sum or Average | 43.50 | 18.31 | 29.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 19.02 | 10.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 16.98 | 2.67 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
February | 7.50 | 17.08 | 2.67 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
March | 0.50 | 17.79 | 0.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.87 | 5.83 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.68 | 1.83 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.68 | 1.83 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.17 | 17.40 | 2.67 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
Annual Sum or Average | 22.00 | 17.15 | 8.17 | 17.82 | 13.67 | 20.92 | 13.67 | 22.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 17.79 | 2.67 | 18.19 | 5.83 | 27.87 | 5.83 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 18.09 | 4.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 8.17 | 17.98 | 4.50 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
March | 0.33 | 18.25 | 0.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.44 | 2.17 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.55 | 6.00 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.33 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.83 | 4.00 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.00 | 18.35 | 3.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Annual Sum or Average | 20.67 | 18.11 | 11.83 | 18.67 | 17.50 | 21.80 | 17.50 | 23.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 18.35 | 4.50 | 18.88 | 6.00 | 27.83 | 6.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 16.92 | 2.50 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
February | 7.67 | 17.14 | 2.83 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 0.33 | 18.15 | 0.17 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.80 | 1.50 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.18 | 3.00 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.16 | 3.50 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.96 | 2.67 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.81 | 2.17 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.33 | 17.37 | 2.67 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
Annual Sum or Average | 22.00 | 17.15 | 8.17 | 17.83 | 21.67 | 22.10 | 13.00 | 23.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.67 | 18.15 | 2.83 | 18.58 | 6.83 | 28.18 | 3.50 | 28.20 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.47 | 60.83 | 22.22 | 60.83 | 22.03 |
February | 454.00 | 22.78 | 8.00 | 22.75 | 8.00 | 22.72 |
March | 430.67 | 23.65 | 18.83 | 23.68 | 0.00 | 23.68 |
April | 249.00 | 23.92 | 31.50 | 24.11 | 0.00 | 24.11 |
May | 60.50 | 24.01 | 177.50 | 24.79 | 0.00 | 24.79 |
June | 0.00 | 0.00 | 368.00 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 487.50 | 24.52 | 0.00 | 24.52 |
August | 0.00 | 0.00 | 489.50 | 24.46 | 0.00 | 24.46 |
September | 0.00 | 0.00 | 371.67 | 24.60 | 0.00 | 24.60 |
October | 110.00 | 23.96 | 121.67 | 24.49 | 0.00 | 24.49 |
November | 356.83 | 23.85 | 13.17 | 23.90 | 0.00 | 23.90 |
December | 489.50 | 23.07 | 3.50 | 23.05 | 3.50 | 23.04 |
Annual Sum or Average | 2652.50 | 23.24 | 2151.67 | 23.79 | 72.33 | 23.74 |
Minimum of Months | 0.00 | 0.00 | 3.50 | 22.22 | 0.00 | 22.03 |
Maximum of Months | 502.00 | 24.01 | 489.50 | 24.79 | 60.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.97 | 321.00 | 20.82 | 321.00 | 20.75 |
February | 454.00 | 21.15 | 247.17 | 20.99 | 247.17 | 20.92 |
March | 478.33 | 22.16 | 65.00 | 22.05 | 57.00 | 21.94 |
April | 439.17 | 23.02 | 2.00 | 23.01 | 2.00 | 23.00 |
May | 232.83 | 23.58 | 76.67 | 23.81 | 0.00 | 23.81 |
June | 34.33 | 23.78 | 282.67 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 473.50 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 426.83 | 24.31 | 0.00 | 24.31 |
September | 54.83 | 23.42 | 228.00 | 24.20 | 0.00 | 24.20 |
October | 376.17 | 23.09 | 12.17 | 23.13 | 0.00 | 23.13 |
November | 488.67 | 22.41 | 7.83 | 22.38 | 7.83 | 22.36 |
December | 497.00 | 21.22 | 227.50 | 21.06 | 227.50 | 20.98 |
Annual Sum or Average | 3557.33 | 22.10 | 2370.33 | 22.46 | 862.50 | 22.23 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 20.82 | 0.00 | 20.75 |
Maximum of Months | 502.00 | 23.78 | 473.50 | 24.31 | 321.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 434.67 | 20.36 | 434.67 | 20.33 |
February | 454.00 | 20.58 | 360.00 | 20.47 | 360.00 | 20.43 |
March | 485.17 | 21.47 | 183.00 | 21.25 | 177.33 | 21.11 |
April | 467.33 | 22.43 | 34.17 | 22.30 | 34.17 | 22.17 |
May | 295.50 | 23.31 | 52.67 | 23.45 | 0.00 | 23.45 |
June | 71.17 | 23.52 | 261.50 | 24.08 | 0.00 | 24.08 |
July | 4.67 | 23.54 | 452.50 | 24.29 | 0.00 | 24.29 |
August | 19.17 | 23.41 | 393.00 | 24.22 | 0.00 | 24.22 |
September | 155.67 | 23.19 | 163.83 | 23.75 | 0.00 | 23.75 |
October | 447.33 | 22.33 | 34.67 | 22.24 | 29.67 | 22.14 |
November | 489.00 | 21.45 | 124.17 | 21.25 | 124.17 | 21.11 |
December | 497.00 | 20.55 | 381.33 | 20.45 | 381.33 | 20.41 |
Annual Sum or Average | 3888.00 | 21.59 | 2875.50 | 21.83 | 1541.33 | 21.56 |
Minimum of Months | 4.67 | 20.43 | 34.17 | 20.36 | 0.00 | 20.33 |
Maximum of Months | 502.00 | 23.54 | 452.50 | 24.29 | 434.67 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 493.83 | 19.83 | 493.83 | 19.83 |
February | 454.00 | 19.90 | 448.33 | 19.89 | 448.33 | 19.89 |
March | 494.00 | 20.71 | 322.50 | 20.54 | 312.00 | 20.43 |
April | 472.50 | 21.61 | 117.00 | 21.32 | 116.83 | 21.12 |
May | 328.17 | 22.80 | 62.50 | 22.96 | 8.50 | 22.91 |
June | 94.50 | 23.52 | 271.67 | 24.09 | 11.00 | 24.13 |
July | 37.67 | 24.90 | 450.83 | 24.43 | 26.67 | 24.49 |
August | 73.00 | 23.52 | 374.50 | 24.15 | 11.50 | 24.19 |
September | 235.50 | 22.84 | 145.17 | 23.37 | 10.83 | 23.43 |
October | 476.00 | 21.49 | 117.50 | 21.23 | 113.67 | 21.04 |
November | 489.00 | 20.58 | 297.83 | 20.41 | 297.83 | 20.33 |
December | 497.00 | 19.88 | 478.67 | 19.86 | 478.67 | 19.85 |
Annual Sum or Average | 4153.33 | 21.03 | 3580.33 | 21.27 | 2329.67 | 21.00 |
Minimum of Months | 37.67 | 19.84 | 62.50 | 19.83 | 8.50 | 19.83 |
Maximum of Months | 502.00 | 24.90 | 493.83 | 24.43 | 493.83 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.91 | 494.17 | 19.90 | 494.17 | 19.90 |
February | 454.00 | 19.98 | 430.00 | 19.95 | 430.00 | 19.94 |
March | 488.17 | 20.88 | 271.83 | 20.70 | 253.33 | 20.56 |
April | 391.00 | 21.55 | 100.50 | 21.42 | 81.17 | 21.21 |
May | 247.17 | 22.60 | 145.67 | 23.24 | 7.83 | 23.23 |
June | 91.67 | 23.83 | 341.83 | 24.25 | 21.67 | 24.36 |
July | 58.67 | 25.91 | 464.00 | 24.62 | 49.67 | 24.78 |
August | 76.00 | 23.79 | 404.17 | 24.24 | 20.00 | 24.32 |
September | 197.00 | 22.72 | 234.33 | 23.59 | 12.83 | 23.65 |
October | 441.50 | 21.56 | 99.50 | 21.38 | 85.17 | 21.19 |
November | 489.00 | 20.68 | 282.00 | 20.49 | 282.00 | 20.41 |
December | 497.00 | 19.94 | 479.00 | 19.92 | 479.00 | 19.91 |
Annual Sum or Average | 3933.17 | 21.05 | 3747.00 | 21.47 | 2216.83 | 21.20 |
Minimum of Months | 58.67 | 19.91 | 99.50 | 19.90 | 7.83 | 19.90 |
Maximum of Months | 502.00 | 25.91 | 494.17 | 24.62 | 494.17 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.67 | 20.25 | 431.00 | 20.09 | 431.00 | 20.04 |
February | 448.50 | 20.28 | 368.83 | 20.09 | 368.83 | 20.01 |
March | 450.50 | 21.27 | 222.00 | 21.01 | 203.50 | 20.82 |
April | 376.17 | 21.60 | 125.50 | 21.56 | 92.50 | 21.35 |
May | 273.50 | 22.62 | 122.50 | 23.11 | 12.67 | 23.08 |
June | 120.67 | 23.50 | 299.67 | 24.09 | 19.83 | 24.19 |
July | 74.17 | 25.13 | 441.67 | 24.54 | 49.33 | 24.69 |
August | 91.00 | 23.90 | 393.33 | 24.26 | 25.00 | 24.36 |
September | 184.33 | 23.06 | 251.00 | 23.85 | 21.50 | 23.97 |
October | 374.67 | 21.73 | 137.00 | 21.86 | 69.50 | 21.64 |
November | 461.83 | 21.04 | 219.00 | 20.78 | 215.17 | 20.63 |
December | 494.67 | 20.23 | 429.33 | 20.12 | 429.33 | 20.07 |
Annual Sum or Average | 3848.67 | 21.33 | 3440.83 | 21.68 | 1938.17 | 21.41 |
Minimum of Months | 74.17 | 20.23 | 122.50 | 20.09 | 12.67 | 20.01 |
Maximum of Months | 498.67 | 25.13 | 441.67 | 24.54 | 431.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.91 | 488.83 | 19.89 | 488.83 | 19.89 |
February | 454.00 | 20.00 | 425.67 | 19.95 | 425.67 | 19.94 |
March | 487.50 | 20.91 | 276.50 | 20.70 | 267.17 | 20.56 |
April | 412.67 | 21.38 | 143.00 | 21.36 | 107.17 | 21.17 |
May | 309.33 | 22.48 | 128.50 | 22.99 | 17.33 | 23.00 |
June | 128.83 | 23.39 | 312.33 | 24.07 | 21.17 | 24.19 |
July | 72.17 | 24.68 | 434.50 | 24.46 | 40.17 | 24.58 |
August | 105.50 | 23.46 | 378.83 | 24.14 | 21.67 | 24.23 |
September | 252.17 | 22.67 | 183.67 | 23.39 | 18.83 | 23.51 |
October | 456.83 | 21.37 | 124.83 | 21.24 | 102.17 | 21.06 |
November | 489.00 | 20.63 | 283.17 | 20.45 | 283.17 | 20.36 |
December | 497.00 | 19.93 | 473.17 | 19.90 | 473.17 | 19.89 |
Annual Sum or Average | 4167.00 | 21.07 | 3653.00 | 21.40 | 2266.50 | 21.15 |
Minimum of Months | 72.17 | 19.91 | 124.83 | 19.89 | 17.33 | 19.89 |
Maximum of Months | 502.00 | 24.68 | 488.83 | 24.46 | 488.83 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 493.33 | 20.13 | 493.33 | 20.13 |
February | 454.00 | 20.23 | 453.33 | 20.23 | 453.33 | 20.23 |
March | 512.00 | 20.86 | 328.33 | 20.70 | 328.33 | 20.63 |
April | 485.00 | 21.47 | 103.67 | 21.29 | 103.67 | 21.17 |
May | 430.67 | 22.74 | 19.33 | 22.79 | 2.00 | 22.78 |
June | 123.00 | 23.59 | 227.67 | 23.98 | 7.17 | 24.00 |
July | 14.17 | 24.92 | 453.00 | 24.32 | 12.00 | 24.34 |
August | 30.33 | 23.61 | 389.50 | 24.20 | 3.00 | 24.21 |
September | 183.33 | 23.33 | 154.17 | 23.75 | 7.00 | 23.80 |
October | 458.33 | 22.27 | 12.83 | 22.25 | 10.50 | 22.21 |
November | 489.00 | 21.21 | 146.50 | 21.06 | 146.50 | 20.96 |
December | 497.00 | 20.35 | 457.50 | 20.32 | 457.50 | 20.31 |
Annual Sum or Average | 4178.83 | 21.33 | 3239.17 | 21.54 | 2024.33 | 21.29 |
Minimum of Months | 14.17 | 20.14 | 12.83 | 20.13 | 2.00 | 20.13 |
Maximum of Months | 512.00 | 24.92 | 493.33 | 24.32 | 493.33 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.22 | 492.67 | 20.22 | 492.67 | 20.21 |
February | 454.00 | 20.33 | 437.33 | 20.31 | 437.33 | 20.30 |
March | 502.83 | 21.09 | 241.50 | 20.89 | 241.50 | 20.79 |
April | 435.50 | 21.98 | 60.67 | 21.90 | 48.67 | 21.75 |
May | 288.33 | 22.88 | 93.83 | 23.33 | 0.00 | 23.33 |
June | 62.00 | 23.81 | 337.00 | 24.30 | 9.17 | 24.34 |
July | 28.33 | 26.43 | 485.67 | 24.57 | 28.33 | 24.67 |
August | 26.17 | 24.50 | 443.50 | 24.37 | 9.33 | 24.41 |
September | 108.50 | 23.35 | 295.67 | 24.11 | 8.33 | 24.16 |
October | 393.50 | 22.46 | 41.67 | 22.60 | 5.67 | 22.57 |
November | 489.00 | 21.35 | 120.33 | 21.19 | 120.33 | 21.08 |
December | 497.00 | 20.40 | 458.50 | 20.37 | 458.50 | 20.36 |
Annual Sum or Average | 3787.17 | 21.38 | 3508.33 | 21.83 | 1859.83 | 21.56 |
Minimum of Months | 26.17 | 20.22 | 41.67 | 20.22 | 0.00 | 20.21 |
Maximum of Months | 502.83 | 26.43 | 492.67 | 24.57 | 492.67 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 19.59 | 456.67 | 19.50 | 456.67 | 19.47 |
February | 454.00 | 19.67 | 412.17 | 19.59 | 412.17 | 19.56 |
March | 494.17 | 20.88 | 213.17 | 20.62 | 204.00 | 20.44 |
April | 441.83 | 21.45 | 85.83 | 21.31 | 74.00 | 21.12 |
May | 371.83 | 22.39 | 56.17 | 22.62 | 9.33 | 22.55 |
June | 161.33 | 23.07 | 245.67 | 23.81 | 29.17 | 23.83 |
July | 80.33 | 24.20 | 449.67 | 24.39 | 59.83 | 24.44 |
August | 86.83 | 23.67 | 423.00 | 24.27 | 43.17 | 24.32 |
September | 118.33 | 23.21 | 313.83 | 24.13 | 26.33 | 24.23 |
October | 349.17 | 22.17 | 98.00 | 22.55 | 13.17 | 22.45 |
November | 459.67 | 21.30 | 122.67 | 21.05 | 119.17 | 20.87 |
December | 494.67 | 19.96 | 424.17 | 19.83 | 424.17 | 19.78 |
Annual Sum or Average | 4012.67 | 21.12 | 3301.00 | 21.48 | 1871.17 | 21.19 |
Minimum of Months | 80.33 | 19.59 | 56.17 | 19.50 | 9.33 | 19.47 |
Maximum of Months | 500.50 | 24.20 | 456.67 | 24.39 | 456.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.19 | 487.67 | 20.18 | 487.67 | 20.17 |
February | 454.00 | 20.32 | 432.67 | 20.29 | 432.67 | 20.28 |
March | 509.17 | 21.13 | 252.83 | 20.92 | 252.67 | 20.82 |
April | 442.50 | 21.75 | 71.17 | 21.64 | 62.67 | 21.49 |
May | 315.17 | 22.74 | 84.17 | 23.15 | 0.17 | 23.15 |
June | 78.17 | 23.81 | 328.83 | 24.27 | 14.33 | 24.33 |
July | 29.33 | 25.75 | 467.83 | 24.53 | 25.17 | 24.61 |
August | 34.33 | 24.69 | 446.33 | 24.40 | 15.17 | 24.47 |
September | 128.50 | 23.38 | 251.67 | 24.05 | 10.83 | 24.13 |
October | 426.67 | 22.30 | 36.17 | 22.39 | 7.50 | 22.37 |
November | 489.00 | 21.27 | 133.17 | 21.12 | 133.17 | 21.02 |
December | 497.00 | 20.38 | 455.67 | 20.35 | 455.67 | 20.34 |
Annual Sum or Average | 3905.83 | 21.36 | 3448.17 | 21.77 | 1897.67 | 21.51 |
Minimum of Months | 29.33 | 20.19 | 36.17 | 20.18 | 0.17 | 20.17 |
Maximum of Months | 509.17 | 25.75 | 487.67 | 24.53 | 487.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.09 | 481.67 | 20.07 | 481.67 | 20.06 |
February | 454.00 | 20.20 | 428.83 | 20.17 | 428.83 | 20.17 |
March | 490.67 | 21.05 | 271.33 | 20.87 | 260.17 | 20.75 |
April | 471.50 | 22.09 | 54.83 | 21.90 | 54.83 | 21.74 |
May | 289.83 | 23.18 | 64.50 | 23.39 | 0.00 | 23.39 |
June | 63.00 | 23.87 | 283.50 | 24.23 | 6.33 | 24.25 |
July | 20.83 | 25.41 | 466.67 | 24.45 | 20.00 | 24.49 |
August | 29.67 | 23.70 | 410.33 | 24.25 | 5.50 | 24.26 |
September | 172.17 | 23.27 | 168.33 | 23.76 | 9.00 | 23.83 |
October | 450.33 | 22.07 | 44.00 | 21.97 | 37.83 | 21.86 |
November | 489.00 | 21.08 | 187.00 | 20.89 | 187.00 | 20.78 |
December | 497.00 | 20.20 | 443.83 | 20.15 | 443.83 | 20.14 |
Annual Sum or Average | 3930.00 | 21.31 | 3304.83 | 21.60 | 1935.00 | 21.33 |
Minimum of Months | 20.83 | 20.09 | 44.00 | 20.07 | 0.00 | 20.06 |
Maximum of Months | 502.00 | 25.41 | 481.67 | 24.45 | 481.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.02 | 417.33 | 20.01 | 417.33 | 20.01 |
February | 385.00 | 20.16 | 355.33 | 20.12 | 355.33 | 20.10 |
March | 414.00 | 21.14 | 195.00 | 20.97 | 182.67 | 20.83 |
April | 336.17 | 21.86 | 63.67 | 21.86 | 41.67 | 21.70 |
May | 221.00 | 22.94 | 108.50 | 23.52 | 4.17 | 23.56 |
June | 70.50 | 24.03 | 282.17 | 24.38 | 15.17 | 24.47 |
July | 43.83 | 26.35 | 402.83 | 24.73 | 42.33 | 24.88 |
August | 46.17 | 24.16 | 343.67 | 24.38 | 14.67 | 24.45 |
September | 157.50 | 23.19 | 191.83 | 23.91 | 15.17 | 24.02 |
October | 365.33 | 21.94 | 48.33 | 21.95 | 28.67 | 21.85 |
November | 416.83 | 21.03 | 155.00 | 20.85 | 155.00 | 20.74 |
December | 422.00 | 20.12 | 395.00 | 20.09 | 395.00 | 20.08 |
Annual Sum or Average | 3305.33 | 21.29 | 2958.67 | 21.71 | 1667.17 | 21.45 |
Minimum of Months | 43.83 | 20.02 | 48.33 | 20.01 | 4.17 | 20.01 |
Maximum of Months | 427.00 | 26.35 | 417.33 | 24.73 | 417.33 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 20.56 | 386.50 | 20.39 | 383.50 | 20.31 |
February | 445.67 | 20.66 | 330.67 | 20.44 | 330.67 | 20.36 |
March | 432.67 | 21.65 | 165.50 | 21.47 | 140.83 | 21.27 |
April | 361.83 | 22.11 | 72.67 | 22.17 | 39.50 | 22.01 |
May | 235.83 | 23.03 | 127.83 | 23.55 | 2.50 | 23.57 |
June | 80.83 | 23.83 | 318.67 | 24.24 | 13.00 | 24.30 |
July | 53.50 | 25.81 | 461.33 | 24.61 | 45.00 | 24.74 |
August | 49.17 | 24.75 | 425.83 | 24.42 | 22.50 | 24.51 |
September | 132.50 | 23.65 | 287.67 | 24.20 | 21.33 | 24.33 |
October | 329.00 | 22.29 | 110.50 | 22.63 | 22.17 | 22.53 |
November | 437.00 | 21.47 | 127.50 | 21.28 | 120.00 | 21.13 |
December | 490.33 | 20.60 | 367.50 | 20.45 | 366.00 | 20.39 |
Annual Sum or Average | 3542.50 | 21.63 | 3182.17 | 22.08 | 1507.00 | 21.82 |
Minimum of Months | 49.17 | 20.56 | 72.67 | 20.39 | 2.50 | 20.31 |
Maximum of Months | 494.17 | 25.81 | 461.33 | 24.61 | 383.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 476.83 | 20.11 | 476.83 | 20.10 |
February | 454.00 | 20.30 | 406.83 | 20.23 | 406.83 | 20.21 |
March | 479.33 | 21.21 | 220.50 | 21.03 | 208.00 | 20.90 |
April | 404.50 | 21.82 | 83.67 | 21.88 | 47.50 | 21.73 |
May | 271.00 | 22.84 | 137.00 | 23.42 | 5.50 | 23.46 |
June | 94.33 | 23.86 | 333.33 | 24.26 | 20.50 | 24.36 |
July | 48.17 | 25.41 | 460.50 | 24.53 | 35.33 | 24.64 |
August | 65.67 | 24.05 | 415.67 | 24.31 | 19.33 | 24.39 |
September | 195.50 | 23.15 | 218.67 | 23.81 | 17.83 | 23.93 |
October | 438.50 | 21.90 | 67.33 | 21.92 | 37.50 | 21.82 |
November | 486.00 | 21.05 | 178.83 | 20.87 | 178.83 | 20.77 |
December | 497.00 | 20.24 | 448.17 | 20.20 | 448.17 | 20.18 |
Annual Sum or Average | 3936.00 | 21.34 | 3447.33 | 21.74 | 1902.17 | 21.49 |
Minimum of Months | 48.17 | 20.14 | 67.33 | 20.11 | 5.50 | 20.10 |
Maximum of Months | 502.00 | 25.41 | 476.83 | 24.53 | 476.83 | 24.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46624 | 19.00797 | -0.2593 | 7.94889 |
February | 454.00000 | 22.77655 | 18.42941 | -0.1817 | 6.22883 |
March | 514.00000 | 23.73932 | 24.83101 | 0.12483 | 5.96129 |
April | 485.00000 | 24.17043 | 28.21463 | 0.27880 | 6.91048 |
May | 508.00000 | 24.43269 | 32.19009 | -0.4538 | 10.00069 |
June | 496.00000 | 24.40921 | 43.28970 | -0.3295 | 7.85759 |
July | 497.00000 | 24.51019 | 51.32816 | -0.2280 | 6.73598 |
August | 514.00000 | 24.44182 | 47.99837 | -0.2719 | 7.13976 |
September | 485.00000 | 24.46348 | 43.46384 | -0.3242 | 7.93076 |
October | 502.00000 | 24.34681 | 33.30836 | 0.37473 | 8.20187 |
November | 489.00000 | 24.00082 | 28.02333 | 0.21670 | 6.26942 |
December | 497.00000 | 23.07915 | 21.77327 | -0.0818 | 5.75603 |
Annual Sum or Average | 5943.00000 | 23.91054 | 32.75908 | -0.0949 | 7.25551 |
Minimum of Months | 454.00000 | 22.46624 | 18.42941 | -0.4538 | 5.75603 |
Maximum of Months | 514.00000 | 24.51019 | 51.32816 | 0.37473 | 10.00069 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.96690 | 20.50134 | -0.6019 | 13.72617 |
February | 454.00000 | 21.14977 | 19.82187 | -0.5554 | 12.19838 |
March | 514.00000 | 22.29110 | 27.09065 | -0.2000 | 7.43676 |
April | 485.00000 | 23.12923 | 30.78443 | 0.04072 | 5.91748 |
May | 508.00000 | 23.93461 | 33.92062 | -0.6286 | 13.98425 |
June | 496.00000 | 24.17378 | 44.25612 | -0.4293 | 9.28856 |
July | 497.00000 | 24.29587 | 52.24201 | -0.3190 | 7.45097 |
August | 514.00000 | 24.25351 | 48.87108 | -0.3614 | 8.03572 |
September | 485.00000 | 24.11342 | 44.78713 | -0.4703 | 10.26755 |
October | 502.00000 | 23.33658 | 36.35581 | 0.13118 | 6.12952 |
November | 489.00000 | 22.41048 | 31.41317 | -0.1489 | 6.32883 |
December | 497.00000 | 21.21884 | 23.74863 | -0.5094 | 11.22171 |
Annual Sum or Average | 5943.00000 | 22.95263 | 34.58675 | -0.3369 | 9.32096 |
Minimum of Months | 454.00000 | 20.96690 | 19.82187 | -0.6286 | 5.91748 |
Maximum of Months | 514.00000 | 24.29587 | 52.24201 | 0.13118 | 13.98425 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42976 | 20.63303 | -0.7633 | 18.94965 |
February | 454.00000 | 20.57689 | 20.28486 | -0.7224 | 17.55858 |
March | 514.00000 | 21.61399 | 27.79963 | -0.3767 | 10.44294 |
April | 485.00000 | 22.49293 | 31.82107 | -0.1139 | 6.82206 |
May | 508.00000 | 23.65903 | 34.46118 | -0.7234 | 17.23994 |
June | 496.00000 | 24.06854 | 44.59107 | -0.4600 | 10.07490 |
July | 497.00000 | 24.25922 | 52.28695 | -0.3247 | 7.56360 |
August | 514.00000 | 24.17196 | 48.99000 | -0.3895 | 8.53523 |
September | 485.00000 | 23.82862 | 45.50895 | -0.5743 | 13.09697 |
October | 502.00000 | 22.51231 | 38.06212 | -0.0703 | 6.77172 |
November | 489.00000 | 21.45417 | 32.88500 | -0.3908 | 9.39890 |
December | 497.00000 | 20.55224 | 24.50752 | -0.7019 | 16.83412 |
Annual Sum or Average | 5943.00000 | 22.48324 | 35.25497 | -0.4663 | 11.90914 |
Minimum of Months | 454.00000 | 20.42976 | 20.28486 | -0.7633 | 6.77172 |
Maximum of Months | 514.00000 | 24.25922 | 52.28695 | -0.0703 | 18.94965 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84310 | 21.72169 | -0.9782 | 27.45280 |
February | 454.00000 | 19.90000 | 21.63561 | -0.9466 | 26.24892 |
March | 514.00000 | 20.83346 | 29.71343 | -0.5952 | 16.13672 |
April | 485.00000 | 21.67031 | 33.64120 | -0.3148 | 9.65086 |
May | 508.00000 | 23.27225 | 36.46135 | -0.8444 | 22.60758 |
June | 496.00000 | 24.03979 | 45.39023 | -0.4448 | 10.61704 |
July | 497.00000 | 24.33674 | 53.14353 | -0.2590 | 7.34538 |
August | 514.00000 | 24.10252 | 49.92707 | -0.3890 | 9.30111 |
September | 485.00000 | 23.45748 | 47.52093 | -0.6957 | 17.90811 |
October | 502.00000 | 21.61909 | 40.39846 | -0.2888 | 9.43682 |
November | 489.00000 | 20.58181 | 34.44200 | -0.6300 | 15.08398 |
December | 497.00000 | 19.88307 | 25.71852 | -0.9287 | 25.64363 |
Annual Sum or Average | 5943.00000 | 21.97888 | 36.74545 | -0.6074 | 16.38887 |
Minimum of Months | 454.00000 | 19.84310 | 21.63561 | -0.9782 | 7.34538 |
Maximum of Months | 514.00000 | 24.33674 | 53.14353 | -0.2590 | 27.45280 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91338 | 21.12875 | -0.9498 | 26.24764 |
February | 454.00000 | 19.98265 | 21.08373 | -0.9075 | 24.80476 |
March | 514.00000 | 21.02947 | 28.92853 | -0.5151 | 14.11681 |
April | 485.00000 | 22.06592 | 32.29307 | -0.1826 | 9.22758 |
May | 508.00000 | 23.43828 | 35.36792 | -0.7120 | 19.49791 |
June | 496.00000 | 24.09931 | 44.81931 | -0.3384 | 9.69797 |
July | 497.00000 | 24.40262 | 52.51805 | -0.1487 | 7.24842 |
August | 514.00000 | 24.11625 | 49.48014 | -0.2999 | 8.73426 |
September | 485.00000 | 23.56732 | 46.60717 | -0.5852 | 15.82965 |
October | 502.00000 | 21.85222 | 39.32489 | -0.2091 | 8.84299 |
November | 489.00000 | 20.67540 | 33.71220 | -0.5980 | 14.28877 |
December | 497.00000 | 19.93904 | 25.18004 | -0.9120 | 24.84386 |
Annual Sum or Average | 5943.00000 | 22.10726 | 35.97289 | -0.5274 | 15.21576 |
Minimum of Months | 454.00000 | 19.91338 | 21.08373 | -0.9498 | 7.24842 |
Maximum of Months | 514.00000 | 24.40262 | 52.51805 | -0.1487 | 26.24764 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27582 | 20.76557 | -0.8304 | 23.01699 |
February | 454.00000 | 20.32329 | 20.67056 | -0.7974 | 22.34292 |
March | 514.00000 | 21.60677 | 28.02076 | -0.3650 | 12.46908 |
April | 485.00000 | 22.20352 | 31.82184 | -0.1590 | 9.46560 |
May | 508.00000 | 23.35973 | 35.51326 | -0.7677 | 21.41541 |
June | 496.00000 | 23.98075 | 45.20133 | -0.4265 | 11.31542 |
July | 497.00000 | 24.33558 | 52.84279 | -0.2157 | 7.82993 |
August | 514.00000 | 24.13454 | 49.34819 | -0.3116 | 9.06855 |
September | 485.00000 | 23.74606 | 45.87633 | -0.5116 | 14.70394 |
October | 502.00000 | 22.36839 | 37.83024 | -0.0726 | 9.13872 |
November | 489.00000 | 21.20314 | 32.68945 | -0.4573 | 12.60983 |
December | 497.00000 | 20.25042 | 24.79804 | -0.8094 | 21.73134 |
Annual Sum or Average | 5943.00000 | 22.33207 | 35.55174 | -0.4750 | 14.54283 |
Minimum of Months | 454.00000 | 20.25042 | 20.67056 | -0.8304 | 7.82993 |
Maximum of Months | 514.00000 | 24.33558 | 52.84279 | -0.0726 | 23.01699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90834 | 20.94498 | -0.9600 | 26.73035 |
February | 454.00000 | 20.00451 | 20.84638 | -0.9124 | 25.16853 |
March | 514.00000 | 21.06622 | 28.72956 | -0.5155 | 14.43347 |
April | 485.00000 | 21.82264 | 32.49727 | -0.2454 | 10.01288 |
May | 508.00000 | 23.15583 | 36.02341 | -0.8035 | 23.47556 |
June | 496.00000 | 23.93406 | 45.36216 | -0.3880 | 11.52895 |
July | 497.00000 | 24.26535 | 53.10134 | -0.2038 | 8.09027 |
August | 514.00000 | 24.01344 | 49.92234 | -0.3368 | 9.89425 |
September | 485.00000 | 23.33602 | 47.34979 | -0.6653 | 18.77413 |
October | 502.00000 | 21.61094 | 39.60115 | -0.2661 | 9.47499 |
November | 489.00000 | 20.63121 | 33.60038 | -0.6110 | 14.71945 |
December | 497.00000 | 19.92809 | 25.01320 | -0.9162 | 25.07804 |
Annual Sum or Average | 5943.00000 | 21.98971 | 36.18784 | -0.5663 | 16.38805 |
Minimum of Months | 454.00000 | 19.90834 | 20.84638 | -0.9600 | 8.09027 |
Maximum of Months | 514.00000 | 24.26535 | 53.10134 | -0.2038 | 26.73035 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13844 | 21.51143 | -0.8902 | 23.19127 |
February | 454.00000 | 20.23176 | 21.53443 | -0.8568 | 21.75140 |
March | 514.00000 | 20.87188 | 30.03778 | -0.5905 | 14.42621 |
April | 485.00000 | 21.47370 | 34.23082 | -0.3692 | 8.97134 |
May | 508.00000 | 22.94182 | 37.69894 | -0.9888 | 27.30357 |
June | 496.00000 | 23.98513 | 45.95250 | -0.5067 | 11.15836 |
July | 497.00000 | 24.27165 | 53.44269 | -0.3191 | 7.52960 |
August | 514.00000 | 24.15426 | 49.98158 | -0.3916 | 8.66716 |
September | 485.00000 | 23.78462 | 46.92883 | -0.5895 | 13.53982 |
October | 502.00000 | 22.42247 | 38.71779 | -0.0843 | 6.50258 |
November | 489.00000 | 21.20808 | 33.54898 | -0.4388 | 9.85875 |
December | 497.00000 | 20.34943 | 25.49788 | -0.7786 | 18.98811 |
Annual Sum or Average | 5943.00000 | 22.16776 | 36.69636 | -0.5657 | 14.29822 |
Minimum of Months | 454.00000 | 20.13844 | 21.51143 | -0.9888 | 6.50258 |
Maximum of Months | 514.00000 | 24.27165 | 53.44269 | -0.0843 | 27.30357 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22430 | 21.34950 | -0.8582 | 21.89637 |
February | 454.00000 | 20.32585 | 21.40385 | -0.8154 | 20.20334 |
March | 514.00000 | 21.15271 | 29.53481 | -0.4870 | 12.03333 |
April | 485.00000 | 22.23262 | 32.69598 | -0.1579 | 7.78703 |
May | 508.00000 | 23.50564 | 35.85461 | -0.7411 | 19.25906 |
June | 496.00000 | 24.19632 | 44.77942 | -0.3523 | 8.89813 |
July | 497.00000 | 24.45244 | 52.40970 | -0.1702 | 6.67479 |
August | 514.00000 | 24.27744 | 49.20037 | -0.2659 | 7.47588 |
September | 485.00000 | 24.03599 | 45.70284 | -0.4354 | 10.69309 |
October | 502.00000 | 22.82618 | 37.59799 | 0.03215 | 6.64763 |
November | 489.00000 | 21.35146 | 33.18808 | -0.3930 | 9.35360 |
December | 497.00000 | 20.39794 | 25.37423 | -0.7633 | 18.33768 |
Annual Sum or Average | 5943.00000 | 22.43049 | 35.85977 | -0.4488 | 12.40017 |
Minimum of Months | 454.00000 | 20.22430 | 21.34950 | -0.8582 | 6.64763 |
Maximum of Months | 514.00000 | 24.45244 | 52.40970 | 0.03215 | 21.89637 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60781 | 19.45902 | -0.9264 | 25.76755 |
February | 454.00000 | 19.67017 | 19.69618 | -0.8969 | 24.24905 |
March | 514.00000 | 20.99971 | 27.44945 | -0.4668 | 12.60784 |
April | 485.00000 | 21.73144 | 31.88836 | -0.2555 | 8.95040 |
May | 508.00000 | 22.91672 | 36.23858 | -0.9348 | 26.59285 |
June | 496.00000 | 23.83231 | 46.34062 | -0.5066 | 12.39628 |
July | 497.00000 | 24.31021 | 54.13297 | -0.2518 | 7.67053 |
August | 514.00000 | 24.17832 | 49.96862 | -0.3019 | 8.51862 |
September | 485.00000 | 24.01887 | 45.51598 | -0.4050 | 11.17730 |
October | 502.00000 | 22.83590 | 35.83387 | 0.07498 | 7.61265 |
November | 489.00000 | 21.48404 | 30.73872 | -0.3269 | 9.60586 |
December | 497.00000 | 19.98046 | 23.64382 | -0.8022 | 20.97059 |
Annual Sum or Average | 5943.00000 | 22.14842 | 35.18653 | -0.4981 | 14.63511 |
Minimum of Months | 454.00000 | 19.60781 | 19.45902 | -0.9348 | 7.61265 |
Maximum of Months | 514.00000 | 24.31021 | 54.13297 | 0.07498 | 26.59285 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19198 | 21.25027 | -0.8737 | 22.60970 |
February | 454.00000 | 20.31960 | 21.26161 | -0.8257 | 20.71423 |
March | 514.00000 | 21.15590 | 29.43008 | -0.4912 | 12.15638 |
April | 485.00000 | 21.97993 | 32.95696 | -0.2216 | 8.17854 |
May | 508.00000 | 23.34358 | 36.28361 | -0.7974 | 21.39832 |
June | 496.00000 | 24.16175 | 44.99953 | -0.3596 | 9.24933 |
July | 497.00000 | 24.41661 | 52.69826 | -0.1936 | 6.89810 |
August | 514.00000 | 24.28392 | 49.33824 | -0.2691 | 7.66014 |
September | 485.00000 | 23.96519 | 46.10992 | -0.4699 | 11.51508 |
October | 502.00000 | 22.56874 | 37.98532 | -0.0279 | 6.65750 |
November | 489.00000 | 21.26860 | 33.20967 | -0.4134 | 9.54729 |
December | 497.00000 | 20.38130 | 25.27590 | -0.7684 | 18.55665 |
Annual Sum or Average | 5943.00000 | 22.35203 | 36.00335 | -0.4741 | 12.89099 |
Minimum of Months | 454.00000 | 20.19198 | 21.25027 | -0.8737 | 6.65750 |
Maximum of Months | 514.00000 | 24.41661 | 52.69826 | -0.0279 | 22.60970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08863 | 21.44772 | -0.8797 | 23.13025 |
February | 454.00000 | 20.19733 | 21.38859 | -0.8379 | 21.41546 |
March | 514.00000 | 21.17847 | 29.33804 | -0.4821 | 12.82264 |
April | 485.00000 | 22.14341 | 32.92224 | -0.1887 | 7.62134 |
May | 508.00000 | 23.58907 | 35.76652 | -0.7378 | 18.06176 |
June | 496.00000 | 24.15163 | 44.95321 | -0.4114 | 9.35762 |
July | 497.00000 | 24.38082 | 52.92718 | -0.2516 | 6.97662 |
August | 514.00000 | 24.20467 | 49.62231 | -0.3562 | 8.28318 |
September | 485.00000 | 23.78761 | 46.63915 | -0.5802 | 13.62103 |
October | 502.00000 | 22.26368 | 39.09105 | -0.1206 | 7.17462 |
November | 489.00000 | 21.07935 | 33.73163 | -0.4743 | 10.88407 |
December | 497.00000 | 20.20363 | 25.36811 | -0.8086 | 20.50493 |
Annual Sum or Average | 5943.00000 | 22.28885 | 36.20183 | -0.5088 | 13.27343 |
Minimum of Months | 454.00000 | 20.08863 | 21.38859 | -0.8797 | 6.97662 |
Maximum of Months | 514.00000 | 24.38082 | 52.92718 | -0.1206 | 23.13025 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.02143 | 20.29827 | -0.8892 | 23.43771 |
February | 385.00000 | 20.16208 | 20.26726 | -0.8349 | 21.34330 |
March | 433.00000 | 21.25950 | 28.09470 | -0.4411 | 11.70236 |
April | 410.00000 | 22.30255 | 31.48401 | -0.1183 | 7.95943 |
May | 430.00000 | 23.61492 | 34.64088 | -0.6651 | 17.44617 |
June | 418.00000 | 24.21289 | 44.26601 | -0.3262 | 9.19666 |
July | 422.00000 | 24.51591 | 52.06266 | -0.1450 | 7.18358 |
August | 433.00000 | 24.23356 | 48.94186 | -0.2881 | 8.28077 |
September | 410.00000 | 23.80359 | 45.93752 | -0.5171 | 13.48023 |
October | 427.00000 | 22.26563 | 37.90344 | -0.1000 | 7.38447 |
November | 417.00000 | 21.03456 | 32.40337 | -0.4815 | 11.10257 |
December | 422.00000 | 20.12305 | 24.25358 | -0.8282 | 21.05081 |
Annual Sum or Average | 5034.00000 | 22.30938 | 35.13530 | -0.4676 | 13.25227 |
Minimum of Months | 385.00000 | 20.02143 | 20.26726 | -0.8892 | 7.18358 |
Maximum of Months | 433.00000 | 24.51591 | 52.06266 | -0.1000 | 23.43771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63069 | 20.44738 | -0.7115 | 18.78569 |
February | 454.00000 | 20.71956 | 20.35439 | -0.6703 | 17.47722 |
March | 514.00000 | 22.03644 | 27.52522 | -0.2381 | 9.89119 |
April | 485.00000 | 22.66697 | 31.09688 | -0.0364 | 7.84229 |
May | 508.00000 | 23.68073 | 34.82055 | -0.6612 | 16.83697 |
June | 496.00000 | 24.13501 | 44.68502 | -0.3827 | 9.59725 |
July | 497.00000 | 24.41868 | 52.52735 | -0.1988 | 7.17604 |
August | 514.00000 | 24.26508 | 48.99892 | -0.2728 | 7.89868 |
September | 485.00000 | 24.04788 | 45.14127 | -0.4063 | 11.13605 |
October | 502.00000 | 22.96954 | 36.60980 | 0.08486 | 7.91401 |
November | 489.00000 | 21.75701 | 31.93287 | -0.2930 | 9.40019 |
December | 497.00000 | 20.65795 | 24.42731 | -0.6729 | 16.82032 |
Annual Sum or Average | 5943.00000 | 22.68092 | 34.98347 | -0.3699 | 11.69825 |
Minimum of Months | 454.00000 | 20.63069 | 20.35439 | -0.7115 | 7.17604 |
Maximum of Months | 514.00000 | 24.41868 | 52.52735 | 0.08486 | 18.78569 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14159 | 20.65283 | -0.8645 | 22.64219 |
February | 454.00000 | 20.29523 | 20.59469 | -0.8056 | 20.56295 |
March | 514.00000 | 21.40734 | 28.37686 | -0.4040 | 11.52965 |
April | 485.00000 | 22.24014 | 31.87075 | -0.1306 | 8.19773 |
May | 508.00000 | 23.50529 | 35.32875 | -0.6891 | 18.50426 |
June | 496.00000 | 24.10575 | 44.83293 | -0.3396 | 9.63001 |
July | 497.00000 | 24.36509 | 52.74988 | -0.1823 | 7.28971 |
August | 514.00000 | 24.16899 | 49.52599 | -0.2908 | 8.41869 |
September | 485.00000 | 23.71255 | 46.49878 | -0.5385 | 14.04076 |
October | 502.00000 | 22.17027 | 38.50354 | -0.1143 | 7.46187 |
November | 489.00000 | 21.06341 | 33.04586 | -0.4680 | 10.83589 |
December | 497.00000 | 20.24064 | 24.67380 | -0.7985 | 20.04315 |
Annual Sum or Average | 5943.00000 | 22.30087 | 35.65891 | -0.4667 | 13.21669 |
Minimum of Months | 454.00000 | 20.14159 | 20.59469 | -0.8645 | 7.28971 |
Maximum of Months | 514.00000 | 24.36509 | 52.74988 | -0.1143 | 22.64219 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.116841E+12 | 0.00 | 496.37 | 207963.07 | 04-JAN-07:12 | 0.00 | 36.25 | 51.78 | 0.50 | 0.00 | 0.12 | 0.58 | 04-JAN-07:12 |
February | 0.100363E+12 | 0.00 | 449.44 | 220148.95 | 23-FEB-06:11 | 0.00 | 35.79 | 51.58 | 0.47 | 0.00 | 0.12 | 0.61 | 23-FEB-06:11 |
March | 0.467023E+11 | 0.00 | 376.15 | 199077.58 | 02-MAR-07:01 | 0.00 | 31.64 | 45.63 | 0.17 | 0.00 | 0.05 | 0.55 | 02-MAR-07:01 |
April | 0.114130E+11 | 0.00 | 224.71 | 208160.76 | 06-APR-06:01 | 0.00 | 30.29 | 39.27 | 0.04 | 0.00 | 0.01 | 0.58 | 06-APR-06:01 |
May | 0.979743E+09 | 0.00 | 50.18 | 139857.43 | 01-MAY-06:02 | 0.00 | 42.28 | 43.58 | 0.00 | 0.00 | 0.00 | 0.39 | 01-MAY-06:02 |
June | 0.154089E+09 | 0.00 | 56.54 | 10551.02 | 14-JUN-06:03 | 0.00 | 41.41 | 42.96 | 0.00 | 0.00 | 0.00 | 0.03 | 14-JUN-06:03 |
July | 10059783.67 | 0.00 | 100.93 | 5866.75 | 06-JUL-06:08 | 0.00 | 34.35 | 37.92 | 0.00 | 0.00 | 0.00 | 0.02 | 06-JUL-06:08 |
August | 38850571.87 | 0.00 | 57.49 | 14281.14 | 02-AUG-06:07 | 0.00 | 33.31 | 35.36 | 0.00 | 0.00 | 0.00 | 0.04 | 02-AUG-06:07 |
September | 0.284559E+09 | 0.00 | 34.95 | 53106.40 | 30-SEP-06:03 | 0.00 | 39.41 | 40.41 | 0.00 | 0.00 | 0.00 | 0.15 | 30-SEP-06:03 |
October | 0.653105E+10 | 0.00 | 183.73 | 195599.06 | 17-OCT-06:01 | 0.00 | 30.25 | 37.46 | 0.02 | 0.00 | 0.01 | 0.55 | 17-OCT-06:01 |
November | 0.266099E+11 | 0.00 | 331.94 | 208935.64 | 20-NOV-06:11 | 0.00 | 27.53 | 41.65 | 0.09 | 0.00 | 0.03 | 0.58 | 20-NOV-06:11 |
December | 0.978039E+11 | 0.00 | 467.24 | 216165.80 | 11-DEC-07:06 | 0.00 | 33.97 | 49.54 | 0.40 | 0.00 | 0.10 | 0.60 | 11-DEC-07:06 |
Annual Sum or Average | 0.407731E+12 | 0.00 | 2829.67 | 0.00 | 34.70 | 43.05 | 0.14 | 0.00 | 0.04 | ||||
Minimum of Months | 10059783.67 | 0.00 | 34.95 | 5866.75 | 0.00 | 27.53 | 35.36 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.116841E+12 | 0.00 | 496.37 | 220148.95 | 0.00 | 42.28 | 51.78 | 0.50 | 0.00 | 0.12 | 0.61 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.196063E+10 | 0.459106E+09 | 33.50 | 0.163339E+10 | 0.327240E+09 | 0.00 | 0.95 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 | 32393.42 | 15-MAR-14:10 | 32393.42 | 15-MAR-14:10 | 8385.36 | 14-MAR-10:50 | 7276.71 | 15-MAR-14:10 | 0.00 |
April | 0.693411E+09 | 0.176657E+09 | 36.01 | 0.625613E+09 | 67798274.87 | 0.00 | 0.45 | 07-APR-14:10 | 0.00 | 01-APR-00:10 | 13542.44 | 07-APR-14:10 | 13542.44 | 07-APR-14:10 | 2678.10 | 08-APR-14:00 | 3306.34 | 07-APR-14:10 | 0.00 |
May | 0.778438E+10 | 0.185155E+10 | 189.54 | 0.709279E+10 | 0.691588E+09 | 0.00 | 1.00 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 | 40550.77 | 23-MAY-14:30 | 40550.77 | 23-MAY-14:30 | 10885.51 | 24-MAY-06:03 | 8577.78 | 10-MAY-15:00 | 0.00 |
June | 0.378664E+11 | 0.848163E+10 | 372.15 | 0.288645E+11 | 0.900183E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 98335.82 | 27-JUN-06:03 | 64287.22 | 12-JUN-14:10 | 57777.47 | 27-JUN-06:03 | 20615.77 | 27-JUN-06:03 | 0.00 |
July | 0.671077E+11 | 0.148500E+11 | 427.59 | 0.477726E+11 | 0.193351E+11 | 0.00 | 1.00 | 03-JUL-10:00 | 0.00 | 01-JUL-00:10 | 118520.03 | 20-JUL-04:03 | 66172.09 | 21-JUL-14:10 | 71021.56 | 20-JUL-04:03 | 24570.25 | 20-JUL-04:03 | 0.00 |
August | 0.571890E+11 | 0.127084E+11 | 418.37 | 0.444088E+11 | 0.127803E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 118494.46 | 14-AUG-08:00 | 67519.24 | 09-AUG-16:00 | 72475.06 | 14-AUG-06:03 | 24471.86 | 15-AUG-08:20 | 0.00 |
September | 0.253507E+11 | 0.564692E+10 | 303.23 | 0.192273E+11 | 0.612342E+10 | 0.00 | 1.00 | 08-SEP-11:00 | 0.00 | 01-SEP-00:10 | 85088.34 | 14-SEP-06:03 | 57162.41 | 21-SEP-16:00 | 50351.07 | 14-SEP-06:03 | 17972.87 | 15-SEP-14:50 | 0.00 |
October | 0.280236E+10 | 0.680894E+09 | 85.80 | 0.240678E+10 | 0.395580E+09 | 0.00 | 0.98 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 33797.60 | 11-OCT-15:00 | 33797.60 | 11-OCT-15:00 | 5497.23 | 12-OCT-15:00 | 7144.13 | 11-OCT-15:00 | 0.00 |
November | 0.433408E+09 | 0.110933E+09 | 18.83 | 0.310172E+09 | 0.123235E+09 | 0.00 | 0.37 | 16-NOV-17:00 | 0.00 | 01-NOV-00:10 | 10967.75 | 16-NOV-17:00 | 8494.35 | 16-NOV-17:00 | 2801.10 | 04-NOV-15:00 | 2731.56 | 16-NOV-17:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.201188E+12 | 0.449661E+11 | 1885.03 | 0.152342E+12 | 0.488461E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.671077E+11 | 0.148500E+11 | 427.59 | 0.477726E+11 | 0.193351E+11 | 0.00 | 1.00 | 0.00 | 118520.03 | 67519.24 | 72475.06 | 24570.25 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.192586E+10 | 0.448223E+09 | 33.50 | 0.160327E+10 | 0.322586E+09 | 0.00 | 1.00 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 33896.29 | 15-MAR-13:50 | 33896.29 | 15-MAR-13:50 | 8154.09 | 14-MAR-10:40 | 7490.53 | 15-MAR-13:50 | 0.00 |
April | 0.703806E+09 | 0.179209E+09 | 39.72 | 0.639549E+09 | 64256894.87 | 0.00 | 0.48 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 13709.43 | 08-APR-13:30 | 13356.90 | 07-APR-14:00 | 2129.40 | 08-APR-14:30 | 3326.25 | 08-APR-13:30 | 0.00 |
May | 0.796610E+10 | 0.189083E+10 | 199.81 | 0.719215E+10 | 0.773950E+09 | 0.00 | 1.00 | 10-MAY-13:10 | 0.00 | 01-MAY-00:10 | 39632.40 | 23-MAY-14:30 | 39632.40 | 23-MAY-14:30 | 7070.53 | 14-MAY-16:05 | 8744.80 | 10-MAY-15:00 | 0.00 |
June | 0.358960E+11 | 0.805576E+10 | 378.01 | 0.272908E+11 | 0.860522E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 88299.90 | 27-JUN-07:40 | 60636.05 | 12-JUN-15:00 | 50128.65 | 27-JUN-07:40 | 18688.60 | 27-JUN-13:00 | 0.00 |
July | 0.613570E+11 | 0.136085E+11 | 431.04 | 0.434795E+11 | 0.178774E+11 | 0.00 | 1.00 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 | 113078.48 | 20-JUL-06:03 | 61582.67 | 21-JUL-13:40 | 67712.62 | 20-JUL-05:03 | 23641.26 | 21-JUL-05:03 | 0.00 |
August | 0.501688E+11 | 0.112105E+11 | 416.57 | 0.389680E+11 | 0.112009E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 111701.39 | 14-AUG-06:03 | 62984.64 | 09-AUG-15:10 | 69236.04 | 14-AUG-06:03 | 23234.87 | 15-AUG-14:30 | 0.00 |
September | 0.217104E+11 | 0.488559E+10 | 301.60 | 0.162781E+11 | 0.543230E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 74578.77 | 15-SEP-11:00 | 52441.50 | 21-SEP-15:40 | 33492.97 | 15-SEP-11:00 | 15700.96 | 15-SEP-11:00 | 0.00 |
October | 0.248232E+10 | 0.609511E+09 | 85.72 | 0.207457E+10 | 0.407750E+09 | 0.00 | 0.88 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 28206.96 | 11-OCT-15:00 | 28206.96 | 11-OCT-15:00 | 5590.88 | 12-OCT-15:00 | 6135.07 | 11-OCT-15:00 | 0.00 |
November | 0.393067E+09 | 0.100963E+09 | 18.83 | 0.273529E+09 | 0.119538E+09 | 0.00 | 0.33 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 9202.00 | 16-NOV-18:00 | 7150.39 | 16-NOV-12:40 | 2746.73 | 04-NOV-15:00 | 2315.80 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.182603E+12 | 0.409891E+11 | 1904.81 | 0.137799E+12 | 0.448039E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.613570E+11 | 0.136085E+11 | 431.04 | 0.434795E+11 | 0.178774E+11 | 0.00 | 1.00 | 0.00 | 113078.48 | 62984.64 | 69236.04 | 23641.26 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 885290.64 | 240131.44 | 0.60 | 881973.23 | 3317.41 | 0.00 | 0.03 | 09-JAN-06:20 | 0.00 | 01-JAN-00:03 | 953.25 | 09-JAN-06:20 | 953.25 | 09-JAN-06:20 | 19.05 | 03-JAN-05:50 | 257.66 | 09-JAN-06:20 | 0.00 |
February | 728009.63 | 197572.42 | 0.56 | 711788.48 | 16221.15 | 0.00 | 0.03 | 07-FEB-06:30 | 0.00 | 01-FEB-00:10 | 816.46 | 07-FEB-06:30 | 816.46 | 07-FEB-06:30 | 26.51 | 20-FEB-03:40 | 220.93 | 07-FEB-06:30 | 0.00 |
March | 0.209462E+10 | 0.487903E+09 | 33.93 | 0.176050E+10 | 0.334128E+09 | 0.00 | 1.00 | 15-MAR-13:20 | 0.00 | 01-MAR-00:10 | 40545.24 | 15-MAR-14:00 | 40545.24 | 15-MAR-14:00 | 8874.65 | 14-MAR-10:50 | 8999.96 | 15-MAR-14:00 | 0.00 |
April | 0.722121E+09 | 0.184610E+09 | 38.35 | 0.643228E+09 | 78892938.23 | 0.00 | 0.46 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 14492.65 | 08-APR-13:30 | 13694.68 | 07-APR-14:00 | 2571.67 | 08-APR-14:00 | 3534.41 | 08-APR-13:30 | 0.00 |
May | 0.818563E+10 | 0.195243E+10 | 198.82 | 0.731982E+10 | 0.865801E+09 | 0.00 | 1.00 | 10-MAY-13:00 | 0.00 | 01-MAY-00:10 | 44965.41 | 10-MAY-14:30 | 44965.41 | 10-MAY-14:30 | 8107.32 | 14-MAY-16:13 | 9974.46 | 10-MAY-14:30 | 0.00 |
June | 0.376769E+11 | 0.849072E+10 | 377.03 | 0.285333E+11 | 0.914362E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 125243.30 | 27-JUN-14:55 | 80422.69 | 27-JUN-15:05 | 69977.64 | 27-JUN-14:55 | 26270.69 | 27-JUN-15:15 | 0.00 |
July | 0.647907E+11 | 0.144233E+11 | 430.51 | 0.460204E+11 | 0.187703E+11 | 0.00 | 1.00 | 02-JUL-15:52 | 0.00 | 01-JUL-00:10 | 125243.30 | 21-JUL-05:03 | 72625.25 | 21-JUL-13:30 | 72693.03 | 21-JUL-05:03 | 26223.76 | 21-JUL-05:03 | 0.00 |
August | 0.524209E+11 | 0.117745E+11 | 415.95 | 0.405792E+11 | 0.118417E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 123909.09 | 15-AUG-14:20 | 78589.33 | 13-AUG-15:02 | 76895.67 | 14-AUG-06:03 | 25988.63 | 15-AUG-14:20 | 0.00 |
September | 0.217190E+11 | 0.493375E+10 | 300.04 | 0.159391E+11 | 0.577987E+10 | 0.00 | 1.00 | 08-SEP-12:50 | 0.00 | 01-SEP-00:10 | 85734.64 | 15-SEP-12:30 | 58279.13 | 21-SEP-15:30 | 37917.83 | 15-SEP-12:30 | 18320.11 | 15-SEP-12:30 | 0.00 |
October | 0.233600E+10 | 0.580420E+09 | 83.33 | 0.189471E+10 | 0.441288E+09 | 0.00 | 0.79 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27350.17 | 11-OCT-15:00 | 27350.17 | 11-OCT-15:00 | 5848.85 | 12-OCT-15:00 | 6103.48 | 11-OCT-15:00 | 0.00 |
November | 0.414163E+09 | 0.106686E+09 | 18.83 | 0.283410E+09 | 0.130752E+09 | 0.00 | 0.34 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 10520.94 | 27-NOV-07:03 | 9405.58 | 27-NOV-07:03 | 2992.66 | 04-NOV-15:00 | 2641.55 | 27-NOV-07:03 | 0.00 |
December | 1377613.16 | 374070.28 | 1.07 | 1320837.08 | 56776.08 | 0.00 | 0.02 | 28-DEC-06:06 | 0.00 | 01-DEC-00:10 | 607.96 | 28-DEC-06:06 | 607.96 | 28-DEC-06:06 | 36.36 | 18-DEC-00:20 | 164.79 | 28-DEC-06:06 | 0.00 |
Annual Sum or Average | 0.190363E+12 | 0.429351E+11 | 1899.03 | 0.142977E+12 | 0.473864E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 728009.63 | 197572.42 | 0.56 | 711788.48 | 3317.41 | 0.00 | 0.02 | 0.00 | 607.96 | 607.96 | 19.05 | 164.79 | 0.00 | ||||||
Maximum of Months | 0.647907E+11 | 0.144233E+11 | 430.51 | 0.460204E+11 | 0.187703E+11 | 0.00 | 1.00 | 0.00 | 125243.30 | 80422.69 | 76895.67 | 26270.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.09 | 0.00 | 363.09 | 5.41 | 2162.74 | 0.00 | 0.00 | 0.00 |
February | 553.22 | 0.00 | 553.22 | 35.85 | 2023.71 | 0.00 | 0.00 | 0.00 |
March | 670.90 | 0.00 | 670.90 | 219.88 | 1456.90 | 0.00 | 0.00 | 0.00 |
April | 854.86 | 3.41 | 851.45 | 466.20 | 1035.96 | 0.00 | 0.00 | 0.00 |
May | 993.30 | 42.12 | 951.18 | 776.03 | 675.21 | 0.00 | 0.00 | 0.00 |
June | 1194.74 | 101.70 | 1093.03 | 1279.36 | 445.71 | 0.00 | 0.00 | 0.00 |
July | 1108.28 | 71.54 | 1036.73 | 1374.42 | 314.48 | 0.00 | 0.00 | 0.00 |
August | 958.97 | 14.59 | 944.38 | 1124.46 | 413.27 | 0.00 | 0.00 | 0.00 |
September | 729.79 | 0.15 | 729.64 | 660.17 | 661.00 | 0.00 | 0.00 | 0.00 |
October | 545.55 | 0.00 | 545.55 | 275.07 | 1018.66 | 0.00 | 0.00 | 0.00 |
November | 366.60 | 0.00 | 366.60 | 84.75 | 1314.71 | 0.00 | 0.00 | 0.00 |
December | 339.84 | 0.00 | 339.84 | 6.17 | 2052.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 723.97 | 19.54 | 704.42 | 528.61 | 1126.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.84 | 0.00 | 339.84 | 5.41 | 314.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1194.74 | 101.70 | 1093.03 | 1374.42 | 2162.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 442.97 | 142.84 | 300.13 | 173.82 | 1309.58 | 0.00 | 0.00 | 0.00 |
February | 649.98 | 195.04 | 454.94 | 311.48 | 1239.67 | 0.00 | 0.00 | 0.00 |
March | 932.70 | 390.61 | 542.09 | 734.64 | 893.51 | 0.00 | 0.00 | 0.00 |
April | 1234.49 | 545.46 | 689.03 | 1163.62 | 655.83 | 0.00 | 0.00 | 0.00 |
May | 1383.07 | 611.81 | 771.26 | 1497.28 | 456.04 | 0.00 | 0.00 | 0.00 |
June | 1544.66 | 682.66 | 861.99 | 1869.23 | 301.28 | 0.00 | 0.00 | 0.00 |
July | 1483.28 | 653.07 | 830.21 | 1930.07 | 210.86 | 0.00 | 0.00 | 0.00 |
August | 1339.56 | 562.27 | 777.29 | 1706.25 | 273.24 | 0.00 | 0.00 | 0.00 |
September | 1114.75 | 494.46 | 620.29 | 1285.18 | 421.40 | 0.00 | 0.00 | 0.00 |
October | 756.45 | 312.89 | 443.56 | 684.55 | 641.89 | 0.00 | 0.00 | 0.00 |
November | 429.07 | 137.64 | 291.43 | 272.88 | 836.72 | 0.00 | 0.00 | 0.00 |
December | 345.42 | 71.37 | 274.05 | 91.09 | 1285.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 972.81 | 400.98 | 571.83 | 980.27 | 707.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.42 | 71.37 | 274.05 | 91.09 | 210.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1544.66 | 682.66 | 861.99 | 1930.07 | 1309.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1561.30 | 911.38 | 649.92 | 1265.96 | 1845.84 | 0.00 | 0.00 | 0.00 |
February | 1782.62 | 859.56 | 923.05 | 1423.52 | 1813.49 | 0.00 | 0.00 | 0.00 |
March | 2175.80 | 1222.57 | 953.23 | 2136.01 | 1348.88 | 0.00 | 0.00 | 0.00 |
April | 1801.91 | 720.05 | 1081.86 | 1845.39 | 1074.17 | 0.00 | 0.00 | 0.00 |
May | 1576.83 | 457.98 | 1118.85 | 1747.35 | 743.54 | 0.00 | 0.00 | 0.00 |
June | 1532.17 | 324.67 | 1207.49 | 1894.84 | 489.03 | 0.00 | 0.00 | 0.00 |
July | 1564.10 | 379.50 | 1184.59 | 2142.79 | 341.17 | 0.00 | 0.00 | 0.00 |
August | 1755.95 | 569.32 | 1186.63 | 2369.56 | 437.67 | 0.00 | 0.00 | 0.00 |
September | 2041.65 | 994.44 | 1047.22 | 2544.82 | 677.61 | 0.00 | 0.00 | 0.00 |
October | 1953.56 | 1115.91 | 837.65 | 2117.51 | 991.07 | 0.00 | 0.00 | 0.00 |
November | 1399.10 | 789.84 | 609.26 | 1335.82 | 1247.27 | 0.00 | 0.00 | 0.00 |
December | 1305.56 | 675.69 | 629.87 | 1003.27 | 1812.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1703.68 | 751.34 | 952.34 | 1821.21 | 1064.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.56 | 324.67 | 609.26 | 1003.27 | 341.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2175.80 | 1222.57 | 1207.49 | 2544.82 | 1845.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.06 | 89.22 | 290.84 | 106.92 | 1361.22 | 0.00 | 0.00 | 0.00 |
February | 615.98 | 158.31 | 457.67 | 267.67 | 1281.25 | 0.00 | 0.00 | 0.00 |
March | 965.44 | 413.38 | 552.06 | 776.14 | 918.27 | 0.00 | 0.00 | 0.00 |
April | 1182.05 | 484.69 | 697.36 | 1116.01 | 686.50 | 0.00 | 0.00 | 0.00 |
May | 1394.42 | 630.19 | 764.23 | 1526.80 | 483.55 | 0.00 | 0.00 | 0.00 |
June | 1682.40 | 791.33 | 891.07 | 2064.81 | 329.28 | 0.00 | 0.00 | 0.00 |
July | 1504.13 | 659.46 | 844.67 | 1969.08 | 233.94 | 0.00 | 0.00 | 0.00 |
August | 1360.40 | 578.46 | 781.94 | 1753.79 | 292.99 | 0.00 | 0.00 | 0.00 |
September | 1068.34 | 461.37 | 606.97 | 1238.25 | 443.48 | 0.00 | 0.00 | 0.00 |
October | 692.55 | 243.95 | 448.59 | 616.10 | 664.57 | 0.00 | 0.00 | 0.00 |
November | 410.41 | 118.26 | 292.14 | 252.04 | 853.31 | 0.00 | 0.00 | 0.00 |
December | 355.79 | 77.52 | 278.26 | 103.06 | 1306.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 969.26 | 393.32 | 575.94 | 986.40 | 735.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.79 | 77.52 | 278.26 | 103.06 | 233.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1682.40 | 791.33 | 891.07 | 2064.81 | 1361.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 0.90 | 738.22 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 10.90 | 690.71 | 0.00 | 0.00 | 0.00 |
March | 223.62 | 0.00 | 223.62 | 78.03 | 491.67 | 0.00 | 0.00 | 0.00 |
April | 284.94 | 1.14 | 283.80 | 165.09 | 344.43 | 0.00 | 0.00 | 0.00 |
May | 331.09 | 14.04 | 317.05 | 274.34 | 217.68 | 0.00 | 0.00 | 0.00 |
June | 398.23 | 33.90 | 364.33 | 437.49 | 145.63 | 0.00 | 0.00 | 0.00 |
July | 369.41 | 23.85 | 345.56 | 467.58 | 102.05 | 0.00 | 0.00 | 0.00 |
August | 319.64 | 4.86 | 314.78 | 379.43 | 139.54 | 0.00 | 0.00 | 0.00 |
September | 243.25 | 0.05 | 243.20 | 219.78 | 233.73 | 0.00 | 0.00 | 0.00 |
October | 181.84 | 0.00 | 181.84 | 85.02 | 374.87 | 0.00 | 0.00 | 0.00 |
November | 122.19 | 0.00 | 122.19 | 24.32 | 478.72 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.48 | 718.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.31 | 6.51 | 234.80 | 179.71 | 388.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 0.90 | 102.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.23 | 33.90 | 364.33 | 467.58 | 738.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 0.90 | 738.26 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 10.90 | 690.75 | 0.00 | 0.00 | 0.00 |
March | 223.63 | 0.00 | 223.63 | 78.03 | 491.70 | 0.00 | 0.00 | 0.00 |
April | 284.95 | 1.14 | 283.81 | 165.10 | 344.45 | 0.00 | 0.00 | 0.00 |
May | 331.10 | 14.04 | 317.06 | 274.35 | 217.70 | 0.00 | 0.00 | 0.00 |
June | 398.24 | 33.90 | 364.34 | 437.50 | 145.63 | 0.00 | 0.00 | 0.00 |
July | 369.42 | 23.85 | 345.58 | 467.60 | 102.05 | 0.00 | 0.00 | 0.00 |
August | 319.65 | 4.86 | 314.79 | 379.44 | 139.54 | 0.00 | 0.00 | 0.00 |
September | 243.26 | 0.05 | 243.21 | 219.79 | 233.74 | 0.00 | 0.00 | 0.00 |
October | 181.85 | 0.00 | 181.85 | 85.02 | 374.89 | 0.00 | 0.00 | 0.00 |
November | 122.20 | 0.00 | 122.20 | 24.32 | 478.76 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.48 | 718.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.32 | 6.51 | 234.81 | 179.72 | 388.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 0.90 | 102.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.24 | 33.90 | 364.34 | 467.60 | 738.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.03 | 0.00 | 121.03 | 0.90 | 738.26 | 0.00 | 0.00 | 0.00 |
February | 184.40 | 0.00 | 184.40 | 10.90 | 690.75 | 0.00 | 0.00 | 0.00 |
March | 223.63 | 0.00 | 223.63 | 78.03 | 491.70 | 0.00 | 0.00 | 0.00 |
April | 284.95 | 1.14 | 283.81 | 165.10 | 344.45 | 0.00 | 0.00 | 0.00 |
May | 331.10 | 14.04 | 317.06 | 274.35 | 217.70 | 0.00 | 0.00 | 0.00 |
June | 398.24 | 33.90 | 364.34 | 437.50 | 145.63 | 0.00 | 0.00 | 0.00 |
July | 369.42 | 23.85 | 345.58 | 467.60 | 102.05 | 0.00 | 0.00 | 0.00 |
August | 319.65 | 4.86 | 314.79 | 379.44 | 139.54 | 0.00 | 0.00 | 0.00 |
September | 243.26 | 0.05 | 243.21 | 219.79 | 233.74 | 0.00 | 0.00 | 0.00 |
October | 181.85 | 0.00 | 181.85 | 85.02 | 374.89 | 0.00 | 0.00 | 0.00 |
November | 122.20 | 0.00 | 122.20 | 24.32 | 478.76 | 0.00 | 0.00 | 0.00 |
December | 113.28 | 0.00 | 113.28 | 1.48 | 718.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 241.32 | 6.51 | 234.81 | 179.72 | 388.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.28 | 0.00 | 113.28 | 0.90 | 102.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 398.24 | 33.90 | 364.34 | 467.60 | 738.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 426.12 | 137.40 | 288.72 | 166.07 | 1296.96 | 0.00 | 0.00 | 0.00 |
February | 625.25 | 187.62 | 437.63 | 299.30 | 1226.76 | 0.00 | 0.00 | 0.00 |
March | 897.21 | 375.75 | 521.47 | 718.12 | 882.80 | 0.00 | 0.00 | 0.00 |
April | 1187.52 | 524.71 | 662.81 | 1132.82 | 649.10 | 0.00 | 0.00 | 0.00 |
May | 1330.45 | 588.52 | 741.92 | 1461.17 | 442.53 | 0.00 | 0.00 | 0.00 |
June | 1485.88 | 656.68 | 829.20 | 1815.37 | 295.92 | 0.00 | 0.00 | 0.00 |
July | 1426.84 | 628.21 | 798.62 | 1871.65 | 207.17 | 0.00 | 0.00 | 0.00 |
August | 1288.59 | 540.88 | 747.71 | 1649.71 | 276.66 | 0.00 | 0.00 | 0.00 |
September | 1072.33 | 475.64 | 596.69 | 1234.22 | 442.53 | 0.00 | 0.00 | 0.00 |
October | 727.67 | 300.98 | 426.68 | 641.23 | 693.35 | 0.00 | 0.00 | 0.00 |
November | 412.74 | 132.40 | 280.34 | 251.29 | 884.83 | 0.00 | 0.00 | 0.00 |
December | 332.28 | 68.66 | 263.62 | 84.68 | 1299.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 935.79 | 385.72 | 550.07 | 947.30 | 713.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.28 | 68.66 | 263.62 | 84.68 | 207.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1485.88 | 656.68 | 829.20 | 1871.65 | 1299.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.85 | 5.43 | 11.42 | 6.57 | 51.28 | 0.00 | 0.00 | 0.00 |
February | 24.72 | 7.42 | 17.30 | 11.83 | 48.51 | 0.00 | 0.00 | 0.00 |
March | 35.47 | 14.86 | 20.62 | 28.39 | 34.91 | 0.00 | 0.00 | 0.00 |
April | 46.95 | 20.75 | 26.21 | 44.79 | 25.66 | 0.00 | 0.00 | 0.00 |
May | 52.60 | 23.27 | 29.33 | 57.77 | 17.50 | 0.00 | 0.00 | 0.00 |
June | 58.75 | 25.96 | 32.79 | 71.78 | 11.70 | 0.00 | 0.00 | 0.00 |
July | 56.42 | 24.84 | 31.58 | 74.00 | 8.19 | 0.00 | 0.00 | 0.00 |
August | 50.95 | 21.39 | 29.56 | 65.23 | 10.94 | 0.00 | 0.00 | 0.00 |
September | 42.40 | 18.81 | 23.59 | 48.80 | 17.50 | 0.00 | 0.00 | 0.00 |
October | 28.77 | 11.90 | 16.87 | 25.35 | 27.41 | 0.00 | 0.00 | 0.00 |
November | 16.32 | 5.24 | 11.08 | 9.94 | 34.99 | 0.00 | 0.00 | 0.00 |
December | 13.14 | 2.71 | 10.42 | 3.35 | 51.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.00 | 15.25 | 21.75 | 37.46 | 28.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.14 | 2.71 | 10.42 | 3.35 | 8.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.75 | 25.96 | 32.79 | 74.00 | 51.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.42 | 303.79 | 216.64 | 431.27 | 626.09 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 286.51 | 307.68 | 487.00 | 613.80 | 0.00 | 0.00 | 0.00 |
March | 725.26 | 407.51 | 317.74 | 729.41 | 463.37 | 0.00 | 0.00 | 0.00 |
April | 600.63 | 240.01 | 360.62 | 630.57 | 362.37 | 0.00 | 0.00 | 0.00 |
May | 525.60 | 152.66 | 372.95 | 599.96 | 243.27 | 0.00 | 0.00 | 0.00 |
June | 510.72 | 108.22 | 402.50 | 645.22 | 161.97 | 0.00 | 0.00 | 0.00 |
July | 521.36 | 126.50 | 394.86 | 724.31 | 114.10 | 0.00 | 0.00 | 0.00 |
August | 585.31 | 189.77 | 395.54 | 796.19 | 152.70 | 0.00 | 0.00 | 0.00 |
September | 680.54 | 331.47 | 349.07 | 850.73 | 246.64 | 0.00 | 0.00 | 0.00 |
October | 651.18 | 371.96 | 279.21 | 704.51 | 369.92 | 0.00 | 0.00 | 0.00 |
November | 466.36 | 263.27 | 203.08 | 443.29 | 457.50 | 0.00 | 0.00 | 0.00 |
December | 435.18 | 225.22 | 209.95 | 337.85 | 627.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.89 | 250.44 | 317.44 | 615.78 | 368.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.18 | 108.22 | 203.08 | 337.85 | 114.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.26 | 407.51 | 402.50 | 850.73 | 627.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.42 | 303.79 | 216.64 | 431.27 | 626.09 | 0.00 | 0.00 | 0.00 |
February | 594.20 | 286.51 | 307.68 | 487.00 | 613.80 | 0.00 | 0.00 | 0.00 |
March | 725.26 | 407.51 | 317.74 | 729.41 | 463.37 | 0.00 | 0.00 | 0.00 |
April | 600.63 | 240.01 | 360.62 | 630.57 | 362.37 | 0.00 | 0.00 | 0.00 |
May | 525.60 | 152.66 | 372.95 | 599.96 | 243.27 | 0.00 | 0.00 | 0.00 |
June | 510.72 | 108.22 | 402.50 | 645.22 | 161.97 | 0.00 | 0.00 | 0.00 |
July | 521.36 | 126.50 | 394.86 | 724.31 | 114.10 | 0.00 | 0.00 | 0.00 |
August | 585.31 | 189.77 | 395.54 | 796.19 | 152.70 | 0.00 | 0.00 | 0.00 |
September | 680.54 | 331.47 | 349.07 | 850.73 | 246.64 | 0.00 | 0.00 | 0.00 |
October | 651.18 | 371.96 | 279.21 | 704.51 | 369.92 | 0.00 | 0.00 | 0.00 |
November | 466.36 | 263.27 | 203.08 | 443.29 | 457.50 | 0.00 | 0.00 | 0.00 |
December | 435.18 | 225.22 | 209.95 | 337.85 | 627.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.89 | 250.44 | 317.44 | 615.78 | 368.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.18 | 108.22 | 203.08 | 337.85 | 114.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.26 | 407.51 | 402.50 | 850.73 | 627.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 520.39 | 303.77 | 216.62 | 431.24 | 626.05 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.50 | 307.66 | 486.97 | 613.76 | 0.00 | 0.00 | 0.00 |
March | 725.21 | 407.49 | 317.72 | 729.37 | 463.34 | 0.00 | 0.00 | 0.00 |
April | 600.59 | 240.00 | 360.59 | 630.53 | 362.35 | 0.00 | 0.00 | 0.00 |
May | 525.57 | 152.65 | 372.92 | 599.92 | 243.25 | 0.00 | 0.00 | 0.00 |
June | 510.69 | 108.22 | 402.47 | 645.18 | 161.96 | 0.00 | 0.00 | 0.00 |
July | 521.33 | 126.49 | 394.84 | 724.26 | 114.09 | 0.00 | 0.00 | 0.00 |
August | 585.27 | 189.76 | 395.51 | 796.14 | 152.69 | 0.00 | 0.00 | 0.00 |
September | 680.50 | 331.45 | 349.05 | 850.68 | 246.62 | 0.00 | 0.00 | 0.00 |
October | 651.13 | 371.94 | 279.19 | 704.47 | 369.89 | 0.00 | 0.00 | 0.00 |
November | 466.33 | 263.26 | 203.07 | 443.26 | 457.47 | 0.00 | 0.00 | 0.00 |
December | 435.15 | 225.21 | 209.94 | 337.83 | 627.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.85 | 250.43 | 317.42 | 615.74 | 368.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.15 | 108.22 | 203.07 | 337.83 | 114.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 725.21 | 407.49 | 402.47 | 850.68 | 627.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.60 | 85.83 | 279.77 | 103.34 | 1342.37 | 0.00 | 0.00 | 0.00 |
February | 592.54 | 152.29 | 440.26 | 261.61 | 1264.94 | 0.00 | 0.00 | 0.00 |
March | 928.71 | 397.65 | 531.06 | 764.07 | 909.18 | 0.00 | 0.00 | 0.00 |
April | 1137.07 | 466.24 | 670.83 | 1092.39 | 677.66 | 0.00 | 0.00 | 0.00 |
May | 1341.36 | 606.21 | 735.15 | 1490.58 | 472.02 | 0.00 | 0.00 | 0.00 |
June | 1618.39 | 761.22 | 857.17 | 2004.77 | 327.83 | 0.00 | 0.00 | 0.00 |
July | 1446.90 | 634.37 | 812.53 | 1909.86 | 232.36 | 0.00 | 0.00 | 0.00 |
August | 1308.64 | 556.44 | 752.20 | 1694.32 | 299.48 | 0.00 | 0.00 | 0.00 |
September | 1027.69 | 443.81 | 583.88 | 1188.16 | 467.03 | 0.00 | 0.00 | 0.00 |
October | 666.20 | 234.67 | 431.52 | 579.02 | 714.43 | 0.00 | 0.00 | 0.00 |
November | 394.79 | 113.76 | 281.03 | 233.94 | 899.86 | 0.00 | 0.00 | 0.00 |
December | 342.25 | 74.57 | 267.68 | 97.72 | 1317.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 932.38 | 378.35 | 554.03 | 955.37 | 741.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.25 | 74.57 | 267.68 | 97.72 | 232.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1618.39 | 761.22 | 857.17 | 2004.77 | 1342.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.46 | 3.39 | 11.06 | 4.09 | 53.08 | 0.00 | 0.00 | 0.00 |
February | 23.43 | 6.02 | 17.41 | 10.34 | 50.01 | 0.00 | 0.00 | 0.00 |
March | 36.72 | 15.72 | 21.00 | 30.21 | 35.95 | 0.00 | 0.00 | 0.00 |
April | 44.96 | 18.43 | 26.52 | 43.19 | 26.79 | 0.00 | 0.00 | 0.00 |
May | 53.04 | 23.97 | 29.07 | 58.94 | 18.66 | 0.00 | 0.00 | 0.00 |
June | 63.99 | 30.10 | 33.89 | 79.27 | 12.96 | 0.00 | 0.00 | 0.00 |
July | 57.21 | 25.08 | 32.13 | 75.51 | 9.19 | 0.00 | 0.00 | 0.00 |
August | 51.74 | 22.00 | 29.74 | 66.99 | 11.84 | 0.00 | 0.00 | 0.00 |
September | 40.63 | 17.55 | 23.09 | 46.98 | 18.47 | 0.00 | 0.00 | 0.00 |
October | 26.34 | 9.28 | 17.06 | 22.89 | 28.25 | 0.00 | 0.00 | 0.00 |
November | 15.61 | 4.50 | 11.11 | 9.25 | 35.58 | 0.00 | 0.00 | 0.00 |
December | 13.53 | 2.95 | 10.58 | 3.86 | 52.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.87 | 14.96 | 21.91 | 37.77 | 29.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.53 | 2.95 | 10.58 | 3.86 | 9.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.99 | 30.10 | 33.89 | 79.27 | 53.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.09 | 0.00 | 363.09 | 2.62 | 2242.39 | 0.00 | 0.00 | 0.00 |
February | 553.22 | 0.00 | 553.22 | 28.76 | 2103.29 | 0.00 | 0.00 | 0.00 |
March | 670.90 | 0.00 | 670.90 | 209.56 | 1536.17 | 0.00 | 0.00 | 0.00 |
April | 854.86 | 3.41 | 851.45 | 447.59 | 1101.32 | 0.00 | 0.00 | 0.00 |
May | 993.30 | 42.12 | 951.18 | 763.26 | 710.50 | 0.00 | 0.00 | 0.00 |
June | 1194.74 | 101.70 | 1093.03 | 1277.36 | 461.28 | 0.00 | 0.00 | 0.00 |
July | 1108.28 | 71.54 | 1036.73 | 1377.67 | 322.84 | 0.00 | 0.00 | 0.00 |
August | 958.97 | 14.59 | 944.38 | 1123.74 | 429.13 | 0.00 | 0.00 | 0.00 |
September | 729.79 | 0.15 | 729.64 | 650.07 | 703.17 | 0.00 | 0.00 | 0.00 |
October | 545.55 | 0.00 | 545.55 | 253.49 | 1105.83 | 0.00 | 0.00 | 0.00 |
November | 366.60 | 0.00 | 366.60 | 72.44 | 1418.13 | 0.00 | 0.00 | 0.00 |
December | 339.84 | 0.00 | 339.84 | 4.29 | 2149.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 723.97 | 19.54 | 704.42 | 520.56 | 1185.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 339.84 | 0.00 | 339.84 | 2.62 | 322.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1194.74 | 101.70 | 1093.03 | 1377.67 | 2242.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 442.97 | 142.84 | 300.13 | 168.40 | 1359.50 | 0.00 | 0.00 | 0.00 |
February | 649.98 | 195.04 | 454.94 | 301.90 | 1288.22 | 0.00 | 0.00 | 0.00 |
March | 932.70 | 390.61 | 542.09 | 723.27 | 941.20 | 0.00 | 0.00 | 0.00 |
April | 1234.49 | 545.46 | 689.03 | 1151.03 | 692.18 | 0.00 | 0.00 | 0.00 |
May | 1383.07 | 611.81 | 771.26 | 1492.07 | 476.83 | 0.00 | 0.00 | 0.00 |
June | 1544.66 | 682.66 | 861.99 | 1869.90 | 311.02 | 0.00 | 0.00 | 0.00 |
July | 1483.28 | 653.07 | 830.21 | 1933.47 | 216.10 | 0.00 | 0.00 | 0.00 |
August | 1339.56 | 562.27 | 777.29 | 1707.31 | 282.94 | 0.00 | 0.00 | 0.00 |
September | 1114.75 | 494.46 | 620.29 | 1279.18 | 444.84 | 0.00 | 0.00 | 0.00 |
October | 756.45 | 312.89 | 443.56 | 668.55 | 691.48 | 0.00 | 0.00 | 0.00 |
November | 429.07 | 137.64 | 291.43 | 261.35 | 898.86 | 0.00 | 0.00 | 0.00 |
December | 345.42 | 71.37 | 274.05 | 86.67 | 1345.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 972.81 | 400.98 | 571.83 | 973.89 | 743.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 345.42 | 71.37 | 274.05 | 86.67 | 216.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1544.66 | 682.66 | 861.99 | 1933.47 | 1359.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1561.30 | 911.38 | 649.92 | 1251.91 | 1922.31 | 0.00 | 0.00 | 0.00 |
February | 1782.62 | 859.56 | 923.05 | 1406.60 | 1889.21 | 0.00 | 0.00 | 0.00 |
March | 2175.80 | 1222.57 | 953.23 | 2118.53 | 1424.58 | 0.00 | 0.00 | 0.00 |
April | 1801.91 | 720.05 | 1081.86 | 1828.94 | 1137.82 | 0.00 | 0.00 | 0.00 |
May | 1576.83 | 457.98 | 1118.85 | 1740.44 | 782.75 | 0.00 | 0.00 | 0.00 |
June | 1532.17 | 324.67 | 1207.49 | 1895.99 | 509.05 | 0.00 | 0.00 | 0.00 |
July | 1564.10 | 379.50 | 1184.59 | 2147.95 | 352.22 | 0.00 | 0.00 | 0.00 |
August | 1755.95 | 569.32 | 1186.63 | 2371.59 | 455.54 | 0.00 | 0.00 | 0.00 |
September | 2041.65 | 994.44 | 1047.22 | 2538.15 | 717.59 | 0.00 | 0.00 | 0.00 |
October | 1953.56 | 1115.91 | 837.65 | 2094.42 | 1070.04 | 0.00 | 0.00 | 0.00 |
November | 1399.10 | 789.84 | 609.26 | 1314.10 | 1343.01 | 0.00 | 0.00 | 0.00 |
December | 1305.56 | 675.69 | 629.87 | 988.07 | 1900.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1703.68 | 751.34 | 952.34 | 1810.41 | 1121.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.56 | 324.67 | 609.26 | 988.07 | 352.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2175.80 | 1222.57 | 1207.49 | 2538.15 | 1922.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.06 | 89.22 | 290.84 | 103.54 | 1411.28 | 0.00 | 0.00 | 0.00 |
February | 615.98 | 158.31 | 457.67 | 261.31 | 1331.03 | 0.00 | 0.00 | 0.00 |
March | 965.44 | 413.38 | 552.06 | 767.91 | 968.68 | 0.00 | 0.00 | 0.00 |
April | 1182.05 | 484.69 | 697.36 | 1105.42 | 727.58 | 0.00 | 0.00 | 0.00 |
May | 1394.42 | 630.19 | 764.23 | 1521.00 | 509.05 | 0.00 | 0.00 | 0.00 |
June | 1682.40 | 791.33 | 891.07 | 2065.94 | 342.44 | 0.00 | 0.00 | 0.00 |
July | 1504.13 | 659.46 | 844.67 | 1972.54 | 241.46 | 0.00 | 0.00 | 0.00 |
August | 1360.40 | 578.46 | 781.94 | 1754.20 | 304.91 | 0.00 | 0.00 | 0.00 |
September | 1068.34 | 461.37 | 606.97 | 1231.33 | 471.25 | 0.00 | 0.00 | 0.00 |
October | 692.55 | 243.95 | 448.59 | 601.93 | 718.42 | 0.00 | 0.00 | 0.00 |
November | 410.41 | 118.26 | 292.14 | 242.18 | 917.44 | 0.00 | 0.00 | 0.00 |
December | 355.79 | 77.52 | 278.26 | 99.25 | 1365.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 969.26 | 393.32 | 575.94 | 981.08 | 772.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.79 | 77.52 | 278.26 | 99.25 | 241.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1682.40 | 791.33 | 891.07 | 2065.94 | 1411.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972507E+09 | 0.00 | 0.972507E+09 | 14494714.19 | 0.579267E+10 |
February | 0.133834E+10 | 0.00 | 0.133834E+10 | 86730637.51 | 0.489575E+10 |
March | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.588922E+09 | 0.390215E+10 |
April | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.120839E+10 | 0.268520E+10 |
May | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.207852E+10 | 0.180847E+10 |
June | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.331611E+10 | 0.115528E+10 |
July | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.368123E+10 | 0.842314E+09 |
August | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.301175E+10 | 0.110691E+10 |
September | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.171115E+10 | 0.171330E+10 |
October | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.736760E+09 | 0.272838E+10 |
November | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.219667E+09 | 0.340772E+10 |
December | 0.910238E+09 | 0.00 | 0.910238E+09 | 16534796.67 | 0.549844E+10 |
Annual Sum or Average | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.166703E+11 | 0.355366E+11 |
Minimum of Months | 0.910238E+09 | 0.00 | 0.910238E+09 | 14494714.19 | 0.842314E+09 |
Maximum of Months | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.368123E+10 | 0.579267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.465548E+09 | 0.350757E+10 |
February | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.753539E+09 | 0.299900E+10 |
March | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.196766E+10 | 0.239319E+10 |
April | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.301610E+10 | 0.169992E+10 |
May | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.401031E+10 | 0.122145E+10 |
June | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.484504E+10 | 0.780912E+09 |
July | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.516950E+10 | 0.564780E+09 |
August | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.457003E+10 | 0.731845E+09 |
September | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.333119E+10 | 0.109227E+10 |
October | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.183349E+10 | 0.171925E+10 |
November | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.707302E+09 | 0.216878E+10 |
December | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.243981E+09 | 0.344349E+10 |
Annual Sum or Average | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.309137E+11 | 0.223225E+11 |
Minimum of Months | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.243981E+09 | 0.564780E+09 |
Maximum of Months | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.516950E+10 | 0.350757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.339075E+10 | 0.494391E+10 |
February | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.344379E+10 | 0.438719E+10 |
March | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.572109E+10 | 0.361284E+10 |
April | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.478326E+10 | 0.278424E+10 |
May | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.468010E+10 | 0.199151E+10 |
June | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.491142E+10 | 0.126758E+10 |
July | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.573924E+10 | 0.913783E+09 |
August | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.634662E+10 | 0.117225E+10 |
September | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.659616E+10 | 0.175637E+10 |
October | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.567153E+10 | 0.265448E+10 |
November | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.346246E+10 | 0.323294E+10 |
December | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.268715E+10 | 0.485346E+10 |
Annual Sum or Average | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.574336E+11 | 0.335705E+11 |
Minimum of Months | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.268715E+10 | 0.913783E+09 |
Maximum of Months | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.659616E+10 | 0.494391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.286366E+09 | 0.364589E+10 |
February | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.647537E+09 | 0.309961E+10 |
March | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.207883E+10 | 0.245949E+10 |
April | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.289270E+10 | 0.177942E+10 |
May | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.408939E+10 | 0.129513E+10 |
June | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535198E+10 | 0.853496E+09 |
July | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.527398E+10 | 0.626593E+09 |
August | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.469735E+10 | 0.784756E+09 |
September | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.320955E+10 | 0.114950E+10 |
October | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.165016E+10 | 0.177997E+10 |
November | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.653296E+09 | 0.221178E+10 |
December | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.276031E+09 | 0.349825E+10 |
Annual Sum or Average | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.311072E+11 | 0.231839E+11 |
Minimum of Months | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.276031E+09 | 0.626593E+09 |
Maximum of Months | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535198E+10 | 0.364589E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324154E+09 | 0.00 | 0.324154E+09 | 2405270.15 | 0.197724E+10 |
February | 0.446093E+09 | 0.00 | 0.446093E+09 | 26376590.56 | 0.167096E+10 |
March | 0.598947E+09 | 0.00 | 0.598947E+09 | 0.209004E+09 | 0.131689E+10 |
April | 0.738563E+09 | 2947159.07 | 0.735616E+09 | 0.427920E+09 | 0.892758E+09 |
May | 0.886780E+09 | 37604498.19 | 0.849175E+09 | 0.734796E+09 | 0.583043E+09 |
June | 0.103220E+10 | 87866326.22 | 0.944336E+09 | 0.113396E+10 | 0.377462E+09 |
July | 0.989422E+09 | 63869394.40 | 0.925552E+09 | 0.125236E+10 | 0.273321E+09 |
August | 0.856125E+09 | 13024079.41 | 0.843101E+09 | 0.101626E+10 | 0.373735E+09 |
September | 0.630512E+09 | 130993.15 | 0.630381E+09 | 0.569675E+09 | 0.605822E+09 |
October | 0.487046E+09 | 0.00 | 0.487046E+09 | 0.227718E+09 | 0.100404E+10 |
November | 0.316725E+09 | 0.00 | 0.316725E+09 | 63045432.55 | 0.124085E+10 |
December | 0.303398E+09 | 0.00 | 0.303398E+09 | 3960713.00 | 0.192403E+10 |
Annual Sum or Average | 0.760997E+10 | 0.205442E+09 | 0.740452E+10 | 0.566748E+10 | 0.122402E+11 |
Minimum of Months | 0.303398E+09 | 0.00 | 0.303398E+09 | 2405270.15 | 0.273321E+09 |
Maximum of Months | 0.103220E+10 | 87866326.22 | 0.944336E+09 | 0.125236E+10 | 0.197724E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324166E+09 | 0.00 | 0.324166E+09 | 2404649.57 | 0.197737E+10 |
February | 0.446109E+09 | 0.00 | 0.446109E+09 | 26373492.26 | 0.167107E+10 |
March | 0.598971E+09 | 0.00 | 0.598971E+09 | 0.209005E+09 | 0.131698E+10 |
April | 0.738592E+09 | 2947238.29 | 0.735645E+09 | 0.427928E+09 | 0.892815E+09 |
May | 0.886815E+09 | 37605509.01 | 0.849210E+09 | 0.734819E+09 | 0.583079E+09 |
June | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.113400E+10 | 0.377484E+09 |
July | 0.989461E+09 | 63871111.23 | 0.925590E+09 | 0.125241E+10 | 0.273336E+09 |
August | 0.856159E+09 | 13024429.50 | 0.843134E+09 | 0.101630E+10 | 0.373756E+09 |
September | 0.630537E+09 | 130996.67 | 0.630406E+09 | 0.569695E+09 | 0.605858E+09 |
October | 0.487064E+09 | 0.00 | 0.487064E+09 | 0.227721E+09 | 0.100410E+10 |
November | 0.316737E+09 | 0.00 | 0.316737E+09 | 63044798.39 | 0.124093E+10 |
December | 0.303409E+09 | 0.00 | 0.303409E+09 | 3960281.43 | 0.192415E+10 |
Annual Sum or Average | 0.761026E+10 | 0.205448E+09 | 0.740482E+10 | 0.566766E+10 | 0.122409E+11 |
Minimum of Months | 0.303409E+09 | 0.00 | 0.303409E+09 | 2404649.57 | 0.273336E+09 |
Maximum of Months | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.125241E+10 | 0.197737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324166E+09 | 0.00 | 0.324166E+09 | 2404649.57 | 0.197737E+10 |
February | 0.446109E+09 | 0.00 | 0.446109E+09 | 26373492.26 | 0.167107E+10 |
March | 0.598971E+09 | 0.00 | 0.598971E+09 | 0.209005E+09 | 0.131698E+10 |
April | 0.738592E+09 | 2947238.29 | 0.735645E+09 | 0.427928E+09 | 0.892815E+09 |
May | 0.886815E+09 | 37605509.01 | 0.849210E+09 | 0.734819E+09 | 0.583079E+09 |
June | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.113400E+10 | 0.377484E+09 |
July | 0.989461E+09 | 63871111.23 | 0.925590E+09 | 0.125241E+10 | 0.273336E+09 |
August | 0.856159E+09 | 13024429.50 | 0.843134E+09 | 0.101630E+10 | 0.373756E+09 |
September | 0.630537E+09 | 130996.67 | 0.630406E+09 | 0.569695E+09 | 0.605858E+09 |
October | 0.487064E+09 | 0.00 | 0.487064E+09 | 0.227721E+09 | 0.100410E+10 |
November | 0.316737E+09 | 0.00 | 0.316737E+09 | 63044798.39 | 0.124093E+10 |
December | 0.303409E+09 | 0.00 | 0.303409E+09 | 3960281.43 | 0.192415E+10 |
Annual Sum or Average | 0.761026E+10 | 0.205448E+09 | 0.740482E+10 | 0.566766E+10 | 0.122409E+11 |
Minimum of Months | 0.303409E+09 | 0.00 | 0.303409E+09 | 2404649.57 | 0.273336E+09 |
Maximum of Months | 0.103224E+10 | 87868688.09 | 0.944375E+09 | 0.125241E+10 | 0.197737E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114132E+10 | 0.368023E+09 | 0.773295E+09 | 0.444791E+09 | 0.347378E+10 |
February | 0.151260E+10 | 0.453892E+09 | 0.105871E+10 | 0.724059E+09 | 0.296779E+10 |
March | 0.240309E+10 | 0.100640E+10 | 0.139670E+10 | 0.192342E+10 | 0.236450E+10 |
April | 0.307804E+10 | 0.136004E+10 | 0.171800E+10 | 0.293626E+10 | 0.168247E+10 |
May | 0.356346E+10 | 0.157630E+10 | 0.198716E+10 | 0.391360E+10 | 0.118527E+10 |
June | 0.385141E+10 | 0.170213E+10 | 0.214928E+10 | 0.470545E+10 | 0.767013E+09 |
July | 0.382164E+10 | 0.168261E+10 | 0.213903E+10 | 0.501303E+10 | 0.554876E+09 |
August | 0.345136E+10 | 0.144869E+10 | 0.200267E+10 | 0.441859E+10 | 0.740993E+09 |
September | 0.277948E+10 | 0.123287E+10 | 0.154662E+10 | 0.319910E+10 | 0.114704E+10 |
October | 0.194898E+10 | 0.806147E+09 | 0.114283E+10 | 0.171746E+10 | 0.185708E+10 |
November | 0.106983E+10 | 0.343189E+09 | 0.726645E+09 | 0.651335E+09 | 0.229348E+10 |
December | 0.889981E+09 | 0.183888E+09 | 0.706092E+09 | 0.226796E+09 | 0.348045E+10 |
Annual Sum or Average | 0.295112E+11 | 0.121642E+11 | 0.173470E+11 | 0.298739E+11 | 0.225147E+11 |
Minimum of Months | 0.889981E+09 | 0.183888E+09 | 0.706092E+09 | 0.226796E+09 | 0.554876E+09 |
Maximum of Months | 0.385141E+10 | 0.170213E+10 | 0.214928E+10 | 0.501303E+10 | 0.348045E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45126691.54 | 14551315.80 | 30575375.73 | 17586648.80 | 0.137350E+09 |
February | 59806742.31 | 17946463.36 | 41860278.95 | 28628638.31 | 0.117344E+09 |
March | 95016148.63 | 39792019.63 | 55224129.00 | 76050174.21 | 93490376.51 |
April | 0.121703E+09 | 53774767.72 | 67928318.11 | 0.116097E+09 | 66523243.40 |
May | 0.140896E+09 | 62325660.64 | 78570500.95 | 0.154740E+09 | 46864550.16 |
June | 0.152281E+09 | 67300549.10 | 84980731.10 | 0.186049E+09 | 30327001.91 |
July | 0.151104E+09 | 66528845.45 | 84575443.71 | 0.198211E+09 | 21939286.22 |
August | 0.136464E+09 | 57279803.41 | 79183956.05 | 0.174707E+09 | 29298196.02 |
September | 0.109898E+09 | 48746454.24 | 61151775.08 | 0.126489E+09 | 45353078.11 |
October | 77060880.03 | 31874343.11 | 45186536.92 | 67906950.83 | 73427257.43 |
November | 42300300.33 | 13569398.48 | 28730901.85 | 25753212.25 | 90681955.16 |
December | 35189031.70 | 7270783.46 | 27918248.24 | 8967293.27 | 0.137614E+09 |
Annual Sum or Average | 0.116685E+10 | 0.480960E+09 | 0.685886E+09 | 0.118119E+10 | 0.890212E+09 |
Minimum of Months | 35189031.70 | 7270783.46 | 27918248.24 | 8967293.27 | 21939286.22 |
Maximum of Months | 0.152281E+09 | 67300549.10 | 84980731.10 | 0.198211E+09 | 0.137614E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139391E+10 | 0.813662E+09 | 0.580244E+09 | 0.115510E+10 | 0.167691E+10 |
February | 0.143748E+10 | 0.693137E+09 | 0.744340E+09 | 0.117816E+10 | 0.148490E+10 |
March | 0.194252E+10 | 0.109149E+10 | 0.851036E+09 | 0.195366E+10 | 0.124109E+10 |
April | 0.155682E+10 | 0.622108E+09 | 0.934716E+09 | 0.163444E+10 | 0.939271E+09 |
May | 0.140778E+10 | 0.408874E+09 | 0.998901E+09 | 0.160693E+10 | 0.651575E+09 |
June | 0.132378E+10 | 0.280513E+09 | 0.104327E+10 | 0.167241E+10 | 0.419815E+09 |
July | 0.139641E+10 | 0.338811E+09 | 0.105760E+10 | 0.193999E+10 | 0.305605E+09 |
August | 0.156770E+10 | 0.508283E+09 | 0.105941E+10 | 0.213251E+10 | 0.408996E+09 |
September | 0.176396E+10 | 0.859176E+09 | 0.904784E+09 | 0.220510E+10 | 0.639283E+09 |
October | 0.174411E+10 | 0.996265E+09 | 0.747843E+09 | 0.188696E+10 | 0.990785E+09 |
November | 0.120880E+10 | 0.682406E+09 | 0.526394E+09 | 0.114901E+10 | 0.118584E+10 |
December | 0.116558E+10 | 0.603240E+09 | 0.562342E+09 | 0.904909E+09 | 0.168080E+10 |
Annual Sum or Average | 0.179088E+11 | 0.789796E+10 | 0.100109E+11 | 0.194192E+11 | 0.116249E+11 |
Minimum of Months | 0.116558E+10 | 0.280513E+09 | 0.526394E+09 | 0.904909E+09 | 0.305605E+09 |
Maximum of Months | 0.194252E+10 | 0.109149E+10 | 0.105941E+10 | 0.220510E+10 | 0.168080E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139391E+10 | 0.813662E+09 | 0.580244E+09 | 0.115510E+10 | 0.167691E+10 |
February | 0.143748E+10 | 0.693137E+09 | 0.744340E+09 | 0.117816E+10 | 0.148490E+10 |
March | 0.194252E+10 | 0.109149E+10 | 0.851036E+09 | 0.195366E+10 | 0.124109E+10 |
April | 0.155682E+10 | 0.622108E+09 | 0.934716E+09 | 0.163444E+10 | 0.939271E+09 |
May | 0.140778E+10 | 0.408874E+09 | 0.998901E+09 | 0.160693E+10 | 0.651575E+09 |
June | 0.132378E+10 | 0.280513E+09 | 0.104327E+10 | 0.167241E+10 | 0.419815E+09 |
July | 0.139641E+10 | 0.338811E+09 | 0.105760E+10 | 0.193999E+10 | 0.305605E+09 |
August | 0.156770E+10 | 0.508283E+09 | 0.105941E+10 | 0.213251E+10 | 0.408996E+09 |
September | 0.176396E+10 | 0.859176E+09 | 0.904784E+09 | 0.220510E+10 | 0.639283E+09 |
October | 0.174411E+10 | 0.996265E+09 | 0.747843E+09 | 0.188696E+10 | 0.990785E+09 |
November | 0.120880E+10 | 0.682406E+09 | 0.526394E+09 | 0.114901E+10 | 0.118584E+10 |
December | 0.116558E+10 | 0.603240E+09 | 0.562342E+09 | 0.904909E+09 | 0.168080E+10 |
Annual Sum or Average | 0.179088E+11 | 0.789796E+10 | 0.100109E+11 | 0.194192E+11 | 0.116249E+11 |
Minimum of Months | 0.116558E+10 | 0.280513E+09 | 0.526394E+09 | 0.904909E+09 | 0.305605E+09 |
Maximum of Months | 0.194252E+10 | 0.109149E+10 | 0.105941E+10 | 0.220510E+10 | 0.168080E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139382E+10 | 0.813611E+09 | 0.580207E+09 | 0.115503E+10 | 0.167681E+10 |
February | 0.143739E+10 | 0.693093E+09 | 0.744293E+09 | 0.117808E+10 | 0.148481E+10 |
March | 0.194240E+10 | 0.109142E+10 | 0.850982E+09 | 0.195354E+10 | 0.124101E+10 |
April | 0.155673E+10 | 0.622069E+09 | 0.934657E+09 | 0.163434E+10 | 0.939212E+09 |
May | 0.140769E+10 | 0.408848E+09 | 0.998838E+09 | 0.160683E+10 | 0.651534E+09 |
June | 0.132370E+10 | 0.280495E+09 | 0.104320E+10 | 0.167230E+10 | 0.419789E+09 |
July | 0.139632E+10 | 0.338790E+09 | 0.105753E+10 | 0.193987E+10 | 0.305586E+09 |
August | 0.156760E+10 | 0.508251E+09 | 0.105935E+10 | 0.213238E+10 | 0.408970E+09 |
September | 0.176385E+10 | 0.859121E+09 | 0.904727E+09 | 0.220496E+10 | 0.639242E+09 |
October | 0.174400E+10 | 0.996202E+09 | 0.747796E+09 | 0.188684E+10 | 0.990722E+09 |
November | 0.120872E+10 | 0.682363E+09 | 0.526360E+09 | 0.114894E+10 | 0.118576E+10 |
December | 0.116551E+10 | 0.603202E+09 | 0.562306E+09 | 0.904852E+09 | 0.168070E+10 |
Annual Sum or Average | 0.179077E+11 | 0.789746E+10 | 0.100102E+11 | 0.194180E+11 | 0.116241E+11 |
Minimum of Months | 0.116551E+10 | 0.280495E+09 | 0.526360E+09 | 0.904852E+09 | 0.305586E+09 |
Maximum of Months | 0.194240E+10 | 0.109142E+10 | 0.105935E+10 | 0.220496E+10 | 0.168070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.979234E+09 | 0.229885E+09 | 0.749349E+09 | 0.276795E+09 | 0.359540E+10 |
February | 0.143348E+10 | 0.368414E+09 | 0.106507E+10 | 0.632875E+09 | 0.306014E+10 |
March | 0.248745E+10 | 0.106506E+10 | 0.142238E+10 | 0.204648E+10 | 0.243516E+10 |
April | 0.294730E+10 | 0.120851E+10 | 0.173879E+10 | 0.283147E+10 | 0.175650E+10 |
May | 0.359270E+10 | 0.162366E+10 | 0.196904E+10 | 0.399238E+10 | 0.126427E+10 |
June | 0.419487E+10 | 0.197309E+10 | 0.222179E+10 | 0.519635E+10 | 0.849745E+09 |
July | 0.387539E+10 | 0.169910E+10 | 0.217629E+10 | 0.511536E+10 | 0.622356E+09 |
August | 0.350506E+10 | 0.149038E+10 | 0.201468E+10 | 0.453807E+10 | 0.802116E+09 |
September | 0.266377E+10 | 0.115036E+10 | 0.151341E+10 | 0.307971E+10 | 0.121055E+10 |
October | 0.178434E+10 | 0.628545E+09 | 0.115580E+10 | 0.155084E+10 | 0.191353E+10 |
November | 0.102330E+10 | 0.294877E+09 | 0.728420E+09 | 0.606375E+09 | 0.233243E+10 |
December | 0.916678E+09 | 0.199733E+09 | 0.716944E+09 | 0.261726E+09 | 0.352895E+10 |
Annual Sum or Average | 0.294036E+11 | 0.119316E+11 | 0.174720E+11 | 0.301284E+11 | 0.233711E+11 |
Minimum of Months | 0.916678E+09 | 0.199733E+09 | 0.716944E+09 | 0.261726E+09 | 0.622356E+09 |
Maximum of Months | 0.419487E+10 | 0.197309E+10 | 0.222179E+10 | 0.519635E+10 | 0.359540E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38717917.76 | 9089412.29 | 29628505.47 | 10944159.25 | 0.142159E+09 |
February | 56678404.17 | 14566707.70 | 42111696.47 | 25023151.90 | 0.120995E+09 |
March | 98351102.73 | 42111491.08 | 56239611.65 | 80915588.02 | 96283883.76 |
April | 0.116533E+09 | 47783122.10 | 68750079.23 | 0.111953E+09 | 69450276.94 |
May | 0.142052E+09 | 64197993.46 | 77853845.79 | 0.157855E+09 | 49987941.95 |
June | 0.165861E+09 | 78013909.58 | 87847222.32 | 0.205459E+09 | 33598148.25 |
July | 0.153229E+09 | 67180589.64 | 86048435.07 | 0.202256E+09 | 24607372.19 |
August | 0.138587E+09 | 58928107.66 | 79658462.03 | 0.179431E+09 | 31714928.64 |
September | 0.105323E+09 | 45484091.01 | 59838578.33 | 0.121769E+09 | 47864108.86 |
October | 70551039.24 | 24852018.57 | 45699020.67 | 61318741.89 | 75659219.89 |
November | 40460141.23 | 11659124.40 | 28801016.83 | 23975399.42 | 92222354.60 |
December | 36244509.01 | 7897243.42 | 28347265.59 | 10348350.30 | 0.139532E+09 |
Annual Sum or Average | 0.116259E+10 | 0.471764E+09 | 0.690824E+09 | 0.119125E+10 | 0.924074E+09 |
Minimum of Months | 36244509.01 | 7897243.42 | 28347265.59 | 10348350.30 | 24607372.19 |
Maximum of Months | 0.165861E+09 | 78013909.58 | 87847222.32 | 0.205459E+09 | 0.142159E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972507E+09 | 0.00 | 0.972507E+09 | 7017951.95 | 0.600601E+10 |
February | 0.133834E+10 | 0.00 | 0.133834E+10 | 69578708.36 | 0.508827E+10 |
March | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.561276E+09 | 0.411448E+10 |
April | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.116016E+10 | 0.285463E+10 |
May | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.204431E+10 | 0.190301E+10 |
June | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.331092E+10 | 0.119564E+10 |
July | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.368995E+10 | 0.864698E+09 |
August | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.300983E+10 | 0.114938E+10 |
September | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.168497E+10 | 0.182261E+10 |
October | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.678946E+09 | 0.296184E+10 |
November | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.187763E+09 | 0.367580E+10 |
December | 0.910238E+09 | 0.00 | 0.910238E+09 | 11501808.47 | 0.575592E+10 |
Annual Sum or Average | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.164162E+11 | 0.373923E+11 |
Minimum of Months | 0.910238E+09 | 0.00 | 0.910238E+09 | 7017951.95 | 0.864698E+09 |
Maximum of Months | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.368995E+10 | 0.600601E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.451049E+09 | 0.364129E+10 |
February | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.730358E+09 | 0.311646E+10 |
March | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.193720E+10 | 0.252092E+10 |
April | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.298348E+10 | 0.179414E+10 |
May | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.399636E+10 | 0.127714E+10 |
June | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.484679E+10 | 0.806174E+09 |
July | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.517860E+10 | 0.578791E+09 |
August | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.457286E+10 | 0.757832E+09 |
September | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.331564E+10 | 0.115303E+10 |
October | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.179065E+10 | 0.185205E+10 |
November | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.677417E+09 | 0.232984E+10 |
December | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.232127E+09 | 0.360389E+10 |
Annual Sum or Average | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.307125E+11 | 0.234316E+11 |
Minimum of Months | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.232127E+09 | 0.578791E+09 |
Maximum of Months | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.517860E+10 | 0.364129E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.335311E+10 | 0.514872E+10 |
February | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.340284E+10 | 0.457037E+10 |
March | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.567427E+10 | 0.381561E+10 |
April | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.474061E+10 | 0.294924E+10 |
May | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.466159E+10 | 0.209650E+10 |
June | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.491441E+10 | 0.131947E+10 |
July | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.575308E+10 | 0.943388E+09 |
August | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.635206E+10 | 0.122012E+10 |
September | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.657888E+10 | 0.186000E+10 |
October | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.560969E+10 | 0.286600E+10 |
November | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.340616E+10 | 0.348109E+10 |
December | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.264645E+10 | 0.509010E+10 |
Annual Sum or Average | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.570931E+11 | 0.353606E+11 |
Minimum of Months | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.264645E+10 | 0.943388E+09 |
Maximum of Months | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.657888E+10 | 0.514872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.277334E+09 | 0.377997E+10 |
February | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.632151E+09 | 0.322002E+10 |
March | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.205677E+10 | 0.259450E+10 |
April | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.286525E+10 | 0.188588E+10 |
May | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.407385E+10 | 0.136345E+10 |
June | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535493E+10 | 0.887610E+09 |
July | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.528324E+10 | 0.646727E+09 |
August | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.469844E+10 | 0.816682E+09 |
September | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.319160E+10 | 0.122147E+10 |
October | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.161222E+10 | 0.192422E+10 |
November | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.627738E+09 | 0.237801E+10 |
December | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.265835E+09 | 0.365838E+10 |
Annual Sum or Average | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.309394E+11 | 0.243769E+11 |
Minimum of Months | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.265835E+09 | 0.646727E+09 |
Maximum of Months | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.535493E+10 | 0.377997E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.41 | 2162.74 | 363.09 | 0.00 | 363.09 | 0.00 | 0.00 |
February | 35.85 | 2023.71 | 553.22 | 0.00 | 553.22 | 0.00 | 0.00 |
March | 219.88 | 1456.90 | 670.90 | 0.00 | 670.90 | 0.00 | 0.00 |
April | 466.20 | 1035.96 | 854.86 | 3.41 | 851.45 | 0.00 | 0.00 |
May | 776.03 | 675.21 | 993.30 | 42.12 | 951.18 | 0.00 | 0.00 |
June | 1279.36 | 445.71 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
July | 1374.42 | 314.48 | 1108.28 | 71.54 | 1036.73 | 0.00 | 0.00 |
August | 1124.46 | 413.27 | 958.97 | 14.59 | 944.38 | 0.00 | 0.00 |
September | 660.17 | 661.00 | 729.79 | 0.15 | 729.64 | 0.00 | 0.00 |
October | 275.07 | 1018.66 | 545.55 | 0.00 | 545.55 | 0.00 | 0.00 |
November | 84.75 | 1314.71 | 366.60 | 0.00 | 366.60 | 0.00 | 0.00 |
December | 6.17 | 2052.88 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 528.61 | 1126.86 | 723.97 | 19.54 | 704.42 | 0.00 | 0.00 |
Minimum of Months | 5.41 | 314.48 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1374.42 | 2162.74 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.82 | 1309.58 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 311.48 | 1239.67 | 649.98 | 195.04 | 454.94 | 0.00 | 0.00 |
March | 734.64 | 893.51 | 932.70 | 390.61 | 542.09 | 0.00 | 0.00 |
April | 1163.62 | 655.83 | 1234.49 | 545.46 | 689.03 | 0.00 | 0.00 |
May | 1497.28 | 456.04 | 1383.07 | 611.81 | 771.26 | 0.00 | 0.00 |
June | 1869.23 | 301.28 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
July | 1930.07 | 210.86 | 1483.28 | 653.07 | 830.21 | 0.00 | 0.00 |
August | 1706.25 | 273.24 | 1339.56 | 562.27 | 777.29 | 0.00 | 0.00 |
September | 1285.18 | 421.40 | 1114.75 | 494.46 | 620.29 | 0.00 | 0.00 |
October | 684.55 | 641.89 | 756.45 | 312.89 | 443.56 | 0.00 | 0.00 |
November | 272.88 | 836.72 | 429.07 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 91.09 | 1285.65 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 980.27 | 707.84 | 972.81 | 400.98 | 571.83 | 0.00 | 0.00 |
Minimum of Months | 91.09 | 210.86 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1930.07 | 1309.58 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1265.96 | 1845.84 | 1561.30 | 911.38 | 649.92 | 0.00 | 0.00 |
February | 1423.52 | 1813.49 | 1782.62 | 859.56 | 923.05 | 0.00 | 0.00 |
March | 2136.01 | 1348.88 | 2175.80 | 1222.57 | 953.23 | 0.00 | 0.00 |
April | 1845.39 | 1074.17 | 1801.91 | 720.05 | 1081.86 | 0.00 | 0.00 |
May | 1747.35 | 743.54 | 1576.83 | 457.98 | 1118.85 | 0.00 | 0.00 |
June | 1894.84 | 489.03 | 1532.17 | 324.67 | 1207.49 | 0.00 | 0.00 |
July | 2142.79 | 341.17 | 1564.10 | 379.50 | 1184.59 | 0.00 | 0.00 |
August | 2369.56 | 437.67 | 1755.95 | 569.32 | 1186.63 | 0.00 | 0.00 |
September | 2544.82 | 677.61 | 2041.65 | 994.44 | 1047.22 | 0.00 | 0.00 |
October | 2117.51 | 991.07 | 1953.56 | 1115.91 | 837.65 | 0.00 | 0.00 |
November | 1335.82 | 1247.27 | 1399.10 | 789.84 | 609.26 | 0.00 | 0.00 |
December | 1003.27 | 1812.07 | 1305.56 | 675.69 | 629.87 | 0.00 | 0.00 |
Annual Sum or Average | 1821.21 | 1064.51 | 1703.68 | 751.34 | 952.34 | 0.00 | 0.00 |
Minimum of Months | 1003.27 | 341.17 | 1305.56 | 324.67 | 609.26 | 0.00 | 0.00 |
Maximum of Months | 2544.82 | 1845.84 | 2175.80 | 1222.57 | 1207.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 106.92 | 1361.22 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 267.67 | 1281.25 | 615.98 | 158.31 | 457.67 | 0.00 | 0.00 |
March | 776.14 | 918.27 | 965.44 | 413.38 | 552.06 | 0.00 | 0.00 |
April | 1116.01 | 686.50 | 1182.05 | 484.69 | 697.36 | 0.00 | 0.00 |
May | 1526.80 | 483.55 | 1394.42 | 630.19 | 764.23 | 0.00 | 0.00 |
June | 2064.81 | 329.28 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
July | 1969.08 | 233.94 | 1504.13 | 659.46 | 844.67 | 0.00 | 0.00 |
August | 1753.79 | 292.99 | 1360.40 | 578.46 | 781.94 | 0.00 | 0.00 |
September | 1238.25 | 443.48 | 1068.34 | 461.37 | 606.97 | 0.00 | 0.00 |
October | 616.10 | 664.57 | 692.55 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 252.04 | 853.31 | 410.41 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 103.06 | 1306.10 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 986.40 | 735.16 | 969.26 | 393.32 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 103.06 | 233.94 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2064.81 | 1361.22 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.69 | 2214.74 | 363.08 | 0.00 | 363.08 | 0.00 | 0.00 |
February | 32.71 | 2072.21 | 553.20 | 0.00 | 553.20 | 0.00 | 0.00 |
March | 234.10 | 1475.08 | 670.88 | 0.00 | 670.88 | 0.00 | 0.00 |
April | 495.28 | 1033.33 | 854.84 | 3.41 | 851.43 | 0.00 | 0.00 |
May | 823.04 | 653.08 | 993.28 | 42.12 | 951.16 | 0.00 | 0.00 |
June | 1312.49 | 436.89 | 1194.71 | 101.70 | 1093.01 | 0.00 | 0.00 |
July | 1402.77 | 306.15 | 1108.25 | 71.54 | 1036.71 | 0.00 | 0.00 |
August | 1138.31 | 418.63 | 958.95 | 14.59 | 944.36 | 0.00 | 0.00 |
September | 659.36 | 701.21 | 729.78 | 0.15 | 729.63 | 0.00 | 0.00 |
October | 255.06 | 1124.64 | 545.54 | 0.00 | 545.54 | 0.00 | 0.00 |
November | 72.97 | 1436.24 | 366.59 | 0.00 | 366.59 | 0.00 | 0.00 |
December | 4.44 | 2155.14 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 539.16 | 1164.45 | 723.95 | 19.54 | 704.41 | 0.00 | 0.00 |
Minimum of Months | 2.69 | 306.15 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1402.77 | 2214.74 | 1194.71 | 101.70 | 1093.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 172.63 | 1348.24 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 311.13 | 1275.27 | 649.97 | 195.04 | 454.93 | 0.00 | 0.00 |
March | 746.52 | 917.71 | 932.69 | 390.60 | 542.09 | 0.00 | 0.00 |
April | 1177.61 | 674.76 | 1234.47 | 545.45 | 689.02 | 0.00 | 0.00 |
May | 1518.95 | 460.03 | 1383.05 | 611.79 | 771.26 | 0.00 | 0.00 |
June | 1887.15 | 307.62 | 1544.63 | 682.65 | 861.98 | 0.00 | 0.00 |
July | 1945.66 | 215.36 | 1483.25 | 653.05 | 830.20 | 0.00 | 0.00 |
August | 1714.94 | 287.59 | 1339.54 | 562.26 | 777.28 | 0.00 | 0.00 |
September | 1283.02 | 460.03 | 1114.73 | 494.45 | 620.28 | 0.00 | 0.00 |
October | 666.58 | 720.77 | 756.44 | 312.88 | 443.56 | 0.00 | 0.00 |
November | 261.22 | 919.81 | 429.06 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 88.02 | 1350.83 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 984.75 | 742.17 | 972.79 | 400.97 | 571.82 | 0.00 | 0.00 |
Minimum of Months | 88.02 | 215.36 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1945.66 | 1350.83 | 1544.63 | 682.65 | 861.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1293.77 | 1878.22 | 1561.24 | 911.34 | 649.90 | 0.00 | 0.00 |
February | 1460.98 | 1841.36 | 1782.55 | 859.53 | 923.02 | 0.00 | 0.00 |
March | 2188.20 | 1390.08 | 2175.72 | 1222.52 | 953.20 | 0.00 | 0.00 |
April | 1891.68 | 1087.10 | 1801.84 | 720.02 | 1081.82 | 0.00 | 0.00 |
May | 1799.84 | 729.80 | 1576.78 | 457.96 | 1118.82 | 0.00 | 0.00 |
June | 1935.62 | 485.89 | 1532.12 | 324.66 | 1207.46 | 0.00 | 0.00 |
July | 2172.88 | 342.29 | 1564.05 | 379.49 | 1184.56 | 0.00 | 0.00 |
August | 2388.52 | 458.10 | 1755.89 | 569.30 | 1186.59 | 0.00 | 0.00 |
September | 2552.15 | 739.90 | 2041.58 | 994.40 | 1047.18 | 0.00 | 0.00 |
October | 2113.49 | 1109.73 | 1953.48 | 1115.86 | 837.62 | 0.00 | 0.00 |
November | 1329.85 | 1372.47 | 1399.04 | 789.81 | 609.24 | 0.00 | 0.00 |
December | 1013.54 | 1882.58 | 1305.51 | 675.66 | 629.85 | 0.00 | 0.00 |
Annual Sum or Average | 1847.30 | 1105.84 | 1703.62 | 751.31 | 952.31 | 0.00 | 0.00 |
Minimum of Months | 1013.54 | 342.29 | 1305.51 | 324.66 | 609.24 | 0.00 | 0.00 |
Maximum of Months | 2552.15 | 1882.58 | 2175.72 | 1222.52 | 1207.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.43 | 1395.44 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 271.95 | 1314.95 | 615.97 | 158.31 | 457.66 | 0.00 | 0.00 |
March | 794.28 | 945.13 | 965.43 | 413.37 | 552.05 | 0.00 | 0.00 |
April | 1135.58 | 704.45 | 1182.03 | 484.68 | 697.35 | 0.00 | 0.00 |
May | 1549.52 | 490.69 | 1394.40 | 630.18 | 764.22 | 0.00 | 0.00 |
June | 2084.03 | 340.80 | 1682.38 | 791.32 | 891.06 | 0.00 | 0.00 |
July | 1985.37 | 241.55 | 1504.11 | 659.45 | 844.66 | 0.00 | 0.00 |
August | 1761.31 | 311.32 | 1360.38 | 578.45 | 781.94 | 0.00 | 0.00 |
September | 1235.14 | 485.50 | 1068.32 | 461.36 | 606.96 | 0.00 | 0.00 |
October | 601.91 | 742.68 | 692.54 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 243.19 | 935.44 | 410.40 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 101.58 | 1369.66 | 355.78 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 993.14 | 770.40 | 969.25 | 393.31 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 101.58 | 241.55 | 355.78 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2084.03 | 1395.44 | 1682.38 | 791.32 | 891.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.62 | 2242.39 | 363.09 | 0.00 | 363.09 | 0.00 | 0.00 |
February | 28.76 | 2103.29 | 553.22 | 0.00 | 553.22 | 0.00 | 0.00 |
March | 209.56 | 1536.17 | 670.90 | 0.00 | 670.90 | 0.00 | 0.00 |
April | 447.59 | 1101.32 | 854.86 | 3.41 | 851.45 | 0.00 | 0.00 |
May | 763.26 | 710.50 | 993.30 | 42.12 | 951.18 | 0.00 | 0.00 |
June | 1277.36 | 461.28 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
July | 1377.67 | 322.84 | 1108.28 | 71.54 | 1036.73 | 0.00 | 0.00 |
August | 1123.74 | 429.13 | 958.97 | 14.59 | 944.38 | 0.00 | 0.00 |
September | 650.07 | 703.17 | 729.79 | 0.15 | 729.64 | 0.00 | 0.00 |
October | 253.49 | 1105.83 | 545.55 | 0.00 | 545.55 | 0.00 | 0.00 |
November | 72.44 | 1418.13 | 366.60 | 0.00 | 366.60 | 0.00 | 0.00 |
December | 4.29 | 2149.01 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Annual Sum or Average | 520.56 | 1185.70 | 723.97 | 19.54 | 704.42 | 0.00 | 0.00 |
Minimum of Months | 2.62 | 322.84 | 339.84 | 0.00 | 339.84 | 0.00 | 0.00 |
Maximum of Months | 1377.67 | 2242.39 | 1194.74 | 101.70 | 1093.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.40 | 1359.50 | 442.97 | 142.84 | 300.13 | 0.00 | 0.00 |
February | 301.90 | 1288.22 | 649.98 | 195.04 | 454.94 | 0.00 | 0.00 |
March | 723.27 | 941.20 | 932.70 | 390.61 | 542.09 | 0.00 | 0.00 |
April | 1151.03 | 692.18 | 1234.49 | 545.46 | 689.03 | 0.00 | 0.00 |
May | 1492.07 | 476.83 | 1383.07 | 611.81 | 771.26 | 0.00 | 0.00 |
June | 1869.90 | 311.02 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
July | 1933.47 | 216.10 | 1483.28 | 653.07 | 830.21 | 0.00 | 0.00 |
August | 1707.31 | 282.94 | 1339.56 | 562.27 | 777.29 | 0.00 | 0.00 |
September | 1279.18 | 444.84 | 1114.75 | 494.46 | 620.29 | 0.00 | 0.00 |
October | 668.55 | 691.48 | 756.45 | 312.89 | 443.56 | 0.00 | 0.00 |
November | 261.35 | 898.86 | 429.07 | 137.64 | 291.43 | 0.00 | 0.00 |
December | 86.67 | 1345.54 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Annual Sum or Average | 973.89 | 743.01 | 972.81 | 400.98 | 571.83 | 0.00 | 0.00 |
Minimum of Months | 86.67 | 216.10 | 345.42 | 71.37 | 274.05 | 0.00 | 0.00 |
Maximum of Months | 1933.47 | 1359.50 | 1544.66 | 682.66 | 861.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1251.91 | 1922.31 | 1561.30 | 911.38 | 649.92 | 0.00 | 0.00 |
February | 1406.60 | 1889.21 | 1782.62 | 859.56 | 923.05 | 0.00 | 0.00 |
March | 2118.53 | 1424.58 | 2175.80 | 1222.57 | 953.23 | 0.00 | 0.00 |
April | 1828.94 | 1137.82 | 1801.91 | 720.05 | 1081.86 | 0.00 | 0.00 |
May | 1740.44 | 782.75 | 1576.83 | 457.98 | 1118.85 | 0.00 | 0.00 |
June | 1895.99 | 509.05 | 1532.17 | 324.67 | 1207.49 | 0.00 | 0.00 |
July | 2147.95 | 352.22 | 1564.10 | 379.50 | 1184.59 | 0.00 | 0.00 |
August | 2371.59 | 455.54 | 1755.95 | 569.32 | 1186.63 | 0.00 | 0.00 |
September | 2538.15 | 717.59 | 2041.65 | 994.44 | 1047.22 | 0.00 | 0.00 |
October | 2094.42 | 1070.04 | 1953.56 | 1115.91 | 837.65 | 0.00 | 0.00 |
November | 1314.10 | 1343.01 | 1399.10 | 789.84 | 609.26 | 0.00 | 0.00 |
December | 988.07 | 1900.43 | 1305.56 | 675.69 | 629.87 | 0.00 | 0.00 |
Annual Sum or Average | 1810.41 | 1121.28 | 1703.68 | 751.34 | 952.34 | 0.00 | 0.00 |
Minimum of Months | 988.07 | 352.22 | 1305.56 | 324.67 | 609.26 | 0.00 | 0.00 |
Maximum of Months | 2538.15 | 1922.31 | 2175.80 | 1222.57 | 1207.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.54 | 1411.28 | 380.06 | 89.22 | 290.84 | 0.00 | 0.00 |
February | 261.31 | 1331.03 | 615.98 | 158.31 | 457.67 | 0.00 | 0.00 |
March | 767.91 | 968.68 | 965.44 | 413.38 | 552.06 | 0.00 | 0.00 |
April | 1105.42 | 727.58 | 1182.05 | 484.69 | 697.36 | 0.00 | 0.00 |
May | 1521.00 | 509.05 | 1394.42 | 630.19 | 764.23 | 0.00 | 0.00 |
June | 2065.94 | 342.44 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
July | 1972.54 | 241.46 | 1504.13 | 659.46 | 844.67 | 0.00 | 0.00 |
August | 1754.20 | 304.91 | 1360.40 | 578.46 | 781.94 | 0.00 | 0.00 |
September | 1231.33 | 471.25 | 1068.34 | 461.37 | 606.97 | 0.00 | 0.00 |
October | 601.93 | 718.42 | 692.55 | 243.95 | 448.59 | 0.00 | 0.00 |
November | 242.18 | 917.44 | 410.41 | 118.26 | 292.14 | 0.00 | 0.00 |
December | 99.25 | 1365.88 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Annual Sum or Average | 981.08 | 772.99 | 969.26 | 393.32 | 575.94 | 0.00 | 0.00 |
Minimum of Months | 99.25 | 241.46 | 355.79 | 77.52 | 278.26 | 0.00 | 0.00 |
Maximum of Months | 2065.94 | 1411.28 | 1682.40 | 791.33 | 891.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14494714.19 | 0.579267E+10 | 0.972507E+09 | 0.00 | 0.972507E+09 | 0.00 | 0.00 |
February | 86730637.51 | 0.489575E+10 | 0.133834E+10 | 0.00 | 0.133834E+10 | 0.00 | 0.00 |
March | 0.588922E+09 | 0.390215E+10 | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.00 | 0.00 |
April | 0.120839E+10 | 0.268520E+10 | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.00 | 0.00 |
May | 0.207852E+10 | 0.180847E+10 | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.00 | 0.00 |
June | 0.331611E+10 | 0.115528E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
July | 0.368123E+10 | 0.842314E+09 | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.00 | 0.00 |
August | 0.301175E+10 | 0.110691E+10 | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.00 | 0.00 |
September | 0.171115E+10 | 0.171330E+10 | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.00 | 0.00 |
October | 0.736760E+09 | 0.272838E+10 | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.00 | 0.00 |
November | 0.219667E+09 | 0.340772E+10 | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.00 | 0.00 |
December | 16534796.67 | 0.549844E+10 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166703E+11 | 0.355366E+11 | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.00 | 0.00 |
Minimum of Months | 14494714.19 | 0.842314E+09 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368123E+10 | 0.579267E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.465548E+09 | 0.350757E+10 | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.00 | 0.00 |
February | 0.753539E+09 | 0.299900E+10 | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.00 | 0.00 |
March | 0.196766E+10 | 0.239319E+10 | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.00 | 0.00 |
April | 0.301610E+10 | 0.169992E+10 | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.00 | 0.00 |
May | 0.401031E+10 | 0.122145E+10 | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.00 | 0.00 |
June | 0.484504E+10 | 0.780912E+09 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
July | 0.516950E+10 | 0.564780E+09 | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.00 | 0.00 |
August | 0.457003E+10 | 0.731845E+09 | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.00 | 0.00 |
September | 0.333119E+10 | 0.109227E+10 | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.00 | 0.00 |
October | 0.183349E+10 | 0.171925E+10 | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.00 | 0.00 |
November | 0.707302E+09 | 0.216878E+10 | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.00 | 0.00 |
December | 0.243981E+09 | 0.344349E+10 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309137E+11 | 0.223225E+11 | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243981E+09 | 0.564780E+09 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.516950E+10 | 0.350757E+10 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.339075E+10 | 0.494391E+10 | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.00 | 0.00 |
February | 0.344379E+10 | 0.438719E+10 | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.00 | 0.00 |
March | 0.572109E+10 | 0.361284E+10 | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.00 | 0.00 |
April | 0.478326E+10 | 0.278424E+10 | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.00 | 0.00 |
May | 0.468010E+10 | 0.199151E+10 | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.00 | 0.00 |
June | 0.491142E+10 | 0.126758E+10 | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.00 | 0.00 |
July | 0.573924E+10 | 0.913783E+09 | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.00 | 0.00 |
August | 0.634662E+10 | 0.117225E+10 | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.00 | 0.00 |
September | 0.659616E+10 | 0.175637E+10 | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.00 | 0.00 |
October | 0.567153E+10 | 0.265448E+10 | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.00 | 0.00 |
November | 0.346246E+10 | 0.323294E+10 | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.00 | 0.00 |
December | 0.268715E+10 | 0.485346E+10 | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574336E+11 | 0.335705E+11 | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268715E+10 | 0.913783E+09 | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.659616E+10 | 0.494391E+10 | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286366E+09 | 0.364589E+10 | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.00 | 0.00 |
February | 0.647537E+09 | 0.309961E+10 | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.00 | 0.00 |
March | 0.207883E+10 | 0.245949E+10 | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.00 | 0.00 |
April | 0.289270E+10 | 0.177942E+10 | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.00 | 0.00 |
May | 0.408939E+10 | 0.129513E+10 | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.00 | 0.00 |
June | 0.535198E+10 | 0.853496E+09 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
July | 0.527398E+10 | 0.626593E+09 | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.00 | 0.00 |
August | 0.469735E+10 | 0.784756E+09 | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.00 | 0.00 |
September | 0.320955E+10 | 0.114950E+10 | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.00 | 0.00 |
October | 0.165016E+10 | 0.177997E+10 | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.00 | 0.00 |
November | 0.653296E+09 | 0.221178E+10 | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.00 | 0.00 |
December | 0.276031E+09 | 0.349825E+10 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311072E+11 | 0.231839E+11 | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276031E+09 | 0.626593E+09 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535198E+10 | 0.364589E+10 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7214569.28 | 0.593197E+10 | 0.972485E+09 | 0.00 | 0.972485E+09 | 0.00 | 0.00 |
February | 79123575.07 | 0.501310E+10 | 0.133831E+10 | 0.00 | 0.133831E+10 | 0.00 | 0.00 |
March | 0.627014E+09 | 0.395085E+10 | 0.179689E+10 | 0.00 | 0.179689E+10 | 0.00 | 0.00 |
April | 0.128378E+10 | 0.267839E+10 | 0.221575E+10 | 8841635.65 | 0.220691E+10 | 0.00 | 0.00 |
May | 0.220443E+10 | 0.174920E+10 | 0.266041E+10 | 0.112816E+09 | 0.254759E+10 | 0.00 | 0.00 |
June | 0.340197E+10 | 0.113243E+10 | 0.309669E+10 | 0.263604E+09 | 0.283309E+10 | 0.00 | 0.00 |
July | 0.375718E+10 | 0.819994E+09 | 0.296834E+10 | 0.191612E+09 | 0.277673E+10 | 0.00 | 0.00 |
August | 0.304885E+10 | 0.112125E+10 | 0.256844E+10 | 39072938.42 | 0.252937E+10 | 0.00 | 0.00 |
September | 0.170906E+10 | 0.181754E+10 | 0.189159E+10 | 392986.49 | 0.189119E+10 | 0.00 | 0.00 |
October | 0.683160E+09 | 0.301225E+10 | 0.146117E+10 | 0.00 | 0.146117E+10 | 0.00 | 0.00 |
November | 0.189135E+09 | 0.372272E+10 | 0.950199E+09 | 0.00 | 0.950199E+09 | 0.00 | 0.00 |
December | 11881275.87 | 0.577233E+10 | 0.910216E+09 | 0.00 | 0.910216E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170028E+11 | 0.367220E+11 | 0.228305E+11 | 0.616338E+09 | 0.222142E+11 | 0.00 | 0.00 |
Minimum of Months | 7214569.28 | 0.819994E+09 | 0.910216E+09 | 0.00 | 0.910216E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375718E+10 | 0.593197E+10 | 0.309669E+10 | 0.263604E+09 | 0.283309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462378E+09 | 0.361113E+10 | 0.118644E+10 | 0.382575E+09 | 0.803870E+09 | 0.00 | 0.00 |
February | 0.752688E+09 | 0.308513E+10 | 0.157240E+10 | 0.471838E+09 | 0.110057E+10 | 0.00 | 0.00 |
March | 0.199947E+10 | 0.245799E+10 | 0.249811E+10 | 0.104619E+10 | 0.145192E+10 | 0.00 | 0.00 |
April | 0.305236E+10 | 0.174899E+10 | 0.319975E+10 | 0.141382E+10 | 0.178593E+10 | 0.00 | 0.00 |
May | 0.406834E+10 | 0.123214E+10 | 0.370436E+10 | 0.163863E+10 | 0.206573E+10 | 0.00 | 0.00 |
June | 0.489150E+10 | 0.797340E+09 | 0.400369E+10 | 0.176943E+10 | 0.223426E+10 | 0.00 | 0.00 |
July | 0.521124E+10 | 0.576815E+09 | 0.397275E+10 | 0.174914E+10 | 0.222361E+10 | 0.00 | 0.00 |
August | 0.459329E+10 | 0.770291E+09 | 0.358783E+10 | 0.150597E+10 | 0.208186E+10 | 0.00 | 0.00 |
September | 0.332559E+10 | 0.119240E+10 | 0.288938E+10 | 0.128161E+10 | 0.160777E+10 | 0.00 | 0.00 |
October | 0.178537E+10 | 0.193051E+10 | 0.202604E+10 | 0.838022E+09 | 0.118802E+10 | 0.00 | 0.00 |
November | 0.677089E+09 | 0.238416E+10 | 0.111213E+10 | 0.356759E+09 | 0.755376E+09 | 0.00 | 0.00 |
December | 0.235763E+09 | 0.361806E+10 | 0.925170E+09 | 0.191159E+09 | 0.734010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.310551E+11 | 0.234049E+11 | 0.306781E+11 | 0.126451E+11 | 0.180329E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235763E+09 | 0.576815E+09 | 0.925170E+09 | 0.191159E+09 | 0.734010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521124E+10 | 0.361806E+10 | 0.400369E+10 | 0.176943E+10 | 0.223426E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.346523E+10 | 0.503063E+10 | 0.418163E+10 | 0.244094E+10 | 0.174069E+10 | 0.00 | 0.00 |
February | 0.353440E+10 | 0.445462E+10 | 0.431234E+10 | 0.207937E+10 | 0.223297E+10 | 0.00 | 0.00 |
March | 0.586086E+10 | 0.372318E+10 | 0.582745E+10 | 0.327439E+10 | 0.255305E+10 | 0.00 | 0.00 |
April | 0.490323E+10 | 0.281775E+10 | 0.467038E+10 | 0.186628E+10 | 0.280409E+10 | 0.00 | 0.00 |
May | 0.482070E+10 | 0.195468E+10 | 0.422324E+10 | 0.122660E+10 | 0.299664E+10 | 0.00 | 0.00 |
June | 0.501712E+10 | 0.125942E+10 | 0.397126E+10 | 0.841520E+09 | 0.312974E+10 | 0.00 | 0.00 |
July | 0.581985E+10 | 0.916795E+09 | 0.418914E+10 | 0.101641E+10 | 0.317273E+10 | 0.00 | 0.00 |
August | 0.639741E+10 | 0.122696E+10 | 0.470299E+10 | 0.152482E+10 | 0.317817E+10 | 0.00 | 0.00 |
September | 0.661516E+10 | 0.191781E+10 | 0.529177E+10 | 0.257747E+10 | 0.271430E+10 | 0.00 | 0.00 |
October | 0.566076E+10 | 0.297229E+10 | 0.523221E+10 | 0.298873E+10 | 0.224348E+10 | 0.00 | 0.00 |
November | 0.344697E+10 | 0.355743E+10 | 0.362632E+10 | 0.204718E+10 | 0.157915E+10 | 0.00 | 0.00 |
December | 0.271467E+10 | 0.504231E+10 | 0.349667E+10 | 0.180968E+10 | 0.168699E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.582564E+11 | 0.348739E+11 | 0.537254E+11 | 0.236934E+11 | 0.300320E+11 | 0.00 | 0.00 |
Minimum of Months | 0.271467E+10 | 0.916795E+09 | 0.349667E+10 | 0.841520E+09 | 0.157915E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661516E+10 | 0.504231E+10 | 0.582745E+10 | 0.327439E+10 | 0.317817E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287739E+09 | 0.373755E+10 | 0.101795E+10 | 0.238974E+09 | 0.778977E+09 | 0.00 | 0.00 |
February | 0.657898E+09 | 0.318113E+10 | 0.149016E+10 | 0.382981E+09 | 0.110718E+10 | 0.00 | 0.00 |
March | 0.212739E+10 | 0.253144E+10 | 0.258580E+10 | 0.110717E+10 | 0.147862E+10 | 0.00 | 0.00 |
April | 0.294343E+10 | 0.182595E+10 | 0.306383E+10 | 0.125629E+10 | 0.180754E+10 | 0.00 | 0.00 |
May | 0.415023E+10 | 0.131425E+10 | 0.373475E+10 | 0.168786E+10 | 0.204689E+10 | 0.00 | 0.00 |
June | 0.540181E+10 | 0.883343E+09 | 0.436074E+10 | 0.205110E+10 | 0.230963E+10 | 0.00 | 0.00 |
July | 0.531762E+10 | 0.646963E+09 | 0.402862E+10 | 0.176628E+10 | 0.226234E+10 | 0.00 | 0.00 |
August | 0.471751E+10 | 0.833831E+09 | 0.364365E+10 | 0.154931E+10 | 0.209434E+10 | 0.00 | 0.00 |
September | 0.320148E+10 | 0.125842E+10 | 0.276909E+10 | 0.119585E+10 | 0.157324E+10 | 0.00 | 0.00 |
October | 0.161216E+10 | 0.198919E+10 | 0.185489E+10 | 0.653397E+09 | 0.120149E+10 | 0.00 | 0.00 |
November | 0.630350E+09 | 0.242466E+10 | 0.106376E+10 | 0.306536E+09 | 0.757221E+09 | 0.00 | 0.00 |
December | 0.272075E+09 | 0.366848E+10 | 0.952922E+09 | 0.207630E+09 | 0.745292E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313197E+11 | 0.242952E+11 | 0.305662E+11 | 0.124034E+11 | 0.181628E+11 | 0.00 | 0.00 |
Minimum of Months | 0.272075E+09 | 0.646963E+09 | 0.952922E+09 | 0.207630E+09 | 0.745292E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540181E+10 | 0.373755E+10 | 0.436074E+10 | 0.205110E+10 | 0.230963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7017951.95 | 0.600601E+10 | 0.972507E+09 | 0.00 | 0.972507E+09 | 0.00 | 0.00 |
February | 69578708.36 | 0.508827E+10 | 0.133834E+10 | 0.00 | 0.133834E+10 | 0.00 | 0.00 |
March | 0.561276E+09 | 0.411448E+10 | 0.179693E+10 | 0.00 | 0.179693E+10 | 0.00 | 0.00 |
April | 0.116016E+10 | 0.285463E+10 | 0.221579E+10 | 8841895.54 | 0.220695E+10 | 0.00 | 0.00 |
May | 0.204431E+10 | 0.190301E+10 | 0.266046E+10 | 0.112819E+09 | 0.254765E+10 | 0.00 | 0.00 |
June | 0.331092E+10 | 0.119564E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
July | 0.368995E+10 | 0.864698E+09 | 0.296841E+10 | 0.191617E+09 | 0.277679E+10 | 0.00 | 0.00 |
August | 0.300983E+10 | 0.114938E+10 | 0.256850E+10 | 39074086.91 | 0.252942E+10 | 0.00 | 0.00 |
September | 0.168497E+10 | 0.182261E+10 | 0.189163E+10 | 392998.04 | 0.189123E+10 | 0.00 | 0.00 |
October | 0.678946E+09 | 0.296184E+10 | 0.146121E+10 | 0.00 | 0.146121E+10 | 0.00 | 0.00 |
November | 0.187763E+09 | 0.367580E+10 | 0.950221E+09 | 0.00 | 0.950221E+09 | 0.00 | 0.00 |
December | 11501808.47 | 0.575592E+10 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.164162E+11 | 0.373923E+11 | 0.228310E+11 | 0.616357E+09 | 0.222146E+11 | 0.00 | 0.00 |
Minimum of Months | 7017951.95 | 0.864698E+09 | 0.910238E+09 | 0.00 | 0.910238E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368995E+10 | 0.600601E+10 | 0.309675E+10 | 0.263611E+09 | 0.283314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451049E+09 | 0.364129E+10 | 0.118646E+10 | 0.382582E+09 | 0.803882E+09 | 0.00 | 0.00 |
February | 0.730358E+09 | 0.311646E+10 | 0.157243E+10 | 0.471847E+09 | 0.110058E+10 | 0.00 | 0.00 |
March | 0.193720E+10 | 0.252092E+10 | 0.249815E+10 | 0.104621E+10 | 0.145194E+10 | 0.00 | 0.00 |
April | 0.298348E+10 | 0.179414E+10 | 0.319980E+10 | 0.141384E+10 | 0.178595E+10 | 0.00 | 0.00 |
May | 0.399636E+10 | 0.127714E+10 | 0.370442E+10 | 0.163866E+10 | 0.206575E+10 | 0.00 | 0.00 |
June | 0.484679E+10 | 0.806174E+09 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
July | 0.517860E+10 | 0.578791E+09 | 0.397281E+10 | 0.174917E+10 | 0.222364E+10 | 0.00 | 0.00 |
August | 0.457286E+10 | 0.757832E+09 | 0.358788E+10 | 0.150600E+10 | 0.208188E+10 | 0.00 | 0.00 |
September | 0.331564E+10 | 0.115303E+10 | 0.288943E+10 | 0.128164E+10 | 0.160779E+10 | 0.00 | 0.00 |
October | 0.179065E+10 | 0.185205E+10 | 0.202607E+10 | 0.838038E+09 | 0.118803E+10 | 0.00 | 0.00 |
November | 0.677417E+09 | 0.232984E+10 | 0.111215E+10 | 0.356766E+09 | 0.755387E+09 | 0.00 | 0.00 |
December | 0.232127E+09 | 0.360389E+10 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.307125E+11 | 0.234316E+11 | 0.306785E+11 | 0.126454E+11 | 0.180332E+11 | 0.00 | 0.00 |
Minimum of Months | 0.232127E+09 | 0.578791E+09 | 0.925184E+09 | 0.191163E+09 | 0.734021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517860E+10 | 0.364129E+10 | 0.400375E+10 | 0.176946E+10 | 0.223429E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335311E+10 | 0.514872E+10 | 0.418179E+10 | 0.244104E+10 | 0.174076E+10 | 0.00 | 0.00 |
February | 0.340284E+10 | 0.457037E+10 | 0.431251E+10 | 0.207945E+10 | 0.223305E+10 | 0.00 | 0.00 |
March | 0.567427E+10 | 0.381561E+10 | 0.582767E+10 | 0.327453E+10 | 0.255314E+10 | 0.00 | 0.00 |
April | 0.474061E+10 | 0.294924E+10 | 0.467054E+10 | 0.186636E+10 | 0.280418E+10 | 0.00 | 0.00 |
May | 0.466159E+10 | 0.209650E+10 | 0.422338E+10 | 0.122665E+10 | 0.299673E+10 | 0.00 | 0.00 |
June | 0.491441E+10 | 0.131947E+10 | 0.397138E+10 | 0.841555E+09 | 0.312983E+10 | 0.00 | 0.00 |
July | 0.575308E+10 | 0.943388E+09 | 0.418927E+10 | 0.101645E+10 | 0.317282E+10 | 0.00 | 0.00 |
August | 0.635206E+10 | 0.122012E+10 | 0.470315E+10 | 0.152488E+10 | 0.317827E+10 | 0.00 | 0.00 |
September | 0.657888E+10 | 0.186000E+10 | 0.529196E+10 | 0.257758E+10 | 0.271438E+10 | 0.00 | 0.00 |
October | 0.560969E+10 | 0.286600E+10 | 0.523241E+10 | 0.298886E+10 | 0.224356E+10 | 0.00 | 0.00 |
November | 0.340616E+10 | 0.348109E+10 | 0.362646E+10 | 0.204726E+10 | 0.157920E+10 | 0.00 | 0.00 |
December | 0.264645E+10 | 0.509010E+10 | 0.349681E+10 | 0.180976E+10 | 0.168705E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.570931E+11 | 0.353606E+11 | 0.537273E+11 | 0.236944E+11 | 0.300330E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264645E+10 | 0.943388E+09 | 0.349681E+10 | 0.841555E+09 | 0.157920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657888E+10 | 0.514872E+10 | 0.582767E+10 | 0.327453E+10 | 0.317827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277334E+09 | 0.377997E+10 | 0.101796E+10 | 0.238978E+09 | 0.778987E+09 | 0.00 | 0.00 |
February | 0.632151E+09 | 0.322002E+10 | 0.149018E+10 | 0.382987E+09 | 0.110719E+10 | 0.00 | 0.00 |
March | 0.205677E+10 | 0.259450E+10 | 0.258583E+10 | 0.110719E+10 | 0.147864E+10 | 0.00 | 0.00 |
April | 0.286525E+10 | 0.188588E+10 | 0.306387E+10 | 0.125631E+10 | 0.180756E+10 | 0.00 | 0.00 |
May | 0.407385E+10 | 0.136345E+10 | 0.373480E+10 | 0.168789E+10 | 0.204691E+10 | 0.00 | 0.00 |
June | 0.535493E+10 | 0.887610E+09 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
July | 0.528324E+10 | 0.646727E+09 | 0.402867E+10 | 0.176631E+10 | 0.226236E+10 | 0.00 | 0.00 |
August | 0.469844E+10 | 0.816682E+09 | 0.364369E+10 | 0.154933E+10 | 0.209436E+10 | 0.00 | 0.00 |
September | 0.319160E+10 | 0.122147E+10 | 0.276913E+10 | 0.119586E+10 | 0.157326E+10 | 0.00 | 0.00 |
October | 0.161222E+10 | 0.192422E+10 | 0.185492E+10 | 0.653408E+09 | 0.120151E+10 | 0.00 | 0.00 |
November | 0.627738E+09 | 0.237801E+10 | 0.106377E+10 | 0.306541E+09 | 0.757230E+09 | 0.00 | 0.00 |
December | 0.265835E+09 | 0.365838E+10 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309394E+11 | 0.243769E+11 | 0.305666E+11 | 0.124036E+11 | 0.181630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265835E+09 | 0.646727E+09 | 0.952935E+09 | 0.207634E+09 | 0.745301E+09 | 0.00 | 0.00 |
Maximum of Months | 0.535493E+10 | 0.377997E+10 | 0.436079E+10 | 0.205114E+10 | 0.230966E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.522658E+10 | -0.497663E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -249957330.6 | 60.05 | 0.00 | 0.00 |
February | 0.481066E+10 | -0.458711E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -223549142.6 | 60.05 | 0.00 | 0.00 |
March | 0.559740E+10 | -0.535740E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -239998403.5 | 60.05 | 0.00 | 0.00 |
April | 0.486294E+10 | -0.463455E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -228382867.9 | 60.05 | 0.00 | 0.00 |
May | 0.492882E+10 | -0.469578E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233043934.6 | 60.05 | 0.00 | 0.00 |
June | 0.460661E+10 | -0.438171E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224899328.0 | 60.05 | 0.00 | 0.00 |
July | 0.416262E+10 | -0.393131E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231311456.7 | 60.05 | 0.00 | 0.00 |
August | 0.449996E+10 | -0.426810E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231865254.4 | 60.05 | 0.00 | 0.00 |
September | 0.413535E+10 | -0.391085E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224499037.5 | 60.05 | 0.00 | 0.00 |
October | 0.447049E+10 | -0.423621E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234274621.1 | 60.05 | 0.00 | 0.00 |
November | 0.465977E+10 | -0.442963E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -230141198.5 | 60.05 | 0.00 | 0.00 |
December | 0.488857E+10 | -0.464342E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245151494.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.568498E+11 | -0.540527E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.279707E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.413535E+10 | -0.535740E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -249957330.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.559740E+10 | -0.391085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -223549142.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 4433.29 | 32.59 | 236.17 | 250.83 | 3566.29 | 33.72 | 243.00 | 224.00 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5564.35 | 32.78 | 246.33 | 256.17 | 1866.82 | 27.01 | 241.00 | 237.67 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7947.08 | 29.83 | 255.00 | 326.83 | 1507.88 | 21.82 | 190.67 | 294.33 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 2081.46 | 18.78 | 3.33 | 346.00 | 1170.02 | 20.97 | 201.17 | 311.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1886.02 | 18.85 | 0.50 | 384.00 | 1112.42 | 21.11 | 184.33 | 337.83 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:19 | 1699.30 | 18.65 | 0.00 | 393.17 | 979.10 | 20.87 | 224.50 | 353.83 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1782.64 | 18.68 | 1.00 | 400.00 | 1013.05 | 20.90 | 221.17 | 355.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2114.15 | 19.16 | 4.67 | 377.50 | 1176.23 | 21.37 | 254.00 | 338.17 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3016.72 | 20.65 | 33.33 | 324.33 | 1551.94 | 22.00 | 220.33 | 292.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 6431.02 | 32.23 | 277.67 | 298.33 | 1587.10 | 22.41 | 196.83 | 277.00 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 4171.27 | 32.39 | 240.50 | 240.67 | 1696.42 | 27.89 | 219.17 | 217.33 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3736.40 | 31.21 | 209.17 | 239.17 | 2926.26 | 33.09 | 223.33 | 208.67 |
Annual Sum or Average | 3928.50 | 0.51 | 3536.63 | 24.43 | 1507.67 | 3837.00 | 1557.93 | 23.67 | 2619.50 | 3448.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1699.30 | 18.65 | 0.00 | 239.17 | 979.10 | 20.87 | 184.33 | 208.67 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7947.08 | 32.78 | 277.67 | 400.00 | 3566.29 | 33.72 | 254.00 | 355.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:20 | 1522.75 | 20.83 | 70.83 | 236.17 | 762.65 | 21.58 | 84.00 | 188.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 2105.02 | 21.98 | 83.33 | 248.33 | 1093.83 | 22.84 | 112.00 | 217.17 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2836.87 | 21.68 | 104.50 | 320.00 | 1249.85 | 22.42 | 90.17 | 285.33 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 3080.93 | 21.10 | 104.33 | 350.50 | 1728.75 | 22.37 | 88.17 | 315.17 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4115.81 | 22.59 | 103.50 | 392.17 | 1749.47 | 22.35 | 59.00 | 347.67 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3743.24 | 21.83 | 133.33 | 403.17 | 1649.07 | 22.09 | 79.17 | 372.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3539.47 | 21.98 | 135.17 | 409.83 | 1561.57 | 22.10 | 81.00 | 372.00 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3260.65 | 21.37 | 110.50 | 379.00 | 1456.79 | 22.33 | 77.33 | 345.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3322.93 | 22.82 | 85.83 | 323.83 | 1832.09 | 23.79 | 102.00 | 288.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2106.25 | 20.82 | 81.67 | 288.67 | 1140.59 | 22.66 | 95.00 | 254.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1533.72 | 21.15 | 87.00 | 230.00 | 842.21 | 21.98 | 91.33 | 178.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1312.48 | 20.10 | 60.33 | 226.17 | 659.48 | 21.06 | 69.17 | 173.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2857.60 | 21.57 | 1160.33 | 3807.83 | 1367.90 | 22.31 | 1028.33 | 3340.17 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1312.48 | 20.10 | 60.33 | 226.17 | 659.48 | 21.06 | 59.00 | 173.83 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 4115.81 | 22.82 | 135.17 | 409.83 | 1832.09 | 23.79 | 112.00 | 372.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-11:20 | 655.71 | 15.92 | 0.00 | 220.67 | 368.38 | 18.17 | 0.00 | 136.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 861.52 | 17.01 | 0.00 | 241.83 | 481.01 | 19.15 | 0.67 | 192.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 911.37 | 17.56 | 0.00 | 314.17 | 535.61 | 19.79 | 4.33 | 266.00 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1051.27 | 18.12 | 0.00 | 350.17 | 620.82 | 20.23 | 59.17 | 316.00 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1263.28 | 20.32 | 26.67 | 401.50 | 767.87 | 22.43 | 163.33 | 363.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1414.12 | 21.76 | 81.83 | 413.17 | 830.83 | 22.69 | 236.67 | 389.50 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1345.47 | 21.42 | 75.83 | 419.17 | 788.69 | 22.43 | 234.83 | 389.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1190.90 | 18.83 | 0.00 | 387.17 | 709.63 | 20.98 | 141.17 | 353.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 995.06 | 18.36 | 0.00 | 321.50 | 617.93 | 20.58 | 42.00 | 272.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 799.85 | 16.77 | 0.00 | 281.17 | 461.99 | 18.99 | 0.33 | 222.33 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:39 | 635.98 | 15.39 | 0.00 | 217.33 | 355.50 | 17.55 | 0.00 | 127.33 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:09 | 660.22 | 15.85 | 0.00 | 207.50 | 362.67 | 18.02 | 0.00 | 118.00 |
Annual Sum or Average | 3928.50 | 0.52 | 1031.30 | 18.48 | 184.33 | 3775.33 | 605.59 | 20.39 | 882.50 | 3147.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 635.98 | 15.39 | 0.00 | 207.50 | 355.50 | 17.55 | 0.00 | 118.00 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1414.12 | 21.76 | 81.83 | 419.17 | 830.83 | 22.69 | 236.67 | 389.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1426.64 | 21.27 | 86.00 | 235.83 | 778.22 | 22.23 | 87.00 | 189.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:50 | 1926.76 | 20.40 | 68.17 | 248.17 | 1043.01 | 22.71 | 97.50 | 217.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2785.35 | 21.52 | 101.67 | 322.00 | 1576.35 | 22.75 | 99.17 | 287.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 3297.10 | 20.86 | 104.67 | 346.17 | 1399.71 | 20.89 | 55.50 | 312.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3530.01 | 18.16 | 43.00 | 390.50 | 1955.61 | 18.89 | 0.17 | 353.83 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3733.17 | 17.92 | 52.83 | 400.83 | 1609.90 | 18.87 | 0.17 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3330.46 | 17.98 | 54.83 | 407.17 | 1516.01 | 19.05 | 6.17 | 371.00 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3117.58 | 19.92 | 85.50 | 382.83 | 1694.12 | 21.29 | 63.17 | 347.17 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3406.68 | 22.40 | 83.50 | 321.83 | 1506.43 | 22.19 | 69.17 | 290.33 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:20 | 1976.09 | 20.50 | 79.67 | 288.00 | 1061.45 | 22.43 | 91.67 | 254.17 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:39 | 1465.77 | 20.77 | 86.83 | 228.50 | 782.14 | 21.55 | 82.33 | 181.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:50 | 1356.11 | 19.74 | 56.33 | 221.67 | 729.02 | 21.71 | 72.17 | 173.67 |
Annual Sum or Average | 3928.50 | 0.51 | 2760.49 | 19.96 | 903.00 | 3793.50 | 1365.03 | 21.01 | 724.17 | 3348.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1356.11 | 17.92 | 43.00 | 221.67 | 729.02 | 18.87 | 0.17 | 173.67 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3733.17 | 22.40 | 104.67 | 407.17 | 1955.61 | 22.75 | 99.17 | 371.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:30 | 4299.04 | 32.13 | 233.33 | 248.83 | 3468.92 | 33.25 | 233.00 | 221.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5417.85 | 32.40 | 242.00 | 254.67 | 1764.78 | 24.98 | 107.00 | 236.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7807.59 | 28.72 | 235.00 | 325.67 | 1405.53 | 19.05 | 19.17 | 291.83 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 1982.02 | 14.93 | 0.00 | 343.83 | 1099.63 | 18.42 | 11.50 | 309.17 |
May | 332.17 | 0.52 | 0.48 | 01-MAY-06:49 | 1801.01 | 15.21 | 0.00 | 381.33 | 1054.42 | 18.78 | 3.83 | 333.17 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:30 | 1628.84 | 15.05 | 0.00 | 390.50 | 933.71 | 18.55 | 0.33 | 350.67 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1707.10 | 15.00 | 0.00 | 397.17 | 963.53 | 18.50 | 7.33 | 351.67 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2018.59 | 15.43 | 0.00 | 374.33 | 1111.23 | 18.91 | 18.83 | 334.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2875.13 | 17.10 | 17.00 | 321.83 | 1448.62 | 19.52 | 28.50 | 289.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:30 | 6296.77 | 31.63 | 270.67 | 297.50 | 1485.84 | 19.52 | 25.33 | 274.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:49 | 4051.33 | 32.05 | 237.67 | 239.50 | 1612.60 | 26.22 | 135.33 | 215.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3592.28 | 29.73 | 195.33 | 236.50 | 2838.77 | 32.70 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.51 | 3425.93 | 21.99 | 1431.00 | 3811.67 | 1480.80 | 21.50 | 807.00 | 3414.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1628.84 | 14.93 | 0.00 | 236.50 | 933.71 | 18.42 | 0.33 | 206.50 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7807.59 | 32.40 | 270.67 | 397.17 | 3468.92 | 33.25 | 233.00 | 351.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:30 | 1477.23 | 20.32 | 70.00 | 234.83 | 728.29 | 21.32 | 78.17 | 183.83 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-09:00 | 2005.24 | 20.24 | 69.33 | 246.50 | 1048.45 | 22.63 | 98.50 | 214.67 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:30 | 2755.43 | 21.12 | 103.17 | 317.50 | 1194.25 | 22.22 | 79.83 | 281.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2997.68 | 20.65 | 104.00 | 349.00 | 1663.95 | 22.18 | 83.00 | 312.33 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4019.07 | 22.14 | 103.50 | 389.83 | 1675.06 | 22.17 | 58.17 | 344.33 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3653.59 | 21.40 | 132.83 | 400.83 | 1582.25 | 21.91 | 76.83 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3450.61 | 21.54 | 135.17 | 406.83 | 1495.10 | 21.92 | 77.50 | 369.83 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3173.41 | 20.91 | 110.17 | 377.00 | 1389.67 | 22.15 | 69.50 | 343.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3229.69 | 22.36 | 85.83 | 322.33 | 1758.60 | 23.59 | 87.83 | 284.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2043.95 | 20.34 | 81.33 | 286.83 | 1091.91 | 22.44 | 84.50 | 249.83 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-07:40 | 1489.96 | 20.70 | 87.00 | 228.00 | 810.18 | 21.75 | 84.67 | 173.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1272.13 | 19.60 | 59.67 | 224.67 | 630.27 | 20.80 | 64.00 | 169.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2779.03 | 21.02 | 1142.00 | 3784.17 | 1310.61 | 22.11 | 942.50 | 3298.50 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1272.13 | 19.60 | 59.67 | 224.67 | 630.27 | 20.80 | 58.17 | 169.83 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 4019.07 | 22.36 | 135.17 | 406.83 | 1758.60 | 23.59 | 98.50 | 369.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.55 | 0.48 | 01-JAN-11:30 | 631.52 | 11.93 | 0.00 | 217.33 | 354.64 | 15.52 | 0.00 | 127.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 830.96 | 13.29 | 0.00 | 240.00 | 463.58 | 16.71 | 0.00 | 187.00 |
March | 339.33 | 0.52 | 0.48 | 01-MAR-08:39 | 879.34 | 14.04 | 0.00 | 311.50 | 518.04 | 17.55 | 0.00 | 259.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1019.92 | 14.67 | 0.00 | 349.50 | 600.63 | 18.11 | 0.17 | 310.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1219.44 | 17.21 | 26.17 | 399.83 | 743.96 | 20.55 | 40.67 | 359.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1364.42 | 18.96 | 74.50 | 411.83 | 802.49 | 20.68 | 71.33 | 386.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1298.16 | 18.57 | 71.00 | 418.17 | 761.88 | 20.41 | 62.50 | 386.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1148.56 | 15.42 | 0.00 | 385.50 | 686.24 | 18.92 | 12.17 | 350.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 958.85 | 15.24 | 0.00 | 319.33 | 598.71 | 18.74 | 0.00 | 267.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 771.20 | 13.09 | 0.00 | 278.67 | 446.03 | 16.59 | 0.00 | 215.50 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:50 | 612.75 | 11.46 | 0.00 | 214.67 | 342.29 | 14.91 | 0.00 | 119.83 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:20 | 636.12 | 11.82 | 0.00 | 205.00 | 348.79 | 15.33 | 0.00 | 109.50 |
Annual Sum or Average | 3928.50 | 0.52 | 995.24 | 15.08 | 171.67 | 3751.33 | 585.19 | 18.18 | 186.83 | 3080.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 612.75 | 11.46 | 0.00 | 205.00 | 342.29 | 14.91 | 0.00 | 109.50 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1364.42 | 18.96 | 74.50 | 418.17 | 802.49 | 20.68 | 71.33 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1387.24 | 20.90 | 85.00 | 233.33 | 749.39 | 22.12 | 85.67 | 183.17 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-11:20 | 1868.53 | 19.99 | 68.17 | 247.00 | 999.73 | 22.61 | 95.33 | 214.33 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2712.40 | 21.11 | 101.67 | 320.50 | 1517.41 | 22.62 | 95.83 | 284.50 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:40 | 3159.57 | 20.43 | 104.50 | 343.83 | 1339.77 | 20.74 | 53.67 | 309.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-07:10 | 3423.89 | 17.67 | 43.00 | 389.00 | 1862.82 | 18.73 | 0.00 | 349.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3586.28 | 17.43 | 52.67 | 399.33 | 1533.94 | 18.69 | 0.00 | 366.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3203.50 | 17.49 | 54.83 | 404.33 | 1447.36 | 18.87 | 3.83 | 369.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3031.18 | 19.47 | 85.50 | 380.17 | 1626.84 | 21.14 | 60.17 | 342.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3320.02 | 21.97 | 83.50 | 320.33 | 1436.48 | 22.05 | 65.67 | 288.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:30 | 1917.47 | 20.08 | 78.67 | 286.33 | 1016.74 | 22.31 | 90.00 | 251.67 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:50 | 1424.53 | 20.40 | 86.50 | 226.17 | 752.13 | 21.44 | 81.83 | 175.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1313.67 | 19.16 | 53.83 | 220.00 | 699.26 | 21.60 | 71.50 | 168.17 |
Annual Sum or Average | 3928.50 | 0.51 | 2670.28 | 19.51 | 897.83 | 3770.33 | 1306.27 | 20.87 | 703.50 | 3302.83 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1313.67 | 17.43 | 43.00 | 220.00 | 699.26 | 18.69 | 0.00 | 168.17 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3586.28 | 21.97 | 104.50 | 404.33 | 1862.82 | 22.62 | 95.83 | 369.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:30 | 4299.02 | 32.13 | 233.33 | 248.83 | 3468.82 | 33.25 | 233.00 | 221.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5417.76 | 32.40 | 242.00 | 254.67 | 1764.65 | 24.99 | 107.00 | 236.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7807.47 | 28.72 | 235.00 | 325.67 | 1405.42 | 19.05 | 19.17 | 291.83 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:10 | 1981.89 | 14.94 | 0.00 | 343.83 | 1099.54 | 18.42 | 11.50 | 309.17 |
May | 332.17 | 0.52 | 0.48 | 01-MAY-06:49 | 1800.92 | 15.21 | 0.00 | 381.33 | 1054.34 | 18.78 | 3.83 | 333.17 |
June | 430.67 | 0.52 | 0.48 | 01-JUN-06:30 | 1628.76 | 15.05 | 0.00 | 390.50 | 933.65 | 18.55 | 0.33 | 350.67 |
July | 439.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1707.00 | 15.01 | 0.00 | 397.17 | 963.45 | 18.50 | 7.33 | 351.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2018.46 | 15.43 | 0.00 | 374.33 | 1111.14 | 18.91 | 18.83 | 334.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2875.00 | 17.10 | 17.00 | 321.83 | 1448.51 | 19.52 | 28.50 | 289.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:30 | 6296.67 | 31.64 | 270.67 | 297.50 | 1485.73 | 19.52 | 25.33 | 274.83 |
November | 258.33 | 0.52 | 0.48 | 01-NOV-07:49 | 4051.28 | 32.05 | 237.67 | 239.50 | 1612.50 | 26.22 | 135.33 | 215.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3592.24 | 29.73 | 195.33 | 236.50 | 2838.67 | 32.70 | 216.83 | 206.50 |
Annual Sum or Average | 3928.50 | 0.51 | 3425.84 | 22.00 | 1431.00 | 3811.67 | 1480.71 | 21.50 | 807.00 | 3414.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1628.76 | 14.94 | 0.00 | 236.50 | 933.65 | 18.42 | 0.33 | 206.50 | |
Maximum of Months | 439.00 | 0.52 | 0.48 | 7807.47 | 32.40 | 270.67 | 397.17 | 3468.82 | 33.25 | 233.00 | 351.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:30 | 1477.19 | 20.32 | 70.00 | 234.83 | 728.24 | 21.32 | 78.17 | 183.83 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-09:00 | 2005.18 | 20.24 | 69.33 | 246.50 | 1048.38 | 22.63 | 98.50 | 214.67 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-07:30 | 2755.38 | 21.12 | 103.17 | 317.50 | 1194.18 | 22.22 | 79.83 | 281.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2997.62 | 20.65 | 104.00 | 349.00 | 1663.87 | 22.18 | 83.17 | 312.33 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-05:30 | 4019.01 | 22.14 | 103.50 | 389.83 | 1674.99 | 22.17 | 58.17 | 344.33 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3653.52 | 21.40 | 132.83 | 400.83 | 1582.18 | 21.92 | 76.83 | 369.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3450.54 | 21.54 | 135.17 | 406.83 | 1495.03 | 21.93 | 77.50 | 369.83 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3173.34 | 20.91 | 110.17 | 377.00 | 1389.59 | 22.15 | 69.50 | 343.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3229.64 | 22.36 | 85.83 | 322.33 | 1758.52 | 23.60 | 87.83 | 284.50 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2043.90 | 20.34 | 81.33 | 286.83 | 1091.85 | 22.44 | 84.50 | 249.83 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-07:40 | 1489.92 | 20.70 | 87.00 | 228.00 | 810.13 | 21.75 | 84.67 | 173.83 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-08:09 | 1272.08 | 19.60 | 59.67 | 224.67 | 630.22 | 20.80 | 64.00 | 169.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2778.97 | 21.02 | 1142.00 | 3784.17 | 1310.54 | 22.11 | 942.67 | 3298.33 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1272.08 | 19.60 | 59.67 | 224.67 | 630.22 | 20.80 | 58.17 | 169.83 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 4019.01 | 22.36 | 135.17 | 406.83 | 1758.52 | 23.60 | 98.50 | 369.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.55 | 0.48 | 01-JAN-11:30 | 631.49 | 11.93 | 0.00 | 217.33 | 354.62 | 15.52 | 0.00 | 127.67 |
February | 262.50 | 0.53 | 0.48 | 01-FEB-12:50 | 830.92 | 13.29 | 0.00 | 240.00 | 463.54 | 16.71 | 0.00 | 187.00 |
March | 339.33 | 0.52 | 0.48 | 01-MAR-08:39 | 879.31 | 14.05 | 0.00 | 311.50 | 518.00 | 17.56 | 0.00 | 259.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1019.88 | 14.67 | 0.00 | 349.50 | 600.59 | 18.12 | 0.17 | 310.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:10 | 1219.41 | 17.22 | 26.17 | 399.83 | 743.91 | 20.55 | 40.67 | 359.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1364.38 | 18.96 | 74.50 | 411.83 | 802.44 | 20.68 | 71.33 | 386.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1298.11 | 18.57 | 71.00 | 418.17 | 761.83 | 20.42 | 62.50 | 386.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1148.52 | 15.42 | 0.00 | 385.50 | 686.19 | 18.92 | 12.17 | 350.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 958.83 | 15.24 | 0.00 | 319.33 | 598.67 | 18.74 | 0.00 | 267.67 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 771.17 | 13.09 | 0.00 | 278.67 | 445.99 | 16.59 | 0.00 | 215.33 |
November | 258.33 | 0.56 | 0.48 | 01-NOV-08:50 | 612.72 | 11.46 | 0.00 | 214.67 | 342.26 | 14.91 | 0.00 | 119.67 |
December | 230.67 | 0.55 | 0.48 | 01-DEC-12:20 | 636.09 | 11.82 | 0.00 | 205.00 | 348.76 | 15.33 | 0.00 | 109.50 |
Annual Sum or Average | 3928.50 | 0.52 | 995.21 | 15.08 | 171.67 | 3751.33 | 585.15 | 18.18 | 186.83 | 3080.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 612.72 | 11.46 | 0.00 | 205.00 | 342.26 | 14.91 | 0.00 | 109.50 | |
Maximum of Months | 439.00 | 0.56 | 0.48 | 1364.38 | 18.96 | 74.50 | 418.17 | 802.44 | 20.68 | 71.33 | 386.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1387.20 | 20.90 | 85.00 | 233.33 | 749.34 | 22.12 | 85.67 | 183.17 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-11:20 | 1868.47 | 19.99 | 68.17 | 247.00 | 999.66 | 22.62 | 95.33 | 214.33 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 2712.35 | 21.11 | 101.67 | 320.50 | 1517.34 | 22.62 | 95.83 | 284.50 |
April | 371.17 | 0.52 | 0.48 | 01-APR-07:40 | 3159.50 | 20.43 | 104.50 | 343.83 | 1339.70 | 20.74 | 53.67 | 309.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-07:10 | 3423.84 | 17.67 | 43.00 | 389.00 | 1862.75 | 18.73 | 0.00 | 349.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3586.21 | 17.43 | 52.67 | 399.33 | 1533.86 | 18.69 | 0.00 | 366.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 3203.43 | 17.49 | 54.83 | 404.33 | 1447.29 | 18.88 | 4.00 | 369.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:49 | 3031.11 | 19.47 | 85.50 | 380.17 | 1626.76 | 21.14 | 60.17 | 342.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3319.98 | 21.97 | 83.50 | 320.33 | 1436.41 | 22.06 | 65.83 | 288.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:30 | 1917.42 | 20.08 | 78.67 | 286.33 | 1016.68 | 22.32 | 90.00 | 251.67 |
November | 258.33 | 0.54 | 0.48 | 01-NOV-08:50 | 1424.48 | 20.40 | 86.50 | 226.17 | 752.08 | 21.44 | 81.83 | 175.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1313.62 | 19.16 | 53.83 | 220.00 | 699.21 | 21.60 | 71.50 | 168.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2670.22 | 19.51 | 897.83 | 3770.33 | 1306.20 | 20.87 | 703.83 | 3302.67 | ||
Minimum of Months | 230.67 | 0.51 | 0.48 | 1313.62 | 17.43 | 43.00 | 220.00 | 699.21 | 18.69 | 0.00 | 168.00 | |
Maximum of Months | 439.00 | 0.54 | 0.48 | 3586.21 | 21.97 | 104.50 | 404.33 | 1862.75 | 22.62 | 95.83 | 369.17 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157754E+11 | 25090.92 | 04-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146313E+11 | 27542.26 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744826E+10 | 23582.64 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130370E+10 | 13017.48 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11536190.93 | 4708.02 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410626.21 | 5.39 | 12-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1102581.65 | 5.48 | 17-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 510569.31 | 5.54 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 117924.57 | 389.28 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486399E+09 | 10645.21 | 17-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276621E+10 | 12160.10 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132660E+11 | 27577.51 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 117924.57 | 5.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157754E+11 | 27577.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594418E+09 | 12367.15 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2214370.66 | 12332.34 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232849.89 | 3880.83 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594418E+09 | 12367.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.746846E+10 | 8843.63 | 03-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633943E+10 | 8919.66 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353818E+10 | 8838.63 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188700E+10 | 8896.67 | 24-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.697208E+09 | 8914.06 | 30-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157535E+09 | 8997.16 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10050598.00 | 4090.93 | 06-JUL-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32278430.15 | 5991.33 | 02-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207528E+09 | 8901.06 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.981297E+09 | 8909.31 | 06-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250472E+10 | 8828.18 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625527E+10 | 8934.09 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10050598.00 | 4090.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.746846E+10 | 8997.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328521E+10 | 6502.86 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258811E+10 | 6560.45 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.958087E+09 | 6487.41 | 09-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153486E+09 | 6482.96 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 948938.62 | 1372.06 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22924582.56 | 6471.89 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396688E+09 | 6489.17 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246752E+10 | 6571.40 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328521E+10 | 6571.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.518690E+10 | 7191.77 | 03-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429152E+10 | 7250.93 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222092E+10 | 7180.53 | 10-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.445046E+09 | 7176.00 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4966293.34 | 7060.71 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 50688901.35 | 7176.25 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.549803E+09 | 7175.92 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359379E+10 | 7263.09 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.518690E+10 | 7263.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.356126E+10 | 6668.82 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285049E+10 | 6728.09 | 07-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110111E+10 | 6649.53 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228461E+09 | 6646.23 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4291446.58 | 4152.81 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33822308.61 | 6636.96 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.447688E+09 | 6643.87 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255023E+10 | 6739.30 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356126E+10 | 6739.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166003E+11 | 24701.13 | 04-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153678E+11 | 29142.13 | 07-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.845237E+10 | 23372.54 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201647E+10 | 14062.59 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45009320.86 | 5997.34 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 414397.06 | 5.15 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 988471.57 | 5.07 | 21-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 470566.00 | 5.35 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7528764.03 | 1109.06 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101634E+10 | 11824.11 | 17-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420604E+10 | 13609.14 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143647E+11 | 28307.37 | 11-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 414397.06 | 5.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166003E+11 | 29142.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292504E+10 | 18074.41 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211769E+10 | 18049.19 | 01-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234332E+09 | 17990.76 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15839776.61 | 18024.47 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1388911.14 | 7800.64 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108541E+09 | 18025.31 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177344E+10 | 18065.24 | 19-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.717626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292504E+10 | 18074.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.341088E+10 | 9443.76 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.269659E+10 | 9441.03 | 10-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752734E+09 | 9442.00 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159379E+09 | 9426.48 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1435796.47 | 4287.95 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75344839.10 | 9408.55 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.575646E+09 | 9427.25 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289505E+10 | 9447.04 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341088E+10 | 9447.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.330113E+10 | 7117.24 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261124E+10 | 7115.54 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.872692E+09 | 7106.08 | 06-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124074E+09 | 7103.95 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 126563.38 | 736.47 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 779803.16 | 2096.21 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115685E+09 | 7106.07 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.775534E+09 | 7110.01 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292105E+10 | 7112.53 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.330113E+10 | 7117.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467757E+10 | 7677.84 | 03-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.379440E+10 | 7675.19 | 03-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145500E+10 | 7675.49 | 01-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191605E+09 | 7656.33 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119958E+09 | 7648.77 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779149E+09 | 7683.15 | 21-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379215E+10 | 7676.31 | 23-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467757E+10 | 7683.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345705E+10 | 7240.55 | 17-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276841E+10 | 7247.02 | 28-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100349E+10 | 7235.83 | 06-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197619E+09 | 7222.34 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2087150.20 | 3485.60 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1207109.57 | 1353.97 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134045E+09 | 7213.76 | 20-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787255E+09 | 7239.77 | 22-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290834E+10 | 7242.31 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345705E+10 | 7247.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175852E+11 | 26951.87 | 04-JAN-07:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161384E+11 | 28711.98 | 07-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870251E+10 | 27118.06 | 07-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227615E+10 | 16074.06 | 17-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96665924.65 | 7809.69 | 01-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2697012.01 | 1303.90 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 937648.78 | 5.90 | 21-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 389604.36 | 5.49 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29843532.96 | 2830.19 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133721E+10 | 14104.65 | 17-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.469152E+10 | 14985.37 | 24-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153095E+11 | 28416.81 | 11-DEC-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 389604.36 | 5.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175852E+11 | 28711.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.755149E+10 | 24678.78 | 18-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.617088E+10 | 24675.39 | 15-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206650E+10 | 24662.95 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313035E+09 | 24673.29 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215434E+09 | 24680.71 | 16-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140227E+10 | 24684.31 | 13-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.622784E+10 | 24691.13 | 14-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.755149E+10 | 24691.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.548263E+10 | 11157.09 | 19-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.463467E+10 | 11240.29 | 07-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183525E+10 | 11141.92 | 20-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.585807E+09 | 11131.28 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37663519.72 | 11101.90 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5993.96 | 29.97 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10182329.69 | 11095.78 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424179E+09 | 11117.65 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160310E+10 | 11152.84 | 20-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.508804E+10 | 11157.63 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.548263E+10 | 11240.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.466773E+10 | 8083.79 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385878E+10 | 8154.48 | 07-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161396E+10 | 8088.76 | 27-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372196E+09 | 8075.39 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10844696.82 | 6828.23 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9998833.94 | 7609.46 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.422580E+09 | 8067.54 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152757E+10 | 8084.06 | 21-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434786E+10 | 8085.30 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.466773E+10 | 8154.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.707169E+10 | 9143.80 | 14-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598539E+10 | 9239.49 | 07-FEB-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286642E+10 | 9144.57 | 21-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.650172E+09 | 9148.44 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19062333.62 | 9098.51 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12292307.85 | 9093.18 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584654E+09 | 9149.36 | 30-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199011E+10 | 9146.96 | 13-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.619928E+10 | 9147.75 | 18-DEC-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.707169E+10 | 9239.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505297E+10 | 8465.87 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423024E+10 | 8547.45 | 07-FEB-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193698E+10 | 8460.36 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584108E+09 | 8450.81 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41990911.97 | 8437.46 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 285142.74 | 960.78 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19664954.94 | 7395.05 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.561332E+09 | 8446.96 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169618E+10 | 8466.14 | 21-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452636E+10 | 8467.37 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505297E+10 | 8547.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.196063E+10 | 0.163339E+10 | 32393.42 | 15-MAR-14:10 | 32393.42 | 0.00 |
April | 0.00 | 0.00 | 0.693411E+09 | 0.625613E+09 | 13542.44 | 07-APR-14:10 | 13542.44 | 0.00 |
May | 0.00 | 0.00 | 0.778438E+10 | 0.709279E+10 | 40550.77 | 23-MAY-14:30 | 40550.77 | 0.00 |
June | 0.00 | 0.00 | 0.378664E+11 | 0.288645E+11 | 98335.82 | 27-JUN-06:03 | 40558.36 | 0.00 |
July | 0.00 | 0.00 | 0.671077E+11 | 0.477726E+11 | 118520.03 | 20-JUL-04:03 | 47498.47 | 0.00 |
August | 0.00 | 0.00 | 0.571890E+11 | 0.444088E+11 | 118494.46 | 14-AUG-08:00 | 50223.47 | 0.00 |
September | 0.00 | 0.00 | 0.253507E+11 | 0.192273E+11 | 85088.34 | 14-SEP-06:03 | 34737.27 | 0.00 |
October | 0.00 | 0.00 | 0.280236E+10 | 0.240678E+10 | 33797.60 | 11-OCT-15:00 | 33797.60 | 0.00 |
November | 0.00 | 0.00 | 0.433408E+09 | 0.310172E+09 | 10967.75 | 16-NOV-17:00 | 8494.35 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201188E+12 | 0.152342E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671077E+11 | 0.477726E+11 | 118520.03 | 50223.47 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192586E+10 | 0.160327E+10 | 33896.29 | 15-MAR-13:50 | 33896.29 | 0.00 |
April | 0.00 | 0.00 | 0.703806E+09 | 0.639549E+09 | 13709.43 | 08-APR-13:30 | 12077.45 | 0.00 |
May | 0.00 | 0.00 | 0.796610E+10 | 0.719215E+10 | 39632.40 | 23-MAY-14:30 | 39632.40 | 0.00 |
June | 0.00 | 0.00 | 0.358960E+11 | 0.272908E+11 | 88299.90 | 27-JUN-07:40 | 38171.24 | 0.00 |
July | 0.00 | 0.00 | 0.613570E+11 | 0.434795E+11 | 113078.48 | 20-JUL-06:03 | 45998.91 | 0.00 |
August | 0.00 | 0.00 | 0.501688E+11 | 0.389680E+11 | 111701.39 | 14-AUG-06:03 | 42465.34 | 0.00 |
September | 0.00 | 0.00 | 0.217104E+11 | 0.162781E+11 | 74578.77 | 15-SEP-11:00 | 41085.80 | 0.00 |
October | 0.00 | 0.00 | 0.248232E+10 | 0.207457E+10 | 28206.96 | 11-OCT-15:00 | 28206.96 | 0.00 |
November | 0.00 | 0.00 | 0.393067E+09 | 0.273529E+09 | 9202.00 | 16-NOV-18:00 | 6632.30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182603E+12 | 0.137799E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.613570E+11 | 0.434795E+11 | 113078.48 | 45998.91 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 885290.64 | 881973.23 | 953.25 | 09-JAN-06:20 | 953.25 | 0.00 |
February | 0.00 | 0.00 | 728009.63 | 711788.48 | 816.46 | 07-FEB-06:30 | 816.46 | 0.00 |
March | 0.00 | 0.00 | 0.209462E+10 | 0.176050E+10 | 40545.24 | 15-MAR-14:00 | 40545.24 | 0.00 |
April | 0.00 | 0.00 | 0.722121E+09 | 0.643228E+09 | 14492.65 | 08-APR-13:30 | 12370.31 | 0.00 |
May | 0.00 | 0.00 | 0.818563E+10 | 0.731982E+10 | 44965.41 | 10-MAY-14:30 | 44965.41 | 0.00 |
June | 0.00 | 0.00 | 0.376769E+11 | 0.285333E+11 | 125243.30 | 27-JUN-14:55 | 55265.66 | 0.00 |
July | 0.00 | 0.00 | 0.647907E+11 | 0.460204E+11 | 125243.30 | 21-JUL-05:03 | 52550.26 | 0.00 |
August | 0.00 | 0.00 | 0.524209E+11 | 0.405792E+11 | 123909.09 | 15-AUG-14:20 | 60633.29 | 0.00 |
September | 0.00 | 0.00 | 0.217190E+11 | 0.159391E+11 | 85734.64 | 15-SEP-12:30 | 47816.81 | 0.00 |
October | 0.00 | 0.00 | 0.233600E+10 | 0.189471E+10 | 27350.17 | 11-OCT-15:00 | 27350.17 | 0.00 |
November | 0.00 | 0.00 | 0.414163E+09 | 0.283410E+09 | 10520.94 | 27-NOV-07:03 | 9405.58 | 0.00 |
December | 0.00 | 0.00 | 1377613.16 | 1320837.08 | 607.96 | 28-DEC-06:06 | 607.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190363E+12 | 0.142977E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 728009.63 | 711788.48 | 607.96 | 607.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.647907E+11 | 0.460204E+11 | 125243.30 | 60633.29 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 43623.36 | 207963.07 | 04-JAN-07:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 41485.86 | 220148.95 | 23-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17436.62 | 199077.58 | 02-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4403.15 | 208160.76 | 06-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 365.79 | 139857.43 | 01-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 59.45 | 10551.02 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 3.76 | 5866.75 | 06-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14.51 | 14281.14 | 02-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 109.78 | 53106.40 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2438.42 | 195599.06 | 17-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10266.15 | 208935.64 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 36515.81 | 216165.80 | 11-DEC-07:06 |
Annual Sum or Average | 0.00 | 12929.06 | ||||
Minimum of Months | 0.00 | 0.00 | 3.76 | 5866.75 | ||
Maximum of Months | 0.00 | 0.00 | 43623.36 | 220148.95 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1848.53 | 6796.28 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1886.54 | 6820.17 | 15-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1990.33 | 6798.48 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1778.59 | 6590.17 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1743.71 | 6284.03 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1681.00 | 5894.62 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1458.82 | 5548.21 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1584.16 | 5368.52 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.74 | 5540.97 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1572.44 | 5884.37 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1699.57 | 6261.58 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1724.36 | 6582.72 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1704.61 | ||||
Minimum of Months | 0.00 | 0.00 | 1458.82 | 5368.52 | ||
Maximum of Months | 0.00 | 0.00 | 1990.33 | 6820.17 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153692E+10 | 0.32 | 2685.16 | 02-JAN-05:01 | 0.82 |
February | 0.132772E+10 | 0.31 | 2685.16 | 06-FEB-07:01 | 0.82 |
March | 0.161796E+10 | 0.32 | 2539.89 | 15-MAR-14:10 | 0.79 |
April | 0.174117E+10 | 0.31 | 4252.14 | 24-APR-05:03 | 1.06 |
May | 0.264533E+10 | 0.37 | 5023.50 | 23-MAY-14:30 | 1.17 |
June | 0.458289E+10 | 0.51 | 9484.18 | 12-JUN-12:10 | 1.72 |
July | 0.591227E+10 | 0.56 | 11181.62 | 05-JUL-15:50 | 1.91 |
August | 0.602710E+10 | 0.58 | 11181.62 | 14-AUG-09:20 | 1.91 |
September | 0.394968E+10 | 0.46 | 8212.06 | 18-SEP-12:10 | 1.58 |
October | 0.213883E+10 | 0.33 | 5320.13 | 11-OCT-16:00 | 1.21 |
November | 0.151113E+10 | 0.30 | 2138.57 | 01-NOV-12:08 | 0.73 |
December | 0.137580E+10 | 0.29 | 1652.74 | 07-DEC-06:04 | 0.65 |
Annual Sum or Average | 0.343668E+11 | 0.39 | |||
Minimum of Months | 0.132772E+10 | 0.29 | 1652.74 | 0.65 | |
Maximum of Months | 0.602710E+10 | 0.58 | 11181.62 | 1.91 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158110E+10 | 0.33 | 2823.70 | 02-JAN-06:01 | 0.87 |
February | 0.140723E+10 | 0.33 | 2823.70 | 02-FEB-07:02 | 0.87 |
March | 0.157274E+10 | 0.32 | 3115.36 | 15-MAR-13:50 | 0.92 |
April | 0.156749E+10 | 0.31 | 3068.61 | 21-APR-15:10 | 0.91 |
May | 0.244980E+10 | 0.38 | 5172.77 | 23-MAY-14:30 | 1.24 |
June | 0.425465E+10 | 0.51 | 8689.21 | 12-JUN-15:20 | 1.70 |
July | 0.520307E+10 | 0.54 | 10555.59 | 17-JUL-06:03 | 1.92 |
August | 0.496971E+10 | 0.54 | 10555.59 | 14-AUG-06:03 | 1.92 |
September | 0.301415E+10 | 0.42 | 7476.97 | 21-SEP-15:40 | 1.55 |
October | 0.163896E+10 | 0.31 | 3872.33 | 11-OCT-15:20 | 1.04 |
November | 0.132975E+10 | 0.29 | 2823.70 | 13-NOV-07:03 | 0.87 |
December | 0.146300E+10 | 0.31 | 2823.70 | 11-DEC-07:10 | 0.88 |
Annual Sum or Average | 0.304516E+11 | 0.38 | |||
Minimum of Months | 0.132975E+10 | 0.29 | 2823.70 | 0.87 | |
Maximum of Months | 0.520307E+10 | 0.54 | 10555.59 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192438E+10 | 0.38 | 2719.35 | 02-JAN-05:01 | 0.79 |
February | 0.173683E+10 | 0.37 | 2719.35 | 01-FEB-06:11 | 0.79 |
March | 0.170021E+10 | 0.33 | 3245.62 | 15-MAR-13:50 | 0.87 |
April | 0.154121E+10 | 0.30 | 2865.67 | 21-APR-14:50 | 0.81 |
May | 0.225257E+10 | 0.35 | 5008.92 | 31-MAY-16:00 | 1.12 |
June | 0.387981E+10 | 0.46 | 11995.80 | 27-JUN-15:15 | 1.90 |
July | 0.477967E+10 | 0.49 | 11995.80 | 17-JUL-06:03 | 1.91 |
August | 0.445736E+10 | 0.48 | 11995.80 | 15-AUG-14:20 | 1.91 |
September | 0.258731E+10 | 0.37 | 6898.29 | 21-SEP-15:30 | 1.35 |
October | 0.154912E+10 | 0.29 | 3159.27 | 11-OCT-15:20 | 0.85 |
November | 0.137658E+10 | 0.29 | 2719.35 | 03-NOV-06:02 | 0.79 |
December | 0.178524E+10 | 0.35 | 2719.35 | 01-DEC-07:03 | 0.79 |
Annual Sum or Average | 0.295703E+11 | 0.37 | |||
Minimum of Months | 0.137658E+10 | 0.29 | 2719.35 | 0.79 | |
Maximum of Months | 0.477967E+10 | 0.49 | 11995.80 | 1.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.754387E+09 | 0.678948E+09 | 842.84 | 04-JAN-07:12 | 758.55 | 758.55 | 41.35 | 2.67 |
February | 0.651634E+09 | 0.586471E+09 | 894.59 | 07-FEB-07:25 | 805.13 | 805.13 | 42.00 | 2.87 |
March | 0.323227E+09 | 0.290904E+09 | 833.24 | 07-MAR-07:01 | 749.91 | 749.91 | 43.80 | 2.62 |
April | 83836705.93 | 75453035.34 | 779.58 | 17-APR-06:01 | 701.62 | 701.62 | 42.23 | 2.25 |
May | 11430461.85 | 10287415.66 | 609.89 | 01-MAY-06:02 | 548.90 | 548.90 | 27.47 | 1.03 |
June | 2181045.71 | 1962941.14 | 132.73 | 14-JUN-06:03 | 119.46 | 119.46 | 42.47 | 0.14 |
July | 94455.30 | 85009.77 | 57.72 | 06-JUL-06:08 | 51.95 | 51.95 | 36.72 | 0.06 |
August | 369018.13 | 332116.31 | 120.03 | 02-AUG-06:07 | 108.03 | 108.03 | 33.66 | 0.13 |
September | 3299962.77 | 2969966.49 | 433.75 | 30-SEP-06:03 | 390.37 | 390.37 | 38.25 | 0.58 |
October | 49751250.19 | 44776125.18 | 757.25 | 30-OCT-06:01 | 681.52 | 681.52 | 39.74 | 2.02 |
November | 0.183898E+09 | 0.165508E+09 | 776.91 | 24-NOV-07:01 | 699.22 | 699.22 | 43.64 | 2.22 |
December | 0.640621E+09 | 0.576559E+09 | 892.76 | 11-DEC-07:01 | 803.48 | 803.48 | 42.66 | 2.87 |
Annual Sum or Average | 0.270473E+10 | 0.243426E+10 | ||||||
Minimum of Months | 94455.30 | 85009.77 | 57.72 | 51.95 | 51.95 | 27.47 | 0.06 | |
Maximum of Months | 0.754387E+09 | 0.678948E+09 | 894.59 | 805.13 | 805.13 | 43.80 | 2.87 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.99 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.54 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.93 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:02 | 2.06 | 2.06 | 56.88 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.03 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.09 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.25 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.42 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.35 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.19 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.09 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.81 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.54 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.19 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 35.52 | 35.52 | 43623.36 | 207963.07 | 04-JAN-07:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 42.60 | 42.60 | 41485.86 | 220148.95 | 23-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.44 | 33.44 | 17436.62 | 199077.58 | 02-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.87 | 22.87 | 4403.15 | 208160.76 | 06-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.25 | 21.25 | 365.79 | 139857.43 | 01-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 43.29 | 43.29 | 59.45 | 10551.02 | 14-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 36.80 | 36.80 | 3.76 | 5866.75 | 06-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.10 | 33.10 | 14.51 | 14281.14 | 02-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40.18 | 40.18 | 109.78 | 53106.40 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.87 | 25.87 | 2438.42 | 195599.06 | 17-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.79 | 26.79 | 10266.15 | 208935.64 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.23 | 28.23 | 36515.81 | 216165.80 | 11-DEC-07:06 |
Annual Sum or Average | 0.00 | 12929.06 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.25 | 21.25 | 3.76 | 5866.75 | ||
Maximum of Months | 0.00 | 0.00 | 43.29 | 43.29 | 43623.36 | 220148.95 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.99 | 57.99 | 1848.53 | 6796.28 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.39 | 57.39 | 1886.54 | 6820.17 | 15-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.39 | 57.39 | 1990.33 | 6798.48 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.46 | 57.46 | 1778.59 | 6590.17 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.08 | 58.08 | 1743.71 | 6284.03 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.74 | 57.74 | 1681.00 | 5894.62 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.87 | 57.87 | 1458.82 | 5548.21 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.95 | 57.95 | 1584.16 | 5368.52 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1499.74 | 5540.97 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.01 | 57.01 | 1572.44 | 5884.37 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 1699.57 | 6261.58 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.60 | 57.60 | 1724.36 | 6582.72 | 29-DEC-12:17 |
Annual Sum or Average | 0.00 | 1704.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.01 | 57.01 | 1458.82 | 5368.52 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 1990.33 | 6820.17 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.358716E+11 | 0.00 | 0.00 | 0.153692E+10 | 0.00 | 0.00 |
February | 0.307030E+11 | 0.00 | 0.00 | 0.132772E+10 | 0.00 | 0.00 |
March | 0.152666E+11 | 0.00 | 0.00 | 0.207707E+10 | 0.00 | 0.00 |
April | 0.401770E+10 | 0.00 | 0.00 | 0.191782E+10 | 0.00 | 0.00 |
May | 0.718951E+09 | 0.00 | 0.00 | 0.449689E+10 | 0.00 | 0.00 |
June | 0.157945E+09 | 0.00 | 0.00 | 0.130645E+11 | 0.00 | 0.00 |
July | 11153179.66 | 0.00 | 0.00 | 0.207622E+11 | 0.00 | 0.00 |
August | 32788999.46 | 0.00 | 0.00 | 0.187355E+11 | 0.00 | 0.00 |
September | 0.207646E+09 | 0.00 | 0.00 | 0.959660E+10 | 0.00 | 0.00 |
October | 0.157513E+10 | 0.00 | 0.00 | 0.281973E+10 | 0.00 | 0.00 |
November | 0.666510E+10 | 0.00 | 0.00 | 0.162206E+10 | 0.00 | 0.00 |
December | 0.281330E+11 | 0.00 | 0.00 | 0.137580E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123361E+12 | 0.00 | 0.00 | 0.793329E+11 | 0.00 | 0.00 |
Minimum of Months | 11153179.66 | 0.00 | 0.00 | 0.132772E+10 | 0.00 | 0.00 |
Maximum of Months | 0.358716E+11 | 0.00 | 0.00 | 0.207622E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.343719E+11 | 0.00 | 0.00 | 0.158110E+10 | 0.00 | 0.00 |
February | 0.293561E+11 | 0.00 | 0.00 | 0.140723E+10 | 0.00 | 0.00 |
March | 0.127706E+11 | 0.00 | 0.00 | 0.202097E+10 | 0.00 | 0.00 |
April | 0.270499E+10 | 0.00 | 0.00 | 0.174670E+10 | 0.00 | 0.00 |
May | 48658830.90 | 0.00 | 0.00 | 0.434063E+10 | 0.00 | 0.00 |
June | 414397.06 | 0.00 | 0.00 | 0.123104E+11 | 0.00 | 0.00 |
July | 988471.57 | 0.00 | 0.00 | 0.188116E+11 | 0.00 | 0.00 |
August | 470566.00 | 0.00 | 0.00 | 0.161803E+11 | 0.00 | 0.00 |
September | 9515676.76 | 0.00 | 0.00 | 0.789974E+10 | 0.00 | 0.00 |
October | 0.146276E+10 | 0.00 | 0.00 | 0.224847E+10 | 0.00 | 0.00 |
November | 0.723216E+10 | 0.00 | 0.00 | 0.143072E+10 | 0.00 | 0.00 |
December | 0.286547E+11 | 0.00 | 0.00 | 0.146300E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.116613E+12 | 0.00 | 0.00 | 0.714408E+11 | 0.00 | 0.00 |
Minimum of Months | 414397.06 | 0.00 | 0.00 | 0.140723E+10 | 0.00 | 0.00 |
Maximum of Months | 0.343719E+11 | 0.00 | 0.00 | 0.188116E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.474117E+11 | 0.00 | 0.00 | 0.192463E+10 | 0.00 | 0.00 |
February | 0.410184E+11 | 0.00 | 0.00 | 0.173703E+10 | 0.00 | 0.00 |
March | 0.190216E+11 | 0.00 | 0.00 | 0.218812E+10 | 0.00 | 0.00 |
April | 0.478147E+10 | 0.00 | 0.00 | 0.172582E+10 | 0.00 | 0.00 |
May | 0.206227E+09 | 0.00 | 0.00 | 0.420500E+10 | 0.00 | 0.00 |
June | 2988148.71 | 0.00 | 0.00 | 0.123705E+11 | 0.00 | 0.00 |
July | 937648.78 | 0.00 | 0.00 | 0.192030E+11 | 0.00 | 0.00 |
August | 389604.36 | 0.00 | 0.00 | 0.162318E+11 | 0.00 | 0.00 |
September | 81981959.38 | 0.00 | 0.00 | 0.752107E+10 | 0.00 | 0.00 |
October | 0.354539E+10 | 0.00 | 0.00 | 0.212954E+10 | 0.00 | 0.00 |
November | 0.129107E+11 | 0.00 | 0.00 | 0.148326E+10 | 0.00 | 0.00 |
December | 0.416989E+11 | 0.00 | 0.00 | 0.178561E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.170681E+12 | 0.00 | 0.00 | 0.725054E+11 | 0.00 | 0.00 |
Minimum of Months | 389604.36 | 0.00 | 0.00 | 0.148326E+10 | 0.00 | 0.00 |
Maximum of Months | 0.474117E+11 | 0.00 | 0.00 | 0.192030E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153692E+10 | 0.00 | 0.358716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132772E+10 | 0.00 | 0.307030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161796E+10 | 0.196063E+10 | 0.152666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174117E+10 | 0.693411E+09 | 0.401770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264533E+10 | 0.778438E+10 | 0.718951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458289E+10 | 0.378664E+11 | 0.157945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591227E+10 | 0.671077E+11 | 11153179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.602710E+10 | 0.571890E+11 | 32788999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394968E+10 | 0.253507E+11 | 0.207646E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213883E+10 | 0.280236E+10 | 0.157513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151113E+10 | 0.433408E+09 | 0.666510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137580E+10 | 0.00 | 0.281330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343668E+11 | 0.201188E+12 | 0.123361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132772E+10 | 0.00 | 11153179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.602710E+10 | 0.671077E+11 | 0.358716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158110E+10 | 0.00 | 0.343719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140723E+10 | 0.00 | 0.293561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157274E+10 | 0.192586E+10 | 0.127706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156749E+10 | 0.703806E+09 | 0.270499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244980E+10 | 0.796610E+10 | 48658830.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.425465E+10 | 0.358960E+11 | 414397.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.520307E+10 | 0.613570E+11 | 988471.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496971E+10 | 0.501688E+11 | 470566.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301415E+10 | 0.217104E+11 | 9515676.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163896E+10 | 0.248232E+10 | 0.146276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132975E+10 | 0.393067E+09 | 0.723216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146300E+10 | 0.00 | 0.286547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304516E+11 | 0.182603E+12 | 0.116613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132975E+10 | 0.00 | 414397.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520307E+10 | 0.613570E+11 | 0.343719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192438E+10 | 885290.64 | 0.474117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173683E+10 | 728009.63 | 0.410184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170021E+10 | 0.209462E+10 | 0.190216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154121E+10 | 0.722121E+09 | 0.478147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225257E+10 | 0.818563E+10 | 0.206227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387981E+10 | 0.376769E+11 | 2988148.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.477967E+10 | 0.647907E+11 | 937648.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.445736E+10 | 0.524209E+11 | 389604.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258731E+10 | 0.217190E+11 | 81981959.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154912E+10 | 0.233600E+10 | 0.354539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137658E+10 | 0.414163E+09 | 0.129107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178524E+10 | 1377613.16 | 0.416989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295703E+11 | 0.190363E+12 | 0.170681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137658E+10 | 728009.63 | 389604.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.477967E+10 | 0.647907E+11 | 0.474117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153692E+10 | 0.358716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132772E+10 | 0.307030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161796E+10 | 0.152666E+11 | 0.00 | 0.00 | 0.459106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174117E+10 | 0.401770E+10 | 0.00 | 0.00 | 0.176657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264533E+10 | 0.718951E+09 | 0.00 | 0.00 | 0.185155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458289E+10 | 0.157945E+09 | 0.00 | 0.00 | 0.848163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591227E+10 | 11153179.66 | 0.00 | 0.00 | 0.148500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.602710E+10 | 32788999.46 | 0.00 | 0.00 | 0.127084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394968E+10 | 0.207646E+09 | 0.00 | 0.00 | 0.564692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213883E+10 | 0.157513E+10 | 0.00 | 0.00 | 0.680894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151113E+10 | 0.666510E+10 | 0.00 | 0.00 | 0.110933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137580E+10 | 0.281330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343668E+11 | 0.123361E+12 | 0.00 | 0.00 | 0.449661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132772E+10 | 11153179.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.602710E+10 | 0.358716E+11 | 0.00 | 0.00 | 0.148500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158110E+10 | 0.343719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140723E+10 | 0.293561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157274E+10 | 0.127706E+11 | 0.00 | 0.00 | 0.448223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156749E+10 | 0.270499E+10 | 0.00 | 0.00 | 0.179209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244980E+10 | 48658830.90 | 0.00 | 0.00 | 0.189083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.425465E+10 | 414397.06 | 0.00 | 0.00 | 0.805576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.520307E+10 | 988471.57 | 0.00 | 0.00 | 0.136085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.496971E+10 | 470566.00 | 0.00 | 0.00 | 0.112105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301415E+10 | 9515676.76 | 0.00 | 0.00 | 0.488559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163896E+10 | 0.146276E+10 | 0.00 | 0.00 | 0.609511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132975E+10 | 0.723216E+10 | 0.00 | 0.00 | 0.100963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146300E+10 | 0.286547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304516E+11 | 0.116613E+12 | 0.00 | 0.00 | 0.409891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132975E+10 | 414397.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520307E+10 | 0.343719E+11 | 0.00 | 0.00 | 0.136085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192438E+10 | 0.474117E+11 | 0.00 | 0.00 | 240131.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173683E+10 | 0.410184E+11 | 0.00 | 0.00 | 197572.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170021E+10 | 0.190216E+11 | 0.00 | 0.00 | 0.487903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154121E+10 | 0.478147E+10 | 0.00 | 0.00 | 0.184610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225257E+10 | 0.206227E+09 | 0.00 | 0.00 | 0.195243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387981E+10 | 2988148.71 | 0.00 | 0.00 | 0.849072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.477967E+10 | 937648.78 | 0.00 | 0.00 | 0.144233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.445736E+10 | 389604.36 | 0.00 | 0.00 | 0.117745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258731E+10 | 81981959.38 | 0.00 | 0.00 | 0.493375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154912E+10 | 0.354539E+10 | 0.00 | 0.00 | 0.580420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137658E+10 | 0.129107E+11 | 0.00 | 0.00 | 0.106686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178524E+10 | 0.416989E+11 | 0.00 | 0.00 | 374070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295703E+11 | 0.170681E+12 | 0.00 | 0.00 | 0.429351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137658E+10 | 389604.36 | 0.00 | 0.00 | 197572.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.477967E+10 | 0.474117E+11 | 0.00 | 0.00 | 0.144233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142229E+11 | 0.00 | 0.00 | 1464365.77 | 0.00 | 0.497308E+09 | 0.256811E+10 | 0.00 | 0.28 |
February | 0.133145E+11 | 0.00 | 0.00 | 1691333.47 | 0.00 | 2825853.60 | 0.279778E+10 | 0.00 | 0.28 |
March | 0.631683E+10 | 6189844.65 | 0.00 | 17695398.19 | 0.00 | 0.00 | 0.109924E+11 | 0.00 | 0.39 |
April | 0.158003E+10 | 0.00 | 0.00 | 28558945.51 | 0.00 | 0.00 | 0.158657E+11 | 0.00 | 0.51 |
May | 0.813421E+09 | 5124930.23 | 0.00 | 41169125.97 | 7161097.25 | 0.00 | 0.201035E+11 | 0.00 | 0.93 |
June | 0.375099E+09 | 0.174406E+10 | 0.00 | 35853683.90 | 0.217138E+09 | 0.00 | 0.127275E+11 | 0.00 | 1.13 |
July | 0.181174E+09 | 0.617054E+10 | 0.00 | 19822397.48 | 0.493800E+09 | 0.00 | 0.393158E+10 | 0.00 | 0.90 |
August | 0.306225E+09 | 0.343392E+10 | 0.00 | 35484057.52 | 0.218090E+09 | 0.00 | 0.833066E+10 | 0.00 | 1.07 |
September | 0.102828E+10 | 0.119754E+10 | 0.00 | 37896743.98 | 21124548.89 | 0.00 | 0.151237E+11 | 0.00 | 1.12 |
October | 0.698296E+09 | 0.00 | 0.00 | 37183175.65 | 193374.94 | 0.00 | 0.189245E+11 | 0.00 | 0.65 |
November | 0.275507E+10 | 0.00 | 0.00 | 22372980.70 | 5352254.15 | 0.00 | 0.128217E+11 | 0.00 | 0.39 |
December | 0.115471E+11 | 0.00 | 0.00 | 4132571.27 | 0.00 | 0.00 | 0.511651E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.531389E+11 | 0.125574E+11 | 0.00 | 0.283325E+09 | 0.962859E+09 | 0.500134E+09 | 0.129304E+12 | 0.00 | 0.66 |
Minimum of Months | 0.181174E+09 | 0.00 | 0.00 | 1464365.77 | 0.00 | 0.00 | 0.256811E+10 | 0.00 | 0.28 |
Maximum of Months | 0.142229E+11 | 0.617054E+10 | 0.00 | 41169125.97 | 0.493800E+09 | 0.497308E+09 | 0.201035E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197711E+10 | 0.00 | 0.00 | 0.27 |
February | 0.140664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140828E+10 | 0.00 | 0.00 | 0.27 |
March | 0.132028E+11 | 3024516.24 | 0.00 | 2144971.30 | 3372291.03 | 0.108105E+09 | 0.141472E+10 | 0.00 | 0.33 |
April | 0.787162E+10 | 0.00 | 0.00 | 6044773.28 | 0.00 | 9037156.43 | 0.484338E+10 | 0.00 | 0.38 |
May | 0.362962E+10 | 702114.67 | 0.00 | 19192057.73 | 26369678.54 | 0.00 | 0.106413E+11 | 0.00 | 0.64 |
June | 0.814004E+09 | 0.134308E+10 | 0.00 | 21503779.24 | 0.205971E+09 | 0.00 | 0.811433E+10 | 0.00 | 0.80 |
July | 0.339500E+09 | 0.456914E+10 | 0.00 | 12335475.06 | 0.524421E+09 | 0.00 | 0.248824E+10 | 0.00 | 0.67 |
August | 0.616628E+09 | 0.251329E+10 | 0.00 | 21767925.42 | 0.176288E+09 | 0.00 | 0.519009E+10 | 0.00 | 0.75 |
September | 0.203629E+10 | 0.815497E+09 | 0.00 | 18839505.63 | 30171615.65 | 0.00 | 0.823671E+10 | 0.00 | 0.74 |
October | 0.649227E+10 | 0.00 | 0.00 | 8403745.55 | 1844091.18 | 785398.38 | 0.587321E+10 | 0.00 | 0.42 |
November | 0.104980E+11 | 0.00 | 0.00 | 837923.52 | 9535967.57 | 29188768.83 | 0.125782E+10 | 0.00 | 0.30 |
December | 0.144730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116204E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.887366E+11 | 0.924473E+10 | 0.00 | 0.111070E+09 | 0.977974E+09 | 0.469455E+10 | 0.480599E+11 | 0.00 | 0.49 |
Minimum of Months | 0.339500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.146964E+11 | 0.456914E+10 | 0.00 | 21767925.42 | 0.524421E+09 | 0.197711E+10 | 0.106413E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.926409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624401E+10 | 0.00 | 0.00 | 0.26 |
February | 0.937198E+10 | 0.00 | 0.00 | 0.00 | 50787.48 | 0.507075E+10 | 0.00 | 8235.71 | 0.26 |
March | 0.119416E+11 | 447624.18 | 0.00 | 1641430.57 | 59835.74 | 0.111341E+10 | 0.864262E+09 | 0.00 | 0.33 |
April | 0.915659E+10 | 0.00 | 0.00 | 2854755.20 | 0.00 | 0.128571E+09 | 0.297949E+10 | 0.00 | 0.37 |
May | 0.468844E+10 | 985227.32 | 0.00 | 15578957.00 | 32663227.57 | 0.00 | 0.924685E+10 | 0.00 | 0.63 |
June | 0.141462E+10 | 0.134107E+10 | 0.00 | 19411249.23 | 0.277619E+09 | 0.00 | 0.758424E+10 | 0.00 | 0.83 |
July | 0.525627E+09 | 0.460456E+10 | 0.00 | 11250007.97 | 0.534752E+09 | 0.00 | 0.224187E+10 | 0.00 | 0.71 |
August | 0.101012E+10 | 0.249370E+10 | 0.00 | 18510667.20 | 0.270062E+09 | 0.00 | 0.439033E+10 | 0.00 | 0.77 |
September | 0.321233E+10 | 0.792212E+09 | 0.00 | 13311774.95 | 66064559.64 | 0.00 | 0.607760E+10 | 0.00 | 0.71 |
October | 0.800955E+10 | 0.00 | 0.00 | 3822718.68 | 54078.44 | 0.117368E+09 | 0.310674E+10 | 0.00 | 0.39 |
November | 0.102919E+11 | 0.00 | 640072.99 | 43020.35 | 13944757.63 | 0.491694E+09 | 0.130194E+09 | 33324.52 | 0.30 |
December | 0.948349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497166E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.783703E+11 | 0.923298E+10 | 640072.99 | 86424581.16 | 0.119527E+10 | 0.181375E+11 | 0.366216E+11 | 41560.23 | 0.49 |
Minimum of Months | 0.525627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.119416E+11 | 0.460456E+10 | 640072.99 | 19411249.23 | 0.534752E+09 | 0.624401E+10 | 0.924685E+10 | 33324.52 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 64095892.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358621E+10 | 0.00 | 0.00 | 0.29 |
February | 0.253826E+09 | 0.00 | 0.00 | 0.00 | 10706.70 | 0.316022E+10 | 0.00 | 2490.75 | 0.29 |
March | 0.128181E+10 | 104282.31 | 0.00 | 296149.37 | 3739.83 | 0.165201E+10 | 0.104834E+09 | 0.00 | 0.34 |
April | 0.195287E+10 | 0.00 | 0.00 | 328983.10 | 0.00 | 0.353506E+09 | 0.277818E+09 | 0.00 | 0.37 |
May | 0.132331E+10 | 0.00 | 0.00 | 3055357.25 | 7093560.56 | 9599984.09 | 0.164641E+10 | 0.00 | 0.65 |
June | 0.362222E+09 | 0.435410E+09 | 0.00 | 5002016.18 | 55826607.77 | 0.00 | 0.175273E+10 | 0.00 | 1.02 |
July | 0.116395E+09 | 0.142404E+10 | 0.00 | 3042387.46 | 0.101108E+09 | 0.00 | 0.575463E+09 | 0.00 | 0.92 |
August | 0.307682E+09 | 0.729594E+09 | 0.00 | 4543802.17 | 50955083.03 | 0.00 | 0.956123E+09 | 0.00 | 0.94 |
September | 0.935984E+09 | 0.197325E+09 | 0.00 | 2461461.74 | 20042424.14 | 4738181.11 | 0.100580E+10 | 0.00 | 0.75 |
October | 0.182145E+10 | 0.00 | 0.00 | 346838.37 | 11400.48 | 0.275523E+09 | 0.249499E+09 | 0.00 | 0.39 |
November | 0.114060E+10 | 0.00 | 592828.15 | 0.00 | 2518770.51 | 0.118299E+10 | 0.00 | 11022.11 | 0.30 |
December | 0.154058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319587E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.971430E+10 | 0.278647E+10 | 592828.15 | 19076995.64 | 0.237571E+09 | 0.134207E+11 | 0.656868E+10 | 13512.86 | 0.55 |
Minimum of Months | 64095892.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.195287E+10 | 0.142404E+10 | 592828.15 | 5002016.18 | 0.101108E+09 | 0.358621E+10 | 0.175273E+10 | 11022.11 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321229E+10 | 0.00 | 0.00 | 0.42 |
February | 0.642451E+09 | 0.00 | 0.00 | 0.00 | 10620.20 | 0.248257E+10 | 0.00 | 2927.70 | 0.43 |
March | 0.173897E+10 | 133966.54 | 0.00 | 335963.98 | 0.00 | 0.104043E+10 | 0.135705E+09 | 0.00 | 0.52 |
April | 0.160111E+10 | 0.00 | 0.00 | 1667497.79 | 0.00 | 0.178958E+09 | 0.105278E+10 | 0.00 | 0.64 |
May | 0.106998E+10 | 0.00 | 0.00 | 4503745.66 | 7036244.87 | 3589641.71 | 0.246462E+10 | 0.00 | 1.20 |
June | 0.333704E+09 | 0.405093E+09 | 0.00 | 5635232.65 | 37320324.22 | 0.00 | 0.223594E+10 | 0.00 | 1.66 |
July | 85656245.62 | 0.120174E+10 | 0.00 | 4483358.51 | 0.107602E+09 | 0.00 | 0.874412E+09 | 0.00 | 1.53 |
August | 0.261344E+09 | 0.580362E+09 | 0.00 | 5235441.43 | 57245668.10 | 0.00 | 0.115987E+10 | 0.00 | 1.52 |
September | 0.812640E+09 | 0.170089E+09 | 0.00 | 3452672.09 | 27223026.21 | 3094611.45 | 0.148707E+10 | 0.00 | 1.29 |
October | 0.170415E+10 | 0.00 | 0.00 | 644995.80 | 11308.37 | 0.193369E+09 | 0.453180E+09 | 0.00 | 0.62 |
November | 0.130190E+10 | 0.00 | 570571.21 | 2193.66 | 2498418.95 | 0.981349E+09 | 8785997.52 | 7792.84 | 0.47 |
December | 0.190011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292484E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.988576E+10 | 0.235742E+10 | 570571.21 | 25961101.58 | 0.238948E+09 | 0.110205E+11 | 0.987237E+10 | 10720.53 | 0.90 |
Minimum of Months | 85656245.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.173897E+10 | 0.120174E+10 | 570571.21 | 5635232.65 | 0.107602E+09 | 0.321229E+10 | 0.246462E+10 | 7792.84 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.996506E+09 | 0.00 | 0.00 | 332268.36 | 0.00 | 0.302615E+10 | 0.213446E+09 | 0.00 | 0.33 |
February | 0.120094E+10 | 0.00 | 0.00 | 570123.54 | 13069.04 | 0.248569E+10 | 0.350557E+09 | 3602.78 | 0.35 |
March | 0.176489E+10 | 535420.06 | 0.00 | 2668503.87 | 0.00 | 0.101463E+10 | 0.132727E+10 | 0.00 | 0.49 |
April | 0.176352E+10 | 0.00 | 0.00 | 3565091.23 | 0.00 | 0.322024E+09 | 0.207622E+10 | 0.00 | 0.62 |
May | 0.142017E+10 | 5632951.91 | 0.00 | 6054289.48 | 4000439.68 | 17162791.42 | 0.311683E+10 | 0.00 | 1.01 |
June | 0.538323E+09 | 0.506418E+09 | 0.00 | 6281448.43 | 54509567.28 | 0.00 | 0.227407E+10 | 0.00 | 1.28 |
July | 0.187579E+09 | 0.170260E+10 | 0.00 | 4000401.33 | 0.125994E+09 | 0.00 | 0.703902E+09 | 0.00 | 1.13 |
August | 0.381293E+09 | 0.917260E+09 | 0.00 | 6990038.32 | 51720389.18 | 0.00 | 0.140119E+10 | 0.00 | 1.30 |
September | 0.840808E+09 | 0.299035E+09 | 0.00 | 7622651.00 | 23069074.91 | 4934047.24 | 0.283946E+10 | 0.00 | 1.38 |
October | 0.166862E+10 | 0.00 | 0.00 | 4141386.26 | 13915.90 | 0.183216E+09 | 0.216478E+10 | 0.00 | 0.73 |
November | 0.149543E+10 | 0.00 | 384067.34 | 1257764.73 | 3431903.35 | 0.959663E+09 | 0.633670E+09 | 8725.74 | 0.40 |
December | 0.817107E+09 | 0.00 | 0.00 | 180289.90 | 0.00 | 0.294820E+10 | 0.124412E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.130752E+11 | 0.343149E+10 | 384067.34 | 43664256.46 | 0.262752E+09 | 0.109617E+11 | 0.172258E+11 | 12328.51 | 0.78 |
Minimum of Months | 0.187579E+09 | 0.00 | 0.00 | 180289.90 | 0.00 | 0.00 | 0.124412E+09 | 0.00 | 0.33 |
Maximum of Months | 0.176489E+10 | 0.170260E+10 | 384067.34 | 7622651.00 | 0.125994E+09 | 0.302615E+10 | 0.311683E+10 | 8725.74 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332836E+10 | 0.00 | 0.00 | 0.45 |
February | 0.570130E+09 | 0.00 | 0.00 | 12187.35 | 11520.49 | 0.282207E+10 | 16083615.82 | 3175.88 | 0.46 |
March | 0.164665E+10 | 47104.17 | 0.00 | 475992.15 | 68006.64 | 0.130545E+10 | 0.249679E+09 | 0.00 | 0.56 |
April | 0.177193E+10 | 0.00 | 0.00 | 1666206.45 | 0.00 | 0.334637E+09 | 0.105226E+10 | 0.00 | 0.72 |
May | 0.143220E+10 | 1656424.33 | 0.00 | 4347248.25 | 6178942.10 | 16275482.48 | 0.224578E+10 | 0.00 | 1.27 |
June | 0.507031E+09 | 0.398620E+09 | 0.00 | 5755181.72 | 56743406.34 | 0.00 | 0.186806E+10 | 0.00 | 1.71 |
July | 0.171847E+09 | 0.122939E+10 | 0.00 | 3460536.17 | 0.111790E+09 | 0.00 | 0.475891E+09 | 0.00 | 1.36 |
August | 0.396304E+09 | 0.621599E+09 | 0.00 | 4500479.02 | 53772969.27 | 0.00 | 0.810323E+09 | 0.00 | 1.42 |
September | 0.103034E+10 | 0.149360E+09 | 0.00 | 3195690.12 | 39428572.45 | 6164042.62 | 0.118650E+10 | 0.00 | 1.28 |
October | 0.191524E+10 | 0.00 | 0.00 | 733516.31 | 12267.00 | 0.249982E+09 | 0.449145E+09 | 0.00 | 0.70 |
November | 0.128675E+10 | 0.00 | 607837.31 | 25309.53 | 2710215.30 | 0.116476E+10 | 32888116.15 | 8255.72 | 0.51 |
December | 0.285455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309547E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.113198E+11 | 0.240067E+10 | 607837.31 | 24172347.07 | 0.270715E+09 | 0.123232E+11 | 0.838661E+10 | 11431.60 | 0.91 |
Minimum of Months | 0.171847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.191524E+10 | 0.122939E+10 | 607837.31 | 5755181.72 | 0.111790E+09 | 0.332836E+10 | 0.224578E+10 | 8255.72 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369316E+10 | 0.00 | 0.00 | 0.29 |
February | 0.222196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340262E+10 | 0.00 | 0.00 | 0.29 |
March | 0.139436E+10 | 0.00 | 0.00 | 31233.59 | 947594.71 | 0.182347E+10 | 17032221.45 | 0.00 | 0.33 |
April | 0.225998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330579E+09 | 0.00 | 0.00 | 0.35 |
May | 0.190008E+10 | 0.00 | 0.00 | 901007.31 | 2435937.29 | 974334.98 | 0.574083E+09 | 0.00 | 0.52 |
June | 0.411978E+09 | 0.288025E+09 | 0.00 | 3430707.40 | 55486255.40 | 0.00 | 0.121500E+10 | 0.00 | 0.75 |
July | 0.111248E+09 | 0.106882E+10 | 0.00 | 2446714.84 | 0.128451E+09 | 0.00 | 0.473286E+09 | 0.00 | 0.70 |
August | 0.275791E+09 | 0.618677E+09 | 0.00 | 4097540.94 | 54115764.98 | 0.00 | 0.907465E+09 | 0.00 | 0.79 |
September | 0.907357E+09 | 0.181665E+09 | 0.00 | 2562397.28 | 8088771.66 | 0.00 | 0.109659E+10 | 0.00 | 0.71 |
October | 0.216662E+10 | 0.00 | 0.00 | 476529.40 | 40748.55 | 32103273.41 | 0.360025E+09 | 0.00 | 0.40 |
November | 0.210787E+10 | 0.00 | 2376.18 | 0.00 | 1123701.81 | 0.467616E+09 | 0.00 | 1765.16 | 0.30 |
December | 0.524261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305008E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.124544E+11 | 0.215719E+10 | 2376.18 | 13946130.78 | 0.250690E+09 | 0.128006E+11 | 0.464348E+10 | 1765.16 | 0.48 |
Minimum of Months | 0.111248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.225998E+10 | 0.106882E+10 | 2376.18 | 4097540.94 | 0.128451E+09 | 0.369316E+10 | 0.121500E+10 | 1765.16 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.314730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281968E+10 | 0.00 | 0.00 | 0.37 |
February | 0.615507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233304E+10 | 0.00 | 0.00 | 0.38 |
March | 0.171995E+10 | 785806.99 | 0.00 | 87874.58 | 0.00 | 0.892703E+09 | 37144832.43 | 0.00 | 0.43 |
April | 0.154392E+10 | 0.00 | 0.00 | 986519.45 | 0.00 | 97551011.88 | 0.662459E+09 | 0.00 | 0.50 |
May | 0.988214E+09 | 0.00 | 0.00 | 2993085.52 | 2020037.19 | 416371.90 | 0.163179E+10 | 0.00 | 0.88 |
June | 0.238037E+09 | 0.293726E+09 | 0.00 | 4701595.97 | 34734026.95 | 0.00 | 0.180403E+10 | 0.00 | 1.31 |
July | 62838212.47 | 0.987793E+09 | 0.00 | 3846448.83 | 0.100730E+09 | 0.00 | 0.772707E+09 | 0.00 | 1.22 |
August | 0.188416E+09 | 0.523803E+09 | 0.00 | 5158205.28 | 40766277.02 | 0.00 | 0.115744E+10 | 0.00 | 1.31 |
September | 0.542973E+09 | 0.161897E+09 | 0.00 | 3956114.82 | 5988582.26 | 0.00 | 0.171308E+10 | 0.00 | 1.20 |
October | 0.149054E+10 | 0.00 | 0.00 | 1152521.11 | 33791.34 | 17986270.86 | 0.731791E+09 | 0.00 | 0.56 |
November | 0.177291E+10 | 0.00 | 2844.37 | 36247.39 | 931846.42 | 0.317100E+09 | 48269323.92 | 589.90 | 0.40 |
December | 0.528521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241018E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.100066E+11 | 0.196800E+10 | 2844.37 | 22918612.94 | 0.185204E+09 | 0.888865E+10 | 0.855871E+10 | 589.90 | 0.74 |
Minimum of Months | 62838212.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.177291E+10 | 0.987793E+09 | 2844.37 | 5158205.28 | 0.100730E+09 | 0.281968E+10 | 0.180403E+10 | 589.90 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530265E+10 | 0.00 | 0.00 | 0.41 |
February | 0.318838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474285E+10 | 0.00 | 0.00 | 0.40 |
March | 0.150918E+10 | 2416956.94 | 0.00 | 262301.55 | 0.00 | 0.248039E+10 | 49565465.42 | 0.00 | 0.40 |
April | 0.169743E+10 | 0.00 | 0.00 | 627394.47 | 0.00 | 0.108715E+10 | 0.406272E+09 | 0.00 | 0.43 |
May | 0.166750E+10 | 797060.98 | 0.00 | 1742331.77 | 1962103.82 | 0.364065E+09 | 0.830125E+09 | 0.00 | 0.62 |
June | 0.685830E+09 | 0.349454E+09 | 0.00 | 3120678.73 | 61306406.75 | 91207467.97 | 0.961634E+09 | 0.00 | 0.84 |
July | 0.184241E+09 | 0.136274E+10 | 0.00 | 2681661.65 | 0.121008E+09 | 5460453.65 | 0.435756E+09 | 0.00 | 0.81 |
August | 0.405952E+09 | 0.853672E+09 | 0.00 | 5591963.17 | 43342909.22 | 19156028.78 | 0.956960E+09 | 0.00 | 1.04 |
September | 0.673369E+09 | 0.269097E+09 | 0.00 | 6338985.88 | 9822595.14 | 0.124423E+09 | 0.223022E+10 | 0.00 | 1.16 |
October | 0.156975E+10 | 2827.32 | 0.00 | 2428941.40 | 37957.12 | 0.546855E+09 | 0.136515E+10 | 0.00 | 0.60 |
November | 0.134569E+10 | 0.00 | 0.00 | 345981.87 | 1128836.44 | 0.162385E+10 | 0.267925E+09 | 0.00 | 0.37 |
December | 0.293252E+09 | 0.00 | 0.00 | 25570.14 | 0.00 | 0.456009E+10 | 22684269.51 | 0.00 | 0.38 |
Annual Sum or Average | 0.106412E+11 | 0.283818E+10 | 0.00 | 23165810.64 | 0.238609E+09 | 0.209481E+11 | 0.752629E+10 | 0.00 | 0.62 |
Minimum of Months | 0.184241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5460453.65 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.169743E+10 | 0.136274E+10 | 0.00 | 6338985.88 | 0.121008E+09 | 0.530265E+10 | 0.223022E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298590E+10 | 0.00 | 0.00 | 0.39 |
February | 0.471651E+09 | 0.00 | 0.00 | 54.32 | 0.00 | 0.260999E+10 | 2825456.71 | 0.00 | 0.40 |
March | 0.167054E+10 | 39050.56 | 0.00 | 85082.27 | 778401.48 | 0.103580E+10 | 59420882.14 | 0.00 | 0.44 |
April | 0.175045E+10 | 0.00 | 0.00 | 781736.90 | 0.00 | 0.163467E+09 | 0.461519E+09 | 0.00 | 0.52 |
May | 0.123869E+10 | 232180.65 | 0.00 | 2556446.74 | 1869204.98 | 958380.45 | 0.132915E+10 | 0.00 | 0.89 |
June | 0.304244E+09 | 0.310608E+09 | 0.00 | 4525142.02 | 36933217.93 | 0.00 | 0.151804E+10 | 0.00 | 1.32 |
July | 98076865.93 | 0.100462E+10 | 0.00 | 2938857.67 | 81173192.70 | 0.00 | 0.445856E+09 | 0.00 | 1.05 |
August | 0.224006E+09 | 0.584523E+09 | 0.00 | 4296778.54 | 32052256.24 | 0.00 | 0.841611E+09 | 0.00 | 1.19 |
September | 0.650549E+09 | 0.146845E+09 | 0.00 | 3523253.97 | 7243912.19 | 0.00 | 0.134963E+10 | 0.00 | 1.12 |
October | 0.170208E+10 | 0.00 | 0.00 | 891144.98 | 35152.14 | 23358325.51 | 0.580652E+09 | 0.00 | 0.58 |
November | 0.180601E+10 | 0.00 | 2856.35 | 26179.24 | 969372.59 | 0.384818E+09 | 33253810.12 | 716.23 | 0.41 |
December | 0.538900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252046E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.107403E+11 | 0.204687E+10 | 2856.35 | 19624676.66 | 0.161055E+09 | 0.972474E+10 | 0.662195E+10 | 716.23 | 0.73 |
Minimum of Months | 98076865.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.180601E+10 | 0.100462E+10 | 2856.35 | 4525142.02 | 81173192.70 | 0.298590E+10 | 0.151804E+10 | 716.23 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338118E+10 | 0.00 | 0.00 | 0.28 |
February | 0.601632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285668E+10 | 0.00 | 0.00 | 0.29 |
March | 0.173144E+10 | 732304.14 | 0.00 | 332968.73 | 636658.47 | 0.125603E+10 | 0.130039E+09 | 0.00 | 0.33 |
April | 0.211942E+10 | 0.00 | 0.00 | 426049.62 | 0.00 | 0.141469E+09 | 0.366595E+09 | 0.00 | 0.37 |
May | 0.113765E+10 | 24047.67 | 0.00 | 3596772.42 | 5684290.33 | 0.00 | 0.182217E+10 | 0.00 | 0.66 |
June | 0.280975E+09 | 0.432312E+09 | 0.00 | 5171382.50 | 44421006.77 | 0.00 | 0.178300E+10 | 0.00 | 0.97 |
July | 98287328.55 | 0.140264E+10 | 0.00 | 3095243.54 | 0.109992E+09 | 0.00 | 0.583120E+09 | 0.00 | 0.85 |
August | 0.248262E+09 | 0.729026E+09 | 0.00 | 4790114.97 | 36990809.07 | 0.00 | 0.103286E+10 | 0.00 | 0.89 |
September | 0.811129E+09 | 0.209116E+09 | 0.00 | 2998952.03 | 7710110.38 | 0.00 | 0.122155E+10 | 0.00 | 0.76 |
October | 0.198503E+10 | 0.00 | 0.00 | 644462.23 | 388843.68 | 82430549.53 | 0.420484E+09 | 0.00 | 0.40 |
November | 0.190225E+10 | 0.00 | 33309.00 | 0.00 | 1974295.69 | 0.587022E+09 | 0.00 | 3142.27 | 0.30 |
December | 0.500734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293108E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.117186E+11 | 0.277385E+10 | 33309.00 | 21055946.04 | 0.207798E+09 | 0.112359E+11 | 0.735981E+10 | 3142.27 | 0.53 |
Minimum of Months | 98287328.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.211942E+10 | 0.140264E+10 | 33309.00 | 5171382.50 | 0.109992E+09 | 0.338118E+10 | 0.182217E+10 | 3142.27 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.523770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310771E+10 | 0.00 | 0.00 | 0.44 |
February | 0.971725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240283E+10 | 0.00 | 0.00 | 0.45 |
March | 0.210773E+10 | 1688338.66 | 0.00 | 382457.05 | 0.00 | 0.802062E+09 | 0.212123E+09 | 0.00 | 0.52 |
April | 0.178092E+10 | 0.00 | 0.00 | 1960258.65 | 0.00 | 73193301.54 | 0.117136E+10 | 0.00 | 0.67 |
May | 0.106723E+10 | 0.00 | 0.00 | 4838379.14 | 5761658.59 | 0.00 | 0.249921E+10 | 0.00 | 1.20 |
June | 0.297772E+09 | 0.389234E+09 | 0.00 | 5621626.00 | 30780617.48 | 0.00 | 0.221240E+10 | 0.00 | 1.57 |
July | 76329037.69 | 0.116463E+10 | 0.00 | 4456281.53 | 0.106224E+09 | 0.00 | 0.878731E+09 | 0.00 | 1.40 |
August | 0.250366E+09 | 0.561386E+09 | 0.00 | 5301338.95 | 41756544.53 | 0.00 | 0.121233E+10 | 0.00 | 1.43 |
September | 0.789137E+09 | 0.174809E+09 | 0.00 | 3825789.70 | 12349638.68 | 246065.71 | 0.163396E+10 | 0.00 | 1.29 |
October | 0.186539E+10 | 0.00 | 0.00 | 967074.33 | 392475.80 | 68702146.95 | 0.626976E+09 | 0.00 | 0.64 |
November | 0.192195E+10 | 0.00 | 34537.62 | 34312.21 | 1992737.24 | 0.556473E+09 | 35263440.27 | 3547.60 | 0.48 |
December | 0.488782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290725E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.121411E+11 | 0.229175E+10 | 34537.62 | 27387517.56 | 0.199258E+09 | 0.991847E+10 | 0.104824E+11 | 3547.60 | 0.88 |
Minimum of Months | 76329037.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.210773E+10 | 0.116463E+10 | 34537.62 | 5621626.00 | 0.106224E+09 | 0.310771E+10 | 0.249921E+10 | 3547.60 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132695E+10 | 0.00 | 0.00 | 538075.62 | 0.00 | 0.265155E+10 | 0.338357E+09 | 0.00 | 0.33 |
February | 0.149952E+10 | 0.00 | 0.00 | 770456.06 | 0.00 | 0.212414E+10 | 0.479153E+09 | 0.00 | 0.34 |
March | 0.209567E+10 | 6188160.06 | 0.00 | 3234362.78 | 0.00 | 0.589634E+09 | 0.159069E+10 | 0.00 | 0.46 |
April | 0.184794E+10 | 0.00 | 0.00 | 3989548.82 | 0.00 | 0.122015E+09 | 0.214058E+10 | 0.00 | 0.61 |
May | 0.119742E+10 | 4393664.30 | 0.00 | 6541498.91 | 2546431.97 | 389034.43 | 0.313663E+10 | 0.00 | 0.99 |
June | 0.429394E+09 | 0.490205E+09 | 0.00 | 6329141.45 | 48103898.17 | 0.00 | 0.216975E+10 | 0.00 | 1.20 |
July | 0.151738E+09 | 0.167537E+10 | 0.00 | 3648131.89 | 0.110235E+09 | 0.00 | 0.646229E+09 | 0.00 | 1.01 |
August | 0.317688E+09 | 0.909613E+09 | 0.00 | 6992241.91 | 36274528.98 | 0.00 | 0.136705E+10 | 0.00 | 1.20 |
September | 0.713173E+09 | 0.308826E+09 | 0.00 | 8084801.68 | 9395077.17 | 0.00 | 0.291637E+10 | 0.00 | 1.37 |
October | 0.156774E+10 | 444382.77 | 0.00 | 5327131.68 | 101969.78 | 51392276.51 | 0.260050E+10 | 0.00 | 0.77 |
November | 0.195778E+10 | 0.00 | 41214.43 | 1787510.88 | 2285858.05 | 0.480943E+09 | 0.877060E+09 | 989.20 | 0.41 |
December | 0.142543E+10 | 0.00 | 0.00 | 276189.78 | 0.00 | 0.236664E+10 | 0.181320E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.145304E+11 | 0.339504E+10 | 41214.43 | 47519091.46 | 0.208943E+09 | 0.838671E+10 | 0.184437E+11 | 989.20 | 0.75 |
Minimum of Months | 0.151738E+09 | 0.00 | 0.00 | 276189.78 | 0.00 | 0.00 | 0.181320E+09 | 0.00 | 0.33 |
Maximum of Months | 0.209567E+10 | 0.167537E+10 | 41214.43 | 8084801.68 | 0.110235E+09 | 0.265155E+10 | 0.313663E+10 | 989.20 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317165E+10 | 0.00 | 0.00 | 0.45 |
February | 0.898761E+09 | 0.00 | 0.00 | 17182.78 | 0.00 | 0.257076E+10 | 17337792.67 | 0.00 | 0.46 |
March | 0.203200E+10 | 501799.03 | 0.00 | 556118.00 | 916056.07 | 0.905121E+09 | 0.311839E+09 | 0.00 | 0.53 |
April | 0.195769E+10 | 0.00 | 0.00 | 1778194.00 | 0.00 | 0.139643E+09 | 0.100418E+10 | 0.00 | 0.70 |
May | 0.127113E+10 | 33472.80 | 0.00 | 4615023.54 | 5884220.55 | 348332.30 | 0.220806E+10 | 0.00 | 1.23 |
June | 0.406592E+09 | 0.400376E+09 | 0.00 | 5471596.75 | 36364212.29 | 0.00 | 0.178055E+10 | 0.00 | 1.58 |
July | 0.156067E+09 | 0.122769E+10 | 0.00 | 3253771.91 | 87003187.11 | 0.00 | 0.431835E+09 | 0.00 | 1.21 |
August | 0.346137E+09 | 0.613286E+09 | 0.00 | 4349317.37 | 31938982.46 | 0.00 | 0.803020E+09 | 0.00 | 1.29 |
September | 0.881130E+09 | 0.167615E+09 | 0.00 | 3537463.97 | 16159708.01 | 252729.56 | 0.128043E+10 | 0.00 | 1.23 |
October | 0.201468E+10 | 0.00 | 0.00 | 941418.92 | 403104.66 | 84729870.60 | 0.562569E+09 | 0.00 | 0.69 |
November | 0.193435E+10 | 0.00 | 36764.33 | 54402.35 | 2046703.69 | 0.596172E+09 | 54026879.44 | 3680.79 | 0.50 |
December | 0.678943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281400E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.131359E+11 | 0.240950E+10 | 36764.33 | 24574489.59 | 0.180716E+09 | 0.102827E+11 | 0.845385E+10 | 3680.79 | 0.86 |
Minimum of Months | 0.156067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.203200E+10 | 0.122769E+10 | 36764.33 | 5471596.75 | 87003187.11 | 0.317165E+10 | 0.220806E+10 | 3680.79 | 1.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.138994E+12 | 0.176894E+11 | 0.00 | 0.150341E+12 | 0.448125E+11 |
February | 0.212886E+12 | 0.176789E+11 | 0.00 | 0.140112E+12 | 0.398511E+11 |
March | 0.313020E+12 | 0.127487E+11 | 0.00 | 0.176513E+12 | 0.304381E+11 |
April | 0.369363E+12 | 0.983039E+10 | 0.00 | 0.212695E+12 | 0.910731E+10 |
May | 0.448658E+12 | 0.577529E+10 | 0.00 | 0.223440E+12 | 0.302592E+11 |
June | 0.481882E+12 | 0.211850E+10 | 0.00 | 0.123518E+12 | 0.136570E+12 |
July | 0.447690E+12 | -967973902.5 | 0.00 | -185951027.7 | 0.236144E+12 |
August | 0.383817E+12 | 0.626880E+09 | 0.00 | 0.802117E+11 | 0.195498E+12 |
September | 0.296028E+12 | 0.327623E+10 | 0.00 | 0.178303E+12 | 0.844321E+11 |
October | 0.204041E+12 | 0.818740E+10 | 0.00 | 0.217016E+12 | 0.132190E+11 |
November | 0.109150E+12 | 0.108716E+11 | 0.00 | 0.174232E+12 | 0.165069E+11 |
December | 0.124810E+12 | 0.178692E+11 | 0.00 | 0.155530E+12 | 0.399672E+11 |
Annual Sum or Average | 0.353034E+13 | 0.105705E+12 | 0.00 | 0.183173E+13 | 0.876805E+12 |