Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:21:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1755.85 | 352.43 | 352.43 |
Net Site Energy | 1755.85 | 352.43 | 352.43 |
Total Source Energy | 5560.78 | 1116.13 | 1116.13 |
Net Source Energy | 5560.78 | 1116.13 | 1116.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 512.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1755.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 512.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 84.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 42.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 17.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 512.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 84.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 42.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 352.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 352.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1755.851 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1755.851 | 100.00 |
Total On-Site and Utility Electric Sources | 1755.851 | 100.00 |
Total Electricity End Uses | 1755.851 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 68.33 |
Time Setpoint Not Met During Occupied Cooling | 295.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1432.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 17-FEB-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73625.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14592.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3198.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 160184.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73625.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14592.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3198.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 56.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1624.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 952.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 268.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 133.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5560.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 11.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1116.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 11.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1116.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.64 | 0.283660 | 0.292000 | 0.771489 | 0.756427 | 0.500000 | 0.001343 |
CORE_MID VAV BOX COMPONENT | 2.13 | 0.351102 | 0.350000 | 0.747103 | 0.936271 | 0.500000 | 0.001085 |
CORE_TOP VAV BOX COMPONENT | 2.27 | 0.330627 | 0.344000 | 0.779768 | 0.881673 | 0.500000 | 0.001152 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.695523 | 0.227155 | 0.236000 | 0.164143 | 0.605747 | 0.500000 | 0.001677 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.696335 | 0.143640 | 0.200000 | 0.139267 | 0.383041 | 0.500000 | 0.002652 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.844864 | 0.187002 | 0.200000 | 0.168973 | 0.498673 | 0.500000 | 0.002037 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.769652 | 0.129949 | 0.200000 | 0.153930 | 0.346530 | 0.500000 | 0.002932 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.603022 | 0.262000 | 0.270000 | 0.162816 | 0.698667 | 0.500000 | 0.001454 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.626305 | 0.159701 | 0.200000 | 0.125261 | 0.425870 | 0.500000 | 0.002386 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.739287 | 0.213708 | 0.220000 | 0.162643 | 0.569889 | 0.500000 | 0.001783 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.652561 | 0.153266 | 0.200000 | 0.130512 | 0.408708 | 0.500000 | 0.002486 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.606300 | 0.260584 | 0.260000 | 0.157638 | 0.694889 | 0.500000 | 0.001462 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.674003 | 0.148400 | 0.200000 | 0.134801 | 0.395732 | 0.500000 | 0.002567 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.754182 | 0.209488 | 0.209000 | 0.157624 | 0.558634 | 0.500000 | 0.001819 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.703164 | 0.142236 | 0.200000 | 0.140633 | 0.379296 | 0.500000 | 0.002679 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25745.54 |
CORE_MID VAV BOX REHEAT COIL | 24931.74 |
CORE_TOP VAV BOX REHEAT COIL | 26829.95 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11336.34 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7396.17 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11291.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7371.56 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7780.85 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5172.03 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7720.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5132.15 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9010.70 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5960.41 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8941.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5921.55 |
PACU_VAV_BOT HEATING COIL | 9592.66 |
PACU_VAV_MID HEATING COIL | 11015.47 |
PACU_VAV_TOP HEATING COIL | 8991.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.63 | 1.35 | 5.26 | 1.35 | 4.75 | 4.75 | 0.300000 | 0.284531 | 4.75 |
PACU_VAV_MID | 2.44 | 1.34 | 4.87 | 1.34 | 4.26 | 4.26 | 0.300000 | 0.313736 | 4.26 |
PACU_VAV_TOP | 2.64 | 1.41 | 5.27 | 1.99 | 4.94 | 4.94 | 0.300000 | 0.402571 | 4.94 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.75 |
PACU_VAV_MID_OA_CONTROLLER | 4.26 |
PACU_VAV_TOP_OA_CONTROLLER | 4.94 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.75 | 115912.94 | 0.706620 | 1.58 | 38633.78 | 0.706620 |
PACU_VAV_MID COOLING COIL | 4.26 | 105887.65 | 0.701083 | 1.42 | 35292.35 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.94 | 119091.22 | 0.710688 | 1.65 | 39693.10 | 0.710688 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.75 |
PACU_VAV_MID FAN | 4.26 |
PACU_VAV_TOP FAN | 4.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.538_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4258E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4642E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7805E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8122E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1664E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1906E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1728E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9256E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1005 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1255E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3525E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8306E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4279E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4774E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7830E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8266E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1688E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2018E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0929E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8450E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8489E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6393E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8704E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3949E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5645E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5796E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3667E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3777E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1161E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1203E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8538E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8905E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4205E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4501E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1233E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1450E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6140E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4693E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0389E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1324E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8614E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.8911E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8530E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8896E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4193E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4473E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1211E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1372E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8330E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2787E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3393E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9605E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6361E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8435E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7451E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7742E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3763E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4050E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3492E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3655E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8071E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9431E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1068 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1984E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9905E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.6744E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9344E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7523E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7070E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5556E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7590E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3272E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0085E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9498E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3934E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5512E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2124E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1734E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7115E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2115E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2421E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9079E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5595E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7998E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8067E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9426E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1068 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1979E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9899E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.6739E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9343E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7521E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7068E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5554E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7586E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3269E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0086E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9497E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3934E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5511E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2122E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1733E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7115E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2114E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2420E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9078E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5593E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7996E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36646.24354 | 36646.24354 | 2.64209 | 2.64209 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3320.06855 | 3320.06855 | 0.14067 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29633.94204 | 29633.94204 | 2.13458 | 2.13458 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10285.51903 | 10285.51903 | 0.43369 | 0.43369 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31172.75972 | 31172.75972 | 2.26677 | 2.26677 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 18944.06807 | 18944.06807 | 0.80398 | 0.80398 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9564.63080 | 9564.63080 | 0.69552 | 0.69552 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8662.58693 | 8662.58693 | 0.33970 | 0.33970 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9575.84869 | 9575.84869 | 0.69634 | 0.69634 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5646.63333 | 5646.63333 | 0.22163 | 0.22163 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11618.36393 | 11618.36393 | 0.84486 | 0.84486 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8629.24373 | 8629.24373 | 0.33835 | 0.33835 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10584.10833 | 10584.10833 | 0.76965 | 0.76965 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5628.42986 | 5628.42986 | 0.22090 | 0.22090 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8292.71513 | 8292.71513 | 0.60302 | 0.60302 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5479.91560 | 5479.91560 | 0.23316 | 0.23316 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8612.95721 | 8612.95721 | 0.62631 | 0.62631 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3641.57851 | 3641.57851 | 0.15498 | 0.15498 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10166.65075 | 10166.65075 | 0.73929 | 0.73929 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5437.52257 | 5437.52257 | 0.23135 | 0.23135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8974.04188 | 8974.04188 | 0.65256 | 0.65256 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 32.53067 | 1.65338E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3613.64917 | 3613.64917 | 0.15379 | 0.15379 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8337.69052 | 8337.69052 | 0.60630 | 0.60630 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6342.10475 | 6342.10475 | 0.27001 | 0.27001 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9268.79057 | 9268.79057 | 0.67400 | 0.67400 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4194.46427 | 4194.46427 | 0.17861 | 0.17861 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10371.35938 | 10371.35938 | 0.75418 | 0.75418 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6293.46477 | 6293.46477 | 0.26793 | 0.26793 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9669.81572 | 9669.81572 | 0.70316 | 0.70316 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4167.22008 | 4167.22008 | 0.17744 | 0.17744 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 78580.58 | 4.75421 | 4.75421 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 11821.45 | 1.19797 | 1.19797 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71752.14 | 4.26410 | 4.26410 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 11826.63 | 1.32769 | 1.32769 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80878.85 | 4.94461 | 4.94461 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 11840.08 | 1.99056 | 1.99056 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64209 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28366 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77149 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75643 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34316E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25745.54246 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13458 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35110 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74710 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93627 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08516E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24931.74318 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26677 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33063 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77977 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88167 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15235E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26829.95140 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69552 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22716 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16414 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60575 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67727E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11336.33792 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69634 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14364 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13927 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38304 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65246E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7396.16964 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84486 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18700 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16897 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49867 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03741E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11291.26400 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76965 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12995 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15393 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34653 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93193E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7371.55761 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60302 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26200 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16282 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69867 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45420E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7780.85052 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62631 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15970 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12526 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42587 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38570E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5172.03067 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73929 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21371 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16264 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56989 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78280E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7720.29468 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65256 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15327 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13051 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40871 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48588E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5132.14687 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60630 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26058 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15764 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69489 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.46210E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9010.70068 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67400 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14840 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13480 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39573 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56739E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5960.41450 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75418 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20949 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20900 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15762 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55863 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81872E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8941.28869 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70316 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14224 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14063 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37930 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67865E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5921.54508 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63163 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35272 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.26326 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35272 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.75421 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.75421 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28453 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.43611 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33780 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.87223 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33780 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.26410 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.26410 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31374 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63657 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.40608 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.27314 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99056 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.94461 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.94461 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.40257 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.75421 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.26410 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.94461 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.75421 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.75421 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 115912.93803 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70662 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58458 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38633.78225 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70662 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 9592.66084 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.75421 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.26410 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.26410 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105887.64503 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42122 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35292.35209 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 11015.47078 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.26410 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.94461 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.94461 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 119091.22020 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71069 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64804 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39693.10369 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71069 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 8991.53187 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.94461 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 115656.81 | 394637.42 | 12.49 | 3.20 | 3.58 | 3.77 | 3.91 | 10.91 | 12.21 | 12.88 | 13.35 | 5.4942 | 4.3553 | 2.9332 | 1.2556 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 105714.70 | 360713.54 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.92 | 13.38 | 4.9278 | 3.9009 | 2.6251 | 1.1317 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 118781.64 | 405299.78 | 12.46 | 3.19 | 3.57 | 3.77 | 3.91 | 10.90 | 12.18 | 12.85 | 13.33 | 5.7142 | 4.5350 | 3.0482 | 1.3010 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2163087835 | 0.2666180732 | Pass | Pass | 0.2385541471 | 0.4238627189 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8271306830E-002 | 9.4352170573E-002 | Pass | Pass | 0.2280126539 | 0.5244740028 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5847094848E-002 | 4.2575830740E-002 | Pass | Pass | 0.2187745495 | 0.4391155618 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.9830202633E-002 | 5.4185443662E-002 | Pass | Pass | 0.2882459012 | 0.5865779156 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1442469151 | 0.2258285003 | Pass | Pass | 0.1886730531 | 0.3889356615 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1419871212 | 0.2195679919 | Pass | Pass | 0.1893188219 | 0.3896126616 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1400970126 | 0.2090770960 | Pass | Pass | 0.1893219300 | 0.3887022956 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2215746677 | 0.2986509887 | Pass | Pass | 0.2020930796 | 0.4082241592 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3321153270 | 0.5488220249 | Pass | Pass | 0.2205840895 | 0.4426512716 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2209091390 | 0.3616598472 | Pass | Pass | 0.1909100318 | 0.3878001571 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1787875931 | 0.2195231226 | Pass | Pass | 0.2373327807 | 0.4231819772 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2511946222 | 0.2842255369 | Pass | Pass | 0.2387253831 | 0.4244781743 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3501719293 | 0.5318244249 | Pass | Pass | 0.2679231181 | 0.4567759606 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2379756604 | 0.3039666272 | Pass | Pass | 0.2378753505 | 0.4226017147 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1357025442 | 0.2134529388 | Pass | Pass | 0.1885032735 | 0.3880593882 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2105881936 | 0.2967626490 | Pass | Pass | 0.1895918495 | 0.3897238460 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3101516929 | 0.5464181539 | Pass | Pass | 0.2069392442 | 0.4146574448 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2032985707 | 0.3206998239 | Pass | Pass | 0.1883847183 | 0.3864175574 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3102.92 | -43.9 | 0.00 | 198.93 | 2726.02 | 5983.96 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.538_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.538_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.538_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.059 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 8.77 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.60 | 0.0000 | Y | 5.49 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.27 | 0.0000 | Y | 8.56 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.67 | 0.0000 | Y | 5.50 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.79 | 0.0000 | Y | 8.73 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.59 | 0.0000 | Y | 5.49 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.89 | 0.0000 | Y | 8.77 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.60 | 0.0000 | Y | 5.49 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.27 | 0.0000 | Y | 8.56 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.67 | 0.0000 | Y | 5.50 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.64 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.73 | 41.73 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.73 | 62.73 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.73 | 47.05 | 41.64 | |
Exterior Lighting Total | 5686.19 | 50.86 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 115912.94 | 81906.34 | 34006.60 | 0.71 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105887.65 | 74236.05 | 31651.59 | 0.70 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 119091.22 | 84636.69 | 34454.53 | 0.71 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 115656.8 | 3.20 | 10.91 | N/A | N/A | 12.49 | |
PACU_VAV_MID COOLING COIL | 105714.7 | 3.21 | 10.94 | N/A | N/A | 12.53 | |
PACU_VAV_TOP COOLING COIL | 118781.6 | 3.19 | 10.90 | N/A | N/A | 12.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25745.54 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24931.74 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26829.95 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11336.34 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7396.17 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11291.26 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7371.56 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7780.85 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5172.03 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7720.29 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5132.15 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9010.70 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5960.41 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8941.29 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5921.55 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 9592.66 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 11015.47 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 8991.53 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.75 | 10407.02 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.26 | 9334.15 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.94 | 10823.81 | 2189.01 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115656.81 | 3.20 | 10.91 | 12.49 | 5.4942 | 3.58 | 12.21 | 4.3553 | 3.77 | 12.88 | 2.9332 | 3.91 | 13.35 | 1.2556 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105714.70 | 3.21 | 10.94 | 12.53 | 4.9278 | 3.59 | 12.25 | 3.9009 | 3.79 | 12.92 | 2.6251 | 3.92 | 13.38 | 1.1317 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 118781.64 | 3.19 | 10.90 | 12.46 | 5.7142 | 3.57 | 12.18 | 4.5350 | 3.77 | 12.85 | 3.0482 | 3.91 | 13.33 | 1.3010 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36646.24 | 36646.24 | 37.26 | 2.642 | 2.642 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_MID | 29633.94 | 29633.94 | 30.13 | 2.135 | 2.135 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_TOP | 31172.76 | 31172.76 | 31.69 | 2.267 | 2.267 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00888 | 33.74 | 0.01654 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9564.63 | 9564.63 | 46.13 | 0.696 | 0.696 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00887 | 33.82 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9575.85 | 9575.85 | 72.95 | 0.696 | 0.696 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00874 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11618.36 | 11618.36 | 56.04 | 0.845 | 0.845 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00881 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10584.11 | 10584.11 | 80.64 | 0.770 | 0.770 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00872 | 32.79 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8292.72 | 8292.72 | 40.00 | 0.603 | 0.603 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00887 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8612.96 | 8612.96 | 65.62 | 0.626 | 0.626 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00873 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10166.65 | 10166.65 | 49.03 | 0.739 | 0.739 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00880 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8974.04 | 8974.04 | 68.37 | 0.653 | 0.653 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00872 | 32.53 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8337.69 | 8337.69 | 40.21 | 0.606 | 0.606 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00891 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9268.79 | 9268.79 | 70.61 | 0.674 | 0.674 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00874 | 30.67 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10371.36 | 10371.36 | 50.02 | 0.754 | 0.754 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00883 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9669.82 | 9669.82 | 73.67 | 0.703 | 0.703 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00873 | 32.79 | 0.01653 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3320.07 | 3320.07 | 3.38 | 0.141 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_MID | 10285.52 | 10285.52 | 10.46 | 0.434 | 0.434 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_TOP | 18944.07 | 18944.07 | 19.26 | 0.804 | 0.804 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8662.59 | 8662.59 | 41.78 | 0.340 | 0.340 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00773 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5646.63 | 5646.63 | 43.02 | 0.222 | 0.222 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00774 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8629.24 | 8629.24 | 41.62 | 0.338 | 0.338 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00772 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5628.43 | 5628.43 | 42.88 | 0.221 | 0.221 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00774 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5479.92 | 5479.92 | 26.43 | 0.233 | 0.233 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3641.58 | 3641.58 | 27.74 | 0.155 | 0.155 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5437.52 | 5437.52 | 26.23 | 0.231 | 0.231 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3613.65 | 3613.65 | 27.53 | 0.154 | 0.154 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6342.10 | 6342.10 | 30.59 | 0.270 | 0.270 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4194.46 | 4194.46 | 31.95 | 0.179 | 0.179 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6293.46 | 6293.46 | 30.35 | 0.268 | 0.268 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4167.22 | 4167.22 | 31.75 | 0.177 | 0.177 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.75 | 4.75 | 1.20 | 1.20 | 4.7542 | 1.3527 | 4.7542 | 0.2845 | 0.3000 |
PACU_VAV_MID | 4.26 | 4.26 | 1.33 | 1.33 | 4.2641 | 1.3378 | 4.2641 | 0.3137 | 0.3000 |
PACU_VAV_TOP | 4.94 | 4.94 | 1.99 | 1.99 | 4.9446 | 1.9906 | 4.9446 | 0.4026 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25745.542 | 25745.542 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25745.54 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00799956 | 51.6716 | 3320.07 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24931.743 | 24931.743 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24931.74 | 14472.71 | 0.433688 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 10285.52 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26829.951 | 26829.951 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26829.95 | 26829.95 | 0.803985 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 18944.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11336.338 | 11336.338 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11336.34 | 11336.34 | 0.339704 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00772893 | 50.8897 | 8662.59 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7396.170 | 7396.170 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7396.17 | 7396.17 | 0.221633 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00774183 | 50.9744 | 5646.63 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11291.264 | 11291.264 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 11291.26 | 11291.26 | 0.338353 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00772446 | 50.8605 | 8629.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7371.558 | 7371.558 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7371.56 | 7371.56 | 0.220896 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00773802 | 50.9495 | 5628.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7780.851 | 7780.851 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7780.85 | 7780.85 | 0.233160 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784464 | 50.6848 | 5479.92 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5172.031 | 5172.031 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5172.03 | 5172.03 | 0.154985 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784914 | 50.7135 | 3641.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7720.295 | 7720.295 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7720.29 | 7720.29 | 0.231346 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784274 | 50.6727 | 5437.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5132.147 | 5132.147 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5132.15 | 5132.15 | 0.153790 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784727 | 50.7016 | 3613.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9010.701 | 9010.701 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9010.70 | 9010.70 | 0.270014 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782650 | 50.5694 | 6342.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5960.414 | 5960.414 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5960.41 | 5960.41 | 0.178609 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00783154 | 50.6016 | 4194.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8941.289 | 8941.289 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8941.29 | 8941.29 | 0.267934 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782427 | 50.5552 | 6293.46 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5921.545 | 5921.545 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5921.55 | 5921.55 | 0.177445 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782969 | 50.5898 | 4167.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 115912.938 | 81906.342 | 4.754211 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 119215.18 | 86286.43 | 4.754211 | 26.49 | 19.08 | 0.01077658 | 11.02 | 11.02 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 25.1392 | 24.00 | 0.00883853 | 47.5172 | 65282.93 | 0.00 | 119521.80 | 83297.20 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 9592.661 | 9592.661 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9592.66 | 9592.66 | 1.426263 | 7.24 | 6.48 | 0.00568538 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 83.7973 | 21.00 | 0.00786921 | 50.8414 | 21492.73 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 105887.645 | 74236.051 | 4.264095 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 109770.91 | 77359.61 | 4.264095 | 26.79 | 19.38 | 0.01104851 | 11.03 | 11.03 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.0287 | 24.00 | 0.00889639 | 47.8242 | 58347.10 | 0.00 | 109184.38 | 75519.11 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 11015.471 | 11015.471 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11015.47 | 11015.47 | 1.279229 | 5.68 | 5.38 | 0.00543321 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 93.4290 | 21.00 | 0.00793354 | 51.2511 | 26689.69 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 119091.220 | 84636.693 | 4.944613 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 122325.74 | 89026.66 | 4.944613 | 26.36 | 18.99 | 0.01071168 | 11.02 | 11.02 | 0.00850000 | 33.74 | 0.01653608 | 25.09 | 24.1712 | 24.00 | 0.00884973 | 47.5769 | 67849.04 | 0.00 | 122799.03 | 86038.73 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 8991.532 | 8991.532 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8991.53 | 8991.53 | 1.483384 | 7.79 | 6.86 | 0.00577723 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 80.5705 | 21.00 | 0.00793391 | 51.2534 | 27840.07 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25745.542 | 25745.542 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25745.54 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25745.54 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.81 | 0.00799956 | 21.00 | 0.00799956 | 51.6716 | 3320.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24931.743 | 24931.743 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24931.74 | 14472.71 | 1.0000 | 0.52179947 | 0.433688 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24931.74 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 10285.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26829.951 | 26829.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26829.95 | 26829.95 | 1.0000 | 0.96732770 | 0.803985 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26829.95 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 18944.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11336.338 | 11336.338 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11336.34 | 11336.34 | 1.0000 | 0.40872059 | 0.339704 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11336.34 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00772893 | 20.70 | 0.00772893 | 50.8897 | 8662.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7396.170 | 7396.170 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7396.17 | 7396.17 | 1.0000 | 0.26666167 | 0.221633 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7396.17 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00774183 | 20.70 | 0.00774183 | 50.9744 | 5646.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11291.264 | 11291.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 11291.26 | 11291.26 | 1.0000 | 0.40709550 | 0.338353 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11291.26 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00772446 | 20.70 | 0.00772446 | 50.8605 | 8629.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7371.558 | 7371.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7371.56 | 7371.56 | 1.0000 | 0.26577431 | 0.220896 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7371.56 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00773802 | 20.70 | 0.00773802 | 50.9495 | 5628.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7780.851 | 7780.851 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7780.85 | 7780.85 | 1.0000 | 0.28053097 | 0.233160 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7780.85 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784464 | 21.00 | 0.00784464 | 50.6848 | 5479.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5172.031 | 5172.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5172.03 | 5172.03 | 1.0000 | 0.18647251 | 0.154985 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5172.03 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784914 | 21.00 | 0.00784914 | 50.7135 | 3641.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7720.295 | 7720.295 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7720.29 | 7720.29 | 1.0000 | 0.27834769 | 0.231346 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7720.29 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784274 | 21.00 | 0.00784274 | 50.6727 | 5437.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5132.147 | 5132.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5132.15 | 5132.15 | 1.0000 | 0.18503454 | 0.153790 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5132.15 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784727 | 21.00 | 0.00784727 | 50.7016 | 3613.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9010.701 | 9010.701 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9010.70 | 9010.70 | 1.0000 | 0.32487201 | 0.270014 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9010.70 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782650 | 21.00 | 0.00782650 | 50.5694 | 6342.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5960.414 | 5960.414 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5960.41 | 5960.41 | 1.0000 | 0.21489692 | 0.178609 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5960.41 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00783154 | 21.00 | 0.00783154 | 50.6016 | 4194.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8941.289 | 8941.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8941.29 | 8941.29 | 1.0000 | 0.32236943 | 0.267934 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8941.29 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782427 | 21.00 | 0.00782427 | 50.5552 | 6293.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5921.545 | 5921.545 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5921.55 | 5921.55 | 1.0000 | 0.21349552 | 0.177445 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5921.55 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782969 | 21.00 | 0.00782969 | 50.5898 | 4167.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 115912.938 | 81906.342 | 4.754211 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8731 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.754211 | 5.72010960 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 119215.18 | 86286.43 | 1.0285 | 5.72010960 | 4.754211 | 26.49 | 19.08 | 0.01077658 | 54102.0 | 11.02 | 11.02 | 0.00850000 | 32510.3 | -999.0 | -999.00 | -999.00 | -999.00 | 10407.021 | 108808.16 | 33.90 | 0.01653638 | 25.13 | 1.19517000 | 25.1392 | 24.00 | 0.00883853 | 24.00 | 0.00883853 | 47.5172 | 65282.93 | 0.00 | 119521.80 | 83297.20 | 5.49420851 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.82 | 11.79 | 0.00859960 | 33568.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9592.661 | 9592.661 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.754211 | 5.72010960 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9592.66 | 9592.66 | 1.0000 | 1.71603288 | 1.426263 | 7.24 | 6.48 | 0.00568538 | 21567.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9592.66 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 83.7973 | 20.88 | 0.00790011 | 21.00 | 0.00786921 | 50.8414 | 21492.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105887.645 | 74236.051 | 4.264095 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.98273 | 1025.3786 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.264095 | 5.13041851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 109770.91 | 77359.61 | 1.0367 | 5.13041851 | 4.264095 | 26.79 | 19.38 | 0.01104851 | 55099.2 | 11.03 | 11.03 | 0.00850000 | 32511.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9334.152 | 100436.76 | 33.90 | 0.01653638 | 25.13 | 1.19517000 | 28.0287 | 24.00 | 0.00889639 | 24.00 | 0.00889639 | 47.8242 | 58347.10 | 0.00 | 109184.38 | 75519.11 | 4.92780576 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850611 | 33165.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11015.471 | 11015.471 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.264095 | 5.13041851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11015.47 | 11015.47 | 1.0000 | 1.53912555 | 1.279229 | 5.68 | 5.38 | 0.00543321 | 19350.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11015.47 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 93.4290 | 21.00 | 0.00793645 | 21.00 | 0.00793354 | 51.2511 | 26689.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 119091.220 | 84636.693 | 4.944613 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7525 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.944613 | 5.94919463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 122325.74 | 89026.66 | 1.0272 | 5.94919463 | 4.944613 | 26.36 | 18.99 | 0.01071168 | 53800.6 | 11.02 | 11.02 | 0.00850000 | 32510.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10823.812 | 111501.93 | 33.74 | 0.01653608 | 25.09 | 1.19517000 | 24.1712 | 24.00 | 0.00884973 | 24.00 | 0.00884973 | 47.5769 | 67849.04 | 0.00 | 122799.03 | 86038.73 | 5.71424641 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.92 | 11.90 | 0.00866239 | 33832.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8991.532 | 8991.532 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.944613 | 5.94919463 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 21:50:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8991.53 | 8991.53 | 1.0000 | 1.78475839 | 1.483384 | 7.79 | 6.86 | 0.00577723 | 22356.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8991.53 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 80.5705 | 21.00 | 0.00793391 | 21.00 | 0.00793391 | 51.2534 | 27840.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.75 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.26 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4376.83 | 490.50 | 0.00 |
CORE_MID | 3070.83 | 1729.67 | 0.33 |
CORE_TOP | 2909.83 | 2132.17 | 57.00 |
PERIMETER_TOP_ZN_3 | 3540.00 | 2391.83 | 435.00 |
PERIMETER_TOP_ZN_2 | 3589.00 | 2282.83 | 464.67 |
PERIMETER_TOP_ZN_1 | 3938.00 | 1728.33 | 389.17 |
PERIMETER_TOP_ZN_4 | 3427.33 | 2384.00 | 452.67 |
PERIMETER_BOT_ZN_3 | 3370.00 | 2203.17 | 108.67 |
PERIMETER_BOT_ZN_2 | 3751.83 | 1817.33 | 162.67 |
PERIMETER_BOT_ZN_1 | 4243.83 | 2089.33 | 894.00 |
PERIMETER_BOT_ZN_4 | 3648.50 | 1824.17 | 131.00 |
PERIMETER_MID_ZN_3 | 3505.17 | 2139.83 | 192.17 |
PERIMETER_MID_ZN_2 | 2951.83 | 1845.67 | 272.00 |
PERIMETER_MID_ZN_1 | 4110.67 | 1409.33 | 247.83 |
PERIMETER_MID_ZN_4 | 3505.17 | 2045.33 | 249.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5060.17 | 3515.33 | 1432.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.33 | 7.00 | 0.33 | 5.50 |
PERIMETER_TOP_ZN_2 | 0.33 | 43.17 | 0.33 | 42.50 |
PERIMETER_TOP_ZN_1 | 0.17 | 43.33 | 0.17 | 41.33 |
PERIMETER_TOP_ZN_4 | 0.33 | 34.17 | 0.33 | 23.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 23.83 | 0.00 | 23.83 |
PERIMETER_BOT_ZN_1 | 68.00 | 192.50 | 68.00 | 191.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 21.00 | 0.00 | 14.83 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 28.33 | 0.00 | 28.33 |
PERIMETER_MID_ZN_1 | 0.00 | 37.17 | 0.00 | 36.67 |
PERIMETER_MID_ZN_4 | 0.00 | 26.33 | 0.00 | 18.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 68.33 | 312.17 | 68.33 | 295.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.612 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.494 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.489 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.574 | 0.029 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.782 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.760 | 0.029 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.820 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.519 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.687 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.717 | 1.255 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.691 | 0.016 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.577 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.726 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.776 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.806 | 0.026 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 9628788.01 | 0.00 | 9628788.01 | 0.00 | 9628788.01 | 13393058.27 | 5961.63 | 159.55 | 2638.82 | 2.11 |
CORE_MID | 7779529.79 | 0.00 | 7779529.79 | 0.00 | 7779529.79 | 13393058.27 | 7329.59 | 50.24 | 1380.17 | 2.50 |
CORE_TOP | 7713938.04 | 0.00 | 7713938.04 | 0.00 | 7713938.04 | 13393058.27 | 7491.65 | 23.10 | 1245.25 | 3.17 |
PERIMETER_TOP_ZN_3 | 1908217.87 | 0.00 | 1908217.87 | 189985.33 | 2098203.20 | 2823374.22 | 5401.48 | 61.53 | 3296.98 | 3.17 |
PERIMETER_TOP_ZN_2 | 1645593.69 | 0.00 | 1645593.69 | 126656.12 | 1772249.82 | 1787429.43 | 4300.69 | 2.90 | 4456.41 | 3.17 |
PERIMETER_TOP_ZN_1 | 2522967.08 | 0.00 | 2522967.08 | 189985.33 | 2712952.41 | 2823374.22 | 4388.58 | 585.96 | 3785.47 | 3.17 |
PERIMETER_TOP_ZN_4 | 1727302.28 | 0.00 | 1727302.28 | 126656.12 | 1853958.40 | 1787312.18 | 4321.29 | 14.88 | 4423.83 | 3.17 |
PERIMETER_BOT_ZN_3 | 1724139.97 | 0.00 | 1724139.97 | 101014.83 | 1825154.80 | 2823374.22 | 6334.18 | 240.93 | 2184.89 | 2.11 |
PERIMETER_BOT_ZN_2 | 1445338.81 | 0.00 | 1445338.81 | 67342.82 | 1512681.63 | 1787429.43 | 4449.57 | 54.75 | 4255.68 | 2.11 |
PERIMETER_BOT_ZN_1 | 2376163.30 | 0.00 | 2376163.30 | 4199580.43 | 6575743.73 | 2823374.22 | 4984.00 | 102.59 | 3673.42 | 2.11 |
PERIMETER_BOT_ZN_4 | 1453520.23 | 0.00 | 1453520.23 | 67342.82 | 1520863.04 | 1787312.18 | 4756.78 | 117.38 | 3885.85 | 2.11 |
PERIMETER_MID_ZN_3 | 1916091.24 | 0.00 | 1916091.24 | 158148.70 | 2074239.94 | 2823374.22 | 5201.60 | 93.39 | 3465.01 | 2.50 |
PERIMETER_MID_ZN_2 | 1649382.43 | 0.00 | 1649382.43 | 105431.83 | 1754814.26 | 1787429.43 | 4292.85 | 9.86 | 4457.29 | 911.50 |
PERIMETER_MID_ZN_1 | 2575963.56 | 0.00 | 2575963.56 | 158148.70 | 2734112.26 | 2823374.22 | 4778.81 | 68.71 | 3912.48 | 2.50 |
PERIMETER_MID_ZN_4 | 1695776.18 | 0.00 | 1695776.18 | 105431.83 | 1801208.01 | 1787312.18 | 4342.10 | 23.58 | 4394.32 | 2.50 |
Total Facility | 47762712.47 | 0.00 | 47762712.47 | 5595724.86 | 53358437.33 | 67843644.98 | 7578.85 | 1172.24 | 4512.42 | 912.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.4498 | 0.0000 | 0.4498 | 0.0000 | 0.4498 | 0.4247 | 3146.75 | 159.55 | 2636.71 |
CORE_MID | 0.3633 | 0.0000 | 0.3633 | 0.0000 | 0.3633 | 0.4247 | 4515.09 | 50.24 | 1377.67 |
CORE_TOP | 0.3602 | 0.0000 | 0.3602 | 0.0000 | 0.3602 | 0.4247 | 4677.32 | 23.10 | 1242.58 |
PERIMETER_TOP_ZN_3 | 0.0891 | 0.0000 | 0.0891 | 0.0046 | 0.0937 | 0.0895 | 2587.15 | 61.53 | 3294.32 |
PERIMETER_TOP_ZN_2 | 0.0768 | 0.0000 | 0.0768 | 0.0030 | 0.0799 | 0.0567 | 1486.36 | 2.90 | 4453.74 |
PERIMETER_TOP_ZN_1 | 0.1178 | 0.0000 | 0.1178 | 0.0046 | 0.1224 | 0.0895 | 1574.24 | 585.96 | 3782.80 |
PERIMETER_TOP_ZN_4 | 0.0807 | 0.0000 | 0.0807 | 0.0030 | 0.0837 | 0.0567 | 1506.95 | 14.88 | 4421.16 |
PERIMETER_BOT_ZN_3 | 0.0805 | 0.0000 | 0.0805 | 0.0024 | 0.0829 | 0.0895 | 3519.29 | 240.93 | 2182.78 |
PERIMETER_BOT_ZN_2 | 0.0675 | 0.0000 | 0.0675 | 0.0016 | 0.0691 | 0.0567 | 1634.68 | 54.75 | 4253.57 |
PERIMETER_BOT_ZN_1 | 0.1110 | 0.0000 | 0.1110 | 0.1940 | 0.3050 | 0.0895 | 2169.11 | 102.59 | 3671.30 |
PERIMETER_BOT_ZN_4 | 0.0679 | 0.0000 | 0.0679 | 0.0016 | 0.0695 | 0.0567 | 1941.89 | 117.38 | 3883.74 |
PERIMETER_MID_ZN_3 | 0.0895 | 0.0000 | 0.0895 | 0.0038 | 0.0933 | 0.0895 | 2387.10 | 93.39 | 3462.51 |
PERIMETER_MID_ZN_2 | 0.0714 | 0.0000 | 0.0714 | 0.0027 | 0.0740 | 0.0567 | 1469.68 | 5.03 | 3559.29 |
PERIMETER_MID_ZN_1 | 0.1203 | 0.0000 | 0.1203 | 0.0038 | 0.1241 | 0.0895 | 1964.31 | 68.71 | 3909.98 |
PERIMETER_MID_ZN_4 | 0.0792 | 0.0000 | 0.0792 | 0.0025 | 0.0817 | 0.0567 | 1527.60 | 23.58 | 4391.82 |
Total Facility | 2.2250 | 0.0000 | 2.2250 | 0.2276 | 2.4526 | 2.1513 | 4762.85 | 1172.24 | 4509.14 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 24070839.64 | 0.00 | 24070839.64 | 22614548.33 | 4272.58 | 0.00 | 4487.42 | 2.11 |
PACU_VAV_MID | 22606991.58 | 0.00 | 22606991.58 | 22614548.33 | 4271.54 | 0.00 | 4488.46 | 2.50 |
PACU_VAV_TOP | 22464058.05 | 0.00 | 22464058.05 | 22614548.33 | 4288.10 | 0.85 | 4471.05 | 3.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1244 | 0.0000 | 1.1244 | 0.7171 | 1457.69 | 0.00 | 4485.31 |
PACU_VAV_MID | 1.0558 | 0.0000 | 1.0558 | 0.7171 | 1457.04 | 0.00 | 4485.96 |
PACU_VAV_TOP | 1.0490 | 0.0000 | 1.0490 | 0.7171 | 1473.77 | 0.85 | 4468.38 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 1386.17 | 0.00 | 0.00 | 0.00 | 3101.25 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 1319.21 | 0.00 | 0.00 | 0.00 | 3169.25 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 1253.89 | 0.00 | 0.00 | 0.00 | 3221.97 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.2805 | 0.0000 | 0.0000 | 0.0000 | 1.1370 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.9994 | 0.0000 | 0.0000 | 0.0000 | 1.1498 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0466 | 0.0000 | 0.0000 | 0.0000 | 1.1413 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
Electricity:Building | 1020.33 | 13465.67 | 28-MAY-17:20 | 74341.76 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1020.33 | 13465.67 | 28-MAY-17:20 | 74341.76 | 25-OCT-07:10 |
InteriorLights:Electricity | 300.64 | 987.92 | 28-MAY-17:20 | 32642.50 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.64 | 987.92 | 28-MAY-17:20 | 32642.50 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 300.64 | 987.92 | 28-MAY-17:20 | 32642.50 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.64 | 987.92 | 28-MAY-17:20 | 32642.50 | 25-OCT-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.10 | 422.10 | 26-MAR-17:10 | 2793.69 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.77 | 36.00 | 01-JAN-09:40 | 1358.45 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.77 | 36.00 | 01-JAN-09:40 | 1358.45 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.89 | 267.21 | 28-MAY-17:10 | 1768.58 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.89 | 422.10 | 12-MAR-17:10 | 2793.68 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.56 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.56 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:40 | 859.95 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.50 | 22.79 | 01-JAN-09:40 | 859.95 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.06 | 422.10 | 26-MAR-17:10 | 2793.69 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.73 | 36.00 | 01-JAN-09:40 | 1358.45 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.88 | 267.21 | 28-MAY-17:10 | 1768.58 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.47 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.87 | 422.10 | 12-MAR-17:10 | 2793.68 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.54 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.89 | 267.21 | 12-MAR-17:10 | 1768.52 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:30 | 859.95 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.49 | 22.79 | 01-JAN-09:30 | 859.95 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.10 | 422.10 | 26-MAR-17:10 | 2793.69 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.77 | 36.00 | 01-JAN-09:40 | 1358.45 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.77 | 36.00 | 01-JAN-09:40 | 1358.45 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.89 | 267.21 | 28-MAY-17:10 | 1768.58 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.49 | 22.79 | 01-JAN-07:50 | 860.01 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.89 | 422.10 | 12-MAR-17:10 | 2793.68 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.56 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.56 | 36.00 | 01-JAN-07:50 | 1358.45 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.91 | 267.21 | 12-MAR-17:10 | 1768.52 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:40 | 859.95 | 01-FEB-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.50 | 22.79 | 01-JAN-09:40 | 859.95 | 01-FEB-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 642.35 | 367.92 | 01-JAN-00:10 | 101298.78 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
ElectricityPurchased:Plant | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
ElectricityNet:Plant | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
Cogeneration:ElectricityNet | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1755.85 | 13840.93 | 28-MAY-17:30 | 160184.79 | 30-AUG-16:00 |
Heating:Electricity | 17.75 | 0.00 | 01-JAN-00:10 | 96427.78 | 06-FEB-07:10 |
General:Heating:Electricity | 17.75 | 0.00 | 01-JAN-00:10 | 96427.78 | 06-FEB-07:10 |
Fans:Electricity | 84.87 | 0.00 | 01-JAN-00:10 | 14592.01 | 30-AUG-16:00 |
General:Fans:Electricity | 84.87 | 0.00 | 01-JAN-00:10 | 14592.01 | 30-AUG-16:00 |
ExteriorLights:Electricity | 50.86 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.86 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 512.82 | 0.00 | 01-JAN-00:10 | 74944.89 | 21-JUL-16:00 |
General:Cooling:Electricity | 512.82 | 0.00 | 01-JAN-00:10 | 74944.89 | 21-JUL-16:00 |
Electricity:Plant | 42.31 | 0.00 | 01-JAN-00:10 | 5362.35 | 23-JAN-12:30 |
WaterSystems:Electricity | 42.17 | 0.00 | 01-JAN-00:10 | 5355.50 | 23-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 42.17 | 0.00 | 01-JAN-00:10 | 5355.50 | 23-JAN-12:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
WIRED_LTG_ELECTRICITY | 8.45 | 0.00 | 01-JAN-00:10 | 917.25 | 25-OCT-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 17-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3811.24 | 0.00 | 01-JAN-00:10 | 449472.37 | 06-OCT-14:10 |
EnergyTransfer:Building | 1540.86 | 0.00 | 01-JAN-00:10 | 164706.37 | 10-OCT-13:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 296.65 | 0.00 | 01-JAN-00:10 | 25184.71 | 10-OCT-08:00 |
Heating:EnergyTransfer | 9.20 | 0.00 | 01-JAN-00:10 | 64069.93 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.20 | 0.00 | 01-JAN-00:10 | 64069.93 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1531.67 | 0.00 | 01-JAN-00:10 | 164706.37 | 10-OCT-13:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 296.65 | 0.00 | 01-JAN-00:10 | 25184.71 | 10-OCT-08:00 |
General:Cooling:EnergyTransfer | 1531.67 | 0.00 | 01-JAN-00:10 | 164706.37 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 296.65 | 0.00 | 01-JAN-00:10 | 25184.71 | 10-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 56.73 | 0.00 | 01-JAN-00:10 | 10324.02 | 18-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.93 | 0.00 | 01-JAN-00:10 | 7490.29 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.93 | 0.00 | 01-JAN-00:10 | 7490.29 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.80 | 0.00 | 01-JAN-00:10 | 10324.02 | 18-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.80 | 0.00 | 01-JAN-00:10 | 10324.02 | 18-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.96 | 0.00 | 01-JAN-00:10 | 4912.76 | 10-OCT-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 2210.59 | 31-DEC-12:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 2210.59 | 31-DEC-12:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.25 | 0.00 | 01-JAN-00:10 | 4912.76 | 10-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.25 | 0.00 | 01-JAN-00:10 | 4912.76 | 10-OCT-14:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 37.44 | 0.00 | 01-JAN-00:10 | 5296.06 | 10-OCT-15:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.37 | 0.00 | 01-JAN-00:10 | 2105.69 | 31-DEC-12:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.37 | 0.00 | 01-JAN-00:10 | 2105.69 | 31-DEC-12:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 37.07 | 0.00 | 01-JAN-00:10 | 5296.06 | 10-OCT-15:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 37.07 | 0.00 | 01-JAN-00:10 | 5296.06 | 10-OCT-15:00 |
EnergyTransfer:Zone:CORE_MID | 215.93 | 0.00 | 01-JAN-00:10 | 19744.94 | 10-OCT-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2639.36 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2639.36 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 215.92 | 0.00 | 01-JAN-00:10 | 19744.94 | 10-OCT-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 215.92 | 0.00 | 01-JAN-00:10 | 19744.94 | 10-OCT-08:00 |
EnergyTransfer:Zone:CORE_TOP | 219.53 | 0.00 | 01-JAN-00:10 | 21295.75 | 05-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.16 | 0.00 | 01-JAN-00:10 | 9981.74 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.16 | 0.00 | 01-JAN-00:10 | 9981.74 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 219.37 | 0.00 | 01-JAN-00:10 | 21295.75 | 05-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 219.37 | 0.00 | 01-JAN-00:10 | 21295.75 | 05-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.07 | 0.00 | 01-JAN-00:10 | 7720.97 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.92 | 0.00 | 01-JAN-00:10 | 7530.73 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.92 | 0.00 | 01-JAN-00:10 | 7530.73 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.15 | 0.00 | 01-JAN-00:10 | 7720.97 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 56.15 | 0.00 | 01-JAN-00:10 | 7720.97 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.45 | 0.00 | 01-JAN-00:10 | 7701.81 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.44 | 0.00 | 01-JAN-00:10 | 4621.35 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.44 | 0.00 | 01-JAN-00:10 | 4621.35 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.01 | 0.00 | 01-JAN-00:10 | 7701.81 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.01 | 0.00 | 01-JAN-00:10 | 7701.81 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.68 | 0.00 | 01-JAN-00:10 | 11963.37 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.52 | 0.00 | 01-JAN-00:10 | 6098.90 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.52 | 0.00 | 01-JAN-00:10 | 6098.90 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.16 | 0.00 | 01-JAN-00:10 | 11963.37 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.16 | 0.00 | 01-JAN-00:10 | 11963.37 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.38 | 0.00 | 01-JAN-00:10 | 8895.24 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.54 | 0.00 | 01-JAN-00:10 | 4373.65 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.54 | 0.00 | 01-JAN-00:10 | 4373.65 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.84 | 0.00 | 01-JAN-00:10 | 8895.24 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.84 | 0.00 | 01-JAN-00:10 | 8895.24 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.91 | 0.00 | 01-JAN-00:10 | 7233.14 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 2576.62 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 2576.62 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.83 | 0.00 | 01-JAN-00:10 | 7233.14 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 54.83 | 0.00 | 01-JAN-00:10 | 7233.14 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.53 | 0.00 | 01-JAN-00:10 | 6922.77 | 11-SEP-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1526.49 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 1526.49 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.50 | 0.00 | 01-JAN-00:10 | 6922.77 | 11-SEP-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.50 | 0.00 | 01-JAN-00:10 | 6922.77 | 11-SEP-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 80.17 | 0.00 | 01-JAN-00:10 | 12643.24 | 30-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 6794.63 | 05-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.02 | 0.00 | 01-JAN-00:10 | 6794.63 | 05-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 78.15 | 0.00 | 01-JAN-00:10 | 12643.24 | 30-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 78.15 | 0.00 | 01-JAN-00:10 | 12643.24 | 30-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.38 | 0.00 | 01-JAN-00:10 | 7542.66 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1451.25 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1451.25 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.35 | 0.00 | 01-JAN-00:10 | 7542.66 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 46.35 | 0.00 | 01-JAN-00:10 | 7542.66 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 55.24 | 0.00 | 01-JAN-00:10 | 7132.62 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.17 | 0.00 | 01-JAN-00:10 | 3544.22 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.17 | 0.00 | 01-JAN-00:10 | 3544.22 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 55.07 | 0.00 | 01-JAN-00:10 | 7132.62 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 55.07 | 0.00 | 01-JAN-00:10 | 7132.62 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.56 | 0.00 | 01-JAN-00:10 | 7453.25 | 12-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2219.16 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2219.16 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.47 | 0.00 | 01-JAN-00:10 | 7453.25 | 12-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.47 | 0.00 | 01-JAN-00:10 | 7453.25 | 12-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.88 | 0.00 | 01-JAN-00:10 | 10962.80 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 2795.58 | 20-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 2795.58 | 20-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.79 | 0.00 | 01-JAN-00:10 | 10962.80 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.79 | 0.00 | 01-JAN-00:10 | 10962.80 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.37 | 0.00 | 01-JAN-00:10 | 8330.77 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.10 | 0.00 | 01-JAN-00:10 | 2024.85 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.10 | 0.00 | 01-JAN-00:10 | 2024.85 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.27 | 0.00 | 01-JAN-00:10 | 8330.77 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.27 | 0.00 | 01-JAN-00:10 | 8330.77 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
EnergyTransfer:HVAC | 2230.95 | 0.00 | 01-JAN-00:10 | 291589.01 | 06-OCT-14:10 |
HeatingCoils:EnergyTransfer | 17.75 | 0.00 | 01-JAN-00:10 | 96427.78 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2213.20 | 0.00 | 01-JAN-00:10 | 291589.01 | 06-OCT-14:10 |
EnergyTransfer:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -296.649 | 0.000 | 0.000 | 32.697 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.399 |
CORE_MID | 0.000 | 0.000 | 0.003 | -215.924 | 0.000 | 0.000 | 33.249 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -4.681 |
CORE_TOP | 0.000 | 0.000 | 0.161 | -219.368 | 0.000 | 0.000 | 33.729 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -1.875 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.925 | -56.146 | 0.000 | 0.000 | 7.193 | 8.767 | 24.333 | 24.382 | 0.000 | 0.216 | 7.727 | 0.000 | -16.541 | 0.000 | -0.855 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.442 | -49.009 | 0.000 | 0.000 | 4.507 | 5.488 | 15.404 | 34.554 | 0.000 | 0.138 | 0.000 | 0.000 | -10.400 | 0.000 | -0.595 | -0.528 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.518 | -74.161 | 0.000 | 0.000 | 7.038 | 8.555 | 24.332 | 59.521 | 0.000 | 0.201 | 0.001 | 0.000 | -16.193 | 0.000 | -0.965 | -8.848 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.535 | -48.842 | 0.000 | 0.000 | 4.571 | 5.502 | 15.403 | 34.180 | 0.000 | 0.144 | 0.112 | 0.000 | -11.007 | 0.000 | -0.599 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.078 | -54.833 | 0.000 | 0.000 | 7.133 | 8.731 | 24.333 | 24.575 | 0.000 | 0.122 | 8.098 | 0.000 | -17.737 | 0.000 | -0.499 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.029 | -47.504 | 0.000 | 0.000 | 4.449 | 5.474 | 15.404 | 34.636 | 0.000 | 0.074 | 0.000 | 0.000 | -11.515 | 0.000 | -0.357 | -0.690 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.019 | -78.148 | 0.000 | 0.000 | 7.038 | 8.540 | 24.332 | 59.888 | 0.000 | 10.810 | 0.000 | 0.000 | -17.845 | 0.000 | -12.775 | -3.858 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.030 | -46.350 | 0.000 | 0.000 | 4.490 | 5.485 | 15.403 | 34.256 | 0.000 | 0.075 | 0.001 | 0.000 | -12.194 | 0.000 | -0.360 | -0.836 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.167 | -55.070 | 0.000 | 0.000 | 7.122 | 8.767 | 24.333 | 24.349 | 0.000 | 0.183 | 8.643 | 0.000 | -17.720 | 0.000 | -0.773 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.092 | -47.470 | 0.000 | 0.000 | 3.309 | 5.488 | 15.404 | 34.521 | 0.000 | 0.117 | 0.126 | 0.000 | -11.053 | 0.000 | -0.533 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.084 | -72.793 | 0.000 | 0.000 | 6.981 | 8.555 | 24.332 | 59.498 | 0.000 | 0.170 | 0.000 | 0.000 | -17.228 | 0.000 | -0.863 | -8.737 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.101 | -47.273 | 0.000 | 0.000 | 4.519 | 5.502 | 15.403 | 34.145 | 0.000 | 0.119 | 0.001 | 0.000 | -11.766 | 0.000 | -0.539 | -0.211 |
TOPFLOOR_PLENUM | 2.928 | -53.796 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.231 | 51.971 | 0.000 | 0.000 | 0.000 | -1.334 | 0.000 |
MIDFLOOR_PLENUM | 0.710 | -31.254 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.263 | 31.660 | 0.000 | 0.000 | 0.000 | -1.379 | 0.000 |
FIRSTFLOOR_PLENUM | 0.375 | -37.065 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.197 | 37.647 | 0.000 | 0.000 | 0.000 | -1.154 | 0.000 |
Total Facility | 4.013 | -122.115 | 5.183 | -1409.540 | 0.000 | 0.000 | 168.026 | 300.639 | 719.689 | 458.505 | 0.000 | 13.060 | 145.991 | 0.000 | -171.200 | 0.000 | -23.580 | -88.665 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | -43444.59 | 0.00 | 0.00 | 290.12 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 35532.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | -34544.51 | 0.00 | 0.00 | 307.60 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 30999.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-JUL-04:02 | 0.00 | 0.00 | 0.00 | -34492.64 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31838.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-15:23 | 0.00 | 0.00 | 0.00 | -11683.37 | 0.00 | 0.00 | 26.90 | 36.00 | 478.42 | 3148.46 | 0.00 | 79.93 | 7913.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 07-MAY-10:22 | 0.00 | 0.00 | 0.00 | -12688.20 | 0.00 | 0.00 | 14.99 | 22.79 | 302.86 | 5570.15 | 0.00 | 29.35 | 6748.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-14:01 | 0.00 | 0.00 | 0.00 | -16729.87 | 0.00 | 0.00 | 21.43 | 36.00 | 478.41 | 11917.51 | 0.00 | 0.00 | 4297.76 | 0.00 | -0.00 | 0.00 | -21.24 | 0.00 |
PERIMETER_TOP_ZN_4 | 01-OCT-16:12 | 0.00 | 0.00 | 0.00 | -13745.57 | 0.00 | 0.00 | 14.92 | 22.79 | 302.86 | 7170.22 | 0.00 | 0.00 | 6236.16 | 0.00 | -0.00 | 0.00 | -1.38 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-AUG-04:02 | 0.00 | 0.00 | 0.00 | -8520.87 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 2.56 | 8139.59 | 0.00 | -180.71 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-OCT-09:42 | 0.00 | 0.00 | 0.00 | -11131.49 | 0.00 | 0.00 | 15.87 | 22.79 | 302.86 | 6457.24 | 0.00 | 17.55 | 4315.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-15:12 | 0.00 | 0.00 | 0.00 | -14176.19 | 0.00 | 0.00 | 22.96 | 36.00 | 478.41 | 9016.34 | 0.00 | 0.00 | 4637.25 | 0.00 | -0.00 | 0.00 | -14.78 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-16:52 | 0.00 | 0.00 | 0.00 | -11977.11 | 0.00 | 0.00 | 14.91 | 22.79 | 302.86 | 6911.87 | 0.00 | 18.05 | 4706.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-15:23 | 0.00 | 0.00 | 0.00 | -9680.28 | 0.00 | 0.00 | 28.51 | 36.00 | 478.42 | 3253.96 | 0.00 | 71.42 | 5811.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 03-SEP-09:42 | 0.00 | 0.00 | 0.00 | -12574.43 | 0.00 | 0.00 | 14.71 | 22.79 | 302.86 | 7262.91 | 0.00 | 10.17 | 4960.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-11:42 | 0.00 | 0.00 | 0.00 | -14349.41 | 0.00 | 0.00 | 23.19 | 36.00 | 478.41 | 10258.69 | 0.00 | 77.39 | 3475.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 08-OCT-15:52 | 0.00 | 0.00 | 0.00 | -12736.88 | 0.00 | 0.00 | 14.82 | 22.79 | 302.86 | 5814.85 | 0.00 | 55.42 | 6526.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 18-JUL-14:50 | 0.00 | -10323.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 10291.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-OCT-14:10 | 0.00 | -4912.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 4864.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-OCT-15:00 | 0.00 | -5295.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 5251.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-04:02 | 0.00 | 7952.06 | 0.00 | -205422.62 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.87 | 183608.08 | 0.00 | -2781.01 | 0.00 | -0.25 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-MAR-06:01 | 0.00 | 0.00 | 17223.12 | 0.00 | 0.00 | 0.00 | 887.04 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23284.10 |
CORE_TOP | 06-FEB-07:12 | 0.00 | 0.00 | 18660.07 | 0.00 | 0.00 | 0.00 | 875.16 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24709.17 |
PERIMETER_TOP_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 9728.80 | 0.00 | 0.00 | 0.00 | 111.35 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2269.92 | 0.00 | -23.19 | -8335.85 |
PERIMETER_TOP_ZN_2 | 06-FEB-06:11 | 0.00 | 0.00 | 5779.73 | 0.00 | 0.00 | 0.00 | 70.50 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1526.69 | 0.00 | -15.48 | -4807.41 |
PERIMETER_TOP_ZN_1 | 06-FEB-06:11 | 0.00 | 0.00 | 8971.34 | 0.00 | 0.00 | 0.00 | 108.88 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2348.81 | 0.00 | -24.40 | -7495.82 |
PERIMETER_TOP_ZN_4 | 06-FEB-06:11 | 0.00 | 0.00 | 5503.39 | 0.00 | 0.00 | 0.00 | 70.14 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1550.13 | 0.00 | -15.68 | -4507.08 |
PERIMETER_BOT_ZN_3 | 10-JAN-06:11 | 0.00 | 0.00 | 5661.06 | 0.00 | 0.00 | 0.00 | 98.94 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3014.66 | 0.00 | -28.02 | -3506.14 |
PERIMETER_BOT_ZN_2 | 06-FEB-07:04 | 0.00 | 0.00 | 3581.71 | 0.00 | 0.00 | 0.00 | 122.37 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1836.70 | 0.00 | -10.77 | -2547.10 |
PERIMETER_BOT_ZN_1 | 21-DEC-07:10 | 0.00 | 0.00 | 7068.33 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 13808.28 | 0.00 | -3336.62 | 0.00 | -18823.99 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-07:04 | 0.00 | 0.00 | 3544.67 | 0.00 | 0.00 | 0.00 | 122.36 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1847.48 | 0.00 | -10.77 | -2499.24 |
PERIMETER_MID_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 6894.78 | 0.00 | 0.00 | 0.00 | 104.17 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2615.01 | 0.00 | -22.00 | -5150.76 |
PERIMETER_MID_ZN_2 | 13-MAR-05:12 | 0.00 | 0.00 | 4378.92 | 0.00 | 0.00 | 0.00 | 63.53 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1546.94 | 0.00 | -9.31 | -3385.57 |
PERIMETER_MID_ZN_1 | 21-DEC-07:03 | 0.00 | 0.00 | 6218.15 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3271.69 | 0.00 | -50.11 | -4180.35 |
PERIMETER_MID_ZN_4 | 08-FEB-07:03 | 0.00 | 0.00 | 4128.46 | 0.00 | 0.00 | 0.00 | 121.82 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.55 | 0.00 | -13.04 | -3764.15 |
TOPFLOOR_PLENUM | 06-FEB-07:04 | 9024.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -38.85 | -8985.46 |
MIDFLOOR_PLENUM | 31-DEC-14:03 | 3641.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3642.46 |
FIRSTFLOOR_PLENUM | 05-JAN-06:01 | 5311.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -54.32 | -5257.25 |
Total Facility | 06-FEB-07:01 | -2244.65 | 9543.83 | 88712.68 | -9543.83 | 0.00 | 0.00 | 4491.44 | 10880.98 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26655.40 | 0.00 | -21392.33 | -76289.57 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2633 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7542 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.8722 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2731 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9446 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6316 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3527 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4361 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3378 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6366 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4061 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6421 | 2.6421 | 0.7715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1346 | 2.1346 | 0.7471 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2668 | 2.2668 | 0.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6955 | 0.6955 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6963 | 0.6963 | 0.1393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8449 | 0.8449 | 0.1690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7697 | 0.7697 | 0.1539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6030 | 0.6030 | 0.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6263 | 0.6263 | 0.1253 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7393 | 0.7393 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6526 | 0.6526 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6063 | 0.6063 | 0.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6740 | 0.6740 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7542 | 0.7542 | 0.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7032 | 0.7032 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2633 | 4.7542 | 5.2633 | 1.3527 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.8722 | 4.2641 | 4.8722 | 1.3378 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2731 | 4.9446 | 5.2731 | 1.4061 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3210 | 1.3210 | 0.7715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0673 | 1.0673 | 0.7471 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1334 | 1.1334 | 0.7798 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3478 | 0.3478 | 0.1641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3482 | 0.3482 | 0.1393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4224 | 0.4224 | 0.1690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3848 | 0.3848 | 0.1539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3015 | 0.3015 | 0.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3132 | 0.3132 | 0.1253 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3696 | 0.3696 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3263 | 0.3263 | 0.1305 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3031 | 0.3031 | 0.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3370 | 0.3370 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3771 | 0.3771 | 0.1576 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3516 | 0.3516 | 0.1406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6316 | 1.3527 | 1.3527 | 1.3527 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4361 | 1.3378 | 1.3378 | 1.3378 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6366 | 1.4061 | 1.4061 | 1.4061 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 68.33 |
Number of hours cooling loads not met | 295.00 |
Number of hours not met | 363.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 17.75 | 96427.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 512.82 | 74944.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.64 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.86 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 84.87 | 14592.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 42.17 | 5355.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1755.85 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1755.85 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.34 |
Space Heating | 3.56 |
Space Cooling | 102.93 |
Fans (All) | 17.04 |
Service Water Heating | 8.46 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 352.43 |
Subtotal | 352.43 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.12 |
Space Heating | 1.01 |
Space Cooling | 29.21 |
Fans (All) | 4.83 |
Service Water Heating | 2.40 |
Receptacle Equipment | 40.99 |
Miscellaneous | 4.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8179.50 | 580.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8647.67 | 112.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8578.33 | 181.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8574.00 | 186.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8531.00 | 229.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8653.33 | 106.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8631.50 | 128.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8620.50 | 139.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8673.33 | 86.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8593.50 | 166.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8586.17 | 173.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8549.00 | 211.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8506.67 | 253.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8179.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 580.50 | 0.00 | 0.00 | 0.00 |
Average | 8616.89 | 143.11 | 0.00 | 0.00 | 0.00 |
Sum | 155104.00 | 2576.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128120.67 | 183.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 183.33 | 0.00 | 0.00 | 0.00 |
Average | 34133.07 | 10.26 | 0.00 | 0.00 | 0.00 |
Sum | 614395.33 | 184.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7881.00 | 879.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7587.50 | 1172.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7547.00 | 1213.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7529.50 | 1230.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7544.50 | 1215.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7980.33 | 779.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7764.33 | 995.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6992.17 | 1767.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7729.67 | 1030.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7573.50 | 1186.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7518.33 | 1241.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7490.17 | 1269.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7479.33 | 1280.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8023.83 | 736.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8261.83 | 498.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8406.17 | 353.83 | 0.00 | 0.00 | 0.00 |
Min | 6992.17 | 26.83 | 0.00 | 0.00 | 0.00 |
Max | 8733.17 | 1767.83 | 0.00 | 0.00 | 0.00 |
Average | 7820.85 | 939.15 | 0.00 | 0.00 | 0.00 |
Sum | 140775.33 | 16904.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127966.67 | 337.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24893.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24894.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20320.00 | 4589.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24897.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24896.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.67 | 4589.00 | 0.00 | 0.00 | 0.00 |
Average | 33865.78 | 277.56 | 0.00 | 0.00 | 0.00 |
Sum | 609584.00 | 4996.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194344E+11 | 39334.81 | 02-JAN-06:12 | 16.00 | 15.39 | 0.198326E+10 | 2606.69 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.178999E+11 | 30623.55 | 28-FEB-06:13 | 18.47 | 17.93 | 0.180179E+10 | 2606.61 | 09-FEB-14:00 | 18.47 | 17.93 |
March | 0.218816E+11 | 38067.81 | 09-MAR-06:02 | 1.10 | -2.1 | 0.215286E+10 | 2606.65 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.227737E+11 | 35785.96 | 28-APR-05:13 | 22.90 | 21.77 | 0.191933E+10 | 2606.71 | 10-APR-13:00 | 22.90 | 21.77 |
May | 0.284030E+11 | 43448.78 | 31-MAY-05:03 | 23.80 | 21.58 | 0.207830E+10 | 2606.54 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.284876E+11 | 41936.50 | 20-JUN-04:02 | 24.50 | 23.30 | 0.207105E+10 | 2606.54 | 01-JUN-13:09 | 24.50 | 23.30 |
July | 0.284160E+11 | 42578.53 | 12-JUL-05:03 | 23.90 | 23.16 | 0.192449E+10 | 2606.54 | 03-JUL-13:09 | 23.90 | 23.16 |
August | 0.301576E+11 | 41264.36 | 01-AUG-04:03 | 23.90 | 22.80 | 0.216067E+10 | 2606.55 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.276521E+11 | 40946.57 | 01-SEP-04:23 | 24.10 | 23.23 | 0.191826E+10 | 2606.54 | 18-SEP-13:09 | 28.08 | 25.82 |
October | 0.276649E+11 | 40769.41 | 24-OCT-04:02 | 25.83 | 25.19 | 0.199561E+10 | 2606.69 | 17-OCT-13:09 | 25.83 | 25.19 |
November | 0.232080E+11 | 36220.91 | 06-NOV-07:03 | 19.08 | 17.86 | 0.197370E+10 | 2606.62 | 10-NOV-10:09 | 22.75 | 18.16 |
December | 0.206690E+11 | 38193.41 | 18-DEC-06:12 | 3.33 | 0.55 | 0.191753E+10 | 2606.66 | 08-DEC-10:00 | 3.33 | 0.55 |
Annual Sum or Average | 0.296648E+12 | 0.238969E+11 | ||||||||
Minimum of Months | 0.178999E+11 | 30623.55 | 1.10 | -2.1 | 0.180179E+10 | 2606.54 | 3.33 | 0.55 | ||
Maximum of Months | 0.301576E+11 | 43448.78 | 25.83 | 25.19 | 0.216067E+10 | 2606.71 | 28.08 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161434E+10 | 5719.75 | 19-JAN-14:50 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.198855E+10 | 6588.98 | 24-FEB-14:50 | 25.78 | 20.93 | 0.00 | 0.00 | 01-FEB-00:10 | 25.78 | 20.93 |
March | 0.262208E+10 | 6559.88 | 29-MAR-14:50 | 26.83 | 21.36 | 0.00 | 0.00 | 01-MAR-00:10 | 26.83 | 21.36 |
April | 0.410478E+10 | 9210.89 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.662770E+10 | 9911.32 | 10-MAY-14:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.14 |
June | 0.731405E+10 | 9948.30 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.696713E+10 | 10324.02 | 18-JUL-14:50 | 35.00 | 25.65 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.65 |
August | 0.706970E+10 | 10050.88 | 03-AUG-15:20 | 35.17 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 35.17 | 24.83 |
September | 0.550027E+10 | 9356.06 | 01-SEP-14:00 | 32.20 | 22.62 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 22.62 |
October | 0.534971E+10 | 9565.36 | 05-OCT-15:00 | 34.00 | 24.05 | 0.00 | 0.00 | 01-OCT-00:10 | 34.00 | 24.05 |
November | 0.273005E+10 | 7814.93 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.36 |
December | 0.190850E+10 | 6885.60 | 15-DEC-15:00 | 29.00 | 21.56 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.56 |
Annual Sum or Average | 0.537968E+11 | 0.00 | ||||||||
Minimum of Months | 0.161434E+10 | 5719.75 | 25.00 | 20.93 | 0.00 | 0.00 | 25.00 | 20.93 | ||
Maximum of Months | 0.731405E+10 | 10324.02 | 35.17 | 26.19 | 0.00 | 0.00 | 35.17 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841268E+09 | 3254.60 | 04-JAN-07:01 | 1.17 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | -1.3 |
February | 0.101838E+10 | 2754.33 | 13-FEB-07:01 | 4.08 | 0.66 | 0.00 | 0.00 | 01-FEB-00:10 | 4.08 | 0.66 |
March | 0.135010E+10 | 3487.72 | 09-MAR-07:01 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.211052E+10 | 3518.83 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.388201E+10 | 4185.08 | 30-MAY-12:03 | 30.87 | 24.09 | 0.00 | 0.00 | 01-MAY-00:10 | 30.87 | 24.09 |
June | 0.409720E+10 | 4196.70 | 12-JUN-16:00 | 33.30 | 21.04 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 21.04 |
July | 0.410936E+10 | 4530.63 | 05-JUL-15:00 | 31.70 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 31.70 | 25.84 |
August | 0.421823E+10 | 4477.45 | 28-AUG-15:30 | 33.00 | 24.29 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 24.29 |
September | 0.348507E+10 | 4509.76 | 11-SEP-14:30 | 28.55 | 24.74 | 0.00 | 0.00 | 01-SEP-00:10 | 28.55 | 24.74 |
October | 0.337382E+10 | 4912.76 | 10-OCT-14:10 | 30.83 | 22.61 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 22.61 |
November | 0.164609E+10 | 3473.40 | 06-NOV-16:00 | 28.30 | 20.26 | 0.00 | 0.00 | 01-NOV-00:10 | 28.30 | 20.26 |
December | 0.112197E+10 | 3489.70 | 18-DEC-07:01 | 2.50 | 0.21 | 0.00 | 0.00 | 01-DEC-00:10 | 2.50 | 0.21 |
Annual Sum or Average | 0.312540E+11 | 0.00 | ||||||||
Minimum of Months | 0.841268E+09 | 2754.33 | 1.17 | -2.3 | 0.00 | 0.00 | 1.17 | -2.3 | ||
Maximum of Months | 0.421823E+10 | 4912.76 | 33.30 | 25.84 | 0.00 | 0.00 | 33.30 | 25.84 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122238E+10 | 3784.50 | 03-JAN-07:07 | 2.33 | 0.16 | 0.00 | 0.00 | 01-JAN-00:10 | 2.33 | 0.16 |
February | 0.136167E+10 | 3273.95 | 13-FEB-07:01 | 4.08 | 0.66 | 0.00 | 0.00 | 01-FEB-00:10 | 4.08 | 0.66 |
March | 0.177528E+10 | 3835.77 | 09-MAR-07:01 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.248980E+10 | 3845.99 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.423969E+10 | 4510.99 | 30-MAY-12:10 | 30.87 | 24.09 | 0.00 | 0.00 | 01-MAY-00:10 | 30.87 | 24.09 |
June | 0.445835E+10 | 4523.85 | 19-JUN-14:10 | 31.05 | 25.15 | 0.00 | 0.00 | 01-JUN-00:10 | 31.05 | 25.15 |
July | 0.449457E+10 | 4978.11 | 05-JUL-14:10 | 31.70 | 26.13 | 0.00 | 0.00 | 01-JUL-00:10 | 31.70 | 26.13 |
August | 0.487701E+10 | 5052.00 | 28-AUG-15:30 | 33.00 | 24.29 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 24.29 |
September | 0.412691E+10 | 4925.48 | 11-SEP-14:30 | 28.55 | 24.74 | 0.00 | 0.00 | 01-SEP-00:10 | 28.55 | 24.74 |
October | 0.407946E+10 | 5296.06 | 10-OCT-15:00 | 30.00 | 22.39 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.39 |
November | 0.232720E+10 | 4400.23 | 06-NOV-16:50 | 26.88 | 19.82 | 0.00 | 0.00 | 01-NOV-00:10 | 26.88 | 19.82 |
December | 0.161313E+10 | 3644.61 | 18-DEC-07:07 | 2.50 | 0.21 | 0.00 | 0.00 | 01-DEC-00:10 | 2.50 | 0.21 |
Annual Sum or Average | 0.370654E+11 | 0.00 | ||||||||
Minimum of Months | 0.122238E+10 | 3273.95 | 1.18 | -2.3 | 0.00 | 0.00 | 1.18 | -2.3 | ||
Maximum of Months | 0.487701E+10 | 5296.06 | 33.00 | 26.13 | 0.00 | 0.00 | 33.00 | 26.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138112E+11 | 22478.85 | 02-JAN-06:12 | 16.00 | 15.39 | 0.183816E+10 | 2606.57 | 02-JAN-10:39 | 22.67 | 18.77 |
February | 0.128639E+11 | 15148.00 | 28-FEB-17:00 | 23.80 | 20.44 | 0.170011E+10 | 2606.66 | 27-FEB-10:09 | 23.80 | 20.44 |
March | 0.156912E+11 | 15065.47 | 30-MAR-16:00 | 25.50 | 21.27 | 0.206280E+10 | 2606.63 | 06-MAR-10:09 | 25.50 | 21.27 |
April | 0.164514E+11 | 16614.02 | 28-APR-16:00 | 32.20 | 25.55 | 0.189544E+10 | 2606.66 | 10-APR-13:00 | 32.20 | 25.55 |
May | 0.213094E+11 | 34547.18 | 31-MAY-05:03 | 23.80 | 21.58 | 0.207013E+10 | 2606.54 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.214847E+11 | 32554.39 | 13-JUN-04:02 | 23.90 | 21.88 | 0.206425E+10 | 2606.54 | 07-JUN-09:09 | 23.90 | 21.88 |
July | 0.215697E+11 | 32453.65 | 18-JUL-04:02 | 24.40 | 22.88 | 0.191743E+10 | 2606.54 | 03-JUL-13:09 | 24.40 | 22.88 |
August | 0.223456E+11 | 32404.06 | 30-AUG-04:02 | 24.45 | 22.91 | 0.215386E+10 | 2606.54 | 25-AUG-13:09 | 24.45 | 22.91 |
September | 0.202708E+11 | 32315.43 | 06-SEP-04:02 | 24.55 | 23.26 | 0.190932E+10 | 2606.54 | 18-SEP-13:09 | 28.08 | 25.82 |
October | 0.199343E+11 | 31621.78 | 06-OCT-04:02 | 25.10 | 25.10 | 0.198300E+10 | 2606.68 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.158909E+11 | 17090.83 | 06-NOV-17:00 | 26.60 | 19.72 | 0.193584E+10 | 2606.60 | 10-NOV-10:00 | 25.50 | 19.29 |
December | 0.143008E+11 | 15881.27 | 15-DEC-17:00 | 28.00 | 21.24 | 0.181434E+10 | 2606.61 | 18-DEC-14:09 | 16.17 | 10.34 |
Annual Sum or Average | 0.215924E+12 | 0.233447E+11 | ||||||||
Minimum of Months | 0.128639E+11 | 15065.47 | 16.00 | 15.39 | 0.170011E+10 | 2606.54 | 16.17 | 10.34 | ||
Maximum of Months | 0.223456E+11 | 34547.18 | 32.20 | 25.55 | 0.215386E+10 | 2606.68 | 32.20 | 25.82 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127489E+11 | 15956.29 | 02-JAN-14:40 | 26.67 | 18.58 | 0.173097E+10 | 2606.61 | 02-JAN-10:00 | 26.67 | 18.58 |
February | 0.123258E+11 | 15688.88 | 27-FEB-17:00 | 24.40 | 20.28 | 0.162567E+10 | 2606.58 | 28-FEB-10:00 | 22.20 | 19.62 |
March | 0.152933E+11 | 16338.63 | 29-MAR-16:00 | 26.60 | 21.18 | 0.198541E+10 | 2606.60 | 24-MAR-13:00 | 26.60 | 21.18 |
April | 0.167845E+11 | 19181.15 | 28-APR-16:00 | 32.20 | 25.55 | 0.186560E+10 | 2606.65 | 10-APR-13:00 | 32.20 | 25.55 |
May | 0.226263E+11 | 33931.54 | 08-MAY-04:02 | 24.32 | 22.06 | 0.206796E+10 | 2606.55 | 12-MAY-09:09 | 26.88 | 22.17 |
June | 0.230629E+11 | 34280.26 | 12-JUN-04:02 | 23.90 | 21.28 | 0.206304E+10 | 2606.60 | 07-JUN-09:09 | 23.90 | 21.28 |
July | 0.229939E+11 | 34493.80 | 11-JUL-04:02 | 24.60 | 23.70 | 0.191699E+10 | 2606.54 | 14-JUL-09:09 | 24.08 | 23.26 |
August | 0.236545E+11 | 34465.57 | 25-AUG-04:02 | 24.28 | 22.05 | 0.215168E+10 | 2606.54 | 22-AUG-13:09 | 24.28 | 22.05 |
September | 0.209652E+11 | 34204.03 | 18-SEP-04:02 | 25.00 | 23.33 | 0.190507E+10 | 2606.57 | 21-SEP-09:09 | 22.98 | 21.00 |
October | 0.201987E+11 | 34019.64 | 06-OCT-04:02 | 25.10 | 25.10 | 0.196885E+10 | 2606.68 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.152957E+11 | 17996.44 | 02-NOV-15:20 | 29.20 | 23.96 | 0.187103E+10 | 2606.65 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.134178E+11 | 16746.29 | 15-DEC-16:40 | 28.00 | 21.24 | 0.171332E+10 | 2606.58 | 11-DEC-10:20 | 28.00 | 21.24 |
Annual Sum or Average | 0.219368E+12 | 0.228656E+11 | ||||||||
Minimum of Months | 0.123258E+11 | 15688.88 | 23.90 | 18.58 | 0.162567E+10 | 2606.54 | 22.17 | 15.50 | ||
Maximum of Months | 0.236545E+11 | 34493.80 | 32.20 | 25.55 | 0.215168E+10 | 2606.68 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199832E+10 | 3929.53 | 02-JAN-13:40 | 26.00 | 18.55 | 0.345322E+09 | 549.48 | 17-JAN-14:50 | 25.00 | 19.73 |
February | 0.228894E+10 | 4003.85 | 28-FEB-15:00 | 25.00 | 20.38 | 0.328917E+09 | 549.48 | 28-FEB-10:00 | 25.00 | 20.38 |
March | 0.309351E+10 | 5163.16 | 30-MAR-13:30 | 28.55 | 22.55 | 0.401977E+09 | 549.49 | 24-MAR-13:00 | 28.55 | 22.55 |
April | 0.409909E+10 | 6243.11 | 28-APR-15:10 | 33.12 | 23.52 | 0.387523E+09 | 549.50 | 12-APR-13:00 | 33.12 | 23.52 |
May | 0.668760E+10 | 10275.03 | 29-MAY-18:12 | 29.03 | 23.48 | 0.437341E+09 | 549.47 | 04-MAY-13:00 | 29.03 | 23.48 |
June | 0.726462E+10 | 10151.75 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436161E+09 | 549.48 | 07-JUN-09:09 | 26.78 | 22.12 |
July | 0.709529E+10 | 11683.65 | 23-JUL-15:23 | 31.95 | 25.52 | 0.405804E+09 | 549.47 | 14-JUL-13:00 | 31.95 | 25.52 |
August | 0.709570E+10 | 10208.54 | 27-AUG-15:53 | 34.00 | 24.69 | 0.454759E+09 | 549.48 | 25-AUG-13:09 | 34.00 | 24.69 |
September | 0.571842E+10 | 11561.99 | 10-SEP-15:22 | 34.95 | 27.14 | 0.402748E+09 | 549.48 | 07-SEP-13:00 | 34.95 | 27.14 |
October | 0.523761E+10 | 9628.47 | 08-OCT-16:42 | 29.33 | 24.72 | 0.412447E+09 | 549.50 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.320047E+10 | 5123.45 | 02-NOV-14:00 | 29.40 | 24.47 | 0.382005E+09 | 549.48 | 06-NOV-10:30 | 24.65 | 20.15 |
December | 0.236771E+10 | 4529.88 | 15-DEC-15:00 | 29.00 | 21.56 | 0.342125E+09 | 549.47 | 08-DEC-14:39 | 29.00 | 21.56 |
Annual Sum or Average | 0.561473E+11 | 0.473713E+10 | ||||||||
Minimum of Months | 0.199832E+10 | 3929.53 | 25.00 | 18.55 | 0.328917E+09 | 549.47 | 22.17 | 15.50 | ||
Maximum of Months | 0.726462E+10 | 11683.65 | 34.95 | 27.14 | 0.454759E+09 | 549.50 | 34.95 | 27.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195831E+10 | 4321.74 | 19-JAN-10:30 | 23.85 | 21.17 | 0.227245E+09 | 347.87 | 02-JAN-10:30 | 23.85 | 21.17 |
February | 0.217209E+10 | 4507.99 | 27-FEB-10:30 | 21.90 | 19.28 | 0.216960E+09 | 347.87 | 09-FEB-10:00 | 21.90 | 19.28 |
March | 0.296943E+10 | 5192.57 | 26-MAR-11:32 | 27.93 | 20.32 | 0.265617E+09 | 347.87 | 06-MAR-10:09 | 27.93 | 20.32 |
April | 0.394492E+10 | 11683.27 | 23-APR-11:13 | 26.80 | 20.29 | 0.249684E+09 | 347.88 | 10-APR-13:00 | 26.80 | 20.29 |
May | 0.577706E+10 | 12685.27 | 07-MAY-10:22 | 30.55 | 23.68 | 0.276861E+09 | 347.86 | 04-MAY-13:00 | 30.55 | 23.68 |
June | 0.606630E+10 | 11438.16 | 25-JUN-10:23 | 29.15 | 24.33 | 0.276021E+09 | 347.86 | 07-JUN-09:09 | 29.15 | 24.33 |
July | 0.595053E+10 | 12126.09 | 23-JUL-10:02 | 31.02 | 26.38 | 0.256815E+09 | 347.86 | 24-JUL-09:30 | 30.55 | 26.01 |
August | 0.586862E+10 | 12096.66 | 06-AUG-09:23 | 29.50 | 26.85 | 0.287644E+09 | 347.86 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.479113E+10 | 12182.06 | 10-SEP-10:02 | 33.82 | 27.46 | 0.254714E+09 | 347.86 | 21-SEP-09:09 | 22.98 | 21.00 |
October | 0.456931E+10 | 12587.72 | 09-OCT-09:52 | 29.00 | 22.62 | 0.261988E+09 | 347.88 | 02-OCT-09:00 | 29.00 | 22.62 |
November | 0.285614E+10 | 5498.82 | 11-NOV-10:02 | 24.68 | 21.72 | 0.250202E+09 | 347.87 | 06-NOV-10:09 | 24.68 | 21.72 |
December | 0.208635E+10 | 3541.22 | 16-DEC-10:10 | 24.33 | 21.30 | 0.222512E+09 | 347.87 | 08-DEC-10:00 | 24.33 | 21.30 |
Annual Sum or Average | 0.490102E+11 | 0.304626E+10 | ||||||||
Minimum of Months | 0.195831E+10 | 3541.22 | 21.90 | 19.28 | 0.216960E+09 | 347.86 | 21.90 | 19.28 | ||
Maximum of Months | 0.606630E+10 | 12685.27 | 33.82 | 27.46 | 0.287644E+09 | 347.88 | 30.55 | 26.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.442132E+10 | 16729.85 | 01-JAN-14:01 | 25.83 | 18.00 | 0.390827E+09 | 549.50 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.447469E+10 | 14974.08 | 26-FEB-13:13 | 26.27 | 18.89 | 0.357664E+09 | 549.50 | 09-FEB-14:00 | 26.27 | 18.89 |
March | 0.457328E+10 | 14437.52 | 26-MAR-14:23 | 26.90 | 20.14 | 0.420022E+09 | 549.51 | 24-MAR-13:00 | 26.90 | 20.14 |
April | 0.511033E+10 | 8363.94 | 28-APR-14:20 | 32.90 | 23.03 | 0.389872E+09 | 549.51 | 10-APR-13:00 | 32.90 | 23.03 |
May | 0.686836E+10 | 12272.70 | 22-MAY-04:02 | 26.10 | 22.31 | 0.437045E+09 | 549.48 | 03-MAY-13:00 | 26.10 | 22.31 |
June | 0.706457E+10 | 10753.72 | 05-JUN-04:02 | 25.22 | 22.37 | 0.435783E+09 | 549.48 | 07-JUN-09:09 | 26.78 | 22.12 |
July | 0.708426E+10 | 14023.26 | 23-JUL-14:02 | 33.03 | 26.02 | 0.405586E+09 | 549.47 | 14-JUL-13:00 | 33.03 | 26.02 |
August | 0.786041E+10 | 14088.73 | 27-AUG-15:13 | 32.67 | 23.88 | 0.454757E+09 | 549.48 | 25-AUG-13:09 | 32.67 | 23.88 |
September | 0.712636E+10 | 14953.16 | 24-SEP-13:13 | 31.27 | 25.21 | 0.403278E+09 | 549.48 | 20-SEP-13:00 | 31.27 | 25.21 |
October | 0.818312E+10 | 15229.58 | 09-OCT-13:12 | 31.00 | 23.42 | 0.416404E+09 | 554.59 | 13-OCT-13:39 | 32.73 | 23.24 |
November | 0.623266E+10 | 16072.88 | 11-NOV-13:22 | 26.35 | 22.79 | 0.404443E+09 | 566.14 | 06-NOV-14:09 | 26.35 | 22.79 |
December | 0.516280E+10 | 16315.84 | 10-DEC-14:32 | 27.67 | 20.09 | 0.376597E+09 | 552.31 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.741622E+11 | 0.489228E+10 | ||||||||
Minimum of Months | 0.442132E+10 | 8363.94 | 25.22 | 18.00 | 0.357664E+09 | 549.47 | 14.17 | 9.63 | ||
Maximum of Months | 0.818312E+10 | 16729.85 | 33.03 | 26.02 | 0.454757E+09 | 566.14 | 33.03 | 26.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205396E+10 | 9972.76 | 01-JAN-15:22 | 25.00 | 18.55 | 0.222212E+09 | 347.84 | 02-JAN-14:00 | 27.00 | 18.67 |
February | 0.237150E+10 | 11803.28 | 26-FEB-17:12 | 24.03 | 19.67 | 0.208037E+09 | 347.83 | 28-FEB-14:00 | 25.00 | 20.38 |
March | 0.302014E+10 | 9335.92 | 26-MAR-15:43 | 25.72 | 20.08 | 0.250760E+09 | 347.84 | 24-MAR-13:00 | 25.72 | 20.08 |
April | 0.404014E+10 | 11955.99 | 16-APR-16:03 | 20.82 | 13.18 | 0.240280E+09 | 347.85 | 12-APR-13:00 | 20.82 | 13.18 |
May | 0.538990E+10 | 13583.93 | 29-MAY-16:52 | 30.60 | 23.80 | 0.275407E+09 | 347.84 | 09-MAY-13:00 | 30.60 | 23.80 |
June | 0.574370E+10 | 13596.58 | 11-JUN-16:52 | 33.30 | 21.96 | 0.274927E+09 | 347.84 | 01-JUN-13:09 | 33.30 | 21.96 |
July | 0.550238E+10 | 13594.86 | 16-JUL-16:42 | 29.78 | 24.79 | 0.255899E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.575793E+10 | 12051.76 | 27-AUG-15:53 | 34.00 | 24.69 | 0.286620E+09 | 347.84 | 25-AUG-13:09 | 34.00 | 24.69 |
September | 0.480695E+10 | 13549.25 | 03-SEP-16:32 | 31.47 | 24.85 | 0.252932E+09 | 347.84 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.466741E+10 | 13746.11 | 01-OCT-16:12 | 27.47 | 18.24 | 0.258197E+09 | 347.85 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.310763E+10 | 8626.95 | 11-NOV-16:03 | 25.82 | 22.87 | 0.238350E+09 | 347.84 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.238197E+10 | 10446.68 | 10-DEC-15:52 | 27.00 | 20.22 | 0.217540E+09 | 347.84 | 01-DEC-14:00 | 27.00 | 20.22 |
Annual Sum or Average | 0.488436E+11 | 0.298116E+10 | ||||||||
Minimum of Months | 0.205396E+10 | 8626.95 | 20.82 | 13.18 | 0.208037E+09 | 347.83 | 20.82 | 13.18 | ||
Maximum of Months | 0.575793E+10 | 13746.11 | 34.00 | 24.85 | 0.286620E+09 | 347.85 | 34.00 | 24.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256155E+10 | 3608.45 | 02-JAN-13:30 | 26.00 | 18.64 | 0.357414E+09 | 549.48 | 02-JAN-10:30 | 26.00 | 18.64 |
February | 0.240945E+10 | 3106.81 | 28-FEB-15:00 | 25.00 | 20.38 | 0.333781E+09 | 549.47 | 28-FEB-10:50 | 25.00 | 20.38 |
March | 0.298964E+10 | 3989.02 | 30-MAR-13:10 | 29.12 | 22.70 | 0.405212E+09 | 549.47 | 30-MAR-13:00 | 27.70 | 22.30 |
April | 0.340250E+10 | 4644.89 | 28-APR-15:10 | 33.12 | 23.52 | 0.388318E+09 | 549.49 | 12-APR-13:00 | 33.12 | 23.52 |
May | 0.566033E+10 | 8060.38 | 31-MAY-05:02 | 23.80 | 21.58 | 0.436843E+09 | 549.47 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.629815E+10 | 7344.16 | 05-JUN-04:02 | 25.22 | 22.37 | 0.435868E+09 | 549.48 | 01-JUN-13:09 | 25.22 | 22.37 |
July | 0.657846E+10 | 8060.81 | 24-JUL-04:02 | 26.28 | 24.56 | 0.405540E+09 | 549.48 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.710490E+10 | 8523.29 | 23-AUG-04:02 | 26.38 | 23.83 | 0.455213E+09 | 549.48 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.594164E+10 | 7212.90 | 18-SEP-04:02 | 25.00 | 23.33 | 0.403958E+09 | 549.48 | 07-SEP-13:00 | 25.00 | 23.33 |
October | 0.547621E+10 | 7921.52 | 23-OCT-04:02 | 24.92 | 24.16 | 0.417820E+09 | 549.50 | 17-OCT-13:09 | 24.92 | 24.16 |
November | 0.349404E+10 | 4764.86 | 03-NOV-14:00 | 29.40 | 23.47 | 0.398295E+09 | 549.48 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.291661E+10 | 4144.98 | 15-DEC-15:00 | 29.00 | 21.56 | 0.359261E+09 | 549.48 | 01-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.548335E+11 | 0.479752E+10 | ||||||||
Minimum of Months | 0.240945E+10 | 3106.81 | 23.80 | 18.64 | 0.333781E+09 | 549.47 | 23.27 | 18.64 | ||
Maximum of Months | 0.710490E+10 | 8523.29 | 33.12 | 24.56 | 0.455213E+09 | 549.50 | 33.12 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224560E+10 | 3944.80 | 19-JAN-10:30 | 23.85 | 21.17 | 0.241638E+09 | 347.87 | 18-JAN-10:09 | 23.85 | 21.17 |
February | 0.215249E+10 | 3909.89 | 27-FEB-10:30 | 21.90 | 19.28 | 0.224018E+09 | 347.87 | 09-FEB-10:00 | 21.90 | 19.28 |
March | 0.276391E+10 | 4298.65 | 26-MAR-10:27 | 26.35 | 20.17 | 0.271229E+09 | 347.87 | 23-MAR-09:09 | 26.35 | 20.17 |
April | 0.335348E+10 | 7939.93 | 23-APR-11:13 | 26.80 | 20.29 | 0.251819E+09 | 347.88 | 10-APR-13:00 | 26.80 | 20.29 |
May | 0.505029E+10 | 11049.05 | 07-MAY-10:22 | 30.55 | 23.68 | 0.277032E+09 | 347.86 | 09-MAY-09:30 | 28.60 | 23.11 |
June | 0.538244E+10 | 8529.85 | 11-JUN-11:32 | 30.00 | 21.13 | 0.276169E+09 | 347.86 | 01-JUN-13:09 | 30.00 | 21.13 |
July | 0.555579E+10 | 10200.38 | 23-JUL-10:02 | 31.02 | 26.38 | 0.257069E+09 | 347.86 | 24-JUL-09:30 | 30.55 | 26.01 |
August | 0.587233E+10 | 10644.17 | 06-AUG-09:23 | 29.50 | 26.85 | 0.288378E+09 | 347.86 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.490774E+10 | 11108.24 | 03-SEP-10:52 | 31.10 | 24.96 | 0.256081E+09 | 347.86 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.475044E+10 | 11129.76 | 09-OCT-09:42 | 28.68 | 22.57 | 0.265236E+09 | 347.88 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.308290E+10 | 5095.99 | 06-NOV-09:40 | 23.27 | 19.77 | 0.259279E+09 | 347.87 | 10-NOV-10:09 | 22.75 | 18.16 |
December | 0.238672E+10 | 3474.25 | 16-DEC-10:10 | 24.33 | 21.30 | 0.236445E+09 | 347.88 | 08-DEC-10:00 | 24.33 | 21.30 |
Annual Sum or Average | 0.475041E+11 | 0.310439E+10 | ||||||||
Minimum of Months | 0.215249E+10 | 3474.25 | 21.90 | 19.28 | 0.224018E+09 | 347.86 | 21.90 | 15.50 | ||
Maximum of Months | 0.587233E+10 | 11129.76 | 31.10 | 26.85 | 0.288378E+09 | 347.88 | 30.55 | 26.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387053E+10 | 14176.27 | 01-JAN-15:12 | 25.00 | 18.55 | 0.384155E+09 | 549.51 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.379486E+10 | 12948.08 | 26-FEB-13:13 | 26.27 | 18.89 | 0.352312E+09 | 562.35 | 02-FEB-13:09 | 26.27 | 18.89 |
March | 0.375878E+10 | 10267.46 | 06-MAR-13:00 | 27.20 | 21.71 | 0.409965E+09 | 549.50 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.454721E+10 | 11268.96 | 28-APR-16:10 | 32.02 | 25.39 | 0.387044E+09 | 587.94 | 28-APR-12:09 | 32.02 | 25.39 |
May | 0.743331E+10 | 11490.10 | 19-MAY-12:00 | 32.20 | 23.63 | 0.438941E+09 | 605.09 | 19-MAY-12:09 | 32.30 | 23.64 |
June | 0.796519E+10 | 11641.60 | 28-JUN-12:00 | 32.80 | 25.51 | 0.438168E+09 | 612.58 | 28-JUN-12:09 | 32.80 | 25.64 |
July | 0.816067E+10 | 12279.24 | 21-JUL-16:10 | 35.45 | 25.77 | 0.408655E+09 | 642.95 | 20-JUL-12:09 | 35.45 | 25.77 |
August | 0.961144E+10 | 12741.68 | 30-AUG-16:10 | 36.07 | 23.60 | 0.459108E+09 | 637.25 | 10-AUG-12:09 | 36.07 | 23.60 |
September | 0.829964E+10 | 12960.71 | 03-SEP-13:32 | 31.83 | 24.36 | 0.405936E+09 | 626.10 | 01-SEP-12:09 | 31.83 | 24.36 |
October | 0.928322E+10 | 13936.16 | 09-OCT-11:42 | 30.83 | 23.19 | 0.423679E+09 | 647.95 | 06-OCT-12:09 | 30.83 | 23.19 |
November | 0.644115E+10 | 13513.00 | 05-NOV-13:52 | 27.20 | 20.73 | 0.409680E+09 | 611.08 | 02-NOV-12:09 | 27.20 | 20.73 |
December | 0.498367E+10 | 13574.79 | 17-DEC-14:02 | 18.83 | 12.37 | 0.375039E+09 | 583.81 | 15-DEC-13:09 | 18.83 | 12.37 |
Annual Sum or Average | 0.781497E+11 | 0.489268E+10 | ||||||||
Minimum of Months | 0.375878E+10 | 10267.46 | 18.83 | 12.37 | 0.352312E+09 | 549.50 | 14.17 | 9.63 | ||
Maximum of Months | 0.961144E+10 | 14176.27 | 36.07 | 25.77 | 0.459108E+09 | 647.95 | 36.07 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235402E+10 | 7692.74 | 01-JAN-15:52 | 25.00 | 18.55 | 0.234170E+09 | 347.84 | 02-JAN-10:09 | 20.67 | 17.79 |
February | 0.228389E+10 | 8969.10 | 26-FEB-17:12 | 24.03 | 19.67 | 0.216984E+09 | 347.84 | 28-FEB-10:39 | 21.63 | 19.43 |
March | 0.267829E+10 | 5083.59 | 06-MAR-16:30 | 25.55 | 21.32 | 0.260223E+09 | 347.84 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.330703E+10 | 7969.93 | 23-APR-17:12 | 26.63 | 21.58 | 0.246768E+09 | 347.85 | 18-APR-13:00 | 26.63 | 21.58 |
May | 0.459515E+10 | 11317.66 | 29-MAY-16:12 | 32.07 | 23.52 | 0.276392E+09 | 347.84 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.500081E+10 | 11319.37 | 25-JUN-16:11 | 32.60 | 24.55 | 0.275912E+09 | 347.84 | 01-JUN-13:09 | 32.60 | 24.55 |
July | 0.504557E+10 | 11337.95 | 16-JUL-16:42 | 29.78 | 24.79 | 0.256769E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.569388E+10 | 9592.34 | 06-AUG-17:23 | 25.50 | 23.74 | 0.288274E+09 | 347.84 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.484430E+10 | 11976.42 | 03-SEP-16:52 | 31.10 | 24.95 | 0.255866E+09 | 347.84 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.474349E+10 | 11524.61 | 08-OCT-16:22 | 30.00 | 24.93 | 0.264929E+09 | 347.85 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.315443E+10 | 8141.22 | 05-NOV-15:53 | 27.20 | 19.54 | 0.253737E+09 | 347.84 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.264969E+10 | 5496.94 | 15-DEC-16:30 | 28.00 | 21.24 | 0.232336E+09 | 347.84 | 01-DEC-14:00 | 28.00 | 21.24 |
Annual Sum or Average | 0.463506E+11 | 0.306236E+10 | ||||||||
Minimum of Months | 0.228389E+10 | 5083.59 | 24.03 | 18.55 | 0.216984E+09 | 347.84 | 20.67 | 15.14 | ||
Maximum of Months | 0.569388E+10 | 11976.42 | 32.60 | 24.95 | 0.288274E+09 | 347.85 | 32.60 | 25.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237832E+10 | 4097.31 | 02-JAN-13:30 | 26.00 | 18.64 | 0.356880E+09 | 549.48 | 17-JAN-14:09 | 25.00 | 20.14 |
February | 0.247389E+10 | 3794.65 | 28-FEB-15:00 | 25.00 | 20.38 | 0.339124E+09 | 549.48 | 28-FEB-10:09 | 25.00 | 20.38 |
March | 0.318774E+10 | 4874.66 | 30-MAR-13:10 | 29.12 | 22.70 | 0.414266E+09 | 549.48 | 27-MAR-09:09 | 29.12 | 22.70 |
April | 0.395571E+10 | 5547.95 | 28-APR-15:00 | 33.30 | 23.06 | 0.394299E+09 | 549.49 | 10-APR-13:00 | 33.30 | 23.06 |
May | 0.630720E+10 | 8637.60 | 08-MAY-04:02 | 24.32 | 22.06 | 0.437573E+09 | 549.47 | 30-MAY-09:30 | 28.35 | 24.32 |
June | 0.678658E+10 | 8360.05 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436282E+09 | 549.47 | 01-JUN-13:09 | 25.22 | 22.37 |
July | 0.666026E+10 | 9680.31 | 23-JUL-15:23 | 31.95 | 25.52 | 0.405793E+09 | 549.47 | 14-JUL-13:00 | 31.95 | 25.52 |
August | 0.670414E+10 | 8381.99 | 14-AUG-04:02 | 26.10 | 24.05 | 0.455056E+09 | 549.48 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.550256E+10 | 8239.65 | 11-SEP-04:02 | 24.83 | 23.63 | 0.403500E+09 | 549.48 | 07-SEP-13:00 | 24.83 | 23.63 |
October | 0.511901E+10 | 8640.80 | 08-OCT-14:32 | 31.67 | 25.93 | 0.416098E+09 | 549.50 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.332182E+10 | 4748.46 | 03-NOV-14:00 | 29.40 | 23.47 | 0.394343E+09 | 549.48 | 28-NOV-10:00 | 26.60 | 21.19 |
December | 0.267397E+10 | 4219.51 | 15-DEC-15:00 | 29.00 | 21.56 | 0.355170E+09 | 549.48 | 01-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.550712E+11 | 0.480838E+10 | ||||||||
Minimum of Months | 0.237832E+10 | 3794.65 | 24.32 | 18.64 | 0.339124E+09 | 549.47 | 22.17 | 15.50 | ||
Maximum of Months | 0.678658E+10 | 9680.31 | 33.30 | 25.93 | 0.455056E+09 | 549.50 | 33.30 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215344E+10 | 4551.19 | 19-JAN-10:00 | 23.00 | 20.89 | 0.172164E+09 | 338.71 | 18-JAN-11:20 | 23.00 | 20.89 |
February | 0.228105E+10 | 4626.86 | 27-FEB-10:00 | 21.10 | 19.21 | 0.162519E+09 | 338.73 | 09-FEB-11:09 | 21.10 | 19.21 |
March | 0.303209E+10 | 5214.56 | 06-MAR-10:00 | 24.40 | 20.99 | 0.197621E+09 | 338.72 | 24-MAR-14:20 | 25.70 | 16.54 |
April | 0.380674E+10 | 12179.85 | 23-APR-09:42 | 25.82 | 20.99 | 0.185215E+09 | 338.73 | 10-APR-14:09 | 25.82 | 20.99 |
May | 0.540126E+10 | 12214.21 | 07-MAY-10:12 | 30.37 | 23.67 | 0.204791E+09 | 338.73 | 15-MAY-07:10 | 25.28 | 22.97 |
June | 0.562243E+10 | 10616.90 | 25-JUN-10:23 | 29.15 | 24.33 | 0.203895E+09 | 338.74 | 26-JUN-07:10 | 25.68 | 23.94 |
July | 0.554002E+10 | 12160.10 | 16-JUL-10:32 | 30.77 | 25.98 | 0.190302E+09 | 338.73 | 10-JUL-07:10 | 30.77 | 25.98 |
August | 0.548325E+10 | 11666.41 | 06-AUG-09:23 | 29.50 | 26.85 | 0.212480E+09 | 338.73 | 28-AUG-07:10 | 25.50 | 23.74 |
September | 0.453590E+10 | 12572.75 | 03-SEP-09:42 | 29.98 | 24.61 | 0.188661E+09 | 338.73 | 11-SEP-07:10 | 25.68 | 24.28 |
October | 0.440176E+10 | 12191.00 | 09-OCT-09:42 | 28.68 | 22.57 | 0.194589E+09 | 338.73 | 17-OCT-12:20 | 21.33 | 14.79 |
November | 0.293775E+10 | 5484.81 | 06-NOV-09:30 | 23.00 | 19.64 | 0.187189E+09 | 338.74 | 06-NOV-08:39 | 23.00 | 19.64 |
December | 0.227525E+10 | 3863.20 | 16-DEC-09:50 | 23.67 | 21.09 | 0.168495E+09 | 338.73 | 08-DEC-11:09 | 23.67 | 21.09 |
Annual Sum or Average | 0.474710E+11 | 0.226792E+10 | ||||||||
Minimum of Months | 0.215344E+10 | 3863.20 | 21.10 | 19.21 | 0.162519E+09 | 338.71 | 21.10 | 14.79 | ||
Maximum of Months | 0.562243E+10 | 12572.75 | 30.77 | 26.85 | 0.212480E+09 | 338.74 | 30.77 | 25.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483635E+10 | 13655.65 | 01-JAN-13:32 | 25.67 | 18.12 | 0.400708E+09 | 560.39 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.465573E+10 | 13466.87 | 26-FEB-13:13 | 26.27 | 18.89 | 0.365859E+09 | 552.42 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.462953E+10 | 8087.28 | 29-MAR-13:40 | 25.00 | 21.26 | 0.431159E+09 | 549.50 | 24-MAR-13:00 | 25.00 | 21.26 |
April | 0.491099E+10 | 7611.58 | 28-APR-14:00 | 32.70 | 23.02 | 0.396367E+09 | 549.51 | 10-APR-13:00 | 32.70 | 23.02 |
May | 0.645009E+10 | 10303.75 | 22-MAY-04:02 | 26.10 | 22.31 | 0.437551E+09 | 549.48 | 03-MAY-13:00 | 26.10 | 22.31 |
June | 0.657055E+10 | 9920.81 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436129E+09 | 549.47 | 01-JUN-13:09 | 25.22 | 22.37 |
July | 0.662417E+10 | 10499.57 | 23-JUL-15:23 | 31.95 | 25.52 | 0.405716E+09 | 549.47 | 14-JUL-13:00 | 31.95 | 25.52 |
August | 0.740620E+10 | 10640.14 | 27-AUG-15:13 | 32.67 | 23.88 | 0.455207E+09 | 549.48 | 25-AUG-13:09 | 32.67 | 23.88 |
September | 0.681154E+10 | 13252.63 | 24-SEP-13:13 | 31.27 | 25.21 | 0.404164E+09 | 549.48 | 20-SEP-13:00 | 31.27 | 25.21 |
October | 0.797061E+10 | 14347.32 | 09-OCT-11:42 | 30.83 | 23.19 | 0.419248E+09 | 566.51 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.643290E+10 | 13892.97 | 05-NOV-13:52 | 27.20 | 20.73 | 0.410814E+09 | 581.99 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.549587E+10 | 13469.92 | 17-DEC-11:32 | 19.33 | 13.30 | 0.386465E+09 | 566.03 | 15-DEC-14:39 | 19.33 | 13.30 |
Annual Sum or Average | 0.727945E+11 | 0.494939E+10 | ||||||||
Minimum of Months | 0.462953E+10 | 7611.58 | 19.33 | 13.30 | 0.365859E+09 | 549.47 | 19.33 | 13.30 | ||
Maximum of Months | 0.797061E+10 | 14347.32 | 32.70 | 25.52 | 0.455207E+09 | 581.99 | 32.70 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228937E+10 | 5321.01 | 19-JAN-16:00 | 25.00 | 20.82 | 0.229143E+09 | 347.84 | 02-JAN-14:00 | 25.00 | 20.82 |
February | 0.245320E+10 | 11125.06 | 26-FEB-17:12 | 24.03 | 19.67 | 0.214820E+09 | 347.84 | 09-FEB-14:00 | 24.03 | 19.67 |
March | 0.302659E+10 | 6313.77 | 06-MAR-16:30 | 25.55 | 21.32 | 0.258888E+09 | 347.84 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.383787E+10 | 12371.15 | 23-APR-17:42 | 25.78 | 21.36 | 0.246264E+09 | 347.85 | 10-APR-13:00 | 25.78 | 21.36 |
May | 0.504400E+10 | 12472.74 | 29-MAY-16:12 | 32.07 | 23.52 | 0.276320E+09 | 347.84 | 30-MAY-09:39 | 28.53 | 24.38 |
June | 0.533843E+10 | 12394.18 | 11-JUN-16:52 | 33.30 | 21.96 | 0.275693E+09 | 347.84 | 01-JUN-13:09 | 33.30 | 21.96 |
July | 0.513138E+10 | 12486.34 | 16-JUL-16:32 | 30.17 | 24.94 | 0.256429E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.540883E+10 | 10241.51 | 06-AUG-17:23 | 25.50 | 23.74 | 0.287510E+09 | 347.84 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.454616E+10 | 12400.10 | 03-SEP-16:21 | 31.65 | 24.79 | 0.254614E+09 | 347.84 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.448512E+10 | 12736.03 | 08-OCT-15:52 | 31.00 | 25.22 | 0.261868E+09 | 347.85 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.313831E+10 | 9354.78 | 05-NOV-15:53 | 27.20 | 19.54 | 0.246532E+09 | 347.84 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.257438E+10 | 5898.51 | 15-DEC-15:40 | 28.33 | 21.35 | 0.225100E+09 | 347.84 | 01-DEC-14:00 | 28.33 | 21.35 |
Annual Sum or Average | 0.472736E+11 | 0.303318E+10 | ||||||||
Minimum of Months | 0.228937E+10 | 5321.01 | 24.03 | 19.54 | 0.214820E+09 | 347.84 | 22.17 | 15.14 | ||
Maximum of Months | 0.540883E+10 | 12736.03 | 33.30 | 25.22 | 0.287510E+09 | 347.85 | 33.30 | 24.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.857823E+09 | 8610.60 | 10-JAN-07:03 | 3.17 |
February | 0.456439E+09 | 9024.23 | 06-FEB-07:04 | 3.90 |
March | 0.503824E+09 | 5936.02 | 13-MAR-06:02 | 5.92 |
April | 0.121621E+09 | 3516.50 | 11-APR-05:03 | 10.63 |
May | 14644272.44 | 4623.20 | 30-MAY-04:02 | 25.60 |
June | 15205493.75 | 3891.67 | 26-JUN-04:02 | 25.00 |
July | 14151943.36 | 4229.50 | 10-JUL-04:02 | 25.40 |
August | 14396066.91 | 3766.41 | 14-AUG-04:02 | 26.10 |
September | 12150737.17 | 4679.87 | 11-SEP-04:02 | 24.83 |
October | 63028837.94 | 3030.28 | 23-OCT-04:02 | 24.92 |
November | 0.217558E+09 | 3754.47 | 15-NOV-06:02 | 7.70 |
December | 0.637612E+09 | 8563.18 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.292845E+10 | |||
Minimum of Months | 12150737.17 | 3030.28 | 0.50 | |
Maximum of Months | 0.857823E+09 | 9024.23 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239668E+09 | 3289.89 | 16-JAN-14:32 | 26.67 |
February | 0.150689E+09 | 3166.43 | 19-FEB-12:23 | 21.90 |
March | 77683465.20 | 1964.23 | 05-MAR-10:23 | 24.15 |
April | 9184639.60 | 2063.78 | 02-APR-15:05 | 18.72 |
May | 10391275.15 | 2474.14 | 22-MAY-04:02 | 26.10 |
June | 7543198.80 | 1912.66 | 05-JUN-04:02 | 25.22 |
July | 9972618.27 | 2174.62 | 19-JUL-04:02 | 27.20 |
August | 8482464.19 | 2202.89 | 14-AUG-04:02 | 26.10 |
September | 12292051.85 | 1963.15 | 03-SEP-15:41 | 32.28 |
October | 14280948.93 | 2639.40 | 29-OCT-12:07 | 22.17 |
November | 34907974.84 | 3097.42 | 26-NOV-13:32 | 20.90 |
December | 0.134927E+09 | 3641.14 | 31-DEC-14:03 | 22.17 |
Annual Sum or Average | 0.710022E+09 | |||
Minimum of Months | 7543198.80 | 1912.66 | 18.72 | |
Maximum of Months | 0.239668E+09 | 3641.14 | 32.28 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78241421.49 | 5311.48 | 05-JAN-06:01 | 0.17 |
February | 53742250.84 | 2913.92 | 19-FEB-12:50 | 22.10 |
March | 37946460.61 | 5200.11 | 09-MAR-06:02 | 1.10 |
April | 8956961.82 | 1861.48 | 16-APR-14:50 | 22.02 |
May | 16317207.28 | 3555.72 | 01-MAY-04:02 | 26.10 |
June | 16232878.93 | 3287.18 | 02-JUN-04:03 | 24.40 |
July | 19645846.73 | 3515.75 | 19-JUL-04:02 | 27.20 |
August | 20082429.93 | 3988.68 | 23-AUG-04:02 | 26.38 |
September | 22663544.16 | 4040.31 | 07-SEP-04:02 | 25.60 |
October | 23832445.47 | 4102.93 | 23-OCT-04:02 | 24.92 |
November | 24526574.71 | 2683.67 | 26-NOV-10:43 | 16.23 |
December | 52738654.68 | 3243.05 | 31-DEC-12:03 | 23.00 |
Annual Sum or Average | 0.374927E+09 | |||
Minimum of Months | 8956961.82 | 1861.48 | 0.17 | |
Maximum of Months | 78241421.49 | 5311.48 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 1583615.27 | 15002.81 | 06-FEB-07:01 | 3.90 |
March | 1148205.31 | 17223.08 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 2731820.58 | |||
Minimum of Months | 0.00 | 0.00 | 3.90 | |
Maximum of Months | 1583615.27 | 17223.08 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57986268.54 | 17816.31 | 04-JAN-07:01 | 1.17 |
February | 54174931.98 | 18660.10 | 06-FEB-07:12 | 4.00 |
March | 16559923.91 | 18181.33 | 10-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 386662.62 | 2577.75 | 16-NOV-07:03 | 9.77 |
December | 31786205.75 | 18059.20 | 20-DEC-07:03 | 1.83 |
Annual Sum or Average | 0.160894E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 57986268.54 | 18660.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371295E+09 | 9317.62 | 10-JAN-06:11 | 3.00 |
February | 0.178200E+09 | 9728.82 | 06-FEB-06:11 | 3.07 |
March | 0.135685E+09 | 8849.96 | 13-MAR-05:12 | 6.57 |
April | 1581300.64 | 7929.38 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 820690.39 | 5099.78 | 28-OCT-06:03 | 10.00 |
November | 16738669.84 | 8066.40 | 15-NOV-07:02 | 7.80 |
December | 0.220370E+09 | 9074.20 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.924690E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.371295E+09 | 9728.82 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164191E+09 | 5431.27 | 05-JAN-06:13 | 0.33 |
February | 72134903.04 | 5779.78 | 06-FEB-06:11 | 3.07 |
March | 77022765.23 | 5131.09 | 21-MAR-06:03 | 10.00 |
April | 1348915.58 | 4789.07 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 956530.22 | 4922.58 | 28-OCT-06:03 | 10.00 |
November | 7022997.06 | 5149.67 | 16-NOV-07:03 | 9.77 |
December | 0.119754E+09 | 5361.16 | 21-DEC-06:13 | 0.67 |
Annual Sum or Average | 0.442432E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.33 | |
Maximum of Months | 0.164191E+09 | 5779.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187248E+09 | 8600.69 | 10-JAN-06:11 | 3.00 |
February | 95670233.10 | 8971.38 | 06-FEB-06:11 | 3.07 |
March | 0.104630E+09 | 8045.66 | 13-MAR-05:12 | 6.57 |
April | 1122748.99 | 6852.16 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 536988.88 | 3579.93 | 28-OCT-06:03 | 10.00 |
November | 7016655.99 | 7697.03 | 16-NOV-07:03 | 9.77 |
December | 0.122131E+09 | 8541.46 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.518356E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.187248E+09 | 8971.38 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209932E+09 | 5416.29 | 28-JAN-06:13 | 9.33 |
February | 0.101188E+09 | 5503.45 | 06-FEB-06:11 | 3.07 |
March | 82444673.43 | 5115.71 | 03-MAR-07:03 | 10.78 |
April | 1236044.16 | 4821.34 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 911283.92 | 4863.73 | 28-OCT-06:03 | 10.00 |
November | 11745433.81 | 5123.05 | 24-NOV-07:03 | 13.08 |
December | 0.127574E+09 | 5379.37 | 21-DEC-06:13 | 0.67 |
Annual Sum or Average | 0.535031E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 0.209932E+09 | 5503.45 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27903627.89 | 5661.09 | 10-JAN-06:11 | 3.00 |
February | 22204340.22 | 5435.10 | 13-FEB-07:02 | 4.08 |
March | 17105463.23 | 5316.85 | 22-MAR-06:02 | 7.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 10408544.99 | 5274.90 | 22-DEC-07:03 | 10.33 |
Annual Sum or Average | 77621976.34 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 27903627.89 | 5661.09 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9175712.05 | 3420.39 | 25-JAN-07:02 | 9.00 |
February | 6497728.73 | 3581.73 | 06-FEB-07:04 | 3.90 |
March | 7263304.82 | 3429.08 | 22-MAR-06:02 | 7.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 6063077.91 | 3488.20 | 26-DEC-07:01 | 5.32 |
Annual Sum or Average | 28999823.52 | |||
Minimum of Months | 0.00 | 0.00 | 3.90 | |
Maximum of Months | 9175712.05 | 3581.73 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530423E+09 | 6800.34 | 05-JAN-07:10 | 0.83 |
February | 0.316559E+09 | 6812.40 | 17-FEB-07:10 | 1.28 |
March | 0.478183E+09 | 6712.50 | 09-MAR-07:10 | 1.18 |
April | 96849325.77 | 5293.99 | 17-APR-06:40 | 13.83 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 9163940.44 | 3273.38 | 27-OCT-06:07 | 14.83 |
November | 0.129546E+09 | 5364.48 | 13-NOV-07:55 | 11.60 |
December | 0.457857E+09 | 7068.40 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.201858E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 0.530423E+09 | 7068.40 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10178323.25 | 3536.06 | 21-JAN-07:03 | 1.17 |
February | 7682225.46 | 3544.68 | 06-FEB-07:04 | 3.90 |
March | 7217461.36 | 3214.45 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 5073383.40 | 3405.21 | 23-DEC-07:03 | 7.17 |
Annual Sum or Average | 30151393.47 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 10178323.25 | 3544.68 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66466102.24 | 6686.37 | 10-JAN-06:11 | 3.00 |
February | 36311190.98 | 6894.78 | 06-FEB-06:11 | 3.07 |
March | 23624065.77 | 6384.16 | 13-MAR-05:12 | 6.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 834235.77 | 4521.08 | 16-NOV-07:03 | 9.77 |
December | 39856965.81 | 6574.91 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.167093E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 66466102.24 | 6894.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32053376.58 | 4304.04 | 07-JAN-06:11 | 4.33 |
February | 16540073.26 | 4258.40 | 06-FEB-06:14 | 3.07 |
March | 15392281.34 | 4378.88 | 13-MAR-05:12 | 6.57 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 772145.90 | 3084.71 | 16-NOV-07:03 | 9.77 |
December | 27326715.19 | 4193.18 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 92084592.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 32053376.58 | 4378.88 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30711652.63 | 6125.98 | 28-JAN-07:03 | 8.50 |
February | 16960333.67 | 6207.95 | 14-FEB-07:03 | 9.50 |
March | 14901429.66 | 5965.89 | 10-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 43891.15 | 292.61 | 16-NOV-07:03 | 9.77 |
December | 21159811.53 | 6218.17 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 83777118.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 30711652.63 | 6218.17 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40206612.73 | 4116.87 | 23-JAN-07:03 | 6.17 |
February | 20773673.71 | 4128.44 | 08-FEB-07:03 | 11.70 |
March | 14588326.29 | 3930.03 | 13-MAR-06:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 1092191.12 | 4113.64 | 16-NOV-07:03 | 9.77 |
December | 23893479.11 | 4117.84 | 19-DEC-07:03 | 10.00 |
Annual Sum or Average | 0.100554E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 40206612.73 | 4128.44 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.798760E+09 | 1184.79 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.689684E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.791900E+09 | 1184.79 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.679778E+09 | 1184.79 | 06-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707929E+09 | 947.97 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.693365E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655754E+09 | 774.31 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747008E+09 | 947.97 | 08-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.689590E+09 | 1184.79 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.738301E+09 | 1358.45 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.783813E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.790923E+09 | 1358.45 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.876680E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655754E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.798760E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488564E+09 | 750.07 | 03-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427107E+09 | 750.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491176E+09 | 750.07 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.428085E+09 | 750.07 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452093E+09 | 600.14 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.445212E+09 | 450.21 | 02-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418625E+09 | 450.21 | 11-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.473549E+09 | 490.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433794E+09 | 750.07 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.460976E+09 | 860.01 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.482808E+09 | 860.01 | 20-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.485984E+09 | 860.01 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548797E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418625E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.491176E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.736070E+09 | 1184.79 | 13-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655661E+09 | 1184.79 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.773503E+09 | 1184.79 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.681277E+09 | 1184.79 | 06-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.718819E+09 | 947.97 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.707279E+09 | 774.31 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.664718E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751528E+09 | 947.97 | 07-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.684549E+09 | 1184.79 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.721982E+09 | 1358.45 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.731009E+09 | 1184.79 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.728645E+09 | 1358.45 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855504E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655661E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.773503E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.483209E+09 | 750.02 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.426123E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.499148E+09 | 750.02 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.434221E+09 | 750.02 | 06-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.454926E+09 | 600.10 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.446826E+09 | 600.10 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421592E+09 | 600.10 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479189E+09 | 750.02 | 08-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.441131E+09 | 750.02 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465045E+09 | 859.95 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.475574E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475336E+09 | 859.95 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550232E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421592E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.499148E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.792385E+09 | 1184.79 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.686190E+09 | 1184.79 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.788437E+09 | 1184.79 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.678000E+09 | 1184.79 | 06-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.706626E+09 | 947.97 | 23-MAY-07:19 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.692391E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.654546E+09 | 774.31 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745274E+09 | 947.97 | 08-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687580E+09 | 1184.79 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.736157E+09 | 1358.45 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.778974E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.784670E+09 | 1358.45 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.873123E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.654546E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.792385E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.486531E+09 | 750.07 | 03-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425658E+09 | 750.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489817E+09 | 750.07 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.427278E+09 | 750.07 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451250E+09 | 600.14 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.444305E+09 | 450.21 | 02-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418112E+09 | 450.21 | 11-JUL-15:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472857E+09 | 490.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.432636E+09 | 750.07 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.460168E+09 | 860.01 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.480856E+09 | 860.01 | 20-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.484254E+09 | 860.01 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547372E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418112E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.489817E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.735475E+09 | 1184.79 | 13-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655375E+09 | 1184.79 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.771063E+09 | 1184.79 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.679877E+09 | 1184.79 | 06-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.717078E+09 | 947.97 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.705658E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663282E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.750433E+09 | 947.97 | 07-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683113E+09 | 1184.79 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.720985E+09 | 1358.45 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.729914E+09 | 1184.79 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.727267E+09 | 1358.45 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853952E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655375E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.771063E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481246E+09 | 750.02 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424683E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.497376E+09 | 750.02 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.432982E+09 | 750.02 | 06-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453642E+09 | 600.10 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.445778E+09 | 600.10 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420521E+09 | 600.10 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478017E+09 | 750.02 | 08-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.439882E+09 | 750.02 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463680E+09 | 859.95 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.473887E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.473544E+09 | 859.95 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548524E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420521E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.497376E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.798760E+09 | 1184.79 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.689684E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.791900E+09 | 1184.79 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.679778E+09 | 1184.79 | 06-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.707929E+09 | 947.97 | 23-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.693365E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655754E+09 | 774.31 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.747008E+09 | 947.97 | 08-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.689590E+09 | 1184.79 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.738301E+09 | 1358.45 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.783813E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.790923E+09 | 1358.45 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.876680E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655754E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.798760E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488564E+09 | 750.07 | 03-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427107E+09 | 750.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491176E+09 | 750.07 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.428085E+09 | 750.07 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452093E+09 | 600.14 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.445212E+09 | 450.21 | 02-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418625E+09 | 450.21 | 11-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.473549E+09 | 490.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433794E+09 | 750.07 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.460963E+09 | 860.01 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.482808E+09 | 860.01 | 20-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.485984E+09 | 860.01 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.548796E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418625E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.491176E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.736070E+09 | 1184.79 | 13-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655661E+09 | 1184.79 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.773503E+09 | 1184.79 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.681277E+09 | 1184.79 | 06-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.718819E+09 | 947.97 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.707279E+09 | 774.31 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.664718E+09 | 947.97 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751528E+09 | 947.97 | 07-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.684549E+09 | 1184.79 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.721982E+09 | 1358.45 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.731009E+09 | 1184.79 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.728645E+09 | 1358.45 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.855504E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655661E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.773503E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.483209E+09 | 750.02 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.426123E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.499148E+09 | 750.02 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.434197E+09 | 750.02 | 06-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.454926E+09 | 600.10 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.446826E+09 | 600.10 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421592E+09 | 600.10 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479181E+09 | 750.02 | 08-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.441131E+09 | 750.02 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465045E+09 | 859.95 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.475574E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.475336E+09 | 859.95 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.550229E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421592E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.499148E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.798760E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1431423.25 | 0.169431E+09 |
February | 0.901968E+09 | 0.689684E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1706842.35 | 0.130174E+09 |
March | 0.107774E+10 | 0.791900E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4789061.59 | 0.141467E+09 |
April | 0.956342E+09 | 0.679778E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7365844.70 | 64515683.57 |
May | 0.103597E+10 | 0.707929E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30054912.88 | 11786030.50 |
June | 0.103308E+10 | 0.693365E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26972689.31 | 9058695.02 |
July | 0.959235E+09 | 0.655754E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37108925.47 | 4092392.28 |
August | 0.107774E+10 | 0.747008E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36596487.10 | 11650731.92 |
September | 0.956342E+09 | 0.689590E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33813478.40 | 17808863.80 |
October | 0.994195E+09 | 0.738301E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28971528.46 | 55672637.88 |
November | 0.984487E+09 | 0.783813E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4219366.34 | 87673696.89 |
December | 0.959235E+09 | 0.790923E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2801722.23 | 0.151914E+09 |
Annual Sum or Average | 0.119305E+11 | 0.876680E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215832E+09 | 0.855245E+09 |
Minimum of Months | 0.901968E+09 | 0.655754E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1431423.25 | 4092392.28 |
Maximum of Months | 0.107774E+10 | 0.798760E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37108925.47 | 0.169431E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.488564E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 628284.94 | 0.117465E+09 |
February | 0.571020E+09 | 0.427107E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 903430.01 | 91057452.16 |
March | 0.682301E+09 | 0.491176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2408371.78 | 98725439.34 |
April | 0.605444E+09 | 0.428085E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4667949.58 | 45712666.90 |
May | 0.655854E+09 | 0.452093E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19335863.49 | 8210938.41 |
June | 0.654023E+09 | 0.445212E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17900821.36 | 6083897.24 |
July | 0.607275E+09 | 0.418625E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24372372.07 | 2930279.86 |
August | 0.682301E+09 | 0.473549E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24065074.29 | 7802439.51 |
September | 0.605444E+09 | 0.433794E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21728493.13 | 12017914.55 |
October | 0.629407E+09 | 0.460976E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18013173.57 | 38757931.83 |
November | 0.623262E+09 | 0.482808E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2192445.55 | 61875607.90 |
December | 0.607275E+09 | 0.485984E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432091.22 | 0.104253E+09 |
Annual Sum or Average | 0.755301E+10 | 0.548797E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137648E+09 | 0.594893E+09 |
Minimum of Months | 0.571020E+09 | 0.418625E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 628284.94 | 2930279.86 |
Maximum of Months | 0.682301E+09 | 0.491176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24372372.07 | 0.117465E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.736070E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362330.37 | 0.196319E+09 |
February | 0.901968E+09 | 0.655661E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 845353.24 | 0.149709E+09 |
March | 0.107774E+10 | 0.773503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2831786.63 | 0.151604E+09 |
April | 0.956342E+09 | 0.681277E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6690465.09 | 68750097.74 |
May | 0.103597E+10 | 0.718819E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30249761.38 | 11702915.88 |
June | 0.103308E+10 | 0.707279E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27591279.75 | 8686716.86 |
July | 0.959235E+09 | 0.664718E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37666776.38 | 4021644.19 |
August | 0.107774E+10 | 0.751528E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36109223.72 | 11873260.34 |
September | 0.956342E+09 | 0.684549E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31561871.60 | 19285065.45 |
October | 0.994195E+09 | 0.721982E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23595576.64 | 65381639.93 |
November | 0.984487E+09 | 0.731009E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2333847.62 | 0.102767E+09 |
December | 0.959235E+09 | 0.728645E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1490551.11 | 0.174708E+09 |
Annual Sum or Average | 0.119305E+11 | 0.855504E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201329E+09 | 0.964809E+09 |
Minimum of Months | 0.901968E+09 | 0.655661E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362330.37 | 4021644.19 |
Maximum of Months | 0.107774E+10 | 0.773503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37666776.38 | 0.196319E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.483209E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 754899.90 | 0.118338E+09 |
February | 0.570983E+09 | 0.426123E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006232.38 | 91026923.80 |
March | 0.682256E+09 | 0.499148E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3088749.98 | 97284620.46 |
April | 0.605404E+09 | 0.434221E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4503151.14 | 46533187.32 |
May | 0.655811E+09 | 0.454926E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20704368.57 | 8397310.19 |
June | 0.653980E+09 | 0.446826E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18010242.62 | 6591300.95 |
July | 0.607235E+09 | 0.421592E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25107830.65 | 3181389.69 |
August | 0.682256E+09 | 0.479189E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24755868.99 | 8673962.80 |
September | 0.605404E+09 | 0.441131E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22340397.02 | 12773444.05 |
October | 0.629366E+09 | 0.465045E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18849541.93 | 40080180.24 |
November | 0.623221E+09 | 0.475574E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2795800.35 | 60567003.78 |
December | 0.607235E+09 | 0.475336E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1671019.84 | 0.105427E+09 |
Annual Sum or Average | 0.755252E+10 | 0.550232E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143588E+09 | 0.598875E+09 |
Minimum of Months | 0.570983E+09 | 0.421592E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 754899.90 | 3181389.69 |
Maximum of Months | 0.682256E+09 | 0.499148E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25107830.65 | 0.118338E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.792385E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736616.20 | 0.100747E+09 |
February | 0.901968E+09 | 0.686190E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 975959.87 | 76720460.49 |
March | 0.107774E+10 | 0.788437E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2836827.65 | 79260417.27 |
April | 0.956342E+09 | 0.678000E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4367113.84 | 34646797.63 |
May | 0.103597E+10 | 0.706626E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17490903.59 | 4669783.01 |
June | 0.103308E+10 | 0.692391E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15476746.20 | 4233696.36 |
July | 0.959235E+09 | 0.654546E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21600059.54 | 1785723.07 |
August | 0.107774E+10 | 0.745274E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20112393.74 | 6839301.81 |
September | 0.956342E+09 | 0.687580E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18975765.05 | 10596054.40 |
October | 0.994195E+09 | 0.736157E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15830417.52 | 33717583.91 |
November | 0.984487E+09 | 0.778974E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2082433.60 | 53971875.29 |
December | 0.959235E+09 | 0.784670E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1413659.44 | 91921130.13 |
Annual Sum or Average | 0.119305E+11 | 0.873123E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121899E+09 | 0.499110E+09 |
Minimum of Months | 0.901968E+09 | 0.654546E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736616.20 | 1785723.07 |
Maximum of Months | 0.107774E+10 | 0.792385E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21600059.54 | 0.100747E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.486531E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283624.88 | 71471418.30 |
February | 0.571020E+09 | 0.425658E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495731.18 | 54589686.34 |
March | 0.682301E+09 | 0.489817E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1316074.06 | 56705270.85 |
April | 0.605444E+09 | 0.427278E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2563949.29 | 25474361.49 |
May | 0.655854E+09 | 0.451250E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10620313.12 | 3862880.65 |
June | 0.654023E+09 | 0.444305E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9863737.41 | 3189149.12 |
July | 0.607275E+09 | 0.418112E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13338377.83 | 1574728.97 |
August | 0.682301E+09 | 0.472857E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12823854.56 | 5078999.64 |
September | 0.605444E+09 | 0.432636E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11571775.05 | 7845838.71 |
October | 0.629407E+09 | 0.460168E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9452119.66 | 24289918.47 |
November | 0.623262E+09 | 0.480856E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1075799.57 | 38734045.93 |
December | 0.607275E+09 | 0.484254E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 726853.47 | 64098505.22 |
Annual Sum or Average | 0.755301E+10 | 0.547372E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74132210.08 | 0.356915E+09 |
Minimum of Months | 0.571020E+09 | 0.418112E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283624.88 | 1574728.97 |
Maximum of Months | 0.682301E+09 | 0.489817E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13338377.83 | 71471418.30 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.735475E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35368937.88 | 0.325228E+10 |
February | 0.901968E+09 | 0.655375E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60040431.24 | 0.202861E+10 |
March | 0.107774E+10 | 0.771063E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158942E+09 | 0.212990E+10 |
April | 0.956342E+09 | 0.679877E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532022E+09 | 0.676783E+09 |
May | 0.103597E+10 | 0.717078E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174002E+10 | 18032530.25 |
June | 0.103308E+10 | 0.705658E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206774E+10 | 18104953.30 |
July | 0.959235E+09 | 0.663282E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181201E+10 | 10262155.31 |
August | 0.107774E+10 | 0.750433E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195635E+10 | 30452568.11 |
September | 0.956342E+09 | 0.683113E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100818E+10 | 87947369.41 |
October | 0.994195E+09 | 0.720985E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102874E+10 | 0.467243E+09 |
November | 0.984487E+09 | 0.729914E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281053E+09 | 0.145030E+10 |
December | 0.959235E+09 | 0.727267E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129115E+09 | 0.260482E+10 |
Annual Sum or Average | 0.119305E+11 | 0.853952E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108096E+11 | 0.127747E+11 |
Minimum of Months | 0.901968E+09 | 0.655375E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35368937.88 | 10262155.31 |
Maximum of Months | 0.107774E+10 | 0.771063E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206774E+10 | 0.325228E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481246E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 298296.15 | 71698644.53 |
February | 0.570983E+09 | 0.424683E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 480481.80 | 54470969.30 |
March | 0.682256E+09 | 0.497376E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1478531.67 | 56218274.66 |
April | 0.605404E+09 | 0.432982E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2378071.69 | 26076580.34 |
May | 0.655811E+09 | 0.453642E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11212519.60 | 3827929.37 |
June | 0.653980E+09 | 0.445778E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9743071.62 | 3526698.83 |
July | 0.607235E+09 | 0.420521E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13502187.55 | 1648641.63 |
August | 0.682256E+09 | 0.478017E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12998889.58 | 5507404.60 |
September | 0.605404E+09 | 0.439882E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11631259.04 | 8287673.32 |
October | 0.629366E+09 | 0.463680E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9538934.26 | 25326831.42 |
November | 0.623221E+09 | 0.473887E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189603.41 | 38294524.91 |
December | 0.607235E+09 | 0.473544E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 776018.36 | 64938293.82 |
Annual Sum or Average | 0.755252E+10 | 0.548524E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75227864.73 | 0.359822E+09 |
Minimum of Months | 0.570983E+09 | 0.420521E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 298296.15 | 1648641.63 |
Maximum of Months | 0.682256E+09 | 0.497376E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13502187.55 | 71698644.53 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.798760E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1117268.00 | 0.153861E+09 |
February | 0.901968E+09 | 0.689684E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383866.35 | 0.118743E+09 |
March | 0.107774E+10 | 0.791900E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4004669.54 | 0.126774E+09 |
April | 0.956342E+09 | 0.679778E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6228448.24 | 57215671.83 |
May | 0.103597E+10 | 0.707929E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25554028.53 | 10070035.11 |
June | 0.103308E+10 | 0.693365E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23131128.39 | 7727634.20 |
July | 0.959235E+09 | 0.655754E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32156298.69 | 3305829.86 |
August | 0.107774E+10 | 0.747008E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31006139.04 | 10072390.29 |
September | 0.956342E+09 | 0.689590E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28767751.15 | 15891188.87 |
October | 0.994195E+09 | 0.738301E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24480160.85 | 50498379.40 |
November | 0.984487E+09 | 0.783813E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3350249.87 | 80752710.14 |
December | 0.959235E+09 | 0.790923E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2267382.22 | 0.138380E+09 |
Annual Sum or Average | 0.119305E+11 | 0.876680E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183447E+09 | 0.773292E+09 |
Minimum of Months | 0.901968E+09 | 0.655754E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1117268.00 | 3305829.86 |
Maximum of Months | 0.107774E+10 | 0.798760E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32156298.69 | 0.153861E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.488564E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509475.53 | 0.106106E+09 |
February | 0.421807E+09 | 0.427107E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 767958.84 | 82402003.60 |
March | 0.502994E+09 | 0.491176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2073909.17 | 87489116.15 |
April | 0.447140E+09 | 0.428085E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3975869.34 | 40048197.44 |
May | 0.484071E+09 | 0.452093E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16334027.17 | 6996655.28 |
June | 0.482240E+09 | 0.445212E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15300611.10 | 5190297.01 |
July | 0.448971E+09 | 0.418625E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21029653.61 | 2365714.18 |
August | 0.502994E+09 | 0.473549E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20337259.41 | 6738990.84 |
September | 0.447140E+09 | 0.433794E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18340507.57 | 10686218.39 |
October | 0.465148E+09 | 0.460963E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15273480.96 | 34850686.00 |
November | 0.460569E+09 | 0.482808E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1832365.61 | 56181024.99 |
December | 0.448971E+09 | 0.485984E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236719.74 | 94275632.59 |
Annual Sum or Average | 0.557719E+10 | 0.548796E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117012E+09 | 0.533330E+09 |
Minimum of Months | 0.421807E+09 | 0.418625E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509475.53 | 2365714.18 |
Maximum of Months | 0.502994E+09 | 0.491176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21029653.61 | 0.106106E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.736070E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 300760.02 | 0.175937E+09 |
February | 0.901968E+09 | 0.655661E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 715107.56 | 0.134776E+09 |
March | 0.107774E+10 | 0.773503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2315971.60 | 0.134963E+09 |
April | 0.956342E+09 | 0.681277E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5642791.44 | 60680421.56 |
May | 0.103597E+10 | 0.718819E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25517874.58 | 10041424.49 |
June | 0.103308E+10 | 0.707279E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23575477.00 | 7455290.69 |
July | 0.959235E+09 | 0.664718E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32429421.96 | 3273430.02 |
August | 0.107774E+10 | 0.751528E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30330494.31 | 10309138.27 |
September | 0.956342E+09 | 0.684549E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26368004.05 | 17208012.81 |
October | 0.994195E+09 | 0.721982E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19765980.78 | 58473071.69 |
November | 0.984487E+09 | 0.731009E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1936634.41 | 92448480.02 |
December | 0.959235E+09 | 0.728645E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253650.02 | 0.156940E+09 |
Annual Sum or Average | 0.119305E+11 | 0.855504E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170152E+09 | 0.862506E+09 |
Minimum of Months | 0.901968E+09 | 0.655661E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 300760.02 | 3273430.02 |
Maximum of Months | 0.107774E+10 | 0.773503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32429421.96 | 0.175937E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.483209E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544978.32 | 0.106851E+09 |
February | 0.570983E+09 | 0.426123E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769682.33 | 82579935.24 |
March | 0.682256E+09 | 0.499148E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2453461.16 | 86983220.91 |
April | 0.605404E+09 | 0.434197E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3649376.06 | 41269015.26 |
May | 0.655811E+09 | 0.454926E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17100568.11 | 7245935.21 |
June | 0.653980E+09 | 0.446826E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15066981.30 | 5668613.65 |
July | 0.607235E+09 | 0.421592E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21144983.16 | 2615892.96 |
August | 0.682256E+09 | 0.479181E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20608666.89 | 7541110.86 |
September | 0.605404E+09 | 0.441131E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18407389.26 | 11513189.28 |
October | 0.629366E+09 | 0.465045E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15424514.62 | 36272951.61 |
November | 0.623221E+09 | 0.475574E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110781.87 | 55447736.85 |
December | 0.607235E+09 | 0.475336E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311190.18 | 95430321.94 |
Annual Sum or Average | 0.755252E+10 | 0.550229E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118593E+09 | 0.539419E+09 |
Minimum of Months | 0.570983E+09 | 0.421592E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544978.32 | 2615892.96 |
Maximum of Months | 0.682256E+09 | 0.499148E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21144983.16 | 0.106851E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396918.99 | 0.234185E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815005.81 | 0.180156E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3089881.26 | 0.186600E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5955799.87 | 83472425.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28195843.25 | 11452449.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26035426.81 | 9468385.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38380058.63 | 3507959.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35156050.38 | 13053263.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31651401.40 | 21792194.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23603500.82 | 75580095.03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2270847.03 | 0.124032E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1544738.53 | 0.210547E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197095E+09 | 0.115385E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396918.99 | 3507959.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38380058.63 | 0.234185E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922830.66 | 0.277788E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1587299.42 | 0.215027E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5015757.15 | 0.226316E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8041544.06 | 0.101917E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37095435.97 | 13975111.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33876748.02 | 11747693.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50220127.14 | 4176611.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46377301.94 | 15412748.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41837481.15 | 25690229.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32016811.74 | 89562133.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3565292.68 | 0.148047E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2558965.06 | 0.249571E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263116E+09 | 0.137923E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 922830.66 | 4176611.10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50220127.14 | 0.277788E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224694.72 | 0.270327E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420671.01 | 0.209728E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2368688.53 | 0.224605E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4933557.78 | 0.104458E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32812456.69 | 12382289.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30971405.43 | 10064562.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45747898.19 | 3717717.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44176262.07 | 13554000.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39445441.70 | 22275060.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26263516.16 | 83920760.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2282446.77 | 0.139107E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1457269.49 | 0.240128E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231104E+09 | 0.133427E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224694.72 | 3717717.13 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45747898.19 | 0.270327E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | 16-JAN-15:00 | 329.23 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.30 | 20-FEB-14:53 | 446.62 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 05-MAR-12:30 | 419.81 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.71 | 29-APR-17:02 | 250.68 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.56 | 07-MAY-14:00 | 47.57 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.54 | 10-JUN-17:02 | 74.93 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.00 | 22-JUL-18:50 | 47.75 | 31-JUL-02:70 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 08-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.79 | 20-AUG-13:52 | 104.98 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 | 09-SEP-17:02 | 115.15 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.35 | 09-OCT-14:00 | 187.64 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.36 | 05-NOV-13:00 | 294.87 | 12-NOV-07:05 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.90 | 10-DEC-11:20 | 412.86 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 | 47.57 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 223.35 | 446.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 03-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 16-JAN-15:00 | 217.56 | 21-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.54 | 20-FEB-14:53 | 327.51 | 05-FEB-10:00 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.07 | 05-MAR-13:00 | 280.90 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.07 | 29-APR-17:50 | 170.43 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 600.14 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 21-MAY-13:30 | 40.50 | 14-MAY-12:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 02-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.70 | 10-JUN-17:02 | 48.51 | 06-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 11-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.32 | 22-JUL-18:50 | 52.26 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.02 | 20-AUG-14:10 | 69.98 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.34 | 09-SEP-17:02 | 77.25 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.11 | 09-OCT-14:00 | 126.25 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 20-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.02 | 05-NOV-13:00 | 232.85 | 12-NOV-08:50 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.75 | 10-DEC-15:20 | 274.64 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 40.50 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 156.11 | 327.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 13-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 19-JAN-12:10 | 377.46 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 02-FEB-13:00 | 467.60 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.30 | 26-MAR-13:48 | 432.49 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.09 | 29-APR-17:02 | 267.64 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.33 | 21-MAY-13:30 | 48.09 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.59 | 10-JUN-17:02 | 74.55 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.16 | 22-JUL-18:50 | 48.54 | 31-JUL-02:70 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 07-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.01 | 20-AUG-13:52 | 105.87 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.90 | 09-SEP-17:02 | 118.18 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.51 | 09-OCT-13:56 | 202.98 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 | 07-NOV-13:00 | 358.29 | 12-NOV-10:53 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 13-DEC-14:00 | 420.41 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 48.09 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 197.51 | 467.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 16-JAN-12:40 | 231.91 | 22-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 26-FEB-12:03 | 297.37 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 | 05-MAR-12:50 | 285.30 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 06-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 | 23-APR-13:20 | 185.71 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.91 | 21-MAY-13:30 | 42.48 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.67 | 10-JUN-17:08 | 52.30 | 06-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.06 | 02-JUL-12:00 | 35.08 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 08-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.96 | 20-AUG-13:52 | 72.80 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.71 | 09-SEP-17:07 | 77.15 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.68 | 09-OCT-12:00 | 130.66 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 | 11-NOV-12:10 | 198.29 | 12-NOV-07:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.23 | 10-DEC-11:20 | 275.59 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 35.08 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 160.68 | 297.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 16-JAN-14:50 | 200.47 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.39 | 20-FEB-15:10 | 282.08 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.10 | 05-MAR-13:00 | 237.11 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.76 | 29-APR-17:30 | 136.08 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 23-MAY-07:19 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.37 | 07-MAY-14:00 | 27.16 | 14-MAY-11:53 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.97 | 10-JUN-17:02 | 40.53 | 06-JUN-22:10 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.84 | 22-JUL-18:50 | 23.25 | 31-JUL-02:30 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 08-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 | 20-AUG-14:00 | 61.27 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 09-SEP-17:02 | 61.75 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 | 09-OCT-13:50 | 119.69 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.47 | 11-NOV-13:00 | 173.35 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.13 | 10-DEC-15:00 | 255.23 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.53 | 23.25 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 | 282.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 03-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 16-JAN-14:50 | 135.13 | 22-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.02 | 20-FEB-15:10 | 200.14 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 05-MAR-13:00 | 162.59 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 | 29-APR-17:50 | 94.26 | 01-APR-21:00 |
May | 827.22 | 01-MAY-09:09 | 600.14 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 21-MAY-14:10 | 30.62 | 14-MAY-11:53 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 02-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 10-JUN-17:02 | 28.56 | 18-JUN-14:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 11-JUL-15:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.04 | 22-JUL-18:50 | 23.04 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | 20-AUG-14:00 | 42.48 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 | 09-SEP-17:02 | 45.07 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 09-OCT-13:50 | 82.21 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 20-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 05-NOV-13:00 | 134.33 | 12-NOV-08:20 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 10-DEC-14:50 | 172.44 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 | 23.04 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 200.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 13-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.25 | 02-JAN-13:00 | 25060.73 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4639.63 | 02-FEB-13:00 | 24411.90 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5317.54 | 30-MAR-12:00 | 24801.03 | 09-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9255.39 | 28-APR-16:03 | 14396.70 | 11-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10048.08 | 25-MAY-16:03 | 1724.05 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10649.59 | 28-JUN-16:03 | 2030.82 | 07-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13107.80 | 21-JUL-16:02 | 1407.91 | 13-JUL-11:10 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 07-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13587.15 | 30-AUG-16:02 | 2581.09 | 29-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9429.88 | 06-SEP-16:03 | 3917.19 | 07-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9132.48 | 06-OCT-11:02 | 9504.35 | 27-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5498.12 | 02-NOV-11:03 | 16927.24 | 15-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4789.31 | 13-DEC-13:00 | 25543.88 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.25 | 1407.91 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13587.15 | 25543.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 16-JAN-13:50 | 134.69 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 | 26-FEB-14:00 | 188.79 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 05-MAR-13:00 | 163.51 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 06-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 29-APR-17:10 | 97.49 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 | 21-MAY-14:10 | 18.31 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 10-JUN-17:10 | 30.54 | 06-JUN-21:20 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 16-JUL-12:50 | 19.03 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 08-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.49 | 20-AUG-14:00 | 43.70 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.10 | 09-SEP-17:08 | 44.67 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.99 | 09-OCT-11:50 | 84.38 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 | 11-NOV-12:20 | 119.02 | 12-NOV-08:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 10-DEC-11:30 | 172.77 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 18.31 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.99 | 188.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 16-JAN-15:00 | 299.28 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 20-FEB-15:00 | 418.35 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 | 05-MAR-12:50 | 370.29 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 | 29-APR-17:02 | 215.00 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 23-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.66 | 07-MAY-14:00 | 42.19 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.91 | 10-JUN-17:02 | 65.20 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.62 | 22-JUL-18:50 | 39.11 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 08-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.69 | 20-AUG-14:00 | 91.45 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.60 | 09-SEP-23:00 | 97.60 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.84 | 09-OCT-13:50 | 174.19 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.03 | 11-NOV-13:00 | 262.29 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 | 10-DEC-15:00 | 378.56 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 39.11 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 189.84 | 418.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 03-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 16-JAN-15:00 | 197.51 | 21-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 20-FEB-15:00 | 305.51 | 05-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 750.07 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 | 05-MAR-13:00 | 246.58 | 20-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 750.07 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 | 29-APR-17:50 | 144.78 | 01-APR-21:00 |
May | 805.43 | 01-MAY-07:10 | 600.14 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.27 | 21-MAY-13:50 | 30.73 | 14-MAY-12:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 02-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.55 | 10-JUN-17:02 | 42.25 | 06-JUN-22:10 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 11-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 | 22-JUL-18:50 | 39.43 | 30-JUL-11:10 |
August | 805.43 | 01-AUG-07:10 | 490.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 | 20-AUG-14:00 | 60.88 | 25-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.08 | 09-SEP-23:00 | 65.39 | 05-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.90 | 09-OCT-13:50 | 116.86 | 29-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 20-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 05-NOV-13:00 | 206.84 | 12-NOV-08:50 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 10-DEC-14:50 | 251.08 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 30.73 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 125.90 | 305.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 13-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 19-JAN-12:10 | 321.01 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 02-FEB-13:00 | 436.63 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 26-MAR-14:00 | 379.71 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 06-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.26 | 29-APR-17:02 | 225.72 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.03 | 21-MAY-13:50 | 42.64 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.26 | 10-JUN-17:02 | 65.00 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.04 | 22-JUL-18:50 | 39.86 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 07-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.55 | 20-AUG-13:56 | 92.23 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.90 | 09-SEP-23:00 | 100.28 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.41 | 09-OCT-13:44 | 186.20 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 07-NOV-13:00 | 292.45 | 12-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 13-DEC-14:00 | 385.84 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 39.86 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 163.41 | 436.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 16-JAN-12:40 | 199.81 | 22-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 26-FEB-12:03 | 278.51 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.28 | 05-MAR-12:50 | 250.93 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 06-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.03 | 29-APR-17:08 | 157.07 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 21-MAY-13:50 | 33.45 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 10-JUN-17:08 | 45.49 | 06-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 | 16-JUL-13:00 | 29.17 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 08-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.03 | 20-AUG-14:00 | 63.33 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.56 | 09-SEP-23:00 | 65.55 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.52 | 09-OCT-11:50 | 120.33 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 11-NOV-12:20 | 176.10 | 12-NOV-07:05 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 10-DEC-11:00 | 251.94 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 29.17 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 126.52 | 278.51 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 16-JAN-14:53 | 440.22 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 02-FEB-13:00 | 629.89 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 05-MAR-13:00 | 542.77 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.72 | 29-APR-17:02 | 310.92 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.40 | 07-MAY-14:00 | 57.52 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.09 | 10-JUN-17:02 | 87.06 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.92 | 22-JUL-18:53 | 44.79 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.76 | 20-AUG-14:00 | 126.25 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.83 | 09-SEP-17:02 | 121.92 | 05-SEP-03:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.40 | 09-OCT-14:00 | 263.89 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 05-NOV-13:00 | 378.45 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 10-DEC-15:00 | 579.85 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 44.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.40 | 629.89 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.57 | 16-JAN-15:00 | 546.77 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 | 20-FEB-14:53 | 762.47 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 | 05-MAR-13:00 | 678.31 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.54 | 29-APR-17:02 | 382.36 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.98 | 21-MAY-13:53 | 63.51 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.60 | 10-JUN-17:02 | 109.80 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 | 22-JUL-18:53 | 57.07 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.90 | 20-AUG-14:00 | 158.44 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.21 | 09-SEP-17:02 | 156.19 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.22 | 09-OCT-14:00 | 313.77 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 | 05-NOV-13:00 | 473.29 | 12-NOV-07:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 10-DEC-15:00 | 695.31 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 57.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.22 | 762.47 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 | 16-JAN-15:00 | 497.62 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 | 02-FEB-13:00 | 669.23 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.68 | 26-MAR-14:00 | 658.78 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.71 | 29-APR-17:02 | 415.63 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.08 | 07-MAY-14:00 | 123.76 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.40 | 10-JUN-17:02 | 108.41 | 18-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.36 | 02-JUL-10:55 | 99.72 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.73 | 20-AUG-13:52 | 150.68 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 09-SEP-22:53 | 160.51 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.73 | 08-OCT-13:51 | 281.22 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.62 | 07-NOV-22:03 | 447.73 | 12-NOV-11:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 10-DEC-10:55 | 651.96 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 | 99.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.06 | 669.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 39334.81 | 02-JAN-06:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30623.55 | 28-FEB-06:13 | 1905.79 | 2147.94 | 22231.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38067.81 | 09-MAR-06:02 | 3176.32 | 1058.67 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35785.96 | 28-APR-05:13 | 1905.79 | 2147.94 | 22231.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43448.78 | 31-MAY-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41936.50 | 20-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42578.53 | 12-JUL-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41264.36 | 01-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40946.57 | 01-SEP-04:23 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40769.41 | 24-OCT-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36220.91 | 06-NOV-07:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38193.41 | 18-DEC-06:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 30623.55 | 0.00 | 846.94 | 22231.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43448.78 | 5082.11 | 8592.08 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5719.75 | 19-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
February | 6588.98 | 24-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
March | 6559.88 | 29-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 0.00 |
April | 9210.89 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.09 | 0.00 |
May | 9911.32 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 0.00 |
June | 9948.30 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | 0.00 |
July | 10324.02 | 18-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 0.00 |
August | 10050.88 | 03-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 0.00 |
September | 9356.06 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
October | 9565.36 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 0.00 |
November | 7814.93 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 0.00 |
December | 6885.60 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5719.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10324.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 | 8.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3254.60 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.72 |
February | 2754.33 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.57 |
March | 3487.72 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.86 |
April | 3518.83 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 0.00 |
May | 4185.08 | 30-MAY-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.44 | 0.00 |
June | 4196.70 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
July | 4530.63 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.78 | 0.00 |
August | 4477.45 | 28-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 | 0.00 |
September | 4509.76 | 11-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 0.00 |
October | 4912.76 | 10-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 0.00 |
November | 3473.40 | 06-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 0.00 |
December | 3489.70 | 18-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2754.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4912.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 130.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3784.50 | 03-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.63 |
February | 3273.95 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.46 |
March | 3835.77 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.03 |
April | 3845.99 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 0.00 |
May | 4510.99 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 0.00 |
June | 4523.85 | 19-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 |
July | 4978.11 | 05-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 |
August | 5052.00 | 28-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.35 | 0.00 |
September | 4925.48 | 11-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
October | 5296.06 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 0.00 |
November | 4400.23 | 06-NOV-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
December | 3644.61 | 18-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3273.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5296.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 | 105.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22478.85 | 02-JAN-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15148.00 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15065.47 | 30-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16614.02 | 28-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34547.18 | 31-MAY-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32554.39 | 13-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32453.65 | 18-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32404.06 | 30-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32315.43 | 06-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31621.78 | 06-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17090.83 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15881.27 | 15-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15065.47 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34547.18 | 6035.01 | 6443.98 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15956.29 | 02-JAN-14:40 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15688.88 | 27-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16338.63 | 29-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19181.15 | 28-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33931.54 | 08-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34280.26 | 12-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34493.80 | 11-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34465.57 | 25-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34204.03 | 18-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34019.64 | 06-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17996.44 | 02-NOV-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16746.29 | 15-DEC-16:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15688.88 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34493.80 | 6198.29 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3929.53 | 02-JAN-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 0.00 |
February | 4003.85 | 28-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
March | 5163.16 | 30-MAR-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
April | 6243.11 | 28-APR-15:10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 | 0.00 |
May | 10275.03 | 29-MAY-18:12 | 0.00 | 197.54 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 0.00 |
June | 10151.75 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
July | 11683.65 | 23-JUL-15:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 0.00 |
August | 10208.54 | 27-AUG-15:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 | 0.00 |
September | 11561.99 | 10-SEP-15:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | 0.00 |
October | 9628.47 | 08-OCT-16:42 | 334.80 | 197.54 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 90.14 | 0.00 |
November | 5123.45 | 02-NOV-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
December | 4529.88 | 15-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3929.53 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11683.65 | 1306.65 | 711.15 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 | 9.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4321.74 | 19-JAN-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
February | 4507.99 | 27-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
March | 5192.57 | 26-MAR-11:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 0.00 |
April | 11683.27 | 23-APR-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
May | 12685.27 | 07-MAY-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.35 | 0.00 |
June | 11438.16 | 25-JUN-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
July | 12126.09 | 23-JUL-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 0.00 |
August | 12096.66 | 06-AUG-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 0.00 |
September | 12182.06 | 10-SEP-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 | 0.00 |
October | 12587.72 | 09-OCT-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
November | 5498.82 | 11-NOV-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
December | 3541.22 | 16-DEC-10:10 | 261.23 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3541.22 | 169.56 | 91.16 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12685.27 | 827.22 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 | 14.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16729.85 | 01-JAN-14:01 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 |
February | 14974.08 | 26-FEB-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 |
March | 14437.52 | 26-MAR-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
April | 8363.94 | 28-APR-14:20 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 0.00 |
May | 12272.70 | 22-MAY-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 0.00 |
June | 10753.72 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 |
July | 14023.26 | 23-JUL-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 78.48 | 0.00 |
August | 14088.73 | 27-AUG-15:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 | 0.00 |
September | 14953.16 | 24-SEP-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 66.62 | 0.00 |
October | 15229.58 | 09-OCT-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 132.27 | 0.00 |
November | 16072.88 | 11-NOV-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 |
December | 16315.84 | 10-DEC-14:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8363.94 | 0.00 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16729.85 | 1272.23 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 132.27 | 36.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9972.76 | 01-JAN-15:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
February | 11803.28 | 26-FEB-17:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 |
March | 9335.92 | 26-MAR-15:43 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
April | 11955.99 | 16-APR-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.40 |
May | 13583.93 | 29-MAY-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 | 0.00 |
June | 13596.58 | 11-JUN-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | 0.00 |
July | 13594.86 | 16-JUL-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 0.00 |
August | 12051.76 | 27-AUG-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 86.92 | 0.00 |
September | 13549.25 | 03-SEP-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 | 0.00 |
October | 13746.11 | 01-OCT-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
November | 8626.95 | 11-NOV-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
December | 10446.68 | 10-DEC-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8626.95 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13746.11 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 86.92 | 86.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3608.45 | 02-JAN-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
February | 3106.81 | 28-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 |
March | 3989.02 | 30-MAR-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
April | 4644.89 | 28-APR-15:10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
May | 8060.38 | 31-MAY-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
June | 7344.16 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
July | 8060.81 | 24-JUL-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
August | 8523.29 | 23-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
September | 7212.90 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
October | 7921.52 | 23-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
November | 4764.86 | 03-NOV-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
December | 4144.98 | 15-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3106.81 | 0.00 | 223.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8523.29 | 1306.65 | 711.15 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 6.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3944.80 | 19-JAN-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
February | 3909.89 | 27-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
March | 4298.65 | 26-MAR-10:27 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
April | 7939.93 | 23-APR-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 | 0.00 |
May | 11049.05 | 07-MAY-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 | 0.00 |
June | 8529.85 | 11-JUN-11:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 | 0.00 |
July | 10200.38 | 23-JUL-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 |
August | 10644.17 | 06-AUG-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 | 0.00 |
September | 11108.24 | 03-SEP-10:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 0.00 |
October | 11129.76 | 09-OCT-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 0.00 |
November | 5095.99 | 06-NOV-09:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
December | 3474.25 | 16-DEC-10:10 | 261.23 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3474.25 | 127.17 | 68.37 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11129.76 | 827.22 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 | 2.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14176.27 | 01-JAN-15:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
February | 12948.08 | 26-FEB-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
March | 10267.46 | 06-MAR-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3922.34 | 0.00 |
April | 11268.96 | 28-APR-16:10 | 1205.27 | 1079.96 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8429.25 | 0.00 |
May | 11490.10 | 19-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8345.23 | 0.00 |
June | 11641.60 | 28-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8926.44 | 0.00 |
July | 12279.24 | 21-JUL-16:10 | 2008.79 | 1799.94 | 3986.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11175.11 | 0.00 |
August | 12741.68 | 30-AUG-16:10 | 2410.55 | 2159.93 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11193.85 | 0.00 |
September | 12960.71 | 03-SEP-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 | 0.00 |
October | 13936.16 | 09-OCT-11:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 0.00 |
November | 13513.00 | 05-NOV-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
December | 13574.79 | 17-DEC-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10267.46 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14176.27 | 2410.55 | 2159.93 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11193.85 | 121.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7692.74 | 01-JAN-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
February | 8969.10 | 26-FEB-17:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
March | 5083.59 | 06-MAR-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
April | 7969.93 | 23-APR-17:12 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 11317.66 | 29-MAY-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
June | 11319.37 | 25-JUN-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 0.00 |
July | 11337.95 | 16-JUL-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
August | 9592.34 | 06-AUG-17:23 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 |
September | 11976.42 | 03-SEP-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 | 0.00 |
October | 11524.61 | 08-OCT-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 0.00 |
November | 8141.22 | 05-NOV-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
December | 5496.94 | 15-DEC-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5083.59 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11976.42 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 9.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4097.31 | 02-JAN-13:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
February | 3794.65 | 28-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
March | 4874.66 | 30-MAR-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 0.00 |
April | 5547.95 | 28-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 | 0.00 |
May | 8637.60 | 08-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
June | 8360.05 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 |
July | 9680.31 | 23-JUL-15:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 71.42 | 0.00 |
August | 8381.99 | 14-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
September | 8239.65 | 11-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 |
October | 8640.80 | 08-OCT-14:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 116.96 | 0.00 |
November | 4748.46 | 03-NOV-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 0.00 |
December | 4219.51 | 15-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3794.65 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9680.31 | 1306.65 | 711.15 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 116.96 | 12.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4551.19 | 19-JAN-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
February | 4626.86 | 27-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
March | 5214.56 | 06-MAR-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
April | 12179.85 | 23-APR-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
May | 12214.21 | 07-MAY-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 0.00 |
June | 10616.90 | 25-JUN-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 | 0.00 |
July | 12160.10 | 16-JUL-10:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | 0.00 |
August | 11666.41 | 06-AUG-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 |
September | 12572.75 | 03-SEP-09:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 0.00 |
October | 12191.00 | 09-OCT-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 | 0.00 |
November | 5484.81 | 06-NOV-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
December | 3863.20 | 16-DEC-09:50 | 254.35 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3863.20 | 169.56 | 91.16 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12572.75 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 12.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13655.65 | 01-JAN-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 |
February | 13466.87 | 26-FEB-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 |
March | 8087.28 | 29-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 0.00 |
April | 7611.58 | 28-APR-14:00 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
May | 10303.75 | 22-MAY-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 0.00 |
June | 9920.81 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
July | 10499.57 | 23-JUL-15:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 71.29 | 0.00 |
August | 10640.14 | 27-AUG-15:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 0.00 |
September | 13252.63 | 24-SEP-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 57.40 | 0.00 |
October | 14347.32 | 09-OCT-11:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 77.39 | 0.00 |
November | 13892.97 | 05-NOV-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
December | 13469.92 | 17-DEC-11:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7611.58 | 0.00 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14347.32 | 1306.65 | 647.98 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 | 190.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5321.01 | 19-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 0.00 |
February | 11125.06 | 26-FEB-17:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
March | 6313.77 | 06-MAR-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 0.00 |
April | 12371.15 | 23-APR-17:42 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 |
May | 12472.74 | 29-MAY-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 | 0.00 |
June | 12394.18 | 11-JUN-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.11 | 0.00 |
July | 12486.34 | 16-JUL-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 0.00 |
August | 10241.51 | 06-AUG-17:23 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
September | 12400.10 | 03-SEP-16:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 0.00 |
October | 12736.03 | 08-OCT-15:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 | 0.00 |
November | 9354.78 | 05-NOV-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
December | 5898.51 | 15-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5321.01 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12736.03 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 55.42 | 16.96 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.121007E+12 | 124120.90 | 10-JAN-07:10 | 0.00 | 0.00 |
February | 0.113225E+12 | 142019.62 | 06-FEB-07:10 | 0.00 | 0.00 |
March | 0.130912E+12 | 121037.18 | 29-MAR-15:20 | 0.00 | 0.00 |
April | 0.132313E+12 | 147022.08 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.167167E+12 | 145014.45 | 18-MAY-15:39 | 0.00 | 0.00 |
June | 0.170568E+12 | 152366.10 | 28-JUN-15:09 | 0.00 | 0.00 |
July | 0.170557E+12 | 159174.00 | 21-JUL-15:00 | 0.00 | 0.00 |
August | 0.180362E+12 | 160184.79 | 30-AUG-15:00 | 0.00 | 0.00 |
September | 0.158869E+12 | 151150.73 | 06-SEP-15:00 | 0.00 | 0.00 |
October | 0.157295E+12 | 155556.17 | 05-OCT-14:00 | 0.00 | 0.00 |
November | 0.129518E+12 | 140664.42 | 02-NOV-15:09 | 0.00 | 0.00 |
December | 0.124057E+12 | 131396.82 | 21-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.175585E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.113225E+12 | 121037.18 | 0.00 | 0.00 | |
Maximum of Months | 0.180362E+12 | 160184.79 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.255026E+11 | 0.517597E+10 | 0.605851E+11 | 0.225889E+10 | 0.445193E+10 | 12379742.02 | 0.601140E+10 | 0.130385E+11 | 0.00 | 0.00 | 0.00 | 0.397001E+10 | 0.00 |
February | 0.229133E+11 | 0.433555E+10 | 0.548702E+11 | 0.204965E+10 | 0.422930E+10 | 11196021.66 | 0.315692E+10 | 0.180794E+11 | 0.00 | 0.00 | 0.00 | 0.357965E+10 | 0.00 |
March | 0.271006E+11 | 0.438227E+10 | 0.627783E+11 | 0.235660E+10 | 0.499214E+10 | 12675672.10 | 0.341864E+10 | 0.217991E+11 | 0.00 | 0.00 | 0.00 | 0.407176E+10 | 0.00 |
April | 0.239855E+11 | 0.384887E+10 | 0.586172E+11 | 0.219342E+10 | 0.563610E+10 | 11960507.72 | 0.210671E+09 | 0.343374E+11 | 0.00 | 0.00 | 0.00 | 0.347163E+10 | 0.00 |
May | 0.257142E+11 | 0.360887E+10 | 0.616817E+11 | 0.230733E+10 | 0.887743E+10 | 12527707.06 | 0.00 | 0.614876E+11 | 0.00 | 0.00 | 0.00 | 0.347775E+10 | 0.00 |
June | 0.255178E+11 | 0.330914E+10 | 0.604966E+11 | 0.226952E+10 | 0.942720E+10 | 12231776.97 | 0.00 | 0.662811E+11 | 0.00 | 0.00 | 0.00 | 0.325441E+10 | 0.00 |
July | 0.238724E+11 | 0.354970E+10 | 0.597911E+11 | 0.223030E+10 | 0.939325E+10 | 12256437.81 | 0.00 | 0.687104E+11 | 0.00 | 0.00 | 0.00 | 0.299746E+10 | 0.00 |
August | 0.267913E+11 | 0.382930E+10 | 0.627783E+11 | 0.235638E+10 | 0.102536E+11 | 12675672.10 | 0.00 | 0.710169E+11 | 0.00 | 0.00 | 0.00 | 0.332355E+10 | 0.00 |
September | 0.240620E+11 | 0.405484E+10 | 0.585950E+11 | 0.219222E+10 | 0.837517E+10 | 11960507.72 | 0.00 | 0.584311E+11 | 0.00 | 0.00 | 0.00 | 0.314717E+10 | 0.00 |
October | 0.251476E+11 | 0.459822E+10 | 0.605962E+11 | 0.225940E+10 | 0.872720E+10 | 12379742.02 | 58008373.19 | 0.524323E+11 | 0.00 | 0.00 | 0.00 | 0.346407E+10 | 0.00 |
November | 0.252053E+11 | 0.487649E+10 | 0.591197E+11 | 0.220149E+10 | 0.566027E+10 | 12059151.09 | 0.506484E+09 | 0.283070E+11 | 0.00 | 0.00 | 0.00 | 0.362921E+10 | 0.00 |
December | 0.248263E+11 | 0.528855E+10 | 0.597800E+11 | 0.223018E+10 | 0.484968E+10 | 12256437.81 | 0.439062E+10 | 0.188990E+11 | 0.00 | 0.00 | 0.00 | 0.378037E+10 | 0.00 |
Annual Sum or Average | 0.300639E+12 | 0.508578E+11 | 0.719689E+12 | 0.269054E+11 | 0.848733E+11 | 0.146559E+09 | 0.177527E+11 | 0.512820E+12 | 0.00 | 0.00 | 0.00 | 0.421670E+11 | 0.00 |
Minimum of Months | 0.229133E+11 | 0.330914E+10 | 0.548702E+11 | 0.204965E+10 | 0.422930E+10 | 11196021.66 | 0.00 | 0.130385E+11 | 0.00 | 0.00 | 0.00 | 0.299746E+10 | 0.00 |
Maximum of Months | 0.271006E+11 | 0.528855E+10 | 0.627783E+11 | 0.235660E+10 | 0.102536E+11 | 12675672.10 | 0.601140E+10 | 0.710169E+11 | 0.00 | 0.00 | 0.00 | 0.407176E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30940.97 | 13-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 7866.07 | 19-JAN-15:30 | 6.85 | 03-JAN-12:09 | 78907.20 | 10-JAN-07:10 |
February | 31618.07 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:09 | 8439.05 | 27-FEB-15:30 | 6.85 | 03-FEB-12:09 | 96427.78 | 06-FEB-07:10 |
March | 30940.97 | 27-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 7379.37 | 29-MAR-15:20 | 6.85 | 08-MAR-12:09 | 70280.27 | 13-MAR-06:10 |
April | 30940.97 | 14-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 11-APR-07:10 | 11003.75 | 28-APR-15:20 | 6.85 | 01-APR-05:10 | 17663.15 | 11-APR-06:10 |
May | 28290.68 | 23-MAY-07:19 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-12:09 | 11977.57 | 04-MAY-15:00 | 6.85 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 26756.14 | 16-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 02-JUN-12:09 | 12541.15 | 12-JUN-15:00 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 27649.74 | 14-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 18-JUL-12:09 | 13350.87 | 05-JUL-14:39 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 28740.43 | 21-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-12:09 | 14592.01 | 30-AUG-15:00 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 30940.97 | 26-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:09 | 13299.28 | 11-SEP-14:09 | 6.85 | 10-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 25-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-12:09 | 14464.65 | 10-OCT-14:09 | 6.85 | 01-OCT-05:10 | 8607.10 | 28-OCT-06:10 |
November | 31791.75 | 21-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 15-NOV-13:09 | 11511.74 | 06-NOV-15:30 | 6.85 | 01-NOV-05:10 | 29368.31 | 16-NOV-07:10 |
December | 32642.50 | 12-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 05-DEC-08:09 | 9875.56 | 15-DEC-15:30 | 6.85 | 20-DEC-12:09 | 86152.95 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26756.14 | 5686.19 | 41699.26 | 1410.29 | 7379.37 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 14592.01 | 6.85 | 96427.78 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 40833.03 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 5355.50 | 23-JAN-12:30 | 0.00 |
February | 40680.34 | 24-FEB-13:00 | 0.00 | 0.00 | 0.00 | 5353.74 | 01-FEB-12:50 | 0.00 |
March | 43563.18 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 5127.22 | 01-MAR-12:00 | 0.00 |
April | 63976.74 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 4958.62 | 03-APR-11:00 | 0.00 |
May | 63763.88 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4594.10 | 01-MAY-11:30 | 0.00 |
June | 69689.96 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 4236.54 | 01-JUN-11:50 | 0.00 |
July | 74944.89 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 4198.75 | 03-JUL-11:00 | 0.00 |
August | 73922.75 | 03-AUG-15:50 | 0.00 | 0.00 | 0.00 | 4217.20 | 31-AUG-11:20 | 0.00 |
September | 66287.52 | 06-SEP-15:00 | 0.00 | 0.00 | 0.00 | 4257.37 | 29-SEP-11:00 | 0.00 |
October | 70488.13 | 06-OCT-10:00 | 0.00 | 0.00 | 0.00 | 4620.75 | 30-OCT-11:20 | 0.00 |
November | 57701.92 | 02-NOV-14:39 | 0.00 | 0.00 | 0.00 | 4989.71 | 30-NOV-12:30 | 0.00 |
December | 47796.14 | 15-DEC-15:09 | 0.00 | 0.00 | 0.00 | 5339.36 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 40680.34 | 0.00 | 0.00 | 0.00 | 4198.75 | 0.00 | ||
Maximum of Months | 74944.89 | 0.00 | 0.00 | 0.00 | 5355.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 124120.90 | 10-JAN-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3512.02 | 6.85 | 78907.20 | 0.00 | 0.00 |
February | 142019.62 | 06-FEB-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3895.21 | 6.85 | 96427.78 | 0.00 | 0.00 |
March | 121037.18 | 29-MAR-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 7379.37 | 6.85 | 0.00 | 41022.13 | 0.00 |
April | 147022.08 | 28-APR-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 10740.12 | 6.85 | 0.00 | 63976.74 | 0.00 |
May | 145014.45 | 18-MAY-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 11323.15 | 6.85 | 0.00 | 61407.54 | 0.00 |
June | 152366.10 | 28-JUN-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 11759.15 | 6.85 | 0.00 | 68654.34 | 0.00 |
July | 159174.00 | 21-JUL-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12273.06 | 6.85 | 0.00 | 74944.89 | 0.00 |
August | 160184.79 | 30-AUG-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14592.01 | 6.85 | 0.00 | 73625.64 | 0.00 |
September | 151150.73 | 06-SEP-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12891.64 | 6.85 | 0.00 | 66287.52 | 0.00 |
October | 155556.17 | 05-OCT-14:00 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14379.00 | 6.85 | 0.00 | 69860.32 | 0.00 |
November | 140664.42 | 02-NOV-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 11213.07 | 6.85 | 0.00 | 57143.05 | 0.00 |
December | 131396.82 | 21-DEC-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3548.46 | 6.85 | 86152.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 121037.18 | 10880.98 | 22496.85 | 0.00 | 975.80 | 3512.02 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 160184.79 | 25681.07 | 41670.51 | 5686.19 | 1410.29 | 14592.01 | 6.85 | 96427.78 | 74944.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.17 | 18.93 | 0.17 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 1.00 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.00 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.42 | 1.83 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.33 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.17 | 0.33 | 19.17 | 7.00 | 26.72 | 5.50 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.41 | 0.17 | 19.41 | 2.50 | 27.56 | 1.83 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.17 | 18.80 | 0.17 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.96 | 1.00 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.91 | 7.83 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.64 | 6.50 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.73 | 9.83 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.63 | 5.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.86 | 7.33 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.66 | 4.33 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.04 | 0.33 | 19.04 | 43.17 | 27.63 | 42.50 | 27.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.28 | 0.17 | 19.28 | 10.17 | 27.96 | 9.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.96 | 3.17 | 27.96 |
February | 0.17 | 19.29 | 0.17 | 19.29 | 1.50 | 26.23 | 1.50 | 26.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.49 | 1.17 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 2.67 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 1.00 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.42 | 2.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.50 | 4.00 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.85 | 7.17 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.04 | 8.33 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.79 | 5.50 | 27.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.92 | 4.17 | 27.92 |
Annual Sum or Average | 0.17 | 19.29 | 0.17 | 19.29 | 43.33 | 27.72 | 41.33 | 27.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.23 | 0.33 | 26.93 |
Maximum of Months | 0.17 | 19.29 | 0.17 | 19.29 | 9.00 | 28.04 | 8.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.29 | 0.17 | 19.29 | 0.33 | 23.36 | 0.33 | 24.71 |
February | 0.17 | 18.86 | 0.17 | 18.86 | 0.50 | 24.18 | 0.50 | 25.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.45 | 0.33 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 1.67 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.15 | 3.00 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.04 | 2.83 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.73 | 4.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.72 | 2.50 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.21 | 3.50 | 28.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.02 | 3.50 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
Annual Sum or Average | 0.33 | 19.08 | 0.33 | 19.08 | 34.17 | 27.76 | 23.50 | 27.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 23.36 | 0.33 | 24.71 |
Maximum of Months | 0.17 | 19.29 | 0.17 | 19.29 | 6.83 | 28.21 | 4.67 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 4.00 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.66 | 5.00 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.52 | 3.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.69 | 6.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.58 | 2.83 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 27.64 | 23.83 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.74 | 6.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 18.13 | 18.17 | 18.13 | 3.67 | 19.02 | 3.67 | 19.77 |
February | 9.83 | 18.40 | 9.83 | 18.40 | 1.17 | 18.91 | 1.17 | 19.38 |
March | 14.50 | 18.51 | 14.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
April | 2.67 | 19.66 | 2.67 | 19.66 | 2.00 | 21.07 | 2.00 | 21.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 24.87 | 21.83 | 24.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 24.93 | 26.83 | 24.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 25.26 | 26.00 | 25.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 25.29 | 31.33 | 25.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 26.06 | 16.67 | 26.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 25.68 | 41.33 | 25.66 |
November | 4.50 | 19.69 | 4.50 | 19.69 | 15.00 | 23.67 | 15.00 | 24.59 |
December | 18.33 | 18.81 | 18.33 | 18.81 | 5.67 | 19.93 | 5.67 | 20.79 |
Annual Sum or Average | 68.00 | 18.60 | 68.00 | 18.60 | 192.50 | 22.65 | 191.50 | 23.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 | 18.51 |
Maximum of Months | 18.33 | 19.69 | 18.33 | 19.69 | 42.17 | 26.06 | 41.33 | 26.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 0.67 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 1.33 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.73 | 2.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.48 | 2.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.49 | 1.67 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 3.33 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.75 | 3.33 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.00 | 27.70 | 14.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 3.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.50 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 1.17 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 5.00 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 3.33 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.76 | 6.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.66 | 3.00 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.89 | 5.33 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.71 | 3.33 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 28.33 | 27.79 | 28.33 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.98 | 6.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.83 | 4.00 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.74 | 1.50 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.35 | 1.50 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.71 | 6.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.88 | 8.83 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.29 | 8.00 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.86 | 4.83 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 37.17 | 27.67 | 36.67 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.88 | 8.83 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.44 | 0.17 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.67 | 0.50 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.74 | 1.67 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.99 | 2.17 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.95 | 2.50 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.62 | 2.83 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.57 | 1.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 3.33 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.87 | 3.33 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.33 | 27.83 | 18.67 | 27.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 3.33 | 28.07 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 178.50 | 23.70 | 130.83 | 24.08 | 0.00 | 24.08 |
February | 103.00 | 23.79 | 198.67 | 24.24 | 0.00 | 24.24 |
March | 95.00 | 23.73 | 220.67 | 24.31 | 0.00 | 24.31 |
April | 0.00 | 0.00 | 378.33 | 24.58 | 0.00 | 24.58 |
May | 0.00 | 0.00 | 508.00 | 24.43 | 0.00 | 24.43 |
June | 0.00 | 0.00 | 495.83 | 24.38 | 0.00 | 24.38 |
July | 0.00 | 0.00 | 497.00 | 24.42 | 0.00 | 24.42 |
August | 0.00 | 0.00 | 514.00 | 24.39 | 0.00 | 24.39 |
September | 0.00 | 0.00 | 484.67 | 24.40 | 0.00 | 24.40 |
October | 0.00 | 0.00 | 445.33 | 24.51 | 0.00 | 24.51 |
November | 7.17 | 23.92 | 300.83 | 24.56 | 0.00 | 24.56 |
December | 106.83 | 23.72 | 202.67 | 24.31 | 0.00 | 24.31 |
Annual Sum or Average | 490.50 | 23.73 | 4376.83 | 24.39 | 0.00 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 130.83 | 24.08 | 0.00 | 24.08 |
Maximum of Months | 178.50 | 23.92 | 514.00 | 24.58 | 0.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.17 | 22.69 | 49.00 | 22.86 | 0.00 | 22.86 |
February | 317.17 | 22.81 | 80.33 | 23.09 | 0.33 | 23.08 |
March | 313.50 | 22.93 | 105.33 | 23.27 | 0.00 | 23.27 |
April | 111.00 | 23.30 | 194.67 | 23.99 | 0.00 | 23.99 |
May | 0.83 | 23.22 | 422.17 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 420.67 | 24.25 | 0.00 | 24.25 |
July | 0.83 | 23.25 | 422.83 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 456.50 | 24.25 | 0.00 | 24.25 |
September | 1.67 | 23.24 | 376.17 | 24.28 | 0.00 | 24.28 |
October | 40.83 | 23.29 | 339.50 | 24.22 | 0.00 | 24.22 |
November | 206.33 | 23.27 | 127.50 | 23.67 | 0.00 | 23.67 |
December | 334.33 | 22.84 | 76.17 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 1729.67 | 22.91 | 3070.83 | 23.79 | 0.33 | 23.79 |
Minimum of Months | 0.00 | 0.00 | 49.00 | 22.86 | 0.00 | 22.86 |
Maximum of Months | 403.17 | 23.30 | 456.50 | 24.28 | 0.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.00 | 22.00 | 43.33 | 22.06 | 16.67 | 22.01 |
February | 361.00 | 22.26 | 68.50 | 22.37 | 19.67 | 22.28 |
March | 368.50 | 22.53 | 84.33 | 22.75 | 9.67 | 22.69 |
April | 171.67 | 23.11 | 175.83 | 23.71 | 0.00 | 23.71 |
May | 2.17 | 23.23 | 411.17 | 24.28 | 0.00 | 24.28 |
June | 1.83 | 23.38 | 432.50 | 24.25 | 0.00 | 24.25 |
July | 1.67 | 23.27 | 437.00 | 24.29 | 0.00 | 24.29 |
August | 1.33 | 23.33 | 440.00 | 24.27 | 0.00 | 24.27 |
September | 11.50 | 23.29 | 358.67 | 24.26 | 0.00 | 24.26 |
October | 76.50 | 23.02 | 308.00 | 24.06 | 0.00 | 24.06 |
November | 303.33 | 22.84 | 84.50 | 23.12 | 0.00 | 23.12 |
December | 398.67 | 22.27 | 66.00 | 22.45 | 11.00 | 22.40 |
Annual Sum or Average | 2132.17 | 22.44 | 2909.83 | 23.45 | 57.00 | 23.42 |
Minimum of Months | 1.33 | 22.00 | 43.33 | 22.06 | 0.00 | 22.01 |
Maximum of Months | 434.00 | 23.38 | 440.00 | 24.29 | 19.67 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.83 | 21.41 | 144.00 | 21.37 | 112.00 | 21.21 |
February | 382.33 | 21.69 | 116.17 | 21.67 | 68.00 | 21.46 |
March | 386.33 | 22.03 | 121.83 | 22.18 | 46.67 | 22.01 |
April | 202.67 | 22.94 | 205.00 | 23.59 | 10.67 | 23.64 |
May | 15.50 | 26.14 | 483.00 | 24.45 | 15.33 | 24.50 |
June | 10.17 | 25.42 | 483.67 | 24.41 | 6.67 | 24.44 |
July | 25.17 | 26.43 | 484.50 | 24.60 | 25.00 | 24.68 |
August | 19.33 | 25.69 | 492.17 | 24.43 | 17.83 | 24.47 |
September | 33.83 | 24.70 | 420.33 | 24.42 | 19.50 | 24.48 |
October | 117.33 | 23.26 | 353.50 | 24.08 | 23.00 | 24.14 |
November | 330.33 | 22.26 | 108.83 | 22.59 | 14.83 | 22.52 |
December | 415.00 | 21.68 | 127.00 | 21.76 | 75.50 | 21.62 |
Annual Sum or Average | 2391.83 | 22.12 | 3540.00 | 23.24 | 435.00 | 23.15 |
Minimum of Months | 10.17 | 21.41 | 108.83 | 21.37 | 6.67 | 21.21 |
Maximum of Months | 453.83 | 26.43 | 492.17 | 24.60 | 112.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.67 | 21.67 | 114.50 | 21.73 | 68.17 | 21.57 |
February | 343.17 | 21.85 | 122.00 | 22.04 | 44.67 | 21.87 |
March | 314.00 | 22.03 | 170.33 | 22.54 | 37.33 | 22.38 |
April | 157.00 | 22.89 | 267.67 | 23.82 | 14.67 | 23.89 |
May | 45.83 | 26.51 | 469.50 | 24.65 | 43.50 | 24.81 |
June | 30.17 | 26.35 | 468.83 | 24.54 | 26.83 | 24.66 |
July | 54.00 | 26.56 | 470.17 | 24.76 | 51.50 | 24.94 |
August | 40.83 | 25.99 | 478.00 | 24.54 | 35.17 | 24.66 |
September | 73.83 | 25.14 | 404.17 | 24.60 | 44.17 | 24.76 |
October | 123.00 | 23.65 | 355.83 | 24.25 | 36.33 | 24.39 |
November | 268.00 | 22.33 | 144.33 | 22.93 | 10.17 | 22.88 |
December | 391.33 | 21.83 | 123.67 | 22.04 | 52.17 | 21.92 |
Annual Sum or Average | 2282.83 | 22.51 | 3589.00 | 23.54 | 464.67 | 23.55 |
Minimum of Months | 30.17 | 21.67 | 114.50 | 21.73 | 10.17 | 21.57 |
Maximum of Months | 441.67 | 26.56 | 478.00 | 24.76 | 68.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 299.67 | 22.03 | 153.83 | 22.54 | 55.50 | 22.43 |
February | 254.33 | 22.14 | 169.67 | 22.75 | 36.67 | 22.61 |
March | 287.50 | 22.12 | 182.33 | 22.66 | 38.33 | 22.50 |
April | 170.83 | 22.94 | 241.17 | 23.78 | 11.17 | 23.83 |
May | 21.67 | 26.15 | 472.83 | 24.47 | 20.50 | 24.55 |
June | 10.17 | 25.16 | 468.00 | 24.39 | 6.00 | 24.42 |
July | 25.50 | 26.20 | 479.83 | 24.57 | 24.00 | 24.65 |
August | 30.67 | 26.06 | 489.50 | 24.49 | 29.00 | 24.58 |
September | 57.67 | 25.75 | 429.17 | 24.63 | 44.83 | 24.79 |
October | 103.83 | 24.61 | 401.83 | 24.55 | 52.00 | 24.74 |
November | 196.50 | 22.87 | 242.00 | 23.80 | 19.67 | 23.87 |
December | 270.00 | 22.21 | 207.83 | 22.98 | 51.50 | 22.93 |
Annual Sum or Average | 1728.33 | 22.76 | 3938.00 | 23.84 | 389.17 | 23.85 |
Minimum of Months | 10.17 | 22.03 | 153.83 | 22.54 | 6.00 | 22.43 |
Maximum of Months | 299.67 | 26.20 | 489.50 | 24.63 | 55.50 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 423.33 | 21.51 | 135.17 | 21.57 | 91.00 | 21.41 |
February | 350.83 | 21.66 | 130.00 | 21.86 | 58.83 | 21.67 |
March | 354.33 | 21.84 | 149.50 | 22.20 | 45.33 | 22.05 |
April | 211.00 | 22.83 | 222.50 | 23.63 | 19.17 | 23.74 |
May | 38.83 | 25.00 | 439.00 | 24.45 | 22.00 | 24.54 |
June | 28.50 | 25.29 | 442.00 | 24.46 | 17.33 | 24.54 |
July | 41.00 | 25.85 | 446.33 | 24.61 | 32.83 | 24.74 |
August | 37.00 | 24.94 | 460.00 | 24.43 | 22.33 | 24.51 |
September | 75.50 | 24.27 | 386.17 | 24.40 | 29.67 | 24.52 |
October | 131.33 | 23.41 | 336.00 | 24.13 | 33.17 | 24.25 |
November | 312.17 | 22.10 | 137.83 | 22.67 | 15.00 | 22.61 |
December | 380.17 | 21.62 | 142.83 | 21.90 | 66.00 | 21.76 |
Annual Sum or Average | 2384.00 | 22.22 | 3427.33 | 23.32 | 452.67 | 23.28 |
Minimum of Months | 28.50 | 21.51 | 130.00 | 21.57 | 15.00 | 21.41 |
Maximum of Months | 423.33 | 25.85 | 460.00 | 24.61 | 91.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.33 | 21.86 | 46.50 | 21.94 | 17.67 | 21.89 |
February | 389.00 | 22.07 | 65.00 | 22.12 | 28.50 | 22.02 |
March | 413.50 | 22.28 | 66.00 | 22.41 | 14.17 | 22.35 |
April | 231.50 | 23.09 | 162.33 | 23.55 | 8.33 | 23.59 |
May | 11.67 | 26.25 | 464.67 | 24.38 | 11.67 | 24.42 |
June | 1.00 | 26.24 | 478.00 | 24.33 | 1.00 | 24.33 |
July | 5.33 | 26.29 | 489.83 | 24.46 | 5.33 | 24.48 |
August | 0.83 | 26.57 | 512.83 | 24.38 | 0.83 | 24.38 |
September | 3.17 | 25.83 | 475.17 | 24.38 | 3.17 | 24.39 |
October | 62.17 | 23.60 | 393.50 | 24.27 | 8.00 | 24.30 |
November | 263.17 | 22.89 | 135.33 | 23.32 | 0.00 | 23.32 |
December | 377.50 | 22.18 | 80.83 | 22.45 | 10.00 | 22.42 |
Annual Sum or Average | 2203.17 | 22.38 | 3370.00 | 23.51 | 108.67 | 23.49 |
Minimum of Months | 0.83 | 21.86 | 46.50 | 21.94 | 0.00 | 21.89 |
Maximum of Months | 444.33 | 26.57 | 512.83 | 24.46 | 28.50 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.33 | 22.32 | 67.67 | 22.54 | 8.17 | 22.50 |
February | 321.00 | 22.40 | 89.17 | 22.68 | 9.50 | 22.62 |
March | 300.33 | 22.43 | 139.67 | 22.97 | 8.00 | 22.92 |
April | 135.17 | 23.15 | 266.67 | 23.97 | 9.17 | 24.01 |
May | 26.17 | 26.72 | 479.33 | 24.58 | 26.17 | 24.69 |
June | 8.67 | 26.60 | 480.50 | 24.44 | 8.00 | 24.48 |
July | 25.17 | 26.87 | 488.33 | 24.66 | 25.17 | 24.76 |
August | 14.00 | 26.96 | 511.33 | 24.51 | 14.00 | 24.57 |
September | 26.17 | 26.83 | 474.33 | 24.61 | 26.17 | 24.72 |
October | 62.33 | 24.46 | 415.50 | 24.49 | 22.00 | 24.59 |
November | 174.67 | 23.11 | 220.17 | 23.81 | 0.00 | 23.81 |
December | 321.33 | 22.39 | 119.17 | 22.87 | 6.33 | 22.85 |
Annual Sum or Average | 1817.33 | 22.82 | 3751.83 | 23.89 | 162.67 | 23.94 |
Minimum of Months | 8.67 | 22.32 | 67.67 | 22.54 | 0.00 | 22.50 |
Maximum of Months | 402.33 | 26.96 | 511.33 | 24.66 | 26.17 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 285.17 | 22.17 | 164.00 | 22.87 | 38.50 | 22.79 |
February | 234.83 | 22.23 | 173.83 | 23.01 | 24.17 | 22.92 |
March | 306.33 | 22.02 | 173.00 | 22.62 | 40.00 | 22.52 |
April | 204.00 | 23.01 | 240.00 | 23.70 | 43.67 | 23.72 |
May | 106.67 | 24.33 | 494.83 | 24.35 | 106.67 | 24.35 |
June | 99.00 | 24.20 | 486.67 | 24.33 | 98.83 | 24.31 |
July | 120.00 | 24.38 | 492.00 | 24.48 | 120.00 | 24.46 |
August | 111.00 | 24.39 | 514.00 | 24.48 | 111.00 | 24.46 |
September | 117.67 | 24.67 | 484.17 | 24.55 | 117.67 | 24.57 |
October | 121.83 | 24.83 | 445.00 | 24.74 | 91.83 | 24.84 |
November | 135.67 | 23.43 | 325.17 | 24.27 | 45.50 | 24.33 |
December | 247.17 | 22.42 | 251.17 | 23.40 | 56.17 | 23.40 |
Annual Sum or Average | 2089.33 | 23.09 | 4243.83 | 23.98 | 894.00 | 24.00 |
Minimum of Months | 99.00 | 22.02 | 164.00 | 22.62 | 24.17 | 22.52 |
Maximum of Months | 306.33 | 24.83 | 514.00 | 24.74 | 120.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.83 | 22.09 | 66.83 | 22.36 | 8.50 | 22.32 |
February | 319.67 | 22.23 | 98.83 | 22.55 | 17.33 | 22.46 |
March | 327.00 | 22.29 | 112.67 | 22.70 | 11.00 | 22.64 |
April | 165.50 | 23.17 | 231.50 | 23.90 | 10.67 | 23.96 |
May | 15.67 | 26.51 | 458.67 | 24.46 | 15.67 | 24.52 |
June | 9.50 | 26.42 | 468.67 | 24.43 | 8.33 | 24.48 |
July | 13.17 | 26.76 | 483.33 | 24.55 | 13.17 | 24.61 |
August | 5.33 | 26.98 | 511.17 | 24.45 | 5.33 | 24.47 |
September | 17.00 | 26.75 | 472.00 | 24.53 | 17.00 | 24.61 |
October | 51.50 | 24.47 | 425.50 | 24.47 | 19.00 | 24.55 |
November | 204.67 | 22.96 | 195.67 | 23.62 | 0.33 | 23.63 |
December | 313.33 | 22.27 | 123.67 | 22.83 | 4.67 | 22.82 |
Annual Sum or Average | 1824.17 | 22.60 | 3648.50 | 23.78 | 131.00 | 23.80 |
Minimum of Months | 5.33 | 22.09 | 66.83 | 22.36 | 0.33 | 22.32 |
Maximum of Months | 381.83 | 26.98 | 511.17 | 24.55 | 19.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.00 | 21.73 | 76.50 | 21.81 | 38.67 | 21.71 |
February | 362.17 | 22.05 | 86.83 | 22.14 | 33.00 | 21.99 |
March | 358.17 | 22.33 | 100.67 | 22.58 | 16.50 | 22.49 |
April | 169.83 | 23.28 | 224.83 | 23.84 | 10.33 | 23.89 |
May | 11.17 | 26.24 | 503.50 | 24.41 | 11.17 | 24.45 |
June | 2.50 | 26.18 | 491.17 | 24.38 | 2.50 | 24.39 |
July | 13.67 | 26.21 | 490.17 | 24.52 | 13.67 | 24.57 |
August | 10.50 | 25.81 | 508.17 | 24.39 | 10.50 | 24.42 |
September | 13.33 | 25.60 | 445.50 | 24.41 | 12.67 | 24.45 |
October | 86.83 | 23.45 | 375.50 | 24.19 | 15.17 | 24.23 |
November | 281.33 | 22.65 | 113.00 | 23.07 | 0.50 | 23.07 |
December | 394.33 | 22.06 | 89.33 | 22.26 | 27.50 | 22.19 |
Annual Sum or Average | 2139.83 | 22.36 | 3505.17 | 23.51 | 192.17 | 23.48 |
Minimum of Months | 2.50 | 21.73 | 76.50 | 21.81 | 0.50 | 21.71 |
Maximum of Months | 436.00 | 26.24 | 508.17 | 24.52 | 38.67 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.00 | 21.92 | 66.83 | 22.07 | 26.50 | 21.96 |
February | 288.67 | 22.12 | 76.50 | 22.38 | 16.83 | 22.28 |
March | 265.67 | 22.24 | 113.50 | 22.78 | 12.67 | 22.71 |
April | 137.50 | 23.21 | 215.33 | 24.01 | 14.50 | 24.09 |
May | 31.50 | 26.78 | 401.83 | 24.71 | 31.50 | 24.85 |
June | 17.50 | 26.55 | 402.50 | 24.57 | 16.17 | 24.65 |
July | 37.17 | 26.76 | 402.33 | 24.81 | 37.17 | 24.96 |
August | 26.33 | 26.27 | 407.50 | 24.59 | 24.33 | 24.69 |
September | 43.50 | 25.87 | 346.00 | 24.72 | 34.33 | 24.87 |
October | 96.83 | 23.99 | 307.00 | 24.43 | 30.67 | 24.57 |
November | 216.17 | 22.63 | 123.83 | 23.31 | 2.17 | 23.32 |
December | 320.83 | 22.09 | 88.67 | 22.38 | 25.17 | 22.31 |
Annual Sum or Average | 1845.67 | 22.69 | 2951.83 | 23.75 | 272.00 | 23.81 |
Minimum of Months | 17.50 | 21.92 | 66.83 | 22.07 | 2.17 | 21.96 |
Maximum of Months | 364.00 | 26.78 | 407.50 | 24.81 | 37.17 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.17 | 22.38 | 148.33 | 23.09 | 27.33 | 23.06 |
February | 212.67 | 22.52 | 173.50 | 23.26 | 18.17 | 23.21 |
March | 250.00 | 22.44 | 172.50 | 23.10 | 13.50 | 23.02 |
April | 131.50 | 23.29 | 267.00 | 24.03 | 10.33 | 24.07 |
May | 11.17 | 26.22 | 500.00 | 24.42 | 11.17 | 24.46 |
June | 3.00 | 25.64 | 488.50 | 24.36 | 2.50 | 24.37 |
July | 14.33 | 26.17 | 488.17 | 24.51 | 14.33 | 24.56 |
August | 17.00 | 26.25 | 509.00 | 24.45 | 17.00 | 24.50 |
September | 38.67 | 26.53 | 456.17 | 24.64 | 38.50 | 24.78 |
October | 84.00 | 25.16 | 422.17 | 24.66 | 48.67 | 24.84 |
November | 157.50 | 23.44 | 273.50 | 24.19 | 18.50 | 24.30 |
December | 233.33 | 22.62 | 211.83 | 23.51 | 27.83 | 23.56 |
Annual Sum or Average | 1409.33 | 23.06 | 4110.67 | 24.07 | 247.83 | 24.12 |
Minimum of Months | 3.00 | 22.38 | 148.33 | 23.09 | 2.50 | 23.02 |
Maximum of Months | 256.17 | 26.53 | 509.00 | 24.66 | 48.67 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.67 | 21.81 | 87.50 | 22.00 | 34.17 | 21.90 |
February | 323.33 | 22.03 | 106.67 | 22.34 | 26.00 | 22.23 |
March | 323.00 | 22.15 | 132.50 | 22.62 | 16.67 | 22.53 |
April | 169.00 | 23.20 | 249.50 | 23.93 | 17.50 | 24.02 |
May | 19.50 | 26.48 | 460.17 | 24.48 | 19.00 | 24.56 |
June | 17.50 | 26.15 | 464.33 | 24.45 | 14.50 | 24.52 |
July | 26.33 | 26.42 | 467.67 | 24.58 | 25.17 | 24.68 |
August | 17.50 | 26.01 | 483.17 | 24.43 | 16.00 | 24.49 |
September | 40.83 | 25.24 | 419.00 | 24.49 | 26.00 | 24.60 |
October | 93.67 | 23.85 | 367.17 | 24.30 | 28.67 | 24.42 |
November | 265.83 | 22.50 | 150.00 | 23.16 | 1.33 | 23.16 |
December | 350.17 | 21.95 | 117.50 | 22.38 | 24.83 | 22.32 |
Annual Sum or Average | 2045.33 | 22.47 | 3505.17 | 23.62 | 249.83 | 23.63 |
Minimum of Months | 17.50 | 21.81 | 87.50 | 22.00 | 1.33 | 21.90 |
Maximum of Months | 398.67 | 26.48 | 483.17 | 24.58 | 34.17 | 24.68 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15178 | 34.48519 | 0.34993 | 7.92473 |
February | 454.00000 | 24.21978 | 38.50291 | 0.39712 | 8.70397 |
March | 514.00000 | 24.22193 | 38.12765 | 0.40554 | 8.86110 |
April | 485.00000 | 24.45739 | 42.71356 | 0.51173 | 10.84374 |
May | 508.00000 | 24.42745 | 46.58817 | -0.2813 | 7.20508 |
June | 496.00000 | 24.38467 | 46.59135 | -0.2907 | 7.23146 |
July | 497.00000 | 24.42194 | 46.17319 | -0.2823 | 7.17080 |
August | 514.00000 | 24.39152 | 46.73292 | -0.2829 | 7.16858 |
September | 485.00000 | 24.39631 | 46.28138 | -0.2902 | 7.20496 |
October | 502.00000 | 24.45837 | 43.70720 | 0.54615 | 11.59658 |
November | 489.00000 | 24.38225 | 39.57015 | 0.47487 | 10.02585 |
December | 497.00000 | 24.24045 | 37.29306 | 0.40350 | 8.87724 |
Annual Sum or Average | 5943.00000 | 24.34654 | 42.25516 | 0.13561 | 8.55960 |
Minimum of Months | 454.00000 | 24.15178 | 34.48519 | -0.2907 | 7.16858 |
Maximum of Months | 514.00000 | 24.45837 | 46.73292 | 0.54615 | 11.59658 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96883 | 37.71561 | 0.07846 | 6.20957 |
February | 454.00000 | 23.18834 | 41.11323 | 0.15842 | 6.75629 |
March | 514.00000 | 23.38739 | 40.69502 | 0.21139 | 6.96071 |
April | 485.00000 | 23.96280 | 44.43188 | 0.39105 | 8.55455 |
May | 508.00000 | 24.18316 | 48.00933 | -0.3726 | 8.24001 |
June | 496.00000 | 24.17513 | 47.87840 | -0.3719 | 8.20504 |
July | 497.00000 | 24.19896 | 47.70454 | -0.3650 | 8.15159 |
August | 514.00000 | 24.19149 | 48.23048 | -0.3632 | 8.08584 |
September | 485.00000 | 24.14981 | 48.04605 | -0.3845 | 8.44109 |
October | 502.00000 | 24.13841 | 45.26198 | 0.46170 | 9.85554 |
November | 489.00000 | 23.76298 | 41.48943 | 0.31759 | 7.64171 |
December | 497.00000 | 23.24854 | 40.20046 | 0.16975 | 6.77619 |
Annual Sum or Average | 5943.00000 | 23.79992 | 44.25260 | -0.0080 | 7.82776 |
Minimum of Months | 454.00000 | 22.96883 | 37.71561 | -0.3845 | 6.20957 |
Maximum of Months | 514.00000 | 24.19896 | 48.23048 | 0.46170 | 9.85554 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.27237 | 38.74320 | -0.0926 | 6.94968 |
February | 454.00000 | 22.60367 | 41.72759 | 0.01598 | 7.11992 |
March | 514.00000 | 22.95914 | 40.99888 | 0.10598 | 6.89896 |
April | 485.00000 | 23.76503 | 44.01970 | 0.34353 | 8.07820 |
May | 508.00000 | 24.17702 | 47.70530 | -0.3624 | 8.08890 |
June | 496.00000 | 24.19374 | 47.58169 | -0.3505 | 7.87302 |
July | 497.00000 | 24.22835 | 47.44132 | -0.3410 | 7.79391 |
August | 514.00000 | 24.18786 | 48.03492 | -0.3524 | 7.92548 |
September | 485.00000 | 24.11488 | 47.87978 | -0.3900 | 8.58028 |
October | 502.00000 | 24.00172 | 45.19564 | 0.43091 | 9.53862 |
November | 489.00000 | 23.28687 | 41.92567 | 0.20053 | 6.88164 |
December | 497.00000 | 22.61469 | 41.03944 | 0.01334 | 6.91391 |
Annual Sum or Average | 5943.00000 | 23.53984 | 44.37618 | -0.0664 | 7.72300 |
Minimum of Months | 454.00000 | 22.27237 | 38.74320 | -0.3900 | 6.88164 |
Maximum of Months | 514.00000 | 24.22835 | 48.03492 | 0.43091 | 9.53862 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.65991 | 42.17037 | -0.2561 | 9.18426 |
February | 454.00000 | 22.03968 | 44.15608 | -0.1276 | 9.03661 |
March | 514.00000 | 22.52703 | 43.15659 | -0.0021 | 7.99952 |
April | 485.00000 | 23.61520 | 46.23004 | 0.32332 | 8.53005 |
May | 508.00000 | 24.36275 | 49.45304 | -0.2517 | 7.10700 |
June | 496.00000 | 24.37053 | 48.54877 | -0.2322 | 6.84307 |
July | 497.00000 | 24.48205 | 49.09947 | -0.1965 | 6.90838 |
August | 514.00000 | 24.34554 | 49.98475 | -0.2454 | 7.05213 |
September | 485.00000 | 24.29173 | 50.38586 | -0.2937 | 7.84544 |
October | 502.00000 | 23.98999 | 48.26093 | 0.45585 | 10.80573 |
November | 489.00000 | 22.82547 | 44.62377 | 0.09286 | 7.33377 |
December | 497.00000 | 22.05929 | 44.62348 | -0.1271 | 8.45878 |
Annual Sum or Average | 5943.00000 | 23.38994 | 46.74077 | -0.0722 | 8.08421 |
Minimum of Months | 454.00000 | 21.65991 | 42.17037 | -0.2937 | 6.84307 |
Maximum of Months | 514.00000 | 24.48205 | 50.38586 | 0.45585 | 10.80573 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.98425 | 41.16004 | -0.1507 | 8.38379 |
February | 454.00000 | 22.38111 | 43.04197 | -0.0180 | 8.45164 |
March | 514.00000 | 22.86874 | 41.84284 | 0.11024 | 8.68749 |
April | 485.00000 | 23.77514 | 45.19146 | 0.40411 | 10.09017 |
May | 508.00000 | 24.40097 | 48.81780 | -0.1750 | 7.21027 |
June | 496.00000 | 24.37734 | 48.11705 | -0.1695 | 6.78803 |
July | 497.00000 | 24.50119 | 48.51485 | -0.1309 | 7.08702 |
August | 514.00000 | 24.34591 | 49.47446 | -0.1902 | 7.02765 |
September | 485.00000 | 24.30700 | 49.73116 | -0.2368 | 8.21729 |
October | 502.00000 | 24.05502 | 47.42712 | 0.50842 | 12.27166 |
November | 489.00000 | 23.15183 | 43.42137 | 0.19707 | 8.00585 |
December | 497.00000 | 22.30225 | 43.69541 | -0.0481 | 8.37499 |
Annual Sum or Average | 5943.00000 | 23.54540 | 45.88817 | 0.00773 | 8.37825 |
Minimum of Months | 454.00000 | 21.98425 | 41.16004 | -0.2368 | 6.78803 |
Maximum of Months | 514.00000 | 24.50119 | 49.73116 | 0.50842 | 12.27166 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.95320 | 38.54757 | 0.09886 | 9.68373 |
February | 454.00000 | 23.07153 | 40.96378 | 0.16092 | 9.74581 |
March | 514.00000 | 23.04012 | 41.33716 | 0.14592 | 8.93255 |
April | 485.00000 | 23.76937 | 45.41756 | 0.37907 | 9.59563 |
May | 508.00000 | 24.34878 | 49.43086 | -0.2519 | 7.21539 |
June | 496.00000 | 24.33851 | 48.67125 | -0.2494 | 7.02058 |
July | 497.00000 | 24.45863 | 49.13945 | -0.2052 | 6.98751 |
August | 514.00000 | 24.35905 | 49.74445 | -0.2204 | 6.98579 |
September | 485.00000 | 24.37914 | 49.68756 | -0.2233 | 7.77446 |
October | 502.00000 | 24.28992 | 46.60941 | 0.58217 | 13.91988 |
November | 489.00000 | 23.74699 | 41.31952 | 0.36614 | 10.60387 |
December | 497.00000 | 23.17604 | 41.10482 | 0.19060 | 10.38792 |
Annual Sum or Average | 5943.00000 | 23.83199 | 45.19548 | 0.06264 | 9.06085 |
Minimum of Months | 454.00000 | 22.95320 | 38.54757 | -0.2519 | 6.98579 |
Maximum of Months | 514.00000 | 24.45863 | 49.74445 | 0.58217 | 13.91988 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92532 | 40.98047 | -0.1668 | 9.02440 |
February | 454.00000 | 22.21872 | 43.11130 | -0.0522 | 9.30375 |
March | 514.00000 | 22.55210 | 42.40448 | 0.03737 | 8.57904 |
April | 485.00000 | 23.56551 | 45.73677 | 0.35781 | 9.85309 |
May | 508.00000 | 24.26047 | 49.37987 | -0.2396 | 7.56265 |
June | 496.00000 | 24.29642 | 48.49548 | -0.2117 | 7.25987 |
July | 497.00000 | 24.39143 | 48.94770 | -0.1876 | 7.24570 |
August | 514.00000 | 24.27792 | 49.74832 | -0.2183 | 7.18906 |
September | 485.00000 | 24.18773 | 50.11155 | -0.2771 | 8.51867 |
October | 502.00000 | 23.93651 | 47.72192 | 0.48306 | 11.77748 |
November | 489.00000 | 22.83679 | 43.83634 | 0.13097 | 8.06319 |
December | 497.00000 | 22.21889 | 43.53476 | -0.0607 | 8.81322 |
Annual Sum or Average | 5943.00000 | 23.39706 | 46.18755 | -0.0345 | 8.58968 |
Minimum of Months | 454.00000 | 21.92532 | 40.98047 | -0.2771 | 7.18906 |
Maximum of Months | 514.00000 | 24.39143 | 50.11155 | 0.48306 | 11.77748 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10130 | 40.74654 | -0.1284 | 7.21083 |
February | 454.00000 | 22.33223 | 44.22761 | -0.0475 | 7.30503 |
March | 514.00000 | 22.62061 | 43.53513 | 0.02308 | 6.92334 |
April | 485.00000 | 23.59355 | 47.24911 | 0.30373 | 7.73853 |
May | 508.00000 | 24.28360 | 49.04897 | -0.3191 | 7.59154 |
June | 496.00000 | 24.31010 | 48.09910 | -0.2914 | 7.15131 |
July | 497.00000 | 24.42891 | 47.89547 | -0.2439 | 6.86810 |
August | 514.00000 | 24.37366 | 48.39068 | -0.2496 | 6.83614 |
September | 485.00000 | 24.36194 | 48.38175 | -0.2791 | 7.12796 |
October | 502.00000 | 24.21512 | 46.55825 | 0.50301 | 10.94986 |
November | 489.00000 | 23.42533 | 43.64517 | 0.24345 | 7.26936 |
December | 497.00000 | 22.62527 | 42.92975 | 0.02575 | 7.10465 |
Annual Sum or Average | 5943.00000 | 23.56351 | 45.90170 | -0.0394 | 7.50774 |
Minimum of Months | 454.00000 | 22.10130 | 40.74654 | -0.3191 | 6.83614 |
Maximum of Months | 514.00000 | 24.42891 | 49.04897 | 0.50301 | 10.94986 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.68844 | 39.52232 | 0.03095 | 6.94419 |
February | 454.00000 | 22.88829 | 42.82439 | 0.10684 | 7.28274 |
March | 514.00000 | 23.16242 | 41.92988 | 0.17802 | 7.93812 |
April | 485.00000 | 23.92034 | 45.77087 | 0.42013 | 9.66612 |
May | 508.00000 | 24.41767 | 48.30226 | -0.2118 | 7.05840 |
June | 496.00000 | 24.38515 | 47.58072 | -0.2070 | 6.66499 |
July | 497.00000 | 24.53276 | 47.30061 | -0.1518 | 6.66413 |
August | 514.00000 | 24.43675 | 47.91656 | -0.1732 | 6.51808 |
September | 485.00000 | 24.47331 | 47.78949 | -0.1919 | 6.99943 |
October | 502.00000 | 24.34980 | 45.79553 | 0.57297 | 12.80799 |
November | 489.00000 | 23.83178 | 42.34265 | 0.36639 | 8.77344 |
December | 497.00000 | 23.00552 | 41.99328 | 0.13312 | 7.56641 |
Annual Sum or Average | 5943.00000 | 23.84668 | 44.93554 | 0.07142 | 7.90670 |
Minimum of Months | 454.00000 | 22.68844 | 39.52232 | -0.2118 | 6.51808 |
Maximum of Months | 514.00000 | 24.53276 | 48.30226 | 0.57297 | 12.80799 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13828 | 38.75139 | 0.20250 | 9.52811 |
February | 454.00000 | 23.24567 | 43.52489 | 0.24950 | 9.45212 |
March | 514.00000 | 22.92238 | 44.03838 | 0.15445 | 8.78887 |
April | 485.00000 | 23.70693 | 50.07667 | 0.37977 | 9.28587 |
May | 508.00000 | 24.34136 | 56.39226 | -0.2466 | 6.77389 |
June | 496.00000 | 24.34775 | 56.23323 | -0.2340 | 6.54800 |
July | 497.00000 | 24.49616 | 56.56167 | -0.1664 | 6.23007 |
August | 514.00000 | 24.49728 | 56.69910 | -0.1316 | 6.08330 |
September | 485.00000 | 24.51682 | 55.70636 | -0.1287 | 6.35353 |
October | 502.00000 | 24.55973 | 49.75551 | 0.68074 | 16.03495 |
November | 489.00000 | 24.15534 | 43.60841 | 0.51330 | 12.27509 |
December | 497.00000 | 23.45790 | 41.83013 | 0.31393 | 10.94799 |
Annual Sum or Average | 5943.00000 | 23.95208 | 49.47649 | 0.13011 | 9.01603 |
Minimum of Months | 454.00000 | 22.92238 | 38.75139 | -0.2466 | 6.08330 |
Maximum of Months | 514.00000 | 24.55973 | 56.69910 | 0.68074 | 16.03495 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.58460 | 39.47407 | 0.00881 | 7.25916 |
February | 454.00000 | 22.79211 | 42.79524 | 0.08780 | 7.74327 |
March | 514.00000 | 22.96301 | 42.40209 | 0.12878 | 7.54989 |
April | 485.00000 | 23.84596 | 46.12443 | 0.40090 | 9.48759 |
May | 508.00000 | 24.31368 | 48.82302 | -0.2665 | 7.32659 |
June | 496.00000 | 24.35411 | 47.87247 | -0.2349 | 6.93842 |
July | 497.00000 | 24.47007 | 47.63551 | -0.1953 | 6.75205 |
August | 514.00000 | 24.41810 | 48.08176 | -0.1874 | 6.50166 |
September | 485.00000 | 24.43122 | 47.98151 | -0.2099 | 6.94212 |
October | 502.00000 | 24.33677 | 45.90728 | 0.56885 | 12.61782 |
November | 489.00000 | 23.66707 | 42.62704 | 0.33024 | 8.41670 |
December | 497.00000 | 22.97882 | 41.77608 | 0.13396 | 7.73793 |
Annual Sum or Average | 5943.00000 | 23.76859 | 45.14043 | 0.04567 | 7.93627 |
Minimum of Months | 454.00000 | 22.58460 | 39.47407 | -0.2665 | 6.50166 |
Maximum of Months | 514.00000 | 24.47007 | 48.82302 | 0.56885 | 12.61782 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.02681 | 41.50766 | -0.1476 | 7.74670 |
February | 454.00000 | 22.43137 | 43.83933 | -0.0221 | 7.80892 |
March | 514.00000 | 22.84088 | 42.98132 | 0.08096 | 7.36776 |
April | 485.00000 | 23.81435 | 46.44915 | 0.36968 | 8.67761 |
May | 508.00000 | 24.36923 | 49.41458 | -0.2639 | 7.06184 |
June | 496.00000 | 24.36321 | 48.53842 | -0.2523 | 6.85366 |
July | 497.00000 | 24.46528 | 49.00551 | -0.2193 | 6.86372 |
August | 514.00000 | 24.35299 | 49.76730 | -0.2581 | 7.00670 |
September | 485.00000 | 24.32414 | 50.17758 | -0.2922 | 7.50686 |
October | 502.00000 | 24.11687 | 47.94585 | 0.48153 | 10.80479 |
November | 489.00000 | 23.23270 | 44.16479 | 0.19458 | 7.16942 |
December | 497.00000 | 22.45298 | 43.90332 | -0.0183 | 7.45351 |
Annual Sum or Average | 5943.00000 | 23.57322 | 46.49090 | -0.0299 | 7.69046 |
Minimum of Months | 454.00000 | 22.02681 | 41.50766 | -0.2922 | 6.85366 |
Maximum of Months | 514.00000 | 24.46528 | 50.17758 | 0.48153 | 10.80479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.27350 | 40.36217 | -0.0721 | 7.61719 |
February | 385.00000 | 22.62772 | 42.40168 | 0.04166 | 7.64877 |
March | 433.00000 | 23.00899 | 41.48932 | 0.14337 | 8.19898 |
April | 410.00000 | 23.90236 | 45.39120 | 0.41905 | 10.01171 |
May | 430.00000 | 24.48765 | 48.58162 | -0.1867 | 7.32896 |
June | 418.00000 | 24.44628 | 47.82165 | -0.1935 | 6.93234 |
July | 422.00000 | 24.57924 | 48.17723 | -0.1504 | 7.19064 |
August | 433.00000 | 24.42182 | 49.14338 | -0.2065 | 7.13741 |
September | 410.00000 | 24.40360 | 49.40696 | -0.2367 | 8.11697 |
October | 427.00000 | 24.19692 | 47.14144 | 0.52269 | 12.26378 |
November | 417.00000 | 23.40353 | 42.73332 | 0.25394 | 8.04578 |
December | 422.00000 | 22.57328 | 42.87698 | 0.02404 | 7.76792 |
Annual Sum or Average | 5034.00000 | 23.69952 | 45.47559 | 0.02925 | 8.18914 |
Minimum of Months | 385.00000 | 22.27350 | 40.36217 | -0.2367 | 6.93234 |
Maximum of Months | 433.00000 | 24.57924 | 49.40696 | 0.52269 | 12.26378 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32894 | 37.72225 | 0.20339 | 9.18193 |
February | 454.00000 | 23.44582 | 40.59276 | 0.25919 | 9.31902 |
March | 514.00000 | 23.34883 | 41.09872 | 0.22567 | 8.55606 |
April | 485.00000 | 23.97101 | 45.60606 | 0.42473 | 9.74853 |
May | 508.00000 | 24.37210 | 49.38213 | -0.2596 | 7.09237 |
June | 496.00000 | 24.34315 | 48.66385 | -0.2659 | 6.98875 |
July | 497.00000 | 24.45406 | 49.05559 | -0.2245 | 6.91492 |
August | 514.00000 | 24.38082 | 49.52375 | -0.2299 | 6.88709 |
September | 485.00000 | 24.43278 | 49.46503 | -0.2175 | 7.36207 |
October | 502.00000 | 24.40751 | 46.32029 | 0.60399 | 13.98396 |
November | 489.00000 | 24.04349 | 41.02701 | 0.44351 | 10.97703 |
December | 497.00000 | 23.53251 | 40.41706 | 0.28791 | 10.12653 |
Annual Sum or Average | 5943.00000 | 24.00787 | 44.93714 | 0.10195 | 8.91860 |
Minimum of Months | 454.00000 | 23.32894 | 37.72225 | -0.2659 | 6.88709 |
Maximum of Months | 514.00000 | 24.45406 | 49.52375 | 0.60399 | 13.98396 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29591 | 40.40593 | -0.0591 | 7.89492 |
February | 454.00000 | 22.62640 | 42.83440 | 0.05497 | 8.27269 |
March | 514.00000 | 22.88685 | 42.25637 | 0.12346 | 7.98188 |
April | 485.00000 | 23.82565 | 45.91535 | 0.41499 | 10.03441 |
May | 508.00000 | 24.31707 | 49.31659 | -0.2387 | 7.23699 |
June | 496.00000 | 24.33613 | 48.44258 | -0.2195 | 7.00492 |
July | 497.00000 | 24.42453 | 48.82586 | -0.1971 | 6.99884 |
August | 514.00000 | 24.32456 | 49.53087 | -0.2210 | 6.91092 |
September | 485.00000 | 24.28420 | 49.88613 | -0.2590 | 7.79801 |
October | 502.00000 | 24.11658 | 47.42361 | 0.51832 | 11.92300 |
November | 489.00000 | 23.25262 | 43.45400 | 0.23328 | 7.97072 |
December | 497.00000 | 22.59815 | 42.94775 | 0.04423 | 8.00322 |
Annual Sum or Average | 5943.00000 | 23.61366 | 45.95666 | 0.01497 | 8.16297 |
Minimum of Months | 454.00000 | 22.29591 | 40.40593 | -0.2590 | 6.91092 |
Maximum of Months | 514.00000 | 24.42453 | 49.88613 | 0.51832 | 11.92300 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208089E+11 | 0.470973E+10 | 251.61 | 0.144770E+11 | 0.633190E+10 | 0.00 | 1.00 | 02-JAN-06:12 | 0.00 | 01-JAN-00:10 | 67294.59 | 19-JAN-15:10 | 53588.01 | 02-JAN-06:12 | 24740.30 | 20-JAN-07:02 | 14551.94 | 19-JAN-15:10 | 0.00 |
February | 0.284080E+11 | 0.638899E+10 | 290.79 | 0.186874E+11 | 0.972061E+10 | 0.00 | 1.00 | 01-FEB-13:10 | 0.00 | 01-FEB-00:10 | 65332.87 | 27-FEB-15:40 | 48634.77 | 27-FEB-15:20 | 21546.35 | 24-FEB-11:10 | 14771.11 | 24-FEB-13:05 | 0.00 |
March | 0.338765E+11 | 0.766035E+10 | 352.11 | 0.234742E+11 | 0.104024E+11 | 0.00 | 1.00 | 06-MAR-09:20 | 0.00 | 01-MAR-00:10 | 68741.17 | 28-MAR-12:00 | 45854.58 | 29-MAR-15:00 | 25693.15 | 07-MAR-13:00 | 15626.38 | 30-MAR-12:00 | 0.00 |
April | 0.529547E+11 | 0.119568E+11 | 392.17 | 0.379394E+11 | 0.150153E+11 | 0.00 | 1.00 | 03-APR-15:40 | 0.00 | 01-APR-00:10 | 85264.53 | 28-APR-16:00 | 59534.54 | 28-APR-15:00 | 29049.42 | 28-APR-17:00 | 21422.00 | 28-APR-16:00 | 0.00 |
May | 0.918753E+11 | 0.215200E+11 | 449.68 | 0.629011E+11 | 0.289742E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:10 | 90598.39 | 30-MAY-12:03 | 79899.20 | 31-MAY-05:02 | 33441.09 | 26-MAY-11:30 | 22066.90 | 30-MAY-12:03 | 0.00 |
June | 0.977950E+11 | 0.232141E+11 | 451.93 | 0.665158E+11 | 0.312792E+11 | 0.00 | 1.00 | 01-JUN-06:05 | 0.00 | 01-JUN-00:10 | 95192.91 | 29-JUN-12:04 | 77617.11 | 05-JUN-04:02 | 40836.33 | 29-JUN-17:00 | 24048.69 | 29-JUN-12:04 | 0.00 |
July | 0.102381E+12 | 0.242746E+11 | 461.25 | 0.668653E+11 | 0.355162E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 105450.00 | 05-JUL-12:04 | 82132.27 | 24-JUL-04:02 | 39872.81 | 12-JUL-12:02 | 26113.47 | 20-JUL-12:03 | 0.00 |
August | 0.109033E+12 | 0.257048E+11 | 473.03 | 0.724531E+11 | 0.365804E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 102352.51 | 07-AUG-12:02 | 81863.69 | 07-AUG-04:02 | 41161.37 | 09-AUG-17:00 | 25789.90 | 03-AUG-16:00 | 0.00 |
September | 0.932134E+11 | 0.212743E+11 | 448.99 | 0.614091E+11 | 0.318043E+11 | 0.00 | 1.00 | 01-SEP-04:23 | 0.00 | 01-SEP-00:10 | 102801.49 | 05-SEP-12:02 | 81406.44 | 18-SEP-04:02 | 39959.66 | 05-SEP-12:02 | 24111.72 | 05-SEP-12:02 | 0.00 |
October | 0.830979E+11 | 0.191280E+11 | 438.61 | 0.580569E+11 | 0.250410E+11 | 0.00 | 1.00 | 01-OCT-16:22 | 0.00 | 01-OCT-00:10 | 105434.11 | 06-OCT-12:02 | 81286.93 | 23-OCT-04:02 | 46275.84 | 24-OCT-12:03 | 25567.99 | 06-OCT-12:02 | 0.00 |
November | 0.462738E+11 | 0.104071E+11 | 385.24 | 0.330738E+11 | 0.132000E+11 | 0.00 | 1.00 | 01-NOV-05:13 | 0.00 | 01-NOV-00:10 | 89231.34 | 07-NOV-13:05 | 60334.50 | 06-NOV-16:00 | 34378.75 | 07-NOV-13:05 | 20359.59 | 07-NOV-13:05 | 0.00 |
December | 0.305381E+11 | 0.687180E+10 | 291.17 | 0.211530E+11 | 0.938508E+10 | 0.00 | 1.00 | 01-DEC-14:50 | 0.00 | 01-DEC-00:10 | 77722.09 | 14-DEC-13:05 | 55257.62 | 15-DEC-15:30 | 29212.08 | 14-DEC-13:05 | 17615.78 | 14-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.790257E+12 | 0.183110E+12 | 4686.57 | 0.537006E+12 | 0.253251E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.208089E+11 | 0.470973E+10 | 251.61 | 0.144770E+11 | 0.633190E+10 | 0.00 | 1.00 | 0.00 | 65332.87 | 45854.58 | 21546.35 | 14551.94 | 0.00 | ||||||
Maximum of Months | 0.109033E+12 | 0.257048E+11 | 473.03 | 0.724531E+11 | 0.365804E+11 | 0.00 | 1.00 | 0.00 | 105450.00 | 82132.27 | 46275.84 | 26113.47 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.178933E+11 | 0.407172E+10 | 249.28 | 0.122058E+11 | 0.568754E+10 | 0.00 | 1.00 | 02-JAN-10:30 | 0.00 | 01-JAN-00:10 | 58646.82 | 19-JAN-15:10 | 40096.95 | 19-JAN-15:30 | 19343.99 | 19-JAN-14:50 | 12682.47 | 19-JAN-15:10 | 0.00 |
February | 0.251871E+11 | 0.568667E+10 | 293.19 | 0.165607E+11 | 0.862637E+10 | 0.00 | 1.00 | 01-FEB-13:30 | 0.00 | 01-FEB-00:10 | 56723.11 | 27-FEB-15:30 | 42277.45 | 27-FEB-15:20 | 17633.45 | 23-FEB-10:20 | 12790.41 | 24-FEB-14:00 | 0.00 |
March | 0.302395E+11 | 0.685393E+10 | 355.11 | 0.208895E+11 | 0.934997E+10 | 0.00 | 1.00 | 06-MAR-09:40 | 0.00 | 01-MAR-00:10 | 58449.42 | 30-MAR-13:00 | 40827.70 | 29-MAR-15:00 | 21392.56 | 07-MAR-11:30 | 13793.24 | 30-MAR-13:00 | 0.00 |
April | 0.476976E+11 | 0.108023E+11 | 398.53 | 0.337640E+11 | 0.139336E+11 | 0.00 | 1.00 | 04-APR-13:00 | 0.00 | 01-APR-00:10 | 80640.24 | 28-APR-16:00 | 55099.85 | 28-APR-15:20 | 26711.88 | 28-APR-16:00 | 20131.78 | 28-APR-16:00 | 0.00 |
May | 0.828356E+11 | 0.193331E+11 | 448.88 | 0.557214E+11 | 0.271142E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:10 | 115932.31 | 22-MAY-04:02 | 73564.73 | 30-MAY-04:02 | 42579.20 | 22-MAY-04:02 | 25292.80 | 22-MAY-04:02 | 0.00 |
June | 0.880677E+11 | 0.207850E+11 | 450.51 | 0.586283E+11 | 0.294394E+11 | 0.00 | 1.00 | 01-JUN-07:05 | 0.00 | 01-JUN-00:10 | 84615.14 | 19-JUN-11:00 | 73047.35 | 05-JUN-04:02 | 32899.44 | 29-JUN-15:00 | 21532.58 | 28-JUN-14:30 | 0.00 |
July | 0.915757E+11 | 0.215334E+11 | 456.59 | 0.578854E+11 | 0.336903E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 90504.07 | 03-JUL-04:02 | 74411.90 | 05-JUL-04:02 | 34297.65 | 22-JUL-10:30 | 23121.89 | 21-JUL-16:00 | 0.00 |
August | 0.940631E+11 | 0.220045E+11 | 463.10 | 0.600102E+11 | 0.340529E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 89975.67 | 05-AUG-05:03 | 73845.75 | 28-AUG-04:02 | 36048.03 | 09-AUG-17:10 | 22717.58 | 03-AUG-15:50 | 0.00 |
September | 0.797883E+11 | 0.181243E+11 | 436.10 | 0.502062E+11 | 0.295821E+11 | 0.00 | 1.00 | 01-SEP-04:23 | 0.00 | 01-SEP-00:10 | 92157.62 | 05-SEP-05:12 | 74250.12 | 11-SEP-04:02 | 34196.90 | 05-SEP-06:03 | 20458.18 | 06-SEP-16:00 | 0.00 |
October | 0.709235E+11 | 0.162709E+11 | 429.00 | 0.476693E+11 | 0.232543E+11 | 0.00 | 1.00 | 01-OCT-15:13 | 0.00 | 01-OCT-00:10 | 91361.47 | 06-OCT-14:00 | 69193.83 | 07-OCT-05:03 | 40050.03 | 07-OCT-08:00 | 22071.71 | 06-OCT-11:00 | 0.00 |
November | 0.388674E+11 | 0.879312E+10 | 382.85 | 0.269304E+11 | 0.119370E+11 | 0.00 | 1.00 | 01-NOV-07:15 | 0.00 | 01-NOV-00:10 | 76354.14 | 02-NOV-14:50 | 52010.76 | 02-NOV-15:20 | 26935.08 | 03-NOV-16:10 | 17991.76 | 02-NOV-15:00 | 0.00 |
December | 0.260454E+11 | 0.588688E+10 | 287.97 | 0.175778E+11 | 0.846765E+10 | 0.00 | 1.00 | 08-DEC-13:20 | 0.00 | 01-DEC-00:10 | 64344.50 | 14-DEC-13:30 | 48310.06 | 15-DEC-15:30 | 25984.54 | 12-DEC-15:00 | 14845.63 | 15-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.693184E+12 | 0.160146E+12 | 4651.10 | 0.458049E+12 | 0.235135E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.178933E+11 | 0.407172E+10 | 249.28 | 0.122058E+11 | 0.568754E+10 | 0.00 | 1.00 | 0.00 | 56723.11 | 40096.95 | 17633.45 | 12682.47 | 0.00 | ||||||
Maximum of Months | 0.940631E+11 | 0.220045E+11 | 463.10 | 0.600102E+11 | 0.340529E+11 | 0.00 | 1.00 | 0.00 | 115932.31 | 74411.90 | 42579.20 | 25292.80 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185582E+11 | 0.425707E+10 | 246.32 | 0.126429E+11 | 0.591532E+10 | 0.00 | 1.00 | 01-JAN-15:22 | 0.00 | 01-JAN-00:10 | 63400.46 | 19-JAN-15:00 | 46684.17 | 01-JAN-15:22 | 19564.55 | 19-JAN-14:40 | 13696.45 | 19-JAN-15:00 | 0.00 |
February | 0.264000E+11 | 0.600376E+10 | 291.17 | 0.175575E+11 | 0.884253E+10 | 0.00 | 1.00 | 01-FEB-14:10 | 0.00 | 01-FEB-00:10 | 61962.45 | 24-FEB-14:30 | 47308.95 | 27-FEB-15:30 | 16973.77 | 24-FEB-16:00 | 13836.97 | 24-FEB-14:10 | 0.00 |
March | 0.319046E+11 | 0.728482E+10 | 354.89 | 0.222083E+11 | 0.969633E+10 | 0.00 | 1.00 | 06-MAR-10:30 | 0.00 | 01-MAR-00:10 | 62995.45 | 29-MAR-15:00 | 47178.15 | 29-MAR-15:00 | 21598.58 | 07-MAR-11:30 | 14737.47 | 30-MAR-13:00 | 0.00 |
April | 0.507155E+11 | 0.115783E+11 | 399.09 | 0.363511E+11 | 0.143644E+11 | 0.00 | 1.00 | 04-APR-13:20 | 0.00 | 01-APR-00:10 | 89722.66 | 28-APR-16:00 | 64837.94 | 28-APR-15:20 | 26416.88 | 28-APR-16:00 | 22422.96 | 28-APR-16:00 | 0.00 |
May | 0.879703E+11 | 0.206345E+11 | 449.56 | 0.606075E+11 | 0.273628E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 129517.16 | 22-MAY-04:02 | 84995.52 | 22-MAY-04:02 | 44521.64 | 22-MAY-04:02 | 28313.12 | 22-MAY-04:02 | 0.00 |
June | 0.939928E+11 | 0.222821E+11 | 451.66 | 0.643955E+11 | 0.295973E+11 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 94448.04 | 28-JUN-14:30 | 79734.22 | 05-JUN-04:02 | 32637.09 | 29-JUN-15:00 | 24397.09 | 28-JUN-14:00 | 0.00 |
July | 0.969479E+11 | 0.229023E+11 | 457.89 | 0.631047E+11 | 0.338432E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 106202.26 | 03-JUL-04:02 | 85203.71 | 03-JUL-04:02 | 33597.38 | 22-JUL-10:00 | 25882.10 | 21-JUL-16:00 | 0.00 |
August | 0.991921E+11 | 0.233076E+11 | 464.81 | 0.649610E+11 | 0.342311E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 95004.64 | 23-AUG-04:02 | 84316.03 | 28-AUG-04:02 | 34481.71 | 07-AUG-13:00 | 25429.99 | 03-AUG-15:50 | 0.00 |
September | 0.833582E+11 | 0.190326E+11 | 438.54 | 0.534280E+11 | 0.299302E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 92213.89 | 11-SEP-14:00 | 78205.02 | 11-SEP-04:02 | 33638.08 | 18-SEP-10:00 | 22649.52 | 01-SEP-15:00 | 0.00 |
October | 0.738953E+11 | 0.170334E+11 | 428.28 | 0.503229E+11 | 0.235724E+11 | 0.00 | 1.00 | 01-OCT-14:53 | 0.00 | 01-OCT-00:10 | 99571.67 | 06-OCT-14:00 | 71249.03 | 05-OCT-15:00 | 39483.42 | 07-OCT-08:00 | 24050.84 | 05-OCT-15:00 | 0.00 |
November | 0.398986E+11 | 0.910676E+10 | 380.11 | 0.273897E+11 | 0.125089E+11 | 0.00 | 1.00 | 01-NOV-09:20 | 0.00 | 01-NOV-00:10 | 83808.97 | 02-NOV-14:30 | 59041.51 | 02-NOV-14:40 | 26891.31 | 07-NOV-13:05 | 19713.37 | 02-NOV-14:40 | 0.00 |
December | 0.269249E+11 | 0.614037E+10 | 286.89 | 0.181016E+11 | 0.882328E+10 | 0.00 | 1.00 | 08-DEC-14:00 | 0.00 | 01-DEC-00:10 | 69575.63 | 15-DEC-14:50 | 54283.62 | 15-DEC-15:00 | 26171.68 | 12-DEC-15:00 | 16365.46 | 15-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.729759E+12 | 0.169564E+12 | 4649.19 | 0.491071E+12 | 0.238688E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.185582E+11 | 0.425707E+10 | 246.32 | 0.126429E+11 | 0.591532E+10 | 0.00 | 1.00 | 0.00 | 61962.45 | 46684.17 | 16973.77 | 13696.45 | 0.00 | ||||||
Maximum of Months | 0.991921E+11 | 0.233076E+11 | 464.81 | 0.649610E+11 | 0.342311E+11 | 0.00 | 1.00 | 0.00 | 129517.16 | 85203.71 | 44521.64 | 28313.12 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 312.94 | 0.00 | 312.94 | 237.02 | 1174.35 | 0.17 | 0.00 | 0.00 |
February | 369.19 | 0.00 | 369.19 | 317.76 | 977.73 | 0.00 | 0.00 | 0.00 |
March | 428.30 | 0.00 | 428.30 | 451.85 | 846.31 | 0.00 | 0.00 | 0.00 |
April | 505.48 | 2.07 | 503.41 | 700.55 | 534.07 | 0.00 | 0.00 | 0.00 |
May | 572.56 | 20.94 | 551.61 | 1186.56 | 160.22 | 0.00 | 0.00 | 0.00 |
June | 651.12 | 45.08 | 606.03 | 1406.28 | 139.59 | 0.00 | 0.00 | 0.00 |
July | 631.87 | 24.07 | 607.80 | 1350.76 | 95.61 | 0.00 | 0.00 | 0.00 |
August | 565.85 | 4.45 | 561.40 | 1225.75 | 130.02 | 0.00 | 0.00 | 0.00 |
September | 488.77 | 0.04 | 488.73 | 968.20 | 181.37 | 0.00 | 0.00 | 0.00 |
October | 424.73 | 0.00 | 424.73 | 783.72 | 339.20 | 0.00 | 0.00 | 0.00 |
November | 322.44 | 0.00 | 322.44 | 361.26 | 746.20 | 0.00 | 0.00 | 0.00 |
December | 290.91 | 0.00 | 290.91 | 255.06 | 997.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 464.15 | 8.08 | 456.07 | 773.15 | 524.53 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 290.91 | 0.00 | 290.91 | 237.02 | 95.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 651.12 | 45.08 | 607.80 | 1406.28 | 1174.35 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 536.93 | 273.40 | 263.52 | 643.13 | 718.31 | 0.17 | 0.00 | 0.00 |
February | 597.88 | 288.64 | 309.24 | 754.86 | 602.61 | 0.00 | 0.00 | 0.00 |
March | 703.31 | 339.19 | 364.12 | 955.72 | 528.50 | 0.00 | 0.00 | 0.00 |
April | 771.80 | 349.06 | 422.74 | 1192.69 | 346.89 | 0.00 | 0.00 | 0.00 |
May | 795.52 | 344.95 | 450.57 | 1490.33 | 106.75 | 0.00 | 0.00 | 0.00 |
June | 806.79 | 319.95 | 486.84 | 1570.31 | 92.82 | 0.00 | 0.00 | 0.00 |
July | 777.86 | 284.65 | 493.21 | 1514.68 | 62.40 | 0.00 | 0.00 | 0.00 |
August | 716.77 | 246.43 | 470.34 | 1398.78 | 86.26 | 0.00 | 0.00 | 0.00 |
September | 634.93 | 218.29 | 416.64 | 1176.02 | 118.62 | 0.00 | 0.00 | 0.00 |
October | 627.44 | 264.78 | 362.66 | 1102.91 | 218.31 | 0.00 | 0.00 | 0.00 |
November | 555.51 | 283.39 | 272.12 | 778.70 | 465.75 | 0.00 | 0.00 | 0.00 |
December | 437.38 | 198.12 | 239.25 | 548.08 | 627.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 663.73 | 284.11 | 379.62 | 1095.70 | 329.79 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 437.38 | 198.12 | 239.25 | 548.08 | 62.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.79 | 349.06 | 493.21 | 1570.31 | 718.31 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1808.85 | 1290.03 | 518.83 | 2579.15 | 1089.16 | 0.17 | 0.00 | 0.00 |
February | 1640.53 | 1061.89 | 578.64 | 2392.01 | 931.30 | 0.00 | 0.00 | 0.00 |
March | 1047.35 | 472.67 | 574.68 | 1573.03 | 834.61 | 0.00 | 0.00 | 0.00 |
April | 776.28 | 181.90 | 594.38 | 1291.70 | 552.96 | 0.00 | 0.00 | 0.00 |
May | 593.14 | 25.21 | 567.93 | 1243.98 | 164.49 | 0.00 | 0.00 | 0.00 |
June | 585.92 | 5.46 | 580.45 | 1273.35 | 143.52 | 0.00 | 0.00 | 0.00 |
July | 613.36 | 11.27 | 602.09 | 1319.99 | 93.20 | 0.00 | 0.00 | 0.00 |
August | 721.58 | 86.61 | 634.97 | 1560.39 | 135.69 | 0.00 | 0.00 | 0.00 |
September | 865.78 | 228.17 | 637.61 | 1714.27 | 192.43 | 0.00 | 0.00 | 0.00 |
October | 1343.27 | 699.71 | 643.55 | 2438.32 | 356.70 | 0.00 | 0.00 | 0.00 |
November | 1709.39 | 1176.93 | 532.46 | 2660.97 | 732.27 | 0.00 | 0.00 | 0.00 |
December | 1767.47 | 1269.30 | 498.17 | 2630.76 | 961.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.00 | 539.74 | 580.26 | 1887.40 | 513.46 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 585.92 | 5.46 | 498.17 | 1243.98 | 93.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1808.85 | 1290.03 | 643.55 | 2660.97 | 1089.16 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 571.10 | 308.82 | 262.28 | 738.45 | 758.19 | 0.17 | 0.00 | 0.00 |
February | 646.62 | 327.28 | 319.34 | 867.55 | 638.67 | 0.00 | 0.00 | 0.00 |
March | 637.31 | 282.12 | 355.19 | 888.41 | 555.85 | 0.00 | 0.00 | 0.00 |
April | 791.55 | 364.13 | 427.42 | 1250.27 | 366.68 | 0.00 | 0.00 | 0.00 |
May | 658.27 | 214.43 | 443.84 | 1278.70 | 116.69 | 0.00 | 0.00 | 0.00 |
June | 731.26 | 256.42 | 474.85 | 1448.85 | 103.06 | 0.00 | 0.00 | 0.00 |
July | 667.51 | 185.16 | 482.35 | 1327.85 | 68.63 | 0.00 | 0.00 | 0.00 |
August | 674.93 | 206.61 | 468.33 | 1344.91 | 94.43 | 0.00 | 0.00 | 0.00 |
September | 621.50 | 213.20 | 408.30 | 1169.49 | 127.72 | 0.00 | 0.00 | 0.00 |
October | 636.29 | 274.93 | 361.35 | 1148.20 | 235.30 | 0.00 | 0.00 | 0.00 |
November | 545.37 | 274.08 | 271.29 | 813.43 | 494.53 | 0.00 | 0.00 | 0.00 |
December | 524.60 | 278.98 | 245.63 | 720.15 | 646.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 641.83 | 264.88 | 376.95 | 1083.83 | 349.02 | 0.17 | 0.00 | 0.00 |
Minimum of Months | 524.60 | 185.16 | 245.63 | 720.15 | 68.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 791.55 | 364.13 | 482.35 | 1448.85 | 758.19 | 0.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.31 | 0.00 | 104.31 | 75.06 | 426.54 | 0.00 | 0.00 | 0.00 |
February | 123.06 | 0.00 | 123.06 | 105.77 | 349.45 | 0.00 | 0.00 | 0.00 |
March | 142.76 | 0.00 | 142.76 | 155.13 | 292.60 | 0.00 | 0.00 | 0.00 |
April | 168.49 | 0.69 | 167.80 | 241.55 | 177.60 | 0.00 | 0.00 | 0.00 |
May | 190.84 | 6.98 | 183.86 | 405.58 | 48.08 | 0.00 | 0.00 | 0.00 |
June | 217.03 | 15.03 | 202.00 | 478.11 | 42.73 | 0.00 | 0.00 | 0.00 |
July | 210.61 | 8.02 | 202.59 | 457.70 | 30.17 | 0.00 | 0.00 | 0.00 |
August | 188.61 | 1.48 | 187.12 | 409.99 | 46.59 | 0.00 | 0.00 | 0.00 |
September | 162.91 | 0.01 | 162.90 | 324.06 | 67.46 | 0.00 | 0.00 | 0.00 |
October | 141.57 | 0.00 | 141.57 | 259.55 | 126.27 | 0.00 | 0.00 | 0.00 |
November | 107.47 | 0.00 | 107.47 | 113.91 | 281.37 | 0.00 | 0.00 | 0.00 |
December | 96.97 | 0.00 | 96.97 | 79.54 | 370.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 154.71 | 2.69 | 152.01 | 259.75 | 187.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.97 | 0.00 | 96.97 | 75.06 | 30.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.03 | 15.03 | 202.59 | 478.11 | 426.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.31 | 0.00 | 104.31 | 75.07 | 426.57 | 0.00 | 0.00 | 0.00 |
February | 123.06 | 0.00 | 123.06 | 105.77 | 349.47 | 0.00 | 0.00 | 0.00 |
March | 142.76 | 0.00 | 142.76 | 155.13 | 292.62 | 0.00 | 0.00 | 0.00 |
April | 168.49 | 0.69 | 167.80 | 241.56 | 177.61 | 0.00 | 0.00 | 0.00 |
May | 190.85 | 6.98 | 183.87 | 405.60 | 48.08 | 0.00 | 0.00 | 0.00 |
June | 217.04 | 15.03 | 202.01 | 478.13 | 42.73 | 0.00 | 0.00 | 0.00 |
July | 210.62 | 8.02 | 202.60 | 457.72 | 30.17 | 0.00 | 0.00 | 0.00 |
August | 188.62 | 1.48 | 187.13 | 410.01 | 46.59 | 0.00 | 0.00 | 0.00 |
September | 162.92 | 0.01 | 162.91 | 324.08 | 67.46 | 0.00 | 0.00 | 0.00 |
October | 141.58 | 0.00 | 141.58 | 259.56 | 126.28 | 0.00 | 0.00 | 0.00 |
November | 107.48 | 0.00 | 107.48 | 113.91 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 96.97 | 0.00 | 96.97 | 79.54 | 370.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 154.71 | 2.69 | 152.02 | 259.76 | 187.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.97 | 0.00 | 96.97 | 75.07 | 30.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.04 | 15.03 | 202.60 | 478.13 | 426.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.31 | 0.00 | 104.31 | 75.07 | 426.57 | 0.00 | 0.00 | 0.00 |
February | 123.06 | 0.00 | 123.06 | 105.77 | 349.47 | 0.00 | 0.00 | 0.00 |
March | 142.76 | 0.00 | 142.76 | 155.13 | 292.62 | 0.00 | 0.00 | 0.00 |
April | 168.49 | 0.69 | 167.80 | 241.56 | 177.61 | 0.00 | 0.00 | 0.00 |
May | 190.85 | 6.98 | 183.87 | 405.60 | 48.08 | 0.00 | 0.00 | 0.00 |
June | 217.04 | 15.03 | 202.01 | 478.13 | 42.73 | 0.00 | 0.00 | 0.00 |
July | 210.62 | 8.02 | 202.60 | 457.72 | 30.17 | 0.00 | 0.00 | 0.00 |
August | 188.62 | 1.48 | 187.13 | 410.01 | 46.59 | 0.00 | 0.00 | 0.00 |
September | 162.92 | 0.01 | 162.91 | 324.08 | 67.46 | 0.00 | 0.00 | 0.00 |
October | 141.58 | 0.00 | 141.58 | 259.56 | 126.28 | 0.00 | 0.00 | 0.00 |
November | 107.48 | 0.00 | 107.48 | 113.91 | 281.39 | 0.00 | 0.00 | 0.00 |
December | 96.97 | 0.00 | 96.97 | 79.54 | 370.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 154.71 | 2.69 | 152.02 | 259.76 | 187.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.97 | 0.00 | 96.97 | 75.07 | 30.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.04 | 15.03 | 202.60 | 478.13 | 426.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.50 | 263.00 | 253.50 | 603.52 | 772.59 | 0.00 | 0.00 | 0.00 |
February | 575.14 | 277.66 | 297.48 | 719.77 | 637.53 | 0.00 | 0.00 | 0.00 |
March | 676.55 | 326.28 | 350.27 | 926.56 | 544.06 | 0.00 | 0.00 | 0.00 |
April | 742.43 | 335.78 | 406.65 | 1162.67 | 346.69 | 0.00 | 0.00 | 0.00 |
May | 765.25 | 331.82 | 433.42 | 1454.43 | 101.13 | 0.00 | 0.00 | 0.00 |
June | 776.09 | 307.77 | 468.32 | 1529.21 | 88.33 | 0.00 | 0.00 | 0.00 |
July | 748.26 | 273.82 | 474.44 | 1470.13 | 63.78 | 0.00 | 0.00 | 0.00 |
August | 689.50 | 237.05 | 452.45 | 1349.55 | 95.57 | 0.00 | 0.00 | 0.00 |
September | 610.77 | 209.98 | 400.79 | 1134.16 | 136.33 | 0.00 | 0.00 | 0.00 |
October | 603.57 | 254.70 | 348.86 | 1060.34 | 243.64 | 0.00 | 0.00 | 0.00 |
November | 534.37 | 272.60 | 261.77 | 733.72 | 518.12 | 0.00 | 0.00 | 0.00 |
December | 420.73 | 190.58 | 230.15 | 512.60 | 684.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.48 | 273.30 | 365.18 | 1056.54 | 351.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 420.73 | 190.58 | 230.15 | 512.60 | 63.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 776.09 | 335.78 | 474.44 | 1529.21 | 772.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.42 | 10.40 | 10.02 | 23.86 | 30.55 | 0.00 | 0.00 | 0.00 |
February | 22.74 | 10.98 | 11.76 | 28.46 | 25.21 | 0.00 | 0.00 | 0.00 |
March | 26.75 | 12.90 | 13.85 | 36.64 | 21.51 | 0.00 | 0.00 | 0.00 |
April | 29.36 | 13.28 | 16.08 | 45.97 | 13.71 | 0.00 | 0.00 | 0.00 |
May | 30.26 | 13.12 | 17.14 | 57.51 | 4.00 | 0.00 | 0.00 | 0.00 |
June | 30.69 | 12.17 | 18.52 | 60.46 | 3.49 | 0.00 | 0.00 | 0.00 |
July | 29.59 | 10.83 | 18.76 | 58.13 | 2.52 | 0.00 | 0.00 | 0.00 |
August | 27.26 | 9.37 | 17.89 | 53.36 | 3.78 | 0.00 | 0.00 | 0.00 |
September | 24.15 | 8.30 | 15.85 | 44.84 | 5.39 | 0.00 | 0.00 | 0.00 |
October | 23.86 | 10.07 | 13.79 | 41.92 | 9.63 | 0.00 | 0.00 | 0.00 |
November | 21.13 | 10.78 | 10.35 | 29.01 | 20.49 | 0.00 | 0.00 | 0.00 |
December | 16.64 | 7.54 | 9.10 | 20.27 | 27.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.24 | 10.81 | 14.44 | 41.77 | 13.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.64 | 7.54 | 9.10 | 20.27 | 2.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.69 | 13.28 | 18.76 | 60.46 | 30.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.94 | 430.00 | 172.94 | 862.12 | 409.97 | 0.00 | 0.00 | 0.00 |
February | 546.83 | 353.95 | 192.88 | 802.03 | 344.99 | 0.00 | 0.00 | 0.00 |
March | 349.11 | 157.55 | 191.56 | 534.24 | 292.80 | 0.00 | 0.00 | 0.00 |
April | 258.76 | 60.63 | 198.13 | 440.49 | 186.59 | 0.00 | 0.00 | 0.00 |
May | 197.71 | 8.40 | 189.31 | 423.13 | 50.34 | 0.00 | 0.00 | 0.00 |
June | 195.30 | 1.82 | 193.48 | 431.81 | 43.94 | 0.00 | 0.00 | 0.00 |
July | 204.45 | 3.76 | 200.69 | 445.28 | 30.15 | 0.00 | 0.00 | 0.00 |
August | 240.53 | 28.87 | 211.66 | 520.04 | 50.39 | 0.00 | 0.00 | 0.00 |
September | 288.59 | 76.06 | 212.53 | 572.69 | 74.90 | 0.00 | 0.00 | 0.00 |
October | 447.75 | 233.23 | 214.51 | 812.62 | 138.53 | 0.00 | 0.00 | 0.00 |
November | 569.79 | 392.30 | 177.48 | 884.48 | 284.44 | 0.00 | 0.00 | 0.00 |
December | 589.15 | 423.09 | 166.05 | 877.22 | 366.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 373.33 | 179.91 | 193.42 | 633.03 | 188.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 195.30 | 1.82 | 166.05 | 423.13 | 30.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 602.94 | 430.00 | 214.51 | 884.48 | 409.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.94 | 430.00 | 172.94 | 862.12 | 409.97 | 0.00 | 0.00 | 0.00 |
February | 546.83 | 353.95 | 192.88 | 802.03 | 344.99 | 0.00 | 0.00 | 0.00 |
March | 349.11 | 157.55 | 191.56 | 534.24 | 292.80 | 0.00 | 0.00 | 0.00 |
April | 258.76 | 60.63 | 198.13 | 440.49 | 186.59 | 0.00 | 0.00 | 0.00 |
May | 197.71 | 8.40 | 189.31 | 423.13 | 50.34 | 0.00 | 0.00 | 0.00 |
June | 195.30 | 1.82 | 193.48 | 431.81 | 43.94 | 0.00 | 0.00 | 0.00 |
July | 204.45 | 3.76 | 200.69 | 445.28 | 30.15 | 0.00 | 0.00 | 0.00 |
August | 240.53 | 28.87 | 211.66 | 520.04 | 50.39 | 0.00 | 0.00 | 0.00 |
September | 288.59 | 76.06 | 212.53 | 572.69 | 74.90 | 0.00 | 0.00 | 0.00 |
October | 447.75 | 233.23 | 214.51 | 812.62 | 138.53 | 0.00 | 0.00 | 0.00 |
November | 569.79 | 392.30 | 177.48 | 884.48 | 284.44 | 0.00 | 0.00 | 0.00 |
December | 589.15 | 423.09 | 166.05 | 877.22 | 366.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 373.33 | 179.91 | 193.42 | 633.03 | 188.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 195.30 | 1.82 | 166.05 | 423.13 | 30.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 602.94 | 430.00 | 214.51 | 884.48 | 409.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.90 | 429.97 | 172.93 | 862.06 | 409.94 | 0.00 | 0.00 | 0.00 |
February | 546.80 | 353.93 | 192.87 | 801.98 | 344.97 | 0.00 | 0.00 | 0.00 |
March | 349.09 | 157.54 | 191.55 | 534.20 | 292.78 | 0.00 | 0.00 | 0.00 |
April | 258.74 | 60.63 | 198.11 | 440.46 | 186.58 | 0.00 | 0.00 | 0.00 |
May | 197.70 | 8.40 | 189.30 | 423.11 | 50.33 | 0.00 | 0.00 | 0.00 |
June | 195.29 | 1.82 | 193.47 | 431.78 | 43.93 | 0.00 | 0.00 | 0.00 |
July | 204.44 | 3.76 | 200.68 | 445.26 | 30.15 | 0.00 | 0.00 | 0.00 |
August | 240.51 | 28.87 | 211.64 | 520.00 | 50.39 | 0.00 | 0.00 | 0.00 |
September | 288.57 | 76.05 | 212.52 | 572.66 | 74.90 | 0.00 | 0.00 | 0.00 |
October | 447.72 | 233.22 | 214.50 | 812.57 | 138.52 | 0.00 | 0.00 | 0.00 |
November | 569.75 | 392.28 | 177.47 | 884.42 | 284.42 | 0.00 | 0.00 | 0.00 |
December | 589.11 | 423.07 | 166.04 | 877.16 | 366.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 373.31 | 179.90 | 193.41 | 632.99 | 188.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 195.29 | 1.82 | 166.04 | 423.11 | 30.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 602.90 | 429.97 | 214.50 | 884.42 | 409.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 549.38 | 297.07 | 252.30 | 703.14 | 814.24 | 0.00 | 0.00 | 0.00 |
February | 622.02 | 314.82 | 307.19 | 833.94 | 677.97 | 0.00 | 0.00 | 0.00 |
March | 613.06 | 271.39 | 341.67 | 862.15 | 574.32 | 0.00 | 0.00 | 0.00 |
April | 761.44 | 350.27 | 411.16 | 1217.02 | 368.78 | 0.00 | 0.00 | 0.00 |
May | 633.22 | 206.27 | 426.95 | 1246.04 | 108.74 | 0.00 | 0.00 | 0.00 |
June | 703.44 | 246.66 | 456.78 | 1409.34 | 98.20 | 0.00 | 0.00 | 0.00 |
July | 642.11 | 178.11 | 464.00 | 1288.19 | 68.46 | 0.00 | 0.00 | 0.00 |
August | 649.25 | 198.74 | 450.51 | 1295.47 | 103.68 | 0.00 | 0.00 | 0.00 |
September | 597.85 | 205.09 | 392.76 | 1124.40 | 145.56 | 0.00 | 0.00 | 0.00 |
October | 612.08 | 264.47 | 347.61 | 1100.15 | 261.42 | 0.00 | 0.00 | 0.00 |
November | 524.62 | 263.65 | 260.97 | 767.97 | 552.13 | 0.00 | 0.00 | 0.00 |
December | 504.64 | 268.36 | 236.28 | 681.75 | 709.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 617.41 | 254.80 | 362.60 | 1044.92 | 371.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 504.64 | 178.11 | 236.28 | 681.75 | 68.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 761.44 | 350.27 | 464.00 | 1409.34 | 814.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.72 | 11.75 | 9.98 | 27.80 | 32.19 | 0.00 | 0.00 | 0.00 |
February | 24.59 | 12.45 | 12.15 | 32.97 | 26.81 | 0.00 | 0.00 | 0.00 |
March | 24.24 | 10.73 | 13.51 | 34.09 | 22.71 | 0.00 | 0.00 | 0.00 |
April | 30.11 | 13.85 | 16.26 | 48.12 | 14.58 | 0.00 | 0.00 | 0.00 |
May | 25.04 | 8.16 | 16.88 | 49.27 | 4.30 | 0.00 | 0.00 | 0.00 |
June | 27.81 | 9.75 | 18.06 | 55.72 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 25.39 | 7.04 | 18.35 | 50.93 | 2.71 | 0.00 | 0.00 | 0.00 |
August | 25.67 | 7.86 | 17.81 | 51.22 | 4.10 | 0.00 | 0.00 | 0.00 |
September | 23.64 | 8.11 | 15.53 | 44.46 | 5.76 | 0.00 | 0.00 | 0.00 |
October | 24.20 | 10.46 | 13.74 | 43.50 | 10.34 | 0.00 | 0.00 | 0.00 |
November | 20.74 | 10.42 | 10.32 | 30.36 | 21.83 | 0.00 | 0.00 | 0.00 |
December | 19.95 | 10.61 | 9.34 | 26.96 | 28.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.41 | 10.07 | 14.34 | 41.32 | 14.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.95 | 7.04 | 9.34 | 26.96 | 2.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.11 | 13.85 | 18.35 | 55.72 | 32.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 312.94 | 0.00 | 312.94 | 222.82 | 1264.79 | 0.00 | 0.00 | 0.00 |
February | 369.19 | 0.00 | 369.19 | 304.51 | 1057.92 | 0.00 | 0.00 | 0.00 |
March | 428.30 | 0.00 | 428.30 | 442.19 | 905.57 | 0.00 | 0.00 | 0.00 |
April | 505.48 | 2.07 | 503.41 | 697.10 | 564.53 | 0.00 | 0.00 | 0.00 |
May | 572.56 | 20.94 | 551.61 | 1196.52 | 163.00 | 0.00 | 0.00 | 0.00 |
June | 651.12 | 45.08 | 606.03 | 1419.20 | 140.55 | 0.00 | 0.00 | 0.00 |
July | 631.87 | 24.07 | 607.80 | 1365.03 | 95.00 | 0.00 | 0.00 | 0.00 |
August | 565.85 | 4.45 | 561.40 | 1235.41 | 133.24 | 0.00 | 0.00 | 0.00 |
September | 488.77 | 0.04 | 488.73 | 975.75 | 190.84 | 0.00 | 0.00 | 0.00 |
October | 424.73 | 0.00 | 424.73 | 784.28 | 361.84 | 0.00 | 0.00 | 0.00 |
November | 322.44 | 0.00 | 322.44 | 346.73 | 813.92 | 0.00 | 0.00 | 0.00 |
December | 290.91 | 0.00 | 290.91 | 241.58 | 1082.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 464.15 | 8.08 | 456.07 | 772.09 | 561.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 290.91 | 0.00 | 290.91 | 222.82 | 95.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 651.12 | 45.08 | 607.80 | 1419.20 | 1264.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 536.93 | 273.40 | 263.52 | 627.39 | 769.55 | 0.00 | 0.00 | 0.00 |
February | 597.88 | 288.64 | 309.24 | 741.79 | 646.69 | 0.00 | 0.00 | 0.00 |
March | 703.31 | 339.19 | 364.12 | 949.85 | 560.54 | 0.00 | 0.00 | 0.00 |
April | 771.80 | 349.06 | 422.74 | 1192.48 | 363.34 | 0.00 | 0.00 | 0.00 |
May | 795.52 | 344.95 | 450.57 | 1498.89 | 108.57 | 0.00 | 0.00 | 0.00 |
June | 806.79 | 319.95 | 486.84 | 1580.11 | 93.26 | 0.00 | 0.00 | 0.00 |
July | 777.86 | 284.65 | 493.21 | 1525.35 | 62.06 | 0.00 | 0.00 | 0.00 |
August | 716.77 | 246.43 | 470.34 | 1406.59 | 88.18 | 0.00 | 0.00 | 0.00 |
September | 634.93 | 218.29 | 416.64 | 1182.04 | 124.47 | 0.00 | 0.00 | 0.00 |
October | 627.44 | 264.78 | 362.66 | 1104.86 | 231.34 | 0.00 | 0.00 | 0.00 |
November | 555.51 | 283.39 | 272.12 | 767.44 | 501.52 | 0.00 | 0.00 | 0.00 |
December | 437.38 | 198.12 | 239.25 | 535.91 | 674.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 663.73 | 284.11 | 379.62 | 1094.65 | 350.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 437.38 | 198.12 | 239.25 | 535.91 | 62.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.79 | 349.06 | 493.21 | 1580.11 | 769.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1808.85 | 1290.03 | 518.83 | 2561.36 | 1167.21 | 0.00 | 0.00 | 0.00 |
February | 1640.53 | 1061.89 | 578.64 | 2375.95 | 999.96 | 0.00 | 0.00 | 0.00 |
March | 1047.35 | 472.67 | 574.68 | 1564.89 | 889.96 | 0.00 | 0.00 | 0.00 |
April | 776.28 | 181.90 | 594.38 | 1290.87 | 583.50 | 0.00 | 0.00 | 0.00 |
May | 593.14 | 25.21 | 567.93 | 1253.68 | 168.08 | 0.00 | 0.00 | 0.00 |
June | 585.92 | 5.46 | 580.45 | 1285.39 | 144.84 | 0.00 | 0.00 | 0.00 |
July | 613.36 | 11.27 | 602.09 | 1333.75 | 93.29 | 0.00 | 0.00 | 0.00 |
August | 721.58 | 86.61 | 634.97 | 1570.76 | 139.31 | 0.00 | 0.00 | 0.00 |
September | 865.78 | 228.17 | 637.61 | 1722.54 | 202.13 | 0.00 | 0.00 | 0.00 |
October | 1343.27 | 699.71 | 643.55 | 2443.05 | 376.61 | 0.00 | 0.00 | 0.00 |
November | 1709.39 | 1176.93 | 532.46 | 2649.15 | 785.57 | 0.00 | 0.00 | 0.00 |
December | 1767.47 | 1269.30 | 498.17 | 2616.72 | 1033.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.00 | 539.74 | 580.26 | 1886.67 | 546.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 585.92 | 5.46 | 498.17 | 1253.68 | 93.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1808.85 | 1290.03 | 643.55 | 2649.15 | 1167.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 571.10 | 308.82 | 262.28 | 728.68 | 814.72 | 0.00 | 0.00 | 0.00 |
February | 646.62 | 327.28 | 319.34 | 858.34 | 689.28 | 0.00 | 0.00 | 0.00 |
March | 637.31 | 282.12 | 355.19 | 882.95 | 594.45 | 0.00 | 0.00 | 0.00 |
April | 791.55 | 364.13 | 427.42 | 1248.51 | 387.72 | 0.00 | 0.00 | 0.00 |
May | 658.27 | 214.43 | 443.84 | 1284.36 | 119.55 | 0.00 | 0.00 | 0.00 |
June | 731.26 | 256.42 | 474.85 | 1456.56 | 104.58 | 0.00 | 0.00 | 0.00 |
July | 667.51 | 185.16 | 482.35 | 1336.13 | 69.07 | 0.00 | 0.00 | 0.00 |
August | 674.93 | 206.61 | 468.33 | 1350.90 | 97.10 | 0.00 | 0.00 | 0.00 |
September | 621.50 | 213.20 | 408.30 | 1172.91 | 134.94 | 0.00 | 0.00 | 0.00 |
October | 636.29 | 274.93 | 361.35 | 1148.19 | 250.20 | 0.00 | 0.00 | 0.00 |
November | 545.37 | 274.08 | 271.29 | 803.96 | 537.02 | 0.00 | 0.00 | 0.00 |
December | 524.60 | 278.98 | 245.63 | 710.93 | 698.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 641.83 | 264.88 | 376.95 | 1082.74 | 373.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 524.60 | 185.16 | 245.63 | 710.93 | 69.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 791.55 | 364.13 | 482.35 | 1456.56 | 814.72 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.838177E+09 | 0.00 | 0.838177E+09 | 0.634832E+09 | 0.314538E+10 |
February | 0.893151E+09 | 0.00 | 0.893151E+09 | 0.768725E+09 | 0.236534E+10 |
March | 0.114715E+10 | 0.00 | 0.114715E+10 | 0.121024E+10 | 0.226676E+10 |
April | 0.131021E+10 | 5377575.54 | 0.130484E+10 | 0.181582E+10 | 0.138431E+10 |
May | 0.153354E+10 | 56093230.24 | 0.147744E+10 | 0.317809E+10 | 0.429138E+09 |
June | 0.168770E+10 | 0.116860E+09 | 0.157084E+10 | 0.364507E+10 | 0.361823E+09 |
July | 0.169240E+10 | 64477283.85 | 0.162792E+10 | 0.361788E+10 | 0.256080E+09 |
August | 0.151557E+10 | 11920180.05 | 0.150365E+10 | 0.328304E+10 | 0.348250E+09 |
September | 0.126689E+10 | 97575.10 | 0.126679E+10 | 0.250957E+10 | 0.470098E+09 |
October | 0.113759E+10 | 0.00 | 0.113759E+10 | 0.209911E+10 | 0.908514E+09 |
November | 0.835757E+09 | 0.00 | 0.835757E+09 | 0.936383E+09 | 0.193414E+10 |
December | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.683156E+09 | 0.267162E+10 |
Annual Sum or Average | 0.146373E+11 | 0.254826E+09 | 0.143825E+11 | 0.243819E+11 | 0.165414E+11 |
Minimum of Months | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.634832E+09 | 0.256080E+09 |
Maximum of Months | 0.169240E+10 | 0.116860E+09 | 0.162792E+10 | 0.364507E+10 | 0.314538E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143810E+10 | 0.732287E+09 | 0.705815E+09 | 0.172255E+10 | 0.192391E+10 |
February | 0.144640E+10 | 0.698285E+09 | 0.748118E+09 | 0.182616E+10 | 0.145784E+10 |
March | 0.188374E+10 | 0.908478E+09 | 0.975265E+09 | 0.255981E+10 | 0.141554E+10 |
April | 0.200050E+10 | 0.904773E+09 | 0.109573E+10 | 0.309145E+10 | 0.899129E+09 |
May | 0.213071E+10 | 0.923918E+09 | 0.120680E+10 | 0.399169E+10 | 0.285925E+09 |
June | 0.209120E+10 | 0.829311E+09 | 0.126189E+10 | 0.407024E+10 | 0.240586E+09 |
July | 0.208342E+10 | 0.762419E+09 | 0.132100E+10 | 0.405691E+10 | 0.167130E+09 |
August | 0.191981E+10 | 0.660044E+09 | 0.125976E+10 | 0.374650E+10 | 0.231043E+09 |
September | 0.164574E+10 | 0.565799E+09 | 0.107994E+10 | 0.304823E+10 | 0.307451E+09 |
October | 0.168054E+10 | 0.709182E+09 | 0.971357E+09 | 0.295404E+10 | 0.584724E+09 |
November | 0.143988E+10 | 0.734539E+09 | 0.705340E+09 | 0.201840E+10 | 0.120722E+10 |
December | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.146799E+10 | 0.167986E+10 |
Annual Sum or Average | 0.209315E+11 | 0.895968E+10 | 0.119718E+11 | 0.345540E+11 | 0.104004E+11 |
Minimum of Months | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.146799E+10 | 0.167130E+09 |
Maximum of Months | 0.213071E+10 | 0.923918E+09 | 0.132100E+10 | 0.407024E+10 | 0.192391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484483E+10 | 0.345521E+10 | 0.138963E+10 | 0.690800E+10 | 0.291721E+10 |
February | 0.396877E+10 | 0.256892E+10 | 0.139985E+10 | 0.578674E+10 | 0.225301E+10 |
March | 0.280522E+10 | 0.126600E+10 | 0.153922E+10 | 0.421321E+10 | 0.223542E+10 |
April | 0.201212E+10 | 0.471490E+09 | 0.154063E+10 | 0.334810E+10 | 0.143327E+10 |
May | 0.158865E+10 | 67515546.51 | 0.152114E+10 | 0.333187E+10 | 0.440559E+09 |
June | 0.151869E+10 | 14155698.93 | 0.150454E+10 | 0.330053E+10 | 0.372000E+09 |
July | 0.164282E+10 | 30194881.76 | 0.161263E+10 | 0.353545E+10 | 0.249626E+09 |
August | 0.193269E+10 | 0.231981E+09 | 0.170071E+10 | 0.417934E+10 | 0.363427E+09 |
September | 0.224410E+10 | 0.591416E+09 | 0.165269E+10 | 0.444339E+10 | 0.498788E+09 |
October | 0.359780E+10 | 0.187412E+10 | 0.172369E+10 | 0.653081E+10 | 0.955373E+09 |
November | 0.443075E+10 | 0.305061E+10 | 0.138013E+10 | 0.689723E+10 | 0.189805E+10 |
December | 0.473399E+10 | 0.339970E+10 | 0.133429E+10 | 0.704622E+10 | 0.257578E+10 |
Annual Sum or Average | 0.353204E+11 | 0.170213E+11 | 0.182991E+11 | 0.595209E+11 | 0.161925E+11 |
Minimum of Months | 0.151869E+10 | 14155698.93 | 0.133429E+10 | 0.330053E+10 | 0.249626E+09 |
Maximum of Months | 0.484483E+10 | 0.345521E+10 | 0.172369E+10 | 0.704622E+10 | 0.291721E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152965E+10 | 0.827149E+09 | 0.702499E+09 | 0.197787E+10 | 0.203073E+10 |
February | 0.156430E+10 | 0.791751E+09 | 0.772548E+09 | 0.209878E+10 | 0.154506E+10 |
March | 0.170697E+10 | 0.755631E+09 | 0.951335E+09 | 0.237952E+10 | 0.148880E+10 |
April | 0.205171E+10 | 0.943823E+09 | 0.110788E+10 | 0.324071E+10 | 0.950431E+09 |
May | 0.176311E+10 | 0.574337E+09 | 0.118877E+10 | 0.342486E+10 | 0.312549E+09 |
June | 0.189543E+10 | 0.664628E+09 | 0.123080E+10 | 0.375542E+10 | 0.267137E+09 |
July | 0.178785E+10 | 0.495921E+09 | 0.129193E+10 | 0.355651E+10 | 0.183823E+09 |
August | 0.180774E+10 | 0.553374E+09 | 0.125437E+10 | 0.360221E+10 | 0.252926E+09 |
September | 0.161093E+10 | 0.552625E+09 | 0.105830E+10 | 0.303131E+10 | 0.331048E+09 |
October | 0.170423E+10 | 0.736379E+09 | 0.967852E+09 | 0.307533E+10 | 0.630230E+09 |
November | 0.141361E+10 | 0.710423E+09 | 0.703186E+09 | 0.210842E+10 | 0.128183E+10 |
December | 0.140510E+10 | 0.747211E+09 | 0.657885E+09 | 0.192884E+10 | 0.173204E+10 |
Annual Sum or Average | 0.202406E+11 | 0.835325E+10 | 0.118874E+11 | 0.341798E+11 | 0.110066E+11 |
Minimum of Months | 0.140510E+10 | 0.495921E+09 | 0.657885E+09 | 0.192884E+10 | 0.183823E+09 |
Maximum of Months | 0.205171E+10 | 0.943823E+09 | 0.129193E+10 | 0.375542E+10 | 0.203073E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279379E+09 | 0.00 | 0.279379E+09 | 0.201053E+09 | 0.114245E+10 |
February | 0.297703E+09 | 0.00 | 0.297703E+09 | 0.255877E+09 | 0.845383E+09 |
March | 0.382365E+09 | 0.00 | 0.382365E+09 | 0.415489E+09 | 0.783695E+09 |
April | 0.436717E+09 | 1792440.37 | 0.434925E+09 | 0.626089E+09 | 0.460335E+09 |
May | 0.511154E+09 | 18696858.78 | 0.492457E+09 | 0.108632E+10 | 0.128775E+09 |
June | 0.562540E+09 | 38951544.32 | 0.523589E+09 | 0.123925E+10 | 0.110758E+09 |
July | 0.564106E+09 | 21491411.10 | 0.542615E+09 | 0.122589E+10 | 80811779.13 |
August | 0.505167E+09 | 3973205.36 | 0.501194E+09 | 0.109813E+10 | 0.124780E+09 |
September | 0.422275E+09 | 32523.50 | 0.422243E+09 | 0.839972E+09 | 0.174852E+09 |
October | 0.379180E+09 | 0.00 | 0.379180E+09 | 0.695177E+09 | 0.338205E+09 |
November | 0.278573E+09 | 0.00 | 0.278573E+09 | 0.295250E+09 | 0.729323E+09 |
December | 0.259715E+09 | 0.00 | 0.259715E+09 | 0.213027E+09 | 0.992866E+09 |
Annual Sum or Average | 0.487887E+10 | 84937983.43 | 0.479394E+10 | 0.819152E+10 | 0.591223E+10 |
Minimum of Months | 0.259715E+09 | 0.00 | 0.259715E+09 | 0.201053E+09 | 80811779.13 |
Maximum of Months | 0.564106E+09 | 38951544.32 | 0.542615E+09 | 0.123925E+10 | 0.114245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279391E+09 | 0.00 | 0.279391E+09 | 0.201060E+09 | 0.114251E+10 |
February | 0.297716E+09 | 0.00 | 0.297716E+09 | 0.255888E+09 | 0.845432E+09 |
March | 0.382381E+09 | 0.00 | 0.382381E+09 | 0.415506E+09 | 0.783741E+09 |
April | 0.436736E+09 | 1792488.55 | 0.434943E+09 | 0.626118E+09 | 0.460360E+09 |
May | 0.511175E+09 | 18697361.36 | 0.492477E+09 | 0.108637E+10 | 0.128780E+09 |
June | 0.562562E+09 | 38952591.35 | 0.523610E+09 | 0.123931E+10 | 0.110762E+09 |
July | 0.564128E+09 | 21491988.79 | 0.542636E+09 | 0.122595E+10 | 80814036.28 |
August | 0.505187E+09 | 3973312.16 | 0.501214E+09 | 0.109818E+10 | 0.124785E+09 |
September | 0.422292E+09 | 32524.37 | 0.422259E+09 | 0.840011E+09 | 0.174860E+09 |
October | 0.379196E+09 | 0.00 | 0.379196E+09 | 0.695210E+09 | 0.338222E+09 |
November | 0.278584E+09 | 0.00 | 0.278584E+09 | 0.295263E+09 | 0.729363E+09 |
December | 0.259726E+09 | 0.00 | 0.259726E+09 | 0.213036E+09 | 0.992925E+09 |
Annual Sum or Average | 0.487907E+10 | 84940266.59 | 0.479413E+10 | 0.819189E+10 | 0.591256E+10 |
Minimum of Months | 0.259726E+09 | 0.00 | 0.259726E+09 | 0.201060E+09 | 80814036.28 |
Maximum of Months | 0.564128E+09 | 38952591.35 | 0.542636E+09 | 0.123931E+10 | 0.114251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279391E+09 | 0.00 | 0.279391E+09 | 0.201060E+09 | 0.114251E+10 |
February | 0.297716E+09 | 0.00 | 0.297716E+09 | 0.255888E+09 | 0.845432E+09 |
March | 0.382381E+09 | 0.00 | 0.382381E+09 | 0.415506E+09 | 0.783741E+09 |
April | 0.436736E+09 | 1792488.55 | 0.434943E+09 | 0.626118E+09 | 0.460360E+09 |
May | 0.511175E+09 | 18697361.36 | 0.492477E+09 | 0.108637E+10 | 0.128780E+09 |
June | 0.562562E+09 | 38952591.35 | 0.523610E+09 | 0.123931E+10 | 0.110762E+09 |
July | 0.564128E+09 | 21491988.79 | 0.542636E+09 | 0.122595E+10 | 80814036.28 |
August | 0.505187E+09 | 3973312.16 | 0.501214E+09 | 0.109818E+10 | 0.124785E+09 |
September | 0.422292E+09 | 32524.37 | 0.422259E+09 | 0.840011E+09 | 0.174860E+09 |
October | 0.379196E+09 | 0.00 | 0.379196E+09 | 0.695210E+09 | 0.338222E+09 |
November | 0.278584E+09 | 0.00 | 0.278584E+09 | 0.295263E+09 | 0.729363E+09 |
December | 0.259726E+09 | 0.00 | 0.259726E+09 | 0.213036E+09 | 0.992925E+09 |
Annual Sum or Average | 0.487907E+10 | 84940266.59 | 0.479413E+10 | 0.819189E+10 | 0.591256E+10 |
Minimum of Months | 0.259726E+09 | 0.00 | 0.259726E+09 | 0.201060E+09 | 80814036.28 |
Maximum of Months | 0.564128E+09 | 38952591.35 | 0.542636E+09 | 0.123931E+10 | 0.114251E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138338E+10 | 0.704420E+09 | 0.678961E+09 | 0.161647E+10 | 0.206931E+10 |
February | 0.139137E+10 | 0.671712E+09 | 0.719655E+09 | 0.174127E+10 | 0.154232E+10 |
March | 0.181207E+10 | 0.873907E+09 | 0.938160E+09 | 0.248171E+10 | 0.145722E+10 |
April | 0.192439E+10 | 0.870343E+09 | 0.105404E+10 | 0.301363E+10 | 0.898613E+09 |
May | 0.204964E+10 | 0.888759E+09 | 0.116088E+10 | 0.389555E+10 | 0.270873E+09 |
June | 0.201163E+10 | 0.797752E+09 | 0.121388E+10 | 0.396371E+10 | 0.228950E+09 |
July | 0.200415E+10 | 0.733406E+09 | 0.127074E+10 | 0.393759E+10 | 0.170826E+09 |
August | 0.184676E+10 | 0.634927E+09 | 0.121183E+10 | 0.361462E+10 | 0.255966E+09 |
September | 0.158312E+10 | 0.544268E+09 | 0.103885E+10 | 0.293973E+10 | 0.353359E+09 |
October | 0.161659E+10 | 0.682195E+09 | 0.934400E+09 | 0.284002E+10 | 0.652552E+09 |
November | 0.138509E+10 | 0.706586E+09 | 0.678504E+09 | 0.190180E+10 | 0.134297E+10 |
December | 0.112689E+10 | 0.510455E+09 | 0.616438E+09 | 0.137294E+10 | 0.183385E+10 |
Annual Sum or Average | 0.201351E+11 | 0.861873E+10 | 0.115163E+11 | 0.333190E+11 | 0.110768E+11 |
Minimum of Months | 0.112689E+10 | 0.510455E+09 | 0.616438E+09 | 0.137294E+10 | 0.170826E+09 |
Maximum of Months | 0.204964E+10 | 0.888759E+09 | 0.127074E+10 | 0.396371E+10 | 0.206931E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54697674.06 | 27852150.30 | 26845523.76 | 63913824.23 | 81818456.86 |
February | 55013401.75 | 26558898.83 | 28454502.92 | 68848056.16 | 60981824.66 |
March | 71647461.22 | 34553478.34 | 37093982.88 | 98124498.21 | 57617158.72 |
April | 76088476.40 | 34412581.77 | 41675894.63 | 0.119156E+09 | 35530335.61 |
May | 81040954.01 | 35140749.15 | 45900204.86 | 0.154026E+09 | 10710062.23 |
June | 79537936.51 | 31542404.61 | 47995531.90 | 0.156722E+09 | 9052485.10 |
July | 79242127.09 | 28998224.77 | 50243902.32 | 0.155689E+09 | 6754325.82 |
August | 73019170.48 | 25104440.70 | 47914729.78 | 0.142919E+09 | 10120672.34 |
September | 62595064.04 | 21519883.18 | 41075180.86 | 0.116234E+09 | 13971485.78 |
October | 63918682.98 | 26973367.90 | 36945315.08 | 0.112292E+09 | 25801324.39 |
November | 54765240.59 | 27937789.58 | 26827451.01 | 75195549.02 | 53100017.08 |
December | 44556329.54 | 20182945.32 | 24373384.21 | 54284892.48 | 72508839.31 |
Annual Sum or Average | 0.796123E+09 | 0.340777E+09 | 0.455346E+09 | 0.131740E+10 | 0.437967E+09 |
Minimum of Months | 44556329.54 | 20182945.32 | 24373384.21 | 54284892.48 | 6754325.82 |
Maximum of Months | 81040954.01 | 35140749.15 | 50243902.32 | 0.156722E+09 | 81818456.86 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161492E+10 | 0.115171E+10 | 0.463204E+09 | 0.230910E+10 | 0.109806E+10 |
February | 0.132290E+10 | 0.856288E+09 | 0.466612E+09 | 0.194028E+10 | 0.834598E+09 |
March | 0.935059E+09 | 0.421991E+09 | 0.513068E+09 | 0.143090E+10 | 0.784235E+09 |
April | 0.670700E+09 | 0.157160E+09 | 0.513540E+09 | 0.114174E+10 | 0.483636E+09 |
May | 0.529547E+09 | 22504722.32 | 0.507042E+09 | 0.113332E+10 | 0.134824E+09 |
June | 0.506228E+09 | 4718469.90 | 0.501510E+09 | 0.111925E+10 | 0.113881E+09 |
July | 0.547603E+09 | 10064754.93 | 0.537538E+09 | 0.119265E+10 | 80763820.25 |
August | 0.644224E+09 | 77325523.64 | 0.566899E+09 | 0.139286E+10 | 0.134968E+09 |
September | 0.748025E+09 | 0.197135E+09 | 0.550890E+09 | 0.148442E+10 | 0.194153E+09 |
October | 0.119925E+10 | 0.624693E+09 | 0.574556E+09 | 0.217652E+10 | 0.371030E+09 |
November | 0.147689E+10 | 0.101685E+10 | 0.460038E+09 | 0.229256E+10 | 0.737265E+09 |
December | 0.157797E+10 | 0.113321E+10 | 0.444759E+09 | 0.234954E+10 | 0.981010E+09 |
Annual Sum or Average | 0.117733E+11 | 0.567365E+10 | 0.609966E+10 | 0.199631E+11 | 0.594843E+10 |
Minimum of Months | 0.506228E+09 | 4718469.90 | 0.444759E+09 | 0.111925E+10 | 80763820.25 |
Maximum of Months | 0.161492E+10 | 0.115171E+10 | 0.574556E+09 | 0.234954E+10 | 0.109806E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161492E+10 | 0.115171E+10 | 0.463204E+09 | 0.230910E+10 | 0.109806E+10 |
February | 0.132290E+10 | 0.856288E+09 | 0.466612E+09 | 0.194028E+10 | 0.834598E+09 |
March | 0.935059E+09 | 0.421991E+09 | 0.513068E+09 | 0.143090E+10 | 0.784235E+09 |
April | 0.670700E+09 | 0.157160E+09 | 0.513540E+09 | 0.114174E+10 | 0.483636E+09 |
May | 0.529547E+09 | 22504722.32 | 0.507042E+09 | 0.113332E+10 | 0.134824E+09 |
June | 0.506228E+09 | 4718469.90 | 0.501510E+09 | 0.111925E+10 | 0.113881E+09 |
July | 0.547603E+09 | 10064754.93 | 0.537538E+09 | 0.119265E+10 | 80763820.25 |
August | 0.644224E+09 | 77325523.64 | 0.566899E+09 | 0.139286E+10 | 0.134968E+09 |
September | 0.748025E+09 | 0.197135E+09 | 0.550890E+09 | 0.148442E+10 | 0.194153E+09 |
October | 0.119925E+10 | 0.624693E+09 | 0.574556E+09 | 0.217652E+10 | 0.371030E+09 |
November | 0.147689E+10 | 0.101685E+10 | 0.460038E+09 | 0.229256E+10 | 0.737265E+09 |
December | 0.157797E+10 | 0.113321E+10 | 0.444759E+09 | 0.234954E+10 | 0.981010E+09 |
Annual Sum or Average | 0.117733E+11 | 0.567365E+10 | 0.609966E+10 | 0.199631E+11 | 0.594843E+10 |
Minimum of Months | 0.506228E+09 | 4718469.90 | 0.444759E+09 | 0.111925E+10 | 80763820.25 |
Maximum of Months | 0.161492E+10 | 0.115171E+10 | 0.574556E+09 | 0.234954E+10 | 0.109806E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161481E+10 | 0.115164E+10 | 0.463174E+09 | 0.230895E+10 | 0.109799E+10 |
February | 0.132282E+10 | 0.856233E+09 | 0.466583E+09 | 0.194016E+10 | 0.834545E+09 |
March | 0.935000E+09 | 0.421964E+09 | 0.513036E+09 | 0.143081E+10 | 0.784186E+09 |
April | 0.670658E+09 | 0.157150E+09 | 0.513508E+09 | 0.114167E+10 | 0.483605E+09 |
May | 0.529514E+09 | 22503300.15 | 0.507010E+09 | 0.113325E+10 | 0.134815E+09 |
June | 0.506196E+09 | 4718171.72 | 0.501478E+09 | 0.111918E+10 | 0.113873E+09 |
July | 0.547568E+09 | 10064118.89 | 0.537504E+09 | 0.119257E+10 | 80758716.44 |
August | 0.644183E+09 | 77320637.11 | 0.566863E+09 | 0.139278E+10 | 0.134960E+09 |
September | 0.747977E+09 | 0.197122E+09 | 0.550855E+09 | 0.148432E+10 | 0.194141E+09 |
October | 0.119917E+10 | 0.624653E+09 | 0.574520E+09 | 0.217639E+10 | 0.371006E+09 |
November | 0.147680E+10 | 0.101679E+10 | 0.460009E+09 | 0.229242E+10 | 0.737219E+09 |
December | 0.157787E+10 | 0.113314E+10 | 0.444731E+09 | 0.234939E+10 | 0.980948E+09 |
Annual Sum or Average | 0.117726E+11 | 0.567329E+10 | 0.609927E+10 | 0.199619E+11 | 0.594805E+10 |
Minimum of Months | 0.506196E+09 | 4718171.72 | 0.444731E+09 | 0.111918E+10 | 80758716.44 |
Maximum of Months | 0.161481E+10 | 0.115164E+10 | 0.574520E+09 | 0.234939E+10 | 0.109799E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147145E+10 | 0.795675E+09 | 0.675773E+09 | 0.188330E+10 | 0.218085E+10 |
February | 0.150478E+10 | 0.761624E+09 | 0.743157E+09 | 0.201746E+10 | 0.164015E+10 |
March | 0.164202E+10 | 0.726878E+09 | 0.915142E+09 | 0.230918E+10 | 0.153825E+10 |
April | 0.197364E+10 | 0.907910E+09 | 0.106573E+10 | 0.315452E+10 | 0.955876E+09 |
May | 0.169603E+10 | 0.552483E+09 | 0.114355E+10 | 0.333740E+10 | 0.291239E+09 |
June | 0.182332E+10 | 0.639338E+09 | 0.118398E+10 | 0.365302E+10 | 0.254541E+09 |
July | 0.171983E+10 | 0.477051E+09 | 0.124278E+10 | 0.345028E+10 | 0.183353E+09 |
August | 0.173896E+10 | 0.532318E+09 | 0.120664E+10 | 0.346978E+10 | 0.277685E+09 |
September | 0.154963E+10 | 0.531597E+09 | 0.101804E+10 | 0.291445E+10 | 0.377298E+09 |
October | 0.163939E+10 | 0.708359E+09 | 0.931030E+09 | 0.294665E+10 | 0.700191E+09 |
November | 0.135982E+10 | 0.683391E+09 | 0.676434E+09 | 0.199059E+10 | 0.143112E+10 |
December | 0.135163E+10 | 0.718779E+09 | 0.632856E+09 | 0.182599E+10 | 0.189969E+10 |
Annual Sum or Average | 0.194705E+11 | 0.803540E+10 | 0.114351E+11 | 0.329526E+11 | 0.117302E+11 |
Minimum of Months | 0.135163E+10 | 0.477051E+09 | 0.632856E+09 | 0.182599E+10 | 0.183353E+09 |
Maximum of Months | 0.197364E+10 | 0.907910E+09 | 0.124278E+10 | 0.365302E+10 | 0.218085E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58179554.07 | 31460172.89 | 26719381.17 | 74463836.42 | 86228767.22 |
February | 59497511.12 | 30113829.44 | 29383681.68 | 79768284.73 | 64850025.32 |
March | 64923815.41 | 28740022.43 | 36183792.98 | 91302443.16 | 60820952.48 |
April | 78035874.09 | 35897815.02 | 42138059.07 | 0.124726E+09 | 37794437.01 |
May | 67059315.84 | 21844593.16 | 45214722.68 | 0.131957E+09 | 11515322.42 |
June | 72092132.19 | 25278777.36 | 46813354.82 | 0.144437E+09 | 10064314.56 |
July | 68000196.35 | 18862099.47 | 49138096.88 | 0.136421E+09 | 7249592.05 |
August | 68756798.92 | 21047292.51 | 47709506.41 | 0.137192E+09 | 10979407.83 |
September | 61270976.14 | 21018785.90 | 40252190.24 | 0.115234E+09 | 14918016.48 |
October | 64819802.43 | 28007805.59 | 36811996.84 | 0.116508E+09 | 27684905.15 |
November | 53766094.55 | 27020571.99 | 26745522.56 | 78705946.41 | 56585084.23 |
December | 53442281.79 | 28419778.39 | 25022503.40 | 72197667.48 | 75112138.76 |
Annual Sum or Average | 0.769844E+09 | 0.317712E+09 | 0.452133E+09 | 0.130291E+10 | 0.463803E+09 |
Minimum of Months | 53442281.79 | 18862099.47 | 25022503.40 | 72197667.48 | 7249592.05 |
Maximum of Months | 78035874.09 | 35897815.02 | 49138096.88 | 0.144437E+09 | 86228767.22 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.838177E+09 | 0.00 | 0.838177E+09 | 0.596795E+09 | 0.338760E+10 |
February | 0.893151E+09 | 0.00 | 0.893151E+09 | 0.736663E+09 | 0.255933E+10 |
March | 0.114715E+10 | 0.00 | 0.114715E+10 | 0.118436E+10 | 0.242549E+10 |
April | 0.131021E+10 | 5377575.54 | 0.130484E+10 | 0.180689E+10 | 0.146326E+10 |
May | 0.153354E+10 | 56093230.24 | 0.147744E+10 | 0.320477E+10 | 0.436589E+09 |
June | 0.168770E+10 | 0.116860E+09 | 0.157084E+10 | 0.367856E+10 | 0.364312E+09 |
July | 0.169240E+10 | 64477283.85 | 0.162792E+10 | 0.365610E+10 | 0.254437E+09 |
August | 0.151557E+10 | 11920180.05 | 0.150365E+10 | 0.330893E+10 | 0.356860E+09 |
September | 0.126689E+10 | 97575.10 | 0.126679E+10 | 0.252915E+10 | 0.494654E+09 |
October | 0.113759E+10 | 0.00 | 0.113759E+10 | 0.210063E+10 | 0.969141E+09 |
November | 0.835757E+09 | 0.00 | 0.835757E+09 | 0.898731E+09 | 0.210967E+10 |
December | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.647048E+09 | 0.289869E+10 |
Annual Sum or Average | 0.146373E+11 | 0.254826E+09 | 0.143825E+11 | 0.243486E+11 | 0.177200E+11 |
Minimum of Months | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.596795E+09 | 0.254437E+09 |
Maximum of Months | 0.169240E+10 | 0.116860E+09 | 0.162792E+10 | 0.367856E+10 | 0.338760E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143810E+10 | 0.732287E+09 | 0.705815E+09 | 0.168039E+10 | 0.206116E+10 |
February | 0.144640E+10 | 0.698285E+09 | 0.748118E+09 | 0.179455E+10 | 0.156448E+10 |
March | 0.188374E+10 | 0.908478E+09 | 0.975265E+09 | 0.254409E+10 | 0.150134E+10 |
April | 0.200050E+10 | 0.904773E+09 | 0.109573E+10 | 0.309092E+10 | 0.941768E+09 |
May | 0.213071E+10 | 0.923918E+09 | 0.120680E+10 | 0.401462E+10 | 0.290807E+09 |
June | 0.209120E+10 | 0.829311E+09 | 0.126189E+10 | 0.409564E+10 | 0.241729E+09 |
July | 0.208342E+10 | 0.762419E+09 | 0.132100E+10 | 0.408551E+10 | 0.166230E+09 |
August | 0.191981E+10 | 0.660044E+09 | 0.125976E+10 | 0.376742E+10 | 0.236173E+09 |
September | 0.164574E+10 | 0.565799E+09 | 0.107994E+10 | 0.306385E+10 | 0.322636E+09 |
October | 0.168054E+10 | 0.709182E+09 | 0.971357E+09 | 0.295925E+10 | 0.619627E+09 |
November | 0.143988E+10 | 0.734539E+09 | 0.705340E+09 | 0.198921E+10 | 0.129993E+10 |
December | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.143537E+10 | 0.180733E+10 |
Annual Sum or Average | 0.209315E+11 | 0.895968E+10 | 0.119718E+11 | 0.345208E+11 | 0.110532E+11 |
Minimum of Months | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.143537E+10 | 0.166230E+09 |
Maximum of Months | 0.213071E+10 | 0.923918E+09 | 0.132100E+10 | 0.409564E+10 | 0.206116E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.484483E+10 | 0.345521E+10 | 0.138963E+10 | 0.686035E+10 | 0.312626E+10 |
February | 0.396877E+10 | 0.256892E+10 | 0.139985E+10 | 0.574789E+10 | 0.241911E+10 |
March | 0.280522E+10 | 0.126600E+10 | 0.153922E+10 | 0.419139E+10 | 0.238367E+10 |
April | 0.201212E+10 | 0.471490E+09 | 0.154063E+10 | 0.334592E+10 | 0.151242E+10 |
May | 0.158865E+10 | 67515546.51 | 0.152114E+10 | 0.335786E+10 | 0.450193E+09 |
June | 0.151869E+10 | 14155698.93 | 0.150454E+10 | 0.333173E+10 | 0.375430E+09 |
July | 0.164282E+10 | 30194881.76 | 0.161263E+10 | 0.357233E+10 | 0.249871E+09 |
August | 0.193269E+10 | 0.231981E+09 | 0.170071E+10 | 0.420711E+10 | 0.373135E+09 |
September | 0.224410E+10 | 0.591416E+09 | 0.165269E+10 | 0.446482E+10 | 0.523909E+09 |
October | 0.359780E+10 | 0.187412E+10 | 0.172369E+10 | 0.654346E+10 | 0.100871E+10 |
November | 0.443075E+10 | 0.305061E+10 | 0.138013E+10 | 0.686661E+10 | 0.203620E+10 |
December | 0.473399E+10 | 0.339970E+10 | 0.133429E+10 | 0.700863E+10 | 0.276932E+10 |
Annual Sum or Average | 0.353204E+11 | 0.170213E+11 | 0.182991E+11 | 0.594981E+11 | 0.172282E+11 |
Minimum of Months | 0.151869E+10 | 14155698.93 | 0.133429E+10 | 0.333173E+10 | 0.249871E+09 |
Maximum of Months | 0.484483E+10 | 0.345521E+10 | 0.172369E+10 | 0.700863E+10 | 0.312626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152965E+10 | 0.827149E+09 | 0.702499E+09 | 0.195170E+10 | 0.218214E+10 |
February | 0.156430E+10 | 0.791751E+09 | 0.772548E+09 | 0.207651E+10 | 0.166750E+10 |
March | 0.170697E+10 | 0.755631E+09 | 0.951335E+09 | 0.236489E+10 | 0.159219E+10 |
April | 0.205171E+10 | 0.943823E+09 | 0.110788E+10 | 0.323615E+10 | 0.100498E+10 |
May | 0.176311E+10 | 0.574337E+09 | 0.118877E+10 | 0.344002E+10 | 0.320199E+09 |
June | 0.189543E+10 | 0.664628E+09 | 0.123080E+10 | 0.377540E+10 | 0.271077E+09 |
July | 0.178785E+10 | 0.495921E+09 | 0.129193E+10 | 0.357870E+10 | 0.185006E+09 |
August | 0.180774E+10 | 0.553374E+09 | 0.125437E+10 | 0.361825E+10 | 0.260059E+09 |
September | 0.161093E+10 | 0.552625E+09 | 0.105830E+10 | 0.304019E+10 | 0.349767E+09 |
October | 0.170423E+10 | 0.736379E+09 | 0.967852E+09 | 0.307532E+10 | 0.670131E+09 |
November | 0.141361E+10 | 0.710423E+09 | 0.703186E+09 | 0.208385E+10 | 0.139197E+10 |
December | 0.140510E+10 | 0.747211E+09 | 0.657885E+09 | 0.190417E+10 | 0.187119E+10 |
Annual Sum or Average | 0.202406E+11 | 0.835325E+10 | 0.118874E+11 | 0.341451E+11 | 0.117662E+11 |
Minimum of Months | 0.140510E+10 | 0.495921E+09 | 0.657885E+09 | 0.190417E+10 | 0.185006E+09 |
Maximum of Months | 0.205171E+10 | 0.943823E+09 | 0.129193E+10 | 0.377540E+10 | 0.218214E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.02 | 1174.35 | 312.94 | 0.00 | 312.94 | 0.00 | 0.00 |
February | 317.76 | 977.73 | 369.19 | 0.00 | 369.19 | 0.00 | 0.00 |
March | 451.85 | 846.31 | 428.30 | 0.00 | 428.30 | 0.00 | 0.00 |
April | 700.55 | 534.07 | 505.48 | 2.07 | 503.41 | 0.00 | 0.00 |
May | 1186.56 | 160.22 | 572.56 | 20.94 | 551.61 | 0.00 | 0.00 |
June | 1406.28 | 139.59 | 651.12 | 45.08 | 606.03 | 0.00 | 0.00 |
July | 1350.76 | 95.61 | 631.87 | 24.07 | 607.80 | 0.00 | 0.00 |
August | 1225.75 | 130.02 | 565.85 | 4.45 | 561.40 | 0.00 | 0.00 |
September | 968.20 | 181.37 | 488.77 | 0.04 | 488.73 | 0.00 | 0.00 |
October | 783.72 | 339.20 | 424.73 | 0.00 | 424.73 | 0.00 | 0.00 |
November | 361.26 | 746.20 | 322.44 | 0.00 | 322.44 | 0.00 | 0.00 |
December | 255.06 | 997.47 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Annual Sum or Average | 773.15 | 524.53 | 464.15 | 8.08 | 456.07 | 0.00 | 0.00 |
Minimum of Months | 237.02 | 95.61 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Maximum of Months | 1406.28 | 1174.35 | 651.12 | 45.08 | 607.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 643.13 | 718.31 | 536.93 | 273.40 | 263.52 | 0.00 | 0.00 |
February | 754.86 | 602.61 | 597.88 | 288.64 | 309.24 | 0.00 | 0.00 |
March | 955.72 | 528.50 | 703.31 | 339.19 | 364.12 | 0.00 | 0.00 |
April | 1192.69 | 346.89 | 771.80 | 349.06 | 422.74 | 0.00 | 0.00 |
May | 1490.33 | 106.75 | 795.52 | 344.95 | 450.57 | 0.00 | 0.00 |
June | 1570.31 | 92.82 | 806.79 | 319.95 | 486.84 | 0.00 | 0.00 |
July | 1514.68 | 62.40 | 777.86 | 284.65 | 493.21 | 0.00 | 0.00 |
August | 1398.78 | 86.26 | 716.77 | 246.43 | 470.34 | 0.00 | 0.00 |
September | 1176.02 | 118.62 | 634.93 | 218.29 | 416.64 | 0.00 | 0.00 |
October | 1102.91 | 218.31 | 627.44 | 264.78 | 362.66 | 0.00 | 0.00 |
November | 778.70 | 465.75 | 555.51 | 283.39 | 272.12 | 0.00 | 0.00 |
December | 548.08 | 627.19 | 437.38 | 198.12 | 239.25 | 0.00 | 0.00 |
Annual Sum or Average | 1095.70 | 329.79 | 663.73 | 284.11 | 379.62 | 0.00 | 0.00 |
Minimum of Months | 548.08 | 62.40 | 437.38 | 198.12 | 239.25 | 0.00 | 0.00 |
Maximum of Months | 1570.31 | 718.31 | 806.79 | 349.06 | 493.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2579.15 | 1089.16 | 1808.85 | 1290.03 | 518.83 | 0.00 | 0.00 |
February | 2392.01 | 931.30 | 1640.53 | 1061.89 | 578.64 | 0.00 | 0.00 |
March | 1573.03 | 834.61 | 1047.35 | 472.67 | 574.68 | 0.00 | 0.00 |
April | 1291.70 | 552.96 | 776.28 | 181.90 | 594.38 | 0.00 | 0.00 |
May | 1243.98 | 164.49 | 593.14 | 25.21 | 567.93 | 0.00 | 0.00 |
June | 1273.35 | 143.52 | 585.92 | 5.46 | 580.45 | 0.00 | 0.00 |
July | 1319.99 | 93.20 | 613.36 | 11.27 | 602.09 | 0.00 | 0.00 |
August | 1560.39 | 135.69 | 721.58 | 86.61 | 634.97 | 0.00 | 0.00 |
September | 1714.27 | 192.43 | 865.78 | 228.17 | 637.61 | 0.00 | 0.00 |
October | 2438.32 | 356.70 | 1343.27 | 699.71 | 643.55 | 0.00 | 0.00 |
November | 2660.97 | 732.27 | 1709.39 | 1176.93 | 532.46 | 0.00 | 0.00 |
December | 2630.76 | 961.69 | 1767.47 | 1269.30 | 498.17 | 0.00 | 0.00 |
Annual Sum or Average | 1887.40 | 513.46 | 1120.00 | 539.74 | 580.26 | 0.00 | 0.00 |
Minimum of Months | 1243.98 | 93.20 | 585.92 | 5.46 | 498.17 | 0.00 | 0.00 |
Maximum of Months | 2660.97 | 1089.16 | 1808.85 | 1290.03 | 643.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 738.45 | 758.19 | 571.10 | 308.82 | 262.28 | 0.00 | 0.00 |
February | 867.55 | 638.67 | 646.62 | 327.28 | 319.34 | 0.00 | 0.00 |
March | 888.41 | 555.85 | 637.31 | 282.12 | 355.19 | 0.00 | 0.00 |
April | 1250.27 | 366.68 | 791.55 | 364.13 | 427.42 | 0.00 | 0.00 |
May | 1278.70 | 116.69 | 658.27 | 214.43 | 443.84 | 0.00 | 0.00 |
June | 1448.85 | 103.06 | 731.26 | 256.42 | 474.85 | 0.00 | 0.00 |
July | 1327.85 | 68.63 | 667.51 | 185.16 | 482.35 | 0.00 | 0.00 |
August | 1344.91 | 94.43 | 674.93 | 206.61 | 468.33 | 0.00 | 0.00 |
September | 1169.49 | 127.72 | 621.50 | 213.20 | 408.30 | 0.00 | 0.00 |
October | 1148.20 | 235.30 | 636.29 | 274.93 | 361.35 | 0.00 | 0.00 |
November | 813.43 | 494.53 | 545.37 | 274.08 | 271.29 | 0.00 | 0.00 |
December | 720.15 | 646.67 | 524.60 | 278.98 | 245.63 | 0.00 | 0.00 |
Annual Sum or Average | 1083.83 | 349.02 | 641.83 | 264.88 | 376.95 | 0.00 | 0.00 |
Minimum of Months | 720.15 | 68.63 | 524.60 | 185.16 | 245.63 | 0.00 | 0.00 |
Maximum of Months | 1448.85 | 758.19 | 791.55 | 364.13 | 482.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.20 | 1279.67 | 312.93 | 0.00 | 312.93 | 0.00 | 0.00 |
February | 317.32 | 1048.38 | 369.19 | 0.00 | 369.19 | 0.00 | 0.00 |
March | 465.39 | 877.83 | 428.29 | 0.00 | 428.29 | 0.00 | 0.00 |
April | 724.66 | 532.81 | 505.47 | 2.07 | 503.40 | 0.00 | 0.00 |
May | 1216.79 | 144.24 | 572.54 | 20.94 | 551.60 | 0.00 | 0.00 |
June | 1434.36 | 128.19 | 651.11 | 45.08 | 606.02 | 0.00 | 0.00 |
July | 1373.13 | 90.52 | 631.86 | 24.07 | 607.78 | 0.00 | 0.00 |
August | 1230.02 | 139.77 | 565.84 | 4.45 | 561.39 | 0.00 | 0.00 |
September | 972.22 | 202.38 | 488.76 | 0.04 | 488.72 | 0.00 | 0.00 |
October | 778.67 | 378.83 | 424.72 | 0.00 | 424.72 | 0.00 | 0.00 |
November | 341.73 | 844.15 | 322.43 | 0.00 | 322.43 | 0.00 | 0.00 |
December | 238.61 | 1112.13 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Annual Sum or Average | 779.28 | 562.45 | 464.14 | 8.08 | 456.06 | 0.00 | 0.00 |
Minimum of Months | 225.20 | 90.52 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Maximum of Months | 1434.36 | 1279.67 | 651.11 | 45.08 | 607.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 627.38 | 803.14 | 536.92 | 273.40 | 263.52 | 0.00 | 0.00 |
February | 748.23 | 662.74 | 597.88 | 288.64 | 309.24 | 0.00 | 0.00 |
March | 963.20 | 565.58 | 703.30 | 339.18 | 364.12 | 0.00 | 0.00 |
April | 1208.64 | 360.39 | 771.79 | 349.06 | 422.73 | 0.00 | 0.00 |
May | 1511.94 | 105.13 | 795.51 | 344.94 | 450.56 | 0.00 | 0.00 |
June | 1589.67 | 91.82 | 806.78 | 319.94 | 486.83 | 0.00 | 0.00 |
July | 1528.25 | 66.30 | 777.85 | 284.65 | 493.20 | 0.00 | 0.00 |
August | 1402.91 | 99.35 | 716.76 | 246.43 | 470.34 | 0.00 | 0.00 |
September | 1179.00 | 141.72 | 634.92 | 218.28 | 416.64 | 0.00 | 0.00 |
October | 1102.27 | 253.27 | 627.43 | 264.77 | 362.66 | 0.00 | 0.00 |
November | 762.73 | 538.61 | 555.50 | 283.38 | 272.12 | 0.00 | 0.00 |
December | 532.87 | 711.75 | 437.37 | 198.12 | 239.25 | 0.00 | 0.00 |
Annual Sum or Average | 1098.31 | 365.13 | 663.72 | 284.10 | 379.62 | 0.00 | 0.00 |
Minimum of Months | 532.87 | 66.30 | 437.37 | 198.12 | 239.25 | 0.00 | 0.00 |
Maximum of Months | 1589.67 | 803.14 | 806.78 | 349.06 | 493.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2586.30 | 1229.88 | 1808.78 | 1289.97 | 518.81 | 0.00 | 0.00 |
February | 2406.05 | 1034.95 | 1640.47 | 1061.84 | 578.62 | 0.00 | 0.00 |
March | 1602.68 | 878.38 | 1047.31 | 472.65 | 574.66 | 0.00 | 0.00 |
April | 1321.43 | 559.75 | 776.26 | 181.89 | 594.36 | 0.00 | 0.00 |
May | 1269.38 | 151.01 | 593.12 | 25.21 | 567.91 | 0.00 | 0.00 |
June | 1295.40 | 131.80 | 585.90 | 5.46 | 580.44 | 0.00 | 0.00 |
July | 1335.83 | 90.46 | 613.34 | 11.27 | 602.07 | 0.00 | 0.00 |
August | 1560.07 | 151.17 | 721.56 | 86.61 | 634.95 | 0.00 | 0.00 |
September | 1718.04 | 224.71 | 865.75 | 228.16 | 637.59 | 0.00 | 0.00 |
October | 2437.81 | 415.57 | 1343.22 | 699.69 | 643.53 | 0.00 | 0.00 |
November | 2653.37 | 853.30 | 1709.33 | 1176.89 | 532.44 | 0.00 | 0.00 |
December | 2631.60 | 1098.78 | 1767.40 | 1269.25 | 498.15 | 0.00 | 0.00 |
Annual Sum or Average | 1899.04 | 565.86 | 1119.96 | 539.72 | 580.24 | 0.00 | 0.00 |
Minimum of Months | 1269.38 | 90.46 | 585.90 | 5.46 | 498.15 | 0.00 | 0.00 |
Maximum of Months | 2653.37 | 1229.88 | 1808.78 | 1289.97 | 643.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.95 | 846.43 | 571.10 | 308.82 | 262.28 | 0.00 | 0.00 |
February | 866.91 | 704.78 | 646.61 | 327.27 | 319.34 | 0.00 | 0.00 |
March | 896.24 | 597.02 | 637.30 | 282.12 | 355.18 | 0.00 | 0.00 |
April | 1265.14 | 383.36 | 791.54 | 364.12 | 427.42 | 0.00 | 0.00 |
May | 1295.31 | 113.04 | 658.26 | 214.43 | 443.83 | 0.00 | 0.00 |
June | 1465.07 | 102.09 | 731.25 | 256.41 | 474.84 | 0.00 | 0.00 |
July | 1339.12 | 71.16 | 667.50 | 185.15 | 482.35 | 0.00 | 0.00 |
August | 1346.69 | 107.78 | 674.92 | 206.60 | 468.32 | 0.00 | 0.00 |
September | 1168.86 | 151.32 | 621.49 | 213.20 | 408.29 | 0.00 | 0.00 |
October | 1143.65 | 271.76 | 636.28 | 274.93 | 361.35 | 0.00 | 0.00 |
November | 798.34 | 573.96 | 545.37 | 274.08 | 271.29 | 0.00 | 0.00 |
December | 708.70 | 737.31 | 524.60 | 278.97 | 245.62 | 0.00 | 0.00 |
Annual Sum or Average | 1086.24 | 386.67 | 641.82 | 264.88 | 376.94 | 0.00 | 0.00 |
Minimum of Months | 708.70 | 71.16 | 524.60 | 185.15 | 245.62 | 0.00 | 0.00 |
Maximum of Months | 1465.07 | 846.43 | 791.54 | 364.12 | 482.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.82 | 1264.79 | 312.94 | 0.00 | 312.94 | 0.00 | 0.00 |
February | 304.51 | 1057.92 | 369.19 | 0.00 | 369.19 | 0.00 | 0.00 |
March | 442.19 | 905.57 | 428.30 | 0.00 | 428.30 | 0.00 | 0.00 |
April | 697.10 | 564.53 | 505.48 | 2.07 | 503.41 | 0.00 | 0.00 |
May | 1196.52 | 163.00 | 572.56 | 20.94 | 551.61 | 0.00 | 0.00 |
June | 1419.20 | 140.55 | 651.12 | 45.08 | 606.03 | 0.00 | 0.00 |
July | 1365.03 | 95.00 | 631.87 | 24.07 | 607.80 | 0.00 | 0.00 |
August | 1235.41 | 133.24 | 565.85 | 4.45 | 561.40 | 0.00 | 0.00 |
September | 975.75 | 190.84 | 488.77 | 0.04 | 488.73 | 0.00 | 0.00 |
October | 784.28 | 361.84 | 424.73 | 0.00 | 424.73 | 0.00 | 0.00 |
November | 346.73 | 813.92 | 322.44 | 0.00 | 322.44 | 0.00 | 0.00 |
December | 241.58 | 1082.25 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Annual Sum or Average | 772.09 | 561.90 | 464.15 | 8.08 | 456.07 | 0.00 | 0.00 |
Minimum of Months | 222.82 | 95.00 | 290.91 | 0.00 | 290.91 | 0.00 | 0.00 |
Maximum of Months | 1419.20 | 1264.79 | 651.12 | 45.08 | 607.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 627.39 | 769.55 | 536.93 | 273.40 | 263.52 | 0.00 | 0.00 |
February | 741.79 | 646.69 | 597.88 | 288.64 | 309.24 | 0.00 | 0.00 |
March | 949.85 | 560.54 | 703.31 | 339.19 | 364.12 | 0.00 | 0.00 |
April | 1192.48 | 363.34 | 771.80 | 349.06 | 422.74 | 0.00 | 0.00 |
May | 1498.89 | 108.57 | 795.52 | 344.95 | 450.57 | 0.00 | 0.00 |
June | 1580.11 | 93.26 | 806.79 | 319.95 | 486.84 | 0.00 | 0.00 |
July | 1525.35 | 62.06 | 777.86 | 284.65 | 493.21 | 0.00 | 0.00 |
August | 1406.59 | 88.18 | 716.77 | 246.43 | 470.34 | 0.00 | 0.00 |
September | 1182.04 | 124.47 | 634.93 | 218.29 | 416.64 | 0.00 | 0.00 |
October | 1104.86 | 231.34 | 627.44 | 264.78 | 362.66 | 0.00 | 0.00 |
November | 767.44 | 501.52 | 555.51 | 283.39 | 272.12 | 0.00 | 0.00 |
December | 535.91 | 674.78 | 437.38 | 198.12 | 239.25 | 0.00 | 0.00 |
Annual Sum or Average | 1094.65 | 350.49 | 663.73 | 284.11 | 379.62 | 0.00 | 0.00 |
Minimum of Months | 535.91 | 62.06 | 437.38 | 198.12 | 239.25 | 0.00 | 0.00 |
Maximum of Months | 1580.11 | 769.55 | 806.79 | 349.06 | 493.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2561.36 | 1167.21 | 1808.85 | 1290.03 | 518.83 | 0.00 | 0.00 |
February | 2375.95 | 999.96 | 1640.53 | 1061.89 | 578.64 | 0.00 | 0.00 |
March | 1564.89 | 889.96 | 1047.35 | 472.67 | 574.68 | 0.00 | 0.00 |
April | 1290.87 | 583.50 | 776.28 | 181.90 | 594.38 | 0.00 | 0.00 |
May | 1253.68 | 168.08 | 593.14 | 25.21 | 567.93 | 0.00 | 0.00 |
June | 1285.39 | 144.84 | 585.92 | 5.46 | 580.45 | 0.00 | 0.00 |
July | 1333.75 | 93.29 | 613.36 | 11.27 | 602.09 | 0.00 | 0.00 |
August | 1570.76 | 139.31 | 721.58 | 86.61 | 634.97 | 0.00 | 0.00 |
September | 1722.54 | 202.13 | 865.78 | 228.17 | 637.61 | 0.00 | 0.00 |
October | 2443.05 | 376.61 | 1343.27 | 699.71 | 643.55 | 0.00 | 0.00 |
November | 2649.15 | 785.57 | 1709.39 | 1176.93 | 532.46 | 0.00 | 0.00 |
December | 2616.72 | 1033.95 | 1767.47 | 1269.30 | 498.17 | 0.00 | 0.00 |
Annual Sum or Average | 1886.67 | 546.30 | 1120.00 | 539.74 | 580.26 | 0.00 | 0.00 |
Minimum of Months | 1253.68 | 93.29 | 585.92 | 5.46 | 498.17 | 0.00 | 0.00 |
Maximum of Months | 2649.15 | 1167.21 | 1808.85 | 1290.03 | 643.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 728.68 | 814.72 | 571.10 | 308.82 | 262.28 | 0.00 | 0.00 |
February | 858.34 | 689.28 | 646.62 | 327.28 | 319.34 | 0.00 | 0.00 |
March | 882.95 | 594.45 | 637.31 | 282.12 | 355.19 | 0.00 | 0.00 |
April | 1248.51 | 387.72 | 791.55 | 364.13 | 427.42 | 0.00 | 0.00 |
May | 1284.36 | 119.55 | 658.27 | 214.43 | 443.84 | 0.00 | 0.00 |
June | 1456.56 | 104.58 | 731.26 | 256.42 | 474.85 | 0.00 | 0.00 |
July | 1336.13 | 69.07 | 667.51 | 185.16 | 482.35 | 0.00 | 0.00 |
August | 1350.90 | 97.10 | 674.93 | 206.61 | 468.33 | 0.00 | 0.00 |
September | 1172.91 | 134.94 | 621.50 | 213.20 | 408.30 | 0.00 | 0.00 |
October | 1148.19 | 250.20 | 636.29 | 274.93 | 361.35 | 0.00 | 0.00 |
November | 803.96 | 537.02 | 545.37 | 274.08 | 271.29 | 0.00 | 0.00 |
December | 710.93 | 698.62 | 524.60 | 278.98 | 245.63 | 0.00 | 0.00 |
Annual Sum or Average | 1082.74 | 373.10 | 641.83 | 264.88 | 376.95 | 0.00 | 0.00 |
Minimum of Months | 710.93 | 69.07 | 524.60 | 185.16 | 245.63 | 0.00 | 0.00 |
Maximum of Months | 1456.56 | 814.72 | 791.55 | 364.13 | 482.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.634832E+09 | 0.314538E+10 | 0.838177E+09 | 0.00 | 0.838177E+09 | 0.00 | 0.00 |
February | 0.768725E+09 | 0.236534E+10 | 0.893151E+09 | 0.00 | 0.893151E+09 | 0.00 | 0.00 |
March | 0.121024E+10 | 0.226676E+10 | 0.114715E+10 | 0.00 | 0.114715E+10 | 0.00 | 0.00 |
April | 0.181582E+10 | 0.138431E+10 | 0.131021E+10 | 5377575.54 | 0.130484E+10 | 0.00 | 0.00 |
May | 0.317809E+10 | 0.429138E+09 | 0.153354E+10 | 56093230.24 | 0.147744E+10 | 0.00 | 0.00 |
June | 0.364507E+10 | 0.361823E+09 | 0.168770E+10 | 0.116860E+09 | 0.157084E+10 | 0.00 | 0.00 |
July | 0.361788E+10 | 0.256080E+09 | 0.169240E+10 | 64477283.85 | 0.162792E+10 | 0.00 | 0.00 |
August | 0.328304E+10 | 0.348250E+09 | 0.151557E+10 | 11920180.05 | 0.150365E+10 | 0.00 | 0.00 |
September | 0.250957E+10 | 0.470098E+09 | 0.126689E+10 | 97575.10 | 0.126679E+10 | 0.00 | 0.00 |
October | 0.209911E+10 | 0.908514E+09 | 0.113759E+10 | 0.00 | 0.113759E+10 | 0.00 | 0.00 |
November | 0.936383E+09 | 0.193414E+10 | 0.835757E+09 | 0.00 | 0.835757E+09 | 0.00 | 0.00 |
December | 0.683156E+09 | 0.267162E+10 | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243819E+11 | 0.165414E+11 | 0.146373E+11 | 0.254826E+09 | 0.143825E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634832E+09 | 0.256080E+09 | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364507E+10 | 0.314538E+10 | 0.169240E+10 | 0.116860E+09 | 0.162792E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.172255E+10 | 0.192391E+10 | 0.143810E+10 | 0.732287E+09 | 0.705815E+09 | 0.00 | 0.00 |
February | 0.182616E+10 | 0.145784E+10 | 0.144640E+10 | 0.698285E+09 | 0.748118E+09 | 0.00 | 0.00 |
March | 0.255981E+10 | 0.141554E+10 | 0.188374E+10 | 0.908478E+09 | 0.975265E+09 | 0.00 | 0.00 |
April | 0.309145E+10 | 0.899129E+09 | 0.200050E+10 | 0.904773E+09 | 0.109573E+10 | 0.00 | 0.00 |
May | 0.399169E+10 | 0.285925E+09 | 0.213071E+10 | 0.923918E+09 | 0.120680E+10 | 0.00 | 0.00 |
June | 0.407024E+10 | 0.240586E+09 | 0.209120E+10 | 0.829311E+09 | 0.126189E+10 | 0.00 | 0.00 |
July | 0.405691E+10 | 0.167130E+09 | 0.208342E+10 | 0.762419E+09 | 0.132100E+10 | 0.00 | 0.00 |
August | 0.374650E+10 | 0.231043E+09 | 0.191981E+10 | 0.660044E+09 | 0.125976E+10 | 0.00 | 0.00 |
September | 0.304823E+10 | 0.307451E+09 | 0.164574E+10 | 0.565799E+09 | 0.107994E+10 | 0.00 | 0.00 |
October | 0.295404E+10 | 0.584724E+09 | 0.168054E+10 | 0.709182E+09 | 0.971357E+09 | 0.00 | 0.00 |
November | 0.201840E+10 | 0.120722E+10 | 0.143988E+10 | 0.734539E+09 | 0.705340E+09 | 0.00 | 0.00 |
December | 0.146799E+10 | 0.167986E+10 | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345540E+11 | 0.104004E+11 | 0.209315E+11 | 0.895968E+10 | 0.119718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146799E+10 | 0.167130E+09 | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.00 | 0.00 |
Maximum of Months | 0.407024E+10 | 0.192391E+10 | 0.213071E+10 | 0.923918E+09 | 0.132100E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.690800E+10 | 0.291721E+10 | 0.484483E+10 | 0.345521E+10 | 0.138963E+10 | 0.00 | 0.00 |
February | 0.578674E+10 | 0.225301E+10 | 0.396877E+10 | 0.256892E+10 | 0.139985E+10 | 0.00 | 0.00 |
March | 0.421321E+10 | 0.223542E+10 | 0.280522E+10 | 0.126600E+10 | 0.153922E+10 | 0.00 | 0.00 |
April | 0.334810E+10 | 0.143327E+10 | 0.201212E+10 | 0.471490E+09 | 0.154063E+10 | 0.00 | 0.00 |
May | 0.333187E+10 | 0.440559E+09 | 0.158865E+10 | 67515546.51 | 0.152114E+10 | 0.00 | 0.00 |
June | 0.330053E+10 | 0.372000E+09 | 0.151869E+10 | 14155698.93 | 0.150454E+10 | 0.00 | 0.00 |
July | 0.353545E+10 | 0.249626E+09 | 0.164282E+10 | 30194881.76 | 0.161263E+10 | 0.00 | 0.00 |
August | 0.417934E+10 | 0.363427E+09 | 0.193269E+10 | 0.231981E+09 | 0.170071E+10 | 0.00 | 0.00 |
September | 0.444339E+10 | 0.498788E+09 | 0.224410E+10 | 0.591416E+09 | 0.165269E+10 | 0.00 | 0.00 |
October | 0.653081E+10 | 0.955373E+09 | 0.359780E+10 | 0.187412E+10 | 0.172369E+10 | 0.00 | 0.00 |
November | 0.689723E+10 | 0.189805E+10 | 0.443075E+10 | 0.305061E+10 | 0.138013E+10 | 0.00 | 0.00 |
December | 0.704622E+10 | 0.257578E+10 | 0.473399E+10 | 0.339970E+10 | 0.133429E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595209E+11 | 0.161925E+11 | 0.353204E+11 | 0.170213E+11 | 0.182991E+11 | 0.00 | 0.00 |
Minimum of Months | 0.330053E+10 | 0.249626E+09 | 0.151869E+10 | 14155698.93 | 0.133429E+10 | 0.00 | 0.00 |
Maximum of Months | 0.704622E+10 | 0.291721E+10 | 0.484483E+10 | 0.345521E+10 | 0.172369E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197787E+10 | 0.203073E+10 | 0.152965E+10 | 0.827149E+09 | 0.702499E+09 | 0.00 | 0.00 |
February | 0.209878E+10 | 0.154506E+10 | 0.156430E+10 | 0.791751E+09 | 0.772548E+09 | 0.00 | 0.00 |
March | 0.237952E+10 | 0.148880E+10 | 0.170697E+10 | 0.755631E+09 | 0.951335E+09 | 0.00 | 0.00 |
April | 0.324071E+10 | 0.950431E+09 | 0.205171E+10 | 0.943823E+09 | 0.110788E+10 | 0.00 | 0.00 |
May | 0.342486E+10 | 0.312549E+09 | 0.176311E+10 | 0.574337E+09 | 0.118877E+10 | 0.00 | 0.00 |
June | 0.375542E+10 | 0.267137E+09 | 0.189543E+10 | 0.664628E+09 | 0.123080E+10 | 0.00 | 0.00 |
July | 0.355651E+10 | 0.183823E+09 | 0.178785E+10 | 0.495921E+09 | 0.129193E+10 | 0.00 | 0.00 |
August | 0.360221E+10 | 0.252926E+09 | 0.180774E+10 | 0.553374E+09 | 0.125437E+10 | 0.00 | 0.00 |
September | 0.303131E+10 | 0.331048E+09 | 0.161093E+10 | 0.552625E+09 | 0.105830E+10 | 0.00 | 0.00 |
October | 0.307533E+10 | 0.630230E+09 | 0.170423E+10 | 0.736379E+09 | 0.967852E+09 | 0.00 | 0.00 |
November | 0.210842E+10 | 0.128183E+10 | 0.141361E+10 | 0.710423E+09 | 0.703186E+09 | 0.00 | 0.00 |
December | 0.192884E+10 | 0.173204E+10 | 0.140510E+10 | 0.747211E+09 | 0.657885E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341798E+11 | 0.110066E+11 | 0.202406E+11 | 0.835325E+10 | 0.118874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192884E+10 | 0.183823E+09 | 0.140510E+10 | 0.495921E+09 | 0.657885E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375542E+10 | 0.203073E+10 | 0.205171E+10 | 0.943823E+09 | 0.129193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.603172E+09 | 0.342747E+10 | 0.838161E+09 | 0.00 | 0.838161E+09 | 0.00 | 0.00 |
February | 0.767652E+09 | 0.253625E+10 | 0.893134E+09 | 0.00 | 0.893134E+09 | 0.00 | 0.00 |
March | 0.124650E+10 | 0.235118E+10 | 0.114713E+10 | 0.00 | 0.114713E+10 | 0.00 | 0.00 |
April | 0.187832E+10 | 0.138106E+10 | 0.131019E+10 | 5377417.48 | 0.130481E+10 | 0.00 | 0.00 |
May | 0.325905E+10 | 0.386336E+09 | 0.153350E+10 | 56091581.50 | 0.147741E+10 | 0.00 | 0.00 |
June | 0.371787E+10 | 0.332281E+09 | 0.168767E+10 | 0.116857E+09 | 0.157081E+10 | 0.00 | 0.00 |
July | 0.367779E+10 | 0.242440E+09 | 0.169236E+10 | 64475388.69 | 0.162789E+10 | 0.00 | 0.00 |
August | 0.329448E+10 | 0.374349E+09 | 0.151554E+10 | 11919829.69 | 0.150362E+10 | 0.00 | 0.00 |
September | 0.251999E+10 | 0.524572E+09 | 0.126686E+10 | 97572.24 | 0.126676E+10 | 0.00 | 0.00 |
October | 0.208560E+10 | 0.101465E+10 | 0.113757E+10 | 0.00 | 0.113757E+10 | 0.00 | 0.00 |
November | 0.885777E+09 | 0.218805E+10 | 0.835741E+09 | 0.00 | 0.835741E+09 | 0.00 | 0.00 |
December | 0.639099E+09 | 0.297872E+10 | 0.779166E+09 | 0.00 | 0.779166E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.245753E+11 | 0.177373E+11 | 0.146370E+11 | 0.254819E+09 | 0.143822E+11 | 0.00 | 0.00 |
Minimum of Months | 0.603172E+09 | 0.242440E+09 | 0.779166E+09 | 0.00 | 0.779166E+09 | 0.00 | 0.00 |
Maximum of Months | 0.371787E+10 | 0.342747E+10 | 0.169236E+10 | 0.116857E+09 | 0.162789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168039E+10 | 0.215112E+10 | 0.143808E+10 | 0.732273E+09 | 0.705807E+09 | 0.00 | 0.00 |
February | 0.181011E+10 | 0.160330E+10 | 0.144638E+10 | 0.698271E+09 | 0.748109E+09 | 0.00 | 0.00 |
March | 0.257983E+10 | 0.151484E+10 | 0.188371E+10 | 0.908460E+09 | 0.975254E+09 | 0.00 | 0.00 |
April | 0.313279E+10 | 0.934143E+09 | 0.200047E+10 | 0.904756E+09 | 0.109572E+10 | 0.00 | 0.00 |
May | 0.404957E+10 | 0.281583E+09 | 0.213068E+10 | 0.923900E+09 | 0.120678E+10 | 0.00 | 0.00 |
June | 0.412043E+10 | 0.238003E+09 | 0.209117E+10 | 0.829295E+09 | 0.126187E+10 | 0.00 | 0.00 |
July | 0.409327E+10 | 0.177581E+09 | 0.208339E+10 | 0.762405E+09 | 0.132098E+10 | 0.00 | 0.00 |
August | 0.375754E+10 | 0.266087E+09 | 0.191978E+10 | 0.660031E+09 | 0.125975E+10 | 0.00 | 0.00 |
September | 0.305597E+10 | 0.367330E+09 | 0.164571E+10 | 0.565788E+09 | 0.107992E+10 | 0.00 | 0.00 |
October | 0.295231E+10 | 0.678353E+09 | 0.168051E+10 | 0.709168E+09 | 0.971345E+09 | 0.00 | 0.00 |
November | 0.197700E+10 | 0.139607E+10 | 0.143986E+10 | 0.734524E+09 | 0.705332E+09 | 0.00 | 0.00 |
December | 0.142723E+10 | 0.190636E+10 | 0.117145E+10 | 0.530638E+09 | 0.640811E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.346364E+11 | 0.115148E+11 | 0.209312E+11 | 0.895951E+10 | 0.119717E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142723E+10 | 0.177581E+09 | 0.117145E+10 | 0.530638E+09 | 0.640811E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412043E+10 | 0.215112E+10 | 0.213068E+10 | 0.923900E+09 | 0.132098E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.692715E+10 | 0.329412E+10 | 0.484465E+10 | 0.345506E+10 | 0.138958E+10 | 0.00 | 0.00 |
February | 0.582072E+10 | 0.250374E+10 | 0.396862E+10 | 0.256881E+10 | 0.139981E+10 | 0.00 | 0.00 |
March | 0.429261E+10 | 0.235266E+10 | 0.280512E+10 | 0.126595E+10 | 0.153917E+10 | 0.00 | 0.00 |
April | 0.342515E+10 | 0.145088E+10 | 0.201206E+10 | 0.471470E+09 | 0.154059E+10 | 0.00 | 0.00 |
May | 0.339990E+10 | 0.404463E+09 | 0.158861E+10 | 67512744.79 | 0.152109E+10 | 0.00 | 0.00 |
June | 0.335768E+10 | 0.341635E+09 | 0.151865E+10 | 14155111.51 | 0.150450E+10 | 0.00 | 0.00 |
July | 0.357788E+10 | 0.242286E+09 | 0.164277E+10 | 30193628.75 | 0.161258E+10 | 0.00 | 0.00 |
August | 0.417850E+10 | 0.404896E+09 | 0.193263E+10 | 0.231972E+09 | 0.170066E+10 | 0.00 | 0.00 |
September | 0.445316E+10 | 0.582448E+09 | 0.224403E+10 | 0.591392E+09 | 0.165263E+10 | 0.00 | 0.00 |
October | 0.652943E+10 | 0.111307E+10 | 0.359767E+10 | 0.187404E+10 | 0.172363E+10 | 0.00 | 0.00 |
November | 0.687754E+10 | 0.221175E+10 | 0.443057E+10 | 0.305049E+10 | 0.138009E+10 | 0.00 | 0.00 |
December | 0.704848E+10 | 0.294297E+10 | 0.473381E+10 | 0.339956E+10 | 0.133425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.598882E+11 | 0.178449E+11 | 0.353192E+11 | 0.170206E+11 | 0.182986E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335768E+10 | 0.242286E+09 | 0.151865E+10 | 14155111.51 | 0.133425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.704848E+10 | 0.329412E+10 | 0.484465E+10 | 0.345506E+10 | 0.172363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195777E+10 | 0.226708E+10 | 0.152963E+10 | 0.827135E+09 | 0.702492E+09 | 0.00 | 0.00 |
February | 0.209723E+10 | 0.170500E+10 | 0.156428E+10 | 0.791738E+09 | 0.772540E+09 | 0.00 | 0.00 |
March | 0.240048E+10 | 0.159907E+10 | 0.170694E+10 | 0.755618E+09 | 0.951325E+09 | 0.00 | 0.00 |
April | 0.327924E+10 | 0.993670E+09 | 0.205168E+10 | 0.943807E+09 | 0.110787E+10 | 0.00 | 0.00 |
May | 0.346935E+10 | 0.302755E+09 | 0.176309E+10 | 0.574327E+09 | 0.118876E+10 | 0.00 | 0.00 |
June | 0.379746E+10 | 0.264606E+09 | 0.189541E+10 | 0.664617E+09 | 0.123079E+10 | 0.00 | 0.00 |
July | 0.358670E+10 | 0.190603E+09 | 0.178783E+10 | 0.495913E+09 | 0.129191E+10 | 0.00 | 0.00 |
August | 0.360697E+10 | 0.288665E+09 | 0.180772E+10 | 0.553365E+09 | 0.125435E+10 | 0.00 | 0.00 |
September | 0.302968E+10 | 0.392216E+09 | 0.161091E+10 | 0.552615E+09 | 0.105829E+10 | 0.00 | 0.00 |
October | 0.306316E+10 | 0.727876E+09 | 0.170421E+10 | 0.736367E+09 | 0.967842E+09 | 0.00 | 0.00 |
November | 0.206930E+10 | 0.148770E+10 | 0.141359E+10 | 0.710411E+09 | 0.703179E+09 | 0.00 | 0.00 |
December | 0.189819E+10 | 0.197481E+10 | 0.140508E+10 | 0.747199E+09 | 0.657879E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342555E+11 | 0.121940E+11 | 0.202404E+11 | 0.835311E+10 | 0.118872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189819E+10 | 0.190603E+09 | 0.140508E+10 | 0.495913E+09 | 0.657879E+09 | 0.00 | 0.00 |
Maximum of Months | 0.379746E+10 | 0.226708E+10 | 0.205168E+10 | 0.943807E+09 | 0.129191E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.596795E+09 | 0.338760E+10 | 0.838177E+09 | 0.00 | 0.838177E+09 | 0.00 | 0.00 |
February | 0.736663E+09 | 0.255933E+10 | 0.893151E+09 | 0.00 | 0.893151E+09 | 0.00 | 0.00 |
March | 0.118436E+10 | 0.242549E+10 | 0.114715E+10 | 0.00 | 0.114715E+10 | 0.00 | 0.00 |
April | 0.180689E+10 | 0.146326E+10 | 0.131021E+10 | 5377575.54 | 0.130484E+10 | 0.00 | 0.00 |
May | 0.320477E+10 | 0.436589E+09 | 0.153354E+10 | 56093230.24 | 0.147744E+10 | 0.00 | 0.00 |
June | 0.367856E+10 | 0.364312E+09 | 0.168770E+10 | 0.116860E+09 | 0.157084E+10 | 0.00 | 0.00 |
July | 0.365610E+10 | 0.254437E+09 | 0.169240E+10 | 64477283.85 | 0.162792E+10 | 0.00 | 0.00 |
August | 0.330893E+10 | 0.356860E+09 | 0.151557E+10 | 11920180.05 | 0.150365E+10 | 0.00 | 0.00 |
September | 0.252915E+10 | 0.494654E+09 | 0.126689E+10 | 97575.10 | 0.126679E+10 | 0.00 | 0.00 |
October | 0.210063E+10 | 0.969141E+09 | 0.113759E+10 | 0.00 | 0.113759E+10 | 0.00 | 0.00 |
November | 0.898731E+09 | 0.210967E+10 | 0.835757E+09 | 0.00 | 0.835757E+09 | 0.00 | 0.00 |
December | 0.647048E+09 | 0.289869E+10 | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.243486E+11 | 0.177200E+11 | 0.146373E+11 | 0.254826E+09 | 0.143825E+11 | 0.00 | 0.00 |
Minimum of Months | 0.596795E+09 | 0.254437E+09 | 0.779181E+09 | 0.00 | 0.779181E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367856E+10 | 0.338760E+10 | 0.169240E+10 | 0.116860E+09 | 0.162792E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168039E+10 | 0.206116E+10 | 0.143810E+10 | 0.732287E+09 | 0.705815E+09 | 0.00 | 0.00 |
February | 0.179455E+10 | 0.156448E+10 | 0.144640E+10 | 0.698285E+09 | 0.748118E+09 | 0.00 | 0.00 |
March | 0.254409E+10 | 0.150134E+10 | 0.188374E+10 | 0.908478E+09 | 0.975265E+09 | 0.00 | 0.00 |
April | 0.309092E+10 | 0.941768E+09 | 0.200050E+10 | 0.904773E+09 | 0.109573E+10 | 0.00 | 0.00 |
May | 0.401462E+10 | 0.290807E+09 | 0.213071E+10 | 0.923918E+09 | 0.120680E+10 | 0.00 | 0.00 |
June | 0.409564E+10 | 0.241729E+09 | 0.209120E+10 | 0.829311E+09 | 0.126189E+10 | 0.00 | 0.00 |
July | 0.408551E+10 | 0.166230E+09 | 0.208342E+10 | 0.762419E+09 | 0.132100E+10 | 0.00 | 0.00 |
August | 0.376742E+10 | 0.236173E+09 | 0.191981E+10 | 0.660044E+09 | 0.125976E+10 | 0.00 | 0.00 |
September | 0.306385E+10 | 0.322636E+09 | 0.164574E+10 | 0.565799E+09 | 0.107994E+10 | 0.00 | 0.00 |
October | 0.295925E+10 | 0.619627E+09 | 0.168054E+10 | 0.709182E+09 | 0.971357E+09 | 0.00 | 0.00 |
November | 0.198921E+10 | 0.129993E+10 | 0.143988E+10 | 0.734539E+09 | 0.705340E+09 | 0.00 | 0.00 |
December | 0.143537E+10 | 0.180733E+10 | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345208E+11 | 0.110532E+11 | 0.209315E+11 | 0.895968E+10 | 0.119718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143537E+10 | 0.166230E+09 | 0.117147E+10 | 0.530649E+09 | 0.640818E+09 | 0.00 | 0.00 |
Maximum of Months | 0.409564E+10 | 0.206116E+10 | 0.213071E+10 | 0.923918E+09 | 0.132100E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.686035E+10 | 0.312626E+10 | 0.484483E+10 | 0.345521E+10 | 0.138963E+10 | 0.00 | 0.00 |
February | 0.574789E+10 | 0.241911E+10 | 0.396877E+10 | 0.256892E+10 | 0.139985E+10 | 0.00 | 0.00 |
March | 0.419139E+10 | 0.238367E+10 | 0.280522E+10 | 0.126600E+10 | 0.153922E+10 | 0.00 | 0.00 |
April | 0.334592E+10 | 0.151242E+10 | 0.201212E+10 | 0.471490E+09 | 0.154063E+10 | 0.00 | 0.00 |
May | 0.335786E+10 | 0.450193E+09 | 0.158865E+10 | 67515546.51 | 0.152114E+10 | 0.00 | 0.00 |
June | 0.333173E+10 | 0.375430E+09 | 0.151869E+10 | 14155698.93 | 0.150454E+10 | 0.00 | 0.00 |
July | 0.357233E+10 | 0.249871E+09 | 0.164282E+10 | 30194881.76 | 0.161263E+10 | 0.00 | 0.00 |
August | 0.420711E+10 | 0.373135E+09 | 0.193269E+10 | 0.231981E+09 | 0.170071E+10 | 0.00 | 0.00 |
September | 0.446482E+10 | 0.523909E+09 | 0.224410E+10 | 0.591416E+09 | 0.165269E+10 | 0.00 | 0.00 |
October | 0.654346E+10 | 0.100871E+10 | 0.359780E+10 | 0.187412E+10 | 0.172369E+10 | 0.00 | 0.00 |
November | 0.686661E+10 | 0.203620E+10 | 0.443075E+10 | 0.305061E+10 | 0.138013E+10 | 0.00 | 0.00 |
December | 0.700863E+10 | 0.276932E+10 | 0.473399E+10 | 0.339970E+10 | 0.133429E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.594981E+11 | 0.172282E+11 | 0.353204E+11 | 0.170213E+11 | 0.182991E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333173E+10 | 0.249871E+09 | 0.151869E+10 | 14155698.93 | 0.133429E+10 | 0.00 | 0.00 |
Maximum of Months | 0.700863E+10 | 0.312626E+10 | 0.484483E+10 | 0.345521E+10 | 0.172369E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195170E+10 | 0.218214E+10 | 0.152965E+10 | 0.827149E+09 | 0.702499E+09 | 0.00 | 0.00 |
February | 0.207651E+10 | 0.166750E+10 | 0.156430E+10 | 0.791751E+09 | 0.772548E+09 | 0.00 | 0.00 |
March | 0.236489E+10 | 0.159219E+10 | 0.170697E+10 | 0.755631E+09 | 0.951335E+09 | 0.00 | 0.00 |
April | 0.323615E+10 | 0.100498E+10 | 0.205171E+10 | 0.943823E+09 | 0.110788E+10 | 0.00 | 0.00 |
May | 0.344002E+10 | 0.320199E+09 | 0.176311E+10 | 0.574337E+09 | 0.118877E+10 | 0.00 | 0.00 |
June | 0.377540E+10 | 0.271077E+09 | 0.189543E+10 | 0.664628E+09 | 0.123080E+10 | 0.00 | 0.00 |
July | 0.357870E+10 | 0.185006E+09 | 0.178785E+10 | 0.495921E+09 | 0.129193E+10 | 0.00 | 0.00 |
August | 0.361825E+10 | 0.260059E+09 | 0.180774E+10 | 0.553374E+09 | 0.125437E+10 | 0.00 | 0.00 |
September | 0.304019E+10 | 0.349767E+09 | 0.161093E+10 | 0.552625E+09 | 0.105830E+10 | 0.00 | 0.00 |
October | 0.307532E+10 | 0.670131E+09 | 0.170423E+10 | 0.736379E+09 | 0.967852E+09 | 0.00 | 0.00 |
November | 0.208385E+10 | 0.139197E+10 | 0.141361E+10 | 0.710423E+09 | 0.703186E+09 | 0.00 | 0.00 |
December | 0.190417E+10 | 0.187119E+10 | 0.140510E+10 | 0.747211E+09 | 0.657885E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341451E+11 | 0.117662E+11 | 0.202406E+11 | 0.835325E+10 | 0.118874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190417E+10 | 0.185006E+09 | 0.140510E+10 | 0.495921E+09 | 0.657885E+09 | 0.00 | 0.00 |
Maximum of Months | 0.377540E+10 | 0.218214E+10 | 0.205171E+10 | 0.943823E+09 | 0.129193E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.397001E+10 | -0.373481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235203033.9 | 60.05 | 0.00 | 0.00 |
February | 0.357964E+10 | -0.336766E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -211982026.1 | 60.05 | 0.00 | 0.00 |
March | 0.407178E+10 | -0.383734E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234443584.8 | 60.05 | 0.00 | 0.00 |
April | 0.347169E+10 | -0.324696E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224727823.0 | 60.05 | 0.00 | 0.00 |
May | 0.347776E+10 | -0.324585E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231906537.1 | 60.05 | 0.00 | 0.00 |
June | 0.325441E+10 | -0.302960E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224815623.6 | 60.05 | 0.00 | 0.00 |
July | 0.299748E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232011681.5 | 60.05 | 0.00 | 0.00 |
August | 0.332353E+10 | -0.309126E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232268069.4 | 60.05 | 0.00 | 0.00 |
September | 0.314709E+10 | -0.292240E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224693852.4 | 60.05 | 0.00 | 0.00 |
October | 0.346414E+10 | -0.323242E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231724085.0 | 60.05 | 0.00 | 0.00 |
November | 0.362918E+10 | -0.340406E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225123926.9 | 60.05 | 0.00 | 0.00 |
December | 0.378040E+10 | -0.354630E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234096783.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.421671E+11 | -0.394241E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.274300E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.299748E+10 | -0.383734E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -235203033.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.407178E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -211982026.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7783.28 | 36.71 | 297.50 | 296.00 | 1469.35 | 25.14 | 177.00 | 279.33 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3368.38 | 27.26 | 165.50 | 279.17 | 1220.88 | 20.66 | 108.83 | 260.83 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1560.12 | 18.37 | 0.00 | 319.33 | 928.03 | 20.56 | 112.67 | 281.00 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 1225.23 | 17.64 | 0.00 | 322.00 | 715.12 | 19.76 | 89.33 | 282.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1089.15 | 17.88 | 0.00 | 347.83 | 618.52 | 20.04 | 64.33 | 298.50 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 1032.66 | 17.51 | 0.00 | 349.33 | 589.53 | 19.68 | 46.83 | 302.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1143.06 | 17.86 | 0.00 | 359.00 | 633.59 | 20.01 | 90.33 | 312.33 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1334.37 | 18.16 | 0.00 | 345.50 | 726.94 | 20.28 | 137.17 | 307.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:30 | 1577.53 | 18.30 | 0.00 | 317.17 | 849.25 | 20.46 | 155.67 | 281.83 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:19 | 2671.23 | 21.05 | 39.33 | 313.50 | 1164.62 | 21.62 | 188.00 | 283.67 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:39 | 7850.24 | 36.13 | 297.00 | 288.17 | 1318.80 | 22.84 | 143.83 | 268.50 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-07:49 | 7935.15 | 37.50 | 279.33 | 284.17 | 1861.04 | 27.09 | 171.33 | 267.33 |
Annual Sum or Average | 4027.67 | 0.52 | 3005.28 | 23.08 | 1078.67 | 3821.17 | 972.74 | 21.35 | 1485.33 | 3425.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1032.66 | 17.51 | 0.00 | 279.17 | 589.53 | 19.68 | 46.83 | 260.83 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7935.15 | 37.50 | 297.50 | 359.00 | 1861.04 | 27.09 | 188.00 | 312.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1903.14 | 19.71 | 81.50 | 267.50 | 1071.77 | 22.41 | 74.67 | 215.50 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2180.96 | 21.59 | 89.67 | 258.17 | 1165.33 | 22.46 | 66.33 | 224.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2236.03 | 20.19 | 74.33 | 313.33 | 1180.23 | 21.11 | 48.00 | 271.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2323.72 | 20.44 | 95.83 | 323.17 | 1241.37 | 21.48 | 68.00 | 290.17 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-06:40 | 2620.87 | 21.09 | 106.00 | 357.17 | 1052.30 | 20.59 | 49.50 | 310.83 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2346.15 | 20.54 | 114.00 | 356.00 | 1000.86 | 21.13 | 62.67 | 317.83 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:30 | 2266.42 | 20.79 | 112.33 | 362.83 | 982.68 | 20.55 | 53.67 | 314.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2089.52 | 20.71 | 105.17 | 346.00 | 1096.69 | 21.83 | 76.00 | 305.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1991.46 | 20.77 | 95.00 | 312.83 | 1028.84 | 21.86 | 67.83 | 275.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2057.00 | 20.25 | 79.17 | 299.50 | 1072.78 | 21.96 | 58.33 | 266.50 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1728.13 | 20.57 | 84.00 | 262.00 | 893.74 | 21.33 | 57.17 | 225.17 |
December | 282.83 | 0.55 | 0.48 | 01-DEC-07:49 | 1861.32 | 21.41 | 89.17 | 253.33 | 1000.51 | 22.14 | 66.67 | 202.50 |
Annual Sum or Average | 4027.67 | 0.53 | 2147.21 | 20.67 | 1126.17 | 3711.83 | 1064.13 | 21.53 | 748.83 | 3219.17 | ||
Minimum of Months | 282.83 | 0.52 | 0.48 | 1728.13 | 19.71 | 74.33 | 253.33 | 893.74 | 20.55 | 48.00 | 202.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2620.87 | 21.59 | 114.00 | 362.83 | 1241.37 | 22.46 | 76.00 | 317.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.58 | 0.48 | 01-JAN-09:39 | 517.63 | 14.57 | 0.00 | 247.17 | 338.17 | 17.07 | 0.00 | 151.17 |
February | 295.50 | 0.56 | 0.48 | 01-FEB-11:00 | 597.43 | 15.77 | 0.00 | 245.33 | 391.57 | 18.19 | 0.00 | 177.83 |
March | 296.00 | 0.54 | 0.48 | 02-MAR-12:00 | 701.28 | 16.87 | 0.00 | 304.17 | 444.10 | 19.08 | 0.00 | 231.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 838.32 | 17.33 | 0.00 | 325.17 | 514.25 | 19.43 | 14.67 | 282.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1037.90 | 19.61 | 27.17 | 369.67 | 598.79 | 20.67 | 84.67 | 326.67 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:30 | 1206.35 | 20.84 | 58.00 | 373.83 | 650.84 | 22.90 | 176.50 | 345.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1179.24 | 19.39 | 23.67 | 376.17 | 646.29 | 21.51 | 143.83 | 340.33 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1031.71 | 18.05 | 0.00 | 352.83 | 584.81 | 20.15 | 64.67 | 317.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 861.71 | 17.26 | 0.00 | 314.50 | 499.54 | 19.35 | 9.67 | 263.50 |
October | 330.00 | 0.53 | 0.48 | 01-OCT-08:09 | 738.24 | 16.99 | 0.00 | 294.83 | 455.71 | 19.25 | 0.00 | 241.50 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:20 | 531.57 | 15.15 | 0.00 | 239.33 | 349.26 | 17.65 | 0.00 | 157.83 |
December | 282.83 | 0.57 | 0.48 | 01-DEC-09:30 | 517.87 | 14.80 | 0.00 | 238.50 | 340.33 | 17.36 | 0.00 | 139.17 |
Annual Sum or Average | 4027.67 | 0.53 | 838.75 | 17.40 | 108.83 | 3681.50 | 496.02 | 19.55 | 494.00 | 2974.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 517.63 | 14.57 | 0.00 | 238.50 | 338.17 | 17.07 | 0.00 | 139.17 | |
Maximum of Months | 394.00 | 0.58 | 0.48 | 1206.35 | 20.84 | 58.00 | 376.17 | 650.84 | 22.90 | 176.50 | 345.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:30 | 2260.17 | 22.59 | 109.50 | 272.33 | 1262.26 | 23.12 | 82.33 | 223.00 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1985.42 | 20.44 | 79.17 | 263.67 | 1044.19 | 21.19 | 51.33 | 230.50 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 2111.49 | 19.43 | 68.83 | 308.67 | 1140.53 | 21.81 | 56.67 | 264.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:39 | 2437.83 | 19.13 | 82.00 | 324.67 | 1289.41 | 20.21 | 53.00 | 290.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:09 | 2012.62 | 14.76 | 0.00 | 354.50 | 893.23 | 18.08 | 0.00 | 313.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2125.29 | 14.65 | 0.00 | 355.67 | 912.44 | 17.91 | 0.00 | 314.50 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1965.35 | 15.20 | 3.67 | 363.67 | 879.05 | 18.19 | 0.00 | 319.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2028.71 | 17.68 | 59.00 | 347.50 | 937.78 | 18.44 | 5.50 | 307.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1863.46 | 19.42 | 80.67 | 311.33 | 975.85 | 20.52 | 52.50 | 275.50 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:20 | 2424.72 | 22.45 | 108.83 | 307.33 | 1008.37 | 21.74 | 53.50 | 270.00 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1949.92 | 21.37 | 93.50 | 264.00 | 1059.98 | 22.29 | 66.67 | 226.67 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-09:30 | 2039.92 | 21.47 | 88.00 | 267.67 | 1147.27 | 23.63 | 75.67 | 215.50 |
Annual Sum or Average | 4027.67 | 0.53 | 2099.63 | 18.80 | 773.17 | 3741.00 | 1036.57 | 20.40 | 497.17 | 3250.83 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1863.46 | 14.65 | 0.00 | 263.67 | 879.05 | 17.91 | 0.00 | 215.50 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2437.83 | 22.59 | 109.50 | 363.67 | 1289.41 | 23.63 | 82.33 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7648.35 | 36.44 | 297.33 | 295.83 | 1360.55 | 22.69 | 92.33 | 276.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3249.72 | 25.20 | 165.33 | 277.83 | 1175.00 | 19.93 | 36.50 | 265.00 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1480.27 | 14.66 | 0.00 | 316.33 | 869.34 | 18.26 | 0.17 | 277.33 |
April | 347.33 | 0.54 | 0.48 | 01-APR-08:09 | 1173.69 | 14.12 | 0.00 | 319.83 | 681.37 | 17.57 | 0.00 | 279.83 |
May | 353.67 | 0.53 | 0.48 | 01-MAY-07:40 | 1048.56 | 14.27 | 0.00 | 345.00 | 594.45 | 17.76 | 0.00 | 293.50 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 995.06 | 13.91 | 0.00 | 347.50 | 567.73 | 17.38 | 0.00 | 297.00 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1100.80 | 14.17 | 0.00 | 357.17 | 608.50 | 17.61 | 0.00 | 307.50 |
August | 380.83 | 0.53 | 0.48 | 01-AUG-07:30 | 1281.54 | 14.48 | 0.00 | 344.17 | 693.73 | 17.89 | 0.00 | 303.50 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1509.40 | 14.53 | 0.00 | 315.17 | 804.00 | 17.96 | 0.00 | 278.83 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:19 | 2565.42 | 17.55 | 39.33 | 312.50 | 1086.97 | 19.02 | 7.33 | 281.83 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:39 | 7724.42 | 35.85 | 296.17 | 286.67 | 1218.92 | 20.09 | 46.00 | 267.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-07:49 | 7790.73 | 37.29 | 279.33 | 283.33 | 1744.26 | 24.83 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2925.42 | 20.31 | 1077.50 | 3801.33 | 917.99 | 19.07 | 293.33 | 3394.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 995.06 | 13.91 | 0.00 | 277.83 | 567.73 | 17.38 | 0.00 | 265.00 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 7790.73 | 37.29 | 297.33 | 357.17 | 1744.26 | 24.83 | 111.00 | 307.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1850.80 | 19.22 | 81.50 | 264.67 | 1030.68 | 22.20 | 72.33 | 211.67 |
February | 295.50 | 0.54 | 0.48 | 01-FEB-11:39 | 2125.07 | 21.12 | 89.67 | 255.83 | 1122.88 | 22.25 | 65.17 | 220.83 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2171.89 | 19.70 | 74.33 | 310.50 | 1124.08 | 20.91 | 47.83 | 266.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2253.30 | 19.99 | 95.83 | 321.33 | 1191.51 | 21.30 | 68.00 | 286.83 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-06:40 | 2550.21 | 20.64 | 106.00 | 354.33 | 999.73 | 20.39 | 49.17 | 306.67 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2290.20 | 20.10 | 114.00 | 353.50 | 944.67 | 20.17 | 54.00 | 312.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:30 | 2206.83 | 20.36 | 112.33 | 361.17 | 935.85 | 20.39 | 53.67 | 311.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 2015.77 | 20.07 | 103.00 | 344.67 | 1052.20 | 21.66 | 75.83 | 300.83 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1909.96 | 18.93 | 80.50 | 309.50 | 985.99 | 21.68 | 67.67 | 272.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 1994.65 | 19.75 | 79.17 | 298.33 | 1025.70 | 21.76 | 57.00 | 264.83 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1675.41 | 20.08 | 84.00 | 259.00 | 853.58 | 21.11 | 55.50 | 221.67 |
December | 282.83 | 0.55 | 0.48 | 01-DEC-07:49 | 1809.68 | 20.78 | 87.83 | 250.33 | 964.67 | 21.92 | 62.83 | 199.83 |
Annual Sum or Average | 4027.67 | 0.53 | 2084.21 | 20.06 | 1108.17 | 3683.17 | 1017.52 | 21.26 | 729.00 | 3176.17 | ||
Minimum of Months | 282.83 | 0.52 | 0.48 | 1675.41 | 18.93 | 74.33 | 250.33 | 853.58 | 20.17 | 47.83 | 199.83 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2550.21 | 21.12 | 114.00 | 361.17 | 1191.51 | 22.25 | 75.83 | 312.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.59 | 0.48 | 01-JAN-09:39 | 498.74 | 11.13 | 0.00 | 241.67 | 328.52 | 14.86 | 0.00 | 141.00 |
February | 295.50 | 0.56 | 0.48 | 01-FEB-11:00 | 576.00 | 12.38 | 0.00 | 242.33 | 380.66 | 16.10 | 0.00 | 172.33 |
March | 296.00 | 0.54 | 0.48 | 02-MAR-12:00 | 676.89 | 13.63 | 0.00 | 300.50 | 431.37 | 17.19 | 0.00 | 223.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 809.15 | 14.01 | 0.00 | 323.83 | 498.54 | 17.49 | 0.00 | 278.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 995.12 | 14.89 | 2.17 | 365.17 | 581.42 | 19.65 | 27.50 | 325.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:30 | 1163.93 | 17.80 | 58.00 | 372.17 | 625.61 | 20.96 | 59.83 | 340.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1136.53 | 15.95 | 23.50 | 374.00 | 621.01 | 19.31 | 24.67 | 336.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 994.27 | 14.49 | 0.00 | 351.17 | 563.19 | 17.94 | 0.00 | 312.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 831.02 | 13.79 | 0.00 | 312.00 | 482.24 | 17.19 | 0.00 | 257.33 |
October | 330.00 | 0.53 | 0.48 | 01-OCT-08:20 | 711.53 | 13.62 | 0.00 | 293.17 | 441.38 | 17.18 | 0.00 | 236.50 |
November | 308.00 | 0.58 | 0.48 | 01-NOV-10:30 | 512.13 | 11.66 | 0.00 | 234.00 | 339.35 | 15.44 | 0.00 | 151.50 |
December | 282.83 | 0.58 | 0.48 | 01-DEC-09:39 | 498.51 | 11.29 | 0.00 | 233.17 | 330.44 | 15.10 | 0.00 | 129.83 |
Annual Sum or Average | 4027.67 | 0.54 | 808.21 | 13.90 | 83.67 | 3643.17 | 479.62 | 17.54 | 112.00 | 2905.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 498.51 | 11.13 | 0.00 | 233.17 | 328.52 | 14.86 | 0.00 | 129.83 | |
Maximum of Months | 394.00 | 0.59 | 0.48 | 1163.93 | 17.80 | 58.00 | 374.00 | 625.61 | 20.96 | 59.83 | 340.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:39 | 2209.04 | 22.21 | 109.50 | 270.50 | 1220.46 | 23.02 | 82.17 | 219.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1921.64 | 20.02 | 79.17 | 261.50 | 995.24 | 21.07 | 51.17 | 227.17 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 2054.12 | 18.97 | 68.83 | 306.67 | 1091.79 | 21.67 | 56.67 | 260.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:50 | 2368.44 | 18.67 | 82.00 | 323.00 | 1237.97 | 20.05 | 53.00 | 287.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:09 | 1951.13 | 14.19 | 0.00 | 352.50 | 851.94 | 17.87 | 0.00 | 309.83 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:40 | 2070.68 | 14.10 | 0.00 | 354.17 | 864.69 | 17.70 | 0.00 | 309.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1907.95 | 14.64 | 3.67 | 361.67 | 839.21 | 17.98 | 0.00 | 316.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1965.52 | 17.19 | 59.00 | 346.17 | 895.06 | 18.25 | 5.50 | 303.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1813.91 | 18.98 | 80.50 | 309.67 | 934.16 | 20.37 | 52.17 | 271.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 2356.15 | 21.76 | 105.67 | 305.67 | 961.21 | 21.62 | 53.50 | 267.67 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1844.58 | 19.51 | 80.00 | 261.33 | 1019.74 | 22.18 | 66.67 | 223.17 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-09:30 | 1974.07 | 20.73 | 85.00 | 265.17 | 1103.21 | 23.54 | 75.50 | 211.50 |
Annual Sum or Average | 4027.67 | 0.53 | 2036.07 | 18.18 | 753.33 | 3718.00 | 992.00 | 20.24 | 496.33 | 3207.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1813.91 | 14.10 | 0.00 | 261.33 | 839.21 | 17.70 | 0.00 | 211.50 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2368.44 | 22.21 | 109.50 | 361.67 | 1237.97 | 23.54 | 82.17 | 316.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7648.30 | 36.44 | 297.33 | 295.83 | 1360.48 | 22.69 | 92.33 | 276.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3249.64 | 25.20 | 165.33 | 277.83 | 1174.93 | 19.93 | 36.50 | 265.00 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1480.19 | 14.66 | 0.00 | 316.33 | 869.28 | 18.26 | 0.17 | 277.33 |
April | 347.33 | 0.54 | 0.48 | 01-APR-08:09 | 1173.63 | 14.12 | 0.00 | 319.83 | 681.32 | 17.57 | 0.00 | 279.83 |
May | 353.67 | 0.53 | 0.48 | 01-MAY-07:40 | 1048.50 | 14.27 | 0.00 | 345.00 | 594.41 | 17.76 | 0.00 | 293.50 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 995.00 | 13.91 | 0.00 | 347.50 | 567.69 | 17.38 | 0.00 | 297.00 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1100.73 | 14.17 | 0.00 | 357.17 | 608.45 | 17.62 | 0.00 | 307.50 |
August | 380.83 | 0.53 | 0.48 | 01-AUG-07:30 | 1281.46 | 14.48 | 0.00 | 344.17 | 693.68 | 17.89 | 0.00 | 303.50 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1509.30 | 14.54 | 0.00 | 315.17 | 803.93 | 17.96 | 0.00 | 278.83 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:19 | 2565.31 | 17.55 | 39.33 | 312.50 | 1086.89 | 19.02 | 7.33 | 281.83 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:39 | 7724.36 | 35.85 | 296.17 | 286.67 | 1218.85 | 20.09 | 46.00 | 267.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-07:49 | 7790.69 | 37.29 | 279.33 | 283.33 | 1744.18 | 24.83 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2925.35 | 20.31 | 1077.50 | 3801.33 | 917.92 | 19.07 | 293.33 | 3394.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 995.00 | 13.91 | 0.00 | 277.83 | 567.69 | 17.38 | 0.00 | 265.00 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 7790.69 | 37.29 | 297.33 | 357.17 | 1744.18 | 24.83 | 111.00 | 307.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:49 | 1850.79 | 19.22 | 81.50 | 264.67 | 1030.64 | 22.20 | 72.33 | 211.67 |
February | 295.50 | 0.54 | 0.48 | 01-FEB-11:39 | 2125.05 | 21.12 | 89.67 | 255.83 | 1122.84 | 22.25 | 65.17 | 220.83 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2171.86 | 19.71 | 74.33 | 310.50 | 1124.03 | 20.91 | 47.83 | 266.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2253.26 | 19.99 | 95.83 | 321.33 | 1191.46 | 21.30 | 68.00 | 286.83 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-06:40 | 2550.16 | 20.65 | 106.00 | 354.33 | 999.67 | 20.39 | 49.17 | 306.67 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2290.14 | 20.10 | 114.00 | 353.50 | 944.61 | 20.17 | 54.00 | 312.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:30 | 2206.75 | 20.36 | 112.33 | 361.17 | 935.78 | 20.39 | 53.67 | 311.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 2015.70 | 20.07 | 103.00 | 344.67 | 1052.13 | 21.66 | 75.83 | 300.83 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1909.89 | 18.93 | 80.50 | 309.50 | 985.93 | 21.68 | 67.67 | 272.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 1994.60 | 19.75 | 79.17 | 298.33 | 1025.64 | 21.76 | 57.00 | 264.83 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1675.39 | 20.08 | 84.00 | 259.00 | 853.54 | 21.11 | 55.50 | 221.67 |
December | 282.83 | 0.55 | 0.48 | 01-DEC-07:49 | 1809.66 | 20.78 | 87.83 | 250.33 | 964.64 | 21.92 | 62.83 | 199.83 |
Annual Sum or Average | 4027.67 | 0.53 | 2084.17 | 20.06 | 1108.17 | 3683.17 | 1017.46 | 21.27 | 729.00 | 3176.17 | ||
Minimum of Months | 282.83 | 0.52 | 0.48 | 1675.39 | 18.93 | 74.33 | 250.33 | 853.54 | 20.17 | 47.83 | 199.83 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2550.16 | 21.12 | 114.00 | 361.17 | 1191.46 | 22.25 | 75.83 | 312.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.59 | 0.48 | 01-JAN-09:39 | 498.74 | 11.13 | 0.00 | 241.67 | 328.50 | 14.86 | 0.00 | 141.00 |
February | 295.50 | 0.56 | 0.48 | 01-FEB-11:00 | 576.00 | 12.39 | 0.00 | 242.33 | 380.64 | 16.10 | 0.00 | 172.33 |
March | 296.00 | 0.54 | 0.48 | 02-MAR-12:00 | 676.88 | 13.63 | 0.00 | 300.50 | 431.35 | 17.19 | 0.00 | 223.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 809.12 | 14.01 | 0.00 | 323.83 | 498.51 | 17.49 | 0.00 | 278.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 995.07 | 14.89 | 2.17 | 365.17 | 581.38 | 19.65 | 27.50 | 325.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:30 | 1163.88 | 17.80 | 58.00 | 372.17 | 625.57 | 20.96 | 59.83 | 340.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1136.47 | 15.95 | 23.50 | 374.00 | 620.97 | 19.31 | 24.67 | 336.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 994.22 | 14.49 | 0.00 | 351.17 | 563.14 | 17.94 | 0.00 | 312.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 830.99 | 13.80 | 0.00 | 312.00 | 482.20 | 17.19 | 0.00 | 257.33 |
October | 330.00 | 0.53 | 0.48 | 01-OCT-08:20 | 711.51 | 13.62 | 0.00 | 293.17 | 441.35 | 17.19 | 0.00 | 236.50 |
November | 308.00 | 0.58 | 0.48 | 01-NOV-10:30 | 512.13 | 11.66 | 0.00 | 234.00 | 339.34 | 15.44 | 0.00 | 151.50 |
December | 282.83 | 0.58 | 0.48 | 01-DEC-09:39 | 498.51 | 11.29 | 0.00 | 233.17 | 330.42 | 15.10 | 0.00 | 129.83 |
Annual Sum or Average | 4027.67 | 0.54 | 808.18 | 13.90 | 83.67 | 3643.17 | 479.58 | 17.54 | 112.00 | 2905.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 498.51 | 11.13 | 0.00 | 233.17 | 328.50 | 14.86 | 0.00 | 129.83 | |
Maximum of Months | 394.00 | 0.59 | 0.48 | 1163.88 | 17.80 | 58.00 | 374.00 | 625.57 | 20.96 | 59.83 | 340.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:39 | 2209.02 | 22.21 | 109.50 | 270.50 | 1220.43 | 23.02 | 82.33 | 219.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1921.62 | 20.02 | 79.17 | 261.50 | 995.20 | 21.07 | 51.17 | 227.17 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 2054.09 | 18.97 | 68.83 | 306.67 | 1091.74 | 21.67 | 56.67 | 260.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:50 | 2368.40 | 18.68 | 82.00 | 323.00 | 1237.91 | 20.05 | 53.00 | 287.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:09 | 1951.07 | 14.20 | 0.00 | 352.50 | 851.88 | 17.87 | 0.00 | 309.83 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:40 | 2070.61 | 14.10 | 0.00 | 354.17 | 864.64 | 17.70 | 0.00 | 309.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1907.87 | 14.64 | 3.67 | 361.67 | 839.15 | 17.98 | 0.00 | 316.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1965.45 | 17.19 | 59.00 | 346.17 | 894.99 | 18.25 | 5.50 | 303.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1813.85 | 18.98 | 80.50 | 309.67 | 934.10 | 20.37 | 52.17 | 271.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 2356.11 | 21.77 | 105.67 | 305.67 | 961.15 | 21.62 | 53.50 | 267.67 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1844.57 | 19.51 | 80.00 | 261.33 | 1019.70 | 22.18 | 66.67 | 223.17 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-09:30 | 1974.06 | 20.73 | 85.00 | 265.17 | 1103.17 | 23.54 | 75.50 | 211.50 |
Annual Sum or Average | 4027.67 | 0.53 | 2036.02 | 18.18 | 753.33 | 3718.00 | 991.94 | 20.24 | 496.50 | 3207.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1813.85 | 14.10 | 0.00 | 261.33 | 839.15 | 17.70 | 0.00 | 211.50 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2368.40 | 22.21 | 109.50 | 361.67 | 1237.91 | 23.54 | 82.33 | 316.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14835745.93 | 2884.79 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3633082.46 | 1450.09 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1978597.99 | 1167.96 | 09-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11987069.63 | 2610.35 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32434496.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14835745.93 | 2884.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.848233E+09 | 7720.29 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.538955E+09 | 7720.29 | 03-FEB-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.866091E+09 | 7720.29 | 02-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174268E+09 | 7720.29 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23483738.14 | 4887.49 | 27-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224765E+09 | 7720.29 | 09-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752863E+09 | 7720.29 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.866091E+09 | 7720.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66234006.41 | 5172.03 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40748711.27 | 5172.03 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78174718.30 | 5172.03 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56931234.66 | 5172.03 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78174718.30 | 5172.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229736E+09 | 7780.85 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152669E+09 | 7780.85 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144487E+09 | 7780.85 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103095E+09 | 7780.85 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229736E+09 | 7780.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 95552428.14 | 5132.15 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67162578.63 | 5132.15 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90786416.96 | 5132.15 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56352918.21 | 5132.15 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95552428.14 | 5132.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 71486863.02 | 4715.03 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25045688.34 | 3456.07 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16849979.55 | 3223.20 | 09-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64120493.31 | 4692.09 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71486863.02 | 4715.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12704130.25 | 24931.74 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25224564.83 | 24931.74 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37928695.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25224564.83 | 24931.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123874E+09 | 8941.29 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60449651.08 | 8941.29 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110535E+09 | 8941.29 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 280136.42 | 1867.58 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90932647.72 | 8941.29 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123874E+09 | 8941.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241261E+09 | 5960.41 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100951E+09 | 5960.41 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122829E+09 | 5960.41 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104504.39 | 645.19 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 389396.76 | 185.46 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3281470.74 | 4428.93 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187582E+09 | 5960.41 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241261E+09 | 5960.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390083E+09 | 9010.70 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185439E+09 | 9010.70 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150179E+09 | 9010.70 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5559524.34 | 6466.25 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243988E+09 | 9010.70 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390083E+09 | 9010.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314702E+09 | 5921.55 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149889E+09 | 5921.55 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138860E+09 | 5921.55 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 312160.13 | 140.84 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8731107.75 | 5921.55 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204902E+09 | 5921.55 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.817396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314702E+09 | 5921.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151976E+09 | 6271.47 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45847567.59 | 5202.48 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33016615.02 | 5093.30 | 09-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108095E+09 | 6150.68 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151976E+09 | 6271.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.541580E+09 | 26829.95 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.331394E+09 | 26829.95 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289131E+09 | 26829.95 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5502849.22 | 10331.92 | 16-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.389056E+09 | 26829.95 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.541580E+09 | 26829.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.462759E+09 | 11291.26 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241712E+09 | 11291.26 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316380E+09 | 11291.26 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7798926.33 | 9787.26 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4619721.63 | 5262.34 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27749047.25 | 11291.26 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358123E+09 | 11291.26 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462759E+09 | 11291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561449E+09 | 7396.17 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266976E+09 | 7396.17 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271579E+09 | 7396.17 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5834379.28 | 7396.17 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5723208.97 | 7027.31 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44695143.80 | 7396.17 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461095E+09 | 7396.17 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561449E+09 | 7396.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107769E+10 | 11336.34 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526272E+09 | 11336.34 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403527E+09 | 11336.34 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9517083.50 | 11336.34 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10065216.22 | 7287.36 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87184552.58 | 11336.34 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.714718E+09 | 11336.34 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107769E+10 | 11336.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.819944E+09 | 7371.56 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.407074E+09 | 7371.56 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359015E+09 | 7371.56 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13147709.44 | 7371.56 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13414931.34 | 6943.90 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98734900.60 | 7371.56 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586778E+09 | 7371.56 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.819944E+09 | 7371.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208089E+11 | 0.144770E+11 | 67294.59 | 19-JAN-15:10 | 45876.65 | 0.00 |
February | 0.00 | 0.00 | 0.284080E+11 | 0.186874E+11 | 65332.87 | 27-FEB-15:40 | 48525.22 | 0.00 |
March | 0.00 | 0.00 | 0.338765E+11 | 0.234742E+11 | 68741.17 | 28-MAR-12:00 | 44282.97 | 0.00 |
April | 0.00 | 0.00 | 0.529547E+11 | 0.379394E+11 | 85264.53 | 28-APR-16:00 | 58386.91 | 0.00 |
May | 0.00 | 0.00 | 0.918753E+11 | 0.629011E+11 | 90598.39 | 30-MAY-12:03 | 61725.51 | 0.00 |
June | 0.00 | 0.00 | 0.977950E+11 | 0.665158E+11 | 95192.91 | 29-JUN-12:04 | 61425.94 | 0.00 |
July | 0.00 | 0.00 | 0.102381E+12 | 0.668653E+11 | 105450.00 | 05-JUL-12:04 | 65828.39 | 0.00 |
August | 0.00 | 0.00 | 0.109033E+12 | 0.724531E+11 | 102352.51 | 07-AUG-12:02 | 62987.29 | 0.00 |
September | 0.00 | 0.00 | 0.932134E+11 | 0.614091E+11 | 102801.49 | 05-SEP-12:02 | 62841.84 | 0.00 |
October | 0.00 | 0.00 | 0.830979E+11 | 0.580569E+11 | 105434.11 | 06-OCT-12:02 | 62534.08 | 0.00 |
November | 0.00 | 0.00 | 0.462738E+11 | 0.330738E+11 | 89231.34 | 07-NOV-13:05 | 54852.59 | 0.00 |
December | 0.00 | 0.00 | 0.305381E+11 | 0.211530E+11 | 77722.09 | 14-DEC-13:05 | 48510.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.790257E+12 | 0.537006E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.208089E+11 | 0.144770E+11 | 65332.87 | 44282.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109033E+12 | 0.724531E+11 | 105450.00 | 65828.39 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.178933E+11 | 0.122058E+11 | 58646.82 | 19-JAN-15:10 | 39652.26 | 0.00 |
February | 0.00 | 0.00 | 0.251871E+11 | 0.165607E+11 | 56723.11 | 27-FEB-15:30 | 42276.43 | 0.00 |
March | 0.00 | 0.00 | 0.302395E+11 | 0.208895E+11 | 58449.42 | 30-MAR-13:00 | 40585.95 | 0.00 |
April | 0.00 | 0.00 | 0.476976E+11 | 0.337640E+11 | 80640.24 | 28-APR-16:00 | 53928.37 | 0.00 |
May | 0.00 | 0.00 | 0.828356E+11 | 0.557214E+11 | 115932.31 | 22-MAY-04:02 | 73353.11 | 0.00 |
June | 0.00 | 0.00 | 0.880677E+11 | 0.586283E+11 | 84615.14 | 19-JUN-11:00 | 54930.47 | 0.00 |
July | 0.00 | 0.00 | 0.915757E+11 | 0.578854E+11 | 90504.07 | 03-JUL-04:02 | 73906.03 | 0.00 |
August | 0.00 | 0.00 | 0.940631E+11 | 0.600102E+11 | 89975.67 | 05-AUG-05:03 | 69621.65 | 0.00 |
September | 0.00 | 0.00 | 0.797883E+11 | 0.502062E+11 | 92157.62 | 05-SEP-05:12 | 62042.27 | 0.00 |
October | 0.00 | 0.00 | 0.709235E+11 | 0.476693E+11 | 91361.47 | 06-OCT-14:00 | 55811.85 | 0.00 |
November | 0.00 | 0.00 | 0.388674E+11 | 0.269304E+11 | 76354.14 | 02-NOV-14:50 | 51752.16 | 0.00 |
December | 0.00 | 0.00 | 0.260454E+11 | 0.175778E+11 | 64344.50 | 14-DEC-13:30 | 41933.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.693184E+12 | 0.458049E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.178933E+11 | 0.122058E+11 | 56723.11 | 39652.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.940631E+11 | 0.600102E+11 | 115932.31 | 73906.03 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185582E+11 | 0.126429E+11 | 63400.46 | 19-JAN-15:00 | 43899.92 | 0.00 |
February | 0.00 | 0.00 | 0.264000E+11 | 0.175575E+11 | 61962.45 | 24-FEB-14:30 | 45592.79 | 0.00 |
March | 0.00 | 0.00 | 0.319046E+11 | 0.222083E+11 | 62995.45 | 29-MAR-15:00 | 47178.15 | 0.00 |
April | 0.00 | 0.00 | 0.507155E+11 | 0.363511E+11 | 89722.66 | 28-APR-16:00 | 63305.79 | 0.00 |
May | 0.00 | 0.00 | 0.879703E+11 | 0.606075E+11 | 129517.16 | 22-MAY-04:02 | 84995.52 | 0.00 |
June | 0.00 | 0.00 | 0.939928E+11 | 0.643955E+11 | 94448.04 | 28-JUN-14:30 | 66798.45 | 0.00 |
July | 0.00 | 0.00 | 0.969479E+11 | 0.631047E+11 | 106202.26 | 03-JUL-04:02 | 85203.71 | 0.00 |
August | 0.00 | 0.00 | 0.991921E+11 | 0.649610E+11 | 95004.64 | 23-AUG-04:02 | 70401.24 | 0.00 |
September | 0.00 | 0.00 | 0.833582E+11 | 0.534280E+11 | 92213.89 | 11-SEP-14:00 | 63863.83 | 0.00 |
October | 0.00 | 0.00 | 0.738953E+11 | 0.503229E+11 | 99571.67 | 06-OCT-14:00 | 64024.77 | 0.00 |
November | 0.00 | 0.00 | 0.398986E+11 | 0.273897E+11 | 83808.97 | 02-NOV-14:30 | 58848.91 | 0.00 |
December | 0.00 | 0.00 | 0.269249E+11 | 0.181016E+11 | 69575.63 | 15-DEC-14:50 | 54081.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.729759E+12 | 0.491071E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.185582E+11 | 0.126429E+11 | 61962.45 | 43899.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.991921E+11 | 0.649610E+11 | 129517.16 | 85203.71 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1385.48 | 5050.51 | 23-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1383.11 | 5042.58 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1423.55 | 4927.82 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1243.96 | 4652.33 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1203.09 | 4360.95 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1160.06 | 4060.79 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1024.13 | 3860.87 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1145.37 | 3945.82 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1118.91 | 4183.57 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1198.17 | 4514.46 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1304.42 | 4805.33 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1315.27 | 4995.41 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1241.35 | ||||
Minimum of Months | 0.00 | 0.00 | 1024.13 | 3860.87 | ||
Maximum of Months | 0.00 | 0.00 | 1423.55 | 5050.51 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162244E+10 | 0.30 | 4379.60 | 03-JAN-07:01 | 1.05 |
February | 0.152947E+10 | 0.30 | 3182.30 | 27-FEB-15:30 | 0.86 |
March | 0.182066E+10 | 0.32 | 3757.58 | 09-MAR-06:02 | 0.96 |
April | 0.205471E+10 | 0.32 | 3784.30 | 28-APR-15:20 | 0.95 |
May | 0.330413E+10 | 0.41 | 10402.86 | 31-MAY-05:02 | 1.78 |
June | 0.353929E+10 | 0.44 | 9106.28 | 05-JUN-04:02 | 1.64 |
July | 0.361617E+10 | 0.44 | 10402.86 | 24-JUL-04:02 | 1.79 |
August | 0.413904E+10 | 0.47 | 10402.86 | 22-AUG-04:02 | 1.78 |
September | 0.340376E+10 | 0.43 | 10402.86 | 18-SEP-04:02 | 1.78 |
October | 0.353608E+10 | 0.42 | 10402.86 | 23-OCT-04:02 | 1.78 |
November | 0.227291E+10 | 0.34 | 4599.97 | 06-NOV-16:20 | 1.07 |
December | 0.184529E+10 | 0.31 | 4379.60 | 18-DEC-07:01 | 1.05 |
Annual Sum or Average | 0.326840E+11 | 0.38 | |||
Minimum of Months | 0.152947E+10 | 0.30 | 3182.30 | 0.86 | |
Maximum of Months | 0.413904E+10 | 0.47 | 10402.86 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142206E+10 | 0.29 | 2526.56 | 19-JAN-15:30 | 0.80 |
February | 0.135546E+10 | 0.29 | 2700.78 | 27-FEB-15:30 | 0.84 |
March | 0.158381E+10 | 0.31 | 2337.40 | 29-MAR-15:20 | 0.77 |
April | 0.178753E+10 | 0.32 | 3465.97 | 28-APR-15:30 | 0.96 |
May | 0.278635E+10 | 0.40 | 9330.42 | 22-MAY-04:02 | 1.78 |
June | 0.292747E+10 | 0.42 | 9330.42 | 05-JUN-04:02 | 1.78 |
July | 0.288883E+10 | 0.41 | 9330.42 | 03-JUL-04:02 | 1.78 |
August | 0.307628E+10 | 0.42 | 9330.42 | 07-AUG-04:02 | 1.78 |
September | 0.253434E+10 | 0.39 | 9330.42 | 11-SEP-04:02 | 1.78 |
October | 0.266808E+10 | 0.38 | 8815.44 | 07-OCT-05:03 | 1.72 |
November | 0.174466E+10 | 0.32 | 3651.80 | 06-NOV-15:40 | 1.00 |
December | 0.151836E+10 | 0.30 | 3132.47 | 15-DEC-15:30 | 0.91 |
Annual Sum or Average | 0.262932E+11 | 0.36 | |||
Minimum of Months | 0.135546E+10 | 0.29 | 2337.40 | 0.77 | |
Maximum of Months | 0.307628E+10 | 0.42 | 9330.42 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140744E+10 | 0.28 | 2353.83 | 19-JAN-15:30 | 0.71 |
February | 0.134437E+10 | 0.28 | 2555.96 | 27-FEB-15:30 | 0.75 |
March | 0.158766E+10 | 0.30 | 2386.38 | 29-MAR-15:20 | 0.72 |
April | 0.179385E+10 | 0.31 | 3754.86 | 28-APR-15:30 | 0.93 |
May | 0.278695E+10 | 0.38 | 10618.34 | 22-MAY-04:02 | 1.76 |
June | 0.296043E+10 | 0.40 | 9627.11 | 05-JUN-04:02 | 1.65 |
July | 0.288825E+10 | 0.39 | 10819.48 | 03-JUL-04:02 | 1.78 |
August | 0.303828E+10 | 0.40 | 10819.48 | 28-AUG-04:02 | 1.78 |
September | 0.243707E+10 | 0.36 | 9568.52 | 11-SEP-04:02 | 1.65 |
October | 0.252304E+10 | 0.35 | 5872.46 | 07-OCT-05:03 | 1.21 |
November | 0.164270E+10 | 0.30 | 3531.58 | 02-NOV-14:50 | 0.89 |
December | 0.148603E+10 | 0.28 | 3003.32 | 15-DEC-15:00 | 0.82 |
Annual Sum or Average | 0.258961E+11 | 0.34 | |||
Minimum of Months | 0.134437E+10 | 0.28 | 2353.83 | 0.71 | |
Maximum of Months | 0.303828E+10 | 0.40 | 10819.48 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.48 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.58 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.63 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.76 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.05 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.06 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.15 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.16 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.11 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.64 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.83 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:02 | 2.06 | 2.06 | 57.75 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.58 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.64 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.48 | 58.48 | 1385.48 | 5050.51 | 23-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.08 | 58.08 | 1383.11 | 5042.58 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.12 | 58.12 | 1423.55 | 4927.82 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.22 | 58.22 | 1243.96 | 4652.33 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.69 | 58.69 | 1203.09 | 4360.95 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.46 | 58.46 | 1160.06 | 4060.79 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.54 | 58.54 | 1024.13 | 3860.87 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.55 | 58.55 | 1145.37 | 3945.82 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.51 | 58.51 | 1118.91 | 4183.57 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.75 | 57.75 | 1198.17 | 4514.46 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.29 | 58.29 | 1304.42 | 4805.33 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.17 | 58.17 | 1315.27 | 4995.41 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1241.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.75 | 57.75 | 1024.13 | 3860.87 | ||
Maximum of Months | 0.00 | 0.00 | 58.69 | 58.69 | 1423.55 | 5050.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.758676E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.872163E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106625E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.141858E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.248242E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.267533E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.278908E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.298438E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.246780E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.226875E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129048E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.969831E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.220437E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.758676E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.298438E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.663518E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.757660E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.900222E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125899E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.221195E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.237124E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.244223E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.250808E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.206586E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189397E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.105556E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.819677E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.189490E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.663518E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.250808E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.927991E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.916741E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.105451E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.134085E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234214E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.252425E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257906E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.263459E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.214697E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.195903E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.110133E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.102443E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.205519E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.916741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.263459E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162244E+10 | 0.208089E+11 | 0.125459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152947E+10 | 0.284080E+11 | 0.803169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182066E+10 | 0.338765E+11 | 0.118152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205471E+10 | 0.529547E+11 | 0.174268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330413E+10 | 0.918753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353929E+10 | 0.977950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361617E+10 | 0.102381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413904E+10 | 0.109033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340376E+10 | 0.932134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353608E+10 | 0.830979E+11 | 23483738.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227291E+10 | 0.462738E+11 | 0.224765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184529E+10 | 0.305381E+11 | 0.981229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326840E+11 | 0.790257E+12 | 0.464302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152947E+10 | 0.208089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413904E+10 | 0.109033E+12 | 0.125459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142206E+10 | 0.178933E+11 | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135546E+10 | 0.251871E+11 | 0.534478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158381E+10 | 0.302395E+11 | 0.564478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178753E+10 | 0.476976E+11 | 104504.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.278635E+10 | 0.828356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292747E+10 | 0.880677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288883E+10 | 0.915757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307628E+10 | 0.940631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253434E+10 | 0.797883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266808E+10 | 0.709235E+11 | 701556.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174466E+10 | 0.388674E+11 | 17852239.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151836E+10 | 0.260454E+11 | 0.791525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262932E+11 | 0.693184E+12 | 0.305055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135546E+10 | 0.178933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307628E+10 | 0.940631E+11 | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140744E+10 | 0.185582E+11 | 0.361540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134437E+10 | 0.264000E+11 | 0.181927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158766E+10 | 0.319046E+11 | 0.167265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179385E+10 | 0.507155E+11 | 36298098.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.278695E+10 | 0.879703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296043E+10 | 0.939928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288825E+10 | 0.969479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303828E+10 | 0.991921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243707E+10 | 0.833582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252304E+10 | 0.738953E+11 | 33823078.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164270E+10 | 0.398986E+11 | 0.263866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148603E+10 | 0.269249E+11 | 0.261787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258961E+11 | 0.729759E+12 | 0.100592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134437E+10 | 0.185582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303828E+10 | 0.991921E+11 | 0.361540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162244E+10 | 0.00 | 0.00 | 0.00 | 0.470973E+10 | 0.125459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152947E+10 | 0.00 | 0.00 | 0.00 | 0.638899E+10 | 0.803169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182066E+10 | 0.00 | 0.00 | 0.00 | 0.766035E+10 | 0.118152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205471E+10 | 0.00 | 0.00 | 0.00 | 0.119568E+11 | 0.174268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.330413E+10 | 0.00 | 0.00 | 0.00 | 0.215200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353929E+10 | 0.00 | 0.00 | 0.00 | 0.232141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.361617E+10 | 0.00 | 0.00 | 0.00 | 0.242746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413904E+10 | 0.00 | 0.00 | 0.00 | 0.257048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340376E+10 | 0.00 | 0.00 | 0.00 | 0.212743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353608E+10 | 0.00 | 0.00 | 0.00 | 0.191280E+11 | 23483738.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227291E+10 | 0.00 | 0.00 | 0.00 | 0.104071E+11 | 0.224765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184529E+10 | 0.00 | 0.00 | 0.00 | 0.687180E+10 | 0.981229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326840E+11 | 0.00 | 0.00 | 0.00 | 0.183110E+12 | 0.464302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152947E+10 | 0.00 | 0.00 | 0.00 | 0.470973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413904E+10 | 0.00 | 0.00 | 0.00 | 0.257048E+11 | 0.125459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142206E+10 | 0.00 | 0.00 | 0.00 | 0.407172E+10 | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135546E+10 | 0.00 | 0.00 | 0.00 | 0.568667E+10 | 0.534478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158381E+10 | 0.00 | 0.00 | 0.00 | 0.685393E+10 | 0.564478E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178753E+10 | 0.00 | 0.00 | 0.00 | 0.108023E+11 | 104504.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.278635E+10 | 0.00 | 0.00 | 0.00 | 0.193331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292747E+10 | 0.00 | 0.00 | 0.00 | 0.207850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288883E+10 | 0.00 | 0.00 | 0.00 | 0.215334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307628E+10 | 0.00 | 0.00 | 0.00 | 0.220045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.253434E+10 | 0.00 | 0.00 | 0.00 | 0.181243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266808E+10 | 0.00 | 0.00 | 0.00 | 0.162709E+11 | 701556.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174466E+10 | 0.00 | 0.00 | 0.00 | 0.879312E+10 | 17852239.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151836E+10 | 0.00 | 0.00 | 0.00 | 0.588688E+10 | 0.791525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262932E+11 | 0.00 | 0.00 | 0.00 | 0.160146E+12 | 0.305055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135546E+10 | 0.00 | 0.00 | 0.00 | 0.407172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.307628E+10 | 0.00 | 0.00 | 0.00 | 0.220045E+11 | 0.114141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140744E+10 | 0.00 | 0.00 | 0.00 | 0.425707E+10 | 0.361540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134437E+10 | 0.00 | 0.00 | 0.00 | 0.600376E+10 | 0.181927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158766E+10 | 0.00 | 0.00 | 0.00 | 0.728482E+10 | 0.167265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179385E+10 | 0.00 | 0.00 | 0.00 | 0.115783E+11 | 36298098.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.278695E+10 | 0.00 | 0.00 | 0.00 | 0.206345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296043E+10 | 0.00 | 0.00 | 0.00 | 0.222821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288825E+10 | 0.00 | 0.00 | 0.00 | 0.229023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303828E+10 | 0.00 | 0.00 | 0.00 | 0.233076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243707E+10 | 0.00 | 0.00 | 0.00 | 0.190326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252304E+10 | 0.00 | 0.00 | 0.00 | 0.170334E+11 | 33823078.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164270E+10 | 0.00 | 0.00 | 0.00 | 0.910676E+10 | 0.263866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148603E+10 | 0.00 | 0.00 | 0.00 | 0.614037E+10 | 0.261787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258961E+11 | 0.00 | 0.00 | 0.00 | 0.169564E+12 | 0.100592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134437E+10 | 0.00 | 0.00 | 0.00 | 0.425707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303828E+10 | 0.00 | 0.00 | 0.00 | 0.233076E+11 | 0.361540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133108E+10 | 0.142075E+10 | 0.00 | 24419160.71 | 4455185.15 | 0.00 | 0.108543E+11 | 0.00 | 0.52 |
February | 0.931116E+09 | 0.183088E+10 | 0.00 | 16764654.39 | 29454560.07 | 0.00 | 0.579651E+10 | 0.00 | 0.51 |
March | 0.110165E+10 | 0.283452E+10 | 0.00 | 22322428.35 | 42576843.38 | 0.00 | 0.798479E+10 | 0.00 | 0.58 |
April | 0.243311E+09 | 0.517494E+10 | 0.00 | 9939602.84 | 81431102.39 | 0.00 | 0.204594E+10 | 0.00 | 0.46 |
May | 0.00 | 0.134562E+11 | 0.00 | 0.00 | 0.146236E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.145123E+11 | 0.00 | 0.00 | 0.159247E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.157350E+11 | 0.00 | 0.00 | 0.262548E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.155375E+11 | 0.00 | 0.00 | 0.167119E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.128694E+11 | 0.00 | 0.00 | 0.215293E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 0.110135E+09 | 0.947972E+10 | 0.00 | 9395452.30 | 0.150213E+09 | 0.00 | 0.216344E+10 | 0.00 | 0.39 |
November | 0.677936E+09 | 0.370475E+10 | 0.00 | 22603615.83 | 29457929.08 | 0.00 | 0.564014E+10 | 0.00 | 0.59 |
December | 0.130207E+10 | 0.279871E+10 | 0.00 | 23344138.32 | 45603685.76 | 0.00 | 0.904082E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.569730E+10 | 0.993546E+11 | 0.00 | 0.128789E+09 | 0.133364E+10 | 0.00 | 0.435259E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.142075E+10 | 0.00 | 0.00 | 4455185.15 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.133108E+10 | 0.157350E+11 | 0.00 | 24419160.71 | 0.262548E+09 | 0.00 | 0.108543E+11 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.736111E+10 | 0.874726E+09 | 0.00 | 2716280.39 | 0.391517E+09 | 0.00 | 0.183009E+10 | 0.00 | 0.41 |
February | 0.403337E+10 | 0.114069E+10 | 0.00 | 1760101.87 | 0.475385E+09 | 1101776.00 | 0.103167E+10 | 0.00 | 0.40 |
March | 0.420433E+10 | 0.182948E+10 | 0.00 | 4371039.27 | 0.602673E+09 | 598052.85 | 0.249098E+10 | 0.00 | 0.44 |
April | 0.750284E+09 | 0.378170E+10 | 0.00 | 3491774.66 | 0.685174E+09 | 0.00 | 0.861824E+09 | 0.00 | 0.35 |
May | 0.00 | 0.119541E+11 | 0.00 | 0.00 | 0.187738E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.134441E+11 | 0.00 | 0.00 | 0.157870E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.148444E+11 | 0.00 | 0.00 | 0.350660E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.150398E+11 | 0.00 | 0.00 | 0.166162E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.120773E+11 | 0.00 | 0.00 | 0.348869E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.500257E+09 | 0.891485E+10 | 0.00 | 3958668.08 | 0.244617E+09 | 0.00 | 0.110509E+10 | 0.00 | 0.32 |
November | 0.210987E+10 | 0.310455E+10 | 0.00 | 5892545.88 | 0.384003E+09 | 0.00 | 0.205784E+10 | 0.00 | 0.42 |
December | 0.561364E+10 | 0.202406E+10 | 0.00 | 2735037.96 | 0.504106E+09 | 0.00 | 0.178582E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.245729E+11 | 0.890297E+11 | 0.00 | 24925448.11 | 0.449877E+10 | 1699828.84 | 0.111633E+11 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.874726E+09 | 0.00 | 0.00 | 0.157870E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.736111E+10 | 0.150398E+11 | 0.00 | 5892545.88 | 0.685174E+09 | 1101776.00 | 0.249098E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.777194E+10 | 0.634793E+09 | 0.00 | 714213.57 | 0.681775E+09 | 81763487.55 | 0.690794E+09 | 0.00 | 0.41 |
February | 0.400987E+10 | 0.900303E+09 | 0.00 | 678707.51 | 0.839333E+09 | 53364495.86 | 0.634434E+09 | 0.00 | 0.39 |
March | 0.486956E+10 | 0.161779E+10 | 0.00 | 2147803.35 | 0.840730E+09 | 25091831.56 | 0.137356E+10 | 0.00 | 0.44 |
April | 0.888254E+09 | 0.342195E+10 | 0.00 | 2886451.60 | 0.105855E+10 | 0.00 | 0.713042E+09 | 0.00 | 0.35 |
May | 0.00 | 0.115439E+11 | 0.00 | 0.00 | 0.287538E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.130168E+11 | 0.00 | 0.00 | 0.186235E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.144840E+11 | 0.00 | 0.00 | 0.329811E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.146120E+11 | 0.00 | 0.00 | 0.221475E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.115907E+11 | 0.00 | 0.00 | 0.619581E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.567507E+09 | 0.860991E+10 | 0.00 | 2794672.16 | 0.388272E+09 | 0.00 | 0.812450E+09 | 0.00 | 0.31 |
November | 0.244513E+10 | 0.257300E+10 | 0.00 | 3181697.08 | 0.989329E+09 | 937468.54 | 0.122533E+10 | 0.00 | 0.41 |
December | 0.633303E+10 | 0.145807E+10 | 47646.88 | 772061.13 | 0.109820E+10 | 47144605.88 | 0.398942E+09 | 17266.90 | 0.40 |
Annual Sum or Average | 0.268853E+11 | 0.844632E+11 | 47646.88 | 13175606.40 | 0.754082E+10 | 0.208302E+09 | 0.584855E+10 | 17266.90 | 0.33 |
Minimum of Months | 0.00 | 0.634793E+09 | 0.00 | 0.00 | 0.186235E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.777194E+10 | 0.146120E+11 | 47646.88 | 3181697.08 | 0.109820E+10 | 81763487.55 | 0.137356E+10 | 17266.90 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135573E+10 | 0.138019E+09 | 73220.14 | 15553.04 | 0.151152E+09 | 0.447762E+09 | 4491935.33 | 2099.49 | 0.41 |
February | 0.766751E+09 | 0.189663E+09 | 0.00 | 25091.60 | 0.196998E+09 | 0.184941E+09 | 40442306.17 | 1802.47 | 0.39 |
March | 0.106788E+10 | 0.416072E+09 | 0.00 | 257080.83 | 0.168699E+09 | 0.167628E+09 | 81065891.43 | 0.00 | 0.45 |
April | 0.234638E+09 | 0.921567E+09 | 0.00 | 650517.78 | 0.218837E+09 | 888548.22 | 0.108359E+09 | 0.00 | 0.39 |
May | 0.00 | 0.348572E+10 | 0.00 | 0.00 | 35044385.62 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.425057E+10 | 0.00 | 0.00 | 38557631.29 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.470633E+10 | 0.00 | 0.00 | 54606695.82 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.449120E+10 | 0.00 | 0.00 | 49045325.47 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.322845E+10 | 0.00 | 0.00 | 0.146590E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.160879E+09 | 0.239894E+10 | 0.00 | 479796.13 | 93126114.20 | 1839721.97 | 0.127469E+09 | 0.00 | 0.37 |
November | 0.623920E+09 | 0.647170E+09 | 1127512.01 | 400910.62 | 0.187192E+09 | 21975989.67 | 0.121345E+09 | 11657.18 | 0.42 |
December | 0.110401E+10 | 0.355406E+09 | 893705.74 | 50496.49 | 0.221661E+09 | 0.311207E+09 | 17229746.17 | 19576.27 | 0.40 |
Annual Sum or Average | 0.531381E+10 | 0.252291E+11 | 2094437.88 | 1879446.49 | 0.156151E+10 | 0.113624E+10 | 0.500403E+09 | 35135.41 | 0.39 |
Minimum of Months | 0.00 | 0.138019E+09 | 0.00 | 0.00 | 35044385.62 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.135573E+10 | 0.470633E+10 | 1127512.01 | 650517.78 | 0.221661E+09 | 0.447762E+09 | 0.127469E+09 | 19576.27 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126462E+10 | 0.134528E+09 | 164590.49 | 24184.12 | 0.117897E+09 | 0.226441E+09 | 42816264.60 | 3074.70 | 0.55 |
February | 0.676300E+09 | 0.221985E+09 | 75520.38 | 171079.45 | 0.134101E+09 | 80479642.51 | 85445922.12 | 2167.43 | 0.54 |
March | 0.712814E+09 | 0.465401E+09 | 0.00 | 819008.84 | 0.102725E+09 | 0.115047E+09 | 0.313160E+09 | 0.00 | 0.65 |
April | 0.129418E+09 | 0.937702E+09 | 0.00 | 1045244.14 | 0.161055E+09 | 1419223.91 | 0.234521E+09 | 0.00 | 0.60 |
May | 0.00 | 0.297683E+10 | 0.00 | 0.00 | 37261471.28 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.350800E+10 | 0.00 | 0.00 | 34514703.88 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.393348E+10 | 0.00 | 0.00 | 58959855.97 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.368553E+10 | 0.00 | 0.00 | 62719382.56 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.263579E+10 | 0.00 | 0.00 | 0.178793E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.124079E+09 | 0.205742E+10 | 0.00 | 487909.48 | 98638081.81 | 1607620.97 | 0.122643E+09 | 0.00 | 0.50 |
November | 0.431913E+09 | 0.575061E+09 | 369075.88 | 676028.48 | 0.155495E+09 | 7041882.68 | 0.221608E+09 | 6410.58 | 0.57 |
December | 0.973220E+09 | 0.303004E+09 | 252289.94 | 141907.05 | 0.167773E+09 | 0.185722E+09 | 56847024.02 | 10493.74 | 0.54 |
Annual Sum or Average | 0.431236E+10 | 0.214347E+11 | 861476.70 | 3365361.55 | 0.130993E+10 | 0.617758E+09 | 0.107704E+10 | 22146.44 | 0.53 |
Minimum of Months | 0.00 | 0.134528E+09 | 0.00 | 0.00 | 34514703.88 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.126462E+10 | 0.393348E+10 | 369075.88 | 1045244.14 | 0.178793E+09 | 0.226441E+09 | 0.313160E+09 | 10493.74 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.861706E+09 | 0.371101E+09 | 0.00 | 4137645.22 | 90203804.83 | 0.184748E+09 | 0.152655E+10 | 0.00 | 0.62 |
February | 0.499575E+09 | 0.596887E+09 | 0.00 | 2354816.13 | 0.109270E+09 | 75208103.89 | 0.763571E+09 | 1149.15 | 0.60 |
March | 0.792747E+09 | 0.691453E+09 | 0.00 | 2235773.40 | 0.116003E+09 | 0.138936E+09 | 0.701888E+09 | 0.00 | 0.61 |
April | 0.196028E+09 | 0.117269E+10 | 0.00 | 1262855.13 | 0.209296E+09 | 852579.61 | 0.220538E+09 | 0.00 | 0.48 |
May | 0.00 | 0.353684E+10 | 0.00 | 0.00 | 42980369.47 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.407648E+10 | 0.00 | 0.00 | 49327975.08 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.464098E+10 | 0.00 | 0.00 | 67156574.38 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.491502E+10 | 0.00 | 0.00 | 58547471.76 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.402754E+10 | 0.00 | 0.00 | 0.136408E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.130415E+09 | 0.359298E+10 | 0.00 | 1262131.48 | 60648348.99 | 309617.71 | 0.269536E+09 | 0.00 | 0.55 |
November | 0.343936E+09 | 0.129878E+10 | 91431.60 | 3871225.71 | 0.114595E+09 | 5090031.81 | 0.966160E+09 | 7767.17 | 0.74 |
December | 0.774658E+09 | 0.910104E+09 | 189847.89 | 3962487.22 | 0.121099E+09 | 0.153617E+09 | 0.107606E+10 | 12541.41 | 0.66 |
Annual Sum or Average | 0.359907E+10 | 0.298309E+11 | 281279.50 | 19086934.28 | 0.117554E+10 | 0.558761E+09 | 0.552430E+10 | 21457.73 | 0.52 |
Minimum of Months | 0.00 | 0.371101E+09 | 0.00 | 0.00 | 42980369.47 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.861706E+09 | 0.491502E+10 | 189847.89 | 4137645.22 | 0.209296E+09 | 0.184748E+09 | 0.152655E+10 | 12541.41 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116345E+10 | 0.138049E+09 | 182104.20 | 419429.66 | 0.148597E+09 | 0.315688E+09 | 0.230178E+09 | 3214.44 | 0.62 |
February | 0.667750E+09 | 0.212610E+09 | 83946.00 | 418199.10 | 0.183336E+09 | 0.130258E+09 | 0.148167E+09 | 2202.82 | 0.61 |
March | 0.834918E+09 | 0.325231E+09 | 0.00 | 1150974.47 | 0.190173E+09 | 0.145358E+09 | 0.349626E+09 | 0.00 | 0.72 |
April | 0.196668E+09 | 0.866394E+09 | 0.00 | 969819.43 | 0.244035E+09 | 1919481.58 | 0.168286E+09 | 0.00 | 0.62 |
May | 0.00 | 0.268316E+10 | 0.00 | 0.00 | 0.112672E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.322730E+10 | 0.00 | 0.00 | 60110407.48 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.351205E+10 | 0.00 | 0.00 | 79933977.45 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.352931E+10 | 0.00 | 0.00 | 0.118525E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.252026E+10 | 0.00 | 0.00 | 0.265970E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.167308E+09 | 0.196329E+10 | 0.00 | 505538.92 | 0.144280E+09 | 1731365.79 | 0.112881E+09 | 0.00 | 0.53 |
November | 0.522189E+09 | 0.544877E+09 | 403111.90 | 802133.76 | 0.227418E+09 | 21153213.30 | 0.227392E+09 | 6775.82 | 0.66 |
December | 0.986689E+09 | 0.326328E+09 | 850469.73 | 432736.00 | 0.231081E+09 | 0.235431E+09 | 0.142962E+09 | 13428.40 | 0.62 |
Annual Sum or Average | 0.453897E+10 | 0.198488E+11 | 1519631.83 | 4698831.34 | 0.200613E+10 | 0.851539E+09 | 0.137949E+10 | 25621.48 | 0.56 |
Minimum of Months | 0.00 | 0.138049E+09 | 0.00 | 0.00 | 60110407.48 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.116345E+10 | 0.352931E+10 | 850469.73 | 1150974.47 | 0.265970E+09 | 0.315688E+09 | 0.349626E+09 | 13428.40 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196626E+10 | 0.123522E+09 | 0.00 | 40834.15 | 99361239.95 | 65948525.86 | 68621835.51 | 0.00 | 0.41 |
February | 0.108428E+10 | 0.152497E+09 | 0.00 | 20852.79 | 0.129198E+09 | 45937585.73 | 47365015.96 | 0.00 | 0.40 |
March | 0.138813E+10 | 0.271587E+09 | 0.00 | 50139.48 | 0.183186E+09 | 50290308.46 | 39483847.59 | 0.00 | 0.44 |
April | 0.279720E+09 | 0.650412E+09 | 0.00 | 330229.32 | 0.208101E+09 | 0.00 | 56815092.13 | 0.00 | 0.33 |
May | 0.00 | 0.263021E+10 | 0.00 | 0.00 | 32733529.29 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.322638E+10 | 0.00 | 0.00 | 34732756.76 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.370270E+10 | 0.00 | 0.00 | 55408370.30 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.371842E+10 | 0.00 | 0.00 | 35268913.13 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.278842E+10 | 0.00 | 0.00 | 45435677.39 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 0.149922E+09 | 0.202046E+10 | 0.00 | 767465.46 | 37523712.70 | 0.00 | 0.199115E+09 | 0.00 | 0.34 |
November | 0.746129E+09 | 0.586916E+09 | 0.00 | 673247.35 | 57472412.33 | 0.00 | 0.215005E+09 | 0.00 | 0.43 |
December | 0.167153E+10 | 0.364241E+09 | 0.00 | 72276.62 | 98765976.56 | 27190202.55 | 23937887.13 | 0.00 | 0.41 |
Annual Sum or Average | 0.728597E+10 | 0.202358E+11 | 0.00 | 1955045.17 | 0.101719E+10 | 0.189367E+09 | 0.650344E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.123522E+09 | 0.00 | 0.00 | 32733529.29 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.196626E+10 | 0.371842E+10 | 0.00 | 767465.46 | 0.208101E+09 | 65948525.86 | 0.215005E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133717E+10 | 0.132403E+09 | 0.00 | 221671.26 | 55249997.12 | 18819896.69 | 0.265048E+09 | 0.00 | 0.51 |
February | 0.738457E+09 | 0.176622E+09 | 0.00 | 243790.63 | 72548147.28 | 12955202.63 | 0.159419E+09 | 0.00 | 0.51 |
March | 0.842291E+09 | 0.375586E+09 | 0.00 | 776301.01 | 59809491.93 | 26861472.55 | 0.297623E+09 | 0.00 | 0.58 |
April | 0.135874E+09 | 0.748097E+09 | 0.00 | 886610.62 | 91205197.25 | 0.00 | 0.192555E+09 | 0.00 | 0.51 |
May | 0.00 | 0.234232E+10 | 0.00 | 0.00 | 25249441.23 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.274178E+10 | 0.00 | 0.00 | 26708126.29 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.315849E+10 | 0.00 | 0.00 | 42627963.65 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.306811E+10 | 0.00 | 0.00 | 27133841.67 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.229572E+10 | 0.00 | 0.00 | 34955556.24 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 91577982.17 | 0.173559E+10 | 0.00 | 782234.78 | 28313386.55 | 0.00 | 0.199032E+09 | 0.00 | 0.46 |
November | 0.400593E+09 | 0.516355E+09 | 0.00 | 1435017.22 | 31249936.92 | 0.00 | 0.408180E+09 | 0.00 | 0.58 |
December | 0.108857E+10 | 0.306251E+09 | 0.00 | 477847.46 | 59186826.94 | 17311456.60 | 0.233147E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.463454E+10 | 0.175973E+11 | 0.00 | 4823472.97 | 0.554238E+09 | 75948028.47 | 0.175500E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.132403E+09 | 0.00 | 0.00 | 25249441.23 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.133717E+10 | 0.315849E+10 | 0.00 | 1435017.22 | 91205197.25 | 26861472.55 | 0.408180E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124661E+10 | 0.356614E+09 | 215241.62 | 1814306.79 | 28602816.13 | 0.524998E+09 | 0.764620E+09 | 2350.95 | 0.55 |
February | 0.798053E+09 | 0.538881E+09 | 471636.32 | 846752.50 | 28033066.45 | 0.296554E+09 | 0.257314E+09 | 470.03 | 0.54 |
March | 0.101108E+10 | 0.636063E+09 | 8040.04 | 727691.21 | 67561749.45 | 0.492457E+09 | 0.199028E+09 | 30.48 | 0.54 |
April | 0.235579E+09 | 0.105251E+10 | 964070.23 | 623161.58 | 0.163646E+09 | 78412831.90 | 74184063.75 | 5611.79 | 0.43 |
May | 0.00 | 0.337030E+10 | 0.00 | 0.00 | 43119867.25 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.400911E+10 | 0.00 | 0.00 | 44232945.30 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.457646E+10 | 0.00 | 0.00 | 56634378.41 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.499202E+10 | 0.00 | 0.00 | 39027729.99 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.392264E+10 | 0.00 | 0.00 | 61534992.96 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.151081E+09 | 0.342032E+10 | 0.00 | 1171505.37 | 40262669.58 | 14090561.13 | 0.235381E+09 | 0.00 | 0.54 |
November | 0.385639E+09 | 0.120831E+10 | 0.00 | 3719278.55 | 34059294.33 | 0.140435E+09 | 0.878771E+09 | 0.00 | 0.73 |
December | 0.101908E+10 | 0.862113E+09 | 29364.39 | 2695203.92 | 52828145.33 | 0.488566E+09 | 0.725017E+09 | 405.49 | 0.63 |
Annual Sum or Average | 0.484712E+10 | 0.289453E+11 | 1688352.59 | 11597899.93 | 0.659544E+09 | 0.203551E+10 | 0.313431E+10 | 8868.74 | 0.49 |
Minimum of Months | 0.00 | 0.356614E+09 | 0.00 | 0.00 | 28033066.45 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.124661E+10 | 0.499202E+10 | 964070.23 | 3719278.55 | 0.163646E+09 | 0.524998E+09 | 0.878771E+09 | 5611.79 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137730E+10 | 0.156629E+09 | 0.00 | 555623.19 | 49267655.30 | 30032674.53 | 0.296512E+09 | 0.00 | 0.54 |
February | 0.797518E+09 | 0.211763E+09 | 0.00 | 340243.12 | 67808584.85 | 23794684.87 | 0.132774E+09 | 0.00 | 0.54 |
March | 0.962315E+09 | 0.289757E+09 | 0.00 | 781685.89 | 97474623.90 | 28670038.23 | 0.237345E+09 | 0.00 | 0.60 |
April | 0.186982E+09 | 0.744719E+09 | 0.00 | 627153.01 | 0.102199E+09 | 0.00 | 0.108987E+09 | 0.00 | 0.50 |
May | 0.00 | 0.212750E+10 | 0.00 | 0.00 | 30762354.27 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.253500E+10 | 0.00 | 0.00 | 19194946.96 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.282036E+10 | 0.00 | 0.00 | 32837860.91 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.298032E+10 | 0.00 | 0.00 | 25127737.43 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.225393E+10 | 0.00 | 0.00 | 28234765.50 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.108965E+09 | 0.170531E+10 | 0.00 | 782281.43 | 18893688.48 | 0.00 | 0.181846E+09 | 0.00 | 0.46 |
November | 0.521195E+09 | 0.530563E+09 | 0.00 | 1137987.28 | 30875990.82 | 0.00 | 0.313705E+09 | 0.00 | 0.60 |
December | 0.120094E+10 | 0.364205E+09 | 0.00 | 563662.60 | 52977089.73 | 16906839.80 | 0.200286E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.515522E+10 | 0.167201E+11 | 0.00 | 4788636.51 | 0.555654E+09 | 99404237.43 | 0.147146E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.156629E+09 | 0.00 | 0.00 | 18893688.48 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.137730E+10 | 0.298032E+10 | 0.00 | 1137987.28 | 0.102199E+09 | 30032674.53 | 0.313705E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167499E+10 | 0.177499E+09 | 0.00 | 43910.06 | 0.104706E+09 | 0.170222E+09 | 68491253.57 | 0.00 | 0.41 |
February | 0.932322E+09 | 0.232069E+09 | 0.00 | 59662.03 | 0.129452E+09 | 56344789.81 | 68837509.34 | 0.00 | 0.40 |
March | 0.118649E+10 | 0.473857E+09 | 0.00 | 256825.37 | 0.106490E+09 | 70659246.06 | 0.127407E+09 | 0.00 | 0.45 |
April | 0.232780E+09 | 0.102538E+10 | 0.00 | 572208.21 | 0.118581E+09 | 0.00 | 0.104896E+09 | 0.00 | 0.39 |
May | 0.00 | 0.363840E+10 | 0.00 | 0.00 | 30766923.03 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.444007E+10 | 0.00 | 0.00 | 33722989.55 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.487954E+10 | 0.00 | 0.00 | 55017708.03 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.467850E+10 | 0.00 | 0.00 | 36177995.44 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.341173E+10 | 0.00 | 0.00 | 53993338.33 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.163222E+09 | 0.251575E+10 | 0.00 | 591199.89 | 51896762.58 | 0.00 | 0.156482E+09 | 0.00 | 0.37 |
November | 0.696693E+09 | 0.715073E+09 | 0.00 | 541861.15 | 0.106239E+09 | 604040.48 | 0.156787E+09 | 0.00 | 0.42 |
December | 0.143648E+10 | 0.416720E+09 | 0.00 | 73190.20 | 0.150257E+09 | 98433909.80 | 18837380.57 | 0.00 | 0.40 |
Annual Sum or Average | 0.632298E+10 | 0.266046E+11 | 0.00 | 2138856.90 | 0.977300E+09 | 0.396264E+09 | 0.701738E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.177499E+09 | 0.00 | 0.00 | 30766923.03 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.167499E+10 | 0.487954E+10 | 0.00 | 591199.89 | 0.150257E+09 | 0.170222E+09 | 0.156787E+09 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141231E+10 | 0.144979E+09 | 0.00 | 131591.25 | 96791835.62 | 84519703.39 | 0.143654E+09 | 0.00 | 0.55 |
February | 0.725487E+09 | 0.229907E+09 | 0.00 | 254466.16 | 98202507.30 | 28770000.84 | 0.159424E+09 | 0.00 | 0.56 |
March | 0.833598E+09 | 0.470553E+09 | 0.00 | 932579.57 | 76398447.17 | 58838241.61 | 0.346422E+09 | 0.00 | 0.65 |
April | 0.141877E+09 | 0.963419E+09 | 0.00 | 961720.91 | 0.115420E+09 | 0.00 | 0.239672E+09 | 0.00 | 0.60 |
May | 0.00 | 0.305059E+10 | 0.00 | 0.00 | 27990601.63 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.359959E+10 | 0.00 | 0.00 | 32095212.63 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.403072E+10 | 0.00 | 0.00 | 48210500.91 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.377141E+10 | 0.00 | 0.00 | 44895065.85 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.273158E+10 | 0.00 | 0.00 | 91799793.05 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.124027E+09 | 0.209734E+10 | 0.00 | 562997.70 | 59968822.77 | 0.00 | 0.153101E+09 | 0.00 | 0.50 |
November | 0.466602E+09 | 0.597296E+09 | 13923.37 | 877968.15 | 98105555.99 | 461594.52 | 0.295178E+09 | 833.41 | 0.58 |
December | 0.112401E+10 | 0.317274E+09 | 0.00 | 287219.84 | 0.133689E+09 | 73218067.08 | 0.139273E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.482791E+10 | 0.220047E+11 | 13923.37 | 4008543.59 | 0.923568E+09 | 0.245808E+09 | 0.147672E+10 | 833.41 | 0.53 |
Minimum of Months | 0.00 | 0.144979E+09 | 0.00 | 0.00 | 27990601.63 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.141231E+10 | 0.403072E+10 | 13923.37 | 961720.91 | 0.133689E+09 | 84519703.39 | 0.346422E+09 | 833.41 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936836E+09 | 0.420452E+09 | 0.00 | 4985478.34 | 49419213.12 | 65676457.96 | 0.183542E+10 | 0.00 | 0.66 |
February | 0.558169E+09 | 0.670214E+09 | 0.00 | 2805439.01 | 47571099.37 | 26535358.00 | 0.856486E+09 | 0.00 | 0.62 |
March | 0.890711E+09 | 0.762779E+09 | 0.00 | 2372255.70 | 66347047.55 | 38926373.32 | 0.736890E+09 | 0.00 | 0.60 |
April | 0.200408E+09 | 0.130762E+10 | 0.00 | 1078598.43 | 0.104350E+09 | 0.00 | 0.193889E+09 | 0.00 | 0.47 |
May | 0.00 | 0.370119E+10 | 0.00 | 0.00 | 30764202.16 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.426502E+10 | 0.00 | 0.00 | 36591840.99 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.482666E+10 | 0.00 | 0.00 | 56385726.95 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.514964E+10 | 0.00 | 0.00 | 36174796.05 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.425316E+10 | 0.00 | 0.00 | 49163827.20 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.130608E+09 | 0.376996E+10 | 0.00 | 1403883.50 | 32963861.98 | 0.00 | 0.297135E+09 | 0.00 | 0.56 |
November | 0.364978E+09 | 0.136795E+10 | 0.00 | 4266518.50 | 54408160.98 | 271640.73 | 0.108478E+10 | 0.00 | 0.76 |
December | 0.908964E+09 | 0.983219E+09 | 0.00 | 4600639.76 | 65622056.79 | 44635921.84 | 0.128025E+10 | 0.00 | 0.69 |
Annual Sum or Average | 0.399067E+10 | 0.314779E+11 | 0.00 | 21512813.23 | 0.629762E+09 | 0.176046E+09 | 0.628485E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.420452E+09 | 0.00 | 0.00 | 30764202.16 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.936836E+09 | 0.514964E+10 | 0.00 | 4985478.34 | 0.104350E+09 | 65676457.96 | 0.183542E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134077E+10 | 0.171617E+09 | 0.00 | 609260.43 | 0.100198E+09 | 0.121046E+09 | 0.276079E+09 | 0.00 | 0.59 |
February | 0.749225E+09 | 0.262459E+09 | 0.00 | 491336.15 | 0.105972E+09 | 45812256.17 | 0.172691E+09 | 0.00 | 0.60 |
March | 0.946518E+09 | 0.379566E+09 | 0.00 | 1107657.68 | 0.118266E+09 | 60989899.65 | 0.317256E+09 | 0.00 | 0.69 |
April | 0.201658E+09 | 0.987765E+09 | 0.00 | 843229.27 | 0.129752E+09 | 0.00 | 0.135964E+09 | 0.00 | 0.60 |
May | 0.00 | 0.287671E+10 | 0.00 | 0.00 | 36579321.40 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.341848E+10 | 0.00 | 0.00 | 27760250.08 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.369243E+10 | 0.00 | 0.00 | 37079937.23 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.375840E+10 | 0.00 | 0.00 | 41248081.37 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.270469E+10 | 0.00 | 0.00 | 0.122442E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.151660E+09 | 0.209682E+10 | 0.00 | 561629.40 | 54917839.27 | 0.00 | 0.140358E+09 | 0.00 | 0.52 |
November | 0.584711E+09 | 0.615239E+09 | 14873.29 | 884908.69 | 0.119041E+09 | 954191.20 | 0.235575E+09 | 521.95 | 0.63 |
December | 0.117627E+10 | 0.393685E+09 | 0.00 | 533403.59 | 0.136638E+09 | 73378046.19 | 0.171036E+09 | 0.00 | 0.60 |
Annual Sum or Average | 0.515081E+10 | 0.213579E+11 | 14873.29 | 5031425.21 | 0.102989E+10 | 0.302180E+09 | 0.144896E+10 | 521.95 | 0.55 |
Minimum of Months | 0.00 | 0.171617E+09 | 0.00 | 0.00 | 27760250.08 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.134077E+10 | 0.375840E+10 | 14873.29 | 1107657.68 | 0.136638E+09 | 0.121046E+09 | 0.317256E+09 | 521.95 | 0.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.232389E+12 | 0.445779E+10 | 0.00 | 0.155679E+12 | 0.702990E+11 |
February | 0.243528E+12 | 0.269120E+10 | 0.00 | 0.107376E+12 | 0.980745E+11 |
March | 0.268592E+12 | 0.237489E+10 | 0.00 | 0.122812E+12 | 0.117820E+12 |
April | 0.296841E+12 | -0.139995E+10 | 0.00 | 0.305780E+11 | 0.185705E+12 |
May | 0.291299E+12 | -0.864984E+10 | 0.00 | -0.744814E+11 | 0.324169E+12 |
June | 0.288828E+12 | -0.873029E+10 | 0.00 | -0.852118E+11 | 0.346137E+12 |
July | 0.298904E+12 | -0.108533E+11 | 0.00 | -0.951315E+11 | 0.359615E+12 |
August | 0.278685E+12 | -0.111373E+11 | 0.00 | -0.947679E+11 | 0.373306E+12 |
September | 0.241535E+12 | -0.930830E+10 | 0.00 | -0.757104E+11 | 0.314791E+12 |
October | 0.251608E+12 | -0.664513E+10 | 0.00 | -0.223623E+11 | 0.280349E+12 |
November | 0.202183E+12 | 0.248662E+09 | 0.00 | 0.866054E+11 | 0.153347E+12 |
December | 0.208530E+12 | 0.302571E+10 | 0.00 | 0.143548E+12 | 0.102407E+12 |
Annual Sum or Average | 0.310292E+13 | -0.439259E+11 | 0.00 | 0.198932E+12 | 0.272602E+13 |
Minimum of Months | 0.202183E+12 | -0.111373E+11 | 0.00 | -0.951315E+11 | 0.702990E+11 |
Maximum of Months | 0.298904E+12 | 0.445779E+10 | 0.00 | 0.155679E+12 | 0.373306E+12 |