Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2024-07-03 12:20:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1880.12 | 377.37 | 377.37 |
Net Site Energy | 1880.12 | 377.37 | 377.37 |
Total Source Energy | 5954.35 | 1195.13 | 1195.13 |
Net Source Energy | 5954.35 | 1195.13 | 1195.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 642.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 98.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 642.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 98.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 642.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 300.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 98.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 377.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 157.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 377.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1880.123 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1880.123 | 100.00 |
Total On-Site and Utility Electric Sources | 1880.123 | 100.00 |
Total Electricity End Uses | 1880.123 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 17.83 |
Time Setpoint Not Met During Occupied Cooling | 496.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1395.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-15:30 | - | - | - | - | - | - | - | - | - | - | - | 24-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75613.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14718.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2887.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 161987.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 75613.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14718.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2887.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 5.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2035.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 951.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 312.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 124.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5954.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1195.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 408.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1195.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.65 | 0.283089 | 0.290000 | 0.767750 | 0.754905 | 0.500000 | 0.001346 |
CORE_MID VAV BOX COMPONENT | 2.15 | 0.348949 | 0.348000 | 0.747416 | 0.930532 | 0.500000 | 0.001092 |
CORE_TOP VAV BOX COMPONENT | 2.33 | 0.321768 | 0.336000 | 0.782603 | 0.858049 | 0.500000 | 0.001184 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.726893 | 0.217352 | 0.227000 | 0.165005 | 0.579606 | 0.500000 | 0.001753 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.698691 | 0.143156 | 0.200000 | 0.139738 | 0.381749 | 0.500000 | 0.002661 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.743588 | 0.212472 | 0.222000 | 0.165077 | 0.566592 | 0.500000 | 0.001793 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.791447 | 0.126370 | 0.200000 | 0.158289 | 0.336987 | 0.500000 | 0.003015 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.616396 | 0.256315 | 0.263000 | 0.162112 | 0.683507 | 0.500000 | 0.001486 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.620875 | 0.161098 | 0.200000 | 0.124175 | 0.429595 | 0.500000 | 0.002365 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.625243 | 0.252689 | 0.259000 | 0.161938 | 0.673836 | 0.500000 | 0.001508 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.656683 | 0.152304 | 0.200000 | 0.131337 | 0.406143 | 0.500000 | 0.002502 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.632663 | 0.249725 | 0.249000 | 0.157533 | 0.665933 | 0.500000 | 0.001526 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.671364 | 0.148983 | 0.200000 | 0.134273 | 0.397288 | 0.500000 | 0.002557 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.642850 | 0.245767 | 0.245000 | 0.157498 | 0.655380 | 0.500000 | 0.001550 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.716777 | 0.139535 | 0.200000 | 0.143355 | 0.372092 | 0.500000 | 0.002731 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25611.65 |
CORE_MID VAV BOX REHEAT COIL | 24933.31 |
CORE_TOP VAV BOX REHEAT COIL | 26107.14 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 9846.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 6461.42 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 9822.98 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 6470.35 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6304.98 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4170.04 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6269.96 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4381.30 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 7751.51 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5104.56 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 7712.03 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5124.47 |
PACU_VAV_BOT HEATING COIL | 3853.58 |
PACU_VAV_MID HEATING COIL | 5111.06 |
PACU_VAV_TOP HEATING COIL | 2853.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.58 | 1.35 | 5.17 | 1.35 | 4.69 | 4.69 | 0.300000 | 0.287343 | 4.69 |
PACU_VAV_MID | 2.41 | 1.34 | 4.81 | 1.34 | 4.26 | 4.26 | 0.300000 | 0.314564 | 4.26 |
PACU_VAV_TOP | 2.64 | 1.41 | 5.29 | 1.77 | 5.02 | 5.02 | 0.300000 | 0.353146 | 5.02 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.69 |
PACU_VAV_MID_OA_CONTROLLER | 4.26 |
PACU_VAV_TOP_OA_CONTROLLER | 5.02 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.69 | 115634.07 | 0.703782 | 1.56 | 38540.84 | 0.703782 |
PACU_VAV_MID COOLING COIL | 4.26 | 105788.60 | 0.701083 | 1.42 | 35259.34 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 5.02 | 120664.38 | 0.710999 | 1.67 | 40217.44 | 0.710999 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.69 |
PACU_VAV_MID FAN | 4.26 |
PACU_VAV_TOP FAN | 5.02 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.57_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2430E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2816E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5513E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5832E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0952E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1195E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8128E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7132E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5844E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8594E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1994E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7391E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2446E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2915E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5531E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5940E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0971E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1281E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8421E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7183E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5486E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4909E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6288E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2786E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4032E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4180E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1752E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1859E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9731E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9772E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8262E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8624E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4028E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4318E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0970E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1175E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5772E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4440E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0150E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1155E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8150E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.6976E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8257E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8616E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4019E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4296E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0954E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1115E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8750E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2864E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3980E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9772E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6527E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8452E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7706E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7988E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4152E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4427E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3641E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3800E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.2824E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.7035E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1001 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.8981E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.7833E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.5721E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6921E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6309E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4166E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4135E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5245E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2155E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9695E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9207E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3682E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5318E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1628E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1500E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7533E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2188E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2999E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9237E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5760E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8012E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.2819E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.7030E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1001 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.8976E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.7826E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5717E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6920E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6307E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4164E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4133E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5242E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2153E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9696E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9206E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3683E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5317E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1626E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1499E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7533E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2187E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2999E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9236E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5757E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8010E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36707.00360 | 36707.00360 | 2.64741 | 2.64741 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2407.51529 | 2407.51529 | 0.10233 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29805.55737 | 29805.55737 | 2.14775 | 2.14775 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 9025.75220 | 9025.75220 | 0.38047 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32019.64257 | 32019.64257 | 2.32918 | 2.32918 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 17155.06145 | 17155.06145 | 0.72767 | 0.72767 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9992.24557 | 9992.24557 | 0.72689 | 0.72689 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.15033 | 1.71652E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 7534.55833 | 7534.55833 | 0.29517 | 0.29517 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9604.60659 | 9604.60659 | 0.69869 | 0.69869 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 4944.27842 | 4944.27842 | 0.19369 | 0.19369 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10221.75294 | 10221.75294 | 0.74359 | 0.74359 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 7516.22107 | 7516.22107 | 0.29446 | 0.29446 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10879.71699 | 10879.71699 | 0.79145 | 0.79145 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 4951.03952 | 4951.03952 | 0.19396 | 0.19396 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8473.52524 | 8473.52524 | 0.61640 | 0.61640 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 4447.02053 | 4447.02053 | 0.18900 | 0.18900 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8535.13675 | 8535.13675 | 0.62087 | 0.62087 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 2940.15995 | 2940.15995 | 0.12500 | 0.12500 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8595.13149 | 8595.13149 | 0.62524 | 0.62524 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 4422.52908 | 4422.52908 | 0.18795 | 0.18795 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9027.39400 | 9027.39400 | 0.65668 | 0.65668 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.03867 | 1.71650E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 2956.35796 | 2956.35796 | 0.12570 | 0.12570 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8696.97504 | 8696.97504 | 0.63266 | 0.63266 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5459.74461 | 5459.74461 | 0.23236 | 0.23236 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9229.05052 | 9229.05052 | 0.67136 | 0.67136 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3594.59992 | 3594.59992 | 0.15302 | 0.15302 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8837.02012 | 8837.02012 | 0.64285 | 0.64285 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5432.11130 | 5432.11130 | 0.23118 | 0.23118 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9853.33335 | 9853.33335 | 0.71678 | 0.71678 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3608.53572 | 3608.53572 | 0.15361 | 0.15361 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76246.70 | 4.68887 | 4.68887 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 5214.58 | 1.05235 | 1.05235 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70196.87 | 4.26011 | 4.26011 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 5920.79 | 1.19487 | 1.19487 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80595.03 | 5.01610 | 5.01610 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 5912.49 | 1.77141 | 1.77141 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64741 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28309 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76775 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75490 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34586E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25611.65090 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14775 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34895 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74742 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93053 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09185E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24933.30683 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32918 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32177 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78260 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85805 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18408E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26107.13580 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72689 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21735 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16500 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57961 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75292E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9846.78300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69869 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14316 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13974 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38175 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66143E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6461.42426 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74359 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21247 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16508 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56659 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79318E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9822.98001 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79145 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12637 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15829 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33699 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01495E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6470.34937 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61640 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25631 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16211 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68351 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48645E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6304.98381 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62087 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16110 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12417 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42960 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36502E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4170.03805 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62524 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25269 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16194 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67384 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50778E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6269.96172 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65668 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15230 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13134 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40614 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50158E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4381.30141 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63266 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24972 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15753 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66593 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52568E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7751.50540 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67136 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14898 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13427 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39729 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55734E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5104.56268 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64285 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24577 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15750 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65538 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55025E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7712.03240 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71678 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13953 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14336 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37209 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73051E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5124.46829 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58331 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34731 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.16661 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34731 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68887 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.68887 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28734 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.40570 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34008 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.81140 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34008 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.26011 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.26011 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31456 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64490 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41071 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.28979 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.77141 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01610 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.01610 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.35315 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.68887 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.26011 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.01610 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68887 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.68887 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 115634.07496 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70378 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56280 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38540.83718 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70378 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 3853.58088 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.68887 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.26011 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.26011 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105788.59970 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.41989 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35259.34028 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 5111.05680 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.26011 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01610 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.01610 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 120664.38178 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71100 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.67187 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 40217.43845 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71100 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 2853.48260 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.01610 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 115420.25 | 393830.25 | 12.51 | 3.20 | 3.59 | 3.78 | 3.92 | 10.93 | 12.24 | 12.90 | 13.37 | 5.4168 | 4.2949 | 2.8947 | 1.2403 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 105615.82 | 360376.14 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.93 | 13.38 | 4.9214 | 3.8958 | 2.6216 | 1.1305 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 120345.94 | 410637.40 | 12.46 | 3.19 | 3.57 | 3.76 | 3.91 | 10.89 | 12.18 | 12.85 | 13.33 | 5.7948 | 4.5991 | 3.0912 | 1.3192 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_NORTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_EAST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_SOUTH_0.25 | N/A | 3.241 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_WEST_0.25 | N/A | 3.241 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2631387439 | 0.2897574435 | Pass | Pass | 0.2522599218 | 0.4325841137 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9729877391E-002 | 0.1073067461 | Pass | Pass | 0.2011714894 | 0.3979404395 | Fail | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0462141441E-002 | 4.9386540873E-002 | Pass | Pass | 0.2245761470 | 0.4346292737 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7948204840E-002 | 5.6124434149E-002 | Pass | Pass | 0.3128777347 | 0.7061851928 | Fail | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1546365287 | 0.2249160533 | Pass | Pass | 0.2025287814 | 0.4000456983 | Pass | Fail |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1636553606 | 0.2468622665 | Pass | Pass | 0.1961938868 | 0.3955369380 | Pass | Fail |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1682164018 | 0.2335965177 | Pass | Pass | 0.1948425445 | 0.3946991987 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2673223975 | 0.3557130964 | Pass | Pass | 0.1973297140 | 0.3966829064 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2766645777 | 0.4338351529 | Pass | Pass | 0.2344885273 | 0.4583242141 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2405612001 | 0.3369305934 | Pass | Pass | 0.1957640903 | 0.3940188854 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2192711526 | 0.2416506048 | Pass | Pass | 0.2506719461 | 0.4312215166 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3305478508 | 0.3715608320 | Pass | Pass | 0.2536916296 | 0.4319057631 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3443441751 | 0.4452252097 | Pass | Pass | 0.3014646437 | 0.4948248087 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2786235490 | 0.3096839140 | Pass | Pass | 0.2510200341 | 0.4304074590 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1523347811 | 0.2264103441 | Pass | Pass | 0.2022583353 | 0.3989685787 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2469369242 | 0.3699260991 | Pass | Pass | 0.2056048239 | 0.3981309261 | Pass | Fail |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2581181389 | 0.4348600530 | Pass | Pass | 0.2286852103 | 0.4370333224 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2131651047 | 0.3217116597 | Pass | Pass | 0.2027953678 | 0.3979372759 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2949.75 | -73.6 | 0.00 | -1116.7 | 3469.62 | 5229.11 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.241 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.241 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.241 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.71 | 0.0000 | Y | 8.71 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.24 | 0.0000 | Y | 8.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 8.68 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.47 | 0.0000 | Y | 5.46 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.19 | 0.0000 | Y | 8.53 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.45 | 0.0000 | Y | 5.46 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.71 | 0.0000 | Y | 8.71 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.24 | 0.0000 | Y | 8.55 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 5.47 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 300.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.82 | 41.82 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.82 | 62.82 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.82 | 46.78 | 41.40 | |
Exterior Lighting Total | 5686.19 | 50.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 115634.07 | 81381.22 | 34252.86 | 0.70 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105788.60 | 74166.61 | 31621.99 | 0.70 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 120664.38 | 85792.26 | 34872.12 | 0.71 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 115420.3 | 3.20 | 10.93 | N/A | N/A | 12.51 | |
PACU_VAV_MID COOLING COIL | 105615.8 | 3.21 | 10.94 | N/A | N/A | 12.53 | |
PACU_VAV_TOP COOLING COIL | 120345.9 | 3.19 | 10.89 | N/A | N/A | 12.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25611.65 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24933.31 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26107.14 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9846.78 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6461.42 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9822.98 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6470.35 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6304.98 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4170.04 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6269.96 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4381.30 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7751.51 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5104.56 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7712.03 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5124.47 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 3853.58 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 5111.06 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 2853.48 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.69 | 10263.98 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.26 | 9325.42 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.02 | 10980.29 | 2189.01 | 1.00 | 1.13 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115420.25 | 3.20 | 10.93 | 12.51 | 5.4168 | 3.59 | 12.24 | 4.2949 | 3.78 | 12.90 | 2.8947 | 3.92 | 13.37 | 1.2403 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105615.82 | 3.21 | 10.94 | 12.53 | 4.9214 | 3.59 | 12.25 | 3.8958 | 3.79 | 12.93 | 2.6216 | 3.92 | 13.38 | 1.1305 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 120345.94 | 3.19 | 10.89 | 12.46 | 5.7948 | 3.57 | 12.18 | 4.5991 | 3.76 | 12.85 | 3.0912 | 3.91 | 13.33 | 1.3192 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36707.00 | 36707.00 | 37.32 | 2.647 | 2.647 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_MID | 29805.56 | 29805.56 | 30.30 | 2.148 | 2.148 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_TOP | 32019.64 | 32019.64 | 32.56 | 2.329 | 2.329 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00887 | 33.13 | 0.01717 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9992.25 | 9992.25 | 48.19 | 0.727 | 0.727 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00892 | 32.15 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9604.61 | 9604.61 | 73.17 | 0.699 | 0.699 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00878 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10221.75 | 10221.75 | 49.30 | 0.744 | 0.744 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00891 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10879.72 | 10879.72 | 82.89 | 0.791 | 0.791 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00875 | 32.26 | 0.01717 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8473.53 | 8473.53 | 40.87 | 0.616 | 0.616 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00890 | 31.93 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8535.14 | 8535.14 | 65.02 | 0.621 | 0.621 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00876 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8595.13 | 8595.13 | 41.45 | 0.625 | 0.625 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00890 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9027.39 | 9027.39 | 68.78 | 0.657 | 0.657 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 32.04 | 0.01717 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8696.98 | 8696.98 | 41.95 | 0.633 | 0.633 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00895 | 31.82 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9229.05 | 9229.05 | 70.31 | 0.671 | 0.671 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00877 | 30.46 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8837.02 | 8837.02 | 42.62 | 0.643 | 0.643 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00894 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9853.33 | 9853.33 | 75.07 | 0.717 | 0.717 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00876 | 32.26 | 0.01717 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2407.52 | 2407.52 | 2.45 | 0.102 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_MID | 9025.75 | 9025.75 | 9.18 | 0.380 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_TOP | 17155.06 | 17155.06 | 17.44 | 0.728 | 0.728 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7534.56 | 7534.56 | 36.34 | 0.295 | 0.295 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 4944.28 | 4944.28 | 37.67 | 0.194 | 0.194 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00782 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 7516.22 | 7516.22 | 36.25 | 0.294 | 0.294 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 4951.04 | 4951.04 | 37.72 | 0.194 | 0.194 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00782 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 4447.02 | 4447.02 | 21.45 | 0.189 | 0.189 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 2940.16 | 2940.16 | 22.40 | 0.125 | 0.125 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 4422.53 | 4422.53 | 21.33 | 0.188 | 0.188 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 2956.36 | 2956.36 | 22.52 | 0.126 | 0.126 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5459.74 | 5459.74 | 26.33 | 0.232 | 0.232 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3594.60 | 3594.60 | 27.38 | 0.153 | 0.153 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5432.11 | 5432.11 | 26.20 | 0.231 | 0.231 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3608.54 | 3608.54 | 27.49 | 0.154 | 0.154 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 8.70 | 0.00699 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.69 | 4.69 | 1.05 | 1.05 | 4.6889 | 1.3473 | 4.6889 | 0.2873 | 0.3000 |
PACU_VAV_MID | 4.26 | 4.26 | 1.19 | 1.19 | 4.2601 | 1.3401 | 4.2601 | 0.3146 | 0.3000 |
PACU_VAV_TOP | 5.02 | 5.02 | 1.77 | 1.77 | 5.0161 | 1.7714 | 5.0161 | 0.3531 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25611.651 | 25611.651 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25611.65 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00799842 | 51.6459 | 2407.52 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24933.307 | 24933.307 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24933.31 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 9025.75 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26107.136 | 26107.136 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26107.14 | 24274.67 | 0.727672 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 17155.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 9846.783 | 9846.783 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 9846.78 | 9846.78 | 0.295173 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00781482 | 51.4259 | 7534.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 6461.424 | 6461.424 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6461.42 | 6461.42 | 0.193692 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00781551 | 51.4310 | 4944.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 9822.980 | 9822.980 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 9822.98 | 9822.98 | 0.294460 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00781428 | 51.4223 | 7516.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 6470.349 | 6470.349 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6470.35 | 6470.35 | 0.193959 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00781586 | 51.4333 | 4951.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6304.984 | 6304.984 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6304.98 | 6304.98 | 0.189002 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789057 | 50.9591 | 4447.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4170.038 | 4170.038 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4170.04 | 4170.04 | 0.125004 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789211 | 50.9690 | 2940.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6269.962 | 6269.962 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6269.96 | 6269.96 | 0.187952 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788976 | 50.9540 | 4422.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4381.301 | 4381.301 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4381.30 | 4193.20 | 0.125698 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789291 | 50.9741 | 2956.36 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 7751.505 | 7751.505 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7751.51 | 7751.51 | 0.232364 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788760 | 50.9403 | 5459.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5104.563 | 5104.563 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5104.56 | 5104.56 | 0.153017 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788976 | 50.9541 | 3594.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 7712.032 | 7712.032 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7712.03 | 7712.03 | 0.231181 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788678 | 50.9351 | 5432.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5124.468 | 5124.468 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5124.47 | 5124.47 | 0.153614 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789038 | 50.9581 | 3608.54 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 115634.075 | 81381.216 | 4.688867 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 119865.57 | 84303.36 | 4.688867 | 26.36 | 19.20 | 0.01099591 | 11.02 | 11.02 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 25.4895 | 24.00 | 0.00886193 | 47.6245 | 63944.46 | 0.00 | 119234.25 | 82767.05 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 3853.581 | 3853.581 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3853.58 | 3853.58 | 1.406660 | 10.53 | 9.69 | 0.00713442 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 84.9651 | 21.00 | 0.00790615 | 51.0584 | 17173.58 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 105788.600 | 74166.612 | 4.260107 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 110569.57 | 75719.33 | 4.260107 | 26.50 | 19.44 | 0.01124778 | 11.03 | 11.03 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 28.0549 | 24.00 | 0.00892474 | 47.9577 | 58290.91 | 0.00 | 109082.25 | 75437.50 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 5111.057 | 5111.057 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5111.06 | 5111.06 | 1.278032 | 9.49 | 9.13 | 0.00705349 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 93.5164 | 21.00 | 0.00792526 | 51.1802 | 27120.74 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 120664.382 | 85792.259 | 5.016098 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 124745.96 | 88833.13 | 5.016098 | 26.11 | 19.01 | 0.01085219 | 11.02 | 11.02 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 23.8267 | 24.00 | 0.00887319 | 47.6846 | 68852.35 | 0.00 | 124421.17 | 87203.05 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 2853.483 | 2853.483 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2853.48 | 2853.48 | 1.504829 | 11.23 | 10.06 | 0.00719282 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 79.4223 | 21.00 | 0.00796462 | 51.4307 | 27804.46 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25611.651 | 25611.651 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25611.65 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25611.65 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00799842 | 21.00 | 0.00799842 | 51.6459 | 2407.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24933.307 | 24933.307 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24933.31 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24933.31 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 9025.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26107.136 | 26107.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26107.14 | 24274.67 | 1.0000 | 0.87519969 | 0.727672 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26107.14 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 17155.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9846.783 | 9846.783 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 9846.78 | 9846.78 | 1.0000 | 0.35501614 | 0.295173 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9846.78 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.50 | 0.00781482 | 20.70 | 0.00781482 | 51.4259 | 7534.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6461.424 | 6461.424 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6461.42 | 6461.42 | 1.0000 | 0.23296034 | 0.193692 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6461.42 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.49 | 0.00781551 | 20.70 | 0.00781551 | 51.4310 | 4944.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9822.980 | 9822.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 9822.98 | 9822.98 | 1.0000 | 0.35415795 | 0.294460 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9822.98 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.50 | 0.00781428 | 20.70 | 0.00781428 | 51.4223 | 7516.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6470.349 | 6470.349 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6470.35 | 6470.35 | 1.0000 | 0.23328213 | 0.193959 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6470.35 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.49 | 0.00781586 | 20.70 | 0.00781586 | 51.4333 | 4951.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6304.984 | 6304.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6304.98 | 6304.98 | 1.0000 | 0.22732003 | 0.189002 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6304.98 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00789057 | 21.00 | 0.00789057 | 50.9591 | 4447.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4170.038 | 4170.038 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4170.04 | 4170.04 | 1.0000 | 0.15034665 | 0.125004 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4170.04 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00789211 | 21.00 | 0.00789211 | 50.9690 | 2940.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6269.962 | 6269.962 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6269.96 | 6269.96 | 1.0000 | 0.22605735 | 0.187952 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6269.96 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00788976 | 21.00 | 0.00788976 | 50.9540 | 4422.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4381.301 | 4381.301 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4381.30 | 4193.20 | 1.0000 | 0.15118168 | 0.125698 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4381.30 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00789291 | 21.00 | 0.00789291 | 50.9741 | 2956.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7751.505 | 7751.505 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7751.51 | 7751.51 | 1.0000 | 0.27947296 | 0.232364 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7751.51 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788760 | 21.00 | 0.00788760 | 50.9403 | 5459.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5104.563 | 5104.563 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5104.56 | 5104.56 | 1.0000 | 0.18404002 | 0.153017 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5104.56 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788976 | 21.00 | 0.00788976 | 50.9541 | 3594.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7712.032 | 7712.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7712.03 | 7712.03 | 1.0000 | 0.27804980 | 0.231181 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7712.03 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788678 | 21.00 | 0.00788678 | 50.9351 | 5432.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5124.468 | 5124.468 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5124.47 | 5124.47 | 1.0000 | 0.18475770 | 0.153614 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5124.47 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00789038 | 21.00 | 0.00789038 | 50.9581 | 3608.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 115634.075 | 81381.216 | 4.688867 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2808 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.688867 | 5.63948265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 119865.57 | 84303.36 | 1.0366 | 5.63948265 | 4.688867 | 26.36 | 19.20 | 0.01099591 | 54529.4 | 11.02 | 11.02 | 0.00850000 | 32510.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10263.981 | 109601.59 | 33.20 | 0.01716721 | 25.32 | 1.19517000 | 25.4895 | 24.00 | 0.00886193 | 24.00 | 0.00886193 | 47.6245 | 63944.46 | 0.00 | 119234.25 | 82767.05 | 5.41676571 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.70 | 11.69 | 0.00854508 | 33310.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3853.581 | 3853.581 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.688867 | 5.63948265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3853.58 | 3853.58 | 1.0000 | 1.69184479 | 1.406660 | 10.53 | 9.69 | 0.00713442 | 28566.7 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3853.58 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 84.9651 | 20.89 | 0.00793441 | 21.00 | 0.00790615 | 51.0584 | 17173.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105788.600 | 74166.612 | 4.260107 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.98142 | 1025.7491 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.260107 | 5.12379645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 110569.57 | 75719.33 | 1.0452 | 5.12379645 | 4.260107 | 26.50 | 19.44 | 0.01124778 | 55309.9 | 11.03 | 11.03 | 0.00850000 | 32511.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9325.421 | 101244.15 | 32.87 | 0.01716657 | 25.24 | 1.19517000 | 28.0549 | 24.00 | 0.00892474 | 24.00 | 0.00892474 | 47.9577 | 58290.91 | 0.00 | 109082.25 | 75437.50 | 4.92144522 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.62 | 0.00850428 | 33157.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5111.057 | 5111.057 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.260107 | 5.12379645 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5111.06 | 5111.06 | 1.0000 | 1.53713893 | 1.278032 | 9.49 | 9.13 | 0.00705349 | 27301.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5111.06 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 93.5164 | 20.90 | 0.00792802 | 21.00 | 0.00792526 | 51.1802 | 27120.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 120664.382 | 85792.259 | 5.016098 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0137 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.016098 | 6.03305631 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 124745.96 | 88833.13 | 1.0338 | 6.03305631 | 5.016098 | 26.11 | 19.01 | 0.01085219 | 53908.1 | 11.02 | 11.02 | 0.00850000 | 32509.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10980.294 | 113765.67 | 32.87 | 0.01716657 | 25.24 | 1.19517000 | 23.8267 | 24.00 | 0.00887319 | 24.00 | 0.00887319 | 47.6846 | 68852.35 | 0.00 | 124421.17 | 87203.05 | 5.79479619 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.93 | 11.91 | 0.00866647 | 33851.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 2853.483 | 2853.483 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.016098 | 6.03305631 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2853.48 | 2853.48 | 1.0000 | 1.80991689 | 1.504829 | 11.23 | 10.06 | 0.00719282 | 29424.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2853.48 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 79.4223 | 21.00 | 0.00796462 | 21.00 | 0.00796462 | 51.4307 | 27804.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5369.67 | 27.17 | 0.00 |
CORE_MID | 4160.67 | 621.83 | 0.00 |
CORE_TOP | 3833.33 | 1127.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 4204.83 | 1533.67 | 323.33 |
PERIMETER_TOP_ZN_2 | 4361.00 | 1471.00 | 433.83 |
PERIMETER_TOP_ZN_1 | 4710.17 | 1199.17 | 464.00 |
PERIMETER_TOP_ZN_4 | 4064.00 | 1678.17 | 366.50 |
PERIMETER_BOT_ZN_3 | 4552.50 | 932.00 | 85.00 |
PERIMETER_BOT_ZN_2 | 4906.00 | 763.67 | 252.50 |
PERIMETER_BOT_ZN_1 | 5238.00 | 1352.00 | 1005.50 |
PERIMETER_BOT_ZN_4 | 4816.50 | 838.00 | 200.00 |
PERIMETER_MID_ZN_3 | 4449.67 | 1142.33 | 196.33 |
PERIMETER_MID_ZN_2 | 3736.67 | 1115.33 | 345.50 |
PERIMETER_MID_ZN_1 | 4964.67 | 853.33 | 365.50 |
PERIMETER_MID_ZN_4 | 4385.50 | 1257.00 | 294.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5563.33 | 2790.17 | 1395.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 16.00 | 0.00 | 14.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 45.50 | 0.00 | 44.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 72.50 | 0.00 | 70.67 |
PERIMETER_TOP_ZN_4 | 0.00 | 39.00 | 0.00 | 28.83 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 31.17 | 0.00 | 31.17 |
PERIMETER_BOT_ZN_1 | 17.83 | 387.50 | 17.83 | 386.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 28.33 | 0.00 | 22.00 |
PERIMETER_MID_ZN_3 | 0.00 | 1.33 | 0.00 | 1.17 |
PERIMETER_MID_ZN_2 | 0.00 | 34.17 | 0.00 | 34.17 |
PERIMETER_MID_ZN_1 | 0.00 | 113.50 | 0.00 | 113.50 |
PERIMETER_MID_ZN_4 | 0.00 | 30.67 | 0.00 | 23.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 17.83 | 513.00 | 17.83 | 496.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.504 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.445 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.440 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.545 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.749 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.688 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.766 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.468 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.635 | 0.022 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.644 | 1.253 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.626 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.551 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.711 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.700 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.759 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8247072.11 | 0.00 | 8247072.11 | 0.00 | 8247072.11 | 13393058.27 | 6367.58 | 474.81 | 1917.61 | 221.34 |
CORE_MID | 7199708.62 | 0.00 | 7199708.62 | 0.00 | 7199708.62 | 13393058.27 | 8478.22 | 138.64 | 143.14 | 144.62 |
CORE_TOP | 7126511.68 | 0.00 | 7126511.68 | 0.00 | 7126511.68 | 13393058.27 | 8695.42 | 23.73 | 40.85 | 144.43 |
PERIMETER_TOP_ZN_3 | 1849426.65 | 0.00 | 1849426.65 | 242475.02 | 2091901.68 | 2823374.22 | 6049.47 | 70.81 | 2639.72 | 144.43 |
PERIMETER_TOP_ZN_2 | 1606967.71 | 0.00 | 1606967.71 | 161649.04 | 1768616.76 | 1787429.43 | 3617.44 | 4.67 | 5137.90 | 144.43 |
PERIMETER_TOP_ZN_1 | 2323187.38 | 0.00 | 2323187.38 | 242475.02 | 2565662.40 | 2823374.22 | 5235.24 | 35.88 | 3488.88 | 144.43 |
PERIMETER_TOP_ZN_4 | 1651804.74 | 0.00 | 1651804.74 | 161649.04 | 1813453.79 | 1787312.18 | 3654.99 | 26.28 | 5078.73 | 144.43 |
PERIMETER_BOT_ZN_3 | 1618931.18 | 0.00 | 1618931.18 | 128923.74 | 1747854.92 | 2823374.22 | 6725.43 | 737.51 | 1297.07 | 221.34 |
PERIMETER_BOT_ZN_2 | 1384069.99 | 0.00 | 1384069.99 | 85948.64 | 1470018.63 | 1787429.43 | 3773.90 | 99.69 | 4886.41 | 221.34 |
PERIMETER_BOT_ZN_1 | 2196265.96 | 0.00 | 2196265.96 | 4188758.26 | 6385024.22 | 2823374.22 | 4838.40 | 475.29 | 3446.31 | 221.34 |
PERIMETER_BOT_ZN_4 | 1369182.34 | 0.00 | 1369182.34 | 85948.64 | 1455130.98 | 1787312.18 | 4180.61 | 152.28 | 4427.11 | 221.34 |
PERIMETER_MID_ZN_3 | 1867529.35 | 0.00 | 1867529.35 | 201842.66 | 2069372.01 | 2823374.22 | 5876.84 | 151.55 | 2731.61 | 144.62 |
PERIMETER_MID_ZN_2 | 1610017.82 | 0.00 | 1610017.82 | 134560.97 | 1744578.79 | 1787429.43 | 3634.34 | 14.32 | 5111.33 | 1053.62 |
PERIMETER_MID_ZN_1 | 2362394.06 | 0.00 | 2362394.06 | 201842.66 | 2564236.73 | 2823374.22 | 4982.91 | 110.39 | 3666.70 | 144.62 |
PERIMETER_MID_ZN_4 | 1634332.36 | 0.00 | 1634332.36 | 134560.97 | 1768893.33 | 1787312.18 | 3733.95 | 34.58 | 4991.48 | 144.62 |
Total Facility | 44047401.96 | 0.00 | 44047401.96 | 5970634.68 | 50018036.65 | 67843644.98 | 8760.00 | 1457.02 | 5385.21 | 1180.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3695 | 0.0000 | 0.3695 | 0.0000 | 0.3695 | 0.4247 | 3597.10 | 441.13 | 1904.77 |
CORE_MID | 0.3263 | 0.0000 | 0.3263 | 0.0000 | 0.3263 | 0.4247 | 5664.12 | 138.45 | 140.43 |
CORE_TOP | 0.3231 | 0.0000 | 0.3231 | 0.0000 | 0.3231 | 0.4247 | 5879.86 | 23.65 | 39.49 |
PERIMETER_TOP_ZN_3 | 0.0843 | 0.0000 | 0.0843 | 0.0061 | 0.0904 | 0.0895 | 3237.86 | 70.47 | 2634.67 |
PERIMETER_TOP_ZN_2 | 0.0733 | 0.0000 | 0.0733 | 0.0040 | 0.0774 | 0.0567 | 943.94 | 4.57 | 4994.49 |
PERIMETER_TOP_ZN_1 | 0.1064 | 0.0000 | 0.1064 | 0.0061 | 0.1125 | 0.0895 | 2424.32 | 35.73 | 3482.96 |
PERIMETER_TOP_ZN_4 | 0.0751 | 0.0000 | 0.0751 | 0.0040 | 0.0791 | 0.0567 | 982.32 | 26.28 | 4934.39 |
PERIMETER_BOT_ZN_3 | 0.0724 | 0.0000 | 0.0724 | 0.0032 | 0.0756 | 0.0895 | 4014.34 | 632.02 | 1296.63 |
PERIMETER_BOT_ZN_2 | 0.0622 | 0.0000 | 0.0622 | 0.0021 | 0.0643 | 0.0567 | 1173.00 | 98.70 | 4671.30 |
PERIMETER_BOT_ZN_1 | 0.0993 | 0.0000 | 0.0993 | 0.1930 | 0.2923 | 0.0895 | 2080.98 | 422.64 | 3439.38 |
PERIMETER_BOT_ZN_4 | 0.0613 | 0.0000 | 0.0613 | 0.0021 | 0.0634 | 0.0567 | 1582.43 | 151.65 | 4208.92 |
PERIMETER_MID_ZN_3 | 0.0852 | 0.0000 | 0.0852 | 0.0050 | 0.0902 | 0.0895 | 3063.25 | 151.41 | 2728.34 |
PERIMETER_MID_ZN_2 | 0.0696 | 0.0000 | 0.0696 | 0.0035 | 0.0731 | 0.0567 | 943.83 | 8.10 | 4082.07 |
PERIMETER_MID_ZN_1 | 0.1083 | 0.0000 | 0.1083 | 0.0050 | 0.1133 | 0.0895 | 2171.26 | 110.15 | 3661.60 |
PERIMETER_MID_ZN_4 | 0.0744 | 0.0000 | 0.0744 | 0.0034 | 0.0777 | 0.0567 | 1061.10 | 34.53 | 4847.36 |
Total Facility | 1.9905 | 0.0000 | 1.9905 | 0.2377 | 2.2282 | 2.1513 | 5943.00 | 1348.34 | 5113.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21431890.33 | 0.00 | 21431890.33 | 22614548.33 | 3519.06 | 0.00 | 5240.94 | 221.34 |
PACU_VAV_MID | 21227112.43 | 0.00 | 21227112.43 | 22614548.33 | 3602.22 | 0.00 | 5157.78 | 144.62 |
PACU_VAV_TOP | 21059182.33 | 0.00 | 21059182.33 | 22614548.33 | 3605.88 | 0.00 | 5154.12 | 144.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9615 | 0.0000 | 0.9615 | 0.7171 | 923.40 | 0.00 | 5019.60 |
PACU_VAV_MID | 0.9657 | 0.0000 | 0.9657 | 0.7171 | 929.84 | 0.00 | 5013.16 |
PACU_VAV_TOP | 0.9579 | 0.0000 | 0.9579 | 0.7171 | 933.31 | 0.00 | 5009.69 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5240.94 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5157.78 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5154.12 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1385 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1449 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1365 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
Electricity:Building | 1019.99 | 13465.67 | 09-JUL-17:20 | 74341.76 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1019.99 | 13465.67 | 09-JUL-17:20 | 74341.76 | 27-SEP-07:10 |
InteriorLights:Electricity | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 300.30 | 987.92 | 09-JUL-17:20 | 32642.50 | 27-SEP-07:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.04 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.88 | 267.21 | 04-JUL-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.88 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.87 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.01 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-09:50 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.68 | 36.00 | 01-JAN-09:50 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 267.21 | 29-MAY-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.86 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.86 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:50 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:50 | 859.95 | 15-JUN-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.04 | 422.10 | 02-APR-17:10 | 2793.69 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.71 | 36.00 | 01-JAN-10:00 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.88 | 267.21 | 04-JUL-17:10 | 1768.58 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:40 | 860.01 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.88 | 422.10 | 19-MAR-17:10 | 2793.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-07:40 | 1358.45 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.87 | 267.21 | 12-MAR-17:10 | 1768.52 | 15-JUN-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-10:00 | 859.95 | 15-JUN-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 770.19 | 367.92 | 01-JAN-00:10 | 91741.70 | 28-JUL-15:30 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 25-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 25-JAN-08:10 |
ElectricityPurchased:Facility | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
ElectricityPurchased:Plant | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
Cogeneration:ElectricityPurchased | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
General:Cogeneration:ElectricityPurchased | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
ElectricityNet:Plant | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
Cogeneration:ElectricityNet | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
General:Cogeneration:ElectricityNet | 1880.12 | 13838.70 | 09-JUL-17:30 | 161987.49 | 28-JUL-15:30 |
Heating:Electricity | 1.80 | 0.00 | 01-JAN-00:10 | 38066.27 | 04-FEB-07:10 |
General:Heating:Electricity | 1.80 | 0.00 | 01-JAN-00:10 | 38066.27 | 04-FEB-07:10 |
Fans:Electricity | 98.73 | 0.00 | 01-JAN-00:10 | 15130.33 | 31-JUL-14:30 |
General:Fans:Electricity | 98.73 | 0.00 | 01-JAN-00:10 | 15130.33 | 31-JUL-14:30 |
ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 642.75 | 0.00 | 01-JAN-00:10 | 75613.40 | 28-JUL-15:30 |
General:Cooling:Electricity | 642.75 | 0.00 | 01-JAN-00:10 | 75613.40 | 28-JUL-15:30 |
Electricity:Plant | 39.31 | 0.00 | 01-JAN-00:10 | 4626.57 | 18-JAN-12:50 |
WaterSystems:Electricity | 39.17 | 0.00 | 01-JAN-00:10 | 4619.72 | 18-JAN-12:50 |
Water Heater:WaterSystems:Electricity | 39.17 | 0.00 | 01-JAN-00:10 | 4619.72 | 18-JAN-12:50 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-FEB-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-FEB-17:10 |
WIRED_LTG_ELECTRICITY | 8.44 | 0.00 | 01-JAN-00:10 | 917.25 | 27-SEP-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4608.03 | 0.00 | 01-JAN-00:10 | 456978.19 | 31-JUL-14:10 |
EnergyTransfer:Building | 1742.93 | 0.00 | 01-JAN-00:10 | 169181.47 | 31-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 322.98 | 0.00 | 01-JAN-00:10 | 25456.48 | 05-SEP-08:00 |
Heating:EnergyTransfer | 2.17 | 0.00 | 01-JAN-00:10 | 23055.09 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.17 | 0.00 | 01-JAN-00:10 | 23055.09 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1740.77 | 0.00 | 01-JAN-00:10 | 169181.47 | 31-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 322.98 | 0.00 | 01-JAN-00:10 | 25456.48 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1740.77 | 0.00 | 01-JAN-00:10 | 169181.47 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 322.98 | 0.00 | 01-JAN-00:10 | 25456.48 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.84 | 0.00 | 01-JAN-00:10 | 11636.69 | 28-JUL-15:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 4047.98 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.18 | 0.00 | 01-JAN-00:10 | 4047.98 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.66 | 0.00 | 01-JAN-00:10 | 11636.69 | 28-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.66 | 0.00 | 01-JAN-00:10 | 11636.69 | 28-JUL-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.57 | 0.00 | 01-JAN-00:10 | 5004.28 | 31-JUL-14:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.15 | 0.00 | 01-JAN-00:10 | 1540.12 | 05-FEB-12:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.15 | 0.00 | 01-JAN-00:10 | 1540.12 | 05-FEB-12:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.42 | 0.00 | 01-JAN-00:10 | 5004.28 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.42 | 0.00 | 01-JAN-00:10 | 5004.28 | 31-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.90 | 0.00 | 01-JAN-00:10 | 5455.16 | 31-JUL-15:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1492.33 | 05-FEB-12:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1492.33 | 05-FEB-12:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.66 | 0.00 | 01-JAN-00:10 | 5455.16 | 31-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 46.66 | 0.00 | 01-JAN-00:10 | 5455.16 | 31-JUL-15:20 |
EnergyTransfer:Zone:CORE_MID | 234.45 | 0.00 | 01-JAN-00:10 | 19310.80 | 02-OCT-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 234.45 | 0.00 | 01-JAN-00:10 | 19310.80 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 234.45 | 0.00 | 01-JAN-00:10 | 19310.80 | 02-OCT-08:00 |
EnergyTransfer:Zone:CORE_TOP | 242.27 | 0.00 | 01-JAN-00:10 | 21860.71 | 31-JUL-14:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 2183.24 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 2183.24 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 242.27 | 0.00 | 01-JAN-00:10 | 21860.71 | 31-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 242.27 | 0.00 | 01-JAN-00:10 | 21860.71 | 31-JUL-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.05 | 0.00 | 01-JAN-00:10 | 7970.54 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 3521.84 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 3521.84 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.98 | 0.00 | 01-JAN-00:10 | 7970.54 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.98 | 0.00 | 01-JAN-00:10 | 7970.54 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.10 | 0.00 | 01-JAN-00:10 | 8044.46 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2083.14 | 04-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.03 | 0.00 | 01-JAN-00:10 | 2083.14 | 04-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.06 | 0.00 | 01-JAN-00:10 | 8044.46 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 57.06 | 0.00 | 01-JAN-00:10 | 8044.46 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.87 | 0.00 | 01-JAN-00:10 | 11123.68 | 04-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2810.95 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2810.95 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.84 | 0.00 | 01-JAN-00:10 | 11123.68 | 04-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 84.84 | 0.00 | 01-JAN-00:10 | 11123.68 | 04-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.10 | 0.00 | 01-JAN-00:10 | 8677.72 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2248.78 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 2248.78 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.05 | 0.00 | 01-JAN-00:10 | 8677.72 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.05 | 0.00 | 01-JAN-00:10 | 8677.72 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.69 | 0.00 | 01-JAN-00:10 | 7193.76 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 549.46 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 549.46 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.69 | 0.00 | 01-JAN-00:10 | 7193.76 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.69 | 0.00 | 01-JAN-00:10 | 7193.76 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.18 | 0.00 | 01-JAN-00:10 | 7192.36 | 25-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 314.13 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 314.13 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.18 | 0.00 | 01-JAN-00:10 | 7192.36 | 25-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.18 | 0.00 | 01-JAN-00:10 | 7192.36 | 25-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.48 | 0.00 | 01-JAN-00:10 | 10794.30 | 27-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.40 | 0.00 | 01-JAN-00:10 | 4551.60 | 16-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.40 | 0.00 | 01-JAN-00:10 | 4551.60 | 16-MAR-07:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.08 | 0.00 | 01-JAN-00:10 | 10794.30 | 27-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 92.08 | 0.00 | 01-JAN-00:10 | 10794.30 | 27-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 54.53 | 0.00 | 01-JAN-00:10 | 7176.43 | 01-SEP-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 399.33 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 399.33 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 54.53 | 0.00 | 01-JAN-00:10 | 7176.43 | 01-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 54.53 | 0.00 | 01-JAN-00:10 | 7176.43 | 01-SEP-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.38 | 0.00 | 01-JAN-00:10 | 7229.60 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1772.88 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1772.88 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.38 | 0.00 | 01-JAN-00:10 | 7229.60 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.38 | 0.00 | 01-JAN-00:10 | 7229.60 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.46 | 0.00 | 01-JAN-00:10 | 7507.67 | 12-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 841.21 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 841.21 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.45 | 0.00 | 01-JAN-00:10 | 7507.67 | 12-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 54.45 | 0.00 | 01-JAN-00:10 | 7507.67 | 12-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.90 | 0.00 | 01-JAN-00:10 | 9980.10 | 04-DEC-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1292.34 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1292.34 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.90 | 0.00 | 01-JAN-00:10 | 9980.10 | 04-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 81.90 | 0.00 | 01-JAN-00:10 | 9980.10 | 04-DEC-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.19 | 0.00 | 01-JAN-00:10 | 8059.50 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1161.34 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 1161.34 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.18 | 0.00 | 01-JAN-00:10 | 8059.50 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 54.18 | 0.00 | 01-JAN-00:10 | 8059.50 | 17-MAY-16:00 |
PlantLoopHeatingDemand:Facility | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
EnergyTransfer:HVAC | 2828.67 | 0.00 | 01-JAN-00:10 | 288683.99 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 1.80 | 0.00 | 01-JAN-00:10 | 38066.27 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2826.87 | 0.00 | 01-JAN-00:10 | 288683.99 | 21-AUG-16:00 |
EnergyTransfer:Plant | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
WaterSystems:EnergyTransfer | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -322.984 | 0.000 | 0.000 | 32.659 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -32.027 |
CORE_MID | 0.000 | 0.000 | 0.000 | -234.448 | 0.000 | 0.000 | 32.847 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 14.247 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_TOP | 0.000 | 0.000 | 0.001 | -242.270 | 0.000 | 0.000 | 33.088 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 21.827 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.064 | -65.982 | 0.000 | 0.000 | 7.011 | 8.707 | 24.333 | 27.588 | 0.000 | 0.344 | 8.344 | 0.000 | -9.891 | 0.000 | -0.518 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.033 | -57.061 | 0.000 | 0.000 | 4.408 | 5.472 | 15.404 | 36.650 | 0.000 | 0.225 | 1.516 | 0.000 | -6.286 | 0.000 | -0.361 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.033 | -84.839 | 0.000 | 0.000 | 6.935 | 8.546 | 24.332 | 56.912 | 0.000 | 0.323 | 0.000 | 0.000 | -10.063 | 0.000 | -0.594 | -1.584 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.048 | -57.050 | 0.000 | 0.000 | 4.472 | 5.471 | 15.403 | 35.677 | 0.000 | 0.229 | 2.929 | 0.000 | -6.814 | 0.000 | -0.365 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -64.688 | 0.000 | 0.000 | 6.951 | 8.677 | 24.333 | 27.720 | 0.000 | 0.192 | 8.063 | 0.000 | -10.935 | 0.000 | -0.313 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -56.184 | 0.000 | 0.000 | 4.375 | 5.460 | 15.404 | 36.750 | 0.000 | 0.120 | 1.546 | 0.000 | -7.245 | 0.000 | -0.226 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.398 | -92.076 | 0.000 | 0.000 | 6.869 | 8.530 | 24.332 | 57.080 | 0.000 | 11.469 | 0.326 | 0.000 | -11.522 | 0.000 | -5.406 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -54.524 | 0.000 | 0.000 | 4.397 | 5.456 | 15.403 | 35.681 | 0.000 | 0.118 | 1.548 | 0.000 | -7.849 | 0.000 | -0.231 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.004 | -63.375 | 0.000 | 0.000 | 6.963 | 8.707 | 24.333 | 27.673 | 0.000 | 0.292 | 6.573 | 0.000 | -10.691 | 0.000 | -0.478 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.003 | -54.453 | 0.000 | 0.000 | 3.244 | 5.472 | 15.404 | 36.747 | 0.000 | 0.190 | 0.457 | 0.000 | -6.736 | 0.000 | -0.329 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.001 | -81.895 | 0.000 | 0.000 | 6.896 | 8.546 | 24.332 | 57.054 | 0.000 | 0.272 | 0.001 | 0.000 | -10.766 | 0.000 | -0.539 | -3.903 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.004 | -54.183 | 0.000 | 0.000 | 4.429 | 5.471 | 15.403 | 35.711 | 0.000 | 0.188 | 0.671 | 0.000 | -7.358 | 0.000 | -0.336 | -0.000 |
TOPFLOOR_PLENUM | 1.181 | -68.663 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.363 | 67.904 | 0.000 | 0.000 | 0.000 | -0.784 | -0.000 |
MIDFLOOR_PLENUM | 0.155 | -39.415 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.413 | 39.695 | 0.000 | 0.000 | 0.000 | -0.849 | -0.000 |
FIRSTFLOOR_PLENUM | 0.241 | -46.656 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.309 | 46.828 | 0.000 | 0.000 | 0.000 | -0.722 | -0.000 |
Total Facility | 1.576 | -154.733 | 0.589 | -1586.012 | 0.000 | 0.000 | 165.543 | 300.299 | 719.689 | 471.243 | 0.000 | 15.047 | 222.476 | 0.000 | -106.154 | 0.000 | -12.050 | -37.519 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | -44825.82 | 0.00 | 0.00 | 284.31 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 36919.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | -35470.15 | 0.00 | 0.00 | 304.09 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 31928.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:02 | 0.00 | 0.00 | 0.00 | -36073.47 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 33419.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-15:22 | 0.00 | 0.00 | 0.00 | -12299.90 | 0.00 | 0.00 | 27.19 | 36.00 | 478.42 | 2438.60 | 0.00 | 77.24 | 9242.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:12 | 0.00 | 0.00 | 0.00 | -12794.11 | 0.00 | 0.00 | 14.93 | 22.79 | 302.86 | 6861.49 | 0.00 | 22.57 | 5569.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-DEC-12:52 | 0.00 | 0.00 | 0.00 | -14421.50 | 0.00 | 0.00 | 22.83 | 36.00 | 478.41 | 11131.33 | 0.00 | 0.00 | 2761.88 | 0.00 | -0.00 | 0.00 | -8.95 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-APR-15:42 | 0.00 | 0.00 | 0.00 | -14189.55 | 0.00 | 0.00 | 14.94 | 22.79 | 302.86 | 8054.77 | 0.00 | 0.00 | 5808.01 | 0.00 | -0.00 | 0.00 | -13.82 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-SEP-15:31 | 0.00 | 0.00 | 0.00 | -9151.69 | 0.00 | 0.00 | 29.76 | 36.00 | 478.42 | 2476.38 | 0.00 | 55.32 | 6075.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:22 | 0.00 | 0.00 | 0.00 | -11538.71 | 0.00 | 0.00 | 15.16 | 22.79 | 302.86 | 5678.40 | 0.00 | 15.10 | 5504.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -11963.76 | 0.00 | 0.00 | 23.91 | 36.00 | 478.41 | 11291.97 | 0.00 | 25.02 | 108.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-15:31 | 0.00 | 0.00 | 0.00 | -12153.86 | 0.00 | 0.00 | 14.69 | 22.79 | 302.86 | 7944.03 | 0.00 | 23.67 | 3845.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-15:51 | 0.00 | 0.00 | 0.00 | -10697.70 | 0.00 | 0.00 | 28.05 | 36.00 | 478.42 | 3070.69 | 0.00 | 165.70 | 6918.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -12665.49 | 0.00 | 0.00 | 14.45 | 22.79 | 302.86 | 7588.34 | 0.00 | 15.49 | 4721.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -12487.77 | 0.00 | 0.00 | 23.03 | 36.00 | 478.41 | 11167.37 | 0.00 | 33.29 | 749.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-15:31 | 0.00 | 0.00 | 0.00 | -13382.74 | 0.00 | 0.00 | 13.78 | 22.79 | 302.86 | 7861.21 | 0.00 | 32.42 | 5149.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:30 | 0.00 | -11636.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 11602.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 31-JUL-14:30 | 0.00 | -5004.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 | 4966.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:10 | 0.00 | -5546.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 | 5515.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JUL-04:02 | 0.00 | 9813.74 | 0.00 | -204490.98 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 15.20 | 182033.95 | 0.00 | -4007.45 | 0.00 | -7.36 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-FEB-07:03 | 0.00 | 0.00 | 8733.03 | 0.00 | 0.00 | 0.00 | 445.27 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12920.19 |
PERIMETER_TOP_ZN_3 | 04-FEB-06:12 | 0.00 | 0.00 | 7006.61 | 0.00 | 0.00 | 0.00 | 102.62 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2682.88 | 0.00 | -93.71 | -5121.45 |
PERIMETER_TOP_ZN_2 | 14-DEC-07:02 | 0.00 | 0.00 | 4497.69 | 0.00 | 0.00 | 0.00 | 121.30 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -554.60 | 0.00 | 0.00 | -4754.87 |
PERIMETER_TOP_ZN_1 | 04-FEB-06:12 | 0.00 | 0.00 | 6781.18 | 0.00 | 0.00 | 0.00 | 101.40 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2667.62 | 0.00 | -95.73 | -4908.04 |
PERIMETER_TOP_ZN_4 | 04-FEB-06:14 | 0.00 | 0.00 | 4674.27 | 0.00 | 0.00 | 0.00 | 65.52 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1782.89 | 0.00 | -65.38 | -3390.88 |
PERIMETER_BOT_ZN_3 | 04-FEB-07:03 | 0.00 | 0.00 | 2197.83 | 0.00 | 0.00 | 0.00 | 93.95 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2874.16 | 0.00 | -54.50 | -151.94 |
PERIMETER_BOT_ZN_2 | 04-FEB-07:03 | 0.00 | 0.00 | 1256.53 | 0.00 | 0.00 | 0.00 | 59.67 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -315.15 | 0.00 | -36.32 | -1464.09 |
PERIMETER_BOT_ZN_1 | 16-MAR-07:00 | 0.00 | 0.00 | 4551.37 | 0.00 | 0.00 | 0.00 | 214.28 | 315.99 | 637.88 | 0.00 | 0.00 | 0.00 | 10378.16 | 0.00 | -1906.34 | 0.00 | -14191.36 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-FEB-07:03 | 0.00 | 0.00 | 1597.32 | 0.00 | 0.00 | 0.00 | 59.67 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1924.73 | 0.00 | -36.32 | -195.31 |
PERIMETER_MID_ZN_3 | 16-MAR-06:01 | 0.00 | 0.00 | 5176.67 | 0.00 | 0.00 | 0.00 | 188.72 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2802.36 | 0.00 | -74.25 | -3579.49 |
PERIMETER_MID_ZN_2 | 26-JAN-07:02 | 0.00 | 0.00 | 3435.86 | 0.00 | 0.00 | 0.00 | 120.68 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1352.31 | 0.00 | -9.92 | -2884.79 |
PERIMETER_MID_ZN_1 | 04-FEB-07:03 | 0.00 | 0.00 | 4668.48 | 0.00 | 0.00 | 0.00 | 96.46 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2193.62 | 0.00 | -83.66 | -3276.48 |
PERIMETER_MID_ZN_4 | 26-JAN-07:02 | 0.00 | 0.00 | 3332.41 | 0.00 | 0.00 | 0.00 | 120.96 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1367.63 | 0.00 | -9.86 | -2766.34 |
TOPFLOOR_PLENUM | 05-JUL-04:02 | 5349.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.17 | -5347.77 |
MIDFLOOR_PLENUM | 05-FEB-12:13 | 3162.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.22 | -3091.07 |
FIRSTFLOOR_PLENUM | 29-SEP-04:02 | 4010.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.25 | -4003.43 |
Total Facility | 04-FEB-07:03 | -19840.32 | 20529.49 | 49605.85 | -20529.49 | 0.00 | 0.00 | 2163.37 | 3626.85 | 22473.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21102.16 | 0.00 | -1203.34 | -35723.36 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1666 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6889 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.8114 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2601 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2898 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0161 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5833 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3473 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4057 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3401 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6449 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4107 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6474 | 2.6474 | 0.7678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1477 | 2.1477 | 0.7474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3292 | 2.3292 | 0.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7269 | 0.7269 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6987 | 0.6987 | 0.1397 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7436 | 0.7436 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7914 | 0.7914 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6164 | 0.6164 | 0.1621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6209 | 0.6209 | 0.1242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6252 | 0.6252 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6567 | 0.6567 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6327 | 0.6327 | 0.1575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6714 | 0.6714 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6429 | 0.6429 | 0.1575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7168 | 0.7168 | 0.1434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1666 | 4.6889 | 5.1666 | 1.3473 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.8114 | 4.2601 | 4.8114 | 1.3401 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2898 | 5.0161 | 5.2898 | 1.4107 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3237 | 1.3237 | 0.7678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0739 | 1.0739 | 0.7474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1646 | 1.1646 | 0.7826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3634 | 0.3634 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3493 | 0.3493 | 0.1397 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3718 | 0.3718 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3957 | 0.3957 | 0.1583 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3082 | 0.3082 | 0.1621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3104 | 0.3104 | 0.1242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3126 | 0.3126 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3283 | 0.3283 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3163 | 0.3163 | 0.1575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3357 | 0.3357 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3214 | 0.3214 | 0.1575 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3584 | 0.3584 | 0.1434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5833 | 1.3473 | 1.3473 | 1.3473 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4057 | 1.3401 | 1.3401 | 1.3401 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6449 | 1.4107 | 1.4107 | 1.4107 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 17.83 |
Number of hours cooling loads not met | 496.83 |
Number of hours not met | 514.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 1.80 | 38066.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 642.75 | 75613.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 300.30 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.63 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 98.73 | 15130.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 39.17 | 4619.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1880.12 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1880.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.27 |
Space Heating | 0.36 |
Space Cooling | 129.01 |
Fans (All) | 19.82 |
Service Water Heating | 7.86 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 377.37 |
Subtotal | 377.37 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.97 |
Space Heating | 0.10 |
Space Cooling | 34.19 |
Fans (All) | 5.25 |
Service Water Heating | 2.08 |
Receptacle Equipment | 38.28 |
Miscellaneous | 4.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7582.83 | 1177.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8717.50 | 42.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8727.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8506.17 | 253.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8384.00 | 376.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8315.17 | 444.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8290.50 | 469.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8708.67 | 51.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8425.67 | 334.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8349.83 | 410.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8258.33 | 501.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8571.00 | 189.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8421.17 | 338.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8368.67 | 391.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8279.17 | 480.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8273.67 | 486.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
Min | 7582.83 | 0.83 | 0.00 | 0.00 | 0.00 |
Max | 8759.17 | 1177.17 | 0.00 | 0.00 | 0.00 |
Average | 8427.47 | 332.53 | 0.00 | 0.00 | 0.00 |
Sum | 151694.50 | 5985.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127908.67 | 395.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128293.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24890.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.33 | 395.33 | 0.00 | 0.00 | 0.00 |
Average | 34119.42 | 23.92 | 0.00 | 0.00 | 0.00 |
Sum | 614149.50 | 430.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7218.67 | 1541.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8570.00 | 190.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8626.17 | 133.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6577.67 | 2182.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6578.83 | 2181.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6426.00 | 2334.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6610.83 | 2149.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7005.17 | 1754.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6681.67 | 2078.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5679.33 | 3080.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6625.00 | 2135.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6531.83 | 2228.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6527.00 | 2233.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6335.33 | 2424.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6477.17 | 2282.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6883.50 | 1876.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7321.83 | 1438.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7531.00 | 1229.00 | 0.00 | 0.00 | 0.00 |
Min | 5679.33 | 133.83 | 0.00 | 0.00 | 0.00 |
Max | 8626.17 | 3080.67 | 0.00 | 0.00 | 0.00 |
Average | 6900.39 | 1859.61 | 0.00 | 0.00 | 0.00 |
Sum | 124207.00 | 33473.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127709.17 | 594.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128238.67 | 65.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128273.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24872.33 | 36.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24871.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24904.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20435.33 | 4473.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24879.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24877.83 | 31.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128273.33 | 4473.67 | 0.00 | 0.00 | 0.00 |
Average | 33848.64 | 294.69 | 0.00 | 0.00 | 0.00 |
Sum | 609275.50 | 5304.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239702E+11 | 36978.62 | 02-JAN-07:03 | 19.08 | 19.01 | 0.199426E+10 | 2606.73 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.220435E+11 | 39455.93 | 21-FEB-06:12 | 15.60 | 15.30 | 0.180942E+10 | 2606.69 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.262034E+11 | 36467.94 | 06-MAR-07:03 | 22.88 | 21.60 | 0.216115E+10 | 2606.66 | 01-MAR-10:09 | 22.88 | 21.60 |
April | 0.257697E+11 | 40949.74 | 12-APR-04:03 | 24.40 | 22.16 | 0.191903E+10 | 2606.66 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.289539E+11 | 44825.78 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207817E+10 | 2606.54 | 30-MAY-13:09 | 25.97 | 24.15 |
June | 0.291319E+11 | 43538.98 | 06-JUN-05:03 | 23.98 | 23.24 | 0.207108E+10 | 2606.54 | 05-JUN-13:09 | 23.98 | 23.24 |
July | 0.290887E+11 | 41945.36 | 06-JUL-04:02 | 23.90 | 22.27 | 0.192458E+10 | 2606.54 | 14-JUL-13:09 | 28.90 | 25.03 |
August | 0.305227E+11 | 40837.16 | 30-AUG-04:03 | 25.50 | 23.18 | 0.216061E+10 | 2606.54 | 07-AUG-13:30 | 25.50 | 23.18 |
September | 0.286152E+11 | 41150.64 | 12-SEP-04:02 | 24.40 | 22.75 | 0.191833E+10 | 2606.54 | 11-SEP-13:09 | 24.40 | 22.75 |
October | 0.288393E+11 | 43408.44 | 26-OCT-05:03 | 23.80 | 22.28 | 0.199623E+10 | 2606.55 | 10-OCT-13:09 | 23.80 | 22.28 |
November | 0.261151E+11 | 41252.85 | 20-NOV-05:02 | 24.40 | 20.52 | 0.197701E+10 | 2606.70 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.237301E+11 | 39271.69 | 09-DEC-05:03 | 25.00 | 22.66 | 0.192473E+10 | 2606.64 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.322984E+12 | 0.239346E+11 | ||||||||
Minimum of Months | 0.220435E+11 | 36467.94 | 15.60 | 15.30 | 0.180942E+10 | 2606.54 | 19.08 | 15.05 | ||
Maximum of Months | 0.305227E+11 | 44825.78 | 25.50 | 23.24 | 0.216115E+10 | 2606.73 | 28.90 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279952E+10 | 7984.49 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.345895E+10 | 8020.37 | 22-FEB-15:30 | 27.80 | 14.62 | 0.00 | 0.00 | 01-FEB-00:10 | 27.80 | 14.62 |
March | 0.462079E+10 | 9214.59 | 27-MAR-15:00 | 27.80 | 22.40 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 22.40 |
April | 0.585697E+10 | 10111.30 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.737636E+10 | 11163.55 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.768417E+10 | 10502.10 | 09-JUN-13:40 | 30.93 | 24.93 | 0.00 | 0.00 | 01-JUN-00:10 | 30.93 | 24.93 |
July | 0.844361E+10 | 11636.69 | 28-JUL-15:30 | 35.00 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.05 |
August | 0.772206E+10 | 11095.85 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.716955E+10 | 10830.63 | 18-SEP-13:50 | 31.10 | 24.96 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 24.96 |
October | 0.610113E+10 | 10512.49 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.441091E+10 | 8573.62 | 10-NOV-14:30 | 28.90 | 24.27 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.27 |
December | 0.301968E+10 | 7447.84 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.686637E+11 | 0.00 | ||||||||
Minimum of Months | 0.279952E+10 | 7447.84 | 27.40 | 14.62 | 0.00 | 0.00 | 27.40 | 14.62 | ||
Maximum of Months | 0.844361E+10 | 11636.69 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168876E+10 | 3842.44 | 02-JAN-16:30 | 25.30 | 20.50 | 0.00 | 0.00 | 01-JAN-00:10 | 25.30 | 20.50 |
February | 0.189575E+10 | 3427.43 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.256960E+10 | 3946.17 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.310982E+10 | 4228.26 | 17-APR-15:50 | 31.78 | 20.21 | 0.00 | 0.00 | 01-APR-00:10 | 31.78 | 20.21 |
May | 0.403018E+10 | 4548.59 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.434743E+10 | 4394.58 | 26-JUN-12:02 | 30.68 | 25.17 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 25.17 |
July | 0.454943E+10 | 5004.28 | 31-JUL-14:30 | 31.95 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 31.95 | 25.05 |
August | 0.448103E+10 | 4748.59 | 21-AUG-16:00 | 32.20 | 26.46 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 26.46 |
September | 0.418413E+10 | 4820.91 | 11-SEP-12:02 | 31.52 | 24.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.52 | 24.53 |
October | 0.387535E+10 | 4593.17 | 02-OCT-15:20 | 30.73 | 25.15 | 0.00 | 0.00 | 01-OCT-00:10 | 30.73 | 25.15 |
November | 0.279702E+10 | 4218.77 | 06-NOV-16:30 | 27.80 | 20.19 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.19 |
December | 0.188679E+10 | 3525.59 | 11-DEC-15:50 | 24.08 | 17.65 | 0.00 | 0.00 | 01-DEC-00:10 | 24.08 | 17.65 |
Annual Sum or Average | 0.394153E+11 | 0.00 | ||||||||
Minimum of Months | 0.168876E+10 | 3427.43 | 24.08 | 14.07 | 0.00 | 0.00 | 24.08 | 14.07 | ||
Maximum of Months | 0.454943E+10 | 5004.28 | 34.15 | 26.46 | 0.00 | 0.00 | 34.15 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240621E+10 | 4598.42 | 02-JAN-16:10 | 25.50 | 20.58 | 0.00 | 0.00 | 01-JAN-00:10 | 25.50 | 20.58 |
February | 0.248829E+10 | 4201.52 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.317554E+10 | 4484.86 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.357225E+10 | 4705.11 | 17-APR-15:50 | 31.78 | 20.21 | 0.00 | 0.00 | 01-APR-00:10 | 31.78 | 20.21 |
May | 0.454531E+10 | 5196.86 | 22-MAY-12:08 | 33.48 | 23.09 | 0.00 | 0.00 | 01-MAY-00:10 | 33.48 | 23.09 |
June | 0.482102E+10 | 4919.53 | 26-JUN-12:15 | 30.77 | 25.13 | 0.00 | 0.00 | 01-JUN-00:10 | 30.77 | 25.13 |
July | 0.502571E+10 | 5546.72 | 31-JUL-12:10 | 32.93 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 25.13 |
August | 0.512018E+10 | 5206.63 | 21-AUG-16:00 | 32.20 | 26.46 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 26.46 |
September | 0.477693E+10 | 5184.12 | 11-SEP-12:10 | 31.52 | 24.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.52 | 24.53 |
October | 0.459596E+10 | 5006.51 | 02-OCT-16:00 | 30.00 | 25.50 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 25.50 |
November | 0.359147E+10 | 4760.83 | 06-NOV-16:30 | 27.80 | 20.19 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.19 |
December | 0.253728E+10 | 4234.74 | 11-DEC-16:00 | 23.90 | 17.60 | 0.00 | 0.00 | 01-DEC-00:10 | 23.90 | 17.60 |
Annual Sum or Average | 0.466562E+11 | 0.00 | ||||||||
Minimum of Months | 0.240621E+10 | 4201.52 | 23.90 | 14.07 | 0.00 | 0.00 | 23.90 | 14.07 | ||
Maximum of Months | 0.512018E+10 | 5546.72 | 33.48 | 26.46 | 0.00 | 0.00 | 33.48 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162065E+11 | 25120.19 | 14-JAN-06:03 | 23.62 | 21.60 | 0.195792E+10 | 2606.66 | 12-JAN-10:09 | 23.62 | 21.60 |
February | 0.153974E+11 | 23868.60 | 11-FEB-06:03 | 23.90 | 22.27 | 0.178258E+10 | 2606.68 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.186424E+11 | 17411.19 | 27-MAR-16:00 | 27.20 | 22.19 | 0.213840E+10 | 2606.65 | 01-MAR-10:09 | 27.20 | 22.19 |
April | 0.189797E+11 | 22864.49 | 13-APR-04:03 | 24.40 | 22.09 | 0.190691E+10 | 2606.66 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.214867E+11 | 35471.14 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207050E+10 | 2606.54 | 30-MAY-13:09 | 25.97 | 24.15 |
June | 0.219407E+11 | 32289.18 | 20-JUN-04:02 | 24.90 | 23.73 | 0.206563E+10 | 2606.54 | 05-JUN-13:09 | 24.90 | 23.73 |
July | 0.220762E+11 | 32897.51 | 06-JUL-04:02 | 23.90 | 22.27 | 0.191883E+10 | 2606.54 | 31-JUL-13:09 | 31.47 | 25.13 |
August | 0.227382E+11 | 32070.40 | 08-AUG-04:02 | 26.10 | 23.70 | 0.215459E+10 | 2606.54 | 07-AUG-13:30 | 26.10 | 23.70 |
September | 0.212398E+11 | 32997.66 | 12-SEP-04:02 | 24.40 | 22.75 | 0.191221E+10 | 2606.54 | 11-SEP-13:50 | 24.40 | 22.75 |
October | 0.210413E+11 | 33158.61 | 23-OCT-05:04 | 23.72 | 21.83 | 0.198828E+10 | 2606.57 | 18-OCT-09:09 | 23.72 | 21.83 |
November | 0.183500E+11 | 32629.32 | 20-NOV-05:02 | 24.40 | 20.52 | 0.196375E+10 | 2606.65 | 13-NOV-10:09 | 24.40 | 20.52 |
December | 0.163486E+11 | 30685.60 | 09-DEC-06:03 | 24.90 | 22.63 | 0.188799E+10 | 2606.62 | 04-DEC-10:20 | 24.90 | 22.63 |
Annual Sum or Average | 0.234448E+12 | 0.237476E+11 | ||||||||
Minimum of Months | 0.153974E+11 | 17411.19 | 23.62 | 19.12 | 0.178258E+10 | 2606.54 | 23.07 | 17.34 | ||
Maximum of Months | 0.227382E+11 | 35471.14 | 27.20 | 23.73 | 0.215459E+10 | 2606.68 | 31.47 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156048E+11 | 19125.75 | 02-JAN-15:00 | 28.90 | 23.37 | 0.188987E+10 | 2606.60 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.151769E+11 | 17897.50 | 21-FEB-16:00 | 26.10 | 14.02 | 0.174608E+10 | 2606.60 | 16-FEB-10:09 | 26.10 | 14.02 |
March | 0.188284E+11 | 19651.64 | 27-MAR-15:40 | 27.40 | 22.26 | 0.210298E+10 | 2606.64 | 02-MAR-14:09 | 27.40 | 22.26 |
April | 0.197841E+11 | 33899.93 | 13-APR-05:03 | 24.40 | 22.09 | 0.189802E+10 | 2606.67 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.229424E+11 | 35315.05 | 23-MAY-04:02 | 24.90 | 21.94 | 0.206789E+10 | 2606.55 | 08-MAY-09:09 | 24.90 | 21.94 |
June | 0.236688E+11 | 36073.78 | 19-JUN-04:02 | 24.40 | 22.82 | 0.206508E+10 | 2606.54 | 05-JUN-13:09 | 24.40 | 22.82 |
July | 0.239602E+11 | 35713.71 | 24-JUL-04:02 | 24.32 | 23.63 | 0.191863E+10 | 2606.54 | 25-JUL-13:09 | 32.30 | 25.97 |
August | 0.242320E+11 | 35033.81 | 07-AUG-04:02 | 25.68 | 24.34 | 0.215266E+10 | 2606.54 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.224409E+11 | 34996.63 | 25-SEP-04:02 | 24.40 | 22.60 | 0.191044E+10 | 2606.54 | 11-SEP-13:00 | 24.40 | 22.60 |
October | 0.214685E+11 | 35708.57 | 10-OCT-04:02 | 24.32 | 22.47 | 0.198261E+10 | 2606.64 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.182322E+11 | 33885.69 | 20-NOV-06:03 | 24.40 | 20.29 | 0.194415E+10 | 2606.62 | 02-NOV-09:09 | 24.40 | 20.29 |
December | 0.159317E+11 | 21140.13 | 09-DEC-06:03 | 24.90 | 22.63 | 0.182765E+10 | 2606.64 | 05-DEC-10:20 | 24.90 | 22.63 |
Annual Sum or Average | 0.242271E+12 | 0.235060E+11 | ||||||||
Minimum of Months | 0.151769E+11 | 17897.50 | 24.32 | 14.02 | 0.174608E+10 | 2606.54 | 24.40 | 14.02 | ||
Maximum of Months | 0.242320E+11 | 36073.78 | 28.90 | 24.34 | 0.215266E+10 | 2606.67 | 32.30 | 25.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321611E+10 | 5105.35 | 02-JAN-15:00 | 28.90 | 23.37 | 0.384736E+09 | 549.49 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.343364E+10 | 5252.22 | 17-FEB-14:10 | 26.70 | 21.67 | 0.362097E+09 | 549.49 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.443056E+10 | 5772.26 | 27-MAR-15:00 | 27.80 | 22.40 | 0.434295E+09 | 549.49 | 02-MAR-14:09 | 27.80 | 22.40 |
April | 0.519954E+10 | 7755.75 | 16-APR-16:42 | 31.02 | 22.09 | 0.399566E+09 | 549.50 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.686636E+10 | 12203.17 | 29-MAY-13:23 | 32.75 | 25.26 | 0.437306E+09 | 549.47 | 22-MAY-13:00 | 32.75 | 25.26 |
June | 0.754654E+10 | 12268.30 | 11-JUN-15:52 | 31.10 | 24.23 | 0.436616E+09 | 549.47 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.774132E+10 | 12267.81 | 30-JUL-11:32 | 33.33 | 24.76 | 0.406042E+09 | 549.47 | 19-JUL-13:00 | 33.33 | 24.76 |
August | 0.737093E+10 | 12300.31 | 06-AUG-15:22 | 30.00 | 24.59 | 0.455068E+09 | 549.48 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.662551E+10 | 10588.37 | 18-SEP-04:02 | 27.80 | 24.12 | 0.403784E+09 | 549.47 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.571581E+10 | 9997.60 | 02-OCT-04:02 | 26.70 | 25.03 | 0.418619E+09 | 549.49 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.444147E+10 | 6056.47 | 30-NOV-06:03 | 25.60 | 24.37 | 0.407324E+09 | 549.49 | 14-NOV-14:20 | 25.60 | 24.37 |
December | 0.339647E+10 | 5047.96 | 08-DEC-14:10 | 27.70 | 22.74 | 0.374029E+09 | 549.48 | 01-DEC-10:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.659843E+11 | 0.491948E+10 | ||||||||
Minimum of Months | 0.321611E+10 | 5047.96 | 25.60 | 21.67 | 0.362097E+09 | 549.47 | 25.00 | 16.72 | ||
Maximum of Months | 0.774132E+10 | 12300.31 | 33.33 | 25.26 | 0.455068E+09 | 549.50 | 33.33 | 25.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291427E+10 | 9371.88 | 01-JAN-09:53 | 25.00 | 21.12 | 0.254109E+09 | 347.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.318044E+10 | 5052.96 | 28-FEB-10:10 | 24.40 | 16.25 | 0.234101E+09 | 347.88 | 23-FEB-10:00 | 24.40 | 16.25 |
March | 0.421357E+10 | 6673.82 | 27-MAR-10:30 | 25.85 | 21.67 | 0.283097E+09 | 347.87 | 02-MAR-14:09 | 25.85 | 21.67 |
April | 0.495136E+10 | 12080.68 | 09-APR-09:02 | 24.27 | 18.85 | 0.253864E+09 | 347.88 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.584386E+10 | 11342.71 | 14-MAY-10:23 | 29.15 | 23.76 | 0.276644E+09 | 347.86 | 31-MAY-09:39 | 30.53 | 23.99 |
June | 0.611296E+10 | 12794.11 | 11-JUN-09:12 | 30.20 | 24.17 | 0.276333E+09 | 347.86 | 14-JUN-09:39 | 28.53 | 23.70 |
July | 0.634592E+10 | 12642.37 | 04-JUL-11:22 | 31.70 | 25.31 | 0.257125E+09 | 347.86 | 06-JUL-13:00 | 32.20 | 25.37 |
August | 0.608532E+10 | 12071.15 | 06-AUG-10:43 | 30.82 | 24.91 | 0.287903E+09 | 347.86 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.562551E+10 | 9553.36 | 04-SEP-10:43 | 28.98 | 23.72 | 0.255605E+09 | 347.86 | 14-SEP-09:39 | 29.27 | 25.00 |
October | 0.506035E+10 | 9220.66 | 09-OCT-11:43 | 28.95 | 24.01 | 0.265069E+09 | 347.87 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.382823E+10 | 5868.51 | 07-NOV-09:50 | 25.32 | 21.18 | 0.260120E+09 | 347.88 | 02-NOV-09:09 | 25.32 | 21.18 |
December | 0.290095E+10 | 4907.16 | 08-DEC-10:30 | 26.65 | 22.70 | 0.241177E+09 | 347.88 | 04-DEC-10:00 | 26.65 | 22.70 |
Annual Sum or Average | 0.570627E+11 | 0.314515E+10 | ||||||||
Minimum of Months | 0.290095E+10 | 4907.16 | 24.27 | 16.25 | 0.234101E+09 | 347.86 | 21.70 | 15.05 | ||
Maximum of Months | 0.634592E+10 | 12794.11 | 31.70 | 25.31 | 0.287903E+09 | 347.88 | 32.20 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622611E+10 | 13954.43 | 01-JAN-13:12 | 26.83 | 21.65 | 0.408469E+09 | 599.55 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.597302E+10 | 14420.67 | 20-FEB-14:12 | 26.30 | 17.81 | 0.373700E+09 | 582.34 | 21-FEB-14:30 | 25.85 | 14.25 |
March | 0.652998E+10 | 13263.63 | 26-MAR-13:32 | 27.60 | 22.33 | 0.443652E+09 | 554.97 | 01-MAR-14:30 | 27.60 | 22.33 |
April | 0.614481E+10 | 12655.85 | 16-APR-12:02 | 30.78 | 21.05 | 0.400215E+09 | 549.50 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.685464E+10 | 12571.91 | 29-MAY-13:23 | 32.75 | 25.26 | 0.437029E+09 | 549.47 | 22-MAY-13:00 | 32.75 | 25.26 |
June | 0.720077E+10 | 12418.83 | 11-JUN-15:52 | 31.10 | 24.23 | 0.436368E+09 | 549.47 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.756060E+10 | 12790.55 | 30-JUL-11:32 | 33.33 | 24.76 | 0.405845E+09 | 549.47 | 19-JUL-13:00 | 33.33 | 24.76 |
August | 0.792381E+10 | 12939.51 | 20-AUG-12:43 | 32.20 | 25.64 | 0.455133E+09 | 549.48 | 07-AUG-13:00 | 32.20 | 25.64 |
September | 0.814939E+10 | 12914.03 | 17-SEP-14:32 | 31.10 | 24.59 | 0.404269E+09 | 559.15 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.850593E+10 | 13517.50 | 15-OCT-15:42 | 28.98 | 20.79 | 0.421339E+09 | 576.08 | 25-OCT-13:20 | 30.20 | 22.36 |
November | 0.738323E+10 | 13889.96 | 19-NOV-14:32 | 26.70 | 20.85 | 0.415750E+09 | 600.07 | 07-NOV-14:09 | 26.70 | 20.85 |
December | 0.638891E+10 | 14418.99 | 10-DEC-12:52 | 28.30 | 23.48 | 0.393905E+09 | 600.78 | 04-DEC-14:39 | 28.30 | 23.48 |
Annual Sum or Average | 0.848412E+11 | 0.499567E+10 | ||||||||
Minimum of Months | 0.597302E+10 | 12418.83 | 26.30 | 17.81 | 0.373700E+09 | 549.47 | 25.50 | 14.25 | ||
Maximum of Months | 0.850593E+10 | 14420.67 | 33.33 | 25.64 | 0.455133E+09 | 600.78 | 33.33 | 25.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309541E+10 | 5675.70 | 03-JAN-15:40 | 26.70 | 20.74 | 0.238427E+09 | 347.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.333144E+10 | 14098.32 | 20-FEB-17:32 | 25.57 | 17.57 | 0.224508E+09 | 347.84 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.441795E+10 | 11854.54 | 12-MAR-16:52 | 24.40 | 18.65 | 0.270552E+09 | 347.84 | 02-MAR-14:09 | 24.40 | 18.65 |
April | 0.497571E+10 | 14185.66 | 02-APR-15:42 | 26.70 | 18.26 | 0.249964E+09 | 347.84 | 17-APR-09:09 | 22.15 | 19.68 |
May | 0.579487E+10 | 13888.89 | 29-MAY-16:42 | 31.97 | 24.40 | 0.275188E+09 | 347.84 | 23-MAY-13:00 | 31.97 | 24.40 |
June | 0.572299E+10 | 13800.91 | 11-JUN-15:52 | 31.10 | 24.23 | 0.275285E+09 | 347.84 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.611934E+10 | 13825.04 | 09-JUL-16:52 | 30.00 | 25.18 | 0.256126E+09 | 347.84 | 19-JUL-13:00 | 27.80 | 25.31 |
August | 0.606783E+10 | 13780.67 | 06-AUG-15:22 | 30.00 | 24.59 | 0.287069E+09 | 347.84 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.535471E+10 | 13883.03 | 17-SEP-16:32 | 31.10 | 24.71 | 0.254146E+09 | 347.84 | 11-SEP-13:00 | 31.10 | 24.71 |
October | 0.496519E+10 | 14040.87 | 15-OCT-15:42 | 28.98 | 20.79 | 0.262938E+09 | 347.85 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.393194E+10 | 10581.99 | 05-NOV-15:53 | 27.80 | 24.12 | 0.254062E+09 | 347.84 | 14-NOV-14:00 | 23.90 | 15.88 |
December | 0.327439E+10 | 13498.68 | 10-DEC-14:52 | 28.90 | 22.68 | 0.232592E+09 | 347.84 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.570518E+11 | 0.308086E+10 | ||||||||
Minimum of Months | 0.309541E+10 | 5675.70 | 24.40 | 17.57 | 0.224508E+09 | 347.84 | 21.70 | 13.99 | ||
Maximum of Months | 0.611934E+10 | 14185.66 | 31.97 | 25.18 | 0.287069E+09 | 347.85 | 31.97 | 25.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349188E+10 | 4623.00 | 02-JAN-15:00 | 28.90 | 23.37 | 0.401571E+09 | 549.48 | 05-JAN-10:00 | 20.60 | 17.38 |
February | 0.342170E+10 | 4624.50 | 17-FEB-13:40 | 26.70 | 21.06 | 0.370973E+09 | 549.49 | 28-FEB-10:39 | 24.40 | 16.17 |
March | 0.412475E+10 | 4852.78 | 06-MAR-14:10 | 24.90 | 22.15 | 0.441024E+09 | 549.48 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.462668E+10 | 5848.81 | 17-APR-15:20 | 32.03 | 19.94 | 0.401568E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.628806E+10 | 8234.24 | 24-MAY-05:02 | 23.98 | 22.69 | 0.437410E+09 | 549.47 | 22-MAY-13:00 | 23.98 | 22.69 |
June | 0.696527E+10 | 8716.58 | 05-JUN-04:02 | 25.60 | 23.64 | 0.436394E+09 | 549.48 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.733490E+10 | 8381.66 | 31-JUL-04:02 | 26.10 | 24.52 | 0.405887E+09 | 549.47 | 19-JUL-13:00 | 26.10 | 24.52 |
August | 0.730208E+10 | 8600.63 | 15-AUG-04:02 | 27.80 | 25.24 | 0.455360E+09 | 549.48 | 07-AUG-13:00 | 27.80 | 25.24 |
September | 0.670829E+10 | 9152.03 | 10-SEP-15:31 | 31.10 | 25.07 | 0.404283E+09 | 549.47 | 07-SEP-13:00 | 31.10 | 25.07 |
October | 0.601273E+10 | 7883.88 | 26-OCT-05:02 | 23.80 | 22.28 | 0.420123E+09 | 549.48 | 10-OCT-13:09 | 23.80 | 22.28 |
November | 0.472513E+10 | 5450.19 | 03-NOV-13:50 | 29.40 | 24.41 | 0.413628E+09 | 549.49 | 14-NOV-10:09 | 22.30 | 16.07 |
December | 0.368806E+10 | 4836.08 | 01-DEC-14:10 | 26.10 | 19.79 | 0.391221E+09 | 549.48 | 12-DEC-14:09 | 18.80 | 13.12 |
Annual Sum or Average | 0.646895E+11 | 0.497944E+10 | ||||||||
Minimum of Months | 0.342170E+10 | 4623.00 | 23.80 | 19.79 | 0.370973E+09 | 549.47 | 18.80 | 13.12 | ||
Maximum of Months | 0.733490E+10 | 9152.03 | 32.03 | 25.24 | 0.455360E+09 | 549.50 | 31.10 | 25.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314345E+10 | 10624.30 | 01-JAN-10:42 | 26.42 | 21.52 | 0.262167E+09 | 347.89 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.316924E+10 | 4870.08 | 28-FEB-10:00 | 24.40 | 16.28 | 0.238547E+09 | 347.88 | 23-FEB-10:20 | 24.40 | 16.28 |
March | 0.400083E+10 | 5955.14 | 27-MAR-10:30 | 25.85 | 21.67 | 0.285937E+09 | 347.88 | 01-MAR-10:09 | 25.85 | 21.67 |
April | 0.455245E+10 | 10856.92 | 09-APR-10:12 | 26.30 | 18.69 | 0.255250E+09 | 347.88 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.543653E+10 | 8381.30 | 14-MAY-10:23 | 29.15 | 23.76 | 0.277081E+09 | 347.86 | 31-MAY-09:39 | 30.53 | 23.99 |
June | 0.571393E+10 | 11081.87 | 11-JUN-09:12 | 30.20 | 24.17 | 0.276477E+09 | 347.86 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.606092E+10 | 11539.54 | 23-JUL-10:22 | 31.65 | 24.80 | 0.257334E+09 | 347.86 | 07-JUL-09:20 | 31.65 | 24.80 |
August | 0.603870E+10 | 10353.55 | 06-AUG-10:43 | 30.82 | 24.91 | 0.288461E+09 | 347.86 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.570481E+10 | 11055.87 | 10-SEP-09:32 | 29.43 | 24.83 | 0.256253E+09 | 347.86 | 14-SEP-09:39 | 29.27 | 25.00 |
October | 0.526727E+10 | 8247.52 | 22-OCT-11:13 | 28.70 | 22.74 | 0.266307E+09 | 347.86 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.403691E+10 | 5588.46 | 07-NOV-09:30 | 24.75 | 21.38 | 0.262785E+09 | 347.88 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.305959E+10 | 4720.37 | 08-DEC-10:30 | 26.65 | 22.70 | 0.251357E+09 | 347.87 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.561846E+11 | 0.317795E+10 | ||||||||
Minimum of Months | 0.305959E+10 | 4720.37 | 24.40 | 16.28 | 0.238547E+09 | 347.86 | 19.08 | 15.05 | ||
Maximum of Months | 0.606092E+10 | 11539.54 | 31.65 | 24.91 | 0.288461E+09 | 347.89 | 31.65 | 25.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613608E+10 | 11784.95 | 01-JAN-13:22 | 26.65 | 21.70 | 0.413897E+09 | 632.41 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.604053E+10 | 11405.49 | 19-FEB-14:02 | 27.20 | 21.86 | 0.378140E+09 | 600.07 | 22-FEB-13:09 | 27.20 | 14.13 |
March | 0.611051E+10 | 9428.03 | 13-MAR-16:20 | 29.23 | 22.27 | 0.443168E+09 | 562.38 | 01-MAR-14:50 | 29.23 | 22.27 |
April | 0.610720E+10 | 9857.88 | 17-APR-16:10 | 31.60 | 20.14 | 0.401954E+09 | 604.36 | 13-APR-12:09 | 31.60 | 20.14 |
May | 0.755803E+10 | 10579.44 | 22-MAY-12:00 | 33.30 | 23.06 | 0.439720E+09 | 666.81 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.807957E+10 | 9794.95 | 09-JUN-12:00 | 31.10 | 24.24 | 0.438999E+09 | 609.26 | 09-JUN-12:09 | 31.02 | 24.35 |
July | 0.872363E+10 | 10794.30 | 27-JUL-16:50 | 34.50 | 24.87 | 0.410698E+09 | 676.76 | 31-JUL-12:09 | 32.93 | 25.13 |
August | 0.954824E+10 | 10732.50 | 20-AUG-12:43 | 32.20 | 25.64 | 0.461754E+09 | 673.01 | 23-AUG-12:09 | 33.40 | 24.17 |
September | 0.939424E+10 | 11267.42 | 10-SEP-13:32 | 31.10 | 24.95 | 0.414144E+09 | 660.83 | 11-SEP-12:09 | 31.52 | 24.53 |
October | 0.977618E+10 | 11963.01 | 29-OCT-12:32 | 30.20 | 25.52 | 0.434469E+09 | 670.37 | 03-OCT-12:09 | 30.20 | 25.52 |
November | 0.824364E+10 | 11272.19 | 19-NOV-11:23 | 26.70 | 21.51 | 0.424827E+09 | 639.38 | 08-NOV-13:09 | 26.70 | 21.51 |
December | 0.636056E+10 | 11952.68 | 10-DEC-12:52 | 28.30 | 23.48 | 0.399442E+09 | 623.96 | 04-DEC-14:39 | 28.30 | 23.48 |
Annual Sum or Average | 0.920784E+11 | 0.506121E+10 | ||||||||
Minimum of Months | 0.604053E+10 | 9428.03 | 26.65 | 20.14 | 0.378140E+09 | 562.38 | 26.70 | 14.13 | ||
Maximum of Months | 0.977618E+10 | 11963.01 | 34.50 | 25.64 | 0.461754E+09 | 676.76 | 33.48 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306428E+10 | 5026.41 | 02-JAN-16:30 | 25.30 | 20.50 | 0.254878E+09 | 347.84 | 20-JAN-14:00 | 19.40 | 12.60 |
February | 0.313180E+10 | 11519.71 | 19-FEB-17:22 | 25.85 | 21.44 | 0.235206E+09 | 347.84 | 21-FEB-10:09 | 19.78 | 16.20 |
March | 0.400155E+10 | 9169.34 | 12-MAR-16:52 | 24.40 | 18.65 | 0.280545E+09 | 347.84 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.445901E+10 | 11562.52 | 02-APR-15:42 | 26.70 | 18.26 | 0.254741E+09 | 347.85 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.529279E+10 | 11267.90 | 29-MAY-14:53 | 32.80 | 24.31 | 0.276918E+09 | 347.84 | 22-MAY-13:00 | 32.80 | 24.31 |
June | 0.521711E+10 | 11445.62 | 11-JUN-15:52 | 31.10 | 24.23 | 0.276204E+09 | 347.84 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.574024E+10 | 11496.58 | 09-JUL-16:52 | 30.00 | 25.18 | 0.257054E+09 | 347.84 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.594871E+10 | 11419.12 | 20-AUG-16:42 | 30.60 | 24.86 | 0.288406E+09 | 347.84 | 07-AUG-13:00 | 30.60 | 24.86 |
September | 0.532175E+10 | 12153.96 | 10-SEP-15:31 | 31.10 | 25.07 | 0.256076E+09 | 347.84 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.507934E+10 | 11528.75 | 15-OCT-15:32 | 29.07 | 20.86 | 0.266177E+09 | 347.84 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.397174E+10 | 6538.23 | 07-NOV-16:30 | 28.05 | 22.28 | 0.261739E+09 | 347.84 | 14-NOV-10:39 | 22.60 | 16.10 |
December | 0.329675E+10 | 10361.21 | 10-DEC-14:52 | 28.90 | 22.68 | 0.247648E+09 | 347.84 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.545251E+11 | 0.315559E+10 | ||||||||
Minimum of Months | 0.306428E+10 | 5026.41 | 24.40 | 18.26 | 0.235206E+09 | 347.84 | 19.40 | 12.60 | ||
Maximum of Months | 0.594871E+10 | 12153.96 | 32.80 | 25.18 | 0.288406E+09 | 347.85 | 32.80 | 24.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332633E+10 | 4861.48 | 02-JAN-15:00 | 28.90 | 23.37 | 0.397627E+09 | 549.48 | 10-JAN-14:39 | 22.20 | 16.44 |
February | 0.344918E+10 | 4876.54 | 17-FEB-13:40 | 26.70 | 21.06 | 0.369675E+09 | 549.50 | 23-FEB-10:50 | 24.13 | 18.14 |
March | 0.434390E+10 | 5229.20 | 28-MAR-13:30 | 27.20 | 20.57 | 0.441728E+09 | 549.48 | 22-MAR-13:00 | 27.20 | 20.57 |
April | 0.494683E+10 | 6374.71 | 17-APR-15:20 | 32.03 | 19.94 | 0.401908E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.644580E+10 | 10697.48 | 29-MAY-15:51 | 33.30 | 24.52 | 0.437666E+09 | 549.47 | 22-MAY-13:00 | 33.30 | 24.52 |
June | 0.703839E+10 | 8992.29 | 05-JUN-04:02 | 25.60 | 23.64 | 0.436612E+09 | 549.47 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.717023E+10 | 9286.42 | 30-JUL-11:32 | 33.33 | 24.76 | 0.406019E+09 | 549.47 | 19-JUL-13:00 | 33.33 | 24.76 |
August | 0.693831E+10 | 9508.69 | 06-AUG-15:22 | 30.00 | 24.59 | 0.455306E+09 | 549.48 | 07-AUG-13:30 | 28.60 | 24.70 |
September | 0.626065E+10 | 10408.82 | 10-SEP-15:31 | 31.10 | 25.07 | 0.404138E+09 | 549.47 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.556796E+10 | 8522.70 | 30-OCT-04:02 | 26.28 | 24.93 | 0.419723E+09 | 549.48 | 18-OCT-09:09 | 26.28 | 24.93 |
November | 0.442156E+10 | 6974.88 | 30-NOV-06:03 | 25.60 | 24.37 | 0.411742E+09 | 549.49 | 15-NOV-10:09 | 25.60 | 24.37 |
December | 0.346738E+10 | 4892.92 | 09-DEC-06:03 | 24.90 | 22.63 | 0.385738E+09 | 549.49 | 04-DEC-10:09 | 24.90 | 22.63 |
Annual Sum or Average | 0.633765E+11 | 0.496788E+10 | ||||||||
Minimum of Months | 0.332633E+10 | 4861.48 | 24.90 | 19.94 | 0.369675E+09 | 549.47 | 22.20 | 16.44 | ||
Maximum of Months | 0.717023E+10 | 10697.48 | 33.33 | 25.07 | 0.455306E+09 | 549.50 | 33.33 | 24.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299772E+10 | 11423.02 | 01-JAN-10:13 | 25.57 | 21.29 | 0.189768E+09 | 338.74 | 27-JAN-11:09 | 21.88 | 15.22 |
February | 0.316144E+10 | 5465.56 | 28-FEB-09:50 | 24.22 | 16.33 | 0.174111E+09 | 338.73 | 27-FEB-11:09 | 24.22 | 16.33 |
March | 0.412696E+10 | 7350.71 | 26-MAR-10:02 | 25.60 | 21.37 | 0.209365E+09 | 338.73 | 17-MAR-10:30 | 25.60 | 21.37 |
April | 0.470301E+10 | 12448.99 | 16-APR-09:52 | 27.20 | 21.71 | 0.188052E+09 | 338.73 | 20-APR-10:20 | 24.97 | 18.53 |
May | 0.545981E+10 | 11046.20 | 07-MAY-08:32 | 26.33 | 21.77 | 0.204633E+09 | 338.72 | 09-MAY-07:19 | 25.77 | 20.66 |
June | 0.565999E+10 | 12221.35 | 11-JUN-09:12 | 30.20 | 24.17 | 0.204139E+09 | 338.72 | 09-JUN-12:20 | 30.20 | 24.17 |
July | 0.585425E+10 | 12665.23 | 23-JUL-09:02 | 30.50 | 25.12 | 0.190588E+09 | 338.72 | 07-JUL-12:20 | 30.50 | 25.12 |
August | 0.567560E+10 | 11285.07 | 06-AUG-10:43 | 30.82 | 24.91 | 0.212710E+09 | 338.72 | 23-AUG-12:20 | 33.50 | 24.43 |
September | 0.526878E+10 | 12114.78 | 10-SEP-09:32 | 29.43 | 24.83 | 0.189269E+09 | 338.71 | 27-SEP-12:20 | 30.93 | 23.96 |
October | 0.486193E+10 | 11971.42 | 09-OCT-08:52 | 28.30 | 24.27 | 0.196500E+09 | 338.72 | 17-OCT-07:30 | 24.45 | 18.70 |
November | 0.375191E+10 | 6112.45 | 07-NOV-09:30 | 24.75 | 21.38 | 0.193095E+09 | 338.73 | 13-NOV-11:20 | 21.83 | 15.41 |
December | 0.293277E+10 | 4881.07 | 08-DEC-10:00 | 26.10 | 22.56 | 0.180860E+09 | 338.72 | 06-DEC-08:20 | 26.10 | 22.56 |
Annual Sum or Average | 0.544542E+11 | 0.233309E+10 | ||||||||
Minimum of Months | 0.293277E+10 | 4881.07 | 24.22 | 16.33 | 0.174111E+09 | 338.71 | 21.83 | 15.22 | ||
Maximum of Months | 0.585425E+10 | 12665.23 | 30.82 | 25.12 | 0.212710E+09 | 338.74 | 33.50 | 25.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639017E+10 | 11682.50 | 15-JAN-11:43 | 24.72 | 17.05 | 0.416814E+09 | 624.25 | 02-JAN-14:39 | 24.72 | 17.05 |
February | 0.595545E+10 | 11943.28 | 19-FEB-14:02 | 27.20 | 21.86 | 0.379417E+09 | 605.22 | 21-FEB-14:20 | 25.77 | 14.45 |
March | 0.642577E+10 | 11390.23 | 26-MAR-13:23 | 27.50 | 22.30 | 0.449020E+09 | 575.85 | 01-MAR-14:30 | 27.50 | 22.30 |
April | 0.585381E+10 | 11126.58 | 16-APR-14:32 | 31.70 | 21.16 | 0.402459E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.642876E+10 | 10843.12 | 29-MAY-15:51 | 33.30 | 24.52 | 0.437548E+09 | 549.47 | 22-MAY-13:00 | 33.30 | 24.52 |
June | 0.670944E+10 | 9079.04 | 28-JUN-04:02 | 27.62 | 23.78 | 0.436432E+09 | 549.47 | 21-JUN-13:00 | 27.62 | 23.78 |
July | 0.699604E+10 | 10845.19 | 30-JUL-11:32 | 33.33 | 24.76 | 0.405882E+09 | 549.47 | 19-JUL-13:00 | 33.33 | 24.76 |
August | 0.746113E+10 | 11071.50 | 20-AUG-12:43 | 32.20 | 25.64 | 0.455417E+09 | 552.01 | 31-AUG-13:09 | 31.70 | 24.44 |
September | 0.769456E+10 | 11591.58 | 10-SEP-13:32 | 31.10 | 24.95 | 0.404892E+09 | 571.39 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.823012E+10 | 12486.09 | 29-OCT-12:32 | 30.20 | 25.52 | 0.424392E+09 | 592.37 | 25-OCT-13:20 | 30.20 | 25.52 |
November | 0.727128E+10 | 11719.82 | 19-NOV-11:23 | 26.70 | 21.51 | 0.420669E+09 | 621.86 | 07-NOV-14:09 | 26.70 | 21.51 |
December | 0.647983E+10 | 11727.69 | 03-DEC-14:02 | 24.40 | 18.40 | 0.401451E+09 | 625.53 | 04-DEC-14:30 | 25.85 | 18.01 |
Annual Sum or Average | 0.818964E+11 | 0.503439E+10 | ||||||||
Minimum of Months | 0.585381E+10 | 9079.04 | 24.40 | 17.05 | 0.379417E+09 | 549.47 | 24.40 | 14.45 | ||
Maximum of Months | 0.823012E+10 | 12486.09 | 33.33 | 25.64 | 0.455417E+09 | 625.53 | 33.33 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309926E+10 | 5507.02 | 03-JAN-15:30 | 26.70 | 20.80 | 0.247425E+09 | 347.84 | 27-JAN-14:00 | 22.80 | 16.55 |
February | 0.325000E+10 | 12536.13 | 19-FEB-17:22 | 25.85 | 21.44 | 0.230810E+09 | 347.84 | 27-FEB-14:39 | 26.10 | 16.60 |
March | 0.425937E+10 | 11490.42 | 12-MAR-17:53 | 22.80 | 18.84 | 0.276566E+09 | 347.84 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.468356E+10 | 13222.30 | 02-APR-16:12 | 26.33 | 18.20 | 0.253119E+09 | 347.85 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.541109E+10 | 13318.19 | 29-MAY-15:51 | 33.30 | 24.52 | 0.276348E+09 | 347.84 | 23-MAY-13:00 | 33.30 | 24.52 |
June | 0.530463E+10 | 12389.87 | 11-JUN-15:52 | 31.10 | 24.23 | 0.275895E+09 | 347.84 | 21-JUN-13:00 | 29.40 | 23.81 |
July | 0.564595E+10 | 12601.50 | 09-JUL-16:52 | 30.00 | 25.18 | 0.256644E+09 | 347.84 | 19-JUL-13:00 | 27.80 | 25.31 |
August | 0.568559E+10 | 12462.57 | 20-AUG-16:42 | 30.60 | 24.86 | 0.287797E+09 | 347.84 | 07-AUG-13:30 | 30.60 | 24.86 |
September | 0.500898E+10 | 13382.47 | 10-SEP-15:31 | 31.10 | 25.07 | 0.255287E+09 | 347.84 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.476540E+10 | 12675.10 | 15-OCT-15:32 | 29.07 | 20.86 | 0.264909E+09 | 347.84 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.381904E+10 | 9440.34 | 05-NOV-15:23 | 27.80 | 23.97 | 0.258473E+09 | 347.84 | 27-NOV-14:50 | 23.90 | 17.26 |
December | 0.325171E+10 | 8231.46 | 03-DEC-16:42 | 23.98 | 16.39 | 0.240523E+09 | 347.84 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.541846E+11 | 0.312380E+10 | ||||||||
Minimum of Months | 0.309926E+10 | 5507.02 | 22.80 | 16.39 | 0.230810E+09 | 347.84 | 21.70 | 13.99 | ||
Maximum of Months | 0.568559E+10 | 13382.47 | 33.30 | 25.18 | 0.287797E+09 | 347.85 | 33.30 | 25.31 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309958E+09 | 4276.41 | 25-JAN-06:03 | 9.40 |
February | 0.197282E+09 | 4467.50 | 04-FEB-06:03 | 5.50 |
March | 0.207027E+09 | 4556.76 | 16-MAR-05:02 | 6.70 |
April | 38390337.17 | 3418.45 | 12-APR-05:03 | 24.50 |
May | 17448273.75 | 4900.93 | 08-MAY-05:01 | 23.90 |
June | 17427445.87 | 4841.15 | 06-JUN-05:02 | 23.98 |
July | 21442078.00 | 5350.03 | 05-JUL-04:02 | 25.60 |
August | 16406806.45 | 4482.88 | 31-AUG-05:03 | 25.60 |
September | 17379243.51 | 4270.07 | 12-SEP-05:03 | 24.40 |
October | 20661136.69 | 5280.64 | 23-OCT-05:02 | 23.72 |
November | 72205772.58 | 4300.62 | 27-NOV-06:02 | 10.00 |
December | 0.245183E+09 | 4386.29 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 0.118081E+10 | |||
Minimum of Months | 16406806.45 | 3418.45 | 5.50 | |
Maximum of Months | 0.309958E+09 | 5350.03 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28021109.22 | 2576.59 | 22-JAN-16:10 | 20.10 |
February | 18742147.30 | 3162.15 | 05-FEB-12:13 | 20.77 |
March | 6547505.30 | 1957.07 | 05-MAR-10:55 | 26.70 |
April | 9732225.35 | 1683.88 | 16-APR-15:12 | 31.33 |
May | 8572323.35 | 1944.02 | 24-MAY-05:02 | 23.98 |
June | 8563229.53 | 2445.40 | 08-JUN-04:02 | 28.80 |
July | 10300447.69 | 1968.65 | 19-JUL-04:02 | 26.78 |
August | 10279593.96 | 2340.95 | 18-AUG-04:02 | 27.70 |
September | 10294440.37 | 2372.10 | 22-SEP-04:02 | 27.80 |
October | 11279351.35 | 2257.40 | 30-OCT-04:02 | 26.28 |
November | 10486797.89 | 2238.98 | 30-NOV-06:03 | 25.60 |
December | 22101444.57 | 2390.80 | 24-DEC-10:58 | 26.70 |
Annual Sum or Average | 0.154921E+09 | |||
Minimum of Months | 6547505.30 | 1683.88 | 20.10 | |
Maximum of Months | 28021109.22 | 3162.15 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25773266.39 | 2839.20 | 14-JAN-05:03 | 23.90 |
February | 21281301.34 | 2987.48 | 05-FEB-12:13 | 20.77 |
March | 13860962.36 | 2095.27 | 05-MAR-11:02 | 26.97 |
April | 13480288.86 | 3271.10 | 12-APR-04:03 | 24.40 |
May | 18401206.47 | 3565.24 | 26-MAY-04:03 | 23.90 |
June | 18113832.99 | 3698.84 | 08-JUN-04:02 | 28.80 |
July | 19460869.25 | 3621.48 | 12-JUL-04:02 | 26.93 |
August | 20561946.79 | 3916.41 | 15-AUG-04:02 | 27.80 |
September | 22423991.78 | 4010.74 | 29-SEP-04:02 | 24.90 |
October | 22373462.55 | 3881.72 | 04-OCT-04:02 | 26.10 |
November | 21915700.24 | 3934.38 | 20-NOV-05:02 | 24.40 |
December | 23042282.19 | 3316.19 | 09-DEC-05:03 | 25.00 |
Annual Sum or Average | 0.240689E+09 | |||
Minimum of Months | 13480288.86 | 2095.27 | 20.77 | |
Maximum of Months | 25773266.39 | 4010.74 | 28.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 1309946.83 | 8732.98 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 1309946.83 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1309946.83 | 8732.98 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16556878.06 | 6766.24 | 10-JAN-07:03 | 13.07 |
February | 22287064.57 | 7006.70 | 04-FEB-06:12 | 5.40 |
March | 7750251.91 | 6518.47 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 1889895.65 | 6370.65 | 27-NOV-07:02 | 10.37 |
December | 15681346.66 | 6481.03 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 64165436.84 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 22287064.57 | 7006.70 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8840677.63 | 4385.76 | 09-JAN-07:03 | 12.38 |
February | 8382303.37 | 4334.02 | 04-FEB-06:14 | 5.40 |
March | 4604995.70 | 4380.42 | 16-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 762614.31 | 4054.20 | 27-NOV-07:02 | 10.37 |
December | 10507486.00 | 4497.66 | 14-DEC-07:02 | 15.78 |
Annual Sum or Average | 33098077.01 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 10507486.00 | 4497.66 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6981919.46 | 6514.30 | 23-JAN-07:03 | 13.58 |
February | 10791139.64 | 6781.28 | 04-FEB-06:12 | 5.40 |
March | 5199232.74 | 6758.19 | 21-MAR-06:02 | 10.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 739640.96 | 4009.91 | 27-NOV-07:02 | 10.37 |
December | 8835808.84 | 6368.96 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 32547741.64 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 10791139.64 | 6781.28 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12566096.01 | 4486.22 | 24-JAN-07:03 | 11.78 |
February | 15813147.53 | 4674.46 | 04-FEB-06:14 | 5.40 |
March | 5756982.48 | 4339.02 | 20-MAR-06:02 | 10.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 1227910.55 | 3939.44 | 13-NOV-07:02 | 12.30 |
December | 12436859.72 | 4392.77 | 20-DEC-07:03 | 11.60 |
Annual Sum or Average | 47800996.29 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 15813147.53 | 4674.46 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 329673.49 | 2197.82 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 329673.49 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 329673.49 | 2197.82 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 188478.57 | 1256.52 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 188478.57 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 188478.57 | 1256.52 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134907E+09 | 4277.11 | 27-JAN-08:00 | 13.30 |
February | 44037290.82 | 4378.75 | 22-FEB-07:40 | 12.43 |
March | 0.101472E+09 | 4551.60 | 16-MAR-07:00 | 6.70 |
April | 5468651.58 | 3489.05 | 19-APR-06:08 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 26709760.62 | 4245.76 | 13-NOV-07:40 | 12.60 |
December | 85116491.94 | 4299.78 | 13-DEC-08:00 | 13.90 |
Annual Sum or Average | 0.397712E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 0.134907E+09 | 4551.60 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 239597.85 | 1597.32 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 239597.85 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 239597.85 | 1597.32 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 986711.65 | 4814.93 | 25-JAN-07:02 | 9.50 |
February | 1990606.42 | 4791.73 | 04-FEB-07:03 | 5.28 |
March | 454962.39 | 5176.67 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 914658.77 | 4476.60 | 15-DEC-07:02 | 7.88 |
Annual Sum or Average | 4346939.23 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1990606.42 | 5176.67 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 928419.57 | 3435.84 | 26-JAN-07:02 | 10.68 |
February | 504723.70 | 3001.96 | 04-FEB-07:03 | 5.28 |
March | 324284.86 | 2627.51 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 1211256.89 | 2993.28 | 21-DEC-07:03 | 11.88 |
Annual Sum or Average | 2968685.02 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1211256.89 | 3435.84 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 775406.23 | 4668.51 | 04-FEB-07:03 | 5.28 |
March | 118139.64 | 1378.30 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 893545.87 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 775406.23 | 4668.51 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 812744.53 | 3332.40 | 26-JAN-07:02 | 10.68 |
February | 1360969.32 | 2894.84 | 04-FEB-07:03 | 5.28 |
March | 262675.43 | 2866.47 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 1349684.55 | 2928.46 | 21-DEC-07:03 | 11.88 |
Annual Sum or Average | 3786073.83 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 1360969.32 | 3332.40 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793023E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.681835E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.776649E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.672729E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708952E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.704881E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655155E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745007E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687532E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740619E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.764013E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.776232E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.870663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655155E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.793023E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.487511E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425800E+09 | 710.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483899E+09 | 600.14 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426437E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453041E+09 | 490.21 | 25-MAY-14:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452173E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418835E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472121E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434720E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.459707E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.476065E+09 | 750.07 | 08-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.482134E+09 | 860.01 | 06-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547244E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418835E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487511E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737989E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655566E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762327E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674910E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719906E+09 | 947.97 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723123E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.665687E+09 | 947.97 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749790E+09 | 1184.79 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683712E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.717248E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.725903E+09 | 1184.79 | 24-NOV-08:09 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.729878E+09 | 1358.45 | 15-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854604E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655566E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.762327E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481145E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421539E+09 | 710.03 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490128E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426526E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455062E+09 | 600.10 | 02-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455793E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421174E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477233E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436805E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465581E+09 | 859.95 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468962E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.470620E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547057E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421174E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490128E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788286E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.679013E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.773356E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.671588E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708201E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.703852E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.653792E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.743512E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.685989E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.737598E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.759869E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.771837E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.867689E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.653792E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.788286E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.485864E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.424707E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.482701E+09 | 490.21 | 06-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425698E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.452243E+09 | 490.21 | 25-MAY-15:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.451462E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418204E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471369E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433870E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.458742E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474879E+09 | 750.07 | 10-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.480611E+09 | 860.01 | 15-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546035E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418204E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.485864E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737091E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.654318E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.760886E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.673952E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.717827E+09 | 774.31 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.720925E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663955E+09 | 774.31 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.748291E+09 | 947.97 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682889E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.716290E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.724621E+09 | 1184.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.728697E+09 | 1358.45 | 15-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.852974E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.654318E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.760886E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479580E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.420137E+09 | 600.10 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488998E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425597E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.454186E+09 | 600.10 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.454579E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420250E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.476178E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435581E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464282E+09 | 750.02 | 18-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.467251E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.469078E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545570E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420137E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.488998E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.793023E+09 | 1184.79 | 04-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.681835E+09 | 947.97 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.776649E+09 | 1121.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.672717E+09 | 947.97 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.708952E+09 | 774.31 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.704881E+09 | 1184.79 | 15-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.655155E+09 | 774.31 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745007E+09 | 947.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687532E+09 | 1358.45 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.740619E+09 | 1184.79 | 18-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.764013E+09 | 1184.79 | 10-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.776232E+09 | 1358.45 | 15-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.870661E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.655155E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.793023E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.487511E+09 | 750.07 | 04-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.425800E+09 | 710.08 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483891E+09 | 600.14 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426437E+09 | 600.14 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.453041E+09 | 490.21 | 25-MAY-14:50 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.452173E+09 | 750.07 | 15-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.418835E+09 | 450.21 | 05-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472121E+09 | 600.14 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434720E+09 | 860.01 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.459707E+09 | 750.07 | 18-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.476065E+09 | 750.07 | 08-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.482134E+09 | 860.01 | 06-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547243E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.418835E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487511E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.737989E+09 | 1184.79 | 04-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.655566E+09 | 947.97 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762321E+09 | 947.97 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674897E+09 | 947.97 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.719906E+09 | 947.97 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723111E+09 | 1184.79 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.665687E+09 | 947.97 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749777E+09 | 1184.79 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683712E+09 | 1358.45 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.717248E+09 | 1184.79 | 18-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.725903E+09 | 1184.79 | 24-NOV-08:09 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.729878E+09 | 1358.45 | 15-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854599E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.655566E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.762321E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.481145E+09 | 750.02 | 04-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421539E+09 | 710.03 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490128E+09 | 750.02 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426526E+09 | 750.02 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.455062E+09 | 600.10 | 02-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455793E+09 | 859.95 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.421172E+09 | 600.10 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477233E+09 | 750.02 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436805E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465581E+09 | 859.95 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.468962E+09 | 750.02 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.470620E+09 | 859.95 | 15-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547057E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.421172E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490128E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.793023E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4848595.48 | 78323871.50 |
February | 0.901968E+09 | 0.681835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7705050.62 | 0.105957E+09 |
March | 0.107774E+10 | 0.776649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8328670.09 | 96986578.38 |
April | 0.956342E+09 | 0.672729E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18442218.43 | 43151084.27 |
May | 0.103597E+10 | 0.708952E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42545806.59 | 18053165.37 |
June | 0.103308E+10 | 0.704881E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50037099.24 | 5664643.50 |
July | 0.959235E+09 | 0.655155E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47125634.65 | 5447767.46 |
August | 0.107774E+10 | 0.745007E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55403727.22 | 2983576.17 |
September | 0.956342E+09 | 0.687532E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52032610.91 | 5372023.69 |
October | 0.994195E+09 | 0.740619E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34801441.03 | 11189705.36 |
November | 0.984487E+09 | 0.764013E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16534383.74 | 66137167.37 |
December | 0.959235E+09 | 0.776232E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6273856.39 | 78486216.56 |
Annual Sum or Average | 0.119305E+11 | 0.870663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344079E+09 | 0.517753E+09 |
Minimum of Months | 0.901968E+09 | 0.655155E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4848595.48 | 2983576.17 |
Maximum of Months | 0.107774E+10 | 0.793023E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55403727.22 | 0.105957E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.487511E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2403799.77 | 55582595.35 |
February | 0.571020E+09 | 0.425800E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4758952.35 | 74138282.29 |
March | 0.682301E+09 | 0.483899E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5361916.43 | 67571796.13 |
April | 0.605444E+09 | 0.426437E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10988474.89 | 30036106.95 |
May | 0.655854E+09 | 0.453041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28450160.48 | 12259113.09 |
June | 0.654023E+09 | 0.452173E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33558724.78 | 3809714.45 |
July | 0.607275E+09 | 0.418835E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31105247.60 | 3714871.42 |
August | 0.682301E+09 | 0.472121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36590487.40 | 1984904.78 |
September | 0.605444E+09 | 0.434720E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34029669.75 | 3669382.42 |
October | 0.629407E+09 | 0.459707E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22452532.06 | 7703177.10 |
November | 0.623262E+09 | 0.476065E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10932646.53 | 47073039.41 |
December | 0.607275E+09 | 0.482134E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3980540.26 | 53526924.55 |
Annual Sum or Average | 0.755301E+10 | 0.547244E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224613E+09 | 0.361070E+09 |
Minimum of Months | 0.571020E+09 | 0.418835E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2403799.77 | 1984904.78 |
Maximum of Months | 0.682301E+09 | 0.487511E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36590487.40 | 74138282.29 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737989E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2525298.82 | 94392966.09 |
February | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5408091.97 | 0.123472E+09 |
March | 0.107774E+10 | 0.762327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6986883.43 | 0.106799E+09 |
April | 0.956342E+09 | 0.674910E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15969734.00 | 45393448.41 |
May | 0.103597E+10 | 0.719906E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42942594.75 | 17984004.79 |
June | 0.103308E+10 | 0.723123E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50954106.68 | 5477835.24 |
July | 0.959235E+09 | 0.665687E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47859225.38 | 5273422.99 |
August | 0.107774E+10 | 0.749790E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54790667.28 | 3031623.95 |
September | 0.956342E+09 | 0.683712E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49287849.20 | 5771515.08 |
October | 0.994195E+09 | 0.717248E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29533561.51 | 13605758.91 |
November | 0.984487E+09 | 0.725903E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12868121.20 | 80162289.69 |
December | 0.959235E+09 | 0.729878E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3612411.46 | 92692507.13 |
Annual Sum or Average | 0.119305E+11 | 0.854604E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322739E+09 | 0.594056E+09 |
Minimum of Months | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2525298.82 | 3031623.95 |
Maximum of Months | 0.107774E+10 | 0.762327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54790667.28 | 0.123472E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481145E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3465354.71 | 53361183.73 |
February | 0.570983E+09 | 0.421539E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4969547.57 | 74051957.52 |
March | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6058953.92 | 69281774.62 |
April | 0.605404E+09 | 0.426526E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11989861.42 | 32888061.31 |
May | 0.655811E+09 | 0.455062E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28756336.37 | 13560361.38 |
June | 0.653980E+09 | 0.455793E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33513196.47 | 3837123.67 |
July | 0.607235E+09 | 0.421174E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31640333.53 | 3902549.79 |
August | 0.682256E+09 | 0.477233E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36277880.46 | 2093252.96 |
September | 0.605404E+09 | 0.436805E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34000954.80 | 3813495.01 |
October | 0.629366E+09 | 0.465581E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22667345.34 | 8397756.22 |
November | 0.623221E+09 | 0.468962E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11244823.51 | 45482839.78 |
December | 0.607235E+09 | 0.470620E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4249796.98 | 54111148.79 |
Annual Sum or Average | 0.755252E+10 | 0.547057E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228834E+09 | 0.364782E+09 |
Minimum of Months | 0.570983E+09 | 0.421174E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3465354.71 | 2093252.96 |
Maximum of Months | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36277880.46 | 74051957.52 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.788286E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2442182.87 | 49305766.22 |
February | 0.901968E+09 | 0.679013E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4223901.61 | 65447422.32 |
March | 0.107774E+10 | 0.773356E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4878258.71 | 56121186.23 |
April | 0.956342E+09 | 0.671588E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10930704.33 | 23975911.51 |
May | 0.103597E+10 | 0.708201E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24081697.04 | 9121080.27 |
June | 0.103308E+10 | 0.703852E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28234548.68 | 2520389.13 |
July | 0.959235E+09 | 0.653792E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26653016.87 | 2702498.68 |
August | 0.107774E+10 | 0.743512E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30431890.86 | 1696576.84 |
September | 0.956342E+09 | 0.685989E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29016316.79 | 3130706.51 |
October | 0.994195E+09 | 0.737598E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19401108.42 | 6767050.41 |
November | 0.984487E+09 | 0.759869E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8864195.73 | 41786249.12 |
December | 0.959235E+09 | 0.771837E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3321842.47 | 50092223.36 |
Annual Sum or Average | 0.119305E+11 | 0.867689E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192480E+09 | 0.312667E+09 |
Minimum of Months | 0.901968E+09 | 0.653792E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2442182.87 | 1696576.84 |
Maximum of Months | 0.107774E+10 | 0.788286E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30431890.86 | 65447422.32 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.485864E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164335.39 | 35488635.74 |
February | 0.571020E+09 | 0.424707E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2492075.27 | 46917476.85 |
March | 0.682301E+09 | 0.482701E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2872651.04 | 41011888.83 |
April | 0.605444E+09 | 0.425698E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6002243.34 | 18055311.01 |
May | 0.655854E+09 | 0.452243E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15304677.29 | 7007677.34 |
June | 0.654023E+09 | 0.451462E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18094194.44 | 1913260.01 |
July | 0.607275E+09 | 0.418204E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16824807.77 | 2130351.42 |
August | 0.682301E+09 | 0.471369E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19304968.23 | 1265188.67 |
September | 0.605444E+09 | 0.433870E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18132131.67 | 2361743.33 |
October | 0.629407E+09 | 0.458742E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11927034.39 | 5211755.53 |
November | 0.623262E+09 | 0.474879E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5518256.73 | 30112328.28 |
December | 0.607275E+09 | 0.480611E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1985868.05 | 34774348.29 |
Annual Sum or Average | 0.755301E+10 | 0.546035E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119623E+09 | 0.226250E+09 |
Minimum of Months | 0.571020E+09 | 0.418204E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164335.39 | 1265188.67 |
Maximum of Months | 0.682301E+09 | 0.485864E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19304968.23 | 46917476.85 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737091E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101744E+09 | 0.153366E+10 |
February | 0.901968E+09 | 0.654318E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224432E+09 | 0.704051E+09 |
March | 0.107774E+10 | 0.760886E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276506E+09 | 0.988489E+09 |
April | 0.956342E+09 | 0.673952E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661612E+09 | 0.235485E+09 |
May | 0.103597E+10 | 0.717827E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144350E+10 | 37531876.33 |
June | 0.103308E+10 | 0.720925E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165024E+10 | 5691646.23 |
July | 0.959235E+09 | 0.663955E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184279E+10 | 8859326.12 |
August | 0.107774E+10 | 0.748291E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197465E+10 | 17484442.06 |
September | 0.956342E+09 | 0.682889E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142936E+10 | 20812040.17 |
October | 0.994195E+09 | 0.716290E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112379E+10 | 67969466.18 |
November | 0.984487E+09 | 0.724621E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612738E+09 | 0.412786E+09 |
December | 0.959235E+09 | 0.728697E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127221E+09 | 0.137349E+10 |
Annual Sum or Average | 0.119305E+11 | 0.852974E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114686E+11 | 0.540631E+10 |
Minimum of Months | 0.901968E+09 | 0.654318E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101744E+09 | 5691646.23 |
Maximum of Months | 0.107774E+10 | 0.760886E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197465E+10 | 0.153366E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.479580E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457502.00 | 34522175.38 |
February | 0.570983E+09 | 0.420137E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2253944.79 | 47255237.51 |
March | 0.682256E+09 | 0.488998E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898599.52 | 42623428.60 |
April | 0.605404E+09 | 0.425597E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6107224.57 | 19717242.58 |
May | 0.655811E+09 | 0.454186E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15082214.26 | 7845166.61 |
June | 0.653980E+09 | 0.454579E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17933614.20 | 1924257.01 |
July | 0.607235E+09 | 0.420250E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16842944.73 | 2212375.71 |
August | 0.682256E+09 | 0.476178E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18831718.31 | 1349338.04 |
September | 0.605404E+09 | 0.435581E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17808810.42 | 2425221.18 |
October | 0.629366E+09 | 0.464282E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11741628.36 | 5617050.04 |
November | 0.623221E+09 | 0.467251E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5510050.75 | 29615640.36 |
December | 0.607235E+09 | 0.469078E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1937187.21 | 35562772.97 |
Annual Sum or Average | 0.755252E+10 | 0.545570E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118405E+09 | 0.230670E+09 |
Minimum of Months | 0.570983E+09 | 0.420137E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457502.00 | 1349338.04 |
Maximum of Months | 0.682256E+09 | 0.488998E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18831718.31 | 47255237.51 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.793023E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3740868.38 | 73382805.91 |
February | 0.901968E+09 | 0.681835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6471333.28 | 98855076.34 |
March | 0.107774E+10 | 0.776649E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7090049.06 | 88846267.26 |
April | 0.956342E+09 | 0.672717E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15879891.69 | 39163143.26 |
May | 0.103597E+10 | 0.708952E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35996394.05 | 15819554.34 |
June | 0.103308E+10 | 0.704881E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42687596.96 | 4679114.43 |
July | 0.959235E+09 | 0.655155E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40441407.79 | 4534757.16 |
August | 0.107774E+10 | 0.745007E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46938794.73 | 2591985.04 |
September | 0.956342E+09 | 0.687532E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44484592.83 | 4761869.30 |
October | 0.994195E+09 | 0.740619E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29256339.00 | 10475212.66 |
November | 0.984487E+09 | 0.764013E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13654787.87 | 61421145.67 |
December | 0.959235E+09 | 0.776232E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5274482.05 | 73422644.21 |
Annual Sum or Average | 0.119305E+11 | 0.870661E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291917E+09 | 0.477954E+09 |
Minimum of Months | 0.901968E+09 | 0.655155E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3740868.38 | 2591985.04 |
Maximum of Months | 0.107774E+10 | 0.793023E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46938794.73 | 98855076.34 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.487511E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1951315.77 | 51188040.30 |
February | 0.421807E+09 | 0.425800E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062860.30 | 68343134.91 |
March | 0.502994E+09 | 0.483891E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4602668.50 | 60971692.54 |
April | 0.447140E+09 | 0.426437E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9575129.38 | 27018475.56 |
May | 0.484071E+09 | 0.453041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24050337.95 | 10693744.76 |
June | 0.482240E+09 | 0.452173E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28490009.74 | 3159007.96 |
July | 0.448971E+09 | 0.418835E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26549663.23 | 3119516.80 |
August | 0.502994E+09 | 0.472121E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30854573.05 | 1737476.60 |
September | 0.447140E+09 | 0.434720E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28852847.13 | 3241537.76 |
October | 0.465148E+09 | 0.459707E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18966989.06 | 7121964.43 |
November | 0.460569E+09 | 0.476065E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9066960.73 | 43015795.78 |
December | 0.448971E+09 | 0.482134E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3407931.61 | 49487357.77 |
Annual Sum or Average | 0.557719E+10 | 0.547243E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190431E+09 | 0.329098E+09 |
Minimum of Months | 0.421807E+09 | 0.418835E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1951315.77 | 1737476.60 |
Maximum of Months | 0.502994E+09 | 0.487511E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30854573.05 | 68343134.91 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.737989E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1952384.92 | 86030629.89 |
February | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4402926.58 | 0.112831E+09 |
March | 0.107774E+10 | 0.762321E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5860279.77 | 96634854.31 |
April | 0.956342E+09 | 0.674897E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13642010.93 | 40907716.54 |
May | 0.103597E+10 | 0.719906E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36234630.54 | 15733000.38 |
June | 0.103308E+10 | 0.723111E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43495032.09 | 4516430.45 |
July | 0.959235E+09 | 0.665687E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41061326.68 | 4389486.82 |
August | 0.107774E+10 | 0.749777E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46228165.62 | 2635689.19 |
September | 0.956342E+09 | 0.683712E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41567239.91 | 5135529.38 |
October | 0.994195E+09 | 0.717248E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24473523.02 | 12506337.90 |
November | 0.984487E+09 | 0.725903E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10470660.21 | 72691406.18 |
December | 0.959235E+09 | 0.729878E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2896020.84 | 84555290.50 |
Annual Sum or Average | 0.119305E+11 | 0.854599E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272284E+09 | 0.538567E+09 |
Minimum of Months | 0.901968E+09 | 0.655566E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1952384.92 | 2635689.19 |
Maximum of Months | 0.107774E+10 | 0.762321E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46228165.62 | 0.112831E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.481145E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511239.94 | 49910120.30 |
February | 0.570983E+09 | 0.421539E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3734683.57 | 68746614.68 |
March | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4733111.25 | 63190801.06 |
April | 0.605404E+09 | 0.426526E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9680431.27 | 29802867.86 |
May | 0.655811E+09 | 0.455062E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23692272.67 | 12020775.33 |
June | 0.653980E+09 | 0.455793E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28045519.65 | 3250059.75 |
July | 0.607235E+09 | 0.421172E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26587652.34 | 3336288.82 |
August | 0.682256E+09 | 0.477233E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30128125.26 | 1858012.62 |
September | 0.605404E+09 | 0.436805E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28317396.06 | 3412781.91 |
October | 0.629366E+09 | 0.465581E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18527953.83 | 7807138.63 |
November | 0.623221E+09 | 0.468962E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9007914.83 | 42166096.82 |
December | 0.607235E+09 | 0.470620E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3287062.77 | 50463803.27 |
Annual Sum or Average | 0.755252E+10 | 0.547057E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188253E+09 | 0.335965E+09 |
Minimum of Months | 0.570983E+09 | 0.421172E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511239.94 | 1858012.62 |
Maximum of Months | 0.682256E+09 | 0.490128E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30128125.26 | 68746614.68 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2050109.61 | 0.115080E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3792452.01 | 0.152880E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5028129.79 | 0.134087E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13674776.17 | 56876028.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38123775.29 | 19904034.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50273897.20 | 5082616.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47105076.22 | 5152016.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54545290.61 | 3383718.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50469095.56 | 6534508.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28946151.21 | 14735753.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11306867.75 | 94173129.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3676002.67 | 0.113862E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308992E+09 | 0.721751E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2050109.61 | 3383718.74 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54545290.61 | 0.152880E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3852659.59 | 0.134695E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5915930.92 | 0.179293E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7463850.39 | 0.159952E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18720060.58 | 67629527.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50088449.41 | 23407282.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65510808.96 | 6383338.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61300278.28 | 6519178.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72005957.04 | 4021156.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66393687.36 | 7713114.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39349168.84 | 17007822.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16793853.18 | 0.110612E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6083240.22 | 0.131869E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413478E+09 | 0.849102E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3852659.59 | 4021156.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72005957.04 | 0.179293E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1947074.34 | 0.125309E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932301.24 | 0.164341E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2735673.29 | 0.149589E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9967412.70 | 64452233.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43990695.96 | 20009424.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62552032.47 | 6935468.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54306464.93 | 6524301.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69704390.21 | 4115237.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60630327.39 | 5601490.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36259652.21 | 11329948.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15560104.34 | 0.102138E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2948054.94 | 0.123724E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362534E+09 | 0.784070E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1932301.24 | 4115237.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69704390.21 | 0.164341E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.82 | 15-JAN-13:50 | 230.78 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 20-FEB-15:00 | 390.13 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 | 05-MAR-14:00 | 396.28 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.12 | 15-APR-17:02 | 131.36 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 | 29-MAY-16:05 | 91.40 | 07-MAY-19:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.43 | 17-JUN-17:23 | 95.36 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.87 | 30-JUL-15:40 | 78.92 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.69 | 13-AUG-12:40 | 111.77 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.79 | 17-SEP-14:00 | 47.67 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.89 | 29-OCT-12:10 | 82.03 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 | 22-NOV-22:03 | 392.58 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.06 | 10-DEC-15:00 | 359.46 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 47.67 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 | 396.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 15-JAN-14:30 | 168.92 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 710.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 | 19-FEB-15:40 | 259.11 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 | 05-MAR-14:20 | 266.93 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 | 15-APR-17:02 | 87.92 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 25-MAY-14:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.68 | 29-MAY-16:10 | 66.64 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.36 | 17-JUN-17:23 | 61.89 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.55 | 30-JUL-15:40 | 56.11 | 02-JUL-16:00 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.40 | 20-AUG-12:08 | 75.05 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.55 | 17-SEP-14:00 | 32.81 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.15 | 29-OCT-14:10 | 55.19 | 01-OCT-07:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 08-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 22-NOV-22:03 | 314.25 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.59 | 10-DEC-15:00 | 239.67 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 32.81 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.68 | 314.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 29-JAN-12:03 | 244.09 | 08-JAN-10:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.27 | 02-FEB-14:00 | 400.78 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 05-MAR-13:43 | 410.99 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.24 | 15-APR-17:02 | 133.58 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.12 | 29-MAY-16:05 | 91.68 | 07-MAY-19:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 | 17-JUN-17:23 | 95.70 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 | 30-JUL-15:40 | 78.38 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.46 | 20-AUG-12:08 | 112.86 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.86 | 17-SEP-15:56 | 51.18 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.97 | 29-OCT-14:06 | 85.42 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 24-NOV-08:09 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 22-NOV-22:03 | 449.11 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.34 | 10-DEC-14:58 | 372.51 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 51.18 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 229.12 | 449.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 15-JAN-12:30 | 155.47 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 710.03 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 19-FEB-13:40 | 260.69 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 05-MAR-14:20 | 271.62 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 16-APR-13:00 | 93.12 | 30-APR-18:30 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.73 | 29-MAY-15:24 | 71.33 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 | 11-JUN-12:00 | 64.56 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.50 | 30-JUL-15:40 | 50.87 | 02-JUL-16:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 13-AUG-13:00 | 78.01 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.10 | 17-SEP-13:58 | 36.25 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.65 | 29-OCT-12:10 | 56.74 | 01-OCT-07:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 | 19-NOV-10:40 | 260.52 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 | 10-DEC-14:55 | 239.62 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 36.25 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 142.73 | 271.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 | 15-JAN-14:30 | 138.88 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 | 20-FEB-15:10 | 244.99 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.08 | 05-MAR-13:43 | 235.98 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.42 | 15-APR-17:02 | 75.44 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.54 | 29-MAY-16:00 | 50.08 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.11 | 17-JUN-17:40 | 46.59 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.13 | 30-JUL-15:50 | 35.29 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.31 | 13-AUG-13:00 | 60.78 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.22 | 17-SEP-13:50 | 27.15 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.39 | 29-OCT-12:00 | 45.99 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 23-NOV-12:00 | 240.22 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.39 | 10-DEC-15:00 | 226.82 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 27.15 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 125.54 | 244.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 15-JAN-14:30 | 97.22 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 19-FEB-16:10 | 164.33 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 490.21 | 06-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.84 | 05-MAR-13:50 | 162.40 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 | 15-APR-17:02 | 52.58 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 25-MAY-15:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 29-MAY-16:00 | 35.40 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 17-JUN-17:37 | 31.74 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.44 | 30-JUL-15:40 | 28.29 | 02-JUL-15:25 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.88 | 20-AUG-12:10 | 42.58 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.60 | 17-SEP-13:50 | 19.87 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 | 29-OCT-14:00 | 32.19 | 16-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 10-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 23-NOV-12:00 | 184.27 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 15-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.57 | 10-DEC-15:00 | 153.04 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 19.87 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 184.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.16 | 23-JAN-17:10 | 14597.24 | 25-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4161.46 | 02-FEB-13:00 | 13389.20 | 03-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6047.17 | 13-MAR-16:03 | 17332.97 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8601.24 | 17-APR-16:03 | 7503.70 | 19-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9847.09 | 22-MAY-16:02 | 2919.10 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8127.31 | 09-JUN-16:03 | 875.43 | 13-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12355.29 | 27-JUL-16:02 | 1487.96 | 14-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9997.74 | 08-AUG-11:02 | 2129.27 | 28-AUG-12:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8776.07 | 08-SEP-16:03 | 2059.85 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7460.42 | 03-OCT-11:02 | 2684.45 | 31-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4641.12 | 03-NOV-16:05 | 14349.86 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3389.08 | 08-DEC-12:05 | 16717.34 | 15-DEC-07:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2884.16 | 875.43 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12355.29 | 17332.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 15-JAN-12:30 | 96.78 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 600.10 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 19-FEB-13:30 | 165.16 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 05-MAR-13:43 | 165.78 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.89 | 16-APR-13:00 | 54.34 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.20 | 29-MAY-16:15 | 35.71 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.52 | 11-JUN-12:00 | 33.54 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.12 | 30-JUL-15:40 | 25.66 | 02-JUL-15:25 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 13-AUG-13:00 | 44.86 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.72 | 10-SEP-13:00 | 21.80 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 | 29-OCT-12:00 | 34.43 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 23-NOV-12:00 | 162.15 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 10-DEC-13:40 | 153.97 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 21.80 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.20 | 165.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 | 15-JAN-13:50 | 208.92 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 20-FEB-15:10 | 362.32 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 1121.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 26-MAR-12:53 | 358.78 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.87 | 15-APR-17:02 | 116.83 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.06 | 29-MAY-16:00 | 78.56 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.24 | 17-JUN-17:23 | 77.13 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.01 | 30-JUL-15:40 | 57.59 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.70 | 13-AUG-13:00 | 93.42 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.15 | 17-SEP-14:00 | 40.32 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.76 | 29-OCT-14:00 | 74.59 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 10-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.19 | 19-NOV-10:50 | 356.46 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.40 | 10-DEC-14:30 | 334.36 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 | 40.32 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 189.06 | 362.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 04-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.16 | 15-JAN-14:30 | 152.99 | 08-JAN-10:00 |
February | 805.43 | 01-FEB-08:09 | 710.08 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 | 19-FEB-16:10 | 240.17 | 04-FEB-05:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.31 | 05-MAR-14:00 | 240.70 | 16-MAR-02:00 |
April | 805.43 | 03-APR-07:10 | 600.14 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 | 15-APR-17:02 | 78.05 | 18-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 25-MAY-14:50 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.74 | 29-MAY-16:00 | 52.41 | 07-MAY-19:00 |
June | 805.43 | 01-JUN-07:10 | 750.07 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.74 | 17-JUN-17:23 | 50.28 | 18-JUN-20:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 | 30-JUL-15:40 | 43.86 | 02-JUL-15:25 |
August | 805.43 | 01-AUG-07:10 | 600.14 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.47 | 20-AUG-12:10 | 62.94 | 14-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 860.01 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.30 | 17-SEP-16:40 | 27.72 | 19-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.19 | 29-OCT-14:00 | 49.46 | 16-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 750.07 | 08-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 22-NOV-22:03 | 281.62 | 11-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 06-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.22 | 10-DEC-14:30 | 222.22 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.16 | 27.72 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 140.74 | 281.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 04-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 29-JAN-12:30 | 222.42 | 08-JAN-10:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 02-FEB-14:00 | 371.00 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 05-MAR-14:00 | 370.32 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.86 | 15-APR-17:02 | 118.67 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.83 | 29-MAY-16:00 | 78.45 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 1184.79 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.57 | 17-JUN-17:23 | 77.33 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.01 | 30-JUL-15:40 | 57.11 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.68 | 13-AUG-12:40 | 94.53 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.43 | 17-SEP-16:37 | 43.61 | 03-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 18-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.36 | 29-OCT-13:57 | 80.70 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 24-NOV-08:09 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 22-NOV-22:03 | 403.85 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 15-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.44 | 10-DEC-14:26 | 343.61 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 43.61 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 189.83 | 403.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 750.02 | 04-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 | 15-JAN-12:30 | 140.57 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 710.03 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | 19-FEB-13:30 | 241.63 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 | 26-MAR-12:53 | 245.09 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 750.02 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.75 | 16-APR-13:00 | 81.66 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 29-MAY-15:54 | 56.72 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 859.95 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.99 | 11-JUN-12:00 | 53.01 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.56 | 30-JUL-15:40 | 39.16 | 02-JUL-15:25 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 13-AUG-13:00 | 65.91 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.62 | 17-SEP-12:53 | 30.62 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.84 | 29-OCT-12:00 | 52.22 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 750.02 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 | 19-NOV-10:50 | 236.71 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 15-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 | 10-DEC-13:50 | 222.32 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | 30.62 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 245.09 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 29-JAN-12:00 | 306.85 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 02-FEB-14:00 | 546.91 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.15 | 05-MAR-13:53 | 530.81 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.24 | 15-APR-17:02 | 167.93 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.59 | 29-MAY-16:00 | 100.01 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.60 | 25-JUN-14:00 | 86.94 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.46 | 30-JUL-15:50 | 70.47 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.36 | 13-AUG-12:55 | 113.42 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.18 | 17-SEP-14:00 | 44.22 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.36 | 29-OCT-12:00 | 104.08 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 | 22-NOV-22:03 | 504.68 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.63 | 10-DEC-14:40 | 502.14 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 | 44.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.59 | 546.91 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.87 | 29-JAN-11:53 | 367.91 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 19-FEB-13:52 | 671.34 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.45 | 05-MAR-14:00 | 663.02 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.52 | 15-APR-17:02 | 211.95 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.55 | 29-MAY-16:00 | 119.99 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.83 | 25-JUN-14:00 | 111.72 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.05 | 30-JUL-15:50 | 90.32 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.17 | 13-AUG-12:55 | 140.64 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.99 | 17-SEP-14:00 | 54.82 | 04-SEP-23:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.05 | 29-OCT-12:00 | 131.61 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 04-NOV-17:03 | 623.81 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.14 | 10-DEC-14:52 | 614.35 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 54.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.55 | 671.34 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.80 | 29-JAN-12:10 | 343.69 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 02-FEB-14:00 | 569.74 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 05-MAR-11:55 | 583.15 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.80 | 15-APR-17:02 | 183.11 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.71 | 29-MAY-15:51 | 145.07 | 07-MAY-19:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.22 | 16-JUN-21:03 | 132.83 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 29-JUL-18:00 | 138.35 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.74 | 13-AUG-12:40 | 154.86 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.62 | 21-SEP-21:03 | 97.72 | 03-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.19 | 29-OCT-08:55 | 120.29 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.24 | 22-NOV-22:03 | 586.81 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 | 10-DEC-09:53 | 519.80 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 97.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.71 | 586.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36978.62 | 02-JAN-07:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39455.93 | 21-FEB-06:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36467.94 | 06-MAR-07:03 | 3811.58 | 6444.06 | 30584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40949.74 | 12-APR-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44825.78 | 08-MAY-05:03 | 4446.85 | 1482.14 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43538.98 | 06-JUN-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41945.36 | 06-JUL-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40837.16 | 30-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41150.64 | 12-SEP-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43408.44 | 26-OCT-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41252.85 | 20-NOV-05:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39271.69 | 09-DEC-05:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36467.94 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44825.78 | 5082.11 | 8592.08 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7984.49 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
February | 8020.37 | 22-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 |
March | 9214.59 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 0.00 |
April | 10111.30 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
May | 11163.55 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 0.00 |
June | 10502.10 | 09-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 0.00 |
July | 11636.69 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.06 | 0.00 |
August | 11095.85 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 0.00 |
September | 10830.63 | 18-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.03 | 0.00 |
October | 10512.49 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
November | 8573.62 | 10-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 |
December | 7447.84 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7447.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 | |
Maximum of Months | 11636.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3842.44 | 02-JAN-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
February | 3427.43 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 0.00 |
March | 3946.17 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 | 0.00 |
April | 4228.26 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 0.00 |
May | 4548.59 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 | 0.00 |
June | 4394.58 | 26-JUN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 | 0.00 |
July | 5004.28 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 | 0.00 |
August | 4748.59 | 21-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.36 | 0.00 |
September | 4820.91 | 11-SEP-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.63 | 0.00 |
October | 4593.17 | 02-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 | 0.00 |
November | 4218.77 | 06-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 0.00 |
December | 3525.59 | 11-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3427.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5004.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 | 9.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4598.42 | 02-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
February | 4201.52 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
March | 4484.86 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 0.00 |
April | 4705.11 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 0.00 |
May | 5196.86 | 22-MAY-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 | 0.00 |
June | 4919.53 | 26-JUN-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 | 0.00 |
July | 5546.72 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 | 0.00 |
August | 5206.63 | 21-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 | 0.00 |
September | 5184.12 | 11-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 | 0.00 |
October | 5006.51 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.88 | 0.00 |
November | 4760.83 | 06-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
December | 4234.74 | 11-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4201.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5546.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 | 8.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25120.19 | 14-JAN-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23868.60 | 11-FEB-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17411.19 | 27-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22864.49 | 13-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35471.14 | 08-MAY-05:03 | 4446.85 | 1482.14 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32289.18 | 20-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32897.51 | 06-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32070.40 | 08-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32997.66 | 12-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33158.61 | 23-OCT-05:04 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32629.32 | 20-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30685.60 | 09-DEC-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17411.19 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35471.14 | 6035.01 | 6443.98 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19125.75 | 02-JAN-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17897.50 | 21-FEB-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19651.64 | 27-MAR-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33899.93 | 13-APR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35315.05 | 23-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36073.78 | 19-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35713.71 | 24-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35033.81 | 07-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34996.63 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35708.57 | 10-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33885.69 | 20-NOV-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21140.13 | 09-DEC-06:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17897.50 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36073.78 | 6198.29 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5105.35 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 0.00 |
February | 5252.22 | 17-FEB-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 0.00 |
March | 5772.26 | 27-MAR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 |
April | 7755.75 | 16-APR-16:42 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 0.00 |
May | 12203.17 | 29-MAY-13:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 | 0.00 |
June | 12268.30 | 11-JUN-15:52 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 99.69 | 0.00 |
July | 12267.81 | 30-JUL-11:32 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 83.41 | 0.00 |
August | 12300.31 | 06-AUG-15:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 77.24 | 0.00 |
September | 10588.37 | 18-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 0.00 |
October | 9997.60 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 0.00 |
November | 6056.47 | 30-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 |
December | 5047.96 | 08-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5047.96 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 0.00 | |
Maximum of Months | 12300.31 | 1306.65 | 647.98 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9371.88 | 01-JAN-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
February | 5052.96 | 28-FEB-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
March | 6673.82 | 27-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
April | 12080.68 | 09-APR-09:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 |
May | 11342.71 | 14-MAY-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 | 0.00 |
June | 12794.11 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 | 0.00 |
July | 12642.37 | 04-JUL-11:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 0.00 |
August | 12071.15 | 06-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
September | 9553.36 | 04-SEP-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 0.00 |
October | 9220.66 | 09-OCT-11:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 | 0.00 |
November | 5868.51 | 07-NOV-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 0.00 |
December | 4907.16 | 08-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4907.16 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12794.11 | 827.22 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 17.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13954.43 | 01-JAN-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
February | 14420.67 | 20-FEB-14:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 |
March | 13263.63 | 26-MAR-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 | 0.00 |
April | 12655.85 | 16-APR-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 61.49 | 0.00 |
May | 12571.91 | 29-MAY-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 154.36 | 0.00 |
June | 12418.83 | 11-JUN-15:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 103.30 | 0.00 |
July | 12790.55 | 30-JUL-11:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 | 0.00 |
August | 12939.51 | 20-AUG-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 113.60 | 0.00 |
September | 12914.03 | 17-SEP-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 113.72 | 0.00 |
October | 13517.50 | 15-OCT-15:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 0.00 |
November | 13889.96 | 19-NOV-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.19 |
December | 14418.99 | 10-DEC-12:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12418.83 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14420.67 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 154.36 | 62.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5675.70 | 03-JAN-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 0.00 |
February | 14098.32 | 20-FEB-17:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
March | 11854.54 | 12-MAR-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
April | 14185.66 | 02-APR-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 |
May | 13888.89 | 29-MAY-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 108.04 | 0.00 |
June | 13800.91 | 11-JUN-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 | 0.00 |
July | 13825.04 | 09-JUL-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 | 0.00 |
August | 13780.67 | 06-AUG-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 0.00 |
September | 13883.03 | 17-SEP-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 77.39 | 0.00 |
October | 14040.87 | 15-OCT-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 | 0.00 |
November | 10581.99 | 05-NOV-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
December | 13498.68 | 10-DEC-14:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5675.70 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14185.66 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 108.04 | 43.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4623.00 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
February | 4624.50 | 17-FEB-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 0.00 |
March | 4852.78 | 06-MAR-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
April | 5848.81 | 17-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 0.00 |
May | 8234.24 | 24-MAY-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 |
June | 8716.58 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 8381.66 | 31-JUL-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
August | 8600.63 | 15-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 0.00 |
September | 9152.03 | 10-SEP-15:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 0.00 |
October | 7883.88 | 26-OCT-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
November | 5450.19 | 03-NOV-13:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 | 0.00 |
December | 4836.08 | 01-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4623.00 | 0.00 | 223.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9152.03 | 1306.65 | 647.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 1.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10624.30 | 01-JAN-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 |
February | 4870.08 | 28-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
March | 5955.14 | 27-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 0.00 |
April | 10856.92 | 09-APR-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 |
May | 8381.30 | 14-MAY-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 0.00 |
June | 11081.87 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 0.00 |
July | 11539.54 | 23-JUL-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 | 0.00 |
August | 10353.55 | 06-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 |
September | 11055.87 | 10-SEP-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 0.00 |
October | 8247.52 | 22-OCT-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.56 | 0.00 |
November | 5588.46 | 07-NOV-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
December | 4720.37 | 08-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4720.37 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11539.54 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 | 4.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11784.95 | 01-JAN-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
February | 11405.49 | 19-FEB-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 |
March | 9428.03 | 13-MAR-16:20 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5201.12 | 0.00 |
April | 9857.88 | 17-APR-16:10 | 1607.03 | 1439.95 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7271.92 | 0.00 |
May | 10579.44 | 22-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8262.20 | 0.00 |
June | 9794.95 | 09-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6950.28 | 0.00 |
July | 10794.30 | 27-JUL-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9360.33 | 0.00 |
August | 10732.50 | 20-AUG-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 | 0.00 |
September | 11267.42 | 10-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 0.00 |
October | 11963.01 | 29-OCT-12:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 | 0.00 |
November | 11272.19 | 19-NOV-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
December | 11952.68 | 10-DEC-12:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9428.03 | 267.84 | 143.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11963.01 | 1607.03 | 1439.95 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9360.33 | 12.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5026.41 | 02-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 |
February | 11519.71 | 19-FEB-17:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 |
March | 9169.34 | 12-MAR-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 |
April | 11562.52 | 02-APR-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 |
May | 11267.90 | 29-MAY-14:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 | 0.00 |
June | 11445.62 | 11-JUN-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 0.00 |
July | 11496.58 | 09-JUL-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 | 0.00 |
August | 11419.12 | 20-AUG-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
September | 12153.96 | 10-SEP-15:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 0.00 |
October | 11528.75 | 15-OCT-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
November | 6538.23 | 07-NOV-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 0.00 |
December | 10361.21 | 10-DEC-14:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5026.41 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12153.96 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 | 21.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4861.48 | 02-JAN-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 0.00 |
February | 4876.54 | 17-FEB-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
March | 5229.20 | 28-MAR-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
April | 6374.71 | 17-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 0.00 |
May | 10697.48 | 29-MAY-15:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 165.70 | 0.00 |
June | 8992.29 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
July | 9286.42 | 30-JUL-11:32 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 71.87 | 0.00 |
August | 9508.69 | 06-AUG-15:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 73.60 | 0.00 |
September | 10408.82 | 10-SEP-15:31 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 84.40 | 0.00 |
October | 8522.70 | 30-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
November | 6974.88 | 30-NOV-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
December | 4892.92 | 09-DEC-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4861.48 | 0.00 | 178.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10697.48 | 1306.65 | 647.98 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 165.70 | 1.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11423.02 | 01-JAN-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 |
February | 5465.56 | 28-FEB-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
March | 7350.71 | 26-MAR-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 |
April | 12448.99 | 16-APR-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
May | 11046.20 | 07-MAY-08:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
June | 12221.35 | 11-JUN-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 0.00 |
July | 12665.23 | 23-JUL-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 |
August | 11285.07 | 06-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 0.00 |
September | 12114.78 | 10-SEP-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
October | 11971.42 | 09-OCT-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 |
November | 6112.45 | 07-NOV-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
December | 4881.07 | 08-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4881.07 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12665.23 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 20.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11682.50 | 15-JAN-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.90 |
February | 11943.28 | 19-FEB-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
March | 11390.23 | 26-MAR-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
April | 11126.58 | 16-APR-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 53.01 | 0.00 |
May | 10843.12 | 29-MAY-15:51 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 166.60 | 0.00 |
June | 9079.04 | 28-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 0.00 |
July | 10845.19 | 30-JUL-11:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 | 0.00 |
August | 11071.50 | 20-AUG-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 99.60 | 0.00 |
September | 11591.58 | 10-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 62.75 | 0.00 |
October | 12486.09 | 29-OCT-12:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 | 0.00 |
November | 11719.82 | 19-NOV-11:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.96 |
December | 11727.69 | 03-DEC-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9079.04 | 0.00 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12486.09 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 166.60 | 89.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5507.02 | 03-JAN-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
February | 12536.13 | 19-FEB-17:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 |
March | 11490.42 | 12-MAR-17:53 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 |
April | 13222.30 | 02-APR-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
May | 13318.19 | 29-MAY-15:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 0.00 |
June | 12389.87 | 11-JUN-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 0.00 |
July | 12601.50 | 09-JUL-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 0.00 |
August | 12462.57 | 20-AUG-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 0.00 |
September | 13382.47 | 10-SEP-15:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 |
October | 12675.10 | 15-OCT-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 | 0.00 |
November | 9440.34 | 05-NOV-15:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 | 0.00 |
December | 8231.46 | 03-DEC-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5507.02 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13382.47 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 53.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.133932E+12 | 137503.85 | 02-JAN-13:00 | 0.00 | 0.00 |
February | 0.125137E+12 | 123522.10 | 17-FEB-15:09 | 0.00 | 0.00 |
March | 0.146325E+12 | 136711.86 | 27-MAR-15:20 | 0.00 | 0.00 |
April | 0.144801E+12 | 143790.73 | 14-APR-15:09 | 0.00 | 0.00 |
May | 0.168231E+12 | 150464.66 | 22-MAY-14:09 | 0.00 | 0.00 |
June | 0.175089E+12 | 148644.17 | 29-JUN-15:20 | 0.00 | 0.00 |
July | 0.178304E+12 | 161987.49 | 28-JUL-15:30 | 0.00 | 0.00 |
August | 0.185719E+12 | 157794.21 | 21-AUG-15:00 | 0.00 | 0.00 |
September | 0.171093E+12 | 155130.85 | 18-SEP-15:30 | 0.00 | 0.00 |
October | 0.167164E+12 | 152498.08 | 02-OCT-14:20 | 0.00 | 0.00 |
November | 0.149384E+12 | 140098.65 | 03-NOV-14:09 | 0.00 | 0.00 |
December | 0.134942E+12 | 134345.39 | 08-DEC-16:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.188012E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.125137E+12 | 123522.10 | 0.00 | 0.00 | |
Maximum of Months | 0.185719E+12 | 161987.49 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.254839E+11 | 0.512820E+10 | 0.605851E+11 | 0.225887E+10 | 0.561069E+10 | 12379742.02 | 0.523716E+09 | 0.307658E+11 | 0.00 | 0.00 | 0.00 | 0.356333E+10 | 0.00 |
February | 0.228719E+11 | 0.428778E+10 | 0.548702E+11 | 0.204964E+10 | 0.565385E+10 | 11196021.66 | 0.360584E+09 | 0.318230E+11 | 0.00 | 0.00 | 0.00 | 0.320902E+10 | 0.00 |
March | 0.269744E+11 | 0.434999E+10 | 0.627783E+11 | 0.235653E+10 | 0.692272E+10 | 12675672.10 | 0.329588E+09 | 0.389246E+11 | 0.00 | 0.00 | 0.00 | 0.367587E+10 | 0.00 |
April | 0.239187E+11 | 0.383914E+10 | 0.586172E+11 | 0.219342E+10 | 0.744748E+10 | 11960507.72 | 11069357.81 | 0.455779E+11 | 0.00 | 0.00 | 0.00 | 0.318438E+10 | 0.00 |
May | 0.257245E+11 | 0.362394E+10 | 0.616817E+11 | 0.230737E+10 | 0.940246E+10 | 12527707.06 | 0.00 | 0.622247E+11 | 0.00 | 0.00 | 0.00 | 0.325386E+10 | 0.00 |
June | 0.256470E+11 | 0.337880E+10 | 0.604966E+11 | 0.226962E+10 | 0.988946E+10 | 12231776.97 | 0.00 | 0.702854E+11 | 0.00 | 0.00 | 0.00 | 0.310996E+10 | 0.00 |
July | 0.238724E+11 | 0.355877E+10 | 0.597911E+11 | 0.223030E+10 | 0.104312E+11 | 12256437.81 | 0.00 | 0.755044E+11 | 0.00 | 0.00 | 0.00 | 0.290383E+10 | 0.00 |
August | 0.267699E+11 | 0.384121E+10 | 0.627783E+11 | 0.235637E+10 | 0.107336E+11 | 12675672.10 | 0.00 | 0.760058E+11 | 0.00 | 0.00 | 0.00 | 0.322153E+10 | 0.00 |
September | 0.240446E+11 | 0.402405E+10 | 0.585950E+11 | 0.219223E+10 | 0.985951E+10 | 11960507.72 | 0.00 | 0.693508E+11 | 0.00 | 0.00 | 0.00 | 0.301534E+10 | 0.00 |
October | 0.251372E+11 | 0.455503E+10 | 0.605962E+11 | 0.225943E+10 | 0.946265E+10 | 12379742.02 | 0.00 | 0.618836E+11 | 0.00 | 0.00 | 0.00 | 0.325755E+10 | 0.00 |
November | 0.250917E+11 | 0.482873E+10 | 0.591197E+11 | 0.220144E+10 | 0.748634E+10 | 12059151.09 | 68955496.60 | 0.472310E+11 | 0.00 | 0.00 | 0.00 | 0.334448E+10 | 0.00 |
December | 0.247627E+11 | 0.521691E+10 | 0.597800E+11 | 0.223017E+10 | 0.583351E+10 | 12256437.81 | 0.502533E+09 | 0.331759E+11 | 0.00 | 0.00 | 0.00 | 0.342816E+10 | 0.00 |
Annual Sum or Average | 0.300299E+12 | 0.506325E+11 | 0.719689E+12 | 0.269054E+11 | 0.987335E+11 | 0.146559E+09 | 0.179645E+10 | 0.642753E+12 | 0.00 | 0.00 | 0.00 | 0.391673E+11 | 0.00 |
Minimum of Months | 0.228719E+11 | 0.337880E+10 | 0.548702E+11 | 0.204964E+10 | 0.561069E+10 | 11196021.66 | 0.00 | 0.307658E+11 | 0.00 | 0.00 | 0.00 | 0.290383E+10 | 0.00 |
Maximum of Months | 0.269744E+11 | 0.521691E+10 | 0.627783E+11 | 0.235653E+10 | 0.107336E+11 | 12675672.10 | 0.523716E+09 | 0.760058E+11 | 0.00 | 0.00 | 0.00 | 0.367587E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30940.97 | 04-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 25-JAN-08:09 | 11397.25 | 02-JAN-15:09 | 6.85 | 01-JAN-06:10 | 25971.05 | 25-JAN-07:10 |
February | 28370.68 | 08-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-08:09 | 10739.70 | 21-FEB-16:19 | 6.85 | 03-FEB-17:10 | 38066.27 | 04-FEB-07:10 |
March | 28901.49 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 15-MAR-11:09 | 12122.64 | 27-MAR-15:30 | 6.85 | 15-MAR-11:09 | 25782.17 | 16-MAR-06:10 |
April | 29070.25 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-07:10 | 12500.75 | 17-APR-15:20 | 6.85 | 01-APR-05:10 | 4007.44 | 19-APR-06:19 |
May | 27476.09 | 25-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 22-MAY-12:09 | 13314.96 | 22-MAY-13:30 | 6.85 | 29-MAY-16:40 | 0.00 | 01-MAY-00:10 |
June | 31270.76 | 15-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-12:09 | 12691.55 | 29-JUN-15:30 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 27476.09 | 05-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 06-JUL-12:09 | 15130.33 | 31-JUL-14:30 | 6.85 | 27-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 29543.89 | 28-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 23-AUG-12:09 | 13931.46 | 21-AUG-15:20 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 32642.50 | 27-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 06-SEP-12:09 | 14249.03 | 18-SEP-14:09 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 31160.83 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-12:09 | 13707.04 | 02-OCT-14:50 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 30711.07 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-07:19 | 12296.27 | 06-NOV-15:30 | 6.85 | 01-NOV-05:10 | 13175.68 | 27-NOV-07:10 |
December | 32642.50 | 15-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 20-DEC-12:09 | 10399.72 | 08-DEC-15:39 | 6.85 | 01-DEC-06:10 | 25084.79 | 15-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 27476.09 | 5686.19 | 41699.26 | 1410.29 | 10399.72 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 15130.33 | 6.85 | 38066.27 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 56690.74 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4619.72 | 18-JAN-12:50 | 0.00 |
February | 44316.49 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4617.53 | 01-FEB-12:30 | 0.00 |
March | 52540.40 | 27-MAR-14:00 | 0.00 | 0.00 | 0.00 | 4600.97 | 01-MAR-12:50 | 0.00 |
April | 60694.26 | 14-APR-14:00 | 0.00 | 0.00 | 0.00 | 4565.99 | 03-APR-11:30 | 0.00 |
May | 67116.25 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 4229.19 | 01-MAY-11:50 | 0.00 |
June | 64697.33 | 08-JUN-15:00 | 0.00 | 0.00 | 0.00 | 4122.68 | 01-JUN-11:20 | 0.00 |
July | 75613.40 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 3880.25 | 03-JUL-11:30 | 0.00 |
August | 72217.63 | 21-AUG-15:00 | 0.00 | 0.00 | 0.00 | 3893.46 | 31-AUG-11:20 | 0.00 |
September | 69202.47 | 18-SEP-15:30 | 0.00 | 0.00 | 0.00 | 4220.34 | 29-SEP-11:39 | 0.00 |
October | 67887.63 | 02-OCT-14:09 | 0.00 | 0.00 | 0.00 | 4288.66 | 31-OCT-11:20 | 0.00 |
November | 57815.02 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 4594.69 | 30-NOV-12:00 | 0.00 |
December | 51185.53 | 08-DEC-15:00 | 0.00 | 0.00 | 0.00 | 4615.25 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 44316.49 | 0.00 | 0.00 | 0.00 | 3880.25 | 0.00 | ||
Maximum of Months | 75613.40 | 0.00 | 0.00 | 0.00 | 4619.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 137503.85 | 02-JAN-13:00 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 10372.57 | 6.85 | 0.00 | 56690.74 | 0.00 |
February | 123522.10 | 17-FEB-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 8862.02 | 6.85 | 0.00 | 43331.16 | 0.00 |
March | 136711.86 | 27-MAR-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12099.02 | 6.85 | 0.00 | 52322.22 | 0.00 |
April | 143790.73 | 14-APR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 11566.05 | 6.85 | 0.00 | 60248.96 | 0.00 |
May | 150464.66 | 22-MAY-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13236.95 | 6.85 | 0.00 | 66143.71 | 0.00 |
June | 148644.17 | 29-JUN-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12670.63 | 6.85 | 0.00 | 64125.96 | 0.00 |
July | 161987.49 | 28-JUL-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14718.01 | 6.85 | 0.00 | 75613.40 | 0.00 |
August | 157794.21 | 21-AUG-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 13915.71 | 6.85 | 0.00 | 72217.63 | 0.00 |
September | 155130.85 | 18-SEP-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14129.73 | 6.85 | 0.00 | 69202.47 | 0.00 |
October | 152498.08 | 02-OCT-14:20 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13508.03 | 6.85 | 0.00 | 67819.13 | 0.00 |
November | 140098.65 | 03-NOV-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 10968.36 | 6.85 | 0.00 | 57815.02 | 0.00 |
December | 134345.39 | 08-DEC-16:10 | 27150.80 | 41670.51 | 0.00 | 1410.29 | 10282.68 | 6.85 | 0.00 | 50517.70 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 123522.10 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 8862.02 | 6.85 | 0.00 | 43331.16 | 0.00 | |
Maximum of Months | 161987.49 | 27150.80 | 41670.51 | 0.00 | 1410.29 | 14718.01 | 6.85 | 0.00 | 75613.40 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.72 | 0.00 | 26.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.45 | 0.00 | 26.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 26.48 | 0.00 | 26.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.72 | 0.00 | 26.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.46 | 2.17 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.48 | 5.83 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.51 | 2.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.40 | 2.17 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.00 | 27.48 | 14.00 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.53 | 5.83 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 4.17 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.59 | 5.00 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.77 | 6.50 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.95 | 13.17 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.73 | 8.00 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.83 | 27.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.50 | 27.80 | 44.67 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.95 | 13.17 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.65 | 7.67 | 26.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.79 | 6.67 | 26.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.66 | 1.50 | 27.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.53 | 2.33 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.53 | 1.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.41 | 1.83 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.52 | 6.00 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.61 | 3.83 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.83 | 7.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.79 | 9.00 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.03 | 14.83 | 26.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.88 | 8.17 | 26.88 |
Annual Sum or Average | 0.00 | 0.00 | 72.50 | 27.06 | 70.67 | 27.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.03 | 1.50 | 26.03 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.83 | 14.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.02 | 1.50 | 28.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.90 | 1.00 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.07 | 3.33 | 28.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.95 | 2.83 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.02 | 2.00 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.01 | 5.33 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.09 | 3.17 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.01 | 4.17 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 4.00 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.83 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 39.00 | 27.99 | 28.83 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.09 | 5.33 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.49 | 0.50 | 27.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 2.17 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.55 | 1.17 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.62 | 3.33 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.71 | 10.17 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.54 | 5.00 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.56 | 6.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.57 | 2.33 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.17 | 27.61 | 31.17 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.71 | 10.17 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 19.85 | 4.67 | 19.85 | 16.00 | 23.66 | 16.00 | 24.52 |
February | 2.00 | 19.87 | 2.00 | 19.87 | 17.00 | 24.47 | 17.00 | 24.96 |
March | 5.67 | 19.31 | 5.67 | 19.31 | 1.50 | 20.06 | 1.50 | 20.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.97 | 6.33 | 24.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.03 | 21.17 | 25.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 24.96 | 28.33 | 24.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 25.42 | 35.67 | 25.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 25.35 | 42.33 | 25.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 25.41 | 61.00 | 25.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 | 25.37 | 81.83 | 25.36 |
November | 0.33 | 20.33 | 0.33 | 20.33 | 56.00 | 25.22 | 56.00 | 25.24 |
December | 5.17 | 19.63 | 5.17 | 19.63 | 19.33 | 23.62 | 19.33 | 24.46 |
Annual Sum or Average | 17.83 | 19.63 | 17.83 | 19.63 | 387.50 | 24.88 | 386.50 | 25.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 20.06 | 1.50 | 20.65 |
Maximum of Months | 5.67 | 20.33 | 5.67 | 20.33 | 82.67 | 25.42 | 81.83 | 25.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.85 | 1.33 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.79 | 0.33 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 2.50 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.72 | 2.00 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.65 | 1.50 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.76 | 4.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.81 | 2.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.81 | 3.17 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 3.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
Annual Sum or Average | 0.00 | 0.00 | 28.33 | 27.74 | 22.00 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 4.00 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.50 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.32 | 1.17 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.74 | 3.83 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.53 | 3.00 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.72 | 4.50 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.85 | 10.17 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.65 | 4.67 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 5.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.80 | 1.67 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.17 | 27.73 | 34.17 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.85 | 10.17 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.87 | 15.83 | 25.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 25.74 | 15.00 | 25.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 1.17 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.83 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.53 | 1.00 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.49 | 2.17 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.73 | 6.00 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 25.95 | 21.17 | 25.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 25.37 | 34.00 | 25.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 25.92 | 15.83 | 25.92 |
Annual Sum or Average | 0.00 | 0.00 | 113.50 | 25.90 | 113.50 | 25.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.73 | 34.00 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.98 | 1.67 | 27.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.83 | 0.67 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.92 | 2.83 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.86 | 2.33 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.77 | 1.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.89 | 4.33 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.94 | 2.67 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.96 | 3.17 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.86 | 3.17 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
Annual Sum or Average | 0.00 | 0.00 | 30.67 | 27.88 | 23.83 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.98 | 4.33 | 27.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 23.94 | 340.00 | 24.58 | 0.00 | 24.58 |
February | 14.33 | 23.90 | 335.00 | 24.52 | 0.00 | 24.52 |
March | 2.17 | 23.96 | 387.50 | 24.52 | 0.00 | 24.52 |
April | 0.00 | 0.00 | 466.00 | 24.44 | 0.00 | 24.44 |
May | 0.00 | 0.00 | 508.00 | 24.43 | 0.00 | 24.43 |
June | 0.00 | 0.00 | 496.00 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 497.00 | 24.43 | 0.00 | 24.43 |
August | 0.00 | 0.00 | 514.00 | 24.39 | 0.00 | 24.39 |
September | 0.00 | 0.00 | 485.00 | 24.41 | 0.00 | 24.41 |
October | 0.00 | 0.00 | 502.00 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 475.00 | 24.52 | 0.00 | 24.52 |
December | 2.83 | 23.93 | 364.17 | 24.58 | 0.00 | 24.58 |
Annual Sum or Average | 27.17 | 23.92 | 5369.67 | 24.47 | 0.00 | 24.47 |
Minimum of Months | 0.00 | 0.00 | 335.00 | 24.39 | 0.00 | 24.39 |
Maximum of Months | 14.33 | 23.96 | 514.00 | 24.58 | 0.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 189.17 | 23.26 | 159.33 | 23.76 | 0.00 | 23.76 |
February | 122.17 | 23.13 | 188.83 | 23.89 | 0.00 | 23.89 |
March | 107.00 | 23.29 | 257.83 | 24.02 | 0.00 | 24.02 |
April | 16.83 | 23.35 | 319.17 | 24.28 | 0.00 | 24.28 |
May | 2.50 | 23.24 | 446.17 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 460.83 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 463.67 | 24.27 | 0.00 | 24.27 |
August | 2.00 | 23.20 | 475.67 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 441.50 | 24.27 | 0.00 | 24.27 |
October | 1.00 | 23.23 | 435.17 | 24.35 | 0.00 | 24.35 |
November | 28.83 | 23.34 | 346.83 | 24.29 | 0.00 | 24.29 |
December | 152.33 | 23.14 | 165.67 | 23.77 | 0.00 | 23.77 |
Annual Sum or Average | 621.83 | 23.22 | 4160.67 | 24.16 | 0.00 | 24.16 |
Minimum of Months | 0.00 | 0.00 | 159.33 | 23.76 | 0.00 | 23.76 |
Maximum of Months | 189.17 | 23.35 | 475.67 | 24.35 | 0.00 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 317.50 | 22.91 | 97.50 | 23.21 | 0.00 | 23.21 |
February | 202.83 | 22.83 | 152.33 | 23.45 | 0.00 | 23.45 |
March | 169.83 | 23.03 | 218.50 | 23.71 | 0.00 | 23.71 |
April | 63.50 | 23.24 | 296.00 | 24.09 | 0.00 | 24.09 |
May | 5.17 | 23.30 | 430.33 | 24.28 | 0.00 | 24.28 |
June | 0.00 | 0.00 | 466.50 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 473.83 | 24.30 | 0.00 | 24.30 |
August | 6.00 | 22.96 | 466.50 | 24.25 | 0.00 | 24.25 |
September | 0.67 | 23.30 | 437.00 | 24.28 | 0.00 | 24.28 |
October | 15.00 | 23.20 | 390.67 | 24.31 | 0.00 | 24.31 |
November | 84.33 | 23.06 | 279.00 | 24.02 | 0.00 | 24.02 |
December | 263.00 | 22.82 | 125.17 | 23.27 | 0.00 | 23.27 |
Annual Sum or Average | 1127.83 | 22.93 | 3833.33 | 23.97 | 0.00 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 97.50 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 317.50 | 23.30 | 473.83 | 24.31 | 0.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 348.33 | 22.41 | 101.67 | 22.75 | 9.17 | 22.71 |
February | 233.50 | 22.61 | 170.33 | 23.18 | 22.17 | 23.17 |
March | 219.17 | 22.85 | 252.83 | 23.57 | 28.33 | 23.60 |
April | 85.50 | 23.63 | 340.00 | 24.18 | 17.67 | 24.23 |
May | 35.83 | 25.77 | 489.33 | 24.50 | 32.83 | 24.58 |
June | 29.67 | 26.43 | 494.17 | 24.54 | 29.67 | 24.64 |
July | 38.17 | 26.59 | 491.00 | 24.68 | 38.17 | 24.81 |
August | 33.50 | 26.19 | 497.00 | 24.52 | 33.50 | 24.62 |
September | 30.33 | 25.98 | 462.83 | 24.53 | 27.50 | 24.62 |
October | 48.33 | 24.76 | 433.00 | 24.47 | 28.67 | 24.55 |
November | 126.50 | 23.27 | 308.00 | 23.97 | 24.67 | 24.02 |
December | 304.83 | 22.49 | 164.67 | 23.03 | 31.00 | 23.05 |
Annual Sum or Average | 1533.67 | 23.15 | 4204.83 | 24.03 | 323.33 | 24.09 |
Minimum of Months | 29.67 | 22.41 | 101.67 | 22.75 | 9.17 | 22.71 |
Maximum of Months | 348.33 | 26.59 | 497.00 | 24.68 | 38.17 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.17 | 22.40 | 156.00 | 23.08 | 10.00 | 23.07 |
February | 196.17 | 22.69 | 211.17 | 23.45 | 18.33 | 23.46 |
March | 171.50 | 23.03 | 293.33 | 23.80 | 28.00 | 23.85 |
April | 102.67 | 24.16 | 361.00 | 24.37 | 36.33 | 24.52 |
May | 50.00 | 25.97 | 471.33 | 24.58 | 44.83 | 24.72 |
June | 42.83 | 26.63 | 490.00 | 24.61 | 42.83 | 24.76 |
July | 63.67 | 26.80 | 487.83 | 24.84 | 63.50 | 25.04 |
August | 56.50 | 25.79 | 488.67 | 24.57 | 44.67 | 24.71 |
September | 52.00 | 26.24 | 455.17 | 24.67 | 46.67 | 24.83 |
October | 71.50 | 25.13 | 428.17 | 24.59 | 45.50 | 24.74 |
November | 108.17 | 23.35 | 331.50 | 24.07 | 23.50 | 24.14 |
December | 283.83 | 22.46 | 186.83 | 23.14 | 29.67 | 23.18 |
Annual Sum or Average | 1471.00 | 23.55 | 4361.00 | 24.19 | 433.83 | 24.31 |
Minimum of Months | 42.83 | 22.40 | 156.00 | 23.08 | 10.00 | 23.07 |
Maximum of Months | 283.83 | 26.80 | 490.00 | 24.84 | 63.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 214.67 | 22.99 | 246.33 | 23.80 | 25.33 | 23.91 |
February | 158.50 | 23.34 | 253.50 | 23.99 | 34.17 | 24.10 |
March | 159.50 | 23.32 | 308.67 | 23.98 | 36.50 | 24.06 |
April | 88.83 | 24.06 | 355.17 | 24.33 | 27.83 | 24.43 |
May | 40.83 | 25.51 | 482.83 | 24.49 | 34.00 | 24.58 |
June | 28.00 | 26.34 | 490.50 | 24.51 | 28.00 | 24.60 |
July | 36.83 | 26.58 | 489.83 | 24.65 | 36.83 | 24.78 |
August | 37.00 | 26.27 | 495.33 | 24.55 | 37.00 | 24.66 |
September | 43.50 | 26.42 | 466.67 | 24.66 | 41.33 | 24.81 |
October | 72.83 | 26.11 | 459.67 | 24.79 | 62.67 | 24.98 |
November | 106.33 | 24.48 | 391.67 | 24.53 | 48.33 | 24.68 |
December | 212.33 | 23.26 | 270.00 | 23.94 | 52.00 | 24.10 |
Annual Sum or Average | 1199.17 | 24.03 | 4710.17 | 24.37 | 464.00 | 24.50 |
Minimum of Months | 28.00 | 22.99 | 246.33 | 23.80 | 25.33 | 23.91 |
Maximum of Months | 214.67 | 26.58 | 495.33 | 24.79 | 62.67 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.00 | 22.13 | 128.00 | 22.67 | 9.67 | 22.62 |
February | 247.33 | 22.56 | 178.33 | 23.22 | 29.00 | 23.25 |
March | 216.00 | 22.75 | 268.50 | 23.58 | 33.00 | 23.65 |
April | 125.17 | 23.72 | 331.50 | 24.23 | 33.83 | 24.36 |
May | 53.17 | 24.98 | 443.17 | 24.49 | 33.17 | 24.60 |
June | 31.67 | 26.05 | 464.33 | 24.50 | 27.67 | 24.61 |
July | 42.17 | 26.18 | 466.33 | 24.64 | 36.50 | 24.78 |
August | 43.83 | 25.32 | 473.17 | 24.48 | 31.00 | 24.59 |
September | 49.00 | 25.24 | 434.17 | 24.52 | 31.33 | 24.65 |
October | 86.67 | 24.47 | 404.67 | 24.47 | 41.00 | 24.61 |
November | 154.67 | 23.03 | 294.67 | 23.87 | 26.83 | 23.93 |
December | 298.50 | 22.30 | 177.17 | 22.99 | 33.50 | 23.04 |
Annual Sum or Average | 1678.17 | 23.07 | 4064.00 | 23.99 | 366.50 | 24.09 |
Minimum of Months | 31.67 | 22.13 | 128.00 | 22.67 | 9.67 | 22.62 |
Maximum of Months | 330.00 | 26.18 | 473.17 | 24.64 | 41.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.67 | 22.96 | 139.17 | 23.39 | 0.00 | 23.39 |
February | 178.50 | 23.06 | 194.83 | 23.67 | 8.17 | 23.71 |
March | 187.17 | 23.16 | 256.67 | 23.79 | 18.17 | 23.84 |
April | 37.83 | 23.93 | 361.17 | 24.24 | 7.67 | 24.28 |
May | 4.67 | 26.00 | 504.67 | 24.38 | 4.67 | 24.39 |
June | 8.00 | 26.36 | 496.00 | 24.42 | 8.00 | 24.45 |
July | 3.33 | 26.67 | 497.00 | 24.50 | 3.33 | 24.52 |
August | 10.50 | 26.18 | 514.00 | 24.43 | 10.50 | 24.47 |
September | 1.83 | 26.48 | 485.00 | 24.43 | 1.83 | 24.44 |
October | 9.67 | 26.14 | 494.83 | 24.45 | 9.67 | 24.48 |
November | 39.33 | 23.99 | 397.17 | 24.28 | 10.17 | 24.32 |
December | 199.50 | 22.99 | 212.00 | 23.66 | 2.83 | 23.68 |
Annual Sum or Average | 932.00 | 23.24 | 4552.50 | 24.17 | 85.00 | 24.20 |
Minimum of Months | 1.83 | 22.96 | 139.17 | 23.39 | 0.00 | 23.39 |
Maximum of Months | 251.67 | 26.67 | 514.00 | 24.50 | 18.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.00 | 23.07 | 233.00 | 23.86 | 2.33 | 23.88 |
February | 108.67 | 23.29 | 263.00 | 24.03 | 9.33 | 24.07 |
March | 97.17 | 23.55 | 331.50 | 24.15 | 18.83 | 24.21 |
April | 32.00 | 25.27 | 409.67 | 24.49 | 18.83 | 24.58 |
May | 18.67 | 26.66 | 499.00 | 24.51 | 18.67 | 24.59 |
June | 27.50 | 26.73 | 496.00 | 24.57 | 27.50 | 24.68 |
July | 49.33 | 26.84 | 497.00 | 24.80 | 49.33 | 24.97 |
August | 32.83 | 26.68 | 514.00 | 24.59 | 32.83 | 24.71 |
September | 33.17 | 26.77 | 485.00 | 24.66 | 33.17 | 24.79 |
October | 25.67 | 26.70 | 500.00 | 24.62 | 25.67 | 24.71 |
November | 26.83 | 24.60 | 433.00 | 24.40 | 11.67 | 24.45 |
December | 159.83 | 23.01 | 244.83 | 23.85 | 4.33 | 23.88 |
Annual Sum or Average | 763.67 | 24.20 | 4906.00 | 24.41 | 252.50 | 24.51 |
Minimum of Months | 18.67 | 23.01 | 233.00 | 23.85 | 2.33 | 23.88 |
Maximum of Months | 159.83 | 26.84 | 514.00 | 24.80 | 49.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.17 | 23.47 | 343.33 | 24.27 | 40.50 | 24.35 |
February | 96.17 | 23.68 | 332.67 | 24.35 | 39.67 | 24.44 |
March | 140.17 | 23.29 | 356.83 | 24.03 | 56.67 | 24.07 |
April | 56.50 | 23.95 | 401.33 | 24.31 | 37.17 | 24.32 |
May | 83.67 | 24.27 | 505.00 | 24.39 | 83.67 | 24.37 |
June | 124.17 | 24.42 | 496.00 | 24.42 | 124.17 | 24.42 |
July | 104.67 | 24.62 | 497.00 | 24.59 | 104.67 | 24.59 |
August | 130.50 | 24.78 | 514.00 | 24.60 | 130.50 | 24.63 |
September | 122.33 | 25.07 | 485.00 | 24.77 | 122.33 | 24.82 |
October | 122.83 | 25.52 | 501.33 | 24.95 | 122.83 | 25.04 |
November | 103.50 | 24.96 | 465.17 | 24.75 | 94.83 | 24.81 |
December | 136.33 | 23.76 | 340.33 | 24.37 | 48.50 | 24.51 |
Annual Sum or Average | 1352.00 | 24.31 | 5238.00 | 24.50 | 1005.50 | 24.56 |
Minimum of Months | 56.50 | 23.29 | 332.67 | 24.03 | 37.17 | 24.07 |
Maximum of Months | 140.17 | 25.52 | 514.00 | 24.95 | 130.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.50 | 22.92 | 192.33 | 23.59 | 0.00 | 23.59 |
February | 141.50 | 23.23 | 244.83 | 23.96 | 14.33 | 24.04 |
March | 124.50 | 23.31 | 326.00 | 24.07 | 19.67 | 24.13 |
April | 35.17 | 25.28 | 411.33 | 24.48 | 21.33 | 24.58 |
May | 16.83 | 26.64 | 491.17 | 24.51 | 16.83 | 24.58 |
June | 16.00 | 26.66 | 493.00 | 24.48 | 16.00 | 24.54 |
July | 23.50 | 26.82 | 495.67 | 24.64 | 23.50 | 24.73 |
August | 23.33 | 26.63 | 514.00 | 24.54 | 23.33 | 24.63 |
September | 19.17 | 26.83 | 483.17 | 24.58 | 19.17 | 24.66 |
October | 27.67 | 26.64 | 493.83 | 24.62 | 27.67 | 24.72 |
November | 35.83 | 24.15 | 414.83 | 24.36 | 12.00 | 24.41 |
December | 174.00 | 23.02 | 256.33 | 23.86 | 6.17 | 23.89 |
Annual Sum or Average | 838.00 | 23.77 | 4816.50 | 24.34 | 200.00 | 24.41 |
Minimum of Months | 16.00 | 22.92 | 192.33 | 23.59 | 0.00 | 23.59 |
Maximum of Months | 200.50 | 26.83 | 514.00 | 24.64 | 27.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 293.17 | 22.81 | 125.33 | 23.23 | 1.00 | 23.23 |
February | 189.83 | 22.95 | 191.33 | 23.56 | 14.17 | 23.60 |
March | 175.50 | 23.17 | 273.33 | 23.84 | 23.00 | 23.90 |
April | 45.67 | 24.16 | 375.17 | 24.29 | 15.17 | 24.34 |
May | 24.33 | 26.04 | 501.83 | 24.48 | 24.33 | 24.55 |
June | 14.33 | 26.44 | 496.00 | 24.47 | 14.33 | 24.52 |
July | 13.33 | 26.58 | 496.00 | 24.56 | 13.33 | 24.61 |
August | 18.00 | 26.07 | 510.17 | 24.45 | 18.00 | 24.50 |
September | 10.00 | 26.18 | 480.67 | 24.45 | 10.00 | 24.48 |
October | 25.00 | 25.71 | 466.50 | 24.50 | 22.17 | 24.56 |
November | 81.50 | 23.74 | 353.00 | 24.19 | 20.50 | 24.25 |
December | 251.67 | 22.87 | 180.33 | 23.45 | 20.33 | 23.51 |
Annual Sum or Average | 1142.33 | 23.33 | 4449.67 | 24.16 | 196.33 | 24.21 |
Minimum of Months | 10.00 | 22.81 | 125.33 | 23.23 | 1.00 | 23.23 |
Maximum of Months | 293.17 | 26.58 | 510.17 | 24.56 | 24.33 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 220.83 | 22.72 | 139.17 | 23.43 | 5.17 | 23.45 |
February | 157.00 | 23.02 | 177.17 | 23.74 | 14.33 | 23.80 |
March | 136.00 | 23.30 | 242.83 | 24.00 | 24.17 | 24.08 |
April | 71.67 | 24.60 | 308.50 | 24.54 | 31.50 | 24.69 |
May | 36.67 | 26.43 | 403.83 | 24.67 | 36.50 | 24.81 |
June | 33.33 | 26.69 | 415.83 | 24.67 | 33.33 | 24.81 |
July | 53.50 | 26.82 | 416.83 | 24.91 | 53.50 | 25.10 |
August | 35.33 | 26.56 | 417.33 | 24.66 | 35.33 | 24.80 |
September | 37.50 | 26.68 | 392.83 | 24.75 | 37.50 | 24.90 |
October | 40.17 | 25.98 | 373.50 | 24.72 | 34.50 | 24.86 |
November | 72.50 | 23.79 | 291.67 | 24.30 | 19.83 | 24.38 |
December | 220.83 | 22.76 | 157.17 | 23.46 | 19.83 | 23.55 |
Annual Sum or Average | 1115.33 | 23.84 | 3736.67 | 24.36 | 345.50 | 24.49 |
Minimum of Months | 33.33 | 22.72 | 139.17 | 23.43 | 5.17 | 23.45 |
Maximum of Months | 220.83 | 26.82 | 417.33 | 24.91 | 53.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.00 | 23.49 | 275.50 | 24.20 | 22.33 | 24.33 |
February | 111.00 | 23.80 | 282.33 | 24.31 | 29.17 | 24.44 |
March | 113.00 | 23.69 | 333.67 | 24.19 | 30.17 | 24.29 |
April | 43.17 | 24.62 | 384.67 | 24.42 | 19.67 | 24.49 |
May | 25.17 | 26.00 | 496.50 | 24.48 | 25.17 | 24.55 |
June | 13.17 | 26.31 | 495.67 | 24.43 | 13.17 | 24.48 |
July | 13.83 | 26.58 | 496.00 | 24.54 | 13.83 | 24.59 |
August | 25.67 | 26.29 | 511.33 | 24.50 | 25.67 | 24.58 |
September | 35.17 | 26.70 | 482.50 | 24.65 | 35.17 | 24.78 |
October | 60.50 | 26.63 | 485.33 | 24.84 | 59.33 | 25.02 |
November | 72.00 | 25.25 | 423.67 | 24.69 | 45.17 | 24.83 |
December | 180.67 | 23.79 | 297.50 | 24.29 | 46.67 | 24.47 |
Annual Sum or Average | 853.33 | 24.43 | 4964.67 | 24.47 | 365.50 | 24.59 |
Minimum of Months | 13.17 | 23.49 | 275.50 | 24.19 | 13.17 | 24.29 |
Maximum of Months | 180.67 | 26.70 | 511.33 | 24.84 | 59.33 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 279.17 | 22.55 | 151.33 | 23.17 | 1.33 | 23.17 |
February | 193.67 | 22.89 | 202.17 | 23.63 | 21.00 | 23.72 |
March | 167.00 | 23.09 | 295.50 | 23.88 | 27.33 | 23.97 |
April | 79.67 | 24.34 | 367.00 | 24.41 | 31.00 | 24.53 |
May | 35.33 | 25.91 | 469.00 | 24.54 | 30.67 | 24.64 |
June | 22.17 | 26.56 | 481.17 | 24.48 | 22.17 | 24.57 |
July | 28.00 | 26.70 | 488.50 | 24.60 | 27.83 | 24.71 |
August | 26.83 | 26.41 | 492.17 | 24.51 | 26.83 | 24.60 |
September | 27.50 | 26.41 | 455.00 | 24.55 | 26.00 | 24.66 |
October | 48.67 | 25.51 | 443.50 | 24.58 | 35.67 | 24.71 |
November | 99.17 | 23.47 | 336.33 | 24.15 | 21.17 | 24.22 |
December | 249.83 | 22.70 | 203.83 | 23.45 | 23.17 | 23.53 |
Annual Sum or Average | 1257.00 | 23.43 | 4385.50 | 24.19 | 294.17 | 24.29 |
Minimum of Months | 22.17 | 22.55 | 151.33 | 23.17 | 1.33 | 23.17 |
Maximum of Months | 279.17 | 26.70 | 492.17 | 24.60 | 35.67 | 24.71 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41919 | 41.01088 | 0.49432 | 10.43989 |
February | 454.00000 | 24.42719 | 41.93856 | 0.50590 | 10.76227 |
March | 514.00000 | 24.40266 | 42.70052 | 0.51278 | 10.86344 |
April | 485.00000 | 24.42560 | 45.87338 | 0.54845 | 11.57695 |
May | 508.00000 | 24.42629 | 47.55962 | -0.2705 | 7.08055 |
June | 496.00000 | 24.39248 | 47.86419 | -0.2741 | 7.10991 |
July | 497.00000 | 24.42564 | 47.62373 | -0.2648 | 7.00149 |
August | 514.00000 | 24.39172 | 47.81948 | -0.2728 | 7.08378 |
September | 485.00000 | 24.41391 | 47.56898 | -0.2684 | 7.04938 |
October | 502.00000 | 24.48708 | 47.14683 | 0.58353 | 12.48496 |
November | 489.00000 | 24.50359 | 46.19305 | 0.57028 | 12.16896 |
December | 497.00000 | 24.43217 | 42.65665 | 0.51004 | 10.78847 |
Annual Sum or Average | 5943.00000 | 24.42877 | 45.51586 | 0.19473 | 9.51853 |
Minimum of Months | 454.00000 | 24.39172 | 41.01088 | -0.2741 | 7.00149 |
Maximum of Months | 514.00000 | 24.50359 | 47.86419 | 0.58353 | 12.48496 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.81833 | 42.82582 | 0.34001 | 7.89595 |
February | 454.00000 | 23.88163 | 43.64149 | 0.36763 | 8.47340 |
March | 514.00000 | 23.98033 | 44.18012 | 0.40236 | 8.79711 |
April | 485.00000 | 24.11234 | 47.15375 | 0.46548 | 9.74219 |
May | 508.00000 | 24.20486 | 48.79255 | -0.3591 | 8.06407 |
June | 496.00000 | 24.21408 | 48.97908 | -0.3476 | 7.88051 |
July | 497.00000 | 24.23055 | 48.74523 | -0.3416 | 7.79253 |
August | 514.00000 | 24.20466 | 49.00489 | -0.3504 | 7.90657 |
September | 485.00000 | 24.21423 | 48.78558 | -0.3492 | 7.91745 |
October | 502.00000 | 24.26111 | 48.28201 | 0.51938 | 10.90173 |
November | 489.00000 | 24.16183 | 47.53423 | 0.47577 | 10.00829 |
December | 497.00000 | 23.81883 | 44.51893 | 0.35490 | 8.14054 |
Annual Sum or Average | 5943.00000 | 24.09314 | 46.88773 | 0.09522 | 8.62394 |
Minimum of Months | 454.00000 | 23.81833 | 42.82582 | -0.3591 | 7.79253 |
Maximum of Months | 514.00000 | 24.26111 | 49.00489 | 0.51938 | 10.90173 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33106 | 42.87977 | 0.21738 | 6.96658 |
February | 454.00000 | 23.54699 | 43.47659 | 0.28418 | 7.86236 |
March | 514.00000 | 23.75004 | 43.88052 | 0.34632 | 8.28376 |
April | 485.00000 | 24.01926 | 46.55634 | 0.44642 | 9.45107 |
May | 508.00000 | 24.18775 | 48.44866 | -0.3501 | 7.94219 |
June | 496.00000 | 24.23743 | 48.81580 | -0.3224 | 7.53866 |
July | 497.00000 | 24.27274 | 48.54578 | -0.3079 | 7.37684 |
August | 514.00000 | 24.20038 | 48.96573 | -0.3364 | 7.75353 |
September | 485.00000 | 24.21929 | 48.70837 | -0.3340 | 7.72384 |
October | 502.00000 | 24.18362 | 48.20807 | 0.50538 | 10.62607 |
November | 489.00000 | 23.95626 | 47.53399 | 0.42536 | 9.23117 |
December | 497.00000 | 23.39377 | 44.60745 | 0.24844 | 7.32945 |
Annual Sum or Average | 5943.00000 | 23.94395 | 46.73678 | 0.06597 | 8.17279 |
Minimum of Months | 454.00000 | 23.33106 | 42.87977 | -0.3501 | 6.96658 |
Maximum of Months | 514.00000 | 24.27274 | 48.96573 | 0.50538 | 10.62607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.92317 | 46.22053 | 0.12500 | 7.34533 |
February | 454.00000 | 23.30465 | 46.63359 | 0.23975 | 8.35932 |
March | 514.00000 | 23.56987 | 47.38024 | 0.32330 | 9.08551 |
April | 485.00000 | 24.07242 | 48.86861 | 0.48394 | 10.54611 |
May | 508.00000 | 24.37377 | 50.80230 | -0.2317 | 7.12525 |
June | 496.00000 | 24.42303 | 50.45323 | -0.1922 | 6.75183 |
July | 497.00000 | 24.52102 | 49.52822 | -0.1580 | 6.77484 |
August | 514.00000 | 24.37754 | 50.70887 | -0.2208 | 7.02340 |
September | 485.00000 | 24.39884 | 50.35181 | -0.2257 | 7.11680 |
October | 502.00000 | 24.31629 | 50.83833 | 0.56617 | 12.36216 |
November | 489.00000 | 23.89836 | 50.46729 | 0.43173 | 9.95808 |
December | 497.00000 | 23.10325 | 48.72834 | 0.19264 | 7.98462 |
Annual Sum or Average | 5943.00000 | 23.94402 | 49.26456 | 0.10922 | 8.36417 |
Minimum of Months | 454.00000 | 22.92317 | 46.22053 | -0.2317 | 6.75183 |
Maximum of Months | 514.00000 | 24.52102 | 50.83833 | 0.56617 | 12.36216 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.22243 | 44.91786 | 0.22391 | 8.46021 |
February | 454.00000 | 23.49893 | 45.58634 | 0.32097 | 9.18328 |
March | 514.00000 | 23.75583 | 46.23419 | 0.40998 | 10.20856 |
April | 485.00000 | 24.14815 | 47.99559 | 0.55351 | 12.58413 |
May | 508.00000 | 24.36102 | 50.31206 | -0.1750 | 7.06268 |
June | 496.00000 | 24.42644 | 50.08482 | -0.1371 | 6.73383 |
July | 497.00000 | 24.56016 | 49.02601 | -0.0861 | 7.16610 |
August | 514.00000 | 24.37188 | 50.30232 | -0.1666 | 7.05434 |
September | 485.00000 | 24.42587 | 49.73402 | -0.1551 | 7.16715 |
October | 502.00000 | 24.32913 | 50.19003 | 0.61190 | 13.80297 |
November | 489.00000 | 23.95349 | 49.75810 | 0.47731 | 10.91034 |
December | 497.00000 | 23.16966 | 48.01852 | 0.23323 | 8.66835 |
Annual Sum or Average | 5943.00000 | 24.02176 | 48.53145 | 0.17386 | 9.07463 |
Minimum of Months | 454.00000 | 23.16966 | 44.91786 | -0.1750 | 6.73383 |
Maximum of Months | 514.00000 | 24.56016 | 50.31206 | 0.61190 | 13.80297 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.71457 | 43.06195 | 0.36715 | 10.68262 |
February | 454.00000 | 23.87325 | 44.35253 | 0.42600 | 11.21982 |
March | 514.00000 | 23.87714 | 45.88498 | 0.43494 | 10.81486 |
April | 485.00000 | 24.16248 | 48.33807 | 0.52388 | 11.63454 |
May | 508.00000 | 24.35892 | 50.88399 | -0.2375 | 7.23890 |
June | 496.00000 | 24.39246 | 50.67543 | -0.2126 | 6.87049 |
July | 497.00000 | 24.49433 | 49.67864 | -0.1724 | 6.86181 |
August | 514.00000 | 24.38955 | 50.54831 | -0.2022 | 6.97619 |
September | 485.00000 | 24.46681 | 49.76258 | -0.1589 | 7.09636 |
October | 502.00000 | 24.49844 | 49.54695 | 0.66250 | 15.31599 |
November | 489.00000 | 24.29601 | 48.36842 | 0.58170 | 13.62514 |
December | 497.00000 | 23.76728 | 45.75218 | 0.40519 | 11.49428 |
Annual Sum or Average | 5943.00000 | 24.19240 | 48.09635 | 0.19872 | 9.96887 |
Minimum of Months | 454.00000 | 23.71457 | 43.06195 | -0.2375 | 6.86181 |
Maximum of Months | 514.00000 | 24.49844 | 50.88399 | 0.66250 | 15.31599 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.81875 | 45.58113 | 0.13462 | 7.85282 |
February | 454.00000 | 23.24223 | 46.01753 | 0.26510 | 9.30809 |
March | 514.00000 | 23.52747 | 46.60310 | 0.36128 | 10.19832 |
April | 485.00000 | 24.01199 | 48.41292 | 0.52129 | 12.06764 |
May | 508.00000 | 24.27789 | 50.60754 | -0.2059 | 7.52816 |
June | 496.00000 | 24.32783 | 50.54785 | -0.1877 | 7.06375 |
July | 497.00000 | 24.43300 | 49.55638 | -0.1401 | 7.12852 |
August | 514.00000 | 24.31503 | 50.52599 | -0.1867 | 7.20553 |
September | 485.00000 | 24.31536 | 50.21693 | -0.2046 | 7.58114 |
October | 502.00000 | 24.22651 | 50.52720 | 0.58511 | 13.21931 |
November | 489.00000 | 23.76688 | 50.15346 | 0.43652 | 10.49778 |
December | 497.00000 | 23.02019 | 47.97031 | 0.20899 | 8.77738 |
Annual Sum or Average | 5943.00000 | 23.86076 | 48.91037 | 0.13039 | 9.02674 |
Minimum of Months | 454.00000 | 22.81875 | 45.58113 | -0.2059 | 7.06375 |
Maximum of Months | 514.00000 | 24.43300 | 50.60754 | 0.58511 | 13.21931 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.49526 | 45.45105 | 0.26933 | 7.46129 |
February | 454.00000 | 23.67041 | 46.22734 | 0.32714 | 8.36042 |
March | 514.00000 | 23.74854 | 47.34210 | 0.35890 | 8.76615 |
April | 485.00000 | 24.12724 | 48.95418 | 0.48234 | 10.16677 |
May | 508.00000 | 24.35830 | 49.91501 | -0.2663 | 7.08220 |
June | 496.00000 | 24.38509 | 49.57912 | -0.2331 | 6.75959 |
July | 497.00000 | 24.48751 | 48.67372 | -0.1935 | 6.55603 |
August | 514.00000 | 24.39554 | 49.41639 | -0.2292 | 6.76877 |
September | 485.00000 | 24.42148 | 49.00305 | -0.2293 | 6.78154 |
October | 502.00000 | 24.40866 | 49.40056 | 0.58193 | 12.48487 |
November | 489.00000 | 24.19073 | 49.17029 | 0.50150 | 10.67068 |
December | 497.00000 | 23.68969 | 47.36458 | 0.33685 | 8.40872 |
Annual Sum or Average | 5943.00000 | 24.11723 | 48.38789 | 0.13979 | 8.34922 |
Minimum of Months | 454.00000 | 23.49526 | 45.45105 | -0.2663 | 6.55603 |
Maximum of Months | 514.00000 | 24.48751 | 49.91501 | 0.58193 | 12.48487 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86205 | 44.11559 | 0.38496 | 9.18640 |
February | 454.00000 | 23.96022 | 45.07941 | 0.43000 | 9.81614 |
March | 514.00000 | 24.03497 | 45.98877 | 0.46912 | 10.49556 |
April | 485.00000 | 24.31363 | 47.86103 | 0.57711 | 12.60500 |
May | 508.00000 | 24.41999 | 49.38159 | -0.1853 | 6.69030 |
June | 496.00000 | 24.44922 | 49.16281 | -0.1576 | 6.53607 |
July | 497.00000 | 24.59396 | 48.12895 | -0.1001 | 6.69891 |
August | 514.00000 | 24.45498 | 48.98921 | -0.1531 | 6.53997 |
September | 485.00000 | 24.51650 | 48.40391 | -0.1353 | 6.58138 |
October | 502.00000 | 24.50718 | 48.74468 | 0.64828 | 14.43326 |
November | 489.00000 | 24.30487 | 48.52312 | 0.56163 | 12.09208 |
December | 497.00000 | 23.83185 | 46.72274 | 0.39421 | 9.45086 |
Annual Sum or Average | 5943.00000 | 24.27236 | 47.60706 | 0.22533 | 9.24706 |
Minimum of Months | 454.00000 | 23.83185 | 44.11559 | -0.1853 | 6.53607 |
Maximum of Months | 514.00000 | 24.59396 | 49.38159 | 0.64828 | 14.43326 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12631 | 44.90463 | 0.50959 | 12.22814 |
February | 454.00000 | 24.18944 | 46.70105 | 0.53226 | 12.43064 |
March | 514.00000 | 23.97544 | 48.93967 | 0.48399 | 11.45905 |
April | 485.00000 | 24.22991 | 52.31929 | 0.55491 | 11.97578 |
May | 508.00000 | 24.40017 | 56.41002 | -0.2108 | 6.55243 |
June | 496.00000 | 24.42316 | 58.52562 | -0.1736 | 6.18968 |
July | 497.00000 | 24.57899 | 56.51673 | -0.1207 | 6.11761 |
August | 514.00000 | 24.55116 | 57.63455 | -0.1089 | 6.13740 |
September | 485.00000 | 24.69316 | 55.63486 | -0.0483 | 6.30531 |
October | 502.00000 | 24.80980 | 53.90347 | 0.77300 | 18.40020 |
November | 489.00000 | 24.62543 | 52.34730 | 0.70538 | 16.42493 |
December | 497.00000 | 24.16267 | 47.37503 | 0.54024 | 13.04442 |
Annual Sum or Average | 5943.00000 | 24.39743 | 52.64309 | 0.28340 | 10.58117 |
Minimum of Months | 454.00000 | 23.97544 | 44.90463 | -0.2108 | 6.11761 |
Maximum of Months | 514.00000 | 24.80980 | 58.52562 | 0.77300 | 18.40020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.64025 | 44.62562 | 0.33018 | 8.31069 |
February | 454.00000 | 23.86316 | 45.30619 | 0.40517 | 9.79452 |
March | 514.00000 | 23.97439 | 46.16123 | 0.45367 | 10.47767 |
April | 485.00000 | 24.29428 | 48.04677 | 0.56901 | 12.41330 |
May | 508.00000 | 24.41006 | 49.53486 | -0.1953 | 6.82240 |
June | 496.00000 | 24.40003 | 49.55208 | -0.1962 | 6.69564 |
July | 497.00000 | 24.53008 | 48.50196 | -0.1361 | 6.54451 |
August | 514.00000 | 24.44978 | 49.10163 | -0.1588 | 6.53270 |
September | 485.00000 | 24.48343 | 48.71368 | -0.1644 | 6.70178 |
October | 502.00000 | 24.49170 | 48.91561 | 0.63891 | 14.18328 |
November | 489.00000 | 24.25439 | 48.69855 | 0.54727 | 11.81652 |
December | 497.00000 | 23.81702 | 46.52879 | 0.39715 | 9.63097 |
Annual Sum or Average | 5943.00000 | 24.21924 | 47.82198 | 0.20511 | 9.14641 |
Minimum of Months | 454.00000 | 23.64025 | 44.62562 | -0.1962 | 6.53270 |
Maximum of Months | 514.00000 | 24.53008 | 49.55208 | 0.63891 | 14.18328 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33551 | 46.00045 | 0.22956 | 7.39584 |
February | 454.00000 | 23.58843 | 46.57075 | 0.31044 | 8.43620 |
March | 514.00000 | 23.78220 | 47.37457 | 0.37322 | 9.16866 |
April | 485.00000 | 24.17190 | 49.10470 | 0.50234 | 10.67978 |
May | 508.00000 | 24.39557 | 50.67584 | -0.2418 | 7.05901 |
June | 496.00000 | 24.41210 | 50.23921 | -0.2157 | 6.78101 |
July | 497.00000 | 24.50516 | 49.37202 | -0.1859 | 6.68550 |
August | 514.00000 | 24.38541 | 50.41352 | -0.2355 | 6.95031 |
September | 485.00000 | 24.40466 | 50.04415 | -0.2400 | 6.98927 |
October | 502.00000 | 24.38271 | 50.54013 | 0.57501 | 12.44414 |
November | 489.00000 | 24.08027 | 50.16173 | 0.47395 | 10.32790 |
December | 497.00000 | 23.46429 | 48.35143 | 0.28258 | 8.08536 |
Annual Sum or Average | 5943.00000 | 24.07856 | 49.08571 | 0.13340 | 8.41076 |
Minimum of Months | 454.00000 | 23.33551 | 46.00045 | -0.2418 | 6.68550 |
Maximum of Months | 514.00000 | 24.50516 | 50.67584 | 0.57501 | 12.44414 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.47224 | 44.54494 | 0.28204 | 8.57041 |
February | 385.00000 | 23.69147 | 45.41782 | 0.35841 | 9.23702 |
March | 433.00000 | 23.87288 | 46.41518 | 0.42610 | 10.20290 |
April | 410.00000 | 24.26332 | 48.11616 | 0.55733 | 12.55309 |
May | 430.00000 | 24.45298 | 50.24703 | -0.1867 | 7.16232 |
June | 418.00000 | 24.50169 | 49.88632 | -0.1575 | 6.90671 |
July | 422.00000 | 24.65311 | 48.74651 | -0.1050 | 7.25228 |
August | 433.00000 | 24.46284 | 50.00927 | -0.1789 | 7.08409 |
September | 410.00000 | 24.52025 | 49.42910 | -0.1667 | 7.22220 |
October | 427.00000 | 24.45130 | 49.95809 | 0.61715 | 13.89725 |
November | 417.00000 | 24.11513 | 49.43532 | 0.50276 | 11.17486 |
December | 422.00000 | 23.42029 | 47.69266 | 0.29049 | 8.72741 |
Annual Sum or Average | 5034.00000 | 24.15866 | 48.34218 | 0.18494 | 9.16036 |
Minimum of Months | 385.00000 | 23.42029 | 44.54494 | -0.1867 | 6.90671 |
Maximum of Months | 433.00000 | 24.65311 | 50.24703 | 0.61715 | 13.89725 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.03992 | 42.95206 | 0.45243 | 11.26833 |
February | 454.00000 | 24.12010 | 44.29498 | 0.48733 | 11.64146 |
March | 514.00000 | 24.05738 | 45.85605 | 0.47677 | 10.98759 |
April | 485.00000 | 24.26160 | 48.53506 | 0.54121 | 11.72520 |
May | 508.00000 | 24.38637 | 50.74114 | -0.2458 | 7.12821 |
June | 496.00000 | 24.38342 | 50.45326 | -0.2352 | 6.89929 |
July | 497.00000 | 24.48130 | 49.51184 | -0.1992 | 6.76725 |
August | 514.00000 | 24.40260 | 50.23382 | -0.2159 | 6.88200 |
September | 485.00000 | 24.49147 | 49.40432 | -0.1697 | 6.91214 |
October | 502.00000 | 24.58309 | 49.16802 | 0.67325 | 15.47196 |
November | 489.00000 | 24.46311 | 48.09122 | 0.61935 | 14.17863 |
December | 497.00000 | 24.05651 | 45.48002 | 0.47900 | 11.97203 |
Annual Sum or Average | 5943.00000 | 24.31115 | 47.91753 | 0.21890 | 10.13341 |
Minimum of Months | 454.00000 | 24.03992 | 42.95206 | -0.2458 | 6.76725 |
Maximum of Months | 514.00000 | 24.58309 | 50.74114 | 0.67325 | 15.47196 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.25930 | 45.42669 | 0.24386 | 7.94575 |
February | 454.00000 | 23.57819 | 45.97772 | 0.34508 | 9.46715 |
March | 514.00000 | 23.78247 | 46.61861 | 0.41854 | 10.35955 |
April | 485.00000 | 24.17839 | 48.60128 | 0.55171 | 12.30496 |
May | 508.00000 | 24.35589 | 50.45245 | -0.2014 | 7.14266 |
June | 496.00000 | 24.36242 | 50.30303 | -0.1990 | 6.88675 |
July | 497.00000 | 24.46463 | 49.33933 | -0.1556 | 6.83552 |
August | 514.00000 | 24.36556 | 50.19689 | -0.1906 | 6.91364 |
September | 485.00000 | 24.37841 | 49.86637 | -0.2043 | 7.17598 |
October | 502.00000 | 24.35328 | 50.19546 | 0.60506 | 13.46980 |
November | 489.00000 | 24.00732 | 49.85524 | 0.48954 | 10.95194 |
December | 497.00000 | 23.40782 | 47.66828 | 0.30330 | 8.92518 |
Annual Sum or Average | 5943.00000 | 24.04390 | 48.72427 | 0.16494 | 9.02040 |
Minimum of Months | 454.00000 | 23.25930 | 45.42669 | -0.2043 | 6.83552 |
Maximum of Months | 514.00000 | 24.46463 | 50.45245 | 0.60506 | 13.46980 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.515850E+11 | 0.114359E+11 | 417.94 | 0.382546E+11 | 0.133304E+11 | 0.00 | 1.00 | 01-JAN-09:23 | 0.00 | 01-JAN-00:10 | 84523.45 | 02-JAN-14:00 | 59780.64 | 02-JAN-15:10 | 28692.78 | 07-JAN-06:13 | 19682.16 | 02-JAN-14:00 | 0.00 |
February | 0.523569E+11 | 0.115609E+11 | 375.63 | 0.394467E+11 | 0.129101E+11 | 0.00 | 1.00 | 01-FEB-10:50 | 0.00 | 01-FEB-00:10 | 76043.02 | 13-FEB-07:03 | 55451.89 | 21-FEB-16:50 | 30905.52 | 13-FEB-06:12 | 16066.97 | 13-FEB-07:03 | 0.00 |
March | 0.630293E+11 | 0.138859E+11 | 433.51 | 0.464186E+11 | 0.166107E+11 | 0.00 | 1.00 | 01-MAR-11:50 | 0.00 | 01-MAR-00:10 | 83455.88 | 06-MAR-07:03 | 58458.62 | 27-MAR-15:40 | 35135.63 | 06-MAR-06:12 | 18081.56 | 13-MAR-15:20 | 0.00 |
April | 0.716338E+11 | 0.160165E+11 | 421.44 | 0.520501E+11 | 0.195837E+11 | 0.00 | 1.00 | 01-APR-05:13 | 0.00 | 01-APR-00:10 | 87768.56 | 13-APR-04:03 | 64147.97 | 17-APR-15:00 | 34851.09 | 13-APR-04:03 | 20846.44 | 14-APR-15:00 | 0.00 |
May | 0.962134E+11 | 0.219992E+11 | 456.00 | 0.650559E+11 | 0.311575E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 109883.43 | 15-MAY-04:02 | 79732.47 | 15-MAY-04:02 | 42555.98 | 27-MAY-04:03 | 23861.74 | 15-MAY-04:02 | 0.00 |
June | 0.108022E+12 | 0.247785E+11 | 457.84 | 0.683961E+11 | 0.396257E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 120548.26 | 08-JUN-04:02 | 80508.13 | 28-JUN-04:02 | 41093.76 | 07-JUN-04:03 | 27830.37 | 08-JUN-04:02 | 0.00 |
July | 0.113747E+12 | 0.266823E+11 | 467.74 | 0.722404E+11 | 0.415070E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 114067.47 | 31-JUL-04:02 | 81486.50 | 31-JUL-04:02 | 38322.89 | 12-JUL-12:02 | 25860.20 | 28-JUL-15:30 | 0.00 |
August | 0.117816E+12 | 0.273768E+11 | 476.38 | 0.744312E+11 | 0.433845E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 122033.58 | 18-AUG-04:02 | 82516.64 | 01-AUG-04:02 | 41897.06 | 21-AUG-12:03 | 27532.13 | 18-AUG-04:02 | 0.00 |
September | 0.108500E+12 | 0.249963E+11 | 458.52 | 0.690813E+11 | 0.394187E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 126330.95 | 22-SEP-04:02 | 81920.22 | 11-SEP-04:02 | 45489.10 | 23-SEP-04:02 | 28475.88 | 22-SEP-04:02 | 0.00 |
October | 0.998494E+11 | 0.226694E+11 | 453.32 | 0.664193E+11 | 0.334301E+11 | 0.00 | 1.00 | 01-OCT-09:23 | 0.00 | 01-OCT-00:10 | 126345.14 | 03-OCT-04:02 | 80144.40 | 30-OCT-04:02 | 48841.76 | 04-OCT-04:02 | 27781.22 | 03-OCT-04:02 | 0.00 |
November | 0.788716E+11 | 0.174646E+11 | 411.10 | 0.535260E+11 | 0.253456E+11 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 103941.43 | 04-NOV-04:03 | 66859.38 | 21-NOV-05:02 | 46721.63 | 04-NOV-04:03 | 22242.40 | 30-NOV-05:03 | 0.00 |
December | 0.552225E+11 | 0.121899E+11 | 411.51 | 0.396309E+11 | 0.155916E+11 | 0.00 | 1.00 | 01-DEC-06:13 | 0.00 | 01-DEC-00:10 | 94242.20 | 09-DEC-06:03 | 59656.65 | 11-DEC-07:03 | 35742.13 | 09-DEC-06:03 | 20206.73 | 09-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.101685E+13 | 0.231056E+12 | 5240.94 | 0.684951E+12 | 0.331896E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.515850E+11 | 0.114359E+11 | 375.63 | 0.382546E+11 | 0.129101E+11 | 0.00 | 1.00 | 0.00 | 76043.02 | 55451.89 | 28692.78 | 16066.97 | 0.00 | ||||||
Maximum of Months | 0.117816E+12 | 0.273768E+11 | 476.38 | 0.744312E+11 | 0.433845E+11 | 0.00 | 1.00 | 0.00 | 126345.14 | 82516.64 | 48841.76 | 28475.88 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.424811E+11 | 0.949331E+10 | 409.96 | 0.302388E+11 | 0.122423E+11 | 0.00 | 1.00 | 01-JAN-09:33 | 0.00 | 01-JAN-00:10 | 77090.62 | 02-JAN-14:00 | 52125.32 | 02-JAN-15:00 | 29704.71 | 14-JAN-06:03 | 17897.33 | 02-JAN-14:00 | 0.00 |
February | 0.445338E+11 | 0.988026E+10 | 374.72 | 0.324175E+11 | 0.121162E+11 | 0.00 | 1.00 | 01-FEB-13:20 | 0.00 | 01-FEB-00:10 | 62716.53 | 11-FEB-06:03 | 47542.34 | 21-FEB-16:20 | 29682.77 | 11-FEB-06:03 | 14001.42 | 19-FEB-15:22 | 0.00 |
March | 0.550279E+11 | 0.121516E+11 | 435.72 | 0.392811E+11 | 0.157467E+11 | 0.00 | 1.00 | 01-MAR-14:30 | 0.00 | 01-MAR-00:10 | 71298.47 | 27-MAR-15:00 | 51965.64 | 27-MAR-15:20 | 26149.87 | 14-MAR-09:40 | 16334.62 | 27-MAR-15:00 | 0.00 |
April | 0.636139E+11 | 0.142295E+11 | 422.57 | 0.450817E+11 | 0.185322E+11 | 0.00 | 1.00 | 01-APR-12:40 | 0.00 | 01-APR-00:10 | 78206.76 | 14-APR-15:00 | 56772.37 | 17-APR-15:00 | 27508.24 | 13-APR-04:03 | 18929.99 | 14-APR-15:00 | 0.00 |
May | 0.851445E+11 | 0.194021E+11 | 449.36 | 0.558422E+11 | 0.293023E+11 | 0.00 | 1.00 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 112093.22 | 30-MAY-04:02 | 73077.81 | 30-MAY-04:02 | 45768.76 | 27-MAY-05:03 | 25158.25 | 29-MAY-15:51 | 0.00 |
June | 0.965705E+11 | 0.220203E+11 | 451.89 | 0.590470E+11 | 0.375235E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 119302.99 | 19-JUN-04:02 | 73223.02 | 08-JUN-04:02 | 52106.00 | 19-JUN-04:02 | 26580.85 | 08-JUN-04:02 | 0.00 |
July | 0.101226E+12 | 0.235817E+11 | 457.94 | 0.620936E+11 | 0.391322E+11 | 0.00 | 1.00 | 01-JUL-04:53 | 0.00 | 01-JUL-00:10 | 117110.06 | 03-JUL-04:02 | 74192.23 | 31-JUL-04:02 | 44752.85 | 03-JUL-04:02 | 25041.00 | 03-JUL-04:02 | 0.00 |
August | 0.102380E+12 | 0.236365E+11 | 465.33 | 0.622323E+11 | 0.401481E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 116373.45 | 18-AUG-04:02 | 75125.22 | 21-AUG-04:02 | 43649.35 | 18-AUG-04:02 | 26109.92 | 18-AUG-04:02 | 0.00 |
September | 0.941730E+11 | 0.215765E+11 | 443.98 | 0.576373E+11 | 0.365357E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 117273.48 | 19-SEP-04:02 | 75115.96 | 11-SEP-04:02 | 45739.29 | 22-SEP-05:03 | 26214.96 | 22-SEP-04:02 | 0.00 |
October | 0.849030E+11 | 0.192444E+11 | 436.61 | 0.546340E+11 | 0.302690E+11 | 0.00 | 1.00 | 01-OCT-10:23 | 0.00 | 01-OCT-00:10 | 119725.16 | 02-OCT-04:02 | 71567.57 | 10-OCT-04:02 | 51436.85 | 02-OCT-04:02 | 25986.20 | 02-OCT-04:02 | 0.00 |
November | 0.660336E+11 | 0.146277E+11 | 402.67 | 0.429257E+11 | 0.231078E+11 | 0.00 | 1.00 | 01-NOV-08:20 | 0.00 | 01-NOV-00:10 | 110067.04 | 30-NOV-06:03 | 61994.02 | 04-NOV-05:03 | 48765.22 | 30-NOV-06:03 | 23675.04 | 30-NOV-06:03 | 0.00 |
December | 0.463221E+11 | 0.102857E+11 | 407.04 | 0.317225E+11 | 0.145997E+11 | 0.00 | 1.00 | 01-DEC-09:10 | 0.00 | 01-DEC-00:10 | 87849.95 | 09-DEC-06:03 | 54533.82 | 09-DEC-06:03 | 33316.13 | 09-DEC-06:03 | 18845.51 | 09-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.882410E+12 | 0.200130E+12 | 5157.78 | 0.573154E+12 | 0.309256E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.424811E+11 | 0.949331E+10 | 374.72 | 0.302388E+11 | 0.121162E+11 | 0.00 | 1.00 | 0.00 | 62716.53 | 47542.34 | 26149.87 | 14001.42 | 0.00 | ||||||
Maximum of Months | 0.102380E+12 | 0.236365E+11 | 465.33 | 0.622323E+11 | 0.401481E+11 | 0.00 | 1.00 | 0.00 | 119725.16 | 75125.22 | 52106.00 | 26580.85 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.434892E+11 | 0.983662E+10 | 408.53 | 0.305617E+11 | 0.129275E+11 | 0.00 | 1.00 | 01-JAN-09:53 | 0.00 | 01-JAN-00:10 | 82509.79 | 02-JAN-14:00 | 58538.37 | 02-JAN-15:00 | 26473.98 | 02-JAN-14:00 | 19120.87 | 02-JAN-14:10 | 0.00 |
February | 0.463662E+11 | 0.103819E+11 | 371.41 | 0.336728E+11 | 0.126934E+11 | 0.00 | 1.00 | 02-FEB-09:50 | 0.00 | 01-FEB-00:10 | 68130.59 | 17-FEB-14:10 | 54008.66 | 22-FEB-16:00 | 24946.06 | 11-FEB-16:00 | 15226.15 | 17-FEB-14:10 | 0.00 |
March | 0.579371E+11 | 0.128871E+11 | 436.42 | 0.415203E+11 | 0.164168E+11 | 0.00 | 1.00 | 01-MAR-14:30 | 0.00 | 01-MAR-00:10 | 79662.90 | 27-MAR-15:00 | 60508.31 | 27-MAR-15:20 | 26310.86 | 14-MAR-09:40 | 18225.00 | 27-MAR-15:00 | 0.00 |
April | 0.680722E+11 | 0.153319E+11 | 423.03 | 0.489200E+11 | 0.191522E+11 | 0.00 | 1.00 | 01-APR-13:10 | 0.00 | 01-APR-00:10 | 97113.72 | 13-APR-05:03 | 66559.12 | 16-APR-16:42 | 38232.98 | 13-APR-05:03 | 20917.83 | 14-APR-15:00 | 0.00 |
May | 0.909602E+11 | 0.208234E+11 | 449.63 | 0.612871E+11 | 0.296730E+11 | 0.00 | 1.00 | 01-MAY-08:20 | 0.00 | 01-MAY-00:10 | 119247.89 | 30-MAY-04:02 | 78893.84 | 29-MAY-16:02 | 46756.20 | 27-MAY-05:03 | 27016.99 | 29-MAY-16:02 | 0.00 |
June | 0.102652E+12 | 0.234867E+11 | 453.13 | 0.649863E+11 | 0.376654E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 131515.52 | 08-JUN-04:02 | 83605.16 | 12-JUN-04:02 | 51159.84 | 19-JUN-04:02 | 30147.45 | 08-JUN-04:02 | 0.00 |
July | 0.107926E+12 | 0.252404E+11 | 459.55 | 0.687543E+11 | 0.391720E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 122259.22 | 31-JUL-04:02 | 82892.70 | 10-JUL-04:02 | 46159.57 | 03-JUL-04:02 | 26788.08 | 31-JUL-04:02 | 0.00 |
August | 0.107876E+12 | 0.249925E+11 | 465.80 | 0.676752E+11 | 0.402007E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 128356.37 | 01-AUG-04:02 | 83913.53 | 01-AUG-04:02 | 47520.48 | 18-AUG-04:02 | 29271.52 | 01-AUG-04:02 | 0.00 |
September | 0.990279E+11 | 0.227780E+11 | 444.07 | 0.624097E+11 | 0.366182E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 134095.91 | 19-SEP-04:02 | 86926.91 | 11-SEP-04:02 | 52647.45 | 22-SEP-04:02 | 29656.24 | 19-SEP-04:02 | 0.00 |
October | 0.877149E+11 | 0.199699E+11 | 433.38 | 0.573814E+11 | 0.303335E+11 | 0.00 | 1.00 | 01-OCT-10:23 | 0.00 | 01-OCT-00:10 | 135678.76 | 02-OCT-04:02 | 75844.06 | 30-OCT-04:02 | 60054.13 | 02-OCT-04:02 | 29564.78 | 02-OCT-04:02 | 0.00 |
November | 0.678795E+11 | 0.151386E+11 | 400.33 | 0.443593E+11 | 0.235202E+11 | 0.00 | 1.00 | 01-NOV-09:40 | 0.00 | 01-NOV-00:10 | 107827.43 | 30-NOV-06:03 | 60082.52 | 10-NOV-14:30 | 50049.49 | 30-NOV-06:03 | 23139.58 | 30-NOV-06:03 | 0.00 |
December | 0.477127E+11 | 0.107003E+11 | 406.94 | 0.324325E+11 | 0.152802E+11 | 0.00 | 1.00 | 01-DEC-11:20 | 0.00 | 01-DEC-00:10 | 76833.29 | 08-DEC-15:50 | 54659.79 | 08-DEC-15:30 | 28389.72 | 09-DEC-06:03 | 17297.60 | 08-DEC-15:40 | 0.00 |
Annual Sum or Average | 0.927614E+12 | 0.211567E+12 | 5152.20 | 0.613960E+12 | 0.313653E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.434892E+11 | 0.983662E+10 | 371.41 | 0.305617E+11 | 0.126934E+11 | 0.00 | 1.00 | 0.00 | 68130.59 | 54008.66 | 24946.06 | 15226.15 | 0.00 | ||||||
Maximum of Months | 0.107926E+12 | 0.252404E+11 | 465.80 | 0.687543E+11 | 0.402007E+11 | 0.00 | 1.00 | 0.00 | 135678.76 | 86926.91 | 60054.13 | 30147.45 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.04 | 0.00 | 331.04 | 358.89 | 691.44 | 0.00 | 0.00 | 0.00 |
February | 391.84 | 0.00 | 391.84 | 527.18 | 577.38 | 0.00 | 0.00 | 0.00 |
March | 467.29 | 0.00 | 467.29 | 618.69 | 487.45 | 0.00 | 0.00 | 0.00 |
April | 523.62 | 2.35 | 521.27 | 854.76 | 320.22 | 0.00 | 0.00 | 0.00 |
May | 597.95 | 26.75 | 571.20 | 1177.14 | 170.15 | 0.00 | 0.00 | 0.00 |
June | 638.74 | 45.99 | 592.75 | 1355.03 | 78.45 | 0.00 | 0.00 | 0.00 |
July | 646.38 | 31.67 | 614.71 | 1438.60 | 115.42 | 0.00 | 0.00 | 0.00 |
August | 572.06 | 5.26 | 566.80 | 1211.52 | 76.01 | 0.00 | 0.00 | 0.00 |
September | 507.48 | 0.04 | 507.44 | 1117.65 | 124.00 | 0.00 | 0.00 | 0.00 |
October | 425.15 | 0.00 | 425.15 | 826.27 | 193.80 | 0.00 | 0.00 | 0.00 |
November | 369.67 | 0.00 | 369.67 | 590.02 | 359.00 | 0.00 | 0.00 | 0.00 |
December | 327.44 | 0.00 | 327.44 | 401.97 | 583.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.68 | 9.39 | 474.30 | 874.82 | 313.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.44 | 0.00 | 327.44 | 358.89 | 76.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 646.38 | 45.99 | 614.71 | 1438.60 | 691.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 531.39 | 254.57 | 276.82 | 744.50 | 433.81 | 0.00 | 0.00 | 0.00 |
February | 613.58 | 284.03 | 329.55 | 925.58 | 362.04 | 0.00 | 0.00 | 0.00 |
March | 749.14 | 354.16 | 394.98 | 1123.29 | 301.43 | 0.00 | 0.00 | 0.00 |
April | 813.00 | 362.76 | 450.24 | 1360.91 | 212.45 | 0.00 | 0.00 | 0.00 |
May | 769.13 | 306.29 | 462.85 | 1411.30 | 108.44 | 0.00 | 0.00 | 0.00 |
June | 759.15 | 291.58 | 467.56 | 1466.32 | 50.87 | 0.00 | 0.00 | 0.00 |
July | 780.03 | 281.30 | 498.74 | 1559.63 | 77.26 | 0.00 | 0.00 | 0.00 |
August | 713.27 | 238.50 | 474.77 | 1386.41 | 49.00 | 0.00 | 0.00 | 0.00 |
September | 687.64 | 248.58 | 439.05 | 1355.52 | 82.44 | 0.00 | 0.00 | 0.00 |
October | 632.94 | 272.58 | 360.36 | 1157.46 | 126.80 | 0.00 | 0.00 | 0.00 |
November | 513.72 | 204.84 | 308.88 | 846.15 | 225.05 | 0.00 | 0.00 | 0.00 |
December | 414.97 | 146.51 | 268.47 | 598.27 | 370.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.94 | 270.29 | 394.65 | 1162.17 | 199.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.97 | 146.51 | 268.47 | 598.27 | 49.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.00 | 362.76 | 498.74 | 1559.63 | 433.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1555.86 | 1010.81 | 545.05 | 2391.07 | 685.80 | 0.00 | 0.00 | 0.00 |
February | 1407.50 | 814.41 | 593.09 | 2282.35 | 582.15 | 0.00 | 0.00 | 0.00 |
March | 1080.64 | 456.89 | 623.76 | 1768.35 | 487.46 | 0.00 | 0.00 | 0.00 |
April | 734.82 | 128.86 | 605.96 | 1323.84 | 333.71 | 0.00 | 0.00 | 0.00 |
May | 588.84 | 12.74 | 576.10 | 1163.48 | 165.80 | 0.00 | 0.00 | 0.00 |
June | 561.40 | 1.06 | 560.35 | 1197.63 | 79.25 | 0.00 | 0.00 | 0.00 |
July | 601.11 | 5.57 | 595.54 | 1345.82 | 114.85 | 0.00 | 0.00 | 0.00 |
August | 682.24 | 57.57 | 624.67 | 1452.55 | 76.95 | 0.00 | 0.00 | 0.00 |
September | 873.36 | 214.02 | 659.34 | 1846.48 | 130.89 | 0.00 | 0.00 | 0.00 |
October | 1201.05 | 563.49 | 637.55 | 2249.64 | 215.68 | 0.00 | 0.00 | 0.00 |
November | 1366.53 | 762.67 | 603.85 | 2304.91 | 372.67 | 0.00 | 0.00 | 0.00 |
December | 1499.41 | 945.74 | 553.67 | 2358.37 | 597.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1010.90 | 412.71 | 598.19 | 1804.66 | 319.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.40 | 1.06 | 545.05 | 1163.48 | 76.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1555.86 | 1010.81 | 659.34 | 2391.07 | 685.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 477.37 | 205.80 | 271.57 | 685.77 | 457.05 | 0.00 | 0.00 | 0.00 |
February | 596.94 | 270.15 | 326.79 | 941.97 | 393.17 | 0.00 | 0.00 | 0.00 |
March | 743.37 | 339.46 | 403.91 | 1163.73 | 336.30 | 0.00 | 0.00 | 0.00 |
April | 818.23 | 378.87 | 439.36 | 1394.94 | 232.57 | 0.00 | 0.00 | 0.00 |
May | 745.92 | 287.15 | 458.78 | 1391.34 | 124.52 | 0.00 | 0.00 | 0.00 |
June | 632.03 | 177.29 | 454.74 | 1255.22 | 57.25 | 0.00 | 0.00 | 0.00 |
July | 706.35 | 218.52 | 487.82 | 1440.70 | 82.96 | 0.00 | 0.00 | 0.00 |
August | 704.74 | 229.67 | 475.07 | 1375.82 | 57.17 | 0.00 | 0.00 | 0.00 |
September | 601.18 | 177.27 | 423.91 | 1211.34 | 86.03 | 0.00 | 0.00 | 0.00 |
October | 598.06 | 233.14 | 364.92 | 1110.67 | 140.39 | 0.00 | 0.00 | 0.00 |
November | 493.34 | 180.96 | 312.38 | 838.78 | 245.82 | 0.00 | 0.00 | 0.00 |
December | 494.22 | 220.96 | 273.26 | 752.81 | 389.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.60 | 243.21 | 391.39 | 1131.31 | 216.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 477.37 | 177.27 | 271.57 | 685.77 | 57.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.23 | 378.87 | 487.82 | 1440.70 | 457.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.34 | 0.00 | 110.34 | 113.89 | 262.66 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 173.39 | 213.92 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 209.81 | 173.49 | 0.00 | 0.00 | 0.00 |
April | 174.53 | 0.78 | 173.75 | 291.23 | 110.07 | 0.00 | 0.00 | 0.00 |
May | 199.31 | 8.92 | 190.39 | 399.35 | 57.05 | 0.00 | 0.00 | 0.00 |
June | 212.90 | 15.33 | 197.57 | 459.33 | 25.38 | 0.00 | 0.00 | 0.00 |
July | 215.45 | 10.56 | 204.89 | 485.63 | 38.66 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.92 | 405.20 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 169.15 | 0.01 | 169.14 | 374.61 | 45.21 | 0.00 | 0.00 | 0.00 |
October | 141.71 | 0.00 | 141.71 | 275.37 | 72.84 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 193.47 | 139.22 | 0.00 | 0.00 | 0.00 |
December | 109.14 | 0.00 | 109.14 | 127.74 | 225.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.22 | 3.13 | 158.09 | 292.99 | 115.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.14 | 0.00 | 109.14 | 113.89 | 25.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.45 | 15.33 | 204.89 | 485.63 | 262.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.35 | 0.00 | 110.35 | 113.90 | 262.67 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 173.39 | 213.93 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 209.82 | 173.50 | 0.00 | 0.00 | 0.00 |
April | 174.54 | 0.78 | 173.76 | 291.25 | 110.08 | 0.00 | 0.00 | 0.00 |
May | 199.32 | 8.92 | 190.40 | 399.37 | 57.05 | 0.00 | 0.00 | 0.00 |
June | 212.91 | 15.33 | 197.58 | 459.35 | 25.38 | 0.00 | 0.00 | 0.00 |
July | 215.46 | 10.56 | 204.90 | 485.65 | 38.66 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.93 | 405.22 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 169.16 | 0.01 | 169.15 | 374.63 | 45.21 | 0.00 | 0.00 | 0.00 |
October | 141.72 | 0.00 | 141.72 | 275.38 | 72.84 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 193.47 | 139.22 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 0.00 | 109.15 | 127.75 | 225.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 3.13 | 158.10 | 293.00 | 115.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.15 | 0.00 | 109.15 | 113.90 | 25.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.46 | 15.33 | 204.90 | 485.65 | 262.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.35 | 0.00 | 110.35 | 113.90 | 262.67 | 0.00 | 0.00 | 0.00 |
February | 130.61 | 0.00 | 130.61 | 173.39 | 213.93 | 0.00 | 0.00 | 0.00 |
March | 155.76 | 0.00 | 155.76 | 209.82 | 173.50 | 0.00 | 0.00 | 0.00 |
April | 174.54 | 0.78 | 173.76 | 291.25 | 110.08 | 0.00 | 0.00 | 0.00 |
May | 199.32 | 8.92 | 190.40 | 399.37 | 57.05 | 0.00 | 0.00 | 0.00 |
June | 212.91 | 15.33 | 197.58 | 459.35 | 25.38 | 0.00 | 0.00 | 0.00 |
July | 215.46 | 10.56 | 204.90 | 485.65 | 38.66 | 0.00 | 0.00 | 0.00 |
August | 190.68 | 1.75 | 188.93 | 405.22 | 28.07 | 0.00 | 0.00 | 0.00 |
September | 169.16 | 0.01 | 169.15 | 374.63 | 45.21 | 0.00 | 0.00 | 0.00 |
October | 141.72 | 0.00 | 141.72 | 275.38 | 72.84 | 0.00 | 0.00 | 0.00 |
November | 123.22 | 0.00 | 123.22 | 193.47 | 139.22 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 0.00 | 109.15 | 127.75 | 225.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.23 | 3.13 | 158.10 | 293.00 | 115.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.15 | 0.00 | 109.15 | 113.90 | 25.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.46 | 15.33 | 204.90 | 485.65 | 262.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 511.17 | 244.88 | 266.29 | 702.69 | 487.55 | 0.00 | 0.00 | 0.00 |
February | 590.24 | 273.22 | 317.02 | 886.34 | 399.27 | 0.00 | 0.00 | 0.00 |
March | 720.63 | 340.68 | 379.95 | 1089.91 | 323.17 | 0.00 | 0.00 | 0.00 |
April | 782.07 | 348.95 | 433.11 | 1325.21 | 224.51 | 0.00 | 0.00 | 0.00 |
May | 739.87 | 294.63 | 445.24 | 1374.03 | 113.39 | 0.00 | 0.00 | 0.00 |
June | 730.26 | 280.49 | 449.77 | 1424.07 | 52.23 | 0.00 | 0.00 | 0.00 |
July | 750.35 | 270.59 | 479.76 | 1511.76 | 81.51 | 0.00 | 0.00 | 0.00 |
August | 686.13 | 229.43 | 456.70 | 1335.54 | 58.26 | 0.00 | 0.00 | 0.00 |
September | 661.47 | 239.12 | 422.35 | 1306.84 | 92.21 | 0.00 | 0.00 | 0.00 |
October | 608.86 | 262.21 | 346.65 | 1115.02 | 147.48 | 0.00 | 0.00 | 0.00 |
November | 494.17 | 197.04 | 297.13 | 807.89 | 259.85 | 0.00 | 0.00 | 0.00 |
December | 399.18 | 140.93 | 258.25 | 562.39 | 421.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.64 | 260.01 | 379.63 | 1121.01 | 220.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 399.18 | 140.93 | 258.25 | 562.39 | 52.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 782.07 | 348.95 | 479.76 | 1511.76 | 487.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.21 | 9.68 | 10.53 | 27.78 | 19.28 | 0.00 | 0.00 | 0.00 |
February | 23.34 | 10.80 | 12.53 | 35.05 | 15.79 | 0.00 | 0.00 | 0.00 |
March | 28.49 | 13.47 | 15.02 | 43.09 | 12.78 | 0.00 | 0.00 | 0.00 |
April | 30.92 | 13.80 | 17.12 | 52.40 | 8.88 | 0.00 | 0.00 | 0.00 |
May | 29.25 | 11.65 | 17.60 | 54.33 | 4.48 | 0.00 | 0.00 | 0.00 |
June | 28.87 | 11.09 | 17.78 | 56.31 | 2.07 | 0.00 | 0.00 | 0.00 |
July | 29.67 | 10.70 | 18.97 | 59.77 | 3.22 | 0.00 | 0.00 | 0.00 |
August | 27.13 | 9.07 | 18.06 | 52.81 | 2.30 | 0.00 | 0.00 | 0.00 |
September | 26.15 | 9.45 | 16.70 | 51.67 | 3.65 | 0.00 | 0.00 | 0.00 |
October | 24.07 | 10.37 | 13.71 | 44.09 | 5.83 | 0.00 | 0.00 | 0.00 |
November | 19.54 | 7.79 | 11.75 | 31.94 | 10.27 | 0.00 | 0.00 | 0.00 |
December | 15.78 | 5.57 | 10.21 | 22.24 | 16.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.29 | 10.28 | 15.01 | 44.32 | 8.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.78 | 5.57 | 10.21 | 22.24 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.92 | 13.80 | 18.97 | 59.77 | 19.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.61 | 336.93 | 181.68 | 795.47 | 269.16 | 0.00 | 0.00 | 0.00 |
February | 469.16 | 271.47 | 197.69 | 762.73 | 223.67 | 0.00 | 0.00 | 0.00 |
March | 360.21 | 152.29 | 207.92 | 597.15 | 178.53 | 0.00 | 0.00 | 0.00 |
April | 244.94 | 42.95 | 201.98 | 448.76 | 117.39 | 0.00 | 0.00 | 0.00 |
May | 196.28 | 4.25 | 192.03 | 393.60 | 56.56 | 0.00 | 0.00 | 0.00 |
June | 187.13 | 0.35 | 186.78 | 404.53 | 25.72 | 0.00 | 0.00 | 0.00 |
July | 200.37 | 1.86 | 198.51 | 451.72 | 38.99 | 0.00 | 0.00 | 0.00 |
August | 227.41 | 19.19 | 208.22 | 482.23 | 30.04 | 0.00 | 0.00 | 0.00 |
September | 291.12 | 71.34 | 219.78 | 613.20 | 50.71 | 0.00 | 0.00 | 0.00 |
October | 400.34 | 187.83 | 212.52 | 747.69 | 88.58 | 0.00 | 0.00 | 0.00 |
November | 455.50 | 254.22 | 201.28 | 766.76 | 151.16 | 0.00 | 0.00 | 0.00 |
December | 499.80 | 315.24 | 184.55 | 785.85 | 236.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.96 | 137.57 | 199.39 | 603.34 | 121.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.13 | 0.35 | 181.68 | 393.60 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.61 | 336.93 | 219.78 | 795.47 | 269.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.61 | 336.93 | 181.68 | 795.47 | 269.16 | 0.00 | 0.00 | 0.00 |
February | 469.16 | 271.47 | 197.69 | 762.73 | 223.67 | 0.00 | 0.00 | 0.00 |
March | 360.21 | 152.29 | 207.92 | 597.15 | 178.53 | 0.00 | 0.00 | 0.00 |
April | 244.94 | 42.95 | 201.98 | 448.76 | 117.39 | 0.00 | 0.00 | 0.00 |
May | 196.28 | 4.25 | 192.03 | 393.60 | 56.56 | 0.00 | 0.00 | 0.00 |
June | 187.13 | 0.35 | 186.78 | 404.53 | 25.72 | 0.00 | 0.00 | 0.00 |
July | 200.37 | 1.86 | 198.51 | 451.72 | 38.99 | 0.00 | 0.00 | 0.00 |
August | 227.41 | 19.19 | 208.22 | 482.23 | 30.04 | 0.00 | 0.00 | 0.00 |
September | 291.12 | 71.34 | 219.78 | 613.20 | 50.71 | 0.00 | 0.00 | 0.00 |
October | 400.34 | 187.83 | 212.52 | 747.69 | 88.58 | 0.00 | 0.00 | 0.00 |
November | 455.50 | 254.22 | 201.28 | 766.76 | 151.16 | 0.00 | 0.00 | 0.00 |
December | 499.80 | 315.24 | 184.55 | 785.85 | 236.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.96 | 137.57 | 199.39 | 603.34 | 121.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.13 | 0.35 | 181.68 | 393.60 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.61 | 336.93 | 219.78 | 795.47 | 269.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.58 | 336.91 | 181.67 | 795.42 | 269.14 | 0.00 | 0.00 | 0.00 |
February | 469.13 | 271.45 | 197.68 | 762.68 | 223.66 | 0.00 | 0.00 | 0.00 |
March | 360.19 | 152.28 | 207.90 | 597.11 | 178.52 | 0.00 | 0.00 | 0.00 |
April | 244.92 | 42.95 | 201.97 | 448.73 | 117.38 | 0.00 | 0.00 | 0.00 |
May | 196.27 | 4.25 | 192.02 | 393.58 | 56.55 | 0.00 | 0.00 | 0.00 |
June | 187.12 | 0.35 | 186.77 | 404.51 | 25.71 | 0.00 | 0.00 | 0.00 |
July | 200.36 | 1.86 | 198.50 | 451.70 | 38.99 | 0.00 | 0.00 | 0.00 |
August | 227.40 | 19.19 | 208.21 | 482.20 | 30.04 | 0.00 | 0.00 | 0.00 |
September | 291.10 | 71.33 | 219.76 | 613.16 | 50.71 | 0.00 | 0.00 | 0.00 |
October | 400.32 | 187.82 | 212.50 | 747.64 | 88.58 | 0.00 | 0.00 | 0.00 |
November | 455.47 | 254.20 | 201.27 | 766.72 | 151.15 | 0.00 | 0.00 | 0.00 |
December | 499.76 | 315.22 | 184.54 | 785.80 | 236.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 336.94 | 137.56 | 199.38 | 603.30 | 121.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.12 | 0.35 | 181.67 | 393.58 | 25.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.58 | 336.91 | 219.76 | 795.42 | 269.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.21 | 197.97 | 261.24 | 646.30 | 515.19 | 0.00 | 0.00 | 0.00 |
February | 574.22 | 259.87 | 314.36 | 899.66 | 433.60 | 0.00 | 0.00 | 0.00 |
March | 715.08 | 326.54 | 388.54 | 1124.34 | 361.48 | 0.00 | 0.00 | 0.00 |
April | 787.10 | 364.45 | 422.65 | 1351.12 | 244.73 | 0.00 | 0.00 | 0.00 |
May | 717.54 | 276.22 | 441.32 | 1349.89 | 129.57 | 0.00 | 0.00 | 0.00 |
June | 607.98 | 170.54 | 437.44 | 1217.82 | 57.60 | 0.00 | 0.00 | 0.00 |
July | 679.47 | 210.21 | 469.27 | 1393.84 | 87.16 | 0.00 | 0.00 | 0.00 |
August | 677.93 | 220.93 | 456.99 | 1323.70 | 67.18 | 0.00 | 0.00 | 0.00 |
September | 578.31 | 170.52 | 407.78 | 1165.64 | 96.90 | 0.00 | 0.00 | 0.00 |
October | 575.31 | 224.27 | 351.04 | 1066.56 | 161.21 | 0.00 | 0.00 | 0.00 |
November | 474.57 | 174.07 | 300.50 | 799.05 | 283.81 | 0.00 | 0.00 | 0.00 |
December | 475.42 | 212.56 | 262.86 | 710.55 | 444.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.45 | 233.96 | 376.50 | 1088.41 | 239.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 459.21 | 170.52 | 261.24 | 646.30 | 57.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.10 | 364.45 | 469.27 | 1393.84 | 515.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.16 | 7.83 | 10.33 | 25.55 | 20.37 | 0.00 | 0.00 | 0.00 |
February | 22.70 | 10.27 | 12.43 | 35.57 | 17.14 | 0.00 | 0.00 | 0.00 |
March | 28.27 | 12.91 | 15.36 | 44.46 | 14.29 | 0.00 | 0.00 | 0.00 |
April | 31.12 | 14.41 | 16.71 | 53.42 | 9.68 | 0.00 | 0.00 | 0.00 |
May | 28.37 | 10.92 | 17.45 | 53.37 | 5.12 | 0.00 | 0.00 | 0.00 |
June | 24.04 | 6.74 | 17.30 | 48.15 | 2.28 | 0.00 | 0.00 | 0.00 |
July | 26.87 | 8.31 | 18.55 | 55.11 | 3.45 | 0.00 | 0.00 | 0.00 |
August | 26.80 | 8.74 | 18.07 | 52.34 | 2.66 | 0.00 | 0.00 | 0.00 |
September | 22.87 | 6.74 | 16.12 | 46.09 | 3.83 | 0.00 | 0.00 | 0.00 |
October | 22.75 | 8.87 | 13.88 | 42.17 | 6.37 | 0.00 | 0.00 | 0.00 |
November | 18.76 | 6.88 | 11.88 | 31.59 | 11.22 | 0.00 | 0.00 | 0.00 |
December | 18.80 | 8.40 | 10.39 | 28.09 | 17.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.14 | 9.25 | 14.89 | 43.03 | 9.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.16 | 6.74 | 10.33 | 25.55 | 2.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.12 | 14.41 | 18.55 | 55.11 | 20.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.04 | 0.00 | 331.04 | 344.01 | 761.71 | 0.00 | 0.00 | 0.00 |
February | 391.84 | 0.00 | 391.84 | 517.87 | 629.48 | 0.00 | 0.00 | 0.00 |
March | 467.29 | 0.00 | 467.29 | 616.19 | 525.35 | 0.00 | 0.00 | 0.00 |
April | 523.62 | 2.35 | 521.27 | 860.13 | 338.52 | 0.00 | 0.00 | 0.00 |
May | 597.95 | 26.75 | 571.20 | 1188.03 | 176.16 | 0.00 | 0.00 | 0.00 |
June | 638.74 | 45.99 | 592.75 | 1370.25 | 79.58 | 0.00 | 0.00 | 0.00 |
July | 646.38 | 31.67 | 614.71 | 1455.28 | 116.32 | 0.00 | 0.00 | 0.00 |
August | 572.06 | 5.26 | 566.80 | 1221.55 | 79.50 | 0.00 | 0.00 | 0.00 |
September | 507.48 | 0.04 | 507.44 | 1129.97 | 129.56 | 0.00 | 0.00 | 0.00 |
October | 425.15 | 0.00 | 425.15 | 830.55 | 208.38 | 0.00 | 0.00 | 0.00 |
November | 369.67 | 0.00 | 369.67 | 585.75 | 395.13 | 0.00 | 0.00 | 0.00 |
December | 327.44 | 0.00 | 327.44 | 389.58 | 643.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 483.68 | 9.39 | 474.30 | 877.49 | 339.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.44 | 0.00 | 327.44 | 344.01 | 79.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 646.38 | 45.99 | 614.71 | 1455.28 | 761.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 531.39 | 254.57 | 276.82 | 733.82 | 471.77 | 0.00 | 0.00 | 0.00 |
February | 613.58 | 284.03 | 329.55 | 919.73 | 390.88 | 0.00 | 0.00 | 0.00 |
March | 749.14 | 354.16 | 394.98 | 1123.98 | 321.35 | 0.00 | 0.00 | 0.00 |
April | 813.00 | 362.76 | 450.24 | 1367.62 | 223.45 | 0.00 | 0.00 | 0.00 |
May | 769.13 | 306.29 | 462.85 | 1421.01 | 112.64 | 0.00 | 0.00 | 0.00 |
June | 759.15 | 291.58 | 467.56 | 1477.79 | 51.68 | 0.00 | 0.00 | 0.00 |
July | 780.03 | 281.30 | 498.74 | 1571.99 | 78.05 | 0.00 | 0.00 | 0.00 |
August | 713.27 | 238.50 | 474.77 | 1394.46 | 51.34 | 0.00 | 0.00 | 0.00 |
September | 687.64 | 248.58 | 439.05 | 1364.87 | 85.71 | 0.00 | 0.00 | 0.00 |
October | 632.94 | 272.58 | 360.36 | 1162.19 | 135.41 | 0.00 | 0.00 | 0.00 |
November | 513.72 | 204.84 | 308.88 | 843.96 | 245.37 | 0.00 | 0.00 | 0.00 |
December | 414.97 | 146.51 | 268.47 | 590.47 | 404.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 664.94 | 270.29 | 394.65 | 1165.25 | 213.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.97 | 146.51 | 268.47 | 590.47 | 51.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.00 | 362.76 | 498.74 | 1571.99 | 471.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1555.86 | 1010.81 | 545.05 | 2378.25 | 744.00 | 0.00 | 0.00 | 0.00 |
February | 1407.50 | 814.41 | 593.09 | 2276.09 | 627.17 | 0.00 | 0.00 | 0.00 |
March | 1080.64 | 456.89 | 623.76 | 1769.44 | 521.01 | 0.00 | 0.00 | 0.00 |
April | 734.82 | 128.86 | 605.96 | 1331.63 | 352.03 | 0.00 | 0.00 | 0.00 |
May | 588.84 | 12.74 | 576.10 | 1175.01 | 172.93 | 0.00 | 0.00 | 0.00 |
June | 561.40 | 1.06 | 560.35 | 1212.48 | 80.72 | 0.00 | 0.00 | 0.00 |
July | 601.11 | 5.57 | 595.54 | 1362.46 | 115.92 | 0.00 | 0.00 | 0.00 |
August | 682.24 | 57.57 | 624.67 | 1463.43 | 80.57 | 0.00 | 0.00 | 0.00 |
September | 873.36 | 214.02 | 659.34 | 1860.10 | 136.44 | 0.00 | 0.00 | 0.00 |
October | 1201.05 | 563.49 | 637.55 | 2256.06 | 229.04 | 0.00 | 0.00 | 0.00 |
November | 1366.53 | 762.67 | 603.85 | 2302.44 | 403.00 | 0.00 | 0.00 | 0.00 |
December | 1499.41 | 945.74 | 553.67 | 2350.63 | 648.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1010.90 | 412.71 | 598.19 | 1809.16 | 341.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.40 | 1.06 | 545.05 | 1175.01 | 80.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1555.86 | 1010.81 | 659.34 | 2378.25 | 744.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 477.37 | 205.80 | 271.57 | 675.54 | 503.05 | 0.00 | 0.00 | 0.00 |
February | 596.94 | 270.15 | 326.79 | 935.47 | 427.54 | 0.00 | 0.00 | 0.00 |
March | 743.37 | 339.46 | 403.91 | 1162.45 | 361.31 | 0.00 | 0.00 | 0.00 |
April | 818.23 | 378.87 | 439.36 | 1398.07 | 245.81 | 0.00 | 0.00 | 0.00 |
May | 745.92 | 287.15 | 458.78 | 1398.07 | 129.90 | 0.00 | 0.00 | 0.00 |
June | 632.03 | 177.29 | 454.74 | 1263.58 | 58.70 | 0.00 | 0.00 | 0.00 |
July | 706.35 | 218.52 | 487.82 | 1450.44 | 84.61 | 0.00 | 0.00 | 0.00 |
August | 704.74 | 229.67 | 475.07 | 1381.60 | 60.11 | 0.00 | 0.00 | 0.00 |
September | 601.18 | 177.27 | 423.91 | 1217.92 | 90.50 | 0.00 | 0.00 | 0.00 |
October | 598.06 | 233.14 | 364.92 | 1112.73 | 150.78 | 0.00 | 0.00 | 0.00 |
November | 493.34 | 180.96 | 312.38 | 835.24 | 270.16 | 0.00 | 0.00 | 0.00 |
December | 494.22 | 220.96 | 273.26 | 744.46 | 427.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.60 | 243.21 | 391.39 | 1132.39 | 233.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 477.37 | 177.27 | 271.57 | 675.54 | 58.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.23 | 378.87 | 487.82 | 1450.44 | 503.05 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.961245E+09 | 0.185194E+10 |
February | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.127536E+10 | 0.139679E+10 |
March | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.165709E+10 | 0.130559E+10 |
April | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.221553E+10 | 0.830004E+09 |
May | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.315285E+10 | 0.455739E+09 |
June | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.351224E+10 | 0.203355E+09 |
July | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.385315E+10 | 0.309137E+09 |
August | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.324494E+10 | 0.203579E+09 |
September | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.289695E+10 | 0.321401E+09 |
October | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.221308E+10 | 0.519072E+09 |
November | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.152933E+10 | 0.930525E+09 |
December | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.107663E+10 | 0.156364E+10 |
Annual Sum or Average | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.275884E+11 | 0.989077E+10 |
Minimum of Months | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.961245E+09 | 0.203355E+09 |
Maximum of Months | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.385315E+10 | 0.185194E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.199407E+10 | 0.116191E+10 |
February | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.223916E+10 | 0.875858E+09 |
March | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.300863E+10 | 0.807356E+09 |
April | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.352749E+10 | 0.550663E+09 |
May | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.378002E+10 | 0.290445E+09 |
June | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.380069E+10 | 0.131851E+09 |
July | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.417732E+10 | 0.206927E+09 |
August | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.371337E+10 | 0.131237E+09 |
September | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.351351E+10 | 0.213694E+09 |
October | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.310014E+10 | 0.339615E+09 |
November | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.219322E+10 | 0.583318E+09 |
December | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.160241E+10 | 0.992821E+09 |
Annual Sum or Average | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.366500E+11 | 0.628569E+10 |
Minimum of Months | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.160241E+10 | 0.131237E+09 |
Maximum of Months | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.417732E+10 | 0.116191E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.640425E+10 | 0.183684E+10 |
February | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.552145E+10 | 0.140834E+10 |
March | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.473635E+10 | 0.130560E+10 |
April | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.343139E+10 | 0.864988E+09 |
May | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.311626E+10 | 0.444069E+09 |
June | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.310426E+10 | 0.205425E+09 |
July | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.360466E+10 | 0.307611E+09 |
August | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.389050E+10 | 0.206112E+09 |
September | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.478607E+10 | 0.339262E+09 |
October | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.602545E+10 | 0.577677E+09 |
November | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.597432E+10 | 0.965951E+09 |
December | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.631667E+10 | 0.160118E+10 |
Annual Sum or Average | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.569116E+11 | 0.100631E+11 |
Minimum of Months | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.310426E+10 | 0.205425E+09 |
Maximum of Months | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.640425E+10 | 0.183684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.183676E+10 | 0.122417E+10 |
February | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.227882E+10 | 0.951167E+09 |
March | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.311694E+10 | 0.900746E+09 |
April | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.361570E+10 | 0.602813E+09 |
May | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.372658E+10 | 0.333514E+09 |
June | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.325353E+10 | 0.148396E+09 |
July | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.385877E+10 | 0.222196E+09 |
August | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.368499E+10 | 0.153131E+09 |
September | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.313980E+10 | 0.223002E+09 |
October | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.297482E+10 | 0.376025E+09 |
November | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.217411E+10 | 0.637164E+09 |
December | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.201632E+10 | 0.104197E+10 |
Annual Sum or Average | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.356771E+11 | 0.681429E+10 |
Minimum of Months | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.183676E+10 | 0.148396E+09 |
Maximum of Months | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.385877E+10 | 0.122417E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295537E+09 | 0.00 | 0.295537E+09 | 0.305050E+09 | 0.703507E+09 |
February | 0.315962E+09 | 0.00 | 0.315962E+09 | 0.419457E+09 | 0.517513E+09 |
March | 0.417179E+09 | 0.00 | 0.417179E+09 | 0.561963E+09 | 0.464687E+09 |
April | 0.452389E+09 | 2032181.97 | 0.450357E+09 | 0.754876E+09 | 0.285303E+09 |
May | 0.533826E+09 | 23879252.18 | 0.509946E+09 | 0.106962E+10 | 0.152792E+09 |
June | 0.551845E+09 | 39734524.34 | 0.512111E+09 | 0.119059E+10 | 65780639.30 |
July | 0.577063E+09 | 28277226.60 | 0.548786E+09 | 0.130070E+10 | 0.103545E+09 |
August | 0.510709E+09 | 4697120.92 | 0.506012E+09 | 0.108528E+10 | 75169355.26 |
September | 0.438446E+09 | 34685.18 | 0.438412E+09 | 0.970986E+09 | 0.117191E+09 |
October | 0.379554E+09 | 0.00 | 0.379554E+09 | 0.737541E+09 | 0.195093E+09 |
November | 0.319379E+09 | 0.00 | 0.319379E+09 | 0.501461E+09 | 0.360853E+09 |
December | 0.292323E+09 | 0.00 | 0.292323E+09 | 0.342142E+09 | 0.603412E+09 |
Annual Sum or Average | 0.508421E+10 | 98654991.19 | 0.498556E+10 | 0.923967E+10 | 0.364485E+10 |
Minimum of Months | 0.292323E+09 | 0.00 | 0.292323E+09 | 0.305050E+09 | 65780639.30 |
Maximum of Months | 0.577063E+09 | 39734524.34 | 0.548786E+09 | 0.130070E+10 | 0.703507E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295549E+09 | 0.00 | 0.295549E+09 | 0.305062E+09 | 0.703546E+09 |
February | 0.315975E+09 | 0.00 | 0.315975E+09 | 0.419475E+09 | 0.517542E+09 |
March | 0.417196E+09 | 0.00 | 0.417196E+09 | 0.561987E+09 | 0.464712E+09 |
April | 0.452408E+09 | 2032236.59 | 0.450376E+09 | 0.754910E+09 | 0.285316E+09 |
May | 0.533847E+09 | 23879894.06 | 0.509967E+09 | 0.106967E+10 | 0.152798E+09 |
June | 0.551867E+09 | 39735592.41 | 0.512131E+09 | 0.119065E+10 | 65782344.26 |
July | 0.577086E+09 | 28277986.70 | 0.548808E+09 | 0.130076E+10 | 0.103548E+09 |
August | 0.510729E+09 | 4697247.18 | 0.506032E+09 | 0.108533E+10 | 75171125.30 |
September | 0.438464E+09 | 34686.11 | 0.438429E+09 | 0.971033E+09 | 0.117196E+09 |
October | 0.379570E+09 | 0.00 | 0.379570E+09 | 0.737576E+09 | 0.195100E+09 |
November | 0.319391E+09 | 0.00 | 0.319391E+09 | 0.501483E+09 | 0.360871E+09 |
December | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.342155E+09 | 0.603446E+09 |
Annual Sum or Average | 0.508442E+10 | 98657643.07 | 0.498576E+10 | 0.924009E+10 | 0.364503E+10 |
Minimum of Months | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.305062E+09 | 65782344.26 |
Maximum of Months | 0.577086E+09 | 39735592.41 | 0.548808E+09 | 0.130076E+10 | 0.703546E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295549E+09 | 0.00 | 0.295549E+09 | 0.305062E+09 | 0.703546E+09 |
February | 0.315975E+09 | 0.00 | 0.315975E+09 | 0.419475E+09 | 0.517542E+09 |
March | 0.417196E+09 | 0.00 | 0.417196E+09 | 0.561987E+09 | 0.464712E+09 |
April | 0.452408E+09 | 2032236.59 | 0.450376E+09 | 0.754910E+09 | 0.285316E+09 |
May | 0.533847E+09 | 23879894.06 | 0.509967E+09 | 0.106967E+10 | 0.152798E+09 |
June | 0.551867E+09 | 39735592.41 | 0.512131E+09 | 0.119065E+10 | 65782344.26 |
July | 0.577086E+09 | 28277986.70 | 0.548808E+09 | 0.130076E+10 | 0.103548E+09 |
August | 0.510729E+09 | 4697247.18 | 0.506032E+09 | 0.108533E+10 | 75171125.30 |
September | 0.438464E+09 | 34686.11 | 0.438429E+09 | 0.971033E+09 | 0.117196E+09 |
October | 0.379570E+09 | 0.00 | 0.379570E+09 | 0.737576E+09 | 0.195100E+09 |
November | 0.319391E+09 | 0.00 | 0.319391E+09 | 0.501483E+09 | 0.360871E+09 |
December | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.342155E+09 | 0.603446E+09 |
Annual Sum or Average | 0.508442E+10 | 98657643.07 | 0.498576E+10 | 0.924009E+10 | 0.364503E+10 |
Minimum of Months | 0.292334E+09 | 0.00 | 0.292334E+09 | 0.305062E+09 | 65782344.26 |
Maximum of Months | 0.577086E+09 | 39735592.41 | 0.548808E+09 | 0.130076E+10 | 0.703546E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136912E+10 | 0.655893E+09 | 0.713232E+09 | 0.188209E+10 | 0.130586E+10 |
February | 0.142790E+10 | 0.660974E+09 | 0.766923E+09 | 0.214424E+10 | 0.965923E+09 |
March | 0.193014E+10 | 0.912484E+09 | 0.101766E+10 | 0.291922E+10 | 0.865590E+09 |
April | 0.202712E+10 | 0.904489E+09 | 0.112263E+10 | 0.343495E+10 | 0.581937E+09 |
May | 0.198166E+10 | 0.789141E+09 | 0.119252E+10 | 0.368021E+10 | 0.303704E+09 |
June | 0.189284E+10 | 0.727023E+09 | 0.116582E+10 | 0.369118E+10 | 0.135379E+09 |
July | 0.200974E+10 | 0.724751E+09 | 0.128499E+10 | 0.404909E+10 | 0.218325E+09 |
August | 0.183773E+10 | 0.614496E+09 | 0.122324E+10 | 0.357711E+10 | 0.156056E+09 |
September | 0.171454E+10 | 0.619811E+09 | 0.109473E+10 | 0.338732E+10 | 0.238998E+09 |
October | 0.163077E+10 | 0.702307E+09 | 0.928464E+09 | 0.298646E+10 | 0.395003E+09 |
November | 0.128089E+10 | 0.510738E+09 | 0.770151E+09 | 0.209405E+10 | 0.673532E+09 |
December | 0.106917E+10 | 0.377467E+09 | 0.691702E+09 | 0.150632E+10 | 0.112889E+10 |
Annual Sum or Average | 0.201716E+11 | 0.819957E+10 | 0.119721E+11 | 0.353523E+11 | 0.696920E+10 |
Minimum of Months | 0.106917E+10 | 0.377467E+09 | 0.691702E+09 | 0.150632E+10 | 0.135379E+09 |
Maximum of Months | 0.202712E+10 | 0.912484E+09 | 0.128499E+10 | 0.404909E+10 | 0.130586E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54133955.09 | 25933416.62 | 28200538.47 | 74416313.30 | 51632496.37 |
February | 56457771.57 | 26134308.99 | 30323462.58 | 84781170.92 | 38191739.27 |
March | 76316054.86 | 36078813.09 | 40237241.78 | 0.115423E+09 | 34224649.32 |
April | 80150581.35 | 35762678.23 | 44387903.11 | 0.135815E+09 | 23009269.59 |
May | 78353173.20 | 31201924.47 | 47151248.73 | 0.145512E+09 | 12008185.86 |
June | 74841127.61 | 28745843.77 | 46095283.84 | 0.145946E+09 | 5352779.10 |
July | 79463329.13 | 28655995.03 | 50807334.10 | 0.160098E+09 | 8632376.77 |
August | 72662332.41 | 24296632.89 | 48365699.52 | 0.141436E+09 | 6170327.50 |
September | 67791450.18 | 24506775.11 | 43284675.07 | 0.133932E+09 | 9449774.53 |
October | 64479227.84 | 27768589.34 | 36710638.49 | 0.118082E+09 | 15618075.08 |
November | 50645196.43 | 20194127.79 | 30451068.64 | 82796790.19 | 26630838.59 |
December | 42273992.56 | 14924701.77 | 27349290.79 | 59558483.02 | 44635277.04 |
Annual Sum or Average | 0.797568E+09 | 0.324204E+09 | 0.473364E+09 | 0.139780E+10 | 0.275556E+09 |
Minimum of Months | 42273992.56 | 14924701.77 | 27349290.79 | 59558483.02 | 5352779.10 |
Maximum of Months | 80150581.35 | 36078813.09 | 50807334.10 | 0.160098E+09 | 51632496.37 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138905E+10 | 0.902429E+09 | 0.486617E+09 | 0.213059E+10 | 0.720915E+09 |
February | 0.113499E+10 | 0.656729E+09 | 0.478262E+09 | 0.184520E+10 | 0.541101E+09 |
March | 0.964783E+09 | 0.407900E+09 | 0.556883E+09 | 0.159941E+10 | 0.478187E+09 |
April | 0.634876E+09 | 0.111331E+09 | 0.523544E+09 | 0.116318E+10 | 0.304263E+09 |
May | 0.525710E+09 | 11373457.81 | 0.514336E+09 | 0.105422E+10 | 0.151483E+09 |
June | 0.485050E+09 | 915359.33 | 0.484135E+09 | 0.104855E+10 | 66656442.24 |
July | 0.536669E+09 | 4974389.47 | 0.531695E+09 | 0.120990E+10 | 0.104443E+09 |
August | 0.609101E+09 | 51398714.70 | 0.557702E+09 | 0.129162E+10 | 80465442.30 |
September | 0.754575E+09 | 0.184909E+09 | 0.569666E+09 | 0.158942E+10 | 0.131448E+09 |
October | 0.107228E+10 | 0.503078E+09 | 0.569201E+09 | 0.200261E+10 | 0.237255E+09 |
November | 0.118066E+10 | 0.658936E+09 | 0.521723E+09 | 0.198745E+10 | 0.391799E+09 |
December | 0.133865E+10 | 0.844344E+09 | 0.494308E+09 | 0.210482E+10 | 0.632576E+09 |
Annual Sum or Average | 0.106264E+11 | 0.433832E+10 | 0.628807E+10 | 0.190270E+11 | 0.384059E+10 |
Minimum of Months | 0.485050E+09 | 915359.33 | 0.478262E+09 | 0.104855E+10 | 66656442.24 |
Maximum of Months | 0.138905E+10 | 0.902429E+09 | 0.569666E+09 | 0.213059E+10 | 0.720915E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138905E+10 | 0.902429E+09 | 0.486617E+09 | 0.213059E+10 | 0.720915E+09 |
February | 0.113499E+10 | 0.656729E+09 | 0.478262E+09 | 0.184520E+10 | 0.541101E+09 |
March | 0.964783E+09 | 0.407900E+09 | 0.556883E+09 | 0.159941E+10 | 0.478187E+09 |
April | 0.634876E+09 | 0.111331E+09 | 0.523544E+09 | 0.116318E+10 | 0.304263E+09 |
May | 0.525710E+09 | 11373457.81 | 0.514336E+09 | 0.105422E+10 | 0.151483E+09 |
June | 0.485050E+09 | 915359.33 | 0.484135E+09 | 0.104855E+10 | 66656442.24 |
July | 0.536669E+09 | 4974389.47 | 0.531695E+09 | 0.120990E+10 | 0.104443E+09 |
August | 0.609101E+09 | 51398714.70 | 0.557702E+09 | 0.129162E+10 | 80465442.30 |
September | 0.754575E+09 | 0.184909E+09 | 0.569666E+09 | 0.158942E+10 | 0.131448E+09 |
October | 0.107228E+10 | 0.503078E+09 | 0.569201E+09 | 0.200261E+10 | 0.237255E+09 |
November | 0.118066E+10 | 0.658936E+09 | 0.521723E+09 | 0.198745E+10 | 0.391799E+09 |
December | 0.133865E+10 | 0.844344E+09 | 0.494308E+09 | 0.210482E+10 | 0.632576E+09 |
Annual Sum or Average | 0.106264E+11 | 0.433832E+10 | 0.628807E+10 | 0.190270E+11 | 0.384059E+10 |
Minimum of Months | 0.485050E+09 | 915359.33 | 0.478262E+09 | 0.104855E+10 | 66656442.24 |
Maximum of Months | 0.138905E+10 | 0.902429E+09 | 0.569666E+09 | 0.213059E+10 | 0.720915E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138896E+10 | 0.902372E+09 | 0.486586E+09 | 0.213045E+10 | 0.720869E+09 |
February | 0.113492E+10 | 0.656688E+09 | 0.478232E+09 | 0.184508E+10 | 0.541067E+09 |
March | 0.964722E+09 | 0.407874E+09 | 0.556848E+09 | 0.159931E+10 | 0.478157E+09 |
April | 0.634835E+09 | 0.111324E+09 | 0.523511E+09 | 0.116311E+10 | 0.304244E+09 |
May | 0.525677E+09 | 11372739.07 | 0.514304E+09 | 0.105416E+10 | 0.151474E+09 |
June | 0.485020E+09 | 915301.49 | 0.484104E+09 | 0.104848E+10 | 66652229.93 |
July | 0.536635E+09 | 4974075.11 | 0.531661E+09 | 0.120982E+10 | 0.104436E+09 |
August | 0.609062E+09 | 51395466.59 | 0.557667E+09 | 0.129154E+10 | 80460357.34 |
September | 0.754527E+09 | 0.184897E+09 | 0.569630E+09 | 0.158932E+10 | 0.131440E+09 |
October | 0.107221E+10 | 0.503046E+09 | 0.569165E+09 | 0.200248E+10 | 0.237240E+09 |
November | 0.118059E+10 | 0.658895E+09 | 0.521690E+09 | 0.198733E+10 | 0.391774E+09 |
December | 0.133857E+10 | 0.844290E+09 | 0.494277E+09 | 0.210468E+10 | 0.632536E+09 |
Annual Sum or Average | 0.106257E+11 | 0.433804E+10 | 0.628767E+10 | 0.190258E+11 | 0.384035E+10 |
Minimum of Months | 0.485020E+09 | 915301.49 | 0.478232E+09 | 0.104848E+10 | 66652229.93 |
Maximum of Months | 0.138896E+10 | 0.902372E+09 | 0.569630E+09 | 0.213045E+10 | 0.720869E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122994E+10 | 0.530241E+09 | 0.699694E+09 | 0.173105E+10 | 0.137989E+10 |
February | 0.138916E+10 | 0.628673E+09 | 0.760489E+09 | 0.217645E+10 | 0.104896E+10 |
March | 0.191528E+10 | 0.874615E+09 | 0.104067E+10 | 0.301143E+10 | 0.968180E+09 |
April | 0.204016E+10 | 0.944659E+09 | 0.109550E+10 | 0.350211E+10 | 0.634337E+09 |
May | 0.192187E+10 | 0.739827E+09 | 0.118204E+10 | 0.361554E+10 | 0.347033E+09 |
June | 0.157588E+10 | 0.442048E+09 | 0.113384E+10 | 0.315659E+10 | 0.149287E+09 |
July | 0.181990E+10 | 0.563018E+09 | 0.125688E+10 | 0.373326E+10 | 0.233460E+09 |
August | 0.181576E+10 | 0.591751E+09 | 0.122401E+10 | 0.354539E+10 | 0.179932E+09 |
September | 0.149897E+10 | 0.441998E+09 | 0.105698E+10 | 0.302135E+10 | 0.251174E+09 |
October | 0.154091E+10 | 0.600692E+09 | 0.940217E+09 | 0.285669E+10 | 0.431784E+09 |
November | 0.123009E+10 | 0.451201E+09 | 0.778885E+09 | 0.207113E+10 | 0.735643E+09 |
December | 0.127336E+10 | 0.569309E+09 | 0.704053E+09 | 0.190314E+10 | 0.119073E+10 |
Annual Sum or Average | 0.192513E+11 | 0.737803E+10 | 0.118733E+11 | 0.343241E+11 | 0.755041E+10 |
Minimum of Months | 0.122994E+10 | 0.441998E+09 | 0.699694E+09 | 0.173105E+10 | 0.149287E+09 |
Maximum of Months | 0.204016E+10 | 0.944659E+09 | 0.125688E+10 | 0.373326E+10 | 0.137989E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48630392.51 | 20965170.66 | 27665221.86 | 68444038.22 | 54559538.84 |
February | 54926052.04 | 24857081.76 | 30068970.27 | 86054665.56 | 41474885.41 |
March | 75728298.02 | 34581375.50 | 41146922.52 | 0.119069E+09 | 38280939.62 |
April | 80665992.58 | 37350830.63 | 43315161.95 | 0.138470E+09 | 25081092.02 |
May | 75988789.82 | 29252006.13 | 46736783.68 | 0.142955E+09 | 13721347.89 |
June | 62308871.72 | 17478117.54 | 44830754.17 | 0.124808E+09 | 5902669.79 |
July | 71956974.33 | 22261134.66 | 49695839.68 | 0.147609E+09 | 9230780.57 |
August | 71793305.40 | 23397217.82 | 48396087.58 | 0.140181E+09 | 7114336.83 |
September | 59267944.34 | 17476161.56 | 41791782.78 | 0.119461E+09 | 9931174.61 |
October | 60925982.45 | 23750735.43 | 37175247.02 | 0.112951E+09 | 17072317.85 |
November | 48636348.25 | 17840022.59 | 30796325.67 | 81890503.25 | 29086641.97 |
December | 50347468.56 | 22509892.26 | 27837576.31 | 75248392.53 | 47080500.92 |
Annual Sum or Average | 0.761176E+09 | 0.291720E+09 | 0.469457E+09 | 0.135714E+10 | 0.298536E+09 |
Minimum of Months | 48630392.51 | 17476161.56 | 27665221.86 | 68444038.22 | 5902669.79 |
Maximum of Months | 80665992.58 | 37350830.63 | 49695839.68 | 0.147609E+09 | 54559538.84 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.921403E+09 | 0.204018E+10 |
February | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.125284E+10 | 0.152283E+10 |
March | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.165042E+10 | 0.140710E+10 |
April | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.222945E+10 | 0.877452E+09 |
May | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.318201E+10 | 0.471840E+09 |
June | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.355169E+10 | 0.206264E+09 |
July | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.389783E+10 | 0.311543E+09 |
August | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.327179E+10 | 0.212923E+09 |
September | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.292889E+10 | 0.335812E+09 |
October | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.222455E+10 | 0.558128E+09 |
November | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.151826E+10 | 0.102419E+10 |
December | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.104346E+10 | 0.172253E+10 |
Annual Sum or Average | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.276726E+11 | 0.106908E+11 |
Minimum of Months | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.921403E+09 | 0.206264E+09 |
Maximum of Months | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.389783E+10 | 0.204018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.196547E+10 | 0.126359E+10 |
February | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.222501E+10 | 0.945617E+09 |
March | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.301047E+10 | 0.860717E+09 |
April | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.354487E+10 | 0.579170E+09 |
May | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.380603E+10 | 0.301683E+09 |
June | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.383042E+10 | 0.133967E+09 |
July | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.421041E+10 | 0.209038E+09 |
August | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.373493E+10 | 0.137501E+09 |
September | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.353775E+10 | 0.222152E+09 |
October | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.311280E+10 | 0.362692E+09 |
November | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.218753E+10 | 0.635994E+09 |
December | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.158150E+10 | 0.108370E+10 |
Annual Sum or Average | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.367472E+11 | 0.673582E+10 |
Minimum of Months | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.158150E+10 | 0.133967E+09 |
Maximum of Months | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.421041E+10 | 0.126359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.636990E+10 | 0.199273E+10 |
February | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.550633E+10 | 0.151725E+10 |
March | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.473928E+10 | 0.139547E+10 |
April | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.345158E+10 | 0.912462E+09 |
May | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.314715E+10 | 0.463171E+09 |
June | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.314275E+10 | 0.209227E+09 |
July | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.364922E+10 | 0.310486E+09 |
August | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.391964E+10 | 0.215792E+09 |
September | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.482139E+10 | 0.353640E+09 |
October | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.604263E+10 | 0.613467E+09 |
November | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.596793E+10 | 0.104458E+10 |
December | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.629593E+10 | 0.173730E+10 |
Annual Sum or Average | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.570537E+11 | 0.107656E+11 |
Minimum of Months | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.314275E+10 | 0.209227E+09 |
Maximum of Months | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.636990E+10 | 0.199273E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.180938E+10 | 0.134737E+10 |
February | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.226310E+10 | 0.103431E+10 |
March | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.311351E+10 | 0.967724E+09 |
April | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.362379E+10 | 0.637131E+09 |
May | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.374459E+10 | 0.347917E+09 |
June | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.327521E+10 | 0.152156E+09 |
July | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.388486E+10 | 0.226624E+09 |
August | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.370048E+10 | 0.161012E+09 |
September | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.315684E+10 | 0.234575E+09 |
October | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.298033E+10 | 0.403854E+09 |
November | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.216494E+10 | 0.700268E+09 |
December | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.199397E+10 | 0.114475E+10 |
Annual Sum or Average | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.357110E+11 | 0.735769E+10 |
Minimum of Months | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.180938E+10 | 0.152156E+09 |
Maximum of Months | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.388486E+10 | 0.134737E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.89 | 691.44 | 331.04 | 0.00 | 331.04 | 0.00 | 0.00 |
February | 527.18 | 577.38 | 391.84 | 0.00 | 391.84 | 0.00 | 0.00 |
March | 618.69 | 487.45 | 467.29 | 0.00 | 467.29 | 0.00 | 0.00 |
April | 854.76 | 320.22 | 523.62 | 2.35 | 521.27 | 0.00 | 0.00 |
May | 1177.14 | 170.15 | 597.95 | 26.75 | 571.20 | 0.00 | 0.00 |
June | 1355.03 | 78.45 | 638.74 | 45.99 | 592.75 | 0.00 | 0.00 |
July | 1438.60 | 115.42 | 646.38 | 31.67 | 614.71 | 0.00 | 0.00 |
August | 1211.52 | 76.01 | 572.06 | 5.26 | 566.80 | 0.00 | 0.00 |
September | 1117.65 | 124.00 | 507.48 | 0.04 | 507.44 | 0.00 | 0.00 |
October | 826.27 | 193.80 | 425.15 | 0.00 | 425.15 | 0.00 | 0.00 |
November | 590.02 | 359.00 | 369.67 | 0.00 | 369.67 | 0.00 | 0.00 |
December | 401.97 | 583.80 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Annual Sum or Average | 874.82 | 313.63 | 483.68 | 9.39 | 474.30 | 0.00 | 0.00 |
Minimum of Months | 358.89 | 76.01 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Maximum of Months | 1438.60 | 691.44 | 646.38 | 45.99 | 614.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 744.50 | 433.81 | 531.39 | 254.57 | 276.82 | 0.00 | 0.00 |
February | 925.58 | 362.04 | 613.58 | 284.03 | 329.55 | 0.00 | 0.00 |
March | 1123.29 | 301.43 | 749.14 | 354.16 | 394.98 | 0.00 | 0.00 |
April | 1360.91 | 212.45 | 813.00 | 362.76 | 450.24 | 0.00 | 0.00 |
May | 1411.30 | 108.44 | 769.13 | 306.29 | 462.85 | 0.00 | 0.00 |
June | 1466.32 | 50.87 | 759.15 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1559.63 | 77.26 | 780.03 | 281.30 | 498.74 | 0.00 | 0.00 |
August | 1386.41 | 49.00 | 713.27 | 238.50 | 474.77 | 0.00 | 0.00 |
September | 1355.52 | 82.44 | 687.64 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1157.46 | 126.80 | 632.94 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 846.15 | 225.05 | 513.72 | 204.84 | 308.88 | 0.00 | 0.00 |
December | 598.27 | 370.68 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Annual Sum or Average | 1162.17 | 199.32 | 664.94 | 270.29 | 394.65 | 0.00 | 0.00 |
Minimum of Months | 598.27 | 49.00 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Maximum of Months | 1559.63 | 433.81 | 813.00 | 362.76 | 498.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2391.07 | 685.80 | 1555.86 | 1010.81 | 545.05 | 0.00 | 0.00 |
February | 2282.35 | 582.15 | 1407.50 | 814.41 | 593.09 | 0.00 | 0.00 |
March | 1768.35 | 487.46 | 1080.64 | 456.89 | 623.76 | 0.00 | 0.00 |
April | 1323.84 | 333.71 | 734.82 | 128.86 | 605.96 | 0.00 | 0.00 |
May | 1163.48 | 165.80 | 588.84 | 12.74 | 576.10 | 0.00 | 0.00 |
June | 1197.63 | 79.25 | 561.40 | 1.06 | 560.35 | 0.00 | 0.00 |
July | 1345.82 | 114.85 | 601.11 | 5.57 | 595.54 | 0.00 | 0.00 |
August | 1452.55 | 76.95 | 682.24 | 57.57 | 624.67 | 0.00 | 0.00 |
September | 1846.48 | 130.89 | 873.36 | 214.02 | 659.34 | 0.00 | 0.00 |
October | 2249.64 | 215.68 | 1201.05 | 563.49 | 637.55 | 0.00 | 0.00 |
November | 2304.91 | 372.67 | 1366.53 | 762.67 | 603.85 | 0.00 | 0.00 |
December | 2358.37 | 597.81 | 1499.41 | 945.74 | 553.67 | 0.00 | 0.00 |
Annual Sum or Average | 1804.66 | 319.10 | 1010.90 | 412.71 | 598.19 | 0.00 | 0.00 |
Minimum of Months | 1163.48 | 76.95 | 561.40 | 1.06 | 545.05 | 0.00 | 0.00 |
Maximum of Months | 2391.07 | 685.80 | 1555.86 | 1010.81 | 659.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 685.77 | 457.05 | 477.37 | 205.80 | 271.57 | 0.00 | 0.00 |
February | 941.97 | 393.17 | 596.94 | 270.15 | 326.79 | 0.00 | 0.00 |
March | 1163.73 | 336.30 | 743.37 | 339.46 | 403.91 | 0.00 | 0.00 |
April | 1394.94 | 232.57 | 818.23 | 378.87 | 439.36 | 0.00 | 0.00 |
May | 1391.34 | 124.52 | 745.92 | 287.15 | 458.78 | 0.00 | 0.00 |
June | 1255.22 | 57.25 | 632.03 | 177.29 | 454.74 | 0.00 | 0.00 |
July | 1440.70 | 82.96 | 706.35 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1375.82 | 57.17 | 704.74 | 229.67 | 475.07 | 0.00 | 0.00 |
September | 1211.34 | 86.03 | 601.18 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1110.67 | 140.39 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 838.78 | 245.82 | 493.34 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 752.81 | 389.03 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1131.31 | 216.08 | 634.60 | 243.21 | 391.39 | 0.00 | 0.00 |
Minimum of Months | 685.77 | 57.17 | 477.37 | 177.27 | 271.57 | 0.00 | 0.00 |
Maximum of Months | 1440.70 | 457.05 | 818.23 | 378.87 | 487.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 341.69 | 788.01 | 331.03 | 0.00 | 331.03 | 0.00 | 0.00 |
February | 520.17 | 641.78 | 391.83 | 0.00 | 391.83 | 0.00 | 0.00 |
March | 629.46 | 520.50 | 467.28 | 0.00 | 467.28 | 0.00 | 0.00 |
April | 873.73 | 330.22 | 523.61 | 2.35 | 521.26 | 0.00 | 0.00 |
May | 1198.08 | 171.14 | 597.94 | 26.75 | 571.19 | 0.00 | 0.00 |
June | 1378.04 | 76.14 | 638.73 | 45.99 | 592.74 | 0.00 | 0.00 |
July | 1456.93 | 115.98 | 646.37 | 31.67 | 614.70 | 0.00 | 0.00 |
August | 1215.63 | 84.20 | 572.05 | 5.26 | 566.78 | 0.00 | 0.00 |
September | 1123.86 | 135.64 | 507.47 | 0.04 | 507.43 | 0.00 | 0.00 |
October | 826.12 | 218.52 | 425.14 | 0.00 | 425.14 | 0.00 | 0.00 |
November | 580.41 | 417.67 | 369.66 | 0.00 | 369.66 | 0.00 | 0.00 |
December | 383.23 | 675.89 | 327.43 | 0.00 | 327.43 | 0.00 | 0.00 |
Annual Sum or Average | 878.99 | 346.74 | 483.67 | 9.39 | 474.29 | 0.00 | 0.00 |
Minimum of Months | 341.69 | 76.14 | 327.43 | 0.00 | 327.43 | 0.00 | 0.00 |
Maximum of Months | 1456.93 | 788.01 | 646.37 | 45.99 | 614.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.48 | 506.83 | 531.38 | 254.56 | 276.82 | 0.00 | 0.00 |
February | 921.39 | 415.06 | 613.57 | 284.02 | 329.55 | 0.00 | 0.00 |
March | 1133.01 | 335.95 | 749.13 | 354.15 | 394.97 | 0.00 | 0.00 |
April | 1377.61 | 233.39 | 812.99 | 362.75 | 450.24 | 0.00 | 0.00 |
May | 1428.36 | 117.87 | 769.12 | 306.28 | 462.84 | 0.00 | 0.00 |
June | 1480.37 | 54.29 | 759.14 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1571.53 | 84.74 | 780.02 | 281.29 | 498.73 | 0.00 | 0.00 |
August | 1388.35 | 60.57 | 713.26 | 238.50 | 474.76 | 0.00 | 0.00 |
September | 1358.51 | 95.85 | 687.63 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1159.10 | 153.31 | 632.93 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 839.83 | 270.12 | 513.71 | 204.83 | 308.87 | 0.00 | 0.00 |
December | 584.63 | 438.14 | 414.97 | 146.50 | 268.46 | 0.00 | 0.00 |
Annual Sum or Average | 1165.34 | 229.73 | 664.93 | 270.29 | 394.64 | 0.00 | 0.00 |
Minimum of Months | 584.63 | 54.29 | 414.97 | 146.50 | 268.46 | 0.00 | 0.00 |
Maximum of Months | 1571.53 | 506.83 | 812.99 | 362.75 | 498.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2386.36 | 807.46 | 1555.80 | 1010.76 | 545.03 | 0.00 | 0.00 |
February | 2288.14 | 670.99 | 1407.45 | 814.38 | 593.07 | 0.00 | 0.00 |
March | 1791.41 | 535.59 | 1080.60 | 456.87 | 623.74 | 0.00 | 0.00 |
April | 1346.24 | 352.15 | 734.79 | 128.85 | 605.94 | 0.00 | 0.00 |
May | 1180.78 | 169.67 | 588.82 | 12.74 | 576.08 | 0.00 | 0.00 |
June | 1213.57 | 77.15 | 561.39 | 1.06 | 560.33 | 0.00 | 0.00 |
July | 1355.14 | 116.98 | 601.10 | 5.57 | 595.52 | 0.00 | 0.00 |
August | 1446.67 | 90.13 | 682.22 | 57.57 | 624.65 | 0.00 | 0.00 |
September | 1839.56 | 152.14 | 873.33 | 214.01 | 659.32 | 0.00 | 0.00 |
October | 2243.02 | 265.74 | 1201.00 | 563.47 | 637.53 | 0.00 | 0.00 |
November | 2300.25 | 453.46 | 1366.48 | 762.64 | 603.83 | 0.00 | 0.00 |
December | 2357.50 | 708.52 | 1499.35 | 945.71 | 553.65 | 0.00 | 0.00 |
Annual Sum or Average | 1809.98 | 365.35 | 1010.86 | 412.69 | 598.17 | 0.00 | 0.00 |
Minimum of Months | 1180.78 | 77.15 | 561.39 | 1.06 | 545.03 | 0.00 | 0.00 |
Maximum of Months | 2386.36 | 807.46 | 1555.80 | 1010.76 | 659.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 671.85 | 535.56 | 477.36 | 205.80 | 271.56 | 0.00 | 0.00 |
February | 935.23 | 450.74 | 596.93 | 270.14 | 326.78 | 0.00 | 0.00 |
March | 1168.80 | 375.77 | 743.36 | 339.46 | 403.90 | 0.00 | 0.00 |
April | 1404.55 | 254.41 | 818.22 | 378.86 | 439.36 | 0.00 | 0.00 |
May | 1403.26 | 134.69 | 745.91 | 287.14 | 458.77 | 0.00 | 0.00 |
June | 1265.97 | 59.87 | 632.02 | 177.29 | 454.73 | 0.00 | 0.00 |
July | 1448.95 | 90.61 | 706.34 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1376.03 | 69.84 | 704.73 | 229.67 | 475.06 | 0.00 | 0.00 |
September | 1211.73 | 100.74 | 601.17 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1108.74 | 167.58 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 830.64 | 295.03 | 493.33 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 738.65 | 462.15 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1131.45 | 248.89 | 634.59 | 243.21 | 391.38 | 0.00 | 0.00 |
Minimum of Months | 671.85 | 59.87 | 477.36 | 177.27 | 271.56 | 0.00 | 0.00 |
Maximum of Months | 1448.95 | 535.56 | 818.22 | 378.86 | 487.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 344.01 | 761.71 | 331.04 | 0.00 | 331.04 | 0.00 | 0.00 |
February | 517.87 | 629.48 | 391.84 | 0.00 | 391.84 | 0.00 | 0.00 |
March | 616.19 | 525.35 | 467.29 | 0.00 | 467.29 | 0.00 | 0.00 |
April | 860.13 | 338.52 | 523.62 | 2.35 | 521.27 | 0.00 | 0.00 |
May | 1188.03 | 176.16 | 597.95 | 26.75 | 571.20 | 0.00 | 0.00 |
June | 1370.25 | 79.58 | 638.74 | 45.99 | 592.75 | 0.00 | 0.00 |
July | 1455.28 | 116.32 | 646.38 | 31.67 | 614.71 | 0.00 | 0.00 |
August | 1221.55 | 79.50 | 572.06 | 5.26 | 566.80 | 0.00 | 0.00 |
September | 1129.97 | 129.56 | 507.48 | 0.04 | 507.44 | 0.00 | 0.00 |
October | 830.55 | 208.38 | 425.15 | 0.00 | 425.15 | 0.00 | 0.00 |
November | 585.75 | 395.13 | 369.67 | 0.00 | 369.67 | 0.00 | 0.00 |
December | 389.58 | 643.12 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Annual Sum or Average | 877.49 | 339.00 | 483.68 | 9.39 | 474.30 | 0.00 | 0.00 |
Minimum of Months | 344.01 | 79.50 | 327.44 | 0.00 | 327.44 | 0.00 | 0.00 |
Maximum of Months | 1455.28 | 761.71 | 646.38 | 45.99 | 614.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 733.82 | 471.77 | 531.39 | 254.57 | 276.82 | 0.00 | 0.00 |
February | 919.73 | 390.88 | 613.58 | 284.03 | 329.55 | 0.00 | 0.00 |
March | 1123.98 | 321.35 | 749.14 | 354.16 | 394.98 | 0.00 | 0.00 |
April | 1367.62 | 223.45 | 813.00 | 362.76 | 450.24 | 0.00 | 0.00 |
May | 1421.01 | 112.64 | 769.13 | 306.29 | 462.85 | 0.00 | 0.00 |
June | 1477.79 | 51.68 | 759.15 | 291.58 | 467.56 | 0.00 | 0.00 |
July | 1571.99 | 78.05 | 780.03 | 281.30 | 498.74 | 0.00 | 0.00 |
August | 1394.46 | 51.34 | 713.27 | 238.50 | 474.77 | 0.00 | 0.00 |
September | 1364.87 | 85.71 | 687.64 | 248.58 | 439.05 | 0.00 | 0.00 |
October | 1162.19 | 135.41 | 632.94 | 272.58 | 360.36 | 0.00 | 0.00 |
November | 843.96 | 245.37 | 513.72 | 204.84 | 308.88 | 0.00 | 0.00 |
December | 590.47 | 404.61 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Annual Sum or Average | 1165.25 | 213.59 | 664.94 | 270.29 | 394.65 | 0.00 | 0.00 |
Minimum of Months | 590.47 | 51.34 | 414.97 | 146.51 | 268.47 | 0.00 | 0.00 |
Maximum of Months | 1571.99 | 471.77 | 813.00 | 362.76 | 498.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2378.25 | 744.00 | 1555.86 | 1010.81 | 545.05 | 0.00 | 0.00 |
February | 2276.09 | 627.17 | 1407.50 | 814.41 | 593.09 | 0.00 | 0.00 |
March | 1769.44 | 521.01 | 1080.64 | 456.89 | 623.76 | 0.00 | 0.00 |
April | 1331.63 | 352.03 | 734.82 | 128.86 | 605.96 | 0.00 | 0.00 |
May | 1175.01 | 172.93 | 588.84 | 12.74 | 576.10 | 0.00 | 0.00 |
June | 1212.48 | 80.72 | 561.40 | 1.06 | 560.35 | 0.00 | 0.00 |
July | 1362.46 | 115.92 | 601.11 | 5.57 | 595.54 | 0.00 | 0.00 |
August | 1463.43 | 80.57 | 682.24 | 57.57 | 624.67 | 0.00 | 0.00 |
September | 1860.10 | 136.44 | 873.36 | 214.02 | 659.34 | 0.00 | 0.00 |
October | 2256.06 | 229.04 | 1201.05 | 563.49 | 637.55 | 0.00 | 0.00 |
November | 2302.44 | 403.00 | 1366.53 | 762.67 | 603.85 | 0.00 | 0.00 |
December | 2350.63 | 648.64 | 1499.41 | 945.74 | 553.67 | 0.00 | 0.00 |
Annual Sum or Average | 1809.16 | 341.37 | 1010.90 | 412.71 | 598.19 | 0.00 | 0.00 |
Minimum of Months | 1175.01 | 80.57 | 561.40 | 1.06 | 545.05 | 0.00 | 0.00 |
Maximum of Months | 2378.25 | 744.00 | 1555.86 | 1010.81 | 659.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 675.54 | 503.05 | 477.37 | 205.80 | 271.57 | 0.00 | 0.00 |
February | 935.47 | 427.54 | 596.94 | 270.15 | 326.79 | 0.00 | 0.00 |
March | 1162.45 | 361.31 | 743.37 | 339.46 | 403.91 | 0.00 | 0.00 |
April | 1398.07 | 245.81 | 818.23 | 378.87 | 439.36 | 0.00 | 0.00 |
May | 1398.07 | 129.90 | 745.92 | 287.15 | 458.78 | 0.00 | 0.00 |
June | 1263.58 | 58.70 | 632.03 | 177.29 | 454.74 | 0.00 | 0.00 |
July | 1450.44 | 84.61 | 706.35 | 218.52 | 487.82 | 0.00 | 0.00 |
August | 1381.60 | 60.11 | 704.74 | 229.67 | 475.07 | 0.00 | 0.00 |
September | 1217.92 | 90.50 | 601.18 | 177.27 | 423.91 | 0.00 | 0.00 |
October | 1112.73 | 150.78 | 598.06 | 233.14 | 364.92 | 0.00 | 0.00 |
November | 835.24 | 270.16 | 493.34 | 180.96 | 312.38 | 0.00 | 0.00 |
December | 744.46 | 427.40 | 494.22 | 220.96 | 273.26 | 0.00 | 0.00 |
Annual Sum or Average | 1132.39 | 233.31 | 634.60 | 243.21 | 391.39 | 0.00 | 0.00 |
Minimum of Months | 675.54 | 58.70 | 477.37 | 177.27 | 271.57 | 0.00 | 0.00 |
Maximum of Months | 1450.44 | 503.05 | 818.23 | 378.87 | 487.82 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.961245E+09 | 0.185194E+10 | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.00 | 0.00 |
February | 0.127536E+10 | 0.139679E+10 | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.00 | 0.00 |
March | 0.165709E+10 | 0.130559E+10 | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.00 | 0.00 |
April | 0.221553E+10 | 0.830004E+09 | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.00 | 0.00 |
May | 0.315285E+10 | 0.455739E+09 | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.00 | 0.00 |
June | 0.351224E+10 | 0.203355E+09 | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.00 | 0.00 |
July | 0.385315E+10 | 0.309137E+09 | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.00 | 0.00 |
August | 0.324494E+10 | 0.203579E+09 | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.00 | 0.00 |
September | 0.289695E+10 | 0.321401E+09 | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.00 | 0.00 |
October | 0.221308E+10 | 0.519072E+09 | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.00 | 0.00 |
November | 0.152933E+10 | 0.930525E+09 | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.00 | 0.00 |
December | 0.107663E+10 | 0.156364E+10 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.275884E+11 | 0.989077E+10 | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.961245E+09 | 0.203355E+09 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385315E+10 | 0.185194E+10 | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199407E+10 | 0.116191E+10 | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.00 | 0.00 |
February | 0.223916E+10 | 0.875858E+09 | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.00 | 0.00 |
March | 0.300863E+10 | 0.807356E+09 | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.00 | 0.00 |
April | 0.352749E+10 | 0.550663E+09 | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.00 | 0.00 |
May | 0.378002E+10 | 0.290445E+09 | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.00 | 0.00 |
June | 0.380069E+10 | 0.131851E+09 | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.00 | 0.00 |
July | 0.417732E+10 | 0.206927E+09 | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.00 | 0.00 |
August | 0.371337E+10 | 0.131237E+09 | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.00 | 0.00 |
September | 0.351351E+10 | 0.213694E+09 | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.00 | 0.00 |
October | 0.310014E+10 | 0.339615E+09 | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.00 | 0.00 |
November | 0.219322E+10 | 0.583318E+09 | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.00 | 0.00 |
December | 0.160241E+10 | 0.992821E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366500E+11 | 0.628569E+10 | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160241E+10 | 0.131237E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417732E+10 | 0.116191E+10 | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640425E+10 | 0.183684E+10 | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.00 | 0.00 |
February | 0.552145E+10 | 0.140834E+10 | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.00 | 0.00 |
March | 0.473635E+10 | 0.130560E+10 | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.00 | 0.00 |
April | 0.343139E+10 | 0.864988E+09 | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.00 | 0.00 |
May | 0.311626E+10 | 0.444069E+09 | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.00 | 0.00 |
June | 0.310426E+10 | 0.205425E+09 | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.00 | 0.00 |
July | 0.360466E+10 | 0.307611E+09 | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.00 | 0.00 |
August | 0.389050E+10 | 0.206112E+09 | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.00 | 0.00 |
September | 0.478607E+10 | 0.339262E+09 | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.00 | 0.00 |
October | 0.602545E+10 | 0.577677E+09 | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.00 | 0.00 |
November | 0.597432E+10 | 0.965951E+09 | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.00 | 0.00 |
December | 0.631667E+10 | 0.160118E+10 | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.569116E+11 | 0.100631E+11 | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310426E+10 | 0.205425E+09 | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.00 | 0.00 |
Maximum of Months | 0.640425E+10 | 0.183684E+10 | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.183676E+10 | 0.122417E+10 | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.00 | 0.00 |
February | 0.227882E+10 | 0.951167E+09 | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.00 | 0.00 |
March | 0.311694E+10 | 0.900746E+09 | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.00 | 0.00 |
April | 0.361570E+10 | 0.602813E+09 | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.00 | 0.00 |
May | 0.372658E+10 | 0.333514E+09 | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.00 | 0.00 |
June | 0.325353E+10 | 0.148396E+09 | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.00 | 0.00 |
July | 0.385877E+10 | 0.222196E+09 | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.00 | 0.00 |
August | 0.368499E+10 | 0.153131E+09 | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.00 | 0.00 |
September | 0.313980E+10 | 0.223002E+09 | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.00 | 0.00 |
October | 0.297482E+10 | 0.376025E+09 | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.00 | 0.00 |
November | 0.217411E+10 | 0.637164E+09 | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.00 | 0.00 |
December | 0.201632E+10 | 0.104197E+10 | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.356771E+11 | 0.681429E+10 | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183676E+10 | 0.148396E+09 | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.385877E+10 | 0.122417E+10 | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915174E+09 | 0.211060E+10 | 0.886634E+09 | 0.00 | 0.886634E+09 | 0.00 | 0.00 |
February | 0.125841E+10 | 0.155260E+10 | 0.947911E+09 | 0.00 | 0.947911E+09 | 0.00 | 0.00 |
March | 0.168594E+10 | 0.139411E+10 | 0.125157E+10 | 0.00 | 0.125157E+10 | 0.00 | 0.00 |
April | 0.226470E+10 | 0.855935E+09 | 0.135720E+10 | 6096655.15 | 0.135111E+10 | 0.00 | 0.00 |
May | 0.320895E+10 | 0.458387E+09 | 0.160152E+10 | 71639040.31 | 0.152988E+10 | 0.00 | 0.00 |
June | 0.357189E+10 | 0.197345E+09 | 0.165558E+10 | 0.119206E+09 | 0.153637E+10 | 0.00 | 0.00 |
July | 0.390223E+10 | 0.310640E+09 | 0.173124E+10 | 84833200.01 | 0.164640E+10 | 0.00 | 0.00 |
August | 0.325593E+10 | 0.225512E+09 | 0.153217E+10 | 14091615.29 | 0.151808E+10 | 0.00 | 0.00 |
September | 0.291305E+10 | 0.351583E+09 | 0.131537E+10 | 104057.40 | 0.131527E+10 | 0.00 | 0.00 |
October | 0.221269E+10 | 0.585293E+09 | 0.113869E+10 | 0.00 | 0.113869E+10 | 0.00 | 0.00 |
November | 0.150443E+10 | 0.108259E+10 | 0.958161E+09 | 0.00 | 0.958161E+09 | 0.00 | 0.00 |
December | 0.102645E+10 | 0.181030E+10 | 0.876992E+09 | 0.00 | 0.876992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.277198E+11 | 0.109349E+11 | 0.152530E+11 | 0.295970E+09 | 0.149571E+11 | 0.00 | 0.00 |
Minimum of Months | 0.915174E+09 | 0.197345E+09 | 0.876992E+09 | 0.00 | 0.876992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390223E+10 | 0.211060E+10 | 0.173124E+10 | 0.119206E+09 | 0.164640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195651E+10 | 0.135749E+10 | 0.142326E+10 | 0.681826E+09 | 0.741432E+09 | 0.00 | 0.00 |
February | 0.222902E+10 | 0.100412E+10 | 0.148436E+10 | 0.687108E+09 | 0.797247E+09 | 0.00 | 0.00 |
March | 0.303465E+10 | 0.899815E+09 | 0.200646E+10 | 0.948563E+09 | 0.105789E+10 | 0.00 | 0.00 |
April | 0.357076E+10 | 0.604946E+09 | 0.210727E+10 | 0.940252E+09 | 0.116702E+10 | 0.00 | 0.00 |
May | 0.382572E+10 | 0.315712E+09 | 0.206002E+10 | 0.820343E+09 | 0.123967E+10 | 0.00 | 0.00 |
June | 0.383713E+10 | 0.140732E+09 | 0.196768E+10 | 0.755769E+09 | 0.121191E+10 | 0.00 | 0.00 |
July | 0.420919E+10 | 0.226957E+09 | 0.208920E+10 | 0.753407E+09 | 0.133580E+10 | 0.00 | 0.00 |
August | 0.371855E+10 | 0.162227E+09 | 0.191040E+10 | 0.638793E+09 | 0.127160E+10 | 0.00 | 0.00 |
September | 0.352126E+10 | 0.248448E+09 | 0.178233E+10 | 0.644318E+09 | 0.113802E+10 | 0.00 | 0.00 |
October | 0.310454E+10 | 0.410621E+09 | 0.169525E+10 | 0.730076E+09 | 0.965175E+09 | 0.00 | 0.00 |
November | 0.217685E+10 | 0.700163E+09 | 0.133153E+10 | 0.530932E+09 | 0.800602E+09 | 0.00 | 0.00 |
December | 0.156588E+10 | 0.117352E+10 | 0.111144E+10 | 0.392392E+09 | 0.719052E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367500E+11 | 0.724475E+10 | 0.209692E+11 | 0.852378E+10 | 0.124454E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156588E+10 | 0.140732E+09 | 0.111144E+10 | 0.392392E+09 | 0.719052E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420919E+10 | 0.135749E+10 | 0.210727E+10 | 0.948563E+09 | 0.133580E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.639163E+10 | 0.216270E+10 | 0.416705E+10 | 0.270723E+10 | 0.145982E+10 | 0.00 | 0.00 |
February | 0.553547E+10 | 0.162327E+10 | 0.340490E+10 | 0.197015E+10 | 0.143476E+10 | 0.00 | 0.00 |
March | 0.479812E+10 | 0.143453E+10 | 0.289429E+10 | 0.122367E+10 | 0.167061E+10 | 0.00 | 0.00 |
April | 0.348946E+10 | 0.912770E+09 | 0.190459E+10 | 0.333987E+09 | 0.157060E+10 | 0.00 | 0.00 |
May | 0.316260E+10 | 0.454441E+09 | 0.157710E+10 | 34119654.69 | 0.154298E+10 | 0.00 | 0.00 |
June | 0.314557E+10 | 0.199965E+09 | 0.145512E+10 | 2746020.15 | 0.145237E+10 | 0.00 | 0.00 |
July | 0.362961E+10 | 0.313321E+09 | 0.160997E+10 | 14922854.05 | 0.159505E+10 | 0.00 | 0.00 |
August | 0.387477E+10 | 0.241391E+09 | 0.182726E+10 | 0.154193E+09 | 0.167307E+10 | 0.00 | 0.00 |
September | 0.476815E+10 | 0.394336E+09 | 0.226368E+10 | 0.554715E+09 | 0.170896E+10 | 0.00 | 0.00 |
October | 0.600771E+10 | 0.711750E+09 | 0.321677E+10 | 0.150920E+10 | 0.170757E+10 | 0.00 | 0.00 |
November | 0.596224E+10 | 0.117537E+10 | 0.354191E+10 | 0.197677E+10 | 0.156514E+10 | 0.00 | 0.00 |
December | 0.631432E+10 | 0.189769E+10 | 0.401587E+10 | 0.253298E+10 | 0.148289E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.570797E+11 | 0.115215E+11 | 0.318785E+11 | 0.130147E+11 | 0.188638E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314557E+10 | 0.199965E+09 | 0.145512E+10 | 2746020.15 | 0.143476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.639163E+10 | 0.216270E+10 | 0.416705E+10 | 0.270723E+10 | 0.170896E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179950E+10 | 0.143445E+10 | 0.127857E+10 | 0.551206E+09 | 0.727360E+09 | 0.00 | 0.00 |
February | 0.226251E+10 | 0.109043E+10 | 0.144409E+10 | 0.653530E+09 | 0.790558E+09 | 0.00 | 0.00 |
March | 0.313050E+10 | 0.100646E+10 | 0.199101E+10 | 0.909196E+09 | 0.108181E+10 | 0.00 | 0.00 |
April | 0.364058E+10 | 0.659418E+09 | 0.212083E+10 | 0.982009E+09 | 0.113882E+10 | 0.00 | 0.00 |
May | 0.375849E+10 | 0.360754E+09 | 0.199786E+10 | 0.769079E+09 | 0.122878E+10 | 0.00 | 0.00 |
June | 0.328140E+10 | 0.155190E+09 | 0.163819E+10 | 0.459526E+09 | 0.117867E+10 | 0.00 | 0.00 |
July | 0.388087E+10 | 0.242691E+09 | 0.189186E+10 | 0.585279E+09 | 0.130658E+10 | 0.00 | 0.00 |
August | 0.368557E+10 | 0.187047E+09 | 0.188755E+10 | 0.615148E+09 | 0.127240E+10 | 0.00 | 0.00 |
September | 0.314081E+10 | 0.261105E+09 | 0.155824E+10 | 0.459475E+09 | 0.109877E+10 | 0.00 | 0.00 |
October | 0.296964E+10 | 0.448856E+09 | 0.160183E+10 | 0.624443E+09 | 0.977392E+09 | 0.00 | 0.00 |
November | 0.215302E+10 | 0.764730E+09 | 0.127872E+10 | 0.469041E+09 | 0.809681E+09 | 0.00 | 0.00 |
December | 0.197839E+10 | 0.123781E+10 | 0.132371E+10 | 0.591819E+09 | 0.731891E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.356813E+11 | 0.784895E+10 | 0.200125E+11 | 0.766975E+10 | 0.123427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.179950E+10 | 0.155190E+09 | 0.127857E+10 | 0.459475E+09 | 0.727360E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388087E+10 | 0.143445E+10 | 0.212083E+10 | 0.982009E+09 | 0.130658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.921403E+09 | 0.204018E+10 | 0.886652E+09 | 0.00 | 0.886652E+09 | 0.00 | 0.00 |
February | 0.125284E+10 | 0.152283E+10 | 0.947930E+09 | 0.00 | 0.947930E+09 | 0.00 | 0.00 |
March | 0.165042E+10 | 0.140710E+10 | 0.125160E+10 | 0.00 | 0.125160E+10 | 0.00 | 0.00 |
April | 0.222945E+10 | 0.877452E+09 | 0.135723E+10 | 6096834.36 | 0.135113E+10 | 0.00 | 0.00 |
May | 0.318201E+10 | 0.471840E+09 | 0.160155E+10 | 71641146.04 | 0.152991E+10 | 0.00 | 0.00 |
June | 0.355169E+10 | 0.206264E+09 | 0.165561E+10 | 0.119209E+09 | 0.153641E+10 | 0.00 | 0.00 |
July | 0.389783E+10 | 0.311543E+09 | 0.173127E+10 | 84835693.56 | 0.164644E+10 | 0.00 | 0.00 |
August | 0.327179E+10 | 0.212923E+09 | 0.153220E+10 | 14092029.49 | 0.151811E+10 | 0.00 | 0.00 |
September | 0.292889E+10 | 0.335812E+09 | 0.131540E+10 | 104060.46 | 0.131530E+10 | 0.00 | 0.00 |
October | 0.222455E+10 | 0.558128E+09 | 0.113872E+10 | 0.00 | 0.113872E+10 | 0.00 | 0.00 |
November | 0.151826E+10 | 0.102419E+10 | 0.958181E+09 | 0.00 | 0.958181E+09 | 0.00 | 0.00 |
December | 0.104346E+10 | 0.172253E+10 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276726E+11 | 0.106908E+11 | 0.152534E+11 | 0.295979E+09 | 0.149574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.921403E+09 | 0.206264E+09 | 0.877010E+09 | 0.00 | 0.877010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.389783E+10 | 0.204018E+10 | 0.173127E+10 | 0.119209E+09 | 0.164644E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196547E+10 | 0.126359E+10 | 0.142328E+10 | 0.681840E+09 | 0.741441E+09 | 0.00 | 0.00 |
February | 0.222501E+10 | 0.945617E+09 | 0.148438E+10 | 0.687122E+09 | 0.797257E+09 | 0.00 | 0.00 |
March | 0.301047E+10 | 0.860717E+09 | 0.200649E+10 | 0.948582E+09 | 0.105791E+10 | 0.00 | 0.00 |
April | 0.354487E+10 | 0.579170E+09 | 0.210730E+10 | 0.940270E+09 | 0.116703E+10 | 0.00 | 0.00 |
May | 0.380603E+10 | 0.301683E+09 | 0.206005E+10 | 0.820359E+09 | 0.123969E+10 | 0.00 | 0.00 |
June | 0.383042E+10 | 0.133967E+09 | 0.196771E+10 | 0.755784E+09 | 0.121193E+10 | 0.00 | 0.00 |
July | 0.421041E+10 | 0.209038E+09 | 0.208924E+10 | 0.753422E+09 | 0.133581E+10 | 0.00 | 0.00 |
August | 0.373493E+10 | 0.137501E+09 | 0.191042E+10 | 0.638805E+09 | 0.127162E+10 | 0.00 | 0.00 |
September | 0.353775E+10 | 0.222152E+09 | 0.178236E+10 | 0.644331E+09 | 0.113803E+10 | 0.00 | 0.00 |
October | 0.311280E+10 | 0.362692E+09 | 0.169528E+10 | 0.730090E+09 | 0.965187E+09 | 0.00 | 0.00 |
November | 0.218753E+10 | 0.635994E+09 | 0.133155E+10 | 0.530943E+09 | 0.800612E+09 | 0.00 | 0.00 |
December | 0.158150E+10 | 0.108370E+10 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367472E+11 | 0.673582E+10 | 0.209695E+11 | 0.852395E+10 | 0.124456E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158150E+10 | 0.133967E+09 | 0.111146E+10 | 0.392399E+09 | 0.719061E+09 | 0.00 | 0.00 |
Maximum of Months | 0.421041E+10 | 0.126359E+10 | 0.210730E+10 | 0.948582E+09 | 0.133581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.636990E+10 | 0.199273E+10 | 0.416721E+10 | 0.270734E+10 | 0.145987E+10 | 0.00 | 0.00 |
February | 0.550633E+10 | 0.151725E+10 | 0.340503E+10 | 0.197023E+10 | 0.143480E+10 | 0.00 | 0.00 |
March | 0.473928E+10 | 0.139547E+10 | 0.289439E+10 | 0.122373E+10 | 0.167067E+10 | 0.00 | 0.00 |
April | 0.345158E+10 | 0.912462E+09 | 0.190465E+10 | 0.334001E+09 | 0.157064E+10 | 0.00 | 0.00 |
May | 0.314715E+10 | 0.463171E+09 | 0.157714E+10 | 34121070.62 | 0.154302E+10 | 0.00 | 0.00 |
June | 0.314275E+10 | 0.209227E+09 | 0.145516E+10 | 2746134.10 | 0.145242E+10 | 0.00 | 0.00 |
July | 0.364922E+10 | 0.310486E+09 | 0.161002E+10 | 14923473.33 | 0.159510E+10 | 0.00 | 0.00 |
August | 0.391964E+10 | 0.215792E+09 | 0.182732E+10 | 0.154199E+09 | 0.167312E+10 | 0.00 | 0.00 |
September | 0.482139E+10 | 0.353640E+09 | 0.226375E+10 | 0.554738E+09 | 0.170902E+10 | 0.00 | 0.00 |
October | 0.604263E+10 | 0.613467E+09 | 0.321689E+10 | 0.150926E+10 | 0.170762E+10 | 0.00 | 0.00 |
November | 0.596793E+10 | 0.104458E+10 | 0.354204E+10 | 0.197685E+10 | 0.156519E+10 | 0.00 | 0.00 |
December | 0.629593E+10 | 0.173730E+10 | 0.401603E+10 | 0.253308E+10 | 0.148294E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.570537E+11 | 0.107656E+11 | 0.318796E+11 | 0.130152E+11 | 0.188644E+11 | 0.00 | 0.00 |
Minimum of Months | 0.314275E+10 | 0.209227E+09 | 0.145516E+10 | 2746134.10 | 0.143480E+10 | 0.00 | 0.00 |
Maximum of Months | 0.636990E+10 | 0.199273E+10 | 0.416721E+10 | 0.270734E+10 | 0.170902E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180938E+10 | 0.134737E+10 | 0.127858E+10 | 0.551215E+09 | 0.727367E+09 | 0.00 | 0.00 |
February | 0.226310E+10 | 0.103431E+10 | 0.144411E+10 | 0.653541E+09 | 0.790565E+09 | 0.00 | 0.00 |
March | 0.311351E+10 | 0.967724E+09 | 0.199104E+10 | 0.909211E+09 | 0.108182E+10 | 0.00 | 0.00 |
April | 0.362379E+10 | 0.637131E+09 | 0.212086E+10 | 0.982026E+09 | 0.113883E+10 | 0.00 | 0.00 |
May | 0.374459E+10 | 0.347917E+09 | 0.199788E+10 | 0.769092E+09 | 0.122879E+10 | 0.00 | 0.00 |
June | 0.327521E+10 | 0.152156E+09 | 0.163821E+10 | 0.459534E+09 | 0.117868E+10 | 0.00 | 0.00 |
July | 0.388486E+10 | 0.226624E+09 | 0.189188E+10 | 0.585288E+09 | 0.130659E+10 | 0.00 | 0.00 |
August | 0.370048E+10 | 0.161012E+09 | 0.188758E+10 | 0.615158E+09 | 0.127242E+10 | 0.00 | 0.00 |
September | 0.315684E+10 | 0.234575E+09 | 0.155826E+10 | 0.459482E+09 | 0.109878E+10 | 0.00 | 0.00 |
October | 0.298033E+10 | 0.403854E+09 | 0.160186E+10 | 0.624453E+09 | 0.977402E+09 | 0.00 | 0.00 |
November | 0.216494E+10 | 0.700268E+09 | 0.127874E+10 | 0.469049E+09 | 0.809690E+09 | 0.00 | 0.00 |
December | 0.199397E+10 | 0.114475E+10 | 0.132373E+10 | 0.591829E+09 | 0.731899E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357110E+11 | 0.735769E+10 | 0.200127E+11 | 0.766988E+10 | 0.123428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180938E+10 | 0.152156E+09 | 0.127858E+10 | 0.459482E+09 | 0.727367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388486E+10 | 0.134737E+10 | 0.212086E+10 | 0.982026E+09 | 0.130659E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356337E+10 | -0.333105E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232316127.9 | 60.05 | 0.00 | 0.00 |
February | 0.320910E+10 | -0.299936E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209738255.1 | 60.05 | 0.00 | 0.00 |
March | 0.367576E+10 | -0.344344E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232321553.6 | 60.05 | 0.00 | 0.00 |
April | 0.318437E+10 | -0.295991E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224457672.2 | 60.05 | 0.00 | 0.00 |
May | 0.325401E+10 | -0.302209E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231911193.9 | 60.05 | 0.00 | 0.00 |
June | 0.310995E+10 | -0.288520E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224748505.0 | 60.05 | 0.00 | 0.00 |
July | 0.290379E+10 | -0.267180E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231989147.4 | 60.05 | 0.00 | 0.00 |
August | 0.322146E+10 | -0.298917E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232288433.7 | 60.05 | 0.00 | 0.00 |
September | 0.301541E+10 | -0.279079E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224628723.6 | 60.05 | 0.00 | 0.00 |
October | 0.325749E+10 | -0.302594E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231541279.6 | 60.05 | 0.00 | 0.00 |
November | 0.334446E+10 | -0.312062E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223843242.8 | 60.05 | 0.00 | 0.00 |
December | 0.342816E+10 | -0.319605E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232114823.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.391673E+11 | -0.364354E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273190E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.290379E+10 | -0.344344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -232321553.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.367576E+10 | -0.267180E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209738255.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7151.19 | 35.94 | 274.83 | 293.50 | 1417.94 | 24.98 | 194.17 | 277.33 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2646.16 | 25.13 | 135.83 | 278.50 | 1100.78 | 20.55 | 130.83 | 252.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:49 | 1621.16 | 18.77 | 5.67 | 328.83 | 902.02 | 20.65 | 158.17 | 294.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 1253.19 | 18.20 | 0.00 | 327.00 | 715.48 | 20.31 | 99.67 | 293.50 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:19 | 1071.61 | 17.72 | 0.00 | 348.17 | 602.52 | 19.84 | 59.00 | 300.00 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:19 | 1011.85 | 17.06 | 0.00 | 326.00 | 563.45 | 19.20 | 53.50 | 276.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:10 | 1134.46 | 17.92 | 0.00 | 355.33 | 633.12 | 20.07 | 94.83 | 306.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1351.48 | 18.39 | 0.00 | 343.83 | 740.72 | 20.52 | 150.33 | 305.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1630.69 | 18.59 | 0.00 | 316.50 | 872.10 | 20.74 | 187.67 | 281.17 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:09 | 2174.77 | 20.41 | 31.67 | 315.67 | 1086.95 | 21.55 | 201.17 | 289.17 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 4070.67 | 31.18 | 247.67 | 292.83 | 1225.96 | 24.34 | 235.67 | 274.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6793.53 | 36.23 | 278.67 | 280.00 | 1644.99 | 26.34 | 211.50 | 262.50 |
Annual Sum or Average | 4111.50 | 0.52 | 2458.42 | 22.28 | 974.33 | 3806.17 | 924.04 | 21.38 | 1776.50 | 3412.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1011.85 | 17.06 | 0.00 | 278.50 | 563.45 | 19.20 | 53.50 | 252.50 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7151.19 | 36.23 | 278.67 | 355.33 | 1644.99 | 26.34 | 235.67 | 306.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2252.64 | 22.67 | 102.67 | 269.00 | 1193.06 | 23.11 | 76.83 | 229.33 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:49 | 2354.86 | 21.78 | 101.33 | 260.83 | 894.26 | 20.87 | 45.67 | 227.67 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2186.11 | 19.76 | 86.00 | 322.83 | 1185.73 | 21.90 | 68.00 | 289.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2604.39 | 20.76 | 99.83 | 325.33 | 1394.15 | 21.81 | 70.67 | 291.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:10 | 2385.00 | 20.10 | 103.83 | 358.50 | 1018.82 | 20.77 | 57.83 | 312.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2311.80 | 20.27 | 111.33 | 342.50 | 996.87 | 21.05 | 65.00 | 300.50 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2293.07 | 20.64 | 115.67 | 363.00 | 995.49 | 20.54 | 54.33 | 320.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:40 | 2263.76 | 20.90 | 97.17 | 346.83 | 1027.88 | 20.86 | 47.33 | 309.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 2219.18 | 21.52 | 104.17 | 312.00 | 1155.90 | 22.44 | 74.83 | 272.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2193.78 | 21.63 | 94.50 | 303.67 | 1167.88 | 22.57 | 70.33 | 269.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1745.20 | 20.53 | 84.83 | 273.50 | 900.62 | 22.08 | 64.50 | 234.00 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1892.19 | 21.39 | 87.17 | 255.83 | 780.89 | 20.76 | 46.50 | 213.67 |
Annual Sum or Average | 4111.50 | 0.53 | 2236.83 | 20.93 | 1188.50 | 3733.83 | 1063.50 | 21.53 | 741.83 | 3269.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1745.20 | 19.76 | 84.83 | 255.83 | 780.89 | 20.54 | 45.67 | 213.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2604.39 | 22.67 | 115.67 | 363.00 | 1394.15 | 23.11 | 76.83 | 320.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-09:50 | 560.12 | 15.01 | 0.00 | 249.83 | 357.07 | 17.46 | 0.00 | 160.33 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:20 | 638.85 | 15.87 | 0.00 | 251.83 | 396.17 | 18.15 | 0.00 | 185.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 765.07 | 17.08 | 0.00 | 315.17 | 464.90 | 19.25 | 0.00 | 260.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 914.83 | 17.98 | 0.00 | 332.00 | 547.77 | 20.04 | 32.17 | 297.83 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:49 | 1091.72 | 19.39 | 27.00 | 368.33 | 607.92 | 20.48 | 103.83 | 331.50 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:19 | 1164.20 | 20.82 | 66.50 | 358.00 | 640.26 | 21.67 | 143.17 | 318.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1220.56 | 19.66 | 26.17 | 375.50 | 674.24 | 21.78 | 175.33 | 340.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1097.72 | 18.40 | 0.00 | 351.67 | 624.89 | 20.51 | 97.83 | 316.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 921.79 | 17.58 | 0.00 | 314.67 | 530.64 | 19.68 | 12.50 | 267.33 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 732.26 | 16.70 | 0.00 | 295.67 | 449.48 | 18.93 | 0.00 | 232.17 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 645.17 | 16.03 | 0.00 | 258.83 | 388.42 | 18.30 | 0.00 | 184.67 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:09 | 612.07 | 15.74 | 0.00 | 245.00 | 378.35 | 18.13 | 0.00 | 168.33 |
Annual Sum or Average | 4111.50 | 0.53 | 887.00 | 17.70 | 119.67 | 3716.50 | 516.26 | 19.67 | 564.83 | 3063.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 560.12 | 15.01 | 0.00 | 245.00 | 357.07 | 17.46 | 0.00 | 160.33 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 1220.56 | 20.82 | 66.50 | 375.50 | 674.24 | 21.78 | 175.33 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:50 | 1938.72 | 21.54 | 91.50 | 271.17 | 1059.82 | 22.35 | 67.00 | 226.67 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1782.17 | 19.65 | 71.50 | 267.67 | 912.09 | 20.56 | 46.83 | 230.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2145.63 | 19.71 | 86.17 | 320.50 | 1133.72 | 21.90 | 69.17 | 288.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:00 | 2375.41 | 19.43 | 80.67 | 335.33 | 1282.00 | 20.69 | 51.83 | 301.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2141.38 | 14.62 | 0.00 | 351.83 | 1116.00 | 17.89 | 0.00 | 312.50 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:49 | 1791.32 | 14.32 | 0.00 | 334.83 | 812.03 | 17.53 | 0.33 | 291.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 2030.04 | 15.28 | 3.67 | 359.33 | 916.13 | 18.32 | 0.00 | 320.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2189.30 | 18.16 | 56.83 | 343.50 | 1139.24 | 18.71 | 5.50 | 306.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1803.26 | 19.55 | 80.83 | 315.50 | 941.52 | 20.75 | 52.00 | 279.50 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2175.28 | 21.87 | 103.00 | 301.00 | 1155.35 | 22.95 | 79.00 | 266.33 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:20 | 1697.27 | 20.12 | 83.00 | 274.00 | 898.01 | 22.26 | 69.17 | 237.83 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 1943.13 | 21.66 | 84.67 | 266.50 | 1051.90 | 23.52 | 75.50 | 232.00 |
Annual Sum or Average | 4111.50 | 0.52 | 2007.72 | 18.57 | 741.83 | 3741.17 | 1033.78 | 20.44 | 516.33 | 3294.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1697.27 | 14.32 | 0.00 | 266.50 | 812.03 | 17.53 | 0.00 | 226.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2375.41 | 21.87 | 103.00 | 359.33 | 1282.00 | 23.52 | 79.00 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7020.72 | 35.64 | 274.83 | 292.67 | 1317.60 | 22.54 | 81.67 | 274.67 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2541.44 | 22.74 | 135.00 | 278.17 | 1022.11 | 17.68 | 0.00 | 250.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1545.24 | 15.07 | 5.67 | 326.67 | 847.82 | 18.28 | 1.00 | 290.67 |
April | 357.50 | 0.53 | 0.48 | 01-APR-07:49 | 1202.47 | 14.72 | 0.00 | 325.50 | 683.34 | 18.17 | 0.00 | 289.33 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:30 | 1032.28 | 14.13 | 0.00 | 345.83 | 579.43 | 17.56 | 0.00 | 293.17 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:30 | 975.20 | 13.38 | 0.00 | 323.50 | 541.95 | 16.83 | 0.00 | 271.50 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1092.36 | 14.27 | 0.00 | 353.00 | 608.35 | 17.73 | 0.00 | 301.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1298.51 | 14.82 | 0.00 | 343.17 | 708.03 | 18.23 | 0.00 | 301.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1561.24 | 14.77 | 0.00 | 316.00 | 826.32 | 18.21 | 1.17 | 278.33 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:20 | 2078.71 | 16.85 | 31.67 | 315.50 | 1017.72 | 19.04 | 9.17 | 286.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3959.97 | 30.14 | 245.50 | 291.17 | 1144.16 | 21.87 | 71.50 | 272.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6658.42 | 36.01 | 278.50 | 278.67 | 1543.00 | 23.98 | 92.67 | 260.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2383.42 | 19.40 | 971.17 | 3789.83 | 871.60 | 18.98 | 257.17 | 3369.33 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 975.20 | 13.38 | 0.00 | 278.17 | 541.95 | 16.83 | 0.00 | 250.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7020.72 | 36.01 | 278.50 | 353.00 | 1543.00 | 23.98 | 92.67 | 301.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2198.19 | 22.22 | 102.67 | 267.17 | 1150.36 | 22.91 | 74.17 | 224.50 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 2299.04 | 21.32 | 101.00 | 259.67 | 851.39 | 20.66 | 45.67 | 224.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2126.95 | 19.26 | 86.00 | 321.00 | 1134.60 | 21.71 | 68.00 | 285.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2523.65 | 20.30 | 99.83 | 323.33 | 1341.32 | 21.64 | 70.67 | 289.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 2322.83 | 19.65 | 103.67 | 355.83 | 959.80 | 19.99 | 50.33 | 307.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2259.76 | 19.83 | 111.33 | 340.83 | 951.25 | 20.89 | 65.00 | 297.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2234.68 | 20.20 | 115.67 | 361.67 | 948.29 | 20.38 | 54.33 | 315.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2191.18 | 20.46 | 97.17 | 345.67 | 980.88 | 20.69 | 47.33 | 305.00 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-06:49 | 2155.19 | 20.90 | 102.33 | 310.83 | 1109.13 | 22.26 | 74.83 | 269.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2088.23 | 19.81 | 81.33 | 302.33 | 1118.52 | 22.25 | 66.83 | 267.00 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1693.08 | 20.04 | 84.67 | 272.00 | 843.77 | 21.05 | 54.00 | 228.67 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1846.41 | 20.90 | 87.17 | 253.83 | 746.05 | 20.52 | 37.33 | 208.83 |
Annual Sum or Average | 4111.50 | 0.53 | 2173.09 | 20.35 | 1172.83 | 3714.17 | 1015.13 | 21.21 | 708.50 | 3223.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1693.08 | 19.26 | 81.33 | 253.83 | 746.05 | 19.99 | 37.33 | 208.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2523.65 | 22.22 | 115.67 | 361.67 | 1341.32 | 22.91 | 74.83 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-09:00 | 539.83 | 11.49 | 0.00 | 246.50 | 346.48 | 15.20 | 0.00 | 153.17 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:30 | 616.37 | 12.37 | 0.00 | 249.17 | 384.23 | 15.95 | 0.00 | 177.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 738.28 | 13.72 | 0.00 | 311.50 | 450.43 | 17.24 | 0.00 | 255.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 882.43 | 14.66 | 0.00 | 331.17 | 529.97 | 18.13 | 0.00 | 292.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1052.27 | 16.02 | 26.83 | 365.83 | 591.00 | 19.27 | 26.00 | 332.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1121.14 | 17.73 | 65.00 | 355.67 | 614.19 | 19.42 | 33.50 | 314.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1171.53 | 14.92 | 0.00 | 372.33 | 647.26 | 19.59 | 26.17 | 337.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1057.19 | 14.93 | 0.00 | 349.50 | 601.48 | 18.38 | 0.00 | 311.83 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-07:19 | 888.45 | 14.07 | 0.00 | 313.67 | 511.71 | 17.48 | 0.00 | 261.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 705.27 | 13.38 | 0.00 | 293.50 | 434.87 | 16.89 | 0.00 | 225.67 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 621.65 | 12.39 | 0.00 | 255.17 | 375.58 | 15.99 | 0.00 | 175.83 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:20 | 589.39 | 12.13 | 0.00 | 240.67 | 366.19 | 15.82 | 0.00 | 160.17 |
Annual Sum or Average | 4111.50 | 0.53 | 854.37 | 14.16 | 91.83 | 3684.67 | 498.54 | 17.60 | 85.67 | 2997.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 539.83 | 11.49 | 0.00 | 240.67 | 346.48 | 15.20 | 0.00 | 153.17 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 1171.53 | 17.73 | 65.00 | 372.33 | 647.26 | 19.59 | 33.50 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1890.39 | 21.14 | 91.50 | 270.00 | 1022.18 | 22.24 | 66.67 | 221.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1726.90 | 19.23 | 71.17 | 264.17 | 870.70 | 20.44 | 47.00 | 227.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2086.75 | 19.26 | 86.00 | 318.17 | 1083.18 | 21.76 | 69.17 | 286.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:00 | 2240.06 | 18.96 | 80.67 | 332.33 | 1228.50 | 20.52 | 51.83 | 299.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2077.18 | 14.06 | 0.00 | 349.67 | 1071.20 | 17.69 | 0.00 | 308.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:00 | 1744.62 | 13.76 | 0.00 | 333.50 | 775.06 | 17.31 | 0.00 | 287.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1973.01 | 14.72 | 3.67 | 357.50 | 874.08 | 18.11 | 0.00 | 317.50 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2116.11 | 17.68 | 56.83 | 342.00 | 1091.82 | 18.53 | 5.50 | 303.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1752.36 | 19.11 | 80.83 | 313.83 | 900.93 | 20.61 | 52.00 | 275.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2117.17 | 21.47 | 103.00 | 299.50 | 1111.13 | 22.83 | 78.83 | 263.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1647.46 | 19.69 | 83.00 | 272.00 | 860.68 | 22.15 | 68.50 | 232.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:20 | 1884.13 | 20.98 | 82.00 | 263.67 | 1008.55 | 23.43 | 73.50 | 229.00 |
Annual Sum or Average | 4111.50 | 0.53 | 1944.23 | 18.08 | 738.67 | 3716.33 | 990.33 | 20.28 | 513.00 | 3252.00 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1647.46 | 13.76 | 0.00 | 263.67 | 775.06 | 17.31 | 0.00 | 221.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2240.06 | 21.47 | 103.00 | 357.50 | 1228.50 | 23.43 | 78.83 | 317.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 7020.65 | 35.64 | 274.83 | 292.67 | 1317.52 | 22.54 | 81.67 | 274.67 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2541.35 | 22.74 | 135.00 | 278.17 | 1022.04 | 17.68 | 0.00 | 250.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1545.15 | 15.08 | 5.67 | 326.50 | 847.76 | 18.28 | 1.00 | 290.67 |
April | 357.50 | 0.53 | 0.48 | 01-APR-07:49 | 1202.40 | 14.72 | 0.00 | 325.50 | 683.29 | 18.17 | 0.00 | 289.17 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:30 | 1032.22 | 14.13 | 0.00 | 345.83 | 579.39 | 17.56 | 0.00 | 293.17 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:30 | 975.15 | 13.38 | 0.00 | 323.50 | 541.91 | 16.83 | 0.00 | 271.50 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:10 | 1092.30 | 14.27 | 0.00 | 353.00 | 608.31 | 17.73 | 0.00 | 301.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1298.43 | 14.82 | 0.00 | 343.17 | 707.98 | 18.23 | 0.00 | 301.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1561.14 | 14.77 | 0.00 | 316.00 | 826.25 | 18.21 | 1.17 | 278.33 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-08:20 | 2078.60 | 16.86 | 31.67 | 315.50 | 1017.64 | 19.04 | 9.17 | 286.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3959.87 | 30.14 | 245.50 | 291.17 | 1144.07 | 21.87 | 71.50 | 272.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6658.35 | 36.01 | 278.50 | 278.67 | 1542.90 | 23.98 | 92.67 | 260.67 |
Annual Sum or Average | 4111.50 | 0.52 | 2383.35 | 19.40 | 971.17 | 3789.67 | 871.54 | 18.98 | 257.17 | 3369.17 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 975.15 | 13.38 | 0.00 | 278.17 | 541.91 | 16.83 | 0.00 | 250.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 7020.65 | 36.01 | 278.50 | 353.00 | 1542.90 | 23.98 | 92.67 | 301.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 2198.16 | 22.22 | 102.67 | 267.17 | 1150.32 | 22.91 | 74.17 | 224.50 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 2299.00 | 21.32 | 101.00 | 259.67 | 851.34 | 20.66 | 45.67 | 224.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 2126.91 | 19.26 | 86.00 | 321.00 | 1134.55 | 21.71 | 68.00 | 285.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2523.60 | 20.30 | 99.83 | 323.33 | 1341.26 | 21.64 | 70.67 | 289.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 2322.77 | 19.65 | 103.67 | 355.83 | 959.74 | 19.99 | 50.33 | 307.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-05:00 | 2259.69 | 19.83 | 111.33 | 340.83 | 951.19 | 20.90 | 65.00 | 297.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 2234.60 | 20.20 | 115.67 | 361.67 | 948.22 | 20.38 | 54.33 | 315.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 2191.11 | 20.46 | 97.17 | 345.67 | 980.81 | 20.70 | 47.33 | 305.00 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-06:49 | 2155.12 | 20.91 | 102.33 | 310.83 | 1109.06 | 22.26 | 74.83 | 269.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 2088.19 | 19.81 | 81.33 | 302.33 | 1118.46 | 22.25 | 66.83 | 267.00 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1693.04 | 20.04 | 84.67 | 272.00 | 843.72 | 21.05 | 54.00 | 228.67 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1846.37 | 20.90 | 87.17 | 253.83 | 746.00 | 20.52 | 37.33 | 208.83 |
Annual Sum or Average | 4111.50 | 0.53 | 2173.04 | 20.35 | 1172.83 | 3714.17 | 1015.07 | 21.21 | 708.50 | 3223.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1693.04 | 19.26 | 81.33 | 253.83 | 746.00 | 19.99 | 37.33 | 208.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2523.60 | 22.22 | 115.67 | 361.67 | 1341.26 | 22.91 | 74.83 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-09:00 | 539.82 | 11.50 | 0.00 | 246.50 | 346.46 | 15.20 | 0.00 | 153.17 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:30 | 616.36 | 12.37 | 0.00 | 249.17 | 384.20 | 15.96 | 0.00 | 177.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-09:50 | 738.25 | 13.73 | 0.00 | 311.50 | 450.40 | 17.24 | 0.00 | 255.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-07:30 | 882.39 | 14.67 | 0.00 | 331.17 | 529.93 | 18.14 | 0.00 | 292.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1052.22 | 16.02 | 26.83 | 365.83 | 590.96 | 19.27 | 26.00 | 332.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1121.08 | 17.73 | 65.00 | 355.67 | 614.14 | 19.42 | 33.50 | 314.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1171.47 | 14.92 | 0.00 | 372.33 | 647.21 | 19.59 | 26.17 | 337.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:30 | 1057.15 | 14.93 | 0.00 | 349.50 | 601.44 | 18.38 | 0.00 | 311.83 |
September | 349.67 | 0.53 | 0.48 | 01-SEP-07:19 | 888.41 | 14.07 | 0.00 | 313.67 | 511.67 | 17.48 | 0.00 | 261.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 705.25 | 13.38 | 0.00 | 293.50 | 434.85 | 16.89 | 0.00 | 225.67 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:20 | 621.64 | 12.40 | 0.00 | 255.17 | 375.55 | 15.99 | 0.00 | 175.83 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:20 | 589.38 | 12.14 | 0.00 | 240.67 | 366.17 | 15.82 | 0.00 | 160.17 |
Annual Sum or Average | 4111.50 | 0.53 | 854.34 | 14.16 | 91.83 | 3684.67 | 498.51 | 17.60 | 85.67 | 2997.00 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 539.82 | 11.50 | 0.00 | 240.67 | 346.46 | 15.20 | 0.00 | 153.17 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 1171.47 | 17.73 | 65.00 | 372.33 | 647.21 | 19.59 | 33.50 | 337.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1890.36 | 21.14 | 91.50 | 270.00 | 1022.14 | 22.24 | 66.67 | 221.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1726.87 | 19.23 | 71.17 | 264.17 | 870.65 | 20.44 | 47.00 | 227.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:50 | 2086.71 | 19.26 | 86.00 | 318.17 | 1083.13 | 21.76 | 69.17 | 286.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:00 | 2240.01 | 18.97 | 80.67 | 332.33 | 1228.45 | 20.52 | 51.83 | 299.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:49 | 2077.12 | 14.06 | 0.00 | 349.67 | 1071.14 | 17.69 | 0.00 | 308.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:00 | 1744.55 | 13.76 | 0.00 | 333.50 | 775.01 | 17.31 | 0.00 | 287.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1972.94 | 14.72 | 3.67 | 357.50 | 874.02 | 18.12 | 0.00 | 317.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 2116.04 | 17.68 | 56.83 | 342.00 | 1091.75 | 18.53 | 5.50 | 303.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:00 | 1752.29 | 19.11 | 80.83 | 313.83 | 900.87 | 20.61 | 52.00 | 275.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 2117.13 | 21.47 | 103.00 | 299.50 | 1111.07 | 22.83 | 78.83 | 263.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1647.42 | 19.69 | 83.00 | 272.00 | 860.63 | 22.15 | 68.50 | 232.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:20 | 1884.11 | 20.98 | 82.00 | 263.67 | 1008.50 | 23.43 | 73.67 | 229.00 |
Annual Sum or Average | 4111.50 | 0.53 | 1944.18 | 18.09 | 738.67 | 3716.33 | 990.28 | 20.28 | 513.17 | 3251.83 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1647.42 | 13.76 | 0.00 | 263.67 | 775.01 | 17.31 | 0.00 | 221.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2240.01 | 21.47 | 103.00 | 357.50 | 1228.45 | 23.43 | 78.83 | 317.33 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234601E+09 | 6269.96 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80975297.28 | 6269.96 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176279E+09 | 6269.96 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11069357.81 | 5104.87 | 19-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42000188.30 | 6269.96 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154052E+09 | 6269.96 | 12-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234601E+09 | 6269.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 373896.12 | 2492.64 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 373896.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 373896.12 | 2492.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2942825.79 | 3811.77 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2942825.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2942825.79 | 3811.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2855572.28 | 2904.53 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2855572.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2855572.28 | 2904.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 346590.86 | 1264.38 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4829155.97 | 7712.03 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1497798.30 | 2943.50 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 673846.18 | 1558.81 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7347391.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4829155.97 | 7712.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2905037.14 | 5104.56 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5074710.59 | 5104.56 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2671021.51 | 5104.56 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9619613.44 | 5104.56 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20270382.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9619613.44 | 5104.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6042554.18 | 6880.14 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14024933.42 | 7751.51 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3611487.59 | 7751.51 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6916004.59 | 6399.45 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30594979.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14024933.42 | 7751.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8555498.18 | 5124.47 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16666997.48 | 5124.47 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4710775.37 | 5124.47 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14431389.97 | 5124.47 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44364661.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16666997.48 | 5124.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7499719.56 | 1769.79 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7499719.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7499719.56 | 1769.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4052670.61 | 6396.28 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16552557.72 | 16473.28 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5874618.30 | 4198.24 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26479846.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16552557.72 | 16473.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30136155.19 | 9822.98 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30663651.52 | 9822.98 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25967784.30 | 9822.98 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1650912.19 | 5730.14 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44948804.80 | 9822.98 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44948804.80 | 9822.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 45951702.53 | 6461.42 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29045516.85 | 6461.42 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22365220.06 | 6461.42 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2795261.17 | 6461.42 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70654497.36 | 6461.42 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70654497.36 | 6461.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85030297.57 | 9846.78 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70870840.48 | 9846.78 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39774671.70 | 9846.78 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10294188.92 | 9846.78 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86490033.04 | 9846.78 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86490033.04 | 9846.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106094E+09 | 6470.35 | 09-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78208564.91 | 6470.35 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52710330.59 | 6470.35 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12214946.01 | 6470.35 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108872E+09 | 6470.35 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108872E+09 | 6470.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.515850E+11 | 0.382546E+11 | 84523.45 | 02-JAN-14:00 | 57205.80 | 0.00 |
February | 0.00 | 0.00 | 0.523569E+11 | 0.394467E+11 | 76043.02 | 13-FEB-07:03 | 45726.57 | 0.00 |
March | 0.00 | 0.00 | 0.630293E+11 | 0.464186E+11 | 83455.88 | 06-MAR-07:03 | 49494.16 | 0.00 |
April | 0.00 | 0.00 | 0.716338E+11 | 0.520501E+11 | 87768.56 | 13-APR-04:03 | 52917.47 | 0.00 |
May | 0.00 | 0.00 | 0.962134E+11 | 0.650559E+11 | 109883.43 | 15-MAY-04:02 | 79732.47 | 0.00 |
June | 0.00 | 0.00 | 0.108022E+12 | 0.683961E+11 | 120548.26 | 08-JUN-04:02 | 80110.43 | 0.00 |
July | 0.00 | 0.00 | 0.113747E+12 | 0.722404E+11 | 114067.47 | 31-JUL-04:02 | 81486.50 | 0.00 |
August | 0.00 | 0.00 | 0.117816E+12 | 0.744312E+11 | 122033.58 | 18-AUG-04:02 | 80852.18 | 0.00 |
September | 0.00 | 0.00 | 0.108500E+12 | 0.690813E+11 | 126330.95 | 22-SEP-04:02 | 81156.41 | 0.00 |
October | 0.00 | 0.00 | 0.998494E+11 | 0.664193E+11 | 126345.14 | 03-OCT-04:02 | 77676.17 | 0.00 |
November | 0.00 | 0.00 | 0.788716E+11 | 0.535260E+11 | 103941.43 | 04-NOV-04:03 | 57219.80 | 0.00 |
December | 0.00 | 0.00 | 0.552225E+11 | 0.396309E+11 | 94242.20 | 09-DEC-06:03 | 58500.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101685E+13 | 0.684951E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.515850E+11 | 0.382546E+11 | 76043.02 | 45726.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117816E+12 | 0.744312E+11 | 126345.14 | 81486.50 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424811E+11 | 0.302388E+11 | 77090.62 | 02-JAN-14:00 | 50812.76 | 0.00 |
February | 0.00 | 0.00 | 0.445338E+11 | 0.324175E+11 | 62716.53 | 11-FEB-06:03 | 33033.75 | 0.00 |
March | 0.00 | 0.00 | 0.550279E+11 | 0.392811E+11 | 71298.47 | 27-MAR-15:00 | 51960.44 | 0.00 |
April | 0.00 | 0.00 | 0.636139E+11 | 0.450817E+11 | 78206.76 | 14-APR-15:00 | 53709.73 | 0.00 |
May | 0.00 | 0.00 | 0.851445E+11 | 0.558422E+11 | 112093.22 | 30-MAY-04:02 | 73077.81 | 0.00 |
June | 0.00 | 0.00 | 0.965705E+11 | 0.590470E+11 | 119302.99 | 19-JUN-04:02 | 67196.99 | 0.00 |
July | 0.00 | 0.00 | 0.101226E+12 | 0.620936E+11 | 117110.06 | 03-JUL-04:02 | 72357.21 | 0.00 |
August | 0.00 | 0.00 | 0.102380E+12 | 0.622323E+11 | 116373.45 | 18-AUG-04:02 | 72724.09 | 0.00 |
September | 0.00 | 0.00 | 0.941730E+11 | 0.576373E+11 | 117273.48 | 19-SEP-04:02 | 71667.62 | 0.00 |
October | 0.00 | 0.00 | 0.849030E+11 | 0.546340E+11 | 119725.16 | 02-OCT-04:02 | 68288.31 | 0.00 |
November | 0.00 | 0.00 | 0.660336E+11 | 0.429257E+11 | 110067.04 | 30-NOV-06:03 | 61301.81 | 0.00 |
December | 0.00 | 0.00 | 0.463221E+11 | 0.317225E+11 | 87849.95 | 09-DEC-06:03 | 54533.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.882410E+12 | 0.573154E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.424811E+11 | 0.302388E+11 | 62716.53 | 33033.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102380E+12 | 0.622323E+11 | 119725.16 | 73077.81 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.434892E+11 | 0.305617E+11 | 82509.79 | 02-JAN-14:00 | 56035.81 | 0.00 |
February | 0.00 | 0.00 | 0.463662E+11 | 0.336728E+11 | 68130.59 | 17-FEB-14:10 | 50590.56 | 0.00 |
March | 0.00 | 0.00 | 0.579371E+11 | 0.415203E+11 | 79662.90 | 27-MAR-15:00 | 60498.67 | 0.00 |
April | 0.00 | 0.00 | 0.680722E+11 | 0.489200E+11 | 97113.72 | 13-APR-05:03 | 58880.74 | 0.00 |
May | 0.00 | 0.00 | 0.909602E+11 | 0.612871E+11 | 119247.89 | 30-MAY-04:02 | 78422.06 | 0.00 |
June | 0.00 | 0.00 | 0.102652E+12 | 0.649863E+11 | 131515.52 | 08-JUN-04:02 | 82181.47 | 0.00 |
July | 0.00 | 0.00 | 0.107926E+12 | 0.687543E+11 | 122259.22 | 31-JUL-04:02 | 79822.60 | 0.00 |
August | 0.00 | 0.00 | 0.107876E+12 | 0.676752E+11 | 128356.37 | 01-AUG-04:02 | 83913.53 | 0.00 |
September | 0.00 | 0.00 | 0.990279E+11 | 0.624097E+11 | 134095.91 | 19-SEP-04:02 | 81875.40 | 0.00 |
October | 0.00 | 0.00 | 0.877149E+11 | 0.573814E+11 | 135678.76 | 02-OCT-04:02 | 75624.63 | 0.00 |
November | 0.00 | 0.00 | 0.678795E+11 | 0.443593E+11 | 107827.43 | 30-NOV-06:03 | 57777.94 | 0.00 |
December | 0.00 | 0.00 | 0.477127E+11 | 0.324325E+11 | 76833.29 | 08-DEC-15:50 | 54359.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.927614E+12 | 0.613960E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.434892E+11 | 0.305617E+11 | 68130.59 | 50590.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107926E+12 | 0.687543E+11 | 135678.76 | 83913.53 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1234.94 | 4498.45 | 18-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1231.08 | 4486.70 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1276.68 | 4397.95 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1133.37 | 4208.06 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1119.67 | 4017.04 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1104.42 | 3828.64 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 989.21 | 3713.29 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1107.31 | 3799.89 | 31-AUG-11:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1068.21 | 3964.34 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1121.18 | 4181.62 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1195.21 | 4364.20 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1184.68 | 4474.93 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 1146.71 | ||||
Minimum of Months | 0.00 | 0.00 | 989.21 | 3713.29 | ||
Maximum of Months | 0.00 | 0.00 | 1276.68 | 4498.45 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.225717E+10 | 0.34 | 4454.68 | 02-JAN-15:10 | 1.06 |
February | 0.224030E+10 | 0.35 | 4245.81 | 21-FEB-17:00 | 1.03 |
March | 0.266844E+10 | 0.37 | 4498.27 | 27-MAR-15:40 | 1.07 |
April | 0.283187E+10 | 0.39 | 4749.41 | 17-APR-15:20 | 1.10 |
May | 0.363991E+10 | 0.44 | 10259.88 | 24-MAY-05:02 | 1.78 |
June | 0.382050E+10 | 0.46 | 10259.88 | 05-JUN-04:02 | 1.78 |
July | 0.407449E+10 | 0.47 | 10259.88 | 05-JUL-04:02 | 1.78 |
August | 0.432092E+10 | 0.49 | 10259.88 | 02-AUG-04:02 | 1.78 |
September | 0.395255E+10 | 0.47 | 10259.88 | 09-SEP-04:02 | 1.78 |
October | 0.385020E+10 | 0.45 | 10259.88 | 26-OCT-05:02 | 1.78 |
November | 0.309947E+10 | 0.40 | 6791.29 | 21-NOV-05:02 | 1.37 |
December | 0.233737E+10 | 0.34 | 5898.15 | 11-DEC-07:03 | 1.26 |
Annual Sum or Average | 0.390932E+11 | 0.41 | |||
Minimum of Months | 0.224030E+10 | 0.34 | 4245.81 | 1.03 | |
Maximum of Months | 0.432092E+10 | 0.49 | 10259.88 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172593E+10 | 0.31 | 3581.92 | 02-JAN-15:10 | 0.98 |
February | 0.175167E+10 | 0.33 | 3370.32 | 21-FEB-16:20 | 0.95 |
March | 0.217049E+10 | 0.35 | 3808.61 | 27-MAR-15:20 | 1.02 |
April | 0.232365E+10 | 0.37 | 3856.17 | 17-APR-15:20 | 1.03 |
May | 0.288755E+10 | 0.41 | 9321.69 | 08-MAY-05:01 | 1.78 |
June | 0.303548E+10 | 0.43 | 9321.69 | 06-JUN-05:02 | 1.78 |
July | 0.316569E+10 | 0.43 | 9321.69 | 03-JUL-04:02 | 1.78 |
August | 0.323319E+10 | 0.44 | 9321.69 | 01-AUG-04:02 | 1.78 |
September | 0.299098E+10 | 0.42 | 9321.69 | 11-SEP-04:02 | 1.78 |
October | 0.289971E+10 | 0.40 | 9321.69 | 23-OCT-05:02 | 1.78 |
November | 0.227740E+10 | 0.36 | 6921.40 | 04-NOV-05:03 | 1.47 |
December | 0.179621E+10 | 0.32 | 5216.53 | 09-DEC-06:03 | 1.24 |
Annual Sum or Average | 0.302580E+11 | 0.38 | |||
Minimum of Months | 0.172593E+10 | 0.31 | 3370.32 | 0.95 | |
Maximum of Months | 0.323319E+10 | 0.44 | 9321.69 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162759E+10 | 0.29 | 3391.32 | 02-JAN-15:00 | 0.87 |
February | 0.166188E+10 | 0.31 | 3184.80 | 21-FEB-16:20 | 0.84 |
March | 0.208378E+10 | 0.33 | 3839.24 | 27-MAR-15:20 | 0.93 |
April | 0.229196E+10 | 0.35 | 5126.41 | 13-APR-05:03 | 1.11 |
May | 0.287500E+10 | 0.38 | 9498.44 | 30-MAY-04:02 | 1.62 |
June | 0.303348E+10 | 0.40 | 10570.40 | 12-JUN-04:02 | 1.74 |
July | 0.319102E+10 | 0.40 | 10463.93 | 10-JUL-04:02 | 1.73 |
August | 0.317953E+10 | 0.40 | 9996.48 | 01-AUG-04:02 | 1.68 |
September | 0.291598E+10 | 0.39 | 10975.90 | 11-SEP-04:02 | 1.78 |
October | 0.271274E+10 | 0.36 | 9163.08 | 02-OCT-04:02 | 1.59 |
November | 0.210946E+10 | 0.33 | 5040.38 | 04-NOV-05:03 | 1.10 |
December | 0.169993E+10 | 0.30 | 3192.49 | 08-DEC-15:30 | 0.84 |
Annual Sum or Average | 0.293823E+11 | 0.35 | |||
Minimum of Months | 0.162759E+10 | 0.29 | 3184.80 | 0.84 | |
Maximum of Months | 0.319102E+10 | 0.40 | 10975.90 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.80 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.89 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.98 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.19 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.12 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.22 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.19 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.19 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.72 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 58.00 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.91 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.80 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.72 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.66 | 58.66 | 1234.94 | 4498.45 | 18-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.30 | 58.30 | 1231.08 | 4486.70 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.33 | 58.33 | 1276.68 | 4397.95 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.40 | 58.40 | 1133.37 | 4208.06 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.80 | 58.80 | 1119.67 | 4017.04 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.55 | 58.55 | 1104.42 | 3828.64 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.59 | 58.59 | 989.21 | 3713.29 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.60 | 58.60 | 1107.31 | 3799.89 | 31-AUG-11:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.57 | 58.57 | 1068.21 | 3964.34 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.87 | 57.87 | 1121.18 | 4181.62 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.42 | 58.42 | 1195.21 | 4364.20 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.34 | 58.34 | 1184.68 | 4474.93 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 1146.71 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.87 | 57.87 | 989.21 | 3713.29 | ||
Maximum of Months | 0.00 | 0.00 | 58.80 | 58.80 | 1276.68 | 4498.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.139277E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138883E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167306E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.188594E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.256391E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285990E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.307568E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.316977E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.289488E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.265196E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.206061E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146814E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.270855E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.138883E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.316977E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.112371E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116725E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143346E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.165532E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.222897E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.250558E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267474E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.268697E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.245674E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.221441E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.169051E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.121135E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230490E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.112371E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.268697E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.117355E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122766E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151117E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.176239E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.236984E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265201E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.284314E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.281720E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.256940E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.226826E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172750E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.127170E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241938E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117355E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.284314E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.225717E+10 | 0.515850E+11 | 0.234601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224030E+10 | 0.523569E+11 | 87147591.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266844E+10 | 0.630293E+11 | 0.176279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283187E+10 | 0.716338E+11 | 11069357.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363991E+10 | 0.962134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.382050E+10 | 0.108022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407449E+10 | 0.113747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.432092E+10 | 0.117816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395255E+10 | 0.108500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385020E+10 | 0.998494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309947E+10 | 0.788716E+11 | 42000188.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233737E+10 | 0.552225E+11 | 0.154052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390932E+11 | 0.101685E+13 | 0.705150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.224030E+10 | 0.515850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.432092E+10 | 0.117816E+12 | 0.234601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172593E+10 | 0.424811E+11 | 17849680.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175167E+10 | 0.445338E+11 | 40595797.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217049E+10 | 0.550279E+11 | 12491082.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232365E+10 | 0.636139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288755E+10 | 0.851445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303548E+10 | 0.965705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.316569E+10 | 0.101226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.323319E+10 | 0.102380E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299098E+10 | 0.941730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289971E+10 | 0.849030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227740E+10 | 0.660336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179621E+10 | 0.463221E+11 | 31640854.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302580E+11 | 0.882410E+12 | 0.102577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172593E+10 | 0.424811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.323319E+10 | 0.102380E+12 | 40595797.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162759E+10 | 0.434892E+11 | 0.271265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166188E+10 | 0.463662E+11 | 0.232841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208378E+10 | 0.579371E+11 | 0.140818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229196E+10 | 0.680722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.287500E+10 | 0.909602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303348E+10 | 0.102652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319102E+10 | 0.107926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317953E+10 | 0.107876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291598E+10 | 0.990279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271274E+10 | 0.877149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210946E+10 | 0.678795E+11 | 26955308.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169993E+10 | 0.477127E+11 | 0.316840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293823E+11 | 0.927614E+12 | 0.988720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162759E+10 | 0.434892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319102E+10 | 0.107926E+12 | 0.316840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.225717E+10 | 0.00 | 0.00 | 0.00 | 0.114359E+11 | 0.234601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224030E+10 | 0.00 | 0.00 | 0.00 | 0.115609E+11 | 87147591.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266844E+10 | 0.00 | 0.00 | 0.00 | 0.138859E+11 | 0.176279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283187E+10 | 0.00 | 0.00 | 0.00 | 0.160165E+11 | 11069357.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363991E+10 | 0.00 | 0.00 | 0.00 | 0.219992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.382050E+10 | 0.00 | 0.00 | 0.00 | 0.247785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407449E+10 | 0.00 | 0.00 | 0.00 | 0.266823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.432092E+10 | 0.00 | 0.00 | 0.00 | 0.273768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395255E+10 | 0.00 | 0.00 | 0.00 | 0.249963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385020E+10 | 0.00 | 0.00 | 0.00 | 0.226694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309947E+10 | 0.00 | 0.00 | 0.00 | 0.174646E+11 | 42000188.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233737E+10 | 0.00 | 0.00 | 0.00 | 0.121899E+11 | 0.154052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390932E+11 | 0.00 | 0.00 | 0.00 | 0.231056E+12 | 0.705150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.224030E+10 | 0.00 | 0.00 | 0.00 | 0.114359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.432092E+10 | 0.00 | 0.00 | 0.00 | 0.273768E+11 | 0.234601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.172593E+10 | 0.00 | 0.00 | 0.00 | 0.949331E+10 | 17849680.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175167E+10 | 0.00 | 0.00 | 0.00 | 0.988026E+10 | 40595797.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217049E+10 | 0.00 | 0.00 | 0.00 | 0.121516E+11 | 12491082.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232365E+10 | 0.00 | 0.00 | 0.00 | 0.142295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288755E+10 | 0.00 | 0.00 | 0.00 | 0.194021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303548E+10 | 0.00 | 0.00 | 0.00 | 0.220203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.316569E+10 | 0.00 | 0.00 | 0.00 | 0.235817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.323319E+10 | 0.00 | 0.00 | 0.00 | 0.236365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.299098E+10 | 0.00 | 0.00 | 0.00 | 0.215765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289971E+10 | 0.00 | 0.00 | 0.00 | 0.192444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227740E+10 | 0.00 | 0.00 | 0.00 | 0.146277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179621E+10 | 0.00 | 0.00 | 0.00 | 0.102857E+11 | 31640854.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302580E+11 | 0.00 | 0.00 | 0.00 | 0.200130E+12 | 0.102577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172593E+10 | 0.00 | 0.00 | 0.00 | 0.949331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.323319E+10 | 0.00 | 0.00 | 0.00 | 0.236365E+11 | 40595797.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162759E+10 | 0.00 | 0.00 | 0.00 | 0.983662E+10 | 0.271265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166188E+10 | 0.00 | 0.00 | 0.00 | 0.103819E+11 | 0.232841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208378E+10 | 0.00 | 0.00 | 0.00 | 0.128871E+11 | 0.140818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229196E+10 | 0.00 | 0.00 | 0.00 | 0.153319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.287500E+10 | 0.00 | 0.00 | 0.00 | 0.208234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303348E+10 | 0.00 | 0.00 | 0.00 | 0.234867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319102E+10 | 0.00 | 0.00 | 0.00 | 0.252404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317953E+10 | 0.00 | 0.00 | 0.00 | 0.249925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291598E+10 | 0.00 | 0.00 | 0.00 | 0.227780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271274E+10 | 0.00 | 0.00 | 0.00 | 0.199699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210946E+10 | 0.00 | 0.00 | 0.00 | 0.151386E+11 | 26955308.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169993E+10 | 0.00 | 0.00 | 0.00 | 0.107003E+11 | 0.316840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293823E+11 | 0.00 | 0.00 | 0.00 | 0.211567E+12 | 0.988720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.162759E+10 | 0.00 | 0.00 | 0.00 | 0.983662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319102E+10 | 0.00 | 0.00 | 0.00 | 0.252404E+11 | 0.316840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215340E+09 | 0.324694E+10 | 0.00 | 21110608.41 | 0.419174E+09 | 0.00 | 0.280364E+10 | 0.00 | 0.38 |
February | 0.109278E+09 | 0.374213E+10 | 0.00 | 14118009.09 | 0.316603E+09 | 0.00 | 0.146000E+10 | 0.00 | 0.36 |
March | 99712619.10 | 0.508323E+10 | 0.00 | 16471018.27 | 0.496738E+09 | 0.00 | 0.219649E+10 | 0.00 | 0.38 |
April | 10132848.45 | 0.678542E+10 | 0.00 | 4288319.80 | 0.990855E+09 | 0.00 | 0.363148E+09 | 0.00 | 0.36 |
May | 0.00 | 0.119931E+11 | 0.00 | 0.00 | 0.192604E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.159408E+11 | 0.00 | 0.00 | 0.225371E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.160743E+11 | 0.00 | 0.00 | 0.364628E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.172972E+11 | 0.00 | 0.00 | 0.253648E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.148714E+11 | 0.00 | 0.00 | 0.310429E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.00 | 0.120750E+11 | 0.00 | 0.00 | 0.248788E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 0.119677E+09 | 0.897957E+10 | 0.00 | 4881358.75 | 0.936705E+09 | 0.00 | 0.316242E+09 | 0.00 | 0.35 |
December | 95221250.85 | 0.380246E+10 | 0.00 | 18995631.15 | 0.871063E+09 | 0.00 | 0.245185E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.649361E+09 | 0.119892E+12 | 0.00 | 79864945.46 | 0.199858E+11 | 0.00 | 0.959138E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.324694E+10 | 0.00 | 0.00 | 0.316603E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.215340E+09 | 0.172972E+11 | 0.00 | 21110608.41 | 0.364628E+10 | 0.00 | 0.280364E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102332E+10 | 0.219373E+10 | 0.00 | 5735185.57 | 0.104826E+10 | 0.00 | 0.113567E+10 | 0.00 | 0.30 |
February | 0.551013E+09 | 0.266434E+10 | 0.00 | 5403545.81 | 0.971989E+09 | 0.00 | 0.668581E+09 | 0.00 | 0.30 |
March | 0.595585E+09 | 0.380736E+10 | 0.00 | 5774947.42 | 0.119644E+10 | 0.00 | 0.108450E+10 | 0.00 | 0.32 |
April | 33165573.38 | 0.550078E+10 | 0.00 | 2414096.52 | 0.144116E+10 | 0.00 | 0.249954E+09 | 0.00 | 0.31 |
May | 0.00 | 0.105219E+11 | 0.00 | 0.00 | 0.220459E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.143489E+11 | 0.00 | 0.00 | 0.278316E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.147346E+11 | 0.00 | 0.00 | 0.394905E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.157395E+11 | 0.00 | 0.00 | 0.303163E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.135589E+11 | 0.00 | 0.00 | 0.328255E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.108190E+11 | 0.00 | 0.00 | 0.246579E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.206690E+09 | 0.775415E+10 | 0.00 | 1496954.63 | 0.130587E+10 | 0.00 | 97375726.08 | 0.00 | 0.30 |
December | 0.646983E+09 | 0.250944E+10 | 0.00 | 6617095.94 | 0.176629E+10 | 0.00 | 0.116958E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.305676E+10 | 0.104153E+12 | 0.00 | 27441825.89 | 0.254468E+11 | 0.00 | 0.440567E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.219373E+10 | 0.00 | 0.00 | 0.971989E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.102332E+10 | 0.157395E+11 | 0.00 | 6617095.94 | 0.394905E+10 | 0.00 | 0.116958E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113129E+10 | 0.151223E+10 | 0.00 | 2911894.55 | 0.189868E+10 | 0.00 | 0.673112E+09 | 0.00 | 0.30 |
February | 0.566643E+09 | 0.212502E+10 | 0.00 | 3574439.12 | 0.153871E+10 | 912587.15 | 0.449194E+09 | 0.00 | 0.30 |
March | 0.768426E+09 | 0.339226E+10 | 0.00 | 4001055.97 | 0.158464E+10 | 0.00 | 0.729554E+09 | 0.00 | 0.31 |
April | 36036785.14 | 0.492838E+10 | 0.00 | 2070438.73 | 0.184371E+10 | 0.00 | 0.207198E+09 | 0.00 | 0.31 |
May | 0.00 | 0.997370E+10 | 0.00 | 0.00 | 0.236784E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.137829E+11 | 0.00 | 0.00 | 0.284339E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.141356E+11 | 0.00 | 0.00 | 0.393582E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.150872E+11 | 0.00 | 0.00 | 0.319558E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.130559E+11 | 0.00 | 0.00 | 0.329859E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.100729E+11 | 0.00 | 0.00 | 0.287933E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
November | 0.202209E+09 | 0.686067E+10 | 0.00 | 799416.90 | 0.214585E+10 | 0.00 | 46707669.08 | 0.00 | 0.29 |
December | 0.851245E+09 | 0.197200E+10 | 0.00 | 3450945.26 | 0.237733E+10 | 0.00 | 0.601357E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.355585E+10 | 0.968988E+11 | 0.00 | 16808190.53 | 0.299095E+11 | 912587.15 | 0.270712E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.151223E+10 | 0.00 | 0.00 | 0.153871E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.113129E+10 | 0.150872E+11 | 0.00 | 4001055.97 | 0.393582E+10 | 912587.15 | 0.729554E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.314058E+09 | 0.368111E+09 | 19259.52 | 262406.18 | 0.386439E+09 | 11178777.80 | 48870241.21 | 48.88 | 0.30 |
February | 0.135763E+09 | 0.578153E+09 | 74051.46 | 693149.49 | 0.289142E+09 | 17942745.57 | 63420709.48 | 2578.92 | 0.32 |
March | 0.222146E+09 | 0.896653E+09 | 0.00 | 617839.61 | 0.313853E+09 | 6722573.86 | 82622499.33 | 0.00 | 0.34 |
April | 9609767.57 | 0.139583E+10 | 0.00 | 463480.39 | 0.345564E+09 | 0.00 | 45482062.48 | 0.00 | 0.37 |
May | 0.00 | 0.315961E+10 | 0.00 | 0.00 | 0.395796E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.470636E+10 | 0.00 | 0.00 | 0.455752E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.506117E+10 | 0.00 | 0.00 | 0.588145E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.489453E+10 | 0.00 | 0.00 | 0.488581E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.406681E+10 | 0.00 | 0.00 | 0.594060E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.276457E+10 | 0.00 | 0.00 | 0.568111E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 42349892.43 | 0.180722E+10 | 0.00 | 178527.40 | 0.386585E+09 | 1462312.41 | 9651020.48 | 0.00 | 0.33 |
December | 0.236802E+09 | 0.521494E+09 | 74035.49 | 348386.82 | 0.467556E+09 | 12098180.91 | 52416608.99 | 4329.56 | 0.30 |
Annual Sum or Average | 0.960729E+09 | 0.302205E+11 | 167346.47 | 2563789.89 | 0.527958E+10 | 49404590.55 | 0.302463E+09 | 6957.35 | 0.38 |
Minimum of Months | 0.00 | 0.368111E+09 | 0.00 | 0.00 | 0.289142E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.314058E+09 | 0.506117E+10 | 74051.46 | 693149.49 | 0.594060E+09 | 17942745.57 | 82622499.33 | 4329.56 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173692E+09 | 0.396445E+09 | 50321.48 | 721948.84 | 0.270662E+09 | 5373421.93 | 0.145642E+09 | 83.44 | 0.42 |
February | 0.113902E+09 | 0.545749E+09 | 62966.22 | 867139.09 | 0.233612E+09 | 9112360.90 | 71234635.70 | 1930.06 | 0.46 |
March | 92073447.55 | 0.883807E+09 | 0.00 | 1314252.38 | 0.229522E+09 | 4279159.23 | 0.218340E+09 | 0.00 | 0.51 |
April | 6671096.05 | 0.141257E+10 | 0.00 | 523458.63 | 0.264379E+09 | 0.00 | 49505045.49 | 0.00 | 0.56 |
May | 0.00 | 0.269274E+10 | 0.00 | 0.00 | 0.324522E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.383987E+10 | 0.00 | 0.00 | 0.354254E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.419443E+10 | 0.00 | 0.00 | 0.450131E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.400186E+10 | 0.00 | 0.00 | 0.461691E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.351695E+10 | 0.00 | 0.00 | 0.454825E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.250680E+10 | 0.00 | 0.00 | 0.451917E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 34601995.94 | 0.153431E+10 | 0.00 | 206227.08 | 0.337510E+09 | 270118.95 | 10176426.01 | 0.00 | 0.45 |
December | 0.165922E+09 | 0.461695E+09 | 275993.20 | 398636.46 | 0.399420E+09 | 9845763.04 | 78903692.32 | 7612.14 | 0.41 |
Annual Sum or Average | 0.586862E+09 | 0.259872E+11 | 389280.90 | 4031662.48 | 0.423244E+10 | 28880824.05 | 0.573802E+09 | 9625.65 | 0.52 |
Minimum of Months | 0.00 | 0.396445E+09 | 0.00 | 0.00 | 0.229522E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.173692E+09 | 0.419443E+10 | 275993.20 | 1314252.38 | 0.461691E+09 | 9845763.04 | 0.218340E+09 | 7612.14 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151758E+09 | 0.965556E+09 | 0.00 | 4181118.77 | 0.207341E+09 | 3091330.30 | 0.539915E+09 | 0.00 | 0.51 |
February | 87669156.57 | 0.109692E+10 | 0.00 | 2776064.47 | 0.174987E+09 | 12027246.34 | 0.259809E+09 | 0.00 | 0.49 |
March | 0.130637E+09 | 0.133387E+10 | 0.00 | 2597082.34 | 0.223909E+09 | 5952450.86 | 0.333052E+09 | 0.00 | 0.47 |
April | 9164448.21 | 0.168801E+10 | 0.00 | 634997.38 | 0.316738E+09 | 0.00 | 60578957.41 | 0.00 | 0.42 |
May | 0.00 | 0.310678E+10 | 0.00 | 0.00 | 0.416204E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.442055E+10 | 0.00 | 0.00 | 0.486577E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.487734E+10 | 0.00 | 0.00 | 0.617472E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.523856E+10 | 0.00 | 0.00 | 0.465673E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.514214E+10 | 0.00 | 0.00 | 0.477383E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.433975E+10 | 0.00 | 0.00 | 0.350568E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 25269827.91 | 0.305250E+10 | 0.00 | 1116592.47 | 0.222237E+09 | 247653.19 | 50150031.54 | 0.00 | 0.51 |
December | 0.119441E+09 | 0.134353E+10 | 71295.64 | 2976293.11 | 0.254399E+09 | 7947328.85 | 0.416559E+09 | 86.55 | 0.50 |
Annual Sum or Average | 0.523939E+09 | 0.366055E+11 | 71295.64 | 14282148.54 | 0.421349E+10 | 29266009.53 | 0.166006E+10 | 86.55 | 0.48 |
Minimum of Months | 0.00 | 0.965556E+09 | 0.00 | 0.00 | 0.174987E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.151758E+09 | 0.523856E+10 | 71295.64 | 4181118.77 | 0.617472E+09 | 12027246.34 | 0.539915E+09 | 86.55 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253028E+09 | 0.303120E+09 | 199829.04 | 740798.47 | 0.400744E+09 | 9783704.59 | 0.132300E+09 | 1225.43 | 0.47 |
February | 0.112673E+09 | 0.475046E+09 | 132762.96 | 987407.82 | 0.327836E+09 | 18382898.54 | 0.103073E+09 | 2710.53 | 0.49 |
March | 0.183745E+09 | 0.802823E+09 | 0.00 | 1327860.70 | 0.327640E+09 | 7208864.67 | 0.166634E+09 | 0.00 | 0.55 |
April | 10527588.05 | 0.131902E+10 | 0.00 | 483192.17 | 0.360276E+09 | 0.00 | 52666804.50 | 0.00 | 0.57 |
May | 0.00 | 0.256867E+10 | 0.00 | 0.00 | 0.456813E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.346675E+10 | 0.00 | 0.00 | 0.524165E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.388979E+10 | 0.00 | 0.00 | 0.631197E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.391248E+10 | 0.00 | 0.00 | 0.595712E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.320714E+10 | 0.00 | 0.00 | 0.627015E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.227896E+10 | 0.00 | 0.00 | 0.632180E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 39186132.80 | 0.143363E+10 | 0.00 | 195101.20 | 0.493883E+09 | 1253740.97 | 13457704.08 | 0.00 | 0.47 |
December | 0.196594E+09 | 0.476745E+09 | 238789.69 | 607684.21 | 0.470427E+09 | 13399069.03 | 94162824.37 | 9145.97 | 0.47 |
Annual Sum or Average | 0.795752E+09 | 0.241342E+11 | 571381.69 | 4342044.58 | 0.584789E+10 | 50028277.80 | 0.562295E+09 | 13081.93 | 0.53 |
Minimum of Months | 0.00 | 0.303120E+09 | 0.00 | 0.00 | 0.327640E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.253028E+09 | 0.391248E+10 | 238789.69 | 1327860.70 | 0.632180E+09 | 18382898.54 | 0.166634E+09 | 9145.97 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354920E+09 | 0.421147E+09 | 0.00 | 500986.11 | 0.199722E+09 | 0.00 | 91956887.80 | 0.00 | 0.28 |
February | 0.176527E+09 | 0.540477E+09 | 0.00 | 720475.21 | 0.161017E+09 | 324611.74 | 68725941.37 | 0.00 | 0.28 |
March | 0.256695E+09 | 0.750086E+09 | 0.00 | 498990.22 | 0.229457E+09 | 0.00 | 67189145.33 | 0.00 | 0.29 |
April | 12071792.34 | 0.115981E+10 | 0.00 | 413979.62 | 0.290649E+09 | 0.00 | 44372416.73 | 0.00 | 0.31 |
May | 0.00 | 0.250271E+10 | 0.00 | 0.00 | 0.507389E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.368906E+10 | 0.00 | 0.00 | 0.630545E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.404374E+10 | 0.00 | 0.00 | 0.848903E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.406724E+10 | 0.00 | 0.00 | 0.631628E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.340520E+10 | 0.00 | 0.00 | 0.765256E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.240766E+10 | 0.00 | 0.00 | 0.640915E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 51294535.39 | 0.163152E+10 | 0.00 | 358944.66 | 0.271394E+09 | 0.00 | 17060632.49 | 0.00 | 0.30 |
December | 0.263379E+09 | 0.552071E+09 | 0.00 | 730970.81 | 0.305134E+09 | 0.00 | 0.107620E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.111489E+10 | 0.251707E+11 | 0.00 | 3224346.63 | 0.548201E+10 | 324611.74 | 0.396925E+09 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.421147E+09 | 0.00 | 0.00 | 0.161017E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.354920E+09 | 0.406724E+10 | 0.00 | 730970.81 | 0.848903E+09 | 324611.74 | 0.107620E+09 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177254E+09 | 0.423695E+09 | 0.00 | 1396263.93 | 0.107140E+09 | 0.00 | 0.204387E+09 | 0.00 | 0.38 |
February | 96374797.47 | 0.508550E+09 | 0.00 | 1342370.86 | 94252454.54 | 248646.47 | 0.118689E+09 | 0.00 | 0.40 |
March | 89988611.55 | 0.773315E+09 | 0.00 | 1637241.68 | 0.114772E+09 | 0.00 | 0.234651E+09 | 0.00 | 0.44 |
April | 6994505.63 | 0.120027E+10 | 0.00 | 558931.89 | 0.176119E+09 | 0.00 | 53811408.83 | 0.00 | 0.46 |
May | 0.00 | 0.220679E+10 | 0.00 | 0.00 | 0.334766E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.315897E+10 | 0.00 | 0.00 | 0.360694E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.357556E+10 | 0.00 | 0.00 | 0.437850E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.347774E+10 | 0.00 | 0.00 | 0.376782E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.305120E+10 | 0.00 | 0.00 | 0.454243E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.218180E+10 | 0.00 | 0.00 | 0.429868E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 32429684.56 | 0.136325E+10 | 0.00 | 479996.50 | 0.195974E+09 | 0.00 | 26042512.78 | 0.00 | 0.40 |
December | 0.145345E+09 | 0.481166E+09 | 0.00 | 982129.05 | 0.222306E+09 | 0.00 | 0.152772E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.548386E+09 | 0.224023E+11 | 0.00 | 6396933.91 | 0.330477E+10 | 248646.47 | 0.790353E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.423695E+09 | 0.00 | 0.00 | 94252454.54 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.177254E+09 | 0.357556E+10 | 0.00 | 1637241.68 | 0.454243E+09 | 248646.47 | 0.234651E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191583E+09 | 0.934860E+09 | 5283.32 | 3561071.17 | 96896193.72 | 59433373.79 | 0.412591E+09 | 577.39 | 0.45 |
February | 0.121140E+09 | 0.101601E+10 | 30145.27 | 3186461.68 | 92833202.21 | 26396948.01 | 0.210856E+09 | 236.25 | 0.45 |
March | 0.186741E+09 | 0.124505E+10 | 0.00 | 1707692.97 | 0.152232E+09 | 60435159.77 | 0.163853E+09 | 0.00 | 0.41 |
April | 13882605.79 | 0.159109E+10 | 0.00 | 444780.57 | 0.288555E+09 | 1749221.73 | 44964107.99 | 0.00 | 0.38 |
May | 0.00 | 0.295578E+10 | 0.00 | 0.00 | 0.518504E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.423405E+10 | 0.00 | 0.00 | 0.611776E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.473734E+10 | 0.00 | 0.00 | 0.840587E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.534225E+10 | 0.00 | 0.00 | 0.516888E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.502825E+10 | 0.00 | 0.00 | 0.530285E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.428416E+10 | 0.00 | 0.00 | 0.343931E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 24919628.48 | 0.292084E+10 | 0.00 | 1426027.12 | 0.175626E+09 | 11221137.49 | 58007235.58 | 0.00 | 0.48 |
December | 0.155693E+09 | 0.130637E+10 | 557897.87 | 2297691.41 | 0.145261E+09 | 47181118.85 | 0.324543E+09 | 5998.66 | 0.45 |
Annual Sum or Average | 0.693959E+09 | 0.355961E+11 | 593326.46 | 12623724.92 | 0.431337E+10 | 0.206417E+09 | 0.121481E+10 | 6812.30 | 0.45 |
Minimum of Months | 0.00 | 0.934860E+09 | 0.00 | 0.00 | 92833202.21 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.191583E+09 | 0.534225E+10 | 557897.87 | 3561071.17 | 0.840587E+09 | 60435159.77 | 0.412591E+09 | 5998.66 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240332E+09 | 0.369243E+09 | 0.00 | 1022107.75 | 0.143579E+09 | 0.00 | 0.160961E+09 | 0.00 | 0.38 |
February | 0.126873E+09 | 0.488076E+09 | 0.00 | 1166308.12 | 0.109523E+09 | 262986.72 | 96593030.62 | 0.00 | 0.39 |
March | 0.169475E+09 | 0.760924E+09 | 0.00 | 1251242.87 | 0.131483E+09 | 0.00 | 0.141592E+09 | 0.00 | 0.44 |
April | 8841467.92 | 0.121334E+10 | 0.00 | 484125.83 | 0.175091E+09 | 0.00 | 49027915.18 | 0.00 | 0.46 |
May | 0.00 | 0.218897E+10 | 0.00 | 0.00 | 0.339774E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.282542E+10 | 0.00 | 0.00 | 0.456591E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.330777E+10 | 0.00 | 0.00 | 0.555307E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.345153E+10 | 0.00 | 0.00 | 0.404697E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.283944E+10 | 0.00 | 0.00 | 0.491888E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.210694E+10 | 0.00 | 0.00 | 0.429730E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 40013626.25 | 0.135349E+10 | 0.00 | 359041.28 | 0.210062E+09 | 0.00 | 18045910.25 | 0.00 | 0.39 |
December | 0.177739E+09 | 0.519585E+09 | 0.00 | 976543.21 | 0.226453E+09 | 0.00 | 0.145839E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.763275E+09 | 0.214247E+11 | 0.00 | 5259369.05 | 0.367418E+10 | 262986.72 | 0.612059E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.369243E+09 | 0.00 | 0.00 | 0.109523E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.240332E+09 | 0.345153E+10 | 0.00 | 1251242.87 | 0.555307E+09 | 262986.72 | 0.160961E+09 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367800E+09 | 0.490116E+09 | 0.00 | 360720.99 | 0.226606E+09 | 520340.69 | 69649749.15 | 0.00 | 0.30 |
February | 0.168276E+09 | 0.675497E+09 | 0.00 | 769841.50 | 0.191791E+09 | 5553382.88 | 79373898.50 | 0.00 | 0.32 |
March | 0.259801E+09 | 0.101551E+10 | 0.00 | 586517.01 | 0.213441E+09 | 371726.15 | 78058990.31 | 0.00 | 0.34 |
April | 12708810.92 | 0.152772E+10 | 0.00 | 453141.92 | 0.280991E+09 | 0.00 | 49059782.86 | 0.00 | 0.37 |
May | 0.00 | 0.330617E+10 | 0.00 | 0.00 | 0.417425E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.489151E+10 | 0.00 | 0.00 | 0.498097E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.522413E+10 | 0.00 | 0.00 | 0.694935E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.507829E+10 | 0.00 | 0.00 | 0.527498E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.421821E+10 | 0.00 | 0.00 | 0.626416E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.294564E+10 | 0.00 | 0.00 | 0.505849E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 52172129.80 | 0.195635E+10 | 0.00 | 225434.05 | 0.271404E+09 | 0.00 | 11741155.09 | 0.00 | 0.33 |
December | 0.281719E+09 | 0.625464E+09 | 0.00 | 529500.04 | 0.351146E+09 | 394803.03 | 82136347.62 | 0.00 | 0.30 |
Annual Sum or Average | 0.114248E+10 | 0.319546E+11 | 0.00 | 2925155.50 | 0.480560E+10 | 6840252.76 | 0.370020E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.490116E+09 | 0.00 | 0.00 | 0.191791E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.367800E+09 | 0.522413E+10 | 0.00 | 769841.50 | 0.694935E+09 | 5553382.88 | 82136347.62 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.207977E+09 | 0.421850E+09 | 0.00 | 940377.38 | 0.203511E+09 | 542562.66 | 0.189071E+09 | 0.00 | 0.43 |
February | 0.138089E+09 | 0.578337E+09 | 0.00 | 1065721.18 | 0.179998E+09 | 629619.73 | 93620702.03 | 0.00 | 0.46 |
March | 0.113673E+09 | 0.922559E+09 | 0.00 | 1448921.36 | 0.176582E+09 | 645752.31 | 0.255241E+09 | 0.00 | 0.51 |
April | 10570459.90 | 0.147994E+10 | 0.00 | 516054.07 | 0.221478E+09 | 0.00 | 53375696.79 | 0.00 | 0.55 |
May | 0.00 | 0.278839E+10 | 0.00 | 0.00 | 0.326650E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.395277E+10 | 0.00 | 0.00 | 0.373245E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.435271E+10 | 0.00 | 0.00 | 0.466262E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.417950E+10 | 0.00 | 0.00 | 0.406439E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.360756E+10 | 0.00 | 0.00 | 0.457279E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.258187E+10 | 0.00 | 0.00 | 0.415472E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 39034660.34 | 0.160370E+10 | 0.00 | 296433.34 | 0.244077E+09 | 0.00 | 17974257.44 | 0.00 | 0.45 |
December | 0.197778E+09 | 0.512759E+09 | 0.00 | 541389.42 | 0.327462E+09 | 805891.72 | 0.114850E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.707123E+09 | 0.269819E+11 | 0.00 | 4808896.75 | 0.379845E+10 | 2623826.41 | 0.724132E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.421850E+09 | 0.00 | 0.00 | 0.176582E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.207977E+09 | 0.435271E+10 | 0.00 | 1448921.36 | 0.466262E+09 | 805891.72 | 0.255241E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181371E+09 | 0.106447E+10 | 0.00 | 4582859.39 | 99283957.99 | 0.00 | 0.611871E+09 | 0.00 | 0.52 |
February | 0.122630E+09 | 0.122204E+10 | 0.00 | 3181103.17 | 99556960.58 | 837456.12 | 0.270023E+09 | 0.00 | 0.50 |
March | 0.152748E+09 | 0.148210E+10 | 0.00 | 2662745.22 | 0.142066E+09 | 134683.90 | 0.343340E+09 | 0.00 | 0.48 |
April | 14206609.40 | 0.185723E+10 | 0.00 | 610992.88 | 0.258488E+09 | 0.00 | 61363001.63 | 0.00 | 0.43 |
May | 0.00 | 0.328553E+10 | 0.00 | 0.00 | 0.411482E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.460188E+10 | 0.00 | 0.00 | 0.524741E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.505473E+10 | 0.00 | 0.00 | 0.709105E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.548410E+10 | 0.00 | 0.00 | 0.479671E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.540464E+10 | 0.00 | 0.00 | 0.473682E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.459623E+10 | 0.00 | 0.00 | 0.300952E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 31540409.70 | 0.319359E+10 | 0.00 | 1250371.89 | 0.154279E+09 | 0.00 | 56588837.03 | 0.00 | 0.51 |
December | 0.148662E+09 | 0.144691E+10 | 0.00 | 3410848.35 | 0.182267E+09 | 153840.24 | 0.501432E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.651159E+09 | 0.386934E+11 | 0.00 | 15698920.91 | 0.383557E+10 | 1125980.26 | 0.184462E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.106447E+10 | 0.00 | 0.00 | 99283957.99 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.181371E+09 | 0.548410E+10 | 0.00 | 4582859.39 | 0.709105E+09 | 837456.12 | 0.611871E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295751E+09 | 0.372114E+09 | 0.00 | 836194.93 | 0.263110E+09 | 1008441.41 | 0.142878E+09 | 0.00 | 0.45 |
February | 0.145982E+09 | 0.572842E+09 | 0.00 | 1059909.53 | 0.200320E+09 | 4972511.20 | 0.104949E+09 | 0.00 | 0.47 |
March | 0.208500E+09 | 0.905881E+09 | 0.00 | 1272085.59 | 0.221179E+09 | 517636.70 | 0.154995E+09 | 0.00 | 0.54 |
April | 13766289.20 | 0.149297E+10 | 0.00 | 461302.81 | 0.245284E+09 | 0.00 | 53079798.81 | 0.00 | 0.56 |
May | 0.00 | 0.280233E+10 | 0.00 | 0.00 | 0.357786E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.367731E+10 | 0.00 | 0.00 | 0.467870E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.414594E+10 | 0.00 | 0.00 | 0.582948E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.422042E+10 | 0.00 | 0.00 | 0.456382E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.341584E+10 | 0.00 | 0.00 | 0.523472E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.249097E+10 | 0.00 | 0.00 | 0.466542E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 46548675.45 | 0.159509E+10 | 0.00 | 240895.11 | 0.299494E+09 | 0.00 | 14379024.46 | 0.00 | 0.46 |
December | 0.242803E+09 | 0.564292E+09 | 0.00 | 736986.55 | 0.338558E+09 | 1019110.95 | 0.108165E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.953351E+09 | 0.262560E+11 | 0.00 | 4607374.53 | 0.442294E+10 | 7517700.26 | 0.578446E+09 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.372114E+09 | 0.00 | 0.00 | 0.200320E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.295751E+09 | 0.422042E+10 | 0.00 | 1272085.59 | 0.582948E+09 | 4972511.20 | 0.154995E+09 | 0.00 | 0.59 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.198796E+12 | 0.354701E+09 | 0.00 | -0.892216E+10 | 0.168321E+12 |
February | 0.210590E+12 | -926316293.6 | 0.00 | -0.168553E+11 | 0.175080E+12 |
March | 0.283083E+12 | -0.195506E+10 | 0.00 | -0.306876E+11 | 0.214919E+12 |
April | 0.300141E+12 | -0.417613E+10 | 0.00 | -0.596431E+11 | 0.248898E+12 |
May | 0.284498E+12 | -0.939087E+10 | 0.00 | -0.115515E+12 | 0.334543E+12 |
June | 0.254608E+12 | -0.108107E+11 | 0.00 | -0.155639E+12 | 0.377529E+12 |
July | 0.278067E+12 | -0.104619E+11 | 0.00 | -0.169514E+12 | 0.398404E+12 |
August | 0.302204E+12 | -0.118183E+11 | 0.00 | -0.171257E+12 | 0.404078E+12 |
September | 0.232691E+12 | -0.100845E+11 | 0.00 | -0.154364E+12 | 0.371052E+12 |
October | 0.234597E+12 | -0.861138E+10 | 0.00 | -0.127208E+12 | 0.334351E+12 |
November | 0.178014E+12 | -0.484085E+10 | 0.00 | -0.758431E+11 | 0.260016E+12 |
December | 0.192465E+12 | -838758807.3 | 0.00 | -0.312551E+11 | 0.182433E+12 |
Annual Sum or Average | 0.294975E+13 | -0.735601E+11 | 0.00 | -0.111670E+13 | 0.346962E+13 |
Minimum of Months | 0.178014E+12 | -0.118183E+11 | 0.00 | -0.171257E+12 | 0.168321E+12 |
Maximum of Months | 0.302204E+12 | 0.354701E+09 | 0.00 | -0.892216E+10 | 0.404078E+12 |