Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:20:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1534.55 | 308.01 | 308.01 |
Net Site Energy | 1534.55 | 308.01 | 308.01 |
Total Source Energy | 4387.25 | 880.59 | 880.59 |
Net Source Energy | 4387.25 | 880.59 | 880.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 226.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 70.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 303.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 79.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1307.63 | 226.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 226.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 70.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 303.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 79.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 226.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 70.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 303.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 79.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 41.23 | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 262.46 | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 41.23 | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 262.46 | 45.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1307.629 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1307.629 | 100.00 |
Total On-Site and Utility Electric Sources | 1307.629 | 100.00 |
Total Electricity End Uses | 1307.629 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 306.50 |
Time Setpoint Not Met During Occupied Cooling | 45.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1700.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:20 | 26-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 185997.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 53036.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27002.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4248.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 153056.31 | 185997.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 185997.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 53036.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27002.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4248.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 245.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 222.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 962.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 252.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 171.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4141.26 | 245.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 193.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 831.21 | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 193.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 831.21 | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.73 | 0.274048 | 0.285000 | 0.779406 | 0.730794 | 0.500000 | 0.001390 | 0.000116 | 0.779406 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.21 | 0.339235 | 0.346000 | 0.764400 | 0.904627 | 0.500000 | 0.001123 | 0.000174 | 0.764400 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.25 | 0.332505 | 0.350000 | 0.788887 | 0.886681 | 0.500000 | 0.001146 | 0.000272 | 0.938507 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.628908 | 0.251216 | 0.264000 | 0.166032 | 0.669909 | 0.500000 | 0.001517 | 0.000123 | 0.426413 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.803839 | 0.124430 | 0.200000 | 0.160768 | 0.331814 | 0.500000 | 0.003062 | 0.000081 | 0.278819 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.20 | 0.131296 | 0.200000 | 0.240665 | 0.350122 | 0.500000 | 0.002902 | 0.000123 | 0.423699 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.877907 | 0.113925 | 0.200000 | 0.175581 | 0.303799 | 0.500000 | 0.003344 | 0.000080 | 0.277248 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.507654 | 0.311219 | 0.323000 | 0.163972 | 0.829918 | 0.500000 | 0.001224 | 0.000092 | 0.318765 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.667855 | 0.149766 | 0.200000 | 0.133571 | 0.399375 | 0.500000 | 0.002544 | 0.000061 | 0.211298 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.992249 | 0.159226 | 0.200000 | 0.198450 | 0.424602 | 0.500000 | 0.002393 | 0.000091 | 0.316196 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.737320 | 0.135647 | 0.200000 | 0.147464 | 0.361726 | 0.500000 | 0.002809 | 0.000061 | 0.209618 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.557174 | 0.283559 | 0.289000 | 0.161023 | 0.756157 | 0.500000 | 0.001344 | 0.000096 | 0.332205 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.804107 | 0.124389 | 0.200000 | 0.160821 | 0.331703 | 0.500000 | 0.003063 | 0.000063 | 0.218926 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.12 | 0.141127 | 0.200000 | 0.223900 | 0.376339 | 0.500000 | 0.002700 | 0.000095 | 0.329484 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.820951 | 0.121829 | 0.200000 | 0.164190 | 0.324876 | 0.500000 | 0.003127 | 0.000063 | 0.217419 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13240.10 | 0.000116 | 287.10 |
CORE_MID VAV BOX REHEAT COIL | 19904.87 | 0.000174 | 479.13 |
CORE_TOP VAV BOX REHEAT COIL | 31102.57 | 0.000272 | 821.31 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14094.43 | 0.000123 | 371.74 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9215.29 | 0.000081 | 243.04 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14004.90 | 0.000123 | 369.38 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9163.45 | 0.000080 | 241.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10543.08 | 0.000092 | 278.15 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6987.79 | 0.000061 | 184.34 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10458.32 | 0.000091 | 275.92 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6932.38 | 0.000061 | 182.88 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10986.49 | 0.000096 | 289.84 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7239.44 | 0.000063 | 190.98 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10896.75 | 0.000095 | 287.47 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7189.74 | 0.000063 | 189.67 |
PACU_VAV_BOT HEATING COIL | 21468.83 | 0.000188 | 361.65 |
PACU_VAV_MID HEATING COIL | 22456.55 | 0.000196 | 374.86 |
PACU_VAV_TOP HEATING COIL | 21967.65 | 0.000192 | 370.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.82 | 1.42 | 5.64 | 1.48 | 4.93 | 4.93 | 0.300000 | 0.300535 | 4.93 |
PACU_VAV_MID | 2.76 | 1.47 | 5.51 | 1.63 | 4.59 | 4.59 | 0.300000 | 0.354217 | 4.59 |
PACU_VAV_TOP | 2.88 | 1.53 | 5.77 | 2.34 | 5.17 | 5.17 | 0.300000 | 0.453897 | 5.17 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.93 |
PACU_VAV_MID_OA_CONTROLLER | 4.59 |
PACU_VAV_TOP_OA_CONTROLLER | 5.17 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.93 | 86560.51 | 0.800374 | 1.64 | 28850.62 | 0.800374 |
PACU_VAV_MID COOLING COIL | 4.59 | 81291.90 | 0.800621 | 1.53 | 27094.59 | 0.800621 |
PACU_VAV_TOP COOLING COIL | 5.17 | 90239.51 | 0.800388 | 1.72 | 30076.83 | 0.800388 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.93 |
PACU_VAV_MID FAN | 4.59 |
PACU_VAV_TOP FAN | 5.17 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000188 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000196 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000192 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002168 | 0.260199 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002168 | 653.00 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 247852.63 | 247852.63 | 0.002168 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2607E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2676E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4263E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4324E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6683E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7157E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1452E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1682E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1627 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9501E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1872 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1164 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1063 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7176E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5786E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7177E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2607E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2679E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4263E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4327E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6683E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7175E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1449E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1679E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2506E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2965E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8499E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0038E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9161E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5140E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3760E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5338E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5435E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5712E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2168E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2369E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8248E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8314E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8379E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8458E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6999E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7581E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9147E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9618E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3567E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3902E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1449E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1679E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6186E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6474E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5656E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0238E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2371E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3569E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5786E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7177E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7000E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7586E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9147E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9617E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3564E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3888E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1452E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1682E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9356E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1328E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4429E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7911E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6933E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4057E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3760E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5339E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3663E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4684E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9878E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1074E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6955E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7264E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8380E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8460E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1617 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1157 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1826 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1340 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1145 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9330E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2201E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4367E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0031E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1558E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6259E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8767E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7507E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4162E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2761E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4738E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2316E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4198E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1082E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6853E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7791E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9563E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2201E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4367E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6996E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0015E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2340E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6764E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5350E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3131E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2761E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4738E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1617 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1157 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1826 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1340 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1145 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9324E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2196E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4365E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.0031E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1555E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6258E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8764E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7503E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4158E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2756E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4735E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2317E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4196E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1083E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6852E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7789E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9561E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2196E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4365E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6996E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0013E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2339E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6761E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5346E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3127E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2756E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4736E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37419.39673 | 37419.39673 | 2.73476 | 2.73476 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5504.34546 | 5504.34546 | 0.23505 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30255.87052 | 30255.87052 | 2.20925 | 2.20925 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12318.06057 | 12318.06057 | 0.52776 | 0.52776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30579.90380 | 30579.90380 | 2.25396 | 2.25396 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21787.71652 | 21787.71652 | 0.93851 | 0.93851 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8532.61647 | 8532.61647 | 0.62891 | 0.62891 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9864.44467 | 9864.44467 | 0.42641 | 0.42641 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10906.05351 | 10906.05351 | 0.80384 | 0.80384 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6449.43382 | 6449.43382 | 0.27882 | 0.27882 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16326.06163 | 16326.06163 | 1.20333 | 1.20333 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9801.86564 | 9801.86564 | 0.42370 | 0.42370 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11910.96917 | 11910.96917 | 0.87791 | 0.87791 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6413.19609 | 6413.19609 | 0.27725 | 0.27725 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6887.49633 | 6887.49633 | 0.50765 | 0.50765 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7381.29781 | 7381.29781 | 0.31876 | 0.31876 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9061.13496 | 9061.13496 | 0.66786 | 0.66786 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.81033E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4891.90111 | 4891.90111 | 0.21130 | 0.21130 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 13462.25273 | 13462.25273 | 0.99225 | 0.99225 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7322.06177 | 7322.06177 | 0.31620 | 0.31620 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10003.54038 | 10003.54038 | 0.73732 | 0.73732 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4853.16753 | 4853.16753 | 0.20962 | 0.20962 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7559.36433 | 7559.36433 | 0.55717 | 0.55717 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7691.85711 | 7691.85711 | 0.33220 | 0.33220 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10909.68718 | 10909.68718 | 0.80411 | 0.80411 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5068.18791 | 5068.18791 | 0.21893 | 0.21893 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15188.74090 | 15188.74090 | 1.11950 | 1.11950 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7629.14038 | 7629.14038 | 0.32948 | 0.32948 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11138.21405 | 11138.21405 | 0.82095 | 0.82095 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5033.45476 | 5033.45476 | 0.21742 | 0.21742 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73504.50 | 4.92644 | 4.92644 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 24013.17 | 1.48057 | 1.48057 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69008.08 | 4.58982 | 4.58982 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24229.77 | 1.62579 | 1.62579 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76659.96 | 5.16568 | 5.16568 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 24066.21 | 2.34469 | 2.34469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.73476 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27405 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77941 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73079 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39027E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15830E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77941 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13240.09501 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15830E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.10066 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20925 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33924 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76440 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90463 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12311E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74136E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76440 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19904.87001 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74136E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 479.12793 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25396 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33251 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78889 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88668 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14585E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72099E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93851 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31102.56697 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72099E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 821.30966 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62891 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25122 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16603 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66991 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51662E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23304E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42641 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14094.42576 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23304E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 371.73587 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80384 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12443 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16077 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33181 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06196E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.06194E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27882 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9215.29028 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.06194E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 243.04247 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20333 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13130 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24067 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35012 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90184E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22521E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42370 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14004.90203 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22521E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 369.37697 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87791 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11392 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17558 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30380 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34431E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.01659E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27725 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9163.45099 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.01659E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 241.67652 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50765 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31122 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16397 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82992 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22422E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.22354E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31876 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10543.07661 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.22354E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 278.15246 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66786 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14977 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13357 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39938 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54397E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11323E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21130 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6987.79282 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11323E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 184.34493 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99225 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15923 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19845 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42460 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39283E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.14940E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31620 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10458.32452 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.14940E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.91917 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73732 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13565 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14746 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36173 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80876E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.06474E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20962 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6932.37578 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.06474E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.88463 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55717 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28356 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16102 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75616 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34364E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.61146E-005 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33220 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10986.49035 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.61146E-005 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.83742 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80411 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12439 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16082 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33170 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06298E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.33338E-005 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21893 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7239.44298 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.33338E-005 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.97662 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11950 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14113 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22390 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37634 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69970E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.53295E-005 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32948 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10896.75111 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.53295E-005 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.47265 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82095 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12183 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16419 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32488 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12735E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.28990E-005 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21742 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7189.74320 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.28990E-005 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 189.66694 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81992 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42286 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.63984 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48057 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.92644 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.92644 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30053 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75549 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.47433 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51098 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62579 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.58982 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.58982 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.35422 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88397 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53193 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.76794 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.34469 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.16568 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.16568 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.45390 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.92644 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.58982 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.16568 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.92644 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.92644 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86560.51092 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80037 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64198 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28850.61829 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80037 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 21468.83329 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87819E-004 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 361.65095 |
248 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.92644 |
249 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.87819E-004 |
250 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.58982 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.58982 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81291.89586 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80062 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.52979 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27094.58889 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80062 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 22456.55131 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96460E-004 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 374.86087 |
260 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.58982 |
261 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.96460E-004 |
262 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.16568 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.16568 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 90239.51013 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80039 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.72172 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30076.82873 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80039 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 21967.64751 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92183E-004 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 370.72332 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.16568 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.92183E-004 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.16832E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.26020 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.16832E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 653.00365 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 247852.63057 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 247852.63000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.16832E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 12549.21 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 18856.36 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 29475.28 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13354.01 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8731.13 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13269.20 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8682.03 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9989.77 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6621.00 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9909.48 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6568.50 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10409.82 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6859.39 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10324.81 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6812.31 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 17317.12 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 17788.11 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 17783.34 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85305.08 | 291073.02 | 11.74 | 3.04 | 3.36 | 3.53 | 3.74 | 10.37 | 11.45 | 12.05 | 12.75 | 5.6167 | 4.4544 | 2.9895 | 1.2186 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 80141.31 | 273453.51 | 11.76 | 3.04 | 3.36 | 3.54 | 3.74 | 10.39 | 11.47 | 12.07 | 12.77 | 5.2329 | 4.1530 | 2.7879 | 1.1317 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 88907.63 | 303365.44 | 11.72 | 3.04 | 3.35 | 3.53 | 3.73 | 10.36 | 11.44 | 12.03 | 12.73 | 5.8895 | 4.6693 | 3.1331 | 1.2802 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.7860076767E-002 | 6.6843252900E-002 | Pass | Pass | 0.2078971329 | 0.3914165945 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1187497699 | 6.3865940195E-002 | Pass | Pass | 0.4225415435 | 0.4715287279 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7667125793E-002 | 3.8239238714E-002 | Pass | Pass | 0.3256653029 | 0.4555641849 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0828430617E-002 | 4.4678894264E-002 | Pass | Pass | 0.2144649598 | 0.3893901997 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7793796566E-002 | 1.9274542454E-002 | Pass | Pass | 0.6531351820 | 1.3783849185 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5548043727E-002 | 1.6254582965E-002 | Pass | Pass | 10.7161802484 | 24.7701901086 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2253997918 | 0.2092203525 | Pass | Pass | 14.0060236464 | 31.2545716827 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2280936681 | 0.2171476077 | Pass | Pass | 10.8385632121 | 23.9428024429 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2128195498 | 0.2033933794 | Pass | Pass | 10.8680768027 | 23.9563553206 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2313879202 | 0.2199392856 | Pass | Pass | 10.2439062831 | 22.5577761151 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1009977966 | 0.1307005496 | Pass | Pass | 1.6474778138 | 3.7690987398 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1130672631 | 0.1487364099 | Pass | Pass | 1.3680999350 | 3.0635003123 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.7460966980E-002 | 0.1237239597 | Pass | Pass | 1.6748432056 | 3.8625495568 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1154570790 | 0.1518894596 | Pass | Pass | 1.2990985839 | 2.8893780810 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1279426646 | 0.1495914996 | Pass | Pass | 2.2781843925 | 4.5079158881 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1355934113 | 0.1603968395 | Pass | Pass | 1.8021794351 | 3.4569631712 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1260789142 | 0.1460870999 | Pass | Pass | 2.1056594028 | 4.2089866633 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1379599705 | 0.1631006032 | Pass | Pass | 1.7586876073 | 3.2639353078 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3038.44 | 75.87 | 0.00 | 2463.44 | 453.10 | 6030.86 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.36 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.36 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.36 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 195.79 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.09 | 0.0000 | Y | 9.17 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.60 | 0.0000 | Y | 5.70 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.58 | 0.0000 | Y | 5.70 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.96 | 0.0000 | Y | 9.13 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.52 | 0.0000 | Y | 5.68 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.11 | 0.0000 | Y | 8.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.49 | 0.0000 | Y | 5.68 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 27.09 | 0.0000 | Y | 9.17 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.60 | 0.0000 | Y | 5.70 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 8.86 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.58 | 0.0000 | Y | 5.70 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 303.98 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.59 | 42.59 | 4.51 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.55 | 63.07 | 4.83 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.55 | 47.80 | 42.30 | |
Exterior Lighting Total | 5686.19 | 51.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 247852.63 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86560.51 | 69280.80 | 17279.71 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81291.90 | 65084.03 | 16207.87 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 90239.51 | 72226.61 | 18012.90 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85305.1 | 3.04 | 10.37 | N/A | N/A | 11.74 | |
PACU_VAV_MID COOLING COIL | 80141.3 | 3.04 | 10.39 | N/A | N/A | 11.76 | |
PACU_VAV_TOP COOLING COIL | 88907.6 | 3.04 | 10.36 | N/A | N/A | 11.72 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13240.10 | 12549.21 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 19904.87 | 18856.36 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 31102.57 | 29475.28 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14094.43 | 13354.01 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9215.29 | 8731.13 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14004.90 | 13269.20 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9163.45 | 8682.03 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10543.08 | 9989.77 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6987.79 | 6621.00 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10458.32 | 9909.48 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6932.38 | 6568.50 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10986.49 | 10409.82 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7239.44 | 6859.39 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10896.75 | 10324.81 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7189.74 | 6812.31 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 21468.83 | 17317.12 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 22456.55 | 17788.11 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 21967.65 | 17783.34 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.93 | 10784.04 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.59 | 10047.16 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.17 | 11234.78 | 2174.89 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002168 | 653.00 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85305.08 | 3.04 | 10.37 | 11.74 | 5.6167 | 3.36 | 11.45 | 4.4544 | 3.53 | 12.05 | 2.9895 | 3.74 | 12.75 | 1.2186 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80141.31 | 3.04 | 10.39 | 11.76 | 5.2329 | 3.36 | 11.47 | 4.1530 | 3.54 | 12.07 | 2.7879 | 3.74 | 12.77 | 1.1317 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88907.63 | 3.04 | 10.36 | 11.72 | 5.8895 | 3.35 | 11.44 | 4.6693 | 3.53 | 12.03 | 3.1331 | 3.73 | 12.73 | 1.2802 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37419.40 | 37419.40 | 38.05 | 2.735 | 2.735 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 30255.87 | 30255.87 | 30.76 | 2.209 | 2.209 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 30579.90 | 30579.90 | 31.09 | 2.254 | 2.254 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00889 | 29.30 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8532.62 | 8532.62 | 41.15 | 0.629 | 0.629 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00880 | 29.30 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10906.05 | 10906.05 | 83.09 | 0.804 | 0.804 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00865 | 23.68 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16326.06 | 16326.06 | 78.74 | 1.203 | 1.203 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00866 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11910.97 | 11910.97 | 90.75 | 0.878 | 0.878 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6887.50 | 6887.50 | 33.22 | 0.508 | 0.508 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9061.13 | 9061.13 | 69.03 | 0.668 | 0.668 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00868 | 22.36 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13462.25 | 13462.25 | 64.93 | 0.992 | 0.992 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00869 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10003.54 | 10003.54 | 76.22 | 0.737 | 0.737 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00866 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7559.36 | 7559.36 | 36.46 | 0.557 | 0.557 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10909.69 | 10909.69 | 83.11 | 0.804 | 0.804 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15188.74 | 15188.74 | 73.26 | 1.120 | 1.120 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11138.21 | 11138.21 | 84.86 | 0.821 | 0.821 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5504.35 | 5504.35 | 5.60 | 0.235 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 12318.06 | 12318.06 | 12.52 | 0.528 | 0.528 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 21787.72 | 21787.72 | 22.15 | 0.939 | 0.939 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9864.44 | 9864.44 | 47.58 | 0.426 | 0.426 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6449.43 | 6449.43 | 49.13 | 0.279 | 0.279 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9801.87 | 9801.87 | 47.27 | 0.424 | 0.424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6413.20 | 6413.20 | 48.86 | 0.277 | 0.277 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7381.30 | 7381.30 | 35.60 | 0.319 | 0.319 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4891.90 | 4891.90 | 37.27 | 0.211 | 0.211 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7322.06 | 7322.06 | 35.31 | 0.316 | 0.316 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4853.17 | 4853.17 | 36.98 | 0.210 | 0.210 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7691.86 | 7691.86 | 37.10 | 0.332 | 0.332 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5068.19 | 5068.19 | 38.61 | 0.219 | 0.219 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7629.14 | 7629.14 | 36.80 | 0.329 | 0.329 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5033.45 | 5033.45 | 38.35 | 0.217 | 0.217 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.93 | 4.93 | 1.48 | 1.48 | 4.9264 | 1.4806 | 4.9264 | 0.3005 | 0.3000 |
PACU_VAV_MID | 4.59 | 4.59 | 1.63 | 1.63 | 4.5898 | 1.6258 | 4.5898 | 0.3542 | 0.3000 |
PACU_VAV_TOP | 5.17 | 5.17 | 2.34 | 2.34 | 5.1657 | 2.3447 | 5.1657 | 0.4539 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13240.095 | 13240.095 | 0.779406 | 0.00011583 | 287.101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13240.10 | 13240.10 | 0.779406 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 5504.35 | 0.00 | 13286.20 | 13286.20 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 19904.870 | 19904.870 | 0.764400 | 0.00017414 | 479.128 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19904.87 | 19904.87 | 0.764400 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 12318.06 | 0.00 | 19969.34 | 19969.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 31102.567 | 31102.567 | 0.938507 | 0.00027210 | 821.310 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31102.57 | 31102.57 | 0.938507 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 21787.72 | 0.00 | 31212.18 | 31212.18 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 14094.426 | 14094.426 | 0.426413 | 0.00012330 | 371.736 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14094.43 | 14094.43 | 0.426413 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777221 | 49.5489 | 9864.44 | 0.00 | 14140.87 | 14140.87 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9215.290 | 9215.290 | 0.278819 | 0.00008062 | 243.042 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9215.29 | 9215.29 | 0.278819 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777208 | 49.5482 | 6449.43 | 0.00 | 9245.60 | 9245.60 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 14004.902 | 14004.902 | 0.423699 | 0.00012252 | 369.377 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14004.90 | 14004.90 | 0.423699 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776985 | 49.5341 | 9801.87 | 0.00 | 14051.07 | 14051.07 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9163.451 | 9163.451 | 0.277248 | 0.00008017 | 241.677 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9163.45 | 9163.45 | 0.277248 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777009 | 49.5357 | 6413.20 | 0.00 | 9193.60 | 9193.60 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10543.077 | 10543.077 | 0.318765 | 0.00009224 | 278.152 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10543.08 | 10543.08 | 0.318765 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771905 | 49.2144 | 7381.30 | 0.00 | 10578.41 | 10578.41 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6987.793 | 6987.793 | 0.211298 | 0.00006113 | 184.345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6987.79 | 6987.79 | 0.211298 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773231 | 49.2978 | 4891.90 | 0.00 | 7011.14 | 7011.14 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10458.325 | 10458.325 | 0.316196 | 0.00009149 | 275.919 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10458.32 | 10458.32 | 0.316196 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771400 | 49.1826 | 7322.06 | 0.00 | 10493.40 | 10493.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6932.376 | 6932.376 | 0.209618 | 0.00006065 | 182.885 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6932.38 | 6932.38 | 0.209618 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772759 | 49.2682 | 4853.17 | 0.00 | 6955.55 | 6955.55 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10986.490 | 10986.490 | 0.332205 | 0.00009611 | 289.837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10986.49 | 10986.49 | 0.332205 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765803 | 48.8307 | 7691.86 | 0.00 | 11023.22 | 11023.22 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7239.443 | 7239.443 | 0.218926 | 0.00006333 | 190.977 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7239.44 | 7239.44 | 0.218926 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00767256 | 48.9222 | 5068.19 | 0.00 | 7263.58 | 7263.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10896.751 | 10896.751 | 0.329484 | 0.00009533 | 287.473 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10896.75 | 10896.75 | 0.329484 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765148 | 48.7895 | 7629.14 | 0.00 | 10933.20 | 10933.20 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7189.743 | 7189.743 | 0.217419 | 0.00006290 | 189.667 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7189.74 | 7189.74 | 0.217419 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00766696 | 48.8870 | 5033.45 | 0.00 | 7213.72 | 7213.72 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86560.511 | 69280.801 | 4.926443 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 87530.99 | 82957.15 | 4.926443 | 25.31 | 16.96 | 0.00880760 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 24.2603 | 24.00 | 0.00880314 | 46.6930 | 66838.40 | 0.00 | 89255.51 | 69716.73 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 21468.833 | 21468.833 | 1.477933 | 0.00018782 | 361.651 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21468.83 | 21468.83 | 1.477933 | 0.62 | 0.15 | 0.00368333 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 80.8677 | 21.00 | 0.00784263 | 49.9905 | 21257.37 | 0.00 | 20957.20 | 20957.20 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 81291.896 | 65084.026 | 4.589817 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 82270.28 | 77776.74 | 4.589817 | 25.41 | 17.01 | 0.00882453 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 26.0396 | 24.00 | 0.00882559 | 46.8104 | 62271.37 | 0.00 | 83822.86 | 65513.69 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 22456.551 | 22456.551 | 1.376945 | 0.00019646 | 374.861 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22456.55 | 22456.55 | 1.376945 | -0.87 | -1.17 | 0.00336664 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 86.7987 | 21.00 | 0.00779566 | 49.6952 | 25098.99 | 0.00 | 21524.92 | 21524.92 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 90239.510 | 72226.606 | 5.165683 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 91205.38 | 86573.69 | 5.165683 | 25.25 | 16.93 | 0.00879720 | 11.01 | 11.01 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 23.1367 | 24.00 | 0.00878988 | 46.6236 | 70043.45 | 0.00 | 93049.05 | 72684.59 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 21967.648 | 21967.648 | 1.549705 | 0.00019218 | 370.723 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21967.65 | 21967.65 | 1.549705 | 0.92 | 0.54 | 0.00383446 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 77.1224 | 19.60 | 0.00764728 | 53.1670 | 28223.09 | 0.00 | 21522.16 | 21522.16 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13240.095 | 13240.095 | 0.779406 | 0.00011583 | 287.101 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 5.2365 | 5.341922 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13240.10 | 13240.10 | 1.0000 | 0.92514795 | 0.779406 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11581831 | 60.00 | 32.22 | 27.78 | 0.000 | 13240.10 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.67 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 5504.35 | 0.00 | 13286.20 | 13286.20 | 0.92514795 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.88 | 16.98 | 0.00800000 | 47421.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 19904.870 | 19904.870 | 0.764400 | 0.00017414 | 479.128 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 7.8725 | 8.030929 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19904.87 | 19904.87 | 1.0000 | 0.90733563 | 0.764400 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.17411872 | 60.00 | 32.22 | 27.78 | 0.000 | 19904.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 12318.06 | 0.00 | 19969.34 | 19969.34 | 0.90733563 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.38 | 19.46 | 0.00800000 | 55068.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 31102.567 | 31102.567 | 0.938507 | 0.00027210 | 821.310 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 12.3012 | 12.548815 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31102.57 | 31102.57 | 1.0000 | 1.11399868 | 0.938507 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.27207107 | 60.00 | 32.22 | 27.78 | 0.000 | 31102.57 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 21787.72 | 0.00 | 31212.18 | 31212.18 | 1.11399868 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.26 | 0.00800000 | 61078.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14094.426 | 14094.426 | 0.426413 | 0.00012330 | 371.736 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 5.5744 | 5.686615 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14094.43 | 14094.43 | 1.0000 | 0.50614887 | 0.426413 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12329161 | 60.00 | 32.22 | 27.78 | 0.000 | 14094.43 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777221 | 21.00 | 0.00777221 | 49.5489 | 9864.44 | 0.00 | 14140.87 | 14140.87 | 0.50614887 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9215.290 | 9215.290 | 0.278819 | 0.00008062 | 243.042 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 3.6447 | 3.718052 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9215.29 | 9215.29 | 1.0000 | 0.33095609 | 0.278819 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08061116 | 60.00 | 32.22 | 27.78 | 0.000 | 9215.29 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777208 | 21.00 | 0.00777208 | 49.5482 | 6449.43 | 0.00 | 9245.60 | 9245.60 | 0.33095609 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14004.902 | 14004.902 | 0.423699 | 0.00012252 | 369.377 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 5.5390 | 5.650496 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14004.90 | 14004.90 | 1.0000 | 0.50292723 | 0.423699 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12250849 | 60.00 | 32.22 | 27.78 | 0.000 | 14004.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776985 | 21.00 | 0.00776985 | 49.5341 | 9801.87 | 0.00 | 14051.07 | 14051.07 | 0.50292723 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9163.451 | 9163.451 | 0.277248 | 0.00008017 | 241.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 3.6242 | 3.697137 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9163.45 | 9163.45 | 1.0000 | 0.32909061 | 0.277248 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08015769 | 60.00 | 32.22 | 27.78 | 0.000 | 9163.45 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777009 | 21.00 | 0.00777009 | 49.5357 | 6413.20 | 0.00 | 9193.60 | 9193.60 | 0.32909061 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10543.077 | 10543.077 | 0.318765 | 0.00009224 | 278.152 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 4.1698 | 4.253768 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10543.08 | 10543.08 | 1.0000 | 0.37837074 | 0.318765 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09222602 | 60.00 | 32.22 | 27.78 | 0.000 | 10543.08 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771905 | 21.00 | 0.00771905 | 49.2144 | 7381.30 | 0.00 | 10578.41 | 10578.41 | 0.37837074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6987.793 | 6987.793 | 0.211298 | 0.00006113 | 184.345 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 2.7637 | 2.819334 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6987.79 | 6987.79 | 1.0000 | 0.25080918 | 0.211298 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06112602 | 60.00 | 32.22 | 27.78 | 0.000 | 6987.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773231 | 21.00 | 0.00773231 | 49.2978 | 4891.90 | 0.00 | 7011.14 | 7011.14 | 0.25080918 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10458.325 | 10458.325 | 0.316196 | 0.00009149 | 275.919 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 4.1363 | 4.219574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10458.32 | 10458.32 | 1.0000 | 0.37532119 | 0.316196 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09148465 | 60.00 | 32.22 | 27.78 | 0.000 | 10458.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771400 | 21.00 | 0.00771400 | 49.1826 | 7322.06 | 0.00 | 10493.40 | 10493.40 | 0.37532119 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6932.376 | 6932.376 | 0.209618 | 0.00006065 | 182.885 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 2.7418 | 2.796975 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6932.38 | 6932.38 | 1.0000 | 0.24881519 | 0.209618 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06064126 | 60.00 | 32.22 | 27.78 | 0.000 | 6932.38 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772759 | 21.00 | 0.00772759 | 49.2682 | 4853.17 | 0.00 | 6955.55 | 6955.55 | 0.24881519 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10986.490 | 10986.490 | 0.332205 | 0.00009611 | 289.837 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 4.3452 | 4.432670 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10986.49 | 10986.49 | 1.0000 | 0.39432379 | 0.332205 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09610481 | 60.00 | 32.22 | 27.78 | 0.000 | 10986.49 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765803 | 21.00 | 0.00765803 | 48.8307 | 7691.86 | 0.00 | 11023.22 | 11023.22 | 0.39432379 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7239.443 | 7239.443 | 0.218926 | 0.00006333 | 190.977 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 2.8632 | 2.920866 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7239.44 | 7239.44 | 1.0000 | 0.25986259 | 0.218926 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06332734 | 60.00 | 32.22 | 27.78 | 0.000 | 7239.44 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00767256 | 21.00 | 0.00767256 | 48.9222 | 5068.19 | 0.00 | 7263.58 | 7263.58 | 0.25986259 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10896.751 | 10896.751 | 0.329484 | 0.00009533 | 287.473 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 4.3097 | 4.396464 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10896.75 | 10896.75 | 1.0000 | 0.39109498 | 0.329484 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09531981 | 60.00 | 32.22 | 27.78 | 0.000 | 10896.75 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765148 | 21.00 | 0.00765148 | 48.7895 | 7629.14 | 0.00 | 10933.20 | 10933.20 | 0.39109498 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61015.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7189.743 | 7189.743 | 0.217419 | 0.00006290 | 189.667 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 2.8436 | 2.900814 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7189.74 | 7189.74 | 1.0000 | 0.25807444 | 0.217419 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06289259 | 60.00 | 32.22 | 27.78 | 0.000 | 7189.74 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00766696 | 21.00 | 0.00766696 | 48.8870 | 5033.45 | 0.00 | 7213.72 | 7213.72 | 0.25807444 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.9 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86560.511 | 69280.801 | 4.926443 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2129 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.926443 | 5.84764188 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 87530.99 | 82957.15 | 1.0112 | 5.84764188 | 4.926443 | 25.31 | 16.96 | 0.00880760 | 47873.3 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10784.037 | 76746.95 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 24.2603 | 24.00 | 0.00880314 | 24.00 | 0.00880314 | 46.6930 | 66838.40 | 0.00 | 89255.51 | 69716.73 | 5.61670423 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.53 | 14.07 | 0.00982074 | 39431.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21468.833 | 21468.833 | 1.477933 | 0.00018782 | 361.651 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.926443 | 5.84764188 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 8.4910 | 8.661935 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21468.83 | 21468.83 | 1.0000 | 1.75429256 | 1.477933 | 0.62 | 0.15 | 0.00368333 | 9840.3 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.18779956 | 60.00 | 32.22 | 27.78 | 0.000 | 21468.83 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 80.8677 | 21.00 | 0.00788055 | 21.00 | 0.00784263 | 49.9905 | 21257.37 | 0.00 | 20957.20 | 20957.20 | 1.75429256 | 2.80 | 1.50 | 0.00368333 | 12044.5 | 14.61 | 7.68 | 0.00368333 | 23990.8 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81291.896 | 65084.026 | 4.589817 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2444 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.589817 | 5.44807105 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 82270.28 | 77776.74 | 1.0120 | 5.44807105 | 4.589817 | 25.41 | 17.01 | 0.00882453 | 48014.6 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10047.161 | 72223.12 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 26.0396 | 24.00 | 0.00882559 | 24.00 | 0.00882559 | 46.8104 | 62271.37 | 0.00 | 83822.86 | 65513.69 | 5.23291343 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.43 | 14.02 | 0.00981284 | 39304.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 22456.551 | 22456.551 | 1.376945 | 0.00019646 | 374.861 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.589817 | 5.44807105 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 8.8817 | 9.060445 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22456.55 | 22456.55 | 1.0000 | 1.63442132 | 1.376945 | -0.87 | -1.17 | 0.00336664 | 7536.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.19643967 | 60.00 | 32.22 | 27.78 | 0.000 | 22456.55 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 86.7987 | 21.00 | 0.00781348 | 21.00 | 0.00779566 | 49.6952 | 25098.99 | 0.00 | 21524.92 | 21524.92 | 1.63442132 | 2.80 | 1.05 | 0.00336664 | 11250.9 | 15.83 | 7.89 | 0.00336664 | 24420.6 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 90239.510 | 72226.606 | 5.165683 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1936 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.165683 | 6.13161833 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 91205.38 | 86573.69 | 1.0107 | 6.13161833 | 5.165683 | 25.25 | 16.93 | 0.00879720 | 47785.6 | 11.01 | 11.01 | 0.00850000 | 32490.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11234.784 | 79970.60 | 29.40 | 0.00882150 | 18.34 | 1.19517000 | 23.1367 | 24.00 | 0.00878988 | 24.00 | 0.00878988 | 46.6236 | 70043.45 | 0.00 | 93049.05 | 72684.59 | 5.88946576 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.60 | 14.10 | 0.00982894 | 39523.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21967.648 | 21967.648 | 1.549705 | 0.00019218 | 370.723 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.165683 | 6.13161833 | 4197.9300 | 999.8980 | 2.16810174 | 54.44 | 82.22 | 27.78 | 252840.76 | 8.6883 | 8.863189 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21967.65 | 21967.65 | 1.0000 | 1.83948550 | 1.549705 | 0.92 | 0.54 | 0.00383446 | 10516.2 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.19216296 | 60.00 | 32.22 | 27.78 | 0.000 | 21967.65 | -4.20 | 0.00269032 | -4.20 | 1.19517000 | 77.1224 | 18.16 | 0.00769149 | 19.60 | 0.00764728 | 53.1670 | 28223.09 | 0.00 | 21522.16 | 21522.16 | 1.83948550 | 2.80 | 1.71 | 0.00383446 | 12423.3 | 14.36 | 7.74 | 0.00383446 | 24123.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.93 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.59 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.17 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1978.17 | 2105.67 | 32.00 |
CORE_MID | 1203.67 | 3499.67 | 168.83 |
CORE_TOP | 1416.33 | 4098.50 | 634.50 |
PERIMETER_TOP_ZN_3 | 2214.17 | 4430.00 | 1472.00 |
PERIMETER_TOP_ZN_2 | 2550.50 | 4162.50 | 1394.83 |
PERIMETER_TOP_ZN_1 | 2457.17 | 4006.50 | 1179.33 |
PERIMETER_TOP_ZN_4 | 2504.00 | 4419.67 | 1472.83 |
PERIMETER_BOT_ZN_3 | 1642.00 | 4481.50 | 1026.17 |
PERIMETER_BOT_ZN_2 | 2155.50 | 3926.83 | 925.50 |
PERIMETER_BOT_ZN_1 | 2056.33 | 4089.50 | 878.50 |
PERIMETER_BOT_ZN_4 | 2179.50 | 4048.17 | 961.00 |
PERIMETER_MID_ZN_3 | 1813.67 | 4102.33 | 955.17 |
PERIMETER_MID_ZN_2 | 1853.17 | 3477.67 | 884.67 |
PERIMETER_MID_ZN_1 | 2165.67 | 3638.67 | 723.50 |
PERIMETER_MID_ZN_4 | 2154.33 | 4116.83 | 965.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4150.00 | 4930.50 | 1700.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.17 | 0.00 | 2.17 | 0.00 |
CORE_MID | 3.17 | 0.00 | 3.17 | 0.00 |
CORE_TOP | 5.50 | 0.00 | 5.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 19.17 | 0.00 | 17.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 7.50 | 8.17 | 6.50 | 8.17 |
PERIMETER_TOP_ZN_1 | 6.17 | 10.00 | 5.50 | 10.00 |
PERIMETER_TOP_ZN_4 | 7.00 | 16.00 | 6.17 | 9.00 |
PERIMETER_BOT_ZN_3 | 4.67 | 0.00 | 4.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 3.17 | 6.00 | 3.00 | 6.00 |
PERIMETER_BOT_ZN_1 | 297.00 | 6.17 | 297.00 | 6.17 |
PERIMETER_BOT_ZN_4 | 3.33 | 10.83 | 2.83 | 4.50 |
PERIMETER_MID_ZN_3 | 4.83 | 0.00 | 4.67 | 0.00 |
PERIMETER_MID_ZN_2 | 2.50 | 9.17 | 2.33 | 9.17 |
PERIMETER_MID_ZN_1 | 2.17 | 11.17 | 2.17 | 11.17 |
PERIMETER_MID_ZN_4 | 2.50 | 16.00 | 2.33 | 8.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 309.33 | 59.00 | 306.50 | 45.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 1.044 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.731 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.712 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.753 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.256 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 1.308 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.329 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.690 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 1.085 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 1.051 | 0.829 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 1.123 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.758 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.169 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 1.291 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.287 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 16458540.79 | 0.00 | 16458540.79 | 0.00 | 16458540.79 | 13393058.27 | 5062.81 | 51.61 | 3645.58 | 40.46 |
CORE_MID | 11570592.32 | 0.00 | 11570592.32 | 0.00 | 11570592.32 | 13393058.27 | 5670.34 | 53.59 | 3036.06 | 44.72 |
CORE_TOP | 11309089.87 | 0.00 | 11309089.87 | 0.00 | 11309089.87 | 13393058.27 | 5730.11 | 42.53 | 2987.36 | 45.17 |
PERIMETER_TOP_ZN_3 | 2519989.07 | 0.00 | 2519989.07 | 242662.85 | 2762651.92 | 2823374.22 | 5623.15 | 55.89 | 3080.96 | 45.17 |
PERIMETER_TOP_ZN_2 | 2660137.39 | 0.00 | 2660137.39 | 161774.26 | 2821911.65 | 1787429.43 | 4075.95 | 3.37 | 4680.68 | 45.17 |
PERIMETER_TOP_ZN_1 | 4369965.89 | 0.00 | 4369965.89 | 242662.85 | 4612628.75 | 2823374.22 | 4083.79 | 2.63 | 4673.57 | 45.17 |
PERIMETER_TOP_ZN_4 | 2824836.27 | 0.00 | 2824836.27 | 161774.26 | 2986610.53 | 1787312.18 | 4068.99 | 5.79 | 4685.22 | 45.17 |
PERIMETER_BOT_ZN_3 | 2306299.91 | 0.00 | 2306299.91 | 129022.55 | 2435322.46 | 2823374.22 | 5499.81 | 60.84 | 3199.36 | 40.46 |
PERIMETER_BOT_ZN_2 | 2291840.65 | 0.00 | 2291840.65 | 86014.52 | 2377855.16 | 1787429.43 | 4084.34 | 6.12 | 4669.54 | 40.46 |
PERIMETER_BOT_ZN_1 | 3514702.71 | 0.00 | 3514702.71 | 2835943.55 | 6350646.26 | 2823374.22 | 4097.06 | 18.69 | 4644.26 | 40.46 |
PERIMETER_BOT_ZN_4 | 2378846.11 | 0.00 | 2378846.11 | 86014.52 | 2464860.62 | 1787312.18 | 4064.21 | 5.10 | 4690.69 | 40.46 |
PERIMETER_MID_ZN_3 | 2531944.02 | 0.00 | 2531944.02 | 201998.19 | 2733942.21 | 2823374.22 | 5566.03 | 63.63 | 3130.34 | 44.72 |
PERIMETER_MID_ZN_2 | 2690634.66 | 0.00 | 2690634.66 | 134664.65 | 2825299.31 | 1787429.43 | 4022.26 | 3.66 | 4734.08 | 953.72 |
PERIMETER_MID_ZN_1 | 4305107.14 | 0.00 | 4305107.14 | 201998.19 | 4507105.32 | 2823374.22 | 4053.55 | 4.17 | 4702.28 | 44.72 |
PERIMETER_MID_ZN_4 | 2729401.73 | 0.00 | 2729401.73 | 134664.65 | 2864066.38 | 1787312.18 | 4022.30 | 6.15 | 4731.55 | 44.72 |
Total Facility | 74461928.54 | 0.00 | 74461928.54 | 4619195.04 | 79081123.58 | 67843644.98 | 5856.31 | 252.74 | 4795.21 | 978.42 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7652 | 0.0000 | 0.7652 | 0.0000 | 0.7652 | 0.4247 | 2275.43 | 51.61 | 3615.96 |
CORE_MID | 0.5365 | 0.0000 | 0.5365 | 0.0000 | 0.5365 | 0.4247 | 2886.44 | 53.59 | 3002.97 |
CORE_TOP | 0.5237 | 0.0000 | 0.5237 | 0.0000 | 0.5237 | 0.4247 | 2949.56 | 42.53 | 2950.91 |
PERIMETER_TOP_ZN_3 | 0.1168 | 0.0000 | 0.1168 | 0.0055 | 0.1223 | 0.0895 | 2842.59 | 55.89 | 3044.52 |
PERIMETER_TOP_ZN_2 | 0.1233 | 0.0000 | 0.1233 | 0.0037 | 0.1270 | 0.0567 | 1295.39 | 3.37 | 4644.24 |
PERIMETER_TOP_ZN_1 | 0.2028 | 0.0000 | 0.2028 | 0.0055 | 0.2083 | 0.0895 | 1303.24 | 2.63 | 4637.13 |
PERIMETER_TOP_ZN_4 | 0.1305 | 0.0000 | 0.1305 | 0.0037 | 0.1342 | 0.0567 | 1288.44 | 5.79 | 4648.78 |
PERIMETER_BOT_ZN_3 | 0.1069 | 0.0000 | 0.1069 | 0.0029 | 0.1099 | 0.0895 | 2712.43 | 60.84 | 3169.73 |
PERIMETER_BOT_ZN_2 | 0.1064 | 0.0000 | 0.1064 | 0.0020 | 0.1084 | 0.0567 | 1296.98 | 6.12 | 4639.90 |
PERIMETER_BOT_ZN_1 | 0.1632 | 0.0000 | 0.1632 | 0.1295 | 0.2927 | 0.0895 | 1309.68 | 18.69 | 4614.63 |
PERIMETER_BOT_ZN_4 | 0.1102 | 0.0000 | 0.1102 | 0.0020 | 0.1122 | 0.0567 | 1276.86 | 5.10 | 4661.04 |
PERIMETER_MID_ZN_3 | 0.1174 | 0.0000 | 0.1174 | 0.0046 | 0.1220 | 0.0895 | 2782.12 | 63.63 | 3097.24 |
PERIMETER_MID_ZN_2 | 0.1147 | 0.0000 | 0.1147 | 0.0033 | 0.1180 | 0.0567 | 1238.40 | 3.66 | 3791.94 |
PERIMETER_MID_ZN_1 | 0.2000 | 0.0000 | 0.2000 | 0.0046 | 0.2045 | 0.0895 | 1269.65 | 4.17 | 4669.18 |
PERIMETER_MID_ZN_4 | 0.1263 | 0.0000 | 0.1263 | 0.0031 | 0.1294 | 0.0567 | 1238.44 | 6.15 | 4698.41 |
Total Facility | 3.4441 | 0.0000 | 3.4441 | 0.1702 | 3.6142 | 2.1513 | 3059.51 | 252.74 | 4748.85 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 37971449.18 | 0.00 | 37971449.18 | 22614548.33 | 4039.72 | 4.44 | 4715.83 | 40.46 |
PACU_VAV_MID | 33571940.93 | 0.00 | 33571940.93 | 22614548.33 | 4019.22 | 4.03 | 4736.75 | 44.72 |
PACU_VAV_TOP | 33369529.64 | 0.00 | 33369529.64 | 22614548.33 | 4073.74 | 1.70 | 4684.56 | 45.05 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.7641 | 0.0000 | 1.7641 | 0.7171 | 1252.35 | 4.44 | 4686.21 |
PACU_VAV_MID | 1.5570 | 0.0000 | 1.5570 | 0.7171 | 1235.31 | 4.03 | 4703.66 |
PACU_VAV_TOP | 1.5457 | 0.0000 | 1.5457 | 0.7171 | 1293.19 | 1.70 | 4648.12 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3692.42 | 0.00 | 0.00 | 0.00 | 1076.70 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 3393.67 | 0.00 | 0.00 | 0.00 | 1413.22 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 3344.61 | 0.00 | 0.00 | 0.00 | 1454.74 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5469 | 0.0000 | 0.0000 | 0.0000 | 1.1017 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.2997 | 0.0000 | 0.0000 | 0.0000 | 1.0996 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3021 | 0.0000 | 0.0000 | 0.0000 | 1.0945 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 982 |
Defaulted Fields | 577 |
Fields with Defaults | 2420 |
Autosized Fields | 193 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
Electricity:Building | 1023.67 | 13465.67 | 07-MAY-17:20 | 74341.76 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1023.67 | 13465.67 | 07-MAY-17:20 | 74341.76 | 02-JAN-08:10 |
InteriorLights:Electricity | 303.98 | 987.92 | 07-MAY-17:20 | 32642.50 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 303.98 | 987.92 | 07-MAY-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 303.98 | 987.92 | 07-MAY-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 303.98 | 987.92 | 07-MAY-17:20 | 32642.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.51 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.17 | 36.00 | 15-JAN-11:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.17 | 36.00 | 15-JAN-11:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 21.10 | 267.21 | 23-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.79 | 01-JAN-10:20 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.79 | 01-JAN-10:20 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 33.20 | 422.10 | 19-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 21.10 | 267.21 | 19-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.70 | 22.79 | 01-JAN-13:30 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.70 | 22.79 | 01-JAN-13:30 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.46 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.13 | 36.00 | 08-JAN-11:30 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.13 | 36.00 | 08-JAN-11:30 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 21.09 | 267.21 | 23-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.68 | 22.79 | 01-JAN-10:10 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.68 | 22.79 | 01-JAN-10:10 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 33.17 | 422.10 | 19-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.84 | 36.00 | 01-JAN-10:00 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.84 | 36.00 | 01-JAN-10:00 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.08 | 267.21 | 19-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.68 | 22.79 | 01-JAN-13:20 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.68 | 22.79 | 01-JAN-13:20 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.51 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.17 | 36.00 | 15-JAN-11:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.17 | 36.00 | 15-JAN-11:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 21.10 | 267.21 | 23-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.70 | 22.79 | 01-JAN-10:20 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.70 | 22.79 | 01-JAN-10:20 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 33.20 | 422.10 | 19-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 21.10 | 267.21 | 19-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.70 | 22.79 | 01-JAN-13:30 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.70 | 22.79 | 01-JAN-13:30 | 859.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 176.90 | 368.59 | 02-JUL-17:50 | 81449.51 | 10-AUG-15:20 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
ElectricityPurchased:Plant | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
Cogeneration:ElectricityPurchased | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
ElectricityNet:Plant | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
Cogeneration:ElectricityNet | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
General:Cogeneration:ElectricityNet | 1307.63 | 13840.93 | 02-JUL-17:50 | 153056.31 | 10-AUG-15:20 |
Fans:Electricity | 79.67 | 0.00 | 01-JAN-00:50 | 27002.48 | 10-AUG-15:20 |
General:Fans:Electricity | 79.67 | 0.00 | 01-JAN-00:50 | 27002.48 | 10-AUG-15:20 |
ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 70.33 | 0.00 | 01-JAN-00:10 | 53443.20 | 29-AUG-15:30 |
General:Cooling:Electricity | 70.33 | 0.00 | 01-JAN-00:10 | 53443.20 | 29-AUG-15:30 |
Electricity:Plant | 55.42 | 0.00 | 01-JAN-01:30 | 6743.46 | 02-JAN-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 54.28 | 0.00 | 01-JAN-00:10 | 6514.45 | 09-FEB-12:20 |
Water Heater:WaterSystems:Electricity | 54.28 | 0.00 | 01-JAN-00:10 | 6514.45 | 09-FEB-12:20 |
Pumps:Electricity | 1.13 | 0.00 | 01-JAN-00:50 | 568.43 | 26-DEC-07:40 |
General:Pumps:Electricity | 1.13 | 0.00 | 01-JAN-00:50 | 568.43 | 26-DEC-07:40 |
WIRED_LTG_ELECTRICITY | 8.54 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 226.92 | 0.00 | 01-JAN-00:50 | 185997.07 | 26-DEC-07:20 |
NaturalGas:Plant | 226.92 | 0.00 | 01-JAN-00:50 | 185997.07 | 26-DEC-07:20 |
Heating:NaturalGas | 226.92 | 0.00 | 01-JAN-00:50 | 185997.07 | 26-DEC-07:20 |
Boiler:Heating:NaturalGas | 226.92 | 0.00 | 01-JAN-00:50 | 185997.07 | 26-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1635.28 | 0.00 | 01-JAN-00:50 | 400039.08 | 26-DEC-07:20 |
EnergyTransfer:Building | 966.25 | 0.00 | 01-JAN-00:50 | 159952.39 | 10-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 215.75 | 0.00 | 01-JAN-00:40 | 23887.96 | 14-AUG-16:00 |
Heating:EnergyTransfer | 70.08 | 0.00 | 01-JAN-00:50 | 125352.98 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 5573.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 70.08 | 0.00 | 01-JAN-00:50 | 125352.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 5573.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 896.18 | 0.00 | 01-JAN-00:50 | 159952.39 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 215.66 | 0.00 | 01-JAN-00:40 | 23887.96 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer | 896.18 | 0.00 | 01-JAN-00:50 | 159952.39 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 215.66 | 0.00 | 01-JAN-00:40 | 23887.96 | 14-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.63 | 0.00 | 01-JAN-00:10 | 10245.83 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.65 | 0.00 | 01-JAN-00:10 | 10245.83 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.65 | 0.00 | 01-JAN-00:10 | 10245.83 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.98 | 0.00 | 01-JAN-00:10 | 10160.22 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.98 | 0.00 | 01-JAN-00:10 | 10160.22 | 10-AUG-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 19.11 | 0.00 | 01-JAN-00:10 | 8689.37 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.72 | 0.00 | 01-JAN-00:10 | 8689.37 | 02-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.72 | 0.00 | 01-JAN-00:10 | 8689.37 | 02-JAN-08:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.38 | 0.00 | 01-JAN-00:10 | 4531.76 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.38 | 0.00 | 01-JAN-00:10 | 4531.76 | 14-AUG-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.59 | 0.00 | 01-JAN-00:40 | 7366.27 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.23 | 0.00 | 01-JAN-00:40 | 7366.27 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.23 | 0.00 | 01-JAN-00:40 | 7366.27 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.36 | 0.00 | 01-JAN-00:10 | 5070.97 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.36 | 0.00 | 01-JAN-00:10 | 5070.97 | 14-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 142.45 | 0.00 | 01-JAN-00:10 | 17627.39 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.52 | 0.00 | 01-JAN-00:10 | 12338.77 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.52 | 0.00 | 01-JAN-00:10 | 12338.77 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 141.93 | 0.00 | 01-JAN-00:10 | 17627.39 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 141.93 | 0.00 | 01-JAN-00:10 | 17627.39 | 14-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 131.20 | 0.00 | 01-JAN-00:10 | 19263.10 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.55 | 0.00 | 01-JAN-00:10 | 19263.10 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.55 | 0.00 | 01-JAN-00:10 | 19263.10 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 128.65 | 0.00 | 01-JAN-00:10 | 19115.00 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 128.65 | 0.00 | 01-JAN-00:10 | 19115.00 | 24-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.99 | 0.00 | 01-JAN-00:10 | 6871.67 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.03 | 0.00 | 01-JAN-00:10 | 6871.67 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.03 | 0.00 | 01-JAN-00:10 | 6871.67 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.96 | 0.00 | 01-JAN-00:10 | 6284.14 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.96 | 0.00 | 01-JAN-00:10 | 6284.14 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.33 | 0.00 | 01-JAN-00:10 | 8862.70 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.63 | 0.00 | 01-JAN-00:10 | 5698.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.63 | 0.00 | 01-JAN-00:10 | 5698.55 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.70 | 0.00 | 01-JAN-00:10 | 8862.70 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.70 | 0.00 | 01-JAN-00:10 | 8862.70 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.15 | 0.00 | 01-JAN-00:10 | 13767.91 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.56 | 0.00 | 01-JAN-00:10 | 8662.21 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.56 | 0.00 | 01-JAN-00:10 | 8662.21 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.59 | 0.00 | 01-JAN-00:10 | 13767.91 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.59 | 0.00 | 01-JAN-00:10 | 13767.91 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.65 | 0.00 | 01-JAN-00:10 | 9822.17 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.84 | 0.00 | 01-JAN-00:10 | 5802.18 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.84 | 0.00 | 01-JAN-00:10 | 5802.18 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.81 | 0.00 | 01-JAN-00:10 | 9822.17 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 26.81 | 0.00 | 01-JAN-00:10 | 9822.17 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.33 | 0.00 | 01-JAN-00:40 | 5360.47 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.30 | 0.00 | 01-JAN-00:40 | 5360.47 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.30 | 0.00 | 01-JAN-00:40 | 5360.47 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.03 | 0.00 | 01-JAN-00:20 | 4883.65 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.03 | 0.00 | 01-JAN-00:20 | 4883.65 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.43 | 0.00 | 01-JAN-00:40 | 7282.13 | 24-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.38 | 0.00 | 01-JAN-00:40 | 4518.88 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.38 | 0.00 | 01-JAN-00:40 | 4518.88 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.05 | 0.00 | 01-JAN-00:20 | 7282.13 | 24-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.05 | 0.00 | 01-JAN-00:20 | 7282.13 | 24-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.46 | 0.00 | 01-JAN-00:40 | 13002.33 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.69 | 0.00 | 01-JAN-00:40 | 8621.22 | 26-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.69 | 0.00 | 01-JAN-00:40 | 8621.22 | 26-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.77 | 0.00 | 01-JAN-00:20 | 13002.33 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.77 | 0.00 | 01-JAN-00:20 | 13002.33 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.14 | 0.00 | 01-JAN-00:40 | 7943.06 | 10-AUG-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.40 | 0.00 | 01-JAN-00:40 | 4599.71 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.40 | 0.00 | 01-JAN-00:40 | 4599.71 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.74 | 0.00 | 01-JAN-00:20 | 7943.06 | 10-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.74 | 0.00 | 01-JAN-00:20 | 7943.06 | 10-AUG-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.76 | 0.00 | 01-JAN-00:10 | 5787.20 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.12 | 0.00 | 01-JAN-00:10 | 5696.57 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.12 | 0.00 | 01-JAN-00:10 | 5696.57 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.64 | 0.00 | 01-JAN-00:10 | 5787.20 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.64 | 0.00 | 01-JAN-00:10 | 5787.20 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.06 | 0.00 | 01-JAN-00:10 | 8951.57 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.41 | 0.00 | 01-JAN-00:10 | 4812.33 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.41 | 0.00 | 01-JAN-00:10 | 4812.33 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.65 | 0.00 | 01-JAN-00:10 | 8951.57 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 27.65 | 0.00 | 01-JAN-00:10 | 8951.57 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.26 | 0.00 | 01-JAN-00:10 | 13619.48 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.58 | 0.00 | 01-JAN-00:10 | 7168.30 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.58 | 0.00 | 01-JAN-00:10 | 7168.30 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.67 | 0.00 | 01-JAN-00:10 | 13619.48 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 48.67 | 0.00 | 01-JAN-00:10 | 13619.48 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 29.98 | 0.00 | 01-JAN-00:10 | 9376.00 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.38 | 0.00 | 01-JAN-00:10 | 4807.70 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.38 | 0.00 | 01-JAN-00:10 | 4807.70 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.60 | 0.00 | 01-JAN-00:10 | 9376.00 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 28.60 | 0.00 | 01-JAN-00:10 | 9376.00 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 206.10 | 0.00 | 01-JAN-00:50 | 150545.10 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 464.00 | 0.00 | 01-JAN-00:50 | 214480.23 | 10-AUG-15:20 |
HeatingCoils:EnergyTransfer | 154.62 | 0.00 | 01-JAN-00:50 | 148507.92 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 154.62 | 0.00 | 01-JAN-00:50 | 148507.92 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 154.62 | 0.00 | 01-JAN-00:50 | 148507.92 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 309.39 | 0.00 | 01-JAN-00:10 | 214468.46 | 10-AUG-15:20 |
EnergyTransfer:Plant | 205.02 | 0.00 | 01-JAN-00:50 | 148894.19 | 26-DEC-07:20 |
WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 153.53 | 0.00 | 01-JAN-00:50 | 146857.01 | 26-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.089 | -215.661 | 0.000 | 0.000 | 32.909 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -139.688 |
CORE_MID | 0.000 | 0.000 | 0.518 | -141.927 | 0.000 | 0.000 | 34.197 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -80.142 |
CORE_TOP | 0.000 | 0.000 | 2.553 | -128.647 | 0.000 | 0.000 | 35.053 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -96.313 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.028 | -23.960 | 0.000 | 0.000 | 7.601 | 9.173 | 24.333 | 13.742 | 0.000 | 0.009 | 0.001 | 0.000 | -29.286 | 0.000 | -3.141 | -4.499 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.626 | -25.701 | 0.000 | 0.000 | 4.788 | 5.701 | 15.404 | 26.276 | 0.000 | 0.005 | 0.000 | 0.000 | -18.845 | 0.000 | -2.109 | -9.145 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.558 | -45.593 | 0.000 | 0.000 | 7.497 | 8.864 | 24.332 | 56.853 | 0.000 | 0.007 | 0.001 | 0.000 | -28.918 | 0.000 | -3.253 | -24.348 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.839 | -26.807 | 0.000 | 0.000 | 4.852 | 5.697 | 15.403 | 28.464 | 0.000 | 0.005 | 0.000 | 0.000 | -19.458 | 0.000 | -2.130 | -9.866 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.301 | -23.030 | 0.000 | 0.000 | 7.544 | 9.127 | 24.333 | 13.902 | 0.000 | 0.006 | 0.001 | 0.000 | -30.739 | 0.000 | -1.764 | -1.679 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.383 | -24.049 | 0.000 | 0.000 | 4.727 | 5.685 | 15.404 | 26.292 | 0.000 | 0.003 | 0.001 | 0.000 | -20.037 | 0.000 | -1.203 | -8.205 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 11.688 | -32.768 | 0.000 | 0.000 | 7.606 | 8.839 | 24.332 | 57.343 | 0.000 | 0.383 | 0.000 | 0.000 | -30.645 | 0.000 | -32.432 | -14.348 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.398 | -24.741 | 0.000 | 0.000 | 4.775 | 5.677 | 15.403 | 28.563 | 0.000 | 0.003 | 0.001 | 0.000 | -20.728 | 0.000 | -1.214 | -9.136 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.120 | -26.644 | 0.000 | 0.000 | 7.479 | 9.173 | 24.333 | 13.409 | 0.000 | 0.008 | 4.189 | 0.000 | -31.281 | 0.000 | -2.786 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.406 | -27.654 | 0.000 | 0.000 | 3.509 | 5.701 | 15.404 | 26.036 | 0.000 | 0.005 | 0.001 | 0.000 | -20.010 | 0.000 | -1.862 | -2.535 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.581 | -48.674 | 0.000 | 0.000 | 7.373 | 8.864 | 24.332 | 56.462 | 0.000 | 0.006 | 0.001 | 0.000 | -30.771 | 0.000 | -2.879 | -16.294 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.381 | -28.598 | 0.000 | 0.000 | 4.776 | 5.697 | 15.403 | 28.252 | 0.000 | 0.004 | 0.001 | 0.000 | -20.723 | 0.000 | -1.885 | -4.307 |
TOPFLOOR_PLENUM | 14.647 | -21.980 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.005 | 12.174 | 0.000 | 0.000 | 0.000 | -4.846 | -0.000 |
MIDFLOOR_PLENUM | 6.725 | -12.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.010 | 10.446 | 0.000 | 0.000 | 0.000 | -4.798 | -0.000 |
FIRSTFLOOR_PLENUM | 4.232 | -17.357 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.007 | 17.041 | 0.000 | 0.000 | 0.000 | -3.924 | -0.000 |
Total Facility | 25.604 | -51.719 | 44.471 | -844.454 | 0.000 | 0.000 | 174.687 | 303.983 | 719.689 | 375.594 | 0.000 | 0.467 | 43.858 | 0.000 | -301.442 | 0.000 | -70.225 | -420.506 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -40600.61 | 0.00 | 0.00 | 319.60 | 715.98 | 7410.35 | 0.00 | 0.00 | 0.00 | 32154.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -29267.47 | 0.00 | 0.00 | 710.51 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 23383.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-15:20 | 0.00 | 0.00 | 0.00 | -19115.13 | 0.00 | 0.00 | 3497.10 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 2365.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -6284.18 | 0.00 | 0.00 | 737.22 | 647.98 | 1435.25 | 3606.66 | 0.00 | 20.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -163.06 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:52 | 0.00 | 0.00 | 0.00 | -13853.52 | 0.00 | 0.00 | 15.73 | 22.79 | 302.86 | 9398.97 | 0.00 | 0.00 | 4174.30 | 0.00 | -0.00 | 0.00 | -61.13 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:32 | 0.00 | 0.00 | 0.00 | -22231.94 | 0.00 | 0.00 | 22.29 | 36.00 | 478.41 | 13911.04 | 0.00 | 0.00 | 7858.53 | 0.00 | -0.00 | 0.00 | -74.33 | 0.00 |
PERIMETER_TOP_ZN_4 | 10-SEP-16:12 | 0.00 | 0.00 | 0.00 | -15818.73 | 0.00 | 0.00 | 14.06 | 22.79 | 302.86 | 11438.41 | 0.00 | 0.00 | 4082.07 | 0.00 | -0.00 | 0.00 | -41.45 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -4883.61 | 0.00 | 0.00 | 737.22 | 647.98 | 1435.25 | 3653.33 | 0.00 | 10.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1600.96 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:42 | 0.00 | 0.00 | 0.00 | -11665.64 | 0.00 | 0.00 | 16.35 | 22.79 | 302.86 | 10474.52 | 0.00 | 0.00 | 906.12 | 0.00 | -0.00 | 0.00 | -57.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 30-JUL-14:12 | 0.00 | 0.00 | 0.00 | -16908.40 | 0.00 | 0.00 | 26.50 | 36.00 | 478.41 | 9579.89 | 0.00 | 0.00 | 6788.62 | 0.00 | -0.00 | 0.00 | -1.02 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-17:31 | 0.00 | 0.00 | 0.00 | -13955.48 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 11487.64 | 0.00 | 0.00 | 2213.96 | 0.00 | -0.00 | 0.00 | -13.32 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -5787.19 | 0.00 | 0.00 | 737.22 | 647.98 | 1435.25 | 3625.50 | 0.00 | 16.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -675.59 |
PERIMETER_MID_ZN_2 | 30-JUL-08:52 | 0.00 | 0.00 | 0.00 | -14830.36 | 0.00 | 0.00 | 14.15 | 22.79 | 302.86 | 10346.31 | 0.00 | 0.00 | 4189.15 | 0.00 | -0.00 | 0.00 | -44.89 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:12 | 0.00 | 0.00 | 0.00 | -19556.94 | 0.00 | 0.00 | 24.66 | 36.00 | 478.41 | 13046.33 | 0.00 | 0.00 | 5989.28 | 0.00 | -0.00 | 0.00 | -17.75 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-16:41 | 0.00 | 0.00 | 0.00 | -16063.62 | 0.00 | 0.00 | 12.63 | 22.79 | 302.86 | 12228.57 | 0.00 | 0.00 | 3531.16 | 0.00 | -0.00 | 0.00 | -34.39 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:50 | 0.00 | -10159.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 10141.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-15:30 | 0.00 | -4531.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 4521.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-16:00 | 0.00 | -5070.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 5063.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-15:20 | 0.00 | -19442.92 | 0.00 | -140507.98 | 0.00 | 0.00 | 17714.89 | 25681.07 | 41670.51 | 69321.20 | 0.00 | 850.87 | 4712.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 6509.58 | 0.00 | 0.00 | 0.00 | 500.32 | 715.98 | 7410.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15136.22 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 13492.94 | 0.00 | 0.00 | 0.00 | 525.36 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17760.20 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 20946.39 | 0.00 | 0.00 | 0.00 | 536.35 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25224.64 |
PERIMETER_TOP_ZN_3 | 21-FEB-05:51 | 0.00 | 0.00 | 7625.18 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1668.47 | 0.00 | -128.18 | -6387.97 |
PERIMETER_TOP_ZN_2 | 21-FEB-05:51 | 0.00 | 0.00 | 6921.01 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1112.27 | 0.00 | -86.41 | -6076.48 |
PERIMETER_TOP_ZN_1 | 21-FEB-05:51 | 0.00 | 0.00 | 10229.50 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1671.91 | 0.00 | -132.39 | -8984.64 |
PERIMETER_TOP_ZN_4 | 21-FEB-05:51 | 0.00 | 0.00 | 7116.45 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1095.74 | 0.00 | -87.08 | -6287.78 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 5789.35 | 0.00 | 0.00 | 0.00 | 113.18 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1129.29 | 0.00 | -34.89 | -5527.16 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5262.86 | 0.00 | 0.00 | 0.00 | 71.65 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -767.90 | 0.00 | -23.57 | -5042.40 |
PERIMETER_BOT_ZN_1 | 26-DEC-07:50 | 0.00 | 0.00 | 8620.09 | 0.00 | 0.00 | 0.00 | 231.29 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 6353.44 | 0.00 | -2166.57 | 0.00 | -14128.94 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5437.84 | 0.00 | 0.00 | 0.00 | 71.65 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -750.55 | 0.00 | -23.61 | -5234.69 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 6187.17 | 0.00 | 0.00 | 0.00 | 113.18 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1134.50 | 0.00 | -54.84 | -5899.82 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5759.25 | 0.00 | 0.00 | 0.00 | 71.65 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -774.41 | 0.00 | -37.14 | -5518.71 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 8440.78 | 0.00 | 0.00 | 0.00 | 113.18 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.51 | 0.00 | -55.54 | -8123.72 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5776.38 | 0.00 | 0.00 | 0.00 | 71.65 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -755.05 | 0.00 | -37.15 | -5555.19 |
TOPFLOOR_PLENUM | 26-DEC-06:09 | 11296.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10.42 | -11286.37 |
MIDFLOOR_PLENUM | 02-JAN-08:20 | 8843.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.00 | -8776.56 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 7515.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -49.21 | -7466.47 |
Total Facility | 02-JAN-06:11 | 6530.26 | 0.00 | 122474.29 | 0.00 | 0.00 | 0.00 | 2670.98 | 3626.85 | 19712.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11362.79 | 0.00 | -1872.71 | -141779.25 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6398 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9264 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.5110 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5898 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7679 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1657 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8199 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4229 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7555 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4743 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8840 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5319 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7348 | 2.7348 | 0.7794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2092 | 2.2092 | 0.7644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2540 | 2.2540 | 0.7889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6289 | 0.6289 | 0.1660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8038 | 0.8038 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2033 | 1.2033 | 0.2407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8779 | 0.8779 | 0.1756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5077 | 0.5077 | 0.1640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6679 | 0.6679 | 0.1336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9922 | 0.9922 | 0.1984 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7373 | 0.7373 | 0.1475 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5572 | 0.5572 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8041 | 0.8041 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1195 | 1.1195 | 0.2239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8210 | 0.8210 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6398 | 4.9264 | 5.6398 | 1.4229 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.5110 | 4.5898 | 5.5110 | 1.4743 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7679 | 5.1657 | 5.7679 | 1.5319 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3674 | 1.3674 | 0.7794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1046 | 1.1046 | 0.7644 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1270 | 1.1270 | 0.7889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3145 | 0.3145 | 0.1660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4019 | 0.4019 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6017 | 0.6017 | 0.2407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4390 | 0.4390 | 0.1756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2538 | 0.2538 | 0.1640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3339 | 0.3339 | 0.1336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4961 | 0.4961 | 0.1984 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3687 | 0.3687 | 0.1475 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2786 | 0.2786 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4021 | 0.4021 | 0.1608 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5598 | 0.5598 | 0.2239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4105 | 0.4105 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8199 | 1.4229 | 1.4229 | 1.4229 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7555 | 1.4743 | 1.4743 | 1.4743 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8840 | 1.5319 | 1.5319 | 1.5319 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 306.50 |
Number of hours cooling loads not met | 45.67 |
Number of hours not met | 352.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 226.92 | 185997.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 70.33 | 53443.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 303.98 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.64 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 79.67 | 27002.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.13 | 568.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 54.28 | 6514.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1307.63 |
Natural Gas | 0.00 | 226.92 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1534.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 61.01 |
Space Heating | 0.00 |
Space Cooling | 14.12 |
Fans (All) | 15.99 |
Service Water Heating | 10.90 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 262.46 |
Subtotal | 262.46 |
Natural Gas [MJ/m2] | |
Space Heating | 45.55 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 45.55 |
Subtotal | 45.55 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.81 |
Space Heating | 14.79 |
Space Cooling | 4.58 |
Fans (All) | 5.19 |
Service Water Heating | 3.54 |
Receptacle Equipment | 46.90 |
Miscellaneous | 5.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8698.83 | 61.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8739.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8698.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 61.17 | 0.00 | 0.00 | 0.00 |
Average | 8746.84 | 13.16 | 0.00 | 0.00 | 0.00 |
Sum | 157443.17 | 236.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128275.33 | 28.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 28.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.74 | 1.59 | 0.00 | 0.00 | 0.00 |
Sum | 614551.33 | 28.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8581.67 | 178.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8581.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 178.33 | 0.00 | 0.00 | 0.00 |
Average | 8732.97 | 27.03 | 0.00 | 0.00 | 0.00 |
Sum | 157193.50 | 486.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128203.67 | 100.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128299.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128299.33 | 100.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.07 | 6.26 | 0.00 | 0.00 | 0.00 |
Sum | 614467.33 | 112.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985543E+10 | 11809.99 | 13-JAN-17:00 | 2.20 | 1.77 | 0.186054E+10 | 2606.60 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.108597E+11 | 14969.83 | 28-FEB-17:00 | 14.40 | 10.82 | 0.177426E+10 | 2606.64 | 09-FEB-10:09 | 14.40 | 10.82 |
March | 0.158684E+11 | 17025.71 | 02-MAR-17:00 | 12.80 | 8.57 | 0.215031E+10 | 2606.66 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.172335E+11 | 36721.64 | 28-APR-06:02 | 11.10 | 10.22 | 0.191592E+10 | 2606.65 | 27-APR-13:20 | 11.10 | 10.22 |
May | 0.221474E+11 | 37258.86 | 08-MAY-06:03 | 9.90 | 9.62 | 0.207741E+10 | 2606.68 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.238654E+11 | 39552.48 | 29-JUN-05:12 | 12.80 | 11.40 | 0.207217E+10 | 2606.71 | 05-JUN-13:00 | 12.80 | 11.40 |
July | 0.245775E+11 | 40612.30 | 17-JUL-05:12 | 14.07 | 12.34 | 0.192780E+10 | 2606.64 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.266453E+11 | 40236.62 | 11-AUG-05:12 | 13.40 | 12.29 | 0.216246E+10 | 2606.90 | 09-AUG-09:00 | 13.40 | 12.29 |
September | 0.220846E+11 | 38666.19 | 05-SEP-06:02 | 11.02 | 9.56 | 0.192026E+10 | 2606.66 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.180313E+11 | 37535.15 | 10-OCT-06:02 | 12.12 | 10.88 | 0.199234E+10 | 2606.65 | 05-OCT-09:00 | 12.12 | 10.88 |
November | 0.132184E+11 | 17269.00 | 06-NOV-17:00 | 11.70 | 10.80 | 0.195724E+10 | 2606.63 | 10-NOV-10:20 | 7.07 | 5.84 |
December | 0.112750E+11 | 14062.18 | 06-DEC-15:50 | 3.58 | 3.15 | 0.187465E+10 | 2606.64 | 12-DEC-10:20 | 3.87 | 3.71 |
Annual Sum or Average | 0.215662E+12 | 0.236854E+11 | ||||||||
Minimum of Months | 0.985543E+10 | 11809.99 | 2.20 | 1.77 | 0.177426E+10 | 2606.60 | 3.87 | 3.71 | ||
Maximum of Months | 0.266453E+11 | 40612.30 | 14.40 | 12.34 | 0.216246E+10 | 2606.90 | 21.10 | 15.48 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 462652.30 | 246.89 | 11-JAN-17:20 | 12.40 | 9.38 | 0.00 | 0.00 | 01-JAN-00:10 | 12.40 | 9.38 |
February | 0.101068E+09 | 2085.25 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.579680E+09 | 3045.56 | 14-MAR-15:00 | 16.10 | 10.31 | 0.00 | 0.00 | 01-MAR-00:10 | 16.10 | 10.31 |
April | 0.161491E+10 | 8553.18 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.289917E+10 | 8815.11 | 15-MAY-14:30 | 23.30 | 13.06 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.06 |
June | 0.372030E+10 | 8826.98 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.489417E+10 | 9964.81 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.477860E+10 | 10160.22 | 10-AUG-14:50 | 30.07 | 18.95 | 0.00 | 0.00 | 01-AUG-00:10 | 30.07 | 18.95 |
September | 0.255567E+10 | 7899.03 | 14-SEP-14:30 | 23.90 | 17.04 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.04 |
October | 0.758269E+09 | 5553.08 | 04-OCT-14:40 | 21.50 | 11.47 | 0.00 | 0.00 | 01-OCT-00:10 | 21.50 | 11.47 |
November | 73972753.74 | 2502.75 | 04-NOV-14:10 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 4137111.78 | 439.53 | 02-DEC-14:50 | 11.78 | 5.57 | 0.00 | 0.00 | 01-DEC-00:10 | 11.78 | 5.57 |
Annual Sum or Average | 0.219804E+11 | 0.00 | ||||||||
Minimum of Months | 462652.30 | 246.89 | 11.78 | 5.57 | 0.00 | 0.00 | 11.78 | 5.57 | ||
Maximum of Months | 0.489417E+10 | 10160.22 | 30.07 | 18.95 | 0.00 | 0.00 | 30.07 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14428524.43 | 1844.32 | 14-JAN-06:11 | 2.20 | 1.14 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.14 |
February | 0.113226E+09 | 2035.28 | 04-FEB-07:03 | 7.30 | 6.18 | 0.00 | 0.00 | 01-FEB-00:10 | 7.30 | 6.18 |
March | 0.350085E+09 | 2651.61 | 02-MAR-07:02 | 0.78 | -0.1 | 0.00 | 0.00 | 01-MAR-00:10 | 0.78 | -0.1 |
April | 0.700576E+09 | 2941.17 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.131319E+10 | 3065.21 | 15-MAY-15:30 | 23.60 | 12.74 | 0.00 | 0.00 | 01-MAY-00:10 | 23.60 | 12.74 |
June | 0.197681E+10 | 3463.81 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.263568E+10 | 4447.06 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.295417E+10 | 4531.76 | 14-AUG-15:30 | 27.25 | 17.25 | 0.00 | 0.00 | 01-AUG-00:10 | 27.25 | 17.25 |
September | 0.159241E+10 | 3547.58 | 14-SEP-15:50 | 24.32 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 24.32 | 17.03 |
October | 0.573988E+09 | 2361.92 | 28-OCT-06:03 | 7.80 | 6.34 | 0.00 | 0.00 | 01-OCT-00:10 | 7.80 | 6.34 |
November | 0.135351E+09 | 1809.12 | 09-NOV-07:03 | 6.70 | 5.68 | 0.00 | 0.00 | 01-NOV-00:10 | 6.70 | 5.68 |
December | 21990206.76 | 1647.71 | 02-DEC-06:11 | 4.97 | 2.41 | 0.00 | 0.00 | 01-DEC-00:10 | 4.97 | 2.41 |
Annual Sum or Average | 0.123819E+11 | 0.00 | ||||||||
Minimum of Months | 14428524.43 | 1647.71 | 0.78 | -0.1 | 0.00 | 0.00 | 0.78 | -0.1 | ||
Maximum of Months | 0.295417E+10 | 4531.76 | 28.50 | 19.00 | 0.00 | 0.00 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81905788.26 | 2308.47 | 13-JAN-06:11 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 0.201717E+09 | 2472.43 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.575024E+09 | 3216.89 | 02-MAR-07:02 | 0.78 | -0.1 | 0.00 | 0.00 | 01-MAR-00:10 | 0.78 | -0.1 |
April | 0.111375E+10 | 3442.70 | 28-APR-06:06 | 11.10 | 10.22 | 0.00 | 0.00 | 01-APR-00:10 | 11.10 | 10.22 |
May | 0.197430E+10 | 3651.13 | 08-MAY-06:08 | 9.90 | 9.62 | 0.00 | 0.00 | 01-MAY-00:10 | 9.90 | 9.62 |
June | 0.264075E+10 | 3884.09 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.331007E+10 | 4973.89 | 31-JUL-16:00 | 28.90 | 19.18 | 0.00 | 0.00 | 01-JUL-00:10 | 28.90 | 19.18 |
August | 0.372477E+10 | 5070.97 | 14-AUG-16:00 | 27.50 | 16.95 | 0.00 | 0.00 | 01-AUG-00:10 | 27.50 | 16.95 |
September | 0.231985E+10 | 4373.81 | 11-SEP-16:00 | 23.30 | 16.14 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.14 |
October | 0.101267E+10 | 3208.54 | 05-OCT-06:06 | 8.48 | 5.36 | 0.00 | 0.00 | 01-OCT-00:10 | 8.48 | 5.36 |
November | 0.280689E+09 | 2660.26 | 10-NOV-07:02 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 0.121765E+09 | 2151.95 | 07-DEC-07:03 | 6.10 | 3.18 | 0.00 | 0.00 | 01-DEC-00:10 | 6.10 | 3.18 |
Annual Sum or Average | 0.173573E+11 | 0.00 | ||||||||
Minimum of Months | 81905788.26 | 2151.95 | 0.60 | -0.1 | 0.00 | 0.00 | 0.60 | -0.1 | ||
Maximum of Months | 0.372477E+10 | 5070.97 | 28.90 | 19.18 | 0.00 | 0.00 | 28.90 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.677852E+10 | 6959.14 | 12-JAN-17:00 | 7.20 | 5.41 | 0.161207E+10 | 2374.76 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.746272E+10 | 7910.31 | 28-FEB-17:00 | 14.40 | 10.82 | 0.155279E+10 | 2573.09 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.101205E+11 | 9568.31 | 02-MAR-17:00 | 12.80 | 8.57 | 0.200651E+10 | 2606.57 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.109972E+11 | 14910.01 | 27-APR-16:00 | 27.20 | 16.90 | 0.185874E+10 | 2606.64 | 14-APR-09:09 | 27.20 | 16.90 |
May | 0.144327E+11 | 15366.77 | 15-MAY-16:00 | 23.90 | 12.85 | 0.205533E+10 | 2606.66 | 05-MAY-09:09 | 23.90 | 12.85 |
June | 0.160366E+11 | 21474.95 | 12-JUN-06:02 | 14.60 | 13.50 | 0.205972E+10 | 2606.68 | 09-JUN-13:09 | 14.60 | 13.50 |
July | 0.168147E+11 | 22945.59 | 25-JUL-05:12 | 13.90 | 13.23 | 0.191848E+10 | 2606.64 | 11-JUL-09:09 | 13.90 | 13.23 |
August | 0.182297E+11 | 29269.19 | 14-AUG-06:02 | 15.47 | 13.75 | 0.215339E+10 | 2606.83 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.141019E+11 | 16243.73 | 11-SEP-16:00 | 23.30 | 16.14 | 0.190200E+10 | 2606.65 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.109589E+11 | 14427.44 | 04-OCT-16:00 | 21.10 | 11.40 | 0.191420E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.843071E+10 | 8469.41 | 06-NOV-17:00 | 11.70 | 10.80 | 0.175226E+10 | 2606.60 | 06-NOV-14:39 | 11.70 | 10.80 |
December | 0.756337E+10 | 7325.39 | 06-DEC-16:20 | 2.57 | 2.27 | 0.161173E+10 | 2478.74 | 06-DEC-14:00 | 2.57 | 2.27 |
Annual Sum or Average | 0.141927E+12 | 0.223972E+11 | ||||||||
Minimum of Months | 0.677852E+10 | 6959.14 | 2.57 | 2.27 | 0.155279E+10 | 2374.76 | 2.57 | 2.27 | ||
Maximum of Months | 0.182297E+11 | 29269.19 | 27.20 | 16.90 | 0.215339E+10 | 2606.83 | 27.20 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487835E+10 | 6696.18 | 11-JAN-17:00 | 12.20 | 9.27 | 0.152907E+10 | 2261.05 | 11-JAN-14:00 | 12.20 | 9.27 |
February | 0.602625E+10 | 7737.72 | 28-FEB-17:00 | 14.40 | 10.82 | 0.145395E+10 | 2492.25 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.920414E+10 | 8572.44 | 02-MAR-17:00 | 12.80 | 8.57 | 0.187335E+10 | 2570.46 | 02-MAR-14:00 | 12.80 | 8.57 |
April | 0.103364E+11 | 16284.96 | 27-APR-15:50 | 27.20 | 16.97 | 0.178107E+10 | 2606.64 | 27-APR-13:50 | 27.20 | 16.97 |
May | 0.136214E+11 | 16945.92 | 15-MAY-16:00 | 23.90 | 12.85 | 0.201923E+10 | 2606.66 | 05-MAY-09:09 | 23.90 | 12.85 |
June | 0.154989E+11 | 17799.86 | 28-JUN-16:00 | 26.10 | 16.29 | 0.204388E+10 | 2606.68 | 09-JUN-13:09 | 26.10 | 16.29 |
July | 0.165306E+11 | 19115.00 | 24-JUL-15:20 | 30.03 | 18.73 | 0.190806E+10 | 2606.64 | 20-JUL-13:09 | 30.03 | 18.73 |
August | 0.176812E+11 | 19102.45 | 14-AUG-15:30 | 27.25 | 17.25 | 0.214254E+10 | 2606.82 | 09-AUG-09:00 | 27.25 | 17.25 |
September | 0.129491E+11 | 17069.28 | 14-SEP-15:50 | 24.32 | 17.03 | 0.186405E+10 | 2606.61 | 07-SEP-13:09 | 24.32 | 17.03 |
October | 0.968017E+10 | 14239.63 | 04-OCT-16:00 | 21.10 | 11.40 | 0.180567E+10 | 2606.60 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.686534E+10 | 7579.10 | 02-NOV-16:00 | 13.30 | 10.88 | 0.161938E+10 | 2448.85 | 02-NOV-13:00 | 13.30 | 10.88 |
December | 0.537578E+10 | 7012.47 | 05-DEC-16:00 | 6.10 | 4.53 | 0.150067E+10 | 2330.90 | 05-DEC-14:00 | 6.10 | 4.53 |
Annual Sum or Average | 0.128648E+12 | 0.215409E+11 | ||||||||
Minimum of Months | 0.487835E+10 | 6696.18 | 6.10 | 4.53 | 0.145395E+10 | 2261.05 | 6.10 | 4.53 | ||
Maximum of Months | 0.176812E+11 | 19115.00 | 30.03 | 18.73 | 0.214254E+10 | 2606.82 | 30.03 | 18.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205247E+09 | 1226.26 | 11-JAN-16:20 | 13.67 | 10.10 | 0.305879E+09 | 433.61 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.516367E+09 | 1507.11 | 27-FEB-16:20 | 19.23 | 12.34 | 0.284821E+09 | 501.24 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.130330E+10 | 1593.79 | 10-MAR-14:50 | 16.20 | 11.59 | 0.361624E+09 | 525.61 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.189433E+10 | 4520.89 | 27-APR-15:20 | 27.20 | 17.16 | 0.353711E+09 | 549.50 | 27-APR-13:00 | 27.20 | 17.16 |
May | 0.295633E+10 | 4739.53 | 15-MAY-14:30 | 23.30 | 13.06 | 0.413056E+09 | 549.50 | 15-MAY-13:09 | 23.30 | 13.06 |
June | 0.361157E+10 | 5214.89 | 21-JUN-15:30 | 24.70 | 15.68 | 0.425515E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.413958E+10 | 6284.14 | 24-JUL-15:00 | 30.60 | 18.78 | 0.399458E+09 | 549.50 | 20-JUL-13:09 | 30.60 | 18.78 |
August | 0.424211E+10 | 5725.22 | 09-AUG-15:20 | 28.47 | 18.71 | 0.447345E+09 | 549.54 | 09-AUG-09:00 | 28.47 | 18.71 |
September | 0.260346E+10 | 4295.41 | 12-SEP-15:00 | 24.40 | 16.71 | 0.378389E+09 | 549.49 | 12-SEP-13:00 | 24.40 | 16.71 |
October | 0.154762E+10 | 2684.03 | 04-OCT-15:30 | 21.40 | 11.45 | 0.350441E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.692072E+09 | 1439.31 | 02-NOV-14:40 | 13.67 | 11.26 | 0.313438E+09 | 484.05 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.247779E+09 | 1145.75 | 29-DEC-16:00 | 10.60 | 8.76 | 0.295539E+09 | 419.49 | 05-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.239598E+11 | 0.432921E+10 | ||||||||
Minimum of Months | 0.205247E+09 | 1145.75 | 10.60 | 8.76 | 0.284821E+09 | 419.49 | 10.60 | 8.76 | ||
Maximum of Months | 0.424211E+10 | 6284.14 | 30.60 | 18.78 | 0.447345E+09 | 549.54 | 30.60 | 18.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200984E+09 | 1099.56 | 20-JAN-10:45 | 5.32 | 3.17 | 0.193593E+09 | 265.33 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.555390E+09 | 1415.66 | 27-FEB-15:50 | 19.50 | 12.39 | 0.181740E+09 | 309.18 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.135961E+10 | 2716.03 | 14-MAR-09:45 | 9.63 | 7.44 | 0.235525E+09 | 347.88 | 02-MAR-10:09 | 9.63 | 7.44 |
April | 0.221920E+10 | 6710.31 | 27-APR-09:20 | 18.17 | 12.47 | 0.234134E+09 | 347.88 | 20-APR-09:00 | 18.17 | 12.47 |
May | 0.310735E+10 | 6926.99 | 15-MAY-09:10 | 17.48 | 11.96 | 0.262953E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.397774E+10 | 13854.65 | 25-JUN-08:52 | 16.70 | 12.03 | 0.270238E+09 | 347.88 | 09-JUN-13:09 | 16.70 | 12.03 |
July | 0.426289E+10 | 12667.41 | 30-JUL-09:02 | 20.87 | 15.88 | 0.252713E+09 | 348.34 | 31-JUL-09:39 | 22.93 | 17.42 |
August | 0.457266E+10 | 12890.34 | 13-AUG-09:12 | 21.50 | 16.14 | 0.283760E+09 | 348.42 | 10-AUG-09:00 | 21.50 | 16.14 |
September | 0.293467E+10 | 10433.76 | 10-SEP-10:13 | 17.77 | 13.72 | 0.240230E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.160261E+10 | 4749.71 | 04-OCT-09:20 | 16.13 | 10.66 | 0.226064E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.630492E+09 | 1411.51 | 02-NOV-10:40 | 12.43 | 10.47 | 0.197137E+09 | 304.32 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.277270E+09 | 1193.60 | 05-DEC-10:25 | 7.50 | 5.28 | 0.187326E+09 | 278.99 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.257009E+11 | 0.276541E+10 | ||||||||
Minimum of Months | 0.200984E+09 | 1099.56 | 5.32 | 3.17 | 0.181740E+09 | 265.33 | 5.32 | 3.17 | ||
Maximum of Months | 0.457266E+10 | 13854.65 | 21.50 | 16.14 | 0.283760E+09 | 348.42 | 22.93 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801879E+09 | 6922.77 | 20-JAN-13:25 | 6.70 | 4.72 | 0.317691E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.155812E+10 | 8862.26 | 27-FEB-14:30 | 19.15 | 11.80 | 0.308573E+09 | 549.49 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.310739E+10 | 10004.74 | 14-MAR-13:40 | 15.20 | 10.17 | 0.386420E+09 | 549.50 | 02-MAR-14:00 | 15.20 | 10.17 |
April | 0.397804E+10 | 12108.75 | 27-APR-13:10 | 26.10 | 16.37 | 0.364824E+09 | 549.51 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.493215E+10 | 18064.91 | 14-MAY-13:43 | 22.70 | 12.26 | 0.409893E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.530830E+10 | 9443.97 | 28-JUN-13:10 | 24.50 | 15.71 | 0.419538E+09 | 549.51 | 09-JUN-13:09 | 24.50 | 15.71 |
July | 0.638254E+10 | 18067.63 | 23-JUL-13:32 | 27.23 | 16.89 | 0.395171E+09 | 549.52 | 20-JUL-13:09 | 27.23 | 16.89 |
August | 0.724261E+10 | 18511.76 | 13-AUG-13:12 | 26.73 | 18.53 | 0.444196E+09 | 550.34 | 29-AUG-13:20 | 29.17 | 20.09 |
September | 0.597100E+10 | 22231.54 | 10-SEP-13:32 | 21.67 | 14.47 | 0.379257E+09 | 549.97 | 15-SEP-13:39 | 21.70 | 16.54 |
October | 0.380779E+10 | 17143.91 | 08-OCT-13:02 | 18.17 | 13.70 | 0.367326E+09 | 549.83 | 04-OCT-13:00 | 18.17 | 13.70 |
November | 0.146761E+10 | 8976.40 | 04-NOV-13:30 | 20.85 | 16.00 | 0.326611E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.103621E+10 | 6983.43 | 05-DEC-12:30 | 10.30 | 6.13 | 0.314058E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.455936E+11 | 0.443356E+10 | ||||||||
Minimum of Months | 0.801879E+09 | 6922.77 | 6.70 | 4.72 | 0.308573E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.724261E+10 | 22231.54 | 27.23 | 18.53 | 0.444196E+09 | 550.34 | 29.17 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222388E+09 | 1441.25 | 05-JAN-15:50 | 6.20 | 4.71 | 0.194293E+09 | 290.17 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.542891E+09 | 3502.44 | 27-FEB-15:30 | 19.70 | 12.30 | 0.182959E+09 | 347.83 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.138563E+10 | 5201.56 | 14-MAR-16:00 | 17.20 | 10.94 | 0.227569E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.226649E+10 | 8217.78 | 26-APR-16:00 | 24.40 | 14.49 | 0.218654E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.339671E+10 | 14878.63 | 14-MAY-16:22 | 23.05 | 11.91 | 0.253680E+09 | 347.85 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.379439E+10 | 12018.50 | 18-JUN-16:52 | 17.20 | 12.22 | 0.262135E+09 | 347.85 | 09-JUN-13:09 | 17.20 | 12.22 |
July | 0.480108E+10 | 15671.72 | 23-JUL-16:52 | 26.70 | 15.58 | 0.248720E+09 | 347.85 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.464877E+10 | 15054.84 | 06-AUG-16:52 | 23.40 | 15.11 | 0.278214E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.318936E+10 | 15818.29 | 10-SEP-16:12 | 22.20 | 14.38 | 0.232511E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.167311E+10 | 6653.72 | 04-OCT-16:00 | 21.10 | 11.40 | 0.216769E+09 | 347.83 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.612529E+09 | 2497.36 | 04-NOV-15:30 | 20.55 | 15.94 | 0.196605E+09 | 319.66 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.274089E+09 | 1560.15 | 05-DEC-15:40 | 7.40 | 5.40 | 0.188547E+09 | 306.82 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.268074E+11 | 0.270066E+10 | ||||||||
Minimum of Months | 0.222388E+09 | 1441.25 | 6.20 | 4.71 | 0.182959E+09 | 290.17 | 6.10 | 4.61 | ||
Maximum of Months | 0.480108E+10 | 15818.29 | 26.70 | 15.94 | 0.278214E+09 | 347.88 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328235E+09 | 1191.75 | 11-JAN-16:20 | 13.67 | 10.10 | 0.307271E+09 | 431.27 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.645163E+09 | 1398.39 | 28-FEB-15:00 | 13.90 | 10.81 | 0.285336E+09 | 481.92 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.146938E+10 | 1452.77 | 10-MAR-14:40 | 16.30 | 11.68 | 0.361777E+09 | 495.53 | 10-MAR-14:50 | 16.20 | 11.59 |
April | 0.178686E+10 | 2696.07 | 27-APR-16:00 | 27.20 | 16.90 | 0.350236E+09 | 549.49 | 27-APR-13:00 | 27.20 | 16.90 |
May | 0.248672E+10 | 3213.76 | 05-MAY-15:30 | 24.70 | 17.20 | 0.416374E+09 | 549.49 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.299874E+10 | 3970.09 | 21-JUN-15:40 | 24.80 | 15.84 | 0.428551E+09 | 549.50 | 09-JUN-13:09 | 24.80 | 15.84 |
July | 0.350114E+10 | 4883.65 | 24-JUL-15:00 | 30.60 | 18.78 | 0.401946E+09 | 549.50 | 21-JUL-13:00 | 30.60 | 18.78 |
August | 0.372142E+10 | 4550.20 | 09-AUG-15:30 | 28.70 | 18.83 | 0.450719E+09 | 549.53 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.249529E+10 | 3383.15 | 14-SEP-15:50 | 24.32 | 17.03 | 0.388774E+09 | 549.49 | 14-SEP-09:09 | 24.32 | 17.03 |
October | 0.186664E+10 | 2104.91 | 04-OCT-15:30 | 21.40 | 11.45 | 0.368978E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.118812E+10 | 1471.97 | 06-NOV-12:00 | 13.90 | 10.05 | 0.327454E+09 | 496.77 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.542760E+09 | 1169.26 | 29-DEC-16:10 | 10.40 | 8.63 | 0.298957E+09 | 427.58 | 29-DEC-14:20 | 10.40 | 8.63 |
Annual Sum or Average | 0.230305E+11 | 0.438637E+10 | ||||||||
Minimum of Months | 0.328235E+09 | 1169.26 | 10.40 | 8.63 | 0.285336E+09 | 427.58 | 10.40 | 8.63 | ||
Maximum of Months | 0.372142E+10 | 4883.65 | 30.60 | 18.83 | 0.450719E+09 | 549.53 | 30.60 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288421E+09 | 949.20 | 20-JAN-10:45 | 5.32 | 3.17 | 0.194540E+09 | 271.57 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.598040E+09 | 1147.32 | 27-FEB-15:40 | 19.60 | 12.34 | 0.184422E+09 | 306.44 | 27-FEB-10:00 | 19.60 | 12.34 |
March | 0.134203E+10 | 1587.83 | 14-MAR-10:00 | 10.00 | 7.75 | 0.240240E+09 | 347.88 | 02-MAR-10:09 | 10.00 | 7.75 |
April | 0.189373E+10 | 5049.15 | 27-APR-09:30 | 18.35 | 12.60 | 0.237620E+09 | 347.88 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.257156E+10 | 7828.79 | 15-MAY-06:02 | 11.97 | 9.44 | 0.267806E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.343945E+10 | 9839.85 | 25-JUN-08:52 | 16.70 | 12.03 | 0.273683E+09 | 347.88 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.377219E+10 | 11665.81 | 23-JUL-08:42 | 18.72 | 13.76 | 0.255212E+09 | 348.14 | 31-JUL-09:39 | 22.93 | 17.42 |
August | 0.424926E+10 | 8990.13 | 14-AUG-06:02 | 15.47 | 13.75 | 0.286560E+09 | 348.20 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.274181E+10 | 5781.35 | 11-SEP-09:30 | 17.80 | 13.71 | 0.248156E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.173520E+10 | 4022.48 | 04-OCT-08:30 | 14.75 | 10.13 | 0.239958E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.939046E+09 | 1248.65 | 02-NOV-10:40 | 12.43 | 10.47 | 0.207040E+09 | 317.56 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.478281E+09 | 1092.12 | 05-DEC-10:25 | 7.50 | 5.28 | 0.190338E+09 | 297.35 | 05-DEC-10:30 | 7.50 | 5.28 |
Annual Sum or Average | 0.240490E+11 | 0.282558E+10 | ||||||||
Minimum of Months | 0.288421E+09 | 949.20 | 5.32 | 3.17 | 0.184422E+09 | 271.57 | 5.32 | 3.17 | ||
Maximum of Months | 0.424926E+10 | 11665.81 | 19.60 | 13.76 | 0.286560E+09 | 348.20 | 26.10 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318714E+09 | 1978.53 | 20-JAN-13:50 | 6.70 | 4.72 | 0.300662E+09 | 537.98 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.865427E+09 | 5967.19 | 27-FEB-13:08 | 17.88 | 11.31 | 0.293366E+09 | 549.51 | 07-FEB-14:09 | 17.88 | 11.31 |
March | 0.183199E+10 | 6133.38 | 02-MAR-13:20 | 12.57 | 7.60 | 0.367376E+09 | 549.50 | 28-MAR-13:09 | 11.20 | 4.56 |
April | 0.246133E+10 | 9339.53 | 27-APR-13:40 | 26.10 | 16.65 | 0.349332E+09 | 549.51 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.311675E+10 | 10645.61 | 14-MAY-13:53 | 22.80 | 12.27 | 0.396964E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.355477E+10 | 7215.18 | 28-JUN-13:30 | 24.70 | 15.69 | 0.410567E+09 | 549.52 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.487753E+10 | 16907.99 | 30-JUL-14:12 | 26.87 | 17.81 | 0.393576E+09 | 549.60 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.626648E+10 | 13820.39 | 06-AUG-13:53 | 22.60 | 15.75 | 0.443563E+09 | 549.91 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.472767E+10 | 15578.35 | 10-SEP-13:42 | 21.93 | 14.56 | 0.380281E+09 | 549.95 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.301018E+10 | 14856.50 | 08-OCT-13:43 | 19.63 | 14.09 | 0.369154E+09 | 549.68 | 03-OCT-13:00 | 19.63 | 14.09 |
November | 0.112274E+10 | 6661.19 | 04-NOV-13:40 | 20.93 | 15.98 | 0.318525E+09 | 549.50 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.614727E+09 | 4160.37 | 05-DEC-12:00 | 10.00 | 6.07 | 0.301010E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.327683E+11 | 0.432438E+10 | ||||||||
Minimum of Months | 0.318714E+09 | 1978.53 | 6.70 | 4.72 | 0.293366E+09 | 537.98 | 6.78 | 4.56 | ||
Maximum of Months | 0.626648E+10 | 16907.99 | 26.87 | 17.81 | 0.443563E+09 | 549.95 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289025E+09 | 1172.37 | 20-JAN-15:50 | 5.87 | 4.23 | 0.194949E+09 | 284.06 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.611800E+09 | 2199.45 | 27-FEB-15:40 | 19.60 | 12.34 | 0.183678E+09 | 343.94 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.139235E+10 | 2973.14 | 02-MAR-16:30 | 13.05 | 8.47 | 0.230682E+09 | 345.03 | 02-MAR-14:00 | 13.05 | 8.47 |
April | 0.190919E+10 | 5793.49 | 26-APR-17:30 | 23.60 | 13.73 | 0.223964E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.277486E+10 | 12394.27 | 14-MAY-17:11 | 22.60 | 11.84 | 0.262732E+09 | 347.85 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.318769E+10 | 6885.09 | 18-JUN-18:33 | 16.30 | 12.47 | 0.269369E+09 | 347.86 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.421567E+10 | 13955.86 | 30-JUL-17:31 | 26.70 | 17.74 | 0.255099E+09 | 347.85 | 28-JUL-13:39 | 26.70 | 17.74 |
August | 0.419596E+10 | 11552.13 | 06-AUG-17:52 | 23.80 | 15.26 | 0.285104E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.289573E+10 | 10099.70 | 10-SEP-17:02 | 21.93 | 14.12 | 0.245746E+09 | 347.85 | 05-SEP-09:09 | 21.93 | 14.12 |
October | 0.182973E+10 | 5861.35 | 04-OCT-16:00 | 21.10 | 11.40 | 0.232062E+09 | 347.84 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.972150E+09 | 2079.63 | 04-NOV-15:40 | 20.37 | 15.93 | 0.203907E+09 | 323.26 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.467301E+09 | 1339.46 | 05-DEC-15:30 | 8.05 | 5.82 | 0.190476E+09 | 311.73 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.247415E+11 | 0.277777E+10 | ||||||||
Minimum of Months | 0.289025E+09 | 1172.37 | 5.87 | 4.23 | 0.183678E+09 | 284.06 | 5.60 | 4.08 | ||
Maximum of Months | 0.421567E+10 | 13955.86 | 26.70 | 17.74 | 0.285104E+09 | 347.88 | 26.70 | 17.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441195E+09 | 1260.92 | 11-JAN-16:20 | 13.67 | 10.10 | 0.308871E+09 | 451.20 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.821854E+09 | 1515.43 | 28-FEB-15:00 | 13.90 | 10.81 | 0.291776E+09 | 517.03 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.169792E+10 | 1576.50 | 10-MAR-14:50 | 16.20 | 11.59 | 0.379982E+09 | 533.41 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.207869E+10 | 4173.43 | 27-APR-15:40 | 27.20 | 17.03 | 0.368933E+09 | 549.50 | 27-APR-13:00 | 27.20 | 17.03 |
May | 0.308161E+10 | 4393.10 | 05-MAY-13:30 | 23.85 | 16.52 | 0.424749E+09 | 549.50 | 05-MAY-09:09 | 23.85 | 16.52 |
June | 0.369959E+10 | 4876.19 | 21-JUN-15:30 | 24.70 | 15.68 | 0.431525E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.417614E+10 | 5787.20 | 24-JUL-15:00 | 30.60 | 18.78 | 0.403006E+09 | 549.50 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.431847E+10 | 5321.88 | 25-AUG-14:00 | 27.40 | 18.74 | 0.451764E+09 | 549.54 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.276831E+10 | 4151.43 | 12-SEP-14:40 | 24.40 | 16.65 | 0.391256E+09 | 549.49 | 07-SEP-13:09 | 24.40 | 16.65 |
October | 0.188546E+10 | 2778.76 | 04-OCT-15:30 | 21.40 | 11.45 | 0.371955E+09 | 549.48 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.110695E+10 | 1468.71 | 02-NOV-14:40 | 13.67 | 11.26 | 0.326909E+09 | 504.20 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.567573E+09 | 1198.17 | 05-DEC-15:00 | 10.00 | 7.01 | 0.300425E+09 | 440.52 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.266438E+11 | 0.445115E+10 | ||||||||
Minimum of Months | 0.441195E+09 | 1198.17 | 10.00 | 7.01 | 0.291776E+09 | 440.52 | 10.00 | 7.01 | ||
Maximum of Months | 0.431847E+10 | 5787.20 | 30.60 | 18.78 | 0.451764E+09 | 549.54 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342950E+09 | 1186.09 | 05-JAN-09:40 | 1.67 | 1.50 | 0.143333E+09 | 270.70 | 05-JAN-09:50 | 2.23 | 2.03 |
February | 0.755033E+09 | 1492.43 | 08-FEB-10:00 | 2.20 | 1.26 | 0.136365E+09 | 316.59 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.170456E+10 | 3211.41 | 14-MAR-09:00 | 7.80 | 5.89 | 0.177463E+09 | 338.72 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.241625E+10 | 6993.12 | 27-APR-09:00 | 17.80 | 12.21 | 0.175150E+09 | 338.73 | 20-APR-10:09 | 17.80 | 12.21 |
May | 0.320140E+10 | 12638.42 | 14-MAY-08:43 | 16.32 | 11.34 | 0.196316E+09 | 338.74 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.398746E+10 | 12156.92 | 25-JUN-07:42 | 15.32 | 11.39 | 0.200556E+09 | 338.73 | 07-JUN-10:09 | 15.32 | 11.39 |
July | 0.424684E+10 | 14832.07 | 30-JUL-08:52 | 20.60 | 15.79 | 0.188048E+09 | 339.01 | 31-JUL-08:00 | 22.20 | 16.89 |
August | 0.455934E+10 | 13407.33 | 13-AUG-08:52 | 20.90 | 15.90 | 0.210296E+09 | 338.94 | 10-AUG-08:00 | 20.90 | 15.90 |
September | 0.306542E+10 | 8510.41 | 10-SEP-09:02 | 16.28 | 13.48 | 0.180468E+09 | 338.73 | 14-SEP-07:10 | 14.18 | 13.39 |
October | 0.194144E+10 | 5444.11 | 04-OCT-09:00 | 15.60 | 10.49 | 0.171602E+09 | 338.73 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.941431E+09 | 1516.91 | 02-NOV-10:40 | 12.43 | 10.47 | 0.149067E+09 | 319.90 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.491553E+09 | 1339.66 | 05-DEC-10:00 | 6.70 | 5.10 | 0.139526E+09 | 291.39 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.276537E+11 | 0.206819E+10 | ||||||||
Minimum of Months | 0.342950E+09 | 1186.09 | 1.67 | 1.26 | 0.136365E+09 | 270.70 | 2.20 | 1.26 | ||
Maximum of Months | 0.455934E+10 | 14832.07 | 20.90 | 15.90 | 0.210296E+09 | 339.01 | 22.20 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109996E+10 | 7396.09 | 20-JAN-13:20 | 6.70 | 4.72 | 0.324604E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.202045E+10 | 9012.49 | 27-FEB-14:10 | 18.58 | 11.55 | 0.316748E+09 | 549.49 | 09-FEB-10:39 | 18.58 | 11.55 |
March | 0.364077E+10 | 10325.66 | 01-MAR-13:30 | 11.15 | 5.98 | 0.400938E+09 | 549.50 | 14-MAR-13:00 | 15.60 | 10.50 |
April | 0.421969E+10 | 11609.07 | 27-APR-13:10 | 26.10 | 16.37 | 0.376761E+09 | 549.95 | 27-APR-13:50 | 26.10 | 16.74 |
May | 0.501802E+10 | 14451.44 | 07-MAY-13:32 | 20.93 | 15.98 | 0.421467E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.528971E+10 | 8930.60 | 28-JUN-13:10 | 24.50 | 15.71 | 0.427640E+09 | 549.52 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.630131E+10 | 19558.06 | 30-JUL-12:12 | 26.10 | 17.39 | 0.400966E+09 | 549.98 | 31-JUL-13:50 | 28.12 | 18.80 |
August | 0.719322E+10 | 19029.85 | 06-AUG-13:13 | 22.00 | 15.46 | 0.450118E+09 | 550.48 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.609505E+10 | 19092.58 | 10-SEP-13:02 | 20.87 | 14.20 | 0.390960E+09 | 550.32 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.432503E+10 | 18999.02 | 08-OCT-13:02 | 18.17 | 13.70 | 0.383194E+09 | 549.83 | 04-OCT-13:00 | 18.17 | 13.70 |
November | 0.199278E+10 | 9123.85 | 04-NOV-13:30 | 20.85 | 16.00 | 0.341928E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.147874E+10 | 7886.74 | 05-DEC-12:30 | 10.30 | 6.13 | 0.322260E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.486747E+11 | 0.455758E+10 | ||||||||
Minimum of Months | 0.109996E+10 | 7396.09 | 6.70 | 4.72 | 0.316748E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.719322E+10 | 19558.06 | 26.10 | 17.39 | 0.450118E+09 | 550.48 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396792E+09 | 1415.56 | 05-JAN-15:50 | 6.20 | 4.71 | 0.195735E+09 | 300.25 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.800456E+09 | 3601.02 | 27-FEB-15:30 | 19.70 | 12.30 | 0.186306E+09 | 347.83 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.174290E+10 | 5080.86 | 14-MAR-16:00 | 17.20 | 10.94 | 0.236047E+09 | 347.84 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.241722E+10 | 7959.95 | 26-APR-16:00 | 24.40 | 14.49 | 0.227292E+09 | 347.85 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.342485E+10 | 15471.15 | 07-MAY-16:51 | 21.70 | 16.17 | 0.262556E+09 | 347.85 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.375899E+10 | 11759.40 | 18-JUN-16:52 | 17.20 | 12.22 | 0.268604E+09 | 347.86 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.473091E+10 | 16063.55 | 23-JUL-16:41 | 26.88 | 15.68 | 0.253091E+09 | 347.85 | 28-JUL-13:39 | 21.10 | 15.48 |
August | 0.459447E+10 | 14089.00 | 06-AUG-16:32 | 23.53 | 15.27 | 0.283311E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.324627E+10 | 12684.94 | 10-SEP-16:22 | 22.20 | 14.33 | 0.241946E+09 | 347.85 | 12-SEP-13:00 | 24.40 | 16.54 |
October | 0.199247E+10 | 6635.15 | 04-OCT-16:00 | 21.10 | 11.40 | 0.228083E+09 | 347.83 | 12-OCT-13:00 | 15.00 | 11.02 |
November | 0.975139E+09 | 2619.95 | 04-NOV-15:30 | 20.55 | 15.94 | 0.202402E+09 | 335.32 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.518282E+09 | 1552.15 | 05-DEC-15:40 | 7.40 | 5.40 | 0.190860E+09 | 320.97 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.285987E+11 | 0.277623E+10 | ||||||||
Minimum of Months | 0.396792E+09 | 1415.56 | 6.20 | 4.71 | 0.186306E+09 | 300.25 | 6.10 | 4.61 | ||
Maximum of Months | 0.473091E+10 | 16063.55 | 26.88 | 16.17 | 0.283311E+09 | 347.88 | 26.10 | 16.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88949258.67 | 6509.58 | 02-JAN-06:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 88949258.67 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 88949258.67 | 6509.58 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358396E+10 | 10944.54 | 09-JAN-06:07 | -1.5 |
February | 0.212911E+10 | 10715.65 | 21-FEB-06:10 | 1.70 |
March | 0.129137E+10 | 6731.36 | 06-MAR-07:04 | 6.70 |
April | 0.668279E+09 | 4946.05 | 19-APR-05:03 | 1.78 |
May | 0.363563E+09 | 4169.73 | 11-MAY-05:03 | 5.10 |
June | 0.195961E+09 | 4127.74 | 25-JUN-06:57 | 13.90 |
July | 0.130174E+09 | 3946.54 | 23-JUL-06:20 | 14.63 |
August | 0.162544E+09 | 3843.44 | 06-AUG-06:53 | 12.00 |
September | 0.351429E+09 | 4900.30 | 10-SEP-07:32 | 13.67 |
October | 0.861743E+09 | 3979.36 | 16-OCT-06:03 | 6.60 |
November | 0.184940E+10 | 9582.80 | 24-NOV-07:06 | 1.20 |
December | 0.305924E+10 | 11296.80 | 26-DEC-06:09 | -0.8 |
Annual Sum or Average | 0.146468E+11 | |||
Minimum of Months | 0.130174E+09 | 3843.44 | -1.5 | |
Maximum of Months | 0.358396E+10 | 11296.80 | 14.63 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188291E+10 | 8843.35 | 02-JAN-08:20 | 6.70 |
February | 0.107905E+10 | 6075.58 | 21-FEB-07:12 | 1.50 |
March | 0.687205E+09 | 2118.06 | 06-MAR-10:50 | 9.13 |
April | 0.286381E+09 | 3749.27 | 02-APR-11:23 | 16.40 |
May | 56869601.67 | 4030.24 | 29-MAY-17:12 | 16.50 |
June | 18277024.36 | 2789.61 | 18-JUN-16:52 | 17.20 |
July | 28013014.34 | 4223.38 | 30-JUL-14:52 | 27.20 |
August | 18581104.71 | 3814.77 | 06-AUG-14:32 | 23.33 |
September | 56359350.44 | 4074.44 | 10-SEP-15:02 | 22.70 |
October | 0.345423E+09 | 4974.33 | 08-OCT-13:02 | 18.17 |
November | 0.878425E+09 | 3028.67 | 11-NOV-11:53 | 5.00 |
December | 0.138685E+10 | 6670.16 | 26-DEC-07:20 | -1.5 |
Annual Sum or Average | 0.672435E+10 | |||
Minimum of Months | 18277024.36 | 2118.06 | -1.5 | |
Maximum of Months | 0.188291E+10 | 8843.35 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149429E+10 | 7515.60 | 02-JAN-08:10 | 6.70 |
February | 0.705710E+09 | 2977.64 | 21-FEB-08:20 | 1.47 |
March | 0.254319E+09 | 2285.12 | 14-MAR-07:08 | 5.10 |
April | 49749890.61 | 2791.90 | 02-APR-12:32 | 18.33 |
May | 19444935.69 | 2795.16 | 29-MAY-16:00 | 16.10 |
June | 21723517.80 | 2111.76 | 18-JUN-15:17 | 18.70 |
July | 27582578.34 | 2682.43 | 30-JUL-15:31 | 27.60 |
August | 18197829.84 | 2134.97 | 06-AUG-14:32 | 23.33 |
September | 22737241.35 | 2870.12 | 10-SEP-16:22 | 22.20 |
October | 0.102086E+09 | 3204.11 | 08-OCT-13:02 | 18.17 |
November | 0.521945E+09 | 2818.86 | 13-NOV-08:09 | 0.78 |
December | 0.994308E+09 | 3260.06 | 26-DEC-09:10 | -0.9 |
Annual Sum or Average | 0.423210E+10 | |||
Minimum of Months | 18197829.84 | 2111.76 | -0.9 | |
Maximum of Months | 0.149429E+10 | 7515.60 | 27.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408196E+09 | 13492.94 | 02-JAN-06:11 | 6.10 |
February | 36757987.51 | 9684.08 | 21-FEB-06:01 | 1.70 |
March | 1533869.93 | 8223.28 | 06-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 6186705.68 | 8689.57 | 27-NOV-07:03 | 11.70 |
December | 65539719.98 | 10338.69 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.518214E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.408196E+09 | 13492.94 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117864E+10 | 20946.38 | 02-JAN-06:11 | 6.10 |
February | 0.410137E+09 | 19005.76 | 21-FEB-05:51 | 1.70 |
March | 74945327.11 | 16582.26 | 06-MAR-06:11 | 6.70 |
April | 5436401.99 | 14428.44 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 15048381.13 | 14891.52 | 23-OCT-06:03 | 10.40 |
November | 0.231714E+09 | 17038.47 | 13-NOV-06:01 | 1.70 |
December | 0.637467E+09 | 19851.79 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.255338E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.117864E+10 | 20946.38 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215275E+10 | 7587.70 | 09-JAN-05:01 | 0.22 |
February | 0.107118E+10 | 7625.24 | 21-FEB-05:51 | 1.70 |
March | 0.301239E+09 | 6868.66 | 06-MAR-06:11 | 6.70 |
April | 72367621.60 | 6146.38 | 18-APR-05:12 | 3.30 |
May | 3040801.58 | 5658.54 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2366428.98 | 5591.90 | 28-SEP-06:03 | 8.40 |
October | 93734992.77 | 6188.22 | 30-OCT-05:12 | 7.20 |
November | 0.701724E+09 | 7047.77 | 24-NOV-06:11 | 1.83 |
December | 0.162992E+10 | 7444.53 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.602832E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.215275E+10 | 7625.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131637E+10 | 6866.02 | 09-JAN-05:01 | 0.22 |
February | 0.611017E+09 | 6921.08 | 21-FEB-05:51 | 1.70 |
March | 0.157365E+09 | 6022.52 | 06-MAR-06:11 | 6.70 |
April | 34149814.28 | 5109.65 | 18-APR-05:12 | 3.30 |
May | 3647312.86 | 4420.01 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2095768.06 | 4405.37 | 28-SEP-06:03 | 8.40 |
October | 63079470.53 | 5138.01 | 16-OCT-05:12 | 7.03 |
November | 0.433930E+09 | 6248.44 | 24-NOV-06:11 | 1.83 |
December | 0.100486E+10 | 6673.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.362651E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.131637E+10 | 6921.08 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163888E+10 | 10084.02 | 17-JAN-05:01 | 1.60 |
February | 0.722254E+09 | 10229.59 | 21-FEB-05:51 | 1.70 |
March | 0.231598E+09 | 9037.79 | 06-MAR-06:11 | 6.70 |
April | 70980853.15 | 7682.46 | 18-APR-05:12 | 3.30 |
May | 6278657.23 | 6717.44 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 3098740.73 | 6686.46 | 27-SEP-06:03 | 8.40 |
October | 77479694.04 | 7649.36 | 16-OCT-05:12 | 7.03 |
November | 0.537965E+09 | 9334.48 | 24-NOV-06:11 | 1.83 |
December | 0.126963E+10 | 10085.38 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.455816E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.163888E+10 | 10229.59 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136412E+10 | 7046.04 | 09-JAN-05:01 | 0.22 |
February | 0.647254E+09 | 7116.52 | 21-FEB-05:51 | 1.70 |
March | 0.198879E+09 | 6195.98 | 06-MAR-06:11 | 6.70 |
April | 53922362.31 | 5210.10 | 18-APR-05:12 | 3.30 |
May | 5260081.01 | 4441.59 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 2661766.60 | 4418.39 | 28-SEP-06:03 | 8.40 |
October | 67649705.41 | 5180.09 | 16-OCT-05:12 | 7.03 |
November | 0.458891E+09 | 6416.99 | 24-NOV-06:11 | 1.83 |
December | 0.104046E+10 | 6892.89 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.383910E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.136412E+10 | 7116.52 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122708E+10 | 5789.34 | 02-JAN-06:11 | 6.10 |
February | 0.425968E+09 | 5210.67 | 21-FEB-06:01 | 1.70 |
March | 62714623.28 | 4722.84 | 06-MAR-06:11 | 6.70 |
April | 9285802.86 | 4417.17 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2659223.34 | 4270.15 | 30-OCT-06:03 | 7.20 |
November | 85645385.67 | 4679.94 | 24-NOV-06:11 | 1.83 |
December | 0.487597E+09 | 5208.68 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.230095E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.122708E+10 | 5789.34 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.756731E+09 | 5262.85 | 02-JAN-06:11 | 6.10 |
February | 0.207948E+09 | 4421.28 | 21-FEB-06:01 | 1.70 |
March | 26254775.35 | 3904.84 | 06-MAR-06:11 | 6.70 |
April | 3577814.12 | 3505.31 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2089806.98 | 3103.87 | 31-OCT-06:03 | 10.18 |
November | 57082741.64 | 3896.21 | 24-NOV-06:11 | 1.83 |
December | 0.329747E+09 | 4538.63 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.138343E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.756731E+09 | 5262.85 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300030E+10 | 8548.25 | 06-JAN-08:00 | -2.8 |
February | 0.165248E+10 | 7929.31 | 14-FEB-07:10 | 0.68 |
March | 0.116235E+10 | 7403.79 | 01-MAR-07:10 | -0.1 |
April | 0.661998E+09 | 7036.87 | 19-APR-06:10 | 2.48 |
May | 0.428631E+09 | 6229.68 | 18-MAY-06:10 | 5.68 |
June | 0.208377E+09 | 5244.39 | 15-JUN-06:20 | 9.80 |
July | 33784648.31 | 4840.98 | 03-JUL-06:06 | 11.88 |
August | 52099796.08 | 4933.01 | 18-AUG-06:10 | 11.63 |
September | 0.191113E+09 | 5633.00 | 28-SEP-06:10 | 8.40 |
October | 0.605948E+09 | 6093.60 | 24-OCT-06:10 | 6.28 |
November | 0.145443E+10 | 7867.46 | 24-NOV-07:10 | 1.20 |
December | 0.223732E+10 | 8621.22 | 26-DEC-07:50 | -1.2 |
Annual Sum or Average | 0.116888E+11 | |||
Minimum of Months | 33784648.31 | 4840.98 | -2.8 | |
Maximum of Months | 0.300030E+10 | 8621.22 | 11.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.762715E+09 | 5437.83 | 02-JAN-06:11 | 6.10 |
February | 0.213645E+09 | 4468.05 | 21-FEB-06:01 | 1.70 |
March | 36344278.15 | 3999.72 | 06-MAR-06:11 | 6.70 |
April | 6593332.92 | 3505.89 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2426078.05 | 2933.91 | 28-OCT-06:03 | 7.80 |
November | 58836402.95 | 3939.79 | 24-NOV-06:11 | 1.83 |
December | 0.317178E+09 | 4644.03 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.139774E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.762715E+09 | 5437.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101557E+10 | 6187.15 | 02-JAN-06:11 | 6.10 |
February | 0.329761E+09 | 5713.14 | 21-FEB-05:51 | 1.70 |
March | 47061720.32 | 5114.61 | 06-MAR-06:11 | 6.70 |
April | 5885950.01 | 4693.37 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 7706308.19 | 4651.84 | 30-OCT-06:03 | 7.20 |
November | 0.160063E+09 | 5245.13 | 24-NOV-06:11 | 1.83 |
December | 0.554304E+09 | 5921.63 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.212035E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.101557E+10 | 6187.15 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659468E+09 | 5759.24 | 02-JAN-06:11 | 6.10 |
February | 0.200245E+09 | 5110.16 | 21-FEB-05:51 | 1.70 |
March | 27804830.89 | 4350.05 | 06-MAR-06:11 | 6.70 |
April | 4340893.10 | 3691.42 | 18-APR-06:02 | 3.40 |
May | 126307.89 | 842.05 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 8409603.36 | 3596.38 | 16-OCT-06:03 | 6.60 |
November | 0.111782E+09 | 4541.15 | 24-NOV-06:11 | 1.83 |
December | 0.394303E+09 | 5430.94 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.140648E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.659468E+09 | 5759.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.743467E+09 | 8440.76 | 02-JAN-06:11 | 6.10 |
February | 0.222755E+09 | 7075.62 | 21-FEB-06:01 | 1.70 |
March | 38214713.96 | 6376.00 | 06-MAR-06:11 | 6.70 |
April | 7271676.30 | 5546.68 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 7578547.89 | 5405.69 | 16-OCT-06:03 | 6.60 |
November | 0.115934E+09 | 6602.75 | 24-NOV-06:11 | 1.83 |
December | 0.445450E+09 | 7798.95 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.158067E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.743467E+09 | 8440.76 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644213E+09 | 5776.37 | 02-JAN-06:11 | 6.10 |
February | 0.203641E+09 | 5060.03 | 21-FEB-05:51 | 1.70 |
March | 35660890.69 | 4349.61 | 06-MAR-06:11 | 6.70 |
April | 6743659.48 | 3668.19 | 18-APR-06:02 | 3.40 |
May | 153639.62 | 1024.26 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 7975810.21 | 3566.20 | 16-OCT-06:03 | 6.60 |
November | 0.112339E+09 | 4519.23 | 24-NOV-06:11 | 1.83 |
December | 0.370316E+09 | 5432.81 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.138104E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.644213E+09 | 5776.37 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.922641E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.742986E+09 | 1358.45 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.800974E+09 | 1184.79 | 07-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.665752E+09 | 947.97 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.697171E+09 | 711.15 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.680233E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638723E+09 | 947.97 | 12-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.725166E+09 | 947.97 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.692141E+09 | 1184.79 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.792086E+09 | 1358.45 | 20-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.887470E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.927199E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.917254E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638723E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.927199E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556721E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.458134E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500609E+09 | 750.07 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420759E+09 | 490.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.444411E+09 | 450.21 | 01-MAY-14:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.434545E+09 | 450.21 | 08-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407200E+09 | 450.21 | 12-JUL-07:49 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.462328E+09 | 490.21 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.432375E+09 | 750.07 | 21-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.487622E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.540082E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.556228E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.570101E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407200E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.556721E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848693E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.698668E+09 | 1358.45 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.781477E+09 | 1184.79 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.664770E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.701333E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.686095E+09 | 711.15 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.647689E+09 | 947.97 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.731330E+09 | 947.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683670E+09 | 1184.79 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.755110E+09 | 1358.45 | 20-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.825102E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.840332E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.886427E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.647689E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.848693E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556192E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.453142E+09 | 859.95 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500676E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.421571E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442567E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431976E+09 | 490.17 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.408495E+09 | 750.02 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461348E+09 | 710.03 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437676E+09 | 750.02 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.489002E+09 | 859.95 | 18-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.538288E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.556241E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.569717E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.408495E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.556241E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.915174E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.738120E+09 | 1358.45 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.796724E+09 | 1184.79 | 07-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.664256E+09 | 947.97 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.696174E+09 | 711.15 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.679488E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638121E+09 | 947.97 | 12-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.723805E+09 | 774.31 | 02-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.689780E+09 | 1184.79 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.787549E+09 | 1358.45 | 20-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.879426E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.917989E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.912661E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638121E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.917989E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554404E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.456080E+09 | 860.01 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.498976E+09 | 750.07 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420180E+09 | 490.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.443724E+09 | 450.21 | 05-MAY-14:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.434070E+09 | 450.21 | 08-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.406752E+09 | 450.21 | 12-JUL-07:49 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461454E+09 | 490.21 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.431569E+09 | 750.07 | 21-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.486136E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.537560E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.553628E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.568453E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.406752E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.554404E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.844351E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.696512E+09 | 1358.45 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.779594E+09 | 1184.79 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.663764E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.700397E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.685074E+09 | 711.15 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.646057E+09 | 947.97 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.730015E+09 | 774.31 | 02-AUG-07:19 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.681877E+09 | 1184.79 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.752661E+09 | 1358.45 | 26-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.822189E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.836981E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.883947E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.646057E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.844351E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553885E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.450859E+09 | 859.95 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.498864E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420815E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.441925E+09 | 490.17 | 02-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431302E+09 | 450.19 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407403E+09 | 710.03 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.460327E+09 | 710.03 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436481E+09 | 750.02 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.486994E+09 | 859.95 | 20-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.535471E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.553114E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.567744E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.407403E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.553885E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.922641E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.742986E+09 | 1358.45 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.800974E+09 | 1184.79 | 07-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.665752E+09 | 947.97 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.697171E+09 | 711.15 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.680233E+09 | 711.15 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.638723E+09 | 947.97 | 12-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.725166E+09 | 947.97 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.692141E+09 | 1184.79 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.792086E+09 | 1358.45 | 20-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.887470E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.927199E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.917254E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.638723E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.927199E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556721E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.458134E+09 | 860.01 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500609E+09 | 750.07 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420759E+09 | 490.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.444411E+09 | 450.21 | 01-MAY-14:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.434545E+09 | 450.21 | 08-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407200E+09 | 450.21 | 12-JUL-07:49 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.462328E+09 | 490.21 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.432375E+09 | 750.07 | 21-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.487622E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.540082E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.556228E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.570101E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407200E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.556721E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848693E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.698668E+09 | 1358.45 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.781477E+09 | 1184.79 | 13-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.664770E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.701333E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.686060E+09 | 711.15 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.647689E+09 | 947.97 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.731330E+09 | 947.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683670E+09 | 1184.79 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.755104E+09 | 1358.45 | 20-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.825064E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.840332E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.886419E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.647689E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.848693E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556192E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.453076E+09 | 859.95 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.500676E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.421571E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.442567E+09 | 490.17 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431976E+09 | 490.17 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.408495E+09 | 750.02 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461348E+09 | 710.03 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437652E+09 | 750.02 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.489002E+09 | 859.95 | 18-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.538288E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.556241E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.569708E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.408495E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.556241E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.922641E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367911E+09 |
February | 0.901968E+09 | 0.742986E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330829E+09 |
March | 0.107774E+10 | 0.800974E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326227E+09 |
April | 0.956342E+09 | 0.665752E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 817363.76 | 0.319840E+09 |
May | 0.103597E+10 | 0.697171E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19006.21 | 0.260677E+09 |
June | 0.103308E+10 | 0.680233E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210034.35 | 0.219688E+09 |
July | 0.959235E+09 | 0.638723E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3263980.01 | 0.185292E+09 |
August | 0.107774E+10 | 0.725166E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4896275.03 | 0.149835E+09 |
September | 0.956342E+09 | 0.692141E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19426.45 | 0.119022E+09 |
October | 0.994195E+09 | 0.792086E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260107E+09 |
November | 0.984487E+09 | 0.887470E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288087E+09 |
December | 0.959235E+09 | 0.927199E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313210E+09 |
Annual Sum or Average | 0.119305E+11 | 0.917254E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9226085.82 | 0.314072E+10 |
Minimum of Months | 0.901968E+09 | 0.638723E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119022E+09 |
Maximum of Months | 0.107774E+10 | 0.927199E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4896275.03 | 0.367911E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.556721E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245063E+09 |
February | 0.571020E+09 | 0.458134E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223420E+09 |
March | 0.682301E+09 | 0.500609E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219170E+09 |
April | 0.605444E+09 | 0.420759E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509945.46 | 0.216486E+09 |
May | 0.655854E+09 | 0.444411E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12672.48 | 0.175154E+09 |
June | 0.654023E+09 | 0.434545E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140027.61 | 0.148396E+09 |
July | 0.607275E+09 | 0.407200E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1705115.58 | 0.124555E+09 |
August | 0.682301E+09 | 0.462328E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3078718.22 | 0.101424E+09 |
September | 0.605444E+09 | 0.432375E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12952.00 | 80011696.97 |
October | 0.629407E+09 | 0.487622E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174966E+09 |
November | 0.623262E+09 | 0.540082E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191696E+09 |
December | 0.607275E+09 | 0.556228E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208803E+09 |
Annual Sum or Average | 0.755301E+10 | 0.570101E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5459431.36 | 0.210914E+10 |
Minimum of Months | 0.571020E+09 | 0.407200E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80011696.97 |
Maximum of Months | 0.682301E+09 | 0.556721E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3078718.22 | 0.245063E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.848693E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377285E+09 |
February | 0.901968E+09 | 0.698668E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353463E+09 |
March | 0.107774E+10 | 0.781477E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340705E+09 |
April | 0.956342E+09 | 0.664770E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 524462.22 | 0.331260E+09 |
May | 0.103597E+10 | 0.701333E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19002.60 | 0.265582E+09 |
June | 0.103308E+10 | 0.686095E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210021.02 | 0.221544E+09 |
July | 0.959235E+09 | 0.647689E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2065271.83 | 0.188159E+09 |
August | 0.107774E+10 | 0.731330E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4488443.99 | 0.153894E+09 |
September | 0.956342E+09 | 0.683670E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19419.55 | 0.124778E+09 |
October | 0.994195E+09 | 0.755110E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276312E+09 |
November | 0.984487E+09 | 0.825102E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296628E+09 |
December | 0.959235E+09 | 0.840332E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323795E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886427E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7326621.22 | 0.325340E+10 |
Minimum of Months | 0.901968E+09 | 0.647689E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124778E+09 |
Maximum of Months | 0.107774E+10 | 0.848693E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4488443.99 | 0.377285E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.556192E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245727E+09 |
February | 0.570983E+09 | 0.453142E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224782E+09 |
March | 0.682256E+09 | 0.500676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220884E+09 |
April | 0.605404E+09 | 0.421571E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229527.95 | 0.217182E+09 |
May | 0.655811E+09 | 0.442567E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12672.77 | 0.179028E+09 |
June | 0.653980E+09 | 0.431976E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140022.35 | 0.148956E+09 |
July | 0.607235E+09 | 0.408495E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1557493.54 | 0.129146E+09 |
August | 0.682256E+09 | 0.461348E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3138035.41 | 0.103870E+09 |
September | 0.605404E+09 | 0.437676E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951.76 | 82462414.99 |
October | 0.629366E+09 | 0.489002E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176249E+09 |
November | 0.623221E+09 | 0.538288E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192380E+09 |
December | 0.607235E+09 | 0.556241E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209478E+09 |
Annual Sum or Average | 0.755252E+10 | 0.569717E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5090703.79 | 0.213014E+10 |
Minimum of Months | 0.570983E+09 | 0.408495E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82462414.99 |
Maximum of Months | 0.682256E+09 | 0.556241E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3138035.41 | 0.245727E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.915174E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208720E+09 |
February | 0.901968E+09 | 0.738120E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188485E+09 |
March | 0.107774E+10 | 0.796724E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181152E+09 |
April | 0.956342E+09 | 0.664256E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499131.53 | 0.173867E+09 |
May | 0.103597E+10 | 0.696174E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11815.91 | 0.140811E+09 |
June | 0.103308E+10 | 0.679488E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118678.55 | 0.118716E+09 |
July | 0.959235E+09 | 0.638121E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2207571.72 | 0.100255E+09 |
August | 0.107774E+10 | 0.723805E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2877157.14 | 81571105.90 |
September | 0.956342E+09 | 0.689780E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771.80 | 66599777.40 |
October | 0.994195E+09 | 0.787549E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151603E+09 |
November | 0.984487E+09 | 0.879426E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169771E+09 |
December | 0.959235E+09 | 0.917989E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182266E+09 |
Annual Sum or Average | 0.119305E+11 | 0.912661E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5726126.65 | 0.176382E+10 |
Minimum of Months | 0.901968E+09 | 0.638121E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66599777.40 |
Maximum of Months | 0.107774E+10 | 0.917989E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2877157.14 | 0.208720E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.554404E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139019E+09 |
February | 0.571020E+09 | 0.456080E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127770E+09 |
March | 0.682301E+09 | 0.498976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123638E+09 |
April | 0.605444E+09 | 0.420180E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262719.44 | 0.121159E+09 |
May | 0.655854E+09 | 0.443724E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.02 | 97213623.21 |
June | 0.654023E+09 | 0.434070E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79119.01 | 83061695.59 |
July | 0.607275E+09 | 0.406752E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 937912.96 | 69266383.00 |
August | 0.682301E+09 | 0.461454E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1663630.17 | 57367434.49 |
September | 0.605444E+09 | 0.431569E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.88 | 45965552.35 |
October | 0.629407E+09 | 0.486136E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103376E+09 |
November | 0.623262E+09 | 0.537560E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113179E+09 |
December | 0.607275E+09 | 0.553628E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121582E+09 |
Annual Sum or Average | 0.755301E+10 | 0.568453E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2959106.49 | 0.120260E+10 |
Minimum of Months | 0.571020E+09 | 0.406752E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45965552.35 |
Maximum of Months | 0.682301E+09 | 0.554404E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1663630.17 | 0.139019E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.844351E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398738E+10 |
February | 0.901968E+09 | 0.696512E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348542E+10 |
March | 0.107774E+10 | 0.779594E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367711E+10 |
April | 0.956342E+09 | 0.663764E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14218576.93 | 0.275586E+10 |
May | 0.103597E+10 | 0.700397E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1604612.63 | 0.242744E+10 |
June | 0.103308E+10 | 0.685074E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15759020.08 | 0.185973E+10 |
July | 0.959235E+09 | 0.646057E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93402775.55 | 0.120108E+10 |
August | 0.107774E+10 | 0.730015E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254795E+09 | 0.114947E+10 |
September | 0.956342E+09 | 0.681877E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3498790.92 | 0.174945E+10 |
October | 0.994195E+09 | 0.752661E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278678E+10 |
November | 0.984487E+09 | 0.822189E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349655E+10 |
December | 0.959235E+09 | 0.836981E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385555E+10 |
Annual Sum or Average | 0.119305E+11 | 0.883947E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383279E+09 | 0.324318E+11 |
Minimum of Months | 0.901968E+09 | 0.646057E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114947E+10 |
Maximum of Months | 0.107774E+10 | 0.844351E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254795E+09 | 0.398738E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.553885E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139384E+09 |
February | 0.570983E+09 | 0.450859E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128042E+09 |
March | 0.682256E+09 | 0.498864E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123965E+09 |
April | 0.605404E+09 | 0.420815E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143190.19 | 0.120519E+09 |
May | 0.655811E+09 | 0.441925E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.30 | 99945814.80 |
June | 0.653980E+09 | 0.431302E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79119.24 | 82949766.20 |
July | 0.607235E+09 | 0.407403E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 840503.48 | 73214135.28 |
August | 0.682256E+09 | 0.460327E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1688384.63 | 59133583.10 |
September | 0.605404E+09 | 0.436481E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.91 | 47725567.42 |
October | 0.629366E+09 | 0.486994E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103735E+09 |
November | 0.623221E+09 | 0.535471E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113255E+09 |
December | 0.607235E+09 | 0.553114E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121880E+09 |
Annual Sum or Average | 0.755252E+10 | 0.567744E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2766922.76 | 0.121375E+10 |
Minimum of Months | 0.570983E+09 | 0.407403E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47725567.42 |
Maximum of Months | 0.682256E+09 | 0.553885E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1688384.63 | 0.139384E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.922641E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324857E+09 |
February | 0.901968E+09 | 0.742986E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295546E+09 |
March | 0.107774E+10 | 0.800974E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291352E+09 |
April | 0.956342E+09 | 0.665752E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 667909.42 | 0.282975E+09 |
May | 0.103597E+10 | 0.697171E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17144.22 | 0.227567E+09 |
June | 0.103308E+10 | 0.680233E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180273.02 | 0.190163E+09 |
July | 0.959235E+09 | 0.638723E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2914086.93 | 0.160289E+09 |
August | 0.107774E+10 | 0.725166E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4230078.62 | 0.130544E+09 |
September | 0.956342E+09 | 0.692141E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17285.12 | 0.105496E+09 |
October | 0.994195E+09 | 0.792086E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235669E+09 |
November | 0.984487E+09 | 0.887470E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260387E+09 |
December | 0.959235E+09 | 0.927199E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281103E+09 |
Annual Sum or Average | 0.119305E+11 | 0.917254E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8026777.33 | 0.278595E+10 |
Minimum of Months | 0.901968E+09 | 0.638723E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105496E+09 |
Maximum of Months | 0.107774E+10 | 0.927199E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4230078.62 | 0.324857E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.556721E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216099E+09 |
February | 0.421807E+09 | 0.458134E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199132E+09 |
March | 0.502994E+09 | 0.500609E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194647E+09 |
April | 0.447140E+09 | 0.420759E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 417695.31 | 0.190286E+09 |
May | 0.484071E+09 | 0.444411E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11427.47 | 0.152006E+09 |
June | 0.482240E+09 | 0.434545E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120180.98 | 0.127853E+09 |
July | 0.448971E+09 | 0.407200E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591210.18 | 0.107266E+09 |
August | 0.502994E+09 | 0.462328E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2646487.96 | 87849782.82 |
September | 0.447140E+09 | 0.432375E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11522.24 | 70357782.49 |
October | 0.465148E+09 | 0.487622E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156957E+09 |
November | 0.460569E+09 | 0.540082E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172376E+09 |
December | 0.448971E+09 | 0.556228E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187058E+09 |
Annual Sum or Average | 0.557719E+10 | 0.570101E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4798524.14 | 0.186189E+10 |
Minimum of Months | 0.421807E+09 | 0.407200E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70357782.49 |
Maximum of Months | 0.502994E+09 | 0.556721E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2646487.96 | 0.216099E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.848693E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333588E+09 |
February | 0.901968E+09 | 0.698668E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314626E+09 |
March | 0.107774E+10 | 0.781477E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302819E+09 |
April | 0.956342E+09 | 0.664770E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 428922.66 | 0.291885E+09 |
May | 0.103597E+10 | 0.701333E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17140.85 | 0.231685E+09 |
June | 0.103308E+10 | 0.686060E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180260.02 | 0.192213E+09 |
July | 0.959235E+09 | 0.647689E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1802752.09 | 0.163009E+09 |
August | 0.107774E+10 | 0.731330E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3780775.38 | 0.134135E+09 |
September | 0.956342E+09 | 0.683670E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17211.65 | 0.110057E+09 |
October | 0.994195E+09 | 0.755104E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247758E+09 |
November | 0.984487E+09 | 0.825064E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267170E+09 |
December | 0.959235E+09 | 0.840332E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290208E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886419E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6227062.65 | 0.287915E+10 |
Minimum of Months | 0.901968E+09 | 0.647689E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110057E+09 |
Maximum of Months | 0.107774E+10 | 0.848693E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3780775.38 | 0.333588E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.556192E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216720E+09 |
February | 0.570983E+09 | 0.453076E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200182E+09 |
March | 0.682256E+09 | 0.500676E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196363E+09 |
April | 0.605404E+09 | 0.421571E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193098.75 | 0.191555E+09 |
May | 0.655811E+09 | 0.442567E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11431.14 | 0.156235E+09 |
June | 0.653980E+09 | 0.431976E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120183.32 | 0.129303E+09 |
July | 0.607235E+09 | 0.408495E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1292979.79 | 0.111801E+09 |
August | 0.682256E+09 | 0.461348E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2641020.79 | 90651441.91 |
September | 0.605404E+09 | 0.437652E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11523.48 | 72876194.13 |
October | 0.629366E+09 | 0.489002E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158536E+09 |
November | 0.623221E+09 | 0.538288E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173100E+09 |
December | 0.607235E+09 | 0.556241E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187688E+09 |
Annual Sum or Average | 0.755252E+10 | 0.569708E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4270237.27 | 0.188501E+10 |
Minimum of Months | 0.570983E+09 | 0.408495E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72876194.13 |
Maximum of Months | 0.682256E+09 | 0.556241E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2641020.79 | 0.216720E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456600E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422127E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412568E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587147.36 | 0.393344E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1265.50 | 0.313411E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82723.67 | 0.260505E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2387365.61 | 0.219891E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3895759.36 | 0.181516E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.80 | 0.148758E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338356E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373886E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402632E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6954604.29 | 0.392359E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148758E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3895759.36 | 0.456600E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552730E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509106E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505119E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 961360.99 | 0.487128E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1810.09 | 0.392773E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107570.39 | 0.327905E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3356613.06 | 0.275886E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5161296.20 | 0.227474E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.54 | 0.183906E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407766E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446138E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482337E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9589075.27 | 0.479827E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183906E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5161296.20 | 0.552730E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551813E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509565E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503708E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485196.05 | 0.498461E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410961E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33220.60 | 0.345681E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1116742.79 | 0.292135E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3581808.49 | 0.233921E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186639E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403956E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436719E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472578E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5216967.93 | 0.484614E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186639E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3581808.49 | 0.551813E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 625.25 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 572.88 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 07-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 551.39 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 | 01-APR-17:03 | 594.59 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 440.38 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 587.59 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.28 | 23-JUL-14:00 | 291.94 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.21 | 13-AUG-14:53 | 420.37 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 272.76 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 20-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 528.80 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 594.90 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 480.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.76 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 | 625.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 414.08 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 381.57 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 371.96 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 01-APR-17:03 | 400.31 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 01-MAY-14:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 291.71 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 08-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 388.67 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 12-JUL-07:49 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.98 | 23-JUL-16:00 | 197.40 | 02-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 08-AUG-17:00 | 280.90 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 178.77 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 351.88 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 394.25 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 318.72 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.77 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 414.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 626.10 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 613.80 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 574.20 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 01-APR-17:20 | 603.64 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 440.38 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 584.22 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.06 | 23-JUL-15:40 | 294.20 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 08-AUG-17:00 | 426.75 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 271.66 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 20-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 528.46 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 594.51 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 482.93 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.66 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 626.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 413.72 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 381.44 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 370.34 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 01-APR-16:00 | 393.35 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 293.15 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 386.37 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 23-JUL-13:13 | 196.94 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 710.03 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 | 13-AUG-12:00 | 288.41 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 178.35 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 351.62 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.43 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 319.25 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.35 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 413.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 356.19 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 326.73 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 07-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 306.29 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.28 | 01-APR-17:03 | 323.87 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 05-MAY-16:00 | 248.67 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 28-JUN-16:00 | 335.69 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 23-JUL-14:10 | 166.95 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 | 13-AUG-15:00 | 232.45 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 14-SEP-17:00 | 158.02 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 20-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 287.11 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 341.07 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 269.02 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.02 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 64.28 | 356.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 235.86 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 216.57 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 213.67 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 01-APR-17:03 | 227.39 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 05-MAY-14:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 164.87 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 08-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 228.53 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 12-JUL-07:49 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 | 23-JUL-16:10 | 111.57 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 161.49 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 104.63 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 190.94 | 31-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 225.94 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 178.68 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.45 | 235.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 19123.84 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17629.33 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17235.46 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.12 | 27-APR-16:10 | 14856.99 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.35 | 05-MAY-16:10 | 12085.43 | 11-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2152.84 | 28-JUN-17:00 | 9391.05 | 15-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.60 | 31-JUL-16:10 | 8306.48 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:19 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.23 | 10-AUG-17:00 | 9385.85 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.39 | 14-SEP-17:00 | 10200.12 | 27-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12269.66 | 13-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16150.03 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18605.40 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8306.48 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.23 | 19123.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 235.75 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 215.79 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 208.72 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 01-APR-17:03 | 215.67 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 166.55 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 222.63 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 710.03 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 | 23-JUL-13:45 | 115.64 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 710.03 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 167.15 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 104.34 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 20-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 191.03 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 225.51 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 178.90 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.34 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 | 235.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 556.41 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 510.46 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 07-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 495.19 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 01-APR-17:03 | 523.72 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 387.32 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 524.90 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.98 | 23-JUL-14:10 | 261.50 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.75 | 13-AUG-15:00 | 366.15 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 245.51 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 20-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 446.27 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.43 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 418.64 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.51 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 556.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 367.63 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 337.62 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 750.07 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 332.57 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 490.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 01-APR-17:03 | 351.40 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 01-MAY-14:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 255.17 | 22-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 08-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 347.15 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 12-JUL-07:49 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 23-JUL-16:10 | 172.69 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 490.21 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 13-AUG-15:00 | 244.54 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 160.55 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 296.45 | 31-OCT-21:05 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 347.29 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 277.68 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.55 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 367.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 556.85 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 550.78 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 13-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 513.34 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.51 | 01-APR-17:03 | 530.90 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 385.78 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 522.51 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 23-JUL-15:27 | 263.29 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | 08-AUG-17:00 | 371.39 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 245.09 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 20-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 445.58 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.04 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 421.44 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 49.51 | 556.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 367.61 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 336.47 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 332.01 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 01-APR-16:00 | 346.75 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 256.85 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 345.82 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 23-JUL-13:45 | 176.20 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 710.03 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 13-AUG-12:20 | 250.79 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 160.95 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 18-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 296.36 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 346.67 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 278.25 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.95 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 367.61 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 791.44 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 734.20 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 706.16 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | 01-APR-17:03 | 732.55 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 05-MAY-16:00 | 548.62 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 28-JUN-15:00 | 737.64 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 | 23-JUL-13:53 | 368.28 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 | 13-AUG-15:10 | 504.38 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 14-SEP-17:00 | 339.57 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 634.07 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.38 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 593.28 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | 791.44 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 971.87 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 892.58 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 873.57 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | 01-APR-17:03 | 922.06 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 05-MAY-16:00 | 681.71 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 28-JUN-15:00 | 925.39 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.43 | 23-JUL-13:53 | 457.53 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.79 | 13-AUG-15:10 | 641.27 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 14-SEP-17:00 | 417.01 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 770.29 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 904.07 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 729.24 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | 971.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 945.33 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 856.64 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 829.06 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.99 | 01-APR-17:03 | 909.85 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 658.84 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 28-JUN-17:00 | 874.91 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 24-JUL-14:00 | 433.15 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 08-AUG-17:00 | 630.78 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 405.17 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 793.69 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 903.47 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 750.94 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.99 | 945.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11809.99 | 13-JAN-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14969.83 | 28-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17025.71 | 02-MAR-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36721.64 | 28-APR-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37258.86 | 08-MAY-06:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39552.48 | 29-JUN-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40612.30 | 17-JUL-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40236.62 | 11-AUG-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38666.19 | 05-SEP-06:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37535.15 | 10-OCT-06:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17269.00 | 06-NOV-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14062.18 | 06-DEC-15:50 | 6035.01 | 6443.98 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11809.99 | 2541.06 | 2863.91 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40612.30 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 246.89 | 11-JAN-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.39 |
February | 2085.25 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.01 |
March | 3045.56 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 |
April | 8553.18 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
May | 8815.11 | 15-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
June | 8826.98 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
July | 9964.81 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 0.00 |
August | 10160.22 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
September | 7899.03 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
October | 5553.08 | 04-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 |
November | 2502.75 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
December | 439.53 | 02-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 246.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10160.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54 | 116.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1844.32 | 14-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 |
February | 2035.28 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 |
March | 2651.61 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.64 |
April | 2941.17 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
May | 3065.21 | 15-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
June | 3463.81 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 0.00 |
July | 4447.06 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 | 0.00 |
August | 4531.76 | 14-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 0.00 |
September | 3547.58 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
October | 2361.92 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.56 |
November | 1809.12 | 09-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.01 |
December | 1647.71 | 02-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1647.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4531.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 | 142.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2308.47 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.89 |
February | 2472.43 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 |
March | 3216.89 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 |
April | 3442.70 | 28-APR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.39 |
May | 3651.13 | 08-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.46 |
June | 3884.09 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
July | 4973.89 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 0.00 |
August | 5070.97 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
September | 4373.81 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
October | 3208.54 | 05-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 |
November | 2660.26 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 |
December | 2151.95 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2151.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5070.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 126.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6959.14 | 12-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7910.31 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9568.31 | 02-MAR-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14910.01 | 27-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15366.77 | 15-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21474.95 | 12-JUN-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22945.59 | 25-JUL-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29269.19 | 14-AUG-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16243.73 | 11-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14427.44 | 04-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8469.41 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7325.39 | 06-DEC-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6959.14 | 2541.06 | 2863.91 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29269.19 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6696.18 | 11-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7737.72 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8572.44 | 02-MAR-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16284.96 | 27-APR-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16945.92 | 15-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17799.86 | 28-JUN-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19115.00 | 24-JUL-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19102.45 | 14-AUG-15:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17069.28 | 14-SEP-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14239.63 | 04-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7579.10 | 02-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7012.47 | 05-DEC-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6696.18 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19115.00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1226.26 | 11-JAN-16:20 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 |
February | 1507.11 | 27-FEB-16:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
March | 1593.79 | 10-MAR-14:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
April | 4520.89 | 27-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
May | 4739.53 | 15-MAY-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
June | 5214.89 | 21-JUN-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 0.00 |
July | 6284.14 | 24-JUL-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 0.00 |
August | 5725.22 | 09-AUG-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 0.00 |
September | 4295.41 | 12-SEP-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
October | 2684.03 | 04-OCT-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
November | 1439.31 | 02-NOV-14:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 |
December | 1145.75 | 29-DEC-16:00 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1145.75 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6284.14 | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 49.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1099.56 | 20-JAN-10:45 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.57 |
February | 1415.66 | 27-FEB-15:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 |
March | 2716.03 | 14-MAR-09:45 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 |
April | 6710.31 | 27-APR-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 |
May | 6926.99 | 15-MAY-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 |
June | 13854.65 | 25-JUN-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.13 |
July | 12667.41 | 30-JUL-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
August | 12890.34 | 13-AUG-09:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 |
September | 10433.76 | 10-SEP-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.15 |
October | 4749.71 | 04-OCT-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
November | 1411.51 | 02-NOV-10:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
December | 1193.60 | 05-DEC-10:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1099.56 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | |
Maximum of Months | 13854.65 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6922.77 | 20-JAN-13:25 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
February | 8862.26 | 27-FEB-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
March | 10004.74 | 14-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
April | 12108.75 | 27-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 0.00 |
May | 18064.91 | 14-MAY-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.11 |
June | 9443.97 | 28-JUN-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 | 0.00 |
July | 18067.63 | 23-JUL-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 0.00 |
August | 18511.76 | 13-AUG-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
September | 22231.54 | 10-SEP-13:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 |
October | 17143.91 | 08-OCT-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.50 |
November | 8976.40 | 04-NOV-13:30 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6983.43 | 05-DEC-12:30 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6922.77 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22231.54 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 134.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1441.25 | 05-JAN-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 |
February | 3502.44 | 27-FEB-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 |
March | 5201.56 | 14-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
April | 8217.78 | 26-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
May | 14878.63 | 14-MAY-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
June | 12018.50 | 18-JUN-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.65 |
July | 15671.72 | 23-JUL-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 |
August | 15054.84 | 06-AUG-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 |
September | 15818.29 | 10-SEP-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 |
October | 6653.72 | 04-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
November | 2497.36 | 04-NOV-15:30 | 84.78 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
December | 1560.15 | 05-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1441.25 | 84.78 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15818.29 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 141.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1191.75 | 11-JAN-16:20 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
February | 1398.39 | 28-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1452.77 | 10-MAR-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 |
April | 2696.07 | 27-APR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
May | 3213.76 | 05-MAY-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
June | 3970.09 | 21-JUN-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
July | 4883.65 | 24-JUL-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 0.00 |
August | 4550.20 | 09-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 0.00 |
September | 3383.15 | 14-SEP-15:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
October | 2104.91 | 04-OCT-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
November | 1471.97 | 06-NOV-12:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
December | 1169.26 | 29-DEC-16:10 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1169.26 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4883.65 | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 26.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.20 | 20-JAN-10:45 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
February | 1147.32 | 27-FEB-15:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 |
March | 1587.83 | 14-MAR-10:00 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
April | 5049.15 | 27-APR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
May | 7828.79 | 15-MAY-06:02 | 847.82 | 683.72 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
June | 9839.85 | 25-JUN-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
July | 11665.81 | 23-JUL-08:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 |
August | 8990.13 | 14-AUG-06:02 | 847.82 | 683.72 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.36 |
September | 5781.35 | 11-SEP-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
October | 4022.48 | 04-OCT-08:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
November | 1248.65 | 02-NOV-10:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
December | 1092.12 | 05-DEC-10:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 949.20 | 211.95 | 113.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | |
Maximum of Months | 11665.81 | 1654.44 | 820.45 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1978.53 | 20-JAN-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1946.63 |
February | 5967.19 | 27-FEB-13:08 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.40 |
March | 6133.38 | 02-MAR-13:20 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1263.08 |
April | 9339.53 | 27-APR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 221.82 | 0.00 |
May | 10645.61 | 14-MAY-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.76 |
June | 7215.18 | 28-JUN-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 0.00 |
July | 16907.99 | 30-JUL-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
August | 13820.39 | 06-AUG-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 |
September | 15578.35 | 10-SEP-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 |
October | 14856.50 | 08-OCT-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.48 |
November | 6661.19 | 04-NOV-13:40 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4160.37 | 05-DEC-12:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1978.53 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16907.99 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 221.82 | 1946.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1172.37 | 20-JAN-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
February | 2199.45 | 27-FEB-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
March | 2973.14 | 02-MAR-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
April | 5793.49 | 26-APR-17:30 | 84.78 | 136.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 12394.27 | 14-MAY-17:11 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 |
June | 6885.09 | 18-JUN-18:33 | 0.00 | 68.36 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 |
July | 13955.86 | 30-JUL-17:31 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 |
August | 11552.13 | 06-AUG-17:52 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.52 |
September | 10099.70 | 10-SEP-17:02 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 |
October | 5861.35 | 04-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
November | 2079.63 | 04-NOV-15:40 | 84.78 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
December | 1339.46 | 05-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1172.37 | 0.00 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | |
Maximum of Months | 13955.86 | 805.38 | 410.20 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1260.92 | 11-JAN-16:20 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
February | 1515.43 | 28-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1576.50 | 10-MAR-14:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 |
April | 4173.43 | 27-APR-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 0.00 |
May | 4393.10 | 05-MAY-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 4876.19 | 21-JUN-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
July | 5787.20 | 24-JUL-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 0.00 |
August | 5321.88 | 25-AUG-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
September | 4151.43 | 12-SEP-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
October | 2778.76 | 04-OCT-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 |
November | 1468.71 | 02-NOV-14:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
December | 1198.17 | 05-DEC-15:00 | 1306.65 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1198.17 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5787.20 | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 43.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1186.09 | 05-JAN-09:40 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 |
February | 1492.43 | 08-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 |
March | 3211.41 | 14-MAR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 |
April | 6993.12 | 27-APR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 |
May | 12638.42 | 14-MAY-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 |
June | 12156.92 | 25-JUN-07:42 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 |
July | 14832.07 | 30-JUL-08:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 |
August | 13407.33 | 13-AUG-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.95 |
September | 8510.41 | 10-SEP-09:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.12 |
October | 5444.11 | 04-OCT-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
November | 1516.91 | 02-NOV-10:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.27 |
December | 1339.66 | 05-DEC-10:00 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1186.09 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | |
Maximum of Months | 14832.07 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7396.09 | 20-JAN-13:20 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
February | 9012.49 | 27-FEB-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
March | 10325.66 | 01-MAR-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
April | 11609.07 | 27-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 0.00 |
May | 14451.44 | 07-MAY-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.71 |
June | 8930.60 | 28-JUN-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
July | 19558.06 | 30-JUL-12:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
August | 19029.85 | 06-AUG-13:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.65 |
September | 19092.58 | 10-SEP-13:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.60 |
October | 18999.02 | 08-OCT-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 |
November | 9123.85 | 04-NOV-13:30 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7886.74 | 05-DEC-12:30 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7396.09 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19558.06 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 100.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1415.56 | 05-JAN-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.92 |
February | 3601.02 | 27-FEB-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 |
March | 5080.86 | 14-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
April | 7959.95 | 26-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
May | 15471.15 | 07-MAY-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.01 |
June | 11759.40 | 18-JUN-16:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 |
July | 16063.55 | 23-JUL-16:41 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.39 |
August | 14089.00 | 06-AUG-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 |
September | 12684.94 | 10-SEP-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 |
October | 6635.15 | 04-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
November | 2619.95 | 04-NOV-15:30 | 84.78 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
December | 1552.15 | 05-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1415.56 | 84.78 | 68.36 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16063.55 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 117.35 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.105259E+12 | 89656.10 | 13-JAN-16:00 | 0.737719E+11 | 176288.92 | 02-JAN-06:19 |
February | 0.937959E+11 | 87194.73 | 27-FEB-15:09 | 0.405490E+11 | 167465.41 | 21-FEB-07:10 |
March | 0.107007E+12 | 84290.88 | 14-MAR-15:00 | 0.148220E+11 | 111612.20 | 06-MAR-07:10 |
April | 0.100528E+12 | 127074.12 | 27-APR-15:09 | 0.499324E+10 | 88072.26 | 18-APR-06:10 |
May | 0.109605E+12 | 120144.66 | 15-MAY-15:30 | 0.146421E+10 | 45140.29 | 18-MAY-06:10 |
June | 0.113604E+12 | 128412.38 | 28-JUN-15:30 | 0.567481E+09 | 16918.70 | 15-JUN-06:10 |
July | 0.121667E+12 | 147725.11 | 31-JUL-15:20 | 0.141737E+09 | 8908.58 | 03-JUL-06:19 |
August | 0.136232E+12 | 153056.31 | 10-AUG-15:20 | 0.158510E+09 | 15843.61 | 03-AUG-06:19 |
September | 0.109829E+12 | 128225.24 | 14-SEP-15:20 | 0.626433E+09 | 33051.28 | 28-SEP-06:10 |
October | 0.104389E+12 | 108690.14 | 04-OCT-15:09 | 0.487242E+10 | 76888.53 | 16-OCT-06:10 |
November | 0.102234E+12 | 89684.52 | 07-NOV-16:00 | 0.289281E+11 | 138717.42 | 24-NOV-07:10 |
December | 0.103479E+12 | 89715.04 | 06-DEC-16:30 | 0.560296E+11 | 185997.07 | 26-DEC-07:19 |
Annual Sum or Average | 0.130763E+13 | 0.226925E+12 | ||||
Minimum of Months | 0.937959E+11 | 84290.88 | 0.141737E+09 | 8908.58 | ||
Maximum of Months | 0.136232E+12 | 153056.31 | 0.737719E+11 | 185997.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.266300E+11 | 0.628818E+10 | 0.605851E+11 | 0.225896E+10 | 0.433443E+10 | 0.331264E+09 | 0.00 | 835790.50 | 0.00 | 0.00 | 0.00 | 0.482995E+10 | 0.00 |
February | 0.233716E+11 | 0.491554E+10 | 0.548702E+11 | 0.204972E+10 | 0.383191E+10 | 0.185756E+09 | 0.00 | 0.159379E+09 | 0.00 | 0.00 | 0.00 | 0.441175E+10 | 0.00 |
March | 0.271841E+11 | 0.442863E+10 | 0.627783E+11 | 0.235662E+10 | 0.478553E+10 | 78354267.96 | 0.00 | 0.248815E+09 | 0.00 | 0.00 | 0.00 | 0.514712E+10 | 0.00 |
April | 0.238354E+11 | 0.340219E+10 | 0.586172E+11 | 0.219329E+10 | 0.542213E+10 | 35625990.84 | 0.00 | 0.249558E+10 | 0.00 | 0.00 | 0.00 | 0.452637E+10 | 0.00 |
May | 0.255713E+11 | 0.290318E+10 | 0.616817E+11 | 0.230719E+10 | 0.723976E+10 | 21193658.31 | 0.00 | 0.520298E+10 | 0.00 | 0.00 | 0.00 | 0.467754E+10 | 0.00 |
June | 0.253399E+11 | 0.254241E+10 | 0.604966E+11 | 0.226931E+10 | 0.879261E+10 | 16044964.93 | 0.00 | 0.966970E+10 | 0.00 | 0.00 | 0.00 | 0.447775E+10 | 0.00 |
July | 0.236971E+11 | 0.273940E+10 | 0.597911E+11 | 0.223007E+10 | 0.109559E+11 | 12975675.43 | 0.00 | 0.181118E+11 | 0.00 | 0.00 | 0.00 | 0.412887E+10 | 0.00 |
August | 0.265782E+11 | 0.320959E+10 | 0.627783E+11 | 0.235614E+10 | 0.125899E+11 | 13633839.51 | 0.00 | 0.241991E+11 | 0.00 | 0.00 | 0.00 | 0.450678E+10 | 0.00 |
September | 0.240521E+11 | 0.386004E+10 | 0.585950E+11 | 0.219219E+10 | 0.819364E+10 | 15819591.30 | 0.00 | 0.879591E+10 | 0.00 | 0.00 | 0.00 | 0.412397E+10 | 0.00 |
October | 0.255550E+11 | 0.500879E+10 | 0.605962E+11 | 0.225951E+10 | 0.537511E+10 | 35674106.70 | 0.00 | 0.117239E+10 | 0.00 | 0.00 | 0.00 | 0.438631E+10 | 0.00 |
November | 0.261517E+11 | 0.580107E+10 | 0.591197E+11 | 0.220160E+10 | 0.408270E+10 | 0.135233E+09 | 0.00 | 0.268617E+09 | 0.00 | 0.00 | 0.00 | 0.447352E+10 | 0.00 |
December | 0.260165E+11 | 0.653724E+10 | 0.597800E+11 | 0.223029E+10 | 0.407096E+10 | 0.251783E+09 | 0.00 | 21297.05 | 0.00 | 0.00 | 0.00 | 0.459198E+10 | 0.00 |
Annual Sum or Average | 0.303983E+12 | 0.516363E+11 | 0.719689E+12 | 0.269049E+11 | 0.796746E+11 | 0.113336E+10 | 0.00 | 0.703252E+11 | 0.00 | 0.00 | 0.00 | 0.542819E+11 | 0.00 |
Minimum of Months | 0.233716E+11 | 0.254241E+10 | 0.548702E+11 | 0.204972E+10 | 0.383191E+10 | 12975675.43 | 0.00 | 21297.05 | 0.00 | 0.00 | 0.00 | 0.412397E+10 | 0.00 |
Maximum of Months | 0.271841E+11 | 0.653724E+10 | 0.627783E+11 | 0.235662E+10 | 0.125899E+11 | 0.331264E+09 | 0.00 | 0.241991E+11 | 0.00 | 0.00 | 0.00 | 0.514712E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.737719E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.405490E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148220E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.499324E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.146421E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.567481E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.141737E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.158510E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.626433E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.487242E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.289281E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.560296E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226925E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.141737E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.737719E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 7962.60 | 02-JAN-07:10 | 556.02 | 02-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 32642.50 | 02-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 02-FEB-08:09 | 6354.14 | 21-FEB-07:10 | 551.01 | 21-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 30940.97 | 22-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 5660.25 | 02-MAR-15:30 | 471.37 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 28290.68 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 04-APR-11:09 | 18184.16 | 27-APR-14:30 | 365.85 | 18-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 26379.99 | 17-MAY-07:10 | 3328.83 | 01-MAY-19:19 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:09 | 18850.36 | 15-MAY-14:50 | 214.16 | 18-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 26260.02 | 16-JUN-07:10 | 3328.83 | 01-JUN-19:00 | 41699.26 | 01-JUN-07:10 | 1410.29 | 05-JUN-16:10 | 19299.69 | 28-JUN-15:20 | 98.45 | 14-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 28580.47 | 12-JUL-07:49 | 3328.83 | 01-JUL-20:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 12-JUL-11:09 | 25815.42 | 31-JUL-14:50 | 55.76 | 03-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 27943.37 | 02-AUG-07:30 | 5686.19 | 16-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-11:09 | 27002.48 | 10-AUG-15:20 | 91.52 | 18-AUG-06:19 | 0.00 | 01-AUG-00:10 |
September | 30940.97 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-11:09 | 22141.97 | 11-SEP-15:30 | 178.31 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 26-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 10-OCT-11:09 | 15595.02 | 04-OCT-15:20 | 326.47 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 02-NOV-16:10 | 4812.29 | 24-NOV-07:10 | 516.61 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 6983.29 | 26-DEC-07:10 | 568.43 | 26-DEC-07:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26260.02 | 3328.83 | 41699.26 | 1410.29 | 4812.29 | 55.76 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 27002.48 | 568.43 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 456.46 | 03-JAN-07:30 | 0.00 | 0.00 | 0.00 | 6463.99 | 27-JAN-12:30 | 0.00 |
February | 9577.45 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6514.45 | 09-FEB-12:20 | 0.00 |
March | 8521.98 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6420.25 | 03-MAR-12:20 | 0.00 |
April | 36271.22 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 6250.80 | 03-APR-11:39 | 0.00 |
May | 29379.32 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6199.99 | 01-MAY-11:20 | 0.00 |
June | 35870.81 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 | 5815.84 | 01-JUN-11:20 | 0.00 |
July | 50708.33 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 5767.43 | 03-JUL-11:30 | 0.00 |
August | 53443.20 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 | 5699.25 | 29-AUG-11:20 | 0.00 |
September | 34079.06 | 14-SEP-15:30 | 0.00 | 0.00 | 0.00 | 5776.64 | 29-SEP-11:30 | 0.00 |
October | 20617.14 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 5828.89 | 31-OCT-11:20 | 0.00 |
November | 13450.73 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 | 6210.38 | 29-NOV-12:00 | 0.00 |
December | 19.43 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 6261.88 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19.43 | 0.00 | 0.00 | 0.00 | 5699.25 | 0.00 | ||
Maximum of Months | 53443.20 | 0.00 | 0.00 | 0.00 | 6514.45 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 89656.10 | 13-JAN-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3075.57 | 188.88 | 0.00 | 0.00 | 0.00 |
February | 87194.73 | 27-FEB-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 5046.99 | 6.85 | 0.00 | 9577.45 | 0.00 |
March | 84290.88 | 14-MAR-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 5493.47 | 6.85 | 0.00 | 5047.89 | 0.00 |
April | 127074.12 | 27-APR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 17590.82 | 6.85 | 0.00 | 36104.28 | 0.00 |
May | 120144.66 | 15-MAY-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 18594.86 | 6.85 | 0.00 | 28168.94 | 0.00 |
June | 128412.38 | 28-JUN-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 19280.60 | 6.85 | 0.00 | 35870.81 | 0.00 |
July | 147725.11 | 31-JUL-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 25722.61 | 6.89 | 0.00 | 48984.22 | 0.00 |
August | 153056.31 | 10-AUG-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 27002.48 | 6.91 | 0.00 | 53036.74 | 0.00 |
September | 128225.24 | 14-SEP-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 21210.51 | 6.90 | 0.00 | 33988.99 | 0.00 |
October | 108690.14 | 04-OCT-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 15357.52 | 6.85 | 0.00 | 20311.82 | 0.00 |
November | 89684.52 | 07-NOV-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3659.00 | 6.85 | 0.00 | 0.00 | 0.00 |
December | 89715.04 | 06-DEC-16:30 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3291.52 | 107.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 84290.88 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 3075.57 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 153056.31 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 27002.48 | 188.88 | 0.00 | 53036.74 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 176288.92 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 167465.41 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 111612.20 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 88072.26 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 45140.29 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 16918.70 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8908.58 | 03-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 15843.61 | 03-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 33051.28 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 76888.53 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 138717.42 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 185997.07 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 8908.58 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 185997.07 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.46 | 2.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 19.46 | 2.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.46 | 2.17 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.16 | 3.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 19.16 | 3.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.16 | 3.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 19.25 | 3.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.50 | 19.48 | 0.50 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 19.28 | 1.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Annual Sum or Average | 5.50 | 19.28 | 5.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.48 | 3.67 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 18.87 | 8.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 3.50 | 18.48 | 2.83 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
March | 0.17 | 19.15 | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.18 | 0.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 5.50 | 19.13 | 5.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Annual Sum or Average | 19.17 | 18.88 | 17.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.33 | 19.18 | 8.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.57 | 3.33 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
February | 0.83 | 19.31 | 0.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.82 | 1.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.97 | 2.67 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.83 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.03 | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 2.33 | 19.02 | 2.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 7.50 | 18.82 | 6.50 | 19.00 | 8.17 | 22.28 | 8.17 | 23.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.35 | 3.33 | 19.35 | 2.67 | 28.06 | 2.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.20 | 3.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.67 | 19.24 | 0.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.17 | 19.37 | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.92 | 2.50 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.04 | 2.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.20 | 1.67 | 28.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.79 | 0.33 | 27.79 |
November | 0.17 | 19.08 | 0.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 1.83 | 18.95 | 1.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 6.17 | 19.13 | 5.50 | 19.28 | 10.00 | 23.25 | 10.00 | 24.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 0.00 | 19.08 |
Maximum of Months | 3.33 | 19.37 | 3.00 | 19.37 | 2.67 | 28.20 | 2.67 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.67 | 3.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.83 | 19.40 | 0.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.07 | 2.67 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.96 | 1.00 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.36 | 2.50 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.23 | 1.67 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.95 | 1.17 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.07 | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 2.00 | 18.99 | 1.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 7.00 | 18.87 | 6.17 | 19.04 | 16.00 | 24.05 | 9.00 | 25.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.40 | 3.33 | 19.40 | 4.83 | 28.36 | 2.67 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 19.29 | 4.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.17 | 19.13 | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.76 | 0.33 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Annual Sum or Average | 4.67 | 19.32 | 4.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.76 | 4.17 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 19.15 | 2.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.69 | 2.33 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.72 | 2.17 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 3.17 | 19.15 | 3.00 | 19.27 | 6.00 | 23.40 | 6.00 | 24.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.32 | 2.83 | 19.32 | 2.33 | 27.72 | 2.33 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.50 | 18.41 | 71.50 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
February | 43.00 | 18.63 | 43.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
March | 35.33 | 19.15 | 35.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 17.83 | 19.22 | 17.83 | 19.22 | 0.17 | 19.26 | 0.17 | 19.29 |
May | 8.50 | 19.90 | 8.50 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
June | 0.17 | 20.43 | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.52 | 1.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.65 | 2.17 | 27.65 |
September | 2.00 | 19.90 | 2.00 | 19.90 | 1.67 | 22.25 | 1.67 | 23.54 |
October | 14.50 | 19.91 | 14.50 | 19.91 | 0.67 | 20.08 | 0.67 | 20.24 |
November | 43.83 | 19.14 | 43.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
December | 60.33 | 18.59 | 60.33 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
Annual Sum or Average | 297.00 | 18.85 | 297.00 | 18.85 | 6.17 | 18.94 | 6.17 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 0.00 | 18.41 |
Maximum of Months | 71.50 | 20.43 | 71.50 | 20.43 | 2.17 | 27.65 | 2.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.71 | 2.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.75 | 1.00 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 0.33 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.06 | 1.33 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.85 | 1.33 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.96 | 0.50 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Annual Sum or Average | 3.33 | 18.74 | 2.83 | 19.04 | 10.83 | 24.67 | 4.50 | 25.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.33 | 2.67 | 19.33 | 3.83 | 28.06 | 1.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 19.19 | 3.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.17 | 19.18 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.78 | 1.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Annual Sum or Average | 4.83 | 19.31 | 4.67 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.78 | 3.50 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.34 | 2.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.65 | 1.33 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.83 | 1.17 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.11 | 2.83 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.67 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.77 | 1.17 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 2.50 | 19.41 | 2.33 | 19.49 | 9.17 | 25.03 | 9.17 | 26.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.90 | 2.00 | 19.90 | 2.83 | 28.11 | 2.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.46 | 2.00 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.58 | 1.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 2.67 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.90 | 2.83 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.17 | 1.67 | 28.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.74 | 0.67 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.36 | 0.17 | 19.36 | 0.17 | 22.00 | 0.17 | 23.32 |
Annual Sum or Average | 2.17 | 19.45 | 2.17 | 19.45 | 11.17 | 25.45 | 11.17 | 26.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.46 | 2.00 | 19.46 | 2.83 | 28.17 | 2.83 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.33 | 2.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.08 | 2.33 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.88 | 1.00 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.25 | 2.17 | 28.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.11 | 1.67 | 28.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.86 | 1.50 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 2.50 | 19.40 | 2.33 | 19.48 | 16.00 | 26.09 | 8.83 | 26.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.90 | 2.00 | 19.90 | 4.83 | 28.25 | 2.33 | 28.27 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 22.99 | 32.00 | 22.79 | 32.00 | 22.62 |
February | 409.50 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
March | 290.83 | 23.93 | 7.33 | 23.96 | 0.00 | 23.96 |
April | 88.33 | 23.96 | 94.83 | 24.61 | 0.00 | 24.61 |
May | 1.17 | 24.00 | 210.00 | 24.87 | 0.00 | 24.87 |
June | 0.00 | 0.00 | 272.50 | 24.74 | 0.00 | 24.74 |
July | 0.00 | 0.00 | 409.33 | 24.64 | 0.00 | 24.64 |
August | 0.00 | 0.00 | 469.83 | 24.47 | 0.00 | 24.47 |
September | 0.00 | 0.00 | 349.00 | 24.66 | 0.00 | 24.66 |
October | 43.67 | 23.86 | 102.33 | 25.01 | 0.00 | 25.01 |
November | 282.00 | 23.78 | 31.00 | 23.91 | 0.00 | 23.91 |
December | 488.67 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
Annual Sum or Average | 2105.67 | 23.55 | 1978.17 | 24.08 | 32.00 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 | 22.62 |
Maximum of Months | 501.50 | 24.00 | 469.83 | 25.01 | 32.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.37 | 109.50 | 21.15 | 109.50 | 20.99 |
February | 452.00 | 22.04 | 34.33 | 21.93 | 34.33 | 21.84 |
March | 511.00 | 22.96 | 0.17 | 22.96 | 0.17 | 22.96 |
April | 357.50 | 23.33 | 29.17 | 23.44 | 0.00 | 23.44 |
May | 186.17 | 23.55 | 60.83 | 23.78 | 0.00 | 23.78 |
June | 72.17 | 23.59 | 129.33 | 24.18 | 0.00 | 24.18 |
July | 8.50 | 23.55 | 279.50 | 24.39 | 0.00 | 24.39 |
August | 22.50 | 23.52 | 359.33 | 24.26 | 0.00 | 24.26 |
September | 74.33 | 23.33 | 168.17 | 24.11 | 0.00 | 24.11 |
October | 345.33 | 23.09 | 8.50 | 23.14 | 0.00 | 23.14 |
November | 471.17 | 22.41 | 1.00 | 22.40 | 1.00 | 22.40 |
December | 497.00 | 21.79 | 23.83 | 21.73 | 23.83 | 21.67 |
Annual Sum or Average | 3499.67 | 22.48 | 1203.67 | 22.83 | 168.83 | 22.74 |
Minimum of Months | 8.50 | 21.37 | 0.17 | 21.15 | 0.00 | 20.99 |
Maximum of Months | 511.00 | 23.59 | 359.33 | 24.39 | 109.50 | 24.39 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.73 | 225.83 | 20.47 | 225.83 | 20.33 |
February | 454.00 | 21.27 | 128.33 | 21.03 | 128.33 | 20.87 |
March | 514.00 | 22.17 | 29.67 | 22.08 | 29.67 | 22.00 |
April | 404.00 | 22.78 | 17.33 | 22.85 | 0.17 | 22.85 |
May | 270.17 | 23.19 | 44.00 | 23.34 | 0.00 | 23.34 |
June | 149.17 | 23.40 | 89.83 | 23.74 | 0.00 | 23.74 |
July | 78.00 | 23.47 | 238.00 | 24.09 | 0.00 | 24.09 |
August | 74.33 | 23.36 | 289.83 | 24.05 | 0.00 | 24.05 |
September | 217.50 | 23.15 | 103.00 | 23.50 | 0.00 | 23.50 |
October | 449.33 | 22.51 | 3.50 | 22.50 | 3.50 | 22.48 |
November | 489.00 | 21.58 | 75.50 | 21.41 | 75.50 | 21.27 |
December | 497.00 | 21.00 | 171.50 | 20.78 | 171.50 | 20.65 |
Annual Sum or Average | 4098.50 | 21.99 | 1416.33 | 22.09 | 634.50 | 21.89 |
Minimum of Months | 74.33 | 20.73 | 3.50 | 20.47 | 0.00 | 20.33 |
Maximum of Months | 514.00 | 23.47 | 289.83 | 24.09 | 225.83 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 388.67 | 19.96 | 388.67 | 19.91 |
February | 454.00 | 20.48 | 258.50 | 20.27 | 258.50 | 20.17 |
March | 514.00 | 21.24 | 139.50 | 21.03 | 139.50 | 20.89 |
April | 432.67 | 22.10 | 57.67 | 22.00 | 44.33 | 21.86 |
May | 313.83 | 22.64 | 52.00 | 22.85 | 1.17 | 22.84 |
June | 185.50 | 23.08 | 91.67 | 23.47 | 0.00 | 23.47 |
July | 121.17 | 23.23 | 240.33 | 23.89 | 0.00 | 23.89 |
August | 139.50 | 23.13 | 271.50 | 23.82 | 0.00 | 23.82 |
September | 296.83 | 22.61 | 75.33 | 22.92 | 0.83 | 22.91 |
October | 484.50 | 21.69 | 52.33 | 21.53 | 52.33 | 21.40 |
November | 489.00 | 20.71 | 219.50 | 20.49 | 219.50 | 20.37 |
December | 497.00 | 20.26 | 367.17 | 20.14 | 367.17 | 20.10 |
Annual Sum or Average | 4430.00 | 21.38 | 2214.17 | 21.38 | 1472.00 | 21.12 |
Minimum of Months | 121.17 | 20.08 | 52.00 | 19.96 | 0.00 | 19.91 |
Maximum of Months | 514.00 | 23.23 | 388.67 | 23.89 | 388.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.11 | 377.50 | 19.98 | 377.50 | 19.93 |
February | 454.00 | 20.62 | 239.67 | 20.42 | 239.67 | 20.32 |
March | 508.67 | 21.40 | 110.00 | 21.16 | 110.00 | 21.00 |
April | 339.67 | 22.00 | 85.00 | 22.11 | 34.67 | 21.97 |
May | 266.33 | 22.45 | 127.83 | 23.06 | 4.83 | 23.07 |
June | 158.00 | 22.96 | 212.17 | 23.77 | 3.50 | 23.80 |
July | 120.17 | 23.37 | 308.50 | 24.09 | 10.17 | 24.15 |
August | 124.67 | 23.37 | 329.67 | 24.03 | 13.17 | 24.11 |
September | 262.67 | 22.40 | 152.17 | 23.09 | 4.83 | 23.10 |
October | 440.33 | 21.62 | 58.00 | 21.53 | 46.50 | 21.40 |
November | 489.00 | 20.72 | 202.67 | 20.51 | 202.67 | 20.39 |
December | 497.00 | 20.29 | 347.33 | 20.16 | 347.33 | 20.10 |
Annual Sum or Average | 4162.50 | 21.32 | 2550.50 | 21.58 | 1394.83 | 21.33 |
Minimum of Months | 120.17 | 20.11 | 58.00 | 19.98 | 3.50 | 19.93 |
Maximum of Months | 508.67 | 23.37 | 377.50 | 24.09 | 377.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 20.42 | 314.50 | 20.19 | 313.67 | 20.08 |
February | 410.00 | 20.92 | 201.50 | 20.77 | 186.67 | 20.62 |
March | 422.33 | 21.34 | 131.00 | 21.27 | 102.33 | 21.10 |
April | 327.33 | 21.93 | 118.83 | 22.24 | 39.17 | 22.09 |
May | 282.00 | 22.43 | 134.17 | 23.04 | 8.83 | 23.08 |
June | 206.50 | 22.80 | 168.83 | 23.51 | 3.00 | 23.53 |
July | 154.67 | 23.19 | 279.33 | 23.96 | 10.17 | 24.03 |
August | 159.17 | 23.19 | 309.33 | 23.93 | 12.00 | 24.01 |
September | 248.17 | 22.54 | 193.33 | 23.32 | 7.67 | 23.36 |
October | 371.50 | 21.68 | 125.33 | 22.07 | 40.00 | 21.94 |
November | 456.33 | 20.92 | 190.67 | 20.82 | 168.67 | 20.66 |
December | 471.83 | 20.56 | 290.33 | 20.36 | 287.17 | 20.25 |
Annual Sum or Average | 4006.50 | 21.50 | 2457.17 | 21.82 | 1179.33 | 21.57 |
Minimum of Months | 154.67 | 20.42 | 118.83 | 20.19 | 3.00 | 20.08 |
Maximum of Months | 496.67 | 23.19 | 314.50 | 23.96 | 313.67 | 24.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 383.00 | 20.00 | 383.00 | 19.95 |
February | 450.00 | 20.62 | 246.67 | 20.41 | 246.00 | 20.30 |
March | 488.33 | 21.18 | 142.67 | 21.02 | 134.50 | 20.88 |
April | 379.00 | 21.74 | 97.17 | 21.90 | 45.33 | 21.77 |
May | 314.33 | 22.44 | 119.50 | 22.96 | 15.17 | 23.04 |
June | 225.33 | 22.77 | 167.33 | 23.44 | 4.33 | 23.48 |
July | 157.83 | 23.18 | 284.17 | 23.97 | 12.83 | 24.05 |
August | 173.17 | 22.99 | 280.17 | 23.81 | 9.50 | 23.88 |
September | 296.33 | 22.42 | 143.17 | 23.05 | 7.67 | 23.09 |
October | 451.50 | 21.48 | 73.50 | 21.48 | 49.83 | 21.35 |
November | 484.83 | 20.71 | 212.50 | 20.51 | 210.50 | 20.40 |
December | 497.00 | 20.33 | 354.17 | 20.19 | 354.17 | 20.13 |
Annual Sum or Average | 4419.67 | 21.33 | 2504.00 | 21.53 | 1472.83 | 21.30 |
Minimum of Months | 157.83 | 20.12 | 73.50 | 20.00 | 4.33 | 19.95 |
Maximum of Months | 502.00 | 23.18 | 383.00 | 23.97 | 383.00 | 24.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 358.00 | 20.30 | 358.00 | 20.26 |
February | 454.00 | 20.76 | 222.17 | 20.61 | 222.17 | 20.54 |
March | 514.00 | 21.36 | 75.67 | 21.25 | 75.67 | 21.16 |
April | 463.33 | 22.19 | 9.17 | 22.17 | 6.50 | 22.15 |
May | 383.50 | 23.01 | 21.17 | 23.07 | 0.00 | 23.07 |
June | 215.50 | 23.38 | 51.67 | 23.55 | 0.00 | 23.55 |
July | 86.00 | 23.49 | 209.50 | 24.02 | 0.00 | 24.02 |
August | 104.33 | 23.41 | 262.33 | 23.96 | 0.00 | 23.96 |
September | 288.17 | 23.12 | 68.50 | 23.33 | 0.00 | 23.33 |
October | 484.67 | 22.34 | 0.50 | 22.34 | 0.50 | 22.33 |
November | 489.00 | 21.33 | 87.83 | 21.19 | 87.83 | 21.08 |
December | 497.00 | 20.69 | 275.50 | 20.58 | 275.50 | 20.53 |
Annual Sum or Average | 4481.50 | 21.75 | 1642.00 | 21.75 | 1026.17 | 21.54 |
Minimum of Months | 86.00 | 20.41 | 0.50 | 20.30 | 0.00 | 20.26 |
Maximum of Months | 514.00 | 23.49 | 358.00 | 24.02 | 358.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 344.67 | 20.32 | 344.67 | 20.27 |
February | 454.00 | 20.96 | 192.50 | 20.81 | 192.50 | 20.72 |
March | 513.33 | 21.72 | 44.67 | 21.61 | 44.67 | 21.51 |
April | 360.50 | 22.50 | 40.50 | 22.63 | 4.67 | 22.60 |
May | 258.00 | 22.88 | 100.33 | 23.34 | 0.00 | 23.34 |
June | 107.00 | 23.26 | 210.83 | 24.06 | 0.67 | 24.07 |
July | 68.67 | 23.84 | 330.33 | 24.33 | 8.33 | 24.38 |
August | 62.83 | 23.84 | 370.50 | 24.26 | 9.33 | 24.32 |
September | 204.00 | 23.04 | 183.17 | 23.68 | 2.67 | 23.70 |
October | 410.50 | 22.35 | 20.00 | 22.46 | 0.00 | 22.46 |
November | 489.00 | 21.35 | 75.67 | 21.22 | 75.67 | 21.11 |
December | 497.00 | 20.73 | 242.33 | 20.60 | 242.33 | 20.54 |
Annual Sum or Average | 3926.83 | 21.69 | 2155.50 | 22.04 | 925.50 | 21.83 |
Minimum of Months | 62.83 | 20.43 | 20.00 | 20.32 | 0.00 | 20.27 |
Maximum of Months | 513.33 | 23.84 | 370.50 | 24.33 | 344.67 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.50 | 20.31 | 316.33 | 20.09 | 316.33 | 20.00 |
February | 435.33 | 20.99 | 143.17 | 20.75 | 139.17 | 20.57 |
March | 467.17 | 21.40 | 62.17 | 21.25 | 56.33 | 21.10 |
April | 379.00 | 21.95 | 72.33 | 22.15 | 20.17 | 22.03 |
May | 338.33 | 22.37 | 81.00 | 22.79 | 2.50 | 22.76 |
June | 242.33 | 22.67 | 114.83 | 23.29 | 0.00 | 23.29 |
July | 119.50 | 22.93 | 284.50 | 24.00 | 4.00 | 24.03 |
August | 113.67 | 23.00 | 325.17 | 24.01 | 7.33 | 24.06 |
September | 200.33 | 22.68 | 222.00 | 23.64 | 6.33 | 23.69 |
October | 353.67 | 22.09 | 90.00 | 22.62 | 4.17 | 22.61 |
November | 459.50 | 21.10 | 100.00 | 21.05 | 80.83 | 20.88 |
December | 481.17 | 20.65 | 244.83 | 20.44 | 241.33 | 20.32 |
Annual Sum or Average | 4089.50 | 21.52 | 2056.33 | 21.87 | 878.50 | 21.63 |
Minimum of Months | 113.67 | 20.31 | 62.17 | 20.09 | 0.00 | 20.00 |
Maximum of Months | 499.50 | 23.00 | 325.17 | 24.01 | 316.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.44 | 345.50 | 20.33 | 345.50 | 20.28 |
February | 452.67 | 20.93 | 191.17 | 20.76 | 191.17 | 20.66 |
March | 499.83 | 21.49 | 62.00 | 21.38 | 61.83 | 21.28 |
April | 393.67 | 22.18 | 45.67 | 22.38 | 5.50 | 22.35 |
May | 290.17 | 22.93 | 108.00 | 23.37 | 2.33 | 23.39 |
June | 173.33 | 23.18 | 164.00 | 23.77 | 0.33 | 23.77 |
July | 57.00 | 23.85 | 349.50 | 24.38 | 7.50 | 24.43 |
August | 71.33 | 23.51 | 355.50 | 24.19 | 6.50 | 24.23 |
September | 195.67 | 23.02 | 194.50 | 23.73 | 2.17 | 23.74 |
October | 431.67 | 22.22 | 23.17 | 22.35 | 0.00 | 22.35 |
November | 483.83 | 21.26 | 85.00 | 21.15 | 82.67 | 21.05 |
December | 497.00 | 20.74 | 255.50 | 20.61 | 255.50 | 20.55 |
Annual Sum or Average | 4048.17 | 21.64 | 2179.50 | 21.99 | 961.00 | 21.78 |
Minimum of Months | 57.00 | 20.44 | 23.17 | 20.33 | 0.00 | 20.28 |
Maximum of Months | 502.00 | 23.85 | 355.50 | 24.38 | 345.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 316.50 | 20.23 | 316.50 | 20.16 |
February | 454.00 | 20.87 | 187.33 | 20.65 | 187.33 | 20.53 |
March | 514.00 | 21.77 | 54.17 | 21.64 | 54.17 | 21.53 |
April | 420.33 | 22.59 | 22.00 | 22.64 | 4.00 | 22.62 |
May | 273.17 | 23.10 | 57.00 | 23.29 | 0.00 | 23.29 |
June | 127.17 | 23.41 | 104.17 | 23.79 | 0.00 | 23.79 |
July | 55.00 | 23.50 | 268.17 | 24.13 | 0.00 | 24.13 |
August | 70.00 | 23.38 | 309.50 | 24.05 | 0.00 | 24.05 |
September | 234.50 | 23.08 | 99.67 | 23.42 | 0.00 | 23.42 |
October | 466.17 | 22.29 | 9.17 | 22.27 | 7.17 | 22.24 |
November | 489.00 | 21.23 | 120.67 | 21.04 | 120.67 | 20.91 |
December | 497.00 | 20.63 | 265.33 | 20.49 | 265.33 | 20.42 |
Annual Sum or Average | 4102.33 | 21.71 | 1813.67 | 21.82 | 955.17 | 21.59 |
Minimum of Months | 55.00 | 20.39 | 9.17 | 20.23 | 0.00 | 20.16 |
Maximum of Months | 514.00 | 23.50 | 316.50 | 24.13 | 316.50 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.28 | 285.50 | 20.13 | 285.50 | 20.07 |
February | 385.00 | 20.90 | 162.50 | 20.71 | 162.50 | 20.60 |
March | 422.17 | 21.64 | 44.50 | 21.50 | 44.50 | 21.39 |
April | 292.50 | 22.34 | 49.33 | 22.58 | 5.67 | 22.54 |
May | 234.67 | 22.85 | 99.50 | 23.35 | 3.83 | 23.39 |
June | 125.00 | 23.24 | 165.67 | 23.95 | 4.83 | 24.00 |
July | 85.33 | 23.71 | 256.83 | 24.30 | 9.83 | 24.38 |
August | 85.50 | 23.60 | 284.83 | 24.20 | 10.00 | 24.28 |
September | 213.83 | 22.84 | 129.67 | 23.45 | 4.00 | 23.49 |
October | 367.67 | 21.99 | 29.17 | 22.09 | 8.33 | 22.05 |
November | 417.00 | 21.08 | 110.17 | 20.89 | 110.17 | 20.77 |
December | 422.00 | 20.56 | 235.50 | 20.41 | 235.50 | 20.34 |
Annual Sum or Average | 3477.67 | 21.60 | 1853.17 | 21.90 | 884.67 | 21.68 |
Minimum of Months | 85.33 | 20.28 | 29.17 | 20.13 | 3.83 | 20.07 |
Maximum of Months | 427.00 | 23.71 | 285.50 | 24.30 | 285.50 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 20.75 | 243.33 | 20.53 | 239.67 | 20.40 |
February | 394.33 | 21.26 | 135.83 | 21.19 | 114.83 | 21.03 |
March | 405.33 | 21.81 | 73.17 | 21.86 | 40.17 | 21.74 |
April | 298.33 | 22.38 | 93.50 | 22.84 | 5.00 | 22.82 |
May | 249.67 | 22.92 | 142.17 | 23.47 | 5.17 | 23.51 |
June | 160.83 | 23.15 | 189.67 | 23.81 | 2.00 | 23.83 |
July | 99.17 | 23.57 | 306.00 | 24.21 | 9.17 | 24.27 |
August | 101.00 | 23.60 | 341.17 | 24.16 | 11.83 | 24.23 |
September | 190.00 | 23.03 | 220.33 | 23.76 | 6.50 | 23.81 |
October | 343.83 | 22.25 | 102.17 | 22.77 | 5.33 | 22.77 |
November | 445.17 | 21.40 | 113.67 | 21.40 | 86.33 | 21.25 |
December | 460.83 | 20.94 | 204.67 | 20.77 | 197.50 | 20.65 |
Annual Sum or Average | 3638.67 | 21.83 | 2165.67 | 22.30 | 723.50 | 22.10 |
Minimum of Months | 99.17 | 20.75 | 73.17 | 20.53 | 2.00 | 20.40 |
Maximum of Months | 490.17 | 23.60 | 341.17 | 24.21 | 239.67 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 310.83 | 20.26 | 310.83 | 20.19 |
February | 445.67 | 20.94 | 171.17 | 20.74 | 170.67 | 20.63 |
March | 481.33 | 21.59 | 66.00 | 21.50 | 57.17 | 21.39 |
April | 364.17 | 22.21 | 65.17 | 22.50 | 7.00 | 22.46 |
May | 280.83 | 22.93 | 131.33 | 23.42 | 10.17 | 23.51 |
June | 173.33 | 23.11 | 185.83 | 23.75 | 3.67 | 23.78 |
July | 102.33 | 23.62 | 314.83 | 24.24 | 12.83 | 24.32 |
August | 113.33 | 23.36 | 327.00 | 24.07 | 9.33 | 24.13 |
September | 240.83 | 22.91 | 170.50 | 23.54 | 6.83 | 23.59 |
October | 433.67 | 22.00 | 39.83 | 22.13 | 9.00 | 22.10 |
November | 482.33 | 21.11 | 119.50 | 20.97 | 115.50 | 20.85 |
December | 497.00 | 20.68 | 252.33 | 20.52 | 252.33 | 20.44 |
Annual Sum or Average | 4116.83 | 21.64 | 2154.33 | 21.96 | 965.33 | 21.76 |
Minimum of Months | 102.33 | 20.42 | 39.83 | 20.26 | 3.67 | 20.19 |
Maximum of Months | 502.00 | 23.62 | 327.00 | 24.24 | 310.83 | 24.32 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.98847 | 31.35816 | -0.0434 | 6.63173 |
February | 454.00000 | 23.70706 | 31.18595 | 0.15414 | 5.85900 |
March | 514.00000 | 24.11702 | 29.84220 | 0.27449 | 6.69998 |
April | 485.00000 | 24.34480 | 32.55679 | 0.37061 | 8.14933 |
May | 508.00000 | 24.39505 | 36.25002 | -0.4260 | 9.24724 |
June | 496.00000 | 24.41117 | 38.20328 | -0.3822 | 8.56025 |
July | 497.00000 | 24.52654 | 42.33540 | -0.3076 | 7.65396 |
August | 514.00000 | 24.42955 | 45.55966 | -0.3067 | 7.52912 |
September | 485.00000 | 24.47746 | 43.11202 | -0.3374 | 8.06137 |
October | 502.00000 | 24.37063 | 35.86059 | 0.40050 | 8.63655 |
November | 489.00000 | 24.01995 | 35.90165 | 0.27665 | 6.94828 |
December | 497.00000 | 23.59932 | 31.41149 | 0.12367 | 5.58547 |
Annual Sum or Average | 5943.00000 | 24.11811 | 36.16525 | -0.0191 | 7.47464 |
Minimum of Months | 454.00000 | 22.98847 | 29.84220 | -0.4260 | 5.58547 |
Maximum of Months | 514.00000 | 24.52654 | 45.55966 | 0.40050 | 9.24724 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37193 | 34.19431 | -0.4029 | 9.89857 |
February | 454.00000 | 22.04845 | 34.43878 | -0.2186 | 7.05319 |
March | 514.00000 | 22.96875 | 33.03034 | 0.00976 | 5.57133 |
April | 485.00000 | 23.56255 | 35.07480 | 0.18501 | 6.26941 |
May | 508.00000 | 23.91876 | 38.03238 | -0.6032 | 13.11705 |
June | 496.00000 | 24.08251 | 39.55881 | -0.5137 | 10.82278 |
July | 497.00000 | 24.22615 | 43.53060 | -0.4298 | 9.19414 |
August | 514.00000 | 24.17968 | 46.74298 | -0.4161 | 8.94039 |
September | 485.00000 | 24.04243 | 44.91120 | -0.5081 | 10.86246 |
October | 502.00000 | 23.43660 | 38.99909 | 0.17510 | 6.23773 |
November | 489.00000 | 22.46621 | 39.87926 | -0.0794 | 6.10344 |
December | 497.00000 | 21.79191 | 34.97230 | -0.2843 | 7.34611 |
Annual Sum or Average | 5943.00000 | 23.18344 | 38.63932 | -0.2581 | 8.46495 |
Minimum of Months | 454.00000 | 21.37193 | 33.03034 | -0.6032 | 5.57133 |
Maximum of Months | 514.00000 | 24.22615 | 46.74298 | 0.18501 | 13.11705 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.73132 | 35.14616 | -0.5771 | 14.05593 |
February | 454.00000 | 21.27389 | 35.53041 | -0.4189 | 10.47014 |
March | 514.00000 | 22.17078 | 34.33164 | -0.1839 | 6.73554 |
April | 485.00000 | 23.00753 | 36.10963 | 0.05178 | 6.14899 |
May | 508.00000 | 23.59576 | 38.76612 | -0.7150 | 16.86466 |
June | 496.00000 | 23.90187 | 39.90618 | -0.5768 | 12.49229 |
July | 497.00000 | 24.06720 | 43.70186 | -0.4825 | 10.31523 |
August | 514.00000 | 24.02491 | 46.90066 | -0.4719 | 10.15394 |
September | 485.00000 | 23.67046 | 45.93362 | -0.6417 | 14.60815 |
October | 502.00000 | 22.67688 | 40.86734 | -0.0105 | 6.11626 |
November | 489.00000 | 21.58498 | 41.87432 | -0.3014 | 8.17953 |
December | 497.00000 | 21.00178 | 36.35059 | -0.4951 | 11.21399 |
Annual Sum or Average | 5943.00000 | 22.65337 | 39.64046 | -0.4023 | 10.61611 |
Minimum of Months | 454.00000 | 20.73132 | 34.33164 | -0.7150 | 6.11626 |
Maximum of Months | 514.00000 | 24.06720 | 46.90066 | 0.05178 | 16.86466 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07707 | 36.84456 | -0.7790 | 20.33735 |
February | 454.00000 | 20.47594 | 37.31273 | -0.6418 | 16.10024 |
March | 514.00000 | 21.24243 | 36.96356 | -0.4134 | 9.99103 |
April | 485.00000 | 22.30786 | 38.12369 | -0.1147 | 7.30024 |
May | 508.00000 | 23.18214 | 40.39173 | -0.8473 | 22.63555 |
June | 496.00000 | 23.71379 | 40.96116 | -0.6328 | 14.70184 |
July | 497.00000 | 23.93932 | 44.29361 | -0.5123 | 11.51688 |
August | 514.00000 | 23.85425 | 47.99465 | -0.5215 | 11.86345 |
September | 485.00000 | 23.16801 | 48.22862 | -0.8138 | 21.14151 |
October | 502.00000 | 21.76809 | 43.97925 | -0.2292 | 7.67209 |
November | 489.00000 | 20.71225 | 44.22970 | -0.5337 | 12.70228 |
December | 497.00000 | 20.25698 | 38.38885 | -0.7171 | 17.44909 |
Annual Sum or Average | 5943.00000 | 22.07139 | 41.49759 | -0.5628 | 14.43651 |
Minimum of Months | 454.00000 | 20.07707 | 36.84456 | -0.8473 | 7.30024 |
Maximum of Months | 514.00000 | 23.93932 | 48.22862 | -0.1147 | 22.63555 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10685 | 36.26750 | -0.7685 | 19.85309 |
February | 454.00000 | 20.61950 | 36.57503 | -0.5955 | 14.48426 |
March | 514.00000 | 21.42748 | 36.08710 | -0.3477 | 9.38820 |
April | 485.00000 | 22.62317 | 36.77313 | -0.0021 | 7.54594 |
May | 508.00000 | 23.25981 | 39.69032 | -0.7601 | 20.96472 |
June | 496.00000 | 23.79884 | 40.19000 | -0.5216 | 13.22446 |
July | 497.00000 | 24.01087 | 43.79141 | -0.4097 | 10.79684 |
August | 514.00000 | 23.93846 | 47.35406 | -0.4052 | 10.70302 |
September | 485.00000 | 23.20589 | 47.48075 | -0.7331 | 20.18543 |
October | 502.00000 | 21.92028 | 42.97944 | -0.1704 | 7.76218 |
November | 489.00000 | 20.72371 | 43.68397 | -0.5234 | 12.41437 |
December | 497.00000 | 20.28872 | 37.83064 | -0.7038 | 17.01789 |
Annual Sum or Average | 5943.00000 | 22.17316 | 40.74768 | -0.4946 | 13.68320 |
Minimum of Months | 454.00000 | 20.10685 | 36.08710 | -0.7685 | 7.54594 |
Maximum of Months | 514.00000 | 24.01087 | 47.48075 | -0.0021 | 20.96472 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46078 | 35.17821 | -0.6632 | 17.43117 |
February | 454.00000 | 21.24719 | 34.87528 | -0.4277 | 12.72637 |
March | 514.00000 | 21.83400 | 34.57308 | -0.2353 | 9.48829 |
April | 485.00000 | 22.68248 | 36.04489 | 0.01805 | 8.24795 |
May | 508.00000 | 23.20017 | 39.39023 | -0.7800 | 22.27751 |
June | 496.00000 | 23.60804 | 40.53459 | -0.6128 | 15.77969 |
July | 497.00000 | 23.90719 | 43.83345 | -0.4539 | 12.08072 |
August | 514.00000 | 23.85368 | 47.30916 | -0.4336 | 11.81473 |
September | 485.00000 | 23.34755 | 46.46971 | -0.6487 | 18.68558 |
October | 502.00000 | 22.38122 | 41.15687 | -0.0391 | 8.53517 |
November | 489.00000 | 21.16373 | 42.13078 | -0.4069 | 11.49195 |
December | 497.00000 | 20.74912 | 36.40865 | -0.5741 | 15.13207 |
Annual Sum or Average | 5943.00000 | 22.37918 | 39.85501 | -0.4386 | 13.64856 |
Minimum of Months | 454.00000 | 20.46078 | 34.57308 | -0.7800 | 8.24795 |
Maximum of Months | 514.00000 | 23.90719 | 47.30916 | 0.01805 | 22.27751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12437 | 36.00742 | -0.7658 | 19.86646 |
February | 454.00000 | 20.65142 | 36.26302 | -0.5923 | 15.03316 |
March | 514.00000 | 21.32688 | 35.95447 | -0.3746 | 10.08158 |
April | 485.00000 | 22.28940 | 37.34138 | -0.0808 | 8.11399 |
May | 508.00000 | 23.07245 | 40.09903 | -0.8109 | 23.75216 |
June | 496.00000 | 23.50984 | 41.11479 | -0.6261 | 16.35242 |
July | 497.00000 | 23.88637 | 44.11961 | -0.4312 | 12.18941 |
August | 514.00000 | 23.74864 | 48.01083 | -0.4682 | 12.70900 |
September | 485.00000 | 23.10226 | 47.67296 | -0.7566 | 21.55850 |
October | 502.00000 | 21.75946 | 43.14074 | -0.2071 | 8.07756 |
November | 489.00000 | 20.73570 | 43.44196 | -0.5242 | 12.54205 |
December | 497.00000 | 20.32567 | 37.53253 | -0.6981 | 17.03799 |
Annual Sum or Average | 5943.00000 | 22.05620 | 40.91762 | -0.5278 | 14.77275 |
Minimum of Months | 454.00000 | 20.12437 | 35.95447 | -0.8109 | 8.07756 |
Maximum of Months | 514.00000 | 23.88637 | 48.01083 | -0.0808 | 23.75216 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40948 | 36.57401 | -0.6809 | 16.13617 |
February | 454.00000 | 20.76098 | 37.12555 | -0.5572 | 12.64083 |
March | 514.00000 | 21.36228 | 36.58652 | -0.3786 | 8.58199 |
April | 485.00000 | 22.27277 | 38.38108 | -0.1281 | 6.41647 |
May | 508.00000 | 23.25424 | 40.72310 | -0.8460 | 21.37021 |
June | 496.00000 | 23.77840 | 41.36675 | -0.6358 | 14.07770 |
July | 497.00000 | 24.02776 | 44.62915 | -0.5067 | 10.77528 |
August | 514.00000 | 23.95759 | 48.20838 | -0.5043 | 10.82134 |
September | 485.00000 | 23.49795 | 47.58864 | -0.7089 | 16.54912 |
October | 502.00000 | 22.40174 | 42.30487 | -0.0711 | 5.92856 |
November | 489.00000 | 21.32881 | 42.84663 | -0.3541 | 8.61148 |
December | 497.00000 | 20.68717 | 37.67629 | -0.5781 | 12.46040 |
Annual Sum or Average | 5943.00000 | 22.32379 | 41.19050 | -0.4960 | 12.03514 |
Minimum of Months | 454.00000 | 20.40948 | 36.57401 | -0.8460 | 5.92856 |
Maximum of Months | 514.00000 | 24.02776 | 48.20838 | -0.0711 | 21.37021 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43093 | 36.53326 | -0.6708 | 15.76064 |
February | 454.00000 | 20.96204 | 36.77841 | -0.4967 | 11.16776 |
March | 514.00000 | 21.72234 | 35.92469 | -0.2750 | 7.56353 |
April | 485.00000 | 22.92162 | 36.65182 | 0.05486 | 6.64131 |
May | 508.00000 | 23.53670 | 39.56859 | -0.6987 | 17.49282 |
June | 496.00000 | 24.04587 | 40.01578 | -0.4687 | 11.00001 |
July | 497.00000 | 24.21300 | 43.76698 | -0.3694 | 9.10608 |
August | 514.00000 | 24.15906 | 47.12391 | -0.3477 | 8.78165 |
September | 485.00000 | 23.71105 | 46.45912 | -0.5763 | 14.00595 |
October | 502.00000 | 22.68201 | 41.34356 | 0.01608 | 6.33700 |
November | 489.00000 | 21.35026 | 42.77022 | -0.3398 | 8.45142 |
December | 497.00000 | 20.73188 | 37.59046 | -0.5610 | 12.11062 |
Annual Sum or Average | 5943.00000 | 22.55100 | 40.39800 | -0.3943 | 10.70138 |
Minimum of Months | 454.00000 | 20.43093 | 35.92469 | -0.6987 | 6.33700 |
Maximum of Months | 514.00000 | 24.21300 | 47.12391 | 0.05486 | 17.49282 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33200 | 34.38945 | -0.6513 | 15.91597 |
February | 454.00000 | 21.13525 | 34.23888 | -0.4076 | 10.85756 |
March | 514.00000 | 21.66863 | 33.85226 | -0.2428 | 8.17193 |
April | 485.00000 | 22.48763 | 35.94983 | -0.0163 | 7.36626 |
May | 508.00000 | 23.01576 | 39.66772 | -0.8398 | 22.99215 |
June | 496.00000 | 23.47223 | 40.91409 | -0.6666 | 16.66491 |
July | 497.00000 | 23.96898 | 44.06038 | -0.4505 | 11.20848 |
August | 514.00000 | 23.93895 | 47.42598 | -0.4086 | 10.48805 |
September | 485.00000 | 23.62537 | 45.67249 | -0.5439 | 14.65077 |
October | 502.00000 | 22.79811 | 39.36173 | 0.08945 | 7.64256 |
November | 489.00000 | 21.33138 | 40.47303 | -0.3105 | 9.24650 |
December | 497.00000 | 20.77676 | 35.17738 | -0.5109 | 12.50338 |
Annual Sum or Average | 5943.00000 | 22.38898 | 39.29807 | -0.4140 | 12.33003 |
Minimum of Months | 454.00000 | 20.33200 | 33.85226 | -0.8398 | 7.36626 |
Maximum of Months | 514.00000 | 23.96898 | 47.42598 | 0.08945 | 22.99215 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44449 | 36.18941 | -0.6691 | 15.76027 |
February | 454.00000 | 20.93753 | 36.46801 | -0.5034 | 11.64140 |
March | 514.00000 | 21.56479 | 35.77991 | -0.3119 | 8.13097 |
April | 485.00000 | 22.57547 | 37.16525 | -0.0264 | 6.87024 |
May | 508.00000 | 23.48845 | 39.55514 | -0.7065 | 17.99813 |
June | 496.00000 | 23.83831 | 40.75663 | -0.5497 | 12.77169 |
July | 497.00000 | 24.25900 | 43.54696 | -0.3368 | 8.75523 |
August | 514.00000 | 24.10340 | 47.38651 | -0.3714 | 9.24006 |
September | 485.00000 | 23.75218 | 46.21838 | -0.5569 | 13.62532 |
October | 502.00000 | 22.51601 | 41.48777 | -0.0197 | 6.41619 |
November | 489.00000 | 21.29079 | 42.59418 | -0.3540 | 8.68111 |
December | 497.00000 | 20.74096 | 37.25215 | -0.5606 | 12.20029 |
Annual Sum or Average | 5943.00000 | 22.47119 | 40.38937 | -0.4138 | 11.00868 |
Minimum of Months | 454.00000 | 20.44449 | 35.77991 | -0.7065 | 6.41619 |
Maximum of Months | 514.00000 | 24.25900 | 47.38651 | -0.0197 | 17.99813 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38870 | 36.39726 | -0.6697 | 16.19688 |
February | 454.00000 | 20.86737 | 36.68543 | -0.5150 | 12.24810 |
March | 514.00000 | 21.76730 | 36.09725 | -0.2692 | 7.51252 |
April | 485.00000 | 22.79369 | 37.23248 | 0.00688 | 6.34760 |
May | 508.00000 | 23.54791 | 39.55279 | -0.7235 | 17.36237 |
June | 496.00000 | 23.92373 | 40.47718 | -0.5612 | 12.15605 |
July | 497.00000 | 24.11039 | 44.02610 | -0.4556 | 9.78326 |
August | 514.00000 | 24.03132 | 47.66812 | -0.4602 | 9.97341 |
September | 485.00000 | 23.59251 | 47.06755 | -0.6671 | 15.50659 |
October | 502.00000 | 22.41827 | 42.40065 | -0.0638 | 6.23766 |
November | 489.00000 | 21.23207 | 43.08906 | -0.3792 | 9.29722 |
December | 497.00000 | 20.63339 | 37.65560 | -0.5868 | 13.00315 |
Annual Sum or Average | 5943.00000 | 22.45488 | 40.71824 | -0.4453 | 11.29573 |
Minimum of Months | 454.00000 | 20.38870 | 36.09725 | -0.7235 | 6.23766 |
Maximum of Months | 514.00000 | 24.11039 | 47.66812 | 0.00688 | 17.36237 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.28098 | 35.26913 | -0.6963 | 16.92241 |
February | 385.00000 | 20.89946 | 35.26928 | -0.5039 | 11.71754 |
March | 433.00000 | 21.69856 | 34.90314 | -0.2677 | 7.74923 |
April | 410.00000 | 22.87526 | 35.67524 | 0.05722 | 6.97240 |
May | 430.00000 | 23.46967 | 38.72449 | -0.7000 | 18.13272 |
June | 418.00000 | 23.93573 | 39.73933 | -0.4904 | 12.03685 |
July | 422.00000 | 24.16646 | 43.27800 | -0.3785 | 9.85829 |
August | 433.00000 | 24.07837 | 46.81909 | -0.3771 | 9.83002 |
September | 410.00000 | 23.49192 | 46.29500 | -0.6442 | 16.51603 |
October | 427.00000 | 22.30290 | 41.41964 | -0.0698 | 6.75919 |
November | 417.00000 | 21.07737 | 42.12829 | -0.4118 | 9.72695 |
December | 422.00000 | 20.55576 | 36.57646 | -0.6054 | 13.47398 |
Annual Sum or Average | 5034.00000 | 22.41174 | 39.69944 | -0.4239 | 11.64009 |
Minimum of Months | 385.00000 | 20.28098 | 34.90314 | -0.7000 | 6.75919 |
Maximum of Months | 433.00000 | 24.16646 | 46.81909 | 0.05722 | 18.13272 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.83908 | 34.69118 | -0.5418 | 13.82574 |
February | 454.00000 | 21.66521 | 34.22997 | -0.2977 | 10.09376 |
March | 514.00000 | 22.30293 | 33.74770 | -0.1043 | 7.66532 |
April | 485.00000 | 23.10988 | 35.22801 | 0.12664 | 7.61706 |
May | 508.00000 | 23.56481 | 38.59612 | -0.6579 | 16.98994 |
June | 496.00000 | 23.85969 | 40.02823 | -0.5312 | 12.63171 |
July | 497.00000 | 24.11896 | 43.50663 | -0.3880 | 9.83761 |
August | 514.00000 | 24.05840 | 46.94673 | -0.3672 | 9.62714 |
September | 485.00000 | 23.74171 | 45.46994 | -0.5132 | 13.56915 |
October | 502.00000 | 22.91722 | 39.80698 | 0.10222 | 7.79433 |
November | 489.00000 | 21.68101 | 41.06105 | -0.2540 | 8.89710 |
December | 497.00000 | 21.18398 | 35.59062 | -0.4345 | 11.40321 |
Annual Sum or Average | 5943.00000 | 22.76246 | 39.10566 | -0.3225 | 10.83679 |
Minimum of Months | 454.00000 | 20.83908 | 33.74770 | -0.6579 | 7.61706 |
Maximum of Months | 514.00000 | 24.11896 | 46.94673 | 0.12664 | 16.98994 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41600 | 35.67527 | -0.6602 | 15.90783 |
February | 454.00000 | 20.99946 | 35.78265 | -0.4738 | 11.64779 |
March | 514.00000 | 21.75160 | 35.29541 | -0.2496 | 7.90434 |
April | 485.00000 | 22.73027 | 36.54262 | 0.03166 | 7.19694 |
May | 508.00000 | 23.46685 | 39.28385 | -0.6801 | 18.07515 |
June | 496.00000 | 23.78590 | 40.59376 | -0.5373 | 12.94228 |
July | 497.00000 | 24.11310 | 43.75895 | -0.3611 | 9.83204 |
August | 514.00000 | 23.98342 | 47.59249 | -0.3927 | 10.21234 |
September | 485.00000 | 23.54287 | 46.57227 | -0.6072 | 15.70594 |
October | 502.00000 | 22.30547 | 41.82652 | -0.0616 | 6.76238 |
November | 489.00000 | 21.15622 | 42.56461 | -0.3881 | 9.45557 |
December | 497.00000 | 20.67650 | 36.89295 | -0.5730 | 12.85113 |
Annual Sum or Average | 5943.00000 | 22.42218 | 40.22465 | -0.4127 | 11.54085 |
Minimum of Months | 454.00000 | 20.41600 | 35.29541 | -0.6801 | 6.76238 |
Maximum of Months | 514.00000 | 24.11310 | 47.59249 | 0.03166 | 18.07515 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.515070E+11 | 0.00 | 426.03 | 174234.70 | 02-JAN-06:11 | 0.00 | 31.12 | 47.70 | 0.18 | 0.00 | 0.08 | 0.70 | 02-JAN-06:11 |
February | 0.272530E+11 | 0.00 | 323.79 | 166854.19 | 06-FEB-06:11 | 0.00 | 29.21 | 43.69 | 0.10 | 0.00 | 0.05 | 0.67 | 06-FEB-06:11 |
March | 0.959428E+10 | 0.00 | 275.49 | 170694.10 | 01-MAR-07:01 | 0.00 | 27.22 | 38.68 | 0.03 | 0.00 | 0.01 | 0.69 | 01-MAR-07:01 |
April | 0.317106E+10 | 0.00 | 121.57 | 155430.89 | 18-APR-06:02 | 0.00 | 31.15 | 35.99 | 0.01 | 0.00 | 0.00 | 0.63 | 18-APR-06:02 |
May | 0.892016E+09 | 0.00 | 52.03 | 67450.33 | 18-MAY-06:03 | 0.00 | 35.92 | 37.58 | 0.00 | 0.00 | 0.00 | 0.27 | 18-MAY-06:03 |
June | 0.340977E+09 | 0.00 | 24.00 | 10926.40 | 15-JUN-06:05 | 0.00 | 38.99 | 39.70 | 0.00 | 0.00 | 0.00 | 0.04 | 15-JUN-06:05 |
July | 85232022.84 | 0.00 | 58.85 | 11311.26 | 12-JUL-06:06 | 0.00 | 31.00 | 33.40 | 0.00 | 0.00 | 0.00 | 0.05 | 12-JUL-06:06 |
August | 95249394.95 | 0.00 | 108.23 | 11789.65 | 01-AUG-06:07 | 0.00 | 36.80 | 40.24 | 0.00 | 0.00 | 0.00 | 0.05 | 01-AUG-06:07 |
September | 0.380873E+09 | 0.00 | 56.24 | 54334.95 | 28-SEP-06:03 | 0.00 | 37.68 | 39.48 | 0.00 | 0.00 | 0.00 | 0.22 | 28-SEP-06:03 |
October | 0.308693E+10 | 0.00 | 164.84 | 140686.83 | 31-OCT-06:03 | 0.00 | 30.95 | 37.59 | 0.01 | 0.00 | 0.00 | 0.57 | 31-OCT-06:03 |
November | 0.188973E+11 | 0.00 | 318.68 | 161606.26 | 28-NOV-07:01 | 0.00 | 27.76 | 41.48 | 0.06 | 0.00 | 0.03 | 0.65 | 28-NOV-07:01 |
December | 0.382295E+11 | 0.00 | 384.56 | 162807.09 | 21-DEC-07:01 | 0.00 | 28.78 | 44.64 | 0.12 | 0.00 | 0.06 | 0.66 | 21-DEC-07:01 |
Annual Sum or Average | 0.153533E+12 | 0.00 | 2314.29 | 0.00 | 32.22 | 39.99 | 0.04 | 0.00 | 0.02 | ||||
Minimum of Months | 85232022.84 | 0.00 | 24.00 | 10926.40 | 0.00 | 27.22 | 33.40 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.515070E+11 | 0.00 | 426.03 | 174234.70 | 0.00 | 38.99 | 47.70 | 0.18 | 0.00 | 0.08 | 0.70 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2824018.97 | 752627.61 | 0.42 | 2590215.13 | 233803.83 | 0.00 | 0.15 | 03-JAN-07:25 | 0.00 | 01-JAN-00:05 | 3467.54 | 03-JAN-07:25 | 3292.02 | 03-JAN-07:25 | 175.51 | 03-JAN-07:25 | 912.91 | 03-JAN-07:25 | 0.00 |
February | 0.211916E+09 | 52919225.27 | 8.00 | 0.195303E+09 | 16612783.14 | 0.00 | 0.51 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 13330.76 | 27-FEB-15:10 | 13330.76 | 27-FEB-15:10 | 1272.44 | 27-FEB-17:30 | 3205.00 | 27-FEB-15:10 | 0.00 |
March | 0.321181E+09 | 82529779.92 | 22.33 | 0.283806E+09 | 37375076.92 | 0.00 | 0.43 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10815.83 | 18-MAR-16:00 | 10815.83 | 18-MAR-16:00 | 1448.77 | 09-MAR-12:00 | 2659.21 | 18-MAR-16:00 | 0.00 |
April | 0.353408E+10 | 0.816437E+09 | 67.71 | 0.340468E+10 | 0.129399E+09 | 0.00 | 1.00 | 26-APR-13:20 | 0.00 | 01-APR-00:10 | 51950.68 | 27-APR-15:00 | 51950.68 | 27-APR-15:00 | 4139.30 | 28-APR-13:00 | 11850.26 | 27-APR-15:00 | 0.00 |
May | 0.770096E+10 | 0.176350E+10 | 159.03 | 0.690822E+10 | 0.792738E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 46599.70 | 15-MAY-16:00 | 46599.70 | 15-MAY-16:00 | 5595.23 | 05-MAY-18:00 | 9804.45 | 15-MAY-16:00 | 0.00 |
June | 0.146596E+11 | 0.334714E+10 | 264.77 | 0.137081E+11 | 0.951441E+09 | 0.00 | 1.00 | 09-JUN-13:50 | 0.00 | 01-JUN-00:10 | 53880.48 | 28-JUN-15:30 | 53880.48 | 28-JUN-15:30 | 10107.71 | 12-JUN-06:02 | 11946.50 | 28-JUN-15:30 | 0.00 |
July | 0.281712E+11 | 0.632488E+10 | 350.18 | 0.251131E+11 | 0.305805E+10 | 0.00 | 1.00 | 06-JUL-14:30 | 0.00 | 01-JUL-00:10 | 71647.56 | 31-JUL-16:00 | 66799.33 | 24-JUL-15:00 | 15689.34 | 31-JUL-06:03 | 17476.16 | 24-JUL-15:00 | 0.00 |
August | 0.380933E+11 | 0.860712E+10 | 375.40 | 0.335915E+11 | 0.450170E+10 | 0.00 | 1.00 | 07-AUG-09:00 | 0.00 | 01-AUG-00:10 | 72382.29 | 10-AUG-15:30 | 68771.18 | 10-AUG-16:00 | 19006.87 | 30-AUG-06:03 | 18190.51 | 10-AUG-16:00 | 0.00 |
September | 0.139892E+11 | 0.314005E+10 | 229.85 | 0.117607E+11 | 0.222848E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 57860.73 | 12-SEP-16:00 | 55154.30 | 12-SEP-15:20 | 14598.88 | 14-SEP-11:00 | 12343.15 | 12-SEP-16:00 | 0.00 |
October | 0.180820E+10 | 0.430126E+09 | 59.60 | 0.171346E+10 | 94737123.60 | 0.00 | 1.00 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 35441.99 | 04-OCT-15:00 | 35441.99 | 04-OCT-15:00 | 3580.24 | 08-OCT-13:02 | 7440.64 | 04-OCT-15:00 | 0.00 |
November | 0.366284E+09 | 86568535.76 | 7.67 | 0.252063E+09 | 0.114221E+09 | 0.00 | 0.71 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 19368.19 | 04-NOV-14:20 | 14748.52 | 04-NOV-14:20 | 5485.21 | 04-NOV-16:00 | 4421.61 | 04-NOV-14:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.108859E+12 | 0.246520E+11 | 1544.95 | 0.969337E+11 | 0.119250E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.380933E+11 | 0.860712E+10 | 375.40 | 0.335915E+11 | 0.450170E+10 | 0.00 | 1.00 | 0.00 | 72382.29 | 68771.18 | 19006.87 | 18190.51 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.210345E+09 | 52355320.72 | 8.00 | 0.196605E+09 | 13739820.74 | 0.00 | 0.55 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 13578.77 | 27-FEB-15:00 | 13578.77 | 27-FEB-15:00 | 1177.37 | 27-FEB-17:25 | 3232.54 | 27-FEB-15:00 | 0.00 |
March | 0.322623E+09 | 82059170.64 | 22.17 | 0.290740E+09 | 31882962.75 | 0.00 | 0.49 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 12030.88 | 18-MAR-16:00 | 12030.88 | 18-MAR-16:00 | 1341.87 | 09-MAR-12:00 | 2905.79 | 18-MAR-16:00 | 0.00 |
April | 0.350365E+10 | 0.809283E+09 | 70.94 | 0.338393E+10 | 0.119722E+09 | 0.00 | 1.00 | 26-APR-13:10 | 0.00 | 01-APR-00:10 | 49846.92 | 27-APR-14:50 | 49846.92 | 27-APR-14:50 | 4218.73 | 28-APR-13:00 | 11343.15 | 27-APR-15:00 | 0.00 |
May | 0.734009E+10 | 0.168028E+10 | 162.21 | 0.660658E+10 | 0.733511E+09 | 0.00 | 1.00 | 04-MAY-12:40 | 0.00 | 01-MAY-00:10 | 44298.93 | 04-MAY-15:00 | 44298.93 | 04-MAY-15:00 | 6390.95 | 07-MAY-16:11 | 9428.27 | 04-MAY-15:00 | 0.00 |
June | 0.134516E+11 | 0.308035E+10 | 269.49 | 0.125718E+11 | 0.879858E+09 | 0.00 | 1.00 | 09-JUN-13:30 | 0.00 | 01-JUN-00:10 | 49984.85 | 28-JUN-15:30 | 49984.85 | 28-JUN-15:30 | 5518.56 | 12-JUN-12:50 | 11083.14 | 28-JUN-15:30 | 0.00 |
July | 0.253931E+11 | 0.571642E+10 | 352.61 | 0.227128E+11 | 0.268031E+10 | 0.00 | 1.00 | 06-JUL-14:40 | 0.00 | 01-JUL-00:10 | 65671.85 | 31-JUL-14:40 | 59623.45 | 31-JUL-15:20 | 11876.10 | 31-JUL-10:30 | 15559.60 | 24-JUL-15:00 | 0.00 |
August | 0.334197E+11 | 0.758227E+10 | 375.41 | 0.295095E+11 | 0.391020E+10 | 0.00 | 1.00 | 06-AUG-13:13 | 0.00 | 01-AUG-00:10 | 67191.91 | 29-AUG-14:40 | 62533.77 | 10-AUG-15:20 | 15747.17 | 30-AUG-13:00 | 16762.13 | 29-AUG-15:20 | 0.00 |
September | 0.124764E+11 | 0.281100E+10 | 230.54 | 0.104646E+11 | 0.201179E+10 | 0.00 | 1.00 | 08-SEP-13:50 | 0.00 | 01-SEP-00:10 | 52578.57 | 14-SEP-13:00 | 49300.69 | 12-SEP-15:20 | 14294.56 | 14-SEP-13:00 | 11102.16 | 14-SEP-13:00 | 0.00 |
October | 0.161693E+10 | 0.385239E+09 | 58.25 | 0.151808E+10 | 98858850.86 | 0.00 | 1.00 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 | 31746.37 | 04-OCT-15:00 | 31746.37 | 04-OCT-15:00 | 4348.63 | 08-OCT-13:02 | 6665.36 | 04-OCT-15:00 | 0.00 |
November | 0.383128E+09 | 89209910.56 | 7.67 | 0.275257E+09 | 0.107871E+09 | 0.00 | 0.76 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 19812.91 | 04-NOV-13:40 | 15622.06 | 04-NOV-14:00 | 5127.92 | 04-NOV-16:00 | 4458.72 | 04-NOV-13:40 | 0.00 |
December | 43020.58 | 11655.65 | 0.02 | 42697.15 | 323.44 | 0.00 | 0.02 | 27-DEC-07:04 | 0.00 | 01-DEC-00:10 | 501.91 | 27-DEC-07:04 | 498.13 | 27-DEC-07:04 | 3.77 | 27-DEC-07:04 | 135.98 | 27-DEC-07:04 | 0.00 |
Annual Sum or Average | 0.981177E+11 | 0.222885E+11 | 1557.32 | 0.875299E+11 | 0.105877E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.334197E+11 | 0.758227E+10 | 375.41 | 0.295095E+11 | 0.391020E+10 | 0.00 | 1.00 | 0.00 | 67191.91 | 62533.77 | 15747.17 | 16762.13 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 306623.24 | 83162.89 | 0.25 | 290659.09 | 15964.15 | 0.00 | 0.03 | 03-JAN-07:12 | 0.00 | 01-JAN-00:05 | 666.90 | 03-JAN-07:12 | 600.08 | 03-JAN-07:12 | 66.82 | 03-JAN-07:12 | 180.50 | 03-JAN-07:12 | 0.00 |
February | 0.215832E+09 | 54103964.99 | 8.08 | 0.196455E+09 | 19376818.41 | 0.00 | 0.50 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 13470.71 | 27-FEB-15:00 | 13470.71 | 27-FEB-15:00 | 1382.55 | 27-FEB-17:13 | 3250.36 | 27-FEB-15:00 | 0.00 |
March | 0.329246E+09 | 84226408.69 | 22.00 | 0.292254E+09 | 36992542.66 | 0.00 | 0.45 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 12113.99 | 18-MAR-16:00 | 12113.99 | 18-MAR-16:00 | 1493.17 | 09-MAR-12:00 | 2956.98 | 18-MAR-16:00 | 0.00 |
April | 0.375525E+10 | 0.869864E+09 | 71.09 | 0.359781E+10 | 0.157438E+09 | 0.00 | 1.00 | 26-APR-13:30 | 0.00 | 01-APR-00:10 | 57561.79 | 27-APR-14:40 | 57561.79 | 27-APR-14:40 | 4016.27 | 28-APR-13:00 | 13077.81 | 27-APR-15:00 | 0.00 |
May | 0.765878E+10 | 0.175919E+10 | 160.17 | 0.679918E+10 | 0.859603E+09 | 0.00 | 1.00 | 04-MAY-12:50 | 0.00 | 01-MAY-00:10 | 48074.45 | 04-MAY-15:00 | 48074.45 | 04-MAY-15:00 | 6251.80 | 05-MAY-18:00 | 10232.40 | 04-MAY-15:00 | 0.00 |
June | 0.140954E+11 | 0.324221E+10 | 268.14 | 0.130322E+11 | 0.106320E+10 | 0.00 | 1.00 | 09-JUN-13:40 | 0.00 | 01-JUN-00:10 | 57977.23 | 28-JUN-15:20 | 57977.23 | 28-JUN-15:20 | 5345.03 | 12-JUN-12:30 | 12853.64 | 28-JUN-15:20 | 0.00 |
July | 0.268474E+11 | 0.607053E+10 | 351.25 | 0.237152E+11 | 0.313222E+10 | 0.00 | 1.00 | 06-JUL-15:00 | 0.00 | 01-JUL-00:10 | 73743.41 | 31-JUL-14:40 | 68316.84 | 24-JUL-15:00 | 11848.15 | 31-JUL-10:30 | 17672.57 | 24-JUL-15:00 | 0.00 |
August | 0.350887E+11 | 0.800970E+10 | 374.03 | 0.307456E+11 | 0.434313E+10 | 0.00 | 1.00 | 06-AUG-16:12 | 0.00 | 01-AUG-00:10 | 75608.63 | 10-AUG-14:50 | 71386.08 | 10-AUG-15:20 | 15967.21 | 30-AUG-13:00 | 18661.88 | 10-AUG-15:20 | 0.00 |
September | 0.125461E+11 | 0.284486E+10 | 227.40 | 0.103414E+11 | 0.220470E+10 | 0.00 | 1.00 | 08-SEP-14:10 | 0.00 | 01-SEP-00:10 | 53504.18 | 14-SEP-13:30 | 50353.76 | 12-SEP-15:20 | 13853.91 | 14-SEP-13:00 | 11288.14 | 14-SEP-13:30 | 0.00 |
October | 0.147745E+10 | 0.357023E+09 | 54.67 | 0.136982E+10 | 0.107629E+09 | 0.00 | 1.00 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 30989.70 | 04-OCT-15:00 | 30989.70 | 04-OCT-15:00 | 3226.22 | 08-OCT-13:02 | 6511.13 | 04-OCT-15:00 | 0.00 |
November | 0.394950E+09 | 92838638.30 | 7.67 | 0.274748E+09 | 0.120202E+09 | 0.00 | 0.72 | 04-NOV-13:40 | 0.00 | 01-NOV-00:10 | 20659.46 | 04-NOV-13:40 | 15757.49 | 04-NOV-14:00 | 5678.81 | 04-NOV-13:00 | 4698.77 | 04-NOV-13:40 | 0.00 |
December | 35537.80 | 9641.40 | 0.02 | 33890.41 | 1647.39 | 0.00 | 0.02 | 26-DEC-06:01 | 0.00 | 01-DEC-00:10 | 414.61 | 26-DEC-06:01 | 395.39 | 26-DEC-06:01 | 19.22 | 26-DEC-06:01 | 112.48 | 26-DEC-06:01 | 0.00 |
Annual Sum or Average | 0.102409E+12 | 0.233847E+11 | 1544.77 | 0.903650E+11 | 0.120445E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 35537.80 | 9641.40 | 0.02 | 33890.41 | 1647.39 | 0.00 | 0.02 | 0.00 | 414.61 | 395.39 | 19.22 | 112.48 | 0.00 | ||||||
Maximum of Months | 0.350887E+11 | 0.800970E+10 | 374.03 | 0.307456E+11 | 0.434313E+10 | 0.00 | 1.00 | 0.00 | 75608.63 | 71386.08 | 15967.21 | 18661.88 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.13 | 0.00 | 241.13 | 10.11 | 1446.73 | 0.00 | 0.00 | 0.00 |
February | 375.20 | 0.00 | 375.20 | 79.81 | 1283.75 | 0.00 | 0.00 | 0.00 |
March | 552.80 | 0.00 | 552.80 | 240.88 | 1060.63 | 0.00 | 0.00 | 0.00 |
April | 782.27 | 2.77 | 779.49 | 513.30 | 862.74 | 0.00 | 0.00 | 0.00 |
May | 1006.58 | 29.90 | 976.68 | 816.36 | 709.10 | 0.00 | 0.00 | 0.00 |
June | 1058.39 | 69.89 | 988.50 | 943.04 | 553.53 | 0.00 | 0.00 | 0.00 |
July | 1005.94 | 78.87 | 927.07 | 1017.09 | 500.78 | 0.00 | 0.00 | 0.00 |
August | 814.32 | 22.01 | 792.31 | 840.80 | 488.59 | 0.00 | 0.00 | 0.00 |
September | 632.53 | 0.19 | 632.35 | 487.62 | 712.84 | 0.00 | 0.00 | 0.00 |
October | 433.39 | 0.00 | 433.39 | 204.73 | 934.05 | 0.00 | 0.00 | 0.00 |
November | 272.99 | 0.00 | 272.99 | 43.22 | 1159.95 | 0.00 | 0.00 | 0.00 |
December | 204.90 | 0.00 | 204.90 | 5.46 | 1451.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 616.22 | 17.10 | 599.13 | 435.75 | 928.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.90 | 0.00 | 204.90 | 5.46 | 488.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1058.39 | 78.87 | 988.50 | 1017.09 | 1451.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 258.31 | 65.49 | 192.82 | 93.85 | 915.06 | 0.00 | 0.00 | 0.00 |
February | 473.97 | 168.22 | 305.75 | 314.65 | 807.01 | 0.00 | 0.00 | 0.00 |
March | 707.67 | 256.18 | 451.49 | 594.42 | 674.75 | 0.00 | 0.00 | 0.00 |
April | 1097.01 | 455.82 | 641.18 | 1111.62 | 553.03 | 0.00 | 0.00 | 0.00 |
May | 1167.31 | 405.85 | 761.46 | 1238.71 | 473.62 | 0.00 | 0.00 | 0.00 |
June | 1397.99 | 608.28 | 789.71 | 1591.82 | 375.67 | 0.00 | 0.00 | 0.00 |
July | 1301.85 | 584.35 | 717.51 | 1551.10 | 333.64 | 0.00 | 0.00 | 0.00 |
August | 1279.54 | 640.10 | 639.44 | 1578.71 | 324.53 | 0.00 | 0.00 | 0.00 |
September | 946.03 | 436.32 | 509.71 | 1041.23 | 455.62 | 0.00 | 0.00 | 0.00 |
October | 616.62 | 262.01 | 354.62 | 566.76 | 598.46 | 0.00 | 0.00 | 0.00 |
November | 302.23 | 85.32 | 216.91 | 165.50 | 743.56 | 0.00 | 0.00 | 0.00 |
December | 247.90 | 79.81 | 168.09 | 118.55 | 927.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 817.87 | 338.05 | 479.82 | 833.21 | 597.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.90 | 65.49 | 168.09 | 93.85 | 324.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1397.99 | 640.10 | 789.71 | 1591.82 | 927.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1065.37 | 632.62 | 432.75 | 949.35 | 1309.61 | 0.00 | 0.00 | 0.00 |
February | 1638.38 | 1014.18 | 624.20 | 1666.92 | 1192.76 | 0.00 | 0.00 | 0.00 |
March | 1762.43 | 939.88 | 822.54 | 1873.10 | 1048.92 | 0.00 | 0.00 | 0.00 |
April | 1860.79 | 807.94 | 1052.84 | 2090.29 | 903.77 | 0.00 | 0.00 | 0.00 |
May | 1701.45 | 506.88 | 1194.57 | 1925.98 | 763.07 | 0.00 | 0.00 | 0.00 |
June | 1556.66 | 417.94 | 1138.72 | 1796.72 | 609.48 | 0.00 | 0.00 | 0.00 |
July | 1697.61 | 621.75 | 1075.85 | 2168.23 | 555.23 | 0.00 | 0.00 | 0.00 |
August | 1823.86 | 850.50 | 973.37 | 2412.45 | 534.48 | 0.00 | 0.00 | 0.00 |
September | 2020.77 | 1115.93 | 904.83 | 2511.93 | 727.12 | 0.00 | 0.00 | 0.00 |
October | 1830.47 | 1130.18 | 700.29 | 2081.25 | 926.60 | 0.00 | 0.00 | 0.00 |
November | 1082.24 | 620.21 | 462.02 | 1039.15 | 1097.91 | 0.00 | 0.00 | 0.00 |
December | 1132.33 | 732.78 | 399.55 | 1112.47 | 1350.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1597.01 | 781.12 | 815.88 | 1802.80 | 916.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1065.37 | 417.94 | 399.55 | 949.35 | 534.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2020.77 | 1130.18 | 1194.57 | 2511.93 | 1350.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 272.45 | 80.34 | 192.11 | 118.04 | 922.14 | 0.00 | 0.00 | 0.00 |
February | 488.48 | 183.59 | 304.90 | 348.39 | 819.47 | 0.00 | 0.00 | 0.00 |
March | 684.49 | 231.03 | 453.46 | 580.55 | 691.20 | 0.00 | 0.00 | 0.00 |
April | 1041.38 | 398.16 | 643.22 | 1055.29 | 582.12 | 0.00 | 0.00 | 0.00 |
May | 1340.01 | 544.37 | 795.64 | 1478.93 | 498.04 | 0.00 | 0.00 | 0.00 |
June | 1288.72 | 500.37 | 788.35 | 1452.30 | 396.43 | 0.00 | 0.00 | 0.00 |
July | 1592.04 | 836.86 | 755.18 | 1968.54 | 367.16 | 0.00 | 0.00 | 0.00 |
August | 1317.00 | 672.50 | 644.50 | 1655.17 | 354.94 | 0.00 | 0.00 | 0.00 |
September | 1072.50 | 514.61 | 557.89 | 1243.48 | 482.58 | 0.00 | 0.00 | 0.00 |
October | 610.58 | 248.78 | 361.79 | 572.40 | 616.08 | 0.00 | 0.00 | 0.00 |
November | 304.06 | 85.76 | 218.30 | 173.76 | 747.70 | 0.00 | 0.00 | 0.00 |
December | 255.62 | 87.60 | 168.03 | 140.85 | 937.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 857.85 | 366.72 | 491.13 | 902.60 | 617.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.62 | 80.34 | 168.03 | 118.04 | 354.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1592.04 | 836.86 | 795.64 | 1968.54 | 937.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.37 | 0.00 | 80.37 | 2.91 | 505.87 | 0.00 | 0.00 | 0.00 |
February | 125.06 | 0.00 | 125.06 | 25.94 | 448.72 | 0.00 | 0.00 | 0.00 |
March | 184.26 | 0.00 | 184.26 | 82.15 | 364.77 | 0.00 | 0.00 | 0.00 |
April | 260.74 | 0.92 | 259.82 | 177.27 | 291.03 | 0.00 | 0.00 | 0.00 |
May | 335.51 | 9.97 | 325.54 | 278.83 | 239.75 | 0.00 | 0.00 | 0.00 |
June | 352.78 | 23.30 | 329.48 | 320.73 | 186.81 | 0.00 | 0.00 | 0.00 |
July | 335.30 | 26.29 | 309.01 | 344.07 | 169.44 | 0.00 | 0.00 | 0.00 |
August | 271.43 | 7.34 | 264.09 | 283.47 | 166.65 | 0.00 | 0.00 | 0.00 |
September | 210.83 | 0.06 | 210.77 | 162.23 | 250.35 | 0.00 | 0.00 | 0.00 |
October | 144.46 | 0.00 | 144.46 | 63.78 | 338.84 | 0.00 | 0.00 | 0.00 |
November | 90.99 | 0.00 | 90.99 | 11.83 | 424.28 | 0.00 | 0.00 | 0.00 |
December | 68.30 | 0.00 | 68.30 | 1.13 | 519.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.40 | 5.70 | 199.70 | 146.94 | 324.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.30 | 0.00 | 68.30 | 1.13 | 166.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.78 | 26.29 | 329.48 | 344.07 | 519.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.37 | 0.00 | 80.37 | 2.91 | 505.90 | 0.00 | 0.00 | 0.00 |
February | 125.07 | 0.00 | 125.07 | 25.94 | 448.75 | 0.00 | 0.00 | 0.00 |
March | 184.26 | 0.00 | 184.26 | 82.15 | 364.79 | 0.00 | 0.00 | 0.00 |
April | 260.75 | 0.92 | 259.83 | 177.28 | 291.05 | 0.00 | 0.00 | 0.00 |
May | 335.52 | 9.97 | 325.56 | 278.84 | 239.77 | 0.00 | 0.00 | 0.00 |
June | 352.79 | 23.30 | 329.50 | 320.74 | 186.82 | 0.00 | 0.00 | 0.00 |
July | 335.31 | 26.29 | 309.02 | 344.08 | 169.45 | 0.00 | 0.00 | 0.00 |
August | 271.44 | 7.34 | 264.10 | 283.48 | 166.66 | 0.00 | 0.00 | 0.00 |
September | 210.84 | 0.06 | 210.78 | 162.23 | 250.36 | 0.00 | 0.00 | 0.00 |
October | 144.46 | 0.00 | 144.46 | 63.78 | 338.86 | 0.00 | 0.00 | 0.00 |
November | 91.00 | 0.00 | 91.00 | 11.83 | 424.31 | 0.00 | 0.00 | 0.00 |
December | 68.30 | 0.00 | 68.30 | 1.13 | 519.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.41 | 5.70 | 199.71 | 146.95 | 324.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.30 | 0.00 | 68.30 | 1.13 | 166.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.79 | 26.29 | 329.50 | 344.08 | 519.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.37 | 0.00 | 80.37 | 2.91 | 505.90 | 0.00 | 0.00 | 0.00 |
February | 125.07 | 0.00 | 125.07 | 25.94 | 448.75 | 0.00 | 0.00 | 0.00 |
March | 184.26 | 0.00 | 184.26 | 82.15 | 364.79 | 0.00 | 0.00 | 0.00 |
April | 260.75 | 0.92 | 259.83 | 177.28 | 291.05 | 0.00 | 0.00 | 0.00 |
May | 335.52 | 9.97 | 325.56 | 278.84 | 239.77 | 0.00 | 0.00 | 0.00 |
June | 352.79 | 23.30 | 329.50 | 320.74 | 186.82 | 0.00 | 0.00 | 0.00 |
July | 335.31 | 26.29 | 309.02 | 344.08 | 169.45 | 0.00 | 0.00 | 0.00 |
August | 271.44 | 7.34 | 264.10 | 283.48 | 166.66 | 0.00 | 0.00 | 0.00 |
September | 210.84 | 0.06 | 210.78 | 162.23 | 250.36 | 0.00 | 0.00 | 0.00 |
October | 144.46 | 0.00 | 144.46 | 63.78 | 338.86 | 0.00 | 0.00 | 0.00 |
November | 91.00 | 0.00 | 91.00 | 11.83 | 424.31 | 0.00 | 0.00 | 0.00 |
December | 68.30 | 0.00 | 68.30 | 1.13 | 519.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.41 | 5.70 | 199.71 | 146.95 | 324.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.30 | 0.00 | 68.30 | 1.13 | 166.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.79 | 26.29 | 329.50 | 344.08 | 519.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 248.48 | 63.00 | 185.48 | 87.93 | 922.88 | 0.00 | 0.00 | 0.00 |
February | 455.93 | 161.82 | 294.11 | 299.27 | 817.90 | 0.00 | 0.00 | 0.00 |
March | 680.74 | 246.43 | 434.31 | 574.09 | 680.09 | 0.00 | 0.00 | 0.00 |
April | 1055.27 | 438.48 | 616.79 | 1075.59 | 555.68 | 0.00 | 0.00 | 0.00 |
May | 1122.90 | 390.40 | 732.49 | 1199.89 | 474.06 | 0.00 | 0.00 | 0.00 |
June | 1344.80 | 585.13 | 759.67 | 1540.29 | 379.03 | 0.00 | 0.00 | 0.00 |
July | 1252.32 | 562.11 | 690.21 | 1499.69 | 334.83 | 0.00 | 0.00 | 0.00 |
August | 1230.85 | 615.74 | 615.11 | 1523.46 | 330.61 | 0.00 | 0.00 | 0.00 |
September | 910.03 | 419.71 | 490.32 | 998.31 | 473.51 | 0.00 | 0.00 | 0.00 |
October | 593.16 | 252.04 | 341.12 | 534.40 | 635.75 | 0.00 | 0.00 | 0.00 |
November | 290.73 | 82.08 | 208.66 | 151.01 | 784.89 | 0.00 | 0.00 | 0.00 |
December | 238.47 | 76.77 | 161.70 | 109.41 | 957.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 786.75 | 325.19 | 461.57 | 802.00 | 611.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 238.47 | 63.00 | 161.70 | 87.93 | 330.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1344.80 | 615.74 | 759.67 | 1540.29 | 957.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.82 | 2.49 | 7.33 | 3.48 | 36.49 | 0.00 | 0.00 | 0.00 |
February | 18.03 | 6.40 | 11.63 | 11.83 | 32.34 | 0.00 | 0.00 | 0.00 |
March | 26.92 | 9.74 | 17.17 | 22.70 | 26.89 | 0.00 | 0.00 | 0.00 |
April | 41.72 | 17.34 | 24.39 | 42.53 | 21.97 | 0.00 | 0.00 | 0.00 |
May | 44.40 | 15.44 | 28.96 | 47.44 | 18.74 | 0.00 | 0.00 | 0.00 |
June | 53.17 | 23.14 | 30.04 | 60.90 | 14.99 | 0.00 | 0.00 | 0.00 |
July | 49.52 | 22.23 | 27.29 | 59.30 | 13.24 | 0.00 | 0.00 | 0.00 |
August | 48.67 | 24.35 | 24.32 | 60.24 | 13.07 | 0.00 | 0.00 | 0.00 |
September | 35.98 | 16.60 | 19.39 | 39.47 | 18.72 | 0.00 | 0.00 | 0.00 |
October | 23.45 | 9.97 | 13.49 | 21.13 | 25.14 | 0.00 | 0.00 | 0.00 |
November | 11.50 | 3.25 | 8.25 | 5.97 | 31.03 | 0.00 | 0.00 | 0.00 |
December | 9.43 | 3.04 | 6.39 | 4.33 | 37.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.11 | 12.86 | 18.25 | 31.71 | 24.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.43 | 2.49 | 6.39 | 3.48 | 13.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.17 | 24.35 | 30.04 | 60.90 | 37.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.12 | 210.87 | 144.25 | 318.76 | 456.27 | 0.00 | 0.00 | 0.00 |
February | 546.12 | 338.05 | 208.06 | 559.54 | 421.87 | 0.00 | 0.00 | 0.00 |
March | 587.47 | 313.29 | 274.18 | 632.60 | 368.64 | 0.00 | 0.00 | 0.00 |
April | 620.25 | 269.31 | 350.94 | 707.69 | 311.23 | 0.00 | 0.00 | 0.00 |
May | 567.14 | 168.96 | 398.19 | 653.92 | 260.57 | 0.00 | 0.00 | 0.00 |
June | 518.88 | 139.31 | 379.57 | 610.19 | 207.47 | 0.00 | 0.00 | 0.00 |
July | 565.86 | 207.25 | 358.61 | 730.44 | 192.06 | 0.00 | 0.00 | 0.00 |
August | 607.95 | 283.49 | 324.45 | 809.99 | 188.29 | 0.00 | 0.00 | 0.00 |
September | 673.58 | 371.97 | 301.61 | 839.27 | 263.51 | 0.00 | 0.00 | 0.00 |
October | 610.15 | 376.72 | 233.43 | 693.34 | 343.30 | 0.00 | 0.00 | 0.00 |
November | 360.74 | 206.73 | 154.01 | 344.96 | 399.19 | 0.00 | 0.00 | 0.00 |
December | 377.44 | 244.25 | 133.18 | 370.74 | 480.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 532.33 | 260.37 | 271.96 | 606.12 | 323.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.12 | 139.31 | 133.18 | 318.76 | 188.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 673.58 | 376.72 | 398.19 | 839.27 | 480.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.12 | 210.87 | 144.25 | 318.76 | 456.27 | 0.00 | 0.00 | 0.00 |
February | 546.12 | 338.05 | 208.06 | 559.54 | 421.87 | 0.00 | 0.00 | 0.00 |
March | 587.47 | 313.29 | 274.18 | 632.60 | 368.64 | 0.00 | 0.00 | 0.00 |
April | 620.25 | 269.31 | 350.94 | 707.69 | 311.23 | 0.00 | 0.00 | 0.00 |
May | 567.14 | 168.96 | 398.19 | 653.92 | 260.57 | 0.00 | 0.00 | 0.00 |
June | 518.88 | 139.31 | 379.57 | 610.19 | 207.47 | 0.00 | 0.00 | 0.00 |
July | 565.86 | 207.25 | 358.61 | 730.44 | 192.06 | 0.00 | 0.00 | 0.00 |
August | 607.95 | 283.49 | 324.45 | 809.99 | 188.29 | 0.00 | 0.00 | 0.00 |
September | 673.58 | 371.97 | 301.61 | 839.27 | 263.51 | 0.00 | 0.00 | 0.00 |
October | 610.15 | 376.72 | 233.43 | 693.34 | 343.30 | 0.00 | 0.00 | 0.00 |
November | 360.74 | 206.73 | 154.01 | 344.96 | 399.19 | 0.00 | 0.00 | 0.00 |
December | 377.44 | 244.25 | 133.18 | 370.74 | 480.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 532.33 | 260.37 | 271.96 | 606.12 | 323.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.12 | 139.31 | 133.18 | 318.76 | 188.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 673.58 | 376.72 | 398.19 | 839.27 | 480.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.10 | 210.86 | 144.24 | 318.74 | 456.24 | 0.00 | 0.00 | 0.00 |
February | 546.08 | 338.03 | 208.05 | 559.51 | 421.85 | 0.00 | 0.00 | 0.00 |
March | 587.43 | 313.27 | 274.16 | 632.56 | 368.62 | 0.00 | 0.00 | 0.00 |
April | 620.21 | 269.29 | 350.92 | 707.65 | 311.21 | 0.00 | 0.00 | 0.00 |
May | 567.11 | 168.95 | 398.16 | 653.88 | 260.55 | 0.00 | 0.00 | 0.00 |
June | 518.85 | 139.30 | 379.55 | 610.15 | 207.46 | 0.00 | 0.00 | 0.00 |
July | 565.83 | 207.23 | 358.59 | 730.40 | 192.04 | 0.00 | 0.00 | 0.00 |
August | 607.91 | 283.48 | 324.43 | 809.94 | 188.27 | 0.00 | 0.00 | 0.00 |
September | 673.54 | 371.95 | 301.59 | 839.22 | 263.50 | 0.00 | 0.00 | 0.00 |
October | 610.11 | 376.70 | 233.41 | 693.30 | 343.28 | 0.00 | 0.00 | 0.00 |
November | 360.72 | 206.72 | 154.00 | 344.93 | 399.17 | 0.00 | 0.00 | 0.00 |
December | 377.41 | 244.24 | 133.17 | 370.71 | 480.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 532.29 | 260.35 | 271.94 | 606.08 | 323.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.10 | 139.30 | 133.17 | 318.74 | 188.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 673.54 | 376.70 | 398.16 | 839.22 | 480.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.08 | 77.28 | 184.80 | 113.57 | 931.42 | 0.00 | 0.00 | 0.00 |
February | 469.90 | 176.60 | 293.30 | 336.46 | 832.02 | 0.00 | 0.00 | 0.00 |
March | 658.45 | 222.24 | 436.20 | 564.66 | 696.44 | 0.00 | 0.00 | 0.00 |
April | 1001.76 | 383.01 | 618.75 | 1026.73 | 581.44 | 0.00 | 0.00 | 0.00 |
May | 1289.03 | 523.66 | 765.37 | 1433.63 | 503.33 | 0.00 | 0.00 | 0.00 |
June | 1239.69 | 481.33 | 758.36 | 1408.26 | 399.01 | 0.00 | 0.00 | 0.00 |
July | 1531.47 | 805.02 | 726.45 | 1902.19 | 375.47 | 0.00 | 0.00 | 0.00 |
August | 1266.89 | 646.91 | 619.98 | 1597.81 | 364.26 | 0.00 | 0.00 | 0.00 |
September | 1031.69 | 495.03 | 536.66 | 1192.81 | 505.20 | 0.00 | 0.00 | 0.00 |
October | 587.34 | 239.31 | 348.03 | 542.31 | 653.24 | 0.00 | 0.00 | 0.00 |
November | 292.49 | 82.50 | 210.00 | 161.32 | 788.48 | 0.00 | 0.00 | 0.00 |
December | 245.90 | 84.26 | 161.63 | 133.67 | 968.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 825.21 | 352.77 | 472.44 | 871.28 | 632.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.90 | 77.28 | 161.63 | 113.57 | 364.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1531.47 | 805.02 | 765.37 | 1902.19 | 968.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.36 | 3.06 | 7.31 | 4.49 | 36.83 | 0.00 | 0.00 | 0.00 |
February | 18.58 | 6.98 | 11.60 | 13.30 | 32.90 | 0.00 | 0.00 | 0.00 |
March | 26.03 | 8.79 | 17.25 | 22.33 | 27.54 | 0.00 | 0.00 | 0.00 |
April | 39.61 | 15.14 | 24.46 | 40.60 | 22.99 | 0.00 | 0.00 | 0.00 |
May | 50.97 | 20.70 | 30.26 | 56.68 | 19.90 | 0.00 | 0.00 | 0.00 |
June | 49.02 | 19.03 | 29.98 | 55.68 | 15.78 | 0.00 | 0.00 | 0.00 |
July | 60.55 | 31.83 | 28.72 | 75.21 | 14.85 | 0.00 | 0.00 | 0.00 |
August | 50.09 | 25.58 | 24.51 | 63.18 | 14.40 | 0.00 | 0.00 | 0.00 |
September | 40.79 | 19.57 | 21.22 | 47.16 | 19.98 | 0.00 | 0.00 | 0.00 |
October | 23.22 | 9.46 | 13.76 | 21.44 | 25.83 | 0.00 | 0.00 | 0.00 |
November | 11.56 | 3.26 | 8.30 | 6.38 | 31.18 | 0.00 | 0.00 | 0.00 |
December | 9.72 | 3.33 | 6.39 | 5.29 | 38.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.63 | 13.95 | 18.68 | 34.45 | 25.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.72 | 3.06 | 6.39 | 4.49 | 14.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.55 | 31.83 | 30.26 | 75.21 | 38.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 241.13 | 0.00 | 241.13 | 7.56 | 1533.63 | 0.00 | 0.00 | 0.00 |
February | 375.20 | 0.00 | 375.20 | 70.34 | 1374.65 | 0.00 | 0.00 | 0.00 |
March | 552.80 | 0.00 | 552.80 | 223.26 | 1140.03 | 0.00 | 0.00 | 0.00 |
April | 782.27 | 2.77 | 779.49 | 495.13 | 919.66 | 0.00 | 0.00 | 0.00 |
May | 1006.58 | 29.90 | 976.68 | 801.62 | 748.53 | 0.00 | 0.00 | 0.00 |
June | 1058.39 | 69.89 | 988.50 | 934.38 | 578.88 | 0.00 | 0.00 | 0.00 |
July | 1005.94 | 78.87 | 927.07 | 1011.84 | 522.18 | 0.00 | 0.00 | 0.00 |
August | 814.32 | 22.01 | 792.31 | 834.50 | 512.01 | 0.00 | 0.00 | 0.00 |
September | 632.53 | 0.19 | 632.35 | 473.81 | 761.93 | 0.00 | 0.00 | 0.00 |
October | 433.39 | 0.00 | 433.39 | 185.33 | 1017.52 | 0.00 | 0.00 | 0.00 |
November | 272.99 | 0.00 | 272.99 | 34.63 | 1260.20 | 0.00 | 0.00 | 0.00 |
December | 204.90 | 0.00 | 204.90 | 3.15 | 1556.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 616.22 | 17.10 | 599.13 | 425.19 | 991.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.90 | 0.00 | 204.90 | 3.15 | 512.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1058.39 | 78.87 | 988.50 | 1011.84 | 1556.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 258.31 | 65.49 | 192.82 | 88.80 | 968.75 | 0.00 | 0.00 | 0.00 |
February | 473.97 | 168.22 | 305.75 | 302.85 | 860.23 | 0.00 | 0.00 | 0.00 |
March | 707.67 | 256.18 | 451.49 | 581.86 | 720.03 | 0.00 | 0.00 | 0.00 |
April | 1097.01 | 455.82 | 641.18 | 1100.46 | 584.35 | 0.00 | 0.00 | 0.00 |
May | 1167.31 | 405.85 | 761.46 | 1231.28 | 496.79 | 0.00 | 0.00 | 0.00 |
June | 1397.99 | 608.28 | 789.71 | 1589.00 | 391.02 | 0.00 | 0.00 | 0.00 |
July | 1301.85 | 584.35 | 717.51 | 1548.92 | 345.94 | 0.00 | 0.00 | 0.00 |
August | 1279.54 | 640.10 | 639.44 | 1576.38 | 337.79 | 0.00 | 0.00 | 0.00 |
September | 946.03 | 436.32 | 509.71 | 1033.00 | 483.08 | 0.00 | 0.00 | 0.00 |
October | 616.62 | 262.01 | 354.62 | 553.49 | 644.89 | 0.00 | 0.00 | 0.00 |
November | 302.23 | 85.32 | 216.91 | 156.50 | 802.55 | 0.00 | 0.00 | 0.00 |
December | 247.90 | 79.81 | 168.09 | 112.46 | 991.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 817.87 | 338.05 | 479.82 | 825.58 | 634.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.90 | 65.49 | 168.09 | 88.80 | 337.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1397.99 | 640.10 | 789.71 | 1589.00 | 991.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1065.37 | 632.62 | 432.75 | 934.10 | 1387.93 | 0.00 | 0.00 | 0.00 |
February | 1638.38 | 1014.18 | 624.20 | 1646.21 | 1271.53 | 0.00 | 0.00 | 0.00 |
March | 1762.43 | 939.88 | 822.54 | 1856.76 | 1122.45 | 0.00 | 0.00 | 0.00 |
April | 1860.79 | 807.94 | 1052.84 | 2076.40 | 958.09 | 0.00 | 0.00 | 0.00 |
May | 1701.45 | 506.88 | 1194.57 | 1916.65 | 805.12 | 0.00 | 0.00 | 0.00 |
June | 1556.66 | 417.94 | 1138.72 | 1792.35 | 639.34 | 0.00 | 0.00 | 0.00 |
July | 1697.61 | 621.75 | 1075.85 | 2166.39 | 579.74 | 0.00 | 0.00 | 0.00 |
August | 1823.86 | 850.50 | 973.37 | 2410.21 | 560.04 | 0.00 | 0.00 | 0.00 |
September | 2020.77 | 1115.93 | 904.83 | 2500.45 | 772.85 | 0.00 | 0.00 | 0.00 |
October | 1830.47 | 1130.18 | 700.29 | 2062.64 | 999.96 | 0.00 | 0.00 | 0.00 |
November | 1082.24 | 620.21 | 462.02 | 1019.41 | 1185.48 | 0.00 | 0.00 | 0.00 |
December | 1132.33 | 732.78 | 399.55 | 1096.71 | 1443.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1597.01 | 781.12 | 815.88 | 1790.41 | 975.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1065.37 | 417.94 | 399.55 | 934.10 | 560.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2020.77 | 1130.18 | 1194.57 | 2500.45 | 1443.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 272.45 | 80.34 | 192.11 | 114.26 | 976.69 | 0.00 | 0.00 | 0.00 |
February | 488.48 | 183.59 | 304.90 | 339.84 | 875.00 | 0.00 | 0.00 | 0.00 |
March | 684.49 | 231.03 | 453.46 | 569.95 | 739.75 | 0.00 | 0.00 | 0.00 |
April | 1041.38 | 398.16 | 643.22 | 1044.90 | 618.11 | 0.00 | 0.00 | 0.00 |
May | 1340.01 | 544.37 | 795.64 | 1471.56 | 525.69 | 0.00 | 0.00 | 0.00 |
June | 1288.72 | 500.37 | 788.35 | 1448.56 | 416.02 | 0.00 | 0.00 | 0.00 |
July | 1592.04 | 836.86 | 755.18 | 1967.26 | 383.12 | 0.00 | 0.00 | 0.00 |
August | 1317.00 | 672.50 | 644.50 | 1652.50 | 371.96 | 0.00 | 0.00 | 0.00 |
September | 1072.50 | 514.61 | 557.89 | 1234.71 | 513.95 | 0.00 | 0.00 | 0.00 |
October | 610.58 | 248.78 | 361.79 | 560.23 | 666.81 | 0.00 | 0.00 | 0.00 |
November | 304.06 | 85.76 | 218.30 | 166.07 | 808.11 | 0.00 | 0.00 | 0.00 |
December | 255.62 | 87.60 | 168.03 | 136.78 | 1002.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 857.85 | 366.72 | 491.13 | 895.87 | 657.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.62 | 80.34 | 168.03 | 114.26 | 371.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1592.04 | 836.86 | 795.64 | 1967.26 | 1002.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645835E+09 | 0.00 | 0.645835E+09 | 27070362.68 | 0.387492E+10 |
February | 0.907684E+09 | 0.00 | 0.907684E+09 | 0.193077E+09 | 0.310566E+10 |
March | 0.148061E+10 | 0.00 | 0.148061E+10 | 0.645165E+09 | 0.284080E+10 |
April | 0.202763E+10 | 7192628.59 | 0.202044E+10 | 0.133047E+10 | 0.223623E+10 |
May | 0.269602E+10 | 80094863.53 | 0.261593E+10 | 0.218654E+10 | 0.189925E+10 |
June | 0.274335E+10 | 0.181160E+09 | 0.256219E+10 | 0.244436E+10 | 0.143475E+10 |
July | 0.269432E+10 | 0.211248E+09 | 0.248307E+10 | 0.272418E+10 | 0.134128E+10 |
August | 0.218107E+10 | 58960942.61 | 0.212211E+10 | 0.225200E+10 | 0.130864E+10 |
September | 0.163953E+10 | 483472.07 | 0.163904E+10 | 0.126392E+10 | 0.184768E+10 |
October | 0.116079E+10 | 0.00 | 0.116079E+10 | 0.548340E+09 | 0.250177E+10 |
November | 0.707600E+09 | 0.00 | 0.707600E+09 | 0.112020E+09 | 0.300659E+10 |
December | 0.548793E+09 | 0.00 | 0.548793E+09 | 14636872.07 | 0.388876E+10 |
Annual Sum or Average | 0.194333E+11 | 0.539139E+09 | 0.188941E+11 | 0.137418E+11 | 0.292863E+11 |
Minimum of Months | 0.548793E+09 | 0.00 | 0.548793E+09 | 14636872.07 | 0.130864E+10 |
Maximum of Months | 0.274335E+10 | 0.211248E+09 | 0.261593E+10 | 0.272418E+10 | 0.388876E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691850E+09 | 0.175407E+09 | 0.516443E+09 | 0.251376E+09 | 0.245090E+10 |
February | 0.114662E+10 | 0.406961E+09 | 0.739663E+09 | 0.761209E+09 | 0.195232E+10 |
March | 0.189542E+10 | 0.686158E+09 | 0.120926E+10 | 0.159209E+10 | 0.180725E+10 |
April | 0.284344E+10 | 0.118149E+10 | 0.166195E+10 | 0.288131E+10 | 0.143346E+10 |
May | 0.312653E+10 | 0.108702E+10 | 0.203951E+10 | 0.331777E+10 | 0.126855E+10 |
June | 0.362359E+10 | 0.157665E+10 | 0.204694E+10 | 0.412600E+10 | 0.973736E+09 |
July | 0.348688E+10 | 0.156511E+10 | 0.192177E+10 | 0.415446E+10 | 0.893635E+09 |
August | 0.342712E+10 | 0.171444E+10 | 0.171268E+10 | 0.422841E+10 | 0.869212E+09 |
September | 0.245211E+10 | 0.113094E+10 | 0.132118E+10 | 0.269886E+10 | 0.118097E+10 |
October | 0.165156E+10 | 0.701758E+09 | 0.949803E+09 | 0.151802E+10 | 0.160293E+10 |
November | 0.783391E+09 | 0.221159E+09 | 0.562232E+09 | 0.428976E+09 | 0.192731E+10 |
December | 0.663975E+09 | 0.213753E+09 | 0.450222E+09 | 0.317530E+09 | 0.248501E+10 |
Annual Sum or Average | 0.257925E+11 | 0.106609E+11 | 0.151316E+11 | 0.262760E+11 | 0.188453E+11 |
Minimum of Months | 0.663975E+09 | 0.175407E+09 | 0.450222E+09 | 0.251376E+09 | 0.869212E+09 |
Maximum of Months | 0.362359E+10 | 0.171444E+10 | 0.204694E+10 | 0.422841E+10 | 0.248501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285350E+10 | 0.169442E+10 | 0.115908E+10 | 0.254274E+10 | 0.350767E+10 |
February | 0.396357E+10 | 0.245351E+10 | 0.151007E+10 | 0.403261E+10 | 0.288553E+10 |
March | 0.472048E+10 | 0.251738E+10 | 0.220310E+10 | 0.501692E+10 | 0.280942E+10 |
April | 0.482316E+10 | 0.209419E+10 | 0.272897E+10 | 0.541803E+10 | 0.234256E+10 |
May | 0.455717E+10 | 0.135763E+10 | 0.319954E+10 | 0.515855E+10 | 0.204381E+10 |
June | 0.403487E+10 | 0.108331E+10 | 0.295156E+10 | 0.465709E+10 | 0.157978E+10 |
July | 0.454687E+10 | 0.166531E+10 | 0.288156E+10 | 0.580738E+10 | 0.148712E+10 |
August | 0.488504E+10 | 0.227798E+10 | 0.260706E+10 | 0.646150E+10 | 0.143155E+10 |
September | 0.523783E+10 | 0.289250E+10 | 0.234533E+10 | 0.651092E+10 | 0.188470E+10 |
October | 0.490274E+10 | 0.302708E+10 | 0.187566E+10 | 0.557442E+10 | 0.248181E+10 |
November | 0.280516E+10 | 0.160759E+10 | 0.119757E+10 | 0.269347E+10 | 0.284580E+10 |
December | 0.303283E+10 | 0.196266E+10 | 0.107017E+10 | 0.297963E+10 | 0.361831E+10 |
Annual Sum or Average | 0.503632E+11 | 0.246336E+11 | 0.257297E+11 | 0.568532E+11 | 0.289181E+11 |
Minimum of Months | 0.280516E+10 | 0.108331E+10 | 0.107017E+10 | 0.254274E+10 | 0.143155E+10 |
Maximum of Months | 0.523783E+10 | 0.302708E+10 | 0.319954E+10 | 0.651092E+10 | 0.361831E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.729733E+09 | 0.215185E+09 | 0.514548E+09 | 0.316152E+09 | 0.246986E+10 |
February | 0.118174E+10 | 0.444131E+09 | 0.737608E+09 | 0.842820E+09 | 0.198247E+10 |
March | 0.183334E+10 | 0.618801E+09 | 0.121454E+10 | 0.155496E+10 | 0.185131E+10 |
April | 0.269925E+10 | 0.103203E+10 | 0.166722E+10 | 0.273530E+10 | 0.150887E+10 |
May | 0.358909E+10 | 0.145805E+10 | 0.213103E+10 | 0.396116E+10 | 0.133394E+10 |
June | 0.334037E+10 | 0.129696E+10 | 0.204342E+10 | 0.376435E+10 | 0.102754E+10 |
July | 0.426413E+10 | 0.224144E+10 | 0.202268E+10 | 0.527253E+10 | 0.983390E+09 |
August | 0.352745E+10 | 0.180122E+10 | 0.172623E+10 | 0.443322E+10 | 0.950678E+09 |
September | 0.277991E+10 | 0.133386E+10 | 0.144605E+10 | 0.322311E+10 | 0.125085E+10 |
October | 0.163536E+10 | 0.666333E+09 | 0.969031E+09 | 0.153312E+10 | 0.165011E+10 |
November | 0.788130E+09 | 0.222286E+09 | 0.565845E+09 | 0.450397E+09 | 0.193804E+10 |
December | 0.684662E+09 | 0.234616E+09 | 0.450046E+09 | 0.377258E+09 | 0.251085E+10 |
Annual Sum or Average | 0.270532E+11 | 0.115649E+11 | 0.154883E+11 | 0.284644E+11 | 0.194579E+11 |
Minimum of Months | 0.684662E+09 | 0.215185E+09 | 0.450046E+09 | 0.316152E+09 | 0.950678E+09 |
Maximum of Months | 0.426413E+10 | 0.224144E+10 | 0.213103E+10 | 0.527253E+10 | 0.251085E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215268E+09 | 0.00 | 0.215268E+09 | 7783626.78 | 0.135492E+10 |
February | 0.302547E+09 | 0.00 | 0.302547E+09 | 62744963.38 | 0.108554E+10 |
March | 0.493515E+09 | 0.00 | 0.493515E+09 | 0.220030E+09 | 0.977003E+09 |
April | 0.675845E+09 | 2397429.43 | 0.673448E+09 | 0.459496E+09 | 0.754357E+09 |
May | 0.898631E+09 | 26697024.69 | 0.871934E+09 | 0.746814E+09 | 0.642159E+09 |
June | 0.914408E+09 | 60383693.28 | 0.854025E+09 | 0.831331E+09 | 0.484204E+09 |
July | 0.898065E+09 | 70412523.88 | 0.827652E+09 | 0.921557E+09 | 0.453825E+09 |
August | 0.726990E+09 | 19652717.68 | 0.707337E+09 | 0.759238E+09 | 0.446356E+09 |
September | 0.546484E+09 | 161149.73 | 0.546322E+09 | 0.420490E+09 | 0.648897E+09 |
October | 0.386913E+09 | 0.00 | 0.386913E+09 | 0.170833E+09 | 0.907545E+09 |
November | 0.235856E+09 | 0.00 | 0.235856E+09 | 30661636.03 | 0.109973E+10 |
December | 0.182922E+09 | 0.00 | 0.182922E+09 | 3026622.52 | 0.139132E+10 |
Annual Sum or Average | 0.647744E+10 | 0.179705E+09 | 0.629774E+10 | 0.463401E+10 | 0.102459E+11 |
Minimum of Months | 0.182922E+09 | 0.00 | 0.182922E+09 | 3026622.52 | 0.446356E+09 |
Maximum of Months | 0.914408E+09 | 70412523.88 | 0.871934E+09 | 0.921557E+09 | 0.139132E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215276E+09 | 0.00 | 0.215276E+09 | 7782774.49 | 0.135501E+10 |
February | 0.302558E+09 | 0.00 | 0.302558E+09 | 62743794.45 | 0.108561E+10 |
March | 0.493534E+09 | 0.00 | 0.493534E+09 | 0.220032E+09 | 0.977065E+09 |
April | 0.675872E+09 | 2397493.88 | 0.673474E+09 | 0.459507E+09 | 0.754404E+09 |
May | 0.898666E+09 | 26697742.32 | 0.871968E+09 | 0.746834E+09 | 0.642198E+09 |
June | 0.914444E+09 | 60385316.41 | 0.854059E+09 | 0.831356E+09 | 0.484233E+09 |
July | 0.898101E+09 | 70414416.59 | 0.827687E+09 | 0.921590E+09 | 0.453852E+09 |
August | 0.727019E+09 | 19653245.95 | 0.707366E+09 | 0.759267E+09 | 0.446382E+09 |
September | 0.546505E+09 | 161154.06 | 0.546344E+09 | 0.420502E+09 | 0.648935E+09 |
October | 0.386928E+09 | 0.00 | 0.386928E+09 | 0.170835E+09 | 0.907601E+09 |
November | 0.235864E+09 | 0.00 | 0.235864E+09 | 30660546.47 | 0.109980E+10 |
December | 0.182929E+09 | 0.00 | 0.182929E+09 | 3026244.37 | 0.139141E+10 |
Annual Sum or Average | 0.647770E+10 | 0.179709E+09 | 0.629799E+10 | 0.463414E+10 | 0.102465E+11 |
Minimum of Months | 0.182929E+09 | 0.00 | 0.182929E+09 | 3026244.37 | 0.446382E+09 |
Maximum of Months | 0.914444E+09 | 70414416.59 | 0.871968E+09 | 0.921590E+09 | 0.139141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215276E+09 | 0.00 | 0.215276E+09 | 7782774.49 | 0.135501E+10 |
February | 0.302558E+09 | 0.00 | 0.302558E+09 | 62743794.45 | 0.108561E+10 |
March | 0.493534E+09 | 0.00 | 0.493534E+09 | 0.220032E+09 | 0.977065E+09 |
April | 0.675872E+09 | 2397493.88 | 0.673474E+09 | 0.459507E+09 | 0.754404E+09 |
May | 0.898666E+09 | 26697742.32 | 0.871968E+09 | 0.746834E+09 | 0.642198E+09 |
June | 0.914444E+09 | 60385316.41 | 0.854059E+09 | 0.831356E+09 | 0.484233E+09 |
July | 0.898101E+09 | 70414416.59 | 0.827687E+09 | 0.921590E+09 | 0.453852E+09 |
August | 0.727019E+09 | 19653245.95 | 0.707366E+09 | 0.759267E+09 | 0.446382E+09 |
September | 0.546505E+09 | 161154.06 | 0.546344E+09 | 0.420502E+09 | 0.648935E+09 |
October | 0.386928E+09 | 0.00 | 0.386928E+09 | 0.170835E+09 | 0.907601E+09 |
November | 0.235864E+09 | 0.00 | 0.235864E+09 | 30660546.47 | 0.109980E+10 |
December | 0.182929E+09 | 0.00 | 0.182929E+09 | 3026244.37 | 0.139141E+10 |
Annual Sum or Average | 0.647770E+10 | 0.179709E+09 | 0.629799E+10 | 0.463414E+10 | 0.102465E+11 |
Minimum of Months | 0.182929E+09 | 0.00 | 0.182929E+09 | 3026244.37 | 0.446382E+09 |
Maximum of Months | 0.914444E+09 | 70414416.59 | 0.871968E+09 | 0.921590E+09 | 0.139141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.665525E+09 | 0.168732E+09 | 0.496793E+09 | 0.235499E+09 | 0.247184E+10 |
February | 0.110299E+10 | 0.391475E+09 | 0.711520E+09 | 0.724001E+09 | 0.197867E+10 |
March | 0.182330E+10 | 0.660047E+09 | 0.116325E+10 | 0.153766E+10 | 0.182154E+10 |
April | 0.273525E+10 | 0.113653E+10 | 0.159872E+10 | 0.278793E+10 | 0.144033E+10 |
May | 0.300757E+10 | 0.104566E+10 | 0.196191E+10 | 0.321377E+10 | 0.126971E+10 |
June | 0.348571E+10 | 0.151665E+10 | 0.196906E+10 | 0.399244E+10 | 0.982457E+09 |
July | 0.335421E+10 | 0.150555E+10 | 0.184865E+10 | 0.401676E+10 | 0.896805E+09 |
August | 0.329671E+10 | 0.164920E+10 | 0.164752E+10 | 0.408043E+10 | 0.885506E+09 |
September | 0.235881E+10 | 0.108790E+10 | 0.127091E+10 | 0.258763E+10 | 0.122733E+10 |
October | 0.158872E+10 | 0.675053E+09 | 0.913664E+09 | 0.143133E+10 | 0.170280E+10 |
November | 0.753582E+09 | 0.212743E+09 | 0.540839E+09 | 0.391413E+09 | 0.203445E+10 |
December | 0.638710E+09 | 0.205619E+09 | 0.433091E+09 | 0.293053E+09 | 0.256347E+10 |
Annual Sum or Average | 0.248111E+11 | 0.102552E+11 | 0.145559E+11 | 0.252919E+11 | 0.192749E+11 |
Minimum of Months | 0.638710E+09 | 0.168732E+09 | 0.433091E+09 | 0.235499E+09 | 0.885506E+09 |
Maximum of Months | 0.348571E+10 | 0.164920E+10 | 0.196906E+10 | 0.408043E+10 | 0.256347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26314251.24 | 6671511.59 | 19642739.65 | 9311405.44 | 97734475.80 |
February | 43611429.05 | 15478560.31 | 28132868.74 | 28626346.90 | 78234724.96 |
March | 72091522.60 | 26097647.10 | 45993875.50 | 60797525.43 | 72022182.83 |
April | 0.108149E+09 | 44937423.00 | 63211821.09 | 0.110232E+09 | 56949447.92 |
May | 0.118917E+09 | 41344367.65 | 77572145.90 | 0.127070E+09 | 50203166.19 |
June | 0.137822E+09 | 59967020.72 | 77854822.95 | 0.157857E+09 | 38845472.67 |
July | 0.132622E+09 | 59528271.20 | 73094072.13 | 0.158819E+09 | 35458876.64 |
August | 0.130349E+09 | 65207857.07 | 65141280.00 | 0.161337E+09 | 35012110.13 |
September | 93265234.25 | 43014572.25 | 50250661.99 | 0.102313E+09 | 48527395.11 |
October | 62816474.46 | 26691003.25 | 36125471.21 | 56593592.61 | 67327317.05 |
November | 29795965.36 | 8411666.13 | 21384299.23 | 15476101.18 | 80440148.47 |
December | 25254026.77 | 8129989.92 | 17124036.85 | 11587045.71 | 0.101357E+09 |
Annual Sum or Average | 0.981008E+09 | 0.405480E+09 | 0.575528E+09 | 0.100002E+10 | 0.762113E+09 |
Minimum of Months | 25254026.77 | 6671511.59 | 17124036.85 | 9311405.44 | 35012110.13 |
Maximum of Months | 0.137822E+09 | 65207857.07 | 77854822.95 | 0.161337E+09 | 0.101357E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.951149E+09 | 0.564795E+09 | 0.386353E+09 | 0.853758E+09 | 0.122208E+10 |
February | 0.132117E+10 | 0.817818E+09 | 0.503349E+09 | 0.135365E+10 | 0.102060E+10 |
March | 0.157347E+10 | 0.839110E+09 | 0.734357E+09 | 0.169435E+10 | 0.987373E+09 |
April | 0.160770E+10 | 0.698049E+09 | 0.909646E+09 | 0.183433E+10 | 0.806716E+09 |
May | 0.151903E+10 | 0.452533E+09 | 0.106650E+10 | 0.175146E+10 | 0.697901E+09 |
June | 0.134494E+10 | 0.361096E+09 | 0.983843E+09 | 0.158162E+10 | 0.537763E+09 |
July | 0.151560E+10 | 0.555091E+09 | 0.960514E+09 | 0.195641E+10 | 0.514405E+09 |
August | 0.162832E+10 | 0.759310E+09 | 0.869014E+09 | 0.216947E+10 | 0.504305E+09 |
September | 0.174591E+10 | 0.964148E+09 | 0.781767E+09 | 0.217540E+10 | 0.683029E+09 |
October | 0.163422E+10 | 0.100901E+10 | 0.625212E+09 | 0.185705E+10 | 0.919493E+09 |
November | 0.935036E+09 | 0.535853E+09 | 0.399183E+09 | 0.894125E+09 | 0.103470E+10 |
December | 0.101092E+10 | 0.654208E+09 | 0.356716E+09 | 0.992977E+09 | 0.128669E+10 |
Annual Sum or Average | 0.167875E+11 | 0.821102E+10 | 0.857646E+10 | 0.191146E+11 | 0.102151E+11 |
Minimum of Months | 0.935036E+09 | 0.361096E+09 | 0.356716E+09 | 0.853758E+09 | 0.504305E+09 |
Maximum of Months | 0.174591E+10 | 0.100901E+10 | 0.106650E+10 | 0.217540E+10 | 0.128669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.951149E+09 | 0.564795E+09 | 0.386353E+09 | 0.853758E+09 | 0.122208E+10 |
February | 0.132117E+10 | 0.817818E+09 | 0.503349E+09 | 0.135365E+10 | 0.102060E+10 |
March | 0.157347E+10 | 0.839110E+09 | 0.734357E+09 | 0.169435E+10 | 0.987373E+09 |
April | 0.160770E+10 | 0.698049E+09 | 0.909646E+09 | 0.183433E+10 | 0.806716E+09 |
May | 0.151903E+10 | 0.452533E+09 | 0.106650E+10 | 0.175146E+10 | 0.697901E+09 |
June | 0.134494E+10 | 0.361096E+09 | 0.983843E+09 | 0.158162E+10 | 0.537763E+09 |
July | 0.151560E+10 | 0.555091E+09 | 0.960514E+09 | 0.195641E+10 | 0.514405E+09 |
August | 0.162832E+10 | 0.759310E+09 | 0.869014E+09 | 0.216947E+10 | 0.504305E+09 |
September | 0.174591E+10 | 0.964148E+09 | 0.781767E+09 | 0.217540E+10 | 0.683029E+09 |
October | 0.163422E+10 | 0.100901E+10 | 0.625212E+09 | 0.185705E+10 | 0.919493E+09 |
November | 0.935036E+09 | 0.535853E+09 | 0.399183E+09 | 0.894125E+09 | 0.103470E+10 |
December | 0.101092E+10 | 0.654208E+09 | 0.356716E+09 | 0.992977E+09 | 0.128669E+10 |
Annual Sum or Average | 0.167875E+11 | 0.821102E+10 | 0.857646E+10 | 0.191146E+11 | 0.102151E+11 |
Minimum of Months | 0.935036E+09 | 0.361096E+09 | 0.356716E+09 | 0.853758E+09 | 0.504305E+09 |
Maximum of Months | 0.174591E+10 | 0.100901E+10 | 0.106650E+10 | 0.217540E+10 | 0.128669E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.951088E+09 | 0.564759E+09 | 0.386329E+09 | 0.853704E+09 | 0.122200E+10 |
February | 0.132108E+10 | 0.817767E+09 | 0.503317E+09 | 0.135357E+10 | 0.102053E+10 |
March | 0.157337E+10 | 0.839057E+09 | 0.734311E+09 | 0.169424E+10 | 0.987311E+09 |
April | 0.160759E+10 | 0.698005E+09 | 0.909589E+09 | 0.183422E+10 | 0.806665E+09 |
May | 0.151894E+10 | 0.452504E+09 | 0.106643E+10 | 0.175135E+10 | 0.697857E+09 |
June | 0.134485E+10 | 0.361073E+09 | 0.983781E+09 | 0.158152E+10 | 0.537729E+09 |
July | 0.151551E+10 | 0.555056E+09 | 0.960453E+09 | 0.195629E+10 | 0.514372E+09 |
August | 0.162822E+10 | 0.759262E+09 | 0.868959E+09 | 0.216934E+10 | 0.504273E+09 |
September | 0.174580E+10 | 0.964087E+09 | 0.781717E+09 | 0.217526E+10 | 0.682986E+09 |
October | 0.163411E+10 | 0.100894E+10 | 0.625172E+09 | 0.185693E+10 | 0.919435E+09 |
November | 0.934976E+09 | 0.535819E+09 | 0.399157E+09 | 0.894068E+09 | 0.103464E+10 |
December | 0.101086E+10 | 0.654167E+09 | 0.356694E+09 | 0.992914E+09 | 0.128661E+10 |
Annual Sum or Average | 0.167864E+11 | 0.821050E+10 | 0.857591E+10 | 0.191134E+11 | 0.102144E+11 |
Minimum of Months | 0.934976E+09 | 0.361073E+09 | 0.356694E+09 | 0.853704E+09 | 0.504273E+09 |
Maximum of Months | 0.174580E+10 | 0.100894E+10 | 0.106643E+10 | 0.217526E+10 | 0.128661E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.701968E+09 | 0.206997E+09 | 0.494971E+09 | 0.304178E+09 | 0.249472E+10 |
February | 0.113678E+10 | 0.427231E+09 | 0.709545E+09 | 0.813968E+09 | 0.201282E+10 |
March | 0.176358E+10 | 0.595255E+09 | 0.116833E+10 | 0.151238E+10 | 0.186534E+10 |
April | 0.259655E+10 | 0.992758E+09 | 0.160379E+10 | 0.266129E+10 | 0.150709E+10 |
May | 0.345253E+10 | 0.140257E+10 | 0.204996E+10 | 0.383982E+10 | 0.134813E+10 |
June | 0.321328E+10 | 0.124761E+10 | 0.196567E+10 | 0.365022E+10 | 0.103424E+10 |
July | 0.410189E+10 | 0.215615E+10 | 0.194573E+10 | 0.509482E+10 | 0.100567E+10 |
August | 0.339324E+10 | 0.173268E+10 | 0.166056E+10 | 0.427957E+10 | 0.975632E+09 |
September | 0.267414E+10 | 0.128311E+10 | 0.139103E+10 | 0.309176E+10 | 0.130949E+10 |
October | 0.157314E+10 | 0.640978E+09 | 0.932164E+09 | 0.145252E+10 | 0.174964E+10 |
November | 0.758144E+09 | 0.213827E+09 | 0.544316E+09 | 0.418138E+09 | 0.204374E+10 |
December | 0.658612E+09 | 0.225689E+09 | 0.432923E+09 | 0.358019E+09 | 0.259358E+10 |
Annual Sum or Average | 0.260239E+11 | 0.111249E+11 | 0.148990E+11 | 0.274767E+11 | 0.199401E+11 |
Minimum of Months | 0.658612E+09 | 0.206997E+09 | 0.432923E+09 | 0.304178E+09 | 0.975632E+09 |
Maximum of Months | 0.410189E+10 | 0.215615E+10 | 0.204996E+10 | 0.509482E+10 | 0.259358E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27755118.08 | 8184449.75 | 19570668.33 | 12026839.60 | 98638815.59 |
February | 44946994.89 | 16892286.15 | 28054708.74 | 32183411.58 | 79585062.26 |
March | 69730341.87 | 23535763.83 | 46194578.04 | 59798064.31 | 73753953.40 |
April | 0.102665E+09 | 39252638.59 | 63412414.49 | 0.105225E+09 | 59589110.20 |
May | 0.136510E+09 | 55456227.52 | 81053341.15 | 0.151823E+09 | 53303742.54 |
June | 0.127050E+09 | 49329020.13 | 77720816.20 | 0.144326E+09 | 40892730.98 |
July | 0.162184E+09 | 85252100.53 | 76932317.02 | 0.201444E+09 | 39763311.79 |
August | 0.134165E+09 | 68508435.27 | 65656896.20 | 0.169210E+09 | 38575602.47 |
September | 0.105733E+09 | 50732702.02 | 55000037.08 | 0.122245E+09 | 51776053.19 |
October | 62200459.73 | 25343627.85 | 36856831.89 | 57431087.04 | 69179204.10 |
November | 29976239.05 | 8454514.73 | 21521724.32 | 16532721.11 | 80807753.29 |
December | 26040846.00 | 8923505.54 | 17117340.45 | 14155676.11 | 0.102548E+09 |
Annual Sum or Average | 0.102896E+10 | 0.439865E+09 | 0.589092E+09 | 0.108640E+10 | 0.788413E+09 |
Minimum of Months | 26040846.00 | 8184449.75 | 17117340.45 | 12026839.60 | 38575602.47 |
Maximum of Months | 0.162184E+09 | 85252100.53 | 81053341.15 | 0.201444E+09 | 0.102548E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645835E+09 | 0.00 | 0.645835E+09 | 20237598.13 | 0.410768E+10 |
February | 0.907684E+09 | 0.00 | 0.907684E+09 | 0.170174E+09 | 0.332555E+10 |
March | 0.148061E+10 | 0.00 | 0.148061E+10 | 0.597982E+09 | 0.305347E+10 |
April | 0.202763E+10 | 7192628.59 | 0.202044E+10 | 0.128338E+10 | 0.238376E+10 |
May | 0.269602E+10 | 80094863.53 | 0.261593E+10 | 0.214705E+10 | 0.200487E+10 |
June | 0.274335E+10 | 0.181160E+09 | 0.256219E+10 | 0.242191E+10 | 0.150046E+10 |
July | 0.269432E+10 | 0.211248E+09 | 0.248307E+10 | 0.271011E+10 | 0.139860E+10 |
August | 0.218107E+10 | 58960942.61 | 0.212211E+10 | 0.223513E+10 | 0.137136E+10 |
September | 0.163953E+10 | 483472.07 | 0.163904E+10 | 0.122811E+10 | 0.197492E+10 |
October | 0.116079E+10 | 0.00 | 0.116079E+10 | 0.496378E+09 | 0.272533E+10 |
November | 0.707600E+09 | 0.00 | 0.707600E+09 | 89757712.95 | 0.326644E+10 |
December | 0.548793E+09 | 0.00 | 0.548793E+09 | 8435233.18 | 0.416829E+10 |
Annual Sum or Average | 0.194333E+11 | 0.539139E+09 | 0.188941E+11 | 0.134087E+11 | 0.312808E+11 |
Minimum of Months | 0.548793E+09 | 0.00 | 0.548793E+09 | 8435233.18 | 0.137136E+10 |
Maximum of Months | 0.274335E+10 | 0.211248E+09 | 0.261593E+10 | 0.271011E+10 | 0.416829E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691850E+09 | 0.175407E+09 | 0.516443E+09 | 0.237847E+09 | 0.259470E+10 |
February | 0.114662E+10 | 0.406961E+09 | 0.739663E+09 | 0.732652E+09 | 0.208107E+10 |
March | 0.189542E+10 | 0.686158E+09 | 0.120926E+10 | 0.155845E+10 | 0.192852E+10 |
April | 0.284344E+10 | 0.118149E+10 | 0.166195E+10 | 0.285240E+10 | 0.151463E+10 |
May | 0.312653E+10 | 0.108702E+10 | 0.203951E+10 | 0.329786E+10 | 0.133061E+10 |
June | 0.362359E+10 | 0.157665E+10 | 0.204694E+10 | 0.411868E+10 | 0.101354E+10 |
July | 0.348688E+10 | 0.156511E+10 | 0.192177E+10 | 0.414863E+10 | 0.926563E+09 |
August | 0.342712E+10 | 0.171444E+10 | 0.171268E+10 | 0.422219E+10 | 0.904724E+09 |
September | 0.245211E+10 | 0.113094E+10 | 0.132118E+10 | 0.267754E+10 | 0.125214E+10 |
October | 0.165156E+10 | 0.701758E+09 | 0.949803E+09 | 0.148247E+10 | 0.172729E+10 |
November | 0.783391E+09 | 0.221159E+09 | 0.562232E+09 | 0.405646E+09 | 0.208020E+10 |
December | 0.663975E+09 | 0.213753E+09 | 0.450222E+09 | 0.301211E+09 | 0.265582E+10 |
Annual Sum or Average | 0.257925E+11 | 0.106609E+11 | 0.151316E+11 | 0.260356E+11 | 0.200098E+11 |
Minimum of Months | 0.663975E+09 | 0.175407E+09 | 0.450222E+09 | 0.237847E+09 | 0.904724E+09 |
Maximum of Months | 0.362359E+10 | 0.171444E+10 | 0.204694E+10 | 0.422219E+10 | 0.265582E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285350E+10 | 0.169442E+10 | 0.115908E+10 | 0.250189E+10 | 0.371742E+10 |
February | 0.396357E+10 | 0.245351E+10 | 0.151007E+10 | 0.398251E+10 | 0.307609E+10 |
March | 0.472048E+10 | 0.251738E+10 | 0.220310E+10 | 0.497315E+10 | 0.300637E+10 |
April | 0.482316E+10 | 0.209419E+10 | 0.272897E+10 | 0.538204E+10 | 0.248336E+10 |
May | 0.455717E+10 | 0.135763E+10 | 0.319954E+10 | 0.513357E+10 | 0.215643E+10 |
June | 0.403487E+10 | 0.108331E+10 | 0.295156E+10 | 0.464578E+10 | 0.165716E+10 |
July | 0.454687E+10 | 0.166531E+10 | 0.288156E+10 | 0.580245E+10 | 0.155278E+10 |
August | 0.488504E+10 | 0.227798E+10 | 0.260706E+10 | 0.645550E+10 | 0.150002E+10 |
September | 0.523783E+10 | 0.289250E+10 | 0.234533E+10 | 0.648116E+10 | 0.200324E+10 |
October | 0.490274E+10 | 0.302708E+10 | 0.187566E+10 | 0.552457E+10 | 0.267830E+10 |
November | 0.280516E+10 | 0.160759E+10 | 0.119757E+10 | 0.264232E+10 | 0.307277E+10 |
December | 0.303283E+10 | 0.196266E+10 | 0.107017E+10 | 0.293744E+10 | 0.386745E+10 |
Annual Sum or Average | 0.503632E+11 | 0.246336E+11 | 0.257297E+11 | 0.564624E+11 | 0.307714E+11 |
Minimum of Months | 0.280516E+10 | 0.108331E+10 | 0.107017E+10 | 0.250189E+10 | 0.150002E+10 |
Maximum of Months | 0.523783E+10 | 0.302708E+10 | 0.319954E+10 | 0.648116E+10 | 0.386745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.729733E+09 | 0.215185E+09 | 0.514548E+09 | 0.306036E+09 | 0.261597E+10 |
February | 0.118174E+10 | 0.444131E+09 | 0.737608E+09 | 0.822129E+09 | 0.211680E+10 |
March | 0.183334E+10 | 0.618801E+09 | 0.121454E+10 | 0.152657E+10 | 0.198135E+10 |
April | 0.269925E+10 | 0.103203E+10 | 0.166722E+10 | 0.270837E+10 | 0.160215E+10 |
May | 0.358909E+10 | 0.145805E+10 | 0.213103E+10 | 0.394143E+10 | 0.140800E+10 |
June | 0.334037E+10 | 0.129696E+10 | 0.204342E+10 | 0.375467E+10 | 0.107833E+10 |
July | 0.426413E+10 | 0.224144E+10 | 0.202268E+10 | 0.526911E+10 | 0.102614E+10 |
August | 0.352745E+10 | 0.180122E+10 | 0.172623E+10 | 0.442606E+10 | 0.996268E+09 |
September | 0.277991E+10 | 0.133386E+10 | 0.144605E+10 | 0.320036E+10 | 0.133216E+10 |
October | 0.163536E+10 | 0.666333E+09 | 0.969031E+09 | 0.150052E+10 | 0.178599E+10 |
November | 0.788130E+09 | 0.222286E+09 | 0.565845E+09 | 0.430461E+09 | 0.209463E+10 |
December | 0.684662E+09 | 0.234616E+09 | 0.450046E+09 | 0.366356E+09 | 0.268570E+10 |
Annual Sum or Average | 0.270532E+11 | 0.115649E+11 | 0.154883E+11 | 0.282521E+11 | 0.207235E+11 |
Minimum of Months | 0.684662E+09 | 0.215185E+09 | 0.450046E+09 | 0.306036E+09 | 0.996268E+09 |
Maximum of Months | 0.426413E+10 | 0.224144E+10 | 0.213103E+10 | 0.526911E+10 | 0.268570E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.11 | 1446.73 | 241.13 | 0.00 | 241.13 | 0.00 | 0.00 |
February | 79.81 | 1283.75 | 375.20 | 0.00 | 375.20 | 0.00 | 0.00 |
March | 240.88 | 1060.63 | 552.80 | 0.00 | 552.80 | 0.00 | 0.00 |
April | 513.30 | 862.74 | 782.27 | 2.77 | 779.49 | 0.00 | 0.00 |
May | 816.36 | 709.10 | 1006.58 | 29.90 | 976.68 | 0.00 | 0.00 |
June | 943.04 | 553.53 | 1058.39 | 69.89 | 988.50 | 0.00 | 0.00 |
July | 1017.09 | 500.78 | 1005.94 | 78.87 | 927.07 | 0.00 | 0.00 |
August | 840.80 | 488.59 | 814.32 | 22.01 | 792.31 | 0.00 | 0.00 |
September | 487.62 | 712.84 | 632.53 | 0.19 | 632.35 | 0.00 | 0.00 |
October | 204.73 | 934.05 | 433.39 | 0.00 | 433.39 | 0.00 | 0.00 |
November | 43.22 | 1159.95 | 272.99 | 0.00 | 272.99 | 0.00 | 0.00 |
December | 5.46 | 1451.90 | 204.90 | 0.00 | 204.90 | 0.00 | 0.00 |
Annual Sum or Average | 435.75 | 928.66 | 616.22 | 17.10 | 599.13 | 0.00 | 0.00 |
Minimum of Months | 5.46 | 488.59 | 204.90 | 0.00 | 204.90 | 0.00 | 0.00 |
Maximum of Months | 1017.09 | 1451.90 | 1058.39 | 78.87 | 988.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 93.85 | 915.06 | 258.31 | 65.49 | 192.82 | 0.00 | 0.00 |
February | 314.65 | 807.01 | 473.97 | 168.22 | 305.75 | 0.00 | 0.00 |
March | 594.42 | 674.75 | 707.67 | 256.18 | 451.49 | 0.00 | 0.00 |
April | 1111.62 | 553.03 | 1097.01 | 455.82 | 641.18 | 0.00 | 0.00 |
May | 1238.71 | 473.62 | 1167.31 | 405.85 | 761.46 | 0.00 | 0.00 |
June | 1591.82 | 375.67 | 1397.99 | 608.28 | 789.71 | 0.00 | 0.00 |
July | 1551.10 | 333.64 | 1301.85 | 584.35 | 717.51 | 0.00 | 0.00 |
August | 1578.71 | 324.53 | 1279.54 | 640.10 | 639.44 | 0.00 | 0.00 |
September | 1041.23 | 455.62 | 946.03 | 436.32 | 509.71 | 0.00 | 0.00 |
October | 566.76 | 598.46 | 616.62 | 262.01 | 354.62 | 0.00 | 0.00 |
November | 165.50 | 743.56 | 302.23 | 85.32 | 216.91 | 0.00 | 0.00 |
December | 118.55 | 927.80 | 247.90 | 79.81 | 168.09 | 0.00 | 0.00 |
Annual Sum or Average | 833.21 | 597.58 | 817.87 | 338.05 | 479.82 | 0.00 | 0.00 |
Minimum of Months | 93.85 | 324.53 | 247.90 | 65.49 | 168.09 | 0.00 | 0.00 |
Maximum of Months | 1591.82 | 927.80 | 1397.99 | 640.10 | 789.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 949.35 | 1309.61 | 1065.37 | 632.62 | 432.75 | 0.00 | 0.00 |
February | 1666.92 | 1192.76 | 1638.38 | 1014.18 | 624.20 | 0.00 | 0.00 |
March | 1873.10 | 1048.92 | 1762.43 | 939.88 | 822.54 | 0.00 | 0.00 |
April | 2090.29 | 903.77 | 1860.79 | 807.94 | 1052.84 | 0.00 | 0.00 |
May | 1925.98 | 763.07 | 1701.45 | 506.88 | 1194.57 | 0.00 | 0.00 |
June | 1796.72 | 609.48 | 1556.66 | 417.94 | 1138.72 | 0.00 | 0.00 |
July | 2168.23 | 555.23 | 1697.61 | 621.75 | 1075.85 | 0.00 | 0.00 |
August | 2412.45 | 534.48 | 1823.86 | 850.50 | 973.37 | 0.00 | 0.00 |
September | 2511.93 | 727.12 | 2020.77 | 1115.93 | 904.83 | 0.00 | 0.00 |
October | 2081.25 | 926.60 | 1830.47 | 1130.18 | 700.29 | 0.00 | 0.00 |
November | 1039.15 | 1097.91 | 1082.24 | 620.21 | 462.02 | 0.00 | 0.00 |
December | 1112.47 | 1350.92 | 1132.33 | 732.78 | 399.55 | 0.00 | 0.00 |
Annual Sum or Average | 1802.80 | 916.99 | 1597.01 | 781.12 | 815.88 | 0.00 | 0.00 |
Minimum of Months | 949.35 | 534.48 | 1065.37 | 417.94 | 399.55 | 0.00 | 0.00 |
Maximum of Months | 2511.93 | 1350.92 | 2020.77 | 1130.18 | 1194.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.04 | 922.14 | 272.45 | 80.34 | 192.11 | 0.00 | 0.00 |
February | 348.39 | 819.47 | 488.48 | 183.59 | 304.90 | 0.00 | 0.00 |
March | 580.55 | 691.20 | 684.49 | 231.03 | 453.46 | 0.00 | 0.00 |
April | 1055.29 | 582.12 | 1041.38 | 398.16 | 643.22 | 0.00 | 0.00 |
May | 1478.93 | 498.04 | 1340.01 | 544.37 | 795.64 | 0.00 | 0.00 |
June | 1452.30 | 396.43 | 1288.72 | 500.37 | 788.35 | 0.00 | 0.00 |
July | 1968.54 | 367.16 | 1592.04 | 836.86 | 755.18 | 0.00 | 0.00 |
August | 1655.17 | 354.94 | 1317.00 | 672.50 | 644.50 | 0.00 | 0.00 |
September | 1243.48 | 482.58 | 1072.50 | 514.61 | 557.89 | 0.00 | 0.00 |
October | 572.40 | 616.08 | 610.58 | 248.78 | 361.79 | 0.00 | 0.00 |
November | 173.76 | 747.70 | 304.06 | 85.76 | 218.30 | 0.00 | 0.00 |
December | 140.85 | 937.44 | 255.62 | 87.60 | 168.03 | 0.00 | 0.00 |
Annual Sum or Average | 902.60 | 617.01 | 857.85 | 366.72 | 491.13 | 0.00 | 0.00 |
Minimum of Months | 118.04 | 354.94 | 255.62 | 80.34 | 168.03 | 0.00 | 0.00 |
Maximum of Months | 1968.54 | 937.44 | 1592.04 | 836.86 | 795.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.72 | 1517.67 | 241.12 | 0.00 | 241.12 | 0.00 | 0.00 |
February | 77.81 | 1346.21 | 375.19 | 0.00 | 375.19 | 0.00 | 0.00 |
March | 246.45 | 1094.36 | 552.79 | 0.00 | 552.79 | 0.00 | 0.00 |
April | 531.83 | 873.13 | 782.25 | 2.77 | 779.47 | 0.00 | 0.00 |
May | 836.50 | 719.29 | 1006.56 | 29.90 | 976.65 | 0.00 | 0.00 |
June | 962.21 | 560.44 | 1058.37 | 69.89 | 988.48 | 0.00 | 0.00 |
July | 1032.23 | 508.34 | 1005.92 | 78.87 | 927.06 | 0.00 | 0.00 |
August | 850.42 | 499.97 | 814.30 | 22.01 | 792.29 | 0.00 | 0.00 |
September | 486.69 | 751.07 | 632.52 | 0.19 | 632.33 | 0.00 | 0.00 |
October | 191.35 | 1016.56 | 433.38 | 0.00 | 433.38 | 0.00 | 0.00 |
November | 35.49 | 1272.89 | 272.99 | 0.00 | 272.99 | 0.00 | 0.00 |
December | 3.39 | 1558.45 | 204.89 | 0.00 | 204.89 | 0.00 | 0.00 |
Annual Sum or Average | 440.84 | 974.72 | 616.21 | 17.10 | 599.12 | 0.00 | 0.00 |
Minimum of Months | 3.39 | 499.97 | 204.89 | 0.00 | 204.89 | 0.00 | 0.00 |
Maximum of Months | 1032.23 | 1558.45 | 1058.37 | 78.87 | 988.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.40 | 959.37 | 258.30 | 65.49 | 192.81 | 0.00 | 0.00 |
February | 311.11 | 850.24 | 473.96 | 168.22 | 305.74 | 0.00 | 0.00 |
March | 596.79 | 706.98 | 707.66 | 256.18 | 451.48 | 0.00 | 0.00 |
April | 1118.12 | 577.66 | 1096.99 | 455.81 | 641.18 | 0.00 | 0.00 |
May | 1247.33 | 492.80 | 1167.30 | 405.84 | 761.46 | 0.00 | 0.00 |
June | 1601.19 | 394.02 | 1397.97 | 608.26 | 789.70 | 0.00 | 0.00 |
July | 1558.98 | 348.07 | 1301.83 | 584.33 | 717.50 | 0.00 | 0.00 |
August | 1583.70 | 343.68 | 1279.52 | 640.09 | 639.43 | 0.00 | 0.00 |
September | 1037.79 | 492.23 | 946.02 | 436.31 | 509.71 | 0.00 | 0.00 |
October | 555.53 | 660.89 | 616.61 | 262.00 | 354.61 | 0.00 | 0.00 |
November | 156.98 | 815.93 | 302.23 | 85.32 | 216.91 | 0.00 | 0.00 |
December | 113.74 | 994.93 | 247.90 | 79.80 | 168.09 | 0.00 | 0.00 |
Annual Sum or Average | 833.71 | 635.37 | 817.86 | 338.05 | 479.82 | 0.00 | 0.00 |
Minimum of Months | 91.40 | 343.68 | 247.90 | 65.49 | 168.09 | 0.00 | 0.00 |
Maximum of Months | 1601.19 | 994.93 | 1397.97 | 640.09 | 789.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 956.25 | 1368.79 | 1065.33 | 632.60 | 432.73 | 0.00 | 0.00 |
February | 1678.60 | 1265.60 | 1638.32 | 1014.14 | 624.18 | 0.00 | 0.00 |
March | 1897.75 | 1105.91 | 1762.36 | 939.84 | 822.52 | 0.00 | 0.00 |
April | 2123.03 | 933.68 | 1860.72 | 807.91 | 1052.81 | 0.00 | 0.00 |
May | 1961.71 | 781.68 | 1701.39 | 506.86 | 1194.53 | 0.00 | 0.00 |
June | 1830.54 | 622.40 | 1556.61 | 417.93 | 1138.68 | 0.00 | 0.00 |
July | 2191.28 | 576.16 | 1697.55 | 621.73 | 1075.82 | 0.00 | 0.00 |
August | 2429.92 | 564.85 | 1823.80 | 850.46 | 973.34 | 0.00 | 0.00 |
September | 2517.77 | 790.53 | 2020.69 | 1115.89 | 904.80 | 0.00 | 0.00 |
October | 2079.99 | 1029.88 | 1830.40 | 1130.14 | 700.27 | 0.00 | 0.00 |
November | 1034.84 | 1197.55 | 1082.19 | 620.19 | 462.01 | 0.00 | 0.00 |
December | 1112.18 | 1441.15 | 1132.28 | 732.74 | 399.54 | 0.00 | 0.00 |
Annual Sum or Average | 1818.32 | 971.73 | 1596.95 | 781.09 | 815.86 | 0.00 | 0.00 |
Minimum of Months | 956.25 | 564.85 | 1065.33 | 417.93 | 399.54 | 0.00 | 0.00 |
Maximum of Months | 2517.77 | 1441.15 | 2020.69 | 1130.14 | 1194.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.06 | 968.25 | 272.45 | 80.34 | 192.11 | 0.00 | 0.00 |
February | 349.76 | 864.92 | 488.48 | 183.58 | 304.89 | 0.00 | 0.00 |
March | 586.99 | 723.98 | 684.48 | 231.03 | 453.45 | 0.00 | 0.00 |
April | 1067.33 | 604.43 | 1041.36 | 398.15 | 643.21 | 0.00 | 0.00 |
May | 1490.31 | 523.23 | 1339.99 | 544.37 | 795.63 | 0.00 | 0.00 |
June | 1463.94 | 414.79 | 1288.71 | 500.36 | 788.35 | 0.00 | 0.00 |
July | 1977.40 | 390.32 | 1592.02 | 836.85 | 755.18 | 0.00 | 0.00 |
August | 1660.98 | 378.66 | 1316.98 | 672.49 | 644.50 | 0.00 | 0.00 |
September | 1239.97 | 525.18 | 1072.48 | 514.60 | 557.88 | 0.00 | 0.00 |
October | 563.75 | 679.07 | 610.57 | 248.78 | 361.79 | 0.00 | 0.00 |
November | 167.70 | 819.66 | 304.06 | 85.76 | 218.30 | 0.00 | 0.00 |
December | 138.95 | 1006.62 | 255.62 | 87.59 | 168.03 | 0.00 | 0.00 |
Annual Sum or Average | 905.73 | 657.30 | 857.84 | 366.71 | 491.12 | 0.00 | 0.00 |
Minimum of Months | 118.06 | 378.66 | 255.62 | 80.34 | 168.03 | 0.00 | 0.00 |
Maximum of Months | 1977.40 | 1006.62 | 1592.02 | 836.85 | 795.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.56 | 1533.63 | 241.13 | 0.00 | 241.13 | 0.00 | 0.00 |
February | 70.34 | 1374.65 | 375.20 | 0.00 | 375.20 | 0.00 | 0.00 |
March | 223.26 | 1140.03 | 552.80 | 0.00 | 552.80 | 0.00 | 0.00 |
April | 495.13 | 919.66 | 782.27 | 2.77 | 779.49 | 0.00 | 0.00 |
May | 801.62 | 748.53 | 1006.58 | 29.90 | 976.68 | 0.00 | 0.00 |
June | 934.38 | 578.88 | 1058.39 | 69.89 | 988.50 | 0.00 | 0.00 |
July | 1011.84 | 522.18 | 1005.94 | 78.87 | 927.07 | 0.00 | 0.00 |
August | 834.50 | 512.01 | 814.32 | 22.01 | 792.31 | 0.00 | 0.00 |
September | 473.81 | 761.93 | 632.53 | 0.19 | 632.35 | 0.00 | 0.00 |
October | 185.33 | 1017.52 | 433.39 | 0.00 | 433.39 | 0.00 | 0.00 |
November | 34.63 | 1260.20 | 272.99 | 0.00 | 272.99 | 0.00 | 0.00 |
December | 3.15 | 1556.26 | 204.90 | 0.00 | 204.90 | 0.00 | 0.00 |
Annual Sum or Average | 425.19 | 991.91 | 616.22 | 17.10 | 599.13 | 0.00 | 0.00 |
Minimum of Months | 3.15 | 512.01 | 204.90 | 0.00 | 204.90 | 0.00 | 0.00 |
Maximum of Months | 1011.84 | 1556.26 | 1058.39 | 78.87 | 988.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 88.80 | 968.75 | 258.31 | 65.49 | 192.82 | 0.00 | 0.00 |
February | 302.85 | 860.23 | 473.97 | 168.22 | 305.75 | 0.00 | 0.00 |
March | 581.86 | 720.03 | 707.67 | 256.18 | 451.49 | 0.00 | 0.00 |
April | 1100.46 | 584.35 | 1097.01 | 455.82 | 641.18 | 0.00 | 0.00 |
May | 1231.28 | 496.79 | 1167.31 | 405.85 | 761.46 | 0.00 | 0.00 |
June | 1589.00 | 391.02 | 1397.99 | 608.28 | 789.71 | 0.00 | 0.00 |
July | 1548.92 | 345.94 | 1301.85 | 584.35 | 717.51 | 0.00 | 0.00 |
August | 1576.38 | 337.79 | 1279.54 | 640.10 | 639.44 | 0.00 | 0.00 |
September | 1033.00 | 483.08 | 946.03 | 436.32 | 509.71 | 0.00 | 0.00 |
October | 553.49 | 644.89 | 616.62 | 262.01 | 354.62 | 0.00 | 0.00 |
November | 156.50 | 802.55 | 302.23 | 85.32 | 216.91 | 0.00 | 0.00 |
December | 112.46 | 991.57 | 247.90 | 79.81 | 168.09 | 0.00 | 0.00 |
Annual Sum or Average | 825.58 | 634.51 | 817.87 | 338.05 | 479.82 | 0.00 | 0.00 |
Minimum of Months | 88.80 | 337.79 | 247.90 | 65.49 | 168.09 | 0.00 | 0.00 |
Maximum of Months | 1589.00 | 991.57 | 1397.99 | 640.10 | 789.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 934.10 | 1387.93 | 1065.37 | 632.62 | 432.75 | 0.00 | 0.00 |
February | 1646.21 | 1271.53 | 1638.38 | 1014.18 | 624.20 | 0.00 | 0.00 |
March | 1856.76 | 1122.45 | 1762.43 | 939.88 | 822.54 | 0.00 | 0.00 |
April | 2076.40 | 958.09 | 1860.79 | 807.94 | 1052.84 | 0.00 | 0.00 |
May | 1916.65 | 805.12 | 1701.45 | 506.88 | 1194.57 | 0.00 | 0.00 |
June | 1792.35 | 639.34 | 1556.66 | 417.94 | 1138.72 | 0.00 | 0.00 |
July | 2166.39 | 579.74 | 1697.61 | 621.75 | 1075.85 | 0.00 | 0.00 |
August | 2410.21 | 560.04 | 1823.86 | 850.50 | 973.37 | 0.00 | 0.00 |
September | 2500.45 | 772.85 | 2020.77 | 1115.93 | 904.83 | 0.00 | 0.00 |
October | 2062.64 | 999.96 | 1830.47 | 1130.18 | 700.29 | 0.00 | 0.00 |
November | 1019.41 | 1185.48 | 1082.24 | 620.21 | 462.02 | 0.00 | 0.00 |
December | 1096.71 | 1443.94 | 1132.33 | 732.78 | 399.55 | 0.00 | 0.00 |
Annual Sum or Average | 1790.41 | 975.75 | 1597.01 | 781.12 | 815.88 | 0.00 | 0.00 |
Minimum of Months | 934.10 | 560.04 | 1065.37 | 417.94 | 399.55 | 0.00 | 0.00 |
Maximum of Months | 2500.45 | 1443.94 | 2020.77 | 1130.18 | 1194.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 114.26 | 976.69 | 272.45 | 80.34 | 192.11 | 0.00 | 0.00 |
February | 339.84 | 875.00 | 488.48 | 183.59 | 304.90 | 0.00 | 0.00 |
March | 569.95 | 739.75 | 684.49 | 231.03 | 453.46 | 0.00 | 0.00 |
April | 1044.90 | 618.11 | 1041.38 | 398.16 | 643.22 | 0.00 | 0.00 |
May | 1471.56 | 525.69 | 1340.01 | 544.37 | 795.64 | 0.00 | 0.00 |
June | 1448.56 | 416.02 | 1288.72 | 500.37 | 788.35 | 0.00 | 0.00 |
July | 1967.26 | 383.12 | 1592.04 | 836.86 | 755.18 | 0.00 | 0.00 |
August | 1652.50 | 371.96 | 1317.00 | 672.50 | 644.50 | 0.00 | 0.00 |
September | 1234.71 | 513.95 | 1072.50 | 514.61 | 557.89 | 0.00 | 0.00 |
October | 560.23 | 666.81 | 610.58 | 248.78 | 361.79 | 0.00 | 0.00 |
November | 166.07 | 808.11 | 304.06 | 85.76 | 218.30 | 0.00 | 0.00 |
December | 136.78 | 1002.73 | 255.62 | 87.60 | 168.03 | 0.00 | 0.00 |
Annual Sum or Average | 895.87 | 657.14 | 857.85 | 366.72 | 491.13 | 0.00 | 0.00 |
Minimum of Months | 114.26 | 371.96 | 255.62 | 80.34 | 168.03 | 0.00 | 0.00 |
Maximum of Months | 1967.26 | 1002.73 | 1592.04 | 836.86 | 795.64 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27070362.68 | 0.387492E+10 | 0.645835E+09 | 0.00 | 0.645835E+09 | 0.00 | 0.00 |
February | 0.193077E+09 | 0.310566E+10 | 0.907684E+09 | 0.00 | 0.907684E+09 | 0.00 | 0.00 |
March | 0.645165E+09 | 0.284080E+10 | 0.148061E+10 | 0.00 | 0.148061E+10 | 0.00 | 0.00 |
April | 0.133047E+10 | 0.223623E+10 | 0.202763E+10 | 7192628.59 | 0.202044E+10 | 0.00 | 0.00 |
May | 0.218654E+10 | 0.189925E+10 | 0.269602E+10 | 80094863.53 | 0.261593E+10 | 0.00 | 0.00 |
June | 0.244436E+10 | 0.143475E+10 | 0.274335E+10 | 0.181160E+09 | 0.256219E+10 | 0.00 | 0.00 |
July | 0.272418E+10 | 0.134128E+10 | 0.269432E+10 | 0.211248E+09 | 0.248307E+10 | 0.00 | 0.00 |
August | 0.225200E+10 | 0.130864E+10 | 0.218107E+10 | 58960942.61 | 0.212211E+10 | 0.00 | 0.00 |
September | 0.126392E+10 | 0.184768E+10 | 0.163953E+10 | 483472.07 | 0.163904E+10 | 0.00 | 0.00 |
October | 0.548340E+09 | 0.250177E+10 | 0.116079E+10 | 0.00 | 0.116079E+10 | 0.00 | 0.00 |
November | 0.112020E+09 | 0.300659E+10 | 0.707600E+09 | 0.00 | 0.707600E+09 | 0.00 | 0.00 |
December | 14636872.07 | 0.388876E+10 | 0.548793E+09 | 0.00 | 0.548793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137418E+11 | 0.292863E+11 | 0.194333E+11 | 0.539139E+09 | 0.188941E+11 | 0.00 | 0.00 |
Minimum of Months | 14636872.07 | 0.130864E+10 | 0.548793E+09 | 0.00 | 0.548793E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272418E+10 | 0.388876E+10 | 0.274335E+10 | 0.211248E+09 | 0.261593E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251376E+09 | 0.245090E+10 | 0.691850E+09 | 0.175407E+09 | 0.516443E+09 | 0.00 | 0.00 |
February | 0.761209E+09 | 0.195232E+10 | 0.114662E+10 | 0.406961E+09 | 0.739663E+09 | 0.00 | 0.00 |
March | 0.159209E+10 | 0.180725E+10 | 0.189542E+10 | 0.686158E+09 | 0.120926E+10 | 0.00 | 0.00 |
April | 0.288131E+10 | 0.143346E+10 | 0.284344E+10 | 0.118149E+10 | 0.166195E+10 | 0.00 | 0.00 |
May | 0.331777E+10 | 0.126855E+10 | 0.312653E+10 | 0.108702E+10 | 0.203951E+10 | 0.00 | 0.00 |
June | 0.412600E+10 | 0.973736E+09 | 0.362359E+10 | 0.157665E+10 | 0.204694E+10 | 0.00 | 0.00 |
July | 0.415446E+10 | 0.893635E+09 | 0.348688E+10 | 0.156511E+10 | 0.192177E+10 | 0.00 | 0.00 |
August | 0.422841E+10 | 0.869212E+09 | 0.342712E+10 | 0.171444E+10 | 0.171268E+10 | 0.00 | 0.00 |
September | 0.269886E+10 | 0.118097E+10 | 0.245211E+10 | 0.113094E+10 | 0.132118E+10 | 0.00 | 0.00 |
October | 0.151802E+10 | 0.160293E+10 | 0.165156E+10 | 0.701758E+09 | 0.949803E+09 | 0.00 | 0.00 |
November | 0.428976E+09 | 0.192731E+10 | 0.783391E+09 | 0.221159E+09 | 0.562232E+09 | 0.00 | 0.00 |
December | 0.317530E+09 | 0.248501E+10 | 0.663975E+09 | 0.213753E+09 | 0.450222E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262760E+11 | 0.188453E+11 | 0.257925E+11 | 0.106609E+11 | 0.151316E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251376E+09 | 0.869212E+09 | 0.663975E+09 | 0.175407E+09 | 0.450222E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422841E+10 | 0.248501E+10 | 0.362359E+10 | 0.171444E+10 | 0.204694E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254274E+10 | 0.350767E+10 | 0.285350E+10 | 0.169442E+10 | 0.115908E+10 | 0.00 | 0.00 |
February | 0.403261E+10 | 0.288553E+10 | 0.396357E+10 | 0.245351E+10 | 0.151007E+10 | 0.00 | 0.00 |
March | 0.501692E+10 | 0.280942E+10 | 0.472048E+10 | 0.251738E+10 | 0.220310E+10 | 0.00 | 0.00 |
April | 0.541803E+10 | 0.234256E+10 | 0.482316E+10 | 0.209419E+10 | 0.272897E+10 | 0.00 | 0.00 |
May | 0.515855E+10 | 0.204381E+10 | 0.455717E+10 | 0.135763E+10 | 0.319954E+10 | 0.00 | 0.00 |
June | 0.465709E+10 | 0.157978E+10 | 0.403487E+10 | 0.108331E+10 | 0.295156E+10 | 0.00 | 0.00 |
July | 0.580738E+10 | 0.148712E+10 | 0.454687E+10 | 0.166531E+10 | 0.288156E+10 | 0.00 | 0.00 |
August | 0.646150E+10 | 0.143155E+10 | 0.488504E+10 | 0.227798E+10 | 0.260706E+10 | 0.00 | 0.00 |
September | 0.651092E+10 | 0.188470E+10 | 0.523783E+10 | 0.289250E+10 | 0.234533E+10 | 0.00 | 0.00 |
October | 0.557442E+10 | 0.248181E+10 | 0.490274E+10 | 0.302708E+10 | 0.187566E+10 | 0.00 | 0.00 |
November | 0.269347E+10 | 0.284580E+10 | 0.280516E+10 | 0.160759E+10 | 0.119757E+10 | 0.00 | 0.00 |
December | 0.297963E+10 | 0.361831E+10 | 0.303283E+10 | 0.196266E+10 | 0.107017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.568532E+11 | 0.289181E+11 | 0.503632E+11 | 0.246336E+11 | 0.257297E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254274E+10 | 0.143155E+10 | 0.280516E+10 | 0.108331E+10 | 0.107017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.651092E+10 | 0.361831E+10 | 0.523783E+10 | 0.302708E+10 | 0.319954E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316152E+09 | 0.246986E+10 | 0.729733E+09 | 0.215185E+09 | 0.514548E+09 | 0.00 | 0.00 |
February | 0.842820E+09 | 0.198247E+10 | 0.118174E+10 | 0.444131E+09 | 0.737608E+09 | 0.00 | 0.00 |
March | 0.155496E+10 | 0.185131E+10 | 0.183334E+10 | 0.618801E+09 | 0.121454E+10 | 0.00 | 0.00 |
April | 0.273530E+10 | 0.150887E+10 | 0.269925E+10 | 0.103203E+10 | 0.166722E+10 | 0.00 | 0.00 |
May | 0.396116E+10 | 0.133394E+10 | 0.358909E+10 | 0.145805E+10 | 0.213103E+10 | 0.00 | 0.00 |
June | 0.376435E+10 | 0.102754E+10 | 0.334037E+10 | 0.129696E+10 | 0.204342E+10 | 0.00 | 0.00 |
July | 0.527253E+10 | 0.983390E+09 | 0.426413E+10 | 0.224144E+10 | 0.202268E+10 | 0.00 | 0.00 |
August | 0.443322E+10 | 0.950678E+09 | 0.352745E+10 | 0.180122E+10 | 0.172623E+10 | 0.00 | 0.00 |
September | 0.322311E+10 | 0.125085E+10 | 0.277991E+10 | 0.133386E+10 | 0.144605E+10 | 0.00 | 0.00 |
October | 0.153312E+10 | 0.165011E+10 | 0.163536E+10 | 0.666333E+09 | 0.969031E+09 | 0.00 | 0.00 |
November | 0.450397E+09 | 0.193804E+10 | 0.788130E+09 | 0.222286E+09 | 0.565845E+09 | 0.00 | 0.00 |
December | 0.377258E+09 | 0.251085E+10 | 0.684662E+09 | 0.234616E+09 | 0.450046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.284644E+11 | 0.194579E+11 | 0.270532E+11 | 0.115649E+11 | 0.154883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.316152E+09 | 0.950678E+09 | 0.684662E+09 | 0.215185E+09 | 0.450046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.527253E+10 | 0.251085E+10 | 0.426413E+10 | 0.224144E+10 | 0.213103E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 23349175.76 | 0.406493E+10 | 0.645820E+09 | 0.00 | 0.645820E+09 | 0.00 | 0.00 |
February | 0.188233E+09 | 0.325675E+10 | 0.907663E+09 | 0.00 | 0.907663E+09 | 0.00 | 0.00 |
March | 0.660094E+09 | 0.293113E+10 | 0.148058E+10 | 0.00 | 0.148058E+10 | 0.00 | 0.00 |
April | 0.137851E+10 | 0.226317E+10 | 0.202759E+10 | 7192417.18 | 0.202040E+10 | 0.00 | 0.00 |
May | 0.224048E+10 | 0.192656E+10 | 0.269596E+10 | 80092509.32 | 0.261587E+10 | 0.00 | 0.00 |
June | 0.249404E+10 | 0.145267E+10 | 0.274330E+10 | 0.181154E+09 | 0.256214E+10 | 0.00 | 0.00 |
July | 0.276474E+10 | 0.136153E+10 | 0.269427E+10 | 0.211241E+09 | 0.248303E+10 | 0.00 | 0.00 |
August | 0.227777E+10 | 0.133912E+10 | 0.218103E+10 | 58959209.59 | 0.212207E+10 | 0.00 | 0.00 |
September | 0.126149E+10 | 0.194677E+10 | 0.163949E+10 | 483457.86 | 0.163901E+10 | 0.00 | 0.00 |
October | 0.512504E+09 | 0.272275E+10 | 0.116077E+10 | 0.00 | 0.116077E+10 | 0.00 | 0.00 |
November | 91982728.98 | 0.329934E+10 | 0.707584E+09 | 0.00 | 0.707584E+09 | 0.00 | 0.00 |
December | 9079111.25 | 0.417415E+10 | 0.548780E+09 | 0.00 | 0.548780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139023E+11 | 0.307389E+11 | 0.194328E+11 | 0.539123E+09 | 0.188937E+11 | 0.00 | 0.00 |
Minimum of Months | 9079111.25 | 0.133912E+10 | 0.548780E+09 | 0.00 | 0.548780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.276474E+10 | 0.417415E+10 | 0.274330E+10 | 0.211241E+09 | 0.261587E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244810E+09 | 0.256958E+10 | 0.691839E+09 | 0.175404E+09 | 0.516436E+09 | 0.00 | 0.00 |
February | 0.752627E+09 | 0.205690E+10 | 0.114661E+10 | 0.406953E+09 | 0.739653E+09 | 0.00 | 0.00 |
March | 0.159845E+10 | 0.189357E+10 | 0.189539E+10 | 0.686144E+09 | 0.120924E+10 | 0.00 | 0.00 |
April | 0.289817E+10 | 0.149728E+10 | 0.284340E+10 | 0.118147E+10 | 0.166193E+10 | 0.00 | 0.00 |
May | 0.334084E+10 | 0.131991E+10 | 0.312648E+10 | 0.108700E+10 | 0.203948E+10 | 0.00 | 0.00 |
June | 0.415029E+10 | 0.102130E+10 | 0.362353E+10 | 0.157662E+10 | 0.204691E+10 | 0.00 | 0.00 |
July | 0.417558E+10 | 0.932264E+09 | 0.348683E+10 | 0.156508E+10 | 0.192175E+10 | 0.00 | 0.00 |
August | 0.424177E+10 | 0.920518E+09 | 0.342706E+10 | 0.171441E+10 | 0.171266E+10 | 0.00 | 0.00 |
September | 0.268994E+10 | 0.127585E+10 | 0.245208E+10 | 0.113091E+10 | 0.132116E+10 | 0.00 | 0.00 |
October | 0.148793E+10 | 0.177013E+10 | 0.165153E+10 | 0.701744E+09 | 0.949790E+09 | 0.00 | 0.00 |
November | 0.406889E+09 | 0.211489E+10 | 0.783378E+09 | 0.221155E+09 | 0.562224E+09 | 0.00 | 0.00 |
December | 0.304640E+09 | 0.266482E+10 | 0.663964E+09 | 0.213749E+09 | 0.450215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262919E+11 | 0.200370E+11 | 0.257921E+11 | 0.106606E+11 | 0.151315E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244810E+09 | 0.920518E+09 | 0.663964E+09 | 0.175404E+09 | 0.450215E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424177E+10 | 0.266482E+10 | 0.362353E+10 | 0.171441E+10 | 0.204691E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256122E+10 | 0.366617E+10 | 0.285339E+10 | 0.169435E+10 | 0.115904E+10 | 0.00 | 0.00 |
February | 0.406087E+10 | 0.306173E+10 | 0.396342E+10 | 0.245340E+10 | 0.151001E+10 | 0.00 | 0.00 |
March | 0.508294E+10 | 0.296206E+10 | 0.472030E+10 | 0.251728E+10 | 0.220302E+10 | 0.00 | 0.00 |
April | 0.550289E+10 | 0.242010E+10 | 0.482298E+10 | 0.209410E+10 | 0.272888E+10 | 0.00 | 0.00 |
May | 0.525426E+10 | 0.209366E+10 | 0.455701E+10 | 0.135757E+10 | 0.319944E+10 | 0.00 | 0.00 |
June | 0.474476E+10 | 0.161326E+10 | 0.403473E+10 | 0.108327E+10 | 0.295147E+10 | 0.00 | 0.00 |
July | 0.586912E+10 | 0.154318E+10 | 0.454672E+10 | 0.166524E+10 | 0.288148E+10 | 0.00 | 0.00 |
August | 0.650829E+10 | 0.151288E+10 | 0.488487E+10 | 0.227788E+10 | 0.260699E+10 | 0.00 | 0.00 |
September | 0.652605E+10 | 0.204904E+10 | 0.523763E+10 | 0.289238E+10 | 0.234525E+10 | 0.00 | 0.00 |
October | 0.557104E+10 | 0.275842E+10 | 0.490255E+10 | 0.302695E+10 | 0.187560E+10 | 0.00 | 0.00 |
November | 0.268232E+10 | 0.310404E+10 | 0.280505E+10 | 0.160752E+10 | 0.119752E+10 | 0.00 | 0.00 |
December | 0.297887E+10 | 0.385998E+10 | 0.303271E+10 | 0.196258E+10 | 0.107013E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573426E+11 | 0.306445E+11 | 0.503614E+11 | 0.246325E+11 | 0.257288E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256122E+10 | 0.151288E+10 | 0.280505E+10 | 0.108327E+10 | 0.107013E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652605E+10 | 0.385998E+10 | 0.523763E+10 | 0.302695E+10 | 0.319944E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316204E+09 | 0.259335E+10 | 0.729723E+09 | 0.215181E+09 | 0.514542E+09 | 0.00 | 0.00 |
February | 0.846151E+09 | 0.209240E+10 | 0.118172E+10 | 0.444124E+09 | 0.737600E+09 | 0.00 | 0.00 |
March | 0.157218E+10 | 0.193910E+10 | 0.183331E+10 | 0.618791E+09 | 0.121452E+10 | 0.00 | 0.00 |
April | 0.276651E+10 | 0.156668E+10 | 0.269922E+10 | 0.103201E+10 | 0.166721E+10 | 0.00 | 0.00 |
May | 0.399165E+10 | 0.140143E+10 | 0.358904E+10 | 0.145803E+10 | 0.213101E+10 | 0.00 | 0.00 |
June | 0.379454E+10 | 0.107513E+10 | 0.334033E+10 | 0.129693E+10 | 0.204340E+10 | 0.00 | 0.00 |
July | 0.529627E+10 | 0.104543E+10 | 0.426407E+10 | 0.224141E+10 | 0.202266E+10 | 0.00 | 0.00 |
August | 0.444878E+10 | 0.101421E+10 | 0.352741E+10 | 0.180119E+10 | 0.172622E+10 | 0.00 | 0.00 |
September | 0.321400E+10 | 0.136127E+10 | 0.277987E+10 | 0.133384E+10 | 0.144603E+10 | 0.00 | 0.00 |
October | 0.150995E+10 | 0.181882E+10 | 0.163534E+10 | 0.666322E+09 | 0.969021E+09 | 0.00 | 0.00 |
November | 0.434671E+09 | 0.212455E+10 | 0.788120E+09 | 0.222282E+09 | 0.565838E+09 | 0.00 | 0.00 |
December | 0.372175E+09 | 0.269612E+10 | 0.684653E+09 | 0.234612E+09 | 0.450040E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285631E+11 | 0.207285E+11 | 0.270528E+11 | 0.115647E+11 | 0.154881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.316204E+09 | 0.101421E+10 | 0.684653E+09 | 0.215181E+09 | 0.450040E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529627E+10 | 0.269612E+10 | 0.426407E+10 | 0.224141E+10 | 0.213101E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20237598.13 | 0.410768E+10 | 0.645835E+09 | 0.00 | 0.645835E+09 | 0.00 | 0.00 |
February | 0.170174E+09 | 0.332555E+10 | 0.907684E+09 | 0.00 | 0.907684E+09 | 0.00 | 0.00 |
March | 0.597982E+09 | 0.305347E+10 | 0.148061E+10 | 0.00 | 0.148061E+10 | 0.00 | 0.00 |
April | 0.128338E+10 | 0.238376E+10 | 0.202763E+10 | 7192628.59 | 0.202044E+10 | 0.00 | 0.00 |
May | 0.214705E+10 | 0.200487E+10 | 0.269602E+10 | 80094863.53 | 0.261593E+10 | 0.00 | 0.00 |
June | 0.242191E+10 | 0.150046E+10 | 0.274335E+10 | 0.181160E+09 | 0.256219E+10 | 0.00 | 0.00 |
July | 0.271011E+10 | 0.139860E+10 | 0.269432E+10 | 0.211248E+09 | 0.248307E+10 | 0.00 | 0.00 |
August | 0.223513E+10 | 0.137136E+10 | 0.218107E+10 | 58960942.61 | 0.212211E+10 | 0.00 | 0.00 |
September | 0.122811E+10 | 0.197492E+10 | 0.163953E+10 | 483472.07 | 0.163904E+10 | 0.00 | 0.00 |
October | 0.496378E+09 | 0.272533E+10 | 0.116079E+10 | 0.00 | 0.116079E+10 | 0.00 | 0.00 |
November | 89757712.95 | 0.326644E+10 | 0.707600E+09 | 0.00 | 0.707600E+09 | 0.00 | 0.00 |
December | 8435233.18 | 0.416829E+10 | 0.548793E+09 | 0.00 | 0.548793E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134087E+11 | 0.312808E+11 | 0.194333E+11 | 0.539139E+09 | 0.188941E+11 | 0.00 | 0.00 |
Minimum of Months | 8435233.18 | 0.137136E+10 | 0.548793E+09 | 0.00 | 0.548793E+09 | 0.00 | 0.00 |
Maximum of Months | 0.271011E+10 | 0.416829E+10 | 0.274335E+10 | 0.211248E+09 | 0.261593E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237847E+09 | 0.259470E+10 | 0.691850E+09 | 0.175407E+09 | 0.516443E+09 | 0.00 | 0.00 |
February | 0.732652E+09 | 0.208107E+10 | 0.114662E+10 | 0.406961E+09 | 0.739663E+09 | 0.00 | 0.00 |
March | 0.155845E+10 | 0.192852E+10 | 0.189542E+10 | 0.686158E+09 | 0.120926E+10 | 0.00 | 0.00 |
April | 0.285240E+10 | 0.151463E+10 | 0.284344E+10 | 0.118149E+10 | 0.166195E+10 | 0.00 | 0.00 |
May | 0.329786E+10 | 0.133061E+10 | 0.312653E+10 | 0.108702E+10 | 0.203951E+10 | 0.00 | 0.00 |
June | 0.411868E+10 | 0.101354E+10 | 0.362359E+10 | 0.157665E+10 | 0.204694E+10 | 0.00 | 0.00 |
July | 0.414863E+10 | 0.926563E+09 | 0.348688E+10 | 0.156511E+10 | 0.192177E+10 | 0.00 | 0.00 |
August | 0.422219E+10 | 0.904724E+09 | 0.342712E+10 | 0.171444E+10 | 0.171268E+10 | 0.00 | 0.00 |
September | 0.267754E+10 | 0.125214E+10 | 0.245211E+10 | 0.113094E+10 | 0.132118E+10 | 0.00 | 0.00 |
October | 0.148247E+10 | 0.172729E+10 | 0.165156E+10 | 0.701758E+09 | 0.949803E+09 | 0.00 | 0.00 |
November | 0.405646E+09 | 0.208020E+10 | 0.783391E+09 | 0.221159E+09 | 0.562232E+09 | 0.00 | 0.00 |
December | 0.301211E+09 | 0.265582E+10 | 0.663975E+09 | 0.213753E+09 | 0.450222E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260356E+11 | 0.200098E+11 | 0.257925E+11 | 0.106609E+11 | 0.151316E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237847E+09 | 0.904724E+09 | 0.663975E+09 | 0.175407E+09 | 0.450222E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422219E+10 | 0.265582E+10 | 0.362359E+10 | 0.171444E+10 | 0.204694E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250189E+10 | 0.371742E+10 | 0.285350E+10 | 0.169442E+10 | 0.115908E+10 | 0.00 | 0.00 |
February | 0.398251E+10 | 0.307609E+10 | 0.396357E+10 | 0.245351E+10 | 0.151007E+10 | 0.00 | 0.00 |
March | 0.497315E+10 | 0.300637E+10 | 0.472048E+10 | 0.251738E+10 | 0.220310E+10 | 0.00 | 0.00 |
April | 0.538204E+10 | 0.248336E+10 | 0.482316E+10 | 0.209419E+10 | 0.272897E+10 | 0.00 | 0.00 |
May | 0.513357E+10 | 0.215643E+10 | 0.455717E+10 | 0.135763E+10 | 0.319954E+10 | 0.00 | 0.00 |
June | 0.464578E+10 | 0.165716E+10 | 0.403487E+10 | 0.108331E+10 | 0.295156E+10 | 0.00 | 0.00 |
July | 0.580245E+10 | 0.155278E+10 | 0.454687E+10 | 0.166531E+10 | 0.288156E+10 | 0.00 | 0.00 |
August | 0.645550E+10 | 0.150002E+10 | 0.488504E+10 | 0.227798E+10 | 0.260706E+10 | 0.00 | 0.00 |
September | 0.648116E+10 | 0.200324E+10 | 0.523783E+10 | 0.289250E+10 | 0.234533E+10 | 0.00 | 0.00 |
October | 0.552457E+10 | 0.267830E+10 | 0.490274E+10 | 0.302708E+10 | 0.187566E+10 | 0.00 | 0.00 |
November | 0.264232E+10 | 0.307277E+10 | 0.280516E+10 | 0.160759E+10 | 0.119757E+10 | 0.00 | 0.00 |
December | 0.293744E+10 | 0.386745E+10 | 0.303283E+10 | 0.196266E+10 | 0.107017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.564624E+11 | 0.307714E+11 | 0.503632E+11 | 0.246336E+11 | 0.257297E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250189E+10 | 0.150002E+10 | 0.280516E+10 | 0.108331E+10 | 0.107017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.648116E+10 | 0.386745E+10 | 0.523783E+10 | 0.302708E+10 | 0.319954E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306036E+09 | 0.261597E+10 | 0.729733E+09 | 0.215185E+09 | 0.514548E+09 | 0.00 | 0.00 |
February | 0.822129E+09 | 0.211680E+10 | 0.118174E+10 | 0.444131E+09 | 0.737608E+09 | 0.00 | 0.00 |
March | 0.152657E+10 | 0.198135E+10 | 0.183334E+10 | 0.618801E+09 | 0.121454E+10 | 0.00 | 0.00 |
April | 0.270837E+10 | 0.160215E+10 | 0.269925E+10 | 0.103203E+10 | 0.166722E+10 | 0.00 | 0.00 |
May | 0.394143E+10 | 0.140800E+10 | 0.358909E+10 | 0.145805E+10 | 0.213103E+10 | 0.00 | 0.00 |
June | 0.375467E+10 | 0.107833E+10 | 0.334037E+10 | 0.129696E+10 | 0.204342E+10 | 0.00 | 0.00 |
July | 0.526911E+10 | 0.102614E+10 | 0.426413E+10 | 0.224144E+10 | 0.202268E+10 | 0.00 | 0.00 |
August | 0.442606E+10 | 0.996268E+09 | 0.352745E+10 | 0.180122E+10 | 0.172623E+10 | 0.00 | 0.00 |
September | 0.320036E+10 | 0.133216E+10 | 0.277991E+10 | 0.133386E+10 | 0.144605E+10 | 0.00 | 0.00 |
October | 0.150052E+10 | 0.178599E+10 | 0.163536E+10 | 0.666333E+09 | 0.969031E+09 | 0.00 | 0.00 |
November | 0.430461E+09 | 0.209463E+10 | 0.788130E+09 | 0.222286E+09 | 0.565845E+09 | 0.00 | 0.00 |
December | 0.366356E+09 | 0.268570E+10 | 0.684662E+09 | 0.234616E+09 | 0.450046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282521E+11 | 0.207235E+11 | 0.270532E+11 | 0.115649E+11 | 0.154883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.306036E+09 | 0.996268E+09 | 0.684662E+09 | 0.215185E+09 | 0.450046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.526911E+10 | 0.268570E+10 | 0.426413E+10 | 0.224144E+10 | 0.213103E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.483010E+10 | -0.458408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246019356.5 | 60.05 | 0.00 | 0.00 |
February | 0.441160E+10 | -0.419457E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -217031703.3 | 60.05 | 0.00 | 0.00 |
March | 0.514719E+10 | -0.491064E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236547115.8 | 60.05 | 0.00 | 0.00 |
April | 0.452642E+10 | -0.429981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226608719.5 | 60.05 | 0.00 | 0.00 |
May | 0.467757E+10 | -0.444432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233253641.6 | 60.05 | 0.00 | 0.00 |
June | 0.447764E+10 | -0.425257E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225072685.1 | 60.05 | 0.00 | 0.00 |
July | 0.412894E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231500699.8 | 60.05 | 0.00 | 0.00 |
August | 0.450680E+10 | -0.427461E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232192447.6 | 60.05 | 0.00 | 0.00 |
September | 0.412382E+10 | -0.389919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224629708.9 | 60.05 | 0.00 | 0.00 |
October | 0.438634E+10 | -0.415238E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233959100.2 | 60.05 | 0.00 | 0.00 |
November | 0.447354E+10 | -0.424363E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229904253.9 | 60.05 | 0.00 | 0.00 |
December | 0.459194E+10 | -0.435083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241109650.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.542819E+11 | -0.515041E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277783E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.412382E+10 | -0.491064E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -246019356.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514719E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -217031703.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2752.09 | 32.29 | 222.33 | 219.00 | 2197.51 | 33.54 | 226.00 | 187.50 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4689.04 | 33.25 | 243.17 | 243.67 | 2070.44 | 29.39 | 222.17 | 221.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7764.82 | 33.06 | 208.83 | 312.00 | 1690.81 | 21.84 | 156.00 | 267.33 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2189.81 | 18.65 | 2.83 | 344.33 | 1220.11 | 20.88 | 213.33 | 307.33 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2000.57 | 18.54 | 4.83 | 384.83 | 1096.11 | 20.72 | 210.50 | 343.33 |
June | 375.17 | 0.53 | 0.48 | 01-JUN-06:19 | 1747.28 | 18.11 | 0.00 | 394.17 | 1006.76 | 20.33 | 191.00 | 343.83 |
July | 471.00 | 0.55 | 0.48 | 01-JUL-05:00 | 1556.83 | 16.90 | 0.00 | 393.00 | 915.75 | 19.12 | 151.50 | 337.50 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1851.87 | 17.95 | 2.67 | 372.83 | 1114.36 | 20.19 | 160.50 | 326.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2991.98 | 20.79 | 42.17 | 319.17 | 1482.59 | 21.67 | 187.00 | 288.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 7215.50 | 34.59 | 220.50 | 284.67 | 1974.15 | 23.03 | 157.67 | 256.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:20 | 3067.16 | 31.82 | 224.67 | 224.17 | 2463.70 | 33.16 | 229.67 | 193.83 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3696.50 | 35.43 | 149.50 | 207.33 | 3150.63 | 36.90 | 149.67 | 167.17 |
Annual Sum or Average | 3714.00 | 0.52 | 3110.46 | 23.95 | 1321.50 | 3699.17 | 1524.23 | 23.68 | 2255.00 | 3239.83 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1556.83 | 16.90 | 0.00 | 207.33 | 915.75 | 19.12 | 149.67 | 167.17 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 7764.82 | 35.43 | 243.17 | 394.17 | 3150.63 | 36.90 | 229.67 | 343.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 913.62 | 18.96 | 61.50 | 198.83 | 569.48 | 21.22 | 76.00 | 129.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1473.30 | 19.70 | 68.33 | 226.83 | 790.18 | 21.91 | 79.83 | 179.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2666.91 | 22.09 | 79.00 | 302.00 | 1194.76 | 23.03 | 91.33 | 253.00 |
April | 379.50 | 0.52 | 0.48 | 01-APR-06:19 | 2804.50 | 21.12 | 105.50 | 346.67 | 1588.83 | 23.21 | 104.67 | 306.33 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-06:00 | 2895.55 | 21.04 | 132.67 | 390.83 | 1267.46 | 21.36 | 92.00 | 349.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3039.46 | 20.27 | 89.00 | 402.67 | 1687.16 | 22.32 | 77.67 | 356.33 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2867.10 | 20.73 | 148.50 | 406.33 | 1305.67 | 21.67 | 102.00 | 370.50 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3352.76 | 22.21 | 116.33 | 377.67 | 1468.20 | 21.99 | 74.33 | 337.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2737.77 | 21.79 | 82.67 | 322.83 | 1536.03 | 23.02 | 78.00 | 284.50 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-07:49 | 2450.96 | 21.99 | 83.00 | 270.50 | 1099.11 | 22.65 | 89.33 | 225.17 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1138.50 | 20.35 | 79.17 | 207.50 | 597.99 | 21.17 | 72.00 | 144.00 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 1072.55 | 21.50 | 56.33 | 182.00 | 583.92 | 22.15 | 57.17 | 104.33 |
Annual Sum or Average | 3714.00 | 0.53 | 2465.15 | 20.99 | 1102.00 | 3634.67 | 1221.89 | 22.13 | 994.33 | 3040.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 913.62 | 18.96 | 56.33 | 182.00 | 569.48 | 21.17 | 57.17 | 104.33 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3352.76 | 22.21 | 148.50 | 406.33 | 1687.16 | 23.21 | 104.67 | 370.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.60 | 0.48 | 03-JAN-10:30 | 491.44 | 14.25 | 0.00 | 177.17 | 269.77 | 16.44 | 0.00 | 46.33 |
February | 259.50 | 0.56 | 0.48 | 01-FEB-11:09 | 622.46 | 15.49 | 0.00 | 214.00 | 354.25 | 17.74 | 0.00 | 127.33 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:39 | 836.80 | 17.02 | 0.00 | 297.50 | 498.62 | 19.28 | 4.17 | 215.00 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 982.93 | 17.77 | 0.00 | 348.17 | 572.37 | 19.90 | 33.17 | 300.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 1225.96 | 20.02 | 40.00 | 399.33 | 702.73 | 22.07 | 163.83 | 366.83 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1284.66 | 21.21 | 60.83 | 413.17 | 759.18 | 23.28 | 194.67 | 384.17 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1086.93 | 20.33 | 79.33 | 423.50 | 653.58 | 22.40 | 182.00 | 382.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 954.47 | 17.85 | 0.00 | 390.67 | 586.05 | 20.04 | 54.67 | 345.17 |
September | 301.17 | 0.52 | 0.48 | 01-SEP-07:49 | 908.91 | 17.90 | 0.00 | 313.33 | 555.12 | 20.11 | 17.33 | 255.17 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:50 | 677.62 | 16.04 | 0.00 | 258.83 | 413.24 | 18.38 | 0.33 | 165.33 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:39 | 529.45 | 14.58 | 0.00 | 190.33 | 290.42 | 16.72 | 0.00 | 64.83 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 457.77 | 14.23 | 0.00 | 151.33 | 270.01 | 16.70 | 0.00 | 36.17 |
Annual Sum or Average | 3714.00 | 0.53 | 906.93 | 17.81 | 180.17 | 3577.33 | 535.00 | 19.98 | 650.17 | 2689.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 457.77 | 14.23 | 0.00 | 151.33 | 269.77 | 16.44 | 0.00 | 36.17 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 1284.66 | 21.21 | 79.33 | 423.50 | 759.18 | 23.28 | 194.67 | 384.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:20 | 1023.10 | 18.87 | 65.17 | 199.67 | 562.37 | 21.17 | 68.67 | 136.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-10:00 | 1471.75 | 19.88 | 66.67 | 229.00 | 770.96 | 21.68 | 71.83 | 181.67 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:39 | 2357.65 | 22.15 | 78.17 | 304.67 | 1273.91 | 23.11 | 94.17 | 251.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:00 | 2828.67 | 20.84 | 105.50 | 344.33 | 1243.19 | 20.76 | 60.00 | 306.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:09 | 2920.92 | 17.72 | 52.50 | 390.33 | 1583.55 | 18.63 | 12.33 | 354.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 2989.78 | 17.34 | 42.83 | 402.00 | 1356.40 | 18.43 | 1.17 | 361.33 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-09:00 | 3291.18 | 16.48 | 58.83 | 402.83 | 1449.01 | 17.25 | 4.67 | 360.50 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:10 | 3117.65 | 19.28 | 75.83 | 380.17 | 1803.21 | 20.74 | 54.50 | 341.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:09 | 3442.11 | 22.98 | 100.50 | 314.83 | 1950.03 | 23.92 | 95.67 | 271.67 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:00 | 2354.95 | 22.33 | 87.33 | 272.17 | 1073.45 | 23.23 | 85.17 | 225.17 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:20 | 1093.63 | 18.83 | 63.50 | 208.50 | 585.44 | 20.52 | 60.17 | 140.67 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-10:09 | 1093.79 | 20.33 | 48.67 | 182.50 | 587.30 | 21.08 | 50.00 | 101.00 |
Annual Sum or Average | 3714.00 | 0.53 | 2531.19 | 19.43 | 845.50 | 3631.00 | 1275.49 | 20.50 | 658.33 | 3032.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1023.10 | 16.48 | 42.83 | 182.50 | 562.37 | 17.25 | 1.17 | 101.00 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 3442.11 | 22.98 | 105.50 | 402.83 | 1950.03 | 23.92 | 95.67 | 361.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:09 | 2635.62 | 30.49 | 207.17 | 216.33 | 2129.75 | 33.21 | 222.50 | 182.67 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4558.93 | 32.09 | 231.50 | 240.83 | 1978.88 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:40 | 7608.54 | 32.26 | 207.67 | 309.83 | 1578.63 | 18.98 | 12.33 | 263.33 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 2082.19 | 14.69 | 0.00 | 342.83 | 1143.61 | 18.20 | 10.83 | 302.83 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 1912.10 | 14.65 | 0.00 | 382.67 | 1036.32 | 18.10 | 3.50 | 340.00 |
June | 375.17 | 0.53 | 0.48 | 01-JUN-06:19 | 1670.36 | 14.47 | 0.00 | 392.50 | 954.91 | 17.93 | 0.00 | 340.33 |
July | 471.00 | 0.55 | 0.48 | 01-JUL-05:00 | 1485.50 | 13.11 | 0.00 | 389.67 | 865.65 | 16.61 | 1.00 | 332.50 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1756.04 | 14.24 | 0.00 | 369.33 | 1043.42 | 17.81 | 5.83 | 322.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2854.67 | 17.25 | 27.00 | 317.83 | 1378.94 | 19.09 | 29.83 | 282.83 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 7052.25 | 33.75 | 218.00 | 282.67 | 1855.32 | 20.33 | 28.33 | 254.50 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:20 | 2957.20 | 30.64 | 215.33 | 222.50 | 2395.69 | 32.84 | 227.00 | 190.00 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3561.77 | 34.94 | 149.17 | 204.83 | 3049.98 | 36.51 | 149.67 | 161.50 |
Annual Sum or Average | 3714.00 | 0.52 | 3001.14 | 21.20 | 1255.83 | 3671.83 | 1447.69 | 21.57 | 848.00 | 3192.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1485.50 | 13.11 | 0.00 | 204.83 | 865.65 | 16.61 | 0.00 | 161.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 7608.54 | 34.94 | 231.50 | 392.50 | 3049.98 | 36.51 | 227.00 | 340.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 01-JAN-10:20 | 884.08 | 18.46 | 61.33 | 197.00 | 548.16 | 20.99 | 72.50 | 124.50 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-08:39 | 1429.93 | 19.20 | 68.00 | 225.67 | 756.80 | 21.68 | 74.33 | 175.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2597.20 | 21.62 | 79.00 | 300.00 | 1141.09 | 22.83 | 80.67 | 249.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-06:19 | 2729.27 | 20.66 | 105.33 | 345.17 | 1529.69 | 23.03 | 95.50 | 303.67 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:10 | 2824.44 | 20.61 | 132.33 | 388.50 | 1212.69 | 21.18 | 85.17 | 344.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:19 | 2949.87 | 19.81 | 89.00 | 400.83 | 1619.06 | 22.12 | 75.83 | 352.00 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:10 | 2786.44 | 20.14 | 146.50 | 404.17 | 1246.46 | 20.68 | 87.17 | 365.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3204.92 | 20.23 | 98.50 | 373.67 | 1402.06 | 21.81 | 71.33 | 332.83 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2663.70 | 21.31 | 82.67 | 320.33 | 1478.31 | 22.81 | 68.50 | 280.83 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-07:49 | 2380.91 | 21.30 | 81.00 | 268.17 | 1050.31 | 22.43 | 77.50 | 221.17 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-08:20 | 1084.38 | 18.46 | 65.67 | 204.00 | 573.71 | 20.93 | 67.83 | 137.83 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:39 | 1037.26 | 21.02 | 56.33 | 179.00 | 558.26 | 21.90 | 54.83 | 98.67 |
Annual Sum or Average | 3714.00 | 0.53 | 2390.15 | 20.25 | 1065.67 | 3606.50 | 1170.75 | 21.82 | 911.17 | 2986.33 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 884.08 | 18.46 | 56.33 | 179.00 | 548.16 | 20.68 | 54.83 | 98.67 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 3204.92 | 21.62 | 146.50 | 404.17 | 1619.06 | 23.03 | 95.50 | 365.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.61 | 0.48 | 06-JAN-10:00 | 473.17 | 10.06 | 0.00 | 172.50 | 259.26 | 13.62 | 0.00 | 34.17 |
February | 259.50 | 0.56 | 0.48 | 01-FEB-11:09 | 599.68 | 11.56 | 0.00 | 210.67 | 341.43 | 15.13 | 0.00 | 120.67 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:50 | 806.78 | 13.49 | 0.00 | 293.17 | 482.20 | 17.03 | 0.00 | 206.67 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:30 | 948.35 | 14.27 | 0.00 | 346.00 | 553.25 | 17.71 | 0.17 | 294.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 1179.55 | 16.07 | 26.67 | 397.83 | 678.31 | 19.99 | 51.67 | 362.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1240.40 | 18.32 | 59.00 | 411.00 | 734.14 | 21.52 | 73.67 | 380.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1046.18 | 15.67 | 44.67 | 420.83 | 633.38 | 20.53 | 86.83 | 378.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 922.28 | 14.49 | 0.00 | 389.17 | 568.81 | 18.10 | 1.67 | 340.00 |
September | 301.17 | 0.52 | 0.48 | 01-SEP-07:00 | 875.95 | 14.67 | 0.00 | 311.33 | 537.47 | 18.17 | 0.00 | 247.67 |
October | 245.33 | 0.56 | 0.48 | 01-OCT-09:20 | 652.48 | 12.51 | 0.00 | 256.00 | 399.69 | 16.13 | 0.00 | 156.17 |
November | 242.67 | 0.59 | 0.48 | 01-NOV-11:50 | 510.08 | 10.43 | 0.00 | 184.00 | 279.28 | 13.92 | 0.00 | 53.67 |
December | 160.33 | 0.62 | 0.48 | 01-DEC-10:20 | 439.29 | 10.26 | 0.00 | 145.67 | 259.75 | 14.06 | 0.00 | 29.33 |
Annual Sum or Average | 3714.00 | 0.54 | 874.08 | 14.07 | 130.33 | 3538.17 | 517.28 | 17.79 | 214.00 | 2605.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 439.29 | 10.06 | 0.00 | 145.67 | 259.26 | 13.62 | 0.00 | 29.33 | |
Maximum of Months | 471.00 | 0.62 | 0.48 | 1240.40 | 18.32 | 59.00 | 420.83 | 734.14 | 21.52 | 86.83 | 380.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 01-JAN-13:30 | 992.40 | 18.47 | 64.83 | 198.00 | 539.60 | 21.07 | 67.67 | 130.33 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-10:00 | 1426.36 | 19.46 | 66.50 | 227.17 | 723.52 | 20.58 | 61.00 | 176.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:50 | 2292.69 | 21.75 | 78.17 | 302.50 | 1218.45 | 22.91 | 91.67 | 245.67 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:00 | 2717.24 | 20.41 | 105.50 | 342.33 | 1188.49 | 20.62 | 55.33 | 303.50 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-08:20 | 2834.89 | 17.23 | 52.33 | 389.67 | 1518.62 | 18.46 | 8.83 | 351.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 2870.79 | 16.85 | 42.83 | 398.50 | 1294.17 | 18.25 | 0.83 | 358.83 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-09:00 | 3160.43 | 15.99 | 58.83 | 399.33 | 1381.24 | 17.09 | 4.00 | 357.83 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:30 | 3030.61 | 18.83 | 75.83 | 377.00 | 1727.31 | 20.59 | 54.17 | 337.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:20 | 3351.01 | 22.58 | 100.50 | 312.67 | 1845.77 | 23.52 | 91.50 | 266.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-09:20 | 2291.54 | 21.94 | 87.33 | 269.17 | 994.72 | 21.86 | 73.50 | 218.83 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:30 | 1060.51 | 18.42 | 63.00 | 206.83 | 561.00 | 20.40 | 58.50 | 133.17 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-10:09 | 1059.05 | 19.92 | 48.67 | 180.50 | 561.88 | 20.97 | 49.67 | 94.33 |
Annual Sum or Average | 3714.00 | 0.53 | 2448.00 | 18.99 | 844.33 | 3603.67 | 1215.23 | 20.18 | 616.67 | 2973.83 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 992.40 | 15.99 | 42.83 | 180.50 | 539.60 | 17.09 | 0.83 | 94.33 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 3351.01 | 22.58 | 105.50 | 399.33 | 1845.77 | 23.52 | 91.67 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:09 | 2635.60 | 30.49 | 207.17 | 216.33 | 2129.69 | 33.21 | 222.50 | 182.67 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4558.88 | 32.09 | 231.50 | 240.83 | 1978.79 | 27.95 | 157.17 | 219.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:40 | 7608.44 | 32.26 | 207.67 | 309.83 | 1578.51 | 18.98 | 12.33 | 263.33 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 2082.06 | 14.69 | 0.00 | 342.83 | 1143.52 | 18.20 | 10.83 | 302.83 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 1911.97 | 14.65 | 0.00 | 382.67 | 1036.24 | 18.10 | 3.50 | 340.00 |
June | 375.17 | 0.53 | 0.48 | 01-JUN-06:19 | 1670.27 | 14.47 | 0.00 | 392.33 | 954.84 | 17.93 | 0.00 | 340.33 |
July | 471.00 | 0.55 | 0.48 | 01-JUL-05:00 | 1485.42 | 13.11 | 0.00 | 389.67 | 865.58 | 16.61 | 1.00 | 332.50 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1755.95 | 14.24 | 0.00 | 369.33 | 1043.35 | 17.81 | 5.83 | 322.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2854.56 | 17.26 | 27.00 | 317.83 | 1378.84 | 19.09 | 30.00 | 282.83 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 7052.20 | 33.75 | 218.00 | 282.50 | 1855.21 | 20.33 | 28.33 | 254.50 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-08:20 | 2957.17 | 30.64 | 215.33 | 222.50 | 2395.61 | 32.84 | 227.00 | 189.83 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3561.79 | 34.94 | 149.17 | 204.83 | 3049.91 | 36.51 | 149.67 | 161.50 |
Annual Sum or Average | 3714.00 | 0.52 | 3001.06 | 21.20 | 1255.83 | 3671.50 | 1447.61 | 21.57 | 848.17 | 3192.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1485.42 | 13.11 | 0.00 | 204.83 | 865.58 | 16.61 | 0.00 | 161.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 7608.44 | 34.94 | 231.50 | 392.33 | 3049.91 | 36.51 | 227.00 | 340.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 01-JAN-10:20 | 884.05 | 18.46 | 61.33 | 197.00 | 548.12 | 20.99 | 72.50 | 124.50 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-08:39 | 1429.89 | 19.20 | 68.00 | 225.67 | 756.76 | 21.68 | 74.33 | 175.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2597.15 | 21.62 | 79.00 | 300.00 | 1141.02 | 22.83 | 80.67 | 249.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-06:19 | 2729.20 | 20.66 | 105.33 | 345.17 | 1529.62 | 23.03 | 95.50 | 303.67 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:10 | 2824.36 | 20.61 | 132.33 | 388.50 | 1212.62 | 21.18 | 85.17 | 344.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:19 | 2949.81 | 19.81 | 89.00 | 400.83 | 1618.98 | 22.12 | 75.83 | 352.00 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:10 | 2786.39 | 20.14 | 146.50 | 404.17 | 1246.40 | 20.68 | 87.17 | 365.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3204.88 | 20.24 | 98.50 | 373.67 | 1402.00 | 21.81 | 71.33 | 332.83 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2663.66 | 21.31 | 82.67 | 320.33 | 1478.25 | 22.81 | 68.50 | 280.83 |
October | 245.33 | 0.54 | 0.48 | 01-OCT-07:49 | 2380.88 | 21.30 | 81.00 | 268.17 | 1050.26 | 22.43 | 77.50 | 221.17 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-08:20 | 1084.34 | 18.46 | 65.67 | 204.00 | 573.67 | 20.93 | 67.83 | 137.83 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-09:39 | 1037.24 | 21.02 | 56.33 | 179.00 | 558.22 | 21.90 | 54.83 | 98.67 |
Annual Sum or Average | 3714.00 | 0.53 | 2390.10 | 20.25 | 1065.67 | 3606.50 | 1170.69 | 21.82 | 911.17 | 2986.33 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 884.05 | 18.46 | 56.33 | 179.00 | 548.12 | 20.68 | 54.83 | 98.67 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 3204.88 | 21.62 | 146.50 | 404.17 | 1618.98 | 23.03 | 95.50 | 365.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.61 | 0.48 | 06-JAN-10:00 | 473.14 | 10.07 | 0.00 | 172.50 | 259.23 | 13.62 | 0.00 | 34.17 |
February | 259.50 | 0.56 | 0.48 | 01-FEB-11:09 | 599.65 | 11.56 | 0.00 | 210.67 | 341.41 | 15.13 | 0.00 | 120.67 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:50 | 806.75 | 13.50 | 0.00 | 293.17 | 482.17 | 17.03 | 0.00 | 206.67 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:30 | 948.32 | 14.27 | 0.00 | 346.00 | 553.21 | 17.71 | 0.17 | 294.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 1179.50 | 16.07 | 26.67 | 397.83 | 678.27 | 19.99 | 51.67 | 362.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1240.36 | 18.32 | 59.00 | 411.00 | 734.09 | 21.52 | 73.67 | 380.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1046.15 | 15.67 | 44.67 | 420.83 | 633.34 | 20.53 | 86.83 | 378.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 922.26 | 14.49 | 0.00 | 389.17 | 568.78 | 18.10 | 1.67 | 340.00 |
September | 301.17 | 0.52 | 0.48 | 01-SEP-07:00 | 875.93 | 14.67 | 0.00 | 311.33 | 537.44 | 18.17 | 0.00 | 247.67 |
October | 245.33 | 0.56 | 0.48 | 01-OCT-09:20 | 652.46 | 12.52 | 0.00 | 256.00 | 399.67 | 16.13 | 0.00 | 156.17 |
November | 242.67 | 0.59 | 0.48 | 01-NOV-11:50 | 510.06 | 10.43 | 0.00 | 184.00 | 279.26 | 13.93 | 0.00 | 53.67 |
December | 160.33 | 0.62 | 0.48 | 01-DEC-10:20 | 439.28 | 10.26 | 0.00 | 145.67 | 259.73 | 14.06 | 0.00 | 29.33 |
Annual Sum or Average | 3714.00 | 0.54 | 874.05 | 14.07 | 130.33 | 3538.17 | 517.25 | 17.79 | 214.00 | 2605.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 439.28 | 10.07 | 0.00 | 145.67 | 259.23 | 13.62 | 0.00 | 29.33 | |
Maximum of Months | 471.00 | 0.62 | 0.48 | 1240.36 | 18.32 | 59.00 | 420.83 | 734.09 | 21.52 | 86.83 | 380.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 01-JAN-13:30 | 992.37 | 18.47 | 64.83 | 198.00 | 539.57 | 21.07 | 67.67 | 130.33 |
February | 259.50 | 0.54 | 0.48 | 01-FEB-10:00 | 1426.32 | 19.46 | 66.50 | 227.17 | 723.47 | 20.58 | 61.00 | 176.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:50 | 2292.64 | 21.76 | 78.17 | 302.50 | 1218.39 | 22.91 | 91.67 | 245.67 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:00 | 2717.18 | 20.42 | 105.50 | 342.33 | 1188.42 | 20.62 | 55.33 | 303.50 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-08:20 | 2834.81 | 17.23 | 52.33 | 389.67 | 1518.54 | 18.46 | 8.83 | 351.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 2870.72 | 16.85 | 42.83 | 398.50 | 1294.09 | 18.25 | 0.83 | 358.83 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-09:00 | 3160.37 | 15.99 | 58.83 | 399.33 | 1381.18 | 17.09 | 4.00 | 357.83 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:30 | 3030.58 | 18.83 | 75.83 | 377.00 | 1727.25 | 20.59 | 54.17 | 337.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:20 | 3350.97 | 22.58 | 100.50 | 312.67 | 1845.69 | 23.52 | 91.50 | 266.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-09:20 | 2291.52 | 21.94 | 87.33 | 269.17 | 994.67 | 21.86 | 73.67 | 218.83 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:30 | 1060.48 | 18.42 | 63.00 | 206.83 | 560.96 | 20.40 | 58.50 | 133.17 |
December | 160.33 | 0.56 | 0.48 | 01-DEC-10:09 | 1059.03 | 19.92 | 48.67 | 180.50 | 561.84 | 20.97 | 49.67 | 94.33 |
Annual Sum or Average | 3714.00 | 0.53 | 2447.95 | 18.99 | 844.33 | 3603.67 | 1215.17 | 20.18 | 616.83 | 2973.83 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 992.37 | 15.99 | 42.83 | 180.50 | 539.57 | 17.09 | 0.83 | 94.33 | |
Maximum of Months | 471.00 | 0.56 | 0.48 | 3350.97 | 22.58 | 105.50 | 399.33 | 1845.69 | 23.52 | 91.67 | 358.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461564E+10 | 12316.25 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265306E+10 | 10350.96 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412107E+09 | 7588.48 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112200E+09 | 4895.59 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68275.19 | 76.86 | 17-MAY-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1564.77 | 2.61 | 28-JUN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 377359.92 | 5.18 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 951267.94 | 5.34 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 206711.79 | 5.16 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8014880.89 | 884.68 | 31-OCT-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124135E+10 | 7707.42 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316796E+10 | 11539.66 | 26-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1564.77 | 2.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461564E+10 | 12316.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400752E+09 | 10346.90 | 03-JAN-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400752E+09 | 10346.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467187E+10 | 8154.46 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271217E+10 | 8138.54 | 24-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188169E+10 | 8134.09 | 09-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103692E+10 | 8161.15 | 26-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.674798E+09 | 8207.11 | 23-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.347787E+09 | 8218.72 | 09-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88043771.70 | 8153.15 | 03-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90332867.50 | 8201.55 | 03-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.309887E+09 | 8202.86 | 26-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.933685E+09 | 8217.99 | 11-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244453E+10 | 8136.88 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364837E+10 | 8134.62 | 29-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 88043771.70 | 8134.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.467187E+10 | 8218.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168232E+10 | 5458.67 | 04-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.748495E+09 | 5446.28 | 21-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181529E+09 | 5440.12 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22766989.06 | 5432.36 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18714760.22 | 4645.43 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372898E+09 | 5440.01 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104553E+10 | 5448.72 | 11-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168232E+10 | 5458.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237311E+10 | 5910.01 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115044E+10 | 5894.89 | 22-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320654E+09 | 5892.55 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46715812.45 | 5885.50 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17484887.44 | 5883.89 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.442658E+09 | 5890.30 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139676E+10 | 5892.27 | 11-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.574783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237311E+10 | 5910.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181594E+10 | 5659.51 | 04-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.857744E+09 | 5640.67 | 22-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270078E+09 | 5640.83 | 10-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46784542.29 | 5633.81 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74092.82 | 287.19 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28730206.71 | 4224.41 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449384E+09 | 5640.13 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116830E+10 | 5640.33 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181594E+10 | 5659.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.569122E+10 | 13238.81 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352593E+10 | 11528.18 | 18-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107616E+10 | 8862.42 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349744E+09 | 6447.89 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27030036.08 | 2488.85 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 301945.07 | 4.83 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 767349.76 | 4.83 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 143095.01 | 4.85 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112668E+09 | 3162.90 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217497E+10 | 9307.47 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447304E+10 | 12199.90 | 26-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.569122E+10 | 13238.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133083E+10 | 14777.45 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215157E+09 | 14759.20 | 22-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10391111.62 | 14607.42 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74896015.35 | 14784.05 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408451E+09 | 14770.90 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133083E+10 | 14784.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186013E+10 | 8765.77 | 03-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.780974E+09 | 8762.30 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195322E+09 | 8742.60 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40225613.14 | 8719.58 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 623407.87 | 1347.57 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60154581.14 | 8713.79 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.620870E+09 | 8763.78 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137575E+10 | 8764.23 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.493405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186013E+10 | 8765.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177082E+10 | 6013.44 | 09-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.831395E+09 | 6008.29 | 06-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196828E+09 | 5992.66 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28345570.42 | 5979.66 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1170388.48 | 1886.73 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 255963.89 | 967.70 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75741931.12 | 5976.33 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.646573E+09 | 6005.93 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133946E+10 | 6011.80 | 26-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177082E+10 | 6013.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203007E+10 | 6331.25 | 05-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.897084E+09 | 6331.71 | 06-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169718E+09 | 6333.33 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24263401.25 | 6278.52 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38255766.12 | 6280.10 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.575283E+09 | 6316.62 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142754E+10 | 6332.24 | 18-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203007E+10 | 6333.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174127E+10 | 6036.14 | 09-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.842700E+09 | 6027.26 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.241056E+09 | 6015.20 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46922001.97 | 6002.09 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1348239.68 | 2090.61 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 247659.09 | 534.78 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84201880.96 | 5998.76 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.652603E+09 | 6028.19 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133097E+10 | 6034.42 | 26-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174127E+10 | 6036.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.605958E+10 | 14465.73 | 07-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387409E+10 | 13604.30 | 18-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154310E+10 | 10952.39 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.561851E+09 | 8356.17 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86953701.72 | 4226.87 | 18-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 310478.86 | 4.97 | 31-JUL-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 788566.15 | 5.34 | 09-AUG-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11731525.06 | 1630.40 | 27-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265449E+09 | 4455.86 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248993E+10 | 10222.94 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496182E+10 | 12200.40 | 26-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.605958E+10 | 14465.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.384026E+10 | 21427.47 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164266E+10 | 21418.77 | 16-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291670E+09 | 21404.95 | 06-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30491673.80 | 21228.40 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70019819.85 | 21244.79 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117231E+10 | 21431.85 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272759E+10 | 21430.22 | 28-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.977500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.384026E+10 | 21431.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.317230E+10 | 10429.78 | 03-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170781E+10 | 10422.61 | 22-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.765169E+09 | 10421.46 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260290E+09 | 10385.98 | 07-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36690136.07 | 10373.33 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 812881.48 | 1044.15 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17343967.42 | 10378.82 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368175E+09 | 10379.60 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152571E+10 | 10422.55 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265379E+10 | 10422.77 | 18-DEC-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317230E+10 | 10429.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258685E+10 | 6914.99 | 06-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142485E+10 | 6909.15 | 13-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.573746E+09 | 6903.95 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134361E+09 | 6886.85 | 12-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21063209.90 | 6872.03 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 642213.23 | 944.29 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13173598.61 | 6875.63 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312329E+09 | 6879.74 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123582E+10 | 6909.75 | 13-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216387E+10 | 6919.37 | 11-DEC-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258685E+10 | 6919.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346664E+10 | 7587.88 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196359E+10 | 7584.10 | 06-FEB-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758896E+09 | 7587.08 | 14-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200121E+09 | 7585.85 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11812826.20 | 7532.07 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9037538.48 | 7536.60 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323049E+09 | 7540.64 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150182E+10 | 7587.76 | 13-NOV-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286241E+10 | 7587.55 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346664E+10 | 7587.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275139E+10 | 7155.09 | 09-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161634E+10 | 7158.39 | 13-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779915E+09 | 7152.54 | 06-MAR-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244487E+09 | 7127.91 | 07-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36920453.77 | 7119.27 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1117405.49 | 897.70 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20535074.67 | 7122.73 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403005E+09 | 7127.17 | 31-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140780E+10 | 7153.23 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234191E+10 | 7153.37 | 18-DEC-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.960343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275139E+10 | 7158.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2824018.97 | 2590215.13 | 3467.54 | 03-JAN-07:25 | 3292.02 | 0.00 |
February | 0.00 | 0.00 | 0.211916E+09 | 0.195303E+09 | 13330.76 | 27-FEB-15:10 | 13330.76 | 0.00 |
March | 0.00 | 0.00 | 0.321181E+09 | 0.283806E+09 | 10815.83 | 18-MAR-16:00 | 10815.83 | 0.00 |
April | 0.00 | 0.00 | 0.353408E+10 | 0.340468E+10 | 51950.68 | 27-APR-15:00 | 51950.68 | 0.00 |
May | 0.00 | 0.00 | 0.770096E+10 | 0.690822E+10 | 46599.70 | 15-MAY-16:00 | 46599.70 | 0.00 |
June | 0.00 | 0.00 | 0.146596E+11 | 0.137081E+11 | 53880.48 | 28-JUN-15:30 | 53880.48 | 0.00 |
July | 0.00 | 0.00 | 0.281712E+11 | 0.251131E+11 | 71647.56 | 31-JUL-16:00 | 65481.60 | 0.00 |
August | 0.00 | 0.00 | 0.380933E+11 | 0.335915E+11 | 72382.29 | 10-AUG-15:30 | 68296.21 | 0.00 |
September | 0.00 | 0.00 | 0.139892E+11 | 0.117607E+11 | 57860.73 | 12-SEP-16:00 | 54733.37 | 0.00 |
October | 0.00 | 0.00 | 0.180820E+10 | 0.171346E+10 | 35441.99 | 04-OCT-15:00 | 35441.99 | 0.00 |
November | 0.00 | 0.00 | 0.366284E+09 | 0.252063E+09 | 19368.19 | 04-NOV-14:20 | 14748.52 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108859E+12 | 0.969337E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.380933E+11 | 0.335915E+11 | 72382.29 | 68296.21 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.210345E+09 | 0.196605E+09 | 13578.77 | 27-FEB-15:00 | 13578.77 | 0.00 |
March | 0.00 | 0.00 | 0.322623E+09 | 0.290740E+09 | 12030.88 | 18-MAR-16:00 | 12030.88 | 0.00 |
April | 0.00 | 0.00 | 0.350365E+10 | 0.338393E+10 | 49846.92 | 27-APR-14:50 | 49846.92 | 0.00 |
May | 0.00 | 0.00 | 0.734009E+10 | 0.660658E+10 | 44298.93 | 04-MAY-15:00 | 44298.93 | 0.00 |
June | 0.00 | 0.00 | 0.134516E+11 | 0.125718E+11 | 49984.85 | 28-JUN-15:30 | 49984.85 | 0.00 |
July | 0.00 | 0.00 | 0.253931E+11 | 0.227128E+11 | 65671.85 | 31-JUL-14:40 | 59417.92 | 0.00 |
August | 0.00 | 0.00 | 0.334197E+11 | 0.295095E+11 | 67191.91 | 29-AUG-14:40 | 60187.97 | 0.00 |
September | 0.00 | 0.00 | 0.124764E+11 | 0.104646E+11 | 52578.57 | 14-SEP-13:00 | 38284.01 | 0.00 |
October | 0.00 | 0.00 | 0.161693E+10 | 0.151808E+10 | 31746.37 | 04-OCT-15:00 | 31746.37 | 0.00 |
November | 0.00 | 0.00 | 0.383128E+09 | 0.275257E+09 | 19812.91 | 04-NOV-13:40 | 15439.56 | 0.00 |
December | 0.00 | 0.00 | 43020.58 | 42697.15 | 501.91 | 27-DEC-07:04 | 498.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.981177E+11 | 0.875299E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.334197E+11 | 0.295095E+11 | 67191.91 | 60187.97 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 306623.24 | 290659.09 | 666.90 | 03-JAN-07:12 | 600.08 | 0.00 |
February | 0.00 | 0.00 | 0.215832E+09 | 0.196455E+09 | 13470.71 | 27-FEB-15:00 | 13470.71 | 0.00 |
March | 0.00 | 0.00 | 0.329246E+09 | 0.292254E+09 | 12113.99 | 18-MAR-16:00 | 12113.99 | 0.00 |
April | 0.00 | 0.00 | 0.375525E+10 | 0.359781E+10 | 57561.79 | 27-APR-14:40 | 57561.79 | 0.00 |
May | 0.00 | 0.00 | 0.765878E+10 | 0.679918E+10 | 48074.45 | 04-MAY-15:00 | 48074.45 | 0.00 |
June | 0.00 | 0.00 | 0.140954E+11 | 0.130322E+11 | 57977.23 | 28-JUN-15:20 | 57977.23 | 0.00 |
July | 0.00 | 0.00 | 0.268474E+11 | 0.237152E+11 | 73743.41 | 31-JUL-14:40 | 67194.86 | 0.00 |
August | 0.00 | 0.00 | 0.350887E+11 | 0.307456E+11 | 75608.63 | 10-AUG-14:50 | 70565.84 | 0.00 |
September | 0.00 | 0.00 | 0.125461E+11 | 0.103414E+11 | 53504.18 | 14-SEP-13:30 | 43201.95 | 0.00 |
October | 0.00 | 0.00 | 0.147745E+10 | 0.136982E+10 | 30989.70 | 04-OCT-15:00 | 30989.70 | 0.00 |
November | 0.00 | 0.00 | 0.394950E+09 | 0.274748E+09 | 20659.46 | 04-NOV-13:40 | 15517.95 | 0.00 |
December | 0.00 | 0.00 | 35537.80 | 33890.41 | 414.61 | 26-DEC-06:01 | 395.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.102409E+12 | 0.903650E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 35537.80 | 33890.41 | 414.61 | 395.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.350887E+11 | 0.307456E+11 | 75608.63 | 70565.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 19230.51 | 174234.70 | 02-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11265.29 | 166854.19 | 06-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3582.10 | 170694.10 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1223.40 | 155430.89 | 18-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 333.04 | 67450.33 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 131.55 | 10926.40 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.82 | 11311.26 | 12-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 35.56 | 11789.65 | 01-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 146.94 | 54334.95 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1152.53 | 140686.83 | 31-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 7290.64 | 161606.26 | 28-NOV-07:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14273.25 | 162807.09 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 4868.51 | ||||
Minimum of Months | 0.00 | 0.00 | 31.82 | 10926.40 | ||
Maximum of Months | 0.00 | 0.00 | 19230.51 | 174234.70 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1702.15 | 6226.75 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1724.48 | 6234.19 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1823.75 | 6212.85 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1649.61 | 6074.20 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1649.95 | 5884.98 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1631.24 | 5653.23 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1446.19 | 5455.86 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1586.59 | 5376.19 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1495.25 | 5493.56 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1541.18 | 5706.33 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1627.90 | 5930.86 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1615.25 | 6114.32 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1623.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1446.19 | 5376.19 | ||
Maximum of Months | 0.00 | 0.00 | 1823.75 | 6234.19 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140188E+10 | 0.28 | 2634.26 | 02-JAN-06:11 | 0.78 |
February | 0.128243E+10 | 0.28 | 1751.02 | 27-FEB-15:30 | 0.63 |
March | 0.175009E+10 | 0.31 | 2172.09 | 02-MAR-16:20 | 0.70 |
April | 0.202618E+10 | 0.32 | 5941.82 | 27-APR-14:50 | 1.24 |
May | 0.274398E+10 | 0.37 | 6437.90 | 15-MAY-15:20 | 1.31 |
June | 0.335534E+10 | 0.41 | 6719.94 | 28-JUN-15:20 | 1.34 |
July | 0.419019E+10 | 0.44 | 9442.83 | 24-JUL-14:10 | 1.66 |
August | 0.491926E+10 | 0.49 | 9723.56 | 10-AUG-15:40 | 1.69 |
September | 0.327534E+10 | 0.39 | 8550.33 | 11-SEP-15:30 | 1.56 |
October | 0.215670E+10 | 0.32 | 6284.42 | 04-OCT-15:30 | 1.29 |
November | 0.148443E+10 | 0.28 | 1805.48 | 06-NOV-17:00 | 0.64 |
December | 0.136608E+10 | 0.27 | 1654.95 | 01-DEC-06:11 | 0.62 |
Annual Sum or Average | 0.299519E+11 | 0.35 | |||
Minimum of Months | 0.128243E+10 | 0.27 | 1654.95 | 0.62 | |
Maximum of Months | 0.491926E+10 | 0.49 | 9723.56 | 1.69 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138850E+10 | 0.28 | 2728.31 | 02-JAN-07:08 | 0.82 |
February | 0.124087E+10 | 0.28 | 2728.31 | 21-FEB-06:01 | 0.82 |
March | 0.151928E+10 | 0.30 | 2728.31 | 06-MAR-07:02 | 0.82 |
April | 0.173607E+10 | 0.31 | 6134.37 | 27-APR-14:30 | 1.32 |
May | 0.233819E+10 | 0.35 | 6175.00 | 15-MAY-14:50 | 1.34 |
June | 0.284381E+10 | 0.40 | 6206.81 | 28-JUN-15:20 | 1.33 |
July | 0.353208E+10 | 0.42 | 8271.99 | 31-JUL-14:50 | 1.59 |
August | 0.403351E+10 | 0.46 | 8532.40 | 10-AUG-15:20 | 1.63 |
September | 0.261438E+10 | 0.37 | 7296.09 | 11-SEP-14:50 | 1.48 |
October | 0.167497E+10 | 0.30 | 5302.94 | 04-OCT-15:00 | 1.22 |
November | 0.128630E+10 | 0.27 | 2728.31 | 13-NOV-07:01 | 0.82 |
December | 0.131602E+10 | 0.27 | 2728.31 | 11-DEC-07:03 | 0.82 |
Annual Sum or Average | 0.255240E+11 | 0.33 | |||
Minimum of Months | 0.124087E+10 | 0.27 | 2728.31 | 0.82 | |
Maximum of Months | 0.403351E+10 | 0.46 | 8532.40 | 1.63 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154405E+10 | 0.30 | 2600.03 | 02-JAN-06:11 | 0.75 |
February | 0.130861E+10 | 0.28 | 2600.03 | 01-FEB-07:03 | 0.75 |
March | 0.151616E+10 | 0.29 | 2600.03 | 01-MAR-07:01 | 0.75 |
April | 0.165988E+10 | 0.29 | 6110.32 | 27-APR-14:30 | 1.22 |
May | 0.215759E+10 | 0.33 | 6248.68 | 15-MAY-14:50 | 1.25 |
June | 0.259346E+10 | 0.36 | 6372.94 | 28-JUN-15:20 | 1.26 |
July | 0.323365E+10 | 0.38 | 8221.61 | 31-JUL-14:50 | 1.47 |
August | 0.363708E+10 | 0.41 | 8751.21 | 10-AUG-15:20 | 1.53 |
September | 0.230392E+10 | 0.33 | 6489.18 | 14-SEP-14:30 | 1.27 |
October | 0.154344E+10 | 0.28 | 4449.95 | 04-OCT-14:50 | 1.02 |
November | 0.131197E+10 | 0.27 | 2600.03 | 10-NOV-07:02 | 0.75 |
December | 0.138885E+10 | 0.27 | 2600.03 | 01-DEC-07:01 | 0.75 |
Annual Sum or Average | 0.241987E+11 | 0.32 | |||
Minimum of Months | 0.130861E+10 | 0.27 | 2600.03 | 0.75 | |
Maximum of Months | 0.363708E+10 | 0.41 | 8751.21 | 1.53 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.318884E+09 | 0.286996E+09 | 558.22 | 07-JAN-07:15 | 502.40 | 502.40 | 42.00 | 1.71 |
February | 0.174560E+09 | 0.157104E+09 | 557.86 | 18-FEB-07:03 | 502.07 | 502.07 | 38.30 | 1.71 |
March | 65678595.85 | 59110736.27 | 530.62 | 06-MAR-07:02 | 477.56 | 477.56 | 36.97 | 1.48 |
April | 23665483.11 | 21298934.80 | 518.30 | 18-APR-06:02 | 466.47 | 466.47 | 32.28 | 1.34 |
May | 8665951.25 | 7799356.13 | 373.75 | 18-MAY-06:03 | 336.37 | 336.37 | 31.58 | 0.57 |
June | 3813187.96 | 3431869.16 | 98.54 | 14-JUN-06:05 | 88.69 | 88.69 | 37.90 | 0.11 |
July | 719237.62 | 647313.86 | 84.56 | 03-JUL-06:06 | 76.11 | 76.11 | 34.11 | 0.09 |
August | 958167.40 | 862350.66 | 84.79 | 21-AUG-06:08 | 76.31 | 76.31 | 41.99 | 0.09 |
September | 3859083.58 | 3473175.22 | 349.24 | 28-SEP-06:03 | 314.31 | 314.31 | 34.39 | 0.51 |
October | 23294364.69 | 20964928.22 | 514.97 | 31-OCT-06:03 | 463.47 | 463.47 | 34.14 | 1.30 |
November | 0.123173E+09 | 0.110856E+09 | 542.74 | 24-NOV-07:01 | 488.47 | 488.47 | 39.58 | 1.59 |
December | 0.239526E+09 | 0.215574E+09 | 563.08 | 26-DEC-07:01 | 506.77 | 506.77 | 41.81 | 1.74 |
Annual Sum or Average | 0.986798E+09 | 0.888118E+09 | ||||||
Minimum of Months | 719237.62 | 647313.86 | 84.56 | 76.11 | 76.11 | 31.58 | 0.09 | |
Maximum of Months | 0.318884E+09 | 0.286996E+09 | 563.08 | 506.77 | 506.77 | 42.00 | 1.74 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.14 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.83 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.01 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.90 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.21 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.31 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.42 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.35 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.20 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.18 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.07 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 34.32 | 60.00 | 19230.51 | 174234.70 | 02-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 27.99 | 27.99 | 11265.29 | 166854.19 | 06-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.66 | 26.66 | 3582.10 | 170694.10 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21.74 | 21.74 | 1223.40 | 155430.89 | 18-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 39.77 | 39.77 | 333.04 | 67450.33 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44.08 | 44.08 | 131.55 | 10926.40 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 33.90 | 33.90 | 31.82 | 11311.26 | 12-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.30 | 28.30 | 35.56 | 11789.65 | 01-AUG-06:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 34.52 | 34.52 | 146.94 | 54334.95 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 38.64 | 38.64 | 1152.53 | 140686.83 | 31-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.04 | 24.04 | 7290.64 | 161606.26 | 28-NOV-07:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.28 | 29.28 | 14273.25 | 162807.09 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 4868.51 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.74 | 21.74 | 31.82 | 10926.40 | ||
Maximum of Months | 0.00 | 0.00 | 44.08 | 60.00 | 19230.51 | 174234.70 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.14 | 58.14 | 1702.15 | 6226.75 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.61 | 57.61 | 1724.48 | 6234.19 | 10-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 1823.75 | 6212.85 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 1649.61 | 6074.20 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 1649.95 | 5884.98 | 01-MAY-11:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 1631.24 | 5653.23 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1446.19 | 5455.86 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.95 | 57.95 | 1586.59 | 5376.19 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1495.25 | 5493.56 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.04 | 57.04 | 1541.18 | 5706.33 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 1627.90 | 5930.86 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.74 | 57.74 | 1615.25 | 6114.32 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1623.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.04 | 57.04 | 1446.19 | 5376.19 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 1823.75 | 6234.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.155596E+11 | 0.00 | 0.00 | 0.140263E+10 | 0.00 | 0.00 |
February | 0.812192E+10 | 0.00 | 0.00 | 0.133535E+10 | 0.00 | 0.00 |
March | 0.306606E+10 | 0.00 | 0.00 | 0.183262E+10 | 0.00 | 0.00 |
April | 0.126538E+10 | 0.00 | 0.00 | 0.284262E+10 | 0.00 | 0.00 |
May | 0.674940E+09 | 0.00 | 0.00 | 0.450748E+10 | 0.00 | 0.00 |
June | 0.347789E+09 | 0.00 | 0.00 | 0.670249E+10 | 0.00 | 0.00 |
July | 88421131.61 | 0.00 | 0.00 | 0.105151E+11 | 0.00 | 0.00 |
August | 91284135.44 | 0.00 | 0.00 | 0.135264E+11 | 0.00 | 0.00 |
September | 0.310094E+09 | 0.00 | 0.00 | 0.641538E+10 | 0.00 | 0.00 |
October | 0.100663E+10 | 0.00 | 0.00 | 0.258683E+10 | 0.00 | 0.00 |
November | 0.495082E+10 | 0.00 | 0.00 | 0.157100E+10 | 0.00 | 0.00 |
December | 0.104269E+11 | 0.00 | 0.00 | 0.136608E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459099E+11 | 0.00 | 0.00 | 0.546039E+11 | 0.00 | 0.00 |
Minimum of Months | 88421131.61 | 0.00 | 0.00 | 0.133535E+10 | 0.00 | 0.00 |
Maximum of Months | 0.155596E+11 | 0.00 | 0.00 | 0.135264E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.144243E+11 | 0.00 | 0.00 | 0.138850E+10 | 0.00 | 0.00 |
February | 0.709324E+10 | 0.00 | 0.00 | 0.129322E+10 | 0.00 | 0.00 |
March | 0.188948E+10 | 0.00 | 0.00 | 0.160134E+10 | 0.00 | 0.00 |
April | 0.489501E+09 | 0.00 | 0.00 | 0.254535E+10 | 0.00 | 0.00 |
May | 30172072.11 | 0.00 | 0.00 | 0.401847E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.592415E+10 | 0.00 | 0.00 |
July | 301945.07 | 0.00 | 0.00 | 0.924850E+10 | 0.00 | 0.00 |
August | 767349.76 | 0.00 | 0.00 | 0.116158E+11 | 0.00 | 0.00 |
September | 646717.99 | 0.00 | 0.00 | 0.542539E+10 | 0.00 | 0.00 |
October | 0.371022E+09 | 0.00 | 0.00 | 0.206021E+10 | 0.00 | 0.00 |
November | 0.474519E+10 | 0.00 | 0.00 | 0.137551E+10 | 0.00 | 0.00 |
December | 0.103552E+11 | 0.00 | 0.00 | 0.131604E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.393999E+11 | 0.00 | 0.00 | 0.478125E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129322E+10 | 0.00 | 0.00 |
Maximum of Months | 0.144243E+11 | 0.00 | 0.00 | 0.116158E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.218770E+11 | 0.00 | 0.00 | 0.154413E+10 | 0.00 | 0.00 |
February | 0.122293E+11 | 0.00 | 0.00 | 0.136272E+10 | 0.00 | 0.00 |
March | 0.471250E+10 | 0.00 | 0.00 | 0.160039E+10 | 0.00 | 0.00 |
April | 0.143160E+10 | 0.00 | 0.00 | 0.252975E+10 | 0.00 | 0.00 |
May | 0.193440E+09 | 0.00 | 0.00 | 0.391678E+10 | 0.00 | 0.00 |
June | 2572500.20 | 0.00 | 0.00 | 0.583567E+10 | 0.00 | 0.00 |
July | 310478.86 | 0.00 | 0.00 | 0.930419E+10 | 0.00 | 0.00 |
August | 788566.15 | 0.00 | 0.00 | 0.116468E+11 | 0.00 | 0.00 |
September | 71821704.24 | 0.00 | 0.00 | 0.514878E+10 | 0.00 | 0.00 |
October | 0.174203E+10 | 0.00 | 0.00 | 0.190046E+10 | 0.00 | 0.00 |
November | 0.933338E+10 | 0.00 | 0.00 | 0.140481E+10 | 0.00 | 0.00 |
December | 0.177114E+11 | 0.00 | 0.00 | 0.138886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.693062E+11 | 0.00 | 0.00 | 0.475833E+11 | 0.00 | 0.00 |
Minimum of Months | 310478.86 | 0.00 | 0.00 | 0.136272E+10 | 0.00 | 0.00 |
Maximum of Months | 0.218770E+11 | 0.00 | 0.00 | 0.116468E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140188E+10 | 2824018.97 | 0.155596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128243E+10 | 0.211916E+09 | 0.812192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175009E+10 | 0.321181E+09 | 0.306606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202618E+10 | 0.353408E+10 | 0.126538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274398E+10 | 0.770096E+10 | 0.674940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335534E+10 | 0.146596E+11 | 0.347789E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.419019E+10 | 0.281712E+11 | 88421131.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.491926E+10 | 0.380933E+11 | 91284135.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327534E+10 | 0.139892E+11 | 0.310094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215670E+10 | 0.180820E+10 | 0.100663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148443E+10 | 0.366284E+09 | 0.495082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136608E+10 | 0.00 | 0.104269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299519E+11 | 0.108859E+12 | 0.459099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128243E+10 | 0.00 | 88421131.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.491926E+10 | 0.380933E+11 | 0.155596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138850E+10 | 0.00 | 0.144243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124087E+10 | 0.210345E+09 | 0.709324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151928E+10 | 0.322623E+09 | 0.188948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173607E+10 | 0.350365E+10 | 0.489501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233819E+10 | 0.734009E+10 | 30172072.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.284381E+10 | 0.134516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353208E+10 | 0.253931E+11 | 301945.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.403351E+10 | 0.334197E+11 | 767349.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261438E+10 | 0.124764E+11 | 646717.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167497E+10 | 0.161693E+10 | 0.371022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128630E+10 | 0.383128E+09 | 0.474519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131602E+10 | 43020.58 | 0.103552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255240E+11 | 0.981177E+11 | 0.393999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403351E+10 | 0.334197E+11 | 0.144243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154405E+10 | 306623.24 | 0.218770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130861E+10 | 0.215832E+09 | 0.122293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151616E+10 | 0.329246E+09 | 0.471250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165988E+10 | 0.375525E+10 | 0.143160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215759E+10 | 0.765878E+10 | 0.193440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.259346E+10 | 0.140954E+11 | 2572500.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323365E+10 | 0.268474E+11 | 310478.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363708E+10 | 0.350887E+11 | 788566.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230392E+10 | 0.125461E+11 | 71821704.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154344E+10 | 0.147745E+10 | 0.174203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131197E+10 | 0.394950E+09 | 0.933338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138885E+10 | 35537.80 | 0.177114E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241987E+11 | 0.102409E+12 | 0.693062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130861E+10 | 35537.80 | 310478.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363708E+10 | 0.350887E+11 | 0.218770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140188E+10 | 0.155596E+11 | 0.00 | 0.00 | 752627.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128243E+10 | 0.812192E+10 | 0.00 | 0.00 | 52919225.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175009E+10 | 0.306606E+10 | 0.00 | 0.00 | 82529779.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202618E+10 | 0.126538E+10 | 0.00 | 0.00 | 0.816437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.274398E+10 | 0.674940E+09 | 0.00 | 0.00 | 0.176350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335534E+10 | 0.347789E+09 | 0.00 | 0.00 | 0.334714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.419019E+10 | 88421131.61 | 0.00 | 0.00 | 0.632488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.491926E+10 | 91284135.44 | 0.00 | 0.00 | 0.860712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327534E+10 | 0.310094E+09 | 0.00 | 0.00 | 0.314005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215670E+10 | 0.100663E+10 | 0.00 | 0.00 | 0.430126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148443E+10 | 0.495082E+10 | 0.00 | 0.00 | 86568535.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136608E+10 | 0.104269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299519E+11 | 0.459099E+11 | 0.00 | 0.00 | 0.246520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128243E+10 | 88421131.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.491926E+10 | 0.155596E+11 | 0.00 | 0.00 | 0.860712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138850E+10 | 0.144243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124087E+10 | 0.709324E+10 | 0.00 | 0.00 | 52355320.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151928E+10 | 0.188948E+10 | 0.00 | 0.00 | 82059170.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173607E+10 | 0.489501E+09 | 0.00 | 0.00 | 0.809283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233819E+10 | 30172072.11 | 0.00 | 0.00 | 0.168028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.284381E+10 | 0.00 | 0.00 | 0.00 | 0.308035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353208E+10 | 301945.07 | 0.00 | 0.00 | 0.571642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.403351E+10 | 767349.76 | 0.00 | 0.00 | 0.758227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261438E+10 | 646717.99 | 0.00 | 0.00 | 0.281100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167497E+10 | 0.371022E+09 | 0.00 | 0.00 | 0.385239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128630E+10 | 0.474519E+10 | 0.00 | 0.00 | 89209910.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131602E+10 | 0.103552E+11 | 0.00 | 0.00 | 11655.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255240E+11 | 0.393999E+11 | 0.00 | 0.00 | 0.222885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403351E+10 | 0.144243E+11 | 0.00 | 0.00 | 0.758227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154405E+10 | 0.218770E+11 | 0.00 | 0.00 | 83162.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130861E+10 | 0.122293E+11 | 0.00 | 0.00 | 54103964.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151616E+10 | 0.471250E+10 | 0.00 | 0.00 | 84226408.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165988E+10 | 0.143160E+10 | 0.00 | 0.00 | 0.869864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215759E+10 | 0.193440E+09 | 0.00 | 0.00 | 0.175919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.259346E+10 | 2572500.20 | 0.00 | 0.00 | 0.324221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.323365E+10 | 310478.86 | 0.00 | 0.00 | 0.607053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363708E+10 | 788566.15 | 0.00 | 0.00 | 0.800970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230392E+10 | 71821704.24 | 0.00 | 0.00 | 0.284486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154344E+10 | 0.174203E+10 | 0.00 | 0.00 | 0.357023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131197E+10 | 0.933338E+10 | 0.00 | 0.00 | 92838638.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138885E+10 | 0.177114E+11 | 0.00 | 0.00 | 9641.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241987E+11 | 0.693062E+11 | 0.00 | 0.00 | 0.233847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130861E+10 | 310478.86 | 0.00 | 0.00 | 9641.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363708E+10 | 0.218770E+11 | 0.00 | 0.00 | 0.800970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.783238E+10 | 0.00 | 0.00 | 6136908.48 | 0.00 | 0.216497E+09 | 0.476535E+10 | 0.00 | 0.29 |
February | 0.431826E+10 | 0.00 | 0.00 | 13811012.79 | 0.00 | 0.00 | 0.852667E+10 | 0.00 | 0.36 |
March | 0.138664E+10 | 0.00 | 0.00 | 30350895.51 | 0.00 | 0.00 | 0.164354E+11 | 0.00 | 0.50 |
April | 0.786118E+09 | 10026514.59 | 0.00 | 35067573.36 | 0.00 | 0.00 | 0.176646E+11 | 0.00 | 0.64 |
May | 0.930341E+09 | 7959366.88 | 0.00 | 43656496.81 | 0.00 | 0.00 | 0.217186E+11 | 0.00 | 0.95 |
June | 0.652225E+09 | 9691042.89 | 0.00 | 45965460.58 | 1717434.68 | 0.00 | 0.207027E+11 | 0.00 | 1.14 |
July | 0.614669E+09 | 0.135134E+09 | 0.00 | 42129447.86 | 12295558.73 | 0.00 | 0.150062E+11 | 0.00 | 1.09 |
August | 0.445846E+09 | 0.390215E+09 | 0.00 | 41673229.60 | 14930256.71 | 0.00 | 0.131454E+11 | 0.00 | 1.07 |
September | 0.757857E+09 | 7679496.62 | 0.00 | 43285947.41 | 0.00 | 0.00 | 0.189699E+11 | 0.00 | 1.05 |
October | 0.759733E+09 | 0.00 | 0.00 | 35675171.67 | 0.00 | 0.00 | 0.195577E+11 | 0.00 | 0.70 |
November | 0.278769E+10 | 0.00 | 0.00 | 20676865.88 | 0.00 | 0.00 | 0.120863E+11 | 0.00 | 0.42 |
December | 0.581612E+10 | 0.00 | 0.00 | 12194316.14 | 0.00 | 0.00 | 0.751163E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.270879E+11 | 0.560705E+09 | 0.00 | 0.370623E+09 | 28943250.11 | 0.216497E+09 | 0.176090E+12 | 0.00 | 0.71 |
Minimum of Months | 0.445846E+09 | 0.00 | 0.00 | 6136908.48 | 0.00 | 0.00 | 0.476535E+10 | 0.00 | 0.29 |
Maximum of Months | 0.783238E+10 | 0.390215E+09 | 0.00 | 45965460.58 | 14930256.71 | 0.216497E+09 | 0.217186E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512330E+09 | 0.00 | 0.00 | 0.28 |
February | 0.100646E+11 | 0.00 | 0.00 | 249875.58 | 0.00 | 57011616.27 | 0.585083E+09 | 0.00 | 0.31 |
March | 0.892568E+10 | 0.00 | 0.00 | 3030680.43 | 0.00 | 3205007.19 | 0.361100E+10 | 0.00 | 0.36 |
April | 0.545944E+10 | 4813818.14 | 0.00 | 10073628.23 | 5489656.79 | 0.00 | 0.676329E+10 | 0.00 | 0.43 |
May | 0.342435E+10 | 5915853.49 | 0.00 | 20491021.28 | 0.00 | 0.00 | 0.114817E+11 | 0.00 | 0.63 |
June | 0.184224E+10 | 5584015.70 | 0.00 | 25228057.86 | 1860008.12 | 0.00 | 0.125201E+11 | 0.00 | 0.78 |
July | 0.138630E+10 | 93299430.48 | 0.00 | 24412579.11 | 10096857.32 | 0.00 | 0.914075E+10 | 0.00 | 0.75 |
August | 0.109399E+10 | 0.284057E+09 | 0.00 | 23980490.99 | 11767126.80 | 0.00 | 0.800430E+10 | 0.00 | 0.73 |
September | 0.271895E+10 | 149757.52 | 0.00 | 20399936.99 | 5494109.56 | 0.00 | 0.968944E+10 | 0.00 | 0.68 |
October | 0.590679E+10 | 0.00 | 0.00 | 9197057.45 | 0.00 | 0.00 | 0.678806E+10 | 0.00 | 0.45 |
November | 0.945847E+10 | 0.00 | 0.00 | 1198179.95 | 0.00 | 7131877.95 | 0.151608E+10 | 0.00 | 0.32 |
December | 0.111736E+11 | 0.00 | 0.00 | 21274.97 | 0.00 | 0.112862E+09 | 0.153525E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.726973E+11 | 0.393819E+09 | 0.00 | 0.138283E+09 | 34707758.59 | 0.692540E+09 | 0.702534E+11 | 0.00 | 0.50 |
Minimum of Months | 0.109399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.112428E+11 | 0.284057E+09 | 0.00 | 25228057.86 | 11767126.80 | 0.512330E+09 | 0.125201E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.945332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159052E+10 | 0.00 | 0.00 | 0.27 |
February | 0.931075E+10 | 0.00 | 0.00 | 47679.65 | 0.00 | 0.628307E+09 | 0.144068E+09 | 0.00 | 0.30 |
March | 0.105219E+11 | 0.00 | 0.00 | 797922.39 | 0.00 | 74263281.21 | 0.138311E+10 | 0.00 | 0.36 |
April | 0.701664E+10 | 891622.67 | 0.00 | 5987295.71 | 262772.28 | 5501645.60 | 0.470250E+10 | 0.00 | 0.42 |
May | 0.466089E+10 | 2158128.96 | 0.00 | 16151319.30 | 0.00 | 0.00 | 0.964164E+10 | 0.00 | 0.61 |
June | 0.303869E+10 | 1812764.12 | 0.00 | 21233087.59 | 1235365.57 | 0.00 | 0.109586E+11 | 0.00 | 0.76 |
July | 0.223058E+10 | 76659942.58 | 0.00 | 20622244.14 | 14087425.87 | 0.00 | 0.806275E+10 | 0.00 | 0.76 |
August | 0.184524E+10 | 0.217537E+09 | 0.00 | 19841290.32 | 26093016.45 | 0.00 | 0.642057E+10 | 0.00 | 0.72 |
September | 0.432947E+10 | 0.00 | 0.00 | 13651410.77 | 2029895.89 | 0.00 | 0.687234E+10 | 0.00 | 0.64 |
October | 0.797210E+10 | 0.00 | 0.00 | 3766236.95 | 0.00 | 11176185.33 | 0.334571E+10 | 0.00 | 0.42 |
November | 0.971856E+10 | 0.00 | 0.00 | 10337.27 | 0.00 | 0.281641E+09 | 67495796.14 | 0.00 | 0.31 |
December | 0.949580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108334E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.795940E+11 | 0.299060E+09 | 0.00 | 0.102109E+09 | 43708476.05 | 0.367475E+10 | 0.515988E+11 | 0.00 | 0.49 |
Minimum of Months | 0.184524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.105219E+11 | 0.217537E+09 | 0.00 | 21233087.59 | 26093016.45 | 0.159052E+10 | 0.109586E+11 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.613854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175876E+10 | 0.00 | 0.00 | 0.27 |
February | 0.101965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112799E+10 | 0.00 | 0.00 | 0.31 |
March | 0.216263E+10 | 0.00 | 0.00 | 1030.12 | 0.00 | 0.356050E+09 | 9307991.31 | 0.00 | 0.35 |
April | 0.174998E+10 | 242758.65 | 0.00 | 873557.10 | 55303.95 | 97146439.70 | 0.586898E+09 | 0.00 | 0.42 |
May | 0.129104E+10 | 784406.52 | 0.00 | 3323394.27 | 0.00 | 6409447.19 | 0.183075E+10 | 0.00 | 0.65 |
June | 0.786760E+09 | 537227.04 | 0.00 | 4972668.60 | 259999.25 | 0.00 | 0.234369E+10 | 0.00 | 0.85 |
July | 0.547103E+09 | 23222937.25 | 0.00 | 5157859.57 | 2964887.69 | 0.00 | 0.186434E+10 | 0.00 | 0.89 |
August | 0.532437E+09 | 64023874.49 | 0.00 | 4350363.40 | 5491625.23 | 0.00 | 0.127128E+10 | 0.00 | 0.79 |
September | 0.127766E+10 | 427218.81 | 0.00 | 2267555.60 | 0.00 | 2911650.36 | 0.103491E+10 | 0.00 | 0.64 |
October | 0.194495E+10 | 0.00 | 0.00 | 268653.55 | 0.00 | 0.131668E+09 | 0.246441E+09 | 0.00 | 0.40 |
November | 0.126819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865409E+09 | 0.00 | 0.00 | 0.31 |
December | 0.707620E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155141E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.139019E+11 | 89238422.76 | 0.00 | 21215082.20 | 8771816.13 | 0.589776E+10 | 0.918761E+10 | 0.00 | 0.52 |
Minimum of Months | 0.532437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.216263E+10 | 64023874.49 | 0.00 | 5157859.57 | 5491625.23 | 0.175876E+10 | 0.234369E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.766436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151470E+10 | 0.00 | 0.00 | 0.42 |
February | 0.113470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935029E+09 | 0.00 | 0.00 | 0.47 |
March | 0.199274E+10 | 0.00 | 0.00 | 268402.60 | 0.00 | 0.259385E+09 | 0.213310E+09 | 0.00 | 0.55 |
April | 0.126379E+10 | 212492.18 | 0.00 | 2224641.27 | 53550.54 | 53917090.89 | 0.133589E+10 | 0.00 | 0.73 |
May | 0.114639E+10 | 714910.67 | 0.00 | 3992239.65 | 0.00 | 7777213.30 | 0.214448E+10 | 0.00 | 1.08 |
June | 0.684525E+09 | 374159.94 | 0.00 | 6024810.53 | 251755.99 | 0.00 | 0.293231E+10 | 0.00 | 1.48 |
July | 0.515059E+09 | 18784980.50 | 0.00 | 6154386.82 | 2828472.62 | 0.00 | 0.209414E+10 | 0.00 | 1.47 |
August | 0.423410E+09 | 56912017.12 | 0.00 | 6008906.69 | 3599177.77 | 0.00 | 0.160556E+10 | 0.00 | 1.43 |
September | 0.114871E+10 | 485604.14 | 0.00 | 3445296.49 | 0.00 | 2164091.67 | 0.146471E+10 | 0.00 | 1.14 |
October | 0.163072E+10 | 0.00 | 0.00 | 795589.88 | 0.00 | 0.114921E+09 | 0.617600E+09 | 0.00 | 0.65 |
November | 0.131475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746788E+09 | 0.00 | 0.00 | 0.47 |
December | 0.846713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133354E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.128679E+11 | 77484164.54 | 0.00 | 28914273.93 | 6732956.92 | 0.496822E+10 | 0.124080E+11 | 0.00 | 0.86 |
Minimum of Months | 0.423410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.199274E+10 | 56912017.12 | 0.00 | 6154386.82 | 3599177.77 | 0.151470E+10 | 0.293231E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150241E+10 | 0.00 | 0.00 | 287581.84 | 0.00 | 0.179349E+10 | 0.153450E+09 | 0.00 | 0.40 |
February | 0.162588E+10 | 0.00 | 0.00 | 1706151.44 | 0.00 | 0.991164E+09 | 0.835761E+09 | 0.00 | 0.50 |
March | 0.219145E+10 | 0.00 | 0.00 | 3847862.87 | 0.00 | 0.369963E+09 | 0.213885E+10 | 0.00 | 0.67 |
April | 0.176686E+10 | 829417.84 | 0.00 | 5139224.06 | 0.00 | 0.133667E+09 | 0.278809E+10 | 0.00 | 0.85 |
May | 0.175688E+10 | 1478291.25 | 0.00 | 6747665.84 | 0.00 | 12120911.55 | 0.348732E+10 | 0.00 | 1.10 |
June | 0.134424E+10 | 679621.88 | 0.00 | 7148141.31 | 376872.25 | 0.00 | 0.332382E+10 | 0.00 | 1.27 |
July | 0.928770E+09 | 42364020.48 | 0.00 | 7693626.37 | 1190894.92 | 0.00 | 0.269690E+10 | 0.00 | 1.37 |
August | 0.829829E+09 | 0.130534E+09 | 0.00 | 7423798.01 | 2101688.16 | 0.00 | 0.197451E+10 | 0.00 | 1.31 |
September | 0.154191E+10 | 2432663.00 | 0.00 | 8414346.99 | 0.00 | 5150331.74 | 0.323279E+10 | 0.00 | 1.46 |
October | 0.196561E+10 | 0.00 | 0.00 | 4553000.22 | 0.00 | 0.144261E+09 | 0.275477E+10 | 0.00 | 0.88 |
November | 0.193437E+10 | 0.00 | 0.00 | 871828.27 | 0.00 | 0.929150E+09 | 0.354635E+09 | 0.00 | 0.49 |
December | 0.138875E+10 | 0.00 | 0.00 | 889632.35 | 0.00 | 0.157454E+10 | 0.431801E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.187770E+11 | 0.178318E+09 | 0.00 | 54722859.57 | 3669455.34 | 0.595351E+10 | 0.241727E+11 | 0.00 | 0.89 |
Minimum of Months | 0.829829E+09 | 0.00 | 0.00 | 287581.84 | 0.00 | 0.00 | 0.153450E+09 | 0.00 | 0.40 |
Maximum of Months | 0.219145E+10 | 0.130534E+09 | 0.00 | 8414346.99 | 2101688.16 | 0.179349E+10 | 0.348732E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173480E+10 | 0.00 | 0.00 | 0.45 |
February | 0.113130E+10 | 0.00 | 0.00 | 84094.65 | 0.00 | 0.106535E+10 | 67871661.85 | 0.00 | 0.51 |
March | 0.198763E+10 | 0.00 | 0.00 | 600834.54 | 0.00 | 0.376851E+09 | 0.425969E+09 | 0.00 | 0.62 |
April | 0.169639E+10 | 433290.82 | 0.00 | 1977718.52 | 0.00 | 0.111668E+09 | 0.107895E+10 | 0.00 | 0.81 |
May | 0.146002E+10 | 623216.45 | 0.00 | 4732518.37 | 0.00 | 9496543.16 | 0.204628E+10 | 0.00 | 1.21 |
June | 0.108256E+10 | 1316098.75 | 0.00 | 4942950.56 | 274953.38 | 0.00 | 0.206847E+10 | 0.00 | 1.43 |
July | 0.686963E+09 | 40957209.94 | 0.00 | 6490999.45 | 1486802.40 | 0.00 | 0.186824E+10 | 0.00 | 1.62 |
August | 0.669858E+09 | 84345343.80 | 0.00 | 4709249.78 | 4533836.93 | 0.00 | 0.115138E+10 | 0.00 | 1.30 |
September | 0.141343E+10 | 766475.77 | 0.00 | 3511721.74 | 0.00 | 5466965.48 | 0.129218E+10 | 0.00 | 1.26 |
October | 0.192587E+10 | 0.00 | 0.00 | 817785.46 | 0.00 | 0.151281E+09 | 0.546296E+09 | 0.00 | 0.73 |
November | 0.136277E+10 | 0.00 | 0.00 | 24113.46 | 0.00 | 0.885402E+09 | 2476314.13 | 0.00 | 0.52 |
December | 0.848292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152976E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.150178E+11 | 0.128442E+09 | 0.00 | 27891986.54 | 6295592.71 | 0.587007E+10 | 0.105481E+11 | 0.00 | 0.91 |
Minimum of Months | 0.669858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.198763E+10 | 84345343.80 | 0.00 | 6490999.45 | 4533836.93 | 0.173480E+10 | 0.206847E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.925782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170687E+10 | 0.00 | 0.00 | 0.28 |
February | 0.144624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942306E+09 | 0.00 | 0.00 | 0.31 |
March | 0.258012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157408E+09 | 0.00 | 0.00 | 0.36 |
April | 0.229307E+10 | 850294.03 | 0.00 | 161907.30 | 659968.44 | 26207401.49 | 0.124142E+09 | 0.00 | 0.40 |
May | 0.159397E+10 | 1245882.91 | 0.00 | 1815109.47 | 0.00 | 0.00 | 0.111822E+10 | 0.00 | 0.55 |
June | 0.842323E+09 | 1458247.48 | 0.00 | 3655674.18 | 361315.66 | 0.00 | 0.177864E+10 | 0.00 | 0.70 |
July | 0.500584E+09 | 23577035.07 | 0.00 | 4266531.00 | 2586752.22 | 0.00 | 0.155650E+10 | 0.00 | 0.73 |
August | 0.526984E+09 | 69503521.84 | 0.00 | 3681374.86 | 3141042.67 | 0.00 | 0.119042E+10 | 0.00 | 0.68 |
September | 0.131829E+10 | 598286.11 | 0.00 | 2029956.14 | 520224.41 | 0.00 | 0.100139E+10 | 0.00 | 0.60 |
October | 0.231351E+10 | 0.00 | 0.00 | 283421.08 | 0.00 | 3300364.69 | 0.285245E+09 | 0.00 | 0.42 |
November | 0.209282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346232E+09 | 0.00 | 0.00 | 0.32 |
December | 0.134324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120910E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.177769E+11 | 97233267.44 | 0.00 | 15893974.04 | 7269303.41 | 0.439143E+10 | 0.705455E+10 | 0.00 | 0.47 |
Minimum of Months | 0.500584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.258012E+10 | 69503521.84 | 0.00 | 4266531.00 | 3141042.67 | 0.170687E+10 | 0.177864E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.883981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127230E+10 | 0.00 | 0.00 | 0.36 |
February | 0.136990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578491E+09 | 0.00 | 0.00 | 0.40 |
March | 0.203047E+10 | 0.00 | 0.00 | 155612.54 | 0.00 | 68178223.65 | 0.137602E+09 | 0.00 | 0.47 |
April | 0.123659E+10 | 1120125.43 | 0.00 | 1714162.27 | 537607.15 | 9860464.31 | 0.100815E+10 | 0.00 | 0.60 |
May | 0.980684E+09 | 1426998.06 | 0.00 | 3224445.22 | 0.00 | 0.00 | 0.169073E+10 | 0.00 | 0.88 |
June | 0.469206E+09 | 1289649.40 | 0.00 | 5517175.22 | 294326.02 | 0.00 | 0.253453E+10 | 0.00 | 1.26 |
July | 0.333927E+09 | 25491559.54 | 0.00 | 5536289.93 | 2071998.37 | 0.00 | 0.186740E+10 | 0.00 | 1.24 |
August | 0.283932E+09 | 74435176.65 | 0.00 | 5650438.31 | 1568025.29 | 0.00 | 0.162080E+10 | 0.00 | 1.25 |
September | 0.867882E+09 | 1156036.47 | 0.00 | 3632510.86 | 0.00 | 0.00 | 0.154943E+10 | 0.00 | 1.03 |
October | 0.154475E+10 | 0.00 | 0.00 | 1096352.35 | 0.00 | 2041756.18 | 0.759860E+09 | 0.00 | 0.60 |
November | 0.172344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266377E+09 | 0.00 | 0.00 | 0.42 |
December | 0.117535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912201E+09 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.129001E+11 | 0.104920E+09 | 0.00 | 26526986.70 | 4471956.83 | 0.310945E+10 | 0.111685E+11 | 0.00 | 0.74 |
Minimum of Months | 0.283932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.203047E+10 | 74435176.65 | 0.00 | 5650438.31 | 2071998.37 | 0.127230E+10 | 0.253453E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.789032E+09 | 0.00 | 0.00 | 4953.98 | 0.00 | 0.331744E+10 | 12560784.49 | 0.00 | 0.44 |
February | 0.141567E+10 | 0.00 | 0.00 | 239794.16 | 0.00 | 0.199464E+10 | 0.173986E+09 | 0.00 | 0.47 |
March | 0.223202E+10 | 0.00 | 0.00 | 844011.77 | 0.00 | 0.122139E+10 | 0.610098E+09 | 0.00 | 0.54 |
April | 0.205190E+10 | 4567710.68 | 0.00 | 1529403.46 | 0.00 | 0.675907E+09 | 0.798796E+09 | 0.00 | 0.61 |
May | 0.205258E+10 | 2760501.53 | 0.00 | 2440688.63 | 0.00 | 0.438609E+09 | 0.120742E+10 | 0.00 | 0.79 |
June | 0.156063E+10 | 2232918.33 | 0.00 | 3440642.42 | 437287.45 | 0.238425E+09 | 0.141858E+10 | 0.00 | 0.90 |
July | 0.862194E+09 | 49888841.74 | 0.00 | 5061859.23 | 2902836.08 | 70042862.50 | 0.160675E+10 | 0.00 | 1.00 |
August | 0.827022E+09 | 0.164820E+09 | 0.00 | 5259295.33 | 2163918.70 | 61379661.25 | 0.133010E+10 | 0.00 | 1.03 |
September | 0.140345E+10 | 5049867.81 | 0.00 | 6152421.95 | 0.00 | 0.202474E+09 | 0.214482E+10 | 0.00 | 1.18 |
October | 0.196940E+10 | 0.00 | 0.00 | 2809807.77 | 0.00 | 0.585383E+09 | 0.176131E+10 | 0.00 | 0.74 |
November | 0.182239E+10 | 0.00 | 0.00 | 262748.77 | 0.00 | 0.170988E+10 | 98814102.15 | 0.00 | 0.48 |
December | 0.107117E+10 | 0.00 | 0.00 | 193888.09 | 0.00 | 0.274845E+10 | 0.140125E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.180575E+11 | 0.229320E+09 | 0.00 | 28239515.56 | 5504042.23 | 0.132640E+11 | 0.113034E+11 | 0.00 | 0.72 |
Minimum of Months | 0.789032E+09 | 0.00 | 0.00 | 4953.98 | 0.00 | 61379661.25 | 12560784.49 | 0.00 | 0.42 |
Maximum of Months | 0.223202E+10 | 0.164820E+09 | 0.00 | 6152421.95 | 2902836.08 | 0.331744E+10 | 0.214482E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.906718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147168E+10 | 0.00 | 0.00 | 0.40 |
February | 0.146646E+10 | 0.00 | 0.00 | 35478.27 | 0.00 | 0.650599E+09 | 34280645.76 | 0.00 | 0.45 |
March | 0.218045E+10 | 0.00 | 0.00 | 283391.97 | 0.00 | 0.129632E+09 | 0.191363E+09 | 0.00 | 0.53 |
April | 0.169005E+10 | 1677010.85 | 0.00 | 1232977.29 | 240603.84 | 23047080.98 | 0.646735E+09 | 0.00 | 0.64 |
May | 0.122134E+10 | 1210750.59 | 0.00 | 3486895.84 | 0.00 | 0.00 | 0.154857E+10 | 0.00 | 0.96 |
June | 0.747942E+09 | 3588460.04 | 0.00 | 4237855.00 | 324939.21 | 0.00 | 0.178662E+10 | 0.00 | 1.17 |
July | 0.372482E+09 | 42683522.40 | 0.00 | 5660920.77 | 627416.33 | 0.00 | 0.176409E+10 | 0.00 | 1.34 |
August | 0.392816E+09 | 95352626.21 | 0.00 | 4614682.10 | 1972936.08 | 0.00 | 0.126670E+10 | 0.00 | 1.12 |
September | 0.995811E+09 | 1575915.84 | 0.00 | 3511443.46 | 0.00 | 0.00 | 0.138800E+10 | 0.00 | 1.09 |
October | 0.189625E+10 | 0.00 | 0.00 | 862950.18 | 0.00 | 3610918.27 | 0.590315E+09 | 0.00 | 0.66 |
November | 0.188235E+10 | 0.00 | 0.00 | 17347.51 | 0.00 | 0.306237E+09 | 8337218.34 | 0.00 | 0.46 |
December | 0.129772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100598E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.150504E+11 | 0.146088E+09 | 0.00 | 23943942.40 | 3165895.46 | 0.359079E+10 | 0.922501E+10 | 0.00 | 0.77 |
Minimum of Months | 0.372482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.218045E+10 | 95352626.21 | 0.00 | 5660920.77 | 1972936.08 | 0.147168E+10 | 0.178662E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143545E+10 | 0.00 | 0.00 | 0.28 |
February | 0.162969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635474E+09 | 0.00 | 0.00 | 0.31 |
March | 0.249871E+10 | 0.00 | 0.00 | 10881.13 | 0.00 | 97562565.96 | 38737065.75 | 0.00 | 0.35 |
April | 0.175064E+10 | 1320131.78 | 0.00 | 1105579.59 | 1156414.42 | 12841048.22 | 0.723262E+09 | 0.00 | 0.42 |
May | 0.111206E+10 | 2101362.25 | 0.00 | 3945638.22 | 0.00 | 0.00 | 0.203354E+10 | 0.00 | 0.66 |
June | 0.602950E+09 | 1719383.61 | 0.00 | 5636322.58 | 391816.88 | 0.00 | 0.252868E+10 | 0.00 | 0.86 |
July | 0.436875E+09 | 28600204.52 | 0.00 | 5565678.30 | 2126936.50 | 0.00 | 0.195706E+10 | 0.00 | 0.87 |
August | 0.418845E+09 | 84285051.80 | 0.00 | 4826486.50 | 2478784.30 | 0.00 | 0.149349E+10 | 0.00 | 0.79 |
September | 0.110261E+10 | 1194875.55 | 0.00 | 2967045.92 | 0.00 | 0.00 | 0.132291E+10 | 0.00 | 0.66 |
October | 0.204945E+10 | 0.00 | 0.00 | 531961.81 | 0.00 | 17941106.14 | 0.429370E+09 | 0.00 | 0.41 |
November | 0.189652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419573E+09 | 0.00 | 0.00 | 0.32 |
December | 0.130916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111457E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.158654E+11 | 0.119221E+09 | 0.00 | 24589594.05 | 6153952.10 | 0.373341E+10 | 0.105270E+11 | 0.00 | 0.52 |
Minimum of Months | 0.418845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.249871E+10 | 84285051.80 | 0.00 | 5636322.58 | 2478784.30 | 0.143545E+10 | 0.252868E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137024E+10 | 0.00 | 0.00 | 0.44 |
February | 0.168201E+10 | 0.00 | 0.00 | 175.02 | 0.00 | 0.580220E+09 | 1261452.70 | 0.00 | 0.49 |
March | 0.230774E+10 | 0.00 | 0.00 | 452856.55 | 0.00 | 64325603.17 | 0.318635E+09 | 0.00 | 0.57 |
April | 0.137825E+10 | 1133825.64 | 0.00 | 2554737.92 | 1154963.24 | 13952509.51 | 0.143741E+10 | 0.00 | 0.75 |
May | 0.112542E+10 | 1861601.86 | 0.00 | 4263980.37 | 0.00 | 283551.80 | 0.219773E+10 | 0.00 | 1.09 |
June | 0.613356E+09 | 1174361.53 | 0.00 | 6261792.71 | 391325.19 | 0.00 | 0.297135E+10 | 0.00 | 1.46 |
July | 0.491710E+09 | 23803670.08 | 0.00 | 6362722.19 | 2101321.98 | 0.00 | 0.209457E+10 | 0.00 | 1.43 |
August | 0.406719E+09 | 73384316.28 | 0.00 | 6169173.29 | 1275361.09 | 0.00 | 0.174894E+10 | 0.00 | 1.39 |
September | 0.113139E+10 | 1286212.32 | 0.00 | 3771883.44 | 0.00 | 0.00 | 0.164496E+10 | 0.00 | 1.17 |
October | 0.185812E+10 | 0.00 | 0.00 | 1108551.99 | 0.00 | 21479200.38 | 0.769806E+09 | 0.00 | 0.69 |
November | 0.188283E+10 | 0.00 | 0.00 | 723.81 | 0.00 | 0.429114E+09 | 4604770.01 | 0.00 | 0.50 |
December | 0.131643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111163E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.153187E+11 | 0.102644E+09 | 0.00 | 30946597.28 | 4922971.51 | 0.359125E+10 | 0.131893E+11 | 0.00 | 0.87 |
Minimum of Months | 0.406719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.230774E+10 | 73384316.28 | 0.00 | 6362722.19 | 2101321.98 | 0.137024E+10 | 0.297135E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193161E+10 | 0.00 | 0.00 | 437191.11 | 0.00 | 0.134159E+10 | 0.260492E+09 | 0.00 | 0.39 |
February | 0.205700E+10 | 0.00 | 0.00 | 2206979.91 | 0.00 | 0.546577E+09 | 0.101872E+10 | 0.00 | 0.50 |
March | 0.245743E+10 | 0.00 | 0.00 | 4595773.23 | 0.00 | 97811886.66 | 0.233239E+10 | 0.00 | 0.68 |
April | 0.177427E+10 | 7639710.43 | 0.00 | 5577200.99 | 736.32 | 22184472.70 | 0.286007E+10 | 0.00 | 0.83 |
May | 0.151040E+10 | 3925467.39 | 0.00 | 7353956.50 | 0.00 | 0.00 | 0.353896E+10 | 0.00 | 1.10 |
June | 0.107170E+10 | 2146453.53 | 0.00 | 7642420.14 | 544814.08 | 0.00 | 0.335305E+10 | 0.00 | 1.24 |
July | 0.777071E+09 | 49448321.02 | 0.00 | 7725206.14 | 2645226.27 | 0.00 | 0.259416E+10 | 0.00 | 1.30 |
August | 0.686203E+09 | 0.164407E+09 | 0.00 | 7501289.45 | 1404497.95 | 0.00 | 0.208705E+10 | 0.00 | 1.24 |
September | 0.133059E+10 | 6626661.94 | 0.00 | 8972545.42 | 0.00 | 0.00 | 0.334782E+10 | 0.00 | 1.45 |
October | 0.205970E+10 | 0.00 | 0.00 | 5499224.47 | 0.00 | 15877711.82 | 0.307690E+10 | 0.00 | 0.92 |
November | 0.251829E+10 | 0.00 | 0.00 | 1212069.06 | 0.00 | 0.378806E+09 | 0.520617E+09 | 0.00 | 0.49 |
December | 0.196334E+10 | 0.00 | 0.00 | 1275256.76 | 0.00 | 0.105595E+10 | 0.596077E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.201376E+11 | 0.234194E+09 | 0.00 | 59999113.18 | 4595274.61 | 0.345879E+10 | 0.255863E+11 | 0.00 | 0.88 |
Minimum of Months | 0.686203E+09 | 0.00 | 0.00 | 437191.11 | 0.00 | 0.00 | 0.260492E+09 | 0.00 | 0.39 |
Maximum of Months | 0.251829E+10 | 0.164407E+09 | 0.00 | 8972545.42 | 2645226.27 | 0.134159E+10 | 0.353896E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137331E+10 | 0.00 | 0.00 | 0.45 |
February | 0.165066E+10 | 0.00 | 0.00 | 120434.76 | 0.00 | 0.564772E+09 | 0.104410E+09 | 0.00 | 0.50 |
March | 0.223025E+10 | 0.00 | 0.00 | 720024.36 | 0.00 | 0.113068E+09 | 0.479585E+09 | 0.00 | 0.61 |
April | 0.170684E+10 | 3288080.46 | 0.00 | 2064384.26 | 302065.84 | 25140281.07 | 0.109532E+10 | 0.00 | 0.78 |
May | 0.119392E+10 | 1782949.19 | 0.00 | 5147749.01 | 0.00 | 289491.61 | 0.213192E+10 | 0.00 | 1.18 |
June | 0.826448E+09 | 4223192.00 | 0.00 | 5333823.20 | 399522.63 | 0.00 | 0.213246E+10 | 0.00 | 1.37 |
July | 0.558129E+09 | 48552926.87 | 0.00 | 6016563.46 | 422173.69 | 0.00 | 0.181259E+10 | 0.00 | 1.51 |
August | 0.564095E+09 | 0.110338E+09 | 0.00 | 4843384.68 | 2062825.82 | 0.00 | 0.123494E+10 | 0.00 | 1.23 |
September | 0.117253E+10 | 2149018.94 | 0.00 | 3870905.92 | 0.00 | 0.00 | 0.147682E+10 | 0.00 | 1.24 |
October | 0.205041E+10 | 0.00 | 0.00 | 1014326.55 | 0.00 | 23036030.71 | 0.641988E+09 | 0.00 | 0.73 |
November | 0.190654E+10 | 0.00 | 0.00 | 39297.44 | 0.00 | 0.432735E+09 | 26039912.87 | 0.00 | 0.51 |
December | 0.139996E+10 | 0.00 | 0.00 | 1460.38 | 0.00 | 0.107345E+10 | 5194136.42 | 0.00 | 0.44 |
Annual Sum or Average | 0.164330E+11 | 0.170334E+09 | 0.00 | 29172354.03 | 3186587.98 | 0.360581E+10 | 0.111412E+11 | 0.00 | 0.88 |
Minimum of Months | 0.558129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.223025E+10 | 0.110338E+09 | 0.00 | 6016563.46 | 2062825.82 | 0.137331E+10 | 0.213246E+10 | 0.00 | 1.51 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.654232E+11 | 0.928144E+10 | 0.00 | 0.150198E+12 | 0.222671E+11 |
February | 0.126943E+12 | 0.830500E+10 | 0.00 | 0.161759E+12 | 0.140935E+11 |
March | 0.220763E+12 | 0.828253E+10 | 0.00 | 0.202700E+12 | 0.644953E+10 |
April | 0.339593E+12 | 0.717295E+10 | 0.00 | 0.228909E+12 | 0.151107E+11 |
May | 0.442085E+12 | 0.592469E+10 | 0.00 | 0.247055E+12 | 0.284750E+11 |
June | 0.443787E+12 | 0.469113E+10 | 0.00 | 0.232417E+12 | 0.521028E+11 |
July | 0.469922E+12 | 0.340219E+10 | 0.00 | 0.230910E+12 | 0.985801E+11 |
August | 0.370128E+12 | 0.260712E+10 | 0.00 | 0.180465E+12 | 0.130864E+12 |
September | 0.264891E+12 | 0.335671E+10 | 0.00 | 0.238132E+12 | 0.480531E+11 |
October | 0.170416E+12 | 0.653182E+10 | 0.00 | 0.234489E+12 | 0.786047E+10 |
November | 0.731494E+11 | 0.785003E+10 | 0.00 | 0.189893E+12 | 0.114437E+11 |
December | 0.513424E+11 | 0.846483E+10 | 0.00 | 0.166513E+12 | 0.178002E+11 |
Annual Sum or Average | 0.303844E+13 | 0.758704E+11 | 0.00 | 0.246344E+13 | 0.453100E+12 |