Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:20:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2279.82 | 457.59 | 457.59 |
Net Site Energy | 2279.82 | 457.59 | 457.59 |
Total Source Energy | 5413.51 | 1086.57 | 1086.57 |
Net Source Energy | 5413.51 | 1086.57 | 1086.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 867.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 146.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1412.48 | 867.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 867.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 146.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 102.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 867.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 146.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 102.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 4.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.84 | 174.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.51 | 174.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 62.84 | 174.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.51 | 174.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1412.475 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1412.475 | 100.00 |
Total On-Site and Utility Electric Sources | 1412.475 | 100.00 |
Total Electricity End Uses | 1412.475 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 617.00 |
Time Setpoint Not Met During Occupied Cooling | 97.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3025.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-07:19 | 02-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 356036.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 80662.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41699.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33897.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3542.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 186900.54 | 356036.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 356036.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 80662.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 33897.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3542.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 940.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 464.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 954.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 324.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4473.31 | 940.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 188.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 93.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 897.86 | 188.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 188.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 93.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 897.86 | 188.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.84 | 0.263523 | 0.276000 | 0.784940 | 0.702727 | 0.500000 | 0.001446 | 0.000150 | 0.784940 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.32 | 0.322842 | 0.332000 | 0.770714 | 0.860912 | 0.500000 | 0.001180 | 0.000233 | 0.831470 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.40 | 0.312346 | 0.333000 | 0.799013 | 0.832923 | 0.500000 | 0.001220 | 0.000410 | 1.47 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.731086 | 0.216106 | 0.230000 | 0.168150 | 0.576281 | 0.500000 | 0.001763 | 0.000197 | 0.704361 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.899315 | 0.111220 | 0.200000 | 0.179863 | 0.300000 | 0.500000 | 0.003426 | 0.000127 | 0.456033 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.08 | 0.146140 | 0.200000 | 0.216220 | 0.389707 | 0.500000 | 0.002607 | 0.000195 | 0.696430 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.975417 | 0.102536 | 0.200000 | 0.195083 | 0.300000 | 0.500000 | 0.003716 | 0.000129 | 0.460975 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.579604 | 0.272586 | 0.285000 | 0.165187 | 0.726895 | 0.500000 | 0.001398 | 0.000152 | 0.544559 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.731371 | 0.136759 | 0.200000 | 0.146274 | 0.364691 | 0.500000 | 0.002786 | 0.000099 | 0.354710 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.867434 | 0.182137 | 0.200000 | 0.173487 | 0.485698 | 0.500000 | 0.002092 | 0.000150 | 0.537849 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.775945 | 0.128895 | 0.200000 | 0.155189 | 0.343719 | 0.500000 | 0.002956 | 0.000100 | 0.359130 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.642675 | 0.245835 | 0.253000 | 0.162597 | 0.655559 | 0.500000 | 0.001550 | 0.000154 | 0.551883 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.886055 | 0.112884 | 0.200000 | 0.177211 | 0.301025 | 0.500000 | 0.003375 | 0.000100 | 0.358973 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.990442 | 0.159516 | 0.200000 | 0.198088 | 0.425377 | 0.500000 | 0.002388 | 0.000152 | 0.544588 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.908226 | 0.110122 | 0.200000 | 0.181645 | 0.300000 | 0.500000 | 0.003460 | 0.000102 | 0.363427 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17113.31 | 0.000150 | 394.93 |
CORE_MID VAV BOX REHEAT COIL | 26681.19 | 0.000233 | 704.78 |
CORE_TOP VAV BOX REHEAT COIL | 46903.09 | 0.000410 | 1237.61 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22507.79 | 0.000197 | 593.40 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14572.04 | 0.000127 | 384.17 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22254.67 | 0.000195 | 586.73 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14729.76 | 0.000129 | 388.33 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17407.87 | 0.000152 | 459.02 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11338.44 | 0.000099 | 298.97 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17193.69 | 0.000150 | 453.38 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11479.50 | 0.000100 | 302.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17641.32 | 0.000154 | 465.17 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11474.28 | 0.000100 | 302.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17408.49 | 0.000152 | 459.03 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11616.45 | 0.000102 | 306.29 |
PACU_VAV_BOT HEATING COIL | 51592.95 | 0.000451 | 788.58 |
PACU_VAV_MID HEATING COIL | 52527.18 | 0.000460 | 786.82 |
PACU_VAV_TOP HEATING COIL | 52374.46 | 0.000458 | 812.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.90 | 1.43 | 5.80 | 2.22 | 5.07 | 5.07 | 0.300000 | 0.438480 | 5.07 |
PACU_VAV_MID | 2.87 | 1.49 | 5.75 | 2.65 | 4.77 | 4.77 | 0.300000 | 0.555942 | 4.77 |
PACU_VAV_TOP | 3.04 | 1.56 | 6.09 | 3.78 | 5.45 | 5.45 | 0.300000 | 0.693952 | 5.45 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.07 |
PACU_VAV_MID_OA_CONTROLLER | 4.77 |
PACU_VAV_TOP_OA_CONTROLLER | 5.45 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.07 | 110266.65 | 0.744560 | 1.69 | 36751.87 | 0.744560 |
PACU_VAV_MID COOLING COIL | 4.77 | 105784.51 | 0.737272 | 1.59 | 35257.98 | 0.737272 |
PACU_VAV_TOP COOLING COIL | 5.45 | 116887.87 | 0.749826 | 1.82 | 38958.73 | 0.749826 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.07 |
PACU_VAV_MID FAN | 4.77 |
PACU_VAV_TOP FAN | 5.45 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000451 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000460 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000458 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003821 | 0.458575 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003821 | 1150.86 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 436816.48 | 436816.48 | 0.003821 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.36_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3077E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3146E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4525E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4584E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6949E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7434E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6026E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6282E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1802 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7113E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2056 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1107 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1235 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2822E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0870E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9083E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3078E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3158E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4526E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4597E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6965E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7516E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6024E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6280E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.1706E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7439E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.7831E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4350E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8413E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9515E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9724E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8144E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3097E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.3379E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9847E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.0050E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5571E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5642E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3717E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3805E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.9473E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.0087E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1329E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1824E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5866E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6233E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6024E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6280E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7446E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7183E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6580E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0733E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3626E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4184E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0870E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9083E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.9471E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.0092E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1322E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1811E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5851E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6174E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6026E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6282E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0656E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2036E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3928E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7522E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9636E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5370E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9724E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8145E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6107E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6923E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1010E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1913E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0244E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0566E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3719E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3807E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1795 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1168 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2014 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1323 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1323 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.6839E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7993E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7067E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9001E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5888E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.5379E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2941E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6552E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8408E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8615E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7478E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4011E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5374E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2414E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7773E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9460E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0621E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7993E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7067E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8312E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0734E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.1935E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6431E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8038E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4441E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7479E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1795 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1168 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2014 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1323 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1323 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.6831E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7987E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7064E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9000E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5885E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.5378E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2938E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6547E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8404E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7475E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4012E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5373E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2415E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7772E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9458E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0619E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7987E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7064E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8312E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0731E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.1934E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6429E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8033E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4438E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7475E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37649.77317 | 37649.77317 | 2.84399 | 2.84399 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9574.89660 | 9574.89660 | 0.43064 | 0.43064 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30757.29714 | 30757.29714 | 2.32143 | 2.32143 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18695.91298 | 18695.91298 | 0.83147 | 0.83147 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31499.44770 | 31499.44770 | 2.39944 | 2.39944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 32833.00491 | 32833.00491 | 1.46505 | 1.46505 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9597.02777 | 9597.02777 | 0.73109 | 0.73109 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15747.55492 | 15747.55492 | 0.70436 | 0.70436 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11805.49878 | 11805.49878 | 0.89931 | 0.89931 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10195.26024 | 10195.26024 | 0.45603 | 0.45603 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14191.77189 | 14191.77189 | 1.08110 | 1.08110 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15570.58752 | 15570.58752 | 0.69643 | 0.69643 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12804.52627 | 12804.52627 | 0.97542 | 0.97542 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10305.53299 | 10305.53299 | 0.46098 | 0.46098 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7608.72921 | 7608.72921 | 0.57960 | 0.57960 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12180.27604 | 12180.27604 | 0.54456 | 0.54456 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9601.15291 | 9601.15291 | 0.73137 | 0.73137 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7933.36952 | 7933.36952 | 0.35471 | 0.35471 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11387.27709 | 11387.27709 | 0.86743 | 0.86743 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12030.54817 | 12030.54817 | 0.53785 | 0.53785 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10186.31021 | 10186.31021 | 0.77594 | 0.77594 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8031.98524 | 8031.98524 | 0.35913 | 0.35913 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8436.52592 | 8436.52592 | 0.64267 | 0.64267 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12344.58747 | 12344.58747 | 0.55188 | 0.55188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11631.57711 | 11631.57711 | 0.88606 | 0.88606 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8029.07137 | 8029.07137 | 0.35897 | 0.35897 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13001.83758 | 13001.83758 | 0.99044 | 0.99044 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12181.81008 | 12181.81008 | 0.54459 | 0.54459 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11922.61098 | 11922.61098 | 0.90823 | 0.90823 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8128.46347 | 8128.46347 | 0.36343 | 0.36343 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 75382.94 | 5.06509 | 5.06509 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 53579.26 | 2.22094 | 2.22094 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71453.64 | 4.76729 | 4.76729 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 53561.21 | 2.65034 | 2.65034 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80208.03 | 5.45117 | 5.45117 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 53778.38 | 3.78285 | 3.78285 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 03:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.84399 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26352 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78494 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70273 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44580E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49715E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78494 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17113.31176 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49715E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 394.93464 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32143 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32284 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77071 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86091 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18014E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33419E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.83147 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26681.19131 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33419E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 704.77646 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39944 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31235 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33300 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79901 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83292 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21980E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.10329E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.46505 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 46903.09002 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.10329E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1237.61029 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73109 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21611 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16815 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57628 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.76303E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96908E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70436 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22507.79227 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96908E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 593.39609 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89931 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11122 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17986 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42564E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27483E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45603 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14572.03873 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27483E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 384.17202 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08110 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14614 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21622 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38971 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60709E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94694E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69643 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22254.67426 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94694E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 586.72654 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97542 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10254 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19508 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71577E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28862E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46098 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14729.76266 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28862E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 388.32796 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57960 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27259 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16519 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72689 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39773E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52292E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54456 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17407.86606 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52292E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.02008 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73137 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13676 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14627 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36469 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78592E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.91936E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35471 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11338.43863 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.91936E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.97159 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86743 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18214 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17349 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48570 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09183E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50418E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53785 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17193.69145 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50418E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 453.37676 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77594 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12889 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15519 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34372 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.95590E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00428E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35913 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11479.50022 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00428E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.68843 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64267 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24583 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25300 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16260 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65556 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54982E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54334E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55188 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17641.32129 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54334E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 465.16806 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88606 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11288 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17721 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30103 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37513E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00382E-004 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35897 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11474.28405 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00382E-004 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.54852 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99044 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15952 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19809 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42538 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38847E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52297E-004 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54459 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17408.48875 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52297E-004 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.03309 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90823 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11012 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18165 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.45981E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01626E-004 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36343 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11616.45131 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01626E-004 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.29450 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89917 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42508 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.79834 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.22094 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06509 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.06509 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43848 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87441 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49026 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74883 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.65034 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.76729 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.76729 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.55594 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.04318 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55833 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.08635 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.78285 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.45117 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.45117 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.69395 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.06509 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.76729 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.45117 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06509 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06509 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 110266.64736 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74456 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68819 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36751.87357 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74456 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 51592.94568 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.51358E-004 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 788.57809 |
248 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.06509 |
249 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.51358E-004 |
250 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.76729 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.76729 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105784.51282 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73727 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58894 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35257.97812 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73727 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 52527.17744 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59531E-004 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 786.81541 |
260 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.76729 |
261 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.59531E-004 |
262 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.45117 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.45117 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116887.87365 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74983 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.81688 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38958.72829 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74983 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 52374.45502 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.58195E-004 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 812.16156 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.45117 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.58195E-004 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.82146E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.45858 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.82146E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1150.85627 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 436816.48090 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 436816.48000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.82146E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16215.83 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25288.33 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 44445.71 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21325.14 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13806.33 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21085.35 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13955.75 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16493.72 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10742.97 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16290.82 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10876.61 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16714.86 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10871.65 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16494.28 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11006.33 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 34388.40 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 34182.29 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 35502.92 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 109603.51 | 373982.72 | 12.33 | 3.15 | 3.53 | 3.72 | 3.89 | 10.74 | 12.06 | 12.70 | 13.27 | 5.5878 | 4.4534 | 2.9984 | 1.2406 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 105219.41 | 359023.51 | 12.38 | 3.16 | 3.55 | 3.74 | 3.90 | 10.77 | 12.10 | 12.75 | 13.29 | 5.2593 | 4.1857 | 2.8171 | 1.1761 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 116121.55 | 396223.19 | 12.30 | 3.14 | 3.52 | 3.71 | 3.88 | 10.72 | 12.02 | 12.66 | 13.24 | 6.0137 | 4.7931 | 3.2271 | 1.3298 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.0193182685E-002 | 3.7083238147E-002 | Pass | Pass | 0.4900019796 | 0.4898032132 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1569948245 | 0.1045922223 | Pass | Pass | 0.4965918972 | 0.4759267359 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7410148431E-002 | 3.9931211475E-002 | Pass | Pass | 0.4980261704 | 0.4643743207 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3303755755E-002 | 4.3532422215E-002 | Pass | Pass | 0.5007279663 | 0.4657773665 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 9.0063729146E-003 | 7.8549553596E-003 | Pass | Pass | 0.4993582098 | 0.4850434614 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 8.9183861078E-002 | 9.1900207726E-002 | Pass | Pass | 19.7955048366 | 47.0878550599 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4092545055 | 0.4088460728 | Pass | Pass | 16.1927770430 | 76.2969590938 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4254420673 | 0.4265380307 | Pass | Pass | 36.0161999830 | 124.1834230175 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3839009973 | 0.4012787121 | Pass | Pass | 50.2773125898 | 149.0797672734 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4306633683 | 0.4252546148 | Pass | Pass | 23.4134686760 | 71.8027411813 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3009995255 | 0.2883724784 | Pass | Pass | 24.7858229760 | 68.7907754720 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3048353594 | 0.2987035553 | Pass | Pass | 14.7036950149 | 36.2453242442 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2575192583 | 0.2680673605 | Pass | Pass | 15.1197792230 | 37.0618970434 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3123709339 | 0.3006182113 | Pass | Pass | 14.9876974310 | 36.9426793176 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3037497845 | 0.2915931820 | Pass | Pass | 18.8228311329 | 47.4410361666 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3030777191 | 0.3013750862 | Pass | Pass | 16.1467277650 | 42.5852039980 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2636444037 | 0.2794218502 | Pass | Pass | 17.2127296947 | 45.4036799994 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3090436565 | 0.2997504868 | Pass | Pass | 14.5634075405 | 37.0827195982 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3623.15 | 130.15 | 0.00 | 1847.60 | 1043.87 | 6644.76 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.36_SHGC_EAST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.36_SHGC_WEST_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.36_SHGC_WEST_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 195.79 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.045 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.17 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 8.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.79 | 0.0000 | Y | 5.53 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.08 | 0.0000 | Y | 8.83 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.84 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.52 | 0.0000 | Y | 8.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 5.52 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.17 | 0.0000 | Y | 8.86 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 8.66 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.79 | 0.0000 | Y | 5.53 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.51 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.24 | 42.24 | 4.47 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.63 | 62.93 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.63 | 47.43 | 41.98 | |
Exterior Lighting Total | 5686.19 | 51.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 436816.48 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 110266.65 | 82100.10 | 28166.55 | 0.74 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105784.51 | 77991.98 | 27792.53 | 0.74 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116887.87 | 87645.59 | 29242.28 | 0.75 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 109603.5 | 3.15 | 10.74 | N/A | N/A | 12.33 | |
PACU_VAV_MID COOLING COIL | 105219.4 | 3.16 | 10.77 | N/A | N/A | 12.38 | |
PACU_VAV_TOP COOLING COIL | 116121.6 | 3.14 | 10.72 | N/A | N/A | 12.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17113.31 | 16215.83 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 26681.19 | 25288.33 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 46903.09 | 44445.71 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22507.79 | 21325.14 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14572.04 | 13806.33 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22254.67 | 21085.35 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14729.76 | 13955.75 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17407.87 | 16493.72 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11338.44 | 10742.97 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17193.69 | 16290.82 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11479.50 | 10876.61 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17641.32 | 16714.86 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11474.28 | 10871.65 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17408.49 | 16494.28 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11616.45 | 11006.33 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 51592.95 | 34388.40 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 52527.18 | 34182.29 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 52374.46 | 35502.92 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.07 | 11641.90 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.77 | 10957.44 | 2298.46 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.45 | 12529.31 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003821 | 1150.86 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 109603.51 | 3.15 | 10.74 | 12.33 | 5.5878 | 3.53 | 12.06 | 4.4534 | 3.72 | 12.70 | 2.9984 | 3.89 | 13.27 | 1.2406 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105219.41 | 3.16 | 10.77 | 12.38 | 5.2593 | 3.55 | 12.10 | 4.1857 | 3.74 | 12.75 | 2.8171 | 3.90 | 13.29 | 1.1761 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 116121.55 | 3.14 | 10.72 | 12.30 | 6.0137 | 3.52 | 12.02 | 4.7931 | 3.71 | 12.66 | 3.2271 | 3.88 | 13.24 | 1.3298 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37649.77 | 37649.77 | 38.28 | 2.844 | 2.844 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 30757.30 | 30757.30 | 31.27 | 2.321 | 2.321 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 31499.45 | 31499.45 | 32.03 | 2.399 | 2.399 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00888 | 31.09 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9597.03 | 9597.03 | 46.29 | 0.731 | 0.731 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00895 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11805.50 | 11805.50 | 89.94 | 0.899 | 0.899 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00874 | 25.67 | 0.01535 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14191.77 | 14191.77 | 68.45 | 1.081 | 1.081 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00881 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12804.53 | 12804.53 | 97.56 | 0.975 | 0.975 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7608.73 | 7608.73 | 36.70 | 0.580 | 0.580 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00896 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9601.15 | 9601.15 | 73.14 | 0.731 | 0.731 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00874 | 26.27 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11387.28 | 11387.28 | 54.92 | 0.867 | 0.867 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00881 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10186.31 | 10186.31 | 77.61 | 0.776 | 0.776 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00872 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8436.53 | 8436.53 | 40.69 | 0.643 | 0.643 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00898 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11631.58 | 11631.58 | 88.61 | 0.886 | 0.886 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00873 | 25.03 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13001.84 | 13001.84 | 62.71 | 0.990 | 0.990 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00881 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11922.61 | 11922.61 | 90.84 | 0.908 | 0.908 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 29.54 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9574.90 | 9574.90 | 9.74 | 0.431 | 0.431 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 18695.91 | 18695.91 | 19.01 | 0.831 | 0.831 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 32833.00 | 32833.00 | 33.38 | 1.465 | 1.465 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15747.55 | 15747.55 | 75.95 | 0.704 | 0.704 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10195.26 | 10195.26 | 77.67 | 0.456 | 0.456 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15570.59 | 15570.59 | 75.10 | 0.696 | 0.696 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10305.53 | 10305.53 | 78.52 | 0.461 | 0.461 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12180.28 | 12180.28 | 58.75 | 0.545 | 0.545 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7933.37 | 7933.37 | 60.44 | 0.355 | 0.355 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12030.55 | 12030.55 | 58.02 | 0.538 | 0.538 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8031.99 | 8031.99 | 61.19 | 0.359 | 0.359 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12344.59 | 12344.59 | 59.54 | 0.552 | 0.552 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8029.07 | 8029.07 | 61.17 | 0.359 | 0.359 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12181.81 | 12181.81 | 58.75 | 0.545 | 0.545 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8128.46 | 8128.46 | 61.93 | 0.363 | 0.363 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.07 | 5.07 | 2.22 | 2.22 | 5.0651 | 2.2209 | 5.0651 | 0.4385 | 0.3000 |
PACU_VAV_MID | 4.77 | 4.77 | 2.65 | 2.65 | 4.7673 | 2.6503 | 4.7673 | 0.5559 | 0.3000 |
PACU_VAV_TOP | 5.45 | 5.45 | 3.78 | 3.78 | 5.4512 | 3.7829 | 5.4512 | 0.6940 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17113.312 | 17113.312 | 0.784940 | 0.00014971 | 394.935 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 17113.31 | 17113.31 | 0.784940 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 9574.90 | 0.00 | 17169.98 | 17169.98 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26681.191 | 26681.191 | 0.831470 | 0.00023342 | 704.776 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26681.19 | 26681.19 | 0.831470 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 18695.91 | 0.00 | 26776.79 | 26776.79 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 46903.090 | 46903.090 | 1.465053 | 0.00041033 | 1237.610 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46903.09 | 46903.09 | 1.465053 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 32833.00 | 0.00 | 47061.67 | 47061.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22507.792 | 22507.792 | 0.704361 | 0.00019691 | 593.396 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22507.79 | 22507.79 | 0.704361 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00775226 | 47.8246 | 15747.55 | 0.00 | 22580.24 | 22580.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14572.039 | 14572.039 | 0.456033 | 0.00012748 | 384.172 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14572.04 | 14572.04 | 0.456033 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774518 | 47.7817 | 10195.26 | 0.00 | 14618.90 | 14618.90 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22254.674 | 22254.674 | 0.696430 | 0.00019469 | 586.727 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22254.67 | 22254.67 | 0.696430 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774950 | 47.8078 | 15570.59 | 0.00 | 22326.33 | 22326.33 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14729.763 | 14729.763 | 0.460975 | 0.00012886 | 388.328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14729.76 | 14729.76 | 0.460975 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774785 | 47.7979 | 10305.53 | 0.00 | 14777.12 | 14777.12 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17407.866 | 17407.866 | 0.544559 | 0.00015229 | 459.020 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17407.87 | 17407.87 | 0.544559 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00782443 | 48.2625 | 12180.28 | 0.00 | 17464.47 | 17464.47 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11338.439 | 11338.439 | 0.354710 | 0.00009919 | 298.972 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11338.44 | 11338.44 | 0.354710 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00782116 | 48.2427 | 7933.37 | 0.00 | 11375.26 | 11375.26 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17193.691 | 17193.691 | 0.537849 | 0.00015042 | 453.377 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17193.69 | 17193.69 | 0.537849 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00782190 | 48.2471 | 12030.55 | 0.00 | 17249.62 | 17249.62 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11479.500 | 11479.500 | 0.359130 | 0.00010043 | 302.688 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11479.50 | 11479.50 | 0.359130 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00782363 | 48.2577 | 8031.99 | 0.00 | 11516.76 | 11516.76 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17641.321 | 17641.321 | 0.551883 | 0.00015433 | 465.168 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17641.32 | 17641.32 | 0.551883 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773439 | 47.7152 | 12344.59 | 0.00 | 17698.62 | 17698.62 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11474.284 | 11474.284 | 0.358973 | 0.00010038 | 302.549 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11474.28 | 11474.28 | 0.358973 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772863 | 47.6803 | 8029.07 | 0.00 | 11511.51 | 11511.51 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17408.489 | 17408.489 | 0.544588 | 0.00015230 | 459.033 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17408.49 | 17408.49 | 0.544588 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773060 | 47.6922 | 12181.81 | 0.00 | 17465.07 | 17465.07 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11616.451 | 11616.451 | 0.363427 | 0.00010163 | 306.295 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11616.45 | 11616.45 | 0.363427 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00773210 | 47.7014 | 8128.46 | 0.00 | 11654.12 | 11654.12 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 110266.647 | 82100.099 | 5.065085 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 112577.56 | 85369.97 | 5.065085 | 25.70 | 18.02 | 0.01039045 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 23.5962 | 24.00 | 0.00885364 | 45.4372 | 66477.34 | 0.00 | 113699.71 | 81629.99 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 51592.946 | 51592.946 | 1.519526 | 0.00045136 | 788.578 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51592.95 | 51592.95 | 1.519526 | -16.62 | -16.62 | 0.00192519 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 78.6542 | 18.16 | 0.00769246 | 56.6094 | 21267.35 | 0.00 | 41593.18 | 41593.18 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 105784.513 | 77991.981 | 4.767294 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 108331.26 | 80885.88 | 4.767294 | 25.81 | 18.16 | 0.01052726 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 25.0702 | 24.00 | 0.00890528 | 45.6989 | 62486.10 | 0.00 | 109078.03 | 77577.48 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 52527.177 | 52527.177 | 1.430188 | 0.00045953 | 786.815 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52527.18 | 52527.18 | 1.430188 | -19.02 | -19.02 | 0.00154442 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 83.5673 | 17.60 | 0.00734054 | 56.0061 | 21374.60 | 0.00 | 41336.00 | 41336.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 116887.874 | 87645.591 | 5.451174 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 119058.18 | 91206.28 | 5.451174 | 25.58 | 17.91 | 0.01029725 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.9250 | 24.00 | 0.00886944 | 45.5178 | 71377.92 | 0.00 | 120527.09 | 87083.93 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 52374.455 | 52374.455 | 1.635352 | 0.00045819 | 812.162 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 03:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52374.46 | 52374.46 | 1.635352 | -14.95 | -14.95 | 0.00229422 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 73.0833 | 15.60 | 0.00735516 | 63.7264 | 24356.57 | 0.00 | 42947.53 | 42947.53 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17113.312 | 17113.312 | 0.784940 | 0.00014971 | 394.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.8404 | 3.917735 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 17113.31 | 17113.31 | 1.0000 | 0.90154797 | 0.784940 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14969944 | 60.00 | 32.22 | 27.78 | 0.000 | 17113.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 9574.90 | 0.00 | 17169.98 | 17169.98 | 0.90154797 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.48 | 18.53 | 0.00800000 | 52104.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 26681.191 | 26681.191 | 0.831470 | 0.00023342 | 704.776 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 5.9876 | 6.108101 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26681.19 | 26681.19 | 1.0000 | 0.95499005 | 0.831470 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.23339489 | 60.00 | 32.22 | 27.78 | 0.000 | 26681.19 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 18695.91 | 0.00 | 26776.79 | 26776.79 | 0.95499005 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61098.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 46903.090 | 46903.090 | 1.465053 | 0.00041033 | 1237.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 10.5256 | 10.737482 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46903.09 | 46903.09 | 1.0000 | 1.68269542 | 1.465053 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.41028683 | 60.00 | 32.22 | 27.78 | 0.000 | 46903.09 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 32833.00 | 0.00 | 47061.67 | 47061.67 | 1.68269542 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61027.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22507.792 | 22507.792 | 0.704361 | 0.00019691 | 593.396 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 5.0510 | 5.152688 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22507.79 | 22507.79 | 1.0000 | 0.80899780 | 0.704361 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.19688790 | 60.00 | 32.22 | 27.78 | 0.000 | 22507.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775226 | 21.00 | 0.00775226 | 47.8246 | 15747.55 | 0.00 | 22580.24 | 22580.24 | 0.80899780 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14572.039 | 14572.039 | 0.456033 | 0.00012748 | 384.172 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.2702 | 3.335964 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14572.04 | 14572.04 | 1.0000 | 0.52377974 | 0.456033 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12746955 | 60.00 | 32.22 | 27.78 | 0.000 | 14572.04 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774518 | 21.00 | 0.00774518 | 47.7817 | 10195.26 | 0.00 | 14618.90 | 14618.90 | 0.52377974 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22254.674 | 22254.674 | 0.696430 | 0.00019469 | 586.727 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 4.9942 | 5.094742 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22254.67 | 22254.67 | 1.0000 | 0.79988904 | 0.696430 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.19467374 | 60.00 | 32.22 | 27.78 | 0.000 | 22254.67 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774950 | 21.00 | 0.00774950 | 47.8078 | 15570.59 | 0.00 | 22326.33 | 22326.33 | 0.79988904 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14729.763 | 14729.763 | 0.460975 | 0.00012886 | 388.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.3055 | 3.372071 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14729.76 | 14729.76 | 1.0000 | 0.52945568 | 0.460975 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12884924 | 60.00 | 32.22 | 27.78 | 0.000 | 14729.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774785 | 21.00 | 0.00774785 | 47.7979 | 10305.53 | 0.00 | 14777.12 | 14777.12 | 0.52945568 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17407.866 | 17407.866 | 0.544559 | 0.00015229 | 459.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.9065 | 3.985167 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17407.87 | 17407.87 | 1.0000 | 0.62545662 | 0.544559 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15227607 | 60.00 | 32.22 | 27.78 | 0.000 | 17407.87 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782443 | 21.00 | 0.00782443 | 48.2625 | 12180.28 | 0.00 | 17464.47 | 17464.47 | 0.62545662 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11338.439 | 11338.439 | 0.354710 | 0.00009919 | 298.972 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 2.5445 | 2.595698 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11338.44 | 11338.44 | 1.0000 | 0.40740436 | 0.354710 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09918349 | 60.00 | 32.22 | 27.78 | 0.000 | 11338.44 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782116 | 21.00 | 0.00782116 | 48.2427 | 7933.37 | 0.00 | 11375.26 | 11375.26 | 0.40740436 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17193.691 | 17193.691 | 0.537849 | 0.00015042 | 453.377 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.8585 | 3.936136 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17193.69 | 17193.69 | 1.0000 | 0.61774906 | 0.537849 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15040257 | 60.00 | 32.22 | 27.78 | 0.000 | 17193.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782190 | 21.00 | 0.00782190 | 48.2471 | 12030.55 | 0.00 | 17249.62 | 17249.62 | 0.61774906 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11479.500 | 11479.500 | 0.359130 | 0.00010043 | 302.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 2.5761 | 2.627992 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11479.50 | 11479.50 | 1.0000 | 0.41248082 | 0.359130 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10041743 | 60.00 | 32.22 | 27.78 | 0.000 | 11479.50 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782363 | 21.00 | 0.00782363 | 48.2577 | 8031.99 | 0.00 | 11516.76 | 11516.76 | 0.41248082 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17641.321 | 17641.321 | 0.551883 | 0.00015433 | 465.168 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.9589 | 4.038612 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17641.32 | 17641.32 | 1.0000 | 0.63386813 | 0.551883 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15431823 | 60.00 | 32.22 | 27.78 | 0.000 | 17641.32 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773439 | 21.00 | 0.00773439 | 47.7152 | 12344.59 | 0.00 | 17698.62 | 17698.62 | 0.63386813 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11474.284 | 11474.284 | 0.358973 | 0.00010038 | 302.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 2.5750 | 2.626797 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11474.28 | 11474.28 | 1.0000 | 0.41230048 | 0.358973 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10037180 | 60.00 | 32.22 | 27.78 | 0.000 | 11474.28 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772863 | 21.00 | 0.00772863 | 47.6803 | 8029.07 | 0.00 | 11511.51 | 11511.51 | 0.41230048 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17408.489 | 17408.489 | 0.544588 | 0.00015230 | 459.033 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 3.9067 | 3.985310 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17408.49 | 17408.49 | 1.0000 | 0.62548917 | 0.544588 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15228152 | 60.00 | 32.22 | 27.78 | 0.000 | 17408.49 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773060 | 21.00 | 0.00773060 | 47.6922 | 12181.81 | 0.00 | 17465.07 | 17465.07 | 0.62548917 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11616.451 | 11616.451 | 0.363427 | 0.00010163 | 306.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 2.6069 | 2.659344 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11616.45 | 11616.45 | 1.0000 | 0.41741672 | 0.363427 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.10161542 | 60.00 | 32.22 | 27.78 | 0.000 | 11616.45 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773210 | 21.00 | 0.00773210 | 47.7014 | 8128.46 | 0.00 | 11654.12 | 11654.12 | 0.41741672 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.4 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 110266.647 | 82100.099 | 5.065085 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1553 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.065085 | 5.81753311 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 112577.56 | 85369.97 | 1.0210 | 5.81753311 | 5.065085 | 25.70 | 18.02 | 0.01039045 | 52304.9 | 10.85 | 10.85 | 0.00850000 | 32327.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11641.903 | 100935.66 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 23.5962 | 24.00 | 0.00885364 | 24.00 | 0.00885364 | 45.4372 | 66477.34 | 0.00 | 113699.71 | 81629.99 | 5.58778453 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.36 | 12.35 | 0.00893443 | 34974.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51592.946 | 51592.946 | 1.519526 | 0.00045136 | 788.578 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.065085 | 5.81753311 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 11.5781 | 11.811126 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51592.95 | 51592.95 | 1.0000 | 1.74525993 | 1.519526 | -16.62 | -16.62 | 0.00192519 | -11944.0 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.45131155 | 60.00 | 32.22 | 27.78 | 0.000 | 51592.95 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 78.6542 | 18.69 | 0.00768757 | 18.16 | 0.00769246 | 56.6094 | 21267.35 | 0.00 | 41593.18 | 41593.18 | 1.74525993 | 2.80 | -1.30 | 0.00192519 | 7638.4 | 26.43 | 11.06 | 0.00192519 | 31470.4 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105784.513 | 77991.981 | 4.767294 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4097 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.767294 | 5.47550327 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 108331.26 | 80885.88 | 1.0241 | 5.47550327 | 4.767294 | 25.81 | 18.16 | 0.01052726 | 52764.6 | 10.85 | 10.85 | 0.00850000 | 32328.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10957.442 | 97373.82 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 25.0702 | 24.00 | 0.00890528 | 24.00 | 0.00890528 | 45.6989 | 62486.10 | 0.00 | 109078.03 | 77577.48 | 5.25926228 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.22 | 12.20 | 0.00883630 | 34582.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52527.177 | 52527.177 | 1.430188 | 0.00045953 | 786.815 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.767294 | 5.47550327 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 11.7878 | 12.024999 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52527.18 | 52527.18 | 1.0000 | 1.64265098 | 1.430188 | -19.02 | -19.02 | 0.00154442 | -15306.6 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.45948379 | 60.00 | 32.22 | 27.78 | 0.000 | 52527.18 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 83.5673 | 17.48 | 0.00756088 | 17.60 | 0.00734054 | 56.0061 | 21374.60 | 0.00 | 41336.00 | 41336.00 | 1.64265098 | 2.80 | -1.90 | 0.00154442 | 6684.1 | 27.77 | 11.23 | 0.00154442 | 31848.3 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116887.874 | 87645.591 | 5.451174 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9821 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.451174 | 6.26097717 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 119058.18 | 91206.28 | 1.0186 | 6.26097717 | 5.451174 | 25.58 | 17.91 | 0.01029725 | 51947.6 | 10.85 | 10.85 | 0.00850000 | 32327.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12529.313 | 106528.86 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 21.9250 | 24.00 | 0.00886944 | 24.00 | 0.00886944 | 45.5178 | 71377.92 | 0.00 | 120527.09 | 87083.93 | 6.01371590 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.49 | 12.47 | 0.00900426 | 35280.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52374.455 | 52374.455 | 1.635352 | 0.00045819 | 812.162 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.451174 | 6.26097717 | 4197.9300 | 999.8980 | 3.82107130 | 54.44 | 82.22 | 27.78 | 445607.59 | 11.7535 | 11.990036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 03:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52374.46 | 52374.46 | 1.0000 | 1.87829315 | 1.635352 | -14.95 | -14.95 | 0.00229422 | -9347.7 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.45814784 | 60.00 | 32.22 | 27.78 | 0.000 | 52374.46 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 73.0833 | 15.60 | 0.00754230 | 15.60 | 0.00735516 | 63.7264 | 24356.57 | 0.00 | 42947.53 | 42947.53 | 1.87829315 | 2.80 | -0.73 | 0.00229422 | 8563.2 | 25.46 | 11.03 | 0.00229422 | 31428.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.07 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.77 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.45 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2491.67 | 2820.83 | 312.50 |
CORE_MID | 2982.33 | 3612.50 | 1220.83 |
CORE_TOP | 3434.33 | 3888.17 | 1866.33 |
PERIMETER_TOP_ZN_3 | 4060.67 | 4109.83 | 2570.33 |
PERIMETER_TOP_ZN_2 | 4005.00 | 4048.00 | 2430.83 |
PERIMETER_TOP_ZN_1 | 3707.50 | 3809.50 | 2065.67 |
PERIMETER_TOP_ZN_4 | 3959.67 | 4146.67 | 2479.17 |
PERIMETER_BOT_ZN_3 | 3819.50 | 4153.83 | 2388.33 |
PERIMETER_BOT_ZN_2 | 3905.00 | 3921.83 | 2201.67 |
PERIMETER_BOT_ZN_1 | 3666.17 | 4069.83 | 2164.50 |
PERIMETER_BOT_ZN_4 | 3837.83 | 3969.67 | 2193.17 |
PERIMETER_MID_ZN_3 | 3881.17 | 3896.83 | 2204.83 |
PERIMETER_MID_ZN_2 | 3278.17 | 3361.83 | 1899.17 |
PERIMETER_MID_ZN_1 | 3580.50 | 3538.83 | 1718.00 |
PERIMETER_MID_ZN_4 | 3796.50 | 3925.33 | 2143.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5117.33 | 4751.83 | 3025.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.50 | 0.67 | 2.50 | 0.67 |
CORE_MID | 9.67 | 0.33 | 9.00 | 0.33 |
CORE_TOP | 27.67 | 0.00 | 22.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 258.50 | 4.33 | 143.83 | 2.50 |
PERIMETER_TOP_ZN_2 | 162.33 | 21.67 | 54.83 | 21.17 |
PERIMETER_TOP_ZN_1 | 147.17 | 24.83 | 54.33 | 23.33 |
PERIMETER_TOP_ZN_4 | 166.33 | 28.00 | 61.33 | 16.00 |
PERIMETER_BOT_ZN_3 | 161.00 | 0.33 | 126.17 | 0.33 |
PERIMETER_BOT_ZN_2 | 54.83 | 14.17 | 27.17 | 14.17 |
PERIMETER_BOT_ZN_1 | 554.50 | 23.00 | 539.83 | 22.67 |
PERIMETER_BOT_ZN_4 | 58.33 | 21.50 | 32.83 | 11.83 |
PERIMETER_MID_ZN_3 | 124.00 | 0.83 | 77.17 | 0.50 |
PERIMETER_MID_ZN_2 | 66.83 | 22.67 | 22.67 | 22.67 |
PERIMETER_MID_ZN_1 | 57.17 | 25.00 | 26.33 | 24.83 |
PERIMETER_MID_ZN_4 | 71.83 | 28.50 | 28.00 | 16.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 776.00 | 118.00 | 617.00 | 97.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.918 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.678 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.673 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.784 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.329 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 1.139 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.345 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.682 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.103 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.927 | 0.852 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.087 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.767 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.233 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 1.107 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.281 | 0.049 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.81 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.60 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.81 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.60 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.11 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14568240.03 | 0.00 | 14568240.03 | 0.00 | 14568240.03 | 13393058.27 | 6105.68 | 44.38 | 2609.94 | 223.30 |
CORE_MID | 10814396.39 | 0.00 | 10814396.39 | 0.00 | 10814396.39 | 13393058.27 | 6612.62 | 23.63 | 2123.75 | 271.99 |
CORE_TOP | 10734331.61 | 0.00 | 10734331.61 | 0.00 | 10734331.61 | 13393058.27 | 6559.39 | 25.92 | 2174.70 | 92.00 |
PERIMETER_TOP_ZN_3 | 2633506.91 | 0.00 | 2633506.91 | 375619.99 | 3009126.90 | 2823374.22 | 5666.56 | 50.70 | 3042.74 | 92.00 |
PERIMETER_TOP_ZN_2 | 2824163.16 | 0.00 | 2824163.16 | 250411.82 | 3074574.99 | 1787429.43 | 4059.07 | 1.49 | 4699.44 | 92.00 |
PERIMETER_TOP_ZN_1 | 3813702.05 | 0.00 | 3813702.05 | 375619.99 | 4189322.04 | 2823374.22 | 4083.90 | 1.84 | 4674.26 | 92.00 |
PERIMETER_TOP_ZN_4 | 2872091.42 | 0.00 | 2872091.42 | 250411.82 | 3122503.24 | 1787312.18 | 4060.90 | 3.61 | 4695.49 | 92.00 |
PERIMETER_BOT_ZN_3 | 2299578.75 | 0.00 | 2299578.75 | 199714.28 | 2499293.03 | 2823374.22 | 6126.34 | 57.80 | 2575.87 | 223.30 |
PERIMETER_BOT_ZN_2 | 2346010.48 | 0.00 | 2346010.48 | 133142.05 | 2479152.53 | 1787429.43 | 4115.38 | 5.58 | 4639.04 | 223.30 |
PERIMETER_BOT_ZN_1 | 3120609.17 | 0.00 | 3120609.17 | 2957967.51 | 6078576.68 | 2823374.22 | 4433.99 | 105.99 | 4220.02 | 223.30 |
PERIMETER_BOT_ZN_4 | 2321220.86 | 0.00 | 2321220.86 | 133142.05 | 2454362.92 | 1787312.18 | 4134.13 | 15.75 | 4610.13 | 223.30 |
PERIMETER_MID_ZN_3 | 2576786.04 | 0.00 | 2576786.04 | 312674.11 | 2889460.15 | 2823374.22 | 5895.95 | 50.05 | 2814.00 | 271.99 |
PERIMETER_MID_ZN_2 | 2802293.28 | 0.00 | 2802293.28 | 208448.16 | 3010741.44 | 1787429.43 | 4047.77 | 4.03 | 4708.19 | 1180.99 |
PERIMETER_MID_ZN_1 | 3709160.44 | 0.00 | 3709160.44 | 312674.11 | 4021834.55 | 2823374.22 | 4086.50 | 5.31 | 4668.19 | 271.99 |
PERIMETER_MID_ZN_4 | 2735354.31 | 0.00 | 2735354.31 | 208448.16 | 2943802.47 | 1787312.18 | 4053.36 | 3.80 | 4702.84 | 271.99 |
Total Facility | 70171444.91 | 0.00 | 70171444.91 | 5718274.06 | 75889718.97 | 67843644.98 | 6771.83 | 325.99 | 4811.34 | 1283.66 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6727 | 0.0000 | 0.6727 | 0.0000 | 0.6727 | 0.4247 | 3334.84 | 44.38 | 2563.78 |
CORE_MID | 0.4977 | 0.0000 | 0.4977 | 0.0000 | 0.4977 | 0.4247 | 3841.76 | 23.63 | 2077.61 |
CORE_TOP | 0.4942 | 0.0000 | 0.4942 | 0.0000 | 0.4942 | 0.4247 | 3796.47 | 25.92 | 2120.61 |
PERIMETER_TOP_ZN_3 | 0.1215 | 0.0000 | 0.1215 | 0.0086 | 0.1301 | 0.0895 | 2903.64 | 50.70 | 2988.66 |
PERIMETER_TOP_ZN_2 | 0.1303 | 0.0000 | 0.1303 | 0.0058 | 0.1361 | 0.0567 | 1296.49 | 1.49 | 4645.02 |
PERIMETER_TOP_ZN_1 | 0.1762 | 0.0000 | 0.1762 | 0.0086 | 0.1848 | 0.0895 | 1320.99 | 1.84 | 4620.18 |
PERIMETER_TOP_ZN_4 | 0.1320 | 0.0000 | 0.1320 | 0.0058 | 0.1377 | 0.0567 | 1298.32 | 3.61 | 4641.07 |
PERIMETER_BOT_ZN_3 | 0.1057 | 0.0000 | 0.1057 | 0.0046 | 0.1103 | 0.0895 | 3355.51 | 57.80 | 2529.70 |
PERIMETER_BOT_ZN_2 | 0.1081 | 0.0000 | 0.1081 | 0.0031 | 0.1112 | 0.0567 | 1344.93 | 5.56 | 4592.51 |
PERIMETER_BOT_ZN_1 | 0.1440 | 0.0000 | 0.1440 | 0.1335 | 0.2775 | 0.0895 | 1663.20 | 105.95 | 4173.85 |
PERIMETER_BOT_ZN_4 | 0.1066 | 0.0000 | 0.1066 | 0.0031 | 0.1097 | 0.0567 | 1363.79 | 15.70 | 4563.51 |
PERIMETER_MID_ZN_3 | 0.1188 | 0.0000 | 0.1188 | 0.0072 | 0.1260 | 0.0895 | 3125.09 | 50.05 | 2767.86 |
PERIMETER_MID_ZN_2 | 0.1209 | 0.0000 | 0.1209 | 0.0051 | 0.1260 | 0.0567 | 1277.47 | 4.01 | 3752.53 |
PERIMETER_MID_ZN_1 | 0.1713 | 0.0000 | 0.1713 | 0.0072 | 0.1785 | 0.0895 | 1315.64 | 5.31 | 4622.05 |
PERIMETER_MID_ZN_4 | 0.1256 | 0.0000 | 0.1256 | 0.0048 | 0.1304 | 0.0567 | 1283.01 | 3.78 | 4656.21 |
Total Facility | 3.2258 | 0.0000 | 3.2258 | 0.1972 | 3.4230 | 2.1513 | 3983.39 | 325.83 | 4738.22 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32525264.70 | 0.00 | 32525264.70 | 22614548.33 | 4100.04 | 2.08 | 4657.88 | 223.30 |
PACU_VAV_MID | 29863595.35 | 0.00 | 29863595.35 | 22614548.33 | 4066.83 | 0.74 | 4692.42 | 271.97 |
PACU_VAV_TOP | 30179941.00 | 0.00 | 30179941.00 | 22614548.33 | 4067.62 | 1.39 | 4690.99 | 91.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5001 | 0.0000 | 1.5001 | 0.7171 | 1329.21 | 2.08 | 4611.71 |
PACU_VAV_MID | 1.3754 | 0.0000 | 1.3754 | 0.7171 | 1296.14 | 0.74 | 4646.12 |
PACU_VAV_TOP | 1.3907 | 0.0000 | 1.3907 | 0.7171 | 1305.04 | 1.39 | 4636.57 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.75 | 2784.64 | 0.00 | 0.00 | 0.00 | 2233.72 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.22 | 2708.80 | 0.00 | 0.00 | 0.00 | 2406.46 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2514.55 | 0.00 | 0.00 | 0.00 | 2377.75 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5741 | 0.0000 | 0.0000 | 0.0000 | 1.0380 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3238 | 0.0000 | 0.0000 | 0.0000 | 1.0441 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3920 | 0.0000 | 0.0000 | 0.0000 | 1.0398 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 982 |
Defaulted Fields | 577 |
Fields with Defaults | 2420 |
Autosized Fields | 193 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
Electricity:Building | 1021.20 | 13465.67 | 09-APR-17:20 | 74341.76 | 17-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1021.20 | 13465.67 | 09-APR-17:20 | 74341.76 | 17-JAN-08:10 |
InteriorLights:Electricity | 301.51 | 987.92 | 09-APR-17:20 | 32642.50 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.51 | 987.92 | 09-APR-17:20 | 32642.50 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 301.51 | 987.92 | 09-APR-17:20 | 32642.50 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.51 | 987.92 | 09-APR-17:20 | 32642.50 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.19 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.96 | 267.21 | 09-APR-17:10 | 1768.58 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.99 | 422.10 | 26-MAR-17:10 | 2793.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.93 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.53 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.53 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.16 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.83 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.83 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.94 | 267.21 | 09-APR-17:10 | 1768.58 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.97 | 422.10 | 26-MAR-17:10 | 2793.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.64 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.92 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.19 | 422.10 | 09-APR-17:10 | 2793.69 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.86 | 36.00 | 01-JAN-10:10 | 1358.45 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.96 | 267.21 | 09-APR-17:10 | 1768.58 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-09:40 | 860.01 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.99 | 422.10 | 26-MAR-17:10 | 2793.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.66 | 36.00 | 01-JAN-09:40 | 1358.45 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.93 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.53 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.53 | 22.79 | 01-JAN-10:00 | 859.95 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 275.93 | 368.59 | 04-JUL-17:30 | 115970.52 | 04-AUG-07:20 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-13:20 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-13:20 |
ElectricityPurchased:Facility | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
ElectricityPurchased:Plant | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
Cogeneration:ElectricityPurchased | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
General:Cogeneration:ElectricityPurchased | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
ElectricityNet:Plant | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
Cogeneration:ElectricityNet | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
General:Cogeneration:ElectricityNet | 1412.48 | 13834.26 | 30-APR-17:30 | 186900.54 | 04-AUG-07:20 |
Fans:Electricity | 102.33 | 0.00 | 01-JAN-00:40 | 33897.33 | 04-AUG-07:20 |
General:Fans:Electricity | 102.33 | 0.00 | 01-JAN-00:40 | 33897.33 | 04-AUG-07:20 |
ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 146.70 | 0.00 | 01-JAN-00:10 | 80662.91 | 04-AUG-07:20 |
General:Cooling:Electricity | 146.70 | 0.00 | 01-JAN-00:10 | 80662.91 | 04-AUG-07:20 |
Electricity:Plant | 64.08 | 0.00 | 01-JAN-00:40 | 8471.16 | 02-FEB-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 59.81 | 0.00 | 01-JAN-00:10 | 7618.75 | 17-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 59.81 | 0.00 | 01-JAN-00:10 | 7618.75 | 17-FEB-13:00 |
Pumps:Electricity | 4.27 | 0.00 | 01-JAN-00:40 | 1156.50 | 31-JAN-07:20 |
General:Pumps:Electricity | 4.27 | 0.00 | 01-JAN-00:40 | 1156.50 | 31-JAN-07:20 |
WIRED_LTG_ELECTRICITY | 8.47 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-16:50 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 867.34 | 0.00 | 01-JAN-00:40 | 356036.47 | 02-FEB-07:20 |
NaturalGas:Plant | 867.34 | 0.00 | 01-JAN-00:40 | 356036.47 | 02-FEB-07:20 |
Heating:NaturalGas | 867.34 | 0.00 | 01-JAN-00:40 | 356036.47 | 02-FEB-07:20 |
Boiler:Heating:NaturalGas | 867.34 | 0.00 | 01-JAN-00:40 | 356036.47 | 02-FEB-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3142.16 | 0.00 | 01-JAN-00:40 | 705512.86 | 02-FEB-07:10 |
EnergyTransfer:Building | 1194.55 | 0.00 | 01-JAN-00:40 | 170834.69 | 04-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 209.75 | 0.00 | 01-JAN-00:40 | 25680.35 | 04-AUG-07:50 |
Heating:EnergyTransfer | 290.77 | 0.00 | 01-JAN-00:40 | 163254.79 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.27 | 0.00 | 01-JAN-00:10 | 9016.73 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 290.77 | 0.00 | 01-JAN-00:40 | 163254.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.27 | 0.00 | 01-JAN-00:10 | 9016.73 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 903.78 | 0.00 | 01-JAN-00:40 | 170834.69 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 209.49 | 0.00 | 01-JAN-00:40 | 25680.35 | 04-AUG-07:50 |
General:Cooling:EnergyTransfer | 903.78 | 0.00 | 01-JAN-00:40 | 170834.69 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 209.49 | 0.00 | 01-JAN-00:40 | 25680.35 | 04-AUG-07:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.65 | 0.00 | 01-JAN-00:40 | 17906.55 | 02-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 39.69 | 0.00 | 01-JAN-00:40 | 17906.55 | 02-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 39.69 | 0.00 | 01-JAN-00:40 | 17906.55 | 02-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.96 | 0.00 | 01-JAN-00:10 | 11213.35 | 26-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.96 | 0.00 | 01-JAN-00:10 | 11213.35 | 26-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.73 | 0.00 | 01-JAN-00:40 | 9601.08 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.48 | 0.00 | 01-JAN-00:40 | 9601.08 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.48 | 0.00 | 01-JAN-00:40 | 9601.08 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.25 | 0.00 | 01-JAN-00:10 | 5481.29 | 26-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.25 | 0.00 | 01-JAN-00:10 | 5481.29 | 26-JUN-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.82 | 0.00 | 01-JAN-00:40 | 8417.18 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.72 | 0.00 | 01-JAN-00:40 | 8417.18 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.72 | 0.00 | 01-JAN-00:40 | 8417.18 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.10 | 0.00 | 01-JAN-00:10 | 5765.65 | 26-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.10 | 0.00 | 01-JAN-00:10 | 5765.65 | 26-JUN-14:50 |
EnergyTransfer:Zone:CORE_MID | 141.90 | 0.00 | 01-JAN-00:40 | 19097.05 | 05-JUL-09:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 3.66 | 0.00 | 01-JAN-00:20 | 16254.34 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 3.66 | 0.00 | 01-JAN-00:20 | 16254.34 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 138.23 | 0.00 | 01-JAN-00:40 | 19097.05 | 05-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 138.23 | 0.00 | 01-JAN-00:40 | 19097.05 | 05-JUL-09:10 |
EnergyTransfer:Zone:CORE_TOP | 140.71 | 0.00 | 01-JAN-00:40 | 23992.91 | 11-DEC-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 16.29 | 0.00 | 01-JAN-00:40 | 23992.91 | 11-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 16.29 | 0.00 | 01-JAN-00:40 | 23992.91 | 11-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 124.42 | 0.00 | 01-JAN-00:20 | 21101.19 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 124.42 | 0.00 | 01-JAN-00:20 | 21101.19 | 26-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.48 | 0.00 | 01-JAN-00:40 | 10275.57 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.32 | 0.00 | 01-JAN-00:40 | 10275.57 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.32 | 0.00 | 01-JAN-00:40 | 10275.57 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.16 | 0.00 | 01-JAN-00:10 | 7546.75 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.16 | 0.00 | 01-JAN-00:10 | 7546.75 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.65 | 0.00 | 01-JAN-00:40 | 9643.01 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.96 | 0.00 | 01-JAN-00:40 | 8968.71 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.96 | 0.00 | 01-JAN-00:40 | 8968.71 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.69 | 0.00 | 01-JAN-00:20 | 9643.01 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.69 | 0.00 | 01-JAN-00:20 | 9643.01 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.58 | 0.00 | 01-JAN-00:40 | 14391.33 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 20.24 | 0.00 | 01-JAN-00:40 | 12293.83 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 20.24 | 0.00 | 01-JAN-00:40 | 12293.83 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.34 | 0.00 | 01-JAN-00:20 | 14391.33 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.34 | 0.00 | 01-JAN-00:20 | 14391.33 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 47.23 | 0.00 | 01-JAN-00:40 | 10116.17 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.83 | 0.00 | 01-JAN-00:40 | 9317.25 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.83 | 0.00 | 01-JAN-00:40 | 9317.25 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.40 | 0.00 | 01-JAN-00:20 | 10116.17 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 29.40 | 0.00 | 01-JAN-00:20 | 10116.17 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 41.76 | 0.00 | 01-JAN-00:40 | 7717.68 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.03 | 0.00 | 01-JAN-00:40 | 7717.68 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.03 | 0.00 | 01-JAN-00:40 | 7717.68 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.73 | 0.00 | 01-JAN-00:20 | 5824.41 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.73 | 0.00 | 01-JAN-00:20 | 5824.41 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 35.80 | 0.00 | 01-JAN-00:40 | 7764.68 | 26-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.37 | 0.00 | 01-JAN-00:40 | 6521.76 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.37 | 0.00 | 01-JAN-00:40 | 6521.76 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.43 | 0.00 | 01-JAN-00:20 | 7764.68 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.43 | 0.00 | 01-JAN-00:20 | 7764.68 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.30 | 0.00 | 01-JAN-00:40 | 14392.42 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.46 | 0.00 | 01-JAN-00:40 | 14392.42 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.46 | 0.00 | 01-JAN-00:40 | 14392.42 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.84 | 0.00 | 01-JAN-00:20 | 12747.38 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.84 | 0.00 | 01-JAN-00:20 | 12747.38 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.19 | 0.00 | 01-JAN-00:40 | 7907.62 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.76 | 0.00 | 01-JAN-00:40 | 6572.62 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.76 | 0.00 | 01-JAN-00:40 | 6572.62 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.43 | 0.00 | 01-JAN-00:20 | 7907.62 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 25.43 | 0.00 | 01-JAN-00:20 | 7907.62 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.73 | 0.00 | 01-JAN-00:40 | 8030.16 | 11-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 17.08 | 0.00 | 01-JAN-00:40 | 8030.16 | 11-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 17.08 | 0.00 | 01-JAN-00:40 | 8030.16 | 11-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.65 | 0.00 | 01-JAN-00:20 | 6930.69 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.65 | 0.00 | 01-JAN-00:20 | 6930.69 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 39.75 | 0.00 | 01-JAN-00:40 | 9587.89 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.88 | 0.00 | 01-JAN-00:40 | 6784.40 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.88 | 0.00 | 01-JAN-00:40 | 6784.40 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.87 | 0.00 | 01-JAN-00:20 | 9587.89 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.87 | 0.00 | 01-JAN-00:20 | 9587.89 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.94 | 0.00 | 01-JAN-00:40 | 13402.81 | 07-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.53 | 0.00 | 01-JAN-00:40 | 9164.36 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.53 | 0.00 | 01-JAN-00:40 | 9164.36 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.41 | 0.00 | 01-JAN-00:20 | 13402.81 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.41 | 0.00 | 01-JAN-00:20 | 13402.81 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.57 | 0.00 | 01-JAN-00:40 | 9668.01 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.18 | 0.00 | 01-JAN-00:40 | 6883.31 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.18 | 0.00 | 01-JAN-00:40 | 6883.31 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.39 | 0.00 | 01-JAN-00:20 | 9668.01 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.39 | 0.00 | 01-JAN-00:20 | 9668.01 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 680.21 | 0.00 | 01-JAN-00:40 | 285626.75 | 02-FEB-07:20 |
PlantLoopHeatingDemand:Plant | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
EnergyTransfer:HVAC | 1271.86 | 0.00 | 01-JAN-00:40 | 390708.50 | 04-AUG-07:20 |
HeatingCoils:EnergyTransfer | 623.24 | 0.00 | 01-JAN-00:40 | 283215.92 | 02-FEB-07:20 |
PlantLoopHeatingDemand:HVAC | 623.24 | 0.00 | 01-JAN-00:40 | 283215.92 | 02-FEB-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 623.24 | 0.00 | 01-JAN-00:40 | 283215.92 | 02-FEB-07:20 |
CoolingCoils:EnergyTransfer | 648.61 | 0.00 | 01-JAN-00:10 | 390708.50 | 04-AUG-07:20 |
EnergyTransfer:Plant | 675.75 | 0.00 | 01-JAN-00:40 | 284339.71 | 02-FEB-07:20 |
WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
Boilers:EnergyTransfer | 618.78 | 0.00 | 01-JAN-00:40 | 281928.87 | 02-FEB-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.265 | -209.487 | 0.000 | 0.000 | 33.525 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -146.655 |
CORE_MID | 0.000 | 0.000 | 3.665 | -138.233 | 0.000 | 0.000 | 34.875 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -87.660 |
CORE_TOP | 0.000 | 0.000 | 16.288 | -124.420 | 0.000 | 0.000 | 35.593 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -114.814 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 29.321 | -26.158 | 0.000 | 0.000 | 7.658 | 8.862 | 24.333 | 18.264 | 0.000 | 0.049 | 0.001 | 0.000 | -42.638 | 0.000 | -6.957 | -12.733 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 16.955 | -28.692 | 0.000 | 0.000 | 4.818 | 5.552 | 15.404 | 34.449 | 0.000 | 0.033 | 0.000 | 0.000 | -26.446 | 0.000 | -4.682 | -17.390 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 20.239 | -45.342 | 0.000 | 0.000 | 7.479 | 8.658 | 24.332 | 70.899 | 0.000 | 0.046 | 0.001 | 0.000 | -38.761 | 0.000 | -7.188 | -40.363 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 17.829 | -29.401 | 0.000 | 0.000 | 4.866 | 5.529 | 15.403 | 35.984 | 0.000 | 0.031 | 0.000 | 0.000 | -27.411 | 0.000 | -4.699 | -18.132 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 19.032 | -22.725 | 0.000 | 0.000 | 7.641 | 8.829 | 24.333 | 18.627 | 0.000 | 0.032 | 0.000 | 0.000 | -43.448 | 0.000 | -3.816 | -8.506 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 10.375 | -25.429 | 0.000 | 0.000 | 4.781 | 5.539 | 15.404 | 34.627 | 0.000 | 0.019 | 0.000 | 0.000 | -27.341 | 0.000 | -2.598 | -15.377 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 31.457 | -32.840 | 0.000 | 0.000 | 7.719 | 8.642 | 24.332 | 71.860 | 0.000 | 1.075 | 0.002 | 0.000 | -39.850 | 0.000 | -48.290 | -24.106 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 10.764 | -25.426 | 0.000 | 0.000 | 4.815 | 5.516 | 15.403 | 36.219 | 0.000 | 0.017 | 0.000 | 0.000 | -28.345 | 0.000 | -2.609 | -16.354 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 17.082 | -27.652 | 0.000 | 0.000 | 7.573 | 8.862 | 24.333 | 18.014 | 0.000 | 0.042 | 2.167 | 0.000 | -44.400 | 0.000 | -6.020 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 9.884 | -29.866 | 0.000 | 0.000 | 3.538 | 5.552 | 15.404 | 34.252 | 0.000 | 0.029 | 0.000 | 0.000 | -27.493 | 0.000 | -4.044 | -7.257 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 10.528 | -47.409 | 0.000 | 0.000 | 7.375 | 8.658 | 24.332 | 70.556 | 0.000 | 0.038 | 0.002 | 0.000 | -40.479 | 0.000 | -6.233 | -27.366 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.185 | -30.389 | 0.000 | 0.000 | 4.811 | 5.529 | 15.403 | 35.818 | 0.000 | 0.026 | 0.000 | 0.000 | -28.539 | 0.000 | -4.063 | -8.781 |
TOPFLOOR_PLENUM | 39.692 | -25.959 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.040 | 0.001 | 0.000 | 0.000 | 0.000 | -10.551 | -3.223 |
MIDFLOOR_PLENUM | 16.481 | -15.250 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.061 | 8.987 | 0.000 | 0.000 | 0.000 | -10.279 | -0.002 |
FIRSTFLOOR_PLENUM | 10.723 | -19.101 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 16.626 | 0.000 | 0.000 | 0.000 | -8.294 | -0.000 |
Total Facility | 66.897 | -60.310 | 223.869 | -843.468 | 0.000 | 0.000 | 177.066 | 301.513 | 719.689 | 479.570 | 0.000 | 1.584 | 27.787 | 0.000 | -415.151 | 0.000 | -130.324 | -548.717 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-JUL-05:12 | 0.00 | 0.00 | 0.00 | -41599.11 | 0.00 | 0.00 | 316.90 | 715.98 | 7410.35 | 0.00 | 0.00 | 0.00 | 33155.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 19-JUN-05:12 | 0.00 | 0.00 | 0.00 | -32634.16 | 0.00 | 0.00 | 334.50 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 28557.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-06:03 | 0.00 | 0.00 | 0.00 | -30364.61 | 0.00 | 0.00 | 708.28 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 24482.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:11 | 0.00 | 0.00 | 0.00 | -11610.38 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 3139.82 | 0.00 | 186.62 | 7861.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:22 | 0.00 | 0.00 | 0.00 | -15371.87 | 0.00 | 0.00 | 12.64 | 22.79 | 302.86 | 10427.66 | 0.00 | 0.00 | 4625.61 | 0.00 | -0.00 | 0.00 | -19.69 | 0.00 |
PERIMETER_TOP_ZN_1 | 16-APR-13:42 | 0.00 | 0.00 | 0.00 | -19268.30 | 0.00 | 0.00 | 22.35 | 36.00 | 478.41 | 13146.89 | 0.00 | 0.00 | 5618.49 | 0.00 | -0.00 | 0.00 | -33.84 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:41 | 0.00 | 0.00 | 0.00 | -17154.06 | 0.00 | 0.00 | 10.68 | 22.79 | 302.86 | 12238.30 | 0.00 | 14.05 | 4565.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7554.99 | 0.00 | 0.00 | 146.19 | 216.00 | 637.89 | 3045.82 | 0.00 | 0.00 | 3517.63 | 0.00 | -0.00 | 0.00 | -8.53 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -13131.49 | 0.00 | 0.00 | 14.97 | 22.79 | 302.86 | 10913.32 | 0.00 | 0.00 | 1895.33 | 0.00 | -0.00 | 0.00 | -17.77 | 0.00 |
PERIMETER_BOT_ZN_1 | 17-SEP-13:21 | 0.00 | 0.00 | 0.00 | -15643.29 | 0.00 | 0.00 | 23.62 | 36.00 | 478.41 | 14604.15 | 0.00 | 0.00 | 543.94 | 0.00 | -0.00 | 0.00 | -42.83 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-18:31 | 0.00 | 0.00 | 0.00 | -14228.27 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 7118.65 | 0.00 | 0.00 | 6850.01 | 0.00 | -0.00 | 0.00 | -7.60 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:21 | 0.00 | 0.00 | 0.00 | -10518.93 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 4260.74 | 0.00 | 80.44 | 5755.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -16723.75 | 0.00 | 0.00 | 12.73 | 22.79 | 302.86 | 10809.81 | 0.00 | 0.00 | 5614.20 | 0.00 | -0.00 | 0.00 | -38.64 | 0.00 |
PERIMETER_MID_ZN_1 | 17-SEP-13:21 | 0.00 | 0.00 | 0.00 | -18304.91 | 0.00 | 0.00 | 21.94 | 36.00 | 478.41 | 14491.30 | 0.00 | 0.00 | 3359.01 | 0.00 | -0.00 | 0.00 | -81.76 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -17010.27 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 10927.00 | 0.00 | 33.93 | 5782.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:30 | 0.00 | -11213.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 11169.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 26-JUN-15:40 | 0.00 | -5481.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 | 5437.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-06:15 | 0.00 | -6001.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6043.93 | 0.00 | -0.00 | 0.00 | -42.63 | 0.00 |
Total Facility | 05-JUL-06:03 | 0.00 | -7879.56 | 0.00 | -171922.14 | 0.00 | 0.00 | 3528.94 | 8560.47 | 22496.85 | 35895.98 | 0.00 | 0.00 | 112824.74 | 0.00 | 0.00 | 0.00 | -3505.28 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 11015.30 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16869.09 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 19143.32 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21797.11 |
CORE_TOP | 30-JAN-05:11 | 0.00 | 0.00 | 26824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29477.79 |
PERIMETER_TOP_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 11083.64 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4804.10 | 0.00 | -1179.00 | -5659.97 |
PERIMETER_TOP_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 10434.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3100.98 | 0.00 | -791.34 | -6896.12 |
PERIMETER_TOP_ZN_1 | 30-JAN-05:11 | 0.00 | 0.00 | 13826.37 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4688.47 | 0.00 | -1192.11 | -8505.23 |
PERIMETER_TOP_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 10970.42 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3206.26 | 0.00 | -791.84 | -7326.46 |
PERIMETER_BOT_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 8250.64 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4907.90 | 0.00 | -647.51 | -3254.67 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 7745.40 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3190.58 | 0.00 | -434.33 | -4474.65 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 15439.38 | 0.00 | 0.00 | 0.00 | 223.06 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 26553.00 | 0.00 | -5848.53 | 0.00 | -37457.60 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 8030.79 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3290.21 | 0.00 | -434.83 | -4659.89 |
PERIMETER_MID_ZN_3 | 02-FEB-04:12 | 0.00 | 0.00 | 8704.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5871.16 | 0.00 | -1068.75 | -2323.81 |
PERIMETER_MID_ZN_2 | 02-FEB-04:12 | 0.00 | 0.00 | 8396.07 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3793.96 | 0.00 | -718.23 | -4238.03 |
PERIMETER_MID_ZN_1 | 11-DEC-05:11 | 0.00 | 0.00 | 10746.18 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4165.35 | 0.00 | -599.76 | -6540.50 |
PERIMETER_MID_ZN_4 | 02-FEB-04:12 | 0.00 | 0.00 | 8568.19 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3915.14 | 0.00 | -717.87 | -4289.33 |
TOPFLOOR_PLENUM | 03-FEB-06:10 | 18915.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -211.44 | -18704.13 |
MIDFLOOR_PLENUM | 02-JAN-08:11 | 10252.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -283.84 | -9968.16 |
FIRSTFLOOR_PLENUM | 02-JAN-08:45 | 8549.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -219.61 | -8329.49 |
Total Facility | 02-JAN-05:01 | 14066.08 | 0.00 | 160968.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22448.51 | 0.00 | -6180.22 | -163048.44 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7983 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0651 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.7488 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7673 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.0864 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4512 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8992 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4251 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8744 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4903 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0432 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5583 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8440 | 2.8440 | 0.7849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3214 | 2.3214 | 0.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3994 | 2.3994 | 0.7990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7311 | 0.7311 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8993 | 0.8993 | 0.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0811 | 1.0811 | 0.2162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9754 | 0.9754 | 0.1951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5796 | 0.5796 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7314 | 0.7314 | 0.1463 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8674 | 0.8674 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7759 | 0.7759 | 0.1552 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6427 | 0.6427 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8861 | 0.8861 | 0.1772 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9904 | 0.9904 | 0.1981 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9082 | 0.9082 | 0.1816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7983 | 5.0651 | 5.7983 | 1.4251 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.7488 | 4.7673 | 5.7488 | 1.4903 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.0864 | 5.4512 | 6.0864 | 1.5583 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4220 | 1.4220 | 0.7849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1607 | 1.1607 | 0.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1997 | 1.1997 | 0.7990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3655 | 0.3655 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4497 | 0.4497 | 0.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5405 | 0.5405 | 0.2162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4877 | 0.4877 | 0.1951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2898 | 0.2898 | 0.1652 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3657 | 0.3657 | 0.1463 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4337 | 0.4337 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3880 | 0.3880 | 0.1552 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3213 | 0.3213 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4430 | 0.4430 | 0.1772 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4952 | 0.4952 | 0.1981 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4541 | 0.4541 | 0.1816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8992 | 1.4251 | 1.4251 | 1.4251 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8744 | 1.4903 | 1.4903 | 1.4903 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0432 | 1.5583 | 1.5583 | 1.5583 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 617.00 |
Number of hours cooling loads not met | 97.17 |
Number of hours not met | 714.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 867.34 | 356036.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 146.70 | 80662.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.51 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.26 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 102.33 | 33897.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 4.27 | 1156.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.81 | 7618.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1412.48 |
Natural Gas | 0.00 | 867.34 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2279.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.52 |
Space Heating | 0.00 |
Space Cooling | 29.44 |
Fans (All) | 20.54 |
Service Water Heating | 12.00 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 283.51 |
Subtotal | 283.51 |
Natural Gas [MJ/m2] | |
Space Heating | 174.09 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 174.09 |
Subtotal | 174.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.23 |
Space Heating | 38.04 |
Space Cooling | 6.43 |
Fans (All) | 4.49 |
Service Water Heating | 2.62 |
Receptacle Equipment | 31.57 |
Miscellaneous | 3.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8503.33 | 256.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8689.00 | 71.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8696.67 | 63.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8679.67 | 80.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8693.50 | 66.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8698.50 | 61.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8664.17 | 95.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8651.17 | 108.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8503.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 256.67 | 0.00 | 0.00 | 0.00 |
Average | 8703.52 | 56.48 | 0.00 | 0.00 | 0.00 |
Sum | 156663.33 | 1016.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128225.67 | 78.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 78.33 | 0.00 | 0.00 | 0.00 |
Average | 34138.98 | 4.35 | 0.00 | 0.00 | 0.00 |
Sum | 614501.67 | 78.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8100.50 | 659.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8377.50 | 382.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8494.67 | 265.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8349.33 | 410.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8337.83 | 422.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8332.50 | 427.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8310.33 | 449.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8495.33 | 264.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8347.67 | 412.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8293.50 | 466.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8283.67 | 476.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8311.33 | 448.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8312.83 | 447.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8281.17 | 478.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8251.83 | 508.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8004.67 | 755.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8367.17 | 392.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8362.83 | 397.17 | 0.00 | 0.00 | 0.00 |
Min | 8004.67 | 264.67 | 0.00 | 0.00 | 0.00 |
Max | 8495.33 | 755.33 | 0.00 | 0.00 | 0.00 |
Average | 8311.93 | 448.07 | 0.00 | 0.00 | 0.00 |
Sum | 149614.67 | 8065.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127880.67 | 423.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128113.67 | 190.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128202.17 | 101.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24891.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14013.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24897.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24892.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24440.33 | 468.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14009.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24882.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10130.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24887.67 | 21.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128202.17 | 468.67 | 0.00 | 0.00 | 0.00 |
Average | 34070.93 | 72.41 | 0.00 | 0.00 | 0.00 |
Sum | 613276.67 | 1303.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:11
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.888540E+10 | 9883.08 | 13-JAN-17:00 | 2.20 | 0.77 | 0.167335E+10 | 2606.54 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.908663E+10 | 11195.34 | 24-FEB-17:00 | 7.20 | 5.13 | 0.162388E+10 | 2606.61 | 24-FEB-14:09 | 7.20 | 5.13 |
March | 0.126355E+11 | 16329.05 | 24-MAR-16:00 | 10.60 | 5.50 | 0.208693E+10 | 2606.64 | 28-MAR-09:20 | 8.13 | 5.04 |
April | 0.149607E+11 | 37466.06 | 17-APR-06:02 | 10.00 | 8.65 | 0.189808E+10 | 2606.68 | 11-APR-13:09 | 10.00 | 8.65 |
May | 0.216119E+11 | 41558.02 | 30-MAY-05:12 | 14.60 | 14.60 | 0.207741E+10 | 2606.71 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.255516E+11 | 41468.11 | 19-JUN-05:12 | 11.87 | 10.77 | 0.207214E+10 | 2606.69 | 01-JUN-09:00 | 11.87 | 10.77 |
July | 0.266251E+11 | 41606.36 | 10-JUL-05:12 | 17.20 | 16.74 | 0.192736E+10 | 2606.65 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.278586E+11 | 40557.47 | 21-AUG-05:12 | 15.93 | 15.21 | 0.216337E+10 | 2836.64 | 04-AUG-07:49 | 15.93 | 15.21 |
September | 0.233524E+11 | 40951.07 | 12-SEP-05:12 | 15.93 | 15.59 | 0.191916E+10 | 2606.65 | 06-SEP-09:09 | 15.93 | 15.59 |
October | 0.167736E+11 | 33856.22 | 23-OCT-05:01 | -2.7 | -3.7 | 0.198983E+10 | 2606.64 | 17-OCT-09:30 | -2.7 | -3.7 |
November | 0.125254E+11 | 18403.57 | 03-NOV-16:00 | 15.00 | 9.33 | 0.189913E+10 | 2606.65 | 01-NOV-09:09 | 15.00 | 9.33 |
December | 0.962057E+10 | 11222.45 | 07-DEC-16:10 | -5.4 | -8.6 | 0.173850E+10 | 2606.62 | 07-DEC-10:39 | -5.4 | -8.6 |
Annual Sum or Average | 0.209487E+12 | 0.230691E+11 | ||||||||
Minimum of Months | 0.888540E+10 | 9883.08 | -5.4 | -8.6 | 0.162388E+10 | 2606.54 | -5.4 | -8.6 | ||
Maximum of Months | 0.278586E+11 | 41606.36 | 17.20 | 16.74 | 0.216337E+10 | 2836.64 | 21.28 | 16.97 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 18173161.13 | 781.64 | 24-FEB-14:40 | 8.13 | 5.47 | 0.00 | 0.00 | 01-FEB-00:10 | 8.13 | 5.47 |
March | 0.258323E+09 | 2702.17 | 19-MAR-14:15 | 18.30 | 13.68 | 0.00 | 0.00 | 01-MAR-00:10 | 18.30 | 13.68 |
April | 0.142783E+10 | 8822.06 | 18-APR-14:30 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.315558E+10 | 9845.38 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.556842E+10 | 11213.35 | 26-JUN-13:30 | 31.40 | 21.76 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 21.76 |
July | 0.612967E+10 | 10664.29 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.566680E+10 | 11157.44 | 04-AUG-15:10 | 33.90 | 25.49 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.49 |
September | 0.307504E+10 | 10058.66 | 07-SEP-15:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.565472E+09 | 4200.25 | 20-OCT-14:50 | 23.18 | 13.31 | 0.00 | 0.00 | 01-OCT-00:10 | 23.18 | 13.31 |
November | 93901551.31 | 2104.50 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.259592E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.612967E+10 | 11213.35 | 33.90 | 25.49 | 0.00 | 0.00 | 33.90 | 25.49 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27202048.28 | 3620.77 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 31740423.84 | 3239.85 | 04-FEB-04:02 | -31.0 | -31.2 | 0.00 | 0.00 | 01-FEB-00:10 | -31.0 | -31.2 |
March | 0.123281E+09 | 2586.70 | 30-MAR-06:02 | 1.10 | 0.61 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | 0.61 |
April | 0.659971E+09 | 3786.54 | 17-APR-16:00 | 19.40 | 11.31 | 0.00 | 0.00 | 01-APR-00:10 | 19.40 | 11.31 |
May | 0.153844E+10 | 4254.53 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.326847E+10 | 5481.29 | 26-JUN-15:40 | 31.50 | 22.02 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 22.02 |
July | 0.371761E+10 | 5404.23 | 03-JUL-06:15 | 19.27 | 18.06 | 0.00 | 0.00 | 01-JUL-00:10 | 19.27 | 18.06 |
August | 0.348616E+10 | 5004.94 | 04-AUG-15:30 | 33.90 | 25.83 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.83 |
September | 0.195848E+10 | 4735.32 | 07-SEP-16:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.313417E+09 | 2386.93 | 14-OCT-06:03 | -1.4 | -2.3 | 0.00 | 0.00 | 01-OCT-00:10 | -1.4 | -2.3 |
November | 0.113862E+09 | 2577.89 | 25-NOV-05:01 | -15.3 | -15.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.3 | -15.7 |
December | 11799772.21 | 2865.74 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.152504E+11 | 0.00 | ||||||||
Minimum of Months | 11799772.21 | 2386.93 | -31.0 | -31.2 | 0.00 | 0.00 | -31.0 | -31.2 | ||
Maximum of Months | 0.371761E+10 | 5481.29 | 33.90 | 25.83 | 0.00 | 0.00 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81671225.76 | 3241.20 | 06-JAN-05:11 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.105604E+09 | 3940.93 | 02-FEB-07:10 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -36.7 | -36.8 |
March | 0.260227E+09 | 2924.25 | 30-MAR-06:02 | 1.10 | 0.61 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | 0.61 |
April | 0.867009E+09 | 3881.71 | 18-APR-15:20 | 27.20 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 20.26 |
May | 0.200855E+10 | 4415.97 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.369820E+10 | 5765.65 | 26-JUN-14:50 | 31.20 | 21.88 | 0.00 | 0.00 | 01-JUN-00:10 | 31.20 | 21.88 |
July | 0.425879E+10 | 6001.87 | 03-JUL-06:15 | 19.27 | 18.06 | 0.00 | 0.00 | 01-JUL-00:10 | 19.27 | 18.06 |
August | 0.429434E+10 | 5332.16 | 04-AUG-12:10 | 31.20 | 26.19 | 0.00 | 0.00 | 01-AUG-00:10 | 31.20 | 26.19 |
September | 0.269634E+10 | 5376.06 | 11-SEP-12:10 | 27.88 | 20.86 | 0.00 | 0.00 | 01-SEP-00:10 | 27.88 | 20.86 |
October | 0.545589E+09 | 2910.17 | 26-OCT-06:02 | -0.9 | -2.2 | 0.00 | 0.00 | 01-OCT-00:10 | -0.9 | -2.2 |
November | 0.215291E+09 | 2634.09 | 10-NOV-07:01 | -2.2 | -2.8 | 0.00 | 0.00 | 01-NOV-00:10 | -2.2 | -2.8 |
December | 69889110.53 | 2555.06 | 08-DEC-17:10 | -19.2 | -19.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.2 | -19.4 |
Annual Sum or Average | 0.191015E+11 | 0.00 | ||||||||
Minimum of Months | 69889110.53 | 2555.06 | -36.7 | -36.8 | 0.00 | 0.00 | -36.7 | -36.8 | ||
Maximum of Months | 0.429434E+10 | 6001.87 | 31.20 | 26.19 | 0.00 | 0.00 | 31.20 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.446194E+10 | 6647.67 | 13-JAN-17:00 | 2.20 | 0.77 | 0.149916E+10 | 2333.26 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.543696E+10 | 6911.36 | 24-FEB-17:00 | 7.20 | 5.13 | 0.141714E+10 | 2362.69 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.836353E+10 | 9372.45 | 24-MAR-16:00 | 10.60 | 5.50 | 0.185365E+10 | 2606.48 | 24-MAR-13:20 | 10.60 | 5.50 |
April | 0.104146E+11 | 19232.30 | 17-APR-06:02 | 10.00 | 8.65 | 0.177684E+10 | 2606.64 | 14-APR-09:09 | 10.00 | 8.65 |
May | 0.149512E+11 | 30648.84 | 30-MAY-05:12 | 14.60 | 14.60 | 0.205484E+10 | 2606.69 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.181700E+11 | 32637.84 | 19-JUN-05:12 | 11.87 | 10.77 | 0.206303E+10 | 2606.66 | 01-JUN-09:00 | 11.87 | 10.77 |
July | 0.191076E+11 | 31147.30 | 05-JUL-06:03 | 19.60 | 18.69 | 0.192122E+10 | 2606.64 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.193639E+11 | 28805.14 | 14-AUG-06:03 | 16.10 | 15.45 | 0.215671E+10 | 2722.75 | 04-AUG-07:40 | 16.10 | 15.45 |
September | 0.151604E+11 | 32399.60 | 18-SEP-05:12 | 17.20 | 13.61 | 0.189751E+10 | 2606.66 | 06-SEP-09:09 | 17.20 | 13.61 |
October | 0.989016E+10 | 11037.32 | 20-OCT-16:00 | 21.30 | 12.72 | 0.189170E+10 | 2606.58 | 12-OCT-09:09 | 21.30 | 12.72 |
November | 0.741842E+10 | 10370.96 | 03-NOV-16:00 | 15.00 | 9.33 | 0.169033E+10 | 2606.53 | 08-NOV-14:30 | 13.90 | 12.22 |
December | 0.549484E+10 | 6537.89 | 07-DEC-16:10 | -5.4 | -8.6 | 0.149732E+10 | 2313.55 | 07-DEC-14:00 | -5.4 | -8.6 |
Annual Sum or Average | 0.138233E+12 | 0.217195E+11 | ||||||||
Minimum of Months | 0.446194E+10 | 6537.89 | -5.4 | -8.6 | 0.141714E+10 | 2313.55 | -5.4 | -8.6 | ||
Maximum of Months | 0.193639E+11 | 32637.84 | 21.30 | 18.69 | 0.215671E+10 | 2722.75 | 21.30 | 16.97 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258701E+10 | 6452.36 | 13-JAN-16:50 | 2.48 | 0.97 | 0.146373E+10 | 2234.04 | 13-JAN-14:00 | 2.48 | 0.97 |
February | 0.357090E+10 | 6978.14 | 24-FEB-17:00 | 7.20 | 5.13 | 0.135908E+10 | 2319.97 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.675584E+10 | 8927.19 | 24-MAR-16:00 | 10.60 | 5.50 | 0.174459E+10 | 2593.57 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.949060E+10 | 17839.77 | 17-APR-15:20 | 19.40 | 11.61 | 0.169544E+10 | 2606.66 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.145073E+11 | 19002.01 | 31-MAY-15:20 | 29.43 | 19.40 | 0.202646E+10 | 2606.69 | 09-MAY-13:09 | 29.43 | 19.40 |
June | 0.182208E+11 | 30369.39 | 12-JUN-06:03 | 17.88 | 17.07 | 0.205028E+10 | 2606.65 | 09-JUN-09:20 | 17.88 | 17.07 |
July | 0.191570E+11 | 29450.45 | 03-JUL-06:03 | 19.08 | 17.92 | 0.191658E+10 | 2606.67 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.190084E+11 | 20009.02 | 04-AUG-15:20 | 33.90 | 25.66 | 0.214861E+10 | 2606.72 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.139320E+11 | 19933.17 | 11-SEP-06:03 | 19.50 | 17.29 | 0.184886E+10 | 2606.71 | 06-SEP-09:39 | 19.50 | 17.29 |
October | 0.859892E+10 | 10442.07 | 20-OCT-16:00 | 21.30 | 12.72 | 0.174568E+10 | 2594.47 | 03-OCT-13:00 | 21.30 | 12.72 |
November | 0.552026E+10 | 9158.24 | 03-NOV-16:00 | 15.00 | 9.33 | 0.157546E+10 | 2575.83 | 03-NOV-13:00 | 15.00 | 9.33 |
December | 0.307132E+10 | 6317.57 | 01-DEC-16:10 | -2.1 | -4.3 | 0.142656E+10 | 2194.29 | 01-DEC-14:00 | -2.1 | -4.3 |
Annual Sum or Average | 0.124420E+12 | 0.210013E+11 | ||||||||
Minimum of Months | 0.258701E+10 | 6317.57 | -2.1 | -4.3 | 0.135908E+10 | 2194.29 | -2.1 | -4.3 | ||
Maximum of Months | 0.191570E+11 | 30369.39 | 33.90 | 25.66 | 0.214861E+10 | 2606.72 | 29.43 | 19.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23192099.09 | 977.26 | 14-JAN-17:02 | -7.4 | -8.6 | 0.300782E+09 | 406.85 | 18-JAN-10:09 | -13.4 | -13.8 |
February | 61665726.59 | 1199.85 | 24-FEB-16:30 | 7.75 | 5.51 | 0.274024E+09 | 431.04 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.577556E+09 | 1578.64 | 28-MAR-15:30 | 16.40 | 10.50 | 0.344046E+09 | 516.71 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.155273E+10 | 6917.01 | 16-APR-15:02 | 28.40 | 20.34 | 0.332509E+09 | 549.50 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.336981E+10 | 6346.48 | 31-MAY-14:50 | 29.90 | 19.65 | 0.417905E+09 | 549.51 | 09-MAY-13:09 | 29.90 | 19.65 |
June | 0.520117E+10 | 11611.42 | 25-JUN-17:11 | 31.50 | 21.73 | 0.429275E+09 | 549.76 | 26-JUN-13:39 | 31.50 | 21.88 |
July | 0.545259E+10 | 9193.74 | 02-JUL-18:42 | 27.38 | 20.97 | 0.404175E+09 | 549.50 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.514009E+10 | 6995.31 | 04-AUG-15:20 | 33.90 | 25.66 | 0.450813E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.307998E+10 | 6289.70 | 11-SEP-14:00 | 28.90 | 20.23 | 0.375155E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.118543E+10 | 1829.80 | 20-OCT-15:40 | 21.97 | 12.95 | 0.337325E+09 | 535.00 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.503928E+09 | 1549.03 | 03-NOV-15:40 | 15.37 | 9.43 | 0.313359E+09 | 512.96 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 10186616.11 | 993.33 | 02-DEC-17:03 | 1.70 | 0.90 | 0.292739E+09 | 406.82 | 12-DEC-14:50 | -15.7 | -16.2 |
Annual Sum or Average | 0.261583E+11 | 0.427211E+10 | ||||||||
Minimum of Months | 10186616.11 | 977.26 | -7.4 | -8.6 | 0.274024E+09 | 406.82 | -15.7 | -16.2 | ||
Maximum of Months | 0.545259E+10 | 11611.42 | 33.90 | 25.66 | 0.450813E+09 | 549.76 | 31.50 | 21.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54517847.49 | 1175.62 | 12-JAN-10:25 | -1.4 | -2.2 | 0.192539E+09 | 263.66 | 12-JAN-10:39 | -0.9 | -1.9 |
February | 0.190791E+09 | 1641.02 | 24-FEB-10:10 | 4.60 | 1.53 | 0.176785E+09 | 330.03 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.891200E+09 | 3228.50 | 28-MAR-09:25 | 8.60 | 5.36 | 0.226063E+09 | 347.88 | 28-MAR-09:50 | 9.53 | 5.99 |
April | 0.192865E+10 | 8229.16 | 18-APR-09:30 | 24.20 | 19.59 | 0.216672E+09 | 347.89 | 18-APR-09:09 | 24.20 | 19.59 |
May | 0.380526E+10 | 15217.10 | 29-MAY-09:32 | 23.33 | 18.40 | 0.268757E+09 | 348.34 | 31-MAY-09:39 | 26.83 | 19.51 |
June | 0.538864E+10 | 15337.37 | 25-JUN-08:32 | 25.37 | 20.95 | 0.270040E+09 | 348.54 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.571042E+10 | 15377.72 | 02-JUL-09:22 | 26.15 | 21.26 | 0.255990E+09 | 348.65 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.522727E+10 | 9096.98 | 02-AUG-09:00 | 23.90 | 20.06 | 0.285637E+09 | 348.36 | 02-AUG-09:39 | 25.03 | 20.70 |
September | 0.355049E+10 | 10505.84 | 03-SEP-10:32 | 18.70 | 13.50 | 0.241488E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.139351E+10 | 3396.21 | 20-OCT-09:30 | 13.70 | 9.50 | 0.218469E+09 | 347.87 | 20-OCT-09:09 | 13.70 | 9.50 |
November | 0.508026E+09 | 1620.28 | 04-NOV-09:40 | 8.13 | 4.42 | 0.196409E+09 | 316.47 | 03-NOV-13:00 | 8.13 | 4.42 |
December | 43596082.87 | 1164.98 | 05-DEC-09:45 | -6.2 | -8.3 | 0.186101E+09 | 261.45 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.286924E+11 | 0.273495E+10 | ||||||||
Minimum of Months | 43596082.87 | 1164.98 | -6.2 | -8.3 | 0.176785E+09 | 261.45 | -5.9 | -8.1 | ||
Maximum of Months | 0.571042E+10 | 15377.72 | 26.15 | 21.26 | 0.285637E+09 | 348.65 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765014E+09 | 5607.37 | 12-JAN-12:30 | 1.95 | 0.38 | 0.327063E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.109097E+10 | 8952.50 | 24-FEB-13:35 | 7.43 | 4.81 | 0.302257E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.202504E+10 | 9279.15 | 24-MAR-13:30 | 12.75 | 6.50 | 0.376076E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.334820E+10 | 19278.35 | 16-APR-13:42 | 27.62 | 20.47 | 0.347586E+09 | 549.98 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.489174E+10 | 14892.14 | 29-MAY-12:53 | 25.00 | 19.70 | 0.418163E+09 | 549.51 | 08-MAY-13:00 | 25.00 | 19.70 |
June | 0.648679E+10 | 15948.98 | 25-JUN-15:12 | 32.20 | 22.35 | 0.426286E+09 | 550.07 | 26-JUN-13:20 | 31.30 | 21.65 |
July | 0.712993E+10 | 17902.08 | 30-JUL-13:12 | 26.87 | 20.18 | 0.402969E+09 | 550.03 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.768434E+10 | 17871.49 | 13-AUG-12:32 | 24.27 | 19.51 | 0.449910E+09 | 550.06 | 11-AUG-13:30 | 24.27 | 19.51 |
September | 0.626052E+10 | 18229.59 | 17-SEP-13:32 | 26.67 | 18.01 | 0.382218E+09 | 557.75 | 07-SEP-13:20 | 26.67 | 18.01 |
October | 0.343356E+10 | 17734.82 | 01-OCT-14:02 | 19.07 | 12.30 | 0.371549E+09 | 549.58 | 20-OCT-13:50 | 22.47 | 12.96 |
November | 0.138126E+10 | 10920.89 | 03-NOV-13:30 | 15.85 | 10.76 | 0.330247E+09 | 549.51 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.845032E+09 | 6800.86 | 01-DEC-13:30 | -0.9 | -3.3 | 0.317082E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.453424E+11 | 0.445140E+10 | ||||||||
Minimum of Months | 0.765014E+09 | 5607.37 | -0.9 | -3.3 | 0.302257E+09 | 549.49 | 1.70 | 0.50 | ||
Maximum of Months | 0.768434E+10 | 19278.35 | 32.20 | 22.35 | 0.449910E+09 | 557.75 | 31.30 | 21.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100664E+09 | 1605.46 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192948E+09 | 297.87 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.250602E+09 | 3183.99 | 24-FEB-16:30 | 7.75 | 5.51 | 0.177681E+09 | 338.68 | 24-FEB-16:10 | 7.75 | 5.51 |
March | 0.859264E+09 | 3676.64 | 21-MAR-16:00 | -0.6 | -4.1 | 0.220477E+09 | 341.52 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.222937E+10 | 16688.00 | 16-APR-15:02 | 28.40 | 20.34 | 0.210355E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.374987E+10 | 14821.89 | 14-MAY-16:32 | 21.70 | 15.60 | 0.256082E+09 | 347.86 | 08-MAY-13:00 | 21.70 | 15.60 |
June | 0.528421E+10 | 17121.33 | 25-JUN-17:11 | 31.50 | 21.73 | 0.266488E+09 | 347.85 | 16-JUN-13:50 | 31.50 | 21.73 |
July | 0.570254E+10 | 17153.92 | 02-JUL-16:41 | 28.98 | 21.21 | 0.253564E+09 | 347.85 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.540508E+10 | 16289.75 | 13-AUG-16:32 | 25.20 | 20.49 | 0.281669E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.357082E+10 | 16048.59 | 04-SEP-16:42 | 22.20 | 14.41 | 0.230424E+09 | 347.86 | 06-SEP-09:50 | 25.13 | 18.36 |
October | 0.153640E+10 | 5920.66 | 20-OCT-15:30 | 22.30 | 13.06 | 0.214060E+09 | 347.82 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.578299E+09 | 3841.06 | 03-NOV-15:30 | 15.55 | 9.47 | 0.196273E+09 | 347.34 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.134221E+09 | 1594.74 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186915E+09 | 296.95 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.294013E+11 | 0.268694E+10 | ||||||||
Minimum of Months | 0.100664E+09 | 1594.74 | -1.5 | -4.1 | 0.177681E+09 | 296.95 | -1.6 | -4.0 | ||
Maximum of Months | 0.570254E+10 | 17153.92 | 31.50 | 21.73 | 0.281669E+09 | 347.86 | 31.50 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16650688.72 | 974.00 | 14-JAN-17:02 | -7.4 | -8.6 | 0.299974E+09 | 406.83 | 18-JAN-10:09 | -13.4 | -13.8 |
February | 32639707.77 | 1047.61 | 24-FEB-16:30 | 7.75 | 5.51 | 0.272897E+09 | 406.77 | 16-FEB-10:09 | 7.75 | 5.51 |
March | 0.440446E+09 | 1326.06 | 28-MAR-15:30 | 16.40 | 10.50 | 0.339006E+09 | 467.17 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.108179E+10 | 3354.34 | 18-APR-15:00 | 28.30 | 20.65 | 0.320073E+09 | 549.48 | 18-APR-09:00 | 28.30 | 20.65 |
May | 0.234893E+10 | 4205.64 | 31-MAY-15:00 | 30.00 | 19.70 | 0.407346E+09 | 549.49 | 08-MAY-13:00 | 30.00 | 19.70 |
June | 0.398454E+10 | 5738.70 | 26-JUN-14:30 | 31.40 | 21.97 | 0.429198E+09 | 549.50 | 20-JUN-13:00 | 31.40 | 21.97 |
July | 0.454365E+10 | 7558.39 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404278E+09 | 549.50 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.462796E+10 | 5824.41 | 04-AUG-15:30 | 33.90 | 25.83 | 0.453249E+09 | 570.38 | 04-AUG-07:49 | 33.90 | 25.83 |
September | 0.317923E+10 | 5625.95 | 11-SEP-14:00 | 28.90 | 20.23 | 0.388196E+09 | 549.50 | 06-SEP-09:09 | 28.90 | 20.23 |
October | 0.167936E+10 | 1847.55 | 01-OCT-14:02 | 19.07 | 12.30 | 0.357920E+09 | 540.13 | 11-OCT-13:00 | 17.20 | 12.37 |
November | 0.777050E+09 | 1512.44 | 03-NOV-15:40 | 15.37 | 9.43 | 0.323692E+09 | 517.96 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 12796185.63 | 987.32 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293748E+09 | 406.82 | 12-DEC-14:20 | -15.9 | -16.4 |
Annual Sum or Average | 0.227250E+11 | 0.428958E+10 | ||||||||
Minimum of Months | 12796185.63 | 974.00 | -7.4 | -8.6 | 0.272897E+09 | 406.77 | -15.9 | -16.4 | ||
Maximum of Months | 0.462796E+10 | 7558.39 | 33.90 | 25.83 | 0.453249E+09 | 570.38 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49580485.73 | 959.32 | 13-JAN-11:00 | 2.20 | 0.51 | 0.192843E+09 | 263.85 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 0.136292E+09 | 1207.62 | 24-FEB-10:10 | 4.60 | 1.53 | 0.176509E+09 | 306.86 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.689840E+09 | 1568.86 | 28-MAR-09:50 | 9.53 | 5.99 | 0.224245E+09 | 347.88 | 28-MAR-09:20 | 9.53 | 5.99 |
April | 0.135660E+10 | 5639.66 | 18-APR-09:30 | 24.20 | 19.59 | 0.213971E+09 | 347.88 | 13-APR-09:09 | 24.20 | 19.59 |
May | 0.275715E+10 | 6561.16 | 31-MAY-09:20 | 26.47 | 19.61 | 0.268988E+09 | 347.88 | 04-MAY-09:00 | 26.47 | 19.61 |
June | 0.445719E+10 | 11667.13 | 25-JUN-09:12 | 26.67 | 21.38 | 0.272016E+09 | 355.59 | 26-JUN-07:00 | 25.00 | 21.93 |
July | 0.505665E+10 | 13123.95 | 02-JUL-09:11 | 25.97 | 21.17 | 0.256721E+09 | 348.31 | 05-JUL-09:39 | 23.87 | 20.31 |
August | 0.490128E+10 | 8370.76 | 20-AUG-10:43 | 22.80 | 18.46 | 0.287565E+09 | 370.07 | 04-AUG-07:49 | 22.80 | 18.46 |
September | 0.360419E+10 | 10876.45 | 17-SEP-10:02 | 24.60 | 17.39 | 0.249536E+09 | 347.88 | 06-SEP-09:09 | 24.60 | 17.39 |
October | 0.164300E+10 | 2858.61 | 20-OCT-09:50 | 14.70 | 9.97 | 0.238307E+09 | 347.87 | 19-OCT-09:50 | 14.70 | 9.97 |
November | 0.699555E+09 | 1399.88 | 04-NOV-09:00 | 5.60 | 2.83 | 0.204496E+09 | 328.81 | 03-NOV-13:30 | 5.60 | 2.83 |
December | 77333324.39 | 1031.33 | 05-DEC-09:30 | -6.4 | -8.4 | 0.186969E+09 | 273.07 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.254287E+11 | 0.277216E+10 | ||||||||
Minimum of Months | 49580485.73 | 959.32 | -6.4 | -8.4 | 0.176509E+09 | 263.85 | -5.9 | -8.1 | ||
Maximum of Months | 0.505665E+10 | 13123.95 | 26.67 | 21.38 | 0.287565E+09 | 370.07 | 26.47 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113041E+09 | 1492.26 | 13-JAN-14:30 | 3.90 | 1.72 | 0.268231E+09 | 498.93 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.253843E+09 | 2330.21 | 24-FEB-14:30 | 8.05 | 5.40 | 0.260397E+09 | 549.51 | 24-FEB-14:09 | 8.05 | 5.40 |
March | 0.721027E+09 | 4564.15 | 24-MAR-14:00 | 13.30 | 6.51 | 0.338145E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.151979E+10 | 9951.64 | 18-APR-12:00 | 27.80 | 20.94 | 0.324832E+09 | 549.61 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.278523E+10 | 10379.91 | 31-MAY-12:00 | 29.40 | 19.85 | 0.397500E+09 | 549.50 | 22-MAY-13:00 | 29.40 | 19.85 |
June | 0.478546E+10 | 12025.11 | 26-JUN-11:10 | 30.10 | 22.03 | 0.418808E+09 | 554.67 | 26-JUN-12:09 | 30.68 | 21.60 |
July | 0.598079E+10 | 14810.82 | 30-JUL-13:02 | 26.78 | 20.36 | 0.401889E+09 | 549.71 | 05-JUL-13:00 | 26.78 | 20.36 |
August | 0.704917E+10 | 13075.39 | 06-AUG-14:52 | 19.40 | 12.05 | 0.450759E+09 | 567.68 | 04-AUG-12:09 | 19.40 | 12.05 |
September | 0.573629E+10 | 15641.20 | 17-SEP-13:21 | 26.40 | 17.95 | 0.384620E+09 | 602.65 | 07-SEP-12:09 | 26.40 | 17.95 |
October | 0.260677E+10 | 14191.63 | 01-OCT-14:02 | 19.07 | 12.30 | 0.372831E+09 | 549.56 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.100913E+10 | 10244.84 | 05-NOV-15:23 | 15.30 | 10.66 | 0.316614E+09 | 549.48 | 03-NOV-13:09 | 15.30 | 10.66 |
December | 0.279481E+09 | 1658.04 | 02-DEC-12:40 | 5.40 | 2.84 | 0.277049E+09 | 521.39 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.328400E+11 | 0.421167E+10 | ||||||||
Minimum of Months | 0.113041E+09 | 1492.26 | 3.90 | 1.72 | 0.260397E+09 | 498.93 | 3.90 | 1.72 | ||
Maximum of Months | 0.704917E+10 | 15641.20 | 30.10 | 22.03 | 0.450759E+09 | 602.65 | 30.68 | 21.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57353062.07 | 1223.87 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192883E+09 | 289.17 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.162468E+09 | 1837.88 | 24-FEB-16:30 | 7.75 | 5.51 | 0.176888E+09 | 338.68 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.633297E+09 | 1857.77 | 21-MAR-17:00 | -1.1 | -4.4 | 0.218674E+09 | 338.55 | 23-MAR-15:00 | 17.20 | 10.15 |
April | 0.154572E+10 | 9017.87 | 15-APR-17:04 | 29.72 | 18.80 | 0.210885E+09 | 347.84 | 18-APR-09:30 | 24.20 | 19.59 |
May | 0.259762E+10 | 8593.07 | 14-MAY-17:01 | 21.42 | 15.87 | 0.257276E+09 | 347.85 | 08-MAY-13:00 | 21.42 | 15.87 |
June | 0.425605E+10 | 13152.93 | 25-JUN-17:11 | 31.50 | 21.73 | 0.269890E+09 | 347.86 | 20-JUN-13:00 | 31.50 | 21.73 |
July | 0.498160E+10 | 14226.86 | 02-JUL-18:31 | 27.57 | 20.99 | 0.256396E+09 | 347.85 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.499046E+10 | 11410.68 | 06-AUG-15:32 | 18.67 | 11.76 | 0.287370E+09 | 347.87 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.350154E+10 | 13529.73 | 04-SEP-17:32 | 21.13 | 14.17 | 0.244494E+09 | 347.85 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.181099E+10 | 5040.48 | 11-OCT-16:00 | 17.80 | 11.96 | 0.230346E+09 | 347.84 | 02-OCT-13:00 | 17.80 | 11.96 |
November | 0.768460E+09 | 3172.04 | 03-NOV-15:40 | 15.37 | 9.43 | 0.204718E+09 | 347.67 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 0.121024E+09 | 1284.22 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187761E+09 | 299.51 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.254266E+11 | 0.273758E+10 | ||||||||
Minimum of Months | 57353062.07 | 1223.87 | -1.6 | -4.4 | 0.176888E+09 | 289.17 | -1.7 | -4.1 | ||
Maximum of Months | 0.499046E+10 | 14226.86 | 31.50 | 21.73 | 0.287370E+09 | 347.87 | 31.50 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39463178.49 | 1056.11 | 13-JAN-14:40 | 3.90 | 1.72 | 0.302608E+09 | 414.13 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.126904E+09 | 1186.07 | 24-FEB-16:30 | 7.75 | 5.51 | 0.276257E+09 | 437.81 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.815657E+09 | 1548.98 | 28-MAR-15:30 | 16.40 | 10.50 | 0.351886E+09 | 527.88 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.178554E+10 | 5465.01 | 18-APR-15:00 | 28.30 | 20.65 | 0.344734E+09 | 549.49 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.345521E+10 | 5811.75 | 31-MAY-14:50 | 29.90 | 19.65 | 0.426484E+09 | 549.51 | 09-MAY-13:09 | 29.90 | 19.65 |
June | 0.514475E+10 | 10518.15 | 25-JUN-18:21 | 30.25 | 21.63 | 0.433133E+09 | 549.86 | 27-JUN-13:20 | 29.60 | 22.39 |
July | 0.542750E+10 | 10421.76 | 02-JUL-18:31 | 27.57 | 20.99 | 0.405086E+09 | 549.81 | 03-JUL-13:00 | 29.40 | 24.07 |
August | 0.518267E+10 | 7267.16 | 04-AUG-07:33 | 25.03 | 24.26 | 0.453513E+09 | 565.56 | 04-AUG-07:40 | 25.03 | 24.26 |
September | 0.330528E+10 | 6105.75 | 11-SEP-13:40 | 28.70 | 20.26 | 0.387666E+09 | 549.50 | 06-SEP-09:09 | 28.70 | 20.26 |
October | 0.161674E+10 | 2086.18 | 02-OCT-15:00 | 18.30 | 14.84 | 0.357996E+09 | 549.48 | 11-OCT-13:00 | 17.20 | 12.37 |
November | 0.734266E+09 | 1731.04 | 03-NOV-13:10 | 15.68 | 10.94 | 0.323768E+09 | 524.25 | 07-NOV-14:30 | 13.05 | 11.26 |
December | 17959793.22 | 975.44 | 02-DEC-17:03 | 1.70 | 0.90 | 0.293938E+09 | 406.81 | 11-DEC-14:39 | -19.4 | -20.0 |
Annual Sum or Average | 0.276519E+11 | 0.435707E+10 | ||||||||
Minimum of Months | 17959793.22 | 975.44 | 1.70 | 0.90 | 0.276257E+09 | 406.81 | -19.4 | -20.0 | ||
Maximum of Months | 0.542750E+10 | 10518.15 | 30.25 | 24.26 | 0.453513E+09 | 565.56 | 29.90 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75533098.29 | 1269.79 | 12-JAN-10:00 | -2.8 | -3.3 | 0.141907E+09 | 270.55 | 12-JAN-09:00 | -2.8 | -3.3 |
February | 0.266726E+09 | 1904.81 | 24-FEB-09:35 | 3.87 | 1.06 | 0.130937E+09 | 338.71 | 24-FEB-09:00 | 4.40 | 1.36 |
March | 0.109892E+10 | 4006.75 | 28-MAR-09:00 | 7.20 | 4.38 | 0.168755E+09 | 338.72 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.215724E+10 | 8316.68 | 18-APR-09:00 | 22.80 | 18.62 | 0.162539E+09 | 338.73 | 18-APR-07:10 | 22.80 | 18.62 |
May | 0.386298E+10 | 14690.60 | 28-MAY-08:42 | 19.22 | 16.73 | 0.199830E+09 | 339.00 | 31-MAY-08:00 | 26.10 | 19.69 |
June | 0.528731E+10 | 16660.45 | 25-JUN-09:01 | 26.38 | 21.26 | 0.200697E+09 | 358.57 | 26-JUN-07:00 | 25.00 | 21.93 |
July | 0.562488E+10 | 16714.93 | 02-JUL-08:31 | 25.03 | 20.84 | 0.189903E+09 | 339.32 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.516828E+10 | 15373.82 | 27-AUG-09:22 | 23.60 | 19.50 | 0.211375E+09 | 358.17 | 04-AUG-07:40 | 23.60 | 19.50 |
September | 0.375143E+10 | 14705.59 | 17-SEP-09:22 | 23.05 | 16.72 | 0.180840E+09 | 338.74 | 05-SEP-07:40 | 23.05 | 16.72 |
October | 0.176011E+10 | 4217.38 | 20-OCT-09:00 | 12.20 | 8.72 | 0.167607E+09 | 338.72 | 19-OCT-10:20 | 12.20 | 8.72 |
November | 0.713434E+09 | 2008.50 | 04-NOV-09:30 | 7.50 | 4.04 | 0.147677E+09 | 328.87 | 03-NOV-10:50 | 7.50 | 4.04 |
December | 98902748.22 | 1312.72 | 05-DEC-09:45 | -6.2 | -8.3 | 0.137475E+09 | 278.10 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.298657E+11 | 0.203954E+10 | ||||||||
Minimum of Months | 75533098.29 | 1269.79 | -6.2 | -8.3 | 0.130937E+09 | 270.55 | -6.1 | -8.3 | ||
Maximum of Months | 0.562488E+10 | 16714.93 | 26.38 | 21.26 | 0.211375E+09 | 358.57 | 26.10 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.888312E+09 | 6340.00 | 12-JAN-12:30 | 1.95 | 0.38 | 0.333471E+09 | 549.49 | 12-JAN-10:00 | 1.95 | 0.38 |
February | 0.127952E+10 | 9183.92 | 24-FEB-13:35 | 7.43 | 4.81 | 0.310640E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.236812E+10 | 9461.26 | 24-MAR-13:10 | 12.38 | 6.48 | 0.386831E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.358549E+10 | 16434.21 | 16-APR-11:53 | 25.00 | 19.68 | 0.359581E+09 | 549.93 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.490924E+10 | 10025.31 | 30-MAY-13:20 | 26.70 | 19.86 | 0.427026E+09 | 550.07 | 30-MAY-13:50 | 26.70 | 19.86 |
June | 0.633465E+10 | 16618.06 | 25-JUN-13:02 | 31.78 | 22.68 | 0.431599E+09 | 550.07 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.701663E+10 | 17481.03 | 30-JUL-13:02 | 26.78 | 20.36 | 0.404819E+09 | 550.03 | 05-JUL-13:50 | 26.78 | 20.36 |
August | 0.763114E+10 | 16492.22 | 13-AUG-12:32 | 24.27 | 19.51 | 0.453464E+09 | 550.28 | 21-AUG-13:50 | 29.32 | 21.76 |
September | 0.651588E+10 | 18304.73 | 17-SEP-13:21 | 26.40 | 17.95 | 0.393067E+09 | 566.79 | 07-SEP-13:20 | 26.40 | 17.95 |
October | 0.407117E+10 | 17074.32 | 01-OCT-13:12 | 18.80 | 12.23 | 0.388043E+09 | 549.65 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.174982E+10 | 11231.19 | 03-NOV-13:10 | 15.68 | 10.94 | 0.345021E+09 | 549.66 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.105944E+10 | 7364.40 | 01-DEC-13:13 | -0.9 | -3.3 | 0.322362E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.474094E+11 | 0.455593E+10 | ||||||||
Minimum of Months | 0.888312E+09 | 6340.00 | -0.9 | -3.3 | 0.310640E+09 | 549.49 | 1.70 | 0.38 | ||
Maximum of Months | 0.763114E+10 | 18304.73 | 31.78 | 22.68 | 0.453464E+09 | 566.79 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134065E+09 | 1568.08 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193755E+09 | 308.09 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.331248E+09 | 3256.36 | 24-FEB-16:30 | 7.75 | 5.51 | 0.179251E+09 | 344.46 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.107542E+10 | 4007.79 | 21-MAR-16:00 | -0.6 | -4.1 | 0.224309E+09 | 347.40 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.241604E+10 | 14374.17 | 15-APR-17:04 | 29.72 | 18.80 | 0.216623E+09 | 347.84 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.372128E+10 | 14854.21 | 07-MAY-16:32 | 18.33 | 12.66 | 0.263424E+09 | 347.86 | 08-MAY-13:00 | 19.40 | 13.87 |
June | 0.515399E+10 | 17011.38 | 25-JUN-17:41 | 31.20 | 21.79 | 0.270699E+09 | 347.86 | 20-JUN-13:00 | 31.20 | 21.79 |
July | 0.558743E+10 | 16540.17 | 02-JUL-18:31 | 27.57 | 20.99 | 0.255554E+09 | 347.85 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.532944E+10 | 15137.36 | 13-AUG-16:32 | 25.20 | 20.49 | 0.285439E+09 | 347.86 | 08-AUG-09:09 | 25.20 | 20.49 |
September | 0.370039E+10 | 15115.58 | 17-SEP-14:42 | 27.20 | 18.12 | 0.238909E+09 | 347.85 | 06-SEP-09:09 | 27.20 | 18.12 |
October | 0.195493E+10 | 5928.33 | 11-OCT-16:00 | 17.80 | 11.96 | 0.223349E+09 | 347.83 | 11-OCT-13:00 | 17.80 | 11.96 |
November | 0.807654E+09 | 4009.46 | 03-NOV-15:30 | 15.55 | 9.47 | 0.202083E+09 | 347.76 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.177195E+09 | 1572.67 | 01-DEC-15:50 | -1.6 | -4.0 | 0.188393E+09 | 309.25 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.303891E+11 | 0.274179E+10 | ||||||||
Minimum of Months | 0.134065E+09 | 1568.08 | -1.6 | -4.1 | 0.179251E+09 | 308.09 | -1.7 | -4.1 | ||
Maximum of Months | 0.558743E+10 | 17011.38 | 31.20 | 21.79 | 0.285439E+09 | 347.86 | 31.20 | 21.79 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235553E+09 | 11015.33 | 02-JAN-05:01 | -4.5 |
February | 20037726.18 | 7328.38 | 06-FEB-06:01 | -15.0 |
March | 120412.94 | 2006.88 | 06-MAR-07:01 | -12.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 2499509.84 | 6198.50 | 27-NOV-07:01 | -9.4 |
December | 7093725.78 | 6319.24 | 26-DEC-07:01 | -6.6 |
Annual Sum or Average | 0.265305E+09 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.235553E+09 | 11015.33 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113075E+11 | 18450.51 | 31-JAN-06:10 | -30.6 |
February | 0.711425E+10 | 18915.55 | 03-FEB-06:10 | -33.9 |
March | 0.373215E+10 | 15555.16 | 06-MAR-06:09 | -14.1 |
April | 0.155855E+10 | 13232.93 | 03-APR-05:07 | -7.2 |
May | 0.333860E+09 | 4547.67 | 14-MAY-07:10 | 11.57 |
June | 0.151161E+09 | 3688.43 | 03-JUN-05:05 | 5.78 |
July | 79842925.50 | 3643.36 | 23-JUL-07:00 | 14.40 |
August | 0.135497E+09 | 3494.76 | 07-AUG-05:03 | 8.80 |
September | 0.560167E+09 | 6655.09 | 30-SEP-05:03 | 0.10 |
October | 0.138743E+10 | 8024.04 | 23-OCT-06:01 | -3.0 |
November | 0.465100E+10 | 16077.09 | 28-NOV-06:09 | -18.2 |
December | 0.868101E+10 | 17285.52 | 11-DEC-06:10 | -22.1 |
Annual Sum or Average | 0.396924E+11 | |||
Minimum of Months | 79842925.50 | 3494.76 | -33.9 | |
Maximum of Months | 0.113075E+11 | 18915.55 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456493E+10 | 10252.03 | 02-JAN-08:11 | -7.6 |
February | 0.283099E+10 | 9735.74 | 06-FEB-08:05 | -14.8 |
March | 0.175680E+10 | 7817.74 | 06-MAR-07:14 | -12.6 |
April | 0.689651E+09 | 6965.89 | 03-APR-06:11 | -7.0 |
May | 88103247.77 | 3846.44 | 21-MAY-16:02 | 18.72 |
June | 27843359.60 | 4543.60 | 11-JUN-15:11 | 33.13 |
July | 32286430.17 | 3946.31 | 02-JUL-15:11 | 29.40 |
August | 19239034.88 | 3868.08 | 13-AUG-15:12 | 25.93 |
September | 0.136565E+09 | 4829.05 | 17-SEP-10:02 | 24.60 |
October | 0.783055E+09 | 6717.93 | 29-OCT-13:23 | 13.35 |
November | 0.200615E+10 | 9226.27 | 27-NOV-07:50 | -9.4 |
December | 0.354507E+10 | 10157.53 | 11-DEC-08:07 | -21.7 |
Annual Sum or Average | 0.164807E+11 | |||
Minimum of Months | 19239034.88 | 3846.44 | -21.7 | |
Maximum of Months | 0.456493E+10 | 10252.03 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323316E+10 | 8549.08 | 02-JAN-08:45 | -8.1 |
February | 0.195392E+10 | 5729.28 | 06-FEB-06:12 | -15.0 |
March | 0.116050E+10 | 3955.76 | 06-MAR-09:15 | -8.9 |
April | 0.368423E+09 | 3043.71 | 03-APR-08:00 | -6.1 |
May | 22005434.51 | 2440.99 | 14-MAY-15:06 | 21.70 |
June | 17067108.20 | 1919.94 | 25-JUN-15:12 | 32.20 |
July | 29205616.19 | 2594.25 | 02-JUL-15:11 | 29.40 |
August | 21406761.41 | 2454.13 | 06-AUG-11:38 | 15.93 |
September | 49141107.02 | 3798.78 | 29-SEP-05:02 | 0.92 |
October | 0.210553E+09 | 7065.34 | 23-OCT-05:01 | -2.7 |
November | 0.123973E+10 | 5652.29 | 27-NOV-07:01 | -9.4 |
December | 0.241795E+10 | 5373.29 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.107231E+11 | |||
Minimum of Months | 17067108.20 | 1919.94 | -21.7 | |
Maximum of Months | 0.323316E+10 | 8549.08 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165589E+10 | 19143.34 | 02-JAN-05:01 | -4.5 |
February | 0.693297E+09 | 17718.04 | 06-FEB-05:01 | -14.5 |
March | 0.127171E+09 | 15633.75 | 06-MAR-06:01 | -14.1 |
April | 29514580.38 | 14788.85 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.353438E+09 | 17592.05 | 27-NOV-05:01 | -9.4 |
December | 0.805510E+09 | 17818.55 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.366483E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.165589E+10 | 19143.34 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591998E+10 | 26823.74 | 30-JAN-05:11 | -28.0 |
February | 0.316581E+10 | 26129.05 | 06-FEB-05:01 | -14.5 |
March | 0.110393E+10 | 25581.67 | 06-MAR-05:11 | -15.2 |
April | 0.255678E+09 | 24496.77 | 03-APR-04:11 | -6.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4721380.58 | 19407.80 | 30-SEP-06:03 | 0.60 |
October | 71243906.23 | 21186.04 | 16-OCT-05:01 | 0.48 |
November | 0.184056E+10 | 26422.91 | 27-NOV-05:11 | -9.4 |
December | 0.392568E+10 | 26763.69 | 11-DEC-00:02 | -21.7 |
Annual Sum or Average | 0.162876E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.0 | |
Maximum of Months | 0.591998E+10 | 26823.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.951385E+10 | 11083.70 | 30-JAN-05:11 | -28.0 |
February | 0.563307E+10 | 10827.81 | 02-FEB-03:12 | -35.0 |
March | 0.252854E+10 | 10485.25 | 06-MAR-04:32 | -15.8 |
April | 0.668535E+09 | 9972.83 | 03-APR-04:11 | -6.9 |
May | 9996611.35 | 7703.39 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 65409715.83 | 8552.24 | 30-SEP-05:01 | 0.10 |
October | 0.439107E+09 | 8845.01 | 23-OCT-05:01 | -2.7 |
November | 0.338224E+10 | 10528.81 | 26-NOV-01:12 | -24.4 |
December | 0.708049E+10 | 10831.10 | 10-DEC-23:22 | -21.4 |
Annual Sum or Average | 0.293212E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.951385E+10 | 11083.70 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563105E+10 | 10434.42 | 30-JAN-05:11 | -28.0 |
February | 0.310637E+10 | 10060.50 | 02-FEB-03:12 | -35.0 |
March | 0.131989E+10 | 9647.13 | 06-MAR-04:32 | -15.8 |
April | 0.357591E+09 | 9117.78 | 03-APR-04:11 | -6.9 |
May | 2162440.41 | 6159.13 | 02-MAY-06:02 | 2.30 |
June | 96098.02 | 131.58 | 06-JUN-06:05 | 11.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 31977543.78 | 7349.77 | 30-SEP-05:01 | 0.10 |
October | 0.223536E+09 | 7777.15 | 23-OCT-05:01 | -2.7 |
November | 0.201170E+10 | 9733.05 | 27-NOV-01:12 | -11.5 |
December | 0.427064E+10 | 10085.78 | 10-DEC-23:22 | -21.4 |
Annual Sum or Average | 0.169550E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.563105E+10 | 10434.42 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643382E+10 | 13826.53 | 30-JAN-05:11 | -28.0 |
February | 0.348652E+10 | 13346.99 | 02-FEB-03:12 | -35.0 |
March | 0.180589E+10 | 12953.21 | 06-MAR-04:32 | -15.8 |
April | 0.551159E+09 | 12370.22 | 03-APR-04:11 | -6.9 |
May | 11732610.22 | 9037.30 | 02-MAY-06:02 | 2.30 |
June | 382693.76 | 1913.47 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 49319871.58 | 10190.53 | 30-SEP-05:01 | 0.10 |
October | 0.278493E+09 | 10657.16 | 16-OCT-05:01 | 0.48 |
November | 0.236243E+10 | 13128.00 | 27-NOV-01:12 | -11.5 |
December | 0.525920E+10 | 13399.96 | 11-DEC-00:42 | -21.7 |
Annual Sum or Average | 0.202389E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.643382E+10 | 13826.53 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583645E+10 | 10970.57 | 30-JAN-05:11 | -28.0 |
February | 0.329960E+10 | 10571.85 | 02-FEB-03:12 | -35.0 |
March | 0.148094E+10 | 10058.73 | 06-MAR-04:32 | -15.8 |
April | 0.388174E+09 | 9553.83 | 03-APR-04:11 | -6.9 |
May | 9728974.09 | 6513.76 | 02-MAY-06:02 | 2.30 |
June | 1033576.46 | 2403.91 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 48922011.51 | 7737.38 | 30-SEP-05:01 | 0.10 |
October | 0.263649E+09 | 8090.13 | 23-OCT-05:01 | -2.7 |
November | 0.208996E+10 | 10173.43 | 27-NOV-01:12 | -11.5 |
December | 0.441098E+10 | 10597.61 | 10-DEC-23:22 | -21.4 |
Annual Sum or Average | 0.178294E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.583645E+10 | 10970.57 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678437E+10 | 8250.68 | 30-JAN-05:11 | -28.0 |
February | 0.422993E+10 | 8092.54 | 02-FEB-03:12 | -35.0 |
March | 0.191922E+10 | 7620.80 | 06-MAR-05:01 | -15.4 |
April | 0.509012E+09 | 7385.99 | 03-APR-04:01 | -6.8 |
May | 4874481.53 | 6051.61 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1868929.41 | 5486.21 | 30-SEP-06:03 | 0.60 |
October | 21756884.56 | 6091.02 | 16-OCT-06:02 | -0.4 |
November | 0.147049E+10 | 7724.94 | 27-NOV-05:01 | -9.4 |
December | 0.409076E+10 | 8041.70 | 10-DEC-23:22 | -21.4 |
Annual Sum or Average | 0.190323E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.678437E+10 | 8250.68 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392330E+10 | 7745.48 | 30-JAN-05:11 | -28.0 |
February | 0.216873E+10 | 7418.69 | 02-FEB-03:12 | -35.0 |
March | 0.857678E+09 | 6955.85 | 06-MAR-05:01 | -15.4 |
April | 0.216817E+09 | 6703.57 | 03-APR-04:01 | -6.8 |
May | 286243.86 | 2385.37 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 630405.46 | 2358.52 | 30-SEP-06:03 | 0.60 |
October | 8810173.28 | 5059.87 | 27-OCT-06:02 | 0.25 |
November | 0.806357E+09 | 7112.22 | 27-NOV-05:01 | -9.4 |
December | 0.239232E+10 | 7427.51 | 10-DEC-23:22 | -21.4 |
Annual Sum or Average | 0.103749E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.392330E+10 | 7745.48 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862656E+10 | 14528.32 | 31-JAN-07:10 | -30.5 |
February | 0.546309E+10 | 15439.71 | 02-FEB-07:10 | -36.7 |
March | 0.404607E+10 | 11658.02 | 06-MAR-07:50 | -12.3 |
April | 0.189334E+10 | 10852.82 | 03-APR-06:50 | -6.8 |
May | 0.482114E+09 | 8432.97 | 02-MAY-06:10 | 2.30 |
June | 0.154870E+09 | 7170.27 | 02-JUN-06:30 | 7.50 |
July | 1658770.76 | 3809.77 | 24-JUL-06:07 | 12.35 |
August | 17116212.79 | 6908.94 | 16-AUG-06:06 | 9.97 |
September | 0.337378E+09 | 8570.41 | 29-SEP-06:10 | 0.10 |
October | 0.884825E+09 | 8939.26 | 23-OCT-06:10 | -3.0 |
November | 0.317180E+10 | 12481.24 | 28-NOV-07:50 | -16.9 |
December | 0.637823E+10 | 13459.23 | 11-DEC-07:10 | -21.7 |
Annual Sum or Average | 0.314571E+11 | |||
Minimum of Months | 1658770.76 | 3809.77 | -36.7 | |
Maximum of Months | 0.862656E+10 | 15439.71 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405648E+10 | 8030.87 | 30-JAN-05:11 | -28.0 |
February | 0.223217E+10 | 7693.04 | 02-FEB-03:12 | -35.0 |
March | 0.964739E+09 | 7195.57 | 06-MAR-05:01 | -15.4 |
April | 0.194354E+09 | 6998.62 | 03-APR-04:01 | -6.8 |
May | 2230345.75 | 5132.56 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2455454.18 | 5042.31 | 30-SEP-06:03 | 0.60 |
October | 9458102.37 | 5201.91 | 16-OCT-06:02 | -0.4 |
November | 0.849829E+09 | 7376.03 | 27-NOV-05:01 | -9.4 |
December | 0.245249E+10 | 7727.53 | 11-DEC-00:42 | -21.7 |
Annual Sum or Average | 0.107642E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.405648E+10 | 8030.87 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.621100E+10 | 8606.67 | 30-JAN-03:22 | -26.9 |
February | 0.343519E+10 | 8704.33 | 02-FEB-04:12 | -35.4 |
March | 0.116593E+10 | 8138.79 | 06-MAR-05:01 | -15.4 |
April | 0.223416E+09 | 7989.75 | 03-APR-04:01 | -6.8 |
May | 506988.31 | 4224.90 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 5778303.56 | 6412.36 | 29-SEP-06:02 | 0.10 |
October | 56134021.74 | 6737.89 | 16-OCT-05:01 | 0.48 |
November | 0.177540E+10 | 8458.08 | 26-NOV-04:53 | -25.0 |
December | 0.420860E+10 | 8587.54 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.170820E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.621100E+10 | 8704.33 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362279E+10 | 8290.93 | 30-JAN-03:22 | -26.9 |
February | 0.185027E+10 | 8396.08 | 02-FEB-04:12 | -35.4 |
March | 0.614194E+09 | 7682.88 | 06-MAR-05:01 | -15.4 |
April | 0.124423E+09 | 7531.07 | 03-APR-04:01 | -6.8 |
May | 287675.43 | 2397.30 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4174860.14 | 5358.43 | 29-SEP-06:02 | 0.10 |
October | 34654864.56 | 5548.54 | 16-OCT-05:01 | 0.48 |
November | 0.105262E+10 | 7873.20 | 24-NOV-05:01 | -14.7 |
December | 0.258109E+10 | 8327.97 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.988451E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.362279E+10 | 8396.08 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373505E+10 | 10677.16 | 30-JAN-04:42 | -27.7 |
February | 0.179476E+10 | 10719.50 | 02-FEB-04:53 | -36.1 |
March | 0.748627E+09 | 10099.34 | 06-MAR-05:01 | -15.4 |
April | 0.165793E+09 | 9836.99 | 03-APR-04:01 | -6.8 |
May | 729863.62 | 5140.39 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4779824.65 | 7454.56 | 29-SEP-06:02 | 0.10 |
October | 34764260.19 | 7624.01 | 23-OCT-06:01 | -3.0 |
November | 0.110038E+10 | 10470.69 | 27-NOV-00:53 | -11.7 |
December | 0.294268E+10 | 10746.17 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.105276E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.373505E+10 | 10746.17 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372508E+10 | 8435.66 | 30-JAN-03:22 | -26.9 |
February | 0.193430E+10 | 8568.20 | 02-FEB-04:12 | -35.4 |
March | 0.660119E+09 | 7809.12 | 06-MAR-05:01 | -15.4 |
April | 0.119826E+09 | 7697.84 | 03-APR-04:01 | -6.8 |
May | 1225175.73 | 5357.26 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6050411.44 | 5440.21 | 29-SEP-06:02 | 0.10 |
October | 39852993.41 | 5930.31 | 16-OCT-05:01 | 0.48 |
November | 0.108351E+10 | 8051.00 | 24-NOV-05:01 | -14.7 |
December | 0.261452E+10 | 8492.42 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.101845E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.372508E+10 | 8568.20 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.852120E+09 | 1358.45 | 02-JAN-16:19 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.712532E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.771319E+09 | 947.97 | 01-MAR-16:40 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.665929E+09 | 947.97 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.688682E+09 | 711.15 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.681984E+09 | 774.31 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.639876E+09 | 774.31 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.720190E+09 | 711.15 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.676546E+09 | 947.97 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.747161E+09 | 1358.45 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.824577E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.880760E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886167E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.639876E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.880760E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523869E+09 | 860.01 | 02-JAN-16:19 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.441729E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485945E+09 | 640.13 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420166E+09 | 490.21 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440149E+09 | 450.21 | 09-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.435068E+09 | 450.21 | 05-JUN-15:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407334E+09 | 450.21 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.458663E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.427874E+09 | 490.21 | 13-SEP-15:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463910E+09 | 860.01 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511661E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.536110E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555248E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407334E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.536110E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.802946E+09 | 1358.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.678630E+09 | 1184.79 | 14-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762328E+09 | 947.97 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.664966E+09 | 947.97 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.693913E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.687182E+09 | 774.31 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.643726E+09 | 774.31 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.724920E+09 | 711.15 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.672158E+09 | 947.97 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.722756E+09 | 1358.45 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.788595E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.815665E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.865779E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.643726E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.815665E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.521097E+09 | 859.95 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.438083E+09 | 750.02 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485477E+09 | 600.10 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420540E+09 | 600.10 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.436726E+09 | 450.19 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431820E+09 | 490.17 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405975E+09 | 490.17 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.456827E+09 | 490.17 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.425577E+09 | 600.10 | 12-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467269E+09 | 859.95 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.507131E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.532250E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552877E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405975E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.532250E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846508E+09 | 1358.45 | 02-JAN-16:19 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.707752E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.769477E+09 | 947.97 | 01-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.664444E+09 | 947.97 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.687808E+09 | 711.15 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.681288E+09 | 774.31 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.639471E+09 | 774.31 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.719430E+09 | 711.15 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.675209E+09 | 947.97 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.744021E+09 | 1358.45 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.820386E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.873466E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.882926E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.639471E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.873466E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522032E+09 | 860.01 | 02-JAN-16:19 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.439798E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485044E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419591E+09 | 490.21 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.439495E+09 | 450.21 | 09-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.434559E+09 | 450.21 | 05-JUN-15:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.406991E+09 | 450.21 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.458106E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.427141E+09 | 490.21 | 13-SEP-15:39 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.462866E+09 | 860.01 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.510257E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.533529E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553941E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.406991E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.533529E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.801308E+09 | 1358.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.677648E+09 | 1184.79 | 14-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.761477E+09 | 947.97 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.663534E+09 | 947.97 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.693014E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.686090E+09 | 774.31 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.642842E+09 | 774.31 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.723728E+09 | 711.15 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.671145E+09 | 947.97 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.721752E+09 | 1358.45 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.787102E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.812205E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.864185E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.642842E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.812205E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.519221E+09 | 859.95 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.436684E+09 | 750.02 | 14-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.484446E+09 | 600.10 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.419510E+09 | 600.10 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.436142E+09 | 450.19 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431234E+09 | 490.17 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405570E+09 | 490.17 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.456284E+09 | 490.17 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.424763E+09 | 600.10 | 12-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.466178E+09 | 859.95 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.505576E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.530049E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.551566E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405570E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.530049E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.852120E+09 | 1358.45 | 02-JAN-16:19 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.712532E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.771319E+09 | 947.97 | 01-MAR-16:40 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.665916E+09 | 947.97 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.688682E+09 | 711.15 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.681984E+09 | 774.31 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.639876E+09 | 774.31 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.720190E+09 | 711.15 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.676546E+09 | 947.97 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.747161E+09 | 1358.45 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.824577E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.880760E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886166E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.639876E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.880760E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523869E+09 | 860.01 | 02-JAN-16:19 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.441729E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485945E+09 | 640.13 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420166E+09 | 490.21 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.440149E+09 | 450.21 | 09-MAY-15:20 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.435068E+09 | 450.21 | 05-JUN-15:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.407334E+09 | 450.21 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.458663E+09 | 410.22 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.427874E+09 | 490.21 | 13-SEP-15:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.463910E+09 | 860.01 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511661E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.536110E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555248E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.407334E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.536110E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.802946E+09 | 1358.45 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.678630E+09 | 1184.79 | 14-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.762328E+09 | 947.97 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.664953E+09 | 947.97 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.693913E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.687182E+09 | 774.31 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.643726E+09 | 774.31 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.724920E+09 | 711.15 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.672158E+09 | 947.97 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.722743E+09 | 1358.45 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.788595E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.815665E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.865776E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.643726E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.815665E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.521097E+09 | 859.95 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.438083E+09 | 750.02 | 10-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.485477E+09 | 600.10 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420540E+09 | 600.10 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.436726E+09 | 450.19 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.431820E+09 | 490.17 | 05-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.405975E+09 | 490.17 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.456827E+09 | 490.17 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.425577E+09 | 600.10 | 12-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467269E+09 | 859.95 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.507131E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.532250E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552877E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.405975E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.532250E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.852120E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129194E+10 |
February | 0.901968E+09 | 0.712532E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946902E+09 |
March | 0.107774E+10 | 0.771319E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816814E+09 |
April | 0.956342E+09 | 0.665929E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4601426.15 | 0.512090E+09 |
May | 0.103597E+10 | 0.688682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1586128.24 | 0.292093E+09 |
June | 0.103308E+10 | 0.681984E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20825472.46 | 0.171934E+09 |
July | 0.959235E+09 | 0.639876E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7177217.01 | 0.125791E+09 |
August | 0.107774E+10 | 0.720190E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7947228.01 | 0.169294E+09 |
September | 0.956342E+09 | 0.676546E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6435054.06 | 0.259655E+09 |
October | 0.994195E+09 | 0.747161E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483576E+09 |
November | 0.984487E+09 | 0.824577E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804638E+09 |
December | 0.959235E+09 | 0.880760E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108210E+10 |
Annual Sum or Average | 0.119305E+11 | 0.886167E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48572525.92 | 0.695682E+10 |
Minimum of Months | 0.901968E+09 | 0.639876E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125791E+09 |
Maximum of Months | 0.107774E+10 | 0.880760E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20825472.46 | 0.129194E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.523869E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862686E+09 |
February | 0.571020E+09 | 0.441729E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634184E+09 |
March | 0.682301E+09 | 0.485945E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550709E+09 |
April | 0.605444E+09 | 0.420166E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3331609.83 | 0.350287E+09 |
May | 0.655854E+09 | 0.440149E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057327.87 | 0.198332E+09 |
June | 0.654023E+09 | 0.435068E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14102573.73 | 0.115481E+09 |
July | 0.607275E+09 | 0.407334E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4766164.16 | 84643148.44 |
August | 0.682301E+09 | 0.458663E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5317531.78 | 0.113267E+09 |
September | 0.605444E+09 | 0.427874E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4165138.18 | 0.178016E+09 |
October | 0.629407E+09 | 0.463910E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331949E+09 |
November | 0.623262E+09 | 0.511661E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538918E+09 |
December | 0.607275E+09 | 0.536110E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723792E+09 |
Annual Sum or Average | 0.755301E+10 | 0.555248E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32740345.57 | 0.468226E+10 |
Minimum of Months | 0.571020E+09 | 0.407334E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84643148.44 |
Maximum of Months | 0.682301E+09 | 0.536110E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14102573.73 | 0.862686E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.802946E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130997E+10 |
February | 0.901968E+09 | 0.678630E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973839E+09 |
March | 0.107774E+10 | 0.762328E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850000E+09 |
April | 0.956342E+09 | 0.664966E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3835813.30 | 0.535936E+09 |
May | 0.103597E+10 | 0.693913E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1586107.67 | 0.297801E+09 |
June | 0.103308E+10 | 0.687182E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20630961.47 | 0.171306E+09 |
July | 0.959235E+09 | 0.643726E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6817365.55 | 0.126189E+09 |
August | 0.107774E+10 | 0.724920E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7673232.23 | 0.175086E+09 |
September | 0.956342E+09 | 0.672158E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5019891.99 | 0.277541E+09 |
October | 0.994195E+09 | 0.722756E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528137E+09 |
November | 0.984487E+09 | 0.788595E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831643E+09 |
December | 0.959235E+09 | 0.815665E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111039E+10 |
Annual Sum or Average | 0.119305E+11 | 0.865779E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45563372.22 | 0.718784E+10 |
Minimum of Months | 0.901968E+09 | 0.643726E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126189E+09 |
Maximum of Months | 0.107774E+10 | 0.815665E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20630961.47 | 0.130997E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.521097E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863277E+09 |
February | 0.570983E+09 | 0.438083E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637338E+09 |
March | 0.682256E+09 | 0.485477E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551927E+09 |
April | 0.605404E+09 | 0.420540E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2441674.10 | 0.354512E+09 |
May | 0.655811E+09 | 0.436726E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1061272.12 | 0.198448E+09 |
June | 0.653980E+09 | 0.431820E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13967896.93 | 0.116082E+09 |
July | 0.607235E+09 | 0.405975E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4776492.27 | 87537144.50 |
August | 0.682256E+09 | 0.456827E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5327311.39 | 0.117370E+09 |
September | 0.605404E+09 | 0.425577E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3921923.57 | 0.179092E+09 |
October | 0.629366E+09 | 0.467269E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330224E+09 |
November | 0.623221E+09 | 0.507131E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539437E+09 |
December | 0.607235E+09 | 0.532250E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724045E+09 |
Annual Sum or Average | 0.755252E+10 | 0.552877E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31496570.38 | 0.469929E+10 |
Minimum of Months | 0.570983E+09 | 0.405975E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87537144.50 |
Maximum of Months | 0.682256E+09 | 0.532250E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13967896.93 | 0.863277E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846508E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695956E+09 |
February | 0.901968E+09 | 0.707752E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517250E+09 |
March | 0.107774E+10 | 0.769477E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442855E+09 |
April | 0.956342E+09 | 0.664444E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4429071.43 | 0.271230E+09 |
May | 0.103597E+10 | 0.687808E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 896076.66 | 0.149686E+09 |
June | 0.103308E+10 | 0.681288E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13615097.23 | 90174905.51 |
July | 0.959235E+09 | 0.639471E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4606356.64 | 65713344.63 |
August | 0.107774E+10 | 0.719430E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4494489.28 | 92595440.94 |
September | 0.956342E+09 | 0.675209E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3864567.76 | 0.147763E+09 |
October | 0.994195E+09 | 0.744021E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287017E+09 |
November | 0.984487E+09 | 0.820386E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459767E+09 |
December | 0.959235E+09 | 0.873466E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596055E+09 |
Annual Sum or Average | 0.119305E+11 | 0.882926E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31905659.00 | 0.381606E+10 |
Minimum of Months | 0.901968E+09 | 0.639471E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65713344.63 |
Maximum of Months | 0.107774E+10 | 0.873466E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13615097.23 | 0.695956E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.522032E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465678E+09 |
February | 0.571020E+09 | 0.439798E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347737E+09 |
March | 0.682301E+09 | 0.485044E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301061E+09 |
April | 0.605444E+09 | 0.419591E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2457194.66 | 0.189487E+09 |
May | 0.655854E+09 | 0.439495E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574921.21 | 0.107382E+09 |
June | 0.654023E+09 | 0.434559E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7978935.46 | 63258031.04 |
July | 0.607275E+09 | 0.406991E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581574.78 | 46850780.47 |
August | 0.682301E+09 | 0.458106E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2896579.65 | 64619948.59 |
September | 0.605444E+09 | 0.427141E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2134659.33 | 0.104259E+09 |
October | 0.629407E+09 | 0.462866E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199976E+09 |
November | 0.623262E+09 | 0.510257E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308612E+09 |
December | 0.607275E+09 | 0.533529E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399239E+09 |
Annual Sum or Average | 0.755301E+10 | 0.553941E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18623865.09 | 0.259816E+10 |
Minimum of Months | 0.571020E+09 | 0.406991E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46850780.47 |
Maximum of Months | 0.682301E+09 | 0.533529E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7978935.46 | 0.465678E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.801308E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906770E+10 |
February | 0.901968E+09 | 0.677648E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689363E+10 |
March | 0.107774E+10 | 0.761477E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598428E+10 |
April | 0.956342E+09 | 0.663534E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21461041.97 | 0.372207E+10 |
May | 0.103597E+10 | 0.693014E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67292860.18 | 0.207413E+10 |
June | 0.103308E+10 | 0.686090E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260971E+09 | 0.113658E+10 |
July | 0.959235E+09 | 0.642842E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228902E+09 | 0.547957E+09 |
August | 0.107774E+10 | 0.723728E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324785E+09 | 0.822638E+09 |
September | 0.956342E+09 | 0.671145E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171697E+09 | 0.188701E+10 |
October | 0.994195E+09 | 0.721752E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372849E+10 |
November | 0.984487E+09 | 0.787102E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520201E+10 |
December | 0.959235E+09 | 0.812205E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722310E+10 |
Annual Sum or Average | 0.119305E+11 | 0.864185E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107511E+10 | 0.482896E+11 |
Minimum of Months | 0.901968E+09 | 0.642842E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547957E+09 |
Maximum of Months | 0.107774E+10 | 0.812205E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324785E+09 | 0.906770E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.519221E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465715E+09 |
February | 0.570983E+09 | 0.436684E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349104E+09 |
March | 0.682256E+09 | 0.484446E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301512E+09 |
April | 0.605404E+09 | 0.419510E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558420.56 | 0.193467E+09 |
May | 0.655811E+09 | 0.436142E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 594487.27 | 0.106887E+09 |
June | 0.653980E+09 | 0.431234E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7771164.77 | 63666845.70 |
July | 0.607235E+09 | 0.405570E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2543186.40 | 49520071.55 |
August | 0.682256E+09 | 0.456284E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2861527.20 | 67636533.04 |
September | 0.605404E+09 | 0.424763E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1963019.34 | 0.104981E+09 |
October | 0.629366E+09 | 0.466178E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198333E+09 |
November | 0.623221E+09 | 0.505576E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309059E+09 |
December | 0.607235E+09 | 0.530049E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399254E+09 |
Annual Sum or Average | 0.755252E+10 | 0.551566E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17291805.55 | 0.260914E+10 |
Minimum of Months | 0.570983E+09 | 0.405570E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49520071.55 |
Maximum of Months | 0.682256E+09 | 0.530049E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7771164.77 | 0.465715E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.852120E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108781E+10 |
February | 0.901968E+09 | 0.712532E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812383E+09 |
March | 0.107774E+10 | 0.771319E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709924E+09 |
April | 0.956342E+09 | 0.665916E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4396439.37 | 0.450606E+09 |
May | 0.103597E+10 | 0.688682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334065.10 | 0.254043E+09 |
June | 0.103308E+10 | 0.681984E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17962574.82 | 0.149514E+09 |
July | 0.959235E+09 | 0.639876E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6205803.12 | 0.108526E+09 |
August | 0.107774E+10 | 0.720190E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6714695.71 | 0.147301E+09 |
September | 0.956342E+09 | 0.676546E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5376450.96 | 0.230969E+09 |
October | 0.994195E+09 | 0.747161E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439285E+09 |
November | 0.984487E+09 | 0.824577E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705085E+09 |
December | 0.959235E+09 | 0.880760E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924655E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886166E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41990029.08 | 0.602010E+10 |
Minimum of Months | 0.901968E+09 | 0.639876E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108526E+09 |
Maximum of Months | 0.107774E+10 | 0.880760E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17962574.82 | 0.108781E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.523869E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726526E+09 |
February | 0.421807E+09 | 0.441729E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544279E+09 |
March | 0.502994E+09 | 0.485945E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478727E+09 |
April | 0.447140E+09 | 0.420166E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3082573.36 | 0.306408E+09 |
May | 0.484071E+09 | 0.440149E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 889794.36 | 0.171520E+09 |
June | 0.482240E+09 | 0.435068E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12387619.39 | 0.100167E+09 |
July | 0.448971E+09 | 0.407334E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4124226.74 | 72735444.82 |
August | 0.502994E+09 | 0.458663E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4553651.82 | 98284772.67 |
September | 0.447140E+09 | 0.427874E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3563148.86 | 0.156769E+09 |
October | 0.465148E+09 | 0.463910E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299190E+09 |
November | 0.460569E+09 | 0.511661E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471242E+09 |
December | 0.448971E+09 | 0.536110E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617935E+09 |
Annual Sum or Average | 0.557719E+10 | 0.555248E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28601014.52 | 0.404378E+10 |
Minimum of Months | 0.421807E+09 | 0.407334E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72735444.82 |
Maximum of Months | 0.502994E+09 | 0.536110E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12387619.39 | 0.726526E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.802946E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111058E+10 |
February | 0.901968E+09 | 0.678630E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839131E+09 |
March | 0.107774E+10 | 0.762328E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740575E+09 |
April | 0.956342E+09 | 0.664953E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3311173.43 | 0.470486E+09 |
May | 0.103597E+10 | 0.693913E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1333871.89 | 0.259153E+09 |
June | 0.103308E+10 | 0.687182E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17465503.46 | 0.149440E+09 |
July | 0.959235E+09 | 0.643726E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5721461.84 | 0.109354E+09 |
August | 0.107774E+10 | 0.724920E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6454420.16 | 0.152475E+09 |
September | 0.956342E+09 | 0.672158E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4202227.01 | 0.245182E+09 |
October | 0.994195E+09 | 0.722743E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474544E+09 |
November | 0.984487E+09 | 0.788595E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729891E+09 |
December | 0.959235E+09 | 0.815665E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952285E+09 |
Annual Sum or Average | 0.119305E+11 | 0.865776E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38488657.80 | 0.623310E+10 |
Minimum of Months | 0.901968E+09 | 0.643726E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109354E+09 |
Maximum of Months | 0.107774E+10 | 0.815665E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17465503.46 | 0.111058E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.521097E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726979E+09 |
February | 0.570983E+09 | 0.438083E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546578E+09 |
March | 0.682256E+09 | 0.485477E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479464E+09 |
April | 0.605404E+09 | 0.420540E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2100953.69 | 0.310757E+09 |
May | 0.655811E+09 | 0.436726E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 895973.81 | 0.172878E+09 |
June | 0.653980E+09 | 0.431820E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11648309.05 | 0.101244E+09 |
July | 0.607235E+09 | 0.405975E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3936453.63 | 75844738.04 |
August | 0.682256E+09 | 0.456827E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4428428.50 | 0.102420E+09 |
September | 0.605404E+09 | 0.425577E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3149543.99 | 0.158635E+09 |
October | 0.629366E+09 | 0.467269E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297894E+09 |
November | 0.623221E+09 | 0.507131E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472047E+09 |
December | 0.607235E+09 | 0.532250E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618162E+09 |
Annual Sum or Average | 0.755252E+10 | 0.552877E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26159662.67 | 0.406290E+10 |
Minimum of Months | 0.570983E+09 | 0.405975E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75844738.04 |
Maximum of Months | 0.682256E+09 | 0.532250E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11648309.05 | 0.726979E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146377E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110891E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982368E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5379670.50 | 0.628802E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235784.45 | 0.346453E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22497124.06 | 0.200901E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6195318.66 | 0.147018E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6246705.37 | 0.203356E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4872445.34 | 0.326081E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633200E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986797E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126670E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46427048.38 | 0.829436E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147018E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22497124.06 | 0.146377E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183221E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138046E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121783E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6792312.26 | 0.780313E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595953.22 | 0.439013E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28998227.47 | 0.254178E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8077413.17 | 0.185532E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8289484.47 | 0.255005E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7139593.96 | 0.401973E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760593E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120298E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156878E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60892984.55 | 0.102789E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185532E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28998227.47 | 0.183221E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191604E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142578E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125338E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3276154.29 | 0.798790E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186474.40 | 0.458551E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20568057.38 | 0.260825E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4201256.83 | 0.193336E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6455286.71 | 0.262676E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4569407.03 | 0.403914E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753067E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121305E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161188E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40256636.65 | 0.105513E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193336E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20568057.38 | 0.191604E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:19 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2528.58 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1769.73 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:40 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1355.10 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.51 | 15-APR-17:01 | 1007.25 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 31-MAY-13:00 | 692.60 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.18 | 11-JUN-15:26 | 575.63 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.14 | 02-JUL-15:40 | 264.65 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 | 04-AUG-16:40 | 349.86 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.18 | 17-SEP-15:00 | 518.22 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 715.35 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1937.15 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2965.54 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.65 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 262.18 | 2965.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:19 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1685.75 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1179.50 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 640.13 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 919.70 | 05-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 | 15-APR-17:10 | 671.57 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 09-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 31-MAY-13:00 | 463.83 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 05-JUN-15:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.65 | 18-JUN-16:20 | 383.89 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 | 02-JUL-15:30 | 181.53 | 09-JUL-10:10 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 04-AUG-16:40 | 238.95 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 13-SEP-15:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 17-SEP-15:00 | 343.19 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 478.09 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.71 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1976.85 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.53 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 185.65 | 1976.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2623.80 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 14-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1771.12 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1539.99 | 05-MAR-13:55 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 | 15-APR-17:10 | 1007.28 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 31-MAY-13:00 | 702.58 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.07 | 11-JUN-15:26 | 577.40 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.22 | 02-JUL-15:25 | 266.23 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 | 04-AUG-16:40 | 372.70 | 06-AUG-13:40 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 17-SEP-14:56 | 542.56 | 24-SEP-13:40 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 740.33 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1938.84 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2965.57 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.23 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 270.07 | 2965.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1685.79 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1179.07 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 910.44 | 05-MAR-14:50 |
April | 827.17 | 03-APR-09:09 | 600.10 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.73 | 15-APR-17:04 | 671.50 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 31-MAY-13:00 | 462.47 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.05 | 11-JUN-15:26 | 379.35 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.22 | 02-JUL-11:00 | 183.56 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 04-AUG-16:40 | 240.10 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 12-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 | 17-SEP-11:40 | 362.47 | 24-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 480.50 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.67 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1976.98 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.56 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 175.05 | 1976.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:19 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1342.49 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 943.60 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 744.22 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.69 | 15-APR-17:01 | 557.73 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 31-MAY-13:00 | 371.44 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.33 | 18-JUN-16:00 | 327.96 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.23 | 02-JUL-16:00 | 138.55 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 04-AUG-16:40 | 194.00 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 | 17-SEP-14:50 | 299.48 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 443.86 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1035.00 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1584.28 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.55 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 166.69 | 1584.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:19 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 910.28 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 629.16 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 507.18 | 05-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.33 | 15-APR-17:01 | 371.36 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 09-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 31-MAY-13:00 | 260.09 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 05-JUN-15:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.67 | 18-JUN-16:00 | 225.86 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 | 02-JUL-16:00 | 96.16 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 04-AUG-16:40 | 133.85 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 13-SEP-15:39 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | 17-SEP-14:50 | 204.09 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.32 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 689.92 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1054.96 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.16 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 108.67 | 1054.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43750.06 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 14-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 50420.58 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27545.77 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2907.97 | 18-APR-12:00 | 23006.47 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.04 | 31-MAY-12:00 | 14657.69 | 02-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5824.65 | 26-JUN-16:10 | 11042.24 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4457.99 | 26-JUL-16:10 | 8055.48 | 24-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6633.03 | 04-AUG-16:10 | 11058.09 | 07-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5314.28 | 07-SEP-16:05 | 16428.63 | 29-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19448.62 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 31641.58 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 35611.47 | 11-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8055.48 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6633.03 | 50420.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 895.02 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 14-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 628.99 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 505.77 | 12-MAR-16:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 | 15-APR-17:07 | 368.87 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 31-MAY-13:00 | 253.85 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.14 | 11-JUN-15:26 | 219.60 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 02-JUL-11:20 | 101.76 | 09-JUL-10:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 04-AUG-16:40 | 138.76 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 12-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 17-SEP-14:45 | 203.89 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 303.07 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 689.89 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1053.51 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.76 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 93.14 | 1053.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:19 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2103.33 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1479.37 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:40 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1179.99 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.11 | 15-APR-17:01 | 866.30 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 31-MAY-13:00 | 612.58 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.73 | 11-JUN-15:15 | 517.56 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.55 | 02-JUL-16:00 | 226.55 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 04-AUG-16:40 | 305.75 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.97 | 17-SEP-14:50 | 457.63 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 667.20 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1618.01 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2466.80 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.55 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 221.73 | 2466.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-16:19 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1414.18 | 29-JAN-11:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 985.93 | 10-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 640.13 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 840.04 | 05-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 490.21 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.71 | 15-APR-17:10 | 575.63 | 02-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 09-MAY-15:20 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 31-MAY-13:00 | 408.96 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 05-JUN-15:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.84 | 18-JUN-16:00 | 344.93 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.30 | 02-JUL-16:00 | 161.16 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 410.22 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 04-AUG-16:40 | 208.52 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 490.21 | 13-SEP-15:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 | 17-SEP-14:50 | 302.93 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 445.30 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1078.26 | 20-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.46 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.16 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.84 | 1644.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2269.11 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 14-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1480.27 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1341.86 | 05-MAR-13:55 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.60 | 15-APR-17:10 | 871.08 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 31-MAY-13:00 | 620.43 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.20 | 11-JUN-15:14 | 519.34 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.90 | 02-JUL-15:53 | 232.08 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 04-AUG-16:40 | 311.27 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 06-SEP-16:00 | 463.45 | 24-SEP-12:50 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 687.75 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1619.77 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2466.79 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.08 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 221.20 | 2466.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1402.17 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 10-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 985.69 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 803.91 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 | 15-APR-17:06 | 573.81 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 31-MAY-13:00 | 408.40 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 05-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.72 | 11-JUN-15:54 | 341.91 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 02-JUL-11:20 | 157.41 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 490.17 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 04-AUG-16:40 | 209.66 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 12-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.39 | 17-SEP-11:30 | 312.84 | 24-SEP-16:10 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 446.98 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1078.22 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.50 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.41 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 144.72 | 1644.50 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2837.26 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1964.81 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1640.25 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.71 | 15-APR-17:01 | 1269.10 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 31-MAY-13:00 | 853.31 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.85 | 11-JUN-15:00 | 727.49 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.28 | 02-JUL-15:00 | 296.59 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 | 04-AUG-16:40 | 403.84 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.35 | 17-SEP-15:00 | 635.71 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 984.27 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2092.32 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3438.24 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.85 | 3438.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3535.65 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2479.29 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2038.94 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.99 | 15-APR-17:01 | 1516.40 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 | 31-MAY-13:00 | 1077.64 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.28 | 11-JUN-15:00 | 913.30 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 | 02-JUL-15:00 | 370.39 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.69 | 04-AUG-16:40 | 507.20 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 | 17-SEP-15:00 | 802.21 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1188.39 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2593.27 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4282.82 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.28 | 4282.82 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3726.14 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2595.57 | 10-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2087.06 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.35 | 15-APR-17:01 | 1513.04 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | 31-MAY-13:00 | 1050.20 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.17 | 18-JUN-16:00 | 874.46 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.75 | 25-JUL-16:00 | 396.40 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.40 | 04-AUG-16:30 | 529.39 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 | 06-SEP-16:00 | 776.40 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1074.77 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2816.91 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4380.64 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.17 | 4380.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9883.08 | 13-JAN-17:00 | 12070.02 | 12887.96 | 27982.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11195.34 | 24-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16329.05 | 24-MAR-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37466.06 | 17-APR-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41558.02 | 30-MAY-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41468.11 | 19-JUN-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41606.36 | 10-JUL-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40557.47 | 21-AUG-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40951.07 | 12-SEP-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33856.22 | 23-OCT-05:01 | 5082.11 | 1693.87 | 59282.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18403.57 | 03-NOV-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11222.45 | 07-DEC-16:10 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9883.08 | 2541.06 | 1693.87 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41606.36 | 12070.02 | 12887.96 | 59282.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.73 |
February | 781.64 | 24-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.93 |
March | 2702.17 | 19-MAR-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.02 |
April | 8822.06 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 | 0.00 |
May | 9845.38 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 0.00 |
June | 11213.35 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 | 0.00 |
July | 10664.29 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
August | 11157.44 | 04-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 0.00 |
September | 10058.66 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 0.00 |
October | 4200.25 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 |
November | 2104.50 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.82 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11213.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 819.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3620.77 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.07 |
February | 3239.85 | 04-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.97 |
March | 2586.70 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.74 |
April | 3786.54 | 17-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4254.53 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 | 0.00 |
June | 5481.29 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 | 0.00 |
July | 5404.23 | 03-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.58 |
August | 5004.94 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 0.00 |
September | 4735.32 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2386.93 | 14-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.58 |
November | 2577.89 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1450.29 |
December | 2865.74 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2386.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5481.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 1450.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3241.20 | 06-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.66 |
February | 3940.93 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.21 |
March | 2924.25 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.99 |
April | 3881.71 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 | 0.00 |
May | 4415.97 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
June | 5765.65 | 26-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.16 | 0.00 |
July | 6001.87 | 03-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 |
August | 5332.16 | 04-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 | 0.00 |
September | 5376.06 | 11-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 0.00 |
October | 2910.17 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.09 |
November | 2634.09 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.42 |
December | 2555.06 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2555.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6001.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.86 | 794.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6647.67 | 13-JAN-17:00 | 12070.02 | 12887.96 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6911.36 | 24-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9372.45 | 24-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19232.30 | 17-APR-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30648.84 | 30-MAY-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32637.84 | 19-JUN-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31147.30 | 05-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28805.14 | 14-AUG-06:03 | 5082.11 | 8592.08 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32399.60 | 18-SEP-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11037.32 | 20-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10370.96 | 03-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6537.89 | 07-DEC-16:10 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6537.89 | 3176.32 | 3579.89 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32637.84 | 12070.02 | 12887.96 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6452.36 | 13-JAN-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6978.14 | 24-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8927.19 | 24-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17839.77 | 17-APR-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19002.01 | 31-MAY-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30369.39 | 12-JUN-06:03 | 5082.11 | 8592.08 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29450.45 | 03-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20009.02 | 04-AUG-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19933.17 | 11-SEP-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10442.07 | 20-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9158.24 | 03-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6317.57 | 01-DEC-16:10 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6317.57 | 3811.58 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30369.39 | 6035.01 | 8592.08 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 977.26 | 14-JAN-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.43 |
February | 1199.85 | 24-FEB-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.63 |
March | 1578.64 | 28-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 |
April | 6917.01 | 16-APR-15:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 0.00 |
May | 6346.48 | 31-MAY-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 0.00 |
June | 11611.42 | 25-JUN-17:11 | 0.00 | 251.99 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 186.62 | 0.00 |
July | 9193.74 | 02-JUL-18:42 | 0.00 | 215.99 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 0.00 |
August | 6995.31 | 04-AUG-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 0.00 |
September | 6289.70 | 11-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 0.00 |
October | 1829.80 | 20-OCT-15:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
November | 1549.03 | 03-NOV-15:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 |
December | 993.33 | 02-DEC-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 977.26 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11611.42 | 1306.65 | 711.15 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 186.62 | 199.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1175.62 | 12-JAN-10:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.24 |
February | 1641.02 | 24-FEB-10:10 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.04 |
March | 3228.50 | 28-MAR-09:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.88 |
April | 8229.16 | 18-APR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
May | 15217.10 | 29-MAY-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 |
June | 15337.37 | 25-JUN-08:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 |
July | 15377.72 | 02-JUL-09:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
August | 9096.98 | 02-AUG-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 10505.84 | 03-SEP-10:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.44 |
October | 3396.21 | 20-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
November | 1620.28 | 04-NOV-09:40 | 261.23 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 |
December | 1164.98 | 05-DEC-09:45 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1164.98 | 169.56 | 91.16 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15377.72 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 297.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5607.37 | 12-JAN-12:30 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 |
February | 8952.50 | 24-FEB-13:35 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.76 |
March | 9279.15 | 24-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.36 |
April | 19278.35 | 16-APR-13:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 |
May | 14892.14 | 29-MAY-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 |
June | 15948.98 | 25-JUN-15:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 197.70 | 0.00 |
July | 17902.08 | 30-JUL-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
August | 17871.49 | 13-AUG-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.43 |
September | 18229.59 | 17-SEP-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 |
October | 17734.82 | 01-OCT-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.11 |
November | 10920.89 | 03-NOV-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.77 |
December | 6800.86 | 01-DEC-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5607.37 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19278.35 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 197.70 | 249.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1605.46 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.23 |
February | 3183.99 | 24-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.90 |
March | 3676.64 | 21-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 |
April | 16688.00 | 16-APR-15:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 |
May | 14821.89 | 14-MAY-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 |
June | 17121.33 | 25-JUN-17:11 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 0.00 |
July | 17153.92 | 02-JUL-16:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 0.00 |
August | 16289.75 | 13-AUG-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 |
September | 16048.59 | 04-SEP-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.21 |
October | 5920.66 | 20-OCT-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
November | 3841.06 | 03-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 |
December | 1594.74 | 01-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1594.74 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17153.92 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 164.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 974.00 | 14-JAN-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.11 |
February | 1047.61 | 24-FEB-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.63 |
March | 1326.06 | 28-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
April | 3354.34 | 18-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
May | 4205.64 | 31-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
June | 5738.70 | 26-JUN-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 |
July | 7558.39 | 05-JUL-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
August | 5824.41 | 04-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
September | 5625.95 | 11-SEP-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
October | 1847.55 | 01-OCT-14:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.48 |
November | 1512.44 | 03-NOV-15:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
December | 987.32 | 02-DEC-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 974.00 | 267.84 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7558.39 | 1306.65 | 711.15 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 106.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 959.32 | 13-JAN-11:00 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 |
February | 1207.62 | 24-FEB-10:10 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
March | 1568.86 | 28-MAR-09:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.05 |
April | 5639.66 | 18-APR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
May | 6561.16 | 31-MAY-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
June | 11667.13 | 25-JUN-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 |
July | 13123.95 | 02-JUL-09:11 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 |
August | 8370.76 | 20-AUG-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 |
September | 10876.45 | 17-SEP-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 |
October | 2858.61 | 20-OCT-09:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 |
November | 1399.88 | 04-NOV-09:00 | 508.69 | 273.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 |
December | 1031.33 | 05-DEC-09:30 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 959.32 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13123.95 | 1654.44 | 820.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 161.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1492.26 | 13-JAN-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2122.17 |
February | 2330.21 | 24-FEB-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.80 |
March | 4564.15 | 24-MAR-14:00 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.57 |
April | 9951.64 | 18-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2907.97 | 0.00 |
May | 10379.91 | 31-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.04 | 0.00 |
June | 12025.11 | 26-JUN-11:10 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4702.43 | 0.00 |
July | 14810.82 | 30-JUL-13:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 |
August | 13075.39 | 06-AUG-14:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.38 |
September | 15641.20 | 17-SEP-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 |
October | 14191.63 | 01-OCT-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.65 |
November | 10244.84 | 05-NOV-15:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 |
December | 1658.04 | 02-DEC-12:40 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1492.26 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15641.20 | 1306.65 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4702.43 | 2122.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1223.87 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 |
February | 1837.88 | 24-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 |
March | 1857.77 | 21-MAR-17:00 | 254.33 | 227.89 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 |
April | 9017.87 | 15-APR-17:04 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 0.00 |
May | 8593.07 | 14-MAY-17:01 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 |
June | 13152.93 | 25-JUN-17:11 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 | 0.00 |
July | 14226.86 | 02-JUL-18:31 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 |
August | 11410.68 | 06-AUG-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.66 |
September | 13529.73 | 04-SEP-17:32 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 |
October | 5040.48 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.19 |
November | 3172.04 | 03-NOV-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 |
December | 1284.22 | 01-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1223.87 | 0.00 | 113.94 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14226.86 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 | 89.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1056.11 | 13-JAN-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.95 |
February | 1186.07 | 24-FEB-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 |
March | 1548.98 | 28-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 |
April | 5465.01 | 18-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
May | 5811.75 | 31-MAY-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.73 | 0.00 |
June | 10518.15 | 25-JUN-18:21 | 0.00 | 287.98 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 0.00 |
July | 10421.76 | 02-JUL-18:31 | 0.00 | 287.98 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 0.00 |
August | 7267.16 | 04-AUG-07:33 | 3816.70 | 1943.94 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
September | 6105.75 | 11-SEP-13:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 | 0.00 |
October | 2086.18 | 02-OCT-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 |
November | 1731.04 | 03-NOV-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 |
December | 975.44 | 02-DEC-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 975.44 | 0.00 | 287.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10518.15 | 3816.70 | 1943.94 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 92.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1269.79 | 12-JAN-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.41 |
February | 1904.81 | 24-FEB-09:35 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 |
March | 4006.75 | 28-MAR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.48 |
April | 8316.68 | 18-APR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
May | 14690.60 | 28-MAY-08:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.55 |
June | 16660.45 | 25-JUN-09:01 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 |
July | 16714.93 | 02-JUL-08:31 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 |
August | 15373.82 | 27-AUG-09:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
September | 14705.59 | 17-SEP-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.73 |
October | 4217.38 | 20-OCT-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 |
November | 2008.50 | 04-NOV-09:30 | 0.00 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 |
December | 1312.72 | 05-DEC-09:45 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1269.79 | 0.00 | 113.95 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 | |
Maximum of Months | 16714.93 | 1610.86 | 820.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6340.00 | 12-JAN-12:30 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.93 |
February | 9183.92 | 24-FEB-13:35 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 |
March | 9461.26 | 24-MAR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 |
April | 16434.21 | 16-APR-11:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
May | 10025.31 | 30-MAY-13:20 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 0.00 |
June | 16618.06 | 25-JUN-13:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 113.63 | 0.00 |
July | 17481.03 | 30-JUL-13:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
August | 16492.22 | 13-AUG-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.57 |
September | 18304.73 | 17-SEP-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.76 |
October | 17074.32 | 01-OCT-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.54 |
November | 11231.19 | 03-NOV-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.12 |
December | 7364.40 | 01-DEC-13:13 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6340.00 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18304.73 | 5088.93 | 2591.92 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 113.63 | 235.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1568.08 | 12-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.68 |
February | 3256.36 | 24-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
March | 4007.79 | 21-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.72 |
April | 14374.17 | 15-APR-17:04 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 72.56 | 0.00 |
May | 14854.21 | 07-MAY-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.21 |
June | 17011.38 | 25-JUN-17:41 | 0.00 | 205.09 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 | 0.00 |
July | 16540.17 | 02-JUL-18:31 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
August | 15137.36 | 13-AUG-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 |
September | 15115.58 | 17-SEP-14:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
October | 5928.33 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 |
November | 4009.46 | 03-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 |
December | 1572.67 | 01-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1568.08 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17011.38 | 805.38 | 410.20 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 72.56 | 136.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.108198E+12 | 91286.46 | 19-JAN-16:00 | 0.253418E+12 | 345152.68 | 30-JAN-07:40 |
February | 0.957867E+11 | 83112.89 | 14-FEB-16:00 | 0.167749E+12 | 356036.47 | 02-FEB-07:19 |
March | 0.108181E+12 | 83463.21 | 23-MAR-15:00 | 0.972524E+11 | 272047.71 | 06-MAR-07:19 |
April | 0.103589E+12 | 144793.85 | 18-APR-15:09 | 0.358132E+11 | 228512.34 | 03-APR-06:10 |
May | 0.116939E+12 | 146553.54 | 31-MAY-15:09 | 0.191353E+10 | 88832.79 | 02-MAY-06:10 |
June | 0.140989E+12 | 177797.53 | 26-JUN-07:49 | 0.413664E+09 | 29110.93 | 05-JUN-06:10 |
July | 0.150732E+12 | 174659.08 | 05-JUL-10:50 | 10380364.49 | 3487.26 | 24-JUL-06:10 |
August | 0.155636E+12 | 186900.54 | 04-AUG-07:19 | 57748175.18 | 10429.63 | 07-AUG-06:10 |
September | 0.119949E+12 | 153630.98 | 07-SEP-15:00 | 0.319647E+10 | 112235.94 | 29-SEP-06:10 |
October | 0.104077E+12 | 103648.91 | 20-OCT-15:09 | 0.173833E+11 | 135912.11 | 16-OCT-06:10 |
November | 0.102910E+12 | 90596.78 | 27-NOV-16:00 | 0.958903E+11 | 289914.65 | 28-NOV-07:19 |
December | 0.105488E+12 | 91066.23 | 11-DEC-16:30 | 0.194243E+12 | 318774.73 | 11-DEC-07:19 |
Annual Sum or Average | 0.141248E+13 | 0.867341E+12 | ||||
Minimum of Months | 0.957867E+11 | 83112.89 | 10380364.49 | 3487.26 | ||
Maximum of Months | 0.155636E+12 | 186900.54 | 0.253418E+12 | 356036.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.260829E+11 | 0.602207E+10 | 0.605851E+11 | 0.225894E+10 | 0.650613E+10 | 0.122481E+10 | 0.00 | 274031.77 | 0.00 | 0.00 | 0.00 | 0.551823E+10 | 0.00 |
February | 0.231281E+11 | 0.477907E+10 | 0.548702E+11 | 0.204969E+10 | 0.507109E+10 | 0.785474E+09 | 0.00 | 155712.84 | 0.00 | 0.00 | 0.00 | 0.510292E+10 | 0.00 |
March | 0.269531E+11 | 0.441157E+10 | 0.627783E+11 | 0.235654E+10 | 0.510648E+10 | 0.470805E+09 | 0.00 | 0.144772E+09 | 0.00 | 0.00 | 0.00 | 0.595980E+10 | 0.00 |
April | 0.238310E+11 | 0.348415E+10 | 0.586172E+11 | 0.219327E+10 | 0.592849E+10 | 0.175956E+09 | 0.00 | 0.417868E+10 | 0.00 | 0.00 | 0.00 | 0.518038E+10 | 0.00 |
May | 0.254935E+11 | 0.302042E+10 | 0.616817E+11 | 0.230710E+10 | 0.831920E+10 | 25768894.10 | 0.00 | 0.108544E+11 | 0.00 | 0.00 | 0.00 | 0.523729E+10 | 0.00 |
June | 0.253496E+11 | 0.270375E+10 | 0.604966E+11 | 0.226932E+10 | 0.141083E+11 | 15795697.79 | 0.00 | 0.311789E+11 | 0.00 | 0.00 | 0.00 | 0.486630E+10 | 0.00 |
July | 0.236832E+11 | 0.287876E+10 | 0.597911E+11 | 0.223007E+10 | 0.156025E+11 | 12316665.48 | 0.00 | 0.421720E+11 | 0.00 | 0.00 | 0.00 | 0.436213E+10 | 0.00 |
August | 0.265210E+11 | 0.333052E+10 | 0.627783E+11 | 0.235609E+10 | 0.158197E+11 | 13025346.60 | 0.00 | 0.401341E+11 | 0.00 | 0.00 | 0.00 | 0.468283E+10 | 0.00 |
September | 0.239233E+11 | 0.388110E+10 | 0.585950E+11 | 0.219211E+10 | 0.101681E+11 | 28878958.28 | 0.00 | 0.168750E+11 | 0.00 | 0.00 | 0.00 | 0.428545E+10 | 0.00 |
October | 0.251910E+11 | 0.491326E+10 | 0.605962E+11 | 0.225947E+10 | 0.527832E+10 | 93431500.13 | 0.00 | 0.110986E+10 | 0.00 | 0.00 | 0.00 | 0.463563E+10 | 0.00 |
November | 0.256825E+11 | 0.558954E+10 | 0.591197E+11 | 0.220157E+10 | 0.493788E+10 | 0.475585E+09 | 0.00 | 48522162.51 | 0.00 | 0.00 | 0.00 | 0.485505E+10 | 0.00 |
December | 0.256736E+11 | 0.625066E+10 | 0.597800E+11 | 0.223027E+10 | 0.547987E+10 | 0.948192E+09 | 0.00 | 220872.38 | 0.00 | 0.00 | 0.00 | 0.512491E+10 | 0.00 |
Annual Sum or Average | 0.301513E+12 | 0.512649E+11 | 0.719689E+12 | 0.269044E+11 | 0.102326E+12 | 0.427004E+10 | 0.00 | 0.146697E+12 | 0.00 | 0.00 | 0.00 | 0.598109E+11 | 0.00 |
Minimum of Months | 0.231281E+11 | 0.270375E+10 | 0.548702E+11 | 0.204969E+10 | 0.493788E+10 | 12316665.48 | 0.00 | 155712.84 | 0.00 | 0.00 | 0.00 | 0.428545E+10 | 0.00 |
Maximum of Months | 0.269531E+11 | 0.625066E+10 | 0.627783E+11 | 0.235654E+10 | 0.158197E+11 | 0.122481E+10 | 0.00 | 0.421720E+11 | 0.00 | 0.00 | 0.00 | 0.595980E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.253418E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.167749E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.972524E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.358132E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.191353E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.413664E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 10380364.49 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 57748175.18 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.319647E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.173833E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.958903E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194243E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.867341E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 10380364.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253418E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-13:20 | 8747.49 | 02-JAN-06:19 | 1156.50 | 31-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 30940.97 | 14-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-12:20 | 8637.32 | 06-FEB-07:10 | 1154.60 | 02-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 28700.47 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:20 | 7484.14 | 06-MAR-07:10 | 970.93 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 28290.68 | 10-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 04-APR-16:10 | 23526.96 | 18-APR-14:00 | 940.15 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 25990.55 | 09-MAY-15:30 | 3328.83 | 01-MAY-19:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 02-MAY-11:09 | 24760.46 | 30-MAY-15:30 | 413.02 | 02-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 26798.99 | 13-JUN-07:10 | 3328.83 | 01-JUN-19:40 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-16:10 | 31991.39 | 26-JUN-15:39 | 164.87 | 02-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 26798.99 | 20-JUL-07:10 | 3328.83 | 01-JUL-19:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 06-JUL-07:10 | 32074.49 | 03-JUL-15:09 | 26.39 | 24-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 26300.01 | 31-AUG-07:10 | 5686.19 | 08-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 33897.33 | 04-AUG-07:19 | 65.96 | 07-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 28290.68 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-07:10 | 25681.60 | 07-SEP-15:00 | 495.08 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 10483.62 | 20-OCT-15:30 | 674.18 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 8086.50 | 27-NOV-07:10 | 998.16 | 28-NOV-07:40 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-08:20 | 8306.83 | 11-DEC-07:10 | 1077.16 | 11-DEC-08:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 25990.55 | 3328.83 | 41699.26 | 1410.29 | 7484.14 | 26.39 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 33897.33 | 1156.50 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 75.96 | 02-JAN-06:19 | 0.00 | 0.00 | 0.00 | 7495.34 | 31-JAN-12:50 | 0.00 |
February | 58.24 | 06-FEB-06:30 | 0.00 | 0.00 | 0.00 | 7618.75 | 17-FEB-12:00 | 0.00 |
March | 6353.55 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7573.30 | 01-MAR-12:50 | 0.00 |
April | 48248.21 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 7211.40 | 03-APR-11:39 | 0.00 |
May | 49493.44 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6986.86 | 01-MAY-11:00 | 0.00 |
June | 76616.73 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 6574.34 | 02-JUN-11:30 | 0.00 |
July | 72766.43 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 6191.21 | 03-JUL-11:39 | 0.00 |
August | 80662.91 | 04-AUG-07:19 | 0.00 | 0.00 | 0.00 | 5807.06 | 01-AUG-11:39 | 0.00 |
September | 59944.69 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 5875.52 | 29-SEP-11:20 | 0.00 |
October | 20967.15 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6263.95 | 31-OCT-11:30 | 0.00 |
November | 3949.09 | 03-NOV-13:39 | 0.00 | 0.00 | 0.00 | 6719.53 | 30-NOV-12:39 | 0.00 |
December | 59.31 | 04-DEC-01:30 | 0.00 | 0.00 | 0.00 | 7176.76 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 58.24 | 0.00 | 0.00 | 0.00 | 5807.06 | 0.00 | ||
Maximum of Months | 80662.91 | 0.00 | 0.00 | 0.00 | 7618.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 91286.46 | 19-JAN-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3201.40 | 896.11 | 0.00 | 0.00 | 0.00 |
February | 83112.89 | 14-FEB-16:00 | 30940.97 | 41670.51 | 0.00 | 1410.29 | 2955.02 | 334.20 | 0.00 | 0.00 | 0.00 |
March | 83463.21 | 23-MAR-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 4654.72 | 6.85 | 0.00 | 4581.37 | 0.00 |
April | 144793.85 | 18-APR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 23313.49 | 6.92 | 0.00 | 47328.91 | 0.00 |
May | 146553.54 | 31-MAY-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 24304.05 | 6.92 | 0.00 | 48738.09 | 0.00 |
June | 177797.53 | 26-JUN-07:49 | 25681.07 | 41699.26 | 0.00 | 1410.29 | 28541.60 | 6.85 | 0.00 | 76616.73 | 0.00 |
July | 174659.08 | 05-JUL-10:50 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 28138.02 | 6.85 | 0.00 | 72766.43 | 0.00 |
August | 186900.54 | 04-AUG-07:19 | 25681.07 | 41699.26 | 0.00 | 1410.29 | 33897.33 | 6.85 | 0.00 | 80662.91 | 0.00 |
September | 153630.98 | 07-SEP-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 25681.60 | 6.87 | 0.00 | 54593.65 | 0.00 |
October | 103648.91 | 20-OCT-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 10051.51 | 6.85 | 0.00 | 20317.80 | 0.00 |
November | 90596.78 | 27-NOV-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3091.80 | 745.62 | 0.00 | 0.00 | 0.00 |
December | 91066.23 | 11-DEC-16:30 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3343.53 | 929.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 83112.89 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 2955.02 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 186900.54 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 33897.33 | 929.24 | 0.00 | 80662.91 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 345152.68 | 30-JAN-07:40 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 356036.47 | 02-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 272047.71 | 06-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 228512.34 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 88832.79 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 29110.93 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3487.26 | 24-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 10429.63 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 112235.94 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 135912.11 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 289914.65 | 28-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 318774.73 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 3487.26 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 356036.47 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.45 | 2.50 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.02 | 0.67 | 25.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.45 | 2.50 | 19.45 | 0.67 | 20.10 | 0.67 | 20.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.45 | 2.50 | 19.45 | 0.67 | 25.02 | 0.67 | 25.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 19.25 | 4.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 1.50 | 19.79 | 1.50 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.33 | 24.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.81 | 0.83 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
December | 2.17 | 19.56 | 2.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Annual Sum or Average | 9.67 | 19.45 | 9.00 | 19.54 | 0.33 | 19.63 | 0.33 | 19.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.81 | 4.67 | 19.81 | 0.33 | 24.69 | 0.33 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 18.91 | 10.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
February | 4.83 | 19.01 | 4.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 1.17 | 18.26 | 0.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
April | 0.33 | 18.04 | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.17 | 18.83 | 2.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
December | 5.50 | 18.88 | 4.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 27.67 | 18.87 | 22.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.67 | 19.01 | 10.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.67 | 16.85 | 61.67 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
February | 60.83 | 17.30 | 38.17 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
March | 11.50 | 16.65 | 4.50 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
April | 2.50 | 16.84 | 0.83 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.48 | 2.17 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.33 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22.67 | 16.53 | 11.50 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
December | 52.33 | 16.55 | 27.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
Annual Sum or Average | 258.50 | 16.86 | 143.83 | 17.39 | 4.33 | 17.49 | 2.50 | 17.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.67 | 17.30 | 61.67 | 17.83 | 3.67 | 27.48 | 2.17 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.83 | 15.69 | 23.83 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 34.17 | 16.30 | 14.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 8.33 | 15.86 | 1.17 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
April | 2.00 | 15.76 | 0.17 | 16.04 | 0.17 | 16.84 | 0.17 | 17.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 3.50 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.14 | 5.50 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.09 | 7.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.89 | 2.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.89 | 2.50 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.50 | 15.30 | 4.83 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
December | 34.50 | 15.47 | 10.83 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
Annual Sum or Average | 162.33 | 15.74 | 54.83 | 16.19 | 21.67 | 17.26 | 21.17 | 18.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.83 | 16.30 | 23.83 | 16.93 | 7.33 | 28.14 | 7.33 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.50 | 16.14 | 23.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
February | 31.83 | 16.78 | 14.50 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
March | 6.50 | 16.40 | 1.67 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
April | 1.67 | 15.74 | 0.17 | 16.04 | 1.67 | 21.78 | 1.67 | 23.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 4.00 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.84 | 5.33 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.70 | 4.67 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.06 | 5.33 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.65 | 1.17 | 27.65 |
November | 15.17 | 15.75 | 5.67 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
December | 29.50 | 15.87 | 9.00 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
Annual Sum or Average | 147.17 | 16.19 | 54.33 | 16.75 | 24.83 | 17.96 | 23.33 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 0.00 | 16.15 |
Maximum of Months | 62.50 | 16.78 | 23.33 | 17.45 | 6.00 | 28.06 | 5.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.00 | 15.68 | 25.50 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 37.00 | 16.62 | 18.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
March | 8.17 | 15.84 | 1.83 | 16.05 | 0.00 | 16.05 | 0.00 | 16.05 |
April | 1.83 | 15.43 | 0.17 | 15.76 | 2.00 | 22.07 | 1.33 | 23.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.17 | 1.67 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.59 | 3.17 | 28.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.44 | 4.67 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.10 | 2.50 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.14 | 2.67 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.33 | 15.06 | 4.33 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
December | 35.00 | 15.39 | 11.50 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
Annual Sum or Average | 166.33 | 15.78 | 61.33 | 16.21 | 28.00 | 17.54 | 16.00 | 18.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 69.00 | 16.62 | 25.50 | 17.28 | 9.83 | 28.59 | 4.67 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.50 | 18.46 | 54.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 63.83 | 18.63 | 51.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
March | 4.33 | 18.83 | 3.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
April | 0.33 | 18.23 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.65 | 0.33 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.33 | 19.24 | 3.67 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 17.67 | 18.31 | 12.83 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
Annual Sum or Average | 161.00 | 18.54 | 126.17 | 18.91 | 0.33 | 18.92 | 0.33 | 18.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.50 | 19.24 | 54.83 | 19.43 | 0.33 | 24.65 | 0.33 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.00 | 17.26 | 13.33 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
February | 18.33 | 17.60 | 10.33 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
March | 0.50 | 17.60 | 0.17 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
April | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.79 | 3.33 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.79 | 5.83 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.84 | 1.83 | 26.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.67 | 2.83 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.10 | 0.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
December | 7.67 | 16.73 | 2.83 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
Annual Sum or Average | 54.83 | 17.32 | 27.17 | 17.96 | 14.17 | 19.38 | 14.17 | 20.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.00 | 18.10 | 13.33 | 18.57 | 5.83 | 27.79 | 5.83 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.00 | 16.28 | 151.17 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
February | 102.00 | 16.50 | 98.17 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
March | 68.33 | 17.49 | 68.17 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
April | 34.00 | 18.28 | 33.83 | 18.28 | 0.83 | 18.40 | 0.83 | 18.51 |
May | 5.00 | 19.43 | 5.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.47 | 1.67 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 3.00 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.14 | 3.17 | 27.14 |
September | 4.83 | 19.56 | 4.83 | 19.56 | 12.50 | 23.29 | 12.17 | 24.30 |
October | 14.17 | 19.00 | 14.17 | 19.00 | 1.50 | 19.42 | 1.50 | 19.81 |
November | 56.67 | 17.54 | 56.33 | 17.55 | 0.33 | 17.57 | 0.33 | 17.60 |
December | 109.50 | 16.91 | 108.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
Annual Sum or Average | 554.50 | 16.97 | 539.83 | 16.99 | 23.00 | 17.19 | 22.67 | 17.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 0.00 | 16.29 |
Maximum of Months | 160.00 | 19.56 | 151.17 | 19.56 | 12.50 | 27.59 | 12.17 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.67 | 17.49 | 14.83 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
February | 21.00 | 18.16 | 14.33 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
March | 0.50 | 17.67 | 0.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
April | 0.17 | 17.08 | 0.00 | 17.08 | 1.17 | 26.48 | 0.67 | 26.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 0.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.05 | 2.50 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.98 | 3.83 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 1.50 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.78 | 2.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 17.88 | 0.33 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
December | 8.00 | 16.61 | 3.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
Annual Sum or Average | 58.33 | 17.62 | 32.83 | 18.23 | 21.50 | 20.07 | 11.83 | 20.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.67 | 18.16 | 14.83 | 18.70 | 8.50 | 28.05 | 3.83 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 17.66 | 34.83 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
February | 32.67 | 17.76 | 21.17 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
March | 3.33 | 18.02 | 2.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
April | 0.33 | 18.19 | 0.17 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.17 | 24.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.67 | 16.85 | 5.17 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
December | 22.67 | 17.09 | 13.83 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Annual Sum or Average | 124.00 | 17.52 | 77.17 | 18.03 | 0.83 | 18.06 | 0.50 | 18.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.33 | 18.19 | 34.83 | 18.58 | 0.67 | 27.34 | 0.33 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.00 | 16.28 | 9.83 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 17.83 | 16.83 | 7.17 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
March | 1.17 | 16.14 | 0.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
April | 0.17 | 16.99 | 0.00 | 16.99 | 0.50 | 24.78 | 0.50 | 25.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 4.00 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.97 | 6.00 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.17 | 6.50 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.72 | 2.50 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.95 | 3.17 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.50 | 15.43 | 1.33 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
December | 13.17 | 15.97 | 4.17 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Annual Sum or Average | 66.83 | 16.28 | 22.67 | 16.83 | 22.67 | 19.08 | 22.67 | 20.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.00 | 16.99 | 9.83 | 17.55 | 6.50 | 28.17 | 6.50 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 17.10 | 11.33 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
February | 14.17 | 17.83 | 8.50 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
March | 0.67 | 17.12 | 0.17 | 17.45 | 0.17 | 19.09 | 0.17 | 20.27 |
April | 0.17 | 17.08 | 0.00 | 17.08 | 1.50 | 26.89 | 1.50 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.75 | 4.00 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.79 | 4.83 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.63 | 4.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.01 | 5.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
November | 6.33 | 16.33 | 2.00 | 16.86 | 0.50 | 17.46 | 0.50 | 17.99 |
December | 10.83 | 16.52 | 4.33 | 17.06 | 0.17 | 17.17 | 0.17 | 17.28 |
Annual Sum or Average | 57.17 | 17.08 | 26.33 | 17.70 | 25.00 | 20.02 | 24.83 | 21.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 0.00 | 17.28 |
Maximum of Months | 25.00 | 17.83 | 11.33 | 18.44 | 5.67 | 28.01 | 5.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.83 | 16.33 | 11.50 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
February | 19.50 | 17.21 | 9.50 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
March | 0.83 | 16.65 | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
April | 0.17 | 16.96 | 0.00 | 16.96 | 2.67 | 27.36 | 1.67 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.08 | 1.67 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.47 | 3.17 | 28.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.32 | 4.67 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.99 | 2.33 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.97 | 3.17 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7.00 | 15.39 | 1.83 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
December | 14.50 | 15.78 | 5.00 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Annual Sum or Average | 71.83 | 16.37 | 28.00 | 16.89 | 28.50 | 19.40 | 16.67 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.83 | 17.21 | 11.50 | 17.92 | 9.50 | 28.47 | 4.67 | 28.50 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.80 | 153.00 | 21.54 | 153.00 | 21.38 |
February | 454.00 | 22.57 | 75.17 | 22.33 | 75.17 | 22.15 |
March | 460.83 | 23.40 | 2.83 | 23.39 | 2.00 | 23.38 |
April | 289.50 | 23.78 | 60.33 | 23.93 | 0.00 | 23.93 |
May | 28.33 | 23.98 | 320.00 | 24.54 | 0.00 | 24.54 |
June | 0.00 | 0.00 | 460.00 | 24.43 | 0.00 | 24.43 |
July | 0.00 | 0.00 | 493.33 | 24.51 | 0.00 | 24.51 |
August | 1.33 | 24.61 | 507.67 | 24.44 | 1.33 | 24.44 |
September | 26.67 | 24.00 | 282.00 | 24.63 | 0.00 | 24.63 |
October | 198.83 | 24.00 | 34.17 | 24.19 | 0.00 | 24.19 |
November | 362.33 | 23.30 | 45.83 | 23.26 | 23.67 | 23.15 |
December | 497.00 | 22.59 | 57.33 | 22.43 | 57.33 | 22.31 |
Annual Sum or Average | 2820.83 | 22.92 | 2491.67 | 23.46 | 312.50 | 23.32 |
Minimum of Months | 0.00 | 0.00 | 2.83 | 21.54 | 0.00 | 21.38 |
Maximum of Months | 502.00 | 24.61 | 507.67 | 24.63 | 153.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.65 | 425.33 | 20.57 | 425.33 | 20.53 |
February | 454.00 | 21.15 | 240.83 | 20.96 | 240.83 | 20.86 |
March | 511.67 | 22.09 | 87.50 | 21.90 | 87.50 | 21.75 |
April | 395.83 | 22.65 | 62.17 | 22.68 | 27.33 | 22.58 |
May | 151.00 | 23.51 | 197.00 | 23.91 | 0.00 | 23.91 |
June | 31.17 | 23.36 | 382.17 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 472.33 | 24.30 | 0.00 | 24.30 |
August | 1.00 | 24.25 | 484.00 | 24.25 | 1.00 | 24.25 |
September | 136.50 | 23.41 | 192.17 | 23.99 | 0.00 | 23.99 |
October | 463.67 | 23.09 | 0.00 | 23.09 | 0.00 | 23.09 |
November | 468.67 | 21.92 | 135.17 | 21.63 | 135.17 | 21.45 |
December | 497.00 | 20.99 | 303.67 | 20.81 | 303.67 | 20.72 |
Annual Sum or Average | 3612.50 | 21.91 | 2982.33 | 22.29 | 1220.83 | 22.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.57 | 0.00 | 20.53 |
Maximum of Months | 511.67 | 24.25 | 484.00 | 24.30 | 425.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.19 | 471.67 | 20.15 | 471.67 | 20.13 |
February | 454.00 | 20.57 | 343.00 | 20.43 | 343.00 | 20.38 |
March | 514.00 | 21.46 | 219.50 | 21.20 | 219.50 | 21.06 |
April | 408.67 | 22.01 | 111.50 | 21.91 | 78.50 | 21.71 |
May | 219.83 | 23.19 | 161.67 | 23.59 | 0.00 | 23.59 |
June | 68.83 | 23.10 | 348.67 | 24.05 | 0.00 | 24.05 |
July | 11.00 | 23.37 | 446.50 | 24.24 | 0.00 | 24.24 |
August | 19.33 | 23.36 | 427.50 | 24.17 | 0.67 | 24.17 |
September | 212.50 | 22.90 | 153.83 | 23.46 | 2.50 | 23.44 |
October | 492.50 | 22.16 | 51.67 | 22.01 | 51.67 | 21.89 |
November | 488.50 | 21.13 | 248.83 | 20.82 | 248.83 | 20.67 |
December | 497.00 | 20.37 | 450.00 | 20.31 | 450.00 | 20.29 |
Annual Sum or Average | 3888.17 | 21.38 | 3434.33 | 21.71 | 1866.33 | 21.41 |
Minimum of Months | 11.00 | 20.19 | 51.67 | 20.15 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 23.37 | 471.67 | 24.24 | 471.67 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.59 | 498.17 | 19.58 | 498.17 | 19.58 |
February | 454.00 | 19.82 | 436.50 | 19.79 | 436.50 | 19.78 |
March | 514.00 | 20.69 | 352.33 | 20.52 | 352.33 | 20.45 |
April | 422.67 | 21.21 | 204.33 | 21.09 | 169.50 | 20.88 |
May | 247.67 | 22.68 | 173.50 | 23.24 | 7.33 | 23.19 |
June | 107.00 | 23.34 | 355.33 | 24.09 | 22.50 | 24.17 |
July | 43.83 | 24.24 | 447.17 | 24.33 | 21.83 | 24.37 |
August | 68.83 | 23.33 | 398.00 | 24.05 | 18.67 | 24.06 |
September | 266.83 | 22.26 | 175.00 | 22.88 | 23.17 | 22.76 |
October | 497.00 | 21.20 | 181.67 | 20.94 | 181.67 | 20.78 |
November | 489.00 | 20.27 | 341.67 | 20.04 | 341.67 | 19.94 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4109.83 | 20.78 | 4060.67 | 21.16 | 2570.33 | 20.88 |
Minimum of Months | 43.83 | 19.59 | 173.50 | 19.58 | 7.33 | 19.58 |
Maximum of Months | 514.00 | 24.24 | 498.17 | 24.33 | 498.17 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 487.83 | 19.68 | 487.83 | 19.68 |
February | 454.00 | 19.99 | 407.33 | 19.92 | 407.33 | 19.89 |
March | 506.33 | 20.89 | 290.33 | 20.65 | 290.33 | 20.54 |
April | 388.50 | 21.37 | 198.33 | 21.43 | 138.83 | 21.21 |
May | 218.83 | 22.90 | 228.00 | 23.66 | 19.33 | 23.75 |
June | 122.67 | 23.51 | 363.00 | 24.17 | 31.67 | 24.32 |
July | 66.00 | 25.38 | 452.00 | 24.56 | 48.17 | 24.70 |
August | 77.67 | 23.76 | 413.67 | 24.15 | 28.83 | 24.22 |
September | 234.33 | 22.34 | 213.17 | 23.23 | 27.83 | 23.21 |
October | 491.67 | 21.42 | 125.17 | 21.19 | 124.50 | 21.04 |
November | 489.00 | 20.34 | 331.83 | 20.13 | 331.83 | 20.05 |
December | 497.00 | 19.84 | 494.33 | 19.84 | 494.33 | 19.84 |
Annual Sum or Average | 4048.00 | 20.96 | 4005.00 | 21.39 | 2430.83 | 21.13 |
Minimum of Months | 66.00 | 19.70 | 125.17 | 19.68 | 19.33 | 19.68 |
Maximum of Months | 506.33 | 25.38 | 494.33 | 24.56 | 494.33 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.00 | 20.08 | 417.00 | 19.87 | 417.00 | 19.79 |
February | 435.00 | 20.48 | 331.17 | 20.24 | 323.67 | 20.12 |
March | 454.50 | 21.08 | 275.50 | 20.89 | 258.33 | 20.74 |
April | 354.83 | 21.35 | 212.17 | 21.52 | 138.17 | 21.30 |
May | 224.33 | 22.61 | 207.33 | 23.40 | 13.67 | 23.39 |
June | 130.00 | 23.26 | 335.17 | 24.04 | 26.00 | 24.15 |
July | 73.17 | 24.50 | 429.83 | 24.41 | 37.33 | 24.52 |
August | 94.00 | 23.96 | 408.17 | 24.22 | 38.00 | 24.33 |
September | 229.67 | 22.67 | 234.33 | 23.49 | 36.83 | 23.54 |
October | 384.17 | 21.59 | 164.50 | 21.74 | 100.67 | 21.54 |
November | 460.17 | 20.72 | 285.33 | 20.47 | 271.33 | 20.30 |
December | 477.67 | 20.28 | 407.00 | 20.10 | 404.67 | 20.03 |
Annual Sum or Average | 3809.50 | 21.21 | 3707.50 | 21.63 | 2065.67 | 21.35 |
Minimum of Months | 73.17 | 20.08 | 164.50 | 19.87 | 13.67 | 19.79 |
Maximum of Months | 492.00 | 24.50 | 429.83 | 24.41 | 417.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 490.17 | 19.70 | 490.17 | 19.70 |
February | 450.33 | 20.06 | 401.17 | 19.97 | 401.17 | 19.94 |
March | 491.50 | 20.76 | 322.00 | 20.59 | 319.17 | 20.51 |
April | 381.50 | 21.18 | 218.50 | 21.31 | 153.67 | 21.11 |
May | 276.17 | 22.46 | 180.83 | 23.13 | 18.83 | 23.16 |
June | 138.67 | 22.97 | 344.33 | 23.95 | 23.17 | 24.06 |
July | 82.33 | 24.32 | 420.83 | 24.38 | 36.50 | 24.52 |
August | 106.50 | 23.39 | 399.83 | 24.06 | 31.50 | 24.13 |
September | 282.33 | 22.22 | 199.00 | 22.96 | 39.00 | 22.96 |
October | 456.33 | 21.10 | 176.67 | 20.95 | 162.00 | 20.80 |
November | 482.00 | 20.28 | 330.17 | 20.09 | 327.83 | 20.00 |
December | 497.00 | 19.85 | 476.17 | 19.82 | 476.17 | 19.81 |
Annual Sum or Average | 4146.67 | 20.90 | 3959.67 | 21.29 | 2479.17 | 21.04 |
Minimum of Months | 82.33 | 19.72 | 176.67 | 19.70 | 18.83 | 19.70 |
Maximum of Months | 502.00 | 24.32 | 490.17 | 24.38 | 490.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 502.00 | 19.71 | 502.00 | 19.71 |
February | 454.00 | 19.99 | 448.67 | 19.99 | 448.67 | 19.98 |
March | 514.00 | 20.68 | 379.33 | 20.58 | 379.33 | 20.54 |
April | 463.67 | 21.20 | 218.17 | 21.02 | 206.33 | 20.89 |
May | 373.67 | 22.69 | 85.83 | 22.91 | 7.50 | 22.88 |
June | 97.83 | 22.96 | 307.67 | 23.92 | 2.67 | 23.92 |
July | 12.67 | 24.01 | 451.50 | 24.27 | 6.17 | 24.27 |
August | 30.17 | 23.72 | 434.50 | 24.15 | 10.00 | 24.16 |
September | 221.33 | 22.83 | 168.67 | 23.43 | 2.50 | 23.41 |
October | 498.50 | 21.97 | 41.33 | 21.86 | 41.33 | 21.78 |
November | 489.00 | 20.90 | 284.83 | 20.64 | 284.83 | 20.52 |
December | 497.00 | 20.06 | 497.00 | 20.06 | 497.00 | 20.06 |
Annual Sum or Average | 4153.83 | 21.03 | 3819.50 | 21.34 | 2388.33 | 21.06 |
Minimum of Months | 12.67 | 19.71 | 41.33 | 19.71 | 2.50 | 19.71 |
Maximum of Months | 514.00 | 24.01 | 502.00 | 24.27 | 502.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 492.67 | 19.87 | 492.67 | 19.87 |
February | 454.00 | 20.23 | 417.33 | 20.19 | 417.33 | 20.17 |
March | 514.00 | 21.00 | 300.17 | 20.80 | 300.17 | 20.70 |
April | 414.67 | 21.49 | 177.00 | 21.45 | 136.00 | 21.26 |
May | 236.00 | 22.88 | 178.00 | 23.63 | 3.67 | 23.64 |
June | 98.83 | 23.51 | 378.00 | 24.21 | 18.50 | 24.30 |
July | 39.50 | 26.17 | 478.33 | 24.60 | 34.50 | 24.73 |
August | 23.83 | 25.09 | 478.33 | 24.33 | 17.17 | 24.38 |
September | 178.33 | 23.12 | 232.33 | 23.92 | 12.17 | 23.99 |
October | 474.67 | 22.38 | 20.00 | 22.34 | 16.67 | 22.28 |
November | 489.00 | 21.01 | 262.67 | 20.75 | 262.67 | 20.63 |
December | 497.00 | 20.17 | 490.17 | 20.16 | 490.17 | 20.16 |
Annual Sum or Average | 3921.83 | 21.23 | 3905.00 | 21.67 | 2201.67 | 21.39 |
Minimum of Months | 23.83 | 19.88 | 20.00 | 19.87 | 3.67 | 19.87 |
Maximum of Months | 514.00 | 26.17 | 492.67 | 24.60 | 492.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.76 | 478.67 | 18.69 | 478.67 | 18.67 |
February | 451.17 | 19.65 | 363.83 | 19.43 | 363.83 | 19.35 |
March | 493.33 | 20.57 | 288.33 | 20.29 | 284.67 | 20.14 |
April | 412.33 | 21.17 | 203.67 | 21.15 | 157.50 | 20.94 |
May | 332.17 | 22.33 | 115.67 | 22.85 | 8.50 | 22.80 |
June | 171.00 | 22.82 | 307.00 | 23.76 | 43.17 | 23.79 |
July | 98.50 | 23.97 | 450.83 | 24.30 | 76.17 | 24.31 |
August | 96.17 | 23.79 | 467.33 | 24.23 | 68.33 | 24.26 |
September | 193.67 | 22.87 | 249.50 | 23.86 | 26.17 | 23.97 |
October | 374.00 | 22.24 | 78.17 | 22.47 | 19.83 | 22.36 |
November | 453.33 | 20.71 | 248.83 | 20.48 | 226.67 | 20.25 |
December | 492.17 | 19.65 | 414.33 | 19.48 | 411.00 | 19.40 |
Annual Sum or Average | 4069.83 | 20.87 | 3666.17 | 21.25 | 2164.50 | 20.93 |
Minimum of Months | 96.17 | 18.76 | 78.17 | 18.69 | 8.50 | 18.67 |
Maximum of Months | 502.00 | 23.97 | 478.67 | 24.30 | 478.67 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.88 | 492.67 | 19.86 | 492.67 | 19.86 |
February | 454.00 | 20.29 | 409.67 | 20.22 | 409.67 | 20.20 |
March | 512.50 | 20.94 | 324.67 | 20.76 | 324.67 | 20.68 |
April | 409.33 | 21.48 | 168.00 | 21.45 | 130.50 | 21.27 |
May | 299.33 | 22.61 | 128.17 | 23.14 | 4.83 | 23.12 |
June | 104.00 | 23.16 | 357.83 | 24.07 | 14.17 | 24.15 |
July | 33.50 | 25.98 | 471.17 | 24.56 | 28.00 | 24.67 |
August | 25.17 | 24.85 | 478.50 | 24.34 | 16.33 | 24.38 |
September | 199.33 | 22.93 | 232.67 | 23.74 | 16.00 | 23.80 |
October | 452.00 | 22.11 | 39.33 | 22.12 | 22.33 | 22.05 |
November | 481.50 | 20.95 | 259.67 | 20.70 | 258.50 | 20.57 |
December | 497.00 | 20.17 | 475.50 | 20.14 | 475.50 | 20.13 |
Annual Sum or Average | 3969.67 | 21.18 | 3837.83 | 21.61 | 2193.17 | 21.33 |
Minimum of Months | 25.17 | 19.88 | 39.33 | 19.86 | 4.83 | 19.86 |
Maximum of Months | 512.50 | 25.98 | 492.67 | 24.56 | 492.67 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 492.67 | 19.73 | 492.67 | 19.73 |
February | 454.00 | 20.11 | 409.33 | 20.06 | 409.33 | 20.04 |
March | 514.00 | 21.00 | 300.83 | 20.78 | 300.83 | 20.69 |
April | 415.17 | 21.62 | 144.00 | 21.56 | 104.33 | 21.36 |
May | 206.33 | 23.07 | 182.67 | 23.58 | 1.00 | 23.57 |
June | 63.83 | 23.42 | 387.00 | 24.21 | 7.67 | 24.24 |
July | 12.00 | 24.72 | 475.33 | 24.37 | 9.67 | 24.38 |
August | 31.17 | 23.85 | 446.17 | 24.20 | 12.83 | 24.21 |
September | 222.50 | 22.73 | 179.83 | 23.40 | 5.00 | 23.37 |
October | 489.83 | 21.83 | 74.67 | 21.67 | 72.83 | 21.54 |
November | 489.00 | 20.78 | 291.67 | 20.49 | 291.67 | 20.36 |
December | 497.00 | 19.99 | 497.00 | 19.99 | 497.00 | 19.99 |
Annual Sum or Average | 3896.83 | 21.03 | 3881.17 | 21.47 | 2204.83 | 21.16 |
Minimum of Months | 12.00 | 19.74 | 74.67 | 19.73 | 1.00 | 19.73 |
Maximum of Months | 514.00 | 24.72 | 497.00 | 24.37 | 497.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.65 | 415.33 | 19.63 | 415.33 | 19.62 |
February | 385.00 | 20.14 | 336.00 | 20.05 | 336.00 | 20.02 |
March | 423.00 | 21.05 | 223.67 | 20.81 | 223.67 | 20.70 |
April | 321.00 | 21.55 | 139.17 | 21.74 | 83.33 | 21.53 |
May | 184.33 | 23.21 | 185.50 | 23.89 | 18.33 | 24.01 |
June | 89.33 | 23.91 | 314.83 | 24.36 | 27.00 | 24.51 |
July | 46.00 | 26.08 | 397.50 | 24.69 | 39.00 | 24.84 |
August | 48.17 | 24.29 | 367.00 | 24.30 | 22.00 | 24.38 |
September | 193.83 | 22.75 | 177.67 | 23.61 | 16.50 | 23.69 |
October | 406.33 | 21.79 | 51.17 | 21.68 | 47.67 | 21.56 |
November | 415.83 | 20.64 | 255.00 | 20.41 | 255.00 | 20.30 |
December | 422.00 | 19.91 | 415.33 | 19.90 | 415.33 | 19.89 |
Annual Sum or Average | 3361.83 | 21.12 | 3278.17 | 21.57 | 1899.17 | 21.30 |
Minimum of Months | 46.00 | 19.65 | 51.17 | 19.63 | 16.50 | 19.62 |
Maximum of Months | 427.00 | 26.08 | 415.33 | 24.69 | 415.33 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.50 | 20.38 | 391.50 | 20.13 | 391.50 | 20.04 |
February | 425.50 | 20.85 | 294.83 | 20.60 | 284.67 | 20.46 |
March | 445.17 | 21.46 | 226.67 | 21.26 | 204.50 | 21.08 |
April | 344.17 | 21.80 | 167.50 | 22.07 | 86.17 | 21.87 |
May | 179.50 | 23.01 | 224.00 | 23.76 | 6.33 | 23.80 |
June | 88.83 | 23.80 | 365.67 | 24.25 | 21.33 | 24.36 |
July | 44.67 | 25.46 | 464.17 | 24.51 | 32.00 | 24.62 |
August | 55.33 | 24.81 | 460.33 | 24.37 | 31.67 | 24.46 |
September | 191.33 | 23.26 | 247.67 | 23.98 | 26.33 | 24.10 |
October | 362.17 | 22.29 | 113.33 | 22.57 | 38.50 | 22.47 |
November | 444.50 | 21.19 | 238.83 | 21.00 | 213.00 | 20.77 |
December | 467.17 | 20.56 | 386.00 | 20.38 | 382.00 | 20.30 |
Annual Sum or Average | 3538.83 | 21.54 | 3580.50 | 22.03 | 1718.00 | 21.74 |
Minimum of Months | 44.67 | 20.38 | 113.33 | 20.13 | 6.33 | 20.04 |
Maximum of Months | 490.50 | 25.46 | 464.17 | 24.51 | 391.50 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 483.67 | 19.84 | 483.67 | 19.82 |
February | 450.00 | 20.34 | 376.17 | 20.22 | 376.17 | 20.18 |
March | 488.17 | 21.04 | 268.67 | 20.84 | 266.17 | 20.74 |
April | 369.83 | 21.55 | 168.83 | 21.74 | 100.67 | 21.58 |
May | 234.83 | 22.85 | 200.00 | 23.52 | 10.33 | 23.59 |
June | 102.83 | 23.42 | 371.17 | 24.16 | 20.00 | 24.26 |
July | 49.67 | 25.36 | 451.83 | 24.51 | 33.33 | 24.64 |
August | 60.83 | 24.09 | 441.50 | 24.25 | 25.67 | 24.32 |
September | 243.67 | 22.66 | 204.17 | 23.45 | 20.50 | 23.52 |
October | 445.83 | 21.64 | 81.50 | 21.61 | 61.33 | 21.49 |
November | 480.67 | 20.72 | 281.67 | 20.50 | 278.33 | 20.38 |
December | 497.00 | 20.10 | 467.33 | 20.05 | 467.33 | 20.03 |
Annual Sum or Average | 3925.33 | 21.14 | 3796.50 | 21.60 | 2143.50 | 21.33 |
Minimum of Months | 49.67 | 19.87 | 81.50 | 19.84 | 10.33 | 19.82 |
Maximum of Months | 502.00 | 25.36 | 483.67 | 24.51 | 483.67 | 24.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79710 | 13.96315 | -0.4541 | 10.67657 |
February | 454.00000 | 22.57040 | 17.45657 | -0.2349 | 7.54386 |
March | 514.00000 | 23.51993 | 21.86839 | 0.04400 | 5.89302 |
April | 485.00000 | 24.02484 | 28.20242 | 0.24094 | 6.85858 |
May | 508.00000 | 24.40162 | 40.62661 | -0.3974 | 8.99326 |
June | 496.00000 | 24.39946 | 47.71809 | -0.3020 | 7.43297 |
July | 497.00000 | 24.50207 | 51.87984 | -0.2282 | 6.70749 |
August | 514.00000 | 24.43250 | 50.90370 | -0.2548 | 6.92113 |
September | 485.00000 | 24.42967 | 37.30317 | -0.3821 | 8.87231 |
October | 502.00000 | 24.27549 | 26.87018 | 0.30540 | 7.14472 |
November | 489.00000 | 23.56008 | 23.71310 | 0.07430 | 6.79386 |
December | 497.00000 | 22.58987 | 15.90550 | -0.2417 | 7.14170 |
Annual Sum or Average | 5943.00000 | 23.71649 | 31.49759 | -0.1526 | 7.57997 |
Minimum of Months | 454.00000 | 21.79710 | 13.96315 | -0.4541 | 5.89302 |
Maximum of Months | 514.00000 | 24.50207 | 51.87984 | 0.30540 | 10.67657 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65362 | 14.77365 | -0.7275 | 17.60019 |
February | 454.00000 | 21.14972 | 18.73525 | -0.5618 | 12.89777 |
March | 514.00000 | 22.09748 | 23.96402 | -0.2770 | 8.15598 |
April | 485.00000 | 22.91702 | 30.70322 | -0.0069 | 6.88688 |
May | 508.00000 | 23.92854 | 42.35216 | -0.5619 | 12.34583 |
June | 496.00000 | 24.16470 | 48.83601 | -0.4015 | 8.87965 |
July | 497.00000 | 24.28622 | 52.81378 | -0.3210 | 7.47883 |
August | 514.00000 | 24.23908 | 51.90771 | -0.3478 | 7.81807 |
September | 485.00000 | 24.00395 | 38.88799 | -0.5509 | 12.64366 |
October | 502.00000 | 23.16417 | 29.82333 | 0.03969 | 5.75227 |
November | 489.00000 | 21.99992 | 25.95908 | -0.2913 | 9.56161 |
December | 497.00000 | 20.98941 | 17.07487 | -0.6141 | 14.13846 |
Annual Sum or Average | 5943.00000 | 22.81230 | 33.11619 | -0.3843 | 10.32423 |
Minimum of Months | 454.00000 | 20.65362 | 14.77365 | -0.7275 | 5.75227 |
Maximum of Months | 514.00000 | 24.28622 | 52.81378 | 0.03969 | 17.60019 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19167 | 15.07722 | -0.8724 | 23.24102 |
February | 454.00000 | 20.56753 | 19.37391 | -0.7314 | 18.21089 |
March | 514.00000 | 21.45595 | 24.55831 | -0.4492 | 11.11000 |
April | 485.00000 | 22.33701 | 31.52491 | -0.1512 | 8.53389 |
May | 508.00000 | 23.68034 | 42.92409 | -0.6460 | 15.14943 |
June | 496.00000 | 24.03156 | 49.30726 | -0.4418 | 10.07084 |
July | 497.00000 | 24.20802 | 53.18337 | -0.3420 | 7.82510 |
August | 514.00000 | 24.11653 | 52.34998 | -0.3882 | 8.50784 |
September | 485.00000 | 23.60197 | 39.79177 | -0.6941 | 17.59810 |
October | 502.00000 | 22.19125 | 31.24787 | -0.1977 | 7.23240 |
November | 489.00000 | 21.12919 | 26.99890 | -0.5219 | 14.01094 |
December | 497.00000 | 20.37282 | 17.63686 | -0.7981 | 20.32292 |
Annual Sum or Average | 5943.00000 | 22.33832 | 33.79309 | -0.5180 | 13.43681 |
Minimum of Months | 454.00000 | 20.19167 | 15.07722 | -0.8724 | 7.23240 |
Maximum of Months | 514.00000 | 24.20802 | 53.18337 | -0.1512 | 23.24102 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.59035 | 15.60128 | -1.1220 | 33.62687 |
February | 454.00000 | 19.81546 | 20.39361 | -0.9883 | 28.18823 |
March | 514.00000 | 20.69257 | 26.25195 | -0.6696 | 16.85336 |
April | 485.00000 | 21.59392 | 33.16876 | -0.3394 | 12.34835 |
May | 508.00000 | 23.40351 | 43.90700 | -0.7301 | 19.31608 |
June | 496.00000 | 23.99752 | 50.03531 | -0.4174 | 11.17401 |
July | 497.00000 | 24.26478 | 53.90861 | -0.2868 | 7.74315 |
August | 514.00000 | 24.02633 | 53.35910 | -0.3912 | 9.19840 |
September | 485.00000 | 23.13642 | 41.62601 | -0.8460 | 24.77481 |
October | 502.00000 | 21.22527 | 33.54202 | -0.4373 | 11.11373 |
November | 489.00000 | 20.26750 | 28.80662 | -0.7705 | 21.59705 |
December | 497.00000 | 19.74890 | 18.59354 | -1.0402 | 29.98373 |
Annual Sum or Average | 5943.00000 | 21.83119 | 35.06082 | -0.6673 | 18.73105 |
Minimum of Months | 454.00000 | 19.59035 | 15.60128 | -1.1220 | 7.74315 |
Maximum of Months | 514.00000 | 24.26478 | 53.90861 | -0.2868 | 33.62687 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70350 | 15.25594 | -1.0755 | 31.67780 |
February | 454.00000 | 19.99164 | 19.76259 | -0.9196 | 25.60856 |
March | 514.00000 | 20.93754 | 25.14156 | -0.5799 | 15.15263 |
April | 485.00000 | 21.95894 | 31.82455 | -0.2177 | 11.96420 |
May | 508.00000 | 23.61059 | 42.91759 | -0.5784 | 16.24963 |
June | 496.00000 | 23.97818 | 49.56830 | -0.3268 | 11.33648 |
July | 497.00000 | 24.33541 | 53.27101 | -0.1603 | 7.78573 |
August | 514.00000 | 24.03362 | 52.83077 | -0.2990 | 8.66470 |
September | 485.00000 | 23.32791 | 40.48881 | -0.6996 | 21.95838 |
October | 502.00000 | 21.47623 | 32.37168 | -0.3512 | 9.57016 |
November | 489.00000 | 20.33640 | 28.13120 | -0.7427 | 20.13075 |
December | 497.00000 | 19.84257 | 17.96253 | -1.0072 | 28.56923 |
Annual Sum or Average | 5943.00000 | 21.97813 | 34.25514 | -0.5771 | 17.30059 |
Minimum of Months | 454.00000 | 19.70350 | 15.25594 | -1.0755 | 7.78573 |
Maximum of Months | 514.00000 | 24.33541 | 53.27101 | -0.1603 | 31.67780 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15568 | 14.96143 | -0.9037 | 27.07919 |
February | 454.00000 | 20.62733 | 19.01191 | -0.7192 | 21.13041 |
March | 514.00000 | 21.44641 | 24.29824 | -0.4445 | 13.87458 |
April | 485.00000 | 22.14587 | 31.27869 | -0.1689 | 12.48714 |
May | 508.00000 | 23.48865 | 43.17024 | -0.6543 | 18.34446 |
June | 496.00000 | 23.90563 | 49.94150 | -0.4090 | 11.96039 |
July | 497.00000 | 24.24448 | 53.66143 | -0.2432 | 8.26817 |
August | 514.00000 | 24.07473 | 52.69414 | -0.3019 | 9.07907 |
September | 485.00000 | 23.50250 | 39.96749 | -0.6254 | 20.55933 |
October | 502.00000 | 22.23803 | 30.60294 | -0.1481 | 9.82818 |
November | 489.00000 | 20.95534 | 27.24436 | -0.5677 | 17.54034 |
December | 497.00000 | 20.43776 | 17.32459 | -0.8189 | 24.01247 |
Annual Sum or Average | 5943.00000 | 22.28293 | 33.81074 | -0.4988 | 16.12291 |
Minimum of Months | 454.00000 | 20.15568 | 14.96143 | -0.9037 | 8.26817 |
Maximum of Months | 514.00000 | 24.24448 | 53.66143 | -0.1481 | 27.07919 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72388 | 15.03092 | -1.0755 | 31.77317 |
February | 454.00000 | 20.08868 | 19.38734 | -0.9033 | 25.42679 |
March | 514.00000 | 20.90628 | 24.99245 | -0.5980 | 15.76016 |
April | 485.00000 | 21.83019 | 31.85328 | -0.2397 | 12.79525 |
May | 508.00000 | 23.19188 | 43.92408 | -0.7214 | 21.07153 |
June | 496.00000 | 23.81298 | 50.16785 | -0.3905 | 12.81302 |
July | 497.00000 | 24.18349 | 53.90342 | -0.2173 | 8.87516 |
August | 514.00000 | 23.93686 | 53.30533 | -0.3257 | 9.74859 |
September | 485.00000 | 23.03893 | 41.18621 | -0.7980 | 25.69022 |
October | 502.00000 | 21.37711 | 32.23779 | -0.3728 | 10.93017 |
November | 489.00000 | 20.33488 | 27.94634 | -0.7432 | 20.57159 |
December | 497.00000 | 19.85365 | 17.78839 | -1.0052 | 28.67420 |
Annual Sum or Average | 5943.00000 | 21.87225 | 34.44275 | -0.6136 | 18.59985 |
Minimum of Months | 454.00000 | 19.72388 | 15.03092 | -1.0755 | 8.87516 |
Maximum of Months | 514.00000 | 24.18349 | 53.90342 | -0.2173 | 31.77317 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.71023 | 15.57609 | -1.0754 | 31.20752 |
February | 454.00000 | 19.99175 | 20.39998 | -0.9414 | 25.57325 |
March | 514.00000 | 20.68054 | 26.51575 | -0.6820 | 16.15981 |
April | 485.00000 | 21.32021 | 34.06455 | -0.4261 | 11.50519 |
May | 508.00000 | 23.05000 | 45.63066 | -0.8933 | 24.15216 |
June | 496.00000 | 23.92564 | 50.48569 | -0.4867 | 11.39454 |
July | 497.00000 | 24.23174 | 53.95568 | -0.3337 | 7.76727 |
August | 514.00000 | 24.11971 | 52.98606 | -0.3796 | 8.37637 |
September | 485.00000 | 23.55202 | 40.60793 | -0.7050 | 18.19784 |
October | 502.00000 | 21.97831 | 32.13382 | -0.2372 | 7.31648 |
November | 489.00000 | 20.90013 | 28.02632 | -0.5831 | 15.31737 |
December | 497.00000 | 20.05877 | 18.55930 | -0.9277 | 24.72192 |
Annual Sum or Average | 5943.00000 | 21.97599 | 35.04260 | -0.6374 | 16.74662 |
Minimum of Months | 454.00000 | 19.71023 | 15.57609 | -1.0754 | 7.31648 |
Maximum of Months | 514.00000 | 24.23174 | 53.95568 | -0.2372 | 31.20752 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88037 | 15.59734 | -1.0188 | 28.75097 |
February | 454.00000 | 20.23332 | 20.12893 | -0.8582 | 22.28389 |
March | 514.00000 | 20.99953 | 25.70859 | -0.5731 | 13.86603 |
April | 485.00000 | 21.91056 | 32.52227 | -0.2544 | 10.43394 |
May | 508.00000 | 23.67330 | 43.51434 | -0.6168 | 16.10477 |
June | 496.00000 | 24.08299 | 49.39764 | -0.3392 | 9.98377 |
July | 497.00000 | 24.43963 | 52.82773 | -0.1623 | 6.96662 |
August | 514.00000 | 24.24528 | 52.07201 | -0.2472 | 7.09710 |
September | 485.00000 | 23.87299 | 39.27554 | -0.5181 | 14.60528 |
October | 502.00000 | 22.48173 | 30.93805 | -0.0971 | 6.55243 |
November | 489.00000 | 21.01263 | 27.66657 | -0.5431 | 14.22865 |
December | 497.00000 | 20.17172 | 18.26244 | -0.8904 | 23.24882 |
Annual Sum or Average | 5943.00000 | 22.26666 | 34.11875 | -0.5075 | 14.44831 |
Minimum of Months | 454.00000 | 19.88037 | 15.59734 | -1.0188 | 6.55243 |
Maximum of Months | 514.00000 | 24.43963 | 52.82773 | -0.0971 | 28.75097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.75962 | 13.92482 | -1.1499 | 35.00421 |
February | 454.00000 | 19.67997 | 18.18392 | -0.8764 | 24.65731 |
March | 514.00000 | 20.71777 | 23.73578 | -0.5819 | 15.92168 |
April | 485.00000 | 21.65780 | 31.19662 | -0.2844 | 11.94420 |
May | 508.00000 | 23.02863 | 44.67105 | -0.8336 | 23.26896 |
June | 496.00000 | 23.73092 | 51.26720 | -0.4968 | 13.23199 |
July | 497.00000 | 24.24848 | 55.10942 | -0.2647 | 7.81979 |
August | 514.00000 | 24.17884 | 53.51928 | -0.2667 | 7.90441 |
September | 485.00000 | 23.77641 | 38.87924 | -0.5085 | 16.26738 |
October | 502.00000 | 22.79707 | 28.66568 | 0.02788 | 7.65147 |
November | 489.00000 | 21.02398 | 25.61762 | -0.4780 | 15.42307 |
December | 497.00000 | 19.71440 | 16.38398 | -0.9006 | 25.91859 |
Annual Sum or Average | 5943.00000 | 21.95995 | 33.57101 | -0.5493 | 17.03354 |
Minimum of Months | 454.00000 | 18.75962 | 13.92482 | -1.1499 | 7.65147 |
Maximum of Months | 514.00000 | 24.24848 | 55.10942 | 0.02788 | 35.00421 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.87957 | 15.37695 | -1.0238 | 29.03269 |
February | 454.00000 | 20.29428 | 19.79001 | -0.8473 | 22.22597 |
March | 514.00000 | 20.94947 | 25.59386 | -0.5937 | 14.43549 |
April | 485.00000 | 21.91285 | 32.29896 | -0.2445 | 10.54036 |
May | 508.00000 | 23.27644 | 44.47457 | -0.7567 | 20.45108 |
June | 496.00000 | 23.97532 | 49.84299 | -0.3866 | 10.93662 |
July | 497.00000 | 24.41635 | 53.01647 | -0.1776 | 7.07477 |
August | 514.00000 | 24.26004 | 52.14595 | -0.2399 | 7.10673 |
September | 485.00000 | 23.71873 | 39.67694 | -0.5762 | 16.45845 |
October | 502.00000 | 22.31185 | 30.84037 | -0.1311 | 7.02841 |
November | 489.00000 | 21.00381 | 27.46777 | -0.5439 | 14.49113 |
December | 497.00000 | 20.17314 | 18.09339 | -0.8904 | 23.40380 |
Annual Sum or Average | 5943.00000 | 22.19598 | 34.18154 | -0.5324 | 15.21254 |
Minimum of Months | 454.00000 | 19.87957 | 15.37695 | -1.0238 | 7.02841 |
Maximum of Months | 514.00000 | 24.41635 | 53.01647 | -0.1311 | 29.03269 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74448 | 15.80683 | -1.0379 | 29.90121 |
February | 454.00000 | 20.10657 | 20.26486 | -0.8775 | 23.30803 |
March | 514.00000 | 21.00005 | 25.89067 | -0.5621 | 13.81391 |
April | 485.00000 | 21.98825 | 32.58153 | -0.2278 | 9.73967 |
May | 508.00000 | 23.67717 | 43.26545 | -0.6374 | 15.45801 |
June | 496.00000 | 24.15079 | 49.47180 | -0.3713 | 9.36827 |
July | 497.00000 | 24.34210 | 53.37849 | -0.2663 | 7.15380 |
August | 514.00000 | 24.15815 | 52.76666 | -0.3487 | 8.02586 |
September | 485.00000 | 23.53289 | 40.67597 | -0.7044 | 18.76097 |
October | 502.00000 | 21.88304 | 32.49675 | -0.2579 | 7.97971 |
November | 489.00000 | 20.78103 | 28.06270 | -0.6119 | 16.62395 |
December | 497.00000 | 19.99359 | 18.46538 | -0.9330 | 25.25274 |
Annual Sum or Average | 5943.00000 | 22.12991 | 34.55398 | -0.5675 | 15.37624 |
Minimum of Months | 454.00000 | 19.74448 | 15.80683 | -1.0379 | 7.15380 |
Maximum of Months | 514.00000 | 24.34210 | 53.37849 | -0.2278 | 29.90121 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.64775 | 14.86913 | -1.0436 | 30.25116 |
February | 385.00000 | 20.13505 | 19.07212 | -0.8499 | 22.43387 |
March | 433.00000 | 21.12434 | 24.44863 | -0.5120 | 13.07825 |
April | 410.00000 | 22.19645 | 30.81456 | -0.1497 | 10.47510 |
May | 430.00000 | 23.77337 | 42.22394 | -0.5345 | 14.70979 |
June | 418.00000 | 24.14493 | 48.80262 | -0.2994 | 10.23884 |
July | 422.00000 | 24.46151 | 52.47772 | -0.1481 | 7.60145 |
August | 433.00000 | 24.16214 | 52.13280 | -0.2817 | 8.11807 |
September | 410.00000 | 23.56738 | 39.55842 | -0.6232 | 18.85999 |
October | 427.00000 | 21.92321 | 30.94522 | -0.2284 | 7.76699 |
November | 417.00000 | 20.65056 | 26.70740 | -0.6355 | 16.65517 |
December | 422.00000 | 19.90905 | 17.29861 | -0.9431 | 25.74284 |
Annual Sum or Average | 5034.00000 | 22.15451 | 33.38430 | -0.5187 | 15.43459 |
Minimum of Months | 385.00000 | 19.64775 | 14.86913 | -1.0436 | 7.60145 |
Maximum of Months | 433.00000 | 24.46151 | 52.47772 | -0.1481 | 30.25116 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46603 | 14.90496 | -0.7927 | 22.86486 |
February | 454.00000 | 21.05623 | 18.74594 | -0.5837 | 16.70601 |
March | 514.00000 | 21.82495 | 23.87435 | -0.3259 | 11.30608 |
April | 485.00000 | 22.54428 | 30.70256 | -0.0583 | 10.29019 |
May | 508.00000 | 23.78015 | 42.49314 | -0.5582 | 14.43767 |
June | 496.00000 | 24.10161 | 49.27329 | -0.3524 | 9.74601 |
July | 497.00000 | 24.36011 | 53.01278 | -0.2139 | 7.33977 |
August | 514.00000 | 24.22843 | 52.05657 | -0.2554 | 7.72482 |
September | 485.00000 | 23.85906 | 39.11163 | -0.4974 | 15.42326 |
October | 502.00000 | 22.85508 | 29.59375 | 0.01968 | 8.15891 |
November | 489.00000 | 21.53006 | 26.47749 | -0.3979 | 13.91333 |
December | 497.00000 | 20.78624 | 17.04545 | -0.6934 | 19.69894 |
Annual Sum or Average | 5943.00000 | 22.62905 | 33.23740 | -0.3912 | 13.09466 |
Minimum of Months | 454.00000 | 20.46603 | 14.90496 | -0.7927 | 7.33977 |
Maximum of Months | 514.00000 | 24.36011 | 53.01278 | 0.01968 | 22.86486 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86706 | 15.04934 | -0.9957 | 28.29998 |
February | 454.00000 | 20.36951 | 19.21339 | -0.7955 | 21.07341 |
March | 514.00000 | 21.19125 | 24.65848 | -0.4959 | 12.96754 |
April | 485.00000 | 22.18524 | 31.31124 | -0.1367 | 10.43403 |
May | 508.00000 | 23.51365 | 43.22196 | -0.6169 | 16.64427 |
June | 496.00000 | 24.01936 | 49.49121 | -0.3312 | 10.40473 |
July | 497.00000 | 24.32015 | 53.22078 | -0.1823 | 7.73437 |
August | 514.00000 | 24.12518 | 52.59159 | -0.2696 | 8.09036 |
September | 485.00000 | 23.42586 | 40.30285 | -0.6601 | 19.80790 |
October | 502.00000 | 21.92145 | 31.35051 | -0.2162 | 8.22626 |
November | 489.00000 | 20.78578 | 27.29832 | -0.5968 | 16.00602 |
December | 497.00000 | 20.09528 | 17.58682 | -0.8997 | 24.21072 |
Annual Sum or Average | 5943.00000 | 22.16673 | 33.90537 | -0.5143 | 15.26406 |
Minimum of Months | 454.00000 | 19.86706 | 15.04934 | -0.9957 | 7.73437 |
Maximum of Months | 514.00000 | 24.32015 | 53.22078 | -0.1367 | 28.29998 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.190016E+12 | 0.00 | 614.33 | 276120.28 | 31-JAN-07:05 | 0.00 | 39.68 | 56.12 | 0.93 | 0.00 | 0.16 | 0.63 | 31-JAN-07:05 |
February | 0.120627E+12 | 0.00 | 476.10 | 282706.91 | 02-FEB-07:12 | 0.00 | 35.40 | 52.11 | 0.59 | 0.00 | 0.11 | 0.65 | 02-FEB-07:12 |
March | 0.648628E+11 | 0.00 | 412.96 | 235051.68 | 31-MAR-06:01 | 0.00 | 30.48 | 45.74 | 0.24 | 0.00 | 0.06 | 0.54 | 31-MAR-06:01 |
April | 0.228935E+11 | 0.00 | 269.36 | 244655.32 | 26-APR-06:01 | 0.00 | 32.19 | 42.67 | 0.08 | 0.00 | 0.02 | 0.56 | 26-APR-06:01 |
May | 0.117365E+10 | 0.00 | 66.42 | 173782.62 | 02-MAY-06:02 | 0.00 | 43.04 | 44.64 | 0.01 | 0.00 | 0.00 | 0.40 | 02-MAY-06:02 |
June | 0.249390E+09 | 0.00 | 82.85 | 19515.19 | 05-JUN-06:05 | 0.00 | 40.09 | 42.50 | 0.00 | 0.00 | 0.00 | 0.04 | 05-JUN-06:05 |
July | 6272270.00 | 0.00 | 94.29 | 9537.50 | 24-JUL-06:07 | 0.00 | 35.65 | 38.75 | 0.00 | 0.00 | 0.00 | 0.02 | 24-JUL-06:07 |
August | 34711933.28 | 0.00 | 87.67 | 14749.84 | 07-AUG-06:06 | 0.00 | 35.73 | 38.60 | 0.00 | 0.00 | 0.00 | 0.03 | 07-AUG-06:06 |
September | 0.197464E+10 | 0.00 | 103.67 | 208438.14 | 29-SEP-06:02 | 0.00 | 36.29 | 39.86 | 0.01 | 0.00 | 0.00 | 0.48 | 29-SEP-06:02 |
October | 0.109265E+11 | 0.00 | 236.81 | 225912.41 | 26-OCT-06:02 | 0.00 | 28.06 | 37.60 | 0.04 | 0.00 | 0.01 | 0.52 | 26-OCT-06:02 |
November | 0.664986E+11 | 0.00 | 397.78 | 265926.74 | 20-NOV-06:11 | 0.00 | 33.08 | 46.99 | 0.28 | 0.00 | 0.06 | 0.61 | 20-NOV-06:11 |
December | 0.139520E+12 | 0.00 | 532.72 | 253794.43 | 11-DEC-07:07 | 0.00 | 36.67 | 52.79 | 0.61 | 0.00 | 0.12 | 0.58 | 11-DEC-07:07 |
Annual Sum or Average | 0.618783E+12 | 0.00 | 3374.96 | 0.00 | 35.53 | 44.83 | 0.23 | 0.00 | 0.04 | ||||
Minimum of Months | 6272270.00 | 0.00 | 66.42 | 9537.50 | 0.00 | 28.06 | 37.60 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.190016E+12 | 0.00 | 614.33 | 282706.91 | 0.00 | 43.04 | 56.12 | 0.93 | 0.00 | 0.16 | 0.65 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.161351E+09 | 42314725.57 | 11.00 | 0.142329E+09 | 19022420.52 | 0.00 | 0.25 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7712.66 | 25-MAR-15:00 | 6879.32 | 25-MAR-15:00 | 1025.85 | 25-MAR-15:40 | 1981.15 | 25-MAR-15:00 | 0.00 |
April | 0.542952E+10 | 0.128149E+10 | 75.98 | 0.424299E+10 | 0.118652E+10 | 0.00 | 1.00 | 18-APR-08:40 | 0.00 | 01-APR-00:10 | 67012.65 | 18-APR-15:00 | 56596.12 | 18-APR-15:00 | 22730.44 | 18-APR-09:30 | 15558.02 | 18-APR-15:00 | 0.00 |
May | 0.147989E+11 | 0.345640E+10 | 222.79 | 0.111516E+11 | 0.364724E+10 | 0.00 | 1.00 | 05-MAY-12:50 | 0.00 | 01-MAY-00:10 | 71377.04 | 30-MAY-11:00 | 60650.70 | 31-MAY-15:00 | 29376.28 | 30-MAY-10:10 | 16031.83 | 31-MAY-15:00 | 0.00 |
June | 0.460337E+11 | 0.104691E+11 | 345.42 | 0.343925E+11 | 0.116412E+11 | 0.00 | 1.00 | 08-JUN-15:50 | 0.00 | 01-JUN-00:10 | 128332.12 | 26-JUN-07:50 | 73224.67 | 26-JUN-15:50 | 74337.32 | 26-JUN-06:03 | 26695.19 | 26-JUN-07:45 | 0.00 |
July | 0.661556E+11 | 0.146247E+11 | 434.14 | 0.448640E+11 | 0.212917E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 120254.86 | 05-JUL-10:50 | 71593.33 | 03-JUL-15:00 | 68367.04 | 05-JUL-06:03 | 25519.87 | 05-JUL-10:50 | 0.00 |
August | 0.648198E+11 | 0.144134E+11 | 423.64 | 0.449078E+11 | 0.199120E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 129595.42 | 03-AUG-06:03 | 73218.28 | 04-AUG-16:00 | 93338.13 | 04-AUG-07:00 | 26860.46 | 04-AUG-07:33 | 0.00 |
September | 0.262104E+11 | 0.607828E+10 | 244.83 | 0.232067E+11 | 0.300368E+10 | 0.00 | 1.00 | 01-SEP-11:00 | 0.00 | 01-SEP-00:10 | 99240.59 | 11-SEP-09:50 | 68986.57 | 07-SEP-15:50 | 39866.88 | 11-SEP-09:50 | 21202.47 | 11-SEP-09:50 | 0.00 |
October | 0.165068E+10 | 0.403117E+09 | 49.65 | 0.143739E+10 | 0.213297E+09 | 0.00 | 0.96 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 36123.10 | 20-OCT-15:00 | 36123.10 | 20-OCT-15:00 | 5248.18 | 02-OCT-15:00 | 7670.47 | 20-OCT-15:00 | 0.00 |
November | 58292914.63 | 15432475.57 | 5.67 | 53535882.59 | 4757032.04 | 0.00 | 0.17 | 03-NOV-15:00 | 0.00 | 01-NOV-00:10 | 5059.30 | 03-NOV-15:00 | 5059.30 | 03-NOV-15:00 | 567.24 | 03-NOV-12:10 | 1325.54 | 03-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.225318E+12 | 0.507841E+11 | 1813.11 | 0.164399E+12 | 0.609193E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.661556E+11 | 0.146247E+11 | 434.14 | 0.449078E+11 | 0.212917E+11 | 0.00 | 1.00 | 0.00 | 129595.42 | 73224.67 | 93338.13 | 26860.46 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.204570E+09 | 53325590.06 | 12.85 | 0.171182E+09 | 33388636.26 | 0.00 | 0.29 | 19-MAR-14:38 | 0.00 | 01-MAR-00:10 | 8766.29 | 19-MAR-14:38 | 8193.26 | 25-MAR-15:00 | 3045.26 | 19-MAR-14:38 | 2228.36 | 19-MAR-14:38 | 0.00 |
April | 0.591315E+10 | 0.138358E+10 | 81.62 | 0.468811E+10 | 0.122503E+10 | 0.00 | 1.00 | 15-APR-13:40 | 0.00 | 01-APR-00:10 | 69211.56 | 18-APR-12:40 | 57872.60 | 18-APR-15:00 | 26117.25 | 18-APR-09:30 | 15737.65 | 18-APR-12:30 | 0.00 |
May | 0.154369E+11 | 0.359536E+10 | 239.26 | 0.115313E+11 | 0.390565E+10 | 0.00 | 1.00 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 | 71546.37 | 30-MAY-11:00 | 59346.96 | 31-MAY-15:00 | 30498.41 | 30-MAY-10:00 | 15759.26 | 31-MAY-15:00 | 0.00 |
June | 0.441780E+11 | 0.100508E+11 | 348.24 | 0.329659E+11 | 0.112121E+11 | 0.00 | 1.00 | 08-JUN-15:30 | 0.00 | 01-JUN-00:10 | 123115.65 | 26-JUN-07:50 | 68222.51 | 26-JUN-15:30 | 71403.80 | 26-JUN-06:03 | 25610.08 | 26-JUN-07:45 | 0.00 |
July | 0.605903E+11 | 0.134266E+11 | 435.46 | 0.409324E+11 | 0.196579E+11 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:10 | 111163.59 | 03-JUL-08:50 | 66357.52 | 03-JUL-15:10 | 66320.06 | 05-JUL-06:03 | 23494.55 | 05-JUL-10:50 | 0.00 |
August | 0.566922E+11 | 0.126713E+11 | 423.54 | 0.392809E+11 | 0.174113E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 124327.60 | 04-AUG-06:03 | 71099.79 | 04-AUG-15:20 | 88490.86 | 04-AUG-07:05 | 25697.42 | 04-AUG-07:30 | 0.00 |
September | 0.228398E+11 | 0.532292E+10 | 237.94 | 0.201945E+11 | 0.264534E+10 | 0.00 | 1.00 | 01-SEP-12:00 | 0.00 | 01-SEP-00:10 | 88575.16 | 11-SEP-09:50 | 66612.30 | 07-SEP-16:00 | 35419.70 | 11-SEP-09:50 | 19135.81 | 06-SEP-14:20 | 0.00 |
October | 0.144964E+10 | 0.357132E+09 | 49.99 | 0.123991E+10 | 0.209724E+09 | 0.00 | 0.87 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 30536.86 | 20-OCT-15:00 | 30536.86 | 20-OCT-15:00 | 4762.49 | 02-OCT-15:00 | 6658.66 | 20-OCT-15:00 | 0.00 |
November | 78277911.17 | 20429173.43 | 5.67 | 67070532.18 | 11207378.99 | 0.00 | 0.24 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 7104.46 | 03-NOV-13:30 | 5973.38 | 03-NOV-13:50 | 1413.40 | 03-NOV-13:00 | 1829.07 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.207383E+12 | 0.468815E+11 | 1834.56 | 0.151071E+12 | 0.563116E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.605903E+11 | 0.134266E+11 | 435.46 | 0.409324E+11 | 0.196579E+11 | 0.00 | 1.00 | 0.00 | 124327.60 | 71099.79 | 88490.86 | 25697.42 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1010801.22 | 274031.77 | 0.52 | 1007296.44 | 3504.78 | 0.00 | 0.04 | 02-JAN-06:17 | 0.00 | 01-JAN-00:03 | 1124.85 | 02-JAN-06:17 | 1124.85 | 02-JAN-06:17 | 8.99 | 11-JAN-05:43 | 303.86 | 02-JAN-06:17 | 0.00 |
February | 573565.97 | 155712.84 | 0.44 | 565194.19 | 8371.77 | 0.00 | 0.02 | 06-FEB-06:30 | 0.00 | 01-FEB-00:05 | 644.53 | 06-FEB-06:30 | 644.53 | 06-FEB-06:30 | 17.09 | 07-FEB-05:50 | 174.72 | 06-FEB-06:30 | 0.00 |
March | 0.187738E+09 | 49131753.39 | 11.89 | 0.156119E+09 | 31618936.32 | 0.00 | 0.29 | 19-MAR-13:53 | 0.00 | 01-MAR-00:10 | 9593.33 | 19-MAR-13:53 | 7951.38 | 25-MAR-15:00 | 3337.56 | 19-MAR-13:53 | 2440.15 | 19-MAR-13:53 | 0.00 |
April | 0.647034E+10 | 0.151361E+10 | 81.67 | 0.507979E+10 | 0.139055E+10 | 0.00 | 1.00 | 15-APR-13:30 | 0.00 | 01-APR-00:10 | 96171.09 | 16-APR-13:42 | 69646.69 | 16-APR-15:02 | 35846.03 | 16-APR-13:42 | 21470.82 | 16-APR-13:42 | 0.00 |
May | 0.162732E+11 | 0.380269E+10 | 240.06 | 0.121907E+11 | 0.408257E+10 | 0.00 | 1.00 | 04-MAY-14:00 | 0.00 | 01-MAY-00:10 | 73143.58 | 31-MAY-15:00 | 67921.72 | 31-MAY-15:00 | 28045.47 | 30-MAY-10:00 | 17702.35 | 31-MAY-15:00 | 0.00 |
June | 0.466582E+11 | 0.106590E+11 | 348.38 | 0.351354E+11 | 0.115228E+11 | 0.00 | 1.00 | 08-JUN-15:30 | 0.00 | 01-JUN-00:10 | 132187.84 | 26-JUN-06:03 | 79047.84 | 25-JUN-15:12 | 79235.16 | 26-JUN-06:03 | 27580.87 | 26-JUN-06:03 | 0.00 |
July | 0.635136E+11 | 0.141207E+11 | 433.83 | 0.427777E+11 | 0.207359E+11 | 0.00 | 1.00 | 01-JUL-13:00 | 0.00 | 01-JUL-00:10 | 115687.52 | 06-JUL-15:10 | 73762.88 | 03-JUL-15:00 | 56380.29 | 17-JUL-16:10 | 24621.97 | 06-JUL-15:10 | 0.00 |
August | 0.580435E+11 | 0.130494E+11 | 423.27 | 0.406068E+11 | 0.174367E+11 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 137169.52 | 04-AUG-07:15 | 81372.93 | 04-AUG-15:10 | 96688.90 | 04-AUG-07:15 | 28319.05 | 04-AUG-07:15 | 0.00 |
September | 0.233118E+11 | 0.547380E+10 | 235.12 | 0.205090E+11 | 0.280278E+10 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 85429.20 | 11-SEP-10:00 | 74559.87 | 07-SEP-15:50 | 32509.99 | 11-SEP-10:00 | 20521.67 | 06-SEP-14:00 | 0.00 |
October | 0.140308E+10 | 0.349611E+09 | 48.39 | 0.117196E+10 | 0.231120E+09 | 0.00 | 0.79 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29718.13 | 20-OCT-15:00 | 29718.13 | 20-OCT-15:00 | 4668.33 | 02-OCT-15:00 | 6638.02 | 20-OCT-15:00 | 0.00 |
November | 47523575.27 | 12660513.51 | 5.77 | 40333879.63 | 7189695.64 | 0.00 | 0.13 | 03-NOV-13:40 | 0.00 | 01-NOV-00:10 | 4000.88 | 03-NOV-13:40 | 3438.11 | 03-NOV-14:40 | 708.40 | 03-NOV-13:30 | 1058.47 | 03-NOV-13:40 | 0.00 |
December | 812945.82 | 220872.38 | 0.77 | 794636.09 | 18309.73 | 0.00 | 0.02 | 13-DEC-06:07 | 0.00 | 01-DEC-00:10 | 655.43 | 13-DEC-06:07 | 655.43 | 13-DEC-06:07 | 24.49 | 04-DEC-01:30 | 177.66 | 13-DEC-06:07 | 0.00 |
Annual Sum or Average | 0.215911E+12 | 0.490313E+11 | 1830.12 | 0.157670E+12 | 0.582413E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 573565.97 | 155712.84 | 0.44 | 565194.19 | 3504.78 | 0.00 | 0.02 | 0.00 | 644.53 | 644.53 | 8.99 | 174.72 | 0.00 | ||||||
Maximum of Months | 0.635136E+11 | 0.141207E+11 | 433.83 | 0.427777E+11 | 0.207359E+11 | 0.00 | 1.00 | 0.00 | 137169.52 | 81372.93 | 96688.90 | 28319.05 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.00 | 0.00 | 390.00 | 2.15 | 3018.14 | 0.00 | 0.00 | 0.00 |
February | 494.45 | 0.00 | 494.45 | 33.15 | 2415.77 | 0.00 | 0.00 | 0.00 |
March | 741.02 | 0.00 | 741.02 | 241.16 | 1541.76 | 0.00 | 0.00 | 0.00 |
April | 855.46 | 4.21 | 851.25 | 480.93 | 1059.75 | 0.00 | 0.00 | 0.00 |
May | 1115.54 | 41.93 | 1073.61 | 974.22 | 627.74 | 0.00 | 0.00 | 0.00 |
June | 1303.81 | 118.34 | 1185.47 | 1464.13 | 435.34 | 0.00 | 0.00 | 0.00 |
July | 1222.77 | 81.79 | 1140.98 | 1432.97 | 381.15 | 0.00 | 0.00 | 0.00 |
August | 1023.82 | 18.14 | 1005.67 | 1194.14 | 446.60 | 0.00 | 0.00 | 0.00 |
September | 784.97 | 0.19 | 784.78 | 727.37 | 765.26 | 0.00 | 0.00 | 0.00 |
October | 583.64 | 0.00 | 583.64 | 286.81 | 1150.50 | 0.00 | 0.00 | 0.00 |
November | 408.26 | 0.00 | 408.26 | 73.07 | 1789.70 | 0.00 | 0.00 | 0.00 |
December | 264.82 | 0.00 | 264.82 | 0.61 | 2652.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 767.15 | 22.14 | 745.01 | 579.14 | 1352.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 264.82 | 0.00 | 264.82 | 0.61 | 381.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1303.81 | 118.34 | 1185.47 | 1464.13 | 3018.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 557.14 | 229.26 | 327.87 | 244.15 | 1816.82 | 0.00 | 0.00 | 0.00 |
February | 738.48 | 324.73 | 413.76 | 427.81 | 1432.28 | 0.00 | 0.00 | 0.00 |
March | 1003.37 | 398.27 | 605.10 | 770.95 | 946.37 | 0.00 | 0.00 | 0.00 |
April | 1232.04 | 539.55 | 692.49 | 1170.47 | 680.18 | 0.00 | 0.00 | 0.00 |
May | 1547.35 | 676.12 | 871.23 | 1707.70 | 420.97 | 0.00 | 0.00 | 0.00 |
June | 1702.82 | 741.55 | 961.27 | 2085.96 | 291.11 | 0.00 | 0.00 | 0.00 |
July | 1721.11 | 794.16 | 926.95 | 2157.77 | 254.65 | 0.00 | 0.00 | 0.00 |
August | 1450.86 | 625.50 | 825.36 | 1822.92 | 296.48 | 0.00 | 0.00 | 0.00 |
September | 1294.04 | 611.50 | 682.54 | 1506.63 | 491.01 | 0.00 | 0.00 | 0.00 |
October | 824.65 | 344.45 | 480.20 | 736.36 | 720.61 | 0.00 | 0.00 | 0.00 |
November | 486.55 | 158.04 | 328.51 | 263.87 | 1109.40 | 0.00 | 0.00 | 0.00 |
December | 376.89 | 161.84 | 215.04 | 170.63 | 1635.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1079.63 | 467.75 | 611.87 | 1092.36 | 838.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.89 | 158.04 | 215.04 | 170.63 | 254.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1721.11 | 794.16 | 961.27 | 2157.77 | 1816.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2425.42 | 1659.77 | 765.65 | 2131.08 | 2467.65 | 0.00 | 0.00 | 0.00 |
February | 2598.79 | 1755.77 | 843.03 | 2380.05 | 1986.33 | 0.00 | 0.00 | 0.00 |
March | 2261.53 | 1190.85 | 1070.68 | 2170.72 | 1444.29 | 0.00 | 0.00 | 0.00 |
April | 2037.49 | 952.57 | 1084.92 | 2175.19 | 1083.61 | 0.00 | 0.00 | 0.00 |
May | 1687.99 | 457.64 | 1230.35 | 1909.60 | 682.90 | 0.00 | 0.00 | 0.00 |
June | 1638.78 | 333.67 | 1305.12 | 2059.83 | 465.45 | 0.00 | 0.00 | 0.00 |
July | 1734.77 | 437.12 | 1297.65 | 2276.00 | 405.69 | 0.00 | 0.00 | 0.00 |
August | 1954.51 | 700.93 | 1253.57 | 2604.59 | 478.38 | 0.00 | 0.00 | 0.00 |
September | 2368.45 | 1247.98 | 1120.47 | 2951.09 | 777.83 | 0.00 | 0.00 | 0.00 |
October | 2473.16 | 1551.56 | 921.60 | 2710.03 | 1114.33 | 0.00 | 0.00 | 0.00 |
November | 1866.00 | 1168.15 | 697.85 | 1744.76 | 1597.65 | 0.00 | 0.00 | 0.00 |
December | 1989.81 | 1507.26 | 482.55 | 1876.29 | 2286.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2083.37 | 1076.41 | 1006.96 | 2248.21 | 1229.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1638.78 | 333.67 | 482.55 | 1744.76 | 405.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2598.79 | 1755.77 | 1305.12 | 2951.09 | 2467.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.54 | 223.57 | 328.98 | 252.08 | 1861.13 | 0.00 | 0.00 | 0.00 |
February | 810.21 | 399.25 | 410.96 | 526.34 | 1486.15 | 0.00 | 0.00 | 0.00 |
March | 967.22 | 359.86 | 607.36 | 729.61 | 977.76 | 0.00 | 0.00 | 0.00 |
April | 1410.89 | 697.66 | 713.23 | 1427.47 | 708.71 | 0.00 | 0.00 | 0.00 |
May | 1414.97 | 565.25 | 849.72 | 1571.87 | 444.36 | 0.00 | 0.00 | 0.00 |
June | 1660.30 | 719.53 | 940.76 | 2048.17 | 313.05 | 0.00 | 0.00 | 0.00 |
July | 1782.65 | 846.79 | 935.87 | 2260.79 | 279.78 | 0.00 | 0.00 | 0.00 |
August | 1558.49 | 715.24 | 843.24 | 1988.36 | 320.05 | 0.00 | 0.00 | 0.00 |
September | 1261.55 | 598.80 | 662.75 | 1478.73 | 513.60 | 0.00 | 0.00 | 0.00 |
October | 879.10 | 390.84 | 488.26 | 822.75 | 753.08 | 0.00 | 0.00 | 0.00 |
November | 526.20 | 194.59 | 331.61 | 330.07 | 1135.66 | 0.00 | 0.00 | 0.00 |
December | 404.68 | 190.77 | 213.91 | 220.14 | 1670.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1103.57 | 491.94 | 611.63 | 1141.05 | 869.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 404.68 | 190.77 | 213.91 | 220.14 | 279.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1782.65 | 846.79 | 940.76 | 2260.79 | 1861.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 129.99 | 0.00 | 129.99 | 0.78 | 1008.36 | 0.00 | 0.00 | 0.00 |
February | 164.81 | 0.00 | 164.81 | 11.16 | 810.20 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 247.00 | 86.61 | 514.54 | 0.00 | 0.00 | 0.00 |
April | 285.14 | 1.40 | 283.74 | 172.79 | 346.39 | 0.00 | 0.00 | 0.00 |
May | 371.83 | 13.98 | 357.85 | 342.21 | 200.13 | 0.00 | 0.00 | 0.00 |
June | 434.58 | 39.44 | 395.14 | 498.86 | 142.53 | 0.00 | 0.00 | 0.00 |
July | 407.57 | 27.26 | 380.31 | 485.58 | 126.16 | 0.00 | 0.00 | 0.00 |
August | 341.26 | 6.05 | 335.21 | 401.05 | 152.61 | 0.00 | 0.00 | 0.00 |
September | 261.65 | 0.06 | 261.58 | 240.34 | 271.78 | 0.00 | 0.00 | 0.00 |
October | 194.54 | 0.00 | 194.54 | 88.52 | 417.82 | 0.00 | 0.00 | 0.00 |
November | 136.08 | 0.00 | 136.08 | 21.37 | 633.44 | 0.00 | 0.00 | 0.00 |
December | 88.27 | 0.00 | 88.27 | 0.09 | 906.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.70 | 7.38 | 248.33 | 196.88 | 459.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.27 | 0.00 | 88.27 | 0.09 | 126.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.58 | 39.44 | 395.14 | 498.86 | 1008.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.00 | 0.00 | 130.00 | 0.78 | 1008.42 | 0.00 | 0.00 | 0.00 |
February | 164.81 | 0.00 | 164.81 | 11.15 | 810.26 | 0.00 | 0.00 | 0.00 |
March | 247.01 | 0.00 | 247.01 | 86.61 | 514.58 | 0.00 | 0.00 | 0.00 |
April | 285.15 | 1.40 | 283.75 | 172.79 | 346.41 | 0.00 | 0.00 | 0.00 |
May | 371.84 | 13.98 | 357.87 | 342.22 | 200.14 | 0.00 | 0.00 | 0.00 |
June | 434.60 | 39.45 | 395.15 | 498.88 | 142.54 | 0.00 | 0.00 | 0.00 |
July | 407.59 | 27.26 | 380.32 | 485.60 | 126.17 | 0.00 | 0.00 | 0.00 |
August | 341.27 | 6.05 | 335.22 | 401.07 | 152.62 | 0.00 | 0.00 | 0.00 |
September | 261.66 | 0.06 | 261.59 | 240.35 | 271.80 | 0.00 | 0.00 | 0.00 |
October | 194.55 | 0.00 | 194.55 | 88.52 | 417.85 | 0.00 | 0.00 | 0.00 |
November | 136.09 | 0.00 | 136.09 | 21.37 | 633.48 | 0.00 | 0.00 | 0.00 |
December | 88.27 | 0.00 | 88.27 | 0.09 | 906.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.71 | 7.38 | 248.34 | 196.89 | 459.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.27 | 0.00 | 88.27 | 0.09 | 126.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.60 | 39.45 | 395.15 | 498.88 | 1008.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 130.00 | 0.00 | 130.00 | 0.78 | 1008.42 | 0.00 | 0.00 | 0.00 |
February | 164.81 | 0.00 | 164.81 | 11.15 | 810.26 | 0.00 | 0.00 | 0.00 |
March | 247.01 | 0.00 | 247.01 | 86.61 | 514.58 | 0.00 | 0.00 | 0.00 |
April | 285.15 | 1.40 | 283.75 | 172.79 | 346.41 | 0.00 | 0.00 | 0.00 |
May | 371.84 | 13.98 | 357.87 | 342.22 | 200.14 | 0.00 | 0.00 | 0.00 |
June | 434.60 | 39.45 | 395.15 | 498.88 | 142.54 | 0.00 | 0.00 | 0.00 |
July | 407.59 | 27.26 | 380.32 | 485.60 | 126.17 | 0.00 | 0.00 | 0.00 |
August | 341.27 | 6.05 | 335.22 | 401.07 | 152.62 | 0.00 | 0.00 | 0.00 |
September | 261.66 | 0.06 | 261.59 | 240.35 | 271.80 | 0.00 | 0.00 | 0.00 |
October | 194.55 | 0.00 | 194.55 | 88.52 | 417.85 | 0.00 | 0.00 | 0.00 |
November | 136.09 | 0.00 | 136.09 | 21.37 | 633.48 | 0.00 | 0.00 | 0.00 |
December | 88.27 | 0.00 | 88.27 | 0.09 | 906.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 255.71 | 7.38 | 248.34 | 196.89 | 459.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.27 | 0.00 | 88.27 | 0.09 | 126.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 434.60 | 39.45 | 395.15 | 498.88 | 1008.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 535.94 | 220.54 | 315.40 | 238.18 | 1760.78 | 0.00 | 0.00 | 0.00 |
February | 710.38 | 312.37 | 398.01 | 416.05 | 1401.03 | 0.00 | 0.00 | 0.00 |
March | 965.19 | 383.11 | 582.08 | 756.56 | 923.25 | 0.00 | 0.00 | 0.00 |
April | 1185.17 | 519.02 | 666.15 | 1149.47 | 658.01 | 0.00 | 0.00 | 0.00 |
May | 1488.47 | 650.39 | 838.08 | 1666.61 | 406.67 | 0.00 | 0.00 | 0.00 |
June | 1638.02 | 713.33 | 924.69 | 2023.11 | 287.07 | 0.00 | 0.00 | 0.00 |
July | 1655.62 | 763.94 | 891.68 | 2087.46 | 254.95 | 0.00 | 0.00 | 0.00 |
August | 1395.66 | 601.70 | 793.96 | 1758.93 | 302.90 | 0.00 | 0.00 | 0.00 |
September | 1244.80 | 588.23 | 656.57 | 1444.13 | 517.04 | 0.00 | 0.00 | 0.00 |
October | 793.27 | 331.34 | 461.93 | 687.11 | 769.45 | 0.00 | 0.00 | 0.00 |
November | 468.04 | 152.03 | 316.01 | 243.26 | 1138.99 | 0.00 | 0.00 | 0.00 |
December | 362.55 | 155.69 | 206.86 | 162.74 | 1619.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1038.55 | 449.95 | 588.59 | 1056.26 | 834.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.55 | 152.03 | 206.86 | 162.74 | 254.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1655.62 | 763.94 | 924.69 | 2087.46 | 1760.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.19 | 8.72 | 12.47 | 9.42 | 69.62 | 0.00 | 0.00 | 0.00 |
February | 28.09 | 12.35 | 15.74 | 16.45 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 38.16 | 15.15 | 23.01 | 29.91 | 36.50 | 0.00 | 0.00 | 0.00 |
April | 46.86 | 20.52 | 26.34 | 45.45 | 26.02 | 0.00 | 0.00 | 0.00 |
May | 58.85 | 25.72 | 33.14 | 65.90 | 16.08 | 0.00 | 0.00 | 0.00 |
June | 64.77 | 28.20 | 36.56 | 79.99 | 11.35 | 0.00 | 0.00 | 0.00 |
July | 65.46 | 30.21 | 35.26 | 82.54 | 10.08 | 0.00 | 0.00 | 0.00 |
August | 55.18 | 23.79 | 31.39 | 69.55 | 11.98 | 0.00 | 0.00 | 0.00 |
September | 49.22 | 23.26 | 25.96 | 57.10 | 20.44 | 0.00 | 0.00 | 0.00 |
October | 31.37 | 13.10 | 18.26 | 27.17 | 30.42 | 0.00 | 0.00 | 0.00 |
November | 18.51 | 6.01 | 12.49 | 9.62 | 45.03 | 0.00 | 0.00 | 0.00 |
December | 14.33 | 6.16 | 8.18 | 6.43 | 64.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.06 | 17.79 | 23.27 | 41.76 | 32.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.33 | 6.01 | 8.18 | 6.43 | 10.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.46 | 30.21 | 36.56 | 82.54 | 69.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.46 | 553.24 | 255.21 | 729.47 | 816.42 | 0.00 | 0.00 | 0.00 |
February | 866.25 | 585.24 | 281.01 | 811.82 | 672.24 | 0.00 | 0.00 | 0.00 |
March | 753.83 | 396.94 | 356.89 | 741.52 | 486.83 | 0.00 | 0.00 | 0.00 |
April | 679.15 | 317.52 | 361.64 | 741.76 | 361.94 | 0.00 | 0.00 | 0.00 |
May | 562.66 | 152.54 | 410.11 | 654.86 | 222.57 | 0.00 | 0.00 | 0.00 |
June | 546.26 | 111.22 | 435.04 | 698.98 | 154.04 | 0.00 | 0.00 | 0.00 |
July | 578.25 | 145.70 | 432.55 | 766.66 | 137.86 | 0.00 | 0.00 | 0.00 |
August | 651.49 | 233.64 | 417.85 | 873.27 | 169.04 | 0.00 | 0.00 | 0.00 |
September | 789.47 | 415.98 | 373.49 | 985.24 | 283.60 | 0.00 | 0.00 | 0.00 |
October | 824.37 | 517.18 | 307.20 | 900.83 | 416.62 | 0.00 | 0.00 | 0.00 |
November | 621.99 | 389.37 | 232.61 | 581.85 | 570.09 | 0.00 | 0.00 | 0.00 |
December | 663.26 | 502.41 | 160.85 | 632.73 | 777.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 694.45 | 358.80 | 335.65 | 759.57 | 421.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 546.26 | 111.22 | 160.85 | 581.85 | 137.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 866.25 | 585.24 | 435.04 | 985.24 | 816.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.46 | 553.24 | 255.21 | 729.47 | 816.42 | 0.00 | 0.00 | 0.00 |
February | 866.25 | 585.24 | 281.01 | 811.82 | 672.24 | 0.00 | 0.00 | 0.00 |
March | 753.83 | 396.94 | 356.89 | 741.52 | 486.83 | 0.00 | 0.00 | 0.00 |
April | 679.15 | 317.52 | 361.64 | 741.76 | 361.94 | 0.00 | 0.00 | 0.00 |
May | 562.66 | 152.54 | 410.11 | 654.86 | 222.57 | 0.00 | 0.00 | 0.00 |
June | 546.26 | 111.22 | 435.04 | 698.98 | 154.04 | 0.00 | 0.00 | 0.00 |
July | 578.25 | 145.70 | 432.55 | 766.66 | 137.86 | 0.00 | 0.00 | 0.00 |
August | 651.49 | 233.64 | 417.85 | 873.27 | 169.04 | 0.00 | 0.00 | 0.00 |
September | 789.47 | 415.98 | 373.49 | 985.24 | 283.60 | 0.00 | 0.00 | 0.00 |
October | 824.37 | 517.18 | 307.20 | 900.83 | 416.62 | 0.00 | 0.00 | 0.00 |
November | 621.99 | 389.37 | 232.61 | 581.85 | 570.09 | 0.00 | 0.00 | 0.00 |
December | 663.26 | 502.41 | 160.85 | 632.73 | 777.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 694.45 | 358.80 | 335.65 | 759.57 | 421.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 546.26 | 111.22 | 160.85 | 581.85 | 137.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 866.25 | 585.24 | 435.04 | 985.24 | 816.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 808.41 | 553.21 | 255.20 | 729.42 | 816.37 | 0.00 | 0.00 | 0.00 |
February | 866.19 | 585.21 | 280.99 | 811.77 | 672.20 | 0.00 | 0.00 | 0.00 |
March | 753.78 | 396.92 | 356.87 | 741.47 | 486.80 | 0.00 | 0.00 | 0.00 |
April | 679.11 | 317.50 | 361.61 | 741.71 | 361.92 | 0.00 | 0.00 | 0.00 |
May | 562.62 | 152.53 | 410.09 | 654.82 | 222.56 | 0.00 | 0.00 | 0.00 |
June | 546.22 | 111.21 | 435.01 | 698.93 | 154.03 | 0.00 | 0.00 | 0.00 |
July | 578.21 | 145.69 | 432.52 | 766.61 | 137.86 | 0.00 | 0.00 | 0.00 |
August | 651.45 | 233.63 | 417.83 | 873.21 | 169.03 | 0.00 | 0.00 | 0.00 |
September | 789.42 | 415.96 | 373.46 | 985.18 | 283.58 | 0.00 | 0.00 | 0.00 |
October | 824.32 | 517.14 | 307.18 | 900.77 | 416.60 | 0.00 | 0.00 | 0.00 |
November | 621.95 | 389.35 | 232.60 | 581.81 | 570.05 | 0.00 | 0.00 | 0.00 |
December | 663.22 | 502.38 | 160.84 | 632.69 | 777.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 694.40 | 358.77 | 335.63 | 759.53 | 421.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 546.22 | 111.21 | 160.84 | 581.81 | 137.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 866.19 | 585.21 | 435.01 | 985.18 | 816.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 531.52 | 215.06 | 316.46 | 248.57 | 1801.46 | 0.00 | 0.00 | 0.00 |
February | 779.38 | 384.05 | 395.33 | 516.30 | 1451.17 | 0.00 | 0.00 | 0.00 |
March | 930.42 | 346.17 | 584.25 | 720.85 | 953.39 | 0.00 | 0.00 | 0.00 |
April | 1357.20 | 671.11 | 686.09 | 1396.96 | 692.03 | 0.00 | 0.00 | 0.00 |
May | 1361.13 | 543.74 | 817.39 | 1536.36 | 427.39 | 0.00 | 0.00 | 0.00 |
June | 1597.13 | 692.15 | 904.97 | 1985.80 | 308.61 | 0.00 | 0.00 | 0.00 |
July | 1714.83 | 814.57 | 900.26 | 2184.29 | 282.92 | 0.00 | 0.00 | 0.00 |
August | 1499.19 | 688.03 | 811.16 | 1917.10 | 329.78 | 0.00 | 0.00 | 0.00 |
September | 1213.55 | 576.01 | 637.54 | 1415.80 | 540.17 | 0.00 | 0.00 | 0.00 |
October | 845.65 | 375.97 | 469.69 | 777.44 | 802.31 | 0.00 | 0.00 | 0.00 |
November | 506.18 | 187.18 | 319.00 | 310.19 | 1165.72 | 0.00 | 0.00 | 0.00 |
December | 389.28 | 183.51 | 205.77 | 213.40 | 1653.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1061.58 | 473.22 | 588.36 | 1104.81 | 864.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 389.28 | 183.51 | 205.77 | 213.40 | 282.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1714.83 | 814.57 | 904.97 | 2184.29 | 1801.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.02 | 8.50 | 12.51 | 9.83 | 71.23 | 0.00 | 0.00 | 0.00 |
February | 30.82 | 15.19 | 15.63 | 20.41 | 57.38 | 0.00 | 0.00 | 0.00 |
March | 36.79 | 13.69 | 23.10 | 28.50 | 37.70 | 0.00 | 0.00 | 0.00 |
April | 53.66 | 26.54 | 27.13 | 55.23 | 27.36 | 0.00 | 0.00 | 0.00 |
May | 53.82 | 21.50 | 32.32 | 60.75 | 16.90 | 0.00 | 0.00 | 0.00 |
June | 63.15 | 27.37 | 35.78 | 78.52 | 12.20 | 0.00 | 0.00 | 0.00 |
July | 67.80 | 32.21 | 35.60 | 86.36 | 11.19 | 0.00 | 0.00 | 0.00 |
August | 59.28 | 27.20 | 32.07 | 75.80 | 13.04 | 0.00 | 0.00 | 0.00 |
September | 47.98 | 22.77 | 25.21 | 55.98 | 21.36 | 0.00 | 0.00 | 0.00 |
October | 33.44 | 14.87 | 18.57 | 30.74 | 31.72 | 0.00 | 0.00 | 0.00 |
November | 20.01 | 7.40 | 12.61 | 12.26 | 46.09 | 0.00 | 0.00 | 0.00 |
December | 15.39 | 7.26 | 8.14 | 8.44 | 65.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.97 | 18.71 | 23.26 | 43.68 | 34.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.39 | 7.26 | 8.14 | 8.44 | 11.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.80 | 32.21 | 35.78 | 86.36 | 71.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.00 | 0.00 | 390.00 | 1.79 | 3076.18 | 0.00 | 0.00 | 0.00 |
February | 494.45 | 0.00 | 494.45 | 29.14 | 2494.62 | 0.00 | 0.00 | 0.00 |
March | 741.02 | 0.00 | 741.02 | 230.32 | 1612.31 | 0.00 | 0.00 | 0.00 |
April | 855.46 | 4.21 | 851.25 | 470.23 | 1123.93 | 0.00 | 0.00 | 0.00 |
May | 1115.54 | 41.93 | 1073.61 | 962.84 | 657.04 | 0.00 | 0.00 | 0.00 |
June | 1303.81 | 118.34 | 1185.47 | 1459.98 | 453.34 | 0.00 | 0.00 | 0.00 |
July | 1222.77 | 81.79 | 1140.98 | 1432.44 | 393.77 | 0.00 | 0.00 | 0.00 |
August | 1023.82 | 18.14 | 1005.67 | 1190.34 | 465.02 | 0.00 | 0.00 | 0.00 |
September | 784.97 | 0.19 | 784.78 | 713.86 | 813.79 | 0.00 | 0.00 | 0.00 |
October | 583.64 | 0.00 | 583.64 | 261.99 | 1241.57 | 0.00 | 0.00 | 0.00 |
November | 408.26 | 0.00 | 408.26 | 62.51 | 1889.72 | 0.00 | 0.00 | 0.00 |
December | 264.82 | 0.00 | 264.82 | 0.23 | 2735.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 767.15 | 22.14 | 745.01 | 571.21 | 1407.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 264.82 | 0.00 | 264.82 | 0.23 | 393.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1303.81 | 118.34 | 1185.47 | 1459.98 | 3076.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 557.14 | 229.26 | 327.87 | 241.05 | 1852.16 | 0.00 | 0.00 | 0.00 |
February | 738.48 | 324.73 | 413.76 | 420.76 | 1480.53 | 0.00 | 0.00 | 0.00 |
March | 1003.37 | 398.27 | 605.10 | 760.41 | 989.13 | 0.00 | 0.00 | 0.00 |
April | 1232.04 | 539.55 | 692.49 | 1163.31 | 716.92 | 0.00 | 0.00 | 0.00 |
May | 1547.35 | 676.12 | 871.23 | 1703.40 | 438.31 | 0.00 | 0.00 | 0.00 |
June | 1702.82 | 741.55 | 961.27 | 2085.13 | 302.45 | 0.00 | 0.00 | 0.00 |
July | 1721.11 | 794.16 | 926.95 | 2159.21 | 262.58 | 0.00 | 0.00 | 0.00 |
August | 1450.86 | 625.50 | 825.36 | 1822.09 | 307.68 | 0.00 | 0.00 | 0.00 |
September | 1294.04 | 611.50 | 682.54 | 1499.51 | 518.14 | 0.00 | 0.00 | 0.00 |
October | 824.65 | 344.45 | 480.20 | 716.58 | 772.32 | 0.00 | 0.00 | 0.00 |
November | 486.55 | 158.04 | 328.51 | 252.38 | 1168.23 | 0.00 | 0.00 | 0.00 |
December | 376.89 | 161.84 | 215.04 | 166.59 | 1686.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1079.63 | 467.75 | 611.87 | 1086.14 | 871.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.89 | 158.04 | 215.04 | 166.59 | 262.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1721.11 | 794.16 | 961.27 | 2159.21 | 1852.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2425.42 | 1659.77 | 765.65 | 2120.40 | 2526.71 | 0.00 | 0.00 | 0.00 |
February | 2598.79 | 1755.77 | 843.03 | 2363.59 | 2061.62 | 0.00 | 0.00 | 0.00 |
March | 2261.53 | 1190.85 | 1070.68 | 2155.88 | 1513.14 | 0.00 | 0.00 | 0.00 |
April | 2037.49 | 952.57 | 1084.92 | 2166.22 | 1146.85 | 0.00 | 0.00 | 0.00 |
May | 1687.99 | 457.64 | 1230.35 | 1903.02 | 716.17 | 0.00 | 0.00 | 0.00 |
June | 1638.78 | 333.67 | 1305.12 | 2057.65 | 487.13 | 0.00 | 0.00 | 0.00 |
July | 1734.77 | 437.12 | 1297.65 | 2277.02 | 420.97 | 0.00 | 0.00 | 0.00 |
August | 1954.51 | 700.93 | 1253.57 | 2604.30 | 499.16 | 0.00 | 0.00 | 0.00 |
September | 2368.45 | 1247.98 | 1120.47 | 2941.43 | 823.98 | 0.00 | 0.00 | 0.00 |
October | 2473.16 | 1551.56 | 921.60 | 2684.54 | 1197.19 | 0.00 | 0.00 | 0.00 |
November | 1866.00 | 1168.15 | 697.85 | 1720.57 | 1687.98 | 0.00 | 0.00 | 0.00 |
December | 1989.81 | 1507.26 | 482.55 | 1863.42 | 2365.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2083.37 | 1076.41 | 1006.96 | 2237.32 | 1283.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1638.78 | 333.67 | 482.55 | 1720.57 | 420.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2598.79 | 1755.77 | 1305.12 | 2941.43 | 2526.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 552.54 | 223.57 | 328.98 | 250.59 | 1897.09 | 0.00 | 0.00 | 0.00 |
February | 810.21 | 399.25 | 410.96 | 521.94 | 1535.14 | 0.00 | 0.00 | 0.00 |
March | 967.22 | 359.86 | 607.36 | 722.43 | 1022.82 | 0.00 | 0.00 | 0.00 |
April | 1410.89 | 697.66 | 713.23 | 1422.11 | 749.66 | 0.00 | 0.00 | 0.00 |
May | 1414.97 | 565.25 | 849.72 | 1565.98 | 466.09 | 0.00 | 0.00 | 0.00 |
June | 1660.30 | 719.53 | 940.76 | 2046.44 | 327.14 | 0.00 | 0.00 | 0.00 |
July | 1782.65 | 846.79 | 935.87 | 2261.23 | 289.90 | 0.00 | 0.00 | 0.00 |
August | 1558.49 | 715.24 | 843.24 | 1986.82 | 333.69 | 0.00 | 0.00 | 0.00 |
September | 1261.55 | 598.80 | 662.75 | 1470.17 | 544.38 | 0.00 | 0.00 | 0.00 |
October | 879.10 | 390.84 | 488.26 | 807.44 | 809.16 | 0.00 | 0.00 | 0.00 |
November | 526.20 | 194.59 | 331.61 | 320.54 | 1196.58 | 0.00 | 0.00 | 0.00 |
December | 404.68 | 190.77 | 213.91 | 217.42 | 1723.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1103.57 | 491.94 | 611.63 | 1135.78 | 904.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 404.68 | 190.77 | 213.91 | 217.42 | 289.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1782.65 | 846.79 | 940.76 | 2261.23 | 1897.09 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104458E+10 | 0.00 | 0.104458E+10 | 5752779.95 | 0.808379E+10 |
February | 0.119617E+10 | 0.00 | 0.119617E+10 | 80185193.69 | 0.584424E+10 |
March | 0.198476E+10 | 0.00 | 0.198476E+10 | 0.645925E+09 | 0.412944E+10 |
April | 0.221736E+10 | 10924820.31 | 0.220643E+10 | 0.124658E+10 | 0.274688E+10 |
May | 0.298786E+10 | 0.112307E+09 | 0.287555E+10 | 0.260934E+10 | 0.168133E+10 |
June | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.379503E+10 | 0.112841E+10 |
July | 0.327506E+10 | 0.219066E+09 | 0.305600E+10 | 0.383806E+10 | 0.102087E+10 |
August | 0.274219E+10 | 48599256.74 | 0.269359E+10 | 0.319838E+10 | 0.119617E+10 |
September | 0.203465E+10 | 504502.48 | 0.203415E+10 | 0.188533E+10 | 0.198356E+10 |
October | 0.156323E+10 | 0.00 | 0.156323E+10 | 0.768181E+09 | 0.308151E+10 |
November | 0.105822E+10 | 0.00 | 0.105822E+10 | 0.189392E+09 | 0.463891E+10 |
December | 0.709306E+09 | 0.00 | 0.709306E+09 | 1624182.24 | 0.710334E+10 |
Annual Sum or Average | 0.241929E+11 | 0.698132E+09 | 0.234947E+11 | 0.182638E+11 | 0.426385E+11 |
Minimum of Months | 0.709306E+09 | 0.00 | 0.709306E+09 | 1624182.24 | 0.102087E+10 |
Maximum of Months | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.383806E+10 | 0.808379E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149224E+10 | 0.614060E+09 | 0.878177E+09 | 0.653938E+09 | 0.486616E+10 |
February | 0.178654E+10 | 0.785576E+09 | 0.100096E+10 | 0.103497E+10 | 0.346497E+10 |
March | 0.268743E+10 | 0.106672E+10 | 0.162071E+10 | 0.206492E+10 | 0.253476E+10 |
April | 0.319346E+10 | 0.139852E+10 | 0.179494E+10 | 0.303386E+10 | 0.176303E+10 |
May | 0.414442E+10 | 0.181093E+10 | 0.233350E+10 | 0.457392E+10 | 0.112752E+10 |
June | 0.441370E+10 | 0.192210E+10 | 0.249160E+10 | 0.540680E+10 | 0.754564E+09 |
July | 0.460983E+10 | 0.212708E+10 | 0.248275E+10 | 0.577936E+10 | 0.682063E+09 |
August | 0.388600E+10 | 0.167534E+10 | 0.221066E+10 | 0.488252E+10 | 0.794093E+09 |
September | 0.335415E+10 | 0.158501E+10 | 0.176914E+10 | 0.390519E+10 | 0.127270E+10 |
October | 0.220875E+10 | 0.922577E+09 | 0.128617E+10 | 0.197227E+10 | 0.193009E+10 |
November | 0.126114E+10 | 0.409643E+09 | 0.851500E+09 | 0.683961E+09 | 0.287555E+10 |
December | 0.100946E+10 | 0.433485E+09 | 0.575971E+09 | 0.457026E+09 | 0.438012E+10 |
Annual Sum or Average | 0.340471E+11 | 0.147510E+11 | 0.192961E+11 | 0.344487E+11 | 0.264456E+11 |
Minimum of Months | 0.100946E+10 | 0.409643E+09 | 0.575971E+09 | 0.457026E+09 | 0.682063E+09 |
Maximum of Months | 0.460983E+10 | 0.212708E+10 | 0.249160E+10 | 0.577936E+10 | 0.486616E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649625E+10 | 0.444552E+10 | 0.205072E+10 | 0.570788E+10 | 0.660935E+10 |
February | 0.628700E+10 | 0.424755E+10 | 0.203945E+10 | 0.575782E+10 | 0.480532E+10 |
March | 0.605729E+10 | 0.318957E+10 | 0.286772E+10 | 0.581405E+10 | 0.386840E+10 |
April | 0.528118E+10 | 0.246906E+10 | 0.281212E+10 | 0.563810E+10 | 0.280871E+10 |
May | 0.452112E+10 | 0.122574E+10 | 0.329538E+10 | 0.511468E+10 | 0.182908E+10 |
June | 0.424773E+10 | 0.864862E+09 | 0.338287E+10 | 0.533908E+10 | 0.120643E+10 |
July | 0.464640E+10 | 0.117077E+10 | 0.347563E+10 | 0.609603E+10 | 0.108660E+10 |
August | 0.523496E+10 | 0.187738E+10 | 0.335757E+10 | 0.697613E+10 | 0.128129E+10 |
September | 0.613903E+10 | 0.323476E+10 | 0.290426E+10 | 0.764922E+10 | 0.201613E+10 |
October | 0.662412E+10 | 0.415570E+10 | 0.246841E+10 | 0.725855E+10 | 0.298462E+10 |
November | 0.483666E+10 | 0.302784E+10 | 0.180882E+10 | 0.452241E+10 | 0.414111E+10 |
December | 0.532952E+10 | 0.403705E+10 | 0.129247E+10 | 0.502544E+10 | 0.612353E+10 |
Annual Sum or Average | 0.657012E+11 | 0.339458E+11 | 0.317554E+11 | 0.708994E+11 | 0.387606E+11 |
Minimum of Months | 0.424773E+10 | 0.864862E+09 | 0.129247E+10 | 0.452241E+10 | 0.108660E+10 |
Maximum of Months | 0.662412E+10 | 0.444552E+10 | 0.347563E+10 | 0.764922E+10 | 0.660935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147993E+10 | 0.598799E+09 | 0.881133E+09 | 0.675166E+09 | 0.498485E+10 |
February | 0.196005E+10 | 0.965855E+09 | 0.994198E+09 | 0.127332E+10 | 0.359530E+10 |
March | 0.259060E+10 | 0.963846E+09 | 0.162676E+10 | 0.195420E+10 | 0.261883E+10 |
April | 0.365702E+10 | 0.180833E+10 | 0.184869E+10 | 0.369999E+10 | 0.183698E+10 |
May | 0.378985E+10 | 0.151396E+10 | 0.227589E+10 | 0.421010E+10 | 0.119017E+10 |
June | 0.430349E+10 | 0.186503E+10 | 0.243846E+10 | 0.530885E+10 | 0.811436E+09 |
July | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.605531E+10 | 0.749363E+09 |
August | 0.417425E+10 | 0.191571E+10 | 0.225854E+10 | 0.532563E+10 | 0.857219E+09 |
September | 0.326994E+10 | 0.155208E+10 | 0.171786E+10 | 0.383286E+10 | 0.133126E+10 |
October | 0.235459E+10 | 0.104682E+10 | 0.130776E+10 | 0.220365E+10 | 0.201706E+10 |
November | 0.136391E+10 | 0.504373E+09 | 0.859538E+09 | 0.855538E+09 | 0.294362E+10 |
December | 0.108388E+10 | 0.510958E+09 | 0.572924E+09 | 0.589612E+09 | 0.447525E+10 |
Annual Sum or Average | 0.348022E+11 | 0.155138E+11 | 0.192884E+11 | 0.359842E+11 | 0.274113E+11 |
Minimum of Months | 0.108388E+10 | 0.504373E+09 | 0.572924E+09 | 0.589612E+09 | 0.749363E+09 |
Maximum of Months | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.605531E+10 | 0.498485E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348178E+09 | 0.00 | 0.348178E+09 | 2083397.24 | 0.270079E+10 |
February | 0.398703E+09 | 0.00 | 0.398703E+09 | 26986649.08 | 0.196005E+10 |
March | 0.661556E+09 | 0.00 | 0.661556E+09 | 0.231974E+09 | 0.137815E+10 |
April | 0.739084E+09 | 3641434.48 | 0.735443E+09 | 0.447863E+09 | 0.897833E+09 |
May | 0.995906E+09 | 37433802.47 | 0.958472E+09 | 0.916562E+09 | 0.536030E+09 |
June | 0.112644E+10 | 0.102239E+09 | 0.102420E+10 | 0.129304E+10 | 0.369434E+09 |
July | 0.109164E+10 | 73018512.17 | 0.101862E+10 | 0.130057E+10 | 0.337903E+09 |
August | 0.914020E+09 | 16198985.80 | 0.897821E+09 | 0.107417E+10 | 0.408763E+09 |
September | 0.678185E+09 | 168159.54 | 0.678017E+09 | 0.622964E+09 | 0.704455E+09 |
October | 0.521051E+09 | 0.00 | 0.521051E+09 | 0.237087E+09 | 0.111909E+10 |
November | 0.352723E+09 | 0.00 | 0.352723E+09 | 55382308.39 | 0.164189E+10 |
December | 0.236424E+09 | 0.00 | 0.236424E+09 | 254391.26 | 0.242756E+10 |
Annual Sum or Average | 0.806391E+10 | 0.232700E+09 | 0.783121E+10 | 0.620895E+10 | 0.144819E+11 |
Minimum of Months | 0.236424E+09 | 0.00 | 0.236424E+09 | 254391.26 | 0.337903E+09 |
Maximum of Months | 0.112644E+10 | 0.102239E+09 | 0.102420E+10 | 0.130057E+10 | 0.270079E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348191E+09 | 0.00 | 0.348191E+09 | 2082974.38 | 0.270096E+10 |
February | 0.398719E+09 | 0.00 | 0.398719E+09 | 26985594.14 | 0.196018E+10 |
March | 0.661581E+09 | 0.00 | 0.661581E+09 | 0.231975E+09 | 0.137824E+10 |
April | 0.739114E+09 | 3641532.36 | 0.735473E+09 | 0.447877E+09 | 0.897892E+09 |
May | 0.995945E+09 | 37434808.70 | 0.958510E+09 | 0.916591E+09 | 0.536063E+09 |
June | 0.112648E+10 | 0.102242E+09 | 0.102424E+10 | 0.129309E+10 | 0.369456E+09 |
July | 0.109168E+10 | 73020474.93 | 0.101866E+10 | 0.130062E+10 | 0.337922E+09 |
August | 0.914056E+09 | 16199421.24 | 0.897857E+09 | 0.107421E+10 | 0.408786E+09 |
September | 0.678212E+09 | 168164.06 | 0.678044E+09 | 0.622986E+09 | 0.704497E+09 |
October | 0.521072E+09 | 0.00 | 0.521072E+09 | 0.237090E+09 | 0.111916E+10 |
November | 0.352736E+09 | 0.00 | 0.352736E+09 | 55381467.41 | 0.164199E+10 |
December | 0.236433E+09 | 0.00 | 0.236433E+09 | 254340.58 | 0.242771E+10 |
Annual Sum or Average | 0.806422E+10 | 0.232706E+09 | 0.783152E+10 | 0.620915E+10 | 0.144829E+11 |
Minimum of Months | 0.236433E+09 | 0.00 | 0.236433E+09 | 254340.58 | 0.337922E+09 |
Maximum of Months | 0.112648E+10 | 0.102242E+09 | 0.102424E+10 | 0.130062E+10 | 0.270096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.348191E+09 | 0.00 | 0.348191E+09 | 2082974.38 | 0.270096E+10 |
February | 0.398719E+09 | 0.00 | 0.398719E+09 | 26985594.14 | 0.196018E+10 |
March | 0.661581E+09 | 0.00 | 0.661581E+09 | 0.231975E+09 | 0.137824E+10 |
April | 0.739114E+09 | 3641532.36 | 0.735473E+09 | 0.447877E+09 | 0.897892E+09 |
May | 0.995945E+09 | 37434808.70 | 0.958510E+09 | 0.916591E+09 | 0.536063E+09 |
June | 0.112648E+10 | 0.102242E+09 | 0.102424E+10 | 0.129309E+10 | 0.369456E+09 |
July | 0.109168E+10 | 73020474.93 | 0.101866E+10 | 0.130062E+10 | 0.337922E+09 |
August | 0.914056E+09 | 16199421.24 | 0.897857E+09 | 0.107421E+10 | 0.408786E+09 |
September | 0.678212E+09 | 168164.06 | 0.678044E+09 | 0.622986E+09 | 0.704497E+09 |
October | 0.521072E+09 | 0.00 | 0.521072E+09 | 0.237090E+09 | 0.111916E+10 |
November | 0.352736E+09 | 0.00 | 0.352736E+09 | 55381467.41 | 0.164199E+10 |
December | 0.236433E+09 | 0.00 | 0.236433E+09 | 254340.58 | 0.242771E+10 |
Annual Sum or Average | 0.806422E+10 | 0.232706E+09 | 0.783152E+10 | 0.620915E+10 | 0.144829E+11 |
Minimum of Months | 0.236433E+09 | 0.00 | 0.236433E+09 | 254340.58 | 0.337922E+09 |
Maximum of Months | 0.112648E+10 | 0.102242E+09 | 0.102424E+10 | 0.130062E+10 | 0.270096E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.143546E+10 | 0.590693E+09 | 0.844764E+09 | 0.637947E+09 | 0.471607E+10 |
February | 0.171856E+10 | 0.755682E+09 | 0.962876E+09 | 0.100652E+10 | 0.338938E+10 |
March | 0.258517E+10 | 0.102613E+10 | 0.155905E+10 | 0.202638E+10 | 0.247282E+10 |
April | 0.307195E+10 | 0.134530E+10 | 0.172665E+10 | 0.297944E+10 | 0.170555E+10 |
May | 0.398673E+10 | 0.174201E+10 | 0.224471E+10 | 0.446384E+10 | 0.108924E+10 |
June | 0.424576E+10 | 0.184896E+10 | 0.239680E+10 | 0.524389E+10 | 0.744079E+09 |
July | 0.443442E+10 | 0.204614E+10 | 0.238829E+10 | 0.559106E+10 | 0.682846E+09 |
August | 0.373813E+10 | 0.161159E+10 | 0.212655E+10 | 0.471111E+10 | 0.811277E+09 |
September | 0.322653E+10 | 0.152470E+10 | 0.170183E+10 | 0.374320E+10 | 0.134017E+10 |
October | 0.212470E+10 | 0.887469E+09 | 0.123723E+10 | 0.184035E+10 | 0.206089E+10 |
November | 0.121316E+10 | 0.394054E+09 | 0.819102E+09 | 0.630530E+09 | 0.295226E+10 |
December | 0.971045E+09 | 0.416989E+09 | 0.554056E+09 | 0.435893E+09 | 0.433640E+10 |
Annual Sum or Average | 0.327516E+11 | 0.141897E+11 | 0.185619E+11 | 0.333102E+11 | 0.263010E+11 |
Minimum of Months | 0.971045E+09 | 0.394054E+09 | 0.554056E+09 | 0.435893E+09 | 0.682846E+09 |
Maximum of Months | 0.443442E+10 | 0.204614E+10 | 0.239680E+10 | 0.559106E+10 | 0.471607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56756641.16 | 23355452.37 | 33401188.79 | 25223865.42 | 0.186469E+09 |
February | 67950228.96 | 29878973.09 | 38071255.87 | 39796878.43 | 0.134013E+09 |
March | 0.102215E+09 | 40572207.13 | 61643250.83 | 80121170.61 | 97773249.22 |
April | 0.121462E+09 | 53191929.36 | 68270153.47 | 0.117804E+09 | 67436089.88 |
May | 0.157632E+09 | 68877591.03 | 88753975.11 | 0.176496E+09 | 43067472.24 |
June | 0.167874E+09 | 73106021.70 | 94767490.68 | 0.207339E+09 | 29420208.32 |
July | 0.175333E+09 | 80902339.86 | 94430689.23 | 0.221066E+09 | 26999114.90 |
August | 0.147802E+09 | 63720642.10 | 84081763.75 | 0.186273E+09 | 32077181.59 |
September | 0.127574E+09 | 60285129.18 | 67288816.16 | 0.148003E+09 | 52989211.75 |
October | 84008885.11 | 35089740.27 | 48919144.83 | 72765947.73 | 81485702.85 |
November | 47967101.97 | 15580550.31 | 32386551.65 | 24930577.23 | 0.116730E+09 |
December | 38394264.64 | 16487372.76 | 21906891.88 | 17234810.56 | 0.171457E+09 |
Annual Sum or Average | 0.129497E+10 | 0.561048E+09 | 0.733921E+09 | 0.131705E+10 | 0.103992E+10 |
Minimum of Months | 38394264.64 | 15580550.31 | 21906891.88 | 17234810.56 | 26999114.90 |
Maximum of Months | 0.175333E+09 | 80902339.86 | 94767490.68 | 0.221066E+09 | 0.186469E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216538E+10 | 0.148181E+10 | 0.683565E+09 | 0.195380E+10 | 0.218671E+10 |
February | 0.209563E+10 | 0.141582E+10 | 0.679809E+09 | 0.196396E+10 | 0.162628E+10 |
March | 0.201906E+10 | 0.106317E+10 | 0.955895E+09 | 0.198608E+10 | 0.130394E+10 |
April | 0.176037E+10 | 0.823002E+09 | 0.937365E+09 | 0.192263E+10 | 0.938145E+09 |
May | 0.150702E+10 | 0.408571E+09 | 0.109845E+10 | 0.175397E+10 | 0.596137E+09 |
June | 0.141589E+10 | 0.288281E+09 | 0.112761E+10 | 0.181175E+10 | 0.399272E+09 |
July | 0.154878E+10 | 0.390249E+09 | 0.115853E+10 | 0.205341E+10 | 0.369256E+09 |
August | 0.174496E+10 | 0.625781E+09 | 0.111918E+10 | 0.233895E+10 | 0.452757E+09 |
September | 0.204631E+10 | 0.107823E+10 | 0.968077E+09 | 0.255375E+10 | 0.735092E+09 |
October | 0.220800E+10 | 0.138521E+10 | 0.822794E+09 | 0.241278E+10 | 0.111588E+10 |
November | 0.161219E+10 | 0.100926E+10 | 0.602931E+09 | 0.150815E+10 | 0.147766E+10 |
December | 0.177647E+10 | 0.134565E+10 | 0.430818E+09 | 0.169472E+10 | 0.208232E+10 |
Annual Sum or Average | 0.219001E+11 | 0.113150E+11 | 0.105850E+11 | 0.239539E+11 | 0.132835E+11 |
Minimum of Months | 0.141589E+10 | 0.288281E+09 | 0.430818E+09 | 0.150815E+10 | 0.369256E+09 |
Maximum of Months | 0.220800E+10 | 0.148181E+10 | 0.115853E+10 | 0.255375E+10 | 0.218671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216538E+10 | 0.148181E+10 | 0.683565E+09 | 0.195380E+10 | 0.218671E+10 |
February | 0.209563E+10 | 0.141582E+10 | 0.679809E+09 | 0.196396E+10 | 0.162628E+10 |
March | 0.201906E+10 | 0.106317E+10 | 0.955895E+09 | 0.198608E+10 | 0.130394E+10 |
April | 0.176037E+10 | 0.823002E+09 | 0.937365E+09 | 0.192263E+10 | 0.938145E+09 |
May | 0.150702E+10 | 0.408571E+09 | 0.109845E+10 | 0.175397E+10 | 0.596137E+09 |
June | 0.141589E+10 | 0.288281E+09 | 0.112761E+10 | 0.181175E+10 | 0.399272E+09 |
July | 0.154878E+10 | 0.390249E+09 | 0.115853E+10 | 0.205341E+10 | 0.369256E+09 |
August | 0.174496E+10 | 0.625781E+09 | 0.111918E+10 | 0.233895E+10 | 0.452757E+09 |
September | 0.204631E+10 | 0.107823E+10 | 0.968077E+09 | 0.255375E+10 | 0.735092E+09 |
October | 0.220800E+10 | 0.138521E+10 | 0.822794E+09 | 0.241278E+10 | 0.111588E+10 |
November | 0.161219E+10 | 0.100926E+10 | 0.602931E+09 | 0.150815E+10 | 0.147766E+10 |
December | 0.177647E+10 | 0.134565E+10 | 0.430818E+09 | 0.169472E+10 | 0.208232E+10 |
Annual Sum or Average | 0.219001E+11 | 0.113150E+11 | 0.105850E+11 | 0.239539E+11 | 0.132835E+11 |
Minimum of Months | 0.141589E+10 | 0.288281E+09 | 0.430818E+09 | 0.150815E+10 | 0.369256E+09 |
Maximum of Months | 0.220800E+10 | 0.148181E+10 | 0.115853E+10 | 0.255375E+10 | 0.218671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216524E+10 | 0.148172E+10 | 0.683521E+09 | 0.195368E+10 | 0.218657E+10 |
February | 0.209550E+10 | 0.141573E+10 | 0.679766E+09 | 0.196383E+10 | 0.162618E+10 |
March | 0.201894E+10 | 0.106310E+10 | 0.955835E+09 | 0.198595E+10 | 0.130385E+10 |
April | 0.176026E+10 | 0.822950E+09 | 0.937306E+09 | 0.192251E+10 | 0.938086E+09 |
May | 0.150693E+10 | 0.408545E+09 | 0.109838E+10 | 0.175386E+10 | 0.596100E+09 |
June | 0.141580E+10 | 0.288263E+09 | 0.112754E+10 | 0.181163E+10 | 0.399247E+09 |
July | 0.154869E+10 | 0.390225E+09 | 0.115846E+10 | 0.205328E+10 | 0.369232E+09 |
August | 0.174485E+10 | 0.625741E+09 | 0.111911E+10 | 0.233881E+10 | 0.452728E+09 |
September | 0.204618E+10 | 0.107816E+10 | 0.968016E+09 | 0.255359E+10 | 0.735045E+09 |
October | 0.220786E+10 | 0.138512E+10 | 0.822742E+09 | 0.241262E+10 | 0.111581E+10 |
November | 0.161209E+10 | 0.100920E+10 | 0.602893E+09 | 0.150805E+10 | 0.147757E+10 |
December | 0.177636E+10 | 0.134557E+10 | 0.430791E+09 | 0.169461E+10 | 0.208219E+10 |
Annual Sum or Average | 0.218987E+11 | 0.113143E+11 | 0.105844E+11 | 0.239524E+11 | 0.132826E+11 |
Minimum of Months | 0.141580E+10 | 0.288263E+09 | 0.430791E+09 | 0.150805E+10 | 0.369232E+09 |
Maximum of Months | 0.220786E+10 | 0.148172E+10 | 0.115846E+10 | 0.255359E+10 | 0.218657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142362E+10 | 0.576014E+09 | 0.847610E+09 | 0.665765E+09 | 0.482502E+10 |
February | 0.188548E+10 | 0.929104E+09 | 0.956373E+09 | 0.124903E+10 | 0.351068E+10 |
March | 0.249204E+10 | 0.927171E+09 | 0.156486E+10 | 0.193073E+10 | 0.255356E+10 |
April | 0.351788E+10 | 0.173952E+10 | 0.177835E+10 | 0.362092E+10 | 0.179375E+10 |
May | 0.364566E+10 | 0.145635E+10 | 0.218931E+10 | 0.411498E+10 | 0.114472E+10 |
June | 0.413975E+10 | 0.179406E+10 | 0.234569E+10 | 0.514720E+10 | 0.799927E+09 |
July | 0.459300E+10 | 0.218174E+10 | 0.241126E+10 | 0.585040E+10 | 0.757767E+09 |
August | 0.401543E+10 | 0.184282E+10 | 0.217262E+10 | 0.513475E+10 | 0.883283E+09 |
September | 0.314553E+10 | 0.149303E+10 | 0.165250E+10 | 0.366976E+10 | 0.140012E+10 |
October | 0.226500E+10 | 0.100699E+10 | 0.125801E+10 | 0.208230E+10 | 0.214890E+10 |
November | 0.131202E+10 | 0.485182E+09 | 0.826836E+09 | 0.804019E+09 | 0.302154E+10 |
December | 0.104264E+10 | 0.491515E+09 | 0.551127E+09 | 0.571572E+09 | 0.442807E+10 |
Annual Sum or Average | 0.334780E+11 | 0.149235E+11 | 0.185545E+11 | 0.348414E+11 | 0.272673E+11 |
Minimum of Months | 0.104264E+10 | 0.485182E+09 | 0.551127E+09 | 0.571572E+09 | 0.757767E+09 |
Maximum of Months | 0.459300E+10 | 0.218174E+10 | 0.241126E+10 | 0.585040E+10 | 0.482502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56288645.62 | 22774998.79 | 33513646.83 | 26323615.98 | 0.190777E+09 |
February | 74549841.78 | 36735805.67 | 37814036.11 | 49385165.47 | 0.138809E+09 |
March | 98532578.60 | 36659379.69 | 61873198.91 | 76339175.07 | 0.100965E+09 |
April | 0.139093E+09 | 68778927.37 | 70314300.83 | 0.143167E+09 | 70923303.64 |
May | 0.144146E+09 | 57582503.70 | 86563075.68 | 0.162702E+09 | 45261209.78 |
June | 0.163682E+09 | 70935327.01 | 92746286.79 | 0.203515E+09 | 31628370.25 |
July | 0.181602E+09 | 86263690.25 | 95338741.58 | 0.231319E+09 | 29961390.44 |
August | 0.158766E+09 | 72863059.01 | 85903142.39 | 0.203023E+09 | 34924196.48 |
September | 0.124371E+09 | 59032682.10 | 65338373.22 | 0.145098E+09 | 55359562.21 |
October | 89555749.66 | 39815349.08 | 49740400.58 | 82332103.39 | 84965696.34 |
November | 51875834.80 | 19183582.39 | 32692252.41 | 31790046.12 | 0.119469E+09 |
December | 41225041.30 | 19434016.87 | 21791024.43 | 22599344.37 | 0.175082E+09 |
Annual Sum or Average | 0.132369E+10 | 0.590059E+09 | 0.733628E+09 | 0.137759E+10 | 0.107813E+10 |
Minimum of Months | 41225041.30 | 19183582.39 | 21791024.43 | 22599344.37 | 29961390.44 |
Maximum of Months | 0.181602E+09 | 86263690.25 | 95338741.58 | 0.231319E+09 | 0.190777E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104458E+10 | 0.00 | 0.104458E+10 | 4785580.32 | 0.823923E+10 |
February | 0.119617E+10 | 0.00 | 0.119617E+10 | 70497799.37 | 0.603497E+10 |
March | 0.198476E+10 | 0.00 | 0.198476E+10 | 0.616899E+09 | 0.431841E+10 |
April | 0.221736E+10 | 10924820.31 | 0.220643E+10 | 0.121884E+10 | 0.291324E+10 |
May | 0.298786E+10 | 0.112307E+09 | 0.287555E+10 | 0.257886E+10 | 0.175981E+10 |
June | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.378428E+10 | 0.117505E+10 |
July | 0.327506E+10 | 0.219066E+09 | 0.305600E+10 | 0.383664E+10 | 0.105468E+10 |
August | 0.274219E+10 | 48599256.74 | 0.269359E+10 | 0.318820E+10 | 0.124550E+10 |
September | 0.203465E+10 | 504502.48 | 0.203415E+10 | 0.185032E+10 | 0.210935E+10 |
October | 0.156323E+10 | 0.00 | 0.156323E+10 | 0.701719E+09 | 0.332543E+10 |
November | 0.105822E+10 | 0.00 | 0.105822E+10 | 0.162038E+09 | 0.489816E+10 |
December | 0.709306E+09 | 0.00 | 0.709306E+09 | 605769.29 | 0.732668E+10 |
Annual Sum or Average | 0.241929E+11 | 0.698132E+09 | 0.234947E+11 | 0.180137E+11 | 0.444005E+11 |
Minimum of Months | 0.709306E+09 | 0.00 | 0.709306E+09 | 605769.29 | 0.105468E+10 |
Maximum of Months | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.383664E+10 | 0.823923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149224E+10 | 0.614060E+09 | 0.878177E+09 | 0.645632E+09 | 0.496082E+10 |
February | 0.178654E+10 | 0.785576E+09 | 0.100096E+10 | 0.101790E+10 | 0.358171E+10 |
March | 0.268743E+10 | 0.106672E+10 | 0.162071E+10 | 0.203669E+10 | 0.264930E+10 |
April | 0.319346E+10 | 0.139852E+10 | 0.179494E+10 | 0.301530E+10 | 0.185824E+10 |
May | 0.414442E+10 | 0.181093E+10 | 0.233350E+10 | 0.456239E+10 | 0.117397E+10 |
June | 0.441370E+10 | 0.192210E+10 | 0.249160E+10 | 0.540467E+10 | 0.783945E+09 |
July | 0.460983E+10 | 0.212708E+10 | 0.248275E+10 | 0.578323E+10 | 0.703296E+09 |
August | 0.388600E+10 | 0.167534E+10 | 0.221066E+10 | 0.488028E+10 | 0.824082E+09 |
September | 0.335415E+10 | 0.158501E+10 | 0.176914E+10 | 0.388673E+10 | 0.134302E+10 |
October | 0.220875E+10 | 0.922577E+09 | 0.128617E+10 | 0.191929E+10 | 0.206857E+10 |
November | 0.126114E+10 | 0.409643E+09 | 0.851500E+09 | 0.654167E+09 | 0.302805E+10 |
December | 0.100946E+10 | 0.433485E+09 | 0.575971E+09 | 0.446197E+09 | 0.451762E+10 |
Annual Sum or Average | 0.340471E+11 | 0.147510E+11 | 0.192961E+11 | 0.342525E+11 | 0.274926E+11 |
Minimum of Months | 0.100946E+10 | 0.409643E+09 | 0.575971E+09 | 0.446197E+09 | 0.703296E+09 |
Maximum of Months | 0.460983E+10 | 0.212708E+10 | 0.249160E+10 | 0.578323E+10 | 0.496082E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.649625E+10 | 0.444552E+10 | 0.205072E+10 | 0.567928E+10 | 0.676754E+10 |
February | 0.628700E+10 | 0.424755E+10 | 0.203945E+10 | 0.571800E+10 | 0.498747E+10 |
March | 0.605729E+10 | 0.318957E+10 | 0.286772E+10 | 0.577432E+10 | 0.405280E+10 |
April | 0.528118E+10 | 0.246906E+10 | 0.281212E+10 | 0.561484E+10 | 0.297264E+10 |
May | 0.452112E+10 | 0.122574E+10 | 0.329538E+10 | 0.509706E+10 | 0.191820E+10 |
June | 0.424773E+10 | 0.864862E+09 | 0.338287E+10 | 0.533343E+10 | 0.126265E+10 |
July | 0.464640E+10 | 0.117077E+10 | 0.347563E+10 | 0.609876E+10 | 0.112754E+10 |
August | 0.523496E+10 | 0.187738E+10 | 0.335757E+10 | 0.697536E+10 | 0.133695E+10 |
September | 0.613903E+10 | 0.323476E+10 | 0.290426E+10 | 0.762418E+10 | 0.213577E+10 |
October | 0.662412E+10 | 0.415570E+10 | 0.246841E+10 | 0.719028E+10 | 0.320656E+10 |
November | 0.483666E+10 | 0.302784E+10 | 0.180882E+10 | 0.445971E+10 | 0.437525E+10 |
December | 0.532952E+10 | 0.403705E+10 | 0.129247E+10 | 0.499097E+10 | 0.633525E+10 |
Annual Sum or Average | 0.657012E+11 | 0.339458E+11 | 0.317554E+11 | 0.705562E+11 | 0.404786E+11 |
Minimum of Months | 0.424773E+10 | 0.864862E+09 | 0.129247E+10 | 0.445971E+10 | 0.112754E+10 |
Maximum of Months | 0.662412E+10 | 0.444552E+10 | 0.347563E+10 | 0.762418E+10 | 0.676754E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147993E+10 | 0.598799E+09 | 0.881133E+09 | 0.671180E+09 | 0.508116E+10 |
February | 0.196005E+10 | 0.965855E+09 | 0.994198E+09 | 0.126268E+10 | 0.371382E+10 |
March | 0.259060E+10 | 0.963846E+09 | 0.162676E+10 | 0.193495E+10 | 0.273953E+10 |
April | 0.365702E+10 | 0.180833E+10 | 0.184869E+10 | 0.368610E+10 | 0.194313E+10 |
May | 0.378985E+10 | 0.151396E+10 | 0.227589E+10 | 0.419432E+10 | 0.124839E+10 |
June | 0.430349E+10 | 0.186503E+10 | 0.243846E+10 | 0.530437E+10 | 0.847959E+09 |
July | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.605648E+10 | 0.776479E+09 |
August | 0.417425E+10 | 0.191571E+10 | 0.225854E+10 | 0.532149E+10 | 0.893767E+09 |
September | 0.326994E+10 | 0.155208E+10 | 0.171786E+10 | 0.381069E+10 | 0.141102E+10 |
October | 0.235459E+10 | 0.104682E+10 | 0.130776E+10 | 0.216265E+10 | 0.216726E+10 |
November | 0.136391E+10 | 0.504373E+09 | 0.859538E+09 | 0.830839E+09 | 0.310153E+10 |
December | 0.108388E+10 | 0.510958E+09 | 0.572924E+09 | 0.582346E+09 | 0.461525E+10 |
Annual Sum or Average | 0.348022E+11 | 0.155138E+11 | 0.192884E+11 | 0.358181E+11 | 0.285393E+11 |
Minimum of Months | 0.108388E+10 | 0.504373E+09 | 0.572924E+09 | 0.582346E+09 | 0.776479E+09 |
Maximum of Months | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.605648E+10 | 0.508116E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.15 | 3018.14 | 390.00 | 0.00 | 390.00 | 0.00 | 0.00 |
February | 33.15 | 2415.77 | 494.45 | 0.00 | 494.45 | 0.00 | 0.00 |
March | 241.16 | 1541.76 | 741.02 | 0.00 | 741.02 | 0.00 | 0.00 |
April | 480.93 | 1059.75 | 855.46 | 4.21 | 851.25 | 0.00 | 0.00 |
May | 974.22 | 627.74 | 1115.54 | 41.93 | 1073.61 | 0.00 | 0.00 |
June | 1464.13 | 435.34 | 1303.81 | 118.34 | 1185.47 | 0.00 | 0.00 |
July | 1432.97 | 381.15 | 1222.77 | 81.79 | 1140.98 | 0.00 | 0.00 |
August | 1194.14 | 446.60 | 1023.82 | 18.14 | 1005.67 | 0.00 | 0.00 |
September | 727.37 | 765.26 | 784.97 | 0.19 | 784.78 | 0.00 | 0.00 |
October | 286.81 | 1150.50 | 583.64 | 0.00 | 583.64 | 0.00 | 0.00 |
November | 73.07 | 1789.70 | 408.26 | 0.00 | 408.26 | 0.00 | 0.00 |
December | 0.61 | 2652.08 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Annual Sum or Average | 579.14 | 1352.06 | 767.15 | 22.14 | 745.01 | 0.00 | 0.00 |
Minimum of Months | 0.61 | 381.15 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Maximum of Months | 1464.13 | 3018.14 | 1303.81 | 118.34 | 1185.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.15 | 1816.82 | 557.14 | 229.26 | 327.87 | 0.00 | 0.00 |
February | 427.81 | 1432.28 | 738.48 | 324.73 | 413.76 | 0.00 | 0.00 |
March | 770.95 | 946.37 | 1003.37 | 398.27 | 605.10 | 0.00 | 0.00 |
April | 1170.47 | 680.18 | 1232.04 | 539.55 | 692.49 | 0.00 | 0.00 |
May | 1707.70 | 420.97 | 1547.35 | 676.12 | 871.23 | 0.00 | 0.00 |
June | 2085.96 | 291.11 | 1702.82 | 741.55 | 961.27 | 0.00 | 0.00 |
July | 2157.77 | 254.65 | 1721.11 | 794.16 | 926.95 | 0.00 | 0.00 |
August | 1822.92 | 296.48 | 1450.86 | 625.50 | 825.36 | 0.00 | 0.00 |
September | 1506.63 | 491.01 | 1294.04 | 611.50 | 682.54 | 0.00 | 0.00 |
October | 736.36 | 720.61 | 824.65 | 344.45 | 480.20 | 0.00 | 0.00 |
November | 263.87 | 1109.40 | 486.55 | 158.04 | 328.51 | 0.00 | 0.00 |
December | 170.63 | 1635.35 | 376.89 | 161.84 | 215.04 | 0.00 | 0.00 |
Annual Sum or Average | 1092.36 | 838.59 | 1079.63 | 467.75 | 611.87 | 0.00 | 0.00 |
Minimum of Months | 170.63 | 254.65 | 376.89 | 158.04 | 215.04 | 0.00 | 0.00 |
Maximum of Months | 2157.77 | 1816.82 | 1721.11 | 794.16 | 961.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2131.08 | 2467.65 | 2425.42 | 1659.77 | 765.65 | 0.00 | 0.00 |
February | 2380.05 | 1986.33 | 2598.79 | 1755.77 | 843.03 | 0.00 | 0.00 |
March | 2170.72 | 1444.29 | 2261.53 | 1190.85 | 1070.68 | 0.00 | 0.00 |
April | 2175.19 | 1083.61 | 2037.49 | 952.57 | 1084.92 | 0.00 | 0.00 |
May | 1909.60 | 682.90 | 1687.99 | 457.64 | 1230.35 | 0.00 | 0.00 |
June | 2059.83 | 465.45 | 1638.78 | 333.67 | 1305.12 | 0.00 | 0.00 |
July | 2276.00 | 405.69 | 1734.77 | 437.12 | 1297.65 | 0.00 | 0.00 |
August | 2604.59 | 478.38 | 1954.51 | 700.93 | 1253.57 | 0.00 | 0.00 |
September | 2951.09 | 777.83 | 2368.45 | 1247.98 | 1120.47 | 0.00 | 0.00 |
October | 2710.03 | 1114.33 | 2473.16 | 1551.56 | 921.60 | 0.00 | 0.00 |
November | 1744.76 | 1597.65 | 1866.00 | 1168.15 | 697.85 | 0.00 | 0.00 |
December | 1876.29 | 2286.26 | 1989.81 | 1507.26 | 482.55 | 0.00 | 0.00 |
Annual Sum or Average | 2248.21 | 1229.09 | 2083.37 | 1076.41 | 1006.96 | 0.00 | 0.00 |
Minimum of Months | 1744.76 | 405.69 | 1638.78 | 333.67 | 482.55 | 0.00 | 0.00 |
Maximum of Months | 2951.09 | 2467.65 | 2598.79 | 1755.77 | 1305.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 252.08 | 1861.13 | 552.54 | 223.57 | 328.98 | 0.00 | 0.00 |
February | 526.34 | 1486.15 | 810.21 | 399.25 | 410.96 | 0.00 | 0.00 |
March | 729.61 | 977.76 | 967.22 | 359.86 | 607.36 | 0.00 | 0.00 |
April | 1427.47 | 708.71 | 1410.89 | 697.66 | 713.23 | 0.00 | 0.00 |
May | 1571.87 | 444.36 | 1414.97 | 565.25 | 849.72 | 0.00 | 0.00 |
June | 2048.17 | 313.05 | 1660.30 | 719.53 | 940.76 | 0.00 | 0.00 |
July | 2260.79 | 279.78 | 1782.65 | 846.79 | 935.87 | 0.00 | 0.00 |
August | 1988.36 | 320.05 | 1558.49 | 715.24 | 843.24 | 0.00 | 0.00 |
September | 1478.73 | 513.60 | 1261.55 | 598.80 | 662.75 | 0.00 | 0.00 |
October | 822.75 | 753.08 | 879.10 | 390.84 | 488.26 | 0.00 | 0.00 |
November | 330.07 | 1135.66 | 526.20 | 194.59 | 331.61 | 0.00 | 0.00 |
December | 220.14 | 1670.87 | 404.68 | 190.77 | 213.91 | 0.00 | 0.00 |
Annual Sum or Average | 1141.05 | 869.21 | 1103.57 | 491.94 | 611.63 | 0.00 | 0.00 |
Minimum of Months | 220.14 | 279.78 | 404.68 | 190.77 | 213.91 | 0.00 | 0.00 |
Maximum of Months | 2260.79 | 1861.13 | 1782.65 | 846.79 | 940.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.33 | 3025.21 | 389.99 | 0.00 | 389.99 | 0.00 | 0.00 |
February | 33.46 | 2430.72 | 494.44 | 0.00 | 494.44 | 0.00 | 0.00 |
March | 259.83 | 1543.69 | 741.01 | 0.00 | 741.01 | 0.00 | 0.00 |
April | 518.37 | 1039.20 | 855.44 | 4.21 | 851.23 | 0.00 | 0.00 |
May | 1026.64 | 600.42 | 1115.52 | 41.93 | 1073.59 | 0.00 | 0.00 |
June | 1496.62 | 427.60 | 1303.78 | 118.33 | 1185.45 | 0.00 | 0.00 |
July | 1456.77 | 378.49 | 1222.74 | 81.79 | 1140.96 | 0.00 | 0.00 |
August | 1203.18 | 457.86 | 1023.79 | 18.14 | 1005.65 | 0.00 | 0.00 |
September | 721.04 | 815.37 | 784.96 | 0.19 | 784.76 | 0.00 | 0.00 |
October | 265.56 | 1253.52 | 583.63 | 0.00 | 583.63 | 0.00 | 0.00 |
November | 64.10 | 1900.41 | 408.25 | 0.00 | 408.25 | 0.00 | 0.00 |
December | 0.28 | 2719.15 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Annual Sum or Average | 590.67 | 1377.72 | 767.13 | 22.14 | 745.00 | 0.00 | 0.00 |
Minimum of Months | 0.28 | 378.49 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Maximum of Months | 1496.62 | 3025.21 | 1303.78 | 118.33 | 1185.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 247.60 | 1830.40 | 557.13 | 229.26 | 327.87 | 0.00 | 0.00 |
February | 432.51 | 1456.43 | 738.47 | 324.72 | 413.75 | 0.00 | 0.00 |
March | 786.48 | 959.75 | 1003.36 | 398.26 | 605.10 | 0.00 | 0.00 |
April | 1194.92 | 684.02 | 1232.03 | 539.54 | 692.48 | 0.00 | 0.00 |
May | 1732.50 | 422.75 | 1547.33 | 676.11 | 871.22 | 0.00 | 0.00 |
June | 2103.10 | 298.42 | 1702.79 | 741.54 | 961.25 | 0.00 | 0.00 |
July | 2170.00 | 265.03 | 1721.09 | 794.14 | 926.94 | 0.00 | 0.00 |
August | 1828.47 | 314.87 | 1450.84 | 625.49 | 825.35 | 0.00 | 0.00 |
September | 1501.23 | 537.49 | 1294.02 | 611.49 | 682.53 | 0.00 | 0.00 |
October | 714.28 | 799.87 | 824.64 | 344.44 | 480.19 | 0.00 | 0.00 |
November | 252.88 | 1184.02 | 486.54 | 158.04 | 328.51 | 0.00 | 0.00 |
December | 169.18 | 1683.04 | 376.88 | 161.84 | 215.04 | 0.00 | 0.00 |
Annual Sum or Average | 1098.02 | 866.97 | 1079.61 | 467.74 | 611.87 | 0.00 | 0.00 |
Minimum of Months | 169.18 | 265.03 | 376.88 | 158.04 | 215.04 | 0.00 | 0.00 |
Maximum of Months | 2170.00 | 1830.40 | 1721.09 | 794.14 | 961.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2188.35 | 2449.22 | 2425.32 | 1659.70 | 765.63 | 0.00 | 0.00 |
February | 2435.41 | 2016.68 | 2598.69 | 1755.69 | 843.00 | 0.00 | 0.00 |
March | 2224.50 | 1460.47 | 2261.45 | 1190.80 | 1070.65 | 0.00 | 0.00 |
April | 2225.22 | 1085.79 | 2037.42 | 952.53 | 1084.89 | 0.00 | 0.00 |
May | 1964.53 | 667.70 | 1687.94 | 457.62 | 1230.32 | 0.00 | 0.00 |
June | 2096.88 | 462.11 | 1638.73 | 333.65 | 1305.08 | 0.00 | 0.00 |
July | 2299.92 | 413.58 | 1734.71 | 437.10 | 1297.61 | 0.00 | 0.00 |
August | 2619.74 | 507.11 | 1954.44 | 700.90 | 1253.54 | 0.00 | 0.00 |
September | 2955.67 | 850.78 | 2368.36 | 1247.93 | 1120.44 | 0.00 | 0.00 |
October | 2702.43 | 1249.84 | 2473.07 | 1551.50 | 921.57 | 0.00 | 0.00 |
November | 1745.50 | 1710.22 | 1865.92 | 1168.10 | 697.82 | 0.00 | 0.00 |
December | 1898.16 | 2332.30 | 1989.73 | 1507.20 | 482.54 | 0.00 | 0.00 |
Annual Sum or Average | 2278.68 | 1263.62 | 2083.30 | 1076.37 | 1006.93 | 0.00 | 0.00 |
Minimum of Months | 1745.50 | 413.58 | 1638.73 | 333.65 | 482.54 | 0.00 | 0.00 |
Maximum of Months | 2955.67 | 2449.22 | 2598.69 | 1755.69 | 1305.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.40 | 1872.68 | 552.54 | 223.56 | 328.97 | 0.00 | 0.00 |
February | 536.71 | 1508.55 | 810.20 | 399.24 | 410.96 | 0.00 | 0.00 |
March | 749.36 | 991.09 | 967.21 | 359.85 | 607.35 | 0.00 | 0.00 |
April | 1452.19 | 719.40 | 1410.87 | 697.65 | 713.22 | 0.00 | 0.00 |
May | 1597.10 | 444.29 | 1414.95 | 565.24 | 849.71 | 0.00 | 0.00 |
June | 2064.32 | 320.82 | 1660.28 | 719.52 | 940.75 | 0.00 | 0.00 |
July | 2270.65 | 294.10 | 1782.63 | 846.77 | 935.86 | 0.00 | 0.00 |
August | 1992.90 | 342.82 | 1558.47 | 715.23 | 843.24 | 0.00 | 0.00 |
September | 1471.78 | 561.53 | 1261.54 | 598.79 | 662.75 | 0.00 | 0.00 |
October | 808.18 | 834.03 | 879.09 | 390.83 | 488.26 | 0.00 | 0.00 |
November | 322.46 | 1211.81 | 526.19 | 194.59 | 331.61 | 0.00 | 0.00 |
December | 221.84 | 1718.62 | 404.67 | 190.77 | 213.90 | 0.00 | 0.00 |
Annual Sum or Average | 1148.50 | 898.83 | 1103.56 | 491.93 | 611.62 | 0.00 | 0.00 |
Minimum of Months | 221.84 | 294.10 | 404.67 | 190.77 | 213.90 | 0.00 | 0.00 |
Maximum of Months | 2270.65 | 1872.68 | 1782.63 | 846.77 | 940.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.79 | 3076.18 | 390.00 | 0.00 | 390.00 | 0.00 | 0.00 |
February | 29.14 | 2494.62 | 494.45 | 0.00 | 494.45 | 0.00 | 0.00 |
March | 230.32 | 1612.31 | 741.02 | 0.00 | 741.02 | 0.00 | 0.00 |
April | 470.23 | 1123.93 | 855.46 | 4.21 | 851.25 | 0.00 | 0.00 |
May | 962.84 | 657.04 | 1115.54 | 41.93 | 1073.61 | 0.00 | 0.00 |
June | 1459.98 | 453.34 | 1303.81 | 118.34 | 1185.47 | 0.00 | 0.00 |
July | 1432.44 | 393.77 | 1222.77 | 81.79 | 1140.98 | 0.00 | 0.00 |
August | 1190.34 | 465.02 | 1023.82 | 18.14 | 1005.67 | 0.00 | 0.00 |
September | 713.86 | 813.79 | 784.97 | 0.19 | 784.78 | 0.00 | 0.00 |
October | 261.99 | 1241.57 | 583.64 | 0.00 | 583.64 | 0.00 | 0.00 |
November | 62.51 | 1889.72 | 408.26 | 0.00 | 408.26 | 0.00 | 0.00 |
December | 0.23 | 2735.47 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Annual Sum or Average | 571.21 | 1407.93 | 767.15 | 22.14 | 745.01 | 0.00 | 0.00 |
Minimum of Months | 0.23 | 393.77 | 264.82 | 0.00 | 264.82 | 0.00 | 0.00 |
Maximum of Months | 1459.98 | 3076.18 | 1303.81 | 118.34 | 1185.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 241.05 | 1852.16 | 557.14 | 229.26 | 327.87 | 0.00 | 0.00 |
February | 420.76 | 1480.53 | 738.48 | 324.73 | 413.76 | 0.00 | 0.00 |
March | 760.41 | 989.13 | 1003.37 | 398.27 | 605.10 | 0.00 | 0.00 |
April | 1163.31 | 716.92 | 1232.04 | 539.55 | 692.49 | 0.00 | 0.00 |
May | 1703.40 | 438.31 | 1547.35 | 676.12 | 871.23 | 0.00 | 0.00 |
June | 2085.13 | 302.45 | 1702.82 | 741.55 | 961.27 | 0.00 | 0.00 |
July | 2159.21 | 262.58 | 1721.11 | 794.16 | 926.95 | 0.00 | 0.00 |
August | 1822.09 | 307.68 | 1450.86 | 625.50 | 825.36 | 0.00 | 0.00 |
September | 1499.51 | 518.14 | 1294.04 | 611.50 | 682.54 | 0.00 | 0.00 |
October | 716.58 | 772.32 | 824.65 | 344.45 | 480.20 | 0.00 | 0.00 |
November | 252.38 | 1168.23 | 486.55 | 158.04 | 328.51 | 0.00 | 0.00 |
December | 166.59 | 1686.68 | 376.89 | 161.84 | 215.04 | 0.00 | 0.00 |
Annual Sum or Average | 1086.14 | 871.79 | 1079.63 | 467.75 | 611.87 | 0.00 | 0.00 |
Minimum of Months | 166.59 | 262.58 | 376.89 | 158.04 | 215.04 | 0.00 | 0.00 |
Maximum of Months | 2159.21 | 1852.16 | 1721.11 | 794.16 | 961.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2120.40 | 2526.71 | 2425.42 | 1659.77 | 765.65 | 0.00 | 0.00 |
February | 2363.59 | 2061.62 | 2598.79 | 1755.77 | 843.03 | 0.00 | 0.00 |
March | 2155.88 | 1513.14 | 2261.53 | 1190.85 | 1070.68 | 0.00 | 0.00 |
April | 2166.22 | 1146.85 | 2037.49 | 952.57 | 1084.92 | 0.00 | 0.00 |
May | 1903.02 | 716.17 | 1687.99 | 457.64 | 1230.35 | 0.00 | 0.00 |
June | 2057.65 | 487.13 | 1638.78 | 333.67 | 1305.12 | 0.00 | 0.00 |
July | 2277.02 | 420.97 | 1734.77 | 437.12 | 1297.65 | 0.00 | 0.00 |
August | 2604.30 | 499.16 | 1954.51 | 700.93 | 1253.57 | 0.00 | 0.00 |
September | 2941.43 | 823.98 | 2368.45 | 1247.98 | 1120.47 | 0.00 | 0.00 |
October | 2684.54 | 1197.19 | 2473.16 | 1551.56 | 921.60 | 0.00 | 0.00 |
November | 1720.57 | 1687.98 | 1866.00 | 1168.15 | 697.85 | 0.00 | 0.00 |
December | 1863.42 | 2365.31 | 1989.81 | 1507.26 | 482.55 | 0.00 | 0.00 |
Annual Sum or Average | 2237.32 | 1283.57 | 2083.37 | 1076.41 | 1006.96 | 0.00 | 0.00 |
Minimum of Months | 1720.57 | 420.97 | 1638.78 | 333.67 | 482.55 | 0.00 | 0.00 |
Maximum of Months | 2941.43 | 2526.71 | 2598.79 | 1755.77 | 1305.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.59 | 1897.09 | 552.54 | 223.57 | 328.98 | 0.00 | 0.00 |
February | 521.94 | 1535.14 | 810.21 | 399.25 | 410.96 | 0.00 | 0.00 |
March | 722.43 | 1022.82 | 967.22 | 359.86 | 607.36 | 0.00 | 0.00 |
April | 1422.11 | 749.66 | 1410.89 | 697.66 | 713.23 | 0.00 | 0.00 |
May | 1565.98 | 466.09 | 1414.97 | 565.25 | 849.72 | 0.00 | 0.00 |
June | 2046.44 | 327.14 | 1660.30 | 719.53 | 940.76 | 0.00 | 0.00 |
July | 2261.23 | 289.90 | 1782.65 | 846.79 | 935.87 | 0.00 | 0.00 |
August | 1986.82 | 333.69 | 1558.49 | 715.24 | 843.24 | 0.00 | 0.00 |
September | 1470.17 | 544.38 | 1261.55 | 598.80 | 662.75 | 0.00 | 0.00 |
October | 807.44 | 809.16 | 879.10 | 390.84 | 488.26 | 0.00 | 0.00 |
November | 320.54 | 1196.58 | 526.20 | 194.59 | 331.61 | 0.00 | 0.00 |
December | 217.42 | 1723.14 | 404.68 | 190.77 | 213.91 | 0.00 | 0.00 |
Annual Sum or Average | 1135.78 | 904.98 | 1103.57 | 491.94 | 611.63 | 0.00 | 0.00 |
Minimum of Months | 217.42 | 289.90 | 404.68 | 190.77 | 213.91 | 0.00 | 0.00 |
Maximum of Months | 2261.23 | 1897.09 | 1782.65 | 846.79 | 940.76 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5752779.95 | 0.808379E+10 | 0.104458E+10 | 0.00 | 0.104458E+10 | 0.00 | 0.00 |
February | 80185193.69 | 0.584424E+10 | 0.119617E+10 | 0.00 | 0.119617E+10 | 0.00 | 0.00 |
March | 0.645925E+09 | 0.412944E+10 | 0.198476E+10 | 0.00 | 0.198476E+10 | 0.00 | 0.00 |
April | 0.124658E+10 | 0.274688E+10 | 0.221736E+10 | 10924820.31 | 0.220643E+10 | 0.00 | 0.00 |
May | 0.260934E+10 | 0.168133E+10 | 0.298786E+10 | 0.112307E+09 | 0.287555E+10 | 0.00 | 0.00 |
June | 0.379503E+10 | 0.112841E+10 | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.00 | 0.00 |
July | 0.383806E+10 | 0.102087E+10 | 0.327506E+10 | 0.219066E+09 | 0.305600E+10 | 0.00 | 0.00 |
August | 0.319838E+10 | 0.119617E+10 | 0.274219E+10 | 48599256.74 | 0.269359E+10 | 0.00 | 0.00 |
September | 0.188533E+10 | 0.198356E+10 | 0.203465E+10 | 504502.48 | 0.203415E+10 | 0.00 | 0.00 |
October | 0.768181E+09 | 0.308151E+10 | 0.156323E+10 | 0.00 | 0.156323E+10 | 0.00 | 0.00 |
November | 0.189392E+09 | 0.463891E+10 | 0.105822E+10 | 0.00 | 0.105822E+10 | 0.00 | 0.00 |
December | 1624182.24 | 0.710334E+10 | 0.709306E+09 | 0.00 | 0.709306E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182638E+11 | 0.426385E+11 | 0.241929E+11 | 0.698132E+09 | 0.234947E+11 | 0.00 | 0.00 |
Minimum of Months | 1624182.24 | 0.102087E+10 | 0.709306E+09 | 0.00 | 0.709306E+09 | 0.00 | 0.00 |
Maximum of Months | 0.383806E+10 | 0.808379E+10 | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.653938E+09 | 0.486616E+10 | 0.149224E+10 | 0.614060E+09 | 0.878177E+09 | 0.00 | 0.00 |
February | 0.103497E+10 | 0.346497E+10 | 0.178654E+10 | 0.785576E+09 | 0.100096E+10 | 0.00 | 0.00 |
March | 0.206492E+10 | 0.253476E+10 | 0.268743E+10 | 0.106672E+10 | 0.162071E+10 | 0.00 | 0.00 |
April | 0.303386E+10 | 0.176303E+10 | 0.319346E+10 | 0.139852E+10 | 0.179494E+10 | 0.00 | 0.00 |
May | 0.457392E+10 | 0.112752E+10 | 0.414442E+10 | 0.181093E+10 | 0.233350E+10 | 0.00 | 0.00 |
June | 0.540680E+10 | 0.754564E+09 | 0.441370E+10 | 0.192210E+10 | 0.249160E+10 | 0.00 | 0.00 |
July | 0.577936E+10 | 0.682063E+09 | 0.460983E+10 | 0.212708E+10 | 0.248275E+10 | 0.00 | 0.00 |
August | 0.488252E+10 | 0.794093E+09 | 0.388600E+10 | 0.167534E+10 | 0.221066E+10 | 0.00 | 0.00 |
September | 0.390519E+10 | 0.127270E+10 | 0.335415E+10 | 0.158501E+10 | 0.176914E+10 | 0.00 | 0.00 |
October | 0.197227E+10 | 0.193009E+10 | 0.220875E+10 | 0.922577E+09 | 0.128617E+10 | 0.00 | 0.00 |
November | 0.683961E+09 | 0.287555E+10 | 0.126114E+10 | 0.409643E+09 | 0.851500E+09 | 0.00 | 0.00 |
December | 0.457026E+09 | 0.438012E+10 | 0.100946E+10 | 0.433485E+09 | 0.575971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344487E+11 | 0.264456E+11 | 0.340471E+11 | 0.147510E+11 | 0.192961E+11 | 0.00 | 0.00 |
Minimum of Months | 0.457026E+09 | 0.682063E+09 | 0.100946E+10 | 0.409643E+09 | 0.575971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.577936E+10 | 0.486616E+10 | 0.460983E+10 | 0.212708E+10 | 0.249160E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570788E+10 | 0.660935E+10 | 0.649625E+10 | 0.444552E+10 | 0.205072E+10 | 0.00 | 0.00 |
February | 0.575782E+10 | 0.480532E+10 | 0.628700E+10 | 0.424755E+10 | 0.203945E+10 | 0.00 | 0.00 |
March | 0.581405E+10 | 0.386840E+10 | 0.605729E+10 | 0.318957E+10 | 0.286772E+10 | 0.00 | 0.00 |
April | 0.563810E+10 | 0.280871E+10 | 0.528118E+10 | 0.246906E+10 | 0.281212E+10 | 0.00 | 0.00 |
May | 0.511468E+10 | 0.182908E+10 | 0.452112E+10 | 0.122574E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.533908E+10 | 0.120643E+10 | 0.424773E+10 | 0.864862E+09 | 0.338287E+10 | 0.00 | 0.00 |
July | 0.609603E+10 | 0.108660E+10 | 0.464640E+10 | 0.117077E+10 | 0.347563E+10 | 0.00 | 0.00 |
August | 0.697613E+10 | 0.128129E+10 | 0.523496E+10 | 0.187738E+10 | 0.335757E+10 | 0.00 | 0.00 |
September | 0.764922E+10 | 0.201613E+10 | 0.613903E+10 | 0.323476E+10 | 0.290426E+10 | 0.00 | 0.00 |
October | 0.725855E+10 | 0.298462E+10 | 0.662412E+10 | 0.415570E+10 | 0.246841E+10 | 0.00 | 0.00 |
November | 0.452241E+10 | 0.414111E+10 | 0.483666E+10 | 0.302784E+10 | 0.180882E+10 | 0.00 | 0.00 |
December | 0.502544E+10 | 0.612353E+10 | 0.532952E+10 | 0.403705E+10 | 0.129247E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.708994E+11 | 0.387606E+11 | 0.657012E+11 | 0.339458E+11 | 0.317554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.452241E+10 | 0.108660E+10 | 0.424773E+10 | 0.864862E+09 | 0.129247E+10 | 0.00 | 0.00 |
Maximum of Months | 0.764922E+10 | 0.660935E+10 | 0.662412E+10 | 0.444552E+10 | 0.347563E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.675166E+09 | 0.498485E+10 | 0.147993E+10 | 0.598799E+09 | 0.881133E+09 | 0.00 | 0.00 |
February | 0.127332E+10 | 0.359530E+10 | 0.196005E+10 | 0.965855E+09 | 0.994198E+09 | 0.00 | 0.00 |
March | 0.195420E+10 | 0.261883E+10 | 0.259060E+10 | 0.963846E+09 | 0.162676E+10 | 0.00 | 0.00 |
April | 0.369999E+10 | 0.183698E+10 | 0.365702E+10 | 0.180833E+10 | 0.184869E+10 | 0.00 | 0.00 |
May | 0.421010E+10 | 0.119017E+10 | 0.378985E+10 | 0.151396E+10 | 0.227589E+10 | 0.00 | 0.00 |
June | 0.530885E+10 | 0.811436E+09 | 0.430349E+10 | 0.186503E+10 | 0.243846E+10 | 0.00 | 0.00 |
July | 0.605531E+10 | 0.749363E+09 | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.00 | 0.00 |
August | 0.532563E+10 | 0.857219E+09 | 0.417425E+10 | 0.191571E+10 | 0.225854E+10 | 0.00 | 0.00 |
September | 0.383286E+10 | 0.133126E+10 | 0.326994E+10 | 0.155208E+10 | 0.171786E+10 | 0.00 | 0.00 |
October | 0.220365E+10 | 0.201706E+10 | 0.235459E+10 | 0.104682E+10 | 0.130776E+10 | 0.00 | 0.00 |
November | 0.855538E+09 | 0.294362E+10 | 0.136391E+10 | 0.504373E+09 | 0.859538E+09 | 0.00 | 0.00 |
December | 0.589612E+09 | 0.447525E+10 | 0.108388E+10 | 0.510958E+09 | 0.572924E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.359842E+11 | 0.274113E+11 | 0.348022E+11 | 0.155138E+11 | 0.192884E+11 | 0.00 | 0.00 |
Minimum of Months | 0.589612E+09 | 0.749363E+09 | 0.108388E+10 | 0.504373E+09 | 0.572924E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605531E+10 | 0.498485E+10 | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 6249346.00 | 0.810272E+10 | 0.104456E+10 | 0.00 | 0.104456E+10 | 0.00 | 0.00 |
February | 80957837.37 | 0.588040E+10 | 0.119614E+10 | 0.00 | 0.119614E+10 | 0.00 | 0.00 |
March | 0.695925E+09 | 0.413463E+10 | 0.198472E+10 | 0.00 | 0.198472E+10 | 0.00 | 0.00 |
April | 0.134362E+10 | 0.269362E+10 | 0.221731E+10 | 10924499.20 | 0.220639E+10 | 0.00 | 0.00 |
May | 0.274974E+10 | 0.160816E+10 | 0.298780E+10 | 0.112303E+09 | 0.287549E+10 | 0.00 | 0.00 |
June | 0.387923E+10 | 0.110835E+10 | 0.337940E+10 | 0.306722E+09 | 0.307268E+10 | 0.00 | 0.00 |
July | 0.390182E+10 | 0.101375E+10 | 0.327500E+10 | 0.219059E+09 | 0.305594E+10 | 0.00 | 0.00 |
August | 0.322260E+10 | 0.122634E+10 | 0.274213E+10 | 48597828.28 | 0.269353E+10 | 0.00 | 0.00 |
September | 0.186894E+10 | 0.211345E+10 | 0.203461E+10 | 504487.65 | 0.203410E+10 | 0.00 | 0.00 |
October | 0.711267E+09 | 0.335742E+10 | 0.156319E+10 | 0.00 | 0.156319E+10 | 0.00 | 0.00 |
November | 0.166145E+09 | 0.492587E+10 | 0.105820E+10 | 0.00 | 0.105820E+10 | 0.00 | 0.00 |
December | 763072.43 | 0.728298E+10 | 0.709290E+09 | 0.00 | 0.709290E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186273E+11 | 0.434477E+11 | 0.241923E+11 | 0.698112E+09 | 0.234942E+11 | 0.00 | 0.00 |
Minimum of Months | 763072.43 | 0.101375E+10 | 0.709290E+09 | 0.00 | 0.709290E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390182E+10 | 0.810272E+10 | 0.337940E+10 | 0.306722E+09 | 0.307268E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.663171E+09 | 0.490254E+10 | 0.149221E+10 | 0.614048E+09 | 0.878165E+09 | 0.00 | 0.00 |
February | 0.104632E+10 | 0.352339E+10 | 0.178651E+10 | 0.785561E+09 | 0.100095E+10 | 0.00 | 0.00 |
March | 0.210650E+10 | 0.257060E+10 | 0.268739E+10 | 0.106670E+10 | 0.162069E+10 | 0.00 | 0.00 |
April | 0.309724E+10 | 0.177299E+10 | 0.319341E+10 | 0.139849E+10 | 0.179492E+10 | 0.00 | 0.00 |
May | 0.464034E+10 | 0.113231E+10 | 0.414436E+10 | 0.181089E+10 | 0.233347E+10 | 0.00 | 0.00 |
June | 0.545123E+10 | 0.773499E+09 | 0.441363E+10 | 0.192206E+10 | 0.249157E+10 | 0.00 | 0.00 |
July | 0.581213E+10 | 0.709845E+09 | 0.460975E+10 | 0.212704E+10 | 0.248272E+10 | 0.00 | 0.00 |
August | 0.489738E+10 | 0.843355E+09 | 0.388594E+10 | 0.167531E+10 | 0.221063E+10 | 0.00 | 0.00 |
September | 0.389120E+10 | 0.139316E+10 | 0.335410E+10 | 0.158498E+10 | 0.176912E+10 | 0.00 | 0.00 |
October | 0.191312E+10 | 0.214237E+10 | 0.220871E+10 | 0.922559E+09 | 0.128615E+10 | 0.00 | 0.00 |
November | 0.655460E+09 | 0.306899E+10 | 0.126112E+10 | 0.409635E+09 | 0.851488E+09 | 0.00 | 0.00 |
December | 0.453128E+09 | 0.450786E+10 | 0.100944E+10 | 0.433476E+09 | 0.575963E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.346272E+11 | 0.273409E+11 | 0.340466E+11 | 0.147507E+11 | 0.192958E+11 | 0.00 | 0.00 |
Minimum of Months | 0.453128E+09 | 0.709845E+09 | 0.100944E+10 | 0.409635E+09 | 0.575963E+09 | 0.00 | 0.00 |
Maximum of Months | 0.581213E+10 | 0.490254E+10 | 0.460975E+10 | 0.212704E+10 | 0.249157E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.586128E+10 | 0.656000E+10 | 0.649599E+10 | 0.444534E+10 | 0.205065E+10 | 0.00 | 0.00 |
February | 0.589174E+10 | 0.487875E+10 | 0.628676E+10 | 0.424737E+10 | 0.203938E+10 | 0.00 | 0.00 |
March | 0.595810E+10 | 0.391173E+10 | 0.605706E+10 | 0.318944E+10 | 0.286763E+10 | 0.00 | 0.00 |
April | 0.576777E+10 | 0.281438E+10 | 0.528099E+10 | 0.246895E+10 | 0.281204E+10 | 0.00 | 0.00 |
May | 0.526180E+10 | 0.178837E+10 | 0.452097E+10 | 0.122569E+10 | 0.329528E+10 | 0.00 | 0.00 |
June | 0.543513E+10 | 0.119779E+10 | 0.424759E+10 | 0.864826E+09 | 0.338277E+10 | 0.00 | 0.00 |
July | 0.616011E+10 | 0.110774E+10 | 0.464625E+10 | 0.117072E+10 | 0.347553E+10 | 0.00 | 0.00 |
August | 0.701671E+10 | 0.135824E+10 | 0.523477E+10 | 0.187730E+10 | 0.335747E+10 | 0.00 | 0.00 |
September | 0.766110E+10 | 0.220523E+10 | 0.613880E+10 | 0.323463E+10 | 0.290417E+10 | 0.00 | 0.00 |
October | 0.723818E+10 | 0.334757E+10 | 0.662386E+10 | 0.415553E+10 | 0.246833E+10 | 0.00 | 0.00 |
November | 0.452434E+10 | 0.443289E+10 | 0.483647E+10 | 0.302772E+10 | 0.180876E+10 | 0.00 | 0.00 |
December | 0.508404E+10 | 0.624683E+10 | 0.532931E+10 | 0.403688E+10 | 0.129243E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.718603E+11 | 0.398495E+11 | 0.656988E+11 | 0.339444E+11 | 0.317544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.452434E+10 | 0.110774E+10 | 0.424759E+10 | 0.864826E+09 | 0.129243E+10 | 0.00 | 0.00 |
Maximum of Months | 0.766110E+10 | 0.656000E+10 | 0.662386E+10 | 0.444534E+10 | 0.347553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.692089E+09 | 0.501580E+10 | 0.147991E+10 | 0.598789E+09 | 0.881123E+09 | 0.00 | 0.00 |
February | 0.129841E+10 | 0.364949E+10 | 0.196003E+10 | 0.965840E+09 | 0.994187E+09 | 0.00 | 0.00 |
March | 0.200707E+10 | 0.265452E+10 | 0.259057E+10 | 0.963830E+09 | 0.162674E+10 | 0.00 | 0.00 |
April | 0.376409E+10 | 0.186467E+10 | 0.365697E+10 | 0.180830E+10 | 0.184867E+10 | 0.00 | 0.00 |
May | 0.427768E+10 | 0.118998E+10 | 0.378980E+10 | 0.151393E+10 | 0.227587E+10 | 0.00 | 0.00 |
June | 0.535071E+10 | 0.831555E+09 | 0.430343E+10 | 0.186500E+10 | 0.243844E+10 | 0.00 | 0.00 |
July | 0.608172E+10 | 0.787728E+09 | 0.477460E+10 | 0.226800E+10 | 0.250660E+10 | 0.00 | 0.00 |
August | 0.533777E+10 | 0.918207E+09 | 0.417420E+10 | 0.191568E+10 | 0.225852E+10 | 0.00 | 0.00 |
September | 0.381486E+10 | 0.145548E+10 | 0.326990E+10 | 0.155206E+10 | 0.171784E+10 | 0.00 | 0.00 |
October | 0.216464E+10 | 0.223387E+10 | 0.235455E+10 | 0.104681E+10 | 0.130775E+10 | 0.00 | 0.00 |
November | 0.835809E+09 | 0.314101E+10 | 0.136389E+10 | 0.504365E+09 | 0.859528E+09 | 0.00 | 0.00 |
December | 0.594172E+09 | 0.460316E+10 | 0.108387E+10 | 0.510950E+09 | 0.572918E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362190E+11 | 0.283455E+11 | 0.348017E+11 | 0.155135E+11 | 0.192882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.594172E+09 | 0.787728E+09 | 0.108387E+10 | 0.504365E+09 | 0.572918E+09 | 0.00 | 0.00 |
Maximum of Months | 0.608172E+10 | 0.501580E+10 | 0.477460E+10 | 0.226800E+10 | 0.250660E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4785580.32 | 0.823923E+10 | 0.104458E+10 | 0.00 | 0.104458E+10 | 0.00 | 0.00 |
February | 70497799.37 | 0.603497E+10 | 0.119617E+10 | 0.00 | 0.119617E+10 | 0.00 | 0.00 |
March | 0.616899E+09 | 0.431841E+10 | 0.198476E+10 | 0.00 | 0.198476E+10 | 0.00 | 0.00 |
April | 0.121884E+10 | 0.291324E+10 | 0.221736E+10 | 10924820.31 | 0.220643E+10 | 0.00 | 0.00 |
May | 0.257886E+10 | 0.175981E+10 | 0.298786E+10 | 0.112307E+09 | 0.287555E+10 | 0.00 | 0.00 |
June | 0.378428E+10 | 0.117505E+10 | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.00 | 0.00 |
July | 0.383664E+10 | 0.105468E+10 | 0.327506E+10 | 0.219066E+09 | 0.305600E+10 | 0.00 | 0.00 |
August | 0.318820E+10 | 0.124550E+10 | 0.274219E+10 | 48599256.74 | 0.269359E+10 | 0.00 | 0.00 |
September | 0.185032E+10 | 0.210935E+10 | 0.203465E+10 | 504502.48 | 0.203415E+10 | 0.00 | 0.00 |
October | 0.701719E+09 | 0.332543E+10 | 0.156323E+10 | 0.00 | 0.156323E+10 | 0.00 | 0.00 |
November | 0.162038E+09 | 0.489816E+10 | 0.105822E+10 | 0.00 | 0.105822E+10 | 0.00 | 0.00 |
December | 605769.29 | 0.732668E+10 | 0.709306E+09 | 0.00 | 0.709306E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180137E+11 | 0.444005E+11 | 0.241929E+11 | 0.698132E+09 | 0.234947E+11 | 0.00 | 0.00 |
Minimum of Months | 605769.29 | 0.105468E+10 | 0.709306E+09 | 0.00 | 0.709306E+09 | 0.00 | 0.00 |
Maximum of Months | 0.383664E+10 | 0.823923E+10 | 0.337947E+10 | 0.306731E+09 | 0.307274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.645632E+09 | 0.496082E+10 | 0.149224E+10 | 0.614060E+09 | 0.878177E+09 | 0.00 | 0.00 |
February | 0.101790E+10 | 0.358171E+10 | 0.178654E+10 | 0.785576E+09 | 0.100096E+10 | 0.00 | 0.00 |
March | 0.203669E+10 | 0.264930E+10 | 0.268743E+10 | 0.106672E+10 | 0.162071E+10 | 0.00 | 0.00 |
April | 0.301530E+10 | 0.185824E+10 | 0.319346E+10 | 0.139852E+10 | 0.179494E+10 | 0.00 | 0.00 |
May | 0.456239E+10 | 0.117397E+10 | 0.414442E+10 | 0.181093E+10 | 0.233350E+10 | 0.00 | 0.00 |
June | 0.540467E+10 | 0.783945E+09 | 0.441370E+10 | 0.192210E+10 | 0.249160E+10 | 0.00 | 0.00 |
July | 0.578323E+10 | 0.703296E+09 | 0.460983E+10 | 0.212708E+10 | 0.248275E+10 | 0.00 | 0.00 |
August | 0.488028E+10 | 0.824082E+09 | 0.388600E+10 | 0.167534E+10 | 0.221066E+10 | 0.00 | 0.00 |
September | 0.388673E+10 | 0.134302E+10 | 0.335415E+10 | 0.158501E+10 | 0.176914E+10 | 0.00 | 0.00 |
October | 0.191929E+10 | 0.206857E+10 | 0.220875E+10 | 0.922577E+09 | 0.128617E+10 | 0.00 | 0.00 |
November | 0.654167E+09 | 0.302805E+10 | 0.126114E+10 | 0.409643E+09 | 0.851500E+09 | 0.00 | 0.00 |
December | 0.446197E+09 | 0.451762E+10 | 0.100946E+10 | 0.433485E+09 | 0.575971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342525E+11 | 0.274926E+11 | 0.340471E+11 | 0.147510E+11 | 0.192961E+11 | 0.00 | 0.00 |
Minimum of Months | 0.446197E+09 | 0.703296E+09 | 0.100946E+10 | 0.409643E+09 | 0.575971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.578323E+10 | 0.496082E+10 | 0.460983E+10 | 0.212708E+10 | 0.249160E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.567928E+10 | 0.676754E+10 | 0.649625E+10 | 0.444552E+10 | 0.205072E+10 | 0.00 | 0.00 |
February | 0.571800E+10 | 0.498747E+10 | 0.628700E+10 | 0.424755E+10 | 0.203945E+10 | 0.00 | 0.00 |
March | 0.577432E+10 | 0.405280E+10 | 0.605729E+10 | 0.318957E+10 | 0.286772E+10 | 0.00 | 0.00 |
April | 0.561484E+10 | 0.297264E+10 | 0.528118E+10 | 0.246906E+10 | 0.281212E+10 | 0.00 | 0.00 |
May | 0.509706E+10 | 0.191820E+10 | 0.452112E+10 | 0.122574E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.533343E+10 | 0.126265E+10 | 0.424773E+10 | 0.864862E+09 | 0.338287E+10 | 0.00 | 0.00 |
July | 0.609876E+10 | 0.112754E+10 | 0.464640E+10 | 0.117077E+10 | 0.347563E+10 | 0.00 | 0.00 |
August | 0.697536E+10 | 0.133695E+10 | 0.523496E+10 | 0.187738E+10 | 0.335757E+10 | 0.00 | 0.00 |
September | 0.762418E+10 | 0.213577E+10 | 0.613903E+10 | 0.323476E+10 | 0.290426E+10 | 0.00 | 0.00 |
October | 0.719028E+10 | 0.320656E+10 | 0.662412E+10 | 0.415570E+10 | 0.246841E+10 | 0.00 | 0.00 |
November | 0.445971E+10 | 0.437525E+10 | 0.483666E+10 | 0.302784E+10 | 0.180882E+10 | 0.00 | 0.00 |
December | 0.499097E+10 | 0.633525E+10 | 0.532952E+10 | 0.403705E+10 | 0.129247E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.705562E+11 | 0.404786E+11 | 0.657012E+11 | 0.339458E+11 | 0.317554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445971E+10 | 0.112754E+10 | 0.424773E+10 | 0.864862E+09 | 0.129247E+10 | 0.00 | 0.00 |
Maximum of Months | 0.762418E+10 | 0.676754E+10 | 0.662412E+10 | 0.444552E+10 | 0.347563E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.671180E+09 | 0.508116E+10 | 0.147993E+10 | 0.598799E+09 | 0.881133E+09 | 0.00 | 0.00 |
February | 0.126268E+10 | 0.371382E+10 | 0.196005E+10 | 0.965855E+09 | 0.994198E+09 | 0.00 | 0.00 |
March | 0.193495E+10 | 0.273953E+10 | 0.259060E+10 | 0.963846E+09 | 0.162676E+10 | 0.00 | 0.00 |
April | 0.368610E+10 | 0.194313E+10 | 0.365702E+10 | 0.180833E+10 | 0.184869E+10 | 0.00 | 0.00 |
May | 0.419432E+10 | 0.124839E+10 | 0.378985E+10 | 0.151396E+10 | 0.227589E+10 | 0.00 | 0.00 |
June | 0.530437E+10 | 0.847959E+09 | 0.430349E+10 | 0.186503E+10 | 0.243846E+10 | 0.00 | 0.00 |
July | 0.605648E+10 | 0.776479E+09 | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.00 | 0.00 |
August | 0.532149E+10 | 0.893767E+09 | 0.417425E+10 | 0.191571E+10 | 0.225854E+10 | 0.00 | 0.00 |
September | 0.381069E+10 | 0.141102E+10 | 0.326994E+10 | 0.155208E+10 | 0.171786E+10 | 0.00 | 0.00 |
October | 0.216265E+10 | 0.216726E+10 | 0.235459E+10 | 0.104682E+10 | 0.130776E+10 | 0.00 | 0.00 |
November | 0.830839E+09 | 0.310153E+10 | 0.136391E+10 | 0.504373E+09 | 0.859538E+09 | 0.00 | 0.00 |
December | 0.582346E+09 | 0.461525E+10 | 0.108388E+10 | 0.510958E+09 | 0.572924E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358181E+11 | 0.285393E+11 | 0.348022E+11 | 0.155138E+11 | 0.192884E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582346E+09 | 0.776479E+09 | 0.108388E+10 | 0.504373E+09 | 0.572924E+09 | 0.00 | 0.00 |
Maximum of Months | 0.605648E+10 | 0.508116E+10 | 0.477466E+10 | 0.226804E+10 | 0.250662E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.551824E+10 | -0.526311E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -255123798.4 | 60.05 | 0.00 | 0.00 |
February | 0.510306E+10 | -0.487798E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -225082131.7 | 60.05 | 0.00 | 0.00 |
March | 0.595971E+10 | -0.571793E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241777051.2 | 60.05 | 0.00 | 0.00 |
April | 0.518044E+10 | -0.495087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229564856.5 | 60.05 | 0.00 | 0.00 |
May | 0.523724E+10 | -0.500407E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233174616.9 | 60.05 | 0.00 | 0.00 |
June | 0.486626E+10 | -0.464127E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224994799.5 | 60.05 | 0.00 | 0.00 |
July | 0.436218E+10 | -0.413070E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231483546.3 | 60.05 | 0.00 | 0.00 |
August | 0.468286E+10 | -0.445094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231920939.2 | 60.05 | 0.00 | 0.00 |
September | 0.428545E+10 | -0.406062E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224828175.2 | 60.05 | 0.00 | 0.00 |
October | 0.463561E+10 | -0.440059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235017970.1 | 60.05 | 0.00 | 0.00 |
November | 0.485496E+10 | -0.462151E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -233453062.4 | 60.05 | 0.00 | 0.00 |
December | 0.512489E+10 | -0.487588E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -249006865.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.598109E+11 | -0.569955E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.281543E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.428545E+10 | -0.571793E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -255123798.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.595971E+10 | -0.406062E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224828175.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 7570.67 | 37.48 | 205.17 | 245.33 | 6245.65 | 38.28 | 203.83 | 223.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8958.26 | 37.69 | 222.33 | 256.00 | 2620.60 | 29.06 | 197.33 | 239.83 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8166.85 | 30.57 | 272.67 | 329.00 | 1566.77 | 21.87 | 215.17 | 296.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 2460.19 | 19.32 | 17.50 | 347.67 | 1471.54 | 21.55 | 174.67 | 307.33 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1894.56 | 18.94 | 0.67 | 398.50 | 1060.60 | 21.14 | 225.50 | 355.33 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:49 | 1930.76 | 19.18 | 0.33 | 399.50 | 1097.00 | 21.40 | 247.83 | 361.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2005.07 | 19.47 | 4.83 | 409.17 | 1150.48 | 21.69 | 266.83 | 370.17 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2225.87 | 19.38 | 8.50 | 381.17 | 1253.12 | 21.58 | 262.33 | 348.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 3234.78 | 21.12 | 54.67 | 334.67 | 1594.25 | 22.09 | 222.67 | 306.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7712.61 | 33.41 | 293.67 | 307.33 | 2074.69 | 23.29 | 210.83 | 285.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5397.67 | 32.79 | 234.83 | 248.67 | 2939.34 | 31.15 | 230.17 | 228.83 |
December | 186.17 | 0.51 | 0.48 | 01-DEC-07:00 | 6582.33 | 36.38 | 168.83 | 222.50 | 6048.10 | 39.83 | 184.50 | 189.33 |
Annual Sum or Average | 3807.33 | 0.51 | 4354.93 | 25.48 | 1484.00 | 3879.50 | 2056.80 | 24.66 | 2641.67 | 3512.83 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1894.56 | 18.94 | 0.33 | 222.50 | 1060.60 | 21.14 | 174.67 | 189.33 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8958.26 | 37.69 | 293.67 | 409.17 | 6245.65 | 39.83 | 266.83 | 370.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:39 | 1989.16 | 22.45 | 66.17 | 232.00 | 1018.02 | 22.93 | 99.33 | 191.67 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2460.30 | 23.50 | 78.50 | 243.83 | 1361.58 | 24.16 | 97.67 | 210.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3121.56 | 21.92 | 103.67 | 323.50 | 1339.32 | 22.94 | 123.83 | 285.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3673.85 | 21.60 | 77.33 | 349.50 | 2201.65 | 23.83 | 84.00 | 317.17 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3834.49 | 22.38 | 136.67 | 406.67 | 1654.12 | 22.39 | 86.50 | 366.67 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-04:00 | 3466.14 | 21.14 | 95.67 | 407.00 | 1908.19 | 23.15 | 82.50 | 379.17 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4376.40 | 22.64 | 123.33 | 417.17 | 1911.74 | 22.82 | 78.33 | 384.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-05:40 | 3477.48 | 21.43 | 110.83 | 384.17 | 1584.76 | 22.76 | 98.67 | 358.67 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 3514.52 | 22.45 | 95.17 | 331.67 | 1987.29 | 23.70 | 108.33 | 303.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-06:40 | 2203.29 | 21.17 | 88.83 | 294.33 | 1211.74 | 23.24 | 119.00 | 265.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1734.41 | 21.56 | 83.50 | 236.00 | 925.25 | 22.61 | 89.50 | 197.50 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-07:00 | 1559.26 | 22.03 | 64.17 | 201.50 | 837.74 | 23.48 | 76.33 | 133.83 |
Annual Sum or Average | 3807.33 | 0.51 | 3137.25 | 21.98 | 1123.83 | 3827.33 | 1563.63 | 23.10 | 1144.00 | 3393.83 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1559.26 | 21.14 | 64.17 | 201.50 | 837.74 | 22.39 | 76.33 | 133.83 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4376.40 | 23.50 | 136.67 | 417.17 | 2201.65 | 24.16 | 123.83 | 384.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 696.43 | 16.04 | 0.00 | 215.67 | 426.70 | 18.55 | 0.50 | 143.33 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:20 | 734.41 | 16.40 | 0.00 | 231.83 | 458.21 | 18.87 | 0.50 | 175.33 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:30 | 995.55 | 17.88 | 0.00 | 320.00 | 580.50 | 20.09 | 23.17 | 270.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 1172.58 | 18.81 | 0.00 | 350.83 | 724.51 | 20.98 | 105.33 | 299.83 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1329.38 | 20.15 | 34.33 | 416.83 | 756.46 | 22.23 | 204.33 | 382.17 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1606.36 | 22.87 | 104.67 | 416.33 | 939.63 | 24.23 | 283.83 | 394.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1509.44 | 20.95 | 68.50 | 425.00 | 893.07 | 23.11 | 270.83 | 400.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1249.57 | 19.12 | 0.67 | 392.67 | 732.59 | 21.26 | 185.67 | 363.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 1037.15 | 18.53 | 0.00 | 332.17 | 639.36 | 20.73 | 58.50 | 291.17 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:40 | 816.24 | 16.93 | 0.00 | 285.50 | 484.88 | 19.24 | 0.33 | 233.33 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 692.31 | 15.93 | 0.00 | 225.67 | 394.93 | 18.20 | 0.00 | 153.50 |
December | 186.17 | 0.58 | 0.48 | 01-DEC-10:30 | 507.84 | 14.64 | 0.00 | 180.33 | 320.89 | 17.30 | 0.00 | 75.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1105.69 | 18.69 | 208.17 | 3792.83 | 655.12 | 20.85 | 1133.00 | 3182.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 507.84 | 14.64 | 0.00 | 180.33 | 320.89 | 17.30 | 0.00 | 75.50 | |
Maximum of Months | 428.67 | 0.58 | 0.48 | 1606.36 | 22.87 | 104.67 | 425.00 | 939.63 | 24.23 | 283.83 | 400.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 2161.17 | 24.05 | 84.17 | 230.67 | 1253.02 | 24.55 | 99.17 | 192.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:20 | 2462.35 | 21.69 | 63.33 | 242.33 | 1393.36 | 23.79 | 89.33 | 212.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:39 | 2672.38 | 21.62 | 95.33 | 326.17 | 1446.23 | 22.78 | 119.83 | 291.17 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4796.37 | 22.59 | 84.50 | 351.83 | 1999.15 | 21.99 | 59.67 | 307.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-07:10 | 2868.96 | 17.94 | 51.00 | 405.50 | 1561.43 | 19.07 | 3.17 | 372.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3666.75 | 18.41 | 50.33 | 407.00 | 1681.52 | 19.49 | 3.67 | 374.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-06:10 | 4071.06 | 18.89 | 56.00 | 414.17 | 1807.30 | 19.71 | 13.67 | 383.17 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:30 | 3418.39 | 20.32 | 84.67 | 388.50 | 1928.67 | 21.75 | 70.33 | 357.67 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:19 | 3556.06 | 22.66 | 97.00 | 336.33 | 2095.32 | 24.03 | 98.17 | 306.67 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:49 | 2262.06 | 21.19 | 86.67 | 295.33 | 1236.17 | 23.06 | 105.50 | 264.17 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1791.10 | 21.37 | 83.83 | 238.50 | 975.73 | 22.30 | 81.50 | 199.00 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:20 | 1641.51 | 21.03 | 55.00 | 206.17 | 940.71 | 23.12 | 68.00 | 132.33 |
Annual Sum or Average | 3807.33 | 0.51 | 3080.91 | 20.65 | 891.83 | 3842.50 | 1584.19 | 21.79 | 812.00 | 3391.50 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1641.51 | 17.94 | 50.33 | 206.17 | 940.71 | 19.07 | 3.17 | 132.33 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4796.37 | 24.05 | 97.00 | 414.17 | 2095.32 | 24.55 | 119.83 | 383.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 7355.35 | 37.12 | 205.17 | 243.83 | 6081.27 | 37.91 | 200.17 | 221.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8760.37 | 37.46 | 222.33 | 255.67 | 2468.02 | 27.04 | 105.83 | 238.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8016.20 | 29.68 | 253.00 | 327.67 | 1459.09 | 19.07 | 17.33 | 293.83 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 2331.10 | 15.66 | 0.00 | 346.83 | 1376.37 | 19.20 | 38.17 | 302.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1812.98 | 15.20 | 0.00 | 395.83 | 1005.99 | 18.68 | 6.00 | 351.67 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:49 | 1850.32 | 15.64 | 0.00 | 396.83 | 1045.13 | 19.12 | 11.83 | 355.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1918.59 | 15.96 | 0.00 | 406.83 | 1093.75 | 19.45 | 19.33 | 366.83 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2122.74 | 15.71 | 0.00 | 379.00 | 1181.91 | 19.19 | 30.67 | 346.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 3089.39 | 17.65 | 26.00 | 333.33 | 1486.05 | 19.64 | 52.00 | 303.83 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7554.57 | 32.86 | 291.67 | 306.17 | 1953.74 | 20.53 | 39.83 | 283.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5251.31 | 32.39 | 230.50 | 248.00 | 2831.32 | 30.07 | 185.83 | 226.00 |
December | 186.17 | 0.51 | 0.48 | 01-DEC-07:00 | 6380.87 | 35.55 | 167.50 | 220.00 | 5890.31 | 39.63 | 184.17 | 186.00 |
Annual Sum or Average | 3807.33 | 0.51 | 4224.34 | 23.11 | 1396.17 | 3860.00 | 1961.87 | 22.54 | 891.17 | 3475.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1812.98 | 15.20 | 0.00 | 220.00 | 1005.99 | 18.68 | 6.00 | 186.00 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8760.37 | 37.46 | 291.67 | 406.83 | 6081.27 | 39.63 | 200.17 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:39 | 1929.19 | 21.91 | 65.67 | 229.83 | 973.09 | 22.69 | 90.33 | 187.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2310.07 | 21.03 | 62.83 | 240.67 | 1308.46 | 23.95 | 93.50 | 207.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3044.91 | 21.45 | 102.67 | 321.33 | 1279.64 | 22.74 | 104.83 | 283.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3571.91 | 21.13 | 77.33 | 348.33 | 2083.93 | 22.81 | 68.50 | 313.33 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-05:19 | 3742.88 | 21.94 | 136.33 | 404.17 | 1583.29 | 22.20 | 81.33 | 362.83 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-04:00 | 3359.35 | 20.68 | 95.67 | 404.50 | 1815.29 | 22.36 | 69.00 | 374.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4268.37 | 22.19 | 123.33 | 415.00 | 1833.00 | 22.64 | 72.33 | 381.17 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-05:40 | 3385.02 | 20.97 | 110.67 | 382.00 | 1514.02 | 22.58 | 83.33 | 356.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 3417.33 | 21.98 | 95.17 | 330.50 | 1910.64 | 23.50 | 97.17 | 299.50 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-06:40 | 2138.28 | 20.68 | 88.50 | 292.50 | 1161.39 | 23.03 | 107.00 | 262.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1686.80 | 21.10 | 82.50 | 234.67 | 889.78 | 22.22 | 81.17 | 192.83 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-08:09 | 1512.20 | 21.55 | 64.17 | 199.33 | 773.00 | 22.03 | 66.00 | 129.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3047.91 | 21.39 | 1104.83 | 3802.83 | 1493.52 | 22.71 | 1014.50 | 3349.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1512.20 | 20.68 | 62.83 | 199.33 | 773.00 | 22.03 | 66.00 | 129.50 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4268.37 | 22.19 | 136.33 | 415.00 | 2083.93 | 23.95 | 107.00 | 381.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.56 | 0.48 | 01-JAN-10:09 | 669.18 | 12.44 | 0.00 | 212.33 | 411.98 | 16.16 | 0.00 | 135.67 |
February | 226.83 | 0.55 | 0.48 | 01-FEB-09:30 | 706.92 | 12.93 | 0.00 | 227.33 | 443.63 | 16.64 | 0.00 | 166.67 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:30 | 960.39 | 14.38 | 0.00 | 318.33 | 561.07 | 17.86 | 0.00 | 264.33 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:30 | 1131.44 | 15.65 | 0.00 | 349.83 | 702.83 | 19.16 | 18.33 | 293.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1276.60 | 15.63 | 3.17 | 413.33 | 730.29 | 20.17 | 50.83 | 379.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 1538.12 | 19.48 | 75.67 | 414.00 | 906.50 | 22.43 | 118.50 | 392.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:49 | 1455.55 | 17.85 | 30.67 | 424.33 | 862.83 | 21.23 | 100.17 | 397.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1205.11 | 15.78 | 0.00 | 391.17 | 708.12 | 19.29 | 20.33 | 360.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 999.44 | 15.39 | 0.00 | 331.17 | 619.32 | 18.88 | 0.00 | 286.50 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:40 | 786.52 | 13.37 | 0.00 | 282.67 | 468.64 | 16.94 | 0.00 | 227.67 |
November | 254.83 | 0.55 | 0.48 | 01-NOV-08:39 | 666.94 | 12.10 | 0.00 | 222.33 | 380.68 | 15.65 | 0.00 | 144.83 |
December | 186.17 | 0.59 | 0.48 | 01-DEC-10:30 | 487.49 | 10.76 | 0.00 | 174.17 | 310.13 | 14.68 | 0.00 | 69.67 |
Annual Sum or Average | 3807.33 | 0.52 | 1064.10 | 15.16 | 109.50 | 3761.00 | 633.15 | 18.75 | 308.17 | 3117.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 487.49 | 10.76 | 0.00 | 174.17 | 310.13 | 14.68 | 0.00 | 69.67 | |
Maximum of Months | 428.67 | 0.59 | 0.48 | 1538.12 | 19.48 | 75.67 | 424.33 | 906.50 | 22.43 | 118.50 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 2103.01 | 23.70 | 84.17 | 229.50 | 1208.26 | 24.46 | 97.83 | 186.50 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2388.13 | 21.28 | 63.33 | 241.00 | 1334.71 | 23.70 | 87.83 | 209.67 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:39 | 2602.08 | 21.21 | 94.50 | 324.00 | 1391.33 | 22.66 | 114.83 | 287.50 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4583.10 | 22.15 | 84.50 | 349.50 | 1910.50 | 21.85 | 55.17 | 302.83 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-07:10 | 2783.13 | 17.45 | 50.50 | 403.33 | 1497.55 | 18.89 | 2.17 | 367.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3518.69 | 17.92 | 50.33 | 405.17 | 1603.61 | 19.31 | 1.33 | 370.17 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3957.01 | 18.41 | 56.00 | 412.83 | 1721.05 | 19.55 | 7.67 | 381.67 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:30 | 3320.90 | 19.86 | 84.67 | 386.83 | 1844.29 | 21.60 | 64.50 | 354.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:30 | 3463.24 | 22.24 | 97.00 | 334.50 | 1986.98 | 23.90 | 93.83 | 303.50 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:49 | 2173.41 | 20.48 | 83.33 | 294.17 | 1182.26 | 22.95 | 102.17 | 261.17 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1686.44 | 19.70 | 70.50 | 236.17 | 937.69 | 22.20 | 81.00 | 195.50 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:30 | 1593.52 | 20.62 | 55.00 | 203.00 | 902.95 | 23.04 | 67.33 | 128.50 |
Annual Sum or Average | 3807.33 | 0.51 | 2978.02 | 20.10 | 873.83 | 3820.00 | 1514.55 | 21.65 | 775.67 | 3349.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1593.52 | 17.45 | 50.33 | 203.00 | 902.95 | 18.89 | 1.33 | 128.50 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4583.10 | 23.70 | 97.00 | 412.83 | 1986.98 | 24.46 | 114.83 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 7355.37 | 37.12 | 205.17 | 243.83 | 6081.16 | 37.91 | 200.17 | 221.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8760.33 | 37.46 | 222.33 | 255.67 | 2467.90 | 27.04 | 105.83 | 238.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8016.07 | 29.68 | 253.00 | 327.67 | 1458.97 | 19.07 | 17.33 | 293.83 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 2330.98 | 15.66 | 0.00 | 346.83 | 1376.28 | 19.20 | 38.33 | 302.33 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1812.87 | 15.20 | 0.00 | 395.83 | 1005.92 | 18.68 | 6.00 | 351.67 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:49 | 1850.22 | 15.64 | 0.00 | 396.83 | 1045.05 | 19.12 | 11.83 | 355.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1918.49 | 15.96 | 0.00 | 406.83 | 1093.67 | 19.45 | 19.50 | 366.83 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2122.62 | 15.71 | 0.00 | 379.00 | 1181.82 | 19.20 | 30.67 | 346.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 3089.27 | 17.65 | 26.00 | 333.33 | 1485.94 | 19.64 | 52.00 | 303.83 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7554.49 | 32.86 | 291.67 | 306.17 | 1953.63 | 20.53 | 40.00 | 283.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5251.27 | 32.39 | 230.50 | 248.00 | 2831.22 | 30.07 | 185.83 | 226.00 |
December | 186.17 | 0.51 | 0.48 | 01-DEC-07:00 | 6380.90 | 35.55 | 167.50 | 220.00 | 5890.24 | 39.63 | 184.17 | 186.00 |
Annual Sum or Average | 3807.33 | 0.51 | 4224.25 | 23.11 | 1396.17 | 3860.00 | 1961.77 | 22.55 | 891.67 | 3475.00 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1812.87 | 15.20 | 0.00 | 220.00 | 1005.92 | 18.68 | 6.00 | 186.00 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8760.33 | 37.46 | 291.67 | 406.83 | 6081.16 | 39.63 | 200.17 | 366.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:39 | 1929.17 | 21.91 | 65.67 | 229.83 | 973.04 | 22.69 | 90.33 | 187.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2310.05 | 21.03 | 62.83 | 240.67 | 1308.41 | 23.95 | 93.50 | 207.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3044.85 | 21.45 | 102.67 | 321.33 | 1279.57 | 22.74 | 104.83 | 283.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3571.87 | 21.14 | 77.33 | 348.33 | 2083.86 | 22.81 | 68.50 | 313.33 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-05:19 | 3742.80 | 21.94 | 136.33 | 404.17 | 1583.21 | 22.20 | 81.33 | 362.83 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-04:00 | 3359.28 | 20.68 | 95.67 | 404.50 | 1815.20 | 22.36 | 69.00 | 374.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4268.31 | 22.19 | 123.33 | 415.00 | 1832.91 | 22.64 | 72.33 | 381.17 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-05:40 | 3384.96 | 20.97 | 110.67 | 382.00 | 1513.94 | 22.58 | 83.50 | 356.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 3417.29 | 21.98 | 95.17 | 330.50 | 1910.56 | 23.50 | 97.33 | 299.50 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-06:40 | 2138.24 | 20.68 | 88.50 | 292.50 | 1161.33 | 23.03 | 107.17 | 262.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1686.76 | 21.10 | 82.50 | 234.67 | 889.72 | 22.22 | 81.17 | 192.83 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-08:09 | 1512.19 | 21.55 | 64.17 | 199.33 | 772.96 | 22.03 | 66.00 | 129.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3047.86 | 21.39 | 1104.83 | 3802.83 | 1493.45 | 22.71 | 1015.00 | 3349.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1512.19 | 20.68 | 62.83 | 199.33 | 772.96 | 22.03 | 66.00 | 129.50 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4268.31 | 22.19 | 136.33 | 415.00 | 2083.86 | 23.95 | 107.17 | 381.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.56 | 0.48 | 01-JAN-10:09 | 669.17 | 12.44 | 0.00 | 212.33 | 411.95 | 16.16 | 0.00 | 135.67 |
February | 226.83 | 0.55 | 0.48 | 01-FEB-09:30 | 706.91 | 12.94 | 0.00 | 227.33 | 443.60 | 16.64 | 0.00 | 166.67 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:30 | 960.35 | 14.38 | 0.00 | 318.33 | 561.03 | 17.86 | 0.00 | 264.33 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:30 | 1131.41 | 15.65 | 0.00 | 349.83 | 702.79 | 19.16 | 18.33 | 292.83 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1276.55 | 15.63 | 3.17 | 413.33 | 730.24 | 20.17 | 50.83 | 379.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 1538.07 | 19.48 | 75.67 | 414.00 | 906.44 | 22.43 | 118.50 | 392.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:49 | 1455.51 | 17.86 | 30.67 | 424.33 | 862.78 | 21.23 | 100.17 | 397.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1205.07 | 15.79 | 0.00 | 391.17 | 708.07 | 19.29 | 20.33 | 360.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 999.42 | 15.40 | 0.00 | 331.17 | 619.28 | 18.88 | 0.00 | 286.50 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:40 | 786.50 | 13.37 | 0.00 | 282.67 | 468.60 | 16.94 | 0.00 | 227.67 |
November | 254.83 | 0.55 | 0.48 | 01-NOV-08:39 | 666.91 | 12.10 | 0.00 | 222.33 | 380.65 | 15.65 | 0.00 | 144.83 |
December | 186.17 | 0.59 | 0.48 | 01-DEC-10:30 | 487.49 | 10.76 | 0.00 | 174.17 | 310.11 | 14.68 | 0.00 | 69.67 |
Annual Sum or Average | 3807.33 | 0.52 | 1064.07 | 15.16 | 109.50 | 3761.00 | 633.10 | 18.76 | 308.17 | 3117.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 487.49 | 10.76 | 0.00 | 174.17 | 310.11 | 14.68 | 0.00 | 69.67 | |
Maximum of Months | 428.67 | 0.59 | 0.48 | 1538.07 | 19.48 | 75.67 | 424.33 | 906.44 | 22.43 | 118.50 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 2102.99 | 23.70 | 84.17 | 229.50 | 1208.21 | 24.46 | 97.83 | 186.50 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:30 | 2388.11 | 21.28 | 63.33 | 241.00 | 1334.66 | 23.70 | 87.83 | 209.67 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:39 | 2602.03 | 21.21 | 94.50 | 324.00 | 1391.26 | 22.66 | 114.83 | 287.50 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4583.06 | 22.16 | 84.50 | 349.50 | 1910.42 | 21.85 | 55.17 | 302.83 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-07:10 | 2783.06 | 17.45 | 50.50 | 403.33 | 1497.47 | 18.89 | 2.17 | 367.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3518.62 | 17.92 | 50.33 | 405.17 | 1603.52 | 19.32 | 1.33 | 370.17 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3956.94 | 18.41 | 56.00 | 412.83 | 1720.95 | 19.55 | 7.67 | 381.67 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:30 | 3320.84 | 19.86 | 84.67 | 386.83 | 1844.20 | 21.60 | 64.50 | 354.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:30 | 3463.20 | 22.24 | 97.00 | 334.50 | 1986.90 | 23.90 | 93.83 | 303.50 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:49 | 2173.37 | 20.48 | 83.33 | 294.17 | 1182.20 | 22.96 | 102.33 | 261.17 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1686.40 | 19.71 | 70.50 | 236.17 | 937.64 | 22.20 | 81.17 | 195.50 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:30 | 1593.51 | 20.63 | 55.00 | 203.00 | 902.92 | 23.04 | 67.33 | 128.50 |
Annual Sum or Average | 3807.33 | 0.51 | 2977.97 | 20.10 | 873.83 | 3820.00 | 1514.48 | 21.65 | 776.00 | 3349.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1593.51 | 17.45 | 50.33 | 203.00 | 902.92 | 18.89 | 1.33 | 128.50 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4583.06 | 23.70 | 97.00 | 412.83 | 1986.90 | 24.46 | 114.83 | 381.67 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276705E+11 | 37878.94 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179333E+11 | 39488.68 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.983935E+10 | 23870.73 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318421E+10 | 16577.46 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58814305.68 | 4661.61 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 632070.65 | 5.82 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 864401.28 | 5.88 | 05-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 768505.99 | 5.49 | 21-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137580E+09 | 6745.84 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116224E+10 | 9058.24 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.886830E+10 | 29497.40 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196882E+11 | 36028.76 | 11-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.885448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 632070.65 | 5.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276705E+11 | 39488.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.770411E+09 | 13709.01 | 02-JAN-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244214E+09 | 13679.88 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 414613.29 | 6910.22 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20781963.14 | 13675.24 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85023586.80 | 13677.75 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.770411E+09 | 13709.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100816E+11 | 10202.28 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675804E+10 | 10675.75 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520152E+10 | 9675.48 | 20-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269726E+10 | 9888.75 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.657638E+09 | 9760.82 | 08-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.226392E+09 | 9770.99 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5359695.92 | 4893.76 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33588953.22 | 9680.26 | 16-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.462559E+09 | 10131.34 | 20-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118138E+10 | 9694.60 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405488E+10 | 9678.25 | 27-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767092E+10 | 9681.33 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5359695.92 | 4893.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100816E+11 | 10675.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.536974E+10 | 7592.14 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341462E+10 | 7946.60 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163717E+10 | 7187.57 | 11-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.580794E+09 | 7184.11 | 05-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 466688.38 | 3293.28 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2975249.07 | 3270.32 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41237998.20 | 7175.18 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145839E+10 | 7200.46 | 27-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.363424E+10 | 7203.23 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.536974E+10 | 7946.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860694E+10 | 8155.65 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.577131E+10 | 8531.11 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307786E+10 | 7733.54 | 14-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106923E+10 | 7736.11 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22672471.77 | 7723.74 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8930788.12 | 7046.52 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101130E+09 | 7720.60 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223807E+10 | 7740.41 | 27-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.561040E+10 | 7743.82 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860694E+10 | 8531.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.562157E+10 | 7881.23 | 30-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359336E+10 | 8249.72 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187348E+10 | 7462.82 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.549343E+09 | 7455.17 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12842652.53 | 7447.14 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15691120.95 | 7414.29 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 59893015.05 | 7440.89 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153255E+10 | 7474.04 | 27-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373382E+10 | 7476.82 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562157E+10 | 8249.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277597E+11 | 39251.74 | 30-JAN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184385E+11 | 40839.55 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108589E+11 | 23976.65 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399327E+10 | 17583.14 | 03-APR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110687E+09 | 5901.91 | 02-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2810155.32 | 713.34 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 767399.86 | 5.37 | 03-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 690856.44 | 5.16 | 01-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265830E+09 | 8059.99 | 29-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197436E+10 | 11401.91 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.993748E+10 | 29032.88 | 28-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204811E+11 | 35665.09 | 11-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 690856.44 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.277597E+11 | 40839.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.508536E+10 | 19755.88 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260056E+10 | 19760.81 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689936E+09 | 19749.91 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115636E+09 | 19747.80 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125282E+10 | 19789.34 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297086E+10 | 19761.95 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508536E+10 | 19789.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.512561E+10 | 10772.80 | 30-JAN-08:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282317E+10 | 11204.10 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141654E+10 | 10426.42 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.420717E+09 | 10415.89 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3456184.37 | 6585.68 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16476056.92 | 10335.86 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118059E+09 | 10339.32 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178021E+10 | 10414.12 | 25-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424975E+10 | 10423.30 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.512561E+10 | 11204.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.524111E+10 | 8247.94 | 30-JAN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317464E+10 | 8611.51 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139589E+10 | 7991.24 | 06-MAR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.424659E+09 | 7991.58 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 429328.09 | 3498.76 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21550003.90 | 7940.65 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202104E+09 | 7949.13 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194714E+10 | 8000.27 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406494E+10 | 7996.93 | 13-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.524111E+10 | 8611.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.789451E+10 | 8609.00 | 30-JAN-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486881E+10 | 8982.81 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199825E+10 | 8310.14 | 15-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485845E+09 | 8306.84 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2099896.62 | 5413.12 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20116775.57 | 8231.07 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190370E+09 | 8258.57 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258271E+10 | 8312.91 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.572021E+10 | 8311.65 | 18-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.789451E+10 | 8982.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.536094E+10 | 8468.44 | 30-JAN-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329983E+10 | 8842.93 | 02-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153241E+10 | 8153.29 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426158E+09 | 8150.32 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6980464.94 | 8113.72 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41905601.74 | 8087.80 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231958E+09 | 8101.97 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196239E+10 | 8148.50 | 20-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407431E+10 | 8141.83 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.536094E+10 | 8842.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.306737E+11 | 39838.42 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198006E+11 | 41117.04 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113549E+11 | 23477.65 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.432462E+10 | 18205.71 | 03-APR-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169226E+09 | 7678.11 | 02-MAY-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15556073.76 | 2394.38 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 704891.57 | 5.91 | 03-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 634876.90 | 5.78 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409856E+09 | 10226.57 | 29-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248240E+10 | 13672.83 | 23-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109782E+11 | 31866.12 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224736E+11 | 37755.88 | 09-DEC-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 634876.90 | 5.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.306737E+11 | 41117.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113230E+11 | 26769.31 | 31-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.708143E+10 | 27677.62 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305716E+10 | 26642.78 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.827201E+09 | 26622.07 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28436734.98 | 26399.03 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.300972E+09 | 26650.04 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415108E+10 | 26648.11 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.842113E+10 | 26635.71 | 04-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113230E+11 | 27677.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.815413E+10 | 12788.67 | 31-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.482669E+10 | 13384.96 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.280307E+10 | 12281.73 | 13-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105720E+10 | 12278.07 | 03-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36146867.08 | 12212.11 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3128979.03 | 3272.79 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127154E+09 | 12248.13 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.597946E+09 | 12273.25 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.338407E+10 | 12281.21 | 21-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687335E+10 | 12284.99 | 02-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.815413E+10 | 13384.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.736793E+10 | 9429.44 | 31-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458827E+10 | 9871.76 | 02-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229840E+10 | 9049.61 | 11-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.835571E+09 | 9042.62 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9642572.92 | 8673.92 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4178341.13 | 1266.40 | 06-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108687E+09 | 8998.94 | 29-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.637646E+09 | 9044.68 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.310344E+10 | 9046.87 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588599E+10 | 9045.53 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736793E+10 | 9871.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115120E+11 | 10271.74 | 30-JAN-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732315E+10 | 10749.24 | 02-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367098E+10 | 9877.01 | 14-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115062E+10 | 9873.69 | 26-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25486161.33 | 9822.43 | 03-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37018.93 | 105.56 | 05-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149611E+09 | 9831.91 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.909429E+09 | 9870.95 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.447575E+10 | 9876.96 | 18-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.881997E+10 | 9873.71 | 02-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115120E+11 | 10749.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.771038E+10 | 9893.21 | 30-JAN-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492815E+10 | 10359.99 | 02-FEB-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266472E+10 | 9480.85 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.931146E+09 | 9477.10 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45269215.42 | 9433.25 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10401175.43 | 3625.85 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.186469E+09 | 9461.29 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.817320E+09 | 9480.95 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326468E+10 | 9483.54 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.606898E+10 | 9480.24 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.771038E+10 | 10359.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.161351E+09 | 0.142329E+09 | 7712.66 | 25-MAR-15:00 | 6879.32 | 0.00 |
April | 0.00 | 0.00 | 0.542952E+10 | 0.424299E+10 | 67012.65 | 18-APR-15:00 | 56596.12 | 0.00 |
May | 0.00 | 0.00 | 0.147989E+11 | 0.111516E+11 | 71377.04 | 30-MAY-11:00 | 45381.13 | 0.00 |
June | 0.00 | 0.00 | 0.460337E+11 | 0.343925E+11 | 128332.12 | 26-JUN-07:50 | 57199.47 | 0.00 |
July | 0.00 | 0.00 | 0.661556E+11 | 0.448640E+11 | 120254.86 | 05-JUL-10:50 | 63571.51 | 0.00 |
August | 0.00 | 0.00 | 0.648198E+11 | 0.449078E+11 | 129595.42 | 03-AUG-06:03 | 43631.36 | 0.00 |
September | 0.00 | 0.00 | 0.262104E+11 | 0.232067E+11 | 99240.59 | 11-SEP-09:50 | 59373.71 | 0.00 |
October | 0.00 | 0.00 | 0.165068E+10 | 0.143739E+10 | 36123.10 | 20-OCT-15:00 | 36123.10 | 0.00 |
November | 0.00 | 0.00 | 58292914.63 | 53535882.59 | 5059.30 | 03-NOV-15:00 | 5059.30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.225318E+12 | 0.164399E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.661556E+11 | 0.449078E+11 | 129595.42 | 63571.51 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.204570E+09 | 0.171182E+09 | 8766.29 | 19-MAR-14:38 | 5721.02 | 0.00 |
April | 0.00 | 0.00 | 0.591315E+10 | 0.468811E+10 | 69211.56 | 18-APR-12:40 | 50754.42 | 0.00 |
May | 0.00 | 0.00 | 0.154369E+11 | 0.115313E+11 | 71546.37 | 30-MAY-11:00 | 44858.37 | 0.00 |
June | 0.00 | 0.00 | 0.441780E+11 | 0.329659E+11 | 123115.65 | 26-JUN-07:50 | 54628.45 | 0.00 |
July | 0.00 | 0.00 | 0.605903E+11 | 0.409324E+11 | 111163.59 | 03-JUL-08:50 | 51721.22 | 0.00 |
August | 0.00 | 0.00 | 0.566922E+11 | 0.392809E+11 | 124327.60 | 04-AUG-06:03 | 37235.66 | 0.00 |
September | 0.00 | 0.00 | 0.228398E+11 | 0.201945E+11 | 88575.16 | 11-SEP-09:50 | 53155.46 | 0.00 |
October | 0.00 | 0.00 | 0.144964E+10 | 0.123991E+10 | 30536.86 | 20-OCT-15:00 | 30536.86 | 0.00 |
November | 0.00 | 0.00 | 78277911.17 | 67070532.18 | 7104.46 | 03-NOV-13:30 | 5904.83 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207383E+12 | 0.151071E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.605903E+11 | 0.409324E+11 | 124327.60 | 54628.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1010801.22 | 1007296.44 | 1124.85 | 02-JAN-06:17 | 1124.85 | 0.00 |
February | 0.00 | 0.00 | 573565.97 | 565194.19 | 644.53 | 06-FEB-06:30 | 644.53 | 0.00 |
March | 0.00 | 0.00 | 0.187738E+09 | 0.156119E+09 | 9593.33 | 19-MAR-13:53 | 6255.77 | 0.00 |
April | 0.00 | 0.00 | 0.647034E+10 | 0.507979E+10 | 96171.09 | 16-APR-13:42 | 60325.06 | 0.00 |
May | 0.00 | 0.00 | 0.162732E+11 | 0.121907E+11 | 73143.58 | 31-MAY-15:00 | 67921.72 | 0.00 |
June | 0.00 | 0.00 | 0.466582E+11 | 0.351354E+11 | 132187.84 | 26-JUN-06:03 | 52952.68 | 0.00 |
July | 0.00 | 0.00 | 0.635136E+11 | 0.427777E+11 | 115687.52 | 06-JUL-15:10 | 59659.27 | 0.00 |
August | 0.00 | 0.00 | 0.580435E+11 | 0.406068E+11 | 137169.52 | 04-AUG-07:15 | 40480.61 | 0.00 |
September | 0.00 | 0.00 | 0.233118E+11 | 0.205090E+11 | 85429.20 | 11-SEP-10:00 | 52919.21 | 0.00 |
October | 0.00 | 0.00 | 0.140308E+10 | 0.117196E+10 | 29718.13 | 20-OCT-15:00 | 29718.13 | 0.00 |
November | 0.00 | 0.00 | 47523575.27 | 40333879.63 | 4000.88 | 03-NOV-13:40 | 3344.12 | 0.00 |
December | 0.00 | 0.00 | 812945.82 | 794636.09 | 655.43 | 13-DEC-06:07 | 655.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.215911E+12 | 0.157670E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 573565.97 | 565194.19 | 644.53 | 644.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.635136E+11 | 0.427777E+11 | 137169.52 | 67921.72 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 70943.83 | 276120.28 | 31-JAN-07:05 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49862.25 | 282706.91 | 02-FEB-07:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24216.99 | 235051.68 | 31-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 8832.37 | 244655.32 | 26-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 438.19 | 173782.62 | 02-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 96.22 | 19515.19 | 05-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2.34 | 9537.50 | 24-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 12.96 | 14749.84 | 07-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 761.82 | 208438.14 | 29-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4079.50 | 225912.41 | 26-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25655.32 | 265926.74 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52090.82 | 253794.43 | 11-DEC-07:07 |
Annual Sum or Average | 0.00 | 19621.48 | ||||
Minimum of Months | 0.00 | 0.00 | 2.34 | 9537.50 | ||
Maximum of Months | 0.00 | 0.00 | 70943.83 | 282706.91 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1955.34 | 7209.51 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 2006.59 | 7256.35 | 21-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2124.75 | 7245.52 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1900.47 | 7041.25 | 03-APR-11:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1858.67 | 6708.65 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1781.01 | 6265.15 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1533.17 | 5851.66 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1652.33 | 5617.77 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1557.45 | 5750.35 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1633.73 | 6122.65 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1773.50 | 6552.23 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1811.04 | 6933.66 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1797.80 | ||||
Minimum of Months | 0.00 | 0.00 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 2124.75 | 7256.35 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193371E+10 | 0.37 | 2843.58 | 02-JAN-05:01 | 0.84 |
February | 0.155822E+10 | 0.35 | 2843.58 | 01-FEB-07:01 | 0.85 |
March | 0.167419E+10 | 0.33 | 2176.97 | 24-MAR-14:30 | 0.73 |
April | 0.198252E+10 | 0.34 | 7307.51 | 18-APR-15:00 | 1.46 |
May | 0.290644E+10 | 0.39 | 8115.51 | 31-MAY-14:10 | 1.55 |
June | 0.501064E+10 | 0.53 | 11637.25 | 26-JUN-06:03 | 1.95 |
July | 0.586516E+10 | 0.56 | 11637.25 | 03-JUL-14:50 | 1.95 |
August | 0.620706E+10 | 0.58 | 11637.25 | 03-AUG-06:03 | 1.95 |
September | 0.409727E+10 | 0.47 | 10568.48 | 11-SEP-15:10 | 1.84 |
October | 0.205116E+10 | 0.33 | 4534.36 | 20-OCT-15:40 | 1.10 |
November | 0.165302E+10 | 0.32 | 3306.24 | 03-NOV-15:30 | 0.91 |
December | 0.160446E+10 | 0.33 | 2843.58 | 11-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.365438E+11 | 0.41 | |||
Minimum of Months | 0.155822E+10 | 0.32 | 2176.97 | 0.73 | |
Maximum of Months | 0.620706E+10 | 0.58 | 11637.25 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.204121E+10 | 0.40 | 3004.66 | 02-JAN-05:01 | 0.90 |
February | 0.159087E+10 | 0.35 | 3004.66 | 01-FEB-06:01 | 0.90 |
March | 0.163493E+10 | 0.33 | 3004.66 | 01-MAR-06:01 | 0.90 |
April | 0.198121E+10 | 0.35 | 8307.25 | 18-APR-15:00 | 1.64 |
May | 0.279660E+10 | 0.41 | 8455.44 | 30-MAY-15:30 | 1.66 |
June | 0.472469E+10 | 0.53 | 10953.06 | 26-JUN-06:03 | 1.95 |
July | 0.510488E+10 | 0.54 | 10435.34 | 03-JUL-15:10 | 1.89 |
August | 0.508300E+10 | 0.54 | 10953.06 | 04-AUG-07:05 | 1.94 |
September | 0.322889E+10 | 0.43 | 10063.45 | 07-SEP-16:00 | 1.85 |
October | 0.163908E+10 | 0.31 | 3376.49 | 20-OCT-15:20 | 0.96 |
November | 0.154708E+10 | 0.33 | 3004.66 | 13-NOV-07:01 | 0.90 |
December | 0.175327E+10 | 0.36 | 3004.66 | 01-DEC-07:01 | 0.90 |
Annual Sum or Average | 0.331257E+11 | 0.41 | |||
Minimum of Months | 0.154708E+10 | 0.31 | 3004.66 | 0.90 | |
Maximum of Months | 0.510488E+10 | 0.54 | 10953.06 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.253122E+10 | 0.47 | 2899.24 | 02-JAN-05:01 | 0.82 |
February | 0.192200E+10 | 0.40 | 2899.24 | 01-FEB-05:01 | 0.82 |
March | 0.179736E+10 | 0.35 | 2899.24 | 01-MAR-06:01 | 0.82 |
April | 0.196475E+10 | 0.34 | 7912.21 | 18-APR-15:00 | 1.46 |
May | 0.261616E+10 | 0.38 | 8313.34 | 30-MAY-15:30 | 1.51 |
June | 0.437295E+10 | 0.48 | 10814.75 | 26-JUN-15:40 | 1.78 |
July | 0.463250E+10 | 0.48 | 10139.09 | 03-JUL-15:20 | 1.71 |
August | 0.452968E+10 | 0.48 | 11563.70 | 04-AUG-07:15 | 1.85 |
September | 0.284192E+10 | 0.39 | 9618.18 | 07-SEP-15:50 | 1.65 |
October | 0.158807E+10 | 0.30 | 2899.24 | 16-OCT-05:01 | 0.82 |
November | 0.173778E+10 | 0.35 | 2899.24 | 10-NOV-07:01 | 0.82 |
December | 0.212214E+10 | 0.40 | 2899.24 | 01-DEC-06:01 | 0.82 |
Annual Sum or Average | 0.326565E+11 | 0.40 | |||
Minimum of Months | 0.158807E+10 | 0.30 | 2899.24 | 0.82 | |
Maximum of Months | 0.463250E+10 | 0.48 | 11563.70 | 1.85 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.121243E+10 | 0.109119E+10 | 1155.16 | 31-JAN-07:12 | 1039.64 | 1039.64 | 42.31 | 3.70 |
February | 0.774278E+09 | 0.696850E+09 | 1183.62 | 02-FEB-07:01 | 1065.26 | 1065.26 | 43.34 | 3.77 |
March | 0.458130E+09 | 0.412317E+09 | 972.27 | 06-MAR-07:01 | 875.05 | 875.05 | 45.00 | 2.93 |
April | 0.163995E+09 | 0.147596E+09 | 940.60 | 03-APR-06:01 | 846.54 | 846.54 | 45.04 | 2.65 |
May | 13241187.04 | 11917068.34 | 821.25 | 02-MAY-06:02 | 739.13 | 739.13 | 33.82 | 1.59 |
June | 3563920.82 | 3207528.74 | 168.80 | 02-JUN-06:05 | 151.92 | 151.92 | 46.70 | 0.18 |
July | 60227.67 | 54204.90 | 88.16 | 24-JUL-06:07 | 79.34 | 79.34 | 35.42 | 0.09 |
August | 349674.50 | 314707.05 | 139.73 | 16-AUG-06:06 | 125.76 | 125.76 | 36.76 | 0.15 |
September | 16918450.55 | 15226605.50 | 886.79 | 30-SEP-06:03 | 798.11 | 798.11 | 36.91 | 2.07 |
October | 81051758.11 | 72946582.30 | 901.31 | 16-OCT-06:02 | 811.18 | 811.18 | 37.42 | 2.22 |
November | 0.463526E+09 | 0.417174E+09 | 1001.82 | 28-NOV-07:19 | 901.64 | 901.64 | 42.19 | 3.12 |
December | 0.935935E+09 | 0.842342E+09 | 1074.21 | 11-DEC-08:45 | 966.79 | 966.79 | 43.39 | 3.45 |
Annual Sum or Average | 0.412348E+10 | 0.371113E+10 | ||||||
Minimum of Months | 60227.67 | 54204.90 | 88.16 | 79.34 | 79.34 | 33.82 | 0.09 | |
Maximum of Months | 0.121243E+10 | 0.109119E+10 | 1183.62 | 1065.26 | 1065.26 | 46.70 | 3.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.87 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.69 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.76 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.77 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.83 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.98 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.10 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.24 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.11 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.04 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.05 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.69 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.11 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 34.31 | 34.31 | 70943.83 | 276120.28 | 31-JAN-07:05 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 41.39 | 60.00 | 49862.25 | 282706.91 | 02-FEB-07:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 42.22 | 42.22 | 24216.99 | 235051.68 | 31-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.06 | 25.06 | 8832.37 | 244655.32 | 26-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.06 | 21.06 | 438.19 | 173782.62 | 02-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.24 | 47.24 | 96.22 | 19515.19 | 05-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 36.56 | 36.56 | 2.34 | 9537.50 | 24-JUL-06:07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 35.14 | 35.14 | 12.96 | 14749.84 | 07-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 34.50 | 34.50 | 761.82 | 208438.14 | 29-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.51 | 22.51 | 4079.50 | 225912.41 | 26-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.68 | 27.68 | 25655.32 | 265926.74 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.83 | 31.83 | 52090.82 | 253794.43 | 11-DEC-07:07 |
Annual Sum or Average | 0.00 | 19621.48 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.06 | 21.06 | 2.34 | 9537.50 | ||
Maximum of Months | 0.00 | 0.00 | 47.24 | 60.00 | 70943.83 | 282706.91 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.87 | 57.87 | 1955.34 | 7209.51 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 57.23 | 57.23 | 2006.59 | 7256.35 | 21-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.21 | 57.21 | 2124.75 | 7245.52 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.29 | 57.29 | 1900.47 | 7041.25 | 03-APR-11:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.95 | 57.95 | 1858.67 | 6708.65 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.60 | 57.60 | 1781.01 | 6265.15 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.75 | 57.75 | 1533.17 | 5851.66 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.85 | 57.85 | 1652.33 | 5617.77 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 1557.45 | 5750.35 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.90 | 56.90 | 1633.73 | 6122.65 | 31-OCT-11:13 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.66 | 57.66 | 1773.50 | 6552.23 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 1811.04 | 6933.66 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1797.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.90 | 56.90 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 57.95 | 57.95 | 2124.75 | 7256.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.581208E+11 | 0.00 | 0.00 | 0.193371E+10 | 0.00 | 0.00 |
February | 0.377148E+11 | 0.00 | 0.00 | 0.155822E+10 | 0.00 | 0.00 |
March | 0.216298E+11 | 0.00 | 0.00 | 0.171650E+10 | 0.00 | 0.00 |
April | 0.808082E+10 | 0.00 | 0.00 | 0.326401E+10 | 0.00 | 0.00 |
May | 0.752434E+09 | 0.00 | 0.00 | 0.636284E+10 | 0.00 | 0.00 |
June | 0.227024E+09 | 0.00 | 0.00 | 0.154797E+11 | 0.00 | 0.00 |
July | 6224097.20 | 0.00 | 0.00 | 0.204898E+11 | 0.00 | 0.00 |
August | 34357459.21 | 0.00 | 0.00 | 0.206204E+11 | 0.00 | 0.00 |
September | 0.627736E+09 | 0.00 | 0.00 | 0.101755E+11 | 0.00 | 0.00 |
October | 0.254589E+10 | 0.00 | 0.00 | 0.245428E+10 | 0.00 | 0.00 |
November | 0.181730E+11 | 0.00 | 0.00 | 0.166845E+10 | 0.00 | 0.00 |
December | 0.404226E+11 | 0.00 | 0.00 | 0.160446E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.188335E+12 | 0.00 | 0.00 | 0.873280E+11 | 0.00 | 0.00 |
Minimum of Months | 6224097.20 | 0.00 | 0.00 | 0.155822E+10 | 0.00 | 0.00 |
Maximum of Months | 0.581208E+11 | 0.00 | 0.00 | 0.206204E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.564673E+11 | 0.00 | 0.00 | 0.204121E+10 | 0.00 | 0.00 |
February | 0.352055E+11 | 0.00 | 0.00 | 0.159087E+10 | 0.00 | 0.00 |
March | 0.178919E+11 | 0.00 | 0.00 | 0.168826E+10 | 0.00 | 0.00 |
April | 0.586628E+10 | 0.00 | 0.00 | 0.336479E+10 | 0.00 | 0.00 |
May | 0.123653E+09 | 0.00 | 0.00 | 0.639196E+10 | 0.00 | 0.00 |
June | 2810155.32 | 0.00 | 0.00 | 0.147755E+11 | 0.00 | 0.00 |
July | 767399.86 | 0.00 | 0.00 | 0.185315E+11 | 0.00 | 0.00 |
August | 690856.44 | 0.00 | 0.00 | 0.177543E+11 | 0.00 | 0.00 |
September | 0.365878E+09 | 0.00 | 0.00 | 0.855181E+10 | 0.00 | 0.00 |
October | 0.271685E+10 | 0.00 | 0.00 | 0.199621E+10 | 0.00 | 0.00 |
November | 0.194627E+11 | 0.00 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
December | 0.415612E+11 | 0.00 | 0.00 | 0.175327E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.179666E+12 | 0.00 | 0.00 | 0.800072E+11 | 0.00 | 0.00 |
Minimum of Months | 690856.44 | 0.00 | 0.00 | 0.156751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.564673E+11 | 0.00 | 0.00 | 0.185315E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.767411E+11 | 0.00 | 0.00 | 0.253149E+10 | 0.00 | 0.00 |
February | 0.485483E+11 | 0.00 | 0.00 | 0.192216E+10 | 0.00 | 0.00 |
March | 0.258492E+11 | 0.00 | 0.00 | 0.184649E+10 | 0.00 | 0.00 |
April | 0.912636E+10 | 0.00 | 0.00 | 0.347836E+10 | 0.00 | 0.00 |
May | 0.285770E+09 | 0.00 | 0.00 | 0.641884E+10 | 0.00 | 0.00 |
June | 33301588.27 | 0.00 | 0.00 | 0.150320E+11 | 0.00 | 0.00 |
July | 704891.57 | 0.00 | 0.00 | 0.187532E+11 | 0.00 | 0.00 |
August | 634876.90 | 0.00 | 0.00 | 0.175791E+11 | 0.00 | 0.00 |
September | 0.101021E+10 | 0.00 | 0.00 | 0.831572E+10 | 0.00 | 0.00 |
October | 0.574571E+10 | 0.00 | 0.00 | 0.193768E+10 | 0.00 | 0.00 |
November | 0.293573E+11 | 0.00 | 0.00 | 0.175044E+10 | 0.00 | 0.00 |
December | 0.585430E+11 | 0.00 | 0.00 | 0.212236E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.255242E+12 | 0.00 | 0.00 | 0.816878E+11 | 0.00 | 0.00 |
Minimum of Months | 634876.90 | 0.00 | 0.00 | 0.175044E+10 | 0.00 | 0.00 |
Maximum of Months | 0.767411E+11 | 0.00 | 0.00 | 0.187532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193371E+10 | 0.00 | 0.581208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155822E+10 | 0.00 | 0.377148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167419E+10 | 0.161351E+09 | 0.216298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198252E+10 | 0.542952E+10 | 0.808082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290644E+10 | 0.147989E+11 | 0.752434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.501064E+10 | 0.460337E+11 | 0.227024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.586516E+10 | 0.661556E+11 | 6224097.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.620706E+10 | 0.648198E+11 | 34357459.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409727E+10 | 0.262104E+11 | 0.627736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205116E+10 | 0.165068E+10 | 0.254589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165302E+10 | 58292914.63 | 0.181730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160446E+10 | 0.00 | 0.404226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365438E+11 | 0.225318E+12 | 0.188335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155822E+10 | 0.00 | 6224097.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.620706E+10 | 0.661556E+11 | 0.581208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.204121E+10 | 0.00 | 0.564673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159087E+10 | 0.00 | 0.352055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163493E+10 | 0.204570E+09 | 0.178919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198121E+10 | 0.591315E+10 | 0.586628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279660E+10 | 0.154369E+11 | 0.123653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472469E+10 | 0.441780E+11 | 2810155.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510488E+10 | 0.605903E+11 | 767399.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.508300E+10 | 0.566922E+11 | 690856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.322889E+10 | 0.228398E+11 | 0.365878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163908E+10 | 0.144964E+10 | 0.271685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154708E+10 | 78277911.17 | 0.194627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175327E+10 | 0.00 | 0.415612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331257E+11 | 0.207383E+12 | 0.179666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154708E+10 | 0.00 | 690856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.510488E+10 | 0.605903E+11 | 0.564673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.253122E+10 | 1010801.22 | 0.767411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192200E+10 | 573565.97 | 0.485483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179736E+10 | 0.187738E+09 | 0.258492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196475E+10 | 0.647034E+10 | 0.912636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261616E+10 | 0.162732E+11 | 0.285770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.437295E+10 | 0.466582E+11 | 33301588.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.463250E+10 | 0.635136E+11 | 704891.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.452968E+10 | 0.580435E+11 | 634876.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.284192E+10 | 0.233118E+11 | 0.101021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158807E+10 | 0.140308E+10 | 0.574571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173778E+10 | 47523575.27 | 0.293573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212214E+10 | 812945.82 | 0.585430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326565E+11 | 0.215911E+12 | 0.255242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158807E+10 | 573565.97 | 634876.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463250E+10 | 0.635136E+11 | 0.767411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193371E+10 | 0.581208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155822E+10 | 0.377148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167419E+10 | 0.216298E+11 | 0.00 | 0.00 | 42314725.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198252E+10 | 0.808082E+10 | 0.00 | 0.00 | 0.128149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290644E+10 | 0.752434E+09 | 0.00 | 0.00 | 0.345640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.501064E+10 | 0.227024E+09 | 0.00 | 0.00 | 0.104691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.586516E+10 | 6224097.20 | 0.00 | 0.00 | 0.146247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.620706E+10 | 34357459.21 | 0.00 | 0.00 | 0.144134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409727E+10 | 0.627736E+09 | 0.00 | 0.00 | 0.607828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205116E+10 | 0.254589E+10 | 0.00 | 0.00 | 0.403117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165302E+10 | 0.181730E+11 | 0.00 | 0.00 | 15432475.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160446E+10 | 0.404226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365438E+11 | 0.188335E+12 | 0.00 | 0.00 | 0.507841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155822E+10 | 6224097.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.620706E+10 | 0.581208E+11 | 0.00 | 0.00 | 0.146247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.204121E+10 | 0.564673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159087E+10 | 0.352055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163493E+10 | 0.178919E+11 | 0.00 | 0.00 | 53325590.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198121E+10 | 0.586628E+10 | 0.00 | 0.00 | 0.138358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279660E+10 | 0.123653E+09 | 0.00 | 0.00 | 0.359536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472469E+10 | 2810155.32 | 0.00 | 0.00 | 0.100508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.510488E+10 | 767399.86 | 0.00 | 0.00 | 0.134266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.508300E+10 | 690856.44 | 0.00 | 0.00 | 0.126713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.322889E+10 | 0.365878E+09 | 0.00 | 0.00 | 0.532292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163908E+10 | 0.271685E+10 | 0.00 | 0.00 | 0.357132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154708E+10 | 0.194627E+11 | 0.00 | 0.00 | 20429173.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175327E+10 | 0.415612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331257E+11 | 0.179666E+12 | 0.00 | 0.00 | 0.468815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154708E+10 | 690856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.510488E+10 | 0.564673E+11 | 0.00 | 0.00 | 0.134266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.253122E+10 | 0.767411E+11 | 0.00 | 0.00 | 274031.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192200E+10 | 0.485483E+11 | 0.00 | 0.00 | 155712.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179736E+10 | 0.258492E+11 | 0.00 | 0.00 | 49131753.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196475E+10 | 0.912636E+10 | 0.00 | 0.00 | 0.151361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261616E+10 | 0.285770E+09 | 0.00 | 0.00 | 0.380269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.437295E+10 | 33301588.27 | 0.00 | 0.00 | 0.106590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.463250E+10 | 704891.57 | 0.00 | 0.00 | 0.141207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.452968E+10 | 634876.90 | 0.00 | 0.00 | 0.130494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.284192E+10 | 0.101021E+10 | 0.00 | 0.00 | 0.547380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158807E+10 | 0.574571E+10 | 0.00 | 0.00 | 0.349611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173778E+10 | 0.293573E+11 | 0.00 | 0.00 | 12660513.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212214E+10 | 0.585430E+11 | 0.00 | 0.00 | 220872.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326565E+11 | 0.255242E+12 | 0.00 | 0.00 | 0.490313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158807E+10 | 634876.90 | 0.00 | 0.00 | 155712.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.463250E+10 | 0.767411E+11 | 0.00 | 0.00 | 0.141207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202211E+11 | 0.00 | 0.00 | 435884.05 | 0.00 | 0.749188E+09 | 0.565312E+09 | 0.00 | 0.26 |
February | 0.143212E+11 | 0.00 | 0.00 | 2174547.28 | 0.00 | 68335862.68 | 0.314220E+10 | 0.00 | 0.28 |
March | 0.780918E+10 | 0.00 | 0.00 | 15334452.55 | 0.00 | 746034.77 | 0.105946E+11 | 0.00 | 0.37 |
April | 0.252427E+10 | 0.238170E+09 | 0.00 | 23952254.31 | 40285582.79 | 0.00 | 0.136532E+11 | 0.00 | 0.49 |
May | 0.835664E+09 | 0.279150E+09 | 0.00 | 37129557.70 | 61346185.64 | 0.00 | 0.171179E+11 | 0.00 | 0.93 |
June | 0.236958E+09 | 0.311859E+10 | 0.00 | 29901681.65 | 0.187285E+09 | 0.00 | 0.106501E+11 | 0.00 | 1.00 |
July | 0.300548E+09 | 0.551474E+10 | 0.00 | 20756308.86 | 0.606721E+09 | 0.00 | 0.438144E+10 | 0.00 | 1.00 |
August | 0.417795E+09 | 0.569665E+10 | 0.00 | 29114742.41 | 0.232298E+09 | 0.00 | 0.666568E+10 | 0.00 | 1.06 |
September | 0.849413E+09 | 0.528799E+09 | 0.00 | 37401880.70 | 91509540.30 | 0.00 | 0.157786E+11 | 0.00 | 0.90 |
October | 0.943251E+09 | 0.00 | 0.00 | 35984180.97 | 2947480.81 | 0.00 | 0.182219E+11 | 0.00 | 0.57 |
November | 0.714478E+10 | 0.00 | 0.00 | 17404562.45 | 0.00 | 6120848.46 | 0.108782E+11 | 0.00 | 0.41 |
December | 0.150963E+11 | 0.00 | 0.00 | 2999489.46 | 0.00 | 18290320.27 | 0.394046E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.707005E+11 | 0.153761E+11 | 0.00 | 0.252590E+09 | 0.122239E+10 | 0.842681E+09 | 0.115590E+12 | 0.00 | 0.63 |
Minimum of Months | 0.236958E+09 | 0.00 | 0.00 | 435884.05 | 0.00 | 0.00 | 0.565312E+09 | 0.00 | 0.26 |
Maximum of Months | 0.202211E+11 | 0.569665E+10 | 0.00 | 37401880.70 | 0.606721E+09 | 0.749188E+09 | 0.182219E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570261E+10 | 0.00 | 0.00 | 0.26 |
February | 0.144941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237166E+10 | 0.00 | 0.00 | 0.27 |
March | 0.140874E+11 | 0.00 | 0.00 | 990373.73 | 136256.36 | 0.272839E+09 | 0.139567E+10 | 0.00 | 0.31 |
April | 0.798363E+10 | 0.107816E+09 | 0.00 | 6410075.42 | 0.128960E+09 | 63326973.00 | 0.463585E+10 | 0.00 | 0.39 |
May | 0.287846E+10 | 0.227314E+09 | 0.00 | 17612316.42 | 0.124814E+09 | 0.00 | 0.950502E+10 | 0.00 | 0.66 |
June | 0.119317E+10 | 0.246542E+10 | 0.00 | 17462632.89 | 0.226123E+09 | 0.00 | 0.620083E+10 | 0.00 | 0.71 |
July | 0.532445E+09 | 0.430605E+10 | 0.00 | 11916430.32 | 0.548417E+09 | 0.00 | 0.259493E+10 | 0.00 | 0.72 |
August | 0.770676E+09 | 0.421645E+10 | 0.00 | 17045632.90 | 0.223884E+09 | 0.00 | 0.389203E+10 | 0.00 | 0.74 |
September | 0.283613E+10 | 0.430941E+09 | 0.00 | 16703959.29 | 62237426.77 | 0.00 | 0.759287E+10 | 0.00 | 0.59 |
October | 0.764088E+10 | 0.00 | 0.00 | 5563418.67 | 3469253.70 | 0.00 | 0.453897E+10 | 0.00 | 0.36 |
November | 0.114947E+11 | 0.00 | 0.00 | 1763031.12 | 0.00 | 0.885433E+09 | 0.197152E+10 | 0.00 | 0.31 |
December | 0.155490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259921E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.951953E+11 | 0.117540E+11 | 0.00 | 95467870.77 | 0.131804E+10 | 0.118951E+11 | 0.423277E+11 | 0.00 | 0.47 |
Minimum of Months | 0.532445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.157347E+11 | 0.430605E+10 | 0.00 | 17612316.42 | 0.548417E+09 | 0.570261E+10 | 0.950502E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.805779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113935E+11 | 0.00 | 0.00 | 0.25 |
February | 0.913382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635483E+10 | 0.00 | 0.00 | 0.26 |
March | 0.124764E+11 | 0.00 | 0.00 | 274354.38 | 0.00 | 0.199881E+10 | 0.480875E+09 | 0.00 | 0.31 |
April | 0.888894E+10 | 0.127083E+09 | 0.00 | 3901484.66 | 0.151317E+09 | 0.366312E+09 | 0.283950E+10 | 0.00 | 0.39 |
May | 0.419528E+10 | 0.179382E+09 | 0.00 | 14762513.63 | 81490852.80 | 0.00 | 0.774758E+10 | 0.00 | 0.65 |
June | 0.162608E+10 | 0.234471E+10 | 0.00 | 14344465.23 | 0.327728E+09 | 0.00 | 0.543346E+10 | 0.00 | 0.72 |
July | 0.758612E+09 | 0.444957E+10 | 0.00 | 9500499.41 | 0.677480E+09 | 0.00 | 0.227225E+10 | 0.00 | 0.77 |
August | 0.109654E+10 | 0.386014E+10 | 0.00 | 14235130.26 | 0.408754E+09 | 0.00 | 0.315288E+10 | 0.00 | 0.75 |
September | 0.422426E+10 | 0.352449E+09 | 0.00 | 10258268.46 | 0.100877E+09 | 9083052.18 | 0.485898E+10 | 0.00 | 0.56 |
October | 0.959134E+10 | 0.00 | 0.00 | 1151611.61 | 4348485.08 | 0.123985E+09 | 0.154469E+10 | 0.00 | 0.35 |
November | 0.937578E+10 | 0.00 | 313360.16 | 176391.45 | 8447.56 | 0.340017E+10 | 0.361576E+09 | 259288.70 | 0.30 |
December | 0.893986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751396E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.783647E+11 | 0.113133E+11 | 313360.16 | 68604719.08 | 0.175200E+10 | 0.311606E+11 | 0.286918E+11 | 259288.70 | 0.46 |
Minimum of Months | 0.758612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.124764E+11 | 0.444957E+10 | 313360.16 | 14762513.63 | 0.677480E+09 | 0.113935E+11 | 0.774758E+10 | 259288.70 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108405E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567374E+10 | 0.00 | 0.00 | 0.34 |
February | 0.225807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404148E+10 | 0.00 | 0.00 | 0.31 |
March | 0.117242E+10 | 0.00 | 0.00 | 6191.30 | 0.00 | 0.206696E+10 | 24219748.89 | 0.00 | 0.31 |
April | 0.148527E+10 | 48991121.18 | 0.00 | 581692.53 | 23084669.61 | 0.693732E+09 | 0.365061E+09 | 0.00 | 0.39 |
May | 0.109270E+10 | 56091545.50 | 0.00 | 3320824.91 | 16486940.31 | 16190324.29 | 0.153239E+10 | 0.00 | 0.72 |
June | 0.450070E+09 | 0.765539E+09 | 0.00 | 3724829.91 | 66860066.54 | 0.00 | 0.124436E+10 | 0.00 | 0.93 |
July | 0.174982E+09 | 0.137508E+10 | 0.00 | 2656119.71 | 0.120781E+09 | 0.00 | 0.571315E+09 | 0.00 | 0.98 |
August | 0.287121E+09 | 0.115173E+10 | 0.00 | 3315431.89 | 88330296.07 | 0.00 | 0.686054E+09 | 0.00 | 0.91 |
September | 0.113835E+10 | 0.103717E+09 | 0.00 | 1831981.66 | 20049698.08 | 73273069.29 | 0.699267E+09 | 0.00 | 0.59 |
October | 0.177704E+10 | 0.00 | 0.00 | 72496.88 | 915125.08 | 0.517536E+09 | 79858568.61 | 0.00 | 0.35 |
November | 0.858400E+09 | 0.00 | 79640.40 | 0.00 | 1777.76 | 0.218348E+10 | 0.00 | 90316.57 | 0.32 |
December | 42539540.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420631E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.881310E+10 | 0.350115E+10 | 79640.40 | 15509568.80 | 0.336510E+09 | 0.194727E+11 | 0.520252E+10 | 90316.57 | 0.54 |
Minimum of Months | 42539540.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.177704E+10 | 0.137508E+10 | 79640.40 | 3724829.91 | 0.120781E+09 | 0.567374E+10 | 0.153239E+10 | 90316.57 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193661E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453028E+10 | 0.00 | 0.00 | 0.44 |
February | 0.610015E+09 | 0.00 | 0.00 | 1400.48 | 0.00 | 0.315350E+10 | 4427980.50 | 0.00 | 0.45 |
March | 0.166762E+10 | 0.00 | 0.00 | 244739.72 | 0.00 | 0.153758E+10 | 0.198581E+09 | 0.00 | 0.52 |
April | 0.151877E+10 | 73804850.35 | 0.00 | 1245177.53 | 18449003.35 | 0.573559E+09 | 0.788093E+09 | 0.00 | 0.72 |
May | 0.971101E+09 | 69556964.95 | 0.00 | 4329868.68 | 10693083.51 | 4008381.72 | 0.205450E+10 | 0.00 | 1.27 |
June | 0.496937E+09 | 0.732910E+09 | 0.00 | 4319010.51 | 57477521.57 | 1339746.39 | 0.150420E+10 | 0.00 | 1.60 |
July | 0.154246E+09 | 0.126356E+10 | 0.00 | 3665820.05 | 0.114036E+09 | 0.00 | 0.769102E+09 | 0.00 | 1.74 |
August | 0.282215E+09 | 0.105711E+10 | 0.00 | 4208716.82 | 87666021.09 | 0.00 | 0.902706E+09 | 0.00 | 1.53 |
September | 0.103052E+10 | 0.110580E+09 | 0.00 | 3206266.10 | 17289291.79 | 43869248.91 | 0.106133E+10 | 0.00 | 1.10 |
October | 0.205176E+10 | 0.00 | 0.00 | 157427.20 | 978872.17 | 0.369745E+09 | 0.125265E+09 | 0.00 | 0.59 |
November | 0.101631E+10 | 0.00 | 78410.55 | 769.62 | 1269.93 | 0.197490E+10 | 3293427.10 | 67832.27 | 0.51 |
December | 0.276840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362238E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.102700E+11 | 0.330752E+10 | 78410.55 | 21379196.70 | 0.306591E+09 | 0.158112E+11 | 0.741150E+10 | 67832.27 | 0.91 |
Minimum of Months | 0.154246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.205176E+10 | 0.126356E+10 | 78410.55 | 4329868.68 | 0.114036E+09 | 0.453028E+10 | 0.205450E+10 | 67832.27 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131038E+10 | 0.00 | 0.00 | 865390.34 | 0.00 | 0.408093E+10 | 0.573453E+09 | 0.00 | 0.36 |
February | 0.147620E+10 | 0.00 | 0.00 | 1230775.29 | 0.00 | 0.265872E+10 | 0.652387E+09 | 0.00 | 0.38 |
March | 0.170145E+10 | 0.00 | 0.00 | 2823864.55 | 0.00 | 0.162652E+10 | 0.152131E+10 | 0.00 | 0.50 |
April | 0.161998E+10 | 0.135672E+09 | 0.00 | 3668976.60 | 18692399.35 | 0.647190E+09 | 0.196926E+10 | 0.00 | 0.69 |
May | 0.128867E+10 | 86055125.59 | 0.00 | 5508624.25 | 14258491.01 | 19545456.30 | 0.250191E+10 | 0.00 | 1.04 |
June | 0.626652E+09 | 0.897761E+09 | 0.00 | 4271635.45 | 90434581.56 | 406915.97 | 0.153267E+10 | 0.00 | 1.16 |
July | 0.263480E+09 | 0.168023E+10 | 0.00 | 3355132.24 | 0.143473E+09 | 0.00 | 0.697951E+09 | 0.00 | 1.26 |
August | 0.354584E+09 | 0.151692E+10 | 0.00 | 5591109.17 | 85027203.80 | 0.00 | 0.116394E+10 | 0.00 | 1.32 |
September | 0.115615E+10 | 0.229864E+09 | 0.00 | 6268491.18 | 9850806.05 | 58275252.42 | 0.203607E+10 | 0.00 | 1.11 |
October | 0.172061E+10 | 698512.01 | 0.00 | 5003442.79 | 589860.50 | 0.306866E+09 | 0.243578E+10 | 0.00 | 0.71 |
November | 0.159184E+10 | 0.00 | 96105.04 | 1127981.92 | 2285.98 | 0.173836E+10 | 0.685412E+09 | 95094.38 | 0.46 |
December | 0.774838E+09 | 0.00 | 0.00 | 1431330.27 | 0.00 | 0.360391E+10 | 0.805415E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.138848E+11 | 0.454720E+10 | 96105.04 | 41146754.04 | 0.362328E+09 | 0.147407E+11 | 0.165755E+11 | 95094.38 | 0.78 |
Minimum of Months | 0.263480E+09 | 0.00 | 0.00 | 865390.34 | 0.00 | 0.00 | 0.573453E+09 | 0.00 | 0.36 |
Maximum of Months | 0.172061E+10 | 0.168023E+10 | 96105.04 | 6268491.18 | 0.143473E+09 | 0.408093E+10 | 0.250191E+10 | 95094.38 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.476824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473602E+10 | 0.00 | 0.00 | 0.49 |
February | 0.726025E+09 | 0.00 | 0.00 | 80608.46 | 0.00 | 0.342797E+10 | 66015179.53 | 0.00 | 0.50 |
March | 0.152269E+10 | 0.00 | 0.00 | 508354.48 | 0.00 | 0.189681E+10 | 0.316550E+09 | 0.00 | 0.58 |
April | 0.152108E+10 | 54651796.02 | 0.00 | 2027685.60 | 26076889.88 | 0.639154E+09 | 0.115139E+10 | 0.00 | 0.82 |
May | 0.140983E+10 | 57073738.63 | 0.00 | 3721002.32 | 19409965.18 | 20177365.16 | 0.161237E+10 | 0.00 | 1.28 |
June | 0.623879E+09 | 0.655486E+09 | 0.00 | 3528303.33 | 71712708.05 | 1820257.16 | 0.119379E+10 | 0.00 | 1.50 |
July | 0.240524E+09 | 0.139868E+10 | 0.00 | 3177723.60 | 95311975.15 | 0.00 | 0.537919E+09 | 0.00 | 1.59 |
August | 0.352535E+09 | 0.102718E+10 | 0.00 | 4038493.51 | 97295802.65 | 0.00 | 0.763435E+09 | 0.00 | 1.53 |
September | 0.133259E+10 | 0.120086E+09 | 0.00 | 2577108.80 | 17266454.48 | 91243090.01 | 0.803285E+09 | 0.00 | 1.11 |
October | 0.188043E+10 | 0.00 | 0.00 | 938798.82 | 1061706.64 | 0.462795E+09 | 0.554421E+09 | 0.00 | 0.69 |
November | 0.113228E+10 | 0.00 | 84387.42 | 100012.39 | 2012.69 | 0.207698E+10 | 69534973.07 | 66809.58 | 0.56 |
December | 0.444919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375673E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.116636E+11 | 0.331315E+10 | 84387.42 | 20698091.32 | 0.328138E+09 | 0.171097E+11 | 0.706871E+10 | 66809.58 | 0.93 |
Minimum of Months | 0.240524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.188043E+10 | 0.139868E+10 | 84387.42 | 4038493.51 | 97295802.65 | 0.473602E+10 | 0.161237E+10 | 66809.58 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587234E+10 | 0.00 | 0.00 | 0.34 |
February | 0.180143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431409E+10 | 0.00 | 0.00 | 0.31 |
March | 0.109674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242148E+10 | 0.00 | 0.00 | 0.32 |
April | 0.151219E+10 | 16032963.72 | 0.00 | 80458.73 | 26295656.50 | 0.916194E+09 | 81659330.13 | 0.00 | 0.34 |
May | 0.165710E+10 | 38997214.55 | 0.00 | 874687.49 | 14336252.96 | 11866944.52 | 0.497019E+09 | 0.00 | 0.53 |
June | 0.550129E+09 | 0.566858E+09 | 0.00 | 2611433.55 | 42871368.49 | 0.00 | 0.847240E+09 | 0.00 | 0.69 |
July | 0.165927E+09 | 0.997358E+09 | 0.00 | 2300798.92 | 0.132162E+09 | 0.00 | 0.493773E+09 | 0.00 | 0.76 |
August | 0.278034E+09 | 0.103077E+10 | 0.00 | 3058171.97 | 64161242.50 | 0.00 | 0.691997E+09 | 0.00 | 0.79 |
September | 0.119493E+10 | 0.102195E+09 | 0.00 | 2137292.61 | 19728489.41 | 7237102.35 | 0.900529E+09 | 0.00 | 0.58 |
October | 0.241502E+10 | 0.00 | 0.00 | 99012.61 | 620283.90 | 66099514.70 | 0.138793E+09 | 0.00 | 0.36 |
November | 0.137566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187201E+10 | 0.00 | 0.00 | 0.32 |
December | 87431877.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432103E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.106212E+11 | 0.275221E+10 | 0.00 | 11161855.88 | 0.300175E+09 | 0.198023E+11 | 0.365101E+10 | 0.00 | 0.47 |
Minimum of Months | 87431877.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.241502E+10 | 0.103077E+10 | 0.00 | 3058171.97 | 0.132162E+09 | 0.587234E+10 | 0.900529E+09 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436629E+10 | 0.00 | 0.00 | 0.41 |
February | 0.530772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316337E+10 | 0.00 | 0.00 | 0.41 |
March | 0.152620E+10 | 0.00 | 0.00 | 46093.05 | 0.00 | 0.150133E+10 | 53013746.30 | 0.00 | 0.44 |
April | 0.138656E+10 | 43788120.70 | 0.00 | 662717.13 | 7654826.62 | 0.548184E+09 | 0.399010E+09 | 0.00 | 0.53 |
May | 0.934279E+09 | 55828423.22 | 0.00 | 2649931.45 | 8177893.35 | 207791.68 | 0.135178E+10 | 0.00 | 0.92 |
June | 0.433167E+09 | 0.608424E+09 | 0.00 | 3691060.04 | 26239930.52 | 0.00 | 0.120457E+10 | 0.00 | 1.26 |
July | 0.115900E+09 | 0.102632E+10 | 0.00 | 3420146.73 | 94476714.92 | 0.00 | 0.699855E+09 | 0.00 | 1.40 |
August | 0.179900E+09 | 0.997462E+09 | 0.00 | 4313877.37 | 46069588.54 | 0.00 | 0.978112E+09 | 0.00 | 1.34 |
September | 0.756031E+09 | 0.112489E+09 | 0.00 | 3910038.20 | 15542550.52 | 845301.93 | 0.144466E+10 | 0.00 | 1.03 |
October | 0.191615E+10 | 0.00 | 0.00 | 457729.92 | 549265.32 | 25882901.62 | 0.403244E+09 | 0.00 | 0.51 |
November | 0.132185E+10 | 0.00 | 0.00 | 18044.46 | 0.00 | 0.145207E+10 | 39647997.86 | 0.00 | 0.44 |
December | 0.434467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326937E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.972938E+10 | 0.284431E+10 | 0.00 | 19169638.36 | 0.198711E+09 | 0.143275E+11 | 0.657389E+10 | 0.00 | 0.76 |
Minimum of Months | 0.115900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.191615E+10 | 0.102632E+10 | 0.00 | 4313877.37 | 94476714.92 | 0.436629E+10 | 0.144466E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815289E+10 | 0.00 | 0.00 | 0.48 |
February | 0.572069E+09 | 0.00 | 0.00 | 49007.69 | 0.00 | 0.544504E+10 | 46513957.05 | 0.00 | 0.42 |
March | 0.107932E+10 | 0.00 | 0.00 | 313437.16 | 0.00 | 0.356429E+10 | 0.197890E+09 | 0.00 | 0.43 |
April | 0.108020E+10 | 95607308.21 | 0.00 | 755546.03 | 7870744.31 | 0.182220E+10 | 0.445862E+09 | 0.00 | 0.47 |
May | 0.161675E+10 | 71079014.77 | 0.00 | 1301051.61 | 12614555.56 | 0.325083E+09 | 0.552292E+09 | 0.00 | 0.64 |
June | 0.718229E+09 | 0.733905E+09 | 0.00 | 2230423.64 | 52067897.69 | 0.122612E+09 | 0.646050E+09 | 0.00 | 0.78 |
July | 0.251041E+09 | 0.131091E+10 | 0.00 | 2346255.90 | 0.146790E+09 | 2860841.72 | 0.454924E+09 | 0.00 | 0.91 |
August | 0.318544E+09 | 0.150344E+10 | 0.00 | 4616484.34 | 53307940.78 | 23468721.52 | 0.933221E+09 | 0.00 | 1.09 |
September | 0.106746E+10 | 0.245406E+09 | 0.00 | 5287019.98 | 12152901.32 | 0.231177E+09 | 0.156378E+10 | 0.00 | 0.96 |
October | 0.164976E+10 | 382248.56 | 0.00 | 2667610.74 | 403879.40 | 0.626147E+09 | 0.153909E+10 | 0.00 | 0.57 |
November | 0.127939E+10 | 0.00 | 0.00 | 580183.18 | 0.00 | 0.285188E+10 | 0.377699E+09 | 0.00 | 0.45 |
December | 0.682928E+09 | 0.00 | 0.00 | 5150.78 | 0.00 | 0.575636E+10 | 11342500.47 | 0.00 | 0.42 |
Annual Sum or Average | 0.106706E+11 | 0.396072E+10 | 0.00 | 20152171.04 | 0.285208E+09 | 0.289240E+11 | 0.676866E+10 | 0.00 | 0.64 |
Minimum of Months | 0.251041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2860841.72 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.164976E+10 | 0.150344E+10 | 0.00 | 5287019.98 | 0.146790E+09 | 0.815289E+10 | 0.156378E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296854E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464635E+10 | 0.00 | 0.00 | 0.44 |
February | 0.559643E+09 | 0.00 | 0.00 | 12763.33 | 0.00 | 0.348710E+10 | 14955752.38 | 0.00 | 0.45 |
March | 0.138212E+10 | 0.00 | 0.00 | 106641.36 | 0.00 | 0.178557E+10 | 98779554.23 | 0.00 | 0.47 |
April | 0.146080E+10 | 31957298.45 | 0.00 | 950606.78 | 16526315.16 | 0.517333E+09 | 0.550395E+09 | 0.00 | 0.57 |
May | 0.133875E+10 | 45248849.41 | 0.00 | 1847776.76 | 13266184.59 | 7814554.76 | 0.843138E+09 | 0.00 | 0.88 |
June | 0.522370E+09 | 0.540822E+09 | 0.00 | 3039953.01 | 34022888.63 | 0.00 | 0.913881E+09 | 0.00 | 1.15 |
July | 0.150904E+09 | 0.111579E+10 | 0.00 | 2878216.52 | 73683423.74 | 0.00 | 0.500659E+09 | 0.00 | 1.25 |
August | 0.215495E+09 | 0.100396E+10 | 0.00 | 3968881.17 | 38509752.09 | 0.00 | 0.830249E+09 | 0.00 | 1.32 |
September | 0.100147E+10 | 0.124454E+09 | 0.00 | 2975321.78 | 14357549.85 | 10518291.08 | 0.105432E+10 | 0.00 | 0.98 |
October | 0.200163E+10 | 0.00 | 0.00 | 954677.34 | 582740.47 | 31374431.22 | 0.568120E+09 | 0.00 | 0.58 |
November | 0.146273E+10 | 0.00 | 0.00 | 81927.63 | 0.00 | 0.148517E+10 | 55261410.71 | 0.00 | 0.48 |
December | 0.455329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347320E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.108481E+11 | 0.286223E+10 | 0.00 | 16816765.70 | 0.190949E+09 | 0.154444E+11 | 0.542976E+10 | 0.00 | 0.75 |
Minimum of Months | 0.150904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.200163E+10 | 0.111579E+10 | 0.00 | 3968881.17 | 73683423.74 | 0.464635E+10 | 0.105432E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541449E+10 | 0.00 | 0.00 | 0.32 |
February | 0.524778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377198E+10 | 0.00 | 0.00 | 0.30 |
March | 0.170615E+10 | 0.00 | 0.00 | 17242.17 | 28745.85 | 0.162669E+10 | 35009745.14 | 0.00 | 0.31 |
April | 0.182085E+10 | 49925362.11 | 0.00 | 708976.90 | 13933323.26 | 0.394492E+09 | 0.411655E+09 | 0.00 | 0.39 |
May | 0.958210E+09 | 72861011.35 | 0.00 | 3749343.07 | 24735004.00 | 281024.67 | 0.172097E+10 | 0.00 | 0.72 |
June | 0.339409E+09 | 0.809519E+09 | 0.00 | 4290265.56 | 47171267.52 | 0.00 | 0.137977E+10 | 0.00 | 0.91 |
July | 0.142098E+09 | 0.132088E+10 | 0.00 | 2979520.37 | 0.111378E+09 | 0.00 | 0.605280E+09 | 0.00 | 0.92 |
August | 0.256524E+09 | 0.125882E+10 | 0.00 | 3434180.17 | 50822115.69 | 0.00 | 0.746663E+09 | 0.00 | 0.88 |
September | 0.111673E+10 | 0.127620E+09 | 0.00 | 2309818.52 | 13176504.59 | 18271312.98 | 0.937261E+09 | 0.00 | 0.60 |
October | 0.221490E+10 | 0.00 | 0.00 | 206635.99 | 731904.53 | 0.138006E+09 | 0.171186E+09 | 0.00 | 0.35 |
November | 0.128752E+10 | 0.00 | 0.00 | 7561.08 | 0.00 | 0.184043E+10 | 23250832.56 | 0.00 | 0.32 |
December | 0.126853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413248E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.106343E+11 | 0.363963E+10 | 0.00 | 17703543.83 | 0.261977E+09 | 0.173371E+11 | 0.603104E+10 | 0.00 | 0.53 |
Minimum of Months | 0.126853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.221490E+10 | 0.132088E+10 | 0.00 | 4290265.56 | 0.111378E+09 | 0.541449E+10 | 0.172097E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488957E+10 | 0.00 | 0.00 | 0.48 |
February | 0.987445E+09 | 0.00 | 0.00 | 22060.75 | 0.00 | 0.311594E+10 | 16289830.94 | 0.00 | 0.48 |
March | 0.199150E+10 | 0.00 | 0.00 | 403012.25 | 31329.55 | 0.138582E+10 | 0.311427E+09 | 0.00 | 0.55 |
April | 0.182339E+10 | 65985823.53 | 0.00 | 1514781.78 | 11916307.40 | 0.371816E+09 | 0.881058E+09 | 0.00 | 0.73 |
May | 0.926827E+09 | 84891895.40 | 0.00 | 4697721.17 | 17687971.24 | 260702.07 | 0.218626E+10 | 0.00 | 1.27 |
June | 0.479592E+09 | 0.755330E+09 | 0.00 | 4526423.67 | 39329743.85 | 0.00 | 0.153516E+10 | 0.00 | 1.53 |
July | 0.150417E+09 | 0.119861E+10 | 0.00 | 3876956.32 | 0.105129E+09 | 0.00 | 0.792376E+09 | 0.00 | 1.61 |
August | 0.271959E+09 | 0.109649E+10 | 0.00 | 4223207.55 | 60386915.89 | 0.00 | 0.986855E+09 | 0.00 | 1.46 |
September | 0.108643E+10 | 0.124323E+09 | 0.00 | 3776553.12 | 12386137.52 | 10651827.78 | 0.130712E+10 | 0.00 | 1.12 |
October | 0.235990E+10 | 0.00 | 0.00 | 404120.26 | 797688.67 | 0.119057E+09 | 0.298953E+09 | 0.00 | 0.62 |
November | 0.145759E+10 | 0.00 | 0.00 | 34593.12 | 0.00 | 0.184382E+10 | 22471860.29 | 0.00 | 0.54 |
December | 0.543137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374120E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.124012E+11 | 0.332564E+10 | 0.00 | 23479429.99 | 0.247665E+09 | 0.154781E+11 | 0.833797E+10 | 0.00 | 0.91 |
Minimum of Months | 0.150417E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.235990E+10 | 0.119861E+10 | 0.00 | 4697721.17 | 0.105129E+09 | 0.488957E+10 | 0.218626E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145162E+10 | 0.00 | 0.00 | 1329052.31 | 0.00 | 0.388473E+10 | 0.846610E+09 | 0.00 | 0.36 |
February | 0.177239E+10 | 0.00 | 0.00 | 1600989.80 | 0.00 | 0.230628E+10 | 0.898037E+09 | 0.00 | 0.38 |
March | 0.197068E+10 | 34321.15 | 0.00 | 3502296.82 | 15293.19 | 0.129281E+10 | 0.175973E+10 | 0.00 | 0.51 |
April | 0.184558E+10 | 0.133303E+09 | 0.00 | 4045023.21 | 11948236.95 | 0.357934E+09 | 0.199560E+10 | 0.00 | 0.67 |
May | 0.106528E+10 | 0.117867E+09 | 0.00 | 5913589.61 | 19570341.03 | 1021470.54 | 0.262564E+10 | 0.00 | 1.02 |
June | 0.493294E+09 | 0.952556E+09 | 0.00 | 4696686.37 | 58731696.84 | 0.00 | 0.157014E+10 | 0.00 | 1.09 |
July | 0.214479E+09 | 0.160331E+10 | 0.00 | 3441776.11 | 0.129754E+09 | 0.00 | 0.669195E+09 | 0.00 | 1.13 |
August | 0.325231E+09 | 0.164121E+10 | 0.00 | 5274441.08 | 50590067.77 | 0.00 | 0.111822E+10 | 0.00 | 1.24 |
September | 0.102010E+10 | 0.266029E+09 | 0.00 | 6986761.72 | 10559879.80 | 14056232.57 | 0.235708E+10 | 0.00 | 1.10 |
October | 0.174405E+10 | 431586.01 | 0.00 | 6617042.29 | 679826.99 | 92307611.32 | 0.299883E+10 | 0.00 | 0.76 |
November | 0.192594E+10 | 0.00 | 0.00 | 1720209.56 | 0.00 | 0.130342E+10 | 0.100415E+10 | 0.00 | 0.47 |
December | 0.937461E+09 | 0.00 | 0.00 | 1931899.68 | 0.00 | 0.341282E+10 | 0.110861E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.147661E+11 | 0.471474E+10 | 0.00 | 47059768.56 | 0.281849E+09 | 0.126654E+11 | 0.189518E+11 | 0.00 | 0.76 |
Minimum of Months | 0.214479E+09 | 0.00 | 0.00 | 1329052.31 | 0.00 | 0.00 | 0.669195E+09 | 0.00 | 0.36 |
Maximum of Months | 0.197068E+10 | 0.164121E+10 | 0.00 | 6986761.72 | 0.129754E+09 | 0.388473E+10 | 0.299883E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.594188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484325E+10 | 0.00 | 0.00 | 0.49 |
February | 0.104086E+10 | 0.00 | 0.00 | 97806.39 | 0.00 | 0.323526E+10 | 76788390.45 | 0.00 | 0.50 |
March | 0.195280E+10 | 0.00 | 0.00 | 605855.04 | 32113.47 | 0.152518E+10 | 0.351317E+09 | 0.00 | 0.57 |
April | 0.182908E+10 | 54333943.86 | 0.00 | 2206432.13 | 15814600.20 | 0.329066E+09 | 0.114808E+10 | 0.00 | 0.79 |
May | 0.122795E+10 | 77298185.37 | 0.00 | 3881800.13 | 26419413.35 | 4053773.46 | 0.165720E+10 | 0.00 | 1.22 |
June | 0.574748E+09 | 0.701248E+09 | 0.00 | 3739131.08 | 44786216.37 | 0.00 | 0.114988E+10 | 0.00 | 1.40 |
July | 0.236190E+09 | 0.131083E+10 | 0.00 | 3089957.67 | 72489534.82 | 0.00 | 0.477263E+09 | 0.00 | 1.41 |
August | 0.335038E+09 | 0.111809E+10 | 0.00 | 3720087.48 | 54609771.93 | 0.00 | 0.739355E+09 | 0.00 | 1.41 |
September | 0.133418E+10 | 0.145981E+09 | 0.00 | 2746895.13 | 11380994.91 | 24279693.05 | 0.899968E+09 | 0.00 | 1.06 |
October | 0.222544E+10 | 0.00 | 0.00 | 1187157.67 | 817648.23 | 0.137651E+09 | 0.654112E+09 | 0.00 | 0.69 |
November | 0.161461E+10 | 0.00 | 0.00 | 116027.10 | 0.00 | 0.174973E+10 | 74011719.69 | 0.00 | 0.56 |
December | 0.585380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381580E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.135505E+11 | 0.340778E+10 | 0.00 | 21391149.81 | 0.226350E+09 | 0.156643E+11 | 0.722798E+10 | 0.00 | 0.88 |
Minimum of Months | 0.236190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.222544E+10 | 0.131083E+10 | 0.00 | 3881800.13 | 72489534.82 | 0.484325E+10 | 0.165720E+10 | 0.00 | 1.41 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:11
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.211875E+12 | 0.249445E+11 | 0.00 | 0.163115E+12 | 0.634037E+11 |
February | 0.229366E+12 | 0.189215E+11 | 0.00 | 0.152900E+12 | 0.471229E+11 |
March | 0.327927E+12 | 0.169519E+11 | 0.00 | 0.182312E+12 | 0.330880E+11 |
April | 0.379734E+12 | 0.102978E+11 | 0.00 | 0.189784E+12 | 0.349114E+11 |
May | 0.429222E+12 | 0.576323E+10 | 0.00 | 0.221858E+12 | 0.581034E+11 |
June | 0.442316E+12 | 0.109581E+10 | 0.00 | 0.106152E+12 | 0.168213E+12 |
July | 0.444412E+12 | -396831890.6 | 0.00 | 0.338204E+11 | 0.232436E+12 |
August | 0.389196E+12 | 0.682643E+09 | 0.00 | 0.783675E+11 | 0.219713E+12 |
September | 0.279756E+12 | 0.482664E+10 | 0.00 | 0.179977E+12 | 0.904589E+11 |
October | 0.222162E+12 | 0.104811E+11 | 0.00 | 0.211550E+12 | 0.120700E+11 |
November | 0.144255E+12 | 0.157026E+11 | 0.00 | 0.169007E+12 | 0.296243E+11 |
December | 0.122930E+12 | 0.208774E+11 | 0.00 | 0.158752E+12 | 0.547240E+11 |
Annual Sum or Average | 0.362315E+13 | 0.130148E+12 | 0.00 | 0.184760E+13 | 0.104387E+13 |
Minimum of Months | 0.122930E+12 | -396831890.6 | 0.00 | 0.338204E+11 | 0.120700E+11 |
Maximum of Months | 0.444412E+12 | 0.249445E+11 | 0.00 | 0.221858E+12 | 0.232436E+12 |