Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:20:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1407.63 | 282.53 | 282.53 |
Net Site Energy | 1407.63 | 282.53 | 282.53 |
Total Source Energy | 4436.25 | 890.42 | 890.42 |
Net Source Energy | 4436.25 | 890.42 | 890.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 10.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1397.21 | 10.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 10.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 159.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 90.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 10.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 159.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 90.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.00 | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 280.44 | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.00 | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 280.44 | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1397.208 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1397.208 | 100.00 |
Total On-Site and Utility Electric Sources | 1397.208 | 100.00 |
Total Electricity End Uses | 1397.208 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 37.83 |
Time Setpoint Not Met During Occupied Cooling | 111.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 491.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:00 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 89287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58550.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41666.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12592.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4514.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 144422.42 | 89287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 89287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 58550.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 53.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12592.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4514.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 11.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 954.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 286.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 154.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4424.96 | 11.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 888.16 | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 888.16 | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.70 | 0.277107 | 0.282000 | 0.762687 | 0.738953 | 0.500000 | 0.001375 | 0.000096 | 0.762687 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.18 | 0.344173 | 0.342000 | 0.744723 | 0.917794 | 0.500000 | 0.001107 | 0.000154 | 0.744723 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.23 | 0.335931 | 0.346000 | 0.771919 | 0.895815 | 0.500000 | 0.001134 | 0.000238 | 0.824812 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.635250 | 0.248708 | 0.256000 | 0.162624 | 0.663221 | 0.500000 | 0.001532 | 0.000103 | 0.341183 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.680079 | 0.147074 | 0.200000 | 0.136016 | 0.392197 | 0.500000 | 0.002591 | 0.000067 | 0.223025 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.856880 | 0.184380 | 0.200000 | 0.171376 | 0.491681 | 0.500000 | 0.002066 | 0.000103 | 0.341771 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.758051 | 0.131937 | 0.200000 | 0.151610 | 0.351833 | 0.500000 | 0.002888 | 0.000067 | 0.222452 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.507998 | 0.311009 | 0.316000 | 0.160527 | 0.829356 | 0.500000 | 0.001225 | 0.000071 | 0.244724 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.578921 | 0.172773 | 0.200000 | 0.115784 | 0.460727 | 0.500000 | 0.002205 | 0.000047 | 0.163622 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.704130 | 0.224379 | 0.228000 | 0.160542 | 0.598343 | 0.500000 | 0.001698 | 0.000071 | 0.246104 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.616729 | 0.162170 | 0.200000 | 0.123346 | 0.432454 | 0.500000 | 0.002349 | 0.000047 | 0.162720 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.559366 | 0.282448 | 0.280000 | 0.156622 | 0.753194 | 0.500000 | 0.001349 | 0.000077 | 0.265629 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.670990 | 0.149066 | 0.200000 | 0.134198 | 0.397509 | 0.500000 | 0.002556 | 0.000051 | 0.176500 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.776976 | 0.203342 | 0.202000 | 0.156949 | 0.542245 | 0.500000 | 0.001874 | 0.000077 | 0.266595 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.699007 | 0.143082 | 0.200000 | 0.139801 | 0.381551 | 0.500000 | 0.002663 | 0.000051 | 0.175630 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 10989.48 | 0.000096 | 232.03 |
CORE_MID VAV BOX REHEAT COIL | 17609.21 | 0.000154 | 412.26 |
CORE_TOP VAV BOX REHEAT COIL | 27235.18 | 0.000238 | 719.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11789.60 | 0.000103 | 316.48 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7701.25 | 0.000067 | 206.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11809.42 | 0.000103 | 317.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7681.86 | 0.000067 | 206.17 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8065.26 | 0.000071 | 212.86 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5391.40 | 0.000047 | 142.28 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8110.59 | 0.000071 | 214.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5361.77 | 0.000047 | 141.50 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8752.23 | 0.000077 | 230.97 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5814.74 | 0.000051 | 153.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8783.96 | 0.000077 | 231.80 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5786.16 | 0.000051 | 152.69 |
PACU_VAV_BOT HEATING COIL | 11123.30 | 0.000097 | 194.04 |
PACU_VAV_MID HEATING COIL | 12155.44 | 0.000106 | 210.19 |
PACU_VAV_TOP HEATING COIL | 10417.74 | 0.000091 | 182.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.56 | 1.32 | 5.11 | 1.32 | 4.55 | 4.55 | 0.300000 | 0.290695 | 4.55 |
PACU_VAV_MID | 2.44 | 1.33 | 4.88 | 1.33 | 4.20 | 4.20 | 0.300000 | 0.317552 | 4.20 |
PACU_VAV_TOP | 2.58 | 1.39 | 5.16 | 2.02 | 4.79 | 4.79 | 0.300000 | 0.421366 | 4.79 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.55 |
PACU_VAV_MID_OA_CONTROLLER | 4.20 |
PACU_VAV_TOP_OA_CONTROLLER | 4.79 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.55 | 81809.21 | 0.800544 | 1.52 | 27267.01 | 0.800544 |
PACU_VAV_MID COOLING COIL | 4.20 | 76163.17 | 0.800252 | 1.40 | 25385.18 | 0.800252 |
PACU_VAV_TOP COOLING COIL | 4.79 | 85584.54 | 0.800647 | 1.60 | 28525.33 | 0.800647 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.55 |
PACU_VAV_MID FAN | 4.20 |
PACU_VAV_TOP FAN | 4.79 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000097 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000106 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000091 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001615 | 0.193773 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.001615 | 486.30 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 184578.61 | 184578.61 | 0.001615 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2885E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3354E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8753E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9161E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4345E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4669E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1053 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9111E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1180 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3761E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8297E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1553E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2871E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3300E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8738E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9102E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4332E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4626E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3213E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5363E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8996E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2524E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2517E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1439E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0666E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0835E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7449E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7570E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7228E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7269E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9605E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9981E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4878E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5172E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1732E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1926E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7561E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5682E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1301E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1982E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9552E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2731E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9610E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9984E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4884E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5182E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1742E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1954E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7688E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7436E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4468E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5063E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6566E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3288E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3689E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4140E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1177E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1660E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9798E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9999E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1052 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.0331E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1159 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5820E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3461E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0350E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1820E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4577E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7823E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1866E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1561E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0877E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1580E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0630E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4889E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6260E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3127E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2199E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6162E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6567E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3130E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4305E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5496E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2653E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1052 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.0324E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1159 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5813E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3456E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0345E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1820E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4575E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7822E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1864E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1558E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0874E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1581E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0629E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4890E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6259E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3125E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2197E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6161E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6566E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3129E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4303E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5493E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2651E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36844.81483 | 36844.81483 | 2.70456 | 2.70456 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3452.91539 | 3452.91539 | 0.14892 | 0.42469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29692.44750 | 29692.44750 | 2.17755 | 2.17755 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10250.15312 | 10250.15312 | 0.44003 | 0.44003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30135.18140 | 30135.18140 | 2.23098 | 2.23098 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 19084.71760 | 19084.71760 | 0.82481 | 0.82481 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8580.84267 | 8580.84267 | 0.63525 | 0.63525 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8545.46242 | 8545.46242 | 0.34118 | 0.34118 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9186.44221 | 9186.44221 | 0.68008 | 0.68008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5580.61035 | 5580.61035 | 0.22303 | 0.22303 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11574.61025 | 11574.61025 | 0.85688 | 0.85688 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8559.68550 | 8559.68550 | 0.34177 | 0.34177 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10239.68444 | 10239.68444 | 0.75805 | 0.75805 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5566.67262 | 5566.67262 | 0.22245 | 0.22245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6861.90819 | 6861.90819 | 0.50800 | 0.50800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5647.95939 | 5647.95939 | 0.24472 | 0.24472 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7819.98150 | 7819.98150 | 0.57892 | 0.57892 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3775.17780 | 3775.17780 | 0.16362 | 0.16362 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9511.24519 | 9511.24519 | 0.70413 | 0.70413 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5679.64467 | 5679.64467 | 0.24610 | 0.24610 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8330.69094 | 8330.69094 | 0.61673 | 0.61673 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3754.46160 | 3754.46160 | 0.16272 | 0.16272 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7555.79809 | 7555.79809 | 0.55937 | 0.55937 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6128.69221 | 6128.69221 | 0.26563 | 0.26563 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9063.66846 | 9063.66846 | 0.67099 | 0.67099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4071.47312 | 4071.47312 | 0.17650 | 0.17650 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10495.26420 | 10495.26420 | 0.77698 | 0.77698 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6150.87093 | 6150.87093 | 0.26659 | 0.26659 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9442.11589 | 9442.11589 | 0.69901 | 0.69901 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4051.48703 | 4051.48703 | 0.17563 | 0.17563 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 70882.45 | 4.55078 | 4.55078 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 12762.66 | 1.24186 | 1.24186 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66153.15 | 4.19551 | 4.19551 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 12760.86 | 1.32439 | 1.32439 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74047.98 | 4.79036 | 4.79036 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 12705.33 | 2.01850 | 2.01850 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.70456 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27711 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76269 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73895 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37492E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.61408E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76269 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10989.48395 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.61408E-005 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 232.02952 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17755 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34417 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74472 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91779 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10700E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54053E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74472 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17609.21274 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54053E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 412.26273 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23098 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33593 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77192 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89582 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13416E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38265E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82481 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27235.18021 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38265E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 719.43493 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63525 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24871 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16262 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66322 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53192E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03141E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34118 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11789.60192 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03141E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 316.48111 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68008 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14707 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13602 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39220 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59054E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.73739E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22303 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7701.25339 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.73739E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 206.68453 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85688 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18438 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17138 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49168 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06638E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03314E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34177 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11809.42131 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03314E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.00874 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75805 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13194 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15161 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35183 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88773E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.72043E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22245 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7681.86185 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.72043E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 206.16759 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50800 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31101 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16053 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82936 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22505E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.05584E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24472 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8065.26106 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.05584E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 212.86145 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57892 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17277 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11578 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46073 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20521E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.71663E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16362 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5391.40307 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71663E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.27966 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70413 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22438 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16054 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59834 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69802E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.09550E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24610 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8110.58943 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.09550E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 214.05576 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61673 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16217 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12335 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43245 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34938E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.69071E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16272 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5361.76948 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.69071E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.49880 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55937 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28245 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28000 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15662 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75319 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34892E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.65684E-005 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26563 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8752.23463 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.65684E-005 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.96834 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67099 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14907 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39751 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55592E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.08699E-005 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17650 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5814.74067 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.08699E-005 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.43950 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77698 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20334 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15695 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54224 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87369E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.68459E-005 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26659 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8783.95865 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.68459E-005 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.80435 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69901 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14308 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13980 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38155 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66281E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.06198E-005 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17563 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5786.15609 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.06198E-005 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 152.68613 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55617 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32289 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.11234 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32289 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55078 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.55078 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.29069 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44195 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33229 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.88389 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33229 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.19551 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.19551 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31755 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58062 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39355 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.16124 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.01850 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79036 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.79036 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.42137 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.55078 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.19551 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.79036 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55078 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.55078 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81809.20806 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80054 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.51677 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27267.00905 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80054 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 11123.30160 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.73115E-005 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 194.03624 |
248 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.55078 |
249 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.73115E-005 |
250 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.19551 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.19551 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 76163.17006 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80025 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.39836 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25385.18458 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80025 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 12155.44045 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06341E-004 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 210.18650 |
260 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.19551 |
261 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.06341E-004 |
262 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79036 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.79036 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85584.54416 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80065 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59663 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28525.32857 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80065 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 10417.73522 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11389E-005 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 182.70291 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.79036 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.11389E-005 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.61477E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.19377 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.61477E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 486.29907 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 184578.60574 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 184578.61000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.61477E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 10418.17 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 16683.74 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 25812.12 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11182.12 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7304.44 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11200.92 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7286.05 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7642.59 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5108.78 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7685.53 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5080.71 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8293.40 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5509.84 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8323.46 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5482.76 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 9598.31 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 10316.29 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 9079.92 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 80704.08 | 275373.75 | 11.81 | 3.05 | 3.38 | 3.55 | 3.76 | 10.41 | 11.52 | 12.12 | 12.83 | 5.1656 | 4.1045 | 2.7562 | 1.1125 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 75166.17 | 256477.62 | 11.83 | 3.06 | 3.38 | 3.56 | 3.77 | 10.43 | 11.55 | 12.14 | 12.86 | 4.7624 | 3.7877 | 2.5445 | 1.0220 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 84405.55 | 288003.68 | 11.79 | 3.05 | 3.37 | 3.55 | 3.75 | 10.40 | 11.51 | 12.10 | 12.81 | 5.4376 | 4.3181 | 2.8994 | 1.1733 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0548030025E-003 | 5.1199892798E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7850068683E-002 | 4.4812085282E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0031276568E-002 | 6.5181994247E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.4782653654E-003 | 5.9607924251E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1897363790E-003 | 5.7467766614E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8419955169E-002 | 1.1040056525E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.1344588740E-002 | 2.1137315141E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7245975038E-002 | 8.7495287206E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.1787937828E-002 | 7.4094291187E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6276544067E-002 | 3.4938497305E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1691962989E-002 | 1.7931278148E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.5557106645E-002 | 7.6504613124E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.5600557629E-002 | 5.9872909091E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.2767313223E-002 | 3.0900050196E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4526007818E-002 | 1.9221065407E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.5826998441E-002 | 8.9787935244E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9065589074E-002 | 7.5003313234E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.8326225327E-002 | 3.4254338283E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3526.63 | 34.78 | 0.00 | 2203.99 | 871.76 | 6637.18 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.557 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.20 | 0.0000 | Y | 8.87 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 8.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.81 | 0.0000 | Y | 5.53 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.48 | 0.0000 | Y | 8.63 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.74 | 0.0000 | Y | 5.52 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.19 | 0.0000 | Y | 8.87 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 8.64 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.81 | 0.0000 | Y | 5.53 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.49 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.14 | 42.14 | 4.46 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.75 | 62.95 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.75 | 46.20 | 40.89 | |
Exterior Lighting Total | 5686.19 | 50.17 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 184578.61 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81809.21 | 65491.89 | 16317.32 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 76163.17 | 60949.76 | 15213.41 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85584.54 | 68523.04 | 17061.50 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 80704.1 | 3.05 | 10.41 | N/A | N/A | 11.81 | |
PACU_VAV_MID COOLING COIL | 75166.2 | 3.06 | 10.43 | N/A | N/A | 11.83 | |
PACU_VAV_TOP COOLING COIL | 84405.5 | 3.05 | 10.40 | N/A | N/A | 11.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 10989.48 | 10418.17 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 17609.21 | 16683.74 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 27235.18 | 25812.12 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11789.60 | 11182.12 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7701.25 | 7304.44 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11809.42 | 11200.92 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7681.86 | 7286.05 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8065.26 | 7642.59 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5391.40 | 5108.78 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8110.59 | 7685.53 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5361.77 | 5080.71 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8752.23 | 8293.40 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5814.74 | 5509.84 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8783.96 | 8323.46 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5786.16 | 5482.76 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 11123.30 | 9598.31 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 12155.44 | 10316.29 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 10417.74 | 9079.92 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.55 | 9961.70 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.20 | 9184.02 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.79 | 10486.16 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001615 | 486.30 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80704.08 | 3.05 | 10.41 | 11.81 | 5.1656 | 3.38 | 11.52 | 4.1045 | 3.55 | 12.12 | 2.7562 | 3.76 | 12.83 | 1.1125 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 75166.17 | 3.06 | 10.43 | 11.83 | 4.7624 | 3.38 | 11.55 | 3.7877 | 3.56 | 12.14 | 2.5445 | 3.77 | 12.86 | 1.0220 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84405.55 | 3.05 | 10.40 | 11.79 | 5.4376 | 3.37 | 11.51 | 4.3181 | 3.55 | 12.10 | 2.8994 | 3.75 | 12.81 | 1.1733 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36844.81 | 36844.81 | 37.46 | 2.705 | 2.705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_MID | 29692.45 | 29692.45 | 30.19 | 2.178 | 2.178 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_TOP | 30135.18 | 30135.18 | 30.64 | 2.231 | 2.231 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00890 | 31.30 | 0.00823 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8580.84 | 8580.84 | 41.39 | 0.635 | 0.635 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00878 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9186.44 | 9186.44 | 69.99 | 0.680 | 0.680 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00867 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11574.61 | 11574.61 | 55.82 | 0.857 | 0.857 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00871 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10239.68 | 10239.68 | 78.01 | 0.758 | 0.758 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6861.91 | 6861.91 | 33.10 | 0.508 | 0.508 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00886 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7819.98 | 7819.98 | 59.58 | 0.579 | 0.579 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00870 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9511.25 | 9511.25 | 45.87 | 0.704 | 0.704 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00876 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8330.69 | 8330.69 | 63.47 | 0.617 | 0.617 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00869 | 30.05 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7555.80 | 7555.80 | 36.44 | 0.559 | 0.559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00882 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9063.67 | 9063.67 | 69.05 | 0.671 | 0.671 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00867 | 26.12 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10495.26 | 10495.26 | 50.62 | 0.777 | 0.777 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00873 | 30.93 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9442.12 | 9442.12 | 71.94 | 0.699 | 0.699 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00866 | 30.41 | 0.00823 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3452.92 | 3452.92 | 3.51 | 0.149 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_MID | 10250.15 | 10250.15 | 10.42 | 0.440 | 0.440 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_TOP | 19084.72 | 19084.72 | 19.40 | 0.825 | 0.825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8545.46 | 8545.46 | 41.22 | 0.341 | 0.341 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00766 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5580.61 | 5580.61 | 42.51 | 0.223 | 0.223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00767 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8559.69 | 8559.69 | 41.28 | 0.342 | 0.342 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00766 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5566.67 | 5566.67 | 42.41 | 0.222 | 0.222 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00767 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5647.96 | 5647.96 | 27.24 | 0.245 | 0.245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3775.18 | 3775.18 | 28.76 | 0.164 | 0.164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5679.64 | 5679.64 | 27.39 | 0.246 | 0.246 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3754.46 | 3754.46 | 28.60 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6128.69 | 6128.69 | 29.56 | 0.266 | 0.266 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4071.47 | 4071.47 | 31.02 | 0.177 | 0.177 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6150.87 | 6150.87 | 29.67 | 0.267 | 0.267 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4051.49 | 4051.49 | 30.87 | 0.176 | 0.176 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.55 | 4.55 | 1.24 | 1.24 | 4.5508 | 1.3229 | 4.5508 | 0.2907 | 0.3000 |
PACU_VAV_MID | 4.20 | 4.20 | 1.32 | 1.32 | 4.1955 | 1.3323 | 4.1955 | 0.3176 | 0.3000 |
PACU_VAV_TOP | 4.79 | 4.79 | 2.02 | 2.02 | 4.7904 | 2.0185 | 4.7904 | 0.4214 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 10989.484 | 10989.484 | 0.762687 | 0.00009614 | 232.030 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10989.48 | 10989.48 | 0.762687 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00799975 | 50.7543 | 3452.92 | 0.00 | 11029.14 | 11029.14 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 17609.213 | 17609.213 | 0.744723 | 0.00015405 | 412.263 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17609.21 | 17609.21 | 0.744723 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 10250.15 | 0.00 | 17667.05 | 17667.05 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27235.180 | 27235.180 | 0.824812 | 0.00023827 | 719.435 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27235.18 | 27235.18 | 0.824812 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 19084.72 | 0.00 | 27332.95 | 27332.95 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11789.602 | 11789.602 | 0.341183 | 0.00010314 | 316.481 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11789.60 | 11789.60 | 0.341183 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00765534 | 49.5154 | 8545.46 | 0.00 | 11841.57 | 11841.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7701.253 | 7701.253 | 0.223025 | 0.00006737 | 206.685 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7701.25 | 7701.25 | 0.223025 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00767419 | 49.6366 | 5580.61 | 0.00 | 7735.21 | 7735.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11809.421 | 11809.421 | 0.341771 | 0.00010331 | 317.009 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11809.42 | 11809.42 | 0.341771 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00765774 | 49.5307 | 8559.69 | 0.00 | 11861.48 | 11861.48 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7681.862 | 7681.862 | 0.222452 | 0.00006720 | 206.168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7681.86 | 7681.86 | 0.222452 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00767090 | 49.6155 | 5566.67 | 0.00 | 7715.73 | 7715.73 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8065.261 | 8065.261 | 0.244724 | 0.00007056 | 212.861 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8065.26 | 8065.26 | 0.244724 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781808 | 49.6176 | 5647.96 | 0.00 | 8092.87 | 8092.87 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5391.403 | 5391.403 | 0.163622 | 0.00004717 | 142.280 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5391.40 | 5391.40 | 0.163622 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782555 | 49.6645 | 3775.18 | 0.00 | 5409.77 | 5409.77 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8110.589 | 8110.589 | 0.246104 | 0.00007095 | 214.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8110.59 | 8110.59 | 0.246104 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781971 | 49.6278 | 5679.64 | 0.00 | 8138.34 | 8138.34 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5361.769 | 5361.769 | 0.162720 | 0.00004691 | 141.499 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5361.77 | 5361.77 | 0.162720 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782397 | 49.6546 | 3754.46 | 0.00 | 5380.04 | 5380.04 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8752.235 | 8752.235 | 0.265629 | 0.00007657 | 230.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8752.23 | 8752.23 | 0.265629 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777639 | 49.3568 | 6128.69 | 0.00 | 8782.02 | 8782.02 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5814.741 | 5814.741 | 0.176500 | 0.00005087 | 153.440 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5814.74 | 5814.74 | 0.176500 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778452 | 49.4078 | 4071.47 | 0.00 | 5834.46 | 5834.46 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8783.959 | 8783.959 | 0.266595 | 0.00007685 | 231.804 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8783.96 | 8783.96 | 0.266595 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777769 | 49.3650 | 6150.87 | 0.00 | 8813.84 | 8813.84 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5786.156 | 5786.156 | 0.175630 | 0.00005062 | 152.686 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5786.16 | 5786.16 | 0.175630 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00778277 | 49.3968 | 4051.49 | 0.00 | 5805.79 | 5805.79 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 81809.208 | 65491.887 | 4.550778 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 81825.04 | 79505.00 | 4.550778 | 25.92 | 17.01 | 0.00867060 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 26.2630 | 24.00 | 0.00882628 | 46.6085 | 61470.48 | 0.00 | 84356.27 | 65762.38 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 11123.302 | 11123.302 | 1.365233 | 0.00009731 | 194.036 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11123.30 | 11123.30 | 1.365233 | 5.94 | 5.36 | 0.00541252 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 87.5433 | 21.00 | 0.00786659 | 49.9212 | 20316.23 | 0.00 | 11619.76 | 11619.76 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 76163.170 | 60949.755 | 4.195511 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 76261.09 | 74056.54 | 4.195511 | 26.08 | 17.07 | 0.00867595 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 28.4869 | 24.00 | 0.00885222 | 46.7435 | 56666.93 | 0.00 | 78534.45 | 61216.82 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 12155.440 | 12155.440 | 1.258653 | 0.00010634 | 210.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12155.44 | 12155.44 | 1.258653 | 4.67 | 4.44 | 0.00520251 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 94.9562 | 21.00 | 0.00791197 | 50.2050 | 26447.16 | 0.00 | 12488.53 | 12488.53 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 85584.544 | 68523.044 | 4.790364 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 85543.29 | 83184.14 | 4.790364 | 25.82 | 16.97 | 0.00866473 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 24.9495 | 24.00 | 0.00880815 | 46.5140 | 64685.79 | 0.00 | 88249.15 | 68812.15 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 10417.735 | 10417.735 | 1.437109 | 0.00009114 | 182.703 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10417.74 | 10417.74 | 1.437109 | 6.70 | 5.90 | 0.00553949 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 83.1649 | 21.00 | 0.00791590 | 50.2296 | 27525.91 | 0.00 | 10992.39 | 10992.39 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 10989.484 | 10989.484 | 0.762687 | 0.00009614 | 232.030 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 5.8364 | 5.953823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10989.48 | 10989.48 | 1.0000 | 0.90132750 | 0.762687 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.09613099 | 60.00 | 32.22 | 27.78 | 0.000 | 10989.48 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.80 | 0.00799975 | 21.00 | 0.00799975 | 50.7543 | 3452.92 | 0.00 | 11029.14 | 11029.14 | 0.90132750 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.80 | 16.24 | 0.00800000 | 45296.4 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 17609.213 | 17609.213 | 0.744723 | 0.00015405 | 412.263 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 9.3520 | 9.540224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17609.21 | 17609.21 | 1.0000 | 0.88009811 | 0.744723 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.15403736 | 60.00 | 32.22 | 27.78 | 0.000 | 17609.21 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 10250.15 | 0.00 | 17667.05 | 17667.05 | 0.88009811 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.49 | 18.86 | 0.00800000 | 53133.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 27235.180 | 27235.180 | 0.824812 | 0.00023827 | 719.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 14.4642 | 14.755329 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27235.18 | 27235.18 | 1.0000 | 0.97474507 | 0.824812 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.23824093 | 60.00 | 32.22 | 27.78 | 0.000 | 27235.18 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 19084.72 | 0.00 | 27332.95 | 27332.95 | 0.97474507 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61101.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11789.602 | 11789.602 | 0.341183 | 0.00010314 | 316.481 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 6.2613 | 6.387307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11789.60 | 11789.60 | 1.0000 | 0.40320260 | 0.341183 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10313006 | 60.00 | 32.22 | 27.78 | 0.000 | 11789.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00765534 | 20.70 | 0.00765534 | 49.5154 | 8545.46 | 0.00 | 11841.57 | 11841.57 | 0.40320260 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.60 | 21.65 | 0.00800000 | 62428.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7701.253 | 7701.253 | 0.223025 | 0.00006737 | 206.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.0900 | 4.172343 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7701.25 | 7701.25 | 1.0000 | 0.26356624 | 0.223025 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06736705 | 60.00 | 32.22 | 27.78 | 0.000 | 7701.25 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00767419 | 20.70 | 0.00767419 | 49.6366 | 5580.61 | 0.00 | 7735.21 | 7735.21 | 0.26356624 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.58 | 21.65 | 0.00800000 | 62408.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11809.421 | 11809.421 | 0.341771 | 0.00010331 | 317.009 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 6.2718 | 6.398044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11809.42 | 11809.42 | 1.0000 | 0.40389712 | 0.341771 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10330343 | 60.00 | 32.22 | 27.78 | 0.000 | 11809.42 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00765774 | 20.70 | 0.00765774 | 49.5307 | 8559.69 | 0.00 | 11861.48 | 11861.48 | 0.40389712 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.60 | 21.65 | 0.00800000 | 62427.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7681.862 | 7681.862 | 0.222452 | 0.00006720 | 206.168 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.0797 | 4.161838 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7681.86 | 7681.86 | 1.0000 | 0.26288933 | 0.222452 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06719742 | 60.00 | 32.22 | 27.78 | 0.000 | 7681.86 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00767090 | 20.70 | 0.00767090 | 49.6155 | 5566.67 | 0.00 | 7715.73 | 7715.73 | 0.26288933 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.58 | 21.65 | 0.00800000 | 62409.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8065.261 | 8065.261 | 0.244724 | 0.00007056 | 212.861 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.2833 | 4.369554 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8065.26 | 8065.26 | 1.0000 | 0.28920962 | 0.244724 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07055122 | 60.00 | 32.22 | 27.78 | 0.000 | 8065.26 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781808 | 21.00 | 0.00781808 | 49.6176 | 5647.96 | 0.00 | 8092.87 | 8092.87 | 0.28920962 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61042.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5391.403 | 5391.403 | 0.163622 | 0.00004717 | 142.280 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 2.8633 | 2.920925 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5391.40 | 5391.40 | 1.0000 | 0.19336507 | 0.163622 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04716153 | 60.00 | 32.22 | 27.78 | 0.000 | 5391.40 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00782555 | 21.00 | 0.00782555 | 49.6645 | 3775.18 | 0.00 | 5409.77 | 5409.77 | 0.19336507 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61036.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8110.589 | 8110.589 | 0.246104 | 0.00007095 | 214.056 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.3074 | 4.394111 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8110.59 | 8110.59 | 1.0000 | 0.29084098 | 0.246104 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07094774 | 60.00 | 32.22 | 27.78 | 0.000 | 8110.59 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781971 | 21.00 | 0.00781971 | 49.6278 | 5679.64 | 0.00 | 8138.34 | 8138.34 | 0.29084098 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61041.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5361.769 | 5361.769 | 0.162720 | 0.00004691 | 141.499 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 2.8476 | 2.904871 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5361.77 | 5361.77 | 1.0000 | 0.19229879 | 0.162720 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04690231 | 60.00 | 32.22 | 27.78 | 0.000 | 5361.77 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00782397 | 21.00 | 0.00782397 | 49.6546 | 3754.46 | 0.00 | 5380.04 | 5380.04 | 0.19229879 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61037.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8752.235 | 8752.235 | 0.265629 | 0.00007657 | 230.968 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.6482 | 4.741738 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8752.23 | 8752.23 | 1.0000 | 0.31391465 | 0.265629 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07656056 | 60.00 | 32.22 | 27.78 | 0.000 | 8752.23 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00777639 | 21.00 | 0.00777639 | 49.3568 | 6128.69 | 0.00 | 8782.02 | 8782.02 | 0.31391465 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61035.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5814.741 | 5814.741 | 0.176500 | 0.00005087 | 153.440 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 3.0881 | 3.150279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5814.74 | 5814.74 | 1.0000 | 0.20858411 | 0.176500 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05086470 | 60.00 | 32.22 | 27.78 | 0.000 | 5814.74 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00778452 | 21.00 | 0.00778452 | 49.4078 | 4071.47 | 0.00 | 5834.46 | 5834.46 | 0.20858411 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61031.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8783.959 | 8783.959 | 0.266595 | 0.00007685 | 231.804 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 4.6650 | 4.758926 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8783.96 | 8783.96 | 1.0000 | 0.31505597 | 0.266595 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07683806 | 60.00 | 32.22 | 27.78 | 0.000 | 8783.96 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00777769 | 21.00 | 0.00777769 | 49.3650 | 6150.87 | 0.00 | 8813.84 | 8813.84 | 0.31505597 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61035.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5786.156 | 5786.156 | 0.175630 | 0.00005062 | 152.686 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 3.0729 | 3.134792 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5786.16 | 5786.16 | 1.0000 | 0.20755600 | 0.175630 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.05061465 | 60.00 | 32.22 | 27.78 | 0.000 | 5786.16 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00778277 | 21.00 | 0.00778277 | 49.3968 | 4051.49 | 0.00 | 5805.79 | 5805.79 | 0.20755600 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81809.208 | 65491.887 | 4.550778 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9582 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.550778 | 5.37801198 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 81825.04 | 79505.00 | 1.0002 | 5.37801198 | 4.550778 | 25.92 | 17.01 | 0.00867060 | 48144.1 | 10.99 | 10.99 | 0.00850000 | 32470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9961.702 | 71863.34 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 26.2630 | 24.00 | 0.00882628 | 24.00 | 0.00882628 | 46.6085 | 61470.48 | 0.00 | 84356.27 | 65762.38 | 5.16562116 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.22 | 13.90 | 0.00977336 | 38992.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 11123.302 | 11123.302 | 1.365233 | 0.00009731 | 194.036 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.550778 | 5.37801198 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 5.9074 | 6.026322 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11123.30 | 11123.30 | 1.0000 | 1.61340359 | 1.365233 | 5.94 | 5.36 | 0.00541252 | 19563.9 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.09730157 | 60.00 | 32.22 | 27.78 | 0.000 | 11123.30 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 87.5433 | 20.97 | 0.00790096 | 21.00 | 0.00786659 | 49.9212 | 20316.23 | 0.00 | 11619.76 | 11619.76 | 1.61340359 | 2.80 | 2.80 | 0.00541252 | 16378.1 | 9.90 | 7.46 | 0.00541252 | 23580.1 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 76163.170 | 60949.755 | 4.195511 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9682 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.195511 | 4.95816564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 76261.09 | 74056.54 | 1.0013 | 4.95816564 | 4.195511 | 26.08 | 17.07 | 0.00867595 | 48323.7 | 10.99 | 10.99 | 0.00850000 | 32470.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9184.020 | 67077.07 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 28.4869 | 24.00 | 0.00885222 | 24.00 | 0.00885222 | 46.7435 | 56666.93 | 0.00 | 78534.45 | 61216.82 | 4.76235558 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.10 | 13.84 | 0.00975893 | 38831.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12155.440 | 12155.440 | 1.258653 | 0.00010634 | 210.187 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.195511 | 4.95816564 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 6.4556 | 6.585509 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12155.44 | 12155.44 | 1.0000 | 1.48744969 | 1.258653 | 4.67 | 4.44 | 0.00520251 | 17746.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.10633025 | 60.00 | 32.22 | 27.78 | 0.000 | 12155.44 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 94.9562 | 21.00 | 0.00791502 | 21.00 | 0.00791197 | 50.2050 | 26447.16 | 0.00 | 12488.53 | 12488.53 | 1.48744969 | 2.80 | 2.80 | 0.00520251 | 15851.8 | 11.08 | 7.77 | 0.00520251 | 24247.7 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85584.544 | 68523.044 | 4.790364 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9473 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.790364 | 5.66114974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 85543.29 | 83184.14 | 0.9995 | 5.66114974 | 4.790364 | 25.82 | 16.97 | 0.00866473 | 48031.9 | 10.99 | 10.99 | 0.00850000 | 32470.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10486.159 | 75057.13 | 31.30 | 0.00823349 | 18.45 | 1.19517000 | 24.9495 | 24.00 | 0.00880815 | 24.00 | 0.00880815 | 46.5140 | 64685.79 | 0.00 | 88249.15 | 68812.15 | 5.43757712 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 13.94 | 0.00978315 | 39092.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 10417.735 | 10417.735 | 1.437109 | 0.00009114 | 182.703 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.790364 | 5.66114974 | 4197.9300 | 999.8980 | 1.61460944 | 54.44 | 82.22 | 27.78 | 188293.32 | 5.5327 | 5.644064 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10417.74 | 10417.74 | 1.0000 | 1.69834492 | 1.437109 | 6.70 | 5.90 | 0.00553949 | 20650.9 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.09112960 | 60.00 | 32.22 | 27.78 | 0.000 | 10417.74 | 3.80 | 0.00505843 | 3.80 | 1.19517000 | 83.1649 | 21.00 | 0.00791590 | 21.00 | 0.00791590 | 50.2296 | 27525.91 | 0.00 | 10992.39 | 10992.39 | 1.69834492 | 2.80 | 2.80 | 0.00553949 | 16696.3 | 9.18 | 7.26 | 0.00553949 | 23168.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.55 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.20 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4015.33 | 297.67 | 12.00 |
CORE_MID | 2403.00 | 1816.67 | 0.83 |
CORE_TOP | 1831.50 | 2802.00 | 4.00 |
PERIMETER_TOP_ZN_3 | 1683.17 | 3605.00 | 187.17 |
PERIMETER_TOP_ZN_2 | 2180.67 | 3046.00 | 146.83 |
PERIMETER_TOP_ZN_1 | 2581.50 | 2543.00 | 149.33 |
PERIMETER_TOP_ZN_4 | 2223.33 | 3306.17 | 276.67 |
PERIMETER_BOT_ZN_3 | 1277.17 | 3678.33 | 10.50 |
PERIMETER_BOT_ZN_2 | 2252.50 | 2544.17 | 28.83 |
PERIMETER_BOT_ZN_1 | 2379.17 | 2550.33 | 98.83 |
PERIMETER_BOT_ZN_4 | 2389.67 | 2647.33 | 50.33 |
PERIMETER_MID_ZN_3 | 1768.00 | 3073.00 | 18.50 |
PERIMETER_MID_ZN_2 | 1808.50 | 2406.17 | 65.67 |
PERIMETER_MID_ZN_1 | 2888.17 | 1932.17 | 72.50 |
PERIMETER_MID_ZN_4 | 2405.83 | 2768.50 | 108.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4786.17 | 4353.67 | 491.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 9.33 | 0.00 | 9.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 20.33 | 0.00 | 20.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 23.83 | 0.00 | 19.67 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 3.67 | 0.00 | 3.67 |
PERIMETER_BOT_ZN_1 | 37.83 | 29.33 | 37.83 | 29.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 11.17 | 0.00 | 9.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 12.33 | 0.00 | 12.33 |
PERIMETER_MID_ZN_1 | 0.00 | 29.17 | 0.00 | 29.17 |
PERIMETER_MID_ZN_4 | 0.00 | 21.67 | 0.00 | 19.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 37.83 | 119.00 | 37.83 | 111.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 1.489 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 0.975 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.959 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.978 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 1.511 | 0.027 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 1.575 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 1.689 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.868 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 1.309 | 0.015 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 1.257 | 0.812 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 1.396 | 0.015 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.961 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 1.378 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 1.554 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 1.617 | 0.023 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 112.00 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 23381987.13 | 0.00 | 23381987.13 | 0.00 | 23381987.13 | 13393058.27 | 3960.14 | 26.45 | 4773.41 | 28.06 |
CORE_MID | 15354023.82 | 0.00 | 15354023.82 | 0.00 | 15354023.82 | 13393058.27 | 4153.06 | 17.29 | 4589.65 | 31.94 |
CORE_TOP | 15126491.41 | 0.00 | 15126491.41 | 0.00 | 15126491.41 | 13393058.27 | 4178.75 | 13.98 | 4567.27 | 36.19 |
PERIMETER_TOP_ZN_3 | 3251914.01 | 0.00 | 3251914.01 | 149098.74 | 3401012.74 | 2823374.22 | 4101.51 | 18.80 | 4639.69 | 36.19 |
PERIMETER_TOP_ZN_2 | 3177151.92 | 0.00 | 3177151.92 | 99398.56 | 3276550.48 | 1787429.43 | 3882.13 | 2.47 | 4875.39 | 36.19 |
PERIMETER_TOP_ZN_1 | 5224177.38 | 0.00 | 5224177.38 | 149098.74 | 5373276.12 | 2823374.22 | 3908.81 | 3.93 | 4847.26 | 36.19 |
PERIMETER_TOP_ZN_4 | 3554311.70 | 0.00 | 3554311.70 | 99398.56 | 3653710.26 | 1787312.18 | 3883.61 | 2.97 | 4873.42 | 36.19 |
PERIMETER_BOT_ZN_3 | 2885630.80 | 0.00 | 2885630.80 | 79275.26 | 2964906.06 | 2823374.22 | 4129.10 | 19.02 | 4611.88 | 28.06 |
PERIMETER_BOT_ZN_2 | 2745888.89 | 0.00 | 2745888.89 | 52849.85 | 2798738.74 | 1787429.43 | 3918.91 | 9.20 | 4831.89 | 28.06 |
PERIMETER_BOT_ZN_1 | 4171187.78 | 0.00 | 4171187.78 | 2726356.63 | 6897544.41 | 2823374.22 | 3947.98 | 17.77 | 4794.25 | 28.06 |
PERIMETER_BOT_ZN_4 | 2928854.58 | 0.00 | 2928854.58 | 52849.85 | 2981704.43 | 1787312.18 | 3950.82 | 9.26 | 4799.92 | 28.06 |
PERIMETER_MID_ZN_3 | 3191463.21 | 0.00 | 3191463.21 | 124113.44 | 3315576.65 | 2823374.22 | 4049.71 | 23.40 | 4686.89 | 31.94 |
PERIMETER_MID_ZN_2 | 3143986.44 | 0.00 | 3143986.44 | 82741.80 | 3226728.24 | 1787429.43 | 3846.11 | 1.89 | 4912.00 | 940.94 |
PERIMETER_MID_ZN_1 | 5149686.61 | 0.00 | 5149686.61 | 124113.44 | 5273800.05 | 2823374.22 | 3959.84 | 16.50 | 4783.66 | 31.94 |
PERIMETER_MID_ZN_4 | 3396577.59 | 0.00 | 3396577.59 | 82741.80 | 3479319.38 | 1787312.18 | 3859.86 | 5.44 | 4894.69 | 31.94 |
Total Facility | 96683333.26 | 0.00 | 96683333.26 | 3822036.67 | 0.10E+09 | 67843644.98 | 4384.17 | 107.95 | 5019.48 | 956.94 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 1.0893 | 0.0000 | 1.0893 | 0.0000 | 1.0893 | 0.4247 | 1171.20 | 26.45 | 4745.35 |
CORE_MID | 0.7137 | 0.0000 | 0.7137 | 0.0000 | 0.7137 | 0.4247 | 1368.00 | 17.29 | 4557.71 |
CORE_TOP | 0.7023 | 0.0000 | 0.7023 | 0.0000 | 0.7023 | 0.4247 | 1397.94 | 13.98 | 4531.07 |
PERIMETER_TOP_ZN_3 | 0.1510 | 0.0000 | 0.1510 | 0.0040 | 0.1550 | 0.0895 | 1320.70 | 18.80 | 4603.50 |
PERIMETER_TOP_ZN_2 | 0.1477 | 0.0000 | 0.1477 | 0.0027 | 0.1504 | 0.0567 | 1101.33 | 2.47 | 4839.20 |
PERIMETER_TOP_ZN_1 | 0.2431 | 0.0000 | 0.2431 | 0.0040 | 0.2471 | 0.0895 | 1128.01 | 3.93 | 4811.06 |
PERIMETER_TOP_ZN_4 | 0.1651 | 0.0000 | 0.1651 | 0.0027 | 0.1678 | 0.0567 | 1102.80 | 2.97 | 4837.23 |
PERIMETER_BOT_ZN_3 | 0.1341 | 0.0000 | 0.1341 | 0.0021 | 0.1363 | 0.0895 | 1340.15 | 19.02 | 4583.82 |
PERIMETER_BOT_ZN_2 | 0.1278 | 0.0000 | 0.1278 | 0.0014 | 0.1292 | 0.0567 | 1129.96 | 9.20 | 4803.83 |
PERIMETER_BOT_ZN_1 | 0.1942 | 0.0000 | 0.1942 | 0.1259 | 0.3201 | 0.0895 | 1159.04 | 17.77 | 4766.20 |
PERIMETER_BOT_ZN_4 | 0.1363 | 0.0000 | 0.1363 | 0.0014 | 0.1377 | 0.0567 | 1161.87 | 9.26 | 4771.86 |
PERIMETER_MID_ZN_3 | 0.1483 | 0.0000 | 0.1483 | 0.0033 | 0.1517 | 0.0895 | 1264.66 | 23.40 | 4654.94 |
PERIMETER_MID_ZN_2 | 0.1347 | 0.0000 | 0.1347 | 0.0023 | 0.1370 | 0.0567 | 1056.06 | 1.06 | 3976.89 |
PERIMETER_MID_ZN_1 | 0.2399 | 0.0000 | 0.2399 | 0.0033 | 0.2432 | 0.0895 | 1174.78 | 16.50 | 4751.72 |
PERIMETER_MID_ZN_4 | 0.1579 | 0.0000 | 0.1579 | 0.0022 | 0.1601 | 0.0567 | 1074.81 | 5.44 | 4862.75 |
Total Facility | 4.4853 | 0.0000 | 4.4853 | 0.1554 | 4.6407 | 2.1513 | 1581.75 | 107.95 | 4971.54 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 50436212.04 | 0.00 | 50436212.04 | 22614548.33 | 3881.50 | 0.92 | 4877.58 | 28.06 |
PACU_VAV_MID | 42227255.71 | 0.00 | 42227255.71 | 22614548.33 | 3838.44 | 0.36 | 4921.19 | 31.94 |
PACU_VAV_TOP | 42364553.80 | 0.00 | 42364553.80 | 22614548.33 | 3867.61 | 2.45 | 4889.94 | 36.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 2.3486 | 0.0000 | 2.3486 | 0.7171 | 1092.56 | 0.92 | 4849.53 |
PACU_VAV_MID | 1.9636 | 0.0000 | 1.9636 | 0.7171 | 1053.39 | 0.36 | 4889.25 |
PACU_VAV_TOP | 1.9681 | 0.0000 | 1.9681 | 0.7171 | 1086.80 | 2.45 | 4853.75 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 4689.26 | 0.00 | 0.00 | 0.00 | 189.65 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 4661.40 | 0.00 | 0.00 | 0.00 | 262.29 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 4665.41 | 0.00 | 0.00 | 0.00 | 253.28 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.9468 | 0.0000 | 0.0000 | 0.0000 | 1.1788 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.4570 | 0.0000 | 0.0000 | 0.0000 | 1.1309 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.4663 | 0.0000 | 0.0000 | 0.0000 | 1.1079 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 982 |
Defaulted Fields | 577 |
Fields with Defaults | 2420 |
Autosized Fields | 193 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
Electricity:Building | 1021.18 | 13472.34 | 30-APR-17:20 | 74313.01 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1021.18 | 13472.34 | 30-APR-17:20 | 74313.01 | 02-JAN-16:50 |
InteriorLights:Electricity | 301.49 | 994.59 | 30-APR-17:20 | 32642.50 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.49 | 994.59 | 30-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 301.49 | 994.59 | 30-APR-17:20 | 32642.50 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.49 | 994.59 | 30-APR-17:20 | 32642.50 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.20 | 422.10 | 16-APR-17:10 | 2793.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.87 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.87 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.96 | 269.43 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.97 | 422.10 | 16-APR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.64 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.64 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.93 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.53 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.53 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.17 | 422.10 | 16-APR-17:10 | 2793.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.94 | 269.43 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.96 | 422.10 | 16-APR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.63 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.63 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.92 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.52 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.20 | 422.10 | 16-APR-17:10 | 2793.69 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.87 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.87 | 36.00 | 01-JAN-09:10 | 1358.45 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.96 | 269.43 | 16-APR-17:10 | 1768.58 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-07:20 | 860.01 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.97 | 422.10 | 16-APR-17:10 | 2793.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.64 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.64 | 36.00 | 01-JAN-07:30 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.93 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.53 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.53 | 22.79 | 01-JAN-09:10 | 859.95 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 276.83 | 367.92 | 01-JAN-00:10 | 72553.25 | 16-OCT-11:00 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-17:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-17:10 |
ElectricityPurchased:Facility | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
ElectricityPurchased:Plant | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
Cogeneration:ElectricityPurchased | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
General:Cogeneration:ElectricityPurchased | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
ElectricityNet:Plant | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
Cogeneration:ElectricityNet | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
General:Cogeneration:ElectricityNet | 1397.21 | 13858.13 | 14-MAY-17:40 | 144422.42 | 16-OCT-11:00 |
Fans:Electricity | 90.59 | 0.00 | 01-JAN-00:10 | 20249.55 | 16-OCT-16:00 |
General:Fans:Electricity | 90.59 | 0.00 | 01-JAN-00:10 | 20249.55 | 16-OCT-16:00 |
ExteriorLights:Electricity | 50.17 | 0.00 | 01-JAN-07:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.17 | 0.00 | 01-JAN-07:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 159.33 | 0.00 | 01-JAN-00:10 | 58550.11 | 16-OCT-11:00 |
General:Cooling:Electricity | 159.33 | 0.00 | 01-JAN-00:10 | 58550.11 | 16-OCT-11:00 |
Electricity:Plant | 49.02 | 0.00 | 01-JAN-00:10 | 5807.93 | 27-FEB-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 48.82 | 0.00 | 01-JAN-00:10 | 5763.72 | 03-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 48.82 | 0.00 | 01-JAN-00:10 | 5763.72 | 03-FEB-12:50 |
Pumps:Electricity | 0.20 | 0.00 | 01-JAN-00:10 | 347.37 | 03-JAN-07:10 |
General:Pumps:Electricity | 0.20 | 0.00 | 01-JAN-00:10 | 347.37 | 03-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 8.47 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-17:00 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 10.42 | 0.00 | 01-JAN-00:10 | 89287.93 | 03-JAN-07:10 |
NaturalGas:Plant | 10.42 | 0.00 | 01-JAN-00:10 | 89287.93 | 03-JAN-07:10 |
Heating:NaturalGas | 10.42 | 0.00 | 01-JAN-00:10 | 89287.93 | 03-JAN-07:10 |
Boiler:Heating:NaturalGas | 10.42 | 0.00 | 01-JAN-00:10 | 89287.93 | 03-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1893.32 | 0.00 | 01-JAN-00:10 | 372976.95 | 31-JUL-15:40 |
EnergyTransfer:Building | 1125.40 | 0.00 | 01-JAN-00:10 | 157703.26 | 16-OCT-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 259.52 | 0.00 | 01-JAN-00:10 | 24627.89 | 02-OCT-08:00 |
Heating:EnergyTransfer | 9.31 | 0.00 | 01-JAN-00:10 | 36183.62 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.31 | 0.00 | 01-JAN-00:10 | 36183.62 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1116.09 | 0.00 | 01-JAN-00:10 | 157703.26 | 16-OCT-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 259.52 | 0.00 | 01-JAN-00:10 | 24627.89 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer | 1116.09 | 0.00 | 01-JAN-00:10 | 157703.26 | 16-OCT-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 259.52 | 0.00 | 01-JAN-00:10 | 24627.89 | 02-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.83 | 0.00 | 01-JAN-00:10 | 9294.88 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.92 | 0.00 | 01-JAN-00:10 | 5064.52 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.92 | 0.00 | 01-JAN-00:10 | 5064.52 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.91 | 0.00 | 01-JAN-00:10 | 9294.88 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.91 | 0.00 | 01-JAN-00:10 | 9294.88 | 16-OCT-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.77 | 0.00 | 01-JAN-00:10 | 4548.01 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.36 | 0.00 | 01-JAN-00:10 | 2130.35 | 02-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.36 | 0.00 | 01-JAN-00:10 | 2130.35 | 02-JAN-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.41 | 0.00 | 01-JAN-00:10 | 4548.01 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.41 | 0.00 | 01-JAN-00:10 | 4548.01 | 16-OCT-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.66 | 0.00 | 01-JAN-00:10 | 4620.71 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.40 | 0.00 | 01-JAN-00:10 | 1811.70 | 25-DEC-10:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.40 | 0.00 | 01-JAN-00:10 | 1811.70 | 25-DEC-10:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.26 | 0.00 | 01-JAN-00:10 | 4620.71 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.26 | 0.00 | 01-JAN-00:10 | 4620.71 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_MID | 167.98 | 0.00 | 01-JAN-00:10 | 17746.55 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 167.98 | 0.00 | 01-JAN-00:10 | 17746.55 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 167.98 | 0.00 | 01-JAN-00:10 | 17746.55 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_TOP | 159.65 | 0.00 | 01-JAN-00:10 | 19448.16 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.02 | 0.00 | 01-JAN-00:10 | 6526.03 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.02 | 0.00 | 01-JAN-00:10 | 6526.03 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 159.63 | 0.00 | 01-JAN-00:10 | 19448.16 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 159.63 | 0.00 | 01-JAN-00:10 | 19448.16 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.98 | 0.00 | 01-JAN-00:10 | 5841.53 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.31 | 0.00 | 01-JAN-00:10 | 4056.75 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.31 | 0.00 | 01-JAN-00:10 | 4056.75 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.67 | 0.00 | 01-JAN-00:10 | 5841.53 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.67 | 0.00 | 01-JAN-00:10 | 5841.53 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.19 | 0.00 | 01-JAN-00:10 | 6511.97 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2627.74 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 2627.74 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.09 | 0.00 | 01-JAN-00:10 | 6511.97 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.09 | 0.00 | 01-JAN-00:10 | 6511.97 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.40 | 0.00 | 01-JAN-00:10 | 12097.36 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.13 | 0.00 | 01-JAN-00:10 | 3221.07 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.13 | 0.00 | 01-JAN-00:10 | 3221.07 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.27 | 0.00 | 01-JAN-00:10 | 12097.36 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.27 | 0.00 | 01-JAN-00:10 | 12097.36 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.16 | 0.00 | 01-JAN-00:10 | 7809.97 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.20 | 0.00 | 01-JAN-00:10 | 2574.57 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.20 | 0.00 | 01-JAN-00:10 | 2574.57 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.96 | 0.00 | 01-JAN-00:10 | 7809.97 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 35.96 | 0.00 | 01-JAN-00:10 | 7809.97 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.57 | 0.00 | 01-JAN-00:10 | 4580.09 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 1800.61 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 1800.61 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.55 | 0.00 | 01-JAN-00:10 | 4580.09 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 29.55 | 0.00 | 01-JAN-00:10 | 4580.09 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.62 | 0.00 | 01-JAN-00:10 | 5782.55 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 538.88 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 538.88 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.61 | 0.00 | 01-JAN-00:10 | 5782.55 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 29.61 | 0.00 | 01-JAN-00:10 | 5782.55 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.22 | 0.00 | 01-JAN-00:10 | 12164.14 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.80 | 0.00 | 01-JAN-00:10 | 5010.25 | 30-MAR-06:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.80 | 0.00 | 01-JAN-00:10 | 5010.25 | 30-MAR-06:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.42 | 0.00 | 01-JAN-00:10 | 12164.14 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.42 | 0.00 | 01-JAN-00:10 | 12164.14 | 16-OCT-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.28 | 0.00 | 01-JAN-00:10 | 6413.14 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 992.20 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 992.20 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.27 | 0.00 | 01-JAN-00:10 | 6413.14 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.27 | 0.00 | 01-JAN-00:10 | 6413.14 | 16-OCT-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.85 | 0.00 | 01-JAN-00:10 | 5367.18 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2049.06 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 2049.06 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.83 | 0.00 | 01-JAN-00:10 | 5367.18 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.83 | 0.00 | 01-JAN-00:10 | 5367.18 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.79 | 0.00 | 01-JAN-00:10 | 6545.25 | 16-OCT-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 930.16 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 930.16 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.78 | 0.00 | 01-JAN-00:10 | 6545.25 | 16-OCT-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.78 | 0.00 | 01-JAN-00:10 | 6545.25 | 16-OCT-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.75 | 0.00 | 01-JAN-00:10 | 11137.73 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1524.87 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1524.87 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.74 | 0.00 | 01-JAN-00:10 | 11137.73 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.74 | 0.00 | 01-JAN-00:10 | 11137.73 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.21 | 0.00 | 01-JAN-00:10 | 7388.34 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1425.61 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1425.61 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.19 | 0.00 | 01-JAN-00:10 | 7388.34 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.19 | 0.00 | 01-JAN-00:10 | 7388.34 | 29-SEP-15:30 |
PlantLoopHeatingDemand:Facility | 52.73 | 0.00 | 01-JAN-00:10 | 65897.47 | 03-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
EnergyTransfer:HVAC | 715.26 | 0.00 | 01-JAN-00:10 | 240999.59 | 31-JUL-15:40 |
HeatingCoils:EnergyTransfer | 6.66 | 0.00 | 01-JAN-00:10 | 64090.92 | 03-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 6.66 | 0.00 | 01-JAN-00:10 | 64090.92 | 03-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 6.66 | 0.00 | 01-JAN-00:10 | 64090.92 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 708.60 | 0.00 | 01-JAN-00:10 | 240992.89 | 31-JUL-15:40 |
EnergyTransfer:Plant | 52.66 | 0.00 | 01-JAN-00:10 | 69852.10 | 03-JAN-07:10 |
WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
Boilers:EnergyTransfer | 6.59 | 0.00 | 01-JAN-00:10 | 68045.56 | 03-JAN-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -259.520 | 0.000 | 0.000 | 32.665 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -95.497 |
CORE_MID | 0.000 | 0.000 | 0.000 | -167.976 | 0.000 | 0.000 | 32.959 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.336 |
CORE_TOP | 0.000 | 0.000 | 0.020 | -159.628 | 0.000 | 0.000 | 33.453 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -61.198 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.310 | -32.668 | 0.000 | 0.000 | 7.213 | 8.869 | 24.333 | 13.381 | 0.000 | 0.014 | 4.997 | 0.000 | -25.161 | 0.000 | -1.288 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.094 | -33.092 | 0.000 | 0.000 | 4.485 | 5.553 | 15.404 | 29.297 | 0.000 | 0.007 | 0.000 | 0.000 | -16.339 | 0.000 | -0.893 | -4.516 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.130 | -56.269 | 0.000 | 0.000 | 7.058 | 8.639 | 24.332 | 57.479 | 0.000 | 0.011 | 0.001 | 0.000 | -25.571 | 0.000 | -1.398 | -14.410 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.195 | -35.962 | 0.000 | 0.000 | 4.590 | 5.531 | 15.403 | 33.417 | 0.000 | 0.009 | 0.000 | 0.000 | -17.029 | 0.000 | -0.900 | -5.256 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.016 | -29.552 | 0.000 | 0.000 | 7.160 | 8.836 | 24.333 | 13.637 | 0.000 | 0.008 | 2.481 | 0.000 | -26.197 | 0.000 | -0.721 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.002 | -29.614 | 0.000 | 0.000 | 4.433 | 5.540 | 15.404 | 29.358 | 0.000 | 0.004 | 0.001 | 0.000 | -17.432 | 0.000 | -0.513 | -7.182 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.804 | -44.422 | 0.000 | 0.000 | 7.098 | 8.627 | 24.332 | 58.024 | 0.000 | 0.343 | 0.001 | 0.000 | -27.162 | 0.000 | -17.497 | -11.148 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.004 | -31.271 | 0.000 | 0.000 | 4.485 | 5.517 | 15.403 | 33.610 | 0.000 | 0.004 | 0.000 | 0.000 | -18.316 | 0.000 | -0.520 | -8.918 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.020 | -33.831 | 0.000 | 0.000 | 7.089 | 8.869 | 24.333 | 13.011 | 0.000 | 0.011 | 8.608 | 0.000 | -26.955 | 0.000 | -1.154 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.006 | -33.784 | 0.000 | 0.000 | 3.290 | 5.553 | 15.404 | 29.039 | 0.000 | 0.006 | 0.000 | 0.000 | -17.338 | 0.000 | -0.793 | -1.382 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.006 | -57.740 | 0.000 | 0.000 | 6.975 | 8.639 | 24.332 | 57.179 | 0.000 | 0.009 | 0.003 | 0.000 | -27.202 | 0.000 | -1.241 | -10.956 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.016 | -36.192 | 0.000 | 0.000 | 4.504 | 5.531 | 15.403 | 33.230 | 0.000 | 0.007 | 0.000 | 0.000 | -18.199 | 0.000 | -0.804 | -3.498 |
TOPFLOOR_PLENUM | 4.921 | -33.906 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.012 | 31.065 | 0.000 | 0.000 | 0.000 | -2.091 | -0.000 |
MIDFLOOR_PLENUM | 1.362 | -16.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.015 | 17.079 | 0.000 | 0.000 | 0.000 | -2.047 | -0.000 |
FIRSTFLOOR_PLENUM | 0.401 | -24.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.010 | 25.522 | 0.000 | 0.000 | 0.000 | -1.673 | -0.000 |
Total Facility | 6.684 | -74.575 | 2.623 | -1041.522 | 0.000 | 0.000 | 167.457 | 301.490 | 719.689 | 400.661 | 0.000 | 0.469 | 89.759 | 0.000 | -262.900 | 0.000 | -33.531 | -276.300 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | -40207.43 | 0.00 | 0.00 | 316.00 | 715.98 | 7410.35 | 0.00 | 0.00 | 0.00 | 31765.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 16-OCT-05:12 | 0.00 | 0.00 | 0.00 | -31000.73 | 0.00 | 0.00 | 337.43 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 26921.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 16-OCT-14:00 | 0.00 | 0.00 | 0.00 | -19448.93 | 0.00 | 0.00 | 3591.74 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 2604.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | -5841.97 | 0.00 | 0.00 | 757.17 | 647.98 | 1435.25 | 2570.41 | 0.00 | 47.62 | 383.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:53 | 0.00 | 0.00 | 0.00 | -11525.41 | 0.00 | 0.00 | 16.24 | 22.79 | 302.86 | 4854.35 | 0.00 | 0.00 | 6350.22 | 0.00 | -0.00 | 0.00 | -21.04 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-12:52 | 0.00 | 0.00 | 0.00 | -15648.66 | 0.00 | 0.00 | 23.77 | 36.00 | 478.41 | 12283.93 | 0.00 | 0.00 | 2844.16 | 0.00 | -0.00 | 0.00 | -17.61 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:02 | 0.00 | 0.00 | 0.00 | -13401.44 | 0.00 | 0.00 | 15.03 | 22.79 | 302.86 | 7404.42 | 0.00 | 0.00 | 5670.75 | 0.00 | -0.00 | 0.00 | -14.40 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -4580.36 | 0.00 | 0.00 | 737.21 | 647.98 | 1435.25 | 2898.12 | 0.00 | 30.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1169.14 |
PERIMETER_BOT_ZN_2 | 15-OCT-09:43 | 0.00 | 0.00 | 0.00 | -9558.60 | 0.00 | 0.00 | 16.96 | 22.79 | 302.86 | 5258.98 | 0.00 | 21.31 | 3935.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -12602.23 | 0.00 | 0.00 | 25.54 | 36.00 | 478.41 | 12235.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -43.75 | -129.94 |
PERIMETER_BOT_ZN_4 | 30-JUL-16:42 | 0.00 | 0.00 | 0.00 | -9849.09 | 0.00 | 0.00 | 16.77 | 22.79 | 302.86 | 5877.00 | 0.00 | 0.00 | 3663.12 | 0.00 | -0.00 | 0.00 | -33.44 | 0.00 |
PERIMETER_MID_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -5367.50 | 0.00 | 0.00 | 737.21 | 647.98 | 1435.25 | 2880.26 | 0.00 | 48.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -381.51 |
PERIMETER_MID_ZN_2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -11719.86 | 0.00 | 0.00 | 15.90 | 22.79 | 302.86 | 6607.96 | 0.00 | 0.00 | 4787.40 | 0.00 | -0.00 | 0.00 | -17.05 | 0.00 |
PERIMETER_MID_ZN_1 | 19-NOV-12:52 | 0.00 | 0.00 | 0.00 | -14264.32 | 0.00 | 0.00 | 23.85 | 36.00 | 478.41 | 12303.59 | 0.00 | 0.00 | 1437.79 | 0.00 | -0.00 | 0.00 | -15.32 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-16:12 | 0.00 | 0.00 | 0.00 | -12187.84 | 0.00 | 0.00 | 15.78 | 22.79 | 302.86 | 6664.69 | 0.00 | 0.00 | 5233.88 | 0.00 | -0.00 | 0.00 | -52.16 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:10 | 0.00 | -9295.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.85 | 9238.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4548.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 4534.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4621.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 4610.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-14:30 | 0.00 | -17375.84 | 0.00 | -140340.20 | 0.00 | 0.00 | 17646.68 | 25681.07 | 41659.26 | 56551.86 | 0.00 | 935.30 | 15241.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-07:03 | 0.00 | 0.00 | 13599.47 | 0.00 | 0.00 | 0.00 | 916.85 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19690.27 |
PERIMETER_TOP_ZN_3 | 09-JAN-06:12 | 0.00 | 0.00 | 6004.22 | 0.00 | 0.00 | 0.00 | 104.46 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2421.49 | 0.00 | -52.39 | -4423.61 |
PERIMETER_TOP_ZN_2 | 03-JAN-06:12 | 0.00 | 0.00 | 4700.23 | 0.00 | 0.00 | 0.00 | 66.33 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1452.25 | 0.00 | -14.64 | -3799.04 |
PERIMETER_TOP_ZN_1 | 03-JAN-06:12 | 0.00 | 0.00 | 6522.25 | 0.00 | 0.00 | 0.00 | 102.85 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2217.47 | 0.00 | -22.61 | -5173.84 |
PERIMETER_TOP_ZN_4 | 03-JAN-06:12 | 0.00 | 0.00 | 4770.02 | 0.00 | 0.00 | 0.00 | 66.06 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1447.11 | 0.00 | -14.78 | -3873.55 |
PERIMETER_BOT_ZN_3 | 03-JAN-07:02 | 0.00 | 0.00 | 3692.78 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2284.73 | 0.00 | -3.41 | -2688.65 |
PERIMETER_BOT_ZN_2 | 30-MAR-06:02 | 0.00 | 0.00 | 2694.38 | 0.00 | 0.00 | 0.00 | 122.38 | 236.70 | 403.81 | 3150.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.50 | -6583.88 |
PERIMETER_BOT_ZN_1 | 30-MAR-06:10 | 0.00 | 0.00 | 5176.75 | 0.00 | 0.00 | 0.00 | 193.31 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 5789.75 | 0.00 | -1936.86 | 0.00 | -10313.64 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-JAN-07:02 | 0.00 | 0.00 | 2709.45 | 0.00 | 0.00 | 0.00 | 122.27 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1528.05 | 0.00 | -2.29 | -1991.85 |
PERIMETER_MID_ZN_3 | 03-JAN-07:02 | 0.00 | 0.00 | 4046.13 | 0.00 | 0.00 | 0.00 | 193.29 | 452.82 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2268.17 | 0.00 | -5.34 | -3056.63 |
PERIMETER_MID_ZN_2 | 03-JAN-07:02 | 0.00 | 0.00 | 2942.23 | 0.00 | 0.00 | 0.00 | 122.37 | 200.05 | 403.81 | 1754.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.59 | -5419.24 |
PERIMETER_MID_ZN_1 | 30-MAR-06:02 | 0.00 | 0.00 | 4363.38 | 0.00 | 0.00 | 0.00 | 192.82 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1969.18 | 0.00 | -55.11 | -3622.62 |
PERIMETER_MID_ZN_4 | 03-JAN-07:02 | 0.00 | 0.00 | 2962.84 | 0.00 | 0.00 | 0.00 | 122.37 | 286.65 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1503.41 | 0.00 | -3.57 | -2268.68 |
TOPFLOOR_PLENUM | 03-JAN-07:02 | 6003.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8.78 | -5995.06 |
MIDFLOOR_PLENUM | 25-DEC-12:53 | 4135.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.03 | -4126.84 |
FIRSTFLOOR_PLENUM | 24-DEC-10:50 | 2752.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -75.13 | -2677.36 |
Total Facility | 03-JAN-07:02 | -9984.19 | 12606.46 | 60564.36 | -12606.46 | 0.00 | 0.00 | 4407.74 | 10384.28 | 22496.85 | 5427.31 | 0.00 | 0.00 | 0.00 | 0.00 | -11263.79 | 0.00 | -13766.82 | -68265.76 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1123 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5508 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.8839 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1955 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1612 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7904 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5562 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3229 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4419 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3323 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5806 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3935 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7046 | 2.7046 | 0.7627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1776 | 2.1776 | 0.7447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2310 | 2.2310 | 0.7719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6352 | 0.6352 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6801 | 0.6801 | 0.1360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8569 | 0.8569 | 0.1714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7581 | 0.7581 | 0.1516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5080 | 0.5080 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5789 | 0.5789 | 0.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7041 | 0.7041 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6167 | 0.6167 | 0.1233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5594 | 0.5594 | 0.1566 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6710 | 0.6710 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7770 | 0.7770 | 0.1569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6990 | 0.6990 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1123 | 4.5508 | 5.1123 | 1.3229 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.8839 | 4.1955 | 4.8839 | 1.3323 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1612 | 4.7904 | 5.1612 | 1.3935 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3523 | 1.3523 | 0.7627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0888 | 1.0888 | 0.7447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1155 | 1.1155 | 0.7719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3176 | 0.3176 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3400 | 0.3400 | 0.1360 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4284 | 0.4284 | 0.1714 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3790 | 0.3790 | 0.1516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2540 | 0.2540 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2895 | 0.2895 | 0.1158 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3521 | 0.3521 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3084 | 0.3084 | 0.1233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2797 | 0.2797 | 0.1566 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3355 | 0.3355 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3885 | 0.3885 | 0.1569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3495 | 0.3495 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5562 | 1.3229 | 1.3229 | 1.3229 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4419 | 1.3323 | 1.3323 | 1.3323 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5806 | 1.3935 | 1.3935 | 1.3935 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 37.83 |
Number of hours cooling loads not met | 111.33 |
Number of hours not met | 149.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 10.42 | 89287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 159.33 | 58550.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.49 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.17 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 90.59 | 20249.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.20 | 347.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 48.82 | 5763.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1397.21 |
Natural Gas | 0.00 | 10.42 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1407.63 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.51 |
Space Heating | 0.00 |
Space Cooling | 31.98 |
Fans (All) | 18.18 |
Service Water Heating | 9.80 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 280.44 |
Subtotal | 280.44 |
Natural Gas [MJ/m2] | |
Space Heating | 2.09 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 2.09 |
Subtotal | 2.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.42 |
Space Heating | 0.74 |
Space Cooling | 11.32 |
Fans (All) | 6.44 |
Service Water Heating | 3.47 |
Receptacle Equipment | 51.13 |
Miscellaneous | 5.49 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8720.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8700.50 | 59.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8707.67 | 52.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8717.00 | 43.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8707.17 | 52.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8708.83 | 51.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8695.17 | 64.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8684.00 | 76.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8684.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 76.00 | 0.00 | 0.00 | 0.00 |
Average | 8727.64 | 32.36 | 0.00 | 0.00 | 0.00 |
Sum | 157097.50 | 582.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128291.33 | 12.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 12.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.63 | 0.70 | 0.00 | 0.00 | 0.00 |
Sum | 614567.33 | 12.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7662.83 | 1097.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8364.17 | 395.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8641.83 | 118.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8645.50 | 114.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8645.67 | 114.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8598.50 | 161.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8571.67 | 188.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8596.83 | 163.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8431.50 | 328.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8709.33 | 50.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8601.50 | 158.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8590.67 | 169.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8477.33 | 282.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8208.33 | 551.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8592.50 | 167.50 | 0.00 | 0.00 | 0.00 |
Min | 7662.83 | 25.33 | 0.00 | 0.00 | 0.00 |
Max | 8734.67 | 1097.17 | 0.00 | 0.00 | 0.00 |
Average | 8529.69 | 230.31 | 0.00 | 0.00 | 0.00 |
Sum | 153534.33 | 4145.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127758.67 | 545.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128144.83 | 159.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128241.67 | 62.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24742.17 | 166.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128241.67 | 545.33 | 0.00 | 0.00 | 0.00 |
Average | 34091.45 | 51.88 | 0.00 | 0.00 | 0.00 |
Sum | 613646.17 | 933.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189108E+11 | 36013.85 | 17-JAN-07:03 | 15.33 | 13.25 | 0.199234E+10 | 2606.76 | 10-JAN-14:09 | 15.33 | 13.25 |
February | 0.171918E+11 | 27262.54 | 03-FEB-07:03 | 14.33 | 5.13 | 0.180722E+10 | 2606.91 | 01-FEB-14:09 | 14.33 | 5.13 |
March | 0.199648E+11 | 31219.69 | 24-MAR-06:03 | 12.17 | 12.17 | 0.215859E+10 | 2606.73 | 01-MAR-14:09 | 12.17 | 12.17 |
April | 0.204064E+11 | 36155.38 | 28-APR-06:02 | 14.17 | 12.31 | 0.191836E+10 | 2606.81 | 13-APR-09:00 | 14.17 | 12.31 |
May | 0.223113E+11 | 36462.77 | 01-MAY-06:02 | 14.17 | 12.31 | 0.207830E+10 | 2606.85 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.234499E+11 | 38901.28 | 26-JUN-05:12 | 17.33 | 15.20 | 0.207210E+10 | 2606.65 | 02-JUN-09:00 | 17.33 | 15.20 |
July | 0.242423E+11 | 39693.21 | 31-JUL-05:12 | 17.00 | 16.37 | 0.192641E+10 | 2606.65 | 12-JUL-09:00 | 17.00 | 16.37 |
August | 0.261785E+11 | 39589.42 | 21-AUG-05:12 | 16.83 | 15.53 | 0.216168E+10 | 2606.63 | 15-AUG-13:50 | 16.83 | 15.53 |
September | 0.230604E+11 | 39531.35 | 25-SEP-05:12 | 17.00 | 16.37 | 0.191988E+10 | 2606.67 | 21-SEP-09:09 | 17.00 | 16.37 |
October | 0.239361E+11 | 40213.47 | 16-OCT-05:12 | 18.33 | 9.34 | 0.199598E+10 | 2606.78 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.204659E+11 | 37358.79 | 13-NOV-07:02 | 12.33 | 11.14 | 0.197525E+10 | 2606.95 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.194002E+11 | 35436.53 | 08-DEC-07:02 | 11.37 | 11.15 | 0.192263E+10 | 2607.04 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.259518E+12 | 0.239287E+11 | ||||||||
Minimum of Months | 0.171918E+11 | 27262.54 | 11.37 | 5.13 | 0.180722E+10 | 2606.63 | 12.17 | 5.13 | ||
Maximum of Months | 0.261785E+11 | 40213.47 | 18.33 | 16.37 | 0.216168E+10 | 2607.04 | 23.00 | 16.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130568E+10 | 5163.16 | 18-JAN-15:00 | 23.00 | 14.79 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 14.79 |
February | 0.118164E+10 | 4754.49 | 01-FEB-13:50 | 19.83 | 15.75 | 0.00 | 0.00 | 01-FEB-00:10 | 19.83 | 15.75 |
March | 0.167559E+10 | 6307.40 | 23-MAR-14:30 | 22.50 | 17.35 | 0.00 | 0.00 | 01-MAR-00:10 | 22.50 | 17.35 |
April | 0.304418E+10 | 7980.67 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.299407E+10 | 7131.66 | 03-MAY-13:30 | 23.50 | 15.91 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 15.91 |
June | 0.395528E+10 | 7053.15 | 30-JUN-13:30 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.496674E+10 | 8396.69 | 31-JUL-13:30 | 27.50 | 21.02 | 0.00 | 0.00 | 01-JUL-00:10 | 27.50 | 21.02 |
August | 0.518870E+10 | 8120.30 | 14-AUG-13:10 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.362368E+10 | 9294.46 | 29-SEP-14:20 | 33.67 | 17.73 | 0.00 | 0.00 | 01-SEP-00:10 | 33.67 | 17.73 |
October | 0.315851E+10 | 9294.88 | 16-OCT-13:10 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.150570E+10 | 4594.73 | 10-NOV-14:20 | 19.67 | 15.74 | 0.00 | 0.00 | 01-NOV-00:10 | 19.67 | 15.74 |
December | 0.130586E+10 | 4610.16 | 19-DEC-14:10 | 22.83 | 9.79 | 0.00 | 0.00 | 01-DEC-00:10 | 22.83 | 9.79 |
Annual Sum or Average | 0.339056E+11 | 0.00 | ||||||||
Minimum of Months | 0.118164E+10 | 4594.73 | 19.67 | 9.79 | 0.00 | 0.00 | 19.67 | 9.79 | ||
Maximum of Months | 0.518870E+10 | 9294.88 | 33.75 | 21.02 | 0.00 | 0.00 | 33.75 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.580461E+09 | 1842.66 | 10-JAN-07:02 | 4.67 | 1.27 | 0.00 | 0.00 | 01-JAN-00:10 | 4.67 | 1.27 |
February | 0.576252E+09 | 1405.43 | 03-FEB-16:20 | 20.00 | 10.06 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 10.06 |
March | 0.653311E+09 | 1947.67 | 30-MAR-06:02 | 5.58 | 4.20 | 0.00 | 0.00 | 01-MAR-00:10 | 5.58 | 4.20 |
April | 0.118832E+10 | 2412.42 | 26-APR-15:50 | 22.17 | 16.38 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.38 |
May | 0.129594E+10 | 2308.50 | 03-MAY-15:50 | 21.17 | 15.06 | 0.00 | 0.00 | 01-MAY-00:10 | 21.17 | 15.06 |
June | 0.186284E+10 | 2633.71 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.240432E+10 | 3253.18 | 31-JUL-15:40 | 24.67 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 24.67 | 20.10 |
August | 0.263701E+10 | 3122.97 | 14-AUG-16:00 | 25.00 | 18.49 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 18.49 |
September | 0.192701E+10 | 3797.54 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.188927E+10 | 4548.01 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.776653E+09 | 1441.38 | 10-NOV-15:10 | 18.83 | 15.81 | 0.00 | 0.00 | 01-NOV-00:10 | 18.83 | 15.81 |
December | 0.617165E+09 | 1627.56 | 19-DEC-15:40 | 21.33 | 8.71 | 0.00 | 0.00 | 01-DEC-00:10 | 21.33 | 8.71 |
Annual Sum or Average | 0.164085E+11 | 0.00 | ||||||||
Minimum of Months | 0.576252E+09 | 1405.43 | 4.67 | 1.27 | 0.00 | 0.00 | 4.67 | 1.27 | ||
Maximum of Months | 0.263701E+10 | 4548.01 | 32.00 | 20.10 | 0.00 | 0.00 | 32.00 | 20.10 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119040E+10 | 2576.20 | 18-JAN-15:30 | 22.50 | 15.11 | 0.00 | 0.00 | 01-JAN-00:10 | 22.50 | 15.11 |
February | 0.108190E+10 | 2138.57 | 03-FEB-16:00 | 21.00 | 10.02 | 0.00 | 0.00 | 01-FEB-00:10 | 21.00 | 10.02 |
March | 0.118539E+10 | 2489.37 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.178015E+10 | 2887.24 | 26-APR-15:40 | 22.33 | 16.35 | 0.00 | 0.00 | 01-APR-00:10 | 22.33 | 16.35 |
May | 0.194843E+10 | 2703.91 | 04-MAY-15:20 | 22.00 | 16.22 | 0.00 | 0.00 | 01-MAY-00:10 | 22.00 | 16.22 |
June | 0.246013E+10 | 3002.73 | 26-JUN-16:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.00 | 17.40 |
July | 0.301822E+10 | 3801.06 | 31-JUL-15:20 | 25.33 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 25.33 | 20.29 |
August | 0.334195E+10 | 3693.34 | 14-AUG-15:50 | 25.17 | 18.63 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 18.63 |
September | 0.264114E+10 | 4096.69 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.270764E+10 | 4620.71 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.160230E+10 | 2926.99 | 01-NOV-06:07 | 11.83 | 10.47 | 0.00 | 0.00 | 01-NOV-00:10 | 11.83 | 10.47 |
December | 0.130228E+10 | 2512.73 | 19-DEC-16:00 | 21.00 | 8.28 | 0.00 | 0.00 | 01-DEC-00:10 | 21.00 | 8.28 |
Annual Sum or Average | 0.242599E+11 | 0.00 | ||||||||
Minimum of Months | 0.108190E+10 | 2138.57 | 11.83 | 8.28 | 0.00 | 0.00 | 11.83 | 8.28 | ||
Maximum of Months | 0.334195E+10 | 4620.71 | 32.00 | 20.29 | 0.00 | 0.00 | 32.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114681E+11 | 13610.15 | 19-JAN-16:20 | 18.67 | 14.64 | 0.193946E+10 | 2606.66 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.106419E+11 | 13276.84 | 03-FEB-17:00 | 18.00 | 9.93 | 0.176693E+10 | 2606.86 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.122882E+11 | 13845.32 | 24-MAR-16:00 | 18.00 | 14.96 | 0.211469E+10 | 2606.69 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.134181E+11 | 14834.82 | 27-APR-16:00 | 18.00 | 14.37 | 0.189600E+10 | 2606.75 | 13-APR-09:00 | 18.00 | 14.37 |
May | 0.145840E+11 | 14888.45 | 04-MAY-16:00 | 22.00 | 15.83 | 0.205949E+10 | 2606.80 | 03-MAY-13:00 | 22.00 | 15.83 |
June | 0.157226E+11 | 15265.46 | 30-JUN-16:00 | 22.70 | 17.88 | 0.206040E+10 | 2606.64 | 22-JUN-09:50 | 22.70 | 17.88 |
July | 0.166349E+11 | 16604.96 | 31-JUL-05:12 | 17.00 | 16.37 | 0.191762E+10 | 2606.63 | 13-JUL-09:09 | 17.00 | 16.37 |
August | 0.178461E+11 | 15930.07 | 14-AUG-16:00 | 25.00 | 18.49 | 0.215361E+10 | 2606.62 | 21-AUG-09:50 | 21.50 | 17.17 |
September | 0.152196E+11 | 16140.07 | 29-SEP-16:00 | 32.00 | 16.86 | 0.190811E+10 | 2606.65 | 21-SEP-09:09 | 32.00 | 16.86 |
October | 0.157748E+11 | 31004.34 | 16-OCT-05:12 | 18.33 | 9.34 | 0.198265E+10 | 2606.72 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.125428E+11 | 13978.88 | 01-NOV-16:00 | 16.80 | 12.58 | 0.195007E+10 | 2606.83 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.118346E+11 | 13507.26 | 07-DEC-16:30 | 17.00 | 14.57 | 0.188592E+10 | 2606.95 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.167976E+12 | 0.236350E+11 | ||||||||
Minimum of Months | 0.106419E+11 | 13276.84 | 16.80 | 9.34 | 0.176693E+10 | 2606.62 | 16.83 | 9.93 | ||
Maximum of Months | 0.178461E+11 | 31004.34 | 32.00 | 18.49 | 0.215361E+10 | 2606.95 | 32.00 | 17.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101927E+11 | 13137.67 | 18-JAN-15:50 | 22.17 | 15.30 | 0.185442E+10 | 2606.67 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.966137E+10 | 12921.12 | 02-FEB-16:20 | 17.67 | 13.13 | 0.169869E+10 | 2606.88 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.113727E+11 | 14361.86 | 24-MAR-15:40 | 18.00 | 15.12 | 0.203074E+10 | 2606.64 | 09-MAR-14:09 | 18.00 | 15.12 |
April | 0.129563E+11 | 16011.30 | 27-APR-15:20 | 18.80 | 14.83 | 0.186600E+10 | 2606.71 | 13-APR-09:00 | 18.80 | 14.83 |
May | 0.140653E+11 | 16193.46 | 03-MAY-15:20 | 21.67 | 15.26 | 0.203473E+10 | 2606.82 | 03-MAY-13:00 | 21.67 | 15.26 |
June | 0.157195E+11 | 16794.89 | 30-JUN-15:20 | 22.90 | 17.86 | 0.204748E+10 | 2606.64 | 27-JUN-09:09 | 22.90 | 17.86 |
July | 0.169256E+11 | 17653.23 | 31-JUL-15:20 | 25.33 | 20.29 | 0.190915E+10 | 2606.63 | 13-JUL-09:39 | 25.33 | 20.29 |
August | 0.179554E+11 | 17367.89 | 17-AUG-15:30 | 25.85 | 20.49 | 0.214396E+10 | 2606.62 | 14-AUG-13:20 | 25.85 | 20.49 |
September | 0.146420E+11 | 17660.29 | 29-SEP-14:50 | 33.17 | 17.55 | 0.189248E+10 | 2606.67 | 13-SEP-09:09 | 33.17 | 17.55 |
October | 0.146835E+11 | 19448.16 | 16-OCT-14:00 | 32.00 | 15.83 | 0.196007E+10 | 2606.69 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.110242E+11 | 13233.23 | 01-NOV-16:00 | 16.80 | 12.58 | 0.189531E+10 | 2606.82 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.104289E+11 | 12997.69 | 07-DEC-16:00 | 18.00 | 14.97 | 0.180857E+10 | 2606.93 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.159627E+12 | 0.231416E+11 | ||||||||
Minimum of Months | 0.966137E+10 | 12921.12 | 16.80 | 12.58 | 0.169869E+10 | 2606.62 | 16.83 | 12.37 | ||
Maximum of Months | 0.179554E+11 | 19448.16 | 33.17 | 20.49 | 0.214396E+10 | 2606.93 | 33.17 | 20.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171217E+10 | 2765.58 | 18-JAN-15:00 | 23.00 | 14.79 | 0.364728E+09 | 549.49 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.166301E+10 | 2395.92 | 03-FEB-15:00 | 23.00 | 8.84 | 0.337629E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.203186E+10 | 3035.09 | 23-MAR-15:20 | 21.67 | 17.34 | 0.403131E+09 | 549.49 | 10-MAR-14:00 | 21.67 | 17.34 |
April | 0.256467E+10 | 4172.78 | 26-APR-14:00 | 26.00 | 16.74 | 0.382053E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.297680E+10 | 4491.83 | 04-MAY-13:50 | 23.00 | 16.67 | 0.420931E+09 | 549.54 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.365055E+10 | 4322.10 | 27-JUN-16:00 | 22.00 | 18.09 | 0.428483E+09 | 549.49 | 27-JUN-09:09 | 22.00 | 18.09 |
July | 0.408950E+10 | 4922.66 | 31-JUL-14:00 | 27.00 | 20.84 | 0.401088E+09 | 549.49 | 13-JUL-09:39 | 27.00 | 20.84 |
August | 0.410720E+10 | 4794.37 | 18-AUG-15:00 | 27.00 | 20.85 | 0.448877E+09 | 549.49 | 14-AUG-13:20 | 27.00 | 20.85 |
September | 0.311963E+10 | 5680.59 | 29-SEP-13:50 | 34.33 | 17.92 | 0.392524E+09 | 549.49 | 13-SEP-09:30 | 34.33 | 17.92 |
October | 0.305763E+10 | 5841.53 | 16-OCT-13:10 | 33.75 | 16.65 | 0.404111E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.192231E+10 | 2484.36 | 10-NOV-14:10 | 19.83 | 15.69 | 0.379309E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.177272E+10 | 2723.00 | 05-DEC-15:00 | 25.00 | 13.22 | 0.354944E+09 | 549.50 | 04-DEC-14:20 | 25.00 | 13.22 |
Annual Sum or Average | 0.326681E+11 | 0.471781E+10 | ||||||||
Minimum of Months | 0.166301E+10 | 2395.92 | 19.83 | 8.84 | 0.337629E+09 | 549.49 | 18.00 | 8.84 | ||
Maximum of Months | 0.410720E+10 | 5841.53 | 34.33 | 20.85 | 0.448877E+09 | 549.54 | 34.33 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166511E+10 | 3184.10 | 20-JAN-10:00 | 19.00 | 14.77 | 0.245784E+09 | 347.88 | 05-JAN-10:00 | 19.00 | 14.77 |
February | 0.160778E+10 | 2991.86 | 02-FEB-10:10 | 17.17 | 12.19 | 0.223278E+09 | 347.91 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.203904E+10 | 4799.40 | 23-MAR-09:30 | 20.50 | 15.62 | 0.267263E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.292455E+10 | 6167.89 | 30-APR-10:23 | 25.50 | 16.81 | 0.249193E+09 | 347.91 | 13-APR-09:00 | 25.50 | 16.81 |
May | 0.298365E+10 | 5373.53 | 28-MAY-09:03 | 19.33 | 14.45 | 0.269919E+09 | 347.91 | 03-MAY-13:00 | 19.33 | 14.45 |
June | 0.354138E+10 | 10093.07 | 25-JUN-09:02 | 22.17 | 16.55 | 0.271761E+09 | 347.89 | 22-JUN-09:00 | 22.17 | 16.55 |
July | 0.423882E+10 | 11531.39 | 23-JUL-09:53 | 25.00 | 20.21 | 0.254930E+09 | 347.88 | 17-JUL-09:50 | 25.00 | 20.21 |
August | 0.447004E+10 | 7437.74 | 20-AUG-09:43 | 22.00 | 18.63 | 0.285791E+09 | 347.88 | 31-AUG-09:09 | 23.00 | 18.43 |
September | 0.315400E+10 | 9788.99 | 10-SEP-08:43 | 21.50 | 17.28 | 0.250112E+09 | 347.89 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.293323E+10 | 11470.41 | 15-OCT-08:43 | 32.33 | 15.60 | 0.260218E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.182618E+10 | 2757.10 | 01-NOV-09:30 | 15.00 | 12.66 | 0.251016E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.170771E+10 | 3128.83 | 05-DEC-09:50 | 25.67 | 12.88 | 0.238534E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.330915E+11 | 0.306780E+10 | ||||||||
Minimum of Months | 0.160778E+10 | 2757.10 | 15.00 | 12.19 | 0.223278E+09 | 347.88 | 17.17 | 11.71 | ||
Maximum of Months | 0.447004E+10 | 11531.39 | 32.33 | 20.21 | 0.285791E+09 | 347.91 | 25.50 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499803E+10 | 14726.71 | 22-JAN-12:32 | 17.00 | 12.24 | 0.403044E+09 | 549.80 | 18-JAN-14:00 | 17.00 | 12.24 |
February | 0.374429E+10 | 11971.29 | 20-FEB-12:43 | 17.00 | 10.17 | 0.359654E+09 | 549.79 | 03-FEB-14:50 | 17.00 | 10.17 |
March | 0.375945E+10 | 10051.52 | 19-MAR-13:13 | 19.67 | 15.00 | 0.422705E+09 | 549.74 | 23-MAR-13:00 | 23.00 | 17.27 |
April | 0.408858E+10 | 7728.96 | 26-APR-13:10 | 26.83 | 17.07 | 0.387278E+09 | 549.52 | 13-APR-13:50 | 26.83 | 17.07 |
May | 0.347040E+10 | 5906.52 | 04-MAY-12:40 | 23.33 | 16.64 | 0.419918E+09 | 549.55 | 03-MAY-13:00 | 23.33 | 16.64 |
June | 0.385155E+10 | 5329.63 | 30-JUN-13:10 | 23.00 | 17.85 | 0.426336E+09 | 549.49 | 27-JUN-09:09 | 23.00 | 17.85 |
July | 0.454918E+10 | 7289.80 | 31-JUL-12:50 | 28.00 | 21.19 | 0.400086E+09 | 549.49 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.566133E+10 | 8361.91 | 30-AUG-13:00 | 24.00 | 18.12 | 0.449427E+09 | 549.50 | 14-AUG-13:20 | 24.00 | 18.12 |
September | 0.552740E+10 | 12192.16 | 10-SEP-14:02 | 22.83 | 18.25 | 0.396224E+09 | 562.42 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.623005E+10 | 15393.39 | 29-OCT-12:32 | 22.33 | 15.66 | 0.413000E+09 | 577.85 | 16-OCT-13:09 | 22.33 | 15.66 |
November | 0.512708E+10 | 15648.67 | 19-NOV-12:52 | 27.00 | 14.96 | 0.403907E+09 | 549.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.526103E+10 | 14568.00 | 17-DEC-13:32 | 22.67 | 10.00 | 0.390956E+09 | 549.81 | 20-DEC-14:50 | 19.20 | 11.87 |
Annual Sum or Average | 0.562684E+11 | 0.487253E+10 | ||||||||
Minimum of Months | 0.347040E+10 | 5329.63 | 17.00 | 10.00 | 0.359654E+09 | 549.49 | 17.00 | 10.17 | ||
Maximum of Months | 0.623005E+10 | 15648.67 | 28.00 | 21.19 | 0.449427E+09 | 577.85 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184934E+10 | 4689.69 | 18-JAN-15:00 | 23.00 | 14.79 | 0.232595E+09 | 347.85 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.183918E+10 | 5024.64 | 22-FEB-15:50 | 16.30 | 12.09 | 0.212157E+09 | 347.89 | 01-FEB-14:09 | 16.30 | 12.09 |
March | 0.231704E+10 | 6546.39 | 23-MAR-15:50 | 21.17 | 17.23 | 0.252481E+09 | 347.86 | 10-MAR-14:00 | 21.17 | 17.23 |
April | 0.312908E+10 | 11885.00 | 30-APR-16:33 | 22.00 | 15.83 | 0.238725E+09 | 347.87 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.326092E+10 | 12321.40 | 28-MAY-16:33 | 19.33 | 14.37 | 0.262046E+09 | 347.89 | 03-MAY-13:00 | 19.33 | 14.37 |
June | 0.390372E+10 | 12311.23 | 18-JUN-16:23 | 21.50 | 17.31 | 0.267792E+09 | 347.85 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.438687E+10 | 13402.56 | 09-JUL-16:02 | 20.67 | 15.87 | 0.252301E+09 | 347.85 | 17-JUL-09:00 | 23.00 | 17.86 |
August | 0.454049E+10 | 12172.68 | 27-AUG-15:23 | 22.00 | 18.09 | 0.282390E+09 | 347.85 | 14-AUG-13:20 | 22.00 | 18.09 |
September | 0.349849E+10 | 12184.51 | 10-SEP-16:03 | 21.83 | 16.78 | 0.246167E+09 | 347.85 | 05-SEP-13:09 | 21.83 | 16.78 |
October | 0.312294E+10 | 12708.88 | 15-OCT-15:22 | 30.50 | 15.19 | 0.252904E+09 | 347.86 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.218826E+10 | 4779.50 | 10-NOV-14:50 | 19.17 | 15.85 | 0.237850E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.192584E+10 | 4697.27 | 19-DEC-15:30 | 21.50 | 8.94 | 0.225065E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.359622E+11 | 0.296247E+10 | ||||||||
Minimum of Months | 0.183918E+10 | 4689.69 | 16.30 | 8.94 | 0.212157E+09 | 347.85 | 16.30 | 11.58 | ||
Maximum of Months | 0.454049E+10 | 13402.56 | 30.50 | 18.09 | 0.282390E+09 | 347.91 | 24.00 | 18.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188300E+10 | 2213.57 | 18-JAN-14:10 | 24.33 | 14.82 | 0.374118E+09 | 549.49 | 18-JAN-14:00 | 23.00 | 14.79 |
February | 0.171936E+10 | 1839.19 | 01-FEB-12:10 | 25.67 | 14.54 | 0.339750E+09 | 548.37 | 01-FEB-14:30 | 19.00 | 15.33 |
March | 0.200004E+10 | 1897.01 | 23-MAR-15:20 | 21.67 | 17.34 | 0.405301E+09 | 549.48 | 23-MAR-13:09 | 21.67 | 17.34 |
April | 0.214484E+10 | 2746.89 | 26-APR-14:00 | 26.00 | 16.74 | 0.383420E+09 | 549.50 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.250069E+10 | 3179.14 | 04-MAY-14:10 | 22.83 | 16.63 | 0.424205E+09 | 549.53 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.290921E+10 | 3130.03 | 27-JUN-16:00 | 22.00 | 18.09 | 0.429774E+09 | 549.49 | 23-JUN-09:09 | 22.00 | 18.09 |
July | 0.335522E+10 | 3722.79 | 31-JUL-13:10 | 27.83 | 21.13 | 0.402114E+09 | 549.49 | 11-JUL-09:09 | 27.83 | 21.13 |
August | 0.338666E+10 | 3660.51 | 18-AUG-15:00 | 27.00 | 20.85 | 0.450462E+09 | 549.49 | 15-AUG-13:00 | 27.00 | 20.85 |
September | 0.276306E+10 | 4283.42 | 29-SEP-13:10 | 35.67 | 18.16 | 0.396721E+09 | 549.49 | 13-SEP-09:09 | 35.67 | 18.16 |
October | 0.291240E+10 | 4580.09 | 16-OCT-12:30 | 35.05 | 17.21 | 0.410679E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.202397E+10 | 2088.30 | 19-NOV-12:23 | 26.50 | 15.22 | 0.389991E+09 | 549.50 | 10-NOV-10:00 | 26.50 | 15.22 |
December | 0.195357E+10 | 2086.10 | 19-DEC-13:40 | 24.00 | 10.42 | 0.363776E+09 | 547.80 | 05-DEC-14:00 | 24.00 | 10.42 |
Annual Sum or Average | 0.295520E+11 | 0.477031E+10 | ||||||||
Minimum of Months | 0.171936E+10 | 1839.19 | 21.67 | 10.42 | 0.339750E+09 | 547.80 | 19.00 | 10.42 | ||
Maximum of Months | 0.338666E+10 | 4580.09 | 35.67 | 21.13 | 0.450462E+09 | 549.53 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167980E+10 | 2951.83 | 20-JAN-09:50 | 18.67 | 14.64 | 0.255125E+09 | 347.88 | 05-JAN-10:00 | 18.67 | 14.64 |
February | 0.151172E+10 | 2689.51 | 21-FEB-10:00 | 17.00 | 11.03 | 0.228441E+09 | 347.90 | 01-FEB-14:09 | 17.00 | 11.03 |
March | 0.182612E+10 | 3853.99 | 23-MAR-09:30 | 20.50 | 15.62 | 0.273255E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.244811E+10 | 4718.40 | 30-APR-10:13 | 25.33 | 16.65 | 0.251699E+09 | 347.91 | 13-APR-09:00 | 25.33 | 16.65 |
May | 0.253272E+10 | 4190.15 | 04-MAY-09:30 | 21.00 | 15.49 | 0.272814E+09 | 347.90 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.290155E+10 | 4813.64 | 25-JUN-09:53 | 23.00 | 17.26 | 0.273312E+09 | 347.88 | 22-JUN-09:39 | 23.00 | 17.26 |
July | 0.364958E+10 | 8514.39 | 23-JUL-09:53 | 25.00 | 20.21 | 0.255974E+09 | 347.88 | 12-JUL-09:00 | 25.00 | 20.21 |
August | 0.390426E+10 | 5565.54 | 06-AUG-10:13 | 23.67 | 19.78 | 0.287151E+09 | 347.88 | 15-AUG-13:50 | 24.33 | 19.44 |
September | 0.281878E+10 | 5690.96 | 10-SEP-09:13 | 22.33 | 17.55 | 0.253185E+09 | 347.88 | 12-SEP-09:30 | 22.00 | 16.63 |
October | 0.279868E+10 | 9558.69 | 15-OCT-09:43 | 31.33 | 16.43 | 0.263630E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.183879E+10 | 2774.16 | 01-NOV-09:30 | 15.00 | 12.66 | 0.258097E+09 | 347.90 | 06-NOV-10:00 | 19.00 | 13.20 |
December | 0.170333E+10 | 2911.81 | 05-DEC-09:50 | 25.67 | 12.88 | 0.247393E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.296134E+11 | 0.312008E+10 | ||||||||
Minimum of Months | 0.151172E+10 | 2689.51 | 15.00 | 11.03 | 0.228441E+09 | 347.88 | 17.00 | 11.03 | ||
Maximum of Months | 0.390426E+10 | 9558.69 | 31.33 | 20.21 | 0.287151E+09 | 347.91 | 25.33 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417641E+10 | 11837.64 | 22-JAN-12:03 | 17.00 | 11.99 | 0.403946E+09 | 549.79 | 18-JAN-14:00 | 17.00 | 11.99 |
February | 0.282769E+10 | 8676.09 | 20-FEB-15:03 | 17.00 | 11.69 | 0.355375E+09 | 549.73 | 03-FEB-14:00 | 17.00 | 11.69 |
March | 0.254898E+10 | 6651.64 | 23-MAR-14:00 | 23.00 | 17.27 | 0.410771E+09 | 549.52 | 01-MAR-14:09 | 23.00 | 17.27 |
April | 0.274546E+10 | 6543.74 | 26-APR-12:00 | 26.00 | 17.28 | 0.382633E+09 | 549.53 | 13-APR-09:00 | 26.00 | 17.28 |
May | 0.235498E+10 | 4160.49 | 04-MAY-12:30 | 23.50 | 16.62 | 0.409298E+09 | 549.54 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.259045E+10 | 3627.65 | 27-JUN-13:00 | 24.00 | 18.72 | 0.416379E+09 | 549.50 | 12-JUN-13:09 | 24.00 | 18.72 |
July | 0.343297E+10 | 8334.47 | 31-JUL-12:00 | 28.00 | 21.19 | 0.396520E+09 | 549.49 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.445301E+10 | 8266.82 | 18-AUG-12:00 | 28.00 | 21.20 | 0.447311E+09 | 549.49 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.455442E+10 | 11798.05 | 29-SEP-12:00 | 36.00 | 18.21 | 0.396773E+09 | 680.69 | 29-SEP-12:09 | 36.00 | 18.21 |
October | 0.573455E+10 | 12603.72 | 29-OCT-12:32 | 22.33 | 15.66 | 0.416742E+09 | 706.23 | 16-OCT-12:09 | 22.33 | 15.66 |
November | 0.435170E+10 | 12514.38 | 19-NOV-12:23 | 26.50 | 15.22 | 0.404763E+09 | 549.98 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.465006E+10 | 12172.58 | 25-DEC-12:43 | 22.17 | 9.14 | 0.391877E+09 | 558.61 | 19-DEC-13:09 | 22.17 | 9.14 |
Annual Sum or Average | 0.444207E+11 | 0.483239E+10 | ||||||||
Minimum of Months | 0.235498E+10 | 3627.65 | 17.00 | 9.14 | 0.355375E+09 | 549.49 | 17.00 | 9.14 | ||
Maximum of Months | 0.573455E+10 | 12603.72 | 36.00 | 21.20 | 0.447311E+09 | 706.23 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175855E+10 | 3645.19 | 18-JAN-15:30 | 22.50 | 15.11 | 0.244508E+09 | 347.85 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.164040E+10 | 4050.17 | 22-FEB-16:30 | 15.00 | 12.17 | 0.221589E+09 | 347.88 | 01-FEB-14:09 | 15.00 | 12.17 |
March | 0.196529E+10 | 4830.20 | 23-MAR-16:00 | 21.00 | 17.19 | 0.263146E+09 | 347.85 | 01-MAR-14:09 | 21.00 | 17.19 |
April | 0.251557E+10 | 6298.94 | 30-APR-16:53 | 22.00 | 15.83 | 0.247435E+09 | 347.86 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.269213E+10 | 8005.39 | 28-MAY-16:33 | 19.33 | 14.37 | 0.270531E+09 | 347.88 | 03-MAY-13:00 | 19.33 | 14.37 |
June | 0.317556E+10 | 5360.06 | 29-JUN-16:00 | 23.00 | 18.43 | 0.272759E+09 | 347.85 | 23-JUN-09:09 | 23.00 | 18.43 |
July | 0.375881E+10 | 9851.20 | 30-JUL-16:42 | 21.17 | 18.40 | 0.255845E+09 | 347.85 | 12-JUL-09:00 | 21.17 | 18.40 |
August | 0.391995E+10 | 7593.51 | 27-AUG-16:23 | 21.00 | 17.45 | 0.286863E+09 | 347.85 | 15-AUG-13:00 | 21.00 | 17.45 |
September | 0.309972E+10 | 9703.71 | 04-SEP-16:23 | 19.00 | 15.57 | 0.253583E+09 | 347.85 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.286726E+10 | 7806.25 | 15-OCT-15:43 | 30.17 | 14.99 | 0.261785E+09 | 347.85 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.204420E+10 | 4032.56 | 07-NOV-15:40 | 19.00 | 14.59 | 0.251617E+09 | 347.89 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.183416E+10 | 3906.03 | 19-DEC-15:30 | 21.50 | 8.94 | 0.237767E+09 | 347.90 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.312716E+11 | 0.306743E+10 | ||||||||
Minimum of Months | 0.164040E+10 | 3645.19 | 15.00 | 8.94 | 0.221589E+09 | 347.85 | 15.00 | 12.17 | ||
Maximum of Months | 0.391995E+10 | 9851.20 | 30.17 | 18.43 | 0.286863E+09 | 347.90 | 26.83 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197415E+10 | 2758.18 | 18-JAN-14:10 | 24.33 | 14.82 | 0.381296E+09 | 549.49 | 24-JAN-14:30 | 24.50 | 15.08 |
February | 0.184842E+10 | 2473.10 | 03-FEB-15:00 | 23.00 | 8.84 | 0.353132E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.220627E+10 | 2874.36 | 23-MAR-15:20 | 21.67 | 17.34 | 0.420751E+09 | 549.49 | 09-MAR-14:09 | 21.67 | 17.34 |
April | 0.260866E+10 | 3797.29 | 26-APR-14:00 | 26.00 | 16.74 | 0.391403E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.302619E+10 | 4132.97 | 04-MAY-14:10 | 22.83 | 16.63 | 0.429051E+09 | 549.54 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.361107E+10 | 3994.68 | 26-JUN-16:00 | 22.00 | 17.40 | 0.432487E+09 | 549.50 | 22-JUN-09:50 | 22.00 | 17.40 |
July | 0.398376E+10 | 4504.28 | 31-JUL-13:10 | 27.83 | 21.13 | 0.403245E+09 | 549.49 | 13-JUL-09:09 | 27.83 | 21.13 |
August | 0.403157E+10 | 4391.42 | 18-AUG-15:00 | 27.00 | 20.85 | 0.451966E+09 | 549.49 | 15-AUG-13:50 | 27.00 | 20.85 |
September | 0.317833E+10 | 5165.05 | 29-SEP-13:10 | 35.67 | 18.16 | 0.398544E+09 | 549.49 | 13-SEP-09:09 | 35.67 | 18.16 |
October | 0.320092E+10 | 5367.18 | 16-OCT-12:30 | 35.05 | 17.21 | 0.412147E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.213281E+10 | 2564.46 | 01-NOV-14:00 | 17.00 | 13.47 | 0.395450E+09 | 549.52 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.202914E+10 | 2741.74 | 05-DEC-15:00 | 25.00 | 13.22 | 0.372484E+09 | 549.54 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.338313E+11 | 0.484196E+10 | ||||||||
Minimum of Months | 0.184842E+10 | 2473.10 | 17.00 | 8.84 | 0.353132E+09 | 549.49 | 19.00 | 8.84 | ||
Maximum of Months | 0.403157E+10 | 5367.18 | 35.67 | 21.13 | 0.451966E+09 | 549.54 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188391E+10 | 3774.07 | 20-JAN-09:30 | 18.00 | 14.38 | 0.184798E+09 | 338.73 | 05-JAN-11:20 | 18.00 | 14.38 |
February | 0.178924E+10 | 3625.62 | 21-FEB-09:40 | 16.00 | 10.67 | 0.167574E+09 | 338.75 | 01-FEB-13:39 | 16.00 | 10.67 |
March | 0.221223E+10 | 5154.66 | 23-MAR-09:00 | 19.00 | 14.76 | 0.200118E+09 | 338.74 | 10-MAR-08:09 | 19.00 | 14.76 |
April | 0.295362E+10 | 6444.80 | 30-APR-10:23 | 25.50 | 16.81 | 0.185000E+09 | 338.76 | 13-APR-10:09 | 25.50 | 16.81 |
May | 0.298999E+10 | 6995.01 | 28-MAY-08:23 | 18.50 | 14.07 | 0.200650E+09 | 338.77 | 24-MAY-10:39 | 18.50 | 14.07 |
June | 0.343565E+10 | 7349.05 | 25-JUN-09:53 | 23.00 | 17.26 | 0.201286E+09 | 338.73 | 02-JUN-10:09 | 23.00 | 17.26 |
July | 0.408420E+10 | 11719.04 | 23-JUL-09:02 | 25.00 | 19.70 | 0.189053E+09 | 338.73 | 12-JUL-10:09 | 25.00 | 19.70 |
August | 0.432833E+10 | 11194.43 | 13-AUG-08:53 | 24.00 | 19.32 | 0.211237E+09 | 338.72 | 22-AUG-10:20 | 21.33 | 15.75 |
September | 0.314016E+10 | 6874.82 | 03-SEP-08:43 | 19.67 | 15.00 | 0.185937E+09 | 338.73 | 13-SEP-08:39 | 21.33 | 17.45 |
October | 0.301724E+10 | 11371.21 | 15-OCT-08:23 | 31.00 | 15.00 | 0.193616E+09 | 338.76 | 18-OCT-12:09 | 23.83 | 17.80 |
November | 0.202157E+10 | 3501.05 | 13-NOV-09:20 | 17.33 | 13.62 | 0.188029E+09 | 338.74 | 06-NOV-11:09 | 17.33 | 13.62 |
December | 0.192775E+10 | 3647.88 | 05-DEC-09:30 | 25.00 | 12.45 | 0.179896E+09 | 338.74 | 07-DEC-11:39 | 21.00 | 14.37 |
Annual Sum or Average | 0.337839E+11 | 0.228719E+10 | ||||||||
Minimum of Months | 0.178924E+10 | 3501.05 | 16.00 | 10.67 | 0.167574E+09 | 338.72 | 16.00 | 10.67 | ||
Maximum of Months | 0.432833E+10 | 11719.04 | 31.00 | 19.70 | 0.211237E+09 | 338.77 | 25.50 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545541E+10 | 13642.17 | 22-JAN-12:32 | 17.00 | 12.24 | 0.410768E+09 | 555.00 | 18-JAN-14:09 | 17.00 | 12.24 |
February | 0.403652E+10 | 12035.40 | 20-FEB-11:43 | 16.83 | 9.71 | 0.368811E+09 | 549.83 | 03-FEB-14:00 | 16.83 | 9.71 |
March | 0.395960E+10 | 9602.06 | 19-MAR-12:33 | 20.33 | 15.40 | 0.436591E+09 | 549.75 | 24-MAR-13:50 | 19.00 | 15.88 |
April | 0.407826E+10 | 7209.61 | 26-APR-13:00 | 27.00 | 17.13 | 0.395151E+09 | 549.53 | 13-APR-09:00 | 27.00 | 17.13 |
May | 0.346401E+10 | 5496.31 | 04-MAY-12:30 | 23.50 | 16.62 | 0.428715E+09 | 549.55 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.374436E+10 | 4872.86 | 30-JUN-13:10 | 23.00 | 17.85 | 0.431586E+09 | 549.49 | 22-JUN-09:50 | 23.00 | 17.85 |
July | 0.436179E+10 | 6816.11 | 31-JUL-12:40 | 28.00 | 21.19 | 0.403001E+09 | 549.49 | 28-JUL-13:39 | 28.00 | 21.19 |
August | 0.548129E+10 | 7895.49 | 30-AUG-12:50 | 23.83 | 17.97 | 0.452667E+09 | 549.67 | 30-AUG-13:09 | 23.83 | 18.18 |
September | 0.550978E+10 | 10814.49 | 29-SEP-13:10 | 35.67 | 18.16 | 0.401161E+09 | 568.47 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.635672E+10 | 13701.77 | 01-OCT-12:13 | 25.67 | 20.79 | 0.418285E+09 | 586.89 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.552974E+10 | 14264.24 | 19-NOV-12:52 | 27.00 | 14.96 | 0.410551E+09 | 549.95 | 08-NOV-14:50 | 27.00 | 14.96 |
December | 0.576201E+10 | 13491.63 | 25-DEC-12:53 | 22.00 | 9.04 | 0.398383E+09 | 555.80 | 19-DEC-14:09 | 22.00 | 9.04 |
Annual Sum or Average | 0.577395E+11 | 0.495567E+10 | ||||||||
Minimum of Months | 0.346401E+10 | 4872.86 | 16.83 | 9.04 | 0.368811E+09 | 549.49 | 16.83 | 9.04 | ||
Maximum of Months | 0.635672E+10 | 14264.24 | 35.67 | 21.19 | 0.452667E+09 | 586.89 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204348E+10 | 4643.18 | 18-JAN-15:00 | 23.00 | 14.79 | 0.241864E+09 | 347.85 | 09-JAN-14:00 | 23.00 | 14.79 |
February | 0.197832E+10 | 5026.69 | 22-FEB-15:40 | 16.60 | 12.17 | 0.221427E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.241919E+10 | 6338.76 | 23-MAR-15:50 | 21.17 | 17.23 | 0.263448E+09 | 347.86 | 01-MAR-14:09 | 21.17 | 17.23 |
April | 0.308761E+10 | 11174.80 | 30-APR-16:23 | 22.00 | 15.83 | 0.245963E+09 | 347.87 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.321287E+10 | 6975.70 | 28-MAY-17:23 | 18.00 | 14.13 | 0.269155E+09 | 347.89 | 03-MAY-13:00 | 18.00 | 14.13 |
June | 0.378104E+10 | 11484.97 | 18-JUN-16:23 | 21.50 | 17.31 | 0.272220E+09 | 347.85 | 22-JUN-09:50 | 22.67 | 17.06 |
July | 0.421014E+10 | 12191.83 | 30-JUL-16:12 | 21.67 | 18.54 | 0.254924E+09 | 347.85 | 13-JUL-09:09 | 21.67 | 18.54 |
August | 0.438856E+10 | 11282.46 | 27-AUG-15:23 | 22.00 | 18.09 | 0.285708E+09 | 347.85 | 15-AUG-13:00 | 22.00 | 18.09 |
September | 0.345434E+10 | 11641.89 | 10-SEP-15:32 | 22.00 | 17.02 | 0.251551E+09 | 347.85 | 12-SEP-09:39 | 22.33 | 16.84 |
October | 0.316021E+10 | 9406.03 | 15-OCT-15:02 | 30.83 | 15.40 | 0.259245E+09 | 347.86 | 03-OCT-13:00 | 30.83 | 15.40 |
November | 0.233335E+10 | 4753.36 | 07-NOV-15:30 | 19.00 | 14.51 | 0.247655E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.212331E+10 | 4662.89 | 19-DEC-15:30 | 21.50 | 8.94 | 0.235038E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.361924E+11 | 0.304820E+10 | ||||||||
Minimum of Months | 0.197832E+10 | 4643.18 | 16.60 | 8.94 | 0.221427E+09 | 347.85 | 16.60 | 12.17 | ||
Maximum of Months | 0.438856E+10 | 12191.83 | 30.83 | 18.54 | 0.285708E+09 | 347.91 | 30.83 | 18.54 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831065E+09 | 6003.89 | 03-JAN-07:02 | 3.67 |
February | 0.595640E+09 | 3846.62 | 09-FEB-06:03 | 6.45 |
March | 0.707826E+09 | 4966.26 | 30-MAR-06:02 | 5.58 |
April | 0.349365E+09 | 3508.12 | 20-APR-05:03 | 9.17 |
May | 0.294903E+09 | 3641.97 | 19-MAY-05:03 | 8.67 |
June | 0.142318E+09 | 3396.78 | 14-JUN-05:03 | 13.17 |
July | 77751134.06 | 2988.84 | 06-JUL-05:03 | 14.33 |
August | 93203350.11 | 3105.00 | 06-AUG-07:07 | 19.50 |
September | 0.184868E+09 | 3340.76 | 20-SEP-05:03 | 12.00 |
October | 0.319240E+09 | 3557.47 | 30-OCT-05:03 | 10.83 |
November | 0.558071E+09 | 3880.07 | 24-NOV-06:03 | 8.92 |
December | 0.766538E+09 | 3960.42 | 20-DEC-06:03 | 8.67 |
Annual Sum or Average | 0.492079E+10 | |||
Minimum of Months | 77751134.06 | 2988.84 | 3.67 | |
Maximum of Months | 0.831065E+09 | 6003.89 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358807E+09 | 3934.40 | 08-JAN-13:53 | 17.00 |
February | 0.209757E+09 | 3187.68 | 20-FEB-11:43 | 16.83 |
March | 0.287284E+09 | 2417.85 | 19-MAR-12:33 | 20.33 |
April | 42023824.54 | 2847.96 | 23-APR-14:10 | 18.83 |
May | 25247856.76 | 2342.22 | 14-MAY-14:27 | 18.50 |
June | 12703815.30 | 1785.81 | 18-JUN-15:43 | 22.17 |
July | 19017713.05 | 1787.27 | 09-JUL-09:23 | 19.50 |
August | 15369938.68 | 1786.00 | 13-AUG-08:53 | 24.00 |
September | 17142668.44 | 2390.60 | 17-SEP-11:53 | 21.00 |
October | 34891509.81 | 3381.10 | 15-OCT-09:43 | 31.33 |
November | 0.105711E+09 | 3468.65 | 05-NOV-12:02 | 18.00 |
December | 0.234030E+09 | 4134.38 | 25-DEC-12:53 | 22.00 |
Annual Sum or Average | 0.136199E+10 | |||
Minimum of Months | 12703815.30 | 1785.81 | 16.83 | |
Maximum of Months | 0.358807E+09 | 4134.38 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 91240792.68 | 2634.52 | 29-JAN-10:37 | 14.67 |
February | 42608209.77 | 2416.91 | 20-FEB-10:30 | 15.00 |
March | 46262623.42 | 2240.93 | 12-MAR-11:43 | 19.33 |
April | 16979550.55 | 2217.71 | 16-APR-14:55 | 18.00 |
May | 21317361.77 | 2122.70 | 14-MAY-15:32 | 17.33 |
June | 14756352.63 | 1849.63 | 04-JUN-14:15 | 20.00 |
July | 22970951.73 | 1795.05 | 17-JUL-05:12 | 15.67 |
August | 21243639.20 | 2147.08 | 13-AUG-13:40 | 24.00 |
September | 25191287.89 | 2152.00 | 04-SEP-10:30 | 21.00 |
October | 29987139.76 | 2331.26 | 08-OCT-11:03 | 21.83 |
November | 25902950.15 | 2598.14 | 19-NOV-09:07 | 24.33 |
December | 42581135.62 | 2752.25 | 24-DEC-10:50 | 15.33 |
Annual Sum or Average | 0.401042E+09 | |||
Minimum of Months | 14756352.63 | 1795.05 | 14.67 | |
Maximum of Months | 91240792.68 | 2752.25 | 24.33 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16478457.83 | 13599.69 | 02-JAN-07:03 | 11.00 |
February | 783250.51 | 3025.00 | 13-FEB-07:03 | 14.17 |
March | 1768676.62 | 12841.24 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 846923.87 | 5646.16 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 19877308.83 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 16478457.83 | 13599.69 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131818E+09 | 6004.25 | 09-JAN-06:12 | 2.33 |
February | 31794583.17 | 5259.16 | 06-FEB-07:03 | 9.50 |
March | 62285237.39 | 5764.47 | 30-MAR-05:12 | 5.03 |
April | 5260134.44 | 5255.27 | 01-APR-06:03 | 7.67 |
May | 120144.34 | 600.72 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 919171.73 | 5128.61 | 30-OCT-06:02 | 10.50 |
November | 17595301.46 | 5263.54 | 06-NOV-07:02 | 11.17 |
December | 60395156.68 | 5523.06 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.310188E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.131818E+09 | 6004.25 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43054073.08 | 4700.25 | 03-JAN-06:12 | 4.33 |
February | 12129936.71 | 3865.23 | 10-FEB-07:03 | 7.57 |
March | 18326362.95 | 4494.34 | 30-MAR-05:12 | 5.03 |
April | 1252436.38 | 3815.49 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 760482.89 | 3781.70 | 30-OCT-06:02 | 10.50 |
November | 3503105.80 | 3777.84 | 24-NOV-07:03 | 8.75 |
December | 15006167.15 | 4228.11 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 94032564.96 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 43054073.08 | 4700.25 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50647558.07 | 6522.27 | 03-JAN-06:12 | 4.33 |
February | 15320746.49 | 5700.41 | 11-FEB-07:03 | 8.08 |
March | 39175086.63 | 6372.75 | 30-MAR-05:12 | 5.03 |
April | 4204902.00 | 5727.68 | 01-APR-06:03 | 7.67 |
May | 937663.20 | 3618.38 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 3508388.31 | 5155.79 | 27-NOV-07:03 | 14.67 |
December | 15936798.02 | 5707.37 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 0.129731E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 50647558.07 | 6522.27 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78628547.13 | 4770.03 | 03-JAN-06:12 | 4.33 |
February | 20773944.18 | 3917.04 | 06-FEB-07:03 | 9.50 |
March | 39152952.34 | 4501.05 | 30-MAR-05:12 | 5.03 |
April | 4313144.07 | 3921.37 | 01-APR-06:03 | 7.67 |
May | 768091.67 | 1849.57 | 15-MAY-06:03 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1300601.37 | 3786.93 | 30-OCT-06:02 | 10.50 |
November | 12392870.53 | 3926.67 | 06-NOV-07:02 | 11.17 |
December | 38143469.13 | 4280.37 | 13-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.195474E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 78628547.13 | 4770.03 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8514270.54 | 3692.82 | 03-JAN-07:02 | 3.67 |
February | 797875.31 | 1688.82 | 06-FEB-07:03 | 9.50 |
March | 5187775.57 | 3661.66 | 30-MAR-06:02 | 5.58 |
April | 489273.61 | 3261.82 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1053810.90 | 2955.22 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 16043005.92 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 8514270.54 | 3692.82 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 860435.50 | 2640.15 | 03-JAN-07:02 | 3.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 790537.62 | 2694.42 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 1650973.12 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 860435.50 | 2694.42 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245684E+09 | 5072.37 | 03-JAN-07:10 | 3.67 |
February | 0.262446E+09 | 4461.92 | 09-FEB-07:10 | 7.08 |
March | 0.474843E+09 | 5177.12 | 30-MAR-06:10 | 5.58 |
April | 0.205195E+09 | 4141.65 | 19-APR-06:15 | 10.67 |
May | 0.174741E+09 | 4070.83 | 15-MAY-06:10 | 11.33 |
June | 49609012.19 | 3829.90 | 01-JUN-06:10 | 13.17 |
July | 381606.05 | 1401.64 | 17-JUL-06:10 | 15.12 |
August | 1128074.19 | 2142.90 | 28-AUG-06:08 | 14.00 |
September | 14106905.25 | 3787.92 | 20-SEP-06:08 | 12.17 |
October | 47873645.15 | 4057.67 | 12-OCT-06:10 | 9.67 |
November | 0.117143E+09 | 4146.32 | 30-NOV-07:10 | 8.67 |
December | 0.210721E+09 | 4570.05 | 13-DEC-07:10 | 7.17 |
Annual Sum or Average | 0.180387E+10 | |||
Minimum of Months | 381606.05 | 1401.64 | 3.67 | |
Maximum of Months | 0.474843E+09 | 5177.12 | 15.12 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2433498.89 | 2709.52 | 03-JAN-07:02 | 3.67 |
February | 7957.08 | 53.05 | 28-FEB-07:03 | 11.33 |
March | 1478837.80 | 2642.37 | 30-MAR-06:02 | 5.58 |
April | 272076.92 | 1813.85 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 99529.74 | 663.53 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 4291900.42 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 2433498.89 | 2709.52 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12591565.83 | 4046.18 | 03-JAN-07:02 | 3.67 |
February | 438515.91 | 1131.57 | 06-FEB-07:03 | 9.50 |
March | 4862653.92 | 4027.60 | 30-MAR-06:02 | 5.58 |
April | 306090.32 | 2040.60 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1967519.93 | 3822.01 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 20166345.89 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 12591565.83 | 4046.18 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3737806.81 | 2942.31 | 03-JAN-07:02 | 3.67 |
February | 356651.14 | 1075.72 | 11-FEB-07:03 | 8.08 |
March | 1189391.26 | 2919.67 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 418420.86 | 1493.11 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 5702270.08 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 3737806.81 | 2942.31 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2929769.79 | 4356.60 | 03-JAN-07:02 | 3.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2397811.73 | 4363.43 | 30-MAR-06:02 | 5.58 |
April | 209775.45 | 1398.50 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 97440.50 | 649.60 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 5634797.46 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 2929769.79 | 4363.43 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8885702.31 | 2962.92 | 03-JAN-07:02 | 3.67 |
February | 984035.75 | 1691.82 | 28-FEB-07:03 | 11.33 |
March | 3719225.56 | 2939.68 | 30-MAR-06:02 | 5.58 |
April | 477198.89 | 2711.49 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2136219.26 | 2782.39 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 16202381.77 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 8885702.31 | 2962.92 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826284E+09 | 1358.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.693716E+09 | 1358.45 | 27-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.789425E+09 | 947.97 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.670727E+09 | 947.97 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.706893E+09 | 774.31 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.699200E+09 | 774.31 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.654108E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.739280E+09 | 774.31 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.692445E+09 | 1184.79 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.778564E+09 | 1184.79 | 05-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.803681E+09 | 1358.45 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.814892E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886921E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.654108E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.826284E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505359E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.432014E+09 | 860.01 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495499E+09 | 600.14 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425476E+09 | 600.14 | 21-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451406E+09 | 450.21 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.446929E+09 | 450.21 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.417906E+09 | 450.21 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.470426E+09 | 450.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435285E+09 | 600.14 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.478494E+09 | 750.07 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.498577E+09 | 860.01 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.495329E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555270E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.417906E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505359E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770188E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664991E+09 | 1358.45 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.776769E+09 | 947.97 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671282E+09 | 947.97 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.713412E+09 | 774.31 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.708010E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.661873E+09 | 774.31 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.744347E+09 | 774.31 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.686452E+09 | 1011.14 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.730678E+09 | 947.97 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.759318E+09 | 1358.45 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.751457E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.863878E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.661873E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.776769E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.501616E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.428887E+09 | 859.95 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495659E+09 | 750.02 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425945E+09 | 600.10 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450775E+09 | 600.10 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.445016E+09 | 490.17 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.416481E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471271E+09 | 600.10 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438323E+09 | 750.02 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.474592E+09 | 750.02 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.488926E+09 | 859.95 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493910E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553140E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.416481E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.501616E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821226E+09 | 1358.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.690107E+09 | 1358.45 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.786740E+09 | 947.97 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.670055E+09 | 947.97 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.706077E+09 | 774.31 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.698536E+09 | 774.31 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.653496E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.738443E+09 | 774.31 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.690329E+09 | 1011.14 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.772986E+09 | 1184.79 | 20-OCT-15:50 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.799655E+09 | 1358.45 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.808582E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883623E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.653496E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.821226E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504283E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.430985E+09 | 860.01 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.494368E+09 | 600.14 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.424754E+09 | 600.14 | 21-APR-15:39 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450623E+09 | 450.21 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.446250E+09 | 450.21 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.417340E+09 | 450.21 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.469606E+09 | 450.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434380E+09 | 600.14 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.476651E+09 | 750.07 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.496966E+09 | 860.01 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493988E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.554019E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.417340E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.504283E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.769041E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.665569E+09 | 1358.45 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.775573E+09 | 947.97 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.670253E+09 | 947.97 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712262E+09 | 774.31 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.706652E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.660829E+09 | 711.15 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.743362E+09 | 774.31 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.685175E+09 | 947.97 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.729287E+09 | 947.97 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.758868E+09 | 1358.45 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.750285E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.862716E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.660829E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.775573E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.500141E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.427875E+09 | 859.95 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.494382E+09 | 750.02 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425148E+09 | 600.10 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450031E+09 | 600.10 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.444552E+09 | 490.17 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415886E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.470539E+09 | 600.10 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437179E+09 | 750.02 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.472839E+09 | 750.02 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.487812E+09 | 859.95 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.490968E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.551735E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.415886E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500141E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826284E+09 | 1358.45 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.693681E+09 | 1358.45 | 27-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.789425E+09 | 947.97 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.670727E+09 | 947.97 | 21-APR-15:50 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.706893E+09 | 774.31 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.699200E+09 | 774.31 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.654108E+09 | 711.15 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.739280E+09 | 774.31 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.692445E+09 | 1184.79 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.778564E+09 | 1184.79 | 05-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.803681E+09 | 1358.45 | 06-NOV-16:19 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.814892E+09 | 1358.45 | 01-DEC-16:10 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886918E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.654108E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.826284E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505359E+09 | 860.01 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.432014E+09 | 860.01 | 27-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495499E+09 | 600.14 | 01-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425476E+09 | 600.14 | 21-APR-15:30 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451406E+09 | 450.21 | 04-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.446929E+09 | 450.21 | 08-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.417906E+09 | 450.21 | 28-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.470426E+09 | 450.21 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435285E+09 | 600.14 | 18-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.478494E+09 | 750.07 | 20-OCT-15:39 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.498577E+09 | 860.01 | 06-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.495305E+09 | 860.01 | 01-DEC-16:10 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555268E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.417906E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505359E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.770188E+09 | 1358.45 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.664991E+09 | 1358.45 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.776769E+09 | 947.97 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671282E+09 | 947.97 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.713412E+09 | 774.31 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.707997E+09 | 774.31 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.661873E+09 | 774.31 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.744347E+09 | 774.31 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.686452E+09 | 1011.14 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.730678E+09 | 947.97 | 04-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.759318E+09 | 1358.45 | 06-NOV-16:40 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.751457E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.863876E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.661873E+09 | 774.31 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.776769E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.501616E+09 | 859.95 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.428887E+09 | 859.95 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495659E+09 | 750.02 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425945E+09 | 600.10 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450775E+09 | 600.10 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.445016E+09 | 490.17 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.416481E+09 | 490.17 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471271E+09 | 600.10 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.438323E+09 | 750.02 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.474592E+09 | 750.02 | 05-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.488926E+09 | 859.95 | 06-NOV-16:40 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493910E+09 | 859.95 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553140E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.416481E+09 | 490.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.501616E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.826284E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366301.27 | 0.133445E+09 |
February | 0.901968E+09 | 0.693716E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30168.36 | 0.157418E+09 |
March | 0.107774E+10 | 0.789425E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49990.86 | 0.173200E+09 |
April | 0.956342E+09 | 0.670727E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 454445.74 | 0.103896E+09 |
May | 0.103597E+10 | 0.706893E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127755E+09 |
June | 0.103308E+10 | 0.699200E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14665.80 | 69484936.81 |
July | 0.959235E+09 | 0.654108E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201425.27 | 49738829.08 |
August | 0.107774E+10 | 0.739280E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244845.52 | 60567816.57 |
September | 0.956342E+09 | 0.692445E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1833853.58 | 58369646.80 |
October | 0.994195E+09 | 0.778564E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6974296.21 | 89296157.21 |
November | 0.984487E+09 | 0.803681E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832375.12 | 0.129266E+09 |
December | 0.959235E+09 | 0.814892E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 573948.72 | 0.135259E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886921E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13576316.45 | 0.128770E+10 |
Minimum of Months | 0.901968E+09 | 0.654108E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49738829.08 |
Maximum of Months | 0.107774E+10 | 0.826284E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6974296.21 | 0.173200E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.505359E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150771.12 | 92041003.97 |
February | 0.571020E+09 | 0.432014E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16616.06 | 0.108445E+09 |
March | 0.682301E+09 | 0.495499E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 0.119098E+09 |
April | 0.605444E+09 | 0.425476E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78406.68 | 73302823.62 |
May | 0.655854E+09 | 0.451406E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88490263.66 |
June | 0.654023E+09 | 0.446929E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9775.86 | 47590802.73 |
July | 0.607275E+09 | 0.417906E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706883.81 | 35492299.53 |
August | 0.682301E+09 | 0.470426E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736617.90 | 42758041.29 |
September | 0.605444E+09 | 0.435285E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222194.17 | 41026297.23 |
October | 0.629407E+09 | 0.478494E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4110899.31 | 62054847.33 |
November | 0.623262E+09 | 0.498577E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250023.38 | 89286682.39 |
December | 0.607275E+09 | 0.495329E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117164.43 | 93493280.69 |
Annual Sum or Average | 0.755301E+10 | 0.555270E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7399362.98 | 0.893080E+09 |
Minimum of Months | 0.571020E+09 | 0.417906E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35492299.53 |
Maximum of Months | 0.682301E+09 | 0.505359E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4110899.31 | 0.119098E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.770188E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147934.54 | 0.149652E+09 |
February | 0.901968E+09 | 0.664991E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24923.14 | 0.173523E+09 |
March | 0.107774E+10 | 0.776769E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183303E+09 |
April | 0.956342E+09 | 0.671282E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154947.67 | 0.111388E+09 |
May | 0.103597E+10 | 0.713412E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129627E+09 |
June | 0.103308E+10 | 0.708010E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14666.34 | 68876067.94 |
July | 0.959235E+09 | 0.661873E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177515.37 | 50521608.33 |
August | 0.107774E+10 | 0.744347E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107534.02 | 63798167.65 |
September | 0.956342E+09 | 0.686452E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1822229.08 | 66013192.61 |
October | 0.994195E+09 | 0.730678E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5906748.46 | 0.101332E+09 |
November | 0.984487E+09 | 0.759318E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52979.38 | 0.145115E+09 |
December | 0.959235E+09 | 0.751457E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99835.49 | 0.154723E+09 |
Annual Sum or Average | 0.119305E+11 | 0.863878E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10509313.49 | 0.139787E+10 |
Minimum of Months | 0.901968E+09 | 0.661873E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50521608.33 |
Maximum of Months | 0.107774E+10 | 0.776769E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5906748.46 | 0.183303E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.501616E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206726.93 | 91589733.64 |
February | 0.570983E+09 | 0.428887E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29966.83 | 0.108387E+09 |
March | 0.682256E+09 | 0.495659E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28623.13 | 0.118060E+09 |
April | 0.605404E+09 | 0.425945E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339651.43 | 74532622.61 |
May | 0.655811E+09 | 0.450775E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90084792.14 |
June | 0.653980E+09 | 0.445016E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9840.73 | 48373560.76 |
July | 0.607235E+09 | 0.416481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 903469.42 | 36283796.00 |
August | 0.682256E+09 | 0.471271E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 921417.16 | 43807628.95 |
September | 0.605404E+09 | 0.438323E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1224193.74 | 42800316.00 |
October | 0.629366E+09 | 0.474592E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4516723.23 | 63097078.00 |
November | 0.623221E+09 | 0.488926E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 483331.25 | 89442422.16 |
December | 0.607235E+09 | 0.493910E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 367707.82 | 93270285.33 |
Annual Sum or Average | 0.755252E+10 | 0.553140E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9031651.66 | 0.899729E+09 |
Minimum of Months | 0.570983E+09 | 0.416481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36283796.00 |
Maximum of Months | 0.682256E+09 | 0.501616E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4516723.23 | 0.118060E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.821226E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182055.83 | 77734016.64 |
February | 0.901968E+09 | 0.690107E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18868.41 | 89522842.68 |
March | 0.107774E+10 | 0.786740E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38577.36 | 96400849.46 |
April | 0.956342E+09 | 0.670055E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250413.68 | 56221537.89 |
May | 0.103597E+10 | 0.706077E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 69146043.60 |
June | 0.103308E+10 | 0.698536E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8672.03 | 36513826.66 |
July | 0.959235E+09 | 0.653496E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708051.81 | 25950776.73 |
August | 0.107774E+10 | 0.738443E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 728254.13 | 32428274.42 |
September | 0.956342E+09 | 0.690329E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984259.94 | 31752443.99 |
October | 0.994195E+09 | 0.772986E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3920200.02 | 50930737.76 |
November | 0.984487E+09 | 0.799655E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 444112.72 | 75093539.39 |
December | 0.959235E+09 | 0.808582E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260234.93 | 78824662.08 |
Annual Sum or Average | 0.119305E+11 | 0.883623E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7543720.38 | 0.720520E+09 |
Minimum of Months | 0.901968E+09 | 0.653496E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 25950776.73 |
Maximum of Months | 0.107774E+10 | 0.821226E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3920200.02 | 96400849.46 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.504283E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62017.60 | 54954252.92 |
February | 0.571020E+09 | 0.430985E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9278.18 | 62888852.18 |
March | 0.682301E+09 | 0.494368E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 697.30 | 67752917.22 |
April | 0.605444E+09 | 0.424754E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43209.17 | 40948911.92 |
May | 0.655854E+09 | 0.450623E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 48959635.89 |
June | 0.654023E+09 | 0.446250E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5779.49 | 25667035.95 |
July | 0.607275E+09 | 0.417340E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385914.84 | 19395898.03 |
August | 0.682301E+09 | 0.469606E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403968.49 | 24044114.12 |
September | 0.605444E+09 | 0.434380E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 655260.46 | 23001308.33 |
October | 0.629407E+09 | 0.476651E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2257516.21 | 36283056.65 |
November | 0.623262E+09 | 0.496966E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124484.10 | 52902329.99 |
December | 0.607275E+09 | 0.493988E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50343.71 | 55923463.95 |
Annual Sum or Average | 0.755301E+10 | 0.554019E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3998481.91 | 0.512722E+09 |
Minimum of Months | 0.571020E+09 | 0.417340E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 19395898.03 |
Maximum of Months | 0.682301E+09 | 0.504283E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2257516.21 | 67752917.22 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.769041E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4985819.55 | 0.210580E+10 |
February | 0.901968E+09 | 0.665569E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2703182.71 | 0.192254E+10 |
March | 0.107774E+10 | 0.775573E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 0.243214E+10 |
April | 0.956342E+09 | 0.670253E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8283468.79 | 0.148866E+10 |
May | 0.103597E+10 | 0.712262E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.18 | 0.144420E+10 |
June | 0.103308E+10 | 0.706652E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1440652.89 | 0.100940E+10 |
July | 0.959235E+09 | 0.660829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52435352.61 | 0.615389E+09 |
August | 0.107774E+10 | 0.743362E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53618500.68 | 0.721406E+09 |
September | 0.956342E+09 | 0.685175E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79360139.24 | 0.989625E+09 |
October | 0.994195E+09 | 0.729287E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132765E+09 | 0.974196E+09 |
November | 0.984487E+09 | 0.758868E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 313227.08 | 0.189902E+10 |
December | 0.959235E+09 | 0.750285E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6788968.16 | 0.189444E+10 |
Annual Sum or Average | 0.119305E+11 | 0.862716E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342696E+09 | 0.174968E+11 |
Minimum of Months | 0.901968E+09 | 0.660829E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 0.615389E+09 |
Maximum of Months | 0.107774E+10 | 0.775573E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132765E+09 | 0.243214E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.500141E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73483.87 | 54404995.08 |
February | 0.570983E+09 | 0.427875E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10798.83 | 63061610.37 |
March | 0.682256E+09 | 0.494382E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12010.89 | 67482132.48 |
April | 0.605404E+09 | 0.425148E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126762.60 | 42007128.90 |
May | 0.655811E+09 | 0.450031E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 50494954.56 |
June | 0.653980E+09 | 0.444552E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5784.91 | 26622793.59 |
July | 0.607235E+09 | 0.415886E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 460577.10 | 20246852.49 |
August | 0.682256E+09 | 0.470539E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 447264.19 | 24910359.54 |
September | 0.605404E+09 | 0.437179E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653580.78 | 24324515.39 |
October | 0.629366E+09 | 0.472839E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2380421.13 | 37162797.40 |
November | 0.623221E+09 | 0.487812E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211476.54 | 53236593.14 |
December | 0.607235E+09 | 0.490968E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98667.77 | 55734584.59 |
Annual Sum or Average | 0.755252E+10 | 0.551735E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4480842.48 | 0.519689E+09 |
Minimum of Months | 0.570983E+09 | 0.415886E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 20246852.49 |
Maximum of Months | 0.682256E+09 | 0.500141E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2380421.13 | 67482132.48 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.826284E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210914.77 | 0.122382E+09 |
February | 0.901968E+09 | 0.693681E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21471.71 | 0.143951E+09 |
March | 0.107774E+10 | 0.789425E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32584.95 | 0.155128E+09 |
April | 0.956342E+09 | 0.670727E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 326988.78 | 91400888.65 |
May | 0.103597E+10 | 0.706893E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111571E+09 |
June | 0.103308E+10 | 0.699200E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12832.67 | 59698001.52 |
July | 0.959235E+09 | 0.654108E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1000209.65 | 42425218.88 |
August | 0.107774E+10 | 0.739280E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052646.05 | 52820511.06 |
September | 0.956342E+09 | 0.692445E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1532764.35 | 51105270.57 |
October | 0.994195E+09 | 0.778564E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5867460.89 | 80734665.03 |
November | 0.984487E+09 | 0.803681E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 622858.23 | 0.118094E+09 |
December | 0.959235E+09 | 0.814892E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266433.26 | 0.124900E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886918E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10947165.31 | 0.115421E+10 |
Minimum of Months | 0.901968E+09 | 0.654108E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42425218.88 |
Maximum of Months | 0.107774E+10 | 0.826284E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5867460.89 | 0.155128E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.505359E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100932.92 | 83640835.19 |
February | 0.421807E+09 | 0.432014E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14172.83 | 98111336.81 |
March | 0.502994E+09 | 0.495499E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.77 | 0.105712E+09 |
April | 0.447140E+09 | 0.425476E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66220.13 | 63811276.23 |
May | 0.484071E+09 | 0.451406E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76654666.04 |
June | 0.482240E+09 | 0.446929E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8552.22 | 40670725.61 |
July | 0.448971E+09 | 0.417906E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 596208.42 | 30064234.90 |
August | 0.502994E+09 | 0.470426E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 623629.90 | 36919090.46 |
September | 0.447140E+09 | 0.435285E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021977.44 | 35502677.65 |
October | 0.465148E+09 | 0.478494E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3500783.76 | 55438640.60 |
November | 0.460569E+09 | 0.498577E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193039.32 | 80664027.44 |
December | 0.448971E+09 | 0.495305E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86880.71 | 85436602.57 |
Annual Sum or Average | 0.557719E+10 | 0.555268E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6212922.43 | 0.792626E+09 |
Minimum of Months | 0.421807E+09 | 0.417906E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30064234.90 |
Maximum of Months | 0.502994E+09 | 0.505359E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3500783.76 | 0.105712E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.770188E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105830.19 | 0.134821E+09 |
February | 0.901968E+09 | 0.664991E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21254.94 | 0.156372E+09 |
March | 0.107774E+10 | 0.776769E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163194E+09 |
April | 0.956342E+09 | 0.671282E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108354.00 | 97508959.58 |
May | 0.103597E+10 | 0.713412E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113234E+09 |
June | 0.103308E+10 | 0.707997E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12832.99 | 59391586.02 |
July | 0.959235E+09 | 0.661873E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966480.09 | 43285058.99 |
August | 0.107774E+10 | 0.744347E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 933018.43 | 55662053.23 |
September | 0.956342E+09 | 0.686452E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1519164.43 | 57340890.54 |
October | 0.994195E+09 | 0.730678E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4888656.36 | 90089200.55 |
November | 0.984487E+09 | 0.759318E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45346.81 | 0.129999E+09 |
December | 0.959235E+09 | 0.751457E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82557.35 | 0.139736E+09 |
Annual Sum or Average | 0.119305E+11 | 0.863876E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8683495.59 | 0.124063E+10 |
Minimum of Months | 0.901968E+09 | 0.661873E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43285058.99 |
Maximum of Months | 0.107774E+10 | 0.776769E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4888656.36 | 0.163194E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.501616E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119178.22 | 83515842.61 |
February | 0.570983E+09 | 0.428887E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17136.28 | 98569814.13 |
March | 0.682256E+09 | 0.495659E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17193.65 | 0.105471E+09 |
April | 0.605404E+09 | 0.425945E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235213.74 | 65411126.81 |
May | 0.655811E+09 | 0.450775E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78717309.09 |
June | 0.653980E+09 | 0.445016E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8556.61 | 41809371.39 |
July | 0.607235E+09 | 0.416481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 731812.47 | 31253549.83 |
August | 0.682256E+09 | 0.471271E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 727689.27 | 38313752.76 |
September | 0.605404E+09 | 0.438323E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1019093.74 | 37392515.29 |
October | 0.629366E+09 | 0.474592E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3725606.88 | 56739136.82 |
November | 0.623221E+09 | 0.488926E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355980.86 | 81191936.04 |
December | 0.607235E+09 | 0.493910E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175489.16 | 85550575.59 |
Annual Sum or Average | 0.755252E+10 | 0.553140E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7132950.88 | 0.803936E+09 |
Minimum of Months | 0.570983E+09 | 0.416481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31253549.83 |
Maximum of Months | 0.682256E+09 | 0.501616E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3725606.88 | 0.105471E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117911.13 | 0.180252E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17807.89 | 0.209858E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221130E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160780.07 | 0.130741E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155566E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2504.35 | 82955515.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799792.74 | 61216718.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740807.47 | 77113706.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1688529.45 | 75462954.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6295915.32 | 0.119444E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332336.13 | 0.173313E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73241.67 | 0.186050E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10229626.22 | 0.167310E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61216718.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6295915.32 | 0.221130E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332236.09 | 0.216840E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31797.76 | 0.253627E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11900.37 | 0.271585E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386875.06 | 0.161500E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192969E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4041.07 | 0.103954E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106808.94 | 76435959.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059739.58 | 96214945.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2225936.41 | 92541744.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8524594.20 | 0.146028E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692139.92 | 0.210984E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202526.42 | 0.224500E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14578595.82 | 0.204718E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76435959.91 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8524594.20 | 0.271585E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337592.00 | 0.208908E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5307.81 | 0.248316E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273212E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50109.38 | 0.174960E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210000E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119104E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479765.57 | 91958543.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351968.75 | 0.104151E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2127245.15 | 0.102792E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7718687.16 | 0.143411E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376297.52 | 0.203425E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108528.15 | 0.211130E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11555501.49 | 0.209137E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91958543.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7718687.16 | 0.273212E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 15-JAN-10:00 | 291.31 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 01-FEB-12:00 | 305.33 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 11-MAR-13:00 | 341.40 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 30-APR-11:15 | 209.58 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 226.24 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 29-JUN-11:00 | 143.32 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 23-JUL-10:53 | 122.48 | 09-JUL-17:20 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 06-AUG-12:43 | 101.00 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 29-SEP-14:00 | 122.15 | 24-SEP-15:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 05-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.86 | 15-OCT-09:00 | 216.30 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.56 | 19-NOV-13:00 | 277.55 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 25-DEC-12:00 | 272.47 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 160.86 | 341.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 15-JAN-10:00 | 193.72 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 01-FEB-12:00 | 201.19 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 11-MAR-14:00 | 227.14 | 28-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 600.14 | 21-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 26-APR-13:00 | 139.14 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 145.74 | 29-MAY-13:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 29-JUN-11:00 | 98.83 | 04-JUN-13:30 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 31-JUL-13:00 | 85.14 | 09-JUL-12:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 17-AUG-14:00 | 68.84 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 29-SEP-14:00 | 89.66 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 15-OCT-12:50 | 146.03 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 | 19-NOV-13:00 | 185.35 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 17-DEC-13:00 | 181.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.84 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 227.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 | 15-JAN-10:00 | 299.98 | 06-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 01-FEB-12:00 | 308.16 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 342.40 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 30-APR-10:03 | 220.00 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 216.90 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 29-JUN-11:00 | 142.43 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 | 23-JUL-10:53 | 120.85 | 09-JUL-17:20 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 17-AUG-14:00 | 107.57 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1011.14 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.99 | 29-SEP-14:00 | 152.65 | 03-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 | 15-OCT-08:52 | 230.95 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 | 19-NOV-12:56 | 290.21 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 05-DEC-10:00 | 281.44 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.57 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 | 342.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.52 | 15-JAN-10:00 | 194.54 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 01-FEB-12:00 | 202.05 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 11-MAR-12:20 | 227.98 | 28-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 600.10 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 | 30-APR-11:15 | 174.79 | 16-APR-17:40 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 195.55 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 29-JUN-11:00 | 127.75 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 23-JUL-10:53 | 117.07 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 | 06-AUG-12:43 | 93.55 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 29-SEP-14:00 | 124.97 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.70 | 15-OCT-09:00 | 148.29 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.61 | 19-NOV-12:23 | 186.75 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 25-DEC-12:00 | 182.93 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.55 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 111.70 | 227.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 | 15-JAN-10:00 | 170.24 | 02-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 01-FEB-12:00 | 173.76 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 11-MAR-14:00 | 189.92 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.24 | 30-APR-11:20 | 114.64 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:10 | 116.12 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 29-JUN-11:00 | 77.06 | 07-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 23-JUL-11:00 | 60.52 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 06-AUG-12:30 | 55.55 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1011.14 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 29-SEP-14:00 | 62.44 | 03-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 20-OCT-15:50 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 15-OCT-12:50 | 125.81 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 19-NOV-12:52 | 169.00 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 25-DEC-11:53 | 156.20 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.55 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 86.37 | 189.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 | 15-JAN-14:50 | 119.09 | 02-JAN-03:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 01-FEB-12:00 | 117.21 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 11-MAR-14:00 | 126.61 | 28-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 600.14 | 21-APR-15:39 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 26-APR-13:00 | 78.93 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 76.32 | 20-MAY-18:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 29-JUN-11:00 | 52.78 | 04-JUN-13:53 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | 31-JUL-13:00 | 44.26 | 02-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 17-AUG-14:00 | 38.20 | 21-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 29-SEP-14:00 | 51.95 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 15-OCT-12:50 | 88.03 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 19-NOV-12:52 | 115.74 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 17-DEC-12:53 | 106.53 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 126.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1539.94 | 18-JAN-13:00 | 14298.34 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.42 | 01-FEB-12:10 | 11461.29 | 09-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 11852.09 | 30-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.16 | 26-APR-11:10 | 9087.72 | 03-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 03-MAY-12:00 | 7849.72 | 15-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.60 | 29-JUN-11:10 | 6513.49 | 01-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3162.41 | 19-JUL-12:00 | 5739.67 | 27-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3167.45 | 18-AUG-12:00 | 6750.43 | 28-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8578.57 | 29-SEP-11:02 | 7642.41 | 20-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8697.67 | 16-OCT-11:02 | 9731.98 | 30-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.90 | 28-NOV-14:00 | 10627.43 | 24-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1219.77 | 19-DEC-13:00 | 13089.82 | 22-DEC-07:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5739.67 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8697.67 | 14298.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 15-JAN-10:00 | 114.79 | 02-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 01-FEB-12:00 | 117.32 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 11-MAR-12:30 | 127.53 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.36 | 30-APR-11:20 | 92.14 | 16-APR-17:33 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:10 | 101.43 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 29-JUN-11:00 | 65.19 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 | 23-JUL-11:00 | 61.75 | 09-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 06-AUG-12:23 | 45.94 | 26-AUG-17:25 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 29-SEP-14:00 | 63.19 | 03-SEP-16:50 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 15-OCT-08:52 | 88.95 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 19-NOV-12:42 | 117.42 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 25-DEC-11:53 | 107.02 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.94 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 127.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 15-JAN-10:00 | 262.73 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 01-FEB-12:00 | 278.14 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 11-MAR-13:20 | 298.84 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:50 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 30-APR-11:15 | 185.54 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 189.65 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 29-JUN-11:00 | 123.89 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 23-JUL-10:50 | 99.95 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 06-AUG-12:33 | 89.24 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 | 29-SEP-14:00 | 101.42 | 03-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 05-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.33 | 15-OCT-08:52 | 197.41 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:19 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.95 | 19-NOV-13:00 | 261.57 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:10 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 25-DEC-12:00 | 244.81 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.24 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 129.33 | 298.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 15-JAN-14:50 | 174.37 | 27-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 27-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 01-FEB-12:00 | 183.12 | 25-FEB-03:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 01-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 11-MAR-14:00 | 196.79 | 28-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 600.14 | 21-APR-15:30 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 26-APR-13:00 | 122.89 | 21-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 04-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 118.94 | 20-MAY-18:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 29-JUN-11:00 | 81.85 | 04-JUN-13:33 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 28-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 31-JUL-13:00 | 69.26 | 02-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 | 17-AUG-14:00 | 59.11 | 21-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 600.14 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 29-SEP-14:00 | 82.99 | 03-SEP-07:00 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 20-OCT-15:39 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 | 15-OCT-12:50 | 132.87 | 30-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 06-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 19-NOV-13:00 | 174.74 | 23-NOV-07:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:10 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 17-DEC-13:10 | 162.79 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.11 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 | 196.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 | 14-JAN-11:00 | 268.07 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 01-FEB-12:00 | 280.18 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 302.22 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 26-APR-13:00 | 185.69 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 182.18 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 29-JUN-11:00 | 123.66 | 07-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 31-JUL-13:00 | 100.27 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 | 17-AUG-14:00 | 90.11 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 1011.14 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 29-SEP-14:00 | 125.28 | 03-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 04-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 | 15-OCT-12:46 | 209.30 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:40 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 19-NOV-12:56 | 271.17 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 05-DEC-10:00 | 251.57 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.11 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 | 302.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 15-JAN-10:00 | 175.30 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 01-FEB-12:00 | 184.25 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 11-MAR-12:20 | 199.60 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 30-APR-11:15 | 143.39 | 16-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 162.25 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 29-JUN-11:00 | 104.92 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 490.17 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.04 | 23-JUL-10:50 | 91.97 | 09-JUL-17:30 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 | 06-AUG-12:33 | 76.46 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 29-SEP-14:00 | 102.94 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 750.02 | 05-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.99 | 15-OCT-08:52 | 134.85 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 06-NOV-16:40 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 19-NOV-12:23 | 175.49 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 25-DEC-12:00 | 164.00 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 490.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.46 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 88.99 | 199.60 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.28 | 15-JAN-10:00 | 390.59 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 | 01-FEB-12:00 | 404.94 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 426.17 | 28-MAR-21:25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 30-APR-10:53 | 260.16 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 245.73 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 29-JUN-11:00 | 170.63 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 | 23-JUL-11:00 | 133.81 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 17-AUG-14:00 | 123.47 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 29-SEP-13:40 | 151.68 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.99 | 15-OCT-08:52 | 286.64 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 19-NOV-12:52 | 391.63 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 05-DEC-10:00 | 352.61 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.99 | 426.17 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.38 | 15-JAN-10:00 | 469.56 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.66 | 01-FEB-12:00 | 500.04 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 11-MAR-12:50 | 527.87 | 28-MAR-21:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 | 30-APR-10:53 | 321.08 | 21-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 308.61 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 | 29-JUN-11:00 | 216.02 | 06-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 23-JUL-10:53 | 169.40 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 | 06-AUG-12:53 | 155.52 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.62 | 29-SEP-13:50 | 186.01 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.81 | 15-OCT-08:52 | 351.44 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 19-NOV-12:52 | 480.49 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 04-DEC-10:00 | 439.10 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.81 | 527.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 | 15-JAN-10:00 | 435.48 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 01-FEB-12:00 | 462.14 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 531.75 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 30-APR-10:03 | 352.71 | 16-APR-17:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 374.37 | 29-MAY-13:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 270.04 | 04-JUN-14:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 | 31-JUL-13:00 | 238.15 | 09-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 17-AUG-14:00 | 182.62 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.56 | 29-SEP-13:30 | 229.11 | 03-SEP-17:35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.30 | 15-OCT-08:52 | 320.76 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 | 19-NOV-09:53 | 397.29 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 | 04-DEC-10:00 | 414.68 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.30 | 531.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36013.85 | 17-JAN-07:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27262.54 | 03-FEB-07:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31219.69 | 24-MAR-06:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36155.38 | 28-APR-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36462.77 | 01-MAY-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38901.28 | 26-JUN-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39693.21 | 31-JUL-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39589.42 | 21-AUG-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39531.35 | 25-SEP-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40213.47 | 16-OCT-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37358.79 | 13-NOV-07:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35436.53 | 08-DEC-07:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27262.54 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40213.47 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5163.16 | 18-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 |
February | 4754.49 | 01-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 |
March | 6307.40 | 23-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
April | 7980.67 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
May | 7131.66 | 03-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
June | 7053.15 | 30-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
July | 8396.69 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
August | 8120.30 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 9294.46 | 29-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.04 | 0.00 |
October | 9294.88 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.85 | 0.00 |
November | 4594.73 | 10-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 |
December | 4610.16 | 19-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4594.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9294.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.85 | 47.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1842.66 | 10-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 |
February | 1405.43 | 03-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 |
March | 1947.67 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 |
April | 2412.42 | 26-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
May | 2308.50 | 03-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
June | 2633.71 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
July | 3253.18 | 31-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 3122.97 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
September | 3797.54 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 0.00 |
October | 4548.01 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 0.00 |
November | 1441.38 | 10-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 |
December | 1627.56 | 19-DEC-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1405.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4548.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.46 | 96.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2576.20 | 18-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
February | 2138.57 | 03-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
March | 2489.37 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 |
April | 2887.24 | 26-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.73 |
May | 2703.91 | 04-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
June | 3002.73 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 |
July | 3801.06 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 0.00 |
August | 3693.34 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
September | 4096.69 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | 0.00 |
October | 4620.71 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 | 0.00 |
November | 2926.99 | 01-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 |
December | 2512.73 | 19-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2138.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4620.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | 24.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13610.15 | 19-JAN-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13276.84 | 03-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13845.32 | 24-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14834.82 | 27-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14888.45 | 04-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15265.46 | 30-JUN-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16604.96 | 31-JUL-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15930.07 | 14-AUG-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16140.07 | 29-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31004.34 | 16-OCT-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13978.88 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13507.26 | 07-DEC-16:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13276.84 | 2541.06 | 2863.91 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31004.34 | 6035.01 | 6443.98 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13137.67 | 18-JAN-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12921.12 | 02-FEB-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14361.86 | 24-MAR-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16011.30 | 27-APR-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16193.46 | 03-MAY-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16794.89 | 30-JUN-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17653.23 | 31-JUL-15:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17367.89 | 17-AUG-15:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17660.29 | 29-SEP-14:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19448.16 | 16-OCT-14:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13233.23 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12997.69 | 07-DEC-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12921.12 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19448.16 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2765.58 | 18-JAN-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
February | 2395.92 | 03-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
March | 3035.09 | 23-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
April | 4172.78 | 26-APR-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
May | 4491.83 | 04-MAY-13:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
June | 4322.10 | 27-JUN-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
July | 4922.66 | 31-JUL-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 |
August | 4794.37 | 18-AUG-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 | 0.00 |
September | 5680.59 | 29-SEP-13:50 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 | 0.00 |
October | 5841.53 | 16-OCT-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 | 0.00 |
November | 2484.36 | 10-NOV-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 |
December | 2723.00 | 05-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2395.92 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5841.53 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 | 22.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3184.10 | 20-JAN-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
February | 2991.86 | 02-FEB-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
March | 4799.40 | 23-MAR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
April | 6167.89 | 30-APR-10:23 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
May | 5373.53 | 28-MAY-09:03 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.99 |
June | 10093.07 | 25-JUN-09:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 |
July | 11531.39 | 23-JUL-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
August | 7437.74 | 20-AUG-09:43 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 |
September | 9788.99 | 10-SEP-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 |
October | 11470.41 | 15-OCT-08:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 | 0.00 |
November | 2757.10 | 01-NOV-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 |
December | 3128.83 | 05-DEC-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2757.10 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11531.39 | 827.22 | 410.22 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 62.40 | 66.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14726.71 | 22-JAN-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.27 |
February | 11971.29 | 20-FEB-12:43 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.64 |
March | 10051.52 | 19-MAR-13:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.05 |
April | 7728.96 | 26-APR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 0.00 |
May | 5906.52 | 04-MAY-12:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
June | 5329.63 | 30-JUN-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
July | 7289.80 | 31-JUL-12:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 0.00 |
August | 8361.91 | 30-AUG-13:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 12192.16 | 10-SEP-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 |
October | 15393.39 | 29-OCT-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 |
November | 15648.67 | 19-NOV-12:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 |
December | 14568.00 | 17-DEC-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5329.63 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15648.67 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 221.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4689.69 | 18-JAN-15:00 | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 |
February | 5024.64 | 22-FEB-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
March | 6546.39 | 23-MAR-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
April | 11885.00 | 30-APR-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.29 |
May | 12321.40 | 28-MAY-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.80 |
June | 12311.23 | 18-JUN-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.60 |
July | 13402.56 | 09-JUL-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
August | 12172.68 | 27-AUG-15:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 |
September | 12184.51 | 10-SEP-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.24 |
October | 12708.88 | 15-OCT-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 0.00 |
November | 4779.50 | 10-NOV-14:50 | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 |
December | 4697.27 | 19-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4689.69 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13402.56 | 827.17 | 410.20 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.41 | 96.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2213.57 | 18-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
February | 1839.19 | 01-FEB-12:10 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 | 0.00 |
March | 1897.01 | 23-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
April | 2746.89 | 26-APR-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
May | 3179.14 | 04-MAY-14:10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
June | 3130.03 | 27-JUN-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
July | 3722.79 | 31-JUL-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 0.00 |
August | 3660.51 | 18-AUG-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 0.00 |
September | 4283.42 | 29-SEP-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 |
October | 4580.09 | 16-OCT-12:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 0.00 |
November | 2088.30 | 19-NOV-12:23 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 24.99 | 0.00 |
December | 2086.10 | 19-DEC-13:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1839.19 | 267.84 | 143.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4580.09 | 1306.65 | 647.98 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 4.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2951.83 | 20-JAN-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
February | 2689.51 | 21-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3853.99 | 23-MAR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
April | 4718.40 | 30-APR-10:13 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 |
May | 4190.15 | 04-MAY-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
June | 4813.64 | 25-JUN-09:53 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 |
July | 8514.39 | 23-JUL-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
August | 5565.54 | 06-AUG-10:13 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 |
September | 5690.96 | 10-SEP-09:13 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 |
October | 9558.69 | 15-OCT-09:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
November | 2774.16 | 01-NOV-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
December | 2911.81 | 05-DEC-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2689.51 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9558.69 | 827.22 | 410.22 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 19.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11837.64 | 22-JAN-12:03 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 |
February | 8676.09 | 20-FEB-15:03 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.28 |
March | 6651.64 | 23-MAR-14:00 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 |
April | 6543.74 | 26-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1588.55 | 0.00 |
May | 4160.49 | 04-MAY-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 |
June | 3627.65 | 27-JUN-13:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
July | 8334.47 | 31-JUL-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3154.84 | 0.00 |
August | 8266.82 | 18-AUG-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3167.45 | 0.00 |
September | 11798.05 | 29-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7094.64 | 0.00 |
October | 12603.72 | 29-OCT-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.75 |
November | 12514.38 | 19-NOV-12:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
December | 12172.58 | 25-DEC-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3627.65 | 200.88 | 107.99 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12603.72 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7094.64 | 145.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3645.19 | 18-JAN-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
February | 4050.17 | 22-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
March | 4830.20 | 23-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 |
April | 6298.94 | 30-APR-16:53 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 |
May | 8005.39 | 28-MAY-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 |
June | 5360.06 | 29-JUN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
July | 9851.20 | 30-JUL-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 |
August | 7593.51 | 27-AUG-16:23 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 |
September | 9703.71 | 04-SEP-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
October | 7806.25 | 15-OCT-15:43 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 0.00 |
November | 4032.56 | 07-NOV-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
December | 3906.03 | 19-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3645.19 | 127.16 | 68.36 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9851.20 | 805.38 | 410.20 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 50.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2758.18 | 18-JAN-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
February | 2473.10 | 03-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
March | 2874.36 | 23-MAR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
April | 3797.29 | 26-APR-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 0.00 |
May | 4132.97 | 04-MAY-14:10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
June | 3994.68 | 26-JUN-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
July | 4504.28 | 31-JUL-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 0.00 |
August | 4391.42 | 18-AUG-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 | 0.00 |
September | 5165.05 | 29-SEP-13:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | 0.00 |
October | 5367.18 | 16-OCT-12:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 0.00 |
November | 2564.46 | 01-NOV-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
December | 2741.74 | 05-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2473.10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5367.18 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 15.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3774.07 | 20-JAN-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
February | 3625.62 | 21-FEB-09:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
March | 5154.66 | 23-MAR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6444.80 | 30-APR-10:23 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
May | 6995.01 | 28-MAY-08:23 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.39 |
June | 7349.05 | 25-JUN-09:53 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 |
July | 11719.04 | 23-JUL-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 |
August | 11194.43 | 13-AUG-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
September | 6874.82 | 03-SEP-08:43 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.51 |
October | 11371.21 | 15-OCT-08:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 | 0.00 |
November | 3501.05 | 13-NOV-09:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 |
December | 3647.88 | 05-DEC-09:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3501.05 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11719.04 | 805.43 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.75 | 54.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13642.17 | 22-JAN-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 |
February | 12035.40 | 20-FEB-11:43 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.11 |
March | 9602.06 | 19-MAR-12:33 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.55 |
April | 7209.61 | 26-APR-13:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 0.00 |
May | 5496.31 | 04-MAY-12:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
June | 4872.86 | 30-JUN-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
July | 6816.11 | 31-JUL-12:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 0.00 |
August | 7895.49 | 30-AUG-12:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 10814.49 | 29-SEP-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 38.84 | 0.00 |
October | 13701.77 | 01-OCT-12:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 |
November | 14264.24 | 19-NOV-12:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
December | 13491.63 | 25-DEC-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4872.86 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14264.24 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 38.84 | 141.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4643.18 | 18-JAN-15:00 | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
February | 5026.69 | 22-FEB-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
March | 6338.76 | 23-MAR-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
April | 11174.80 | 30-APR-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 |
May | 6975.70 | 28-MAY-17:23 | 0.00 | 68.36 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.28 |
June | 11484.97 | 18-JUN-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
July | 12191.83 | 30-JUL-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.16 |
August | 11282.46 | 27-AUG-15:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.26 |
September | 11641.89 | 10-SEP-15:32 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.28 |
October | 9406.03 | 15-OCT-15:02 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 0.00 |
November | 4753.36 | 07-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
December | 4662.89 | 19-DEC-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4643.18 | 0.00 | 68.36 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12191.83 | 827.17 | 410.20 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 83.28 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.109412E+12 | 103077.39 | 18-JAN-15:30 | 0.283725E+10 | 89287.93 | 03-JAN-07:10 |
February | 0.964870E+11 | 102154.54 | 01-FEB-11:00 | 0.138827E+10 | 37704.17 | 27-FEB-07:10 |
March | 0.110716E+12 | 109883.16 | 23-MAR-15:09 | 0.250608E+10 | 70539.64 | 30-MAR-06:10 |
April | 0.107926E+12 | 115871.96 | 26-APR-14:09 | 0.644972E+09 | 31756.10 | 01-APR-06:10 |
May | 0.113486E+12 | 105569.11 | 04-MAY-14:09 | 0.479523E+09 | 16160.49 | 15-MAY-06:10 |
June | 0.120471E+12 | 118196.67 | 29-JUN-15:00 | 0.152896E+09 | 10688.64 | 12-JUN-06:19 |
July | 0.130464E+12 | 141655.25 | 31-JUL-15:39 | 8387845.90 | 1180.58 | 17-JUL-06:10 |
August | 0.142496E+12 | 139029.38 | 18-AUG-15:50 | 11933771.95 | 2020.32 | 28-AUG-06:00 |
September | 0.121366E+12 | 140238.03 | 29-SEP-15:00 | 52909599.58 | 12339.53 | 20-SEP-06:19 |
October | 0.127400E+12 | 144422.42 | 16-OCT-10:00 | 0.160529E+09 | 15357.59 | 30-OCT-06:10 |
November | 0.108211E+12 | 102076.64 | 10-NOV-16:49 | 0.555998E+09 | 26488.41 | 24-NOV-07:10 |
December | 0.108773E+12 | 108269.24 | 05-DEC-16:40 | 0.162273E+10 | 46046.22 | 13-DEC-07:10 |
Annual Sum or Average | 0.139721E+13 | 0.104215E+11 | ||||
Minimum of Months | 0.964870E+11 | 102076.64 | 8387845.90 | 1180.58 | ||
Maximum of Months | 0.142496E+12 | 144422.42 | 0.283725E+10 | 89287.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.257953E+11 | 0.540114E+10 | 0.605851E+11 | 0.225881E+10 | 0.572009E+10 | 25994782.46 | 0.00 | 0.537067E+10 | 0.00 | 0.00 | 0.00 | 0.425508E+10 | 0.00 |
February | 0.229780E+11 | 0.445154E+10 | 0.548702E+11 | 0.204957E+10 | 0.506050E+10 | 18620006.73 | 0.00 | 0.318828E+10 | 0.00 | 0.00 | 0.00 | 0.387029E+10 | 0.00 |
March | 0.271083E+11 | 0.430939E+10 | 0.627783E+11 | 0.235664E+10 | 0.572220E+10 | 25921117.96 | 0.00 | 0.389577E+10 | 0.00 | 0.00 | 0.00 | 0.451959E+10 | 0.00 |
April | 0.238978E+11 | 0.359693E+10 | 0.586172E+11 | 0.219337E+10 | 0.690755E+10 | 16067123.42 | 0.00 | 0.869363E+10 | 0.00 | 0.00 | 0.00 | 0.400338E+10 | 0.00 |
May | 0.256821E+11 | 0.333646E+10 | 0.616817E+11 | 0.230731E+10 | 0.712519E+10 | 15742857.70 | 0.00 | 0.915331E+10 | 0.00 | 0.00 | 0.00 | 0.418411E+10 | 0.00 |
June | 0.255386E+11 | 0.308539E+10 | 0.604966E+11 | 0.226955E+10 | 0.843795E+10 | 13201450.16 | 0.00 | 0.165665E+11 | 0.00 | 0.00 | 0.00 | 0.406355E+10 | 0.00 |
July | 0.238428E+11 | 0.324182E+10 | 0.597911E+11 | 0.223028E+10 | 0.101328E+11 | 12297553.23 | 0.00 | 0.274172E+11 | 0.00 | 0.00 | 0.00 | 0.379561E+10 | 0.00 |
August | 0.267148E+11 | 0.354124E+10 | 0.627783E+11 | 0.235633E+10 | 0.115288E+11 | 12736130.94 | 0.00 | 0.313963E+11 | 0.00 | 0.00 | 0.00 | 0.416778E+10 | 0.00 |
September | 0.240728E+11 | 0.391239E+10 | 0.585950E+11 | 0.219225E+10 | 0.903033E+10 | 12247266.73 | 0.00 | 0.197410E+11 | 0.00 | 0.00 | 0.00 | 0.380970E+10 | 0.00 |
October | 0.253704E+11 | 0.467103E+10 | 0.605962E+11 | 0.225945E+10 | 0.883202E+10 | 13380711.28 | 0.00 | 0.216406E+11 | 0.00 | 0.00 | 0.00 | 0.401648E+10 | 0.00 |
November | 0.254395E+11 | 0.507096E+10 | 0.591197E+11 | 0.220143E+10 | 0.627802E+10 | 15185152.65 | 0.00 | 0.604315E+10 | 0.00 | 0.00 | 0.00 | 0.404295E+10 | 0.00 |
December | 0.250498E+11 | 0.555125E+10 | 0.597800E+11 | 0.223008E+10 | 0.581859E+10 | 20422966.36 | 0.00 | 0.622804E+10 | 0.00 | 0.00 | 0.00 | 0.409448E+10 | 0.00 |
Annual Sum or Average | 0.301490E+12 | 0.501696E+11 | 0.719689E+12 | 0.269051E+11 | 0.905940E+11 | 0.201817E+09 | 0.00 | 0.159335E+12 | 0.00 | 0.00 | 0.00 | 0.488230E+11 | 0.00 |
Minimum of Months | 0.229780E+11 | 0.308539E+10 | 0.548702E+11 | 0.204957E+10 | 0.506050E+10 | 12247266.73 | 0.00 | 0.318828E+10 | 0.00 | 0.00 | 0.00 | 0.379561E+10 | 0.00 |
Maximum of Months | 0.271083E+11 | 0.555125E+10 | 0.627783E+11 | 0.235664E+10 | 0.115288E+11 | 25994782.46 | 0.00 | 0.313963E+11 | 0.00 | 0.00 | 0.00 | 0.451959E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.283725E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.138827E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.250608E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.644972E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.479523E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152896E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8387845.90 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 11933771.95 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 52909599.58 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.160529E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.555998E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.162273E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104215E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 8387845.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283725E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-17:10 | 11620.60 | 18-JAN-15:30 | 347.37 | 03-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 32642.50 | 27-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 06-FEB-17:10 | 10886.05 | 03-FEB-15:09 | 174.47 | 10-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 28740.43 | 16-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 06-MAR-12:09 | 12646.38 | 23-MAR-15:20 | 295.73 | 30-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 28290.70 | 21-APR-15:00 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 14-APR-16:10 | 14516.79 | 26-APR-14:30 | 153.83 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 27128.78 | 09-MAY-07:10 | 3328.83 | 01-MAY-18:30 | 41699.26 | 01-MAY-07:10 | 1410.29 | 12-MAY-16:10 | 12801.57 | 03-MAY-15:20 | 103.98 | 15-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 26798.99 | 09-JUN-07:10 | 3328.83 | 01-JUN-18:49 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 13884.16 | 30-JUN-15:00 | 72.39 | 01-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 26426.34 | 12-JUL-07:10 | 3328.83 | 01-JUL-18:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:19 | 18326.57 | 31-JUL-14:30 | 12.59 | 17-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 27128.78 | 21-AUG-07:10 | 5686.19 | 08-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:19 | 17611.73 | 14-AUG-15:20 | 16.77 | 28-AUG-06:00 | 0.00 | 01-AUG-00:10 |
September | 29733.40 | 18-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:19 | 19428.75 | 29-SEP-15:00 | 72.28 | 20-SEP-06:19 | 0.00 | 01-SEP-00:10 |
October | 29780.74 | 23-OCT-15:00 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-07:10 | 20249.55 | 16-OCT-15:00 | 85.94 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 06-NOV-16:40 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 15-NOV-17:10 | 10569.48 | 13-NOV-15:09 | 143.95 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 08-DEC-17:10 | 10822.07 | 19-DEC-15:00 | 208.56 | 13-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26426.34 | 3328.83 | 41699.26 | 1410.29 | 10569.48 | 12.59 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 20249.55 | 347.37 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 24036.14 | 18-JAN-13:20 | 0.00 | 0.00 | 0.00 | 5763.67 | 31-JAN-12:39 | 0.00 |
February | 21529.58 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 5763.72 | 03-FEB-12:50 | 0.00 |
March | 24545.97 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 | 5757.20 | 01-MAR-12:00 | 0.00 |
April | 30382.72 | 26-APR-13:39 | 0.00 | 0.00 | 0.00 | 5439.45 | 04-APR-11:20 | 0.00 |
May | 22056.31 | 03-MAY-12:00 | 0.00 | 0.00 | 0.00 | 5388.47 | 01-MAY-11:39 | 0.00 |
June | 34075.50 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 5358.79 | 01-JUN-11:20 | 0.00 |
July | 51284.79 | 31-JUL-15:39 | 0.00 | 0.00 | 0.00 | 5279.57 | 03-JUL-11:39 | 0.00 |
August | 49543.91 | 18-AUG-15:50 | 0.00 | 0.00 | 0.00 | 5245.01 | 31-AUG-11:20 | 0.00 |
September | 54028.41 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 5351.64 | 28-SEP-11:50 | 0.00 |
October | 58550.11 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 5381.99 | 31-OCT-11:30 | 0.00 |
November | 22771.62 | 28-NOV-13:00 | 0.00 | 0.00 | 0.00 | 5410.93 | 30-NOV-12:20 | 0.00 |
December | 24007.19 | 05-DEC-14:00 | 0.00 | 0.00 | 0.00 | 5723.73 | 26-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 21529.58 | 0.00 | 0.00 | 0.00 | 5245.01 | 0.00 | ||
Maximum of Months | 58550.11 | 0.00 | 0.00 | 0.00 | 5763.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 103077.39 | 18-JAN-15:30 | 25990.55 | 41659.26 | 0.00 | 1410.29 | 11620.60 | 6.85 | 0.00 | 19179.05 | 0.00 |
February | 102154.54 | 01-FEB-11:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 7243.12 | 6.85 | 0.00 | 21529.58 | 0.00 |
March | 109883.16 | 23-MAR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12568.59 | 6.90 | 0.00 | 24314.98 | 0.00 |
April | 115871.96 | 26-APR-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14515.42 | 6.89 | 0.00 | 29683.05 | 0.00 |
May | 105569.11 | 04-MAY-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 12327.18 | 6.89 | 0.00 | 21289.98 | 0.00 |
June | 118196.67 | 29-JUN-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 13493.57 | 6.90 | 0.00 | 32035.47 | 0.00 |
July | 141655.25 | 31-JUL-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 17708.30 | 6.88 | 0.00 | 51284.79 | 0.00 |
August | 139029.38 | 18-AUG-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 16768.95 | 6.89 | 0.00 | 49543.91 | 0.00 |
September | 140238.03 | 29-SEP-15:00 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 19428.75 | 6.85 | 0.00 | 47566.66 | 0.00 |
October | 144422.42 | 16-OCT-10:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 12592.84 | 6.85 | 0.00 | 58550.11 | 0.00 |
November | 102076.64 | 10-NOV-16:49 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 6727.25 | 6.85 | 0.00 | 9703.10 | 0.00 |
December | 108269.24 | 05-DEC-16:40 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 7970.32 | 6.85 | 0.00 | 14639.10 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 102076.64 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 6727.25 | 6.85 | 0.00 | 9703.10 | 0.00 | |
Maximum of Months | 144422.42 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 19428.75 | 6.90 | 0.00 | 58550.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 89287.93 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 37704.17 | 27-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 70539.64 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 31756.10 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 16160.49 | 15-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10688.64 | 12-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1180.58 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 2020.32 | 28-AUG-06:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 12339.53 | 20-SEP-06:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 15357.59 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 26488.41 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 46046.22 | 13-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1180.58 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 89287.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.46 | 0.50 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.62 | 1.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 3.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.62 | 2.33 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 1.00 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 27.64 | 9.33 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.71 | 3.67 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.53 | 1.67 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.68 | 7.33 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.68 | 3.50 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 3.67 | 27.54 |
Annual Sum or Average | 0.00 | 0.00 | 20.33 | 27.60 | 20.33 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.68 | 7.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 2.67 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 2.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.85 | 5.17 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.89 | 3.17 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 2.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.98 | 1.67 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 27.78 | 19.67 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.98 | 5.17 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.83 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 27.44 | 3.67 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 19.73 | 10.50 | 19.73 | 2.00 | 20.41 | 2.00 | 20.97 |
February | 4.33 | 19.94 | 4.33 | 19.94 | 0.83 | 20.61 | 0.83 | 21.16 |
March | 15.33 | 19.62 | 15.33 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
April | 1.50 | 20.35 | 1.50 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.23 | 3.67 | 25.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.08 | 14.67 | 26.08 |
November | 0.17 | 20.29 | 0.17 | 20.29 | 3.67 | 26.93 | 3.67 | 27.22 |
December | 6.00 | 19.99 | 6.00 | 19.99 | 4.50 | 22.04 | 4.50 | 23.21 |
Annual Sum or Average | 37.83 | 19.78 | 37.83 | 19.78 | 29.33 | 21.66 | 29.33 | 22.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 20.35 | 15.33 | 20.35 | 14.67 | 26.93 | 14.67 | 27.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.57 | 3.00 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.57 | 2.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.46 | 1.33 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.74 | 1.17 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.17 | 27.55 | 9.00 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.74 | 3.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 1.50 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.66 | 4.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.60 | 3.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.75 | 1.00 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 27.62 | 12.33 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.75 | 4.17 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.57 | 3.50 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.54 | 3.00 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.36 | 1.00 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.13 | 9.83 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.72 | 4.33 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.62 | 5.67 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 29.17 | 27.43 | 29.17 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.72 | 9.83 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.66 | 2.00 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 5.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.84 | 2.83 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.73 | 2.17 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.77 | 2.17 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.67 | 27.72 | 19.00 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.84 | 5.00 | 27.86 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.00 | 24.07 | 187.00 | 24.59 | 12.00 | 24.60 |
February | 32.33 | 23.99 | 188.17 | 24.64 | 0.00 | 24.64 |
March | 18.50 | 23.98 | 249.33 | 24.59 | 0.00 | 24.59 |
April | 11.50 | 24.00 | 354.33 | 24.51 | 0.00 | 24.51 |
May | 0.00 | 0.00 | 372.67 | 24.58 | 0.00 | 24.58 |
June | 0.00 | 0.00 | 470.50 | 24.43 | 0.00 | 24.43 |
July | 0.00 | 0.00 | 497.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 458.33 | 24.48 | 0.00 | 24.48 |
October | 2.67 | 24.00 | 336.50 | 24.67 | 0.00 | 24.67 |
November | 50.33 | 24.02 | 247.33 | 24.61 | 0.00 | 24.61 |
December | 84.33 | 24.02 | 140.17 | 24.59 | 0.00 | 24.59 |
Annual Sum or Average | 297.67 | 24.03 | 4015.33 | 24.53 | 12.00 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 140.17 | 24.40 | 0.00 | 24.40 |
Maximum of Months | 98.00 | 24.07 | 514.00 | 24.67 | 12.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.83 | 23.31 | 32.83 | 23.39 | 0.83 | 23.39 |
February | 276.00 | 23.33 | 22.83 | 23.40 | 0.00 | 23.40 |
March | 280.00 | 23.36 | 54.17 | 23.49 | 0.00 | 23.49 |
April | 130.33 | 23.34 | 155.67 | 23.84 | 0.00 | 23.84 |
May | 106.33 | 23.44 | 174.00 | 23.99 | 0.00 | 23.99 |
June | 23.00 | 23.44 | 331.67 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 452.00 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 500.00 | 24.17 | 0.00 | 24.17 |
September | 11.00 | 23.44 | 355.67 | 24.21 | 0.00 | 24.21 |
October | 93.67 | 23.65 | 217.00 | 24.14 | 0.00 | 24.14 |
November | 225.67 | 23.55 | 85.00 | 23.81 | 0.00 | 23.81 |
December | 358.83 | 23.47 | 22.17 | 23.52 | 0.00 | 23.52 |
Annual Sum or Average | 1816.67 | 23.41 | 2403.00 | 23.89 | 0.83 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 22.17 | 23.39 | 0.00 | 23.39 |
Maximum of Months | 358.83 | 23.65 | 500.00 | 24.21 | 0.83 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.33 | 22.69 | 17.00 | 22.72 | 2.50 | 22.70 |
February | 368.17 | 22.78 | 12.50 | 22.82 | 0.00 | 22.82 |
March | 387.83 | 22.85 | 33.50 | 22.94 | 0.00 | 22.94 |
April | 224.83 | 23.03 | 109.33 | 23.36 | 0.00 | 23.36 |
May | 198.00 | 23.14 | 121.67 | 23.52 | 0.00 | 23.52 |
June | 88.83 | 23.27 | 266.67 | 23.94 | 0.00 | 23.94 |
July | 21.17 | 23.30 | 392.17 | 24.12 | 0.00 | 24.12 |
August | 20.17 | 23.25 | 418.17 | 24.08 | 0.00 | 24.08 |
September | 91.17 | 23.25 | 255.83 | 23.91 | 0.00 | 23.91 |
October | 202.50 | 23.37 | 163.17 | 23.74 | 0.00 | 23.74 |
November | 347.67 | 23.05 | 32.83 | 23.15 | 0.00 | 23.15 |
December | 439.33 | 22.83 | 8.67 | 22.84 | 1.50 | 22.84 |
Annual Sum or Average | 2802.00 | 22.94 | 1831.50 | 23.41 | 4.00 | 23.41 |
Minimum of Months | 20.17 | 22.69 | 8.67 | 22.72 | 0.00 | 22.70 |
Maximum of Months | 439.33 | 23.37 | 418.17 | 24.12 | 2.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.67 | 21.88 | 65.67 | 21.71 | 61.17 | 21.56 |
February | 417.83 | 22.02 | 27.00 | 21.93 | 24.33 | 21.85 |
March | 448.50 | 22.11 | 50.17 | 22.11 | 26.00 | 22.02 |
April | 307.33 | 22.56 | 82.83 | 22.83 | 4.00 | 22.81 |
May | 268.00 | 22.77 | 111.33 | 23.17 | 0.00 | 23.17 |
June | 142.83 | 23.08 | 247.50 | 23.73 | 0.00 | 23.73 |
July | 66.17 | 23.12 | 355.17 | 24.00 | 0.00 | 24.00 |
August | 108.33 | 23.13 | 333.67 | 23.85 | 0.00 | 23.85 |
September | 199.67 | 22.96 | 204.00 | 23.52 | 0.00 | 23.52 |
October | 268.83 | 22.86 | 127.17 | 23.28 | 0.00 | 23.28 |
November | 425.33 | 22.31 | 29.50 | 22.24 | 22.50 | 22.16 |
December | 486.50 | 21.99 | 49.17 | 21.83 | 49.17 | 21.69 |
Annual Sum or Average | 3605.00 | 22.36 | 1683.17 | 22.78 | 187.17 | 22.69 |
Minimum of Months | 66.17 | 21.88 | 27.00 | 21.71 | 0.00 | 21.56 |
Maximum of Months | 486.50 | 23.13 | 355.17 | 24.00 | 61.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.50 | 22.26 | 54.50 | 22.21 | 31.00 | 22.08 |
February | 358.00 | 22.12 | 46.17 | 22.20 | 15.00 | 22.13 |
March | 346.17 | 22.08 | 89.33 | 22.38 | 15.67 | 22.31 |
April | 208.00 | 22.48 | 213.83 | 23.40 | 2.67 | 23.40 |
May | 212.00 | 22.70 | 202.83 | 23.54 | 0.17 | 23.54 |
June | 140.33 | 23.10 | 285.83 | 23.88 | 5.67 | 23.92 |
July | 82.83 | 23.96 | 386.17 | 24.31 | 20.17 | 24.41 |
August | 96.33 | 23.63 | 378.83 | 24.13 | 15.17 | 24.21 |
September | 166.00 | 22.90 | 266.50 | 23.71 | 3.17 | 23.74 |
October | 197.67 | 22.84 | 179.67 | 23.57 | 1.83 | 23.59 |
November | 348.00 | 22.48 | 45.83 | 22.58 | 9.83 | 22.53 |
December | 463.17 | 22.41 | 31.17 | 22.30 | 26.50 | 22.18 |
Annual Sum or Average | 3046.00 | 22.52 | 2180.67 | 23.18 | 146.83 | 23.16 |
Minimum of Months | 82.83 | 22.08 | 31.17 | 22.20 | 0.17 | 22.08 |
Maximum of Months | 463.17 | 23.96 | 386.17 | 24.31 | 31.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 271.00 | 22.29 | 167.50 | 22.89 | 28.50 | 22.78 |
February | 270.83 | 22.13 | 123.00 | 22.75 | 16.00 | 22.70 |
March | 325.83 | 22.19 | 135.00 | 22.65 | 20.17 | 22.59 |
April | 232.50 | 22.52 | 186.17 | 23.31 | 3.17 | 23.28 |
May | 258.17 | 22.66 | 141.83 | 23.23 | 0.17 | 23.23 |
June | 171.33 | 22.99 | 233.17 | 23.64 | 0.00 | 23.64 |
July | 94.67 | 23.20 | 335.17 | 24.00 | 2.50 | 24.02 |
August | 94.33 | 23.18 | 356.00 | 23.98 | 3.33 | 24.00 |
September | 142.17 | 23.17 | 285.33 | 23.95 | 8.83 | 24.01 |
October | 176.67 | 23.54 | 265.83 | 24.14 | 27.67 | 24.31 |
November | 240.67 | 22.62 | 181.83 | 23.40 | 13.00 | 23.40 |
December | 264.83 | 22.41 | 170.67 | 23.06 | 26.00 | 22.96 |
Annual Sum or Average | 2543.00 | 22.61 | 2581.50 | 23.42 | 149.33 | 23.41 |
Minimum of Months | 94.33 | 22.13 | 123.00 | 22.65 | 0.00 | 22.59 |
Maximum of Months | 325.83 | 23.54 | 356.00 | 24.14 | 28.50 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.33 | 21.80 | 95.17 | 21.82 | 53.83 | 21.67 |
February | 363.50 | 21.83 | 75.50 | 22.03 | 24.83 | 21.94 |
March | 401.83 | 21.94 | 103.17 | 22.21 | 26.17 | 22.13 |
April | 275.00 | 22.54 | 163.83 | 23.20 | 14.00 | 23.26 |
May | 264.83 | 22.70 | 179.83 | 23.40 | 8.67 | 23.46 |
June | 159.00 | 23.08 | 279.17 | 23.82 | 11.50 | 23.90 |
July | 106.00 | 23.86 | 365.50 | 24.23 | 26.83 | 24.37 |
August | 111.67 | 23.41 | 362.17 | 24.02 | 16.50 | 24.11 |
September | 181.50 | 22.98 | 241.67 | 23.73 | 10.17 | 23.80 |
October | 247.50 | 22.80 | 188.00 | 23.48 | 9.00 | 23.55 |
November | 365.00 | 22.12 | 96.67 | 22.38 | 24.33 | 22.30 |
December | 417.00 | 21.87 | 72.67 | 21.81 | 50.83 | 21.67 |
Annual Sum or Average | 3306.17 | 22.32 | 2223.33 | 22.98 | 276.67 | 22.96 |
Minimum of Months | 106.00 | 21.80 | 72.67 | 21.81 | 8.67 | 21.67 |
Maximum of Months | 417.00 | 23.86 | 365.50 | 24.23 | 53.83 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.00 | 22.34 | 7.50 | 22.32 | 6.00 | 22.29 |
February | 448.67 | 22.37 | 0.33 | 22.37 | 0.33 | 22.37 |
March | 487.00 | 22.39 | 10.83 | 22.41 | 2.00 | 22.40 |
April | 368.00 | 22.86 | 25.50 | 22.93 | 0.00 | 22.93 |
May | 307.67 | 23.10 | 39.17 | 23.22 | 0.00 | 23.22 |
June | 155.17 | 23.27 | 188.00 | 23.72 | 0.00 | 23.72 |
July | 37.83 | 23.32 | 356.33 | 24.06 | 0.00 | 24.06 |
August | 66.33 | 23.22 | 335.17 | 23.93 | 0.00 | 23.93 |
September | 171.17 | 23.22 | 179.50 | 23.65 | 0.00 | 23.65 |
October | 250.50 | 23.28 | 118.17 | 23.55 | 0.00 | 23.55 |
November | 425.17 | 22.82 | 14.50 | 22.87 | 0.00 | 22.87 |
December | 490.83 | 22.44 | 2.17 | 22.43 | 2.17 | 22.43 |
Annual Sum or Average | 3678.33 | 22.70 | 1277.17 | 23.06 | 10.50 | 23.05 |
Minimum of Months | 37.83 | 22.34 | 0.33 | 22.32 | 0.00 | 22.29 |
Maximum of Months | 490.83 | 23.32 | 356.33 | 24.06 | 6.00 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.33 | 22.87 | 34.17 | 22.96 | 1.67 | 22.95 |
February | 356.33 | 22.66 | 17.67 | 22.75 | 0.00 | 22.75 |
March | 348.83 | 22.61 | 60.33 | 22.87 | 1.67 | 22.86 |
April | 193.50 | 22.97 | 194.33 | 23.69 | 0.17 | 23.69 |
May | 187.50 | 23.13 | 195.50 | 23.81 | 0.00 | 23.81 |
June | 105.67 | 23.20 | 284.67 | 23.99 | 0.33 | 23.99 |
July | 26.83 | 24.69 | 433.17 | 24.40 | 10.50 | 24.46 |
August | 21.83 | 24.53 | 445.50 | 24.28 | 7.50 | 24.32 |
September | 84.50 | 23.22 | 305.83 | 24.03 | 1.00 | 24.04 |
October | 122.17 | 23.37 | 215.67 | 24.04 | 0.67 | 24.05 |
November | 300.50 | 23.17 | 59.17 | 23.36 | 5.33 | 23.38 |
December | 418.17 | 23.01 | 6.50 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 2544.17 | 22.97 | 2252.50 | 23.61 | 28.83 | 23.63 |
Minimum of Months | 21.83 | 22.61 | 6.50 | 22.75 | 0.00 | 22.75 |
Maximum of Months | 418.17 | 24.69 | 445.50 | 24.40 | 10.50 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.83 | 22.70 | 162.83 | 23.44 | 6.67 | 23.43 |
February | 289.50 | 22.42 | 98.00 | 23.00 | 0.67 | 23.01 |
March | 358.33 | 22.17 | 91.00 | 22.53 | 9.50 | 22.47 |
April | 274.17 | 22.67 | 136.83 | 23.25 | 0.00 | 23.25 |
May | 343.83 | 22.67 | 72.83 | 22.97 | 0.00 | 22.97 |
June | 258.83 | 22.84 | 128.17 | 23.27 | 0.00 | 23.27 |
July | 92.33 | 22.85 | 317.50 | 23.87 | 11.33 | 23.86 |
August | 75.33 | 22.82 | 391.33 | 23.93 | 21.67 | 23.91 |
September | 85.00 | 22.89 | 335.50 | 24.06 | 11.17 | 24.07 |
October | 118.17 | 23.65 | 308.67 | 24.36 | 30.17 | 24.45 |
November | 187.33 | 22.95 | 179.50 | 23.82 | 5.33 | 23.86 |
December | 229.67 | 22.85 | 157.00 | 23.65 | 2.33 | 23.67 |
Annual Sum or Average | 2550.33 | 22.69 | 2379.17 | 23.51 | 98.83 | 23.52 |
Minimum of Months | 75.33 | 22.17 | 72.83 | 22.53 | 0.00 | 22.47 |
Maximum of Months | 358.33 | 23.65 | 391.33 | 24.36 | 30.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 399.67 | 22.56 | 35.00 | 22.67 | 2.17 | 22.66 |
February | 366.33 | 22.53 | 37.67 | 22.70 | 0.00 | 22.70 |
March | 398.33 | 22.54 | 62.67 | 22.77 | 0.83 | 22.77 |
April | 212.50 | 23.00 | 165.50 | 23.62 | 0.83 | 23.63 |
May | 189.83 | 23.13 | 195.00 | 23.78 | 0.83 | 23.79 |
June | 84.67 | 23.31 | 316.33 | 24.06 | 2.83 | 24.08 |
July | 20.00 | 26.12 | 447.00 | 24.44 | 15.67 | 24.52 |
August | 21.17 | 25.27 | 456.00 | 24.30 | 11.83 | 24.36 |
September | 57.67 | 23.58 | 342.00 | 24.21 | 5.33 | 24.24 |
October | 155.33 | 23.45 | 234.67 | 24.01 | 4.67 | 24.05 |
November | 330.83 | 23.04 | 79.00 | 23.30 | 5.33 | 23.33 |
December | 411.00 | 22.70 | 18.83 | 22.78 | 0.00 | 22.78 |
Annual Sum or Average | 2647.33 | 22.86 | 2389.67 | 23.55 | 50.33 | 23.58 |
Minimum of Months | 20.00 | 22.53 | 18.83 | 22.67 | 0.00 | 22.66 |
Maximum of Months | 411.00 | 26.12 | 456.00 | 24.44 | 15.67 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.00 | 22.43 | 23.17 | 22.41 | 12.50 | 22.36 |
February | 396.00 | 22.56 | 3.83 | 22.58 | 0.17 | 22.58 |
March | 422.83 | 22.60 | 30.83 | 22.67 | 2.67 | 22.66 |
April | 275.00 | 22.98 | 79.50 | 23.21 | 0.00 | 23.21 |
May | 220.67 | 23.18 | 117.00 | 23.52 | 0.00 | 23.52 |
June | 75.83 | 23.31 | 282.00 | 23.96 | 0.00 | 23.96 |
July | 16.83 | 23.35 | 418.50 | 24.15 | 0.00 | 24.15 |
August | 30.00 | 23.29 | 398.00 | 24.04 | 0.00 | 24.04 |
September | 115.83 | 23.23 | 239.17 | 23.81 | 0.00 | 23.81 |
October | 219.50 | 23.28 | 152.83 | 23.65 | 0.00 | 23.65 |
November | 382.50 | 22.84 | 20.00 | 22.90 | 1.00 | 22.89 |
December | 473.00 | 22.59 | 3.17 | 22.58 | 2.17 | 22.58 |
Annual Sum or Average | 3073.00 | 22.77 | 1768.00 | 23.26 | 18.50 | 23.25 |
Minimum of Months | 16.83 | 22.43 | 3.17 | 22.41 | 0.00 | 22.36 |
Maximum of Months | 473.00 | 23.35 | 418.50 | 24.15 | 12.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 341.67 | 22.55 | 33.50 | 22.61 | 8.50 | 22.55 |
February | 302.00 | 22.50 | 28.17 | 22.68 | 0.17 | 22.68 |
March | 290.83 | 22.43 | 68.17 | 22.78 | 2.67 | 22.76 |
April | 185.33 | 22.91 | 159.83 | 23.64 | 2.67 | 23.67 |
May | 179.50 | 23.07 | 164.33 | 23.79 | 1.17 | 23.81 |
June | 103.17 | 23.36 | 237.83 | 24.07 | 6.50 | 24.12 |
July | 49.67 | 24.69 | 335.67 | 24.50 | 20.33 | 24.62 |
August | 51.83 | 24.17 | 332.50 | 24.29 | 14.50 | 24.38 |
September | 116.17 | 23.20 | 222.67 | 23.93 | 4.83 | 23.97 |
October | 147.17 | 23.16 | 167.83 | 23.87 | 2.00 | 23.90 |
November | 277.67 | 22.82 | 48.67 | 23.07 | 0.33 | 23.06 |
December | 361.17 | 22.70 | 9.33 | 22.73 | 2.00 | 22.72 |
Annual Sum or Average | 2406.17 | 22.83 | 1808.50 | 23.50 | 65.67 | 23.53 |
Minimum of Months | 49.67 | 22.43 | 9.33 | 22.61 | 0.17 | 22.55 |
Maximum of Months | 361.17 | 24.69 | 335.67 | 24.50 | 20.33 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 229.33 | 22.87 | 172.00 | 23.54 | 10.83 | 23.56 |
February | 242.83 | 22.75 | 127.67 | 23.39 | 4.83 | 23.44 |
March | 276.83 | 22.67 | 139.33 | 23.21 | 2.83 | 23.22 |
April | 189.17 | 22.99 | 194.33 | 23.68 | 0.00 | 23.68 |
May | 213.33 | 23.12 | 157.17 | 23.61 | 0.00 | 23.61 |
June | 106.50 | 23.28 | 262.83 | 23.90 | 0.00 | 23.90 |
July | 25.17 | 23.49 | 391.00 | 24.19 | 1.00 | 24.20 |
August | 21.67 | 23.54 | 423.00 | 24.17 | 1.50 | 24.18 |
September | 76.33 | 23.67 | 343.67 | 24.22 | 8.50 | 24.27 |
October | 124.17 | 24.13 | 305.00 | 24.44 | 27.50 | 24.59 |
November | 201.17 | 23.29 | 198.50 | 23.95 | 8.33 | 24.01 |
December | 225.67 | 23.06 | 173.67 | 23.77 | 7.17 | 23.84 |
Annual Sum or Average | 1932.17 | 23.08 | 2888.17 | 23.85 | 72.50 | 23.89 |
Minimum of Months | 21.67 | 22.67 | 127.67 | 23.21 | 0.00 | 23.22 |
Maximum of Months | 276.83 | 24.13 | 423.00 | 24.44 | 27.50 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 385.67 | 22.33 | 63.67 | 22.47 | 13.33 | 22.41 |
February | 345.33 | 22.40 | 59.83 | 22.70 | 0.17 | 22.70 |
March | 374.17 | 22.46 | 93.17 | 22.78 | 4.83 | 22.77 |
April | 223.33 | 22.94 | 175.67 | 23.58 | 7.17 | 23.64 |
May | 204.17 | 23.12 | 205.50 | 23.77 | 8.17 | 23.83 |
June | 99.67 | 23.47 | 320.83 | 24.07 | 10.67 | 24.14 |
July | 55.33 | 24.82 | 411.00 | 24.42 | 25.00 | 24.54 |
August | 52.17 | 24.21 | 424.83 | 24.23 | 15.50 | 24.31 |
September | 107.00 | 23.41 | 304.00 | 24.07 | 10.33 | 24.14 |
October | 193.17 | 23.26 | 220.17 | 23.87 | 8.33 | 23.93 |
November | 334.83 | 22.71 | 90.50 | 23.06 | 1.33 | 23.06 |
December | 393.67 | 22.46 | 36.67 | 22.59 | 3.17 | 22.58 |
Annual Sum or Average | 2768.50 | 22.76 | 2405.83 | 23.47 | 108.00 | 23.51 |
Minimum of Months | 52.17 | 22.33 | 36.67 | 22.47 | 0.17 | 22.41 |
Maximum of Months | 393.67 | 24.82 | 424.83 | 24.42 | 25.00 | 24.54 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36046 | 36.24287 | 0.40956 | 8.83084 |
February | 454.00000 | 24.34012 | 38.24593 | 0.41992 | 8.92111 |
March | 514.00000 | 24.32569 | 40.96572 | 0.43719 | 9.22805 |
April | 485.00000 | 24.40910 | 43.68340 | 0.49045 | 10.27848 |
May | 508.00000 | 24.42775 | 42.93829 | -0.3651 | 8.27936 |
June | 496.00000 | 24.40667 | 48.00711 | -0.3187 | 7.59923 |
July | 497.00000 | 24.46716 | 51.74345 | -0.2614 | 6.94113 |
August | 514.00000 | 24.40016 | 53.04535 | -0.2662 | 6.93965 |
September | 485.00000 | 24.45310 | 49.01364 | -0.2914 | 7.32052 |
October | 502.00000 | 24.46331 | 40.52799 | 0.50325 | 10.73378 |
November | 489.00000 | 24.43974 | 36.33769 | 0.44607 | 9.67555 |
December | 497.00000 | 24.35002 | 31.66841 | 0.38218 | 8.39719 |
Annual Sum or Average | 5943.00000 | 24.40373 | 42.74464 | 0.12921 | 8.58943 |
Minimum of Months | 454.00000 | 24.32569 | 31.66841 | -0.3651 | 6.93965 |
Maximum of Months | 514.00000 | 24.46716 | 53.04535 | 0.50325 | 10.73378 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60184 | 38.73852 | 0.22017 | 6.55018 |
February | 454.00000 | 23.62046 | 40.87484 | 0.24211 | 6.58960 |
March | 514.00000 | 23.67522 | 43.70626 | 0.27544 | 6.93907 |
April | 485.00000 | 23.88130 | 45.58488 | 0.35749 | 8.00567 |
May | 508.00000 | 23.98036 | 44.66941 | -0.5334 | 11.34368 |
June | 496.00000 | 24.09716 | 49.47939 | -0.4436 | 9.38908 |
July | 497.00000 | 24.17869 | 53.20885 | -0.3777 | 8.20000 |
August | 514.00000 | 24.15576 | 54.51427 | -0.3714 | 8.06853 |
September | 485.00000 | 24.11235 | 50.61874 | -0.4292 | 9.12033 |
October | 502.00000 | 24.09938 | 42.11683 | 0.40177 | 8.70076 |
November | 489.00000 | 23.87579 | 38.41608 | 0.29789 | 7.29390 |
December | 497.00000 | 23.64583 | 34.02572 | 0.20517 | 6.28124 |
Annual Sum or Average | 5943.00000 | 23.91217 | 44.70226 | -0.0157 | 8.05168 |
Minimum of Months | 454.00000 | 23.60184 | 34.02572 | -0.5334 | 6.28124 |
Maximum of Months | 514.00000 | 24.17869 | 54.51427 | 0.40177 | 11.34368 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.91762 | 40.30968 | 0.05212 | 6.25210 |
February | 454.00000 | 23.00428 | 42.51572 | 0.09240 | 6.06694 |
March | 514.00000 | 23.12269 | 45.06956 | 0.14108 | 6.29612 |
April | 485.00000 | 23.55729 | 46.39378 | 0.28058 | 7.29306 |
May | 508.00000 | 23.70175 | 45.27264 | -0.6284 | 14.18407 |
June | 496.00000 | 23.92380 | 49.70620 | -0.4996 | 10.68016 |
July | 497.00000 | 24.05481 | 53.34966 | -0.4135 | 8.84472 |
August | 514.00000 | 24.01612 | 54.80523 | -0.4143 | 8.83954 |
September | 485.00000 | 23.88288 | 51.14695 | -0.5088 | 10.89871 |
October | 502.00000 | 23.80681 | 42.83443 | 0.32768 | 7.79857 |
November | 489.00000 | 23.33153 | 39.89358 | 0.16222 | 6.41687 |
December | 497.00000 | 22.96145 | 35.71129 | 0.03797 | 5.93384 |
Annual Sum or Average | 5943.00000 | 23.52689 | 45.61794 | -0.1166 | 8.31167 |
Minimum of Months | 454.00000 | 22.91762 | 35.71129 | -0.6284 | 5.93384 |
Maximum of Months | 514.00000 | 24.05481 | 54.80523 | 0.32768 | 14.18407 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03158 | 42.24876 | -0.1713 | 7.66396 |
February | 454.00000 | 22.17165 | 45.19598 | -0.1108 | 6.82660 |
March | 514.00000 | 22.34374 | 47.80291 | -0.0482 | 6.85031 |
April | 485.00000 | 23.07714 | 48.58020 | 0.16298 | 6.86900 |
May | 508.00000 | 23.37481 | 46.95512 | -0.7394 | 18.37598 |
June | 496.00000 | 23.77453 | 50.83792 | -0.5457 | 12.22994 |
July | 497.00000 | 23.97658 | 54.25380 | -0.4330 | 9.63077 |
August | 514.00000 | 23.83655 | 56.26307 | -0.4745 | 10.47162 |
September | 485.00000 | 23.57326 | 53.07070 | -0.6179 | 14.29212 |
October | 502.00000 | 23.42001 | 44.57142 | 0.23195 | 7.42536 |
November | 489.00000 | 22.52407 | 42.51874 | -0.0362 | 6.67521 |
December | 497.00000 | 22.02951 | 37.98006 | -0.1929 | 7.34757 |
Annual Sum or Average | 5943.00000 | 23.01710 | 47.55073 | -0.2497 | 9.58172 |
Minimum of Months | 454.00000 | 22.02951 | 37.98006 | -0.7394 | 6.67521 |
Maximum of Months | 514.00000 | 23.97658 | 56.26307 | 0.23195 | 18.37598 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.51936 | 40.90720 | -0.0332 | 7.08102 |
February | 454.00000 | 22.52390 | 44.02309 | -0.0047 | 6.90711 |
March | 514.00000 | 22.73281 | 46.36012 | 0.07088 | 7.43054 |
April | 485.00000 | 23.47522 | 46.84077 | 0.30058 | 8.63623 |
May | 508.00000 | 23.60625 | 45.88666 | -0.6102 | 15.55690 |
June | 496.00000 | 23.83956 | 50.32902 | -0.4649 | 11.54873 |
July | 497.00000 | 24.14567 | 53.28817 | -0.3003 | 8.91750 |
August | 514.00000 | 23.99756 | 55.12599 | -0.3356 | 9.16594 |
September | 485.00000 | 23.69536 | 52.20378 | -0.5174 | 12.77310 |
October | 502.00000 | 23.65021 | 43.65981 | 0.31992 | 8.46441 |
November | 489.00000 | 22.93262 | 41.25453 | 0.08320 | 6.75804 |
December | 497.00000 | 22.51468 | 36.74492 | -0.0558 | 6.66376 |
Annual Sum or Average | 5943.00000 | 23.30822 | 46.41311 | -0.1306 | 9.17607 |
Minimum of Months | 454.00000 | 22.51468 | 36.74492 | -0.6102 | 6.66376 |
Maximum of Months | 514.00000 | 24.14567 | 55.12599 | 0.31992 | 15.55690 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20304 | 38.35745 | 0.17187 | 8.83910 |
February | 454.00000 | 23.00074 | 42.20264 | 0.13082 | 8.35194 |
March | 514.00000 | 22.90500 | 45.41224 | 0.11822 | 8.12939 |
April | 485.00000 | 23.41546 | 46.90231 | 0.27348 | 8.52387 |
May | 508.00000 | 23.38899 | 46.60824 | -0.7198 | 18.47883 |
June | 496.00000 | 23.69129 | 50.98797 | -0.5673 | 13.13131 |
July | 497.00000 | 23.96187 | 54.16006 | -0.4248 | 9.99365 |
August | 514.00000 | 23.93314 | 55.44894 | -0.3974 | 9.71695 |
September | 485.00000 | 23.88774 | 51.30029 | -0.4400 | 11.62655 |
October | 502.00000 | 23.95575 | 42.43306 | 0.42157 | 10.80845 |
November | 489.00000 | 23.50134 | 38.86264 | 0.25896 | 9.01120 |
December | 497.00000 | 23.33409 | 34.00720 | 0.18430 | 8.84390 |
Annual Sum or Average | 5943.00000 | 23.51736 | 45.59612 | -0.0853 | 10.47786 |
Minimum of Months | 454.00000 | 22.90500 | 34.00720 | -0.7198 | 8.12939 |
Maximum of Months | 514.00000 | 23.96187 | 55.44894 | 0.42157 | 18.47883 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20102 | 41.13340 | -0.1036 | 7.90454 |
February | 454.00000 | 22.29746 | 44.10492 | -0.0499 | 7.47850 |
March | 514.00000 | 22.40913 | 46.78694 | 0.00296 | 7.59614 |
April | 485.00000 | 23.22969 | 47.53917 | 0.25045 | 8.82692 |
May | 508.00000 | 23.40523 | 46.39063 | -0.6629 | 18.26801 |
June | 496.00000 | 23.74474 | 50.63579 | -0.4793 | 12.44081 |
July | 497.00000 | 24.02863 | 53.84474 | -0.3327 | 9.76190 |
August | 514.00000 | 23.88752 | 55.71628 | -0.3698 | 10.07227 |
September | 485.00000 | 23.67194 | 52.26230 | -0.5092 | 13.31783 |
October | 502.00000 | 23.47917 | 43.92347 | 0.28639 | 8.83136 |
November | 489.00000 | 22.63631 | 41.31967 | 0.02527 | 7.42578 |
December | 497.00000 | 22.22947 | 36.75398 | -0.1172 | 7.63859 |
Annual Sum or Average | 5943.00000 | 23.10701 | 46.73182 | -0.1734 | 9.98628 |
Minimum of Months | 454.00000 | 22.20102 | 36.75398 | -0.6629 | 7.42578 |
Maximum of Months | 514.00000 | 24.02863 | 55.71628 | 0.28639 | 18.26801 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.43898 | 41.58650 | -0.0668 | 6.26401 |
February | 454.00000 | 22.39050 | 44.78372 | -0.0588 | 5.74966 |
March | 514.00000 | 22.46822 | 47.64406 | -0.0211 | 5.95184 |
April | 485.00000 | 23.12505 | 49.21040 | 0.16121 | 6.22688 |
May | 508.00000 | 23.46320 | 47.51318 | -0.7304 | 17.09554 |
June | 496.00000 | 23.77999 | 51.59577 | -0.5721 | 12.34916 |
July | 497.00000 | 23.99881 | 54.55116 | -0.4540 | 9.59287 |
August | 514.00000 | 23.87901 | 56.38454 | -0.4879 | 10.31308 |
September | 485.00000 | 23.71917 | 53.01427 | -0.5838 | 12.67402 |
October | 502.00000 | 23.66597 | 44.21917 | 0.28602 | 7.30729 |
November | 489.00000 | 22.97358 | 41.74350 | 0.07260 | 5.93114 |
December | 497.00000 | 22.45901 | 37.12014 | -0.0858 | 5.88986 |
Annual Sum or Average | 5943.00000 | 23.20203 | 47.47725 | -0.2138 | 8.80956 |
Minimum of Months | 454.00000 | 22.39050 | 37.12014 | -0.7304 | 5.74966 |
Maximum of Months | 514.00000 | 23.99881 | 56.38454 | 0.28602 | 17.09554 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16376 | 40.03404 | 0.12176 | 6.36864 |
February | 454.00000 | 22.97215 | 43.39107 | 0.09574 | 6.18949 |
March | 514.00000 | 23.10779 | 45.89855 | 0.14966 | 6.83869 |
April | 485.00000 | 23.74137 | 46.74743 | 0.34462 | 8.39179 |
May | 508.00000 | 23.83806 | 45.98265 | -0.5580 | 13.02304 |
June | 496.00000 | 23.95894 | 50.65564 | -0.4595 | 10.65776 |
July | 497.00000 | 24.28673 | 53.12022 | -0.2866 | 7.88364 |
August | 514.00000 | 24.17419 | 54.66065 | -0.3079 | 7.95806 |
September | 485.00000 | 23.97619 | 51.72161 | -0.4439 | 10.12575 |
October | 502.00000 | 24.00063 | 43.03577 | 0.39649 | 8.89803 |
November | 489.00000 | 23.53346 | 40.26377 | 0.22517 | 6.76243 |
December | 497.00000 | 23.18241 | 35.70580 | 0.10108 | 5.94962 |
Annual Sum or Average | 5943.00000 | 23.66570 | 45.96423 | -0.0537 | 8.26928 |
Minimum of Months | 454.00000 | 22.97215 | 35.70580 | -0.5580 | 5.94962 |
Maximum of Months | 514.00000 | 24.28673 | 54.66065 | 0.39649 | 13.02304 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57203 | 37.15156 | 0.28362 | 8.54271 |
February | 454.00000 | 23.13520 | 41.31051 | 0.17939 | 7.55157 |
March | 514.00000 | 22.79266 | 44.99732 | 0.10736 | 7.36899 |
April | 485.00000 | 23.34679 | 47.31100 | 0.25449 | 7.59929 |
May | 508.00000 | 23.14436 | 47.38909 | -0.7996 | 20.16960 |
June | 496.00000 | 23.39041 | 52.62686 | -0.6775 | 15.82622 |
July | 497.00000 | 23.84980 | 55.92587 | -0.4758 | 10.66393 |
August | 514.00000 | 23.91686 | 56.94838 | -0.4130 | 9.59009 |
September | 485.00000 | 24.00780 | 51.62226 | -0.3989 | 9.99887 |
October | 502.00000 | 24.20517 | 42.04600 | 0.48852 | 11.38022 |
November | 489.00000 | 23.81545 | 37.89697 | 0.35628 | 9.17080 |
December | 497.00000 | 23.71954 | 32.69990 | 0.29789 | 8.63804 |
Annual Sum or Average | 5943.00000 | 23.57562 | 45.70925 | -0.0697 | 10.57637 |
Minimum of Months | 454.00000 | 22.79266 | 32.69990 | -0.7996 | 7.36899 |
Maximum of Months | 514.00000 | 24.20517 | 56.94838 | 0.48852 | 20.16960 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.87247 | 40.35640 | 0.05617 | 6.42131 |
February | 454.00000 | 22.84183 | 43.37818 | 0.07001 | 6.26331 |
March | 514.00000 | 22.89668 | 46.09573 | 0.10474 | 6.58642 |
April | 485.00000 | 23.68465 | 46.96344 | 0.33336 | 8.48683 |
May | 508.00000 | 23.82355 | 45.99397 | -0.5552 | 13.24515 |
June | 496.00000 | 24.01068 | 50.46163 | -0.4290 | 10.00839 |
July | 497.00000 | 24.29432 | 53.20242 | -0.2793 | 7.71424 |
August | 514.00000 | 24.17458 | 54.83041 | -0.3077 | 7.88522 |
September | 485.00000 | 24.10182 | 51.26970 | -0.3898 | 9.21104 |
October | 502.00000 | 23.97788 | 43.09708 | 0.39362 | 9.11959 |
November | 489.00000 | 23.38548 | 40.25286 | 0.19735 | 6.84616 |
December | 497.00000 | 22.94791 | 35.81113 | 0.05018 | 6.09302 |
Annual Sum or Average | 5943.00000 | 23.58854 | 46.00770 | -0.0650 | 8.17258 |
Minimum of Months | 454.00000 | 22.84183 | 35.81113 | -0.5552 | 6.09302 |
Maximum of Months | 514.00000 | 24.29432 | 54.83041 | 0.39362 | 13.24515 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60419 | 41.03767 | -0.0247 | 6.40772 |
February | 454.00000 | 22.74243 | 43.82789 | 0.03034 | 5.94904 |
March | 514.00000 | 22.84096 | 46.64927 | 0.07588 | 6.26054 |
April | 485.00000 | 23.41692 | 47.78857 | 0.24358 | 6.92101 |
May | 508.00000 | 23.67222 | 46.31509 | -0.6398 | 14.46617 |
June | 496.00000 | 23.95275 | 50.54518 | -0.4882 | 10.39821 |
July | 497.00000 | 24.10291 | 54.03367 | -0.3962 | 8.56175 |
August | 514.00000 | 23.98536 | 55.85223 | -0.4288 | 9.12615 |
September | 485.00000 | 23.82459 | 52.40876 | -0.5330 | 11.48950 |
October | 502.00000 | 23.73821 | 43.86763 | 0.31024 | 7.68736 |
November | 489.00000 | 23.08996 | 41.23691 | 0.10352 | 6.19489 |
December | 497.00000 | 22.65330 | 36.68151 | -0.0369 | 5.97202 |
Annual Sum or Average | 5943.00000 | 23.38965 | 46.71892 | -0.1508 | 8.30782 |
Minimum of Months | 454.00000 | 22.60419 | 36.68151 | -0.6398 | 5.94904 |
Maximum of Months | 514.00000 | 24.10291 | 55.85223 | 0.31024 | 14.46617 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.86355 | 40.03218 | 0.05695 | 6.52892 |
February | 385.00000 | 22.86359 | 42.90568 | 0.08072 | 6.42545 |
March | 433.00000 | 22.99873 | 45.14115 | 0.13561 | 7.02974 |
April | 410.00000 | 23.66365 | 46.37037 | 0.33642 | 8.60955 |
May | 430.00000 | 23.80158 | 45.45360 | -0.5558 | 13.57961 |
June | 418.00000 | 23.97320 | 50.08339 | -0.4401 | 10.68615 |
July | 422.00000 | 24.26871 | 52.99812 | -0.2873 | 8.53016 |
August | 433.00000 | 24.10886 | 54.84237 | -0.3249 | 8.70670 |
September | 410.00000 | 23.86813 | 51.69490 | -0.4753 | 11.26136 |
October | 427.00000 | 23.86323 | 43.36974 | 0.36628 | 8.76212 |
November | 417.00000 | 23.27359 | 40.33012 | 0.16890 | 6.65965 |
December | 422.00000 | 22.90904 | 35.55944 | 0.04350 | 6.09191 |
Annual Sum or Average | 5034.00000 | 23.54192 | 45.74887 | -0.0760 | 8.58515 |
Minimum of Months | 385.00000 | 22.86355 | 35.55944 | -0.5558 | 6.09191 |
Maximum of Months | 433.00000 | 24.26871 | 54.84237 | 0.36628 | 13.57961 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63403 | 37.34191 | 0.28651 | 8.74915 |
February | 454.00000 | 23.46806 | 40.96427 | 0.24907 | 8.18478 |
March | 514.00000 | 23.35682 | 44.30004 | 0.23098 | 7.89035 |
April | 485.00000 | 23.73947 | 46.13905 | 0.34889 | 8.63829 |
May | 508.00000 | 23.70645 | 45.96106 | -0.6154 | 14.29023 |
June | 496.00000 | 23.90134 | 50.64313 | -0.5017 | 10.90419 |
July | 497.00000 | 24.11472 | 53.88139 | -0.3819 | 8.65052 |
August | 514.00000 | 24.09522 | 55.00971 | -0.3507 | 8.29935 |
September | 485.00000 | 24.12110 | 50.72470 | -0.3634 | 9.24702 |
October | 502.00000 | 24.21287 | 41.86682 | 0.48546 | 11.28963 |
November | 489.00000 | 23.90472 | 37.86680 | 0.36364 | 9.37084 |
December | 497.00000 | 23.77670 | 32.98449 | 0.30104 | 8.85552 |
Annual Sum or Average | 5943.00000 | 23.83741 | 44.84959 | 0.00139 | 9.54434 |
Minimum of Months | 454.00000 | 23.35682 | 32.98449 | -0.6154 | 7.89035 |
Maximum of Months | 514.00000 | 24.21287 | 55.00971 | 0.48546 | 14.29023 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.73519 | 40.04277 | 0.03429 | 6.84356 |
February | 454.00000 | 22.83165 | 42.87278 | 0.08303 | 6.74603 |
March | 514.00000 | 22.89682 | 45.68302 | 0.12380 | 7.06126 |
April | 485.00000 | 23.59751 | 46.73985 | 0.33499 | 8.93106 |
May | 508.00000 | 23.74792 | 45.73726 | -0.5523 | 13.88397 |
June | 496.00000 | 23.97300 | 50.26723 | -0.4098 | 10.09464 |
July | 497.00000 | 24.20204 | 53.49713 | -0.2854 | 8.32083 |
August | 514.00000 | 24.07374 | 55.21653 | -0.3164 | 8.45522 |
September | 485.00000 | 23.95961 | 51.57927 | -0.4168 | 10.32263 |
October | 502.00000 | 23.82034 | 43.27503 | 0.36803 | 9.13177 |
November | 489.00000 | 23.17305 | 40.18839 | 0.15790 | 7.02377 |
December | 497.00000 | 22.80367 | 35.60421 | 0.02782 | 6.53414 |
Annual Sum or Average | 5943.00000 | 23.48856 | 45.92621 | -0.0730 | 8.62752 |
Minimum of Months | 454.00000 | 22.73519 | 35.60421 | -0.5523 | 6.53414 |
Maximum of Months | 514.00000 | 24.20204 | 55.21653 | 0.36803 | 13.88397 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.186008E+10 | 0.00 | 90.69 | 119620.87 | 10-JAN-07:02 | 0.00 | 32.35 | 35.86 | 0.01 | 0.00 | 0.00 | 0.65 | 10-JAN-07:02 |
February | 0.865624E+09 | 0.00 | 74.02 | 72132.10 | 27-FEB-07:03 | 0.00 | 33.82 | 36.77 | 0.00 | 0.00 | 0.00 | 0.39 | 27-FEB-07:03 |
March | 0.159062E+10 | 0.00 | 95.78 | 118772.35 | 30-MAR-06:02 | 0.00 | 36.15 | 39.33 | 0.01 | 0.00 | 0.00 | 0.64 | 30-MAR-06:02 |
April | 0.390587E+09 | 0.00 | 43.90 | 61147.59 | 01-APR-06:03 | 0.00 | 38.28 | 39.62 | 0.00 | 0.00 | 0.00 | 0.33 | 01-APR-06:03 |
May | 0.288664E+09 | 0.00 | 28.41 | 18691.25 | 15-MAY-06:03 | 0.00 | 38.27 | 39.12 | 0.00 | 0.00 | 0.00 | 0.10 | 15-MAY-06:03 |
June | 91882656.02 | 0.00 | 86.13 | 8281.85 | 22-JUN-06:08 | 0.00 | 34.38 | 37.64 | 0.00 | 0.00 | 0.00 | 0.04 | 22-JUN-06:08 |
July | 5049503.93 | 0.00 | 163.79 | 2593.17 | 17-JUL-06:10 | 0.00 | 31.18 | 37.52 | 0.00 | 0.00 | 0.00 | 0.01 | 17-JUL-06:10 |
August | 7192926.06 | 0.00 | 205.25 | 4218.47 | 28-AUG-06:08 | 0.00 | 32.21 | 39.89 | 0.00 | 0.00 | 0.00 | 0.02 | 28-AUG-06:08 |
September | 31825295.98 | 0.00 | 90.94 | 8671.10 | 19-SEP-06:08 | 0.00 | 34.43 | 37.66 | 0.00 | 0.00 | 0.00 | 0.05 | 19-SEP-06:08 |
October | 96998692.12 | 0.00 | 65.66 | 27268.99 | 30-OCT-06:02 | 0.00 | 37.78 | 39.69 | 0.00 | 0.00 | 0.00 | 0.15 | 30-OCT-06:02 |
November | 0.342458E+09 | 0.00 | 35.14 | 44090.88 | 27-NOV-07:03 | 0.00 | 33.47 | 34.73 | 0.00 | 0.00 | 0.00 | 0.24 | 27-NOV-07:03 |
December | 0.102348E+10 | 0.00 | 78.66 | 77926.12 | 26-DEC-07:03 | 0.00 | 31.55 | 34.44 | 0.00 | 0.00 | 0.00 | 0.42 | 26-DEC-07:03 |
Annual Sum or Average | 0.659445E+10 | 0.00 | 1058.35 | 0.00 | 34.49 | 37.70 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5049503.93 | 0.00 | 28.41 | 2593.17 | 0.00 | 31.18 | 34.44 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.186008E+10 | 0.00 | 205.25 | 119620.87 | 0.00 | 38.28 | 39.89 | 0.01 | 0.00 | 0.00 | 0.65 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.869492E+10 | 0.200843E+10 | 205.03 | 0.803935E+10 | 0.655570E+09 | 0.00 | 1.00 | 13-JAN-11:40 | 0.00 | 01-JAN-00:10 | 39493.05 | 18-JAN-13:30 | 39493.05 | 18-JAN-13:30 | 7401.44 | 17-JAN-07:03 | 8670.47 | 18-JAN-13:10 | 0.00 |
February | 0.497463E+10 | 0.118524E+10 | 157.39 | 0.426240E+10 | 0.712230E+09 | 0.00 | 1.00 | 01-FEB-10:00 | 0.00 | 01-FEB-00:10 | 37707.20 | 01-FEB-12:00 | 37707.20 | 01-FEB-12:00 | 7209.93 | 01-FEB-16:00 | 8345.82 | 01-FEB-12:00 | 0.00 |
March | 0.594638E+10 | 0.138256E+10 | 148.58 | 0.471128E+10 | 0.123510E+10 | 0.00 | 1.00 | 22-MAR-12:10 | 0.00 | 01-MAR-00:10 | 40432.30 | 23-MAR-15:00 | 33236.94 | 23-MAR-14:10 | 10976.41 | 23-MAR-16:00 | 8533.11 | 23-MAR-15:00 | 0.00 |
April | 0.132225E+11 | 0.302014E+10 | 252.06 | 0.111164E+11 | 0.210606E+10 | 0.00 | 1.00 | 04-APR-12:20 | 0.00 | 01-APR-00:10 | 46199.61 | 26-APR-14:10 | 44528.14 | 26-APR-14:10 | 13709.83 | 27-APR-06:03 | 10118.41 | 26-APR-14:10 | 0.00 |
May | 0.141724E+11 | 0.327445E+10 | 305.30 | 0.120634E+11 | 0.210902E+10 | 0.00 | 1.00 | 02-MAY-12:40 | 0.00 | 01-MAY-00:10 | 35396.92 | 04-MAY-14:10 | 35221.54 | 03-MAY-13:00 | 14392.75 | 05-MAY-06:03 | 7434.87 | 04-MAY-14:10 | 0.00 |
June | 0.263716E+11 | 0.586481E+10 | 386.65 | 0.199918E+11 | 0.637979E+10 | 0.00 | 1.00 | 13-JUN-10:50 | 0.00 | 01-JUN-00:10 | 56129.55 | 28-JUN-11:00 | 39208.13 | 29-JUN-11:00 | 25017.40 | 28-JUN-06:03 | 11892.35 | 28-JUN-11:00 | 0.00 |
July | 0.448842E+11 | 0.977840E+10 | 423.40 | 0.300356E+11 | 0.148487E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 85490.55 | 31-JUL-15:40 | 52750.41 | 31-JUL-14:10 | 35864.77 | 31-JUL-15:40 | 18188.71 | 31-JUL-15:40 | 0.00 |
August | 0.518214E+11 | 0.112358E+11 | 440.49 | 0.336777E+11 | 0.181437E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 81684.11 | 18-AUG-15:50 | 51495.66 | 17-AUG-14:10 | 43069.05 | 07-AUG-06:03 | 17339.97 | 18-AUG-15:50 | 0.00 |
September | 0.319440E+11 | 0.717629E+10 | 375.59 | 0.231164E+11 | 0.882755E+10 | 0.00 | 1.00 | 01-SEP-10:30 | 0.00 | 01-SEP-00:10 | 63652.16 | 22-SEP-12:30 | 61181.21 | 29-SEP-15:20 | 34666.23 | 22-SEP-10:20 | 17581.46 | 29-SEP-13:00 | 0.00 |
October | 0.353003E+11 | 0.799082E+10 | 383.57 | 0.280880E+11 | 0.721232E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 75024.33 | 03-OCT-13:20 | 66612.52 | 16-OCT-11:00 | 41744.88 | 05-OCT-06:03 | 20207.70 | 16-OCT-11:00 | 0.00 |
November | 0.989978E+10 | 0.229003E+10 | 231.94 | 0.884994E+10 | 0.104984E+10 | 0.00 | 1.00 | 08-NOV-10:30 | 0.00 | 01-NOV-00:10 | 38322.94 | 28-NOV-14:00 | 38322.94 | 28-NOV-14:00 | 8669.74 | 20-NOV-13:10 | 8276.12 | 28-NOV-14:00 | 0.00 |
December | 0.103900E+11 | 0.235587E+10 | 208.82 | 0.101055E+11 | 0.284490E+09 | 0.00 | 1.00 | 04-DEC-09:30 | 0.00 | 01-DEC-00:10 | 40786.32 | 05-DEC-15:10 | 40786.32 | 05-DEC-15:10 | 5631.16 | 07-DEC-15:50 | 8737.15 | 05-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.257622E+12 | 0.575628E+11 | 3518.84 | 0.194058E+12 | 0.635643E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.497463E+10 | 0.118524E+10 | 148.58 | 0.426240E+10 | 0.284490E+09 | 0.00 | 1.00 | 0.00 | 35396.92 | 33236.94 | 5631.16 | 7434.87 | 0.00 | ||||||
Maximum of Months | 0.518214E+11 | 0.112358E+11 | 440.49 | 0.336777E+11 | 0.181437E+11 | 0.00 | 1.00 | 0.00 | 85490.55 | 66612.52 | 43069.05 | 20207.70 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.737625E+10 | 0.172206E+10 | 201.64 | 0.668972E+10 | 0.686528E+09 | 0.00 | 1.00 | 13-JAN-13:20 | 0.00 | 01-JAN-00:10 | 35065.64 | 18-JAN-14:00 | 35065.64 | 18-JAN-14:00 | 7161.43 | 20-JAN-13:20 | 7507.35 | 18-JAN-13:20 | 0.00 |
February | 0.426830E+10 | 0.102271E+10 | 156.17 | 0.363724E+10 | 0.631057E+09 | 0.00 | 1.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 | 29686.97 | 01-FEB-12:00 | 29686.97 | 01-FEB-12:00 | 6797.25 | 01-FEB-14:00 | 6572.86 | 01-FEB-12:00 | 0.00 |
March | 0.538280E+10 | 0.125580E+10 | 151.44 | 0.424005E+10 | 0.114275E+10 | 0.00 | 1.00 | 22-MAR-12:20 | 0.00 | 01-MAR-00:10 | 36941.19 | 23-MAR-15:00 | 30379.69 | 23-MAR-14:00 | 9581.51 | 23-MAR-16:00 | 7796.65 | 23-MAR-15:00 | 0.00 |
April | 0.120326E+11 | 0.276412E+10 | 259.15 | 0.101255E+11 | 0.190717E+10 | 0.00 | 1.00 | 04-APR-12:30 | 0.00 | 01-APR-00:10 | 42197.45 | 26-APR-14:10 | 40617.54 | 26-APR-14:10 | 6448.94 | 13-APR-16:00 | 9302.43 | 26-APR-13:00 | 0.00 |
May | 0.123616E+11 | 0.287669E+10 | 307.90 | 0.104510E+11 | 0.191066E+10 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 33080.45 | 03-MAY-13:00 | 33080.45 | 03-MAY-13:00 | 10044.53 | 05-MAY-15:00 | 6979.30 | 03-MAY-13:00 | 0.00 |
June | 0.232135E+11 | 0.518649E+10 | 390.28 | 0.176724E+11 | 0.554112E+10 | 0.00 | 1.00 | 13-JUN-14:50 | 0.00 | 01-JUN-00:10 | 50651.62 | 29-JUN-13:00 | 33745.89 | 29-JUN-11:00 | 17920.17 | 29-JUN-13:00 | 10732.65 | 29-JUN-13:00 | 0.00 |
July | 0.389398E+11 | 0.852394E+10 | 429.93 | 0.262840E+11 | 0.126558E+11 | 0.00 | 1.00 | 03-JUL-09:10 | 0.00 | 01-JUL-00:10 | 75003.02 | 31-JUL-15:40 | 46230.15 | 31-JUL-14:10 | 31142.36 | 31-JUL-15:40 | 15961.56 | 31-JUL-15:40 | 0.00 |
August | 0.449150E+11 | 0.977581E+10 | 445.64 | 0.295294E+11 | 0.153856E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.00 | 01-AUG-00:10 | 72968.82 | 18-AUG-15:50 | 45966.00 | 18-AUG-15:00 | 30667.60 | 18-AUG-15:50 | 15492.58 | 18-AUG-15:50 | 0.00 |
September | 0.274047E+11 | 0.620084E+10 | 377.72 | 0.199899E+11 | 0.741471E+10 | 0.00 | 1.00 | 01-SEP-10:40 | 0.00 | 01-SEP-00:10 | 57643.50 | 29-SEP-15:20 | 57643.50 | 29-SEP-15:20 | 28100.45 | 22-SEP-10:00 | 16952.71 | 29-SEP-13:00 | 0.00 |
October | 0.297558E+11 | 0.679790E+10 | 383.81 | 0.238085E+11 | 0.594726E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 68684.10 | 03-OCT-13:20 | 60647.05 | 16-OCT-11:00 | 28134.45 | 02-OCT-06:03 | 18399.66 | 16-OCT-11:00 | 0.00 |
November | 0.829221E+10 | 0.193657E+10 | 230.17 | 0.732422E+10 | 0.967986E+09 | 0.00 | 1.00 | 10-NOV-13:10 | 0.00 | 01-NOV-00:10 | 33037.53 | 28-NOV-14:00 | 33037.53 | 28-NOV-14:00 | 7692.77 | 20-NOV-13:10 | 7135.84 | 28-NOV-14:00 | 0.00 |
December | 0.869937E+10 | 0.199524E+10 | 206.79 | 0.841216E+10 | 0.287208E+09 | 0.00 | 1.00 | 05-DEC-09:30 | 0.00 | 01-DEC-00:10 | 34874.01 | 05-DEC-15:10 | 34874.01 | 05-DEC-15:10 | 6352.25 | 07-DEC-13:00 | 7516.25 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.222642E+12 | 0.500582E+11 | 3540.63 | 0.168164E+12 | 0.544779E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.426830E+10 | 0.102271E+10 | 151.44 | 0.363724E+10 | 0.287208E+09 | 0.00 | 1.00 | 0.00 | 29686.97 | 29686.97 | 6352.25 | 6572.86 | 0.00 | ||||||
Maximum of Months | 0.449150E+11 | 0.977581E+10 | 445.64 | 0.295294E+11 | 0.153856E+11 | 0.00 | 1.00 | 0.00 | 75003.02 | 60647.05 | 31142.36 | 18399.66 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.689647E+10 | 0.164017E+10 | 198.17 | 0.609142E+10 | 0.805051E+09 | 0.00 | 1.00 | 13-JAN-13:50 | 0.00 | 01-JAN-00:10 | 36188.83 | 18-JAN-13:30 | 36188.83 | 18-JAN-13:30 | 6967.54 | 20-JAN-13:10 | 7905.19 | 18-JAN-13:20 | 0.00 |
February | 0.401999E+10 | 0.980324E+09 | 151.89 | 0.332838E+10 | 0.691612E+09 | 0.00 | 1.00 | 01-FEB-12:00 | 0.00 | 01-FEB-00:10 | 29853.10 | 01-FEB-12:00 | 29853.10 | 01-FEB-12:00 | 6936.07 | 01-FEB-14:00 | 6610.90 | 01-FEB-12:00 | 0.00 |
March | 0.533853E+10 | 0.125741E+10 | 148.42 | 0.409256E+10 | 0.124597E+10 | 0.00 | 1.00 | 22-MAR-12:50 | 0.00 | 01-MAR-00:10 | 38923.81 | 23-MAR-15:00 | 32124.32 | 23-MAR-14:00 | 10378.93 | 23-MAR-15:50 | 8216.22 | 23-MAR-15:00 | 0.00 |
April | 0.125730E+11 | 0.290938E+10 | 258.40 | 0.102436E+11 | 0.232941E+10 | 0.00 | 1.00 | 04-APR-12:50 | 0.00 | 01-APR-00:10 | 50804.43 | 26-APR-14:00 | 48929.24 | 26-APR-14:00 | 7140.97 | 13-APR-16:00 | 11255.94 | 26-APR-13:50 | 0.00 |
May | 0.128167E+11 | 0.300216E+10 | 306.61 | 0.104970E+11 | 0.231977E+10 | 0.00 | 1.00 | 02-MAY-13:10 | 0.00 | 01-MAY-00:10 | 36237.93 | 03-MAY-13:00 | 36237.93 | 03-MAY-13:00 | 9800.88 | 05-MAY-15:00 | 7645.85 | 03-MAY-13:00 | 0.00 |
June | 0.245647E+11 | 0.551521E+10 | 391.89 | 0.181937E+11 | 0.637106E+10 | 0.00 | 1.00 | 14-JUN-12:10 | 0.00 | 01-JUN-00:10 | 55658.42 | 29-JUN-13:00 | 36443.02 | 27-JUN-13:00 | 19976.26 | 29-JUN-13:00 | 11794.31 | 29-JUN-13:00 | 0.00 |
July | 0.414526E+11 | 0.911490E+10 | 432.90 | 0.274971E+11 | 0.139555E+11 | 0.00 | 1.00 | 03-JUL-10:10 | 0.00 | 01-JUL-00:10 | 85880.04 | 31-JUL-15:10 | 53913.72 | 31-JUL-14:00 | 33757.42 | 31-JUL-15:20 | 18522.00 | 31-JUL-15:10 | 0.00 |
August | 0.475406E+11 | 0.103848E+11 | 447.04 | 0.306138E+11 | 0.169269E+11 | 0.00 | 1.00 | 01-AUG-10:20 | 0.00 | 01-AUG-00:10 | 84735.22 | 18-AUG-15:30 | 53360.74 | 17-AUG-14:00 | 34106.89 | 18-AUG-15:30 | 18223.18 | 17-AUG-15:40 | 0.00 |
September | 0.278671E+11 | 0.636392E+10 | 375.96 | 0.200089E+11 | 0.785817E+10 | 0.00 | 1.00 | 01-SEP-12:50 | 0.00 | 01-SEP-00:10 | 66822.86 | 29-SEP-13:40 | 66822.86 | 29-SEP-13:40 | 26733.18 | 22-SEP-11:40 | 19494.25 | 29-SEP-13:00 | 0.00 |
October | 0.296532E+11 | 0.685186E+10 | 379.94 | 0.234397E+11 | 0.621350E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 72838.25 | 03-OCT-13:10 | 68252.33 | 16-OCT-13:10 | 29422.76 | 01-OCT-12:13 | 19942.75 | 16-OCT-11:00 | 0.00 |
November | 0.760851E+10 | 0.181654E+10 | 224.11 | 0.655144E+10 | 0.105707E+10 | 0.00 | 1.00 | 19-NOV-10:53 | 0.00 | 01-NOV-00:10 | 34378.12 | 19-NOV-12:52 | 34378.12 | 19-NOV-12:52 | 7274.85 | 10-NOV-15:00 | 7807.93 | 19-NOV-12:52 | 0.00 |
December | 0.800349E+10 | 0.187693E+10 | 203.06 | 0.768509E+10 | 0.318396E+09 | 0.00 | 1.00 | 05-DEC-13:50 | 0.00 | 01-DEC-00:10 | 37181.87 | 05-DEC-15:00 | 37181.87 | 05-DEC-15:00 | 6614.35 | 07-DEC-13:00 | 8030.96 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.228335E+12 | 0.517136E+11 | 3518.39 | 0.168243E+12 | 0.600924E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.401999E+10 | 0.980324E+09 | 148.42 | 0.332838E+10 | 0.318396E+09 | 0.00 | 1.00 | 0.00 | 29853.10 | 29853.10 | 6614.35 | 6610.90 | 0.00 | ||||||
Maximum of Months | 0.475406E+11 | 0.103848E+11 | 447.04 | 0.306138E+11 | 0.169269E+11 | 0.00 | 1.00 | 0.00 | 85880.04 | 68252.33 | 34106.89 | 19942.75 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 293.44 | 0.00 | 293.44 | 191.30 | 1077.05 | 0.00 | 0.00 | 0.00 |
February | 368.34 | 0.00 | 368.34 | 225.80 | 978.39 | 0.00 | 0.00 | 0.00 |
March | 451.37 | 0.00 | 451.37 | 324.06 | 1008.86 | 0.00 | 0.00 | 0.00 |
April | 520.04 | 2.00 | 518.04 | 441.83 | 807.18 | 0.00 | 0.00 | 0.00 |
May | 624.92 | 29.10 | 595.82 | 562.22 | 709.57 | 0.00 | 0.00 | 0.00 |
June | 665.88 | 65.10 | 600.78 | 713.15 | 560.04 | 0.00 | 0.00 | 0.00 |
July | 630.49 | 52.85 | 577.64 | 748.13 | 502.43 | 0.00 | 0.00 | 0.00 |
August | 523.60 | 10.48 | 513.11 | 600.59 | 527.79 | 0.00 | 0.00 | 0.00 |
September | 443.17 | 0.07 | 443.10 | 469.00 | 630.11 | 0.00 | 0.00 | 0.00 |
October | 351.54 | 0.00 | 351.54 | 410.57 | 704.14 | 0.00 | 0.00 | 0.00 |
November | 318.29 | 0.00 | 318.29 | 216.77 | 993.76 | 0.00 | 0.00 | 0.00 |
December | 273.17 | 0.00 | 273.17 | 173.69 | 1085.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.72 | 13.37 | 442.35 | 424.31 | 797.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.17 | 0.00 | 273.17 | 173.69 | 502.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.88 | 65.10 | 600.78 | 748.13 | 1085.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.68 | 282.22 | 245.47 | 640.16 | 679.34 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 255.01 | 301.65 | 629.95 | 622.15 | 0.00 | 0.00 | 0.00 |
March | 676.17 | 301.26 | 374.91 | 796.66 | 640.48 | 0.00 | 0.00 | 0.00 |
April | 864.48 | 433.55 | 430.92 | 1152.18 | 527.10 | 0.00 | 0.00 | 0.00 |
May | 815.82 | 340.46 | 475.36 | 1042.96 | 484.10 | 0.00 | 0.00 | 0.00 |
June | 810.74 | 351.77 | 458.97 | 1109.17 | 387.92 | 0.00 | 0.00 | 0.00 |
July | 918.63 | 456.49 | 462.14 | 1353.92 | 349.48 | 0.00 | 0.00 | 0.00 |
August | 907.22 | 481.88 | 425.34 | 1356.01 | 356.45 | 0.00 | 0.00 | 0.00 |
September | 660.53 | 302.68 | 357.85 | 934.41 | 410.31 | 0.00 | 0.00 | 0.00 |
October | 584.69 | 300.51 | 284.17 | 846.90 | 452.28 | 0.00 | 0.00 | 0.00 |
November | 533.01 | 270.79 | 262.22 | 642.94 | 631.29 | 0.00 | 0.00 | 0.00 |
December | 508.48 | 282.52 | 225.96 | 617.71 | 682.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.94 | 338.93 | 359.01 | 929.00 | 518.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.48 | 255.01 | 225.96 | 617.71 | 349.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 918.63 | 481.88 | 475.36 | 1356.01 | 682.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1936.48 | 1420.50 | 515.98 | 2826.27 | 1050.33 | 0.00 | 0.00 | 0.00 |
February | 1521.97 | 937.46 | 584.52 | 2085.43 | 960.36 | 0.00 | 0.00 | 0.00 |
March | 1213.37 | 586.11 | 627.25 | 1637.40 | 1010.88 | 0.00 | 0.00 | 0.00 |
April | 1013.80 | 386.57 | 627.23 | 1457.77 | 847.85 | 0.00 | 0.00 | 0.00 |
May | 721.90 | 88.84 | 633.06 | 835.25 | 773.42 | 0.00 | 0.00 | 0.00 |
June | 633.30 | 38.24 | 595.06 | 733.36 | 606.76 | 0.00 | 0.00 | 0.00 |
July | 670.84 | 75.52 | 595.32 | 909.89 | 538.82 | 0.00 | 0.00 | 0.00 |
August | 861.83 | 271.85 | 589.98 | 1355.47 | 562.63 | 0.00 | 0.00 | 0.00 |
September | 1199.23 | 607.69 | 591.54 | 1894.01 | 651.98 | 0.00 | 0.00 | 0.00 |
October | 1525.14 | 1019.60 | 505.54 | 2418.77 | 709.29 | 0.00 | 0.00 | 0.00 |
November | 1853.66 | 1308.65 | 545.00 | 2692.22 | 972.18 | 0.00 | 0.00 | 0.00 |
December | 2068.78 | 1574.62 | 494.17 | 3034.80 | 1054.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.30 | 692.14 | 575.16 | 1822.65 | 810.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 633.30 | 38.24 | 494.17 | 733.36 | 538.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.78 | 1574.62 | 633.06 | 3034.80 | 1054.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.26 | 253.32 | 248.94 | 636.53 | 711.82 | 0.00 | 0.00 | 0.00 |
February | 599.20 | 276.62 | 322.58 | 721.19 | 646.52 | 0.00 | 0.00 | 0.00 |
March | 686.85 | 303.87 | 382.97 | 836.92 | 663.54 | 0.00 | 0.00 | 0.00 |
April | 946.86 | 493.03 | 453.83 | 1295.87 | 554.04 | 0.00 | 0.00 | 0.00 |
May | 930.11 | 429.62 | 500.49 | 1231.39 | 505.25 | 0.00 | 0.00 | 0.00 |
June | 985.35 | 492.66 | 492.69 | 1379.26 | 399.37 | 0.00 | 0.00 | 0.00 |
July | 1043.07 | 558.14 | 484.93 | 1542.32 | 360.55 | 0.00 | 0.00 | 0.00 |
August | 978.60 | 530.36 | 448.24 | 1468.23 | 374.27 | 0.00 | 0.00 | 0.00 |
September | 837.87 | 448.33 | 389.54 | 1217.42 | 426.07 | 0.00 | 0.00 | 0.00 |
October | 640.51 | 349.69 | 290.82 | 957.05 | 474.11 | 0.00 | 0.00 | 0.00 |
November | 578.57 | 302.63 | 275.94 | 748.47 | 653.92 | 0.00 | 0.00 | 0.00 |
December | 510.98 | 274.07 | 236.91 | 661.38 | 716.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 770.69 | 393.19 | 377.49 | 1059.65 | 539.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 502.26 | 253.32 | 236.91 | 636.53 | 360.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1043.07 | 558.14 | 500.49 | 1542.32 | 716.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 60.55 | 383.41 | 0.00 | 0.00 | 0.00 |
February | 122.77 | 0.00 | 122.77 | 75.63 | 341.12 | 0.00 | 0.00 | 0.00 |
March | 150.45 | 0.00 | 150.45 | 111.13 | 346.85 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.67 | 153.78 | 273.26 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 193.45 | 241.21 | 0.00 | 0.00 | 0.00 |
June | 221.95 | 21.70 | 200.25 | 247.13 | 187.47 | 0.00 | 0.00 | 0.00 |
July | 210.15 | 17.61 | 192.54 | 257.09 | 169.53 | 0.00 | 0.00 | 0.00 |
August | 174.52 | 3.49 | 171.03 | 206.26 | 178.08 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.69 | 159.37 | 217.14 | 0.00 | 0.00 | 0.00 |
October | 117.17 | 0.00 | 117.17 | 136.80 | 247.07 | 0.00 | 0.00 | 0.00 |
November | 106.09 | 0.00 | 106.09 | 69.05 | 354.49 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 54.42 | 386.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.90 | 4.46 | 147.44 | 144.13 | 276.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 54.42 | 169.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.95 | 21.70 | 200.25 | 257.09 | 386.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 60.56 | 383.43 | 0.00 | 0.00 | 0.00 |
February | 122.78 | 0.00 | 122.78 | 75.63 | 341.14 | 0.00 | 0.00 | 0.00 |
March | 150.46 | 0.00 | 150.46 | 111.13 | 346.87 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.68 | 153.79 | 273.28 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 193.46 | 241.23 | 0.00 | 0.00 | 0.00 |
June | 221.96 | 21.70 | 200.26 | 247.14 | 187.49 | 0.00 | 0.00 | 0.00 |
July | 210.16 | 17.61 | 192.55 | 257.10 | 169.54 | 0.00 | 0.00 | 0.00 |
August | 174.53 | 3.49 | 171.04 | 206.27 | 178.09 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.70 | 159.38 | 217.16 | 0.00 | 0.00 | 0.00 |
October | 117.18 | 0.00 | 117.18 | 136.81 | 247.09 | 0.00 | 0.00 | 0.00 |
November | 106.10 | 0.00 | 106.10 | 69.05 | 354.51 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 54.43 | 386.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.91 | 4.46 | 147.45 | 144.14 | 276.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 54.43 | 169.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.96 | 21.70 | 200.26 | 257.10 | 386.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.81 | 0.00 | 97.81 | 60.56 | 383.43 | 0.00 | 0.00 | 0.00 |
February | 122.78 | 0.00 | 122.78 | 75.63 | 341.14 | 0.00 | 0.00 | 0.00 |
March | 150.46 | 0.00 | 150.46 | 111.13 | 346.87 | 0.00 | 0.00 | 0.00 |
April | 173.34 | 0.67 | 172.68 | 153.79 | 273.28 | 0.00 | 0.00 | 0.00 |
May | 208.30 | 9.70 | 198.60 | 193.46 | 241.23 | 0.00 | 0.00 | 0.00 |
June | 221.96 | 21.70 | 200.26 | 247.14 | 187.49 | 0.00 | 0.00 | 0.00 |
July | 210.16 | 17.61 | 192.55 | 257.10 | 169.54 | 0.00 | 0.00 | 0.00 |
August | 174.53 | 3.49 | 171.04 | 206.27 | 178.09 | 0.00 | 0.00 | 0.00 |
September | 147.72 | 0.02 | 147.70 | 159.38 | 217.16 | 0.00 | 0.00 | 0.00 |
October | 117.18 | 0.00 | 117.18 | 136.81 | 247.09 | 0.00 | 0.00 | 0.00 |
November | 106.10 | 0.00 | 106.10 | 69.05 | 354.51 | 0.00 | 0.00 | 0.00 |
December | 91.05 | 0.00 | 91.05 | 54.43 | 386.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.91 | 4.46 | 147.45 | 144.14 | 276.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 91.05 | 0.00 | 91.05 | 54.43 | 169.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 221.96 | 21.70 | 200.26 | 257.10 | 386.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 507.61 | 271.48 | 236.13 | 602.97 | 713.68 | 0.00 | 0.00 | 0.00 |
February | 535.47 | 245.30 | 290.17 | 603.15 | 640.08 | 0.00 | 0.00 | 0.00 |
March | 650.44 | 289.80 | 360.64 | 767.79 | 650.34 | 0.00 | 0.00 | 0.00 |
April | 831.58 | 417.05 | 414.53 | 1117.58 | 532.81 | 0.00 | 0.00 | 0.00 |
May | 784.78 | 327.50 | 457.27 | 1012.17 | 486.60 | 0.00 | 0.00 | 0.00 |
June | 779.89 | 338.38 | 441.51 | 1081.54 | 383.43 | 0.00 | 0.00 | 0.00 |
July | 883.68 | 439.12 | 444.56 | 1314.96 | 352.26 | 0.00 | 0.00 | 0.00 |
August | 872.70 | 463.55 | 409.15 | 1315.52 | 361.06 | 0.00 | 0.00 | 0.00 |
September | 635.40 | 291.16 | 344.23 | 903.70 | 419.98 | 0.00 | 0.00 | 0.00 |
October | 562.44 | 289.08 | 273.36 | 814.26 | 468.57 | 0.00 | 0.00 | 0.00 |
November | 512.73 | 260.49 | 252.24 | 607.83 | 661.84 | 0.00 | 0.00 | 0.00 |
December | 489.14 | 271.77 | 217.37 | 580.79 | 716.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.38 | 326.03 | 345.35 | 895.53 | 531.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 489.14 | 245.30 | 217.37 | 580.79 | 352.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.68 | 463.55 | 457.27 | 1315.52 | 716.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.07 | 10.73 | 9.34 | 23.84 | 28.22 | 0.00 | 0.00 | 0.00 |
February | 21.17 | 9.70 | 11.47 | 23.85 | 25.31 | 0.00 | 0.00 | 0.00 |
March | 25.72 | 11.46 | 14.26 | 30.36 | 25.71 | 0.00 | 0.00 | 0.00 |
April | 32.88 | 16.49 | 16.39 | 44.19 | 21.07 | 0.00 | 0.00 | 0.00 |
May | 31.03 | 12.95 | 18.08 | 40.02 | 19.24 | 0.00 | 0.00 | 0.00 |
June | 30.84 | 13.38 | 17.46 | 42.76 | 15.16 | 0.00 | 0.00 | 0.00 |
July | 34.94 | 17.36 | 17.58 | 51.99 | 13.93 | 0.00 | 0.00 | 0.00 |
August | 34.51 | 18.33 | 16.18 | 52.01 | 14.28 | 0.00 | 0.00 | 0.00 |
September | 25.12 | 11.51 | 13.61 | 35.73 | 16.61 | 0.00 | 0.00 | 0.00 |
October | 22.24 | 11.43 | 10.81 | 32.19 | 18.53 | 0.00 | 0.00 | 0.00 |
November | 20.27 | 10.30 | 9.97 | 24.03 | 26.17 | 0.00 | 0.00 | 0.00 |
December | 19.34 | 10.75 | 8.59 | 22.96 | 28.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.55 | 12.89 | 13.65 | 35.41 | 21.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.34 | 9.70 | 8.59 | 22.96 | 13.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.94 | 18.33 | 18.08 | 52.01 | 28.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.48 | 473.49 | 171.99 | 940.84 | 388.79 | 0.00 | 0.00 | 0.00 |
February | 507.32 | 312.48 | 194.84 | 700.00 | 345.78 | 0.00 | 0.00 | 0.00 |
March | 404.45 | 195.37 | 209.08 | 553.71 | 352.25 | 0.00 | 0.00 | 0.00 |
April | 337.93 | 128.85 | 209.07 | 494.79 | 290.67 | 0.00 | 0.00 | 0.00 |
May | 240.63 | 29.61 | 211.02 | 289.53 | 259.85 | 0.00 | 0.00 | 0.00 |
June | 211.10 | 12.75 | 198.35 | 257.02 | 199.22 | 0.00 | 0.00 | 0.00 |
July | 223.61 | 25.17 | 198.44 | 312.40 | 180.70 | 0.00 | 0.00 | 0.00 |
August | 287.27 | 90.61 | 196.66 | 459.87 | 192.52 | 0.00 | 0.00 | 0.00 |
September | 399.74 | 202.56 | 197.18 | 636.96 | 231.41 | 0.00 | 0.00 | 0.00 |
October | 508.37 | 339.86 | 168.51 | 808.77 | 258.47 | 0.00 | 0.00 | 0.00 |
November | 617.87 | 436.21 | 181.67 | 898.18 | 358.24 | 0.00 | 0.00 | 0.00 |
December | 689.58 | 524.86 | 164.72 | 1010.75 | 390.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.43 | 230.71 | 191.72 | 613.32 | 287.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.10 | 12.75 | 164.72 | 257.02 | 180.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 524.86 | 211.02 | 1010.75 | 390.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.48 | 473.49 | 171.99 | 940.84 | 388.79 | 0.00 | 0.00 | 0.00 |
February | 507.32 | 312.48 | 194.84 | 700.00 | 345.78 | 0.00 | 0.00 | 0.00 |
March | 404.45 | 195.37 | 209.08 | 553.71 | 352.25 | 0.00 | 0.00 | 0.00 |
April | 337.93 | 128.85 | 209.07 | 494.79 | 290.67 | 0.00 | 0.00 | 0.00 |
May | 240.63 | 29.61 | 211.02 | 289.53 | 259.85 | 0.00 | 0.00 | 0.00 |
June | 211.10 | 12.75 | 198.35 | 257.02 | 199.22 | 0.00 | 0.00 | 0.00 |
July | 223.61 | 25.17 | 198.44 | 312.40 | 180.70 | 0.00 | 0.00 | 0.00 |
August | 287.27 | 90.61 | 196.66 | 459.87 | 192.52 | 0.00 | 0.00 | 0.00 |
September | 399.74 | 202.56 | 197.18 | 636.96 | 231.41 | 0.00 | 0.00 | 0.00 |
October | 508.37 | 339.86 | 168.51 | 808.77 | 258.47 | 0.00 | 0.00 | 0.00 |
November | 617.87 | 436.21 | 181.67 | 898.18 | 358.24 | 0.00 | 0.00 | 0.00 |
December | 689.58 | 524.86 | 164.72 | 1010.75 | 390.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.43 | 230.71 | 191.72 | 613.32 | 287.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.10 | 12.75 | 164.72 | 257.02 | 180.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 524.86 | 211.02 | 1010.75 | 390.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 645.44 | 473.46 | 171.98 | 940.78 | 388.76 | 0.00 | 0.00 | 0.00 |
February | 507.28 | 312.46 | 194.82 | 699.95 | 345.76 | 0.00 | 0.00 | 0.00 |
March | 404.42 | 195.35 | 209.07 | 553.68 | 352.23 | 0.00 | 0.00 | 0.00 |
April | 337.91 | 128.85 | 209.06 | 494.76 | 290.65 | 0.00 | 0.00 | 0.00 |
May | 240.62 | 29.61 | 211.01 | 289.52 | 259.84 | 0.00 | 0.00 | 0.00 |
June | 211.09 | 12.74 | 198.34 | 257.01 | 199.21 | 0.00 | 0.00 | 0.00 |
July | 223.60 | 25.17 | 198.43 | 312.38 | 180.69 | 0.00 | 0.00 | 0.00 |
August | 287.25 | 90.61 | 196.65 | 459.84 | 192.51 | 0.00 | 0.00 | 0.00 |
September | 399.71 | 202.55 | 197.17 | 636.92 | 231.40 | 0.00 | 0.00 | 0.00 |
October | 508.34 | 339.84 | 168.50 | 808.72 | 258.45 | 0.00 | 0.00 | 0.00 |
November | 617.84 | 436.18 | 181.65 | 898.13 | 358.22 | 0.00 | 0.00 | 0.00 |
December | 689.54 | 524.83 | 164.71 | 1010.68 | 390.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.40 | 230.69 | 191.71 | 613.28 | 287.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.09 | 12.74 | 164.71 | 257.01 | 180.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.54 | 524.83 | 211.01 | 1010.68 | 390.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.15 | 243.68 | 239.47 | 607.37 | 748.19 | 0.00 | 0.00 | 0.00 |
February | 576.40 | 266.09 | 310.31 | 695.52 | 669.32 | 0.00 | 0.00 | 0.00 |
March | 660.71 | 292.31 | 368.40 | 811.25 | 678.56 | 0.00 | 0.00 | 0.00 |
April | 910.83 | 474.27 | 436.56 | 1258.60 | 565.07 | 0.00 | 0.00 | 0.00 |
May | 894.72 | 413.27 | 481.45 | 1196.68 | 514.97 | 0.00 | 0.00 | 0.00 |
June | 947.86 | 473.91 | 473.95 | 1344.94 | 401.21 | 0.00 | 0.00 | 0.00 |
July | 1003.38 | 536.90 | 466.48 | 1498.33 | 366.96 | 0.00 | 0.00 | 0.00 |
August | 941.37 | 510.18 | 431.19 | 1425.85 | 381.97 | 0.00 | 0.00 | 0.00 |
September | 805.99 | 431.27 | 374.72 | 1178.47 | 442.41 | 0.00 | 0.00 | 0.00 |
October | 616.14 | 336.39 | 279.75 | 921.68 | 495.25 | 0.00 | 0.00 | 0.00 |
November | 556.56 | 291.12 | 265.44 | 714.64 | 692.18 | 0.00 | 0.00 | 0.00 |
December | 491.54 | 263.64 | 227.90 | 630.24 | 754.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.36 | 378.23 | 363.13 | 1025.23 | 558.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 483.15 | 243.68 | 227.90 | 607.37 | 366.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1003.38 | 536.90 | 481.45 | 1498.33 | 754.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.10 | 9.63 | 9.47 | 24.01 | 29.58 | 0.00 | 0.00 | 0.00 |
February | 22.79 | 10.52 | 12.27 | 27.50 | 26.46 | 0.00 | 0.00 | 0.00 |
March | 26.12 | 11.56 | 14.57 | 32.08 | 26.83 | 0.00 | 0.00 | 0.00 |
April | 36.01 | 18.75 | 17.26 | 49.76 | 22.34 | 0.00 | 0.00 | 0.00 |
May | 35.38 | 16.34 | 19.04 | 47.32 | 20.36 | 0.00 | 0.00 | 0.00 |
June | 37.48 | 18.74 | 18.74 | 53.18 | 15.86 | 0.00 | 0.00 | 0.00 |
July | 39.67 | 21.23 | 18.44 | 59.24 | 14.51 | 0.00 | 0.00 | 0.00 |
August | 37.22 | 20.17 | 17.05 | 56.38 | 15.10 | 0.00 | 0.00 | 0.00 |
September | 31.87 | 17.05 | 14.82 | 46.60 | 17.49 | 0.00 | 0.00 | 0.00 |
October | 24.36 | 13.30 | 11.06 | 36.44 | 19.58 | 0.00 | 0.00 | 0.00 |
November | 22.01 | 11.51 | 10.50 | 28.26 | 27.37 | 0.00 | 0.00 | 0.00 |
December | 19.43 | 10.42 | 9.01 | 24.92 | 29.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.31 | 14.95 | 14.36 | 40.54 | 22.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.10 | 9.63 | 9.01 | 24.01 | 14.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.67 | 21.23 | 19.04 | 59.24 | 29.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 293.44 | 0.00 | 293.44 | 171.52 | 1168.26 | 0.00 | 0.00 | 0.00 |
February | 368.34 | 0.00 | 368.34 | 205.87 | 1062.43 | 0.00 | 0.00 | 0.00 |
March | 451.37 | 0.00 | 451.37 | 305.86 | 1082.12 | 0.00 | 0.00 | 0.00 |
April | 520.04 | 2.00 | 518.04 | 431.97 | 857.86 | 0.00 | 0.00 | 0.00 |
May | 624.92 | 29.10 | 595.82 | 549.34 | 749.74 | 0.00 | 0.00 | 0.00 |
June | 665.88 | 65.10 | 600.78 | 709.22 | 587.69 | 0.00 | 0.00 | 0.00 |
July | 630.49 | 52.85 | 577.64 | 748.41 | 525.86 | 0.00 | 0.00 | 0.00 |
August | 523.60 | 10.48 | 513.11 | 599.39 | 554.69 | 0.00 | 0.00 | 0.00 |
September | 443.17 | 0.07 | 443.10 | 462.90 | 669.76 | 0.00 | 0.00 | 0.00 |
October | 351.54 | 0.00 | 351.54 | 400.69 | 753.27 | 0.00 | 0.00 | 0.00 |
November | 318.29 | 0.00 | 318.29 | 197.35 | 1076.72 | 0.00 | 0.00 | 0.00 |
December | 273.17 | 0.00 | 273.17 | 153.23 | 1181.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.72 | 13.37 | 442.35 | 412.58 | 854.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 273.17 | 0.00 | 273.17 | 153.23 | 525.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.88 | 65.10 | 600.78 | 748.41 | 1181.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 527.68 | 282.22 | 245.47 | 622.70 | 729.36 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 255.01 | 301.65 | 615.13 | 668.73 | 0.00 | 0.00 | 0.00 |
March | 676.17 | 301.26 | 374.91 | 783.71 | 680.55 | 0.00 | 0.00 | 0.00 |
April | 864.48 | 433.55 | 430.92 | 1146.79 | 554.82 | 0.00 | 0.00 | 0.00 |
May | 815.82 | 340.46 | 475.36 | 1036.56 | 507.83 | 0.00 | 0.00 | 0.00 |
June | 810.74 | 351.77 | 458.97 | 1107.66 | 404.64 | 0.00 | 0.00 | 0.00 |
July | 918.63 | 456.49 | 462.14 | 1355.90 | 363.67 | 0.00 | 0.00 | 0.00 |
August | 907.22 | 481.88 | 425.34 | 1357.36 | 371.99 | 0.00 | 0.00 | 0.00 |
September | 660.53 | 302.68 | 357.85 | 931.50 | 433.23 | 0.00 | 0.00 | 0.00 |
October | 584.69 | 300.51 | 284.17 | 840.61 | 479.39 | 0.00 | 0.00 | 0.00 |
November | 533.01 | 270.79 | 262.22 | 627.35 | 676.17 | 0.00 | 0.00 | 0.00 |
December | 508.48 | 282.52 | 225.96 | 599.17 | 734.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.94 | 338.93 | 359.01 | 920.82 | 549.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.48 | 255.01 | 225.96 | 599.17 | 363.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 918.63 | 481.88 | 475.36 | 1357.36 | 734.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1936.48 | 1420.50 | 515.98 | 2806.52 | 1125.71 | 0.00 | 0.00 | 0.00 |
February | 1521.97 | 937.46 | 584.52 | 2067.45 | 1034.05 | 0.00 | 0.00 | 0.00 |
March | 1213.37 | 586.11 | 627.25 | 1621.33 | 1079.98 | 0.00 | 0.00 | 0.00 |
April | 1013.80 | 386.57 | 627.23 | 1451.32 | 897.88 | 0.00 | 0.00 | 0.00 |
May | 721.90 | 88.84 | 633.06 | 827.02 | 818.73 | 0.00 | 0.00 | 0.00 |
June | 633.30 | 38.24 | 595.06 | 730.22 | 637.87 | 0.00 | 0.00 | 0.00 |
July | 670.84 | 75.52 | 595.32 | 910.67 | 564.36 | 0.00 | 0.00 | 0.00 |
August | 861.83 | 271.85 | 589.98 | 1357.03 | 590.81 | 0.00 | 0.00 | 0.00 |
September | 1199.23 | 607.69 | 591.54 | 1892.06 | 690.05 | 0.00 | 0.00 | 0.00 |
October | 1525.14 | 1019.60 | 505.54 | 2412.50 | 752.05 | 0.00 | 0.00 | 0.00 |
November | 1853.66 | 1308.65 | 545.00 | 2675.46 | 1039.58 | 0.00 | 0.00 | 0.00 |
December | 2068.78 | 1574.62 | 494.17 | 3014.39 | 1130.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1267.30 | 692.14 | 575.16 | 1813.13 | 862.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 633.30 | 38.24 | 494.17 | 730.22 | 564.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.78 | 1574.62 | 633.06 | 3014.39 | 1130.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.26 | 253.32 | 248.94 | 624.44 | 769.23 | 0.00 | 0.00 | 0.00 |
February | 599.20 | 276.62 | 322.58 | 709.13 | 699.31 | 0.00 | 0.00 | 0.00 |
March | 686.85 | 303.87 | 382.97 | 826.34 | 710.69 | 0.00 | 0.00 | 0.00 |
April | 946.86 | 493.03 | 453.83 | 1291.32 | 587.38 | 0.00 | 0.00 | 0.00 |
May | 930.11 | 429.62 | 500.49 | 1226.66 | 534.60 | 0.00 | 0.00 | 0.00 |
June | 985.35 | 492.66 | 492.69 | 1379.21 | 419.86 | 0.00 | 0.00 | 0.00 |
July | 1043.07 | 558.14 | 484.93 | 1544.82 | 377.81 | 0.00 | 0.00 | 0.00 |
August | 978.60 | 530.36 | 448.24 | 1470.06 | 393.29 | 0.00 | 0.00 | 0.00 |
September | 837.87 | 448.33 | 389.54 | 1215.06 | 452.16 | 0.00 | 0.00 | 0.00 |
October | 640.51 | 349.69 | 290.82 | 951.61 | 505.83 | 0.00 | 0.00 | 0.00 |
November | 578.57 | 302.63 | 275.94 | 737.08 | 706.22 | 0.00 | 0.00 | 0.00 |
December | 510.98 | 274.07 | 236.91 | 648.74 | 775.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 770.69 | 393.19 | 377.49 | 1053.72 | 577.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 502.26 | 253.32 | 236.91 | 624.44 | 377.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1043.07 | 558.14 | 500.49 | 1544.82 | 775.78 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.512376E+09 | 0.288477E+10 |
February | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.546247E+09 | 0.236692E+10 |
March | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.867974E+09 | 0.270212E+10 |
April | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.114523E+10 | 0.209220E+10 |
May | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.150585E+10 | 0.190050E+10 |
June | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.184848E+10 | 0.145162E+10 |
July | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.200378E+10 | 0.134570E+10 |
August | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.160862E+10 | 0.141363E+10 |
September | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.121566E+10 | 0.163325E+10 |
October | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.109968E+10 | 0.188596E+10 |
November | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.561872E+09 | 0.257582E+10 |
December | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.465206E+09 | 0.290811E+10 |
Annual Sum or Average | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.133810E+11 | 0.251606E+11 |
Minimum of Months | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.465206E+09 | 0.134570E+10 |
Maximum of Months | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.200378E+10 | 0.290811E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.171460E+10 | 0.181955E+10 |
February | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.152398E+10 | 0.150511E+10 |
March | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.213378E+10 | 0.171547E+10 |
April | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.298646E+10 | 0.136624E+10 |
May | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.279346E+10 | 0.129660E+10 |
June | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.287498E+10 | 0.100549E+10 |
July | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.362635E+10 | 0.936056E+09 |
August | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.363194E+10 | 0.954702E+09 |
September | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.242200E+10 | 0.106353E+10 |
October | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.226833E+10 | 0.121140E+10 |
November | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.166651E+10 | 0.163631E+10 |
December | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.165449E+10 | 0.182884E+10 |
Annual Sum or Average | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.292969E+11 | 0.163393E+11 |
Minimum of Months | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.152398E+10 | 0.936056E+09 |
Maximum of Months | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.363194E+10 | 0.182884E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.756988E+10 | 0.281321E+10 |
February | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.504508E+10 | 0.232331E+10 |
March | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.438561E+10 | 0.270753E+10 |
April | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.377855E+10 | 0.219762E+10 |
May | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.223714E+10 | 0.207154E+10 |
June | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.190086E+10 | 0.157271E+10 |
July | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.243704E+10 | 0.144317E+10 |
August | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.363049E+10 | 0.150694E+10 |
September | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.490928E+10 | 0.168994E+10 |
October | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.647843E+10 | 0.189975E+10 |
November | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.697824E+10 | 0.251989E+10 |
December | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.812842E+10 | 0.282555E+10 |
Annual Sum or Average | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.574790E+11 | 0.255712E+11 |
Minimum of Months | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.190086E+10 | 0.144317E+10 |
Maximum of Months | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.812842E+10 | 0.282555E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.170489E+10 | 0.190653E+10 |
February | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.174469E+10 | 0.156407E+10 |
March | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.224160E+10 | 0.177722E+10 |
April | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.335890E+10 | 0.143607E+10 |
May | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.329815E+10 | 0.135327E+10 |
June | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.357505E+10 | 0.103516E+10 |
July | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.413095E+10 | 0.965710E+09 |
August | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.393252E+10 | 0.100245E+10 |
September | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.315556E+10 | 0.110436E+10 |
October | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.256336E+10 | 0.126985E+10 |
November | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.194004E+10 | 0.169497E+10 |
December | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.177144E+10 | 0.191892E+10 |
Annual Sum or Average | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.334171E+11 | 0.170286E+11 |
Minimum of Months | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.170489E+10 | 0.965710E+09 |
Maximum of Months | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.413095E+10 | 0.191892E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261968E+09 | 0.00 | 0.261968E+09 | 0.162190E+09 | 0.102692E+10 |
February | 0.297017E+09 | 0.00 | 0.297017E+09 | 0.182964E+09 | 0.825245E+09 |
March | 0.402968E+09 | 0.00 | 0.402968E+09 | 0.297647E+09 | 0.928998E+09 |
April | 0.449291E+09 | 1729250.28 | 0.447561E+09 | 0.398608E+09 | 0.708302E+09 |
May | 0.557900E+09 | 25978888.28 | 0.531922E+09 | 0.518135E+09 | 0.646066E+09 |
June | 0.575295E+09 | 56244704.55 | 0.519050E+09 | 0.640569E+09 | 0.485935E+09 |
July | 0.562871E+09 | 47177856.02 | 0.515693E+09 | 0.688598E+09 | 0.454070E+09 |
August | 0.467445E+09 | 9360129.55 | 0.458085E+09 | 0.552450E+09 | 0.476967E+09 |
September | 0.382882E+09 | 60012.51 | 0.382822E+09 | 0.413092E+09 | 0.562837E+09 |
October | 0.313838E+09 | 0.00 | 0.313838E+09 | 0.366412E+09 | 0.661759E+09 |
November | 0.274992E+09 | 0.00 | 0.274992E+09 | 0.178980E+09 | 0.918829E+09 |
December | 0.243870E+09 | 0.00 | 0.243870E+09 | 0.145768E+09 | 0.103615E+10 |
Annual Sum or Average | 0.479034E+10 | 0.140551E+09 | 0.464979E+10 | 0.454541E+10 | 0.873208E+10 |
Minimum of Months | 0.243870E+09 | 0.00 | 0.243870E+09 | 0.145768E+09 | 0.454070E+09 |
Maximum of Months | 0.575295E+09 | 56244704.55 | 0.531922E+09 | 0.688598E+09 | 0.103615E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261979E+09 | 0.00 | 0.261979E+09 | 0.162196E+09 | 0.102698E+10 |
February | 0.297029E+09 | 0.00 | 0.297029E+09 | 0.182969E+09 | 0.825295E+09 |
March | 0.402984E+09 | 0.00 | 0.402984E+09 | 0.297655E+09 | 0.929054E+09 |
April | 0.449310E+09 | 1729296.77 | 0.447581E+09 | 0.398624E+09 | 0.708344E+09 |
May | 0.557923E+09 | 25979586.60 | 0.531944E+09 | 0.518151E+09 | 0.646104E+09 |
June | 0.575318E+09 | 56246216.43 | 0.519072E+09 | 0.640591E+09 | 0.485964E+09 |
July | 0.562895E+09 | 47179124.17 | 0.515716E+09 | 0.688626E+09 | 0.454096E+09 |
August | 0.467466E+09 | 9360381.16 | 0.458106E+09 | 0.552475E+09 | 0.476995E+09 |
September | 0.382898E+09 | 60014.12 | 0.382838E+09 | 0.413110E+09 | 0.562869E+09 |
October | 0.313851E+09 | 0.00 | 0.313851E+09 | 0.366428E+09 | 0.661796E+09 |
November | 0.275003E+09 | 0.00 | 0.275003E+09 | 0.178985E+09 | 0.918883E+09 |
December | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.145773E+09 | 0.103621E+10 |
Annual Sum or Average | 0.479054E+10 | 0.140555E+09 | 0.464998E+10 | 0.454558E+10 | 0.873259E+10 |
Minimum of Months | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.145773E+09 | 0.454096E+09 |
Maximum of Months | 0.575318E+09 | 56246216.43 | 0.531944E+09 | 0.688626E+09 | 0.103621E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261979E+09 | 0.00 | 0.261979E+09 | 0.162196E+09 | 0.102698E+10 |
February | 0.297029E+09 | 0.00 | 0.297029E+09 | 0.182969E+09 | 0.825295E+09 |
March | 0.402984E+09 | 0.00 | 0.402984E+09 | 0.297655E+09 | 0.929054E+09 |
April | 0.449310E+09 | 1729296.77 | 0.447581E+09 | 0.398624E+09 | 0.708344E+09 |
May | 0.557923E+09 | 25979586.60 | 0.531944E+09 | 0.518151E+09 | 0.646104E+09 |
June | 0.575318E+09 | 56246216.43 | 0.519072E+09 | 0.640591E+09 | 0.485964E+09 |
July | 0.562895E+09 | 47179124.17 | 0.515716E+09 | 0.688626E+09 | 0.454096E+09 |
August | 0.467466E+09 | 9360381.16 | 0.458106E+09 | 0.552475E+09 | 0.476995E+09 |
September | 0.382898E+09 | 60014.12 | 0.382838E+09 | 0.413110E+09 | 0.562869E+09 |
October | 0.313851E+09 | 0.00 | 0.313851E+09 | 0.366428E+09 | 0.661796E+09 |
November | 0.275003E+09 | 0.00 | 0.275003E+09 | 0.178985E+09 | 0.918883E+09 |
December | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.145773E+09 | 0.103621E+10 |
Annual Sum or Average | 0.479054E+10 | 0.140555E+09 | 0.464998E+10 | 0.454558E+10 | 0.873259E+10 |
Minimum of Months | 0.243881E+09 | 0.00 | 0.243881E+09 | 0.145773E+09 | 0.454096E+09 |
Maximum of Months | 0.575318E+09 | 56246216.43 | 0.531944E+09 | 0.688626E+09 | 0.103621E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135957E+10 | 0.727129E+09 | 0.632444E+09 | 0.161500E+10 | 0.191153E+10 |
February | 0.129541E+10 | 0.593438E+09 | 0.701977E+09 | 0.145913E+10 | 0.154849E+10 |
March | 0.174214E+10 | 0.776202E+09 | 0.965943E+09 | 0.205645E+10 | 0.174186E+10 |
April | 0.215546E+10 | 0.108100E+10 | 0.107446E+10 | 0.289677E+10 | 0.138103E+10 |
May | 0.210195E+10 | 0.877188E+09 | 0.122476E+10 | 0.271100E+10 | 0.130332E+10 |
June | 0.202148E+10 | 0.877078E+09 | 0.114440E+10 | 0.280336E+10 | 0.993840E+09 |
July | 0.236684E+10 | 0.117614E+10 | 0.119070E+10 | 0.352198E+10 | 0.943500E+09 |
August | 0.233744E+10 | 0.124157E+10 | 0.109588E+10 | 0.352349E+10 | 0.967063E+09 |
September | 0.164695E+10 | 0.754689E+09 | 0.892256E+09 | 0.234239E+10 | 0.108858E+10 |
October | 0.150644E+10 | 0.774269E+09 | 0.732173E+09 | 0.218090E+10 | 0.125502E+10 |
November | 0.132900E+10 | 0.675184E+09 | 0.653815E+09 | 0.157550E+10 | 0.171550E+10 |
December | 0.131010E+10 | 0.727903E+09 | 0.582198E+09 | 0.155558E+10 | 0.191895E+10 |
Annual Sum or Average | 0.211728E+11 | 0.102818E+11 | 0.108910E+11 | 0.282416E+11 | 0.167687E+11 |
Minimum of Months | 0.129541E+10 | 0.593438E+09 | 0.582198E+09 | 0.145913E+10 | 0.943500E+09 |
Maximum of Months | 0.236684E+10 | 0.124157E+10 | 0.122476E+10 | 0.352349E+10 | 0.191895E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53756276.65 | 28750020.07 | 25006256.58 | 63855632.72 | 75580146.61 |
February | 51219536.05 | 23463985.50 | 27755550.55 | 57692807.34 | 61225821.60 |
March | 68882820.91 | 30690319.97 | 38192500.94 | 81310040.29 | 68871611.61 |
April | 85225060.99 | 42741889.79 | 42483171.20 | 0.114536E+09 | 54604793.73 |
May | 83109119.40 | 34683214.02 | 48425905.38 | 0.107190E+09 | 51532176.86 |
June | 79927343.63 | 34678888.28 | 45248455.35 | 0.110842E+09 | 39295534.59 |
July | 93582551.13 | 46503441.19 | 47079109.94 | 0.139256E+09 | 37305152.12 |
August | 92420346.18 | 49090365.00 | 43329981.18 | 0.139315E+09 | 38236790.93 |
September | 65118747.34 | 29839732.21 | 35279015.14 | 92616071.12 | 43041589.27 |
October | 59563348.69 | 30613901.41 | 28949447.28 | 86230940.14 | 49622384.81 |
November | 52547403.78 | 26696152.82 | 25851250.96 | 62294026.37 | 67829179.75 |
December | 51800200.31 | 28780626.60 | 23019573.71 | 61506177.23 | 75873393.28 |
Annual Sum or Average | 0.837153E+09 | 0.406533E+09 | 0.430620E+09 | 0.111665E+10 | 0.663019E+09 |
Minimum of Months | 51219536.05 | 23463985.50 | 23019573.71 | 57692807.34 | 37305152.12 |
Maximum of Months | 93582551.13 | 49090365.00 | 48425905.38 | 0.139315E+09 | 75873393.28 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172886E+10 | 0.126820E+10 | 0.460665E+09 | 0.251993E+10 | 0.104133E+10 |
February | 0.122730E+10 | 0.755948E+09 | 0.471349E+09 | 0.169344E+10 | 0.836508E+09 |
March | 0.108328E+10 | 0.523271E+09 | 0.560006E+09 | 0.148306E+10 | 0.943473E+09 |
April | 0.875911E+09 | 0.333991E+09 | 0.541921E+09 | 0.128251E+10 | 0.753418E+09 |
May | 0.644509E+09 | 79314692.39 | 0.565194E+09 | 0.775487E+09 | 0.695990E+09 |
June | 0.547168E+09 | 33035549.07 | 0.514132E+09 | 0.666199E+09 | 0.516373E+09 |
July | 0.598921E+09 | 67420449.29 | 0.531501E+09 | 0.836742E+09 | 0.483978E+09 |
August | 0.769431E+09 | 0.242700E+09 | 0.526731E+09 | 0.123172E+10 | 0.515639E+09 |
September | 0.103612E+10 | 0.525035E+09 | 0.511086E+09 | 0.165101E+10 | 0.599816E+09 |
October | 0.136162E+10 | 0.910281E+09 | 0.451344E+09 | 0.216622E+10 | 0.692282E+09 |
November | 0.160153E+10 | 0.113065E+10 | 0.470877E+09 | 0.232809E+10 | 0.928555E+09 |
December | 0.184698E+10 | 0.140579E+10 | 0.441190E+09 | 0.270718E+10 | 0.104671E+10 |
Annual Sum or Average | 0.133216E+11 | 0.727563E+10 | 0.604600E+10 | 0.193416E+11 | 0.905408E+10 |
Minimum of Months | 0.547168E+09 | 33035549.07 | 0.441190E+09 | 0.666199E+09 | 0.483978E+09 |
Maximum of Months | 0.184698E+10 | 0.140579E+10 | 0.565194E+09 | 0.270718E+10 | 0.104671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172886E+10 | 0.126820E+10 | 0.460665E+09 | 0.251993E+10 | 0.104133E+10 |
February | 0.122730E+10 | 0.755948E+09 | 0.471349E+09 | 0.169344E+10 | 0.836508E+09 |
March | 0.108328E+10 | 0.523271E+09 | 0.560006E+09 | 0.148306E+10 | 0.943473E+09 |
April | 0.875911E+09 | 0.333991E+09 | 0.541921E+09 | 0.128251E+10 | 0.753418E+09 |
May | 0.644509E+09 | 79314692.39 | 0.565194E+09 | 0.775487E+09 | 0.695990E+09 |
June | 0.547168E+09 | 33035549.07 | 0.514132E+09 | 0.666199E+09 | 0.516373E+09 |
July | 0.598921E+09 | 67420449.29 | 0.531501E+09 | 0.836742E+09 | 0.483978E+09 |
August | 0.769431E+09 | 0.242700E+09 | 0.526731E+09 | 0.123172E+10 | 0.515639E+09 |
September | 0.103612E+10 | 0.525035E+09 | 0.511086E+09 | 0.165101E+10 | 0.599816E+09 |
October | 0.136162E+10 | 0.910281E+09 | 0.451344E+09 | 0.216622E+10 | 0.692282E+09 |
November | 0.160153E+10 | 0.113065E+10 | 0.470877E+09 | 0.232809E+10 | 0.928555E+09 |
December | 0.184698E+10 | 0.140579E+10 | 0.441190E+09 | 0.270718E+10 | 0.104671E+10 |
Annual Sum or Average | 0.133216E+11 | 0.727563E+10 | 0.604600E+10 | 0.193416E+11 | 0.905408E+10 |
Minimum of Months | 0.547168E+09 | 33035549.07 | 0.441190E+09 | 0.666199E+09 | 0.483978E+09 |
Maximum of Months | 0.184698E+10 | 0.140579E+10 | 0.565194E+09 | 0.270718E+10 | 0.104671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172875E+10 | 0.126812E+10 | 0.460636E+09 | 0.251977E+10 | 0.104126E+10 |
February | 0.122722E+10 | 0.755901E+09 | 0.471320E+09 | 0.169333E+10 | 0.836455E+09 |
March | 0.108321E+10 | 0.523238E+09 | 0.559970E+09 | 0.148297E+10 | 0.943413E+09 |
April | 0.875856E+09 | 0.333969E+09 | 0.541886E+09 | 0.128243E+10 | 0.753370E+09 |
May | 0.644468E+09 | 79309680.15 | 0.565158E+09 | 0.775438E+09 | 0.695947E+09 |
June | 0.547133E+09 | 33033461.41 | 0.514100E+09 | 0.666157E+09 | 0.516340E+09 |
July | 0.598884E+09 | 67416188.70 | 0.531467E+09 | 0.836689E+09 | 0.483948E+09 |
August | 0.769383E+09 | 0.242685E+09 | 0.526698E+09 | 0.123164E+10 | 0.515607E+09 |
September | 0.103606E+10 | 0.525002E+09 | 0.511054E+09 | 0.165090E+10 | 0.599778E+09 |
October | 0.136154E+10 | 0.910223E+09 | 0.451315E+09 | 0.216609E+10 | 0.692239E+09 |
November | 0.160143E+10 | 0.113058E+10 | 0.470847E+09 | 0.232795E+10 | 0.928496E+09 |
December | 0.184686E+10 | 0.140570E+10 | 0.441162E+09 | 0.270701E+10 | 0.104665E+10 |
Annual Sum or Average | 0.133208E+11 | 0.727517E+10 | 0.604561E+10 | 0.193404E+11 | 0.905350E+10 |
Minimum of Months | 0.547133E+09 | 33033461.41 | 0.441162E+09 | 0.666157E+09 | 0.483948E+09 |
Maximum of Months | 0.184686E+10 | 0.140570E+10 | 0.565158E+09 | 0.270701E+10 | 0.104665E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129408E+10 | 0.652673E+09 | 0.641406E+09 | 0.162679E+10 | 0.200394E+10 |
February | 0.139444E+10 | 0.643735E+09 | 0.750702E+09 | 0.168260E+10 | 0.161922E+10 |
March | 0.176966E+10 | 0.782921E+09 | 0.986734E+09 | 0.217286E+10 | 0.181745E+10 |
April | 0.236087E+10 | 0.122930E+10 | 0.113157E+10 | 0.326230E+10 | 0.146467E+10 |
May | 0.239642E+10 | 0.110690E+10 | 0.128952E+10 | 0.320519E+10 | 0.137931E+10 |
June | 0.245685E+10 | 0.122837E+10 | 0.122848E+10 | 0.348608E+10 | 0.103992E+10 |
July | 0.268747E+10 | 0.143803E+10 | 0.124943E+10 | 0.401314E+10 | 0.982860E+09 |
August | 0.252137E+10 | 0.136647E+10 | 0.115490E+10 | 0.381899E+10 | 0.102307E+10 |
September | 0.208912E+10 | 0.111785E+10 | 0.971265E+09 | 0.305459E+10 | 0.114673E+10 |
October | 0.165027E+10 | 0.900974E+09 | 0.749296E+09 | 0.246864E+10 | 0.132647E+10 |
November | 0.144260E+10 | 0.754579E+09 | 0.688021E+09 | 0.185235E+10 | 0.179412E+10 |
December | 0.131653E+10 | 0.706125E+09 | 0.610409E+09 | 0.168804E+10 | 0.202146E+10 |
Annual Sum or Average | 0.233797E+11 | 0.119279E+11 | 0.114517E+11 | 0.323316E+11 | 0.176192E+11 |
Minimum of Months | 0.129408E+10 | 0.643735E+09 | 0.610409E+09 | 0.162679E+10 | 0.982860E+09 |
Maximum of Months | 0.268747E+10 | 0.143803E+10 | 0.128952E+10 | 0.401314E+10 | 0.202146E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51166564.13 | 25806011.66 | 25360552.48 | 64321469.11 | 79234083.98 |
February | 55134634.38 | 25452631.40 | 29682002.98 | 66528334.45 | 64022576.56 |
March | 69970390.27 | 30955887.14 | 39014503.12 | 85912451.96 | 71860401.65 |
April | 93346509.46 | 48605183.06 | 44741326.40 | 0.128988E+09 | 57911624.04 |
May | 94752110.83 | 43765657.45 | 50986453.38 | 0.126730E+09 | 54536573.44 |
June | 97141393.60 | 48568644.04 | 48572749.57 | 0.137836E+09 | 41117677.30 |
July | 0.106260E+09 | 56858395.59 | 49401293.77 | 0.158675E+09 | 38861394.16 |
August | 99692334.42 | 54028886.99 | 45663447.43 | 0.150999E+09 | 40451217.34 |
September | 82601628.21 | 44198754.81 | 38402873.41 | 0.120775E+09 | 45340553.90 |
October | 65249983.87 | 35623575.88 | 29626408.00 | 97607434.12 | 52447349.16 |
November | 57038942.33 | 29835268.09 | 27203674.24 | 73240098.61 | 70937878.54 |
December | 52054398.58 | 27919442.74 | 24134955.84 | 66743162.30 | 79926518.34 |
Annual Sum or Average | 0.924409E+09 | 0.471618E+09 | 0.452790E+09 | 0.127836E+10 | 0.696648E+09 |
Minimum of Months | 51166564.13 | 25452631.40 | 24134955.84 | 64321469.11 | 38861394.16 |
Maximum of Months | 0.106260E+09 | 56858395.59 | 50986453.38 | 0.158675E+09 | 79926518.34 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.459409E+09 | 0.312907E+10 |
February | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.498049E+09 | 0.257022E+10 |
March | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.819228E+09 | 0.289836E+10 |
April | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.111968E+10 | 0.222356E+10 |
May | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.147135E+10 | 0.200811E+10 |
June | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.183831E+10 | 0.152330E+10 |
July | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.200454E+10 | 0.140845E+10 |
August | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.160541E+10 | 0.148569E+10 |
September | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.119983E+10 | 0.173602E+10 |
October | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.107321E+10 | 0.201755E+10 |
November | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.511535E+09 | 0.279087E+10 |
December | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.410419E+09 | 0.316397E+10 |
Annual Sum or Average | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.130110E+11 | 0.269552E+11 |
Minimum of Months | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.410419E+09 | 0.140845E+10 |
Maximum of Months | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.200454E+10 | 0.316397E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.166784E+10 | 0.195352E+10 |
February | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.148813E+10 | 0.161780E+10 |
March | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.209910E+10 | 0.182280E+10 |
April | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.297249E+10 | 0.143810E+10 |
May | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.277631E+10 | 0.136018E+10 |
June | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.287106E+10 | 0.104881E+10 |
July | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.363165E+10 | 0.974065E+09 |
August | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.363555E+10 | 0.996333E+09 |
September | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.241445E+10 | 0.112292E+10 |
October | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.225149E+10 | 0.128400E+10 |
November | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.162608E+10 | 0.175262E+10 |
December | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.160482E+10 | 0.196689E+10 |
Annual Sum or Average | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.290390E+11 | 0.173380E+11 |
Minimum of Months | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.148813E+10 | 0.974065E+09 |
Maximum of Months | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.363555E+10 | 0.196689E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.751698E+10 | 0.301511E+10 |
February | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.500157E+10 | 0.250156E+10 |
March | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.434258E+10 | 0.289262E+10 |
April | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.376183E+10 | 0.232730E+10 |
May | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.221508E+10 | 0.219289E+10 |
June | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.189272E+10 | 0.165336E+10 |
July | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.243914E+10 | 0.151158E+10 |
August | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.363468E+10 | 0.158243E+10 |
September | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.490421E+10 | 0.178861E+10 |
October | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.646164E+10 | 0.201430E+10 |
November | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.693479E+10 | 0.269460E+10 |
December | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.807374E+10 | 0.302752E+10 |
Annual Sum or Average | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.571790E+11 | 0.272019E+11 |
Minimum of Months | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.189272E+10 | 0.151158E+10 |
Maximum of Months | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.807374E+10 | 0.302752E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.167251E+10 | 0.206031E+10 |
February | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.171554E+10 | 0.169177E+10 |
March | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.221327E+10 | 0.190352E+10 |
April | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.334709E+10 | 0.152249E+10 |
May | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.328548E+10 | 0.143188E+10 |
June | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.357490E+10 | 0.108829E+10 |
July | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.413764E+10 | 0.101192E+10 |
August | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.393741E+10 | 0.105338E+10 |
September | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.314943E+10 | 0.117200E+10 |
October | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.254878E+10 | 0.135481E+10 |
November | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.191051E+10 | 0.183052E+10 |
December | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.173759E+10 | 0.207785E+10 |
Annual Sum or Average | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.332302E+11 | 0.181988E+11 |
Minimum of Months | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.167251E+10 | 0.101192E+10 |
Maximum of Months | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.413764E+10 | 0.207785E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 191.30 | 1077.05 | 293.44 | 0.00 | 293.44 | 0.00 | 0.00 |
February | 225.80 | 978.39 | 368.34 | 0.00 | 368.34 | 0.00 | 0.00 |
March | 324.06 | 1008.86 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 441.83 | 807.18 | 520.04 | 2.00 | 518.04 | 0.00 | 0.00 |
May | 562.22 | 709.57 | 624.92 | 29.10 | 595.82 | 0.00 | 0.00 |
June | 713.15 | 560.04 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
July | 748.13 | 502.43 | 630.49 | 52.85 | 577.64 | 0.00 | 0.00 |
August | 600.59 | 527.79 | 523.60 | 10.48 | 513.11 | 0.00 | 0.00 |
September | 469.00 | 630.11 | 443.17 | 0.07 | 443.10 | 0.00 | 0.00 |
October | 410.57 | 704.14 | 351.54 | 0.00 | 351.54 | 0.00 | 0.00 |
November | 216.77 | 993.76 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 173.69 | 1085.76 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Annual Sum or Average | 424.31 | 797.84 | 455.72 | 13.37 | 442.35 | 0.00 | 0.00 |
Minimum of Months | 173.69 | 502.43 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Maximum of Months | 748.13 | 1085.76 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 640.16 | 679.34 | 527.68 | 282.22 | 245.47 | 0.00 | 0.00 |
February | 629.95 | 622.15 | 556.65 | 255.01 | 301.65 | 0.00 | 0.00 |
March | 796.66 | 640.48 | 676.17 | 301.26 | 374.91 | 0.00 | 0.00 |
April | 1152.18 | 527.10 | 864.48 | 433.55 | 430.92 | 0.00 | 0.00 |
May | 1042.96 | 484.10 | 815.82 | 340.46 | 475.36 | 0.00 | 0.00 |
June | 1109.17 | 387.92 | 810.74 | 351.77 | 458.97 | 0.00 | 0.00 |
July | 1353.92 | 349.48 | 918.63 | 456.49 | 462.14 | 0.00 | 0.00 |
August | 1356.01 | 356.45 | 907.22 | 481.88 | 425.34 | 0.00 | 0.00 |
September | 934.41 | 410.31 | 660.53 | 302.68 | 357.85 | 0.00 | 0.00 |
October | 846.90 | 452.28 | 584.69 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 642.94 | 631.29 | 533.01 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 617.71 | 682.81 | 508.48 | 282.52 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 929.00 | 518.12 | 697.94 | 338.93 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 617.71 | 349.48 | 508.48 | 255.01 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1356.01 | 682.81 | 918.63 | 481.88 | 475.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2826.27 | 1050.33 | 1936.48 | 1420.50 | 515.98 | 0.00 | 0.00 |
February | 2085.43 | 960.36 | 1521.97 | 937.46 | 584.52 | 0.00 | 0.00 |
March | 1637.40 | 1010.88 | 1213.37 | 586.11 | 627.25 | 0.00 | 0.00 |
April | 1457.77 | 847.85 | 1013.80 | 386.57 | 627.23 | 0.00 | 0.00 |
May | 835.25 | 773.42 | 721.90 | 88.84 | 633.06 | 0.00 | 0.00 |
June | 733.36 | 606.76 | 633.30 | 38.24 | 595.06 | 0.00 | 0.00 |
July | 909.89 | 538.82 | 670.84 | 75.52 | 595.32 | 0.00 | 0.00 |
August | 1355.47 | 562.63 | 861.83 | 271.85 | 589.98 | 0.00 | 0.00 |
September | 1894.01 | 651.98 | 1199.23 | 607.69 | 591.54 | 0.00 | 0.00 |
October | 2418.77 | 709.29 | 1525.14 | 1019.60 | 505.54 | 0.00 | 0.00 |
November | 2692.22 | 972.18 | 1853.66 | 1308.65 | 545.00 | 0.00 | 0.00 |
December | 3034.80 | 1054.94 | 2068.78 | 1574.62 | 494.17 | 0.00 | 0.00 |
Annual Sum or Average | 1822.65 | 810.86 | 1267.30 | 692.14 | 575.16 | 0.00 | 0.00 |
Minimum of Months | 733.36 | 538.82 | 633.30 | 38.24 | 494.17 | 0.00 | 0.00 |
Maximum of Months | 3034.80 | 1054.94 | 2068.78 | 1574.62 | 633.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 636.53 | 711.82 | 502.26 | 253.32 | 248.94 | 0.00 | 0.00 |
February | 721.19 | 646.52 | 599.20 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 836.92 | 663.54 | 686.85 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1295.87 | 554.04 | 946.86 | 493.03 | 453.83 | 0.00 | 0.00 |
May | 1231.39 | 505.25 | 930.11 | 429.62 | 500.49 | 0.00 | 0.00 |
June | 1379.26 | 399.37 | 985.35 | 492.66 | 492.69 | 0.00 | 0.00 |
July | 1542.32 | 360.55 | 1043.07 | 558.14 | 484.93 | 0.00 | 0.00 |
August | 1468.23 | 374.27 | 978.60 | 530.36 | 448.24 | 0.00 | 0.00 |
September | 1217.42 | 426.07 | 837.87 | 448.33 | 389.54 | 0.00 | 0.00 |
October | 957.05 | 474.11 | 640.51 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 748.47 | 653.92 | 578.57 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 661.38 | 716.44 | 510.98 | 274.07 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1059.65 | 539.97 | 770.69 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 636.53 | 360.55 | 502.26 | 253.32 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1542.32 | 716.44 | 1043.07 | 558.14 | 500.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.67 | 1150.27 | 293.43 | 0.00 | 293.43 | 0.00 | 0.00 |
February | 226.89 | 1023.41 | 368.33 | 0.00 | 368.33 | 0.00 | 0.00 |
March | 333.39 | 1040.59 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 461.36 | 819.83 | 520.03 | 2.00 | 518.03 | 0.00 | 0.00 |
May | 580.36 | 723.67 | 624.91 | 29.10 | 595.81 | 0.00 | 0.00 |
June | 741.42 | 562.45 | 665.87 | 65.10 | 600.77 | 0.00 | 0.00 |
July | 771.30 | 508.61 | 630.47 | 52.84 | 577.63 | 0.00 | 0.00 |
August | 618.80 | 534.26 | 523.59 | 10.48 | 513.10 | 0.00 | 0.00 |
September | 478.13 | 651.46 | 443.16 | 0.07 | 443.09 | 0.00 | 0.00 |
October | 410.42 | 741.25 | 351.53 | 0.00 | 351.53 | 0.00 | 0.00 |
November | 207.16 | 1063.50 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 163.27 | 1160.61 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
Annual Sum or Average | 432.41 | 830.71 | 455.71 | 13.37 | 442.34 | 0.00 | 0.00 |
Minimum of Months | 163.27 | 508.61 | 273.16 | 0.00 | 273.16 | 0.00 | 0.00 |
Maximum of Months | 771.30 | 1160.61 | 665.87 | 65.10 | 600.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 626.81 | 741.90 | 527.68 | 282.21 | 245.46 | 0.00 | 0.00 |
February | 626.99 | 665.39 | 556.64 | 255.00 | 301.64 | 0.00 | 0.00 |
March | 798.15 | 676.05 | 676.16 | 301.26 | 374.90 | 0.00 | 0.00 |
April | 1161.77 | 553.87 | 864.46 | 433.54 | 430.92 | 0.00 | 0.00 |
May | 1052.19 | 505.84 | 815.81 | 340.45 | 475.35 | 0.00 | 0.00 |
June | 1124.30 | 398.59 | 810.73 | 351.76 | 458.97 | 0.00 | 0.00 |
July | 1366.95 | 366.19 | 918.61 | 456.48 | 462.13 | 0.00 | 0.00 |
August | 1367.53 | 375.34 | 907.21 | 481.88 | 425.33 | 0.00 | 0.00 |
September | 939.43 | 436.58 | 660.52 | 302.67 | 357.85 | 0.00 | 0.00 |
October | 846.45 | 487.10 | 584.68 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 631.87 | 688.01 | 533.00 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 603.75 | 744.78 | 508.48 | 282.51 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 930.94 | 552.76 | 697.93 | 338.92 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 603.75 | 366.19 | 508.48 | 255.00 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1367.53 | 744.78 | 918.61 | 481.88 | 475.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2822.45 | 1166.34 | 1936.41 | 1420.44 | 515.97 | 0.00 | 0.00 |
February | 2099.95 | 1037.31 | 1521.91 | 937.42 | 584.50 | 0.00 | 0.00 |
March | 1661.10 | 1056.73 | 1213.32 | 586.09 | 627.23 | 0.00 | 0.00 |
April | 1484.35 | 871.99 | 1013.76 | 386.55 | 627.21 | 0.00 | 0.00 |
May | 868.58 | 779.54 | 721.88 | 88.84 | 633.04 | 0.00 | 0.00 |
June | 771.05 | 597.64 | 633.28 | 38.23 | 595.05 | 0.00 | 0.00 |
July | 937.19 | 542.08 | 670.82 | 75.51 | 595.31 | 0.00 | 0.00 |
August | 1379.58 | 577.54 | 861.80 | 271.84 | 589.96 | 0.00 | 0.00 |
September | 1910.85 | 694.22 | 1199.19 | 607.67 | 591.52 | 0.00 | 0.00 |
October | 2426.27 | 775.39 | 1525.08 | 1019.56 | 505.53 | 0.00 | 0.00 |
November | 2694.50 | 1074.69 | 1853.58 | 1308.60 | 544.99 | 0.00 | 0.00 |
December | 3032.18 | 1172.37 | 2068.70 | 1574.55 | 494.15 | 0.00 | 0.00 |
Annual Sum or Average | 1839.92 | 861.29 | 1267.25 | 692.11 | 575.14 | 0.00 | 0.00 |
Minimum of Months | 771.05 | 542.08 | 633.28 | 38.23 | 494.15 | 0.00 | 0.00 |
Maximum of Months | 3032.18 | 1172.37 | 2068.70 | 1574.55 | 633.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 631.39 | 777.77 | 502.26 | 253.31 | 248.94 | 0.00 | 0.00 |
February | 723.02 | 695.79 | 599.19 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 843.33 | 705.39 | 686.84 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1308.37 | 587.41 | 946.84 | 493.02 | 453.83 | 0.00 | 0.00 |
May | 1244.00 | 535.34 | 930.10 | 429.61 | 500.49 | 0.00 | 0.00 |
June | 1398.12 | 417.07 | 985.34 | 492.65 | 492.69 | 0.00 | 0.00 |
July | 1557.58 | 381.47 | 1043.06 | 558.13 | 484.93 | 0.00 | 0.00 |
August | 1482.22 | 397.07 | 978.59 | 530.35 | 448.24 | 0.00 | 0.00 |
September | 1225.06 | 459.90 | 837.85 | 448.32 | 389.53 | 0.00 | 0.00 |
October | 958.13 | 514.83 | 640.50 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 742.90 | 719.54 | 578.56 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 655.16 | 784.57 | 510.97 | 274.06 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1065.76 | 580.79 | 770.68 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 631.39 | 381.47 | 502.26 | 253.31 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1557.58 | 784.57 | 1043.06 | 558.13 | 500.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.52 | 1168.26 | 293.44 | 0.00 | 293.44 | 0.00 | 0.00 |
February | 205.87 | 1062.43 | 368.34 | 0.00 | 368.34 | 0.00 | 0.00 |
March | 305.86 | 1082.12 | 451.37 | 0.00 | 451.37 | 0.00 | 0.00 |
April | 431.97 | 857.86 | 520.04 | 2.00 | 518.04 | 0.00 | 0.00 |
May | 549.34 | 749.74 | 624.92 | 29.10 | 595.82 | 0.00 | 0.00 |
June | 709.22 | 587.69 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
July | 748.41 | 525.86 | 630.49 | 52.85 | 577.64 | 0.00 | 0.00 |
August | 599.39 | 554.69 | 523.60 | 10.48 | 513.11 | 0.00 | 0.00 |
September | 462.90 | 669.76 | 443.17 | 0.07 | 443.10 | 0.00 | 0.00 |
October | 400.69 | 753.27 | 351.54 | 0.00 | 351.54 | 0.00 | 0.00 |
November | 197.35 | 1076.72 | 318.29 | 0.00 | 318.29 | 0.00 | 0.00 |
December | 153.23 | 1181.29 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Annual Sum or Average | 412.58 | 854.74 | 455.72 | 13.37 | 442.35 | 0.00 | 0.00 |
Minimum of Months | 153.23 | 525.86 | 273.17 | 0.00 | 273.17 | 0.00 | 0.00 |
Maximum of Months | 748.41 | 1181.29 | 665.88 | 65.10 | 600.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 622.70 | 729.36 | 527.68 | 282.22 | 245.47 | 0.00 | 0.00 |
February | 615.13 | 668.73 | 556.65 | 255.01 | 301.65 | 0.00 | 0.00 |
March | 783.71 | 680.55 | 676.17 | 301.26 | 374.91 | 0.00 | 0.00 |
April | 1146.79 | 554.82 | 864.48 | 433.55 | 430.92 | 0.00 | 0.00 |
May | 1036.56 | 507.83 | 815.82 | 340.46 | 475.36 | 0.00 | 0.00 |
June | 1107.66 | 404.64 | 810.74 | 351.77 | 458.97 | 0.00 | 0.00 |
July | 1355.90 | 363.67 | 918.63 | 456.49 | 462.14 | 0.00 | 0.00 |
August | 1357.36 | 371.99 | 907.22 | 481.88 | 425.34 | 0.00 | 0.00 |
September | 931.50 | 433.23 | 660.53 | 302.68 | 357.85 | 0.00 | 0.00 |
October | 840.61 | 479.39 | 584.69 | 300.51 | 284.17 | 0.00 | 0.00 |
November | 627.35 | 676.17 | 533.01 | 270.79 | 262.22 | 0.00 | 0.00 |
December | 599.17 | 734.35 | 508.48 | 282.52 | 225.96 | 0.00 | 0.00 |
Annual Sum or Average | 920.82 | 549.79 | 697.94 | 338.93 | 359.01 | 0.00 | 0.00 |
Minimum of Months | 599.17 | 363.67 | 508.48 | 255.01 | 225.96 | 0.00 | 0.00 |
Maximum of Months | 1357.36 | 734.35 | 918.63 | 481.88 | 475.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2806.52 | 1125.71 | 1936.48 | 1420.50 | 515.98 | 0.00 | 0.00 |
February | 2067.45 | 1034.05 | 1521.97 | 937.46 | 584.52 | 0.00 | 0.00 |
March | 1621.33 | 1079.98 | 1213.37 | 586.11 | 627.25 | 0.00 | 0.00 |
April | 1451.32 | 897.88 | 1013.80 | 386.57 | 627.23 | 0.00 | 0.00 |
May | 827.02 | 818.73 | 721.90 | 88.84 | 633.06 | 0.00 | 0.00 |
June | 730.22 | 637.87 | 633.30 | 38.24 | 595.06 | 0.00 | 0.00 |
July | 910.67 | 564.36 | 670.84 | 75.52 | 595.32 | 0.00 | 0.00 |
August | 1357.03 | 590.81 | 861.83 | 271.85 | 589.98 | 0.00 | 0.00 |
September | 1892.06 | 690.05 | 1199.23 | 607.69 | 591.54 | 0.00 | 0.00 |
October | 2412.50 | 752.05 | 1525.14 | 1019.60 | 505.54 | 0.00 | 0.00 |
November | 2675.46 | 1039.58 | 1853.66 | 1308.65 | 545.00 | 0.00 | 0.00 |
December | 3014.39 | 1130.35 | 2068.78 | 1574.62 | 494.17 | 0.00 | 0.00 |
Annual Sum or Average | 1813.13 | 862.57 | 1267.30 | 692.14 | 575.16 | 0.00 | 0.00 |
Minimum of Months | 730.22 | 564.36 | 633.30 | 38.24 | 494.17 | 0.00 | 0.00 |
Maximum of Months | 3014.39 | 1130.35 | 2068.78 | 1574.62 | 633.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 624.44 | 769.23 | 502.26 | 253.32 | 248.94 | 0.00 | 0.00 |
February | 709.13 | 699.31 | 599.20 | 276.62 | 322.58 | 0.00 | 0.00 |
March | 826.34 | 710.69 | 686.85 | 303.87 | 382.97 | 0.00 | 0.00 |
April | 1291.32 | 587.38 | 946.86 | 493.03 | 453.83 | 0.00 | 0.00 |
May | 1226.66 | 534.60 | 930.11 | 429.62 | 500.49 | 0.00 | 0.00 |
June | 1379.21 | 419.86 | 985.35 | 492.66 | 492.69 | 0.00 | 0.00 |
July | 1544.82 | 377.81 | 1043.07 | 558.14 | 484.93 | 0.00 | 0.00 |
August | 1470.06 | 393.29 | 978.60 | 530.36 | 448.24 | 0.00 | 0.00 |
September | 1215.06 | 452.16 | 837.87 | 448.33 | 389.54 | 0.00 | 0.00 |
October | 951.61 | 505.83 | 640.51 | 349.69 | 290.82 | 0.00 | 0.00 |
November | 737.08 | 706.22 | 578.57 | 302.63 | 275.94 | 0.00 | 0.00 |
December | 648.74 | 775.78 | 510.98 | 274.07 | 236.91 | 0.00 | 0.00 |
Annual Sum or Average | 1053.72 | 577.08 | 770.69 | 393.19 | 377.49 | 0.00 | 0.00 |
Minimum of Months | 624.44 | 377.81 | 502.26 | 253.32 | 236.91 | 0.00 | 0.00 |
Maximum of Months | 1544.82 | 775.78 | 1043.07 | 558.14 | 500.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.512376E+09 | 0.288477E+10 | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.00 | 0.00 |
February | 0.546247E+09 | 0.236692E+10 | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.00 | 0.00 |
March | 0.867974E+09 | 0.270212E+10 | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.00 | 0.00 |
April | 0.114523E+10 | 0.209220E+10 | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.00 | 0.00 |
May | 0.150585E+10 | 0.190050E+10 | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.00 | 0.00 |
June | 0.184848E+10 | 0.145162E+10 | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.00 | 0.00 |
July | 0.200378E+10 | 0.134570E+10 | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.00 | 0.00 |
August | 0.160862E+10 | 0.141363E+10 | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.00 | 0.00 |
September | 0.121566E+10 | 0.163325E+10 | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.00 | 0.00 |
October | 0.109968E+10 | 0.188596E+10 | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.00 | 0.00 |
November | 0.561872E+09 | 0.257582E+10 | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.00 | 0.00 |
December | 0.465206E+09 | 0.290811E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133810E+11 | 0.251606E+11 | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.00 | 0.00 |
Minimum of Months | 0.465206E+09 | 0.134570E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200378E+10 | 0.290811E+10 | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171460E+10 | 0.181955E+10 | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.00 | 0.00 |
February | 0.152398E+10 | 0.150511E+10 | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.00 | 0.00 |
March | 0.213378E+10 | 0.171547E+10 | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.00 | 0.00 |
April | 0.298646E+10 | 0.136624E+10 | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.00 | 0.00 |
May | 0.279346E+10 | 0.129660E+10 | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.00 | 0.00 |
June | 0.287498E+10 | 0.100549E+10 | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.00 | 0.00 |
July | 0.362635E+10 | 0.936056E+09 | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.00 | 0.00 |
August | 0.363194E+10 | 0.954702E+09 | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.00 | 0.00 |
September | 0.242200E+10 | 0.106353E+10 | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.00 | 0.00 |
October | 0.226833E+10 | 0.121140E+10 | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.00 | 0.00 |
November | 0.166651E+10 | 0.163631E+10 | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.00 | 0.00 |
December | 0.165449E+10 | 0.182884E+10 | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292969E+11 | 0.163393E+11 | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152398E+10 | 0.936056E+09 | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363194E+10 | 0.182884E+10 | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756988E+10 | 0.281321E+10 | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.00 | 0.00 |
February | 0.504508E+10 | 0.232331E+10 | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.00 | 0.00 |
March | 0.438561E+10 | 0.270753E+10 | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.00 | 0.00 |
April | 0.377855E+10 | 0.219762E+10 | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.00 | 0.00 |
May | 0.223714E+10 | 0.207154E+10 | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.00 | 0.00 |
June | 0.190086E+10 | 0.157271E+10 | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.00 | 0.00 |
July | 0.243704E+10 | 0.144317E+10 | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.00 | 0.00 |
August | 0.363049E+10 | 0.150694E+10 | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.00 | 0.00 |
September | 0.490928E+10 | 0.168994E+10 | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.00 | 0.00 |
October | 0.647843E+10 | 0.189975E+10 | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.00 | 0.00 |
November | 0.697824E+10 | 0.251989E+10 | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.00 | 0.00 |
December | 0.812842E+10 | 0.282555E+10 | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574790E+11 | 0.255712E+11 | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190086E+10 | 0.144317E+10 | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.00 | 0.00 |
Maximum of Months | 0.812842E+10 | 0.282555E+10 | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170489E+10 | 0.190653E+10 | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.00 | 0.00 |
February | 0.174469E+10 | 0.156407E+10 | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.00 | 0.00 |
March | 0.224160E+10 | 0.177722E+10 | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.00 | 0.00 |
April | 0.335890E+10 | 0.143607E+10 | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.00 | 0.00 |
May | 0.329815E+10 | 0.135327E+10 | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.00 | 0.00 |
June | 0.357505E+10 | 0.103516E+10 | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.00 | 0.00 |
July | 0.413095E+10 | 0.965710E+09 | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.00 | 0.00 |
August | 0.393252E+10 | 0.100245E+10 | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.00 | 0.00 |
September | 0.315556E+10 | 0.110436E+10 | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.00 | 0.00 |
October | 0.256336E+10 | 0.126985E+10 | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.00 | 0.00 |
November | 0.194004E+10 | 0.169497E+10 | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.00 | 0.00 |
December | 0.177144E+10 | 0.191892E+10 | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334171E+11 | 0.170286E+11 | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.170489E+10 | 0.965710E+09 | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.00 | 0.00 |
Maximum of Months | 0.413095E+10 | 0.191892E+10 | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.486582E+09 | 0.308088E+10 | 0.785927E+09 | 0.00 | 0.785927E+09 | 0.00 | 0.00 |
February | 0.548902E+09 | 0.247583E+10 | 0.891075E+09 | 0.00 | 0.891075E+09 | 0.00 | 0.00 |
March | 0.892956E+09 | 0.278711E+10 | 0.120894E+10 | 0.00 | 0.120894E+10 | 0.00 | 0.00 |
April | 0.119586E+10 | 0.212499E+10 | 0.134791E+10 | 5187843.82 | 0.134272E+10 | 0.00 | 0.00 |
May | 0.155444E+10 | 0.193827E+10 | 0.167375E+10 | 77938061.47 | 0.159581E+10 | 0.00 | 0.00 |
June | 0.192175E+10 | 0.145786E+10 | 0.172593E+10 | 0.168737E+09 | 0.155719E+10 | 0.00 | 0.00 |
July | 0.206585E+10 | 0.136226E+10 | 0.168866E+10 | 0.141536E+09 | 0.154712E+10 | 0.00 | 0.00 |
August | 0.165740E+10 | 0.143096E+10 | 0.140238E+10 | 28080891.87 | 0.137430E+10 | 0.00 | 0.00 |
September | 0.123931E+10 | 0.168857E+10 | 0.114868E+10 | 180040.75 | 0.114850E+10 | 0.00 | 0.00 |
October | 0.109927E+10 | 0.198535E+10 | 0.941541E+09 | 0.00 | 0.941541E+09 | 0.00 | 0.00 |
November | 0.536949E+09 | 0.275659E+10 | 0.824997E+09 | 0.00 | 0.824997E+09 | 0.00 | 0.00 |
December | 0.437315E+09 | 0.310858E+10 | 0.731631E+09 | 0.00 | 0.731631E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.136366E+11 | 0.261973E+11 | 0.143714E+11 | 0.421660E+09 | 0.139498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.437315E+09 | 0.136226E+10 | 0.731631E+09 | 0.00 | 0.731631E+09 | 0.00 | 0.00 |
Maximum of Months | 0.206585E+10 | 0.310858E+10 | 0.172593E+10 | 0.168737E+09 | 0.159581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167886E+10 | 0.198711E+10 | 0.141333E+10 | 0.755879E+09 | 0.657450E+09 | 0.00 | 0.00 |
February | 0.151683E+10 | 0.160971E+10 | 0.134663E+10 | 0.616902E+09 | 0.729733E+09 | 0.00 | 0.00 |
March | 0.213776E+10 | 0.181073E+10 | 0.181103E+10 | 0.806892E+09 | 0.100414E+10 | 0.00 | 0.00 |
April | 0.301131E+10 | 0.143564E+10 | 0.224069E+10 | 0.112375E+10 | 0.111694E+10 | 0.00 | 0.00 |
May | 0.281819E+10 | 0.135485E+10 | 0.218506E+10 | 0.911871E+09 | 0.127319E+10 | 0.00 | 0.00 |
June | 0.291420E+10 | 0.103314E+10 | 0.210140E+10 | 0.911757E+09 | 0.118965E+10 | 0.00 | 0.00 |
July | 0.366124E+10 | 0.980805E+09 | 0.246042E+10 | 0.122264E+10 | 0.123778E+10 | 0.00 | 0.00 |
August | 0.366280E+10 | 0.100530E+10 | 0.242986E+10 | 0.129066E+10 | 0.113921E+10 | 0.00 | 0.00 |
September | 0.243501E+10 | 0.113162E+10 | 0.171206E+10 | 0.784529E+09 | 0.927535E+09 | 0.00 | 0.00 |
October | 0.226713E+10 | 0.130464E+10 | 0.156601E+10 | 0.804883E+09 | 0.761122E+09 | 0.00 | 0.00 |
November | 0.163780E+10 | 0.178333E+10 | 0.138155E+10 | 0.701880E+09 | 0.679666E+09 | 0.00 | 0.00 |
December | 0.161708E+10 | 0.199482E+10 | 0.136190E+10 | 0.756684E+09 | 0.605217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293582E+11 | 0.174317E+11 | 0.220099E+11 | 0.106883E+11 | 0.113216E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151683E+10 | 0.980805E+09 | 0.134663E+10 | 0.616902E+09 | 0.605217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366280E+10 | 0.199482E+10 | 0.246042E+10 | 0.129066E+10 | 0.127319E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755964E+10 | 0.312392E+10 | 0.518648E+10 | 0.380451E+10 | 0.138197E+10 | 0.00 | 0.00 |
February | 0.508020E+10 | 0.250947E+10 | 0.368182E+10 | 0.226780E+10 | 0.141402E+10 | 0.00 | 0.00 |
March | 0.444909E+10 | 0.283036E+10 | 0.324976E+10 | 0.156978E+10 | 0.167998E+10 | 0.00 | 0.00 |
April | 0.384744E+10 | 0.226021E+10 | 0.262768E+10 | 0.100195E+10 | 0.162573E+10 | 0.00 | 0.00 |
May | 0.232641E+10 | 0.208793E+10 | 0.193349E+10 | 0.237939E+09 | 0.169555E+10 | 0.00 | 0.00 |
June | 0.199856E+10 | 0.154909E+10 | 0.164147E+10 | 99104559.54 | 0.154236E+10 | 0.00 | 0.00 |
July | 0.251017E+10 | 0.145190E+10 | 0.179673E+10 | 0.202257E+09 | 0.159447E+10 | 0.00 | 0.00 |
August | 0.369508E+10 | 0.154689E+10 | 0.230825E+10 | 0.728085E+09 | 0.158016E+10 | 0.00 | 0.00 |
September | 0.495292E+10 | 0.179941E+10 | 0.310830E+10 | 0.157507E+10 | 0.153323E+10 | 0.00 | 0.00 |
October | 0.649853E+10 | 0.207680E+10 | 0.408479E+10 | 0.273078E+10 | 0.135400E+10 | 0.00 | 0.00 |
November | 0.698413E+10 | 0.278561E+10 | 0.480449E+10 | 0.339189E+10 | 0.141260E+10 | 0.00 | 0.00 |
December | 0.812138E+10 | 0.314007E+10 | 0.554081E+10 | 0.421727E+10 | 0.132354E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580236E+11 | 0.271617E+11 | 0.399640E+11 | 0.218264E+11 | 0.181376E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199856E+10 | 0.145190E+10 | 0.164147E+10 | 99104559.54 | 0.132354E+10 | 0.00 | 0.00 |
Maximum of Months | 0.812138E+10 | 0.314007E+10 | 0.554081E+10 | 0.421727E+10 | 0.169555E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169111E+10 | 0.208318E+10 | 0.134525E+10 | 0.678479E+09 | 0.666766E+09 | 0.00 | 0.00 |
February | 0.174913E+10 | 0.168325E+10 | 0.144957E+10 | 0.669188E+09 | 0.780384E+09 | 0.00 | 0.00 |
March | 0.225877E+10 | 0.188931E+10 | 0.183963E+10 | 0.813877E+09 | 0.102575E+10 | 0.00 | 0.00 |
April | 0.339129E+10 | 0.152258E+10 | 0.245422E+10 | 0.127790E+10 | 0.117632E+10 | 0.00 | 0.00 |
May | 0.333192E+10 | 0.143384E+10 | 0.249117E+10 | 0.115066E+10 | 0.134051E+10 | 0.00 | 0.00 |
June | 0.362392E+10 | 0.108104E+10 | 0.255399E+10 | 0.127694E+10 | 0.127705E+10 | 0.00 | 0.00 |
July | 0.417181E+10 | 0.102172E+10 | 0.279373E+10 | 0.149489E+10 | 0.129883E+10 | 0.00 | 0.00 |
August | 0.396999E+10 | 0.106352E+10 | 0.262106E+10 | 0.142050E+10 | 0.120056E+10 | 0.00 | 0.00 |
September | 0.317536E+10 | 0.119207E+10 | 0.217172E+10 | 0.116205E+10 | 0.100967E+10 | 0.00 | 0.00 |
October | 0.256625E+10 | 0.137892E+10 | 0.171552E+10 | 0.936597E+09 | 0.778922E+09 | 0.00 | 0.00 |
November | 0.192559E+10 | 0.186506E+10 | 0.149964E+10 | 0.784414E+09 | 0.715225E+09 | 0.00 | 0.00 |
December | 0.175478E+10 | 0.210138E+10 | 0.136859E+10 | 0.734044E+09 | 0.634544E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.336099E+11 | 0.183159E+11 | 0.243041E+11 | 0.123996E+11 | 0.119045E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169111E+10 | 0.102172E+10 | 0.134525E+10 | 0.669188E+09 | 0.634544E+09 | 0.00 | 0.00 |
Maximum of Months | 0.417181E+10 | 0.210138E+10 | 0.279373E+10 | 0.149489E+10 | 0.134051E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.459409E+09 | 0.312907E+10 | 0.785942E+09 | 0.00 | 0.785942E+09 | 0.00 | 0.00 |
February | 0.498049E+09 | 0.257022E+10 | 0.891094E+09 | 0.00 | 0.891094E+09 | 0.00 | 0.00 |
March | 0.819228E+09 | 0.289836E+10 | 0.120896E+10 | 0.00 | 0.120896E+10 | 0.00 | 0.00 |
April | 0.111968E+10 | 0.222356E+10 | 0.134794E+10 | 5187996.30 | 0.134275E+10 | 0.00 | 0.00 |
May | 0.147135E+10 | 0.200811E+10 | 0.167378E+10 | 77940352.35 | 0.159584E+10 | 0.00 | 0.00 |
June | 0.183831E+10 | 0.152330E+10 | 0.172597E+10 | 0.168742E+09 | 0.155722E+10 | 0.00 | 0.00 |
July | 0.200454E+10 | 0.140845E+10 | 0.168869E+10 | 0.141540E+09 | 0.154715E+10 | 0.00 | 0.00 |
August | 0.160541E+10 | 0.148569E+10 | 0.140240E+10 | 28081717.27 | 0.137432E+10 | 0.00 | 0.00 |
September | 0.119983E+10 | 0.173602E+10 | 0.114870E+10 | 180046.04 | 0.114852E+10 | 0.00 | 0.00 |
October | 0.107321E+10 | 0.201755E+10 | 0.941559E+09 | 0.00 | 0.941559E+09 | 0.00 | 0.00 |
November | 0.511535E+09 | 0.279087E+10 | 0.825014E+09 | 0.00 | 0.825014E+09 | 0.00 | 0.00 |
December | 0.410419E+09 | 0.316397E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.130110E+11 | 0.269552E+11 | 0.143717E+11 | 0.421672E+09 | 0.139500E+11 | 0.00 | 0.00 |
Minimum of Months | 0.410419E+09 | 0.140845E+10 | 0.731645E+09 | 0.00 | 0.731645E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200454E+10 | 0.316397E+10 | 0.172597E+10 | 0.168742E+09 | 0.159584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166784E+10 | 0.195352E+10 | 0.141335E+10 | 0.755894E+09 | 0.657458E+09 | 0.00 | 0.00 |
February | 0.148813E+10 | 0.161780E+10 | 0.134666E+10 | 0.616914E+09 | 0.729742E+09 | 0.00 | 0.00 |
March | 0.209910E+10 | 0.182280E+10 | 0.181106E+10 | 0.806908E+09 | 0.100415E+10 | 0.00 | 0.00 |
April | 0.297249E+10 | 0.143810E+10 | 0.224072E+10 | 0.112377E+10 | 0.111695E+10 | 0.00 | 0.00 |
May | 0.277631E+10 | 0.136018E+10 | 0.218509E+10 | 0.911889E+09 | 0.127320E+10 | 0.00 | 0.00 |
June | 0.287106E+10 | 0.104881E+10 | 0.210143E+10 | 0.911775E+09 | 0.118966E+10 | 0.00 | 0.00 |
July | 0.363165E+10 | 0.974065E+09 | 0.246045E+10 | 0.122267E+10 | 0.123779E+10 | 0.00 | 0.00 |
August | 0.363555E+10 | 0.996333E+09 | 0.242990E+10 | 0.129068E+10 | 0.113922E+10 | 0.00 | 0.00 |
September | 0.241445E+10 | 0.112292E+10 | 0.171209E+10 | 0.784544E+09 | 0.927545E+09 | 0.00 | 0.00 |
October | 0.225149E+10 | 0.128400E+10 | 0.156603E+10 | 0.804899E+09 | 0.761130E+09 | 0.00 | 0.00 |
November | 0.162608E+10 | 0.175262E+10 | 0.138157E+10 | 0.701894E+09 | 0.679674E+09 | 0.00 | 0.00 |
December | 0.160482E+10 | 0.196689E+10 | 0.136192E+10 | 0.756698E+09 | 0.605224E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290390E+11 | 0.173380E+11 | 0.220103E+11 | 0.106885E+11 | 0.113217E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148813E+10 | 0.974065E+09 | 0.134666E+10 | 0.616914E+09 | 0.605224E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363555E+10 | 0.196689E+10 | 0.246045E+10 | 0.129068E+10 | 0.127320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.751698E+10 | 0.301511E+10 | 0.518668E+10 | 0.380467E+10 | 0.138201E+10 | 0.00 | 0.00 |
February | 0.500157E+10 | 0.250156E+10 | 0.368196E+10 | 0.226789E+10 | 0.141407E+10 | 0.00 | 0.00 |
March | 0.434258E+10 | 0.289262E+10 | 0.324988E+10 | 0.156985E+10 | 0.168004E+10 | 0.00 | 0.00 |
April | 0.376183E+10 | 0.232730E+10 | 0.262776E+10 | 0.100199E+10 | 0.162577E+10 | 0.00 | 0.00 |
May | 0.221508E+10 | 0.219289E+10 | 0.193354E+10 | 0.237949E+09 | 0.169559E+10 | 0.00 | 0.00 |
June | 0.189272E+10 | 0.165336E+10 | 0.164151E+10 | 99108672.29 | 0.154240E+10 | 0.00 | 0.00 |
July | 0.243914E+10 | 0.151158E+10 | 0.179677E+10 | 0.202265E+09 | 0.159451E+10 | 0.00 | 0.00 |
August | 0.363468E+10 | 0.158243E+10 | 0.230832E+10 | 0.728115E+09 | 0.158020E+10 | 0.00 | 0.00 |
September | 0.490421E+10 | 0.178861E+10 | 0.310841E+10 | 0.157514E+10 | 0.153327E+10 | 0.00 | 0.00 |
October | 0.646164E+10 | 0.201430E+10 | 0.408494E+10 | 0.273090E+10 | 0.135404E+10 | 0.00 | 0.00 |
November | 0.693479E+10 | 0.269460E+10 | 0.480468E+10 | 0.339203E+10 | 0.141265E+10 | 0.00 | 0.00 |
December | 0.807374E+10 | 0.302752E+10 | 0.554103E+10 | 0.421745E+10 | 0.132358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.571790E+11 | 0.272019E+11 | 0.399655E+11 | 0.218273E+11 | 0.181381E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189272E+10 | 0.151158E+10 | 0.164151E+10 | 99108672.29 | 0.132358E+10 | 0.00 | 0.00 |
Maximum of Months | 0.807374E+10 | 0.302752E+10 | 0.554103E+10 | 0.421745E+10 | 0.169559E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167251E+10 | 0.206031E+10 | 0.134526E+10 | 0.678490E+09 | 0.666773E+09 | 0.00 | 0.00 |
February | 0.171554E+10 | 0.169177E+10 | 0.144959E+10 | 0.669199E+09 | 0.780392E+09 | 0.00 | 0.00 |
March | 0.221327E+10 | 0.190352E+10 | 0.183965E+10 | 0.813890E+09 | 0.102576E+10 | 0.00 | 0.00 |
April | 0.334709E+10 | 0.152249E+10 | 0.245425E+10 | 0.127792E+10 | 0.117633E+10 | 0.00 | 0.00 |
May | 0.328548E+10 | 0.143188E+10 | 0.249121E+10 | 0.115068E+10 | 0.134052E+10 | 0.00 | 0.00 |
June | 0.357490E+10 | 0.108829E+10 | 0.255402E+10 | 0.127696E+10 | 0.127706E+10 | 0.00 | 0.00 |
July | 0.413764E+10 | 0.101192E+10 | 0.279376E+10 | 0.149492E+10 | 0.129884E+10 | 0.00 | 0.00 |
August | 0.393741E+10 | 0.105338E+10 | 0.262109E+10 | 0.142052E+10 | 0.120057E+10 | 0.00 | 0.00 |
September | 0.314943E+10 | 0.117200E+10 | 0.217175E+10 | 0.116207E+10 | 0.100968E+10 | 0.00 | 0.00 |
October | 0.254878E+10 | 0.135481E+10 | 0.171554E+10 | 0.936613E+09 | 0.778929E+09 | 0.00 | 0.00 |
November | 0.191051E+10 | 0.183052E+10 | 0.149966E+10 | 0.784427E+09 | 0.715232E+09 | 0.00 | 0.00 |
December | 0.173759E+10 | 0.207785E+10 | 0.136861E+10 | 0.734056E+09 | 0.634550E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.332302E+11 | 0.181988E+11 | 0.243044E+11 | 0.123998E+11 | 0.119046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167251E+10 | 0.101192E+10 | 0.134526E+10 | 0.669199E+09 | 0.634550E+09 | 0.00 | 0.00 |
Maximum of Months | 0.413764E+10 | 0.207785E+10 | 0.279376E+10 | 0.149492E+10 | 0.134052E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.425523E+10 | -0.402133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233900141.7 | 60.05 | 0.00 | 0.00 |
February | 0.387025E+10 | -0.365887E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -211376076.7 | 60.05 | 0.00 | 0.00 |
March | 0.451953E+10 | -0.428537E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234156107.3 | 60.05 | 0.00 | 0.00 |
April | 0.400336E+10 | -0.377777E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225592466.2 | 60.05 | 0.00 | 0.00 |
May | 0.418417E+10 | -0.395126E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232909091.6 | 60.05 | 0.00 | 0.00 |
June | 0.406357E+10 | -0.383830E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225273093.8 | 60.05 | 0.00 | 0.00 |
July | 0.379559E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231967009.4 | 60.05 | 0.00 | 0.00 |
August | 0.416781E+10 | -0.393536E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232451435.1 | 60.05 | 0.00 | 0.00 |
September | 0.380967E+10 | -0.358509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224584324.7 | 60.05 | 0.00 | 0.00 |
October | 0.401651E+10 | -0.378454E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231971324.6 | 60.05 | 0.00 | 0.00 |
November | 0.404290E+10 | -0.381753E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225367048.1 | 60.05 | 0.00 | 0.00 |
December | 0.409446E+10 | -0.386073E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233731062.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.488230E+11 | -0.460798E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.274328E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.379559E+10 | -0.428537E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234156107.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.451953E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -211376076.7 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7863.85 | 37.27 | 285.00 | 280.17 | 1734.18 | 25.88 | 169.00 | 265.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:40 | 6966.72 | 35.52 | 275.33 | 274.67 | 1233.16 | 21.06 | 138.50 | 244.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-07:10 | 2047.14 | 18.83 | 11.17 | 315.00 | 1002.95 | 20.31 | 149.17 | 286.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1327.72 | 18.01 | 0.00 | 332.50 | 815.86 | 20.21 | 93.33 | 297.00 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1133.88 | 17.85 | 0.00 | 364.50 | 656.92 | 20.01 | 61.83 | 320.83 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1002.22 | 17.50 | 0.00 | 355.67 | 598.21 | 19.70 | 20.67 | 308.50 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:40 | 1009.80 | 17.54 | 0.00 | 365.17 | 622.94 | 19.76 | 25.83 | 329.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1138.26 | 17.66 | 0.00 | 354.00 | 713.42 | 19.85 | 49.33 | 316.00 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1623.56 | 18.46 | 11.00 | 308.83 | 950.96 | 20.21 | 88.50 | 277.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3509.52 | 24.54 | 115.83 | 303.00 | 1189.50 | 20.86 | 83.83 | 276.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7604.11 | 36.90 | 292.67 | 279.17 | 1557.71 | 25.55 | 179.50 | 270.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7725.99 | 37.39 | 286.17 | 281.17 | 2206.69 | 28.83 | 181.50 | 271.83 |
Annual Sum or Average | 4065.67 | 0.52 | 3260.97 | 23.85 | 1277.17 | 3813.83 | 1055.84 | 21.61 | 1241.00 | 3464.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1002.22 | 17.50 | 0.00 | 274.67 | 598.21 | 19.70 | 20.67 | 244.83 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7863.85 | 37.39 | 292.67 | 365.17 | 2206.69 | 28.83 | 181.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1718.14 | 21.64 | 85.00 | 264.83 | 880.21 | 22.19 | 61.33 | 223.17 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1846.04 | 20.34 | 70.83 | 267.17 | 990.44 | 22.46 | 55.83 | 220.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2288.45 | 21.61 | 106.50 | 315.83 | 1260.41 | 22.51 | 77.67 | 274.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2275.48 | 19.29 | 77.33 | 336.50 | 1234.96 | 21.79 | 65.17 | 305.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2233.57 | 20.07 | 99.50 | 376.50 | 1221.82 | 21.34 | 69.50 | 329.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 2223.54 | 19.24 | 88.83 | 367.17 | 951.28 | 19.40 | 36.33 | 322.33 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2452.96 | 19.73 | 99.67 | 376.17 | 1300.55 | 20.91 | 68.67 | 338.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2469.60 | 20.47 | 102.17 | 362.50 | 1266.47 | 21.47 | 69.67 | 325.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2566.34 | 20.47 | 92.83 | 311.00 | 981.04 | 20.49 | 43.83 | 273.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2339.70 | 20.95 | 88.83 | 282.17 | 967.33 | 20.42 | 42.67 | 234.00 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 1955.88 | 21.88 | 95.17 | 263.00 | 1062.89 | 22.50 | 68.83 | 228.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1695.78 | 21.25 | 86.17 | 264.00 | 878.45 | 21.71 | 63.33 | 220.50 |
Annual Sum or Average | 4065.67 | 0.52 | 2196.64 | 20.50 | 1092.83 | 3786.83 | 1097.65 | 21.38 | 722.83 | 3296.17 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1695.78 | 19.24 | 70.83 | 263.00 | 878.45 | 19.40 | 36.33 | 220.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2566.34 | 21.88 | 106.50 | 376.50 | 1300.55 | 22.51 | 77.67 | 338.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 526.31 | 15.18 | 0.00 | 233.17 | 343.32 | 17.79 | 0.00 | 152.17 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-09:09 | 631.25 | 16.02 | 0.00 | 246.83 | 389.37 | 18.34 | 0.00 | 173.00 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:39 | 740.26 | 16.43 | 0.00 | 305.67 | 444.10 | 18.56 | 0.00 | 248.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 819.89 | 17.66 | 0.00 | 335.83 | 523.13 | 19.85 | 6.50 | 296.17 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1029.94 | 18.32 | 0.00 | 381.17 | 601.92 | 20.49 | 73.83 | 352.50 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1089.10 | 20.15 | 42.50 | 374.17 | 651.16 | 22.23 | 125.83 | 342.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:49 | 1019.40 | 20.06 | 45.17 | 384.67 | 602.08 | 20.59 | 102.17 | 361.17 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 841.40 | 17.76 | 0.00 | 364.67 | 539.68 | 19.94 | 29.83 | 337.83 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 732.15 | 16.93 | 0.00 | 304.00 | 470.35 | 19.18 | 0.00 | 257.33 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 558.82 | 15.42 | 0.00 | 258.17 | 366.86 | 17.86 | 0.00 | 172.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:09 | 534.94 | 14.83 | 0.00 | 236.83 | 345.73 | 17.30 | 0.00 | 160.50 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-08:50 | 478.41 | 14.44 | 0.00 | 226.17 | 317.95 | 17.12 | 0.00 | 131.83 |
Annual Sum or Average | 4065.67 | 0.53 | 774.72 | 17.15 | 87.67 | 3651.33 | 479.81 | 19.27 | 338.17 | 2985.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 478.41 | 14.44 | 0.00 | 226.17 | 317.95 | 17.12 | 0.00 | 131.83 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 1089.10 | 20.15 | 45.17 | 384.67 | 651.16 | 22.23 | 125.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2233.07 | 22.54 | 105.17 | 251.33 | 844.59 | 21.23 | 50.83 | 209.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:09 | 2006.85 | 20.29 | 73.50 | 253.00 | 1104.86 | 22.53 | 60.00 | 214.17 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:39 | 2282.83 | 21.01 | 100.17 | 309.17 | 1240.44 | 21.95 | 71.67 | 266.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3157.99 | 19.49 | 82.33 | 330.67 | 1194.60 | 17.72 | 0.00 | 298.00 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2934.35 | 17.06 | 52.50 | 365.50 | 1204.08 | 17.87 | 0.00 | 328.33 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2503.50 | 14.28 | 0.00 | 360.83 | 1364.66 | 17.82 | 0.00 | 323.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:10 | 2641.64 | 14.40 | 5.67 | 369.83 | 1408.92 | 17.74 | 0.00 | 341.67 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3250.99 | 19.15 | 88.17 | 353.00 | 1332.77 | 17.92 | 7.00 | 323.67 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:40 | 2809.81 | 21.86 | 101.83 | 303.83 | 1505.81 | 22.49 | 71.83 | 269.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2086.81 | 20.53 | 82.00 | 284.33 | 1098.02 | 21.10 | 52.50 | 238.17 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:09 | 2180.53 | 22.41 | 104.33 | 253.83 | 1198.93 | 22.97 | 75.17 | 213.83 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:50 | 1981.58 | 22.40 | 104.67 | 245.67 | 1100.52 | 22.97 | 80.33 | 198.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2549.07 | 19.32 | 900.33 | 3681.00 | 1230.24 | 20.10 | 469.33 | 3224.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1981.58 | 14.28 | 0.00 | 245.67 | 844.59 | 17.72 | 0.00 | 198.00 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3250.99 | 22.54 | 105.17 | 369.83 | 1505.81 | 22.97 | 80.33 | 341.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7710.22 | 36.97 | 284.83 | 279.17 | 1612.25 | 23.50 | 97.50 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6848.72 | 35.29 | 275.33 | 274.00 | 1181.24 | 21.69 | 61.00 | 251.50 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 1958.06 | 15.06 | 11.17 | 314.00 | 941.18 | 17.96 | 5.50 | 282.83 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1265.43 | 14.41 | 0.00 | 331.83 | 772.09 | 17.97 | 0.00 | 293.83 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 1090.27 | 14.29 | 0.00 | 362.17 | 630.15 | 17.78 | 0.00 | 315.83 |
June | 381.00 | 0.53 | 0.48 | 01-JUN-06:00 | 965.93 | 14.04 | 0.00 | 353.67 | 577.24 | 17.54 | 0.00 | 303.67 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:49 | 971.73 | 14.19 | 0.00 | 363.00 | 600.59 | 17.73 | 0.00 | 324.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 1087.83 | 14.24 | 0.00 | 351.33 | 679.64 | 17.78 | 0.00 | 311.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1542.90 | 14.79 | 11.00 | 307.17 | 889.59 | 17.81 | 2.00 | 275.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3401.21 | 21.87 | 115.67 | 302.67 | 1097.65 | 18.20 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7463.42 | 36.66 | 292.67 | 278.50 | 1446.34 | 23.11 | 92.67 | 269.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7567.54 | 37.04 | 285.67 | 279.67 | 2077.94 | 26.76 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.52 | 3176.20 | 21.31 | 1276.33 | 3797.17 | 995.15 | 19.55 | 415.67 | 3435.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 965.93 | 14.04 | 0.00 | 274.00 | 577.24 | 17.54 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7710.22 | 37.04 | 292.67 | 363.00 | 2077.94 | 26.76 | 143.00 | 324.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1666.69 | 21.14 | 85.00 | 263.67 | 840.17 | 21.96 | 57.00 | 219.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1791.42 | 19.83 | 70.83 | 265.00 | 947.24 | 22.24 | 54.83 | 216.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2232.15 | 21.16 | 106.50 | 313.50 | 1214.87 | 22.32 | 77.67 | 270.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2205.30 | 18.81 | 77.33 | 334.83 | 1179.69 | 21.61 | 65.17 | 302.00 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2168.53 | 19.61 | 99.33 | 375.50 | 1175.14 | 21.17 | 69.33 | 323.50 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2165.90 | 18.77 | 88.83 | 364.00 | 905.61 | 19.22 | 36.33 | 317.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2384.35 | 19.26 | 99.17 | 373.00 | 1248.36 | 20.74 | 68.67 | 335.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-06:49 | 2351.96 | 18.66 | 85.67 | 357.67 | 1211.83 | 21.30 | 69.67 | 322.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2512.48 | 20.00 | 92.83 | 309.67 | 936.45 | 20.29 | 43.83 | 268.33 |
October | 296.17 | 0.54 | 0.48 | 01-OCT-09:39 | 2257.52 | 20.01 | 85.00 | 278.83 | 924.72 | 20.21 | 42.67 | 230.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:40 | 1838.64 | 19.66 | 79.50 | 258.83 | 1022.29 | 22.28 | 66.33 | 224.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1646.80 | 20.76 | 86.17 | 261.83 | 838.34 | 21.48 | 58.83 | 216.00 |
Annual Sum or Average | 4065.67 | 0.52 | 2125.83 | 19.74 | 1056.17 | 3756.33 | 1051.20 | 21.19 | 710.33 | 3244.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1646.80 | 18.66 | 70.83 | 258.83 | 838.34 | 19.22 | 36.33 | 216.00 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2512.48 | 21.16 | 106.50 | 375.50 | 1248.36 | 22.32 | 77.67 | 335.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 506.51 | 11.57 | 0.00 | 229.00 | 333.13 | 15.48 | 0.00 | 142.00 |
February | 279.67 | 0.55 | 0.48 | 01-FEB-09:20 | 608.47 | 12.55 | 0.00 | 244.33 | 377.20 | 16.16 | 0.00 | 164.67 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 714.62 | 13.08 | 0.00 | 303.50 | 430.15 | 16.50 | 0.00 | 241.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 791.97 | 14.38 | 0.00 | 334.83 | 508.73 | 17.96 | 0.00 | 292.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 994.52 | 14.76 | 0.00 | 380.33 | 582.03 | 18.37 | 0.00 | 348.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1051.62 | 16.96 | 42.50 | 373.67 | 629.76 | 20.22 | 41.17 | 338.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:00 | 984.41 | 17.01 | 45.17 | 382.67 | 582.81 | 18.57 | 0.00 | 358.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 812.83 | 14.50 | 0.00 | 364.00 | 524.92 | 18.12 | 0.00 | 333.50 |
September | 328.83 | 0.53 | 0.48 | 01-SEP-07:10 | 706.97 | 13.63 | 0.00 | 301.83 | 457.43 | 17.22 | 0.00 | 253.17 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 540.01 | 11.98 | 0.00 | 253.67 | 357.43 | 15.74 | 0.00 | 162.83 |
November | 300.00 | 0.58 | 0.48 | 01-NOV-08:20 | 515.19 | 11.41 | 0.00 | 232.50 | 335.52 | 15.10 | 0.00 | 151.00 |
December | 297.00 | 0.59 | 0.48 | 01-DEC-08:00 | 460.02 | 10.90 | 0.00 | 219.67 | 308.61 | 14.79 | 0.00 | 120.00 |
Annual Sum or Average | 4065.67 | 0.54 | 747.72 | 13.79 | 87.67 | 3620.00 | 465.35 | 17.20 | 41.17 | 2907.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 460.02 | 10.90 | 0.00 | 219.67 | 308.61 | 14.79 | 0.00 | 120.00 | |
Maximum of Months | 408.67 | 0.59 | 0.48 | 1051.62 | 17.01 | 45.17 | 382.67 | 629.76 | 20.22 | 41.17 | 358.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2180.92 | 22.14 | 105.17 | 248.83 | 804.57 | 21.13 | 50.17 | 207.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1946.53 | 19.86 | 73.50 | 251.33 | 1057.94 | 22.41 | 60.00 | 211.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 2224.51 | 20.61 | 100.17 | 307.50 | 1193.15 | 21.82 | 71.67 | 263.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3081.86 | 19.02 | 82.33 | 329.00 | 1134.94 | 17.55 | 0.00 | 294.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2855.44 | 16.55 | 52.50 | 363.50 | 1149.04 | 17.68 | 0.00 | 324.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2429.75 | 13.74 | 0.00 | 359.83 | 1305.94 | 17.63 | 0.00 | 321.50 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:19 | 2560.38 | 13.87 | 5.67 | 368.17 | 1348.82 | 17.55 | 0.00 | 339.83 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3167.56 | 18.68 | 88.17 | 350.33 | 1272.90 | 17.75 | 7.00 | 321.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:49 | 2739.84 | 21.44 | 101.83 | 302.67 | 1446.05 | 22.36 | 71.83 | 267.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2026.26 | 20.10 | 81.83 | 281.00 | 1048.21 | 20.98 | 52.50 | 235.33 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:20 | 2116.41 | 21.76 | 101.83 | 252.00 | 1155.12 | 22.87 | 75.17 | 210.50 |
December | 297.00 | 0.56 | 0.48 | 01-DEC-08:50 | 1863.59 | 20.23 | 88.17 | 239.83 | 1060.80 | 22.87 | 79.67 | 194.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2475.43 | 18.72 | 881.17 | 3654.00 | 1177.71 | 19.96 | 468.00 | 3190.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1863.59 | 13.74 | 0.00 | 239.83 | 804.57 | 17.55 | 0.00 | 194.00 | |
Maximum of Months | 408.67 | 0.56 | 0.48 | 3167.56 | 22.14 | 105.17 | 368.17 | 1446.05 | 22.87 | 79.67 | 339.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7710.19 | 36.97 | 284.83 | 279.17 | 1612.17 | 23.50 | 97.50 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6848.64 | 35.29 | 275.33 | 274.00 | 1181.16 | 21.69 | 61.00 | 251.50 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 1957.96 | 15.07 | 11.17 | 314.00 | 941.11 | 17.96 | 5.50 | 282.83 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1265.38 | 14.41 | 0.00 | 331.83 | 772.04 | 17.97 | 0.00 | 293.83 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 1090.22 | 14.30 | 0.00 | 362.17 | 630.11 | 17.78 | 0.00 | 315.83 |
June | 381.00 | 0.53 | 0.48 | 01-JUN-06:00 | 965.89 | 14.04 | 0.00 | 353.67 | 577.20 | 17.54 | 0.00 | 303.50 |
July | 408.67 | 0.53 | 0.48 | 01-JUL-06:49 | 971.69 | 14.19 | 0.00 | 363.00 | 600.55 | 17.73 | 0.00 | 324.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 1087.79 | 14.24 | 0.00 | 351.33 | 679.60 | 17.78 | 0.00 | 311.50 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 1542.83 | 14.79 | 11.00 | 307.17 | 889.53 | 17.81 | 2.00 | 275.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3401.15 | 21.87 | 115.67 | 302.67 | 1097.59 | 18.20 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7463.37 | 36.66 | 292.67 | 278.50 | 1446.26 | 23.11 | 92.67 | 269.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:19 | 7567.53 | 37.04 | 285.67 | 279.67 | 2077.86 | 26.76 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.52 | 3176.15 | 21.31 | 1276.33 | 3797.17 | 995.09 | 19.55 | 415.67 | 3434.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 965.89 | 14.04 | 0.00 | 274.00 | 577.20 | 17.54 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7710.19 | 37.04 | 292.67 | 363.00 | 2077.86 | 26.76 | 143.00 | 324.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1666.68 | 21.14 | 85.00 | 263.67 | 840.13 | 21.96 | 57.00 | 219.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1791.39 | 19.84 | 70.83 | 265.00 | 947.19 | 22.24 | 54.83 | 216.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2232.11 | 21.16 | 106.50 | 313.50 | 1214.82 | 22.32 | 77.67 | 270.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2205.27 | 18.81 | 77.33 | 334.83 | 1179.64 | 21.61 | 65.17 | 302.00 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2168.48 | 19.61 | 99.33 | 375.50 | 1175.08 | 21.17 | 69.33 | 323.50 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:19 | 2165.86 | 18.77 | 88.83 | 364.00 | 905.56 | 19.22 | 36.33 | 317.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-05:30 | 2384.32 | 19.26 | 99.17 | 373.00 | 1248.32 | 20.74 | 68.67 | 335.00 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-06:49 | 2351.94 | 18.66 | 85.67 | 357.67 | 1211.78 | 21.30 | 69.67 | 322.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:40 | 2512.45 | 20.00 | 92.83 | 309.67 | 936.41 | 20.29 | 43.83 | 268.33 |
October | 296.17 | 0.54 | 0.48 | 01-OCT-09:39 | 2257.50 | 20.02 | 85.00 | 278.83 | 924.68 | 20.21 | 42.67 | 230.33 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:40 | 1838.62 | 19.66 | 79.50 | 258.83 | 1022.25 | 22.28 | 66.33 | 224.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1646.79 | 20.76 | 86.17 | 261.83 | 838.31 | 21.48 | 58.83 | 215.83 |
Annual Sum or Average | 4065.67 | 0.52 | 2125.81 | 19.74 | 1056.17 | 3756.33 | 1051.15 | 21.19 | 710.33 | 3244.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1646.79 | 18.66 | 70.83 | 258.83 | 838.31 | 19.22 | 36.33 | 215.83 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2512.45 | 21.16 | 106.50 | 375.50 | 1248.32 | 22.32 | 77.67 | 335.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.57 | 0.48 | 01-JAN-09:09 | 506.50 | 11.57 | 0.00 | 229.00 | 333.12 | 15.48 | 0.00 | 142.00 |
February | 279.67 | 0.55 | 0.48 | 01-FEB-09:20 | 608.46 | 12.55 | 0.00 | 244.17 | 377.18 | 16.16 | 0.00 | 164.67 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 714.60 | 13.08 | 0.00 | 303.50 | 430.12 | 16.51 | 0.00 | 241.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 791.95 | 14.38 | 0.00 | 334.83 | 508.71 | 17.96 | 0.00 | 292.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 994.49 | 14.76 | 0.00 | 380.33 | 581.99 | 18.37 | 0.00 | 348.33 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1051.59 | 16.96 | 42.50 | 373.67 | 629.72 | 20.22 | 41.17 | 338.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:00 | 984.39 | 17.01 | 45.17 | 382.67 | 582.78 | 18.57 | 0.00 | 358.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 812.82 | 14.50 | 0.00 | 364.00 | 524.90 | 18.12 | 0.00 | 333.50 |
September | 328.83 | 0.53 | 0.48 | 01-SEP-07:10 | 706.96 | 13.64 | 0.00 | 301.83 | 457.41 | 17.22 | 0.00 | 253.17 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 540.00 | 11.98 | 0.00 | 253.67 | 357.42 | 15.75 | 0.00 | 162.83 |
November | 300.00 | 0.58 | 0.48 | 01-NOV-08:20 | 515.19 | 11.42 | 0.00 | 232.50 | 335.50 | 15.11 | 0.00 | 151.00 |
December | 297.00 | 0.59 | 0.48 | 01-DEC-08:00 | 460.02 | 10.90 | 0.00 | 219.67 | 308.59 | 14.79 | 0.00 | 120.00 |
Annual Sum or Average | 4065.67 | 0.54 | 747.70 | 13.79 | 87.67 | 3619.83 | 465.33 | 17.20 | 41.17 | 2907.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 460.02 | 10.90 | 0.00 | 219.67 | 308.59 | 14.79 | 0.00 | 120.00 | |
Maximum of Months | 408.67 | 0.59 | 0.48 | 1051.59 | 17.01 | 45.17 | 382.67 | 629.72 | 20.22 | 41.17 | 358.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 2180.90 | 22.15 | 105.17 | 248.83 | 804.54 | 21.13 | 50.17 | 207.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1946.51 | 19.86 | 73.50 | 251.33 | 1057.89 | 22.41 | 60.00 | 211.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 2224.47 | 20.61 | 100.17 | 307.50 | 1193.10 | 21.82 | 71.67 | 263.17 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:00 | 3081.84 | 19.02 | 82.33 | 329.00 | 1134.89 | 17.55 | 0.00 | 294.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-07:30 | 2855.39 | 16.56 | 52.50 | 363.50 | 1148.98 | 17.68 | 0.00 | 324.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2429.71 | 13.75 | 0.00 | 359.83 | 1305.88 | 17.63 | 0.00 | 321.50 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-07:19 | 2560.36 | 13.88 | 5.67 | 368.17 | 1348.77 | 17.55 | 0.00 | 339.83 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 3167.54 | 18.69 | 88.17 | 350.33 | 1272.85 | 17.75 | 7.00 | 321.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:49 | 2739.81 | 21.44 | 101.83 | 302.67 | 1445.99 | 22.36 | 71.83 | 267.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2026.25 | 20.10 | 81.83 | 281.00 | 1048.17 | 20.98 | 52.50 | 235.33 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-08:20 | 2116.40 | 21.76 | 101.83 | 252.00 | 1155.08 | 22.87 | 75.17 | 210.50 |
December | 297.00 | 0.56 | 0.48 | 01-DEC-08:50 | 1863.59 | 20.23 | 88.17 | 239.83 | 1060.76 | 22.87 | 79.67 | 194.00 |
Annual Sum or Average | 4065.67 | 0.53 | 2475.41 | 18.72 | 881.17 | 3654.00 | 1177.66 | 19.96 | 468.00 | 3190.67 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1863.59 | 13.75 | 0.00 | 239.83 | 804.54 | 17.55 | 0.00 | 194.00 | |
Maximum of Months | 408.67 | 0.56 | 0.48 | 3167.54 | 22.15 | 105.17 | 368.17 | 1445.99 | 22.87 | 79.67 | 339.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49890347.09 | 4606.90 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28150.15 | 187.67 | 11-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21365548.55 | 2506.10 | 30-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 444491.53 | 750.98 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34168.03 | 3.92 | 03-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 354600.61 | 3.92 | 19-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 950268.61 | 4.44 | 31-JUL-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1172263.19 | 4.49 | 18-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 495286.91 | 4.50 | 28-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 353391.59 | 4.49 | 18-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5851882.94 | 1946.53 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80940399.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49890347.09 | 4606.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.368148E+09 | 6113.60 | 23-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.412269E+09 | 6114.64 | 23-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.726698E+09 | 6116.04 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321898E+09 | 6118.79 | 11-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279426E+09 | 6117.82 | 09-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95896790.22 | 6122.96 | 05-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2450737.68 | 2414.03 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4234317.46 | 3159.99 | 28-AUG-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27569124.72 | 6116.68 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81785356.66 | 6111.42 | 25-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192407E+09 | 6117.59 | 16-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328124E+09 | 6124.35 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2450737.68 | 2414.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.726698E+09 | 6124.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3309229.58 | 4390.30 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 509094.39 | 454.81 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3763202.59 | 4390.67 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7581526.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3763202.59 | 4390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 40646571.46 | 5135.43 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5238737.98 | 2681.69 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22262717.67 | 5132.02 | 31-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2457647.99 | 4535.15 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4887539.84 | 3978.76 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75493214.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40646571.46 | 5135.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12879659.51 | 4490.47 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 977463.56 | 853.54 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7946312.80 | 4485.01 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1612987.15 | 2608.68 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1005398.48 | 1454.02 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24421821.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12879659.51 | 4490.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148202E+09 | 5994.00 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11294939.16 | 1890.08 | 09-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92954939.18 | 3957.36 | 30-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1825450.86 | 1655.34 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22721.17 | 3.60 | 04-MAY-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 298804.85 | 3.71 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 727085.78 | 3.99 | 18-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 980304.37 | 4.10 | 18-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 353176.05 | 3.87 | 12-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 211124.86 | 3.61 | 18-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 541219.87 | 433.24 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60386922.12 | 3206.51 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 22721.17 | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148202E+09 | 5994.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8752957.03 | 6584.57 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7897075.42 | 6580.38 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 977167.03 | 2408.24 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 248753.34 | 1658.36 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17875952.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8752957.03 | 6584.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19820060.99 | 4863.63 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3961535.35 | 1945.93 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7134668.42 | 4866.62 | 29-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 47283.00 | 315.22 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1623280.94 | 2354.27 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32586828.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19820060.99 | 4866.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 47302189.46 | 5624.43 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2806275.51 | 2138.77 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17180999.93 | 5607.26 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1448053.11 | 3047.23 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44183.26 | 294.56 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8734739.83 | 5607.04 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 77516441.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47302189.46 | 5624.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 43828227.15 | 4932.87 | 11-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6816295.96 | 2596.78 | 28-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19068382.63 | 4933.69 | 07-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2922660.39 | 4934.39 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 106775.89 | 528.67 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13143557.00 | 4933.10 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85885899.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43828227.15 | 4934.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.281459E+09 | 7045.93 | 09-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53829908.02 | 3647.28 | 09-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181715E+09 | 5661.23 | 30-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5644541.82 | 3222.45 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32393.44 | 3.56 | 03-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 303746.40 | 4.12 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 681393.58 | 4.36 | 19-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 900422.65 | 4.46 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 292948.83 | 4.23 | 06-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 437918.21 | 463.20 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8928327.95 | 2250.06 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159766E+09 | 4959.61 | 22-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693992E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32393.44 | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.281459E+09 | 7045.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 70797346.15 | 19870.79 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4861564.72 | 7964.16 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9762625.51 | 19699.93 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 273002.82 | 1820.02 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3222875.30 | 10507.49 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 88917414.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70797346.15 | 19870.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116940E+09 | 8265.80 | 03-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58651718.24 | 8263.65 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105594E+09 | 8258.48 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15075125.11 | 8247.98 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3917464.84 | 4728.75 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 458104.83 | 890.74 | 12-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6100762.56 | 7196.32 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44801907.09 | 8255.35 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116940E+09 | 8265.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127742E+09 | 5907.63 | 09-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69883695.66 | 5903.81 | 13-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67857851.23 | 5903.71 | 01-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3799751.88 | 5894.20 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1983395.22 | 5901.75 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9357508.32 | 5899.52 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 60952559.20 | 5904.51 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127742E+09 | 5907.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304162E+09 | 7140.12 | 09-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120524E+09 | 7117.12 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163149E+09 | 7145.03 | 30-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17746146.84 | 7101.55 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 391814.77 | 1656.10 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5644102.83 | 7110.55 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 59736471.33 | 7118.86 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178511E+09 | 7113.87 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304162E+09 | 7145.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.240020E+09 | 6199.42 | 09-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125187E+09 | 6178.56 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145226E+09 | 6175.96 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21791294.73 | 6165.09 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5118583.42 | 2830.73 | 15-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10087286.77 | 6172.93 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66272513.20 | 6182.41 | 14-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164391E+09 | 6175.57 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.240020E+09 | 6199.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.869492E+10 | 0.803935E+10 | 39493.05 | 18-JAN-13:30 | 39493.05 | 0.00 |
February | 0.00 | 0.00 | 0.497463E+10 | 0.426240E+10 | 37707.20 | 01-FEB-12:00 | 37707.20 | 0.00 |
March | 0.00 | 0.00 | 0.594638E+10 | 0.471128E+10 | 40432.30 | 23-MAR-15:00 | 30510.06 | 0.00 |
April | 0.00 | 0.00 | 0.132225E+11 | 0.111164E+11 | 46199.61 | 26-APR-14:10 | 44528.14 | 0.00 |
May | 0.00 | 0.00 | 0.141724E+11 | 0.120634E+11 | 35396.92 | 04-MAY-14:10 | 33750.38 | 0.00 |
June | 0.00 | 0.00 | 0.263716E+11 | 0.199918E+11 | 56129.55 | 28-JUN-11:00 | 35960.59 | 0.00 |
July | 0.00 | 0.00 | 0.448842E+11 | 0.300356E+11 | 85490.55 | 31-JUL-15:40 | 49625.78 | 0.00 |
August | 0.00 | 0.00 | 0.518214E+11 | 0.336777E+11 | 81684.11 | 18-AUG-15:50 | 47073.09 | 0.00 |
September | 0.00 | 0.00 | 0.319440E+11 | 0.231164E+11 | 63652.16 | 22-SEP-12:30 | 33509.03 | 0.00 |
October | 0.00 | 0.00 | 0.353003E+11 | 0.280880E+11 | 75024.33 | 03-OCT-13:20 | 45610.33 | 0.00 |
November | 0.00 | 0.00 | 0.989978E+10 | 0.884994E+10 | 38322.94 | 28-NOV-14:00 | 38322.94 | 0.00 |
December | 0.00 | 0.00 | 0.103900E+11 | 0.101055E+11 | 40786.32 | 05-DEC-15:10 | 40786.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.257622E+12 | 0.194058E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.497463E+10 | 0.426240E+10 | 35396.92 | 30510.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.518214E+11 | 0.336777E+11 | 85490.55 | 49625.78 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.737625E+10 | 0.668972E+10 | 35065.64 | 18-JAN-14:00 | 35065.64 | 0.00 |
February | 0.00 | 0.00 | 0.426830E+10 | 0.363724E+10 | 29686.97 | 01-FEB-12:00 | 29686.97 | 0.00 |
March | 0.00 | 0.00 | 0.538280E+10 | 0.424005E+10 | 36941.19 | 23-MAR-15:00 | 28262.42 | 0.00 |
April | 0.00 | 0.00 | 0.120326E+11 | 0.101255E+11 | 42197.45 | 26-APR-14:10 | 40617.54 | 0.00 |
May | 0.00 | 0.00 | 0.123616E+11 | 0.104510E+11 | 33080.45 | 03-MAY-13:00 | 33080.45 | 0.00 |
June | 0.00 | 0.00 | 0.232135E+11 | 0.176724E+11 | 50651.62 | 29-JUN-13:00 | 32731.44 | 0.00 |
July | 0.00 | 0.00 | 0.389398E+11 | 0.262840E+11 | 75003.02 | 31-JUL-15:40 | 43860.66 | 0.00 |
August | 0.00 | 0.00 | 0.449150E+11 | 0.295294E+11 | 72968.82 | 18-AUG-15:50 | 42301.22 | 0.00 |
September | 0.00 | 0.00 | 0.274047E+11 | 0.199899E+11 | 57643.50 | 29-SEP-15:20 | 57643.50 | 0.00 |
October | 0.00 | 0.00 | 0.297558E+11 | 0.238085E+11 | 68684.10 | 03-OCT-13:20 | 41302.23 | 0.00 |
November | 0.00 | 0.00 | 0.829221E+10 | 0.732422E+10 | 33037.53 | 28-NOV-14:00 | 33037.53 | 0.00 |
December | 0.00 | 0.00 | 0.869937E+10 | 0.841216E+10 | 34874.01 | 05-DEC-15:10 | 34874.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222642E+12 | 0.168164E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.426830E+10 | 0.363724E+10 | 29686.97 | 28262.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449150E+11 | 0.295294E+11 | 75003.02 | 57643.50 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.689647E+10 | 0.609142E+10 | 36188.83 | 18-JAN-13:30 | 36188.83 | 0.00 |
February | 0.00 | 0.00 | 0.401999E+10 | 0.332838E+10 | 29853.10 | 01-FEB-12:00 | 29853.10 | 0.00 |
March | 0.00 | 0.00 | 0.533853E+10 | 0.409256E+10 | 38923.81 | 23-MAR-15:00 | 29354.94 | 0.00 |
April | 0.00 | 0.00 | 0.125730E+11 | 0.102436E+11 | 50804.43 | 26-APR-14:00 | 48929.24 | 0.00 |
May | 0.00 | 0.00 | 0.128167E+11 | 0.104970E+11 | 36237.93 | 03-MAY-13:00 | 36237.93 | 0.00 |
June | 0.00 | 0.00 | 0.245647E+11 | 0.181937E+11 | 55658.42 | 29-JUN-13:00 | 35682.16 | 0.00 |
July | 0.00 | 0.00 | 0.414526E+11 | 0.274971E+11 | 85880.04 | 31-JUL-15:10 | 52233.75 | 0.00 |
August | 0.00 | 0.00 | 0.475406E+11 | 0.306138E+11 | 84735.22 | 18-AUG-15:30 | 50628.33 | 0.00 |
September | 0.00 | 0.00 | 0.278671E+11 | 0.200089E+11 | 66822.86 | 29-SEP-13:40 | 66822.86 | 0.00 |
October | 0.00 | 0.00 | 0.296532E+11 | 0.234397E+11 | 72838.25 | 03-OCT-13:10 | 44707.17 | 0.00 |
November | 0.00 | 0.00 | 0.760851E+10 | 0.655144E+10 | 34378.12 | 19-NOV-12:52 | 34378.12 | 0.00 |
December | 0.00 | 0.00 | 0.800349E+10 | 0.768509E+10 | 37181.87 | 05-DEC-15:00 | 37181.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228335E+12 | 0.168243E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.401999E+10 | 0.332838E+10 | 29853.10 | 29354.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.475406E+11 | 0.306138E+11 | 85880.04 | 66822.86 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 694.47 | 119620.87 | 10-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 357.81 | 72132.10 | 27-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 593.87 | 118772.35 | 30-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 150.69 | 61147.59 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 107.77 | 18691.25 | 15-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 35.45 | 8281.85 | 22-JUN-06:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.89 | 2593.17 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2.69 | 4218.47 | 28-AUG-06:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.28 | 8671.10 | 19-SEP-06:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 36.22 | 27268.99 | 30-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 132.12 | 44090.88 | 27-NOV-07:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 382.12 | 77926.12 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 209.11 | ||||
Minimum of Months | 0.00 | 0.00 | 1.89 | 2593.17 | ||
Maximum of Months | 0.00 | 0.00 | 694.47 | 119620.87 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1492.31 | 5440.27 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1503.33 | 5440.51 | 02-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1590.60 | 5413.55 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1448.47 | 5315.59 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1466.11 | 5198.24 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1471.63 | 5065.35 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1321.73 | 4962.73 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1460.09 | 4952.93 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1374.23 | 5036.79 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1404.02 | 5169.43 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1463.72 | 5298.08 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1432.51 | 5394.35 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||
Minimum of Months | 0.00 | 0.00 | 1321.73 | 4952.93 | ||
Maximum of Months | 0.00 | 0.00 | 1590.60 | 5440.51 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.239781E+10 | 0.35 | 4862.48 | 18-JAN-15:30 | 1.16 |
February | 0.206541E+10 | 0.34 | 4293.30 | 03-FEB-15:10 | 1.09 |
March | 0.229847E+10 | 0.35 | 4510.58 | 23-MAR-15:20 | 1.10 |
April | 0.265857E+10 | 0.37 | 5146.48 | 26-APR-14:10 | 1.20 |
May | 0.282339E+10 | 0.38 | 4516.42 | 04-MAY-14:10 | 1.11 |
June | 0.323450E+10 | 0.42 | 5021.25 | 26-JUN-16:00 | 1.18 |
July | 0.392362E+10 | 0.45 | 6995.66 | 31-JUL-14:10 | 1.45 |
August | 0.446612E+10 | 0.49 | 6641.45 | 14-AUG-15:20 | 1.40 |
September | 0.361097E+10 | 0.44 | 6292.92 | 11-SEP-14:10 | 1.35 |
October | 0.364514E+10 | 0.43 | 7335.68 | 16-OCT-08:00 | 1.51 |
November | 0.270919E+10 | 0.37 | 4938.28 | 13-NOV-15:10 | 1.17 |
December | 0.244536E+10 | 0.35 | 4771.84 | 22-DEC-07:02 | 1.15 |
Annual Sum or Average | 0.362786E+11 | 0.40 | |||
Minimum of Months | 0.206541E+10 | 0.34 | 4293.30 | 1.09 | |
Maximum of Months | 0.446612E+10 | 0.49 | 7335.68 | 1.51 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173847E+10 | 0.31 | 3585.55 | 18-JAN-15:40 | 1.01 |
February | 0.156436E+10 | 0.32 | 3636.84 | 03-FEB-15:10 | 1.03 |
March | 0.176318E+10 | 0.33 | 4196.64 | 23-MAR-15:20 | 1.11 |
April | 0.219804E+10 | 0.36 | 4663.26 | 26-APR-14:30 | 1.19 |
May | 0.222703E+10 | 0.36 | 4096.00 | 03-MAY-15:20 | 1.10 |
June | 0.267364E+10 | 0.40 | 4478.86 | 30-JUN-16:00 | 1.15 |
July | 0.319155E+10 | 0.43 | 5711.50 | 31-JUL-14:50 | 1.34 |
August | 0.365808E+10 | 0.47 | 5521.87 | 18-AUG-15:00 | 1.31 |
September | 0.286004E+10 | 0.41 | 7010.51 | 29-SEP-16:00 | 1.53 |
October | 0.276065E+10 | 0.39 | 7697.27 | 16-OCT-16:00 | 1.63 |
November | 0.191610E+10 | 0.33 | 3399.38 | 10-NOV-15:00 | 0.98 |
December | 0.177009E+10 | 0.32 | 3608.70 | 19-DEC-15:40 | 1.03 |
Annual Sum or Average | 0.283212E+11 | 0.37 | |||
Minimum of Months | 0.156436E+10 | 0.31 | 3399.38 | 0.98 | |
Maximum of Months | 0.365808E+10 | 0.47 | 7697.27 | 1.63 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158381E+10 | 0.29 | 3282.48 | 18-JAN-15:30 | 0.89 |
February | 0.143072E+10 | 0.30 | 3027.03 | 03-FEB-14:50 | 0.86 |
March | 0.166055E+10 | 0.31 | 3939.17 | 23-MAR-15:20 | 0.99 |
April | 0.205093E+10 | 0.33 | 4798.86 | 26-APR-14:30 | 1.11 |
May | 0.207477E+10 | 0.33 | 4214.21 | 03-MAY-15:20 | 1.03 |
June | 0.252981E+10 | 0.37 | 4519.20 | 30-JUN-16:00 | 1.07 |
July | 0.301763E+10 | 0.39 | 5760.89 | 31-JUL-14:40 | 1.24 |
August | 0.340460E+10 | 0.42 | 5608.93 | 17-AUG-15:20 | 1.22 |
September | 0.255932E+10 | 0.37 | 7373.35 | 29-SEP-16:00 | 1.45 |
October | 0.242622E+10 | 0.35 | 7576.25 | 16-OCT-16:00 | 1.48 |
November | 0.165274E+10 | 0.30 | 3173.28 | 10-NOV-14:40 | 0.87 |
December | 0.160314E+10 | 0.30 | 3205.37 | 19-DEC-15:30 | 0.89 |
Annual Sum or Average | 0.259942E+11 | 0.34 | |||
Minimum of Months | 0.143072E+10 | 0.29 | 3027.03 | 0.86 | |
Maximum of Months | 0.340460E+10 | 0.42 | 7576.25 | 1.48 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 13615040.44 | 12253536.40 | 401.78 | 03-JAN-07:02 | 361.60 | 361.60 | 35.58 | 1.17 |
February | 7423985.07 | 6681586.56 | 311.34 | 27-FEB-07:03 | 280.21 | 280.21 | 26.87 | 0.52 |
March | 13245445.85 | 11920901.27 | 394.29 | 30-MAR-06:02 | 354.86 | 354.86 | 34.00 | 1.09 |
April | 4106615.70 | 3695954.13 | 331.68 | 01-APR-06:03 | 298.51 | 298.51 | 35.49 | 0.60 |
May | 3215150.64 | 2893635.58 | 160.39 | 15-MAY-06:03 | 144.35 | 144.35 | 37.11 | 0.20 |
June | 969673.18 | 872705.87 | 65.55 | 01-JUN-06:07 | 58.99 | 58.99 | 40.53 | 0.07 |
July | 41115.42 | 37003.87 | 20.97 | 17-JUL-06:10 | 18.87 | 18.87 | 31.48 | 0.02 |
August | 60458.84 | 54412.95 | 35.31 | 28-AUG-06:08 | 31.78 | 31.78 | 32.82 | 0.04 |
September | 286759.00 | 258083.10 | 65.43 | 20-SEP-06:20 | 58.88 | 58.88 | 35.00 | 0.07 |
October | 1000969.26 | 900872.34 | 188.77 | 30-OCT-06:02 | 169.89 | 169.89 | 32.84 | 0.24 |
November | 3126001.56 | 2813401.40 | 250.34 | 27-NOV-07:03 | 225.30 | 225.30 | 30.42 | 0.36 |
December | 8166528.54 | 7349875.69 | 347.88 | 26-DEC-07:03 | 313.10 | 313.10 | 32.42 | 0.68 |
Annual Sum or Average | 55257743.51 | 49731969.16 | ||||||
Minimum of Months | 41115.42 | 37003.87 | 20.97 | 18.87 | 18.87 | 26.87 | 0.02 | |
Maximum of Months | 13615040.44 | 12253536.40 | 401.78 | 361.60 | 361.60 | 40.53 | 1.17 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.36 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.32 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.33 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.30 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.56 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.50 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.55 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.57 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.56 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.35 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.45 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.39 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.30 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.36 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 694.47 | 119620.87 | 10-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 37.09 | 37.09 | 357.81 | 72132.10 | 27-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.52 | 28.52 | 593.87 | 118772.35 | 30-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 40.60 | 40.60 | 150.69 | 61147.59 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33.37 | 33.37 | 107.77 | 18691.25 | 15-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 40.68 | 40.68 | 35.45 | 8281.85 | 22-JUN-06:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.84 | 30.84 | 1.89 | 2593.17 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 31.54 | 31.54 | 2.69 | 4218.47 | 28-AUG-06:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.47 | 31.47 | 12.28 | 8671.10 | 19-SEP-06:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 39.88 | 39.88 | 36.22 | 27268.99 | 30-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.62 | 32.62 | 132.12 | 44090.88 | 27-NOV-07:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 37.34 | 37.34 | 382.12 | 77926.12 | 26-DEC-07:03 |
Annual Sum or Average | 0.00 | 209.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.52 | 28.52 | 1.89 | 2593.17 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 694.47 | 119620.87 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.36 | 58.36 | 1492.31 | 5440.27 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.92 | 57.92 | 1503.33 | 5440.51 | 02-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.93 | 57.93 | 1590.60 | 5413.55 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.97 | 57.97 | 1448.47 | 5315.59 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.43 | 58.43 | 1466.11 | 5198.24 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.07 | 58.07 | 1471.63 | 5065.35 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.11 | 58.11 | 1321.73 | 4962.73 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.13 | 58.13 | 1460.09 | 4952.93 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.11 | 58.11 | 1374.23 | 5036.79 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.29 | 57.29 | 1404.02 | 5169.43 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.03 | 58.03 | 1463.72 | 5298.08 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.98 | 57.98 | 1432.51 | 5394.35 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.29 | 57.29 | 1321.73 | 4952.93 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 1590.60 | 5440.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.474874E+09 | 0.00 | 0.00 | 0.440624E+10 | 0.00 | 0.00 |
February | 0.419022E+09 | 0.00 | 0.00 | 0.325066E+10 | 0.00 | 0.00 |
March | 0.782036E+09 | 0.00 | 0.00 | 0.368103E+10 | 0.00 | 0.00 |
April | 0.326413E+09 | 0.00 | 0.00 | 0.567871E+10 | 0.00 | 0.00 |
May | 0.279460E+09 | 0.00 | 0.00 | 0.609785E+10 | 0.00 | 0.00 |
June | 96251390.83 | 0.00 | 0.00 | 0.909931E+10 | 0.00 | 0.00 |
July | 3401006.29 | 0.00 | 0.00 | 0.137020E+11 | 0.00 | 0.00 |
August | 5406580.65 | 0.00 | 0.00 | 0.157019E+11 | 0.00 | 0.00 |
September | 28064411.63 | 0.00 | 0.00 | 0.107873E+11 | 0.00 | 0.00 |
October | 82138748.25 | 0.00 | 0.00 | 0.116360E+11 | 0.00 | 0.00 |
November | 0.192407E+09 | 0.00 | 0.00 | 0.499922E+10 | 0.00 | 0.00 |
December | 0.339869E+09 | 0.00 | 0.00 | 0.480123E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.302934E+10 | 0.00 | 0.00 | 0.938414E+11 | 0.00 | 0.00 |
Minimum of Months | 3401006.29 | 0.00 | 0.00 | 0.325066E+10 | 0.00 | 0.00 |
Maximum of Months | 0.782036E+09 | 0.00 | 0.00 | 0.157019E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.267905E+09 | 0.00 | 0.00 | 0.346054E+10 | 0.00 | 0.00 |
February | 24879045.99 | 0.00 | 0.00 | 0.258707E+10 | 0.00 | 0.00 |
March | 0.144236E+09 | 0.00 | 0.00 | 0.301898E+10 | 0.00 | 0.00 |
April | 7220614.40 | 0.00 | 0.00 | 0.496216E+10 | 0.00 | 0.00 |
May | 22721.17 | 0.00 | 0.00 | 0.510372E+10 | 0.00 | 0.00 |
June | 298804.85 | 0.00 | 0.00 | 0.786013E+10 | 0.00 | 0.00 |
July | 727085.78 | 0.00 | 0.00 | 0.117155E+11 | 0.00 | 0.00 |
August | 980304.37 | 0.00 | 0.00 | 0.134339E+11 | 0.00 | 0.00 |
September | 353176.05 | 0.00 | 0.00 | 0.906088E+10 | 0.00 | 0.00 |
October | 211124.86 | 0.00 | 0.00 | 0.955855E+10 | 0.00 | 0.00 |
November | 692179.02 | 0.00 | 0.00 | 0.385267E+10 | 0.00 | 0.00 |
December | 84137253.24 | 0.00 | 0.00 | 0.376533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.531664E+09 | 0.00 | 0.00 | 0.783794E+11 | 0.00 | 0.00 |
Minimum of Months | 22721.17 | 0.00 | 0.00 | 0.258707E+10 | 0.00 | 0.00 |
Maximum of Months | 0.267905E+09 | 0.00 | 0.00 | 0.134339E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.114112E+10 | 0.00 | 0.00 | 0.322399E+10 | 0.00 | 0.00 |
February | 0.432938E+09 | 0.00 | 0.00 | 0.241105E+10 | 0.00 | 0.00 |
March | 0.673304E+09 | 0.00 | 0.00 | 0.291796E+10 | 0.00 | 0.00 |
April | 64056860.37 | 0.00 | 0.00 | 0.496031E+10 | 0.00 | 0.00 |
May | 9460256.47 | 0.00 | 0.00 | 0.507693E+10 | 0.00 | 0.00 |
June | 303746.40 | 0.00 | 0.00 | 0.804502E+10 | 0.00 | 0.00 |
July | 681393.58 | 0.00 | 0.00 | 0.121325E+11 | 0.00 | 0.00 |
August | 900422.65 | 0.00 | 0.00 | 0.137894E+11 | 0.00 | 0.00 |
September | 292948.83 | 0.00 | 0.00 | 0.892324E+10 | 0.00 | 0.00 |
October | 18610807.86 | 0.00 | 0.00 | 0.927808E+10 | 0.00 | 0.00 |
November | 0.150669E+09 | 0.00 | 0.00 | 0.346928E+10 | 0.00 | 0.00 |
December | 0.611645E+09 | 0.00 | 0.00 | 0.348007E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.310398E+10 | 0.00 | 0.00 | 0.777078E+11 | 0.00 | 0.00 |
Minimum of Months | 292948.83 | 0.00 | 0.00 | 0.241105E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114112E+10 | 0.00 | 0.00 | 0.137894E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.239781E+10 | 0.869492E+10 | 0.474874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206541E+10 | 0.497463E+10 | 0.419022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229847E+10 | 0.594638E+10 | 0.782036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265857E+10 | 0.132225E+11 | 0.326413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282339E+10 | 0.141724E+11 | 0.279460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323450E+10 | 0.263716E+11 | 96251390.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392362E+10 | 0.448842E+11 | 3401006.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.446612E+10 | 0.518214E+11 | 5406580.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361097E+10 | 0.319440E+11 | 28064411.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364514E+10 | 0.353003E+11 | 82138748.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270919E+10 | 0.989978E+10 | 0.192407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244536E+10 | 0.103900E+11 | 0.339869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362786E+11 | 0.257622E+12 | 0.302934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206541E+10 | 0.497463E+10 | 3401006.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446612E+10 | 0.518214E+11 | 0.782036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173847E+10 | 0.737625E+10 | 0.267905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156436E+10 | 0.426830E+10 | 24879045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176318E+10 | 0.538280E+10 | 0.144236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219804E+10 | 0.120326E+11 | 7220614.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222703E+10 | 0.123616E+11 | 22721.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267364E+10 | 0.232135E+11 | 298804.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319155E+10 | 0.389398E+11 | 727085.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.365808E+10 | 0.449150E+11 | 980304.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286004E+10 | 0.274047E+11 | 353176.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276065E+10 | 0.297558E+11 | 211124.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191610E+10 | 0.829221E+10 | 692179.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177009E+10 | 0.869937E+10 | 84137253.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283212E+11 | 0.222642E+12 | 0.531664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156436E+10 | 0.426830E+10 | 22721.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365808E+10 | 0.449150E+11 | 0.267905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158381E+10 | 0.689647E+10 | 0.114112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143072E+10 | 0.401999E+10 | 0.432938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166055E+10 | 0.533853E+10 | 0.673304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205093E+10 | 0.125730E+11 | 64056860.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207477E+10 | 0.128167E+11 | 9460256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252981E+10 | 0.245647E+11 | 303746.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.301763E+10 | 0.414526E+11 | 681393.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340460E+10 | 0.475406E+11 | 900422.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255932E+10 | 0.278671E+11 | 292948.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242622E+10 | 0.296532E+11 | 18610807.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165274E+10 | 0.760851E+10 | 0.150669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160314E+10 | 0.800349E+10 | 0.611645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259942E+11 | 0.228335E+12 | 0.310398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143072E+10 | 0.401999E+10 | 292948.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.340460E+10 | 0.475406E+11 | 0.114112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.239781E+10 | 0.474874E+09 | 0.00 | 0.00 | 0.200843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206541E+10 | 0.419022E+09 | 0.00 | 0.00 | 0.118524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229847E+10 | 0.782036E+09 | 0.00 | 0.00 | 0.138256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265857E+10 | 0.326413E+09 | 0.00 | 0.00 | 0.302014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282339E+10 | 0.279460E+09 | 0.00 | 0.00 | 0.327445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.323450E+10 | 96251390.83 | 0.00 | 0.00 | 0.586481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.392362E+10 | 3401006.29 | 0.00 | 0.00 | 0.977840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.446612E+10 | 5406580.65 | 0.00 | 0.00 | 0.112358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361097E+10 | 28064411.63 | 0.00 | 0.00 | 0.717629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364514E+10 | 82138748.25 | 0.00 | 0.00 | 0.799082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270919E+10 | 0.192407E+09 | 0.00 | 0.00 | 0.229003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244536E+10 | 0.339869E+09 | 0.00 | 0.00 | 0.235587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362786E+11 | 0.302934E+10 | 0.00 | 0.00 | 0.575628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206541E+10 | 3401006.29 | 0.00 | 0.00 | 0.118524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.446612E+10 | 0.782036E+09 | 0.00 | 0.00 | 0.112358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173847E+10 | 0.267905E+09 | 0.00 | 0.00 | 0.172206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156436E+10 | 24879045.99 | 0.00 | 0.00 | 0.102271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176318E+10 | 0.144236E+09 | 0.00 | 0.00 | 0.125580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219804E+10 | 7220614.40 | 0.00 | 0.00 | 0.276412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222703E+10 | 22721.17 | 0.00 | 0.00 | 0.287669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267364E+10 | 298804.85 | 0.00 | 0.00 | 0.518649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.319155E+10 | 727085.78 | 0.00 | 0.00 | 0.852394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.365808E+10 | 980304.37 | 0.00 | 0.00 | 0.977581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286004E+10 | 353176.05 | 0.00 | 0.00 | 0.620084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276065E+10 | 211124.86 | 0.00 | 0.00 | 0.679790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191610E+10 | 692179.02 | 0.00 | 0.00 | 0.193657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177009E+10 | 84137253.24 | 0.00 | 0.00 | 0.199524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283212E+11 | 0.531664E+09 | 0.00 | 0.00 | 0.500582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156436E+10 | 22721.17 | 0.00 | 0.00 | 0.102271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365808E+10 | 0.267905E+09 | 0.00 | 0.00 | 0.977581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158381E+10 | 0.114112E+10 | 0.00 | 0.00 | 0.164017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143072E+10 | 0.432938E+09 | 0.00 | 0.00 | 0.980324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166055E+10 | 0.673304E+09 | 0.00 | 0.00 | 0.125741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205093E+10 | 64056860.37 | 0.00 | 0.00 | 0.290938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207477E+10 | 9460256.47 | 0.00 | 0.00 | 0.300216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252981E+10 | 303746.40 | 0.00 | 0.00 | 0.551521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.301763E+10 | 681393.58 | 0.00 | 0.00 | 0.911490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340460E+10 | 900422.65 | 0.00 | 0.00 | 0.103848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255932E+10 | 292948.83 | 0.00 | 0.00 | 0.636392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242622E+10 | 18610807.86 | 0.00 | 0.00 | 0.685186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165274E+10 | 0.150669E+09 | 0.00 | 0.00 | 0.181654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160314E+10 | 0.611645E+09 | 0.00 | 0.00 | 0.187693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259942E+11 | 0.310398E+10 | 0.00 | 0.00 | 0.517136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143072E+10 | 292948.83 | 0.00 | 0.00 | 0.980324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.340460E+10 | 0.114112E+10 | 0.00 | 0.00 | 0.103848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115276E+10 | 32652881.97 | 0.00 | 37244034.11 | 0.00 | 0.00 | 0.164403E+11 | 0.00 | 0.84 |
February | 0.107852E+10 | 10685781.75 | 0.00 | 34253184.65 | 0.00 | 0.00 | 0.165820E+11 | 0.00 | 0.86 |
March | 0.832222E+09 | 0.00 | 0.00 | 40240505.24 | 14875681.75 | 0.00 | 0.195286E+11 | 0.00 | 0.87 |
April | 0.666436E+09 | 12433023.50 | 0.00 | 38360988.14 | 18916803.40 | 0.00 | 0.162631E+11 | 0.00 | 0.99 |
May | 0.686847E+09 | 16222964.06 | 0.00 | 41844285.35 | 0.00 | 0.00 | 0.177600E+11 | 0.00 | 1.09 |
June | 0.403173E+09 | 0.285549E+09 | 0.00 | 40089968.18 | 16662196.03 | 0.00 | 0.125578E+11 | 0.00 | 1.21 |
July | 0.445554E+09 | 0.226601E+10 | 0.00 | 26905345.30 | 0.179136E+09 | 0.00 | 0.551424E+10 | 0.00 | 1.13 |
August | 0.185644E+09 | 0.279978E+10 | 0.00 | 26844943.01 | 0.228244E+09 | 0.00 | 0.524109E+10 | 0.00 | 1.21 |
September | 0.399591E+09 | 0.678802E+09 | 0.00 | 35486499.89 | 32232726.64 | 0.00 | 0.102914E+11 | 0.00 | 1.12 |
October | 0.411522E+09 | 0.135912E+10 | 0.00 | 32073981.81 | 0.145657E+09 | 0.00 | 0.102671E+11 | 0.00 | 1.02 |
November | 0.808222E+09 | 3603713.97 | 0.00 | 41104019.01 | 7480986.74 | 0.00 | 0.185272E+11 | 0.00 | 0.98 |
December | 0.134160E+10 | 2753679.32 | 0.00 | 38259558.39 | 0.00 | 0.00 | 0.159403E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.841209E+10 | 0.746760E+10 | 0.00 | 0.432707E+09 | 0.643206E+09 | 0.00 | 0.164913E+12 | 0.00 | 1.01 |
Minimum of Months | 0.185644E+09 | 0.00 | 0.00 | 26844943.01 | 0.00 | 0.00 | 0.524109E+10 | 0.00 | 0.84 |
Maximum of Months | 0.134160E+10 | 0.279978E+10 | 0.00 | 41844285.35 | 0.228244E+09 | 0.00 | 0.195286E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.524091E+10 | 3064654.40 | 0.00 | 10955350.95 | 21858052.07 | 0.00 | 0.568875E+10 | 0.00 | 0.51 |
February | 0.472084E+10 | 5917017.04 | 0.00 | 11212118.01 | 0.00 | 0.00 | 0.655206E+10 | 0.00 | 0.55 |
March | 0.512270E+10 | 0.00 | 0.00 | 12898898.95 | 20092621.20 | 0.00 | 0.779997E+10 | 0.00 | 0.55 |
April | 0.291921E+10 | 3176606.02 | 0.00 | 17612230.73 | 43525617.01 | 0.00 | 0.832931E+10 | 0.00 | 0.67 |
May | 0.251309E+10 | 12662315.94 | 0.00 | 20385805.11 | 17378.11 | 0.00 | 0.977459E+10 | 0.00 | 0.72 |
June | 0.116525E+10 | 0.183772E+09 | 0.00 | 21947823.23 | 31846714.62 | 0.00 | 0.760793E+10 | 0.00 | 0.82 |
July | 0.809133E+09 | 0.150670E+10 | 0.00 | 15294897.55 | 0.181043E+09 | 0.00 | 0.327176E+10 | 0.00 | 0.78 |
August | 0.535755E+09 | 0.186439E+10 | 0.00 | 15306475.38 | 0.259196E+09 | 0.00 | 0.309290E+10 | 0.00 | 0.83 |
September | 0.100787E+10 | 0.482089E+09 | 0.00 | 18238594.71 | 40706867.12 | 0.00 | 0.598053E+10 | 0.00 | 0.75 |
October | 0.141808E+10 | 0.936944E+09 | 0.00 | 15451940.93 | 0.142420E+09 | 0.00 | 0.544863E+10 | 0.00 | 0.68 |
November | 0.366471E+10 | 1543778.61 | 0.00 | 15831654.22 | 10402431.62 | 0.00 | 0.830770E+10 | 0.00 | 0.60 |
December | 0.491999E+10 | 1272190.34 | 0.00 | 12350637.56 | 1219983.20 | 0.00 | 0.586757E+10 | 0.00 | 0.52 |
Annual Sum or Average | 0.340375E+11 | 0.500154E+10 | 0.00 | 0.187486E+09 | 0.752328E+09 | 0.00 | 0.777217E+11 | 0.00 | 0.67 |
Minimum of Months | 0.535755E+09 | 0.00 | 0.00 | 10955350.95 | 0.00 | 0.00 | 0.309290E+10 | 0.00 | 0.51 |
Maximum of Months | 0.524091E+10 | 0.186439E+10 | 0.00 | 21947823.23 | 0.259196E+09 | 0.00 | 0.977459E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.662405E+10 | 1337390.01 | 0.00 | 5852547.26 | 19764505.64 | 23557849.35 | 0.336929E+10 | 0.00 | 0.49 |
February | 0.596865E+10 | 2074706.63 | 0.00 | 6570484.12 | 0.00 | 1279858.01 | 0.443290E+10 | 0.00 | 0.52 |
March | 0.700361E+10 | 0.00 | 0.00 | 7418375.27 | 12455002.17 | 1605401.08 | 0.521422E+10 | 0.00 | 0.53 |
April | 0.393771E+10 | 257052.15 | 0.00 | 14687063.71 | 18993155.14 | 0.00 | 0.718203E+10 | 0.00 | 0.66 |
May | 0.375796E+10 | 3850921.48 | 0.00 | 17381677.62 | 0.00 | 0.00 | 0.836111E+10 | 0.00 | 0.71 |
June | 0.195018E+10 | 89776823.37 | 0.00 | 19910247.24 | 6433498.92 | 0.00 | 0.694920E+10 | 0.00 | 0.83 |
July | 0.121777E+10 | 0.122916E+10 | 0.00 | 13472369.14 | 0.164489E+09 | 0.00 | 0.287100E+10 | 0.00 | 0.81 |
August | 0.827002E+09 | 0.164406E+10 | 0.00 | 13675365.02 | 0.238563E+09 | 0.00 | 0.260106E+10 | 0.00 | 0.87 |
September | 0.192026E+10 | 0.336020E+09 | 0.00 | 15052677.09 | 51901570.56 | 0.00 | 0.477528E+10 | 0.00 | 0.73 |
October | 0.266346E+10 | 0.801230E+09 | 0.00 | 10895731.34 | 0.158585E+09 | 0.00 | 0.343948E+10 | 0.00 | 0.65 |
November | 0.514830E+10 | 0.00 | 0.00 | 9642572.70 | 2937874.21 | 0.00 | 0.553100E+10 | 0.00 | 0.56 |
December | 0.618404E+10 | 87389.13 | 0.00 | 6464084.62 | 807321.67 | 787861.41 | 0.351506E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.472030E+11 | 0.410785E+10 | 0.00 | 0.141023E+09 | 0.674929E+09 | 27230969.85 | 0.582416E+11 | 0.00 | 0.66 |
Minimum of Months | 0.827002E+09 | 0.00 | 0.00 | 5852547.26 | 0.00 | 0.00 | 0.260106E+10 | 0.00 | 0.49 |
Maximum of Months | 0.700361E+10 | 0.164406E+10 | 0.00 | 19910247.24 | 0.238563E+09 | 23557849.35 | 0.836111E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164755E+10 | 244983.86 | 0.00 | 462618.97 | 4198670.40 | 0.160567E+09 | 0.240175E+09 | 0.00 | 0.47 |
February | 0.158868E+10 | 422904.63 | 0.00 | 545690.00 | 0.00 | 50353809.67 | 0.440806E+09 | 0.00 | 0.49 |
March | 0.189257E+10 | 0.00 | 0.00 | 783774.78 | 2623956.11 | 70617858.16 | 0.541352E+09 | 0.00 | 0.51 |
April | 0.117529E+10 | 61032.15 | 0.00 | 2439812.41 | 4001380.72 | 8337722.87 | 0.109971E+10 | 0.00 | 0.64 |
May | 0.105605E+10 | 925056.43 | 0.00 | 3428304.14 | 0.00 | 193840.45 | 0.153565E+10 | 0.00 | 0.73 |
June | 0.553257E+09 | 23210802.26 | 0.00 | 4711149.95 | 1355376.63 | 0.00 | 0.147032E+10 | 0.00 | 0.92 |
July | 0.321871E+09 | 0.340676E+09 | 0.00 | 2961340.88 | 34462112.78 | 0.00 | 0.595481E+09 | 0.00 | 0.92 |
August | 0.294784E+09 | 0.417441E+09 | 0.00 | 2573719.86 | 53491171.03 | 0.00 | 0.427232E+09 | 0.00 | 0.94 |
September | 0.642657E+09 | 88703281.96 | 0.00 | 2647160.87 | 11715565.22 | 0.00 | 0.734921E+09 | 0.00 | 0.74 |
October | 0.787325E+09 | 0.196766E+09 | 0.00 | 1677080.52 | 36544824.60 | 2019580.04 | 0.453295E+09 | 0.00 | 0.65 |
November | 0.151057E+10 | 0.00 | 0.00 | 830261.99 | 618936.30 | 27996144.55 | 0.540045E+09 | 0.00 | 0.51 |
December | 0.164525E+10 | 1808.18 | 0.00 | 422081.33 | 186684.91 | 93774729.19 | 0.233772E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.131159E+11 | 0.106845E+10 | 0.00 | 23482995.72 | 0.149199E+09 | 0.413860E+09 | 0.831276E+10 | 0.00 | 0.67 |
Minimum of Months | 0.294784E+09 | 0.00 | 0.00 | 422081.33 | 0.00 | 0.00 | 0.233772E+09 | 0.00 | 0.47 |
Maximum of Months | 0.189257E+10 | 0.417441E+09 | 0.00 | 4711149.95 | 53491171.03 | 0.160567E+09 | 0.153565E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111412E+10 | 965494.04 | 0.00 | 968610.46 | 2764203.14 | 60326047.74 | 0.586463E+09 | 0.00 | 0.65 |
February | 0.109859E+10 | 397027.48 | 0.00 | 1256146.48 | 0.00 | 18474191.26 | 0.746374E+09 | 0.00 | 0.70 |
March | 0.123187E+10 | 307289.50 | 0.00 | 1797505.18 | 2045496.19 | 27463501.32 | 0.984797E+09 | 0.00 | 0.76 |
April | 0.759228E+09 | 1033520.27 | 0.00 | 3920842.29 | 2696044.41 | 1636721.83 | 0.165885E+10 | 0.00 | 1.12 |
May | 0.795568E+09 | 1176686.31 | 0.00 | 3977360.95 | 0.00 | 0.00 | 0.171194E+10 | 0.00 | 1.14 |
June | 0.478894E+09 | 23211933.13 | 0.00 | 4898495.81 | 482949.25 | 0.00 | 0.137532E+10 | 0.00 | 1.40 |
July | 0.243896E+09 | 0.341875E+09 | 0.00 | 4067245.31 | 14651567.90 | 0.00 | 0.688969E+09 | 0.00 | 1.51 |
August | 0.221073E+09 | 0.513096E+09 | 0.00 | 3294033.70 | 21063431.50 | 0.00 | 0.536163E+09 | 0.00 | 1.60 |
September | 0.500513E+09 | 82037556.31 | 0.00 | 3301197.26 | 8319717.64 | 0.00 | 0.847508E+09 | 0.00 | 1.16 |
October | 0.549058E+09 | 0.173392E+09 | 0.00 | 2104748.42 | 31522331.14 | 1469589.49 | 0.617610E+09 | 0.00 | 0.93 |
November | 0.974961E+09 | 3519.81 | 0.00 | 1538672.59 | 514147.21 | 4754580.01 | 0.847794E+09 | 0.00 | 0.72 |
December | 0.118271E+10 | 35116.93 | 0.00 | 976463.44 | 142253.81 | 23689629.96 | 0.465672E+09 | 0.00 | 0.65 |
Annual Sum or Average | 0.915049E+10 | 0.113753E+10 | 0.00 | 32101321.90 | 84202142.18 | 0.137814E+09 | 0.110675E+11 | 0.00 | 1.03 |
Minimum of Months | 0.221073E+09 | 3519.81 | 0.00 | 968610.46 | 0.00 | 0.00 | 0.465672E+09 | 0.00 | 0.65 |
Maximum of Months | 0.123187E+10 | 0.513096E+09 | 0.00 | 4898495.81 | 31522331.14 | 60326047.74 | 0.171194E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.890402E+09 | 19507290.02 | 0.00 | 7273693.24 | 401675.25 | 57145693.39 | 0.341018E+10 | 0.00 | 1.12 |
February | 0.104652E+10 | 1634580.63 | 0.00 | 5462323.30 | 0.00 | 20649075.63 | 0.269230E+10 | 0.00 | 0.97 |
March | 0.134217E+10 | 1640390.91 | 0.00 | 4980894.09 | 1731575.28 | 42782926.15 | 0.243538E+10 | 0.00 | 0.88 |
April | 0.100482E+10 | 2256290.41 | 0.00 | 5601630.91 | 2935083.23 | 6972962.30 | 0.230167E+10 | 0.00 | 0.99 |
May | 0.114045E+10 | 1219997.02 | 0.00 | 4263458.69 | 0.00 | 598949.54 | 0.182188E+10 | 0.00 | 0.85 |
June | 0.672033E+09 | 27169831.88 | 0.00 | 4719123.69 | 1428318.89 | 0.00 | 0.143502E+10 | 0.00 | 0.97 |
July | 0.371593E+09 | 0.399265E+09 | 0.00 | 3062501.96 | 34995459.39 | 0.00 | 0.605664E+09 | 0.00 | 1.02 |
August | 0.285564E+09 | 0.621050E+09 | 0.00 | 3825961.51 | 52851711.97 | 0.00 | 0.606071E+09 | 0.00 | 1.28 |
September | 0.514607E+09 | 0.155085E+09 | 0.00 | 6369834.00 | 11242583.85 | 0.00 | 0.160892E+10 | 0.00 | 1.25 |
October | 0.552891E+09 | 0.439619E+09 | 0.00 | 6056865.55 | 10943315.66 | 0.00 | 0.143573E+10 | 0.00 | 1.18 |
November | 0.881750E+09 | 825604.30 | 0.00 | 7643176.13 | 110467.21 | 2109170.17 | 0.345115E+10 | 0.00 | 1.20 |
December | 0.911982E+09 | 877533.44 | 0.00 | 8064999.76 | 0.00 | 16648132.45 | 0.304648E+10 | 0.00 | 1.15 |
Annual Sum or Average | 0.961477E+10 | 0.167015E+10 | 0.00 | 67324462.82 | 0.116640E+09 | 0.146907E+09 | 0.248504E+11 | 0.00 | 1.07 |
Minimum of Months | 0.285564E+09 | 825604.30 | 0.00 | 3062501.96 | 0.00 | 0.00 | 0.605664E+09 | 0.00 | 0.85 |
Maximum of Months | 0.134217E+10 | 0.621050E+09 | 0.00 | 8064999.76 | 52851711.97 | 57145693.39 | 0.345115E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129711E+10 | 3343893.46 | 0.00 | 1200854.37 | 1562114.86 | 0.135268E+09 | 0.689954E+09 | 0.00 | 0.78 |
February | 0.136567E+10 | 511487.47 | 0.00 | 1441539.97 | 0.00 | 46845287.12 | 0.828199E+09 | 0.00 | 0.84 |
March | 0.157800E+10 | 0.00 | 0.00 | 2100481.59 | 2446246.22 | 64149236.04 | 0.111819E+10 | 0.00 | 0.91 |
April | 0.957054E+09 | 535359.01 | 0.00 | 4236017.75 | 3236038.65 | 11097675.77 | 0.175402E+10 | 0.00 | 1.23 |
May | 0.921195E+09 | 593813.85 | 0.00 | 4490109.49 | 0.00 | 856368.49 | 0.192541E+10 | 0.00 | 1.26 |
June | 0.487001E+09 | 18259709.00 | 0.00 | 5555244.30 | 1212456.73 | 0.00 | 0.169356E+10 | 0.00 | 1.55 |
July | 0.245352E+09 | 0.382521E+09 | 0.00 | 4115940.45 | 28584037.01 | 0.00 | 0.764208E+09 | 0.00 | 1.56 |
August | 0.224952E+09 | 0.432387E+09 | 0.00 | 3605584.30 | 44718562.49 | 0.00 | 0.570733E+09 | 0.00 | 1.65 |
September | 0.513688E+09 | 77992099.05 | 0.00 | 3912791.14 | 10892497.66 | 0.00 | 0.107627E+10 | 0.00 | 1.31 |
October | 0.678172E+09 | 0.169595E+09 | 0.00 | 2171138.36 | 35041267.64 | 1915467.47 | 0.591072E+09 | 0.00 | 1.03 |
November | 0.132788E+10 | 3213.14 | 0.00 | 1740374.43 | 573852.64 | 26148029.20 | 0.931302E+09 | 0.00 | 0.91 |
December | 0.133546E+10 | 0.00 | 0.00 | 1205571.98 | 175727.22 | 90014447.79 | 0.597164E+09 | 0.00 | 0.80 |
Annual Sum or Average | 0.109315E+11 | 0.108574E+10 | 0.00 | 35775648.13 | 0.128443E+09 | 0.376294E+09 | 0.125401E+11 | 0.00 | 1.15 |
Minimum of Months | 0.224952E+09 | 0.00 | 0.00 | 1200854.37 | 0.00 | 0.00 | 0.570733E+09 | 0.00 | 0.78 |
Maximum of Months | 0.157800E+10 | 0.432387E+09 | 0.00 | 5555244.30 | 44718562.49 | 0.135268E+09 | 0.192541E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203406E+10 | 195867.70 | 0.00 | 388213.65 | 4834385.87 | 22646381.74 | 0.203328E+09 | 0.00 | 0.48 |
February | 0.208488E+10 | 988604.69 | 0.00 | 127152.22 | 0.00 | 2034112.63 | 0.136906E+09 | 0.00 | 0.49 |
March | 0.233989E+10 | 0.00 | 0.00 | 256571.68 | 3130973.32 | 8963437.92 | 0.207185E+09 | 0.00 | 0.50 |
April | 0.143830E+10 | 423991.59 | 0.00 | 1226156.86 | 5196977.51 | 405302.42 | 0.591678E+09 | 0.00 | 0.55 |
May | 0.124932E+10 | 2009300.88 | 0.00 | 2194798.82 | 0.00 | 0.00 | 0.988162E+09 | 0.00 | 0.61 |
June | 0.679394E+09 | 40061979.44 | 0.00 | 3046465.23 | 3506991.61 | 0.00 | 0.948707E+09 | 0.00 | 0.73 |
July | 0.345424E+09 | 0.345303E+09 | 0.00 | 1989935.05 | 37703796.71 | 0.00 | 0.442710E+09 | 0.00 | 0.75 |
August | 0.388786E+09 | 0.389760E+09 | 0.00 | 1416700.23 | 49686747.76 | 0.00 | 0.279035E+09 | 0.00 | 0.75 |
September | 0.740200E+09 | 92800945.79 | 0.00 | 1901237.17 | 10294066.22 | 0.00 | 0.543219E+09 | 0.00 | 0.65 |
October | 0.853672E+09 | 0.200142E+09 | 0.00 | 1428322.43 | 33897951.36 | 0.00 | 0.439694E+09 | 0.00 | 0.60 |
November | 0.164083E+10 | 223921.86 | 0.00 | 729712.38 | 1778720.33 | 0.00 | 0.591487E+09 | 0.00 | 0.51 |
December | 0.204165E+10 | 251853.29 | 0.00 | 217620.53 | 16598.02 | 1084781.38 | 0.151664E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.158364E+11 | 0.107216E+10 | 0.00 | 14922886.25 | 0.150047E+09 | 35134016.09 | 0.552378E+10 | 0.00 | 0.59 |
Minimum of Months | 0.345424E+09 | 0.00 | 0.00 | 127152.22 | 0.00 | 0.00 | 0.136906E+09 | 0.00 | 0.48 |
Maximum of Months | 0.233989E+10 | 0.389760E+09 | 0.00 | 3046465.23 | 49686747.76 | 22646381.74 | 0.988162E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.986041E+09 | 1646078.65 | 0.00 | 1410591.64 | 2066276.16 | 1057641.07 | 0.763849E+09 | 0.00 | 0.60 |
February | 0.105356E+10 | 1057703.82 | 0.00 | 1259587.18 | 0.00 | 0.00 | 0.698050E+09 | 0.00 | 0.63 |
March | 0.116095E+10 | 0.00 | 0.00 | 1653640.43 | 2258289.94 | 986102.50 | 0.858593E+09 | 0.00 | 0.66 |
April | 0.703037E+09 | 2251998.51 | 0.00 | 3306921.83 | 2782929.33 | 0.00 | 0.131606E+10 | 0.00 | 0.93 |
May | 0.683109E+09 | 2555578.77 | 0.00 | 3445436.31 | 0.00 | 0.00 | 0.139707E+10 | 0.00 | 0.96 |
June | 0.420164E+09 | 43212572.50 | 0.00 | 3789345.40 | 2174757.17 | 0.00 | 0.105043E+10 | 0.00 | 1.14 |
July | 0.165976E+09 | 0.380941E+09 | 0.00 | 3224987.58 | 19227267.72 | 0.00 | 0.626679E+09 | 0.00 | 1.27 |
August | 0.152075E+09 | 0.514029E+09 | 0.00 | 2716907.95 | 23872104.92 | 0.00 | 0.519033E+09 | 0.00 | 1.34 |
September | 0.386173E+09 | 90655004.63 | 0.00 | 2967746.15 | 7143037.73 | 0.00 | 0.803019E+09 | 0.00 | 1.02 |
October | 0.411969E+09 | 0.182046E+09 | 0.00 | 2330669.45 | 22764257.54 | 0.00 | 0.742510E+09 | 0.00 | 0.85 |
November | 0.851662E+09 | 359759.35 | 0.00 | 2108507.04 | 1135694.98 | 0.00 | 0.995918E+09 | 0.00 | 0.69 |
December | 0.104283E+10 | 317903.15 | 0.00 | 1420831.59 | 0.00 | 0.00 | 0.620284E+09 | 0.00 | 0.60 |
Annual Sum or Average | 0.801755E+10 | 0.121907E+10 | 0.00 | 29635172.55 | 83424615.50 | 2043743.57 | 0.103915E+11 | 0.00 | 0.89 |
Minimum of Months | 0.152075E+09 | 0.00 | 0.00 | 1259587.18 | 0.00 | 0.00 | 0.519033E+09 | 0.00 | 0.60 |
Maximum of Months | 0.116095E+10 | 0.514029E+09 | 0.00 | 3789345.40 | 23872104.92 | 1057641.07 | 0.139707E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106360E+10 | 21510946.67 | 0.00 | 5426048.65 | 0.00 | 0.259408E+09 | 0.255372E+10 | 0.00 | 0.95 |
February | 0.134076E+10 | 4136674.23 | 0.00 | 3101327.60 | 0.00 | 0.273523E+09 | 0.150957E+10 | 0.00 | 0.78 |
March | 0.172213E+10 | 1762302.37 | 0.00 | 2160206.81 | 1907422.21 | 0.472830E+09 | 0.927412E+09 | 0.00 | 0.68 |
April | 0.129877E+10 | 3191806.03 | 0.00 | 2587301.34 | 3804554.68 | 0.206316E+09 | 0.926982E+09 | 0.00 | 0.71 |
May | 0.151802E+10 | 2229925.36 | 0.00 | 1498166.25 | 99180.82 | 0.177993E+09 | 0.599579E+09 | 0.00 | 0.63 |
June | 0.104503E+10 | 43896560.32 | 0.00 | 1582627.65 | 3598685.53 | 61446519.09 | 0.431098E+09 | 0.00 | 0.70 |
July | 0.478221E+09 | 0.404106E+09 | 0.00 | 1204053.81 | 38956894.91 | 747320.01 | 0.276298E+09 | 0.00 | 0.76 |
August | 0.332383E+09 | 0.600055E+09 | 0.00 | 1717538.41 | 48832278.93 | 4390699.16 | 0.373414E+09 | 0.00 | 0.96 |
September | 0.537284E+09 | 0.178059E+09 | 0.00 | 4198537.66 | 9830796.96 | 20060141.18 | 0.109266E+10 | 0.00 | 1.01 |
October | 0.479023E+09 | 0.445428E+09 | 0.00 | 5129780.91 | 9416656.24 | 71686700.03 | 0.129833E+10 | 0.00 | 1.04 |
November | 0.955206E+09 | 3628413.00 | 0.00 | 5963745.92 | 176259.81 | 0.138858E+09 | 0.268486E+10 | 0.00 | 1.03 |
December | 0.976992E+09 | 1079872.15 | 0.00 | 6912436.08 | 0.00 | 0.223169E+09 | 0.245924E+10 | 0.00 | 1.02 |
Annual Sum or Average | 0.117474E+11 | 0.170909E+10 | 0.00 | 41481771.09 | 0.116623E+09 | 0.191043E+10 | 0.151332E+11 | 0.00 | 0.86 |
Minimum of Months | 0.332383E+09 | 1079872.15 | 0.00 | 1204053.81 | 0.00 | 747320.01 | 0.276298E+09 | 0.00 | 0.63 |
Maximum of Months | 0.172213E+10 | 0.600055E+09 | 0.00 | 6912436.08 | 48832278.93 | 0.472830E+09 | 0.268486E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131145E+10 | 3675384.48 | 0.00 | 1112065.71 | 997016.09 | 7339614.81 | 0.596951E+09 | 0.00 | 0.65 |
February | 0.128413E+10 | 1274644.53 | 0.00 | 1147729.75 | 0.00 | 193044.00 | 0.638404E+09 | 0.00 | 0.69 |
March | 0.145449E+10 | 0.00 | 0.00 | 1566995.60 | 2405774.63 | 3366515.12 | 0.784053E+09 | 0.00 | 0.73 |
April | 0.733528E+09 | 1858948.75 | 0.00 | 3384869.57 | 2644337.32 | 252780.47 | 0.136551E+10 | 0.00 | 0.96 |
May | 0.672459E+09 | 1900367.28 | 0.00 | 3842923.24 | 0.00 | 0.00 | 0.155163E+10 | 0.00 | 1.01 |
June | 0.347123E+09 | 40153927.22 | 0.00 | 4361856.62 | 1911845.95 | 0.00 | 0.130345E+10 | 0.00 | 1.24 |
July | 0.157630E+09 | 0.419451E+09 | 0.00 | 3336667.33 | 21198741.96 | 0.00 | 0.661882E+09 | 0.00 | 1.30 |
August | 0.140059E+09 | 0.459970E+09 | 0.00 | 2755712.13 | 25401750.97 | 0.00 | 0.529924E+09 | 0.00 | 1.35 |
September | 0.293265E+09 | 90048153.73 | 0.00 | 3624738.90 | 7660943.16 | 0.00 | 0.103985E+10 | 0.00 | 1.12 |
October | 0.481756E+09 | 0.187976E+09 | 0.00 | 2193459.46 | 19916143.35 | 0.00 | 0.656117E+09 | 0.00 | 0.89 |
November | 0.105106E+10 | 558295.78 | 0.00 | 1869602.53 | 1209865.09 | 0.00 | 0.994213E+09 | 0.00 | 0.78 |
December | 0.130490E+10 | 254282.68 | 0.00 | 1142943.36 | 12753.57 | 198495.44 | 0.533171E+09 | 0.00 | 0.67 |
Annual Sum or Average | 0.923185E+10 | 0.120712E+10 | 0.00 | 30339564.20 | 83359172.08 | 11350449.84 | 0.106552E+11 | 0.00 | 0.95 |
Minimum of Months | 0.140059E+09 | 0.00 | 0.00 | 1112065.71 | 0.00 | 0.00 | 0.529924E+09 | 0.00 | 0.65 |
Maximum of Months | 0.145449E+10 | 0.459970E+09 | 0.00 | 4361856.62 | 25401750.97 | 7339614.81 | 0.155163E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174900E+10 | 556650.05 | 0.00 | 745982.81 | 4647488.49 | 29347542.51 | 0.369139E+09 | 0.00 | 0.47 |
February | 0.159610E+10 | 1201028.54 | 0.00 | 866501.03 | 0.00 | 769097.16 | 0.567432E+09 | 0.00 | 0.49 |
March | 0.186997E+10 | 0.00 | 0.00 | 1115426.82 | 4225671.53 | 9096869.83 | 0.673235E+09 | 0.00 | 0.51 |
April | 0.111711E+10 | 479428.89 | 0.00 | 2679516.19 | 9365311.54 | 293951.06 | 0.111179E+10 | 0.00 | 0.63 |
May | 0.943011E+09 | 3120072.13 | 0.00 | 3787731.61 | 3654.78 | 0.00 | 0.159492E+10 | 0.00 | 0.73 |
June | 0.472682E+09 | 48016210.40 | 0.00 | 4792235.08 | 6262493.25 | 0.00 | 0.146436E+10 | 0.00 | 0.90 |
July | 0.249801E+09 | 0.411907E+09 | 0.00 | 2912747.49 | 38075163.92 | 0.00 | 0.638623E+09 | 0.00 | 0.88 |
August | 0.274272E+09 | 0.471624E+09 | 0.00 | 2262560.84 | 54511376.39 | 0.00 | 0.457179E+09 | 0.00 | 0.88 |
September | 0.595499E+09 | 0.122586E+09 | 0.00 | 2693287.75 | 12386078.57 | 0.00 | 0.778590E+09 | 0.00 | 0.74 |
October | 0.756095E+09 | 0.233254E+09 | 0.00 | 1970383.64 | 30549215.84 | 0.00 | 0.567153E+09 | 0.00 | 0.65 |
November | 0.142576E+10 | 259073.50 | 0.00 | 1395720.90 | 2187731.44 | 0.00 | 0.772301E+09 | 0.00 | 0.52 |
December | 0.172393E+10 | 200338.23 | 0.00 | 715756.97 | 256574.20 | 1792297.55 | 0.352553E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.127732E+11 | 0.129320E+10 | 0.00 | 25937851.15 | 0.162471E+09 | 41299758.11 | 0.934727E+10 | 0.00 | 0.66 |
Minimum of Months | 0.249801E+09 | 0.00 | 0.00 | 715756.97 | 0.00 | 0.00 | 0.352553E+09 | 0.00 | 0.47 |
Maximum of Months | 0.186997E+10 | 0.471624E+09 | 0.00 | 4792235.08 | 54511376.39 | 29347542.51 | 0.159492E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115784E+10 | 1652783.36 | 0.00 | 1433626.51 | 2838252.63 | 9997923.22 | 0.777234E+09 | 0.00 | 0.68 |
February | 0.115729E+10 | 1105800.57 | 0.00 | 1591642.09 | 0.00 | 690937.49 | 0.875012E+09 | 0.00 | 0.74 |
March | 0.129398E+10 | 248145.28 | 0.00 | 2203117.44 | 3376689.79 | 1577302.16 | 0.109543E+10 | 0.00 | 0.79 |
April | 0.790417E+09 | 2917849.80 | 0.00 | 4067043.64 | 6544090.59 | 0.00 | 0.163970E+10 | 0.00 | 1.11 |
May | 0.767955E+09 | 3367816.19 | 0.00 | 4144740.86 | 3131.51 | 0.00 | 0.171420E+10 | 0.00 | 1.13 |
June | 0.468704E+09 | 46350987.24 | 0.00 | 4714440.88 | 3464335.79 | 0.00 | 0.131328E+10 | 0.00 | 1.35 |
July | 0.230453E+09 | 0.392032E+09 | 0.00 | 3786405.06 | 24471851.46 | 0.00 | 0.701666E+09 | 0.00 | 1.42 |
August | 0.230838E+09 | 0.540160E+09 | 0.00 | 3006631.44 | 32409338.56 | 0.00 | 0.563942E+09 | 0.00 | 1.50 |
September | 0.496908E+09 | 0.105458E+09 | 0.00 | 3218103.78 | 9634217.40 | 0.00 | 0.865546E+09 | 0.00 | 1.15 |
October | 0.544699E+09 | 0.193999E+09 | 0.00 | 2383308.81 | 27943624.05 | 0.00 | 0.759902E+09 | 0.00 | 0.94 |
November | 0.998604E+09 | 533726.88 | 0.00 | 2108611.70 | 1545483.75 | 0.00 | 0.103580E+10 | 0.00 | 0.76 |
December | 0.118766E+10 | 447115.13 | 0.00 | 1448289.51 | 4345.16 | 685056.01 | 0.659261E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.932536E+10 | 0.128827E+10 | 0.00 | 34105961.71 | 0.112235E+09 | 12951218.88 | 0.120010E+11 | 0.00 | 1.02 |
Minimum of Months | 0.230453E+09 | 248145.28 | 0.00 | 1433626.51 | 0.00 | 0.00 | 0.563942E+09 | 0.00 | 0.68 |
Maximum of Months | 0.129398E+10 | 0.540160E+09 | 0.00 | 4714440.88 | 32409338.56 | 9997923.22 | 0.171420E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.881632E+09 | 24800139.96 | 0.00 | 8510727.77 | 0.00 | 5195860.30 | 0.362614E+10 | 0.00 | 1.15 |
February | 0.101798E+10 | 4473229.25 | 0.00 | 6274722.86 | 0.00 | 0.00 | 0.283264E+10 | 0.00 | 1.00 |
March | 0.125426E+10 | 4069452.83 | 0.00 | 5688390.12 | 978394.95 | 4048014.08 | 0.250127E+10 | 0.00 | 0.88 |
April | 0.896074E+09 | 6194887.76 | 0.00 | 5757995.65 | 6709347.40 | 294564.15 | 0.218054E+10 | 0.00 | 0.97 |
May | 0.949506E+09 | 4166358.55 | 0.00 | 4617982.17 | 3662.41 | 0.00 | 0.184180E+10 | 0.00 | 0.83 |
June | 0.558158E+09 | 56373522.06 | 0.00 | 4699948.71 | 6275554.89 | 0.00 | 0.138446E+10 | 0.00 | 0.93 |
July | 0.292048E+09 | 0.489293E+09 | 0.00 | 2814513.42 | 35809821.44 | 0.00 | 0.610906E+09 | 0.00 | 0.95 |
August | 0.223774E+09 | 0.707555E+09 | 0.00 | 3174685.08 | 52101394.27 | 0.00 | 0.617489E+09 | 0.00 | 1.17 |
September | 0.410931E+09 | 0.229525E+09 | 0.00 | 5977528.76 | 7828628.66 | 0.00 | 0.156669E+10 | 0.00 | 1.24 |
October | 0.447766E+09 | 0.508955E+09 | 0.00 | 6274981.66 | 6703470.96 | 0.00 | 0.155100E+10 | 0.00 | 1.15 |
November | 0.810360E+09 | 5202742.84 | 0.00 | 8867838.27 | 420386.55 | 0.00 | 0.365159E+10 | 0.00 | 1.24 |
December | 0.866950E+09 | 2199784.99 | 0.00 | 9534382.90 | 0.00 | 239441.03 | 0.328995E+10 | 0.00 | 1.17 |
Annual Sum or Average | 0.860944E+10 | 0.204281E+10 | 0.00 | 72193697.36 | 0.116831E+09 | 9777879.56 | 0.256545E+11 | 0.00 | 1.06 |
Minimum of Months | 0.223774E+09 | 2199784.99 | 0.00 | 2814513.42 | 0.00 | 0.00 | 0.610906E+09 | 0.00 | 0.83 |
Maximum of Months | 0.125426E+10 | 0.707555E+09 | 0.00 | 9534382.90 | 52101394.27 | 5195860.30 | 0.365159E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140654E+10 | 5031800.55 | 0.00 | 1433769.90 | 1461944.21 | 28172921.58 | 0.715222E+09 | 0.00 | 0.75 |
February | 0.134781E+10 | 1389758.16 | 0.00 | 1672170.73 | 0.00 | 1579258.09 | 0.885944E+09 | 0.00 | 0.83 |
March | 0.149420E+10 | 0.00 | 0.00 | 2306663.97 | 3771841.72 | 9920967.76 | 0.117757E+10 | 0.00 | 0.89 |
April | 0.829602E+09 | 3976053.58 | 0.00 | 4380439.26 | 5276665.43 | 1467899.13 | 0.169388E+10 | 0.00 | 1.18 |
May | 0.759876E+09 | 2495856.77 | 0.00 | 4731656.85 | 0.00 | 0.00 | 0.188759E+10 | 0.00 | 1.21 |
June | 0.391959E+09 | 42994643.95 | 0.00 | 5357242.65 | 3988163.32 | 0.00 | 0.159054E+10 | 0.00 | 1.48 |
July | 0.225844E+09 | 0.464694E+09 | 0.00 | 3636287.37 | 22135338.74 | 0.00 | 0.691512E+09 | 0.00 | 1.46 |
August | 0.212012E+09 | 0.509536E+09 | 0.00 | 2847415.93 | 32248758.41 | 0.00 | 0.533302E+09 | 0.00 | 1.51 |
September | 0.407905E+09 | 0.110907E+09 | 0.00 | 3804598.68 | 11112555.06 | 0.00 | 0.108021E+10 | 0.00 | 1.27 |
October | 0.624592E+09 | 0.211012E+09 | 0.00 | 2286060.58 | 22410023.45 | 0.00 | 0.641391E+09 | 0.00 | 0.99 |
November | 0.123784E+10 | 889242.54 | 0.00 | 2093618.10 | 1631887.29 | 0.00 | 0.105238E+10 | 0.00 | 0.89 |
December | 0.140054E+10 | 314429.16 | 0.00 | 1446482.07 | 224491.98 | 3652076.35 | 0.640813E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.103387E+11 | 0.135324E+10 | 0.00 | 35996406.07 | 0.104262E+09 | 44793122.90 | 0.125903E+11 | 0.00 | 1.10 |
Minimum of Months | 0.212012E+09 | 0.00 | 0.00 | 1433769.90 | 0.00 | 0.00 | 0.533302E+09 | 0.00 | 0.75 |
Maximum of Months | 0.149420E+10 | 0.509536E+09 | 0.00 | 5357242.65 | 32248758.41 | 28172921.58 | 0.188759E+10 | 0.00 | 1.51 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.189592E+12 | 0.429036E+10 | 0.00 | 0.213209E+12 | 0.293155E+11 |
February | 0.220536E+12 | 0.450213E+10 | 0.00 | 0.213037E+12 | 0.169739E+11 |
March | 0.296231E+12 | 0.508640E+10 | 0.00 | 0.221002E+12 | 0.214789E+11 |
April | 0.371961E+12 | 0.299417E+10 | 0.00 | 0.210766E+12 | 0.467762E+11 |
May | 0.385805E+12 | 0.328262E+10 | 0.00 | 0.220756E+12 | 0.486949E+11 |
June | 0.378107E+12 | 0.181828E+10 | 0.00 | 0.172502E+12 | 0.907773E+11 |
July | 0.403788E+12 | 0.550458E+09 | 0.00 | 0.101073E+12 | 0.152697E+12 |
August | 0.377297E+12 | 0.542219E+09 | 0.00 | 0.766117E+11 | 0.175678E+12 |
September | 0.304036E+12 | 0.138504E+10 | 0.00 | 0.146516E+12 | 0.106978E+12 |
October | 0.221351E+12 | 0.194654E+10 | 0.00 | 0.157649E+12 | 0.116413E+12 |
November | 0.203049E+12 | 0.405517E+10 | 0.00 | 0.235139E+12 | 0.320572E+11 |
December | 0.174876E+12 | 0.433071E+10 | 0.00 | 0.235682E+12 | 0.339202E+11 |
Annual Sum or Average | 0.352663E+13 | 0.347841E+11 | 0.00 | 0.220394E+13 | 0.871761E+12 |
Minimum of Months | 0.174876E+12 | 0.542219E+09 | 0.00 | 0.766117E+11 | 0.169739E+11 |