Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:20:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1650.93 | 331.37 | 331.37 |
Net Site Energy | 1650.93 | 331.37 | 331.37 |
Total Source Energy | 5228.49 | 1049.44 | 1049.44 |
Net Source Energy | 5228.49 | 1049.44 | 1049.44 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 124.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 305.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 48.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1650.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 124.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 305.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 48.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 124.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 305.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 302.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 71.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 48.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 331.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 71.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 331.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1650.928 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1650.928 | 100.00 |
Total On-Site and Utility Electric Sources | 1650.928 | 100.00 |
Total Electricity End Uses | 1650.928 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 128.50 |
Time Setpoint Not Met During Occupied Cooling | 115.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1773.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:20 |
Heating | 195320.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 975.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5356.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1951.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 242674.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 195320.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 10880.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 975.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5356.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 1951.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 395.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 967.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 957.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 227.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 152.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5228.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 79.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1049.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 79.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 194.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 192.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1049.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.72 | 0.275549 | 0.283000 | 0.769720 | 0.734798 | 0.500000 | 0.001383 |
CORE_MID VAV BOX COMPONENT | 2.20 | 0.340370 | 0.342000 | 0.753045 | 0.907652 | 0.500000 | 0.001119 |
CORE_TOP VAV BOX COMPONENT | 2.34 | 0.320154 | 0.335000 | 0.784207 | 0.853745 | 0.500000 | 0.001190 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.726007 | 0.217617 | 0.228000 | 0.165530 | 0.580313 | 0.500000 | 0.001751 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.696097 | 0.143690 | 0.200000 | 0.139219 | 0.383172 | 0.500000 | 0.002652 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.840533 | 0.187966 | 0.200000 | 0.168107 | 0.501243 | 0.500000 | 0.002027 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.767238 | 0.130358 | 0.200000 | 0.153448 | 0.347620 | 0.500000 | 0.002923 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.588036 | 0.268677 | 0.276000 | 0.162298 | 0.716471 | 0.500000 | 0.001418 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.598696 | 0.167066 | 0.200000 | 0.119739 | 0.445510 | 0.500000 | 0.002281 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.688894 | 0.229341 | 0.235000 | 0.161890 | 0.611576 | 0.500000 | 0.001661 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.619363 | 0.161481 | 0.200000 | 0.123873 | 0.430615 | 0.500000 | 0.002359 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.631133 | 0.250330 | 0.251000 | 0.158414 | 0.667547 | 0.500000 | 0.001522 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.670365 | 0.149205 | 0.200000 | 0.134073 | 0.397880 | 0.500000 | 0.002554 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.744990 | 0.212072 | 0.213000 | 0.158683 | 0.565526 | 0.500000 | 0.001797 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.697377 | 0.143416 | 0.200000 | 0.139475 | 0.382443 | 0.500000 | 0.002657 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24785.76 |
CORE_MID VAV BOX REHEAT COIL | 24248.82 |
CORE_TOP VAV BOX REHEAT COIL | 35333.63 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16288.52 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10560.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16136.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10652.81 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12467.11 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8150.01 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12332.36 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8236.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12837.64 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8364.90 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12695.32 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8449.74 |
PACU_VAV_BOT HEATING COIL | 24829.27 |
PACU_VAV_MID HEATING COIL | 25569.01 |
PACU_VAV_TOP HEATING COIL | 24852.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.61 | 1.34 | 5.21 | 1.70 | 4.72 | 4.72 | 0.300000 | 0.360782 | 4.72 |
PACU_VAV_MID | 2.47 | 1.34 | 4.95 | 1.94 | 4.35 | 4.35 | 0.300000 | 0.444714 | 4.35 |
PACU_VAV_TOP | 2.69 | 1.41 | 5.37 | 2.76 | 5.07 | 5.07 | 0.300000 | 0.544711 | 5.07 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.72 |
PACU_VAV_MID_OA_CONTROLLER | 4.35 |
PACU_VAV_TOP_OA_CONTROLLER | 5.07 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.72 | 108009.53 | 0.727087 | 1.57 | 35999.58 | 0.727087 |
PACU_VAV_MID COOLING COIL | 4.35 | 102699.86 | 0.717022 | 1.45 | 34229.86 | 0.717022 |
PACU_VAV_TOP COOLING COIL | 5.07 | 113611.56 | 0.734723 | 1.69 | 37866.73 | 0.734723 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.72 |
PACU_VAV_MID FAN | 4.35 |
PACU_VAV_TOP FAN | 5.07 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0154E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0548E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5333E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5658E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3333E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3590E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1011 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6105E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1127 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9971E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6512E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0535E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0182E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0717E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5364E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5846E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3363E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3723E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4712E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0617E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3095E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8955E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1866E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5629E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8084E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8244E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6586E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6702E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2994E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3039E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9419E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9799E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4803E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5112E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1854E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2090E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7332E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5479E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1205E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1871E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9704E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3399E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9411E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9793E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4790E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5082E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1828E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1998E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9026E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3393E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3943E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0120E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7737E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9199E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7990E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8327E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4179E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4521E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4291E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4468E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1093 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7177E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1214 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1854E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3417E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9225E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2977E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9600E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1501E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8013E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0648E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4890E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1345E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0406E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4795E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6142E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3290E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2281E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7764E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2698E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2932E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9575E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6925E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8735E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1093 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7171E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1214 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1847E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3412E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9220E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2976E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9597E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1499E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8011E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0645E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4887E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1346E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0405E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4795E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6142E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3289E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2279E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7763E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2696E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2931E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9574E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6923E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8733E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36398.62141 | 36398.62141 | 2.71986 | 2.71986 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6814.74716 | 6814.74716 | 0.29666 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29492.69775 | 29492.69775 | 2.20189 | 2.20189 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14154.25437 | 14154.25437 | 0.62121 | 0.62121 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31063.55885 | 31063.55885 | 2.34092 | 2.34092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24889.41623 | 24889.41623 | 1.09728 | 1.09728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9633.75779 | 9633.75779 | 0.72601 | 0.72601 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 11439.69640 | 11439.69640 | 0.50584 | 0.50584 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9236.89836 | 9236.89836 | 0.69610 | 0.69610 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7416.21218 | 7416.21218 | 0.32795 | 0.32795 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11153.48408 | 11153.48408 | 0.84053 | 0.84053 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11333.38706 | 11333.38706 | 0.50112 | 0.50112 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10180.93296 | 10180.93296 | 0.76724 | 0.76724 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7481.01810 | 7481.01810 | 0.33082 | 0.33082 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7803.05981 | 7803.05981 | 0.58804 | 0.58804 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8762.17945 | 8762.17945 | 0.38717 | 0.38717 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7944.55991 | 7944.55991 | 0.59870 | 0.59870 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5727.40071 | 5727.40071 | 0.25310 | 0.25310 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9141.42949 | 9141.42949 | 0.68889 | 0.68889 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8667.81022 | 8667.81022 | 0.38298 | 0.38298 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8218.80881 | 8218.80881 | 0.61936 | 0.61936 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59500 | 1.44700E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5787.99762 | 5787.99762 | 0.25579 | 0.25579 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8374.86117 | 8374.86117 | 0.63113 | 0.63113 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9022.32748 | 9022.32748 | 0.39867 | 0.39867 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8895.50644 | 8895.50644 | 0.67037 | 0.67037 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5878.32338 | 5878.32338 | 0.25977 | 0.25977 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9885.70508 | 9885.70508 | 0.74499 | 0.74499 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8922.65812 | 8922.65812 | 0.39425 | 0.39425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9253.95628 | 9253.95628 | 0.69738 | 0.69738 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5937.73585 | 5937.73585 | 0.26241 | 0.26241 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76065.24 | 4.72230 | 4.72230 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 26344.47 | 1.70372 | 1.70372 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71003.10 | 4.35406 | 4.35406 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 26401.97 | 1.93631 | 1.93631 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80209.49 | 5.07245 | 5.07245 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 26383.62 | 2.76302 | 2.76302 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.71986 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27555 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76972 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73480 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38269E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24785.76009 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20189 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34037 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75304 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90765 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11937E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24248.81622 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34092 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32015 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78421 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85374 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19005E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35333.63410 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72601 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21762 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16553 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58031 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75078E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16288.52467 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69610 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14369 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13922 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38317 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65155E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10560.27406 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84053 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18797 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16811 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50124 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02696E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16136.73533 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76724 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13036 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15345 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34762 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92273E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10652.80656 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58804 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26868 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16230 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71647 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41806E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12467.11474 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59870 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16707 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11974 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44551 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28053E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8150.00601 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68889 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22934 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16189 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61158 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66128E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12332.35694 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61936 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16148 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12387 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43062 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35941E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8236.53941 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63113 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25033 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15841 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66755 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52199E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12837.64424 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67037 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14920 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39788 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55353E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8364.90156 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74499 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21207 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15868 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56553 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79656E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12695.32364 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69738 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14342 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13948 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38244 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.65660E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8449.73980 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60742 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33752 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.21485 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70372 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.72230 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.72230 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.36078 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.47288 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34369 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.94575 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.93631 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35406 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35406 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.44471 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68540 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41051 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.37079 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.76302 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.07245 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.07245 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.54471 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.72230 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.35406 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.07245 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.72230 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.72230 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108009.53149 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72709 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57394 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35999.57685 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72709 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 24829.26859 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.72230 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35406 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.35406 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102699.86220 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71702 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45121 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34229.86407 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71702 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 25569.00936 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.35406 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.07245 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.07245 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113611.56336 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73472 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.69065 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37866.73407 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73472 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 24852.24717 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.07245 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 107544.88 | 366958.35 | 12.42 | 3.17 | 3.56 | 3.75 | 3.90 | 10.82 | 12.14 | 12.80 | 13.32 | 5.2660 | 4.1880 | 2.8184 | 1.1860 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 102363.29 | 349278.04 | 12.49 | 3.18 | 3.58 | 3.77 | 3.92 | 10.86 | 12.21 | 12.88 | 13.37 | 4.8553 | 3.8580 | 2.5957 | 1.1033 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 113041.44 | 385713.40 | 12.37 | 3.16 | 3.55 | 3.73 | 3.90 | 10.79 | 12.10 | 12.74 | 13.29 | 5.6564 | 4.5047 | 3.0327 | 1.2650 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.1052747143E-003 | 5.7285901976E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.3497308466E-002 | 2.9956915914E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8798364485E-003 | 4.2483039661E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1626142756E-003 | 3.8537698894E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.6796230130E-003 | 6.7853908694E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5190336722E-002 | 1.1308805651E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.4142832354E-002 | 2.4557947322E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.5383490184E-002 | 2.6310441210E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.5873223491E-002 | 2.8126384385E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.5608274601E-002 | 2.4993611368E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3160099612E-002 | 2.0809090428E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.4027025014E-002 | 2.2517489240E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.4516023106E-002 | 2.3381916286E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.4039964921E-002 | 2.1252798240E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6846499876E-002 | 2.2787402188E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.8066550197E-002 | 2.4733240884E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.8505437975E-002 | 2.6019272308E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.8219983674E-002 | 2.3300354374E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2919.86 | 24.70 | 0.00 | 1149.35 | 1611.87 | 5705.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.557 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 9.01 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 5.57 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 8.69 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.29 | 0.0000 | Y | 5.63 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.50 | 0.0000 | Y | 8.97 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.59 | 0.0000 | Y | 8.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.19 | 0.0000 | Y | 5.61 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 9.01 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 5.57 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.65 | 0.0000 | Y | 8.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.29 | 0.0000 | Y | 5.63 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 302.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 47.60 | 42.13 | |
Exterior Lighting Total | 5686.19 | 51.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108009.53 | 78532.28 | 29477.25 | 0.73 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102699.86 | 73638.04 | 29061.82 | 0.72 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113611.56 | 83473.06 | 30138.50 | 0.73 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 107544.9 | 3.17 | 10.82 | N/A | N/A | 12.42 | |
PACU_VAV_MID COOLING COIL | 102363.3 | 3.18 | 10.86 | N/A | N/A | 12.49 | |
PACU_VAV_TOP COOLING COIL | 113041.4 | 3.16 | 10.79 | N/A | N/A | 12.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24785.76 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24248.82 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 35333.63 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16288.52 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10560.27 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16136.74 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10652.81 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12467.11 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8150.01 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12332.36 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8236.54 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12837.64 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8364.90 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12695.32 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8449.74 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 24829.27 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 25569.01 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 24852.25 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.72 | 10337.16 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.35 | 10072.62 | 2313.39 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.07 | 11032.00 | 2174.89 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107544.88 | 3.17 | 10.82 | 12.42 | 5.2660 | 3.56 | 12.14 | 4.1880 | 3.75 | 12.80 | 2.8184 | 3.90 | 13.32 | 1.1860 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102363.29 | 3.18 | 10.86 | 12.49 | 4.8553 | 3.58 | 12.21 | 3.8580 | 3.77 | 12.88 | 2.5957 | 3.92 | 13.37 | 1.1033 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 113041.44 | 3.16 | 10.79 | 12.37 | 5.6564 | 3.55 | 12.10 | 4.5047 | 3.73 | 12.74 | 3.0327 | 3.90 | 13.29 | 1.2650 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36398.62 | 36398.62 | 37.01 | 2.720 | 2.720 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00884 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 29492.70 | 29492.70 | 29.99 | 2.202 | 2.202 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 31063.56 | 31063.56 | 31.58 | 2.341 | 2.341 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00889 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9633.76 | 9633.76 | 46.46 | 0.726 | 0.726 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9236.90 | 9236.90 | 70.37 | 0.696 | 0.696 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00874 | 31.26 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11153.48 | 11153.48 | 53.79 | 0.841 | 0.841 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00881 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10180.93 | 10180.93 | 77.57 | 0.767 | 0.767 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7803.06 | 7803.06 | 37.63 | 0.588 | 0.588 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00889 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7944.56 | 7944.56 | 60.52 | 0.599 | 0.599 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00875 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9141.43 | 9141.43 | 44.09 | 0.689 | 0.689 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00883 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8218.81 | 8218.81 | 62.62 | 0.619 | 0.619 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00874 | 32.59 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8374.86 | 8374.86 | 40.39 | 0.631 | 0.631 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00890 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8895.51 | 8895.51 | 67.77 | 0.670 | 0.670 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00874 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9885.71 | 9885.71 | 47.68 | 0.745 | 0.745 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00884 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9253.96 | 9253.96 | 70.50 | 0.697 | 0.697 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00873 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6814.75 | 6814.75 | 6.93 | 0.297 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 14154.25 | 14154.25 | 14.39 | 0.621 | 0.621 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 24889.42 | 24889.42 | 25.31 | 1.097 | 1.097 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11439.70 | 11439.70 | 55.17 | 0.506 | 0.506 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7416.21 | 7416.21 | 56.50 | 0.328 | 0.328 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11333.39 | 11333.39 | 54.66 | 0.501 | 0.501 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7481.02 | 7481.02 | 57.00 | 0.331 | 0.331 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8762.18 | 8762.18 | 42.26 | 0.387 | 0.387 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5727.40 | 5727.40 | 43.63 | 0.253 | 0.253 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8667.81 | 8667.81 | 41.81 | 0.383 | 0.383 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5788.00 | 5788.00 | 44.10 | 0.256 | 0.256 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9022.33 | 9022.33 | 43.52 | 0.399 | 0.399 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5878.32 | 5878.32 | 44.78 | 0.260 | 0.260 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8922.66 | 8922.66 | 43.03 | 0.394 | 0.394 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5937.74 | 5937.74 | 45.24 | 0.262 | 0.262 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.72 | 4.72 | 1.70 | 1.70 | 4.7223 | 1.7037 | 4.7223 | 0.3608 | 0.3000 |
PACU_VAV_MID | 4.35 | 4.35 | 1.94 | 1.94 | 4.3541 | 1.9363 | 4.3541 | 0.4447 | 0.3000 |
PACU_VAV_TOP | 5.07 | 5.07 | 2.76 | 2.76 | 5.0724 | 2.7630 | 5.0724 | 0.5447 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24785.760 | 24785.760 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24785.76 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 6814.75 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24248.816 | 24248.816 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24248.82 | 20003.59 | 0.621210 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 14154.25 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 35333.634 | 35333.634 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35333.63 | 35333.63 | 1.097283 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 24889.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16288.525 | 16288.525 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16288.52 | 16288.52 | 0.505839 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776362 | 48.4106 | 11439.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10560.274 | 10560.274 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10560.27 | 10560.27 | 0.327948 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775851 | 48.3792 | 7416.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16136.735 | 16136.735 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16136.74 | 16136.74 | 0.501125 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776090 | 48.3938 | 11333.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10652.807 | 10652.807 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10652.81 | 10652.81 | 0.330822 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776101 | 48.3946 | 7481.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 12467.115 | 12467.115 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12467.11 | 12467.11 | 0.387165 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776451 | 48.4157 | 8762.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8150.006 | 8150.006 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8150.01 | 8150.01 | 0.253098 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00777090 | 48.4550 | 5727.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12332.357 | 12332.357 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12332.36 | 12332.36 | 0.382980 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775736 | 48.3718 | 8667.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8236.539 | 8236.539 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8236.54 | 8236.54 | 0.255785 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00777738 | 48.4949 | 5788.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 12837.644 | 12837.644 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12837.64 | 12837.64 | 0.398672 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770887 | 48.0736 | 9022.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8364.902 | 8364.902 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8364.90 | 8364.90 | 0.259771 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770951 | 48.0776 | 5878.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 12695.324 | 12695.324 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12695.32 | 12695.32 | 0.394252 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770230 | 48.0332 | 8922.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8449.740 | 8449.740 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8449.74 | 8449.74 | 0.262406 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00771488 | 48.1106 | 5937.74 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 108009.531 | 78532.282 | 4.722295 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 108719.98 | 84619.07 | 4.722295 | 26.64 | 18.35 | 0.01027683 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 25.3091 | 24.00 | 0.00885078 | 45.9137 | 62529.53 | 0.00 | 111372.33 | 78549.81 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 24829.269 | 24829.269 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24829.27 | 24829.27 | 1.416689 | -2.22 | -2.42 | 0.00312912 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 84.3636 | 19.62 | 0.00758619 | 51.5217 | 19854.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 102699.862 | 73638.044 | 4.354060 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 103876.23 | 79522.25 | 4.354060 | 26.87 | 18.55 | 0.01043919 | 10.85 | 10.85 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 27.4496 | 24.00 | 0.00889860 | 46.1585 | 57387.76 | 0.00 | 105897.34 | 73724.21 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 25569.009 | 25569.009 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25569.01 | 25569.01 | 1.306218 | -3.98 | -4.05 | 0.00276328 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 91.4985 | 19.88 | 0.00775054 | 51.7888 | 24933.12 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 113611.563 | 83473.060 | 5.072446 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 114126.50 | 89636.21 | 5.072446 | 26.42 | 18.20 | 0.01018055 | 10.97 | 10.97 | 0.00850000 | 34.21 | 0.01447292 | 23.49 | 23.5620 | 24.00 | 0.00884962 | 45.9080 | 67007.81 | 0.00 | 117148.77 | 83456.75 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 24852.247 | 24852.247 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24852.25 | 24852.25 | 1.521734 | -1.20 | -1.35 | 0.00344487 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 78.5400 | 17.60 | 0.00759596 | 58.5527 | 29414.25 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24785.760 | 24785.760 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24785.76 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24785.76 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 6814.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24248.816 | 24248.816 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24248.82 | 20003.59 | 1.0000 | 0.72120975 | 0.621210 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24248.82 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 14154.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 35333.634 | 35333.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35333.63 | 35333.63 | 1.0000 | 1.27391967 | 1.097283 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35333.63 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 24889.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16288.525 | 16288.525 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16288.52 | 16288.52 | 1.0000 | 0.58726685 | 0.505839 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16288.52 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776362 | 21.00 | 0.00776362 | 48.4106 | 11439.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10560.274 | 10560.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10560.27 | 10560.27 | 1.0000 | 0.38074037 | 0.327948 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10560.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775851 | 21.00 | 0.00775851 | 48.3792 | 7416.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16136.735 | 16136.735 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16136.74 | 16136.74 | 1.0000 | 0.58179423 | 0.501125 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16136.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776090 | 21.00 | 0.00776090 | 48.3938 | 11333.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10652.807 | 10652.807 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10652.81 | 10652.81 | 1.0000 | 0.38407654 | 0.330822 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10652.81 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776101 | 21.00 | 0.00776101 | 48.3946 | 7481.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12467.115 | 12467.115 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12467.11 | 12467.11 | 1.0000 | 0.44948965 | 0.387165 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12467.11 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776451 | 21.00 | 0.00776451 | 48.4157 | 8762.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8150.006 | 8150.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8150.01 | 8150.01 | 1.0000 | 0.29384051 | 0.253098 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8150.01 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00777090 | 21.00 | 0.00777090 | 48.4550 | 5727.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12332.357 | 12332.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12332.36 | 12332.36 | 1.0000 | 0.44463109 | 0.382980 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12332.36 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775736 | 21.00 | 0.00775736 | 48.3718 | 8667.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8236.539 | 8236.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8236.54 | 8236.54 | 1.0000 | 0.29696038 | 0.255785 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8236.54 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00777738 | 21.00 | 0.00777738 | 48.4949 | 5788.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12837.644 | 12837.644 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12837.64 | 12837.64 | 1.0000 | 0.46284873 | 0.398672 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12837.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00770887 | 21.00 | 0.00770887 | 48.0736 | 9022.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8364.902 | 8364.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8364.90 | 8364.90 | 1.0000 | 0.30158836 | 0.259771 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8364.90 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00770951 | 21.00 | 0.00770951 | 48.0776 | 5878.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12695.324 | 12695.324 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12695.32 | 12695.32 | 1.0000 | 0.45771750 | 0.394252 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12695.32 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00770230 | 21.00 | 0.00770230 | 48.0332 | 8922.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8449.740 | 8449.740 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8449.74 | 8449.74 | 1.0000 | 0.30464712 | 0.262406 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8449.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00771488 | 21.00 | 0.00771488 | 48.1106 | 5937.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108009.531 | 78532.282 | 4.722295 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9441 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.722295 | 5.48247382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 108719.98 | 84619.07 | 1.0066 | 5.48247382 | 4.722295 | 26.64 | 18.35 | 0.01027683 | 52976.3 | 10.96 | 10.96 | 0.00850000 | 32442.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10337.156 | 98382.82 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 25.3091 | 24.00 | 0.00885078 | 24.00 | 0.00885078 | 45.9137 | 62529.53 | 0.00 | 111372.33 | 78549.81 | 5.26595755 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.06 | 12.03 | 0.00874086 | 34172.9 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24829.269 | 24829.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.722295 | 5.48247382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24829.27 | 24829.27 | 1.0000 | 1.64474215 | 1.416689 | -2.22 | -2.42 | 0.00312912 | 5578.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24829.27 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 84.3636 | 19.77 | 0.00761443 | 19.62 | 0.00758619 | 51.5217 | 19854.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102699.862 | 73638.044 | 4.354060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2459 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.354060 | 5.05496120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 103876.23 | 79522.25 | 1.0115 | 5.05496120 | 4.354060 | 26.87 | 18.55 | 0.01043919 | 53632.5 | 10.85 | 10.85 | 0.00850000 | 32336.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10072.623 | 93803.61 | 34.40 | 0.01447326 | 23.54 | 1.19517000 | 27.4496 | 24.00 | 0.00889860 | 24.00 | 0.00889860 | 46.1585 | 57387.76 | 0.00 | 105897.34 | 73724.21 | 4.85532844 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.79 | 11.77 | 0.00858661 | 33511.8 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25569.009 | 25569.009 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.354060 | 5.05496120 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25569.01 | 25569.01 | 1.0000 | 1.51648836 | 1.306218 | -3.98 | -4.05 | 0.00276328 | 2892.0 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25569.01 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 91.4985 | 21.00 | 0.00777319 | 19.88 | 0.00775054 | 51.7888 | 24933.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113611.563 | 83473.060 | 5.072446 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7651 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.072446 | 5.88899071 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 114126.50 | 89636.21 | 1.0045 | 5.88899071 | 5.072446 | 26.42 | 18.20 | 0.01018055 | 52504.1 | 10.97 | 10.97 | 0.00850000 | 32454.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11032.003 | 103094.50 | 34.21 | 0.01447292 | 23.49 | 1.19517000 | 23.5620 | 24.00 | 0.00884962 | 24.00 | 0.00884962 | 45.9080 | 67007.81 | 0.00 | 117148.77 | 83456.75 | 5.65642009 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.22 | 12.21 | 0.00884928 | 34611.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24852.247 | 24852.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.072446 | 5.88899071 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24852.25 | 24852.25 | 1.0000 | 1.76669721 | 1.521734 | -1.20 | -1.35 | 0.00344487 | 7402.9 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24852.25 | -6.30 | 0.00229779 | -6.30 | 1.19517000 | 78.5400 | 17.47 | 0.00764299 | 17.60 | 0.00759596 | 58.5527 | 29414.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.72 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.35 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2967.00 | 1842.17 | 16.33 |
CORE_MID | 2286.50 | 3099.83 | 262.00 |
CORE_TOP | 2546.00 | 3418.00 | 697.83 |
PERIMETER_TOP_ZN_3 | 3327.83 | 3542.67 | 1355.67 |
PERIMETER_TOP_ZN_2 | 3323.17 | 3392.83 | 1221.33 |
PERIMETER_TOP_ZN_1 | 3163.00 | 3016.00 | 925.33 |
PERIMETER_TOP_ZN_4 | 3201.00 | 3532.33 | 1262.67 |
PERIMETER_BOT_ZN_3 | 2924.83 | 3575.17 | 1005.00 |
PERIMETER_BOT_ZN_2 | 3058.33 | 3190.33 | 799.83 |
PERIMETER_BOT_ZN_1 | 2938.83 | 3234.67 | 785.17 |
PERIMETER_BOT_ZN_4 | 3024.33 | 3248.00 | 829.33 |
PERIMETER_MID_ZN_3 | 3135.50 | 3326.33 | 1010.83 |
PERIMETER_MID_ZN_2 | 2650.33 | 2794.67 | 846.50 |
PERIMETER_MID_ZN_1 | 3064.33 | 2686.50 | 603.50 |
PERIMETER_MID_ZN_4 | 3099.67 | 3268.17 | 931.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4620.33 | 4259.00 | 1773.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.83 | 0.00 | 1.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 20.83 | 3.33 | 9.33 | 2.17 |
PERIMETER_TOP_ZN_2 | 13.67 | 22.50 | 2.67 | 21.67 |
PERIMETER_TOP_ZN_1 | 9.67 | 18.67 | 2.67 | 17.50 |
PERIMETER_TOP_ZN_4 | 14.33 | 26.50 | 3.83 | 15.00 |
PERIMETER_BOT_ZN_3 | 1.17 | 0.00 | 0.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.33 | 10.67 | 0.00 | 10.67 |
PERIMETER_BOT_ZN_1 | 121.33 | 51.00 | 121.33 | 51.00 |
PERIMETER_BOT_ZN_4 | 0.33 | 16.00 | 0.00 | 8.33 |
PERIMETER_MID_ZN_3 | 2.17 | 0.00 | 1.50 | 0.00 |
PERIMETER_MID_ZN_2 | 1.17 | 17.00 | 0.50 | 17.00 |
PERIMETER_MID_ZN_1 | 1.17 | 14.50 | 0.50 | 14.50 |
PERIMETER_MID_ZN_4 | 1.17 | 22.17 | 0.50 | 12.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 141.50 | 135.83 | 128.50 | 115.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.702 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.565 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.566 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.628 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.875 | 0.040 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.775 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.933 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.576 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.754 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.709 | 0.817 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.755 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.618 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.800 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.777 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.890 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.05 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 11055765.50 | 0.00 | 11055765.50 | 0.00 | 11055765.50 | 13393058.27 | 5099.32 | 381.34 | 3279.34 | 3.72 |
CORE_MID | 8940842.95 | 0.00 | 8940842.95 | 0.00 | 8940842.95 | 13393058.27 | 6310.34 | 228.84 | 2220.82 | 16.76 |
CORE_TOP | 8984186.41 | 0.00 | 8984186.41 | 0.00 | 8984186.41 | 13393058.27 | 6573.26 | 59.15 | 2127.59 | 74.51 |
PERIMETER_TOP_ZN_3 | 2099702.62 | 0.00 | 2099702.62 | 253748.86 | 2353451.48 | 2823374.22 | 5237.51 | 83.31 | 3439.17 | 74.51 |
PERIMETER_TOP_ZN_2 | 1850983.50 | 0.00 | 1850983.50 | 169164.89 | 2020148.39 | 1787429.43 | 4248.68 | 4.31 | 4507.01 | 74.51 |
PERIMETER_TOP_ZN_1 | 2583099.35 | 0.00 | 2583099.35 | 253748.86 | 2836848.21 | 2823374.22 | 4535.07 | 689.13 | 3535.80 | 74.51 |
PERIMETER_TOP_ZN_4 | 1974058.58 | 0.00 | 1974058.58 | 169164.89 | 2143223.47 | 1787312.18 | 4273.40 | 17.47 | 4469.13 | 74.51 |
PERIMETER_BOT_ZN_3 | 1918452.31 | 0.00 | 1918452.31 | 134917.23 | 2053369.54 | 2823374.22 | 5768.88 | 398.05 | 2593.07 | 3.72 |
PERIMETER_BOT_ZN_2 | 1588474.42 | 0.00 | 1588474.42 | 89944.28 | 1678418.70 | 1787429.43 | 4361.55 | 60.25 | 4338.20 | 3.72 |
PERIMETER_BOT_ZN_1 | 2357807.09 | 0.00 | 2357807.09 | 2786735.31 | 5144542.40 | 2823374.22 | 4964.00 | 350.91 | 3445.09 | 3.72 |
PERIMETER_BOT_ZN_4 | 1590371.93 | 0.00 | 1590371.93 | 89944.28 | 1680316.20 | 1787312.18 | 4575.86 | 87.83 | 4096.31 | 3.72 |
PERIMETER_MID_ZN_3 | 2060078.98 | 0.00 | 2060078.98 | 211226.68 | 2271305.66 | 2823374.22 | 5044.36 | 188.64 | 3526.99 | 16.76 |
PERIMETER_MID_ZN_2 | 1833014.09 | 0.00 | 1833014.09 | 140816.94 | 1973831.03 | 1787429.43 | 4226.37 | 10.74 | 4522.89 | 925.76 |
PERIMETER_MID_ZN_1 | 2585890.67 | 0.00 | 2585890.67 | 211226.68 | 2797117.35 | 2823374.22 | 4877.13 | 223.04 | 3659.83 | 16.76 |
PERIMETER_MID_ZN_4 | 1878937.65 | 0.00 | 1878937.65 | 140816.94 | 2019754.59 | 1787312.18 | 4278.22 | 25.92 | 4455.87 | 16.76 |
Total Facility | 53301666.05 | 0.00 | 53301666.05 | 4651455.83 | 57953121.87 | 67843644.98 | 6728.11 | 1236.33 | 4567.08 | 986.40 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5165 | 0.0000 | 0.5165 | 0.0000 | 0.5165 | 0.4247 | 2283.37 | 381.34 | 3278.29 |
CORE_MID | 0.4169 | 0.0000 | 0.4169 | 0.0000 | 0.4169 | 0.4247 | 3497.57 | 228.84 | 2216.59 |
CORE_TOP | 0.4181 | 0.0000 | 0.4181 | 0.0000 | 0.4181 | 0.4247 | 3760.94 | 59.15 | 2122.91 |
PERIMETER_TOP_ZN_3 | 0.0977 | 0.0000 | 0.0977 | 0.0059 | 0.1036 | 0.0895 | 2425.19 | 83.31 | 3434.49 |
PERIMETER_TOP_ZN_2 | 0.0862 | 0.0000 | 0.0862 | 0.0039 | 0.0901 | 0.0567 | 1436.62 | 4.31 | 4502.07 |
PERIMETER_TOP_ZN_1 | 0.1203 | 0.0000 | 0.1203 | 0.0059 | 0.1262 | 0.0895 | 1722.78 | 689.13 | 3531.09 |
PERIMETER_TOP_ZN_4 | 0.0919 | 0.0000 | 0.0919 | 0.0039 | 0.0958 | 0.0567 | 1461.33 | 17.47 | 4464.21 |
PERIMETER_BOT_ZN_3 | 0.0896 | 0.0000 | 0.0896 | 0.0031 | 0.0927 | 0.0895 | 2952.96 | 398.05 | 2592.00 |
PERIMETER_BOT_ZN_2 | 0.0742 | 0.0000 | 0.0742 | 0.0021 | 0.0763 | 0.0567 | 1545.82 | 60.25 | 4336.94 |
PERIMETER_BOT_ZN_1 | 0.1102 | 0.0000 | 0.1102 | 0.1271 | 0.2372 | 0.0895 | 2148.08 | 350.91 | 3444.01 |
PERIMETER_BOT_ZN_4 | 0.0743 | 0.0000 | 0.0743 | 0.0021 | 0.0764 | 0.0567 | 1760.12 | 87.81 | 4095.07 |
PERIMETER_MID_ZN_3 | 0.0961 | 0.0000 | 0.0961 | 0.0049 | 0.1010 | 0.0895 | 2231.73 | 188.62 | 3522.64 |
PERIMETER_MID_ZN_2 | 0.0788 | 0.0000 | 0.0788 | 0.0035 | 0.0823 | 0.0567 | 1406.30 | 7.41 | 3620.29 |
PERIMETER_MID_ZN_1 | 0.1207 | 0.0000 | 0.1207 | 0.0049 | 0.1256 | 0.0895 | 2064.39 | 223.04 | 3655.57 |
PERIMETER_MID_ZN_4 | 0.0876 | 0.0000 | 0.0876 | 0.0033 | 0.0909 | 0.0567 | 1465.72 | 25.92 | 4451.36 |
Total Facility | 2.4791 | 0.0000 | 2.4791 | 0.1705 | 2.6496 | 2.1513 | 3911.44 | 1236.29 | 4560.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 24950218.71 | 0.00 | 24950218.71 | 22614548.33 | 4213.99 | 2.14 | 4543.86 | 3.72 |
PACU_VAV_MID | 23316459.10 | 0.00 | 23316459.10 | 22614548.33 | 4207.91 | 0.21 | 4551.88 | 16.76 |
PACU_VAV_TOP | 23576919.70 | 0.00 | 23576919.70 | 22614548.33 | 4239.17 | 1.11 | 4519.72 | 74.51 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1656 | 0.0000 | 1.1656 | 0.7171 | 1398.29 | 1.98 | 4542.73 |
PACU_VAV_MID | 1.0875 | 0.0000 | 1.0875 | 0.7171 | 1395.24 | 0.21 | 4547.55 |
PACU_VAV_TOP | 1.0975 | 0.0000 | 1.0975 | 0.7171 | 1426.85 | 1.11 | 4515.04 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2355.31 | 0.00 | 0.00 | 0.00 | 2211.55 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2264.52 | 0.00 | 0.00 | 0.00 | 2326.15 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2296.65 | 0.00 | 0.00 | 0.00 | 2355.98 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 1.9504 | 0.0000 | 0.0000 | 0.0000 | 1.0591 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.7810 | 0.0000 | 0.0000 | 0.0000 | 1.0580 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.8218 | 0.0000 | 0.0000 | 0.0000 | 1.0505 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
Electricity:Building | 1022.09 | 13465.67 | 29-MAY-17:20 | 74341.76 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1022.09 | 13465.67 | 29-MAY-17:20 | 74341.76 | 03-JAN-08:10 |
InteriorLights:Electricity | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 302.40 | 987.92 | 29-MAY-17:20 | 32642.50 | 03-JAN-08:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.35 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.97 | 267.21 | 21-MAY-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 33.02 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 21.04 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.30 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.97 | 36.00 | 01-JAN-11:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.97 | 36.00 | 01-JAN-11:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.96 | 267.21 | 23-APR-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.55 | 22.79 | 01-JAN-09:10 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.55 | 22.79 | 01-JAN-09:10 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 33.00 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.02 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.61 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.61 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.35 | 422.10 | 16-APR-17:10 | 2793.69 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 9.01 | 36.00 | 01-JAN-11:30 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.97 | 267.21 | 21-MAY-17:10 | 1768.58 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.57 | 22.79 | 01-JAN-09:20 | 860.01 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 33.02 | 422.10 | 12-MAR-17:10 | 2793.68 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.69 | 36.00 | 01-JAN-09:20 | 1358.45 | 03-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 21.04 | 267.21 | 05-MAR-18:10 | 1768.52 | 03-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.63 | 22.79 | 01-JAN-11:00 | 859.95 | 03-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 529.19 | 367.92 | 01-JAN-00:10 | 201652.63 | 13-FEB-07:10 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
ElectricityPurchased:Facility | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
ElectricityPurchased:Plant | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
Cogeneration:ElectricityPurchased | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
ElectricityNet:Plant | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
Cogeneration:ElectricityNet | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
General:Cogeneration:ElectricityNet | 1650.93 | 13840.93 | 09-JUL-17:40 | 242674.82 | 13-FEB-07:10 |
Heating:Electricity | 124.85 | 0.00 | 01-JAN-00:10 | 195320.41 | 13-FEB-07:10 |
General:Heating:Electricity | 124.85 | 0.00 | 01-JAN-00:10 | 195320.41 | 13-FEB-07:10 |
Fans:Electricity | 71.99 | 0.00 | 01-JAN-00:10 | 14770.08 | 02-AUG-16:00 |
General:Fans:Electricity | 71.99 | 0.00 | 01-JAN-00:10 | 14770.08 | 02-AUG-16:00 |
ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 305.46 | 0.00 | 01-JAN-00:10 | 70815.12 | 07-JUL-16:00 |
General:Cooling:Electricity | 305.46 | 0.00 | 01-JAN-00:10 | 70815.12 | 07-JUL-16:00 |
Electricity:Plant | 48.30 | 0.00 | 01-JAN-00:10 | 6221.35 | 30-JAN-13:00 |
WaterSystems:Electricity | 48.15 | 0.00 | 01-JAN-00:10 | 6214.50 | 30-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 48.15 | 0.00 | 01-JAN-00:10 | 6214.50 | 30-JAN-13:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 05-JAN-06:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 05-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 8.50 | 0.00 | 01-JAN-00:10 | 917.25 | 03-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2717.34 | 0.00 | 01-JAN-00:10 | 415023.22 | 07-JUL-16:00 |
EnergyTransfer:Building | 1240.71 | 0.00 | 01-JAN-00:10 | 160455.30 | 02-AUG-15:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 250.78 | 0.00 | 01-JAN-00:10 | 25116.00 | 21-AUG-08:00 |
Heating:EnergyTransfer | 61.05 | 0.00 | 01-JAN-00:10 | 145500.95 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 2640.22 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 61.05 | 0.00 | 01-JAN-00:10 | 145500.95 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 2640.22 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1179.66 | 0.00 | 01-JAN-00:10 | 160455.30 | 02-AUG-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 250.78 | 0.00 | 01-JAN-00:10 | 25116.00 | 21-AUG-08:00 |
General:Cooling:EnergyTransfer | 1179.66 | 0.00 | 01-JAN-00:10 | 160455.30 | 02-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 250.78 | 0.00 | 01-JAN-00:10 | 25116.00 | 21-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.29 | 0.00 | 01-JAN-00:10 | 13160.48 | 13-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.37 | 0.00 | 01-JAN-00:10 | 13160.48 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 11.37 | 0.00 | 01-JAN-00:10 | 13160.48 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.91 | 0.00 | 01-JAN-00:10 | 10435.40 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.91 | 0.00 | 01-JAN-00:10 | 10435.40 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.53 | 0.00 | 01-JAN-00:10 | 7010.52 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.93 | 0.00 | 01-JAN-00:10 | 7010.52 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.93 | 0.00 | 01-JAN-00:10 | 7010.52 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.60 | 0.00 | 01-JAN-00:10 | 4333.73 | 10-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 20.60 | 0.00 | 01-JAN-00:10 | 4333.73 | 10-JUL-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 26.54 | 0.00 | 01-JAN-00:10 | 4688.62 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.48 | 0.00 | 01-JAN-00:10 | 3512.36 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.48 | 0.00 | 01-JAN-00:10 | 3512.36 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.06 | 0.00 | 01-JAN-00:10 | 4688.62 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.06 | 0.00 | 01-JAN-00:10 | 4688.62 | 18-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 182.59 | 0.00 | 01-JAN-00:10 | 18770.50 | 21-AUG-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.40 | 0.00 | 01-JAN-00:10 | 14271.03 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.40 | 0.00 | 01-JAN-00:10 | 14271.03 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 182.20 | 0.00 | 01-JAN-00:10 | 18770.50 | 21-AUG-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 182.20 | 0.00 | 01-JAN-00:10 | 18770.50 | 21-AUG-07:50 |
EnergyTransfer:Zone:CORE_TOP | 179.94 | 0.00 | 01-JAN-00:10 | 26823.66 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.10 | 0.00 | 01-JAN-00:10 | 26823.66 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.10 | 0.00 | 01-JAN-00:10 | 26823.66 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 176.84 | 0.00 | 01-JAN-00:10 | 20701.52 | 07-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 176.84 | 0.00 | 01-JAN-00:10 | 20701.52 | 07-JUL-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.98 | 0.00 | 01-JAN-00:10 | 9189.41 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.86 | 0.00 | 01-JAN-00:10 | 9189.41 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.86 | 0.00 | 01-JAN-00:10 | 9189.41 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.12 | 0.00 | 01-JAN-00:10 | 7285.37 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.12 | 0.00 | 01-JAN-00:10 | 7285.37 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.21 | 0.00 | 01-JAN-00:10 | 8168.13 | 07-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.50 | 0.00 | 01-JAN-00:10 | 7734.20 | 13-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.50 | 0.00 | 01-JAN-00:10 | 7734.20 | 13-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.71 | 0.00 | 01-JAN-00:10 | 8168.13 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.71 | 0.00 | 01-JAN-00:10 | 8168.13 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.61 | 0.00 | 01-JAN-00:10 | 11008.16 | 10-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.20 | 0.00 | 01-JAN-00:10 | 10392.15 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.20 | 0.00 | 01-JAN-00:10 | 10392.15 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.42 | 0.00 | 01-JAN-00:10 | 11008.16 | 10-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 53.42 | 0.00 | 01-JAN-00:10 | 11008.16 | 10-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.78 | 0.00 | 01-JAN-00:10 | 8266.86 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.05 | 0.00 | 01-JAN-00:10 | 7673.26 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.05 | 0.00 | 01-JAN-00:10 | 7673.26 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.73 | 0.00 | 01-JAN-00:10 | 8266.86 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.73 | 0.00 | 01-JAN-00:10 | 8266.86 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.23 | 0.00 | 01-JAN-00:10 | 7040.50 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.74 | 0.00 | 01-JAN-00:10 | 7040.50 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.74 | 0.00 | 01-JAN-00:10 | 7040.50 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.49 | 0.00 | 01-JAN-00:10 | 5975.69 | 09-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.49 | 0.00 | 01-JAN-00:10 | 5975.69 | 09-AUG-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 35.35 | 0.00 | 01-JAN-00:10 | 6811.20 | 07-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.25 | 0.00 | 01-JAN-00:10 | 4893.80 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.25 | 0.00 | 01-JAN-00:10 | 4893.80 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.10 | 0.00 | 01-JAN-00:10 | 6811.20 | 07-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.10 | 0.00 | 01-JAN-00:10 | 6811.20 | 07-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 57.44 | 0.00 | 01-JAN-00:10 | 10548.87 | 03-FEB-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.22 | 0.00 | 01-JAN-00:10 | 10548.87 | 03-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.22 | 0.00 | 01-JAN-00:10 | 10548.87 | 03-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.22 | 0.00 | 01-JAN-00:10 | 10514.13 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 49.22 | 0.00 | 01-JAN-00:10 | 10514.13 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.39 | 0.00 | 01-JAN-00:10 | 6770.56 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.36 | 0.00 | 01-JAN-00:10 | 4888.54 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.36 | 0.00 | 01-JAN-00:10 | 4888.54 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.03 | 0.00 | 01-JAN-00:10 | 6770.56 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.03 | 0.00 | 01-JAN-00:10 | 6770.56 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.39 | 0.00 | 01-JAN-00:10 | 7833.97 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.87 | 0.00 | 01-JAN-00:10 | 7833.97 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.87 | 0.00 | 01-JAN-00:10 | 7833.97 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.52 | 0.00 | 01-JAN-00:10 | 6508.36 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.52 | 0.00 | 01-JAN-00:10 | 6508.36 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.04 | 0.00 | 01-JAN-00:10 | 7800.60 | 07-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.51 | 0.00 | 01-JAN-00:10 | 5559.46 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.51 | 0.00 | 01-JAN-00:10 | 5559.46 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.54 | 0.00 | 01-JAN-00:10 | 7800.60 | 07-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.54 | 0.00 | 01-JAN-00:10 | 7800.60 | 07-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.56 | 0.00 | 01-JAN-00:10 | 10112.34 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.56 | 0.00 | 01-JAN-00:10 | 8290.70 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.56 | 0.00 | 01-JAN-00:10 | 8290.70 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.00 | 0.00 | 01-JAN-00:10 | 10112.34 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.00 | 0.00 | 01-JAN-00:10 | 10112.34 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.06 | 0.00 | 01-JAN-00:10 | 7662.17 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.65 | 0.00 | 01-JAN-00:10 | 5586.24 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.65 | 0.00 | 01-JAN-00:10 | 5586.24 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.41 | 0.00 | 01-JAN-00:10 | 7662.17 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.41 | 0.00 | 01-JAN-00:10 | 7662.17 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
EnergyTransfer:HVAC | 1431.26 | 0.00 | 01-JAN-00:10 | 254041.95 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 124.85 | 0.00 | 01-JAN-00:10 | 195320.41 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1306.42 | 0.00 | 01-JAN-00:10 | 254041.95 | 07-JUL-16:00 |
EnergyTransfer:Plant | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterSystems:EnergyTransfer | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.004 | -250.775 | 0.000 | 0.000 | 33.035 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -104.615 |
CORE_MID | 0.000 | 0.000 | 0.397 | -182.195 | 0.000 | 0.000 | 34.299 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.854 |
CORE_TOP | 0.000 | 0.000 | 3.098 | -176.845 | 0.000 | 0.000 | 34.989 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -48.596 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.865 | -40.117 | 0.000 | 0.000 | 7.484 | 9.014 | 24.333 | 18.207 | 0.000 | 0.135 | 2.148 | 0.000 | -25.729 | 0.000 | -2.339 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.500 | -36.705 | 0.000 | 0.000 | 4.690 | 5.569 | 15.404 | 29.314 | 0.000 | 0.086 | 0.001 | 0.000 | -15.802 | 0.000 | -1.592 | -4.465 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.197 | -53.415 | 0.000 | 0.000 | 7.283 | 8.686 | 24.332 | 51.464 | 0.000 | 0.125 | 0.000 | 0.000 | -24.095 | 0.000 | -2.498 | -16.080 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.049 | -36.733 | 0.000 | 0.000 | 4.755 | 5.635 | 15.403 | 29.687 | 0.000 | 0.086 | 0.000 | 0.000 | -16.899 | 0.000 | -1.600 | -4.382 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.739 | -37.486 | 0.000 | 0.000 | 7.445 | 8.972 | 24.333 | 18.522 | 0.000 | 0.078 | 3.721 | 0.000 | -26.993 | 0.000 | -1.330 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.248 | -34.104 | 0.000 | 0.000 | 4.635 | 5.553 | 15.404 | 29.414 | 0.000 | 0.047 | 0.000 | 0.000 | -16.908 | 0.000 | -0.920 | -4.367 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 8.221 | -49.216 | 0.000 | 0.000 | 7.341 | 8.665 | 24.332 | 51.968 | 0.000 | 3.949 | 0.001 | 0.000 | -25.761 | 0.000 | -20.340 | -9.158 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.358 | -33.029 | 0.000 | 0.000 | 4.679 | 5.613 | 15.403 | 29.846 | 0.000 | 0.045 | 0.000 | 0.000 | -18.113 | 0.000 | -0.926 | -4.878 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.869 | -40.517 | 0.000 | 0.000 | 7.399 | 9.014 | 24.333 | 18.048 | 0.000 | 0.115 | 8.200 | 0.000 | -27.375 | 0.000 | -2.084 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.506 | -36.536 | 0.000 | 0.000 | 3.441 | 5.569 | 15.404 | 29.151 | 0.000 | 0.074 | 0.000 | 0.000 | -16.736 | 0.000 | -1.413 | -0.460 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.561 | -53.996 | 0.000 | 0.000 | 7.193 | 8.686 | 24.332 | 51.204 | 0.000 | 0.106 | 0.002 | 0.000 | -25.580 | 0.000 | -2.220 | -11.287 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.653 | -36.408 | 0.000 | 0.000 | 4.694 | 5.635 | 15.403 | 29.563 | 0.000 | 0.071 | 0.000 | 0.000 | -17.959 | 0.000 | -1.423 | -1.228 |
TOPFLOOR_PLENUM | 11.372 | -36.913 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.132 | 28.980 | 0.000 | 0.000 | 0.000 | -3.571 | -0.001 |
MIDFLOOR_PLENUM | 3.927 | -20.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.164 | 20.141 | 0.000 | 0.000 | 0.000 | -3.633 | -0.000 |
FIRSTFLOOR_PLENUM | 2.482 | -24.058 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.122 | 24.462 | 0.000 | 0.000 | 0.000 | -3.007 | -0.000 |
Total Facility | 17.781 | -81.571 | 43.266 | -1098.078 | 0.000 | 0.000 | 173.359 | 302.396 | 719.689 | 386.386 | 0.000 | 5.336 | 87.658 | 0.000 | -257.950 | 0.000 | -48.897 | -249.374 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-JUL-04:02 | 0.00 | 0.00 | 0.00 | -40730.82 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 34877.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 03-AUG-04:02 | 0.00 | 0.00 | 0.00 | -32003.92 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 29350.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -33566.09 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 30912.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:32 | 0.00 | 0.00 | 0.00 | -11781.09 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 1803.05 | 0.00 | 44.08 | 9511.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUN-08:23 | 0.00 | 0.00 | 0.00 | -11638.15 | 0.00 | 0.00 | 16.07 | 22.79 | 302.86 | 8311.94 | 0.00 | 0.00 | 3012.85 | 0.00 | -0.00 | 0.00 | -28.34 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:23 | 0.00 | 0.00 | 0.00 | -14408.66 | 0.00 | 0.00 | 25.35 | 36.00 | 478.41 | 8886.79 | 0.00 | 1.47 | 4980.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:02 | 0.00 | 0.00 | 0.00 | -13305.60 | 0.00 | 0.00 | 14.94 | 22.79 | 302.86 | 7718.48 | 0.00 | 70.91 | 5175.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | -5975.60 | 0.00 | 0.00 | 737.23 | 647.98 | 1435.25 | 3958.96 | 0.00 | 6.79 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -810.61 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -10429.10 | 0.00 | 0.00 | 16.09 | 22.79 | 302.86 | 7172.39 | 0.00 | 0.00 | 2915.70 | 0.00 | -0.00 | 0.00 | -0.73 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:13 | 0.00 | 0.00 | 0.00 | -11980.98 | 0.00 | 0.00 | 25.47 | 36.00 | 478.41 | 9070.50 | 0.00 | 0.00 | 2371.88 | 0.00 | -0.00 | 0.00 | -1.28 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -11199.20 | 0.00 | 0.00 | 14.89 | 22.79 | 302.86 | 8059.71 | 0.00 | 14.29 | 2784.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:32 | 0.00 | 0.00 | 0.00 | -8474.21 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 1884.01 | 0.00 | 38.88 | 6129.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:52 | 0.00 | 0.00 | 0.00 | -11960.66 | 0.00 | 0.00 | 15.00 | 22.79 | 302.86 | 7090.83 | 0.00 | 0.00 | 4531.65 | 0.00 | -0.00 | 0.00 | -2.47 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:13 | 0.00 | 0.00 | 0.00 | -12813.37 | 0.00 | 0.00 | 25.58 | 36.00 | 478.41 | 9058.84 | 0.00 | 0.00 | 3215.13 | 0.00 | -0.00 | 0.00 | -0.59 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -12820.96 | 0.00 | 0.00 | 13.71 | 22.79 | 302.86 | 7982.39 | 0.00 | 18.95 | 4480.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:00 | 0.00 | -10435.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 | 10394.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-06:03 | 0.00 | -4500.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4508.81 | 0.00 | -0.00 | 0.00 | -7.99 | 0.00 |
FIRSTFLOOR_PLENUM | 18-AUG-16:00 | 0.00 | -4688.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 4652.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 9146.87 | 0.00 | -184171.47 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 163853.38 | 0.00 | -5236.90 | 0.00 | -234.76 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-07:02 | 0.00 | 0.00 | 15840.31 | 0.00 | 0.00 | 0.00 | 896.19 | 2148.02 | 10194.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29079.37 |
CORE_MID | 09-JAN-06:01 | 0.00 | 0.00 | 17479.65 | 0.00 | 0.00 | 0.00 | 500.42 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21217.73 |
CORE_TOP | 09-JAN-05:11 | 0.00 | 0.00 | 31039.72 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33693.51 |
PERIMETER_TOP_ZN_3 | 12-FEB-07:23 | 0.00 | 0.00 | 10762.76 | 0.00 | 0.00 | 0.00 | 59.31 | 75.47 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3940.23 | 0.00 | -811.00 | -6624.72 |
PERIMETER_TOP_ZN_2 | 12-FEB-07:23 | 0.00 | 0.00 | 9680.77 | 0.00 | 0.00 | 0.00 | 37.59 | 47.78 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2534.63 | 0.00 | -548.52 | -6985.85 |
PERIMETER_TOP_ZN_1 | 12-FEB-06:03 | 0.00 | 0.00 | 12315.11 | 0.00 | 0.00 | 0.00 | 59.14 | 44.64 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3864.56 | 0.00 | -1011.49 | -8021.24 |
PERIMETER_TOP_ZN_4 | 12-FEB-07:23 | 0.00 | 0.00 | 9683.08 | 0.00 | 0.00 | 0.00 | 37.59 | 47.77 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2627.83 | 0.00 | -548.54 | -6894.93 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 8193.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3203.39 | 0.00 | -367.10 | -5182.69 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 6811.97 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2173.32 | 0.00 | -250.44 | -4742.36 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 10726.88 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 11926.17 | 0.00 | -4063.02 | 0.00 | -19874.04 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:02 | 0.00 | 0.00 | 6811.79 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1802.71 | 0.00 | -165.76 | -5197.47 |
PERIMETER_MID_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 8968.72 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2596.59 | 0.00 | -363.11 | -6568.46 |
PERIMETER_MID_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 7193.84 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1678.18 | 0.00 | -243.32 | -5626.49 |
PERIMETER_MID_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 10513.64 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2543.77 | 0.00 | -366.49 | -8162.81 |
PERIMETER_MID_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 7235.28 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1727.93 | 0.00 | -243.19 | -5618.30 |
TOPFLOOR_PLENUM | 13-FEB-06:12 | 14122.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -264.38 | -13857.89 |
MIDFLOOR_PLENUM | 09-JAN-07:06 | 7676.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -167.05 | -7509.47 |
FIRSTFLOOR_PLENUM | 09-JAN-07:01 | 3814.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -134.90 | -3679.41 |
Total Facility | 09-JAN-07:01 | 21228.04 | 0.00 | 139716.78 | 0.00 | 0.00 | 0.00 | 4626.03 | 10880.98 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30574.03 | 0.00 | -21125.47 | -147249.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2148 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9458 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3541 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.3708 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0724 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6074 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3375 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4729 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3437 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6854 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4105 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7199 | 2.7199 | 0.7697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2019 | 2.2019 | 0.7530 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3409 | 2.3409 | 0.7842 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7260 | 0.7260 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6961 | 0.6961 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8405 | 0.8405 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7672 | 0.7672 | 0.1534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5880 | 0.5880 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5987 | 0.5987 | 0.1197 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6889 | 0.6889 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6194 | 0.6194 | 0.1239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6311 | 0.6311 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6704 | 0.6704 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7450 | 0.7450 | 0.1587 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6974 | 0.6974 | 0.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2148 | 4.7223 | 5.2148 | 1.3375 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9458 | 4.3541 | 4.9458 | 1.3437 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.3708 | 5.0724 | 5.3708 | 1.4105 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3599 | 1.3599 | 0.7697 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1009 | 1.1009 | 0.7530 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1705 | 1.1705 | 0.7842 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3630 | 0.3630 | 0.1655 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3480 | 0.3480 | 0.1392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4203 | 0.4203 | 0.1681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3836 | 0.3836 | 0.1534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2940 | 0.2940 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2993 | 0.2993 | 0.1197 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3444 | 0.3444 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3097 | 0.3097 | 0.1239 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3156 | 0.3156 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3352 | 0.3352 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3725 | 0.3725 | 0.1587 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3487 | 0.3487 | 0.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6074 | 1.3375 | 1.3375 | 1.3375 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4729 | 1.3437 | 1.3437 | 1.3437 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6854 | 1.4105 | 1.4105 | 1.4105 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 128.50 |
Number of hours cooling loads not met | 115.67 |
Number of hours not met | 244.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 124.85 | 195320.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 305.46 | 70815.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 302.40 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.35 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 71.99 | 14770.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 48.15 | 6214.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1650.93 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1650.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.70 |
Space Heating | 25.06 |
Space Cooling | 61.31 |
Fans (All) | 14.45 |
Service Water Heating | 9.66 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 331.37 |
Subtotal | 331.37 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.32 |
Space Heating | 7.56 |
Space Cooling | 18.50 |
Fans (All) | 4.36 |
Service Water Heating | 2.92 |
Receptacle Equipment | 43.59 |
Miscellaneous | 4.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8395.33 | 364.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8701.50 | 58.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8684.17 | 75.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8716.83 | 43.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8727.33 | 32.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8692.67 | 67.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8611.00 | 149.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8395.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 364.67 | 0.00 | 0.00 | 0.00 |
Average | 8706.02 | 53.98 | 0.00 | 0.00 | 0.00 |
Sum | 156708.33 | 971.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128177.67 | 126.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 126.33 | 0.00 | 0.00 | 0.00 |
Average | 34136.31 | 7.02 | 0.00 | 0.00 | 0.00 |
Sum | 614453.67 | 126.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8240.83 | 519.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8224.17 | 535.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8185.17 | 574.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8199.33 | 560.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8163.17 | 596.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8403.67 | 356.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8256.67 | 503.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8164.17 | 595.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8220.33 | 539.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8210.33 | 549.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8167.17 | 592.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8178.67 | 581.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8117.83 | 642.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8519.33 | 240.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8618.17 | 141.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8645.33 | 114.67 | 0.00 | 0.00 | 0.00 |
Min | 8117.83 | 1.50 | 0.00 | 0.00 | 0.00 |
Max | 8758.50 | 642.17 | 0.00 | 0.00 | 0.00 |
Average | 8335.06 | 424.94 | 0.00 | 0.00 | 0.00 |
Sum | 150031.17 | 7648.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128085.67 | 218.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24903.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24903.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24907.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23945.17 | 963.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24903.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24903.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 963.83 | 0.00 | 0.00 | 0.00 |
Average | 34076.28 | 67.06 | 0.00 | 0.00 | 0.00 |
Sum | 613373.00 | 1207.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124119E+11 | 12522.50 | 31-JAN-17:00 | 19.40 | 13.37 | 0.180201E+10 | 2606.39 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.128248E+11 | 17977.16 | 28-FEB-17:00 | 23.90 | 12.94 | 0.171281E+10 | 2606.64 | 22-FEB-14:09 | 23.90 | 12.94 |
March | 0.189853E+11 | 21022.54 | 31-MAR-06:03 | 17.30 | 16.12 | 0.214912E+10 | 2606.71 | 08-MAR-10:09 | 17.30 | 16.12 |
April | 0.197647E+11 | 30348.25 | 18-APR-06:03 | 13.30 | 12.06 | 0.191598E+10 | 2606.62 | 17-APR-09:09 | 13.30 | 12.06 |
May | 0.242797E+11 | 35859.96 | 30-MAY-06:03 | 20.78 | 18.26 | 0.207879E+10 | 2606.72 | 11-MAY-09:00 | 20.78 | 18.26 |
June | 0.270917E+11 | 38483.59 | 26-JUN-05:12 | 23.30 | 21.67 | 0.207195E+10 | 2606.67 | 09-JUN-09:00 | 23.30 | 21.67 |
July | 0.273470E+11 | 40732.33 | 07-JUL-04:02 | 25.22 | 21.53 | 0.192641E+10 | 2606.54 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.297441E+11 | 40723.27 | 03-AUG-04:02 | 23.90 | 22.21 | 0.216165E+10 | 2606.53 | 25-AUG-13:09 | 30.18 | 18.86 |
September | 0.252770E+11 | 36090.67 | 18-SEP-06:02 | 14.50 | 13.76 | 0.192001E+10 | 2606.65 | 15-SEP-09:00 | 14.50 | 13.76 |
October | 0.216297E+11 | 35125.05 | 10-OCT-06:02 | 15.00 | 14.30 | 0.199152E+10 | 2606.60 | 04-OCT-13:00 | 15.00 | 14.30 |
November | 0.173694E+11 | 20107.09 | 06-NOV-17:00 | 18.90 | 9.61 | 0.196401E+10 | 2606.75 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.140501E+11 | 16630.37 | 14-DEC-17:00 | 13.90 | 10.25 | 0.186452E+10 | 2606.56 | 13-DEC-10:09 | 13.90 | 10.25 |
Annual Sum or Average | 0.250775E+12 | 0.235588E+11 | ||||||||
Minimum of Months | 0.124119E+11 | 12522.50 | 13.30 | 9.61 | 0.171281E+10 | 2606.39 | 10.68 | 10.03 | ||
Maximum of Months | 0.297441E+11 | 40732.33 | 25.22 | 22.21 | 0.216165E+10 | 2606.75 | 30.18 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157433E+09 | 1586.00 | 28-JAN-17:25 | 11.40 | 4.15 | 0.00 | 0.00 | 01-JAN-00:10 | 11.40 | 4.15 |
February | 0.555100E+09 | 3588.69 | 26-FEB-14:07 | 24.50 | 12.58 | 0.00 | 0.00 | 01-FEB-00:10 | 24.50 | 12.58 |
March | 0.166994E+10 | 6839.98 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.285854E+10 | 7782.06 | 17-APR-15:10 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.449706E+10 | 8642.68 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.632473E+10 | 9260.24 | 27-JUN-14:40 | 32.20 | 23.14 | 0.00 | 0.00 | 01-JUN-00:10 | 32.20 | 23.14 |
July | 0.673533E+10 | 10318.28 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.700866E+10 | 10435.40 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.393205E+10 | 8963.05 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.200119E+10 | 6841.69 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.853317E+09 | 3359.21 | 05-NOV-14:43 | 23.80 | 18.47 | 0.00 | 0.00 | 01-NOV-00:10 | 23.80 | 18.47 |
December | 0.320352E+09 | 2489.44 | 10-DEC-14:40 | 17.77 | 8.37 | 0.00 | 0.00 | 01-DEC-00:10 | 17.77 | 8.37 |
Annual Sum or Average | 0.369137E+11 | 0.00 | ||||||||
Minimum of Months | 0.157433E+09 | 1586.00 | 11.40 | 4.15 | 0.00 | 0.00 | 11.40 | 4.15 | ||
Maximum of Months | 0.700866E+10 | 10435.40 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68376953.79 | 1927.05 | 14-JAN-06:01 | -6.7 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.7 | -7.8 |
February | 0.226511E+09 | 2142.33 | 03-FEB-06:01 | -8.4 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.4 | -9.9 |
March | 0.815164E+09 | 2225.04 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.138618E+10 | 3028.98 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.233532E+10 | 3624.57 | 30-MAY-15:30 | 29.20 | 21.54 | 0.00 | 0.00 | 01-MAY-00:10 | 29.20 | 21.54 |
June | 0.346679E+10 | 3981.13 | 26-JUN-06:03 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.383225E+10 | 4501.11 | 17-JUL-06:03 | 21.70 | 19.38 | 0.00 | 0.00 | 01-JUL-00:10 | 21.70 | 19.38 |
August | 0.414782E+10 | 4289.30 | 02-AUG-16:00 | 35.00 | 23.13 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.13 |
September | 0.255057E+10 | 3935.45 | 07-SEP-16:00 | 31.70 | 23.71 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 23.71 |
October | 0.117305E+10 | 2710.89 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.425842E+09 | 1808.33 | 08-NOV-07:03 | 4.40 | 1.76 | 0.00 | 0.00 | 01-NOV-00:10 | 4.40 | 1.76 |
December | 0.172344E+09 | 2067.57 | 09-DEC-06:11 | 2.20 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 2.20 | -1.0 |
Annual Sum or Average | 0.206002E+11 | 0.00 | ||||||||
Minimum of Months | 68376953.79 | 1808.33 | -8.4 | -9.9 | 0.00 | 0.00 | -8.4 | -9.9 | ||
Maximum of Months | 0.414782E+10 | 4501.11 | 35.00 | 23.71 | 0.00 | 0.00 | 35.00 | 23.71 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75211070.89 | 1763.09 | 13-JAN-06:11 | 3.90 | 2.25 | 0.00 | 0.00 | 01-JAN-00:10 | 3.90 | 2.25 |
February | 0.278948E+09 | 2471.41 | 23-FEB-07:03 | 5.00 | 3.70 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.70 |
March | 0.108957E+10 | 2582.88 | 06-MAR-07:03 | 2.80 | 0.11 | 0.00 | 0.00 | 01-MAR-00:10 | 2.80 | 0.11 |
April | 0.168206E+10 | 3140.24 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.262879E+10 | 3959.92 | 30-MAY-15:20 | 29.67 | 21.52 | 0.00 | 0.00 | 01-MAY-00:10 | 29.67 | 21.52 |
June | 0.380131E+10 | 4178.93 | 26-JUN-15:30 | 30.00 | 23.57 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 23.57 |
July | 0.419615E+10 | 4662.67 | 10-JUL-15:50 | 32.70 | 22.31 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 22.31 |
August | 0.467106E+10 | 4688.62 | 18-AUG-16:00 | 35.00 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 23.11 |
September | 0.317043E+10 | 4587.76 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.164139E+10 | 3550.87 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.610153E+09 | 1933.14 | 21-NOV-07:01 | -2.8 | -3.9 | 0.00 | 0.00 | 01-NOV-00:10 | -2.8 | -3.9 |
December | 0.213097E+09 | 2238.72 | 15-DEC-07:03 | 3.22 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 0.92 |
Annual Sum or Average | 0.240582E+11 | 0.00 | ||||||||
Minimum of Months | 75211070.89 | 1763.09 | -2.8 | -3.9 | 0.00 | 0.00 | -2.8 | -3.9 | ||
Maximum of Months | 0.467106E+10 | 4688.62 | 35.00 | 23.57 | 0.00 | 0.00 | 35.00 | 23.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832784E+10 | 8954.73 | 31-JAN-17:00 | 19.40 | 13.37 | 0.154467E+10 | 2296.12 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.942843E+10 | 10784.10 | 28-FEB-17:00 | 23.90 | 12.94 | 0.149469E+10 | 2591.45 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.139616E+11 | 14149.26 | 30-MAR-16:00 | 27.80 | 17.47 | 0.201175E+10 | 2606.60 | 13-MAR-13:00 | 27.80 | 17.47 |
April | 0.145352E+11 | 15068.27 | 18-APR-16:00 | 25.60 | 16.92 | 0.186336E+10 | 2606.61 | 17-APR-09:09 | 25.60 | 16.92 |
May | 0.179254E+11 | 17207.12 | 30-MAY-16:00 | 27.80 | 21.50 | 0.205820E+10 | 2606.71 | 24-MAY-09:09 | 27.80 | 21.50 |
June | 0.202139E+11 | 29557.58 | 26-JUN-05:12 | 23.30 | 21.67 | 0.206203E+10 | 2606.67 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.206021E+11 | 31415.80 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191776E+10 | 2606.56 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.221395E+11 | 32004.97 | 03-AUG-04:02 | 23.90 | 22.21 | 0.215520E+10 | 2606.54 | 25-AUG-09:09 | 24.97 | 18.13 |
September | 0.179309E+11 | 17698.49 | 11-SEP-06:03 | 19.50 | 18.37 | 0.190392E+10 | 2606.61 | 21-SEP-09:09 | 20.97 | 17.73 |
October | 0.147431E+11 | 15679.81 | 11-OCT-16:00 | 26.10 | 17.12 | 0.191038E+10 | 2606.58 | 10-OCT-09:39 | 26.10 | 17.12 |
November | 0.120463E+11 | 11741.33 | 06-NOV-17:00 | 18.90 | 9.61 | 0.178721E+10 | 2606.48 | 07-NOV-14:00 | 18.90 | 8.70 |
December | 0.103409E+11 | 9775.03 | 13-DEC-17:00 | 16.70 | 16.70 | 0.158615E+10 | 2516.83 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.182195E+12 | 0.222953E+11 | ||||||||
Minimum of Months | 0.832784E+10 | 8954.73 | 16.70 | 9.61 | 0.149469E+10 | 2296.12 | 16.70 | 8.70 | ||
Maximum of Months | 0.221395E+11 | 32004.97 | 27.80 | 22.21 | 0.215520E+10 | 2606.71 | 27.80 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.617929E+10 | 9120.56 | 20-JAN-17:00 | 16.70 | 11.48 | 0.148748E+10 | 2222.44 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.785765E+10 | 10610.98 | 28-FEB-17:00 | 23.90 | 12.94 | 0.142045E+10 | 2539.06 | 28-FEB-14:00 | 23.90 | 12.94 |
March | 0.134536E+11 | 16101.24 | 30-MAR-16:00 | 27.80 | 17.47 | 0.190356E+10 | 2606.56 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.145290E+11 | 17150.42 | 17-APR-16:00 | 28.90 | 16.41 | 0.180573E+10 | 2606.62 | 12-APR-13:50 | 28.90 | 16.41 |
May | 0.183687E+11 | 19397.47 | 30-MAY-15:30 | 29.20 | 21.54 | 0.203692E+10 | 2606.63 | 22-MAY-09:39 | 29.20 | 21.54 |
June | 0.212679E+11 | 32434.12 | 26-JUN-05:12 | 23.30 | 21.67 | 0.205586E+10 | 2606.65 | 06-JUN-09:09 | 23.30 | 21.67 |
July | 0.218326E+11 | 33163.23 | 07-JUL-04:02 | 25.22 | 21.53 | 0.191485E+10 | 2606.61 | 03-JUL-09:09 | 25.22 | 21.53 |
August | 0.232736E+11 | 33562.07 | 14-AUG-04:02 | 24.22 | 20.90 | 0.215245E+10 | 2606.64 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.177465E+11 | 19449.84 | 07-SEP-16:00 | 31.70 | 23.71 | 0.188321E+10 | 2606.67 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.137939E+11 | 16567.35 | 11-OCT-16:00 | 26.10 | 17.12 | 0.181717E+10 | 2606.60 | 11-OCT-09:00 | 26.10 | 17.12 |
November | 0.107716E+11 | 10317.21 | 06-NOV-17:00 | 18.90 | 9.61 | 0.164271E+10 | 2542.22 | 06-NOV-14:00 | 18.90 | 9.61 |
December | 0.777041E+10 | 9805.13 | 13-DEC-17:00 | 16.70 | 16.70 | 0.148499E+10 | 2425.50 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.176845E+12 | 0.216054E+11 | ||||||||
Minimum of Months | 0.617929E+10 | 9120.56 | 16.70 | 9.61 | 0.142045E+10 | 2222.44 | 16.70 | 9.61 | ||
Maximum of Months | 0.232736E+11 | 33562.07 | 31.70 | 23.71 | 0.215245E+10 | 2606.67 | 29.20 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357369E+09 | 1879.57 | 31-JAN-16:50 | 19.50 | 13.40 | 0.308018E+09 | 465.52 | 31-JAN-14:00 | 19.50 | 13.40 |
February | 0.865568E+09 | 2529.64 | 28-FEB-15:40 | 23.87 | 12.92 | 0.289403E+09 | 549.47 | 28-FEB-14:00 | 23.87 | 12.92 |
March | 0.239130E+10 | 4688.03 | 30-MAR-15:50 | 27.80 | 17.41 | 0.380757E+09 | 549.48 | 29-MAR-13:00 | 27.80 | 17.41 |
April | 0.311742E+10 | 5065.85 | 19-APR-14:30 | 26.15 | 17.54 | 0.367294E+09 | 549.49 | 12-APR-13:50 | 26.15 | 17.54 |
May | 0.463260E+10 | 6513.62 | 30-MAY-15:00 | 30.60 | 21.44 | 0.424976E+09 | 549.49 | 19-MAY-09:39 | 30.60 | 21.44 |
June | 0.626199E+10 | 7512.76 | 25-JUN-18:53 | 29.40 | 22.34 | 0.433617E+09 | 549.50 | 02-JUN-09:00 | 29.40 | 22.34 |
July | 0.653065E+10 | 11780.92 | 16-JUL-18:32 | 31.67 | 22.10 | 0.404446E+09 | 549.48 | 03-JUL-09:09 | 31.67 | 22.10 |
August | 0.679469E+10 | 8410.81 | 20-AUG-16:42 | 27.88 | 24.54 | 0.454295E+09 | 549.49 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.428208E+10 | 6347.10 | 06-SEP-14:30 | 30.25 | 23.24 | 0.392534E+09 | 549.50 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.260031E+10 | 4395.39 | 02-OCT-14:40 | 26.70 | 20.10 | 0.363774E+09 | 549.47 | 19-OCT-13:39 | 23.33 | 19.60 |
November | 0.156694E+10 | 2158.84 | 02-NOV-15:50 | 22.30 | 16.05 | 0.326181E+09 | 529.81 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.716846E+09 | 2011.61 | 13-DEC-15:00 | 18.30 | 16.86 | 0.301250E+09 | 501.20 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.401178E+11 | 0.444655E+10 | ||||||||
Minimum of Months | 0.357369E+09 | 1879.57 | 18.30 | 12.92 | 0.289403E+09 | 465.52 | 18.30 | 12.92 | ||
Maximum of Months | 0.679469E+10 | 11780.92 | 31.67 | 24.54 | 0.454295E+09 | 549.50 | 31.67 | 22.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443221E+09 | 1547.08 | 31-JAN-15:10 | 20.92 | 13.08 | 0.195149E+09 | 291.63 | 31-JAN-14:00 | 20.92 | 13.08 |
February | 0.894653E+09 | 2184.68 | 27-FEB-10:40 | 14.27 | 6.32 | 0.189010E+09 | 347.86 | 28-FEB-14:09 | 25.00 | 13.72 |
March | 0.219434E+10 | 3653.22 | 30-MAR-11:00 | 22.20 | 17.83 | 0.253269E+09 | 347.88 | 08-MAR-10:09 | 22.20 | 17.83 |
April | 0.306888E+10 | 7866.22 | 16-APR-10:02 | 22.85 | 14.78 | 0.243184E+09 | 347.88 | 12-APR-13:50 | 22.85 | 14.78 |
May | 0.435313E+10 | 11629.01 | 07-MAY-09:23 | 24.15 | 19.65 | 0.271550E+09 | 347.89 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.549544E+10 | 11635.36 | 04-JUN-08:23 | 23.30 | 17.57 | 0.275161E+09 | 347.88 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.575600E+10 | 11628.06 | 02-JUL-10:02 | 26.28 | 22.27 | 0.255885E+09 | 347.86 | 03-JUL-09:09 | 25.60 | 20.69 |
August | 0.585461E+10 | 10983.14 | 27-AUG-10:02 | 27.77 | 22.01 | 0.287532E+09 | 347.88 | 25-AUG-09:50 | 27.77 | 22.01 |
September | 0.400152E+10 | 9326.65 | 24-SEP-10:43 | 27.52 | 19.23 | 0.249488E+09 | 347.88 | 25-SEP-09:30 | 25.55 | 19.33 |
October | 0.240855E+10 | 4472.78 | 11-OCT-10:30 | 24.20 | 19.54 | 0.239529E+09 | 347.87 | 11-OCT-09:00 | 24.20 | 19.54 |
November | 0.145933E+10 | 1868.30 | 06-NOV-10:40 | 16.27 | 12.91 | 0.211440E+09 | 347.84 | 06-NOV-10:00 | 17.20 | 13.02 |
December | 0.776335E+09 | 1641.63 | 12-DEC-15:10 | 22.70 | 16.14 | 0.191887E+09 | 308.05 | 12-DEC-14:00 | 22.70 | 16.14 |
Annual Sum or Average | 0.367060E+11 | 0.286308E+10 | ||||||||
Minimum of Months | 0.443221E+09 | 1547.08 | 14.27 | 6.32 | 0.189010E+09 | 291.63 | 17.20 | 13.02 | ||
Maximum of Months | 0.585461E+10 | 11635.36 | 27.77 | 22.27 | 0.287532E+09 | 347.89 | 27.77 | 22.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135530E+10 | 4693.13 | 11-JAN-14:30 | 6.70 | 2.05 | 0.341109E+09 | 549.47 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.192639E+10 | 13787.20 | 26-FEB-14:32 | 24.80 | 12.68 | 0.317773E+09 | 549.49 | 21-FEB-14:00 | 24.80 | 12.68 |
March | 0.370347E+10 | 9614.19 | 30-MAR-13:40 | 27.43 | 17.97 | 0.407117E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.421227E+10 | 13094.67 | 16-APR-14:02 | 28.62 | 16.11 | 0.376928E+09 | 549.53 | 12-APR-13:50 | 28.62 | 16.11 |
May | 0.527135E+10 | 7824.51 | 29-MAY-13:02 | 28.80 | 20.58 | 0.424826E+09 | 549.49 | 15-MAY-13:09 | 28.80 | 20.58 |
June | 0.647590E+10 | 8968.21 | 25-JUN-16:12 | 33.13 | 22.15 | 0.432520E+09 | 549.50 | 02-JUN-13:09 | 33.13 | 22.15 |
July | 0.686686E+10 | 13554.27 | 16-JUL-13:53 | 33.90 | 23.22 | 0.404272E+09 | 549.48 | 03-JUL-09:09 | 33.90 | 23.22 |
August | 0.796549E+10 | 13996.96 | 20-AUG-14:02 | 28.77 | 24.15 | 0.454531E+09 | 549.49 | 25-AUG-09:50 | 27.23 | 18.71 |
September | 0.595578E+10 | 14325.03 | 24-SEP-14:02 | 28.40 | 19.93 | 0.395129E+09 | 549.50 | 22-SEP-13:50 | 28.40 | 19.93 |
October | 0.465783E+10 | 14407.92 | 09-OCT-14:23 | 27.50 | 19.51 | 0.386342E+09 | 549.49 | 04-OCT-13:00 | 27.50 | 19.51 |
November | 0.303544E+10 | 14006.45 | 11-NOV-14:23 | 21.10 | 11.76 | 0.365173E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.198982E+10 | 6339.95 | 08-DEC-14:10 | 12.80 | 5.52 | 0.342115E+09 | 549.47 | 07-DEC-14:00 | 12.80 | 5.52 |
Annual Sum or Average | 0.534159E+11 | 0.464784E+10 | ||||||||
Minimum of Months | 0.135530E+10 | 4693.13 | 6.70 | 2.05 | 0.317773E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.796549E+10 | 14407.92 | 33.90 | 24.15 | 0.454531E+09 | 549.53 | 33.90 | 23.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.494610E+09 | 1807.67 | 20-JAN-16:40 | 16.87 | 11.91 | 0.196492E+09 | 302.31 | 11-JAN-16:49 | 16.87 | 11.91 |
February | 0.921603E+09 | 4229.84 | 27-FEB-17:00 | 22.20 | 11.44 | 0.184859E+09 | 347.50 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.241750E+10 | 6374.77 | 30-MAR-16:00 | 27.80 | 17.47 | 0.239468E+09 | 347.84 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.323048E+10 | 11819.88 | 09-APR-17:33 | 21.30 | 11.08 | 0.228056E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.433264E+10 | 11759.97 | 21-MAY-18:23 | 24.75 | 19.04 | 0.263270E+09 | 347.84 | 22-MAY-09:50 | 22.43 | 19.37 |
June | 0.530095E+10 | 13305.25 | 11-JUN-16:02 | 32.70 | 21.37 | 0.271708E+09 | 347.85 | 02-JUN-09:00 | 32.70 | 21.37 |
July | 0.549900E+10 | 13218.32 | 23-JUL-18:32 | 28.50 | 21.82 | 0.254323E+09 | 347.84 | 03-JUL-09:09 | 28.50 | 21.82 |
August | 0.576557E+10 | 13200.41 | 13-AUG-17:02 | 31.10 | 22.35 | 0.286242E+09 | 347.84 | 25-AUG-09:00 | 27.80 | 18.82 |
September | 0.395943E+10 | 8983.04 | 17-SEP-17:23 | 24.70 | 20.50 | 0.243777E+09 | 347.84 | 19-SEP-13:09 | 24.90 | 16.60 |
October | 0.254118E+10 | 6631.95 | 11-OCT-16:00 | 26.10 | 17.12 | 0.227610E+09 | 347.83 | 16-OCT-13:00 | 25.00 | 19.11 |
November | 0.150730E+10 | 3847.37 | 06-NOV-16:00 | 20.60 | 10.48 | 0.208462E+09 | 347.80 | 06-NOV-14:00 | 20.60 | 10.48 |
December | 0.764315E+09 | 1946.68 | 11-DEC-16:00 | 21.10 | 15.91 | 0.193442E+09 | 323.54 | 11-DEC-16:10 | 21.02 | 15.88 |
Annual Sum or Average | 0.367346E+11 | 0.279771E+10 | ||||||||
Minimum of Months | 0.494610E+09 | 1807.67 | 16.87 | 10.48 | 0.184859E+09 | 302.31 | 16.87 | 10.48 | ||
Maximum of Months | 0.576557E+10 | 13305.25 | 32.70 | 22.35 | 0.286242E+09 | 347.85 | 32.70 | 21.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408946E+09 | 1780.93 | 31-JAN-16:40 | 19.60 | 13.44 | 0.308925E+09 | 454.53 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.912013E+09 | 2032.48 | 28-FEB-15:20 | 24.43 | 13.32 | 0.288164E+09 | 518.15 | 28-FEB-14:00 | 24.43 | 13.32 |
March | 0.226554E+10 | 2722.38 | 30-MAR-16:00 | 27.80 | 17.47 | 0.372879E+09 | 549.47 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.253382E+10 | 3045.32 | 19-APR-14:30 | 26.15 | 17.54 | 0.355811E+09 | 549.47 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.347695E+10 | 4627.94 | 30-MAY-15:00 | 30.60 | 21.44 | 0.421702E+09 | 549.48 | 18-MAY-09:20 | 30.60 | 21.44 |
June | 0.512220E+10 | 5399.13 | 28-JUN-14:30 | 30.85 | 23.20 | 0.434110E+09 | 549.49 | 09-JUN-09:00 | 30.85 | 23.20 |
July | 0.566254E+10 | 5936.11 | 10-JUL-15:30 | 32.50 | 22.22 | 0.404624E+09 | 549.48 | 03-JUL-09:09 | 32.50 | 22.22 |
August | 0.621877E+10 | 5975.69 | 09-AUG-15:00 | 32.80 | 23.20 | 0.454724E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.433889E+10 | 5675.74 | 06-SEP-14:30 | 30.25 | 23.24 | 0.400468E+09 | 549.49 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.306510E+10 | 4078.61 | 02-OCT-14:30 | 26.70 | 20.05 | 0.386642E+09 | 549.47 | 05-OCT-13:09 | 20.00 | 14.95 |
November | 0.225629E+10 | 2247.97 | 05-NOV-12:53 | 22.20 | 18.11 | 0.349792E+09 | 543.79 | 03-NOV-13:00 | 22.20 | 18.11 |
December | 0.122546E+10 | 1996.32 | 13-DEC-13:30 | 19.45 | 17.14 | 0.307829E+09 | 505.85 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.374865E+11 | 0.448567E+10 | ||||||||
Minimum of Months | 0.408946E+09 | 1780.93 | 19.45 | 13.32 | 0.288164E+09 | 454.53 | 18.30 | 13.32 | ||
Maximum of Months | 0.621877E+10 | 5975.69 | 32.80 | 23.24 | 0.454724E+09 | 549.49 | 33.30 | 23.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521503E+09 | 1350.15 | 31-JAN-15:00 | 21.10 | 12.97 | 0.197104E+09 | 296.01 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.882389E+09 | 1947.91 | 27-FEB-10:40 | 14.27 | 6.32 | 0.190881E+09 | 347.87 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.194473E+10 | 2651.78 | 14-MAR-11:00 | 20.60 | 15.46 | 0.254562E+09 | 347.88 | 08-MAR-10:20 | 20.60 | 15.46 |
April | 0.235101E+10 | 4358.38 | 17-APR-10:10 | 23.27 | 15.57 | 0.242402E+09 | 347.87 | 17-APR-09:09 | 23.27 | 15.57 |
May | 0.337499E+10 | 7219.48 | 07-MAY-09:23 | 24.15 | 19.65 | 0.272153E+09 | 347.89 | 11-MAY-09:00 | 17.20 | 13.27 |
June | 0.467864E+10 | 8365.43 | 11-JUN-10:02 | 25.28 | 14.81 | 0.275749E+09 | 347.88 | 09-JUN-09:00 | 25.28 | 14.81 |
July | 0.512568E+10 | 10184.10 | 04-JUL-09:52 | 27.20 | 23.54 | 0.256622E+09 | 347.86 | 17-JUL-09:00 | 27.80 | 22.02 |
August | 0.547793E+10 | 10427.76 | 27-AUG-09:52 | 27.20 | 21.81 | 0.288290E+09 | 347.86 | 18-AUG-13:00 | 27.20 | 21.81 |
September | 0.400396E+10 | 6326.20 | 08-SEP-09:30 | 26.65 | 22.11 | 0.254198E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.273633E+10 | 4477.17 | 10-OCT-10:20 | 24.23 | 18.95 | 0.252028E+09 | 347.87 | 04-OCT-13:00 | 24.23 | 18.95 |
November | 0.183288E+10 | 2491.47 | 06-NOV-10:10 | 14.87 | 12.62 | 0.233391E+09 | 347.87 | 08-NOV-10:09 | 12.25 | 6.43 |
December | 0.117476E+10 | 1480.98 | 13-DEC-12:00 | 20.00 | 17.41 | 0.200974E+09 | 321.05 | 13-DEC-10:00 | 20.00 | 17.41 |
Annual Sum or Average | 0.341048E+11 | 0.291835E+10 | ||||||||
Minimum of Months | 0.521503E+09 | 1350.15 | 14.27 | 6.32 | 0.190881E+09 | 296.01 | 12.25 | 6.43 | ||
Maximum of Months | 0.547793E+10 | 10427.76 | 27.20 | 23.54 | 0.288290E+09 | 347.89 | 27.80 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897642E+09 | 2752.56 | 28-JAN-14:40 | 11.67 | 4.40 | 0.317249E+09 | 532.20 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.138893E+10 | 9592.97 | 26-FEB-14:32 | 24.80 | 12.68 | 0.301969E+09 | 549.50 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.274531E+10 | 7774.39 | 30-MAR-16:10 | 27.62 | 17.53 | 0.394131E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.304919E+10 | 7892.78 | 17-APR-16:10 | 28.80 | 16.45 | 0.363742E+09 | 549.51 | 12-APR-13:39 | 28.80 | 16.45 |
May | 0.407314E+10 | 9042.73 | 30-MAY-12:00 | 29.40 | 21.24 | 0.415956E+09 | 549.49 | 09-MAY-13:09 | 29.40 | 21.24 |
June | 0.607471E+10 | 9864.54 | 06-JUN-16:20 | 33.90 | 21.85 | 0.431568E+09 | 567.21 | 06-JUN-12:09 | 33.90 | 21.85 |
July | 0.676155E+10 | 10295.70 | 07-JUL-16:10 | 35.50 | 23.98 | 0.404529E+09 | 591.68 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.832811E+10 | 11343.71 | 27-AUG-13:53 | 31.70 | 22.32 | 0.456556E+09 | 617.41 | 18-AUG-12:09 | 31.70 | 22.32 |
September | 0.623766E+10 | 10184.63 | 07-SEP-12:00 | 31.10 | 23.22 | 0.399709E+09 | 595.87 | 07-SEP-12:09 | 31.02 | 23.18 |
October | 0.467581E+10 | 11980.45 | 09-OCT-14:13 | 27.40 | 19.48 | 0.394841E+09 | 585.23 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.305605E+10 | 11569.44 | 11-NOV-13:53 | 21.10 | 11.67 | 0.374048E+09 | 549.49 | 21-NOV-14:20 | 9.27 | 3.66 |
December | 0.192902E+10 | 5911.67 | 12-DEC-13:50 | 22.52 | 17.00 | 0.335507E+09 | 549.49 | 04-DEC-14:09 | 22.52 | 17.00 |
Annual Sum or Average | 0.492171E+11 | 0.458980E+10 | ||||||||
Minimum of Months | 0.897642E+09 | 2752.56 | 11.67 | 4.40 | 0.301969E+09 | 532.20 | 9.27 | 3.66 | ||
Maximum of Months | 0.832811E+10 | 11980.45 | 35.50 | 23.98 | 0.456556E+09 | 617.41 | 33.90 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500511E+09 | 1459.65 | 23-JAN-17:00 | 10.00 | 3.54 | 0.197690E+09 | 302.58 | 23-JAN-16:00 | 10.00 | 3.54 |
February | 0.864726E+09 | 3101.61 | 27-FEB-17:00 | 22.20 | 11.44 | 0.186241E+09 | 345.74 | 28-FEB-14:00 | 25.00 | 13.71 |
March | 0.204595E+10 | 4311.14 | 30-MAR-16:00 | 27.80 | 17.47 | 0.244080E+09 | 347.83 | 30-MAR-13:09 | 27.80 | 17.47 |
April | 0.237616E+10 | 4904.03 | 17-APR-16:00 | 28.90 | 16.41 | 0.230555E+09 | 347.83 | 20-APR-13:00 | 23.90 | 16.60 |
May | 0.320600E+10 | 7058.10 | 29-MAY-16:03 | 30.00 | 20.55 | 0.267410E+09 | 347.84 | 22-MAY-09:09 | 30.00 | 20.55 |
June | 0.439905E+10 | 10543.48 | 04-JUN-16:32 | 31.50 | 19.59 | 0.274782E+09 | 347.85 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.477440E+10 | 10831.42 | 04-JUL-17:52 | 30.60 | 22.43 | 0.256266E+09 | 347.84 | 03-JUL-09:09 | 30.60 | 22.43 |
August | 0.531644E+10 | 11198.16 | 13-AUG-16:51 | 31.10 | 22.45 | 0.288210E+09 | 347.84 | 21-AUG-09:09 | 23.40 | 22.58 |
September | 0.383415E+10 | 8989.00 | 04-SEP-16:42 | 28.22 | 22.25 | 0.253690E+09 | 347.85 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.271621E+10 | 8608.05 | 09-OCT-16:53 | 26.70 | 19.37 | 0.247506E+09 | 347.84 | 10-OCT-09:09 | 21.05 | 17.87 |
November | 0.189760E+10 | 3870.44 | 06-NOV-16:30 | 19.75 | 10.05 | 0.227291E+09 | 347.82 | 15-NOV-14:00 | 21.70 | 11.58 |
December | 0.109805E+10 | 1628.40 | 11-DEC-16:10 | 21.02 | 15.88 | 0.199850E+09 | 335.47 | 12-DEC-14:50 | 22.80 | 16.32 |
Annual Sum or Average | 0.330292E+11 | 0.287357E+10 | ||||||||
Minimum of Months | 0.500511E+09 | 1459.65 | 10.00 | 3.54 | 0.186241E+09 | 302.58 | 10.00 | 3.54 | ||
Maximum of Months | 0.531644E+10 | 11198.16 | 31.50 | 22.45 | 0.288210E+09 | 347.85 | 30.60 | 22.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496577E+09 | 1837.19 | 31-JAN-16:50 | 19.50 | 13.40 | 0.310220E+09 | 477.26 | 31-JAN-14:00 | 19.50 | 13.40 |
February | 0.109530E+10 | 2570.82 | 28-FEB-15:30 | 24.15 | 13.12 | 0.294564E+09 | 549.47 | 28-FEB-14:30 | 24.15 | 13.12 |
March | 0.264179E+10 | 4181.98 | 30-MAR-16:00 | 27.80 | 17.47 | 0.395427E+09 | 549.47 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.311720E+10 | 4616.96 | 18-APR-14:00 | 27.20 | 15.86 | 0.377957E+09 | 549.49 | 12-APR-13:39 | 27.20 | 15.86 |
May | 0.444156E+10 | 5906.83 | 30-MAY-15:00 | 30.60 | 21.44 | 0.430933E+09 | 549.50 | 24-MAY-09:09 | 30.60 | 21.44 |
June | 0.592022E+10 | 7038.03 | 26-JUN-05:12 | 23.30 | 21.67 | 0.435107E+09 | 549.50 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.614273E+10 | 8473.77 | 16-JUL-18:32 | 31.67 | 22.10 | 0.405047E+09 | 549.48 | 03-JUL-09:09 | 31.67 | 22.10 |
August | 0.644393E+10 | 7978.78 | 14-AUG-04:02 | 24.22 | 20.90 | 0.454879E+09 | 549.47 | 18-AUG-13:00 | 33.30 | 22.95 |
September | 0.425345E+10 | 5789.69 | 06-SEP-14:30 | 30.25 | 23.24 | 0.398559E+09 | 549.49 | 21-SEP-09:09 | 20.97 | 17.73 |
October | 0.290247E+10 | 4130.94 | 02-OCT-14:40 | 26.70 | 20.10 | 0.379226E+09 | 549.48 | 11-OCT-09:30 | 21.70 | 18.27 |
November | 0.199177E+10 | 2134.59 | 03-NOV-15:20 | 21.50 | 17.22 | 0.342398E+09 | 547.96 | 03-NOV-13:00 | 21.50 | 17.22 |
December | 0.107115E+10 | 1991.65 | 13-DEC-13:30 | 19.45 | 17.14 | 0.307596E+09 | 518.14 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.405182E+11 | 0.453191E+10 | ||||||||
Minimum of Months | 0.496577E+09 | 1837.19 | 19.45 | 13.12 | 0.294564E+09 | 477.26 | 18.30 | 13.12 | ||
Maximum of Months | 0.644393E+10 | 8473.77 | 31.67 | 23.24 | 0.454879E+09 | 549.50 | 33.30 | 22.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.563971E+09 | 1509.35 | 31-JAN-12:00 | 17.20 | 13.29 | 0.145006E+09 | 288.08 | 31-JAN-15:39 | 20.37 | 13.40 |
February | 0.103599E+10 | 2775.84 | 27-FEB-10:00 | 12.80 | 5.65 | 0.141074E+09 | 338.72 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.235629E+10 | 3785.78 | 13-MAR-10:20 | 14.23 | 6.73 | 0.189813E+09 | 338.72 | 08-MAR-09:39 | 14.23 | 6.73 |
April | 0.305894E+10 | 6883.55 | 16-APR-10:53 | 26.10 | 15.47 | 0.180967E+09 | 338.74 | 18-APR-14:30 | 26.40 | 16.44 |
May | 0.415955E+10 | 11216.85 | 07-MAY-09:02 | 23.58 | 19.38 | 0.201514E+09 | 338.74 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.515468E+10 | 11182.77 | 11-JUN-09:43 | 24.72 | 14.58 | 0.203413E+09 | 338.74 | 05-JUN-07:40 | 24.72 | 14.58 |
July | 0.537530E+10 | 11641.57 | 04-JUL-09:52 | 27.20 | 23.54 | 0.189866E+09 | 338.74 | 03-JUL-07:40 | 27.20 | 23.54 |
August | 0.550625E+10 | 11959.36 | 27-AUG-09:52 | 27.20 | 21.81 | 0.212519E+09 | 338.73 | 14-AUG-07:19 | 27.20 | 21.81 |
September | 0.390707E+10 | 9841.98 | 04-SEP-10:02 | 26.97 | 22.50 | 0.185783E+09 | 338.75 | 11-SEP-07:30 | 20.85 | 19.50 |
October | 0.263330E+10 | 4676.47 | 11-OCT-10:20 | 23.73 | 19.29 | 0.179805E+09 | 338.72 | 03-OCT-10:39 | 23.73 | 19.29 |
November | 0.174897E+10 | 2668.40 | 06-NOV-09:50 | 14.03 | 12.24 | 0.162135E+09 | 338.71 | 08-NOV-09:00 | 11.70 | 6.14 |
December | 0.103564E+10 | 1624.83 | 13-DEC-12:00 | 20.00 | 17.41 | 0.144508E+09 | 308.27 | 13-DEC-13:39 | 19.07 | 17.05 |
Annual Sum or Average | 0.365360E+11 | 0.213640E+10 | ||||||||
Minimum of Months | 0.563971E+09 | 1509.35 | 12.80 | 5.65 | 0.141074E+09 | 288.08 | 11.70 | 6.14 | ||
Maximum of Months | 0.550625E+10 | 11959.36 | 27.20 | 23.54 | 0.212519E+09 | 338.75 | 27.20 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160409E+10 | 4931.02 | 27-JAN-14:30 | 3.35 | -2.1 | 0.348461E+09 | 549.48 | 05-JAN-14:00 | 3.35 | -2.1 |
February | 0.221353E+10 | 11176.03 | 26-FEB-14:03 | 24.50 | 12.58 | 0.325041E+09 | 549.49 | 21-FEB-14:00 | 24.50 | 12.58 |
March | 0.395582E+10 | 9038.58 | 30-MAR-13:40 | 27.43 | 17.97 | 0.420524E+09 | 549.50 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.417678E+10 | 7788.49 | 17-APR-13:50 | 28.72 | 16.68 | 0.386323E+09 | 549.51 | 12-APR-13:39 | 28.72 | 16.68 |
May | 0.503685E+10 | 7220.57 | 29-MAY-13:32 | 28.50 | 20.43 | 0.430935E+09 | 549.50 | 24-MAY-09:09 | 28.50 | 20.43 |
June | 0.609388E+10 | 7091.88 | 26-JUN-05:12 | 23.30 | 21.67 | 0.434576E+09 | 549.50 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.643275E+10 | 10474.81 | 16-JUL-13:53 | 33.90 | 23.22 | 0.405116E+09 | 549.48 | 03-JUL-09:09 | 33.90 | 23.22 |
August | 0.754648E+10 | 12376.46 | 27-AUG-13:53 | 31.70 | 22.32 | 0.455229E+09 | 549.48 | 10-AUG-13:00 | 31.70 | 22.32 |
September | 0.587125E+10 | 9821.06 | 17-SEP-14:43 | 28.12 | 22.39 | 0.400137E+09 | 549.49 | 22-SEP-13:39 | 26.50 | 17.31 |
October | 0.502931E+10 | 12812.45 | 09-OCT-14:13 | 27.40 | 19.48 | 0.397615E+09 | 562.34 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.354955E+10 | 12744.58 | 11-NOV-13:53 | 21.10 | 11.67 | 0.380633E+09 | 549.49 | 14-NOV-14:00 | 20.00 | 9.44 |
December | 0.248660E+10 | 6846.84 | 08-DEC-14:00 | 12.80 | 5.54 | 0.353230E+09 | 549.47 | 07-DEC-14:00 | 12.80 | 5.54 |
Annual Sum or Average | 0.539969E+11 | 0.473782E+10 | ||||||||
Minimum of Months | 0.160409E+10 | 4931.02 | 3.35 | -2.1 | 0.325041E+09 | 549.47 | 3.35 | -2.1 | ||
Maximum of Months | 0.754648E+10 | 12812.45 | 33.90 | 23.22 | 0.455229E+09 | 562.34 | 33.90 | 23.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.598406E+09 | 1683.29 | 27-JAN-16:40 | 4.40 | -1.7 | 0.198646E+09 | 309.85 | 11-JAN-16:49 | 4.40 | -1.7 |
February | 0.108077E+10 | 4142.88 | 27-FEB-17:00 | 22.20 | 11.44 | 0.188029E+09 | 347.83 | 28-FEB-14:50 | 25.00 | 13.71 |
March | 0.256865E+10 | 5986.48 | 30-MAR-16:00 | 27.80 | 17.47 | 0.248211E+09 | 347.83 | 29-MAR-13:00 | 27.80 | 17.47 |
April | 0.314977E+10 | 11160.22 | 09-APR-17:12 | 21.50 | 10.93 | 0.235732E+09 | 347.84 | 12-APR-13:39 | 28.53 | 16.91 |
May | 0.408521E+10 | 11931.91 | 21-MAY-17:32 | 25.97 | 19.50 | 0.269219E+09 | 347.85 | 17-MAY-09:50 | 25.97 | 19.50 |
June | 0.497170E+10 | 11898.51 | 11-JUN-15:52 | 32.80 | 21.45 | 0.274119E+09 | 347.85 | 09-JUN-09:00 | 32.80 | 21.45 |
July | 0.512584E+10 | 12405.08 | 04-JUL-17:52 | 30.60 | 22.43 | 0.255777E+09 | 347.84 | 03-JUL-09:09 | 30.60 | 22.43 |
August | 0.543115E+10 | 12819.98 | 13-AUG-16:51 | 31.10 | 22.45 | 0.287521E+09 | 347.84 | 10-AUG-13:00 | 31.10 | 22.45 |
September | 0.382059E+10 | 10801.72 | 04-SEP-16:12 | 27.97 | 22.70 | 0.249826E+09 | 347.84 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.273556E+10 | 9027.45 | 09-OCT-16:12 | 27.43 | 19.51 | 0.237021E+09 | 347.83 | 17-OCT-13:00 | 25.00 | 20.48 |
November | 0.182475E+10 | 4017.67 | 06-NOV-16:00 | 20.60 | 10.48 | 0.216981E+09 | 347.82 | 15-NOV-14:00 | 21.70 | 11.58 |
December | 0.101653E+10 | 1835.65 | 11-DEC-15:50 | 21.10 | 15.67 | 0.197789E+09 | 335.83 | 11-DEC-15:00 | 21.10 | 15.91 |
Annual Sum or Average | 0.364089E+11 | 0.285887E+10 | ||||||||
Minimum of Months | 0.598406E+09 | 1683.29 | 4.40 | -1.7 | 0.188029E+09 | 309.85 | 4.40 | -1.7 | ||
Maximum of Months | 0.543115E+10 | 12819.98 | 32.80 | 22.70 | 0.287521E+09 | 347.85 | 32.80 | 22.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3855069.72 | 15841.33 | 02-JAN-07:02 | 3.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 3855069.72 | |||
Minimum of Months | 0.00 | 0.00 | 1.80 | |
Maximum of Months | 3855069.72 | 15841.33 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368217E+10 | 12714.17 | 09-JAN-06:07 | -2.4 |
February | 0.233229E+10 | 14122.28 | 13-FEB-06:12 | -5.6 |
March | 0.756478E+09 | 4825.35 | 18-MAR-06:03 | 2.70 |
April | 0.413378E+09 | 5655.70 | 06-APR-05:03 | 0.18 |
May | 0.126997E+09 | 3646.73 | 10-MAY-05:03 | 8.98 |
June | 57389513.51 | 3253.43 | 08-JUN-05:03 | 11.70 |
July | 17282403.96 | 3238.01 | 07-JUL-04:02 | 25.22 |
August | 16625336.54 | 4091.16 | 10-AUG-05:03 | 24.40 |
September | 0.106245E+09 | 3117.84 | 29-SEP-05:03 | 12.30 |
October | 0.592147E+09 | 5548.26 | 26-OCT-06:03 | 2.20 |
November | 0.112023E+10 | 9667.82 | 22-NOV-07:02 | -3.2 |
December | 0.215079E+10 | 12800.04 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.113720E+11 | |||
Minimum of Months | 16625336.54 | 3117.84 | -5.6 | |
Maximum of Months | 0.368217E+10 | 14122.28 | 25.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157442E+10 | 7676.53 | 09-JAN-07:06 | -3.3 |
February | 0.838409E+09 | 6886.90 | 13-FEB-07:11 | -5.6 |
March | 0.155393E+09 | 2776.84 | 26-MAR-13:13 | 18.17 |
April | 33558835.32 | 2167.71 | 09-APR-17:12 | 21.50 |
May | 9702396.71 | 1849.52 | 14-MAY-16:33 | 25.60 |
June | 7577312.53 | 1560.95 | 11-JUN-09:02 | 23.58 |
July | 9642247.29 | 1903.59 | 30-JUL-10:43 | 26.73 |
August | 9060939.67 | 1939.13 | 14-AUG-04:02 | 24.22 |
September | 8811047.73 | 2185.62 | 17-SEP-11:23 | 26.40 |
October | 0.110670E+09 | 2841.70 | 09-OCT-16:12 | 27.43 |
November | 0.332216E+09 | 3398.23 | 11-NOV-11:13 | 17.60 |
December | 0.837960E+09 | 3939.52 | 04-DEC-07:03 | -3.3 |
Annual Sum or Average | 0.392742E+10 | |||
Minimum of Months | 7577312.53 | 1560.95 | -5.6 | |
Maximum of Months | 0.157442E+10 | 7676.53 | 27.43 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108365E+10 | 3814.31 | 09-JAN-07:01 | -3.3 |
February | 0.574393E+09 | 3384.76 | 13-FEB-08:18 | -4.8 |
March | 42214565.03 | 894.84 | 23-MAR-07:40 | 6.50 |
April | 8414383.13 | 1830.62 | 09-APR-16:23 | 21.70 |
May | 8954969.16 | 1767.83 | 29-MAY-14:10 | 28.48 |
June | 10974228.68 | 1574.58 | 18-JUN-11:23 | 26.95 |
July | 11724736.61 | 3036.55 | 07-JUL-04:02 | 25.22 |
August | 14134423.63 | 3209.34 | 14-AUG-04:02 | 24.22 |
September | 16819310.12 | 2259.63 | 17-SEP-11:23 | 26.40 |
October | 56634265.22 | 2465.88 | 22-OCT-11:13 | 21.13 |
November | 0.130902E+09 | 2946.24 | 26-NOV-13:23 | 18.30 |
December | 0.522737E+09 | 2801.29 | 10-DEC-12:53 | 15.60 |
Annual Sum or Average | 0.248155E+10 | |||
Minimum of Months | 8414383.13 | 894.84 | -4.8 | |
Maximum of Months | 0.108365E+10 | 3814.31 | 28.48 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243261E+09 | 17479.66 | 09-JAN-06:01 | -2.4 |
February | 0.103683E+09 | 17060.88 | 13-FEB-06:01 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 780349.51 | 7126.55 | 22-NOV-07:01 | -3.2 |
December | 49454344.56 | 15603.87 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.397179E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.243261E+09 | 17479.66 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161046E+10 | 31039.74 | 09-JAN-05:11 | -2.2 |
February | 0.732435E+09 | 30694.15 | 13-FEB-05:01 | -5.1 |
March | 28707667.49 | 24738.79 | 22-MAR-06:03 | 5.50 |
April | 3862636.37 | 20618.69 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 15142033.97 | 24645.70 | 26-OCT-06:03 | 2.20 |
November | 99205590.69 | 26686.47 | 22-NOV-06:01 | -3.3 |
December | 0.608577E+09 | 29252.06 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.309839E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.161046E+10 | 31039.74 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302206E+10 | 10538.75 | 09-JAN-05:11 | -2.2 |
February | 0.165017E+10 | 10762.84 | 12-FEB-07:23 | -12.5 |
March | 0.177070E+09 | 8971.20 | 23-MAR-05:12 | 6.10 |
April | 47147542.92 | 8637.67 | 06-APR-05:03 | 0.18 |
May | 301553.93 | 1507.77 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 77287198.38 | 9073.32 | 26-OCT-05:11 | 2.20 |
November | 0.451036E+09 | 9654.55 | 22-NOV-05:02 | -2.9 |
December | 0.143988E+10 | 10376.79 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.686496E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.5 | |
Maximum of Months | 0.302206E+10 | 10762.84 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160779E+10 | 9516.32 | 09-JAN-05:11 | -2.2 |
February | 0.838379E+09 | 9680.80 | 12-FEB-07:23 | -12.5 |
March | 87232307.06 | 8009.35 | 23-MAR-05:12 | 6.10 |
April | 22811462.74 | 7378.00 | 07-APR-06:02 | 2.80 |
May | 103671.55 | 518.36 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 213283.51 | 1421.89 | 29-SEP-06:03 | 12.88 |
October | 49885697.64 | 8114.46 | 26-OCT-05:11 | 2.20 |
November | 0.207875E+09 | 8605.63 | 22-NOV-05:02 | -2.9 |
December | 0.686072E+09 | 9351.79 | 04-DEC-05:11 | -2.8 |
Annual Sum or Average | 0.350036E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.5 | |
Maximum of Months | 0.160779E+10 | 9680.80 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190345E+10 | 12137.18 | 09-JAN-05:11 | -2.2 |
February | 0.103503E+10 | 12315.25 | 12-FEB-06:03 | -12.3 |
March | 0.121532E+09 | 10320.37 | 23-MAR-05:12 | 6.10 |
April | 40437582.70 | 9557.16 | 06-APR-06:02 | 1.20 |
May | 520281.22 | 2601.41 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 58835437.16 | 10267.29 | 26-OCT-05:11 | 2.20 |
November | 0.247406E+09 | 10780.53 | 25-NOV-06:01 | 0.68 |
December | 0.790157E+09 | 11820.82 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.419737E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.3 | |
Maximum of Months | 0.190345E+10 | 12315.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177559E+10 | 9509.45 | 09-JAN-05:11 | -2.2 |
February | 0.960550E+09 | 9683.10 | 12-FEB-07:23 | -12.5 |
March | 0.106220E+09 | 7846.98 | 23-MAR-05:12 | 6.10 |
April | 28784662.31 | 7373.92 | 07-APR-06:02 | 2.80 |
May | 628546.53 | 2466.50 | 11-MAY-06:03 | 8.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 335513.01 | 2236.75 | 29-SEP-06:03 | 12.88 |
October | 51195993.50 | 7891.97 | 26-OCT-05:11 | 2.20 |
November | 0.277348E+09 | 8662.17 | 22-NOV-05:02 | -2.9 |
December | 0.847958E+09 | 9314.66 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.404861E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.5 | |
Maximum of Months | 0.177559E+10 | 9683.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156167E+10 | 8049.59 | 09-JAN-05:02 | -2.2 |
February | 0.810211E+09 | 8193.78 | 13-FEB-05:01 | -5.1 |
March | 44481742.40 | 6680.75 | 22-MAR-06:03 | 5.50 |
April | 13836054.85 | 6722.52 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1514015.46 | 5513.19 | 26-OCT-06:03 | 2.20 |
November | 24258250.56 | 6912.71 | 22-NOV-06:01 | -3.3 |
December | 0.282800E+09 | 7433.64 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.273877E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.156167E+10 | 8193.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765519E+09 | 6766.70 | 09-JAN-05:02 | -2.2 |
February | 0.339879E+09 | 6812.07 | 13-FEB-05:01 | -5.1 |
March | 19270825.13 | 5561.22 | 18-MAR-06:03 | 2.70 |
April | 4080526.06 | 5412.55 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 1291069.74 | 3817.28 | 26-OCT-06:03 | 2.20 |
November | 6948242.89 | 5476.31 | 22-NOV-07:01 | -3.2 |
December | 0.111494E+09 | 6031.60 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.124848E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.765519E+09 | 6812.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291430E+10 | 10452.43 | 27-JAN-07:10 | -6.7 |
February | 0.180082E+10 | 10727.20 | 03-FEB-07:10 | -8.9 |
March | 0.732941E+09 | 8624.29 | 06-MAR-07:50 | 2.80 |
April | 0.409595E+09 | 9049.22 | 06-APR-06:10 | 1.20 |
May | 97289853.89 | 7871.31 | 11-MAY-06:03 | 8.17 |
June | 10956121.48 | 6061.58 | 08-JUN-06:07 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 11112061.80 | 3364.58 | 29-SEP-06:08 | 12.88 |
October | 0.358341E+09 | 8652.32 | 26-OCT-07:00 | 2.20 |
November | 0.722715E+09 | 9507.00 | 22-NOV-07:10 | -3.2 |
December | 0.116298E+10 | 9952.11 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.822105E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.291430E+10 | 10727.20 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803583E+09 | 6812.13 | 09-JAN-05:02 | -2.2 |
February | 0.388070E+09 | 6751.75 | 13-FEB-05:01 | -5.1 |
March | 17458083.11 | 5447.51 | 23-MAR-06:03 | 6.10 |
April | 4515092.27 | 5545.13 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 974498.26 | 3205.48 | 31-OCT-06:03 | 8.22 |
November | 12008942.73 | 5473.46 | 22-NOV-07:01 | -3.2 |
December | 0.131650E+09 | 6031.73 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.135826E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.803583E+09 | 6812.13 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151576E+10 | 8968.75 | 09-JAN-05:11 | -2.2 |
February | 0.715598E+09 | 8823.89 | 13-FEB-05:01 | -5.1 |
March | 26776605.07 | 7141.72 | 23-MAR-06:03 | 6.10 |
April | 6022708.95 | 7192.85 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 8986819.19 | 7158.92 | 30-OCT-06:03 | 8.90 |
November | 94596193.08 | 7834.25 | 22-NOV-06:01 | -3.3 |
December | 0.500969E+09 | 8401.51 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.286871E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.151576E+10 | 8968.75 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.833373E+09 | 7193.89 | 09-JAN-05:11 | -2.2 |
February | 0.361759E+09 | 7058.56 | 13-FEB-05:01 | -5.1 |
March | 18097504.24 | 5544.77 | 18-MAR-06:03 | 2.70 |
April | 3812389.99 | 5644.95 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 7256844.72 | 5563.44 | 26-OCT-06:03 | 2.20 |
November | 44240806.71 | 6005.98 | 22-NOV-06:01 | -3.3 |
December | 0.237770E+09 | 6552.96 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.150631E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.833373E+09 | 7193.89 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862169E+09 | 10513.68 | 09-JAN-05:11 | -2.2 |
February | 0.379439E+09 | 10351.28 | 13-FEB-05:01 | -5.1 |
March | 17922215.86 | 8371.66 | 23-MAR-06:03 | 6.10 |
April | 5044651.80 | 8444.86 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 7591129.71 | 8341.76 | 26-OCT-06:03 | 2.20 |
November | 44626718.35 | 8993.30 | 22-NOV-06:01 | -3.3 |
December | 0.243884E+09 | 9707.63 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.156068E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.862169E+09 | 10513.68 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870340E+09 | 7235.33 | 09-JAN-05:11 | -2.2 |
February | 0.400051E+09 | 7083.58 | 13-FEB-05:01 | -5.1 |
March | 18238764.21 | 5462.72 | 23-MAR-06:03 | 6.10 |
April | 4162977.99 | 5769.20 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 7101734.22 | 5467.53 | 26-OCT-06:03 | 2.20 |
November | 61705425.02 | 6011.19 | 22-NOV-06:01 | -3.3 |
December | 0.291387E+09 | 6570.28 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.165299E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.870340E+09 | 7235.33 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846055E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.762897E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.796776E+09 | 1358.45 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.675359E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699833E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.687181E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651426E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.744765E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.703252E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.808123E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.811693E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.826313E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.901367E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651426E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.846055E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.508129E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.460497E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.492356E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.424791E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.447103E+09 | 450.21 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439946E+09 | 450.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415308E+09 | 600.14 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471842E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436677E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.484045E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.494745E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493985E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556942E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415308E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508129E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765762E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.705338E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.777899E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.677143E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712140E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700772E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663635E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749752E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.692213E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.750902E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.748109E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.742755E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.868642E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.663635E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.777899E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507897E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.468127E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.503400E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.431347E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451973E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.442883E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420627E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477530E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.446712E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.500286E+09 | 859.95 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.490384E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493477E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.563464E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420627E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.507897E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.839329E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.757888E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.793132E+09 | 1358.45 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.673272E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699539E+09 | 774.31 | 02-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.686444E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651107E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.743416E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.700764E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.802629E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.805079E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.819465E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.897207E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651107E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.839329E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505975E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.458253E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491163E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.423886E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446374E+09 | 450.21 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439292E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.414667E+09 | 490.21 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471104E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435545E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.481922E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.492680E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.491780E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555264E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.414667E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505975E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.763932E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.704598E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.775420E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.675198E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.710688E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.699319E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.661869E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.747992E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.690150E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.748760E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.746697E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.740187E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.866481E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.661869E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.775420E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505576E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.465983E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.501880E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.429834E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450170E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.441854E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.419226E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.476238E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.444656E+09 | 859.95 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.498301E+09 | 859.95 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.487915E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.491638E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.561327E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.419226E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505576E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846055E+09 | 1358.45 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.762897E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.796776E+09 | 1358.45 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.675359E+09 | 1184.79 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699833E+09 | 947.97 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.687181E+09 | 774.31 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.651426E+09 | 947.97 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.744765E+09 | 1184.79 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.703252E+09 | 1358.45 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.808123E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.811693E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.826313E+09 | 1358.45 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.901367E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.651426E+09 | 774.31 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.846055E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.508129E+09 | 860.01 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.460497E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.492356E+09 | 860.01 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.424791E+09 | 750.07 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.447103E+09 | 450.21 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439946E+09 | 450.21 | 23-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415308E+09 | 600.14 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.471842E+09 | 750.07 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436677E+09 | 750.07 | 05-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.484045E+09 | 860.01 | 19-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.494745E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493961E+09 | 860.01 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556940E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415308E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508129E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765727E+09 | 1358.45 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.705338E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.777861E+09 | 1358.45 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.677143E+09 | 1184.79 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712140E+09 | 947.97 | 02-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700772E+09 | 947.97 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.663635E+09 | 947.97 | 19-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749752E+09 | 1184.79 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.692213E+09 | 1358.45 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.750900E+09 | 1358.45 | 19-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.748109E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.742755E+09 | 1358.45 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.868634E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.663635E+09 | 947.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.777861E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507897E+09 | 859.95 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.468127E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.503400E+09 | 859.95 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.431347E+09 | 859.95 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451973E+09 | 750.02 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.442883E+09 | 600.10 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420627E+09 | 750.02 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.477530E+09 | 750.02 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.446712E+09 | 859.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.500286E+09 | 859.95 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.490384E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493477E+09 | 859.95 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.563464E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420627E+09 | 600.10 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.507897E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846055E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458093E+09 |
February | 0.901968E+09 | 0.762897E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096236.59 | 0.390095E+09 |
March | 0.107774E+10 | 0.796776E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1385393.83 | 0.249948E+09 |
April | 0.956342E+09 | 0.675359E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3374076.72 | 0.157489E+09 |
May | 0.103597E+10 | 0.699833E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8553241.44 | 0.104576E+09 |
June | 0.103308E+10 | 0.687181E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33844452.61 | 52538627.89 |
July | 0.959235E+09 | 0.651426E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36610722.59 | 34943496.02 |
August | 0.107774E+10 | 0.744765E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35464134.03 | 22140447.45 |
September | 0.956342E+09 | 0.703252E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10893362.31 | 51274469.59 |
October | 0.994195E+09 | 0.808123E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3675417.43 | 0.167465E+09 |
November | 0.984487E+09 | 0.811693E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 426747.82 | 0.238546E+09 |
December | 0.959235E+09 | 0.826313E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.35 | 0.412315E+09 |
Annual Sum or Average | 0.119305E+11 | 0.901367E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135324E+09 | 0.233942E+10 |
Minimum of Months | 0.901968E+09 | 0.651426E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22140447.45 |
Maximum of Months | 0.107774E+10 | 0.846055E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36610722.59 | 0.458093E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.508129E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309153E+09 |
February | 0.571020E+09 | 0.460497E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 378644.20 | 0.265225E+09 |
March | 0.682301E+09 | 0.492356E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956293.62 | 0.172458E+09 |
April | 0.605444E+09 | 0.424791E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894532.26 | 0.108336E+09 |
May | 0.655854E+09 | 0.447103E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5165296.87 | 72318249.81 |
June | 0.654023E+09 | 0.439946E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22092678.72 | 35717735.93 |
July | 0.607275E+09 | 0.415308E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23773073.61 | 23842511.99 |
August | 0.682301E+09 | 0.471842E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23169191.13 | 15066536.64 |
September | 0.605444E+09 | 0.436677E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810629.02 | 34338317.40 |
October | 0.629407E+09 | 0.484045E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1890224.45 | 0.114852E+09 |
November | 0.623262E+09 | 0.494745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262434.35 | 0.162771E+09 |
December | 0.607275E+09 | 0.493985E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.80 | 0.277599E+09 |
Annual Sum or Average | 0.755301E+10 | 0.556942E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86393683.04 | 0.159168E+10 |
Minimum of Months | 0.571020E+09 | 0.415308E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15066536.64 |
Maximum of Months | 0.682301E+09 | 0.508129E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23773073.61 | 0.309153E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.765762E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486739E+09 |
February | 0.901968E+09 | 0.705338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51448.64 | 0.416863E+09 |
March | 0.107774E+10 | 0.777899E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 944238.14 | 0.274260E+09 |
April | 0.956342E+09 | 0.677143E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2415428.36 | 0.164227E+09 |
May | 0.103597E+10 | 0.712140E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7831160.32 | 0.105601E+09 |
June | 0.103308E+10 | 0.700772E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33635075.08 | 51888511.90 |
July | 0.959235E+09 | 0.663635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36206214.37 | 34785567.78 |
August | 0.107774E+10 | 0.749752E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34017089.71 | 22919662.61 |
September | 0.956342E+09 | 0.692213E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8884910.42 | 53579776.16 |
October | 0.994195E+09 | 0.750902E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1386388.93 | 0.183711E+09 |
November | 0.984487E+09 | 0.748109E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264415E+09 |
December | 0.959235E+09 | 0.742755E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439176E+09 |
Annual Sum or Average | 0.119305E+11 | 0.868642E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125372E+09 | 0.249817E+10 |
Minimum of Months | 0.901968E+09 | 0.663635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22919662.61 |
Maximum of Months | 0.107774E+10 | 0.777899E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36206214.37 | 0.486739E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.507897E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310017E+09 |
February | 0.570983E+09 | 0.468127E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 472399.00 | 0.265387E+09 |
March | 0.682256E+09 | 0.503400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 735239.84 | 0.176300E+09 |
April | 0.605404E+09 | 0.431347E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1950053.28 | 0.108973E+09 |
May | 0.655811E+09 | 0.451973E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5382589.14 | 71576161.31 |
June | 0.653980E+09 | 0.442883E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22029870.62 | 35930323.04 |
July | 0.607235E+09 | 0.420627E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24027171.37 | 23658023.33 |
August | 0.682256E+09 | 0.477530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22708865.54 | 15980425.84 |
September | 0.605404E+09 | 0.446712E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6880838.19 | 34822793.38 |
October | 0.629366E+09 | 0.500286E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1757477.16 | 0.115351E+09 |
November | 0.623221E+09 | 0.490384E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27167.48 | 0.163708E+09 |
December | 0.607235E+09 | 0.493477E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278081E+09 |
Annual Sum or Average | 0.755252E+10 | 0.563464E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85971671.62 | 0.159979E+10 |
Minimum of Months | 0.570983E+09 | 0.420627E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15980425.84 |
Maximum of Months | 0.682256E+09 | 0.507897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24027171.37 | 0.310017E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.839329E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261853E+09 |
February | 0.901968E+09 | 0.757888E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644081.15 | 0.218037E+09 |
March | 0.107774E+10 | 0.793132E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1093997.27 | 0.133784E+09 |
April | 0.956342E+09 | 0.673272E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2522215.59 | 79662562.37 |
May | 0.103597E+10 | 0.699539E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222536.42 | 52930479.72 |
June | 0.103308E+10 | 0.686444E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19151260.58 | 26940043.09 |
July | 0.959235E+09 | 0.651107E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21278383.08 | 18110179.30 |
August | 0.107774E+10 | 0.743416E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19976142.45 | 11516721.68 |
September | 0.956342E+09 | 0.700764E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5903722.85 | 31066198.88 |
October | 0.994195E+09 | 0.802629E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1786770.94 | 0.101972E+09 |
November | 0.984487E+09 | 0.805079E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41463.60 | 0.145604E+09 |
December | 0.959235E+09 | 0.819465E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.91 | 0.248169E+09 |
Annual Sum or Average | 0.119305E+11 | 0.897207E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77620822.83 | 0.132965E+10 |
Minimum of Months | 0.901968E+09 | 0.651107E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11516721.68 |
Maximum of Months | 0.107774E+10 | 0.839329E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21278383.08 | 0.261853E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.505975E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177545E+09 |
February | 0.571020E+09 | 0.458253E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186289.72 | 0.149687E+09 |
March | 0.682301E+09 | 0.491163E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 616367.68 | 94968896.09 |
April | 0.605444E+09 | 0.423886E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1159380.81 | 56887683.43 |
May | 0.655854E+09 | 0.446374E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2860725.98 | 38413124.06 |
June | 0.654023E+09 | 0.439292E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12013045.46 | 19186538.19 |
July | 0.607275E+09 | 0.414667E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13028820.66 | 13045469.87 |
August | 0.682301E+09 | 0.471104E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12442649.70 | 8522136.85 |
September | 0.605444E+09 | 0.435545E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3544785.46 | 21482166.69 |
October | 0.629407E+09 | 0.481922E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 822404.07 | 71077809.65 |
November | 0.623262E+09 | 0.492680E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8724.63 | 0.101041E+09 |
December | 0.607275E+09 | 0.491780E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168108E+09 |
Annual Sum or Average | 0.755301E+10 | 0.555264E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46683194.18 | 0.919966E+09 |
Minimum of Months | 0.571020E+09 | 0.414667E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8522136.85 |
Maximum of Months | 0.682301E+09 | 0.505975E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13028820.66 | 0.177545E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.763932E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431483E+10 |
February | 0.901968E+09 | 0.704598E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 620510.31 | 0.315259E+10 |
March | 0.107774E+10 | 0.775420E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27230583.43 | 0.226055E+10 |
April | 0.956342E+09 | 0.675198E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141056E+09 | 0.127743E+10 |
May | 0.103597E+10 | 0.710688E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333719E+09 | 0.673527E+09 |
June | 0.103308E+10 | 0.699319E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943175E+09 | 0.249548E+09 |
July | 0.959235E+09 | 0.661869E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977167E+09 | 0.186271E+09 |
August | 0.107774E+10 | 0.747992E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108313E+10 | 0.114920E+09 |
September | 0.956342E+09 | 0.690150E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374366E+09 | 0.452690E+09 |
October | 0.994195E+09 | 0.748760E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68474415.44 | 0.175723E+10 |
November | 0.984487E+09 | 0.746697E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268247E+10 |
December | 0.959235E+09 | 0.740187E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321815E+10 |
Annual Sum or Average | 0.119305E+11 | 0.866481E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394894E+10 | 0.203402E+11 |
Minimum of Months | 0.901968E+09 | 0.661869E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114920E+09 |
Maximum of Months | 0.107774E+10 | 0.775420E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108313E+10 | 0.431483E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.505576E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177925E+09 |
February | 0.570983E+09 | 0.465983E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217525.87 | 0.149384E+09 |
March | 0.682256E+09 | 0.501880E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433940.83 | 97365958.43 |
April | 0.605404E+09 | 0.429834E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091661.31 | 57780440.86 |
May | 0.655811E+09 | 0.450170E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2761084.87 | 38326937.18 |
June | 0.653980E+09 | 0.441854E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11787164.65 | 19513130.88 |
July | 0.607235E+09 | 0.419226E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12953426.16 | 13031643.76 |
August | 0.682256E+09 | 0.476238E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12004293.49 | 9167255.35 |
September | 0.605404E+09 | 0.444656E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3477481.27 | 22027405.75 |
October | 0.629366E+09 | 0.498301E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 724086.30 | 71757309.01 |
November | 0.623221E+09 | 0.487915E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101319E+09 |
December | 0.607235E+09 | 0.491638E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168050E+09 |
Annual Sum or Average | 0.755252E+10 | 0.561327E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45450664.75 | 0.925648E+09 |
Minimum of Months | 0.570983E+09 | 0.419226E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9167255.35 |
Maximum of Months | 0.682256E+09 | 0.505576E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12953426.16 | 0.177925E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846055E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403983E+09 |
February | 0.901968E+09 | 0.762897E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 796101.81 | 0.342446E+09 |
March | 0.107774E+10 | 0.796776E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1121183.14 | 0.222940E+09 |
April | 0.956342E+09 | 0.675359E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2909215.66 | 0.138684E+09 |
May | 0.103597E+10 | 0.699833E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7229994.55 | 91209784.08 |
June | 0.103308E+10 | 0.687181E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28898984.38 | 45383268.69 |
July | 0.959235E+09 | 0.651426E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31570788.48 | 30107935.26 |
August | 0.107774E+10 | 0.744765E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30294735.84 | 19135567.60 |
September | 0.956342E+09 | 0.703252E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9187014.37 | 46674798.36 |
October | 0.994195E+09 | 0.808123E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2855645.74 | 0.152385E+09 |
November | 0.984487E+09 | 0.811693E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143778.90 | 0.217741E+09 |
December | 0.959235E+09 | 0.826313E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373482E+09 |
Annual Sum or Average | 0.119305E+11 | 0.901367E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115007E+09 | 0.208417E+10 |
Minimum of Months | 0.901968E+09 | 0.651426E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19135567.60 |
Maximum of Months | 0.107774E+10 | 0.846055E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31570788.48 | 0.403983E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.508129E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272694E+09 |
February | 0.421807E+09 | 0.460497E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279529.76 | 0.232858E+09 |
March | 0.502994E+09 | 0.492356E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795673.72 | 0.152797E+09 |
April | 0.447140E+09 | 0.424791E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1695343.17 | 94653017.58 |
May | 0.484071E+09 | 0.447103E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4449017.12 | 62714101.66 |
June | 0.482240E+09 | 0.439946E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18798282.79 | 30730887.72 |
July | 0.448971E+09 | 0.415308E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20389495.19 | 20525011.26 |
August | 0.502994E+09 | 0.471842E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19725666.24 | 12997033.96 |
September | 0.447140E+09 | 0.436677E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5783307.59 | 31067225.07 |
October | 0.465148E+09 | 0.484045E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1522181.54 | 0.103318E+09 |
November | 0.460569E+09 | 0.494745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81343.25 | 0.147689E+09 |
December | 0.448971E+09 | 0.493961E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2193.30 | 0.251160E+09 |
Annual Sum or Average | 0.557719E+10 | 0.556940E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73522033.65 | 0.141320E+10 |
Minimum of Months | 0.421807E+09 | 0.415308E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12997033.96 |
Maximum of Months | 0.502994E+09 | 0.508129E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20389495.19 | 0.272694E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.765727E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430167E+09 |
February | 0.901968E+09 | 0.705338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44399.18 | 0.366795E+09 |
March | 0.107774E+10 | 0.777861E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 789117.35 | 0.242828E+09 |
April | 0.956342E+09 | 0.677143E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2053196.07 | 0.144104E+09 |
May | 0.103597E+10 | 0.712140E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6634160.61 | 92132877.29 |
June | 0.103308E+10 | 0.700772E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28613564.63 | 44931335.89 |
July | 0.959235E+09 | 0.663635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30990818.22 | 30041958.18 |
August | 0.107774E+10 | 0.749752E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28765812.14 | 19817934.75 |
September | 0.956342E+09 | 0.692213E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7417834.18 | 48513660.92 |
October | 0.994195E+09 | 0.750900E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1174055.40 | 0.165080E+09 |
November | 0.984487E+09 | 0.748109E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239066E+09 |
December | 0.959235E+09 | 0.742755E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397022E+09 |
Annual Sum or Average | 0.119305E+11 | 0.868634E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106483E+09 | 0.222050E+10 |
Minimum of Months | 0.901968E+09 | 0.663635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19817934.75 |
Maximum of Months | 0.107774E+10 | 0.777861E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30990818.22 | 0.430167E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.507897E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273263E+09 |
February | 0.570983E+09 | 0.468127E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 303589.91 | 0.232898E+09 |
March | 0.682256E+09 | 0.503400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 581333.93 | 0.156493E+09 |
April | 0.605404E+09 | 0.431347E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1575131.54 | 95881380.71 |
May | 0.655811E+09 | 0.451973E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4341695.95 | 62706979.52 |
June | 0.653980E+09 | 0.442883E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18401735.63 | 31226666.86 |
July | 0.607235E+09 | 0.420627E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20117875.78 | 20593584.13 |
August | 0.682256E+09 | 0.477530E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18904659.90 | 13920716.22 |
September | 0.605404E+09 | 0.446712E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5631586.99 | 31857235.13 |
October | 0.629366E+09 | 0.500286E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1319362.91 | 0.104316E+09 |
November | 0.623221E+09 | 0.490384E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.90 | 0.148631E+09 |
December | 0.607235E+09 | 0.493477E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251527E+09 |
Annual Sum or Average | 0.755252E+10 | 0.563464E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71177189.45 | 0.142331E+10 |
Minimum of Months | 0.570983E+09 | 0.420627E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13920716.22 |
Maximum of Months | 0.682256E+09 | 0.507897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20117875.78 | 0.273263E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576710E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271889.41 | 0.493213E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777371.33 | 0.323486E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2338990.32 | 0.194625E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6930759.04 | 0.125895E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31934529.08 | 60607519.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36232795.30 | 39913155.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33123794.74 | 25258908.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8425841.13 | 67880408.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1693276.96 | 0.226657E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86041.14 | 0.325113E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548064E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121815E+09 | 0.300742E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25258908.20 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36232795.30 | 0.576710E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698656E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 865521.20 | 0.598406E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1276207.38 | 0.394700E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3754538.60 | 0.242218E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9771907.60 | 0.158250E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42010353.08 | 76590228.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47301096.43 | 49924033.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43471998.61 | 31433377.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12113182.65 | 80847615.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2919641.21 | 0.268274E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701013.60 | 0.382524E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651056E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164185E+09 | 0.363288E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31433377.02 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47301096.43 | 0.698656E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690717E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64025.45 | 0.593322E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561052.61 | 0.394597E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167632.44 | 0.246194E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5310964.77 | 0.161034E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35246312.31 | 73605677.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40434742.59 | 49346659.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38528888.89 | 29030892.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8900164.81 | 76339005.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1299213.37 | 0.261478E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184655.39 | 0.368956E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626148E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131698E+09 | 0.357077E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29030892.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40434742.59 | 0.690717E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 900.40 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.13 | 26-FEB-13:00 | 1089.30 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 | 11-MAR-16:00 | 634.90 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 | 16-APR-11:53 | 357.11 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 | 07-MAY-12:10 | 282.12 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 | 11-JUN-15:00 | 210.31 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.28 | 08-JUL-18:53 | 149.38 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.42 | 06-AUG-13:52 | 98.00 | 23-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.57 | 17-SEP-15:00 | 186.51 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.92 | 08-OCT-13:53 | 371.92 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 | 19-NOV-15:00 | 624.20 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 | 12-DEC-14:00 | 931.77 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 | 1089.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 595.23 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 26-FEB-16:00 | 726.19 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 | 11-MAR-18:03 | 419.16 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.97 | 08-APR-17:20 | 236.91 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 | 29-MAY-17:50 | 187.23 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.80 | 11-JUN-15:00 | 140.65 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 600.14 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.08 | 08-JUL-19:10 | 100.09 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.86 | 06-AUG-14:10 | 65.40 | 23-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.80 | 17-SEP-15:10 | 123.05 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 | 09-OCT-15:50 | 246.44 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.79 | 19-NOV-15:00 | 415.63 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 12-DEC-14:00 | 619.54 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 120.08 | 726.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 910.79 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 28-FEB-15:00 | 1107.66 | 11-FEB-18:05 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 | 30-MAR-16:00 | 638.14 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 | 16-APR-14:08 | 358.08 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 07-MAY-12:13 | 283.53 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.13 | 11-JUN-15:00 | 210.75 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 | 08-JUL-18:53 | 149.55 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.85 | 06-AUG-14:08 | 98.70 | 23-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.13 | 17-SEP-14:48 | 187.13 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 09-OCT-15:50 | 385.16 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 624.40 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 947.90 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.70 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 175.13 | 1107.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 599.76 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 26-FEB-13:00 | 754.48 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 30-MAR-16:00 | 421.37 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 16-APR-12:10 | 235.12 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.58 | 07-MAY-12:10 | 190.62 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 | 11-JUN-14:55 | 142.27 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.40 | 08-JUL-19:10 | 98.30 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.09 | 06-AUG-13:52 | 66.23 | 23-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 | 17-SEP-12:10 | 122.51 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 | 08-OCT-13:53 | 248.72 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | 27-NOV-13:00 | 415.93 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 618.00 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 124.09 | 754.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 499.44 | 07-JAN-18:10 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 26-FEB-13:00 | 608.27 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.56 | 11-MAR-18:03 | 362.82 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 | 08-APR-17:03 | 188.56 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 02-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 | 07-MAY-11:53 | 158.12 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.96 | 11-JUN-15:10 | 113.10 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.99 | 08-JUL-18:53 | 83.23 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.45 | 06-AUG-14:00 | 55.71 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.81 | 17-SEP-15:00 | 116.09 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 | 08-OCT-13:53 | 228.95 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 | 19-NOV-15:00 | 341.83 | 21-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 12-DEC-14:00 | 583.24 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.71 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 112.45 | 608.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 331.86 | 07-JAN-18:10 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 26-FEB-16:00 | 404.64 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 11-MAR-18:03 | 244.98 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 08-APR-17:03 | 125.17 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 29-MAY-17:50 | 107.62 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 11-JUN-15:10 | 78.00 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | 08-JUL-18:53 | 54.70 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.45 | 06-AUG-14:00 | 37.10 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 | 17-SEP-15:00 | 77.01 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 09-OCT-16:00 | 155.63 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 19-NOV-15:00 | 232.41 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 389.82 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | 404.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23092.21 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.19 | 28-FEB-15:00 | 25043.67 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2811.40 | 30-MAR-16:10 | 14365.70 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.92 | 17-APR-16:10 | 15683.52 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5093.93 | 19-MAY-16:10 | 10409.68 | 11-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7175.56 | 06-JUN-16:05 | 7303.93 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8302.26 | 07-JUL-16:03 | 3486.57 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8009.47 | 01-AUG-16:03 | 3668.09 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5441.32 | 07-SEP-16:03 | 7927.76 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3980.17 | 10-OCT-16:05 | 14851.50 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19626.78 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21580.35 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3486.57 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8302.26 | 25043.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 333.95 | 07-JAN-18:10 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 | 26-FEB-13:00 | 413.33 | 11-FEB-18:15 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 30-MAR-16:00 | 246.25 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 16-APR-11:53 | 124.94 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 | 07-MAY-11:53 | 109.57 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.38 | 11-JUN-15:00 | 79.00 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 08-JUL-18:53 | 55.61 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 06-AUG-14:00 | 38.79 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 24-SEP-13:00 | 77.00 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 | 08-OCT-13:53 | 156.80 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.72 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 387.84 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 413.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 773.54 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 | 26-FEB-13:10 | 922.81 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 11-MAR-16:00 | 579.13 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 16-APR-12:00 | 314.89 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 07-MAY-12:10 | 252.71 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.71 | 11-JUN-15:00 | 181.45 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 | 08-JUL-18:53 | 130.28 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.53 | 06-AUG-14:00 | 87.14 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 | 17-SEP-15:10 | 172.13 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 08-OCT-13:53 | 342.09 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 19-NOV-15:00 | 523.62 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 859.03 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.14 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 169.71 | 922.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 511.09 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 | 26-FEB-15:30 | 614.39 | 11-FEB-19:00 |
March | 805.43 | 01-MAR-08:09 | 860.01 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 11-MAR-18:03 | 381.73 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 750.07 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 08-APR-17:20 | 208.79 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 | 21-MAY-17:00 | 167.58 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 | 11-JUN-15:00 | 121.23 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 600.14 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.89 | 08-JUL-18:53 | 84.56 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 750.07 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.21 | 06-AUG-14:00 | 57.44 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 17-SEP-15:10 | 113.61 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 19-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 09-OCT-16:00 | 226.11 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 19-NOV-15:00 | 348.70 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 12-DEC-15:00 | 571.01 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 107.89 | 614.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 782.01 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 28-FEB-15:00 | 955.95 | 11-FEB-19:00 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 30-MAR-16:00 | 582.02 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 1184.79 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 08-APR-17:20 | 315.79 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 947.97 | 02-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 07-MAY-12:10 | 253.91 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 947.97 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 | 11-JUN-15:00 | 181.81 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 19-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.01 | 08-JUL-18:53 | 130.53 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.31 | 06-AUG-13:56 | 87.63 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.24 | 17-SEP-14:48 | 172.68 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 19-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 09-OCT-15:38 | 352.27 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.50 | 07-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 873.40 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 947.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.63 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 158.78 | 955.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 515.32 | 07-JAN-18:10 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 | 26-FEB-13:10 | 646.49 | 11-FEB-18:15 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 30-MAR-16:00 | 384.06 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 859.95 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 16-APR-12:00 | 207.79 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 750.02 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 | 07-MAY-12:10 | 170.66 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.54 | 11-JUN-15:16 | 122.77 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 750.02 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 | 08-JUL-18:53 | 86.18 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.96 | 06-AUG-14:00 | 59.05 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.16 | 17-SEP-12:10 | 113.44 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 08-OCT-13:53 | 228.36 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 27-NOV-13:00 | 348.93 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 569.56 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 600.10 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 107.96 | 646.49 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1095.50 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 26-FEB-15:00 | 1349.79 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 11-MAR-16:00 | 844.27 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.35 | 16-APR-11:53 | 437.66 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 | 07-MAY-11:53 | 358.18 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.37 | 11-JUN-15:00 | 247.15 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.94 | 08-JUL-18:53 | 175.77 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 | 06-AUG-14:00 | 119.97 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.92 | 17-SEP-14:55 | 248.83 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 08-OCT-13:53 | 504.76 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.98 | 19-NOV-15:00 | 747.53 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1280.56 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.61 | 1349.79 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1360.61 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.66 | 26-FEB-15:13 | 1673.81 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 11-MAR-16:00 | 1031.62 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.55 | 16-APR-12:00 | 553.28 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 | 07-MAY-12:10 | 453.82 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.10 | 11-JUN-15:00 | 315.08 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.32 | 08-JUL-18:53 | 220.25 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.78 | 06-AUG-14:00 | 150.49 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 | 17-SEP-15:00 | 306.32 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.72 | 08-OCT-13:53 | 602.73 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.30 | 19-NOV-15:00 | 912.15 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1539.35 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.10 | 1673.81 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1452.66 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | 26-FEB-15:00 | 1726.25 | 11-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 | 11-MAR-16:00 | 960.81 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 16-APR-11:53 | 531.62 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.74 | 07-MAY-11:53 | 409.84 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.73 | 11-JUN-15:10 | 310.93 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.27 | 08-JUL-18:53 | 235.99 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.06 | 06-AUG-13:52 | 145.49 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 17-SEP-15:00 | 265.30 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 | 08-OCT-13:53 | 560.72 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 19-NOV-15:00 | 915.05 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1416.76 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.27 | 1726.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12522.50 | 31-JAN-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17977.16 | 28-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21022.54 | 31-MAR-06:03 | 3811.58 | 6444.06 | 30584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30348.25 | 18-APR-06:03 | 5082.11 | 8592.08 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35859.96 | 30-MAY-06:03 | 3811.58 | 6444.06 | 30584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38483.59 | 26-JUN-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40732.33 | 07-JUL-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40723.27 | 03-AUG-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36090.67 | 18-SEP-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35125.05 | 10-OCT-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20107.09 | 06-NOV-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16630.37 | 14-DEC-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12522.50 | 0.00 | 1058.67 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40732.33 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1586.00 | 28-JAN-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 |
February | 3588.69 | 26-FEB-14:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 0.00 |
March | 6839.98 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 0.00 |
April | 7782.06 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 | 0.00 |
May | 8642.68 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 0.00 |
June | 9260.24 | 27-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 0.00 |
July | 10318.28 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 0.00 |
August | 10435.40 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 | 0.00 |
September | 8963.05 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 0.00 |
October | 6841.69 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 0.00 |
November | 3359.21 | 05-NOV-14:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 |
December | 2489.44 | 10-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1586.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10435.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 73.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1927.05 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.07 |
February | 2142.33 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.80 |
March | 2225.04 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 0.00 |
April | 3028.98 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.09 |
May | 3624.57 | 30-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
June | 3981.13 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
July | 4501.11 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 |
August | 4289.30 | 02-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 0.00 |
September | 3935.45 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
October | 2710.89 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | 0.00 |
November | 1808.33 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.65 |
December | 2067.57 | 09-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1808.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4501.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 216.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1763.09 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 |
February | 2471.41 | 23-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.19 |
March | 2582.88 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 |
April | 3140.24 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.10 |
May | 3959.92 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 | 0.00 |
June | 4178.93 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 | 0.00 |
July | 4662.67 | 10-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 0.00 |
August | 4688.62 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 0.00 |
September | 4587.76 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 | 0.00 |
October | 3550.87 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 0.00 |
November | 1933.14 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 |
December | 2238.72 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1763.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4688.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 | 144.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8954.73 | 31-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10784.10 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14149.26 | 30-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15068.27 | 18-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17207.12 | 30-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29557.58 | 26-JUN-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31415.80 | 07-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32004.97 | 03-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17698.49 | 11-SEP-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15679.81 | 11-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11741.33 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9775.03 | 13-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8954.73 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32004.97 | 6035.01 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9120.56 | 20-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10610.98 | 28-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16101.24 | 30-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17150.42 | 17-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19397.47 | 30-MAY-15:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32434.12 | 26-JUN-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33163.23 | 07-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33562.07 | 14-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19449.84 | 07-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16567.35 | 11-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10317.21 | 06-NOV-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9805.13 | 13-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9120.56 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33562.07 | 6035.01 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1879.57 | 31-JAN-16:50 | 1272.23 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
February | 2529.64 | 28-FEB-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
March | 4688.03 | 30-MAR-15:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 0.00 |
April | 5065.85 | 19-APR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
May | 6513.62 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 0.00 |
June | 7512.76 | 25-JUN-18:53 | 0.00 | 143.99 | 1544.41 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 0.00 |
July | 11780.92 | 16-JUL-18:32 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 0.00 |
August | 8410.81 | 20-AUG-16:42 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 | 0.00 |
September | 6347.10 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 0.00 |
October | 4395.39 | 02-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
November | 2158.84 | 02-NOV-15:50 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
December | 2011.61 | 13-DEC-15:00 | 1306.65 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1879.57 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11780.92 | 1306.65 | 947.97 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | 15.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1547.08 | 31-JAN-15:10 | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
February | 2184.68 | 27-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 |
March | 3653.22 | 30-MAR-11:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
April | 7866.22 | 16-APR-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
May | 11629.01 | 07-MAY-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
June | 11635.36 | 04-JUN-08:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 |
July | 11628.06 | 02-JUL-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
August | 10983.14 | 27-AUG-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 | 0.00 |
September | 9326.65 | 24-SEP-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 0.00 |
October | 4472.78 | 11-OCT-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
November | 1868.30 | 06-NOV-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
December | 1641.63 | 12-DEC-15:10 | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1547.08 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11635.36 | 827.22 | 450.21 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 38.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4693.13 | 11-JAN-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.81 |
February | 13787.20 | 26-FEB-14:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 |
March | 9614.19 | 30-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | 0.00 |
April | 13094.67 | 16-APR-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 |
May | 7824.51 | 29-MAY-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 | 0.00 |
June | 8968.21 | 25-JUN-16:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 147.37 | 0.00 |
July | 13554.27 | 16-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 0.00 |
August | 13996.96 | 20-AUG-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | 0.00 |
September | 14325.03 | 24-SEP-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
October | 14407.92 | 09-OCT-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
November | 14006.45 | 11-NOV-14:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.26 |
December | 6339.95 | 08-DEC-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4693.13 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14407.92 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 147.37 | 117.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1807.67 | 20-JAN-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
February | 4229.84 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
March | 6374.77 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 |
April | 11819.88 | 09-APR-17:33 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
May | 11759.97 | 21-MAY-18:23 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
June | 13305.25 | 11-JUN-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 70.91 | 0.00 |
July | 13218.32 | 23-JUL-18:32 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 0.00 |
August | 13200.41 | 13-AUG-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 | 0.00 |
September | 8983.04 | 17-SEP-17:23 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
October | 6631.95 | 11-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
November | 3847.37 | 06-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 |
December | 1946.68 | 11-DEC-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1807.67 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13305.25 | 805.38 | 410.20 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 70.91 | 34.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1780.93 | 31-JAN-16:40 | 1272.23 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
February | 2032.48 | 28-FEB-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 0.00 |
March | 2722.38 | 30-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
April | 3045.32 | 19-APR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
May | 4627.94 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.29 | 0.00 |
June | 5399.13 | 28-JUN-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | 0.00 |
July | 5936.11 | 10-JUL-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 | 0.00 |
August | 5975.69 | 09-AUG-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
September | 5675.74 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
October | 4078.61 | 02-OCT-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 0.00 |
November | 2247.97 | 05-NOV-12:53 | 200.88 | 107.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
December | 1996.32 | 13-DEC-13:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1780.93 | 200.88 | 107.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5975.69 | 1272.23 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | 12.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1350.15 | 31-JAN-15:00 | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 |
February | 1947.91 | 27-FEB-10:40 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 |
March | 2651.78 | 14-MAR-11:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
April | 4358.38 | 17-APR-10:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 7219.48 | 07-MAY-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 |
June | 8365.43 | 11-JUN-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
July | 10184.10 | 04-JUL-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
August | 10427.76 | 27-AUG-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 6326.20 | 08-SEP-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
October | 4477.17 | 10-OCT-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
November | 2491.47 | 06-NOV-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 |
December | 1480.98 | 13-DEC-12:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1350.15 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10427.76 | 827.22 | 450.21 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 20.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2752.56 | 28-JAN-14:40 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 |
February | 9592.97 | 26-FEB-14:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 |
March | 7774.39 | 30-MAR-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2811.40 | 0.00 |
April | 7892.78 | 17-APR-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.92 | 0.00 |
May | 9042.73 | 30-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4174.38 | 0.00 |
June | 9864.54 | 06-JUN-16:20 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6838.59 | 0.00 |
July | 10295.70 | 07-JUL-16:10 | 1205.27 | 1079.96 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7668.83 | 0.00 |
August | 11343.71 | 27-AUG-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 52.25 | 0.00 |
September | 10184.63 | 07-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4536.21 | 0.00 |
October | 11980.45 | 09-OCT-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
November | 11569.44 | 11-NOV-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.64 |
December | 5911.67 | 12-DEC-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2752.56 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11980.45 | 1272.23 | 1079.96 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 7668.83 | 158.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1459.65 | 23-JAN-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
February | 3101.61 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
March | 4311.14 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
April | 4904.03 | 17-APR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
May | 7058.10 | 29-MAY-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 0.00 |
June | 10543.48 | 04-JUN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 0.00 |
July | 10831.42 | 04-JUL-17:52 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 0.00 |
August | 11198.16 | 13-AUG-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 | 0.00 |
September | 8989.00 | 04-SEP-16:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
October | 8608.05 | 09-OCT-16:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
November | 3870.44 | 06-NOV-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 |
December | 1628.40 | 11-DEC-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1459.65 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11198.16 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 24.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1837.19 | 31-JAN-16:50 | 1272.23 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
February | 2570.82 | 28-FEB-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
March | 4181.98 | 30-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 0.00 |
April | 4616.96 | 18-APR-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
May | 5906.83 | 30-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 0.00 |
June | 7038.03 | 26-JUN-05:12 | 535.68 | 603.74 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
July | 8473.77 | 16-JUL-18:32 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | 0.00 |
August | 7978.78 | 14-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 |
September | 5789.69 | 06-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 0.00 |
October | 4130.94 | 02-OCT-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
November | 2134.59 | 03-NOV-15:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
December | 1991.65 | 13-DEC-13:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1837.19 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8473.77 | 1306.65 | 947.97 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | 15.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1509.35 | 31-JAN-12:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 |
February | 2775.84 | 27-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 |
March | 3785.78 | 13-MAR-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 |
April | 6883.55 | 16-APR-10:53 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
May | 11216.85 | 07-MAY-09:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
June | 11182.77 | 11-JUN-09:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
July | 11641.57 | 04-JUL-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
August | 11959.36 | 27-AUG-09:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
September | 9841.98 | 04-SEP-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
October | 4676.47 | 11-OCT-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
November | 2668.40 | 06-NOV-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
December | 1624.83 | 13-DEC-12:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1509.35 | 127.17 | 68.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11959.36 | 805.43 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 32.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4931.02 | 27-JAN-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 |
February | 11176.03 | 26-FEB-14:03 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 |
March | 9038.58 | 30-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 |
April | 7788.49 | 17-APR-13:50 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
May | 7220.57 | 29-MAY-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 0.00 |
June | 7091.88 | 26-JUN-05:12 | 535.68 | 603.74 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
July | 10474.81 | 16-JUL-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 0.00 |
August | 12376.46 | 27-AUG-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 78.50 | 0.00 |
September | 9821.06 | 17-SEP-14:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 | 0.00 |
October | 12812.45 | 09-OCT-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 12744.58 | 11-NOV-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.92 |
December | 6846.84 | 08-DEC-14:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4931.02 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12812.45 | 1306.65 | 647.98 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 78.50 | 109.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1683.29 | 27-JAN-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.58 |
February | 4142.88 | 27-FEB-17:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
March | 5986.48 | 30-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
April | 11160.22 | 09-APR-17:12 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 |
May | 11931.91 | 21-MAY-17:32 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 |
June | 11898.51 | 11-JUN-15:52 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 66.43 | 0.00 |
July | 12405.08 | 04-JUL-17:52 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 0.00 |
August | 12819.98 | 13-AUG-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 0.00 |
September | 10801.72 | 04-SEP-16:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | 0.00 |
October | 9027.45 | 09-OCT-16:12 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 0.00 |
November | 4017.67 | 06-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 |
December | 1835.65 | 11-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1683.29 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12819.98 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 66.43 | 59.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.158473E+12 | 242474.07 | 09-JAN-07:10 | 0.00 | 0.00 |
February | 0.126487E+12 | 242674.82 | 13-FEB-07:10 | 0.00 | 0.00 |
March | 0.121093E+12 | 115730.18 | 30-MAR-15:09 | 0.00 | 0.00 |
April | 0.116727E+12 | 120405.67 | 17-APR-15:39 | 0.00 | 0.00 |
May | 0.136661E+12 | 135078.04 | 30-MAY-15:09 | 0.00 | 0.00 |
June | 0.154349E+12 | 144052.45 | 27-JUN-15:39 | 0.00 | 0.00 |
July | 0.160297E+12 | 156832.63 | 07-JUL-15:00 | 0.00 | 0.00 |
August | 0.174382E+12 | 155392.88 | 01-AUG-15:20 | 0.00 | 0.00 |
September | 0.138300E+12 | 148263.80 | 07-SEP-15:50 | 0.00 | 0.00 |
October | 0.121614E+12 | 128803.71 | 10-OCT-15:00 | 0.00 | 0.00 |
November | 0.115053E+12 | 155979.72 | 22-NOV-07:10 | 0.00 | 0.00 |
December | 0.127493E+12 | 204674.89 | 18-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165093E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.115053E+12 | 115730.18 | 0.00 | 0.00 | |
Maximum of Months | 0.174382E+12 | 242674.82 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.258642E+11 | 0.544208E+10 | 0.605851E+11 | 0.225893E+10 | 0.391294E+10 | 12379742.02 | 0.542898E+11 | 0.149187E+10 | 0.00 | 0.00 | 0.00 | 0.461605E+10 | 0.00 |
February | 0.235047E+11 | 0.447543E+10 | 0.548702E+11 | 0.204972E+10 | 0.366096E+10 | 11196021.66 | 0.300341E+11 | 0.368308E+10 | 0.00 | 0.00 | 0.00 | 0.419803E+10 | 0.00 |
March | 0.271449E+11 | 0.443078E+10 | 0.627783E+11 | 0.235658E+10 | 0.448288E+10 | 12675672.10 | 0.469267E+10 | 0.104035E+11 | 0.00 | 0.00 | 0.00 | 0.479055E+10 | 0.00 |
April | 0.239402E+11 | 0.378945E+10 | 0.586172E+11 | 0.219335E+10 | 0.477705E+10 | 11960507.72 | 0.144371E+10 | 0.178849E+11 | 0.00 | 0.00 | 0.00 | 0.406909E+10 | 0.00 |
May | 0.256470E+11 | 0.345949E+10 | 0.616817E+11 | 0.230726E+10 | 0.636227E+10 | 12527707.06 | 0.184999E+09 | 0.329725E+11 | 0.00 | 0.00 | 0.00 | 0.403284E+10 | 0.00 |
June | 0.254527E+11 | 0.317507E+10 | 0.604966E+11 | 0.226944E+10 | 0.867685E+10 | 12231776.97 | 25625123.02 | 0.505342E+11 | 0.00 | 0.00 | 0.00 | 0.370659E+10 | 0.00 |
July | 0.238434E+11 | 0.336986E+10 | 0.597911E+11 | 0.223024E+10 | 0.941242E+10 | 12256437.81 | 0.00 | 0.582902E+11 | 0.00 | 0.00 | 0.00 | 0.334732E+10 | 0.00 |
August | 0.267688E+11 | 0.373343E+10 | 0.627783E+11 | 0.235633E+10 | 0.105009E+11 | 12675672.10 | 0.00 | 0.645639E+11 | 0.00 | 0.00 | 0.00 | 0.366739E+10 | 0.00 |
September | 0.241495E+11 | 0.405491E+10 | 0.585950E+11 | 0.219223E+10 | 0.723327E+10 | 11960507.72 | 29735518.16 | 0.385698E+11 | 0.00 | 0.00 | 0.00 | 0.346322E+10 | 0.00 |
October | 0.256123E+11 | 0.470282E+10 | 0.605962E+11 | 0.225948E+10 | 0.515667E+10 | 12379742.02 | 0.241262E+10 | 0.170155E+11 | 0.00 | 0.00 | 0.00 | 0.384583E+10 | 0.00 |
November | 0.254175E+11 | 0.511872E+10 | 0.591197E+11 | 0.220156E+10 | 0.402099E+10 | 12059151.09 | 0.776702E+10 | 0.730791E+10 | 0.00 | 0.00 | 0.00 | 0.408746E+10 | 0.00 |
December | 0.250509E+11 | 0.559902E+10 | 0.597800E+11 | 0.223021E+10 | 0.378800E+10 | 12256437.81 | 0.239666E+11 | 0.273895E+10 | 0.00 | 0.00 | 0.00 | 0.432677E+10 | 0.00 |
Annual Sum or Average | 0.302396E+12 | 0.513511E+11 | 0.719689E+12 | 0.269053E+11 | 0.719852E+11 | 0.146559E+09 | 0.124847E+12 | 0.305456E+12 | 0.00 | 0.00 | 0.00 | 0.481511E+11 | 0.00 |
Minimum of Months | 0.235047E+11 | 0.317507E+10 | 0.548702E+11 | 0.204972E+10 | 0.366096E+10 | 11196021.66 | 0.00 | 0.149187E+10 | 0.00 | 0.00 | 0.00 | 0.334732E+10 | 0.00 |
Maximum of Months | 0.271449E+11 | 0.559902E+10 | 0.627783E+11 | 0.235658E+10 | 0.105009E+11 | 12675672.10 | 0.542898E+11 | 0.645639E+11 | 0.00 | 0.00 | 0.00 | 0.479055E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 03-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 05-JAN-17:10 | 5736.93 | 09-JAN-07:10 | 6.85 | 05-JAN-06:10 | 194745.30 | 09-JAN-07:10 |
February | 32642.50 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 02-FEB-17:10 | 5356.42 | 13-FEB-07:10 | 6.85 | 02-FEB-06:10 | 195320.41 | 13-FEB-07:10 |
March | 32642.50 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 06-MAR-08:09 | 7939.89 | 30-MAR-15:00 | 6.85 | 06-MAR-08:09 | 67621.75 | 23-MAR-06:10 |
April | 31270.76 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 05-APR-16:10 | 8698.99 | 17-APR-15:50 | 6.85 | 01-APR-05:10 | 62984.65 | 06-APR-06:10 |
May | 28326.84 | 24-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:09 | 11470.28 | 30-MAY-14:00 | 6.85 | 01-MAY-05:10 | 15573.49 | 11-MAY-06:10 |
June | 27609.75 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 12047.04 | 27-JUN-15:30 | 6.85 | 01-JUN-05:10 | 5038.32 | 08-JUN-06:19 |
July | 28960.31 | 27-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 14010.14 | 07-JUL-15:00 | 6.85 | 09-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 30940.97 | 24-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 03-AUG-12:09 | 14770.08 | 02-AUG-15:00 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 32312.69 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:10 | 13892.55 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 5409.03 | 29-SEP-06:10 |
October | 32642.50 | 19-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 24-OCT-11:09 | 10121.98 | 11-OCT-15:30 | 6.85 | 26-OCT-07:10 | 67779.74 | 26-OCT-06:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 13-NOV-12:09 | 5352.33 | 06-NOV-15:30 | 6.85 | 13-NOV-12:09 | 110842.85 | 22-NOV-07:10 |
December | 32642.50 | 06-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-12:09 | 4189.95 | 04-DEC-07:10 | 6.85 | 04-DEC-12:09 | 158531.84 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 27609.75 | 5686.19 | 41699.26 | 1410.29 | 4189.95 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 14770.08 | 6.85 | 195320.41 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 14961.80 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 6214.50 | 30-JAN-12:00 | 0.00 |
February | 19179.20 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6214.45 | 01-FEB-12:00 | 0.00 |
March | 35035.77 | 30-MAR-15:09 | 0.00 | 0.00 | 0.00 | 6145.01 | 02-MAR-12:00 | 0.00 |
April | 38757.33 | 17-APR-15:39 | 0.00 | 0.00 | 0.00 | 5783.54 | 03-APR-11:20 | 0.00 |
May | 51668.96 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 5375.54 | 01-MAY-11:20 | 0.00 |
June | 59817.78 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 4970.88 | 01-JUN-11:50 | 0.00 |
July | 70815.12 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 4599.01 | 03-JUL-11:30 | 0.00 |
August | 69014.18 | 01-AUG-15:20 | 0.00 | 0.00 | 0.00 | 4595.98 | 31-AUG-11:20 | 0.00 |
September | 62238.92 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 4957.59 | 29-SEP-11:39 | 0.00 |
October | 45932.59 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 5361.65 | 31-OCT-11:39 | 0.00 |
November | 20319.36 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 5776.30 | 30-NOV-12:20 | 0.00 |
December | 19910.74 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 5939.74 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14961.80 | 0.00 | 0.00 | 0.00 | 4595.98 | 0.00 | ||
Maximum of Months | 70815.12 | 0.00 | 0.00 | 0.00 | 6214.50 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 242474.07 | 09-JAN-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 5736.93 | 6.85 | 194745.30 | 0.00 | 0.00 |
February | 242674.82 | 13-FEB-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 5356.42 | 6.85 | 195320.41 | 0.00 | 0.00 |
March | 115730.18 | 30-MAR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 7667.44 | 6.85 | 0.00 | 35035.77 | 0.00 |
April | 120405.67 | 17-APR-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 8696.75 | 6.85 | 0.00 | 38757.33 | 0.00 |
May | 135078.04 | 30-MAY-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 11404.85 | 6.85 | 0.00 | 51046.96 | 0.00 |
June | 144052.45 | 27-JUN-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 12025.89 | 6.85 | 0.00 | 59716.93 | 0.00 |
July | 156832.63 | 07-JUL-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14010.14 | 6.85 | 0.00 | 70815.12 | 0.00 |
August | 155392.88 | 01-AUG-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14128.84 | 6.85 | 0.00 | 69014.18 | 0.00 |
September | 148263.80 | 07-SEP-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 13802.22 | 6.85 | 0.00 | 62153.05 | 0.00 |
October | 128803.71 | 10-OCT-15:00 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 9916.01 | 6.85 | 0.00 | 45932.59 | 0.00 |
November | 155979.72 | 22-NOV-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3427.79 | 6.85 | 110842.85 | 0.00 | 0.00 |
December | 204674.89 | 18-DEC-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 4157.04 | 6.85 | 158531.84 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 115730.18 | 10880.98 | 22496.85 | 0.00 | 975.80 | 3427.79 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 242674.82 | 25990.55 | 41670.51 | 5686.19 | 1410.29 | 14128.84 | 6.85 | 195320.41 | 70815.12 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 17.94 | 0.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
February | 0.50 | 18.48 | 0.33 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.61 | 0.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Annual Sum or Average | 1.83 | 18.27 | 1.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.61 | 0.50 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 16.76 | 4.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
February | 8.33 | 16.41 | 3.50 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.48 | 1.83 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
December | 2.33 | 18.20 | 1.50 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
Annual Sum or Average | 20.83 | 16.78 | 9.33 | 17.24 | 3.33 | 18.26 | 2.17 | 18.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.00 | 18.20 | 4.33 | 18.68 | 2.83 | 27.48 | 1.83 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 15.85 | 1.50 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 5.17 | 15.48 | 0.83 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.51 | 1.83 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.80 | 4.17 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.76 | 8.50 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.70 | 6.00 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
December | 1.17 | 16.95 | 0.33 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
Annual Sum or Average | 13.67 | 15.82 | 2.67 | 16.01 | 22.50 | 22.80 | 21.67 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 17.18 | 1.50 | 17.45 | 9.17 | 27.80 | 8.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 16.50 | 1.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
February | 4.00 | 16.05 | 1.17 | 16.32 | 0.67 | 17.59 | 0.67 | 18.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.53 | 3.33 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.67 | 4.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.56 | 2.00 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.65 | 3.33 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
December | 0.83 | 17.40 | 0.33 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
Annual Sum or Average | 9.67 | 16.39 | 2.67 | 16.69 | 18.67 | 23.24 | 17.50 | 24.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 17.40 | 1.17 | 17.89 | 5.00 | 27.67 | 4.83 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.33 | 15.94 | 1.83 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
February | 5.67 | 15.56 | 1.67 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.58 | 1.00 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 1.83 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.01 | 2.83 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.16 | 4.17 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.12 | 3.00 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.57 | 1.50 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
November | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
December | 1.17 | 17.28 | 0.33 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
Annual Sum or Average | 14.33 | 15.91 | 3.83 | 16.08 | 26.50 | 23.15 | 15.00 | 24.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 | 15.66 |
Maximum of Months | 7.33 | 17.28 | 1.83 | 17.71 | 8.67 | 28.16 | 4.17 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.83 | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 0.50 | 18.85 | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 18.84 | 0.83 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.85 | 0.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.60 | 4.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.59 | 3.67 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.08 | 0.00 | 17.08 | 10.67 | 27.25 | 10.67 | 27.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.12 | 0.00 | 17.12 | 4.00 | 27.60 | 4.00 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.17 | 18.16 | 44.17 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
February | 29.67 | 18.41 | 29.67 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
March | 11.00 | 19.54 | 11.00 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
April | 4.50 | 18.81 | 4.50 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.71 | 1.50 | 24.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 24.83 | 12.83 | 24.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25.17 | 20.50 | 25.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 25.17 | 6.83 | 25.17 |
October | 2.00 | 19.48 | 2.00 | 19.48 | 7.17 | 23.95 | 7.17 | 24.92 |
November | 10.00 | 19.42 | 10.00 | 19.42 | 2.00 | 20.15 | 2.00 | 20.76 |
December | 20.00 | 18.49 | 20.00 | 18.49 | 0.17 | 18.52 | 0.17 | 18.56 |
Annual Sum or Average | 121.33 | 18.55 | 121.33 | 18.55 | 51.00 | 19.73 | 51.00 | 20.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.17 | 19.54 | 44.17 | 19.54 | 20.50 | 25.17 | 20.50 | 25.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
February | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.17 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.69 | 1.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.83 | 2.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.80 | 2.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.40 | 1.00 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.12 | 0.00 | 17.12 | 16.00 | 27.50 | 8.33 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.14 | 0.00 | 17.14 | 5.83 | 27.83 | 2.83 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 18.45 | 0.83 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.83 | 18.28 | 0.50 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Annual Sum or Average | 2.17 | 18.46 | 1.50 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.41 | 0.83 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.62 | 0.33 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
February | 0.50 | 17.36 | 0.17 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.60 | 1.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.87 | 3.17 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.77 | 6.00 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.33 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 1.17 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 17.51 | 0.50 | 18.01 | 17.00 | 26.88 | 17.00 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.62 | 0.33 | 18.16 | 6.00 | 27.87 | 6.00 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.70 | 0.33 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
February | 0.50 | 17.58 | 0.17 | 17.99 | 1.17 | 24.00 | 1.17 | 25.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 1.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.51 | 4.00 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.61 | 4.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 1.17 | 17.65 | 0.50 | 18.13 | 14.50 | 26.56 | 14.50 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.70 | 0.33 | 18.23 | 4.17 | 27.61 | 4.17 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.60 | 0.33 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
February | 0.50 | 17.44 | 0.17 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.50 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.74 | 1.50 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.91 | 2.17 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.03 | 3.67 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 2.67 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.54 | 1.50 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 17.53 | 0.50 | 18.03 | 22.17 | 27.20 | 12.67 | 27.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.60 | 0.33 | 18.14 | 7.33 | 28.03 | 3.67 | 28.03 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 22.75 | 15.83 | 22.72 | 15.83 | 22.68 |
February | 399.00 | 23.21 | 7.67 | 23.23 | 0.50 | 23.23 |
March | 209.83 | 23.83 | 97.17 | 24.10 | 0.00 | 24.10 |
April | 59.17 | 23.85 | 210.00 | 24.57 | 0.00 | 24.57 |
May | 1.50 | 24.00 | 409.00 | 24.55 | 0.00 | 24.55 |
June | 0.00 | 0.00 | 449.00 | 24.42 | 0.00 | 24.42 |
July | 0.00 | 0.00 | 497.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 458.83 | 24.48 | 0.00 | 24.48 |
October | 28.33 | 23.66 | 229.17 | 24.63 | 0.00 | 24.63 |
November | 212.33 | 23.84 | 68.50 | 24.09 | 0.00 | 24.09 |
December | 433.50 | 23.51 | 10.83 | 23.54 | 0.00 | 23.54 |
Annual Sum or Average | 1842.17 | 23.33 | 2967.00 | 24.06 | 16.33 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 7.67 | 22.72 | 0.00 | 22.68 |
Maximum of Months | 498.50 | 24.00 | 514.00 | 24.63 | 15.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.20 | 156.83 | 21.04 | 156.83 | 20.94 |
February | 451.33 | 21.80 | 75.50 | 21.64 | 75.50 | 21.51 |
March | 436.33 | 22.90 | 21.00 | 22.96 | 0.00 | 22.96 |
April | 266.00 | 23.21 | 88.33 | 23.48 | 0.00 | 23.48 |
May | 89.00 | 23.30 | 244.83 | 24.03 | 0.00 | 24.03 |
June | 33.67 | 23.46 | 365.33 | 24.20 | 0.00 | 24.20 |
July | 11.33 | 23.11 | 437.50 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 470.00 | 24.25 | 0.00 | 24.25 |
September | 59.00 | 23.15 | 311.00 | 24.15 | 0.00 | 24.15 |
October | 286.00 | 22.98 | 86.50 | 23.26 | 0.00 | 23.26 |
November | 470.50 | 22.73 | 0.00 | 22.73 | 0.00 | 22.73 |
December | 494.67 | 21.76 | 29.67 | 21.71 | 29.67 | 21.66 |
Annual Sum or Average | 3099.83 | 22.31 | 2286.50 | 22.97 | 262.00 | 22.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.04 | 0.00 | 20.94 |
Maximum of Months | 502.00 | 23.46 | 470.00 | 24.25 | 156.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.64 | 307.17 | 20.49 | 307.17 | 20.42 |
February | 452.67 | 21.23 | 143.83 | 21.01 | 143.83 | 20.88 |
March | 463.67 | 22.31 | 35.33 | 22.33 | 15.83 | 22.28 |
April | 314.67 | 22.86 | 63.33 | 23.07 | 0.67 | 23.07 |
May | 138.50 | 23.15 | 216.00 | 23.81 | 0.00 | 23.81 |
June | 45.33 | 23.31 | 353.83 | 24.15 | 0.00 | 24.15 |
July | 16.17 | 22.87 | 429.67 | 24.24 | 0.00 | 24.24 |
August | 3.17 | 23.38 | 456.67 | 24.24 | 0.00 | 24.24 |
September | 117.83 | 22.97 | 252.67 | 23.86 | 0.00 | 23.86 |
October | 380.50 | 22.48 | 58.50 | 22.68 | 1.33 | 22.67 |
November | 486.50 | 21.87 | 46.00 | 21.75 | 46.00 | 21.66 |
December | 497.00 | 21.05 | 183.00 | 20.86 | 183.00 | 20.76 |
Annual Sum or Average | 3418.00 | 21.82 | 2546.00 | 22.40 | 697.83 | 22.18 |
Minimum of Months | 3.17 | 20.64 | 35.33 | 20.49 | 0.00 | 20.42 |
Maximum of Months | 502.00 | 23.38 | 456.67 | 24.24 | 307.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 415.33 | 20.04 | 415.33 | 20.00 |
February | 451.17 | 20.71 | 252.67 | 20.49 | 252.67 | 20.39 |
March | 465.33 | 21.68 | 110.17 | 21.60 | 83.00 | 21.44 |
April | 319.17 | 22.35 | 107.17 | 22.63 | 22.33 | 22.53 |
May | 146.83 | 22.87 | 261.00 | 23.76 | 0.17 | 23.76 |
June | 45.33 | 23.60 | 392.67 | 24.26 | 8.83 | 24.29 |
July | 38.17 | 24.59 | 454.33 | 24.45 | 23.50 | 24.51 |
August | 17.67 | 25.01 | 488.67 | 24.36 | 12.33 | 24.39 |
September | 166.83 | 23.10 | 271.50 | 23.86 | 17.00 | 23.90 |
October | 408.17 | 21.92 | 83.17 | 22.12 | 29.33 | 22.09 |
November | 485.00 | 21.19 | 157.83 | 20.98 | 157.83 | 20.84 |
December | 497.00 | 20.42 | 333.33 | 20.25 | 333.33 | 20.18 |
Annual Sum or Average | 3542.67 | 21.37 | 3327.83 | 22.01 | 1355.67 | 21.73 |
Minimum of Months | 17.67 | 20.14 | 83.17 | 20.04 | 0.17 | 20.00 |
Maximum of Months | 502.00 | 25.01 | 488.67 | 24.45 | 415.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 388.67 | 20.17 | 388.67 | 20.13 |
February | 445.67 | 20.97 | 217.33 | 20.70 | 217.33 | 20.56 |
March | 428.17 | 21.95 | 87.50 | 21.95 | 48.67 | 21.80 |
April | 253.83 | 22.41 | 158.33 | 23.04 | 13.50 | 22.97 |
May | 125.50 | 22.96 | 313.17 | 24.00 | 8.67 | 24.04 |
June | 53.00 | 24.48 | 417.17 | 24.42 | 23.00 | 24.52 |
July | 72.67 | 25.30 | 446.50 | 24.65 | 50.33 | 24.81 |
August | 41.67 | 25.78 | 475.17 | 24.53 | 32.50 | 24.65 |
September | 157.17 | 23.01 | 306.50 | 23.92 | 20.50 | 23.99 |
October | 335.83 | 21.90 | 123.17 | 22.36 | 28.50 | 22.31 |
November | 480.33 | 21.40 | 110.17 | 21.20 | 110.17 | 21.06 |
December | 497.00 | 20.54 | 279.50 | 20.34 | 279.50 | 20.24 |
Annual Sum or Average | 3392.83 | 21.56 | 3323.17 | 22.28 | 1221.33 | 22.06 |
Minimum of Months | 41.67 | 20.28 | 87.50 | 20.17 | 8.67 | 20.13 |
Maximum of Months | 502.00 | 25.78 | 475.17 | 24.65 | 388.67 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.33 | 20.92 | 277.83 | 20.60 | 274.50 | 20.43 |
February | 397.83 | 21.23 | 187.00 | 21.09 | 168.67 | 20.89 |
March | 347.33 | 21.94 | 128.50 | 22.19 | 52.33 | 22.00 |
April | 248.83 | 22.39 | 152.83 | 23.01 | 18.33 | 22.93 |
May | 144.17 | 22.85 | 272.67 | 23.81 | 1.17 | 23.82 |
June | 63.33 | 23.74 | 383.83 | 24.26 | 14.50 | 24.33 |
July | 49.67 | 24.88 | 445.50 | 24.51 | 31.50 | 24.60 |
August | 35.83 | 25.97 | 487.00 | 24.50 | 30.67 | 24.60 |
September | 138.17 | 23.32 | 309.33 | 24.09 | 25.00 | 24.19 |
October | 282.17 | 22.16 | 179.17 | 22.98 | 28.17 | 23.01 |
November | 377.33 | 21.69 | 129.00 | 21.79 | 81.67 | 21.59 |
December | 449.00 | 21.14 | 210.33 | 20.85 | 198.83 | 20.65 |
Annual Sum or Average | 3016.00 | 21.83 | 3163.00 | 22.61 | 925.33 | 22.38 |
Minimum of Months | 35.83 | 20.92 | 128.50 | 20.60 | 1.17 | 20.43 |
Maximum of Months | 482.33 | 25.97 | 487.00 | 24.51 | 274.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 370.50 | 20.15 | 370.50 | 20.08 |
February | 436.00 | 20.78 | 237.33 | 20.60 | 232.33 | 20.49 |
March | 413.17 | 21.58 | 122.83 | 21.68 | 72.50 | 21.52 |
April | 290.17 | 22.15 | 146.83 | 22.76 | 20.00 | 22.70 |
May | 175.17 | 22.73 | 265.50 | 23.69 | 8.17 | 23.74 |
June | 87.50 | 23.56 | 377.83 | 24.23 | 19.33 | 24.32 |
July | 72.17 | 24.40 | 418.33 | 24.46 | 35.33 | 24.57 |
August | 42.17 | 25.03 | 452.83 | 24.44 | 25.00 | 24.54 |
September | 184.50 | 22.86 | 260.33 | 23.77 | 23.50 | 23.86 |
October | 374.83 | 21.80 | 113.33 | 22.24 | 28.17 | 22.22 |
November | 457.67 | 21.20 | 142.83 | 21.04 | 135.33 | 20.90 |
December | 497.00 | 20.57 | 292.50 | 20.36 | 292.50 | 20.26 |
Annual Sum or Average | 3532.33 | 21.45 | 3201.00 | 22.12 | 1262.67 | 21.89 |
Minimum of Months | 42.17 | 20.30 | 113.33 | 20.15 | 8.17 | 20.08 |
Maximum of Months | 502.00 | 25.03 | 452.83 | 24.46 | 370.50 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 400.83 | 20.40 | 400.83 | 20.37 |
February | 454.00 | 20.87 | 224.50 | 20.70 | 224.50 | 20.61 |
March | 500.83 | 21.69 | 60.83 | 21.59 | 57.00 | 21.49 |
April | 421.00 | 22.32 | 31.33 | 22.36 | 12.33 | 22.31 |
May | 223.33 | 23.01 | 179.00 | 23.56 | 4.00 | 23.57 |
June | 38.17 | 23.56 | 381.67 | 24.20 | 2.67 | 24.21 |
July | 15.00 | 24.45 | 466.50 | 24.37 | 8.50 | 24.38 |
August | 5.67 | 26.08 | 503.50 | 24.33 | 5.67 | 24.35 |
September | 74.17 | 23.71 | 325.17 | 24.22 | 16.83 | 24.27 |
October | 366.83 | 22.67 | 83.83 | 22.94 | 6.33 | 22.97 |
November | 477.17 | 21.99 | 36.50 | 21.91 | 35.17 | 21.82 |
December | 497.00 | 20.96 | 231.17 | 20.82 | 231.17 | 20.74 |
Annual Sum or Average | 3575.17 | 21.69 | 2924.83 | 22.29 | 1005.00 | 22.06 |
Minimum of Months | 5.67 | 20.47 | 31.33 | 20.40 | 2.67 | 20.37 |
Maximum of Months | 502.00 | 26.08 | 503.50 | 24.37 | 400.83 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 352.17 | 20.56 | 352.17 | 20.51 |
February | 446.83 | 21.25 | 178.67 | 21.01 | 178.67 | 20.88 |
March | 459.33 | 22.20 | 35.67 | 22.17 | 21.50 | 22.09 |
April | 301.33 | 22.59 | 91.50 | 22.97 | 4.33 | 22.94 |
May | 142.50 | 23.06 | 284.00 | 24.00 | 4.83 | 24.01 |
June | 23.50 | 24.63 | 433.17 | 24.40 | 9.17 | 24.45 |
July | 36.83 | 25.45 | 470.83 | 24.59 | 25.50 | 24.68 |
August | 18.33 | 26.80 | 508.50 | 24.51 | 18.33 | 24.58 |
September | 60.33 | 23.91 | 380.17 | 24.36 | 19.17 | 24.43 |
October | 256.33 | 22.69 | 148.33 | 23.31 | 7.33 | 23.33 |
November | 446.00 | 22.36 | 31.00 | 22.37 | 14.50 | 22.32 |
December | 497.00 | 21.20 | 144.33 | 21.04 | 144.33 | 20.94 |
Annual Sum or Average | 3190.33 | 21.92 | 3058.33 | 22.69 | 799.83 | 22.51 |
Minimum of Months | 18.33 | 20.66 | 31.00 | 20.56 | 4.33 | 20.51 |
Maximum of Months | 502.00 | 26.80 | 508.50 | 24.59 | 352.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.83 | 20.85 | 250.83 | 20.59 | 246.00 | 20.44 |
February | 410.33 | 21.17 | 152.67 | 21.01 | 139.00 | 20.81 |
March | 405.67 | 22.02 | 80.00 | 22.19 | 29.33 | 22.07 |
April | 341.33 | 22.36 | 88.83 | 22.68 | 11.17 | 22.61 |
May | 217.00 | 22.77 | 211.00 | 23.51 | 12.00 | 23.51 |
June | 95.83 | 23.46 | 391.33 | 24.10 | 46.67 | 24.08 |
July | 75.33 | 23.94 | 470.83 | 24.33 | 66.50 | 24.30 |
August | 83.17 | 24.37 | 509.33 | 24.41 | 82.17 | 24.41 |
September | 94.67 | 23.71 | 395.17 | 24.32 | 43.67 | 24.37 |
October | 224.67 | 22.67 | 219.67 | 23.59 | 28.83 | 23.65 |
November | 346.50 | 22.34 | 79.50 | 22.74 | 9.83 | 22.68 |
December | 447.33 | 21.48 | 89.67 | 21.39 | 70.00 | 21.20 |
Annual Sum or Average | 3234.67 | 22.02 | 2938.83 | 22.81 | 785.17 | 22.66 |
Minimum of Months | 75.33 | 20.85 | 79.50 | 20.59 | 9.83 | 20.44 |
Maximum of Months | 492.83 | 24.37 | 509.33 | 24.41 | 246.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 343.17 | 20.53 | 343.17 | 20.48 |
February | 443.50 | 21.07 | 187.00 | 20.89 | 184.50 | 20.77 |
March | 441.50 | 21.98 | 66.17 | 22.04 | 34.00 | 21.95 |
April | 331.17 | 22.50 | 86.00 | 22.86 | 5.00 | 22.83 |
May | 165.33 | 23.02 | 251.50 | 23.85 | 5.83 | 23.87 |
June | 39.17 | 23.92 | 406.33 | 24.33 | 8.00 | 24.37 |
July | 33.17 | 25.11 | 464.67 | 24.50 | 21.00 | 24.57 |
August | 17.17 | 26.73 | 506.50 | 24.49 | 17.17 | 24.56 |
September | 65.83 | 23.82 | 374.83 | 24.34 | 19.17 | 24.41 |
October | 278.33 | 22.68 | 138.67 | 23.25 | 7.00 | 23.28 |
November | 436.17 | 22.17 | 35.67 | 22.19 | 20.67 | 22.13 |
December | 494.67 | 21.17 | 163.83 | 21.01 | 163.83 | 20.90 |
Annual Sum or Average | 3248.00 | 21.84 | 3024.33 | 22.60 | 829.33 | 22.41 |
Minimum of Months | 17.17 | 20.66 | 35.67 | 20.53 | 5.00 | 20.48 |
Maximum of Months | 502.00 | 26.73 | 506.50 | 24.50 | 343.17 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 388.33 | 20.32 | 388.33 | 20.28 |
February | 450.67 | 20.99 | 191.83 | 20.75 | 191.83 | 20.62 |
March | 457.00 | 22.08 | 72.00 | 22.07 | 41.67 | 21.96 |
April | 292.67 | 22.67 | 92.67 | 23.01 | 5.00 | 22.98 |
May | 109.83 | 23.17 | 288.33 | 23.98 | 0.00 | 23.98 |
June | 26.00 | 23.93 | 415.33 | 24.29 | 6.33 | 24.31 |
July | 20.33 | 24.70 | 475.50 | 24.43 | 13.67 | 24.46 |
August | 8.17 | 25.73 | 505.00 | 24.36 | 8.17 | 24.38 |
September | 100.00 | 23.44 | 301.83 | 24.11 | 17.17 | 24.16 |
October | 383.00 | 22.38 | 77.33 | 22.65 | 11.33 | 22.66 |
November | 479.67 | 21.71 | 70.33 | 21.56 | 70.33 | 21.44 |
December | 497.00 | 20.81 | 257.00 | 20.63 | 257.00 | 20.55 |
Annual Sum or Average | 3326.33 | 21.64 | 3135.50 | 22.34 | 1010.83 | 22.10 |
Minimum of Months | 8.17 | 20.42 | 70.33 | 20.32 | 0.00 | 20.28 |
Maximum of Months | 502.00 | 25.73 | 505.00 | 24.43 | 388.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.49 | 307.17 | 20.37 | 307.17 | 20.31 |
February | 370.00 | 21.11 | 155.67 | 20.89 | 151.67 | 20.75 |
March | 355.83 | 22.16 | 53.33 | 22.24 | 20.83 | 22.15 |
April | 213.17 | 22.62 | 117.17 | 23.25 | 4.50 | 23.23 |
May | 102.83 | 23.23 | 257.67 | 24.19 | 7.50 | 24.24 |
June | 35.50 | 24.95 | 356.33 | 24.52 | 18.50 | 24.61 |
July | 48.33 | 25.61 | 392.00 | 24.72 | 36.67 | 24.86 |
August | 27.67 | 26.32 | 412.17 | 24.59 | 25.33 | 24.70 |
September | 114.00 | 23.41 | 258.67 | 24.17 | 21.83 | 24.26 |
October | 282.17 | 22.25 | 94.17 | 22.76 | 11.83 | 22.78 |
November | 396.17 | 21.76 | 50.00 | 21.66 | 44.67 | 21.54 |
December | 422.00 | 20.85 | 196.00 | 20.67 | 196.00 | 20.57 |
Annual Sum or Average | 2794.67 | 21.78 | 2650.33 | 22.54 | 846.50 | 22.35 |
Minimum of Months | 27.67 | 20.49 | 50.00 | 20.37 | 4.50 | 20.31 |
Maximum of Months | 427.00 | 26.32 | 412.17 | 24.72 | 307.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 464.00 | 21.21 | 236.00 | 20.92 | 231.00 | 20.74 |
February | 389.50 | 21.56 | 131.50 | 21.46 | 112.33 | 21.26 |
March | 325.17 | 22.37 | 103.33 | 22.75 | 17.67 | 22.66 |
April | 216.17 | 22.74 | 147.00 | 23.39 | 5.17 | 23.37 |
May | 102.50 | 23.11 | 300.17 | 24.03 | 0.00 | 24.03 |
June | 36.17 | 23.80 | 406.50 | 24.29 | 7.00 | 24.32 |
July | 23.00 | 24.99 | 469.00 | 24.48 | 16.33 | 24.52 |
August | 23.67 | 26.50 | 506.00 | 24.49 | 23.67 | 24.57 |
September | 86.67 | 23.83 | 343.83 | 24.33 | 24.00 | 24.42 |
October | 247.17 | 22.63 | 196.83 | 23.44 | 18.33 | 23.51 |
November | 348.83 | 22.23 | 90.50 | 22.53 | 30.33 | 22.43 |
December | 423.67 | 21.51 | 133.67 | 21.34 | 117.67 | 21.14 |
Annual Sum or Average | 2686.50 | 22.11 | 3064.33 | 22.98 | 603.50 | 22.81 |
Minimum of Months | 23.00 | 21.21 | 90.50 | 20.92 | 0.00 | 20.74 |
Maximum of Months | 464.00 | 26.50 | 506.00 | 24.49 | 231.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 331.50 | 20.43 | 331.50 | 20.36 |
February | 434.50 | 21.05 | 177.33 | 20.87 | 172.00 | 20.73 |
March | 396.17 | 21.95 | 93.17 | 22.16 | 34.33 | 22.06 |
April | 259.17 | 22.52 | 147.67 | 23.16 | 6.67 | 23.15 |
May | 130.83 | 23.06 | 303.17 | 23.97 | 6.00 | 24.01 |
June | 55.67 | 24.08 | 402.67 | 24.34 | 16.67 | 24.42 |
July | 44.67 | 25.14 | 450.33 | 24.51 | 30.33 | 24.61 |
August | 25.17 | 26.01 | 487.33 | 24.46 | 21.00 | 24.54 |
September | 132.17 | 23.32 | 303.33 | 24.08 | 23.50 | 24.17 |
October | 346.17 | 22.23 | 114.00 | 22.73 | 12.50 | 22.76 |
November | 447.50 | 21.67 | 74.67 | 21.59 | 62.83 | 21.47 |
December | 494.17 | 20.95 | 214.50 | 20.75 | 214.50 | 20.64 |
Annual Sum or Average | 3268.17 | 21.72 | 3099.67 | 22.49 | 931.83 | 22.29 |
Minimum of Months | 25.17 | 20.60 | 74.67 | 20.43 | 6.00 | 20.36 |
Maximum of Months | 502.00 | 26.01 | 487.33 | 24.51 | 331.50 | 24.61 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76128 | 26.49904 | -0.1023 | 5.92357 |
February | 454.00000 | 23.35070 | 27.57730 | 0.06430 | 5.96497 |
March | 514.00000 | 24.13278 | 30.71820 | 0.31000 | 7.34901 |
April | 485.00000 | 24.36195 | 35.58899 | 0.41598 | 8.96336 |
May | 508.00000 | 24.45180 | 42.11154 | -0.3436 | 8.08666 |
June | 496.00000 | 24.39741 | 44.18842 | -0.3133 | 7.59785 |
July | 497.00000 | 24.46909 | 46.01325 | -0.2740 | 7.14233 |
August | 514.00000 | 24.40331 | 46.41372 | -0.2827 | 7.17874 |
September | 485.00000 | 24.45864 | 44.71597 | -0.2993 | 7.50327 |
October | 502.00000 | 24.34878 | 37.95864 | 0.43783 | 9.32608 |
November | 489.00000 | 24.15895 | 28.80161 | 0.29879 | 7.19204 |
December | 497.00000 | 23.59311 | 28.35409 | 0.12943 | 5.80023 |
Annual Sum or Average | 5943.00000 | 24.07863 | 36.65257 | 0.00212 | 7.34358 |
Minimum of Months | 454.00000 | 22.76128 | 26.49904 | -0.3436 | 5.80023 |
Maximum of Months | 514.00000 | 24.46909 | 46.41372 | 0.43783 | 9.32608 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19826 | 28.38954 | -0.4616 | 10.24733 |
February | 454.00000 | 21.81663 | 29.31060 | -0.2854 | 8.12978 |
March | 514.00000 | 23.07351 | 33.00171 | 0.06941 | 6.01131 |
April | 485.00000 | 23.63547 | 37.53142 | 0.24946 | 6.90534 |
May | 508.00000 | 23.98776 | 43.41497 | -0.5043 | 10.86304 |
June | 496.00000 | 24.13103 | 45.18984 | -0.4165 | 9.11700 |
July | 497.00000 | 24.20806 | 47.15190 | -0.3731 | 8.32393 |
August | 514.00000 | 24.21223 | 47.52055 | -0.3630 | 8.08726 |
September | 485.00000 | 24.06793 | 45.90081 | -0.4500 | 9.84892 |
October | 502.00000 | 23.45982 | 40.44346 | 0.22257 | 6.79355 |
November | 489.00000 | 22.77737 | 31.60356 | -0.0214 | 5.79312 |
December | 497.00000 | 21.76702 | 31.31480 | -0.2827 | 7.53796 |
Annual Sum or Average | 5943.00000 | 23.20489 | 38.47136 | -0.2182 | 8.13976 |
Minimum of Months | 454.00000 | 21.19826 | 28.38954 | -0.5043 | 5.79312 |
Maximum of Months | 514.00000 | 24.21223 | 47.52055 | 0.24946 | 10.86304 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.64460 | 28.65815 | -0.6255 | 14.93324 |
February | 454.00000 | 21.24126 | 29.84923 | -0.4424 | 11.16163 |
March | 514.00000 | 22.47512 | 33.54351 | -0.0749 | 6.65757 |
April | 485.00000 | 23.28444 | 37.72198 | 0.16617 | 6.66261 |
May | 508.00000 | 23.84045 | 43.11214 | -0.5493 | 12.19136 |
June | 496.00000 | 24.08874 | 45.08945 | -0.4195 | 9.30980 |
July | 497.00000 | 24.19614 | 47.14051 | -0.3642 | 8.27268 |
August | 514.00000 | 24.19193 | 47.53732 | -0.3568 | 8.00290 |
September | 485.00000 | 23.86626 | 45.88100 | -0.5205 | 11.68243 |
October | 502.00000 | 22.84779 | 41.44855 | 0.07232 | 6.47259 |
November | 489.00000 | 21.87554 | 32.78139 | -0.2428 | 7.38729 |
December | 497.00000 | 21.04825 | 32.32091 | -0.4789 | 11.05945 |
Annual Sum or Average | 5943.00000 | 22.81242 | 38.82818 | -0.3192 | 9.46950 |
Minimum of Months | 454.00000 | 20.64460 | 28.65815 | -0.6255 | 6.47259 |
Maximum of Months | 514.00000 | 24.19614 | 47.53732 | 0.16617 | 14.93324 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13532 | 29.34022 | -0.8139 | 21.71605 |
February | 454.00000 | 20.73329 | 31.48270 | -0.6096 | 15.77431 |
March | 514.00000 | 21.89855 | 35.84826 | -0.2217 | 8.64150 |
April | 485.00000 | 22.95013 | 40.18476 | 0.09225 | 7.49464 |
May | 508.00000 | 23.80352 | 44.98508 | -0.5428 | 13.05017 |
June | 496.00000 | 24.18687 | 46.34825 | -0.3428 | 8.61554 |
July | 497.00000 | 24.35592 | 48.99971 | -0.2589 | 7.48716 |
August | 514.00000 | 24.30023 | 49.52561 | -0.2723 | 7.27414 |
September | 485.00000 | 23.80677 | 48.57906 | -0.5245 | 12.85690 |
October | 502.00000 | 22.29891 | 45.30470 | -0.0566 | 7.40487 |
November | 489.00000 | 21.21374 | 35.74938 | -0.4197 | 10.60407 |
December | 497.00000 | 20.42011 | 33.12770 | -0.6784 | 17.09555 |
Annual Sum or Average | 5943.00000 | 22.52301 | 40.86109 | -0.3860 | 11.46511 |
Minimum of Months | 454.00000 | 20.13532 | 29.34022 | -0.8139 | 7.27414 |
Maximum of Months | 514.00000 | 24.35592 | 49.52561 | 0.09225 | 21.71605 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27882 | 29.05740 | -0.7577 | 19.46847 |
February | 454.00000 | 21.03210 | 30.91381 | -0.5150 | 13.94725 |
March | 514.00000 | 22.29554 | 34.95857 | -0.1041 | 7.84799 |
April | 485.00000 | 23.27100 | 39.11762 | 0.20510 | 8.25851 |
May | 508.00000 | 23.94540 | 44.06591 | -0.4320 | 11.68668 |
June | 496.00000 | 24.25846 | 45.74926 | -0.2525 | 7.97144 |
July | 497.00000 | 24.40982 | 48.34462 | -0.1724 | 7.66514 |
August | 514.00000 | 24.34146 | 48.92463 | -0.1943 | 7.15381 |
September | 485.00000 | 23.82705 | 47.91538 | -0.4562 | 12.44253 |
October | 502.00000 | 22.63300 | 44.09806 | 0.04679 | 7.86575 |
November | 489.00000 | 21.44668 | 35.10909 | -0.3424 | 9.38005 |
December | 497.00000 | 20.53894 | 32.84287 | -0.6258 | 15.34960 |
Annual Sum or Average | 5943.00000 | 22.70363 | 40.16179 | -0.2986 | 10.72196 |
Minimum of Months | 454.00000 | 20.27882 | 29.05740 | -0.7577 | 7.15381 |
Maximum of Months | 514.00000 | 24.40982 | 48.92463 | 0.20510 | 19.46847 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.06259 | 28.07880 | -0.5450 | 15.98909 |
February | 454.00000 | 21.65020 | 29.99224 | -0.3541 | 12.36549 |
March | 514.00000 | 22.70948 | 33.92732 | -0.0068 | 8.55840 |
April | 485.00000 | 23.28836 | 38.99465 | 0.19288 | 8.41849 |
May | 508.00000 | 23.83836 | 44.66315 | -0.5135 | 12.83924 |
June | 496.00000 | 24.16094 | 46.35957 | -0.3461 | 9.00156 |
July | 497.00000 | 24.36297 | 48.90488 | -0.2477 | 7.64000 |
August | 514.00000 | 24.34834 | 49.13608 | -0.2242 | 7.15659 |
September | 485.00000 | 23.97506 | 47.54817 | -0.4195 | 11.59169 |
October | 502.00000 | 23.07386 | 42.67820 | 0.16341 | 9.13704 |
November | 489.00000 | 22.33089 | 33.20239 | -0.1233 | 9.32334 |
December | 497.00000 | 21.43862 | 31.42566 | -0.3925 | 12.59063 |
Annual Sum or Average | 5943.00000 | 23.03097 | 39.65132 | -0.2342 | 10.36691 |
Minimum of Months | 454.00000 | 21.06259 | 28.07880 | -0.5450 | 7.15659 |
Maximum of Months | 514.00000 | 24.36297 | 49.13608 | 0.19288 | 15.98909 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29862 | 28.76945 | -0.7583 | 19.98196 |
February | 454.00000 | 20.92404 | 30.77567 | -0.5462 | 14.70523 |
March | 514.00000 | 22.09937 | 34.92119 | -0.1460 | 8.86835 |
April | 485.00000 | 22.98028 | 39.62922 | 0.14159 | 8.41785 |
May | 508.00000 | 23.67425 | 44.74432 | -0.5234 | 13.99712 |
June | 496.00000 | 24.09452 | 46.28407 | -0.3171 | 9.40663 |
July | 497.00000 | 24.26065 | 48.92078 | -0.2365 | 8.22545 |
August | 514.00000 | 24.25655 | 49.24600 | -0.2282 | 7.61342 |
September | 485.00000 | 23.67490 | 48.36049 | -0.5090 | 13.92098 |
October | 502.00000 | 22.39326 | 44.49682 | -0.0062 | 8.03377 |
November | 489.00000 | 21.39236 | 34.91726 | -0.3593 | 10.24787 |
December | 497.00000 | 20.57338 | 32.58542 | -0.6266 | 15.77776 |
Annual Sum or Average | 5943.00000 | 22.56543 | 40.37673 | -0.3416 | 11.57043 |
Minimum of Months | 454.00000 | 20.29862 | 28.76945 | -0.7583 | 7.61342 |
Maximum of Months | 514.00000 | 24.26065 | 49.24600 | 0.14159 | 19.98196 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47375 | 29.23458 | -0.7088 | 16.97685 |
February | 454.00000 | 20.87325 | 31.85370 | -0.5598 | 13.45139 |
March | 514.00000 | 21.74448 | 36.85606 | -0.2574 | 7.84148 |
April | 485.00000 | 22.54717 | 41.83927 | -0.0171 | 6.53896 |
May | 508.00000 | 23.63002 | 46.72552 | -0.6396 | 14.99273 |
June | 496.00000 | 24.15141 | 46.48227 | -0.3952 | 8.87302 |
July | 497.00000 | 24.31585 | 48.40014 | -0.3075 | 7.49351 |
August | 514.00000 | 24.29950 | 48.57159 | -0.3003 | 7.28106 |
September | 485.00000 | 24.10634 | 47.83187 | -0.4239 | 9.60739 |
October | 502.00000 | 23.02745 | 43.48602 | 0.12875 | 6.64381 |
November | 489.00000 | 22.04103 | 34.35768 | -0.1912 | 7.09175 |
December | 497.00000 | 20.95728 | 32.64738 | -0.5042 | 11.41907 |
Annual Sum or Average | 5943.00000 | 22.69385 | 40.76071 | -0.3473 | 9.83564 |
Minimum of Months | 454.00000 | 20.47375 | 29.23458 | -0.7088 | 6.53896 |
Maximum of Months | 514.00000 | 24.31585 | 48.57159 | 0.12875 | 16.97685 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.66279 | 29.36380 | -0.6400 | 14.85926 |
February | 454.00000 | 21.29483 | 31.55775 | -0.4375 | 11.42093 |
March | 514.00000 | 22.38649 | 35.93015 | -0.0865 | 6.85522 |
April | 485.00000 | 23.20272 | 40.30891 | 0.16419 | 7.20547 |
May | 508.00000 | 23.96966 | 45.35154 | -0.4711 | 11.72124 |
June | 496.00000 | 24.30637 | 45.70645 | -0.2787 | 7.56492 |
July | 497.00000 | 24.46476 | 47.67042 | -0.1908 | 7.04823 |
August | 514.00000 | 24.41394 | 47.91887 | -0.1973 | 6.72102 |
September | 485.00000 | 24.22315 | 47.15368 | -0.3259 | 8.59439 |
October | 502.00000 | 23.42386 | 42.31166 | 0.24689 | 7.85134 |
November | 489.00000 | 22.51716 | 33.75600 | -0.0639 | 6.54548 |
December | 497.00000 | 21.20146 | 32.56771 | -0.4230 | 9.85759 |
Annual Sum or Average | 5943.00000 | 23.01798 | 40.03366 | -0.2245 | 8.84006 |
Minimum of Months | 454.00000 | 20.66279 | 29.36380 | -0.6400 | 6.54548 |
Maximum of Months | 514.00000 | 24.46476 | 47.91887 | 0.24689 | 14.85926 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94334 | 26.90076 | -0.5172 | 13.62554 |
February | 454.00000 | 21.51488 | 29.31219 | -0.3457 | 11.14472 |
March | 514.00000 | 22.51875 | 34.57825 | -0.0340 | 7.48997 |
April | 485.00000 | 22.92234 | 40.34047 | 0.09717 | 7.27642 |
May | 508.00000 | 23.58052 | 48.37260 | -0.6179 | 15.07228 |
June | 496.00000 | 24.08908 | 50.23440 | -0.3836 | 9.14003 |
July | 497.00000 | 24.33564 | 53.02358 | -0.2598 | 7.15638 |
August | 514.00000 | 24.41095 | 53.53590 | -0.1928 | 6.47202 |
September | 485.00000 | 24.22362 | 49.66505 | -0.3070 | 8.69628 |
October | 502.00000 | 23.60126 | 41.98707 | 0.32510 | 9.47534 |
November | 489.00000 | 22.97958 | 31.56870 | 0.08245 | 7.79267 |
December | 497.00000 | 21.78072 | 30.16831 | -0.2444 | 8.94693 |
Annual Sum or Average | 5943.00000 | 23.08611 | 40.90624 | -0.1996 | 9.35280 |
Minimum of Months | 454.00000 | 20.94334 | 26.90076 | -0.6179 | 6.47202 |
Maximum of Months | 514.00000 | 24.41095 | 53.53590 | 0.32510 | 15.07228 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.66195 | 29.24418 | -0.6430 | 15.17646 |
February | 454.00000 | 21.15083 | 31.59269 | -0.4742 | 12.04297 |
March | 514.00000 | 22.29482 | 35.80683 | -0.1056 | 7.33700 |
April | 485.00000 | 23.05360 | 40.57546 | 0.12943 | 7.13593 |
May | 508.00000 | 23.83466 | 45.84662 | -0.5243 | 12.62373 |
June | 496.00000 | 24.23520 | 46.11562 | -0.3159 | 8.13933 |
July | 497.00000 | 24.38582 | 48.11104 | -0.2342 | 7.24249 |
August | 514.00000 | 24.39988 | 48.10663 | -0.2098 | 6.79341 |
September | 485.00000 | 24.21084 | 47.33919 | -0.3386 | 8.77382 |
October | 502.00000 | 23.34376 | 42.60037 | 0.22706 | 7.67024 |
November | 489.00000 | 22.39631 | 33.73848 | -0.0912 | 6.85843 |
December | 497.00000 | 21.18576 | 32.51189 | -0.4327 | 10.19509 |
Annual Sum or Average | 5943.00000 | 22.94249 | 40.20029 | -0.2502 | 9.15127 |
Minimum of Months | 454.00000 | 20.66195 | 29.24418 | -0.6430 | 6.79341 |
Maximum of Months | 514.00000 | 24.39988 | 48.11104 | 0.22706 | 15.17646 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42247 | 29.11308 | -0.7096 | 17.55248 |
February | 454.00000 | 21.00882 | 31.21767 | -0.5130 | 13.10970 |
March | 514.00000 | 22.29013 | 35.51752 | -0.1160 | 7.23265 |
April | 485.00000 | 23.24667 | 39.92832 | 0.16499 | 7.17110 |
May | 508.00000 | 23.97240 | 45.01666 | -0.4931 | 11.17076 |
June | 496.00000 | 24.23947 | 46.18779 | -0.3386 | 8.07118 |
July | 497.00000 | 24.37874 | 48.64345 | -0.2672 | 7.20776 |
August | 514.00000 | 24.32603 | 49.19402 | -0.2790 | 7.15813 |
September | 485.00000 | 24.01418 | 48.27923 | -0.4559 | 10.56474 |
October | 502.00000 | 22.75936 | 44.36719 | 0.06341 | 6.79067 |
November | 489.00000 | 21.75671 | 34.95086 | -0.2670 | 8.05089 |
December | 497.00000 | 20.81109 | 32.65277 | -0.5484 | 12.92441 |
Annual Sum or Average | 5943.00000 | 22.78254 | 40.49388 | -0.3123 | 9.72429 |
Minimum of Months | 454.00000 | 20.42247 | 29.11308 | -0.7096 | 6.79067 |
Maximum of Months | 514.00000 | 24.37874 | 49.19402 | 0.16499 | 17.55248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.49275 | 28.08421 | -0.6813 | 16.47888 |
February | 385.00000 | 21.23911 | 30.19484 | -0.4450 | 12.07498 |
March | 433.00000 | 22.51851 | 34.11886 | -0.0478 | 7.14954 |
April | 410.00000 | 23.42296 | 38.71042 | 0.23218 | 7.98300 |
May | 430.00000 | 24.07846 | 43.72440 | -0.4166 | 10.98432 |
June | 418.00000 | 24.35157 | 45.32669 | -0.2628 | 7.86835 |
July | 422.00000 | 24.52208 | 47.75621 | -0.1791 | 7.48134 |
August | 433.00000 | 24.43287 | 48.46148 | -0.2066 | 7.22780 |
September | 410.00000 | 24.02490 | 47.49815 | -0.4125 | 10.88080 |
October | 427.00000 | 22.90914 | 43.07565 | 0.11588 | 7.50861 |
November | 417.00000 | 21.88418 | 33.74225 | -0.2250 | 7.75918 |
December | 422.00000 | 20.85171 | 31.84736 | -0.5255 | 12.16982 |
Annual Sum or Average | 5034.00000 | 22.90413 | 39.43670 | -0.2537 | 9.61296 |
Minimum of Months | 385.00000 | 20.49275 | 28.08421 | -0.6813 | 7.14954 |
Maximum of Months | 433.00000 | 24.52208 | 48.46148 | 0.23218 | 16.47888 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.46054 | 27.69859 | -0.4223 | 12.80042 |
February | 454.00000 | 21.98971 | 29.59956 | -0.2484 | 10.26488 |
March | 514.00000 | 23.08665 | 33.50873 | 0.09345 | 7.72856 |
April | 485.00000 | 23.57519 | 38.68538 | 0.26200 | 8.20226 |
May | 508.00000 | 24.01236 | 44.67100 | -0.4632 | 10.88153 |
June | 496.00000 | 24.22852 | 46.17567 | -0.3382 | 8.28545 |
July | 497.00000 | 24.40220 | 48.52573 | -0.2521 | 7.25521 |
August | 514.00000 | 24.38417 | 48.78213 | -0.2293 | 6.97737 |
September | 485.00000 | 24.17200 | 47.27654 | -0.3560 | 9.49099 |
October | 502.00000 | 23.45931 | 41.79911 | 0.26599 | 8.96549 |
November | 489.00000 | 22.87001 | 32.26860 | 0.02408 | 8.08000 |
December | 497.00000 | 21.92333 | 30.70372 | -0.2491 | 9.71380 |
Annual Sum or Average | 5943.00000 | 23.30697 | 39.21714 | -0.1594 | 9.04407 |
Minimum of Months | 454.00000 | 21.46054 | 27.69859 | -0.4632 | 6.97737 |
Maximum of Months | 514.00000 | 24.40220 | 48.78213 | 0.26599 | 12.80042 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59991 | 28.67483 | -0.6516 | 16.07781 |
February | 454.00000 | 21.19449 | 30.64010 | -0.4512 | 12.22180 |
March | 514.00000 | 22.47868 | 34.68454 | -0.0435 | 7.68176 |
April | 485.00000 | 23.31551 | 39.33197 | 0.22052 | 8.14254 |
May | 508.00000 | 23.91262 | 44.72940 | -0.4561 | 11.42811 |
June | 496.00000 | 24.20446 | 46.07950 | -0.2980 | 8.32470 |
July | 497.00000 | 24.34361 | 48.51153 | -0.2292 | 7.54124 |
August | 514.00000 | 24.33043 | 48.89366 | -0.2228 | 7.15946 |
September | 485.00000 | 23.95508 | 48.04905 | -0.4220 | 10.94222 |
October | 502.00000 | 22.83014 | 43.71940 | 0.10875 | 7.54647 |
November | 489.00000 | 21.88658 | 34.29884 | -0.2167 | 8.03505 |
December | 497.00000 | 20.96757 | 32.23859 | -0.4970 | 11.92048 |
Annual Sum or Average | 5943.00000 | 22.84798 | 40.05963 | -0.2622 | 9.73056 |
Minimum of Months | 454.00000 | 20.59991 | 28.67483 | -0.6516 | 7.15946 |
Maximum of Months | 514.00000 | 24.34361 | 48.89366 | 0.22052 | 16.07781 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.199769E+10 | 0.489820E+09 | 52.83 | 0.123622E+10 | 0.761475E+09 | 0.00 | 0.63 | 19-JAN-20:00 | 0.00 | 01-JAN-00:10 | 21197.72 | 19-JAN-20:00 | 14915.02 | 31-JAN-15:10 | 10159.57 | 19-JAN-16:00 | 4937.47 | 19-JAN-20:00 | 0.00 |
February | 0.496106E+10 | 0.121366E+10 | 132.54 | 0.407509E+10 | 0.885970E+09 | 0.00 | 0.89 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 31798.74 | 28-FEB-15:10 | 31798.74 | 28-FEB-15:10 | 8759.06 | 18-FEB-16:30 | 7053.20 | 28-FEB-15:10 | 0.00 |
March | 0.150129E+11 | 0.351503E+10 | 267.83 | 0.117247E+11 | 0.328813E+10 | 0.00 | 1.00 | 29-MAR-14:50 | 0.00 | 01-MAR-00:10 | 49041.03 | 30-MAR-15:10 | 49041.03 | 30-MAR-15:10 | 14033.50 | 31-MAR-11:30 | 11362.17 | 30-MAR-15:10 | 0.00 |
April | 0.256881E+11 | 0.593094E+10 | 329.33 | 0.210057E+11 | 0.468245E+10 | 0.00 | 1.00 | 04-APR-10:50 | 0.00 | 01-APR-00:10 | 51582.72 | 17-APR-14:00 | 51582.72 | 17-APR-14:00 | 15991.64 | 21-APR-10:30 | 12320.52 | 17-APR-14:00 | 0.00 |
May | 0.489629E+11 | 0.110910E+11 | 410.14 | 0.372809E+11 | 0.116820E+11 | 0.00 | 1.00 | 01-MAY-14:50 | 0.00 | 01-MAY-00:10 | 69929.83 | 30-MAY-15:00 | 56371.92 | 30-MAY-15:00 | 22646.72 | 23-MAY-06:03 | 17250.06 | 30-MAY-15:00 | 0.00 |
June | 0.735298E+11 | 0.173333E+11 | 433.53 | 0.555088E+11 | 0.180210E+11 | 0.00 | 1.00 | 01-JUN-05:13 | 0.00 | 01-JUN-00:10 | 80073.10 | 28-JUN-12:05 | 60085.43 | 19-JUN-16:00 | 26551.10 | 27-JUN-12:00 | 20152.20 | 19-JUN-16:00 | 0.00 |
July | 0.845191E+11 | 0.201468E+11 | 439.78 | 0.606759E+11 | 0.238432E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 89213.71 | 07-JUL-12:03 | 66686.32 | 07-JUL-16:00 | 32123.20 | 26-JUL-06:03 | 23840.92 | 07-JUL-16:00 | 0.00 |
August | 0.964149E+11 | 0.227249E+11 | 465.70 | 0.676683E+11 | 0.287465E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 87345.63 | 17-AUG-12:03 | 77631.96 | 14-AUG-04:02 | 33775.26 | 24-AUG-06:03 | 23274.90 | 01-AUG-15:00 | 0.00 |
September | 0.618762E+11 | 0.139646E+11 | 411.94 | 0.458525E+11 | 0.160237E+11 | 0.00 | 1.00 | 01-SEP-05:13 | 0.00 | 01-SEP-00:10 | 85699.53 | 07-SEP-16:00 | 64749.13 | 07-SEP-15:50 | 26069.37 | 06-SEP-12:03 | 21627.40 | 07-SEP-16:00 | 0.00 |
October | 0.275370E+11 | 0.621706E+10 | 303.40 | 0.205354E+11 | 0.700161E+10 | 0.00 | 1.00 | 02-OCT-05:13 | 0.00 | 01-OCT-00:10 | 68659.64 | 10-OCT-16:00 | 56896.60 | 10-OCT-16:00 | 33072.64 | 02-OCT-05:13 | 16718.89 | 10-OCT-16:00 | 0.00 |
November | 0.109438E+11 | 0.258127E+10 | 220.36 | 0.833913E+10 | 0.260469E+10 | 0.00 | 0.94 | 02-NOV-14:10 | 0.00 | 01-NOV-00:10 | 34671.72 | 02-NOV-14:10 | 28473.82 | 02-NOV-14:10 | 12135.71 | 02-NOV-10:50 | 7435.69 | 03-NOV-15:00 | 0.00 |
December | 0.396239E+10 | 0.940212E+09 | 113.28 | 0.267585E+10 | 0.128654E+10 | 0.00 | 0.88 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 31673.59 | 12-DEC-14:00 | 24102.81 | 12-DEC-14:10 | 15967.38 | 13-DEC-16:40 | 6902.86 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.455406E+12 | 0.106149E+12 | 3580.68 | 0.336579E+12 | 0.118827E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.199769E+10 | 0.489820E+09 | 52.83 | 0.123622E+10 | 0.761475E+09 | 0.00 | 0.63 | 0.00 | 21197.72 | 14915.02 | 8759.06 | 4937.47 | 0.00 | ||||||
Maximum of Months | 0.964149E+11 | 0.227249E+11 | 465.70 | 0.676683E+11 | 0.287465E+11 | 0.00 | 1.00 | 0.00 | 89213.71 | 77631.96 | 33775.26 | 23840.92 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200835E+10 | 0.489702E+09 | 52.83 | 0.126820E+10 | 0.740153E+09 | 0.00 | 0.68 | 19-JAN-16:00 | 0.00 | 01-JAN-00:10 | 21910.88 | 19-JAN-16:00 | 14041.83 | 31-JAN-15:00 | 9854.74 | 19-JAN-15:10 | 5040.02 | 19-JAN-16:00 | 0.00 |
February | 0.494226E+10 | 0.121087E+10 | 135.47 | 0.406288E+10 | 0.879382E+09 | 0.00 | 0.79 | 28-FEB-15:30 | 0.00 | 01-FEB-00:10 | 26376.06 | 28-FEB-15:30 | 26376.06 | 28-FEB-15:30 | 8501.57 | 18-FEB-16:00 | 5983.33 | 28-FEB-15:10 | 0.00 |
March | 0.142263E+11 | 0.334931E+10 | 274.19 | 0.111161E+11 | 0.311023E+10 | 0.00 | 1.00 | 29-MAR-14:50 | 0.00 | 01-MAR-00:10 | 48459.00 | 30-MAR-15:10 | 48459.00 | 30-MAR-15:10 | 12322.28 | 31-MAR-11:30 | 11226.39 | 30-MAR-15:10 | 0.00 |
April | 0.248281E+11 | 0.575164E+10 | 341.21 | 0.203465E+11 | 0.448152E+10 | 0.00 | 1.00 | 04-APR-13:30 | 0.00 | 01-APR-00:10 | 54335.24 | 17-APR-15:40 | 54335.24 | 17-APR-15:40 | 14010.43 | 21-APR-10:40 | 12977.31 | 17-APR-15:40 | 0.00 |
May | 0.462255E+11 | 0.105182E+11 | 423.48 | 0.352264E+11 | 0.109991E+11 | 0.00 | 1.00 | 01-MAY-15:10 | 0.00 | 01-MAY-00:10 | 65988.75 | 30-MAY-15:10 | 52651.37 | 30-MAY-15:00 | 17253.65 | 31-MAY-13:00 | 16250.69 | 30-MAY-15:00 | 0.00 |
June | 0.679196E+11 | 0.160189E+11 | 439.25 | 0.505498E+11 | 0.173698E+11 | 0.00 | 1.00 | 01-JUN-08:70 | 0.00 | 01-JUN-00:10 | 74954.04 | 26-JUN-15:00 | 63568.23 | 26-JUN-05:12 | 23958.12 | 23-JUN-10:50 | 18769.78 | 27-JUN-16:00 | 0.00 |
July | 0.774759E+11 | 0.184349E+11 | 442.37 | 0.544152E+11 | 0.230607E+11 | 0.00 | 1.00 | 01-JUL-07:20 | 0.00 | 01-JUL-00:10 | 79347.88 | 07-JUL-16:00 | 64994.43 | 15-JUL-05:03 | 27152.80 | 26-JUL-10:50 | 22086.94 | 07-JUL-16:00 | 0.00 |
August | 0.865473E+11 | 0.203426E+11 | 463.85 | 0.589091E+11 | 0.276381E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 79254.12 | 17-AUG-15:30 | 71305.52 | 14-AUG-04:02 | 25710.25 | 24-AUG-14:00 | 21508.76 | 01-AUG-15:20 | 0.00 |
September | 0.532059E+11 | 0.120668E+11 | 411.02 | 0.381344E+11 | 0.150715E+11 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 77390.69 | 07-SEP-16:00 | 57201.39 | 07-SEP-15:30 | 22767.70 | 11-SEP-11:00 | 19434.79 | 07-SEP-16:00 | 0.00 |
October | 0.234098E+11 | 0.533468E+10 | 302.36 | 0.169656E+11 | 0.644424E+10 | 0.00 | 1.00 | 02-OCT-09:50 | 0.00 | 01-OCT-00:10 | 59558.80 | 11-OCT-14:10 | 47359.94 | 10-OCT-16:00 | 22581.27 | 18-OCT-15:00 | 14133.95 | 10-OCT-16:00 | 0.00 |
November | 0.973853E+10 | 0.231902E+10 | 219.43 | 0.725965E+10 | 0.247888E+10 | 0.00 | 0.86 | 05-NOV-13:32 | 0.00 | 01-NOV-00:10 | 29002.08 | 05-NOV-13:32 | 23082.93 | 05-NOV-13:32 | 10639.74 | 27-NOV-18:00 | 6351.53 | 05-NOV-13:32 | 0.00 |
December | 0.369216E+10 | 0.883520E+09 | 112.94 | 0.248861E+10 | 0.120356E+10 | 0.00 | 0.84 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 28500.51 | 12-DEC-14:00 | 20953.38 | 12-DEC-14:00 | 10672.31 | 13-DEC-17:02 | 6265.13 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.414220E+12 | 0.967203E+11 | 3618.41 | 0.300742E+12 | 0.113477E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.200835E+10 | 0.489702E+09 | 52.83 | 0.126820E+10 | 0.740153E+09 | 0.00 | 0.68 | 0.00 | 21910.88 | 14041.83 | 8501.57 | 5040.02 | 0.00 | ||||||
Maximum of Months | 0.865473E+11 | 0.203426E+11 | 463.85 | 0.589091E+11 | 0.276381E+11 | 0.00 | 1.00 | 0.00 | 79347.88 | 71305.52 | 27152.80 | 22086.94 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208812E+10 | 0.512351E+09 | 52.83 | 0.129695E+10 | 0.791170E+09 | 0.00 | 0.63 | 19-JAN-17:50 | 0.00 | 01-JAN-00:10 | 22048.37 | 19-JAN-17:50 | 14675.56 | 31-JAN-15:00 | 10703.56 | 19-JAN-16:00 | 5143.92 | 19-JAN-17:50 | 0.00 |
February | 0.511044E+10 | 0.125854E+10 | 134.49 | 0.416431E+10 | 0.946137E+09 | 0.00 | 0.82 | 26-FEB-15:13 | 0.00 | 01-FEB-00:10 | 30266.09 | 26-FEB-15:13 | 30266.09 | 26-FEB-15:13 | 8907.60 | 18-FEB-16:00 | 6858.70 | 26-FEB-15:13 | 0.00 |
March | 0.149369E+11 | 0.353913E+10 | 274.54 | 0.116299E+11 | 0.330704E+10 | 0.00 | 1.00 | 29-MAR-15:10 | 0.00 | 01-MAR-00:10 | 54013.65 | 30-MAR-15:30 | 54013.65 | 30-MAR-15:30 | 12130.55 | 31-MAR-11:30 | 12509.60 | 30-MAR-15:20 | 0.00 |
April | 0.266444E+11 | 0.620232E+10 | 340.99 | 0.218575E+11 | 0.478695E+10 | 0.00 | 1.00 | 04-APR-15:00 | 0.00 | 01-APR-00:10 | 60363.56 | 17-APR-15:40 | 60363.56 | 17-APR-15:40 | 13566.29 | 21-APR-10:50 | 14416.99 | 17-APR-15:40 | 0.00 |
May | 0.496304E+11 | 0.113632E+11 | 425.34 | 0.385225E+11 | 0.111078E+11 | 0.00 | 1.00 | 01-MAY-15:20 | 0.00 | 01-MAY-00:10 | 73968.09 | 30-MAY-15:10 | 63213.58 | 16-MAY-15:40 | 17261.85 | 31-MAY-13:00 | 18168.21 | 30-MAY-15:00 | 0.00 |
June | 0.725011E+11 | 0.171819E+11 | 440.93 | 0.549795E+11 | 0.175216E+11 | 0.00 | 1.00 | 01-JUN-09:30 | 0.00 | 01-JUN-00:10 | 82578.01 | 26-JUN-15:00 | 64407.33 | 27-JUN-15:30 | 24076.39 | 23-JUN-10:40 | 21023.26 | 27-JUN-15:50 | 0.00 |
July | 0.823764E+11 | 0.197085E+11 | 445.01 | 0.592145E+11 | 0.231619E+11 | 0.00 | 1.00 | 01-JUL-08:70 | 0.00 | 01-JUL-00:10 | 89545.63 | 07-JUL-16:00 | 71644.85 | 07-JUL-16:00 | 27234.75 | 26-JUL-10:40 | 24887.26 | 07-JUL-16:00 | 0.00 |
August | 0.910052E+11 | 0.214964E+11 | 465.14 | 0.634009E+11 | 0.276043E+11 | 0.00 | 1.00 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 88719.73 | 01-AUG-15:00 | 71779.46 | 02-AUG-16:00 | 25831.41 | 24-AUG-14:00 | 24257.72 | 01-AUG-15:00 | 0.00 |
September | 0.548678E+11 | 0.125384E+11 | 411.43 | 0.394961E+11 | 0.153717E+11 | 0.00 | 1.00 | 01-SEP-10:30 | 0.00 | 01-SEP-00:10 | 84820.85 | 06-SEP-14:00 | 64754.60 | 07-SEP-15:30 | 22744.17 | 11-SEP-11:00 | 21176.72 | 07-SEP-16:00 | 0.00 |
October | 0.237805E+11 | 0.546374E+10 | 298.87 | 0.171467E+11 | 0.663384E+10 | 0.00 | 1.00 | 02-OCT-11:00 | 0.00 | 01-OCT-00:10 | 64295.94 | 11-OCT-14:00 | 51833.83 | 10-OCT-15:40 | 22639.89 | 18-OCT-15:00 | 15125.15 | 10-OCT-14:00 | 0.00 |
November | 0.100445E+11 | 0.240761E+10 | 217.94 | 0.741647E+10 | 0.262806E+10 | 0.00 | 0.81 | 02-NOV-13:50 | 0.00 | 01-NOV-00:10 | 30240.05 | 02-NOV-13:40 | 23619.53 | 05-NOV-15:05 | 11031.05 | 27-NOV-18:00 | 6726.67 | 02-NOV-13:00 | 0.00 |
December | 0.380672E+10 | 0.915216E+09 | 111.50 | 0.254801E+10 | 0.125871E+10 | 0.00 | 0.82 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 30441.40 | 12-DEC-14:00 | 22412.15 | 12-DEC-14:00 | 10945.47 | 13-DEC-16:00 | 6742.74 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.436793E+12 | 0.102587E+12 | 3619.02 | 0.321673E+12 | 0.115119E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.208812E+10 | 0.512351E+09 | 52.83 | 0.129695E+10 | 0.791170E+09 | 0.00 | 0.63 | 0.00 | 22048.37 | 14675.56 | 8907.60 | 5143.92 | 0.00 | ||||||
Maximum of Months | 0.910052E+11 | 0.214964E+11 | 465.14 | 0.634009E+11 | 0.276043E+11 | 0.00 | 1.00 | 0.00 | 89545.63 | 71779.46 | 27234.75 | 24887.26 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 47.74 | 1775.69 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 144.47 | 1451.86 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 320.87 | 908.32 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 596.63 | 730.12 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 890.41 | 479.27 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1265.62 | 305.69 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1263.06 | 221.55 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1152.80 | 184.04 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 669.24 | 399.84 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 314.28 | 828.48 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 181.03 | 1120.53 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 52.94 | 1423.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 577.33 | 815.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 47.74 | 184.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1265.62 | 1775.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 298.18 | 1058.39 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 513.29 | 872.03 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 752.40 | 559.75 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1092.80 | 460.68 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1323.98 | 316.08 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1560.45 | 203.96 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1571.74 | 148.16 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1463.24 | 122.21 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1049.92 | 257.36 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 729.46 | 515.33 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 466.55 | 673.84 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 306.84 | 847.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 929.55 | 501.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 298.18 | 122.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1571.74 | 1058.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1718.18 | 1493.18 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1742.57 | 1285.80 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1699.81 | 892.10 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1412.48 | 755.88 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1202.27 | 508.27 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1323.25 | 324.88 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1404.66 | 230.47 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1706.77 | 192.77 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1603.01 | 412.25 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 2008.62 | 813.18 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1956.02 | 1040.93 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1808.37 | 1252.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1631.90 | 764.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1202.27 | 192.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 2008.62 | 1493.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 342.52 | 1100.83 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 506.80 | 923.83 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 898.12 | 602.76 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1153.68 | 499.25 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1265.47 | 341.62 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1499.51 | 223.31 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1465.09 | 158.45 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1450.31 | 134.15 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1036.06 | 272.25 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 787.33 | 555.24 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 530.96 | 734.21 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 333.18 | 908.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 941.37 | 535.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 333.18 | 134.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1499.51 | 1100.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.87 | 0.00 | 92.87 | 15.12 | 620.47 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 49.65 | 499.42 | 0.00 | 0.00 | 0.00 |
March | 144.52 | 0.00 | 144.52 | 115.17 | 302.34 | 0.00 | 0.00 | 0.00 |
April | 174.81 | 0.78 | 174.04 | 214.64 | 232.46 | 0.00 | 0.00 | 0.00 |
May | 209.07 | 6.67 | 202.40 | 310.34 | 151.49 | 0.00 | 0.00 | 0.00 |
June | 230.09 | 15.19 | 214.90 | 430.57 | 98.61 | 0.00 | 0.00 | 0.00 |
July | 217.09 | 10.55 | 206.54 | 428.90 | 71.39 | 0.00 | 0.00 | 0.00 |
August | 193.07 | 2.10 | 190.97 | 389.03 | 60.89 | 0.00 | 0.00 | 0.00 |
September | 145.94 | 0.02 | 145.92 | 220.81 | 146.64 | 0.00 | 0.00 | 0.00 |
October | 110.96 | 0.00 | 110.96 | 98.25 | 310.54 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 51.44 | 419.31 | 0.00 | 0.00 | 0.00 |
December | 85.85 | 0.00 | 85.85 | 15.48 | 522.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.80 | 2.96 | 147.85 | 195.77 | 285.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.85 | 0.00 | 85.85 | 15.12 | 60.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.09 | 15.19 | 214.90 | 430.57 | 620.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 15.12 | 620.51 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 49.65 | 499.45 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 115.17 | 302.36 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 214.65 | 232.47 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 310.36 | 151.50 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 430.59 | 98.62 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 428.92 | 71.39 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 389.05 | 60.90 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 220.82 | 146.65 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 98.26 | 310.56 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 51.44 | 419.33 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 15.48 | 523.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 195.78 | 285.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 15.12 | 60.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 430.59 | 620.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.88 | 0.00 | 92.88 | 15.12 | 620.51 | 0.00 | 0.00 | 0.00 |
February | 102.94 | 0.00 | 102.94 | 49.65 | 499.45 | 0.00 | 0.00 | 0.00 |
March | 144.53 | 0.00 | 144.53 | 115.17 | 302.36 | 0.00 | 0.00 | 0.00 |
April | 174.82 | 0.78 | 174.04 | 214.65 | 232.47 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 6.67 | 202.41 | 310.36 | 151.50 | 0.00 | 0.00 | 0.00 |
June | 230.10 | 15.19 | 214.91 | 430.59 | 98.62 | 0.00 | 0.00 | 0.00 |
July | 217.10 | 10.55 | 206.55 | 428.92 | 71.39 | 0.00 | 0.00 | 0.00 |
August | 193.08 | 2.10 | 190.97 | 389.05 | 60.90 | 0.00 | 0.00 | 0.00 |
September | 145.95 | 0.02 | 145.93 | 220.82 | 146.65 | 0.00 | 0.00 | 0.00 |
October | 110.97 | 0.00 | 110.97 | 98.26 | 310.56 | 0.00 | 0.00 | 0.00 |
November | 99.31 | 0.00 | 99.31 | 51.44 | 419.33 | 0.00 | 0.00 | 0.00 |
December | 85.86 | 0.00 | 85.86 | 15.48 | 523.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.81 | 2.96 | 147.85 | 195.78 | 285.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.86 | 0.00 | 85.86 | 15.12 | 60.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 230.10 | 15.19 | 214.91 | 430.59 | 620.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 392.41 | 177.00 | 215.42 | 281.96 | 1077.08 | 0.00 | 0.00 | 0.00 |
February | 494.71 | 265.80 | 228.91 | 495.68 | 877.79 | 0.00 | 0.00 | 0.00 |
March | 622.40 | 283.33 | 339.07 | 737.42 | 553.42 | 0.00 | 0.00 | 0.00 |
April | 752.65 | 343.19 | 409.46 | 1075.89 | 438.57 | 0.00 | 0.00 | 0.00 |
May | 826.46 | 349.50 | 476.96 | 1297.01 | 299.67 | 0.00 | 0.00 | 0.00 |
June | 855.67 | 358.63 | 497.04 | 1517.34 | 197.38 | 0.00 | 0.00 | 0.00 |
July | 834.31 | 350.75 | 483.55 | 1525.91 | 145.22 | 0.00 | 0.00 | 0.00 |
August | 763.12 | 302.75 | 460.36 | 1416.87 | 123.97 | 0.00 | 0.00 | 0.00 |
September | 627.18 | 277.89 | 349.29 | 1005.35 | 280.18 | 0.00 | 0.00 | 0.00 |
October | 535.04 | 278.39 | 256.64 | 686.01 | 566.68 | 0.00 | 0.00 | 0.00 |
November | 427.77 | 193.69 | 234.08 | 420.09 | 741.36 | 0.00 | 0.00 | 0.00 |
December | 370.53 | 168.90 | 201.63 | 282.15 | 909.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.81 | 279.11 | 346.71 | 897.22 | 515.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.53 | 168.90 | 201.63 | 281.96 | 123.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 855.67 | 358.63 | 497.04 | 1525.91 | 1077.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.52 | 7.00 | 8.52 | 11.15 | 42.59 | 0.00 | 0.00 | 0.00 |
February | 19.56 | 10.51 | 9.05 | 19.60 | 34.71 | 0.00 | 0.00 | 0.00 |
March | 24.61 | 11.20 | 13.41 | 29.16 | 21.88 | 0.00 | 0.00 | 0.00 |
April | 29.76 | 13.57 | 16.19 | 42.54 | 17.34 | 0.00 | 0.00 | 0.00 |
May | 32.68 | 13.82 | 18.86 | 51.28 | 11.85 | 0.00 | 0.00 | 0.00 |
June | 33.83 | 14.18 | 19.65 | 59.99 | 7.80 | 0.00 | 0.00 | 0.00 |
July | 32.99 | 13.87 | 19.12 | 60.33 | 5.74 | 0.00 | 0.00 | 0.00 |
August | 30.17 | 11.97 | 18.20 | 56.02 | 4.90 | 0.00 | 0.00 | 0.00 |
September | 24.80 | 10.99 | 13.81 | 39.75 | 11.08 | 0.00 | 0.00 | 0.00 |
October | 21.15 | 11.01 | 10.15 | 27.12 | 22.41 | 0.00 | 0.00 | 0.00 |
November | 16.91 | 7.66 | 9.26 | 16.61 | 29.31 | 0.00 | 0.00 | 0.00 |
December | 14.65 | 6.68 | 7.97 | 11.16 | 35.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.74 | 11.04 | 13.71 | 35.48 | 20.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.65 | 6.68 | 7.97 | 11.15 | 4.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.83 | 14.18 | 19.65 | 60.33 | 42.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 577.74 | 532.12 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 588.53 | 453.06 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 578.96 | 307.92 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 487.36 | 245.94 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 415.26 | 161.58 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 450.39 | 104.99 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 475.93 | 75.00 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 573.16 | 66.22 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 533.74 | 153.23 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 667.04 | 310.06 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 644.30 | 399.04 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 600.48 | 469.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 549.31 | 272.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 415.26 | 66.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 667.04 | 532.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.70 | 346.30 | 150.40 | 577.74 | 532.12 | 0.00 | 0.00 | 0.00 |
February | 463.59 | 310.76 | 152.83 | 588.53 | 453.06 | 0.00 | 0.00 | 0.00 |
March | 416.93 | 217.28 | 199.65 | 578.96 | 307.92 | 0.00 | 0.00 | 0.00 |
April | 312.25 | 101.64 | 210.61 | 487.36 | 245.94 | 0.00 | 0.00 | 0.00 |
May | 252.29 | 29.32 | 222.96 | 415.26 | 161.58 | 0.00 | 0.00 | 0.00 |
June | 233.27 | 12.98 | 220.29 | 450.39 | 104.99 | 0.00 | 0.00 | 0.00 |
July | 235.83 | 17.58 | 218.24 | 475.93 | 75.00 | 0.00 | 0.00 | 0.00 |
August | 281.56 | 52.60 | 228.96 | 573.16 | 66.22 | 0.00 | 0.00 | 0.00 |
September | 309.65 | 115.17 | 194.47 | 533.74 | 153.23 | 0.00 | 0.00 | 0.00 |
October | 448.90 | 290.79 | 158.10 | 667.04 | 310.06 | 0.00 | 0.00 | 0.00 |
November | 482.93 | 320.46 | 162.47 | 644.30 | 399.04 | 0.00 | 0.00 | 0.00 |
December | 489.61 | 344.44 | 145.17 | 600.48 | 469.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.22 | 179.33 | 188.88 | 549.31 | 272.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.27 | 12.98 | 145.17 | 415.26 | 66.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.70 | 346.30 | 228.96 | 667.04 | 532.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.67 | 346.28 | 150.39 | 577.71 | 532.09 | 0.00 | 0.00 | 0.00 |
February | 463.56 | 310.74 | 152.82 | 588.49 | 453.03 | 0.00 | 0.00 | 0.00 |
March | 416.90 | 217.26 | 199.64 | 578.92 | 307.90 | 0.00 | 0.00 | 0.00 |
April | 312.23 | 101.64 | 210.59 | 487.33 | 245.93 | 0.00 | 0.00 | 0.00 |
May | 252.27 | 29.32 | 222.95 | 415.23 | 161.57 | 0.00 | 0.00 | 0.00 |
June | 233.25 | 12.98 | 220.27 | 450.37 | 104.98 | 0.00 | 0.00 | 0.00 |
July | 235.81 | 17.58 | 218.23 | 475.90 | 75.00 | 0.00 | 0.00 | 0.00 |
August | 281.54 | 52.59 | 228.95 | 573.13 | 66.22 | 0.00 | 0.00 | 0.00 |
September | 309.63 | 115.16 | 194.46 | 533.71 | 153.22 | 0.00 | 0.00 | 0.00 |
October | 448.87 | 290.78 | 158.09 | 667.00 | 310.04 | 0.00 | 0.00 | 0.00 |
November | 482.90 | 320.44 | 162.46 | 644.26 | 399.01 | 0.00 | 0.00 | 0.00 |
December | 489.58 | 344.42 | 145.16 | 600.44 | 469.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 368.19 | 179.32 | 188.87 | 549.28 | 272.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 233.25 | 12.98 | 145.16 | 415.23 | 66.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.67 | 346.28 | 228.95 | 667.00 | 532.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 403.06 | 186.97 | 216.10 | 330.68 | 1121.10 | 0.00 | 0.00 | 0.00 |
February | 462.72 | 216.35 | 246.37 | 494.46 | 929.02 | 0.00 | 0.00 | 0.00 |
March | 682.02 | 329.56 | 352.45 | 879.87 | 599.64 | 0.00 | 0.00 | 0.00 |
April | 767.26 | 351.09 | 416.16 | 1134.37 | 479.71 | 0.00 | 0.00 | 0.00 |
May | 771.11 | 292.14 | 478.97 | 1237.20 | 326.73 | 0.00 | 0.00 | 0.00 |
June | 810.93 | 311.96 | 498.97 | 1458.12 | 218.04 | 0.00 | 0.00 | 0.00 |
July | 764.89 | 283.59 | 481.30 | 1421.23 | 155.88 | 0.00 | 0.00 | 0.00 |
August | 749.48 | 280.28 | 469.21 | 1402.60 | 136.89 | 0.00 | 0.00 | 0.00 |
September | 610.62 | 254.35 | 356.27 | 989.72 | 297.75 | 0.00 | 0.00 | 0.00 |
October | 543.99 | 282.39 | 261.60 | 744.85 | 612.99 | 0.00 | 0.00 | 0.00 |
November | 434.15 | 194.87 | 239.28 | 491.51 | 804.53 | 0.00 | 0.00 | 0.00 |
December | 358.17 | 156.66 | 201.51 | 313.92 | 970.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.97 | 261.88 | 352.09 | 910.40 | 552.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.17 | 156.66 | 201.51 | 313.92 | 136.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.93 | 351.09 | 498.97 | 1458.12 | 1121.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.94 | 7.39 | 8.54 | 13.07 | 44.33 | 0.00 | 0.00 | 0.00 |
February | 18.30 | 8.55 | 9.74 | 19.55 | 36.73 | 0.00 | 0.00 | 0.00 |
March | 26.97 | 13.03 | 13.94 | 34.79 | 23.71 | 0.00 | 0.00 | 0.00 |
April | 30.34 | 13.88 | 16.45 | 44.85 | 18.97 | 0.00 | 0.00 | 0.00 |
May | 30.49 | 11.55 | 18.94 | 48.92 | 12.92 | 0.00 | 0.00 | 0.00 |
June | 32.06 | 12.33 | 19.73 | 57.65 | 8.62 | 0.00 | 0.00 | 0.00 |
July | 30.24 | 11.21 | 19.03 | 56.19 | 6.16 | 0.00 | 0.00 | 0.00 |
August | 29.63 | 11.08 | 18.55 | 55.46 | 5.41 | 0.00 | 0.00 | 0.00 |
September | 24.14 | 10.06 | 14.09 | 39.13 | 11.77 | 0.00 | 0.00 | 0.00 |
October | 21.51 | 11.17 | 10.34 | 29.45 | 24.24 | 0.00 | 0.00 | 0.00 |
November | 17.17 | 7.70 | 9.46 | 19.43 | 31.81 | 0.00 | 0.00 | 0.00 |
December | 14.16 | 6.19 | 7.97 | 12.41 | 38.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.28 | 10.35 | 13.92 | 36.00 | 21.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.16 | 6.19 | 7.97 | 12.41 | 5.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.06 | 13.88 | 19.73 | 57.65 | 44.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.63 | 0.00 | 278.63 | 42.77 | 1873.23 | 0.00 | 0.00 | 0.00 |
February | 308.83 | 0.00 | 308.83 | 137.23 | 1534.14 | 0.00 | 0.00 | 0.00 |
March | 433.58 | 0.00 | 433.58 | 307.34 | 971.77 | 0.00 | 0.00 | 0.00 |
April | 524.46 | 2.33 | 522.13 | 588.30 | 769.46 | 0.00 | 0.00 | 0.00 |
May | 627.24 | 20.02 | 607.23 | 888.73 | 498.75 | 0.00 | 0.00 | 0.00 |
June | 690.31 | 45.58 | 644.73 | 1271.10 | 313.52 | 0.00 | 0.00 | 0.00 |
July | 651.31 | 31.66 | 619.65 | 1271.97 | 226.00 | 0.00 | 0.00 | 0.00 |
August | 579.23 | 6.31 | 572.92 | 1160.60 | 188.67 | 0.00 | 0.00 | 0.00 |
September | 437.84 | 0.06 | 437.78 | 664.24 | 427.75 | 0.00 | 0.00 | 0.00 |
October | 332.91 | 0.00 | 332.91 | 299.59 | 898.51 | 0.00 | 0.00 | 0.00 |
November | 297.94 | 0.00 | 297.94 | 160.58 | 1217.16 | 0.00 | 0.00 | 0.00 |
December | 257.57 | 0.00 | 257.57 | 45.75 | 1538.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.43 | 8.87 | 443.57 | 572.30 | 868.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.57 | 0.00 | 257.57 | 42.77 | 188.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 690.31 | 45.58 | 644.73 | 1271.97 | 1873.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 407.94 | 184.00 | 223.94 | 287.85 | 1116.91 | 0.00 | 0.00 | 0.00 |
February | 514.28 | 276.32 | 237.96 | 503.09 | 920.64 | 0.00 | 0.00 | 0.00 |
March | 647.02 | 294.54 | 352.48 | 741.37 | 594.29 | 0.00 | 0.00 | 0.00 |
April | 782.42 | 356.76 | 425.66 | 1087.96 | 481.40 | 0.00 | 0.00 | 0.00 |
May | 859.15 | 363.32 | 495.83 | 1324.68 | 326.45 | 0.00 | 0.00 | 0.00 |
June | 889.51 | 372.82 | 516.70 | 1565.61 | 208.39 | 0.00 | 0.00 | 0.00 |
July | 867.31 | 364.63 | 502.68 | 1578.83 | 151.01 | 0.00 | 0.00 | 0.00 |
August | 793.30 | 314.73 | 478.57 | 1469.78 | 125.07 | 0.00 | 0.00 | 0.00 |
September | 651.99 | 288.88 | 363.11 | 1047.66 | 273.16 | 0.00 | 0.00 | 0.00 |
October | 556.20 | 289.40 | 266.80 | 718.63 | 552.72 | 0.00 | 0.00 | 0.00 |
November | 444.69 | 201.35 | 243.33 | 446.62 | 727.43 | 0.00 | 0.00 | 0.00 |
December | 385.18 | 175.58 | 209.60 | 293.98 | 914.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 650.57 | 290.15 | 360.42 | 924.36 | 530.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.18 | 175.58 | 209.60 | 287.85 | 125.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 889.51 | 372.82 | 516.70 | 1578.83 | 1116.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1490.14 | 1038.92 | 451.22 | 1695.67 | 1579.49 | 0.00 | 0.00 | 0.00 |
February | 1390.80 | 932.29 | 458.51 | 1726.42 | 1361.02 | 0.00 | 0.00 | 0.00 |
March | 1250.80 | 651.84 | 598.96 | 1686.44 | 949.80 | 0.00 | 0.00 | 0.00 |
April | 936.76 | 304.94 | 631.83 | 1406.69 | 794.47 | 0.00 | 0.00 | 0.00 |
May | 756.87 | 87.97 | 668.90 | 1203.04 | 529.28 | 0.00 | 0.00 | 0.00 |
June | 699.80 | 38.94 | 660.86 | 1329.98 | 334.75 | 0.00 | 0.00 | 0.00 |
July | 707.49 | 52.75 | 654.73 | 1414.11 | 236.25 | 0.00 | 0.00 | 0.00 |
August | 844.69 | 157.79 | 686.90 | 1715.87 | 198.01 | 0.00 | 0.00 | 0.00 |
September | 928.95 | 345.52 | 583.43 | 1600.50 | 438.52 | 0.00 | 0.00 | 0.00 |
October | 1346.71 | 872.40 | 474.31 | 1996.18 | 873.57 | 0.00 | 0.00 | 0.00 |
November | 1448.82 | 961.41 | 487.41 | 1928.96 | 1124.32 | 0.00 | 0.00 | 0.00 |
December | 1468.86 | 1033.36 | 435.51 | 1782.86 | 1349.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1104.67 | 538.01 | 566.66 | 1623.68 | 811.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 699.80 | 38.94 | 435.51 | 1203.04 | 198.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1490.14 | 1038.92 | 686.90 | 1996.18 | 1579.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 419.01 | 194.36 | 224.64 | 336.00 | 1162.35 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 224.90 | 256.11 | 501.14 | 976.40 | 0.00 | 0.00 | 0.00 |
March | 708.99 | 342.60 | 366.39 | 890.20 | 642.88 | 0.00 | 0.00 | 0.00 |
April | 797.60 | 364.98 | 432.62 | 1148.60 | 525.54 | 0.00 | 0.00 | 0.00 |
May | 801.61 | 303.70 | 497.91 | 1264.47 | 356.30 | 0.00 | 0.00 | 0.00 |
June | 843.00 | 324.30 | 518.70 | 1503.74 | 230.65 | 0.00 | 0.00 | 0.00 |
July | 795.14 | 294.81 | 500.33 | 1470.20 | 163.01 | 0.00 | 0.00 | 0.00 |
August | 779.13 | 291.36 | 487.76 | 1455.19 | 138.12 | 0.00 | 0.00 | 0.00 |
September | 634.78 | 264.41 | 370.36 | 1031.75 | 291.19 | 0.00 | 0.00 | 0.00 |
October | 565.51 | 293.56 | 271.95 | 778.76 | 599.23 | 0.00 | 0.00 | 0.00 |
November | 451.32 | 202.57 | 248.74 | 516.96 | 793.83 | 0.00 | 0.00 | 0.00 |
December | 372.33 | 162.86 | 209.47 | 324.58 | 979.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 638.25 | 272.24 | 366.02 | 937.44 | 569.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 372.33 | 162.86 | 209.47 | 324.58 | 138.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 843.00 | 364.98 | 518.70 | 1503.74 | 1162.35 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.127869E+09 | 0.475602E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.349499E+09 | 0.351234E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.859428E+09 | 0.243284E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.154647E+10 | 0.189246E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.238488E+10 | 0.128368E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.328050E+10 | 0.792351E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.338298E+10 | 0.593407E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.308766E+10 | 0.492921E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.173468E+10 | 0.103639E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.841765E+09 | 0.221900E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.469242E+09 | 0.290440E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.141792E+09 | 0.381339E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.182068E+11 | 0.257292E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.127869E+09 | 0.492921E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.338298E+10 | 0.475602E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.798648E+09 | 0.283480E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.124175E+10 | 0.210962E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.201523E+10 | 0.149924E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.283253E+10 | 0.119409E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.354614E+10 | 0.846588E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.404468E+10 | 0.528673E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.420974E+10 | 0.396840E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.391915E+10 | 0.327314E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.272139E+10 | 0.667067E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.195378E+10 | 0.138026E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.120930E+10 | 0.174659E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.821836E+09 | 0.227079E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.293142E+11 | 0.158019E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.798648E+09 | 0.327314E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.420974E+10 | 0.283480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.460197E+10 | 0.399932E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.421562E+10 | 0.311062E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.455276E+10 | 0.238940E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.366115E+10 | 0.195924E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.322016E+10 | 0.136134E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.342986E+10 | 0.842092E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.376224E+10 | 0.617279E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.457140E+10 | 0.516306E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.415500E+10 | 0.106854E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.537990E+10 | 0.217802E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.507002E+10 | 0.269809E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.484353E+10 | 0.335480E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.514636E+11 | 0.240951E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.322016E+10 | 0.516306E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.537990E+10 | 0.399932E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.917409E+09 | 0.294846E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.122606E+10 | 0.223492E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.240553E+10 | 0.161442E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.299034E+10 | 0.129405E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.338943E+10 | 0.914999E+09 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.388674E+10 | 0.578811E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.392409E+10 | 0.424395E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.388451E+10 | 0.359296E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.268547E+10 | 0.705669E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.210877E+10 | 0.148717E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.137626E+10 | 0.190308E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.892388E+09 | 0.243380E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.296870E+11 | 0.168991E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.892388E+09 | 0.359296E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.392409E+10 | 0.294846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248747E+09 | 0.00 | 0.248747E+09 | 40489501.74 | 0.166187E+10 |
February | 0.249030E+09 | 0.00 | 0.249030E+09 | 0.120112E+09 | 0.120820E+10 |
March | 0.387084E+09 | 0.00 | 0.387084E+09 | 0.308466E+09 | 0.809784E+09 |
April | 0.453110E+09 | 2009678.92 | 0.451101E+09 | 0.556353E+09 | 0.602527E+09 |
May | 0.559977E+09 | 17871404.04 | 0.542106E+09 | 0.831226E+09 | 0.405757E+09 |
June | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.111605E+10 | 0.255605E+09 |
July | 0.581461E+09 | 28265234.63 | 0.553196E+09 | 0.114876E+10 | 0.191202E+09 |
August | 0.517114E+09 | 5633145.20 | 0.511481E+09 | 0.104198E+10 | 0.163100E+09 |
September | 0.378280E+09 | 53251.27 | 0.378227E+09 | 0.572348E+09 | 0.380084E+09 |
October | 0.297206E+09 | 0.00 | 0.297206E+09 | 0.263160E+09 | 0.831742E+09 |
November | 0.257408E+09 | 0.00 | 0.257408E+09 | 0.133336E+09 | 0.108684E+10 |
December | 0.229948E+09 | 0.00 | 0.229948E+09 | 41462073.38 | 0.140074E+10 |
Annual Sum or Average | 0.475577E+10 | 93209170.84 | 0.466256E+10 | 0.617374E+10 | 0.899746E+10 |
Minimum of Months | 0.229948E+09 | 0.00 | 0.229948E+09 | 40489501.74 | 0.163100E+09 |
Maximum of Months | 0.596400E+09 | 39376456.78 | 0.557023E+09 | 0.114876E+10 | 0.166187E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 40489950.29 | 0.166198E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.120116E+09 | 0.120827E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.308476E+09 | 0.809832E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.556376E+09 | 0.602562E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.831261E+09 | 0.405779E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.111610E+10 | 0.255618E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.114881E+10 | 0.191211E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.104203E+10 | 0.163107E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.572373E+09 | 0.380105E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.263170E+09 | 0.831791E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.133340E+09 | 0.108691E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 41461976.01 | 0.140083E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.617400E+10 | 0.899799E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 40489950.29 | 0.163107E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.114881E+10 | 0.166198E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248757E+09 | 0.00 | 0.248757E+09 | 40489950.29 | 0.166198E+10 |
February | 0.249040E+09 | 0.00 | 0.249040E+09 | 0.120116E+09 | 0.120827E+10 |
March | 0.387100E+09 | 0.00 | 0.387100E+09 | 0.308476E+09 | 0.809832E+09 |
April | 0.453129E+09 | 2009732.94 | 0.451119E+09 | 0.556376E+09 | 0.602562E+09 |
May | 0.560000E+09 | 17871884.42 | 0.542128E+09 | 0.831261E+09 | 0.405779E+09 |
June | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.111610E+10 | 0.255618E+09 |
July | 0.581484E+09 | 28265994.40 | 0.553218E+09 | 0.114881E+10 | 0.191211E+09 |
August | 0.517135E+09 | 5633296.63 | 0.511501E+09 | 0.104203E+10 | 0.163107E+09 |
September | 0.378295E+09 | 53252.70 | 0.378242E+09 | 0.572373E+09 | 0.380105E+09 |
October | 0.297218E+09 | 0.00 | 0.297218E+09 | 0.263170E+09 | 0.831791E+09 |
November | 0.257419E+09 | 0.00 | 0.257419E+09 | 0.133340E+09 | 0.108691E+10 |
December | 0.229957E+09 | 0.00 | 0.229957E+09 | 41461976.01 | 0.140083E+10 |
Annual Sum or Average | 0.475596E+10 | 93211676.32 | 0.466275E+10 | 0.617400E+10 | 0.899799E+10 |
Minimum of Months | 0.229957E+09 | 0.00 | 0.229957E+09 | 40489950.29 | 0.163107E+09 |
Maximum of Months | 0.596423E+09 | 39377515.23 | 0.557046E+09 | 0.114881E+10 | 0.166198E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105104E+10 | 0.474071E+09 | 0.576970E+09 | 0.755199E+09 | 0.288486E+10 |
February | 0.119680E+10 | 0.643031E+09 | 0.553772E+09 | 0.119914E+10 | 0.212354E+10 |
March | 0.166704E+10 | 0.758884E+09 | 0.908160E+09 | 0.197509E+10 | 0.148228E+10 |
April | 0.195086E+10 | 0.889537E+09 | 0.106132E+10 | 0.278871E+10 | 0.113678E+10 |
May | 0.221359E+10 | 0.936093E+09 | 0.127750E+10 | 0.347390E+10 | 0.802631E+09 |
June | 0.221789E+10 | 0.929567E+09 | 0.128832E+10 | 0.393294E+10 | 0.511620E+09 |
July | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.408699E+10 | 0.388964E+09 |
August | 0.204393E+10 | 0.810897E+09 | 0.123303E+10 | 0.379495E+10 | 0.332031E+09 |
September | 0.162564E+10 | 0.720278E+09 | 0.905366E+09 | 0.260587E+10 | 0.726225E+09 |
October | 0.143304E+10 | 0.745643E+09 | 0.687397E+09 | 0.183741E+10 | 0.151779E+10 |
November | 0.110877E+10 | 0.502044E+09 | 0.606724E+09 | 0.108888E+10 | 0.192160E+10 |
December | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.755717E+09 | 0.243688E+10 |
Annual Sum or Average | 0.197356E+11 | 0.880189E+10 | 0.109338E+11 | 0.282948E+11 | 0.162652E+11 |
Minimum of Months | 0.992421E+09 | 0.452382E+09 | 0.540039E+09 | 0.755199E+09 | 0.332031E+09 |
Maximum of Months | 0.223461E+10 | 0.939459E+09 | 0.129515E+10 | 0.408699E+10 | 0.288486E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41557201.42 | 18744328.32 | 22812873.10 | 29859897.26 | 0.114065E+09 |
February | 47320506.07 | 25424863.36 | 21895642.72 | 47413040.73 | 83962849.99 |
March | 65913438.86 | 30005591.80 | 35907847.06 | 78093445.60 | 58608116.76 |
April | 77135194.26 | 35171493.49 | 41963700.77 | 0.110263E+09 | 44947330.82 |
May | 87523548.73 | 37012286.17 | 50511262.56 | 0.137355E+09 | 31735319.33 |
June | 87693210.88 | 36754233.49 | 50938977.38 | 0.155505E+09 | 20228980.67 |
July | 88354573.77 | 37145363.44 | 51209210.33 | 0.161596E+09 | 15379287.65 |
August | 80815226.94 | 32062140.92 | 48753086.02 | 0.150049E+09 | 13128205.95 |
September | 64276518.48 | 28479146.03 | 35797372.45 | 0.103034E+09 | 28714280.61 |
October | 56661118.88 | 29482041.05 | 27179077.83 | 72649604.74 | 60012078.81 |
November | 43839703.36 | 19850374.49 | 23989328.87 | 43053227.36 | 75978298.51 |
December | 39239425.34 | 17886781.13 | 21352644.21 | 29880365.95 | 96352050.86 |
Annual Sum or Average | 0.780330E+09 | 0.348019E+09 | 0.432311E+09 | 0.111875E+10 | 0.643112E+09 |
Minimum of Months | 39239425.34 | 17886781.13 | 21352644.21 | 29859897.26 | 13128205.95 |
Maximum of Months | 88354573.77 | 37145363.44 | 51209210.33 | 0.161596E+09 | 0.114065E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.154742E+10 | 0.142524E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.142377E+10 | 0.109604E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.155068E+10 | 0.824728E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126324E+10 | 0.637487E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111223E+10 | 0.432779E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.116742E+10 | 0.272134E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.127473E+10 | 0.200888E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.153516E+10 | 0.177367E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138345E+10 | 0.397173E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.178660E+10 | 0.830470E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.167003E+10 | 0.103431E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.160833E+10 | 0.125853E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.173231E+11 | 0.858715E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111223E+10 | 0.177367E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.178660E+10 | 0.142524E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133037E+10 | 0.927527E+09 | 0.402843E+09 | 0.154742E+10 | 0.142524E+10 |
February | 0.112152E+10 | 0.751783E+09 | 0.369736E+09 | 0.142377E+10 | 0.109604E+10 |
March | 0.111669E+10 | 0.581952E+09 | 0.534742E+09 | 0.155068E+10 | 0.824728E+09 |
April | 0.809353E+09 | 0.263460E+09 | 0.545893E+09 | 0.126324E+10 | 0.637487E+09 |
May | 0.675724E+09 | 78536548.52 | 0.597187E+09 | 0.111223E+10 | 0.432779E+09 |
June | 0.604624E+09 | 33644551.71 | 0.570980E+09 | 0.116742E+10 | 0.272134E+09 |
July | 0.631639E+09 | 47098022.03 | 0.584540E+09 | 0.127473E+10 | 0.200888E+09 |
August | 0.754129E+09 | 0.140873E+09 | 0.613257E+09 | 0.153516E+10 | 0.177367E+09 |
September | 0.802601E+09 | 0.298524E+09 | 0.504077E+09 | 0.138345E+10 | 0.397173E+09 |
October | 0.120232E+10 | 0.778864E+09 | 0.423460E+09 | 0.178660E+10 | 0.830470E+09 |
November | 0.125176E+10 | 0.830643E+09 | 0.421114E+09 | 0.167003E+10 | 0.103431E+10 |
December | 0.131138E+10 | 0.922561E+09 | 0.388815E+09 | 0.160833E+10 | 0.125853E+10 |
Annual Sum or Average | 0.116121E+11 | 0.565547E+10 | 0.595665E+10 | 0.173231E+11 | 0.858715E+10 |
Minimum of Months | 0.604624E+09 | 33644551.71 | 0.369736E+09 | 0.111223E+10 | 0.177367E+09 |
Maximum of Months | 0.133037E+10 | 0.927527E+09 | 0.613257E+09 | 0.178660E+10 | 0.142524E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133029E+10 | 0.927469E+09 | 0.402817E+09 | 0.154733E+10 | 0.142515E+10 |
February | 0.112145E+10 | 0.751735E+09 | 0.369713E+09 | 0.142368E+10 | 0.109597E+10 |
March | 0.111662E+10 | 0.581915E+09 | 0.534708E+09 | 0.155058E+10 | 0.824675E+09 |
April | 0.809302E+09 | 0.263443E+09 | 0.545859E+09 | 0.126316E+10 | 0.637447E+09 |
May | 0.675681E+09 | 78531585.46 | 0.597149E+09 | 0.111216E+10 | 0.432752E+09 |
June | 0.604586E+09 | 33642425.56 | 0.570944E+09 | 0.116735E+10 | 0.272117E+09 |
July | 0.631599E+09 | 47095045.70 | 0.584504E+09 | 0.127465E+10 | 0.200875E+09 |
August | 0.754082E+09 | 0.140864E+09 | 0.613218E+09 | 0.153506E+10 | 0.177355E+09 |
September | 0.802550E+09 | 0.298505E+09 | 0.504045E+09 | 0.138337E+10 | 0.397148E+09 |
October | 0.120225E+10 | 0.778815E+09 | 0.423434E+09 | 0.178649E+10 | 0.830417E+09 |
November | 0.125168E+10 | 0.830591E+09 | 0.421088E+09 | 0.166992E+10 | 0.103424E+10 |
December | 0.131129E+10 | 0.922503E+09 | 0.388791E+09 | 0.160823E+10 | 0.125845E+10 |
Annual Sum or Average | 0.116114E+11 | 0.565511E+10 | 0.595627E+10 | 0.173220E+11 | 0.858660E+10 |
Minimum of Months | 0.604586E+09 | 33642425.56 | 0.369713E+09 | 0.111216E+10 | 0.177355E+09 |
Maximum of Months | 0.133029E+10 | 0.927469E+09 | 0.613218E+09 | 0.178649E+10 | 0.142515E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107957E+10 | 0.500778E+09 | 0.578790E+09 | 0.885682E+09 | 0.300276E+10 |
February | 0.111940E+10 | 0.523386E+09 | 0.596015E+09 | 0.119619E+10 | 0.224749E+10 |
March | 0.182671E+10 | 0.882705E+09 | 0.944005E+09 | 0.235665E+10 | 0.160609E+10 |
April | 0.198873E+10 | 0.910029E+09 | 0.107870E+10 | 0.294029E+10 | 0.124342E+10 |
May | 0.206535E+10 | 0.782478E+09 | 0.128288E+10 | 0.331371E+10 | 0.875104E+09 |
June | 0.210193E+10 | 0.808598E+09 | 0.129333E+10 | 0.377944E+10 | 0.565170E+09 |
July | 0.204868E+10 | 0.759579E+09 | 0.128910E+10 | 0.380662E+10 | 0.417511E+09 |
August | 0.200742E+10 | 0.750692E+09 | 0.125673E+10 | 0.375673E+10 | 0.366643E+09 |
September | 0.158274E+10 | 0.659277E+09 | 0.923461E+09 | 0.256536E+10 | 0.771768E+09 |
October | 0.145703E+10 | 0.756357E+09 | 0.700675E+09 | 0.199500E+10 | 0.164183E+10 |
November | 0.112531E+10 | 0.505094E+09 | 0.620213E+09 | 0.127399E+10 | 0.208533E+10 |
December | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.840815E+09 | 0.260062E+10 |
Annual Sum or Average | 0.193622E+11 | 0.825858E+10 | 0.111036E+11 | 0.287105E+11 | 0.174237E+11 |
Minimum of Months | 0.959316E+09 | 0.419605E+09 | 0.539712E+09 | 0.840815E+09 | 0.366643E+09 |
Maximum of Months | 0.210193E+10 | 0.910029E+09 | 0.129333E+10 | 0.380662E+10 | 0.300276E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42685035.43 | 19800245.05 | 22884790.38 | 35018931.31 | 0.118726E+09 |
February | 44259987.63 | 20694142.70 | 23565844.93 | 47296014.71 | 88863776.82 |
March | 72226267.00 | 34901238.65 | 37325028.36 | 93179695.80 | 63503160.50 |
April | 78632209.33 | 35981626.23 | 42650583.10 | 0.116256E+09 | 49163544.40 |
May | 81662019.58 | 30938378.45 | 50723641.13 | 0.131021E+09 | 34600799.22 |
June | 83108020.92 | 31971121.65 | 51136899.27 | 0.149435E+09 | 22346294.47 |
July | 81002876.45 | 30032981.75 | 50969894.70 | 0.150510E+09 | 16507997.59 |
August | 79371262.08 | 29681575.71 | 49689686.37 | 0.148537E+09 | 14496727.82 |
September | 62579864.35 | 26067143.10 | 36512721.25 | 0.101432E+09 | 30514990.82 |
October | 57609595.62 | 29905591.65 | 27704003.97 | 78880113.01 | 64916381.41 |
November | 44493501.38 | 19970895.60 | 24522605.78 | 50372212.67 | 82452184.00 |
December | 37930402.25 | 16590743.33 | 21339658.92 | 33244921.74 | 0.102826E+09 |
Annual Sum or Average | 0.765561E+09 | 0.326536E+09 | 0.439025E+09 | 0.113518E+10 | 0.688918E+09 |
Minimum of Months | 37930402.25 | 16590743.33 | 21339658.92 | 33244921.74 | 14496727.82 |
Maximum of Months | 83108020.92 | 35981626.23 | 51136899.27 | 0.150510E+09 | 0.118726E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.114555E+09 | 0.501726E+10 |
February | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.331984E+09 | 0.371139E+10 |
March | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.823184E+09 | 0.260278E+10 |
April | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.152487E+10 | 0.199445E+10 |
May | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.238038E+10 | 0.133586E+10 |
June | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.329470E+10 | 0.812640E+09 |
July | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.340685E+10 | 0.605322E+09 |
August | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.310855E+10 | 0.505333E+09 |
September | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.172172E+10 | 0.110872E+10 |
October | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.802413E+09 | 0.240658E+10 |
November | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.416230E+09 | 0.315488E+10 |
December | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.122529E+09 | 0.412004E+10 |
Annual Sum or Average | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.180480E+11 | 0.273753E+11 |
Minimum of Months | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.114555E+09 | 0.505333E+09 |
Maximum of Months | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.340685E+10 | 0.501726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.770966E+09 | 0.299152E+10 |
February | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.121709E+10 | 0.222722E+10 |
March | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.198568E+10 | 0.159174E+10 |
April | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.281999E+10 | 0.124778E+10 |
May | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.354802E+10 | 0.874360E+09 |
June | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.405806E+10 | 0.540145E+09 |
July | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.422875E+10 | 0.404469E+09 |
August | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.393665E+10 | 0.334989E+09 |
September | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.271554E+10 | 0.708018E+09 |
October | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.192479E+10 | 0.148041E+10 |
November | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.115764E+10 | 0.188550E+10 |
December | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.787386E+09 | 0.244935E+10 |
Annual Sum or Average | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.291506E+11 | 0.167355E+11 |
Minimum of Months | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.770966E+09 | 0.334989E+09 |
Maximum of Months | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.422875E+10 | 0.299152E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.454168E+10 | 0.423050E+10 |
February | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.417655E+10 | 0.329259E+10 |
March | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.451697E+10 | 0.254395E+10 |
April | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.364613E+10 | 0.205927E+10 |
May | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.322222E+10 | 0.141763E+10 |
June | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.344732E+10 | 0.867672E+09 |
July | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.378755E+10 | 0.632784E+09 |
August | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.459579E+10 | 0.530357E+09 |
September | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.414851E+10 | 0.113665E+10 |
October | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.534658E+10 | 0.233978E+10 |
November | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.499986E+10 | 0.291424E+10 |
December | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.477521E+10 | 0.361440E+10 |
Annual Sum or Average | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.512044E+11 | 0.255798E+11 |
Minimum of Months | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.322222E+10 | 0.530357E+09 |
Maximum of Months | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.534658E+10 | 0.423050E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.899932E+09 | 0.311325E+10 |
February | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.121236E+10 | 0.236211E+10 |
March | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.238431E+10 | 0.172190E+10 |
April | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.297716E+10 | 0.136220E+10 |
May | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.338675E+10 | 0.954316E+09 |
June | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.389769E+10 | 0.597836E+09 |
July | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.393777E+10 | 0.436607E+09 |
August | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.389757E+10 | 0.369948E+09 |
September | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.267428E+10 | 0.754764E+09 |
October | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.208582E+10 | 0.160497E+10 |
November | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.133997E+10 | 0.205761E+10 |
December | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.869349E+09 | 0.262376E+10 |
Annual Sum or Average | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.295630E+11 | 0.179593E+11 |
Minimum of Months | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.869349E+09 | 0.369948E+09 |
Maximum of Months | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.393777E+10 | 0.311325E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 47.74 | 1775.69 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 144.47 | 1451.86 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 320.87 | 908.32 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 596.63 | 730.12 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 890.41 | 479.27 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1265.62 | 305.69 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1263.06 | 221.55 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1152.80 | 184.04 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 669.24 | 399.84 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 314.28 | 828.48 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 181.03 | 1120.53 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 52.94 | 1423.76 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 577.33 | 815.87 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 47.74 | 184.04 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1265.62 | 1775.69 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.18 | 1058.39 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 513.29 | 872.03 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 752.40 | 559.75 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1092.80 | 460.68 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1323.98 | 316.08 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1560.45 | 203.96 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1571.74 | 148.16 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1463.24 | 122.21 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1049.92 | 257.36 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 729.46 | 515.33 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 466.55 | 673.84 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 306.84 | 847.82 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 929.55 | 501.07 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 298.18 | 122.21 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1571.74 | 1058.39 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1718.18 | 1493.18 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1742.57 | 1285.80 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1699.81 | 892.10 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1412.48 | 755.88 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1202.27 | 508.27 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1323.25 | 324.88 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1404.66 | 230.47 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1706.77 | 192.77 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1603.01 | 412.25 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 2008.62 | 813.18 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1956.02 | 1040.93 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1808.37 | 1252.54 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1631.90 | 764.05 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1202.27 | 192.77 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 2008.62 | 1493.18 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 342.52 | 1100.83 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 506.80 | 923.83 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 898.12 | 602.76 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1153.68 | 499.25 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1265.47 | 341.62 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1499.51 | 223.31 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1465.09 | 158.45 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1450.31 | 134.15 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1036.06 | 272.25 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 787.33 | 555.24 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 530.96 | 734.21 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 333.18 | 908.68 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 941.37 | 535.87 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 333.18 | 134.15 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1499.51 | 1100.83 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.35 | 1861.49 | 278.62 | 0.00 | 278.62 | 0.00 | 0.00 |
February | 148.95 | 1498.32 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 345.51 | 907.05 | 433.57 | 0.00 | 433.57 | 0.00 | 0.00 |
April | 643.95 | 697.40 | 524.45 | 2.33 | 522.12 | 0.00 | 0.00 |
May | 931.06 | 454.49 | 627.23 | 20.02 | 607.21 | 0.00 | 0.00 |
June | 1291.76 | 295.85 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
July | 1286.73 | 214.17 | 651.30 | 31.66 | 619.64 | 0.00 | 0.00 |
August | 1167.13 | 182.69 | 579.22 | 6.31 | 572.91 | 0.00 | 0.00 |
September | 662.46 | 439.93 | 437.84 | 0.06 | 437.77 | 0.00 | 0.00 |
October | 294.77 | 931.65 | 332.90 | 0.00 | 332.90 | 0.00 | 0.00 |
November | 154.33 | 1257.97 | 297.93 | 0.00 | 297.93 | 0.00 | 0.00 |
December | 46.44 | 1569.00 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 587.32 | 855.96 | 452.43 | 8.87 | 443.56 | 0.00 | 0.00 |
Minimum of Months | 45.35 | 182.69 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1291.76 | 1861.49 | 690.30 | 45.58 | 644.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.11 | 1119.67 | 407.93 | 184.00 | 223.93 | 0.00 | 0.00 |
February | 515.28 | 912.49 | 514.27 | 276.31 | 237.96 | 0.00 | 0.00 |
March | 766.57 | 575.30 | 647.01 | 294.54 | 352.47 | 0.00 | 0.00 |
April | 1118.43 | 455.91 | 782.41 | 356.75 | 425.65 | 0.00 | 0.00 |
May | 1348.29 | 311.52 | 859.14 | 363.32 | 495.82 | 0.00 | 0.00 |
June | 1577.33 | 205.19 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
July | 1586.24 | 150.96 | 867.30 | 364.62 | 502.67 | 0.00 | 0.00 |
August | 1472.89 | 128.87 | 793.29 | 314.72 | 478.56 | 0.00 | 0.00 |
September | 1045.10 | 291.26 | 651.98 | 288.87 | 363.10 | 0.00 | 0.00 |
October | 713.14 | 589.08 | 556.19 | 289.40 | 266.79 | 0.00 | 0.00 |
November | 436.70 | 770.67 | 444.68 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 293.31 | 945.80 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 932.70 | 536.16 | 650.56 | 290.14 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 293.11 | 128.87 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1586.24 | 1119.67 | 889.50 | 372.81 | 516.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1733.19 | 1596.34 | 1490.08 | 1038.88 | 451.20 | 0.00 | 0.00 |
February | 1765.56 | 1359.15 | 1390.74 | 932.25 | 458.49 | 0.00 | 0.00 |
March | 1736.83 | 923.73 | 1250.75 | 651.81 | 598.94 | 0.00 | 0.00 |
April | 1462.05 | 737.82 | 936.73 | 304.92 | 631.81 | 0.00 | 0.00 |
May | 1245.75 | 484.73 | 756.84 | 87.96 | 668.88 | 0.00 | 0.00 |
June | 1351.16 | 314.96 | 699.78 | 38.94 | 660.84 | 0.00 | 0.00 |
July | 1427.75 | 225.00 | 707.47 | 52.75 | 654.71 | 0.00 | 0.00 |
August | 1719.45 | 198.66 | 844.66 | 157.78 | 686.88 | 0.00 | 0.00 |
September | 1601.19 | 459.68 | 928.92 | 345.51 | 583.41 | 0.00 | 0.00 |
October | 2001.08 | 930.17 | 1346.66 | 872.37 | 474.30 | 0.00 | 0.00 |
November | 1932.86 | 1197.09 | 1448.76 | 961.37 | 487.39 | 0.00 | 0.00 |
December | 1801.41 | 1409.62 | 1468.80 | 1033.31 | 435.49 | 0.00 | 0.00 |
Annual Sum or Average | 1647.90 | 816.87 | 1104.63 | 537.99 | 566.64 | 0.00 | 0.00 |
Minimum of Months | 1245.75 | 198.66 | 699.78 | 38.94 | 435.49 | 0.00 | 0.00 |
Maximum of Months | 2001.08 | 1596.34 | 1490.08 | 1038.88 | 686.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 343.75 | 1165.43 | 419.00 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 514.01 | 965.76 | 481.01 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 914.66 | 623.35 | 708.98 | 342.59 | 366.39 | 0.00 | 0.00 |
April | 1179.22 | 498.68 | 797.59 | 364.97 | 432.62 | 0.00 | 0.00 |
May | 1286.11 | 339.64 | 801.60 | 303.69 | 497.91 | 0.00 | 0.00 |
June | 1515.77 | 226.67 | 842.99 | 324.29 | 518.70 | 0.00 | 0.00 |
July | 1477.42 | 162.04 | 795.13 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1458.06 | 142.30 | 779.12 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1028.85 | 309.52 | 634.77 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 774.30 | 637.23 | 565.50 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 510.94 | 836.34 | 451.31 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 326.34 | 1009.35 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 946.40 | 574.35 | 638.25 | 272.23 | 366.01 | 0.00 | 0.00 |
Minimum of Months | 326.34 | 142.30 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1515.77 | 1165.43 | 842.99 | 364.97 | 518.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.77 | 1873.23 | 278.63 | 0.00 | 278.63 | 0.00 | 0.00 |
February | 137.23 | 1534.14 | 308.83 | 0.00 | 308.83 | 0.00 | 0.00 |
March | 307.34 | 971.77 | 433.58 | 0.00 | 433.58 | 0.00 | 0.00 |
April | 588.30 | 769.46 | 524.46 | 2.33 | 522.13 | 0.00 | 0.00 |
May | 888.73 | 498.75 | 627.24 | 20.02 | 607.23 | 0.00 | 0.00 |
June | 1271.10 | 313.52 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
July | 1271.97 | 226.00 | 651.31 | 31.66 | 619.65 | 0.00 | 0.00 |
August | 1160.60 | 188.67 | 579.23 | 6.31 | 572.92 | 0.00 | 0.00 |
September | 664.24 | 427.75 | 437.84 | 0.06 | 437.78 | 0.00 | 0.00 |
October | 299.59 | 898.51 | 332.91 | 0.00 | 332.91 | 0.00 | 0.00 |
November | 160.58 | 1217.16 | 297.94 | 0.00 | 297.94 | 0.00 | 0.00 |
December | 45.75 | 1538.25 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Annual Sum or Average | 572.30 | 868.06 | 452.43 | 8.87 | 443.57 | 0.00 | 0.00 |
Minimum of Months | 42.77 | 188.67 | 257.57 | 0.00 | 257.57 | 0.00 | 0.00 |
Maximum of Months | 1271.97 | 1873.23 | 690.31 | 45.58 | 644.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.85 | 1116.91 | 407.94 | 184.00 | 223.94 | 0.00 | 0.00 |
February | 503.09 | 920.64 | 514.28 | 276.32 | 237.96 | 0.00 | 0.00 |
March | 741.37 | 594.29 | 647.02 | 294.54 | 352.48 | 0.00 | 0.00 |
April | 1087.96 | 481.40 | 782.42 | 356.76 | 425.66 | 0.00 | 0.00 |
May | 1324.68 | 326.45 | 859.15 | 363.32 | 495.83 | 0.00 | 0.00 |
June | 1565.61 | 208.39 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
July | 1578.83 | 151.01 | 867.31 | 364.63 | 502.68 | 0.00 | 0.00 |
August | 1469.78 | 125.07 | 793.30 | 314.73 | 478.57 | 0.00 | 0.00 |
September | 1047.66 | 273.16 | 651.99 | 288.88 | 363.11 | 0.00 | 0.00 |
October | 718.63 | 552.72 | 556.20 | 289.40 | 266.80 | 0.00 | 0.00 |
November | 446.62 | 727.43 | 444.69 | 201.35 | 243.33 | 0.00 | 0.00 |
December | 293.98 | 914.48 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Annual Sum or Average | 924.36 | 530.68 | 650.57 | 290.15 | 360.42 | 0.00 | 0.00 |
Minimum of Months | 287.85 | 125.07 | 385.18 | 175.58 | 209.60 | 0.00 | 0.00 |
Maximum of Months | 1578.83 | 1116.91 | 889.51 | 372.82 | 516.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1695.67 | 1579.49 | 1490.14 | 1038.92 | 451.22 | 0.00 | 0.00 |
February | 1726.42 | 1361.02 | 1390.80 | 932.29 | 458.51 | 0.00 | 0.00 |
March | 1686.44 | 949.80 | 1250.80 | 651.84 | 598.96 | 0.00 | 0.00 |
April | 1406.69 | 794.47 | 936.76 | 304.94 | 631.83 | 0.00 | 0.00 |
May | 1203.04 | 529.28 | 756.87 | 87.97 | 668.90 | 0.00 | 0.00 |
June | 1329.98 | 334.75 | 699.80 | 38.94 | 660.86 | 0.00 | 0.00 |
July | 1414.11 | 236.25 | 707.49 | 52.75 | 654.73 | 0.00 | 0.00 |
August | 1715.87 | 198.01 | 844.69 | 157.79 | 686.90 | 0.00 | 0.00 |
September | 1600.50 | 438.52 | 928.95 | 345.52 | 583.43 | 0.00 | 0.00 |
October | 1996.18 | 873.57 | 1346.71 | 872.40 | 474.31 | 0.00 | 0.00 |
November | 1928.96 | 1124.32 | 1448.82 | 961.41 | 487.41 | 0.00 | 0.00 |
December | 1782.86 | 1349.46 | 1468.86 | 1033.36 | 435.51 | 0.00 | 0.00 |
Annual Sum or Average | 1623.68 | 811.13 | 1104.67 | 538.01 | 566.66 | 0.00 | 0.00 |
Minimum of Months | 1203.04 | 198.01 | 699.80 | 38.94 | 435.51 | 0.00 | 0.00 |
Maximum of Months | 1996.18 | 1579.49 | 1490.14 | 1038.92 | 686.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.00 | 1162.35 | 419.01 | 194.36 | 224.64 | 0.00 | 0.00 |
February | 501.14 | 976.40 | 481.02 | 224.90 | 256.11 | 0.00 | 0.00 |
March | 890.20 | 642.88 | 708.99 | 342.60 | 366.39 | 0.00 | 0.00 |
April | 1148.60 | 525.54 | 797.60 | 364.98 | 432.62 | 0.00 | 0.00 |
May | 1264.47 | 356.30 | 801.61 | 303.70 | 497.91 | 0.00 | 0.00 |
June | 1503.74 | 230.65 | 843.00 | 324.30 | 518.70 | 0.00 | 0.00 |
July | 1470.20 | 163.01 | 795.14 | 294.81 | 500.33 | 0.00 | 0.00 |
August | 1455.19 | 138.12 | 779.13 | 291.36 | 487.76 | 0.00 | 0.00 |
September | 1031.75 | 291.19 | 634.78 | 264.41 | 370.36 | 0.00 | 0.00 |
October | 778.76 | 599.23 | 565.51 | 293.56 | 271.95 | 0.00 | 0.00 |
November | 516.96 | 793.83 | 451.32 | 202.57 | 248.74 | 0.00 | 0.00 |
December | 324.58 | 979.60 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Annual Sum or Average | 937.44 | 569.48 | 638.25 | 272.24 | 366.02 | 0.00 | 0.00 |
Minimum of Months | 324.58 | 138.12 | 372.33 | 162.86 | 209.47 | 0.00 | 0.00 |
Maximum of Months | 1503.74 | 1162.35 | 843.00 | 364.98 | 518.70 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127869E+09 | 0.475602E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.349499E+09 | 0.351234E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.859428E+09 | 0.243284E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.154647E+10 | 0.189246E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.238488E+10 | 0.128368E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.328050E+10 | 0.792351E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.338298E+10 | 0.593407E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.308766E+10 | 0.492921E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.173468E+10 | 0.103639E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.841765E+09 | 0.221900E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.469242E+09 | 0.290440E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.141792E+09 | 0.381339E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182068E+11 | 0.257292E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.127869E+09 | 0.492921E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.338298E+10 | 0.475602E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.798648E+09 | 0.283480E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.124175E+10 | 0.210962E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.201523E+10 | 0.149924E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.283253E+10 | 0.119409E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.354614E+10 | 0.846588E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.404468E+10 | 0.528673E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.420974E+10 | 0.396840E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.391915E+10 | 0.327314E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.272139E+10 | 0.667067E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.195378E+10 | 0.138026E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.120930E+10 | 0.174659E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.821836E+09 | 0.227079E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293142E+11 | 0.158019E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.798648E+09 | 0.327314E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420974E+10 | 0.283480E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460197E+10 | 0.399932E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.421562E+10 | 0.311062E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.455276E+10 | 0.238940E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.366115E+10 | 0.195924E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.322016E+10 | 0.136134E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.342986E+10 | 0.842092E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.376224E+10 | 0.617279E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.457140E+10 | 0.516306E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.415500E+10 | 0.106854E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.537990E+10 | 0.217802E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.507002E+10 | 0.269809E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.484353E+10 | 0.335480E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514636E+11 | 0.240951E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322016E+10 | 0.516306E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.537990E+10 | 0.399932E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.917409E+09 | 0.294846E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.122606E+10 | 0.223492E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.240553E+10 | 0.161442E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.299034E+10 | 0.129405E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.338943E+10 | 0.914999E+09 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.388674E+10 | 0.578811E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.392409E+10 | 0.424395E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.388451E+10 | 0.359296E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.268547E+10 | 0.705669E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.210877E+10 | 0.148717E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.137626E+10 | 0.190308E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.892388E+09 | 0.243380E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296870E+11 | 0.168991E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.892388E+09 | 0.359296E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.392409E+10 | 0.294846E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121469E+09 | 0.498583E+10 | 0.746261E+09 | 0.00 | 0.746261E+09 | 0.00 | 0.00 |
February | 0.360344E+09 | 0.362473E+10 | 0.747110E+09 | 0.00 | 0.747110E+09 | 0.00 | 0.00 |
March | 0.925419E+09 | 0.242945E+10 | 0.116128E+10 | 0.00 | 0.116128E+10 | 0.00 | 0.00 |
April | 0.166911E+10 | 0.180765E+10 | 0.135937E+10 | 6029144.79 | 0.135334E+10 | 0.00 | 0.00 |
May | 0.249375E+10 | 0.121732E+10 | 0.167998E+10 | 53615172.89 | 0.162636E+10 | 0.00 | 0.00 |
June | 0.334824E+10 | 0.766840E+09 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
July | 0.344638E+10 | 0.573624E+09 | 0.174443E+10 | 84797223.43 | 0.165963E+10 | 0.00 | 0.00 |
August | 0.312605E+10 | 0.489313E+09 | 0.155138E+10 | 16899738.46 | 0.153448E+10 | 0.00 | 0.00 |
September | 0.171709E+10 | 0.114029E+10 | 0.113487E+10 | 159756.68 | 0.113471E+10 | 0.00 | 0.00 |
October | 0.789500E+09 | 0.249533E+10 | 0.891642E+09 | 0.00 | 0.891642E+09 | 0.00 | 0.00 |
November | 0.400016E+09 | 0.326067E+10 | 0.772246E+09 | 0.00 | 0.772246E+09 | 0.00 | 0.00 |
December | 0.124386E+09 | 0.420240E+10 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185217E+11 | 0.269934E+11 | 0.142677E+11 | 0.279633E+09 | 0.139880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121469E+09 | 0.489313E+09 | 0.689863E+09 | 0.00 | 0.689863E+09 | 0.00 | 0.00 |
Maximum of Months | 0.344638E+10 | 0.498583E+10 | 0.178925E+10 | 0.118131E+09 | 0.167111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785059E+09 | 0.299893E+10 | 0.109260E+10 | 0.492815E+09 | 0.599783E+09 | 0.00 | 0.00 |
February | 0.124656E+10 | 0.220750E+10 | 0.124412E+10 | 0.668456E+09 | 0.575668E+09 | 0.00 | 0.00 |
March | 0.205319E+10 | 0.154089E+10 | 0.173296E+10 | 0.788890E+09 | 0.944068E+09 | 0.00 | 0.00 |
April | 0.289897E+10 | 0.118173E+10 | 0.202799E+10 | 0.924709E+09 | 0.110329E+10 | 0.00 | 0.00 |
May | 0.361126E+10 | 0.834367E+09 | 0.230112E+10 | 0.973106E+09 | 0.132801E+10 | 0.00 | 0.00 |
June | 0.408844E+10 | 0.531849E+09 | 0.230558E+10 | 0.966321E+09 | 0.133926E+10 | 0.00 | 0.00 |
July | 0.424859E+10 | 0.404343E+09 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
August | 0.394499E+10 | 0.345159E+09 | 0.212475E+10 | 0.842959E+09 | 0.128179E+10 | 0.00 | 0.00 |
September | 0.270890E+10 | 0.754939E+09 | 0.168992E+10 | 0.748757E+09 | 0.941164E+09 | 0.00 | 0.00 |
October | 0.191006E+10 | 0.157780E+10 | 0.148970E+10 | 0.775125E+09 | 0.714577E+09 | 0.00 | 0.00 |
November | 0.113193E+10 | 0.199758E+10 | 0.115261E+10 | 0.521895E+09 | 0.630714E+09 | 0.00 | 0.00 |
December | 0.785597E+09 | 0.253323E+10 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.294135E+11 | 0.169083E+11 | 0.205160E+11 | 0.914990E+10 | 0.113661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.785059E+09 | 0.345159E+09 | 0.103166E+10 | 0.470269E+09 | 0.561391E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424859E+10 | 0.299893E+10 | 0.232297E+10 | 0.976604E+09 | 0.134636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.464217E+10 | 0.427564E+10 | 0.399103E+10 | 0.278252E+10 | 0.120850E+10 | 0.00 | 0.00 |
February | 0.427123E+10 | 0.328806E+10 | 0.336449E+10 | 0.225530E+10 | 0.110919E+10 | 0.00 | 0.00 |
March | 0.465193E+10 | 0.247413E+10 | 0.335001E+10 | 0.174582E+10 | 0.160419E+10 | 0.00 | 0.00 |
April | 0.378963E+10 | 0.191242E+10 | 0.242801E+10 | 0.790362E+09 | 0.163765E+10 | 0.00 | 0.00 |
May | 0.333662E+10 | 0.129831E+10 | 0.202713E+10 | 0.235605E+09 | 0.179152E+10 | 0.00 | 0.00 |
June | 0.350220E+10 | 0.816384E+09 | 0.181384E+10 | 0.100932E+09 | 0.171290E+10 | 0.00 | 0.00 |
July | 0.382410E+10 | 0.602651E+09 | 0.189488E+10 | 0.141291E+09 | 0.175358E+10 | 0.00 | 0.00 |
August | 0.460537E+10 | 0.532088E+09 | 0.226234E+10 | 0.422609E+09 | 0.183973E+10 | 0.00 | 0.00 |
September | 0.415027E+10 | 0.119149E+10 | 0.240775E+10 | 0.895553E+09 | 0.151220E+10 | 0.00 | 0.00 |
October | 0.535969E+10 | 0.249136E+10 | 0.360690E+10 | 0.233654E+10 | 0.127035E+10 | 0.00 | 0.00 |
November | 0.500998E+10 | 0.310285E+10 | 0.375519E+10 | 0.249188E+10 | 0.126332E+10 | 0.00 | 0.00 |
December | 0.482489E+10 | 0.377552E+10 | 0.393405E+10 | 0.276763E+10 | 0.116642E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.519681E+11 | 0.257609E+11 | 0.348356E+11 | 0.169660E+11 | 0.178696E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333662E+10 | 0.532088E+09 | 0.181384E+10 | 0.100932E+09 | 0.110919E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535969E+10 | 0.427564E+10 | 0.399103E+10 | 0.278252E+10 | 0.183973E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.920701E+09 | 0.312148E+10 | 0.112225E+10 | 0.520578E+09 | 0.601675E+09 | 0.00 | 0.00 |
February | 0.124348E+10 | 0.233636E+10 | 0.116366E+10 | 0.544080E+09 | 0.619581E+09 | 0.00 | 0.00 |
March | 0.244983E+10 | 0.166959E+10 | 0.189894E+10 | 0.917606E+09 | 0.981330E+09 | 0.00 | 0.00 |
April | 0.305655E+10 | 0.129258E+10 | 0.206736E+10 | 0.946011E+09 | 0.112135E+10 | 0.00 | 0.00 |
May | 0.344473E+10 | 0.909705E+09 | 0.214702E+10 | 0.813416E+09 | 0.133360E+10 | 0.00 | 0.00 |
June | 0.392887E+10 | 0.587516E+09 | 0.218503E+10 | 0.840569E+09 | 0.134446E+10 | 0.00 | 0.00 |
July | 0.395713E+10 | 0.434019E+09 | 0.212969E+10 | 0.789612E+09 | 0.134007E+10 | 0.00 | 0.00 |
August | 0.390526E+10 | 0.381140E+09 | 0.208679E+10 | 0.780373E+09 | 0.130642E+10 | 0.00 | 0.00 |
September | 0.266679E+10 | 0.802283E+09 | 0.164532E+10 | 0.685344E+09 | 0.959973E+09 | 0.00 | 0.00 |
October | 0.207388E+10 | 0.170674E+10 | 0.151464E+10 | 0.786263E+09 | 0.728379E+09 | 0.00 | 0.00 |
November | 0.132436E+10 | 0.216779E+10 | 0.116980E+10 | 0.525065E+09 | 0.644736E+09 | 0.00 | 0.00 |
December | 0.874060E+09 | 0.270345E+10 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298457E+11 | 0.181126E+11 | 0.201277E+11 | 0.858511E+10 | 0.115426E+11 | 0.00 | 0.00 |
Minimum of Months | 0.874060E+09 | 0.381140E+09 | 0.997247E+09 | 0.436196E+09 | 0.561051E+09 | 0.00 | 0.00 |
Maximum of Months | 0.395713E+10 | 0.312148E+10 | 0.218503E+10 | 0.946011E+09 | 0.134446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114555E+09 | 0.501726E+10 | 0.746277E+09 | 0.00 | 0.746277E+09 | 0.00 | 0.00 |
February | 0.331984E+09 | 0.371139E+10 | 0.747125E+09 | 0.00 | 0.747125E+09 | 0.00 | 0.00 |
March | 0.823184E+09 | 0.260278E+10 | 0.116131E+10 | 0.00 | 0.116131E+10 | 0.00 | 0.00 |
April | 0.152487E+10 | 0.199445E+10 | 0.135940E+10 | 6029322.01 | 0.135337E+10 | 0.00 | 0.00 |
May | 0.238038E+10 | 0.133586E+10 | 0.168001E+10 | 53616748.83 | 0.162639E+10 | 0.00 | 0.00 |
June | 0.329470E+10 | 0.812640E+09 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
July | 0.340685E+10 | 0.605322E+09 | 0.174447E+10 | 84799715.93 | 0.165967E+10 | 0.00 | 0.00 |
August | 0.310855E+10 | 0.505333E+09 | 0.155141E+10 | 16900235.20 | 0.153451E+10 | 0.00 | 0.00 |
September | 0.172172E+10 | 0.110872E+10 | 0.113489E+10 | 159761.37 | 0.113473E+10 | 0.00 | 0.00 |
October | 0.802413E+09 | 0.240658E+10 | 0.891659E+09 | 0.00 | 0.891659E+09 | 0.00 | 0.00 |
November | 0.416230E+09 | 0.315488E+10 | 0.772262E+09 | 0.00 | 0.772262E+09 | 0.00 | 0.00 |
December | 0.122529E+09 | 0.412004E+10 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180480E+11 | 0.273753E+11 | 0.142680E+11 | 0.279641E+09 | 0.139883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.114555E+09 | 0.505333E+09 | 0.689877E+09 | 0.00 | 0.689877E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340685E+10 | 0.501726E+10 | 0.178928E+10 | 0.118135E+09 | 0.167115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770966E+09 | 0.299152E+10 | 0.109261E+10 | 0.492825E+09 | 0.599790E+09 | 0.00 | 0.00 |
February | 0.121709E+10 | 0.222722E+10 | 0.124414E+10 | 0.668469E+09 | 0.575674E+09 | 0.00 | 0.00 |
March | 0.198568E+10 | 0.159174E+10 | 0.173298E+10 | 0.788905E+09 | 0.944080E+09 | 0.00 | 0.00 |
April | 0.281999E+10 | 0.124778E+10 | 0.202802E+10 | 0.924727E+09 | 0.110330E+10 | 0.00 | 0.00 |
May | 0.354802E+10 | 0.874360E+09 | 0.230115E+10 | 0.973125E+09 | 0.132803E+10 | 0.00 | 0.00 |
June | 0.405806E+10 | 0.540145E+09 | 0.230561E+10 | 0.966340E+09 | 0.133927E+10 | 0.00 | 0.00 |
July | 0.422875E+10 | 0.404469E+09 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
August | 0.393665E+10 | 0.334989E+09 | 0.212478E+10 | 0.842976E+09 | 0.128180E+10 | 0.00 | 0.00 |
September | 0.271554E+10 | 0.708018E+09 | 0.168995E+10 | 0.748772E+09 | 0.941176E+09 | 0.00 | 0.00 |
October | 0.192479E+10 | 0.148041E+10 | 0.148972E+10 | 0.775140E+09 | 0.714585E+09 | 0.00 | 0.00 |
November | 0.115764E+10 | 0.188550E+10 | 0.115263E+10 | 0.521905E+09 | 0.630721E+09 | 0.00 | 0.00 |
December | 0.787386E+09 | 0.244935E+10 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.291506E+11 | 0.167355E+11 | 0.205163E+11 | 0.915008E+10 | 0.113662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.770966E+09 | 0.334989E+09 | 0.103168E+10 | 0.470278E+09 | 0.561398E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422875E+10 | 0.299152E+10 | 0.232300E+10 | 0.976623E+09 | 0.134638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454168E+10 | 0.423050E+10 | 0.399118E+10 | 0.278264E+10 | 0.120854E+10 | 0.00 | 0.00 |
February | 0.417655E+10 | 0.329259E+10 | 0.336461E+10 | 0.225539E+10 | 0.110922E+10 | 0.00 | 0.00 |
March | 0.451697E+10 | 0.254395E+10 | 0.335013E+10 | 0.174589E+10 | 0.160424E+10 | 0.00 | 0.00 |
April | 0.364613E+10 | 0.205927E+10 | 0.242809E+10 | 0.790395E+09 | 0.163769E+10 | 0.00 | 0.00 |
May | 0.322222E+10 | 0.141763E+10 | 0.202719E+10 | 0.235614E+09 | 0.179158E+10 | 0.00 | 0.00 |
June | 0.344732E+10 | 0.867672E+09 | 0.181389E+10 | 0.100936E+09 | 0.171295E+10 | 0.00 | 0.00 |
July | 0.378755E+10 | 0.632784E+09 | 0.189493E+10 | 0.141297E+09 | 0.175364E+10 | 0.00 | 0.00 |
August | 0.459579E+10 | 0.530357E+09 | 0.226241E+10 | 0.422627E+09 | 0.183979E+10 | 0.00 | 0.00 |
September | 0.414851E+10 | 0.113665E+10 | 0.240784E+10 | 0.895590E+09 | 0.151225E+10 | 0.00 | 0.00 |
October | 0.534658E+10 | 0.233978E+10 | 0.360703E+10 | 0.233664E+10 | 0.127039E+10 | 0.00 | 0.00 |
November | 0.499986E+10 | 0.291424E+10 | 0.375534E+10 | 0.249198E+10 | 0.126336E+10 | 0.00 | 0.00 |
December | 0.477521E+10 | 0.361440E+10 | 0.393420E+10 | 0.276774E+10 | 0.116646E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.512044E+11 | 0.255798E+11 | 0.348369E+11 | 0.169667E+11 | 0.178701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322222E+10 | 0.530357E+09 | 0.181389E+10 | 0.100936E+09 | 0.110922E+10 | 0.00 | 0.00 |
Maximum of Months | 0.534658E+10 | 0.423050E+10 | 0.399118E+10 | 0.278264E+10 | 0.183979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.899932E+09 | 0.311325E+10 | 0.112227E+10 | 0.520587E+09 | 0.601681E+09 | 0.00 | 0.00 |
February | 0.121236E+10 | 0.236211E+10 | 0.116368E+10 | 0.544089E+09 | 0.619587E+09 | 0.00 | 0.00 |
March | 0.238431E+10 | 0.172190E+10 | 0.189896E+10 | 0.917621E+09 | 0.981340E+09 | 0.00 | 0.00 |
April | 0.297716E+10 | 0.136220E+10 | 0.206738E+10 | 0.946027E+09 | 0.112136E+10 | 0.00 | 0.00 |
May | 0.338675E+10 | 0.954316E+09 | 0.214704E+10 | 0.813430E+09 | 0.133361E+10 | 0.00 | 0.00 |
June | 0.389769E+10 | 0.597836E+09 | 0.218506E+10 | 0.840583E+09 | 0.134448E+10 | 0.00 | 0.00 |
July | 0.393777E+10 | 0.436607E+09 | 0.212971E+10 | 0.789625E+09 | 0.134009E+10 | 0.00 | 0.00 |
August | 0.389757E+10 | 0.369948E+09 | 0.208681E+10 | 0.780386E+09 | 0.130643E+10 | 0.00 | 0.00 |
September | 0.267428E+10 | 0.754764E+09 | 0.164534E+10 | 0.685356E+09 | 0.959983E+09 | 0.00 | 0.00 |
October | 0.208582E+10 | 0.160497E+10 | 0.151466E+10 | 0.786276E+09 | 0.728386E+09 | 0.00 | 0.00 |
November | 0.133997E+10 | 0.205761E+10 | 0.116982E+10 | 0.525073E+09 | 0.644742E+09 | 0.00 | 0.00 |
December | 0.869349E+09 | 0.262376E+10 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295630E+11 | 0.179593E+11 | 0.201280E+11 | 0.858525E+10 | 0.115427E+11 | 0.00 | 0.00 |
Minimum of Months | 0.869349E+09 | 0.369948E+09 | 0.997260E+09 | 0.436203E+09 | 0.561057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.393777E+10 | 0.311325E+10 | 0.218506E+10 | 0.946027E+09 | 0.134448E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.461605E+10 | -0.436950E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246552352.4 | 60.05 | 0.00 | 0.00 |
February | 0.419810E+10 | -0.397953E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -218567806.6 | 60.05 | 0.00 | 0.00 |
March | 0.479049E+10 | -0.455481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235686662.0 | 60.05 | 0.00 | 0.00 |
April | 0.406922E+10 | -0.384332E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225901687.6 | 60.05 | 0.00 | 0.00 |
May | 0.403275E+10 | -0.380052E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232232637.2 | 60.05 | 0.00 | 0.00 |
June | 0.370662E+10 | -0.348189E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224724851.1 | 60.05 | 0.00 | 0.00 |
July | 0.334723E+10 | -0.311564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231598649.6 | 60.05 | 0.00 | 0.00 |
August | 0.366740E+10 | -0.343530E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232102115.3 | 60.05 | 0.00 | 0.00 |
September | 0.346332E+10 | -0.323908E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224231818.3 | 60.05 | 0.00 | 0.00 |
October | 0.384573E+10 | -0.361240E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233329910.8 | 60.05 | 0.00 | 0.00 |
November | 0.408750E+10 | -0.385962E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227884794.4 | 60.05 | 0.00 | 0.00 |
December | 0.432682E+10 | -0.408649E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -240325207.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.481512E+11 | -0.453781E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277314E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.334723E+10 | -0.455481E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -246552352.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.479049E+10 | -0.311564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -218567806.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5944.13 | 33.56 | 265.83 | 271.50 | 1657.27 | 25.59 | 178.50 | 250.33 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6962.61 | 33.59 | 230.83 | 246.83 | 1109.82 | 19.25 | 74.67 | 210.83 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:50 | 1639.75 | 18.12 | 6.83 | 317.83 | 961.50 | 20.22 | 124.00 | 283.00 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:39 | 1350.13 | 17.76 | 0.00 | 324.17 | 773.30 | 19.91 | 104.50 | 280.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1220.07 | 17.94 | 0.00 | 358.50 | 683.84 | 20.09 | 89.67 | 310.67 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1133.53 | 17.68 | 0.00 | 358.67 | 641.54 | 19.85 | 91.67 | 311.00 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1195.26 | 17.85 | 0.00 | 362.50 | 668.51 | 19.99 | 118.50 | 312.83 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1461.06 | 18.48 | 0.00 | 349.33 | 801.51 | 20.60 | 174.83 | 311.50 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:40 | 1564.17 | 18.59 | 6.50 | 307.83 | 880.51 | 20.47 | 122.67 | 268.33 |
October | 293.50 | 0.51 | 0.48 | 01-OCT-10:39 | 2832.02 | 23.85 | 119.33 | 291.83 | 1070.85 | 19.63 | 83.17 | 255.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5850.38 | 34.50 | 285.50 | 272.83 | 1203.10 | 24.25 | 167.17 | 252.83 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5602.08 | 34.35 | 269.83 | 267.67 | 1598.52 | 26.54 | 179.50 | 245.17 |
Annual Sum or Average | 4071.00 | 0.52 | 2776.74 | 22.92 | 1184.67 | 3729.50 | 962.96 | 21.19 | 1508.83 | 3292.00 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1133.53 | 17.68 | 0.00 | 246.83 | 641.54 | 19.25 | 74.67 | 210.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6962.61 | 34.50 | 285.50 | 362.50 | 1657.27 | 26.54 | 179.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:09 | 1403.14 | 19.13 | 71.83 | 240.83 | 715.25 | 19.99 | 55.33 | 179.00 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1863.36 | 18.94 | 60.17 | 222.67 | 1030.30 | 21.08 | 50.00 | 177.17 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2242.56 | 20.56 | 105.50 | 309.83 | 881.09 | 20.10 | 47.50 | 267.33 |
April | 369.33 | 0.52 | 0.48 | 01-APR-08:09 | 2159.60 | 19.96 | 93.33 | 325.00 | 1163.95 | 21.19 | 67.17 | 287.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:10 | 2462.38 | 20.32 | 108.50 | 366.67 | 1018.16 | 20.21 | 50.17 | 327.67 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2486.06 | 20.25 | 110.67 | 368.50 | 1042.13 | 20.91 | 64.00 | 332.50 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2460.73 | 20.28 | 105.50 | 371.83 | 1042.79 | 20.29 | 51.83 | 330.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2255.62 | 20.63 | 102.17 | 350.83 | 1190.30 | 21.92 | 73.50 | 313.33 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2082.99 | 19.39 | 67.33 | 303.17 | 1122.96 | 21.64 | 55.33 | 259.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-08:20 | 2490.79 | 20.88 | 90.83 | 267.17 | 929.04 | 19.93 | 43.83 | 214.83 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1701.57 | 21.17 | 97.00 | 246.83 | 918.85 | 22.00 | 75.50 | 200.83 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-07:49 | 1440.43 | 19.73 | 73.33 | 236.67 | 771.34 | 21.42 | 60.17 | 177.50 |
Annual Sum or Average | 4071.00 | 0.53 | 2130.75 | 20.15 | 1086.17 | 3610.00 | 996.80 | 20.87 | 694.33 | 3067.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1403.14 | 18.94 | 60.17 | 222.67 | 715.25 | 19.93 | 43.83 | 177.17 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2490.79 | 21.17 | 110.67 | 371.83 | 1190.30 | 22.00 | 75.50 | 332.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.59 | 0.48 | 01-JAN-11:20 | 500.43 | 14.35 | 0.00 | 211.33 | 302.57 | 16.75 | 0.00 | 89.17 |
February | 263.00 | 0.59 | 0.48 | 01-FEB-13:50 | 531.48 | 14.55 | 0.00 | 190.50 | 330.34 | 16.90 | 0.00 | 111.67 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-09:30 | 678.09 | 16.37 | 0.00 | 299.67 | 413.74 | 18.58 | 0.00 | 226.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:30 | 809.95 | 17.28 | 0.00 | 328.17 | 485.58 | 19.39 | 0.67 | 271.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1012.67 | 20.33 | 51.83 | 382.67 | 584.27 | 20.48 | 66.67 | 342.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1101.66 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:10 | 1110.01 | 20.48 | 53.33 | 384.83 | 617.52 | 21.45 | 145.83 | 348.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 990.02 | 18.23 | 0.00 | 359.33 | 578.27 | 20.31 | 54.67 | 324.83 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 752.92 | 17.08 | 0.00 | 302.50 | 456.60 | 19.19 | 0.00 | 219.83 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 556.20 | 15.08 | 0.00 | 237.00 | 355.94 | 17.47 | 0.00 | 143.83 |
November | 299.00 | 0.58 | 0.48 | 01-NOV-09:00 | 517.80 | 14.66 | 0.00 | 224.67 | 315.06 | 17.00 | 0.00 | 121.50 |
December | 285.17 | 0.59 | 0.48 | 01-DEC-10:20 | 483.52 | 14.43 | 0.00 | 203.50 | 293.36 | 16.87 | 0.00 | 82.83 |
Annual Sum or Average | 4071.00 | 0.54 | 789.00 | 17.35 | 172.00 | 3510.00 | 467.36 | 19.24 | 445.83 | 2646.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 483.52 | 14.35 | 0.00 | 190.50 | 293.36 | 16.75 | 0.00 | 82.83 | |
Maximum of Months | 411.67 | 0.59 | 0.48 | 1110.01 | 21.05 | 66.83 | 385.83 | 648.41 | 23.06 | 178.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.54 | 0.48 | 01-JAN-10:00 | 1724.54 | 21.14 | 89.83 | 243.83 | 955.65 | 21.84 | 68.00 | 191.33 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1648.22 | 18.89 | 64.00 | 214.33 | 856.95 | 19.72 | 40.33 | 165.33 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2222.20 | 20.89 | 98.17 | 309.33 | 1182.08 | 21.80 | 72.00 | 266.50 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2368.78 | 18.68 | 78.67 | 330.67 | 1304.67 | 20.04 | 51.83 | 288.67 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:30 | 2368.37 | 17.04 | 50.83 | 364.67 | 1008.52 | 18.03 | 0.00 | 325.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2490.05 | 14.72 | 1.67 | 367.50 | 1066.09 | 17.98 | 0.00 | 330.83 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-08:09 | 2471.35 | 17.03 | 52.17 | 367.50 | 1043.28 | 18.02 | 0.00 | 328.00 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:00 | 2423.28 | 19.52 | 89.00 | 352.67 | 1057.45 | 18.72 | 7.67 | 319.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2175.17 | 21.47 | 90.83 | 305.00 | 1149.50 | 22.24 | 62.67 | 256.67 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2351.32 | 20.91 | 92.67 | 262.50 | 902.70 | 19.99 | 42.83 | 210.33 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1596.56 | 19.48 | 80.83 | 248.50 | 857.86 | 21.75 | 68.67 | 200.00 |
December | 285.17 | 0.54 | 0.48 | 01-DEC-10:09 | 1393.57 | 19.37 | 74.17 | 236.50 | 757.14 | 21.35 | 63.33 | 177.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2150.89 | 18.88 | 862.83 | 3603.00 | 1024.87 | 19.93 | 477.33 | 3060.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1393.57 | 14.72 | 1.67 | 214.33 | 757.14 | 17.98 | 0.00 | 165.33 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2490.05 | 21.47 | 98.17 | 367.50 | 1304.67 | 22.24 | 72.00 | 330.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.08 | 33.12 | 258.17 | 269.83 | 1561.52 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.73 | 33.22 | 229.67 | 245.83 | 1060.06 | 18.04 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.16 | 14.23 | 6.67 | 314.67 | 896.80 | 17.63 | 0.50 | 278.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.89 | 14.01 | 0.00 | 321.83 | 731.87 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.51 | 14.26 | 0.00 | 355.83 | 654.37 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.09 | 14.07 | 0.00 | 356.33 | 616.22 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.36 | 14.24 | 0.00 | 359.33 | 640.70 | 17.67 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.63 | 14.86 | 0.00 | 347.33 | 762.74 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.14 | 14.98 | 6.50 | 305.00 | 828.73 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.91 | 21.24 | 117.33 | 290.33 | 988.09 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.91 | 34.09 | 281.17 | 271.67 | 1115.61 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.53 | 32.30 | 249.50 | 263.83 | 1501.05 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.29 | 20.12 | 1149.00 | 3701.83 | 908.51 | 18.87 | 330.17 | 3259.00 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.09 | 14.01 | 0.00 | 245.83 | 616.22 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.73 | 34.09 | 281.17 | 359.33 | 1561.52 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.77 | 18.62 | 71.50 | 239.00 | 684.67 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.50 | 18.44 | 60.17 | 219.33 | 989.09 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.30 | 20.09 | 105.33 | 308.00 | 839.46 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.61 | 19.49 | 93.00 | 322.67 | 1115.83 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.36 | 19.87 | 108.33 | 364.00 | 967.49 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.72 | 19.80 | 110.33 | 366.00 | 992.13 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.59 | 19.83 | 105.33 | 369.00 | 991.41 | 20.11 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.22 | 20.17 | 102.17 | 349.17 | 1140.60 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.73 | 18.89 | 67.33 | 301.33 | 1074.78 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.85 | 20.40 | 90.50 | 265.00 | 884.47 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.27 | 20.71 | 97.00 | 244.33 | 885.48 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.26 | 19.22 | 73.00 | 234.17 | 739.07 | 21.18 | 57.50 | 173.33 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.27 | 19.67 | 1084.00 | 3582.00 | 952.46 | 20.68 | 679.50 | 3015.67 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.77 | 18.44 | 60.17 | 219.33 | 684.67 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.85 | 20.71 | 110.33 | 369.00 | 1140.60 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.96 | 10.47 | 0.00 | 206.50 | 293.15 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.49 | 10.78 | 0.00 | 185.33 | 320.90 | 14.47 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.86 | 12.86 | 0.00 | 296.67 | 401.31 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.39 | 13.81 | 0.00 | 325.67 | 470.58 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.23 | 17.28 | 51.83 | 380.33 | 573.88 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.26 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.85 | 16.16 | 27.33 | 383.17 | 604.40 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.90 | 14.80 | 0.00 | 357.83 | 557.88 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.98 | 13.77 | 0.00 | 299.67 | 441.99 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.67 | 11.52 | 0.00 | 231.00 | 346.46 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.26 | 10.90 | 0.00 | 219.33 | 305.08 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.99 | 10.51 | 0.00 | 198.00 | 283.90 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.54 | 13.79 | 144.83 | 3468.17 | 453.78 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.99 | 10.47 | 0.00 | 185.33 | 283.90 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.85 | 18.08 | 65.67 | 384.67 | 624.76 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.62 | 20.74 | 89.33 | 240.83 | 922.67 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.52 | 18.47 | 64.00 | 211.67 | 817.05 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.20 | 18.82 | 77.50 | 306.83 | 1133.94 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.77 | 18.21 | 78.50 | 327.83 | 1256.61 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.27 | 16.53 | 50.83 | 361.83 | 961.70 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.94 | 14.17 | 1.67 | 364.17 | 1018.49 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.26 | 16.52 | 52.00 | 365.33 | 995.72 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.84 | 18.89 | 86.50 | 351.17 | 1000.66 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.15 | 19.40 | 75.50 | 301.17 | 1102.03 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.89 | 20.49 | 92.50 | 260.67 | 859.80 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.04 | 19.05 | 80.83 | 245.83 | 823.42 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.65 | 18.95 | 73.83 | 233.83 | 726.36 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.55 | 18.14 | 823.00 | 3571.17 | 980.42 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.65 | 14.17 | 1.67 | 211.67 | 726.36 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.94 | 20.74 | 92.50 | 365.33 | 1256.61 | 22.11 | 72.17 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.51 | 0.48 | 01-JAN-09:20 | 5823.03 | 33.12 | 258.17 | 269.83 | 1561.45 | 23.29 | 103.33 | 249.00 |
February | 263.00 | 0.52 | 0.48 | 01-FEB-13:39 | 6853.66 | 33.22 | 229.67 | 245.83 | 1059.99 | 18.05 | 25.83 | 214.17 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 1553.07 | 14.23 | 6.67 | 314.67 | 896.74 | 17.63 | 0.50 | 278.67 |
April | 369.33 | 0.53 | 0.48 | 01-APR-09:50 | 1289.81 | 14.01 | 0.00 | 321.83 | 731.82 | 17.52 | 0.00 | 277.33 |
May | 407.00 | 0.53 | 0.48 | 01-MAY-07:49 | 1172.44 | 14.26 | 0.00 | 355.83 | 654.32 | 17.73 | 0.00 | 307.83 |
June | 411.67 | 0.53 | 0.48 | 01-JUN-07:19 | 1091.03 | 14.07 | 0.00 | 356.33 | 616.17 | 17.53 | 0.00 | 306.83 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-07:49 | 1149.30 | 14.24 | 0.00 | 359.33 | 640.65 | 17.68 | 0.00 | 308.33 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1400.54 | 14.86 | 0.00 | 347.33 | 762.68 | 18.28 | 0.00 | 307.17 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:49 | 1490.05 | 14.99 | 6.50 | 305.00 | 828.67 | 18.12 | 0.00 | 265.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2727.84 | 21.24 | 117.33 | 290.33 | 988.03 | 16.85 | 2.17 | 251.33 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:30 | 5736.86 | 34.09 | 281.17 | 271.67 | 1115.53 | 21.76 | 82.17 | 249.67 |
December | 285.17 | 0.51 | 0.48 | 01-DEC-07:00 | 5429.50 | 32.30 | 249.50 | 263.83 | 1500.98 | 24.34 | 116.17 | 243.00 |
Annual Sum or Average | 4071.00 | 0.52 | 2695.22 | 20.12 | 1149.00 | 3701.83 | 908.45 | 18.87 | 330.17 | 3258.83 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1091.03 | 14.01 | 0.00 | 245.83 | 616.17 | 16.85 | 0.00 | 214.17 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 6853.66 | 34.09 | 281.17 | 359.33 | 1561.45 | 24.34 | 116.17 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-09:20 | 1363.74 | 18.63 | 71.50 | 239.00 | 684.64 | 19.74 | 48.67 | 172.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 1813.48 | 18.44 | 60.17 | 219.33 | 989.06 | 20.87 | 48.50 | 174.00 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-08:39 | 2191.27 | 20.09 | 105.33 | 308.00 | 839.42 | 19.89 | 47.33 | 262.83 |
April | 369.33 | 0.53 | 0.48 | 01-APR-08:09 | 2098.57 | 19.50 | 93.00 | 322.67 | 1115.78 | 21.00 | 67.17 | 283.50 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2391.30 | 19.87 | 108.33 | 364.00 | 967.43 | 20.04 | 50.17 | 323.50 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-06:30 | 2421.66 | 19.80 | 110.33 | 366.00 | 992.07 | 20.75 | 64.00 | 329.00 |
July | 411.00 | 0.52 | 0.48 | 01-JUL-05:00 | 2392.53 | 19.84 | 105.33 | 369.00 | 991.34 | 20.12 | 51.83 | 328.17 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-06:40 | 2184.16 | 20.18 | 102.17 | 349.17 | 1140.53 | 21.75 | 73.50 | 309.67 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-07:10 | 2023.69 | 18.90 | 67.33 | 301.33 | 1074.73 | 21.45 | 55.33 | 253.33 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 2436.83 | 20.40 | 90.50 | 265.00 | 884.43 | 19.72 | 42.67 | 210.00 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-08:20 | 1659.24 | 20.71 | 97.00 | 244.33 | 885.44 | 21.78 | 72.83 | 195.83 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-07:49 | 1400.23 | 19.22 | 73.00 | 234.17 | 739.04 | 21.18 | 57.50 | 173.17 |
Annual Sum or Average | 4071.00 | 0.53 | 2073.23 | 19.67 | 1084.00 | 3582.00 | 952.41 | 20.68 | 679.50 | 3015.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1363.74 | 18.44 | 60.17 | 219.33 | 684.64 | 19.72 | 42.67 | 172.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 2436.83 | 20.71 | 110.33 | 369.00 | 1140.53 | 21.78 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.60 | 0.48 | 01-JAN-11:30 | 482.94 | 10.47 | 0.00 | 206.50 | 293.13 | 14.20 | 0.00 | 79.67 |
February | 263.00 | 0.60 | 0.48 | 01-FEB-13:00 | 513.48 | 10.78 | 0.00 | 185.33 | 320.88 | 14.48 | 0.00 | 106.83 |
March | 351.67 | 0.54 | 0.48 | 01-MAR-12:20 | 654.84 | 12.86 | 0.00 | 296.67 | 401.28 | 16.43 | 0.00 | 220.17 |
April | 369.33 | 0.53 | 0.48 | 01-APR-10:39 | 782.36 | 13.81 | 0.00 | 325.67 | 470.55 | 17.33 | 0.00 | 266.50 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:49 | 976.19 | 17.28 | 51.83 | 380.33 | 573.84 | 20.45 | 52.50 | 348.50 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:49 | 1061.22 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1065.80 | 16.16 | 27.33 | 383.17 | 604.36 | 20.59 | 54.00 | 350.83 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 953.87 | 14.80 | 0.00 | 357.83 | 557.84 | 18.26 | 0.00 | 320.67 |
September | 298.50 | 0.54 | 0.48 | 01-SEP-07:00 | 725.96 | 13.78 | 0.00 | 299.67 | 441.96 | 17.24 | 0.00 | 210.33 |
October | 293.50 | 0.58 | 0.48 | 01-OCT-10:50 | 537.66 | 11.52 | 0.00 | 231.00 | 346.44 | 15.26 | 0.00 | 136.67 |
November | 299.00 | 0.59 | 0.48 | 01-NOV-10:09 | 499.24 | 10.90 | 0.00 | 219.33 | 305.06 | 14.56 | 0.00 | 110.00 |
December | 285.17 | 0.60 | 0.48 | 01-DEC-10:20 | 465.98 | 10.51 | 0.00 | 198.00 | 283.88 | 14.30 | 0.00 | 70.17 |
Annual Sum or Average | 4071.00 | 0.54 | 760.51 | 13.79 | 144.83 | 3468.17 | 453.75 | 17.40 | 174.67 | 2581.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 465.98 | 10.47 | 0.00 | 185.33 | 283.88 | 14.20 | 0.00 | 70.17 | |
Maximum of Months | 411.67 | 0.60 | 0.48 | 1065.80 | 18.08 | 65.67 | 384.67 | 624.72 | 21.23 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 1682.59 | 20.74 | 89.33 | 240.83 | 922.63 | 21.73 | 68.00 | 186.83 |
February | 263.00 | 0.56 | 0.48 | 01-FEB-13:39 | 1597.50 | 18.47 | 64.00 | 211.67 | 817.01 | 19.59 | 40.00 | 162.83 |
March | 351.67 | 0.53 | 0.48 | 01-MAR-11:50 | 2096.16 | 18.82 | 77.50 | 306.83 | 1133.89 | 21.68 | 72.17 | 263.17 |
April | 369.33 | 0.52 | 0.48 | 01-APR-10:39 | 2307.72 | 18.21 | 78.50 | 327.83 | 1256.56 | 19.87 | 51.83 | 285.83 |
May | 407.00 | 0.52 | 0.48 | 01-MAY-08:39 | 2300.21 | 16.54 | 50.83 | 361.83 | 961.64 | 17.84 | 0.00 | 322.83 |
June | 411.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2402.88 | 14.17 | 1.67 | 364.17 | 1018.43 | 17.79 | 0.00 | 328.17 |
July | 411.00 | 0.53 | 0.48 | 01-JUL-08:20 | 2386.20 | 16.52 | 52.00 | 365.33 | 995.66 | 17.82 | 0.00 | 324.50 |
August | 390.50 | 0.52 | 0.48 | 01-AUG-08:09 | 2349.78 | 18.89 | 86.50 | 351.17 | 1000.60 | 18.55 | 7.83 | 314.00 |
September | 298.50 | 0.53 | 0.48 | 01-SEP-08:00 | 2071.10 | 19.40 | 75.50 | 301.17 | 1101.97 | 22.11 | 62.67 | 252.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:50 | 2298.87 | 20.49 | 92.50 | 260.67 | 859.76 | 19.86 | 42.83 | 206.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:00 | 1552.01 | 19.05 | 80.83 | 245.83 | 823.38 | 21.64 | 68.17 | 196.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-10:09 | 1354.63 | 18.95 | 73.83 | 233.83 | 726.32 | 21.24 | 63.17 | 173.83 |
Annual Sum or Average | 4071.00 | 0.53 | 2079.50 | 18.14 | 823.00 | 3571.17 | 980.37 | 19.78 | 476.67 | 3017.50 | ||
Minimum of Months | 263.00 | 0.52 | 0.48 | 1354.63 | 14.17 | 1.67 | 211.67 | 726.32 | 17.79 | 0.00 | 162.83 | |
Maximum of Months | 411.67 | 0.56 | 0.48 | 2402.88 | 20.74 | 92.50 | 365.33 | 1256.56 | 22.11 | 72.17 | 328.17 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267378E+10 | 10513.89 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119636E+10 | 12434.58 | 03-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9388735.56 | 1404.24 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4130950.64 | 1395.05 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1692628.51 | 540.77 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106870E+09 | 6217.33 | 22-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401187E+09 | 9441.07 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267378E+10 | 12434.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 18296197.28 | 24785.76 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18296197.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18296197.28 | 24785.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447064E+10 | 11132.34 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292560E+10 | 11110.51 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117007E+10 | 11089.38 | 24-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.644478E+09 | 11065.90 | 05-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170531E+09 | 11056.38 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25625123.02 | 8735.16 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23737487.74 | 4934.17 | 29-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540364E+09 | 11144.66 | 04-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107007E+10 | 11084.07 | 06-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188494E+10 | 11083.40 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447064E+10 | 11144.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185737E+10 | 8150.01 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102834E+10 | 8150.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123223E+09 | 7927.55 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19246109.00 | 8150.01 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11414007.98 | 5452.90 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67861852.56 | 8150.01 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.594573E+09 | 8150.01 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185737E+10 | 8150.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.333704E+10 | 9474.90 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195641E+10 | 9479.42 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346892E+09 | 9441.58 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78224836.24 | 9440.25 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11473899.21 | 7877.57 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200631E+09 | 9428.12 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125607E+10 | 9440.30 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333704E+10 | 9479.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197876E+10 | 8236.54 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114564E+10 | 8236.54 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161777E+09 | 7764.59 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28135993.77 | 8236.54 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10827612.36 | 4578.40 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108830E+09 | 8236.54 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747320E+09 | 8236.54 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197876E+10 | 8236.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318480E+10 | 11508.07 | 14-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149789E+10 | 13359.15 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27673371.89 | 2266.78 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19744842.96 | 2928.09 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12537534.70 | 2411.37 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192773E+09 | 7847.12 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618842E+09 | 10562.22 | 18-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.555426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318480E+10 | 13359.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243530E+10 | 24248.82 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110239E+10 | 24248.82 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23871861.42 | 14238.79 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.635726E+09 | 24248.82 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243530E+10 | 24248.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184665E+10 | 12021.48 | 02-JAN-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100062E+10 | 11957.66 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98173930.55 | 11902.99 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21649917.09 | 11853.49 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44669752.34 | 11871.08 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169701E+09 | 11867.29 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733398E+09 | 11936.43 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184665E+10 | 12021.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208874E+10 | 8364.90 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113336E+10 | 8364.90 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126130E+09 | 7891.98 | 18-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16891260.11 | 8364.90 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95177370.30 | 7916.19 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275884E+09 | 8364.90 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103102E+10 | 8364.90 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208874E+10 | 8364.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319077E+10 | 10187.05 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170938E+10 | 10165.48 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175931E+09 | 10095.95 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27823117.20 | 10041.90 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66732171.45 | 10133.09 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420062E+09 | 10120.94 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158894E+10 | 10152.07 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.717964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319077E+10 | 10187.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218140E+10 | 8449.74 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122262E+10 | 8449.74 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175814E+09 | 7773.84 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29319327.04 | 8449.74 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91821814.59 | 7780.27 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367331E+09 | 8449.74 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119242E+10 | 8449.74 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.526072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218140E+10 | 8449.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327926E+10 | 13608.13 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158542E+10 | 15981.62 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86129513.47 | 3734.80 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49591011.19 | 4989.06 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24354287.62 | 4208.21 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298214E+09 | 9547.57 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.768820E+09 | 11272.87 | 18-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327926E+10 | 15981.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.664423E+10 | 35333.63 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351062E+10 | 35333.63 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278172E+09 | 35333.63 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23639670.48 | 29380.39 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176241E+09 | 35333.63 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.872097E+09 | 35333.63 | 01-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376596E+10 | 35333.63 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.664423E+10 | 35333.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332239E+10 | 13528.40 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200477E+10 | 13538.22 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400616E+09 | 13443.59 | 22-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121686E+09 | 13373.65 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4075307.11 | 4221.03 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 385997.02 | 667.35 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.264909E+09 | 13489.21 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661830E+09 | 13461.21 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171249E+10 | 13535.85 | 07-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332239E+10 | 13538.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316465E+10 | 10560.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183897E+10 | 10560.27 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364472E+09 | 10560.27 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75029373.90 | 10560.27 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1010033.63 | 1859.13 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1940894.76 | 2770.62 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293825E+09 | 10560.27 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725171E+09 | 10560.27 | 08-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181632E+10 | 10560.27 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316465E+10 | 10560.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513511E+10 | 11711.43 | 02-JAN-06:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303367E+10 | 11693.62 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.603245E+09 | 11656.60 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145184E+09 | 11626.43 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2018781.80 | 3102.98 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 453198.46 | 800.04 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383405E+09 | 11668.33 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121142E+10 | 11683.55 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302504E+10 | 11696.67 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513511E+10 | 11711.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.348059E+10 | 10652.81 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214208E+10 | 10652.81 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.544964E+09 | 10652.81 | 18-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138934E+09 | 10652.81 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7363497.29 | 3942.04 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3217940.17 | 3722.05 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.383174E+09 | 10652.81 | 26-OCT-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.994404E+09 | 10652.81 | 08-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219352E+10 | 10652.81 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348059E+10 | 10652.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.199769E+10 | 0.123622E+10 | 21197.72 | 19-JAN-20:00 | 11767.82 | 0.00 |
February | 0.00 | 0.00 | 0.496106E+10 | 0.407509E+10 | 31798.74 | 28-FEB-15:10 | 31798.74 | 0.00 |
March | 0.00 | 0.00 | 0.150129E+11 | 0.117247E+11 | 49041.03 | 30-MAR-15:10 | 49041.03 | 0.00 |
April | 0.00 | 0.00 | 0.256881E+11 | 0.210057E+11 | 51582.72 | 17-APR-14:00 | 51582.72 | 0.00 |
May | 0.00 | 0.00 | 0.489629E+11 | 0.372809E+11 | 69929.83 | 30-MAY-15:00 | 56371.92 | 0.00 |
June | 0.00 | 0.00 | 0.735298E+11 | 0.555088E+11 | 80073.10 | 28-JUN-12:05 | 55192.61 | 0.00 |
July | 0.00 | 0.00 | 0.845191E+11 | 0.606759E+11 | 89213.71 | 07-JUL-12:03 | 61213.50 | 0.00 |
August | 0.00 | 0.00 | 0.964149E+11 | 0.676683E+11 | 87345.63 | 17-AUG-12:03 | 59799.51 | 0.00 |
September | 0.00 | 0.00 | 0.618762E+11 | 0.458525E+11 | 85699.53 | 07-SEP-16:00 | 64537.23 | 0.00 |
October | 0.00 | 0.00 | 0.275370E+11 | 0.205354E+11 | 68659.64 | 10-OCT-16:00 | 56896.60 | 0.00 |
November | 0.00 | 0.00 | 0.109438E+11 | 0.833913E+10 | 34671.72 | 02-NOV-14:10 | 28473.82 | 0.00 |
December | 0.00 | 0.00 | 0.396239E+10 | 0.267585E+10 | 31673.59 | 12-DEC-14:00 | 24015.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.455406E+12 | 0.336579E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.199769E+10 | 0.123622E+10 | 21197.72 | 11767.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.964149E+11 | 0.676683E+11 | 89213.71 | 64537.23 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200835E+10 | 0.126820E+10 | 21910.88 | 19-JAN-16:00 | 12529.84 | 0.00 |
February | 0.00 | 0.00 | 0.494226E+10 | 0.406288E+10 | 26376.06 | 28-FEB-15:30 | 26376.06 | 0.00 |
March | 0.00 | 0.00 | 0.142263E+11 | 0.111161E+11 | 48459.00 | 30-MAR-15:10 | 48459.00 | 0.00 |
April | 0.00 | 0.00 | 0.248281E+11 | 0.203465E+11 | 54335.24 | 17-APR-15:40 | 54335.24 | 0.00 |
May | 0.00 | 0.00 | 0.462255E+11 | 0.352264E+11 | 65988.75 | 30-MAY-15:10 | 52104.38 | 0.00 |
June | 0.00 | 0.00 | 0.679196E+11 | 0.505498E+11 | 74954.04 | 26-JUN-15:00 | 53650.99 | 0.00 |
July | 0.00 | 0.00 | 0.774759E+11 | 0.544152E+11 | 79347.88 | 07-JUL-16:00 | 61163.05 | 0.00 |
August | 0.00 | 0.00 | 0.865473E+11 | 0.589091E+11 | 79254.12 | 17-AUG-15:30 | 58986.44 | 0.00 |
September | 0.00 | 0.00 | 0.532059E+11 | 0.381344E+11 | 77390.69 | 07-SEP-16:00 | 56680.79 | 0.00 |
October | 0.00 | 0.00 | 0.234098E+11 | 0.169656E+11 | 59558.80 | 11-OCT-14:10 | 44813.39 | 0.00 |
November | 0.00 | 0.00 | 0.973853E+10 | 0.725965E+10 | 29002.08 | 05-NOV-13:32 | 23082.93 | 0.00 |
December | 0.00 | 0.00 | 0.369216E+10 | 0.248861E+10 | 28500.51 | 12-DEC-14:00 | 20953.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.414220E+12 | 0.300742E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200835E+10 | 0.126820E+10 | 21910.88 | 12529.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.865473E+11 | 0.589091E+11 | 79347.88 | 61163.05 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208812E+10 | 0.129695E+10 | 22048.37 | 19-JAN-17:50 | 12103.09 | 0.00 |
February | 0.00 | 0.00 | 0.511044E+10 | 0.416431E+10 | 30266.09 | 26-FEB-15:13 | 30266.09 | 0.00 |
March | 0.00 | 0.00 | 0.149369E+11 | 0.116299E+11 | 54013.65 | 30-MAR-15:30 | 54013.65 | 0.00 |
April | 0.00 | 0.00 | 0.266444E+11 | 0.218575E+11 | 60363.56 | 17-APR-15:40 | 60363.56 | 0.00 |
May | 0.00 | 0.00 | 0.496304E+11 | 0.385225E+11 | 73968.09 | 30-MAY-15:10 | 60259.30 | 0.00 |
June | 0.00 | 0.00 | 0.725011E+11 | 0.549795E+11 | 82578.01 | 26-JUN-15:00 | 61436.61 | 0.00 |
July | 0.00 | 0.00 | 0.823764E+11 | 0.592145E+11 | 89545.63 | 07-JUL-16:00 | 71644.85 | 0.00 |
August | 0.00 | 0.00 | 0.910052E+11 | 0.634009E+11 | 88719.73 | 01-AUG-15:00 | 71041.17 | 0.00 |
September | 0.00 | 0.00 | 0.548678E+11 | 0.394961E+11 | 84820.85 | 06-SEP-14:00 | 63108.59 | 0.00 |
October | 0.00 | 0.00 | 0.237805E+11 | 0.171467E+11 | 64295.94 | 11-OCT-14:00 | 49051.90 | 0.00 |
November | 0.00 | 0.00 | 0.100445E+11 | 0.741647E+10 | 30240.05 | 02-NOV-13:40 | 21849.79 | 0.00 |
December | 0.00 | 0.00 | 0.380672E+10 | 0.254801E+10 | 30441.40 | 12-DEC-14:00 | 22412.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.436793E+12 | 0.321673E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.208812E+10 | 0.129695E+10 | 22048.37 | 12103.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.910052E+11 | 0.634009E+11 | 89545.63 | 71644.85 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1622.14 | 5938.05 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1635.70 | 5938.22 | 01-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1691.06 | 5844.24 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1473.72 | 5521.84 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1409.90 | 5140.54 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1334.31 | 4713.01 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1154.70 | 4387.43 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1273.65 | 4371.12 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1240.92 | 4647.28 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1339.84 | 5078.24 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1479.94 | 5492.35 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1516.69 | 5797.92 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1429.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1154.70 | 4371.12 | ||
Maximum of Months | 0.00 | 0.00 | 1691.06 | 5938.22 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.120402E+10 | 0.28 | 2336.43 | 09-JAN-07:01 | 0.76 |
February | 0.115856E+10 | 0.29 | 1715.18 | 28-FEB-16:20 | 0.65 |
March | 0.154119E+10 | 0.31 | 2462.13 | 30-MAR-16:00 | 0.78 |
April | 0.164219E+10 | 0.31 | 2988.37 | 18-APR-06:03 | 0.87 |
May | 0.220712E+10 | 0.35 | 3981.63 | 22-MAY-06:03 | 1.02 |
June | 0.315088E+10 | 0.43 | 5589.71 | 26-JUN-06:03 | 1.25 |
July | 0.349443E+10 | 0.43 | 6722.23 | 17-JUL-06:03 | 1.41 |
August | 0.402600E+10 | 0.48 | 10333.02 | 14-AUG-04:02 | 1.85 |
September | 0.290786E+10 | 0.40 | 5915.22 | 05-SEP-06:03 | 1.30 |
October | 0.200328E+10 | 0.33 | 4113.25 | 10-OCT-16:00 | 1.04 |
November | 0.143870E+10 | 0.29 | 2382.46 | 06-NOV-15:30 | 0.77 |
December | 0.122277E+10 | 0.28 | 1433.21 | 01-DEC-07:01 | 0.60 |
Annual Sum or Average | 0.259970E+11 | 0.35 | |||
Minimum of Months | 0.115856E+10 | 0.28 | 1433.21 | 0.60 | |
Maximum of Months | 0.402600E+10 | 0.48 | 10333.02 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128752E+10 | 0.30 | 2418.94 | 02-JAN-06:11 | 0.83 |
February | 0.122640E+10 | 0.31 | 2418.94 | 13-FEB-06:06 | 0.84 |
March | 0.149993E+10 | 0.33 | 2758.71 | 30-MAR-16:00 | 0.89 |
April | 0.160818E+10 | 0.33 | 2952.17 | 17-APR-16:00 | 0.92 |
May | 0.214141E+10 | 0.37 | 3812.99 | 30-MAY-15:00 | 1.07 |
June | 0.285815E+10 | 0.44 | 7237.35 | 26-JUN-05:12 | 1.58 |
July | 0.305989E+10 | 0.44 | 8225.17 | 15-JUL-05:03 | 1.71 |
August | 0.337344E+10 | 0.47 | 10068.59 | 14-AUG-04:02 | 1.95 |
September | 0.229826E+10 | 0.38 | 4439.77 | 07-SEP-15:30 | 1.17 |
October | 0.166024E+10 | 0.33 | 3263.84 | 11-OCT-15:30 | 0.98 |
November | 0.131425E+10 | 0.30 | 1773.65 | 21-NOV-06:01 | 0.71 |
December | 0.127550E+10 | 0.29 | 2418.94 | 04-DEC-06:01 | 0.84 |
Annual Sum or Average | 0.236032E+11 | 0.36 | |||
Minimum of Months | 0.122640E+10 | 0.29 | 1773.65 | 0.71 | |
Maximum of Months | 0.337344E+10 | 0.47 | 10068.59 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142140E+10 | 0.31 | 2283.42 | 02-JAN-06:12 | 0.72 |
February | 0.127601E+10 | 0.31 | 2283.42 | 06-FEB-06:01 | 0.73 |
March | 0.144176E+10 | 0.30 | 2719.06 | 30-MAR-16:00 | 0.79 |
April | 0.152668E+10 | 0.30 | 2938.56 | 17-APR-15:40 | 0.82 |
May | 0.201374E+10 | 0.34 | 3708.04 | 30-MAY-15:00 | 0.94 |
June | 0.266783E+10 | 0.39 | 4971.99 | 26-JUN-05:12 | 1.11 |
July | 0.285810E+10 | 0.39 | 5248.38 | 15-JUL-05:03 | 1.15 |
August | 0.310145E+10 | 0.41 | 5967.66 | 14-AUG-04:02 | 1.25 |
September | 0.202715E+10 | 0.34 | 4178.55 | 07-SEP-15:30 | 1.00 |
October | 0.149315E+10 | 0.29 | 2842.58 | 11-OCT-15:30 | 0.81 |
November | 0.126804E+10 | 0.28 | 2283.42 | 21-NOV-06:01 | 0.72 |
December | 0.128973E+10 | 0.28 | 2283.42 | 26-DEC-06:14 | 0.72 |
Annual Sum or Average | 0.223850E+11 | 0.33 | |||
Minimum of Months | 0.126804E+10 | 0.28 | 2283.42 | 0.72 | |
Maximum of Months | 0.310145E+10 | 0.41 | 5967.66 | 1.25 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.23 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.25 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.18 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.27 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.59 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.75 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.89 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.95 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.91 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.48 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.49 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.49 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.18 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.48 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.23 | 58.23 | 1622.14 | 5938.05 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.73 | 57.73 | 1635.70 | 5938.22 | 01-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.77 | 57.77 | 1691.06 | 5844.24 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.88 | 57.88 | 1473.72 | 5521.84 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.44 | 58.44 | 1409.90 | 5140.54 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.21 | 58.21 | 1334.31 | 4713.01 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.33 | 58.33 | 1154.70 | 4387.43 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.38 | 58.38 | 1273.65 | 4371.12 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.34 | 58.34 | 1240.92 | 4647.28 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.50 | 57.50 | 1339.84 | 5078.24 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.07 | 58.07 | 1479.94 | 5492.35 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.90 | 57.90 | 1516.69 | 5797.92 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1429.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.50 | 57.50 | 1154.70 | 4371.12 | ||
Maximum of Months | 0.00 | 0.00 | 58.44 | 58.44 | 1691.06 | 5938.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.160297E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.106246E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.686757E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.834734E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.134687E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.205098E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.236412E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.267509E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168962E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.879612E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.557424E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.704708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164554E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.557424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.267509E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167049E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.101035E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.545296E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.747525E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.126597E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.188771E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.214948E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.237161E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.143651E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.730586E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.508289E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.795936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.151197E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.508289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.237161E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.269600E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166501E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.725848E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.828306E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.133914E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.198497E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.225666E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245978E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.145716E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.848279E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.843878E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.154871E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.186537E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.725848E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.269600E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.120402E+10 | 0.199769E+10 | 0.143359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115856E+10 | 0.496106E+10 | 0.825235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154119E+10 | 0.150129E+11 | 0.181135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164219E+10 | 0.256881E+11 | 0.774216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220712E+10 | 0.489629E+11 | 0.170531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315088E+10 | 0.735298E+11 | 25625123.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.349443E+10 | 0.845191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.402600E+10 | 0.964149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290786E+10 | 0.618762E+11 | 23737487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200328E+10 | 0.275370E+11 | 0.575772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143870E+10 | 0.109438E+11 | 0.155426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122277E+10 | 0.396239E+10 | 0.488409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259970E+11 | 0.455406E+12 | 0.324078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115856E+10 | 0.199769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402600E+10 | 0.964149E+11 | 0.143359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128752E+10 | 0.200835E+10 | 0.149277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122640E+10 | 0.494226E+10 | 0.766625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149993E+10 | 0.142263E+11 | 0.603722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160818E+10 | 0.248281E+11 | 0.115428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214141E+10 | 0.462255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.285815E+10 | 0.679196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.305989E+10 | 0.774759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.337344E+10 | 0.865473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229826E+10 | 0.532059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166024E+10 | 0.234098E+11 | 0.310939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131425E+10 | 0.973853E+10 | 0.144962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127550E+10 | 0.369216E+10 | 0.580035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236032E+11 | 0.414220E+12 | 0.308740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122640E+10 | 0.200835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.337344E+10 | 0.865473E+11 | 0.149277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142140E+10 | 0.208812E+10 | 0.250262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127601E+10 | 0.511044E+10 | 0.141155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144176E+10 | 0.149369E+11 | 0.227760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152668E+10 | 0.266444E+11 | 0.554064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201374E+10 | 0.496304E+11 | 14467619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266783E+10 | 0.725011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285810E+10 | 0.823764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310145E+10 | 0.910052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202715E+10 | 0.548678E+11 | 5998030.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149315E+10 | 0.237805E+11 | 0.152591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+10 | 0.100445E+11 | 0.476313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128973E+10 | 0.380672E+10 | 0.132821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223850E+11 | 0.436793E+12 | 0.615651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126804E+10 | 0.208812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310145E+10 | 0.910052E+11 | 0.250262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.120402E+10 | 0.00 | 0.00 | 0.00 | 0.489820E+09 | 0.143359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115856E+10 | 0.00 | 0.00 | 0.00 | 0.121366E+10 | 0.825235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154119E+10 | 0.00 | 0.00 | 0.00 | 0.351503E+10 | 0.181135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164219E+10 | 0.00 | 0.00 | 0.00 | 0.593094E+10 | 0.774216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220712E+10 | 0.00 | 0.00 | 0.00 | 0.110910E+11 | 0.170531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315088E+10 | 0.00 | 0.00 | 0.00 | 0.173333E+11 | 25625123.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.349443E+10 | 0.00 | 0.00 | 0.00 | 0.201468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.402600E+10 | 0.00 | 0.00 | 0.00 | 0.227249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290786E+10 | 0.00 | 0.00 | 0.00 | 0.139646E+11 | 23737487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200328E+10 | 0.00 | 0.00 | 0.00 | 0.621706E+10 | 0.575772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143870E+10 | 0.00 | 0.00 | 0.00 | 0.258127E+10 | 0.155426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122277E+10 | 0.00 | 0.00 | 0.00 | 0.940212E+09 | 0.488409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259970E+11 | 0.00 | 0.00 | 0.00 | 0.106149E+12 | 0.324078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115856E+10 | 0.00 | 0.00 | 0.00 | 0.489820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402600E+10 | 0.00 | 0.00 | 0.00 | 0.227249E+11 | 0.143359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128752E+10 | 0.00 | 0.00 | 0.00 | 0.489702E+09 | 0.149277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122640E+10 | 0.00 | 0.00 | 0.00 | 0.121087E+10 | 0.766625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149993E+10 | 0.00 | 0.00 | 0.00 | 0.334931E+10 | 0.603722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160818E+10 | 0.00 | 0.00 | 0.00 | 0.575164E+10 | 0.115428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214141E+10 | 0.00 | 0.00 | 0.00 | 0.105182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.285815E+10 | 0.00 | 0.00 | 0.00 | 0.160189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.305989E+10 | 0.00 | 0.00 | 0.00 | 0.184349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.337344E+10 | 0.00 | 0.00 | 0.00 | 0.203426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229826E+10 | 0.00 | 0.00 | 0.00 | 0.120668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166024E+10 | 0.00 | 0.00 | 0.00 | 0.533468E+10 | 0.310939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131425E+10 | 0.00 | 0.00 | 0.00 | 0.231902E+10 | 0.144962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127550E+10 | 0.00 | 0.00 | 0.00 | 0.883520E+09 | 0.580035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236032E+11 | 0.00 | 0.00 | 0.00 | 0.967203E+11 | 0.308740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122640E+10 | 0.00 | 0.00 | 0.00 | 0.489702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.337344E+10 | 0.00 | 0.00 | 0.00 | 0.203426E+11 | 0.149277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142140E+10 | 0.00 | 0.00 | 0.00 | 0.512351E+09 | 0.250262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127601E+10 | 0.00 | 0.00 | 0.00 | 0.125854E+10 | 0.141155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144176E+10 | 0.00 | 0.00 | 0.00 | 0.353913E+10 | 0.227760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152668E+10 | 0.00 | 0.00 | 0.00 | 0.620232E+10 | 0.554064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201374E+10 | 0.00 | 0.00 | 0.00 | 0.113632E+11 | 14467619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.266783E+10 | 0.00 | 0.00 | 0.00 | 0.171819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285810E+10 | 0.00 | 0.00 | 0.00 | 0.197085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310145E+10 | 0.00 | 0.00 | 0.00 | 0.214964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202715E+10 | 0.00 | 0.00 | 0.00 | 0.125384E+11 | 5998030.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149315E+10 | 0.00 | 0.00 | 0.00 | 0.546374E+10 | 0.152591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+10 | 0.00 | 0.00 | 0.00 | 0.240761E+10 | 0.476313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128973E+10 | 0.00 | 0.00 | 0.00 | 0.915216E+09 | 0.132821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223850E+11 | 0.00 | 0.00 | 0.00 | 0.102587E+12 | 0.615651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126804E+10 | 0.00 | 0.00 | 0.00 | 0.512351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.310145E+10 | 0.00 | 0.00 | 0.00 | 0.214964E+11 | 0.250262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107938E+11 | 0.00 | 0.00 | 2811407.42 | 12196086.94 | 3211521.18 | 0.304176E+10 | 0.00 | 0.35 |
February | 0.630152E+10 | 0.00 | 0.00 | 9398497.38 | 0.00 | 0.00 | 0.561958E+10 | 0.00 | 0.45 |
March | 0.156444E+10 | 0.278919E+09 | 0.00 | 25877121.49 | 20599372.47 | 0.00 | 0.115804E+11 | 0.00 | 0.62 |
April | 0.618951E+09 | 0.511114E+09 | 0.00 | 26462290.17 | 37531644.99 | 0.00 | 0.761531E+10 | 0.00 | 0.65 |
May | 0.153691E+09 | 0.285992E+10 | 0.00 | 13178424.07 | 48928329.67 | 0.00 | 0.269655E+10 | 0.00 | 0.52 |
June | 54930091.65 | 0.813858E+10 | 0.00 | 6344883.50 | 73888838.62 | 0.00 | 0.128857E+10 | 0.00 | 0.41 |
July | 0.00 | 0.106465E+11 | 0.00 | 0.00 | 0.195448E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.127602E+11 | 0.00 | 227309.88 | 0.147522E+09 | 0.00 | 1765519.26 | 0.00 | 0.30 |
September | 64325288.98 | 0.517321E+10 | 0.00 | 13467476.53 | 0.100799E+09 | 0.00 | 0.186821E+10 | 0.00 | 0.49 |
October | 0.598638E+09 | 0.155501E+10 | 0.00 | 27940341.97 | 6522624.80 | 0.00 | 0.110149E+11 | 0.00 | 0.62 |
November | 0.168531E+10 | 0.162181E+09 | 0.00 | 26078030.45 | 40226014.24 | 0.00 | 0.120753E+11 | 0.00 | 0.59 |
December | 0.588241E+10 | 35724195.88 | 0.00 | 11296080.18 | 280913.61 | 0.00 | 0.745345E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.277180E+11 | 0.421214E+11 | 0.00 | 0.163082E+09 | 0.683943E+09 | 3211521.18 | 0.642558E+11 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.107938E+11 | 0.127602E+11 | 0.00 | 27940341.97 | 0.195448E+09 | 3211521.18 | 0.120753E+11 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123375E+11 | 0.00 | 0.00 | 0.00 | 30465428.19 | 0.554017E+09 | 0.00 | 0.00 | 0.34 |
February | 0.100978E+11 | 0.00 | 0.00 | 521021.43 | 4929884.32 | 0.137426E+09 | 0.352395E+09 | 0.00 | 0.41 |
March | 0.759308E+10 | 0.112425E+09 | 0.00 | 3857895.03 | 0.172307E+09 | 0.00 | 0.262211E+10 | 0.00 | 0.49 |
April | 0.316461E+10 | 0.235004E+09 | 0.00 | 8619912.49 | 0.246180E+09 | 0.00 | 0.293523E+10 | 0.00 | 0.49 |
May | 0.740773E+09 | 0.198605E+10 | 0.00 | 5628800.44 | 0.348712E+09 | 0.00 | 0.127877E+10 | 0.00 | 0.39 |
June | 0.286235E+09 | 0.705555E+10 | 0.00 | 3138689.69 | 0.125536E+09 | 0.00 | 0.684400E+09 | 0.00 | 0.33 |
July | 0.00 | 0.926307E+10 | 0.00 | 0.00 | 0.382048E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 1622979.08 | 0.115987E+11 | 0.00 | 72011.19 | 0.146207E+09 | 0.00 | 1470764.82 | 0.00 | 0.27 |
September | 0.369610E+09 | 0.427287E+10 | 0.00 | 5599502.19 | 0.522121E+09 | 0.00 | 0.830043E+09 | 0.00 | 0.37 |
October | 0.464524E+10 | 0.122835E+10 | 0.00 | 6569837.54 | 0.146241E+09 | 0.00 | 0.327464E+10 | 0.00 | 0.46 |
November | 0.842493E+10 | 29443114.59 | 0.00 | 1700350.39 | 0.253404E+09 | 1329154.34 | 0.151501E+10 | 0.00 | 0.44 |
December | 0.111079E+11 | 17525215.21 | 0.00 | 55310.92 | 42808772.48 | 0.109029E+09 | 0.108333E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.587694E+11 | 0.357990E+11 | 0.00 | 35763331.29 | 0.242096E+10 | 0.801801E+09 | 0.136024E+11 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4929884.32 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.123375E+11 | 0.115987E+11 | 0.00 | 8619912.49 | 0.522121E+09 | 0.554017E+09 | 0.327464E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.991030E+10 | 0.00 | 0.00 | 0.00 | 25261788.51 | 0.260091E+10 | 0.00 | 0.00 | 0.34 |
February | 0.905356E+10 | 0.00 | 0.00 | 207597.74 | 8486101.42 | 0.101896E+10 | 81864316.67 | 0.00 | 0.42 |
March | 0.880263E+10 | 0.112093E+09 | 0.00 | 2070870.71 | 0.187690E+09 | 20985917.90 | 0.958938E+09 | 0.00 | 0.50 |
April | 0.368064E+10 | 0.176453E+09 | 0.00 | 7119513.60 | 0.268707E+09 | 1429835.16 | 0.206983E+10 | 0.00 | 0.51 |
May | 0.789356E+09 | 0.179450E+10 | 0.00 | 3649328.21 | 0.426347E+09 | 0.00 | 0.100745E+10 | 0.00 | 0.38 |
June | 0.372909E+09 | 0.670770E+10 | 0.00 | 2639494.36 | 0.160067E+09 | 0.00 | 0.517482E+09 | 0.00 | 0.33 |
July | 0.00 | 0.885325E+10 | 0.00 | 0.00 | 0.454165E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.112030E+11 | 0.00 | 0.00 | 0.164449E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.449449E+09 | 0.374227E+10 | 0.00 | 4361759.79 | 0.107316E+10 | 0.00 | 0.519612E+09 | 0.00 | 0.36 |
October | 0.570231E+10 | 0.106209E+10 | 0.00 | 2771504.59 | 0.334819E+09 | 13060172.75 | 0.148263E+10 | 0.00 | 0.44 |
November | 0.874972E+10 | 17648403.24 | 3338853.96 | 310975.10 | 0.301651E+09 | 0.153079E+09 | 0.294561E+09 | 40307.84 | 0.45 |
December | 0.997790E+10 | 1434671.72 | 0.00 | 0.00 | 73956751.66 | 0.786610E+09 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.574888E+11 | 0.336704E+11 | 3338853.96 | 23131044.09 | 0.347876E+10 | 0.459503E+10 | 0.693237E+10 | 40307.84 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8486101.42 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.997790E+10 | 0.112030E+11 | 3338853.96 | 7119513.60 | 0.107316E+10 | 0.260091E+10 | 0.206983E+10 | 40307.84 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551068E+09 | 0.00 | 0.00 | 0.00 | 5332229.98 | 0.225820E+10 | 0.00 | 0.00 | 0.36 |
February | 0.935801E+09 | 0.00 | 296001.33 | 60175.02 | 1494767.84 | 0.127602E+10 | 18353606.05 | 467.60 | 0.43 |
March | 0.171818E+10 | 27301065.44 | 0.00 | 344805.60 | 38380656.88 | 0.228663E+09 | 0.123514E+09 | 0.00 | 0.51 |
April | 0.917436E+09 | 63357123.02 | 0.00 | 1511659.72 | 37657073.77 | 55414935.33 | 0.260326E+09 | 0.00 | 0.54 |
May | 0.214639E+09 | 0.522105E+09 | 0.00 | 801758.15 | 62216357.31 | 284381.19 | 0.176316E+09 | 0.00 | 0.43 |
June | 81870034.61 | 0.210988E+10 | 0.00 | 703073.57 | 33425671.93 | 0.00 | 0.119737E+09 | 0.00 | 0.45 |
July | 0.00 | 0.284893E+10 | 0.00 | 0.00 | 82027730.10 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.337600E+10 | 0.00 | 0.00 | 41035298.21 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.114135E+09 | 0.995677E+09 | 0.00 | 941169.31 | 0.207179E+09 | 0.00 | 0.100558E+09 | 0.00 | 0.40 |
October | 0.124232E+10 | 0.256063E+09 | 0.00 | 305011.40 | 70789443.25 | 0.127363E+09 | 0.142346E+09 | 0.00 | 0.45 |
November | 0.147286E+10 | 3748431.90 | 3672476.16 | 13520.43 | 60750515.99 | 0.473921E+09 | 10472444.33 | 12365.51 | 0.45 |
December | 0.101155E+10 | 0.00 | 91130.96 | 0.00 | 15822040.44 | 0.133424E+10 | 0.00 | 365.68 | 0.40 |
Annual Sum or Average | 0.825986E+10 | 0.102031E+11 | 4059608.45 | 4681173.20 | 0.656111E+09 | 0.575410E+10 | 0.951623E+09 | 13198.80 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1494767.84 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.171818E+10 | 0.337600E+10 | 3672476.16 | 1511659.72 | 0.207179E+09 | 0.225820E+10 | 0.260326E+09 | 12365.51 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.846586E+09 | 0.00 | 0.00 | 0.00 | 4484692.00 | 0.142587E+10 | 0.00 | 0.00 | 0.46 |
February | 0.913900E+09 | 0.00 | 248724.72 | 208180.51 | 1257180.09 | 0.798571E+09 | 0.116602E+09 | 621.59 | 0.56 |
March | 0.127490E+10 | 22389448.49 | 0.00 | 834367.80 | 32879307.08 | 0.123721E+09 | 0.357109E+09 | 0.00 | 0.69 |
April | 0.520920E+09 | 50331088.48 | 0.00 | 2457199.09 | 33973687.26 | 25112614.85 | 0.593249E+09 | 0.00 | 0.82 |
May | 0.130313E+09 | 0.498504E+09 | 0.00 | 1204193.98 | 56565860.45 | 659768.24 | 0.267609E+09 | 0.00 | 0.65 |
June | 52088447.72 | 0.177526E+10 | 0.00 | 915378.06 | 37096476.51 | 0.00 | 0.173916E+09 | 0.00 | 0.64 |
July | 0.00 | 0.248185E+10 | 0.00 | 0.00 | 94666548.05 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.284333E+10 | 0.00 | 0.00 | 59615294.10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 86779830.66 | 0.944570E+09 | 0.00 | 1128066.20 | 0.178305E+09 | 215472.43 | 0.121938E+09 | 0.00 | 0.61 |
October | 0.839273E+09 | 0.222316E+09 | 0.00 | 931397.32 | 62906720.34 | 96279034.69 | 0.406718E+09 | 0.00 | 0.63 |
November | 0.130964E+10 | 4440742.05 | 3041936.00 | 64510.42 | 49806339.65 | 0.263883E+09 | 64675298.27 | 7910.17 | 0.59 |
December | 0.118445E+10 | 0.00 | 75422.30 | 0.00 | 13307186.37 | 0.749590E+09 | 0.00 | 1531.29 | 0.53 |
Annual Sum or Average | 0.715886E+10 | 0.884300E+10 | 3366083.03 | 7743293.37 | 0.624865E+09 | 0.348390E+10 | 0.210182E+10 | 10063.05 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1257180.09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.130964E+10 | 0.284333E+10 | 3041936.00 | 2457199.09 | 0.178305E+09 | 0.142587E+10 | 0.593249E+09 | 7910.17 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100110E+10 | 0.00 | 0.00 | 971887.02 | 5415244.02 | 0.136001E+10 | 0.578887E+09 | 0.00 | 0.38 |
February | 0.977907E+09 | 0.00 | 0.00 | 1868478.31 | 1819123.37 | 0.806226E+09 | 0.725728E+09 | 0.00 | 0.52 |
March | 0.125760E+10 | 61410997.80 | 0.00 | 3329048.67 | 21887433.04 | 0.166024E+09 | 0.108183E+10 | 0.00 | 0.66 |
April | 0.706465E+09 | 88335045.36 | 0.00 | 3544698.36 | 24661265.20 | 43963634.92 | 0.727914E+09 | 0.00 | 0.70 |
May | 0.205654E+09 | 0.592869E+09 | 0.00 | 1138821.90 | 64986792.79 | 288808.54 | 0.237848E+09 | 0.00 | 0.49 |
June | 90808129.85 | 0.214459E+10 | 0.00 | 719596.45 | 52205434.71 | 0.00 | 0.120102E+09 | 0.00 | 0.46 |
July | 0.00 | 0.296566E+10 | 0.00 | 0.00 | 98188586.27 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.391346E+10 | 0.00 | 0.00 | 42611512.98 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.106338E+09 | 0.141907E+10 | 0.00 | 1851279.98 | 0.165857E+09 | 0.00 | 0.190333E+09 | 0.00 | 0.56 |
October | 0.847216E+09 | 0.443958E+09 | 0.00 | 3661708.51 | 39617564.73 | 89656222.47 | 0.125215E+10 | 0.00 | 0.70 |
November | 0.113928E+10 | 8461826.42 | 1524932.89 | 3019807.79 | 61162066.46 | 0.254939E+09 | 0.109756E+10 | 9541.41 | 0.61 |
December | 0.118617E+10 | 6088918.90 | 0.00 | 1898934.81 | 12652318.88 | 0.617479E+09 | 0.846136E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.751854E+10 | 0.116439E+11 | 1524932.89 | 22004261.80 | 0.591064E+09 | 0.333859E+10 | 0.685848E+10 | 9541.41 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1819123.37 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.125760E+10 | 0.391346E+10 | 1524932.89 | 3661708.51 | 0.165857E+09 | 0.136001E+10 | 0.125215E+10 | 9541.41 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.821402E+09 | 0.00 | 0.00 | 0.00 | 4943029.16 | 0.166901E+10 | 0.00 | 0.00 | 0.51 |
February | 0.943893E+09 | 0.00 | 0.00 | 302150.05 | 1660493.94 | 0.978961E+09 | 0.112232E+09 | 0.00 | 0.63 |
March | 0.141337E+10 | 33000170.91 | 0.00 | 1183678.45 | 30875675.14 | 0.192949E+09 | 0.393599E+09 | 0.00 | 0.80 |
April | 0.724003E+09 | 46642248.63 | 0.00 | 2404872.69 | 43937551.52 | 42130305.18 | 0.483956E+09 | 0.00 | 0.90 |
May | 0.202170E+09 | 0.422014E+09 | 0.00 | 941127.40 | 87803967.47 | 727196.80 | 0.214857E+09 | 0.00 | 0.67 |
June | 91447070.26 | 0.165304E+10 | 0.00 | 645495.22 | 85291475.04 | 0.00 | 0.104057E+09 | 0.00 | 0.61 |
July | 0.00 | 0.225210E+10 | 0.00 | 0.00 | 0.146011E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.279750E+10 | 0.00 | 0.00 | 78727405.86 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.111247E+09 | 0.844146E+09 | 0.00 | 972751.56 | 0.242910E+09 | 237493.79 | 97747483.05 | 0.00 | 0.61 |
October | 0.103838E+10 | 0.193756E+09 | 0.00 | 949297.92 | 97059372.64 | 0.111625E+09 | 0.347268E+09 | 0.00 | 0.71 |
November | 0.129491E+10 | 584183.28 | 3338142.83 | 367368.25 | 59206969.97 | 0.384529E+09 | 0.156805E+09 | 7812.36 | 0.67 |
December | 0.110499E+10 | 391096.37 | 82884.64 | 9420.01 | 14276089.31 | 0.994477E+09 | 27511497.50 | 1933.65 | 0.58 |
Annual Sum or Average | 0.774582E+10 | 0.824318E+10 | 3421027.47 | 7776161.56 | 0.892703E+09 | 0.437465E+10 | 0.193803E+10 | 9746.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1660493.94 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.141337E+10 | 0.279750E+10 | 3338142.83 | 2404872.69 | 0.242910E+09 | 0.166901E+10 | 0.483956E+09 | 7812.36 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.805126E+09 | 0.00 | 0.00 | 0.00 | 2571587.23 | 0.215163E+10 | 0.00 | 0.00 | 0.35 |
February | 0.124229E+10 | 0.00 | 0.00 | 1261.41 | 0.00 | 0.119356E+10 | 2854878.72 | 0.00 | 0.42 |
March | 0.209380E+10 | 8988736.64 | 0.00 | 34819.04 | 44148835.74 | 0.125171E+09 | 35836284.58 | 0.00 | 0.49 |
April | 0.120018E+10 | 21110806.18 | 0.00 | 290557.98 | 70767652.05 | 22023771.72 | 58969424.59 | 0.00 | 0.47 |
May | 0.326495E+09 | 0.363490E+09 | 0.00 | 293200.64 | 92767226.82 | 0.00 | 82243808.97 | 0.00 | 0.36 |
June | 99566027.49 | 0.160691E+10 | 0.00 | 542417.68 | 23437227.17 | 0.00 | 98625977.96 | 0.00 | 0.35 |
July | 0.00 | 0.224348E+10 | 0.00 | 0.00 | 52926012.48 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 261562.64 | 0.270833E+10 | 0.00 | 2547.72 | 31292293.19 | 0.00 | 40108.52 | 0.00 | 0.29 |
September | 0.140622E+09 | 0.943568E+09 | 0.00 | 1088010.73 | 31765373.50 | 0.00 | 0.142359E+09 | 0.00 | 0.38 |
October | 0.151090E+10 | 0.245043E+09 | 0.00 | 521128.32 | 10756879.74 | 3407725.99 | 0.259747E+09 | 0.00 | 0.45 |
November | 0.221387E+10 | 2388841.19 | 0.00 | 53298.31 | 35966492.67 | 70470362.75 | 48101030.50 | 0.00 | 0.46 |
December | 0.204283E+10 | 0.00 | 0.00 | 0.00 | 5742888.11 | 0.654348E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.116759E+11 | 0.814330E+10 | 0.00 | 2827241.83 | 0.402142E+09 | 0.422061E+10 | 0.728778E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.221387E+10 | 0.270833E+10 | 0.00 | 1088010.73 | 92767226.82 | 0.215163E+10 | 0.259747E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.982555E+09 | 0.00 | 0.00 | 0.00 | 1897249.09 | 0.118983E+10 | 0.00 | 0.00 | 0.40 |
February | 0.106361E+10 | 0.00 | 0.00 | 181957.54 | 0.00 | 0.618816E+09 | 0.109075E+09 | 0.00 | 0.49 |
March | 0.136527E+10 | 10900304.81 | 0.00 | 483232.97 | 29149200.29 | 46198511.38 | 0.265540E+09 | 0.00 | 0.58 |
April | 0.652689E+09 | 27931491.93 | 0.00 | 1472185.80 | 42453196.18 | 5862576.21 | 0.361069E+09 | 0.00 | 0.63 |
May | 0.151374E+09 | 0.386601E+09 | 0.00 | 1021980.39 | 51964784.61 | 0.00 | 0.225624E+09 | 0.00 | 0.53 |
June | 46810179.10 | 0.142463E+10 | 0.00 | 885387.52 | 16281209.38 | 0.00 | 0.173630E+09 | 0.00 | 0.52 |
July | 0.00 | 0.204196E+10 | 0.00 | 0.00 | 47888125.07 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 192974.00 | 0.236726E+10 | 0.00 | 2062.88 | 23082409.35 | 0.00 | 29407.77 | 0.00 | 0.41 |
September | 93203644.08 | 0.868320E+09 | 0.00 | 1341039.90 | 19045709.07 | 0.00 | 0.175260E+09 | 0.00 | 0.56 |
October | 0.831313E+09 | 0.212541E+09 | 0.00 | 1583497.06 | 3448525.48 | 2521462.08 | 0.669939E+09 | 0.00 | 0.61 |
November | 0.149041E+10 | 1941215.21 | 0.00 | 418431.62 | 26369318.69 | 15792226.83 | 0.231463E+09 | 0.00 | 0.55 |
December | 0.173296E+10 | 0.00 | 0.00 | 0.00 | 4236951.07 | 0.257057E+09 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.841040E+10 | 0.734208E+10 | 0.00 | 7389775.69 | 0.265817E+09 | 0.213607E+10 | 0.221163E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.173296E+10 | 0.236726E+10 | 0.00 | 1583497.06 | 51964784.61 | 0.118983E+10 | 0.669939E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119424E+10 | 0.00 | 0.00 | 76377.59 | 2565124.50 | 0.223220E+10 | 64281222.07 | 0.00 | 0.40 |
February | 0.112918E+10 | 0.00 | 0.00 | 828847.51 | 0.00 | 0.145670E+10 | 0.266944E+09 | 0.00 | 0.50 |
March | 0.162201E+10 | 45754733.16 | 0.00 | 975753.87 | 20190342.71 | 0.546546E+09 | 0.332100E+09 | 0.00 | 0.56 |
April | 0.975105E+09 | 43477408.72 | 0.00 | 1214331.31 | 60165489.78 | 0.287112E+09 | 0.130502E+09 | 0.00 | 0.55 |
May | 0.298319E+09 | 0.474583E+09 | 0.00 | 368947.90 | 93219032.71 | 64521157.81 | 75538216.84 | 0.00 | 0.41 |
June | 0.113362E+09 | 0.190874E+10 | 0.00 | 419986.68 | 74062980.98 | 16268375.81 | 66899729.24 | 0.00 | 0.39 |
July | 0.00 | 0.264749E+10 | 0.00 | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 303454.34 | 0.361148E+10 | 0.00 | 0.00 | 48395920.16 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.146103E+09 | 0.137340E+10 | 0.00 | 1736376.31 | 46273088.12 | 14856122.53 | 0.179107E+09 | 0.00 | 0.53 |
October | 0.982694E+09 | 0.404757E+09 | 0.00 | 3065738.33 | 8758294.42 | 0.252958E+09 | 0.106493E+10 | 0.00 | 0.66 |
November | 0.143442E+10 | 11423159.96 | 0.00 | 2496544.19 | 28707228.29 | 0.471534E+09 | 0.979191E+09 | 0.00 | 0.61 |
December | 0.174787E+10 | 3954181.10 | 0.00 | 803791.23 | 2760006.29 | 0.861966E+09 | 0.426349E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.964360E+10 | 0.105251E+11 | 0.00 | 11986694.91 | 0.492867E+09 | 0.620466E+10 | 0.358584E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.174787E+10 | 0.361148E+10 | 0.00 | 3065738.33 | 0.107770E+09 | 0.223220E+10 | 0.106493E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.894289E+09 | 0.00 | 0.00 | 0.00 | 1962741.96 | 0.135064E+10 | 0.00 | 0.00 | 0.42 |
February | 0.108288E+10 | 0.00 | 0.00 | 186022.49 | 0.00 | 0.720337E+09 | 55066866.71 | 0.00 | 0.51 |
March | 0.147657E+10 | 24830057.64 | 0.00 | 591123.92 | 21258914.69 | 55682363.29 | 0.219927E+09 | 0.00 | 0.62 |
April | 0.789447E+09 | 31615079.56 | 0.00 | 1079380.50 | 44068693.81 | 11320725.71 | 0.217855E+09 | 0.00 | 0.64 |
May | 0.216329E+09 | 0.355633E+09 | 0.00 | 572933.67 | 53314441.42 | 0.00 | 0.138185E+09 | 0.00 | 0.51 |
June | 78325808.37 | 0.136317E+10 | 0.00 | 551754.34 | 19743443.18 | 0.00 | 87258303.46 | 0.00 | 0.48 |
July | 0.00 | 0.189402E+10 | 0.00 | 0.00 | 46515016.88 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 175091.49 | 0.235494E+10 | 0.00 | 2521.41 | 14691123.44 | 0.00 | 54579.56 | 0.00 | 0.40 |
September | 0.105202E+09 | 0.838240E+09 | 0.00 | 1117404.56 | 22379161.76 | 0.00 | 0.123393E+09 | 0.00 | 0.53 |
October | 0.979995E+09 | 0.210290E+09 | 0.00 | 1251166.43 | 5307176.43 | 838808.70 | 0.483436E+09 | 0.00 | 0.62 |
November | 0.155691E+10 | 1870295.47 | 0.00 | 544771.44 | 27406782.75 | 32816381.24 | 0.234319E+09 | 0.00 | 0.58 |
December | 0.169384E+10 | 211287.74 | 0.00 | 27742.28 | 4171922.50 | 0.332433E+09 | 31829067.66 | 0.00 | 0.49 |
Annual Sum or Average | 0.887396E+10 | 0.707482E+10 | 0.00 | 5924821.05 | 0.260819E+09 | 0.250407E+10 | 0.159132E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.169384E+10 | 0.235494E+10 | 0.00 | 1251166.43 | 53314441.42 | 0.135064E+10 | 0.483436E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.855232E+09 | 0.00 | 0.00 | 0.00 | 6408868.40 | 0.191510E+10 | 0.00 | 0.00 | 0.34 |
February | 0.127520E+10 | 0.00 | 0.00 | 73787.26 | 1037076.51 | 0.970326E+09 | 15858958.71 | 0.00 | 0.41 |
March | 0.195611E+10 | 32196153.16 | 0.00 | 343126.15 | 30967423.32 | 67358177.61 | 0.124986E+09 | 0.00 | 0.50 |
April | 0.967378E+09 | 81118024.75 | 0.00 | 1330873.86 | 29611691.49 | 14949408.87 | 0.290097E+09 | 0.00 | 0.51 |
May | 0.229673E+09 | 0.596910E+09 | 0.00 | 953843.94 | 32722445.41 | 0.00 | 0.190569E+09 | 0.00 | 0.43 |
June | 82177520.06 | 0.226349E+10 | 0.00 | 734512.42 | 16688607.21 | 0.00 | 0.126649E+09 | 0.00 | 0.44 |
July | 0.00 | 0.303205E+10 | 0.00 | 0.00 | 53803008.55 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 484289.12 | 0.355392E+10 | 0.00 | 686.41 | 30999094.49 | 0.00 | 180989.44 | 0.00 | 0.38 |
September | 0.141040E+09 | 0.116407E+10 | 0.00 | 907451.22 | 55851684.06 | 0.00 | 0.104506E+09 | 0.00 | 0.40 |
October | 0.140216E+10 | 0.297317E+09 | 0.00 | 451309.26 | 25520735.74 | 19156329.37 | 0.202063E+09 | 0.00 | 0.45 |
November | 0.182865E+10 | 5712044.37 | 184101.44 | 32054.76 | 53601910.88 | 0.226015E+09 | 38639087.69 | 4275.99 | 0.44 |
December | 0.159428E+10 | 812447.25 | 0.00 | 0.00 | 11879729.10 | 0.809633E+09 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.103324E+11 | 0.110276E+11 | 184101.44 | 4827645.28 | 0.349092E+09 | 0.402254E+10 | 0.109355E+10 | 4275.99 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1037076.51 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.195611E+10 | 0.355392E+10 | 184101.44 | 1330873.86 | 55851684.06 | 0.191510E+10 | 0.290097E+09 | 4275.99 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105640E+10 | 0.00 | 0.00 | 0.00 | 5424101.81 | 0.126131E+10 | 0.00 | 0.00 | 0.45 |
February | 0.110361E+10 | 0.00 | 0.00 | 291955.98 | 877722.59 | 0.662101E+09 | 0.146618E+09 | 0.00 | 0.55 |
March | 0.135341E+10 | 23418393.86 | 0.00 | 991237.40 | 28672518.54 | 39971457.92 | 0.474555E+09 | 0.00 | 0.68 |
April | 0.577913E+09 | 68828240.41 | 0.00 | 2401406.04 | 22694264.80 | 7033572.87 | 0.650658E+09 | 0.00 | 0.78 |
May | 0.154738E+09 | 0.527508E+09 | 0.00 | 1403784.07 | 40282811.66 | 0.00 | 0.292099E+09 | 0.00 | 0.66 |
June | 57763794.43 | 0.185499E+10 | 0.00 | 960724.74 | 18958394.18 | 0.00 | 0.186258E+09 | 0.00 | 0.63 |
July | 0.00 | 0.257874E+10 | 0.00 | 0.00 | 69573958.63 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 539851.49 | 0.293952E+10 | 0.00 | 143.17 | 32740838.30 | 0.00 | 23640.22 | 0.00 | 0.50 |
September | 0.117190E+09 | 0.976902E+09 | 0.00 | 1078434.69 | 0.118346E+09 | 0.00 | 0.131903E+09 | 0.00 | 0.60 |
October | 0.977285E+09 | 0.223794E+09 | 0.00 | 1202254.16 | 42088367.80 | 18523488.62 | 0.513188E+09 | 0.00 | 0.65 |
November | 0.150311E+10 | 5207161.61 | 151041.76 | 207007.82 | 44981746.85 | 0.124762E+09 | 0.148495E+09 | 3539.39 | 0.59 |
December | 0.157984E+10 | 0.00 | 0.00 | 0.00 | 10741936.39 | 0.447865E+09 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.848180E+10 | 0.919890E+10 | 151041.76 | 8536948.07 | 0.435382E+09 | 0.256157E+10 | 0.254380E+10 | 3539.39 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 877722.59 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.157984E+10 | 0.293952E+10 | 151041.76 | 2401406.04 | 0.118346E+09 | 0.126131E+10 | 0.650658E+09 | 3539.39 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122605E+10 | 0.00 | 0.00 | 1407788.14 | 6419724.90 | 0.102733E+10 | 0.742707E+09 | 0.00 | 0.37 |
February | 0.123943E+10 | 0.00 | 0.00 | 2243410.21 | 1038833.29 | 0.516929E+09 | 0.844852E+09 | 0.00 | 0.52 |
March | 0.139832E+10 | 77629038.96 | 0.00 | 3492957.57 | 11577361.89 | 36065323.93 | 0.116915E+10 | 0.00 | 0.66 |
April | 0.749991E+09 | 0.116950E+09 | 0.00 | 3209587.96 | 14847055.27 | 14254750.53 | 0.719960E+09 | 0.00 | 0.65 |
May | 0.230990E+09 | 0.687958E+09 | 0.00 | 1203495.60 | 33373537.65 | 0.00 | 0.227713E+09 | 0.00 | 0.48 |
June | 97892573.84 | 0.232600E+10 | 0.00 | 693038.85 | 17991854.95 | 0.00 | 0.111922E+09 | 0.00 | 0.46 |
July | 0.00 | 0.318821E+10 | 0.00 | 0.00 | 52737950.23 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 485109.49 | 0.415166E+10 | 0.00 | 622.94 | 31051606.34 | 0.00 | 181360.66 | 0.00 | 0.44 |
September | 0.133580E+09 | 0.159693E+10 | 0.00 | 1689884.71 | 42144370.02 | 0.00 | 0.173909E+09 | 0.00 | 0.55 |
October | 0.940345E+09 | 0.474790E+09 | 0.00 | 4235705.40 | 12678602.95 | 16230034.45 | 0.141010E+10 | 0.00 | 0.73 |
November | 0.131710E+10 | 20629064.78 | 0.00 | 3987531.21 | 42754029.93 | 70746455.92 | 0.137832E+10 | 0.00 | 0.64 |
December | 0.143163E+10 | 14315542.01 | 0.00 | 2571263.87 | 3162342.48 | 0.337588E+09 | 0.108199E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.876582E+10 | 0.126551E+11 | 0.00 | 24735286.46 | 0.269777E+09 | 0.201915E+10 | 0.786080E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1038833.29 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.143163E+10 | 0.415166E+10 | 0.00 | 4235705.40 | 52737950.23 | 0.102733E+10 | 0.141010E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.969645E+09 | 0.00 | 0.00 | 0.00 | 5642664.66 | 0.143886E+10 | 0.00 | 0.00 | 0.47 |
February | 0.118535E+10 | 0.00 | 0.00 | 339018.31 | 913090.20 | 0.710429E+09 | 0.102660E+09 | 0.00 | 0.59 |
March | 0.155511E+10 | 45892325.87 | 0.00 | 1149778.70 | 17490373.46 | 54637538.51 | 0.369345E+09 | 0.00 | 0.75 |
April | 0.769299E+09 | 71893835.41 | 0.00 | 2043650.82 | 28011127.56 | 13289197.22 | 0.435968E+09 | 0.00 | 0.80 |
May | 0.218202E+09 | 0.514183E+09 | 0.00 | 882582.13 | 40609265.63 | 0.00 | 0.197506E+09 | 0.00 | 0.65 |
June | 92759174.02 | 0.184742E+10 | 0.00 | 598519.76 | 27625801.67 | 0.00 | 93280729.50 | 0.00 | 0.61 |
July | 0.00 | 0.248557E+10 | 0.00 | 0.00 | 66986327.93 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 586346.41 | 0.301697E+10 | 0.00 | 0.00 | 24278889.56 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.133687E+09 | 0.957398E+09 | 0.00 | 849005.21 | 0.128855E+09 | 0.00 | 83462479.55 | 0.00 | 0.58 |
October | 0.114664E+10 | 0.236254E+09 | 0.00 | 1080904.84 | 39177265.21 | 18532888.93 | 0.366557E+09 | 0.00 | 0.68 |
November | 0.150564E+10 | 3958639.15 | 162569.20 | 494289.30 | 48279504.09 | 0.167864E+09 | 0.211594E+09 | 3819.52 | 0.64 |
December | 0.148668E+10 | 1024365.47 | 0.00 | 36584.15 | 10150414.62 | 0.578887E+09 | 42330957.22 | 0.00 | 0.54 |
Annual Sum or Average | 0.906361E+10 | 0.918057E+10 | 162569.20 | 7474333.23 | 0.438019E+09 | 0.298250E+10 | 0.190270E+10 | 3819.52 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 913090.20 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.155511E+10 | 0.301697E+10 | 162569.20 | 2043650.82 | 0.128855E+09 | 0.143886E+10 | 0.435968E+09 | 3819.52 | 0.80 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.188488E+12 | 0.105682E+11 | 0.00 | 0.197666E+12 | 0.758604E+10 |
February | 0.186118E+12 | 0.861413E+10 | 0.00 | 0.190471E+12 | 0.186968E+11 |
March | 0.267020E+12 | 0.551382E+10 | 0.00 | 0.204633E+12 | 0.545796E+11 |
April | 0.296197E+12 | 0.246177E+10 | 0.00 | 0.129664E+12 | 0.950455E+11 |
May | 0.324943E+12 | -419558405.2 | 0.00 | 0.364272E+11 | 0.177791E+12 |
June | 0.315034E+12 | -0.413490E+10 | 0.00 | -0.176182E+11 | 0.264485E+12 |
July | 0.305345E+12 | -0.587463E+10 | 0.00 | -0.613737E+11 | 0.302662E+12 |
August | 0.284910E+12 | -0.720119E+10 | 0.00 | -0.741042E+11 | 0.338531E+12 |
September | 0.223406E+12 | -0.210898E+10 | 0.00 | -0.421923E+10 | 0.208520E+12 |
October | 0.215474E+12 | 0.261435E+10 | 0.00 | 0.144319E+12 | 0.917429E+11 |
November | 0.159275E+12 | 0.556751E+10 | 0.00 | 0.183317E+12 | 0.380348E+11 |
December | 0.153647E+12 | 0.909936E+10 | 0.00 | 0.220108E+12 | 0.142002E+11 |
Annual Sum or Average | 0.291986E+13 | 0.246999E+11 | 0.00 | 0.114929E+13 | 0.161187E+13 |
Minimum of Months | 0.153647E+12 | -0.720119E+10 | 0.00 | -0.741042E+11 | 0.758604E+10 |
Maximum of Months | 0.324943E+12 | 0.105682E+11 | 0.00 | 0.220108E+12 | 0.338531E+12 |