Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000

Simulation Timestamp: 2024-07-03 12:20:27


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2152.80 432.10 432.10
Net Site Energy 2152.80 432.10 432.10
Total Source Energy 6817.91 1368.46 1368.46
Net Source Energy 6817.91 1368.46 1368.46


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 899.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 299.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 49.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 121.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2152.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06


End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 899.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 299.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 49.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 121.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 35.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 899.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 299.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 49.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 121.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 35.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 212.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 432.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 70.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 212.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 432.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 2152.797 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 2152.797 100.00
     
Total On-Site and Utility Electric Sources 2152.797 100.00
Total Electricity End Uses 2152.797 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 805.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2150.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Latitude [deg] 10.82
Longitude [deg] 106.67
Elevation [m] 5.00
Time Zone 7.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 8.6994 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 8.6994 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 8.6994 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 8.6994 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 8.6994 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 8.6994 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 8.6994 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 8.6994 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 8.6994 18.58 8.0700  
Total 4982.19             8.6994 9.29 24.1370  
Conditioned Total 4982.19             8.6994 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 8.6994 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 13-JUN-15:20 - - - - - - - - - - - 03-JAN-12:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 89917.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41670.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 15860.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2875.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 177422.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 89917.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 57.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 15860.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2875.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2849.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 949.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 156.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 384.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 112.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 6817.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 571.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 190.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 77.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1368.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 571.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 190.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 77.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1368.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2]
CORE_BOTTOM VAV BOX COMPONENT 2.64 0.283532 0.291000 0.769194 0.756086 0.500000 0.001344
CORE_MID VAV BOX COMPONENT 2.14 0.350020 0.349000 0.747272 0.933386 0.500000 0.001089
CORE_TOP VAV BOX COMPONENT 2.28 0.328188 0.341000 0.778712 0.875168 0.500000 0.001161
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.736186 0.214608 0.223000 0.164169 0.572289 0.500000 0.001775
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.661728 0.151152 0.200000 0.132346 0.403073 0.500000 0.002521
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 0.716865 0.220393 0.229000 0.164162 0.587714 0.500000 0.001729
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.763213 0.131045 0.200000 0.152643 0.349453 0.500000 0.002907
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.635339 0.248673 0.255000 0.162011 0.663128 0.500000 0.001532
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.601031 0.166417 0.200000 0.120206 0.443778 0.500000 0.002289
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.617240 0.255965 0.263000 0.162334 0.682572 0.500000 0.001488
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.646038 0.154813 0.200000 0.129208 0.412835 0.500000 0.002461
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.641658 0.246224 0.246000 0.157848 0.656598 0.500000 0.001547
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.637595 0.156873 0.200000 0.127519 0.418329 0.500000 0.002429
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 0.624360 0.253046 0.252000 0.157339 0.674789 0.500000 0.001506
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.692722 0.144380 0.200000 0.138544 0.385013 0.500000 0.002639
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 25678.07
CORE_MID VAV BOX REHEAT COIL 24946.24
CORE_TOP VAV BOX REHEAT COIL 25995.83
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 5480.49
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 4418.11
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 5480.24
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 5095.68
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 5408.44
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4012.86
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 5419.22
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4313.35
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 5269.45
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 4256.98
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 5252.46
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 4625.04
PACU_VAV_BOT HEATING COIL 21979.05
PACU_VAV_MID HEATING COIL 19821.58
PACU_VAV_TOP HEATING COIL 23018.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.57 1.34 5.14 1.34 4.73 4.73 0.300000 0.283771 4.73
PACU_VAV_MID 2.37 1.33 4.74 1.33 4.27 4.27 0.300000 0.311277 4.27
PACU_VAV_TOP 2.58 1.39 5.16 1.39 4.96 4.96 0.300000 0.280863 4.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.73
PACU_VAV_MID_OA_CONTROLLER 4.27
PACU_VAV_TOP_OA_CONTROLLER 4.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.73 117519.73 0.701083 1.58 39169.33 0.701083
PACU_VAV_MID COOLING COIL 4.27 105983.93 0.701083 1.42 35324.44 0.701083
PACU_VAV_TOP COOLING COIL 4.96 123076.04 0.701083 1.65 41021.24 0.701083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.73
PACU_VAV_MID FAN 4.27
PACU_VAV_TOP FAN 4.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.90 26.70 26.00 26.40 27.50 28.30 29.20 29.00 28.90 27.20 27.50 27.60


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 10.82 106.67 7.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 27.60 3.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 8.699 89.459 0.000 0.000 0.000 0.000 98.158 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 6 0.167 1.328 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 6 0.167 1.313 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 6 0.167 1.592 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5188
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5277
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3941
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.056
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.890
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.056
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.890
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
39 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
40 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
41 0 21.361010 0.87247630E-01 5.4456762  
42 6 0.22034119E-07 0.34186667E-09 0.51028043E-08 -0.99966795E-13
43 5 -0.15575685E-03 0.30726149E-05 -0.80471308E-04 0.50596976E-08
44 4 0.25098773 0.15612093E-02 0.84928613E-01 -0.27863917E-04
45 3 -6.4488769 0.50236036E-01 -2.0965073 0.25009644E-01
46 2 38.172500 0.18459162 14.265034 -0.30329881
47 1 -78.474946 0.85697261E-01 -28.243456 1.0344939
48 0 46.824353 0.17727373E-02 16.313943  
49 6 0.22220471E-07 0.33897870E-09 0.51439591E-08 -0.10094351E-12
50 5 -0.15674173E-03 0.30417725E-05 -0.80970714E-04 0.51000978E-08
51 4 0.25219758 0.15433791E-02 0.85360851E-01 -0.28028645E-04
52 3 -6.4729780 0.49601353E-01 -2.1036496 0.25127351E-01
53 2 38.252148 0.18206636 14.294681 -0.30418501
54 1 -78.536155 0.84448529E-01 -28.270134 1.0357980
55 0 46.824353 0.17453530E-02 16.313230  
56 6 0.18845480E-07 0.38509844E-09 0.43982754E-08 -0.83379515E-13
57 5 -0.13867918E-03 0.35672754E-05 -0.71780061E-04 0.43666335E-08
58 4 0.22968634 0.18605187E-02 0.77334699E-01 -0.24995801E-04
59 3 -6.0237384 0.61253070E-01 -1.9705638 0.22935651E-01
60 2 36.766583 0.22953206 13.740229 -0.28766105
61 1 -77.393480 0.10834582 -27.770672 1.0114547
62 0 46.824361 0.22782066E-02 16.327018  
63 7 -0.13059908E-08 -0.16504735E-15 0.90649122E-14 -0.12541312E-15
64 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
65 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
66 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
67 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
68 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
69 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
70 0 0.32650513 0.16166393E-04 60.838472  
71 7 -0.12346633E-08 -0.14425327E-15 0.91357699E-14 -0.10087110E-15
72 6 0.94177090E-05 0.64929528E-08 0.31789869E-02 -0.26668006E-04
73 5 -0.68205191E-03 0.38502154E-05 -0.22310594 0.19506899E-02
74 4 0.15716902E-01 0.17535208E-03 4.8192406 -0.45165923E-01
75 3 -0.13809356 0.13952366E-02 -37.963195 0.39801023
76 2 0.49043520 0.23220647E-02 116.37063 -1.4164235
77 1 -0.70792287 0.70803996E-03 -143.84059 2.0479434
78 0 0.34515858 0.17069463E-04 60.838472  
79 7 -0.13059908E-08 -0.16504702E-15 0.90649122E-14 -0.12541312E-15
80 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
81 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
82 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
83 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
84 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
85 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
86 0 0.32650513 0.16166393E-04 60.838472  
87 7 -0.12345751E-08 -0.14398051E-15 0.92894684E-14 -0.10085648E-15
88 6 0.94183649E-05 0.64934092E-08 0.31789851E-02 -0.26667991E-04
89 5 -0.68209995E-03 0.38504865E-05 -0.22310583 0.19506890E-02
90 4 0.15718012E-01 0.17536444E-03 4.8192388 -0.45165906E-01
91 3 -0.13810332 0.13953351E-02 -37.963185 0.39801012
92 2 0.49046985 0.23222288E-02 116.37061 -1.4164232
93 1 -0.70797289 0.70809005E-03 -143.84058 2.0479432
94 0 0.34518296 0.17070678E-04 60.838472  
95 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
96 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
97 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
98 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
99 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
100 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
101 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
102 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
103 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.498_SHGC_EAST_0.22 35 1 VerySmooth 2.831 2.831 1.000 0.221    
2 WINDOW_U_0.498_SHGC_SOUTH_0.22 36 1 VerySmooth 2.831 2.831 1.000 0.221    
3 WINDOW_U_0.498_SHGC_WEST_0.22 37 1 VerySmooth 2.831 2.831 1.000 0.221    
4 WINDOW_U_0.498_SHGC_NORTH_0.22 38 1 VerySmooth 2.831 2.831 1.000 0.221    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.00974E-002 0.13126 0.64120 0.64120 0.24200 0.16318 0.24318 0.00000 0.84000 0.84000 0.10990 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.00974E-002 0.13126 0.64120 0.64120 0.24200 0.16318 0.24318 0.00000 0.84000 0.84000 0.10990 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.00974E-002 0.13126 0.64120 0.64120 0.24200 0.16318 0.24318 0.00000 0.84000 0.84000 0.10990 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.00974E-002 0.13126 0.64120 0.64120 0.24200 0.16318 0.24318 0.00000 0.84000 0.84000 0.10990 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1.043 5.030E-003 7.407E-003 6.602 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5151E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5504E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5650E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5946E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8809E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.9014E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.5694E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.5839E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.7301E-002
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4151E-002
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9015E-002
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3591E-002
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.0132E-002
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8570E-002
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8227E-002
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0568E-002
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5144E-003
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5480E-003
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5642E-003
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5920E-003
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8801E-003
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8991E-003
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.5692E-003
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.5837E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4422E-002
26 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9838E-002
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0539E-002
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7301E-002
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0085E-002
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5052E-002
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3172E-002
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5628E-002
33 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3363E-004
34 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3480E-004
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0516E-004
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0602E-004
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8640E-004
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8671E-004
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9989E-004
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0039E-004
41 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4102E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4402E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0796E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1031E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7720E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7851E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5692E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5837E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1729E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1842E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7295E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.3048E-003
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4477E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.1282E-003
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8227E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0568E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4106E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4408E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0800E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1039E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7725E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7867E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5694E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5839E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6562E-002
66 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.0762E-002
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3007E-002
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8363E-002
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2424E-002
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.6059E-002
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3172E-002
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.5628E-002
73 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4829E-004
74 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5023E-004
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2232E-004
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2412E-004
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0190E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0301E-004
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9990E-004
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0040E-004
81 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.2017E-002
82 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.1440E-002
83 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.3542E-002
84 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.0976E-002
85 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.5016E-002
86 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.4995E-002
87 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.2209E-002
88 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.5024E-002
89 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.3378E-002
90 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9246E-002
91 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 2.9688E-002
92 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.6822E-002
93 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 2.9475E-002
94 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4696E-002
95 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.2554E-002
96 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.5255E-002
97 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.5150E-002
98 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5940E-002
99 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.0404E-002
100 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2929E-002
101 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.7450E-002
102 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 9.3584E-003
103 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.2209E-002
104 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5024E-002
105 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.5459E-002
106 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0131E-002
107 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.2087E-002
108 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.7837E-002
109 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.1751E-002
110 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5660E-002
111 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.2554E-002
112 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5255E-002
113 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.2013E-002
114 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.1437E-002
115 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.3537E-002
116 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.0973E-002
117 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.5011E-002
118 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.4992E-002
119 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.2206E-002
120 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.5023E-002
121 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.3377E-002
122 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9245E-002
123 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 2.9687E-002
124 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.6821E-002
125 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 2.9473E-002
126 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4695E-002
127 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.2551E-002
128 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.5253E-002
129 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.5150E-002
130 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5939E-002
131 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.0404E-002
132 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2928E-002
133 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.7448E-002
134 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 9.3576E-003
135 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.2206E-002
136 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5023E-002
137 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.5458E-002
138 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0129E-002
139 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.2086E-002
140 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.7836E-002
141 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.1749E-002
142 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5658E-002
143 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.2551E-002
144 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5253E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 36676.00154 36676.00154 2.64328 2.64328 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 28.91000 1.71462E-002 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 0.42469   00:10:00 20.10000 1.47983E-002 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 29736.02684 29736.02684 2.14118 2.14118 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 28.91000 1.71462E-002 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 1193.16458 1193.16458 5.07789E-002 0.42469 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 31415.62866 31415.62866 2.28361 2.28361 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:50:00 35.20000 1.71581E-002 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 4642.35298 4642.35298 0.19517 0.42469 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 10127.26038 10127.26038 0.73619 0.73619 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 34.94500 1.71577E-002 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 1564.10466 1564.10466 6.56725E-002 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 9103.00834 9103.00834 0.66173 0.66173 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:40:00 31.48833 1.71511E-002 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 1016.21475 1016.21475 4.26717E-002 5.66790E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 9861.46025 9861.46025 0.71686 0.71686 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:50:00 35.20000 1.71581E-002 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 1614.05613 1614.05613 6.77360E-002 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 10499.10466 10499.10466 0.76321 0.76321 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:10:00 34.57667 1.71570E-002 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 1016.17958 1016.17958 4.26702E-002 5.66753E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 8740.17333 8740.17333 0.63534 0.63534 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 34.94500 1.71577E-002 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 119.08292 119.08292 5.09483E-003 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 8268.24852 8268.24852 0.60103 0.60103 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:40:00 31.48833 1.71511E-002 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 90.87925 90.87925 3.88682E-003 5.66790E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 8491.19484 8491.19484 0.61724 0.61724 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:30:00 35.20000 1.71581E-002 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 153.03864 153.03864 6.54392E-003 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 8887.40564 8887.40564 0.64604 0.64604 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:30:00 34.35000 1.71565E-002 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 90.87728 90.87728 3.88674E-003 5.66753E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 8826.95174 8826.95174 0.64166 0.64166 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 34.94500 1.71577E-002 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 825.01981 825.01981 3.48917E-002 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 8771.10532 8771.10532 0.63760 0.63760 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:30:00 31.24750 1.71506E-002 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 546.76166 546.76166 2.31211E-002 5.66790E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 8588.99262 8588.99262 0.62436 0.62436 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 35.20000 1.71581E-002 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 868.21664 868.21664 3.66992E-002 8.95286E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 9529.46928 9529.46928 0.69272 0.69272 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:10:00 34.57667 1.71570E-002 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 546.75108 546.75108 2.31207E-002 5.66753E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20.10000 1.47983E-002 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 80068.88 4.73252 4.73252 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 0.00 0.00000 0.00000   00:00:00
3 PACU_VAV_MID Cooling Sensible 73620.29 4.26797 4.26797 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 00:00:00
4 PACU_VAV_MID Heating Sensible 0.00 0.00000 0.00000   00:00:00
5 PACU_VAV_TOP Cooling Sensible 82990.35 4.95627 4.95627 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 0.00 0.00000 0.00000   00:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.64328
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28353
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29100
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.76919
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75609
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34376E-003
8 Coil:Heating:Electric CORE_BOTTOM VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 25678.07203
9 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.14118
10 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35002
11 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34900
12 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74727
13 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.93339
14 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08851E-003
16 Coil:Heating:Electric CORE_MID VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 24946.24101
17 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.28361
18 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32819
19 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34100
20 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.77871
21 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87517
22 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
23 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.16092E-003
24 Coil:Heating:Electric CORE_TOP VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 25995.82988
25 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.73619
26 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21461
27 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22300
28 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16417
29 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57229
30 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
31 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.77533E-003
32 Coil:Heating:Electric PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5480.48574
33 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.66173
34 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15115
35 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
36 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13235
37 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40307
38 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.52064E-003
40 Coil:Heating:Electric PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4418.10798
41 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.71686
42 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22039
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22900
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16416
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58771
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.72873E-003
48 Coil:Heating:Electric PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5480.23548
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.76321
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13105
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15264
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34945
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90740E-003
56 Coil:Heating:Electric PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5095.68191
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.63534
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24867
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25500
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16201
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66313
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.53213E-003
64 Coil:Heating:Electric PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5408.44169
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.60103
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16642
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12021
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44378
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28943E-003
72 Coil:Heating:Electric PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4012.85775
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.61724
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25596
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26300
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16233
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68257
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.48849E-003
80 Coil:Heating:Electric PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5419.22013
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.64604
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15481
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12921
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41284
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.46103E-003
88 Coil:Heating:Electric PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4313.34816
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.64166
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24622
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24600
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15785
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65660
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54737E-003
96 Coil:Heating:Electric PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5269.44894
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.63760
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15687
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12752
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41833
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42871E-003
104 Coil:Heating:Electric PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4256.98068
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.62436
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25305
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25200
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15734
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67479
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.50566E-003
112 Coil:Heating:Electric PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 5252.45540
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69272
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14438
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13854
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38501
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.63887E-003
120 Coil:Heating:Electric PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 4625.04205
121 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.57146
122 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.34295
123 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 5.14293
124 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.34295
125 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.73252
126 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.73252
127 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
128 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.28377
129 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.36876
130 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.32852
131 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.73751
132 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.32852
133 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.26797
134 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.26797
135 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
136 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.31128
137 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.58080
138 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.39203
139 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.16161
140 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 1.39203
141 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 4.95627
142 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 4.95627
143 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
144 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.28086
145 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.73252
146 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.26797
147 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 4.95627
148 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.73252
149 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.73252
150 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 117519.72991
151 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.70108
152 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.57735
153 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 39169.32598
154 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.70108
155 Coil:Heating:Electric PACU_VAV_BOT HEATING COIL Design Size Nominal Capacity [W] 21979.05198
156 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.73252
157 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.26797
158 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.26797
159 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 105983.92869
160 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.70108
161 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.42252
162 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 35324.44343
163 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.70108
164 Coil:Heating:Electric PACU_VAV_MID HEATING COIL Design Size Nominal Capacity [W] 19821.57617
165 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.26797
166 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.95627
167 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.95627
168 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 123076.04150
169 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.70108
170 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.65193
171 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 41021.24463
172 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.70108
173 Coil:Heating:Electric PACU_VAV_TOP HEATING COIL Design Size Nominal Capacity [W] 23018.21759
174 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 4.95627
175 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
176 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
177 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
178 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
179 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 117327.79 400339.04 12.53 3.21 3.59 3.79 3.92 10.94 12.25 12.92 13.38 5.4711 4.3310 2.9145 1.2563
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 105810.83 361041.54 12.53 3.21 3.59 3.79 3.92 10.94 12.25 12.92 13.38 4.9340 3.9059 2.6284 1.1330
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 122875.03 419267.00 12.53 3.21 3.59 3.79 3.92 10.94 12.25 12.92 13.38 5.7298 4.5358 3.0523 1.3157


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.22 N/A 2.831 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.22 N/A 2.831 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.22 N/A 2.831 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.592 1.286   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.22 N/A 2.831 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.22 N/A 2.831 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.22 N/A 2.831 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.22 N/A 2.831 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.22 N/A 2.831 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.22 N/A 2.831 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.337 0.312   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.22 N/A 2.831 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.22 N/A 2.831 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.22 N/A 2.831 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.328 1.108   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.22 N/A 2.831 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.22 N/A 2.831 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.337 0.312   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_NORTH_0.22 N/A 2.831 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_EAST_0.22 N/A 2.831 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_SOUTH_0.22 N/A 2.831 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.313 1.097   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.498_SHGC_WEST_0.22 N/A 2.831 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.4294586873 0.3133492927 Pass Pass 0.1979197276 0.3981851509 Pass Fail
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.4370041298E-002 8.2347363675E-002 Pass Pass 0.2005679751 0.4789946310 Fail Fail
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.4247188548E-002 5.8276928899E-002 Pass Pass 0.2560344171 0.8899610622 Fail Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.6239154846E-002 5.0708525392E-002 Pass Pass 0.2876923829 0.9064326427 Fail Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 0.2204266976 0.2714286034 Pass Pass 0.1792615533 0.3894641578 Pass Fail
6 CORE_TOP RunPeriod: RUNPERIOD 1 0.2199495867 0.2864760532 Pass Pass 0.1764797523 0.3802165681 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2160218252 0.2941134117 Pass Pass 0.1761975155 0.3795473751 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2639085258 0.3695604556 Pass Pass 0.1795819038 0.3831636425 Pass Fail
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2220570796 0.3201596695 Pass Pass 0.1910723794 0.4070875134 Pass Fail
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2896093375 0.4001483197 Pass Pass 0.1774829465 0.3798940014 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.3623402431 0.2831178312 Pass Fail 0.1935119597 0.3923917641 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.4113025960 0.3265167590 Pass Fail 0.1957765205 0.3942002832 Pass Fail
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.3718966191 0.3011855704 Pass Fail 0.2110641847 0.4294730968 Pass Fail
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.4294386404 0.3459082032 Pass Fail 0.1930592449 0.3905249409 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.2164492318 0.2787644414 Pass Pass 0.1716943521 0.3759862249 Pass Fail
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2634076373 0.3487945494 Pass Pass 0.1849541430 0.4009896795 Pass Fail
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2212716642 0.2951033567 Pass Pass 0.1904765924 0.4188004054 Pass Fail
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2800409873 0.3645800750 Pass Pass 0.1719508427 0.3750282041 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3160.20 -130.7 0.00 -2155.5 4766.22 5640.28



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 20.10 0.00 20.10 Wetbulb [C] 1.80 0.00
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 35.20 8.50 25.80 Wetbulb [C] 4.10 160.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 57.00 12      
Feb 0.00 0      
Mar 153.60 31      
Apr 87.00 59      
May 227.22 128      
Jun 144.58 109      
Jul 42.40 24      
Aug 164.90 163      
Sep 119.60 50      
Oct 365.70 188      
Nov 70.90 67      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.286 1.592 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.286 1.592 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.286 1.592 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.286 1.592 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.097 1.313 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.097 1.313 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.097 1.313 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.097 1.313 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.108 1.328 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.108 1.328 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.108 1.328 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.108 1.328 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.286 1.592 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.286 1.592 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.286 1.592 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.286 1.592 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.108 1.328 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.108 1.328 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.320 0.337 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.108 1.328 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.108 1.328 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.320 0.337 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.097 1.313 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.097 1.313 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.097 1.313 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.097 1.313 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.498_SHGC_NORTH_0.22   65.26 0.00 0.00 65.26 65.26 2.831 0.221 0.243             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.498_SHGC_EAST_0.22   43.51 0.00 0.00 43.51 43.51 2.831 0.221 0.243             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.498_SHGC_SOUTH_0.22   65.26 0.00 0.00 65.26 65.26 2.831 0.221 0.243             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.498_SHGC_WEST_0.22   43.51 0.00 0.00 43.51 43.51 2.831 0.221 0.243             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.498_SHGC_NORTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.498_SHGC_NORTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.498_SHGC_NORTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.498_SHGC_EAST_0.22   41.85 0.00 0.00 41.85 41.85 2.831 0.221 0.243             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.498_SHGC_EAST_0.22   1.65 0.00 0.00 1.65 1.65 2.831 0.221 0.243             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.498_SHGC_SOUTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.498_SHGC_SOUTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.498_SHGC_SOUTH_0.22   21.75 0.00 0.00 21.75 21.75 2.831 0.221 0.243             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.498_SHGC_WEST_0.22   41.85 0.00 0.00 41.85 41.85 2.831 0.221 0.243             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.498_SHGC_WEST_0.22   1.65 0.00 0.00 1.65 1.65 2.831 0.221 0.243             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.498_SHGC_NORTH_0.22   65.26 0.00 0.00 65.26 65.26 2.831 0.221 0.243             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.498_SHGC_EAST_0.22   43.51 0.00 0.00 43.51 43.51 2.831 0.221 0.243             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.498_SHGC_SOUTH_0.22   65.26 0.00 0.00 65.26 65.26 2.831 0.221 0.243             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.498_SHGC_WEST_0.22   43.51 0.00 0.00 43.51 43.51 2.831 0.221 0.243             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.831 0.221 0.243                      
North Total or Average             195.79 2.831 0.221 0.243                      
Non-North Total or Average             456.84 2.831 0.221 0.243                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 1.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.34 0.0000 Y 8.58
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.51 0.0000 Y 5.47
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.22 0.0000 Y 8.54
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.21 0.0000 Y 5.40
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.29 0.0000 Y 8.56
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.45 0.0000 Y 5.46
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.17 0.0000 Y 8.52
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.16 0.0000 Y 5.39
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.34 0.0000 Y 8.58
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.51 0.0000 Y 5.47
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.22 0.0000 Y 8.54
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.21 0.0000 Y 5.40
Interior Lighting Total       8.6994 4982.19 43341.88               299.70


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   41.93 41.93 4.44
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.83 62.88 4.81
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.83 45.49 40.26
Exterior Lighting Total 5686.19           49.51



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   117519.73 82391.11 35128.62 0.70 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   105983.93 74303.55 31680.37 0.70 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   123076.04 86286.55 36789.49 0.70 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   117327.8 3.21 10.94 N/A N/A 12.53
PACU_VAV_MID COOLING COIL   105810.8 3.21 10.94 N/A N/A 12.53
PACU_VAV_TOP COOLING COIL   122875.0 3.21 10.94 N/A N/A 12.53
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric   25678.07 1.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric   24946.24 1.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric   25995.83 1.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   5480.49 1.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   4418.11 1.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   5480.24 1.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   5095.68 1.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   5408.44 1.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   4012.86 1.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   5419.22 1.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   4313.35 1.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   5269.45 1.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   4256.98 1.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   5252.46 1.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   4625.04 1.00
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric   21979.05 1.00
PACU_VAV_MID HEATING COIL Coil:Heating:Electric   19821.58 1.00
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric   23018.22 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.73 10359.54 2189.01 1.00 1.14 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 4.27 9342.64 2189.01 1.00 1.14 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:50:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 4.96 10849.33 2189.01 1.00 1.13 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 117327.79 3.21 10.94 12.53 5.4711 3.59 12.25 4.3310 3.79 12.92 2.9145 3.92 13.38 1.2563
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 105810.83 3.21 10.94 12.53 4.9340 3.59 12.25 3.9059 3.79 12.92 2.6284 3.92 13.38 1.1330
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 122875.03 3.21 10.94 12.53 5.7298 3.59 12.25 4.5358 3.79 12.92 3.0523 3.92 13.38 1.3157
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 36676.00 36676.00 37.29 2.643 2.643 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 24.00 24.00 0.00883 28.91 0.01715 0.425 0.00
CORE_MID 29736.03 29736.03 30.23 2.141 2.141 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 08:00:00 24.00 24.00 0.00891 28.91 0.01715 0.425 0.00
CORE_TOP 31415.63 31415.63 31.94 2.284 2.284 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:50:00 24.00 24.00 0.00888 35.20 0.01716 0.425 0.00
PERIMETER_TOP_ZN_3 10127.26 10127.26 48.84 0.736 0.736 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 24.00 24.00 0.00890 34.95 0.01716 0.090 0.00
PERIMETER_TOP_ZN_2 9103.01 9103.01 69.35 0.662 0.662 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:40:00 24.00 24.00 0.00879 31.49 0.01715 0.057 0.00
PERIMETER_TOP_ZN_1 9861.46 9861.46 47.56 0.717 0.717 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:50:00 24.00 24.00 0.00891 35.20 0.01716 0.090 0.00
PERIMETER_TOP_ZN_4 10499.10 10499.10 79.99 0.763 0.763 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:10:00 24.00 24.00 0.00875 34.58 0.01716 0.057 0.00
PERIMETER_BOT_ZN_3 8740.17 8740.17 42.15 0.635 0.635 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 24.00 24.00 0.00888 34.95 0.01716 0.090 0.00
PERIMETER_BOT_ZN_2 8268.25 8268.25 62.99 0.601 0.601 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:40:00 24.00 24.00 0.00876 31.49 0.01715 0.057 0.00
PERIMETER_BOT_ZN_1 8491.19 8491.19 40.95 0.617 0.617 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:30:00 24.00 24.00 0.00889 35.20 0.01716 0.090 0.00
PERIMETER_BOT_ZN_4 8887.41 8887.41 67.71 0.646 0.646 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:30:00 24.00 24.00 0.00874 34.35 0.01716 0.057 0.00
PERIMETER_MID_ZN_3 8826.95 8826.95 42.57 0.642 0.642 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 24.00 24.00 0.00893 34.95 0.01716 0.090 0.00
PERIMETER_MID_ZN_2 8771.11 8771.11 66.82 0.638 0.638 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 09:30:00 24.00 24.00 0.00878 31.25 0.01715 0.057 0.00
PERIMETER_MID_ZN_1 8588.99 8588.99 41.43 0.624 0.624 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 14:40:00 24.00 24.00 0.00894 35.20 0.01716 0.090 0.00
PERIMETER_MID_ZN_4 9529.47 9529.47 72.60 0.693 0.693 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:10:00 24.00 24.00 0.00875 34.58 0.01716 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 0.00 0.00 0.00 0.000 0.425   00:10:00 15.60 22.19 0.01480 20.10 0.01480 0.425 0.00
CORE_MID 1193.16 1193.16 1.21 0.051 0.425 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 20.10 0.01480 0.425 0.00
CORE_TOP 4642.35 4642.35 4.72 0.195 0.425 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 20.10 0.01480 0.425 0.00
PERIMETER_TOP_ZN_3 1564.10 1564.10 7.54 0.066 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01000 20.10 0.01480 0.090 0.00
PERIMETER_TOP_ZN_2 1016.21 1016.21 7.74 0.043 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01005 20.10 0.01480 0.057 0.00
PERIMETER_TOP_ZN_1 1614.06 1614.06 7.78 0.068 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00997 20.10 0.01480 0.090 0.00
PERIMETER_TOP_ZN_4 1016.18 1016.18 7.74 0.043 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01005 20.10 0.01480 0.057 0.00
PERIMETER_BOT_ZN_3 119.08 119.08 0.57 0.005 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01211 20.10 0.01480 0.090 0.00
PERIMETER_BOT_ZN_2 90.88 90.88 0.69 0.004 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01190 20.10 0.01480 0.057 0.00
PERIMETER_BOT_ZN_1 153.04 153.04 0.74 0.007 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01170 20.10 0.01480 0.090 0.00
PERIMETER_BOT_ZN_4 90.88 90.88 0.69 0.004 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01190 20.10 0.01480 0.057 0.00
PERIMETER_MID_ZN_3 825.02 825.02 3.98 0.035 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01031 20.10 0.01480 0.090 0.00
PERIMETER_MID_ZN_2 546.76 546.76 4.17 0.023 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01034 20.10 0.01480 0.057 0.00
PERIMETER_MID_ZN_1 868.22 868.22 4.19 0.037 0.090 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01025 20.10 0.01480 0.090 0.00
PERIMETER_MID_ZN_4 546.75 546.75 4.17 0.023 0.057 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.01034 20.10 0.01480 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.73 4.73 0.00 0.00 4.7325 1.3430 4.7325 0.2838 0.3000
PACU_VAV_MID 4.27 4.27 0.00 0.00 4.2680 1.3285 4.2680 0.3113 0.3000
PACU_VAV_TOP 4.96 4.96 0.00 0.00 4.9563 1.3920 4.9563 0.2809 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 25678.072 25678.072 -999.0 -999.0 -999.000   12/21 00:10:00   12/21 00:10:00 25678.07 14177.50 0.424691 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.00800000 51.6928 0.00 0.00 -999.00 -999.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 24946.241 24946.241 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24946.24 14177.50 0.424691 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.00800451 51.7216 1193.16 0.00 -999.00 -999.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 25995.830 25995.830 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 25995.83 14177.50 0.424691 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.00800000 51.6928 4642.35 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 5480.486 5480.486 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5480.49 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.00999685 64.3858 1564.10 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 4418.108 4418.108 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4418.11 1892.12 0.056679 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01004882 64.7148 1016.21 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 5480.235 5480.235 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5480.24 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.00996540 64.1863 1614.06 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 5095.682 5095.682 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5095.68 1892.00 0.056675 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01004888 64.7152 1016.18 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 5408.442 5408.442 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5408.44 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01211319 77.7618 119.08 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 4012.858 4012.858 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4012.86 1892.12 0.056679 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01189539 76.3897 90.88 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 5419.220 5419.220 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5419.22 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01170008 75.1586 153.04 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 4313.348 4313.348 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4313.35 1892.00 0.056675 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01189543 76.3900 90.88 0.00 -999.00 -999.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 5269.449 5269.449 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5269.45 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01030686 66.3525 825.02 0.00 -999.00 -999.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 4256.981 4256.981 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4256.98 1892.12 0.056679 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01034308 66.5817 546.76 0.00 -999.00 -999.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 5252.455 5252.455 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5252.46 2988.74 0.089529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01025180 66.0037 868.22 0.00 -999.00 -999.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 4625.042 4625.042 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4625.04 1892.00 0.056675 12.80 11.59 0.00800000 40.00 21.18 0.00800000 20.10 0.01479830 20.10 0.0000 21.00 0.01034314 66.5820 546.75 0.00 -999.00 -999.00
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 117519.730 82391.111 4.732520 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 120568.04 85947.01 4.732520 26.84 19.33 0.01095729 11.03 11.03 0.00850000 35.20 0.01715815 25.83 25.2544 24.00 0.00885251 47.6084 64880.70 0.00 121178.62 83827.32
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_BOT 21979.052 21979.052 -999.0 -999.0 -999.000   unknown unknown unknown 21979.05 21979.05 1.419756 0.00 -6.26 0.00000000 12.80 11.59 0.00800000 0.00 0.00000000 -6.26 84.1814 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 105983.929 74303.554 4.267973 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:50:00 109702.94 76181.56 4.267973 27.13 19.63 0.01123435 11.03 11.03 0.00850000 35.12 0.01715799 25.81 28.0032 24.00 0.00891621 47.9465 58455.45 0.00 109283.66 75598.78
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_MID 19821.576 19821.576 -999.0 -999.0 -999.000   unknown unknown unknown 19821.58 19821.58 1.280392 0.00 -6.26 0.00000000 12.80 11.59 0.00800000 0.00 0.00000000 -6.26 93.3441 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 123076.042 86286.547 4.956272 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 125971.37 90421.98 4.956272 26.69 19.22 0.01087500 11.03 11.03 0.00850000 35.12 0.01715799 25.81 24.1143 24.00 0.00887034 47.7034 67972.64 0.00 126907.92 87790.66
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_TOP 23018.218 23018.218 -999.0 -999.0 -999.000   unknown unknown unknown 23018.22 23018.22 1.486882 0.00 -6.26 0.00000000 12.80 11.59 0.00800000 0.00 0.00000000 -6.26 80.3810 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes No unknown No 25678.072 25678.072 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 25678.07 14177.50 1.0000 0.51115607 0.424691 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 25678.07 20.10 0.01479830 20.10 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6928 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes No unknown No 24946.241 24946.241 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24946.24 14177.50 1.0000 0.51115607 0.424691 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24946.24 20.10 0.01479830 20.10 0.00000000 0.0000 20.87 0.00800451 21.00 0.00800451 51.7216 1193.16 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes No unknown No 25995.830 25995.830 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 25995.83 14177.50 1.0000 0.51115607 0.424691 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 25995.83 20.10 0.01479830 20.10 0.00000000 0.0000 20.70 0.00800000 21.00 0.00800000 51.6928 4642.35 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes No unknown No 5480.486 5480.486 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5480.49 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5480.49 20.10 0.01479830 20.10 0.00000000 0.0000 20.57 0.00999685 21.00 0.00999685 64.3858 1564.10 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes No unknown No 4418.108 4418.108 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4418.11 1892.12 1.0000 0.06821858 0.056679 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4418.11 20.10 0.01479830 20.10 0.00000000 0.0000 20.57 0.01004882 21.00 0.01004882 64.7148 1016.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes No unknown No 5480.235 5480.235 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5480.24 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5480.24 20.10 0.01479830 20.10 0.00000000 0.0000 20.56 0.00996540 21.00 0.00996540 64.1863 1614.06 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes No unknown No 5095.682 5095.682 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5095.68 1892.00 1.0000 0.06821410 0.056675 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5095.68 20.10 0.01479830 20.10 0.00000000 0.0000 20.57 0.01004888 21.00 0.01004888 64.7152 1016.18 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes No unknown No 5408.442 5408.442 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5408.44 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5408.44 20.10 0.01479830 20.10 0.00000000 0.0000 20.97 0.01211319 21.00 0.01211319 77.7618 119.08 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes No unknown No 4012.858 4012.858 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4012.86 1892.12 1.0000 0.06821858 0.056679 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4012.86 20.10 0.01479830 20.10 0.00000000 0.0000 20.96 0.01189539 21.00 0.01189539 76.3897 90.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes No unknown No 5419.220 5419.220 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5419.22 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5419.22 20.10 0.01479830 20.10 0.00000000 0.0000 20.96 0.01170008 21.00 0.01170008 75.1586 153.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes No unknown No 4313.348 4313.348 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4313.35 1892.00 1.0000 0.06821410 0.056675 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4313.35 20.10 0.01479830 20.10 0.00000000 0.0000 20.96 0.01189543 21.00 0.01189543 76.3900 90.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes No unknown No 5269.449 5269.449 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5269.45 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5269.45 20.10 0.01479830 20.10 0.00000000 0.0000 20.76 0.01030686 21.00 0.01030686 66.3525 825.02 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes No unknown No 4256.981 4256.981 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4256.98 1892.12 1.0000 0.06821858 0.056679 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4256.98 20.10 0.01479830 20.10 0.00000000 0.0000 20.76 0.01034308 21.00 0.01034308 66.5817 546.76 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes No unknown No 5252.455 5252.455 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5252.46 2988.74 1.0000 0.10775618 0.089529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5252.46 20.10 0.01479830 20.10 0.00000000 0.0000 20.75 0.01025180 21.00 0.01025180 66.0037 868.22 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes No unknown No 4625.042 4625.042 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4625.04 1892.00 1.0000 0.06821410 0.056675 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4625.04 20.10 0.01479830 20.10 0.00000000 0.0000 20.76 0.01034314 21.00 0.01034314 66.5820 546.75 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 117519.730 82391.111 4.732520 -999.0 -999.000 -999.0000 1.00000 0.98012 1025.2090 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.732520 5.69603675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 Sensible 120568.04 85947.01 1.0259 5.69603675 4.732520 26.84 19.33 0.01095729 54917.3 11.03 11.03 0.00850000 32511.6 -999.0 -999.00 -999.00 -999.00 10359.537 110208.50 35.20 0.01715815 25.83 1.19517000 25.2544 24.00 0.00885251 24.00 0.00885251 47.6084 64880.70 0.00 121178.62 83827.32 5.47108636 26.67 19.44 0.01118466 55322.4 11.65 11.63 0.00850793 33173.5
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 21979.052 21979.052 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_BOT FAN Fan:VariableVolume 4.732520 5.69603675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   unknown unknown unknown unknown unknown Sensible 21979.05 21979.05 1.0000 1.70881102 1.419756 0.00 -6.26 0.00000000 25.0 12.80 11.59 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 21979.05 0.00 0.00000000 -6.26 1.19517000 84.1814 0.00 0.00000000 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 105983.929 74303.554 4.267973 -999.0 -999.000 -999.0000 1.00000 0.94790 1025.7241 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.267973 5.13691065   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:50:00 Sensible 109702.94 76181.56 1.0351 5.13691065 4.267973 27.13 19.63 0.01123435 55919.4 11.03 11.03 0.00850000 32512.5 -999.0 -999.00 -999.00 -999.00 9342.639 100360.30 35.12 0.01715799 25.81 1.19517000 28.0032 24.00 0.00891621 24.00 0.00891621 47.9465 58455.45 0.00 109283.66 75598.78 4.93404152 26.67 19.44 0.01118466 55322.4 11.65 11.63 0.00850793 33173.5
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 19821.576 19821.576 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_MID FAN Fan:VariableVolume 4.267973 5.13691065   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   unknown unknown unknown unknown unknown Sensible 19821.58 19821.58 1.0000 1.54107320 1.280392 0.00 -6.26 0.00000000 25.0 12.80 11.59 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 19821.58 0.00 0.00000000 -6.26 1.19517000 93.3441 0.00 0.00000000 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 123076.042 86286.547 4.956272 -999.0 -999.000 -999.0000 1.00000 0.99331 1025.0561 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 4.956272 5.96534434   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 Sensible 125971.37 90421.98 1.0235 5.96534434 4.956272 26.69 19.22 0.01087500 54553.8 11.03 11.03 0.00850000 32511.3 -999.0 -999.00 -999.00 -999.00 10849.334 115122.03 35.12 0.01715799 25.81 1.19517000 24.1143 24.00 0.00887034 24.00 0.00887034 47.7034 67972.64 0.00 126907.92 87790.66 5.72975833 26.67 19.44 0.01118466 55322.4 11.65 11.63 0.00850793 33173.5
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 23018.218 23018.218 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PACU_VAV_TOP FAN Fan:VariableVolume 4.956272 5.96534434   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0   unknown unknown unknown unknown unknown Sensible 23018.22 23018.22 1.0000 1.78960330 1.486882 0.00 -6.26 0.00000000 25.0 12.80 11.59 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 23018.22 0.00 0.00000000 -6.26 1.19517000 80.3810 0.00 0.00000000 -999.00 -999.0 -999.0000 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 5943.00 0.00 0.00
CORE_MID 5427.00 1.83 0.00
CORE_TOP 5233.00 19.33 0.00
PERIMETER_TOP_ZN_3 5721.33 393.67 369.33
PERIMETER_TOP_ZN_2 5689.50 563.67 546.50
PERIMETER_TOP_ZN_1 5820.67 497.83 495.00
PERIMETER_TOP_ZN_4 5357.17 518.50 389.50
PERIMETER_BOT_ZN_3 5933.17 110.50 110.50
PERIMETER_BOT_ZN_2 5941.50 332.50 332.50
PERIMETER_BOT_ZN_1 5942.00 1695.17 1695.17
PERIMETER_BOT_ZN_4 5932.33 241.50 241.50
PERIMETER_MID_ZN_3 5878.67 221.33 219.50
PERIMETER_MID_ZN_2 4899.00 403.17 402.50
PERIMETER_MID_ZN_1 5921.17 357.67 357.67
PERIMETER_MID_ZN_4 5656.67 321.67 310.50
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 2244.83 2150.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 0.00 2.33 0.00 0.17
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 39.83 0.00 36.33
PERIMETER_TOP_ZN_2 0.00 79.33 0.00 78.00
PERIMETER_TOP_ZN_1 0.00 74.17 0.00 72.17
PERIMETER_TOP_ZN_4 0.00 59.33 0.00 50.17
PERIMETER_BOT_ZN_3 0.00 13.67 0.00 12.00
PERIMETER_BOT_ZN_2 0.00 54.50 0.00 54.00
PERIMETER_BOT_ZN_1 0.00 666.50 0.00 665.67
PERIMETER_BOT_ZN_4 0.00 49.33 0.00 40.50
PERIMETER_MID_ZN_3 0.00 15.83 0.00 14.17
PERIMETER_MID_ZN_2 0.00 51.83 0.00 51.83
PERIMETER_MID_ZN_1 0.00 75.83 0.00 75.83
PERIMETER_MID_ZN_4 0.00 46.67 0.00 40.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 0.00 823.17 0.00 805.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.49 52.94 2698.04 0.467 0.000 0.000 0.000
CORE_MID 21.49 52.94 2698.04 0.445 0.000 0.000 0.000
CORE_TOP 21.49 52.94 2698.04 0.442 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.53 11.16 568.77 0.626 0.025 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 0.774 0.026 0.000 0.000
PERIMETER_TOP_ZN_1 4.53 11.16 568.77 0.682 0.025 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 0.783 0.026 0.000 0.000
PERIMETER_BOT_ZN_3 4.53 11.16 568.77 0.537 0.013 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 0.656 0.014 0.000 0.000
PERIMETER_BOT_ZN_1 4.53 11.16 568.77 0.675 1.228 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 0.652 0.014 0.000 0.000
PERIMETER_MID_ZN_3 4.53 11.16 568.77 0.633 0.021 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 0.735 0.023 0.000 0.000
PERIMETER_MID_ZN_1 4.53 11.16 568.77 0.689 0.021 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 0.782 0.022 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.49 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.49 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.49 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.51 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.87 7.06 360.05 131.25 0.0000 0.057
Total Facility   108.48 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 7830337.85 0.00 7830337.85 0.00 7830337.85 13393058.27 8017.48 205.77 536.75 371.50
CORE_MID 7241744.38 0.00 7241744.38 0.00 7241744.38 13393058.27 8735.11 6.35 18.54 220.93
CORE_TOP 7206177.61 0.00 7206177.61 0.00 7206177.61 13393058.27 8745.20 4.36 10.44 221.92
PERIMETER_TOP_ZN_3 2119522.17 0.00 2119522.17 148624.63 2268146.80 2823374.22 4810.23 51.67 3898.11 221.92
PERIMETER_TOP_ZN_2 1660017.33 0.00 1660017.33 99082.49 1759099.81 1787429.43 3439.18 1.19 5319.63 221.92
PERIMETER_TOP_ZN_1 2303473.05 0.00 2303473.05 148624.63 2452097.68 2823374.22 4585.37 35.97 4138.66 221.92
PERIMETER_TOP_ZN_4 1689001.18 0.00 1689001.18 99082.49 1788083.67 1787312.18 3465.74 15.95 5278.32 221.92
PERIMETER_BOT_ZN_3 1876091.92 0.00 1876091.92 79023.74 1955115.65 2823374.22 5776.15 265.92 2717.93 371.50
PERIMETER_BOT_ZN_2 1445952.04 0.00 1445952.04 52682.17 1498634.22 1787429.43 3352.73 53.35 5353.91 371.50
PERIMETER_BOT_ZN_1 2319542.03 0.00 2319542.03 4024723.19 6344265.21 2823374.22 4370.46 196.13 4193.41 371.50
PERIMETER_BOT_ZN_4 1447915.79 0.00 1447915.79 52682.17 1500597.97 1787312.18 3680.89 108.93 4970.18 371.50
PERIMETER_MID_ZN_3 2143776.97 0.00 2143776.97 123719.22 2267496.19 2823374.22 4654.23 54.43 4051.34 220.93
PERIMETER_MID_ZN_2 1653487.22 0.00 1653487.22 82478.99 1735966.21 1787429.43 3443.94 2.56 5313.50 1129.93
PERIMETER_MID_ZN_1 2326517.86 0.00 2326517.86 123719.22 2450237.08 2823374.22 4468.90 27.56 4263.55 220.93
PERIMETER_MID_ZN_4 1683703.67 0.00 1683703.67 82478.99 1766182.65 1787312.18 3482.17 15.34 5262.49 220.93
Total Facility 44947261.07 0.00 44947261.07 5116921.93 50064183.00 67843644.98 8760.00 820.40 5653.36 1345.57


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.3393 0.0000 0.3393 0.0000 0.3393 0.4247 5227.75 199.09 516.16
CORE_MID 0.3230 0.0000 0.3230 0.0000 0.3230 0.4247 5922.87 6.18 13.95
CORE_TOP 0.3214 0.0000 0.3214 0.0000 0.3214 0.4247 5931.14 4.15 7.71
PERIMETER_TOP_ZN_3 0.0957 0.0000 0.0957 0.0038 0.0995 0.0895 2005.15 51.33 3886.52
PERIMETER_TOP_ZN_2 0.0750 0.0000 0.0750 0.0025 0.0775 0.0567 842.12 0.80 5100.08
PERIMETER_TOP_ZN_1 0.1044 0.0000 0.1044 0.0038 0.1081 0.0895 1778.70 35.30 4129.00
PERIMETER_TOP_ZN_4 0.0758 0.0000 0.0758 0.0025 0.0783 0.0567 870.01 15.65 5057.34
PERIMETER_BOT_ZN_3 0.0822 0.0000 0.0822 0.0020 0.0842 0.0895 2969.51 262.97 2710.52
PERIMETER_BOT_ZN_2 0.0635 0.0000 0.0635 0.0013 0.0649 0.0567 896.35 50.33 4996.32
PERIMETER_BOT_ZN_1 0.1029 0.0000 0.1029 0.1864 0.2893 0.0895 1577.31 181.85 4183.84
PERIMETER_BOT_ZN_4 0.0632 0.0000 0.0632 0.0013 0.0645 0.0567 1230.52 107.65 4604.83
PERIMETER_MID_ZN_3 0.0969 0.0000 0.0969 0.0031 0.1000 0.0895 1846.43 53.91 4042.66
PERIMETER_MID_ZN_2 0.0712 0.0000 0.0712 0.0022 0.0734 0.0567 844.22 1.30 4188.49
PERIMETER_MID_ZN_1 0.1055 0.0000 0.1055 0.0031 0.1086 0.0895 1660.07 27.24 4255.69
PERIMETER_MID_ZN_4 0.0757 0.0000 0.0757 0.0021 0.0778 0.0567 884.82 15.11 5043.07
Total Facility 1.9957 0.0000 1.9957 0.2142 2.2099 2.1513 5943.00 798.16 5216.79


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 21613496.41 0.00 21613496.41 22614548.33 3274.40 0.00 5485.60 371.50
PACU_VAV_MID 21800938.64 0.00 21800938.64 22614548.33 3434.19 0.00 5325.81 220.93
PACU_VAV_TOP 21698026.36 0.00 21698026.36 22614548.33 3430.62 0.00 5329.38 221.92


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 0.9432 0.0000 0.9432 0.7171 828.89 0.00 5114.11
PACU_VAV_MID 0.9789 0.0000 0.9789 0.7171 838.12 0.00 5104.88
PACU_VAV_TOP 0.9739 0.0000 0.9739 0.7171 835.55 0.00 5107.45


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 0.00 0.00 0.00 0.00 0.00 5485.60 0.00 0.00 0.00
PACU_VAV_MID 0.00 0.00 0.00 0.00 0.00 0.00 5325.81 0.00 0.00 0.00
PACU_VAV_TOP 0.00 0.00 0.00 0.00 0.00 0.00 5329.38 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0961 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.1398 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.1333 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 920
Defaulted Fields 545
Fields with Defaults 2217
Autosized Fields 149
Autosizable Fields 202
Autocalculated Fields 155
Autocalculatable Fields 276



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
Electricity:Building 1019.39 13503.13 18-JUN-17:20 72941.29 18-DEC-17:00
Electricity:Zone:CORE_BOTTOM 322.35 5243.28 01-JAN-00:10 20463.73 02-JAN-08:10
Electricity:SpaceType:GENERAL 1019.39 13503.13 18-JUN-17:20 72941.29 18-DEC-17:00
InteriorLights:Electricity 299.70 1025.38 18-JUN-17:20 31270.78 18-DEC-17:00
InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 299.70 1025.38 18-JUN-17:20 31270.78 18-DEC-17:00
LightsWired:InteriorLights:Electricity 299.70 1025.38 18-JUN-17:20 31270.78 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 299.70 1025.38 18-JUN-17:20 31270.78 18-DEC-17:00
Electricity:Zone:CORE_MID 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:CORE_TOP 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 32.91 422.10 28-MAY-17:10 2620.04 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.58 36.00 01-JAN-09:10 1184.79 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.58 36.00 01-JAN-09:10 1184.79 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_2 20.87 271.65 29-MAY-17:10 1768.58 09-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.47 22.79 01-JAN-07:20 860.01 09-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.47 22.79 01-JAN-07:20 860.01 09-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 32.87 425.61 12-MAR-17:10 2620.03 07-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.54 36.00 01-JAN-08:00 1184.79 07-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.54 36.00 01-JAN-08:00 1184.79 07-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_4 20.81 267.21 12-MAR-17:10 1658.59 18-DEC-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.40 22.79 01-JAN-09:40 750.02 18-DEC-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.40 22.79 01-JAN-09:40 750.02 18-DEC-16:40
Electricity:Zone:PERIMETER_BOT_ZN_3 32.89 422.10 07-MAY-17:10 2620.04 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.56 36.00 01-JAN-09:00 1184.79 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.56 36.00 01-JAN-09:00 1184.79 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_2 20.86 271.65 29-MAY-17:10 1768.58 04-DEC-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.46 22.79 01-JAN-07:20 860.01 04-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.46 22.79 01-JAN-07:20 860.01 04-DEC-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 32.86 425.61 12-MAR-17:10 2620.03 07-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.52 36.00 01-JAN-07:50 1184.79 07-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.52 36.00 01-JAN-07:50 1184.79 07-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_4 20.80 267.21 12-MAR-17:10 1658.59 18-DEC-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.39 22.79 01-JAN-09:30 750.02 18-DEC-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.39 22.79 01-JAN-09:30 750.02 18-DEC-16:50
Electricity:Zone:PERIMETER_MID_ZN_3 32.91 422.10 28-MAY-17:10 2620.04 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 8.58 36.00 01-JAN-09:10 1184.79 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 8.58 36.00 01-JAN-09:10 1184.79 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_2 20.87 271.65 29-MAY-17:10 1768.58 09-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.47 22.79 01-JAN-07:20 860.01 09-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.47 22.79 01-JAN-07:20 860.01 09-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 32.87 425.61 12-MAR-17:10 2620.03 07-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.54 36.00 01-JAN-08:00 1184.79 07-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.54 36.00 01-JAN-08:00 1184.79 07-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_4 20.81 267.21 12-MAR-17:10 1658.59 18-DEC-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.40 22.79 01-JAN-09:40 750.02 18-DEC-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.40 22.79 01-JAN-09:40 750.02 18-DEC-16:40
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 1048.10 367.92 01-JAN-00:10 107260.35 13-JUN-15:00
ExteriorEquipment:Electricity 26.91 367.92 01-JAN-00:10 1410.29 15-FEB-13:10
Transformer:ExteriorEquipment:Electricity 26.91 367.92 01-JAN-00:10 1410.29 15-FEB-13:10
ElectricityPurchased:Facility 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
ElectricityPurchased:Plant 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
Cogeneration:ElectricityPurchased 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
General:Cogeneration:ElectricityPurchased 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
ElectricityNet:Plant 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
Cogeneration:ElectricityNet 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
General:Cogeneration:ElectricityNet 2152.80 13872.05 18-JUN-17:20 177422.83 13-JUN-15:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity 121.50 0.00 01-JAN-00:10 16327.79 12-JUN-15:20
General:Fans:Electricity 121.50 0.00 01-JAN-00:10 16327.79 12-JUN-15:20
ExteriorLights:Electricity 49.51 0.00 01-JAN-06:20 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 49.51 0.00 01-JAN-06:20 5686.19 01-JAN-06:10
Cooling:Electricity 899.70 0.00 01-JAN-00:10 90068.80 13-JUN-15:00
General:Cooling:Electricity 899.70 0.00 01-JAN-00:10 90068.80 13-JUN-15:00
Electricity:Plant 35.80 0.00 01-JAN-00:10 4209.60 06-JAN-12:30
WaterSystems:Electricity 35.65 0.00 01-JAN-00:10 4202.75 06-JAN-12:30
Water Heater:WaterSystems:Electricity 35.65 0.00 01-JAN-00:10 4202.75 06-JAN-12:30
Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 19-MAR-15:30
General:Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 19-MAR-15:30
WIRED_LTG_ELECTRICITY 8.42 0.00 01-JAN-00:10 878.71 18-DEC-17:10
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 5908.91 0.00 01-JAN-00:10 505442.00 13-JUN-15:30
EnergyTransfer:Building 2009.46 0.00 01-JAN-00:10 173886.37 21-FEB-15:10
EnergyTransfer:Zone:CORE_BOTTOM 348.55 0.00 01-JAN-00:10 26867.76 02-JAN-09:00
Heating:EnergyTransfer 0.54 0.00 01-JAN-00:10 1939.42 25-SEP-04:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 0.54 0.00 01-JAN-00:10 1939.42 25-SEP-04:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 2008.92 0.00 01-JAN-00:10 173886.37 21-FEB-15:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 348.55 0.00 01-JAN-00:10 26867.76 02-JAN-09:00
General:Cooling:EnergyTransfer 2008.92 0.00 01-JAN-00:10 173886.37 21-FEB-15:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 348.55 0.00 01-JAN-00:10 26867.76 02-JAN-09:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 85.05 0.00 01-JAN-00:10 10960.84 05-MAY-13:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 0.17 0.00 01-JAN-00:10 1396.88 23-JAN-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 0.17 0.00 01-JAN-00:10 1396.88 23-JAN-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 84.88 0.00 01-JAN-00:10 10960.84 05-MAY-13:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 84.88 0.00 01-JAN-00:10 10960.84 05-MAY-13:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 51.60 0.00 01-JAN-00:10 5390.88 21-FEB-16:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 0.12 0.00 01-JAN-00:10 646.67 17-DEC-10:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 0.12 0.00 01-JAN-00:10 646.67 17-DEC-10:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 51.48 0.00 01-JAN-00:10 5390.88 21-FEB-16:10
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 51.48 0.00 01-JAN-00:10 5390.88 21-FEB-16:10
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 59.34 0.00 01-JAN-00:10 5766.86 30-MAY-11:00
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 0.25 0.00 01-JAN-00:10 933.58 17-AUG-04:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 0.25 0.00 01-JAN-00:10 933.58 17-AUG-04:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 59.09 0.00 01-JAN-00:10 5766.86 30-MAY-11:00
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 59.09 0.00 01-JAN-00:10 5766.86 30-MAY-11:00
EnergyTransfer:Zone:CORE_MID 258.79 0.00 01-JAN-00:10 20488.98 02-JAN-08:40
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 258.79 0.00 01-JAN-00:10 20488.98 02-JAN-08:40
General:Cooling:EnergyTransfer:Zone:CORE_MID 258.79 0.00 01-JAN-00:10 20488.98 02-JAN-08:40
EnergyTransfer:Zone:CORE_TOP 273.07 0.00 01-JAN-00:10 21967.86 21-FEB-14:50
Heating:EnergyTransfer:Zone:CORE_TOP 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_TOP 273.07 0.00 01-JAN-00:10 21967.86 21-FEB-14:50
General:Cooling:EnergyTransfer:Zone:CORE_TOP 273.07 0.00 01-JAN-00:10 21967.86 21-FEB-14:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.87 0.00 01-JAN-00:10 9505.60 12-JUN-15:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.87 0.00 01-JAN-00:10 9505.60 12-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.87 0.00 01-JAN-00:10 9505.60 12-JUN-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 65.91 0.00 01-JAN-00:10 7565.31 05-MAY-09:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 65.91 0.00 01-JAN-00:10 7565.31 05-MAY-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 65.91 0.00 01-JAN-00:10 7565.31 05-MAY-09:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.10 0.00 01-JAN-00:10 10445.11 26-DEC-13:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.10 0.00 01-JAN-00:10 10445.11 26-DEC-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 93.10 0.00 01-JAN-00:10 10445.11 26-DEC-13:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 66.12 0.00 01-JAN-00:10 8307.97 11-APR-15:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 66.12 0.00 01-JAN-00:10 8307.97 11-APR-15:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 66.12 0.00 01-JAN-00:10 8307.97 11-APR-15:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.09 0.00 01-JAN-00:10 8847.39 12-JUN-15:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.09 0.00 01-JAN-00:10 8847.39 12-JUN-15:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 86.09 0.00 01-JAN-00:10 8847.39 12-JUN-15:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 66.74 0.00 01-JAN-00:10 7035.19 20-MAR-09:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 66.74 0.00 01-JAN-00:10 7035.19 20-MAR-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 66.74 0.00 01-JAN-00:10 7035.19 20-MAR-09:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 111.96 0.00 01-JAN-00:10 11578.89 05-MAY-12:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 111.96 0.00 01-JAN-00:10 11578.89 05-MAY-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 111.96 0.00 01-JAN-00:10 11578.89 05-MAY-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 65.92 0.00 01-JAN-00:10 7400.60 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 65.92 0.00 01-JAN-00:10 7400.60 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 65.92 0.00 01-JAN-00:10 7400.60 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 80.38 0.00 01-JAN-00:10 8706.31 12-JUN-15:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 80.38 0.00 01-JAN-00:10 8706.31 12-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 80.38 0.00 01-JAN-00:10 8706.31 12-JUN-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 61.68 0.00 01-JAN-00:10 7209.75 05-MAY-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 61.68 0.00 01-JAN-00:10 7209.75 05-MAY-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 61.68 0.00 01-JAN-00:10 7209.75 05-MAY-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 88.14 0.00 01-JAN-00:10 9314.18 26-DEC-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 88.14 0.00 01-JAN-00:10 9314.18 26-DEC-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 88.14 0.00 01-JAN-00:10 9314.18 26-DEC-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 62.15 0.00 01-JAN-00:10 7697.93 18-APR-15:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 62.15 0.00 01-JAN-00:10 7697.93 18-APR-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 62.15 0.00 01-JAN-00:10 7697.93 18-APR-15:30
PlantLoopHeatingDemand:Facility 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
PlantLoopHeatingDemand:Plant 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
WaterSystems:PlantLoopHeatingDemand 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
General:WaterSystems:PlantLoopHeatingDemand 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
EnergyTransfer:HVAC 3866.52 0.00 01-JAN-00:10 331078.15 13-JUN-15:40
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
CoolingCoils:EnergyTransfer 3866.52 0.00 01-JAN-00:10 331078.15 13-JUN-15:40
EnergyTransfer:Plant 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
WaterSystems:EnergyTransfer 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
WaterUse:WaterSystems:EnergyTransfer 32.93 0.00 01-JAN-00:10 3872.68 12-JAN-12:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.000 -348.549 0.000 0.000 32.660 71.928 250.423 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 -6.463
CORE_MID 0.000 0.000 0.000 -258.791 0.000 0.000 32.738 71.928 115.425 0.000 0.000 0.000 38.699 0.000 0.000 0.000 0.000 -0.000
CORE_TOP 0.000 0.000 0.000 -273.066 0.000 0.000 32.760 71.928 115.425 0.000 0.000 0.000 52.952 0.000 0.000 0.000 0.000 -0.001
PERIMETER_TOP_ZN_3 0.000 0.000 0.000 -84.867 0.000 0.000 6.890 8.581 24.333 37.782 0.000 0.458 10.520 0.000 -3.622 0.000 -0.075 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 0.000 -65.913 0.000 0.000 4.361 5.468 15.404 37.597 0.000 0.304 5.151 0.000 -2.320 0.000 -0.052 -0.001
PERIMETER_TOP_ZN_1 0.000 0.000 0.000 -93.101 0.000 0.000 6.882 8.537 24.332 48.498 0.000 0.453 8.086 0.000 -3.608 0.000 -0.081 -0.001
PERIMETER_TOP_ZN_4 0.000 0.000 0.000 -66.115 0.000 0.000 4.373 5.404 15.403 37.733 0.000 0.306 5.461 0.000 -2.512 0.000 -0.054 -0.000
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -86.090 0.000 0.000 6.886 8.561 24.333 37.901 0.000 0.251 12.146 0.000 -3.944 0.000 -0.043 -0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -66.737 0.000 0.000 4.356 5.456 15.404 37.659 0.000 0.162 6.407 0.000 -2.676 0.000 -0.032 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -111.959 0.000 0.000 6.766 8.523 24.332 48.224 0.000 21.209 7.436 0.000 -4.169 0.000 -0.362 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -65.924 0.000 0.000 4.358 5.393 15.403 37.737 0.000 0.160 5.819 0.000 -2.913 0.000 -0.033 -0.000
PERIMETER_MID_ZN_3 0.000 0.000 0.000 -80.377 0.000 0.000 6.887 8.581 24.333 38.075 0.000 0.389 5.924 0.000 -3.746 0.000 -0.066 -0.001
PERIMETER_MID_ZN_2 0.000 0.000 0.000 -61.676 0.000 0.000 3.215 5.467 15.404 37.814 0.000 0.257 1.962 0.000 -2.398 0.000 -0.045 -0.000
PERIMETER_MID_ZN_1 0.000 0.000 0.000 -88.133 0.000 0.000 6.874 8.537 24.332 48.790 0.000 0.383 3.015 0.000 -3.728 0.000 -0.071 -0.000
PERIMETER_MID_ZN_4 0.000 0.000 0.000 -62.145 0.000 0.000 4.365 5.404 15.403 37.897 0.000 0.254 1.489 0.000 -2.620 0.000 -0.047 -0.000
TOPFLOOR_PLENUM 0.172 -84.880 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.565 84.229 0.000 0.000 0.000 -0.086 0.000
MIDFLOOR_PLENUM 0.116 -51.482 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.585 50.880 0.000 0.000 0.000 -0.098 0.000
FIRSTFLOOR_PLENUM 0.253 -59.087 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.444 58.472 0.000 0.000 0.000 -0.083 -0.000
Total Facility 0.540 -195.449 0.000 -1813.443 0.000 0.000 164.370 299.699 719.689 485.708 0.000 26.181 358.652 0.000 -38.254 0.000 -1.228 -6.469


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 19-SEP-05:03 0.00 0.00 0.00 -43726.06 0.00 0.00 289.14 211.73 7410.35 0.00 0.00 0.00 35814.83 0.00 -0.00 0.00 0.00 0.00
CORE_MID 06-FEB-06:03 0.00 0.00 0.00 -35283.91 0.00 0.00 292.68 211.73 3025.92 0.00 0.00 0.00 31753.58 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 06-FEB-06:03 0.00 0.00 0.00 -37675.19 0.00 0.00 298.96 211.73 3025.92 0.00 0.00 0.00 34138.58 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 18-JUN-12:02 0.00 0.00 0.00 -12975.64 0.00 0.00 25.38 36.00 478.42 4455.20 0.00 132.00 7848.65 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 26-MAR-09:22 0.00 0.00 0.00 -12182.74 0.00 0.00 14.95 22.79 302.86 6073.32 0.00 48.86 5719.96 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 19-NOV-12:22 0.00 0.00 0.00 -13278.87 0.00 0.00 24.20 36.00 478.41 7631.90 0.00 34.04 5074.31 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 29-JAN-16:42 0.00 0.00 0.00 -13540.43 0.00 0.00 14.96 22.79 302.86 4468.41 0.00 29.12 8702.29 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 18-JUN-12:02 0.00 0.00 0.00 -11101.87 0.00 0.00 26.80 36.00 478.42 4554.11 0.00 74.37 5932.19 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 26-MAR-09:22 0.00 0.00 0.00 -10834.65 0.00 0.00 15.90 22.79 302.86 6177.61 0.00 28.33 4287.16 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 05-MAY-12:00 0.00 0.00 0.00 -11578.19 0.00 0.00 286.85 647.98 1275.77 3336.23 0.00 10821.29 0.00 0.00 -0.00 0.00 0.00 -4789.92
PERIMETER_BOT_ZN_4 04-JUL-17:02 0.00 0.00 0.00 -11636.45 0.00 0.00 0.00 22.79 244.42 4784.95 0.00 12.79 6571.51 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 04-JUL-16:32 0.00 0.00 0.00 -11242.04 0.00 0.00 27.09 36.00 478.42 3172.28 0.00 57.61 7470.65 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 26-MAR-09:22 0.00 0.00 0.00 -11648.90 0.00 0.00 15.27 22.79 302.86 6107.62 0.00 41.92 5158.44 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 16-JAN-12:02 0.00 0.00 0.00 -11742.18 0.00 0.00 24.28 36.00 478.41 8367.11 0.00 10.24 2826.15 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 04-JUL-16:32 0.00 0.00 0.00 -12725.70 0.00 0.00 14.62 22.79 302.86 5646.92 0.00 28.71 6709.81 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 05-MAY-13:30 0.00 -10960.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.02 10885.77 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 21-FEB-16:10 0.00 -5390.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.88 5339.07 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 30-MAY-12:10 0.00 -5949.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50 5940.44 0.00 -0.00 0.00 0.00 0.00
Total Facility 20-MAR-04:02 0.00 9073.23 0.00 -207354.77 0.00 0.00 0.00 1072.56 15570.33 0.00 0.00 214.89 183379.66 0.00 -1955.89 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 06-FEB-06:02 5181.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5181.78
MIDFLOOR_PLENUM 02-AUG-04:02 2549.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.72 0.00 0.00 -0.00 0.00 0.00 -2597.54
FIRSTFLOOR_PLENUM 02-AUG-04:02 4288.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.25 0.00 0.00 -0.00 0.00 0.00 -4323.73
Total Facility 25-SEP-04:02 -189749.32 199445.92 0.00 -199445.92 0.00 0.00 0.00 1072.56 15570.33 0.00 0.00 7.21 176132.93 0.00 -3030.50 0.00 -3.20 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 5.1429 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.7325 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 4.7375 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.2680 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.1616 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.9563 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.5715 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3430 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.3688 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3285 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.5808 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3920 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6433 2.6433 0.7692 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1412 2.1412 0.7473 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2836 2.2836 0.7787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7362 0.7362 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6617 0.6617 0.1323 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7169 0.7169 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7632 0.7632 0.1526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6353 0.6353 0.1620 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6010 0.6010 0.1202 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6172 0.6172 0.1623 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6460 0.6460 0.1292 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6417 0.6417 0.1578 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6376 0.6376 0.1275 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6244 0.6244 0.1573 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6927 0.6927 0.1385 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 5.1429 4.7325 5.1429 1.3430 0.0000 1.0000
PACU_VAV_MID 4.7375 4.2680 4.7375 1.3285 0.0000 1.0000
PACU_VAV_TOP 5.1616 4.9563 5.1616 1.3920 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3216 1.3216 0.7692 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0706 1.0706 0.7473 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1418 1.1418 0.7787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3681 0.3681 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3309 0.3309 0.1323 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3584 0.3584 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3816 0.3816 0.1526 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3177 0.3177 0.1620 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3005 0.3005 0.1202 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3086 0.3086 0.1623 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3230 0.3230 0.1292 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3208 0.3208 0.1578 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3188 0.3188 0.1275 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3122 0.3122 0.1573 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3464 0.3464 0.1385 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.5715 1.3430 1.3430 1.3430 0.0000 1.0000
PACU_VAV_MID 2.3688 1.3285 1.3285 1.3285 0.0000 1.0000
PACU_VAV_TOP 2.5808 1.3920 1.3920 1.3920 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Total gross floor area [m2] 4982.19


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 805.50
Number of hours not met 805.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 899.70 90068.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 299.70 31270.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 49.51 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.91 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 121.50 16327.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.15 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 35.65 4202.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 2152.80
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 719.69 2152.80


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 60.15
Space Heating 0.00
Space Cooling 180.58
Fans (All) 24.39
Service Water Heating 7.16
Receptacle Equipment 144.45
Miscellaneous (All) 432.10
Subtotal 432.10


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.92
Space Heating 0.00
Space Cooling 41.79
Fans (All) 5.64
Service Water Heating 1.66
Receptacle Equipment 33.43
Miscellaneous 3.56


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 1574. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 6835.00 1925.00 0.00 0.00 0.00
CORE_MID 8675.50 84.50 0.00 0.00 0.00
CORE_TOP 8688.17 71.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8155.67 604.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8051.00 709.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8014.50 745.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7899.33 860.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8406.83 353.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8079.83 680.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8080.17 679.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7748.83 1011.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8281.00 479.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8129.67 630.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8094.33 665.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7895.83 864.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 8158.83 601.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8728.17 31.83 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8723.17 36.83 0.00 0.00 0.00
Min 6835.00 31.83 0.00 0.00 0.00
Max 8728.17 1925.00 0.00 0.00 0.00
Average 8146.99 613.01 0.00 0.00 0.00
Sum 146645.83 11034.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 127753.33 550.67 0.00 0.00 0.00
CORE_MID 128293.67 10.33 0.00 0.00 0.00
CORE_TOP 128296.67 7.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24636.83 272.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128296.67 550.67 0.00 0.00 0.00
Average 34096.64 46.69 0.00 0.00 0.00
Sum 613739.50 840.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 6392.17 2367.83 0.00 0.00 0.00
CORE_MID 8465.33 294.67 0.00 0.00 0.00
CORE_TOP 8512.83 247.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 5558.83 3201.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 5576.67 3183.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 5420.83 3339.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 5702.50 3057.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 6092.33 2667.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 5765.67 2994.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 3919.00 4841.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 5779.33 2980.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 5572.67 3187.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 5560.00 3200.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 5367.50 3392.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 5581.17 3178.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 6442.83 2317.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 6762.00 1998.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 7066.33 1693.67 0.00 0.00 0.00
Min 3919.00 247.17 0.00 0.00 0.00
Max 8512.83 4841.00 0.00 0.00 0.00
Average 6085.44 2674.56 0.00 0.00 0.00
Sum 109538.00 48142.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 127512.00 792.00 0.00 0.00 0.00
CORE_MID 128255.00 49.00 0.00 0.00 0.00
CORE_TOP 128266.33 37.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24863.17 45.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24863.83 45.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24905.83 3.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 16345.33 8563.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24876.00 33.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24876.00 33.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128266.33 8563.67 0.00 0.00 0.00
Average 33609.86 533.47 0.00 0.00 0.00
Sum 604977.50 9602.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:27

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293063E+11 41050.26 03-JAN-05:02 24.93 22.82 0.199610E+10 2606.54 02-JAN-14:09 24.93 22.82
February 0.267003E+11 41662.80 06-FEB-06:03 23.95 22.59 0.180989E+10 2606.54 21-FEB-10:20 23.53 20.42
March 0.307394E+11 41130.02 08-MAR-05:03 24.00 22.62 0.216012E+10 2606.54 03-MAR-10:09 24.00 22.62
April 0.287841E+11 40821.54 22-APR-04:03 24.58 23.40 0.191788E+10 2606.55 20-APR-13:09 24.58 23.40
May 0.306287E+11 40916.84 26-MAY-04:03 24.00 23.90 0.207729E+10 2606.54 01-MAY-13:09 24.00 23.90
June 0.302978E+11 40561.01 03-JUN-04:03 25.42 25.21 0.207110E+10 2606.55 16-JUN-13:00 36.00 27.59
July 0.288358E+11 40941.83 19-JUL-04:03 24.42 23.71 0.192525E+10 2606.54 10-JUL-13:09 24.42 23.71
August 0.302290E+11 41618.63 21-AUG-04:02 24.17 23.75 0.216086E+10 2606.54 17-AUG-13:09 24.17 23.75
September 0.281576E+11 43730.63 19-SEP-05:03 24.00 24.00 0.191806E+10 2606.54 14-SEP-13:09 24.00 24.00
October 0.287379E+11 41239.15 24-OCT-04:02 24.08 24.04 0.199529E+10 2606.54 30-OCT-13:09 24.42 24.31
November 0.281383E+11 41020.41 07-NOV-05:02 24.00 23.42 0.197596E+10 2606.54 08-NOV-14:09 31.00 25.90
December 0.279934E+11 40716.48 30-DEC-05:03 24.00 24.00 0.192598E+10 2606.54 04-DEC-14:09 24.00 24.00
                     
Annual Sum or Average 0.348549E+12         0.239338E+11        
Minimum of Months 0.267003E+11 40561.01   23.95 22.59 0.180989E+10 2606.54   23.53 20.42
Maximum of Months 0.307394E+11 43730.63   25.42 25.21 0.216086E+10 2606.55   36.00 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.685607E+10 9835.57 04-JAN-14:10 33.83 23.50 0.00 0.00 01-JAN-00:10 33.83 23.50
February 0.682219E+10 10868.84 21-FEB-14:40 34.33 21.86 0.00 0.00 01-FEB-00:10 34.33 21.86
March 0.823255E+10 10925.29 21-MAR-14:00 36.00 23.97 0.00 0.00 01-MAR-00:10 36.00 23.97
April 0.789686E+10 10214.80 11-APR-14:30 34.85 26.00 0.00 0.00 01-APR-00:10 34.85 26.00
May 0.792191E+10 10960.84 05-MAY-13:30 36.20 27.12 0.00 0.00 01-MAY-00:10 36.20 27.12
June 0.830685E+10 10772.11 16-JUN-14:00 36.00 27.59 0.00 0.00 01-JUN-00:10 36.00 27.59
July 0.676456E+10 9423.60 14-JUL-14:30 32.25 24.82 0.00 0.00 01-JUL-00:10 32.25 24.82
August 0.685191E+10 9988.34 14-AUG-13:50 33.13 27.67 0.00 0.00 01-AUG-00:10 33.13 27.67
September 0.659582E+10 9956.36 06-SEP-14:00 34.00 26.51 0.00 0.00 01-SEP-00:10 34.00 26.51
October 0.605118E+10 9500.72 04-OCT-13:50 32.88 26.26 0.00 0.00 01-OCT-00:10 32.88 26.26
November 0.626025E+10 9425.11 22-NOV-13:02 31.50 24.57 0.00 0.00 01-NOV-00:10 31.50 24.57
December 0.632051E+10 9692.83 26-DEC-13:02 32.00 23.12 0.00 0.00 01-DEC-00:10 32.00 23.12
                     
Annual Sum or Average 0.848807E+11         0.00        
Minimum of Months 0.605118E+10 9423.60   31.50 21.86 0.00 0.00   31.50 21.86
Maximum of Months 0.830685E+10 10960.84   36.20 27.67 0.00 0.00   36.20 27.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.425715E+10 5007.80 02-JAN-07:03 23.85 23.26 0.00 0.00 01-JAN-00:10 23.85 23.26
February 0.407124E+10 5390.88 21-FEB-16:10 31.80 23.94 0.00 0.00 01-FEB-00:10 31.80 23.94
March 0.474339E+10 5182.40 20-MAR-15:20 34.77 24.85 0.00 0.00 01-MAR-00:10 34.77 24.85
April 0.449881E+10 4798.87 17-APR-15:40 32.90 26.39 0.00 0.00 01-APR-00:10 32.90 26.39
May 0.478451E+10 5328.93 30-MAY-12:02 33.10 27.55 0.00 0.00 01-MAY-00:10 33.10 27.55
June 0.496744E+10 5383.93 12-JUN-16:00 35.40 27.71 0.00 0.00 01-JUN-00:10 35.40 27.71
July 0.416016E+10 4579.55 17-JUL-14:10 31.67 26.15 0.00 0.00 01-JUL-00:10 31.67 26.15
August 0.424529E+10 4772.09 14-AUG-14:50 32.17 28.09 0.00 0.00 01-AUG-00:10 32.17 28.09
September 0.399689E+10 4904.89 05-SEP-06:03 26.10 25.95 0.00 0.00 01-SEP-00:10 26.10 25.95
October 0.393221E+10 4873.05 10-OCT-14:30 30.50 26.20 0.00 0.00 01-OCT-00:10 30.50 26.20
November 0.397158E+10 4992.28 13-NOV-13:02 31.92 25.57 0.00 0.00 01-NOV-00:10 31.92 25.57
December 0.385438E+10 5054.16 26-DEC-16:00 30.20 22.54 0.00 0.00 01-DEC-00:10 30.20 22.54
                     
Annual Sum or Average 0.514830E+11         0.00        
Minimum of Months 0.385438E+10 4579.55   23.85 22.54 0.00 0.00   23.85 22.54
Maximum of Months 0.496744E+10 5390.88   35.40 28.09 0.00 0.00   35.40 28.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.491706E+10 5323.15 17-JAN-16:00 29.90 22.65 0.00 0.00 01-JAN-00:10 29.90 22.65
February 0.461776E+10 5660.54 21-FEB-16:10 31.80 23.94 0.00 0.00 01-FEB-00:10 31.80 23.94
March 0.534276E+10 5459.20 20-MAR-16:00 34.30 24.91 0.00 0.00 01-MAR-00:10 34.30 24.91
April 0.504141E+10 5296.21 17-APR-15:40 32.90 26.39 0.00 0.00 01-APR-00:10 32.90 26.39
May 0.539300E+10 5950.52 30-MAY-12:10 33.10 27.55 0.00 0.00 01-MAY-00:10 33.10 27.55
June 0.562120E+10 5745.65 12-JUN-16:00 35.40 27.71 0.00 0.00 01-JUN-00:10 35.40 27.71
July 0.482366E+10 5217.63 17-JUL-14:10 31.67 26.15 0.00 0.00 01-JUL-00:10 31.67 26.15
August 0.497419E+10 5312.54 14-AUG-12:08 33.13 27.67 0.00 0.00 01-AUG-00:10 33.13 27.67
September 0.462492E+10 5466.94 05-SEP-12:10 33.02 26.93 0.00 0.00 01-SEP-00:10 33.02 26.93
October 0.455916E+10 5312.75 10-OCT-15:10 29.17 26.02 0.00 0.00 01-OCT-00:10 29.17 26.02
November 0.462247E+10 5335.39 13-NOV-13:10 31.92 25.57 0.00 0.00 01-NOV-00:10 31.92 25.57
December 0.454989E+10 5344.32 26-DEC-16:00 30.20 22.54 0.00 0.00 01-DEC-00:10 30.20 22.54
                     
Annual Sum or Average 0.590875E+11         0.00        
Minimum of Months 0.454989E+10 5217.63   29.17 22.54 0.00 0.00   29.17 22.54
Maximum of Months 0.562120E+10 5950.52   35.40 27.71 0.00 0.00   35.40 27.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.214612E+11 32631.94 10-JAN-05:02 23.95 22.91 0.198928E+10 2606.55 24-JAN-10:09 20.83 18.11
February 0.198080E+11 35286.36 06-FEB-06:03 23.95 22.59 0.180410E+10 2606.53 24-FEB-10:09 28.50 22.00
March 0.230517E+11 32795.49 07-MAR-05:02 24.00 22.62 0.215441E+10 2606.54 03-MAR-10:09 24.00 22.62
April 0.217132E+11 32033.02 05-APR-04:02 26.08 23.61 0.191236E+10 2606.54 20-APR-13:09 33.50 26.37
May 0.230939E+11 32429.39 09-MAY-04:02 24.17 24.17 0.207210E+10 2606.54 01-MAY-13:09 24.17 24.17
June 0.228428E+11 32527.23 01-JUN-04:02 24.17 24.06 0.206629E+10 2606.54 16-JUN-13:00 36.00 27.59
July 0.213893E+11 32816.87 18-JUL-04:22 24.00 23.32 0.191815E+10 2606.53 10-JUL-13:09 24.00 23.32
August 0.223033E+11 32393.81 21-AUG-04:02 24.17 23.75 0.215385E+10 2606.54 03-AUG-13:00 24.17 23.75
September 0.208730E+11 32466.21 13-SEP-04:02 24.42 24.11 0.191129E+10 2606.54 14-SEP-13:09 32.33 27.93
October 0.211465E+11 32915.97 11-OCT-04:02 24.00 23.26 0.198778E+10 2606.54 30-OCT-13:09 24.42 24.31
November 0.206791E+11 32911.04 07-NOV-05:02 24.00 23.42 0.196926E+10 2606.54 08-NOV-14:09 31.00 25.90
December 0.204286E+11 31019.82 26-DEC-06:12 22.33 21.42 0.191754E+10 2606.55 21-DEC-10:09 22.33 21.42
                     
Annual Sum or Average 0.258791E+12         0.238564E+11        
Minimum of Months 0.198080E+11 31019.82   22.33 21.42 0.180410E+10 2606.53   20.83 18.11
Maximum of Months 0.230939E+11 35286.36   26.08 24.17 0.215441E+10 2606.55   36.00 27.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222494E+11 34711.64 09-JAN-05:02 23.92 23.24 0.198559E+10 2606.63 24-JAN-10:30 23.70 19.15
February 0.207580E+11 37677.41 06-FEB-06:03 23.95 22.59 0.180166E+10 2606.55 24-FEB-10:09 28.50 22.00
March 0.245517E+11 34537.20 21-MAR-04:02 25.58 22.99 0.215304E+10 2606.55 03-MAR-10:09 25.58 22.99
April 0.234856E+11 34826.82 10-APR-04:02 25.17 23.75 0.191232E+10 2606.54 20-APR-13:09 33.50 26.37
May 0.246985E+11 34960.32 09-MAY-04:02 24.17 24.17 0.207169E+10 2606.54 25-MAY-13:09 31.17 27.76
June 0.245676E+11 34705.01 26-JUN-04:02 24.00 23.59 0.206616E+10 2606.54 28-JUN-13:09 34.17 26.79
July 0.225850E+11 34618.72 06-JUL-04:02 25.17 23.75 0.191688E+10 2606.53 10-JUL-13:09 28.83 25.76
August 0.234430E+11 35131.29 21-AUG-04:02 24.17 23.75 0.215178E+10 2606.54 17-AUG-13:00 24.17 23.75
September 0.220585E+11 34423.70 14-SEP-04:02 25.50 24.23 0.191023E+10 2606.54 14-SEP-13:09 32.33 27.93
October 0.219908E+11 35041.21 02-OCT-04:02 24.00 23.36 0.198570E+10 2606.55 13-OCT-13:09 31.75 26.46
November 0.215344E+11 34782.04 13-NOV-05:02 25.00 24.24 0.196640E+10 2606.55 16-NOV-14:09 29.85 25.47
December 0.211433E+11 33576.59 26-DEC-06:12 22.33 21.42 0.191236E+10 2606.61 21-DEC-10:09 22.33 21.42
                     
Annual Sum or Average 0.273066E+12         0.238338E+11        
Minimum of Months 0.207580E+11 33576.59   22.33 21.42 0.180166E+10 2606.53   22.33 19.15
Maximum of Months 0.246985E+11 37677.41   25.58 24.24 0.215304E+10 2606.63   34.17 27.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.627215E+10 8526.42 02-JAN-06:12 23.37 23.04 0.419378E+09 549.49 24-JAN-10:30 23.70 19.15
February 0.606564E+10 10197.40 05-FEB-14:32 32.00 25.37 0.380885E+09 549.48 15-FEB-14:00 29.00 24.59
March 0.744780E+10 12584.55 26-MAR-14:02 34.83 25.46 0.455030E+09 549.48 03-MAR-10:09 34.83 25.46
April 0.743592E+10 12281.66 30-APR-12:53 33.70 26.84 0.404558E+09 549.48 20-APR-13:00 33.70 26.84
May 0.854124E+10 12790.53 07-MAY-12:32 35.00 26.20 0.438358E+09 549.48 30-MAY-13:00 28.00 26.50
June 0.918559E+10 12975.46 18-JUN-12:02 33.23 27.06 0.437042E+09 549.48 28-JUN-13:00 34.00 27.29
July 0.757723E+10 12631.63 04-JUL-14:02 32.08 24.88 0.406026E+09 549.47 11-JUL-13:00 25.00 23.59
August 0.739944E+10 12502.13 13-AUG-12:53 34.00 28.60 0.455115E+09 549.47 17-AUG-13:00 27.00 26.21
September 0.665003E+10 12290.05 04-SEP-12:53 32.50 27.43 0.404155E+09 549.47 07-SEP-13:00 32.00 27.49
October 0.629382E+10 10712.64 16-OCT-04:02 26.00 25.22 0.420089E+09 549.48 13-OCT-13:09 26.00 25.22
November 0.612781E+10 11838.24 19-NOV-14:22 31.75 24.87 0.415781E+09 549.48 08-NOV-14:09 31.75 24.87
December 0.587235E+10 6764.32 26-DEC-14:10 31.17 22.67 0.404108E+09 549.48 21-DEC-10:09 31.17 22.67
                     
Annual Sum or Average 0.848690E+11         0.504052E+10        
Minimum of Months 0.587235E+10 6764.32   23.37 22.67 0.380885E+09 549.47   23.70 19.15
Maximum of Months 0.918559E+10 12975.46   35.00 28.60 0.455115E+09 549.49   34.83 27.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.514336E+10 10037.31 16-JAN-11:02 29.63 21.29 0.265976E+09 347.88 24-JAN-10:30 23.70 19.15
February 0.510061E+10 11530.39 20-FEB-09:13 28.47 23.42 0.241496E+09 347.86 24-FEB-10:09 28.50 22.00
March 0.631359E+10 12181.84 26-MAR-09:22 31.90 24.91 0.288238E+09 347.86 03-MAR-10:20 31.90 24.91
April 0.617214E+10 11508.01 09-APR-08:13 29.27 25.57 0.256250E+09 347.86 20-APR-13:00 34.50 26.74
May 0.614342E+10 12005.09 29-MAY-09:02 31.17 27.92 0.277347E+09 347.86 30-MAY-13:00 28.00 26.50
June 0.627458E+10 11249.16 11-JUN-11:53 34.00 27.86 0.276496E+09 347.86 28-JUN-13:00 34.00 27.29
July 0.527602E+10 8753.10 04-JUL-14:02 32.08 24.88 0.256770E+09 347.86 17-JUL-13:00 32.00 26.09
August 0.566287E+10 11556.17 13-AUG-08:53 31.00 27.87 0.288006E+09 347.86 17-AUG-13:00 27.00 26.21
September 0.527363E+10 11564.05 10-SEP-09:23 30.30 26.10 0.255896E+09 347.86 07-SEP-13:00 30.30 26.10
October 0.496439E+10 11512.15 08-OCT-09:53 30.50 26.45 0.265926E+09 347.86 11-OCT-09:30 29.05 25.81
November 0.483293E+10 9561.91 05-NOV-11:13 30.67 23.05 0.263361E+09 347.86 13-NOV-10:20 26.97 24.85
December 0.475671E+10 8280.70 03-DEC-11:13 31.00 22.63 0.256389E+09 347.87 21-DEC-10:09 26.17 20.56
                     
Annual Sum or Average 0.659143E+11         0.319215E+10        
Minimum of Months 0.475671E+10 8280.70   28.47 21.29 0.241496E+09 347.86   23.70 19.15
Maximum of Months 0.631359E+10 12181.84   34.00 27.92 0.288238E+09 347.88   34.50 27.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.907478E+10 12961.67 29-JAN-12:02 30.08 23.23 0.422128E+09 577.76 04-JAN-14:09 30.08 23.23
February 0.816912E+10 12793.14 26-FEB-12:13 32.83 24.74 0.382192E+09 573.13 21-FEB-14:20 32.83 24.74
March 0.850746E+10 12745.10 26-MAR-14:02 34.83 25.46 0.455337E+09 549.48 06-MAR-14:00 34.83 25.46
April 0.732241E+10 11949.01 02-APR-15:42 33.75 27.23 0.404502E+09 549.48 20-APR-13:00 34.50 26.74
May 0.772777E+10 12124.29 07-MAY-12:32 35.00 26.20 0.438036E+09 549.47 30-MAY-13:00 28.00 26.50
June 0.765611E+10 12037.50 18-JUN-12:02 33.23 27.06 0.436658E+09 549.48 28-JUN-13:00 34.00 27.29
July 0.673129E+10 11948.56 04-JUL-14:02 32.08 24.88 0.405598E+09 549.47 11-JUL-13:00 25.00 23.59
August 0.700233E+10 11724.61 13-AUG-12:53 34.00 28.60 0.454921E+09 549.47 17-AUG-13:00 27.00 26.21
September 0.694053E+10 12151.77 04-SEP-12:53 32.50 27.43 0.404244E+09 549.47 07-SEP-13:00 32.00 27.49
October 0.733825E+10 12774.89 29-OCT-11:43 31.50 26.00 0.420555E+09 549.48 13-OCT-13:09 31.50 26.00
November 0.803488E+10 13279.38 19-NOV-12:22 32.40 24.66 0.416674E+09 549.48 22-NOV-14:00 31.50 24.56
December 0.859810E+10 12972.70 03-DEC-11:13 31.00 22.63 0.407528E+09 581.40 26-DEC-14:09 31.17 22.67
                     
Annual Sum or Average 0.931030E+11         0.504837E+10        
Minimum of Months 0.673129E+10 11724.61   30.08 22.63 0.382192E+09 549.47   25.00 22.67
Maximum of Months 0.907478E+10 13279.38   35.00 28.60 0.455337E+09 581.40   34.83 27.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.525338E+10 13541.86 29-JAN-16:42 31.22 23.22 0.264336E+09 347.84 24-JAN-10:00 31.22 23.22
February 0.515959E+10 13064.43 26-FEB-15:32 34.40 24.93 0.240259E+09 347.84 15-FEB-14:00 34.40 24.93
March 0.638400E+10 13521.66 05-MAR-16:42 28.37 23.27 0.287359E+09 347.84 03-MAR-10:09 28.37 23.27
April 0.615489E+10 13430.47 02-APR-15:42 33.75 27.23 0.255625E+09 347.84 20-APR-13:00 34.50 26.74
May 0.610056E+10 13023.32 14-MAY-15:42 34.83 27.45 0.276657E+09 347.84 30-MAY-13:00 28.00 26.50
June 0.618154E+10 13068.96 11-JUN-16:32 33.50 27.84 0.275944E+09 347.84 28-JUN-13:00 34.00 27.29
July 0.527351E+10 13098.07 04-JUL-16:02 31.17 25.29 0.255769E+09 347.84 11-JUL-13:00 25.00 23.59
August 0.558358E+10 13074.65 27-AUG-16:12 32.67 25.94 0.287078E+09 347.84 15-AUG-13:00 32.67 25.94
September 0.523034E+10 13148.33 04-SEP-16:12 32.67 26.80 0.254984E+09 347.84 07-SEP-13:00 32.00 27.49
October 0.500204E+10 12005.19 15-OCT-17:03 28.42 25.82 0.264757E+09 347.84 13-OCT-13:00 28.42 25.82
November 0.490980E+10 13398.21 19-NOV-14:22 31.75 24.87 0.262249E+09 347.84 21-NOV-14:00 31.50 24.93
December 0.488389E+10 12170.98 03-DEC-16:33 28.83 22.68 0.254421E+09 347.84 08-DEC-14:00 33.00 23.65
                     
Annual Sum or Average 0.661171E+11         0.317944E+10        
Minimum of Months 0.488389E+10 12005.19   28.37 22.68 0.240259E+09 347.84   25.00 23.22
Maximum of Months 0.638400E+10 13541.86   34.83 27.84 0.287359E+09 347.84   34.50 27.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.638489E+10 7578.79 02-JAN-07:03 23.85 23.26 0.420070E+09 549.47 09-JAN-14:00 31.00 24.49
February 0.607308E+10 8329.81 06-FEB-06:02 23.95 22.59 0.381246E+09 549.48 21-FEB-10:09 21.92 19.78
March 0.725410E+10 8675.42 28-MAR-04:02 27.25 25.19 0.455112E+09 549.48 03-MAR-10:09 27.25 25.19
April 0.725322E+10 10591.82 30-APR-16:02 32.17 27.26 0.404486E+09 549.48 20-APR-13:09 32.17 27.26
May 0.855779E+10 10982.75 29-MAY-11:53 35.00 28.17 0.438493E+09 549.48 30-MAY-13:00 28.00 26.50
June 0.925427E+10 11102.04 18-JUN-12:02 33.23 27.06 0.437326E+09 553.38 12-JUN-13:00 33.23 27.06
July 0.791841E+10 10976.02 04-JUL-17:02 29.13 25.16 0.406374E+09 549.48 17-JUL-13:00 32.00 26.09
August 0.771119E+10 9172.03 13-AUG-12:53 34.00 28.60 0.455523E+09 549.47 15-AUG-13:00 27.00 27.00
September 0.687174E+10 8990.06 08-SEP-04:02 26.75 24.48 0.404413E+09 549.47 07-SEP-13:00 26.75 24.48
October 0.648386E+10 8844.81 16-OCT-04:02 26.00 25.22 0.420442E+09 549.47 30-OCT-13:00 24.00 24.00
November 0.630125E+10 7768.53 13-NOV-07:03 26.08 24.64 0.416182E+09 549.48 09-NOV-14:00 26.08 24.64
December 0.602787E+10 6728.74 04-DEC-07:03 23.50 23.07 0.405301E+09 549.48 04-DEC-14:00 29.00 23.27
                     
Annual Sum or Average 0.860917E+11         0.504497E+10        
Minimum of Months 0.602787E+10 6728.74   23.50 22.59 0.381246E+09 549.47   21.92 19.78
Maximum of Months 0.925427E+10 11102.04   35.00 28.60 0.455523E+09 553.38   33.23 27.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524900E+10 9225.93 16-JAN-10:13 28.43 21.42 0.266381E+09 347.86 31-JAN-10:09 24.17 21.37
February 0.515382E+10 10470.07 20-FEB-10:13 29.77 23.08 0.241794E+09 347.86 21-FEB-10:20 23.53 20.42
March 0.623096E+10 10834.36 26-MAR-09:22 31.90 24.91 0.288516E+09 347.86 03-MAR-10:09 31.90 24.91
April 0.606946E+10 10712.94 30-APR-10:42 33.22 27.04 0.256426E+09 347.86 20-APR-13:00 33.22 27.04
May 0.613834E+10 10687.08 14-MAY-10:12 32.60 26.07 0.277654E+09 347.86 30-MAY-13:00 28.00 26.50
June 0.628415E+10 9643.85 11-JUN-11:53 34.00 27.86 0.276752E+09 347.86 16-JUN-13:00 36.00 27.59
July 0.544558E+10 8600.46 30-JUL-09:13 28.83 24.44 0.257203E+09 347.86 17-JUL-13:00 28.83 24.44
August 0.585307E+10 10695.52 27-AUG-10:02 31.58 26.86 0.288494E+09 347.86 04-AUG-09:00 31.58 26.86
September 0.541640E+10 10410.66 04-SEP-08:53 30.00 26.93 0.256315E+09 347.86 11-SEP-13:00 27.00 24.83
October 0.506612E+10 8782.66 09-OCT-08:23 28.00 25.71 0.266423E+09 347.86 11-OCT-09:30 29.05 25.81
November 0.494639E+10 8163.63 23-NOV-09:32 28.77 23.95 0.263839E+09 347.86 13-NOV-10:09 28.77 23.95
December 0.488456E+10 8180.45 31-DEC-09:23 29.40 23.97 0.257072E+09 347.86 29-DEC-10:20 29.40 23.97
                     
Annual Sum or Average 0.667379E+11         0.319687E+10        
Minimum of Months 0.488456E+10 8163.63   28.00 21.42 0.241794E+09 347.86   23.53 20.42
Maximum of Months 0.628415E+10 10834.36   34.00 27.86 0.288516E+09 347.86   36.00 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102541E+11 11413.67 16-JAN-11:32 30.03 21.52 0.439924E+09 737.16 04-JAN-13:09 30.03 21.52
February 0.926591E+10 11275.35 21-FEB-13:00 34.10 22.08 0.400269E+09 729.99 21-FEB-13:09 34.25 22.07
March 0.102027E+11 11162.70 21-MAR-12:00 35.00 23.21 0.467672E+09 719.76 21-MAR-12:09 35.23 23.19
April 0.903404E+10 10665.55 18-APR-12:00 34.00 26.52 0.410871E+09 677.90 18-APR-12:09 34.03 26.51
May 0.967664E+10 11578.89 05-MAY-12:00 37.00 25.95 0.445810E+09 748.27 05-MAY-12:09 36.90 26.19
June 0.968958E+10 11042.73 16-JUN-12:00 35.00 28.16 0.444652E+09 703.53 16-JUN-12:09 35.17 28.24
July 0.829226E+10 10166.60 26-JUL-17:00 33.00 26.23 0.409315E+09 625.79 27-JUL-12:09 31.48 25.75
August 0.899343E+10 10673.61 15-AUG-12:00 33.70 27.96 0.460105E+09 675.99 15-AUG-12:09 33.32 27.86
September 0.858389E+10 10508.88 05-SEP-12:00 33.00 26.98 0.409298E+09 665.60 05-SEP-12:09 33.02 26.93
October 0.881166E+10 10947.98 29-OCT-11:43 31.50 26.00 0.426132E+09 665.46 04-OCT-12:09 31.50 26.00
November 0.945165E+10 11006.86 23-NOV-11:32 30.77 24.95 0.428031E+09 670.78 22-NOV-13:09 30.77 24.95
December 0.970854E+10 11406.76 03-DEC-12:22 31.25 24.81 0.422885E+09 706.65 26-DEC-13:09 32.00 23.12
                     
Annual Sum or Average 0.111964E+12         0.516496E+10        
Minimum of Months 0.829226E+10 10166.60   30.03 21.52 0.400269E+09 625.79   30.03 21.52
Maximum of Months 0.102541E+11 11578.89   37.00 28.16 0.467672E+09 748.27   36.90 28.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524125E+10 11528.78 16-JAN-17:32 28.07 21.84 0.266158E+09 347.84 09-JAN-14:00 28.07 21.84
February 0.510551E+10 10790.28 26-FEB-15:32 34.40 24.93 0.241545E+09 347.84 21-FEB-10:09 34.40 24.93
March 0.621725E+10 11440.42 05-MAR-16:32 28.73 23.49 0.288397E+09 347.84 03-MAR-10:09 28.73 23.49
April 0.597424E+10 11632.37 30-APR-16:02 32.17 27.26 0.256276E+09 347.84 20-APR-13:00 32.17 27.26
May 0.602803E+10 11226.06 14-MAY-16:11 33.87 27.36 0.277474E+09 347.84 30-MAY-13:00 28.00 26.50
June 0.615972E+10 11080.61 11-JUN-16:32 33.50 27.84 0.276638E+09 347.84 16-JUN-13:00 36.00 27.59
July 0.537124E+10 11636.95 04-JUL-17:02 29.13 25.16 0.257096E+09 347.84 10-JUL-13:00 28.00 26.07
August 0.571135E+10 11336.80 27-AUG-16:01 32.83 25.70 0.288392E+09 347.84 15-AUG-13:00 32.83 25.70
September 0.530021E+10 11633.11 10-SEP-15:12 30.67 26.54 0.256122E+09 347.84 07-SEP-13:00 30.67 26.54
October 0.501978E+10 10154.84 15-OCT-17:03 28.42 25.82 0.266252E+09 347.84 13-OCT-13:00 28.42 25.82
November 0.492025E+10 10350.18 19-NOV-14:52 31.50 24.93 0.263584E+09 347.84 09-NOV-14:00 31.50 24.93
December 0.487604E+10 11296.26 31-DEC-15:22 31.70 24.08 0.256761E+09 347.84 08-DEC-14:00 31.70 24.08
                     
Annual Sum or Average 0.659249E+11         0.319469E+10        
Minimum of Months 0.487604E+10 10154.84   28.07 21.84 0.241545E+09 347.84   28.00 21.84
Maximum of Months 0.621725E+10 11636.95   34.40 27.84 0.288397E+09 347.84   36.00 27.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.603502E+10 8670.61 02-JAN-06:12 23.37 23.04 0.419929E+09 549.48 09-JAN-14:00 31.00 24.49
February 0.577788E+10 9061.14 27-FEB-05:02 24.00 22.49 0.381189E+09 549.48 15-FEB-14:00 24.00 22.49
March 0.699479E+10 10523.54 26-MAR-14:02 34.83 25.46 0.455154E+09 549.47 03-MAR-10:09 34.83 25.46
April 0.690740E+10 10729.66 30-APR-16:02 32.17 27.26 0.404497E+09 549.47 20-APR-13:09 32.17 27.26
May 0.800102E+10 10990.27 07-MAY-10:32 33.07 26.79 0.438413E+09 549.48 30-MAY-13:00 28.00 26.50
June 0.858766E+10 11210.71 18-JUN-12:02 33.23 27.06 0.437065E+09 549.48 16-JUN-13:00 33.23 27.06
July 0.716900E+10 11241.94 04-JUL-16:32 30.17 25.26 0.406110E+09 549.47 11-JUL-13:00 25.00 23.59
August 0.703705E+10 9911.12 13-AUG-12:53 34.00 28.60 0.455292E+09 549.47 25-AUG-13:00 29.00 26.74
September 0.629041E+10 9626.86 10-SEP-15:12 30.67 26.54 0.404235E+09 549.47 07-SEP-13:00 30.67 26.54
October 0.603648E+10 9058.81 02-OCT-04:02 24.00 23.36 0.420330E+09 549.47 13-OCT-13:09 31.75 26.46
November 0.588366E+10 9149.42 13-NOV-05:02 25.00 24.24 0.416082E+09 549.47 09-NOV-14:00 25.00 24.24
December 0.565860E+10 7790.55 26-DEC-07:03 23.17 21.69 0.404938E+09 549.48 04-DEC-14:00 23.17 21.69
                     
Annual Sum or Average 0.803790E+11         0.504323E+10        
Minimum of Months 0.565860E+10 7790.55   23.17 21.69 0.381189E+09 549.47   23.17 21.69
Maximum of Months 0.858766E+10 11241.94   34.83 28.60 0.455292E+09 549.48   34.83 27.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488021E+10 10223.49 16-JAN-10:02 28.17 21.45 0.197042E+09 338.72 23-JAN-08:20 22.27 18.63
February 0.480534E+10 11088.04 20-FEB-09:13 28.47 23.42 0.178837E+09 338.73 24-FEB-08:20 23.67 18.66
March 0.587887E+10 11648.35 26-MAR-09:22 31.90 24.91 0.212914E+09 338.72 21-MAR-12:20 31.90 24.91
April 0.570105E+10 11432.82 30-APR-08:42 30.18 26.77 0.189684E+09 338.72 13-APR-12:20 30.18 26.77
May 0.569089E+10 11462.66 29-MAY-09:02 31.17 27.92 0.205186E+09 338.72 02-MAY-12:20 31.17 27.92
June 0.579867E+10 10005.95 11-JUN-11:53 34.00 27.86 0.204282E+09 338.72 15-JUN-12:20 35.33 28.32
July 0.492584E+10 9269.34 30-JUL-09:13 28.83 24.44 0.190268E+09 338.72 14-JUL-12:20 28.83 24.44
August 0.531052E+10 11401.84 27-AUG-10:02 31.58 26.86 0.212738E+09 338.72 15-AUG-12:20 31.58 26.86
September 0.492183E+10 11033.28 10-SEP-09:13 29.87 26.08 0.189399E+09 338.72 12-SEP-12:20 32.73 26.56
October 0.468234E+10 11037.42 08-OCT-09:13 29.83 26.26 0.196993E+09 338.72 13-OCT-12:20 31.97 26.42
November 0.456192E+10 9071.81 23-NOV-09:32 28.77 23.95 0.195106E+09 338.72 08-NOV-13:20 28.77 23.95
December 0.452008E+10 9566.14 31-DEC-09:23 29.40 23.97 0.190082E+09 338.73 21-DEC-08:30 29.40 23.97
                     
Annual Sum or Average 0.616776E+11         0.236253E+10        
Minimum of Months 0.452008E+10 9071.81   28.17 21.45 0.178837E+09 338.72   22.27 18.63
Maximum of Months 0.587887E+10 11648.35   34.00 27.92 0.212914E+09 338.73   35.33 28.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.867048E+10 11743.25 16-JAN-12:02 30.38 21.74 0.424763E+09 591.21 17-JAN-14:09 30.95 22.65
February 0.775539E+10 11112.33 26-FEB-12:13 32.83 24.74 0.383678E+09 585.99 21-FEB-14:09 32.83 24.74
March 0.799075E+10 10890.79 19-MAR-12:13 35.93 23.76 0.455479E+09 549.48 06-MAR-14:00 35.93 23.76
April 0.680080E+10 10311.03 30-APR-16:02 32.17 27.26 0.404449E+09 549.47 20-APR-13:09 32.17 27.26
May 0.723390E+10 9221.25 01-MAY-04:02 28.25 26.74 0.438091E+09 549.47 30-MAY-13:00 28.00 26.50
June 0.714644E+10 8884.55 26-JUN-04:02 24.00 23.59 0.436643E+09 549.47 28-JUN-13:00 34.00 27.29
July 0.636734E+10 8913.08 04-JUL-14:32 32.03 24.83 0.405733E+09 549.47 11-JUL-13:00 25.00 23.59
August 0.666062E+10 8762.95 15-AUG-04:02 26.17 25.52 0.455139E+09 549.47 25-AUG-13:00 29.00 26.74
September 0.656114E+10 10423.52 10-SEP-15:12 30.67 26.54 0.404334E+09 549.47 07-SEP-13:00 30.67 26.54
October 0.702010E+10 11109.44 29-OCT-11:43 31.50 26.00 0.420779E+09 549.48 13-OCT-13:00 31.50 26.00
November 0.769299E+10 11321.33 19-NOV-11:53 32.40 24.57 0.417402E+09 561.27 20-NOV-14:09 31.00 24.79
December 0.823539E+10 11642.75 25-DEC-12:42 30.00 24.44 0.410309E+09 595.92 26-DEC-14:09 31.17 22.67
                     
Annual Sum or Average 0.881353E+11         0.505680E+10        
Minimum of Months 0.636734E+10 8762.95   24.00 21.74 0.383678E+09 549.47   25.00 22.65
Maximum of Months 0.867048E+10 11743.25   35.93 27.26 0.455479E+09 595.92   35.93 27.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.499017E+10 12528.85 16-JAN-16:42 29.38 22.09 0.265432E+09 347.84 11-JAN-14:00 29.38 22.09
February 0.487434E+10 11873.17 26-FEB-15:32 34.40 24.93 0.240990E+09 347.84 15-FEB-14:00 34.40 24.93
March 0.597523E+10 12295.20 05-MAR-16:32 28.73 23.49 0.287942E+09 347.84 03-MAR-10:09 28.73 23.49
April 0.570260E+10 12467.33 30-APR-16:02 32.17 27.26 0.255963E+09 347.84 20-APR-13:00 32.17 27.26
May 0.568781E+10 12039.36 14-MAY-16:11 33.87 27.36 0.277060E+09 347.84 30-MAY-13:00 28.00 26.50
June 0.576140E+10 11829.52 11-JUN-16:32 33.50 27.84 0.276254E+09 347.84 16-JUN-13:00 36.00 27.59
July 0.494532E+10 12726.13 04-JUL-16:32 30.17 25.26 0.256394E+09 347.84 11-JUL-13:00 25.00 23.59
August 0.527550E+10 12160.50 27-AUG-16:01 32.83 25.70 0.287742E+09 347.84 15-AUG-13:00 32.83 25.70
September 0.491205E+10 12478.39 10-SEP-15:12 30.67 26.54 0.255504E+09 347.84 07-SEP-13:00 30.67 26.54
October 0.473534E+10 10618.31 15-OCT-17:03 28.42 25.82 0.265537E+09 347.84 13-OCT-13:00 28.42 25.82
November 0.465146E+10 11299.44 19-NOV-16:33 29.70 25.49 0.262984E+09 347.84 21-NOV-14:00 31.50 24.93
December 0.463584E+10 12268.48 25-DEC-16:42 29.33 23.71 0.255799E+09 347.84 08-DEC-14:00 29.33 23.71
                     
Annual Sum or Average 0.621471E+11         0.318760E+10        
Minimum of Months 0.463584E+10 10618.31   28.42 22.09 0.240990E+09 347.84   25.00 22.09
Maximum of Months 0.597523E+10 12726.13   34.40 27.84 0.287942E+09 347.84   36.00 27.59



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16912281.10 3695.73 09-JAN-05:02 23.92
February 16356550.85 5181.87 06-FEB-06:02 23.95
March 16026030.03 4035.63 20-MAR-04:02 27.08
April 13343209.32 3764.51 10-APR-04:02 25.17
May 13814033.41 3490.30 15-MAY-04:02 26.33
June 12858960.28 3756.76 12-JUN-04:02 26.33
July 13818150.66 4222.62 17-JUL-04:02 24.42
August 13232177.12 3966.94 28-AUG-04:02 25.33
September 13214761.66 3805.60 25-SEP-04:02 26.00
October 12973763.01 4047.97 02-OCT-04:02 24.00
November 13047689.59 4250.39 13-NOV-05:02 25.00
December 15991705.86 2820.81 09-DEC-06:03 24.15
         
Annual Sum or Average 0.171589E+09      
Minimum of Months 12858960.28 2820.81   23.92
Maximum of Months 16912281.10 5181.87   27.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10125165.77 1952.11 09-JAN-05:02 23.92
February 7966239.75 1803.59 06-FEB-06:02 23.95
March 10862234.32 2159.63 28-MAR-04:02 27.25
April 10154690.69 2227.04 12-APR-04:02 27.08
May 10993907.31 2465.66 10-MAY-04:02 28.33
June 10181283.19 2284.66 06-JUN-04:02 26.83
July 8309596.49 2089.60 24-JUL-04:02 25.67
August 8940072.14 2549.73 02-AUG-04:02 29.25
September 9427197.98 2106.76 18-SEP-04:03 25.42
October 8980752.64 2034.72 16-OCT-04:02 26.00
November 9430039.62 2192.59 24-NOV-05:02 24.42
December 10172180.48 1763.35 17-DEC-10:13 26.27
         
Annual Sum or Average 0.115543E+09      
Minimum of Months 7966239.75 1763.35   23.92
Maximum of Months 10993907.31 2549.73   29.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20665652.65 3663.96 05-JAN-05:02 24.23
February 17053643.47 3558.12 15-FEB-05:02 24.67
March 19428857.57 3811.36 30-MAR-04:02 26.83
April 21013468.23 3887.65 07-APR-04:02 27.08
May 22631109.48 4032.09 10-MAY-04:02 28.33
June 20126159.73 4065.70 29-JUN-04:02 26.58
July 23000704.34 3826.20 06-JUL-04:02 25.17
August 22494461.54 4288.59 02-AUG-04:02 29.25
September 21058429.65 4038.04 28-SEP-04:02 25.67
October 23975573.27 3751.83 05-OCT-04:02 26.00
November 22394717.80 3777.44 14-NOV-05:02 26.00
December 19101719.99 3154.68 30-DEC-05:03 24.00
         
Annual Sum or Average 0.252944E+09      
Minimum of Months 17053643.47 3154.68   24.00
Maximum of Months 23975573.27 4288.59   29.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:02 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.250423E+12    
Minimum of Months 0.544142E+10 6443.98   0.191215E+11 14019.75  
Maximum of Months 0.648083E+10 6443.98   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.745435E+09 1184.79 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.664175E+09 947.97 07-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.768129E+09 947.97 01-MAR-16:49 0.212947E+10 1435.25 01-MAR-08:09
April 0.668725E+09 711.15 14-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.722885E+09 774.31 17-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.710918E+09 711.15 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.669309E+09 711.15 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.750374E+09 711.15 02-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.683661E+09 711.15 07-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.720365E+09 947.97 30-OCT-15:00 0.204804E+10 1435.25 02-OCT-07:10
November 0.744246E+09 1184.79 06-NOV-16:00 0.200273E+10 1435.25 01-NOV-07:10
December 0.733009E+09 1184.79 01-DEC-16:00 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.858123E+10     0.243325E+11    
Minimum of Months 0.664175E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.768129E+09 1184.79   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.471708E+09 750.07 02-JAN-16:40 0.129621E+10 908.57 02-JAN-08:09
February 0.422222E+09 600.14 01-FEB-16:49 0.117344E+10 908.57 01-FEB-08:09
March 0.487889E+09 600.14 01-MAR-16:40 0.134804E+10 908.57 01-MAR-08:09
April 0.426731E+09 450.21 10-APR-15:09 0.125169E+10 908.57 03-APR-07:10
May 0.462926E+09 490.21 22-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.456809E+09 450.21 01-JUN-15:39 0.129819E+10 908.57 01-JUN-07:10
July 0.430246E+09 450.21 03-JUL-15:39 0.127534E+10 908.57 03-JUL-07:10
August 0.479176E+09 450.21 02-AUG-15:30 0.134804E+10 908.57 01-AUG-07:10
September 0.434906E+09 490.21 22-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.456963E+09 600.14 11-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.474037E+09 860.01 09-NOV-16:00 0.126781E+10 908.57 01-NOV-07:10
December 0.463911E+09 860.01 04-DEC-16:00 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.546752E+10     0.154036E+11    
Minimum of Months 0.422222E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.487889E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.722044E+09 947.97 02-JAN-16:00 0.204757E+10 1435.24 02-JAN-08:09
February 0.653291E+09 754.69 01-FEB-17:30 0.185364E+10 1435.24 01-FEB-08:09
March 0.764067E+09 774.31 01-MAR-16:49 0.212945E+10 1435.24 01-MAR-08:09
April 0.674123E+09 774.31 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.733917E+09 774.31 09-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.724664E+09 774.31 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.683493E+09 774.31 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.759327E+09 774.31 02-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.683987E+09 774.31 21-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.710827E+09 774.31 23-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.721991E+09 1184.79 07-NOV-16:00 0.200271E+10 1435.24 01-NOV-07:10
December 0.705762E+09 1184.79 11-DEC-16:00 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.853749E+10     0.243324E+11    
Minimum of Months 0.653291E+09 754.69   0.185364E+10 1435.24  
Maximum of Months 0.764067E+09 1184.79   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.459784E+09 600.10 02-JAN-16:00 0.129620E+10 908.57 02-JAN-08:09
February 0.413758E+09 477.75 01-FEB-17:40 0.117344E+10 908.57 01-FEB-08:09
March 0.483358E+09 600.10 15-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.425849E+09 600.10 21-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.462272E+09 600.10 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.455503E+09 600.10 20-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.430661E+09 600.10 07-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.479672E+09 600.10 02-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.434267E+09 600.10 19-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.453453E+09 600.10 10-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.456759E+09 710.03 09-NOV-16:00 0.126780E+10 908.57 01-NOV-07:10
December 0.448746E+09 750.02 18-DEC-16:40 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.540408E+10     0.154035E+11    
Minimum of Months 0.413758E+09 477.75   0.117344E+10 908.57  
Maximum of Months 0.483358E+09 750.02   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.743012E+09 1184.79 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.662790E+09 947.97 07-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.766349E+09 947.97 01-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.667687E+09 711.15 14-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.721492E+09 711.15 09-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.710017E+09 711.15 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.668253E+09 711.15 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.749245E+09 711.15 02-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.682420E+09 711.15 07-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.718402E+09 774.31 11-OCT-15:50 0.204804E+10 1435.25 02-OCT-07:10
November 0.741482E+09 1184.79 06-NOV-16:00 0.200273E+10 1435.25 01-NOV-07:10
December 0.730186E+09 1184.79 04-DEC-16:40 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.856133E+10     0.243325E+11    
Minimum of Months 0.662790E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.766349E+09 1184.79   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.470634E+09 750.07 02-JAN-16:49 0.129621E+10 908.57 02-JAN-08:09
February 0.421275E+09 600.14 01-FEB-16:49 0.117344E+10 908.57 01-FEB-08:09
March 0.486937E+09 600.14 01-MAR-16:40 0.134804E+10 908.57 01-MAR-08:09
April 0.426128E+09 450.21 10-APR-15:20 0.125169E+10 908.57 03-APR-07:10
May 0.462193E+09 490.21 22-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.455921E+09 450.21 01-JUN-15:39 0.129819E+10 908.57 01-JUN-07:10
July 0.429139E+09 450.21 03-JUL-15:50 0.127534E+10 908.57 03-JUL-07:10
August 0.478372E+09 450.21 02-AUG-15:39 0.134804E+10 908.57 01-AUG-07:10
September 0.434119E+09 490.21 22-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.455732E+09 600.14 11-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.472649E+09 750.07 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.462671E+09 860.01 04-DEC-16:00 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.545577E+10     0.154036E+11    
Minimum of Months 0.421275E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.486937E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.721308E+09 947.97 02-JAN-16:00 0.204757E+10 1435.24 02-JAN-08:09
February 0.652756E+09 754.69 01-FEB-17:30 0.185364E+10 1435.24 01-FEB-08:09
March 0.763082E+09 774.31 01-MAR-16:49 0.212945E+10 1435.24 01-MAR-08:09
April 0.672602E+09 711.15 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.731955E+09 774.31 17-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.723028E+09 774.31 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.681915E+09 774.31 07-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.757290E+09 774.31 02-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.682575E+09 711.15 07-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.709572E+09 774.31 23-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.721755E+09 1184.79 07-NOV-16:00 0.200271E+10 1435.24 01-NOV-07:10
December 0.705146E+09 1184.79 11-DEC-16:00 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.852298E+10     0.243324E+11    
Minimum of Months 0.652756E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.763082E+09 1184.79   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.458899E+09 600.10 02-JAN-16:00 0.129620E+10 908.57 02-JAN-08:09
February 0.413338E+09 477.75 01-FEB-17:40 0.117344E+10 908.57 01-FEB-08:09
March 0.482180E+09 600.10 15-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.425106E+09 490.17 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.461286E+09 600.10 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.454390E+09 490.17 01-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.429789E+09 600.10 11-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.478690E+09 600.10 02-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.433335E+09 490.17 07-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.452128E+09 600.10 23-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.455932E+09 710.03 09-NOV-16:00 0.126780E+10 908.57 01-NOV-07:10
December 0.447837E+09 750.02 18-DEC-16:49 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.539291E+10     0.154035E+11    
Minimum of Months 0.413338E+09 477.75   0.117344E+10 908.57  
Maximum of Months 0.482180E+09 750.02   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.745435E+09 1184.79 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.664175E+09 947.97 07-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.768127E+09 947.97 01-MAR-16:49 0.212947E+10 1435.25 01-MAR-08:09
April 0.668725E+09 711.15 14-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.722847E+09 774.31 17-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.710918E+09 711.15 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.669309E+09 711.15 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.750374E+09 711.15 02-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.683661E+09 711.15 07-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.720353E+09 947.97 30-OCT-15:00 0.204804E+10 1435.25 02-OCT-07:10
November 0.744246E+09 1184.79 06-NOV-16:00 0.200273E+10 1435.25 01-NOV-07:10
December 0.733009E+09 1184.79 01-DEC-16:00 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.858118E+10     0.243325E+11    
Minimum of Months 0.664175E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.768127E+09 1184.79   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.471708E+09 750.07 02-JAN-16:40 0.129621E+10 908.57 02-JAN-08:09
February 0.422198E+09 600.14 01-FEB-16:49 0.117344E+10 908.57 01-FEB-08:09
March 0.487889E+09 600.14 01-MAR-16:40 0.134804E+10 908.57 01-MAR-08:09
April 0.426731E+09 450.21 10-APR-15:09 0.125169E+10 908.57 03-APR-07:10
May 0.462926E+09 490.21 22-MAY-15:00 0.132213E+10 908.57 01-MAY-07:10
June 0.456809E+09 450.21 01-JUN-15:39 0.129819E+10 908.57 01-JUN-07:10
July 0.430246E+09 450.21 03-JUL-15:39 0.127534E+10 908.57 03-JUL-07:10
August 0.479176E+09 450.21 02-AUG-15:30 0.134804E+10 908.57 01-AUG-07:10
September 0.434906E+09 490.21 22-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.456963E+09 600.14 11-OCT-15:00 0.129650E+10 908.57 02-OCT-07:10
November 0.474037E+09 860.01 09-NOV-16:00 0.126781E+10 908.57 01-NOV-07:10
December 0.463911E+09 860.01 04-DEC-16:00 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.546750E+10     0.154036E+11    
Minimum of Months 0.422198E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.487889E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.722044E+09 947.97 02-JAN-16:00 0.204757E+10 1435.24 02-JAN-08:09
February 0.653291E+09 754.69 01-FEB-17:30 0.185364E+10 1435.24 01-FEB-08:09
March 0.764067E+09 774.31 01-MAR-16:49 0.212945E+10 1435.24 01-MAR-08:09
April 0.674123E+09 774.31 21-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.733911E+09 774.31 09-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.724664E+09 774.31 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.683493E+09 774.31 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.759327E+09 774.31 02-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.683987E+09 774.31 21-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.710827E+09 774.31 23-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.721991E+09 1184.79 07-NOV-16:00 0.200271E+10 1435.24 01-NOV-07:10
December 0.705762E+09 1184.79 11-DEC-16:00 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.853749E+10     0.243324E+11    
Minimum of Months 0.653291E+09 754.69   0.185364E+10 1435.24  
Maximum of Months 0.764067E+09 1184.79   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.459784E+09 600.10 02-JAN-16:00 0.129620E+10 908.57 02-JAN-08:09
February 0.413758E+09 477.75 01-FEB-17:40 0.117344E+10 908.57 01-FEB-08:09
March 0.483358E+09 600.10 15-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.425849E+09 600.10 21-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.462272E+09 600.10 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.455503E+09 600.10 20-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.430653E+09 600.10 07-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.479672E+09 600.10 02-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.434267E+09 600.10 19-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.453429E+09 600.10 10-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.456759E+09 710.03 09-NOV-16:00 0.126780E+10 908.57 01-NOV-07:10
December 0.448746E+09 750.02 18-DEC-16:40 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.540405E+10     0.154035E+11    
Minimum of Months 0.413758E+09 477.75   0.117344E+10 908.57  
Maximum of Months 0.483358E+09 750.02   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.745435E+09 0.204758E+10 0.00 0.00 0.00 0.00 23500932.84 14934545.53
February 0.901968E+09 0.664175E+09 0.185366E+10 0.00 0.00 0.00 0.00 33076465.60 3664378.56
March 0.107774E+10 0.768129E+09 0.212947E+10 0.00 0.00 0.00 0.00 56876623.40 5550418.71
April 0.956342E+09 0.668725E+09 0.197726E+10 0.00 0.00 0.00 0.00 56857031.92 998060.95
May 0.103597E+10 0.722885E+09 0.208852E+10 0.00 0.00 0.00 0.00 61611235.71 3037227.44
June 0.103308E+10 0.710918E+09 0.205071E+10 0.00 0.00 0.00 0.00 54847279.68 3846691.31
July 0.959235E+09 0.669309E+09 0.201461E+10 0.00 0.00 0.00 0.00 34111294.95 3304482.09
August 0.107774E+10 0.750374E+09 0.212947E+10 0.00 0.00 0.00 0.00 41559147.37 5943317.98
September 0.956342E+09 0.683661E+09 0.197634E+10 0.00 0.00 0.00 0.00 31248439.50 3525272.28
October 0.994195E+09 0.720365E+09 0.204804E+10 0.00 0.00 0.00 0.00 25418162.82 6711557.33
November 0.984487E+09 0.744246E+09 0.200273E+10 0.00 0.00 0.00 0.00 20125545.65 7886828.10
December 0.959235E+09 0.733009E+09 0.201415E+10 0.00 0.00 0.00 0.00 19043273.68 15624427.70
                   
Annual Sum or Average 0.119305E+11 0.858123E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.458275E+09 75027207.98
Minimum of Months 0.901968E+09 0.664175E+09 0.185366E+10 0.00 0.00 0.00 0.00 19043273.68 998060.95
Maximum of Months 0.107774E+10 0.768129E+09 0.212947E+10 0.00 0.00 0.00 0.00 61611235.71 15624427.70



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.471708E+09 0.129621E+10 0.00 0.00 0.00 0.00 15407399.74 10410337.95
February 0.571020E+09 0.422222E+09 0.117344E+10 0.00 0.00 0.00 0.00 21459218.62 2771606.65
March 0.682301E+09 0.487889E+09 0.134804E+10 0.00 0.00 0.00 0.00 36873119.70 4069931.76
April 0.605444E+09 0.426731E+09 0.125169E+10 0.00 0.00 0.00 0.00 37403297.93 761303.55
May 0.655854E+09 0.462926E+09 0.132213E+10 0.00 0.00 0.00 0.00 41767631.77 1940958.70
June 0.654023E+09 0.456809E+09 0.129819E+10 0.00 0.00 0.00 0.00 37716310.91 2378929.84
July 0.607275E+09 0.430246E+09 0.127534E+10 0.00 0.00 0.00 0.00 23482320.66 2017840.20
August 0.682301E+09 0.479176E+09 0.134804E+10 0.00 0.00 0.00 0.00 27683688.76 3942369.10
September 0.605444E+09 0.434906E+09 0.125111E+10 0.00 0.00 0.00 0.00 20335508.26 2437561.73
October 0.629407E+09 0.456963E+09 0.129650E+10 0.00 0.00 0.00 0.00 16571802.19 4586217.69
November 0.623262E+09 0.474037E+09 0.126781E+10 0.00 0.00 0.00 0.00 12951124.30 5444699.12
December 0.607275E+09 0.463911E+09 0.127504E+10 0.00 0.00 0.00 0.00 12290400.14 10770272.82
                   
Annual Sum or Average 0.755301E+10 0.546752E+10 0.154036E+11 0.00 0.00 0.00 0.00 0.303942E+09 51532029.10
Minimum of Months 0.571020E+09 0.422222E+09 0.117344E+10 0.00 0.00 0.00 0.00 12290400.14 761303.55
Maximum of Months 0.682301E+09 0.487889E+09 0.134804E+10 0.00 0.00 0.00 0.00 41767631.77 10770272.82



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.722044E+09 0.204757E+10 0.00 0.00 0.00 0.00 21095312.80 17016757.71
February 0.901968E+09 0.653291E+09 0.185364E+10 0.00 0.00 0.00 0.00 30934714.40 4477946.15
March 0.107774E+10 0.764067E+09 0.212945E+10 0.00 0.00 0.00 0.00 55130897.46 6188123.82
April 0.956342E+09 0.674123E+09 0.197725E+10 0.00 0.00 0.00 0.00 57214745.99 978792.34
May 0.103597E+10 0.733917E+09 0.208851E+10 0.00 0.00 0.00 0.00 63217692.53 2889641.00
June 0.103308E+10 0.724664E+09 0.205070E+10 0.00 0.00 0.00 0.00 57300900.28 3485524.28
July 0.959235E+09 0.683493E+09 0.201460E+10 0.00 0.00 0.00 0.00 35724367.32 2945854.20
August 0.107774E+10 0.759327E+09 0.212945E+10 0.00 0.00 0.00 0.00 42535587.37 5671783.42
September 0.956342E+09 0.683987E+09 0.197632E+10 0.00 0.00 0.00 0.00 30883486.17 3611595.46
October 0.994195E+09 0.710827E+09 0.204803E+10 0.00 0.00 0.00 0.00 23952142.84 7342521.08
November 0.984487E+09 0.721991E+09 0.200271E+10 0.00 0.00 0.00 0.00 18304341.99 8863708.55
December 0.959235E+09 0.705762E+09 0.201413E+10 0.00 0.00 0.00 0.00 16692125.67 17409205.73
                   
Annual Sum or Average 0.119305E+11 0.853749E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.452986E+09 80881453.73
Minimum of Months 0.901968E+09 0.653291E+09 0.185364E+10 0.00 0.00 0.00 0.00 16692125.67 978792.34
Maximum of Months 0.107774E+10 0.764067E+09 0.212945E+10 0.00 0.00 0.00 0.00 63217692.53 17409205.73



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.459784E+09 0.129620E+10 0.00 0.00 0.00 0.00 15428746.56 10576405.94
February 0.570983E+09 0.413758E+09 0.117344E+10 0.00 0.00 0.00 0.00 21853181.45 2832001.69
March 0.682256E+09 0.483358E+09 0.134804E+10 0.00 0.00 0.00 0.00 36845946.25 4671973.70
April 0.605404E+09 0.425849E+09 0.125169E+10 0.00 0.00 0.00 0.00 36845020.46 805688.00
May 0.655811E+09 0.462272E+09 0.132212E+10 0.00 0.00 0.00 0.00 41735376.10 2051571.83
June 0.653980E+09 0.455503E+09 0.129818E+10 0.00 0.00 0.00 0.00 37337791.94 2547493.10
July 0.607235E+09 0.430661E+09 0.127533E+10 0.00 0.00 0.00 0.00 23756866.71 2185320.74
August 0.682256E+09 0.479672E+09 0.134804E+10 0.00 0.00 0.00 0.00 28055488.38 4318118.40
September 0.605404E+09 0.434267E+09 0.125110E+10 0.00 0.00 0.00 0.00 20701838.84 2585726.83
October 0.629366E+09 0.453453E+09 0.129649E+10 0.00 0.00 0.00 0.00 17113507.82 4804792.57
November 0.623221E+09 0.456759E+09 0.126780E+10 0.00 0.00 0.00 0.00 13521395.58 5463358.84
December 0.607235E+09 0.448746E+09 0.127503E+10 0.00 0.00 0.00 0.00 12563247.24 10771689.37
                   
Annual Sum or Average 0.755252E+10 0.540408E+10 0.154035E+11 0.00 0.00 0.00 0.00 0.305758E+09 53614141.03
Minimum of Months 0.570983E+09 0.413758E+09 0.117344E+10 0.00 0.00 0.00 0.00 12563247.24 805688.00
Maximum of Months 0.682256E+09 0.483358E+09 0.134804E+10 0.00 0.00 0.00 0.00 41735376.10 10771689.37



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.743012E+09 0.204758E+10 0.00 0.00 0.00 0.00 12959931.12 8098394.53
February 0.901968E+09 0.662790E+09 0.185366E+10 0.00 0.00 0.00 0.00 18158055.76 2088454.10
March 0.107774E+10 0.766349E+09 0.212947E+10 0.00 0.00 0.00 0.00 31602991.40 3098863.19
April 0.956342E+09 0.667687E+09 0.197726E+10 0.00 0.00 0.00 0.00 31349396.62 527698.97
May 0.103597E+10 0.721492E+09 0.208852E+10 0.00 0.00 0.00 0.00 33560023.23 1850572.38
June 0.103308E+10 0.710017E+09 0.205071E+10 0.00 0.00 0.00 0.00 29504728.67 2219419.63
July 0.959235E+09 0.668253E+09 0.201461E+10 0.00 0.00 0.00 0.00 18611340.43 1937878.18
August 0.107774E+10 0.749245E+09 0.212947E+10 0.00 0.00 0.00 0.00 22436247.14 3874159.79
September 0.956342E+09 0.682420E+09 0.197634E+10 0.00 0.00 0.00 0.00 17167770.81 2124479.98
October 0.994195E+09 0.718402E+09 0.204804E+10 0.00 0.00 0.00 0.00 14121313.14 3384483.21
November 0.984487E+09 0.741482E+09 0.200273E+10 0.00 0.00 0.00 0.00 11097085.58 4551141.68
December 0.959235E+09 0.730186E+09 0.201415E+10 0.00 0.00 0.00 0.00 10596562.95 9296704.59
                   
Annual Sum or Average 0.119305E+11 0.856133E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.251165E+09 43052250.23
Minimum of Months 0.901968E+09 0.662790E+09 0.185366E+10 0.00 0.00 0.00 0.00 10596562.95 527698.97
Maximum of Months 0.107774E+10 0.766349E+09 0.212947E+10 0.00 0.00 0.00 0.00 33560023.23 9296704.59



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.470634E+09 0.129621E+10 0.00 0.00 0.00 0.00 8223385.80 5926885.82
February 0.571020E+09 0.421275E+09 0.117344E+10 0.00 0.00 0.00 0.00 11466148.39 1773905.40
March 0.682301E+09 0.486937E+09 0.134804E+10 0.00 0.00 0.00 0.00 19651743.62 2662603.28
April 0.605444E+09 0.426128E+09 0.125169E+10 0.00 0.00 0.00 0.00 19809386.35 459740.21
May 0.655854E+09 0.462193E+09 0.132213E+10 0.00 0.00 0.00 0.00 22309463.76 1237197.26
June 0.654023E+09 0.455921E+09 0.129819E+10 0.00 0.00 0.00 0.00 20107225.98 1430456.35
July 0.607275E+09 0.429139E+09 0.127534E+10 0.00 0.00 0.00 0.00 12604175.84 1260854.72
August 0.682301E+09 0.478372E+09 0.134804E+10 0.00 0.00 0.00 0.00 14658956.17 2750307.35
September 0.605444E+09 0.434119E+09 0.125111E+10 0.00 0.00 0.00 0.00 10864693.45 1612684.77
October 0.629407E+09 0.455732E+09 0.129650E+10 0.00 0.00 0.00 0.00 8880520.39 2539921.71
November 0.623262E+09 0.472649E+09 0.126781E+10 0.00 0.00 0.00 0.00 6958145.70 3344828.62
December 0.607275E+09 0.462671E+09 0.127504E+10 0.00 0.00 0.00 0.00 6623934.80 6618271.01
                   
Annual Sum or Average 0.755301E+10 0.545577E+10 0.154036E+11 0.00 0.00 0.00 0.00 0.162158E+09 31617656.49
Minimum of Months 0.571020E+09 0.421275E+09 0.117344E+10 0.00 0.00 0.00 0.00 6623934.80 459740.21
Maximum of Months 0.682301E+09 0.486937E+09 0.134804E+10 0.00 0.00 0.00 0.00 22309463.76 6618271.01



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.721308E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.147637E+10 0.117099E+09
February 0.901968E+09 0.652756E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.154414E+10 67902508.07
March 0.107774E+10 0.763082E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.223712E+10 9154047.21
April 0.956342E+09 0.672602E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.218077E+10 766364.93
May 0.103597E+10 0.731955E+09 0.208851E+10 0.00 0.00 0.00 0.00 0.229248E+10 2950927.39
June 0.103308E+10 0.723028E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.237942E+10 6185843.47
July 0.959235E+09 0.681915E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.145415E+10 4318425.39
August 0.107774E+10 0.757290E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.191792E+10 5755703.89
September 0.956342E+09 0.682575E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.161081E+10 4898305.69
October 0.994195E+09 0.709572E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.143041E+10 15392382.79
November 0.984487E+09 0.721755E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.145650E+10 22892310.24
December 0.959235E+09 0.705146E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.122897E+10 0.104982E+09
                   
Annual Sum or Average 0.119305E+11 0.852298E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.212091E+11 0.362298E+09
Minimum of Months 0.901968E+09 0.652756E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.122897E+10 766364.93
Maximum of Months 0.107774E+10 0.763082E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.237942E+10 0.117099E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.458899E+09 0.129620E+10 0.00 0.00 0.00 0.00 8052958.42 6063975.98
February 0.570983E+09 0.413338E+09 0.117344E+10 0.00 0.00 0.00 0.00 11420616.89 1872396.83
March 0.682256E+09 0.482180E+09 0.134804E+10 0.00 0.00 0.00 0.00 19331041.43 3057280.32
April 0.605404E+09 0.425106E+09 0.125169E+10 0.00 0.00 0.00 0.00 19216425.75 512414.36
May 0.655811E+09 0.461286E+09 0.132212E+10 0.00 0.00 0.00 0.00 22041762.34 1324349.35
June 0.653980E+09 0.454390E+09 0.129818E+10 0.00 0.00 0.00 0.00 19632844.84 1521942.38
July 0.607235E+09 0.429789E+09 0.127533E+10 0.00 0.00 0.00 0.00 12454576.81 1370248.29
August 0.682256E+09 0.478690E+09 0.134804E+10 0.00 0.00 0.00 0.00 14517440.29 2955708.67
September 0.605404E+09 0.433335E+09 0.125110E+10 0.00 0.00 0.00 0.00 10852626.65 1705722.23
October 0.629366E+09 0.452128E+09 0.129649E+10 0.00 0.00 0.00 0.00 8900856.70 2673577.18
November 0.623221E+09 0.455932E+09 0.126780E+10 0.00 0.00 0.00 0.00 7029720.47 3393241.43
December 0.607235E+09 0.447837E+09 0.127503E+10 0.00 0.00 0.00 0.00 6552808.86 6714638.31
                   
Annual Sum or Average 0.755252E+10 0.539291E+10 0.154035E+11 0.00 0.00 0.00 0.00 0.160004E+09 33165495.32
Minimum of Months 0.570983E+09 0.413338E+09 0.117344E+10 0.00 0.00 0.00 0.00 6552808.86 512414.36
Maximum of Months 0.682256E+09 0.482180E+09 0.134804E+10 0.00 0.00 0.00 0.00 22041762.34 6714638.31



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.745435E+09 0.204758E+10 0.00 0.00 0.00 0.00 19887808.92 13155570.03
February 0.901968E+09 0.664175E+09 0.185366E+10 0.00 0.00 0.00 0.00 27946401.31 3339660.15
March 0.107774E+10 0.768127E+09 0.212947E+10 0.00 0.00 0.00 0.00 48400014.38 4871636.29
April 0.956342E+09 0.668725E+09 0.197726E+10 0.00 0.00 0.00 0.00 48239683.16 868262.64
May 0.103597E+10 0.722847E+09 0.208852E+10 0.00 0.00 0.00 0.00 51969278.07 2582080.89
June 0.103308E+10 0.710918E+09 0.205071E+10 0.00 0.00 0.00 0.00 46327835.70 3211759.71
July 0.959235E+09 0.669309E+09 0.201461E+10 0.00 0.00 0.00 0.00 29010684.86 2750605.02
August 0.107774E+10 0.750374E+09 0.212947E+10 0.00 0.00 0.00 0.00 35117776.91 5193110.92
September 0.956342E+09 0.683661E+09 0.197634E+10 0.00 0.00 0.00 0.00 26715028.32 2995163.00
October 0.994195E+09 0.720353E+09 0.204804E+10 0.00 0.00 0.00 0.00 21809260.99 5659750.85
November 0.984487E+09 0.744246E+09 0.200273E+10 0.00 0.00 0.00 0.00 17114665.97 7097430.70
December 0.959235E+09 0.733009E+09 0.201415E+10 0.00 0.00 0.00 0.00 16145072.64 14071131.05
                   
Annual Sum or Average 0.119305E+11 0.858118E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.388684E+09 65796161.24
Minimum of Months 0.901968E+09 0.664175E+09 0.185366E+10 0.00 0.00 0.00 0.00 16145072.64 868262.64
Maximum of Months 0.107774E+10 0.768127E+09 0.212947E+10 0.00 0.00 0.00 0.00 51969278.07 14071131.05



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.471708E+09 0.129621E+10 0.00 0.00 0.00 0.00 13011639.03 9106259.72
February 0.421807E+09 0.422198E+09 0.117344E+10 0.00 0.00 0.00 0.00 18120492.95 2495082.83
March 0.502994E+09 0.487889E+09 0.134804E+10 0.00 0.00 0.00 0.00 31203199.39 3532913.63
April 0.447140E+09 0.426731E+09 0.125169E+10 0.00 0.00 0.00 0.00 31592547.19 655773.88
May 0.484071E+09 0.462926E+09 0.132213E+10 0.00 0.00 0.00 0.00 35221316.37 1650004.26
June 0.482240E+09 0.456809E+09 0.129819E+10 0.00 0.00 0.00 0.00 31934382.38 1994934.31
July 0.448971E+09 0.430246E+09 0.127534E+10 0.00 0.00 0.00 0.00 20056899.24 1676812.67
August 0.502994E+09 0.479176E+09 0.134804E+10 0.00 0.00 0.00 0.00 23401268.58 3438982.65
September 0.447140E+09 0.434906E+09 0.125111E+10 0.00 0.00 0.00 0.00 17312977.96 2074273.71
October 0.465148E+09 0.456963E+09 0.129650E+10 0.00 0.00 0.00 0.00 14156068.02 3868849.54
November 0.460569E+09 0.474037E+09 0.126781E+10 0.00 0.00 0.00 0.00 11012419.03 4876770.63
December 0.448971E+09 0.463911E+09 0.127504E+10 0.00 0.00 0.00 0.00 10422113.09 9631020.09
                   
Annual Sum or Average 0.557719E+10 0.546750E+10 0.154036E+11 0.00 0.00 0.00 0.00 0.257445E+09 45001677.91
Minimum of Months 0.421807E+09 0.422198E+09 0.117344E+10 0.00 0.00 0.00 0.00 10422113.09 655773.88
Maximum of Months 0.502994E+09 0.487889E+09 0.134804E+10 0.00 0.00 0.00 0.00 35221316.37 9631020.09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.722044E+09 0.204757E+10 0.00 0.00 0.00 0.00 17594047.00 14923682.23
February 0.901968E+09 0.653291E+09 0.185364E+10 0.00 0.00 0.00 0.00 25860647.10 4049622.60
March 0.107774E+10 0.764067E+09 0.212945E+10 0.00 0.00 0.00 0.00 46548503.55 5405691.51
April 0.956342E+09 0.674123E+09 0.197725E+10 0.00 0.00 0.00 0.00 48546123.37 852173.53
May 0.103597E+10 0.733911E+09 0.208851E+10 0.00 0.00 0.00 0.00 53464980.63 2466331.42
June 0.103308E+10 0.724664E+09 0.205070E+10 0.00 0.00 0.00 0.00 48701374.93 2912363.23
July 0.959235E+09 0.683493E+09 0.201460E+10 0.00 0.00 0.00 0.00 30652665.79 2434348.09
August 0.107774E+10 0.759327E+09 0.212945E+10 0.00 0.00 0.00 0.00 35996581.57 4991972.06
September 0.956342E+09 0.683987E+09 0.197632E+10 0.00 0.00 0.00 0.00 26321869.42 3066821.63
October 0.994195E+09 0.710827E+09 0.204803E+10 0.00 0.00 0.00 0.00 20234309.46 6193843.04
November 0.984487E+09 0.721991E+09 0.200271E+10 0.00 0.00 0.00 0.00 15343118.10 7914621.19
December 0.959235E+09 0.705762E+09 0.201413E+10 0.00 0.00 0.00 0.00 13947782.05 15560336.51
                   
Annual Sum or Average 0.119305E+11 0.853749E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.383212E+09 70771807.03
Minimum of Months 0.901968E+09 0.653291E+09 0.185364E+10 0.00 0.00 0.00 0.00 13947782.05 852173.53
Maximum of Months 0.107774E+10 0.764067E+09 0.212945E+10 0.00 0.00 0.00 0.00 53464980.63 15560336.51



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.459784E+09 0.129620E+10 0.00 0.00 0.00 0.00 12731168.96 9378626.26
February 0.570983E+09 0.413758E+09 0.117344E+10 0.00 0.00 0.00 0.00 18097606.23 2595412.71
March 0.682256E+09 0.483358E+09 0.134804E+10 0.00 0.00 0.00 0.00 30714130.98 4066890.67
April 0.605404E+09 0.425849E+09 0.125169E+10 0.00 0.00 0.00 0.00 30647344.71 715835.93
May 0.655811E+09 0.462272E+09 0.132212E+10 0.00 0.00 0.00 0.00 34745741.71 1759768.80
June 0.653980E+09 0.455503E+09 0.129818E+10 0.00 0.00 0.00 0.00 31273456.59 2167653.10
July 0.607235E+09 0.430653E+09 0.127533E+10 0.00 0.00 0.00 0.00 19898266.96 1845731.50
August 0.682256E+09 0.479672E+09 0.134804E+10 0.00 0.00 0.00 0.00 23251941.04 3760195.93
September 0.605404E+09 0.434267E+09 0.125110E+10 0.00 0.00 0.00 0.00 17321557.76 2228122.80
October 0.629366E+09 0.453429E+09 0.129649E+10 0.00 0.00 0.00 0.00 14273460.49 4105048.88
November 0.623221E+09 0.456759E+09 0.126780E+10 0.00 0.00 0.00 0.00 11195566.18 4966382.03
December 0.607235E+09 0.448746E+09 0.127503E+10 0.00 0.00 0.00 0.00 10329181.81 9749991.86
                   
Annual Sum or Average 0.755252E+10 0.540405E+10 0.154035E+11 0.00 0.00 0.00 0.00 0.254479E+09 47339660.48
Minimum of Months 0.570983E+09 0.413758E+09 0.117344E+10 0.00 0.00 0.00 0.00 10329181.81 715835.93
Maximum of Months 0.682256E+09 0.483358E+09 0.134804E+10 0.00 0.00 0.00 0.00 34745741.71 9749991.86



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19867485.11 17807598.13
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30317113.59 4160918.41
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54383515.70 6026819.29
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57673865.09 903095.19
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63319729.36 3027309.45
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56862391.55 3592643.97
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34560303.57 2878203.53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40113387.05 5772284.74
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30094027.44 3403059.46
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23567832.34 6771153.84
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17601560.52 9168084.26
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16093687.71 19440912.87
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.444455E+09 82952083.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16093687.71 903095.19
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63319729.36 19440912.87



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26519573.97 21850948.45
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40225540.20 4774613.47
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71445685.66 7031839.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75365048.54 1032522.51
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82132187.85 3592307.38
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73885879.22 4418483.94
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45858064.28 3386970.56
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53228454.55 6263154.60
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39716739.98 3834374.89
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31326764.02 8151532.72
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23491114.84 10670066.57
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21628165.68 23419715.06
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.584823E+09 98426529.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21628165.68 1032522.51
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82132187.85 23419715.06



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24845272.15 19108246.35
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38624763.45 3004521.22
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 71555565.37 4833090.87
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75905630.30 690078.31
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83793997.43 3169848.53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73593165.45 4668910.02
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39988236.55 3572403.04
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52352940.27 5499750.43
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36613519.41 4213256.81
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27429236.99 8220811.53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21415891.61 9321790.97
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18749647.13 20001906.53
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.564868E+09 86304614.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18749647.13 690078.31
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83793997.43 20001906.53



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1184.79 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 90.18 15-JAN-13:10 204.83 07-JAN-05:00
February 1306.65 01-FEB-10:09 947.97 07-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 165.94 20-FEB-15:58 23.11 19-FEB-07:00
March 1306.65 01-MAR-10:09 947.97 01-MAR-16:49 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 282.84 19-MAR-16:00 41.73 14-MAR-22:00
April 1306.65 03-APR-09:09 711.15 14-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 146.23 30-APR-15:36 15.84 22-APR-03:00
May 1306.65 01-MAY-09:09 774.31 17-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 201.25 07-MAY-15:00 83.65 08-MAY-22:00
June 1306.65 01-JUN-09:09 711.15 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 184.73 18-JUN-14:20 96.71 20-JUN-23:00
July 1306.65 03-JUL-09:09 711.15 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 164.45 04-JUL-14:08 45.85 02-JUL-13:50
August 1306.65 01-AUG-09:09 711.15 02-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 200.29 06-AUG-13:00 89.70 20-AUG-11:00
September 1306.65 01-SEP-09:09 711.15 07-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 195.01 10-SEP-15:00 48.48 15-SEP-22:00
October 1306.65 02-OCT-09:09 947.97 30-OCT-15:00 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 179.31 29-OCT-13:10 42.74 22-OCT-18:00
November 1306.65 01-NOV-09:09 1184.79 06-NOV-16:00 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 93.57 11-NOV-16:00 42.32 25-NOV-05:00
December 1306.65 01-DEC-10:09 1184.79 01-DEC-16:00 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 73.93 31-DEC-09:53 78.12 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 73.93   15.84  
Maximum of Months 1306.65   1184.79   1435.25   0.00 0.00 0.00 0.00 282.84   204.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 750.07 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 58.20 15-JAN-13:10 136.49 07-JAN-05:00
February 827.22 01-FEB-10:09 600.14 01-FEB-16:49 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 113.66 20-FEB-16:00 24.63 19-FEB-07:00
March 827.22 01-MAR-10:09 600.14 01-MAR-16:40 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 194.61 19-MAR-15:37 28.38 05-MAR-07:20
April 827.22 03-APR-09:09 450.21 10-APR-15:09 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 100.78 30-APR-15:38 15.84 23-APR-07:08
May 827.22 01-MAY-09:09 490.21 22-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 141.38 07-MAY-14:38 55.72 08-MAY-22:00
June 827.22 01-JUN-09:09 450.21 01-JUN-15:39 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 133.22 18-JUN-14:48 63.34 20-JUN-23:00
July 827.22 03-JUL-09:09 450.21 03-JUL-15:39 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 124.06 04-JUL-14:10 26.50 02-JUL-13:50
August 827.22 01-AUG-09:09 450.21 02-AUG-15:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 136.23 06-AUG-13:00 63.55 20-AUG-11:00
September 827.22 01-SEP-09:09 490.21 22-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 134.77 10-SEP-14:50 31.66 15-SEP-22:00
October 827.22 02-OCT-09:09 600.14 11-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 125.76 29-OCT-13:10 28.45 22-OCT-18:00
November 827.22 01-NOV-09:09 860.01 09-NOV-16:00 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 62.99 11-NOV-16:00 30.93 26-NOV-10:00
December 827.22 01-DEC-10:09 860.01 04-DEC-16:00 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 48.36 31-DEC-13:00 51.92 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 48.36   15.84  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 194.61   136.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 947.97 02-JAN-16:00 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 75.17 15-JAN-13:05 211.73 07-JAN-05:00
February 1306.65 01-FEB-10:09 754.69 01-FEB-17:30 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 154.49 19-FEB-14:53 26.81 19-FEB-07:00
March 1306.65 01-MAR-10:09 774.31 01-MAR-16:49 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 282.83 19-MAR-16:00 42.49 14-MAR-22:00
April 1306.65 03-APR-09:09 774.31 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 146.52 30-APR-15:38 15.61 22-APR-03:00
May 1306.65 01-MAY-09:09 774.31 09-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 206.09 07-MAY-14:36 82.68 08-MAY-22:00
June 1306.65 01-JUN-09:09 774.31 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 195.19 18-JUN-14:06 93.59 20-JUN-23:00
July 1306.65 03-JUL-09:09 774.31 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 177.13 04-JUL-14:08 34.13 02-JUL-13:50
August 1306.65 01-AUG-09:09 774.31 02-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 209.00 06-AUG-13:00 88.90 20-AUG-11:00
September 1306.65 01-SEP-09:09 774.31 21-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 191.31 10-SEP-14:46 49.08 15-SEP-22:00
October 1306.65 02-OCT-09:09 774.31 23-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 173.71 29-OCT-13:05 43.60 22-OCT-18:00
November 1306.65 01-NOV-09:09 1184.79 07-NOV-16:00 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 83.24 11-NOV-15:50 46.38 26-NOV-10:00
December 1306.65 01-DEC-10:09 1184.79 11-DEC-16:00 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 63.74 31-DEC-12:56 79.81 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   754.69   1435.24   0.00 0.00 0.00 0.00 63.74   15.61  
Maximum of Months 1306.65   1184.79   1435.24   0.00 0.00 0.00 0.00 282.83   211.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 600.10 02-JAN-16:00 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 64.45 15-JAN-13:10 136.74 07-JAN-05:00
February 827.17 01-FEB-10:09 477.75 01-FEB-17:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 109.06 20-FEB-15:56 16.33 19-FEB-07:00
March 827.17 01-MAR-10:09 600.10 15-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 188.55 19-MAR-16:00 28.00 03-MAR-05:40
April 827.17 03-APR-09:09 600.10 21-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 95.48 30-APR-15:36 12.53 09-APR-16:50
May 827.17 01-MAY-09:09 600.10 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 139.57 21-MAY-11:37 55.60 08-MAY-22:00
June 827.17 01-JUN-09:09 600.10 20-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 130.21 18-JUN-14:06 64.84 20-JUN-23:00
July 827.17 03-JUL-09:09 600.10 07-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 122.69 04-JUL-14:08 26.14 02-JUL-13:50
August 827.17 01-AUG-09:09 600.10 02-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 145.97 06-AUG-13:00 59.49 20-AUG-11:00
September 827.17 01-SEP-09:09 600.10 19-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 126.45 10-SEP-14:46 31.82 15-SEP-22:00
October 827.17 02-OCT-09:09 600.10 10-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 122.80 29-OCT-13:10 29.12 22-OCT-18:00
November 827.17 01-NOV-09:09 710.03 09-NOV-16:00 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 59.28 11-NOV-15:50 28.39 26-NOV-10:00
December 827.17 01-DEC-10:09 750.02 18-DEC-16:40 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 53.91 31-DEC-09:53 52.18 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   477.75   908.57   0.00 0.00 0.00 0.00 53.91   12.53  
Maximum of Months 827.17   750.02   908.57   0.00 0.00 0.00 0.00 188.55   136.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1184.79 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 56.18 15-JAN-13:00 130.44 07-JAN-05:00
February 1306.65 01-FEB-10:09 947.97 07-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 89.83 20-FEB-16:00 14.21 19-FEB-07:00
March 1306.65 01-MAR-10:09 947.97 01-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 162.85 19-MAR-16:00 24.73 03-MAR-05:30
April 1306.65 03-APR-09:09 711.15 14-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 78.55 30-APR-15:30 9.99 22-APR-03:00
May 1306.65 01-MAY-09:09 711.15 09-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 109.50 07-MAY-14:36 49.32 08-MAY-22:00
June 1306.65 01-JUN-09:09 711.15 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 100.67 18-JUN-14:06 54.44 20-JUN-23:00
July 1306.65 03-JUL-09:09 711.15 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 91.70 04-JUL-13:48 18.41 02-JUL-13:50
August 1306.65 01-AUG-09:09 711.15 02-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 107.91 06-AUG-13:00 50.95 20-AUG-11:00
September 1306.65 01-SEP-09:09 711.15 07-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 113.45 10-SEP-15:00 31.88 15-SEP-22:00
October 1306.65 02-OCT-09:09 774.31 11-OCT-15:50 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 102.62 29-OCT-13:10 20.19 01-OCT-23:00
November 1306.65 01-NOV-09:09 1184.79 06-NOV-16:00 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 55.07 11-NOV-16:00 24.78 25-NOV-05:00
December 1306.65 01-DEC-10:09 1184.79 04-DEC-16:40 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 41.02 31-DEC-12:50 47.09 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 41.02   9.99  
Maximum of Months 1306.65   1184.79   1435.25   0.00 0.00 0.00 0.00 162.85   130.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 750.07 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 33.25 15-JAN-13:00 90.80 07-JAN-05:00
February 827.22 01-FEB-10:09 600.14 01-FEB-16:49 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 56.50 20-FEB-16:00 14.94 20-FEB-06:55
March 827.22 01-MAR-10:09 600.14 01-MAR-16:40 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 104.63 19-MAR-15:40 17.49 14-MAR-22:00
April 827.22 03-APR-09:09 450.21 10-APR-15:20 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 53.50 02-APR-15:50 8.85 23-APR-07:00
May 827.22 01-MAY-09:09 490.21 22-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 74.97 07-MAY-14:38 33.67 08-MAY-22:00
June 827.22 01-JUN-09:09 450.21 01-JUN-15:39 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 70.89 18-JUN-14:08 35.92 20-JUN-23:00
July 827.22 03-JUL-09:09 450.21 03-JUL-15:50 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 64.76 04-JUL-13:53 11.44 02-JUL-13:10
August 827.22 01-AUG-09:09 450.21 02-AUG-15:39 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 70.64 06-AUG-13:00 36.12 20-AUG-10:50
September 827.22 01-SEP-09:09 490.21 22-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 71.60 10-SEP-14:55 22.22 15-SEP-22:00
October 827.22 02-OCT-09:09 600.14 11-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 67.23 29-OCT-13:10 14.19 01-OCT-23:00
November 827.22 01-NOV-09:09 750.07 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 34.50 11-NOV-16:00 18.12 26-NOV-10:00
December 827.22 01-DEC-10:09 860.01 04-DEC-16:00 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 25.52 31-DEC-12:50 31.83 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 25.52   8.85  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 104.63   90.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 947.97 02-JAN-16:00 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 9331.75 04-JAN-12:02 5190.76 23-JAN-07:03
February 1306.65 01-FEB-10:09 754.69 01-FEB-17:30 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 9052.22 24-FEB-17:03 3429.94 02-FEB-07:03
March 1306.65 01-MAR-10:09 774.31 01-MAR-16:49 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 11249.04 21-MAR-11:02 962.41 15-MAR-06:03
April 1306.65 03-APR-09:09 711.15 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 11707.00 11-APR-16:02 198.83 14-APR-16:00
May 1306.65 01-MAY-09:09 774.31 17-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 13714.82 05-MAY-11:01 181.62 18-MAY-05:03
June 1306.65 01-JUN-09:09 774.31 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 12348.05 12-JUN-16:02 760.92 21-JUN-06:03
July 1306.65 03-JUL-09:09 774.31 07-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 9871.87 20-JUL-16:02 433.59 13-JUL-05:03
August 1306.65 01-AUG-09:09 774.31 02-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 10989.32 15-AUG-11:02 411.58 21-AUG-11:10
September 1306.65 01-SEP-09:09 711.15 07-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 9457.38 13-SEP-16:03 1246.85 15-SEP-17:00
October 1306.65 02-OCT-09:09 774.31 23-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 9039.01 04-OCT-11:02 1243.84 30-OCT-17:00
November 1306.65 01-NOV-09:09 1184.79 07-NOV-16:00 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 8647.73 10-NOV-12:02 2414.36 27-NOV-07:03
December 1306.65 01-DEC-10:09 1184.79 11-DEC-16:00 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 7712.74 08-DEC-12:02 5625.98 21-DEC-07:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 7712.74   181.62  
Maximum of Months 1306.65   1184.79   1435.24   0.00 0.00 0.00 0.00 13714.82   5625.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 600.10 02-JAN-16:00 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 37.64 15-JAN-13:00 91.11 07-JAN-05:00
February 827.17 01-FEB-10:09 477.75 01-FEB-17:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 54.19 20-FEB-15:52 10.76 19-FEB-07:00
March 827.17 01-MAR-10:09 600.10 15-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 100.90 19-MAR-16:00 17.40 03-MAR-05:30
April 827.17 03-APR-09:09 490.17 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 48.74 02-APR-15:04 7.60 22-APR-03:00
May 827.17 01-MAY-09:09 600.10 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 73.81 21-MAY-11:33 33.87 08-MAY-22:00
June 827.17 01-JUN-09:09 490.17 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 68.74 18-JUN-14:06 36.78 20-JUN-23:00
July 827.17 03-JUL-09:09 600.10 11-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 62.92 04-JUL-13:48 11.44 02-JUL-13:50
August 827.17 01-AUG-09:09 600.10 02-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 73.28 06-AUG-13:00 34.10 20-AUG-11:00
September 827.17 01-SEP-09:09 490.17 07-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 67.64 10-SEP-14:55 22.77 15-SEP-22:00
October 827.17 02-OCT-09:09 600.10 23-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 64.44 29-OCT-13:10 14.75 01-OCT-23:00
November 827.17 01-NOV-09:09 710.03 09-NOV-16:00 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 30.65 11-NOV-15:40 16.92 25-NOV-05:00
December 827.17 01-DEC-10:09 750.02 18-DEC-16:49 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 26.78 31-DEC-12:50 31.95 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   477.75   908.57   0.00 0.00 0.00 0.00 26.78   7.60  
Maximum of Months 827.17   750.02   908.57   0.00 0.00 0.00 0.00 100.90   91.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1184.79 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 79.71 15-JAN-13:10 190.45 07-JAN-05:00
February 1306.65 01-FEB-10:09 947.97 07-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 139.46 20-FEB-16:00 21.43 19-FEB-07:00
March 1306.65 01-MAR-10:09 947.97 01-MAR-16:49 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 243.70 19-MAR-16:00 37.37 03-MAR-05:30
April 1306.65 03-APR-09:09 711.15 14-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 121.03 02-APR-15:50 14.62 22-APR-03:00
May 1306.65 01-MAY-09:09 774.31 17-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 168.87 07-MAY-14:36 70.59 08-MAY-22:00
June 1306.65 01-JUN-09:09 711.15 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 155.03 18-JUN-14:06 78.89 20-JUN-23:00
July 1306.65 03-JUL-09:09 711.15 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 142.15 04-JUL-13:58 29.86 02-JUL-14:00
August 1306.65 01-AUG-09:09 711.15 02-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 167.95 06-AUG-13:00 77.06 20-AUG-11:00
September 1306.65 01-SEP-09:09 711.15 07-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 172.63 10-SEP-15:00 43.99 15-SEP-22:00
October 1306.65 02-OCT-09:09 947.97 30-OCT-15:00 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 152.74 29-OCT-13:10 35.44 23-OCT-04:53
November 1306.65 01-NOV-09:09 1184.79 06-NOV-16:00 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 83.98 11-NOV-16:00 37.34 25-NOV-05:00
December 1306.65 01-DEC-10:09 1184.79 01-DEC-16:00 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 62.10 31-DEC-13:00 70.08 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 62.10   14.62  
Maximum of Months 1306.65   1184.79   1435.25   0.00 0.00 0.00 0.00 243.70   190.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 750.07 02-JAN-16:40 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 51.37 15-JAN-13:10 126.71 07-JAN-05:00
February 805.43 01-FEB-08:09 600.14 01-FEB-16:49 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 94.87 20-FEB-16:00 21.95 19-FEB-07:00
March 805.43 01-MAR-08:09 600.14 01-MAR-16:40 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 162.85 19-MAR-15:40 24.90 03-MAR-05:30
April 805.43 03-APR-07:10 450.21 10-APR-15:09 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 84.02 02-APR-15:50 13.60 23-APR-07:00
May 805.43 01-MAY-07:10 490.21 22-MAY-15:00 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 117.82 07-MAY-14:40 47.02 08-MAY-22:00
June 805.43 01-JUN-07:10 450.21 01-JUN-15:39 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 111.30 18-JUN-14:50 51.63 20-JUN-23:00
July 805.43 03-JUL-07:10 450.21 03-JUL-15:39 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 105.69 04-JUL-14:00 17.26 02-JUL-13:20
August 805.43 01-AUG-07:10 450.21 02-AUG-15:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 114.41 06-AUG-13:00 54.65 20-AUG-10:50
September 805.43 01-SEP-07:10 490.21 22-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 114.35 10-SEP-15:00 28.55 15-SEP-22:00
October 805.43 02-OCT-07:10 600.14 11-OCT-15:00 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 105.12 29-OCT-13:10 23.42 23-OCT-04:53
November 805.43 01-NOV-07:10 860.01 09-NOV-16:00 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 55.85 11-NOV-16:00 26.57 26-NOV-10:00
December 805.43 01-DEC-08:09 860.01 04-DEC-16:00 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 40.12 24-DEC-15:10 46.54 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   450.21   908.57   0.00 0.00 0.00 0.00 40.12   13.60  
Maximum of Months 805.43   860.01   908.57   0.00 0.00 0.00 0.00 162.85   126.71  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 947.97 02-JAN-16:00 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 62.26 15-JAN-13:05 196.35 07-JAN-05:00
February 1306.65 01-FEB-10:09 754.69 01-FEB-17:30 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 128.57 20-FEB-15:56 24.49 19-FEB-07:00
March 1306.65 01-MAR-10:09 774.31 01-MAR-16:49 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 236.25 19-MAR-16:00 37.84 03-MAR-05:30
April 1306.65 03-APR-09:09 774.31 21-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 121.88 30-APR-15:30 14.43 22-APR-03:00
May 1306.65 01-MAY-09:09 774.31 09-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 171.28 07-MAY-14:38 69.69 08-MAY-22:00
June 1306.65 01-JUN-09:09 774.31 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 161.97 18-JUN-14:08 76.33 20-JUN-23:00
July 1306.65 03-JUL-09:09 774.31 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 149.16 04-JUL-14:00 20.30 02-JUL-13:20
August 1306.65 01-AUG-09:09 774.31 02-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 175.16 06-AUG-13:00 76.37 20-AUG-11:00
September 1306.65 01-SEP-09:09 774.31 21-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 165.97 10-SEP-15:00 44.50 15-SEP-22:00
October 1306.65 02-OCT-09:09 774.31 23-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 143.93 29-OCT-13:05 35.90 22-OCT-18:00
November 1306.65 01-NOV-09:09 1184.79 07-NOV-16:00 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 67.06 11-NOV-15:40 39.84 26-NOV-10:00
December 1306.65 01-DEC-10:09 1184.79 11-DEC-16:00 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 52.86 31-DEC-12:56 71.47 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   754.69   1435.24   0.00 0.00 0.00 0.00 52.86   14.43  
Maximum of Months 1306.65   1184.79   1435.24   0.00 0.00 0.00 0.00 236.25   196.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 600.10 02-JAN-16:00 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 54.45 15-JAN-13:10 127.36 07-JAN-05:00
February 827.17 01-FEB-10:09 477.75 01-FEB-17:40 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 90.01 20-FEB-15:54 15.10 19-FEB-07:00
March 827.17 01-MAR-10:09 600.10 15-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 157.46 19-MAR-16:00 25.31 03-MAR-05:30
April 827.17 03-APR-09:09 600.10 21-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 75.24 02-APR-15:04 10.51 22-APR-03:00
May 827.17 01-MAY-09:09 600.10 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 115.58 21-MAY-12:00 47.43 08-MAY-22:00
June 827.17 01-JUN-09:09 600.10 20-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 107.53 18-JUN-14:06 53.09 20-JUN-23:00
July 827.17 03-JUL-09:09 600.10 07-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 100.88 04-JUL-13:58 16.31 02-JUL-14:00
August 827.17 01-AUG-09:09 600.10 02-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 119.38 06-AUG-13:00 51.15 20-AUG-11:00
September 827.17 01-SEP-09:09 600.10 19-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 105.38 10-SEP-14:55 29.15 15-SEP-22:00
October 827.17 02-OCT-09:09 600.10 10-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 100.84 29-OCT-13:10 24.05 22-OCT-18:00
November 827.17 01-NOV-09:09 710.03 09-NOV-16:00 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 48.41 05-NOV-11:00 24.93 25-NOV-05:00
December 827.17 01-DEC-10:09 750.02 18-DEC-16:40 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 43.04 31-DEC-12:50 46.83 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   477.75   908.57   0.00 0.00 0.00 0.00 43.04   10.51  
Maximum of Months 827.17   750.02   908.57   0.00 0.00 0.00 0.00 157.46   127.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.05 15-JAN-13:00 277.53 07-JAN-05:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171.05 19-FEB-14:53 30.52 20-FEB-07:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 306.59 19-MAR-16:00 49.59 03-MAR-05:40
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147.24 02-APR-15:31 18.96 22-APR-03:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.97 07-MAY-15:00 83.36 08-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.54 18-JUN-14:30 82.08 20-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 174.57 04-JUL-14:00 27.48 19-JUL-21:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 207.97 06-AUG-13:00 82.78 20-AUG-11:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.13 10-SEP-15:00 56.77 15-SEP-22:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 188.19 29-OCT-12:52 44.30 23-OCT-04:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91.12 11-NOV-16:00 51.08 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.29 24-DEC-14:52 98.59 21-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.29   18.96  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 306.59   277.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 120.77 15-JAN-12:52 333.42 07-JAN-05:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 226.01 19-FEB-14:53 34.01 20-FEB-06:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 397.69 19-MAR-16:00 60.21 03-MAR-05:40
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.36 23-APR-14:52 22.52 22-APR-03:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.22 07-MAY-15:00 106.25 08-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 257.26 18-JUN-14:30 102.11 20-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 227.56 04-JUL-14:10 33.85 19-JUL-21:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.41 06-AUG-13:00 97.35 20-AUG-11:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.65 10-SEP-15:00 67.33 15-SEP-22:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 249.36 29-OCT-12:52 57.40 23-OCT-04:53
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.91 11-NOV-16:00 63.28 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.39 24-DEC-14:52 122.04 21-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.39   22.52  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 397.69   333.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.17 15-JAN-12:52 265.85 07-JAN-05:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 181.28 19-FEB-15:00 31.99 20-FEB-06:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 328.88 19-MAR-16:00 54.33 03-MAR-06:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.02 09-APR-14:43 15.39 13-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 279.41 21-MAY-11:43 100.06 08-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.95 18-JUN-13:52 122.65 20-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171.95 04-JUL-13:50 87.74 02-JUL-13:50
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 290.98 06-AUG-12:55 121.61 20-AUG-11:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 190.33 10-SEP-15:00 77.31 03-SEP-16:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 183.96 29-OCT-12:52 63.98 29-OCT-17:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97.32 11-NOV-16:00 62.03 25-NOV-05:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.83 31-DEC-09:53 111.23 21-DEC-05:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.83   15.39  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 328.88   265.85  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 41050.26 03-JAN-05:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
February 41662.80 06-FEB-06:03 3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00
March 41130.02 08-MAR-05:03 0.00 846.94 22568.22 0.00 0.00 0.00 0.00 0.00 0.00
April 40821.54 22-APR-04:03 0.00 846.94 20126.17 0.00 0.00 0.00 0.00 0.00 0.00
May 40916.84 26-MAY-04:03 0.00 846.94 22568.22 0.00 0.00 0.00 0.00 0.00 0.00
June 40561.01 03-JUN-04:03 0.00 846.94 20126.17 0.00 0.00 0.00 0.00 0.00 0.00
July 40941.83 19-JUL-04:03 0.00 846.94 22568.22 0.00 0.00 0.00 0.00 0.00 0.00
August 41618.63 21-AUG-04:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 43730.63 19-SEP-05:03 3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00
October 41239.15 24-OCT-04:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
November 41020.41 07-NOV-05:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
December 40716.48 30-DEC-05:03 0.00 846.94 20126.17 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 40561.01   0.00 846.94 20126.17 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 43730.63   3811.58 1270.40 44462.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9835.57 04-JAN-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.14 0.00
February 10868.84 21-FEB-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.40 0.00
March 10925.29 21-MAR-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.46 0.00
April 10214.80 11-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.43 0.00
May 10960.84 05-MAY-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.02 0.00
June 10772.11 16-JUN-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.93 0.00
July 9423.60 14-JUL-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.83 0.00
August 9988.34 14-AUG-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.96 0.00
September 9956.36 06-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.56 0.00
October 9500.72 04-OCT-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.23 0.00
November 9425.11 22-NOV-13:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.79 0.00
December 9692.83 26-DEC-13:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.12 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 9423.60   0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.79 0.00
Maximum of Months 10960.84   0.00 0.00 0.00 0.00 0.00 0.00 0.00 75.02 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5007.80 02-JAN-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
February 5390.88 21-FEB-16:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.88 0.00
March 5182.40 20-MAR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.40 0.00
April 4798.87 17-APR-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.16 0.00
May 5328.93 30-MAY-12:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.28 0.00
June 5383.93 12-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.76 0.00
July 4579.55 17-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.89 0.00
August 4772.09 14-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.97 0.00
September 4904.89 05-SEP-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65 0.00
October 4873.05 10-OCT-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.73 0.00
November 4992.28 13-NOV-13:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.09 0.00
December 5054.16 26-DEC-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.21 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4579.55   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5390.88   0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.40 0.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5323.15 17-JAN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.09 0.00
February 5660.54 21-FEB-16:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.07 0.00
March 5459.20 20-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.18 0.00
April 5296.21 17-APR-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.76 0.00
May 5950.52 30-MAY-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50 0.00
June 5745.65 12-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.73 0.00
July 5217.63 17-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.59 0.00
August 5312.54 14-AUG-12:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.73 0.00
September 5466.94 05-SEP-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.96 0.00
October 5312.75 10-OCT-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.32 0.00
November 5335.39 13-NOV-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.79 0.00
December 5344.32 26-DEC-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.23 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5217.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50 0.00
Maximum of Months 5950.52   0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.18 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 32631.94 10-JAN-05:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
February 35286.36 06-FEB-06:03 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
March 32795.49 07-MAR-05:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
April 32033.02 05-APR-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
May 32429.39 09-MAY-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
June 32527.23 01-JUN-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
July 32816.87 18-JUL-04:22 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
August 32393.81 21-AUG-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 32466.21 13-SEP-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
October 32915.97 11-OCT-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
November 32911.04 07-NOV-05:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
December 31019.82 26-DEC-06:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 31019.82   0.00 1058.67 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35286.36   3811.58 2863.91 18155.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 34711.64 09-JAN-05:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
February 37677.41 06-FEB-06:03 3811.58 1270.40 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
March 34537.20 21-MAR-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
April 34826.82 10-APR-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
May 34960.32 09-MAY-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
June 34705.01 26-JUN-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
July 34618.72 06-JUL-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
August 35131.29 21-AUG-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 34423.70 14-SEP-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
October 35041.21 02-OCT-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
November 34782.04 13-NOV-05:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
December 33576.59 26-DEC-06:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 33576.59   0.00 1058.67 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37677.41   3811.58 2863.91 18155.52 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8526.42 02-JAN-06:12 535.68 603.74 2551.55 0.00 0.00 0.00 0.00 0.00 0.00
February 10197.40 05-FEB-14:32 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 78.64 0.00
March 12584.55 26-MAR-14:02 334.80 179.99 2392.08 0.00 0.00 0.00 0.00 130.15 0.00
April 12281.66 30-APR-12:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 54.36 0.00
May 12790.53 07-MAY-12:32 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 80.01 0.00
June 12975.46 18-JUN-12:02 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 132.00 0.00
July 12631.63 04-JUL-14:02 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 137.83 0.00
August 12502.13 13-AUG-12:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 82.74 0.00
September 12290.05 04-SEP-12:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 67.91 0.00
October 10712.64 16-OCT-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.39 0.00
November 11838.24 19-NOV-14:22 334.80 179.99 2392.08 0.00 0.00 0.00 0.00 59.50 0.00
December 6764.32 26-DEC-14:10 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 8.33 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6764.32   0.00 143.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12975.46   1306.65 647.98 2574.02 0.00 0.00 0.00 0.00 137.83 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10037.31 16-JAN-11:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 7.82 0.00
February 11530.39 20-FEB-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 9.08 0.00
March 12181.84 26-MAR-09:22 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 48.86 0.00
April 11508.01 09-APR-08:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 12.24 0.00
May 12005.09 29-MAY-09:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 9.19 0.00
June 11249.16 11-JUN-11:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 92.06 0.00
July 8753.10 04-JUL-14:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 99.62 0.00
August 11556.17 13-AUG-08:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 42.48 0.00
September 11564.05 10-SEP-09:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 21.65 0.00
October 11512.15 08-OCT-09:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 18.41 0.00
November 9561.91 05-NOV-11:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 39.13 0.00
December 8280.70 03-DEC-11:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 22.40 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8280.70   169.56 91.16 1211.43 0.00 0.00 0.00 0.00 7.82 0.00
Maximum of Months 12181.84   211.95 113.95 1514.29 0.00 0.00 0.00 0.00 99.62 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12961.67 29-JAN-12:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 21.55 0.00
February 12793.14 26-FEB-12:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 37.01 0.00
March 12745.10 26-MAR-14:02 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 120.53 0.00
April 11949.01 02-APR-15:42 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 132.37 0.00
May 12124.29 07-MAY-12:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 84.00 0.00
June 12037.50 18-JUN-12:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 147.97 0.00
July 11948.56 04-JUL-14:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 149.28 0.00
August 11724.61 13-AUG-12:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 85.74 0.00
September 12151.77 04-SEP-12:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 65.39 0.00
October 12774.89 29-OCT-11:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 111.40 0.00
November 13279.38 19-NOV-12:22 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 34.04 0.00
December 12972.70 03-DEC-11:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 26.88 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11724.61   267.84 143.99 1913.65 0.00 0.00 0.00 0.00 21.55 0.00
Maximum of Months 13279.38   401.76 215.99 2870.47 0.00 0.00 0.00 0.00 149.28 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13541.86 29-JAN-16:42 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 29.12 0.00
February 13064.43 26-FEB-15:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 91.04 0.00
March 13521.66 05-MAR-16:42 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 11.06 0.00
April 13430.47 02-APR-15:42 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 78.51 0.00
May 13023.32 14-MAY-15:42 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 40.77 0.00
June 13068.96 11-JUN-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 67.52 0.00
July 13098.07 04-JUL-16:02 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 68.66 0.00
August 13074.65 27-AUG-16:12 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 64.99 0.00
September 13148.33 04-SEP-16:12 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 58.92 0.00
October 12005.19 15-OCT-17:03 0.00 91.15 977.67 0.00 0.00 0.00 0.00 11.74 0.00
November 13398.21 19-NOV-14:22 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 33.45 0.00
December 12170.98 03-DEC-16:33 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 15.47 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12005.19   0.00 91.15 977.67 0.00 0.00 0.00 0.00 11.06 0.00
Maximum of Months 13541.86   254.33 136.73 1817.13 0.00 0.00 0.00 0.00 91.04 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7578.79 02-JAN-07:03 803.52 947.98 1913.66 0.00 0.00 0.00 0.00 0.00 0.02
February 8329.81 06-FEB-06:02 803.52 267.81 3827.32 0.00 0.00 0.00 0.00 0.00 0.00
March 8675.42 28-MAR-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 6.76 0.00
April 10591.82 30-APR-16:02 401.76 215.99 2870.49 0.00 0.00 0.00 0.00 65.82 0.00
May 10982.75 29-MAY-11:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 16.49 0.00
June 11102.04 18-JUN-12:02 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 74.37 0.00
July 10976.02 04-JUL-17:02 0.00 179.99 1930.52 0.00 0.00 0.00 0.00 26.79 0.00
August 9172.03 13-AUG-12:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 46.10 0.00
September 8990.06 08-SEP-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 4.26 0.00
October 8844.81 16-OCT-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.34 0.00
November 7768.53 13-NOV-07:03 803.52 711.16 1913.66 0.00 0.00 0.00 0.00 2.10 0.00
December 6728.74 04-DEC-07:03 1071.35 948.21 2551.55 0.00 0.00 0.00 0.00 0.00 0.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6728.74   0.00 143.99 1913.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11102.04   1071.35 948.21 3827.32 0.00 0.00 0.00 0.00 74.37 0.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9225.93 16-JAN-10:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 3.94 0.00
February 10470.07 20-FEB-10:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 12.35 0.00
March 10834.36 26-MAR-09:22 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 28.33 0.00
April 10712.94 30-APR-10:42 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 14.48 0.00
May 10687.08 14-MAY-10:12 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 24.81 0.00
June 9643.85 11-JUN-11:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 50.63 0.00
July 8600.46 30-JUL-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 12.10 0.00
August 10695.52 27-AUG-10:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 18.31 0.00
September 10410.66 04-SEP-08:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 8.85 0.00
October 8782.66 09-OCT-08:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 3.53 0.00
November 8163.63 23-NOV-09:32 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 9.63 0.00
December 8180.45 31-DEC-09:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 5.71 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8163.63   169.56 91.16 1211.43 0.00 0.00 0.00 0.00 3.53 0.00
Maximum of Months 10834.36   211.95 113.95 1514.29 0.00 0.00 0.00 0.00 50.63 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11413.67 16-JAN-11:32 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 5.38 0.00
February 11275.35 21-FEB-13:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 7834.66 0.00
March 11162.70 21-MAR-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 9067.12 0.00
April 10665.55 18-APR-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 8805.88 0.00
May 11578.89 05-MAY-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 10821.29 0.00
June 11042.73 16-JUN-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 9410.44 0.00
July 10166.60 26-JUL-17:00 401.76 395.08 797.35 0.00 0.00 0.00 0.00 8391.94 0.00
August 10673.61 15-AUG-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 8469.80 0.00
September 10508.88 05-SEP-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 7898.04 0.00
October 10947.98 29-OCT-11:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 62.59 0.00
November 11006.86 23-NOV-11:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 21.90 0.00
December 11406.76 03-DEC-12:22 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 10.76 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10166.60   267.84 143.99 797.35 0.00 0.00 0.00 0.00 5.38 0.00
Maximum of Months 11578.89   687.71 647.98 2392.06 0.00 0.00 0.00 0.00 10821.29 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11528.78 16-JAN-17:32 211.94 238.87 1514.28 0.00 0.00 0.00 0.00 3.89 0.00
February 10790.28 26-FEB-15:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 50.03 0.00
March 11440.42 05-MAR-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 10.81 0.00
April 11632.37 30-APR-16:02 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 35.04 0.00
May 11226.06 14-MAY-16:11 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 22.07 0.00
June 11080.61 11-JUN-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 37.01 0.00
July 11636.95 04-JUL-17:02 0.00 113.94 1222.09 0.00 0.00 0.00 0.00 12.79 0.00
August 11336.80 27-AUG-16:01 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 37.31 0.00
September 11633.11 10-SEP-15:12 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 28.52 0.00
October 10154.84 15-OCT-17:03 0.00 91.15 977.67 0.00 0.00 0.00 0.00 6.69 0.00
November 10350.18 19-NOV-14:52 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 16.66 0.00
December 11296.26 31-DEC-15:22 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 16.01 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10154.84   0.00 91.15 977.67 0.00 0.00 0.00 0.00 3.89 0.00
Maximum of Months 11636.95   296.72 238.87 2119.99 0.00 0.00 0.00 0.00 50.03 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8670.61 02-JAN-06:12 535.68 603.74 2551.55 0.00 0.00 0.00 0.00 0.00 0.00
February 9061.14 27-FEB-05:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 5.03
March 10523.54 26-MAR-14:02 334.80 179.99 2392.08 0.00 0.00 0.00 0.00 115.29 0.00
April 10729.66 30-APR-16:02 401.76 215.99 2870.49 0.00 0.00 0.00 0.00 98.31 0.00
May 10990.27 07-MAY-10:32 334.80 179.99 2392.08 0.00 0.00 0.00 0.00 33.36 0.00
June 11210.71 18-JUN-12:02 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 114.31 0.00
July 11241.94 04-JUL-16:32 401.76 215.99 2870.49 0.00 0.00 0.00 0.00 57.61 0.00
August 9911.12 13-AUG-12:53 267.84 143.99 1913.66 0.00 0.00 0.00 0.00 71.85 0.00
September 9626.86 10-SEP-15:12 401.76 215.99 2870.49 0.00 0.00 0.00 0.00 92.00 0.00
October 9058.81 02-OCT-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 0.96
November 9149.42 13-NOV-05:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 4.08
December 7790.55 26-DEC-07:03 1071.35 1263.98 2551.55 0.00 0.00 0.00 0.00 0.00 1.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7790.55   0.00 143.99 1913.66 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11241.94   1071.35 1263.98 2870.49 0.00 0.00 0.00 0.00 115.29 5.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10223.49 16-JAN-10:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 5.51 0.00
February 11088.04 20-FEB-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 7.54 0.00
March 11648.35 26-MAR-09:22 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 41.92 0.00
April 11432.82 30-APR-08:42 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 15.57 0.00
May 11462.66 29-MAY-09:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 7.95 0.00
June 10005.95 11-JUN-11:53 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 78.88 0.00
July 9269.34 30-JUL-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 18.58 0.00
August 11401.84 27-AUG-10:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 27.91 0.00
September 11033.28 10-SEP-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 15.31 0.00
October 11037.42 08-OCT-09:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 10.77 0.00
November 9071.81 23-NOV-09:32 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 14.72 0.00
December 9566.14 31-DEC-09:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 8.74 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9071.81   169.56 91.16 1211.43 0.00 0.00 0.00 0.00 5.51 0.00
Maximum of Months 11648.35   211.95 113.95 1514.29 0.00 0.00 0.00 0.00 78.88 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11743.25 16-JAN-12:02 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 10.24 0.00
February 11112.33 26-FEB-12:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 31.44 0.00
March 10890.79 19-MAR-12:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 161.35 0.00
April 10311.03 30-APR-16:02 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 101.54 0.00
May 9221.25 01-MAY-04:02 0.00 223.18 2574.00 0.00 0.00 0.00 0.00 17.59 0.00
June 8884.55 26-JUN-04:02 0.00 223.18 2574.00 0.00 0.00 0.00 0.00 0.00 1.94
July 8913.08 04-JUL-14:32 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 121.10 0.00
August 8762.95 15-AUG-04:02 0.00 223.18 2574.00 0.00 0.00 0.00 0.00 3.49 0.00
September 10423.52 10-SEP-15:12 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 87.61 0.00
October 11109.44 29-OCT-11:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 95.27 0.00
November 11321.33 19-NOV-11:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 31.72 0.00
December 11642.75 25-DEC-12:42 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 12.88 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8762.95   0.00 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11743.25   401.76 223.18 2870.47 0.00 0.00 0.00 0.00 161.35 1.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12528.85 16-JAN-16:42 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 16.73 0.00
February 11873.17 26-FEB-15:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 77.04 0.00
March 12295.20 05-MAR-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 15.34 0.00
April 12467.33 30-APR-16:02 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 52.26 0.00
May 12039.36 14-MAY-16:11 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 33.75 0.00
June 11829.52 11-JUN-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 57.30 0.00
July 12726.13 04-JUL-16:32 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 28.71 0.00
August 12160.50 27-AUG-16:01 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 57.24 0.00
September 12478.39 10-SEP-15:12 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 41.56 0.00
October 10618.31 15-OCT-17:03 0.00 91.15 977.67 0.00 0.00 0.00 0.00 10.22 0.00
November 11299.44 19-NOV-16:33 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 18.97 0.00
December 12268.48 25-DEC-16:42 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 8.62 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10618.31   0.00 91.15 977.67 0.00 0.00 0.00 0.00 8.62 0.00
Maximum of Months 12726.13   296.72 159.52 2119.99 0.00 0.00 0.00 0.00 77.04 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.170914E+12 151339.58 30-JAN-15:09 0.00 0.00
February 0.159302E+12 160742.51 13-FEB-15:09 0.00 0.00
March 0.188379E+12 163060.61 20-MAR-15:09 0.00 0.00
April 0.182745E+12 162953.38 11-APR-15:00 0.00 0.00
May 0.199037E+12 169445.28 05-MAY-14:20 0.00 0.00
June 0.198836E+12 177422.83 13-JUN-15:20 0.00 0.00
July 0.173003E+12 153047.11 17-JUL-14:09 0.00 0.00
August 0.191267E+12 162488.67 14-AUG-14:30 0.00 0.00
September 0.176224E+12 159492.27 06-SEP-14:30 0.00 0.00
October 0.176189E+12 157858.26 16-OCT-14:09 0.00 0.00
November 0.170695E+12 153269.55 13-NOV-13:50 0.00 0.00
December 0.166207E+12 148420.68 26-DEC-15:09 0.00 0.00
           
Annual Sum or Average 0.215280E+13     0.00 0.00
Minimum of Months 0.159302E+12 148420.68   0.00 0.00
Maximum of Months 0.199037E+12 177422.83   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.251855E+11 0.456186E+10 0.605851E+11 0.225867E+10 0.101402E+11 12379742.02 0.00 0.650782E+11 0.00 0.00 0.00 0.309169E+10 0.00
February 0.227813E+11 0.400802E+10 0.548702E+11 0.204949E+10 0.972122E+10 11196021.66 0.00 0.630679E+11 0.00 0.00 0.00 0.279275E+10 0.00
March 0.269479E+11 0.419680E+10 0.627783E+11 0.235655E+10 0.112539E+11 12675672.10 0.00 0.775889E+11 0.00 0.00 0.00 0.324426E+10 0.00
April 0.239031E+11 0.388710E+10 0.586172E+11 0.219339E+10 0.104393E+11 11960507.72 0.00 0.808147E+11 0.00 0.00 0.00 0.287831E+10 0.00
May 0.258590E+11 0.388975E+10 0.616817E+11 0.230752E+10 0.111629E+11 12527707.06 0.00 0.911046E+11 0.00 0.00 0.00 0.301874E+10 0.00
June 0.256834E+11 0.371634E+10 0.604966E+11 0.226972E+10 0.118107E+11 12231776.97 0.00 0.918931E+11 0.00 0.00 0.00 0.295374E+10 0.00
July 0.240310E+11 0.390630E+10 0.597911E+11 0.223048E+10 0.962669E+10 12256437.81 0.00 0.706150E+11 0.00 0.00 0.00 0.278970E+10 0.00
August 0.268429E+11 0.397154E+10 0.627783E+11 0.235646E+10 0.101237E+11 12675672.10 0.00 0.821012E+11 0.00 0.00 0.00 0.308040E+10 0.00
September 0.240268E+11 0.400992E+10 0.585950E+11 0.219223E+10 0.931524E+10 11960507.72 0.00 0.752411E+11 0.00 0.00 0.00 0.283145E+10 0.00
October 0.250130E+11 0.434010E+10 0.605962E+11 0.225933E+10 0.915772E+10 12379742.02 0.00 0.718274E+11 0.00 0.00 0.00 0.298242E+10 0.00
November 0.249811E+11 0.440359E+10 0.591197E+11 0.220132E+10 0.945792E+10 12059151.09 0.00 0.675341E+11 0.00 0.00 0.00 0.298543E+10 0.00
December 0.244435E+11 0.461491E+10 0.597800E+11 0.222995E+10 0.928972E+10 12256437.81 0.00 0.628345E+11 0.00 0.00 0.00 0.300262E+10 0.00
                           
Annual Sum or Average 0.299699E+12 0.495062E+11 0.719689E+12 0.269051E+11 0.121499E+12 0.146559E+09 0.00 0.899701E+12 0.00 0.00 0.00 0.356515E+11 0.00
Minimum of Months 0.227813E+11 0.371634E+10 0.548702E+11 0.204949E+10 0.915772E+10 11196021.66 0.00 0.628345E+11 0.00 0.00 0.00 0.278970E+10 0.00
Maximum of Months 0.269479E+11 0.461491E+10 0.627783E+11 0.235655E+10 0.118107E+11 12675672.10 0.00 0.918931E+11 0.00 0.00 0.00 0.324426E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 29780.74 02-JAN-16:00 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 02-JAN-17:10 14170.92 17-JAN-15:09 6.85 01-JAN-06:10 0.00 01-JAN-00:10
February 27340.31 07-FEB-16:00 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 15-FEB-13:09 15974.88 21-FEB-15:09 6.85 01-FEB-06:10 0.00 01-FEB-00:10
March 27649.77 01-MAR-16:00 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 08-MAR-12:09 15370.37 20-MAR-14:00 6.85 19-MAR-15:30 0.00 01-MAR-00:10
April 26646.21 21-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 04-APR-12:09 14137.88 17-APR-15:20 6.85 02-APR-15:39 0.00 01-APR-00:10
May 27025.62 17-MAY-07:10 5686.19 01-MAY-05:10 41699.26 01-MAY-07:10 1410.29 03-MAY-12:09 15245.75 05-MAY-15:20 6.85 01-MAY-05:10 0.00 01-MAY-00:10
June 26709.37 20-JUN-07:10 5686.19 01-JUN-05:10 41699.26 01-JUN-07:10 1410.29 06-JUN-12:09 16327.79 12-JUN-15:20 6.85 01-JUN-05:10 0.00 01-JUN-00:10
July 26819.30 11-JUL-07:10 5686.19 01-JUL-05:10 41699.26 03-JUL-07:10 1410.29 03-JUL-11:09 13320.07 24-JUL-14:09 6.85 01-JUL-05:10 0.00 01-JUL-00:10
August 26819.30 02-AUG-07:10 5686.19 01-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-12:09 13911.63 14-AUG-14:30 6.85 01-AUG-05:10 0.00 01-AUG-00:10
September 26646.21 21-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 12-SEP-12:09 13677.33 05-SEP-14:09 6.85 01-SEP-05:10 0.00 01-SEP-00:10
October 27476.12 30-OCT-15:00 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 02-OCT-16:10 13883.63 10-OCT-14:09 6.85 01-OCT-05:10 0.00 01-OCT-00:10
November 31040.88 09-NOV-16:00 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 01-NOV-11:09 13708.37 20-NOV-15:09 6.85 01-NOV-05:10 0.00 01-NOV-00:10
December 31270.78 18-DEC-16:00 5686.19 01-DEC-17:30 41699.26 01-DEC-08:09 1410.29 01-DEC-12:09 14425.01 26-DEC-15:09 6.85 01-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 26646.21   5686.19   41699.26   1410.29   13320.07   6.85   0.00  
Maximum of Months 31270.78   5686.19   41699.26   1410.29   16327.79   6.85   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 66528.51 04-JAN-15:09 0.00 0.00 0.00 4202.75 06-JAN-12:30 0.00
February 75336.41 13-FEB-15:09 0.00 0.00 0.00 4201.41 01-FEB-12:00 0.00
March 76071.20 20-MAR-14:00 0.00 0.00 0.00 3942.69 08-MAR-12:39 0.00
April 77324.27 11-APR-15:00 0.00 0.00 0.00 3882.74 03-APR-11:39 0.00
May 86405.71 04-MAY-12:00 0.00 0.00 0.00 3871.22 01-MAY-11:30 0.00
June 90068.80 13-JUN-14:00 0.00 0.00 0.00 3860.54 01-JUN-11:50 0.00
July 69584.62 21-JUL-14:00 0.00 0.00 0.00 3855.03 28-JUL-11:50 0.00
August 78270.29 22-AUG-14:00 0.00 0.00 0.00 3862.06 31-AUG-11:30 0.00
September 75117.80 06-SEP-14:20 0.00 0.00 0.00 3872.52 29-SEP-11:20 0.00
October 73418.86 16-OCT-14:09 0.00 0.00 0.00 3885.67 31-OCT-11:00 0.00
November 70259.90 13-NOV-13:00 0.00 0.00 0.00 4090.87 30-NOV-12:30 0.00
December 66350.09 12-DEC-13:00 0.00 0.00 0.00 4201.73 26-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 66350.09   0.00 0.00 0.00 3855.03   0.00
Maximum of Months 90068.80   0.00 0.00 0.00 4202.75   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 151339.58 30-JAN-15:09 25681.07 41659.26 0.00 1410.29 14081.04 6.85 0.00 65980.99 0.00
February 160742.51 13-FEB-15:09 25681.07 41659.26 0.00 1410.29 14392.88 6.85 0.00 75336.41 0.00
March 163060.61 20-MAR-15:09 25681.07 41670.51 0.00 1410.29 15320.93 6.85 0.00 75797.61 0.00
April 162953.38 11-APR-15:00 25681.07 41670.51 0.00 1410.29 13683.65 6.85 0.00 77324.27 0.00
May 169445.28 05-MAY-14:20 25681.07 41659.26 0.00 1410.29 14893.18 6.85 0.00 83548.80 0.00
June 177422.83 13-JUN-15:20 25681.07 41670.51 0.00 1410.29 15860.98 6.85 0.00 89917.37 0.00
July 153047.11 17-JUL-14:09 25681.07 41659.26 0.00 1410.29 13032.49 6.85 0.00 69015.63 0.00
August 162488.67 14-AUG-14:30 25681.07 41659.26 0.00 1410.29 13911.63 6.85 0.00 77577.52 0.00
September 159492.27 06-SEP-14:30 25681.07 41659.26 0.00 1410.29 13373.97 6.85 0.00 75116.78 0.00
October 157858.26 16-OCT-14:09 25681.07 41659.26 0.00 1410.29 13432.43 6.85 0.00 73418.86 0.00
November 153269.55 13-NOV-13:50 25681.07 38932.26 0.00 1410.29 13282.16 6.85 0.00 70181.89 0.00
December 148420.68 26-DEC-15:09 25681.07 41659.26 0.00 1410.29 14425.01 6.85 0.00 62981.68 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 148420.68   25681.07 38932.26 0.00 1410.29 13032.49 6.85 0.00 62981.68 0.00
Maximum of Months 177422.83   25681.07 41670.51 0.00 1410.29 15860.98 6.85 0.00 89917.37 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 27.15 0.17 27.17
February 0.00 0.00 0.00 0.00 0.17 26.17 0.00 26.17
March 0.00 0.00 0.00 0.00 0.17 26.22 0.00 26.22
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 26.17 0.00 26.17
August 0.00 0.00 0.00 0.00 0.17 26.23 0.00 26.23
September 0.00 0.00 0.00 0.00 0.17 26.17 0.00 26.17
October 0.00 0.00 0.00 0.00 0.17 26.19 0.00 26.19
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.33 26.74 0.17 26.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 27.15 0.17 27.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 2.00 27.43 2.00 27.43
March 0.00 0.00 0.00 0.00 3.50 27.49 3.33 27.49
April 0.00 0.00 0.00 0.00 4.17 27.52 4.00 27.52
May 0.00 0.00 0.00 0.00 7.67 27.76 6.50 27.77
June 0.00 0.00 0.00 0.00 8.50 27.80 7.17 27.82
July 0.00 0.00 0.00 0.00 7.33 27.48 6.83 27.48
August 0.00 0.00 0.00 0.00 2.83 27.59 2.67 27.60
September 0.00 0.00 0.00 0.00 2.50 27.44 2.50 27.44
October 0.00 0.00 0.00 0.00 1.33 27.32 1.33 27.32
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   39.83 27.60 36.33 27.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.50 27.80 7.17 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.33 27.45 2.33 27.45
February 0.00 0.00 0.00 0.00 7.50 27.59 7.50 27.59
March 0.00 0.00 0.00 0.00 8.83 27.83 8.50 27.84
April 0.00 0.00 0.00 0.00 10.67 27.83 10.67 27.83
May 0.00 0.00 0.00 0.00 9.67 27.92 9.17 27.93
June 0.00 0.00 0.00 0.00 8.33 27.79 7.83 27.80
July 0.00 0.00 0.00 0.00 6.33 27.44 6.33 27.44
August 0.00 0.00 0.00 0.00 5.17 27.78 5.17 27.78
September 0.00 0.00 0.00 0.00 7.83 27.73 7.83 27.73
October 0.00 0.00 0.00 0.00 5.83 27.62 5.83 27.62
November 0.00 0.00 0.00 0.00 3.83 27.46 3.83 27.46
December 0.00 0.00 0.00 0.00 3.00 27.43 3.00 27.43
                 
Annual Sum or Average 0.00   0.00   79.33 27.71 78.00 27.71
Minimum of Months 0.00 0.00 0.00 0.00 2.33 27.43 2.33 27.43
Maximum of Months 0.00 0.00 0.00 0.00 10.67 27.92 10.67 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 10.00 27.86 9.83 27.86
February 0.00 0.00 0.00 0.00 8.50 27.86 8.33 27.87
March 0.00 0.00 0.00 0.00 6.50 27.74 6.00 27.75
April 0.00 0.00 0.00 0.00 3.67 27.50 3.67 27.50
May 0.00 0.00 0.00 0.00 4.83 27.58 4.33 27.60
June 0.00 0.00 0.00 0.00 4.17 27.54 3.67 27.55
July 0.00 0.00 0.00 0.00 2.00 27.35 2.00 27.35
August 0.00 0.00 0.00 0.00 1.83 27.48 1.83 27.48
September 0.00 0.00 0.00 0.00 4.33 27.49 4.33 27.49
October 0.00 0.00 0.00 0.00 7.17 27.66 7.17 27.66
November 0.00 0.00 0.00 0.00 8.00 27.81 7.83 27.82
December 0.00 0.00 0.00 0.00 13.17 27.11 13.17 27.11
                 
Annual Sum or Average 0.00   0.00   74.17 27.59 72.17 27.59
Minimum of Months 0.00 0.00 0.00 0.00 1.83 27.11 1.83 27.11
Maximum of Months 0.00 0.00 0.00 0.00 13.17 27.86 13.17 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.33 28.01 5.33 28.01
February 0.00 0.00 0.00 0.00 5.00 27.98 4.83 27.99
March 0.00 0.00 0.00 0.00 5.83 28.23 4.67 28.26
April 0.00 0.00 0.00 0.00 6.33 28.15 4.83 28.21
May 0.00 0.00 0.00 0.00 5.83 28.16 4.17 28.22
June 0.00 0.00 0.00 0.00 6.33 28.11 4.50 28.14
July 0.00 0.00 0.00 0.00 4.17 27.76 3.33 27.76
August 0.00 0.00 0.00 0.00 3.83 28.00 3.00 28.03
September 0.00 0.00 0.00 0.00 4.17 28.08 3.33 28.09
October 0.00 0.00 0.00 0.00 4.17 27.76 3.83 27.77
November 0.00 0.00 0.00 0.00 3.33 27.77 3.33 27.77
December 0.00 0.00 0.00 0.00 5.00 27.97 5.00 27.97
                 
Annual Sum or Average 0.00   0.00   59.33 28.02 50.17 28.04
Minimum of Months 0.00 0.00 0.00 0.00 3.33 27.76 3.00 27.76
Maximum of Months 0.00 0.00 0.00 0.00 6.33 28.23 5.33 28.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 5.00 27.49 4.33 27.52
June 0.00 0.00 0.00 0.00 6.83 27.54 5.83 27.56
July 0.00 0.00 0.00 0.00 1.33 27.41 1.33 27.41
August 0.00 0.00 0.00 0.00 0.50 27.34 0.50 27.34
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   13.67 27.50 12.00 27.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.83 27.54 5.83 27.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.67 27.47 0.67 27.47
February 0.00 0.00 0.00 0.00 3.17 27.51 3.17 27.51
March 0.00 0.00 0.00 0.00 6.50 27.62 6.50 27.62
April 0.00 0.00 0.00 0.00 8.17 27.61 8.17 27.61
May 0.00 0.00 0.00 0.00 9.00 27.66 8.67 27.67
June 0.00 0.00 0.00 0.00 6.17 27.61 6.00 27.61
July 0.00 0.00 0.00 0.00 2.17 27.42 2.17 27.42
August 0.00 0.00 0.00 0.00 4.50 27.55 4.50 27.55
September 0.00 0.00 0.00 0.00 6.50 27.55 6.50 27.55
October 0.00 0.00 0.00 0.00 4.33 27.45 4.33 27.45
November 0.00 0.00 0.00 0.00 1.50 27.36 1.50 27.36
December 0.00 0.00 0.00 0.00 1.83 27.35 1.83 27.35
                 
Annual Sum or Average 0.00   0.00   54.50 27.56 54.00 27.57
Minimum of Months 0.00 0.00 0.00 0.00 0.67 27.35 0.67 27.35
Maximum of Months 0.00 0.00 0.00 0.00 9.00 27.66 8.67 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 108.50 25.40 108.17 25.40
February 0.00 0.00 0.00 0.00 100.33 25.47 100.33 25.47
March 0.00 0.00 0.00 0.00 61.50 25.59 61.50 25.59
April 0.00 0.00 0.00 0.00 38.83 25.63 38.83 25.63
May 0.00 0.00 0.00 0.00 42.83 25.61 42.83 25.61
June 0.00 0.00 0.00 0.00 41.17 25.74 41.17 25.74
July 0.00 0.00 0.00 0.00 29.00 25.20 29.00 25.20
August 0.00 0.00 0.00 0.00 30.00 25.46 30.00 25.46
September 0.00 0.00 0.00 0.00 29.17 25.42 29.17 25.42
October 0.00 0.00 0.00 0.00 35.17 25.44 35.17 25.44
November 0.00 0.00 0.00 0.00 61.83 25.46 61.83 25.46
December 0.00 0.00 0.00 0.00 88.17 25.51 87.67 25.50
                 
Annual Sum or Average 0.00   0.00   666.50 25.49 665.67 25.49
Minimum of Months 0.00 0.00 0.00 0.00 29.00 25.20 29.00 25.20
Maximum of Months 0.00 0.00 0.00 0.00 108.50 25.74 108.17 25.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.83 27.74 4.67 27.74
February 0.00 0.00 0.00 0.00 3.67 27.79 3.33 27.81
March 0.00 0.00 0.00 0.00 5.17 27.90 4.17 27.92
April 0.00 0.00 0.00 0.00 5.17 27.90 4.17 27.92
May 0.00 0.00 0.00 0.00 5.33 27.82 3.83 27.86
June 0.00 0.00 0.00 0.00 5.83 27.81 3.83 27.85
July 0.00 0.00 0.00 0.00 3.33 27.60 2.17 27.63
August 0.00 0.00 0.00 0.00 3.33 27.79 2.50 27.81
September 0.00 0.00 0.00 0.00 3.33 27.92 2.50 27.94
October 0.00 0.00 0.00 0.00 3.00 27.55 3.00 27.55
November 0.00 0.00 0.00 0.00 1.83 27.61 1.83 27.61
December 0.00 0.00 0.00 0.00 4.50 27.68 4.50 27.68
                 
Annual Sum or Average 0.00   0.00   49.33 27.78 40.50 27.79
Minimum of Months 0.00 0.00 0.00 0.00 1.83 27.55 1.83 27.55
Maximum of Months 0.00 0.00 0.00 0.00 5.83 27.92 4.67 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
May 0.00 0.00 0.00 0.00 5.67 27.58 5.00 27.59
June 0.00 0.00 0.00 0.00 7.00 27.63 6.17 27.63
July 0.00 0.00 0.00 0.00 2.17 27.41 2.00 27.41
August 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.83 27.56 14.17 27.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.00 27.63 6.17 27.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.83 27.56 0.83 27.56
February 0.00 0.00 0.00 0.00 3.33 27.54 3.33 27.54
March 0.00 0.00 0.00 0.00 6.50 27.72 6.50 27.72
April 0.00 0.00 0.00 0.00 8.17 27.69 8.17 27.69
May 0.00 0.00 0.00 0.00 8.67 27.74 8.67 27.74
June 0.00 0.00 0.00 0.00 5.83 27.68 5.83 27.68
July 0.00 0.00 0.00 0.00 1.50 27.48 1.50 27.48
August 0.00 0.00 0.00 0.00 4.17 27.62 4.17 27.62
September 0.00 0.00 0.00 0.00 5.50 27.59 5.50 27.59
October 0.00 0.00 0.00 0.00 3.83 27.51 3.83 27.51
November 0.00 0.00 0.00 0.00 1.67 27.46 1.67 27.46
December 0.00 0.00 0.00 0.00 1.83 27.44 1.83 27.44
                 
Annual Sum or Average 0.00   0.00   51.83 27.64 51.83 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.83 27.44 0.83 27.44
Maximum of Months 0.00 0.00 0.00 0.00 8.67 27.74 8.67 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 20.33 26.08 20.33 26.08
February 0.00 0.00 0.00 0.00 10.00 27.08 10.00 27.08
March 0.00 0.00 0.00 0.00 5.17 27.52 5.17 27.52
April 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
May 0.00 0.00 0.00 0.00 1.83 27.40 1.83 27.40
June 0.00 0.00 0.00 0.00 1.33 27.32 1.33 27.32
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.50 27.33 0.50 27.33
October 0.00 0.00 0.00 0.00 5.00 27.53 5.00 27.53
November 0.00 0.00 0.00 0.00 6.83 27.68 6.83 27.68
December 0.00 0.00 0.00 0.00 24.67 25.91 24.67 25.91
                 
Annual Sum or Average 0.00   0.00   75.83 26.56 75.83 26.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 24.67 27.68 24.67 27.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.83 27.86 4.83 27.86
February 0.00 0.00 0.00 0.00 3.67 27.90 3.50 27.91
March 0.00 0.00 0.00 0.00 5.17 28.03 4.17 28.06
April 0.00 0.00 0.00 0.00 5.33 27.99 4.33 28.02
May 0.00 0.00 0.00 0.00 4.83 28.01 3.83 28.04
June 0.00 0.00 0.00 0.00 5.33 27.94 4.00 27.96
July 0.00 0.00 0.00 0.00 2.17 27.84 1.67 27.83
August 0.00 0.00 0.00 0.00 3.00 27.90 2.33 27.93
September 0.00 0.00 0.00 0.00 3.33 28.00 2.50 28.02
October 0.00 0.00 0.00 0.00 2.67 27.66 2.50 27.67
November 0.00 0.00 0.00 0.00 1.83 27.74 1.83 27.74
December 0.00 0.00 0.00 0.00 4.50 27.81 4.50 27.81
                 
Annual Sum or Average 0.00   0.00   46.67 27.91 40.00 27.92
Minimum of Months 0.00 0.00 0.00 0.00 1.83 27.66 1.67 27.67
Maximum of Months 0.00 0.00 0.00 0.00 5.33 28.03 4.83 28.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 24.47 0.00 24.47
February 0.00 0.00 454.00 24.43 0.00 24.43
March 0.00 0.00 514.00 24.37 0.00 24.37
April 0.00 0.00 485.00 24.40 0.00 24.40
May 0.00 0.00 508.00 24.41 0.00 24.41
June 0.00 0.00 496.00 24.39 0.00 24.39
July 0.00 0.00 497.00 24.45 0.00 24.45
August 0.00 0.00 514.00 24.40 0.00 24.40
September 0.00 0.00 485.00 24.41 0.00 24.41
October 0.00 0.00 502.00 24.46 0.00 24.46
November 0.00 0.00 489.00 24.47 0.00 24.47
December 0.00 0.00 497.00 24.45 0.00 24.45
             
Annual Sum or Average 0.00   5943.00 24.43 0.00 24.43
Minimum of Months 0.00 0.00 454.00 24.37 0.00 24.37
Maximum of Months 0.00 0.00 514.00 24.47 0.00 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 461.00 24.31 0.00 24.31
February 0.00 0.00 422.33 24.27 0.00 24.27
March 0.00 0.00 476.00 24.23 0.00 24.23
April 0.00 0.00 450.83 24.25 0.00 24.25
May 0.00 0.00 479.33 24.27 0.00 24.27
June 0.00 0.00 473.17 24.26 0.00 24.26
July 0.00 0.00 451.83 24.29 0.00 24.29
August 0.67 23.23 459.50 24.26 0.00 24.26
September 1.00 23.20 430.50 24.26 0.00 24.26
October 0.00 0.00 445.17 24.31 0.00 24.31
November 0.00 0.00 447.83 24.30 0.00 24.30
December 0.17 23.27 429.50 24.29 0.00 24.29
             
Annual Sum or Average 1.83 23.22 5427.00 24.27 0.00 24.27
Minimum of Months 0.00 0.00 422.33 24.23 0.00 24.23
Maximum of Months 1.00 23.27 479.33 24.31 0.00 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 23.38 419.33 24.31 0.00 24.31
February 0.00 0.00 391.17 24.28 0.00 24.28
March 1.33 23.35 465.00 24.25 0.00 24.25
April 0.00 0.00 464.33 24.27 0.00 24.27
May 0.00 0.00 480.00 24.29 0.00 24.29
June 0.00 0.00 475.33 24.28 0.00 24.28
July 0.00 0.00 443.17 24.31 0.00 24.31
August 1.67 23.14 444.00 24.27 0.00 24.27
September 2.50 23.16 430.33 24.26 0.00 24.26
October 0.83 23.27 423.33 24.33 0.00 24.33
November 0.33 23.30 412.17 24.31 0.00 24.31
December 9.00 23.30 384.83 24.27 0.00 24.27
             
Annual Sum or Average 19.33 23.28 5233.00 24.29 0.00 24.29
Minimum of Months 0.00 0.00 384.83 24.25 0.00 24.25
Maximum of Months 9.00 23.38 480.00 24.33 0.00 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.50 24.44 464.83 24.41 6.50 24.43
February 19.17 26.43 427.83 24.51 19.00 24.59
March 30.00 26.23 503.83 24.47 30.00 24.57
April 35.83 26.39 484.83 24.60 35.83 24.72
May 51.33 26.48 503.83 24.69 51.33 24.85
June 49.83 26.55 494.67 24.68 49.83 24.84
July 41.17 26.66 490.00 24.70 41.17 24.84
August 43.67 25.97 504.83 24.51 43.67 24.61
September 29.67 26.33 475.17 24.54 29.67 24.64
October 34.17 26.38 475.00 24.60 34.17 24.71
November 16.33 26.22 463.00 24.49 15.83 24.55
December 27.00 24.36 433.50 24.40 12.33 24.44
             
Annual Sum or Average 393.67 26.17 5721.33 24.56 369.33 24.66
Minimum of Months 15.50 24.36 427.83 24.40 6.50 24.43
Maximum of Months 51.33 26.66 504.83 24.70 51.33 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.17 26.50 473.33 24.58 24.67 24.68
February 45.17 26.66 437.00 24.71 45.17 24.87
March 47.00 26.65 502.83 24.61 46.83 24.77
April 55.50 26.72 483.00 24.75 55.50 24.93
May 55.50 26.58 494.83 24.72 54.67 24.89
June 48.50 26.60 492.00 24.66 48.50 24.82
July 43.50 26.64 474.67 24.70 43.50 24.85
August 48.17 26.26 494.33 24.56 47.83 24.70
September 50.00 26.59 463.33 24.69 49.33 24.87
October 57.00 26.36 468.33 24.71 53.33 24.89
November 40.83 26.32 458.50 24.64 37.67 24.78
December 46.33 26.01 447.33 24.62 39.50 24.76
             
Annual Sum or Average 563.67 26.49 5689.50 24.66 546.50 24.82
Minimum of Months 26.17 26.01 437.00 24.56 24.67 24.68
Maximum of Months 57.00 26.72 502.83 24.75 55.50 24.93



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 48.33 26.80 490.50 24.77 47.00 24.94
February 41.83 26.80 447.33 24.72 41.83 24.88
March 38.17 26.48 508.17 24.55 38.17 24.68
April 35.00 26.36 484.33 24.59 35.00 24.70
May 41.00 26.26 501.83 24.60 41.00 24.72
June 39.33 26.26 494.17 24.56 39.33 24.68
July 24.00 26.56 480.83 24.59 24.00 24.68
August 40.67 25.81 501.67 24.47 40.67 24.56
September 33.50 26.40 476.00 24.57 33.50 24.68
October 53.33 26.64 485.67 24.74 53.33 24.91
November 48.33 26.79 479.17 24.75 48.33 24.92
December 54.33 26.69 471.00 24.79 52.83 24.97
             
Annual Sum or Average 497.83 26.51 5820.67 24.64 495.00 24.78
Minimum of Months 24.00 25.81 447.33 24.47 24.00 24.56
Maximum of Months 54.33 26.80 508.17 24.79 53.33 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 49.83 24.88 430.17 24.49 26.17 24.60
February 38.17 25.54 400.67 24.54 26.50 24.66
March 36.50 26.12 475.17 24.52 32.33 24.64
April 37.00 26.58 471.67 24.61 37.00 24.75
May 40.67 26.22 482.00 24.59 37.50 24.72
June 37.33 26.41 478.00 24.57 36.67 24.70
July 32.33 25.96 447.00 24.59 26.67 24.70
August 46.33 25.69 467.50 24.49 40.17 24.61
September 32.83 26.09 443.17 24.54 29.50 24.65
October 52.83 25.46 435.17 24.59 37.17 24.73
November 42.33 25.33 421.33 24.53 28.00 24.64
December 72.33 24.44 405.33 24.43 31.83 24.55
             
Annual Sum or Average 518.50 25.60 5357.17 24.54 389.50 24.66
Minimum of Months 32.33 24.44 400.67 24.43 26.17 24.55
Maximum of Months 72.33 26.58 482.00 24.61 40.17 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 497.17 24.40 0.00 24.40
February 0.00 0.00 454.00 24.41 0.00 24.41
March 3.00 26.18 514.00 24.37 3.00 24.38
April 5.33 26.64 485.00 24.48 5.33 24.50
May 28.33 26.75 508.00 24.64 28.33 24.75
June 31.67 26.79 496.00 24.65 31.67 24.77
July 17.50 26.81 497.00 24.64 17.50 24.71
August 21.50 26.40 514.00 24.50 21.50 24.57
September 1.50 26.93 485.00 24.45 1.50 24.46
October 1.67 26.79 502.00 24.47 1.67 24.47
November 0.00 0.00 489.00 24.43 0.00 24.43
December 0.00 0.00 492.00 24.38 0.00 24.38
             
Annual Sum or Average 110.50 26.69 5933.17 24.49 110.50 24.53
Minimum of Months 0.00 0.00 454.00 24.37 0.00 24.38
Maximum of Months 31.67 26.93 514.00 24.65 31.67 24.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.67 26.93 502.00 24.54 6.67 24.57
February 22.00 26.85 454.00 24.64 22.00 24.74
March 32.67 26.79 514.00 24.60 32.67 24.72
April 40.67 26.80 485.00 24.73 40.67 24.88
May 45.00 26.79 508.00 24.72 45.00 24.88
June 35.17 26.76 496.00 24.65 35.17 24.78
July 23.50 26.83 497.00 24.66 23.50 24.75
August 37.50 26.65 514.00 24.60 37.50 24.73
September 33.00 26.78 485.00 24.67 33.00 24.80
October 30.33 26.79 502.00 24.66 30.33 24.78
November 12.83 26.90 489.00 24.59 12.83 24.65
December 13.17 26.90 495.50 24.57 13.17 24.62
             
Annual Sum or Average 332.50 26.79 5941.50 24.64 332.50 24.75
Minimum of Months 6.67 26.65 454.00 24.54 6.67 24.57
Maximum of Months 45.00 26.93 514.00 24.73 45.00 24.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 106.67 25.66 501.67 25.01 106.67 25.11
February 95.17 25.68 454.00 25.01 95.17 25.11
March 110.67 25.15 514.00 24.73 110.67 24.79
April 116.83 24.74 485.00 24.62 116.83 24.64
May 189.00 24.57 508.00 24.61 189.00 24.60
June 177.50 24.60 496.00 24.60 177.50 24.60
July 113.50 24.43 497.00 24.55 113.50 24.53
August 219.17 24.44 514.00 24.48 219.17 24.47
September 148.83 24.43 485.00 24.53 148.83 24.51
October 164.50 24.73 502.00 24.67 164.50 24.68
November 136.33 25.12 489.00 24.85 136.33 24.90
December 117.00 25.54 496.33 24.97 117.00 25.06
             
Annual Sum or Average 1695.17 24.84 5942.00 24.71 1695.17 24.73
Minimum of Months 95.17 24.43 454.00 24.48 95.17 24.47
Maximum of Months 219.17 25.68 514.00 25.01 219.17 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 18.67 26.87 498.83 24.56 18.67 24.64
February 15.50 26.90 454.00 24.56 15.50 24.64
March 21.83 26.85 514.00 24.54 21.83 24.63
April 24.00 26.90 485.00 24.64 24.00 24.74
May 27.83 26.84 507.83 24.63 27.83 24.74
June 24.83 26.81 496.00 24.60 24.83 24.70
July 16.50 26.78 497.00 24.61 16.50 24.68
August 29.67 26.58 514.00 24.56 29.67 24.66
September 14.33 26.90 485.00 24.55 14.33 24.62
October 19.33 26.76 500.83 24.59 19.33 24.67
November 10.33 26.84 488.50 24.53 10.33 24.58
December 18.67 26.83 491.33 24.54 18.67 24.62
             
Annual Sum or Average 241.50 26.81 5932.33 24.58 241.50 24.66
Minimum of Months 10.33 26.58 454.00 24.53 10.33 24.58
Maximum of Months 29.67 26.90 514.00 24.64 29.67 24.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 25.84 490.33 24.40 1.00 24.40
February 5.00 26.23 452.67 24.43 5.00 24.45
March 12.33 25.92 512.33 24.39 12.33 24.43
April 17.67 26.26 485.00 24.51 17.67 24.57
May 43.50 26.53 506.67 24.67 43.50 24.80
June 44.50 26.59 495.50 24.66 44.50 24.81
July 24.50 26.69 496.83 24.63 24.50 24.72
August 32.50 26.08 511.50 24.49 32.50 24.58
September 12.50 26.15 482.33 24.46 12.50 24.50
October 15.17 26.29 493.83 24.51 15.17 24.56
November 6.83 26.22 480.67 24.45 6.83 24.47
December 5.83 25.14 471.00 24.39 4.00 24.40
             
Annual Sum or Average 221.33 26.34 5878.67 24.50 219.50 24.57
Minimum of Months 1.00 25.14 452.67 24.39 1.00 24.40
Maximum of Months 44.50 26.69 512.33 24.67 44.50 24.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 13.17 26.81 418.17 24.61 13.17 24.68
February 28.67 26.72 381.00 24.73 28.67 24.86
March 38.33 26.68 428.83 24.68 38.33 24.83
April 47.50 26.70 409.50 24.82 47.50 25.00
May 50.17 26.65 423.67 24.81 50.17 24.98
June 41.00 26.62 415.83 24.73 41.00 24.88
July 24.17 26.73 409.50 24.71 24.17 24.82
August 40.50 26.46 420.00 24.65 40.50 24.79
September 38.50 26.61 398.00 24.74 38.50 24.89
October 38.17 26.61 403.83 24.77 38.17 24.92
November 22.00 26.68 397.17 24.69 22.00 24.79
December 21.00 26.60 393.50 24.66 20.33 24.75
             
Annual Sum or Average 403.17 26.64 4899.00 24.72 402.50 24.85
Minimum of Months 13.17 26.46 381.00 24.61 13.17 24.68
Maximum of Months 50.17 26.81 428.83 24.82 50.17 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 42.17 26.94 500.67 24.79 42.17 24.94
February 36.67 26.84 454.00 24.72 36.67 24.87
March 32.17 26.50 513.50 24.53 32.17 24.64
April 16.67 26.20 485.00 24.50 16.67 24.55
May 28.00 26.22 506.17 24.55 28.00 24.63
June 24.33 26.16 495.00 24.50 24.33 24.57
July 5.50 26.38 495.83 24.48 5.50 24.50
August 27.33 25.88 511.00 24.44 27.33 24.51
September 16.67 26.31 483.17 24.49 16.67 24.55
October 41.50 26.64 497.50 24.69 41.50 24.83
November 41.83 26.81 486.50 24.74 41.83 24.89
December 44.83 26.92 492.83 24.79 44.83 24.96
             
Annual Sum or Average 357.67 26.57 5921.17 24.60 357.67 24.71
Minimum of Months 5.50 25.88 454.00 24.44 5.50 24.50
Maximum of Months 44.83 26.94 513.50 24.79 44.83 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.50 26.15 468.67 24.52 20.83 24.62
February 19.83 26.70 432.00 24.53 19.83 24.62
March 28.17 26.58 503.50 24.50 28.17 24.61
April 31.83 26.64 483.00 24.60 31.83 24.72
May 32.67 26.51 495.83 24.58 32.33 24.70
June 32.67 26.48 492.17 24.55 32.67 24.66
July 15.50 26.66 470.50 24.54 15.50 24.61
August 35.17 26.24 493.17 24.50 35.17 24.61
September 21.50 26.53 461.67 24.51 21.50 24.60
October 29.67 26.44 458.00 24.60 29.00 24.71
November 19.17 26.58 455.83 24.53 19.00 24.61
December 30.00 26.02 442.33 24.53 24.67 24.64
             
Annual Sum or Average 321.67 26.44 5656.67 24.54 310.50 24.64
Minimum of Months 15.50 26.02 432.00 24.50 15.50 24.60
Maximum of Months 35.17 26.70 503.50 24.60 35.17 24.72



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.47368 46.85268 0.58310 12.44738
February 454.00000 24.43316 47.06080 0.57665 12.24538
March 514.00000 24.37127 47.28944 0.56365 11.90283
April 485.00000 24.39964 47.26078 0.56802 12.02046
May 508.00000 24.40562 47.21551 -0.2711 7.05142
June 496.00000 24.38972 47.17333 -0.2716 7.05629
July 497.00000 24.45202 47.13973 -0.2618 7.03302
August 514.00000 24.40482 47.39480 -0.2754 7.16776
September 485.00000 24.40517 47.43837 -0.2744 7.08196
October 502.00000 24.46198 47.28084 0.57822 12.33330
November 489.00000 24.46821 47.16478 0.58106 12.39273
December 497.00000 24.45400 47.09191 0.57677 12.26230
           
Annual Sum or Average 5943.00000 24.42642 47.19798 0.21935 10.06194
Minimum of Months 454.00000 24.37127 46.85268 -0.2754 7.03302
Maximum of Months 514.00000 24.47368 47.43837 0.58310 12.44738



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.25865 48.20811 0.52344 10.94740
February 454.00000 24.22598 48.31849 0.51911 10.80496
March 514.00000 24.19293 48.51183 0.51276 10.65751
April 485.00000 24.20864 48.44594 0.51585 10.73598
May 508.00000 24.23749 48.35734 -0.3402 7.76425
June 496.00000 24.23178 48.31237 -0.3383 7.72026
July 497.00000 24.22865 48.46310 -0.3486 7.93766
August 514.00000 24.19995 48.71560 -0.3585 8.05851
September 485.00000 24.19189 48.73572 -0.3595 8.05116
October 502.00000 24.23580 48.58047 0.51711 10.81379
November 489.00000 24.24698 48.47875 0.52027 10.85372
December 497.00000 24.20688 48.43401 0.50863 10.59447
           
Annual Sum or Average 5943.00000 24.22209 48.46456 0.15253 9.56634
Minimum of Months 454.00000 24.19189 48.20811 -0.3595 7.72026
Maximum of Months 514.00000 24.25865 48.73572 0.52344 10.94740



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.21500 47.86112 0.51761 10.82838
February 454.00000 24.20488 47.97114 0.52067 10.85778
March 514.00000 24.20065 48.24014 0.52426 10.92352
April 485.00000 24.24090 48.31369 0.53603 11.19372
May 508.00000 24.25860 48.28650 -0.3170 7.50575
June 496.00000 24.25463 48.24283 -0.3131 7.42545
July 497.00000 24.24031 48.34315 -0.3321 7.71618
August 514.00000 24.18316 48.74689 -0.3512 7.94854
September 485.00000 24.19903 48.69199 -0.3428 7.84285
October 502.00000 24.22333 48.62390 0.52186 10.93689
November 489.00000 24.20954 48.45394 0.51866 10.82823
December 497.00000 24.14057 48.29714 0.49811 10.39158
           
Annual Sum or Average 5943.00000 24.21422 48.34186 0.16165 9.52029
Minimum of Months 454.00000 24.14057 47.86112 -0.3512 7.42545
Maximum of Months 514.00000 24.25860 48.74689 0.53603 11.19372



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.35053 49.25394 0.57789 12.46992
February 454.00000 24.38806 49.04490 0.59591 12.97425
March 514.00000 24.35745 49.89048 0.60399 13.11834
April 485.00000 24.46804 49.83825 0.64066 14.18842
May 508.00000 24.50549 49.84827 -0.1467 6.92107
June 496.00000 24.48745 49.50331 -0.1282 6.75838
July 497.00000 24.52497 49.07048 -0.1658 6.96966
August 514.00000 24.36888 51.20546 -0.2198 7.00831
September 485.00000 24.41135 50.07912 -0.2209 7.03266
October 502.00000 24.43238 50.33881 0.60540 13.34022
November 489.00000 24.39094 49.84130 0.59199 12.85424
December 497.00000 24.29854 49.72687 0.56147 12.10754
           
Annual Sum or Average 5943.00000 24.41529 49.81262 0.27152 10.45254
Minimum of Months 454.00000 24.29854 49.04490 -0.2209 6.75838
Maximum of Months 514.00000 24.52497 51.20546 0.64066 14.18842



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.42906 48.69313 0.63166 14.00558
February 454.00000 24.47278 48.42630 0.65716 14.82270
March 514.00000 24.40523 49.23494 0.65974 14.85959
April 485.00000 24.51864 49.22610 0.69443 15.95850
May 508.00000 24.48660 49.71263 -0.1262 7.06730
June 496.00000 24.45590 49.54148 -0.1238 6.76128
July 497.00000 24.47938 49.17738 -0.1623 6.99486
August 514.00000 24.36042 50.92738 -0.1842 7.03714
September 485.00000 24.44790 49.66048 -0.1632 7.15434
October 502.00000 24.44582 49.99829 0.63748 14.40428
November 489.00000 24.42964 49.45619 0.63044 14.05444
December 497.00000 24.38427 49.14799 0.61361 13.65849
           
Annual Sum or Average 5943.00000 24.44233 49.44480 0.31038 11.36413
Minimum of Months 454.00000 24.36042 48.42630 -0.1842 6.76128
Maximum of Months 514.00000 24.51864 50.92738 0.69443 15.95850



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.54669 48.08312 0.67855 15.57032
February 454.00000 24.51218 48.17717 0.66987 15.23707
March 514.00000 24.40058 49.49687 0.63403 14.02721
April 485.00000 24.45795 49.90856 0.63593 14.04629
May 508.00000 24.45549 50.22618 -0.1856 6.90901
June 496.00000 24.42706 50.10868 -0.1911 6.84267
July 497.00000 24.46506 49.48218 -0.2100 7.07766
August 514.00000 24.34224 51.42597 -0.2397 7.08682
September 485.00000 24.42604 49.95954 -0.2076 7.00107
October 502.00000 24.50038 49.82526 0.64145 14.47134
November 489.00000 24.52365 48.94415 0.66094 15.00517
December 497.00000 24.52253 48.40831 0.66771 15.35811
           
Annual Sum or Average 5943.00000 24.46421 49.51824 0.29258 11.51792
Minimum of Months 454.00000 24.34224 48.08312 -0.2397 6.84267
Maximum of Months 514.00000 24.54669 51.42597 0.67855 15.57032



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.28242 49.08221 0.60064 13.40412
February 454.00000 24.31968 48.86247 0.62257 13.93905
March 514.00000 24.32543 49.53638 0.64173 14.41272
April 485.00000 24.43036 49.56477 0.67157 15.26561
May 508.00000 24.39883 49.98283 -0.1592 7.13158
June 496.00000 24.39027 49.81827 -0.1512 6.97132
July 497.00000 24.38071 49.47531 -0.1959 7.28291
August 514.00000 24.27996 51.21231 -0.2149 7.34970
September 485.00000 24.32965 50.02289 -0.2047 7.32201
October 502.00000 24.32963 50.29586 0.61111 13.69331
November 489.00000 24.29459 49.78218 0.60124 13.32149
December 497.00000 24.20780 49.61001 0.57663 12.85955
           
Annual Sum or Average 5943.00000 24.33062 49.78062 0.28001 11.05128
Minimum of Months 454.00000 24.20780 48.86247 -0.2149 6.97132
Maximum of Months 514.00000 24.43036 51.21231 0.67157 15.26561



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.39021 48.32119 0.57992 12.32798
February 454.00000 24.41478 48.24983 0.59321 12.71861
March 514.00000 24.35649 48.81166 0.58931 12.57632
April 485.00000 24.45419 48.59553 0.62092 13.48733
May 508.00000 24.52164 48.30467 -0.1559 6.62252
June 496.00000 24.51607 48.00351 -0.1313 6.47049
July 497.00000 24.56637 47.81563 -0.1553 6.59522
August 514.00000 24.42131 49.23310 -0.2103 6.73080
September 485.00000 24.44048 48.62566 -0.2187 6.72375
October 502.00000 24.45898 48.86173 0.60177 13.03176
November 489.00000 24.43166 48.59783 0.59368 12.72904
December 497.00000 24.37764 48.65982 0.57479 12.20229
           
Annual Sum or Average 5943.00000 24.44582 48.51080 0.27038 10.15843
Minimum of Months 454.00000 24.35649 47.81563 -0.2187 6.47049
Maximum of Months 514.00000 24.56637 49.23310 0.62092 13.48733



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.50609 47.81129 0.64362 14.15293
February 454.00000 24.53517 47.66538 0.66508 14.85393
March 514.00000 24.46042 48.16704 0.66024 14.70610
April 485.00000 24.55404 48.01158 0.68770 15.59382
May 508.00000 24.53819 48.24388 -0.1237 6.67524
June 496.00000 24.50266 48.12052 -0.1215 6.42943
July 497.00000 24.55582 47.94709 -0.1427 6.54621
August 514.00000 24.45459 49.02887 -0.1613 6.59506
September 485.00000 24.52665 48.24180 -0.1449 6.67211
October 502.00000 24.53608 48.53178 0.64815 14.46643
November 489.00000 24.52809 48.21773 0.64557 14.28326
December 497.00000 24.50175 48.14596 0.63669 14.02525
           
Annual Sum or Average 5943.00000 24.51610 48.18413 0.32108 11.21436
Minimum of Months 454.00000 24.45459 47.66538 -0.1613 6.42943
Maximum of Months 514.00000 24.55582 49.02887 0.68770 15.59382



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.87490 52.42123 0.78461 18.75294
February 454.00000 24.87416 52.42453 0.77918 18.55568
March 514.00000 24.64035 54.97894 0.71908 16.44533
April 485.00000 24.59745 57.01200 0.70754 16.02690
May 508.00000 24.62046 59.90774 -0.0746 6.13066
June 496.00000 24.60546 59.91495 -0.0743 6.14268
July 497.00000 24.57675 56.84592 -0.1208 6.12296
August 514.00000 24.49251 61.64816 -0.1171 6.12285
September 485.00000 24.56439 58.90832 -0.1001 6.09669
October 502.00000 24.65088 58.61975 0.73830 17.09257
November 489.00000 24.77200 56.04389 0.76952 18.16518
December 497.00000 24.82905 52.91488 0.77372 18.44495
           
Annual Sum or Average 5943.00000 24.67311 56.84310 0.39514 12.78864
Minimum of Months 454.00000 24.49251 52.42123 -0.1208 6.09669
Maximum of Months 514.00000 24.87490 61.64816 0.78461 18.75294



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.46581 47.96732 0.63303 13.91822
February 454.00000 24.48168 47.87364 0.64985 14.39908
March 514.00000 24.44181 48.31910 0.65455 14.53296
April 485.00000 24.52535 48.21601 0.67716 15.24333
May 508.00000 24.50575 48.40800 -0.1405 6.60169
June 496.00000 24.48497 48.28165 -0.1341 6.49835
July 497.00000 24.53853 48.07190 -0.1529 6.59153
August 514.00000 24.44216 49.18444 -0.1722 6.64524
September 485.00000 24.48302 48.44541 -0.1654 6.61680
October 502.00000 24.50525 48.66725 0.63906 14.17155
November 489.00000 24.48157 48.37281 0.63347 13.92126
December 497.00000 24.44748 48.33709 0.62330 13.66672
           
Annual Sum or Average 5943.00000 24.48336 48.35122 0.30884 11.03461
Minimum of Months 454.00000 24.44181 47.87364 -0.1722 6.49835
Maximum of Months 514.00000 24.53853 49.18444 0.67716 15.24333



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.37937 49.28489 0.57812 12.35521
February 454.00000 24.40585 49.09134 0.59113 12.72669
March 514.00000 24.35654 49.76618 0.59101 12.68010
April 485.00000 24.45066 49.64531 0.62111 13.56257
May 508.00000 24.50448 49.53439 -0.1676 6.85264
June 496.00000 24.48609 49.21876 -0.1510 6.70806
July 497.00000 24.52649 48.89371 -0.1819 6.86711
August 514.00000 24.38339 50.74474 -0.2314 6.99198
September 485.00000 24.41004 49.81140 -0.2380 6.97764
October 502.00000 24.44261 49.98710 0.59771 13.01327
November 489.00000 24.41425 49.61829 0.58859 12.66703
December 497.00000 24.34733 49.60422 0.56617 12.06441
           
Annual Sum or Average 5943.00000 24.42552 49.60692 0.26048 10.26381
Minimum of Months 454.00000 24.34733 48.89371 -0.2380 6.70806
Maximum of Months 514.00000 24.52649 50.74474 0.62111 13.56257



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 24.52600 48.66495 0.63264 14.01518
February 385.00000 24.56847 48.38923 0.65486 14.73943
March 433.00000 24.48917 49.11890 0.64916 14.57961
April 410.00000 24.60335 49.02032 0.68119 15.60442
May 430.00000 24.57662 49.41140 -0.1393 7.17455
June 418.00000 24.53573 49.31379 -0.1425 6.88440
July 422.00000 24.56303 48.93499 -0.1727 7.02975
August 433.00000 24.44851 50.62789 -0.1941 7.17773
September 410.00000 24.53392 49.32430 -0.1746 7.22350
October 427.00000 24.54050 49.63453 0.63452 14.30651
November 417.00000 24.53073 49.17924 0.63087 14.05673
December 422.00000 24.49183 48.98073 0.61831 13.73080
           
Annual Sum or Average 5034.00000 24.53335 49.22599 0.30385 11.34958
Minimum of Months 385.00000 24.44851 48.38923 -0.1941 6.88440
Maximum of Months 433.00000 24.60335 50.62789 0.68119 15.60442



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.60320 48.02224 0.68214 15.57806
February 454.00000 24.54918 48.15698 0.66730 15.05839
March 514.00000 24.40892 49.34598 0.62218 13.62064
April 485.00000 24.44133 49.71645 0.61671 13.43377
May 508.00000 24.45031 49.92973 -0.2068 6.87662
June 496.00000 24.41641 49.84569 -0.2148 6.83734
July 497.00000 24.46109 49.31510 -0.2266 6.97945
August 514.00000 24.35780 50.96465 -0.2505 7.07692
September 485.00000 24.42795 49.68489 -0.2243 6.93110
October 502.00000 24.51980 49.45993 0.63483 14.18145
November 489.00000 24.55775 48.68130 0.65810 14.84040
December 497.00000 24.59351 48.21426 0.67456 15.42599
           
Annual Sum or Average 5943.00000 24.48140 49.29053 0.28241 11.36941
Minimum of Months 454.00000 24.35780 48.02224 -0.2505 6.83734
Maximum of Months 514.00000 24.60320 50.96465 0.68214 15.57806



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.37241 49.05820 0.61191 13.49313
February 454.00000 24.38799 48.86402 0.62690 13.85207
March 514.00000 24.36882 49.39409 0.63681 14.11932
April 485.00000 24.45740 49.34235 0.66044 14.82177
May 508.00000 24.43329 49.67965 -0.1698 6.92540
June 496.00000 24.41531 49.54430 -0.1656 6.80193
July 497.00000 24.42531 49.26144 -0.1999 7.00633
August 514.00000 24.34037 50.74206 -0.2138 7.10478
September 485.00000 24.37722 49.70745 -0.2093 7.06499
October 502.00000 24.39713 49.89796 0.61417 13.59683
November 489.00000 24.37804 49.49915 0.60884 13.35702
December 497.00000 24.32185 49.42325 0.59313 13.02408
           
Annual Sum or Average 5943.00000 24.38938 49.54265 0.27950 10.90204
Minimum of Months 454.00000 24.32185 48.86402 -0.2138 6.80193
Maximum of Months 514.00000 24.45740 50.74206 0.66044 14.82177



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.101151E+12 0.236333E+11 453.50 0.693661E+11 0.317844E+11 0.00 1.00 01-JAN-00:12 0.00 01-JAN-00:10 110266.42 09-JAN-05:02 77416.72 30-JAN-07:03 34413.18 10-JAN-13:03 23322.05 12-JAN-13:02 0.00
February 0.954913E+11 0.226613E+11 414.63 0.655741E+11 0.299171E+11 0.00 1.00 01-FEB-06:12 0.00 01-FEB-00:10 105720.52 06-FEB-06:02 80550.86 21-FEB-07:03 36632.61 06-FEB-06:03 26044.15 13-FEB-15:20 0.00
March 0.115774E+12 0.278001E+11 480.04 0.774720E+11 0.383018E+11 0.00 1.00 01-MAR-05:02 0.00 01-MAR-00:10 124664.54 28-MAR-04:02 83080.46 20-MAR-04:02 42960.93 28-MAR-04:02 27889.77 28-MAR-04:02 0.00
April 0.120808E+12 0.288481E+11 460.18 0.739592E+11 0.468489E+11 0.00 1.00 01-APR-04:03 0.00 01-APR-00:10 125175.24 12-APR-04:02 82858.46 17-APR-04:02 45422.96 10-APR-17:00 27895.70 12-APR-04:02 0.00
May 0.138299E+12 0.327148E+11 487.12 0.787161E+11 0.595824E+11 0.00 1.00 01-MAY-00:23 0.00 01-MAY-00:02 130461.07 20-MAY-04:02 83677.62 30-MAY-06:03 55137.90 20-MAY-04:02 30132.88 04-MAY-13:00 0.00
June 0.138936E+12 0.330126E+11 471.13 0.797039E+11 0.592320E+11 0.00 1.00 01-JUN-04:02 0.00 01-JUN-00:10 131519.24 10-JUN-04:02 83185.58 19-JUN-06:03 55080.73 10-JUN-04:02 31394.41 13-JUN-15:00 0.00
July 0.111659E+12 0.256696E+11 461.31 0.690435E+11 0.426156E+11 0.00 1.00 01-JUL-04:03 0.00 01-JUL-00:10 114118.97 10-JUL-04:02 81543.00 10-JUL-04:02 39433.74 03-JUL-12:03 24796.16 10-JUL-04:02 0.00
August 0.130376E+12 0.299182E+11 474.03 0.730022E+11 0.573733E+11 0.00 1.00 01-AUG-04:02 0.00 01-AUG-00:10 129879.82 07-AUG-04:02 82934.34 02-AUG-04:02 50591.73 14-AUG-17:00 29672.03 02-AUG-04:02 0.00
September 0.118823E+12 0.272962E+11 450.92 0.678289E+11 0.509942E+11 0.00 1.00 01-SEP-04:03 0.00 01-SEP-00:10 125575.04 25-SEP-04:02 82474.65 05-SEP-06:03 47271.43 19-SEP-05:03 27413.12 25-SEP-04:02 0.00
October 0.115485E+12 0.261653E+11 455.59 0.663399E+11 0.491452E+11 0.00 1.00 01-OCT-06:23 0.00 01-OCT-00:10 115125.27 05-OCT-04:02 81540.50 16-OCT-04:02 45397.52 16-OCT-12:03 25768.43 16-OCT-14:20 0.00
November 0.107656E+12 0.246109E+11 437.82 0.659595E+11 0.416960E+11 0.00 1.00 01-NOV-04:03 0.00 01-NOV-00:10 116843.32 13-NOV-07:03 82499.78 13-NOV-07:03 45639.85 10-NOV-13:02 25745.99 13-NOV-07:03 0.00
December 0.989210E+11 0.227953E+11 439.33 0.653277E+11 0.335933E+11 0.00 1.00 01-DEC-06:12 0.00 01-DEC-00:10 107749.49 04-DEC-07:03 78573.92 26-DEC-07:03 40637.36 30-DEC-05:03 24301.49 11-DEC-13:02 0.00
                                       
Annual Sum or Average 0.139338E+13 0.325126E+12 5485.60 0.852293E+12 0.541084E+12 0.00                         0.00
Minimum of Months 0.954913E+11 0.226613E+11 414.63 0.653277E+11 0.299171E+11 0.00 1.00   0.00   105720.52   77416.72   34413.18   23322.05   0.00
Maximum of Months 0.138936E+12 0.330126E+11 487.12 0.797039E+11 0.595824E+11 0.00 1.00   0.00   131519.24   83677.62   55137.90   31394.41   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.866506E+11 0.201938E+11 438.14 0.578918E+11 0.287588E+11 0.00 1.00 01-JAN-06:40 0.00 01-JAN-00:10 107134.60 09-JAN-05:02 68170.48 09-JAN-05:02 38964.11 09-JAN-05:02 22592.89 09-JAN-05:02 0.00
February 0.829888E+11 0.196259E+11 403.82 0.553682E+11 0.276206E+11 0.00 1.00 01-FEB-07:03 0.00 01-FEB-00:10 113997.82 06-FEB-06:02 73706.11 21-FEB-05:02 43788.59 06-FEB-06:03 24043.28 06-FEB-06:02 0.00
March 0.100996E+12 0.241206E+11 470.65 0.655566E+11 0.354391E+11 0.00 1.00 01-MAR-05:02 0.00 01-MAR-00:10 116991.25 27-MAR-04:02 75130.80 20-MAR-04:02 44364.40 28-MAR-04:02 26394.30 26-MAR-14:02 0.00
April 0.106330E+12 0.251593E+11 448.35 0.625305E+11 0.437996E+11 0.00 1.00 01-APR-04:03 0.00 01-APR-00:10 116920.60 12-APR-04:02 74698.26 03-APR-04:02 45259.52 30-APR-16:02 26549.85 30-APR-16:02 0.00
May 0.121182E+12 0.284342E+11 472.54 0.661001E+11 0.550821E+11 0.00 1.00 01-MAY-00:33 0.00 01-MAY-00:02 121197.09 22-MAY-04:02 74198.93 15-MAY-04:02 58740.60 22-MAY-04:04 26973.92 04-MAY-13:00 0.00
June 0.121662E+12 0.286400E+11 458.61 0.667082E+11 0.549541E+11 0.00 1.00 01-JUN-04:02 0.00 01-JUN-00:10 120552.22 10-JUN-04:02 74252.68 19-JUN-04:02 55485.58 10-JUN-04:02 27991.09 13-JUN-15:00 0.00
July 0.959244E+11 0.218996E+11 446.46 0.565832E+11 0.393412E+11 0.00 1.00 01-JUL-05:03 0.00 01-JUL-00:10 110643.28 10-JUL-04:02 73354.29 24-JUL-04:02 37612.05 10-JUL-04:02 23945.67 10-JUL-04:02 0.00
August 0.112356E+12 0.255589E+11 460.06 0.595610E+11 0.527952E+11 0.00 1.00 01-AUG-04:02 0.00 01-AUG-00:10 122602.32 21-AUG-04:02 73719.30 14-AUG-04:02 64035.96 21-AUG-04:02 26859.68 02-AUG-04:02 0.00
September 0.102887E+12 0.234285E+11 437.32 0.557560E+11 0.471311E+11 0.00 1.00 01-SEP-04:03 0.00 01-SEP-00:10 117421.20 25-SEP-04:02 75342.52 05-SEP-04:02 49665.96 30-SEP-11:00 25510.10 25-SEP-04:02 0.00
October 0.995558E+11 0.224064E+11 439.06 0.546750E+11 0.448808E+11 0.00 1.00 01-OCT-06:23 0.00 01-OCT-00:10 118204.29 30-OCT-04:02 73487.32 16-OCT-04:02 47483.41 30-OCT-04:02 25153.27 30-OCT-04:02 0.00
November 0.923610E+11 0.210093E+11 423.10 0.544715E+11 0.378894E+11 0.00 1.00 01-NOV-05:03 0.00 01-NOV-00:10 112933.30 13-NOV-05:02 73004.73 13-NOV-05:02 39928.57 13-NOV-05:02 24218.99 13-NOV-05:02 0.00
December 0.850336E+11 0.195310E+11 427.69 0.541900E+11 0.308436E+11 0.00 1.00 01-DEC-07:30 0.00 01-DEC-00:10 96542.77 26-DEC-07:03 69905.20 26-DEC-07:03 35656.94 11-DEC-06:13 20670.32 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.120793E+13 0.280007E+12 5325.81 0.709392E+12 0.498536E+12 0.00                         0.00
Minimum of Months 0.829888E+11 0.195310E+11 403.82 0.541900E+11 0.276206E+11 0.00 1.00   0.00   96542.77   68170.48   35656.94   20670.32   0.00
Maximum of Months 0.121662E+12 0.286400E+11 472.54 0.667082E+11 0.550821E+11 0.00 1.00   0.00   122602.32   75342.52   64035.96   27991.09   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.906283E+11 0.212511E+11 436.15 0.616796E+11 0.289487E+11 0.00 1.00 01-JAN-08:62 0.00 01-JAN-00:10 101905.43 09-JAN-05:02 70514.62 05-JAN-15:00 39318.75 09-JAN-05:02 23329.40 05-JAN-15:00 0.00
February 0.873389E+11 0.207807E+11 402.33 0.595656E+11 0.277733E+11 0.00 1.00 01-FEB-08:50 0.00 01-FEB-00:10 124295.21 06-FEB-06:02 79341.01 06-FEB-06:02 44954.20 06-FEB-06:02 26260.03 06-FEB-06:02 0.00
March 0.106940E+12 0.256682E+11 469.56 0.713687E+11 0.355709E+11 0.00 1.00 01-MAR-08:70 0.00 01-MAR-00:10 131951.68 20-MAR-04:02 85262.54 20-MAR-04:02 50033.07 13-MAR-04:02 30072.50 26-MAR-14:02 0.00
April 0.112869E+12 0.268073E+11 452.21 0.687070E+11 0.441615E+11 0.00 1.00 01-APR-04:03 0.00 01-APR-00:10 132615.35 03-APR-04:02 86179.08 17-APR-04:02 49875.46 12-APR-04:02 30208.81 02-APR-15:42 0.00
May 0.127140E+12 0.299555E+11 474.55 0.718104E+11 0.553295E+11 0.00 1.00 01-MAY-00:02 0.00 01-MAY-00:23 140661.91 22-MAY-04:02 86049.43 08-MAY-04:02 64394.59 22-MAY-04:02 30908.75 06-MAY-04:02 0.00
June 0.127953E+12 0.302405E+11 461.17 0.727948E+11 0.551578E+11 0.00 1.00 01-JUN-04:02 0.00 01-JUN-00:10 139786.72 10-JUN-05:03 84136.82 19-JUN-04:02 68385.17 10-JUN-05:03 32239.90 11-JUN-14:32 0.00
July 0.100529E+12 0.230458E+11 447.71 0.610020E+11 0.395265E+11 0.00 1.00 01-JUL-05:03 0.00 01-JUL-00:10 120200.97 10-JUL-04:02 82409.49 31-JUL-04:02 39957.38 10-JUL-04:02 26067.62 04-JUL-14:02 0.00
August 0.116678E+12 0.266241E+11 458.83 0.638849E+11 0.527934E+11 0.00 1.00 01-AUG-04:02 0.00 01-AUG-00:10 136869.07 12-AUG-05:03 84601.82 14-AUG-04:02 63976.01 12-AUG-05:03 31702.15 13-AUG-12:53 0.00
September 0.107288E+12 0.245164E+11 436.81 0.601442E+11 0.471435E+11 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:10 126691.45 11-SEP-04:02 85307.37 05-SEP-04:02 50595.21 25-SEP-04:02 28645.18 04-SEP-12:53 0.00
October 0.103010E+12 0.232558E+11 438.56 0.580687E+11 0.449415E+11 0.00 1.00 01-OCT-06:23 0.00 01-OCT-00:10 135129.77 30-OCT-04:02 81037.25 16-OCT-04:02 56378.02 30-OCT-04:02 28755.10 30-OCT-04:02 0.00
November 0.959882E+11 0.219139E+11 422.59 0.580211E+11 0.379670E+11 0.00 1.00 01-NOV-05:03 0.00 01-NOV-00:10 112812.40 13-NOV-05:02 75319.91 19-NOV-14:22 41650.16 13-NOV-05:02 25741.04 19-NOV-14:22 0.00
December 0.888566E+11 0.205081E+11 428.92 0.576860E+11 0.311706E+11 0.00 1.00 01-DEC-08:65 0.00 01-DEC-00:10 93202.15 26-DEC-07:03 69737.01 26-DEC-15:00 35426.26 30-DEC-06:03 22717.08 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.126522E+13 0.294567E+12 5329.38 0.764733E+12 0.500484E+12 0.00                         0.00
Minimum of Months 0.873389E+11 0.205081E+11 402.33 0.576860E+11 0.277733E+11 0.00 1.00   0.00   93202.15   69737.01   35426.26   22717.08   0.00
Maximum of Months 0.127953E+12 0.302405E+11 474.55 0.727948E+11 0.553295E+11 0.00 1.00   0.00   140661.91   86179.08   68385.17   32239.90   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 402.11 0.00 402.11 912.59 202.95 0.00 0.00 0.00
February 428.94 0.00 428.94 1021.84 155.29 0.00 0.00 0.00
March 440.23 0.00 440.23 1112.09 103.45 0.00 0.00 0.00
April 479.08 6.79 472.29 1247.26 45.65 0.00 0.00 0.00
May 614.13 65.42 548.70 1590.45 55.83 0.00 0.00 0.00
June 750.18 151.61 598.57 1888.81 64.06 0.00 0.00 0.00
July 645.08 67.62 577.47 1483.46 112.67 0.00 0.00 0.00
August 531.11 22.65 508.47 1242.05 84.24 0.00 0.00 0.00
September 452.18 0.22 451.97 1091.23 84.92 0.00 0.00 0.00
October 435.70 0.00 435.70 972.62 111.92 0.00 0.00 0.00
November 412.27 0.00 412.27 929.62 135.66 0.00 0.00 0.00
December 390.65 0.00 390.65 879.36 221.28 0.00 0.00 0.00
                 
Annual Sum or Average 498.77 26.26 472.51 1198.06 114.85 0.00 0.00 0.00
Minimum of Months 390.65 0.00 390.65 879.36 45.65 0.00 0.00 0.00
Maximum of Months 750.18 151.61 598.57 1888.81 221.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 516.92 174.22 342.71 1079.00 128.42 0.00 0.00 0.00
February 586.19 214.93 371.26 1252.02 96.73 0.00 0.00 0.00
March 639.06 250.25 388.81 1398.98 62.97 0.00 0.00 0.00
April 645.87 246.75 399.12 1452.57 28.34 0.00 0.00 0.00
May 555.18 168.05 387.13 1301.57 35.71 0.00 0.00 0.00
June 591.31 194.75 396.57 1367.24 40.01 0.00 0.00 0.00
July 505.06 113.15 391.92 1098.46 72.01 0.00 0.00 0.00
August 555.83 163.39 392.44 1191.47 55.00 0.00 0.00 0.00
September 521.99 142.25 379.75 1148.89 56.75 0.00 0.00 0.00
October 489.22 125.16 364.06 1024.29 74.49 0.00 0.00 0.00
November 473.47 130.84 342.63 996.82 89.73 0.00 0.00 0.00
December 484.52 155.49 329.03 1007.12 142.30 0.00 0.00 0.00
                 
Annual Sum or Average 546.61 172.87 373.74 1192.19 73.57 0.00 0.00 0.00
Minimum of Months 473.47 113.15 329.03 996.82 28.34 0.00 0.00 0.00
Maximum of Months 645.87 250.25 399.12 1452.57 142.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1064.65 444.18 620.46 2243.41 207.53 0.00 0.00 0.00
February 904.04 294.75 609.29 2052.00 154.38 0.00 0.00 0.00
March 616.96 82.86 534.10 1550.91 98.38 0.00 0.00 0.00
April 459.97 0.21 459.77 1214.28 40.74 0.00 0.00 0.00
May 460.29 0.00 460.29 1246.28 51.09 0.00 0.00 0.00
June 458.63 0.00 458.63 1237.60 56.44 0.00 0.00 0.00
July 472.46 0.00 472.46 1103.05 106.36 0.00 0.00 0.00
August 459.94 0.71 459.23 1083.21 77.63 0.00 0.00 0.00
September 509.19 16.63 492.56 1221.78 85.15 0.00 0.00 0.00
October 666.17 106.21 559.95 1466.33 118.30 0.00 0.00 0.00
November 866.24 264.28 601.96 1855.88 145.36 0.00 0.00 0.00
December 1064.10 452.73 611.37 2209.22 231.08 0.00 0.00 0.00
                 
Annual Sum or Average 665.96 138.01 527.95 1537.85 114.40 0.00 0.00 0.00
Minimum of Months 458.63 0.00 458.63 1083.21 40.74 0.00 0.00 0.00
Maximum of Months 1064.65 452.73 620.46 2243.41 231.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 523.76 184.17 339.59 1109.55 142.31 0.00 0.00 0.00
February 575.23 203.56 371.67 1245.67 108.65 0.00 0.00 0.00
March 644.79 254.68 390.11 1420.64 77.53 0.00 0.00 0.00
April 647.98 248.19 399.80 1449.00 34.92 0.00 0.00 0.00
May 551.36 163.34 388.02 1286.91 35.99 0.00 0.00 0.00
June 597.47 205.93 391.54 1371.56 40.95 0.00 0.00 0.00
July 509.37 120.12 389.25 1107.37 74.10 0.00 0.00 0.00
August 553.79 164.00 389.79 1182.05 56.17 0.00 0.00 0.00
September 518.71 143.87 374.84 1138.54 59.40 0.00 0.00 0.00
October 487.17 125.58 361.59 1021.58 77.95 0.00 0.00 0.00
November 475.09 129.57 345.52 1006.04 94.08 0.00 0.00 0.00
December 486.21 159.05 327.16 1029.85 153.58 0.00 0.00 0.00
                 
Annual Sum or Average 547.22 174.87 372.35 1196.52 79.64 0.00 0.00 0.00
Minimum of Months 475.09 120.12 327.16 1006.04 34.92 0.00 0.00 0.00
Maximum of Months 647.98 254.68 399.80 1449.00 153.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.03 0.00 134.03 305.05 71.29 0.00 0.00 0.00
February 142.97 0.00 142.97 342.08 55.40 0.00 0.00 0.00
March 146.74 0.00 146.74 372.83 36.54 0.00 0.00 0.00
April 159.69 2.26 157.42 418.45 16.11 0.00 0.00 0.00
May 204.70 21.81 182.89 532.19 20.87 0.00 0.00 0.00
June 250.05 50.53 199.51 631.16 24.22 0.00 0.00 0.00
July 215.02 22.54 192.48 496.16 41.86 0.00 0.00 0.00
August 177.03 7.55 169.48 413.71 32.62 0.00 0.00 0.00
September 150.72 0.07 150.65 364.40 31.67 0.00 0.00 0.00
October 145.23 0.00 145.23 325.65 39.87 0.00 0.00 0.00
November 137.42 0.00 137.42 310.88 49.49 0.00 0.00 0.00
December 130.21 0.00 130.21 292.92 80.16 0.00 0.00 0.00
                 
Annual Sum or Average 166.25 8.75 157.50 400.60 41.69 0.00 0.00 0.00
Minimum of Months 130.21 0.00 130.21 292.92 16.11 0.00 0.00 0.00
Maximum of Months 250.05 50.53 199.51 631.16 80.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.04 0.00 134.04 305.07 71.30 0.00 0.00 0.00
February 142.98 0.00 142.98 342.09 55.40 0.00 0.00 0.00
March 146.74 0.00 146.74 372.85 36.54 0.00 0.00 0.00
April 159.69 2.26 157.43 418.47 16.11 0.00 0.00 0.00
May 204.71 21.81 182.90 532.22 20.87 0.00 0.00 0.00
June 250.06 50.53 199.52 631.19 24.22 0.00 0.00 0.00
July 215.02 22.54 192.49 496.18 41.87 0.00 0.00 0.00
August 177.04 7.55 169.49 413.73 32.62 0.00 0.00 0.00
September 150.73 0.07 150.65 364.41 31.67 0.00 0.00 0.00
October 145.23 0.00 145.23 325.66 39.87 0.00 0.00 0.00
November 137.42 0.00 137.42 310.89 49.50 0.00 0.00 0.00
December 130.21 0.00 130.21 292.93 80.17 0.00 0.00 0.00
                 
Annual Sum or Average 166.25 8.75 157.50 400.62 41.69 0.00 0.00 0.00
Minimum of Months 130.21 0.00 130.21 292.93 16.11 0.00 0.00 0.00
Maximum of Months 250.06 50.53 199.52 631.19 80.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 134.04 0.00 134.04 305.07 71.30 0.00 0.00 0.00
February 142.98 0.00 142.98 342.09 55.40 0.00 0.00 0.00
March 146.74 0.00 146.74 372.85 36.54 0.00 0.00 0.00
April 159.69 2.26 157.43 418.47 16.11 0.00 0.00 0.00
May 204.71 21.81 182.90 532.22 20.87 0.00 0.00 0.00
June 250.06 50.53 199.52 631.19 24.22 0.00 0.00 0.00
July 215.02 22.54 192.49 496.18 41.87 0.00 0.00 0.00
August 177.04 7.55 169.49 413.73 32.62 0.00 0.00 0.00
September 150.73 0.07 150.65 364.41 31.67 0.00 0.00 0.00
October 145.23 0.00 145.23 325.66 39.87 0.00 0.00 0.00
November 137.42 0.00 137.42 310.89 49.50 0.00 0.00 0.00
December 130.21 0.00 130.21 292.93 80.17 0.00 0.00 0.00
                 
Annual Sum or Average 166.25 8.75 157.50 400.62 41.69 0.00 0.00 0.00
Minimum of Months 130.21 0.00 130.21 292.93 16.11 0.00 0.00 0.00
Maximum of Months 250.06 50.53 199.52 631.19 80.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 497.26 167.59 329.67 1039.74 135.81 0.00 0.00 0.00
February 563.89 206.75 357.14 1207.16 106.41 0.00 0.00 0.00
March 614.74 240.73 374.01 1351.12 72.34 0.00 0.00 0.00
April 621.29 237.36 383.93 1400.84 33.73 0.00 0.00 0.00
May 534.05 161.66 372.40 1253.31 40.51 0.00 0.00 0.00
June 568.81 187.34 381.48 1317.02 45.16 0.00 0.00 0.00
July 485.85 108.84 377.00 1058.28 79.42 0.00 0.00 0.00
August 534.68 157.17 377.51 1145.46 65.33 0.00 0.00 0.00
September 502.13 136.83 365.30 1105.83 65.69 0.00 0.00 0.00
October 470.61 120.40 350.21 988.04 81.53 0.00 0.00 0.00
November 455.46 125.86 329.59 960.93 99.36 0.00 0.00 0.00
December 466.09 149.57 316.51 969.04 153.95 0.00 0.00 0.00
                 
Annual Sum or Average 525.81 166.29 359.52 1148.75 81.62 0.00 0.00 0.00
Minimum of Months 455.46 108.84 316.51 960.93 33.73 0.00 0.00 0.00
Maximum of Months 621.29 240.73 383.93 1400.84 153.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.66 6.63 13.03 41.11 5.37 0.00 0.00 0.00
February 22.30 8.17 14.12 47.73 4.21 0.00 0.00 0.00
March 24.31 9.52 14.79 53.42 2.86 0.00 0.00 0.00
April 24.57 9.38 15.18 55.39 1.33 0.00 0.00 0.00
May 21.12 6.39 14.72 49.55 1.60 0.00 0.00 0.00
June 22.49 7.41 15.08 52.07 1.79 0.00 0.00 0.00
July 19.21 4.30 14.91 41.84 3.14 0.00 0.00 0.00
August 21.14 6.21 14.93 45.29 2.58 0.00 0.00 0.00
September 19.85 5.41 14.44 43.72 2.60 0.00 0.00 0.00
October 18.61 4.76 13.85 39.07 3.22 0.00 0.00 0.00
November 18.01 4.98 13.03 37.99 3.93 0.00 0.00 0.00
December 18.43 5.91 12.51 38.31 6.09 0.00 0.00 0.00
                 
Annual Sum or Average 20.79 6.57 14.22 45.42 3.23 0.00 0.00 0.00
Minimum of Months 18.01 4.30 12.51 37.99 1.33 0.00 0.00 0.00
Maximum of Months 24.57 9.52 15.18 55.39 6.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 354.88 148.06 206.82 743.22 79.34 0.00 0.00 0.00
February 301.34 98.25 203.10 678.51 61.16 0.00 0.00 0.00
March 205.65 27.62 178.03 513.80 38.55 0.00 0.00 0.00
April 153.32 0.07 153.25 402.78 15.44 0.00 0.00 0.00
May 153.43 0.00 153.43 412.89 19.36 0.00 0.00 0.00
June 152.88 0.00 152.88 408.69 21.01 0.00 0.00 0.00
July 157.48 0.00 157.48 366.93 39.53 0.00 0.00 0.00
August 153.31 0.24 153.08 357.90 30.96 0.00 0.00 0.00
September 169.73 5.54 164.18 405.60 32.82 0.00 0.00 0.00
October 222.05 35.40 186.65 488.22 44.47 0.00 0.00 0.00
November 288.74 88.09 200.65 615.60 56.96 0.00 0.00 0.00
December 354.69 150.91 203.79 732.39 89.25 0.00 0.00 0.00
                 
Annual Sum or Average 221.98 46.00 175.98 509.74 44.07 0.00 0.00 0.00
Minimum of Months 152.88 0.00 152.88 357.90 15.44 0.00 0.00 0.00
Maximum of Months 354.88 150.91 206.82 743.22 89.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 354.88 148.06 206.82 743.22 79.34 0.00 0.00 0.00
February 301.34 98.25 203.10 678.51 61.16 0.00 0.00 0.00
March 205.65 27.62 178.03 513.80 38.55 0.00 0.00 0.00
April 153.32 0.07 153.25 402.78 15.44 0.00 0.00 0.00
May 153.43 0.00 153.43 412.89 19.36 0.00 0.00 0.00
June 152.88 0.00 152.88 408.69 21.01 0.00 0.00 0.00
July 157.48 0.00 157.48 366.93 39.53 0.00 0.00 0.00
August 153.31 0.24 153.08 357.90 30.96 0.00 0.00 0.00
September 169.73 5.54 164.18 405.60 32.82 0.00 0.00 0.00
October 222.05 35.40 186.65 488.22 44.47 0.00 0.00 0.00
November 288.74 88.09 200.65 615.60 56.96 0.00 0.00 0.00
December 354.69 150.91 203.79 732.39 89.25 0.00 0.00 0.00
                 
Annual Sum or Average 221.98 46.00 175.98 509.74 44.07 0.00 0.00 0.00
Minimum of Months 152.88 0.00 152.88 357.90 15.44 0.00 0.00 0.00
Maximum of Months 354.88 150.91 206.82 743.22 89.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 354.85 148.05 206.81 743.17 79.33 0.00 0.00 0.00
February 301.32 98.24 203.08 678.46 61.16 0.00 0.00 0.00
March 205.64 27.62 178.02 513.77 38.55 0.00 0.00 0.00
April 153.31 0.07 153.24 402.75 15.44 0.00 0.00 0.00
May 153.42 0.00 153.42 412.86 19.36 0.00 0.00 0.00
June 152.87 0.00 152.87 408.67 21.00 0.00 0.00 0.00
July 157.47 0.00 157.47 366.91 39.53 0.00 0.00 0.00
August 153.30 0.24 153.07 357.88 30.96 0.00 0.00 0.00
September 169.72 5.54 164.17 405.57 32.82 0.00 0.00 0.00
October 222.04 35.40 186.64 488.19 44.47 0.00 0.00 0.00
November 288.72 88.08 200.64 615.56 56.95 0.00 0.00 0.00
December 354.67 150.90 203.77 732.34 89.24 0.00 0.00 0.00
                 
Annual Sum or Average 221.97 46.00 175.97 509.70 44.06 0.00 0.00 0.00
Minimum of Months 152.87 0.00 152.87 357.88 15.44 0.00 0.00 0.00
Maximum of Months 354.85 150.90 206.81 743.17 89.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 503.83 177.16 326.67 1067.15 150.65 0.00 0.00 0.00
February 553.35 195.82 357.53 1199.53 119.50 0.00 0.00 0.00
March 620.26 244.99 375.27 1369.89 86.76 0.00 0.00 0.00
April 623.33 238.74 384.59 1395.99 41.13 0.00 0.00 0.00
May 530.38 157.13 373.26 1237.69 42.09 0.00 0.00 0.00
June 574.74 198.10 376.64 1319.69 47.47 0.00 0.00 0.00
July 489.99 115.55 374.44 1065.67 83.24 0.00 0.00 0.00
August 532.72 157.76 374.96 1135.07 68.17 0.00 0.00 0.00
September 498.97 138.39 360.58 1094.55 69.08 0.00 0.00 0.00
October 468.63 120.80 347.83 982.92 86.11 0.00 0.00 0.00
November 457.01 124.64 332.37 967.05 104.67 0.00 0.00 0.00
December 467.71 153.00 314.72 988.33 167.27 0.00 0.00 0.00
                 
Annual Sum or Average 526.40 168.21 358.18 1151.11 88.85 0.00 0.00 0.00
Minimum of Months 457.01 115.55 314.72 967.05 41.13 0.00 0.00 0.00
Maximum of Months 623.33 244.99 384.59 1395.99 167.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.92 7.00 12.92 42.19 5.96 0.00 0.00 0.00
February 21.88 7.74 14.14 47.43 4.73 0.00 0.00 0.00
March 24.52 9.69 14.84 54.16 3.43 0.00 0.00 0.00
April 24.65 9.44 15.21 55.20 1.63 0.00 0.00 0.00
May 20.97 6.21 14.76 48.94 1.66 0.00 0.00 0.00
June 22.72 7.83 14.89 52.18 1.88 0.00 0.00 0.00
July 19.37 4.57 14.81 42.14 3.29 0.00 0.00 0.00
August 21.06 6.24 14.83 44.88 2.70 0.00 0.00 0.00
September 19.73 5.47 14.26 43.28 2.73 0.00 0.00 0.00
October 18.53 4.78 13.75 38.86 3.40 0.00 0.00 0.00
November 18.07 4.93 13.14 38.24 4.14 0.00 0.00 0.00
December 18.49 6.05 12.44 39.08 6.61 0.00 0.00 0.00
                 
Annual Sum or Average 20.81 6.65 14.16 45.51 3.51 0.00 0.00 0.00
Minimum of Months 18.07 4.57 12.44 38.24 1.63 0.00 0.00 0.00
Maximum of Months 24.65 9.69 15.21 55.20 6.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 402.11 0.00 402.11 918.23 211.52 0.00 0.00 0.00
February 428.94 0.00 428.94 1029.64 162.52 0.00 0.00 0.00
March 440.23 0.00 440.23 1122.28 106.50 0.00 0.00 0.00
April 479.08 6.79 472.29 1260.63 46.16 0.00 0.00 0.00
May 614.13 65.42 548.70 1603.31 56.57 0.00 0.00 0.00
June 750.18 151.61 598.57 1902.22 64.15 0.00 0.00 0.00
July 645.08 67.62 577.47 1495.22 114.08 0.00 0.00 0.00
August 531.11 22.65 508.47 1250.14 86.98 0.00 0.00 0.00
September 452.18 0.22 451.97 1101.45 86.22 0.00 0.00 0.00
October 435.70 0.00 435.70 980.51 115.14 0.00 0.00 0.00
November 412.27 0.00 412.27 936.16 142.75 0.00 0.00 0.00
December 390.65 0.00 390.65 883.29 232.81 0.00 0.00 0.00
                 
Annual Sum or Average 498.77 26.26 472.51 1207.36 118.80 0.00 0.00 0.00
Minimum of Months 390.65 0.00 390.65 883.29 46.16 0.00 0.00 0.00
Maximum of Months 750.18 151.61 598.57 1902.22 232.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 516.92 174.22 342.71 1083.66 133.42 0.00 0.00 0.00
February 586.19 214.93 371.26 1258.40 101.31 0.00 0.00 0.00
March 639.06 250.25 388.81 1407.36 65.32 0.00 0.00 0.00
April 645.87 246.75 399.12 1462.36 28.91 0.00 0.00 0.00
May 555.18 168.05 387.13 1310.37 36.26 0.00 0.00 0.00
June 591.31 194.75 396.57 1376.33 40.08 0.00 0.00 0.00
July 505.06 113.15 391.92 1106.19 72.95 0.00 0.00 0.00
August 555.83 163.39 392.44 1197.34 56.76 0.00 0.00 0.00
September 521.99 142.25 379.75 1156.21 57.53 0.00 0.00 0.00
October 489.22 125.16 364.06 1030.30 76.50 0.00 0.00 0.00
November 473.47 130.84 342.63 1001.94 94.07 0.00 0.00 0.00
December 484.52 155.49 329.03 1010.65 148.99 0.00 0.00 0.00
                 
Annual Sum or Average 546.61 172.87 373.74 1199.08 76.03 0.00 0.00 0.00
Minimum of Months 473.47 113.15 329.03 1001.94 28.91 0.00 0.00 0.00
Maximum of Months 645.87 250.25 399.12 1462.36 148.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1064.65 444.18 620.46 2248.76 215.02 0.00 0.00 0.00
February 904.04 294.75 609.29 2060.08 161.31 0.00 0.00 0.00
March 616.96 82.86 534.10 1561.80 101.97 0.00 0.00 0.00
April 459.97 0.21 459.77 1227.15 41.59 0.00 0.00 0.00
May 460.29 0.00 460.29 1258.54 52.26 0.00 0.00 0.00
June 458.63 0.00 458.63 1249.91 56.84 0.00 0.00 0.00
July 472.46 0.00 472.46 1114.10 108.06 0.00 0.00 0.00
August 459.94 0.71 459.23 1090.90 80.85 0.00 0.00 0.00
September 509.19 16.63 492.56 1232.38 86.55 0.00 0.00 0.00
October 666.17 106.21 559.95 1475.19 121.35 0.00 0.00 0.00
November 866.24 264.28 601.96 1863.37 151.72 0.00 0.00 0.00
December 1064.10 452.73 611.37 2213.06 240.85 0.00 0.00 0.00
                 
Annual Sum or Average 665.96 138.01 527.95 1547.12 118.22 0.00 0.00 0.00
Minimum of Months 458.63 0.00 458.63 1090.90 41.59 0.00 0.00 0.00
Maximum of Months 1064.65 452.73 620.46 2248.76 240.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 523.76 184.17 339.59 1112.36 148.86 0.00 0.00 0.00
February 575.23 203.56 371.67 1250.44 114.36 0.00 0.00 0.00
March 644.79 254.68 390.11 1427.09 80.20 0.00 0.00 0.00
April 647.98 248.19 399.80 1456.64 35.77 0.00 0.00 0.00
May 551.36 163.34 388.02 1293.87 37.12 0.00 0.00 0.00
June 597.47 205.93 391.54 1379.39 41.83 0.00 0.00 0.00
July 509.37 120.12 389.25 1113.86 76.05 0.00 0.00 0.00
August 553.79 164.00 389.79 1186.66 58.96 0.00 0.00 0.00
September 518.71 143.87 374.84 1144.43 60.90 0.00 0.00 0.00
October 487.17 125.58 361.59 1025.72 80.96 0.00 0.00 0.00
November 475.09 129.57 345.52 1009.23 99.66 0.00 0.00 0.00
December 486.21 159.05 327.16 1031.43 162.19 0.00 0.00 0.00
                 
Annual Sum or Average 547.22 174.87 372.35 1201.71 83.07 0.00 0.00 0.00
Minimum of Months 475.09 120.12 327.16 1009.23 35.77 0.00 0.00 0.00
Maximum of Months 647.98 254.68 399.80 1456.64 162.19 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.107702E+10 0.00 0.107702E+10 0.244427E+10 0.543577E+09
February 0.103770E+10 0.00 0.103770E+10 0.247204E+10 0.375681E+09
March 0.117910E+10 0.00 0.117910E+10 0.297862E+10 0.277075E+09
April 0.124178E+10 17598406.75 0.122419E+10 0.323290E+10 0.118334E+09
May 0.164488E+10 0.175229E+09 0.146965E+10 0.425987E+10 0.149529E+09
June 0.194446E+10 0.392960E+09 0.155150E+10 0.489581E+10 0.166044E+09
July 0.172779E+10 0.181103E+09 0.154669E+10 0.397329E+10 0.301778E+09
August 0.142253E+10 60657918.87 0.136188E+10 0.332672E+10 0.225628E+09
September 0.117206E+10 561246.81 0.117150E+10 0.282847E+10 0.220112E+09
October 0.116697E+10 0.00 0.116697E+10 0.260507E+10 0.299772E+09
November 0.106859E+10 0.00 0.106859E+10 0.240958E+10 0.351630E+09
December 0.104631E+10 0.00 0.104631E+10 0.235528E+10 0.592668E+09
           
Annual Sum or Average 0.157292E+11 0.828110E+09 0.149011E+11 0.377819E+11 0.362183E+10
Minimum of Months 0.103770E+10 0.00 0.103770E+10 0.235528E+10 0.118334E+09
Maximum of Months 0.194446E+10 0.392960E+09 0.155150E+10 0.489581E+10 0.592668E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138453E+10 0.466627E+09 0.917904E+09 0.288999E+10 0.343958E+09
February 0.141811E+10 0.519950E+09 0.898162E+09 0.302889E+10 0.234021E+09
March 0.171165E+10 0.670276E+09 0.104138E+10 0.374704E+10 0.168666E+09
April 0.167408E+10 0.639571E+09 0.103451E+10 0.376507E+10 73460764.27
May 0.148699E+10 0.450110E+09 0.103688E+10 0.348614E+10 95638448.67
June 0.153268E+10 0.504785E+09 0.102790E+10 0.354388E+10 0.103718E+09
July 0.135276E+10 0.303052E+09 0.104971E+10 0.294211E+10 0.192883E+09
August 0.148874E+10 0.437626E+09 0.105111E+10 0.319123E+10 0.147304E+09
September 0.135301E+10 0.368700E+09 0.984308E+09 0.297793E+10 0.147092E+09
October 0.131034E+10 0.335231E+09 0.975107E+09 0.274346E+10 0.199514E+09
November 0.122724E+10 0.339142E+09 0.888095E+09 0.258376E+10 0.232571E+09
December 0.129774E+10 0.416457E+09 0.881284E+09 0.269748E+10 0.381128E+09
           
Annual Sum or Average 0.172379E+11 0.545153E+10 0.117864E+11 0.375970E+11 0.231996E+10
Minimum of Months 0.122724E+10 0.303052E+09 0.881284E+09 0.258376E+10 73460764.27
Maximum of Months 0.171165E+10 0.670276E+09 0.105111E+10 0.376507E+10 0.381128E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.285155E+10 0.118970E+10 0.166185E+10 0.600875E+10 0.555843E+09
February 0.218706E+10 0.713065E+09 0.147400E+10 0.496419E+10 0.373488E+09
March 0.165246E+10 0.221927E+09 0.143054E+10 0.415396E+10 0.263511E+09
April 0.119225E+10 535209.43 0.119171E+10 0.314742E+10 0.105593E+09
May 0.123283E+10 0.00 0.123283E+10 0.333804E+10 0.136850E+09
June 0.118877E+10 0.00 0.118877E+10 0.320786E+10 0.146292E+09
July 0.126543E+10 0.00 0.126543E+10 0.295440E+10 0.284864E+09
August 0.123191E+10 1903936.76 0.123000E+10 0.290127E+10 0.207928E+09
September 0.131981E+10 43106103.77 0.127671E+10 0.316685E+10 0.220703E+09
October 0.178426E+10 0.284486E+09 0.149977E+10 0.392741E+10 0.316854E+09
November 0.224528E+10 0.685005E+09 0.156028E+10 0.481045E+10 0.376761E+09
December 0.285009E+10 0.121260E+10 0.163749E+10 0.591717E+10 0.618920E+09
           
Annual Sum or Average 0.210017E+11 0.435232E+10 0.166494E+11 0.484978E+11 0.360761E+10
Minimum of Months 0.118877E+10 0.00 0.118877E+10 0.290127E+10 0.105593E+09
Maximum of Months 0.285155E+10 0.121260E+10 0.166185E+10 0.600875E+10 0.618920E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.140283E+10 0.493279E+09 0.909547E+09 0.297181E+10 0.381156E+09
February 0.139161E+10 0.492457E+09 0.899149E+09 0.301353E+10 0.262844E+09
March 0.172702E+10 0.682138E+09 0.104488E+10 0.380504E+10 0.207669E+09
April 0.167957E+10 0.643301E+09 0.103627E+10 0.375582E+10 90514423.28
May 0.147677E+10 0.437498E+09 0.103927E+10 0.344687E+10 96385195.44
June 0.154864E+10 0.533780E+09 0.101486E+10 0.355507E+10 0.106154E+09
July 0.136431E+10 0.321735E+09 0.104257E+10 0.296599E+10 0.198459E+09
August 0.148327E+10 0.439262E+09 0.104401E+10 0.316600E+10 0.150451E+09
September 0.134449E+10 0.372902E+09 0.971586E+09 0.295109E+10 0.153974E+09
October 0.130483E+10 0.336357E+09 0.968472E+09 0.273619E+10 0.208793E+09
November 0.123142E+10 0.335847E+09 0.895577E+09 0.260766E+10 0.243862E+09
December 0.130228E+10 0.425998E+09 0.876278E+09 0.275834E+10 0.411358E+09
           
Annual Sum or Average 0.172570E+11 0.551455E+10 0.117425E+11 0.377334E+11 0.251162E+10
Minimum of Months 0.123142E+10 0.321735E+09 0.876278E+09 0.260766E+10 90514423.28
Maximum of Months 0.172702E+10 0.682138E+09 0.104488E+10 0.380504E+10 0.411358E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.358988E+09 0.00 0.358988E+09 0.817055E+09 0.190951E+09
February 0.345883E+09 0.00 0.345883E+09 0.827548E+09 0.134024E+09
March 0.393016E+09 0.00 0.393016E+09 0.998582E+09 97856864.53
April 0.413908E+09 5865858.05 0.408043E+09 0.108463E+10 41746227.57
May 0.548267E+09 58406913.62 0.489860E+09 0.142542E+10 55895112.63
June 0.648123E+09 0.130981E+09 0.517143E+09 0.163597E+10 62777344.16
July 0.575902E+09 60364849.74 0.515537E+09 0.132893E+10 0.112127E+09
August 0.474155E+09 20218349.67 0.453937E+09 0.110808E+10 87374827.78
September 0.390669E+09 187073.42 0.390482E+09 0.944516E+09 82079692.40
October 0.388972E+09 0.00 0.388972E+09 0.872215E+09 0.106777E+09
November 0.356181E+09 0.00 0.356181E+09 0.805800E+09 0.128289E+09
December 0.348752E+09 0.00 0.348752E+09 0.784557E+09 0.214712E+09
           
Annual Sum or Average 0.524282E+10 0.276024E+09 0.496679E+10 0.126333E+11 0.131461E+10
Minimum of Months 0.345883E+09 0.00 0.345883E+09 0.784557E+09 41746227.57
Maximum of Months 0.648123E+09 0.130981E+09 0.517143E+09 0.163597E+10 0.214712E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.359002E+09 0.00 0.359002E+09 0.817094E+09 0.190960E+09
February 0.345897E+09 0.00 0.345897E+09 0.827589E+09 0.134029E+09
March 0.393032E+09 0.00 0.393032E+09 0.998633E+09 97859530.24
April 0.413925E+09 5866015.72 0.408059E+09 0.108469E+10 41746600.60
May 0.548287E+09 58408483.62 0.489878E+09 0.142549E+10 55896237.63
June 0.648146E+09 0.130984E+09 0.517162E+09 0.163604E+10 62779577.54
July 0.575922E+09 60366472.37 0.515556E+09 0.132898E+10 0.112132E+09
August 0.474173E+09 20218893.15 0.453954E+09 0.110813E+10 87377886.71
September 0.390684E+09 187078.45 0.390497E+09 0.944560E+09 82082761.96
October 0.388987E+09 0.00 0.388987E+09 0.872254E+09 0.106781E+09
November 0.356194E+09 0.00 0.356194E+09 0.805836E+09 0.128295E+09
December 0.348766E+09 0.00 0.348766E+09 0.784594E+09 0.214722E+09
           
Annual Sum or Average 0.524302E+10 0.276031E+09 0.496699E+10 0.126339E+11 0.131466E+10
Minimum of Months 0.345897E+09 0.00 0.345897E+09 0.784594E+09 41746600.60
Maximum of Months 0.648146E+09 0.130984E+09 0.517162E+09 0.163604E+10 0.214722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.359002E+09 0.00 0.359002E+09 0.817094E+09 0.190960E+09
February 0.345897E+09 0.00 0.345897E+09 0.827589E+09 0.134029E+09
March 0.393032E+09 0.00 0.393032E+09 0.998633E+09 97859530.24
April 0.413925E+09 5866015.72 0.408059E+09 0.108469E+10 41746600.60
May 0.548287E+09 58408483.62 0.489878E+09 0.142549E+10 55896237.63
June 0.648146E+09 0.130984E+09 0.517162E+09 0.163604E+10 62779577.54
July 0.575922E+09 60366472.37 0.515556E+09 0.132898E+10 0.112132E+09
August 0.474173E+09 20218893.15 0.453954E+09 0.110813E+10 87377886.71
September 0.390684E+09 187078.45 0.390497E+09 0.944560E+09 82082761.96
October 0.388987E+09 0.00 0.388987E+09 0.872254E+09 0.106781E+09
November 0.356194E+09 0.00 0.356194E+09 0.805836E+09 0.128295E+09
December 0.348766E+09 0.00 0.348766E+09 0.784594E+09 0.214722E+09
           
Annual Sum or Average 0.524302E+10 0.276031E+09 0.496699E+10 0.126339E+11 0.131466E+10
Minimum of Months 0.345897E+09 0.00 0.345897E+09 0.784594E+09 41746600.60
Maximum of Months 0.648146E+09 0.130984E+09 0.517162E+09 0.163604E+10 0.214722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133185E+10 0.448870E+09 0.882980E+09 0.278485E+10 0.363742E+09
February 0.136415E+10 0.500163E+09 0.863989E+09 0.292036E+10 0.257425E+09
March 0.164653E+10 0.644769E+09 0.100176E+10 0.361883E+10 0.193755E+09
April 0.161039E+10 0.615233E+09 0.995154E+09 0.363097E+10 87423304.87
May 0.143041E+10 0.432981E+09 0.997431E+09 0.335687E+10 0.108494E+09
June 0.147437E+10 0.485576E+09 0.988790E+09 0.341370E+10 0.117042E+09
July 0.130129E+10 0.291519E+09 0.100977E+10 0.283450E+10 0.212707E+09
August 0.143209E+10 0.420973E+09 0.101112E+10 0.306801E+10 0.174981E+09
September 0.130153E+10 0.354670E+09 0.946857E+09 0.286631E+10 0.170264E+09
October 0.126048E+10 0.322474E+09 0.938006E+09 0.264636E+10 0.218359E+09
November 0.118054E+10 0.326236E+09 0.854304E+09 0.249072E+10 0.257546E+09
December 0.124836E+10 0.400610E+09 0.847753E+09 0.259548E+10 0.412328E+09
           
Annual Sum or Average 0.165820E+11 0.524407E+10 0.113379E+11 0.362270E+11 0.257407E+10
Minimum of Months 0.118054E+10 0.291519E+09 0.847753E+09 0.249072E+10 87423304.87
Maximum of Months 0.164653E+10 0.644769E+09 0.101112E+10 0.363097E+10 0.412328E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52660145.69 17747905.58 34912240.10 0.110110E+09 14382040.48
February 53937353.26 19776011.67 34161341.59 0.115468E+09 10178335.09
March 65102162.17 25493581.81 39608580.36 0.143085E+09 7660914.99
April 63673235.12 24325746.10 39347489.02 0.143565E+09 3456638.76
May 56557228.11 17119695.80 39437532.32 0.132728E+09 4289773.11
June 58295072.81 19199225.68 39095847.13 0.134975E+09 4627734.13
July 51451763.28 11526410.80 39925352.48 0.112074E+09 8410242.99
August 56623620.63 16644873.82 39978746.81 0.121306E+09 6918578.92
September 51461181.99 14023326.63 37437855.36 0.113331E+09 6732076.95
October 49838260.44 12750344.95 37087915.50 0.104635E+09 8633702.39
November 46677498.68 12899084.95 33778413.73 98480979.26 10183122.78
December 49359125.00 15839742.50 33519382.50 0.102623E+09 16303072.62
           
Annual Sum or Average 0.655637E+09 0.207346E+09 0.448291E+09 0.143238E+10 0.101776E+09
Minimum of Months 46677498.68 11526410.80 33519382.50 98480979.26 3456638.76
Maximum of Months 65102162.17 25493581.81 39978746.81 0.143565E+09 16303072.62



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.950500E+09 0.396558E+09 0.553943E+09 0.199063E+10 0.212494E+09
February 0.729011E+09 0.237684E+09 0.491328E+09 0.164144E+10 0.147959E+09
March 0.550815E+09 73974117.02 0.476841E+09 0.137616E+10 0.103264E+09
April 0.397414E+09 178399.50 0.397235E+09 0.104401E+10 40011731.22
May 0.410940E+09 0.00 0.410940E+09 0.110587E+10 51845392.44
June 0.396253E+09 0.00 0.396253E+09 0.105933E+10 54445286.93
July 0.421806E+09 0.00 0.421806E+09 0.982797E+09 0.105875E+09
August 0.410632E+09 634632.62 0.409997E+09 0.958599E+09 82918549.85
September 0.439934E+09 14368407.66 0.425565E+09 0.105131E+10 85067812.84
October 0.594745E+09 94826739.91 0.499918E+09 0.130765E+10 0.119121E+09
November 0.748416E+09 0.228330E+09 0.520085E+09 0.159563E+10 0.147632E+09
December 0.950014E+09 0.404190E+09 0.545824E+09 0.196163E+10 0.239038E+09
           
Annual Sum or Average 0.700048E+10 0.145074E+10 0.554974E+10 0.160751E+11 0.138967E+10
Minimum of Months 0.396253E+09 0.00 0.396253E+09 0.958599E+09 40011731.22
Maximum of Months 0.950500E+09 0.404190E+09 0.553943E+09 0.199063E+10 0.239038E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.950500E+09 0.396558E+09 0.553943E+09 0.199063E+10 0.212494E+09
February 0.729011E+09 0.237684E+09 0.491328E+09 0.164144E+10 0.147959E+09
March 0.550815E+09 73974117.02 0.476841E+09 0.137616E+10 0.103264E+09
April 0.397414E+09 178399.50 0.397235E+09 0.104401E+10 40011731.22
May 0.410940E+09 0.00 0.410940E+09 0.110587E+10 51845392.44
June 0.396253E+09 0.00 0.396253E+09 0.105933E+10 54445286.93
July 0.421806E+09 0.00 0.421806E+09 0.982797E+09 0.105875E+09
August 0.410632E+09 634632.62 0.409997E+09 0.958599E+09 82918549.85
September 0.439934E+09 14368407.66 0.425565E+09 0.105131E+10 85067812.84
October 0.594745E+09 94826739.91 0.499918E+09 0.130765E+10 0.119121E+09
November 0.748416E+09 0.228330E+09 0.520085E+09 0.159563E+10 0.147632E+09
December 0.950014E+09 0.404190E+09 0.545824E+09 0.196163E+10 0.239038E+09
           
Annual Sum or Average 0.700048E+10 0.145074E+10 0.554974E+10 0.160751E+11 0.138967E+10
Minimum of Months 0.396253E+09 0.00 0.396253E+09 0.958599E+09 40011731.22
Maximum of Months 0.950500E+09 0.404190E+09 0.553943E+09 0.199063E+10 0.239038E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.950440E+09 0.396533E+09 0.553908E+09 0.199050E+10 0.212480E+09
February 0.728965E+09 0.237669E+09 0.491297E+09 0.164134E+10 0.147950E+09
March 0.550780E+09 73969442.28 0.476811E+09 0.137607E+10 0.103258E+09
April 0.397389E+09 178388.23 0.397210E+09 0.104394E+10 40009202.70
May 0.410914E+09 0.00 0.410914E+09 0.110580E+10 51842116.11
June 0.396228E+09 0.00 0.396228E+09 0.105926E+10 54441846.30
July 0.421779E+09 0.00 0.421779E+09 0.982735E+09 0.105868E+09
August 0.410606E+09 634592.51 0.409971E+09 0.958539E+09 82913309.87
September 0.439906E+09 14367499.66 0.425538E+09 0.105124E+10 85062437.04
October 0.594708E+09 94820747.40 0.499887E+09 0.130757E+10 0.119113E+09
November 0.748368E+09 0.228316E+09 0.520052E+09 0.159553E+10 0.147623E+09
December 0.949954E+09 0.404165E+09 0.545789E+09 0.196150E+10 0.239023E+09
           
Annual Sum or Average 0.700004E+10 0.145065E+10 0.554939E+10 0.160740E+11 0.138958E+10
Minimum of Months 0.396228E+09 0.00 0.396228E+09 0.958539E+09 40009202.70
Maximum of Months 0.950440E+09 0.404165E+09 0.553908E+09 0.199050E+10 0.239023E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134945E+10 0.474509E+09 0.874943E+09 0.285827E+10 0.403509E+09
February 0.133866E+10 0.473718E+09 0.864941E+09 0.290190E+10 0.289102E+09
March 0.166131E+10 0.656182E+09 0.100513E+10 0.366913E+10 0.232383E+09
April 0.161567E+10 0.618822E+09 0.996846E+09 0.361841E+10 0.106610E+09
May 0.142058E+10 0.420851E+09 0.999730E+09 0.331503E+10 0.112731E+09
June 0.148972E+10 0.513469E+09 0.976250E+09 0.342063E+10 0.123045E+09
July 0.131240E+10 0.309492E+09 0.100291E+10 0.285430E+10 0.222952E+09
August 0.142684E+10 0.422547E+09 0.100429E+10 0.304016E+10 0.182598E+09
September 0.129333E+10 0.358712E+09 0.934621E+09 0.283707E+10 0.179060E+09
October 0.125518E+10 0.323558E+09 0.931626E+09 0.263265E+10 0.230637E+09
November 0.118457E+10 0.323068E+09 0.861504E+09 0.250660E+10 0.271305E+09
December 0.125273E+10 0.409788E+09 0.842939E+09 0.264715E+10 0.448010E+09
           
Annual Sum or Average 0.166004E+11 0.530472E+10 0.112957E+11 0.363013E+11 0.280194E+10
Minimum of Months 0.118457E+10 0.309492E+09 0.842939E+09 0.250660E+10 0.106610E+09
Maximum of Months 0.166131E+10 0.656182E+09 0.100513E+10 0.366913E+10 0.448010E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53355979.96 18761608.46 34594371.51 0.113013E+09 15954364.37
February 52929233.04 18730341.46 34198891.58 0.114738E+09 11430819.79
March 65686454.75 25944774.78 39741679.96 0.145074E+09 9188207.37
April 63881894.26 24467603.31 39414290.95 0.143068E+09 4215254.67
May 56168334.98 16640018.50 39528316.48 0.131073E+09 4457254.48
June 58902015.65 20302051.45 38599964.20 0.135248E+09 4865089.77
July 51890886.15 12237012.32 39653873.84 0.112856E+09 8815285.82
August 56415770.54 16707089.12 39708681.43 0.120205E+09 7219740.53
September 51137097.82 14183118.72 36953979.10 0.112175E+09 7079853.71
October 49628696.88 12793148.88 36835548.01 0.104092E+09 9119178.76
November 46836773.01 12773757.78 34063015.23 99108405.05 10727132.24
December 49531592.49 16202610.85 33328981.64 0.104666E+09 17713889.15
           
Annual Sum or Average 0.656365E+09 0.209743E+09 0.446622E+09 0.143532E+10 0.110786E+09
Minimum of Months 46836773.01 12237012.32 33328981.64 99108405.05 4215254.67
Maximum of Months 65686454.75 25944774.78 39741679.96 0.145074E+09 17713889.15



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.107702E+10 0.00 0.107702E+10 0.245939E+10 0.566538E+09
February 0.103770E+10 0.00 0.103770E+10 0.249091E+10 0.393170E+09
March 0.117910E+10 0.00 0.117910E+10 0.300591E+10 0.285260E+09
April 0.124178E+10 17598406.75 0.122419E+10 0.326755E+10 0.119643E+09
May 0.164488E+10 0.175229E+09 0.146965E+10 0.429432E+10 0.151530E+09
June 0.194446E+10 0.392960E+09 0.155150E+10 0.493055E+10 0.166267E+09
July 0.172779E+10 0.181103E+09 0.154669E+10 0.400481E+10 0.305547E+09
August 0.142253E+10 60657918.87 0.136188E+10 0.334839E+10 0.232976E+09
September 0.117206E+10 561246.81 0.117150E+10 0.285496E+10 0.223487E+09
October 0.116697E+10 0.00 0.116697E+10 0.262620E+10 0.308403E+09
November 0.106859E+10 0.00 0.106859E+10 0.242654E+10 0.370015E+09
December 0.104631E+10 0.00 0.104631E+10 0.236581E+10 0.623548E+09
           
Annual Sum or Average 0.157292E+11 0.828110E+09 0.149011E+11 0.380753E+11 0.374638E+10
Minimum of Months 0.103770E+10 0.00 0.103770E+10 0.236581E+10 0.119643E+09
Maximum of Months 0.194446E+10 0.392960E+09 0.155150E+10 0.493055E+10 0.623548E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.138453E+10 0.466627E+09 0.917904E+09 0.290249E+10 0.357342E+09
February 0.141811E+10 0.519950E+09 0.898162E+09 0.304431E+10 0.245090E+09
March 0.171165E+10 0.670276E+09 0.104138E+10 0.376947E+10 0.174965E+09
April 0.167408E+10 0.639571E+09 0.103451E+10 0.379045E+10 74938992.22
May 0.148699E+10 0.450110E+09 0.103688E+10 0.350969E+10 97122452.97
June 0.153268E+10 0.504785E+09 0.102790E+10 0.356745E+10 0.103900E+09
July 0.135276E+10 0.303052E+09 0.104971E+10 0.296282E+10 0.195400E+09
August 0.148874E+10 0.437626E+09 0.105111E+10 0.320695E+10 0.152024E+09
September 0.135301E+10 0.368700E+09 0.984308E+09 0.299690E+10 0.149130E+09
October 0.131034E+10 0.335231E+09 0.975107E+09 0.275955E+10 0.204896E+09
November 0.122724E+10 0.339142E+09 0.888095E+09 0.259703E+10 0.243817E+09
December 0.129774E+10 0.416457E+09 0.881284E+09 0.270694E+10 0.399043E+09
           
Annual Sum or Average 0.172379E+11 0.545153E+10 0.117864E+11 0.378140E+11 0.239767E+10
Minimum of Months 0.122724E+10 0.303052E+09 0.881284E+09 0.259703E+10 74938992.22
Maximum of Months 0.171165E+10 0.670276E+09 0.105111E+10 0.379045E+10 0.399043E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.285155E+10 0.118970E+10 0.166185E+10 0.602308E+10 0.575911E+09
February 0.218706E+10 0.713065E+09 0.147400E+10 0.498375E+10 0.390251E+09
March 0.165246E+10 0.221927E+09 0.143054E+10 0.418312E+10 0.273115E+09
April 0.119225E+10 535209.43 0.119171E+10 0.318077E+10 0.107799E+09
May 0.123283E+10 0.00 0.123283E+10 0.337086E+10 0.139964E+09
June 0.118877E+10 0.00 0.118877E+10 0.323978E+10 0.147331E+09
July 0.126543E+10 0.00 0.126543E+10 0.298401E+10 0.289435E+09
August 0.123191E+10 1903936.76 0.123000E+10 0.292188E+10 0.216542E+09
September 0.131981E+10 43106103.77 0.127671E+10 0.319433E+10 0.224341E+09
October 0.178426E+10 0.284486E+09 0.149977E+10 0.395115E+10 0.325016E+09
November 0.224528E+10 0.685005E+09 0.156028E+10 0.482986E+10 0.393263E+09
December 0.285009E+10 0.121260E+10 0.163749E+10 0.592747E+10 0.645106E+09
           
Annual Sum or Average 0.210017E+11 0.435232E+10 0.166494E+11 0.487901E+11 0.372807E+10
Minimum of Months 0.118877E+10 0.00 0.118877E+10 0.292188E+10 0.107799E+09
Maximum of Months 0.285155E+10 0.121260E+10 0.166185E+10 0.602308E+10 0.645106E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.140283E+10 0.493279E+09 0.909547E+09 0.297935E+10 0.398695E+09
February 0.139161E+10 0.492457E+09 0.899149E+09 0.302506E+10 0.276650E+09
March 0.172702E+10 0.682138E+09 0.104488E+10 0.382232E+10 0.214795E+09
April 0.167957E+10 0.643301E+09 0.103627E+10 0.377562E+10 92713208.88
May 0.147677E+10 0.437498E+09 0.103927E+10 0.346551E+10 99431197.31
June 0.154864E+10 0.533780E+09 0.101486E+10 0.357538E+10 0.108414E+09
July 0.136431E+10 0.321735E+09 0.104257E+10 0.298336E+10 0.203703E+09
August 0.148327E+10 0.439262E+09 0.104401E+10 0.317836E+10 0.157913E+09
September 0.134449E+10 0.372902E+09 0.971586E+09 0.296637E+10 0.157857E+09
October 0.130483E+10 0.336357E+09 0.968472E+09 0.274729E+10 0.216851E+09
November 0.123142E+10 0.335847E+09 0.895577E+09 0.261591E+10 0.258317E+09
December 0.130228E+10 0.425998E+09 0.876278E+09 0.276259E+10 0.434416E+09
           
Annual Sum or Average 0.172570E+11 0.551455E+10 0.117425E+11 0.378971E+11 0.261975E+10
Minimum of Months 0.123142E+10 0.321735E+09 0.876278E+09 0.261591E+10 92713208.88
Maximum of Months 0.172702E+10 0.682138E+09 0.104488E+10 0.382232E+10 0.434416E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 912.59 202.95 402.11 0.00 402.11 0.00 0.00
February 1021.84 155.29 428.94 0.00 428.94 0.00 0.00
March 1112.09 103.45 440.23 0.00 440.23 0.00 0.00
April 1247.26 45.65 479.08 6.79 472.29 0.00 0.00
May 1590.45 55.83 614.13 65.42 548.70 0.00 0.00
June 1888.81 64.06 750.18 151.61 598.57 0.00 0.00
July 1483.46 112.67 645.08 67.62 577.47 0.00 0.00
August 1242.05 84.24 531.11 22.65 508.47 0.00 0.00
September 1091.23 84.92 452.18 0.22 451.97 0.00 0.00
October 972.62 111.92 435.70 0.00 435.70 0.00 0.00
November 929.62 135.66 412.27 0.00 412.27 0.00 0.00
December 879.36 221.28 390.65 0.00 390.65 0.00 0.00
               
Annual Sum or Average 1198.06 114.85 498.77 26.26 472.51 0.00 0.00
Minimum of Months 879.36 45.65 390.65 0.00 390.65 0.00 0.00
Maximum of Months 1888.81 221.28 750.18 151.61 598.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1079.00 128.42 516.92 174.22 342.71 0.00 0.00
February 1252.02 96.73 586.19 214.93 371.26 0.00 0.00
March 1398.98 62.97 639.06 250.25 388.81 0.00 0.00
April 1452.57 28.34 645.87 246.75 399.12 0.00 0.00
May 1301.57 35.71 555.18 168.05 387.13 0.00 0.00
June 1367.24 40.01 591.31 194.75 396.57 0.00 0.00
July 1098.46 72.01 505.06 113.15 391.92 0.00 0.00
August 1191.47 55.00 555.83 163.39 392.44 0.00 0.00
September 1148.89 56.75 521.99 142.25 379.75 0.00 0.00
October 1024.29 74.49 489.22 125.16 364.06 0.00 0.00
November 996.82 89.73 473.47 130.84 342.63 0.00 0.00
December 1007.12 142.30 484.52 155.49 329.03 0.00 0.00
               
Annual Sum or Average 1192.19 73.57 546.61 172.87 373.74 0.00 0.00
Minimum of Months 996.82 28.34 473.47 113.15 329.03 0.00 0.00
Maximum of Months 1452.57 142.30 645.87 250.25 399.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2243.41 207.53 1064.65 444.18 620.46 0.00 0.00
February 2052.00 154.38 904.04 294.75 609.29 0.00 0.00
March 1550.91 98.38 616.96 82.86 534.10 0.00 0.00
April 1214.28 40.74 459.97 0.21 459.77 0.00 0.00
May 1246.28 51.09 460.29 0.00 460.29 0.00 0.00
June 1237.60 56.44 458.63 0.00 458.63 0.00 0.00
July 1103.05 106.36 472.46 0.00 472.46 0.00 0.00
August 1083.21 77.63 459.94 0.71 459.23 0.00 0.00
September 1221.78 85.15 509.19 16.63 492.56 0.00 0.00
October 1466.33 118.30 666.17 106.21 559.95 0.00 0.00
November 1855.88 145.36 866.24 264.28 601.96 0.00 0.00
December 2209.22 231.08 1064.10 452.73 611.37 0.00 0.00
               
Annual Sum or Average 1537.85 114.40 665.96 138.01 527.95 0.00 0.00
Minimum of Months 1083.21 40.74 458.63 0.00 458.63 0.00 0.00
Maximum of Months 2243.41 231.08 1064.65 452.73 620.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1109.55 142.31 523.76 184.17 339.59 0.00 0.00
February 1245.67 108.65 575.23 203.56 371.67 0.00 0.00
March 1420.64 77.53 644.79 254.68 390.11 0.00 0.00
April 1449.00 34.92 647.98 248.19 399.80 0.00 0.00
May 1286.91 35.99 551.36 163.34 388.02 0.00 0.00
June 1371.56 40.95 597.47 205.93 391.54 0.00 0.00
July 1107.37 74.10 509.37 120.12 389.25 0.00 0.00
August 1182.05 56.17 553.79 164.00 389.79 0.00 0.00
September 1138.54 59.40 518.71 143.87 374.84 0.00 0.00
October 1021.58 77.95 487.17 125.58 361.59 0.00 0.00
November 1006.04 94.08 475.09 129.57 345.52 0.00 0.00
December 1029.85 153.58 486.21 159.05 327.16 0.00 0.00
               
Annual Sum or Average 1196.52 79.64 547.22 174.87 372.35 0.00 0.00
Minimum of Months 1006.04 34.92 475.09 120.12 327.16 0.00 0.00
Maximum of Months 1449.00 153.58 647.98 254.68 399.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 915.19 213.89 402.10 0.00 402.10 0.00 0.00
February 1026.26 166.20 428.93 0.00 428.93 0.00 0.00
March 1118.52 109.61 440.22 0.00 440.22 0.00 0.00
April 1255.40 48.32 479.07 6.79 472.28 0.00 0.00
May 1596.62 62.61 614.11 65.42 548.69 0.00 0.00
June 1893.53 72.66 750.16 151.60 598.56 0.00 0.00
July 1488.53 125.59 645.07 67.61 577.45 0.00 0.00
August 1241.17 97.87 531.10 22.65 508.45 0.00 0.00
September 1093.22 95.00 452.17 0.22 451.96 0.00 0.00
October 976.97 119.60 435.69 0.00 435.69 0.00 0.00
November 932.67 148.49 412.26 0.00 412.26 0.00 0.00
December 878.79 240.50 390.64 0.00 390.64 0.00 0.00
               
Annual Sum or Average 1201.83 125.06 498.76 26.26 472.50 0.00 0.00
Minimum of Months 878.79 48.32 390.64 0.00 390.64 0.00 0.00
Maximum of Months 1893.53 240.50 750.16 151.60 598.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1080.85 141.18 516.92 174.22 342.70 0.00 0.00
February 1254.89 110.62 586.18 214.92 371.26 0.00 0.00
March 1404.54 75.20 639.05 250.25 388.80 0.00 0.00
April 1456.22 35.06 645.86 246.74 399.11 0.00 0.00
May 1302.87 42.11 555.17 168.05 387.12 0.00 0.00
June 1369.09 46.94 591.30 194.74 396.56 0.00 0.00
July 1100.13 82.56 505.06 113.14 391.91 0.00 0.00
August 1190.75 67.91 555.82 163.39 392.44 0.00 0.00
September 1149.55 68.29 521.99 142.24 379.74 0.00 0.00
October 1027.10 84.75 489.22 125.16 364.06 0.00 0.00
November 998.92 103.29 473.46 130.84 342.62 0.00 0.00
December 1007.36 160.03 484.51 155.48 329.03 0.00 0.00
               
Annual Sum or Average 1194.17 84.85 546.60 172.86 373.74 0.00 0.00
Minimum of Months 998.92 35.06 473.46 113.14 329.03 0.00 0.00
Maximum of Months 1456.22 160.03 645.86 250.25 399.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2229.60 238.00 1064.61 444.16 620.44 0.00 0.00
February 2035.48 183.48 904.01 294.74 609.27 0.00 0.00
March 1541.36 115.66 616.94 82.85 534.09 0.00 0.00
April 1208.31 46.31 459.96 0.21 459.75 0.00 0.00
May 1238.63 58.07 460.27 0.00 460.27 0.00 0.00
June 1226.05 63.01 458.62 0.00 458.62 0.00 0.00
July 1100.78 118.58 472.44 0.00 472.44 0.00 0.00
August 1073.68 92.87 459.93 0.71 459.22 0.00 0.00
September 1216.77 98.46 509.17 16.63 492.54 0.00 0.00
October 1464.63 133.42 666.14 106.21 559.93 0.00 0.00
November 1846.76 170.87 866.20 264.27 601.94 0.00 0.00
December 2197.12 267.73 1064.06 452.71 611.35 0.00 0.00
               
Annual Sum or Average 1529.18 132.20 665.94 138.01 527.93 0.00 0.00
Minimum of Months 1073.68 46.31 458.62 0.00 458.62 0.00 0.00
Maximum of Months 2229.60 267.73 1064.61 452.71 620.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1109.35 156.61 523.75 184.17 339.58 0.00 0.00
February 1246.96 124.23 575.23 203.56 371.67 0.00 0.00
March 1424.06 90.19 644.79 254.68 390.11 0.00 0.00
April 1451.19 42.76 647.97 248.18 399.79 0.00 0.00
May 1286.63 43.75 551.35 163.34 388.01 0.00 0.00
June 1371.87 49.35 597.46 205.93 391.53 0.00 0.00
July 1107.81 86.53 509.37 120.12 389.25 0.00 0.00
August 1179.95 70.87 553.78 164.00 389.78 0.00 0.00
September 1137.82 71.81 518.70 143.86 374.84 0.00 0.00
October 1021.78 89.51 487.16 125.58 361.58 0.00 0.00
November 1005.29 108.81 475.08 129.57 345.51 0.00 0.00
December 1027.41 173.88 486.21 159.05 327.16 0.00 0.00
               
Annual Sum or Average 1196.62 92.36 547.21 174.86 372.35 0.00 0.00
Minimum of Months 1005.29 42.76 475.08 120.12 327.16 0.00 0.00
Maximum of Months 1451.19 173.88 647.97 254.68 399.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 918.23 211.52 402.11 0.00 402.11 0.00 0.00
February 1029.64 162.52 428.94 0.00 428.94 0.00 0.00
March 1122.28 106.50 440.23 0.00 440.23 0.00 0.00
April 1260.63 46.16 479.08 6.79 472.29 0.00 0.00
May 1603.31 56.57 614.13 65.42 548.70 0.00 0.00
June 1902.22 64.15 750.18 151.61 598.57 0.00 0.00
July 1495.22 114.08 645.08 67.62 577.47 0.00 0.00
August 1250.14 86.98 531.11 22.65 508.47 0.00 0.00
September 1101.45 86.22 452.18 0.22 451.97 0.00 0.00
October 980.51 115.14 435.70 0.00 435.70 0.00 0.00
November 936.16 142.75 412.27 0.00 412.27 0.00 0.00
December 883.29 232.81 390.65 0.00 390.65 0.00 0.00
               
Annual Sum or Average 1207.36 118.80 498.77 26.26 472.51 0.00 0.00
Minimum of Months 883.29 46.16 390.65 0.00 390.65 0.00 0.00
Maximum of Months 1902.22 232.81 750.18 151.61 598.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1083.66 133.42 516.92 174.22 342.71 0.00 0.00
February 1258.40 101.31 586.19 214.93 371.26 0.00 0.00
March 1407.36 65.32 639.06 250.25 388.81 0.00 0.00
April 1462.36 28.91 645.87 246.75 399.12 0.00 0.00
May 1310.37 36.26 555.18 168.05 387.13 0.00 0.00
June 1376.33 40.08 591.31 194.75 396.57 0.00 0.00
July 1106.19 72.95 505.06 113.15 391.92 0.00 0.00
August 1197.34 56.76 555.83 163.39 392.44 0.00 0.00
September 1156.21 57.53 521.99 142.25 379.75 0.00 0.00
October 1030.30 76.50 489.22 125.16 364.06 0.00 0.00
November 1001.94 94.07 473.47 130.84 342.63 0.00 0.00
December 1010.65 148.99 484.52 155.49 329.03 0.00 0.00
               
Annual Sum or Average 1199.08 76.03 546.61 172.87 373.74 0.00 0.00
Minimum of Months 1001.94 28.91 473.47 113.15 329.03 0.00 0.00
Maximum of Months 1462.36 148.99 645.87 250.25 399.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2248.76 215.02 1064.65 444.18 620.46 0.00 0.00
February 2060.08 161.31 904.04 294.75 609.29 0.00 0.00
March 1561.80 101.97 616.96 82.86 534.10 0.00 0.00
April 1227.15 41.59 459.97 0.21 459.77 0.00 0.00
May 1258.54 52.26 460.29 0.00 460.29 0.00 0.00
June 1249.91 56.84 458.63 0.00 458.63 0.00 0.00
July 1114.10 108.06 472.46 0.00 472.46 0.00 0.00
August 1090.90 80.85 459.94 0.71 459.23 0.00 0.00
September 1232.38 86.55 509.19 16.63 492.56 0.00 0.00
October 1475.19 121.35 666.17 106.21 559.95 0.00 0.00
November 1863.37 151.72 866.24 264.28 601.96 0.00 0.00
December 2213.06 240.85 1064.10 452.73 611.37 0.00 0.00
               
Annual Sum or Average 1547.12 118.22 665.96 138.01 527.95 0.00 0.00
Minimum of Months 1090.90 41.59 458.63 0.00 458.63 0.00 0.00
Maximum of Months 2248.76 240.85 1064.65 452.73 620.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1112.36 148.86 523.76 184.17 339.59 0.00 0.00
February 1250.44 114.36 575.23 203.56 371.67 0.00 0.00
March 1427.09 80.20 644.79 254.68 390.11 0.00 0.00
April 1456.64 35.77 647.98 248.19 399.80 0.00 0.00
May 1293.87 37.12 551.36 163.34 388.02 0.00 0.00
June 1379.39 41.83 597.47 205.93 391.54 0.00 0.00
July 1113.86 76.05 509.37 120.12 389.25 0.00 0.00
August 1186.66 58.96 553.79 164.00 389.79 0.00 0.00
September 1144.43 60.90 518.71 143.87 374.84 0.00 0.00
October 1025.72 80.96 487.17 125.58 361.59 0.00 0.00
November 1009.23 99.66 475.09 129.57 345.52 0.00 0.00
December 1031.43 162.19 486.21 159.05 327.16 0.00 0.00
               
Annual Sum or Average 1201.71 83.07 547.22 174.87 372.35 0.00 0.00
Minimum of Months 1009.23 35.77 475.09 120.12 327.16 0.00 0.00
Maximum of Months 1456.64 162.19 647.98 254.68 399.80 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.244427E+10 0.543577E+09 0.107702E+10 0.00 0.107702E+10 0.00 0.00
February 0.247204E+10 0.375681E+09 0.103770E+10 0.00 0.103770E+10 0.00 0.00
March 0.297862E+10 0.277075E+09 0.117910E+10 0.00 0.117910E+10 0.00 0.00
April 0.323290E+10 0.118334E+09 0.124178E+10 17598406.75 0.122419E+10 0.00 0.00
May 0.425987E+10 0.149529E+09 0.164488E+10 0.175229E+09 0.146965E+10 0.00 0.00
June 0.489581E+10 0.166044E+09 0.194446E+10 0.392960E+09 0.155150E+10 0.00 0.00
July 0.397329E+10 0.301778E+09 0.172779E+10 0.181103E+09 0.154669E+10 0.00 0.00
August 0.332672E+10 0.225628E+09 0.142253E+10 60657918.87 0.136188E+10 0.00 0.00
September 0.282847E+10 0.220112E+09 0.117206E+10 561246.81 0.117150E+10 0.00 0.00
October 0.260507E+10 0.299772E+09 0.116697E+10 0.00 0.116697E+10 0.00 0.00
November 0.240958E+10 0.351630E+09 0.106859E+10 0.00 0.106859E+10 0.00 0.00
December 0.235528E+10 0.592668E+09 0.104631E+10 0.00 0.104631E+10 0.00 0.00
               
Annual Sum or Average 0.377819E+11 0.362183E+10 0.157292E+11 0.828110E+09 0.149011E+11 0.00 0.00
Minimum of Months 0.235528E+10 0.118334E+09 0.103770E+10 0.00 0.103770E+10 0.00 0.00
Maximum of Months 0.489581E+10 0.592668E+09 0.194446E+10 0.392960E+09 0.155150E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.288999E+10 0.343958E+09 0.138453E+10 0.466627E+09 0.917904E+09 0.00 0.00
February 0.302889E+10 0.234021E+09 0.141811E+10 0.519950E+09 0.898162E+09 0.00 0.00
March 0.374704E+10 0.168666E+09 0.171165E+10 0.670276E+09 0.104138E+10 0.00 0.00
April 0.376507E+10 73460764.27 0.167408E+10 0.639571E+09 0.103451E+10 0.00 0.00
May 0.348614E+10 95638448.67 0.148699E+10 0.450110E+09 0.103688E+10 0.00 0.00
June 0.354388E+10 0.103718E+09 0.153268E+10 0.504785E+09 0.102790E+10 0.00 0.00
July 0.294211E+10 0.192883E+09 0.135276E+10 0.303052E+09 0.104971E+10 0.00 0.00
August 0.319123E+10 0.147304E+09 0.148874E+10 0.437626E+09 0.105111E+10 0.00 0.00
September 0.297793E+10 0.147092E+09 0.135301E+10 0.368700E+09 0.984308E+09 0.00 0.00
October 0.274346E+10 0.199514E+09 0.131034E+10 0.335231E+09 0.975107E+09 0.00 0.00
November 0.258376E+10 0.232571E+09 0.122724E+10 0.339142E+09 0.888095E+09 0.00 0.00
December 0.269748E+10 0.381128E+09 0.129774E+10 0.416457E+09 0.881284E+09 0.00 0.00
               
Annual Sum or Average 0.375970E+11 0.231996E+10 0.172379E+11 0.545153E+10 0.117864E+11 0.00 0.00
Minimum of Months 0.258376E+10 73460764.27 0.122724E+10 0.303052E+09 0.881284E+09 0.00 0.00
Maximum of Months 0.376507E+10 0.381128E+09 0.171165E+10 0.670276E+09 0.105111E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.600875E+10 0.555843E+09 0.285155E+10 0.118970E+10 0.166185E+10 0.00 0.00
February 0.496419E+10 0.373488E+09 0.218706E+10 0.713065E+09 0.147400E+10 0.00 0.00
March 0.415396E+10 0.263511E+09 0.165246E+10 0.221927E+09 0.143054E+10 0.00 0.00
April 0.314742E+10 0.105593E+09 0.119225E+10 535209.43 0.119171E+10 0.00 0.00
May 0.333804E+10 0.136850E+09 0.123283E+10 0.00 0.123283E+10 0.00 0.00
June 0.320786E+10 0.146292E+09 0.118877E+10 0.00 0.118877E+10 0.00 0.00
July 0.295440E+10 0.284864E+09 0.126543E+10 0.00 0.126543E+10 0.00 0.00
August 0.290127E+10 0.207928E+09 0.123191E+10 1903936.76 0.123000E+10 0.00 0.00
September 0.316685E+10 0.220703E+09 0.131981E+10 43106103.77 0.127671E+10 0.00 0.00
October 0.392741E+10 0.316854E+09 0.178426E+10 0.284486E+09 0.149977E+10 0.00 0.00
November 0.481045E+10 0.376761E+09 0.224528E+10 0.685005E+09 0.156028E+10 0.00 0.00
December 0.591717E+10 0.618920E+09 0.285009E+10 0.121260E+10 0.163749E+10 0.00 0.00
               
Annual Sum or Average 0.484978E+11 0.360761E+10 0.210017E+11 0.435232E+10 0.166494E+11 0.00 0.00
Minimum of Months 0.290127E+10 0.105593E+09 0.118877E+10 0.00 0.118877E+10 0.00 0.00
Maximum of Months 0.600875E+10 0.618920E+09 0.285155E+10 0.121260E+10 0.166185E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.297181E+10 0.381156E+09 0.140283E+10 0.493279E+09 0.909547E+09 0.00 0.00
February 0.301353E+10 0.262844E+09 0.139161E+10 0.492457E+09 0.899149E+09 0.00 0.00
March 0.380504E+10 0.207669E+09 0.172702E+10 0.682138E+09 0.104488E+10 0.00 0.00
April 0.375582E+10 90514423.28 0.167957E+10 0.643301E+09 0.103627E+10 0.00 0.00
May 0.344687E+10 96385195.44 0.147677E+10 0.437498E+09 0.103927E+10 0.00 0.00
June 0.355507E+10 0.106154E+09 0.154864E+10 0.533780E+09 0.101486E+10 0.00 0.00
July 0.296599E+10 0.198459E+09 0.136431E+10 0.321735E+09 0.104257E+10 0.00 0.00
August 0.316600E+10 0.150451E+09 0.148327E+10 0.439262E+09 0.104401E+10 0.00 0.00
September 0.295109E+10 0.153974E+09 0.134449E+10 0.372902E+09 0.971586E+09 0.00 0.00
October 0.273619E+10 0.208793E+09 0.130483E+10 0.336357E+09 0.968472E+09 0.00 0.00
November 0.260766E+10 0.243862E+09 0.123142E+10 0.335847E+09 0.895577E+09 0.00 0.00
December 0.275834E+10 0.411358E+09 0.130228E+10 0.425998E+09 0.876278E+09 0.00 0.00
               
Annual Sum or Average 0.377334E+11 0.251162E+10 0.172570E+11 0.551455E+10 0.117425E+11 0.00 0.00
Minimum of Months 0.260766E+10 90514423.28 0.123142E+10 0.321735E+09 0.876278E+09 0.00 0.00
Maximum of Months 0.380504E+10 0.411358E+09 0.172702E+10 0.682138E+09 0.104488E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.245124E+10 0.572871E+09 0.107699E+10 0.00 0.107699E+10 0.00 0.00
February 0.248273E+10 0.402081E+09 0.103768E+10 0.00 0.103768E+10 0.00 0.00
March 0.299585E+10 0.293576E+09 0.117908E+10 0.00 0.117908E+10 0.00 0.00
April 0.325400E+10 0.125239E+09 0.124176E+10 17597889.49 0.122416E+10 0.00 0.00
May 0.427640E+10 0.167688E+09 0.164484E+10 0.175224E+09 0.146962E+10 0.00 0.00
June 0.490804E+10 0.188336E+09 0.194442E+10 0.392949E+09 0.155147E+10 0.00 0.00
July 0.398688E+10 0.336391E+09 0.172775E+10 0.181098E+09 0.154665E+10 0.00 0.00
August 0.332434E+10 0.262131E+09 0.142250E+10 60656135.97 0.136185E+10 0.00 0.00
September 0.283364E+10 0.246245E+09 0.117204E+10 561230.32 0.117148E+10 0.00 0.00
October 0.261672E+10 0.320340E+09 0.116695E+10 0.00 0.116695E+10 0.00 0.00
November 0.241747E+10 0.384879E+09 0.106857E+10 0.00 0.106857E+10 0.00 0.00
December 0.235374E+10 0.644155E+09 0.104628E+10 0.00 0.104628E+10 0.00 0.00
               
Annual Sum or Average 0.379011E+11 0.394393E+10 0.157289E+11 0.828086E+09 0.149008E+11 0.00 0.00
Minimum of Months 0.235374E+10 0.125239E+09 0.103768E+10 0.00 0.103768E+10 0.00 0.00
Maximum of Months 0.490804E+10 0.644155E+09 0.194442E+10 0.392949E+09 0.155147E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.289496E+10 0.378124E+09 0.138451E+10 0.466618E+09 0.917892E+09 0.00 0.00
February 0.303582E+10 0.267603E+09 0.141809E+10 0.519939E+09 0.898150E+09 0.00 0.00
March 0.376192E+10 0.201416E+09 0.171163E+10 0.670262E+09 0.104137E+10 0.00 0.00
April 0.377453E+10 90879943.63 0.167406E+10 0.639558E+09 0.103450E+10 0.00 0.00
May 0.348960E+10 0.112784E+09 0.148697E+10 0.450101E+09 0.103687E+10 0.00 0.00
June 0.354868E+10 0.121670E+09 0.153266E+10 0.504775E+09 0.102789E+10 0.00 0.00
July 0.294658E+10 0.221117E+09 0.135274E+10 0.303046E+09 0.104969E+10 0.00 0.00
August 0.318931E+10 0.181899E+09 0.148872E+10 0.437617E+09 0.105110E+10 0.00 0.00
September 0.297964E+10 0.176996E+09 0.135299E+10 0.368693E+09 0.984294E+09 0.00 0.00
October 0.275100E+10 0.226992E+09 0.131032E+10 0.335225E+09 0.975094E+09 0.00 0.00
November 0.258920E+10 0.267729E+09 0.122722E+10 0.339135E+09 0.888082E+09 0.00 0.00
December 0.269810E+10 0.428631E+09 0.129772E+10 0.416449E+09 0.881272E+09 0.00 0.00
               
Annual Sum or Average 0.376593E+11 0.267584E+10 0.172376E+11 0.545142E+10 0.117862E+11 0.00 0.00
Minimum of Months 0.258920E+10 90879943.63 0.122722E+10 0.303046E+09 0.881272E+09 0.00 0.00
Maximum of Months 0.377453E+10 0.428631E+09 0.171163E+10 0.670262E+09 0.105110E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.597176E+10 0.637468E+09 0.285144E+10 0.118965E+10 0.166179E+10 0.00 0.00
February 0.492423E+10 0.443869E+09 0.218699E+10 0.713036E+09 0.147395E+10 0.00 0.00
March 0.412839E+10 0.309786E+09 0.165241E+10 0.221918E+09 0.143049E+10 0.00 0.00
April 0.313195E+10 0.120033E+09 0.119222E+10 535187.22 0.119168E+10 0.00 0.00
May 0.331754E+10 0.155533E+09 0.123280E+10 0.00 0.123280E+10 0.00 0.00
June 0.317792E+10 0.163332E+09 0.118873E+10 0.00 0.118873E+10 0.00 0.00
July 0.294833E+10 0.317618E+09 0.126539E+10 0.00 0.126539E+10 0.00 0.00
August 0.287574E+10 0.248750E+09 0.123187E+10 1903857.75 0.122997E+10 0.00 0.00
September 0.315386E+10 0.255198E+09 0.131977E+10 43104314.98 0.127667E+10 0.00 0.00
October 0.392287E+10 0.357354E+09 0.178420E+10 0.284474E+09 0.149972E+10 0.00 0.00
November 0.478680E+10 0.442886E+09 0.224520E+10 0.684977E+09 0.156022E+10 0.00 0.00
December 0.588475E+10 0.717100E+09 0.284998E+10 0.121255E+10 0.163744E+10 0.00 0.00
               
Annual Sum or Average 0.482241E+11 0.416893E+10 0.210010E+11 0.435214E+10 0.166489E+11 0.00 0.00
Minimum of Months 0.287574E+10 0.120033E+09 0.118873E+10 0.00 0.118873E+10 0.00 0.00
Maximum of Months 0.597176E+10 0.717100E+09 0.285144E+10 0.121255E+10 0.166179E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.297128E+10 0.419464E+09 0.140281E+10 0.493271E+09 0.909537E+09 0.00 0.00
February 0.301664E+10 0.300533E+09 0.139159E+10 0.492449E+09 0.899139E+09 0.00 0.00
March 0.381420E+10 0.241572E+09 0.172699E+10 0.682127E+09 0.104487E+10 0.00 0.00
April 0.376148E+10 0.110825E+09 0.167955E+10 0.643290E+09 0.103626E+10 0.00 0.00
May 0.344610E+10 0.117188E+09 0.147675E+10 0.437491E+09 0.103926E+10 0.00 0.00
June 0.355588E+10 0.127910E+09 0.154862E+10 0.533771E+09 0.101485E+10 0.00 0.00
July 0.296716E+10 0.231767E+09 0.136429E+10 0.321729E+09 0.104256E+10 0.00 0.00
August 0.316037E+10 0.189818E+09 0.148325E+10 0.439254E+09 0.104400E+10 0.00 0.00
September 0.294924E+10 0.186140E+09 0.134447E+10 0.372896E+09 0.971575E+09 0.00 0.00
October 0.273674E+10 0.239757E+09 0.130481E+10 0.336351E+09 0.968461E+09 0.00 0.00
November 0.260571E+10 0.282032E+09 0.123141E+10 0.335841E+09 0.895567E+09 0.00 0.00
December 0.275182E+10 0.465724E+09 0.130226E+10 0.425991E+09 0.876268E+09 0.00 0.00
               
Annual Sum or Average 0.377366E+11 0.291273E+10 0.172568E+11 0.551446E+10 0.117423E+11 0.00 0.00
Minimum of Months 0.260571E+10 0.110825E+09 0.123141E+10 0.321729E+09 0.876268E+09 0.00 0.00
Maximum of Months 0.381420E+10 0.465724E+09 0.172699E+10 0.682127E+09 0.104487E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.245939E+10 0.566538E+09 0.107702E+10 0.00 0.107702E+10 0.00 0.00
February 0.249091E+10 0.393170E+09 0.103770E+10 0.00 0.103770E+10 0.00 0.00
March 0.300591E+10 0.285260E+09 0.117910E+10 0.00 0.117910E+10 0.00 0.00
April 0.326755E+10 0.119643E+09 0.124178E+10 17598406.75 0.122419E+10 0.00 0.00
May 0.429432E+10 0.151530E+09 0.164488E+10 0.175229E+09 0.146965E+10 0.00 0.00
June 0.493055E+10 0.166267E+09 0.194446E+10 0.392960E+09 0.155150E+10 0.00 0.00
July 0.400481E+10 0.305547E+09 0.172779E+10 0.181103E+09 0.154669E+10 0.00 0.00
August 0.334839E+10 0.232976E+09 0.142253E+10 60657918.87 0.136188E+10 0.00 0.00
September 0.285496E+10 0.223487E+09 0.117206E+10 561246.81 0.117150E+10 0.00 0.00
October 0.262620E+10 0.308403E+09 0.116697E+10 0.00 0.116697E+10 0.00 0.00
November 0.242654E+10 0.370015E+09 0.106859E+10 0.00 0.106859E+10 0.00 0.00
December 0.236581E+10 0.623548E+09 0.104631E+10 0.00 0.104631E+10 0.00 0.00
               
Annual Sum or Average 0.380753E+11 0.374638E+10 0.157292E+11 0.828110E+09 0.149011E+11 0.00 0.00
Minimum of Months 0.236581E+10 0.119643E+09 0.103770E+10 0.00 0.103770E+10 0.00 0.00
Maximum of Months 0.493055E+10 0.623548E+09 0.194446E+10 0.392960E+09 0.155150E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.290249E+10 0.357342E+09 0.138453E+10 0.466627E+09 0.917904E+09 0.00 0.00
February 0.304431E+10 0.245090E+09 0.141811E+10 0.519950E+09 0.898162E+09 0.00 0.00
March 0.376947E+10 0.174965E+09 0.171165E+10 0.670276E+09 0.104138E+10 0.00 0.00
April 0.379045E+10 74938992.22 0.167408E+10 0.639571E+09 0.103451E+10 0.00 0.00
May 0.350969E+10 97122452.97 0.148699E+10 0.450110E+09 0.103688E+10 0.00 0.00
June 0.356745E+10 0.103900E+09 0.153268E+10 0.504785E+09 0.102790E+10 0.00 0.00
July 0.296282E+10 0.195400E+09 0.135276E+10 0.303052E+09 0.104971E+10 0.00 0.00
August 0.320695E+10 0.152024E+09 0.148874E+10 0.437626E+09 0.105111E+10 0.00 0.00
September 0.299690E+10 0.149130E+09 0.135301E+10 0.368700E+09 0.984308E+09 0.00 0.00
October 0.275955E+10 0.204896E+09 0.131034E+10 0.335231E+09 0.975107E+09 0.00 0.00
November 0.259703E+10 0.243817E+09 0.122724E+10 0.339142E+09 0.888095E+09 0.00 0.00
December 0.270694E+10 0.399043E+09 0.129774E+10 0.416457E+09 0.881284E+09 0.00 0.00
               
Annual Sum or Average 0.378140E+11 0.239767E+10 0.172379E+11 0.545153E+10 0.117864E+11 0.00 0.00
Minimum of Months 0.259703E+10 74938992.22 0.122724E+10 0.303052E+09 0.881284E+09 0.00 0.00
Maximum of Months 0.379045E+10 0.399043E+09 0.171165E+10 0.670276E+09 0.105111E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.602308E+10 0.575911E+09 0.285155E+10 0.118970E+10 0.166185E+10 0.00 0.00
February 0.498375E+10 0.390251E+09 0.218706E+10 0.713065E+09 0.147400E+10 0.00 0.00
March 0.418312E+10 0.273115E+09 0.165246E+10 0.221927E+09 0.143054E+10 0.00 0.00
April 0.318077E+10 0.107799E+09 0.119225E+10 535209.43 0.119171E+10 0.00 0.00
May 0.337086E+10 0.139964E+09 0.123283E+10 0.00 0.123283E+10 0.00 0.00
June 0.323978E+10 0.147331E+09 0.118877E+10 0.00 0.118877E+10 0.00 0.00
July 0.298401E+10 0.289435E+09 0.126543E+10 0.00 0.126543E+10 0.00 0.00
August 0.292188E+10 0.216542E+09 0.123191E+10 1903936.76 0.123000E+10 0.00 0.00
September 0.319433E+10 0.224341E+09 0.131981E+10 43106103.77 0.127671E+10 0.00 0.00
October 0.395115E+10 0.325016E+09 0.178426E+10 0.284486E+09 0.149977E+10 0.00 0.00
November 0.482986E+10 0.393263E+09 0.224528E+10 0.685005E+09 0.156028E+10 0.00 0.00
December 0.592747E+10 0.645106E+09 0.285009E+10 0.121260E+10 0.163749E+10 0.00 0.00
               
Annual Sum or Average 0.487901E+11 0.372807E+10 0.210017E+11 0.435232E+10 0.166494E+11 0.00 0.00
Minimum of Months 0.292188E+10 0.107799E+09 0.118877E+10 0.00 0.118877E+10 0.00 0.00
Maximum of Months 0.602308E+10 0.645106E+09 0.285155E+10 0.121260E+10 0.166185E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.297935E+10 0.398695E+09 0.140283E+10 0.493279E+09 0.909547E+09 0.00 0.00
February 0.302506E+10 0.276650E+09 0.139161E+10 0.492457E+09 0.899149E+09 0.00 0.00
March 0.382232E+10 0.214795E+09 0.172702E+10 0.682138E+09 0.104488E+10 0.00 0.00
April 0.377562E+10 92713208.88 0.167957E+10 0.643301E+09 0.103627E+10 0.00 0.00
May 0.346551E+10 99431197.31 0.147677E+10 0.437498E+09 0.103927E+10 0.00 0.00
June 0.357538E+10 0.108414E+09 0.154864E+10 0.533780E+09 0.101486E+10 0.00 0.00
July 0.298336E+10 0.203703E+09 0.136431E+10 0.321735E+09 0.104257E+10 0.00 0.00
August 0.317836E+10 0.157913E+09 0.148327E+10 0.439262E+09 0.104401E+10 0.00 0.00
September 0.296637E+10 0.157857E+09 0.134449E+10 0.372902E+09 0.971586E+09 0.00 0.00
October 0.274729E+10 0.216851E+09 0.130483E+10 0.336357E+09 0.968472E+09 0.00 0.00
November 0.261591E+10 0.258317E+09 0.123142E+10 0.335847E+09 0.895577E+09 0.00 0.00
December 0.276259E+10 0.434416E+09 0.130228E+10 0.425998E+09 0.876278E+09 0.00 0.00
               
Annual Sum or Average 0.378971E+11 0.261975E+10 0.172570E+11 0.551455E+10 0.117425E+11 0.00 0.00
Minimum of Months 0.261591E+10 92713208.88 0.123142E+10 0.321735E+09 0.876278E+09 0.00 0.00
Maximum of Months 0.382232E+10 0.434416E+09 0.172702E+10 0.682138E+09 0.104488E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 26.42 22.38 20.70 2.25 18.66 103.85 146.57 0.01
February 27.50 22.91 21.01 2.37 18.54 110.59 164.59 0.00
March 28.33 23.63 21.77 3.67 19.85 110.33 194.39 0.01
April 29.15 25.37 24.04 2.98 21.51 118.69 185.56 0.03
May 29.01 26.53 25.72 3.19 23.00 127.71 124.87 0.08
June 28.86 26.50 25.74 3.10 22.78 123.38 156.09 0.05
July 27.25 24.29 23.20 2.32 21.53 137.39 88.28 0.02
August 27.54 25.86 25.31 3.22 21.55 129.55 122.00 0.07
September 27.58 25.59 24.93 2.22 22.01 128.30 103.37 0.04
October 26.89 25.07 24.46 2.18 21.39 123.79 92.41 0.11
November 26.68 24.14 23.20 1.94 20.29 113.70 103.30 0.02
December 25.97 22.85 21.57 2.00 18.63 101.83 131.96 0.00
                 
Annual Sum or Average 27.59 24.60 23.48 2.62 20.82 119.14 134.17 0.04
Minimum of Months 25.97 22.38 20.70 1.94 18.54 101.83 88.28 0.00
Maximum of Months 29.15 26.53 25.74 3.67 23.00 137.39 194.39 0.11



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 34.10 04-JAN-12:00 23.67 19.40 5.00 24.66 266.50 576.50
February 35.00 21-FEB-13:00 22.02 16.00 2.10 24.16 230.00 672.50
March 36.40 21-MAR-12:00 23.01 17.00 5.00 26.97 269.50 658.50
April 35.50 01-APR-13:00 26.96 24.00 2.50 27.14 295.50 519.50
May 37.60 06-MAY-12:00 26.43 22.60 4.00 29.39 317.00 525.50
June 36.00 12-JUN-14:00 27.60 25.00 4.00 28.43 235.00 472.00
July 33.20 15-JUL-15:00 25.63 23.00 2.00 27.95 219.00 181.00
August 34.00 10-AUG-13:00 27.86 26.00 5.00 26.65 344.50 278.50
September 34.00 06-SEP-13:00 26.51 24.00 4.00 25.00 258.00 581.50
October 33.00 04-OCT-13:00 26.23 24.00 4.00 25.16 303.00 428.50
November 34.30 18-NOV-12:00 25.34 22.20 3.00 25.49 289.50 511.50
December 33.00 07-DEC-13:00 23.23 19.00 3.00 22.98 215.00 596.00
                 
Annual Sum or Average                
Minimum of Months 33.00   22.02 16.00 2.00 22.98 215.00 181.00
Maximum of Months 37.60   27.86 26.00 5.00 29.39 344.50 672.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 18.70 23-JAN-05:00 16.92 16.00 2.00 7.75 0.00 0.00
February 20.30 21-FEB-09:00 19.04 18.40 2.00 10.50 258.50 564.00
March 22.00 03-MAR-05:00 19.94 19.00 3.00 13.35 0.00 0.00
April 22.90 14-APR-15:00 22.90 22.90 3.00 14.65 199.50 264.50
May 22.00 10-MAY-19:00 22.00 22.00 2.00 18.28 0.00 0.00
June 23.00 20-JUN-23:00 23.00 23.00 2.00 19.35 0.00 0.00
July 23.00 13-JUL-04:00 22.27 22.00 0.00 13.91 0.00 0.00
August 22.00 20-AUG-10:00 22.00 22.00 5.00 18.28 430.50 41.50
September 22.90 19-SEP-03:00 22.78 22.78 0.00 21.27 0.00 0.00
October 22.50 23-OCT-04:00 22.50 22.50 2.80 18.82 0.00 0.00
November 20.00 25-NOV-04:00 18.63 18.00 2.00 10.69 0.00 0.00
December 18.00 21-DEC-04:00 17.36 17.00 3.00 9.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 18.00   16.92 16.00 0.00 7.75 0.00 0.00
Maximum of Months 23.00   23.00 23.00 5.00 21.27 430.50 564.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 25.53 12-JAN-12:00 32.40 23.10 2.00 25.00 353.00 347.00
February 26.17 14-FEB-15:00 32.30 24.20 2.00 25.16 200.00 199.00
March 26.28 27-MAR-12:00 34.20 23.60 4.00 26.32 326.00 535.00
April 27.93 10-APR-16:49 31.52 26.85 4.08 27.70 110.67 57.00
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 30.11 15-JUN-09:00 33.20 29.20 5.00 26.48 320.50 421.00
July 26.43 20-JUL-14:00 32.80 24.20 1.00 26.65 305.00 253.00
August 28.81 14-AUG-16:00 32.00 28.00 1.00 25.16 107.50 223.00
September 30.06 30-SEP-10:00 32.80 29.40 3.00 25.66 398.00 359.50
October 27.36 16-OCT-14:00 31.50 26.00 3.00 24.16 239.00 346.50
November 27.56 10-NOV-12:00 31.00 26.40 6.00 28.11 388.00 95.50
December 26.86 03-DEC-12:00 31.50 25.30 1.00 23.49 301.00 468.50
                 
Annual Sum or Average                
Minimum of Months 25.53   29.00 23.10 1.00 22.47 0.00 0.00
Maximum of Months 30.11   34.20 29.40 6.00 28.11 398.00 535.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.20 09-JAN-21:00 26.50 24.77 4.00 25.16 0.00 0.00
February 24.40 15-FEB-18:00 28.30 25.33 4.00 20.75 0.00 0.00
March 25.30 28-MAR-06:00 27.20 25.72 3.00 19.87 103.00 28.00
April 27.00 10-APR-17:00 30.50 27.87 4.50 25.00 20.00 20.50
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 29.20 15-JUN-09:00 33.20 30.11 5.00 26.48 320.50 421.00
July 26.00 10-JUL-14:00 26.50 26.11 2.30 23.49 286.00 36.50
August 28.00 02-AUG-10:00 31.00 28.65 4.00 24.16 419.00 195.50
September 29.40 30-SEP-10:00 32.80 30.06 3.00 25.66 398.00 359.50
October 26.50 16-OCT-08:00 29.00 27.04 2.50 21.78 300.00 326.00
November 26.40 10-NOV-12:00 31.00 27.56 6.00 28.11 388.00 95.50
December 26.00 10-DEC-17:00 29.00 26.74 3.00 21.78 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 24.20   26.50 24.77 2.30 19.87 0.00 0.00
Maximum of Months 29.40   33.20 30.11 6.00 28.11 419.00 421.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 29.71 38.82 0.00
February 18.00 13.00 16.00 29.90 44.34 0.00
March 18.00 13.00 16.00 30.35 50.49 0.00
April 18.00 13.00 16.00 30.97 51.18 0.00
May 18.00 13.00 16.00 31.58 43.47 0.00
June 18.00 13.00 16.00 32.02 46.77 0.00
July 18.00 13.00 16.00 32.16 39.95 0.00
August 18.00 13.00 16.00 31.97 43.65 0.00
September 18.00 13.00 16.00 31.50 40.53 0.00
October 18.00 13.00 16.00 30.87 37.35 0.00
November 18.00 13.00 16.00 30.27 35.77 0.00
December 18.00 13.00 16.00 29.84 36.19 0.00
             
Annual Sum or Average 18.00 13.00 16.00 30.93 42.35 0.00
Minimum of Months 18.00 13.00 16.00 29.71 35.77 0.00
Maximum of Months 18.00 13.00 16.00 32.16 51.18 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.309169E+10 -0.286027E+10 0.00 0.00 744.00 0.00 -231414882.6 60.05 0.00 0.00
February 0.279275E+10 -0.258354E+10 0.00 0.00 672.00 0.00 -209207126.3 60.05 0.00 0.00
March 0.324431E+10 -0.301192E+10 0.00 0.00 744.00 0.00 -232384767.7 60.05 0.00 0.00
April 0.287827E+10 -0.265355E+10 0.00 0.00 720.00 0.00 -224719015.6 60.05 0.00 0.00
May 0.301881E+10 -0.278642E+10 0.00 0.00 744.00 0.00 -232396559.1 60.05 0.00 0.00
June 0.295368E+10 -0.272880E+10 0.00 0.00 720.00 0.00 -224883015.9 60.05 0.00 0.00
July 0.278969E+10 -0.255790E+10 0.00 0.00 744.00 0.00 -231787147.5 60.05 0.00 0.00
August 0.308050E+10 -0.284818E+10 0.00 0.00 744.00 0.00 -232317172.7 60.05 0.00 0.00
September 0.283136E+10 -0.260680E+10 0.00 0.00 720.00 0.00 -224559071.2 60.05 0.00 0.00
October 0.298238E+10 -0.275070E+10 0.00 0.00 744.00 0.00 -231674844.9 60.05 0.00 0.00
November 0.298555E+10 -0.276145E+10 0.00 0.00 720.00 0.00 -224101526.9 60.05 0.00 0.00
December 0.300260E+10 -0.277121E+10 0.00 0.00 744.00 0.00 -231387212.3 60.05 0.00 0.00
                     
Annual Sum or Average 0.356516E+11 -0.329208E+11 0.00 0.00 8760.00 0.00 -0.273083E+10 60.05 0.00 0.00
Minimum of Months 0.278969E+10 -0.301192E+10 0.00 0.00 672.00 0.00 -232396559.1 60.05 0.00 0.00
Maximum of Months 0.324431E+10 -0.255790E+10 0.00 0.00 744.00 0.00 -209207126.3 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.51 0.48 01-JAN-07:49 2217.28 25.16 147.67 323.00 1094.02 24.85 305.00 311.67
February 321.17 0.52 0.48 01-FEB-07:10 1749.25 19.02 0.00 294.00 924.98 21.20 199.67 273.00
March 361.17 0.52 0.48 01-MAR-07:49 1322.03 18.81 0.00 326.67 736.93 20.92 161.67 299.67
April 358.33 0.51 0.48 01-APR-07:19 1084.11 18.46 0.00 323.50 616.08 20.60 68.50 287.00
May 376.33 0.53 0.48 01-MAY-07:10 927.95 17.37 0.00 330.00 516.69 19.47 0.00 282.00
June 370.50 0.53 0.48 01-JUN-07:00 906.21 17.54 0.00 323.00 521.19 19.71 0.00 277.33
July 383.17 0.54 0.48 01-JUL-07:30 877.96 16.93 0.00 326.17 477.26 18.99 0.00 275.50
August 369.33 0.52 0.48 01-AUG-07:10 1038.11 17.88 0.00 327.67 568.58 19.97 35.67 286.67
September 357.83 0.53 0.48 01-SEP-06:00 1173.42 17.74 0.00 314.00 617.96 19.78 85.33 275.67
October 356.83 0.51 0.48 01-OCT-06:00 1520.05 19.18 15.00 324.17 773.59 20.75 145.00 286.17
November 337.67 0.51 0.48 01-NOV-07:10 1921.19 23.57 114.83 313.00 941.98 21.73 232.67 281.83
December 349.33 0.51 0.48 01-DEC-06:49 2226.60 25.19 148.67 319.83 1093.99 24.79 301.00 304.17
                         
Annual Sum or Average 4292.33 0.52     1397.59 19.67 426.17 3845.00 732.81 21.02 1534.50 3440.67
Minimum of Months 321.17 0.51 0.48   877.96 16.93 0.00 294.00 477.26 18.99 0.00 273.00
Maximum of Months 383.17 0.54 0.48   2226.60 25.19 148.67 330.00 1094.02 24.85 305.00 311.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-07:19 1863.63 21.59 108.50 308.50 978.07 22.52 77.50 273.50
February 321.17 0.52 0.48 01-FEB-06:40 2067.88 21.71 99.00 286.33 1089.39 22.63 71.17 258.83
March 361.17 0.52 0.48 01-MAR-07:10 2346.86 21.75 112.17 321.83 974.57 21.26 52.17 294.00
April 358.33 0.51 0.48 01-APR-06:19 1935.09 19.98 84.17 328.33 1014.79 21.23 54.33 297.00
May 376.33 0.52 0.48 01-MAY-05:00 1658.82 19.20 87.33 337.83 868.05 21.39 67.33 299.00
June 370.50 0.52 0.48 01-JUN-06:49 1779.87 19.62 84.50 334.17 937.53 21.67 63.33 301.17
July 383.17 0.53 0.48 01-JUL-06:19 1480.12 18.89 86.67 336.17 760.80 20.89 64.17 293.83
August 369.33 0.51 0.48 01-AUG-05:00 1688.00 19.55 86.00 336.50 874.58 20.78 55.00 298.50
September 357.83 0.53 0.48 01-SEP-06:10 1593.46 18.96 83.67 313.83 815.86 20.14 54.50 274.67
October 356.83 0.52 0.48 01-OCT-06:10 1591.38 19.52 86.17 316.00 812.26 20.66 55.17 276.17
November 337.67 0.52 0.48 01-NOV-06:40 1604.95 20.16 84.50 298.50 806.11 21.03 51.33 260.00
December 349.33 0.53 0.48 01-DEC-06:40 1811.85 21.67 112.50 302.00 830.99 21.41 56.00 268.17
                         
Annual Sum or Average 4292.33 0.52     1781.29 20.19 1115.17 3820.00 894.92 21.29 722.00 3394.83
Minimum of Months 321.17 0.51 0.48   1480.12 18.89 83.67 286.33 760.80 20.14 51.33 258.83
Maximum of Months 383.17 0.53 0.48   2346.86 21.75 112.50 337.83 1089.39 22.63 77.50 301.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.55 0.48 01-JAN-08:00 740.54 16.51 0.00 298.33 437.33 18.68 0.00 241.83
February 321.17 0.54 0.48 01-FEB-07:00 815.14 17.04 0.00 280.17 483.22 19.19 0.00 240.83
March 361.17 0.52 0.48 01-MAR-08:09 931.08 17.97 0.00 323.33 551.22 20.09 1.33 289.67
April 358.33 0.50 0.48 01-APR-06:49 1138.35 18.94 0.00 333.17 644.93 21.04 118.50 303.00
May 376.33 0.51 0.48 01-MAY-06:19 1322.52 18.75 3.83 349.33 694.59 20.81 140.67 317.33
June 370.50 0.50 0.48 01-JUN-07:30 1584.26 23.13 112.83 348.50 808.81 22.66 224.50 323.83
July 383.17 0.51 0.48 01-JUL-06:49 1370.66 22.65 116.00 351.50 688.00 22.83 168.83 319.83
August 369.33 0.51 0.48 01-AUG-06:19 1227.61 18.66 0.00 342.83 658.49 20.75 122.67 308.33
September 357.83 0.53 0.48 01-SEP-06:00 996.49 17.46 0.00 314.83 539.39 19.48 42.00 273.83
October 356.83 0.53 0.48 01-OCT-07:49 880.76 17.24 0.00 311.50 483.80 19.28 0.00 260.67
November 337.67 0.54 0.48 01-NOV-07:49 788.33 16.86 0.00 288.50 444.15 18.94 0.00 235.17
December 349.33 0.55 0.48 01-DEC-07:40 721.09 16.27 0.00 291.17 420.66 18.43 0.00 233.50
                         
Annual Sum or Average 4292.33 0.52     1052.55 18.52 232.67 3833.17 575.26 20.23 818.50 3347.83
Minimum of Months 321.17 0.50 0.48   721.09 16.27 0.00 280.17 420.66 18.43 0.00 233.50
Maximum of Months 383.17 0.55 0.48   1584.26 23.13 116.00 351.50 808.81 22.83 224.50 323.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-09:30 1924.04 21.74 109.33 308.00 1007.36 22.60 77.50 275.17
February 321.17 0.53 0.48 01-FEB-08:20 2156.36 21.67 102.33 283.33 907.40 21.05 46.67 255.17
March 361.17 0.52 0.48 01-MAR-08:39 2393.35 21.49 112.67 331.33 992.19 20.94 51.17 298.50
April 358.33 0.51 0.48 01-APR-07:40 2332.07 15.23 0.00 327.67 980.92 18.58 0.00 296.50
May 376.33 0.52 0.48 01-MAY-07:30 1836.13 14.97 0.00 337.17 825.53 18.08 0.00 298.17
June 370.50 0.52 0.48 01-JUN-08:30 1731.03 15.41 0.00 332.67 906.27 18.64 0.00 299.67
July 383.17 0.53 0.48 01-JUL-07:00 1480.25 14.77 0.00 335.50 755.01 17.79 0.00 291.33
August 369.33 0.52 0.48 01-AUG-07:40 1696.43 15.56 8.50 334.50 857.08 18.27 0.00 296.17
September 357.83 0.53 0.48 01-SEP-07:40 1748.23 18.76 87.00 311.50 793.60 18.02 7.67 275.67
October 356.83 0.52 0.48 01-OCT-08:20 1660.58 20.65 101.83 315.33 856.24 21.86 72.67 278.50
November 337.67 0.52 0.48 01-NOV-08:20 1640.54 19.93 85.00 299.83 850.09 22.00 66.00 264.00
December 349.33 0.53 0.48 01-DEC-07:00 1703.56 20.04 90.00 305.17 902.69 22.07 71.83 270.00
                         
Annual Sum or Average 4292.33 0.52     1854.60 18.26 696.67 3822.00 885.00 19.93 393.50 3398.83
Minimum of Months 321.17 0.51 0.48   1480.25 14.77 0.00 283.33 755.01 17.79 0.00 255.17
Maximum of Months 383.17 0.53 0.48   2393.35 21.74 112.67 337.17 1007.36 22.60 77.50 299.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.51 0.48 01-JAN-07:00 2126.19 22.71 147.50 322.33 1030.52 22.65 88.50 309.33
February 321.17 0.52 0.48 01-FEB-07:10 1673.13 15.15 0.00 293.67 873.20 18.74 0.00 271.33
March 361.17 0.52 0.48 01-MAR-07:49 1268.78 15.34 0.00 326.17 703.72 18.80 0.00 298.00
April 358.33 0.52 0.48 01-APR-07:19 1043.38 15.08 0.00 320.00 592.45 18.54 0.00 283.33
May 376.33 0.53 0.48 01-MAY-07:10 894.23 13.71 0.00 327.00 496.98 17.11 0.00 277.00
June 370.50 0.53 0.48 01-JUN-07:00 872.70 14.03 0.00 320.17 501.98 17.51 0.00 273.17
July 383.17 0.54 0.48 01-JUL-07:30 846.99 13.10 0.00 324.17 458.88 16.50 0.00 269.50
August 369.33 0.52 0.48 01-AUG-07:10 999.83 14.27 0.00 325.67 545.90 17.66 0.00 280.50
September 357.83 0.53 0.48 01-SEP-06:00 1129.14 14.00 0.00 310.67 590.85 17.34 0.00 273.17
October 356.83 0.52 0.48 01-OCT-07:10 1459.27 15.43 15.00 322.67 735.49 18.35 4.50 281.83
November 337.67 0.51 0.48 01-NOV-07:19 1842.05 20.86 114.33 312.00 895.20 20.39 39.83 282.17
December 349.33 0.51 0.48 01-DEC-06:49 2134.53 22.76 148.50 318.67 1029.85 22.54 87.50 302.83
                         
Annual Sum or Average 4292.33 0.52     1342.19 16.29 425.33 3823.17 697.67 18.79 220.33 3402.17
Minimum of Months 321.17 0.51 0.48   846.99 13.10 0.00 293.67 458.88 16.50 0.00 269.50
Maximum of Months 383.17 0.54 0.48   2134.53 22.76 148.50 327.00 1030.52 22.65 88.50 309.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-07:19 1807.10 21.14 108.50 307.17 938.85 22.32 77.50 270.50
February 321.17 0.53 0.48 01-FEB-06:40 2014.93 21.26 99.00 285.50 1045.26 22.44 71.17 256.00
March 361.17 0.52 0.48 01-MAR-07:10 2283.42 21.30 112.17 320.50 928.50 21.08 52.17 291.83
April 358.33 0.51 0.48 01-APR-06:19 1864.66 19.52 84.17 325.67 968.12 21.06 54.33 294.33
May 376.33 0.52 0.48 01-MAY-05:00 1619.36 18.75 87.33 336.00 829.57 21.24 67.33 295.33
June 370.50 0.52 0.48 01-JUN-06:49 1728.28 19.17 84.50 331.50 896.45 21.50 63.00 296.67
July 383.17 0.53 0.48 01-JUL-06:30 1439.62 18.44 86.67 333.00 721.35 19.99 56.33 288.00
August 369.33 0.52 0.48 01-AUG-05:00 1639.44 19.10 86.00 334.17 834.77 20.62 55.00 295.83
September 357.83 0.53 0.48 01-SEP-06:10 1533.95 18.51 83.67 312.50 778.71 19.96 54.50 271.67
October 356.83 0.53 0.48 01-OCT-06:10 1548.23 19.04 86.17 313.83 775.91 20.45 55.17 272.33
November 337.67 0.53 0.48 01-NOV-06:40 1554.72 19.68 84.50 295.50 770.24 20.81 51.33 256.50
December 349.33 0.54 0.48 01-DEC-06:40 1760.10 21.22 112.50 300.00 794.26 21.19 56.00 265.50
                         
Annual Sum or Average 4292.33 0.52     1729.07 19.73 1115.17 3795.33 854.85 21.04 713.83 3354.50
Minimum of Months 321.17 0.51 0.48   1439.62 18.44 83.67 285.50 721.35 19.96 51.33 256.00
Maximum of Months 383.17 0.54 0.48   2283.42 21.30 112.50 336.00 1045.26 22.44 77.50 296.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.55 0.48 01-JAN-09:09 713.59 13.04 0.00 295.17 422.31 16.52 0.00 235.00
February 321.17 0.54 0.48 01-FEB-08:09 785.59 13.66 0.00 277.67 466.75 17.13 0.00 235.50
March 361.17 0.52 0.48 01-MAR-08:20 896.76 14.69 0.00 320.00 532.01 18.14 0.00 286.33
April 358.33 0.51 0.48 01-APR-06:00 1095.30 15.53 0.00 330.67 619.82 19.03 0.00 299.17
May 376.33 0.51 0.48 01-MAY-06:19 1271.76 14.92 3.83 347.17 662.92 18.30 1.17 314.00
June 370.50 0.50 0.48 01-JUN-07:30 1522.57 20.47 112.17 347.67 769.29 20.36 33.17 319.67
July 383.17 0.51 0.48 01-JUL-06:49 1319.34 19.90 115.67 350.17 655.38 20.56 59.17 315.83
August 369.33 0.51 0.48 01-AUG-06:40 1180.95 14.95 0.00 340.50 630.11 18.40 0.00 304.67
September 357.83 0.53 0.48 01-SEP-06:00 960.21 13.80 0.00 313.00 517.84 17.13 0.00 270.50
October 356.83 0.53 0.48 01-OCT-07:49 849.42 13.52 0.00 309.83 465.41 16.90 0.00 256.00
November 337.67 0.54 0.48 01-NOV-07:00 760.35 13.19 0.00 286.00 428.05 16.61 0.00 229.17
December 349.33 0.55 0.48 01-DEC-07:49 694.91 12.71 0.00 289.00 405.97 16.17 0.00 228.00
                         
Annual Sum or Average 4292.33 0.53     1013.32 15.10 231.67 3806.83 551.75 17.98 93.50 3293.83
Minimum of Months 321.17 0.50 0.48   694.91 12.71 0.00 277.67 405.97 16.17 0.00 228.00
Maximum of Months 383.17 0.55 0.48   1522.57 20.47 115.67 350.17 769.29 20.56 59.17 319.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-09:39 1868.00 21.35 109.33 305.83 967.72 22.48 77.67 271.50
February 321.17 0.53 0.48 01-FEB-08:30 2102.21 21.27 102.33 282.00 864.92 20.92 46.67 252.83
March 361.17 0.52 0.48 01-MAR-08:50 2336.50 21.07 112.67 329.00 945.86 20.79 51.17 294.00
April 358.33 0.51 0.48 01-APR-07:49 2253.95 14.67 0.00 325.83 935.14 18.37 0.00 294.00
May 376.33 0.52 0.48 01-MAY-07:30 1796.97 14.40 0.00 335.50 787.76 17.85 0.00 294.00
June 370.50 0.52 0.48 01-JUN-08:30 1683.94 14.83 0.00 330.83 865.34 18.41 0.00 295.50
July 383.17 0.53 0.48 01-JUL-07:00 1440.92 14.19 0.00 333.83 721.16 17.55 0.00 289.67
August 369.33 0.52 0.48 01-AUG-07:40 1644.99 15.01 8.50 332.33 818.14 18.05 0.00 291.67
September 357.83 0.53 0.48 01-SEP-07:49 1689.05 18.11 85.00 310.67 756.99 17.82 7.67 271.00
October 356.83 0.53 0.48 01-OCT-08:30 1601.22 18.93 87.50 312.67 819.97 21.73 72.67 275.00
November 337.67 0.52 0.48 01-NOV-08:30 1588.65 19.49 85.00 298.17 813.81 21.88 66.00 260.50
December 349.33 0.53 0.48 01-DEC-07:00 1646.43 19.38 87.33 303.67 864.59 21.95 71.83 267.00
                         
Annual Sum or Average 4292.33 0.52     1800.63 17.63 677.67 3800.33 845.62 19.76 393.67 3356.67
Minimum of Months 321.17 0.51 0.48   1440.92 14.19 0.00 282.00 721.16 17.55 0.00 252.83
Maximum of Months 383.17 0.53 0.48   2336.50 21.35 112.67 335.50 967.72 22.48 77.67 295.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.51 0.48 01-JAN-07:00 2126.07 22.71 147.50 322.33 1030.43 22.65 88.50 309.33
February 321.17 0.52 0.48 01-FEB-07:10 1673.02 15.15 0.00 293.67 873.13 18.74 0.00 271.33
March 361.17 0.52 0.48 01-MAR-07:49 1268.71 15.35 0.00 326.17 703.67 18.80 0.00 298.00
April 358.33 0.52 0.48 01-APR-07:19 1043.33 15.08 0.00 320.00 592.40 18.54 0.00 283.33
May 376.33 0.53 0.48 01-MAY-07:10 894.18 13.71 0.00 327.00 496.94 17.11 0.00 277.00
June 370.50 0.53 0.48 01-JUN-07:00 872.66 14.03 0.00 320.17 501.95 17.51 0.00 273.17
July 383.17 0.54 0.48 01-JUL-07:30 846.94 13.10 0.00 324.17 458.84 16.50 0.00 269.50
August 369.33 0.52 0.48 01-AUG-07:10 999.77 14.28 0.00 325.67 545.86 17.67 0.00 280.50
September 357.83 0.53 0.48 01-SEP-06:00 1129.06 14.01 0.00 310.67 590.80 17.34 0.00 273.17
October 356.83 0.52 0.48 01-OCT-07:10 1459.16 15.43 15.00 322.67 735.42 18.35 4.50 281.83
November 337.67 0.51 0.48 01-NOV-07:19 1841.93 20.86 114.33 312.00 895.11 20.39 39.83 282.17
December 349.33 0.51 0.48 01-DEC-06:49 2134.41 22.76 148.50 318.67 1029.76 22.54 87.50 302.83
                         
Annual Sum or Average 4292.33 0.52     1342.11 16.29 425.33 3823.17 697.61 18.80 220.33 3402.17
Minimum of Months 321.17 0.51 0.48   846.94 13.10 0.00 293.67 458.84 16.50 0.00 269.50
Maximum of Months 383.17 0.54 0.48   2134.41 22.76 148.50 327.00 1030.43 22.65 88.50 309.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-07:19 1807.04 21.14 108.50 307.17 938.79 22.32 77.50 270.50
February 321.17 0.53 0.48 01-FEB-06:40 2014.87 21.27 99.00 285.50 1045.20 22.44 71.17 256.00
March 361.17 0.52 0.48 01-MAR-07:10 2283.37 21.30 112.17 320.50 928.44 21.08 52.17 291.83
April 358.33 0.51 0.48 01-APR-06:19 1864.60 19.52 84.17 325.67 968.05 21.06 54.33 294.33
May 376.33 0.52 0.48 01-MAY-05:00 1619.29 18.75 87.33 336.00 829.51 21.24 67.33 295.33
June 370.50 0.52 0.48 01-JUN-06:49 1728.21 19.17 84.50 331.50 896.39 21.50 63.00 296.67
July 383.17 0.53 0.48 01-JUL-06:30 1439.53 18.44 86.67 333.00 721.29 19.99 56.33 288.00
August 369.33 0.52 0.48 01-AUG-05:00 1639.36 19.10 86.00 334.17 834.71 20.62 55.00 295.83
September 357.83 0.53 0.48 01-SEP-06:10 1533.87 18.51 83.67 312.50 778.65 19.96 54.50 271.67
October 356.83 0.53 0.48 01-OCT-06:10 1548.16 19.04 86.17 313.83 775.85 20.45 55.17 272.33
November 337.67 0.53 0.48 01-NOV-06:40 1554.65 19.68 84.50 295.50 770.18 20.81 51.33 256.50
December 349.33 0.54 0.48 01-DEC-06:40 1760.04 21.22 112.50 300.00 794.20 21.19 56.00 265.50
                         
Annual Sum or Average 4292.33 0.52     1729.00 19.73 1115.17 3795.33 854.79 21.04 713.83 3354.50
Minimum of Months 321.17 0.51 0.48   1439.53 18.44 83.67 285.50 721.29 19.96 51.33 256.00
Maximum of Months 383.17 0.54 0.48   2283.37 21.30 112.50 336.00 1045.20 22.44 77.50 296.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.55 0.48 01-JAN-09:09 713.57 13.04 0.00 295.17 422.28 16.52 0.00 235.00
February 321.17 0.54 0.48 01-FEB-08:09 785.56 13.67 0.00 277.67 466.71 17.13 0.00 235.50
March 361.17 0.52 0.48 01-MAR-08:20 896.73 14.70 0.00 320.00 531.97 18.14 0.00 286.33
April 358.33 0.51 0.48 01-APR-06:00 1095.25 15.53 0.00 330.67 619.77 19.03 0.00 299.17
May 376.33 0.51 0.48 01-MAY-06:19 1271.67 14.92 3.83 347.17 662.87 18.30 1.17 313.83
June 370.50 0.50 0.48 01-JUN-07:30 1522.48 20.47 112.17 347.67 769.23 20.36 33.17 319.67
July 383.17 0.51 0.48 01-JUL-06:49 1319.25 19.90 115.67 350.17 655.32 20.56 59.17 315.83
August 369.33 0.51 0.48 01-AUG-06:40 1180.88 14.95 0.00 340.50 630.06 18.40 0.00 304.67
September 357.83 0.53 0.48 01-SEP-06:00 960.15 13.80 0.00 313.00 517.80 17.13 0.00 270.50
October 356.83 0.53 0.48 01-OCT-07:49 849.37 13.52 0.00 309.83 465.38 16.90 0.00 256.00
November 337.67 0.54 0.48 01-NOV-07:00 760.31 13.19 0.00 286.00 428.02 16.61 0.00 229.17
December 349.33 0.55 0.48 01-DEC-07:49 694.88 12.72 0.00 289.00 405.94 16.17 0.00 228.00
                         
Annual Sum or Average 4292.33 0.53     1013.26 15.11 231.67 3806.83 551.71 17.98 93.50 3293.67
Minimum of Months 321.17 0.50 0.48   694.88 12.72 0.00 277.67 405.94 16.17 0.00 228.00
Maximum of Months 383.17 0.55 0.48   1522.48 20.47 115.67 350.17 769.23 20.56 59.17 319.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.53 0.48 01-JAN-09:39 1867.94 21.35 109.33 305.83 967.66 22.48 77.67 271.50
February 321.17 0.53 0.48 01-FEB-08:30 2102.15 21.27 102.33 282.00 864.86 20.92 46.67 252.83
March 361.17 0.52 0.48 01-MAR-08:50 2336.44 21.07 112.67 329.00 945.80 20.79 51.17 294.00
April 358.33 0.51 0.48 01-APR-07:49 2253.89 14.67 0.00 325.83 935.08 18.38 0.00 294.00
May 376.33 0.52 0.48 01-MAY-07:30 1796.89 14.40 0.00 335.50 787.70 17.85 0.00 294.00
June 370.50 0.52 0.48 01-JUN-08:30 1683.87 14.84 0.00 330.83 865.28 18.41 0.00 295.50
July 383.17 0.53 0.48 01-JUL-07:00 1440.84 14.19 0.00 333.83 721.11 17.55 0.00 289.67
August 369.33 0.52 0.48 01-AUG-07:40 1644.91 15.01 8.50 332.33 818.08 18.05 0.00 291.67
September 357.83 0.53 0.48 01-SEP-07:49 1688.98 18.11 85.00 310.67 756.93 17.82 7.67 271.00
October 356.83 0.53 0.48 01-OCT-08:30 1601.14 18.93 87.50 312.67 819.91 21.73 72.67 274.83
November 337.67 0.52 0.48 01-NOV-08:30 1588.58 19.49 85.00 298.17 813.75 21.88 66.00 260.50
December 349.33 0.53 0.48 01-DEC-07:00 1646.38 19.38 87.33 303.67 864.53 21.95 71.83 267.00
                         
Annual Sum or Average 4292.33 0.52     1800.56 17.63 677.67 3800.33 845.56 19.76 393.67 3356.50
Minimum of Months 321.17 0.51 0.48   1440.84 14.19 0.00 282.00 721.11 17.55 0.00 252.83
Maximum of Months 383.17 0.53 0.48   2336.44 21.35 112.67 335.50 967.66 22.48 77.67 295.50



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.101151E+12 0.693661E+11 110266.42 09-JAN-05:02 76961.14 0.00
February 0.00 0.00 0.954913E+11 0.655741E+11 105720.52 06-FEB-06:02 79828.64 0.00
March 0.00 0.00 0.115774E+12 0.774720E+11 124664.54 28-MAR-04:02 81703.61 0.00
April 0.00 0.00 0.120808E+12 0.739592E+11 125175.24 12-APR-04:02 81294.88 0.00
May 0.00 0.00 0.138299E+12 0.787161E+11 130461.07 20-MAY-04:02 75323.18 0.00
June 0.00 0.00 0.138936E+12 0.797039E+11 131519.24 10-JUN-04:02 76438.51 0.00
July 0.00 0.00 0.111659E+12 0.690435E+11 114118.97 10-JUL-04:02 81543.00 0.00
August 0.00 0.00 0.130376E+12 0.730022E+11 129879.82 07-AUG-04:02 79950.58 0.00
September 0.00 0.00 0.118823E+12 0.678289E+11 125575.04 25-SEP-04:02 81526.62 0.00
October 0.00 0.00 0.115485E+12 0.663399E+11 115125.27 05-OCT-04:02 74982.18 0.00
November 0.00 0.00 0.107656E+12 0.659595E+11 116843.32 13-NOV-07:03 82499.78 0.00
December 0.00 0.00 0.989210E+11 0.653277E+11 107749.49 04-DEC-07:03 78559.13 0.00
                 
Annual Sum or Average 0.00 0.00 0.139338E+13 0.852293E+12       0.00
Minimum of Months 0.00 0.00 0.954913E+11 0.653277E+11 105720.52   74982.18 0.00
Maximum of Months 0.00 0.00 0.138936E+12 0.797039E+11 131519.24   82499.78 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.866506E+11 0.578918E+11 107134.60 09-JAN-05:02 68170.48 0.00
February 0.00 0.00 0.829888E+11 0.553682E+11 113997.82 06-FEB-06:02 72557.82 0.00
March 0.00 0.00 0.100996E+12 0.655566E+11 116991.25 27-MAR-04:02 73546.42 0.00
April 0.00 0.00 0.106330E+12 0.625305E+11 116920.60 12-APR-04:02 71853.73 0.00
May 0.00 0.00 0.121182E+12 0.661001E+11 121197.09 22-MAY-04:02 66303.57 0.00
June 0.00 0.00 0.121662E+12 0.667082E+11 120552.22 10-JUN-04:02 65066.64 0.00
July 0.00 0.00 0.959244E+11 0.565832E+11 110643.28 10-JUL-04:02 73031.23 0.00
August 0.00 0.00 0.112356E+12 0.595610E+11 122602.32 21-AUG-04:02 58566.36 0.00
September 0.00 0.00 0.102887E+12 0.557560E+11 117421.20 25-SEP-04:02 71801.88 0.00
October 0.00 0.00 0.995558E+11 0.546750E+11 118204.29 30-OCT-04:02 70720.88 0.00
November 0.00 0.00 0.923610E+11 0.544715E+11 112933.30 13-NOV-05:02 73004.73 0.00
December 0.00 0.00 0.850336E+11 0.541900E+11 96542.77 26-DEC-07:03 69905.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.120793E+13 0.709392E+12       0.00
Minimum of Months 0.00 0.00 0.829888E+11 0.541900E+11 96542.77   58566.36 0.00
Maximum of Months 0.00 0.00 0.121662E+12 0.667082E+11 122602.32   73546.42 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.906283E+11 0.616796E+11 101905.43 09-JAN-05:02 62586.67 0.00
February 0.00 0.00 0.873389E+11 0.595656E+11 124295.21 06-FEB-06:02 79341.01 0.00
March 0.00 0.00 0.106940E+12 0.713687E+11 131951.68 20-MAR-04:02 85262.54 0.00
April 0.00 0.00 0.112869E+12 0.687070E+11 132615.35 03-APR-04:02 85737.85 0.00
May 0.00 0.00 0.127140E+12 0.718104E+11 140661.91 22-MAY-04:02 76267.31 0.00
June 0.00 0.00 0.127953E+12 0.727948E+11 139786.72 10-JUN-05:03 71401.55 0.00
July 0.00 0.00 0.100529E+12 0.610020E+11 120200.97 10-JUL-04:02 80243.59 0.00
August 0.00 0.00 0.116678E+12 0.638849E+11 136869.07 12-AUG-05:03 72893.07 0.00
September 0.00 0.00 0.107288E+12 0.601442E+11 126691.45 11-SEP-04:02 83800.87 0.00
October 0.00 0.00 0.103010E+12 0.580687E+11 135129.77 30-OCT-04:02 78751.75 0.00
November 0.00 0.00 0.959882E+11 0.580211E+11 112812.40 13-NOV-05:02 71162.24 0.00
December 0.00 0.00 0.888566E+11 0.576860E+11 93202.15 26-DEC-07:03 64821.40 0.00
                 
Annual Sum or Average 0.00 0.00 0.126522E+13 0.764733E+12       0.00
Minimum of Months 0.00 0.00 0.873389E+11 0.576860E+11 93202.15   62586.67 0.00
Maximum of Months 0.00 0.00 0.127953E+12 0.727948E+11 140661.91   85737.85 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 1059.41 3859.61 12-JAN-12:17
February 0.00 0.00 01-FEB-00:10 1059.43 3850.50 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 1115.80 3808.99 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 1015.33 3729.68 03-APR-11:20
May 0.00 0.00 01-MAY-00:02 1031.80 3654.06 01-MAY-11:10
June 0.00 0.00 01-JUN-00:10 1044.17 3583.28 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 946.74 3548.83 31-JUL-11:30
August 0.00 0.00 01-AUG-00:10 1054.75 3593.35 31-AUG-11:20
September 0.00 0.00 01-SEP-00:10 997.32 3662.52 29-SEP-11:17
October 0.00 0.00 01-OCT-00:10 1018.56 3748.71 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 1056.84 3817.28 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 1026.28 3854.78 29-DEC-12:20
             
Annual Sum or Average 0.00     1035.42    
Minimum of Months 0.00 0.00   946.74 3548.83  
Maximum of Months 0.00 0.00   1115.80 3859.61  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.403060E+10 0.46 10355.39 30-JAN-07:03 1.78
February 0.382022E+10 0.47 10355.39 06-FEB-06:02 1.78
March 0.444330E+10 0.49 10355.39 13-MAR-04:02 1.78
April 0.414603E+10 0.48 10355.39 03-APR-04:02 1.78
May 0.447833E+10 0.50 10355.39 01-MAY-06:03 1.78
June 0.476169E+10 0.52 10355.39 05-JUN-06:03 1.78
July 0.394419E+10 0.46 10355.39 05-JUL-06:03 1.78
August 0.417306E+10 0.47 10355.39 07-AUG-04:02 1.78
September 0.379817E+10 0.46 10355.39 05-SEP-04:02 1.78
October 0.371300E+10 0.44 10355.39 16-OCT-04:02 1.78
November 0.381260E+10 0.45 10355.39 13-NOV-07:03 1.78
December 0.372629E+10 0.43 10355.39 04-DEC-07:03 1.78
           
Annual Sum or Average 0.488475E+11 0.47      
Minimum of Months 0.371300E+10 0.43 10355.39   1.78
Maximum of Months 0.476169E+10 0.52 10355.39   1.78



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.311279E+10 0.41 8438.65 09-JAN-05:02 1.67
February 0.298684E+10 0.43 9338.90 06-FEB-06:02 1.78
March 0.340717E+10 0.45 9338.90 13-MAR-04:02 1.78
April 0.312736E+10 0.43 9338.90 03-APR-04:02 1.78
May 0.334934E+10 0.45 9338.90 02-MAY-04:02 1.78
June 0.352998E+10 0.47 9338.90 05-JUN-04:02 1.78
July 0.286845E+10 0.40 9338.90 03-JUL-04:02 1.78
August 0.300562E+10 0.42 9338.90 02-AUG-04:02 1.78
September 0.277211E+10 0.41 9338.90 05-SEP-04:02 1.78
October 0.277140E+10 0.39 9338.90 10-OCT-04:02 1.78
November 0.287843E+10 0.41 9338.90 13-NOV-05:02 1.78
December 0.283961E+10 0.39 9338.90 26-DEC-07:03 1.78
           
Annual Sum or Average 0.366491E+11 0.42      
Minimum of Months 0.277140E+10 0.39 8438.65   1.67
Maximum of Months 0.352998E+10 0.47 9338.90   1.78



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.299676E+10 0.38 6355.35 02-JAN-06:12 1.27
February 0.291416E+10 0.40 10844.99 06-FEB-06:02 1.78
March 0.340341E+10 0.42 10844.99 20-MAR-04:02 1.78
April 0.316593E+10 0.41 10844.99 03-APR-04:02 1.78
May 0.333525E+10 0.42 10844.99 08-MAY-04:02 1.78
June 0.351908E+10 0.44 10760.75 12-JUN-04:02 1.77
July 0.281405E+10 0.38 10456.81 31-JUL-04:02 1.74
August 0.294499E+10 0.39 10795.37 14-AUG-04:02 1.77
September 0.274496E+10 0.38 10844.99 05-SEP-04:02 1.78
October 0.267332E+10 0.37 9939.18 16-OCT-04:02 1.68
November 0.276689E+10 0.37 7572.22 13-NOV-05:02 1.42
December 0.272382E+10 0.36 6928.35 26-DEC-07:03 1.34
           
Annual Sum or Average 0.360026E+11 0.39      
Minimum of Months 0.267332E+10 0.36 6355.35   1.27
Maximum of Months 0.351908E+10 0.44 10844.99   1.78



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:05 2.06 2.06 58.84 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:03 2.06 2.06 58.16 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:03 2.06 2.06 58.13 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:03 2.06 2.06 58.23 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:05 2.06 2.06 58.22 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 58.30 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 58.32 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 58.31 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 58.28 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.82 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 58.20 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:03 2.06 2.06 58.18 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 58.13 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.84 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 58.84 58.84 1059.41 3859.61 12-JAN-12:17
February 0.00 0.00 01-FEB-00:10 58.54 58.54 1059.43 3850.50 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 58.56 58.56 1115.80 3808.99 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 58.59 58.59 1015.33 3729.68 03-APR-11:20
May 0.00 0.00 01-MAY-00:02 58.90 58.90 1031.80 3654.06 01-MAY-11:10
June 0.00 0.00 01-JUN-00:10 58.65 58.65 1044.17 3583.28 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 58.67 58.67 946.74 3548.83 31-JUL-11:30
August 0.00 0.00 01-AUG-00:10 58.67 58.67 1054.75 3593.35 31-AUG-11:20
September 0.00 0.00 01-SEP-00:10 58.64 58.64 997.32 3662.52 29-SEP-11:17
October 0.00 0.00 01-OCT-00:10 58.04 58.04 1018.56 3748.71 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 58.58 58.58 1056.84 3817.28 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 58.56 58.56 1026.28 3854.78 29-DEC-12:20
                 
Annual Sum or Average 0.00         1035.42    
Minimum of Months 0.00 0.00   58.04 58.04 946.74 3548.83  
Maximum of Months 0.00 0.00   58.90 58.90 1115.80 3859.61  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.276639E+11 0.00 0.00
February 0.00 0.00 0.00 0.264816E+11 0.00 0.00
March 0.00 0.00 0.00 0.322434E+11 0.00 0.00
April 0.00 0.00 0.00 0.329942E+11 0.00 0.00
May 0.00 0.00 0.00 0.371932E+11 0.00 0.00
June 0.00 0.00 0.00 0.377743E+11 0.00 0.00
July 0.00 0.00 0.00 0.296138E+11 0.00 0.00
August 0.00 0.00 0.00 0.340913E+11 0.00 0.00
September 0.00 0.00 0.00 0.310944E+11 0.00 0.00
October 0.00 0.00 0.00 0.298783E+11 0.00 0.00
November 0.00 0.00 0.00 0.284235E+11 0.00 0.00
December 0.00 0.00 0.00 0.265216E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.373973E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.264816E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.377743E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.233066E+11 0.00 0.00
February 0.00 0.00 0.00 0.226128E+11 0.00 0.00
March 0.00 0.00 0.00 0.275278E+11 0.00 0.00
April 0.00 0.00 0.00 0.282867E+11 0.00 0.00
May 0.00 0.00 0.00 0.317835E+11 0.00 0.00
June 0.00 0.00 0.00 0.321700E+11 0.00 0.00
July 0.00 0.00 0.00 0.247680E+11 0.00 0.00
August 0.00 0.00 0.00 0.285645E+11 0.00 0.00
September 0.00 0.00 0.00 0.262006E+11 0.00 0.00
October 0.00 0.00 0.00 0.251778E+11 0.00 0.00
November 0.00 0.00 0.00 0.238877E+11 0.00 0.00
December 0.00 0.00 0.00 0.223707E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.316657E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.223707E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.321700E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.242478E+11 0.00 0.00
February 0.00 0.00 0.00 0.236948E+11 0.00 0.00
March 0.00 0.00 0.00 0.290716E+11 0.00 0.00
April 0.00 0.00 0.00 0.299732E+11 0.00 0.00
May 0.00 0.00 0.00 0.332908E+11 0.00 0.00
June 0.00 0.00 0.00 0.337595E+11 0.00 0.00
July 0.00 0.00 0.00 0.258599E+11 0.00 0.00
August 0.00 0.00 0.00 0.295691E+11 0.00 0.00
September 0.00 0.00 0.00 0.272614E+11 0.00 0.00
October 0.00 0.00 0.00 0.259292E+11 0.00 0.00
November 0.00 0.00 0.00 0.246808E+11 0.00 0.00
December 0.00 0.00 0.00 0.232319E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.330570E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.232319E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.337595E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.403060E+10 0.101151E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.382022E+10 0.954913E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.444330E+10 0.115774E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.414603E+10 0.120808E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.447833E+10 0.138299E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.476169E+10 0.138936E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.394419E+10 0.111659E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.417306E+10 0.130376E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.379817E+10 0.118823E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.371300E+10 0.115485E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.381260E+10 0.107656E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.372629E+10 0.989210E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.488475E+11 0.139338E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.371300E+10 0.954913E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.476169E+10 0.138936E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.311279E+10 0.866506E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.298684E+10 0.829888E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.340717E+10 0.100996E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.312736E+10 0.106330E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.334934E+10 0.121182E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352998E+10 0.121662E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.286845E+10 0.959244E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.300562E+10 0.112356E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.277211E+10 0.102887E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.277140E+10 0.995558E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.287843E+10 0.923610E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.283961E+10 0.850336E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.366491E+11 0.120793E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.277140E+10 0.829888E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.352998E+10 0.121662E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.299676E+10 0.906283E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.291416E+10 0.873389E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.340341E+10 0.106940E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.316593E+10 0.112869E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.333525E+10 0.127140E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.351908E+10 0.127953E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.281405E+10 0.100529E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.294499E+10 0.116678E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.274496E+10 0.107288E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.267332E+10 0.103010E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.276689E+10 0.959882E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.272382E+10 0.888566E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.360026E+11 0.126522E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.267332E+10 0.873389E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.351908E+10 0.127953E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.403060E+10 0.00 0.00 0.00 0.236333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.382022E+10 0.00 0.00 0.00 0.226613E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.444330E+10 0.00 0.00 0.00 0.278001E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.414603E+10 0.00 0.00 0.00 0.288481E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.447833E+10 0.00 0.00 0.00 0.327148E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.476169E+10 0.00 0.00 0.00 0.330126E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.394419E+10 0.00 0.00 0.00 0.256696E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.417306E+10 0.00 0.00 0.00 0.299182E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.379817E+10 0.00 0.00 0.00 0.272962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.371300E+10 0.00 0.00 0.00 0.261653E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.381260E+10 0.00 0.00 0.00 0.246109E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.372629E+10 0.00 0.00 0.00 0.227953E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.488475E+11 0.00 0.00 0.00 0.325126E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.371300E+10 0.00 0.00 0.00 0.226613E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.476169E+10 0.00 0.00 0.00 0.330126E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.311279E+10 0.00 0.00 0.00 0.201938E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.298684E+10 0.00 0.00 0.00 0.196259E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.340717E+10 0.00 0.00 0.00 0.241206E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.312736E+10 0.00 0.00 0.00 0.251593E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.334934E+10 0.00 0.00 0.00 0.284342E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352998E+10 0.00 0.00 0.00 0.286400E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.286845E+10 0.00 0.00 0.00 0.218996E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.300562E+10 0.00 0.00 0.00 0.255589E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.277211E+10 0.00 0.00 0.00 0.234285E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.277140E+10 0.00 0.00 0.00 0.224064E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.287843E+10 0.00 0.00 0.00 0.210093E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.283961E+10 0.00 0.00 0.00 0.195310E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.366491E+11 0.00 0.00 0.00 0.280007E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.277140E+10 0.00 0.00 0.00 0.195310E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.352998E+10 0.00 0.00 0.00 0.286400E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.299676E+10 0.00 0.00 0.00 0.212511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.291416E+10 0.00 0.00 0.00 0.207807E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.340341E+10 0.00 0.00 0.00 0.256682E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.316593E+10 0.00 0.00 0.00 0.268073E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.333525E+10 0.00 0.00 0.00 0.299555E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.351908E+10 0.00 0.00 0.00 0.302405E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.281405E+10 0.00 0.00 0.00 0.230458E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.294499E+10 0.00 0.00 0.00 0.266241E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.274496E+10 0.00 0.00 0.00 0.245164E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.267332E+10 0.00 0.00 0.00 0.232558E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.276689E+10 0.00 0.00 0.00 0.219139E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.272382E+10 0.00 0.00 0.00 0.205081E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.360026E+11 0.00 0.00 0.00 0.294567E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.267332E+10 0.00 0.00 0.00 0.205081E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.351908E+10 0.00 0.00 0.00 0.302405E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1058606.34 0.121161E+11 0.00 55379.37 0.220569E+10 0.00 221619.68 0.00 0.34
February 0.00 0.116501E+11 0.00 0.00 0.234282E+10 0.00 0.00 0.00 0.34
March 0.00 0.156583E+11 0.00 0.00 0.236913E+10 0.00 0.00 0.00 0.35
April 0.00 0.185387E+11 0.00 0.00 0.401954E+10 0.00 0.00 0.00 0.34
May 0.00 0.227337E+11 0.00 0.00 0.510913E+10 0.00 0.00 0.00 0.35
June 0.00 0.228308E+11 0.00 0.00 0.409967E+10 0.00 0.00 0.00 0.34
July 0.00 0.160471E+11 0.00 0.00 0.357431E+10 0.00 0.00 0.00 0.34
August 0.00 0.228170E+11 0.00 0.00 0.313263E+10 0.00 0.00 0.00 0.35
September 0.00 0.198180E+11 0.00 0.00 0.397112E+10 0.00 0.00 0.00 0.34
October 0.00 0.191401E+11 0.00 0.00 0.352769E+10 0.00 0.00 0.00 0.34
November 0.00 0.159330E+11 0.00 0.00 0.292361E+10 0.00 0.00 0.00 0.34
December 0.00 0.126835E+11 0.00 0.00 0.264721E+10 0.00 0.00 0.00 0.33
                   
Annual Sum or Average 1058606.34 0.209967E+12 0.00 55379.37 0.399225E+11 0.00 221619.68 0.00 0.34
Minimum of Months 0.00 0.116501E+11 0.00 0.00 0.220569E+10 0.00 0.00 0.00 0.33
Maximum of Months 1058606.34 0.228308E+11 0.00 55379.37 0.510913E+10 0.00 221619.68 0.00 0.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1636518.50 0.111278E+11 0.00 43153.86 0.207241E+10 0.00 1383163.04 0.00 0.30
February 0.00 0.107474E+11 0.00 0.00 0.235833E+10 0.00 0.00 0.00 0.31
March 0.00 0.143350E+11 0.00 0.00 0.269599E+10 0.00 0.00 0.00 0.33
April 0.00 0.171086E+11 0.00 0.00 0.437105E+10 0.00 0.00 0.00 0.32
May 0.00 0.213075E+11 0.00 0.00 0.524367E+10 0.00 0.00 0.00 0.33
June 0.00 0.215064E+11 0.00 0.00 0.437458E+10 0.00 0.00 0.00 0.32
July 0.00 0.150028E+11 0.00 0.00 0.365679E+10 0.00 0.00 0.00 0.32
August 0.00 0.213239E+11 0.00 0.00 0.355784E+10 0.00 0.00 0.00 0.32
September 0.00 0.184405E+11 0.00 0.00 0.425449E+10 0.00 0.00 0.00 0.32
October 0.00 0.175939E+11 0.00 0.00 0.366268E+10 0.00 0.00 0.00 0.31
November 0.00 0.147758E+11 0.00 0.00 0.295060E+10 0.00 0.00 0.00 0.31
December 0.00 0.117015E+11 0.00 0.00 0.250537E+10 0.00 0.00 0.00 0.30
                   
Annual Sum or Average 1636518.50 0.194971E+12 0.00 43153.86 0.417038E+11 0.00 1383163.04 0.00 0.32
Minimum of Months 0.00 0.107474E+11 0.00 0.00 0.207241E+10 0.00 0.00 0.00 0.30
Maximum of Months 1636518.50 0.215064E+11 0.00 43153.86 0.524367E+10 0.00 1383163.04 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 383590.02 0.107733E+11 0.00 13455.89 0.211650E+10 0.00 91833.85 0.00 0.30
February 0.00 0.104047E+11 0.00 0.00 0.237652E+10 0.00 0.00 0.00 0.31
March 0.00 0.138245E+11 0.00 0.00 0.268836E+10 0.00 0.00 0.00 0.32
April 0.00 0.165756E+11 0.00 0.00 0.449652E+10 0.00 0.00 0.00 0.32
May 0.00 0.207680E+11 0.00 0.00 0.531216E+10 0.00 0.00 0.00 0.33
June 0.00 0.208570E+11 0.00 0.00 0.455478E+10 0.00 0.00 0.00 0.32
July 0.00 0.144754E+11 0.00 0.00 0.376675E+10 0.00 0.00 0.00 0.31
August 0.00 0.206659E+11 0.00 0.00 0.368157E+10 0.00 0.00 0.00 0.32
September 0.00 0.179134E+11 0.00 0.00 0.426218E+10 0.00 0.00 0.00 0.32
October 0.00 0.170409E+11 0.00 0.00 0.378075E+10 0.00 0.00 0.00 0.31
November 0.00 0.143314E+11 0.00 0.00 0.302769E+10 0.00 0.00 0.00 0.31
December 0.00 0.111727E+11 0.00 0.00 0.279529E+10 0.00 0.00 0.00 0.30
                   
Annual Sum or Average 383590.02 0.188803E+12 0.00 13455.89 0.428591E+11 0.00 91833.85 0.00 0.31
Minimum of Months 0.00 0.104047E+11 0.00 0.00 0.211650E+10 0.00 0.00 0.00 0.30
Maximum of Months 383590.02 0.208570E+11 0.00 13455.89 0.531216E+10 0.00 91833.85 0.00 0.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 102242.34 0.308196E+10 0.00 0.00 0.447185E+09 0.00 0.00 0.00 0.38
February 0.00 0.318835E+10 0.00 0.00 0.431521E+09 0.00 0.00 0.00 0.40
March 0.00 0.439986E+10 0.00 0.00 0.449847E+09 0.00 0.00 0.00 0.44
April 0.00 0.572451E+10 0.00 0.00 0.717504E+09 0.00 0.00 0.00 0.46
May 0.00 0.791869E+10 0.00 0.00 0.708005E+09 0.00 0.00 0.00 0.51
June 0.00 0.867761E+10 0.00 0.00 0.485776E+09 0.00 0.00 0.00 0.54
July 0.00 0.535054E+10 0.00 0.00 0.519886E+09 0.00 0.00 0.00 0.47
August 0.00 0.688781E+10 0.00 0.00 0.584366E+09 0.00 0.00 0.00 0.46
September 0.00 0.578577E+10 0.00 0.00 0.694941E+09 0.00 0.00 0.00 0.43
October 0.00 0.513214E+10 0.00 0.00 0.634142E+09 0.00 0.00 0.00 0.40
November 0.00 0.417417E+10 0.00 0.00 0.583495E+09 0.00 0.00 0.00 0.39
December 0.00 0.318142E+10 0.00 0.00 0.568251E+09 0.00 0.00 0.00 0.37
                   
Annual Sum or Average 102242.34 0.635028E+11 0.00 0.00 0.682492E+10 0.00 0.00 0.00 0.44
Minimum of Months 0.00 0.308196E+10 0.00 0.00 0.431521E+09 0.00 0.00 0.00 0.37
Maximum of Months 102242.34 0.867761E+10 0.00 0.00 0.717504E+09 0.00 0.00 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 82422.93 0.257291E+10 0.00 0.00 0.297902E+09 0.00 0.00 0.00 0.50
February 0.00 0.274362E+10 0.00 0.00 0.237125E+09 0.00 0.00 0.00 0.54
March 0.00 0.379460E+10 0.00 0.00 0.300422E+09 0.00 0.00 0.00 0.59
April 0.00 0.484388E+10 0.00 0.00 0.495077E+09 0.00 0.00 0.00 0.61
May 0.00 0.567234E+10 0.00 0.00 0.594782E+09 0.00 0.00 0.00 0.58
June 0.00 0.586406E+10 0.00 0.00 0.464518E+09 0.00 0.00 0.00 0.59
July 0.00 0.366260E+10 0.00 0.00 0.467351E+09 0.00 0.00 0.00 0.53
August 0.00 0.528702E+10 0.00 0.00 0.456371E+09 0.00 0.00 0.00 0.56
September 0.00 0.468272E+10 0.00 0.00 0.477712E+09 0.00 0.00 0.00 0.54
October 0.00 0.410816E+10 0.00 0.00 0.463178E+09 0.00 0.00 0.00 0.50
November 0.00 0.335901E+10 0.00 0.00 0.382321E+09 0.00 0.00 0.00 0.49
December 0.00 0.268696E+10 0.00 0.00 0.329799E+09 0.00 0.00 0.00 0.48
                   
Annual Sum or Average 82422.93 0.492779E+11 0.00 0.00 0.496656E+10 0.00 0.00 0.00 0.54
Minimum of Months 0.00 0.257291E+10 0.00 0.00 0.237125E+09 0.00 0.00 0.00 0.48
Maximum of Months 82422.93 0.586406E+10 0.00 0.00 0.594782E+09 0.00 0.00 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 102237.68 0.466292E+10 0.00 0.00 0.246583E+09 0.00 0.00 0.00 0.54
February 0.00 0.446582E+10 0.00 0.00 0.274802E+09 0.00 0.00 0.00 0.53
March 0.00 0.508600E+10 0.00 0.00 0.389601E+09 0.00 0.00 0.00 0.50
April 0.00 0.560221E+10 0.00 0.00 0.737596E+09 0.00 0.00 0.00 0.45
May 0.00 0.699607E+10 0.00 0.00 0.845987E+09 0.00 0.00 0.00 0.46
June 0.00 0.701261E+10 0.00 0.00 0.675127E+09 0.00 0.00 0.00 0.46
July 0.00 0.459443E+10 0.00 0.00 0.654036E+09 0.00 0.00 0.00 0.42
August 0.00 0.644202E+10 0.00 0.00 0.631234E+09 0.00 0.00 0.00 0.44
September 0.00 0.607373E+10 0.00 0.00 0.672631E+09 0.00 0.00 0.00 0.45
October 0.00 0.615026E+10 0.00 0.00 0.514732E+09 0.00 0.00 0.00 0.46
November 0.00 0.570967E+10 0.00 0.00 0.359938E+09 0.00 0.00 0.00 0.50
December 0.00 0.495060E+10 0.00 0.00 0.297926E+09 0.00 0.00 0.00 0.53
                   
Annual Sum or Average 102237.68 0.677463E+11 0.00 0.00 0.630019E+10 0.00 0.00 0.00 0.48
Minimum of Months 0.00 0.446582E+10 0.00 0.00 0.246583E+09 0.00 0.00 0.00 0.42
Maximum of Months 102237.68 0.701261E+10 0.00 0.00 0.845987E+09 0.00 0.00 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 95063.56 0.255229E+10 0.00 0.00 0.410117E+09 0.00 0.00 0.00 0.52
February 0.00 0.269469E+10 0.00 0.00 0.422746E+09 0.00 0.00 0.00 0.55
March 0.00 0.379212E+10 0.00 0.00 0.418771E+09 0.00 0.00 0.00 0.61
April 0.00 0.472931E+10 0.00 0.00 0.660597E+09 0.00 0.00 0.00 0.61
May 0.00 0.543891E+10 0.00 0.00 0.845737E+09 0.00 0.00 0.00 0.59
June 0.00 0.560474E+10 0.00 0.00 0.669275E+09 0.00 0.00 0.00 0.59
July 0.00 0.353889E+10 0.00 0.00 0.658846E+09 0.00 0.00 0.00 0.54
August 0.00 0.509222E+10 0.00 0.00 0.637977E+09 0.00 0.00 0.00 0.56
September 0.00 0.449470E+10 0.00 0.00 0.687644E+09 0.00 0.00 0.00 0.55
October 0.00 0.392849E+10 0.00 0.00 0.758637E+09 0.00 0.00 0.00 0.52
November 0.00 0.328725E+10 0.00 0.00 0.603982E+09 0.00 0.00 0.00 0.51
December 0.00 0.258271E+10 0.00 0.00 0.567961E+09 0.00 0.00 0.00 0.50
                   
Annual Sum or Average 95063.56 0.477363E+11 0.00 0.00 0.734229E+10 0.00 0.00 0.00 0.55
Minimum of Months 0.00 0.255229E+10 0.00 0.00 0.410117E+09 0.00 0.00 0.00 0.50
Maximum of Months 95063.56 0.560474E+10 0.00 0.00 0.845737E+09 0.00 0.00 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 265520.10 0.257718E+10 0.00 0.00 0.552769E+09 0.00 0.00 0.00 0.34
February 0.00 0.260611E+10 0.00 0.00 0.571835E+09 0.00 0.00 0.00 0.36
March 0.00 0.359212E+10 0.00 0.00 0.625789E+09 0.00 0.00 0.00 0.38
April 0.00 0.468399E+10 0.00 0.00 0.903218E+09 0.00 0.00 0.00 0.40
May 0.00 0.666843E+10 0.00 0.00 0.883683E+09 0.00 0.00 0.00 0.45
June 0.00 0.746149E+10 0.00 0.00 0.559746E+09 0.00 0.00 0.00 0.48
July 0.00 0.462263E+10 0.00 0.00 0.640318E+09 0.00 0.00 0.00 0.42
August 0.00 0.586904E+10 0.00 0.00 0.693739E+09 0.00 0.00 0.00 0.41
September 0.00 0.484512E+10 0.00 0.00 0.901355E+09 0.00 0.00 0.00 0.39
October 0.00 0.417556E+10 0.00 0.00 0.904126E+09 0.00 0.00 0.00 0.36
November 0.00 0.345929E+10 0.00 0.00 0.732470E+09 0.00 0.00 0.00 0.35
December 0.00 0.266837E+10 0.00 0.00 0.638607E+09 0.00 0.00 0.00 0.33
                   
Annual Sum or Average 265520.10 0.532293E+11 0.00 0.00 0.860766E+10 0.00 0.00 0.00 0.39
Minimum of Months 0.00 0.257718E+10 0.00 0.00 0.552769E+09 0.00 0.00 0.00 0.33
Maximum of Months 265520.10 0.746149E+10 0.00 0.00 0.904126E+09 0.00 0.00 0.00 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 197005.80 0.215029E+10 0.00 0.00 0.355395E+09 0.00 0.00 0.00 0.44
February 0.00 0.231409E+10 0.00 0.00 0.290242E+09 0.00 0.00 0.00 0.47
March 0.00 0.324884E+10 0.00 0.00 0.307009E+09 0.00 0.00 0.00 0.51
April 0.00 0.414477E+10 0.00 0.00 0.463740E+09 0.00 0.00 0.00 0.52
May 0.00 0.481943E+10 0.00 0.00 0.615362E+09 0.00 0.00 0.00 0.51
June 0.00 0.500239E+10 0.00 0.00 0.463191E+09 0.00 0.00 0.00 0.51
July 0.00 0.313858E+10 0.00 0.00 0.492903E+09 0.00 0.00 0.00 0.46
August 0.00 0.451862E+10 0.00 0.00 0.443554E+09 0.00 0.00 0.00 0.49
September 0.00 0.402510E+10 0.00 0.00 0.475473E+09 0.00 0.00 0.00 0.48
October 0.00 0.343584E+10 0.00 0.00 0.506134E+09 0.00 0.00 0.00 0.44
November 0.00 0.279606E+10 0.00 0.00 0.437149E+09 0.00 0.00 0.00 0.43
December 0.00 0.224638E+10 0.00 0.00 0.369861E+09 0.00 0.00 0.00 0.42
                   
Annual Sum or Average 197005.80 0.418404E+11 0.00 0.00 0.522001E+10 0.00 0.00 0.00 0.47
Minimum of Months 0.00 0.215029E+10 0.00 0.00 0.290242E+09 0.00 0.00 0.00 0.42
Maximum of Months 197005.80 0.500239E+10 0.00 0.00 0.615362E+09 0.00 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 266049.26 0.439782E+10 0.00 0.00 0.308331E+09 0.00 0.00 0.00 0.52
February 0.00 0.423042E+10 0.00 0.00 0.309223E+09 0.00 0.00 0.00 0.51
March 0.00 0.517268E+10 0.00 0.00 0.429055E+09 0.00 0.00 0.00 0.51
April 0.00 0.572748E+10 0.00 0.00 0.868101E+09 0.00 0.00 0.00 0.47
May 0.00 0.712221E+10 0.00 0.00 0.107539E+10 0.00 0.00 0.00 0.49
June 0.00 0.723047E+10 0.00 0.00 0.831061E+09 0.00 0.00 0.00 0.48
July 0.00 0.456375E+10 0.00 0.00 0.802953E+09 0.00 0.00 0.00 0.43
August 0.00 0.661530E+10 0.00 0.00 0.757555E+09 0.00 0.00 0.00 0.46
September 0.00 0.605594E+10 0.00 0.00 0.820816E+09 0.00 0.00 0.00 0.46
October 0.00 0.601070E+10 0.00 0.00 0.607048E+09 0.00 0.00 0.00 0.47
November 0.00 0.555152E+10 0.00 0.00 0.405270E+09 0.00 0.00 0.00 0.50
December 0.00 0.466237E+10 0.00 0.00 0.317828E+09 0.00 0.00 0.00 0.50
                   
Annual Sum or Average 266049.26 0.673407E+11 0.00 0.00 0.753263E+10 0.00 0.00 0.00 0.48
Minimum of Months 0.00 0.423042E+10 0.00 0.00 0.308331E+09 0.00 0.00 0.00 0.43
Maximum of Months 266049.26 0.723047E+10 0.00 0.00 0.107539E+10 0.00 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 211757.97 0.217287E+10 0.00 0.00 0.376131E+09 0.00 0.00 0.00 0.44
February 0.00 0.230429E+10 0.00 0.00 0.371359E+09 0.00 0.00 0.00 0.47
March 0.00 0.327697E+10 0.00 0.00 0.355913E+09 0.00 0.00 0.00 0.52
April 0.00 0.408988E+10 0.00 0.00 0.533933E+09 0.00 0.00 0.00 0.52
May 0.00 0.467725E+10 0.00 0.00 0.730723E+09 0.00 0.00 0.00 0.51
June 0.00 0.489601E+10 0.00 0.00 0.534784E+09 0.00 0.00 0.00 0.51
July 0.00 0.308532E+10 0.00 0.00 0.554650E+09 0.00 0.00 0.00 0.46
August 0.00 0.440725E+10 0.00 0.00 0.499773E+09 0.00 0.00 0.00 0.48
September 0.00 0.387359E+10 0.00 0.00 0.590681E+09 0.00 0.00 0.00 0.47
October 0.00 0.336522E+10 0.00 0.00 0.597790E+09 0.00 0.00 0.00 0.44
November 0.00 0.277807E+10 0.00 0.00 0.511851E+09 0.00 0.00 0.00 0.43
December 0.00 0.223980E+10 0.00 0.00 0.423155E+09 0.00 0.00 0.00 0.42
                   
Annual Sum or Average 211757.97 0.411665E+11 0.00 0.00 0.608074E+10 0.00 0.00 0.00 0.47
Minimum of Months 0.00 0.217287E+10 0.00 0.00 0.355913E+09 0.00 0.00 0.00 0.42
Maximum of Months 211757.97 0.489601E+10 0.00 0.00 0.730723E+09 0.00 0.00 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 583876.31 0.321307E+10 0.00 0.00 0.446975E+09 0.00 0.00 0.00 0.39
February 0.00 0.326932E+10 0.00 0.00 0.482370E+09 0.00 0.00 0.00 0.41
March 0.00 0.454820E+10 0.00 0.00 0.506403E+09 0.00 0.00 0.00 0.45
April 0.00 0.585549E+10 0.00 0.00 0.779590E+09 0.00 0.00 0.00 0.46
May 0.00 0.813280E+10 0.00 0.00 0.746992E+09 0.00 0.00 0.00 0.51
June 0.00 0.895530E+10 0.00 0.00 0.502250E+09 0.00 0.00 0.00 0.55
July 0.00 0.547102E+10 0.00 0.00 0.584352E+09 0.00 0.00 0.00 0.48
August 0.00 0.706764E+10 0.00 0.00 0.627821E+09 0.00 0.00 0.00 0.46
September 0.00 0.586346E+10 0.00 0.00 0.807638E+09 0.00 0.00 0.00 0.44
October 0.00 0.517316E+10 0.00 0.00 0.746631E+09 0.00 0.00 0.00 0.41
November 0.00 0.428581E+10 0.00 0.00 0.618352E+09 0.00 0.00 0.00 0.40
December 0.00 0.330958E+10 0.00 0.00 0.544379E+09 0.00 0.00 0.00 0.38
                   
Annual Sum or Average 583876.31 0.651449E+11 0.00 0.00 0.739375E+10 0.00 0.00 0.00 0.44
Minimum of Months 0.00 0.321307E+10 0.00 0.00 0.446975E+09 0.00 0.00 0.00 0.38
Maximum of Months 583876.31 0.895530E+10 0.00 0.00 0.807638E+09 0.00 0.00 0.00 0.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 402404.76 0.258639E+10 0.00 314.75 0.321667E+09 0.00 68971.21 0.00 0.50
February 0.00 0.273718E+10 0.00 0.00 0.287562E+09 0.00 0.00 0.00 0.54
March 0.00 0.387927E+10 0.00 0.00 0.317405E+09 0.00 0.00 0.00 0.59
April 0.00 0.493730E+10 0.00 0.00 0.500662E+09 0.00 0.00 0.00 0.60
May 0.00 0.575444E+10 0.00 0.00 0.603697E+09 0.00 0.00 0.00 0.58
June 0.00 0.593713E+10 0.00 0.00 0.483243E+09 0.00 0.00 0.00 0.59
July 0.00 0.367216E+10 0.00 0.00 0.515121E+09 0.00 0.00 0.00 0.52
August 0.00 0.533769E+10 0.00 0.00 0.472298E+09 0.00 0.00 0.00 0.55
September 0.00 0.471003E+10 0.00 0.00 0.517708E+09 0.00 0.00 0.00 0.54
October 0.00 0.411375E+10 0.00 0.00 0.494284E+09 0.00 0.00 0.00 0.50
November 0.00 0.338052E+10 0.00 0.00 0.395481E+09 0.00 0.00 0.00 0.49
December 0.00 0.268984E+10 0.00 0.00 0.350286E+09 0.00 0.00 0.00 0.48
                   
Annual Sum or Average 402404.76 0.497357E+11 0.00 314.75 0.525941E+10 0.00 68971.21 0.00 0.54
Minimum of Months 0.00 0.258639E+10 0.00 0.00 0.287562E+09 0.00 0.00 0.00 0.48
Maximum of Months 402404.76 0.593713E+10 0.00 314.75 0.603697E+09 0.00 68971.21 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 462469.53 0.483327E+10 0.00 1078.50 0.245180E+09 0.00 118445.33 0.00 0.54
February 0.00 0.463597E+10 0.00 0.00 0.280196E+09 0.00 0.00 0.00 0.53
March 0.00 0.531706E+10 0.00 0.00 0.404873E+09 0.00 0.00 0.00 0.51
April 0.00 0.573248E+10 0.00 0.00 0.798659E+09 0.00 0.00 0.00 0.46
May 0.00 0.715576E+10 0.00 0.00 0.899714E+09 0.00 0.00 0.00 0.47
June 0.00 0.718622E+10 0.00 0.00 0.727568E+09 0.00 0.00 0.00 0.46
July 0.00 0.468425E+10 0.00 0.00 0.721687E+09 0.00 0.00 0.00 0.43
August 0.00 0.660305E+10 0.00 0.00 0.679720E+09 0.00 0.00 0.00 0.44
September 0.00 0.620695E+10 0.00 0.00 0.741220E+09 0.00 0.00 0.00 0.45
October 0.00 0.632532E+10 0.00 0.00 0.520057E+09 0.00 0.00 0.00 0.46
November 0.00 0.592774E+10 0.00 0.00 0.335525E+09 0.00 0.00 0.00 0.51
December 0.00 0.513297E+10 0.00 0.00 0.268760E+09 0.00 0.00 0.00 0.53
                   
Annual Sum or Average 462469.53 0.697410E+11 0.00 1078.50 0.662316E+10 0.00 118445.33 0.00 0.48
Minimum of Months 0.00 0.463597E+10 0.00 0.00 0.245180E+09 0.00 0.00 0.00 0.43
Maximum of Months 462469.53 0.718622E+10 0.00 1078.50 0.899714E+09 0.00 118445.33 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 512473.42 0.267591E+10 0.00 0.00 0.345176E+09 0.00 0.00 0.00 0.51
February 0.00 0.281971E+10 0.00 0.00 0.378357E+09 0.00 0.00 0.00 0.55
March 0.00 0.400011E+10 0.00 0.00 0.379344E+09 0.00 0.00 0.00 0.61
April 0.00 0.492902E+10 0.00 0.00 0.609196E+09 0.00 0.00 0.00 0.61
May 0.00 0.567364E+10 0.00 0.00 0.747967E+09 0.00 0.00 0.00 0.59
June 0.00 0.583943E+10 0.00 0.00 0.609506E+09 0.00 0.00 0.00 0.60
July 0.00 0.366526E+10 0.00 0.00 0.607896E+09 0.00 0.00 0.00 0.53
August 0.00 0.531672E+10 0.00 0.00 0.532359E+09 0.00 0.00 0.00 0.56
September 0.00 0.462844E+10 0.00 0.00 0.651331E+09 0.00 0.00 0.00 0.55
October 0.00 0.412704E+10 0.00 0.00 0.604362E+09 0.00 0.00 0.00 0.51
November 0.00 0.343774E+10 0.00 0.00 0.492912E+09 0.00 0.00 0.00 0.50
December 0.00 0.274518E+10 0.00 0.00 0.421912E+09 0.00 0.00 0.00 0.49
                   
Annual Sum or Average 512473.42 0.498582E+11 0.00 0.00 0.638032E+10 0.00 0.00 0.00 0.55
Minimum of Months 0.00 0.267591E+10 0.00 0.00 0.345176E+09 0.00 0.00 0.00 0.49
Maximum of Months 512473.42 0.583943E+10 0.00 0.00 0.747967E+09 0.00 0.00 0.00 0.61



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:27

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.234541E+12 -0.723669E+10 0.00 -0.122049E+12 0.343508E+12
February 0.228548E+12 -0.721397E+10 0.00 -0.122360E+12 0.328887E+12
March 0.292572E+12 -0.113728E+11 0.00 -0.153165E+12 0.401298E+12
April 0.288340E+12 -0.124066E+11 0.00 -0.196526E+12 0.420821E+12
May 0.289776E+12 -0.155620E+11 0.00 -0.239830E+12 0.477725E+12
June 0.300418E+12 -0.153579E+11 0.00 -0.232927E+12 0.480444E+12
July 0.250265E+12 -0.941662E+10 0.00 -0.172920E+12 0.378727E+12
August 0.310975E+12 -0.143447E+11 0.00 -0.217292E+12 0.441511E+12
September 0.246056E+12 -0.111130E+11 0.00 -0.204565E+12 0.404239E+12
October 0.271815E+12 -0.107240E+11 0.00 -0.194665E+12 0.389878E+12
November 0.225314E+12 -0.910894E+10 0.00 -0.163856E+12 0.363539E+12
December 0.221575E+12 -0.682720E+10 0.00 -0.135276E+12 0.335646E+12
           
Annual Sum or Average 0.316020E+13 -0.130684E+12 0.00 -0.215543E+13 0.476622E+13
Minimum of Months 0.221575E+12 -0.155620E+11 0.00 -0.239830E+12 0.328887E+12
Maximum of Months 0.310975E+12 -0.682720E+10 0.00 -0.122049E+12 0.480444E+12