Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2024-07-03 12:20:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1722.04 | 345.64 | 345.64 |
Net Site Energy | 1722.04 | 345.64 | 345.64 |
Total Source Energy | 5453.69 | 1094.64 | 1094.64 |
Net Source Energy | 5453.69 | 1094.64 | 1094.64 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 13.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 417.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1722.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 13.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 417.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 149.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 42.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 13.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 417.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 149.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 42.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 125.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 345.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 125.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 345.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1722.038 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1722.038 | 100.00 |
Total On-Site and Utility Electric Sources | 1722.038 | 100.00 |
Total Electricity End Uses | 1722.038 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 73.67 |
Time Setpoint Not Met During Occupied Cooling | 486.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 959.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:00 | - | - | - | - | - | - | - | - | - | - | - | 01-FEB-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88020.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41659.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26982.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 186009.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 88020.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26982.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2249.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 41.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1323.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 953.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 474.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 134.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5453.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 265.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1094.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 8.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 265.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1094.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.94 | 0.254665 | 0.272000 | 0.800470 | 0.679107 | 0.500000 | 0.001496 |
CORE_MID VAV BOX COMPONENT | 2.41 | 0.310772 | 0.325000 | 0.783767 | 0.828725 | 0.500000 | 0.001226 |
CORE_TOP VAV BOX COMPONENT | 2.64 | 0.284154 | 0.310000 | 0.817625 | 0.757743 | 0.500000 | 0.001341 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.906361 | 0.174314 | 0.200000 | 0.181272 | 0.464838 | 0.500000 | 0.002186 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.805208 | 0.124219 | 0.200000 | 0.161042 | 0.331249 | 0.500000 | 0.003067 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.999850 | 0.158015 | 0.200000 | 0.199970 | 0.421374 | 0.500000 | 0.002411 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.913758 | 0.109455 | 0.200000 | 0.182752 | 0.300000 | 0.500000 | 0.003481 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.758627 | 0.208260 | 0.223000 | 0.169174 | 0.555360 | 0.500000 | 0.001829 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.712579 | 0.140366 | 0.200000 | 0.142516 | 0.374309 | 0.500000 | 0.002714 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.843151 | 0.187382 | 0.200000 | 0.168630 | 0.499686 | 0.500000 | 0.002033 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.754971 | 0.132476 | 0.200000 | 0.150994 | 0.353268 | 0.500000 | 0.002876 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.783779 | 0.201577 | 0.211000 | 0.165377 | 0.537538 | 0.500000 | 0.001890 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.769275 | 0.130021 | 0.200000 | 0.153855 | 0.346722 | 0.500000 | 0.002930 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.877830 | 0.179980 | 0.200000 | 0.175566 | 0.479946 | 0.500000 | 0.002117 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.825051 | 0.121223 | 0.200000 | 0.165010 | 0.323261 | 0.500000 | 0.003143 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24271.05 |
CORE_MID VAV BOX REHEAT COIL | 23764.61 |
CORE_TOP VAV BOX REHEAT COIL | 29782.44 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13229.31 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8702.17 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13299.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8648.53 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8852.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5923.71 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8938.01 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5867.32 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10279.90 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6841.71 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10351.71 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6785.78 |
PACU_VAV_BOT HEATING COIL | 12005.73 |
PACU_VAV_MID HEATING COIL | 13734.69 |
PACU_VAV_TOP HEATING COIL | 12630.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.01 | 1.43 | 6.01 | 1.43 | 5.52 | 5.52 | 0.300000 | 0.259521 | 5.52 |
PACU_VAV_MID | 2.83 | 1.44 | 5.67 | 1.68 | 5.08 | 5.08 | 0.300000 | 0.330438 | 5.08 |
PACU_VAV_TOP | 3.13 | 1.54 | 6.26 | 2.43 | 5.98 | 5.98 | 0.300000 | 0.405942 | 5.98 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.52 |
PACU_VAV_MID_OA_CONTROLLER | 5.08 |
PACU_VAV_TOP_OA_CONTROLLER | 5.98 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.52 | 109531.01 | 0.779549 | 1.84 | 36506.69 | 0.779549 |
PACU_VAV_MID COOLING COIL | 5.08 | 102742.43 | 0.771987 | 1.69 | 34244.05 | 0.771987 |
PACU_VAV_TOP COOLING COIL | 5.98 | 116631.06 | 0.786284 | 1.99 | 38873.13 | 0.786284 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.52 |
PACU_VAV_MID FAN | 5.08 |
PACU_VAV_TOP FAN | 5.98 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.538_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2473E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2895E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8241E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8597E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4210E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4497E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1053 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8618E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1180 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3139E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8200E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1403E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2482E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2962E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8251E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8671E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4221E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4551E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8852E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7971E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5899E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5722E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7472E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3693E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4346E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4511E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1985E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2104E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0304E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0346E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9581E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9955E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4875E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5174E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1737E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1953E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7526E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5651E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1291E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1968E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9540E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2688E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9578E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9955E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4870E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5164E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1727E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1916E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2344E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4945E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7944E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2014E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1578E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0995E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0185E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0582E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6866E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7282E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6698E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6889E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1056 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9855E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1165 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5225E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3451E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0194E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7289E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7070E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4516E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4922E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6374E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3036E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1544E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0597E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4880E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6246E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3114E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2193E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0980E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4184E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6807E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1388E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0652E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0456E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1056 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9849E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1165 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5217E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3446E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0189E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7288E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7068E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4514E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4920E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6371E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3033E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1544E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0596E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4880E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6245E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3112E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2192E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0980E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4182E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6806E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1386E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0649E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0454E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37075.80346 | 37075.80346 | 2.94290 | 2.94290 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 4300.67434 | 4300.67434 | 0.20033 | 0.42469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30405.57006 | 30405.57006 | 2.41159 | 2.41159 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11797.46026 | 11797.46026 | 0.54914 | 0.54914 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32955.66775 | 32955.66775 | 2.63750 | 2.63750 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 40.26800 | 5.63027E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 20993.47261 | 20993.47261 | 0.98224 | 0.98224 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 11325.46469 | 11325.46469 | 0.90636 | 0.90636 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9294.73468 | 9294.73468 | 0.43631 | 0.43631 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10061.55696 | 10061.55696 | 0.80521 | 0.80521 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6113.31710 | 6113.31710 | 0.28700 | 0.28700 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12493.67167 | 12493.67167 | 0.99985 | 0.99985 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9343.54432 | 9343.54432 | 0.43861 | 0.43861 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11417.95775 | 11417.95775 | 0.91376 | 0.91376 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6075.75474 | 6075.75474 | 0.28523 | 0.28523 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 9479.32713 | 9479.32713 | 0.75863 | 0.75863 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6227.45282 | 6227.45282 | 0.29194 | 0.29194 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8903.98309 | 8903.98309 | 0.71258 | 0.71258 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 36.41100 | 5.62429E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4166.55785 | 4166.55785 | 0.19537 | 0.19537 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10535.49225 | 10535.49225 | 0.84315 | 0.84315 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6287.68933 | 6287.68933 | 0.29478 | 0.29478 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9433.69870 | 9433.69870 | 0.75497 | 0.75497 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4127.02615 | 4127.02615 | 0.19351 | 0.19351 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9793.68250 | 9793.68250 | 0.78378 | 0.78378 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7228.69903 | 7228.69903 | 0.33904 | 0.33904 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9612.50899 | 9612.50899 | 0.76928 | 0.76928 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4810.08390 | 4810.08390 | 0.22564 | 0.22564 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10968.90576 | 10968.90576 | 0.87783 | 0.87783 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7278.99081 | 7278.99081 | 0.34140 | 0.34140 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10309.46670 | 10309.46670 | 0.82505 | 0.82505 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4770.91141 | 4770.91141 | 0.22380 | 0.22380 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 89781.06 | 5.51703 | 5.51703 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 16141.59 | 1.40029 | 1.40029 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 16:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 84186.36 | 5.08120 | 5.08120 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 16073.24 | 1.67902 | 1.67902 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 95087.86 | 5.98456 | 5.98456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 16060.29 | 2.42939 | 2.42939 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.94290 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25467 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80047 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67911 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49608E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24271.05079 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.41159 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31077 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32500 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78377 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82872 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22598E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23764.61286 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63750 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28415 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81762 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75774 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34082E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29782.44206 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90636 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17431 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18127 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46484 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18571E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13229.31188 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80521 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12422 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16104 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33125 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06717E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8702.16905 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99985 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15802 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19997 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42137 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41116E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13299.01133 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91376 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10945 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18275 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48089E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8648.53457 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75863 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20826 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16917 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55536 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82944E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8852.05623 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71258 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14037 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14252 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37431 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71433E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5923.71340 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84315 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18738 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16863 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49969 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03328E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8938.00636 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75497 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13248 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15099 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35327 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87600E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5867.32329 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78378 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20158 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16538 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53754 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89010E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10279.90123 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76928 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13002 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15386 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34672 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93030E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6841.71267 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87783 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17998 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17557 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47995 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11690E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10351.71413 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82505 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12122 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16501 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32326 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14297E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6785.78009 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.00612 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.43178 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.01223 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.43178 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51703 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.51703 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25952 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.83376 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44358 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.66753 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67902 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.08120 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.08120 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33044 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.13134 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54266 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.26268 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.42939 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.98456 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.98456 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.40594 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.51703 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.08120 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.98456 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51703 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.51703 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 109531.01401 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77955 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.83882 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36506.68697 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77955 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 12005.72904 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.51703 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.08120 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.08120 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102742.43368 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77199 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.69356 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34244.05315 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77199 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 13734.68764 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.08120 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.98456 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.98456 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116631.06237 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78628 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.99465 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38873.13309 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78628 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 12630.32506 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.98456 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 108496.69 | 370206.07 | 12.23 | 3.10 | 3.50 | 3.68 | 3.87 | 10.59 | 11.95 | 12.57 | 13.22 | 5.7930 | 4.6297 | 3.1187 | 1.2572 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 101844.82 | 347508.95 | 12.27 | 3.11 | 3.51 | 3.70 | 3.88 | 10.62 | 11.99 | 12.62 | 13.25 | 5.3354 | 4.2603 | 2.8690 | 1.1650 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 115444.70 | 393913.66 | 12.19 | 3.09 | 3.49 | 3.67 | 3.87 | 10.56 | 11.90 | 12.53 | 13.19 | 6.2839 | 5.0211 | 3.3813 | 1.3575 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.2482492268E-002 | 0.1393643788 | Pass | Pass | 6.3671050466E-002 | 0.2407349045 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1073015306 | 7.1210177191E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.7420671619E-002 | 3.0442875897E-002 | Pass | Pass | 5.5283229726E-002 | 0.3161195745 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4336566934E-002 | 2.5602369952E-002 | Pass | Pass | 0.1176018448 | 0.4503916928 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.2631500259E-002 | 7.9638277302E-002 | Pass | Pass | 2.0756648088E-002 | 0.1397017659 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.5194379396E-002 | 1.7544806827E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4837173890E-002 | 2.8258481187E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.8656116946E-002 | 7.8797119263E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1390794089 | 0.1001498198 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1222856400 | 0.1045709766 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.7614780576E-002 | 7.0271075990E-002 | Pass | Pass | 6.3323206467E-002 | 0.2399790103 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.8335964912E-002 | 0.1230321103 | Pass | Pass | 6.4089865970E-002 | 0.2420551107 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1290213617 | 0.1446017729 | Pass | Pass | 6.2683746223E-002 | 0.2411335941 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1083021476 | 0.1520665423 | Pass | Pass | 6.0902090004E-002 | 0.2329345587 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9357867563E-002 | 5.2462916471E-002 | Pass | Pass | 2.0992566304E-002 | 0.1375104490 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2129251382E-002 | 0.1147278150 | Pass | Pass | 2.0669757408E-002 | 0.1407479264 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1435743492 | 0.1286645322 | Pass | Pass | 3.7894921409E-002 | 0.2210733242 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1152251533 | 0.1455341923 | Pass | Pass | 1.9985133704E-002 | 0.1344353676 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2871.01 | 10.77 | 0.00 | 1186.91 | 2004.59 | 6073.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.538_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.538_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.538_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 3.059 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.25 | 0.0000 | Y | 8.89 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 5.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.25 | 0.0000 | Y | 8.55 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.94 | 0.0000 | Y | 5.56 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.13 | 0.0000 | Y | 8.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.47 | 0.0000 | Y | 5.46 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.20 | 0.0000 | Y | 8.53 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 5.54 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.25 | 0.0000 | Y | 8.89 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 5.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.25 | 0.0000 | Y | 8.55 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.94 | 0.0000 | Y | 5.56 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.79 | 41.79 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.79 | 62.79 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.79 | 47.06 | 41.65 | |
Exterior Lighting Total | 5686.19 | 50.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 109531.01 | 85384.79 | 24146.22 | 0.78 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102742.43 | 79315.85 | 23426.58 | 0.77 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116631.06 | 91705.17 | 24925.90 | 0.79 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 108496.7 | 3.10 | 10.59 | N/A | N/A | 12.23 | |
PACU_VAV_MID COOLING COIL | 101844.8 | 3.11 | 10.62 | N/A | N/A | 12.27 | |
PACU_VAV_TOP COOLING COIL | 115444.7 | 3.09 | 10.56 | N/A | N/A | 12.19 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24271.05 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23764.61 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 29782.44 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13229.31 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8702.17 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13299.01 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8648.53 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8852.06 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5923.71 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8938.01 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5867.32 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10279.90 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6841.71 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10351.71 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6785.78 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 12005.73 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 13734.69 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 12630.33 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.52 | 11998.92 | 2174.89 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.08 | 11051.04 | 2174.89 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.98 | 13015.75 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 108496.69 | 3.10 | 10.59 | 12.23 | 5.7930 | 3.50 | 11.95 | 4.6297 | 3.68 | 12.57 | 3.1187 | 3.87 | 13.22 | 1.2572 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101844.82 | 3.11 | 10.62 | 12.27 | 5.3354 | 3.51 | 11.99 | 4.2603 | 3.70 | 12.62 | 2.8690 | 3.88 | 13.25 | 1.1650 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115444.70 | 3.09 | 10.56 | 12.19 | 6.2839 | 3.49 | 11.90 | 5.0211 | 3.67 | 12.53 | 3.3813 | 3.87 | 13.19 | 1.3575 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37075.80 | 37075.80 | 37.70 | 2.943 | 2.943 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_MID | 30405.57 | 30405.57 | 30.91 | 2.412 | 2.412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 30.96 | 0.00562 | 0.425 | 0.00 |
CORE_TOP | 32955.67 | 32955.67 | 33.51 | 2.637 | 2.637 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00886 | 40.27 | 0.00563 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11325.46 | 11325.46 | 54.62 | 0.906 | 0.906 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00867 | 40.53 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10061.56 | 10061.56 | 76.65 | 0.805 | 0.805 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00862 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12493.67 | 12493.67 | 60.26 | 1.000 | 1.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00866 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11417.96 | 11417.96 | 86.99 | 0.914 | 0.914 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 38.94 | 0.00563 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9479.33 | 9479.33 | 45.72 | 0.759 | 0.759 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00873 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8903.98 | 8903.98 | 67.83 | 0.713 | 0.713 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00866 | 36.41 | 0.00562 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10535.49 | 10535.49 | 50.81 | 0.843 | 0.843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00871 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9433.70 | 9433.70 | 71.87 | 0.755 | 0.755 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 38.72 | 0.00563 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9793.68 | 9793.68 | 47.24 | 0.784 | 0.784 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00871 | 40.67 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9612.51 | 9612.51 | 73.23 | 0.769 | 0.769 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00863 | 35.75 | 0.00562 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10968.91 | 10968.91 | 52.90 | 0.878 | 0.878 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00869 | 40.80 | 0.00563 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10309.47 | 10309.47 | 78.55 | 0.825 | 0.825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 38.94 | 0.00563 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 4300.67 | 4300.67 | 4.37 | 0.200 | 0.425 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_MID | 11797.46 | 11797.46 | 11.99 | 0.549 | 0.549 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
CORE_TOP | 20993.47 | 20993.47 | 21.34 | 0.982 | 0.982 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9294.73 | 9294.73 | 44.83 | 0.436 | 0.436 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6113.32 | 6113.32 | 46.57 | 0.287 | 0.287 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9343.54 | 9343.54 | 45.06 | 0.439 | 0.439 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6075.75 | 6075.75 | 46.29 | 0.285 | 0.285 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6227.45 | 6227.45 | 30.04 | 0.292 | 0.292 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4166.56 | 4166.56 | 31.74 | 0.195 | 0.195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6287.69 | 6287.69 | 30.33 | 0.295 | 0.295 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4127.03 | 4127.03 | 31.44 | 0.194 | 0.194 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7228.70 | 7228.70 | 34.86 | 0.339 | 0.339 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4810.08 | 4810.08 | 36.64 | 0.226 | 0.226 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7278.99 | 7278.99 | 35.11 | 0.341 | 0.341 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4770.91 | 4770.91 | 36.35 | 0.224 | 0.224 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.52 | 5.52 | 1.40 | 1.40 | 5.5170 | 1.4318 | 5.5170 | 0.2595 | 0.3000 |
PACU_VAV_MID | 5.08 | 5.08 | 1.68 | 1.68 | 5.0812 | 1.6790 | 5.0812 | 0.3304 | 0.3000 |
PACU_VAV_TOP | 5.98 | 5.98 | 2.43 | 2.43 | 5.9846 | 2.4294 | 5.9846 | 0.4059 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24271.051 | 24271.051 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24271.05 | 12877.06 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00799998 | 46.9511 | 4300.67 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23764.613 | 23764.613 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23764.61 | 16650.44 | 0.549139 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 11797.46 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 29782.442 | 29782.442 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29782.44 | 29782.44 | 0.982238 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 20993.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13229.312 | 13229.312 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13229.31 | 13229.31 | 0.436308 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792854 | 46.5380 | 9294.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8702.169 | 8702.169 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8702.17 | 8702.17 | 0.287001 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792911 | 46.5413 | 6113.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13299.011 | 13299.011 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13299.01 | 13299.01 | 0.438607 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792916 | 46.5416 | 9343.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8648.535 | 8648.535 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8648.53 | 8648.53 | 0.285232 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792844 | 46.5374 | 6075.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8852.056 | 8852.056 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8852.06 | 8852.06 | 0.291945 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789502 | 46.3439 | 6227.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5923.713 | 5923.713 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5923.71 | 5923.71 | 0.195367 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790236 | 46.3864 | 4166.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8938.006 | 8938.006 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8938.01 | 8938.01 | 0.294779 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789738 | 46.3576 | 6287.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5867.323 | 5867.323 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5867.32 | 5867.32 | 0.193507 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790016 | 46.3737 | 4127.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10279.901 | 10279.901 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10279.90 | 10279.90 | 0.339036 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789536 | 46.3460 | 7228.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6841.713 | 6841.713 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6841.71 | 6841.71 | 0.225643 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790071 | 46.3769 | 4810.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10351.714 | 10351.714 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10351.71 | 10351.71 | 0.341404 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789690 | 46.3548 | 7278.99 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6785.780 | 6785.780 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6785.78 | 6785.78 | 0.223798 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789907 | 46.3674 | 4770.91 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 109531.014 | 85384.790 | 5.517026 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 99857.92 | 99857.92 | 5.517026 | 27.65 | 16.31 | 0.00809563 | 10.85 | 10.03 | 0.00809563 | 40.80 | 0.00563111 | 18.58 | 21.6633 | 24.00 | 0.00877907 | 42.8873 | 68786.48 | 0.00 | 112941.18 | 82691.86 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 12005.729 | 12005.729 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 16:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12005.73 | 12005.73 | 1.655108 | 6.20 | 4.83 | 0.00532803 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 72.2110 | 21.00 | 0.00794556 | 46.6361 | 19100.89 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 102742.434 | 79315.854 | 5.081197 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 93668.87 | 93668.87 | 5.081197 | 27.97 | 16.37 | 0.00804620 | 10.85 | 9.98 | 0.00804620 | 40.80 | 0.00563111 | 18.58 | 23.5214 | 24.00 | 0.00879494 | 42.9636 | 63103.98 | 0.00 | 105941.24 | 76898.12 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 13734.688 | 13734.688 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13734.69 | 13734.69 | 1.524359 | 4.60 | 3.70 | 0.00507087 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 78.4047 | 19.60 | 0.00777155 | 49.7526 | 22436.78 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 116631.062 | 91705.167 | 5.984562 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 106489.89 | 106489.88 | 5.984562 | 27.35 | 16.23 | 0.00812052 | 10.85 | 10.05 | 0.00812052 | 40.67 | 0.00563090 | 18.54 | 19.9709 | 24.00 | 0.00874624 | 42.7288 | 74354.12 | 0.00 | 120262.28 | 88734.85 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 12630.325 | 12630.325 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12630.33 | 12630.33 | 1.795369 | 6.40 | 5.14 | 0.00550457 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 66.5696 | 19.60 | 0.00785137 | 50.2557 | 25308.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24271.051 | 24271.051 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24271.05 | 12877.06 | 1.0000 | 0.46426985 | 0.424691 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24271.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.74 | 0.00799998 | 21.00 | 0.00799998 | 46.9511 | 4300.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23764.613 | 23764.613 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23764.61 | 16650.44 | 1.0000 | 0.60031520 | 0.549139 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23764.61 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 11797.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 29782.442 | 29782.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29782.44 | 29782.44 | 1.0000 | 1.07377686 | 0.982238 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29782.44 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 20993.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13229.312 | 13229.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13229.31 | 13229.31 | 1.0000 | 0.47696992 | 0.436308 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13229.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792854 | 21.00 | 0.00792854 | 46.5380 | 9294.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8702.169 | 8702.169 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8702.17 | 8702.17 | 1.0000 | 0.31374821 | 0.287001 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8702.17 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792911 | 21.00 | 0.00792911 | 46.5413 | 6113.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13299.011 | 13299.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13299.01 | 13299.01 | 1.0000 | 0.47948287 | 0.438607 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13299.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792916 | 21.00 | 0.00792916 | 46.5416 | 9343.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8648.535 | 8648.535 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8648.53 | 8648.53 | 1.0000 | 0.31181447 | 0.285232 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8648.53 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792844 | 21.00 | 0.00792844 | 46.5374 | 6075.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8852.056 | 8852.056 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8852.06 | 8852.06 | 1.0000 | 0.31915224 | 0.291945 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8852.06 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00789502 | 21.00 | 0.00789502 | 46.3439 | 6227.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5923.713 | 5923.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5923.71 | 5923.71 | 1.0000 | 0.21357370 | 0.195367 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5923.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00790236 | 21.00 | 0.00790236 | 46.3864 | 4166.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8938.006 | 8938.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8938.01 | 8938.01 | 1.0000 | 0.32225109 | 0.294779 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8938.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00789738 | 21.00 | 0.00789738 | 46.3576 | 6287.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5867.323 | 5867.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5867.32 | 5867.32 | 1.0000 | 0.21154061 | 0.193507 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5867.32 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00790016 | 21.00 | 0.00790016 | 46.3737 | 4127.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10279.901 | 10279.901 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10279.90 | 10279.90 | 1.0000 | 0.37063180 | 0.339036 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10279.90 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789536 | 21.00 | 0.00789536 | 46.3460 | 7228.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6841.713 | 6841.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6841.71 | 6841.71 | 1.0000 | 0.24667127 | 0.225643 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6841.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00790071 | 21.00 | 0.00790071 | 46.3769 | 4810.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10351.714 | 10351.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10351.71 | 10351.71 | 1.0000 | 0.37322094 | 0.341404 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10351.71 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789690 | 21.00 | 0.00789690 | 46.3548 | 7278.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6785.780 | 6785.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6785.78 | 6785.78 | 1.0000 | 0.24465467 | 0.223798 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6785.78 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789907 | 21.00 | 0.00789907 | 46.3674 | 4770.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 109531.014 | 85384.790 | 5.517026 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8894 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.517026 | 6.03118093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 99857.92 | 99857.92 | 0.9117 | 6.03118093 | 5.517026 | 27.65 | 16.31 | 0.00809563 | 48443.0 | 10.85 | 10.03 | 0.00809563 | 31311.8 | -999.0 | -999.00 | -999.00 | -999.00 | 11998.916 | 87859.01 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 21.6633 | 24.00 | 0.00877907 | 24.00 | 0.00877907 | 42.8873 | 68786.48 | 0.00 | 112941.18 | 82691.86 | 5.79299487 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.70 | 12.69 | 0.00913735 | 35826.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12005.729 | 12005.729 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.517026 | 6.03118093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 16:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12005.73 | 12005.73 | 1.0000 | 1.80935428 | 1.655108 | 6.20 | 4.83 | 0.00532803 | 19613.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12005.73 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 72.2110 | 21.00 | 0.00795890 | 21.00 | 0.00794556 | 46.6361 | 19100.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102742.434 | 79315.854 | 5.081197 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7975 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.081197 | 5.55473568 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 93668.87 | 93668.87 | 0.9117 | 5.55473568 | 5.081197 | 27.97 | 16.37 | 0.00804620 | 48651.9 | 10.85 | 9.98 | 0.00804620 | 31187.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11051.037 | 82617.83 | 40.80 | 0.00563111 | 18.58 | 1.19517000 | 23.5214 | 24.00 | 0.00879494 | 24.00 | 0.00879494 | 42.9636 | 63103.98 | 0.00 | 105941.24 | 76898.12 | 5.33536561 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.56 | 12.55 | 0.00905038 | 35466.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13734.688 | 13734.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.081197 | 5.55473568 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13734.69 | 13734.69 | 1.0000 | 1.66642070 | 1.524359 | 4.60 | 3.70 | 0.00507087 | 17345.4 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13734.69 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 78.4047 | 19.48 | 0.00781307 | 19.60 | 0.00777155 | 49.7526 | 22436.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116631.062 | 91705.167 | 5.984562 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9356 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.984562 | 6.54228839 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 106489.89 | 106489.88 | 0.9130 | 6.54228839 | 5.984562 | 27.35 | 16.23 | 0.00812052 | 48200.8 | 10.85 | 10.05 | 0.00812052 | 31374.6 | -999.0 | -999.00 | -999.00 | -999.00 | 13015.754 | 93474.13 | 40.67 | 0.00563090 | 18.54 | 1.19517000 | 19.9709 | 24.00 | 0.00874624 | 24.00 | 0.00874624 | 42.7288 | 74354.12 | 0.00 | 120262.28 | 88734.85 | 6.28391746 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.85 | 12.83 | 0.00921754 | 36184.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12630.325 | 12630.325 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.984562 | 6.54228839 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12630.33 | 12630.33 | 1.0000 | 1.96268652 | 1.795369 | 6.40 | 5.14 | 0.00550457 | 20258.9 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12630.33 | 0.50 | 0.00431558 | 0.50 | 1.19517000 | 66.5696 | 18.14 | 0.00787218 | 19.60 | 0.00785137 | 50.2557 | 25308.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.52 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.08 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.98 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2266.50 | 884.83 | 2.83 |
CORE_MID | 1677.33 | 2314.50 | 13.17 |
CORE_TOP | 1706.33 | 2726.17 | 80.50 |
PERIMETER_TOP_ZN_3 | 2462.17 | 3044.67 | 591.00 |
PERIMETER_TOP_ZN_2 | 2852.33 | 2608.17 | 523.83 |
PERIMETER_TOP_ZN_1 | 2940.33 | 2095.83 | 423.83 |
PERIMETER_TOP_ZN_4 | 2795.17 | 2804.50 | 625.50 |
PERIMETER_BOT_ZN_3 | 1942.83 | 2987.17 | 155.50 |
PERIMETER_BOT_ZN_2 | 2566.00 | 2295.67 | 196.83 |
PERIMETER_BOT_ZN_1 | 2667.50 | 1959.67 | 279.33 |
PERIMETER_BOT_ZN_4 | 2461.50 | 2451.00 | 187.33 |
PERIMETER_MID_ZN_3 | 2080.17 | 2848.67 | 226.17 |
PERIMETER_MID_ZN_2 | 2199.50 | 2137.33 | 284.67 |
PERIMETER_MID_ZN_1 | 2783.00 | 1808.00 | 218.83 |
PERIMETER_MID_ZN_4 | 2528.83 | 2564.50 | 302.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4312.50 | 3632.67 | 959.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 37.83 | 0.17 | 23.67 |
PERIMETER_TOP_ZN_2 | 0.17 | 72.50 | 0.17 | 63.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 70.50 | 0.00 | 57.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 61.83 | 0.00 | 34.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 9.83 | 0.00 | 5.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 56.67 | 0.00 | 50.83 |
PERIMETER_BOT_ZN_1 | 73.50 | 329.83 | 73.50 | 323.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 51.17 | 0.00 | 28.00 |
PERIMETER_MID_ZN_3 | 0.00 | 20.00 | 0.00 | 12.33 |
PERIMETER_MID_ZN_2 | 0.00 | 60.00 | 0.00 | 55.83 |
PERIMETER_MID_ZN_1 | 0.00 | 62.67 | 0.00 | 55.67 |
PERIMETER_MID_ZN_4 | 0.00 | 52.83 | 0.00 | 30.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 73.67 | 540.00 | 73.67 | 486.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.989 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.667 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.638 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.731 | 0.030 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.152 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.246 | 0.030 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.189 | 0.032 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.675 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.085 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.115 | 1.259 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.028 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.720 | 0.025 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.108 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.232 | 0.025 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.145 | 0.027 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15707590.51 | 0.00 | 15707590.51 | 0.00 | 15707590.51 | 13393058.27 | 5799.25 | 57.25 | 2903.49 | 52.39 |
CORE_MID | 10547260.38 | 0.00 | 10547260.38 | 0.00 | 10547260.38 | 13393058.27 | 6393.34 | 17.27 | 2349.39 | 20.87 |
CORE_TOP | 10098233.77 | 0.00 | 10098233.77 | 0.00 | 10098233.77 | 13393058.27 | 6453.16 | 12.81 | 2294.04 | 20.34 |
PERIMETER_TOP_ZN_3 | 2439125.18 | 0.00 | 2439125.18 | 200996.66 | 2640121.84 | 2823374.22 | 4385.73 | 196.19 | 4178.08 | 20.34 |
PERIMETER_TOP_ZN_2 | 2431472.77 | 0.00 | 2431472.77 | 133996.97 | 2565469.74 | 1787429.43 | 4082.07 | 4.83 | 4673.10 | 20.34 |
PERIMETER_TOP_ZN_1 | 4150183.55 | 0.00 | 4150183.55 | 200996.66 | 4351180.20 | 2823374.22 | 4211.72 | 26.08 | 4522.20 | 20.34 |
PERIMETER_TOP_ZN_4 | 2514706.41 | 0.00 | 2514706.41 | 133996.97 | 2648703.38 | 1787312.18 | 4203.90 | 33.51 | 4522.59 | 20.34 |
PERIMETER_BOT_ZN_3 | 2272361.86 | 0.00 | 2272361.86 | 106869.55 | 2379231.42 | 2823374.22 | 5284.37 | 116.87 | 3358.76 | 52.39 |
PERIMETER_BOT_ZN_2 | 2305835.84 | 0.00 | 2305835.84 | 71245.94 | 2377081.78 | 1787429.43 | 4055.89 | 21.45 | 4682.66 | 52.39 |
PERIMETER_BOT_ZN_1 | 3732674.54 | 0.00 | 3732674.54 | 4230731.89 | 7963406.43 | 2823374.22 | 4252.11 | 34.73 | 4473.16 | 52.39 |
PERIMETER_BOT_ZN_4 | 2189094.66 | 0.00 | 2189094.66 | 71245.94 | 2260340.60 | 1787312.18 | 4353.60 | 64.13 | 4342.27 | 52.39 |
PERIMETER_MID_ZN_3 | 2401180.84 | 0.00 | 2401180.84 | 167314.83 | 2568495.67 | 2823374.22 | 4493.12 | 57.30 | 4209.58 | 20.87 |
PERIMETER_MID_ZN_2 | 2477870.50 | 0.00 | 2477870.50 | 111542.55 | 2589413.04 | 1787429.43 | 4062.60 | 8.76 | 4688.64 | 929.87 |
PERIMETER_MID_ZN_1 | 4100106.23 | 0.00 | 4100106.23 | 167314.83 | 4267421.06 | 2823374.22 | 4155.51 | 27.96 | 4576.54 | 20.87 |
PERIMETER_MID_ZN_4 | 2417196.86 | 0.00 | 2417196.86 | 111542.55 | 2528739.41 | 1787312.18 | 4154.28 | 35.71 | 4570.01 | 20.87 |
Total Facility | 69784893.90 | 0.00 | 69784893.90 | 5707795.32 | 75492689.22 | 67843644.98 | 6601.90 | 558.90 | 4836.39 | 970.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7262 | 0.0000 | 0.7262 | 0.0000 | 0.7262 | 0.4247 | 3034.65 | 57.25 | 2851.10 |
CORE_MID | 0.4900 | 0.0000 | 0.4900 | 0.0000 | 0.4900 | 0.4247 | 3597.20 | 17.27 | 2328.53 |
CORE_TOP | 0.4691 | 0.0000 | 0.4691 | 0.0000 | 0.4691 | 0.4247 | 3655.50 | 12.81 | 2274.69 |
PERIMETER_TOP_ZN_3 | 0.1134 | 0.0000 | 0.1134 | 0.0047 | 0.1181 | 0.0895 | 1588.07 | 196.19 | 4158.74 |
PERIMETER_TOP_ZN_2 | 0.1131 | 0.0000 | 0.1131 | 0.0031 | 0.1162 | 0.0567 | 1284.41 | 4.83 | 4653.76 |
PERIMETER_TOP_ZN_1 | 0.1933 | 0.0000 | 0.1933 | 0.0047 | 0.1980 | 0.0895 | 1414.07 | 26.08 | 4502.86 |
PERIMETER_TOP_ZN_4 | 0.1169 | 0.0000 | 0.1169 | 0.0031 | 0.1200 | 0.0567 | 1406.24 | 33.51 | 4503.25 |
PERIMETER_BOT_ZN_3 | 0.1047 | 0.0000 | 0.1047 | 0.0025 | 0.1072 | 0.0895 | 2519.76 | 116.87 | 3306.36 |
PERIMETER_BOT_ZN_2 | 0.1065 | 0.0000 | 0.1065 | 0.0017 | 0.1081 | 0.0567 | 1291.28 | 21.45 | 4630.27 |
PERIMETER_BOT_ZN_1 | 0.1728 | 0.0000 | 0.1728 | 0.1952 | 0.3681 | 0.0895 | 1487.50 | 34.73 | 4420.77 |
PERIMETER_BOT_ZN_4 | 0.1009 | 0.0000 | 0.1009 | 0.0017 | 0.1026 | 0.0567 | 1588.99 | 64.13 | 4289.87 |
PERIMETER_MID_ZN_3 | 0.1116 | 0.0000 | 0.1116 | 0.0039 | 0.1155 | 0.0895 | 1696.99 | 57.30 | 4188.71 |
PERIMETER_MID_ZN_2 | 0.1087 | 0.0000 | 0.1087 | 0.0028 | 0.1115 | 0.0567 | 1257.80 | 6.92 | 3769.27 |
PERIMETER_MID_ZN_1 | 0.1910 | 0.0000 | 0.1910 | 0.0039 | 0.1949 | 0.0895 | 1359.37 | 27.96 | 4555.67 |
PERIMETER_MID_ZN_4 | 0.1124 | 0.0000 | 0.1124 | 0.0026 | 0.1150 | 0.0567 | 1358.14 | 35.71 | 4549.14 |
Total Facility | 3.2305 | 0.0000 | 3.2305 | 0.2300 | 3.4605 | 2.1513 | 3796.22 | 558.90 | 4775.87 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31319956.52 | 0.00 | 31319956.52 | 22614548.33 | 3983.03 | 1.77 | 4775.20 | 52.39 |
PACU_VAV_MID | 26224238.07 | 0.00 | 26224238.07 | 22614548.33 | 4038.57 | 0.50 | 4720.93 | 20.87 |
PACU_VAV_TOP | 25853889.06 | 0.00 | 25853889.06 | 22614548.33 | 4088.91 | 4.17 | 4666.92 | 20.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4474 | 0.0000 | 1.4474 | 0.7171 | 1218.43 | 1.77 | 4722.80 |
PACU_VAV_MID | 1.2191 | 0.0000 | 1.2191 | 0.7171 | 1242.44 | 0.50 | 4700.06 |
PACU_VAV_TOP | 1.2020 | 0.0000 | 1.2020 | 0.7171 | 1291.25 | 4.17 | 4647.58 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.26 | 2588.41 | 0.00 | 0.00 | 0.00 | 2199.69 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.03 | 2443.29 | 0.00 | 0.00 | 0.00 | 2293.18 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2415.22 | 0.00 | 0.00 | 0.00 | 2306.62 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5885 | 0.0000 | 0.0000 | 0.0000 | 0.9264 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.0928 | 0.0000 | 0.0000 | 0.0000 | 0.9493 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.0823 | 0.0000 | 0.0000 | 0.0000 | 0.9359 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
Electricity:Building | 1020.80 | 13465.67 | 29-MAY-17:20 | 74313.01 | 20-JAN-17:00 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1020.80 | 13465.67 | 29-MAY-17:20 | 74313.01 | 20-JAN-17:00 |
InteriorLights:Electricity | 301.11 | 987.92 | 29-MAY-17:20 | 32642.50 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.11 | 987.92 | 29-MAY-17:20 | 32642.50 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity | 301.11 | 987.92 | 29-MAY-17:20 | 32642.50 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.11 | 987.92 | 29-MAY-17:20 | 32642.50 | 20-JAN-17:00 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.22 | 422.10 | 02-APR-17:10 | 2793.69 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.89 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.89 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.88 | 267.21 | 16-APR-17:10 | 1768.58 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.88 | 422.10 | 02-APR-17:10 | 2793.68 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.55 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.96 | 267.21 | 12-MAR-17:10 | 1768.52 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.56 | 22.79 | 01-JAN-10:20 | 859.95 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.56 | 22.79 | 01-JAN-10:20 | 859.95 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.18 | 422.10 | 02-APR-17:10 | 2793.69 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.85 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.85 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 267.21 | 16-APR-17:10 | 1768.58 | 20-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.87 | 422.10 | 02-APR-17:10 | 2793.68 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.53 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.95 | 267.21 | 12-MAR-17:10 | 1768.52 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.54 | 22.79 | 01-JAN-10:10 | 859.95 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.54 | 22.79 | 01-JAN-10:10 | 859.95 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.22 | 422.10 | 02-APR-17:10 | 2793.69 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.89 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.89 | 36.00 | 01-JAN-10:20 | 1358.45 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.88 | 267.21 | 16-APR-17:10 | 1768.58 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-08:00 | 860.01 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.88 | 422.10 | 02-APR-17:10 | 2793.68 | 20-JAN-08:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.55 | 36.00 | 01-JAN-08:00 | 1358.45 | 20-JAN-08:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.96 | 267.21 | 12-MAR-17:10 | 1768.52 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.56 | 22.79 | 01-JAN-10:20 | 859.95 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.56 | 22.79 | 01-JAN-10:20 | 859.95 | 20-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 607.84 | 367.92 | 01-JAN-00:10 | 116412.89 | 28-JUN-15:00 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 04-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 04-JAN-08:10 |
ElectricityPurchased:Facility | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
ElectricityPurchased:Plant | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
ElectricityNet:Plant | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
Cogeneration:ElectricityNet | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1722.04 | 13839.00 | 04-JUN-17:20 | 186009.55 | 28-JUN-15:00 |
Heating:Electricity | 13.16 | 0.00 | 01-JAN-00:10 | 87536.85 | 02-JAN-07:10 |
General:Heating:Electricity | 13.16 | 0.00 | 01-JAN-00:10 | 87536.85 | 02-JAN-07:10 |
Fans:Electricity | 149.98 | 0.00 | 01-JAN-00:10 | 29826.93 | 19-JUN-14:50 |
General:Fans:Electricity | 149.98 | 0.00 | 01-JAN-00:10 | 29826.93 | 19-JUN-14:50 |
ExteriorLights:Electricity | 50.88 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.88 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 417.79 | 0.00 | 01-JAN-00:10 | 88020.15 | 28-JUN-15:00 |
General:Cooling:Electricity | 417.79 | 0.00 | 01-JAN-00:10 | 88020.15 | 28-JUN-15:00 |
Electricity:Plant | 42.52 | 0.00 | 01-JAN-00:10 | 5415.02 | 24-JAN-12:20 |
WaterSystems:Electricity | 42.37 | 0.00 | 01-JAN-00:10 | 5408.17 | 24-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 42.37 | 0.00 | 01-JAN-00:10 | 5408.17 | 24-JAN-12:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 12-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 8.46 | 0.00 | 01-JAN-00:10 | 917.25 | 20-JAN-17:10 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 01-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3207.65 | 0.00 | 01-JAN-00:10 | 429922.96 | 28-JUN-16:00 |
EnergyTransfer:Building | 1568.06 | 0.00 | 01-JAN-00:10 | 181033.82 | 28-JUN-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 293.96 | 0.00 | 01-JAN-00:10 | 26814.70 | 05-SEP-07:20 |
Heating:EnergyTransfer | 13.31 | 0.00 | 01-JAN-00:10 | 65663.26 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 13.31 | 0.00 | 01-JAN-00:10 | 65663.26 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1554.75 | 0.00 | 01-JAN-00:10 | 181033.82 | 28-JUN-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 293.96 | 0.00 | 01-JAN-00:10 | 26814.70 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1554.75 | 0.00 | 01-JAN-00:10 | 181033.82 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 293.96 | 0.00 | 01-JAN-00:10 | 26814.70 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 70.88 | 0.00 | 01-JAN-00:10 | 13476.34 | 28-JUN-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.43 | 0.00 | 01-JAN-00:10 | 6761.35 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.43 | 0.00 | 01-JAN-00:10 | 6761.35 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.45 | 0.00 | 01-JAN-00:10 | 13476.34 | 28-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.45 | 0.00 | 01-JAN-00:10 | 13476.34 | 28-JUN-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.37 | 0.00 | 01-JAN-00:10 | 6291.49 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.65 | 0.00 | 01-JAN-00:10 | 2567.40 | 02-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.65 | 0.00 | 01-JAN-00:10 | 2567.40 | 02-JAN-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.72 | 0.00 | 01-JAN-00:10 | 6291.49 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.72 | 0.00 | 01-JAN-00:10 | 6291.49 | 19-JUN-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.14 | 0.00 | 01-JAN-00:10 | 6409.13 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.61 | 0.00 | 01-JAN-00:10 | 1994.12 | 01-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.61 | 0.00 | 01-JAN-00:10 | 1994.12 | 01-JAN-13:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 42.53 | 0.00 | 01-JAN-00:10 | 6409.13 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 42.53 | 0.00 | 01-JAN-00:10 | 6409.13 | 28-AUG-07:10 |
EnergyTransfer:Zone:CORE_MID | 200.97 | 0.00 | 01-JAN-00:10 | 20559.90 | 19-JUN-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2379.48 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 2379.48 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 200.97 | 0.00 | 01-JAN-00:10 | 20559.90 | 19-JUN-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 200.97 | 0.00 | 01-JAN-00:10 | 20559.90 | 19-JUN-07:40 |
EnergyTransfer:Zone:CORE_TOP | 200.61 | 0.00 | 01-JAN-00:10 | 22398.88 | 19-JUN-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.11 | 0.00 | 01-JAN-00:10 | 11588.65 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.11 | 0.00 | 01-JAN-00:10 | 11588.65 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 200.50 | 0.00 | 01-JAN-00:10 | 22398.88 | 19-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 200.50 | 0.00 | 01-JAN-00:10 | 22398.88 | 19-JUN-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.42 | 0.00 | 01-JAN-00:10 | 8531.99 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.85 | 0.00 | 01-JAN-00:10 | 7273.72 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.85 | 0.00 | 01-JAN-00:10 | 7273.72 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.57 | 0.00 | 01-JAN-00:10 | 8531.99 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.57 | 0.00 | 01-JAN-00:10 | 8531.99 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.62 | 0.00 | 01-JAN-00:10 | 9107.42 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.37 | 0.00 | 01-JAN-00:10 | 4671.26 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.37 | 0.00 | 01-JAN-00:10 | 4671.26 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.25 | 0.00 | 01-JAN-00:10 | 9107.42 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.25 | 0.00 | 01-JAN-00:10 | 9107.42 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.36 | 0.00 | 01-JAN-00:10 | 12880.92 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 5890.53 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.45 | 0.00 | 01-JAN-00:10 | 5890.53 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.91 | 0.00 | 01-JAN-00:10 | 12880.92 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.91 | 0.00 | 01-JAN-00:10 | 12880.92 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.02 | 0.00 | 01-JAN-00:10 | 9897.21 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.53 | 0.00 | 01-JAN-00:10 | 4421.87 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.53 | 0.00 | 01-JAN-00:10 | 4421.87 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.50 | 0.00 | 01-JAN-00:10 | 9897.21 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.50 | 0.00 | 01-JAN-00:10 | 9897.21 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.95 | 0.00 | 01-JAN-00:10 | 7403.98 | 17-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 2855.89 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.06 | 0.00 | 01-JAN-00:10 | 2855.89 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.89 | 0.00 | 01-JAN-00:10 | 7403.98 | 17-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.89 | 0.00 | 01-JAN-00:10 | 7403.98 | 17-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.12 | 0.00 | 01-JAN-00:10 | 8118.94 | 14-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1404.27 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1404.27 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.10 | 0.00 | 01-JAN-00:10 | 8118.94 | 14-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.10 | 0.00 | 01-JAN-00:10 | 8118.94 | 14-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.99 | 0.00 | 01-JAN-00:10 | 14611.35 | 28-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.90 | 0.00 | 01-JAN-00:10 | 8469.16 | 06-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.90 | 0.00 | 01-JAN-00:10 | 8469.16 | 06-DEC-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.08 | 0.00 | 01-JAN-00:10 | 14611.35 | 28-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.08 | 0.00 | 01-JAN-00:10 | 14611.35 | 28-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.83 | 0.00 | 01-JAN-00:10 | 8175.71 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1291.36 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1291.36 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.81 | 0.00 | 01-JAN-00:10 | 8175.71 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 49.81 | 0.00 | 01-JAN-00:10 | 8175.71 | 26-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.08 | 0.00 | 01-JAN-00:10 | 7661.81 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.12 | 0.00 | 01-JAN-00:10 | 3474.27 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.12 | 0.00 | 01-JAN-00:10 | 3474.27 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 52.96 | 0.00 | 01-JAN-00:10 | 7661.81 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 52.96 | 0.00 | 01-JAN-00:10 | 7661.81 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.93 | 0.00 | 01-JAN-00:10 | 8876.02 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 2180.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 2180.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.87 | 0.00 | 01-JAN-00:10 | 8876.02 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 51.87 | 0.00 | 01-JAN-00:10 | 8876.02 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.67 | 0.00 | 01-JAN-00:10 | 11610.59 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2611.83 | 16-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2611.83 | 16-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.62 | 0.00 | 01-JAN-00:10 | 11610.59 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.62 | 0.00 | 01-JAN-00:10 | 11610.59 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.14 | 0.00 | 01-JAN-00:10 | 9261.12 | 26-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2014.74 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 2014.74 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.05 | 0.00 | 01-JAN-00:10 | 9261.12 | 26-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.05 | 0.00 | 01-JAN-00:10 | 9261.12 | 26-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
EnergyTransfer:HVAC | 1599.96 | 0.00 | 01-JAN-00:10 | 280699.95 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 13.16 | 0.00 | 01-JAN-00:10 | 87536.85 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1586.80 | 0.00 | 01-JAN-00:10 | 280699.95 | 05-SEP-07:40 |
EnergyTransfer:Plant | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
WaterSystems:EnergyTransfer | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 39.63 | 0.00 | 01-JAN-00:10 | 5298.97 | 23-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -293.959 | 0.000 | 0.000 | 32.661 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -61.053 |
CORE_MID | 0.000 | 0.000 | 0.001 | -200.973 | 0.000 | 0.000 | 32.919 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.301 |
CORE_TOP | 0.000 | 0.000 | 0.108 | -200.505 | 0.000 | 0.000 | 33.365 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.321 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.850 | -54.571 | 0.000 | 0.000 | 7.192 | 8.889 | 24.333 | 25.939 | 0.000 | 0.445 | 10.249 | 0.000 | -22.354 | 0.000 | -0.971 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.370 | -53.250 | 0.000 | 0.000 | 4.469 | 5.475 | 15.404 | 44.118 | 0.000 | 0.293 | 0.001 | 0.000 | -14.031 | 0.000 | -0.673 | -2.175 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.454 | -80.904 | 0.000 | 0.000 | 7.025 | 8.550 | 24.332 | 72.542 | 0.000 | 0.435 | 0.003 | 0.000 | -22.279 | 0.000 | -1.066 | -9.088 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.526 | -52.497 | 0.000 | 0.000 | 4.571 | 5.561 | 15.403 | 42.723 | 0.000 | 0.290 | 0.000 | 0.000 | -15.278 | 0.000 | -0.673 | -0.626 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.062 | -51.885 | 0.000 | 0.000 | 7.111 | 8.847 | 24.333 | 25.980 | 0.000 | 0.246 | 9.738 | 0.000 | -23.870 | 0.000 | -0.562 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.015 | -52.104 | 0.000 | 0.000 | 4.420 | 5.460 | 15.404 | 44.113 | 0.000 | 0.157 | 0.000 | 0.000 | -15.354 | 0.000 | -0.400 | -1.711 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.905 | -85.082 | 0.000 | 0.000 | 6.981 | 8.533 | 24.332 | 72.619 | 0.000 | 14.711 | 0.002 | 0.000 | -24.476 | 0.000 | -15.237 | -5.286 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.021 | -49.809 | 0.000 | 0.000 | 4.484 | 5.543 | 15.403 | 42.780 | 0.000 | 0.154 | 0.002 | 0.000 | -16.766 | 0.000 | -0.401 | -1.410 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.119 | -52.962 | 0.000 | 0.000 | 7.092 | 8.889 | 24.333 | 25.785 | 0.000 | 0.374 | 11.210 | 0.000 | -23.959 | 0.000 | -0.879 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.064 | -51.870 | 0.000 | 0.000 | 3.281 | 5.475 | 15.404 | 44.015 | 0.000 | 0.247 | 0.000 | 0.000 | -14.885 | 0.000 | -0.603 | -1.126 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.049 | -79.623 | 0.000 | 0.000 | 6.961 | 8.550 | 24.332 | 72.413 | 0.000 | 0.365 | 0.002 | 0.000 | -23.664 | 0.000 | -0.954 | -8.427 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.083 | -51.054 | 0.000 | 0.000 | 4.511 | 5.561 | 15.403 | 42.673 | 0.000 | 0.241 | 0.000 | 0.000 | -16.300 | 0.000 | -0.606 | -0.514 |
TOPFLOOR_PLENUM | 5.426 | -65.451 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.579 | 60.932 | 0.000 | 0.000 | 0.000 | -1.487 | -0.001 |
MIDFLOOR_PLENUM | 1.648 | -35.719 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.582 | 35.068 | 0.000 | 0.000 | 0.000 | -1.579 | -0.000 |
FIRSTFLOOR_PLENUM | 0.609 | -42.527 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.445 | 42.768 | 0.000 | 0.000 | 0.000 | -1.295 | -0.000 |
Total Facility | 7.683 | -143.696 | 5.626 | -1411.049 | 0.000 | 0.000 | 167.042 | 301.115 | 719.689 | 555.701 | 0.000 | 19.565 | 169.975 | 0.000 | -233.217 | 0.000 | -27.384 | -131.041 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 29-AUG-04:02 | 0.00 | 0.00 | 0.00 | -41845.28 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 35991.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-JUL-04:02 | 0.00 | 0.00 | 0.00 | -33429.29 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 30775.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-AUG-04:03 | 0.00 | 0.00 | 0.00 | -36470.59 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 33816.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-12:42 | 0.00 | 0.00 | 0.00 | -14146.14 | 0.00 | 0.00 | 25.87 | 36.00 | 478.42 | 3709.23 | 0.00 | 306.86 | 9589.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:21 | 0.00 | 0.00 | 0.00 | -14107.17 | 0.00 | 0.00 | 13.12 | 22.79 | 302.86 | 7958.06 | 0.00 | 16.25 | 5794.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:02 | 0.00 | 0.00 | 0.00 | -17268.26 | 0.00 | 0.00 | 22.45 | 36.00 | 478.41 | 11604.37 | 0.00 | 23.24 | 5103.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-16:51 | 0.00 | 0.00 | 0.00 | -15426.51 | 0.00 | 0.00 | 10.92 | 22.79 | 302.86 | 9050.19 | 0.00 | 156.72 | 5883.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 27-AUG-17:41 | 0.00 | 0.00 | 0.00 | -11705.30 | 0.00 | 0.00 | 0.00 | 39.51 | 386.10 | 2562.73 | 0.00 | 109.57 | 8607.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-09:21 | 0.00 | 0.00 | 0.00 | -12107.54 | 0.00 | 0.00 | 14.75 | 22.79 | 302.86 | 8075.59 | 0.00 | 10.14 | 3681.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 28-JUN-17:00 | 0.00 | 0.00 | 0.00 | -14607.35 | 0.00 | 0.00 | 157.91 | 359.99 | 797.35 | 3490.35 | 0.00 | 14569.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4767.43 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:31 | 0.00 | 0.00 | 0.00 | -13271.82 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 9260.76 | 0.00 | 28.69 | 3715.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUN-18:11 | 0.00 | 0.00 | 0.00 | -12097.55 | 0.00 | 0.00 | 0.00 | 36.00 | 386.10 | 3760.46 | 0.00 | 81.27 | 7833.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:11 | 0.00 | 0.00 | 0.00 | -13340.38 | 0.00 | 0.00 | 13.71 | 22.79 | 302.86 | 8199.26 | 0.00 | 35.42 | 4766.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 25-DEC-13:52 | 0.00 | 0.00 | 0.00 | -15012.44 | 0.00 | 0.00 | 23.24 | 36.00 | 478.41 | 13175.15 | 0.00 | 0.00 | 1318.26 | 0.00 | -0.00 | 0.00 | -18.61 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:31 | 0.00 | 0.00 | 0.00 | -14643.27 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 9143.46 | 0.00 | 39.68 | 5192.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:50 | 0.00 | -13476.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 13338.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-14:30 | 0.00 | -6292.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.94 | 6125.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-12:08 | 0.00 | -7823.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 7800.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUL-04:02 | 0.00 | 8465.31 | 0.00 | -216842.51 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 185.31 | 192062.80 | 0.00 | -513.80 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-07:02 | 0.00 | 0.00 | 11897.45 | 0.00 | 0.00 | 0.00 | 889.94 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17961.33 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 24989.36 | 0.00 | 0.00 | 0.00 | 481.40 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29212.66 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 11511.50 | 0.00 | 0.00 | 0.00 | 110.28 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2159.82 | 0.00 | -21.22 | -10229.56 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 8083.92 | 0.00 | 0.00 | 0.00 | 69.72 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1471.91 | 0.00 | -14.29 | -7166.80 |
PERIMETER_TOP_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 12107.45 | 0.00 | 0.00 | 0.00 | 107.41 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2342.73 | 0.00 | -22.74 | -10638.20 |
PERIMETER_TOP_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 7846.34 | 0.00 | 0.00 | 0.00 | 69.28 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1474.95 | 0.00 | -14.52 | -6925.51 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 7369.06 | 0.00 | 0.00 | 0.00 | 102.07 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2516.21 | 0.00 | -13.16 | -5730.58 |
PERIMETER_BOT_ZN_2 | 06-DEC-07:02 | 0.00 | 0.00 | 4517.43 | 0.00 | 0.00 | 0.00 | 122.37 | 286.67 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2358.21 | 0.00 | -7.72 | -2964.36 |
PERIMETER_BOT_ZN_1 | 06-DEC-07:10 | 0.00 | 0.00 | 8909.81 | 0.00 | 0.00 | 0.00 | 193.30 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 13349.58 | 0.00 | -3656.46 | 0.00 | -19886.93 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 4661.01 | 0.00 | 0.00 | 0.00 | 62.70 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1776.55 | 0.00 | -9.28 | -3437.24 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 8935.75 | 0.00 | 0.00 | 0.00 | 103.53 | 150.93 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2465.15 | 0.00 | -20.18 | -7342.78 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5529.85 | 0.00 | 0.00 | 0.00 | 65.68 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1677.87 | 0.00 | -13.44 | -4403.59 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 8453.27 | 0.00 | 0.00 | 0.00 | 100.40 | 150.93 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2652.43 | 0.00 | -21.34 | -6668.72 |
PERIMETER_MID_ZN_4 | 08-DEC-06:11 | 0.00 | 0.00 | 5388.86 | 0.00 | 0.00 | 0.00 | 63.50 | 95.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2032.77 | 0.00 | -3.33 | -3915.61 |
TOPFLOOR_PLENUM | 02-JAN-07:02 | 9110.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -40.93 | -9069.24 |
MIDFLOOR_PLENUM | 25-DEC-16:32 | 4537.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4545.11 |
FIRSTFLOOR_PLENUM | 06-DEC-06:01 | 4762.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -55.41 | -4706.94 |
Total Facility | 02-JAN-07:02 | 2361.07 | 6362.94 | 116582.92 | -6362.94 | 0.00 | 0.00 | 4495.43 | 10880.98 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24374.54 | 0.00 | -16711.38 | -115731.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0122 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5170 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6675 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0812 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.2627 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9846 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0061 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4318 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8338 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.1313 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5427 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9429 | 2.9429 | 0.8005 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4116 | 2.4116 | 0.7838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6375 | 2.6375 | 0.8176 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9064 | 0.9064 | 0.1813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8052 | 0.8052 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9999 | 0.9999 | 0.2000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9138 | 0.9138 | 0.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7586 | 0.7586 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7126 | 0.7126 | 0.1425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8432 | 0.8432 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7550 | 0.7550 | 0.1510 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7838 | 0.7838 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7693 | 0.7693 | 0.1539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8778 | 0.8778 | 0.1756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8251 | 0.8251 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0122 | 5.5170 | 6.0122 | 1.4318 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6675 | 5.0812 | 5.6675 | 1.4436 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.2627 | 5.9846 | 6.2627 | 1.5427 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4715 | 1.4715 | 0.8005 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2058 | 1.2058 | 0.7838 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3187 | 1.3187 | 0.8176 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4532 | 0.4532 | 0.1813 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4026 | 0.4026 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4999 | 0.4999 | 0.2000 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4569 | 0.4569 | 0.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3793 | 0.3793 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3563 | 0.3563 | 0.1425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4216 | 0.4216 | 0.1686 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3775 | 0.3775 | 0.1510 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3919 | 0.3919 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3846 | 0.3846 | 0.1539 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4389 | 0.4389 | 0.1756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4125 | 0.4125 | 0.1650 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0061 | 1.4318 | 1.4318 | 1.4318 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8338 | 1.4436 | 1.4436 | 1.4436 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.1313 | 1.5427 | 1.5427 | 1.5427 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 73.67 |
Number of hours cooling loads not met | 486.00 |
Number of hours not met | 559.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 13.16 | 87536.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 417.79 | 88020.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.11 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.88 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 149.98 | 29826.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 42.37 | 5408.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1722.04 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1722.04 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.44 |
Space Heating | 2.64 |
Space Cooling | 83.86 |
Fans (All) | 30.10 |
Service Water Heating | 8.50 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 345.64 |
Subtotal | 345.64 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.49 |
Space Heating | 0.76 |
Space Cooling | 24.26 |
Fans (All) | 8.71 |
Service Water Heating | 2.46 |
Receptacle Equipment | 41.79 |
Miscellaneous | 4.53 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8483.50 | 276.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8645.00 | 115.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8601.17 | 158.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8615.67 | 144.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8608.50 | 151.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8608.00 | 152.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8645.33 | 114.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8653.83 | 106.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8596.83 | 163.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8531.83 | 228.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
Min | 8483.50 | 1.67 | 0.00 | 0.00 | 0.00 |
Max | 8758.33 | 276.50 | 0.00 | 0.00 | 0.00 |
Average | 8652.24 | 107.76 | 0.00 | 0.00 | 0.00 |
Sum | 155740.33 | 1939.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128193.00 | 111.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24850.83 | 58.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 111.00 | 0.00 | 0.00 | 0.00 |
Average | 34133.71 | 9.62 | 0.00 | 0.00 | 0.00 |
Sum | 614406.83 | 173.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8402.50 | 357.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8512.83 | 247.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8590.17 | 169.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8500.17 | 259.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8466.67 | 293.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8473.67 | 286.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8471.50 | 288.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8461.67 | 298.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8409.00 | 351.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8367.33 | 392.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8413.83 | 346.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8417.50 | 342.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8392.17 | 367.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8391.50 | 368.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8393.33 | 366.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8106.83 | 653.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8531.00 | 229.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8507.50 | 252.50 | 0.00 | 0.00 | 0.00 |
Min | 8106.83 | 169.83 | 0.00 | 0.00 | 0.00 |
Max | 8590.17 | 653.17 | 0.00 | 0.00 | 0.00 |
Average | 8433.84 | 326.16 | 0.00 | 0.00 | 0.00 |
Sum | 151809.17 | 5870.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128109.00 | 195.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128200.33 | 103.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128208.83 | 95.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24908.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24908.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24907.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24745.83 | 163.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24882.33 | 26.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24897.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128208.83 | 195.00 | 0.00 | 0.00 | 0.00 |
Average | 34110.09 | 33.24 | 0.00 | 0.00 | 0.00 |
Sum | 613981.67 | 598.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198483E+11 | 35608.06 | 30-JAN-07:02 | 7.50 | 2.57 | 0.199125E+10 | 2606.68 | 23-JAN-14:09 | 7.50 | 2.57 |
February | 0.158718E+11 | 35454.28 | 01-FEB-07:02 | 5.00 | 3.59 | 0.180658E+10 | 2606.73 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.209570E+11 | 36469.15 | 20-MAR-06:03 | 11.52 | 7.81 | 0.215996E+10 | 2606.69 | 17-MAR-09:00 | 11.52 | 7.81 |
April | 0.249264E+11 | 39667.18 | 26-APR-05:12 | 19.73 | 10.26 | 0.191911E+10 | 2606.67 | 03-APR-09:30 | 19.73 | 10.26 |
May | 0.279067E+11 | 40626.51 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207924E+10 | 2606.65 | 12-MAY-09:09 | 18.00 | 8.93 |
June | 0.300464E+11 | 41118.72 | 09-JUN-04:02 | 25.83 | 12.86 | 0.207251E+10 | 2606.65 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.296677E+11 | 41069.36 | 26-JUL-04:02 | 25.00 | 16.63 | 0.192683E+10 | 2606.70 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.309752E+11 | 41855.22 | 29-AUG-04:02 | 25.17 | 17.65 | 0.216223E+10 | 2606.76 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.283748E+11 | 41351.92 | 01-SEP-04:03 | 24.30 | 19.74 | 0.192136E+10 | 2606.66 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.257739E+11 | 40570.87 | 10-OCT-05:12 | 17.33 | 11.48 | 0.199719E+10 | 2606.66 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.216113E+11 | 38243.91 | 13-NOV-07:02 | 16.00 | 16.00 | 0.197586E+10 | 2606.75 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.179998E+11 | 35515.57 | 27-DEC-07:02 | 6.17 | 2.23 | 0.192131E+10 | 2606.65 | 13-DEC-10:09 | 6.17 | 2.23 |
Annual Sum or Average | 0.293959E+12 | 0.239334E+11 | ||||||||
Minimum of Months | 0.158718E+11 | 35454.28 | 5.00 | 2.23 | 0.180658E+10 | 2606.65 | 6.17 | 2.23 | ||
Maximum of Months | 0.309752E+11 | 41855.22 | 25.83 | 19.74 | 0.216223E+10 | 2606.76 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204014E+10 | 6027.04 | 31-JAN-16:00 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.110765E+10 | 4375.61 | 23-FEB-14:30 | 18.00 | 10.57 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.57 |
March | 0.238615E+10 | 7187.76 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.631710E+10 | 11307.08 | 14-APR-15:00 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.805333E+10 | 11089.55 | 19-MAY-14:20 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.111041E+11 | 13476.34 | 28-JUN-14:50 | 41.83 | 19.32 | 0.00 | 0.00 | 01-JUN-00:10 | 41.83 | 19.32 |
July | 0.975113E+10 | 12689.57 | 20-JUL-14:20 | 39.33 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 39.33 | 20.22 |
August | 0.958775E+10 | 12767.89 | 25-AUG-15:10 | 41.00 | 17.61 | 0.00 | 0.00 | 01-AUG-00:10 | 41.00 | 17.61 |
September | 0.740015E+10 | 11829.11 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.438908E+10 | 10696.72 | 02-OCT-14:10 | 35.00 | 19.69 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.69 |
November | 0.212558E+10 | 7217.42 | 01-NOV-15:40 | 28.33 | 15.88 | 0.00 | 0.00 | 01-NOV-00:10 | 28.33 | 15.88 |
December | 0.118921E+10 | 4712.99 | 22-DEC-16:10 | 24.83 | 10.00 | 0.00 | 0.00 | 01-DEC-00:10 | 24.83 | 10.00 |
Annual Sum or Average | 0.654514E+11 | 0.00 | ||||||||
Minimum of Months | 0.110765E+10 | 4375.61 | 18.00 | 10.00 | 0.00 | 0.00 | 18.00 | 10.00 | ||
Maximum of Months | 0.111041E+11 | 13476.34 | 41.83 | 20.22 | 0.00 | 0.00 | 41.83 | 20.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767395E+09 | 2079.88 | 27-JAN-16:50 | 26.17 | 9.31 | 0.00 | 0.00 | 01-JAN-00:10 | 26.17 | 9.31 |
February | 0.471002E+09 | 1798.18 | 09-FEB-07:02 | 6.17 | 4.62 | 0.00 | 0.00 | 01-FEB-00:10 | 6.17 | 4.62 |
March | 0.985634E+09 | 2647.26 | 28-MAR-06:01 | 3.90 | 0.38 | 0.00 | 0.00 | 01-MAR-00:10 | 3.90 | 0.38 |
April | 0.318009E+10 | 4616.86 | 24-APR-15:50 | 33.83 | 13.43 | 0.00 | 0.00 | 01-APR-00:10 | 33.83 | 13.43 |
May | 0.434613E+10 | 5084.77 | 08-MAY-16:00 | 34.00 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.00 | 13.77 |
June | 0.608214E+10 | 6291.49 | 19-JUN-14:30 | 38.50 | 18.16 | 0.00 | 0.00 | 01-JUN-00:10 | 38.50 | 18.16 |
July | 0.562279E+10 | 6004.81 | 31-JUL-16:00 | 39.00 | 19.54 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 19.54 |
August | 0.561781E+10 | 6171.37 | 14-AUG-15:20 | 38.00 | 19.72 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 19.72 |
September | 0.461850E+10 | 5816.55 | 05-SEP-16:00 | 33.80 | 20.30 | 0.00 | 0.00 | 01-SEP-00:10 | 33.80 | 20.30 |
October | 0.259079E+10 | 5619.48 | 02-OCT-15:50 | 34.17 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 34.17 | 19.12 |
November | 0.103108E+10 | 2955.95 | 01-NOV-16:00 | 28.00 | 15.72 | 0.00 | 0.00 | 01-NOV-00:10 | 28.00 | 15.72 |
December | 0.405195E+09 | 2653.89 | 14-DEC-07:01 | 1.33 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | 1.33 | -1.0 |
Annual Sum or Average | 0.357186E+11 | 0.00 | ||||||||
Minimum of Months | 0.405195E+09 | 1798.18 | 1.33 | -1.0 | 0.00 | 0.00 | 1.33 | -1.0 | ||
Maximum of Months | 0.608214E+10 | 6291.49 | 39.00 | 20.30 | 0.00 | 0.00 | 39.00 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153237E+10 | 2902.19 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.890527E+09 | 2936.27 | 01-FEB-07:05 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.161244E+10 | 3282.86 | 20-MAR-06:10 | 11.52 | 7.81 | 0.00 | 0.00 | 01-MAR-00:10 | 11.52 | 7.81 |
April | 0.371130E+10 | 5032.71 | 14-APR-17:08 | 34.83 | 14.48 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 14.48 |
May | 0.476674E+10 | 5955.03 | 08-MAY-12:07 | 32.17 | 13.12 | 0.00 | 0.00 | 01-MAY-00:10 | 32.17 | 13.12 |
June | 0.624565E+10 | 7797.87 | 26-JUN-12:06 | 37.33 | 17.16 | 0.00 | 0.00 | 01-JUN-00:10 | 37.33 | 17.16 |
July | 0.593682E+10 | 7823.54 | 10-JUL-12:08 | 37.00 | 19.54 | 0.00 | 0.00 | 01-JUL-00:10 | 37.00 | 19.54 |
August | 0.608203E+10 | 6831.61 | 11-AUG-12:09 | 36.17 | 20.54 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 20.54 |
September | 0.531121E+10 | 6758.96 | 05-SEP-17:07 | 34.22 | 20.04 | 0.00 | 0.00 | 01-SEP-00:10 | 34.22 | 20.04 |
October | 0.357276E+10 | 6014.98 | 04-OCT-17:08 | 33.83 | 17.44 | 0.00 | 0.00 | 01-OCT-00:10 | 33.83 | 17.44 |
November | 0.197473E+10 | 3784.04 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.890511E+09 | 2876.76 | 06-DEC-07:01 | -0.5 | -5.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -5.0 |
Annual Sum or Average | 0.425271E+11 | 0.00 | ||||||||
Minimum of Months | 0.890511E+09 | 2876.76 | -0.5 | -5.0 | 0.00 | 0.00 | -0.5 | -5.0 | ||
Maximum of Months | 0.624565E+10 | 7823.54 | 37.33 | 20.54 | 0.00 | 0.00 | 37.33 | 20.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120200E+11 | 14007.58 | 27-JAN-17:00 | 26.00 | 9.22 | 0.194793E+10 | 2606.63 | 06-JAN-14:09 | 26.00 | 9.22 |
February | 0.959826E+10 | 12799.52 | 01-FEB-17:00 | 15.00 | 6.61 | 0.175446E+10 | 2606.65 | 10-FEB-14:09 | 15.83 | 11.90 |
March | 0.129963E+11 | 14865.56 | 20-MAR-16:00 | 28.30 | 14.35 | 0.213036E+10 | 2606.66 | 14-MAR-13:50 | 28.30 | 14.35 |
April | 0.175622E+11 | 28296.36 | 24-APR-06:02 | 16.50 | 5.42 | 0.191156E+10 | 2606.66 | 03-APR-09:30 | 16.50 | 5.42 |
May | 0.203837E+11 | 32642.65 | 30-MAY-05:12 | 18.00 | 8.93 | 0.207434E+10 | 2606.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.228968E+11 | 32833.36 | 12-JUN-05:12 | 20.33 | 10.58 | 0.206951E+10 | 2606.65 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.222415E+11 | 33435.38 | 18-JUL-04:02 | 24.17 | 20.68 | 0.192309E+10 | 2606.69 | 05-JUL-09:09 | 24.17 | 20.68 |
August | 0.228640E+11 | 33204.58 | 17-AUG-04:02 | 24.83 | 15.66 | 0.215855E+10 | 2606.70 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.201639E+11 | 32738.62 | 11-SEP-05:12 | 22.33 | 18.20 | 0.191781E+10 | 2606.67 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.169071E+11 | 32102.01 | 10-OCT-05:12 | 17.33 | 11.48 | 0.198553E+10 | 2606.67 | 03-OCT-13:39 | 17.33 | 11.48 |
November | 0.129471E+11 | 15477.49 | 02-NOV-16:00 | 26.00 | 15.13 | 0.195194E+10 | 2606.71 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.103915E+11 | 12833.28 | 27-DEC-17:00 | 19.00 | 9.46 | 0.184979E+10 | 2606.57 | 22-DEC-10:09 | 19.00 | 9.46 |
Annual Sum or Average | 0.200972E+12 | 0.236749E+11 | ||||||||
Minimum of Months | 0.959826E+10 | 12799.52 | 15.00 | 5.42 | 0.175446E+10 | 2606.57 | 15.83 | 5.42 | ||
Maximum of Months | 0.228968E+11 | 33435.38 | 28.30 | 20.68 | 0.215855E+10 | 2606.71 | 38.17 | 20.68 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106751E+11 | 13936.39 | 27-JAN-17:00 | 26.00 | 9.22 | 0.187147E+10 | 2606.59 | 26-JAN-14:09 | 26.00 | 9.22 |
February | 0.877014E+10 | 12081.98 | 22-FEB-17:00 | 20.00 | 11.26 | 0.167227E+10 | 2606.56 | 03-FEB-14:00 | 20.00 | 11.26 |
March | 0.121279E+11 | 16032.08 | 17-MAR-16:00 | 26.60 | 14.13 | 0.206620E+10 | 2606.65 | 14-MAR-13:50 | 26.60 | 14.13 |
April | 0.176912E+11 | 19392.04 | 24-APR-15:50 | 33.83 | 13.43 | 0.190269E+10 | 2606.65 | 06-APR-09:30 | 33.83 | 13.43 |
May | 0.211513E+11 | 25988.10 | 08-MAY-06:03 | 20.50 | 9.41 | 0.207156E+10 | 2606.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.249401E+11 | 35883.44 | 27-JUN-04:02 | 25.00 | 10.76 | 0.206943E+10 | 2606.65 | 19-JUN-13:09 | 25.00 | 10.76 |
July | 0.240667E+11 | 36454.89 | 26-JUL-04:02 | 25.00 | 16.63 | 0.192357E+10 | 2606.69 | 05-JUL-09:09 | 25.00 | 16.63 |
August | 0.241570E+11 | 36461.98 | 21-AUG-04:03 | 25.00 | 16.17 | 0.215823E+10 | 2606.70 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.206527E+11 | 36164.30 | 08-SEP-04:02 | 25.92 | 19.60 | 0.191650E+10 | 2606.66 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.158066E+11 | 35709.65 | 02-OCT-04:02 | 26.00 | 17.05 | 0.195974E+10 | 2606.65 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.114156E+11 | 16341.06 | 01-NOV-16:00 | 28.00 | 15.72 | 0.189447E+10 | 2606.69 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.905007E+10 | 12324.70 | 22-DEC-17:00 | 24.00 | 9.52 | 0.172335E+10 | 2606.58 | 22-DEC-14:39 | 24.00 | 9.52 |
Annual Sum or Average | 0.200504E+12 | 0.232295E+11 | ||||||||
Minimum of Months | 0.877014E+10 | 12081.98 | 20.00 | 9.22 | 0.167227E+10 | 2606.56 | 18.00 | 9.22 | ||
Maximum of Months | 0.249401E+11 | 36461.98 | 33.83 | 19.60 | 0.215823E+10 | 2606.70 | 33.83 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187923E+10 | 3002.09 | 31-JAN-16:30 | 29.00 | 10.73 | 0.365539E+09 | 549.48 | 06-JAN-14:00 | 29.00 | 10.73 |
February | 0.145875E+10 | 2198.61 | 22-FEB-16:30 | 20.50 | 11.47 | 0.322927E+09 | 549.46 | 16-FEB-14:00 | 20.50 | 11.47 |
March | 0.238617E+10 | 4290.64 | 16-MAR-16:00 | 28.80 | 13.95 | 0.410270E+09 | 549.50 | 21-MAR-13:30 | 25.25 | 12.80 |
April | 0.458973E+10 | 6433.32 | 25-APR-15:00 | 33.00 | 15.10 | 0.396062E+09 | 549.50 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.630226E+10 | 10689.81 | 07-MAY-17:32 | 35.33 | 14.08 | 0.436271E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.890458E+10 | 14019.37 | 25-JUN-18:11 | 37.33 | 14.77 | 0.437104E+09 | 549.50 | 19-JUN-13:09 | 37.33 | 14.77 |
July | 0.814688E+10 | 14145.96 | 23-JUL-12:42 | 36.83 | 22.18 | 0.406514E+09 | 549.51 | 05-JUL-09:09 | 36.83 | 22.18 |
August | 0.769030E+10 | 13875.46 | 13-AUG-16:51 | 38.00 | 19.94 | 0.455386E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.616940E+10 | 13749.98 | 17-SEP-16:02 | 34.40 | 17.62 | 0.403743E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.363496E+10 | 10933.73 | 02-OCT-04:02 | 26.00 | 17.05 | 0.398867E+09 | 549.51 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.207643E+10 | 4248.63 | 01-NOV-15:30 | 28.50 | 15.96 | 0.376858E+09 | 549.50 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.133218E+10 | 2175.01 | 22-DEC-16:50 | 24.17 | 9.62 | 0.329327E+09 | 546.94 | 22-DEC-14:00 | 24.17 | 9.62 |
Annual Sum or Average | 0.545709E+11 | 0.473887E+10 | ||||||||
Minimum of Months | 0.133218E+10 | 2175.01 | 20.50 | 9.62 | 0.322927E+09 | 546.94 | 18.00 | 9.62 | ||
Maximum of Months | 0.890458E+10 | 14145.96 | 38.00 | 22.18 | 0.455386E+09 | 549.51 | 37.33 | 22.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195313E+10 | 3017.29 | 27-JAN-10:30 | 21.00 | 7.83 | 0.248555E+09 | 347.87 | 09-JAN-10:09 | 21.00 | 7.83 |
February | 0.148642E+10 | 3221.92 | 23-FEB-10:30 | 15.00 | 11.05 | 0.219578E+09 | 347.87 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.251598E+10 | 4615.23 | 23-MAR-10:30 | 22.70 | 10.73 | 0.272392E+09 | 347.88 | 14-MAR-13:50 | 22.70 | 10.73 |
April | 0.512498E+10 | 11083.92 | 30-APR-09:42 | 27.50 | 10.26 | 0.254437E+09 | 347.90 | 03-APR-09:20 | 27.50 | 10.26 |
May | 0.641471E+10 | 11851.50 | 29-MAY-09:22 | 27.00 | 11.90 | 0.277000E+09 | 348.18 | 17-MAY-09:00 | 27.00 | 11.90 |
June | 0.814436E+10 | 13238.75 | 18-JUN-09:02 | 32.33 | 17.55 | 0.276893E+09 | 348.18 | 08-JUN-09:00 | 32.33 | 17.55 |
July | 0.740067E+10 | 14107.08 | 23-JUL-09:21 | 32.50 | 22.15 | 0.257534E+09 | 348.15 | 28-JUL-09:00 | 31.00 | 20.55 |
August | 0.720514E+10 | 13162.40 | 13-AUG-09:32 | 32.67 | 21.08 | 0.288468E+09 | 348.17 | 01-AUG-09:00 | 32.67 | 21.08 |
September | 0.562039E+10 | 11801.38 | 10-SEP-10:22 | 32.45 | 19.22 | 0.255846E+09 | 348.46 | 08-SEP-09:00 | 32.45 | 19.22 |
October | 0.383097E+10 | 9262.53 | 01-OCT-11:23 | 34.50 | 19.32 | 0.260249E+09 | 347.90 | 17-OCT-09:20 | 24.67 | 9.84 |
November | 0.213234E+10 | 3881.30 | 01-NOV-10:20 | 23.67 | 16.07 | 0.250731E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.142047E+10 | 1937.88 | 25-DEC-15:52 | 26.00 | 12.00 | 0.222376E+09 | 347.87 | 22-DEC-14:50 | 26.00 | 12.00 |
Annual Sum or Average | 0.532496E+11 | 0.308406E+10 | ||||||||
Minimum of Months | 0.142047E+10 | 1937.88 | 15.00 | 7.83 | 0.219578E+09 | 347.87 | 15.00 | 7.83 | ||
Maximum of Months | 0.814436E+10 | 14107.08 | 34.50 | 22.15 | 0.288468E+09 | 348.46 | 32.67 | 21.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.633587E+10 | 16148.53 | 16-JAN-14:12 | 24.00 | 9.07 | 0.401493E+09 | 549.68 | 31-JAN-14:00 | 28.00 | 11.02 |
February | 0.347606E+10 | 9514.71 | 28-FEB-14:10 | 18.17 | 7.92 | 0.352814E+09 | 549.63 | 23-FEB-14:20 | 18.17 | 7.92 |
March | 0.436412E+10 | 8904.54 | 16-MAR-13:40 | 27.53 | 13.09 | 0.426295E+09 | 549.52 | 09-MAR-14:00 | 27.53 | 13.09 |
April | 0.674223E+10 | 15638.20 | 23-APR-13:23 | 33.00 | 12.49 | 0.396951E+09 | 549.81 | 12-APR-13:00 | 33.00 | 12.49 |
May | 0.698412E+10 | 12958.60 | 07-MAY-15:32 | 35.67 | 14.01 | 0.435315E+09 | 549.50 | 16-MAY-13:00 | 36.00 | 15.44 |
June | 0.867229E+10 | 15050.50 | 04-JUN-16:41 | 38.00 | 16.06 | 0.436695E+09 | 549.50 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.839968E+10 | 15813.46 | 23-JUL-13:22 | 34.00 | 21.31 | 0.406316E+09 | 549.73 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.906434E+10 | 15535.68 | 13-AUG-14:12 | 38.00 | 21.32 | 0.455420E+09 | 550.29 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.863423E+10 | 15998.13 | 10-SEP-13:02 | 34.50 | 19.00 | 0.404249E+09 | 565.72 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.766801E+10 | 17267.92 | 09-OCT-13:02 | 31.17 | 17.33 | 0.410318E+09 | 566.44 | 02-OCT-13:09 | 31.17 | 17.33 |
November | 0.590058E+10 | 16158.16 | 19-NOV-14:02 | 26.17 | 11.19 | 0.401816E+09 | 549.67 | 14-NOV-14:00 | 26.17 | 11.19 |
December | 0.466381E+10 | 16780.80 | 25-DEC-13:52 | 26.00 | 12.00 | 0.378209E+09 | 549.64 | 22-DEC-14:50 | 26.00 | 12.00 |
Annual Sum or Average | 0.809053E+11 | 0.490589E+10 | ||||||||
Minimum of Months | 0.347606E+10 | 8904.54 | 18.17 | 7.92 | 0.352814E+09 | 549.50 | 18.17 | 7.92 | ||
Maximum of Months | 0.906434E+10 | 17267.92 | 38.00 | 21.32 | 0.455420E+09 | 566.44 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240296E+10 | 6093.83 | 31-JAN-16:30 | 29.00 | 10.73 | 0.230130E+09 | 347.85 | 24-JAN-14:00 | 29.00 | 10.73 |
February | 0.165484E+10 | 5999.43 | 22-FEB-16:30 | 20.50 | 11.47 | 0.202758E+09 | 347.83 | 27-FEB-14:00 | 17.00 | 9.60 |
March | 0.266628E+10 | 8329.24 | 18-MAR-17:08 | 26.92 | 12.85 | 0.254009E+09 | 347.85 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.511949E+10 | 14785.72 | 02-APR-16:41 | 31.00 | 12.54 | 0.247715E+09 | 347.85 | 06-APR-09:39 | 25.33 | 12.49 |
May | 0.622423E+10 | 14894.85 | 28-MAY-17:02 | 32.83 | 12.78 | 0.274357E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.788199E+10 | 15349.58 | 25-JUN-17:31 | 38.00 | 15.08 | 0.276299E+09 | 347.85 | 19-JUN-13:00 | 38.00 | 15.08 |
July | 0.669363E+10 | 15426.55 | 16-JUL-16:51 | 37.00 | 20.84 | 0.256953E+09 | 347.86 | 05-JUL-09:09 | 37.00 | 20.84 |
August | 0.660327E+10 | 15309.98 | 13-AUG-16:51 | 38.00 | 19.94 | 0.287734E+09 | 347.86 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.531732E+10 | 14139.85 | 17-SEP-16:02 | 34.40 | 17.62 | 0.254613E+09 | 347.85 | 13-SEP-09:09 | 34.40 | 17.62 |
October | 0.380917E+10 | 15084.07 | 09-OCT-15:42 | 32.83 | 17.35 | 0.248777E+09 | 347.86 | 03-OCT-13:30 | 32.83 | 17.35 |
November | 0.252278E+10 | 7373.97 | 01-NOV-16:00 | 28.00 | 15.72 | 0.235695E+09 | 347.85 | 16-NOV-14:30 | 18.00 | 11.97 |
December | 0.160260E+10 | 6105.29 | 22-DEC-16:30 | 24.50 | 9.81 | 0.212585E+09 | 347.85 | 22-DEC-14:50 | 24.50 | 9.81 |
Annual Sum or Average | 0.524985E+11 | 0.298162E+10 | ||||||||
Minimum of Months | 0.160260E+10 | 5999.43 | 20.50 | 9.81 | 0.202758E+09 | 347.83 | 17.00 | 9.60 | ||
Maximum of Months | 0.788199E+10 | 15426.55 | 38.00 | 20.84 | 0.287734E+09 | 347.86 | 38.00 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196467E+10 | 2274.07 | 27-JAN-16:30 | 26.50 | 9.48 | 0.376902E+09 | 549.48 | 06-JAN-14:00 | 26.50 | 9.48 |
February | 0.152559E+10 | 1541.92 | 22-FEB-16:40 | 20.33 | 11.40 | 0.327468E+09 | 535.93 | 22-FEB-14:20 | 20.33 | 11.40 |
March | 0.207516E+10 | 2972.09 | 20-MAR-14:30 | 27.70 | 14.31 | 0.410658E+09 | 549.49 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.366977E+10 | 5012.50 | 25-APR-15:00 | 33.00 | 15.10 | 0.398690E+09 | 549.49 | 06-APR-09:30 | 33.00 | 15.10 |
May | 0.500835E+10 | 5640.41 | 08-MAY-15:00 | 34.00 | 13.77 | 0.436298E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.750545E+10 | 11572.81 | 11-JUN-18:11 | 33.67 | 14.85 | 0.436769E+09 | 549.50 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.762734E+10 | 11677.26 | 02-JUL-18:21 | 37.00 | 14.49 | 0.406429E+09 | 549.51 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.754900E+10 | 11705.21 | 27-AUG-17:41 | 39.17 | 18.06 | 0.455658E+09 | 549.52 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.666403E+10 | 11406.16 | 17-SEP-16:12 | 34.40 | 17.52 | 0.404753E+09 | 549.50 | 22-SEP-09:00 | 25.00 | 17.32 |
October | 0.407242E+10 | 9611.74 | 02-OCT-04:02 | 26.00 | 17.05 | 0.413968E+09 | 549.50 | 05-OCT-09:20 | 27.00 | 16.87 |
November | 0.243118E+10 | 4027.23 | 02-NOV-14:00 | 27.00 | 15.44 | 0.399027E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.179212E+10 | 2003.79 | 26-DEC-14:00 | 23.00 | 10.16 | 0.352536E+09 | 548.64 | 01-DEC-14:00 | 23.00 | 10.16 |
Annual Sum or Average | 0.518851E+11 | 0.481916E+10 | ||||||||
Minimum of Months | 0.152559E+10 | 1541.92 | 20.33 | 9.48 | 0.327468E+09 | 535.93 | 20.00 | 9.48 | ||
Maximum of Months | 0.762734E+10 | 11705.21 | 39.17 | 18.06 | 0.455658E+09 | 549.52 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203564E+10 | 2917.18 | 27-JAN-10:30 | 21.00 | 7.83 | 0.256042E+09 | 347.87 | 23-JAN-14:09 | 21.00 | 7.83 |
February | 0.149276E+10 | 2640.42 | 23-FEB-10:30 | 15.00 | 11.05 | 0.224589E+09 | 347.87 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.217900E+10 | 3677.69 | 23-MAR-10:30 | 22.70 | 10.73 | 0.276131E+09 | 347.87 | 16-MAR-09:00 | 22.70 | 10.73 |
April | 0.454012E+10 | 8704.14 | 23-APR-11:13 | 29.53 | 11.19 | 0.255224E+09 | 347.89 | 28-APR-09:00 | 25.00 | 10.77 |
May | 0.557646E+10 | 10316.29 | 21-MAY-09:12 | 27.67 | 11.66 | 0.277182E+09 | 348.05 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.724009E+10 | 11667.04 | 11-JUN-10:12 | 30.33 | 13.50 | 0.276941E+09 | 348.09 | 02-JUN-09:50 | 30.33 | 13.50 |
July | 0.710434E+10 | 12107.87 | 23-JUL-09:21 | 32.50 | 22.15 | 0.257688E+09 | 348.03 | 28-JUL-09:00 | 31.00 | 20.55 |
August | 0.722702E+10 | 11763.33 | 27-AUG-11:02 | 37.17 | 17.45 | 0.288849E+09 | 348.10 | 25-AUG-09:20 | 37.17 | 17.45 |
September | 0.604135E+10 | 11446.51 | 10-SEP-11:22 | 33.30 | 19.31 | 0.256476E+09 | 348.05 | 05-SEP-09:39 | 33.30 | 19.31 |
October | 0.435691E+10 | 8763.52 | 15-OCT-09:32 | 25.33 | 10.24 | 0.264798E+09 | 347.89 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.254638E+10 | 4088.75 | 02-NOV-08:40 | 21.00 | 14.47 | 0.259516E+09 | 347.89 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.176422E+10 | 2523.90 | 01-DEC-10:30 | 18.50 | 8.87 | 0.239459E+09 | 347.87 | 13-DEC-10:30 | 12.00 | 10.39 |
Annual Sum or Average | 0.521043E+11 | 0.313290E+10 | ||||||||
Minimum of Months | 0.149276E+10 | 2523.90 | 15.00 | 7.83 | 0.224589E+09 | 347.87 | 12.00 | 7.83 | ||
Maximum of Months | 0.724009E+10 | 12107.87 | 37.17 | 22.15 | 0.288849E+09 | 348.10 | 37.17 | 20.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570416E+10 | 13863.44 | 29-JAN-14:52 | 24.00 | 9.34 | 0.405820E+09 | 554.84 | 17-JAN-14:39 | 24.00 | 9.34 |
February | 0.219725E+10 | 7783.56 | 28-FEB-13:07 | 17.17 | 7.91 | 0.342986E+09 | 549.50 | 13-FEB-14:00 | 17.17 | 7.91 |
March | 0.312916E+10 | 10269.07 | 16-MAR-16:10 | 28.72 | 13.89 | 0.417001E+09 | 549.51 | 16-MAR-13:00 | 28.72 | 13.89 |
April | 0.647659E+10 | 12234.74 | 14-APR-16:50 | 35.00 | 14.56 | 0.397929E+09 | 618.90 | 14-APR-12:09 | 35.00 | 14.56 |
May | 0.730464E+10 | 12695.37 | 15-MAY-17:00 | 37.00 | 15.57 | 0.437181E+09 | 618.48 | 18-MAY-12:09 | 34.00 | 13.67 |
June | 0.991467E+10 | 14611.35 | 28-JUN-17:00 | 42.00 | 19.33 | 0.445212E+09 | 727.20 | 28-JUN-12:09 | 42.00 | 19.33 |
July | 0.100200E+11 | 13731.52 | 20-JUL-17:00 | 39.00 | 20.23 | 0.413457E+09 | 711.99 | 12-JUL-12:09 | 39.00 | 20.23 |
August | 0.112265E+11 | 14425.41 | 25-AUG-17:00 | 41.00 | 17.61 | 0.466179E+09 | 763.75 | 25-AUG-12:09 | 41.00 | 17.61 |
September | 0.105725E+11 | 14169.81 | 10-SEP-13:22 | 34.70 | 19.32 | 0.415629E+09 | 713.73 | 07-SEP-12:09 | 34.70 | 19.32 |
October | 0.846751E+10 | 14591.25 | 09-OCT-13:02 | 31.17 | 17.33 | 0.421751E+09 | 696.50 | 02-OCT-12:09 | 31.17 | 17.33 |
November | 0.585590E+10 | 13520.72 | 19-NOV-12:53 | 26.00 | 10.91 | 0.407555E+09 | 578.04 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.421480E+10 | 13792.34 | 24-DEC-13:42 | 23.83 | 10.31 | 0.379331E+09 | 549.96 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.850838E+11 | 0.495003E+10 | ||||||||
Minimum of Months | 0.219725E+10 | 7783.56 | 17.17 | 7.91 | 0.342986E+09 | 549.50 | 17.17 | 7.91 | ||
Maximum of Months | 0.112265E+11 | 14611.35 | 42.00 | 20.23 | 0.466179E+09 | 763.75 | 42.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231070E+10 | 6920.87 | 29-JAN-16:53 | 24.00 | 9.34 | 0.243728E+09 | 347.84 | 23-JAN-14:00 | 24.00 | 9.34 |
February | 0.155381E+10 | 4408.73 | 22-FEB-16:30 | 20.50 | 11.47 | 0.209792E+09 | 347.83 | 27-FEB-14:00 | 17.00 | 9.60 |
March | 0.218902E+10 | 5507.43 | 18-MAR-17:10 | 26.92 | 12.85 | 0.261178E+09 | 347.84 | 21-MAR-13:00 | 25.50 | 12.96 |
April | 0.435273E+10 | 12011.41 | 23-APR-17:11 | 32.67 | 12.49 | 0.253349E+09 | 347.85 | 06-APR-09:30 | 32.67 | 12.49 |
May | 0.523688E+10 | 12308.83 | 07-MAY-16:41 | 36.00 | 14.34 | 0.276503E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.692630E+10 | 13271.81 | 11-JUN-17:31 | 34.00 | 15.03 | 0.276696E+09 | 347.85 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.631372E+10 | 12838.33 | 04-JUL-18:11 | 36.00 | 14.97 | 0.257422E+09 | 347.86 | 28-JUL-13:50 | 29.50 | 20.43 |
August | 0.653165E+10 | 13195.55 | 27-AUG-17:41 | 39.17 | 18.06 | 0.288634E+09 | 347.87 | 29-AUG-13:39 | 28.67 | 21.18 |
September | 0.565671E+10 | 11812.01 | 10-SEP-14:42 | 35.92 | 19.69 | 0.256374E+09 | 347.85 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.407845E+10 | 12431.63 | 15-OCT-16:52 | 30.00 | 12.07 | 0.262138E+09 | 347.85 | 16-OCT-09:30 | 25.50 | 10.18 |
November | 0.274183E+10 | 6714.52 | 01-NOV-16:00 | 28.00 | 15.72 | 0.254219E+09 | 347.86 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.191830E+10 | 6151.92 | 24-DEC-16:23 | 22.50 | 9.95 | 0.228361E+09 | 347.83 | 20-DEC-14:00 | 22.50 | 9.95 |
Annual Sum or Average | 0.498101E+11 | 0.306839E+10 | ||||||||
Minimum of Months | 0.155381E+10 | 4408.73 | 20.50 | 9.34 | 0.209792E+09 | 347.83 | 17.00 | 9.34 | ||
Maximum of Months | 0.692630E+10 | 13271.81 | 39.17 | 19.69 | 0.288634E+09 | 347.87 | 33.17 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205872E+10 | 2972.82 | 31-JAN-16:30 | 29.00 | 10.73 | 0.382606E+09 | 549.49 | 06-JAN-14:09 | 29.00 | 10.73 |
February | 0.160426E+10 | 2172.52 | 22-FEB-16:20 | 20.67 | 11.54 | 0.339531E+09 | 549.46 | 16-FEB-14:00 | 20.67 | 11.54 |
March | 0.245669E+10 | 4116.38 | 20-MAR-14:30 | 27.70 | 14.31 | 0.426048E+09 | 549.50 | 17-MAR-09:00 | 27.70 | 14.31 |
April | 0.441204E+10 | 5874.32 | 25-APR-14:50 | 32.67 | 15.01 | 0.400472E+09 | 549.50 | 06-APR-09:30 | 32.67 | 15.01 |
May | 0.597678E+10 | 6869.19 | 08-MAY-06:03 | 20.50 | 9.41 | 0.437219E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.820215E+10 | 12097.55 | 11-JUN-18:11 | 33.67 | 14.85 | 0.437220E+09 | 549.64 | 19-JUN-13:00 | 39.00 | 18.45 |
July | 0.750185E+10 | 11943.44 | 16-JUL-18:22 | 32.50 | 21.02 | 0.406562E+09 | 549.51 | 05-JUL-09:09 | 32.50 | 21.02 |
August | 0.722785E+10 | 11855.59 | 27-AUG-15:51 | 40.00 | 18.27 | 0.455600E+09 | 549.51 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.592116E+10 | 11678.62 | 10-SEP-16:52 | 33.80 | 19.51 | 0.404471E+09 | 549.50 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.368672E+10 | 9964.77 | 02-OCT-04:02 | 26.00 | 17.05 | 0.409294E+09 | 549.51 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.226707E+10 | 4009.86 | 01-NOV-15:30 | 28.50 | 15.96 | 0.392448E+09 | 549.50 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.164680E+10 | 2224.79 | 22-DEC-16:50 | 24.17 | 9.62 | 0.347077E+09 | 549.40 | 22-DEC-14:00 | 24.17 | 9.62 |
Annual Sum or Average | 0.529621E+11 | 0.483855E+10 | ||||||||
Minimum of Months | 0.160426E+10 | 2172.52 | 20.50 | 9.41 | 0.339531E+09 | 549.40 | 20.00 | 9.62 | ||
Maximum of Months | 0.820215E+10 | 12097.55 | 40.00 | 21.02 | 0.455600E+09 | 549.64 | 39.00 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217170E+10 | 3567.72 | 27-JAN-10:00 | 20.00 | 7.78 | 0.185717E+09 | 338.72 | 09-JAN-09:09 | 20.00 | 7.78 |
February | 0.166946E+10 | 3749.78 | 23-FEB-10:00 | 14.00 | 11.11 | 0.164984E+09 | 338.72 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.261130E+10 | 4847.93 | 23-MAR-10:10 | 21.97 | 10.49 | 0.203051E+09 | 338.73 | 16-MAR-10:09 | 21.97 | 10.49 |
April | 0.494886E+10 | 11615.29 | 09-APR-09:32 | 24.33 | 9.01 | 0.188516E+09 | 338.74 | 28-APR-10:09 | 25.17 | 10.76 |
May | 0.608620E+10 | 11802.99 | 21-MAY-09:02 | 27.33 | 11.56 | 0.204986E+09 | 339.01 | 30-MAY-10:30 | 28.50 | 14.02 |
June | 0.754942E+10 | 13003.71 | 11-JUN-08:52 | 28.00 | 12.26 | 0.204708E+09 | 343.82 | 19-JUN-07:19 | 29.00 | 12.63 |
July | 0.683402E+10 | 13285.48 | 04-JUL-09:41 | 31.67 | 15.19 | 0.190978E+09 | 339.48 | 05-JUL-10:30 | 34.00 | 15.54 |
August | 0.675391E+10 | 13340.14 | 27-AUG-09:11 | 33.67 | 16.18 | 0.213155E+09 | 339.54 | 28-AUG-10:30 | 35.00 | 21.28 |
September | 0.535643E+10 | 12874.48 | 10-SEP-10:12 | 32.17 | 19.22 | 0.189524E+09 | 339.48 | 05-SEP-10:30 | 32.17 | 19.22 |
October | 0.388066E+10 | 8476.21 | 01-OCT-11:13 | 34.33 | 19.35 | 0.193641E+09 | 338.74 | 04-OCT-07:30 | 23.00 | 17.79 |
November | 0.232969E+10 | 4380.26 | 10-NOV-09:40 | 22.33 | 9.69 | 0.187664E+09 | 338.74 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.167846E+10 | 2528.69 | 27-DEC-10:00 | 14.00 | 6.80 | 0.169388E+09 | 338.71 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.518701E+11 | 0.229631E+10 | ||||||||
Minimum of Months | 0.166946E+10 | 2528.69 | 14.00 | 6.80 | 0.164984E+09 | 338.71 | 14.00 | 7.78 | ||
Maximum of Months | 0.754942E+10 | 13340.14 | 34.33 | 19.35 | 0.213155E+09 | 343.82 | 35.00 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673155E+10 | 14529.30 | 15-JAN-13:42 | 22.67 | 10.33 | 0.409968E+09 | 557.14 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.373114E+10 | 9394.02 | 28-FEB-14:00 | 18.00 | 7.97 | 0.363836E+09 | 549.88 | 23-FEB-14:50 | 18.00 | 7.97 |
March | 0.448273E+10 | 8516.12 | 23-MAR-13:40 | 25.33 | 11.79 | 0.438260E+09 | 549.67 | 16-MAR-13:00 | 25.33 | 11.79 |
April | 0.645226E+10 | 13835.67 | 30-APR-13:23 | 34.00 | 12.40 | 0.401351E+09 | 550.02 | 25-APR-13:09 | 34.00 | 12.40 |
May | 0.657371E+10 | 11764.19 | 07-MAY-13:53 | 35.00 | 13.93 | 0.437028E+09 | 549.50 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.795114E+10 | 12924.52 | 11-JUN-17:31 | 34.00 | 15.03 | 0.436947E+09 | 549.50 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.770228E+10 | 13117.08 | 30-JUL-17:01 | 38.00 | 19.22 | 0.406505E+09 | 549.70 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.850591E+10 | 13710.06 | 27-AUG-11:12 | 37.33 | 17.55 | 0.455792E+09 | 550.27 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.827889E+10 | 14359.43 | 10-SEP-10:52 | 33.30 | 19.18 | 0.405202E+09 | 580.55 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.771461E+10 | 14157.60 | 09-OCT-13:52 | 32.00 | 17.25 | 0.416896E+09 | 582.30 | 02-OCT-13:09 | 32.00 | 17.25 |
November | 0.626714E+10 | 14444.60 | 05-NOV-13:42 | 22.00 | 8.01 | 0.409428E+09 | 563.82 | 01-NOV-13:00 | 22.00 | 8.01 |
December | 0.523314E+10 | 15012.27 | 25-DEC-13:52 | 26.00 | 12.00 | 0.388739E+09 | 549.71 | 29-DEC-14:00 | 20.00 | 9.12 |
Annual Sum or Average | 0.796245E+11 | 0.496995E+10 | ||||||||
Minimum of Months | 0.373114E+10 | 8516.12 | 18.00 | 7.97 | 0.363836E+09 | 549.50 | 18.00 | 7.97 | ||
Maximum of Months | 0.850591E+10 | 15012.27 | 38.00 | 19.22 | 0.455792E+09 | 582.30 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257141E+10 | 5959.48 | 24-JAN-16:30 | 24.50 | 10.78 | 0.239113E+09 | 347.85 | 06-JAN-14:09 | 24.50 | 10.78 |
February | 0.181474E+10 | 5894.82 | 22-FEB-16:30 | 20.50 | 11.47 | 0.211085E+09 | 347.84 | 03-FEB-14:00 | 20.50 | 11.47 |
March | 0.270478E+10 | 7491.31 | 18-MAR-17:08 | 26.92 | 12.85 | 0.263848E+09 | 347.85 | 14-MAR-13:00 | 26.92 | 12.85 |
April | 0.488324E+10 | 13099.90 | 23-APR-16:22 | 33.15 | 12.72 | 0.252071E+09 | 347.85 | 06-APR-09:30 | 33.15 | 12.72 |
May | 0.588278E+10 | 13417.94 | 21-MAY-17:02 | 31.83 | 13.32 | 0.276145E+09 | 347.85 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.733738E+10 | 14643.32 | 11-JUN-17:31 | 34.00 | 15.03 | 0.276600E+09 | 347.85 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.618874E+10 | 13603.53 | 30-JUL-17:01 | 38.00 | 19.22 | 0.257160E+09 | 347.86 | 05-JUL-09:09 | 38.00 | 19.22 |
August | 0.621471E+10 | 14327.73 | 06-AUG-17:01 | 30.83 | 18.57 | 0.288216E+09 | 347.86 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.508720E+10 | 13845.27 | 04-SEP-16:51 | 31.60 | 21.23 | 0.255665E+09 | 347.85 | 22-SEP-09:09 | 24.00 | 17.33 |
October | 0.379951E+10 | 11526.61 | 15-OCT-16:32 | 30.33 | 12.24 | 0.255832E+09 | 347.86 | 03-OCT-13:39 | 30.33 | 12.24 |
November | 0.267664E+10 | 7564.15 | 19-NOV-16:03 | 26.67 | 11.71 | 0.244711E+09 | 347.86 | 16-NOV-14:09 | 26.67 | 11.71 |
December | 0.189355E+10 | 7221.75 | 24-DEC-16:33 | 22.33 | 9.88 | 0.220607E+09 | 347.83 | 20-DEC-14:00 | 22.33 | 9.88 |
Annual Sum or Average | 0.510547E+11 | 0.304105E+10 | ||||||||
Minimum of Months | 0.181474E+10 | 5894.82 | 20.50 | 9.88 | 0.211085E+09 | 347.83 | 20.50 | 9.88 | ||
Maximum of Months | 0.733738E+10 | 14643.32 | 38.00 | 21.23 | 0.288216E+09 | 347.86 | 38.00 | 20.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.889974E+09 | 9110.79 | 02-JAN-07:02 | 6.00 |
February | 0.758070E+09 | 4640.65 | 13-FEB-07:02 | 8.33 |
March | 0.765403E+09 | 6815.53 | 27-MAR-06:01 | 1.97 |
April | 0.308069E+09 | 3899.07 | 21-APR-05:03 | 8.17 |
May | 0.156194E+09 | 3737.72 | 14-MAY-07:20 | 21.33 |
June | 34077565.34 | 3627.63 | 27-JUN-04:02 | 25.00 |
July | 26883260.83 | 4686.19 | 10-JUL-04:02 | 26.83 |
August | 26370772.54 | 4292.68 | 21-AUG-04:03 | 25.00 |
September | 38708508.38 | 3976.89 | 18-SEP-04:02 | 25.42 |
October | 0.449260E+09 | 3943.90 | 26-OCT-05:03 | 7.17 |
November | 0.644539E+09 | 6263.13 | 24-NOV-07:02 | 4.50 |
December | 0.132839E+10 | 9110.12 | 06-DEC-07:02 | -0.5 |
Annual Sum or Average | 0.542594E+10 | |||
Minimum of Months | 26370772.54 | 3627.63 | -0.5 | |
Maximum of Months | 0.132839E+10 | 9110.79 | 26.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284021E+09 | 3925.70 | 16-JAN-12:02 | 24.00 |
February | 0.315578E+09 | 3238.28 | 26-FEB-11:23 | 15.00 |
March | 0.166223E+09 | 2631.62 | 26-MAR-13:23 | 16.90 |
April | 21819282.24 | 2740.59 | 23-APR-15:42 | 33.25 |
May | 18985751.62 | 2335.53 | 07-MAY-15:52 | 36.00 |
June | 17901497.02 | 2751.83 | 25-JUN-16:51 | 38.00 |
July | 23649245.70 | 3119.77 | 02-JUL-16:31 | 38.00 |
August | 17767992.94 | 3062.14 | 27-AUG-15:11 | 40.00 |
September | 15733515.46 | 2461.59 | 10-SEP-14:11 | 35.37 |
October | 36479772.13 | 3502.84 | 15-OCT-15:52 | 31.00 |
November | 0.137633E+09 | 4152.23 | 26-NOV-14:23 | 18.90 |
December | 0.592078E+09 | 4537.11 | 25-DEC-16:32 | 24.67 |
Annual Sum or Average | 0.164787E+10 | |||
Minimum of Months | 15733515.46 | 2335.53 | 15.00 | |
Maximum of Months | 0.592078E+09 | 4537.11 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108865E+09 | 3098.42 | 01-JAN-14:17 | 14.47 |
February | 62999372.63 | 2418.92 | 13-FEB-08:04 | 10.17 |
March | 19657475.00 | 1847.54 | 19-MAR-14:37 | 25.73 |
April | 20284375.81 | 2225.58 | 23-APR-15:11 | 33.10 |
May | 16582448.04 | 1557.10 | 27-MAY-17:42 | 30.00 |
June | 21243259.67 | 3267.71 | 29-JUN-04:02 | 28.00 |
July | 35669319.97 | 3879.48 | 12-JUL-04:02 | 27.83 |
August | 29189849.26 | 3960.48 | 09-AUG-04:02 | 26.00 |
September | 34455439.23 | 4151.42 | 07-SEP-04:02 | 26.10 |
October | 38826684.34 | 3116.29 | 02-OCT-04:02 | 26.00 |
November | 45935188.98 | 3728.03 | 24-NOV-06:11 | 3.33 |
December | 0.175227E+09 | 4762.25 | 06-DEC-06:01 | 0.67 |
Annual Sum or Average | 0.608935E+09 | |||
Minimum of Months | 16582448.04 | 1557.10 | 0.67 | |
Maximum of Months | 0.175227E+09 | 4762.25 | 33.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1427689.93 | 11897.42 | 02-JAN-07:02 | 6.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 1427689.93 | |||
Minimum of Months | 0.00 | 0.00 | 6.00 | |
Maximum of Months | 1427689.93 | 11897.42 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41598747.10 | 24992.19 | 02-JAN-06:11 | 4.67 |
February | 9248084.39 | 22781.21 | 13-FEB-07:02 | 8.33 |
March | 1912320.35 | 22566.44 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 2623183.11 | 23111.26 | 24-NOV-07:02 | 4.50 |
December | 52610234.18 | 23833.74 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.107993E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 52610234.18 | 24992.19 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131102E+09 | 11511.31 | 02-JAN-06:11 | 4.67 |
February | 0.116338E+09 | 10490.11 | 13-FEB-06:12 | 8.00 |
March | 82646975.39 | 10529.81 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 11783151.01 | 8077.56 | 26-OCT-06:03 | 8.17 |
November | 71283333.75 | 10610.85 | 24-NOV-06:11 | 3.33 |
December | 0.436340E+09 | 11226.83 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.849493E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.436340E+09 | 11511.31 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59433349.99 | 8083.77 | 02-JAN-06:11 | 4.67 |
February | 51679330.57 | 7127.14 | 13-FEB-06:12 | 8.00 |
March | 38333759.69 | 7180.24 | 27-MAR-05:12 | 2.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 8258105.84 | 6789.44 | 25-OCT-06:02 | 5.00 |
November | 24776141.57 | 7317.08 | 24-NOV-06:11 | 3.33 |
December | 0.187675E+09 | 7876.67 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.370156E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.187675E+09 | 8083.77 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64223495.60 | 12107.28 | 02-JAN-06:11 | 4.67 |
February | 66531941.49 | 11269.34 | 13-FEB-06:12 | 8.00 |
March | 62938560.71 | 11188.83 | 27-MAR-05:12 | 2.33 |
April | 34166.01 | 170.83 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 6582754.22 | 7723.78 | 26-OCT-06:03 | 8.17 |
November | 27675912.17 | 11202.01 | 24-NOV-06:11 | 3.33 |
December | 0.225776E+09 | 11967.12 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.453763E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.225776E+09 | 12107.28 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79475408.47 | 7846.18 | 02-JAN-06:11 | 4.67 |
February | 75736866.90 | 6900.16 | 13-FEB-06:12 | 8.00 |
March | 51617869.22 | 6837.70 | 27-MAR-05:12 | 2.33 |
April | 175992.36 | 879.96 | 21-APR-06:03 | 9.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 9321362.16 | 6676.58 | 25-OCT-06:02 | 5.00 |
November | 43256517.13 | 7001.30 | 24-NOV-06:11 | 3.33 |
December | 0.266690E+09 | 7725.21 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.526274E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.33 | |
Maximum of Months | 0.266690E+09 | 7846.18 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16732468.19 | 7369.08 | 02-JAN-06:11 | 4.67 |
February | 10985739.82 | 6767.24 | 09-FEB-07:02 | 6.17 |
March | 12849592.53 | 6918.65 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 192524.68 | 1925.25 | 24-NOV-07:02 | 4.50 |
December | 20881009.62 | 6942.39 | 05-DEC-07:01 | -0.5 |
Annual Sum or Average | 61641334.84 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 20881009.62 | 7369.08 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4004337.58 | 4322.80 | 02-JAN-06:11 | 4.67 |
February | 3376382.01 | 4309.57 | 13-FEB-07:02 | 8.33 |
March | 2469190.22 | 4454.05 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 5543430.92 | 4517.45 | 06-DEC-07:02 | -0.5 |
Annual Sum or Average | 15393340.73 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 5543430.92 | 4517.45 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507753E+09 | 7821.88 | 02-JAN-07:10 | 6.00 |
February | 0.550054E+09 | 7887.08 | 08-FEB-07:10 | 6.17 |
March | 0.631525E+09 | 8590.92 | 27-MAR-06:10 | 1.97 |
April | 96969760.48 | 6998.19 | 21-APR-06:10 | 9.33 |
May | 3273604.69 | 5017.17 | 01-MAY-06:05 | 13.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.206483E+09 | 7529.20 | 25-OCT-06:10 | 5.00 |
November | 0.281768E+09 | 7632.44 | 24-NOV-07:08 | 4.50 |
December | 0.626734E+09 | 8909.91 | 06-DEC-07:10 | -0.5 |
Annual Sum or Average | 0.290456E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 0.631525E+09 | 8909.91 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3979716.63 | 4661.02 | 02-JAN-06:11 | 4.67 |
February | 5198585.46 | 4483.52 | 09-FEB-07:02 | 6.17 |
March | 2801633.54 | 4234.40 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 9305128.07 | 4567.85 | 19-DEC-07:02 | 4.00 |
Annual Sum or Average | 21285063.70 | |||
Minimum of Months | 0.00 | 0.00 | 3.90 | |
Maximum of Months | 9305128.07 | 4661.02 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22000320.51 | 8935.74 | 02-JAN-06:11 | 4.67 |
February | 11612813.99 | 8049.93 | 13-FEB-07:02 | 8.33 |
March | 8508632.41 | 8236.77 | 27-MAR-06:01 | 1.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 3567010.00 | 8121.91 | 24-NOV-07:02 | 4.50 |
December | 72925118.71 | 8636.75 | 18-DEC-06:11 | 3.67 |
Annual Sum or Average | 0.118614E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.97 | |
Maximum of Months | 72925118.71 | 8935.74 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12294313.82 | 5529.85 | 02-JAN-06:11 | 4.67 |
February | 8959447.83 | 5229.68 | 08-FEB-07:02 | 6.17 |
March | 5506469.27 | 4896.46 | 29-MAR-06:01 | 3.08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 48801.61 | 325.34 | 26-OCT-06:03 | 8.17 |
November | 1840652.94 | 5056.38 | 24-NOV-07:02 | 4.50 |
December | 34882039.09 | 5511.19 | 06-DEC-06:01 | 0.67 |
Annual Sum or Average | 63531724.56 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 34882039.09 | 5529.85 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8591779.45 | 8453.29 | 02-JAN-06:11 | 4.67 |
February | 5316983.41 | 7861.93 | 13-FEB-07:02 | 8.33 |
March | 4894242.30 | 8077.31 | 28-MAR-06:01 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 709180.58 | 7091.81 | 24-NOV-07:02 | 4.50 |
December | 29106375.69 | 8098.81 | 06-DEC-07:01 | -0.5 |
Annual Sum or Average | 48618561.43 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 29106375.69 | 8453.29 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13469089.81 | 5291.84 | 02-JAN-06:11 | 4.67 |
February | 10345686.78 | 5169.27 | 09-FEB-07:02 | 6.17 |
March | 5764136.88 | 5132.83 | 29-MAR-06:01 | 3.08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 27636.12 | 184.24 | 26-OCT-06:03 | 8.17 |
November | 2845996.09 | 4872.20 | 24-NOV-07:02 | 4.50 |
December | 50562200.14 | 5388.89 | 08-DEC-06:11 | 2.00 |
Annual Sum or Average | 83014745.83 | |||
Minimum of Months | 0.00 | 0.00 | 2.00 | |
Maximum of Months | 50562200.14 | 5388.89 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.830838E+09 | 1358.45 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.721444E+09 | 1358.45 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.790345E+09 | 1184.79 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668204E+09 | 947.97 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699872E+09 | 711.15 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.680816E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.648453E+09 | 774.31 | 10-JUL-15:39 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.752700E+09 | 1184.79 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.688427E+09 | 1184.79 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.781771E+09 | 1358.45 | 27-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.803788E+09 | 1358.45 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.821914E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.888857E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.648453E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.830838E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489096E+09 | 860.01 | 20-JAN-08:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.436995E+09 | 750.07 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490051E+09 | 600.14 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418213E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446457E+09 | 450.21 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.436448E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415703E+09 | 490.21 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.473857E+09 | 750.07 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430544E+09 | 490.21 | 18-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467393E+09 | 600.14 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.483957E+09 | 860.01 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.485990E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547470E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415703E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490051E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.740644E+09 | 1358.45 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.672707E+09 | 1184.79 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.765675E+09 | 1184.79 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671031E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.714257E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700282E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.666345E+09 | 947.97 | 10-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.758170E+09 | 1184.79 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680057E+09 | 947.97 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.714711E+09 | 1121.62 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.733407E+09 | 1358.45 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.732320E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854961E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.666345E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.765675E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503077E+09 | 859.95 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.444722E+09 | 859.95 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.496377E+09 | 859.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426805E+09 | 710.03 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451336E+09 | 560.12 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.440752E+09 | 560.12 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420599E+09 | 600.10 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.481636E+09 | 750.02 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436682E+09 | 750.02 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.478733E+09 | 859.95 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.486575E+09 | 859.95 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493290E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556058E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420599E+09 | 560.12 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.503077E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.822807E+09 | 1358.45 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.717899E+09 | 1358.45 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.787482E+09 | 1184.79 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.666856E+09 | 947.97 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699110E+09 | 711.15 | 25-MAY-12:20 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.680685E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.647593E+09 | 774.31 | 10-JUL-15:50 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.750317E+09 | 1184.79 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.686116E+09 | 947.97 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.776187E+09 | 1358.45 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.796834E+09 | 1358.45 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.815023E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.884691E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.647593E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.822807E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.487183E+09 | 860.01 | 20-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.435564E+09 | 750.07 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488692E+09 | 600.14 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.417792E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446069E+09 | 450.21 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.435726E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.414997E+09 | 490.21 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.472839E+09 | 750.07 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.429642E+09 | 490.21 | 29-SEP-14:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465863E+09 | 600.14 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.481384E+09 | 860.01 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.484020E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545977E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.414997E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.488692E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.740159E+09 | 1358.45 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.671575E+09 | 1184.79 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764371E+09 | 1184.79 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.669206E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.712676E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.698492E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.664096E+09 | 947.97 | 13-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.755659E+09 | 1184.79 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.678799E+09 | 947.97 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.713618E+09 | 1121.62 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.732873E+09 | 1358.45 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.731616E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853314E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664096E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.764371E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.500251E+09 | 859.95 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.443311E+09 | 859.95 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.495043E+09 | 859.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425443E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450406E+09 | 560.12 | 05-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439841E+09 | 450.19 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.419515E+09 | 600.10 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479949E+09 | 750.02 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435392E+09 | 750.02 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.477309E+09 | 859.95 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.484976E+09 | 859.95 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.491685E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.554312E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.419515E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.500251E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.830838E+09 | 1358.45 | 20-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.721444E+09 | 1358.45 | 03-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.790345E+09 | 1184.79 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668204E+09 | 947.97 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.699872E+09 | 711.15 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.680816E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.648453E+09 | 774.31 | 10-JUL-15:39 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.752700E+09 | 1184.79 | 04-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.688427E+09 | 1184.79 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.781771E+09 | 1358.45 | 27-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.803750E+09 | 1358.45 | 02-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.821914E+09 | 1358.45 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.888853E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.648453E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.830838E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489096E+09 | 860.01 | 20-JAN-08:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.436995E+09 | 750.07 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490051E+09 | 600.14 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.418213E+09 | 410.22 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446457E+09 | 450.21 | 25-MAY-15:09 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.436448E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415703E+09 | 490.21 | 10-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.473857E+09 | 750.07 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430544E+09 | 490.21 | 18-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467393E+09 | 600.14 | 13-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.483957E+09 | 860.01 | 28-NOV-16:19 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.485990E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547470E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.415703E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.490051E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.740644E+09 | 1358.45 | 20-JAN-08:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.672707E+09 | 1184.79 | 10-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.765673E+09 | 1184.79 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.671031E+09 | 947.97 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.714257E+09 | 711.15 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.700282E+09 | 711.15 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.666345E+09 | 947.97 | 10-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.758170E+09 | 1184.79 | 04-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.680057E+09 | 947.97 | 05-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.714711E+09 | 1121.62 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.733407E+09 | 1358.45 | 28-NOV-16:30 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.732320E+09 | 1358.45 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.854960E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.666345E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.765673E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503077E+09 | 859.95 | 20-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.444722E+09 | 859.95 | 03-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.496377E+09 | 859.95 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426805E+09 | 710.03 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451336E+09 | 560.12 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.440752E+09 | 560.12 | 22-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420599E+09 | 600.10 | 10-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.481636E+09 | 750.02 | 04-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436682E+09 | 750.02 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.478709E+09 | 859.95 | 27-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.486575E+09 | 859.95 | 02-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.493290E+09 | 859.95 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.556056E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.420599E+09 | 560.12 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.503077E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.830838E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1684759.53 | 0.154459E+09 |
February | 0.901968E+09 | 0.721444E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123696E+09 |
March | 0.107774E+10 | 0.790345E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1681643.87 | 0.165458E+09 |
April | 0.956342E+09 | 0.668204E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31091625.57 | 57003513.88 |
May | 0.103597E+10 | 0.699872E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57645219.36 | 36629492.77 |
June | 0.103308E+10 | 0.680816E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103120E+09 | 11390554.46 |
July | 0.959235E+09 | 0.648453E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101237E+09 | 9702867.85 |
August | 0.107774E+10 | 0.752700E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71079825.33 | 13271507.16 |
September | 0.956342E+09 | 0.688427E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52868014.69 | 25287090.58 |
October | 0.994195E+09 | 0.781771E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20829787.54 | 84678194.25 |
November | 0.984487E+09 | 0.803788E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2909032.69 | 0.141549E+09 |
December | 0.959235E+09 | 0.821914E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 844417.68 | 0.147775E+09 |
Annual Sum or Average | 0.119305E+11 | 0.888857E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444991E+09 | 0.970900E+09 |
Minimum of Months | 0.901968E+09 | 0.648453E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9702867.85 |
Maximum of Months | 0.107774E+10 | 0.830838E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103120E+09 | 0.165458E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.489096E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 695385.20 | 0.107617E+09 |
February | 0.571020E+09 | 0.436995E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85442929.80 |
March | 0.682301E+09 | 0.490051E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080002.44 | 0.114332E+09 |
April | 0.605444E+09 | 0.418213E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19811921.68 | 40419758.36 |
May | 0.655854E+09 | 0.446457E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37614415.24 | 25465002.33 |
June | 0.654023E+09 | 0.436448E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69186347.57 | 7759580.03 |
July | 0.607275E+09 | 0.415703E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67924721.72 | 6678384.37 |
August | 0.682301E+09 | 0.473857E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46811219.50 | 9341941.27 |
September | 0.605444E+09 | 0.430544E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34928275.31 | 17345869.06 |
October | 0.629407E+09 | 0.467393E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12984465.88 | 58967408.50 |
November | 0.623262E+09 | 0.483957E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388735.88 | 97878081.34 |
December | 0.607275E+09 | 0.485990E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354798.59 | 0.101483E+09 |
Annual Sum or Average | 0.755301E+10 | 0.547470E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292780E+09 | 0.672730E+09 |
Minimum of Months | 0.571020E+09 | 0.415703E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6678384.37 |
Maximum of Months | 0.682301E+09 | 0.490051E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69186347.57 | 0.114332E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.740644E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 537296.57 | 0.178780E+09 |
February | 0.901968E+09 | 0.672707E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134921E+09 |
March | 0.107774E+10 | 0.765675E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1498257.14 | 0.176181E+09 |
April | 0.956342E+09 | 0.671031E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28653345.07 | 59037645.01 |
May | 0.103597E+10 | 0.714257E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57413030.82 | 36420415.80 |
June | 0.103308E+10 | 0.700282E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104681E+09 | 11031473.80 |
July | 0.959235E+09 | 0.666345E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102014E+09 | 9483126.36 |
August | 0.107774E+10 | 0.758170E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70355658.80 | 13666530.45 |
September | 0.956342E+09 | 0.680057E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51057905.92 | 26792183.84 |
October | 0.994195E+09 | 0.714711E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17676794.28 | 93872806.68 |
November | 0.984487E+09 | 0.733407E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 972922.60 | 0.159263E+09 |
December | 0.959235E+09 | 0.732320E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47858.05 | 0.166619E+09 |
Annual Sum or Average | 0.119305E+11 | 0.854961E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434908E+09 | 0.106607E+10 |
Minimum of Months | 0.901968E+09 | 0.666345E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9483126.36 |
Maximum of Months | 0.107774E+10 | 0.765675E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104681E+09 | 0.178780E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.503077E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 755932.77 | 0.107786E+09 |
February | 0.570983E+09 | 0.444722E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84659088.85 |
March | 0.682256E+09 | 0.496377E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1092378.13 | 0.113777E+09 |
April | 0.605404E+09 | 0.426805E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18804590.26 | 40499169.19 |
May | 0.655811E+09 | 0.451336E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37341571.41 | 25711750.42 |
June | 0.653980E+09 | 0.440752E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68376948.03 | 8023316.74 |
July | 0.607235E+09 | 0.420599E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67038084.22 | 6817512.24 |
August | 0.682256E+09 | 0.481636E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46714247.64 | 9318133.44 |
September | 0.605404E+09 | 0.436682E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34828298.80 | 17487351.40 |
October | 0.629366E+09 | 0.478733E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13130568.78 | 58766232.62 |
November | 0.623221E+09 | 0.486575E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1498096.47 | 98072097.18 |
December | 0.607235E+09 | 0.493290E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 272641.61 | 0.101670E+09 |
Annual Sum or Average | 0.755252E+10 | 0.556058E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289853E+09 | 0.672588E+09 |
Minimum of Months | 0.570983E+09 | 0.420599E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6817512.24 |
Maximum of Months | 0.682256E+09 | 0.503077E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68376948.03 | 0.113777E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.822807E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819967.68 | 90272560.65 |
February | 0.901968E+09 | 0.717899E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70189554.75 |
March | 0.107774E+10 | 0.787482E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1009800.56 | 89916403.51 |
April | 0.956342E+09 | 0.666856E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18477923.78 | 30237720.06 |
May | 0.103597E+10 | 0.699110E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33274646.62 | 18934057.57 |
June | 0.103308E+10 | 0.680685E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56861710.52 | 5600062.59 |
July | 0.959235E+09 | 0.647593E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55610481.09 | 5127673.01 |
August | 0.107774E+10 | 0.750317E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38699186.50 | 7810066.82 |
September | 0.956342E+09 | 0.686116E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28847804.86 | 14689470.58 |
October | 0.994195E+09 | 0.776187E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11111263.62 | 51477102.84 |
November | 0.984487E+09 | 0.796834E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1315641.19 | 87411810.74 |
December | 0.959235E+09 | 0.815023E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 300048.62 | 89895444.51 |
Annual Sum or Average | 0.119305E+11 | 0.884691E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246328E+09 | 0.561562E+09 |
Minimum of Months | 0.901968E+09 | 0.647593E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5127673.01 |
Maximum of Months | 0.107774E+10 | 0.822807E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56861710.52 | 90272560.65 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.487183E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278351.81 | 64500150.86 |
February | 0.571020E+09 | 0.435564E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49415137.49 |
March | 0.682301E+09 | 0.488692E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591183.84 | 64066667.72 |
April | 0.605444E+09 | 0.417792E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11033325.64 | 22544792.53 |
May | 0.655854E+09 | 0.446069E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20637479.00 | 14012987.45 |
June | 0.654023E+09 | 0.435726E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37257087.56 | 4168828.04 |
July | 0.607275E+09 | 0.414997E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36420176.67 | 3866112.79 |
August | 0.682301E+09 | 0.472839E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24894427.68 | 5937254.80 |
September | 0.605444E+09 | 0.429642E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18678039.42 | 10633544.12 |
October | 0.629407E+09 | 0.465863E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6841113.97 | 36469269.78 |
November | 0.623262E+09 | 0.481384E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 619004.35 | 61265923.70 |
December | 0.607275E+09 | 0.484020E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108406.86 | 62906032.19 |
Annual Sum or Average | 0.755301E+10 | 0.545977E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157359E+09 | 0.399787E+09 |
Minimum of Months | 0.571020E+09 | 0.414997E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3866112.79 |
Maximum of Months | 0.682301E+09 | 0.488692E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37257087.56 | 64500150.86 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.740159E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44681694.36 | 0.224943E+10 |
February | 0.901968E+09 | 0.671575E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277884E+10 |
March | 0.107774E+10 | 0.764371E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149066E+09 | 0.227417E+10 |
April | 0.956342E+09 | 0.669206E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115403E+10 | 0.687315E+09 |
May | 0.103597E+10 | 0.712676E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201420E+10 | 0.301031E+09 |
June | 0.103308E+10 | 0.698492E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320484E+10 | 58635803.95 |
July | 0.959235E+09 | 0.664096E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258528E+10 | 20797384.23 |
August | 0.107774E+10 | 0.755659E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277445E+10 | 81473407.27 |
September | 0.956342E+09 | 0.678799E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186788E+10 | 0.201042E+09 |
October | 0.994195E+09 | 0.713618E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817207E+09 | 0.130960E+10 |
November | 0.984487E+09 | 0.732873E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94786947.89 | 0.208684E+10 |
December | 0.959235E+09 | 0.731616E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4569994.66 | 0.318754E+10 |
Annual Sum or Average | 0.119305E+11 | 0.853314E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147110E+11 | 0.152367E+11 |
Minimum of Months | 0.901968E+09 | 0.664096E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20797384.23 |
Maximum of Months | 0.107774E+10 | 0.764371E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320484E+10 | 0.318754E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.500251E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 292967.05 | 64769983.04 |
February | 0.570983E+09 | 0.443311E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48792635.31 |
March | 0.682256E+09 | 0.495043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574081.72 | 63538501.68 |
April | 0.605404E+09 | 0.425443E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10237010.68 | 22951037.63 |
May | 0.655811E+09 | 0.450406E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20114191.20 | 14471234.38 |
June | 0.653980E+09 | 0.439841E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36640967.66 | 4420429.12 |
July | 0.607235E+09 | 0.419515E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35780148.39 | 3950586.57 |
August | 0.682256E+09 | 0.479949E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24706240.06 | 5882479.88 |
September | 0.605404E+09 | 0.435392E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18497743.93 | 10738317.36 |
October | 0.629366E+09 | 0.477309E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6803077.87 | 36695633.17 |
November | 0.623221E+09 | 0.484976E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 619635.34 | 61693548.82 |
December | 0.607235E+09 | 0.491685E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70181.71 | 62609791.65 |
Annual Sum or Average | 0.755252E+10 | 0.554312E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154336E+09 | 0.400514E+09 |
Minimum of Months | 0.570983E+09 | 0.419515E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3950586.57 |
Maximum of Months | 0.682256E+09 | 0.500251E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36640967.66 | 64769983.04 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.830838E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096347.48 | 0.141952E+09 |
February | 0.901968E+09 | 0.721444E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112354E+09 |
March | 0.107774E+10 | 0.790345E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1387448.50 | 0.147964E+09 |
April | 0.956342E+09 | 0.668204E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26667763.29 | 50274169.89 |
May | 0.103597E+10 | 0.699872E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48883020.15 | 32288269.54 |
June | 0.103308E+10 | 0.680816E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86371066.67 | 9905317.60 |
July | 0.959235E+09 | 0.648453E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85136114.77 | 8379719.14 |
August | 0.107774E+10 | 0.752700E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59680257.73 | 11731620.03 |
September | 0.956342E+09 | 0.688427E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44414416.47 | 22152792.31 |
October | 0.994195E+09 | 0.781771E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17286597.28 | 76793686.93 |
November | 0.984487E+09 | 0.803750E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2146984.65 | 0.130121E+09 |
December | 0.959235E+09 | 0.821914E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497348.16 | 0.135547E+09 |
Annual Sum or Average | 0.119305E+11 | 0.888853E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373567E+09 | 0.879463E+09 |
Minimum of Months | 0.901968E+09 | 0.648453E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8379719.14 |
Maximum of Months | 0.107774E+10 | 0.830838E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86371066.67 | 0.147964E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.489096E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503429.94 | 97731332.29 |
February | 0.421807E+09 | 0.436995E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76662920.49 |
March | 0.502994E+09 | 0.490051E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 903842.93 | 0.101192E+09 |
April | 0.447140E+09 | 0.418213E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17071381.97 | 35199498.28 |
May | 0.484071E+09 | 0.446457E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31979614.02 | 22260815.99 |
June | 0.482240E+09 | 0.436448E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58081468.42 | 6718220.56 |
July | 0.448971E+09 | 0.415703E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57245525.15 | 5731582.76 |
August | 0.502994E+09 | 0.473857E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39394035.83 | 8195456.07 |
September | 0.447140E+09 | 0.430544E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29397989.20 | 15092566.86 |
October | 0.465148E+09 | 0.467393E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10916301.30 | 52705071.58 |
November | 0.460569E+09 | 0.483957E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085310.89 | 89000052.25 |
December | 0.448971E+09 | 0.485990E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229325.24 | 92429545.64 |
Annual Sum or Average | 0.557719E+10 | 0.547470E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246808E+09 | 0.602919E+09 |
Minimum of Months | 0.421807E+09 | 0.415703E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5731582.76 |
Maximum of Months | 0.502994E+09 | 0.490051E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58081468.42 | 0.101192E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.740644E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 451804.08 | 0.160868E+09 |
February | 0.901968E+09 | 0.672707E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121043E+09 |
March | 0.107774E+10 | 0.765673E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261076.99 | 0.156210E+09 |
April | 0.956342E+09 | 0.671031E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24200061.81 | 51990616.45 |
May | 0.103597E+10 | 0.714257E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48330747.76 | 32220670.04 |
June | 0.103308E+10 | 0.700282E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87592095.46 | 9625265.86 |
July | 0.959235E+09 | 0.666345E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85590104.00 | 8223974.85 |
August | 0.107774E+10 | 0.758170E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58872192.64 | 12080954.29 |
September | 0.956342E+09 | 0.680057E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42711907.21 | 23442230.91 |
October | 0.994195E+09 | 0.714711E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14725599.67 | 83880141.13 |
November | 0.984487E+09 | 0.733407E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 810264.69 | 0.143673E+09 |
December | 0.959235E+09 | 0.732320E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40981.75 | 0.150400E+09 |
Annual Sum or Average | 0.119305E+11 | 0.854960E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364587E+09 | 0.953658E+09 |
Minimum of Months | 0.901968E+09 | 0.666345E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8223974.85 |
Maximum of Months | 0.107774E+10 | 0.765673E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87592095.46 | 0.160868E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.503077E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 513427.80 | 98192621.81 |
February | 0.570983E+09 | 0.444722E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76315752.31 |
March | 0.682256E+09 | 0.496377E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864036.18 | 0.101309E+09 |
April | 0.605404E+09 | 0.426805E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15775721.45 | 35694281.13 |
May | 0.655811E+09 | 0.451336E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31155855.88 | 22733253.50 |
June | 0.653980E+09 | 0.440752E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57003714.86 | 6995668.74 |
July | 0.607235E+09 | 0.420599E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55966324.11 | 5894112.34 |
August | 0.682256E+09 | 0.481636E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38980079.72 | 8238693.62 |
September | 0.605404E+09 | 0.436682E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29032023.84 | 15340115.91 |
October | 0.629366E+09 | 0.478709E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10805508.78 | 53026324.84 |
November | 0.623221E+09 | 0.486575E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096937.03 | 89438951.71 |
December | 0.607235E+09 | 0.493290E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141847.03 | 92565004.21 |
Annual Sum or Average | 0.755252E+10 | 0.556056E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241335E+09 | 0.605744E+09 |
Minimum of Months | 0.570983E+09 | 0.420599E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5894112.34 |
Maximum of Months | 0.682256E+09 | 0.503077E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57003714.86 | 0.101309E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391702.51 | 0.214222E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165383E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301506.49 | 0.214073E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29587053.05 | 72076467.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57657928.53 | 44738374.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106604E+09 | 12748255.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105679E+09 | 10858465.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72334491.25 | 16256873.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52394152.37 | 30213159.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18002747.64 | 0.114187E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1251621.98 | 0.195494E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127803.06 | 0.204837E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445332E+09 | 0.129509E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10858465.37 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106604E+09 | 0.214222E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769106.23 | 0.258427E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200484E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1881560.40 | 0.265388E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39105644.32 | 90907887.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74791431.05 | 56911122.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137477E+09 | 16492761.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137037E+09 | 13794682.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94251432.72 | 19786644.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69007393.56 | 37332834.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24829537.60 | 0.138887E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2526404.72 | 0.235443E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387879.74 | 0.245563E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582065E+09 | 0.157942E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13794682.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137477E+09 | 0.265388E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342393.77 | 0.242449E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196669E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 971023.34 | 0.259292E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32953289.15 | 84868333.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70011464.38 | 48501162.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143879E+09 | 13504297.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138191E+09 | 11486801.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98288743.06 | 16668198.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70038338.29 | 33384754.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23483983.19 | 0.130733E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1224248.76 | 0.220679E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103340.50 | 0.228886E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579486E+09 | 0.148712E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11486801.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143879E+09 | 0.259292E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 16-JAN-11:55 | 286.80 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 375.99 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.64 | 18-MAR-17:03 | 319.26 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.07 | 30-APR-15:50 | 165.66 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.09 | 20-MAY-17:02 | 139.21 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.83 | 17-JUN-17:03 | 71.00 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 10-JUL-15:39 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.19 | 22-JUL-17:45 | 114.85 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.68 | 13-AUG-15:55 | 173.02 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.47 | 17-SEP-12:48 | 120.12 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 27-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.16 | 01-OCT-14:48 | 333.76 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.73 | 19-NOV-12:55 | 313.12 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.26 | 25-DEC-16:00 | 264.76 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 419.19 | 375.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 20-JAN-08:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 29-JAN-16:00 | 195.41 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 253.59 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 18-MAR-17:03 | 213.34 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.58 | 30-APR-15:50 | 164.14 | 16-APR-08:40 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.29 | 20-MAY-17:50 | 92.48 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.95 | 17-JUN-18:33 | 51.21 | 11-JUN-06:20 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.58 | 22-JUL-17:50 | 76.70 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.47 | 13-AUG-15:55 | 116.75 | 05-AUG-17:50 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 18-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 | 17-SEP-12:48 | 79.84 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.06 | 01-OCT-14:50 | 242.62 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.40 | 19-NOV-14:50 | 209.66 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 25-DEC-16:00 | 176.40 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.21 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 283.58 | 253.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 31-JAN-14:00 | 324.33 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 405.15 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 | 15-MAR-13:00 | 326.98 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.33 | 30-APR-15:46 | 166.82 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.76 | 20-MAY-18:00 | 139.12 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.25 | 17-JUN-17:03 | 70.60 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 10-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.63 | 22-JUL-17:45 | 114.20 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.59 | 13-AUG-15:55 | 177.63 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.72 | 17-SEP-12:48 | 121.82 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1121.62 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.48 | 01-OCT-14:45 | 398.18 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 01-NOV-16:00 | 327.69 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 | 21-DEC-15:00 | 274.52 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 421.63 | 405.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.59 | 16-JAN-11:55 | 201.74 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 259.85 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 15-MAR-13:00 | 216.87 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 710.03 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 | 30-APR-15:04 | 117.13 | 26-APR-21:20 |
May | 827.17 | 01-MAY-09:09 | 560.12 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.07 | 20-MAY-18:30 | 94.68 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 560.12 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.93 | 17-JUN-17:03 | 49.31 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.32 | 22-JUL-18:00 | 81.80 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.06 | 13-AUG-15:55 | 117.36 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.07 | 17-SEP-12:10 | 79.69 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 | 01-OCT-14:48 | 226.31 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.62 | 19-NOV-12:10 | 209.09 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 | 25-DEC-14:00 | 177.73 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 560.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 275.32 | 259.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 | 16-JAN-12:10 | 177.64 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 212.37 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 18-MAR-17:03 | 179.91 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.78 | 30-APR-15:30 | 95.32 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 25-MAY-12:20 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.57 | 20-MAY-18:00 | 76.80 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.96 | 17-JUN-17:03 | 38.36 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 10-JUL-15:50 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.10 | 22-JUL-18:00 | 62.71 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.34 | 13-AUG-15:55 | 93.87 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.08 | 17-SEP-12:00 | 71.89 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 | 01-OCT-14:28 | 189.84 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 | 19-NOV-15:00 | 190.41 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 25-DEC-15:52 | 158.07 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.36 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 224.10 | 212.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 20-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 29-JAN-16:00 | 125.47 | 01-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 148.55 | 02-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 18-MAR-17:03 | 124.95 | 28-MAR-04:00 |
April | 827.22 | 03-APR-09:09 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 | 30-APR-15:50 | 81.29 | 16-APR-08:30 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.94 | 20-MAY-17:50 | 52.89 | 23-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.34 | 17-JUN-19:00 | 27.90 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.02 | 22-JUL-18:00 | 44.00 | 26-JUL-24:00 |
August | 827.22 | 01-AUG-09:09 | 750.07 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.26 | 13-AUG-15:55 | 64.39 | 05-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 29-SEP-14:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 | 17-SEP-12:20 | 49.26 | 03-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 | 01-OCT-15:10 | 138.05 | 22-OCT-14:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 19-NOV-15:00 | 131.10 | 29-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 25-DEC-16:10 | 107.36 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 154.02 | 148.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.94 | 31-JAN-17:10 | 18139.12 | 12-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 18436.56 | 01-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5346.13 | 20-MAR-17:00 | 21261.72 | 27-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11363.90 | 14-APR-16:02 | 13385.55 | 21-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13431.32 | 31-MAY-16:02 | 10070.97 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18483.14 | 28-JUN-16:01 | 4383.82 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 13-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15489.86 | 20-JUL-16:01 | 1917.50 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17364.03 | 25-AUG-16:01 | 4821.21 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13819.25 | 08-SEP-16:01 | 6972.57 | 22-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1121.62 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10903.65 | 03-OCT-16:02 | 18711.51 | 25-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3466.23 | 01-NOV-16:05 | 19114.23 | 24-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.90 | 21-DEC-15:00 | 24482.54 | 05-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1917.50 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18483.14 | 24482.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 | 16-JAN-12:10 | 128.84 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 150.77 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 15-MAR-13:00 | 126.47 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.60 | 30-APR-15:04 | 66.13 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 560.12 | 05-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.79 | 20-MAY-18:30 | 54.61 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.84 | 17-JUN-17:03 | 28.43 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.08 | 22-JUL-18:00 | 46.44 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.03 | 13-AUG-15:55 | 64.22 | 05-AUG-17:50 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.61 | 17-SEP-12:20 | 48.72 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 | 01-OCT-14:28 | 130.51 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.94 | 19-NOV-12:20 | 130.86 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 25-DEC-13:42 | 107.42 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 147.08 | 150.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 | 16-JAN-11:53 | 272.11 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 03-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 338.79 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 18-MAR-17:03 | 287.68 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.78 | 30-APR-15:10 | 149.04 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.91 | 20-MAY-18:00 | 123.31 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.03 | 17-JUN-17:03 | 62.28 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 10-JUL-15:39 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.83 | 22-JUL-17:45 | 96.19 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.98 | 13-AUG-15:55 | 142.84 | 05-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 1184.79 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.10 | 17-SEP-12:00 | 103.21 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 27-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.98 | 01-OCT-14:36 | 289.83 | 22-OCT-14:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 02-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.75 | 19-NOV-12:53 | 285.65 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 25-DEC-16:00 | 239.61 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.28 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 346.83 | 338.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 20-JAN-08:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 29-JAN-16:00 | 184.44 | 01-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 226.79 | 02-FEB-23:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 | 18-MAR-17:03 | 191.80 | 28-MAR-04:00 |
April | 805.43 | 03-APR-07:10 | 410.22 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.75 | 30-APR-15:30 | 144.86 | 16-APR-09:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 25-MAY-15:09 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.74 | 20-MAY-17:50 | 81.85 | 23-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.01 | 17-JUN-19:00 | 44.50 | 11-JUN-06:10 |
July | 805.43 | 03-JUL-07:10 | 490.21 | 10-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.11 | 22-JUL-18:00 | 64.23 | 26-JUL-24:00 |
August | 805.43 | 01-AUG-07:10 | 750.07 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.55 | 13-AUG-15:55 | 96.26 | 05-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 490.21 | 18-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.40 | 17-SEP-12:30 | 68.55 | 03-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 600.14 | 13-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.36 | 01-OCT-15:20 | 210.05 | 22-OCT-13:55 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 28-NOV-16:19 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.39 | 19-NOV-14:50 | 190.39 | 29-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 25-DEC-16:00 | 159.46 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 243.11 | 226.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 20-JAN-08:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 31-JAN-14:10 | 302.06 | 01-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 10-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 361.94 | 02-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 15-MAR-13:00 | 293.72 | 28-MAR-04:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.56 | 30-APR-15:24 | 149.96 | 21-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.10 | 20-MAY-18:00 | 123.22 | 23-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.47 | 17-JUN-19:00 | 61.93 | 13-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 10-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.35 | 22-JUL-18:00 | 95.66 | 26-JUL-24:00 |
August | 1306.65 | 01-AUG-09:09 | 1184.79 | 04-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.70 | 13-AUG-15:55 | 146.43 | 05-AUG-17:50 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.05 | 17-SEP-12:30 | 104.58 | 03-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1121.62 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.80 | 01-OCT-14:34 | 344.25 | 22-OCT-13:55 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 28-NOV-16:30 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 01-NOV-16:00 | 296.82 | 29-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 21-DEC-15:00 | 247.78 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 353.35 | 361.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 20-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.62 | 16-JAN-12:10 | 189.38 | 01-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 03-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 232.71 | 02-FEB-23:00 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 15-MAR-13:00 | 194.86 | 28-MAR-04:00 |
April | 827.17 | 03-APR-09:09 | 710.03 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.51 | 30-APR-15:24 | 100.40 | 21-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 560.12 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.97 | 20-MAY-18:30 | 83.77 | 23-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 560.12 | 22-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.73 | 17-JUN-17:03 | 43.18 | 13-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 10-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.73 | 22-JUL-18:00 | 68.41 | 26-JUL-24:00 |
August | 827.17 | 01-AUG-09:09 | 750.02 | 04-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.80 | 13-AUG-15:55 | 97.01 | 05-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.18 | 17-SEP-12:00 | 68.46 | 03-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 27-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 01-OCT-15:18 | 197.42 | 22-OCT-14:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 02-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 | 19-NOV-12:53 | 190.43 | 29-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 25-DEC-13:42 | 160.48 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 560.12 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.18 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 229.73 | 232.71 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 31-JAN-14:00 | 421.73 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 500.18 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 | 18-MAR-17:03 | 418.66 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.22 | 30-APR-14:52 | 214.29 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.77 | 20-MAY-17:02 | 173.48 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.80 | 17-JUN-17:03 | 84.91 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.46 | 22-JUL-18:00 | 128.81 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.15 | 13-AUG-16:00 | 196.07 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.15 | 17-SEP-12:00 | 146.49 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.69 | 01-OCT-14:40 | 392.86 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 | 19-NOV-14:53 | 421.74 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 25-DEC-13:52 | 353.03 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.91 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.46 | 500.18 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 16-JAN-12:00 | 494.05 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 621.18 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 | 18-MAR-17:03 | 520.04 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.35 | 30-APR-15:10 | 270.59 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.81 | 20-MAY-17:02 | 220.90 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.40 | 17-JUN-17:03 | 108.35 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.52 | 22-JUL-18:00 | 163.97 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.56 | 13-AUG-16:00 | 246.88 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.87 | 17-SEP-12:00 | 181.76 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.32 | 01-OCT-14:40 | 477.17 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.15 | 19-NOV-15:00 | 516.35 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.80 | 25-DEC-15:52 | 434.99 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.52 | 621.18 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 16-JAN-11:53 | 436.27 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 567.61 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 | 15-MAR-13:00 | 476.62 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.56 | 30-APR-16:00 | 251.38 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.88 | 20-MAY-17:02 | 197.69 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 | 17-JUN-17:03 | 95.69 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.76 | 22-JUL-18:00 | 170.34 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.88 | 13-AUG-16:00 | 287.13 | 05-AUG-17:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.90 | 17-SEP-11:53 | 181.72 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.79 | 01-OCT-14:23 | 605.52 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 | 19-NOV-15:10 | 466.00 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 25-DEC-13:42 | 395.03 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.69 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.76 | 605.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35608.06 | 30-JAN-07:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35454.28 | 01-FEB-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36469.15 | 20-MAR-06:03 | 3811.58 | 6444.06 | 30584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39667.18 | 26-APR-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40626.51 | 30-MAY-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41118.72 | 09-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41069.36 | 26-JUL-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41855.22 | 29-AUG-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41351.92 | 01-SEP-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40570.87 | 10-OCT-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38243.91 | 13-NOV-07:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35515.57 | 27-DEC-07:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35454.28 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41855.22 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6027.04 | 31-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 0.00 |
February | 4375.61 | 23-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 |
March | 7187.76 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 0.00 |
April | 11307.08 | 14-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 |
May | 11089.55 | 19-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.14 | 0.00 |
June | 13476.34 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 0.00 |
July | 12689.57 | 20-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.29 | 0.00 |
August | 12767.89 | 25-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 0.00 |
September | 11829.11 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.39 | 0.00 |
October | 10696.72 | 02-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 | 0.00 |
November | 7217.42 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 |
December | 4712.99 | 22-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4375.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13476.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 31.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2079.88 | 27-JAN-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 0.00 |
February | 1798.18 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 |
March | 2647.26 | 28-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.45 |
April | 4616.86 | 24-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 0.00 |
May | 5084.77 | 08-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.12 | 0.00 |
June | 6291.49 | 19-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.94 | 0.00 |
July | 6004.81 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.26 | 0.00 |
August | 6171.37 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 0.00 |
September | 5816.55 | 05-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 0.00 |
October | 5619.48 | 02-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.37 | 0.00 |
November | 2955.95 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 | 0.00 |
December | 2653.89 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1798.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6291.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.94 | 111.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2902.19 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 | 0.00 |
February | 2936.27 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 |
March | 3282.86 | 20-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 |
April | 5032.71 | 14-APR-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.08 | 0.00 |
May | 5955.03 | 08-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 0.00 |
June | 7797.87 | 26-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.55 | 0.00 |
July | 7823.54 | 10-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 0.00 |
August | 6831.61 | 11-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 | 0.00 |
September | 6758.96 | 05-SEP-17:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 | 0.00 |
October | 6014.98 | 04-OCT-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 0.00 |
November | 3784.04 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 |
December | 2876.76 | 06-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2876.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7823.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 | 70.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14007.58 | 27-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12799.52 | 01-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14865.56 | 20-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28296.36 | 24-APR-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32642.65 | 30-MAY-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32833.36 | 12-JUN-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33435.38 | 18-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33204.58 | 17-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32738.62 | 11-SEP-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32102.01 | 10-OCT-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15477.49 | 02-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12833.28 | 27-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12799.52 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33435.38 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13936.39 | 27-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12081.98 | 22-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16032.08 | 17-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19392.04 | 24-APR-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25988.10 | 08-MAY-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35883.44 | 27-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36454.89 | 26-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36461.98 | 21-AUG-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36164.30 | 08-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35709.65 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16341.06 | 01-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12324.70 | 22-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12081.98 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36461.98 | 6035.01 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3002.09 | 31-JAN-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
February | 2198.61 | 22-FEB-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
March | 4290.64 | 16-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 0.00 |
April | 6433.32 | 25-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 0.00 |
May | 10689.81 | 07-MAY-17:32 | 0.00 | 215.99 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 158.84 | 0.00 |
June | 14019.37 | 25-JUN-18:11 | 0.00 | 251.99 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 253.76 | 0.00 |
July | 14145.96 | 23-JUL-12:42 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 306.86 | 0.00 |
August | 13875.46 | 13-AUG-16:51 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 301.43 | 0.00 |
September | 13749.98 | 17-SEP-16:02 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 77.93 | 0.00 |
October | 10933.73 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
November | 4248.63 | 01-NOV-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 |
December | 2175.01 | 22-DEC-16:50 | 1272.23 | 1121.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2175.01 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14145.96 | 1272.23 | 1121.62 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 306.86 | 17.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3017.29 | 27-JAN-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 |
February | 3221.92 | 23-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 |
March | 4615.23 | 23-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 |
April | 11083.92 | 30-APR-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
May | 11851.50 | 29-MAY-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
June | 13238.75 | 18-JUN-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 48.48 | 0.00 |
July | 14107.08 | 23-JUL-09:21 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 0.00 |
August | 13162.40 | 13-AUG-09:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 0.00 |
September | 11801.38 | 10-SEP-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 | 0.00 |
October | 9262.53 | 01-OCT-11:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 0.00 |
November | 3881.30 | 01-NOV-10:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 1937.88 | 25-DEC-15:52 | 211.95 | 125.06 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1937.88 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14107.08 | 827.22 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.48 | 13.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16148.53 | 16-JAN-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.57 |
February | 9514.71 | 28-FEB-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
March | 8904.54 | 16-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 0.00 |
April | 15638.20 | 23-APR-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 43.86 | 0.00 |
May | 12958.60 | 07-MAY-15:32 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 0.00 |
June | 15050.50 | 04-JUN-16:41 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 0.00 |
July | 15813.46 | 23-JUL-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 191.86 | 0.00 |
August | 15535.68 | 13-AUG-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 208.31 | 0.00 |
September | 15998.13 | 10-SEP-13:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 136.94 | 0.00 |
October | 17267.92 | 09-OCT-13:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 0.00 |
November | 16158.16 | 19-NOV-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.70 |
December | 16780.80 | 25-DEC-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8904.54 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17267.92 | 1306.65 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 208.31 | 63.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6093.83 | 31-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 0.00 |
February | 5999.43 | 22-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 |
March | 8329.24 | 18-MAR-17:08 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 0.00 |
April | 14785.72 | 02-APR-16:41 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 0.00 |
May | 14894.85 | 28-MAY-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 81.47 | 0.00 |
June | 15349.58 | 25-JUN-17:31 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 140.20 | 0.00 |
July | 15426.55 | 16-JUL-16:51 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 156.72 | 0.00 |
August | 15309.98 | 13-AUG-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 177.18 | 0.00 |
September | 14139.85 | 17-SEP-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 0.00 |
October | 15084.07 | 09-OCT-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 0.00 |
November | 7373.97 | 01-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 0.00 |
December | 6105.29 | 22-DEC-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5999.43 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15426.55 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 177.18 | 11.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2274.07 | 27-JAN-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 0.00 |
February | 1541.92 | 22-FEB-16:40 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
March | 2972.09 | 20-MAR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 | 0.00 |
April | 5012.50 | 25-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.92 | 0.00 |
May | 5640.41 | 08-MAY-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 0.00 |
June | 11572.81 | 11-JUN-18:11 | 0.00 | 287.98 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 | 0.00 |
July | 11677.26 | 02-JUL-18:21 | 0.00 | 251.99 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 | 0.00 |
August | 11705.21 | 27-AUG-17:41 | 0.00 | 316.06 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 109.57 | 0.00 |
September | 11406.16 | 17-SEP-16:12 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 0.00 |
October | 9611.74 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
November | 4027.23 | 02-NOV-14:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 0.00 |
December | 2003.79 | 26-DEC-14:00 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1541.92 | 0.00 | 179.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11705.21 | 1306.65 | 711.15 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 | 8.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2917.18 | 27-JAN-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.27 |
February | 2640.42 | 23-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 |
March | 3677.69 | 23-MAR-10:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
April | 8704.14 | 23-APR-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
May | 10316.29 | 21-MAY-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
June | 11667.04 | 11-JUN-10:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
July | 12107.87 | 23-JUL-09:21 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
August | 11763.33 | 27-AUG-11:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 0.00 |
September | 11446.51 | 10-SEP-11:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 23.39 | 0.00 |
October | 8763.52 | 15-OCT-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 |
November | 4088.75 | 02-NOV-08:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
December | 2523.90 | 01-DEC-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2523.90 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12107.87 | 827.22 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 | 7.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13863.44 | 29-JAN-14:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
February | 7783.56 | 28-FEB-13:07 | 3816.70 | 1943.94 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.29 |
March | 10269.07 | 16-MAR-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5259.86 | 0.00 |
April | 12234.74 | 14-APR-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9894.54 | 0.00 |
May | 12695.37 | 15-MAY-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11475.54 | 0.00 |
June | 14611.35 | 28-JUN-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14569.17 | 0.00 |
July | 13731.52 | 20-JUL-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 12598.88 | 0.00 |
August | 14425.41 | 25-AUG-17:00 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13755.80 | 0.00 |
September | 14169.81 | 10-SEP-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 0.00 |
October | 14591.25 | 09-OCT-13:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 0.00 |
November | 13520.72 | 19-NOV-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 |
December | 13792.34 | 24-DEC-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7783.56 | 267.84 | 143.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14611.35 | 3816.70 | 1943.94 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 14569.17 | 1148.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6920.87 | 29-JAN-16:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
February | 4408.73 | 22-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
March | 5507.43 | 18-MAR-17:10 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
April | 12011.41 | 23-APR-17:11 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 | 0.00 |
May | 12308.83 | 07-MAY-16:41 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 0.00 |
June | 13271.81 | 11-JUN-17:31 | 0.00 | 205.09 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 0.00 |
July | 12838.33 | 04-JUL-18:11 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 53.32 | 0.00 |
August | 13195.55 | 27-AUG-17:41 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 | 0.00 |
September | 11812.01 | 10-SEP-14:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 | 0.00 |
October | 12431.63 | 15-OCT-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 0.00 |
November | 6714.52 | 01-NOV-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 0.00 |
December | 6151.92 | 24-DEC-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4408.73 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13271.81 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 | 20.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2972.82 | 31-JAN-16:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 | 0.00 |
February | 2172.52 | 22-FEB-16:20 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
March | 4116.38 | 20-MAR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
April | 5874.32 | 25-APR-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 | 0.00 |
May | 6869.19 | 08-MAY-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
June | 12097.55 | 11-JUN-18:11 | 0.00 | 287.98 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 81.27 | 0.00 |
July | 11943.44 | 16-JUL-18:22 | 0.00 | 215.99 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 160.29 | 0.00 |
August | 11855.59 | 27-AUG-15:51 | 669.60 | 359.98 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 217.78 | 0.00 |
September | 11678.62 | 10-SEP-16:52 | 334.80 | 197.54 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 183.88 | 0.00 |
October | 9964.77 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
November | 4009.86 | 01-NOV-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 | 0.00 |
December | 2224.79 | 22-DEC-16:50 | 1272.23 | 1121.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2172.52 | 0.00 | 197.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12097.55 | 1272.23 | 1121.62 | 4784.15 | 0.00 | 0.00 | 0.00 | 0.00 | 217.78 | 13.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3567.72 | 27-JAN-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
February | 3749.78 | 23-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 |
March | 4847.93 | 23-MAR-10:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
April | 11615.29 | 09-APR-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 |
May | 11802.99 | 21-MAY-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
June | 13003.71 | 11-JUN-08:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 13285.48 | 04-JUL-09:41 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 0.00 |
August | 13340.14 | 27-AUG-09:11 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.42 | 0.00 |
September | 12874.48 | 10-SEP-10:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 | 0.00 |
October | 8476.21 | 01-OCT-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 0.00 |
November | 4380.26 | 10-NOV-09:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
December | 2528.69 | 27-DEC-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2528.69 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13340.14 | 805.43 | 410.22 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.42 | 14.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14529.30 | 15-JAN-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 |
February | 9394.02 | 28-FEB-14:00 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 |
March | 8516.12 | 23-MAR-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 0.00 |
April | 13835.67 | 30-APR-13:23 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 121.04 | 0.00 |
May | 11764.19 | 07-MAY-13:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 0.00 |
June | 12924.52 | 11-JUN-17:31 | 0.00 | 355.56 | 3474.90 | 0.00 | 0.00 | 0.00 | 0.00 | 95.88 | 0.00 |
July | 13117.08 | 30-JUL-17:01 | 0.00 | 251.99 | 2702.70 | 0.00 | 0.00 | 0.00 | 0.00 | 217.65 | 0.00 |
August | 13710.06 | 27-AUG-11:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 113.07 | 0.00 |
September | 14359.43 | 10-SEP-10:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 | 0.00 |
October | 14157.60 | 09-OCT-13:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
November | 14444.60 | 05-NOV-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 |
December | 15012.27 | 25-DEC-13:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8516.12 | 0.00 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15012.27 | 1306.65 | 647.98 | 3474.90 | 0.00 | 0.00 | 0.00 | 0.00 | 217.65 | 66.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5959.48 | 24-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
February | 5894.82 | 22-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 |
March | 7491.31 | 18-MAR-17:08 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
April | 13099.90 | 23-APR-16:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 70.87 | 0.00 |
May | 13417.94 | 21-MAY-17:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 76.08 | 0.00 |
June | 14643.32 | 11-JUN-17:31 | 0.00 | 205.09 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 | 0.00 |
July | 13603.53 | 30-JUL-17:01 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 128.55 | 0.00 |
August | 14327.73 | 06-AUG-17:01 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 0.00 |
September | 13845.27 | 04-SEP-16:51 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 | 0.00 |
October | 11526.61 | 15-OCT-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 | 0.00 |
November | 7564.15 | 19-NOV-16:03 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
December | 7221.75 | 24-DEC-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5894.82 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14643.32 | 805.38 | 410.20 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 128.55 | 33.37 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.117808E+12 | 132810.82 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 0.979336E+11 | 102676.11 | 13-FEB-07:10 | 0.00 | 0.00 |
March | 0.120770E+12 | 121794.63 | 16-MAR-15:50 | 0.00 | 0.00 |
April | 0.139447E+12 | 154246.06 | 14-APR-15:20 | 0.00 | 0.00 |
May | 0.161109E+12 | 159260.00 | 31-MAY-15:00 | 0.00 | 0.00 |
June | 0.189332E+12 | 186009.55 | 28-JUN-14:00 | 0.00 | 0.00 |
July | 0.179461E+12 | 175285.97 | 31-JUL-15:00 | 0.00 | 0.00 |
August | 0.187628E+12 | 179897.09 | 25-AUG-15:20 | 0.00 | 0.00 |
September | 0.163213E+12 | 168862.03 | 08-SEP-15:00 | 0.00 | 0.00 |
October | 0.137014E+12 | 153894.41 | 02-OCT-15:20 | 0.00 | 0.00 |
November | 0.115593E+12 | 122706.57 | 01-NOV-15:50 | 0.00 | 0.00 |
December | 0.112727E+12 | 129321.77 | 06-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.172204E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.979336E+11 | 102676.11 | 0.00 | 0.00 | |
Maximum of Months | 0.189332E+12 | 186009.55 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.256714E+11 | 0.534996E+10 | 0.605851E+11 | 0.225890E+10 | 0.655201E+10 | 12379742.02 | 0.196952E+10 | 0.112695E+11 | 0.00 | 0.00 | 0.00 | 0.413948E+10 | 0.00 |
February | 0.231443E+11 | 0.443448E+10 | 0.548702E+11 | 0.204970E+10 | 0.471443E+10 | 11196021.66 | 0.223879E+10 | 0.274329E+10 | 0.00 | 0.00 | 0.00 | 0.372719E+10 | 0.00 |
March | 0.270630E+11 | 0.438976E+10 | 0.627783E+11 | 0.235658E+10 | 0.662393E+10 | 12675672.10 | 0.195402E+10 | 0.113961E+11 | 0.00 | 0.00 | 0.00 | 0.419593E+10 | 0.00 |
April | 0.238685E+11 | 0.375368E+10 | 0.586172E+11 | 0.219333E+10 | 0.127788E+11 | 11960507.72 | 0.142191E+09 | 0.345669E+11 | 0.00 | 0.00 | 0.00 | 0.351445E+10 | 0.00 |
May | 0.256502E+11 | 0.344793E+10 | 0.616817E+11 | 0.230728E+10 | 0.164861E+11 | 12527707.06 | 6526175.47 | 0.480741E+11 | 0.00 | 0.00 | 0.00 | 0.344263E+10 | 0.00 |
June | 0.254156E+11 | 0.318457E+10 | 0.604966E+11 | 0.226940E+10 | 0.222313E+11 | 12231776.97 | 0.00 | 0.725732E+11 | 0.00 | 0.00 | 0.00 | 0.314953E+10 | 0.00 |
July | 0.238429E+11 | 0.336971E+10 | 0.597911E+11 | 0.223022E+10 | 0.200779E+11 | 12256437.81 | 0.00 | 0.672706E+11 | 0.00 | 0.00 | 0.00 | 0.286640E+10 | 0.00 |
August | 0.268337E+11 | 0.370764E+10 | 0.627783E+11 | 0.235637E+10 | 0.203919E+11 | 12675672.10 | 0.00 | 0.683591E+11 | 0.00 | 0.00 | 0.00 | 0.318822E+10 | 0.00 |
September | 0.240221E+11 | 0.400092E+10 | 0.585950E+11 | 0.219220E+10 | 0.163776E+11 | 11960507.72 | 0.00 | 0.549419E+11 | 0.00 | 0.00 | 0.00 | 0.307164E+10 | 0.00 |
October | 0.253122E+11 | 0.467103E+10 | 0.605962E+11 | 0.225945E+10 | 0.109577E+11 | 12379742.02 | 0.463756E+09 | 0.292821E+11 | 0.00 | 0.00 | 0.00 | 0.345944E+10 | 0.00 |
November | 0.253067E+11 | 0.505049E+10 | 0.591197E+11 | 0.220151E+10 | 0.723277E+10 | 12059151.09 | 0.102326E+10 | 0.119450E+11 | 0.00 | 0.00 | 0.00 | 0.370180E+10 | 0.00 |
December | 0.249842E+11 | 0.551714E+10 | 0.597800E+11 | 0.223019E+10 | 0.555526E+10 | 12256437.81 | 0.536451E+10 | 0.536895E+10 | 0.00 | 0.00 | 0.00 | 0.391466E+10 | 0.00 |
Annual Sum or Average | 0.301115E+12 | 0.508773E+11 | 0.719689E+12 | 0.269051E+11 | 0.149980E+12 | 0.146559E+09 | 0.131626E+11 | 0.417791E+12 | 0.00 | 0.00 | 0.00 | 0.423714E+11 | 0.00 |
Minimum of Months | 0.231443E+11 | 0.318457E+10 | 0.548702E+11 | 0.204970E+10 | 0.471443E+10 | 11196021.66 | 0.00 | 0.274329E+10 | 0.00 | 0.00 | 0.00 | 0.286640E+10 | 0.00 |
Maximum of Months | 0.270630E+11 | 0.551714E+10 | 0.627783E+11 | 0.235658E+10 | 0.222313E+11 | 12675672.10 | 0.536451E+10 | 0.725732E+11 | 0.00 | 0.00 | 0.00 | 0.419593E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 20-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 04-JAN-08:09 | 12003.47 | 27-JAN-16:49 | 6.85 | 12-JAN-08:09 | 87536.85 | 02-JAN-07:10 |
February | 30940.97 | 10-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:09 | 9056.46 | 22-FEB-16:30 | 6.85 | 01-FEB-08:09 | 57270.25 | 13-FEB-07:10 |
March | 30701.00 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 07-MAR-12:09 | 14518.39 | 20-MAR-14:30 | 6.85 | 14-MAR-07:10 | 67256.69 | 27-MAR-06:10 |
April | 28270.60 | 04-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-07:19 | 23849.47 | 24-APR-15:50 | 6.85 | 02-APR-16:40 | 10578.01 | 21-APR-06:10 |
May | 26419.98 | 26-MAY-08:30 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 02-MAY-07:10 | 26521.45 | 08-MAY-15:00 | 6.85 | 07-MAY-15:30 | 2922.24 | 01-MAY-06:10 |
June | 26210.40 | 22-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-16:10 | 29826.93 | 19-JUN-14:50 | 6.85 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 27340.27 | 27-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-12:09 | 27664.01 | 05-JUL-15:20 | 6.85 | 01-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 30940.97 | 04-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-16:10 | 27809.03 | 14-AUG-15:20 | 6.85 | 08-AUG-12:09 | 0.00 | 01-AUG-00:10 |
September | 29094.11 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 06-SEP-12:09 | 24989.84 | 05-SEP-15:00 | 6.85 | 04-SEP-15:39 | 0.00 | 01-SEP-00:10 |
October | 30748.87 | 27-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 18-OCT-07:10 | 21827.56 | 02-OCT-15:30 | 6.85 | 25-OCT-07:10 | 23241.18 | 25-OCT-06:10 |
November | 32642.50 | 28-NOV-16:30 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 02-NOV-07:10 | 14802.20 | 02-NOV-15:39 | 6.85 | 01-NOV-05:10 | 49842.91 | 24-NOV-07:10 |
December | 32642.50 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 05-DEC-12:09 | 10390.81 | 22-DEC-16:49 | 6.85 | 05-DEC-17:10 | 83966.00 | 06-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26210.40 | 5686.19 | 41699.26 | 1410.29 | 9056.46 | 6.85 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 29826.93 | 6.85 | 87536.85 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 33208.92 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 | 5408.17 | 24-JAN-12:20 | 0.00 |
February | 15190.13 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 | 5405.94 | 01-FEB-12:20 | 0.00 |
March | 34704.85 | 16-MAR-15:39 | 0.00 | 0.00 | 0.00 | 5371.87 | 01-MAR-12:30 | 0.00 |
April | 58675.94 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 4979.60 | 03-APR-11:30 | 0.00 |
May | 63506.18 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 4594.81 | 01-MAY-11:50 | 0.00 |
June | 88020.15 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 4219.75 | 01-JUN-11:39 | 0.00 |
July | 79401.35 | 19-JUL-13:39 | 0.00 | 0.00 | 0.00 | 3876.73 | 03-JUL-11:50 | 0.00 |
August | 82413.59 | 25-AUG-15:20 | 0.00 | 0.00 | 0.00 | 3893.44 | 31-AUG-11:00 | 0.00 |
September | 72964.60 | 08-SEP-15:00 | 0.00 | 0.00 | 0.00 | 4246.12 | 29-SEP-11:20 | 0.00 |
October | 64116.80 | 02-OCT-13:50 | 0.00 | 0.00 | 0.00 | 4792.40 | 31-OCT-11:00 | 0.00 |
November | 38397.33 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 5245.65 | 30-NOV-12:50 | 0.00 |
December | 25221.33 | 22-DEC-15:30 | 0.00 | 0.00 | 0.00 | 5391.09 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 15190.13 | 0.00 | 0.00 | 0.00 | 3876.73 | 0.00 | ||
Maximum of Months | 88020.15 | 0.00 | 0.00 | 0.00 | 5408.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 132810.82 | 02-JAN-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3570.92 | 6.85 | 87536.85 | 0.00 | 0.00 |
February | 102676.11 | 13-FEB-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3426.53 | 6.85 | 57270.25 | 0.00 | 0.00 |
March | 121794.63 | 16-MAR-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14249.71 | 6.85 | 0.00 | 34667.46 | 0.00 |
April | 154246.06 | 14-APR-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 22945.54 | 6.85 | 0.00 | 58675.94 | 0.00 |
May | 159260.00 | 31-MAY-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 23783.58 | 6.85 | 0.00 | 63506.18 | 0.00 |
June | 186009.55 | 28-JUN-14:00 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 26982.45 | 6.85 | 0.00 | 88020.15 | 0.00 |
July | 175285.97 | 31-JUL-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 27298.68 | 6.85 | 0.00 | 76336.49 | 0.00 |
August | 179897.09 | 25-AUG-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 25533.95 | 6.85 | 0.00 | 82413.59 | 0.00 |
September | 168862.03 | 08-SEP-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 23990.35 | 6.85 | 0.00 | 72964.60 | 0.00 |
October | 153894.41 | 02-OCT-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 21475.45 | 6.85 | 0.00 | 60138.47 | 0.00 |
November | 122706.57 | 01-NOV-15:50 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 11857.57 | 6.85 | 0.00 | 37918.43 | 0.00 |
December | 129321.77 | 06-DEC-07:10 | 10880.98 | 22496.85 | 5686.19 | 975.80 | 3659.44 | 6.85 | 83966.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 102676.11 | 10880.98 | 22496.85 | 0.00 | 975.80 | 3426.53 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 186009.55 | 25990.55 | 41670.51 | 5686.19 | 1410.29 | 27298.68 | 6.85 | 87536.85 | 88020.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 26.93 | 0.00 | 26.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.42 | 0.83 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.68 | 5.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.60 | 8.50 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.61 | 4.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.49 | 3.50 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.31 | 0.17 | 19.31 | 37.83 | 27.53 | 23.67 | 27.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.31 | 0.17 | 19.31 | 13.50 | 27.68 | 8.50 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.76 | 7.33 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.83 | 12.17 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.14 | 10.83 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.02 | 14.17 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.11 | 7.83 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.80 | 7.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.56 | 2.83 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.39 | 0.17 | 19.39 | 72.50 | 27.91 | 63.00 | 27.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.17 | 19.39 | 17.17 | 28.14 | 14.17 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.86 | 5.00 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.73 | 5.67 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.53 | 5.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.67 | 5.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.74 | 9.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.88 | 5.17 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.00 | 6.83 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.98 | 7.33 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.70 | 3.50 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.81 | 4.17 | 27.81 |
Annual Sum or Average | 0.00 | 0.00 | 70.50 | 27.79 | 57.83 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.00 | 9.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.81 | 0.17 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.28 | 3.83 | 28.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.52 | 4.83 | 28.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.38 | 5.67 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.33 | 7.50 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.51 | 4.17 | 28.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.14 | 4.33 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.99 | 3.33 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 61.83 | 28.34 | 34.17 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.52 | 7.50 | 28.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.41 | 1.00 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.38 | 2.17 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.38 | 1.67 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.28 | 1.00 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.83 | 27.38 | 5.83 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.41 | 2.17 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.61 | 3.50 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.77 | 5.50 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.82 | 9.83 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.77 | 13.00 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.78 | 8.17 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.62 | 7.50 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.49 | 3.33 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 56.67 | 27.73 | 50.83 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.82 | 13.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 19.65 | 12.83 | 19.65 | 5.83 | 21.16 | 5.83 | 22.19 |
February | 16.83 | 19.16 | 16.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 16.50 | 18.88 | 16.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 1.00 | 20.19 | 1.00 | 20.19 | 17.17 | 24.79 | 17.17 | 25.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 25.22 | 27.00 | 25.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 26.25 | 47.83 | 26.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 26.19 | 44.50 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 26.10 | 55.17 | 26.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | 25.79 | 64.83 | 25.77 |
October | 4.33 | 19.76 | 4.33 | 19.76 | 49.67 | 24.90 | 48.33 | 25.29 |
November | 4.00 | 19.96 | 4.00 | 19.96 | 6.67 | 23.19 | 6.67 | 24.40 |
December | 18.00 | 18.62 | 18.00 | 18.62 | 6.17 | 19.96 | 6.17 | 20.95 |
Annual Sum or Average | 73.50 | 19.14 | 73.50 | 19.14 | 329.83 | 23.88 | 323.50 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | 18.88 |
Maximum of Months | 18.00 | 20.19 | 18.00 | 20.19 | 66.83 | 26.25 | 64.83 | 26.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 2.50 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.10 | 4.00 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.15 | 3.50 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.07 | 5.83 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.99 | 4.50 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.87 | 4.17 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.80 | 3.17 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.43 | 0.17 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 51.17 | 28.02 | 28.00 | 28.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.15 | 5.83 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.50 | 4.00 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.45 | 4.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.49 | 2.17 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.38 | 1.83 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.00 | 27.47 | 12.33 | 27.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.50 | 4.00 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 5.50 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.91 | 8.50 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.02 | 10.67 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.86 | 13.50 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.96 | 8.00 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.70 | 6.67 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.55 | 2.83 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.00 | 27.88 | 55.83 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.02 | 13.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.88 | 6.00 | 27.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.59 | 4.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.39 | 1.67 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.53 | 4.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.53 | 7.67 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.71 | 4.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.58 | 7.67 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.49 | 8.50 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.72 | 4.83 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.86 | 5.17 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 62.67 | 27.62 | 55.67 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.88 | 8.50 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.54 | 0.17 | 27.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.69 | 0.17 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.14 | 4.00 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.39 | 4.50 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.31 | 4.50 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.29 | 5.67 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.35 | 3.83 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.98 | 4.17 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.91 | 2.67 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.57 | 0.17 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 52.83 | 28.23 | 30.00 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.39 | 5.67 | 28.42 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 158.67 | 23.96 | 54.83 | 24.41 | 0.00 | 24.41 |
February | 51.50 | 23.99 | 114.33 | 24.69 | 0.00 | 24.69 |
March | 108.67 | 24.02 | 97.50 | 24.68 | 0.00 | 24.68 |
April | 66.17 | 24.01 | 66.33 | 24.99 | 0.00 | 24.99 |
May | 22.33 | 24.00 | 69.67 | 25.64 | 0.00 | 25.64 |
June | 0.00 | 0.00 | 177.50 | 25.05 | 0.00 | 25.05 |
July | 4.50 | 24.00 | 418.33 | 24.55 | 0.00 | 24.55 |
August | 0.00 | 0.00 | 464.00 | 24.46 | 0.00 | 24.46 |
September | 0.17 | 27.20 | 419.50 | 24.58 | 0.17 | 24.59 |
October | 49.17 | 24.00 | 214.17 | 24.83 | 0.00 | 24.83 |
November | 125.33 | 24.01 | 159.17 | 24.56 | 2.67 | 24.55 |
December | 298.33 | 24.03 | 11.17 | 24.10 | 0.00 | 24.10 |
Annual Sum or Average | 884.83 | 24.01 | 2266.50 | 24.61 | 2.83 | 24.61 |
Minimum of Months | 0.00 | 0.00 | 11.17 | 24.10 | 0.00 | 24.10 |
Maximum of Months | 298.33 | 27.20 | 464.00 | 25.64 | 2.67 | 25.64 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.50 | 23.52 | 4.83 | 23.53 | 0.33 | 23.52 |
February | 359.83 | 23.34 | 4.17 | 23.35 | 0.00 | 23.35 |
March | 297.67 | 23.60 | 19.17 | 23.66 | 0.00 | 23.66 |
April | 169.67 | 23.92 | 22.83 | 24.14 | 0.00 | 24.14 |
May | 102.67 | 24.02 | 33.00 | 24.50 | 0.00 | 24.50 |
June | 5.17 | 24.01 | 123.00 | 24.88 | 0.00 | 24.88 |
July | 11.17 | 24.02 | 400.83 | 24.39 | 0.00 | 24.39 |
August | 5.50 | 24.00 | 450.00 | 24.31 | 1.17 | 24.31 |
September | 0.00 | 0.00 | 395.50 | 24.46 | 0.00 | 24.46 |
October | 176.00 | 23.86 | 130.67 | 24.17 | 0.00 | 24.17 |
November | 291.50 | 23.68 | 93.33 | 23.88 | 11.67 | 23.89 |
December | 485.83 | 23.36 | 0.00 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 2314.50 | 23.57 | 1677.33 | 23.96 | 13.17 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.35 | 0.00 | 23.35 |
Maximum of Months | 485.83 | 24.02 | 450.00 | 24.88 | 11.67 | 24.88 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.00 | 23.00 | 11.33 | 22.92 | 11.33 | 22.85 |
February | 413.83 | 22.71 | 2.83 | 22.69 | 2.83 | 22.68 |
March | 386.33 | 23.18 | 12.00 | 23.17 | 6.33 | 23.14 |
April | 195.17 | 23.77 | 21.33 | 23.90 | 0.00 | 23.90 |
May | 128.50 | 23.98 | 31.33 | 24.32 | 0.00 | 24.32 |
June | 5.00 | 23.99 | 162.17 | 24.75 | 0.00 | 24.75 |
July | 12.67 | 24.01 | 406.50 | 24.42 | 0.33 | 24.42 |
August | 7.50 | 24.00 | 451.83 | 24.32 | 2.00 | 24.32 |
September | 3.17 | 23.76 | 395.17 | 24.43 | 0.00 | 24.43 |
October | 243.17 | 23.54 | 109.50 | 23.81 | 0.00 | 23.81 |
November | 357.83 | 23.08 | 60.50 | 23.23 | 15.83 | 23.24 |
December | 497.00 | 22.48 | 41.83 | 22.34 | 41.83 | 22.22 |
Annual Sum or Average | 2726.17 | 23.06 | 1706.33 | 23.54 | 80.50 | 23.50 |
Minimum of Months | 3.17 | 22.48 | 2.83 | 22.34 | 0.00 | 22.22 |
Maximum of Months | 497.00 | 24.01 | 451.83 | 24.75 | 41.83 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.33 | 22.11 | 88.17 | 21.81 | 88.17 | 21.59 |
February | 446.50 | 21.76 | 49.17 | 21.61 | 49.17 | 21.48 |
March | 426.67 | 22.38 | 50.83 | 22.24 | 41.50 | 22.09 |
April | 210.50 | 23.39 | 62.00 | 23.71 | 2.00 | 23.69 |
May | 109.83 | 23.75 | 100.00 | 24.43 | 0.17 | 24.44 |
June | 21.50 | 26.07 | 328.33 | 24.78 | 14.50 | 24.87 |
July | 35.00 | 26.19 | 450.17 | 24.73 | 30.00 | 24.84 |
August | 24.83 | 25.41 | 470.17 | 24.48 | 17.00 | 24.53 |
September | 52.67 | 25.07 | 412.50 | 24.58 | 31.00 | 24.68 |
October | 289.83 | 22.90 | 128.00 | 23.24 | 17.67 | 23.16 |
November | 429.00 | 22.28 | 109.00 | 22.22 | 86.00 | 22.10 |
December | 497.00 | 21.42 | 213.83 | 21.14 | 213.83 | 20.99 |
Annual Sum or Average | 3044.67 | 22.38 | 2462.17 | 23.01 | 591.00 | 22.86 |
Minimum of Months | 21.50 | 21.42 | 49.17 | 21.14 | 0.17 | 20.99 |
Maximum of Months | 501.33 | 26.19 | 470.17 | 24.78 | 213.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.50 | 22.47 | 62.00 | 22.21 | 59.00 | 21.99 |
February | 392.33 | 22.03 | 47.00 | 21.98 | 32.17 | 21.85 |
March | 334.83 | 22.51 | 73.83 | 22.61 | 25.83 | 22.46 |
April | 107.33 | 23.53 | 193.33 | 24.32 | 9.00 | 24.37 |
May | 63.33 | 24.55 | 253.50 | 24.75 | 16.50 | 24.88 |
June | 40.83 | 26.81 | 412.00 | 24.81 | 37.17 | 24.98 |
July | 55.00 | 26.76 | 468.33 | 24.88 | 52.50 | 25.07 |
August | 40.83 | 26.44 | 487.33 | 24.63 | 37.33 | 24.77 |
September | 59.83 | 25.68 | 436.33 | 24.68 | 43.83 | 24.83 |
October | 209.50 | 23.01 | 191.17 | 23.66 | 19.17 | 23.60 |
November | 367.83 | 22.52 | 93.00 | 22.55 | 56.83 | 22.46 |
December | 497.00 | 21.92 | 134.50 | 21.61 | 134.50 | 21.40 |
Annual Sum or Average | 2608.17 | 22.74 | 2852.33 | 23.48 | 523.83 | 23.44 |
Minimum of Months | 40.83 | 21.92 | 47.00 | 21.61 | 9.00 | 21.40 |
Maximum of Months | 497.00 | 26.81 | 487.33 | 24.88 | 134.50 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.00 | 22.42 | 179.83 | 22.95 | 46.33 | 22.75 |
February | 299.67 | 21.90 | 109.17 | 22.26 | 30.33 | 22.11 |
March | 301.33 | 22.46 | 104.67 | 22.70 | 30.00 | 22.53 |
April | 162.17 | 23.37 | 157.67 | 24.03 | 5.67 | 24.05 |
May | 121.67 | 23.66 | 146.17 | 24.34 | 1.83 | 24.36 |
June | 35.33 | 25.31 | 305.67 | 24.74 | 16.17 | 24.84 |
July | 44.67 | 25.89 | 441.17 | 24.73 | 33.17 | 24.85 |
August | 33.00 | 25.85 | 472.83 | 24.54 | 25.00 | 24.63 |
September | 62.50 | 25.61 | 429.83 | 24.71 | 43.33 | 24.86 |
October | 189.00 | 23.43 | 238.83 | 24.06 | 31.33 | 24.14 |
November | 257.33 | 22.66 | 187.33 | 23.16 | 56.33 | 23.06 |
December | 329.17 | 22.14 | 167.17 | 22.23 | 104.33 | 21.97 |
Annual Sum or Average | 2095.83 | 22.85 | 2940.33 | 23.68 | 423.83 | 23.62 |
Minimum of Months | 33.00 | 21.90 | 104.67 | 22.23 | 1.83 | 21.97 |
Maximum of Months | 329.17 | 25.89 | 472.83 | 24.74 | 104.33 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 402.17 | 21.82 | 103.00 | 21.69 | 81.50 | 21.48 |
February | 400.67 | 21.56 | 63.50 | 21.53 | 45.50 | 21.41 |
March | 381.33 | 22.12 | 93.67 | 22.21 | 43.17 | 22.06 |
April | 191.17 | 23.28 | 161.33 | 23.91 | 16.67 | 24.01 |
May | 139.00 | 23.88 | 199.83 | 24.41 | 19.00 | 24.56 |
June | 47.67 | 25.29 | 340.33 | 24.73 | 22.50 | 24.86 |
July | 51.83 | 25.94 | 446.33 | 24.73 | 40.67 | 24.87 |
August | 38.67 | 25.34 | 460.83 | 24.51 | 24.83 | 24.60 |
September | 66.00 | 24.84 | 416.00 | 24.56 | 37.50 | 24.68 |
October | 262.83 | 22.76 | 183.17 | 23.35 | 27.83 | 23.34 |
November | 367.33 | 22.09 | 134.00 | 22.22 | 79.17 | 22.10 |
December | 455.83 | 21.46 | 193.17 | 21.21 | 187.17 | 21.05 |
Annual Sum or Average | 2804.50 | 22.35 | 2795.17 | 23.13 | 625.50 | 23.04 |
Minimum of Months | 38.67 | 21.46 | 63.50 | 21.21 | 16.67 | 21.05 |
Maximum of Months | 455.83 | 25.94 | 460.83 | 24.73 | 187.17 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.53 | 27.67 | 22.41 | 27.67 | 22.31 |
February | 454.00 | 22.07 | 7.00 | 22.04 | 7.00 | 22.02 |
March | 482.17 | 22.58 | 17.50 | 22.51 | 17.50 | 22.44 |
April | 268.50 | 23.68 | 12.00 | 23.73 | 0.00 | 23.73 |
May | 151.17 | 23.92 | 19.67 | 24.12 | 0.00 | 24.12 |
June | 2.00 | 25.45 | 241.50 | 24.81 | 0.83 | 24.82 |
July | 7.50 | 25.72 | 451.33 | 24.61 | 6.50 | 24.63 |
August | 3.33 | 25.87 | 472.33 | 24.46 | 3.00 | 24.47 |
September | 12.83 | 26.31 | 440.00 | 24.58 | 12.83 | 24.63 |
October | 227.33 | 23.59 | 130.17 | 23.94 | 0.00 | 23.94 |
November | 379.33 | 23.12 | 68.83 | 23.29 | 25.33 | 23.33 |
December | 497.00 | 22.24 | 54.83 | 22.10 | 54.83 | 21.98 |
Annual Sum or Average | 2987.17 | 22.78 | 1942.83 | 23.40 | 155.50 | 23.36 |
Minimum of Months | 2.00 | 22.07 | 7.00 | 22.04 | 0.00 | 21.98 |
Maximum of Months | 502.00 | 26.31 | 472.33 | 24.81 | 54.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.00 | 23.03 | 15.50 | 23.03 | 6.50 | 22.98 |
February | 389.00 | 22.48 | 16.83 | 22.56 | 1.33 | 22.56 |
March | 359.00 | 22.89 | 39.67 | 23.01 | 7.50 | 22.97 |
April | 87.67 | 23.70 | 153.83 | 24.47 | 0.83 | 24.48 |
May | 40.33 | 24.17 | 182.83 | 24.85 | 3.17 | 24.89 |
June | 24.33 | 27.11 | 398.33 | 24.77 | 24.17 | 24.90 |
July | 38.67 | 26.90 | 471.83 | 24.85 | 38.67 | 25.00 |
August | 31.17 | 26.92 | 496.50 | 24.68 | 31.17 | 24.80 |
September | 35.83 | 26.71 | 461.83 | 24.74 | 35.83 | 24.87 |
October | 119.67 | 23.65 | 211.17 | 24.35 | 2.17 | 24.37 |
November | 286.33 | 23.40 | 96.00 | 23.66 | 24.67 | 23.69 |
December | 467.67 | 22.81 | 21.67 | 22.72 | 20.83 | 22.64 |
Annual Sum or Average | 2295.67 | 23.21 | 2566.00 | 23.95 | 196.83 | 24.01 |
Minimum of Months | 24.33 | 22.48 | 15.50 | 22.56 | 0.83 | 22.56 |
Maximum of Months | 467.67 | 27.11 | 496.50 | 24.85 | 38.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 215.33 | 23.04 | 148.00 | 23.75 | 9.67 | 23.73 |
February | 331.33 | 22.13 | 51.33 | 22.36 | 9.83 | 22.27 |
March | 350.83 | 22.52 | 65.17 | 22.62 | 21.00 | 22.46 |
April | 155.17 | 23.29 | 97.00 | 24.00 | 1.00 | 23.98 |
May | 148.33 | 23.62 | 64.83 | 24.24 | 0.00 | 24.24 |
June | 19.67 | 24.52 | 243.33 | 25.13 | 3.83 | 25.16 |
July | 45.83 | 25.29 | 449.83 | 24.84 | 41.83 | 24.88 |
August | 45.67 | 25.74 | 485.83 | 24.81 | 44.00 | 24.89 |
September | 63.33 | 26.10 | 461.33 | 24.99 | 60.67 | 25.12 |
October | 121.33 | 23.92 | 280.17 | 24.69 | 32.67 | 24.81 |
November | 169.17 | 23.23 | 218.17 | 24.03 | 27.83 | 24.04 |
December | 293.67 | 22.62 | 102.50 | 23.03 | 27.00 | 22.89 |
Annual Sum or Average | 1959.67 | 23.09 | 2667.50 | 24.07 | 279.33 | 24.09 |
Minimum of Months | 19.67 | 22.13 | 51.33 | 22.36 | 0.00 | 22.27 |
Maximum of Months | 350.83 | 26.10 | 485.83 | 25.13 | 60.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 405.17 | 22.70 | 26.17 | 22.72 | 12.00 | 22.65 |
February | 414.17 | 22.13 | 8.17 | 22.17 | 1.33 | 22.16 |
March | 405.83 | 22.60 | 41.50 | 22.69 | 12.00 | 22.64 |
April | 147.00 | 23.64 | 131.17 | 24.19 | 2.67 | 24.22 |
May | 97.67 | 24.07 | 160.33 | 24.59 | 6.83 | 24.67 |
June | 14.83 | 26.67 | 330.50 | 24.78 | 12.67 | 24.86 |
July | 28.17 | 26.67 | 463.83 | 24.75 | 26.50 | 24.86 |
August | 20.67 | 26.76 | 489.33 | 24.59 | 20.67 | 24.67 |
September | 29.17 | 26.67 | 456.50 | 24.69 | 29.17 | 24.80 |
October | 153.83 | 23.64 | 196.17 | 24.20 | 6.67 | 24.26 |
November | 286.00 | 23.22 | 115.50 | 23.58 | 21.17 | 23.63 |
December | 448.50 | 22.43 | 42.33 | 22.36 | 35.67 | 22.25 |
Annual Sum or Average | 2451.00 | 22.92 | 2461.50 | 23.73 | 187.33 | 23.76 |
Minimum of Months | 14.83 | 22.13 | 8.17 | 22.17 | 1.33 | 22.16 |
Maximum of Months | 448.50 | 26.76 | 489.33 | 24.78 | 35.67 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 22.65 | 25.83 | 22.53 | 25.83 | 22.42 |
February | 439.17 | 22.31 | 7.17 | 22.28 | 7.17 | 22.25 |
March | 403.00 | 22.82 | 25.83 | 22.79 | 14.17 | 22.72 |
April | 191.00 | 23.71 | 38.83 | 23.96 | 0.00 | 23.96 |
May | 92.33 | 23.97 | 72.33 | 24.64 | 0.00 | 24.64 |
June | 7.83 | 27.02 | 294.00 | 24.85 | 7.83 | 24.90 |
July | 15.00 | 26.27 | 452.50 | 24.67 | 14.67 | 24.72 |
August | 13.00 | 25.24 | 471.17 | 24.47 | 9.17 | 24.49 |
September | 25.17 | 25.78 | 418.67 | 24.61 | 20.83 | 24.68 |
October | 263.67 | 23.37 | 116.83 | 23.71 | 0.33 | 23.72 |
November | 402.50 | 22.82 | 65.33 | 22.96 | 34.50 | 22.98 |
December | 497.00 | 22.01 | 91.67 | 21.80 | 91.67 | 21.65 |
Annual Sum or Average | 2848.67 | 22.79 | 2080.17 | 23.43 | 226.17 | 23.39 |
Minimum of Months | 7.83 | 22.01 | 7.17 | 21.80 | 0.00 | 21.65 |
Maximum of Months | 499.00 | 27.02 | 471.17 | 24.85 | 91.67 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 356.17 | 22.67 | 24.83 | 22.68 | 11.50 | 22.61 |
February | 321.00 | 22.27 | 28.33 | 22.37 | 8.50 | 22.32 |
March | 279.83 | 22.72 | 59.17 | 22.99 | 10.00 | 22.92 |
April | 96.33 | 23.82 | 135.67 | 24.57 | 7.17 | 24.65 |
May | 50.50 | 24.74 | 177.67 | 25.06 | 13.67 | 25.18 |
June | 30.33 | 27.12 | 321.50 | 24.99 | 29.83 | 25.16 |
July | 43.00 | 26.84 | 394.33 | 24.99 | 42.83 | 25.15 |
August | 32.00 | 26.58 | 410.50 | 24.72 | 30.17 | 24.85 |
September | 43.50 | 26.10 | 365.00 | 24.81 | 36.33 | 24.96 |
October | 173.50 | 23.26 | 151.83 | 24.00 | 3.17 | 24.03 |
November | 300.67 | 22.85 | 69.00 | 23.03 | 30.50 | 23.03 |
December | 410.50 | 22.24 | 61.67 | 22.03 | 61.00 | 21.87 |
Annual Sum or Average | 2137.33 | 22.98 | 2199.50 | 23.79 | 284.67 | 23.83 |
Minimum of Months | 30.33 | 22.24 | 24.83 | 22.03 | 3.17 | 21.87 |
Maximum of Months | 410.50 | 27.12 | 410.50 | 25.06 | 61.00 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 239.83 | 23.07 | 163.17 | 23.68 | 16.33 | 23.70 |
February | 277.50 | 22.46 | 91.67 | 22.94 | 2.83 | 22.92 |
March | 266.67 | 22.91 | 94.67 | 23.25 | 10.17 | 23.18 |
April | 134.83 | 23.68 | 138.83 | 24.26 | 1.17 | 24.27 |
May | 96.50 | 23.88 | 107.33 | 24.59 | 0.00 | 24.59 |
June | 16.00 | 25.67 | 273.83 | 24.81 | 8.67 | 24.87 |
July | 31.33 | 26.08 | 445.00 | 24.72 | 26.50 | 24.81 |
August | 25.17 | 26.00 | 479.33 | 24.55 | 20.67 | 24.62 |
September | 45.33 | 26.45 | 439.83 | 24.76 | 42.00 | 24.92 |
October | 154.33 | 23.90 | 245.33 | 24.41 | 21.50 | 24.55 |
November | 217.33 | 23.24 | 189.67 | 23.85 | 29.00 | 23.88 |
December | 303.17 | 22.71 | 114.33 | 23.04 | 40.00 | 22.93 |
Annual Sum or Average | 1808.00 | 23.27 | 2783.00 | 24.07 | 218.83 | 24.11 |
Minimum of Months | 16.00 | 22.46 | 91.67 | 22.94 | 0.00 | 22.92 |
Maximum of Months | 303.17 | 26.45 | 479.33 | 24.81 | 42.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.67 | 22.36 | 43.67 | 22.41 | 18.00 | 22.32 |
February | 388.50 | 22.04 | 27.17 | 22.11 | 9.00 | 22.07 |
March | 358.67 | 22.57 | 67.00 | 22.74 | 15.33 | 22.67 |
April | 159.33 | 23.59 | 148.00 | 24.16 | 9.33 | 24.25 |
May | 109.33 | 24.15 | 185.33 | 24.60 | 15.00 | 24.73 |
June | 27.50 | 26.12 | 330.17 | 24.79 | 19.17 | 24.91 |
July | 36.17 | 26.25 | 451.00 | 24.72 | 31.17 | 24.83 |
August | 26.67 | 26.00 | 477.50 | 24.52 | 21.67 | 24.61 |
September | 48.17 | 25.47 | 424.33 | 24.63 | 33.67 | 24.75 |
October | 229.50 | 23.20 | 174.00 | 23.79 | 9.00 | 23.86 |
November | 341.17 | 22.63 | 104.50 | 22.95 | 33.00 | 22.95 |
December | 447.83 | 21.95 | 96.17 | 21.79 | 88.50 | 21.64 |
Annual Sum or Average | 2564.50 | 22.73 | 2528.83 | 23.54 | 302.83 | 23.55 |
Minimum of Months | 26.67 | 21.95 | 27.17 | 21.79 | 9.00 | 21.64 |
Maximum of Months | 447.83 | 26.25 | 477.50 | 24.79 | 88.50 | 24.91 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32331 | 20.82250 | 0.29960 | 7.20878 |
February | 454.00000 | 24.32614 | 33.24469 | 0.36886 | 8.07660 |
March | 514.00000 | 24.36952 | 25.99877 | 0.34897 | 7.86024 |
April | 485.00000 | 24.41261 | 18.65282 | 0.34741 | 7.77973 |
May | 508.00000 | 24.43508 | 18.12515 | -0.4825 | 10.36934 |
June | 496.00000 | 24.40268 | 25.67483 | -0.4172 | 9.14015 |
July | 497.00000 | 24.49491 | 41.71239 | -0.2834 | 7.32561 |
August | 514.00000 | 24.42515 | 44.30741 | -0.2829 | 7.23971 |
September | 485.00000 | 24.50591 | 43.50670 | -0.2672 | 7.28512 |
October | 502.00000 | 24.50937 | 26.07867 | 0.42102 | 9.26384 |
November | 489.00000 | 24.46138 | 25.93564 | 0.38556 | 8.76660 |
December | 497.00000 | 24.31176 | 15.38107 | 0.24609 | 6.44851 |
Annual Sum or Average | 5943.00000 | 24.41516 | 28.25551 | 0.05385 | 8.06623 |
Minimum of Months | 454.00000 | 24.31176 | 15.38107 | -0.4825 | 6.44851 |
Maximum of Months | 514.00000 | 24.50937 | 44.30741 | 0.42102 | 10.36934 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67285 | 22.76575 | 0.13472 | 5.95844 |
February | 454.00000 | 23.49500 | 35.78144 | 0.16555 | 5.93498 |
March | 514.00000 | 23.85855 | 27.58212 | 0.21545 | 6.35388 |
April | 485.00000 | 24.18265 | 19.55416 | 0.28042 | 6.86977 |
May | 508.00000 | 24.26933 | 18.99362 | -0.5569 | 11.79557 |
June | 496.00000 | 24.29378 | 26.54567 | -0.4686 | 9.94163 |
July | 497.00000 | 24.35099 | 43.48924 | -0.3398 | 7.87698 |
August | 514.00000 | 24.29602 | 46.21224 | -0.3393 | 7.77672 |
September | 485.00000 | 24.37724 | 45.07375 | -0.3294 | 7.85109 |
October | 502.00000 | 24.18933 | 27.24844 | 0.32644 | 7.71339 |
November | 489.00000 | 23.92795 | 27.57318 | 0.23904 | 6.91543 |
December | 497.00000 | 23.37980 | 17.32265 | 0.01536 | 5.54523 |
Annual Sum or Average | 5943.00000 | 24.02794 | 29.80800 | -0.0573 | 7.56119 |
Minimum of Months | 454.00000 | 23.37980 | 17.32265 | -0.5569 | 5.54523 |
Maximum of Months | 514.00000 | 24.37724 | 46.21224 | 0.32644 | 11.79557 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05697 | 24.35935 | -0.0140 | 6.07388 |
February | 454.00000 | 22.81684 | 37.21030 | 0.00122 | 5.89654 |
March | 514.00000 | 23.41883 | 28.01836 | 0.10621 | 6.14039 |
April | 485.00000 | 24.07163 | 19.73205 | 0.25775 | 6.73575 |
May | 508.00000 | 24.23239 | 19.16088 | -0.5588 | 11.89755 |
June | 496.00000 | 24.31110 | 26.50163 | -0.4418 | 9.52008 |
July | 497.00000 | 24.38393 | 43.08620 | -0.3132 | 7.60622 |
August | 514.00000 | 24.29812 | 45.83258 | -0.3269 | 7.63798 |
September | 485.00000 | 24.35832 | 44.91204 | -0.3300 | 7.86229 |
October | 502.00000 | 23.91744 | 27.49939 | 0.25531 | 7.23316 |
November | 489.00000 | 23.35877 | 28.34946 | 0.09604 | 6.56684 |
December | 497.00000 | 22.47868 | 18.03091 | -0.2047 | 7.14329 |
Annual Sum or Average | 5943.00000 | 23.73154 | 30.17920 | -0.1246 | 7.54281 |
Minimum of Months | 454.00000 | 22.47868 | 18.03091 | -0.5588 | 5.89654 |
Maximum of Months | 514.00000 | 24.38393 | 45.83258 | 0.25775 | 11.89755 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10786 | 25.69166 | -0.2487 | 8.51887 |
February | 454.00000 | 21.79882 | 40.48632 | -0.2436 | 7.70319 |
March | 514.00000 | 22.67542 | 29.98478 | -0.0712 | 7.33833 |
April | 485.00000 | 23.92289 | 20.18164 | 0.23135 | 7.17083 |
May | 508.00000 | 24.26477 | 19.04604 | -0.5139 | 11.62211 |
June | 496.00000 | 24.48716 | 25.94642 | -0.3038 | 8.09676 |
July | 497.00000 | 24.57816 | 42.93554 | -0.1809 | 6.97791 |
August | 514.00000 | 24.39823 | 45.80433 | -0.2410 | 7.16118 |
September | 485.00000 | 24.41433 | 45.41371 | -0.2718 | 7.82720 |
October | 502.00000 | 23.48091 | 28.74668 | 0.15427 | 7.81503 |
November | 489.00000 | 22.50092 | 30.78971 | -0.1111 | 7.92634 |
December | 497.00000 | 21.41703 | 19.72882 | -0.4737 | 11.62610 |
Annual Sum or Average | 5943.00000 | 23.34786 | 31.16664 | -0.1901 | 8.32338 |
Minimum of Months | 454.00000 | 21.41703 | 19.04604 | -0.5139 | 6.97791 |
Maximum of Months | 514.00000 | 24.57816 | 45.80433 | 0.23135 | 11.62610 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.67496 | 24.39598 | -0.0867 | 7.54653 |
February | 454.00000 | 22.31403 | 39.04030 | -0.0978 | 7.36814 |
March | 514.00000 | 23.10657 | 28.69076 | 0.06505 | 7.38691 |
April | 485.00000 | 24.21437 | 19.36584 | 0.37401 | 9.30695 |
May | 508.00000 | 24.42328 | 18.64141 | -0.3539 | 9.50890 |
June | 496.00000 | 24.52318 | 25.76088 | -0.1844 | 7.42511 |
July | 497.00000 | 24.63011 | 42.66669 | -0.0687 | 6.84128 |
August | 514.00000 | 24.45482 | 45.42393 | -0.1244 | 6.85088 |
September | 485.00000 | 24.45654 | 45.04211 | -0.1788 | 7.39738 |
October | 502.00000 | 23.79960 | 27.67288 | 0.27959 | 9.14819 |
November | 489.00000 | 22.90501 | 29.75195 | 0.01531 | 7.40035 |
December | 497.00000 | 21.91772 | 18.85556 | -0.3295 | 9.61438 |
Annual Sum or Average | 5943.00000 | 23.62748 | 30.38333 | -0.0581 | 7.98525 |
Minimum of Months | 454.00000 | 21.91772 | 18.64141 | -0.3539 | 6.84128 |
Maximum of Months | 514.00000 | 24.63011 | 45.42393 | 0.37401 | 9.61438 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.37734 | 22.23846 | 0.13895 | 9.25469 |
February | 454.00000 | 22.69525 | 37.30568 | 0.01268 | 8.07436 |
March | 514.00000 | 23.20149 | 28.21075 | 0.09191 | 7.92594 |
April | 485.00000 | 24.05761 | 19.60081 | 0.30885 | 8.57621 |
May | 508.00000 | 24.24131 | 18.98828 | -0.5024 | 11.93760 |
June | 496.00000 | 24.43370 | 26.04859 | -0.3295 | 8.52909 |
July | 497.00000 | 24.55588 | 42.93330 | -0.1819 | 7.22738 |
August | 514.00000 | 24.41483 | 45.59278 | -0.1982 | 7.11500 |
September | 485.00000 | 24.48064 | 44.88846 | -0.1764 | 7.53431 |
October | 502.00000 | 23.98111 | 26.96753 | 0.35279 | 10.48514 |
November | 489.00000 | 23.45705 | 27.91815 | 0.19200 | 8.96949 |
December | 497.00000 | 22.92674 | 16.86648 | -0.0468 | 9.90692 |
Annual Sum or Average | 5943.00000 | 23.82576 | 29.74745 | -0.0296 | 8.80302 |
Minimum of Months | 454.00000 | 22.69525 | 16.86648 | -0.5024 | 7.11500 |
Maximum of Months | 514.00000 | 24.55588 | 45.59278 | 0.35279 | 11.93760 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30259 | 24.52573 | -0.1611 | 8.80128 |
February | 454.00000 | 21.86392 | 39.70391 | -0.1983 | 7.96939 |
March | 514.00000 | 22.66841 | 29.32489 | -0.0329 | 7.91794 |
April | 485.00000 | 23.90758 | 19.93453 | 0.29850 | 9.00057 |
May | 508.00000 | 24.20506 | 19.06051 | -0.4427 | 11.94185 |
June | 496.00000 | 24.44243 | 26.01639 | -0.2346 | 8.20142 |
July | 497.00000 | 24.53315 | 42.94160 | -0.1418 | 7.44540 |
August | 514.00000 | 24.36438 | 45.75113 | -0.1867 | 7.52189 |
September | 485.00000 | 24.37173 | 45.37684 | -0.2240 | 8.00601 |
October | 502.00000 | 23.48089 | 28.19853 | 0.20361 | 8.96724 |
November | 489.00000 | 22.62081 | 29.79979 | -0.0406 | 8.37801 |
December | 497.00000 | 21.68815 | 18.64932 | -0.3825 | 11.21108 |
Annual Sum or Average | 5943.00000 | 23.38096 | 30.71309 | -0.1291 | 8.78776 |
Minimum of Months | 454.00000 | 21.68815 | 18.64932 | -0.4427 | 7.44540 |
Maximum of Months | 514.00000 | 24.53315 | 45.75113 | 0.29850 | 11.94185 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53192 | 25.36171 | -0.1440 | 6.54065 |
February | 454.00000 | 22.06526 | 40.28780 | -0.1749 | 6.32374 |
March | 514.00000 | 22.67533 | 30.78681 | -0.0771 | 6.41612 |
April | 485.00000 | 23.92595 | 20.24504 | 0.20735 | 6.40193 |
May | 508.00000 | 24.20270 | 18.95423 | -0.5797 | 12.45092 |
June | 496.00000 | 24.42494 | 25.72850 | -0.3717 | 8.58764 |
July | 497.00000 | 24.55909 | 41.96794 | -0.2134 | 6.80943 |
August | 514.00000 | 24.42239 | 44.67626 | -0.2474 | 6.90508 |
September | 485.00000 | 24.48364 | 44.09501 | -0.2439 | 7.08775 |
October | 502.00000 | 24.00428 | 27.96175 | 0.28648 | 7.72844 |
November | 489.00000 | 23.34872 | 29.49094 | 0.09962 | 6.56314 |
December | 497.00000 | 22.24327 | 19.15167 | -0.2528 | 7.36479 |
Annual Sum or Average | 5943.00000 | 23.58299 | 30.66458 | -0.1437 | 7.44778 |
Minimum of Months | 454.00000 | 22.06526 | 18.95423 | -0.5797 | 6.32374 |
Maximum of Months | 514.00000 | 24.55909 | 44.67626 | 0.28648 | 12.45092 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23653 | 23.80594 | 0.04987 | 6.23431 |
February | 454.00000 | 22.72462 | 38.70257 | 0.00282 | 6.25826 |
March | 514.00000 | 23.30573 | 29.18675 | 0.10257 | 6.57445 |
April | 485.00000 | 24.30069 | 19.09181 | 0.37097 | 8.60191 |
May | 508.00000 | 24.43565 | 18.27953 | -0.3920 | 9.39223 |
June | 496.00000 | 24.52694 | 25.35793 | -0.2282 | 7.34949 |
July | 497.00000 | 24.65824 | 41.54171 | -0.0841 | 6.43468 |
August | 514.00000 | 24.52075 | 44.15146 | -0.1133 | 6.38038 |
September | 485.00000 | 24.55566 | 43.66540 | -0.1384 | 6.61571 |
October | 502.00000 | 24.26437 | 26.88716 | 0.40439 | 9.63114 |
November | 489.00000 | 23.73650 | 28.29166 | 0.22553 | 7.13646 |
December | 497.00000 | 22.89846 | 18.12099 | -0.0763 | 6.47099 |
Annual Sum or Average | 5943.00000 | 23.93775 | 29.69923 | 0.00924 | 7.26325 |
Minimum of Months | 454.00000 | 22.72462 | 18.12099 | -0.3920 | 6.23431 |
Maximum of Months | 514.00000 | 24.65824 | 44.15146 | 0.40439 | 9.63114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.85515 | 21.21364 | 0.27479 | 8.59841 |
February | 454.00000 | 22.72145 | 36.99859 | 0.04721 | 6.96814 |
March | 514.00000 | 23.09599 | 28.17650 | 0.07307 | 7.21452 |
April | 485.00000 | 24.10447 | 18.47664 | 0.29210 | 7.84774 |
May | 508.00000 | 24.23969 | 17.46888 | -0.5595 | 12.66161 |
June | 496.00000 | 24.60808 | 24.38155 | -0.3465 | 8.74696 |
July | 497.00000 | 24.73486 | 41.65090 | -0.1616 | 6.78970 |
August | 514.00000 | 24.68538 | 43.99987 | -0.1347 | 6.61774 |
September | 485.00000 | 24.78189 | 43.06251 | -0.0793 | 6.81697 |
October | 502.00000 | 24.43387 | 25.67821 | 0.47871 | 11.87377 |
November | 489.00000 | 24.02156 | 26.75232 | 0.36196 | 9.35257 |
December | 497.00000 | 23.42749 | 15.80258 | 0.12440 | 8.43696 |
Annual Sum or Average | 5943.00000 | 24.06676 | 28.58589 | 0.02922 | 8.50991 |
Minimum of Months | 454.00000 | 22.72145 | 15.80258 | -0.5595 | 6.61774 |
Maximum of Months | 514.00000 | 24.78189 | 43.99987 | 0.47871 | 12.66161 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00440 | 23.90352 | 0.00367 | 6.45314 |
February | 454.00000 | 22.30640 | 39.42897 | -0.0925 | 6.28441 |
March | 514.00000 | 22.95233 | 29.76918 | 0.02027 | 6.57776 |
April | 485.00000 | 24.16147 | 19.51339 | 0.32981 | 8.22182 |
May | 508.00000 | 24.33222 | 18.59454 | -0.4469 | 10.53514 |
June | 496.00000 | 24.48387 | 25.56650 | -0.2646 | 7.72962 |
July | 497.00000 | 24.60584 | 41.81318 | -0.1433 | 6.75441 |
August | 514.00000 | 24.47789 | 44.44607 | -0.1620 | 6.64692 |
September | 485.00000 | 24.53462 | 43.87803 | -0.1656 | 6.75663 |
October | 502.00000 | 24.16285 | 27.27693 | 0.37055 | 9.13517 |
November | 489.00000 | 23.64535 | 28.36463 | 0.20958 | 7.38222 |
December | 497.00000 | 22.61838 | 18.06797 | -0.1377 | 7.04449 |
Annual Sum or Average | 5943.00000 | 23.78253 | 29.99210 | -0.0409 | 7.47000 |
Minimum of Months | 454.00000 | 22.30640 | 18.06797 | -0.4469 | 6.28441 |
Maximum of Months | 514.00000 | 24.60584 | 44.44607 | 0.37055 | 10.53514 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66469 | 25.35278 | -0.1069 | 6.64354 |
February | 454.00000 | 22.36802 | 39.50442 | -0.0996 | 6.18672 |
March | 514.00000 | 23.10003 | 29.73709 | 0.03503 | 6.45127 |
April | 485.00000 | 24.07614 | 19.94810 | 0.26140 | 6.94194 |
May | 508.00000 | 24.32390 | 18.82318 | -0.5072 | 10.99151 |
June | 496.00000 | 24.49451 | 25.87091 | -0.3251 | 8.19237 |
July | 497.00000 | 24.58167 | 43.18098 | -0.1991 | 6.86965 |
August | 514.00000 | 24.41577 | 46.04787 | -0.2494 | 7.03989 |
September | 485.00000 | 24.45877 | 45.37025 | -0.2668 | 7.50843 |
October | 502.00000 | 23.80606 | 28.51563 | 0.23377 | 7.50720 |
November | 489.00000 | 23.04935 | 30.19466 | 0.02706 | 6.79729 |
December | 497.00000 | 22.01041 | 19.51179 | -0.3117 | 8.40223 |
Annual Sum or Average | 5943.00000 | 23.62093 | 30.94859 | -0.1269 | 7.47374 |
Minimum of Months | 454.00000 | 22.01041 | 18.82318 | -0.5072 | 6.18672 |
Maximum of Months | 514.00000 | 24.58167 | 46.04787 | 0.26140 | 10.99151 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.94074 | 23.92248 | -0.0167 | 6.69158 |
February | 385.00000 | 22.60651 | 38.24901 | -0.0197 | 6.67167 |
March | 433.00000 | 23.30726 | 28.29307 | 0.11096 | 7.05826 |
April | 410.00000 | 24.34110 | 18.82182 | 0.37705 | 9.10569 |
May | 430.00000 | 24.53269 | 17.99996 | -0.3610 | 9.50761 |
June | 418.00000 | 24.62604 | 25.18377 | -0.2067 | 7.71798 |
July | 422.00000 | 24.74265 | 42.13687 | -0.0852 | 6.88077 |
August | 433.00000 | 24.55368 | 44.80649 | -0.1429 | 6.94856 |
September | 410.00000 | 24.57435 | 44.45596 | -0.1815 | 7.37367 |
October | 427.00000 | 23.99940 | 27.10122 | 0.31495 | 9.02669 |
November | 417.00000 | 23.23211 | 29.12241 | 0.09659 | 6.94901 |
December | 422.00000 | 22.30397 | 18.01081 | -0.2244 | 7.88834 |
Annual Sum or Average | 5034.00000 | 23.82008 | 29.77794 | -0.0290 | 7.65722 |
Minimum of Months | 385.00000 | 22.30397 | 17.99996 | -0.3610 | 6.67167 |
Maximum of Months | 433.00000 | 24.74265 | 44.80649 | 0.37705 | 9.50761 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76309 | 21.87605 | 0.24255 | 8.74655 |
February | 454.00000 | 23.17067 | 36.24082 | 0.13454 | 7.43591 |
March | 514.00000 | 23.55848 | 27.90346 | 0.18266 | 7.43455 |
April | 485.00000 | 24.22115 | 19.34042 | 0.33878 | 8.32861 |
May | 508.00000 | 24.33050 | 18.73016 | -0.4886 | 10.98296 |
June | 496.00000 | 24.45314 | 25.95988 | -0.3473 | 8.53248 |
July | 497.00000 | 24.57295 | 43.15659 | -0.1967 | 7.03560 |
August | 514.00000 | 24.44385 | 45.80544 | -0.2048 | 6.89130 |
September | 485.00000 | 24.53235 | 44.79332 | -0.1719 | 7.13875 |
October | 502.00000 | 24.22657 | 26.73598 | 0.41366 | 10.48716 |
November | 489.00000 | 23.85606 | 27.36678 | 0.29698 | 8.89260 |
December | 497.00000 | 23.39260 | 16.46959 | 0.08456 | 8.55643 |
Annual Sum or Average | 5943.00000 | 24.04881 | 29.48938 | 0.02171 | 8.38054 |
Minimum of Months | 454.00000 | 23.17067 | 16.46959 | -0.4886 | 6.89130 |
Maximum of Months | 514.00000 | 24.57295 | 45.80544 | 0.41366 | 10.98296 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.78338 | 24.17695 | -0.0361 | 7.19523 |
February | 454.00000 | 22.34632 | 38.78144 | -0.0722 | 6.60644 |
March | 514.00000 | 23.07416 | 29.08223 | 0.06842 | 7.06181 |
April | 485.00000 | 24.10446 | 19.67750 | 0.33543 | 8.70083 |
May | 508.00000 | 24.31300 | 18.79150 | -0.4243 | 10.69215 |
June | 496.00000 | 24.47036 | 25.90497 | -0.2507 | 7.95288 |
July | 497.00000 | 24.55496 | 43.15911 | -0.1553 | 7.11214 |
August | 514.00000 | 24.40784 | 45.94934 | -0.1893 | 7.12786 |
September | 485.00000 | 24.44278 | 45.27618 | -0.2132 | 7.43566 |
October | 502.00000 | 23.80233 | 27.96890 | 0.28087 | 8.65346 |
November | 489.00000 | 23.11461 | 29.24649 | 0.08528 | 7.49504 |
December | 497.00000 | 22.18292 | 18.37183 | -0.2416 | 8.50762 |
Annual Sum or Average | 5943.00000 | 23.64168 | 30.47789 | -0.0687 | 7.88817 |
Minimum of Months | 454.00000 | 22.18292 | 18.37183 | -0.4243 | 6.60644 |
Maximum of Months | 514.00000 | 24.55496 | 45.94934 | 0.33543 | 10.69215 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.181073E+11 | 0.418645E+10 | 278.44 | 0.179949E+11 | 0.112467E+09 | 0.00 | 1.00 | 05-JAN-16:10 | 0.00 | 01-JAN-00:10 | 50264.78 | 31-JAN-16:50 | 50264.78 | 31-JAN-16:50 | 5718.11 | 08-JAN-15:43 | 12042.27 | 31-JAN-16:50 | 0.00 |
February | 0.397784E+10 | 0.998090E+09 | 150.50 | 0.351335E+10 | 0.464497E+09 | 0.00 | 0.68 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 23249.72 | 22-FEB-16:00 | 23249.72 | 22-FEB-16:00 | 4222.54 | 17-FEB-12:00 | 5352.20 | 22-FEB-16:00 | 0.00 |
March | 0.172502E+11 | 0.407378E+10 | 293.86 | 0.169034E+11 | 0.346839E+09 | 0.00 | 1.00 | 10-MAR-15:20 | 0.00 | 01-MAR-00:10 | 50195.89 | 20-MAR-14:30 | 50195.89 | 20-MAR-14:30 | 2700.70 | 06-MAR-16:00 | 11609.23 | 20-MAR-14:30 | 0.00 |
April | 0.485139E+11 | 0.119565E+11 | 409.26 | 0.484462E+11 | 67724254.43 | 0.00 | 1.00 | 03-APR-09:20 | 0.00 | 01-APR-00:10 | 68122.06 | 14-APR-16:00 | 68122.06 | 14-APR-16:00 | 2457.70 | 16-APR-09:55 | 19445.77 | 14-APR-16:00 | 0.00 |
May | 0.642238E+11 | 0.165448E+11 | 456.43 | 0.642003E+11 | 23489639.15 | 0.00 | 1.00 | 01-MAY-09:40 | 0.00 | 01-MAY-00:10 | 71966.95 | 31-MAY-16:00 | 71966.95 | 31-MAY-16:00 | 2188.33 | 26-MAY-05:10 | 21849.26 | 31-MAY-16:00 | 0.00 |
June | 0.855376E+11 | 0.246753E+11 | 482.36 | 0.853488E+11 | 0.188797E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 89602.67 | 29-JUN-06:03 | 89602.67 | 29-JUN-06:03 | 5545.03 | 30-JUN-11:03 | 28990.13 | 28-JUN-16:00 | 0.00 |
July | 0.879812E+11 | 0.238539E+11 | 498.48 | 0.818422E+11 | 0.613896E+10 | 0.00 | 1.00 | 01-JUL-07:30 | 0.00 | 01-JUL-00:10 | 127424.08 | 14-JUL-04:03 | 90817.65 | 17-JUL-06:03 | 77677.48 | 14-JUL-04:03 | 26840.17 | 19-JUL-14:10 | 0.00 |
August | 0.914391E+11 | 0.246491E+11 | 495.72 | 0.845726E+11 | 0.686648E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 123279.07 | 01-AUG-04:02 | 92619.63 | 14-AUG-06:03 | 59027.84 | 01-AUG-04:02 | 27433.77 | 25-AUG-16:00 | 0.00 |
September | 0.798704E+11 | 0.204405E+11 | 458.66 | 0.726216E+11 | 0.724878E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 119558.32 | 08-SEP-04:02 | 87060.19 | 18-SEP-06:03 | 70212.24 | 05-SEP-06:03 | 26106.21 | 08-SEP-04:02 | 0.00 |
October | 0.450636E+11 | 0.110040E+11 | 385.05 | 0.438459E+11 | 0.121774E+10 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 116303.35 | 03-OCT-06:03 | 86076.53 | 02-OCT-04:02 | 56280.24 | 03-OCT-06:03 | 24546.26 | 03-OCT-06:03 | 0.00 |
November | 0.202518E+11 | 0.463860E+10 | 282.63 | 0.190309E+11 | 0.122088E+10 | 0.00 | 1.00 | 01-NOV-10:10 | 0.00 | 01-NOV-00:10 | 57368.07 | 01-NOV-16:00 | 57368.07 | 01-NOV-16:00 | 29103.55 | 13-NOV-07:02 | 13527.26 | 01-NOV-15:00 | 0.00 |
December | 0.864412E+10 | 0.205202E+10 | 191.58 | 0.862336E+10 | 20752337.00 | 0.00 | 1.00 | 21-DEC-15:00 | 0.00 | 01-DEC-00:10 | 44068.80 | 22-DEC-16:20 | 44068.80 | 22-DEC-16:20 | 1132.58 | 12-DEC-13:00 | 9444.51 | 22-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.570861E+12 | 0.149073E+12 | 4382.97 | 0.546944E+12 | 0.239174E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.397784E+10 | 0.998090E+09 | 150.50 | 0.351335E+10 | 20752337.00 | 0.00 | 0.68 | 0.00 | 23249.72 | 23249.72 | 1132.58 | 5352.20 | 0.00 | ||||||
Maximum of Months | 0.914391E+11 | 0.246753E+11 | 498.48 | 0.853488E+11 | 0.724878E+10 | 0.00 | 1.00 | 0.00 | 127424.08 | 92619.63 | 77677.48 | 28990.13 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.152070E+11 | 0.356381E+10 | 276.61 | 0.150632E+11 | 0.143837E+09 | 0.00 | 1.00 | 18-JAN-15:30 | 0.00 | 01-JAN-00:10 | 42372.62 | 31-JAN-16:30 | 42372.62 | 31-JAN-16:30 | 6166.19 | 08-JAN-15:55 | 10153.72 | 31-JAN-16:30 | 0.00 |
February | 0.344055E+10 | 0.868802E+09 | 151.33 | 0.295037E+10 | 0.490187E+09 | 0.00 | 0.66 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21108.89 | 22-FEB-16:00 | 21108.89 | 22-FEB-16:00 | 3802.80 | 18-FEB-11:20 | 4883.64 | 22-FEB-16:00 | 0.00 |
March | 0.150082E+11 | 0.357631E+10 | 297.35 | 0.145579E+11 | 0.450276E+09 | 0.00 | 1.00 | 10-MAR-15:50 | 0.00 | 01-MAR-00:10 | 45353.12 | 16-MAR-15:40 | 45353.12 | 16-MAR-15:40 | 2496.11 | 17-MAR-20:00 | 10806.76 | 16-MAR-15:40 | 0.00 |
April | 0.433961E+11 | 0.107528E+11 | 411.17 | 0.433309E+11 | 65117540.40 | 0.00 | 1.00 | 03-APR-09:30 | 0.00 | 01-APR-00:10 | 64002.80 | 14-APR-15:20 | 64002.80 | 14-APR-15:20 | 2182.53 | 16-APR-09:45 | 18269.82 | 14-APR-15:20 | 0.00 |
May | 0.578625E+11 | 0.149627E+11 | 460.02 | 0.578395E+11 | 22986247.34 | 0.00 | 1.00 | 01-MAY-09:50 | 0.00 | 01-MAY-00:10 | 64356.86 | 18-MAY-15:20 | 64356.86 | 18-MAY-15:20 | 1884.99 | 26-MAY-05:10 | 19268.18 | 31-MAY-16:00 | 0.00 |
June | 0.779748E+11 | 0.225635E+11 | 479.22 | 0.778345E+11 | 0.140371E+09 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 78971.61 | 30-JUN-04:02 | 78971.61 | 30-JUN-04:02 | 4503.07 | 17-JUN-17:30 | 27385.63 | 28-JUN-15:00 | 0.00 |
July | 0.757754E+11 | 0.205723E+11 | 484.35 | 0.711318E+11 | 0.464359E+10 | 0.00 | 1.00 | 01-JUL-08:30 | 0.00 | 01-JUL-00:10 | 119133.04 | 14-JUL-05:03 | 81620.13 | 10-JUL-04:02 | 71811.95 | 14-JUL-05:03 | 24640.93 | 14-JUL-05:03 | 0.00 |
August | 0.772436E+11 | 0.208808E+11 | 484.64 | 0.722093E+11 | 0.503432E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 115638.40 | 01-AUG-04:02 | 82068.81 | 28-AUG-06:03 | 55746.11 | 01-AUG-04:02 | 25449.61 | 25-AUG-15:20 | 0.00 |
September | 0.646001E+11 | 0.166534E+11 | 434.34 | 0.595240E+11 | 0.507607E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 111939.20 | 05-SEP-06:03 | 74689.60 | 18-SEP-04:02 | 66043.61 | 05-SEP-06:03 | 24090.56 | 08-SEP-04:02 | 0.00 |
October | 0.361422E+11 | 0.894590E+10 | 374.73 | 0.350676E+11 | 0.107463E+10 | 0.00 | 1.00 | 01-OCT-11:13 | 0.00 | 01-OCT-00:10 | 79349.35 | 02-OCT-04:02 | 78851.33 | 02-OCT-04:02 | 37219.14 | 03-OCT-06:03 | 19948.31 | 02-OCT-14:00 | 0.00 |
November | 0.157454E+11 | 0.367863E+10 | 278.22 | 0.147097E+11 | 0.103571E+10 | 0.00 | 1.00 | 01-NOV-10:40 | 0.00 | 01-NOV-00:10 | 49567.05 | 01-NOV-15:30 | 49567.05 | 01-NOV-15:30 | 19085.67 | 13-NOV-15:40 | 11732.37 | 01-NOV-15:20 | 0.00 |
December | 0.697961E+10 | 0.168546E+10 | 188.83 | 0.694105E+10 | 38560831.04 | 0.00 | 1.00 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 | 35646.09 | 22-DEC-16:30 | 35646.09 | 22-DEC-16:30 | 1770.50 | 12-DEC-15:00 | 7611.40 | 22-DEC-16:30 | 0.00 |
Annual Sum or Average | 0.489375E+12 | 0.128704E+12 | 4320.81 | 0.471160E+12 | 0.182157E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.344055E+10 | 0.868802E+09 | 151.33 | 0.295037E+10 | 22986247.34 | 0.00 | 0.66 | 0.00 | 21108.89 | 21108.89 | 1770.50 | 4883.64 | 0.00 | ||||||
Maximum of Months | 0.779748E+11 | 0.225635E+11 | 484.64 | 0.778345E+11 | 0.507607E+10 | 0.00 | 1.00 | 0.00 | 119133.04 | 82068.81 | 71811.95 | 27385.63 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.147525E+11 | 0.351923E+10 | 273.67 | 0.145623E+11 | 0.190208E+09 | 0.00 | 1.00 | 27-JAN-14:20 | 0.00 | 01-JAN-00:10 | 46079.88 | 31-JAN-16:20 | 46079.88 | 31-JAN-16:20 | 2095.22 | 22-JAN-16:50 | 11042.99 | 31-JAN-16:20 | 0.00 |
February | 0.344179E+10 | 0.876398E+09 | 149.72 | 0.285690E+10 | 0.584891E+09 | 0.00 | 0.59 | 22-FEB-16:00 | 0.00 | 01-FEB-00:10 | 21018.01 | 22-FEB-16:00 | 21018.01 | 22-FEB-16:00 | 4304.60 | 18-FEB-14:00 | 4954.29 | 22-FEB-16:00 | 0.00 |
March | 0.155724E+11 | 0.374604E+10 | 296.56 | 0.149275E+11 | 0.644968E+09 | 0.00 | 1.00 | 10-MAR-15:40 | 0.00 | 01-MAR-00:10 | 51885.20 | 16-MAR-15:30 | 51885.20 | 16-MAR-15:30 | 3461.73 | 17-MAR-10:00 | 12363.02 | 16-MAR-15:30 | 0.00 |
April | 0.473984E+11 | 0.118576E+11 | 411.31 | 0.472824E+11 | 0.115945E+09 | 0.00 | 1.00 | 02-APR-13:23 | 0.00 | 01-APR-00:10 | 74909.51 | 14-APR-15:30 | 74909.51 | 14-APR-15:30 | 2550.02 | 16-APR-10:05 | 21381.14 | 14-APR-15:30 | 0.00 |
May | 0.634163E+11 | 0.165667E+11 | 461.24 | 0.633689E+11 | 47354017.68 | 0.00 | 1.00 | 01-MAY-10:40 | 0.00 | 01-MAY-00:10 | 75068.60 | 18-MAY-15:30 | 75068.60 | 18-MAY-15:30 | 2305.72 | 26-MAY-05:10 | 22388.74 | 31-MAY-16:00 | 0.00 |
June | 0.868061E+11 | 0.253344E+11 | 484.76 | 0.866236E+11 | 0.182460E+09 | 0.00 | 1.00 | 01-JUN-07:50 | 0.00 | 01-JUN-00:10 | 90976.76 | 28-JUN-14:50 | 90976.76 | 28-JUN-14:50 | 4594.36 | 17-JUN-17:30 | 32275.06 | 28-JUN-15:00 | 0.00 |
July | 0.836019E+11 | 0.228444E+11 | 491.17 | 0.787038E+11 | 0.489815E+10 | 0.00 | 1.00 | 01-JUL-09:30 | 0.00 | 01-JUL-00:10 | 125880.07 | 24-JUL-04:02 | 92270.42 | 12-JUL-04:02 | 57301.90 | 14-JUL-05:03 | 28367.50 | 19-JUL-13:40 | 0.00 |
August | 0.837933E+11 | 0.228292E+11 | 485.31 | 0.785592E+11 | 0.523415E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 131270.30 | 01-AUG-04:02 | 86631.36 | 25-AUG-15:20 | 68157.85 | 01-AUG-05:03 | 29809.96 | 25-AUG-15:20 | 0.00 |
September | 0.686463E+11 | 0.178481E+11 | 434.24 | 0.634333E+11 | 0.521305E+10 | 0.00 | 1.00 | 01-SEP-08:00 | 0.00 | 01-SEP-00:10 | 107345.79 | 08-SEP-05:03 | 83520.07 | 08-SEP-16:00 | 61903.61 | 05-SEP-06:03 | 25803.43 | 08-SEP-16:00 | 0.00 |
October | 0.372252E+11 | 0.933213E+10 | 371.79 | 0.360151E+11 | 0.121009E+10 | 0.00 | 1.00 | 01-OCT-11:23 | 0.00 | 01-OCT-00:10 | 84723.01 | 02-OCT-04:02 | 84419.87 | 02-OCT-04:02 | 15411.18 | 03-OCT-06:03 | 22566.38 | 02-OCT-13:50 | 0.00 |
November | 0.152604E+11 | 0.362778E+10 | 275.61 | 0.141725E+11 | 0.108789E+10 | 0.00 | 1.00 | 01-NOV-12:10 | 0.00 | 01-NOV-00:10 | 55521.32 | 01-NOV-15:30 | 55521.32 | 01-NOV-15:30 | 15698.75 | 13-NOV-15:40 | 13143.74 | 01-NOV-15:00 | 0.00 |
December | 0.664802E+10 | 0.163147E+10 | 183.90 | 0.658827E+10 | 59748781.37 | 0.00 | 0.95 | 22-DEC-15:30 | 0.00 | 01-DEC-00:10 | 37171.55 | 22-DEC-15:40 | 37171.55 | 22-DEC-15:40 | 2106.15 | 12-DEC-15:00 | 8254.01 | 22-DEC-15:30 | 0.00 |
Annual Sum or Average | 0.526563E+12 | 0.140013E+12 | 4319.28 | 0.507094E+12 | 0.194689E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.344179E+10 | 0.876398E+09 | 149.72 | 0.285690E+10 | 47354017.68 | 0.00 | 0.59 | 0.00 | 21018.01 | 21018.01 | 2095.22 | 4954.29 | 0.00 | ||||||
Maximum of Months | 0.868061E+11 | 0.253344E+11 | 491.17 | 0.866236E+11 | 0.523415E+10 | 0.00 | 1.00 | 0.00 | 131270.30 | 92270.42 | 68157.85 | 32275.06 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.38 | 0.00 | 284.38 | 233.17 | 1204.09 | 0.00 | 0.00 | 0.00 |
February | 324.04 | 0.00 | 324.04 | 156.90 | 1178.24 | 0.00 | 0.00 | 0.00 |
March | 430.65 | 0.00 | 430.65 | 402.15 | 1068.85 | 0.00 | 0.00 | 0.00 |
April | 524.68 | 5.44 | 519.24 | 881.38 | 595.88 | 0.00 | 0.00 | 0.00 |
May | 614.20 | 49.18 | 565.02 | 1213.85 | 405.94 | 0.00 | 0.00 | 0.00 |
June | 713.74 | 129.68 | 584.06 | 1915.36 | 177.31 | 0.00 | 0.00 | 0.00 |
July | 608.68 | 63.41 | 545.27 | 1632.88 | 135.58 | 0.00 | 0.00 | 0.00 |
August | 491.32 | 12.21 | 479.11 | 1358.27 | 169.92 | 0.00 | 0.00 | 0.00 |
September | 463.55 | 0.12 | 463.43 | 1124.80 | 254.67 | 0.00 | 0.00 | 0.00 |
October | 358.64 | 0.00 | 358.64 | 537.63 | 772.61 | 0.00 | 0.00 | 0.00 |
November | 298.81 | 0.00 | 298.81 | 230.70 | 1114.32 | 0.00 | 0.00 | 0.00 |
December | 265.64 | 0.00 | 265.64 | 146.63 | 1451.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.64 | 21.72 | 426.93 | 822.53 | 708.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.64 | 0.00 | 265.64 | 146.63 | 135.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 713.74 | 129.68 | 584.06 | 1915.36 | 1451.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.46 | 384.21 | 228.25 | 786.25 | 748.79 | 0.00 | 0.00 | 0.00 |
February | 603.70 | 345.34 | 258.35 | 680.39 | 741.21 | 0.00 | 0.00 | 0.00 |
March | 755.50 | 388.63 | 366.86 | 978.64 | 668.43 | 0.00 | 0.00 | 0.00 |
April | 1078.43 | 642.76 | 435.67 | 1788.18 | 378.69 | 0.00 | 0.00 | 0.00 |
May | 1117.64 | 662.53 | 455.11 | 1990.09 | 270.04 | 0.00 | 0.00 | 0.00 |
June | 1164.95 | 723.88 | 441.07 | 2413.14 | 113.88 | 0.00 | 0.00 | 0.00 |
July | 983.87 | 554.77 | 429.11 | 2060.26 | 86.58 | 0.00 | 0.00 | 0.00 |
August | 933.78 | 532.91 | 400.87 | 1942.21 | 109.15 | 0.00 | 0.00 | 0.00 |
September | 766.23 | 369.34 | 396.89 | 1527.03 | 160.09 | 0.00 | 0.00 | 0.00 |
October | 769.63 | 468.39 | 301.24 | 1212.54 | 481.57 | 0.00 | 0.00 | 0.00 |
November | 591.80 | 355.27 | 236.54 | 751.82 | 698.84 | 0.00 | 0.00 | 0.00 |
December | 539.57 | 325.81 | 213.76 | 615.95 | 896.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 827.48 | 480.11 | 347.37 | 1398.96 | 444.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 539.57 | 325.81 | 213.76 | 615.95 | 86.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1164.95 | 723.88 | 455.11 | 2413.14 | 896.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2341.59 | 1870.16 | 471.43 | 3563.52 | 1197.26 | 0.00 | 0.00 | 0.00 |
February | 1480.56 | 998.54 | 482.02 | 2006.04 | 1140.79 | 0.00 | 0.00 | 0.00 |
March | 1231.93 | 634.51 | 597.42 | 1800.20 | 1073.08 | 0.00 | 0.00 | 0.00 |
April | 1048.70 | 423.78 | 624.92 | 1994.60 | 625.99 | 0.00 | 0.00 | 0.00 |
May | 702.74 | 116.10 | 586.64 | 1491.00 | 442.35 | 0.00 | 0.00 | 0.00 |
June | 601.75 | 46.39 | 555.36 | 1734.25 | 184.39 | 0.00 | 0.00 | 0.00 |
July | 614.88 | 63.61 | 551.26 | 1683.66 | 136.91 | 0.00 | 0.00 | 0.00 |
August | 747.66 | 206.62 | 541.05 | 1938.32 | 171.22 | 0.00 | 0.00 | 0.00 |
September | 1077.31 | 459.61 | 617.70 | 2315.30 | 257.64 | 0.00 | 0.00 | 0.00 |
October | 1716.58 | 1188.13 | 528.45 | 2886.09 | 764.53 | 0.00 | 0.00 | 0.00 |
November | 2000.47 | 1532.25 | 468.21 | 2999.21 | 1096.84 | 0.00 | 0.00 | 0.00 |
December | 2176.98 | 1723.38 | 453.61 | 3157.91 | 1407.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.80 | 771.77 | 540.02 | 2300.31 | 706.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 601.75 | 46.39 | 453.61 | 1491.00 | 136.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2341.59 | 1870.16 | 624.92 | 3563.52 | 1407.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.43 | 398.04 | 242.39 | 937.53 | 820.52 | 0.00 | 0.00 | 0.00 |
February | 518.81 | 250.82 | 268.00 | 604.23 | 778.81 | 0.00 | 0.00 | 0.00 |
March | 687.19 | 327.59 | 359.59 | 929.06 | 708.84 | 0.00 | 0.00 | 0.00 |
April | 1055.20 | 601.92 | 453.28 | 1810.50 | 425.82 | 0.00 | 0.00 | 0.00 |
May | 1057.90 | 593.17 | 464.74 | 1943.72 | 309.96 | 0.00 | 0.00 | 0.00 |
June | 1124.66 | 661.48 | 463.18 | 2371.54 | 137.04 | 0.00 | 0.00 | 0.00 |
July | 818.55 | 382.10 | 436.45 | 1789.14 | 99.76 | 0.00 | 0.00 | 0.00 |
August | 780.56 | 392.01 | 388.55 | 1697.69 | 122.26 | 0.00 | 0.00 | 0.00 |
September | 680.39 | 285.87 | 394.52 | 1401.28 | 175.76 | 0.00 | 0.00 | 0.00 |
October | 696.18 | 398.07 | 298.11 | 1148.22 | 523.25 | 0.00 | 0.00 | 0.00 |
November | 641.20 | 387.14 | 254.06 | 908.64 | 753.30 | 0.00 | 0.00 | 0.00 |
December | 516.78 | 294.24 | 222.54 | 677.36 | 972.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 769.03 | 414.95 | 354.08 | 1354.74 | 484.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.78 | 250.82 | 222.54 | 604.23 | 99.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.66 | 661.48 | 464.74 | 2371.54 | 972.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.45 | 429.33 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 53.40 | 413.94 | 0.00 | 0.00 | 0.00 |
March | 143.54 | 0.00 | 143.54 | 140.55 | 360.49 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.07 | 301.74 | 198.37 | 0.00 | 0.00 | 0.00 |
May | 204.72 | 16.39 | 188.33 | 413.50 | 131.80 | 0.00 | 0.00 | 0.00 |
June | 237.90 | 43.22 | 194.68 | 646.55 | 55.90 | 0.00 | 0.00 | 0.00 |
July | 202.88 | 21.14 | 181.75 | 547.84 | 45.32 | 0.00 | 0.00 | 0.00 |
August | 163.76 | 4.07 | 159.70 | 452.47 | 59.82 | 0.00 | 0.00 | 0.00 |
September | 154.51 | 0.04 | 154.47 | 371.85 | 92.45 | 0.00 | 0.00 | 0.00 |
October | 119.54 | 0.00 | 119.54 | 172.49 | 288.23 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 68.28 | 420.64 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.95 | 539.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.54 | 7.24 | 142.30 | 274.59 | 252.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.95 | 45.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.90 | 43.22 | 194.68 | 646.55 | 539.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.46 | 429.36 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 53.40 | 413.96 | 0.00 | 0.00 | 0.00 |
March | 143.55 | 0.00 | 143.55 | 140.56 | 360.51 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.08 | 301.76 | 198.38 | 0.00 | 0.00 | 0.00 |
May | 204.73 | 16.39 | 188.34 | 413.52 | 131.80 | 0.00 | 0.00 | 0.00 |
June | 237.91 | 43.23 | 194.69 | 646.58 | 55.90 | 0.00 | 0.00 | 0.00 |
July | 202.89 | 21.14 | 181.76 | 547.87 | 45.33 | 0.00 | 0.00 | 0.00 |
August | 163.77 | 4.07 | 159.70 | 452.50 | 59.83 | 0.00 | 0.00 | 0.00 |
September | 154.52 | 0.04 | 154.47 | 371.87 | 92.45 | 0.00 | 0.00 | 0.00 |
October | 119.55 | 0.00 | 119.55 | 172.50 | 288.25 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 68.28 | 420.66 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.95 | 539.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.55 | 7.24 | 142.31 | 274.61 | 252.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.95 | 45.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.91 | 43.23 | 194.69 | 646.58 | 539.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.79 | 0.00 | 94.79 | 74.46 | 429.36 | 0.00 | 0.00 | 0.00 |
February | 108.01 | 0.00 | 108.01 | 53.40 | 413.96 | 0.00 | 0.00 | 0.00 |
March | 143.55 | 0.00 | 143.55 | 140.56 | 360.51 | 0.00 | 0.00 | 0.00 |
April | 174.89 | 1.81 | 173.08 | 301.76 | 198.38 | 0.00 | 0.00 | 0.00 |
May | 204.73 | 16.39 | 188.34 | 413.52 | 131.80 | 0.00 | 0.00 | 0.00 |
June | 237.91 | 43.23 | 194.69 | 646.58 | 55.90 | 0.00 | 0.00 | 0.00 |
July | 202.89 | 21.14 | 181.76 | 547.87 | 45.33 | 0.00 | 0.00 | 0.00 |
August | 163.77 | 4.07 | 159.70 | 452.50 | 59.83 | 0.00 | 0.00 | 0.00 |
September | 154.52 | 0.04 | 154.47 | 371.87 | 92.45 | 0.00 | 0.00 | 0.00 |
October | 119.55 | 0.00 | 119.55 | 172.50 | 288.25 | 0.00 | 0.00 | 0.00 |
November | 99.60 | 0.00 | 99.60 | 68.28 | 420.66 | 0.00 | 0.00 | 0.00 |
December | 88.54 | 0.00 | 88.54 | 39.95 | 539.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.55 | 7.24 | 142.31 | 274.61 | 252.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.54 | 0.00 | 88.54 | 39.95 | 45.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.91 | 43.23 | 194.69 | 646.58 | 539.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 589.15 | 369.59 | 219.56 | 745.36 | 786.88 | 0.00 | 0.00 | 0.00 |
February | 580.72 | 332.20 | 248.52 | 655.73 | 767.26 | 0.00 | 0.00 | 0.00 |
March | 726.75 | 373.84 | 352.91 | 952.34 | 668.10 | 0.00 | 0.00 | 0.00 |
April | 1037.40 | 618.30 | 419.10 | 1737.22 | 378.66 | 0.00 | 0.00 | 0.00 |
May | 1075.12 | 637.32 | 437.80 | 1933.98 | 266.49 | 0.00 | 0.00 | 0.00 |
June | 1120.62 | 696.34 | 424.29 | 2338.22 | 111.75 | 0.00 | 0.00 | 0.00 |
July | 946.44 | 533.65 | 412.78 | 1988.82 | 90.44 | 0.00 | 0.00 | 0.00 |
August | 898.25 | 512.63 | 385.62 | 1870.48 | 120.17 | 0.00 | 0.00 | 0.00 |
September | 737.07 | 355.28 | 381.79 | 1465.56 | 175.15 | 0.00 | 0.00 | 0.00 |
October | 740.35 | 450.57 | 289.78 | 1155.29 | 526.97 | 0.00 | 0.00 | 0.00 |
November | 569.29 | 341.75 | 227.54 | 701.91 | 768.73 | 0.00 | 0.00 | 0.00 |
December | 519.04 | 313.41 | 205.63 | 563.40 | 974.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.00 | 461.84 | 334.15 | 1345.61 | 468.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 519.04 | 313.41 | 205.63 | 563.40 | 90.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1120.62 | 696.34 | 437.80 | 2338.22 | 974.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.29 | 14.61 | 8.68 | 29.47 | 31.11 | 0.00 | 0.00 | 0.00 |
February | 22.96 | 13.13 | 9.83 | 25.93 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 28.74 | 14.78 | 13.95 | 37.65 | 26.42 | 0.00 | 0.00 | 0.00 |
April | 41.02 | 24.45 | 16.57 | 68.69 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 42.51 | 25.20 | 17.31 | 76.47 | 10.54 | 0.00 | 0.00 | 0.00 |
June | 44.31 | 27.53 | 16.78 | 92.45 | 4.42 | 0.00 | 0.00 | 0.00 |
July | 37.42 | 21.10 | 16.32 | 78.64 | 3.58 | 0.00 | 0.00 | 0.00 |
August | 35.52 | 20.27 | 15.25 | 73.96 | 4.75 | 0.00 | 0.00 | 0.00 |
September | 29.14 | 14.05 | 15.10 | 57.95 | 6.93 | 0.00 | 0.00 | 0.00 |
October | 29.27 | 17.82 | 11.46 | 45.68 | 20.84 | 0.00 | 0.00 | 0.00 |
November | 22.51 | 13.51 | 9.00 | 27.75 | 30.39 | 0.00 | 0.00 | 0.00 |
December | 20.52 | 12.39 | 8.13 | 22.28 | 38.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.47 | 18.26 | 13.21 | 53.20 | 18.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.52 | 12.39 | 8.13 | 22.28 | 3.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.31 | 27.53 | 17.31 | 92.45 | 38.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.52 | 623.38 | 157.14 | 1187.81 | 449.43 | 0.00 | 0.00 | 0.00 |
February | 493.51 | 332.84 | 160.67 | 676.97 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 410.64 | 211.50 | 199.14 | 611.34 | 370.33 | 0.00 | 0.00 | 0.00 |
April | 349.56 | 141.26 | 208.31 | 673.45 | 214.43 | 0.00 | 0.00 | 0.00 |
May | 234.24 | 38.70 | 195.54 | 504.46 | 146.38 | 0.00 | 0.00 | 0.00 |
June | 200.58 | 15.46 | 185.12 | 579.94 | 59.69 | 0.00 | 0.00 | 0.00 |
July | 204.96 | 21.20 | 183.75 | 559.72 | 47.68 | 0.00 | 0.00 | 0.00 |
August | 249.22 | 68.87 | 180.35 | 640.35 | 64.59 | 0.00 | 0.00 | 0.00 |
September | 359.10 | 153.20 | 205.90 | 765.09 | 99.85 | 0.00 | 0.00 | 0.00 |
October | 572.18 | 396.04 | 176.15 | 957.97 | 292.35 | 0.00 | 0.00 | 0.00 |
November | 666.81 | 510.74 | 156.07 | 995.59 | 421.48 | 0.00 | 0.00 | 0.00 |
December | 725.65 | 574.45 | 151.20 | 1047.88 | 534.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.26 | 257.25 | 180.01 | 767.60 | 258.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.58 | 15.46 | 151.20 | 504.46 | 47.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.52 | 623.38 | 208.31 | 1187.81 | 534.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.52 | 623.38 | 157.14 | 1187.81 | 449.43 | 0.00 | 0.00 | 0.00 |
February | 493.51 | 332.84 | 160.67 | 676.97 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 410.64 | 211.50 | 199.14 | 611.34 | 370.33 | 0.00 | 0.00 | 0.00 |
April | 349.56 | 141.26 | 208.31 | 673.45 | 214.43 | 0.00 | 0.00 | 0.00 |
May | 234.24 | 38.70 | 195.54 | 504.46 | 146.38 | 0.00 | 0.00 | 0.00 |
June | 200.58 | 15.46 | 185.12 | 579.94 | 59.69 | 0.00 | 0.00 | 0.00 |
July | 204.96 | 21.20 | 183.75 | 559.72 | 47.68 | 0.00 | 0.00 | 0.00 |
August | 249.22 | 68.87 | 180.35 | 640.35 | 64.59 | 0.00 | 0.00 | 0.00 |
September | 359.10 | 153.20 | 205.90 | 765.09 | 99.85 | 0.00 | 0.00 | 0.00 |
October | 572.18 | 396.04 | 176.15 | 957.97 | 292.35 | 0.00 | 0.00 | 0.00 |
November | 666.81 | 510.74 | 156.07 | 995.59 | 421.48 | 0.00 | 0.00 | 0.00 |
December | 725.65 | 574.45 | 151.20 | 1047.88 | 534.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.26 | 257.25 | 180.01 | 767.60 | 258.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.58 | 15.46 | 151.20 | 504.46 | 47.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.52 | 623.38 | 208.31 | 1187.81 | 534.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 780.47 | 623.34 | 157.13 | 1187.73 | 449.40 | 0.00 | 0.00 | 0.00 |
February | 493.48 | 332.82 | 160.66 | 676.93 | 410.81 | 0.00 | 0.00 | 0.00 |
March | 410.61 | 211.49 | 199.13 | 611.30 | 370.30 | 0.00 | 0.00 | 0.00 |
April | 349.54 | 141.25 | 208.29 | 673.40 | 214.42 | 0.00 | 0.00 | 0.00 |
May | 234.23 | 38.70 | 195.53 | 504.43 | 146.37 | 0.00 | 0.00 | 0.00 |
June | 200.57 | 15.46 | 185.11 | 579.91 | 59.69 | 0.00 | 0.00 | 0.00 |
July | 204.95 | 21.20 | 183.74 | 559.68 | 47.68 | 0.00 | 0.00 | 0.00 |
August | 249.20 | 68.87 | 180.34 | 640.31 | 64.58 | 0.00 | 0.00 | 0.00 |
September | 359.08 | 153.19 | 205.89 | 765.04 | 99.85 | 0.00 | 0.00 | 0.00 |
October | 572.15 | 396.01 | 176.14 | 957.91 | 292.33 | 0.00 | 0.00 | 0.00 |
November | 666.77 | 510.71 | 156.06 | 995.53 | 421.45 | 0.00 | 0.00 | 0.00 |
December | 725.60 | 574.41 | 151.19 | 1047.82 | 534.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 437.23 | 257.24 | 179.99 | 767.55 | 258.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.57 | 15.46 | 151.19 | 504.43 | 47.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 780.47 | 623.34 | 208.29 | 1187.73 | 534.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 616.07 | 382.89 | 233.17 | 897.08 | 867.09 | 0.00 | 0.00 | 0.00 |
February | 499.07 | 241.27 | 257.80 | 586.64 | 804.73 | 0.00 | 0.00 | 0.00 |
March | 661.04 | 315.13 | 345.91 | 907.41 | 709.94 | 0.00 | 0.00 | 0.00 |
April | 1015.05 | 579.01 | 436.04 | 1757.95 | 430.02 | 0.00 | 0.00 | 0.00 |
May | 1017.65 | 570.60 | 447.06 | 1887.09 | 309.80 | 0.00 | 0.00 | 0.00 |
June | 1081.87 | 636.31 | 445.56 | 2296.51 | 136.53 | 0.00 | 0.00 | 0.00 |
July | 787.41 | 367.56 | 419.85 | 1725.82 | 103.51 | 0.00 | 0.00 | 0.00 |
August | 750.86 | 377.10 | 373.77 | 1632.21 | 132.58 | 0.00 | 0.00 | 0.00 |
September | 654.50 | 274.99 | 379.51 | 1343.35 | 191.67 | 0.00 | 0.00 | 0.00 |
October | 669.69 | 382.93 | 286.76 | 1093.85 | 575.41 | 0.00 | 0.00 | 0.00 |
November | 616.80 | 372.41 | 244.40 | 859.33 | 835.22 | 0.00 | 0.00 | 0.00 |
December | 497.12 | 283.04 | 214.07 | 636.20 | 1054.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.77 | 399.16 | 340.61 | 1304.96 | 511.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 497.12 | 241.27 | 214.07 | 586.64 | 103.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1081.87 | 636.31 | 447.06 | 2296.51 | 1054.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.36 | 15.14 | 9.22 | 35.47 | 34.28 | 0.00 | 0.00 | 0.00 |
February | 19.73 | 9.54 | 10.19 | 23.19 | 31.82 | 0.00 | 0.00 | 0.00 |
March | 26.14 | 12.46 | 13.68 | 35.88 | 28.07 | 0.00 | 0.00 | 0.00 |
April | 40.13 | 22.89 | 17.24 | 69.51 | 17.00 | 0.00 | 0.00 | 0.00 |
May | 40.24 | 22.56 | 17.68 | 74.61 | 12.25 | 0.00 | 0.00 | 0.00 |
June | 42.78 | 25.16 | 17.62 | 90.80 | 5.40 | 0.00 | 0.00 | 0.00 |
July | 31.13 | 14.53 | 16.60 | 68.24 | 4.09 | 0.00 | 0.00 | 0.00 |
August | 29.69 | 14.91 | 14.78 | 64.54 | 5.24 | 0.00 | 0.00 | 0.00 |
September | 25.88 | 10.87 | 15.01 | 53.11 | 7.58 | 0.00 | 0.00 | 0.00 |
October | 26.48 | 15.14 | 11.34 | 43.25 | 22.75 | 0.00 | 0.00 | 0.00 |
November | 24.39 | 14.72 | 9.66 | 33.98 | 33.02 | 0.00 | 0.00 | 0.00 |
December | 19.66 | 11.19 | 8.46 | 25.15 | 41.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.25 | 15.78 | 13.47 | 51.60 | 20.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.66 | 9.54 | 8.46 | 23.19 | 4.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.78 | 25.16 | 17.68 | 90.80 | 41.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.38 | 0.00 | 284.38 | 212.60 | 1303.15 | 0.00 | 0.00 | 0.00 |
February | 324.04 | 0.00 | 324.04 | 142.29 | 1283.53 | 0.00 | 0.00 | 0.00 |
March | 430.65 | 0.00 | 430.65 | 386.27 | 1139.52 | 0.00 | 0.00 | 0.00 |
April | 524.68 | 5.44 | 519.24 | 882.45 | 623.72 | 0.00 | 0.00 | 0.00 |
May | 614.20 | 49.18 | 565.02 | 1216.67 | 418.88 | 0.00 | 0.00 | 0.00 |
June | 713.74 | 129.68 | 584.06 | 1926.49 | 180.19 | 0.00 | 0.00 | 0.00 |
July | 608.68 | 63.41 | 545.27 | 1645.61 | 137.47 | 0.00 | 0.00 | 0.00 |
August | 491.32 | 12.21 | 479.11 | 1366.88 | 174.79 | 0.00 | 0.00 | 0.00 |
September | 463.55 | 0.12 | 463.43 | 1129.71 | 264.26 | 0.00 | 0.00 | 0.00 |
October | 358.64 | 0.00 | 358.64 | 528.27 | 829.50 | 0.00 | 0.00 | 0.00 |
November | 298.81 | 0.00 | 298.81 | 212.26 | 1212.50 | 0.00 | 0.00 | 0.00 |
December | 265.64 | 0.00 | 265.64 | 125.31 | 1575.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 448.64 | 21.72 | 426.93 | 817.65 | 759.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.64 | 0.00 | 265.64 | 125.31 | 137.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 713.74 | 129.68 | 584.06 | 1926.49 | 1575.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 612.46 | 384.21 | 228.25 | 768.89 | 800.51 | 0.00 | 0.00 | 0.00 |
February | 603.70 | 345.34 | 258.35 | 667.39 | 797.72 | 0.00 | 0.00 | 0.00 |
March | 755.50 | 388.63 | 366.86 | 967.24 | 704.93 | 0.00 | 0.00 | 0.00 |
April | 1078.43 | 642.76 | 435.67 | 1791.40 | 391.78 | 0.00 | 0.00 | 0.00 |
May | 1117.64 | 662.53 | 455.11 | 1996.49 | 278.09 | 0.00 | 0.00 | 0.00 |
June | 1164.95 | 723.88 | 441.07 | 2424.26 | 116.05 | 0.00 | 0.00 | 0.00 |
July | 983.87 | 554.77 | 429.11 | 2071.57 | 87.92 | 0.00 | 0.00 | 0.00 |
August | 933.78 | 532.91 | 400.87 | 1951.33 | 112.48 | 0.00 | 0.00 | 0.00 |
September | 766.23 | 369.34 | 396.89 | 1532.60 | 165.44 | 0.00 | 0.00 | 0.00 |
October | 769.63 | 468.39 | 301.24 | 1207.21 | 510.67 | 0.00 | 0.00 | 0.00 |
November | 591.80 | 355.27 | 236.54 | 736.01 | 751.12 | 0.00 | 0.00 | 0.00 |
December | 539.57 | 325.81 | 213.76 | 592.57 | 963.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 827.48 | 480.11 | 347.37 | 1395.70 | 472.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 539.57 | 325.81 | 213.76 | 592.57 | 87.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1164.95 | 723.88 | 455.11 | 2424.26 | 963.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2341.59 | 1870.16 | 471.43 | 3545.40 | 1275.83 | 0.00 | 0.00 | 0.00 |
February | 1480.56 | 998.54 | 482.02 | 1988.35 | 1230.40 | 0.00 | 0.00 | 0.00 |
March | 1231.93 | 634.51 | 597.42 | 1786.66 | 1136.50 | 0.00 | 0.00 | 0.00 |
April | 1048.70 | 423.78 | 624.92 | 1998.76 | 654.62 | 0.00 | 0.00 | 0.00 |
May | 702.74 | 116.10 | 586.64 | 1496.16 | 460.54 | 0.00 | 0.00 | 0.00 |
June | 601.75 | 46.39 | 555.36 | 1745.11 | 189.82 | 0.00 | 0.00 | 0.00 |
July | 614.88 | 63.61 | 551.26 | 1695.96 | 140.39 | 0.00 | 0.00 | 0.00 |
August | 747.66 | 206.62 | 541.05 | 1948.38 | 177.78 | 0.00 | 0.00 | 0.00 |
September | 1077.31 | 459.61 | 617.70 | 2323.12 | 267.73 | 0.00 | 0.00 | 0.00 |
October | 1716.58 | 1188.13 | 528.45 | 2880.48 | 811.56 | 0.00 | 0.00 | 0.00 |
November | 2000.47 | 1532.25 | 468.21 | 2980.77 | 1174.78 | 0.00 | 0.00 | 0.00 |
December | 2176.98 | 1723.38 | 453.61 | 3131.03 | 1508.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1311.80 | 771.77 | 540.02 | 2296.20 | 750.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 601.75 | 46.39 | 453.61 | 1496.16 | 140.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2341.59 | 1870.16 | 624.92 | 3545.40 | 1508.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.43 | 398.04 | 242.39 | 926.90 | 881.95 | 0.00 | 0.00 | 0.00 |
February | 518.81 | 250.82 | 268.00 | 595.66 | 843.18 | 0.00 | 0.00 | 0.00 |
March | 687.19 | 327.59 | 359.59 | 919.89 | 753.38 | 0.00 | 0.00 | 0.00 |
April | 1055.20 | 601.92 | 453.28 | 1812.90 | 444.68 | 0.00 | 0.00 | 0.00 |
May | 1057.90 | 593.17 | 464.74 | 1948.65 | 321.93 | 0.00 | 0.00 | 0.00 |
June | 1124.66 | 661.48 | 463.18 | 2381.40 | 140.68 | 0.00 | 0.00 | 0.00 |
July | 818.55 | 382.10 | 436.45 | 1798.16 | 102.01 | 0.00 | 0.00 | 0.00 |
August | 780.56 | 392.01 | 388.55 | 1704.55 | 126.49 | 0.00 | 0.00 | 0.00 |
September | 680.39 | 285.87 | 394.52 | 1405.34 | 182.50 | 0.00 | 0.00 | 0.00 |
October | 696.18 | 398.07 | 298.11 | 1143.61 | 559.32 | 0.00 | 0.00 | 0.00 |
November | 641.20 | 387.14 | 254.06 | 898.24 | 814.05 | 0.00 | 0.00 | 0.00 |
December | 516.78 | 294.24 | 222.54 | 664.36 | 1048.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 769.03 | 414.95 | 354.08 | 1353.16 | 516.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 516.78 | 250.82 | 222.54 | 595.66 | 102.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.66 | 661.48 | 464.74 | 2381.40 | 1048.24 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.624533E+09 | 0.322504E+10 |
February | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.379572E+09 | 0.285040E+10 |
March | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.107711E+10 | 0.286281E+10 |
April | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.228454E+10 | 0.154452E+10 |
May | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.325119E+10 | 0.108728E+10 |
June | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.496461E+10 | 0.459591E+09 |
July | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.437351E+10 | 0.363143E+09 |
August | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.363798E+10 | 0.455118E+09 |
September | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.291547E+10 | 0.660098E+09 |
October | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.143999E+10 | 0.206936E+10 |
November | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.597976E+09 | 0.288833E+10 |
December | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.392740E+09 | 0.388880E+10 |
Annual Sum or Average | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.259392E+11 | 0.223545E+11 |
Minimum of Months | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.379572E+09 | 0.363143E+09 |
Maximum of Months | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.496461E+10 | 0.388880E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.210590E+10 | 0.200557E+10 |
February | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.164600E+10 | 0.179312E+10 |
March | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.262120E+10 | 0.179033E+10 |
April | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.463496E+10 | 0.981570E+09 |
May | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.533026E+10 | 0.723273E+09 |
June | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.625486E+10 | 0.295180E+09 |
July | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.551821E+10 | 0.231907E+09 |
August | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.520201E+10 | 0.292339E+09 |
September | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.395807E+10 | 0.414960E+09 |
October | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.324767E+10 | 0.128984E+10 |
November | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.194871E+10 | 0.181140E+10 |
December | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.164976E+10 | 0.240114E+10 |
Annual Sum or Average | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.441176E+11 | 0.140306E+11 |
Minimum of Months | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.164600E+10 | 0.231907E+09 |
Maximum of Months | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.625486E+10 | 0.240114E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.954453E+10 | 0.320674E+10 |
February | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.485300E+10 | 0.275980E+10 |
March | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.482166E+10 | 0.287413E+10 |
April | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.517000E+10 | 0.162258E+10 |
May | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.399348E+10 | 0.118478E+10 |
June | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.449517E+10 | 0.477926E+09 |
July | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.450950E+10 | 0.366704E+09 |
August | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.519161E+10 | 0.458590E+09 |
September | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.600125E+10 | 0.667807E+09 |
October | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.773011E+10 | 0.204771E+10 |
November | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.777396E+10 | 0.284300E+10 |
December | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.845815E+10 | 0.376934E+10 |
Annual Sum or Average | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.725424E+11 | 0.222791E+11 |
Minimum of Months | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.399348E+10 | 0.366704E+09 |
Maximum of Months | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.954453E+10 | 0.376934E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.251109E+10 | 0.219768E+10 |
February | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.146175E+10 | 0.188411E+10 |
March | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.248840E+10 | 0.189856E+10 |
April | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.469282E+10 | 0.110371E+10 |
May | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.520605E+10 | 0.830185E+09 |
June | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.614704E+10 | 0.355205E+09 |
July | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.479204E+10 | 0.267198E+09 |
August | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.454708E+10 | 0.327455E+09 |
September | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.363213E+10 | 0.455559E+09 |
October | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.307538E+10 | 0.140147E+10 |
November | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.235520E+10 | 0.195256E+10 |
December | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.181423E+10 | 0.260480E+10 |
Annual Sum or Average | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.427232E+11 | 0.152785E+11 |
Minimum of Months | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.146175E+10 | 0.267198E+09 |
Maximum of Months | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.614704E+10 | 0.260480E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253881E+09 | 0.00 | 0.253881E+09 | 0.199413E+09 | 0.114992E+10 |
February | 0.261295E+09 | 0.00 | 0.261295E+09 | 0.129189E+09 | 0.100140E+10 |
March | 0.384467E+09 | 0.00 | 0.384467E+09 | 0.376460E+09 | 0.965524E+09 |
April | 0.453306E+09 | 4704152.51 | 0.448602E+09 | 0.782117E+09 | 0.514181E+09 |
May | 0.548331E+09 | 43905273.21 | 0.504426E+09 | 0.110751E+10 | 0.353004E+09 |
June | 0.616640E+09 | 0.112037E+09 | 0.504603E+09 | 0.167585E+10 | 0.144887E+09 |
July | 0.543407E+09 | 56612211.67 | 0.486794E+09 | 0.146734E+10 | 0.121397E+09 |
August | 0.438627E+09 | 10896523.63 | 0.427731E+09 | 0.121190E+10 | 0.160234E+09 |
September | 0.400489E+09 | 106911.02 | 0.400382E+09 | 0.963831E+09 | 0.239630E+09 |
October | 0.320177E+09 | 0.00 | 0.320177E+09 | 0.461989E+09 | 0.772008E+09 |
November | 0.258161E+09 | 0.00 | 0.258161E+09 | 0.176983E+09 | 0.109029E+10 |
December | 0.237148E+09 | 0.00 | 0.237148E+09 | 0.107007E+09 | 0.144398E+10 |
Annual Sum or Average | 0.471593E+10 | 0.228262E+09 | 0.448767E+10 | 0.865960E+10 | 0.795646E+10 |
Minimum of Months | 0.237148E+09 | 0.00 | 0.237148E+09 | 0.107007E+09 | 0.121397E+09 |
Maximum of Months | 0.616640E+09 | 0.112037E+09 | 0.504603E+09 | 0.167585E+10 | 0.144398E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253892E+09 | 0.00 | 0.253892E+09 | 0.199423E+09 | 0.114999E+10 |
February | 0.261306E+09 | 0.00 | 0.261306E+09 | 0.129192E+09 | 0.100146E+10 |
March | 0.384483E+09 | 0.00 | 0.384483E+09 | 0.376475E+09 | 0.965580E+09 |
April | 0.453327E+09 | 4704278.96 | 0.448622E+09 | 0.782161E+09 | 0.514207E+09 |
May | 0.548355E+09 | 43906453.40 | 0.504448E+09 | 0.110757E+10 | 0.353019E+09 |
June | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.167595E+10 | 0.144892E+09 |
July | 0.543429E+09 | 56613733.42 | 0.486816E+09 | 0.146742E+10 | 0.121402E+09 |
August | 0.438646E+09 | 10896816.53 | 0.427750E+09 | 0.121197E+10 | 0.160241E+09 |
September | 0.400505E+09 | 106913.90 | 0.400398E+09 | 0.963882E+09 | 0.239641E+09 |
October | 0.320191E+09 | 0.00 | 0.320191E+09 | 0.462013E+09 | 0.772049E+09 |
November | 0.258172E+09 | 0.00 | 0.258172E+09 | 0.176991E+09 | 0.109035E+10 |
December | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.107012E+09 | 0.144406E+10 |
Annual Sum or Average | 0.471613E+10 | 0.228268E+09 | 0.448786E+10 | 0.866006E+10 | 0.795689E+10 |
Minimum of Months | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.107012E+09 | 0.121402E+09 |
Maximum of Months | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.167595E+10 | 0.144406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253892E+09 | 0.00 | 0.253892E+09 | 0.199423E+09 | 0.114999E+10 |
February | 0.261306E+09 | 0.00 | 0.261306E+09 | 0.129192E+09 | 0.100146E+10 |
March | 0.384483E+09 | 0.00 | 0.384483E+09 | 0.376475E+09 | 0.965580E+09 |
April | 0.453327E+09 | 4704278.96 | 0.448622E+09 | 0.782161E+09 | 0.514207E+09 |
May | 0.548355E+09 | 43906453.40 | 0.504448E+09 | 0.110757E+10 | 0.353019E+09 |
June | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.167595E+10 | 0.144892E+09 |
July | 0.543429E+09 | 56613733.42 | 0.486816E+09 | 0.146742E+10 | 0.121402E+09 |
August | 0.438646E+09 | 10896816.53 | 0.427750E+09 | 0.121197E+10 | 0.160241E+09 |
September | 0.400505E+09 | 106913.90 | 0.400398E+09 | 0.963882E+09 | 0.239641E+09 |
October | 0.320191E+09 | 0.00 | 0.320191E+09 | 0.462013E+09 | 0.772049E+09 |
November | 0.258172E+09 | 0.00 | 0.258172E+09 | 0.176991E+09 | 0.109035E+10 |
December | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.107012E+09 | 0.144406E+10 |
Annual Sum or Average | 0.471613E+10 | 0.228268E+09 | 0.448786E+10 | 0.866006E+10 | 0.795689E+10 |
Minimum of Months | 0.237158E+09 | 0.00 | 0.237158E+09 | 0.107012E+09 | 0.121402E+09 |
Maximum of Months | 0.616666E+09 | 0.112040E+09 | 0.504626E+09 | 0.167595E+10 | 0.144406E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.157799E+10 | 0.989912E+09 | 0.588076E+09 | 0.199638E+10 | 0.210757E+10 |
February | 0.140489E+10 | 0.803658E+09 | 0.601231E+09 | 0.158634E+10 | 0.185616E+10 |
March | 0.194653E+10 | 0.100131E+10 | 0.945223E+09 | 0.255075E+10 | 0.178944E+10 |
April | 0.268893E+10 | 0.160263E+10 | 0.108630E+10 | 0.450288E+10 | 0.981492E+09 |
May | 0.287959E+10 | 0.170699E+10 | 0.117260E+10 | 0.517997E+10 | 0.713759E+09 |
June | 0.290465E+10 | 0.180490E+10 | 0.109975E+10 | 0.606068E+10 | 0.289659E+09 |
July | 0.253493E+10 | 0.142934E+10 | 0.110559E+10 | 0.532685E+10 | 0.242245E+09 |
August | 0.240587E+10 | 0.137302E+10 | 0.103285E+10 | 0.500990E+10 | 0.321868E+09 |
September | 0.191050E+10 | 0.920890E+09 | 0.989608E+09 | 0.379874E+10 | 0.453981E+09 |
October | 0.198295E+10 | 0.120680E+10 | 0.776144E+09 | 0.309433E+10 | 0.141143E+10 |
November | 0.147559E+10 | 0.885812E+09 | 0.589777E+09 | 0.181935E+10 | 0.199255E+10 |
December | 0.139020E+10 | 0.839438E+09 | 0.550758E+09 | 0.150901E+10 | 0.260943E+10 |
Annual Sum or Average | 0.251026E+11 | 0.145647E+11 | 0.105379E+11 | 0.424352E+11 | 0.147696E+11 |
Minimum of Months | 0.139020E+10 | 0.803658E+09 | 0.550758E+09 | 0.150901E+10 | 0.242245E+09 |
Maximum of Months | 0.290465E+10 | 0.180490E+10 | 0.117260E+10 | 0.606068E+10 | 0.260943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62392202.53 | 39140221.62 | 23251980.91 | 78934873.44 | 83331602.22 |
February | 55548056.57 | 31775917.81 | 23772138.76 | 62722325.46 | 73390711.05 |
March | 76963998.23 | 39590713.41 | 37373284.82 | 0.100855E+09 | 70752964.17 |
April | 0.106318E+09 | 63366664.28 | 42951347.18 | 0.178040E+09 | 38807293.40 |
May | 0.113857E+09 | 67492884.70 | 46363669.73 | 0.204811E+09 | 28221386.27 |
June | 0.114847E+09 | 71364156.88 | 43483059.21 | 0.239634E+09 | 11452849.31 |
July | 0.100229E+09 | 56514785.80 | 43714144.83 | 0.210619E+09 | 9578168.06 |
August | 95125942.06 | 54288084.66 | 40837857.40 | 0.198087E+09 | 12726383.77 |
September | 75539357.12 | 36411166.26 | 39128190.86 | 0.150199E+09 | 17950012.21 |
October | 78403961.98 | 47715931.65 | 30688030.33 | 0.122347E+09 | 55806531.84 |
November | 58343458.76 | 35024224.80 | 23319233.96 | 71935333.20 | 78783579.17 |
December | 54967120.76 | 33190635.74 | 21776485.02 | 59665085.11 | 0.103175E+09 |
Annual Sum or Average | 0.992535E+09 | 0.575875E+09 | 0.416659E+09 | 0.167785E+10 | 0.583976E+09 |
Minimum of Months | 54967120.76 | 31775917.81 | 21776485.02 | 59665085.11 | 9578168.06 |
Maximum of Months | 0.114847E+09 | 71364156.88 | 46363669.73 | 0.239634E+09 | 0.103175E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209053E+10 | 0.166965E+10 | 0.420887E+09 | 0.318142E+10 | 0.120375E+10 |
February | 0.119390E+10 | 0.805205E+09 | 0.388695E+09 | 0.163774E+10 | 0.993894E+09 |
March | 0.109985E+10 | 0.566478E+09 | 0.533373E+09 | 0.163741E+10 | 0.991888E+09 |
April | 0.906063E+09 | 0.366135E+09 | 0.539929E+09 | 0.174558E+10 | 0.555811E+09 |
May | 0.627399E+09 | 0.103652E+09 | 0.523747E+09 | 0.135114E+10 | 0.392056E+09 |
June | 0.519907E+09 | 40077367.12 | 0.479829E+09 | 0.150321E+10 | 0.154720E+09 |
July | 0.548960E+09 | 56793669.63 | 0.492167E+09 | 0.149915E+10 | 0.127708E+09 |
August | 0.667507E+09 | 0.184464E+09 | 0.483043E+09 | 0.171511E+10 | 0.172985E+09 |
September | 0.930783E+09 | 0.397093E+09 | 0.533691E+09 | 0.198311E+10 | 0.258822E+09 |
October | 0.153254E+10 | 0.106074E+10 | 0.471797E+09 | 0.256583E+10 | 0.783023E+09 |
November | 0.172837E+10 | 0.132384E+10 | 0.404531E+09 | 0.258057E+10 | 0.109247E+10 |
December | 0.194357E+10 | 0.153860E+10 | 0.404977E+09 | 0.280665E+10 | 0.143175E+10 |
Annual Sum or Average | 0.137894E+11 | 0.811272E+10 | 0.567666E+10 | 0.242069E+11 | 0.815887E+10 |
Minimum of Months | 0.519907E+09 | 40077367.12 | 0.388695E+09 | 0.135114E+10 | 0.127708E+09 |
Maximum of Months | 0.209053E+10 | 0.166965E+10 | 0.539929E+09 | 0.318142E+10 | 0.143175E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209053E+10 | 0.166965E+10 | 0.420887E+09 | 0.318142E+10 | 0.120375E+10 |
February | 0.119390E+10 | 0.805205E+09 | 0.388695E+09 | 0.163774E+10 | 0.993894E+09 |
March | 0.109985E+10 | 0.566478E+09 | 0.533373E+09 | 0.163741E+10 | 0.991888E+09 |
April | 0.906063E+09 | 0.366135E+09 | 0.539929E+09 | 0.174558E+10 | 0.555811E+09 |
May | 0.627399E+09 | 0.103652E+09 | 0.523747E+09 | 0.135114E+10 | 0.392056E+09 |
June | 0.519907E+09 | 40077367.12 | 0.479829E+09 | 0.150321E+10 | 0.154720E+09 |
July | 0.548960E+09 | 56793669.63 | 0.492167E+09 | 0.149915E+10 | 0.127708E+09 |
August | 0.667507E+09 | 0.184464E+09 | 0.483043E+09 | 0.171511E+10 | 0.172985E+09 |
September | 0.930783E+09 | 0.397093E+09 | 0.533691E+09 | 0.198311E+10 | 0.258822E+09 |
October | 0.153254E+10 | 0.106074E+10 | 0.471797E+09 | 0.256583E+10 | 0.783023E+09 |
November | 0.172837E+10 | 0.132384E+10 | 0.404531E+09 | 0.258057E+10 | 0.109247E+10 |
December | 0.194357E+10 | 0.153860E+10 | 0.404977E+09 | 0.280665E+10 | 0.143175E+10 |
Annual Sum or Average | 0.137894E+11 | 0.811272E+10 | 0.567666E+10 | 0.242069E+11 | 0.815887E+10 |
Minimum of Months | 0.519907E+09 | 40077367.12 | 0.388695E+09 | 0.135114E+10 | 0.127708E+09 |
Maximum of Months | 0.209053E+10 | 0.166965E+10 | 0.539929E+09 | 0.318142E+10 | 0.143175E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209040E+10 | 0.166954E+10 | 0.420860E+09 | 0.318122E+10 | 0.120367E+10 |
February | 0.119382E+10 | 0.805154E+09 | 0.388670E+09 | 0.163763E+10 | 0.993831E+09 |
March | 0.109978E+10 | 0.566442E+09 | 0.533340E+09 | 0.163730E+10 | 0.991825E+09 |
April | 0.906006E+09 | 0.366111E+09 | 0.539894E+09 | 0.174547E+10 | 0.555776E+09 |
May | 0.627359E+09 | 0.103645E+09 | 0.523714E+09 | 0.135106E+10 | 0.392031E+09 |
June | 0.519874E+09 | 40074834.45 | 0.479799E+09 | 0.150312E+10 | 0.154710E+09 |
July | 0.548926E+09 | 56790080.59 | 0.492136E+09 | 0.149905E+10 | 0.127700E+09 |
August | 0.667464E+09 | 0.184452E+09 | 0.483012E+09 | 0.171501E+10 | 0.172975E+09 |
September | 0.930725E+09 | 0.397068E+09 | 0.533657E+09 | 0.198298E+10 | 0.258806E+09 |
October | 0.153244E+10 | 0.106067E+10 | 0.471767E+09 | 0.256566E+10 | 0.782974E+09 |
November | 0.172826E+10 | 0.132376E+10 | 0.404505E+09 | 0.258041E+10 | 0.109240E+10 |
December | 0.194345E+10 | 0.153850E+10 | 0.404951E+09 | 0.280647E+10 | 0.143166E+10 |
Annual Sum or Average | 0.137885E+11 | 0.811221E+10 | 0.567630E+10 | 0.242054E+11 | 0.815836E+10 |
Minimum of Months | 0.519874E+09 | 40074834.45 | 0.388670E+09 | 0.135106E+10 | 0.127700E+09 |
Maximum of Months | 0.209040E+10 | 0.166954E+10 | 0.539894E+09 | 0.318122E+10 | 0.143166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165007E+10 | 0.102554E+10 | 0.624530E+09 | 0.240275E+10 | 0.232242E+10 |
February | 0.120736E+10 | 0.583684E+09 | 0.623678E+09 | 0.141919E+10 | 0.194680E+10 |
March | 0.177053E+10 | 0.844037E+09 | 0.926493E+09 | 0.243042E+10 | 0.190150E+10 |
April | 0.263101E+10 | 0.150080E+10 | 0.113020E+10 | 0.455659E+10 | 0.111461E+10 |
May | 0.272568E+10 | 0.152829E+10 | 0.119740E+10 | 0.505437E+10 | 0.829779E+09 |
June | 0.280420E+10 | 0.164932E+10 | 0.115488E+10 | 0.595255E+10 | 0.353896E+09 |
July | 0.210900E+10 | 0.984467E+09 | 0.112453E+10 | 0.462243E+10 | 0.277230E+09 |
August | 0.201112E+10 | 0.101002E+10 | 0.100110E+10 | 0.437171E+10 | 0.355106E+09 |
September | 0.169647E+10 | 0.712785E+09 | 0.983684E+09 | 0.348197E+10 | 0.496806E+09 |
October | 0.179370E+10 | 0.102563E+10 | 0.768071E+09 | 0.292977E+10 | 0.154117E+10 |
November | 0.159875E+10 | 0.965277E+09 | 0.633475E+09 | 0.222737E+10 | 0.216489E+10 |
December | 0.133148E+10 | 0.758101E+09 | 0.573378E+09 | 0.170401E+10 | 0.282453E+10 |
Annual Sum or Average | 0.233294E+11 | 0.125880E+11 | 0.107414E+11 | 0.411531E+11 | 0.161287E+11 |
Minimum of Months | 0.120736E+10 | 0.583684E+09 | 0.573378E+09 | 0.141919E+10 | 0.277230E+09 |
Maximum of Months | 0.280420E+10 | 0.164932E+10 | 0.119740E+10 | 0.595255E+10 | 0.282453E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 65242295.63 | 40548984.50 | 24693311.13 | 95002245.70 | 91826260.16 |
February | 47737872.79 | 23078251.15 | 24659621.64 | 56113295.75 | 76974645.63 |
March | 70004991.62 | 33372360.83 | 36632630.79 | 96096321.52 | 75183739.56 |
April | 0.104027E+09 | 59340110.61 | 44687199.50 | 0.180163E+09 | 44070671.07 |
May | 0.107771E+09 | 60426971.70 | 47343870.95 | 0.199845E+09 | 32808674.78 |
June | 0.110875E+09 | 65212250.69 | 45663009.11 | 0.235358E+09 | 13992714.15 |
July | 83387558.49 | 38924817.88 | 44462740.62 | 0.182766E+09 | 10961415.89 |
August | 79517495.35 | 39935124.05 | 39582371.30 | 0.172853E+09 | 14040549.09 |
September | 67076679.30 | 28182779.44 | 38893899.86 | 0.137674E+09 | 19643248.25 |
October | 70921161.17 | 40552403.64 | 30368757.53 | 0.115840E+09 | 60936560.05 |
November | 63213042.30 | 38166061.94 | 25046980.36 | 88068096.31 | 85597591.96 |
December | 52645328.69 | 29974517.73 | 22670810.96 | 67374631.54 | 0.111679E+09 |
Annual Sum or Average | 0.922420E+09 | 0.497715E+09 | 0.424705E+09 | 0.162715E+10 | 0.637715E+09 |
Minimum of Months | 47737872.79 | 23078251.15 | 22670810.96 | 56113295.75 | 10961415.89 |
Maximum of Months | 0.110875E+09 | 65212250.69 | 47343870.95 | 0.235358E+09 | 0.111679E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.569421E+09 | 0.349035E+10 |
February | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.344223E+09 | 0.310511E+10 |
March | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.103458E+10 | 0.305209E+10 |
April | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.228732E+10 | 0.161667E+10 |
May | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.325874E+10 | 0.112192E+10 |
June | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.499346E+10 | 0.467049E+09 |
July | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.440759E+10 | 0.368207E+09 |
August | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.366106E+10 | 0.468170E+09 |
September | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.292820E+10 | 0.684962E+09 |
October | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.141492E+10 | 0.222174E+10 |
November | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.550189E+09 | 0.314279E+10 |
December | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.335630E+09 | 0.421975E+10 |
Annual Sum or Average | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.257853E+11 | 0.239588E+11 |
Minimum of Months | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.335630E+09 | 0.368207E+09 |
Maximum of Months | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.499346E+10 | 0.421975E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.205939E+10 | 0.214409E+10 |
February | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.161455E+10 | 0.192986E+10 |
March | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.259065E+10 | 0.188808E+10 |
April | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.464330E+10 | 0.101548E+10 |
May | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.534741E+10 | 0.744841E+09 |
June | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.628369E+10 | 0.300803E+09 |
July | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.554849E+10 | 0.235493E+09 |
August | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.522644E+10 | 0.301255E+09 |
September | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.397251E+10 | 0.428812E+09 |
October | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.323339E+10 | 0.136778E+10 |
November | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.190774E+10 | 0.194691E+10 |
December | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.158715E+10 | 0.258146E+10 |
Annual Sum or Average | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.440147E+11 | 0.148849E+11 |
Minimum of Months | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.158715E+10 | 0.235493E+09 |
Maximum of Months | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.628369E+10 | 0.258146E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.949599E+10 | 0.341719E+10 |
February | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.481022E+10 | 0.297658E+10 |
March | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.478538E+10 | 0.304401E+10 |
April | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.518078E+10 | 0.169677E+10 |
May | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.400733E+10 | 0.123350E+10 |
June | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.452334E+10 | 0.492018E+09 |
July | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.454245E+10 | 0.376024E+09 |
August | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.521855E+10 | 0.476173E+09 |
September | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.602152E+10 | 0.693959E+09 |
October | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.771507E+10 | 0.217368E+10 |
November | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.772616E+10 | 0.304504E+10 |
December | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.838616E+10 | 0.403955E+10 |
Annual Sum or Average | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.724130E+11 | 0.236645E+11 |
Minimum of Months | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.400733E+10 | 0.376024E+09 |
Maximum of Months | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.949599E+10 | 0.403955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.248260E+10 | 0.236222E+10 |
February | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.144102E+10 | 0.203983E+10 |
March | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.246384E+10 | 0.201786E+10 |
April | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.469903E+10 | 0.115260E+10 |
May | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.521926E+10 | 0.862244E+09 |
June | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.617258E+10 | 0.364645E+09 |
July | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.481620E+10 | 0.273231E+09 |
August | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.456548E+10 | 0.338787E+09 |
September | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.364265E+10 | 0.473032E+09 |
October | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.306306E+10 | 0.149807E+10 |
November | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.232823E+10 | 0.211002E+10 |
December | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.177943E+10 | 0.280760E+10 |
Annual Sum or Average | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.426734E+11 | 0.163001E+11 |
Minimum of Months | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.144102E+10 | 0.273231E+09 |
Maximum of Months | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.617258E+10 | 0.280760E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.17 | 1204.09 | 284.38 | 0.00 | 284.38 | 0.00 | 0.00 |
February | 156.90 | 1178.24 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 402.15 | 1068.85 | 430.65 | 0.00 | 430.65 | 0.00 | 0.00 |
April | 881.38 | 595.88 | 524.68 | 5.44 | 519.24 | 0.00 | 0.00 |
May | 1213.85 | 405.94 | 614.20 | 49.18 | 565.02 | 0.00 | 0.00 |
June | 1915.36 | 177.31 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
July | 1632.88 | 135.58 | 608.68 | 63.41 | 545.27 | 0.00 | 0.00 |
August | 1358.27 | 169.92 | 491.32 | 12.21 | 479.11 | 0.00 | 0.00 |
September | 1124.80 | 254.67 | 463.55 | 0.12 | 463.43 | 0.00 | 0.00 |
October | 537.63 | 772.61 | 358.64 | 0.00 | 358.64 | 0.00 | 0.00 |
November | 230.70 | 1114.32 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 146.63 | 1451.91 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Annual Sum or Average | 822.53 | 708.86 | 448.64 | 21.72 | 426.93 | 0.00 | 0.00 |
Minimum of Months | 146.63 | 135.58 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Maximum of Months | 1915.36 | 1451.91 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 786.25 | 748.79 | 612.46 | 384.21 | 228.25 | 0.00 | 0.00 |
February | 680.39 | 741.21 | 603.70 | 345.34 | 258.35 | 0.00 | 0.00 |
March | 978.64 | 668.43 | 755.50 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1788.18 | 378.69 | 1078.43 | 642.76 | 435.67 | 0.00 | 0.00 |
May | 1990.09 | 270.04 | 1117.64 | 662.53 | 455.11 | 0.00 | 0.00 |
June | 2413.14 | 113.88 | 1164.95 | 723.88 | 441.07 | 0.00 | 0.00 |
July | 2060.26 | 86.58 | 983.87 | 554.77 | 429.11 | 0.00 | 0.00 |
August | 1942.21 | 109.15 | 933.78 | 532.91 | 400.87 | 0.00 | 0.00 |
September | 1527.03 | 160.09 | 766.23 | 369.34 | 396.89 | 0.00 | 0.00 |
October | 1212.54 | 481.57 | 769.63 | 468.39 | 301.24 | 0.00 | 0.00 |
November | 751.82 | 698.84 | 591.80 | 355.27 | 236.54 | 0.00 | 0.00 |
December | 615.95 | 896.48 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1398.96 | 444.91 | 827.48 | 480.11 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 615.95 | 86.58 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2413.14 | 896.48 | 1164.95 | 723.88 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3563.52 | 1197.26 | 2341.59 | 1870.16 | 471.43 | 0.00 | 0.00 |
February | 2006.04 | 1140.79 | 1480.56 | 998.54 | 482.02 | 0.00 | 0.00 |
March | 1800.20 | 1073.08 | 1231.93 | 634.51 | 597.42 | 0.00 | 0.00 |
April | 1994.60 | 625.99 | 1048.70 | 423.78 | 624.92 | 0.00 | 0.00 |
May | 1491.00 | 442.35 | 702.74 | 116.10 | 586.64 | 0.00 | 0.00 |
June | 1734.25 | 184.39 | 601.75 | 46.39 | 555.36 | 0.00 | 0.00 |
July | 1683.66 | 136.91 | 614.88 | 63.61 | 551.26 | 0.00 | 0.00 |
August | 1938.32 | 171.22 | 747.66 | 206.62 | 541.05 | 0.00 | 0.00 |
September | 2315.30 | 257.64 | 1077.31 | 459.61 | 617.70 | 0.00 | 0.00 |
October | 2886.09 | 764.53 | 1716.58 | 1188.13 | 528.45 | 0.00 | 0.00 |
November | 2999.21 | 1096.84 | 2000.47 | 1532.25 | 468.21 | 0.00 | 0.00 |
December | 3157.91 | 1407.31 | 2176.98 | 1723.38 | 453.61 | 0.00 | 0.00 |
Annual Sum or Average | 2300.31 | 706.47 | 1311.80 | 771.77 | 540.02 | 0.00 | 0.00 |
Minimum of Months | 1491.00 | 136.91 | 601.75 | 46.39 | 453.61 | 0.00 | 0.00 |
Maximum of Months | 3563.52 | 1407.31 | 2341.59 | 1870.16 | 624.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 937.53 | 820.52 | 640.43 | 398.04 | 242.39 | 0.00 | 0.00 |
February | 604.23 | 778.81 | 518.81 | 250.82 | 268.00 | 0.00 | 0.00 |
March | 929.06 | 708.84 | 687.19 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1810.50 | 425.82 | 1055.20 | 601.92 | 453.28 | 0.00 | 0.00 |
May | 1943.72 | 309.96 | 1057.90 | 593.17 | 464.74 | 0.00 | 0.00 |
June | 2371.54 | 137.04 | 1124.66 | 661.48 | 463.18 | 0.00 | 0.00 |
July | 1789.14 | 99.76 | 818.55 | 382.10 | 436.45 | 0.00 | 0.00 |
August | 1697.69 | 122.26 | 780.56 | 392.01 | 388.55 | 0.00 | 0.00 |
September | 1401.28 | 175.76 | 680.39 | 285.87 | 394.52 | 0.00 | 0.00 |
October | 1148.22 | 523.25 | 696.18 | 398.07 | 298.11 | 0.00 | 0.00 |
November | 908.64 | 753.30 | 641.20 | 387.14 | 254.06 | 0.00 | 0.00 |
December | 677.36 | 972.52 | 516.78 | 294.24 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1354.74 | 484.48 | 769.03 | 414.95 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 604.23 | 99.76 | 516.78 | 250.82 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2371.54 | 972.52 | 1124.66 | 661.48 | 464.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.36 | 1288.04 | 284.37 | 0.00 | 284.37 | 0.00 | 0.00 |
February | 160.21 | 1241.87 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 421.67 | 1081.50 | 430.64 | 0.00 | 430.64 | 0.00 | 0.00 |
April | 905.26 | 595.14 | 524.68 | 5.44 | 519.23 | 0.00 | 0.00 |
May | 1240.53 | 395.40 | 614.19 | 49.18 | 565.01 | 0.00 | 0.00 |
June | 1939.72 | 167.70 | 713.72 | 129.68 | 584.05 | 0.00 | 0.00 |
July | 1643.59 | 135.98 | 608.67 | 63.41 | 545.26 | 0.00 | 0.00 |
August | 1357.47 | 179.48 | 491.31 | 12.21 | 479.10 | 0.00 | 0.00 |
September | 1115.58 | 277.36 | 463.54 | 0.12 | 463.42 | 0.00 | 0.00 |
October | 517.48 | 864.73 | 358.63 | 0.00 | 358.63 | 0.00 | 0.00 |
November | 204.85 | 1261.95 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 119.86 | 1617.42 | 265.63 | 0.00 | 265.63 | 0.00 | 0.00 |
Annual Sum or Average | 823.81 | 756.92 | 448.64 | 21.71 | 426.92 | 0.00 | 0.00 |
Minimum of Months | 119.86 | 135.98 | 265.63 | 0.00 | 265.63 | 0.00 | 0.00 |
Maximum of Months | 1939.72 | 1617.42 | 713.72 | 129.68 | 584.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 774.83 | 817.99 | 612.45 | 384.20 | 228.24 | 0.00 | 0.00 |
February | 681.65 | 797.60 | 603.69 | 345.33 | 258.35 | 0.00 | 0.00 |
March | 990.00 | 694.52 | 755.49 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1805.91 | 393.63 | 1078.41 | 642.75 | 435.67 | 0.00 | 0.00 |
May | 2010.45 | 277.02 | 1117.63 | 662.52 | 455.11 | 0.00 | 0.00 |
June | 2430.67 | 116.17 | 1164.93 | 723.87 | 441.06 | 0.00 | 0.00 |
July | 2067.45 | 94.02 | 983.86 | 554.75 | 429.10 | 0.00 | 0.00 |
August | 1944.44 | 124.92 | 933.76 | 532.90 | 400.87 | 0.00 | 0.00 |
September | 1523.51 | 182.07 | 766.22 | 369.33 | 396.89 | 0.00 | 0.00 |
October | 1200.97 | 547.80 | 769.62 | 468.38 | 301.24 | 0.00 | 0.00 |
November | 729.66 | 799.13 | 591.79 | 355.26 | 236.53 | 0.00 | 0.00 |
December | 585.68 | 1012.77 | 539.56 | 325.80 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1398.81 | 486.86 | 827.47 | 480.10 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 585.68 | 94.02 | 539.56 | 325.80 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2430.67 | 1012.77 | 1164.93 | 723.87 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3563.35 | 1348.26 | 2341.50 | 1870.09 | 471.41 | 0.00 | 0.00 |
February | 2030.88 | 1232.48 | 1480.50 | 998.50 | 482.00 | 0.00 | 0.00 |
March | 1833.97 | 1110.96 | 1231.89 | 634.48 | 597.40 | 0.00 | 0.00 |
April | 2020.30 | 643.29 | 1048.66 | 423.76 | 624.90 | 0.00 | 0.00 |
May | 1513.34 | 439.12 | 702.72 | 116.10 | 586.62 | 0.00 | 0.00 |
June | 1739.79 | 179.07 | 601.73 | 46.38 | 555.35 | 0.00 | 0.00 |
July | 1679.12 | 143.04 | 614.86 | 63.61 | 551.25 | 0.00 | 0.00 |
August | 1921.01 | 193.75 | 747.64 | 206.61 | 541.03 | 0.00 | 0.00 |
September | 2295.21 | 299.56 | 1077.27 | 459.59 | 617.68 | 0.00 | 0.00 |
October | 2873.85 | 877.02 | 1716.52 | 1188.08 | 528.43 | 0.00 | 0.00 |
November | 2986.71 | 1264.41 | 2000.39 | 1532.19 | 468.20 | 0.00 | 0.00 |
December | 3143.58 | 1603.63 | 2176.90 | 1723.30 | 453.59 | 0.00 | 0.00 |
Annual Sum or Average | 2302.74 | 776.13 | 1311.75 | 771.74 | 540.01 | 0.00 | 0.00 |
Minimum of Months | 1513.34 | 143.04 | 601.73 | 46.38 | 453.59 | 0.00 | 0.00 |
Maximum of Months | 3563.35 | 1603.63 | 2341.50 | 1870.09 | 624.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 932.55 | 901.38 | 640.43 | 398.03 | 242.39 | 0.00 | 0.00 |
February | 609.83 | 836.55 | 518.81 | 250.81 | 268.00 | 0.00 | 0.00 |
March | 943.29 | 738.01 | 687.18 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1827.45 | 447.02 | 1055.18 | 601.91 | 453.28 | 0.00 | 0.00 |
May | 1961.70 | 322.05 | 1057.89 | 593.16 | 464.73 | 0.00 | 0.00 |
June | 2387.31 | 141.93 | 1124.64 | 661.47 | 463.17 | 0.00 | 0.00 |
July | 1794.05 | 107.60 | 818.54 | 382.09 | 436.45 | 0.00 | 0.00 |
August | 1696.75 | 137.82 | 780.55 | 392.01 | 388.54 | 0.00 | 0.00 |
September | 1396.47 | 199.25 | 680.38 | 285.87 | 394.51 | 0.00 | 0.00 |
October | 1137.10 | 598.16 | 696.17 | 398.07 | 298.10 | 0.00 | 0.00 |
November | 893.30 | 868.24 | 641.19 | 387.13 | 254.06 | 0.00 | 0.00 |
December | 661.36 | 1096.25 | 516.77 | 294.23 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1356.55 | 531.66 | 769.02 | 414.94 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 609.83 | 107.60 | 516.77 | 250.81 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2387.31 | 1096.25 | 1124.64 | 661.47 | 464.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 212.60 | 1303.15 | 284.38 | 0.00 | 284.38 | 0.00 | 0.00 |
February | 142.29 | 1283.53 | 324.04 | 0.00 | 324.04 | 0.00 | 0.00 |
March | 386.27 | 1139.52 | 430.65 | 0.00 | 430.65 | 0.00 | 0.00 |
April | 882.45 | 623.72 | 524.68 | 5.44 | 519.24 | 0.00 | 0.00 |
May | 1216.67 | 418.88 | 614.20 | 49.18 | 565.02 | 0.00 | 0.00 |
June | 1926.49 | 180.19 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
July | 1645.61 | 137.47 | 608.68 | 63.41 | 545.27 | 0.00 | 0.00 |
August | 1366.88 | 174.79 | 491.32 | 12.21 | 479.11 | 0.00 | 0.00 |
September | 1129.71 | 264.26 | 463.55 | 0.12 | 463.43 | 0.00 | 0.00 |
October | 528.27 | 829.50 | 358.64 | 0.00 | 358.64 | 0.00 | 0.00 |
November | 212.26 | 1212.50 | 298.81 | 0.00 | 298.81 | 0.00 | 0.00 |
December | 125.31 | 1575.48 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Annual Sum or Average | 817.65 | 759.73 | 448.64 | 21.72 | 426.93 | 0.00 | 0.00 |
Minimum of Months | 125.31 | 137.47 | 265.64 | 0.00 | 265.64 | 0.00 | 0.00 |
Maximum of Months | 1926.49 | 1575.48 | 713.74 | 129.68 | 584.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 768.89 | 800.51 | 612.46 | 384.21 | 228.25 | 0.00 | 0.00 |
February | 667.39 | 797.72 | 603.70 | 345.34 | 258.35 | 0.00 | 0.00 |
March | 967.24 | 704.93 | 755.50 | 388.63 | 366.86 | 0.00 | 0.00 |
April | 1791.40 | 391.78 | 1078.43 | 642.76 | 435.67 | 0.00 | 0.00 |
May | 1996.49 | 278.09 | 1117.64 | 662.53 | 455.11 | 0.00 | 0.00 |
June | 2424.26 | 116.05 | 1164.95 | 723.88 | 441.07 | 0.00 | 0.00 |
July | 2071.57 | 87.92 | 983.87 | 554.77 | 429.11 | 0.00 | 0.00 |
August | 1951.33 | 112.48 | 933.78 | 532.91 | 400.87 | 0.00 | 0.00 |
September | 1532.60 | 165.44 | 766.23 | 369.34 | 396.89 | 0.00 | 0.00 |
October | 1207.21 | 510.67 | 769.63 | 468.39 | 301.24 | 0.00 | 0.00 |
November | 736.01 | 751.12 | 591.80 | 355.27 | 236.54 | 0.00 | 0.00 |
December | 592.57 | 963.81 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Annual Sum or Average | 1395.70 | 472.00 | 827.48 | 480.11 | 347.37 | 0.00 | 0.00 |
Minimum of Months | 592.57 | 87.92 | 539.57 | 325.81 | 213.76 | 0.00 | 0.00 |
Maximum of Months | 2424.26 | 963.81 | 1164.95 | 723.88 | 455.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3545.40 | 1275.83 | 2341.59 | 1870.16 | 471.43 | 0.00 | 0.00 |
February | 1988.35 | 1230.40 | 1480.56 | 998.54 | 482.02 | 0.00 | 0.00 |
March | 1786.66 | 1136.50 | 1231.93 | 634.51 | 597.42 | 0.00 | 0.00 |
April | 1998.76 | 654.62 | 1048.70 | 423.78 | 624.92 | 0.00 | 0.00 |
May | 1496.16 | 460.54 | 702.74 | 116.10 | 586.64 | 0.00 | 0.00 |
June | 1745.11 | 189.82 | 601.75 | 46.39 | 555.36 | 0.00 | 0.00 |
July | 1695.96 | 140.39 | 614.88 | 63.61 | 551.26 | 0.00 | 0.00 |
August | 1948.38 | 177.78 | 747.66 | 206.62 | 541.05 | 0.00 | 0.00 |
September | 2323.12 | 267.73 | 1077.31 | 459.61 | 617.70 | 0.00 | 0.00 |
October | 2880.48 | 811.56 | 1716.58 | 1188.13 | 528.45 | 0.00 | 0.00 |
November | 2980.77 | 1174.78 | 2000.47 | 1532.25 | 468.21 | 0.00 | 0.00 |
December | 3131.03 | 1508.20 | 2176.98 | 1723.38 | 453.61 | 0.00 | 0.00 |
Annual Sum or Average | 2296.20 | 750.40 | 1311.80 | 771.77 | 540.02 | 0.00 | 0.00 |
Minimum of Months | 1496.16 | 140.39 | 601.75 | 46.39 | 453.61 | 0.00 | 0.00 |
Maximum of Months | 3545.40 | 1508.20 | 2341.59 | 1870.16 | 624.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 926.90 | 881.95 | 640.43 | 398.04 | 242.39 | 0.00 | 0.00 |
February | 595.66 | 843.18 | 518.81 | 250.82 | 268.00 | 0.00 | 0.00 |
March | 919.89 | 753.38 | 687.19 | 327.59 | 359.59 | 0.00 | 0.00 |
April | 1812.90 | 444.68 | 1055.20 | 601.92 | 453.28 | 0.00 | 0.00 |
May | 1948.65 | 321.93 | 1057.90 | 593.17 | 464.74 | 0.00 | 0.00 |
June | 2381.40 | 140.68 | 1124.66 | 661.48 | 463.18 | 0.00 | 0.00 |
July | 1798.16 | 102.01 | 818.55 | 382.10 | 436.45 | 0.00 | 0.00 |
August | 1704.55 | 126.49 | 780.56 | 392.01 | 388.55 | 0.00 | 0.00 |
September | 1405.34 | 182.50 | 680.39 | 285.87 | 394.52 | 0.00 | 0.00 |
October | 1143.61 | 559.32 | 696.18 | 398.07 | 298.11 | 0.00 | 0.00 |
November | 898.24 | 814.05 | 641.20 | 387.14 | 254.06 | 0.00 | 0.00 |
December | 664.36 | 1048.24 | 516.78 | 294.24 | 222.54 | 0.00 | 0.00 |
Annual Sum or Average | 1353.16 | 516.87 | 769.03 | 414.95 | 354.08 | 0.00 | 0.00 |
Minimum of Months | 595.66 | 102.01 | 516.78 | 250.82 | 222.54 | 0.00 | 0.00 |
Maximum of Months | 2381.40 | 1048.24 | 1124.66 | 661.48 | 464.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.624533E+09 | 0.322504E+10 | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.00 | 0.00 |
February | 0.379572E+09 | 0.285040E+10 | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.00 | 0.00 |
March | 0.107711E+10 | 0.286281E+10 | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.00 | 0.00 |
April | 0.228454E+10 | 0.154452E+10 | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.00 | 0.00 |
May | 0.325119E+10 | 0.108728E+10 | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.00 | 0.00 |
June | 0.496461E+10 | 0.459591E+09 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
July | 0.437351E+10 | 0.363143E+09 | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.00 | 0.00 |
August | 0.363798E+10 | 0.455118E+09 | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.00 | 0.00 |
September | 0.291547E+10 | 0.660098E+09 | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.00 | 0.00 |
October | 0.143999E+10 | 0.206936E+10 | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.00 | 0.00 |
November | 0.597976E+09 | 0.288833E+10 | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.00 | 0.00 |
December | 0.392740E+09 | 0.388880E+10 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259392E+11 | 0.223545E+11 | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.379572E+09 | 0.363143E+09 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Maximum of Months | 0.496461E+10 | 0.388880E+10 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.210590E+10 | 0.200557E+10 | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.00 | 0.00 |
February | 0.164600E+10 | 0.179312E+10 | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.00 | 0.00 |
March | 0.262120E+10 | 0.179033E+10 | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.00 | 0.00 |
April | 0.463496E+10 | 0.981570E+09 | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.00 | 0.00 |
May | 0.533026E+10 | 0.723273E+09 | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.00 | 0.00 |
June | 0.625486E+10 | 0.295180E+09 | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.00 | 0.00 |
July | 0.551821E+10 | 0.231907E+09 | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.00 | 0.00 |
August | 0.520201E+10 | 0.292339E+09 | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.00 | 0.00 |
September | 0.395807E+10 | 0.414960E+09 | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.00 | 0.00 |
October | 0.324767E+10 | 0.128984E+10 | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.00 | 0.00 |
November | 0.194871E+10 | 0.181140E+10 | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.00 | 0.00 |
December | 0.164976E+10 | 0.240114E+10 | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.441176E+11 | 0.140306E+11 | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.164600E+10 | 0.231907E+09 | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.625486E+10 | 0.240114E+10 | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954453E+10 | 0.320674E+10 | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.00 | 0.00 |
February | 0.485300E+10 | 0.275980E+10 | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.00 | 0.00 |
March | 0.482166E+10 | 0.287413E+10 | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.00 | 0.00 |
April | 0.517000E+10 | 0.162258E+10 | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.00 | 0.00 |
May | 0.399348E+10 | 0.118478E+10 | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.00 | 0.00 |
June | 0.449517E+10 | 0.477926E+09 | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.00 | 0.00 |
July | 0.450950E+10 | 0.366704E+09 | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.00 | 0.00 |
August | 0.519161E+10 | 0.458590E+09 | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.00 | 0.00 |
September | 0.600125E+10 | 0.667807E+09 | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.00 | 0.00 |
October | 0.773011E+10 | 0.204771E+10 | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.00 | 0.00 |
November | 0.777396E+10 | 0.284300E+10 | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.00 | 0.00 |
December | 0.845815E+10 | 0.376934E+10 | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.725424E+11 | 0.222791E+11 | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399348E+10 | 0.366704E+09 | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.00 | 0.00 |
Maximum of Months | 0.954453E+10 | 0.376934E+10 | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.251109E+10 | 0.219768E+10 | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.00 | 0.00 |
February | 0.146175E+10 | 0.188411E+10 | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.00 | 0.00 |
March | 0.248840E+10 | 0.189856E+10 | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.00 | 0.00 |
April | 0.469282E+10 | 0.110371E+10 | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.00 | 0.00 |
May | 0.520605E+10 | 0.830185E+09 | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.00 | 0.00 |
June | 0.614704E+10 | 0.355205E+09 | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.00 | 0.00 |
July | 0.479204E+10 | 0.267198E+09 | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.00 | 0.00 |
August | 0.454708E+10 | 0.327455E+09 | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.00 | 0.00 |
September | 0.363213E+10 | 0.455559E+09 | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.00 | 0.00 |
October | 0.307538E+10 | 0.140147E+10 | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.00 | 0.00 |
November | 0.235520E+10 | 0.195256E+10 | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.00 | 0.00 |
December | 0.181423E+10 | 0.260480E+10 | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427232E+11 | 0.152785E+11 | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146175E+10 | 0.267198E+09 | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.614704E+10 | 0.260480E+10 | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598260E+09 | 0.344990E+10 | 0.761664E+09 | 0.00 | 0.761664E+09 | 0.00 | 0.00 |
February | 0.387574E+09 | 0.300433E+10 | 0.783906E+09 | 0.00 | 0.783906E+09 | 0.00 | 0.00 |
March | 0.112941E+10 | 0.289668E+10 | 0.115343E+10 | 0.00 | 0.115343E+10 | 0.00 | 0.00 |
April | 0.234644E+10 | 0.154260E+10 | 0.135996E+10 | 14112710.43 | 0.134585E+10 | 0.00 | 0.00 |
May | 0.332265E+10 | 0.105904E+10 | 0.164504E+10 | 0.131718E+09 | 0.151332E+10 | 0.00 | 0.00 |
June | 0.502775E+10 | 0.434670E+09 | 0.184997E+10 | 0.336118E+09 | 0.151386E+10 | 0.00 | 0.00 |
July | 0.440219E+10 | 0.364201E+09 | 0.163027E+10 | 0.169840E+09 | 0.146043E+10 | 0.00 | 0.00 |
August | 0.363585E+10 | 0.480715E+09 | 0.131592E+10 | 32690156.70 | 0.128323E+10 | 0.00 | 0.00 |
September | 0.289159E+10 | 0.718913E+09 | 0.120150E+10 | 320738.82 | 0.120118E+10 | 0.00 | 0.00 |
October | 0.138602E+10 | 0.231611E+10 | 0.960560E+09 | 0.00 | 0.960560E+09 | 0.00 | 0.00 |
November | 0.530965E+09 | 0.327099E+10 | 0.774506E+09 | 0.00 | 0.774506E+09 | 0.00 | 0.00 |
December | 0.321031E+09 | 0.433211E+10 | 0.711464E+09 | 0.00 | 0.711464E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259797E+11 | 0.238702E+11 | 0.141482E+11 | 0.684799E+09 | 0.134634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321031E+09 | 0.364201E+09 | 0.711464E+09 | 0.00 | 0.711464E+09 | 0.00 | 0.00 |
Maximum of Months | 0.502775E+10 | 0.433211E+10 | 0.184997E+10 | 0.336118E+09 | 0.151386E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.207531E+10 | 0.219091E+10 | 0.164038E+10 | 0.102905E+10 | 0.611328E+09 | 0.00 | 0.00 |
February | 0.164906E+10 | 0.192955E+10 | 0.146044E+10 | 0.835434E+09 | 0.625003E+09 | 0.00 | 0.00 |
March | 0.265161E+10 | 0.186020E+10 | 0.202349E+10 | 0.104090E+10 | 0.982597E+09 | 0.00 | 0.00 |
April | 0.468092E+10 | 0.102030E+10 | 0.279525E+10 | 0.166600E+10 | 0.112925E+10 | 0.00 | 0.00 |
May | 0.538478E+10 | 0.741980E+09 | 0.299345E+10 | 0.177448E+10 | 0.121897E+10 | 0.00 | 0.00 |
June | 0.630031E+10 | 0.301112E+09 | 0.301950E+10 | 0.187627E+10 | 0.114323E+10 | 0.00 | 0.00 |
July | 0.553747E+10 | 0.251824E+09 | 0.263516E+10 | 0.148585E+10 | 0.114931E+10 | 0.00 | 0.00 |
August | 0.520799E+10 | 0.334595E+09 | 0.250100E+10 | 0.142731E+10 | 0.107369E+10 | 0.00 | 0.00 |
September | 0.394893E+10 | 0.471931E+09 | 0.198604E+10 | 0.957301E+09 | 0.102874E+10 | 0.00 | 0.00 |
October | 0.321668E+10 | 0.146723E+10 | 0.206135E+10 | 0.125452E+10 | 0.806832E+09 | 0.00 | 0.00 |
November | 0.189128E+10 | 0.207133E+10 | 0.153393E+10 | 0.920837E+09 | 0.613096E+09 | 0.00 | 0.00 |
December | 0.156868E+10 | 0.271261E+10 | 0.144516E+10 | 0.872629E+09 | 0.572535E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.441130E+11 | 0.153536E+11 | 0.260952E+11 | 0.151406E+11 | 0.109546E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156868E+10 | 0.251824E+09 | 0.144516E+10 | 0.835434E+09 | 0.572535E+09 | 0.00 | 0.00 |
Maximum of Months | 0.630031E+10 | 0.271261E+10 | 0.301950E+10 | 0.187627E+10 | 0.121897E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.954407E+10 | 0.361117E+10 | 0.627147E+10 | 0.500884E+10 | 0.126263E+10 | 0.00 | 0.00 |
February | 0.491311E+10 | 0.298162E+10 | 0.358162E+10 | 0.241556E+10 | 0.116606E+10 | 0.00 | 0.00 |
March | 0.491212E+10 | 0.297560E+10 | 0.329948E+10 | 0.169940E+10 | 0.160009E+10 | 0.00 | 0.00 |
April | 0.523662E+10 | 0.166740E+10 | 0.271813E+10 | 0.109838E+10 | 0.161975E+10 | 0.00 | 0.00 |
May | 0.405334E+10 | 0.117614E+10 | 0.188216E+10 | 0.310949E+09 | 0.157121E+10 | 0.00 | 0.00 |
June | 0.450955E+10 | 0.464151E+09 | 0.155969E+10 | 0.120230E+09 | 0.143946E+10 | 0.00 | 0.00 |
July | 0.449734E+10 | 0.383115E+09 | 0.164685E+10 | 0.170377E+09 | 0.147647E+10 | 0.00 | 0.00 |
August | 0.514523E+10 | 0.518945E+09 | 0.200248E+10 | 0.553380E+09 | 0.144910E+10 | 0.00 | 0.00 |
September | 0.594919E+10 | 0.776450E+09 | 0.279229E+10 | 0.119125E+10 | 0.160104E+10 | 0.00 | 0.00 |
October | 0.769732E+10 | 0.234902E+10 | 0.459752E+10 | 0.318216E+10 | 0.141536E+10 | 0.00 | 0.00 |
November | 0.774156E+10 | 0.327734E+10 | 0.518500E+10 | 0.397144E+10 | 0.121357E+10 | 0.00 | 0.00 |
December | 0.841977E+10 | 0.429515E+10 | 0.583060E+10 | 0.461570E+10 | 0.121491E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.726192E+11 | 0.244761E+11 | 0.413673E+11 | 0.243377E+11 | 0.170296E+11 | 0.00 | 0.00 |
Minimum of Months | 0.405334E+10 | 0.383115E+09 | 0.155969E+10 | 0.120230E+09 | 0.116606E+10 | 0.00 | 0.00 |
Maximum of Months | 0.954407E+10 | 0.429515E+10 | 0.627147E+10 | 0.500884E+10 | 0.161975E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249775E+10 | 0.241424E+10 | 0.171532E+10 | 0.106609E+10 | 0.649223E+09 | 0.00 | 0.00 |
February | 0.147530E+10 | 0.202377E+10 | 0.125510E+10 | 0.606762E+09 | 0.648338E+09 | 0.00 | 0.00 |
March | 0.252652E+10 | 0.197669E+10 | 0.184054E+10 | 0.877410E+09 | 0.963126E+09 | 0.00 | 0.00 |
April | 0.473676E+10 | 0.115868E+10 | 0.273503E+10 | 0.156014E+10 | 0.117489E+10 | 0.00 | 0.00 |
May | 0.525422E+10 | 0.862588E+09 | 0.283346E+10 | 0.158872E+10 | 0.124474E+10 | 0.00 | 0.00 |
June | 0.618791E+10 | 0.367889E+09 | 0.291508E+10 | 0.171453E+10 | 0.120055E+10 | 0.00 | 0.00 |
July | 0.480520E+10 | 0.288192E+09 | 0.219238E+10 | 0.102339E+10 | 0.116899E+10 | 0.00 | 0.00 |
August | 0.454456E+10 | 0.369147E+09 | 0.209063E+10 | 0.104995E+10 | 0.104068E+10 | 0.00 | 0.00 |
September | 0.361964E+10 | 0.516450E+09 | 0.176355E+10 | 0.740968E+09 | 0.102258E+10 | 0.00 | 0.00 |
October | 0.304561E+10 | 0.160211E+10 | 0.186462E+10 | 0.106618E+10 | 0.798439E+09 | 0.00 | 0.00 |
November | 0.231544E+10 | 0.225048E+10 | 0.166197E+10 | 0.100344E+10 | 0.658522E+09 | 0.00 | 0.00 |
December | 0.177138E+10 | 0.293621E+10 | 0.138412E+10 | 0.788075E+09 | 0.596049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427803E+11 | 0.167665E+11 | 0.242518E+11 | 0.130857E+11 | 0.111661E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147530E+10 | 0.288192E+09 | 0.125510E+10 | 0.606762E+09 | 0.596049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.618791E+10 | 0.293621E+10 | 0.291508E+10 | 0.171453E+10 | 0.124474E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.569421E+09 | 0.349035E+10 | 0.761678E+09 | 0.00 | 0.761678E+09 | 0.00 | 0.00 |
February | 0.344223E+09 | 0.310511E+10 | 0.783922E+09 | 0.00 | 0.783922E+09 | 0.00 | 0.00 |
March | 0.103458E+10 | 0.305209E+10 | 0.115346E+10 | 0.00 | 0.115346E+10 | 0.00 | 0.00 |
April | 0.228732E+10 | 0.161667E+10 | 0.135998E+10 | 14113125.25 | 0.134587E+10 | 0.00 | 0.00 |
May | 0.325874E+10 | 0.112192E+10 | 0.164507E+10 | 0.131722E+09 | 0.151335E+10 | 0.00 | 0.00 |
June | 0.499346E+10 | 0.467049E+09 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
July | 0.440759E+10 | 0.368207E+09 | 0.163030E+10 | 0.169845E+09 | 0.146045E+10 | 0.00 | 0.00 |
August | 0.366106E+10 | 0.468170E+09 | 0.131594E+10 | 32691117.58 | 0.128325E+10 | 0.00 | 0.00 |
September | 0.292820E+10 | 0.684962E+09 | 0.120152E+10 | 320748.24 | 0.120120E+10 | 0.00 | 0.00 |
October | 0.141492E+10 | 0.222174E+10 | 0.960577E+09 | 0.00 | 0.960577E+09 | 0.00 | 0.00 |
November | 0.550189E+09 | 0.314279E+10 | 0.774520E+09 | 0.00 | 0.774520E+09 | 0.00 | 0.00 |
December | 0.335630E+09 | 0.421975E+10 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.257853E+11 | 0.239588E+11 | 0.141485E+11 | 0.684819E+09 | 0.134636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335630E+09 | 0.368207E+09 | 0.711477E+09 | 0.00 | 0.711477E+09 | 0.00 | 0.00 |
Maximum of Months | 0.499346E+10 | 0.421975E+10 | 0.185001E+10 | 0.336128E+09 | 0.151388E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205939E+10 | 0.214409E+10 | 0.164041E+10 | 0.102907E+10 | 0.611334E+09 | 0.00 | 0.00 |
February | 0.161455E+10 | 0.192986E+10 | 0.146046E+10 | 0.835450E+09 | 0.625010E+09 | 0.00 | 0.00 |
March | 0.259065E+10 | 0.188808E+10 | 0.202352E+10 | 0.104092E+10 | 0.982608E+09 | 0.00 | 0.00 |
April | 0.464330E+10 | 0.101548E+10 | 0.279530E+10 | 0.166603E+10 | 0.112926E+10 | 0.00 | 0.00 |
May | 0.534741E+10 | 0.744841E+09 | 0.299350E+10 | 0.177452E+10 | 0.121898E+10 | 0.00 | 0.00 |
June | 0.628369E+10 | 0.300803E+09 | 0.301954E+10 | 0.187630E+10 | 0.114324E+10 | 0.00 | 0.00 |
July | 0.554849E+10 | 0.235493E+09 | 0.263520E+10 | 0.148588E+10 | 0.114932E+10 | 0.00 | 0.00 |
August | 0.522644E+10 | 0.301255E+09 | 0.250104E+10 | 0.142734E+10 | 0.107370E+10 | 0.00 | 0.00 |
September | 0.397251E+10 | 0.428812E+09 | 0.198607E+10 | 0.957320E+09 | 0.102875E+10 | 0.00 | 0.00 |
October | 0.323339E+10 | 0.136778E+10 | 0.206138E+10 | 0.125454E+10 | 0.806840E+09 | 0.00 | 0.00 |
November | 0.190774E+10 | 0.194691E+10 | 0.153396E+10 | 0.920855E+09 | 0.613102E+09 | 0.00 | 0.00 |
December | 0.158715E+10 | 0.258146E+10 | 0.144519E+10 | 0.872646E+09 | 0.572541E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.440147E+11 | 0.148849E+11 | 0.260956E+11 | 0.151409E+11 | 0.109547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158715E+10 | 0.235493E+09 | 0.144519E+10 | 0.835450E+09 | 0.572541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.628369E+10 | 0.258146E+10 | 0.301954E+10 | 0.187630E+10 | 0.121898E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.949599E+10 | 0.341719E+10 | 0.627172E+10 | 0.500905E+10 | 0.126267E+10 | 0.00 | 0.00 |
February | 0.481022E+10 | 0.297658E+10 | 0.358176E+10 | 0.241566E+10 | 0.116610E+10 | 0.00 | 0.00 |
March | 0.478538E+10 | 0.304401E+10 | 0.329961E+10 | 0.169947E+10 | 0.160014E+10 | 0.00 | 0.00 |
April | 0.518078E+10 | 0.169677E+10 | 0.271822E+10 | 0.109843E+10 | 0.161979E+10 | 0.00 | 0.00 |
May | 0.400733E+10 | 0.123350E+10 | 0.188221E+10 | 0.310962E+09 | 0.157124E+10 | 0.00 | 0.00 |
June | 0.452334E+10 | 0.492018E+09 | 0.155972E+10 | 0.120235E+09 | 0.143949E+10 | 0.00 | 0.00 |
July | 0.454245E+10 | 0.376024E+09 | 0.164689E+10 | 0.170384E+09 | 0.147651E+10 | 0.00 | 0.00 |
August | 0.521855E+10 | 0.476173E+09 | 0.200254E+10 | 0.553403E+09 | 0.144914E+10 | 0.00 | 0.00 |
September | 0.602152E+10 | 0.693959E+09 | 0.279239E+10 | 0.119130E+10 | 0.160109E+10 | 0.00 | 0.00 |
October | 0.771507E+10 | 0.217368E+10 | 0.459769E+10 | 0.318229E+10 | 0.141540E+10 | 0.00 | 0.00 |
November | 0.772616E+10 | 0.304504E+10 | 0.518521E+10 | 0.397160E+10 | 0.121361E+10 | 0.00 | 0.00 |
December | 0.838616E+10 | 0.403955E+10 | 0.583083E+10 | 0.461589E+10 | 0.121494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.724130E+11 | 0.236645E+11 | 0.413688E+11 | 0.243387E+11 | 0.170301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.400733E+10 | 0.376024E+09 | 0.155972E+10 | 0.120235E+09 | 0.116610E+10 | 0.00 | 0.00 |
Maximum of Months | 0.949599E+10 | 0.403955E+10 | 0.627172E+10 | 0.500905E+10 | 0.161979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248260E+10 | 0.236222E+10 | 0.171534E+10 | 0.106611E+10 | 0.649229E+09 | 0.00 | 0.00 |
February | 0.144102E+10 | 0.203983E+10 | 0.125512E+10 | 0.606772E+09 | 0.648344E+09 | 0.00 | 0.00 |
March | 0.246384E+10 | 0.201786E+10 | 0.184056E+10 | 0.877424E+09 | 0.963135E+09 | 0.00 | 0.00 |
April | 0.469903E+10 | 0.115260E+10 | 0.273507E+10 | 0.156017E+10 | 0.117490E+10 | 0.00 | 0.00 |
May | 0.521926E+10 | 0.862244E+09 | 0.283349E+10 | 0.158874E+10 | 0.124475E+10 | 0.00 | 0.00 |
June | 0.617258E+10 | 0.364645E+09 | 0.291511E+10 | 0.171456E+10 | 0.120056E+10 | 0.00 | 0.00 |
July | 0.481620E+10 | 0.273231E+09 | 0.219241E+10 | 0.102341E+10 | 0.116900E+10 | 0.00 | 0.00 |
August | 0.456548E+10 | 0.338787E+09 | 0.209066E+10 | 0.104997E+10 | 0.104069E+10 | 0.00 | 0.00 |
September | 0.364265E+10 | 0.473032E+09 | 0.176357E+10 | 0.740980E+09 | 0.102259E+10 | 0.00 | 0.00 |
October | 0.306306E+10 | 0.149807E+10 | 0.186465E+10 | 0.106620E+10 | 0.798446E+09 | 0.00 | 0.00 |
November | 0.232823E+10 | 0.211002E+10 | 0.166199E+10 | 0.100346E+10 | 0.658528E+09 | 0.00 | 0.00 |
December | 0.177943E+10 | 0.280760E+10 | 0.138414E+10 | 0.788088E+09 | 0.596054E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.426734E+11 | 0.163001E+11 | 0.242521E+11 | 0.130859E+11 | 0.111662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144102E+10 | 0.273231E+09 | 0.125512E+10 | 0.606772E+09 | 0.596054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.617258E+10 | 0.280760E+10 | 0.291511E+10 | 0.171456E+10 | 0.124475E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.413957E+10 | -0.390564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233937436.9 | 60.05 | 0.00 | 0.00 |
February | 0.372718E+10 | -0.351538E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -211805132.5 | 60.05 | 0.00 | 0.00 |
March | 0.419595E+10 | -0.396234E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233604520.1 | 60.05 | 0.00 | 0.00 |
April | 0.351439E+10 | -0.328969E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224701329.4 | 60.05 | 0.00 | 0.00 |
May | 0.344265E+10 | -0.321079E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231860854.2 | 60.05 | 0.00 | 0.00 |
June | 0.314948E+10 | -0.292479E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224694240.7 | 60.05 | 0.00 | 0.00 |
July | 0.286647E+10 | -0.263463E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231840447.6 | 60.05 | 0.00 | 0.00 |
August | 0.318823E+10 | -0.295607E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232157021.0 | 60.05 | 0.00 | 0.00 |
September | 0.307160E+10 | -0.284767E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223935687.3 | 60.05 | 0.00 | 0.00 |
October | 0.345950E+10 | -0.322791E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231593764.1 | 60.05 | 0.00 | 0.00 |
November | 0.370176E+10 | -0.347676E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224992496.0 | 60.05 | 0.00 | 0.00 |
December | 0.391470E+10 | -0.368046E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234235265.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.423715E+11 | -0.396321E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273936E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.286647E+10 | -0.396234E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234235265.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.419595E+10 | -0.263463E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -211805132.5 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9218.88 | 38.85 | 306.33 | 291.50 | 2436.74 | 28.41 | 169.67 | 288.00 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8283.88 | 36.27 | 234.17 | 264.83 | 1339.57 | 22.68 | 120.67 | 223.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1574.63 | 17.89 | 2.33 | 328.00 | 935.58 | 20.09 | 122.33 | 287.00 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:09 | 1207.17 | 17.60 | 0.00 | 332.00 | 768.63 | 19.77 | 62.33 | 301.67 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:40 | 949.30 | 17.37 | 0.00 | 357.17 | 602.74 | 19.60 | 14.00 | 315.33 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:30 | 784.93 | 16.62 | 0.00 | 361.17 | 511.77 | 18.90 | 0.83 | 309.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:00 | 914.36 | 17.03 | 0.00 | 361.00 | 557.01 | 19.26 | 18.50 | 292.17 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1054.37 | 17.37 | 0.00 | 336.00 | 649.71 | 19.58 | 34.00 | 286.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1522.06 | 18.32 | 11.00 | 318.17 | 866.34 | 20.07 | 103.67 | 286.00 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3179.12 | 23.99 | 140.17 | 318.00 | 1155.51 | 20.01 | 87.50 | 300.33 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8721.07 | 37.48 | 282.00 | 285.17 | 1670.68 | 25.02 | 132.50 | 267.33 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8517.76 | 38.33 | 284.17 | 279.67 | 2272.90 | 28.09 | 164.67 | 274.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3371.53 | 23.55 | 1260.17 | 3832.67 | 1077.27 | 21.44 | 1030.67 | 3431.50 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 784.93 | 16.62 | 0.00 | 264.83 | 511.77 | 18.90 | 0.83 | 223.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9218.88 | 38.85 | 306.33 | 361.17 | 2436.74 | 28.41 | 169.67 | 315.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2076.31 | 20.48 | 87.17 | 266.83 | 1197.38 | 23.03 | 77.33 | 221.83 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2616.93 | 23.04 | 85.83 | 253.33 | 1462.84 | 23.47 | 63.17 | 184.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2139.37 | 19.74 | 86.17 | 312.00 | 1159.01 | 21.90 | 69.67 | 277.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3062.20 | 21.30 | 112.33 | 345.33 | 1724.30 | 22.22 | 82.33 | 321.33 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3424.52 | 21.06 | 118.50 | 377.17 | 1393.54 | 21.68 | 72.33 | 351.00 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3493.73 | 21.77 | 134.33 | 385.83 | 1377.15 | 21.14 | 74.83 | 347.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3006.99 | 20.65 | 115.33 | 379.17 | 1242.19 | 21.13 | 68.33 | 319.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2977.51 | 21.56 | 114.50 | 350.50 | 1655.08 | 22.38 | 83.50 | 305.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:30 | 2342.57 | 21.09 | 102.00 | 316.67 | 1264.60 | 22.17 | 75.17 | 275.17 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-06:00 | 2215.46 | 19.43 | 87.83 | 288.83 | 1234.45 | 21.58 | 72.33 | 250.17 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1845.00 | 20.91 | 80.17 | 267.83 | 978.35 | 21.53 | 52.83 | 202.33 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-07:40 | 2139.86 | 22.83 | 101.67 | 253.83 | 1196.01 | 23.53 | 77.17 | 200.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2669.84 | 21.10 | 1225.83 | 3797.33 | 1333.23 | 22.06 | 869.00 | 3255.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1845.00 | 19.43 | 80.17 | 253.33 | 978.35 | 21.13 | 52.83 | 184.17 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 3493.73 | 23.04 | 134.33 | 385.83 | 1724.30 | 23.53 | 83.50 | 351.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 451.18 | 13.85 | 0.00 | 220.50 | 313.40 | 16.59 | 0.00 | 120.00 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:50 | 556.81 | 14.87 | 0.00 | 222.83 | 360.28 | 17.29 | 0.00 | 125.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 638.82 | 16.16 | 0.00 | 298.50 | 401.00 | 18.37 | 0.00 | 225.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 752.09 | 17.42 | 0.00 | 335.33 | 496.75 | 19.59 | 5.67 | 302.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 889.93 | 18.17 | 2.67 | 388.50 | 587.96 | 20.40 | 52.50 | 373.33 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1036.62 | 21.17 | 81.50 | 399.17 | 637.57 | 23.31 | 125.00 | 395.00 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 917.83 | 20.49 | 62.50 | 394.00 | 586.42 | 22.60 | 109.00 | 360.00 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 762.89 | 17.46 | 0.00 | 347.67 | 486.84 | 19.65 | 7.67 | 293.67 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 726.78 | 16.76 | 0.00 | 313.50 | 447.39 | 18.90 | 1.00 | 253.83 |
October | 348.00 | 0.58 | 0.48 | 01-OCT-07:00 | 521.46 | 14.79 | 0.00 | 256.83 | 349.89 | 17.23 | 0.00 | 173.67 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 490.67 | 14.56 | 0.00 | 230.67 | 328.12 | 17.20 | 0.00 | 121.17 |
December | 290.67 | 0.59 | 0.48 | 01-DEC-09:30 | 455.16 | 14.01 | 0.00 | 206.33 | 308.45 | 16.76 | 0.00 | 95.67 |
Annual Sum or Average | 4135.50 | 0.54 | 707.24 | 16.94 | 146.67 | 3613.83 | 456.48 | 19.26 | 300.83 | 2840.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 451.18 | 13.85 | 0.00 | 206.33 | 308.45 | 16.59 | 0.00 | 95.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1036.62 | 21.17 | 81.50 | 399.17 | 637.57 | 23.31 | 125.00 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:09 | 2330.95 | 21.98 | 105.67 | 243.83 | 1307.92 | 22.37 | 76.33 | 205.33 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2358.35 | 21.21 | 81.17 | 234.50 | 923.45 | 20.10 | 36.67 | 173.50 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:20 | 1944.55 | 19.06 | 79.00 | 310.00 | 1087.61 | 21.53 | 65.33 | 272.83 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2851.99 | 18.95 | 85.00 | 332.83 | 1592.24 | 20.26 | 55.00 | 304.50 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 3064.68 | 16.66 | 54.50 | 361.67 | 1695.54 | 17.20 | 0.00 | 330.33 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:40 | 3082.11 | 12.97 | 0.00 | 367.83 | 1260.22 | 16.79 | 0.00 | 339.17 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-08:20 | 2302.20 | 13.86 | 3.67 | 368.00 | 1045.55 | 17.23 | 0.00 | 318.83 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2379.75 | 16.50 | 49.17 | 340.33 | 1310.19 | 17.35 | 5.00 | 293.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:00 | 1871.79 | 19.18 | 81.83 | 315.83 | 1027.58 | 20.39 | 53.83 | 279.17 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:09 | 2305.85 | 21.05 | 109.33 | 283.33 | 1269.07 | 22.00 | 81.17 | 248.50 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2102.96 | 20.25 | 80.83 | 249.00 | 1176.43 | 21.98 | 62.50 | 204.00 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1776.80 | 20.17 | 80.67 | 234.00 | 944.69 | 20.85 | 53.83 | 193.00 |
Annual Sum or Average | 4135.50 | 0.53 | 2401.43 | 18.16 | 810.83 | 3641.17 | 1239.43 | 19.64 | 489.67 | 3162.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1776.80 | 12.97 | 0.00 | 234.00 | 923.45 | 16.79 | 0.00 | 173.50 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3082.11 | 21.98 | 109.33 | 368.00 | 1695.54 | 22.37 | 81.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9059.71 | 38.64 | 306.33 | 291.00 | 2299.48 | 26.31 | 145.50 | 286.50 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8157.66 | 36.03 | 234.17 | 264.17 | 1239.38 | 20.03 | 40.67 | 219.50 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1490.94 | 14.06 | 2.33 | 326.67 | 872.47 | 17.66 | 1.83 | 283.50 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 1149.54 | 14.17 | 0.00 | 329.00 | 727.80 | 17.76 | 0.00 | 299.17 |
May | 403.17 | 0.53 | 0.48 | 01-MAY-07:40 | 913.49 | 13.98 | 0.00 | 354.17 | 581.20 | 17.59 | 0.00 | 312.00 |
June | 418.17 | 0.54 | 0.48 | 01-JUN-07:30 | 758.56 | 13.25 | 0.00 | 357.50 | 497.42 | 16.89 | 0.00 | 302.33 |
July | 399.50 | 0.54 | 0.48 | 01-JUL-07:00 | 880.71 | 13.53 | 0.00 | 357.83 | 537.19 | 17.11 | 0.00 | 287.50 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1009.53 | 13.84 | 0.00 | 333.33 | 620.01 | 17.44 | 0.00 | 282.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1449.38 | 14.68 | 10.83 | 316.67 | 813.88 | 17.68 | 0.00 | 282.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3070.44 | 21.30 | 139.83 | 316.50 | 1066.74 | 17.40 | 13.17 | 297.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8577.71 | 37.20 | 281.83 | 284.83 | 1550.63 | 22.52 | 89.17 | 266.17 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8346.21 | 37.82 | 282.17 | 279.17 | 2135.55 | 25.86 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.52 | 3289.29 | 20.98 | 1257.50 | 3810.83 | 1014.14 | 19.19 | 421.00 | 3392.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 758.56 | 13.25 | 0.00 | 264.17 | 497.42 | 16.89 | 0.00 | 219.50 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 9059.71 | 38.64 | 306.33 | 357.83 | 2299.48 | 26.31 | 145.50 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2023.01 | 19.99 | 87.17 | 263.00 | 1152.30 | 22.83 | 75.67 | 217.67 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2554.70 | 22.59 | 85.83 | 251.83 | 1413.18 | 23.27 | 63.00 | 179.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2078.28 | 19.25 | 86.17 | 309.00 | 1105.93 | 21.71 | 69.83 | 273.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-06:40 | 2983.42 | 20.85 | 112.33 | 344.67 | 1663.05 | 22.04 | 82.33 | 318.17 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-05:00 | 3339.35 | 20.54 | 117.83 | 376.17 | 1329.32 | 21.52 | 72.33 | 348.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3348.66 | 19.71 | 115.00 | 384.50 | 1315.81 | 20.98 | 74.83 | 342.00 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-05:00 | 2936.52 | 20.19 | 115.33 | 376.50 | 1184.14 | 20.97 | 68.33 | 314.50 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2899.22 | 21.11 | 114.50 | 348.00 | 1596.92 | 22.21 | 83.50 | 301.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 2282.27 | 20.63 | 102.00 | 314.67 | 1214.85 | 21.98 | 75.17 | 271.33 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-06:00 | 2153.85 | 18.95 | 87.83 | 285.17 | 1183.40 | 21.39 | 72.17 | 248.33 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1763.91 | 19.93 | 76.33 | 262.17 | 936.64 | 21.31 | 52.83 | 198.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-07:49 | 1995.49 | 20.38 | 85.33 | 248.00 | 1154.85 | 23.32 | 74.33 | 197.17 |
Annual Sum or Average | 4135.50 | 0.52 | 2587.16 | 20.29 | 1185.67 | 3763.67 | 1279.43 | 21.88 | 864.33 | 3209.33 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1763.91 | 18.95 | 76.33 | 248.00 | 936.64 | 20.97 | 52.83 | 179.17 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3348.66 | 22.59 | 117.83 | 384.50 | 1663.05 | 23.32 | 83.50 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 434.94 | 10.39 | 0.00 | 212.50 | 305.59 | 14.32 | 0.00 | 111.50 |
February | 241.00 | 0.58 | 0.48 | 01-FEB-12:50 | 537.76 | 11.43 | 0.00 | 219.33 | 350.58 | 15.12 | 0.00 | 120.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 617.28 | 12.79 | 0.00 | 296.17 | 389.74 | 16.37 | 0.00 | 218.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 727.10 | 14.30 | 0.00 | 333.83 | 484.35 | 17.92 | 0.00 | 299.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 859.89 | 14.78 | 2.67 | 386.67 | 571.76 | 18.48 | 4.17 | 371.17 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1004.40 | 18.28 | 81.33 | 398.83 | 618.83 | 21.54 | 82.83 | 394.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 885.28 | 17.47 | 62.50 | 393.17 | 567.82 | 20.74 | 62.83 | 356.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:49 | 737.36 | 14.06 | 0.00 | 344.50 | 473.63 | 17.74 | 0.00 | 286.50 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 701.62 | 13.41 | 0.00 | 310.33 | 433.96 | 16.91 | 0.00 | 247.67 |
October | 348.00 | 0.59 | 0.48 | 01-OCT-07:00 | 504.22 | 11.41 | 0.00 | 251.17 | 341.46 | 15.18 | 0.00 | 167.00 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 473.48 | 10.98 | 0.00 | 223.33 | 319.60 | 14.91 | 0.00 | 112.00 |
December | 290.67 | 0.60 | 0.48 | 01-DEC-09:00 | 438.52 | 10.41 | 0.00 | 199.67 | 300.23 | 14.38 | 0.00 | 86.67 |
Annual Sum or Average | 4135.50 | 0.54 | 683.31 | 13.63 | 146.50 | 3569.50 | 443.80 | 17.26 | 149.83 | 2772.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 434.94 | 10.39 | 0.00 | 199.67 | 300.23 | 14.32 | 0.00 | 86.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1004.40 | 18.28 | 81.33 | 398.83 | 618.83 | 21.54 | 82.83 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 2153.12 | 19.50 | 86.50 | 239.17 | 1260.16 | 22.27 | 76.17 | 201.83 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2301.06 | 20.81 | 81.17 | 232.67 | 880.91 | 19.98 | 36.67 | 171.33 |
March | 344.33 | 0.54 | 0.48 | 02-MAR-09:20 | 1887.80 | 18.61 | 79.00 | 308.17 | 1040.46 | 21.40 | 65.33 | 269.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2772.25 | 18.47 | 85.00 | 330.17 | 1529.55 | 20.09 | 55.00 | 302.17 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 2982.56 | 16.16 | 54.50 | 359.50 | 1635.25 | 17.03 | 0.00 | 328.17 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 3011.52 | 12.44 | 0.00 | 365.00 | 1200.06 | 16.60 | 0.00 | 336.50 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:20 | 2241.67 | 13.31 | 3.67 | 365.00 | 999.21 | 17.03 | 0.00 | 315.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2312.02 | 15.97 | 49.17 | 337.83 | 1262.26 | 17.16 | 5.00 | 290.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1818.09 | 18.73 | 81.83 | 313.17 | 983.80 | 20.24 | 53.83 | 275.00 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:20 | 2249.64 | 20.63 | 109.33 | 281.50 | 1223.26 | 21.88 | 81.17 | 246.33 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2041.05 | 19.82 | 80.83 | 245.67 | 1126.59 | 21.87 | 62.33 | 201.17 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1725.18 | 19.76 | 80.67 | 231.33 | 892.70 | 20.52 | 50.50 | 190.00 |
Annual Sum or Average | 4135.50 | 0.54 | 2328.57 | 17.53 | 791.67 | 3609.17 | 1188.36 | 19.47 | 486.00 | 3127.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1725.18 | 12.44 | 0.00 | 231.33 | 880.91 | 16.60 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3011.52 | 20.81 | 109.33 | 365.00 | 1635.25 | 22.27 | 81.17 | 336.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:00 | 9059.70 | 38.64 | 306.33 | 291.00 | 2299.42 | 26.31 | 145.50 | 286.50 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8157.59 | 36.03 | 234.17 | 264.17 | 1239.31 | 20.03 | 40.67 | 219.50 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1490.86 | 14.06 | 2.33 | 326.67 | 872.41 | 17.66 | 1.83 | 283.50 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 1149.49 | 14.17 | 0.00 | 329.00 | 727.76 | 17.76 | 0.00 | 299.17 |
May | 403.17 | 0.53 | 0.48 | 01-MAY-07:40 | 913.46 | 13.98 | 0.00 | 354.17 | 581.17 | 17.59 | 0.00 | 312.00 |
June | 418.17 | 0.54 | 0.48 | 01-JUN-07:30 | 758.54 | 13.25 | 0.00 | 357.50 | 497.40 | 16.89 | 0.00 | 302.33 |
July | 399.50 | 0.54 | 0.48 | 01-JUL-07:00 | 880.67 | 13.53 | 0.00 | 357.83 | 537.16 | 17.11 | 0.00 | 287.50 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1009.49 | 13.84 | 0.00 | 333.33 | 619.97 | 17.44 | 0.00 | 282.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1449.30 | 14.68 | 10.83 | 316.67 | 813.82 | 17.69 | 0.00 | 282.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3070.38 | 21.30 | 139.83 | 316.50 | 1066.69 | 17.40 | 13.17 | 297.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8577.68 | 37.20 | 281.83 | 284.83 | 1550.57 | 22.52 | 89.17 | 266.17 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8346.20 | 37.82 | 282.17 | 279.17 | 2135.48 | 25.86 | 130.67 | 273.67 |
Annual Sum or Average | 4135.50 | 0.52 | 3289.25 | 20.98 | 1257.50 | 3810.83 | 1014.09 | 19.19 | 421.00 | 3392.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 758.54 | 13.25 | 0.00 | 264.17 | 497.40 | 16.89 | 0.00 | 219.50 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 9059.70 | 38.64 | 306.33 | 357.83 | 2299.42 | 26.31 | 145.50 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 2023.01 | 19.99 | 87.17 | 263.00 | 1152.27 | 22.83 | 76.00 | 217.67 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:49 | 2554.69 | 22.59 | 85.83 | 251.83 | 1413.14 | 23.27 | 63.00 | 179.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2078.24 | 19.25 | 86.17 | 309.00 | 1105.89 | 21.71 | 69.83 | 273.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-06:40 | 2983.41 | 20.85 | 112.33 | 344.67 | 1663.00 | 22.04 | 82.33 | 318.17 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-05:00 | 3339.34 | 20.54 | 117.83 | 376.17 | 1329.28 | 21.52 | 72.33 | 348.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3348.65 | 19.71 | 115.00 | 384.50 | 1315.77 | 20.98 | 74.83 | 342.00 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-05:00 | 2936.49 | 20.20 | 115.33 | 376.50 | 1184.10 | 20.97 | 68.33 | 314.50 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2899.19 | 21.11 | 114.50 | 348.00 | 1596.87 | 22.21 | 83.50 | 301.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 2282.23 | 20.64 | 102.00 | 314.67 | 1214.80 | 21.98 | 75.17 | 271.33 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-06:00 | 2153.83 | 18.95 | 87.83 | 285.17 | 1183.37 | 21.39 | 72.17 | 248.33 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1763.89 | 19.93 | 76.33 | 262.17 | 936.61 | 21.31 | 52.83 | 198.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-07:49 | 1995.49 | 20.38 | 85.33 | 248.00 | 1154.83 | 23.32 | 74.33 | 197.17 |
Annual Sum or Average | 4135.50 | 0.52 | 2587.14 | 20.29 | 1185.67 | 3763.67 | 1279.39 | 21.88 | 864.67 | 3209.33 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1763.89 | 18.95 | 76.33 | 248.00 | 936.61 | 20.97 | 52.83 | 179.17 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3348.65 | 22.59 | 117.83 | 384.50 | 1663.00 | 23.32 | 83.50 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.60 | 0.48 | 01-JAN-10:20 | 434.95 | 10.39 | 0.00 | 212.50 | 305.57 | 14.32 | 0.00 | 111.50 |
February | 241.00 | 0.58 | 0.48 | 01-FEB-12:50 | 537.76 | 11.44 | 0.00 | 219.33 | 350.56 | 15.12 | 0.00 | 120.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 617.26 | 12.79 | 0.00 | 296.17 | 389.72 | 16.37 | 0.00 | 218.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:39 | 727.09 | 14.30 | 0.00 | 333.83 | 484.33 | 17.92 | 0.00 | 299.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 859.88 | 14.79 | 2.67 | 386.67 | 571.73 | 18.49 | 4.17 | 371.17 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:00 | 1004.38 | 18.28 | 81.33 | 398.83 | 618.81 | 21.54 | 82.83 | 394.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 885.26 | 17.47 | 62.50 | 393.17 | 567.79 | 20.74 | 62.83 | 356.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:49 | 737.35 | 14.07 | 0.00 | 344.50 | 473.60 | 17.74 | 0.00 | 286.50 |
September | 350.17 | 0.54 | 0.48 | 01-SEP-07:19 | 701.61 | 13.41 | 0.00 | 310.33 | 433.93 | 16.91 | 0.00 | 247.67 |
October | 348.00 | 0.59 | 0.48 | 01-OCT-07:00 | 504.22 | 11.41 | 0.00 | 251.17 | 341.44 | 15.18 | 0.00 | 167.00 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 473.48 | 10.98 | 0.00 | 223.33 | 319.59 | 14.91 | 0.00 | 112.00 |
December | 290.67 | 0.60 | 0.48 | 01-DEC-09:00 | 438.52 | 10.41 | 0.00 | 199.67 | 300.22 | 14.38 | 0.00 | 86.67 |
Annual Sum or Average | 4135.50 | 0.54 | 683.30 | 13.63 | 146.50 | 3569.50 | 443.78 | 17.26 | 149.83 | 2772.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 434.95 | 10.39 | 0.00 | 199.67 | 300.22 | 14.32 | 0.00 | 86.67 | |
Maximum of Months | 418.17 | 0.60 | 0.48 | 1004.38 | 18.28 | 81.33 | 398.83 | 618.81 | 21.54 | 82.83 | 394.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 2153.12 | 19.51 | 86.50 | 239.17 | 1260.13 | 22.27 | 76.17 | 201.83 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:20 | 2301.04 | 20.82 | 81.17 | 232.67 | 880.87 | 19.98 | 36.67 | 171.33 |
March | 344.33 | 0.54 | 0.48 | 02-MAR-09:20 | 1887.77 | 18.61 | 79.00 | 308.17 | 1040.41 | 21.40 | 65.33 | 269.67 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:50 | 2772.24 | 18.47 | 85.00 | 330.17 | 1529.51 | 20.09 | 55.00 | 302.17 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:00 | 2982.54 | 16.16 | 54.50 | 359.50 | 1635.20 | 17.03 | 0.00 | 328.17 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 3011.51 | 12.44 | 0.00 | 365.00 | 1200.02 | 16.60 | 0.00 | 336.50 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:20 | 2241.64 | 13.31 | 3.67 | 365.00 | 999.17 | 17.03 | 0.00 | 315.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:20 | 2312.00 | 15.98 | 49.17 | 337.83 | 1262.22 | 17.16 | 5.00 | 290.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:09 | 1818.06 | 18.73 | 81.83 | 313.17 | 983.75 | 20.24 | 53.83 | 275.00 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:20 | 2249.63 | 20.63 | 109.33 | 281.50 | 1223.22 | 21.88 | 81.17 | 246.33 |
November | 288.50 | 0.55 | 0.48 | 01-NOV-08:50 | 2041.05 | 19.82 | 80.83 | 245.67 | 1126.56 | 21.87 | 62.33 | 201.17 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:30 | 1725.17 | 19.76 | 80.67 | 231.33 | 892.67 | 20.52 | 50.50 | 190.00 |
Annual Sum or Average | 4135.50 | 0.54 | 2328.55 | 17.54 | 791.67 | 3609.17 | 1188.32 | 19.47 | 486.00 | 3127.17 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1725.17 | 12.44 | 0.00 | 231.33 | 880.87 | 16.60 | 0.00 | 171.33 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 3011.51 | 20.82 | 109.33 | 365.00 | 1635.20 | 22.27 | 81.17 | 336.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8092674.52 | 1935.94 | 02-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 240276.63 | 436.60 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17451479.76 | 3348.45 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 349488.17 | 1387.90 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161298E+09 | 6171.25 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161298E+09 | 6171.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.653946E+09 | 8938.01 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713964E+09 | 8938.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.810051E+09 | 8938.01 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137820E+09 | 8938.01 | 07-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6526175.47 | 6555.40 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271572E+09 | 8938.01 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374579E+09 | 8938.01 | 06-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.778980E+09 | 8938.01 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.810051E+09 | 8938.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11086249.84 | 5923.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12518549.52 | 5923.71 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9569314.78 | 5923.71 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17807154.88 | 5923.71 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50981269.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17807154.88 | 5923.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44758293.45 | 8852.06 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46424400.80 | 8852.06 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40435326.57 | 8852.06 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 892128.72 | 3301.76 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72316586.83 | 8852.06 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72316586.83 | 8852.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14575577.70 | 5867.32 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30538503.29 | 5867.32 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19334749.41 | 5867.32 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42794296.87 | 5867.32 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42794296.87 | 5867.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 40334985.22 | 3794.80 | 02-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56688621.75 | 2573.15 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108000E+09 | 6013.08 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8961100.27 | 2151.93 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23037451.36 | 3740.29 | 24-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411554E+09 | 8187.82 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648576E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411554E+09 | 8187.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5856542.95 | 16476.20 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5856542.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5856542.95 | 16476.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17496872.47 | 10351.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17366255.57 | 10351.71 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18153056.25 | 10351.71 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1320282.11 | 9068.53 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78122859.91 | 10351.71 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78122859.91 | 10351.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 31402573.62 | 6841.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33383661.71 | 6841.71 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19983390.06 | 6841.71 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 837824.80 | 1241.67 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7935575.79 | 6841.71 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120446E+09 | 6841.71 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120446E+09 | 6841.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49221602.86 | 10279.90 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43197632.92 | 10279.90 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26825915.37 | 10279.90 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12288082.88 | 10279.90 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190470E+09 | 10279.90 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190470E+09 | 10279.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 48153391.07 | 6785.78 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58326777.69 | 6785.78 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33901603.21 | 6785.78 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1487869.22 | 1167.02 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19440547.68 | 6785.78 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192184E+09 | 6785.78 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.192184E+09 | 6785.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115023E+09 | 5489.10 | 02-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173230E+09 | 4556.85 | 28-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213405E+09 | 8220.58 | 27-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38146598.86 | 3939.34 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71776510.39 | 6028.29 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703294E+09 | 10828.25 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.703294E+09 | 10828.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 85622008.43 | 29782.44 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36306375.67 | 29782.44 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12466194.37 | 29782.44 | 27-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12014295.36 | 29782.44 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200345E+09 | 29782.44 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200345E+09 | 29782.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142602E+09 | 13299.01 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205572E+09 | 13299.01 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152534E+09 | 13299.01 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 730465.17 | 1358.72 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26718560.33 | 9893.49 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74584892.07 | 13299.01 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414319E+09 | 13299.01 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414319E+09 | 13299.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150249E+09 | 8702.17 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185195E+09 | 8702.17 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98240343.47 | 8702.17 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 330193.50 | 839.43 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26964601.87 | 8702.17 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76644189.70 | 8702.17 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434095E+09 | 8702.17 | 04-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.971719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434095E+09 | 8702.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292733E+09 | 12293.38 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313128E+09 | 12303.51 | 13-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188859E+09 | 12281.32 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 384841.83 | 1020.09 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40985856.13 | 10345.44 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179061E+09 | 12224.06 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.859058E+09 | 12291.11 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.859058E+09 | 12303.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258365E+09 | 8648.53 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312709E+09 | 8648.53 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184811E+09 | 8648.53 | 27-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2926327.03 | 1962.90 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48081510.73 | 8648.53 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169333E+09 | 8648.53 | 24-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687428E+09 | 8648.53 | 04-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.687428E+09 | 8648.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.181073E+11 | 0.179949E+11 | 50264.78 | 31-JAN-16:50 | 50264.78 | 0.00 |
February | 0.00 | 0.00 | 0.397784E+10 | 0.351335E+10 | 23249.72 | 22-FEB-16:00 | 23249.72 | 0.00 |
March | 0.00 | 0.00 | 0.172502E+11 | 0.169034E+11 | 50195.89 | 20-MAR-14:30 | 50195.89 | 0.00 |
April | 0.00 | 0.00 | 0.485139E+11 | 0.484462E+11 | 68122.06 | 14-APR-16:00 | 68122.06 | 0.00 |
May | 0.00 | 0.00 | 0.642238E+11 | 0.642003E+11 | 71966.95 | 31-MAY-16:00 | 71966.95 | 0.00 |
June | 0.00 | 0.00 | 0.855376E+11 | 0.853488E+11 | 89602.67 | 29-JUN-06:03 | 89602.67 | 0.00 |
July | 0.00 | 0.00 | 0.879812E+11 | 0.818422E+11 | 127424.08 | 14-JUL-04:03 | 49746.60 | 0.00 |
August | 0.00 | 0.00 | 0.914391E+11 | 0.845726E+11 | 123279.07 | 01-AUG-04:02 | 64251.23 | 0.00 |
September | 0.00 | 0.00 | 0.798704E+11 | 0.726216E+11 | 119558.32 | 08-SEP-04:02 | 78171.18 | 0.00 |
October | 0.00 | 0.00 | 0.450636E+11 | 0.438459E+11 | 116303.35 | 03-OCT-06:03 | 60023.11 | 0.00 |
November | 0.00 | 0.00 | 0.202518E+11 | 0.190309E+11 | 57368.07 | 01-NOV-16:00 | 57368.07 | 0.00 |
December | 0.00 | 0.00 | 0.864412E+10 | 0.862336E+10 | 44068.80 | 22-DEC-16:20 | 44068.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.570861E+12 | 0.546944E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.397784E+10 | 0.351335E+10 | 23249.72 | 23249.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.914391E+11 | 0.853488E+11 | 127424.08 | 89602.67 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.152070E+11 | 0.150632E+11 | 42372.62 | 31-JAN-16:30 | 42372.62 | 0.00 |
February | 0.00 | 0.00 | 0.344055E+10 | 0.295037E+10 | 21108.89 | 22-FEB-16:00 | 21108.89 | 0.00 |
March | 0.00 | 0.00 | 0.150082E+11 | 0.145579E+11 | 45353.12 | 16-MAR-15:40 | 45353.12 | 0.00 |
April | 0.00 | 0.00 | 0.433961E+11 | 0.433309E+11 | 64002.80 | 14-APR-15:20 | 64002.80 | 0.00 |
May | 0.00 | 0.00 | 0.578625E+11 | 0.578395E+11 | 64356.86 | 18-MAY-15:20 | 64356.86 | 0.00 |
June | 0.00 | 0.00 | 0.779748E+11 | 0.778345E+11 | 78971.61 | 30-JUN-04:02 | 78971.61 | 0.00 |
July | 0.00 | 0.00 | 0.757754E+11 | 0.711318E+11 | 119133.04 | 14-JUL-05:03 | 47321.09 | 0.00 |
August | 0.00 | 0.00 | 0.772436E+11 | 0.722093E+11 | 115638.40 | 01-AUG-04:02 | 59892.29 | 0.00 |
September | 0.00 | 0.00 | 0.646001E+11 | 0.595240E+11 | 111939.20 | 05-SEP-06:03 | 45895.59 | 0.00 |
October | 0.00 | 0.00 | 0.361422E+11 | 0.350676E+11 | 79349.35 | 02-OCT-04:02 | 78851.33 | 0.00 |
November | 0.00 | 0.00 | 0.157454E+11 | 0.147097E+11 | 49567.05 | 01-NOV-15:30 | 49567.05 | 0.00 |
December | 0.00 | 0.00 | 0.697961E+10 | 0.694105E+10 | 35646.09 | 22-DEC-16:30 | 35646.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.489375E+12 | 0.471160E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.344055E+10 | 0.295037E+10 | 21108.89 | 21108.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.779748E+11 | 0.778345E+11 | 119133.04 | 78971.61 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147525E+11 | 0.145623E+11 | 46079.88 | 31-JAN-16:20 | 46079.88 | 0.00 |
February | 0.00 | 0.00 | 0.344179E+10 | 0.285690E+10 | 21018.01 | 22-FEB-16:00 | 21018.01 | 0.00 |
March | 0.00 | 0.00 | 0.155724E+11 | 0.149275E+11 | 51885.20 | 16-MAR-15:30 | 51885.20 | 0.00 |
April | 0.00 | 0.00 | 0.473984E+11 | 0.472824E+11 | 74909.51 | 14-APR-15:30 | 74909.51 | 0.00 |
May | 0.00 | 0.00 | 0.634163E+11 | 0.633689E+11 | 75068.60 | 18-MAY-15:30 | 75068.60 | 0.00 |
June | 0.00 | 0.00 | 0.868061E+11 | 0.866236E+11 | 90976.76 | 28-JUN-14:50 | 90976.76 | 0.00 |
July | 0.00 | 0.00 | 0.836019E+11 | 0.787038E+11 | 125880.07 | 24-JUL-04:02 | 82946.39 | 0.00 |
August | 0.00 | 0.00 | 0.837933E+11 | 0.785592E+11 | 131270.30 | 01-AUG-04:02 | 66213.10 | 0.00 |
September | 0.00 | 0.00 | 0.686463E+11 | 0.634333E+11 | 107345.79 | 08-SEP-05:03 | 62423.05 | 0.00 |
October | 0.00 | 0.00 | 0.372252E+11 | 0.360151E+11 | 84723.01 | 02-OCT-04:02 | 84419.87 | 0.00 |
November | 0.00 | 0.00 | 0.152604E+11 | 0.141725E+11 | 55521.32 | 01-NOV-15:30 | 55521.32 | 0.00 |
December | 0.00 | 0.00 | 0.664802E+10 | 0.658827E+10 | 37171.55 | 22-DEC-15:40 | 37171.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.526563E+12 | 0.507094E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.344179E+10 | 0.285690E+10 | 21018.01 | 21018.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.868061E+11 | 0.866236E+11 | 131270.30 | 90976.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1449.17 | 5285.75 | 23-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1444.09 | 5275.91 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1470.16 | 5124.10 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1260.42 | 4755.83 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1190.02 | 4364.77 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1119.68 | 3960.75 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 975.35 | 3690.37 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1094.97 | 3799.45 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1090.12 | 4117.29 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1196.48 | 4561.24 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1332.43 | 4952.66 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1365.29 | 5209.77 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1247.94 | ||||
Minimum of Months | 0.00 | 0.00 | 975.35 | 3690.37 | ||
Maximum of Months | 0.00 | 0.00 | 1470.16 | 5285.75 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269701E+10 | 0.37 | 4936.79 | 26-JAN-17:00 | 1.13 |
February | 0.183497E+10 | 0.32 | 4581.10 | 01-FEB-07:02 | 1.08 |
March | 0.260059E+10 | 0.37 | 5655.76 | 20-MAR-14:30 | 1.22 |
April | 0.467340E+10 | 0.51 | 8418.39 | 25-APR-16:00 | 1.56 |
May | 0.605579E+10 | 0.58 | 10004.75 | 08-MAY-16:00 | 1.75 |
June | 0.771904E+10 | 0.70 | 11994.12 | 26-JUN-12:06 | 1.96 |
July | 0.723446E+10 | 0.66 | 11994.12 | 03-JUL-12:06 | 1.97 |
August | 0.731736E+10 | 0.66 | 11994.12 | 01-AUG-04:02 | 1.94 |
September | 0.628527E+10 | 0.61 | 11994.12 | 05-SEP-06:03 | 1.94 |
October | 0.454980E+10 | 0.49 | 11994.12 | 02-OCT-04:02 | 1.94 |
November | 0.316955E+10 | 0.40 | 6394.59 | 15-NOV-16:40 | 1.32 |
December | 0.227044E+10 | 0.35 | 4985.72 | 05-DEC-07:01 | 1.14 |
Annual Sum or Average | 0.564077E+11 | 0.50 | |||
Minimum of Months | 0.183497E+10 | 0.32 | 4581.10 | 1.08 | |
Maximum of Months | 0.771904E+10 | 0.70 | 11994.12 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197937E+10 | 0.34 | 4171.98 | 27-JAN-16:50 | 1.08 |
February | 0.145615E+10 | 0.31 | 3015.36 | 22-FEB-16:30 | 0.89 |
March | 0.206797E+10 | 0.35 | 4780.52 | 16-MAR-15:30 | 1.16 |
April | 0.418337E+10 | 0.50 | 8435.63 | 24-APR-15:20 | 1.66 |
May | 0.536863E+10 | 0.57 | 8568.76 | 08-MAY-16:00 | 1.67 |
June | 0.730469E+10 | 0.70 | 11046.62 | 28-JUN-04:02 | 1.97 |
July | 0.653890E+10 | 0.64 | 11046.62 | 10-JUL-04:02 | 1.95 |
August | 0.666387E+10 | 0.64 | 11046.62 | 01-AUG-04:02 | 1.94 |
September | 0.521272E+10 | 0.56 | 11046.62 | 18-SEP-04:02 | 1.96 |
October | 0.336345E+10 | 0.43 | 11046.62 | 02-OCT-04:02 | 1.94 |
November | 0.213345E+10 | 0.35 | 5079.33 | 02-NOV-15:40 | 1.20 |
December | 0.166240E+10 | 0.32 | 3386.66 | 22-DEC-16:40 | 0.95 |
Annual Sum or Average | 0.479350E+11 | 0.48 | |||
Minimum of Months | 0.145615E+10 | 0.31 | 3015.36 | 0.89 | |
Maximum of Months | 0.730469E+10 | 0.70 | 11046.62 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.187563E+10 | 0.32 | 3658.57 | 27-JAN-16:30 | 0.91 |
February | 0.142331E+10 | 0.30 | 2611.71 | 22-FEB-16:30 | 0.75 |
March | 0.195537E+10 | 0.34 | 4563.35 | 16-MAR-15:30 | 1.02 |
April | 0.392204E+10 | 0.45 | 8453.34 | 14-APR-15:30 | 1.49 |
May | 0.506163E+10 | 0.51 | 8359.81 | 18-MAY-15:30 | 1.48 |
June | 0.720756E+10 | 0.64 | 11203.88 | 28-JUN-14:50 | 1.77 |
July | 0.630452E+10 | 0.58 | 11820.24 | 12-JUL-04:02 | 1.83 |
August | 0.641065E+10 | 0.58 | 10949.36 | 14-AUG-15:20 | 1.74 |
September | 0.487956E+10 | 0.50 | 10062.51 | 18-SEP-04:02 | 1.67 |
October | 0.304447E+10 | 0.39 | 10199.81 | 02-OCT-04:02 | 1.67 |
November | 0.192977E+10 | 0.33 | 4699.71 | 02-NOV-15:20 | 1.04 |
December | 0.162242E+10 | 0.31 | 3076.30 | 22-DEC-16:30 | 0.83 |
Annual Sum or Average | 0.456369E+11 | 0.44 | |||
Minimum of Months | 0.142331E+10 | 0.30 | 2611.71 | 0.75 | |
Maximum of Months | 0.720756E+10 | 0.64 | 11820.24 | 1.83 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.41 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.52 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.54 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.58 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.03 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.12 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.19 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.28 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.19 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.66 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.75 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.62 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.52 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.66 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.42 | 58.42 | 1449.17 | 5285.75 | 23-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.99 | 57.99 | 1444.09 | 5275.91 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.04 | 58.04 | 1470.16 | 5124.10 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.18 | 58.18 | 1260.42 | 4755.83 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.69 | 58.69 | 1190.02 | 4364.77 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.50 | 58.50 | 1119.68 | 3960.75 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.60 | 58.60 | 975.35 | 3690.37 | 03-JUL-11:17 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.63 | 58.63 | 1094.97 | 3799.45 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.57 | 58.57 | 1090.12 | 4117.29 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.78 | 57.78 | 1196.48 | 4561.24 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.27 | 58.27 | 1332.43 | 4952.66 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.12 | 58.12 | 1365.29 | 5209.77 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1247.94 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.78 | 57.78 | 975.35 | 3690.37 | ||
Maximum of Months | 0.00 | 0.00 | 58.69 | 58.69 | 1470.16 | 5285.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.761591E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.363674E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.757121E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167677E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.226071E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.323943E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.310883E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319665E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.267257E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.158254E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.818398E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.539566E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209779E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.363674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323943E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.573565E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.253391E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.585114E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.149362E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.203313E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.298681E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.271112E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.275447E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.218661E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123206E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.587611E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.434064E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178316E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.253391E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.298681E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.643946E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.352585E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.655172E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157840E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.216283E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.325420E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.291489E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292398E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.227277E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125575E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.614096E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.655242E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.192839E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.352585E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.325420E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.269701E+10 | 0.181073E+11 | 0.732458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183497E+10 | 0.397784E+10 | 0.803686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260059E+10 | 0.172502E+11 | 0.896841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467340E+10 | 0.485139E+11 | 0.137820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605579E+10 | 0.642238E+11 | 6526175.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771904E+10 | 0.855376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.723446E+10 | 0.879812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.731736E+10 | 0.914391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628527E+10 | 0.798704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454980E+10 | 0.450636E+11 | 0.271572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316955E+10 | 0.202518E+11 | 0.375821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227044E+10 | 0.864412E+10 | 0.107320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564077E+11 | 0.570861E+12 | 0.429792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183497E+10 | 0.397784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.771904E+10 | 0.914391E+11 | 0.107320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.197937E+10 | 0.152070E+11 | 0.192466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145615E+10 | 0.344055E+10 | 0.208963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206797E+10 | 0.150082E+11 | 0.206863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418337E+10 | 0.433961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.536863E+10 | 0.578625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730469E+10 | 0.779748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.653890E+10 | 0.757754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666387E+10 | 0.772436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521272E+10 | 0.646001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336345E+10 | 0.361422E+11 | 11286794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213345E+10 | 0.157454E+11 | 64021939.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166240E+10 | 0.697961E+10 | 0.992777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479350E+11 | 0.489375E+12 | 0.167638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145615E+10 | 0.344055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730469E+10 | 0.779748E+11 | 0.992777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.187563E+10 | 0.147525E+11 | 0.104459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142331E+10 | 0.344179E+10 | 0.122614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195537E+10 | 0.155724E+11 | 0.850316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392204E+10 | 0.473984E+11 | 4371827.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506163E+10 | 0.634163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.720756E+10 | 0.868061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.630452E+10 | 0.836019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.641065E+10 | 0.837933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.487956E+10 | 0.686463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304447E+10 | 0.372252E+11 | 0.180897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192977E+10 | 0.152604E+11 | 0.583414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162242E+10 | 0.664802E+10 | 0.329854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456369E+11 | 0.526563E+12 | 0.718827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142331E+10 | 0.344179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.720756E+10 | 0.868061E+11 | 0.329854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.269701E+10 | 0.00 | 0.00 | 0.00 | 0.418645E+10 | 0.732458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183497E+10 | 0.00 | 0.00 | 0.00 | 0.998090E+09 | 0.803686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260059E+10 | 0.00 | 0.00 | 0.00 | 0.407378E+10 | 0.896841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.467340E+10 | 0.00 | 0.00 | 0.00 | 0.119565E+11 | 0.137820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.605579E+10 | 0.00 | 0.00 | 0.00 | 0.165448E+11 | 6526175.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.771904E+10 | 0.00 | 0.00 | 0.00 | 0.246753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.723446E+10 | 0.00 | 0.00 | 0.00 | 0.238539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.731736E+10 | 0.00 | 0.00 | 0.00 | 0.246491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628527E+10 | 0.00 | 0.00 | 0.00 | 0.204405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454980E+10 | 0.00 | 0.00 | 0.00 | 0.110040E+11 | 0.271572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316955E+10 | 0.00 | 0.00 | 0.00 | 0.463860E+10 | 0.375821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227044E+10 | 0.00 | 0.00 | 0.00 | 0.205202E+10 | 0.107320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564077E+11 | 0.00 | 0.00 | 0.00 | 0.149073E+12 | 0.429792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.183497E+10 | 0.00 | 0.00 | 0.00 | 0.998090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.771904E+10 | 0.00 | 0.00 | 0.00 | 0.246753E+11 | 0.107320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.197937E+10 | 0.00 | 0.00 | 0.00 | 0.356381E+10 | 0.192466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145615E+10 | 0.00 | 0.00 | 0.00 | 0.868802E+09 | 0.208963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206797E+10 | 0.00 | 0.00 | 0.00 | 0.357631E+10 | 0.206863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418337E+10 | 0.00 | 0.00 | 0.00 | 0.107528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.536863E+10 | 0.00 | 0.00 | 0.00 | 0.149627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.730469E+10 | 0.00 | 0.00 | 0.00 | 0.225635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.653890E+10 | 0.00 | 0.00 | 0.00 | 0.205723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.666387E+10 | 0.00 | 0.00 | 0.00 | 0.208808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.521272E+10 | 0.00 | 0.00 | 0.00 | 0.166534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336345E+10 | 0.00 | 0.00 | 0.00 | 0.894590E+10 | 11286794.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213345E+10 | 0.00 | 0.00 | 0.00 | 0.367863E+10 | 64021939.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166240E+10 | 0.00 | 0.00 | 0.00 | 0.168546E+10 | 0.992777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.479350E+11 | 0.00 | 0.00 | 0.00 | 0.128704E+12 | 0.167638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145615E+10 | 0.00 | 0.00 | 0.00 | 0.868802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730469E+10 | 0.00 | 0.00 | 0.00 | 0.225635E+11 | 0.992777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.187563E+10 | 0.00 | 0.00 | 0.00 | 0.351923E+10 | 0.104459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142331E+10 | 0.00 | 0.00 | 0.00 | 0.876398E+09 | 0.122614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195537E+10 | 0.00 | 0.00 | 0.00 | 0.374604E+10 | 0.850316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.392204E+10 | 0.00 | 0.00 | 0.00 | 0.118576E+11 | 4371827.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.506163E+10 | 0.00 | 0.00 | 0.00 | 0.165667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.720756E+10 | 0.00 | 0.00 | 0.00 | 0.253344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.630452E+10 | 0.00 | 0.00 | 0.00 | 0.228444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.641065E+10 | 0.00 | 0.00 | 0.00 | 0.228292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.487956E+10 | 0.00 | 0.00 | 0.00 | 0.178481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304447E+10 | 0.00 | 0.00 | 0.00 | 0.933213E+10 | 0.180897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192977E+10 | 0.00 | 0.00 | 0.00 | 0.362778E+10 | 0.583414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162242E+10 | 0.00 | 0.00 | 0.00 | 0.163147E+10 | 0.329854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456369E+11 | 0.00 | 0.00 | 0.00 | 0.140013E+12 | 0.718827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142331E+10 | 0.00 | 0.00 | 0.00 | 0.876398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.720756E+10 | 0.00 | 0.00 | 0.00 | 0.253344E+11 | 0.329854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.920034E+09 | 2944268.32 | 0.00 | 36412011.53 | 8174549.50 | 0.00 | 0.129400E+11 | 0.00 | 0.91 |
February | 0.695335E+09 | 0.00 | 0.00 | 34298410.39 | 1384822.72 | 0.00 | 0.156458E+11 | 0.00 | 0.84 |
March | 0.554530E+09 | 14310096.35 | 0.00 | 40561756.28 | 608486.12 | 0.00 | 0.141391E+11 | 0.00 | 0.94 |
April | 0.317734E+09 | 0.639130E+09 | 0.00 | 27552186.12 | 55714107.14 | 0.00 | 0.543685E+10 | 0.00 | 0.68 |
May | 0.175986E+09 | 0.130304E+10 | 0.00 | 18161405.82 | 41597209.91 | 0.00 | 0.239537E+10 | 0.00 | 0.52 |
June | 0.130303E+09 | 0.341402E+10 | 0.00 | 5452309.22 | 88605207.46 | 0.00 | 0.622614E+09 | 0.00 | 0.36 |
July | 72069374.44 | 0.468676E+10 | 0.00 | 1683840.25 | 0.195193E+09 | 0.00 | 0.219758E+09 | 0.00 | 0.33 |
August | 32347076.93 | 0.471959E+10 | 0.00 | 3183847.54 | 0.125376E+09 | 0.00 | 0.273680E+09 | 0.00 | 0.41 |
September | 51080236.59 | 0.328893E+10 | 0.00 | 9848847.02 | 0.591787E+09 | 0.00 | 0.868770E+09 | 0.00 | 0.50 |
October | 0.395397E+09 | 0.718469E+09 | 0.00 | 33349335.01 | 46024968.48 | 0.00 | 0.941926E+10 | 0.00 | 0.84 |
November | 0.778078E+09 | 19843756.48 | 0.00 | 42992941.69 | 5437087.63 | 0.00 | 0.144671E+11 | 0.00 | 1.00 |
December | 0.897088E+09 | 1038216.47 | 0.00 | 37937721.20 | 292864.83 | 0.00 | 0.156097E+11 | 0.00 | 0.81 |
Annual Sum or Average | 0.501998E+10 | 0.188081E+11 | 0.00 | 0.291435E+09 | 0.116019E+10 | 0.00 | 0.920380E+11 | 0.00 | 0.68 |
Minimum of Months | 32347076.93 | 0.00 | 0.00 | 1683840.25 | 292864.83 | 0.00 | 0.219758E+09 | 0.00 | 0.33 |
Maximum of Months | 0.920034E+09 | 0.471959E+10 | 0.00 | 42992941.69 | 0.591787E+09 | 0.00 | 0.156458E+11 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.324290E+10 | 78864.18 | 0.00 | 12962863.87 | 15497997.73 | 661616.19 | 0.509050E+10 | 0.00 | 0.55 |
February | 0.430814E+10 | 0.00 | 0.00 | 9587710.12 | 3157972.41 | 0.00 | 0.585181E+10 | 0.00 | 0.53 |
March | 0.308752E+10 | 2628148.83 | 0.00 | 16420074.81 | 729830.14 | 0.00 | 0.622144E+10 | 0.00 | 0.59 |
April | 0.725916E+09 | 0.408949E+09 | 0.00 | 17274097.19 | 93680530.28 | 0.00 | 0.321752E+10 | 0.00 | 0.48 |
May | 0.368861E+09 | 0.945275E+09 | 0.00 | 12630943.57 | 48944210.88 | 0.00 | 0.148582E+10 | 0.00 | 0.39 |
June | 0.104986E+09 | 0.289092E+10 | 0.00 | 3341262.04 | 91243560.75 | 0.00 | 0.445077E+09 | 0.00 | 0.30 |
July | 76712623.64 | 0.376177E+10 | 0.00 | 978070.56 | 0.188034E+09 | 0.00 | 0.125779E+09 | 0.00 | 0.28 |
August | 45386500.95 | 0.376302E+10 | 0.00 | 1364449.43 | 0.119604E+09 | 0.00 | 0.152387E+09 | 0.00 | 0.34 |
September | 94312546.94 | 0.257565E+10 | 0.00 | 6627286.60 | 0.262927E+09 | 0.00 | 0.472868E+09 | 0.00 | 0.38 |
October | 0.993202E+09 | 0.582328E+09 | 0.00 | 17313651.28 | 43381400.69 | 0.00 | 0.492942E+10 | 0.00 | 0.54 |
November | 0.256192E+10 | 9254301.61 | 0.00 | 17838898.28 | 18862294.32 | 0.00 | 0.644245E+10 | 0.00 | 0.60 |
December | 0.522993E+10 | 113314.22 | 0.00 | 7682736.92 | 2577325.43 | 0.00 | 0.449650E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.208398E+11 | 0.149400E+11 | 0.00 | 0.124022E+09 | 0.888641E+09 | 661616.19 | 0.389316E+11 | 0.00 | 0.46 |
Minimum of Months | 45386500.95 | 0.00 | 0.00 | 978070.56 | 729830.14 | 0.00 | 0.125779E+09 | 0.00 | 0.28 |
Maximum of Months | 0.522993E+10 | 0.376302E+10 | 0.00 | 17838898.28 | 0.262927E+09 | 661616.19 | 0.644245E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.450735E+10 | 0.00 | 0.00 | 7334258.84 | 167084.60 | 35051750.38 | 0.297426E+10 | 0.00 | 0.55 |
February | 0.575267E+10 | 0.00 | 0.00 | 4643447.44 | 3861372.12 | 12784438.02 | 0.365972E+10 | 0.00 | 0.51 |
March | 0.428527E+10 | 1040584.67 | 0.00 | 10883559.69 | 1575545.96 | 2037660.39 | 0.423623E+10 | 0.00 | 0.59 |
April | 0.108941E+10 | 0.268728E+09 | 0.00 | 16121360.33 | 73633426.43 | 0.00 | 0.218498E+10 | 0.00 | 0.46 |
May | 0.518062E+09 | 0.679997E+09 | 0.00 | 13432729.38 | 45179477.28 | 0.00 | 0.806655E+09 | 0.00 | 0.36 |
June | 0.157140E+09 | 0.256203E+10 | 0.00 | 2453547.28 | 90553286.56 | 0.00 | 0.245255E+09 | 0.00 | 0.29 |
July | 72748765.46 | 0.349894E+10 | 0.00 | 800028.14 | 0.261994E+09 | 0.00 | 68438513.43 | 0.00 | 0.27 |
August | 66422634.52 | 0.355990E+10 | 0.00 | 827261.63 | 0.146457E+09 | 0.00 | 54092673.17 | 0.00 | 0.32 |
September | 0.111214E+09 | 0.238100E+10 | 0.00 | 5630940.92 | 0.320907E+09 | 0.00 | 0.229825E+09 | 0.00 | 0.35 |
October | 0.168076E+10 | 0.497693E+09 | 0.00 | 13087993.02 | 72297875.41 | 0.00 | 0.321361E+10 | 0.00 | 0.50 |
November | 0.388586E+10 | 11804646.66 | 0.00 | 11166032.72 | 30809571.01 | 1146553.71 | 0.409210E+10 | 0.00 | 0.57 |
December | 0.667141E+10 | 0.00 | 0.00 | 2958770.69 | 4598709.11 | 72822663.59 | 0.211607E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.287983E+11 | 0.134611E+11 | 0.00 | 89339930.08 | 0.105203E+10 | 0.123843E+09 | 0.238812E+11 | 0.00 | 0.44 |
Minimum of Months | 66422634.52 | 0.00 | 0.00 | 800028.14 | 167084.60 | 0.00 | 54092673.17 | 0.00 | 0.27 |
Maximum of Months | 0.667141E+10 | 0.355990E+10 | 0.00 | 16121360.33 | 0.320907E+09 | 72822663.59 | 0.423623E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125471E+10 | 0.00 | 0.00 | 663376.49 | 37043.64 | 0.123972E+09 | 0.233172E+09 | 0.00 | 0.55 |
February | 0.169264E+10 | 0.00 | 0.00 | 193398.38 | 856088.96 | 0.109352E+09 | 0.208353E+09 | 0.00 | 0.52 |
March | 0.127089E+10 | 265790.18 | 0.00 | 1714442.09 | 349307.82 | 81906294.57 | 0.476758E+09 | 0.00 | 0.60 |
April | 0.338838E+09 | 89428609.81 | 0.00 | 3502985.63 | 13885617.66 | 0.00 | 0.351686E+09 | 0.00 | 0.51 |
May | 0.151569E+09 | 0.243536E+09 | 0.00 | 3276345.94 | 10016556.36 | 0.00 | 0.145009E+09 | 0.00 | 0.46 |
June | 45513232.16 | 0.101744E+10 | 0.00 | 643920.11 | 17312343.65 | 0.00 | 48620659.63 | 0.00 | 0.47 |
July | 16988436.71 | 0.122888E+10 | 0.00 | 207693.54 | 54419607.67 | 0.00 | 15144981.81 | 0.00 | 0.42 |
August | 18667853.52 | 0.112980E+10 | 0.00 | 177187.62 | 33871157.25 | 0.00 | 7290701.44 | 0.00 | 0.45 |
September | 40785636.21 | 0.716723E+09 | 0.00 | 1387224.85 | 75071880.37 | 0.00 | 41664607.43 | 0.00 | 0.45 |
October | 0.637137E+09 | 0.138421E+09 | 0.00 | 2219918.90 | 15245403.82 | 19977595.57 | 0.349334E+09 | 0.00 | 0.51 |
November | 0.115461E+10 | 1356412.66 | 0.00 | 1322891.25 | 8079436.59 | 71369136.56 | 0.414226E+09 | 0.00 | 0.56 |
December | 0.152449E+10 | 0.00 | 0.00 | 124364.65 | 1019560.91 | 0.353371E+09 | 68982279.59 | 0.00 | 0.49 |
Annual Sum or Average | 0.814684E+10 | 0.456586E+10 | 0.00 | 15433749.46 | 0.230164E+09 | 0.759949E+09 | 0.236024E+10 | 0.00 | 0.50 |
Minimum of Months | 16988436.71 | 0.00 | 0.00 | 124364.65 | 37043.64 | 0.00 | 7290701.44 | 0.00 | 0.42 |
Maximum of Months | 0.169264E+10 | 0.122888E+10 | 0.00 | 3502985.63 | 75071880.37 | 0.353371E+09 | 0.476758E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.774519E+09 | 0.00 | 0.00 | 1570671.28 | 32909.44 | 56694073.06 | 0.673525E+09 | 0.00 | 0.82 |
February | 0.106760E+10 | 0.00 | 0.00 | 863480.41 | 760546.43 | 61367658.33 | 0.714195E+09 | 0.00 | 0.75 |
March | 0.778815E+09 | 639201.25 | 0.00 | 2813226.06 | 130394.45 | 42606276.01 | 0.103194E+10 | 0.00 | 0.96 |
April | 0.195324E+09 | 86443739.23 | 0.00 | 5388298.89 | 11213439.91 | 0.00 | 0.749895E+09 | 0.00 | 1.01 |
May | 0.103567E+09 | 0.194592E+09 | 0.00 | 4728292.26 | 8245603.25 | 0.00 | 0.304694E+09 | 0.00 | 0.84 |
June | 36665900.48 | 0.847974E+09 | 0.00 | 800343.40 | 13801165.29 | 0.00 | 57349634.46 | 0.00 | 0.69 |
July | 14918382.32 | 0.110135E+10 | 0.00 | 241208.67 | 51176413.76 | 0.00 | 19004439.92 | 0.00 | 0.60 |
August | 15877209.94 | 0.106663E+10 | 0.00 | 171872.10 | 31592391.86 | 0.00 | 9425290.92 | 0.00 | 0.67 |
September | 32156947.83 | 0.683401E+09 | 0.00 | 1292595.73 | 57630686.62 | 0.00 | 41015324.51 | 0.00 | 0.67 |
October | 0.374806E+09 | 0.131884E+09 | 0.00 | 3165294.30 | 13405460.38 | 10191604.02 | 0.723773E+09 | 0.00 | 0.87 |
November | 0.792919E+09 | 737011.96 | 0.00 | 2128790.09 | 7613066.64 | 23394371.42 | 0.740747E+09 | 0.00 | 0.85 |
December | 0.131650E+10 | 0.00 | 0.00 | 402422.43 | 905774.34 | 0.178773E+09 | 0.233214E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.550367E+10 | 0.411365E+10 | 0.00 | 23566495.61 | 0.196508E+09 | 0.373027E+09 | 0.529878E+10 | 0.00 | 0.79 |
Minimum of Months | 14918382.32 | 0.00 | 0.00 | 171872.10 | 32909.44 | 0.00 | 9425290.92 | 0.00 | 0.60 |
Maximum of Months | 0.131650E+10 | 0.110135E+10 | 0.00 | 5388298.89 | 57630686.62 | 0.178773E+09 | 0.103194E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.662894E+09 | 160786.05 | 0.00 | 10355472.63 | 0.00 | 52249117.10 | 0.308158E+10 | 0.00 | 1.49 |
February | 0.978153E+09 | 0.00 | 0.00 | 5565530.59 | 944392.58 | 75509094.03 | 0.303036E+10 | 0.00 | 1.01 |
March | 0.877739E+09 | 751410.65 | 0.00 | 6076770.01 | 221752.73 | 70888147.59 | 0.195740E+10 | 0.00 | 1.00 |
April | 0.356061E+09 | 0.141144E+09 | 0.00 | 5489562.02 | 14179167.15 | 270436.16 | 0.564593E+09 | 0.00 | 0.71 |
May | 0.201756E+09 | 0.266324E+09 | 0.00 | 3379790.76 | 11311233.92 | 0.00 | 0.117488E+09 | 0.00 | 0.50 |
June | 61426047.32 | 0.988191E+09 | 0.00 | 456188.62 | 19753505.43 | 0.00 | 30036979.00 | 0.00 | 0.44 |
July | 21115043.20 | 0.122775E+10 | 0.00 | 171209.60 | 67489521.45 | 0.00 | 10881615.31 | 0.00 | 0.42 |
August | 22659880.71 | 0.129462E+10 | 0.00 | 168388.35 | 37031353.87 | 0.00 | 5465582.22 | 0.00 | 0.51 |
September | 44584093.40 | 0.972999E+09 | 0.00 | 2010502.11 | 76352994.79 | 0.00 | 57277099.01 | 0.00 | 0.58 |
October | 0.409011E+09 | 0.235274E+09 | 0.00 | 7886684.56 | 13557209.42 | 9137830.47 | 0.159833E+10 | 0.00 | 1.03 |
November | 0.679803E+09 | 3061382.73 | 0.00 | 9247745.52 | 7585767.54 | 23320595.03 | 0.299556E+10 | 0.00 | 1.34 |
December | 0.864568E+09 | 403882.95 | 0.00 | 7635247.26 | 861023.22 | 0.150396E+09 | 0.307415E+10 | 0.00 | 1.14 |
Annual Sum or Average | 0.517977E+10 | 0.513068E+10 | 0.00 | 58443092.02 | 0.249288E+09 | 0.381771E+09 | 0.165231E+11 | 0.00 | 0.85 |
Minimum of Months | 21115043.20 | 0.00 | 0.00 | 168388.35 | 0.00 | 0.00 | 5465582.22 | 0.00 | 0.42 |
Maximum of Months | 0.978153E+09 | 0.129462E+10 | 0.00 | 10355472.63 | 76352994.79 | 0.150396E+09 | 0.308158E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114854E+10 | 77195.29 | 0.00 | 2029824.74 | 0.00 | 0.109787E+09 | 0.570440E+09 | 0.00 | 1.06 |
February | 0.145776E+10 | 0.00 | 0.00 | 1180295.13 | 863075.23 | 0.109272E+09 | 0.705286E+09 | 0.00 | 0.93 |
March | 0.121632E+10 | 268785.87 | 0.00 | 2442397.99 | 313992.54 | 84449479.79 | 0.710059E+09 | 0.00 | 1.08 |
April | 0.362180E+09 | 0.114642E+09 | 0.00 | 3912462.06 | 7439550.66 | 247150.13 | 0.369766E+09 | 0.00 | 0.88 |
May | 0.194616E+09 | 0.271870E+09 | 0.00 | 2357065.90 | 4786022.06 | 0.00 | 75265387.15 | 0.00 | 0.68 |
June | 59179351.59 | 0.923328E+09 | 0.00 | 258705.71 | 14550549.08 | 0.00 | 21928467.34 | 0.00 | 0.63 |
July | 19852673.08 | 0.959155E+09 | 0.00 | 104199.71 | 60143702.89 | 0.00 | 8740750.55 | 0.00 | 0.53 |
August | 22032244.48 | 0.900308E+09 | 0.00 | 119937.42 | 46377360.18 | 0.00 | 3376670.87 | 0.00 | 0.60 |
September | 43775358.24 | 0.580580E+09 | 0.00 | 1188036.53 | 83206258.94 | 0.00 | 33417569.38 | 0.00 | 0.60 |
October | 0.612599E+09 | 0.109694E+09 | 0.00 | 2951018.23 | 22912316.06 | 18420564.15 | 0.492118E+09 | 0.00 | 0.87 |
November | 0.109809E+10 | 1276682.69 | 0.00 | 2360059.91 | 8355943.40 | 67875055.55 | 0.710996E+09 | 0.00 | 1.04 |
December | 0.130477E+10 | 48691.59 | 0.00 | 967899.52 | 979189.64 | 0.303618E+09 | 0.483054E+09 | 0.00 | 0.85 |
Annual Sum or Average | 0.753971E+10 | 0.386125E+10 | 0.00 | 19871902.84 | 0.249928E+09 | 0.693670E+09 | 0.418445E+10 | 0.00 | 0.81 |
Minimum of Months | 19852673.08 | 0.00 | 0.00 | 104199.71 | 0.00 | 0.00 | 3376670.87 | 0.00 | 0.53 |
Maximum of Months | 0.145776E+10 | 0.959155E+09 | 0.00 | 3912462.06 | 83206258.94 | 0.303618E+09 | 0.710996E+09 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152213E+10 | 109388.07 | 0.00 | 415199.88 | 2013605.05 | 19189722.08 | 0.162527E+09 | 0.00 | 0.52 |
February | 0.198435E+10 | 0.00 | 0.00 | 25118.77 | 292672.91 | 22965109.39 | 45040179.05 | 0.00 | 0.50 |
March | 0.155263E+10 | 1502750.59 | 0.00 | 664260.16 | 360225.64 | 24114764.49 | 0.184913E+09 | 0.00 | 0.52 |
April | 0.381756E+09 | 0.107278E+09 | 0.00 | 1971989.86 | 16438375.99 | 0.00 | 0.277762E+09 | 0.00 | 0.42 |
May | 0.167573E+09 | 0.273164E+09 | 0.00 | 1608177.67 | 8954755.41 | 0.00 | 0.153947E+09 | 0.00 | 0.37 |
June | 59170855.64 | 0.938869E+09 | 0.00 | 545427.17 | 21472250.57 | 0.00 | 63046731.35 | 0.00 | 0.39 |
July | 28307097.83 | 0.121263E+10 | 0.00 | 203073.51 | 53573488.94 | 0.00 | 23298970.33 | 0.00 | 0.38 |
August | 19370390.11 | 0.116694E+10 | 0.00 | 305654.38 | 32936623.90 | 0.00 | 28342691.75 | 0.00 | 0.43 |
September | 33842654.69 | 0.786661E+09 | 0.00 | 1474212.80 | 0.134993E+09 | 0.00 | 0.107253E+09 | 0.00 | 0.48 |
October | 0.517749E+09 | 0.154406E+09 | 0.00 | 2616186.78 | 10664743.83 | 0.00 | 0.626797E+09 | 0.00 | 0.54 |
November | 0.116198E+10 | 1192067.78 | 0.00 | 2162590.51 | 3247628.71 | 197092.64 | 0.658767E+09 | 0.00 | 0.56 |
December | 0.195363E+10 | 0.00 | 0.00 | 167777.63 | 201286.95 | 42439261.48 | 0.120400E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.938249E+10 | 0.464276E+10 | 0.00 | 12159669.13 | 0.285149E+09 | 0.108906E+09 | 0.245210E+10 | 0.00 | 0.46 |
Minimum of Months | 19370390.11 | 0.00 | 0.00 | 25118.77 | 201286.95 | 0.00 | 23298970.33 | 0.00 | 0.37 |
Maximum of Months | 0.198435E+10 | 0.121263E+10 | 0.00 | 2616186.78 | 0.134993E+09 | 42439261.48 | 0.658767E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.842398E+09 | 127493.65 | 0.00 | 1941264.67 | 1692117.20 | 6790981.42 | 0.749364E+09 | 0.00 | 0.77 |
February | 0.109501E+10 | 0.00 | 0.00 | 908524.50 | 246553.93 | 6037890.09 | 0.707034E+09 | 0.00 | 0.69 |
March | 0.868514E+09 | 1654019.37 | 0.00 | 2155460.81 | 108334.91 | 4605895.83 | 0.801679E+09 | 0.00 | 0.79 |
April | 0.179905E+09 | 0.119764E+09 | 0.00 | 4168431.21 | 10119875.15 | 0.00 | 0.749574E+09 | 0.00 | 0.90 |
May | 0.104900E+09 | 0.252789E+09 | 0.00 | 3082827.68 | 7119052.78 | 0.00 | 0.344399E+09 | 0.00 | 0.75 |
June | 37277741.56 | 0.828040E+09 | 0.00 | 751406.27 | 13614864.93 | 0.00 | 84817070.46 | 0.00 | 0.60 |
July | 17773632.16 | 0.108940E+10 | 0.00 | 273626.10 | 42139556.30 | 0.00 | 34109123.73 | 0.00 | 0.56 |
August | 13357568.67 | 0.108554E+10 | 0.00 | 363168.81 | 22861108.81 | 0.00 | 34068612.88 | 0.00 | 0.64 |
September | 28464371.78 | 0.727343E+09 | 0.00 | 1438487.24 | 97436139.43 | 0.00 | 0.109395E+09 | 0.00 | 0.71 |
October | 0.273704E+09 | 0.142006E+09 | 0.00 | 4008028.64 | 8018846.08 | 0.00 | 0.110210E+10 | 0.00 | 0.97 |
November | 0.655740E+09 | 1013336.44 | 0.00 | 3515136.34 | 2735872.01 | 0.00 | 0.119047E+10 | 0.00 | 0.90 |
December | 0.125210E+10 | 38153.57 | 0.00 | 1029209.77 | 131414.87 | 7595363.04 | 0.596646E+09 | 0.00 | 0.67 |
Annual Sum or Average | 0.536915E+10 | 0.424772E+10 | 0.00 | 23635572.03 | 0.206224E+09 | 25030130.38 | 0.650365E+10 | 0.00 | 0.75 |
Minimum of Months | 13357568.67 | 0.00 | 0.00 | 273626.10 | 108334.91 | 0.00 | 34068612.88 | 0.00 | 0.56 |
Maximum of Months | 0.125210E+10 | 0.108940E+10 | 0.00 | 4168431.21 | 97436139.43 | 7595363.04 | 0.119047E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.576344E+09 | 2698727.28 | 0.00 | 9364927.16 | 1142897.39 | 0.290276E+09 | 0.244857E+10 | 0.00 | 1.26 |
February | 0.128406E+10 | 0.00 | 0.00 | 2055210.62 | 291732.31 | 0.336386E+09 | 0.123687E+10 | 0.00 | 0.70 |
March | 0.109529E+10 | 3800145.65 | 0.00 | 3140453.13 | 128186.13 | 0.362973E+09 | 0.749475E+09 | 0.00 | 0.71 |
April | 0.357267E+09 | 0.233925E+09 | 0.00 | 3427178.87 | 11976410.66 | 64377786.40 | 0.340153E+09 | 0.00 | 0.61 |
May | 0.224658E+09 | 0.415513E+09 | 0.00 | 1664949.40 | 8969753.97 | 4663691.41 | 82895103.18 | 0.00 | 0.47 |
June | 88322034.97 | 0.123088E+10 | 0.00 | 355342.26 | 21854285.56 | 0.00 | 21229832.83 | 0.00 | 0.47 |
July | 30033075.46 | 0.155599E+10 | 0.00 | 168989.79 | 52491649.58 | 0.00 | 17043570.02 | 0.00 | 0.46 |
August | 23956268.59 | 0.168809E+10 | 0.00 | 262485.98 | 34399048.71 | 0.00 | 19844218.44 | 0.00 | 0.56 |
September | 49661414.27 | 0.123103E+10 | 0.00 | 2033466.07 | 0.117139E+09 | 0.00 | 0.101573E+09 | 0.00 | 0.65 |
October | 0.362209E+09 | 0.289093E+09 | 0.00 | 7292825.24 | 7556056.85 | 0.126256E+09 | 0.145478E+10 | 0.00 | 1.04 |
November | 0.513695E+09 | 2399445.01 | 0.00 | 9706324.54 | 3230100.29 | 0.168901E+09 | 0.277943E+10 | 0.00 | 1.22 |
December | 0.966347E+09 | 225401.71 | 0.00 | 6567006.81 | 93799.16 | 0.367072E+09 | 0.236742E+10 | 0.00 | 1.01 |
Annual Sum or Average | 0.557185E+10 | 0.665364E+10 | 0.00 | 46039159.87 | 0.259272E+09 | 0.172091E+10 | 0.116193E+11 | 0.00 | 0.76 |
Minimum of Months | 23956268.59 | 0.00 | 0.00 | 168989.79 | 93799.16 | 0.00 | 17043570.02 | 0.00 | 0.46 |
Maximum of Months | 0.128406E+10 | 0.168809E+10 | 0.00 | 9706324.54 | 0.117139E+09 | 0.367072E+09 | 0.277943E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121138E+10 | 561453.06 | 0.00 | 1776088.99 | 1555546.93 | 7575932.90 | 0.445972E+09 | 0.00 | 0.86 |
February | 0.150170E+10 | 0.00 | 0.00 | 821831.50 | 261221.86 | 12651748.99 | 0.462254E+09 | 0.00 | 0.77 |
March | 0.124185E+10 | 2038608.99 | 0.00 | 1496930.48 | 0.00 | 6900826.09 | 0.411498E+09 | 0.00 | 0.82 |
April | 0.301666E+09 | 0.152501E+09 | 0.00 | 2473889.61 | 6767507.88 | 0.00 | 0.344803E+09 | 0.00 | 0.73 |
May | 0.149200E+09 | 0.326204E+09 | 0.00 | 1248006.97 | 2712008.14 | 0.00 | 0.127865E+09 | 0.00 | 0.57 |
June | 49200450.65 | 0.909383E+09 | 0.00 | 387370.50 | 13873455.67 | 0.00 | 50216330.04 | 0.00 | 0.55 |
July | 22695282.10 | 0.979219E+09 | 0.00 | 157038.95 | 44812477.77 | 0.00 | 19734853.06 | 0.00 | 0.48 |
August | 12675942.38 | 0.991440E+09 | 0.00 | 245422.94 | 21766908.12 | 0.00 | 27612742.75 | 0.00 | 0.56 |
September | 27916583.16 | 0.669899E+09 | 0.00 | 1132751.69 | 0.113351E+09 | 0.00 | 83969304.72 | 0.00 | 0.62 |
October | 0.392928E+09 | 0.134323E+09 | 0.00 | 3143005.49 | 8690726.67 | 0.00 | 0.727748E+09 | 0.00 | 0.84 |
November | 0.827551E+09 | 1667959.36 | 0.00 | 3322234.49 | 2884987.66 | 0.00 | 0.101721E+10 | 0.00 | 0.94 |
December | 0.149524E+10 | 17307.86 | 0.00 | 1136594.32 | 162348.50 | 25864156.17 | 0.512709E+09 | 0.00 | 0.76 |
Annual Sum or Average | 0.723400E+10 | 0.416725E+10 | 0.00 | 17341165.92 | 0.216839E+09 | 52992664.16 | 0.423159E+10 | 0.00 | 0.71 |
Minimum of Months | 12675942.38 | 0.00 | 0.00 | 157038.95 | 0.00 | 0.00 | 19734853.06 | 0.00 | 0.48 |
Maximum of Months | 0.150170E+10 | 0.991440E+09 | 0.00 | 3322234.49 | 0.113351E+09 | 25864156.17 | 0.101721E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130637E+10 | 15801.67 | 0.00 | 904794.25 | 3270126.71 | 19082706.89 | 0.279399E+09 | 0.00 | 0.50 |
February | 0.165332E+10 | 0.00 | 0.00 | 340511.29 | 666342.20 | 15566509.94 | 0.302837E+09 | 0.00 | 0.49 |
March | 0.121861E+10 | 670871.95 | 0.00 | 2012533.94 | 153996.48 | 16327374.40 | 0.566801E+09 | 0.00 | 0.55 |
April | 0.325339E+09 | 0.141909E+09 | 0.00 | 2984515.40 | 13029667.57 | 0.00 | 0.405024E+09 | 0.00 | 0.50 |
May | 0.137985E+09 | 0.345706E+09 | 0.00 | 2671771.52 | 10398038.31 | 0.00 | 0.231475E+09 | 0.00 | 0.49 |
June | 35729408.23 | 0.118858E+10 | 0.00 | 760988.60 | 16489176.71 | 0.00 | 91013232.28 | 0.00 | 0.49 |
July | 18793910.83 | 0.134496E+10 | 0.00 | 212039.88 | 42199606.03 | 0.00 | 26446577.81 | 0.00 | 0.44 |
August | 20392652.47 | 0.123158E+10 | 0.00 | 231106.14 | 28904519.14 | 0.00 | 18453925.53 | 0.00 | 0.48 |
September | 40335831.50 | 0.801475E+09 | 0.00 | 1410949.78 | 58917972.42 | 0.00 | 72884743.19 | 0.00 | 0.47 |
October | 0.592030E+09 | 0.159407E+09 | 0.00 | 2230180.92 | 9570500.99 | 0.00 | 0.452731E+09 | 0.00 | 0.50 |
November | 0.114707E+10 | 1404215.76 | 0.00 | 1829285.44 | 4534834.16 | 6162541.67 | 0.520454E+09 | 0.00 | 0.52 |
December | 0.174056E+10 | 0.00 | 0.00 | 188857.64 | 567733.51 | 0.119720E+09 | 0.104060E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.823653E+10 | 0.521570E+10 | 0.00 | 15777534.80 | 0.188703E+09 | 0.176859E+09 | 0.307158E+10 | 0.00 | 0.49 |
Minimum of Months | 18793910.83 | 0.00 | 0.00 | 188857.64 | 153996.48 | 0.00 | 18453925.53 | 0.00 | 0.44 |
Maximum of Months | 0.174056E+10 | 0.134496E+10 | 0.00 | 2984515.40 | 58917972.42 | 0.119720E+09 | 0.566801E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.844750E+09 | 59321.72 | 0.00 | 1996118.09 | 2998249.54 | 12713964.39 | 0.814286E+09 | 0.00 | 0.80 |
February | 0.111441E+10 | 0.00 | 0.00 | 1190024.26 | 619915.98 | 11460521.20 | 0.852435E+09 | 0.00 | 0.76 |
March | 0.830961E+09 | 515464.72 | 0.00 | 3116222.98 | 143267.04 | 9570743.16 | 0.113376E+10 | 0.00 | 0.94 |
April | 0.202425E+09 | 0.129513E+09 | 0.00 | 5018284.23 | 11725952.23 | 0.00 | 0.874286E+09 | 0.00 | 1.03 |
May | 0.114342E+09 | 0.275315E+09 | 0.00 | 3999326.53 | 9195590.51 | 0.00 | 0.412147E+09 | 0.00 | 0.89 |
June | 34060229.63 | 0.964013E+09 | 0.00 | 858975.99 | 15612652.57 | 0.00 | 94675775.44 | 0.00 | 0.72 |
July | 16331041.61 | 0.117003E+10 | 0.00 | 253057.31 | 45360617.53 | 0.00 | 31413109.16 | 0.00 | 0.63 |
August | 20289944.86 | 0.111296E+10 | 0.00 | 242234.01 | 29588903.20 | 0.00 | 19943693.34 | 0.00 | 0.69 |
September | 38386268.49 | 0.724833E+09 | 0.00 | 1344511.25 | 50288712.96 | 0.00 | 74544063.14 | 0.00 | 0.70 |
October | 0.397759E+09 | 0.141453E+09 | 0.00 | 3233850.48 | 9366638.85 | 192258.43 | 0.872888E+09 | 0.00 | 0.90 |
November | 0.829843E+09 | 1050420.49 | 0.00 | 2625701.40 | 4337994.95 | 1742113.56 | 0.906726E+09 | 0.00 | 0.85 |
December | 0.141908E+10 | 0.00 | 0.00 | 683869.64 | 528177.67 | 66109661.17 | 0.384273E+09 | 0.00 | 0.69 |
Annual Sum or Average | 0.586264E+10 | 0.451974E+10 | 0.00 | 24562176.18 | 0.179767E+09 | 0.101789E+09 | 0.647138E+10 | 0.00 | 0.80 |
Minimum of Months | 16331041.61 | 0.00 | 0.00 | 242234.01 | 143267.04 | 0.00 | 19943693.34 | 0.00 | 0.63 |
Maximum of Months | 0.141908E+10 | 0.117003E+10 | 0.00 | 5018284.23 | 50288712.96 | 66109661.17 | 0.113376E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.641646E+09 | 4603996.18 | 0.00 | 10790105.32 | 2263001.47 | 10492378.27 | 0.304678E+10 | 0.00 | 1.37 |
February | 0.943639E+09 | 0.00 | 0.00 | 6254628.48 | 707394.54 | 6698959.52 | 0.314756E+10 | 0.00 | 1.02 |
March | 0.833757E+09 | 1123483.99 | 0.00 | 6628297.75 | 163483.97 | 9177913.00 | 0.198253E+10 | 0.00 | 0.95 |
April | 0.337878E+09 | 0.231599E+09 | 0.00 | 4445272.94 | 13380643.27 | 0.00 | 0.572863E+09 | 0.00 | 0.69 |
May | 0.172759E+09 | 0.388334E+09 | 0.00 | 2505708.50 | 11038645.78 | 0.00 | 0.189529E+09 | 0.00 | 0.52 |
June | 53868893.08 | 0.116152E+10 | 0.00 | 549569.91 | 20371651.40 | 0.00 | 59112601.68 | 0.00 | 0.47 |
July | 21784348.06 | 0.135829E+10 | 0.00 | 174432.41 | 49632816.18 | 0.00 | 19394376.28 | 0.00 | 0.44 |
August | 21500378.23 | 0.143852E+10 | 0.00 | 222130.64 | 28186638.43 | 0.00 | 17769546.91 | 0.00 | 0.54 |
September | 41688000.02 | 0.110886E+10 | 0.00 | 1933477.09 | 59249108.03 | 0.00 | 88733854.04 | 0.00 | 0.61 |
October | 0.374305E+09 | 0.279359E+09 | 0.00 | 7134865.71 | 8300544.29 | 0.00 | 0.165930E+10 | 0.00 | 1.03 |
November | 0.620364E+09 | 2101648.68 | 0.00 | 10566500.09 | 4814218.46 | 268505.82 | 0.308977E+10 | 0.00 | 1.28 |
December | 0.886163E+09 | 243341.56 | 0.00 | 8998788.51 | 429229.68 | 55561703.25 | 0.338214E+10 | 0.00 | 1.17 |
Annual Sum or Average | 0.494935E+10 | 0.597456E+10 | 0.00 | 60203777.35 | 0.198537E+09 | 82199459.86 | 0.172555E+11 | 0.00 | 0.84 |
Minimum of Months | 21500378.23 | 0.00 | 0.00 | 174432.41 | 163483.97 | 0.00 | 17769546.91 | 0.00 | 0.44 |
Maximum of Months | 0.943639E+09 | 0.143852E+10 | 0.00 | 10790105.32 | 59249108.03 | 55561703.25 | 0.338214E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125135E+10 | 1563604.08 | 0.00 | 2104634.32 | 2479926.91 | 18545843.39 | 0.508638E+09 | 0.00 | 0.93 |
February | 0.152167E+10 | 0.00 | 0.00 | 1293934.84 | 664863.08 | 19558972.95 | 0.678733E+09 | 0.00 | 0.88 |
March | 0.121493E+10 | 803071.24 | 0.00 | 2554671.06 | 0.00 | 16428058.39 | 0.689469E+09 | 0.00 | 0.98 |
April | 0.358930E+09 | 0.182683E+09 | 0.00 | 2946954.31 | 6105960.78 | 0.00 | 0.368147E+09 | 0.00 | 0.84 |
May | 0.194511E+09 | 0.395006E+09 | 0.00 | 1657426.91 | 3376876.55 | 0.00 | 0.111764E+09 | 0.00 | 0.70 |
June | 53929963.89 | 0.111764E+10 | 0.00 | 335303.90 | 15269270.36 | 0.00 | 43226600.61 | 0.00 | 0.67 |
July | 21015727.76 | 0.107439E+10 | 0.00 | 106961.52 | 44686444.36 | 0.00 | 15030279.77 | 0.00 | 0.55 |
August | 23383049.72 | 0.102334E+10 | 0.00 | 126252.61 | 25128492.47 | 0.00 | 10932532.89 | 0.00 | 0.62 |
September | 52883618.86 | 0.667017E+09 | 0.00 | 1041177.22 | 59637091.48 | 0.00 | 47632339.42 | 0.00 | 0.62 |
October | 0.607051E+09 | 0.138466E+09 | 0.00 | 2621536.33 | 9912417.44 | 206198.16 | 0.515714E+09 | 0.00 | 0.83 |
November | 0.110135E+10 | 1766294.45 | 0.00 | 2670790.08 | 4448869.96 | 6932746.35 | 0.752274E+09 | 0.00 | 0.94 |
December | 0.149876E+10 | 4903.50 | 0.00 | 1147714.88 | 561569.77 | 0.117692E+09 | 0.500534E+09 | 0.00 | 0.80 |
Annual Sum or Average | 0.789976E+10 | 0.460268E+10 | 0.00 | 18607357.98 | 0.172272E+09 | 0.179364E+09 | 0.424210E+10 | 0.00 | 0.78 |
Minimum of Months | 21015727.76 | 0.00 | 0.00 | 106961.52 | 0.00 | 0.00 | 10932532.89 | 0.00 | 0.55 |
Maximum of Months | 0.152167E+10 | 0.111764E+10 | 0.00 | 2946954.31 | 59637091.48 | 0.117692E+09 | 0.752274E+09 | 0.00 | 0.98 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.196111E+12 | 0.449586E+10 | 0.00 | 0.190298E+12 | 0.593363E+11 |
February | 0.203733E+12 | 0.467244E+10 | 0.00 | 0.196893E+12 | 0.136035E+11 |
March | 0.257505E+12 | 0.461757E+10 | 0.00 | 0.197251E+12 | 0.592270E+11 |
April | 0.302471E+12 | 0.588971E+09 | 0.00 | 0.107395E+12 | 0.173875E+12 |
May | 0.293487E+12 | -909330619.8 | 0.00 | 0.702466E+11 | 0.233577E+12 |
June | 0.298419E+12 | -0.310923E+10 | 0.00 | 0.244283E+10 | 0.322892E+12 |
July | 0.276783E+12 | -0.434952E+10 | 0.00 | -0.400667E+11 | 0.314629E+12 |
August | 0.249451E+12 | -0.395277E+10 | 0.00 | -0.337031E+11 | 0.320835E+12 |
September | 0.216240E+12 | -0.252269E+10 | 0.00 | -0.358709E+11 | 0.268059E+12 |
October | 0.215231E+12 | 0.166478E+10 | 0.00 | 0.139885E+12 | 0.147713E+12 |
November | 0.197756E+12 | 0.410990E+10 | 0.00 | 0.187209E+12 | 0.632026E+11 |
December | 0.163820E+12 | 0.546200E+10 | 0.00 | 0.204886E+12 | 0.276407E+11 |
Annual Sum or Average | 0.287101E+13 | 0.107680E+11 | 0.00 | 0.118687E+13 | 0.200459E+13 |
Minimum of Months | 0.163820E+12 | -0.434952E+10 | 0.00 | -0.400667E+11 | 0.136035E+11 |
Maximum of Months | 0.302471E+12 | 0.546200E+10 | 0.00 | 0.204886E+12 | 0.322892E+12 |