Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2024-07-03 12:20:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2152.80 | 432.10 | 432.10 |
Net Site Energy | 2152.80 | 432.10 | 432.10 |
Total Source Energy | 6817.91 | 1368.46 | 1368.46 |
Net Source Energy | 6817.91 | 1368.46 | 1368.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 899.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 121.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2152.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 899.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 121.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 899.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 121.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 212.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 212.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 432.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2152.797 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2152.797 | 100.00 |
Total On-Site and Utility Electric Sources | 2152.797 | 100.00 |
Total Electricity End Uses | 2152.797 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 805.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2150.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:20 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89917.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15860.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2875.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 177422.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 89917.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15860.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2875.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2849.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 949.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 156.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 384.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6817.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 571.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 77.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1368.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 571.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 190.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 77.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1368.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.64 | 0.283532 | 0.291000 | 0.769194 | 0.756086 | 0.500000 | 0.001344 |
CORE_MID VAV BOX COMPONENT | 2.14 | 0.350020 | 0.349000 | 0.747272 | 0.933386 | 0.500000 | 0.001089 |
CORE_TOP VAV BOX COMPONENT | 2.28 | 0.328188 | 0.341000 | 0.778712 | 0.875168 | 0.500000 | 0.001161 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.736186 | 0.214608 | 0.223000 | 0.164169 | 0.572289 | 0.500000 | 0.001775 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.661728 | 0.151152 | 0.200000 | 0.132346 | 0.403073 | 0.500000 | 0.002521 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.716865 | 0.220393 | 0.229000 | 0.164162 | 0.587714 | 0.500000 | 0.001729 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.763213 | 0.131045 | 0.200000 | 0.152643 | 0.349453 | 0.500000 | 0.002907 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.635339 | 0.248673 | 0.255000 | 0.162011 | 0.663128 | 0.500000 | 0.001532 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.601031 | 0.166417 | 0.200000 | 0.120206 | 0.443778 | 0.500000 | 0.002289 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.617240 | 0.255965 | 0.263000 | 0.162334 | 0.682572 | 0.500000 | 0.001488 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.646038 | 0.154813 | 0.200000 | 0.129208 | 0.412835 | 0.500000 | 0.002461 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.641658 | 0.246224 | 0.246000 | 0.157848 | 0.656598 | 0.500000 | 0.001547 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.637595 | 0.156873 | 0.200000 | 0.127519 | 0.418329 | 0.500000 | 0.002429 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.624360 | 0.253046 | 0.252000 | 0.157339 | 0.674789 | 0.500000 | 0.001506 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.692722 | 0.144380 | 0.200000 | 0.138544 | 0.385013 | 0.500000 | 0.002639 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25678.07 |
CORE_MID VAV BOX REHEAT COIL | 24946.24 |
CORE_TOP VAV BOX REHEAT COIL | 25995.83 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 5480.49 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4418.11 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 5480.24 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5095.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5408.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4012.86 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5419.22 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4313.35 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5269.45 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4256.98 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5252.46 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4625.04 |
PACU_VAV_BOT HEATING COIL | 21979.05 |
PACU_VAV_MID HEATING COIL | 19821.58 |
PACU_VAV_TOP HEATING COIL | 23018.22 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.57 | 1.34 | 5.14 | 1.34 | 4.73 | 4.73 | 0.300000 | 0.283771 | 4.73 |
PACU_VAV_MID | 2.37 | 1.33 | 4.74 | 1.33 | 4.27 | 4.27 | 0.300000 | 0.311277 | 4.27 |
PACU_VAV_TOP | 2.58 | 1.39 | 5.16 | 1.39 | 4.96 | 4.96 | 0.300000 | 0.280863 | 4.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.73 |
PACU_VAV_MID_OA_CONTROLLER | 4.27 |
PACU_VAV_TOP_OA_CONTROLLER | 4.96 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.73 | 117519.73 | 0.701083 | 1.58 | 39169.33 | 0.701083 |
PACU_VAV_MID COOLING COIL | 4.27 | 105983.93 | 0.701083 | 1.42 | 35324.44 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.96 | 123076.04 | 0.701083 | 1.65 | 41021.24 | 0.701083 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.73 |
PACU_VAV_MID FAN | 4.27 |
PACU_VAV_TOP FAN | 4.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5151E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5504E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5650E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5946E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8809E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9014E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5694E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5839E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7301E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4151E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9015E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3591E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0132E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8570E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8227E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0568E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5144E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5480E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5642E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5920E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8801E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8991E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5692E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5837E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4422E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9838E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0539E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7301E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0085E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5052E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3172E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5628E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3363E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3480E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0516E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0602E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8640E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8671E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9989E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0039E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4102E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4402E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0796E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1031E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7720E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7851E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5692E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5837E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1729E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1842E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7295E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3048E-003 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4477E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1282E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8227E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0568E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4106E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4408E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0800E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1039E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7725E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7867E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5694E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5839E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6562E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0762E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3007E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8363E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2424E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6059E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3172E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5628E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4829E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5023E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2232E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2412E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0190E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0301E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9990E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0040E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.2017E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1440E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3542E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0976E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5016E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4995E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2209E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5024E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3378E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9246E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9688E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6822E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9475E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4696E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2554E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5255E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5150E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5940E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0404E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2929E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.7450E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.3584E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2209E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5024E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5459E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0131E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2087E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7837E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1751E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5660E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2554E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5255E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.2013E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1437E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3537E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0973E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5011E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4992E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2206E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5023E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3377E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9245E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9687E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6821E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9473E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4695E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2551E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5253E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5150E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5939E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0404E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2928E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.7448E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.3576E-003 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2206E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5023E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5458E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0129E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2086E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7836E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1749E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5658E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2551E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5253E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36676.00154 | 36676.00154 | 2.64328 | 2.64328 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 29736.02684 | 29736.02684 | 2.14118 | 2.14118 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 1193.16458 | 1193.16458 | 5.07789E-002 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31415.62866 | 31415.62866 | 2.28361 | 2.28361 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 4642.35298 | 4642.35298 | 0.19517 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10127.26038 | 10127.26038 | 0.73619 | 0.73619 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 1564.10466 | 1564.10466 | 6.56725E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9103.00834 | 9103.00834 | 0.66173 | 0.66173 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 1016.21475 | 1016.21475 | 4.26717E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9861.46025 | 9861.46025 | 0.71686 | 0.71686 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 1614.05613 | 1614.05613 | 6.77360E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10499.10466 | 10499.10466 | 0.76321 | 0.76321 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 1016.17958 | 1016.17958 | 4.26702E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8740.17333 | 8740.17333 | 0.63534 | 0.63534 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 119.08292 | 119.08292 | 5.09483E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8268.24852 | 8268.24852 | 0.60103 | 0.60103 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 90.87925 | 90.87925 | 3.88682E-003 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8491.19484 | 8491.19484 | 0.61724 | 0.61724 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 153.03864 | 153.03864 | 6.54392E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8887.40564 | 8887.40564 | 0.64604 | 0.64604 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 90.87728 | 90.87728 | 3.88674E-003 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8826.95174 | 8826.95174 | 0.64166 | 0.64166 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 825.01981 | 825.01981 | 3.48917E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8771.10532 | 8771.10532 | 0.63760 | 0.63760 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 546.76166 | 546.76166 | 2.31211E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8588.99262 | 8588.99262 | 0.62436 | 0.62436 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 868.21664 | 868.21664 | 3.66992E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9529.46928 | 9529.46928 | 0.69272 | 0.69272 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 546.75108 | 546.75108 | 2.31207E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 80068.88 | 4.73252 | 4.73252 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | PACU_VAV_MID | Cooling | Sensible | 73620.29 | 4.26797 | 4.26797 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | PACU_VAV_TOP | Cooling | Sensible | 82990.35 | 4.95627 | 4.95627 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64328 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28353 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76919 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75609 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34376E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25678.07203 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14118 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35002 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74727 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93339 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08851E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24946.24101 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28361 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32819 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77871 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87517 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16092E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25995.82988 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73619 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21461 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16417 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57229 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77533E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5480.48574 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66173 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15115 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13235 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40307 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52064E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4418.10798 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71686 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22039 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16416 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58771 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72873E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5480.23548 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76321 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13105 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15264 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34945 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90740E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5095.68191 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63534 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24867 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16201 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66313 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53213E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5408.44169 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60103 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16642 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12021 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44378 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28943E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4012.85775 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61724 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25596 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16233 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68257 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48849E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5419.22013 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64604 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15481 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12921 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41284 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46103E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4313.34816 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64166 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24622 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24600 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15785 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65660 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54737E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5269.44894 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63760 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15687 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12752 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41833 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42871E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4256.98068 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62436 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25305 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15734 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67479 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50566E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5252.45540 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69272 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14438 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13854 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38501 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63887E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4625.04205 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.57146 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34295 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.14293 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34295 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.73252 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.73252 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28377 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.36876 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32852 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.73751 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32852 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.26797 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.26797 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31128 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.58080 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39203 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.16161 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.39203 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95627 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.95627 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.28086 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.73252 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.26797 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.95627 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.73252 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.73252 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 117519.72991 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57735 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39169.32598 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 21979.05198 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.73252 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.26797 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.26797 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105983.92869 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42252 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35324.44343 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
164 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 19821.57617 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.26797 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95627 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.95627 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 123076.04150 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65193 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 41021.24463 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
173 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 23018.21759 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.95627 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 117327.79 | 400339.04 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.92 | 13.38 | 5.4711 | 4.3310 | 2.9145 | 1.2563 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 105810.83 | 361041.54 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.92 | 13.38 | 4.9340 | 3.9059 | 2.6284 | 1.1330 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 122875.03 | 419267.00 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.92 | 13.38 | 5.7298 | 4.5358 | 3.0523 | 1.3157 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.4294586873 | 0.3133492927 | Pass | Pass | 0.1979197276 | 0.3981851509 | Pass | Fail |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4370041298E-002 | 8.2347363675E-002 | Pass | Pass | 0.2005679751 | 0.4789946310 | Fail | Fail |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.4247188548E-002 | 5.8276928899E-002 | Pass | Pass | 0.2560344171 | 0.8899610622 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6239154846E-002 | 5.0708525392E-002 | Pass | Pass | 0.2876923829 | 0.9064326427 | Fail | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2204266976 | 0.2714286034 | Pass | Pass | 0.1792615533 | 0.3894641578 | Pass | Fail |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2199495867 | 0.2864760532 | Pass | Pass | 0.1764797523 | 0.3802165681 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2160218252 | 0.2941134117 | Pass | Pass | 0.1761975155 | 0.3795473751 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2639085258 | 0.3695604556 | Pass | Pass | 0.1795819038 | 0.3831636425 | Pass | Fail |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2220570796 | 0.3201596695 | Pass | Pass | 0.1910723794 | 0.4070875134 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2896093375 | 0.4001483197 | Pass | Pass | 0.1774829465 | 0.3798940014 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3623402431 | 0.2831178312 | Pass | Fail | 0.1935119597 | 0.3923917641 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4113025960 | 0.3265167590 | Pass | Fail | 0.1957765205 | 0.3942002832 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3718966191 | 0.3011855704 | Pass | Fail | 0.2110641847 | 0.4294730968 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4294386404 | 0.3459082032 | Pass | Fail | 0.1930592449 | 0.3905249409 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2164492318 | 0.2787644414 | Pass | Pass | 0.1716943521 | 0.3759862249 | Pass | Fail |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2634076373 | 0.3487945494 | Pass | Pass | 0.1849541430 | 0.4009896795 | Pass | Fail |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2212716642 | 0.2951033567 | Pass | Pass | 0.1904765924 | 0.4188004054 | Pass | Fail |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2800409873 | 0.3645800750 | Pass | Pass | 0.1719508427 | 0.3750282041 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3160.20 | -130.7 | 0.00 | -2155.5 | 4766.22 | 5640.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 195.79 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.34 | 0.0000 | Y | 8.58 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 5.47 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.21 | 0.0000 | Y | 5.40 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.29 | 0.0000 | Y | 8.56 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.45 | 0.0000 | Y | 5.46 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.17 | 0.0000 | Y | 8.52 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.16 | 0.0000 | Y | 5.39 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.34 | 0.0000 | Y | 8.58 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 5.47 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.22 | 0.0000 | Y | 8.54 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.21 | 0.0000 | Y | 5.40 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 299.70 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.93 | 41.93 | 4.44 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.83 | 62.88 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.83 | 45.49 | 40.26 | |
Exterior Lighting Total | 5686.19 | 49.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 117519.73 | 82391.11 | 35128.62 | 0.70 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105983.93 | 74303.55 | 31680.37 | 0.70 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 123076.04 | 86286.55 | 36789.49 | 0.70 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 117327.8 | 3.21 | 10.94 | N/A | N/A | 12.53 | |
PACU_VAV_MID COOLING COIL | 105810.8 | 3.21 | 10.94 | N/A | N/A | 12.53 | |
PACU_VAV_TOP COOLING COIL | 122875.0 | 3.21 | 10.94 | N/A | N/A | 12.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25678.07 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24946.24 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 25995.83 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5480.49 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4418.11 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5480.24 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5095.68 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5408.44 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4012.86 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5419.22 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4313.35 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5269.45 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4256.98 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5252.46 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4625.04 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 21979.05 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 19821.58 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 23018.22 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.73 | 10359.54 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.27 | 9342.64 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.96 | 10849.33 | 2189.01 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 117327.79 | 3.21 | 10.94 | 12.53 | 5.4711 | 3.59 | 12.25 | 4.3310 | 3.79 | 12.92 | 2.9145 | 3.92 | 13.38 | 1.2563 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105810.83 | 3.21 | 10.94 | 12.53 | 4.9340 | 3.59 | 12.25 | 3.9059 | 3.79 | 12.92 | 2.6284 | 3.92 | 13.38 | 1.1330 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 122875.03 | 3.21 | 10.94 | 12.53 | 5.7298 | 3.59 | 12.25 | 4.5358 | 3.79 | 12.92 | 3.0523 | 3.92 | 13.38 | 1.3157 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36676.00 | 36676.00 | 37.29 | 2.643 | 2.643 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_MID | 29736.03 | 29736.03 | 30.23 | 2.141 | 2.141 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_TOP | 31415.63 | 31415.63 | 31.94 | 2.284 | 2.284 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00888 | 35.20 | 0.01716 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10127.26 | 10127.26 | 48.84 | 0.736 | 0.736 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00890 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9103.01 | 9103.01 | 69.35 | 0.662 | 0.662 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00879 | 31.49 | 0.01715 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9861.46 | 9861.46 | 47.56 | 0.717 | 0.717 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10499.10 | 10499.10 | 79.99 | 0.763 | 0.763 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00875 | 34.58 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8740.17 | 8740.17 | 42.15 | 0.635 | 0.635 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00888 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8268.25 | 8268.25 | 62.99 | 0.601 | 0.601 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00876 | 31.49 | 0.01715 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8491.19 | 8491.19 | 40.95 | 0.617 | 0.617 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 24.00 | 24.00 | 0.00889 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8887.41 | 8887.41 | 67.71 | 0.646 | 0.646 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00874 | 34.35 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8826.95 | 8826.95 | 42.57 | 0.642 | 0.642 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00893 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8771.11 | 8771.11 | 66.82 | 0.638 | 0.638 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00878 | 31.25 | 0.01715 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8588.99 | 8588.99 | 41.43 | 0.624 | 0.624 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9529.47 | 9529.47 | 72.60 | 0.693 | 0.693 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00875 | 34.58 | 0.01716 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 22.19 | 0.01480 | 20.10 | 0.01480 | 0.425 | 0.00 | |
CORE_MID | 1193.16 | 1193.16 | 1.21 | 0.051 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
CORE_TOP | 4642.35 | 4642.35 | 4.72 | 0.195 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 1564.10 | 1564.10 | 7.54 | 0.066 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01000 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 1016.21 | 1016.21 | 7.74 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01005 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 1614.06 | 1614.06 | 7.78 | 0.068 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00997 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 1016.18 | 1016.18 | 7.74 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01005 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 119.08 | 119.08 | 0.57 | 0.005 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01211 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 90.88 | 90.88 | 0.69 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01190 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 153.04 | 153.04 | 0.74 | 0.007 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01170 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 90.88 | 90.88 | 0.69 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01190 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 825.02 | 825.02 | 3.98 | 0.035 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01031 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 546.76 | 546.76 | 4.17 | 0.023 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01034 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 868.22 | 868.22 | 4.19 | 0.037 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01025 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 546.75 | 546.75 | 4.17 | 0.023 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01034 | 20.10 | 0.01480 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.73 | 4.73 | 0.00 | 0.00 | 4.7325 | 1.3430 | 4.7325 | 0.2838 | 0.3000 |
PACU_VAV_MID | 4.27 | 4.27 | 0.00 | 0.00 | 4.2680 | 1.3285 | 4.2680 | 0.3113 | 0.3000 |
PACU_VAV_TOP | 4.96 | 4.96 | 0.00 | 0.00 | 4.9563 | 1.3920 | 4.9563 | 0.2809 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25678.072 | 25678.072 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 25678.07 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24946.241 | 24946.241 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24946.24 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800451 | 51.7216 | 1193.16 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 25995.830 | 25995.830 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25995.83 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 4642.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 5480.486 | 5480.486 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5480.49 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00999685 | 64.3858 | 1564.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4418.108 | 4418.108 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4418.11 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01004882 | 64.7148 | 1016.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 5480.235 | 5480.235 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5480.24 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00996540 | 64.1863 | 1614.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5095.682 | 5095.682 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5095.68 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01004888 | 64.7152 | 1016.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5408.442 | 5408.442 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5408.44 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01211319 | 77.7618 | 119.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4012.858 | 4012.858 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4012.86 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01189539 | 76.3897 | 90.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5419.220 | 5419.220 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5419.22 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01170008 | 75.1586 | 153.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4313.348 | 4313.348 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4313.35 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01189543 | 76.3900 | 90.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5269.449 | 5269.449 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5269.45 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01030686 | 66.3525 | 825.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4256.981 | 4256.981 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4256.98 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01034308 | 66.5817 | 546.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5252.455 | 5252.455 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5252.46 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01025180 | 66.0037 | 868.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4625.042 | 4625.042 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4625.04 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01034314 | 66.5820 | 546.75 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 117519.730 | 82391.111 | 4.732520 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 120568.04 | 85947.01 | 4.732520 | 26.84 | 19.33 | 0.01095729 | 11.03 | 11.03 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 25.2544 | 24.00 | 0.00885251 | 47.6084 | 64880.70 | 0.00 | 121178.62 | 83827.32 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 21979.052 | 21979.052 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 21979.05 | 21979.05 | 1.419756 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 84.1814 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 105983.929 | 74303.554 | 4.267973 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 109702.94 | 76181.56 | 4.267973 | 27.13 | 19.63 | 0.01123435 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 28.0032 | 24.00 | 0.00891621 | 47.9465 | 58455.45 | 0.00 | 109283.66 | 75598.78 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 19821.576 | 19821.576 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 19821.58 | 19821.58 | 1.280392 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 93.3441 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 123076.042 | 86286.547 | 4.956272 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 125971.37 | 90421.98 | 4.956272 | 26.69 | 19.22 | 0.01087500 | 11.03 | 11.03 | 0.00850000 | 35.12 | 0.01715799 | 25.81 | 24.1143 | 24.00 | 0.00887034 | 47.7034 | 67972.64 | 0.00 | 126907.92 | 87790.66 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 23018.218 | 23018.218 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 23018.22 | 23018.22 | 1.486882 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 80.3810 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25678.072 | 25678.072 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 25678.07 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25678.07 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24946.241 | 24946.241 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24946.24 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24946.24 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.87 | 0.00800451 | 21.00 | 0.00800451 | 51.7216 | 1193.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 25995.830 | 25995.830 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25995.83 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25995.83 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.70 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 4642.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5480.486 | 5480.486 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5480.49 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5480.49 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.00999685 | 21.00 | 0.00999685 | 64.3858 | 1564.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4418.108 | 4418.108 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4418.11 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4418.11 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01004882 | 21.00 | 0.01004882 | 64.7148 | 1016.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5480.235 | 5480.235 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5480.24 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5480.24 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.00996540 | 21.00 | 0.00996540 | 64.1863 | 1614.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5095.682 | 5095.682 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5095.68 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5095.68 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01004888 | 21.00 | 0.01004888 | 64.7152 | 1016.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5408.442 | 5408.442 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5408.44 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5408.44 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.97 | 0.01211319 | 21.00 | 0.01211319 | 77.7618 | 119.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4012.858 | 4012.858 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4012.86 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4012.86 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01189539 | 21.00 | 0.01189539 | 76.3897 | 90.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5419.220 | 5419.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5419.22 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5419.22 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01170008 | 21.00 | 0.01170008 | 75.1586 | 153.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4313.348 | 4313.348 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4313.35 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4313.35 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01189543 | 21.00 | 0.01189543 | 76.3900 | 90.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5269.449 | 5269.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5269.45 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5269.45 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01030686 | 21.00 | 0.01030686 | 66.3525 | 825.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4256.981 | 4256.981 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4256.98 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4256.98 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01034308 | 21.00 | 0.01034308 | 66.5817 | 546.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5252.455 | 5252.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5252.46 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5252.46 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.75 | 0.01025180 | 21.00 | 0.01025180 | 66.0037 | 868.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4625.042 | 4625.042 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4625.04 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4625.04 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01034314 | 21.00 | 0.01034314 | 66.5820 | 546.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 117519.730 | 82391.111 | 4.732520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.98012 | 1025.2090 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.732520 | 5.69603675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 120568.04 | 85947.01 | 1.0259 | 5.69603675 | 4.732520 | 26.84 | 19.33 | 0.01095729 | 54917.3 | 11.03 | 11.03 | 0.00850000 | 32511.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10359.537 | 110208.50 | 35.20 | 0.01715815 | 25.83 | 1.19517000 | 25.2544 | 24.00 | 0.00885251 | 24.00 | 0.00885251 | 47.6084 | 64880.70 | 0.00 | 121178.62 | 83827.32 | 5.47108636 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21979.052 | 21979.052 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.732520 | 5.69603675 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 21979.05 | 21979.05 | 1.0000 | 1.70881102 | 1.419756 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21979.05 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 84.1814 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105983.929 | 74303.554 | 4.267973 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.94790 | 1025.7241 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.267973 | 5.13691065 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 109702.94 | 76181.56 | 1.0351 | 5.13691065 | 4.267973 | 27.13 | 19.63 | 0.01123435 | 55919.4 | 11.03 | 11.03 | 0.00850000 | 32512.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9342.639 | 100360.30 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 28.0032 | 24.00 | 0.00891621 | 24.00 | 0.00891621 | 47.9465 | 58455.45 | 0.00 | 109283.66 | 75598.78 | 4.93404152 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19821.576 | 19821.576 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.267973 | 5.13691065 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 19821.58 | 19821.58 | 1.0000 | 1.54107320 | 1.280392 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19821.58 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 93.3441 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 123076.042 | 86286.547 | 4.956272 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99331 | 1025.0561 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.956272 | 5.96534434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 125971.37 | 90421.98 | 1.0235 | 5.96534434 | 4.956272 | 26.69 | 19.22 | 0.01087500 | 54553.8 | 11.03 | 11.03 | 0.00850000 | 32511.3 | -999.0 | -999.00 | -999.00 | -999.00 | 10849.334 | 115122.03 | 35.12 | 0.01715799 | 25.81 | 1.19517000 | 24.1143 | 24.00 | 0.00887034 | 24.00 | 0.00887034 | 47.7034 | 67972.64 | 0.00 | 126907.92 | 87790.66 | 5.72975833 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23018.218 | 23018.218 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.956272 | 5.96534434 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 23018.22 | 23018.22 | 1.0000 | 1.78960330 | 1.486882 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23018.22 | 0.00 | 0.00000000 | -6.26 | 1.19517000 | 80.3810 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5943.00 | 0.00 | 0.00 |
CORE_MID | 5427.00 | 1.83 | 0.00 |
CORE_TOP | 5233.00 | 19.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 5721.33 | 393.67 | 369.33 |
PERIMETER_TOP_ZN_2 | 5689.50 | 563.67 | 546.50 |
PERIMETER_TOP_ZN_1 | 5820.67 | 497.83 | 495.00 |
PERIMETER_TOP_ZN_4 | 5357.17 | 518.50 | 389.50 |
PERIMETER_BOT_ZN_3 | 5933.17 | 110.50 | 110.50 |
PERIMETER_BOT_ZN_2 | 5941.50 | 332.50 | 332.50 |
PERIMETER_BOT_ZN_1 | 5942.00 | 1695.17 | 1695.17 |
PERIMETER_BOT_ZN_4 | 5932.33 | 241.50 | 241.50 |
PERIMETER_MID_ZN_3 | 5878.67 | 221.33 | 219.50 |
PERIMETER_MID_ZN_2 | 4899.00 | 403.17 | 402.50 |
PERIMETER_MID_ZN_1 | 5921.17 | 357.67 | 357.67 |
PERIMETER_MID_ZN_4 | 5656.67 | 321.67 | 310.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 2244.83 | 2150.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 39.83 | 0.00 | 36.33 |
PERIMETER_TOP_ZN_2 | 0.00 | 79.33 | 0.00 | 78.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 74.17 | 0.00 | 72.17 |
PERIMETER_TOP_ZN_4 | 0.00 | 59.33 | 0.00 | 50.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 13.67 | 0.00 | 12.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 54.50 | 0.00 | 54.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 666.50 | 0.00 | 665.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 49.33 | 0.00 | 40.50 |
PERIMETER_MID_ZN_3 | 0.00 | 15.83 | 0.00 | 14.17 |
PERIMETER_MID_ZN_2 | 0.00 | 51.83 | 0.00 | 51.83 |
PERIMETER_MID_ZN_1 | 0.00 | 75.83 | 0.00 | 75.83 |
PERIMETER_MID_ZN_4 | 0.00 | 46.67 | 0.00 | 40.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 823.17 | 0.00 | 805.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.467 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.445 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.442 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.626 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.774 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.682 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.783 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.537 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.656 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.675 | 1.228 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.652 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.633 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.735 | 0.023 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.689 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.782 | 0.022 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7830337.85 | 0.00 | 7830337.85 | 0.00 | 7830337.85 | 13393058.27 | 8017.48 | 205.77 | 536.75 | 371.50 |
CORE_MID | 7241744.38 | 0.00 | 7241744.38 | 0.00 | 7241744.38 | 13393058.27 | 8735.11 | 6.35 | 18.54 | 220.93 |
CORE_TOP | 7206177.61 | 0.00 | 7206177.61 | 0.00 | 7206177.61 | 13393058.27 | 8745.20 | 4.36 | 10.44 | 221.92 |
PERIMETER_TOP_ZN_3 | 2119522.17 | 0.00 | 2119522.17 | 148624.63 | 2268146.80 | 2823374.22 | 4810.23 | 51.67 | 3898.11 | 221.92 |
PERIMETER_TOP_ZN_2 | 1660017.33 | 0.00 | 1660017.33 | 99082.49 | 1759099.81 | 1787429.43 | 3439.18 | 1.19 | 5319.63 | 221.92 |
PERIMETER_TOP_ZN_1 | 2303473.05 | 0.00 | 2303473.05 | 148624.63 | 2452097.68 | 2823374.22 | 4585.37 | 35.97 | 4138.66 | 221.92 |
PERIMETER_TOP_ZN_4 | 1689001.18 | 0.00 | 1689001.18 | 99082.49 | 1788083.67 | 1787312.18 | 3465.74 | 15.95 | 5278.32 | 221.92 |
PERIMETER_BOT_ZN_3 | 1876091.92 | 0.00 | 1876091.92 | 79023.74 | 1955115.65 | 2823374.22 | 5776.15 | 265.92 | 2717.93 | 371.50 |
PERIMETER_BOT_ZN_2 | 1445952.04 | 0.00 | 1445952.04 | 52682.17 | 1498634.22 | 1787429.43 | 3352.73 | 53.35 | 5353.91 | 371.50 |
PERIMETER_BOT_ZN_1 | 2319542.03 | 0.00 | 2319542.03 | 4024723.19 | 6344265.21 | 2823374.22 | 4370.46 | 196.13 | 4193.41 | 371.50 |
PERIMETER_BOT_ZN_4 | 1447915.79 | 0.00 | 1447915.79 | 52682.17 | 1500597.97 | 1787312.18 | 3680.89 | 108.93 | 4970.18 | 371.50 |
PERIMETER_MID_ZN_3 | 2143776.97 | 0.00 | 2143776.97 | 123719.22 | 2267496.19 | 2823374.22 | 4654.23 | 54.43 | 4051.34 | 220.93 |
PERIMETER_MID_ZN_2 | 1653487.22 | 0.00 | 1653487.22 | 82478.99 | 1735966.21 | 1787429.43 | 3443.94 | 2.56 | 5313.50 | 1129.93 |
PERIMETER_MID_ZN_1 | 2326517.86 | 0.00 | 2326517.86 | 123719.22 | 2450237.08 | 2823374.22 | 4468.90 | 27.56 | 4263.55 | 220.93 |
PERIMETER_MID_ZN_4 | 1683703.67 | 0.00 | 1683703.67 | 82478.99 | 1766182.65 | 1787312.18 | 3482.17 | 15.34 | 5262.49 | 220.93 |
Total Facility | 44947261.07 | 0.00 | 44947261.07 | 5116921.93 | 50064183.00 | 67843644.98 | 8760.00 | 820.40 | 5653.36 | 1345.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3393 | 0.0000 | 0.3393 | 0.0000 | 0.3393 | 0.4247 | 5227.75 | 199.09 | 516.16 |
CORE_MID | 0.3230 | 0.0000 | 0.3230 | 0.0000 | 0.3230 | 0.4247 | 5922.87 | 6.18 | 13.95 |
CORE_TOP | 0.3214 | 0.0000 | 0.3214 | 0.0000 | 0.3214 | 0.4247 | 5931.14 | 4.15 | 7.71 |
PERIMETER_TOP_ZN_3 | 0.0957 | 0.0000 | 0.0957 | 0.0038 | 0.0995 | 0.0895 | 2005.15 | 51.33 | 3886.52 |
PERIMETER_TOP_ZN_2 | 0.0750 | 0.0000 | 0.0750 | 0.0025 | 0.0775 | 0.0567 | 842.12 | 0.80 | 5100.08 |
PERIMETER_TOP_ZN_1 | 0.1044 | 0.0000 | 0.1044 | 0.0038 | 0.1081 | 0.0895 | 1778.70 | 35.30 | 4129.00 |
PERIMETER_TOP_ZN_4 | 0.0758 | 0.0000 | 0.0758 | 0.0025 | 0.0783 | 0.0567 | 870.01 | 15.65 | 5057.34 |
PERIMETER_BOT_ZN_3 | 0.0822 | 0.0000 | 0.0822 | 0.0020 | 0.0842 | 0.0895 | 2969.51 | 262.97 | 2710.52 |
PERIMETER_BOT_ZN_2 | 0.0635 | 0.0000 | 0.0635 | 0.0013 | 0.0649 | 0.0567 | 896.35 | 50.33 | 4996.32 |
PERIMETER_BOT_ZN_1 | 0.1029 | 0.0000 | 0.1029 | 0.1864 | 0.2893 | 0.0895 | 1577.31 | 181.85 | 4183.84 |
PERIMETER_BOT_ZN_4 | 0.0632 | 0.0000 | 0.0632 | 0.0013 | 0.0645 | 0.0567 | 1230.52 | 107.65 | 4604.83 |
PERIMETER_MID_ZN_3 | 0.0969 | 0.0000 | 0.0969 | 0.0031 | 0.1000 | 0.0895 | 1846.43 | 53.91 | 4042.66 |
PERIMETER_MID_ZN_2 | 0.0712 | 0.0000 | 0.0712 | 0.0022 | 0.0734 | 0.0567 | 844.22 | 1.30 | 4188.49 |
PERIMETER_MID_ZN_1 | 0.1055 | 0.0000 | 0.1055 | 0.0031 | 0.1086 | 0.0895 | 1660.07 | 27.24 | 4255.69 |
PERIMETER_MID_ZN_4 | 0.0757 | 0.0000 | 0.0757 | 0.0021 | 0.0778 | 0.0567 | 884.82 | 15.11 | 5043.07 |
Total Facility | 1.9957 | 0.0000 | 1.9957 | 0.2142 | 2.2099 | 2.1513 | 5943.00 | 798.16 | 5216.79 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21613496.41 | 0.00 | 21613496.41 | 22614548.33 | 3274.40 | 0.00 | 5485.60 | 371.50 |
PACU_VAV_MID | 21800938.64 | 0.00 | 21800938.64 | 22614548.33 | 3434.19 | 0.00 | 5325.81 | 220.93 |
PACU_VAV_TOP | 21698026.36 | 0.00 | 21698026.36 | 22614548.33 | 3430.62 | 0.00 | 5329.38 | 221.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9432 | 0.0000 | 0.9432 | 0.7171 | 828.89 | 0.00 | 5114.11 |
PACU_VAV_MID | 0.9789 | 0.0000 | 0.9789 | 0.7171 | 838.12 | 0.00 | 5104.88 |
PACU_VAV_TOP | 0.9739 | 0.0000 | 0.9739 | 0.7171 | 835.55 | 0.00 | 5107.45 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5485.60 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5325.81 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5329.38 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0961 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1398 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1333 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 920 |
Defaulted Fields | 545 |
Fields with Defaults | 2217 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
Electricity:Building | 1019.39 | 13503.13 | 18-JUN-17:20 | 72941.29 | 18-DEC-17:00 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1019.39 | 13503.13 | 18-JUN-17:20 | 72941.29 | 18-DEC-17:00 |
InteriorLights:Electricity | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 299.70 | 1025.38 | 18-JUN-17:20 | 31270.78 | 18-DEC-17:00 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 32.91 | 422.10 | 28-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.87 | 271.65 | 29-MAY-17:10 | 1768.58 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.87 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.81 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 32.89 | 422.10 | 07-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.56 | 36.00 | 01-JAN-09:00 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.56 | 36.00 | 01-JAN-09:00 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.86 | 271.65 | 29-MAY-17:10 | 1768.58 | 04-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:20 | 860.01 | 04-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.46 | 22.79 | 01-JAN-07:20 | 860.01 | 04-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.86 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.52 | 36.00 | 01-JAN-07:50 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.52 | 36.00 | 01-JAN-07:50 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.80 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.39 | 22.79 | 01-JAN-09:30 | 750.02 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.39 | 22.79 | 01-JAN-09:30 | 750.02 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 32.91 | 422.10 | 28-MAY-17:10 | 2620.04 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.58 | 36.00 | 01-JAN-09:10 | 1184.79 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.87 | 271.65 | 29-MAY-17:10 | 1768.58 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.47 | 22.79 | 01-JAN-07:20 | 860.01 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.87 | 425.61 | 12-MAR-17:10 | 2620.03 | 07-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.54 | 36.00 | 01-JAN-08:00 | 1184.79 | 07-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.81 | 267.21 | 12-MAR-17:10 | 1658.59 | 18-DEC-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.40 | 22.79 | 01-JAN-09:40 | 750.02 | 18-DEC-16:40 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 1048.10 | 367.92 | 01-JAN-00:10 | 107260.35 | 13-JUN-15:00 |
ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 15-FEB-13:10 |
Transformer:ExteriorEquipment:Electricity | 26.91 | 367.92 | 01-JAN-00:10 | 1410.29 | 15-FEB-13:10 |
ElectricityPurchased:Facility | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
ElectricityPurchased:Plant | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
Cogeneration:ElectricityPurchased | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
General:Cogeneration:ElectricityPurchased | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
ElectricityNet:Plant | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
Cogeneration:ElectricityNet | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
General:Cogeneration:ElectricityNet | 2152.80 | 13872.05 | 18-JUN-17:20 | 177422.83 | 13-JUN-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 121.50 | 0.00 | 01-JAN-00:10 | 16327.79 | 12-JUN-15:20 |
General:Fans:Electricity | 121.50 | 0.00 | 01-JAN-00:10 | 16327.79 | 12-JUN-15:20 |
ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 899.70 | 0.00 | 01-JAN-00:10 | 90068.80 | 13-JUN-15:00 |
General:Cooling:Electricity | 899.70 | 0.00 | 01-JAN-00:10 | 90068.80 | 13-JUN-15:00 |
Electricity:Plant | 35.80 | 0.00 | 01-JAN-00:10 | 4209.60 | 06-JAN-12:30 |
WaterSystems:Electricity | 35.65 | 0.00 | 01-JAN-00:10 | 4202.75 | 06-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 35.65 | 0.00 | 01-JAN-00:10 | 4202.75 | 06-JAN-12:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-15:30 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-15:30 |
WIRED_LTG_ELECTRICITY | 8.42 | 0.00 | 01-JAN-00:10 | 878.71 | 18-DEC-17:10 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5908.91 | 0.00 | 01-JAN-00:10 | 505442.00 | 13-JUN-15:30 |
EnergyTransfer:Building | 2009.46 | 0.00 | 01-JAN-00:10 | 173886.37 | 21-FEB-15:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 348.55 | 0.00 | 01-JAN-00:10 | 26867.76 | 02-JAN-09:00 |
Heating:EnergyTransfer | 0.54 | 0.00 | 01-JAN-00:10 | 1939.42 | 25-SEP-04:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.54 | 0.00 | 01-JAN-00:10 | 1939.42 | 25-SEP-04:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 2008.92 | 0.00 | 01-JAN-00:10 | 173886.37 | 21-FEB-15:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 348.55 | 0.00 | 01-JAN-00:10 | 26867.76 | 02-JAN-09:00 |
General:Cooling:EnergyTransfer | 2008.92 | 0.00 | 01-JAN-00:10 | 173886.37 | 21-FEB-15:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 348.55 | 0.00 | 01-JAN-00:10 | 26867.76 | 02-JAN-09:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.05 | 0.00 | 01-JAN-00:10 | 10960.84 | 05-MAY-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.17 | 0.00 | 01-JAN-00:10 | 1396.88 | 23-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.17 | 0.00 | 01-JAN-00:10 | 1396.88 | 23-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.88 | 0.00 | 01-JAN-00:10 | 10960.84 | 05-MAY-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.88 | 0.00 | 01-JAN-00:10 | 10960.84 | 05-MAY-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.60 | 0.00 | 01-JAN-00:10 | 5390.88 | 21-FEB-16:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.12 | 0.00 | 01-JAN-00:10 | 646.67 | 17-DEC-10:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.12 | 0.00 | 01-JAN-00:10 | 646.67 | 17-DEC-10:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.48 | 0.00 | 01-JAN-00:10 | 5390.88 | 21-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 51.48 | 0.00 | 01-JAN-00:10 | 5390.88 | 21-FEB-16:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.34 | 0.00 | 01-JAN-00:10 | 5766.86 | 30-MAY-11:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.25 | 0.00 | 01-JAN-00:10 | 933.58 | 17-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.25 | 0.00 | 01-JAN-00:10 | 933.58 | 17-AUG-04:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.09 | 0.00 | 01-JAN-00:10 | 5766.86 | 30-MAY-11:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.09 | 0.00 | 01-JAN-00:10 | 5766.86 | 30-MAY-11:00 |
EnergyTransfer:Zone:CORE_MID | 258.79 | 0.00 | 01-JAN-00:10 | 20488.98 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 258.79 | 0.00 | 01-JAN-00:10 | 20488.98 | 02-JAN-08:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 258.79 | 0.00 | 01-JAN-00:10 | 20488.98 | 02-JAN-08:40 |
EnergyTransfer:Zone:CORE_TOP | 273.07 | 0.00 | 01-JAN-00:10 | 21967.86 | 21-FEB-14:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 273.07 | 0.00 | 01-JAN-00:10 | 21967.86 | 21-FEB-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 273.07 | 0.00 | 01-JAN-00:10 | 21967.86 | 21-FEB-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 84.87 | 0.00 | 01-JAN-00:10 | 9505.60 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 84.87 | 0.00 | 01-JAN-00:10 | 9505.60 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 84.87 | 0.00 | 01-JAN-00:10 | 9505.60 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.91 | 0.00 | 01-JAN-00:10 | 7565.31 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.91 | 0.00 | 01-JAN-00:10 | 7565.31 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.91 | 0.00 | 01-JAN-00:10 | 7565.31 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.10 | 0.00 | 01-JAN-00:10 | 10445.11 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.10 | 0.00 | 01-JAN-00:10 | 10445.11 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.10 | 0.00 | 01-JAN-00:10 | 10445.11 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.12 | 0.00 | 01-JAN-00:10 | 8307.97 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.12 | 0.00 | 01-JAN-00:10 | 8307.97 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 66.12 | 0.00 | 01-JAN-00:10 | 8307.97 | 11-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.09 | 0.00 | 01-JAN-00:10 | 8847.39 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.09 | 0.00 | 01-JAN-00:10 | 8847.39 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.09 | 0.00 | 01-JAN-00:10 | 8847.39 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.74 | 0.00 | 01-JAN-00:10 | 7035.19 | 20-MAR-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.74 | 0.00 | 01-JAN-00:10 | 7035.19 | 20-MAR-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.74 | 0.00 | 01-JAN-00:10 | 7035.19 | 20-MAR-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.96 | 0.00 | 01-JAN-00:10 | 11578.89 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.96 | 0.00 | 01-JAN-00:10 | 11578.89 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 111.96 | 0.00 | 01-JAN-00:10 | 11578.89 | 05-MAY-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.92 | 0.00 | 01-JAN-00:10 | 7400.60 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.92 | 0.00 | 01-JAN-00:10 | 7400.60 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 65.92 | 0.00 | 01-JAN-00:10 | 7400.60 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.38 | 0.00 | 01-JAN-00:10 | 8706.31 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.38 | 0.00 | 01-JAN-00:10 | 8706.31 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 80.38 | 0.00 | 01-JAN-00:10 | 8706.31 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.68 | 0.00 | 01-JAN-00:10 | 7209.75 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.68 | 0.00 | 01-JAN-00:10 | 7209.75 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 61.68 | 0.00 | 01-JAN-00:10 | 7209.75 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.14 | 0.00 | 01-JAN-00:10 | 9314.18 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.14 | 0.00 | 01-JAN-00:10 | 9314.18 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 88.14 | 0.00 | 01-JAN-00:10 | 9314.18 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.15 | 0.00 | 01-JAN-00:10 | 7697.93 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.15 | 0.00 | 01-JAN-00:10 | 7697.93 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 62.15 | 0.00 | 01-JAN-00:10 | 7697.93 | 18-APR-15:30 |
PlantLoopHeatingDemand:Facility | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 3866.52 | 0.00 | 01-JAN-00:10 | 331078.15 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3866.52 | 0.00 | 01-JAN-00:10 | 331078.15 | 13-JUN-15:40 |
EnergyTransfer:Plant | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
WaterSystems:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -348.549 | 0.000 | 0.000 | 32.660 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -6.463 |
CORE_MID | 0.000 | 0.000 | 0.000 | -258.791 | 0.000 | 0.000 | 32.738 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 38.699 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -273.066 | 0.000 | 0.000 | 32.760 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 52.952 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -84.867 | 0.000 | 0.000 | 6.890 | 8.581 | 24.333 | 37.782 | 0.000 | 0.458 | 10.520 | 0.000 | -3.622 | 0.000 | -0.075 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -65.913 | 0.000 | 0.000 | 4.361 | 5.468 | 15.404 | 37.597 | 0.000 | 0.304 | 5.151 | 0.000 | -2.320 | 0.000 | -0.052 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -93.101 | 0.000 | 0.000 | 6.882 | 8.537 | 24.332 | 48.498 | 0.000 | 0.453 | 8.086 | 0.000 | -3.608 | 0.000 | -0.081 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -66.115 | 0.000 | 0.000 | 4.373 | 5.404 | 15.403 | 37.733 | 0.000 | 0.306 | 5.461 | 0.000 | -2.512 | 0.000 | -0.054 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -86.090 | 0.000 | 0.000 | 6.886 | 8.561 | 24.333 | 37.901 | 0.000 | 0.251 | 12.146 | 0.000 | -3.944 | 0.000 | -0.043 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -66.737 | 0.000 | 0.000 | 4.356 | 5.456 | 15.404 | 37.659 | 0.000 | 0.162 | 6.407 | 0.000 | -2.676 | 0.000 | -0.032 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -111.959 | 0.000 | 0.000 | 6.766 | 8.523 | 24.332 | 48.224 | 0.000 | 21.209 | 7.436 | 0.000 | -4.169 | 0.000 | -0.362 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -65.924 | 0.000 | 0.000 | 4.358 | 5.393 | 15.403 | 37.737 | 0.000 | 0.160 | 5.819 | 0.000 | -2.913 | 0.000 | -0.033 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -80.377 | 0.000 | 0.000 | 6.887 | 8.581 | 24.333 | 38.075 | 0.000 | 0.389 | 5.924 | 0.000 | -3.746 | 0.000 | -0.066 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -61.676 | 0.000 | 0.000 | 3.215 | 5.467 | 15.404 | 37.814 | 0.000 | 0.257 | 1.962 | 0.000 | -2.398 | 0.000 | -0.045 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -88.133 | 0.000 | 0.000 | 6.874 | 8.537 | 24.332 | 48.790 | 0.000 | 0.383 | 3.015 | 0.000 | -3.728 | 0.000 | -0.071 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -62.145 | 0.000 | 0.000 | 4.365 | 5.404 | 15.403 | 37.897 | 0.000 | 0.254 | 1.489 | 0.000 | -2.620 | 0.000 | -0.047 | -0.000 |
TOPFLOOR_PLENUM | 0.172 | -84.880 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.565 | 84.229 | 0.000 | 0.000 | 0.000 | -0.086 | 0.000 |
MIDFLOOR_PLENUM | 0.116 | -51.482 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.585 | 50.880 | 0.000 | 0.000 | 0.000 | -0.098 | 0.000 |
FIRSTFLOOR_PLENUM | 0.253 | -59.087 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.444 | 58.472 | 0.000 | 0.000 | 0.000 | -0.083 | -0.000 |
Total Facility | 0.540 | -195.449 | 0.000 | -1813.443 | 0.000 | 0.000 | 164.370 | 299.699 | 719.689 | 485.708 | 0.000 | 26.181 | 358.652 | 0.000 | -38.254 | 0.000 | -1.228 | -6.469 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | -43726.06 | 0.00 | 0.00 | 289.14 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 35814.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -35283.91 | 0.00 | 0.00 | 292.68 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 31753.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -37675.19 | 0.00 | 0.00 | 298.96 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 34138.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-12:02 | 0.00 | 0.00 | 0.00 | -12975.64 | 0.00 | 0.00 | 25.38 | 36.00 | 478.42 | 4455.20 | 0.00 | 132.00 | 7848.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 26-MAR-09:22 | 0.00 | 0.00 | 0.00 | -12182.74 | 0.00 | 0.00 | 14.95 | 22.79 | 302.86 | 6073.32 | 0.00 | 48.86 | 5719.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-12:22 | 0.00 | 0.00 | 0.00 | -13278.87 | 0.00 | 0.00 | 24.20 | 36.00 | 478.41 | 7631.90 | 0.00 | 34.04 | 5074.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-JAN-16:42 | 0.00 | 0.00 | 0.00 | -13540.43 | 0.00 | 0.00 | 14.96 | 22.79 | 302.86 | 4468.41 | 0.00 | 29.12 | 8702.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-12:02 | 0.00 | 0.00 | 0.00 | -11101.87 | 0.00 | 0.00 | 26.80 | 36.00 | 478.42 | 4554.11 | 0.00 | 74.37 | 5932.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 26-MAR-09:22 | 0.00 | 0.00 | 0.00 | -10834.65 | 0.00 | 0.00 | 15.90 | 22.79 | 302.86 | 6177.61 | 0.00 | 28.33 | 4287.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 05-MAY-12:00 | 0.00 | 0.00 | 0.00 | -11578.19 | 0.00 | 0.00 | 286.85 | 647.98 | 1275.77 | 3336.23 | 0.00 | 10821.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4789.92 |
PERIMETER_BOT_ZN_4 | 04-JUL-17:02 | 0.00 | 0.00 | 0.00 | -11636.45 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 4784.95 | 0.00 | 12.79 | 6571.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 | -11242.04 | 0.00 | 0.00 | 27.09 | 36.00 | 478.42 | 3172.28 | 0.00 | 57.61 | 7470.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 26-MAR-09:22 | 0.00 | 0.00 | 0.00 | -11648.90 | 0.00 | 0.00 | 15.27 | 22.79 | 302.86 | 6107.62 | 0.00 | 41.92 | 5158.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 16-JAN-12:02 | 0.00 | 0.00 | 0.00 | -11742.18 | 0.00 | 0.00 | 24.28 | 36.00 | 478.41 | 8367.11 | 0.00 | 10.24 | 2826.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 | -12725.70 | 0.00 | 0.00 | 14.62 | 22.79 | 302.86 | 5646.92 | 0.00 | 28.71 | 6709.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 05-MAY-13:30 | 0.00 | -10960.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 10885.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 21-FEB-16:10 | 0.00 | -5390.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.88 | 5339.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:10 | 0.00 | -5949.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 5940.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-MAR-04:02 | 0.00 | 9073.23 | 0.00 | -207354.77 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 214.89 | 183379.66 | 0.00 | -1955.89 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 06-FEB-06:02 | 5181.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5181.78 |
MIDFLOOR_PLENUM | 02-AUG-04:02 | 2549.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2597.54 |
FIRSTFLOOR_PLENUM | 02-AUG-04:02 | 4288.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4323.73 |
Total Facility | 25-SEP-04:02 | -189749.32 | 199445.92 | 0.00 | -199445.92 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 7.21 | 176132.93 | 0.00 | -3030.50 | 0.00 | -3.20 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1429 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7325 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.7375 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2680 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1616 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9563 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5715 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3430 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3688 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3285 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5808 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3920 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6433 | 2.6433 | 0.7692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1412 | 2.1412 | 0.7473 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2836 | 2.2836 | 0.7787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7362 | 0.7362 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6617 | 0.6617 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7169 | 0.7169 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7632 | 0.7632 | 0.1526 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6353 | 0.6353 | 0.1620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6010 | 0.6010 | 0.1202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6172 | 0.6172 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6460 | 0.6460 | 0.1292 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6417 | 0.6417 | 0.1578 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6376 | 0.6376 | 0.1275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6244 | 0.6244 | 0.1573 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6927 | 0.6927 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1429 | 4.7325 | 5.1429 | 1.3430 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.7375 | 4.2680 | 4.7375 | 1.3285 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1616 | 4.9563 | 5.1616 | 1.3920 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3216 | 1.3216 | 0.7692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0706 | 1.0706 | 0.7473 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1418 | 1.1418 | 0.7787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3681 | 0.3681 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3309 | 0.3309 | 0.1323 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3584 | 0.3584 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3816 | 0.3816 | 0.1526 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3177 | 0.3177 | 0.1620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3005 | 0.3005 | 0.1202 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3086 | 0.3086 | 0.1623 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3230 | 0.3230 | 0.1292 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3208 | 0.3208 | 0.1578 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3188 | 0.3188 | 0.1275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3122 | 0.3122 | 0.1573 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3464 | 0.3464 | 0.1385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5715 | 1.3430 | 1.3430 | 1.3430 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3688 | 1.3285 | 1.3285 | 1.3285 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5808 | 1.3920 | 1.3920 | 1.3920 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4982.19 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 805.50 |
Number of hours not met | 805.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 899.70 | 90068.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 299.70 | 31270.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.51 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.91 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 121.50 | 16327.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 35.65 | 4202.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 2152.80 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2152.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.15 |
Space Heating | 0.00 |
Space Cooling | 180.58 |
Fans (All) | 24.39 |
Service Water Heating | 7.16 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 432.10 |
Subtotal | 432.10 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.92 |
Space Heating | 0.00 |
Space Cooling | 41.79 |
Fans (All) | 5.64 |
Service Water Heating | 1.66 |
Receptacle Equipment | 33.43 |
Miscellaneous | 3.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 6835.00 | 1925.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8675.50 | 84.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8688.17 | 71.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8155.67 | 604.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8051.00 | 709.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8014.50 | 745.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7899.33 | 860.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8406.83 | 353.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8079.83 | 680.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8080.17 | 679.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7748.83 | 1011.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8281.00 | 479.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8129.67 | 630.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8094.33 | 665.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7895.83 | 864.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8158.83 | 601.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
Min | 6835.00 | 31.83 | 0.00 | 0.00 | 0.00 |
Max | 8728.17 | 1925.00 | 0.00 | 0.00 | 0.00 |
Average | 8146.99 | 613.01 | 0.00 | 0.00 | 0.00 |
Sum | 146645.83 | 11034.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127753.33 | 550.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128293.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128296.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24636.83 | 272.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128296.67 | 550.67 | 0.00 | 0.00 | 0.00 |
Average | 34096.64 | 46.69 | 0.00 | 0.00 | 0.00 |
Sum | 613739.50 | 840.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6392.17 | 2367.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8465.33 | 294.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8512.83 | 247.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5558.83 | 3201.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5576.67 | 3183.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5420.83 | 3339.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5702.50 | 3057.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6092.33 | 2667.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5765.67 | 2994.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 3919.00 | 4841.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5779.33 | 2980.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5572.67 | 3187.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5560.00 | 3200.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5367.50 | 3392.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5581.17 | 3178.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6442.83 | 2317.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6762.00 | 1998.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7066.33 | 1693.67 | 0.00 | 0.00 | 0.00 |
Min | 3919.00 | 247.17 | 0.00 | 0.00 | 0.00 |
Max | 8512.83 | 4841.00 | 0.00 | 0.00 | 0.00 |
Average | 6085.44 | 2674.56 | 0.00 | 0.00 | 0.00 |
Sum | 109538.00 | 48142.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127512.00 | 792.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128255.00 | 49.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128266.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24863.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24863.83 | 45.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24905.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16345.33 | 8563.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24876.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24876.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128266.33 | 8563.67 | 0.00 | 0.00 | 0.00 |
Average | 33609.86 | 533.47 | 0.00 | 0.00 | 0.00 |
Sum | 604977.50 | 9602.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293063E+11 | 41050.26 | 03-JAN-05:02 | 24.93 | 22.82 | 0.199610E+10 | 2606.54 | 02-JAN-14:09 | 24.93 | 22.82 |
February | 0.267003E+11 | 41662.80 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180989E+10 | 2606.54 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.307394E+11 | 41130.02 | 08-MAR-05:03 | 24.00 | 22.62 | 0.216012E+10 | 2606.54 | 03-MAR-10:09 | 24.00 | 22.62 |
April | 0.287841E+11 | 40821.54 | 22-APR-04:03 | 24.58 | 23.40 | 0.191788E+10 | 2606.55 | 20-APR-13:09 | 24.58 | 23.40 |
May | 0.306287E+11 | 40916.84 | 26-MAY-04:03 | 24.00 | 23.90 | 0.207729E+10 | 2606.54 | 01-MAY-13:09 | 24.00 | 23.90 |
June | 0.302978E+11 | 40561.01 | 03-JUN-04:03 | 25.42 | 25.21 | 0.207110E+10 | 2606.55 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.288358E+11 | 40941.83 | 19-JUL-04:03 | 24.42 | 23.71 | 0.192525E+10 | 2606.54 | 10-JUL-13:09 | 24.42 | 23.71 |
August | 0.302290E+11 | 41618.63 | 21-AUG-04:02 | 24.17 | 23.75 | 0.216086E+10 | 2606.54 | 17-AUG-13:09 | 24.17 | 23.75 |
September | 0.281576E+11 | 43730.63 | 19-SEP-05:03 | 24.00 | 24.00 | 0.191806E+10 | 2606.54 | 14-SEP-13:09 | 24.00 | 24.00 |
October | 0.287379E+11 | 41239.15 | 24-OCT-04:02 | 24.08 | 24.04 | 0.199529E+10 | 2606.54 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.281383E+11 | 41020.41 | 07-NOV-05:02 | 24.00 | 23.42 | 0.197596E+10 | 2606.54 | 08-NOV-14:09 | 31.00 | 25.90 |
December | 0.279934E+11 | 40716.48 | 30-DEC-05:03 | 24.00 | 24.00 | 0.192598E+10 | 2606.54 | 04-DEC-14:09 | 24.00 | 24.00 |
Annual Sum or Average | 0.348549E+12 | 0.239338E+11 | ||||||||
Minimum of Months | 0.267003E+11 | 40561.01 | 23.95 | 22.59 | 0.180989E+10 | 2606.54 | 23.53 | 20.42 | ||
Maximum of Months | 0.307394E+11 | 43730.63 | 25.42 | 25.21 | 0.216086E+10 | 2606.55 | 36.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685607E+10 | 9835.57 | 04-JAN-14:10 | 33.83 | 23.50 | 0.00 | 0.00 | 01-JAN-00:10 | 33.83 | 23.50 |
February | 0.682219E+10 | 10868.84 | 21-FEB-14:40 | 34.33 | 21.86 | 0.00 | 0.00 | 01-FEB-00:10 | 34.33 | 21.86 |
March | 0.823255E+10 | 10925.29 | 21-MAR-14:00 | 36.00 | 23.97 | 0.00 | 0.00 | 01-MAR-00:10 | 36.00 | 23.97 |
April | 0.789686E+10 | 10214.80 | 11-APR-14:30 | 34.85 | 26.00 | 0.00 | 0.00 | 01-APR-00:10 | 34.85 | 26.00 |
May | 0.792191E+10 | 10960.84 | 05-MAY-13:30 | 36.20 | 27.12 | 0.00 | 0.00 | 01-MAY-00:10 | 36.20 | 27.12 |
June | 0.830685E+10 | 10772.11 | 16-JUN-14:00 | 36.00 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 27.59 |
July | 0.676456E+10 | 9423.60 | 14-JUL-14:30 | 32.25 | 24.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.25 | 24.82 |
August | 0.685191E+10 | 9988.34 | 14-AUG-13:50 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.659582E+10 | 9956.36 | 06-SEP-14:00 | 34.00 | 26.51 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 26.51 |
October | 0.605118E+10 | 9500.72 | 04-OCT-13:50 | 32.88 | 26.26 | 0.00 | 0.00 | 01-OCT-00:10 | 32.88 | 26.26 |
November | 0.626025E+10 | 9425.11 | 22-NOV-13:02 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.632051E+10 | 9692.83 | 26-DEC-13:02 | 32.00 | 23.12 | 0.00 | 0.00 | 01-DEC-00:10 | 32.00 | 23.12 |
Annual Sum or Average | 0.848807E+11 | 0.00 | ||||||||
Minimum of Months | 0.605118E+10 | 9423.60 | 31.50 | 21.86 | 0.00 | 0.00 | 31.50 | 21.86 | ||
Maximum of Months | 0.830685E+10 | 10960.84 | 36.20 | 27.67 | 0.00 | 0.00 | 36.20 | 27.67 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425715E+10 | 5007.80 | 02-JAN-07:03 | 23.85 | 23.26 | 0.00 | 0.00 | 01-JAN-00:10 | 23.85 | 23.26 |
February | 0.407124E+10 | 5390.88 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.474339E+10 | 5182.40 | 20-MAR-15:20 | 34.77 | 24.85 | 0.00 | 0.00 | 01-MAR-00:10 | 34.77 | 24.85 |
April | 0.449881E+10 | 4798.87 | 17-APR-15:40 | 32.90 | 26.39 | 0.00 | 0.00 | 01-APR-00:10 | 32.90 | 26.39 |
May | 0.478451E+10 | 5328.93 | 30-MAY-12:02 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.496744E+10 | 5383.93 | 12-JUN-16:00 | 35.40 | 27.71 | 0.00 | 0.00 | 01-JUN-00:10 | 35.40 | 27.71 |
July | 0.416016E+10 | 4579.55 | 17-JUL-14:10 | 31.67 | 26.15 | 0.00 | 0.00 | 01-JUL-00:10 | 31.67 | 26.15 |
August | 0.424529E+10 | 4772.09 | 14-AUG-14:50 | 32.17 | 28.09 | 0.00 | 0.00 | 01-AUG-00:10 | 32.17 | 28.09 |
September | 0.399689E+10 | 4904.89 | 05-SEP-06:03 | 26.10 | 25.95 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 25.95 |
October | 0.393221E+10 | 4873.05 | 10-OCT-14:30 | 30.50 | 26.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.50 | 26.20 |
November | 0.397158E+10 | 4992.28 | 13-NOV-13:02 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.385438E+10 | 5054.16 | 26-DEC-16:00 | 30.20 | 22.54 | 0.00 | 0.00 | 01-DEC-00:10 | 30.20 | 22.54 |
Annual Sum or Average | 0.514830E+11 | 0.00 | ||||||||
Minimum of Months | 0.385438E+10 | 4579.55 | 23.85 | 22.54 | 0.00 | 0.00 | 23.85 | 22.54 | ||
Maximum of Months | 0.496744E+10 | 5390.88 | 35.40 | 28.09 | 0.00 | 0.00 | 35.40 | 28.09 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491706E+10 | 5323.15 | 17-JAN-16:00 | 29.90 | 22.65 | 0.00 | 0.00 | 01-JAN-00:10 | 29.90 | 22.65 |
February | 0.461776E+10 | 5660.54 | 21-FEB-16:10 | 31.80 | 23.94 | 0.00 | 0.00 | 01-FEB-00:10 | 31.80 | 23.94 |
March | 0.534276E+10 | 5459.20 | 20-MAR-16:00 | 34.30 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.30 | 24.91 |
April | 0.504141E+10 | 5296.21 | 17-APR-15:40 | 32.90 | 26.39 | 0.00 | 0.00 | 01-APR-00:10 | 32.90 | 26.39 |
May | 0.539300E+10 | 5950.52 | 30-MAY-12:10 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.562120E+10 | 5745.65 | 12-JUN-16:00 | 35.40 | 27.71 | 0.00 | 0.00 | 01-JUN-00:10 | 35.40 | 27.71 |
July | 0.482366E+10 | 5217.63 | 17-JUL-14:10 | 31.67 | 26.15 | 0.00 | 0.00 | 01-JUL-00:10 | 31.67 | 26.15 |
August | 0.497419E+10 | 5312.54 | 14-AUG-12:08 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.462492E+10 | 5466.94 | 05-SEP-12:10 | 33.02 | 26.93 | 0.00 | 0.00 | 01-SEP-00:10 | 33.02 | 26.93 |
October | 0.455916E+10 | 5312.75 | 10-OCT-15:10 | 29.17 | 26.02 | 0.00 | 0.00 | 01-OCT-00:10 | 29.17 | 26.02 |
November | 0.462247E+10 | 5335.39 | 13-NOV-13:10 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.454989E+10 | 5344.32 | 26-DEC-16:00 | 30.20 | 22.54 | 0.00 | 0.00 | 01-DEC-00:10 | 30.20 | 22.54 |
Annual Sum or Average | 0.590875E+11 | 0.00 | ||||||||
Minimum of Months | 0.454989E+10 | 5217.63 | 29.17 | 22.54 | 0.00 | 0.00 | 29.17 | 22.54 | ||
Maximum of Months | 0.562120E+10 | 5950.52 | 35.40 | 27.71 | 0.00 | 0.00 | 35.40 | 27.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214612E+11 | 32631.94 | 10-JAN-05:02 | 23.95 | 22.91 | 0.198928E+10 | 2606.55 | 24-JAN-10:09 | 20.83 | 18.11 |
February | 0.198080E+11 | 35286.36 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180410E+10 | 2606.53 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.230517E+11 | 32795.49 | 07-MAR-05:02 | 24.00 | 22.62 | 0.215441E+10 | 2606.54 | 03-MAR-10:09 | 24.00 | 22.62 |
April | 0.217132E+11 | 32033.02 | 05-APR-04:02 | 26.08 | 23.61 | 0.191236E+10 | 2606.54 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.230939E+11 | 32429.39 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207210E+10 | 2606.54 | 01-MAY-13:09 | 24.17 | 24.17 |
June | 0.228428E+11 | 32527.23 | 01-JUN-04:02 | 24.17 | 24.06 | 0.206629E+10 | 2606.54 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.213893E+11 | 32816.87 | 18-JUL-04:22 | 24.00 | 23.32 | 0.191815E+10 | 2606.53 | 10-JUL-13:09 | 24.00 | 23.32 |
August | 0.223033E+11 | 32393.81 | 21-AUG-04:02 | 24.17 | 23.75 | 0.215385E+10 | 2606.54 | 03-AUG-13:00 | 24.17 | 23.75 |
September | 0.208730E+11 | 32466.21 | 13-SEP-04:02 | 24.42 | 24.11 | 0.191129E+10 | 2606.54 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.211465E+11 | 32915.97 | 11-OCT-04:02 | 24.00 | 23.26 | 0.198778E+10 | 2606.54 | 30-OCT-13:09 | 24.42 | 24.31 |
November | 0.206791E+11 | 32911.04 | 07-NOV-05:02 | 24.00 | 23.42 | 0.196926E+10 | 2606.54 | 08-NOV-14:09 | 31.00 | 25.90 |
December | 0.204286E+11 | 31019.82 | 26-DEC-06:12 | 22.33 | 21.42 | 0.191754E+10 | 2606.55 | 21-DEC-10:09 | 22.33 | 21.42 |
Annual Sum or Average | 0.258791E+12 | 0.238564E+11 | ||||||||
Minimum of Months | 0.198080E+11 | 31019.82 | 22.33 | 21.42 | 0.180410E+10 | 2606.53 | 20.83 | 18.11 | ||
Maximum of Months | 0.230939E+11 | 35286.36 | 26.08 | 24.17 | 0.215441E+10 | 2606.55 | 36.00 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222494E+11 | 34711.64 | 09-JAN-05:02 | 23.92 | 23.24 | 0.198559E+10 | 2606.63 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.207580E+11 | 37677.41 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180166E+10 | 2606.55 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.245517E+11 | 34537.20 | 21-MAR-04:02 | 25.58 | 22.99 | 0.215304E+10 | 2606.55 | 03-MAR-10:09 | 25.58 | 22.99 |
April | 0.234856E+11 | 34826.82 | 10-APR-04:02 | 25.17 | 23.75 | 0.191232E+10 | 2606.54 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.246985E+11 | 34960.32 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207169E+10 | 2606.54 | 25-MAY-13:09 | 31.17 | 27.76 |
June | 0.245676E+11 | 34705.01 | 26-JUN-04:02 | 24.00 | 23.59 | 0.206616E+10 | 2606.54 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.225850E+11 | 34618.72 | 06-JUL-04:02 | 25.17 | 23.75 | 0.191688E+10 | 2606.53 | 10-JUL-13:09 | 28.83 | 25.76 |
August | 0.234430E+11 | 35131.29 | 21-AUG-04:02 | 24.17 | 23.75 | 0.215178E+10 | 2606.54 | 17-AUG-13:00 | 24.17 | 23.75 |
September | 0.220585E+11 | 34423.70 | 14-SEP-04:02 | 25.50 | 24.23 | 0.191023E+10 | 2606.54 | 14-SEP-13:09 | 32.33 | 27.93 |
October | 0.219908E+11 | 35041.21 | 02-OCT-04:02 | 24.00 | 23.36 | 0.198570E+10 | 2606.55 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.215344E+11 | 34782.04 | 13-NOV-05:02 | 25.00 | 24.24 | 0.196640E+10 | 2606.55 | 16-NOV-14:09 | 29.85 | 25.47 |
December | 0.211433E+11 | 33576.59 | 26-DEC-06:12 | 22.33 | 21.42 | 0.191236E+10 | 2606.61 | 21-DEC-10:09 | 22.33 | 21.42 |
Annual Sum or Average | 0.273066E+12 | 0.238338E+11 | ||||||||
Minimum of Months | 0.207580E+11 | 33576.59 | 22.33 | 21.42 | 0.180166E+10 | 2606.53 | 22.33 | 19.15 | ||
Maximum of Months | 0.246985E+11 | 37677.41 | 25.58 | 24.24 | 0.215304E+10 | 2606.63 | 34.17 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.627215E+10 | 8526.42 | 02-JAN-06:12 | 23.37 | 23.04 | 0.419378E+09 | 549.49 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.606564E+10 | 10197.40 | 05-FEB-14:32 | 32.00 | 25.37 | 0.380885E+09 | 549.48 | 15-FEB-14:00 | 29.00 | 24.59 |
March | 0.744780E+10 | 12584.55 | 26-MAR-14:02 | 34.83 | 25.46 | 0.455030E+09 | 549.48 | 03-MAR-10:09 | 34.83 | 25.46 |
April | 0.743592E+10 | 12281.66 | 30-APR-12:53 | 33.70 | 26.84 | 0.404558E+09 | 549.48 | 20-APR-13:00 | 33.70 | 26.84 |
May | 0.854124E+10 | 12790.53 | 07-MAY-12:32 | 35.00 | 26.20 | 0.438358E+09 | 549.48 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.918559E+10 | 12975.46 | 18-JUN-12:02 | 33.23 | 27.06 | 0.437042E+09 | 549.48 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.757723E+10 | 12631.63 | 04-JUL-14:02 | 32.08 | 24.88 | 0.406026E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.739944E+10 | 12502.13 | 13-AUG-12:53 | 34.00 | 28.60 | 0.455115E+09 | 549.47 | 17-AUG-13:00 | 27.00 | 26.21 |
September | 0.665003E+10 | 12290.05 | 04-SEP-12:53 | 32.50 | 27.43 | 0.404155E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.629382E+10 | 10712.64 | 16-OCT-04:02 | 26.00 | 25.22 | 0.420089E+09 | 549.48 | 13-OCT-13:09 | 26.00 | 25.22 |
November | 0.612781E+10 | 11838.24 | 19-NOV-14:22 | 31.75 | 24.87 | 0.415781E+09 | 549.48 | 08-NOV-14:09 | 31.75 | 24.87 |
December | 0.587235E+10 | 6764.32 | 26-DEC-14:10 | 31.17 | 22.67 | 0.404108E+09 | 549.48 | 21-DEC-10:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.848690E+11 | 0.504052E+10 | ||||||||
Minimum of Months | 0.587235E+10 | 6764.32 | 23.37 | 22.67 | 0.380885E+09 | 549.47 | 23.70 | 19.15 | ||
Maximum of Months | 0.918559E+10 | 12975.46 | 35.00 | 28.60 | 0.455115E+09 | 549.49 | 34.83 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514336E+10 | 10037.31 | 16-JAN-11:02 | 29.63 | 21.29 | 0.265976E+09 | 347.88 | 24-JAN-10:30 | 23.70 | 19.15 |
February | 0.510061E+10 | 11530.39 | 20-FEB-09:13 | 28.47 | 23.42 | 0.241496E+09 | 347.86 | 24-FEB-10:09 | 28.50 | 22.00 |
March | 0.631359E+10 | 12181.84 | 26-MAR-09:22 | 31.90 | 24.91 | 0.288238E+09 | 347.86 | 03-MAR-10:20 | 31.90 | 24.91 |
April | 0.617214E+10 | 11508.01 | 09-APR-08:13 | 29.27 | 25.57 | 0.256250E+09 | 347.86 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.614342E+10 | 12005.09 | 29-MAY-09:02 | 31.17 | 27.92 | 0.277347E+09 | 347.86 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.627458E+10 | 11249.16 | 11-JUN-11:53 | 34.00 | 27.86 | 0.276496E+09 | 347.86 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.527602E+10 | 8753.10 | 04-JUL-14:02 | 32.08 | 24.88 | 0.256770E+09 | 347.86 | 17-JUL-13:00 | 32.00 | 26.09 |
August | 0.566287E+10 | 11556.17 | 13-AUG-08:53 | 31.00 | 27.87 | 0.288006E+09 | 347.86 | 17-AUG-13:00 | 27.00 | 26.21 |
September | 0.527363E+10 | 11564.05 | 10-SEP-09:23 | 30.30 | 26.10 | 0.255896E+09 | 347.86 | 07-SEP-13:00 | 30.30 | 26.10 |
October | 0.496439E+10 | 11512.15 | 08-OCT-09:53 | 30.50 | 26.45 | 0.265926E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.483293E+10 | 9561.91 | 05-NOV-11:13 | 30.67 | 23.05 | 0.263361E+09 | 347.86 | 13-NOV-10:20 | 26.97 | 24.85 |
December | 0.475671E+10 | 8280.70 | 03-DEC-11:13 | 31.00 | 22.63 | 0.256389E+09 | 347.87 | 21-DEC-10:09 | 26.17 | 20.56 |
Annual Sum or Average | 0.659143E+11 | 0.319215E+10 | ||||||||
Minimum of Months | 0.475671E+10 | 8280.70 | 28.47 | 21.29 | 0.241496E+09 | 347.86 | 23.70 | 19.15 | ||
Maximum of Months | 0.631359E+10 | 12181.84 | 34.00 | 27.92 | 0.288238E+09 | 347.88 | 34.50 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.907478E+10 | 12961.67 | 29-JAN-12:02 | 30.08 | 23.23 | 0.422128E+09 | 577.76 | 04-JAN-14:09 | 30.08 | 23.23 |
February | 0.816912E+10 | 12793.14 | 26-FEB-12:13 | 32.83 | 24.74 | 0.382192E+09 | 573.13 | 21-FEB-14:20 | 32.83 | 24.74 |
March | 0.850746E+10 | 12745.10 | 26-MAR-14:02 | 34.83 | 25.46 | 0.455337E+09 | 549.48 | 06-MAR-14:00 | 34.83 | 25.46 |
April | 0.732241E+10 | 11949.01 | 02-APR-15:42 | 33.75 | 27.23 | 0.404502E+09 | 549.48 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.772777E+10 | 12124.29 | 07-MAY-12:32 | 35.00 | 26.20 | 0.438036E+09 | 549.47 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.765611E+10 | 12037.50 | 18-JUN-12:02 | 33.23 | 27.06 | 0.436658E+09 | 549.48 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.673129E+10 | 11948.56 | 04-JUL-14:02 | 32.08 | 24.88 | 0.405598E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.700233E+10 | 11724.61 | 13-AUG-12:53 | 34.00 | 28.60 | 0.454921E+09 | 549.47 | 17-AUG-13:00 | 27.00 | 26.21 |
September | 0.694053E+10 | 12151.77 | 04-SEP-12:53 | 32.50 | 27.43 | 0.404244E+09 | 549.47 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.733825E+10 | 12774.89 | 29-OCT-11:43 | 31.50 | 26.00 | 0.420555E+09 | 549.48 | 13-OCT-13:09 | 31.50 | 26.00 |
November | 0.803488E+10 | 13279.38 | 19-NOV-12:22 | 32.40 | 24.66 | 0.416674E+09 | 549.48 | 22-NOV-14:00 | 31.50 | 24.56 |
December | 0.859810E+10 | 12972.70 | 03-DEC-11:13 | 31.00 | 22.63 | 0.407528E+09 | 581.40 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.931030E+11 | 0.504837E+10 | ||||||||
Minimum of Months | 0.673129E+10 | 11724.61 | 30.08 | 22.63 | 0.382192E+09 | 549.47 | 25.00 | 22.67 | ||
Maximum of Months | 0.907478E+10 | 13279.38 | 35.00 | 28.60 | 0.455337E+09 | 581.40 | 34.83 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525338E+10 | 13541.86 | 29-JAN-16:42 | 31.22 | 23.22 | 0.264336E+09 | 347.84 | 24-JAN-10:00 | 31.22 | 23.22 |
February | 0.515959E+10 | 13064.43 | 26-FEB-15:32 | 34.40 | 24.93 | 0.240259E+09 | 347.84 | 15-FEB-14:00 | 34.40 | 24.93 |
March | 0.638400E+10 | 13521.66 | 05-MAR-16:42 | 28.37 | 23.27 | 0.287359E+09 | 347.84 | 03-MAR-10:09 | 28.37 | 23.27 |
April | 0.615489E+10 | 13430.47 | 02-APR-15:42 | 33.75 | 27.23 | 0.255625E+09 | 347.84 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.610056E+10 | 13023.32 | 14-MAY-15:42 | 34.83 | 27.45 | 0.276657E+09 | 347.84 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.618154E+10 | 13068.96 | 11-JUN-16:32 | 33.50 | 27.84 | 0.275944E+09 | 347.84 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.527351E+10 | 13098.07 | 04-JUL-16:02 | 31.17 | 25.29 | 0.255769E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.558358E+10 | 13074.65 | 27-AUG-16:12 | 32.67 | 25.94 | 0.287078E+09 | 347.84 | 15-AUG-13:00 | 32.67 | 25.94 |
September | 0.523034E+10 | 13148.33 | 04-SEP-16:12 | 32.67 | 26.80 | 0.254984E+09 | 347.84 | 07-SEP-13:00 | 32.00 | 27.49 |
October | 0.500204E+10 | 12005.19 | 15-OCT-17:03 | 28.42 | 25.82 | 0.264757E+09 | 347.84 | 13-OCT-13:00 | 28.42 | 25.82 |
November | 0.490980E+10 | 13398.21 | 19-NOV-14:22 | 31.75 | 24.87 | 0.262249E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.488389E+10 | 12170.98 | 03-DEC-16:33 | 28.83 | 22.68 | 0.254421E+09 | 347.84 | 08-DEC-14:00 | 33.00 | 23.65 |
Annual Sum or Average | 0.661171E+11 | 0.317944E+10 | ||||||||
Minimum of Months | 0.488389E+10 | 12005.19 | 28.37 | 22.68 | 0.240259E+09 | 347.84 | 25.00 | 23.22 | ||
Maximum of Months | 0.638400E+10 | 13541.86 | 34.83 | 27.84 | 0.287359E+09 | 347.84 | 34.50 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.638489E+10 | 7578.79 | 02-JAN-07:03 | 23.85 | 23.26 | 0.420070E+09 | 549.47 | 09-JAN-14:00 | 31.00 | 24.49 |
February | 0.607308E+10 | 8329.81 | 06-FEB-06:02 | 23.95 | 22.59 | 0.381246E+09 | 549.48 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.725410E+10 | 8675.42 | 28-MAR-04:02 | 27.25 | 25.19 | 0.455112E+09 | 549.48 | 03-MAR-10:09 | 27.25 | 25.19 |
April | 0.725322E+10 | 10591.82 | 30-APR-16:02 | 32.17 | 27.26 | 0.404486E+09 | 549.48 | 20-APR-13:09 | 32.17 | 27.26 |
May | 0.855779E+10 | 10982.75 | 29-MAY-11:53 | 35.00 | 28.17 | 0.438493E+09 | 549.48 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.925427E+10 | 11102.04 | 18-JUN-12:02 | 33.23 | 27.06 | 0.437326E+09 | 553.38 | 12-JUN-13:00 | 33.23 | 27.06 |
July | 0.791841E+10 | 10976.02 | 04-JUL-17:02 | 29.13 | 25.16 | 0.406374E+09 | 549.48 | 17-JUL-13:00 | 32.00 | 26.09 |
August | 0.771119E+10 | 9172.03 | 13-AUG-12:53 | 34.00 | 28.60 | 0.455523E+09 | 549.47 | 15-AUG-13:00 | 27.00 | 27.00 |
September | 0.687174E+10 | 8990.06 | 08-SEP-04:02 | 26.75 | 24.48 | 0.404413E+09 | 549.47 | 07-SEP-13:00 | 26.75 | 24.48 |
October | 0.648386E+10 | 8844.81 | 16-OCT-04:02 | 26.00 | 25.22 | 0.420442E+09 | 549.47 | 30-OCT-13:00 | 24.00 | 24.00 |
November | 0.630125E+10 | 7768.53 | 13-NOV-07:03 | 26.08 | 24.64 | 0.416182E+09 | 549.48 | 09-NOV-14:00 | 26.08 | 24.64 |
December | 0.602787E+10 | 6728.74 | 04-DEC-07:03 | 23.50 | 23.07 | 0.405301E+09 | 549.48 | 04-DEC-14:00 | 29.00 | 23.27 |
Annual Sum or Average | 0.860917E+11 | 0.504497E+10 | ||||||||
Minimum of Months | 0.602787E+10 | 6728.74 | 23.50 | 22.59 | 0.381246E+09 | 549.47 | 21.92 | 19.78 | ||
Maximum of Months | 0.925427E+10 | 11102.04 | 35.00 | 28.60 | 0.455523E+09 | 553.38 | 33.23 | 27.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524900E+10 | 9225.93 | 16-JAN-10:13 | 28.43 | 21.42 | 0.266381E+09 | 347.86 | 31-JAN-10:09 | 24.17 | 21.37 |
February | 0.515382E+10 | 10470.07 | 20-FEB-10:13 | 29.77 | 23.08 | 0.241794E+09 | 347.86 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.623096E+10 | 10834.36 | 26-MAR-09:22 | 31.90 | 24.91 | 0.288516E+09 | 347.86 | 03-MAR-10:09 | 31.90 | 24.91 |
April | 0.606946E+10 | 10712.94 | 30-APR-10:42 | 33.22 | 27.04 | 0.256426E+09 | 347.86 | 20-APR-13:00 | 33.22 | 27.04 |
May | 0.613834E+10 | 10687.08 | 14-MAY-10:12 | 32.60 | 26.07 | 0.277654E+09 | 347.86 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.628415E+10 | 9643.85 | 11-JUN-11:53 | 34.00 | 27.86 | 0.276752E+09 | 347.86 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.544558E+10 | 8600.46 | 30-JUL-09:13 | 28.83 | 24.44 | 0.257203E+09 | 347.86 | 17-JUL-13:00 | 28.83 | 24.44 |
August | 0.585307E+10 | 10695.52 | 27-AUG-10:02 | 31.58 | 26.86 | 0.288494E+09 | 347.86 | 04-AUG-09:00 | 31.58 | 26.86 |
September | 0.541640E+10 | 10410.66 | 04-SEP-08:53 | 30.00 | 26.93 | 0.256315E+09 | 347.86 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.506612E+10 | 8782.66 | 09-OCT-08:23 | 28.00 | 25.71 | 0.266423E+09 | 347.86 | 11-OCT-09:30 | 29.05 | 25.81 |
November | 0.494639E+10 | 8163.63 | 23-NOV-09:32 | 28.77 | 23.95 | 0.263839E+09 | 347.86 | 13-NOV-10:09 | 28.77 | 23.95 |
December | 0.488456E+10 | 8180.45 | 31-DEC-09:23 | 29.40 | 23.97 | 0.257072E+09 | 347.86 | 29-DEC-10:20 | 29.40 | 23.97 |
Annual Sum or Average | 0.667379E+11 | 0.319687E+10 | ||||||||
Minimum of Months | 0.488456E+10 | 8163.63 | 28.00 | 21.42 | 0.241794E+09 | 347.86 | 23.53 | 20.42 | ||
Maximum of Months | 0.628415E+10 | 10834.36 | 34.00 | 27.86 | 0.288516E+09 | 347.86 | 36.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102541E+11 | 11413.67 | 16-JAN-11:32 | 30.03 | 21.52 | 0.439924E+09 | 737.16 | 04-JAN-13:09 | 30.03 | 21.52 |
February | 0.926591E+10 | 11275.35 | 21-FEB-13:00 | 34.10 | 22.08 | 0.400269E+09 | 729.99 | 21-FEB-13:09 | 34.25 | 22.07 |
March | 0.102027E+11 | 11162.70 | 21-MAR-12:00 | 35.00 | 23.21 | 0.467672E+09 | 719.76 | 21-MAR-12:09 | 35.23 | 23.19 |
April | 0.903404E+10 | 10665.55 | 18-APR-12:00 | 34.00 | 26.52 | 0.410871E+09 | 677.90 | 18-APR-12:09 | 34.03 | 26.51 |
May | 0.967664E+10 | 11578.89 | 05-MAY-12:00 | 37.00 | 25.95 | 0.445810E+09 | 748.27 | 05-MAY-12:09 | 36.90 | 26.19 |
June | 0.968958E+10 | 11042.73 | 16-JUN-12:00 | 35.00 | 28.16 | 0.444652E+09 | 703.53 | 16-JUN-12:09 | 35.17 | 28.24 |
July | 0.829226E+10 | 10166.60 | 26-JUL-17:00 | 33.00 | 26.23 | 0.409315E+09 | 625.79 | 27-JUL-12:09 | 31.48 | 25.75 |
August | 0.899343E+10 | 10673.61 | 15-AUG-12:00 | 33.70 | 27.96 | 0.460105E+09 | 675.99 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.858389E+10 | 10508.88 | 05-SEP-12:00 | 33.00 | 26.98 | 0.409298E+09 | 665.60 | 05-SEP-12:09 | 33.02 | 26.93 |
October | 0.881166E+10 | 10947.98 | 29-OCT-11:43 | 31.50 | 26.00 | 0.426132E+09 | 665.46 | 04-OCT-12:09 | 31.50 | 26.00 |
November | 0.945165E+10 | 11006.86 | 23-NOV-11:32 | 30.77 | 24.95 | 0.428031E+09 | 670.78 | 22-NOV-13:09 | 30.77 | 24.95 |
December | 0.970854E+10 | 11406.76 | 03-DEC-12:22 | 31.25 | 24.81 | 0.422885E+09 | 706.65 | 26-DEC-13:09 | 32.00 | 23.12 |
Annual Sum or Average | 0.111964E+12 | 0.516496E+10 | ||||||||
Minimum of Months | 0.829226E+10 | 10166.60 | 30.03 | 21.52 | 0.400269E+09 | 625.79 | 30.03 | 21.52 | ||
Maximum of Months | 0.102541E+11 | 11578.89 | 37.00 | 28.16 | 0.467672E+09 | 748.27 | 36.90 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524125E+10 | 11528.78 | 16-JAN-17:32 | 28.07 | 21.84 | 0.266158E+09 | 347.84 | 09-JAN-14:00 | 28.07 | 21.84 |
February | 0.510551E+10 | 10790.28 | 26-FEB-15:32 | 34.40 | 24.93 | 0.241545E+09 | 347.84 | 21-FEB-10:09 | 34.40 | 24.93 |
March | 0.621725E+10 | 11440.42 | 05-MAR-16:32 | 28.73 | 23.49 | 0.288397E+09 | 347.84 | 03-MAR-10:09 | 28.73 | 23.49 |
April | 0.597424E+10 | 11632.37 | 30-APR-16:02 | 32.17 | 27.26 | 0.256276E+09 | 347.84 | 20-APR-13:00 | 32.17 | 27.26 |
May | 0.602803E+10 | 11226.06 | 14-MAY-16:11 | 33.87 | 27.36 | 0.277474E+09 | 347.84 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.615972E+10 | 11080.61 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276638E+09 | 347.84 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.537124E+10 | 11636.95 | 04-JUL-17:02 | 29.13 | 25.16 | 0.257096E+09 | 347.84 | 10-JUL-13:00 | 28.00 | 26.07 |
August | 0.571135E+10 | 11336.80 | 27-AUG-16:01 | 32.83 | 25.70 | 0.288392E+09 | 347.84 | 15-AUG-13:00 | 32.83 | 25.70 |
September | 0.530021E+10 | 11633.11 | 10-SEP-15:12 | 30.67 | 26.54 | 0.256122E+09 | 347.84 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.501978E+10 | 10154.84 | 15-OCT-17:03 | 28.42 | 25.82 | 0.266252E+09 | 347.84 | 13-OCT-13:00 | 28.42 | 25.82 |
November | 0.492025E+10 | 10350.18 | 19-NOV-14:52 | 31.50 | 24.93 | 0.263584E+09 | 347.84 | 09-NOV-14:00 | 31.50 | 24.93 |
December | 0.487604E+10 | 11296.26 | 31-DEC-15:22 | 31.70 | 24.08 | 0.256761E+09 | 347.84 | 08-DEC-14:00 | 31.70 | 24.08 |
Annual Sum or Average | 0.659249E+11 | 0.319469E+10 | ||||||||
Minimum of Months | 0.487604E+10 | 10154.84 | 28.07 | 21.84 | 0.241545E+09 | 347.84 | 28.00 | 21.84 | ||
Maximum of Months | 0.621725E+10 | 11636.95 | 34.40 | 27.84 | 0.288397E+09 | 347.84 | 36.00 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603502E+10 | 8670.61 | 02-JAN-06:12 | 23.37 | 23.04 | 0.419929E+09 | 549.48 | 09-JAN-14:00 | 31.00 | 24.49 |
February | 0.577788E+10 | 9061.14 | 27-FEB-05:02 | 24.00 | 22.49 | 0.381189E+09 | 549.48 | 15-FEB-14:00 | 24.00 | 22.49 |
March | 0.699479E+10 | 10523.54 | 26-MAR-14:02 | 34.83 | 25.46 | 0.455154E+09 | 549.47 | 03-MAR-10:09 | 34.83 | 25.46 |
April | 0.690740E+10 | 10729.66 | 30-APR-16:02 | 32.17 | 27.26 | 0.404497E+09 | 549.47 | 20-APR-13:09 | 32.17 | 27.26 |
May | 0.800102E+10 | 10990.27 | 07-MAY-10:32 | 33.07 | 26.79 | 0.438413E+09 | 549.48 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.858766E+10 | 11210.71 | 18-JUN-12:02 | 33.23 | 27.06 | 0.437065E+09 | 549.48 | 16-JUN-13:00 | 33.23 | 27.06 |
July | 0.716900E+10 | 11241.94 | 04-JUL-16:32 | 30.17 | 25.26 | 0.406110E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.703705E+10 | 9911.12 | 13-AUG-12:53 | 34.00 | 28.60 | 0.455292E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.629041E+10 | 9626.86 | 10-SEP-15:12 | 30.67 | 26.54 | 0.404235E+09 | 549.47 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.603648E+10 | 9058.81 | 02-OCT-04:02 | 24.00 | 23.36 | 0.420330E+09 | 549.47 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.588366E+10 | 9149.42 | 13-NOV-05:02 | 25.00 | 24.24 | 0.416082E+09 | 549.47 | 09-NOV-14:00 | 25.00 | 24.24 |
December | 0.565860E+10 | 7790.55 | 26-DEC-07:03 | 23.17 | 21.69 | 0.404938E+09 | 549.48 | 04-DEC-14:00 | 23.17 | 21.69 |
Annual Sum or Average | 0.803790E+11 | 0.504323E+10 | ||||||||
Minimum of Months | 0.565860E+10 | 7790.55 | 23.17 | 21.69 | 0.381189E+09 | 549.47 | 23.17 | 21.69 | ||
Maximum of Months | 0.858766E+10 | 11241.94 | 34.83 | 28.60 | 0.455292E+09 | 549.48 | 34.83 | 27.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488021E+10 | 10223.49 | 16-JAN-10:02 | 28.17 | 21.45 | 0.197042E+09 | 338.72 | 23-JAN-08:20 | 22.27 | 18.63 |
February | 0.480534E+10 | 11088.04 | 20-FEB-09:13 | 28.47 | 23.42 | 0.178837E+09 | 338.73 | 24-FEB-08:20 | 23.67 | 18.66 |
March | 0.587887E+10 | 11648.35 | 26-MAR-09:22 | 31.90 | 24.91 | 0.212914E+09 | 338.72 | 21-MAR-12:20 | 31.90 | 24.91 |
April | 0.570105E+10 | 11432.82 | 30-APR-08:42 | 30.18 | 26.77 | 0.189684E+09 | 338.72 | 13-APR-12:20 | 30.18 | 26.77 |
May | 0.569089E+10 | 11462.66 | 29-MAY-09:02 | 31.17 | 27.92 | 0.205186E+09 | 338.72 | 02-MAY-12:20 | 31.17 | 27.92 |
June | 0.579867E+10 | 10005.95 | 11-JUN-11:53 | 34.00 | 27.86 | 0.204282E+09 | 338.72 | 15-JUN-12:20 | 35.33 | 28.32 |
July | 0.492584E+10 | 9269.34 | 30-JUL-09:13 | 28.83 | 24.44 | 0.190268E+09 | 338.72 | 14-JUL-12:20 | 28.83 | 24.44 |
August | 0.531052E+10 | 11401.84 | 27-AUG-10:02 | 31.58 | 26.86 | 0.212738E+09 | 338.72 | 15-AUG-12:20 | 31.58 | 26.86 |
September | 0.492183E+10 | 11033.28 | 10-SEP-09:13 | 29.87 | 26.08 | 0.189399E+09 | 338.72 | 12-SEP-12:20 | 32.73 | 26.56 |
October | 0.468234E+10 | 11037.42 | 08-OCT-09:13 | 29.83 | 26.26 | 0.196993E+09 | 338.72 | 13-OCT-12:20 | 31.97 | 26.42 |
November | 0.456192E+10 | 9071.81 | 23-NOV-09:32 | 28.77 | 23.95 | 0.195106E+09 | 338.72 | 08-NOV-13:20 | 28.77 | 23.95 |
December | 0.452008E+10 | 9566.14 | 31-DEC-09:23 | 29.40 | 23.97 | 0.190082E+09 | 338.73 | 21-DEC-08:30 | 29.40 | 23.97 |
Annual Sum or Average | 0.616776E+11 | 0.236253E+10 | ||||||||
Minimum of Months | 0.452008E+10 | 9071.81 | 28.17 | 21.45 | 0.178837E+09 | 338.72 | 22.27 | 18.63 | ||
Maximum of Months | 0.587887E+10 | 11648.35 | 34.00 | 27.92 | 0.212914E+09 | 338.73 | 35.33 | 28.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.867048E+10 | 11743.25 | 16-JAN-12:02 | 30.38 | 21.74 | 0.424763E+09 | 591.21 | 17-JAN-14:09 | 30.95 | 22.65 |
February | 0.775539E+10 | 11112.33 | 26-FEB-12:13 | 32.83 | 24.74 | 0.383678E+09 | 585.99 | 21-FEB-14:09 | 32.83 | 24.74 |
March | 0.799075E+10 | 10890.79 | 19-MAR-12:13 | 35.93 | 23.76 | 0.455479E+09 | 549.48 | 06-MAR-14:00 | 35.93 | 23.76 |
April | 0.680080E+10 | 10311.03 | 30-APR-16:02 | 32.17 | 27.26 | 0.404449E+09 | 549.47 | 20-APR-13:09 | 32.17 | 27.26 |
May | 0.723390E+10 | 9221.25 | 01-MAY-04:02 | 28.25 | 26.74 | 0.438091E+09 | 549.47 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.714644E+10 | 8884.55 | 26-JUN-04:02 | 24.00 | 23.59 | 0.436643E+09 | 549.47 | 28-JUN-13:00 | 34.00 | 27.29 |
July | 0.636734E+10 | 8913.08 | 04-JUL-14:32 | 32.03 | 24.83 | 0.405733E+09 | 549.47 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.666062E+10 | 8762.95 | 15-AUG-04:02 | 26.17 | 25.52 | 0.455139E+09 | 549.47 | 25-AUG-13:00 | 29.00 | 26.74 |
September | 0.656114E+10 | 10423.52 | 10-SEP-15:12 | 30.67 | 26.54 | 0.404334E+09 | 549.47 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.702010E+10 | 11109.44 | 29-OCT-11:43 | 31.50 | 26.00 | 0.420779E+09 | 549.48 | 13-OCT-13:00 | 31.50 | 26.00 |
November | 0.769299E+10 | 11321.33 | 19-NOV-11:53 | 32.40 | 24.57 | 0.417402E+09 | 561.27 | 20-NOV-14:09 | 31.00 | 24.79 |
December | 0.823539E+10 | 11642.75 | 25-DEC-12:42 | 30.00 | 24.44 | 0.410309E+09 | 595.92 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.881353E+11 | 0.505680E+10 | ||||||||
Minimum of Months | 0.636734E+10 | 8762.95 | 24.00 | 21.74 | 0.383678E+09 | 549.47 | 25.00 | 22.65 | ||
Maximum of Months | 0.867048E+10 | 11743.25 | 35.93 | 27.26 | 0.455479E+09 | 595.92 | 35.93 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499017E+10 | 12528.85 | 16-JAN-16:42 | 29.38 | 22.09 | 0.265432E+09 | 347.84 | 11-JAN-14:00 | 29.38 | 22.09 |
February | 0.487434E+10 | 11873.17 | 26-FEB-15:32 | 34.40 | 24.93 | 0.240990E+09 | 347.84 | 15-FEB-14:00 | 34.40 | 24.93 |
March | 0.597523E+10 | 12295.20 | 05-MAR-16:32 | 28.73 | 23.49 | 0.287942E+09 | 347.84 | 03-MAR-10:09 | 28.73 | 23.49 |
April | 0.570260E+10 | 12467.33 | 30-APR-16:02 | 32.17 | 27.26 | 0.255963E+09 | 347.84 | 20-APR-13:00 | 32.17 | 27.26 |
May | 0.568781E+10 | 12039.36 | 14-MAY-16:11 | 33.87 | 27.36 | 0.277060E+09 | 347.84 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.576140E+10 | 11829.52 | 11-JUN-16:32 | 33.50 | 27.84 | 0.276254E+09 | 347.84 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.494532E+10 | 12726.13 | 04-JUL-16:32 | 30.17 | 25.26 | 0.256394E+09 | 347.84 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.527550E+10 | 12160.50 | 27-AUG-16:01 | 32.83 | 25.70 | 0.287742E+09 | 347.84 | 15-AUG-13:00 | 32.83 | 25.70 |
September | 0.491205E+10 | 12478.39 | 10-SEP-15:12 | 30.67 | 26.54 | 0.255504E+09 | 347.84 | 07-SEP-13:00 | 30.67 | 26.54 |
October | 0.473534E+10 | 10618.31 | 15-OCT-17:03 | 28.42 | 25.82 | 0.265537E+09 | 347.84 | 13-OCT-13:00 | 28.42 | 25.82 |
November | 0.465146E+10 | 11299.44 | 19-NOV-16:33 | 29.70 | 25.49 | 0.262984E+09 | 347.84 | 21-NOV-14:00 | 31.50 | 24.93 |
December | 0.463584E+10 | 12268.48 | 25-DEC-16:42 | 29.33 | 23.71 | 0.255799E+09 | 347.84 | 08-DEC-14:00 | 29.33 | 23.71 |
Annual Sum or Average | 0.621471E+11 | 0.318760E+10 | ||||||||
Minimum of Months | 0.463584E+10 | 10618.31 | 28.42 | 22.09 | 0.240990E+09 | 347.84 | 25.00 | 22.09 | ||
Maximum of Months | 0.597523E+10 | 12726.13 | 34.40 | 27.84 | 0.287942E+09 | 347.84 | 36.00 | 27.59 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16912281.10 | 3695.73 | 09-JAN-05:02 | 23.92 |
February | 16356550.85 | 5181.87 | 06-FEB-06:02 | 23.95 |
March | 16026030.03 | 4035.63 | 20-MAR-04:02 | 27.08 |
April | 13343209.32 | 3764.51 | 10-APR-04:02 | 25.17 |
May | 13814033.41 | 3490.30 | 15-MAY-04:02 | 26.33 |
June | 12858960.28 | 3756.76 | 12-JUN-04:02 | 26.33 |
July | 13818150.66 | 4222.62 | 17-JUL-04:02 | 24.42 |
August | 13232177.12 | 3966.94 | 28-AUG-04:02 | 25.33 |
September | 13214761.66 | 3805.60 | 25-SEP-04:02 | 26.00 |
October | 12973763.01 | 4047.97 | 02-OCT-04:02 | 24.00 |
November | 13047689.59 | 4250.39 | 13-NOV-05:02 | 25.00 |
December | 15991705.86 | 2820.81 | 09-DEC-06:03 | 24.15 |
Annual Sum or Average | 0.171589E+09 | |||
Minimum of Months | 12858960.28 | 2820.81 | 23.92 | |
Maximum of Months | 16912281.10 | 5181.87 | 27.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10125165.77 | 1952.11 | 09-JAN-05:02 | 23.92 |
February | 7966239.75 | 1803.59 | 06-FEB-06:02 | 23.95 |
March | 10862234.32 | 2159.63 | 28-MAR-04:02 | 27.25 |
April | 10154690.69 | 2227.04 | 12-APR-04:02 | 27.08 |
May | 10993907.31 | 2465.66 | 10-MAY-04:02 | 28.33 |
June | 10181283.19 | 2284.66 | 06-JUN-04:02 | 26.83 |
July | 8309596.49 | 2089.60 | 24-JUL-04:02 | 25.67 |
August | 8940072.14 | 2549.73 | 02-AUG-04:02 | 29.25 |
September | 9427197.98 | 2106.76 | 18-SEP-04:03 | 25.42 |
October | 8980752.64 | 2034.72 | 16-OCT-04:02 | 26.00 |
November | 9430039.62 | 2192.59 | 24-NOV-05:02 | 24.42 |
December | 10172180.48 | 1763.35 | 17-DEC-10:13 | 26.27 |
Annual Sum or Average | 0.115543E+09 | |||
Minimum of Months | 7966239.75 | 1763.35 | 23.92 | |
Maximum of Months | 10993907.31 | 2549.73 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20665652.65 | 3663.96 | 05-JAN-05:02 | 24.23 |
February | 17053643.47 | 3558.12 | 15-FEB-05:02 | 24.67 |
March | 19428857.57 | 3811.36 | 30-MAR-04:02 | 26.83 |
April | 21013468.23 | 3887.65 | 07-APR-04:02 | 27.08 |
May | 22631109.48 | 4032.09 | 10-MAY-04:02 | 28.33 |
June | 20126159.73 | 4065.70 | 29-JUN-04:02 | 26.58 |
July | 23000704.34 | 3826.20 | 06-JUL-04:02 | 25.17 |
August | 22494461.54 | 4288.59 | 02-AUG-04:02 | 29.25 |
September | 21058429.65 | 4038.04 | 28-SEP-04:02 | 25.67 |
October | 23975573.27 | 3751.83 | 05-OCT-04:02 | 26.00 |
November | 22394717.80 | 3777.44 | 14-NOV-05:02 | 26.00 |
December | 19101719.99 | 3154.68 | 30-DEC-05:03 | 24.00 |
Annual Sum or Average | 0.252944E+09 | |||
Minimum of Months | 17053643.47 | 3154.68 | 24.00 | |
Maximum of Months | 23975573.27 | 4288.59 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745435E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.664175E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.768129E+09 | 947.97 | 01-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668725E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.722885E+09 | 774.31 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710918E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.669309E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.750374E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.683661E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.720365E+09 | 947.97 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.744246E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.733009E+09 | 1184.79 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.858123E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664175E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.768129E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471708E+09 | 750.07 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.422222E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487889E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426731E+09 | 450.21 | 10-APR-15:09 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462926E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.456809E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430246E+09 | 450.21 | 03-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479176E+09 | 450.21 | 02-AUG-15:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434906E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.456963E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474037E+09 | 860.01 | 09-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.463911E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546752E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.422222E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487889E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.722044E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.653291E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764067E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674123E+09 | 774.31 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.733917E+09 | 774.31 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.724664E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.683493E+09 | 774.31 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.759327E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683987E+09 | 774.31 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.710827E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721991E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705762E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853749E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.653291E+09 | 754.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.764067E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.459784E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413758E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483358E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425849E+09 | 600.10 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462272E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455503E+09 | 600.10 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430661E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479672E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434267E+09 | 600.10 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.453453E+09 | 600.10 | 10-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.456759E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.448746E+09 | 750.02 | 18-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.540408E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413758E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.483358E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.743012E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.662790E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.766349E+09 | 947.97 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.667687E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.721492E+09 | 711.15 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710017E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.668253E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.749245E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.682420E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.718402E+09 | 774.31 | 11-OCT-15:50 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.741482E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.730186E+09 | 1184.79 | 04-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.856133E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.662790E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.766349E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.470634E+09 | 750.07 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.421275E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.486937E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426128E+09 | 450.21 | 10-APR-15:20 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462193E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455921E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429139E+09 | 450.21 | 03-JUL-15:50 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478372E+09 | 450.21 | 02-AUG-15:39 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434119E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.455732E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.472649E+09 | 750.07 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.462671E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545577E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.421275E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.486937E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.721308E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.652756E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.763082E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.672602E+09 | 711.15 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.731955E+09 | 774.31 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.723028E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.681915E+09 | 774.31 | 07-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.757290E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682575E+09 | 711.15 | 07-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.709572E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721755E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705146E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.852298E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.652756E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.763082E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.458899E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413338E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.482180E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425106E+09 | 490.17 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.461286E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.454390E+09 | 490.17 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.429789E+09 | 600.10 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.478690E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.433335E+09 | 490.17 | 07-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.452128E+09 | 600.10 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.455932E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.447837E+09 | 750.02 | 18-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.539291E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413338E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.482180E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745435E+09 | 1184.79 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.664175E+09 | 947.97 | 07-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.768127E+09 | 947.97 | 01-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.668725E+09 | 711.15 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.722847E+09 | 774.31 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.710918E+09 | 711.15 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.669309E+09 | 711.15 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.750374E+09 | 711.15 | 02-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.683661E+09 | 711.15 | 07-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.720353E+09 | 947.97 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.744246E+09 | 1184.79 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.733009E+09 | 1184.79 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.858118E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.664175E+09 | 711.15 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.768127E+09 | 1184.79 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.471708E+09 | 750.07 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.422198E+09 | 600.14 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.487889E+09 | 600.14 | 01-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.426731E+09 | 450.21 | 10-APR-15:09 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462926E+09 | 490.21 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.456809E+09 | 450.21 | 01-JUN-15:39 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430246E+09 | 450.21 | 03-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479176E+09 | 450.21 | 02-AUG-15:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434906E+09 | 490.21 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.456963E+09 | 600.14 | 11-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.474037E+09 | 860.01 | 09-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.463911E+09 | 860.01 | 04-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.546750E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.422198E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.487889E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.722044E+09 | 947.97 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.653291E+09 | 754.69 | 01-FEB-17:30 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.764067E+09 | 774.31 | 01-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.674123E+09 | 774.31 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.733911E+09 | 774.31 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.724664E+09 | 774.31 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.683493E+09 | 774.31 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.759327E+09 | 774.31 | 02-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.683987E+09 | 774.31 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.710827E+09 | 774.31 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.721991E+09 | 1184.79 | 07-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.705762E+09 | 1184.79 | 11-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.853749E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.653291E+09 | 754.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.764067E+09 | 1184.79 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.459784E+09 | 600.10 | 02-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413758E+09 | 477.75 | 01-FEB-17:40 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.483358E+09 | 600.10 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.425849E+09 | 600.10 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.462272E+09 | 600.10 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.455503E+09 | 600.10 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.430653E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.479672E+09 | 600.10 | 02-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.434267E+09 | 600.10 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.453429E+09 | 600.10 | 10-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.456759E+09 | 710.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.448746E+09 | 750.02 | 18-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.540405E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.413758E+09 | 477.75 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.483358E+09 | 750.02 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.745435E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23500932.84 | 14934545.53 |
February | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33076465.60 | 3664378.56 |
March | 0.107774E+10 | 0.768129E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56876623.40 | 5550418.71 |
April | 0.956342E+09 | 0.668725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56857031.92 | 998060.95 |
May | 0.103597E+10 | 0.722885E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61611235.71 | 3037227.44 |
June | 0.103308E+10 | 0.710918E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54847279.68 | 3846691.31 |
July | 0.959235E+09 | 0.669309E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34111294.95 | 3304482.09 |
August | 0.107774E+10 | 0.750374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41559147.37 | 5943317.98 |
September | 0.956342E+09 | 0.683661E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31248439.50 | 3525272.28 |
October | 0.994195E+09 | 0.720365E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25418162.82 | 6711557.33 |
November | 0.984487E+09 | 0.744246E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20125545.65 | 7886828.10 |
December | 0.959235E+09 | 0.733009E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19043273.68 | 15624427.70 |
Annual Sum or Average | 0.119305E+11 | 0.858123E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458275E+09 | 75027207.98 |
Minimum of Months | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19043273.68 | 998060.95 |
Maximum of Months | 0.107774E+10 | 0.768129E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61611235.71 | 15624427.70 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.471708E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15407399.74 | 10410337.95 |
February | 0.571020E+09 | 0.422222E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21459218.62 | 2771606.65 |
March | 0.682301E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36873119.70 | 4069931.76 |
April | 0.605444E+09 | 0.426731E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37403297.93 | 761303.55 |
May | 0.655854E+09 | 0.462926E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41767631.77 | 1940958.70 |
June | 0.654023E+09 | 0.456809E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37716310.91 | 2378929.84 |
July | 0.607275E+09 | 0.430246E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23482320.66 | 2017840.20 |
August | 0.682301E+09 | 0.479176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27683688.76 | 3942369.10 |
September | 0.605444E+09 | 0.434906E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20335508.26 | 2437561.73 |
October | 0.629407E+09 | 0.456963E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16571802.19 | 4586217.69 |
November | 0.623262E+09 | 0.474037E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951124.30 | 5444699.12 |
December | 0.607275E+09 | 0.463911E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12290400.14 | 10770272.82 |
Annual Sum or Average | 0.755301E+10 | 0.546752E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303942E+09 | 51532029.10 |
Minimum of Months | 0.571020E+09 | 0.422222E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12290400.14 | 761303.55 |
Maximum of Months | 0.682301E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41767631.77 | 10770272.82 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.722044E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21095312.80 | 17016757.71 |
February | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30934714.40 | 4477946.15 |
March | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55130897.46 | 6188123.82 |
April | 0.956342E+09 | 0.674123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57214745.99 | 978792.34 |
May | 0.103597E+10 | 0.733917E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63217692.53 | 2889641.00 |
June | 0.103308E+10 | 0.724664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57300900.28 | 3485524.28 |
July | 0.959235E+09 | 0.683493E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35724367.32 | 2945854.20 |
August | 0.107774E+10 | 0.759327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42535587.37 | 5671783.42 |
September | 0.956342E+09 | 0.683987E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30883486.17 | 3611595.46 |
October | 0.994195E+09 | 0.710827E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23952142.84 | 7342521.08 |
November | 0.984487E+09 | 0.721991E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18304341.99 | 8863708.55 |
December | 0.959235E+09 | 0.705762E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16692125.67 | 17409205.73 |
Annual Sum or Average | 0.119305E+11 | 0.853749E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452986E+09 | 80881453.73 |
Minimum of Months | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16692125.67 | 978792.34 |
Maximum of Months | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63217692.53 | 17409205.73 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.459784E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15428746.56 | 10576405.94 |
February | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21853181.45 | 2832001.69 |
March | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36845946.25 | 4671973.70 |
April | 0.605404E+09 | 0.425849E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36845020.46 | 805688.00 |
May | 0.655811E+09 | 0.462272E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41735376.10 | 2051571.83 |
June | 0.653980E+09 | 0.455503E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37337791.94 | 2547493.10 |
July | 0.607235E+09 | 0.430661E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23756866.71 | 2185320.74 |
August | 0.682256E+09 | 0.479672E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28055488.38 | 4318118.40 |
September | 0.605404E+09 | 0.434267E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20701838.84 | 2585726.83 |
October | 0.629366E+09 | 0.453453E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17113507.82 | 4804792.57 |
November | 0.623221E+09 | 0.456759E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13521395.58 | 5463358.84 |
December | 0.607235E+09 | 0.448746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12563247.24 | 10771689.37 |
Annual Sum or Average | 0.755252E+10 | 0.540408E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305758E+09 | 53614141.03 |
Minimum of Months | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12563247.24 | 805688.00 |
Maximum of Months | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41735376.10 | 10771689.37 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.743012E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12959931.12 | 8098394.53 |
February | 0.901968E+09 | 0.662790E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18158055.76 | 2088454.10 |
March | 0.107774E+10 | 0.766349E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31602991.40 | 3098863.19 |
April | 0.956342E+09 | 0.667687E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31349396.62 | 527698.97 |
May | 0.103597E+10 | 0.721492E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33560023.23 | 1850572.38 |
June | 0.103308E+10 | 0.710017E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29504728.67 | 2219419.63 |
July | 0.959235E+09 | 0.668253E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18611340.43 | 1937878.18 |
August | 0.107774E+10 | 0.749245E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22436247.14 | 3874159.79 |
September | 0.956342E+09 | 0.682420E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17167770.81 | 2124479.98 |
October | 0.994195E+09 | 0.718402E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14121313.14 | 3384483.21 |
November | 0.984487E+09 | 0.741482E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11097085.58 | 4551141.68 |
December | 0.959235E+09 | 0.730186E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10596562.95 | 9296704.59 |
Annual Sum or Average | 0.119305E+11 | 0.856133E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251165E+09 | 43052250.23 |
Minimum of Months | 0.901968E+09 | 0.662790E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10596562.95 | 527698.97 |
Maximum of Months | 0.107774E+10 | 0.766349E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33560023.23 | 9296704.59 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.470634E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8223385.80 | 5926885.82 |
February | 0.571020E+09 | 0.421275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11466148.39 | 1773905.40 |
March | 0.682301E+09 | 0.486937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19651743.62 | 2662603.28 |
April | 0.605444E+09 | 0.426128E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19809386.35 | 459740.21 |
May | 0.655854E+09 | 0.462193E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22309463.76 | 1237197.26 |
June | 0.654023E+09 | 0.455921E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20107225.98 | 1430456.35 |
July | 0.607275E+09 | 0.429139E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12604175.84 | 1260854.72 |
August | 0.682301E+09 | 0.478372E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14658956.17 | 2750307.35 |
September | 0.605444E+09 | 0.434119E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10864693.45 | 1612684.77 |
October | 0.629407E+09 | 0.455732E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8880520.39 | 2539921.71 |
November | 0.623262E+09 | 0.472649E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6958145.70 | 3344828.62 |
December | 0.607275E+09 | 0.462671E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6623934.80 | 6618271.01 |
Annual Sum or Average | 0.755301E+10 | 0.545577E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162158E+09 | 31617656.49 |
Minimum of Months | 0.571020E+09 | 0.421275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6623934.80 | 459740.21 |
Maximum of Months | 0.682301E+09 | 0.486937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22309463.76 | 6618271.01 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.721308E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147637E+10 | 0.117099E+09 |
February | 0.901968E+09 | 0.652756E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154414E+10 | 67902508.07 |
March | 0.107774E+10 | 0.763082E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223712E+10 | 9154047.21 |
April | 0.956342E+09 | 0.672602E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218077E+10 | 766364.93 |
May | 0.103597E+10 | 0.731955E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229248E+10 | 2950927.39 |
June | 0.103308E+10 | 0.723028E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237942E+10 | 6185843.47 |
July | 0.959235E+09 | 0.681915E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145415E+10 | 4318425.39 |
August | 0.107774E+10 | 0.757290E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191792E+10 | 5755703.89 |
September | 0.956342E+09 | 0.682575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161081E+10 | 4898305.69 |
October | 0.994195E+09 | 0.709572E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143041E+10 | 15392382.79 |
November | 0.984487E+09 | 0.721755E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145650E+10 | 22892310.24 |
December | 0.959235E+09 | 0.705146E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122897E+10 | 0.104982E+09 |
Annual Sum or Average | 0.119305E+11 | 0.852298E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212091E+11 | 0.362298E+09 |
Minimum of Months | 0.901968E+09 | 0.652756E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122897E+10 | 766364.93 |
Maximum of Months | 0.107774E+10 | 0.763082E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237942E+10 | 0.117099E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.458899E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8052958.42 | 6063975.98 |
February | 0.570983E+09 | 0.413338E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11420616.89 | 1872396.83 |
March | 0.682256E+09 | 0.482180E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19331041.43 | 3057280.32 |
April | 0.605404E+09 | 0.425106E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19216425.75 | 512414.36 |
May | 0.655811E+09 | 0.461286E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22041762.34 | 1324349.35 |
June | 0.653980E+09 | 0.454390E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19632844.84 | 1521942.38 |
July | 0.607235E+09 | 0.429789E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12454576.81 | 1370248.29 |
August | 0.682256E+09 | 0.478690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14517440.29 | 2955708.67 |
September | 0.605404E+09 | 0.433335E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10852626.65 | 1705722.23 |
October | 0.629366E+09 | 0.452128E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8900856.70 | 2673577.18 |
November | 0.623221E+09 | 0.455932E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7029720.47 | 3393241.43 |
December | 0.607235E+09 | 0.447837E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6552808.86 | 6714638.31 |
Annual Sum or Average | 0.755252E+10 | 0.539291E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160004E+09 | 33165495.32 |
Minimum of Months | 0.570983E+09 | 0.413338E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6552808.86 | 512414.36 |
Maximum of Months | 0.682256E+09 | 0.482180E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22041762.34 | 6714638.31 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.745435E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19887808.92 | 13155570.03 |
February | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27946401.31 | 3339660.15 |
March | 0.107774E+10 | 0.768127E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48400014.38 | 4871636.29 |
April | 0.956342E+09 | 0.668725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48239683.16 | 868262.64 |
May | 0.103597E+10 | 0.722847E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51969278.07 | 2582080.89 |
June | 0.103308E+10 | 0.710918E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46327835.70 | 3211759.71 |
July | 0.959235E+09 | 0.669309E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29010684.86 | 2750605.02 |
August | 0.107774E+10 | 0.750374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35117776.91 | 5193110.92 |
September | 0.956342E+09 | 0.683661E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26715028.32 | 2995163.00 |
October | 0.994195E+09 | 0.720353E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21809260.99 | 5659750.85 |
November | 0.984487E+09 | 0.744246E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17114665.97 | 7097430.70 |
December | 0.959235E+09 | 0.733009E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16145072.64 | 14071131.05 |
Annual Sum or Average | 0.119305E+11 | 0.858118E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388684E+09 | 65796161.24 |
Minimum of Months | 0.901968E+09 | 0.664175E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16145072.64 | 868262.64 |
Maximum of Months | 0.107774E+10 | 0.768127E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51969278.07 | 14071131.05 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.471708E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13011639.03 | 9106259.72 |
February | 0.421807E+09 | 0.422198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18120492.95 | 2495082.83 |
March | 0.502994E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31203199.39 | 3532913.63 |
April | 0.447140E+09 | 0.426731E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31592547.19 | 655773.88 |
May | 0.484071E+09 | 0.462926E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35221316.37 | 1650004.26 |
June | 0.482240E+09 | 0.456809E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31934382.38 | 1994934.31 |
July | 0.448971E+09 | 0.430246E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20056899.24 | 1676812.67 |
August | 0.502994E+09 | 0.479176E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23401268.58 | 3438982.65 |
September | 0.447140E+09 | 0.434906E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17312977.96 | 2074273.71 |
October | 0.465148E+09 | 0.456963E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14156068.02 | 3868849.54 |
November | 0.460569E+09 | 0.474037E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11012419.03 | 4876770.63 |
December | 0.448971E+09 | 0.463911E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10422113.09 | 9631020.09 |
Annual Sum or Average | 0.557719E+10 | 0.546750E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257445E+09 | 45001677.91 |
Minimum of Months | 0.421807E+09 | 0.422198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10422113.09 | 655773.88 |
Maximum of Months | 0.502994E+09 | 0.487889E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35221316.37 | 9631020.09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.722044E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17594047.00 | 14923682.23 |
February | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25860647.10 | 4049622.60 |
March | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46548503.55 | 5405691.51 |
April | 0.956342E+09 | 0.674123E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48546123.37 | 852173.53 |
May | 0.103597E+10 | 0.733911E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53464980.63 | 2466331.42 |
June | 0.103308E+10 | 0.724664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48701374.93 | 2912363.23 |
July | 0.959235E+09 | 0.683493E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30652665.79 | 2434348.09 |
August | 0.107774E+10 | 0.759327E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35996581.57 | 4991972.06 |
September | 0.956342E+09 | 0.683987E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26321869.42 | 3066821.63 |
October | 0.994195E+09 | 0.710827E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20234309.46 | 6193843.04 |
November | 0.984487E+09 | 0.721991E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15343118.10 | 7914621.19 |
December | 0.959235E+09 | 0.705762E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13947782.05 | 15560336.51 |
Annual Sum or Average | 0.119305E+11 | 0.853749E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383212E+09 | 70771807.03 |
Minimum of Months | 0.901968E+09 | 0.653291E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13947782.05 | 852173.53 |
Maximum of Months | 0.107774E+10 | 0.764067E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53464980.63 | 15560336.51 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.459784E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12731168.96 | 9378626.26 |
February | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18097606.23 | 2595412.71 |
March | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30714130.98 | 4066890.67 |
April | 0.605404E+09 | 0.425849E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30647344.71 | 715835.93 |
May | 0.655811E+09 | 0.462272E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34745741.71 | 1759768.80 |
June | 0.653980E+09 | 0.455503E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31273456.59 | 2167653.10 |
July | 0.607235E+09 | 0.430653E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19898266.96 | 1845731.50 |
August | 0.682256E+09 | 0.479672E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23251941.04 | 3760195.93 |
September | 0.605404E+09 | 0.434267E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17321557.76 | 2228122.80 |
October | 0.629366E+09 | 0.453429E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14273460.49 | 4105048.88 |
November | 0.623221E+09 | 0.456759E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11195566.18 | 4966382.03 |
December | 0.607235E+09 | 0.448746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10329181.81 | 9749991.86 |
Annual Sum or Average | 0.755252E+10 | 0.540405E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254479E+09 | 47339660.48 |
Minimum of Months | 0.570983E+09 | 0.413758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10329181.81 | 715835.93 |
Maximum of Months | 0.682256E+09 | 0.483358E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34745741.71 | 9749991.86 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19867485.11 | 17807598.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30317113.59 | 4160918.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54383515.70 | 6026819.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57673865.09 | 903095.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63319729.36 | 3027309.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56862391.55 | 3592643.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34560303.57 | 2878203.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40113387.05 | 5772284.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30094027.44 | 3403059.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23567832.34 | 6771153.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17601560.52 | 9168084.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16093687.71 | 19440912.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444455E+09 | 82952083.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16093687.71 | 903095.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63319729.36 | 19440912.87 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26519573.97 | 21850948.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40225540.20 | 4774613.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71445685.66 | 7031839.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75365048.54 | 1032522.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82132187.85 | 3592307.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73885879.22 | 4418483.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45858064.28 | 3386970.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53228454.55 | 6263154.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39716739.98 | 3834374.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31326764.02 | 8151532.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23491114.84 | 10670066.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21628165.68 | 23419715.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584823E+09 | 98426529.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21628165.68 | 1032522.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82132187.85 | 23419715.06 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24845272.15 | 19108246.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38624763.45 | 3004521.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71555565.37 | 4833090.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75905630.30 | 690078.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83793997.43 | 3169848.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73593165.45 | 4668910.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39988236.55 | 3572403.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52352940.27 | 5499750.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36613519.41 | 4213256.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27429236.99 | 8220811.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21415891.61 | 9321790.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18749647.13 | 20001906.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564868E+09 | 86304614.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18749647.13 | 690078.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83793997.43 | 20001906.53 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.18 | 15-JAN-13:10 | 204.83 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 165.94 | 20-FEB-15:58 | 23.11 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.84 | 19-MAR-16:00 | 41.73 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.23 | 30-APR-15:36 | 15.84 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.25 | 07-MAY-15:00 | 83.65 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.73 | 18-JUN-14:20 | 96.71 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.45 | 04-JUL-14:08 | 45.85 | 02-JUL-13:50 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.29 | 06-AUG-13:00 | 89.70 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.01 | 10-SEP-15:00 | 48.48 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.31 | 29-OCT-13:10 | 42.74 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.57 | 11-NOV-16:00 | 42.32 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 | 31-DEC-09:53 | 78.12 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 | 15.84 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 282.84 | 204.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 | 15-JAN-13:10 | 136.49 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.66 | 20-FEB-16:00 | 24.63 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.61 | 19-MAR-15:37 | 28.38 | 05-MAR-07:20 |
April | 827.22 | 03-APR-09:09 | 450.21 | 10-APR-15:09 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.78 | 30-APR-15:38 | 15.84 | 23-APR-07:08 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.38 | 07-MAY-14:38 | 55.72 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.22 | 18-JUN-14:48 | 63.34 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 03-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.06 | 04-JUL-14:10 | 26.50 | 02-JUL-13:50 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 02-AUG-15:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.23 | 06-AUG-13:00 | 63.55 | 20-AUG-11:00 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.77 | 10-SEP-14:50 | 31.66 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.76 | 29-OCT-13:10 | 28.45 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.99 | 11-NOV-16:00 | 30.93 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 | 31-DEC-13:00 | 51.92 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 | 15.84 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 194.61 | 136.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 | 15-JAN-13:05 | 211.73 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 | 19-FEB-14:53 | 26.81 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 19-MAR-16:00 | 42.49 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.52 | 30-APR-15:38 | 15.61 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.09 | 07-MAY-14:36 | 82.68 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.19 | 18-JUN-14:06 | 93.59 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.13 | 04-JUL-14:08 | 34.13 | 02-JUL-13:50 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.00 | 06-AUG-13:00 | 88.90 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.31 | 10-SEP-14:46 | 49.08 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.71 | 29-OCT-13:05 | 43.60 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.24 | 11-NOV-15:50 | 46.38 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 31-DEC-12:56 | 79.81 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 754.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 63.74 | 15.61 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 211.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.45 | 15-JAN-13:10 | 136.74 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 | 20-FEB-15:56 | 16.33 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 19-MAR-16:00 | 28.00 | 03-MAR-05:40 |
April | 827.17 | 03-APR-09:09 | 600.10 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 30-APR-15:36 | 12.53 | 09-APR-16:50 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.57 | 21-MAY-11:37 | 55.60 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.21 | 18-JUN-14:06 | 64.84 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.69 | 04-JUL-14:08 | 26.14 | 02-JUL-13:50 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.97 | 06-AUG-13:00 | 59.49 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.45 | 10-SEP-14:46 | 31.82 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 10-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.80 | 29-OCT-13:10 | 29.12 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.28 | 11-NOV-15:50 | 28.39 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.91 | 31-DEC-09:53 | 52.18 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 53.91 | 12.53 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 136.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.18 | 15-JAN-13:00 | 130.44 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.83 | 20-FEB-16:00 | 14.21 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.85 | 19-MAR-16:00 | 24.73 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 | 30-APR-15:30 | 9.99 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.50 | 07-MAY-14:36 | 49.32 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 18-JUN-14:06 | 54.44 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.70 | 04-JUL-13:48 | 18.41 | 02-JUL-13:50 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.91 | 06-AUG-13:00 | 50.95 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.45 | 10-SEP-15:00 | 31.88 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 11-OCT-15:50 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.62 | 29-OCT-13:10 | 20.19 | 01-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 | 11-NOV-16:00 | 24.78 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 04-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 | 31-DEC-12:50 | 47.09 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 | 9.99 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 162.85 | 130.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 750.07 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 15-JAN-13:00 | 90.80 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 | 20-FEB-16:00 | 14.94 | 20-FEB-06:55 |
March | 827.22 | 01-MAR-10:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 19-MAR-15:40 | 17.49 | 14-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 450.21 | 10-APR-15:20 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 02-APR-15:50 | 8.85 | 23-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.97 | 07-MAY-14:38 | 33.67 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.89 | 18-JUN-14:08 | 35.92 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 03-JUL-15:50 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 | 04-JUL-13:53 | 11.44 | 02-JUL-13:10 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 02-AUG-15:39 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.64 | 06-AUG-13:00 | 36.12 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.60 | 10-SEP-14:55 | 22.22 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 | 29-OCT-13:10 | 14.19 | 01-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 750.07 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 11-NOV-16:00 | 18.12 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 31-DEC-12:50 | 31.83 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 | 8.85 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 90.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9331.75 | 04-JAN-12:02 | 5190.76 | 23-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9052.22 | 24-FEB-17:03 | 3429.94 | 02-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11249.04 | 21-MAR-11:02 | 962.41 | 15-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11707.00 | 11-APR-16:02 | 198.83 | 14-APR-16:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13714.82 | 05-MAY-11:01 | 181.62 | 18-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12348.05 | 12-JUN-16:02 | 760.92 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 07-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9871.87 | 20-JUL-16:02 | 433.59 | 13-JUL-05:03 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10989.32 | 15-AUG-11:02 | 411.58 | 21-AUG-11:10 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9457.38 | 13-SEP-16:03 | 1246.85 | 15-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9039.01 | 04-OCT-11:02 | 1243.84 | 30-OCT-17:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8647.73 | 10-NOV-12:02 | 2414.36 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7712.74 | 08-DEC-12:02 | 5625.98 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7712.74 | 181.62 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13714.82 | 5625.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 | 15-JAN-13:00 | 91.11 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 | 20-FEB-15:52 | 10.76 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 19-MAR-16:00 | 17.40 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 490.17 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 02-APR-15:04 | 7.60 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 | 21-MAY-11:33 | 33.87 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.74 | 18-JUN-14:06 | 36.78 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.92 | 04-JUL-13:48 | 11.44 | 02-JUL-13:50 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 | 06-AUG-13:00 | 34.10 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 490.17 | 07-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | 10-SEP-14:55 | 22.77 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.44 | 29-OCT-13:10 | 14.75 | 01-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 11-NOV-15:40 | 16.92 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 31-DEC-12:50 | 31.95 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 7.60 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 91.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1184.79 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 | 15-JAN-13:10 | 190.45 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 947.97 | 07-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.46 | 20-FEB-16:00 | 21.43 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 947.97 | 01-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.70 | 19-MAR-16:00 | 37.37 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 711.15 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 02-APR-15:50 | 14.62 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.87 | 07-MAY-14:36 | 70.59 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.03 | 18-JUN-14:06 | 78.89 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.15 | 04-JUL-13:58 | 29.86 | 02-JUL-14:00 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 02-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.95 | 06-AUG-13:00 | 77.06 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 07-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.63 | 10-SEP-15:00 | 43.99 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 947.97 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.74 | 29-OCT-13:10 | 35.44 | 23-OCT-04:53 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 11-NOV-16:00 | 37.34 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.10 | 31-DEC-13:00 | 70.08 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.10 | 14.62 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 243.70 | 190.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 750.07 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.37 | 15-JAN-13:10 | 126.71 | 07-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 600.14 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 20-FEB-16:00 | 21.95 | 19-FEB-07:00 |
March | 805.43 | 01-MAR-08:09 | 600.14 | 01-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.85 | 19-MAR-15:40 | 24.90 | 03-MAR-05:30 |
April | 805.43 | 03-APR-07:10 | 450.21 | 10-APR-15:09 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.02 | 02-APR-15:50 | 13.60 | 23-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 490.21 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.82 | 07-MAY-14:40 | 47.02 | 08-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 01-JUN-15:39 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.30 | 18-JUN-14:50 | 51.63 | 20-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 03-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 04-JUL-14:00 | 17.26 | 02-JUL-13:20 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 02-AUG-15:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.41 | 06-AUG-13:00 | 54.65 | 20-AUG-10:50 |
September | 805.43 | 01-SEP-07:10 | 490.21 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.35 | 10-SEP-15:00 | 28.55 | 15-SEP-22:00 |
October | 805.43 | 02-OCT-07:10 | 600.14 | 11-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.12 | 29-OCT-13:10 | 23.42 | 23-OCT-04:53 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 11-NOV-16:00 | 26.57 | 26-NOV-10:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 04-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 24-DEC-15:10 | 46.54 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 13.60 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 162.85 | 126.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 947.97 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.26 | 15-JAN-13:05 | 196.35 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 754.69 | 01-FEB-17:30 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.57 | 20-FEB-15:56 | 24.49 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 774.31 | 01-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.25 | 19-MAR-16:00 | 37.84 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.88 | 30-APR-15:30 | 14.43 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 774.31 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.28 | 07-MAY-14:38 | 69.69 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.97 | 18-JUN-14:08 | 76.33 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 774.31 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.16 | 04-JUL-14:00 | 20.30 | 02-JUL-13:20 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 02-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.16 | 06-AUG-13:00 | 76.37 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.97 | 10-SEP-15:00 | 44.50 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 774.31 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.93 | 29-OCT-13:05 | 35.90 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1184.79 | 07-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.06 | 11-NOV-15:40 | 39.84 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 1184.79 | 11-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 31-DEC-12:56 | 71.47 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 754.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 14.43 | |||||
Maximum of Months | 1306.65 | 1184.79 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 236.25 | 196.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 600.10 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 | 15-JAN-13:10 | 127.36 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 477.75 | 01-FEB-17:40 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 | 20-FEB-15:54 | 15.10 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 600.10 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 | 19-MAR-16:00 | 25.31 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 600.10 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.24 | 02-APR-15:04 | 10.51 | 22-APR-03:00 |
May | 827.17 | 01-MAY-09:09 | 600.10 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 | 21-MAY-12:00 | 47.43 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 600.10 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 18-JUN-14:06 | 53.09 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.88 | 04-JUL-13:58 | 16.31 | 02-JUL-14:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 02-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.38 | 06-AUG-13:00 | 51.15 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.38 | 10-SEP-14:55 | 29.15 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 600.10 | 10-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.84 | 29-OCT-13:10 | 24.05 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 710.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 05-NOV-11:00 | 24.93 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 750.02 | 18-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 31-DEC-12:50 | 46.83 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 477.75 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 10.51 | |||||
Maximum of Months | 827.17 | 750.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 | 127.36 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.05 | 15-JAN-13:00 | 277.53 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.05 | 19-FEB-14:53 | 30.52 | 20-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.59 | 19-MAR-16:00 | 49.59 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 | 02-APR-15:31 | 18.96 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.97 | 07-MAY-15:00 | 83.36 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.54 | 18-JUN-14:30 | 82.08 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.57 | 04-JUL-14:00 | 27.48 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.97 | 06-AUG-13:00 | 82.78 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.13 | 10-SEP-15:00 | 56.77 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.19 | 29-OCT-12:52 | 44.30 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.12 | 11-NOV-16:00 | 51.08 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 24-DEC-14:52 | 98.59 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 18.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.59 | 277.53 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.77 | 15-JAN-12:52 | 333.42 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.01 | 19-FEB-14:53 | 34.01 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.69 | 19-MAR-16:00 | 60.21 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 23-APR-14:52 | 22.52 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.22 | 07-MAY-15:00 | 106.25 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.26 | 18-JUN-14:30 | 102.11 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.56 | 04-JUL-14:10 | 33.85 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.41 | 06-AUG-13:00 | 97.35 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.65 | 10-SEP-15:00 | 67.33 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.36 | 29-OCT-12:52 | 57.40 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 | 11-NOV-16:00 | 63.28 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.39 | 24-DEC-14:52 | 122.04 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.39 | 22.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.69 | 333.42 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | 15-JAN-12:52 | 265.85 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.28 | 19-FEB-15:00 | 31.99 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.88 | 19-MAR-16:00 | 54.33 | 03-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.02 | 09-APR-14:43 | 15.39 | 13-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.41 | 21-MAY-11:43 | 100.06 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.95 | 18-JUN-13:52 | 122.65 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.95 | 04-JUL-13:50 | 87.74 | 02-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.98 | 06-AUG-12:55 | 121.61 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.33 | 10-SEP-15:00 | 77.31 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.96 | 29-OCT-12:52 | 63.98 | 29-OCT-17:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.32 | 11-NOV-16:00 | 62.03 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 31-DEC-09:53 | 111.23 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 15.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.88 | 265.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 41050.26 | 03-JAN-05:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41662.80 | 06-FEB-06:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41130.02 | 08-MAR-05:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40821.54 | 22-APR-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40916.84 | 26-MAY-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40561.01 | 03-JUN-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40941.83 | 19-JUL-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41618.63 | 21-AUG-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43730.63 | 19-SEP-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41239.15 | 24-OCT-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41020.41 | 07-NOV-05:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40716.48 | 30-DEC-05:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 40561.01 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43730.63 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9835.57 | 04-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.14 | 0.00 |
February | 10868.84 | 21-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 | 0.00 |
March | 10925.29 | 21-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.46 | 0.00 |
April | 10214.80 | 11-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.43 | 0.00 |
May | 10960.84 | 05-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 0.00 |
June | 10772.11 | 16-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 | 0.00 |
July | 9423.60 | 14-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 0.00 |
August | 9988.34 | 14-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 |
September | 9956.36 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 0.00 |
October | 9500.72 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 | 0.00 |
November | 9425.11 | 22-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 |
December | 9692.83 | 26-DEC-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9423.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 0.00 | |
Maximum of Months | 10960.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5007.80 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
February | 5390.88 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.88 | 0.00 |
March | 5182.40 | 20-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 | 0.00 |
April | 4798.87 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | 0.00 |
May | 5328.93 | 30-MAY-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 0.00 |
June | 5383.93 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.76 | 0.00 |
July | 4579.55 | 17-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 | 0.00 |
August | 4772.09 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 | 0.00 |
September | 4904.89 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
October | 4873.05 | 10-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 0.00 |
November | 4992.28 | 13-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 0.00 |
December | 5054.16 | 26-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4579.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5390.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.40 | 0.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5323.15 | 17-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 0.00 |
February | 5660.54 | 21-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 | 0.00 |
March | 5459.20 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 | 0.00 |
April | 5296.21 | 17-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.76 | 0.00 |
May | 5950.52 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 |
June | 5745.65 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 0.00 |
July | 5217.63 | 17-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 |
August | 5312.54 | 14-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 | 0.00 |
September | 5466.94 | 05-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.96 | 0.00 |
October | 5312.75 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 | 0.00 |
November | 5335.39 | 13-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
December | 5344.32 | 26-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5217.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 0.00 | |
Maximum of Months | 5950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32631.94 | 10-JAN-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35286.36 | 06-FEB-06:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32795.49 | 07-MAR-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32033.02 | 05-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32429.39 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32527.23 | 01-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32816.87 | 18-JUL-04:22 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32393.81 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32466.21 | 13-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32915.97 | 11-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32911.04 | 07-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31019.82 | 26-DEC-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 31019.82 | 0.00 | 1058.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35286.36 | 3811.58 | 2863.91 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34711.64 | 09-JAN-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37677.41 | 06-FEB-06:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34537.20 | 21-MAR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34826.82 | 10-APR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34960.32 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34705.01 | 26-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34618.72 | 06-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35131.29 | 21-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34423.70 | 14-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35041.21 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34782.04 | 13-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33576.59 | 26-DEC-06:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33576.59 | 0.00 | 1058.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37677.41 | 3811.58 | 2863.91 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8526.42 | 02-JAN-06:12 | 535.68 | 603.74 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10197.40 | 05-FEB-14:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 78.64 | 0.00 |
March | 12584.55 | 26-MAR-14:02 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 130.15 | 0.00 |
April | 12281.66 | 30-APR-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 | 0.00 |
May | 12790.53 | 07-MAY-12:32 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 | 0.00 |
June | 12975.46 | 18-JUN-12:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 132.00 | 0.00 |
July | 12631.63 | 04-JUL-14:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 137.83 | 0.00 |
August | 12502.13 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 82.74 | 0.00 |
September | 12290.05 | 04-SEP-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 | 0.00 |
October | 10712.64 | 16-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.00 |
November | 11838.24 | 19-NOV-14:22 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 0.00 |
December | 6764.32 | 26-DEC-14:10 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6764.32 | 0.00 | 143.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12975.46 | 1306.65 | 647.98 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 137.83 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10037.31 | 16-JAN-11:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 0.00 |
February | 11530.39 | 20-FEB-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 | 0.00 |
March | 12181.84 | 26-MAR-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 | 0.00 |
April | 11508.01 | 09-APR-08:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 0.00 |
May | 12005.09 | 29-MAY-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 0.00 |
June | 11249.16 | 11-JUN-11:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 | 0.00 |
July | 8753.10 | 04-JUL-14:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 | 0.00 |
August | 11556.17 | 13-AUG-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 | 0.00 |
September | 11564.05 | 10-SEP-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
October | 11512.15 | 08-OCT-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 0.00 |
November | 9561.91 | 05-NOV-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 | 0.00 |
December | 8280.70 | 03-DEC-11:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8280.70 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 0.00 | |
Maximum of Months | 12181.84 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12961.67 | 29-JAN-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 0.00 |
February | 12793.14 | 26-FEB-12:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 0.00 |
March | 12745.10 | 26-MAR-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 120.53 | 0.00 |
April | 11949.01 | 02-APR-15:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 132.37 | 0.00 |
May | 12124.29 | 07-MAY-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 0.00 |
June | 12037.50 | 18-JUN-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 0.00 |
July | 11948.56 | 04-JUL-14:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 0.00 |
August | 11724.61 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 85.74 | 0.00 |
September | 12151.77 | 04-SEP-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 | 0.00 |
October | 12774.89 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 111.40 | 0.00 |
November | 13279.38 | 19-NOV-12:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 | 0.00 |
December | 12972.70 | 03-DEC-11:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11724.61 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.55 | 0.00 | |
Maximum of Months | 13279.38 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13541.86 | 29-JAN-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
February | 13064.43 | 26-FEB-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 91.04 | 0.00 |
March | 13521.66 | 05-MAR-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 0.00 |
April | 13430.47 | 02-APR-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
May | 13023.32 | 14-MAY-15:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 | 0.00 |
June | 13068.96 | 11-JUN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 67.52 | 0.00 |
July | 13098.07 | 04-JUL-16:02 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | 0.00 |
August | 13074.65 | 27-AUG-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 | 0.00 |
September | 13148.33 | 04-SEP-16:12 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 58.92 | 0.00 |
October | 12005.19 | 15-OCT-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 0.00 |
November | 13398.21 | 19-NOV-14:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.45 | 0.00 |
December | 12170.98 | 03-DEC-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12005.19 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 0.00 | |
Maximum of Months | 13541.86 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 91.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7578.79 | 02-JAN-07:03 | 803.52 | 947.98 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 8329.81 | 06-FEB-06:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8675.42 | 28-MAR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 0.00 |
April | 10591.82 | 30-APR-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 | 0.00 |
May | 10982.75 | 29-MAY-11:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 0.00 |
June | 11102.04 | 18-JUN-12:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 0.00 |
July | 10976.02 | 04-JUL-17:02 | 0.00 | 179.99 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 | 0.00 |
August | 9172.03 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 | 0.00 |
September | 8990.06 | 08-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
October | 8844.81 | 16-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
November | 7768.53 | 13-NOV-07:03 | 803.52 | 711.16 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 0.00 |
December | 6728.74 | 04-DEC-07:03 | 1071.35 | 948.21 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6728.74 | 0.00 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11102.04 | 1071.35 | 948.21 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 | 0.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9225.93 | 16-JAN-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 0.00 |
February | 10470.07 | 20-FEB-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 0.00 |
March | 10834.36 | 26-MAR-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 0.00 |
April | 10712.94 | 30-APR-10:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 |
May | 10687.08 | 14-MAY-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
June | 9643.85 | 11-JUN-11:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 0.00 |
July | 8600.46 | 30-JUL-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 | 0.00 |
August | 10695.52 | 27-AUG-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 | 0.00 |
September | 10410.66 | 04-SEP-08:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
October | 8782.66 | 09-OCT-08:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
November | 8163.63 | 23-NOV-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
December | 8180.45 | 31-DEC-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8163.63 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 | |
Maximum of Months | 10834.36 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11413.67 | 16-JAN-11:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 0.00 |
February | 11275.35 | 21-FEB-13:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7834.66 | 0.00 |
March | 11162.70 | 21-MAR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9067.12 | 0.00 |
April | 10665.55 | 18-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8805.88 | 0.00 |
May | 11578.89 | 05-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10821.29 | 0.00 |
June | 11042.73 | 16-JUN-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9410.44 | 0.00 |
July | 10166.60 | 26-JUL-17:00 | 401.76 | 395.08 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8391.94 | 0.00 |
August | 10673.61 | 15-AUG-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8469.80 | 0.00 |
September | 10508.88 | 05-SEP-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7898.04 | 0.00 |
October | 10947.98 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.59 | 0.00 |
November | 11006.86 | 23-NOV-11:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 | 0.00 |
December | 11406.76 | 03-DEC-12:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10166.60 | 267.84 | 143.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 0.00 | |
Maximum of Months | 11578.89 | 687.71 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10821.29 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11528.78 | 16-JAN-17:32 | 211.94 | 238.87 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 |
February | 10790.28 | 26-FEB-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 0.00 |
March | 11440.42 | 05-MAR-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 | 0.00 |
April | 11632.37 | 30-APR-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 0.00 |
May | 11226.06 | 14-MAY-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 | 0.00 |
June | 11080.61 | 11-JUN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 37.01 | 0.00 |
July | 11636.95 | 04-JUL-17:02 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 0.00 |
August | 11336.80 | 27-AUG-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 | 0.00 |
September | 11633.11 | 10-SEP-15:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 0.00 |
October | 10154.84 | 15-OCT-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
November | 10350.18 | 19-NOV-14:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 0.00 |
December | 11296.26 | 31-DEC-15:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10154.84 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 | |
Maximum of Months | 11636.95 | 296.72 | 238.87 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8670.61 | 02-JAN-06:12 | 535.68 | 603.74 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9061.14 | 27-FEB-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 |
March | 10523.54 | 26-MAR-14:02 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 | 0.00 |
April | 10729.66 | 30-APR-16:02 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.31 | 0.00 |
May | 10990.27 | 07-MAY-10:32 | 334.80 | 179.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 33.36 | 0.00 |
June | 11210.71 | 18-JUN-12:02 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 | 0.00 |
July | 11241.94 | 04-JUL-16:32 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 57.61 | 0.00 |
August | 9911.12 | 13-AUG-12:53 | 267.84 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 71.85 | 0.00 |
September | 9626.86 | 10-SEP-15:12 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 92.00 | 0.00 |
October | 9058.81 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
November | 9149.42 | 13-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
December | 7790.55 | 26-DEC-07:03 | 1071.35 | 1263.98 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7790.55 | 0.00 | 143.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11241.94 | 1071.35 | 1263.98 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 | 5.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10223.49 | 16-JAN-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
February | 11088.04 | 20-FEB-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | 0.00 |
March | 11648.35 | 26-MAR-09:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 | 0.00 |
April | 11432.82 | 30-APR-08:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 | 0.00 |
May | 11462.66 | 29-MAY-09:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 |
June | 10005.95 | 11-JUN-11:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 78.88 | 0.00 |
July | 9269.34 | 30-JUL-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 0.00 |
August | 11401.84 | 27-AUG-10:02 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 0.00 |
September | 11033.28 | 10-SEP-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 | 0.00 |
October | 11037.42 | 08-OCT-09:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 | 0.00 |
November | 9071.81 | 23-NOV-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 |
December | 9566.14 | 31-DEC-09:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9071.81 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 | |
Maximum of Months | 11648.35 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 78.88 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11743.25 | 16-JAN-12:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 0.00 |
February | 11112.33 | 26-FEB-12:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 0.00 |
March | 10890.79 | 19-MAR-12:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 0.00 |
April | 10311.03 | 30-APR-16:02 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 101.54 | 0.00 |
May | 9221.25 | 01-MAY-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
June | 8884.55 | 26-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
July | 8913.08 | 04-JUL-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 121.10 | 0.00 |
August | 8762.95 | 15-AUG-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
September | 10423.52 | 10-SEP-15:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 87.61 | 0.00 |
October | 11109.44 | 29-OCT-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 95.27 | 0.00 |
November | 11321.33 | 19-NOV-11:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 | 0.00 |
December | 11642.75 | 25-DEC-12:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8762.95 | 0.00 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11743.25 | 401.76 | 223.18 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 161.35 | 1.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12528.85 | 16-JAN-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 |
February | 11873.17 | 26-FEB-15:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 0.00 |
March | 12295.20 | 05-MAR-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 |
April | 12467.33 | 30-APR-16:02 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 | 0.00 |
May | 12039.36 | 14-MAY-16:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 | 0.00 |
June | 11829.52 | 11-JUN-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 | 0.00 |
July | 12726.13 | 04-JUL-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 | 0.00 |
August | 12160.50 | 27-AUG-16:01 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 | 0.00 |
September | 12478.39 | 10-SEP-15:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 41.56 | 0.00 |
October | 10618.31 | 15-OCT-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 0.00 |
November | 11299.44 | 19-NOV-16:33 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 |
December | 12268.48 | 25-DEC-16:42 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10618.31 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 | |
Maximum of Months | 12726.13 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.170914E+12 | 151339.58 | 30-JAN-15:09 | 0.00 | 0.00 |
February | 0.159302E+12 | 160742.51 | 13-FEB-15:09 | 0.00 | 0.00 |
March | 0.188379E+12 | 163060.61 | 20-MAR-15:09 | 0.00 | 0.00 |
April | 0.182745E+12 | 162953.38 | 11-APR-15:00 | 0.00 | 0.00 |
May | 0.199037E+12 | 169445.28 | 05-MAY-14:20 | 0.00 | 0.00 |
June | 0.198836E+12 | 177422.83 | 13-JUN-15:20 | 0.00 | 0.00 |
July | 0.173003E+12 | 153047.11 | 17-JUL-14:09 | 0.00 | 0.00 |
August | 0.191267E+12 | 162488.67 | 14-AUG-14:30 | 0.00 | 0.00 |
September | 0.176224E+12 | 159492.27 | 06-SEP-14:30 | 0.00 | 0.00 |
October | 0.176189E+12 | 157858.26 | 16-OCT-14:09 | 0.00 | 0.00 |
November | 0.170695E+12 | 153269.55 | 13-NOV-13:50 | 0.00 | 0.00 |
December | 0.166207E+12 | 148420.68 | 26-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.215280E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.159302E+12 | 148420.68 | 0.00 | 0.00 | |
Maximum of Months | 0.199037E+12 | 177422.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.251855E+11 | 0.456186E+10 | 0.605851E+11 | 0.225867E+10 | 0.101402E+11 | 12379742.02 | 0.00 | 0.650782E+11 | 0.00 | 0.00 | 0.00 | 0.309169E+10 | 0.00 |
February | 0.227813E+11 | 0.400802E+10 | 0.548702E+11 | 0.204949E+10 | 0.972122E+10 | 11196021.66 | 0.00 | 0.630679E+11 | 0.00 | 0.00 | 0.00 | 0.279275E+10 | 0.00 |
March | 0.269479E+11 | 0.419680E+10 | 0.627783E+11 | 0.235655E+10 | 0.112539E+11 | 12675672.10 | 0.00 | 0.775889E+11 | 0.00 | 0.00 | 0.00 | 0.324426E+10 | 0.00 |
April | 0.239031E+11 | 0.388710E+10 | 0.586172E+11 | 0.219339E+10 | 0.104393E+11 | 11960507.72 | 0.00 | 0.808147E+11 | 0.00 | 0.00 | 0.00 | 0.287831E+10 | 0.00 |
May | 0.258590E+11 | 0.388975E+10 | 0.616817E+11 | 0.230752E+10 | 0.111629E+11 | 12527707.06 | 0.00 | 0.911046E+11 | 0.00 | 0.00 | 0.00 | 0.301874E+10 | 0.00 |
June | 0.256834E+11 | 0.371634E+10 | 0.604966E+11 | 0.226972E+10 | 0.118107E+11 | 12231776.97 | 0.00 | 0.918931E+11 | 0.00 | 0.00 | 0.00 | 0.295374E+10 | 0.00 |
July | 0.240310E+11 | 0.390630E+10 | 0.597911E+11 | 0.223048E+10 | 0.962669E+10 | 12256437.81 | 0.00 | 0.706150E+11 | 0.00 | 0.00 | 0.00 | 0.278970E+10 | 0.00 |
August | 0.268429E+11 | 0.397154E+10 | 0.627783E+11 | 0.235646E+10 | 0.101237E+11 | 12675672.10 | 0.00 | 0.821012E+11 | 0.00 | 0.00 | 0.00 | 0.308040E+10 | 0.00 |
September | 0.240268E+11 | 0.400992E+10 | 0.585950E+11 | 0.219223E+10 | 0.931524E+10 | 11960507.72 | 0.00 | 0.752411E+11 | 0.00 | 0.00 | 0.00 | 0.283145E+10 | 0.00 |
October | 0.250130E+11 | 0.434010E+10 | 0.605962E+11 | 0.225933E+10 | 0.915772E+10 | 12379742.02 | 0.00 | 0.718274E+11 | 0.00 | 0.00 | 0.00 | 0.298242E+10 | 0.00 |
November | 0.249811E+11 | 0.440359E+10 | 0.591197E+11 | 0.220132E+10 | 0.945792E+10 | 12059151.09 | 0.00 | 0.675341E+11 | 0.00 | 0.00 | 0.00 | 0.298543E+10 | 0.00 |
December | 0.244435E+11 | 0.461491E+10 | 0.597800E+11 | 0.222995E+10 | 0.928972E+10 | 12256437.81 | 0.00 | 0.628345E+11 | 0.00 | 0.00 | 0.00 | 0.300262E+10 | 0.00 |
Annual Sum or Average | 0.299699E+12 | 0.495062E+11 | 0.719689E+12 | 0.269051E+11 | 0.121499E+12 | 0.146559E+09 | 0.00 | 0.899701E+12 | 0.00 | 0.00 | 0.00 | 0.356515E+11 | 0.00 |
Minimum of Months | 0.227813E+11 | 0.371634E+10 | 0.548702E+11 | 0.204949E+10 | 0.915772E+10 | 11196021.66 | 0.00 | 0.628345E+11 | 0.00 | 0.00 | 0.00 | 0.278970E+10 | 0.00 |
Maximum of Months | 0.269479E+11 | 0.461491E+10 | 0.627783E+11 | 0.235655E+10 | 0.118107E+11 | 12675672.10 | 0.00 | 0.918931E+11 | 0.00 | 0.00 | 0.00 | 0.324426E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 29780.74 | 02-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-17:10 | 14170.92 | 17-JAN-15:09 | 6.85 | 01-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 27340.31 | 07-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 15-FEB-13:09 | 15974.88 | 21-FEB-15:09 | 6.85 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 27649.77 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 08-MAR-12:09 | 15370.37 | 20-MAR-14:00 | 6.85 | 19-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 26646.21 | 21-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 04-APR-12:09 | 14137.88 | 17-APR-15:20 | 6.85 | 02-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 27025.62 | 17-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 03-MAY-12:09 | 15245.75 | 05-MAY-15:20 | 6.85 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 26709.37 | 20-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 06-JUN-12:09 | 16327.79 | 12-JUN-15:20 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 26819.30 | 11-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-11:09 | 13320.07 | 24-JUL-14:09 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 26819.30 | 02-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-12:09 | 13911.63 | 14-AUG-14:30 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 26646.21 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 12-SEP-12:09 | 13677.33 | 05-SEP-14:09 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 27476.12 | 30-OCT-15:00 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-16:10 | 13883.63 | 10-OCT-14:09 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 31040.88 | 09-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 13708.37 | 20-NOV-15:09 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 31270.78 | 18-DEC-16:00 | 5686.19 | 01-DEC-17:30 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-12:09 | 14425.01 | 26-DEC-15:09 | 6.85 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26646.21 | 5686.19 | 41699.26 | 1410.29 | 13320.07 | 6.85 | 0.00 | |||||||
Maximum of Months | 31270.78 | 5686.19 | 41699.26 | 1410.29 | 16327.79 | 6.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 66528.51 | 04-JAN-15:09 | 0.00 | 0.00 | 0.00 | 4202.75 | 06-JAN-12:30 | 0.00 |
February | 75336.41 | 13-FEB-15:09 | 0.00 | 0.00 | 0.00 | 4201.41 | 01-FEB-12:00 | 0.00 |
March | 76071.20 | 20-MAR-14:00 | 0.00 | 0.00 | 0.00 | 3942.69 | 08-MAR-12:39 | 0.00 |
April | 77324.27 | 11-APR-15:00 | 0.00 | 0.00 | 0.00 | 3882.74 | 03-APR-11:39 | 0.00 |
May | 86405.71 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 3871.22 | 01-MAY-11:30 | 0.00 |
June | 90068.80 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3860.54 | 01-JUN-11:50 | 0.00 |
July | 69584.62 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 3855.03 | 28-JUL-11:50 | 0.00 |
August | 78270.29 | 22-AUG-14:00 | 0.00 | 0.00 | 0.00 | 3862.06 | 31-AUG-11:30 | 0.00 |
September | 75117.80 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 3872.52 | 29-SEP-11:20 | 0.00 |
October | 73418.86 | 16-OCT-14:09 | 0.00 | 0.00 | 0.00 | 3885.67 | 31-OCT-11:00 | 0.00 |
November | 70259.90 | 13-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4090.87 | 30-NOV-12:30 | 0.00 |
December | 66350.09 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 4201.73 | 26-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 66350.09 | 0.00 | 0.00 | 0.00 | 3855.03 | 0.00 | ||
Maximum of Months | 90068.80 | 0.00 | 0.00 | 0.00 | 4202.75 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 151339.58 | 30-JAN-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14081.04 | 6.85 | 0.00 | 65980.99 | 0.00 |
February | 160742.51 | 13-FEB-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14392.88 | 6.85 | 0.00 | 75336.41 | 0.00 |
March | 163060.61 | 20-MAR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 15320.93 | 6.85 | 0.00 | 75797.61 | 0.00 |
April | 162953.38 | 11-APR-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 13683.65 | 6.85 | 0.00 | 77324.27 | 0.00 |
May | 169445.28 | 05-MAY-14:20 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14893.18 | 6.85 | 0.00 | 83548.80 | 0.00 |
June | 177422.83 | 13-JUN-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 15860.98 | 6.85 | 0.00 | 89917.37 | 0.00 |
July | 153047.11 | 17-JUL-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13032.49 | 6.85 | 0.00 | 69015.63 | 0.00 |
August | 162488.67 | 14-AUG-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13911.63 | 6.85 | 0.00 | 77577.52 | 0.00 |
September | 159492.27 | 06-SEP-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13373.97 | 6.85 | 0.00 | 75116.78 | 0.00 |
October | 157858.26 | 16-OCT-14:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 13432.43 | 6.85 | 0.00 | 73418.86 | 0.00 |
November | 153269.55 | 13-NOV-13:50 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 13282.16 | 6.85 | 0.00 | 70181.89 | 0.00 |
December | 148420.68 | 26-DEC-15:09 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 14425.01 | 6.85 | 0.00 | 62981.68 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 148420.68 | 25681.07 | 38932.26 | 0.00 | 1410.29 | 13032.49 | 6.85 | 0.00 | 62981.68 | 0.00 | |
Maximum of Months | 177422.83 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 15860.98 | 6.85 | 0.00 | 89917.37 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.15 | 0.17 | 27.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.22 | 0.00 | 26.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.23 | 0.00 | 26.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 26.74 | 0.17 | 26.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.15 | 0.17 | 27.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.43 | 2.00 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.49 | 3.33 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.52 | 4.00 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.76 | 6.50 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.80 | 7.17 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.48 | 6.83 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 2.67 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.44 | 2.50 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.32 | 1.33 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 39.83 | 27.60 | 36.33 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.80 | 7.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.45 | 2.33 | 27.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.59 | 7.50 | 27.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.83 | 8.50 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.83 | 10.67 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.92 | 9.17 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.79 | 7.83 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.44 | 6.33 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.78 | 5.17 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.73 | 7.83 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.62 | 5.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.46 | 3.83 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.43 | 3.00 | 27.43 |
Annual Sum or Average | 0.00 | 0.00 | 79.33 | 27.71 | 78.00 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.43 | 2.33 | 27.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.92 | 10.67 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.86 | 9.83 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.86 | 8.33 | 27.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.74 | 6.00 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.50 | 3.67 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.58 | 4.33 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.54 | 3.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.35 | 2.00 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.48 | 1.83 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.49 | 4.33 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.66 | 7.17 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.81 | 7.83 | 27.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.11 | 13.17 | 27.11 |
Annual Sum or Average | 0.00 | 0.00 | 74.17 | 27.59 | 72.17 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.11 | 1.83 | 27.11 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.86 | 13.17 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.01 | 5.33 | 28.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 4.83 | 27.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.23 | 4.67 | 28.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.15 | 4.83 | 28.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.16 | 4.17 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.11 | 4.50 | 28.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.76 | 3.33 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.00 | 3.00 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.08 | 3.33 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.76 | 3.83 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.77 | 3.33 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.97 | 5.00 | 27.97 |
Annual Sum or Average | 0.00 | 0.00 | 59.33 | 28.02 | 50.17 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.00 | 27.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.23 | 5.33 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.49 | 4.33 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.54 | 5.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.41 | 1.33 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.67 | 27.50 | 12.00 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.54 | 5.83 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.51 | 3.17 | 27.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.62 | 6.50 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.61 | 8.17 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.66 | 8.67 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.61 | 6.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.42 | 2.17 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.55 | 4.50 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.55 | 6.50 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.45 | 4.33 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.36 | 1.50 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.35 | 1.83 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 54.50 | 27.56 | 54.00 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.66 | 8.67 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 108.50 | 25.40 | 108.17 | 25.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 100.33 | 25.47 | 100.33 | 25.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 25.59 | 61.50 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 | 25.63 | 38.83 | 25.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 25.61 | 42.83 | 25.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 25.74 | 41.17 | 25.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 25.20 | 29.00 | 25.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 25.46 | 30.00 | 25.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 25.42 | 29.17 | 25.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 25.44 | 35.17 | 25.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 25.46 | 61.83 | 25.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 25.51 | 87.67 | 25.50 |
Annual Sum or Average | 0.00 | 0.00 | 666.50 | 25.49 | 665.67 | 25.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 25.20 | 29.00 | 25.20 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 108.50 | 25.74 | 108.17 | 25.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.74 | 4.67 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.79 | 3.33 | 27.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.90 | 4.17 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.90 | 4.17 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.82 | 3.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.81 | 3.83 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 2.17 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.79 | 2.50 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.92 | 2.50 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.55 | 3.00 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.68 | 4.50 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 49.33 | 27.78 | 40.50 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.92 | 4.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.58 | 5.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.63 | 6.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.41 | 2.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 27.56 | 14.17 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.63 | 6.17 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.54 | 3.33 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.72 | 6.50 | 27.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.69 | 8.17 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.74 | 8.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.68 | 5.83 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.50 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.62 | 4.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.59 | 5.50 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.51 | 3.83 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.67 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.44 | 1.83 | 27.44 |
Annual Sum or Average | 0.00 | 0.00 | 51.83 | 27.64 | 51.83 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.74 | 8.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 26.08 | 20.33 | 26.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.08 | 10.00 | 27.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.52 | 5.17 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.40 | 1.83 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.32 | 1.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.53 | 5.00 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.68 | 6.83 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 25.91 | 24.67 | 25.91 |
Annual Sum or Average | 0.00 | 0.00 | 75.83 | 26.56 | 75.83 | 26.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.68 | 24.67 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.86 | 4.83 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.90 | 3.50 | 27.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.03 | 4.17 | 28.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.99 | 4.33 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.01 | 3.83 | 28.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.94 | 4.00 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.84 | 1.67 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.90 | 2.33 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.00 | 2.50 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.66 | 2.50 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.74 | 1.83 | 27.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.81 | 4.50 | 27.81 |
Annual Sum or Average | 0.00 | 0.00 | 46.67 | 27.91 | 40.00 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.66 | 1.67 | 27.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.03 | 4.83 | 28.06 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.47 | 0.00 | 24.47 |
February | 0.00 | 0.00 | 454.00 | 24.43 | 0.00 | 24.43 |
March | 0.00 | 0.00 | 514.00 | 24.37 | 0.00 | 24.37 |
April | 0.00 | 0.00 | 485.00 | 24.40 | 0.00 | 24.40 |
May | 0.00 | 0.00 | 508.00 | 24.41 | 0.00 | 24.41 |
June | 0.00 | 0.00 | 496.00 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 497.00 | 24.45 | 0.00 | 24.45 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 485.00 | 24.41 | 0.00 | 24.41 |
October | 0.00 | 0.00 | 502.00 | 24.46 | 0.00 | 24.46 |
November | 0.00 | 0.00 | 489.00 | 24.47 | 0.00 | 24.47 |
December | 0.00 | 0.00 | 497.00 | 24.45 | 0.00 | 24.45 |
Annual Sum or Average | 0.00 | 5943.00 | 24.43 | 0.00 | 24.43 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.37 | 0.00 | 24.37 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.47 | 0.00 | 24.47 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 461.00 | 24.31 | 0.00 | 24.31 |
February | 0.00 | 0.00 | 422.33 | 24.27 | 0.00 | 24.27 |
March | 0.00 | 0.00 | 476.00 | 24.23 | 0.00 | 24.23 |
April | 0.00 | 0.00 | 450.83 | 24.25 | 0.00 | 24.25 |
May | 0.00 | 0.00 | 479.33 | 24.27 | 0.00 | 24.27 |
June | 0.00 | 0.00 | 473.17 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 451.83 | 24.29 | 0.00 | 24.29 |
August | 0.67 | 23.23 | 459.50 | 24.26 | 0.00 | 24.26 |
September | 1.00 | 23.20 | 430.50 | 24.26 | 0.00 | 24.26 |
October | 0.00 | 0.00 | 445.17 | 24.31 | 0.00 | 24.31 |
November | 0.00 | 0.00 | 447.83 | 24.30 | 0.00 | 24.30 |
December | 0.17 | 23.27 | 429.50 | 24.29 | 0.00 | 24.29 |
Annual Sum or Average | 1.83 | 23.22 | 5427.00 | 24.27 | 0.00 | 24.27 |
Minimum of Months | 0.00 | 0.00 | 422.33 | 24.23 | 0.00 | 24.23 |
Maximum of Months | 1.00 | 23.27 | 479.33 | 24.31 | 0.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 23.38 | 419.33 | 24.31 | 0.00 | 24.31 |
February | 0.00 | 0.00 | 391.17 | 24.28 | 0.00 | 24.28 |
March | 1.33 | 23.35 | 465.00 | 24.25 | 0.00 | 24.25 |
April | 0.00 | 0.00 | 464.33 | 24.27 | 0.00 | 24.27 |
May | 0.00 | 0.00 | 480.00 | 24.29 | 0.00 | 24.29 |
June | 0.00 | 0.00 | 475.33 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 443.17 | 24.31 | 0.00 | 24.31 |
August | 1.67 | 23.14 | 444.00 | 24.27 | 0.00 | 24.27 |
September | 2.50 | 23.16 | 430.33 | 24.26 | 0.00 | 24.26 |
October | 0.83 | 23.27 | 423.33 | 24.33 | 0.00 | 24.33 |
November | 0.33 | 23.30 | 412.17 | 24.31 | 0.00 | 24.31 |
December | 9.00 | 23.30 | 384.83 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 19.33 | 23.28 | 5233.00 | 24.29 | 0.00 | 24.29 |
Minimum of Months | 0.00 | 0.00 | 384.83 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 9.00 | 23.38 | 480.00 | 24.33 | 0.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 24.44 | 464.83 | 24.41 | 6.50 | 24.43 |
February | 19.17 | 26.43 | 427.83 | 24.51 | 19.00 | 24.59 |
March | 30.00 | 26.23 | 503.83 | 24.47 | 30.00 | 24.57 |
April | 35.83 | 26.39 | 484.83 | 24.60 | 35.83 | 24.72 |
May | 51.33 | 26.48 | 503.83 | 24.69 | 51.33 | 24.85 |
June | 49.83 | 26.55 | 494.67 | 24.68 | 49.83 | 24.84 |
July | 41.17 | 26.66 | 490.00 | 24.70 | 41.17 | 24.84 |
August | 43.67 | 25.97 | 504.83 | 24.51 | 43.67 | 24.61 |
September | 29.67 | 26.33 | 475.17 | 24.54 | 29.67 | 24.64 |
October | 34.17 | 26.38 | 475.00 | 24.60 | 34.17 | 24.71 |
November | 16.33 | 26.22 | 463.00 | 24.49 | 15.83 | 24.55 |
December | 27.00 | 24.36 | 433.50 | 24.40 | 12.33 | 24.44 |
Annual Sum or Average | 393.67 | 26.17 | 5721.33 | 24.56 | 369.33 | 24.66 |
Minimum of Months | 15.50 | 24.36 | 427.83 | 24.40 | 6.50 | 24.43 |
Maximum of Months | 51.33 | 26.66 | 504.83 | 24.70 | 51.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 26.50 | 473.33 | 24.58 | 24.67 | 24.68 |
February | 45.17 | 26.66 | 437.00 | 24.71 | 45.17 | 24.87 |
March | 47.00 | 26.65 | 502.83 | 24.61 | 46.83 | 24.77 |
April | 55.50 | 26.72 | 483.00 | 24.75 | 55.50 | 24.93 |
May | 55.50 | 26.58 | 494.83 | 24.72 | 54.67 | 24.89 |
June | 48.50 | 26.60 | 492.00 | 24.66 | 48.50 | 24.82 |
July | 43.50 | 26.64 | 474.67 | 24.70 | 43.50 | 24.85 |
August | 48.17 | 26.26 | 494.33 | 24.56 | 47.83 | 24.70 |
September | 50.00 | 26.59 | 463.33 | 24.69 | 49.33 | 24.87 |
October | 57.00 | 26.36 | 468.33 | 24.71 | 53.33 | 24.89 |
November | 40.83 | 26.32 | 458.50 | 24.64 | 37.67 | 24.78 |
December | 46.33 | 26.01 | 447.33 | 24.62 | 39.50 | 24.76 |
Annual Sum or Average | 563.67 | 26.49 | 5689.50 | 24.66 | 546.50 | 24.82 |
Minimum of Months | 26.17 | 26.01 | 437.00 | 24.56 | 24.67 | 24.68 |
Maximum of Months | 57.00 | 26.72 | 502.83 | 24.75 | 55.50 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 26.80 | 490.50 | 24.77 | 47.00 | 24.94 |
February | 41.83 | 26.80 | 447.33 | 24.72 | 41.83 | 24.88 |
March | 38.17 | 26.48 | 508.17 | 24.55 | 38.17 | 24.68 |
April | 35.00 | 26.36 | 484.33 | 24.59 | 35.00 | 24.70 |
May | 41.00 | 26.26 | 501.83 | 24.60 | 41.00 | 24.72 |
June | 39.33 | 26.26 | 494.17 | 24.56 | 39.33 | 24.68 |
July | 24.00 | 26.56 | 480.83 | 24.59 | 24.00 | 24.68 |
August | 40.67 | 25.81 | 501.67 | 24.47 | 40.67 | 24.56 |
September | 33.50 | 26.40 | 476.00 | 24.57 | 33.50 | 24.68 |
October | 53.33 | 26.64 | 485.67 | 24.74 | 53.33 | 24.91 |
November | 48.33 | 26.79 | 479.17 | 24.75 | 48.33 | 24.92 |
December | 54.33 | 26.69 | 471.00 | 24.79 | 52.83 | 24.97 |
Annual Sum or Average | 497.83 | 26.51 | 5820.67 | 24.64 | 495.00 | 24.78 |
Minimum of Months | 24.00 | 25.81 | 447.33 | 24.47 | 24.00 | 24.56 |
Maximum of Months | 54.33 | 26.80 | 508.17 | 24.79 | 53.33 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.83 | 24.88 | 430.17 | 24.49 | 26.17 | 24.60 |
February | 38.17 | 25.54 | 400.67 | 24.54 | 26.50 | 24.66 |
March | 36.50 | 26.12 | 475.17 | 24.52 | 32.33 | 24.64 |
April | 37.00 | 26.58 | 471.67 | 24.61 | 37.00 | 24.75 |
May | 40.67 | 26.22 | 482.00 | 24.59 | 37.50 | 24.72 |
June | 37.33 | 26.41 | 478.00 | 24.57 | 36.67 | 24.70 |
July | 32.33 | 25.96 | 447.00 | 24.59 | 26.67 | 24.70 |
August | 46.33 | 25.69 | 467.50 | 24.49 | 40.17 | 24.61 |
September | 32.83 | 26.09 | 443.17 | 24.54 | 29.50 | 24.65 |
October | 52.83 | 25.46 | 435.17 | 24.59 | 37.17 | 24.73 |
November | 42.33 | 25.33 | 421.33 | 24.53 | 28.00 | 24.64 |
December | 72.33 | 24.44 | 405.33 | 24.43 | 31.83 | 24.55 |
Annual Sum or Average | 518.50 | 25.60 | 5357.17 | 24.54 | 389.50 | 24.66 |
Minimum of Months | 32.33 | 24.44 | 400.67 | 24.43 | 26.17 | 24.55 |
Maximum of Months | 72.33 | 26.58 | 482.00 | 24.61 | 40.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 497.17 | 24.40 | 0.00 | 24.40 |
February | 0.00 | 0.00 | 454.00 | 24.41 | 0.00 | 24.41 |
March | 3.00 | 26.18 | 514.00 | 24.37 | 3.00 | 24.38 |
April | 5.33 | 26.64 | 485.00 | 24.48 | 5.33 | 24.50 |
May | 28.33 | 26.75 | 508.00 | 24.64 | 28.33 | 24.75 |
June | 31.67 | 26.79 | 496.00 | 24.65 | 31.67 | 24.77 |
July | 17.50 | 26.81 | 497.00 | 24.64 | 17.50 | 24.71 |
August | 21.50 | 26.40 | 514.00 | 24.50 | 21.50 | 24.57 |
September | 1.50 | 26.93 | 485.00 | 24.45 | 1.50 | 24.46 |
October | 1.67 | 26.79 | 502.00 | 24.47 | 1.67 | 24.47 |
November | 0.00 | 0.00 | 489.00 | 24.43 | 0.00 | 24.43 |
December | 0.00 | 0.00 | 492.00 | 24.38 | 0.00 | 24.38 |
Annual Sum or Average | 110.50 | 26.69 | 5933.17 | 24.49 | 110.50 | 24.53 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.37 | 0.00 | 24.38 |
Maximum of Months | 31.67 | 26.93 | 514.00 | 24.65 | 31.67 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 26.93 | 502.00 | 24.54 | 6.67 | 24.57 |
February | 22.00 | 26.85 | 454.00 | 24.64 | 22.00 | 24.74 |
March | 32.67 | 26.79 | 514.00 | 24.60 | 32.67 | 24.72 |
April | 40.67 | 26.80 | 485.00 | 24.73 | 40.67 | 24.88 |
May | 45.00 | 26.79 | 508.00 | 24.72 | 45.00 | 24.88 |
June | 35.17 | 26.76 | 496.00 | 24.65 | 35.17 | 24.78 |
July | 23.50 | 26.83 | 497.00 | 24.66 | 23.50 | 24.75 |
August | 37.50 | 26.65 | 514.00 | 24.60 | 37.50 | 24.73 |
September | 33.00 | 26.78 | 485.00 | 24.67 | 33.00 | 24.80 |
October | 30.33 | 26.79 | 502.00 | 24.66 | 30.33 | 24.78 |
November | 12.83 | 26.90 | 489.00 | 24.59 | 12.83 | 24.65 |
December | 13.17 | 26.90 | 495.50 | 24.57 | 13.17 | 24.62 |
Annual Sum or Average | 332.50 | 26.79 | 5941.50 | 24.64 | 332.50 | 24.75 |
Minimum of Months | 6.67 | 26.65 | 454.00 | 24.54 | 6.67 | 24.57 |
Maximum of Months | 45.00 | 26.93 | 514.00 | 24.73 | 45.00 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.67 | 25.66 | 501.67 | 25.01 | 106.67 | 25.11 |
February | 95.17 | 25.68 | 454.00 | 25.01 | 95.17 | 25.11 |
March | 110.67 | 25.15 | 514.00 | 24.73 | 110.67 | 24.79 |
April | 116.83 | 24.74 | 485.00 | 24.62 | 116.83 | 24.64 |
May | 189.00 | 24.57 | 508.00 | 24.61 | 189.00 | 24.60 |
June | 177.50 | 24.60 | 496.00 | 24.60 | 177.50 | 24.60 |
July | 113.50 | 24.43 | 497.00 | 24.55 | 113.50 | 24.53 |
August | 219.17 | 24.44 | 514.00 | 24.48 | 219.17 | 24.47 |
September | 148.83 | 24.43 | 485.00 | 24.53 | 148.83 | 24.51 |
October | 164.50 | 24.73 | 502.00 | 24.67 | 164.50 | 24.68 |
November | 136.33 | 25.12 | 489.00 | 24.85 | 136.33 | 24.90 |
December | 117.00 | 25.54 | 496.33 | 24.97 | 117.00 | 25.06 |
Annual Sum or Average | 1695.17 | 24.84 | 5942.00 | 24.71 | 1695.17 | 24.73 |
Minimum of Months | 95.17 | 24.43 | 454.00 | 24.48 | 95.17 | 24.47 |
Maximum of Months | 219.17 | 25.68 | 514.00 | 25.01 | 219.17 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 26.87 | 498.83 | 24.56 | 18.67 | 24.64 |
February | 15.50 | 26.90 | 454.00 | 24.56 | 15.50 | 24.64 |
March | 21.83 | 26.85 | 514.00 | 24.54 | 21.83 | 24.63 |
April | 24.00 | 26.90 | 485.00 | 24.64 | 24.00 | 24.74 |
May | 27.83 | 26.84 | 507.83 | 24.63 | 27.83 | 24.74 |
June | 24.83 | 26.81 | 496.00 | 24.60 | 24.83 | 24.70 |
July | 16.50 | 26.78 | 497.00 | 24.61 | 16.50 | 24.68 |
August | 29.67 | 26.58 | 514.00 | 24.56 | 29.67 | 24.66 |
September | 14.33 | 26.90 | 485.00 | 24.55 | 14.33 | 24.62 |
October | 19.33 | 26.76 | 500.83 | 24.59 | 19.33 | 24.67 |
November | 10.33 | 26.84 | 488.50 | 24.53 | 10.33 | 24.58 |
December | 18.67 | 26.83 | 491.33 | 24.54 | 18.67 | 24.62 |
Annual Sum or Average | 241.50 | 26.81 | 5932.33 | 24.58 | 241.50 | 24.66 |
Minimum of Months | 10.33 | 26.58 | 454.00 | 24.53 | 10.33 | 24.58 |
Maximum of Months | 29.67 | 26.90 | 514.00 | 24.64 | 29.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 25.84 | 490.33 | 24.40 | 1.00 | 24.40 |
February | 5.00 | 26.23 | 452.67 | 24.43 | 5.00 | 24.45 |
March | 12.33 | 25.92 | 512.33 | 24.39 | 12.33 | 24.43 |
April | 17.67 | 26.26 | 485.00 | 24.51 | 17.67 | 24.57 |
May | 43.50 | 26.53 | 506.67 | 24.67 | 43.50 | 24.80 |
June | 44.50 | 26.59 | 495.50 | 24.66 | 44.50 | 24.81 |
July | 24.50 | 26.69 | 496.83 | 24.63 | 24.50 | 24.72 |
August | 32.50 | 26.08 | 511.50 | 24.49 | 32.50 | 24.58 |
September | 12.50 | 26.15 | 482.33 | 24.46 | 12.50 | 24.50 |
October | 15.17 | 26.29 | 493.83 | 24.51 | 15.17 | 24.56 |
November | 6.83 | 26.22 | 480.67 | 24.45 | 6.83 | 24.47 |
December | 5.83 | 25.14 | 471.00 | 24.39 | 4.00 | 24.40 |
Annual Sum or Average | 221.33 | 26.34 | 5878.67 | 24.50 | 219.50 | 24.57 |
Minimum of Months | 1.00 | 25.14 | 452.67 | 24.39 | 1.00 | 24.40 |
Maximum of Months | 44.50 | 26.69 | 512.33 | 24.67 | 44.50 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 26.81 | 418.17 | 24.61 | 13.17 | 24.68 |
February | 28.67 | 26.72 | 381.00 | 24.73 | 28.67 | 24.86 |
March | 38.33 | 26.68 | 428.83 | 24.68 | 38.33 | 24.83 |
April | 47.50 | 26.70 | 409.50 | 24.82 | 47.50 | 25.00 |
May | 50.17 | 26.65 | 423.67 | 24.81 | 50.17 | 24.98 |
June | 41.00 | 26.62 | 415.83 | 24.73 | 41.00 | 24.88 |
July | 24.17 | 26.73 | 409.50 | 24.71 | 24.17 | 24.82 |
August | 40.50 | 26.46 | 420.00 | 24.65 | 40.50 | 24.79 |
September | 38.50 | 26.61 | 398.00 | 24.74 | 38.50 | 24.89 |
October | 38.17 | 26.61 | 403.83 | 24.77 | 38.17 | 24.92 |
November | 22.00 | 26.68 | 397.17 | 24.69 | 22.00 | 24.79 |
December | 21.00 | 26.60 | 393.50 | 24.66 | 20.33 | 24.75 |
Annual Sum or Average | 403.17 | 26.64 | 4899.00 | 24.72 | 402.50 | 24.85 |
Minimum of Months | 13.17 | 26.46 | 381.00 | 24.61 | 13.17 | 24.68 |
Maximum of Months | 50.17 | 26.81 | 428.83 | 24.82 | 50.17 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 26.94 | 500.67 | 24.79 | 42.17 | 24.94 |
February | 36.67 | 26.84 | 454.00 | 24.72 | 36.67 | 24.87 |
March | 32.17 | 26.50 | 513.50 | 24.53 | 32.17 | 24.64 |
April | 16.67 | 26.20 | 485.00 | 24.50 | 16.67 | 24.55 |
May | 28.00 | 26.22 | 506.17 | 24.55 | 28.00 | 24.63 |
June | 24.33 | 26.16 | 495.00 | 24.50 | 24.33 | 24.57 |
July | 5.50 | 26.38 | 495.83 | 24.48 | 5.50 | 24.50 |
August | 27.33 | 25.88 | 511.00 | 24.44 | 27.33 | 24.51 |
September | 16.67 | 26.31 | 483.17 | 24.49 | 16.67 | 24.55 |
October | 41.50 | 26.64 | 497.50 | 24.69 | 41.50 | 24.83 |
November | 41.83 | 26.81 | 486.50 | 24.74 | 41.83 | 24.89 |
December | 44.83 | 26.92 | 492.83 | 24.79 | 44.83 | 24.96 |
Annual Sum or Average | 357.67 | 26.57 | 5921.17 | 24.60 | 357.67 | 24.71 |
Minimum of Months | 5.50 | 25.88 | 454.00 | 24.44 | 5.50 | 24.50 |
Maximum of Months | 44.83 | 26.94 | 513.50 | 24.79 | 44.83 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 26.15 | 468.67 | 24.52 | 20.83 | 24.62 |
February | 19.83 | 26.70 | 432.00 | 24.53 | 19.83 | 24.62 |
March | 28.17 | 26.58 | 503.50 | 24.50 | 28.17 | 24.61 |
April | 31.83 | 26.64 | 483.00 | 24.60 | 31.83 | 24.72 |
May | 32.67 | 26.51 | 495.83 | 24.58 | 32.33 | 24.70 |
June | 32.67 | 26.48 | 492.17 | 24.55 | 32.67 | 24.66 |
July | 15.50 | 26.66 | 470.50 | 24.54 | 15.50 | 24.61 |
August | 35.17 | 26.24 | 493.17 | 24.50 | 35.17 | 24.61 |
September | 21.50 | 26.53 | 461.67 | 24.51 | 21.50 | 24.60 |
October | 29.67 | 26.44 | 458.00 | 24.60 | 29.00 | 24.71 |
November | 19.17 | 26.58 | 455.83 | 24.53 | 19.00 | 24.61 |
December | 30.00 | 26.02 | 442.33 | 24.53 | 24.67 | 24.64 |
Annual Sum or Average | 321.67 | 26.44 | 5656.67 | 24.54 | 310.50 | 24.64 |
Minimum of Months | 15.50 | 26.02 | 432.00 | 24.50 | 15.50 | 24.60 |
Maximum of Months | 35.17 | 26.70 | 503.50 | 24.60 | 35.17 | 24.72 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47368 | 46.85268 | 0.58310 | 12.44738 |
February | 454.00000 | 24.43316 | 47.06080 | 0.57665 | 12.24538 |
March | 514.00000 | 24.37127 | 47.28944 | 0.56365 | 11.90283 |
April | 485.00000 | 24.39964 | 47.26078 | 0.56802 | 12.02046 |
May | 508.00000 | 24.40562 | 47.21551 | -0.2711 | 7.05142 |
June | 496.00000 | 24.38972 | 47.17333 | -0.2716 | 7.05629 |
July | 497.00000 | 24.45202 | 47.13973 | -0.2618 | 7.03302 |
August | 514.00000 | 24.40482 | 47.39480 | -0.2754 | 7.16776 |
September | 485.00000 | 24.40517 | 47.43837 | -0.2744 | 7.08196 |
October | 502.00000 | 24.46198 | 47.28084 | 0.57822 | 12.33330 |
November | 489.00000 | 24.46821 | 47.16478 | 0.58106 | 12.39273 |
December | 497.00000 | 24.45400 | 47.09191 | 0.57677 | 12.26230 |
Annual Sum or Average | 5943.00000 | 24.42642 | 47.19798 | 0.21935 | 10.06194 |
Minimum of Months | 454.00000 | 24.37127 | 46.85268 | -0.2754 | 7.03302 |
Maximum of Months | 514.00000 | 24.47368 | 47.43837 | 0.58310 | 12.44738 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.25865 | 48.20811 | 0.52344 | 10.94740 |
February | 454.00000 | 24.22598 | 48.31849 | 0.51911 | 10.80496 |
March | 514.00000 | 24.19293 | 48.51183 | 0.51276 | 10.65751 |
April | 485.00000 | 24.20864 | 48.44594 | 0.51585 | 10.73598 |
May | 508.00000 | 24.23749 | 48.35734 | -0.3402 | 7.76425 |
June | 496.00000 | 24.23178 | 48.31237 | -0.3383 | 7.72026 |
July | 497.00000 | 24.22865 | 48.46310 | -0.3486 | 7.93766 |
August | 514.00000 | 24.19995 | 48.71560 | -0.3585 | 8.05851 |
September | 485.00000 | 24.19189 | 48.73572 | -0.3595 | 8.05116 |
October | 502.00000 | 24.23580 | 48.58047 | 0.51711 | 10.81379 |
November | 489.00000 | 24.24698 | 48.47875 | 0.52027 | 10.85372 |
December | 497.00000 | 24.20688 | 48.43401 | 0.50863 | 10.59447 |
Annual Sum or Average | 5943.00000 | 24.22209 | 48.46456 | 0.15253 | 9.56634 |
Minimum of Months | 454.00000 | 24.19189 | 48.20811 | -0.3595 | 7.72026 |
Maximum of Months | 514.00000 | 24.25865 | 48.73572 | 0.52344 | 10.94740 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.21500 | 47.86112 | 0.51761 | 10.82838 |
February | 454.00000 | 24.20488 | 47.97114 | 0.52067 | 10.85778 |
March | 514.00000 | 24.20065 | 48.24014 | 0.52426 | 10.92352 |
April | 485.00000 | 24.24090 | 48.31369 | 0.53603 | 11.19372 |
May | 508.00000 | 24.25860 | 48.28650 | -0.3170 | 7.50575 |
June | 496.00000 | 24.25463 | 48.24283 | -0.3131 | 7.42545 |
July | 497.00000 | 24.24031 | 48.34315 | -0.3321 | 7.71618 |
August | 514.00000 | 24.18316 | 48.74689 | -0.3512 | 7.94854 |
September | 485.00000 | 24.19903 | 48.69199 | -0.3428 | 7.84285 |
October | 502.00000 | 24.22333 | 48.62390 | 0.52186 | 10.93689 |
November | 489.00000 | 24.20954 | 48.45394 | 0.51866 | 10.82823 |
December | 497.00000 | 24.14057 | 48.29714 | 0.49811 | 10.39158 |
Annual Sum or Average | 5943.00000 | 24.21422 | 48.34186 | 0.16165 | 9.52029 |
Minimum of Months | 454.00000 | 24.14057 | 47.86112 | -0.3512 | 7.42545 |
Maximum of Months | 514.00000 | 24.25860 | 48.74689 | 0.53603 | 11.19372 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35053 | 49.25394 | 0.57789 | 12.46992 |
February | 454.00000 | 24.38806 | 49.04490 | 0.59591 | 12.97425 |
March | 514.00000 | 24.35745 | 49.89048 | 0.60399 | 13.11834 |
April | 485.00000 | 24.46804 | 49.83825 | 0.64066 | 14.18842 |
May | 508.00000 | 24.50549 | 49.84827 | -0.1467 | 6.92107 |
June | 496.00000 | 24.48745 | 49.50331 | -0.1282 | 6.75838 |
July | 497.00000 | 24.52497 | 49.07048 | -0.1658 | 6.96966 |
August | 514.00000 | 24.36888 | 51.20546 | -0.2198 | 7.00831 |
September | 485.00000 | 24.41135 | 50.07912 | -0.2209 | 7.03266 |
October | 502.00000 | 24.43238 | 50.33881 | 0.60540 | 13.34022 |
November | 489.00000 | 24.39094 | 49.84130 | 0.59199 | 12.85424 |
December | 497.00000 | 24.29854 | 49.72687 | 0.56147 | 12.10754 |
Annual Sum or Average | 5943.00000 | 24.41529 | 49.81262 | 0.27152 | 10.45254 |
Minimum of Months | 454.00000 | 24.29854 | 49.04490 | -0.2209 | 6.75838 |
Maximum of Months | 514.00000 | 24.52497 | 51.20546 | 0.64066 | 14.18842 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42906 | 48.69313 | 0.63166 | 14.00558 |
February | 454.00000 | 24.47278 | 48.42630 | 0.65716 | 14.82270 |
March | 514.00000 | 24.40523 | 49.23494 | 0.65974 | 14.85959 |
April | 485.00000 | 24.51864 | 49.22610 | 0.69443 | 15.95850 |
May | 508.00000 | 24.48660 | 49.71263 | -0.1262 | 7.06730 |
June | 496.00000 | 24.45590 | 49.54148 | -0.1238 | 6.76128 |
July | 497.00000 | 24.47938 | 49.17738 | -0.1623 | 6.99486 |
August | 514.00000 | 24.36042 | 50.92738 | -0.1842 | 7.03714 |
September | 485.00000 | 24.44790 | 49.66048 | -0.1632 | 7.15434 |
October | 502.00000 | 24.44582 | 49.99829 | 0.63748 | 14.40428 |
November | 489.00000 | 24.42964 | 49.45619 | 0.63044 | 14.05444 |
December | 497.00000 | 24.38427 | 49.14799 | 0.61361 | 13.65849 |
Annual Sum or Average | 5943.00000 | 24.44233 | 49.44480 | 0.31038 | 11.36413 |
Minimum of Months | 454.00000 | 24.36042 | 48.42630 | -0.1842 | 6.76128 |
Maximum of Months | 514.00000 | 24.51864 | 50.92738 | 0.69443 | 15.95850 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54669 | 48.08312 | 0.67855 | 15.57032 |
February | 454.00000 | 24.51218 | 48.17717 | 0.66987 | 15.23707 |
March | 514.00000 | 24.40058 | 49.49687 | 0.63403 | 14.02721 |
April | 485.00000 | 24.45795 | 49.90856 | 0.63593 | 14.04629 |
May | 508.00000 | 24.45549 | 50.22618 | -0.1856 | 6.90901 |
June | 496.00000 | 24.42706 | 50.10868 | -0.1911 | 6.84267 |
July | 497.00000 | 24.46506 | 49.48218 | -0.2100 | 7.07766 |
August | 514.00000 | 24.34224 | 51.42597 | -0.2397 | 7.08682 |
September | 485.00000 | 24.42604 | 49.95954 | -0.2076 | 7.00107 |
October | 502.00000 | 24.50038 | 49.82526 | 0.64145 | 14.47134 |
November | 489.00000 | 24.52365 | 48.94415 | 0.66094 | 15.00517 |
December | 497.00000 | 24.52253 | 48.40831 | 0.66771 | 15.35811 |
Annual Sum or Average | 5943.00000 | 24.46421 | 49.51824 | 0.29258 | 11.51792 |
Minimum of Months | 454.00000 | 24.34224 | 48.08312 | -0.2397 | 6.84267 |
Maximum of Months | 514.00000 | 24.54669 | 51.42597 | 0.67855 | 15.57032 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.28242 | 49.08221 | 0.60064 | 13.40412 |
February | 454.00000 | 24.31968 | 48.86247 | 0.62257 | 13.93905 |
March | 514.00000 | 24.32543 | 49.53638 | 0.64173 | 14.41272 |
April | 485.00000 | 24.43036 | 49.56477 | 0.67157 | 15.26561 |
May | 508.00000 | 24.39883 | 49.98283 | -0.1592 | 7.13158 |
June | 496.00000 | 24.39027 | 49.81827 | -0.1512 | 6.97132 |
July | 497.00000 | 24.38071 | 49.47531 | -0.1959 | 7.28291 |
August | 514.00000 | 24.27996 | 51.21231 | -0.2149 | 7.34970 |
September | 485.00000 | 24.32965 | 50.02289 | -0.2047 | 7.32201 |
October | 502.00000 | 24.32963 | 50.29586 | 0.61111 | 13.69331 |
November | 489.00000 | 24.29459 | 49.78218 | 0.60124 | 13.32149 |
December | 497.00000 | 24.20780 | 49.61001 | 0.57663 | 12.85955 |
Annual Sum or Average | 5943.00000 | 24.33062 | 49.78062 | 0.28001 | 11.05128 |
Minimum of Months | 454.00000 | 24.20780 | 48.86247 | -0.2149 | 6.97132 |
Maximum of Months | 514.00000 | 24.43036 | 51.21231 | 0.67157 | 15.26561 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39021 | 48.32119 | 0.57992 | 12.32798 |
February | 454.00000 | 24.41478 | 48.24983 | 0.59321 | 12.71861 |
March | 514.00000 | 24.35649 | 48.81166 | 0.58931 | 12.57632 |
April | 485.00000 | 24.45419 | 48.59553 | 0.62092 | 13.48733 |
May | 508.00000 | 24.52164 | 48.30467 | -0.1559 | 6.62252 |
June | 496.00000 | 24.51607 | 48.00351 | -0.1313 | 6.47049 |
July | 497.00000 | 24.56637 | 47.81563 | -0.1553 | 6.59522 |
August | 514.00000 | 24.42131 | 49.23310 | -0.2103 | 6.73080 |
September | 485.00000 | 24.44048 | 48.62566 | -0.2187 | 6.72375 |
October | 502.00000 | 24.45898 | 48.86173 | 0.60177 | 13.03176 |
November | 489.00000 | 24.43166 | 48.59783 | 0.59368 | 12.72904 |
December | 497.00000 | 24.37764 | 48.65982 | 0.57479 | 12.20229 |
Annual Sum or Average | 5943.00000 | 24.44582 | 48.51080 | 0.27038 | 10.15843 |
Minimum of Months | 454.00000 | 24.35649 | 47.81563 | -0.2187 | 6.47049 |
Maximum of Months | 514.00000 | 24.56637 | 49.23310 | 0.62092 | 13.48733 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50609 | 47.81129 | 0.64362 | 14.15293 |
February | 454.00000 | 24.53517 | 47.66538 | 0.66508 | 14.85393 |
March | 514.00000 | 24.46042 | 48.16704 | 0.66024 | 14.70610 |
April | 485.00000 | 24.55404 | 48.01158 | 0.68770 | 15.59382 |
May | 508.00000 | 24.53819 | 48.24388 | -0.1237 | 6.67524 |
June | 496.00000 | 24.50266 | 48.12052 | -0.1215 | 6.42943 |
July | 497.00000 | 24.55582 | 47.94709 | -0.1427 | 6.54621 |
August | 514.00000 | 24.45459 | 49.02887 | -0.1613 | 6.59506 |
September | 485.00000 | 24.52665 | 48.24180 | -0.1449 | 6.67211 |
October | 502.00000 | 24.53608 | 48.53178 | 0.64815 | 14.46643 |
November | 489.00000 | 24.52809 | 48.21773 | 0.64557 | 14.28326 |
December | 497.00000 | 24.50175 | 48.14596 | 0.63669 | 14.02525 |
Annual Sum or Average | 5943.00000 | 24.51610 | 48.18413 | 0.32108 | 11.21436 |
Minimum of Months | 454.00000 | 24.45459 | 47.66538 | -0.1613 | 6.42943 |
Maximum of Months | 514.00000 | 24.55582 | 49.02887 | 0.68770 | 15.59382 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.87490 | 52.42123 | 0.78461 | 18.75294 |
February | 454.00000 | 24.87416 | 52.42453 | 0.77918 | 18.55568 |
March | 514.00000 | 24.64035 | 54.97894 | 0.71908 | 16.44533 |
April | 485.00000 | 24.59745 | 57.01200 | 0.70754 | 16.02690 |
May | 508.00000 | 24.62046 | 59.90774 | -0.0746 | 6.13066 |
June | 496.00000 | 24.60546 | 59.91495 | -0.0743 | 6.14268 |
July | 497.00000 | 24.57675 | 56.84592 | -0.1208 | 6.12296 |
August | 514.00000 | 24.49251 | 61.64816 | -0.1171 | 6.12285 |
September | 485.00000 | 24.56439 | 58.90832 | -0.1001 | 6.09669 |
October | 502.00000 | 24.65088 | 58.61975 | 0.73830 | 17.09257 |
November | 489.00000 | 24.77200 | 56.04389 | 0.76952 | 18.16518 |
December | 497.00000 | 24.82905 | 52.91488 | 0.77372 | 18.44495 |
Annual Sum or Average | 5943.00000 | 24.67311 | 56.84310 | 0.39514 | 12.78864 |
Minimum of Months | 454.00000 | 24.49251 | 52.42123 | -0.1208 | 6.09669 |
Maximum of Months | 514.00000 | 24.87490 | 61.64816 | 0.78461 | 18.75294 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46581 | 47.96732 | 0.63303 | 13.91822 |
February | 454.00000 | 24.48168 | 47.87364 | 0.64985 | 14.39908 |
March | 514.00000 | 24.44181 | 48.31910 | 0.65455 | 14.53296 |
April | 485.00000 | 24.52535 | 48.21601 | 0.67716 | 15.24333 |
May | 508.00000 | 24.50575 | 48.40800 | -0.1405 | 6.60169 |
June | 496.00000 | 24.48497 | 48.28165 | -0.1341 | 6.49835 |
July | 497.00000 | 24.53853 | 48.07190 | -0.1529 | 6.59153 |
August | 514.00000 | 24.44216 | 49.18444 | -0.1722 | 6.64524 |
September | 485.00000 | 24.48302 | 48.44541 | -0.1654 | 6.61680 |
October | 502.00000 | 24.50525 | 48.66725 | 0.63906 | 14.17155 |
November | 489.00000 | 24.48157 | 48.37281 | 0.63347 | 13.92126 |
December | 497.00000 | 24.44748 | 48.33709 | 0.62330 | 13.66672 |
Annual Sum or Average | 5943.00000 | 24.48336 | 48.35122 | 0.30884 | 11.03461 |
Minimum of Months | 454.00000 | 24.44181 | 47.87364 | -0.1722 | 6.49835 |
Maximum of Months | 514.00000 | 24.53853 | 49.18444 | 0.67716 | 15.24333 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.37937 | 49.28489 | 0.57812 | 12.35521 |
February | 454.00000 | 24.40585 | 49.09134 | 0.59113 | 12.72669 |
March | 514.00000 | 24.35654 | 49.76618 | 0.59101 | 12.68010 |
April | 485.00000 | 24.45066 | 49.64531 | 0.62111 | 13.56257 |
May | 508.00000 | 24.50448 | 49.53439 | -0.1676 | 6.85264 |
June | 496.00000 | 24.48609 | 49.21876 | -0.1510 | 6.70806 |
July | 497.00000 | 24.52649 | 48.89371 | -0.1819 | 6.86711 |
August | 514.00000 | 24.38339 | 50.74474 | -0.2314 | 6.99198 |
September | 485.00000 | 24.41004 | 49.81140 | -0.2380 | 6.97764 |
October | 502.00000 | 24.44261 | 49.98710 | 0.59771 | 13.01327 |
November | 489.00000 | 24.41425 | 49.61829 | 0.58859 | 12.66703 |
December | 497.00000 | 24.34733 | 49.60422 | 0.56617 | 12.06441 |
Annual Sum or Average | 5943.00000 | 24.42552 | 49.60692 | 0.26048 | 10.26381 |
Minimum of Months | 454.00000 | 24.34733 | 48.89371 | -0.2380 | 6.70806 |
Maximum of Months | 514.00000 | 24.52649 | 50.74474 | 0.62111 | 13.56257 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.52600 | 48.66495 | 0.63264 | 14.01518 |
February | 385.00000 | 24.56847 | 48.38923 | 0.65486 | 14.73943 |
March | 433.00000 | 24.48917 | 49.11890 | 0.64916 | 14.57961 |
April | 410.00000 | 24.60335 | 49.02032 | 0.68119 | 15.60442 |
May | 430.00000 | 24.57662 | 49.41140 | -0.1393 | 7.17455 |
June | 418.00000 | 24.53573 | 49.31379 | -0.1425 | 6.88440 |
July | 422.00000 | 24.56303 | 48.93499 | -0.1727 | 7.02975 |
August | 433.00000 | 24.44851 | 50.62789 | -0.1941 | 7.17773 |
September | 410.00000 | 24.53392 | 49.32430 | -0.1746 | 7.22350 |
October | 427.00000 | 24.54050 | 49.63453 | 0.63452 | 14.30651 |
November | 417.00000 | 24.53073 | 49.17924 | 0.63087 | 14.05673 |
December | 422.00000 | 24.49183 | 48.98073 | 0.61831 | 13.73080 |
Annual Sum or Average | 5034.00000 | 24.53335 | 49.22599 | 0.30385 | 11.34958 |
Minimum of Months | 385.00000 | 24.44851 | 48.38923 | -0.1941 | 6.88440 |
Maximum of Months | 433.00000 | 24.60335 | 50.62789 | 0.68119 | 15.60442 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60320 | 48.02224 | 0.68214 | 15.57806 |
February | 454.00000 | 24.54918 | 48.15698 | 0.66730 | 15.05839 |
March | 514.00000 | 24.40892 | 49.34598 | 0.62218 | 13.62064 |
April | 485.00000 | 24.44133 | 49.71645 | 0.61671 | 13.43377 |
May | 508.00000 | 24.45031 | 49.92973 | -0.2068 | 6.87662 |
June | 496.00000 | 24.41641 | 49.84569 | -0.2148 | 6.83734 |
July | 497.00000 | 24.46109 | 49.31510 | -0.2266 | 6.97945 |
August | 514.00000 | 24.35780 | 50.96465 | -0.2505 | 7.07692 |
September | 485.00000 | 24.42795 | 49.68489 | -0.2243 | 6.93110 |
October | 502.00000 | 24.51980 | 49.45993 | 0.63483 | 14.18145 |
November | 489.00000 | 24.55775 | 48.68130 | 0.65810 | 14.84040 |
December | 497.00000 | 24.59351 | 48.21426 | 0.67456 | 15.42599 |
Annual Sum or Average | 5943.00000 | 24.48140 | 49.29053 | 0.28241 | 11.36941 |
Minimum of Months | 454.00000 | 24.35780 | 48.02224 | -0.2505 | 6.83734 |
Maximum of Months | 514.00000 | 24.60320 | 50.96465 | 0.68214 | 15.57806 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.37241 | 49.05820 | 0.61191 | 13.49313 |
February | 454.00000 | 24.38799 | 48.86402 | 0.62690 | 13.85207 |
March | 514.00000 | 24.36882 | 49.39409 | 0.63681 | 14.11932 |
April | 485.00000 | 24.45740 | 49.34235 | 0.66044 | 14.82177 |
May | 508.00000 | 24.43329 | 49.67965 | -0.1698 | 6.92540 |
June | 496.00000 | 24.41531 | 49.54430 | -0.1656 | 6.80193 |
July | 497.00000 | 24.42531 | 49.26144 | -0.1999 | 7.00633 |
August | 514.00000 | 24.34037 | 50.74206 | -0.2138 | 7.10478 |
September | 485.00000 | 24.37722 | 49.70745 | -0.2093 | 7.06499 |
October | 502.00000 | 24.39713 | 49.89796 | 0.61417 | 13.59683 |
November | 489.00000 | 24.37804 | 49.49915 | 0.60884 | 13.35702 |
December | 497.00000 | 24.32185 | 49.42325 | 0.59313 | 13.02408 |
Annual Sum or Average | 5943.00000 | 24.38938 | 49.54265 | 0.27950 | 10.90204 |
Minimum of Months | 454.00000 | 24.32185 | 48.86402 | -0.2138 | 6.80193 |
Maximum of Months | 514.00000 | 24.45740 | 50.74206 | 0.66044 | 14.82177 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101151E+12 | 0.236333E+11 | 453.50 | 0.693661E+11 | 0.317844E+11 | 0.00 | 1.00 | 01-JAN-00:12 | 0.00 | 01-JAN-00:10 | 110266.42 | 09-JAN-05:02 | 77416.72 | 30-JAN-07:03 | 34413.18 | 10-JAN-13:03 | 23322.05 | 12-JAN-13:02 | 0.00 |
February | 0.954913E+11 | 0.226613E+11 | 414.63 | 0.655741E+11 | 0.299171E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 105720.52 | 06-FEB-06:02 | 80550.86 | 21-FEB-07:03 | 36632.61 | 06-FEB-06:03 | 26044.15 | 13-FEB-15:20 | 0.00 |
March | 0.115774E+12 | 0.278001E+11 | 480.04 | 0.774720E+11 | 0.383018E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 124664.54 | 28-MAR-04:02 | 83080.46 | 20-MAR-04:02 | 42960.93 | 28-MAR-04:02 | 27889.77 | 28-MAR-04:02 | 0.00 |
April | 0.120808E+12 | 0.288481E+11 | 460.18 | 0.739592E+11 | 0.468489E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 125175.24 | 12-APR-04:02 | 82858.46 | 17-APR-04:02 | 45422.96 | 10-APR-17:00 | 27895.70 | 12-APR-04:02 | 0.00 |
May | 0.138299E+12 | 0.327148E+11 | 487.12 | 0.787161E+11 | 0.595824E+11 | 0.00 | 1.00 | 01-MAY-00:23 | 0.00 | 01-MAY-00:02 | 130461.07 | 20-MAY-04:02 | 83677.62 | 30-MAY-06:03 | 55137.90 | 20-MAY-04:02 | 30132.88 | 04-MAY-13:00 | 0.00 |
June | 0.138936E+12 | 0.330126E+11 | 471.13 | 0.797039E+11 | 0.592320E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 131519.24 | 10-JUN-04:02 | 83185.58 | 19-JUN-06:03 | 55080.73 | 10-JUN-04:02 | 31394.41 | 13-JUN-15:00 | 0.00 |
July | 0.111659E+12 | 0.256696E+11 | 461.31 | 0.690435E+11 | 0.426156E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 114118.97 | 10-JUL-04:02 | 81543.00 | 10-JUL-04:02 | 39433.74 | 03-JUL-12:03 | 24796.16 | 10-JUL-04:02 | 0.00 |
August | 0.130376E+12 | 0.299182E+11 | 474.03 | 0.730022E+11 | 0.573733E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 129879.82 | 07-AUG-04:02 | 82934.34 | 02-AUG-04:02 | 50591.73 | 14-AUG-17:00 | 29672.03 | 02-AUG-04:02 | 0.00 |
September | 0.118823E+12 | 0.272962E+11 | 450.92 | 0.678289E+11 | 0.509942E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 125575.04 | 25-SEP-04:02 | 82474.65 | 05-SEP-06:03 | 47271.43 | 19-SEP-05:03 | 27413.12 | 25-SEP-04:02 | 0.00 |
October | 0.115485E+12 | 0.261653E+11 | 455.59 | 0.663399E+11 | 0.491452E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 115125.27 | 05-OCT-04:02 | 81540.50 | 16-OCT-04:02 | 45397.52 | 16-OCT-12:03 | 25768.43 | 16-OCT-14:20 | 0.00 |
November | 0.107656E+12 | 0.246109E+11 | 437.82 | 0.659595E+11 | 0.416960E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 116843.32 | 13-NOV-07:03 | 82499.78 | 13-NOV-07:03 | 45639.85 | 10-NOV-13:02 | 25745.99 | 13-NOV-07:03 | 0.00 |
December | 0.989210E+11 | 0.227953E+11 | 439.33 | 0.653277E+11 | 0.335933E+11 | 0.00 | 1.00 | 01-DEC-06:12 | 0.00 | 01-DEC-00:10 | 107749.49 | 04-DEC-07:03 | 78573.92 | 26-DEC-07:03 | 40637.36 | 30-DEC-05:03 | 24301.49 | 11-DEC-13:02 | 0.00 |
Annual Sum or Average | 0.139338E+13 | 0.325126E+12 | 5485.60 | 0.852293E+12 | 0.541084E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.954913E+11 | 0.226613E+11 | 414.63 | 0.653277E+11 | 0.299171E+11 | 0.00 | 1.00 | 0.00 | 105720.52 | 77416.72 | 34413.18 | 23322.05 | 0.00 | ||||||
Maximum of Months | 0.138936E+12 | 0.330126E+11 | 487.12 | 0.797039E+11 | 0.595824E+11 | 0.00 | 1.00 | 0.00 | 131519.24 | 83677.62 | 55137.90 | 31394.41 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.866506E+11 | 0.201938E+11 | 438.14 | 0.578918E+11 | 0.287588E+11 | 0.00 | 1.00 | 01-JAN-06:40 | 0.00 | 01-JAN-00:10 | 107134.60 | 09-JAN-05:02 | 68170.48 | 09-JAN-05:02 | 38964.11 | 09-JAN-05:02 | 22592.89 | 09-JAN-05:02 | 0.00 |
February | 0.829888E+11 | 0.196259E+11 | 403.82 | 0.553682E+11 | 0.276206E+11 | 0.00 | 1.00 | 01-FEB-07:03 | 0.00 | 01-FEB-00:10 | 113997.82 | 06-FEB-06:02 | 73706.11 | 21-FEB-05:02 | 43788.59 | 06-FEB-06:03 | 24043.28 | 06-FEB-06:02 | 0.00 |
March | 0.100996E+12 | 0.241206E+11 | 470.65 | 0.655566E+11 | 0.354391E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 116991.25 | 27-MAR-04:02 | 75130.80 | 20-MAR-04:02 | 44364.40 | 28-MAR-04:02 | 26394.30 | 26-MAR-14:02 | 0.00 |
April | 0.106330E+12 | 0.251593E+11 | 448.35 | 0.625305E+11 | 0.437996E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 116920.60 | 12-APR-04:02 | 74698.26 | 03-APR-04:02 | 45259.52 | 30-APR-16:02 | 26549.85 | 30-APR-16:02 | 0.00 |
May | 0.121182E+12 | 0.284342E+11 | 472.54 | 0.661001E+11 | 0.550821E+11 | 0.00 | 1.00 | 01-MAY-00:33 | 0.00 | 01-MAY-00:02 | 121197.09 | 22-MAY-04:02 | 74198.93 | 15-MAY-04:02 | 58740.60 | 22-MAY-04:04 | 26973.92 | 04-MAY-13:00 | 0.00 |
June | 0.121662E+12 | 0.286400E+11 | 458.61 | 0.667082E+11 | 0.549541E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 120552.22 | 10-JUN-04:02 | 74252.68 | 19-JUN-04:02 | 55485.58 | 10-JUN-04:02 | 27991.09 | 13-JUN-15:00 | 0.00 |
July | 0.959244E+11 | 0.218996E+11 | 446.46 | 0.565832E+11 | 0.393412E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 110643.28 | 10-JUL-04:02 | 73354.29 | 24-JUL-04:02 | 37612.05 | 10-JUL-04:02 | 23945.67 | 10-JUL-04:02 | 0.00 |
August | 0.112356E+12 | 0.255589E+11 | 460.06 | 0.595610E+11 | 0.527952E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 122602.32 | 21-AUG-04:02 | 73719.30 | 14-AUG-04:02 | 64035.96 | 21-AUG-04:02 | 26859.68 | 02-AUG-04:02 | 0.00 |
September | 0.102887E+12 | 0.234285E+11 | 437.32 | 0.557560E+11 | 0.471311E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 117421.20 | 25-SEP-04:02 | 75342.52 | 05-SEP-04:02 | 49665.96 | 30-SEP-11:00 | 25510.10 | 25-SEP-04:02 | 0.00 |
October | 0.995558E+11 | 0.224064E+11 | 439.06 | 0.546750E+11 | 0.448808E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 118204.29 | 30-OCT-04:02 | 73487.32 | 16-OCT-04:02 | 47483.41 | 30-OCT-04:02 | 25153.27 | 30-OCT-04:02 | 0.00 |
November | 0.923610E+11 | 0.210093E+11 | 423.10 | 0.544715E+11 | 0.378894E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 112933.30 | 13-NOV-05:02 | 73004.73 | 13-NOV-05:02 | 39928.57 | 13-NOV-05:02 | 24218.99 | 13-NOV-05:02 | 0.00 |
December | 0.850336E+11 | 0.195310E+11 | 427.69 | 0.541900E+11 | 0.308436E+11 | 0.00 | 1.00 | 01-DEC-07:30 | 0.00 | 01-DEC-00:10 | 96542.77 | 26-DEC-07:03 | 69905.20 | 26-DEC-07:03 | 35656.94 | 11-DEC-06:13 | 20670.32 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.120793E+13 | 0.280007E+12 | 5325.81 | 0.709392E+12 | 0.498536E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.829888E+11 | 0.195310E+11 | 403.82 | 0.541900E+11 | 0.276206E+11 | 0.00 | 1.00 | 0.00 | 96542.77 | 68170.48 | 35656.94 | 20670.32 | 0.00 | ||||||
Maximum of Months | 0.121662E+12 | 0.286400E+11 | 472.54 | 0.667082E+11 | 0.550821E+11 | 0.00 | 1.00 | 0.00 | 122602.32 | 75342.52 | 64035.96 | 27991.09 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.906283E+11 | 0.212511E+11 | 436.15 | 0.616796E+11 | 0.289487E+11 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:10 | 101905.43 | 09-JAN-05:02 | 70514.62 | 05-JAN-15:00 | 39318.75 | 09-JAN-05:02 | 23329.40 | 05-JAN-15:00 | 0.00 |
February | 0.873389E+11 | 0.207807E+11 | 402.33 | 0.595656E+11 | 0.277733E+11 | 0.00 | 1.00 | 01-FEB-08:50 | 0.00 | 01-FEB-00:10 | 124295.21 | 06-FEB-06:02 | 79341.01 | 06-FEB-06:02 | 44954.20 | 06-FEB-06:02 | 26260.03 | 06-FEB-06:02 | 0.00 |
March | 0.106940E+12 | 0.256682E+11 | 469.56 | 0.713687E+11 | 0.355709E+11 | 0.00 | 1.00 | 01-MAR-08:70 | 0.00 | 01-MAR-00:10 | 131951.68 | 20-MAR-04:02 | 85262.54 | 20-MAR-04:02 | 50033.07 | 13-MAR-04:02 | 30072.50 | 26-MAR-14:02 | 0.00 |
April | 0.112869E+12 | 0.268073E+11 | 452.21 | 0.687070E+11 | 0.441615E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 132615.35 | 03-APR-04:02 | 86179.08 | 17-APR-04:02 | 49875.46 | 12-APR-04:02 | 30208.81 | 02-APR-15:42 | 0.00 |
May | 0.127140E+12 | 0.299555E+11 | 474.55 | 0.718104E+11 | 0.553295E+11 | 0.00 | 1.00 | 01-MAY-00:02 | 0.00 | 01-MAY-00:23 | 140661.91 | 22-MAY-04:02 | 86049.43 | 08-MAY-04:02 | 64394.59 | 22-MAY-04:02 | 30908.75 | 06-MAY-04:02 | 0.00 |
June | 0.127953E+12 | 0.302405E+11 | 461.17 | 0.727948E+11 | 0.551578E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 139786.72 | 10-JUN-05:03 | 84136.82 | 19-JUN-04:02 | 68385.17 | 10-JUN-05:03 | 32239.90 | 11-JUN-14:32 | 0.00 |
July | 0.100529E+12 | 0.230458E+11 | 447.71 | 0.610020E+11 | 0.395265E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 120200.97 | 10-JUL-04:02 | 82409.49 | 31-JUL-04:02 | 39957.38 | 10-JUL-04:02 | 26067.62 | 04-JUL-14:02 | 0.00 |
August | 0.116678E+12 | 0.266241E+11 | 458.83 | 0.638849E+11 | 0.527934E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 136869.07 | 12-AUG-05:03 | 84601.82 | 14-AUG-04:02 | 63976.01 | 12-AUG-05:03 | 31702.15 | 13-AUG-12:53 | 0.00 |
September | 0.107288E+12 | 0.245164E+11 | 436.81 | 0.601442E+11 | 0.471435E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 126691.45 | 11-SEP-04:02 | 85307.37 | 05-SEP-04:02 | 50595.21 | 25-SEP-04:02 | 28645.18 | 04-SEP-12:53 | 0.00 |
October | 0.103010E+12 | 0.232558E+11 | 438.56 | 0.580687E+11 | 0.449415E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 135129.77 | 30-OCT-04:02 | 81037.25 | 16-OCT-04:02 | 56378.02 | 30-OCT-04:02 | 28755.10 | 30-OCT-04:02 | 0.00 |
November | 0.959882E+11 | 0.219139E+11 | 422.59 | 0.580211E+11 | 0.379670E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 112812.40 | 13-NOV-05:02 | 75319.91 | 19-NOV-14:22 | 41650.16 | 13-NOV-05:02 | 25741.04 | 19-NOV-14:22 | 0.00 |
December | 0.888566E+11 | 0.205081E+11 | 428.92 | 0.576860E+11 | 0.311706E+11 | 0.00 | 1.00 | 01-DEC-08:65 | 0.00 | 01-DEC-00:10 | 93202.15 | 26-DEC-07:03 | 69737.01 | 26-DEC-15:00 | 35426.26 | 30-DEC-06:03 | 22717.08 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.126522E+13 | 0.294567E+12 | 5329.38 | 0.764733E+12 | 0.500484E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.873389E+11 | 0.205081E+11 | 402.33 | 0.576860E+11 | 0.277733E+11 | 0.00 | 1.00 | 0.00 | 93202.15 | 69737.01 | 35426.26 | 22717.08 | 0.00 | ||||||
Maximum of Months | 0.127953E+12 | 0.302405E+11 | 474.55 | 0.727948E+11 | 0.553295E+11 | 0.00 | 1.00 | 0.00 | 140661.91 | 86179.08 | 68385.17 | 32239.90 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.11 | 0.00 | 402.11 | 912.59 | 202.95 | 0.00 | 0.00 | 0.00 |
February | 428.94 | 0.00 | 428.94 | 1021.84 | 155.29 | 0.00 | 0.00 | 0.00 |
March | 440.23 | 0.00 | 440.23 | 1112.09 | 103.45 | 0.00 | 0.00 | 0.00 |
April | 479.08 | 6.79 | 472.29 | 1247.26 | 45.65 | 0.00 | 0.00 | 0.00 |
May | 614.13 | 65.42 | 548.70 | 1590.45 | 55.83 | 0.00 | 0.00 | 0.00 |
June | 750.18 | 151.61 | 598.57 | 1888.81 | 64.06 | 0.00 | 0.00 | 0.00 |
July | 645.08 | 67.62 | 577.47 | 1483.46 | 112.67 | 0.00 | 0.00 | 0.00 |
August | 531.11 | 22.65 | 508.47 | 1242.05 | 84.24 | 0.00 | 0.00 | 0.00 |
September | 452.18 | 0.22 | 451.97 | 1091.23 | 84.92 | 0.00 | 0.00 | 0.00 |
October | 435.70 | 0.00 | 435.70 | 972.62 | 111.92 | 0.00 | 0.00 | 0.00 |
November | 412.27 | 0.00 | 412.27 | 929.62 | 135.66 | 0.00 | 0.00 | 0.00 |
December | 390.65 | 0.00 | 390.65 | 879.36 | 221.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 498.77 | 26.26 | 472.51 | 1198.06 | 114.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.65 | 0.00 | 390.65 | 879.36 | 45.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.18 | 151.61 | 598.57 | 1888.81 | 221.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.92 | 174.22 | 342.71 | 1079.00 | 128.42 | 0.00 | 0.00 | 0.00 |
February | 586.19 | 214.93 | 371.26 | 1252.02 | 96.73 | 0.00 | 0.00 | 0.00 |
March | 639.06 | 250.25 | 388.81 | 1398.98 | 62.97 | 0.00 | 0.00 | 0.00 |
April | 645.87 | 246.75 | 399.12 | 1452.57 | 28.34 | 0.00 | 0.00 | 0.00 |
May | 555.18 | 168.05 | 387.13 | 1301.57 | 35.71 | 0.00 | 0.00 | 0.00 |
June | 591.31 | 194.75 | 396.57 | 1367.24 | 40.01 | 0.00 | 0.00 | 0.00 |
July | 505.06 | 113.15 | 391.92 | 1098.46 | 72.01 | 0.00 | 0.00 | 0.00 |
August | 555.83 | 163.39 | 392.44 | 1191.47 | 55.00 | 0.00 | 0.00 | 0.00 |
September | 521.99 | 142.25 | 379.75 | 1148.89 | 56.75 | 0.00 | 0.00 | 0.00 |
October | 489.22 | 125.16 | 364.06 | 1024.29 | 74.49 | 0.00 | 0.00 | 0.00 |
November | 473.47 | 130.84 | 342.63 | 996.82 | 89.73 | 0.00 | 0.00 | 0.00 |
December | 484.52 | 155.49 | 329.03 | 1007.12 | 142.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.61 | 172.87 | 373.74 | 1192.19 | 73.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.47 | 113.15 | 329.03 | 996.82 | 28.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 645.87 | 250.25 | 399.12 | 1452.57 | 142.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1064.65 | 444.18 | 620.46 | 2243.41 | 207.53 | 0.00 | 0.00 | 0.00 |
February | 904.04 | 294.75 | 609.29 | 2052.00 | 154.38 | 0.00 | 0.00 | 0.00 |
March | 616.96 | 82.86 | 534.10 | 1550.91 | 98.38 | 0.00 | 0.00 | 0.00 |
April | 459.97 | 0.21 | 459.77 | 1214.28 | 40.74 | 0.00 | 0.00 | 0.00 |
May | 460.29 | 0.00 | 460.29 | 1246.28 | 51.09 | 0.00 | 0.00 | 0.00 |
June | 458.63 | 0.00 | 458.63 | 1237.60 | 56.44 | 0.00 | 0.00 | 0.00 |
July | 472.46 | 0.00 | 472.46 | 1103.05 | 106.36 | 0.00 | 0.00 | 0.00 |
August | 459.94 | 0.71 | 459.23 | 1083.21 | 77.63 | 0.00 | 0.00 | 0.00 |
September | 509.19 | 16.63 | 492.56 | 1221.78 | 85.15 | 0.00 | 0.00 | 0.00 |
October | 666.17 | 106.21 | 559.95 | 1466.33 | 118.30 | 0.00 | 0.00 | 0.00 |
November | 866.24 | 264.28 | 601.96 | 1855.88 | 145.36 | 0.00 | 0.00 | 0.00 |
December | 1064.10 | 452.73 | 611.37 | 2209.22 | 231.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 665.96 | 138.01 | 527.95 | 1537.85 | 114.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.63 | 0.00 | 458.63 | 1083.21 | 40.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1064.65 | 452.73 | 620.46 | 2243.41 | 231.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.76 | 184.17 | 339.59 | 1109.55 | 142.31 | 0.00 | 0.00 | 0.00 |
February | 575.23 | 203.56 | 371.67 | 1245.67 | 108.65 | 0.00 | 0.00 | 0.00 |
March | 644.79 | 254.68 | 390.11 | 1420.64 | 77.53 | 0.00 | 0.00 | 0.00 |
April | 647.98 | 248.19 | 399.80 | 1449.00 | 34.92 | 0.00 | 0.00 | 0.00 |
May | 551.36 | 163.34 | 388.02 | 1286.91 | 35.99 | 0.00 | 0.00 | 0.00 |
June | 597.47 | 205.93 | 391.54 | 1371.56 | 40.95 | 0.00 | 0.00 | 0.00 |
July | 509.37 | 120.12 | 389.25 | 1107.37 | 74.10 | 0.00 | 0.00 | 0.00 |
August | 553.79 | 164.00 | 389.79 | 1182.05 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 518.71 | 143.87 | 374.84 | 1138.54 | 59.40 | 0.00 | 0.00 | 0.00 |
October | 487.17 | 125.58 | 361.59 | 1021.58 | 77.95 | 0.00 | 0.00 | 0.00 |
November | 475.09 | 129.57 | 345.52 | 1006.04 | 94.08 | 0.00 | 0.00 | 0.00 |
December | 486.21 | 159.05 | 327.16 | 1029.85 | 153.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 547.22 | 174.87 | 372.35 | 1196.52 | 79.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.09 | 120.12 | 327.16 | 1006.04 | 34.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.98 | 254.68 | 399.80 | 1449.00 | 153.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.03 | 0.00 | 134.03 | 305.05 | 71.29 | 0.00 | 0.00 | 0.00 |
February | 142.97 | 0.00 | 142.97 | 342.08 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 372.83 | 36.54 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.42 | 418.45 | 16.11 | 0.00 | 0.00 | 0.00 |
May | 204.70 | 21.81 | 182.89 | 532.19 | 20.87 | 0.00 | 0.00 | 0.00 |
June | 250.05 | 50.53 | 199.51 | 631.16 | 24.22 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.48 | 496.16 | 41.86 | 0.00 | 0.00 | 0.00 |
August | 177.03 | 7.55 | 169.48 | 413.71 | 32.62 | 0.00 | 0.00 | 0.00 |
September | 150.72 | 0.07 | 150.65 | 364.40 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 325.65 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 310.88 | 49.49 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 292.92 | 80.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 400.60 | 41.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 292.92 | 16.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.05 | 50.53 | 199.51 | 631.16 | 80.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.04 | 0.00 | 134.04 | 305.07 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 142.98 | 0.00 | 142.98 | 342.09 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 372.85 | 36.54 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.43 | 418.47 | 16.11 | 0.00 | 0.00 | 0.00 |
May | 204.71 | 21.81 | 182.90 | 532.22 | 20.87 | 0.00 | 0.00 | 0.00 |
June | 250.06 | 50.53 | 199.52 | 631.19 | 24.22 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.49 | 496.18 | 41.87 | 0.00 | 0.00 | 0.00 |
August | 177.04 | 7.55 | 169.49 | 413.73 | 32.62 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 0.07 | 150.65 | 364.41 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 325.66 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 310.89 | 49.50 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 292.93 | 80.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 400.62 | 41.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 292.93 | 16.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.06 | 50.53 | 199.52 | 631.19 | 80.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 134.04 | 0.00 | 134.04 | 305.07 | 71.30 | 0.00 | 0.00 | 0.00 |
February | 142.98 | 0.00 | 142.98 | 342.09 | 55.40 | 0.00 | 0.00 | 0.00 |
March | 146.74 | 0.00 | 146.74 | 372.85 | 36.54 | 0.00 | 0.00 | 0.00 |
April | 159.69 | 2.26 | 157.43 | 418.47 | 16.11 | 0.00 | 0.00 | 0.00 |
May | 204.71 | 21.81 | 182.90 | 532.22 | 20.87 | 0.00 | 0.00 | 0.00 |
June | 250.06 | 50.53 | 199.52 | 631.19 | 24.22 | 0.00 | 0.00 | 0.00 |
July | 215.02 | 22.54 | 192.49 | 496.18 | 41.87 | 0.00 | 0.00 | 0.00 |
August | 177.04 | 7.55 | 169.49 | 413.73 | 32.62 | 0.00 | 0.00 | 0.00 |
September | 150.73 | 0.07 | 150.65 | 364.41 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 145.23 | 0.00 | 145.23 | 325.66 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 137.42 | 0.00 | 137.42 | 310.89 | 49.50 | 0.00 | 0.00 | 0.00 |
December | 130.21 | 0.00 | 130.21 | 292.93 | 80.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 166.25 | 8.75 | 157.50 | 400.62 | 41.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.21 | 0.00 | 130.21 | 292.93 | 16.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 250.06 | 50.53 | 199.52 | 631.19 | 80.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 497.26 | 167.59 | 329.67 | 1039.74 | 135.81 | 0.00 | 0.00 | 0.00 |
February | 563.89 | 206.75 | 357.14 | 1207.16 | 106.41 | 0.00 | 0.00 | 0.00 |
March | 614.74 | 240.73 | 374.01 | 1351.12 | 72.34 | 0.00 | 0.00 | 0.00 |
April | 621.29 | 237.36 | 383.93 | 1400.84 | 33.73 | 0.00 | 0.00 | 0.00 |
May | 534.05 | 161.66 | 372.40 | 1253.31 | 40.51 | 0.00 | 0.00 | 0.00 |
June | 568.81 | 187.34 | 381.48 | 1317.02 | 45.16 | 0.00 | 0.00 | 0.00 |
July | 485.85 | 108.84 | 377.00 | 1058.28 | 79.42 | 0.00 | 0.00 | 0.00 |
August | 534.68 | 157.17 | 377.51 | 1145.46 | 65.33 | 0.00 | 0.00 | 0.00 |
September | 502.13 | 136.83 | 365.30 | 1105.83 | 65.69 | 0.00 | 0.00 | 0.00 |
October | 470.61 | 120.40 | 350.21 | 988.04 | 81.53 | 0.00 | 0.00 | 0.00 |
November | 455.46 | 125.86 | 329.59 | 960.93 | 99.36 | 0.00 | 0.00 | 0.00 |
December | 466.09 | 149.57 | 316.51 | 969.04 | 153.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 525.81 | 166.29 | 359.52 | 1148.75 | 81.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.46 | 108.84 | 316.51 | 960.93 | 33.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 621.29 | 240.73 | 383.93 | 1400.84 | 153.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.66 | 6.63 | 13.03 | 41.11 | 5.37 | 0.00 | 0.00 | 0.00 |
February | 22.30 | 8.17 | 14.12 | 47.73 | 4.21 | 0.00 | 0.00 | 0.00 |
March | 24.31 | 9.52 | 14.79 | 53.42 | 2.86 | 0.00 | 0.00 | 0.00 |
April | 24.57 | 9.38 | 15.18 | 55.39 | 1.33 | 0.00 | 0.00 | 0.00 |
May | 21.12 | 6.39 | 14.72 | 49.55 | 1.60 | 0.00 | 0.00 | 0.00 |
June | 22.49 | 7.41 | 15.08 | 52.07 | 1.79 | 0.00 | 0.00 | 0.00 |
July | 19.21 | 4.30 | 14.91 | 41.84 | 3.14 | 0.00 | 0.00 | 0.00 |
August | 21.14 | 6.21 | 14.93 | 45.29 | 2.58 | 0.00 | 0.00 | 0.00 |
September | 19.85 | 5.41 | 14.44 | 43.72 | 2.60 | 0.00 | 0.00 | 0.00 |
October | 18.61 | 4.76 | 13.85 | 39.07 | 3.22 | 0.00 | 0.00 | 0.00 |
November | 18.01 | 4.98 | 13.03 | 37.99 | 3.93 | 0.00 | 0.00 | 0.00 |
December | 18.43 | 5.91 | 12.51 | 38.31 | 6.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.79 | 6.57 | 14.22 | 45.42 | 3.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.01 | 4.30 | 12.51 | 37.99 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.57 | 9.52 | 15.18 | 55.39 | 6.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.88 | 148.06 | 206.82 | 743.22 | 79.34 | 0.00 | 0.00 | 0.00 |
February | 301.34 | 98.25 | 203.10 | 678.51 | 61.16 | 0.00 | 0.00 | 0.00 |
March | 205.65 | 27.62 | 178.03 | 513.80 | 38.55 | 0.00 | 0.00 | 0.00 |
April | 153.32 | 0.07 | 153.25 | 402.78 | 15.44 | 0.00 | 0.00 | 0.00 |
May | 153.43 | 0.00 | 153.43 | 412.89 | 19.36 | 0.00 | 0.00 | 0.00 |
June | 152.88 | 0.00 | 152.88 | 408.69 | 21.01 | 0.00 | 0.00 | 0.00 |
July | 157.48 | 0.00 | 157.48 | 366.93 | 39.53 | 0.00 | 0.00 | 0.00 |
August | 153.31 | 0.24 | 153.08 | 357.90 | 30.96 | 0.00 | 0.00 | 0.00 |
September | 169.73 | 5.54 | 164.18 | 405.60 | 32.82 | 0.00 | 0.00 | 0.00 |
October | 222.05 | 35.40 | 186.65 | 488.22 | 44.47 | 0.00 | 0.00 | 0.00 |
November | 288.74 | 88.09 | 200.65 | 615.60 | 56.96 | 0.00 | 0.00 | 0.00 |
December | 354.69 | 150.91 | 203.79 | 732.39 | 89.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.98 | 46.00 | 175.98 | 509.74 | 44.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 0.00 | 152.88 | 357.90 | 15.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.88 | 150.91 | 206.82 | 743.22 | 89.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.88 | 148.06 | 206.82 | 743.22 | 79.34 | 0.00 | 0.00 | 0.00 |
February | 301.34 | 98.25 | 203.10 | 678.51 | 61.16 | 0.00 | 0.00 | 0.00 |
March | 205.65 | 27.62 | 178.03 | 513.80 | 38.55 | 0.00 | 0.00 | 0.00 |
April | 153.32 | 0.07 | 153.25 | 402.78 | 15.44 | 0.00 | 0.00 | 0.00 |
May | 153.43 | 0.00 | 153.43 | 412.89 | 19.36 | 0.00 | 0.00 | 0.00 |
June | 152.88 | 0.00 | 152.88 | 408.69 | 21.01 | 0.00 | 0.00 | 0.00 |
July | 157.48 | 0.00 | 157.48 | 366.93 | 39.53 | 0.00 | 0.00 | 0.00 |
August | 153.31 | 0.24 | 153.08 | 357.90 | 30.96 | 0.00 | 0.00 | 0.00 |
September | 169.73 | 5.54 | 164.18 | 405.60 | 32.82 | 0.00 | 0.00 | 0.00 |
October | 222.05 | 35.40 | 186.65 | 488.22 | 44.47 | 0.00 | 0.00 | 0.00 |
November | 288.74 | 88.09 | 200.65 | 615.60 | 56.96 | 0.00 | 0.00 | 0.00 |
December | 354.69 | 150.91 | 203.79 | 732.39 | 89.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.98 | 46.00 | 175.98 | 509.74 | 44.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.88 | 0.00 | 152.88 | 357.90 | 15.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.88 | 150.91 | 206.82 | 743.22 | 89.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.85 | 148.05 | 206.81 | 743.17 | 79.33 | 0.00 | 0.00 | 0.00 |
February | 301.32 | 98.24 | 203.08 | 678.46 | 61.16 | 0.00 | 0.00 | 0.00 |
March | 205.64 | 27.62 | 178.02 | 513.77 | 38.55 | 0.00 | 0.00 | 0.00 |
April | 153.31 | 0.07 | 153.24 | 402.75 | 15.44 | 0.00 | 0.00 | 0.00 |
May | 153.42 | 0.00 | 153.42 | 412.86 | 19.36 | 0.00 | 0.00 | 0.00 |
June | 152.87 | 0.00 | 152.87 | 408.67 | 21.00 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 0.00 | 157.47 | 366.91 | 39.53 | 0.00 | 0.00 | 0.00 |
August | 153.30 | 0.24 | 153.07 | 357.88 | 30.96 | 0.00 | 0.00 | 0.00 |
September | 169.72 | 5.54 | 164.17 | 405.57 | 32.82 | 0.00 | 0.00 | 0.00 |
October | 222.04 | 35.40 | 186.64 | 488.19 | 44.47 | 0.00 | 0.00 | 0.00 |
November | 288.72 | 88.08 | 200.64 | 615.56 | 56.95 | 0.00 | 0.00 | 0.00 |
December | 354.67 | 150.90 | 203.77 | 732.34 | 89.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 221.97 | 46.00 | 175.97 | 509.70 | 44.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 152.87 | 0.00 | 152.87 | 357.88 | 15.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 354.85 | 150.90 | 206.81 | 743.17 | 89.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 503.83 | 177.16 | 326.67 | 1067.15 | 150.65 | 0.00 | 0.00 | 0.00 |
February | 553.35 | 195.82 | 357.53 | 1199.53 | 119.50 | 0.00 | 0.00 | 0.00 |
March | 620.26 | 244.99 | 375.27 | 1369.89 | 86.76 | 0.00 | 0.00 | 0.00 |
April | 623.33 | 238.74 | 384.59 | 1395.99 | 41.13 | 0.00 | 0.00 | 0.00 |
May | 530.38 | 157.13 | 373.26 | 1237.69 | 42.09 | 0.00 | 0.00 | 0.00 |
June | 574.74 | 198.10 | 376.64 | 1319.69 | 47.47 | 0.00 | 0.00 | 0.00 |
July | 489.99 | 115.55 | 374.44 | 1065.67 | 83.24 | 0.00 | 0.00 | 0.00 |
August | 532.72 | 157.76 | 374.96 | 1135.07 | 68.17 | 0.00 | 0.00 | 0.00 |
September | 498.97 | 138.39 | 360.58 | 1094.55 | 69.08 | 0.00 | 0.00 | 0.00 |
October | 468.63 | 120.80 | 347.83 | 982.92 | 86.11 | 0.00 | 0.00 | 0.00 |
November | 457.01 | 124.64 | 332.37 | 967.05 | 104.67 | 0.00 | 0.00 | 0.00 |
December | 467.71 | 153.00 | 314.72 | 988.33 | 167.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 526.40 | 168.21 | 358.18 | 1151.11 | 88.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 457.01 | 115.55 | 314.72 | 967.05 | 41.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.33 | 244.99 | 384.59 | 1395.99 | 167.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.92 | 7.00 | 12.92 | 42.19 | 5.96 | 0.00 | 0.00 | 0.00 |
February | 21.88 | 7.74 | 14.14 | 47.43 | 4.73 | 0.00 | 0.00 | 0.00 |
March | 24.52 | 9.69 | 14.84 | 54.16 | 3.43 | 0.00 | 0.00 | 0.00 |
April | 24.65 | 9.44 | 15.21 | 55.20 | 1.63 | 0.00 | 0.00 | 0.00 |
May | 20.97 | 6.21 | 14.76 | 48.94 | 1.66 | 0.00 | 0.00 | 0.00 |
June | 22.72 | 7.83 | 14.89 | 52.18 | 1.88 | 0.00 | 0.00 | 0.00 |
July | 19.37 | 4.57 | 14.81 | 42.14 | 3.29 | 0.00 | 0.00 | 0.00 |
August | 21.06 | 6.24 | 14.83 | 44.88 | 2.70 | 0.00 | 0.00 | 0.00 |
September | 19.73 | 5.47 | 14.26 | 43.28 | 2.73 | 0.00 | 0.00 | 0.00 |
October | 18.53 | 4.78 | 13.75 | 38.86 | 3.40 | 0.00 | 0.00 | 0.00 |
November | 18.07 | 4.93 | 13.14 | 38.24 | 4.14 | 0.00 | 0.00 | 0.00 |
December | 18.49 | 6.05 | 12.44 | 39.08 | 6.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.81 | 6.65 | 14.16 | 45.51 | 3.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.07 | 4.57 | 12.44 | 38.24 | 1.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.65 | 9.69 | 15.21 | 55.20 | 6.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.11 | 0.00 | 402.11 | 918.23 | 211.52 | 0.00 | 0.00 | 0.00 |
February | 428.94 | 0.00 | 428.94 | 1029.64 | 162.52 | 0.00 | 0.00 | 0.00 |
March | 440.23 | 0.00 | 440.23 | 1122.28 | 106.50 | 0.00 | 0.00 | 0.00 |
April | 479.08 | 6.79 | 472.29 | 1260.63 | 46.16 | 0.00 | 0.00 | 0.00 |
May | 614.13 | 65.42 | 548.70 | 1603.31 | 56.57 | 0.00 | 0.00 | 0.00 |
June | 750.18 | 151.61 | 598.57 | 1902.22 | 64.15 | 0.00 | 0.00 | 0.00 |
July | 645.08 | 67.62 | 577.47 | 1495.22 | 114.08 | 0.00 | 0.00 | 0.00 |
August | 531.11 | 22.65 | 508.47 | 1250.14 | 86.98 | 0.00 | 0.00 | 0.00 |
September | 452.18 | 0.22 | 451.97 | 1101.45 | 86.22 | 0.00 | 0.00 | 0.00 |
October | 435.70 | 0.00 | 435.70 | 980.51 | 115.14 | 0.00 | 0.00 | 0.00 |
November | 412.27 | 0.00 | 412.27 | 936.16 | 142.75 | 0.00 | 0.00 | 0.00 |
December | 390.65 | 0.00 | 390.65 | 883.29 | 232.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 498.77 | 26.26 | 472.51 | 1207.36 | 118.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 390.65 | 0.00 | 390.65 | 883.29 | 46.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 750.18 | 151.61 | 598.57 | 1902.22 | 232.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.92 | 174.22 | 342.71 | 1083.66 | 133.42 | 0.00 | 0.00 | 0.00 |
February | 586.19 | 214.93 | 371.26 | 1258.40 | 101.31 | 0.00 | 0.00 | 0.00 |
March | 639.06 | 250.25 | 388.81 | 1407.36 | 65.32 | 0.00 | 0.00 | 0.00 |
April | 645.87 | 246.75 | 399.12 | 1462.36 | 28.91 | 0.00 | 0.00 | 0.00 |
May | 555.18 | 168.05 | 387.13 | 1310.37 | 36.26 | 0.00 | 0.00 | 0.00 |
June | 591.31 | 194.75 | 396.57 | 1376.33 | 40.08 | 0.00 | 0.00 | 0.00 |
July | 505.06 | 113.15 | 391.92 | 1106.19 | 72.95 | 0.00 | 0.00 | 0.00 |
August | 555.83 | 163.39 | 392.44 | 1197.34 | 56.76 | 0.00 | 0.00 | 0.00 |
September | 521.99 | 142.25 | 379.75 | 1156.21 | 57.53 | 0.00 | 0.00 | 0.00 |
October | 489.22 | 125.16 | 364.06 | 1030.30 | 76.50 | 0.00 | 0.00 | 0.00 |
November | 473.47 | 130.84 | 342.63 | 1001.94 | 94.07 | 0.00 | 0.00 | 0.00 |
December | 484.52 | 155.49 | 329.03 | 1010.65 | 148.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 546.61 | 172.87 | 373.74 | 1199.08 | 76.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.47 | 113.15 | 329.03 | 1001.94 | 28.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 645.87 | 250.25 | 399.12 | 1462.36 | 148.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1064.65 | 444.18 | 620.46 | 2248.76 | 215.02 | 0.00 | 0.00 | 0.00 |
February | 904.04 | 294.75 | 609.29 | 2060.08 | 161.31 | 0.00 | 0.00 | 0.00 |
March | 616.96 | 82.86 | 534.10 | 1561.80 | 101.97 | 0.00 | 0.00 | 0.00 |
April | 459.97 | 0.21 | 459.77 | 1227.15 | 41.59 | 0.00 | 0.00 | 0.00 |
May | 460.29 | 0.00 | 460.29 | 1258.54 | 52.26 | 0.00 | 0.00 | 0.00 |
June | 458.63 | 0.00 | 458.63 | 1249.91 | 56.84 | 0.00 | 0.00 | 0.00 |
July | 472.46 | 0.00 | 472.46 | 1114.10 | 108.06 | 0.00 | 0.00 | 0.00 |
August | 459.94 | 0.71 | 459.23 | 1090.90 | 80.85 | 0.00 | 0.00 | 0.00 |
September | 509.19 | 16.63 | 492.56 | 1232.38 | 86.55 | 0.00 | 0.00 | 0.00 |
October | 666.17 | 106.21 | 559.95 | 1475.19 | 121.35 | 0.00 | 0.00 | 0.00 |
November | 866.24 | 264.28 | 601.96 | 1863.37 | 151.72 | 0.00 | 0.00 | 0.00 |
December | 1064.10 | 452.73 | 611.37 | 2213.06 | 240.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 665.96 | 138.01 | 527.95 | 1547.12 | 118.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.63 | 0.00 | 458.63 | 1090.90 | 41.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1064.65 | 452.73 | 620.46 | 2248.76 | 240.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.76 | 184.17 | 339.59 | 1112.36 | 148.86 | 0.00 | 0.00 | 0.00 |
February | 575.23 | 203.56 | 371.67 | 1250.44 | 114.36 | 0.00 | 0.00 | 0.00 |
March | 644.79 | 254.68 | 390.11 | 1427.09 | 80.20 | 0.00 | 0.00 | 0.00 |
April | 647.98 | 248.19 | 399.80 | 1456.64 | 35.77 | 0.00 | 0.00 | 0.00 |
May | 551.36 | 163.34 | 388.02 | 1293.87 | 37.12 | 0.00 | 0.00 | 0.00 |
June | 597.47 | 205.93 | 391.54 | 1379.39 | 41.83 | 0.00 | 0.00 | 0.00 |
July | 509.37 | 120.12 | 389.25 | 1113.86 | 76.05 | 0.00 | 0.00 | 0.00 |
August | 553.79 | 164.00 | 389.79 | 1186.66 | 58.96 | 0.00 | 0.00 | 0.00 |
September | 518.71 | 143.87 | 374.84 | 1144.43 | 60.90 | 0.00 | 0.00 | 0.00 |
October | 487.17 | 125.58 | 361.59 | 1025.72 | 80.96 | 0.00 | 0.00 | 0.00 |
November | 475.09 | 129.57 | 345.52 | 1009.23 | 99.66 | 0.00 | 0.00 | 0.00 |
December | 486.21 | 159.05 | 327.16 | 1031.43 | 162.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 547.22 | 174.87 | 372.35 | 1201.71 | 83.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 475.09 | 120.12 | 327.16 | 1009.23 | 35.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.98 | 254.68 | 399.80 | 1456.64 | 162.19 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.244427E+10 | 0.543577E+09 |
February | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.247204E+10 | 0.375681E+09 |
March | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.297862E+10 | 0.277075E+09 |
April | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.323290E+10 | 0.118334E+09 |
May | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.425987E+10 | 0.149529E+09 |
June | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.489581E+10 | 0.166044E+09 |
July | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.397329E+10 | 0.301778E+09 |
August | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.332672E+10 | 0.225628E+09 |
September | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.282847E+10 | 0.220112E+09 |
October | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.260507E+10 | 0.299772E+09 |
November | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.240958E+10 | 0.351630E+09 |
December | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.235528E+10 | 0.592668E+09 |
Annual Sum or Average | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.377819E+11 | 0.362183E+10 |
Minimum of Months | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.235528E+10 | 0.118334E+09 |
Maximum of Months | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.489581E+10 | 0.592668E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.288999E+10 | 0.343958E+09 |
February | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.302889E+10 | 0.234021E+09 |
March | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.374704E+10 | 0.168666E+09 |
April | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.376507E+10 | 73460764.27 |
May | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.348614E+10 | 95638448.67 |
June | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.354388E+10 | 0.103718E+09 |
July | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.294211E+10 | 0.192883E+09 |
August | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.319123E+10 | 0.147304E+09 |
September | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.297793E+10 | 0.147092E+09 |
October | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.274346E+10 | 0.199514E+09 |
November | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.258376E+10 | 0.232571E+09 |
December | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.269748E+10 | 0.381128E+09 |
Annual Sum or Average | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.375970E+11 | 0.231996E+10 |
Minimum of Months | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.258376E+10 | 73460764.27 |
Maximum of Months | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.376507E+10 | 0.381128E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.600875E+10 | 0.555843E+09 |
February | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.496419E+10 | 0.373488E+09 |
March | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.415396E+10 | 0.263511E+09 |
April | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.314742E+10 | 0.105593E+09 |
May | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.333804E+10 | 0.136850E+09 |
June | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.320786E+10 | 0.146292E+09 |
July | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.295440E+10 | 0.284864E+09 |
August | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.290127E+10 | 0.207928E+09 |
September | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.316685E+10 | 0.220703E+09 |
October | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.392741E+10 | 0.316854E+09 |
November | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.481045E+10 | 0.376761E+09 |
December | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.591717E+10 | 0.618920E+09 |
Annual Sum or Average | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.484978E+11 | 0.360761E+10 |
Minimum of Months | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.290127E+10 | 0.105593E+09 |
Maximum of Months | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.600875E+10 | 0.618920E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.297181E+10 | 0.381156E+09 |
February | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.301353E+10 | 0.262844E+09 |
March | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.380504E+10 | 0.207669E+09 |
April | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.375582E+10 | 90514423.28 |
May | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.344687E+10 | 96385195.44 |
June | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.355507E+10 | 0.106154E+09 |
July | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.296599E+10 | 0.198459E+09 |
August | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.316600E+10 | 0.150451E+09 |
September | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.295109E+10 | 0.153974E+09 |
October | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.273619E+10 | 0.208793E+09 |
November | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.260766E+10 | 0.243862E+09 |
December | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.275834E+10 | 0.411358E+09 |
Annual Sum or Average | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.377334E+11 | 0.251162E+10 |
Minimum of Months | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.260766E+10 | 90514423.28 |
Maximum of Months | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.380504E+10 | 0.411358E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.358988E+09 | 0.00 | 0.358988E+09 | 0.817055E+09 | 0.190951E+09 |
February | 0.345883E+09 | 0.00 | 0.345883E+09 | 0.827548E+09 | 0.134024E+09 |
March | 0.393016E+09 | 0.00 | 0.393016E+09 | 0.998582E+09 | 97856864.53 |
April | 0.413908E+09 | 5865858.05 | 0.408043E+09 | 0.108463E+10 | 41746227.57 |
May | 0.548267E+09 | 58406913.62 | 0.489860E+09 | 0.142542E+10 | 55895112.63 |
June | 0.648123E+09 | 0.130981E+09 | 0.517143E+09 | 0.163597E+10 | 62777344.16 |
July | 0.575902E+09 | 60364849.74 | 0.515537E+09 | 0.132893E+10 | 0.112127E+09 |
August | 0.474155E+09 | 20218349.67 | 0.453937E+09 | 0.110808E+10 | 87374827.78 |
September | 0.390669E+09 | 187073.42 | 0.390482E+09 | 0.944516E+09 | 82079692.40 |
October | 0.388972E+09 | 0.00 | 0.388972E+09 | 0.872215E+09 | 0.106777E+09 |
November | 0.356181E+09 | 0.00 | 0.356181E+09 | 0.805800E+09 | 0.128289E+09 |
December | 0.348752E+09 | 0.00 | 0.348752E+09 | 0.784557E+09 | 0.214712E+09 |
Annual Sum or Average | 0.524282E+10 | 0.276024E+09 | 0.496679E+10 | 0.126333E+11 | 0.131461E+10 |
Minimum of Months | 0.345883E+09 | 0.00 | 0.345883E+09 | 0.784557E+09 | 41746227.57 |
Maximum of Months | 0.648123E+09 | 0.130981E+09 | 0.517143E+09 | 0.163597E+10 | 0.214712E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359002E+09 | 0.00 | 0.359002E+09 | 0.817094E+09 | 0.190960E+09 |
February | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.827589E+09 | 0.134029E+09 |
March | 0.393032E+09 | 0.00 | 0.393032E+09 | 0.998633E+09 | 97859530.24 |
April | 0.413925E+09 | 5866015.72 | 0.408059E+09 | 0.108469E+10 | 41746600.60 |
May | 0.548287E+09 | 58408483.62 | 0.489878E+09 | 0.142549E+10 | 55896237.63 |
June | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163604E+10 | 62779577.54 |
July | 0.575922E+09 | 60366472.37 | 0.515556E+09 | 0.132898E+10 | 0.112132E+09 |
August | 0.474173E+09 | 20218893.15 | 0.453954E+09 | 0.110813E+10 | 87377886.71 |
September | 0.390684E+09 | 187078.45 | 0.390497E+09 | 0.944560E+09 | 82082761.96 |
October | 0.388987E+09 | 0.00 | 0.388987E+09 | 0.872254E+09 | 0.106781E+09 |
November | 0.356194E+09 | 0.00 | 0.356194E+09 | 0.805836E+09 | 0.128295E+09 |
December | 0.348766E+09 | 0.00 | 0.348766E+09 | 0.784594E+09 | 0.214722E+09 |
Annual Sum or Average | 0.524302E+10 | 0.276031E+09 | 0.496699E+10 | 0.126339E+11 | 0.131466E+10 |
Minimum of Months | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.784594E+09 | 41746600.60 |
Maximum of Months | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163604E+10 | 0.214722E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.359002E+09 | 0.00 | 0.359002E+09 | 0.817094E+09 | 0.190960E+09 |
February | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.827589E+09 | 0.134029E+09 |
March | 0.393032E+09 | 0.00 | 0.393032E+09 | 0.998633E+09 | 97859530.24 |
April | 0.413925E+09 | 5866015.72 | 0.408059E+09 | 0.108469E+10 | 41746600.60 |
May | 0.548287E+09 | 58408483.62 | 0.489878E+09 | 0.142549E+10 | 55896237.63 |
June | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163604E+10 | 62779577.54 |
July | 0.575922E+09 | 60366472.37 | 0.515556E+09 | 0.132898E+10 | 0.112132E+09 |
August | 0.474173E+09 | 20218893.15 | 0.453954E+09 | 0.110813E+10 | 87377886.71 |
September | 0.390684E+09 | 187078.45 | 0.390497E+09 | 0.944560E+09 | 82082761.96 |
October | 0.388987E+09 | 0.00 | 0.388987E+09 | 0.872254E+09 | 0.106781E+09 |
November | 0.356194E+09 | 0.00 | 0.356194E+09 | 0.805836E+09 | 0.128295E+09 |
December | 0.348766E+09 | 0.00 | 0.348766E+09 | 0.784594E+09 | 0.214722E+09 |
Annual Sum or Average | 0.524302E+10 | 0.276031E+09 | 0.496699E+10 | 0.126339E+11 | 0.131466E+10 |
Minimum of Months | 0.345897E+09 | 0.00 | 0.345897E+09 | 0.784594E+09 | 41746600.60 |
Maximum of Months | 0.648146E+09 | 0.130984E+09 | 0.517162E+09 | 0.163604E+10 | 0.214722E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133185E+10 | 0.448870E+09 | 0.882980E+09 | 0.278485E+10 | 0.363742E+09 |
February | 0.136415E+10 | 0.500163E+09 | 0.863989E+09 | 0.292036E+10 | 0.257425E+09 |
March | 0.164653E+10 | 0.644769E+09 | 0.100176E+10 | 0.361883E+10 | 0.193755E+09 |
April | 0.161039E+10 | 0.615233E+09 | 0.995154E+09 | 0.363097E+10 | 87423304.87 |
May | 0.143041E+10 | 0.432981E+09 | 0.997431E+09 | 0.335687E+10 | 0.108494E+09 |
June | 0.147437E+10 | 0.485576E+09 | 0.988790E+09 | 0.341370E+10 | 0.117042E+09 |
July | 0.130129E+10 | 0.291519E+09 | 0.100977E+10 | 0.283450E+10 | 0.212707E+09 |
August | 0.143209E+10 | 0.420973E+09 | 0.101112E+10 | 0.306801E+10 | 0.174981E+09 |
September | 0.130153E+10 | 0.354670E+09 | 0.946857E+09 | 0.286631E+10 | 0.170264E+09 |
October | 0.126048E+10 | 0.322474E+09 | 0.938006E+09 | 0.264636E+10 | 0.218359E+09 |
November | 0.118054E+10 | 0.326236E+09 | 0.854304E+09 | 0.249072E+10 | 0.257546E+09 |
December | 0.124836E+10 | 0.400610E+09 | 0.847753E+09 | 0.259548E+10 | 0.412328E+09 |
Annual Sum or Average | 0.165820E+11 | 0.524407E+10 | 0.113379E+11 | 0.362270E+11 | 0.257407E+10 |
Minimum of Months | 0.118054E+10 | 0.291519E+09 | 0.847753E+09 | 0.249072E+10 | 87423304.87 |
Maximum of Months | 0.164653E+10 | 0.644769E+09 | 0.101112E+10 | 0.363097E+10 | 0.412328E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52660145.69 | 17747905.58 | 34912240.10 | 0.110110E+09 | 14382040.48 |
February | 53937353.26 | 19776011.67 | 34161341.59 | 0.115468E+09 | 10178335.09 |
March | 65102162.17 | 25493581.81 | 39608580.36 | 0.143085E+09 | 7660914.99 |
April | 63673235.12 | 24325746.10 | 39347489.02 | 0.143565E+09 | 3456638.76 |
May | 56557228.11 | 17119695.80 | 39437532.32 | 0.132728E+09 | 4289773.11 |
June | 58295072.81 | 19199225.68 | 39095847.13 | 0.134975E+09 | 4627734.13 |
July | 51451763.28 | 11526410.80 | 39925352.48 | 0.112074E+09 | 8410242.99 |
August | 56623620.63 | 16644873.82 | 39978746.81 | 0.121306E+09 | 6918578.92 |
September | 51461181.99 | 14023326.63 | 37437855.36 | 0.113331E+09 | 6732076.95 |
October | 49838260.44 | 12750344.95 | 37087915.50 | 0.104635E+09 | 8633702.39 |
November | 46677498.68 | 12899084.95 | 33778413.73 | 98480979.26 | 10183122.78 |
December | 49359125.00 | 15839742.50 | 33519382.50 | 0.102623E+09 | 16303072.62 |
Annual Sum or Average | 0.655637E+09 | 0.207346E+09 | 0.448291E+09 | 0.143238E+10 | 0.101776E+09 |
Minimum of Months | 46677498.68 | 11526410.80 | 33519382.50 | 98480979.26 | 3456638.76 |
Maximum of Months | 65102162.17 | 25493581.81 | 39978746.81 | 0.143565E+09 | 16303072.62 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950500E+09 | 0.396558E+09 | 0.553943E+09 | 0.199063E+10 | 0.212494E+09 |
February | 0.729011E+09 | 0.237684E+09 | 0.491328E+09 | 0.164144E+10 | 0.147959E+09 |
March | 0.550815E+09 | 73974117.02 | 0.476841E+09 | 0.137616E+10 | 0.103264E+09 |
April | 0.397414E+09 | 178399.50 | 0.397235E+09 | 0.104401E+10 | 40011731.22 |
May | 0.410940E+09 | 0.00 | 0.410940E+09 | 0.110587E+10 | 51845392.44 |
June | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.105933E+10 | 54445286.93 |
July | 0.421806E+09 | 0.00 | 0.421806E+09 | 0.982797E+09 | 0.105875E+09 |
August | 0.410632E+09 | 634632.62 | 0.409997E+09 | 0.958599E+09 | 82918549.85 |
September | 0.439934E+09 | 14368407.66 | 0.425565E+09 | 0.105131E+10 | 85067812.84 |
October | 0.594745E+09 | 94826739.91 | 0.499918E+09 | 0.130765E+10 | 0.119121E+09 |
November | 0.748416E+09 | 0.228330E+09 | 0.520085E+09 | 0.159563E+10 | 0.147632E+09 |
December | 0.950014E+09 | 0.404190E+09 | 0.545824E+09 | 0.196163E+10 | 0.239038E+09 |
Annual Sum or Average | 0.700048E+10 | 0.145074E+10 | 0.554974E+10 | 0.160751E+11 | 0.138967E+10 |
Minimum of Months | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.958599E+09 | 40011731.22 |
Maximum of Months | 0.950500E+09 | 0.404190E+09 | 0.553943E+09 | 0.199063E+10 | 0.239038E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950500E+09 | 0.396558E+09 | 0.553943E+09 | 0.199063E+10 | 0.212494E+09 |
February | 0.729011E+09 | 0.237684E+09 | 0.491328E+09 | 0.164144E+10 | 0.147959E+09 |
March | 0.550815E+09 | 73974117.02 | 0.476841E+09 | 0.137616E+10 | 0.103264E+09 |
April | 0.397414E+09 | 178399.50 | 0.397235E+09 | 0.104401E+10 | 40011731.22 |
May | 0.410940E+09 | 0.00 | 0.410940E+09 | 0.110587E+10 | 51845392.44 |
June | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.105933E+10 | 54445286.93 |
July | 0.421806E+09 | 0.00 | 0.421806E+09 | 0.982797E+09 | 0.105875E+09 |
August | 0.410632E+09 | 634632.62 | 0.409997E+09 | 0.958599E+09 | 82918549.85 |
September | 0.439934E+09 | 14368407.66 | 0.425565E+09 | 0.105131E+10 | 85067812.84 |
October | 0.594745E+09 | 94826739.91 | 0.499918E+09 | 0.130765E+10 | 0.119121E+09 |
November | 0.748416E+09 | 0.228330E+09 | 0.520085E+09 | 0.159563E+10 | 0.147632E+09 |
December | 0.950014E+09 | 0.404190E+09 | 0.545824E+09 | 0.196163E+10 | 0.239038E+09 |
Annual Sum or Average | 0.700048E+10 | 0.145074E+10 | 0.554974E+10 | 0.160751E+11 | 0.138967E+10 |
Minimum of Months | 0.396253E+09 | 0.00 | 0.396253E+09 | 0.958599E+09 | 40011731.22 |
Maximum of Months | 0.950500E+09 | 0.404190E+09 | 0.553943E+09 | 0.199063E+10 | 0.239038E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.950440E+09 | 0.396533E+09 | 0.553908E+09 | 0.199050E+10 | 0.212480E+09 |
February | 0.728965E+09 | 0.237669E+09 | 0.491297E+09 | 0.164134E+10 | 0.147950E+09 |
March | 0.550780E+09 | 73969442.28 | 0.476811E+09 | 0.137607E+10 | 0.103258E+09 |
April | 0.397389E+09 | 178388.23 | 0.397210E+09 | 0.104394E+10 | 40009202.70 |
May | 0.410914E+09 | 0.00 | 0.410914E+09 | 0.110580E+10 | 51842116.11 |
June | 0.396228E+09 | 0.00 | 0.396228E+09 | 0.105926E+10 | 54441846.30 |
July | 0.421779E+09 | 0.00 | 0.421779E+09 | 0.982735E+09 | 0.105868E+09 |
August | 0.410606E+09 | 634592.51 | 0.409971E+09 | 0.958539E+09 | 82913309.87 |
September | 0.439906E+09 | 14367499.66 | 0.425538E+09 | 0.105124E+10 | 85062437.04 |
October | 0.594708E+09 | 94820747.40 | 0.499887E+09 | 0.130757E+10 | 0.119113E+09 |
November | 0.748368E+09 | 0.228316E+09 | 0.520052E+09 | 0.159553E+10 | 0.147623E+09 |
December | 0.949954E+09 | 0.404165E+09 | 0.545789E+09 | 0.196150E+10 | 0.239023E+09 |
Annual Sum or Average | 0.700004E+10 | 0.145065E+10 | 0.554939E+10 | 0.160740E+11 | 0.138958E+10 |
Minimum of Months | 0.396228E+09 | 0.00 | 0.396228E+09 | 0.958539E+09 | 40009202.70 |
Maximum of Months | 0.950440E+09 | 0.404165E+09 | 0.553908E+09 | 0.199050E+10 | 0.239023E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134945E+10 | 0.474509E+09 | 0.874943E+09 | 0.285827E+10 | 0.403509E+09 |
February | 0.133866E+10 | 0.473718E+09 | 0.864941E+09 | 0.290190E+10 | 0.289102E+09 |
March | 0.166131E+10 | 0.656182E+09 | 0.100513E+10 | 0.366913E+10 | 0.232383E+09 |
April | 0.161567E+10 | 0.618822E+09 | 0.996846E+09 | 0.361841E+10 | 0.106610E+09 |
May | 0.142058E+10 | 0.420851E+09 | 0.999730E+09 | 0.331503E+10 | 0.112731E+09 |
June | 0.148972E+10 | 0.513469E+09 | 0.976250E+09 | 0.342063E+10 | 0.123045E+09 |
July | 0.131240E+10 | 0.309492E+09 | 0.100291E+10 | 0.285430E+10 | 0.222952E+09 |
August | 0.142684E+10 | 0.422547E+09 | 0.100429E+10 | 0.304016E+10 | 0.182598E+09 |
September | 0.129333E+10 | 0.358712E+09 | 0.934621E+09 | 0.283707E+10 | 0.179060E+09 |
October | 0.125518E+10 | 0.323558E+09 | 0.931626E+09 | 0.263265E+10 | 0.230637E+09 |
November | 0.118457E+10 | 0.323068E+09 | 0.861504E+09 | 0.250660E+10 | 0.271305E+09 |
December | 0.125273E+10 | 0.409788E+09 | 0.842939E+09 | 0.264715E+10 | 0.448010E+09 |
Annual Sum or Average | 0.166004E+11 | 0.530472E+10 | 0.112957E+11 | 0.363013E+11 | 0.280194E+10 |
Minimum of Months | 0.118457E+10 | 0.309492E+09 | 0.842939E+09 | 0.250660E+10 | 0.106610E+09 |
Maximum of Months | 0.166131E+10 | 0.656182E+09 | 0.100513E+10 | 0.366913E+10 | 0.448010E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53355979.96 | 18761608.46 | 34594371.51 | 0.113013E+09 | 15954364.37 |
February | 52929233.04 | 18730341.46 | 34198891.58 | 0.114738E+09 | 11430819.79 |
March | 65686454.75 | 25944774.78 | 39741679.96 | 0.145074E+09 | 9188207.37 |
April | 63881894.26 | 24467603.31 | 39414290.95 | 0.143068E+09 | 4215254.67 |
May | 56168334.98 | 16640018.50 | 39528316.48 | 0.131073E+09 | 4457254.48 |
June | 58902015.65 | 20302051.45 | 38599964.20 | 0.135248E+09 | 4865089.77 |
July | 51890886.15 | 12237012.32 | 39653873.84 | 0.112856E+09 | 8815285.82 |
August | 56415770.54 | 16707089.12 | 39708681.43 | 0.120205E+09 | 7219740.53 |
September | 51137097.82 | 14183118.72 | 36953979.10 | 0.112175E+09 | 7079853.71 |
October | 49628696.88 | 12793148.88 | 36835548.01 | 0.104092E+09 | 9119178.76 |
November | 46836773.01 | 12773757.78 | 34063015.23 | 99108405.05 | 10727132.24 |
December | 49531592.49 | 16202610.85 | 33328981.64 | 0.104666E+09 | 17713889.15 |
Annual Sum or Average | 0.656365E+09 | 0.209743E+09 | 0.446622E+09 | 0.143532E+10 | 0.110786E+09 |
Minimum of Months | 46836773.01 | 12237012.32 | 33328981.64 | 99108405.05 | 4215254.67 |
Maximum of Months | 65686454.75 | 25944774.78 | 39741679.96 | 0.145074E+09 | 17713889.15 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.245939E+10 | 0.566538E+09 |
February | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.249091E+10 | 0.393170E+09 |
March | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.300591E+10 | 0.285260E+09 |
April | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.326755E+10 | 0.119643E+09 |
May | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.429432E+10 | 0.151530E+09 |
June | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.493055E+10 | 0.166267E+09 |
July | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.400481E+10 | 0.305547E+09 |
August | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.334839E+10 | 0.232976E+09 |
September | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.285496E+10 | 0.223487E+09 |
October | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.262620E+10 | 0.308403E+09 |
November | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.242654E+10 | 0.370015E+09 |
December | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.236581E+10 | 0.623548E+09 |
Annual Sum or Average | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.380753E+11 | 0.374638E+10 |
Minimum of Months | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.236581E+10 | 0.119643E+09 |
Maximum of Months | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.493055E+10 | 0.623548E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.290249E+10 | 0.357342E+09 |
February | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.304431E+10 | 0.245090E+09 |
March | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.376947E+10 | 0.174965E+09 |
April | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.379045E+10 | 74938992.22 |
May | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.350969E+10 | 97122452.97 |
June | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.356745E+10 | 0.103900E+09 |
July | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.296282E+10 | 0.195400E+09 |
August | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.320695E+10 | 0.152024E+09 |
September | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.299690E+10 | 0.149130E+09 |
October | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.275955E+10 | 0.204896E+09 |
November | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.259703E+10 | 0.243817E+09 |
December | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.270694E+10 | 0.399043E+09 |
Annual Sum or Average | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.378140E+11 | 0.239767E+10 |
Minimum of Months | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.259703E+10 | 74938992.22 |
Maximum of Months | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.379045E+10 | 0.399043E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.602308E+10 | 0.575911E+09 |
February | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.498375E+10 | 0.390251E+09 |
March | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.418312E+10 | 0.273115E+09 |
April | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.318077E+10 | 0.107799E+09 |
May | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.337086E+10 | 0.139964E+09 |
June | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.323978E+10 | 0.147331E+09 |
July | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.298401E+10 | 0.289435E+09 |
August | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.292188E+10 | 0.216542E+09 |
September | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.319433E+10 | 0.224341E+09 |
October | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.395115E+10 | 0.325016E+09 |
November | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.482986E+10 | 0.393263E+09 |
December | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.592747E+10 | 0.645106E+09 |
Annual Sum or Average | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.487901E+11 | 0.372807E+10 |
Minimum of Months | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.292188E+10 | 0.107799E+09 |
Maximum of Months | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.602308E+10 | 0.645106E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.297935E+10 | 0.398695E+09 |
February | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.302506E+10 | 0.276650E+09 |
March | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.382232E+10 | 0.214795E+09 |
April | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.377562E+10 | 92713208.88 |
May | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.346551E+10 | 99431197.31 |
June | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.357538E+10 | 0.108414E+09 |
July | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.298336E+10 | 0.203703E+09 |
August | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.317836E+10 | 0.157913E+09 |
September | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.296637E+10 | 0.157857E+09 |
October | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.274729E+10 | 0.216851E+09 |
November | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.261591E+10 | 0.258317E+09 |
December | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.276259E+10 | 0.434416E+09 |
Annual Sum or Average | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.378971E+11 | 0.261975E+10 |
Minimum of Months | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.261591E+10 | 92713208.88 |
Maximum of Months | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.382232E+10 | 0.434416E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 912.59 | 202.95 | 402.11 | 0.00 | 402.11 | 0.00 | 0.00 |
February | 1021.84 | 155.29 | 428.94 | 0.00 | 428.94 | 0.00 | 0.00 |
March | 1112.09 | 103.45 | 440.23 | 0.00 | 440.23 | 0.00 | 0.00 |
April | 1247.26 | 45.65 | 479.08 | 6.79 | 472.29 | 0.00 | 0.00 |
May | 1590.45 | 55.83 | 614.13 | 65.42 | 548.70 | 0.00 | 0.00 |
June | 1888.81 | 64.06 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
July | 1483.46 | 112.67 | 645.08 | 67.62 | 577.47 | 0.00 | 0.00 |
August | 1242.05 | 84.24 | 531.11 | 22.65 | 508.47 | 0.00 | 0.00 |
September | 1091.23 | 84.92 | 452.18 | 0.22 | 451.97 | 0.00 | 0.00 |
October | 972.62 | 111.92 | 435.70 | 0.00 | 435.70 | 0.00 | 0.00 |
November | 929.62 | 135.66 | 412.27 | 0.00 | 412.27 | 0.00 | 0.00 |
December | 879.36 | 221.28 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Annual Sum or Average | 1198.06 | 114.85 | 498.77 | 26.26 | 472.51 | 0.00 | 0.00 |
Minimum of Months | 879.36 | 45.65 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Maximum of Months | 1888.81 | 221.28 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1079.00 | 128.42 | 516.92 | 174.22 | 342.71 | 0.00 | 0.00 |
February | 1252.02 | 96.73 | 586.19 | 214.93 | 371.26 | 0.00 | 0.00 |
March | 1398.98 | 62.97 | 639.06 | 250.25 | 388.81 | 0.00 | 0.00 |
April | 1452.57 | 28.34 | 645.87 | 246.75 | 399.12 | 0.00 | 0.00 |
May | 1301.57 | 35.71 | 555.18 | 168.05 | 387.13 | 0.00 | 0.00 |
June | 1367.24 | 40.01 | 591.31 | 194.75 | 396.57 | 0.00 | 0.00 |
July | 1098.46 | 72.01 | 505.06 | 113.15 | 391.92 | 0.00 | 0.00 |
August | 1191.47 | 55.00 | 555.83 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1148.89 | 56.75 | 521.99 | 142.25 | 379.75 | 0.00 | 0.00 |
October | 1024.29 | 74.49 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 996.82 | 89.73 | 473.47 | 130.84 | 342.63 | 0.00 | 0.00 |
December | 1007.12 | 142.30 | 484.52 | 155.49 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1192.19 | 73.57 | 546.61 | 172.87 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 996.82 | 28.34 | 473.47 | 113.15 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1452.57 | 142.30 | 645.87 | 250.25 | 399.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2243.41 | 207.53 | 1064.65 | 444.18 | 620.46 | 0.00 | 0.00 |
February | 2052.00 | 154.38 | 904.04 | 294.75 | 609.29 | 0.00 | 0.00 |
March | 1550.91 | 98.38 | 616.96 | 82.86 | 534.10 | 0.00 | 0.00 |
April | 1214.28 | 40.74 | 459.97 | 0.21 | 459.77 | 0.00 | 0.00 |
May | 1246.28 | 51.09 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
June | 1237.60 | 56.44 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
July | 1103.05 | 106.36 | 472.46 | 0.00 | 472.46 | 0.00 | 0.00 |
August | 1083.21 | 77.63 | 459.94 | 0.71 | 459.23 | 0.00 | 0.00 |
September | 1221.78 | 85.15 | 509.19 | 16.63 | 492.56 | 0.00 | 0.00 |
October | 1466.33 | 118.30 | 666.17 | 106.21 | 559.95 | 0.00 | 0.00 |
November | 1855.88 | 145.36 | 866.24 | 264.28 | 601.96 | 0.00 | 0.00 |
December | 2209.22 | 231.08 | 1064.10 | 452.73 | 611.37 | 0.00 | 0.00 |
Annual Sum or Average | 1537.85 | 114.40 | 665.96 | 138.01 | 527.95 | 0.00 | 0.00 |
Minimum of Months | 1083.21 | 40.74 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
Maximum of Months | 2243.41 | 231.08 | 1064.65 | 452.73 | 620.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1109.55 | 142.31 | 523.76 | 184.17 | 339.59 | 0.00 | 0.00 |
February | 1245.67 | 108.65 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1420.64 | 77.53 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1449.00 | 34.92 | 647.98 | 248.19 | 399.80 | 0.00 | 0.00 |
May | 1286.91 | 35.99 | 551.36 | 163.34 | 388.02 | 0.00 | 0.00 |
June | 1371.56 | 40.95 | 597.47 | 205.93 | 391.54 | 0.00 | 0.00 |
July | 1107.37 | 74.10 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1182.05 | 56.17 | 553.79 | 164.00 | 389.79 | 0.00 | 0.00 |
September | 1138.54 | 59.40 | 518.71 | 143.87 | 374.84 | 0.00 | 0.00 |
October | 1021.58 | 77.95 | 487.17 | 125.58 | 361.59 | 0.00 | 0.00 |
November | 1006.04 | 94.08 | 475.09 | 129.57 | 345.52 | 0.00 | 0.00 |
December | 1029.85 | 153.58 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1196.52 | 79.64 | 547.22 | 174.87 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1006.04 | 34.92 | 475.09 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1449.00 | 153.58 | 647.98 | 254.68 | 399.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 915.19 | 213.89 | 402.10 | 0.00 | 402.10 | 0.00 | 0.00 |
February | 1026.26 | 166.20 | 428.93 | 0.00 | 428.93 | 0.00 | 0.00 |
March | 1118.52 | 109.61 | 440.22 | 0.00 | 440.22 | 0.00 | 0.00 |
April | 1255.40 | 48.32 | 479.07 | 6.79 | 472.28 | 0.00 | 0.00 |
May | 1596.62 | 62.61 | 614.11 | 65.42 | 548.69 | 0.00 | 0.00 |
June | 1893.53 | 72.66 | 750.16 | 151.60 | 598.56 | 0.00 | 0.00 |
July | 1488.53 | 125.59 | 645.07 | 67.61 | 577.45 | 0.00 | 0.00 |
August | 1241.17 | 97.87 | 531.10 | 22.65 | 508.45 | 0.00 | 0.00 |
September | 1093.22 | 95.00 | 452.17 | 0.22 | 451.96 | 0.00 | 0.00 |
October | 976.97 | 119.60 | 435.69 | 0.00 | 435.69 | 0.00 | 0.00 |
November | 932.67 | 148.49 | 412.26 | 0.00 | 412.26 | 0.00 | 0.00 |
December | 878.79 | 240.50 | 390.64 | 0.00 | 390.64 | 0.00 | 0.00 |
Annual Sum or Average | 1201.83 | 125.06 | 498.76 | 26.26 | 472.50 | 0.00 | 0.00 |
Minimum of Months | 878.79 | 48.32 | 390.64 | 0.00 | 390.64 | 0.00 | 0.00 |
Maximum of Months | 1893.53 | 240.50 | 750.16 | 151.60 | 598.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1080.85 | 141.18 | 516.92 | 174.22 | 342.70 | 0.00 | 0.00 |
February | 1254.89 | 110.62 | 586.18 | 214.92 | 371.26 | 0.00 | 0.00 |
March | 1404.54 | 75.20 | 639.05 | 250.25 | 388.80 | 0.00 | 0.00 |
April | 1456.22 | 35.06 | 645.86 | 246.74 | 399.11 | 0.00 | 0.00 |
May | 1302.87 | 42.11 | 555.17 | 168.05 | 387.12 | 0.00 | 0.00 |
June | 1369.09 | 46.94 | 591.30 | 194.74 | 396.56 | 0.00 | 0.00 |
July | 1100.13 | 82.56 | 505.06 | 113.14 | 391.91 | 0.00 | 0.00 |
August | 1190.75 | 67.91 | 555.82 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1149.55 | 68.29 | 521.99 | 142.24 | 379.74 | 0.00 | 0.00 |
October | 1027.10 | 84.75 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 998.92 | 103.29 | 473.46 | 130.84 | 342.62 | 0.00 | 0.00 |
December | 1007.36 | 160.03 | 484.51 | 155.48 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1194.17 | 84.85 | 546.60 | 172.86 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 998.92 | 35.06 | 473.46 | 113.14 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1456.22 | 160.03 | 645.86 | 250.25 | 399.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2229.60 | 238.00 | 1064.61 | 444.16 | 620.44 | 0.00 | 0.00 |
February | 2035.48 | 183.48 | 904.01 | 294.74 | 609.27 | 0.00 | 0.00 |
March | 1541.36 | 115.66 | 616.94 | 82.85 | 534.09 | 0.00 | 0.00 |
April | 1208.31 | 46.31 | 459.96 | 0.21 | 459.75 | 0.00 | 0.00 |
May | 1238.63 | 58.07 | 460.27 | 0.00 | 460.27 | 0.00 | 0.00 |
June | 1226.05 | 63.01 | 458.62 | 0.00 | 458.62 | 0.00 | 0.00 |
July | 1100.78 | 118.58 | 472.44 | 0.00 | 472.44 | 0.00 | 0.00 |
August | 1073.68 | 92.87 | 459.93 | 0.71 | 459.22 | 0.00 | 0.00 |
September | 1216.77 | 98.46 | 509.17 | 16.63 | 492.54 | 0.00 | 0.00 |
October | 1464.63 | 133.42 | 666.14 | 106.21 | 559.93 | 0.00 | 0.00 |
November | 1846.76 | 170.87 | 866.20 | 264.27 | 601.94 | 0.00 | 0.00 |
December | 2197.12 | 267.73 | 1064.06 | 452.71 | 611.35 | 0.00 | 0.00 |
Annual Sum or Average | 1529.18 | 132.20 | 665.94 | 138.01 | 527.93 | 0.00 | 0.00 |
Minimum of Months | 1073.68 | 46.31 | 458.62 | 0.00 | 458.62 | 0.00 | 0.00 |
Maximum of Months | 2229.60 | 267.73 | 1064.61 | 452.71 | 620.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1109.35 | 156.61 | 523.75 | 184.17 | 339.58 | 0.00 | 0.00 |
February | 1246.96 | 124.23 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1424.06 | 90.19 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1451.19 | 42.76 | 647.97 | 248.18 | 399.79 | 0.00 | 0.00 |
May | 1286.63 | 43.75 | 551.35 | 163.34 | 388.01 | 0.00 | 0.00 |
June | 1371.87 | 49.35 | 597.46 | 205.93 | 391.53 | 0.00 | 0.00 |
July | 1107.81 | 86.53 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1179.95 | 70.87 | 553.78 | 164.00 | 389.78 | 0.00 | 0.00 |
September | 1137.82 | 71.81 | 518.70 | 143.86 | 374.84 | 0.00 | 0.00 |
October | 1021.78 | 89.51 | 487.16 | 125.58 | 361.58 | 0.00 | 0.00 |
November | 1005.29 | 108.81 | 475.08 | 129.57 | 345.51 | 0.00 | 0.00 |
December | 1027.41 | 173.88 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1196.62 | 92.36 | 547.21 | 174.86 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1005.29 | 42.76 | 475.08 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1451.19 | 173.88 | 647.97 | 254.68 | 399.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 918.23 | 211.52 | 402.11 | 0.00 | 402.11 | 0.00 | 0.00 |
February | 1029.64 | 162.52 | 428.94 | 0.00 | 428.94 | 0.00 | 0.00 |
March | 1122.28 | 106.50 | 440.23 | 0.00 | 440.23 | 0.00 | 0.00 |
April | 1260.63 | 46.16 | 479.08 | 6.79 | 472.29 | 0.00 | 0.00 |
May | 1603.31 | 56.57 | 614.13 | 65.42 | 548.70 | 0.00 | 0.00 |
June | 1902.22 | 64.15 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
July | 1495.22 | 114.08 | 645.08 | 67.62 | 577.47 | 0.00 | 0.00 |
August | 1250.14 | 86.98 | 531.11 | 22.65 | 508.47 | 0.00 | 0.00 |
September | 1101.45 | 86.22 | 452.18 | 0.22 | 451.97 | 0.00 | 0.00 |
October | 980.51 | 115.14 | 435.70 | 0.00 | 435.70 | 0.00 | 0.00 |
November | 936.16 | 142.75 | 412.27 | 0.00 | 412.27 | 0.00 | 0.00 |
December | 883.29 | 232.81 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Annual Sum or Average | 1207.36 | 118.80 | 498.77 | 26.26 | 472.51 | 0.00 | 0.00 |
Minimum of Months | 883.29 | 46.16 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
Maximum of Months | 1902.22 | 232.81 | 750.18 | 151.61 | 598.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1083.66 | 133.42 | 516.92 | 174.22 | 342.71 | 0.00 | 0.00 |
February | 1258.40 | 101.31 | 586.19 | 214.93 | 371.26 | 0.00 | 0.00 |
March | 1407.36 | 65.32 | 639.06 | 250.25 | 388.81 | 0.00 | 0.00 |
April | 1462.36 | 28.91 | 645.87 | 246.75 | 399.12 | 0.00 | 0.00 |
May | 1310.37 | 36.26 | 555.18 | 168.05 | 387.13 | 0.00 | 0.00 |
June | 1376.33 | 40.08 | 591.31 | 194.75 | 396.57 | 0.00 | 0.00 |
July | 1106.19 | 72.95 | 505.06 | 113.15 | 391.92 | 0.00 | 0.00 |
August | 1197.34 | 56.76 | 555.83 | 163.39 | 392.44 | 0.00 | 0.00 |
September | 1156.21 | 57.53 | 521.99 | 142.25 | 379.75 | 0.00 | 0.00 |
October | 1030.30 | 76.50 | 489.22 | 125.16 | 364.06 | 0.00 | 0.00 |
November | 1001.94 | 94.07 | 473.47 | 130.84 | 342.63 | 0.00 | 0.00 |
December | 1010.65 | 148.99 | 484.52 | 155.49 | 329.03 | 0.00 | 0.00 |
Annual Sum or Average | 1199.08 | 76.03 | 546.61 | 172.87 | 373.74 | 0.00 | 0.00 |
Minimum of Months | 1001.94 | 28.91 | 473.47 | 113.15 | 329.03 | 0.00 | 0.00 |
Maximum of Months | 1462.36 | 148.99 | 645.87 | 250.25 | 399.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2248.76 | 215.02 | 1064.65 | 444.18 | 620.46 | 0.00 | 0.00 |
February | 2060.08 | 161.31 | 904.04 | 294.75 | 609.29 | 0.00 | 0.00 |
March | 1561.80 | 101.97 | 616.96 | 82.86 | 534.10 | 0.00 | 0.00 |
April | 1227.15 | 41.59 | 459.97 | 0.21 | 459.77 | 0.00 | 0.00 |
May | 1258.54 | 52.26 | 460.29 | 0.00 | 460.29 | 0.00 | 0.00 |
June | 1249.91 | 56.84 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
July | 1114.10 | 108.06 | 472.46 | 0.00 | 472.46 | 0.00 | 0.00 |
August | 1090.90 | 80.85 | 459.94 | 0.71 | 459.23 | 0.00 | 0.00 |
September | 1232.38 | 86.55 | 509.19 | 16.63 | 492.56 | 0.00 | 0.00 |
October | 1475.19 | 121.35 | 666.17 | 106.21 | 559.95 | 0.00 | 0.00 |
November | 1863.37 | 151.72 | 866.24 | 264.28 | 601.96 | 0.00 | 0.00 |
December | 2213.06 | 240.85 | 1064.10 | 452.73 | 611.37 | 0.00 | 0.00 |
Annual Sum or Average | 1547.12 | 118.22 | 665.96 | 138.01 | 527.95 | 0.00 | 0.00 |
Minimum of Months | 1090.90 | 41.59 | 458.63 | 0.00 | 458.63 | 0.00 | 0.00 |
Maximum of Months | 2248.76 | 240.85 | 1064.65 | 452.73 | 620.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1112.36 | 148.86 | 523.76 | 184.17 | 339.59 | 0.00 | 0.00 |
February | 1250.44 | 114.36 | 575.23 | 203.56 | 371.67 | 0.00 | 0.00 |
March | 1427.09 | 80.20 | 644.79 | 254.68 | 390.11 | 0.00 | 0.00 |
April | 1456.64 | 35.77 | 647.98 | 248.19 | 399.80 | 0.00 | 0.00 |
May | 1293.87 | 37.12 | 551.36 | 163.34 | 388.02 | 0.00 | 0.00 |
June | 1379.39 | 41.83 | 597.47 | 205.93 | 391.54 | 0.00 | 0.00 |
July | 1113.86 | 76.05 | 509.37 | 120.12 | 389.25 | 0.00 | 0.00 |
August | 1186.66 | 58.96 | 553.79 | 164.00 | 389.79 | 0.00 | 0.00 |
September | 1144.43 | 60.90 | 518.71 | 143.87 | 374.84 | 0.00 | 0.00 |
October | 1025.72 | 80.96 | 487.17 | 125.58 | 361.59 | 0.00 | 0.00 |
November | 1009.23 | 99.66 | 475.09 | 129.57 | 345.52 | 0.00 | 0.00 |
December | 1031.43 | 162.19 | 486.21 | 159.05 | 327.16 | 0.00 | 0.00 |
Annual Sum or Average | 1201.71 | 83.07 | 547.22 | 174.87 | 372.35 | 0.00 | 0.00 |
Minimum of Months | 1009.23 | 35.77 | 475.09 | 120.12 | 327.16 | 0.00 | 0.00 |
Maximum of Months | 1456.64 | 162.19 | 647.98 | 254.68 | 399.80 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244427E+10 | 0.543577E+09 | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.00 | 0.00 |
February | 0.247204E+10 | 0.375681E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
March | 0.297862E+10 | 0.277075E+09 | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.00 | 0.00 |
April | 0.323290E+10 | 0.118334E+09 | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.00 | 0.00 |
May | 0.425987E+10 | 0.149529E+09 | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.00 | 0.00 |
June | 0.489581E+10 | 0.166044E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
July | 0.397329E+10 | 0.301778E+09 | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.00 | 0.00 |
August | 0.332672E+10 | 0.225628E+09 | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.00 | 0.00 |
September | 0.282847E+10 | 0.220112E+09 | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.00 | 0.00 |
October | 0.260507E+10 | 0.299772E+09 | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.00 | 0.00 |
November | 0.240958E+10 | 0.351630E+09 | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.00 | 0.00 |
December | 0.235528E+10 | 0.592668E+09 | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377819E+11 | 0.362183E+10 | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235528E+10 | 0.118334E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.489581E+10 | 0.592668E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288999E+10 | 0.343958E+09 | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.00 | 0.00 |
February | 0.302889E+10 | 0.234021E+09 | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.00 | 0.00 |
March | 0.374704E+10 | 0.168666E+09 | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.00 | 0.00 |
April | 0.376507E+10 | 73460764.27 | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.00 | 0.00 |
May | 0.348614E+10 | 95638448.67 | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.00 | 0.00 |
June | 0.354388E+10 | 0.103718E+09 | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.00 | 0.00 |
July | 0.294211E+10 | 0.192883E+09 | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.00 | 0.00 |
August | 0.319123E+10 | 0.147304E+09 | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.00 | 0.00 |
September | 0.297793E+10 | 0.147092E+09 | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.00 | 0.00 |
October | 0.274346E+10 | 0.199514E+09 | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.00 | 0.00 |
November | 0.258376E+10 | 0.232571E+09 | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.00 | 0.00 |
December | 0.269748E+10 | 0.381128E+09 | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375970E+11 | 0.231996E+10 | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258376E+10 | 73460764.27 | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376507E+10 | 0.381128E+09 | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.600875E+10 | 0.555843E+09 | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.00 | 0.00 |
February | 0.496419E+10 | 0.373488E+09 | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.00 | 0.00 |
March | 0.415396E+10 | 0.263511E+09 | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.00 | 0.00 |
April | 0.314742E+10 | 0.105593E+09 | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.00 | 0.00 |
May | 0.333804E+10 | 0.136850E+09 | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.00 | 0.00 |
June | 0.320786E+10 | 0.146292E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
July | 0.295440E+10 | 0.284864E+09 | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.00 | 0.00 |
August | 0.290127E+10 | 0.207928E+09 | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.00 | 0.00 |
September | 0.316685E+10 | 0.220703E+09 | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.00 | 0.00 |
October | 0.392741E+10 | 0.316854E+09 | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.00 | 0.00 |
November | 0.481045E+10 | 0.376761E+09 | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.00 | 0.00 |
December | 0.591717E+10 | 0.618920E+09 | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.484978E+11 | 0.360761E+10 | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290127E+10 | 0.105593E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.600875E+10 | 0.618920E+09 | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297181E+10 | 0.381156E+09 | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.00 | 0.00 |
February | 0.301353E+10 | 0.262844E+09 | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.00 | 0.00 |
March | 0.380504E+10 | 0.207669E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
April | 0.375582E+10 | 90514423.28 | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.00 | 0.00 |
May | 0.344687E+10 | 96385195.44 | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.00 | 0.00 |
June | 0.355507E+10 | 0.106154E+09 | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.00 | 0.00 |
July | 0.296599E+10 | 0.198459E+09 | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.00 | 0.00 |
August | 0.316600E+10 | 0.150451E+09 | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.00 | 0.00 |
September | 0.295109E+10 | 0.153974E+09 | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.00 | 0.00 |
October | 0.273619E+10 | 0.208793E+09 | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.00 | 0.00 |
November | 0.260766E+10 | 0.243862E+09 | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.00 | 0.00 |
December | 0.275834E+10 | 0.411358E+09 | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377334E+11 | 0.251162E+10 | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260766E+10 | 90514423.28 | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380504E+10 | 0.411358E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245124E+10 | 0.572871E+09 | 0.107699E+10 | 0.00 | 0.107699E+10 | 0.00 | 0.00 |
February | 0.248273E+10 | 0.402081E+09 | 0.103768E+10 | 0.00 | 0.103768E+10 | 0.00 | 0.00 |
March | 0.299585E+10 | 0.293576E+09 | 0.117908E+10 | 0.00 | 0.117908E+10 | 0.00 | 0.00 |
April | 0.325400E+10 | 0.125239E+09 | 0.124176E+10 | 17597889.49 | 0.122416E+10 | 0.00 | 0.00 |
May | 0.427640E+10 | 0.167688E+09 | 0.164484E+10 | 0.175224E+09 | 0.146962E+10 | 0.00 | 0.00 |
June | 0.490804E+10 | 0.188336E+09 | 0.194442E+10 | 0.392949E+09 | 0.155147E+10 | 0.00 | 0.00 |
July | 0.398688E+10 | 0.336391E+09 | 0.172775E+10 | 0.181098E+09 | 0.154665E+10 | 0.00 | 0.00 |
August | 0.332434E+10 | 0.262131E+09 | 0.142250E+10 | 60656135.97 | 0.136185E+10 | 0.00 | 0.00 |
September | 0.283364E+10 | 0.246245E+09 | 0.117204E+10 | 561230.32 | 0.117148E+10 | 0.00 | 0.00 |
October | 0.261672E+10 | 0.320340E+09 | 0.116695E+10 | 0.00 | 0.116695E+10 | 0.00 | 0.00 |
November | 0.241747E+10 | 0.384879E+09 | 0.106857E+10 | 0.00 | 0.106857E+10 | 0.00 | 0.00 |
December | 0.235374E+10 | 0.644155E+09 | 0.104628E+10 | 0.00 | 0.104628E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.379011E+11 | 0.394393E+10 | 0.157289E+11 | 0.828086E+09 | 0.149008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235374E+10 | 0.125239E+09 | 0.103768E+10 | 0.00 | 0.103768E+10 | 0.00 | 0.00 |
Maximum of Months | 0.490804E+10 | 0.644155E+09 | 0.194442E+10 | 0.392949E+09 | 0.155147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289496E+10 | 0.378124E+09 | 0.138451E+10 | 0.466618E+09 | 0.917892E+09 | 0.00 | 0.00 |
February | 0.303582E+10 | 0.267603E+09 | 0.141809E+10 | 0.519939E+09 | 0.898150E+09 | 0.00 | 0.00 |
March | 0.376192E+10 | 0.201416E+09 | 0.171163E+10 | 0.670262E+09 | 0.104137E+10 | 0.00 | 0.00 |
April | 0.377453E+10 | 90879943.63 | 0.167406E+10 | 0.639558E+09 | 0.103450E+10 | 0.00 | 0.00 |
May | 0.348960E+10 | 0.112784E+09 | 0.148697E+10 | 0.450101E+09 | 0.103687E+10 | 0.00 | 0.00 |
June | 0.354868E+10 | 0.121670E+09 | 0.153266E+10 | 0.504775E+09 | 0.102789E+10 | 0.00 | 0.00 |
July | 0.294658E+10 | 0.221117E+09 | 0.135274E+10 | 0.303046E+09 | 0.104969E+10 | 0.00 | 0.00 |
August | 0.318931E+10 | 0.181899E+09 | 0.148872E+10 | 0.437617E+09 | 0.105110E+10 | 0.00 | 0.00 |
September | 0.297964E+10 | 0.176996E+09 | 0.135299E+10 | 0.368693E+09 | 0.984294E+09 | 0.00 | 0.00 |
October | 0.275100E+10 | 0.226992E+09 | 0.131032E+10 | 0.335225E+09 | 0.975094E+09 | 0.00 | 0.00 |
November | 0.258920E+10 | 0.267729E+09 | 0.122722E+10 | 0.339135E+09 | 0.888082E+09 | 0.00 | 0.00 |
December | 0.269810E+10 | 0.428631E+09 | 0.129772E+10 | 0.416449E+09 | 0.881272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376593E+11 | 0.267584E+10 | 0.172376E+11 | 0.545142E+10 | 0.117862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258920E+10 | 90879943.63 | 0.122722E+10 | 0.303046E+09 | 0.881272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.377453E+10 | 0.428631E+09 | 0.171163E+10 | 0.670262E+09 | 0.105110E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597176E+10 | 0.637468E+09 | 0.285144E+10 | 0.118965E+10 | 0.166179E+10 | 0.00 | 0.00 |
February | 0.492423E+10 | 0.443869E+09 | 0.218699E+10 | 0.713036E+09 | 0.147395E+10 | 0.00 | 0.00 |
March | 0.412839E+10 | 0.309786E+09 | 0.165241E+10 | 0.221918E+09 | 0.143049E+10 | 0.00 | 0.00 |
April | 0.313195E+10 | 0.120033E+09 | 0.119222E+10 | 535187.22 | 0.119168E+10 | 0.00 | 0.00 |
May | 0.331754E+10 | 0.155533E+09 | 0.123280E+10 | 0.00 | 0.123280E+10 | 0.00 | 0.00 |
June | 0.317792E+10 | 0.163332E+09 | 0.118873E+10 | 0.00 | 0.118873E+10 | 0.00 | 0.00 |
July | 0.294833E+10 | 0.317618E+09 | 0.126539E+10 | 0.00 | 0.126539E+10 | 0.00 | 0.00 |
August | 0.287574E+10 | 0.248750E+09 | 0.123187E+10 | 1903857.75 | 0.122997E+10 | 0.00 | 0.00 |
September | 0.315386E+10 | 0.255198E+09 | 0.131977E+10 | 43104314.98 | 0.127667E+10 | 0.00 | 0.00 |
October | 0.392287E+10 | 0.357354E+09 | 0.178420E+10 | 0.284474E+09 | 0.149972E+10 | 0.00 | 0.00 |
November | 0.478680E+10 | 0.442886E+09 | 0.224520E+10 | 0.684977E+09 | 0.156022E+10 | 0.00 | 0.00 |
December | 0.588475E+10 | 0.717100E+09 | 0.284998E+10 | 0.121255E+10 | 0.163744E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.482241E+11 | 0.416893E+10 | 0.210010E+11 | 0.435214E+10 | 0.166489E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287574E+10 | 0.120033E+09 | 0.118873E+10 | 0.00 | 0.118873E+10 | 0.00 | 0.00 |
Maximum of Months | 0.597176E+10 | 0.717100E+09 | 0.285144E+10 | 0.121255E+10 | 0.166179E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297128E+10 | 0.419464E+09 | 0.140281E+10 | 0.493271E+09 | 0.909537E+09 | 0.00 | 0.00 |
February | 0.301664E+10 | 0.300533E+09 | 0.139159E+10 | 0.492449E+09 | 0.899139E+09 | 0.00 | 0.00 |
March | 0.381420E+10 | 0.241572E+09 | 0.172699E+10 | 0.682127E+09 | 0.104487E+10 | 0.00 | 0.00 |
April | 0.376148E+10 | 0.110825E+09 | 0.167955E+10 | 0.643290E+09 | 0.103626E+10 | 0.00 | 0.00 |
May | 0.344610E+10 | 0.117188E+09 | 0.147675E+10 | 0.437491E+09 | 0.103926E+10 | 0.00 | 0.00 |
June | 0.355588E+10 | 0.127910E+09 | 0.154862E+10 | 0.533771E+09 | 0.101485E+10 | 0.00 | 0.00 |
July | 0.296716E+10 | 0.231767E+09 | 0.136429E+10 | 0.321729E+09 | 0.104256E+10 | 0.00 | 0.00 |
August | 0.316037E+10 | 0.189818E+09 | 0.148325E+10 | 0.439254E+09 | 0.104400E+10 | 0.00 | 0.00 |
September | 0.294924E+10 | 0.186140E+09 | 0.134447E+10 | 0.372896E+09 | 0.971575E+09 | 0.00 | 0.00 |
October | 0.273674E+10 | 0.239757E+09 | 0.130481E+10 | 0.336351E+09 | 0.968461E+09 | 0.00 | 0.00 |
November | 0.260571E+10 | 0.282032E+09 | 0.123141E+10 | 0.335841E+09 | 0.895567E+09 | 0.00 | 0.00 |
December | 0.275182E+10 | 0.465724E+09 | 0.130226E+10 | 0.425991E+09 | 0.876268E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377366E+11 | 0.291273E+10 | 0.172568E+11 | 0.551446E+10 | 0.117423E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260571E+10 | 0.110825E+09 | 0.123141E+10 | 0.321729E+09 | 0.876268E+09 | 0.00 | 0.00 |
Maximum of Months | 0.381420E+10 | 0.465724E+09 | 0.172699E+10 | 0.682127E+09 | 0.104487E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.245939E+10 | 0.566538E+09 | 0.107702E+10 | 0.00 | 0.107702E+10 | 0.00 | 0.00 |
February | 0.249091E+10 | 0.393170E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
March | 0.300591E+10 | 0.285260E+09 | 0.117910E+10 | 0.00 | 0.117910E+10 | 0.00 | 0.00 |
April | 0.326755E+10 | 0.119643E+09 | 0.124178E+10 | 17598406.75 | 0.122419E+10 | 0.00 | 0.00 |
May | 0.429432E+10 | 0.151530E+09 | 0.164488E+10 | 0.175229E+09 | 0.146965E+10 | 0.00 | 0.00 |
June | 0.493055E+10 | 0.166267E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
July | 0.400481E+10 | 0.305547E+09 | 0.172779E+10 | 0.181103E+09 | 0.154669E+10 | 0.00 | 0.00 |
August | 0.334839E+10 | 0.232976E+09 | 0.142253E+10 | 60657918.87 | 0.136188E+10 | 0.00 | 0.00 |
September | 0.285496E+10 | 0.223487E+09 | 0.117206E+10 | 561246.81 | 0.117150E+10 | 0.00 | 0.00 |
October | 0.262620E+10 | 0.308403E+09 | 0.116697E+10 | 0.00 | 0.116697E+10 | 0.00 | 0.00 |
November | 0.242654E+10 | 0.370015E+09 | 0.106859E+10 | 0.00 | 0.106859E+10 | 0.00 | 0.00 |
December | 0.236581E+10 | 0.623548E+09 | 0.104631E+10 | 0.00 | 0.104631E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.380753E+11 | 0.374638E+10 | 0.157292E+11 | 0.828110E+09 | 0.149011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236581E+10 | 0.119643E+09 | 0.103770E+10 | 0.00 | 0.103770E+10 | 0.00 | 0.00 |
Maximum of Months | 0.493055E+10 | 0.623548E+09 | 0.194446E+10 | 0.392960E+09 | 0.155150E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290249E+10 | 0.357342E+09 | 0.138453E+10 | 0.466627E+09 | 0.917904E+09 | 0.00 | 0.00 |
February | 0.304431E+10 | 0.245090E+09 | 0.141811E+10 | 0.519950E+09 | 0.898162E+09 | 0.00 | 0.00 |
March | 0.376947E+10 | 0.174965E+09 | 0.171165E+10 | 0.670276E+09 | 0.104138E+10 | 0.00 | 0.00 |
April | 0.379045E+10 | 74938992.22 | 0.167408E+10 | 0.639571E+09 | 0.103451E+10 | 0.00 | 0.00 |
May | 0.350969E+10 | 97122452.97 | 0.148699E+10 | 0.450110E+09 | 0.103688E+10 | 0.00 | 0.00 |
June | 0.356745E+10 | 0.103900E+09 | 0.153268E+10 | 0.504785E+09 | 0.102790E+10 | 0.00 | 0.00 |
July | 0.296282E+10 | 0.195400E+09 | 0.135276E+10 | 0.303052E+09 | 0.104971E+10 | 0.00 | 0.00 |
August | 0.320695E+10 | 0.152024E+09 | 0.148874E+10 | 0.437626E+09 | 0.105111E+10 | 0.00 | 0.00 |
September | 0.299690E+10 | 0.149130E+09 | 0.135301E+10 | 0.368700E+09 | 0.984308E+09 | 0.00 | 0.00 |
October | 0.275955E+10 | 0.204896E+09 | 0.131034E+10 | 0.335231E+09 | 0.975107E+09 | 0.00 | 0.00 |
November | 0.259703E+10 | 0.243817E+09 | 0.122724E+10 | 0.339142E+09 | 0.888095E+09 | 0.00 | 0.00 |
December | 0.270694E+10 | 0.399043E+09 | 0.129774E+10 | 0.416457E+09 | 0.881284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378140E+11 | 0.239767E+10 | 0.172379E+11 | 0.545153E+10 | 0.117864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259703E+10 | 74938992.22 | 0.122724E+10 | 0.303052E+09 | 0.881284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.379045E+10 | 0.399043E+09 | 0.171165E+10 | 0.670276E+09 | 0.105111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.602308E+10 | 0.575911E+09 | 0.285155E+10 | 0.118970E+10 | 0.166185E+10 | 0.00 | 0.00 |
February | 0.498375E+10 | 0.390251E+09 | 0.218706E+10 | 0.713065E+09 | 0.147400E+10 | 0.00 | 0.00 |
March | 0.418312E+10 | 0.273115E+09 | 0.165246E+10 | 0.221927E+09 | 0.143054E+10 | 0.00 | 0.00 |
April | 0.318077E+10 | 0.107799E+09 | 0.119225E+10 | 535209.43 | 0.119171E+10 | 0.00 | 0.00 |
May | 0.337086E+10 | 0.139964E+09 | 0.123283E+10 | 0.00 | 0.123283E+10 | 0.00 | 0.00 |
June | 0.323978E+10 | 0.147331E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
July | 0.298401E+10 | 0.289435E+09 | 0.126543E+10 | 0.00 | 0.126543E+10 | 0.00 | 0.00 |
August | 0.292188E+10 | 0.216542E+09 | 0.123191E+10 | 1903936.76 | 0.123000E+10 | 0.00 | 0.00 |
September | 0.319433E+10 | 0.224341E+09 | 0.131981E+10 | 43106103.77 | 0.127671E+10 | 0.00 | 0.00 |
October | 0.395115E+10 | 0.325016E+09 | 0.178426E+10 | 0.284486E+09 | 0.149977E+10 | 0.00 | 0.00 |
November | 0.482986E+10 | 0.393263E+09 | 0.224528E+10 | 0.685005E+09 | 0.156028E+10 | 0.00 | 0.00 |
December | 0.592747E+10 | 0.645106E+09 | 0.285009E+10 | 0.121260E+10 | 0.163749E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.487901E+11 | 0.372807E+10 | 0.210017E+11 | 0.435232E+10 | 0.166494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.292188E+10 | 0.107799E+09 | 0.118877E+10 | 0.00 | 0.118877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.602308E+10 | 0.645106E+09 | 0.285155E+10 | 0.121260E+10 | 0.166185E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297935E+10 | 0.398695E+09 | 0.140283E+10 | 0.493279E+09 | 0.909547E+09 | 0.00 | 0.00 |
February | 0.302506E+10 | 0.276650E+09 | 0.139161E+10 | 0.492457E+09 | 0.899149E+09 | 0.00 | 0.00 |
March | 0.382232E+10 | 0.214795E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
April | 0.377562E+10 | 92713208.88 | 0.167957E+10 | 0.643301E+09 | 0.103627E+10 | 0.00 | 0.00 |
May | 0.346551E+10 | 99431197.31 | 0.147677E+10 | 0.437498E+09 | 0.103927E+10 | 0.00 | 0.00 |
June | 0.357538E+10 | 0.108414E+09 | 0.154864E+10 | 0.533780E+09 | 0.101486E+10 | 0.00 | 0.00 |
July | 0.298336E+10 | 0.203703E+09 | 0.136431E+10 | 0.321735E+09 | 0.104257E+10 | 0.00 | 0.00 |
August | 0.317836E+10 | 0.157913E+09 | 0.148327E+10 | 0.439262E+09 | 0.104401E+10 | 0.00 | 0.00 |
September | 0.296637E+10 | 0.157857E+09 | 0.134449E+10 | 0.372902E+09 | 0.971586E+09 | 0.00 | 0.00 |
October | 0.274729E+10 | 0.216851E+09 | 0.130483E+10 | 0.336357E+09 | 0.968472E+09 | 0.00 | 0.00 |
November | 0.261591E+10 | 0.258317E+09 | 0.123142E+10 | 0.335847E+09 | 0.895577E+09 | 0.00 | 0.00 |
December | 0.276259E+10 | 0.434416E+09 | 0.130228E+10 | 0.425998E+09 | 0.876278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378971E+11 | 0.261975E+10 | 0.172570E+11 | 0.551455E+10 | 0.117425E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261591E+10 | 92713208.88 | 0.123142E+10 | 0.321735E+09 | 0.876278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.382232E+10 | 0.434416E+09 | 0.172702E+10 | 0.682138E+09 | 0.104488E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.309169E+10 | -0.286027E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231414882.6 | 60.05 | 0.00 | 0.00 |
February | 0.279275E+10 | -0.258354E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209207126.3 | 60.05 | 0.00 | 0.00 |
March | 0.324431E+10 | -0.301192E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232384767.7 | 60.05 | 0.00 | 0.00 |
April | 0.287827E+10 | -0.265355E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224719015.6 | 60.05 | 0.00 | 0.00 |
May | 0.301881E+10 | -0.278642E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232396559.1 | 60.05 | 0.00 | 0.00 |
June | 0.295368E+10 | -0.272880E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224883015.9 | 60.05 | 0.00 | 0.00 |
July | 0.278969E+10 | -0.255790E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231787147.5 | 60.05 | 0.00 | 0.00 |
August | 0.308050E+10 | -0.284818E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232317172.7 | 60.05 | 0.00 | 0.00 |
September | 0.283136E+10 | -0.260680E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224559071.2 | 60.05 | 0.00 | 0.00 |
October | 0.298238E+10 | -0.275070E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231674844.9 | 60.05 | 0.00 | 0.00 |
November | 0.298555E+10 | -0.276145E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224101526.9 | 60.05 | 0.00 | 0.00 |
December | 0.300260E+10 | -0.277121E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231387212.3 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.356516E+11 | -0.329208E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273083E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.278969E+10 | -0.301192E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -232396559.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.324431E+10 | -0.255790E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209207126.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:49 | 2217.28 | 25.16 | 147.67 | 323.00 | 1094.02 | 24.85 | 305.00 | 311.67 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1749.25 | 19.02 | 0.00 | 294.00 | 924.98 | 21.20 | 199.67 | 273.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1322.03 | 18.81 | 0.00 | 326.67 | 736.93 | 20.92 | 161.67 | 299.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 1084.11 | 18.46 | 0.00 | 323.50 | 616.08 | 20.60 | 68.50 | 287.00 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 927.95 | 17.37 | 0.00 | 330.00 | 516.69 | 19.47 | 0.00 | 282.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 906.21 | 17.54 | 0.00 | 323.00 | 521.19 | 19.71 | 0.00 | 277.33 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 877.96 | 16.93 | 0.00 | 326.17 | 477.26 | 18.99 | 0.00 | 275.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1038.11 | 17.88 | 0.00 | 327.67 | 568.58 | 19.97 | 35.67 | 286.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1173.42 | 17.74 | 0.00 | 314.00 | 617.96 | 19.78 | 85.33 | 275.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 1520.05 | 19.18 | 15.00 | 324.17 | 773.59 | 20.75 | 145.00 | 286.17 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:10 | 1921.19 | 23.57 | 114.83 | 313.00 | 941.98 | 21.73 | 232.67 | 281.83 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2226.60 | 25.19 | 148.67 | 319.83 | 1093.99 | 24.79 | 301.00 | 304.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1397.59 | 19.67 | 426.17 | 3845.00 | 732.81 | 21.02 | 1534.50 | 3440.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 877.96 | 16.93 | 0.00 | 294.00 | 477.26 | 18.99 | 0.00 | 273.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2226.60 | 25.19 | 148.67 | 330.00 | 1094.02 | 24.85 | 305.00 | 311.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1863.63 | 21.59 | 108.50 | 308.50 | 978.07 | 22.52 | 77.50 | 273.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2067.88 | 21.71 | 99.00 | 286.33 | 1089.39 | 22.63 | 71.17 | 258.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2346.86 | 21.75 | 112.17 | 321.83 | 974.57 | 21.26 | 52.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1935.09 | 19.98 | 84.17 | 328.33 | 1014.79 | 21.23 | 54.33 | 297.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1658.82 | 19.20 | 87.33 | 337.83 | 868.05 | 21.39 | 67.33 | 299.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1779.87 | 19.62 | 84.50 | 334.17 | 937.53 | 21.67 | 63.33 | 301.17 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:19 | 1480.12 | 18.89 | 86.67 | 336.17 | 760.80 | 20.89 | 64.17 | 293.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1688.00 | 19.55 | 86.00 | 336.50 | 874.58 | 20.78 | 55.00 | 298.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1593.46 | 18.96 | 83.67 | 313.83 | 815.86 | 20.14 | 54.50 | 274.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-06:10 | 1591.38 | 19.52 | 86.17 | 316.00 | 812.26 | 20.66 | 55.17 | 276.17 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1604.95 | 20.16 | 84.50 | 298.50 | 806.11 | 21.03 | 51.33 | 260.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1811.85 | 21.67 | 112.50 | 302.00 | 830.99 | 21.41 | 56.00 | 268.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1781.29 | 20.19 | 1115.17 | 3820.00 | 894.92 | 21.29 | 722.00 | 3394.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1480.12 | 18.89 | 83.67 | 286.33 | 760.80 | 20.14 | 51.33 | 258.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2346.86 | 21.75 | 112.50 | 337.83 | 1089.39 | 22.63 | 77.50 | 301.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-08:00 | 740.54 | 16.51 | 0.00 | 298.33 | 437.33 | 18.68 | 0.00 | 241.83 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-07:00 | 815.14 | 17.04 | 0.00 | 280.17 | 483.22 | 19.19 | 0.00 | 240.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 931.08 | 17.97 | 0.00 | 323.33 | 551.22 | 20.09 | 1.33 | 289.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1138.35 | 18.94 | 0.00 | 333.17 | 644.93 | 21.04 | 118.50 | 303.00 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1322.52 | 18.75 | 3.83 | 349.33 | 694.59 | 20.81 | 140.67 | 317.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1584.26 | 23.13 | 112.83 | 348.50 | 808.81 | 22.66 | 224.50 | 323.83 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1370.66 | 22.65 | 116.00 | 351.50 | 688.00 | 22.83 | 168.83 | 319.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:19 | 1227.61 | 18.66 | 0.00 | 342.83 | 658.49 | 20.75 | 122.67 | 308.33 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 996.49 | 17.46 | 0.00 | 314.83 | 539.39 | 19.48 | 42.00 | 273.83 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 880.76 | 17.24 | 0.00 | 311.50 | 483.80 | 19.28 | 0.00 | 260.67 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:49 | 788.33 | 16.86 | 0.00 | 288.50 | 444.15 | 18.94 | 0.00 | 235.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:40 | 721.09 | 16.27 | 0.00 | 291.17 | 420.66 | 18.43 | 0.00 | 233.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1052.55 | 18.52 | 232.67 | 3833.17 | 575.26 | 20.23 | 818.50 | 3347.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 721.09 | 16.27 | 0.00 | 280.17 | 420.66 | 18.43 | 0.00 | 233.50 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1584.26 | 23.13 | 116.00 | 351.50 | 808.81 | 22.83 | 224.50 | 323.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:30 | 1924.04 | 21.74 | 109.33 | 308.00 | 1007.36 | 22.60 | 77.50 | 275.17 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:20 | 2156.36 | 21.67 | 102.33 | 283.33 | 907.40 | 21.05 | 46.67 | 255.17 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:39 | 2393.35 | 21.49 | 112.67 | 331.33 | 992.19 | 20.94 | 51.17 | 298.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 2332.07 | 15.23 | 0.00 | 327.67 | 980.92 | 18.58 | 0.00 | 296.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1836.13 | 14.97 | 0.00 | 337.17 | 825.53 | 18.08 | 0.00 | 298.17 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1731.03 | 15.41 | 0.00 | 332.67 | 906.27 | 18.64 | 0.00 | 299.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1480.25 | 14.77 | 0.00 | 335.50 | 755.01 | 17.79 | 0.00 | 291.33 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1696.43 | 15.56 | 8.50 | 334.50 | 857.08 | 18.27 | 0.00 | 296.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:40 | 1748.23 | 18.76 | 87.00 | 311.50 | 793.60 | 18.02 | 7.67 | 275.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:20 | 1660.58 | 20.65 | 101.83 | 315.33 | 856.24 | 21.86 | 72.67 | 278.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:20 | 1640.54 | 19.93 | 85.00 | 299.83 | 850.09 | 22.00 | 66.00 | 264.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1703.56 | 20.04 | 90.00 | 305.17 | 902.69 | 22.07 | 71.83 | 270.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1854.60 | 18.26 | 696.67 | 3822.00 | 885.00 | 19.93 | 393.50 | 3398.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1480.25 | 14.77 | 0.00 | 283.33 | 755.01 | 17.79 | 0.00 | 255.17 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2393.35 | 21.74 | 112.67 | 337.17 | 1007.36 | 22.60 | 77.50 | 299.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 2126.19 | 22.71 | 147.50 | 322.33 | 1030.52 | 22.65 | 88.50 | 309.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1673.13 | 15.15 | 0.00 | 293.67 | 873.20 | 18.74 | 0.00 | 271.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1268.78 | 15.34 | 0.00 | 326.17 | 703.72 | 18.80 | 0.00 | 298.00 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1043.38 | 15.08 | 0.00 | 320.00 | 592.45 | 18.54 | 0.00 | 283.33 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 894.23 | 13.71 | 0.00 | 327.00 | 496.98 | 17.11 | 0.00 | 277.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 872.70 | 14.03 | 0.00 | 320.17 | 501.98 | 17.51 | 0.00 | 273.17 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 846.99 | 13.10 | 0.00 | 324.17 | 458.88 | 16.50 | 0.00 | 269.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 999.83 | 14.27 | 0.00 | 325.67 | 545.90 | 17.66 | 0.00 | 280.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1129.14 | 14.00 | 0.00 | 310.67 | 590.85 | 17.34 | 0.00 | 273.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:10 | 1459.27 | 15.43 | 15.00 | 322.67 | 735.49 | 18.35 | 4.50 | 281.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 1842.05 | 20.86 | 114.33 | 312.00 | 895.20 | 20.39 | 39.83 | 282.17 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2134.53 | 22.76 | 148.50 | 318.67 | 1029.85 | 22.54 | 87.50 | 302.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1342.19 | 16.29 | 425.33 | 3823.17 | 697.67 | 18.79 | 220.33 | 3402.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 846.99 | 13.10 | 0.00 | 293.67 | 458.88 | 16.50 | 0.00 | 269.50 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2134.53 | 22.76 | 148.50 | 327.00 | 1030.52 | 22.65 | 88.50 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1807.10 | 21.14 | 108.50 | 307.17 | 938.85 | 22.32 | 77.50 | 270.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-06:40 | 2014.93 | 21.26 | 99.00 | 285.50 | 1045.26 | 22.44 | 71.17 | 256.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2283.42 | 21.30 | 112.17 | 320.50 | 928.50 | 21.08 | 52.17 | 291.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1864.66 | 19.52 | 84.17 | 325.67 | 968.12 | 21.06 | 54.33 | 294.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1619.36 | 18.75 | 87.33 | 336.00 | 829.57 | 21.24 | 67.33 | 295.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1728.28 | 19.17 | 84.50 | 331.50 | 896.45 | 21.50 | 63.00 | 296.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:30 | 1439.62 | 18.44 | 86.67 | 333.00 | 721.35 | 19.99 | 56.33 | 288.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-05:00 | 1639.44 | 19.10 | 86.00 | 334.17 | 834.77 | 20.62 | 55.00 | 295.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1533.95 | 18.51 | 83.67 | 312.50 | 778.71 | 19.96 | 54.50 | 271.67 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-06:10 | 1548.23 | 19.04 | 86.17 | 313.83 | 775.91 | 20.45 | 55.17 | 272.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-06:40 | 1554.72 | 19.68 | 84.50 | 295.50 | 770.24 | 20.81 | 51.33 | 256.50 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-06:40 | 1760.10 | 21.22 | 112.50 | 300.00 | 794.26 | 21.19 | 56.00 | 265.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1729.07 | 19.73 | 1115.17 | 3795.33 | 854.85 | 21.04 | 713.83 | 3354.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1439.62 | 18.44 | 83.67 | 285.50 | 721.35 | 19.96 | 51.33 | 256.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2283.42 | 21.30 | 112.50 | 336.00 | 1045.26 | 22.44 | 77.50 | 296.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-09:09 | 713.59 | 13.04 | 0.00 | 295.17 | 422.31 | 16.52 | 0.00 | 235.00 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-08:09 | 785.59 | 13.66 | 0.00 | 277.67 | 466.75 | 17.13 | 0.00 | 235.50 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:20 | 896.76 | 14.69 | 0.00 | 320.00 | 532.01 | 18.14 | 0.00 | 286.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1095.30 | 15.53 | 0.00 | 330.67 | 619.82 | 19.03 | 0.00 | 299.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1271.76 | 14.92 | 3.83 | 347.17 | 662.92 | 18.30 | 1.17 | 314.00 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1522.57 | 20.47 | 112.17 | 347.67 | 769.29 | 20.36 | 33.17 | 319.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1319.34 | 19.90 | 115.67 | 350.17 | 655.38 | 20.56 | 59.17 | 315.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1180.95 | 14.95 | 0.00 | 340.50 | 630.11 | 18.40 | 0.00 | 304.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 960.21 | 13.80 | 0.00 | 313.00 | 517.84 | 17.13 | 0.00 | 270.50 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 849.42 | 13.52 | 0.00 | 309.83 | 465.41 | 16.90 | 0.00 | 256.00 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:00 | 760.35 | 13.19 | 0.00 | 286.00 | 428.05 | 16.61 | 0.00 | 229.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:49 | 694.91 | 12.71 | 0.00 | 289.00 | 405.97 | 16.17 | 0.00 | 228.00 |
Annual Sum or Average | 4292.33 | 0.53 | 1013.32 | 15.10 | 231.67 | 3806.83 | 551.75 | 17.98 | 93.50 | 3293.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 694.91 | 12.71 | 0.00 | 277.67 | 405.97 | 16.17 | 0.00 | 228.00 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1522.57 | 20.47 | 115.67 | 350.17 | 769.29 | 20.56 | 59.17 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1868.00 | 21.35 | 109.33 | 305.83 | 967.72 | 22.48 | 77.67 | 271.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:30 | 2102.21 | 21.27 | 102.33 | 282.00 | 864.92 | 20.92 | 46.67 | 252.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:50 | 2336.50 | 21.07 | 112.67 | 329.00 | 945.86 | 20.79 | 51.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 2253.95 | 14.67 | 0.00 | 325.83 | 935.14 | 18.37 | 0.00 | 294.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1796.97 | 14.40 | 0.00 | 335.50 | 787.76 | 17.85 | 0.00 | 294.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1683.94 | 14.83 | 0.00 | 330.83 | 865.34 | 18.41 | 0.00 | 295.50 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1440.92 | 14.19 | 0.00 | 333.83 | 721.16 | 17.55 | 0.00 | 289.67 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1644.99 | 15.01 | 8.50 | 332.33 | 818.14 | 18.05 | 0.00 | 291.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:49 | 1689.05 | 18.11 | 85.00 | 310.67 | 756.99 | 17.82 | 7.67 | 271.00 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-08:30 | 1601.22 | 18.93 | 87.50 | 312.67 | 819.97 | 21.73 | 72.67 | 275.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1588.65 | 19.49 | 85.00 | 298.17 | 813.81 | 21.88 | 66.00 | 260.50 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1646.43 | 19.38 | 87.33 | 303.67 | 864.59 | 21.95 | 71.83 | 267.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1800.63 | 17.63 | 677.67 | 3800.33 | 845.62 | 19.76 | 393.67 | 3356.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1440.92 | 14.19 | 0.00 | 282.00 | 721.16 | 17.55 | 0.00 | 252.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2336.50 | 21.35 | 112.67 | 335.50 | 967.72 | 22.48 | 77.67 | 295.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 2126.07 | 22.71 | 147.50 | 322.33 | 1030.43 | 22.65 | 88.50 | 309.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:10 | 1673.02 | 15.15 | 0.00 | 293.67 | 873.13 | 18.74 | 0.00 | 271.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:49 | 1268.71 | 15.35 | 0.00 | 326.17 | 703.67 | 18.80 | 0.00 | 298.00 |
April | 358.33 | 0.52 | 0.48 | 01-APR-07:19 | 1043.33 | 15.08 | 0.00 | 320.00 | 592.40 | 18.54 | 0.00 | 283.33 |
May | 376.33 | 0.53 | 0.48 | 01-MAY-07:10 | 894.18 | 13.71 | 0.00 | 327.00 | 496.94 | 17.11 | 0.00 | 277.00 |
June | 370.50 | 0.53 | 0.48 | 01-JUN-07:00 | 872.66 | 14.03 | 0.00 | 320.17 | 501.95 | 17.51 | 0.00 | 273.17 |
July | 383.17 | 0.54 | 0.48 | 01-JUL-07:30 | 846.94 | 13.10 | 0.00 | 324.17 | 458.84 | 16.50 | 0.00 | 269.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 999.77 | 14.28 | 0.00 | 325.67 | 545.86 | 17.67 | 0.00 | 280.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1129.06 | 14.01 | 0.00 | 310.67 | 590.80 | 17.34 | 0.00 | 273.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:10 | 1459.16 | 15.43 | 15.00 | 322.67 | 735.42 | 18.35 | 4.50 | 281.83 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:19 | 1841.93 | 20.86 | 114.33 | 312.00 | 895.11 | 20.39 | 39.83 | 282.17 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2134.41 | 22.76 | 148.50 | 318.67 | 1029.76 | 22.54 | 87.50 | 302.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1342.11 | 16.29 | 425.33 | 3823.17 | 697.61 | 18.80 | 220.33 | 3402.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 846.94 | 13.10 | 0.00 | 293.67 | 458.84 | 16.50 | 0.00 | 269.50 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2134.41 | 22.76 | 148.50 | 327.00 | 1030.43 | 22.65 | 88.50 | 309.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-07:19 | 1807.04 | 21.14 | 108.50 | 307.17 | 938.79 | 22.32 | 77.50 | 270.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-06:40 | 2014.87 | 21.27 | 99.00 | 285.50 | 1045.20 | 22.44 | 71.17 | 256.00 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-07:10 | 2283.37 | 21.30 | 112.17 | 320.50 | 928.44 | 21.08 | 52.17 | 291.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1864.60 | 19.52 | 84.17 | 325.67 | 968.05 | 21.06 | 54.33 | 294.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1619.29 | 18.75 | 87.33 | 336.00 | 829.51 | 21.24 | 67.33 | 295.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1728.21 | 19.17 | 84.50 | 331.50 | 896.39 | 21.50 | 63.00 | 296.67 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-06:30 | 1439.53 | 18.44 | 86.67 | 333.00 | 721.29 | 19.99 | 56.33 | 288.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-05:00 | 1639.36 | 19.10 | 86.00 | 334.17 | 834.71 | 20.62 | 55.00 | 295.83 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1533.87 | 18.51 | 83.67 | 312.50 | 778.65 | 19.96 | 54.50 | 271.67 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-06:10 | 1548.16 | 19.04 | 86.17 | 313.83 | 775.85 | 20.45 | 55.17 | 272.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-06:40 | 1554.65 | 19.68 | 84.50 | 295.50 | 770.18 | 20.81 | 51.33 | 256.50 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-06:40 | 1760.04 | 21.22 | 112.50 | 300.00 | 794.20 | 21.19 | 56.00 | 265.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1729.00 | 19.73 | 1115.17 | 3795.33 | 854.79 | 21.04 | 713.83 | 3354.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1439.53 | 18.44 | 83.67 | 285.50 | 721.29 | 19.96 | 51.33 | 256.00 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 2283.37 | 21.30 | 112.50 | 336.00 | 1045.20 | 22.44 | 77.50 | 296.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.55 | 0.48 | 01-JAN-09:09 | 713.57 | 13.04 | 0.00 | 295.17 | 422.28 | 16.52 | 0.00 | 235.00 |
February | 321.17 | 0.54 | 0.48 | 01-FEB-08:09 | 785.56 | 13.67 | 0.00 | 277.67 | 466.71 | 17.13 | 0.00 | 235.50 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:20 | 896.73 | 14.70 | 0.00 | 320.00 | 531.97 | 18.14 | 0.00 | 286.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1095.25 | 15.53 | 0.00 | 330.67 | 619.77 | 19.03 | 0.00 | 299.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1271.67 | 14.92 | 3.83 | 347.17 | 662.87 | 18.30 | 1.17 | 313.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1522.48 | 20.47 | 112.17 | 347.67 | 769.23 | 20.36 | 33.17 | 319.67 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1319.25 | 19.90 | 115.67 | 350.17 | 655.32 | 20.56 | 59.17 | 315.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1180.88 | 14.95 | 0.00 | 340.50 | 630.06 | 18.40 | 0.00 | 304.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 960.15 | 13.80 | 0.00 | 313.00 | 517.80 | 17.13 | 0.00 | 270.50 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 849.37 | 13.52 | 0.00 | 309.83 | 465.38 | 16.90 | 0.00 | 256.00 |
November | 337.67 | 0.54 | 0.48 | 01-NOV-07:00 | 760.31 | 13.19 | 0.00 | 286.00 | 428.02 | 16.61 | 0.00 | 229.17 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:49 | 694.88 | 12.72 | 0.00 | 289.00 | 405.94 | 16.17 | 0.00 | 228.00 |
Annual Sum or Average | 4292.33 | 0.53 | 1013.26 | 15.11 | 231.67 | 3806.83 | 551.71 | 17.98 | 93.50 | 3293.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 694.88 | 12.72 | 0.00 | 277.67 | 405.94 | 16.17 | 0.00 | 228.00 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1522.48 | 20.47 | 115.67 | 350.17 | 769.23 | 20.56 | 59.17 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-09:39 | 1867.94 | 21.35 | 109.33 | 305.83 | 967.66 | 22.48 | 77.67 | 271.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:30 | 2102.15 | 21.27 | 102.33 | 282.00 | 864.86 | 20.92 | 46.67 | 252.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:50 | 2336.44 | 21.07 | 112.67 | 329.00 | 945.80 | 20.79 | 51.17 | 294.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 2253.89 | 14.67 | 0.00 | 325.83 | 935.08 | 18.38 | 0.00 | 294.00 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1796.89 | 14.40 | 0.00 | 335.50 | 787.70 | 17.85 | 0.00 | 294.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-08:30 | 1683.87 | 14.84 | 0.00 | 330.83 | 865.28 | 18.41 | 0.00 | 295.50 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:00 | 1440.84 | 14.19 | 0.00 | 333.83 | 721.11 | 17.55 | 0.00 | 289.67 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1644.91 | 15.01 | 8.50 | 332.33 | 818.08 | 18.05 | 0.00 | 291.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:49 | 1688.98 | 18.11 | 85.00 | 310.67 | 756.93 | 17.82 | 7.67 | 271.00 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-08:30 | 1601.14 | 18.93 | 87.50 | 312.67 | 819.91 | 21.73 | 72.67 | 274.83 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1588.58 | 19.49 | 85.00 | 298.17 | 813.75 | 21.88 | 66.00 | 260.50 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:00 | 1646.38 | 19.38 | 87.33 | 303.67 | 864.53 | 21.95 | 71.83 | 267.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1800.56 | 17.63 | 677.67 | 3800.33 | 845.56 | 19.76 | 393.67 | 3356.50 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1440.84 | 14.19 | 0.00 | 282.00 | 721.11 | 17.55 | 0.00 | 252.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2336.44 | 21.35 | 112.67 | 335.50 | 967.66 | 22.48 | 77.67 | 295.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101151E+12 | 0.693661E+11 | 110266.42 | 09-JAN-05:02 | 76961.14 | 0.00 |
February | 0.00 | 0.00 | 0.954913E+11 | 0.655741E+11 | 105720.52 | 06-FEB-06:02 | 79828.64 | 0.00 |
March | 0.00 | 0.00 | 0.115774E+12 | 0.774720E+11 | 124664.54 | 28-MAR-04:02 | 81703.61 | 0.00 |
April | 0.00 | 0.00 | 0.120808E+12 | 0.739592E+11 | 125175.24 | 12-APR-04:02 | 81294.88 | 0.00 |
May | 0.00 | 0.00 | 0.138299E+12 | 0.787161E+11 | 130461.07 | 20-MAY-04:02 | 75323.18 | 0.00 |
June | 0.00 | 0.00 | 0.138936E+12 | 0.797039E+11 | 131519.24 | 10-JUN-04:02 | 76438.51 | 0.00 |
July | 0.00 | 0.00 | 0.111659E+12 | 0.690435E+11 | 114118.97 | 10-JUL-04:02 | 81543.00 | 0.00 |
August | 0.00 | 0.00 | 0.130376E+12 | 0.730022E+11 | 129879.82 | 07-AUG-04:02 | 79950.58 | 0.00 |
September | 0.00 | 0.00 | 0.118823E+12 | 0.678289E+11 | 125575.04 | 25-SEP-04:02 | 81526.62 | 0.00 |
October | 0.00 | 0.00 | 0.115485E+12 | 0.663399E+11 | 115125.27 | 05-OCT-04:02 | 74982.18 | 0.00 |
November | 0.00 | 0.00 | 0.107656E+12 | 0.659595E+11 | 116843.32 | 13-NOV-07:03 | 82499.78 | 0.00 |
December | 0.00 | 0.00 | 0.989210E+11 | 0.653277E+11 | 107749.49 | 04-DEC-07:03 | 78559.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.139338E+13 | 0.852293E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.954913E+11 | 0.653277E+11 | 105720.52 | 74982.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.138936E+12 | 0.797039E+11 | 131519.24 | 82499.78 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.866506E+11 | 0.578918E+11 | 107134.60 | 09-JAN-05:02 | 68170.48 | 0.00 |
February | 0.00 | 0.00 | 0.829888E+11 | 0.553682E+11 | 113997.82 | 06-FEB-06:02 | 72557.82 | 0.00 |
March | 0.00 | 0.00 | 0.100996E+12 | 0.655566E+11 | 116991.25 | 27-MAR-04:02 | 73546.42 | 0.00 |
April | 0.00 | 0.00 | 0.106330E+12 | 0.625305E+11 | 116920.60 | 12-APR-04:02 | 71853.73 | 0.00 |
May | 0.00 | 0.00 | 0.121182E+12 | 0.661001E+11 | 121197.09 | 22-MAY-04:02 | 66303.57 | 0.00 |
June | 0.00 | 0.00 | 0.121662E+12 | 0.667082E+11 | 120552.22 | 10-JUN-04:02 | 65066.64 | 0.00 |
July | 0.00 | 0.00 | 0.959244E+11 | 0.565832E+11 | 110643.28 | 10-JUL-04:02 | 73031.23 | 0.00 |
August | 0.00 | 0.00 | 0.112356E+12 | 0.595610E+11 | 122602.32 | 21-AUG-04:02 | 58566.36 | 0.00 |
September | 0.00 | 0.00 | 0.102887E+12 | 0.557560E+11 | 117421.20 | 25-SEP-04:02 | 71801.88 | 0.00 |
October | 0.00 | 0.00 | 0.995558E+11 | 0.546750E+11 | 118204.29 | 30-OCT-04:02 | 70720.88 | 0.00 |
November | 0.00 | 0.00 | 0.923610E+11 | 0.544715E+11 | 112933.30 | 13-NOV-05:02 | 73004.73 | 0.00 |
December | 0.00 | 0.00 | 0.850336E+11 | 0.541900E+11 | 96542.77 | 26-DEC-07:03 | 69905.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120793E+13 | 0.709392E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.829888E+11 | 0.541900E+11 | 96542.77 | 58566.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121662E+12 | 0.667082E+11 | 122602.32 | 73546.42 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.906283E+11 | 0.616796E+11 | 101905.43 | 09-JAN-05:02 | 62586.67 | 0.00 |
February | 0.00 | 0.00 | 0.873389E+11 | 0.595656E+11 | 124295.21 | 06-FEB-06:02 | 79341.01 | 0.00 |
March | 0.00 | 0.00 | 0.106940E+12 | 0.713687E+11 | 131951.68 | 20-MAR-04:02 | 85262.54 | 0.00 |
April | 0.00 | 0.00 | 0.112869E+12 | 0.687070E+11 | 132615.35 | 03-APR-04:02 | 85737.85 | 0.00 |
May | 0.00 | 0.00 | 0.127140E+12 | 0.718104E+11 | 140661.91 | 22-MAY-04:02 | 76267.31 | 0.00 |
June | 0.00 | 0.00 | 0.127953E+12 | 0.727948E+11 | 139786.72 | 10-JUN-05:03 | 71401.55 | 0.00 |
July | 0.00 | 0.00 | 0.100529E+12 | 0.610020E+11 | 120200.97 | 10-JUL-04:02 | 80243.59 | 0.00 |
August | 0.00 | 0.00 | 0.116678E+12 | 0.638849E+11 | 136869.07 | 12-AUG-05:03 | 72893.07 | 0.00 |
September | 0.00 | 0.00 | 0.107288E+12 | 0.601442E+11 | 126691.45 | 11-SEP-04:02 | 83800.87 | 0.00 |
October | 0.00 | 0.00 | 0.103010E+12 | 0.580687E+11 | 135129.77 | 30-OCT-04:02 | 78751.75 | 0.00 |
November | 0.00 | 0.00 | 0.959882E+11 | 0.580211E+11 | 112812.40 | 13-NOV-05:02 | 71162.24 | 0.00 |
December | 0.00 | 0.00 | 0.888566E+11 | 0.576860E+11 | 93202.15 | 26-DEC-07:03 | 64821.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126522E+13 | 0.764733E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.873389E+11 | 0.576860E+11 | 93202.15 | 62586.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127953E+12 | 0.727948E+11 | 140661.91 | 85737.85 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1059.41 | 3859.61 | 12-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1059.43 | 3850.50 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1115.80 | 3808.99 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1015.33 | 3729.68 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 1031.80 | 3654.06 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1044.17 | 3583.28 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 946.74 | 3548.83 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1054.75 | 3593.35 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 997.32 | 3662.52 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1018.56 | 3748.71 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1056.84 | 3817.28 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1026.28 | 3854.78 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1035.42 | ||||
Minimum of Months | 0.00 | 0.00 | 946.74 | 3548.83 | ||
Maximum of Months | 0.00 | 0.00 | 1115.80 | 3859.61 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403060E+10 | 0.46 | 10355.39 | 30-JAN-07:03 | 1.78 |
February | 0.382022E+10 | 0.47 | 10355.39 | 06-FEB-06:02 | 1.78 |
March | 0.444330E+10 | 0.49 | 10355.39 | 13-MAR-04:02 | 1.78 |
April | 0.414603E+10 | 0.48 | 10355.39 | 03-APR-04:02 | 1.78 |
May | 0.447833E+10 | 0.50 | 10355.39 | 01-MAY-06:03 | 1.78 |
June | 0.476169E+10 | 0.52 | 10355.39 | 05-JUN-06:03 | 1.78 |
July | 0.394419E+10 | 0.46 | 10355.39 | 05-JUL-06:03 | 1.78 |
August | 0.417306E+10 | 0.47 | 10355.39 | 07-AUG-04:02 | 1.78 |
September | 0.379817E+10 | 0.46 | 10355.39 | 05-SEP-04:02 | 1.78 |
October | 0.371300E+10 | 0.44 | 10355.39 | 16-OCT-04:02 | 1.78 |
November | 0.381260E+10 | 0.45 | 10355.39 | 13-NOV-07:03 | 1.78 |
December | 0.372629E+10 | 0.43 | 10355.39 | 04-DEC-07:03 | 1.78 |
Annual Sum or Average | 0.488475E+11 | 0.47 | |||
Minimum of Months | 0.371300E+10 | 0.43 | 10355.39 | 1.78 | |
Maximum of Months | 0.476169E+10 | 0.52 | 10355.39 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.311279E+10 | 0.41 | 8438.65 | 09-JAN-05:02 | 1.67 |
February | 0.298684E+10 | 0.43 | 9338.90 | 06-FEB-06:02 | 1.78 |
March | 0.340717E+10 | 0.45 | 9338.90 | 13-MAR-04:02 | 1.78 |
April | 0.312736E+10 | 0.43 | 9338.90 | 03-APR-04:02 | 1.78 |
May | 0.334934E+10 | 0.45 | 9338.90 | 02-MAY-04:02 | 1.78 |
June | 0.352998E+10 | 0.47 | 9338.90 | 05-JUN-04:02 | 1.78 |
July | 0.286845E+10 | 0.40 | 9338.90 | 03-JUL-04:02 | 1.78 |
August | 0.300562E+10 | 0.42 | 9338.90 | 02-AUG-04:02 | 1.78 |
September | 0.277211E+10 | 0.41 | 9338.90 | 05-SEP-04:02 | 1.78 |
October | 0.277140E+10 | 0.39 | 9338.90 | 10-OCT-04:02 | 1.78 |
November | 0.287843E+10 | 0.41 | 9338.90 | 13-NOV-05:02 | 1.78 |
December | 0.283961E+10 | 0.39 | 9338.90 | 26-DEC-07:03 | 1.78 |
Annual Sum or Average | 0.366491E+11 | 0.42 | |||
Minimum of Months | 0.277140E+10 | 0.39 | 8438.65 | 1.67 | |
Maximum of Months | 0.352998E+10 | 0.47 | 9338.90 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.299676E+10 | 0.38 | 6355.35 | 02-JAN-06:12 | 1.27 |
February | 0.291416E+10 | 0.40 | 10844.99 | 06-FEB-06:02 | 1.78 |
March | 0.340341E+10 | 0.42 | 10844.99 | 20-MAR-04:02 | 1.78 |
April | 0.316593E+10 | 0.41 | 10844.99 | 03-APR-04:02 | 1.78 |
May | 0.333525E+10 | 0.42 | 10844.99 | 08-MAY-04:02 | 1.78 |
June | 0.351908E+10 | 0.44 | 10760.75 | 12-JUN-04:02 | 1.77 |
July | 0.281405E+10 | 0.38 | 10456.81 | 31-JUL-04:02 | 1.74 |
August | 0.294499E+10 | 0.39 | 10795.37 | 14-AUG-04:02 | 1.77 |
September | 0.274496E+10 | 0.38 | 10844.99 | 05-SEP-04:02 | 1.78 |
October | 0.267332E+10 | 0.37 | 9939.18 | 16-OCT-04:02 | 1.68 |
November | 0.276689E+10 | 0.37 | 7572.22 | 13-NOV-05:02 | 1.42 |
December | 0.272382E+10 | 0.36 | 6928.35 | 26-DEC-07:03 | 1.34 |
Annual Sum or Average | 0.360026E+11 | 0.39 | |||
Minimum of Months | 0.267332E+10 | 0.36 | 6355.35 | 1.27 | |
Maximum of Months | 0.351908E+10 | 0.44 | 10844.99 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.84 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 58.16 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 58.13 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 58.23 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 58.22 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.30 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.32 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.31 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.28 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.82 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 58.20 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 58.18 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 58.13 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.84 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.84 | 58.84 | 1059.41 | 3859.61 | 12-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.54 | 58.54 | 1059.43 | 3850.50 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.56 | 58.56 | 1115.80 | 3808.99 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.59 | 58.59 | 1015.33 | 3729.68 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 58.90 | 58.90 | 1031.80 | 3654.06 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.65 | 58.65 | 1044.17 | 3583.28 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.67 | 58.67 | 946.74 | 3548.83 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.67 | 58.67 | 1054.75 | 3593.35 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.64 | 58.64 | 997.32 | 3662.52 | 29-SEP-11:17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.04 | 58.04 | 1018.56 | 3748.71 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.58 | 58.58 | 1056.84 | 3817.28 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.56 | 58.56 | 1026.28 | 3854.78 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1035.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.04 | 58.04 | 946.74 | 3548.83 | ||
Maximum of Months | 0.00 | 0.00 | 58.90 | 58.90 | 1115.80 | 3859.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.276639E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.264816E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.322434E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.329942E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.371932E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.377743E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.296138E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.340913E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.310944E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.298783E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.284235E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.265216E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.373973E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264816E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.377743E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.233066E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.226128E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.275278E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.282867E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.317835E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.321700E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247680E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.285645E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.262006E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.251778E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.238877E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.223707E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.316657E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.223707E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.321700E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.242478E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.236948E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.290716E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.299732E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.332908E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.337595E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.258599E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.295691E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.272614E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259292E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246808E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.232319E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.330570E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.232319E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.337595E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.403060E+10 | 0.101151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382022E+10 | 0.954913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444330E+10 | 0.115774E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414603E+10 | 0.120808E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447833E+10 | 0.138299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.476169E+10 | 0.138936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.394419E+10 | 0.111659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.417306E+10 | 0.130376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379817E+10 | 0.118823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371300E+10 | 0.115485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381260E+10 | 0.107656E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372629E+10 | 0.989210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488475E+11 | 0.139338E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371300E+10 | 0.954913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.476169E+10 | 0.138936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.311279E+10 | 0.866506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298684E+10 | 0.829888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340717E+10 | 0.100996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312736E+10 | 0.106330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334934E+10 | 0.121182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352998E+10 | 0.121662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286845E+10 | 0.959244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300562E+10 | 0.112356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.277211E+10 | 0.102887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277140E+10 | 0.995558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287843E+10 | 0.923610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283961E+10 | 0.850336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366491E+11 | 0.120793E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277140E+10 | 0.829888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352998E+10 | 0.121662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.299676E+10 | 0.906283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291416E+10 | 0.873389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340341E+10 | 0.106940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316593E+10 | 0.112869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.333525E+10 | 0.127140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.351908E+10 | 0.127953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281405E+10 | 0.100529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294499E+10 | 0.116678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274496E+10 | 0.107288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267332E+10 | 0.103010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276689E+10 | 0.959882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272382E+10 | 0.888566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360026E+11 | 0.126522E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267332E+10 | 0.873389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.351908E+10 | 0.127953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.403060E+10 | 0.00 | 0.00 | 0.00 | 0.236333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382022E+10 | 0.00 | 0.00 | 0.00 | 0.226613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444330E+10 | 0.00 | 0.00 | 0.00 | 0.278001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.414603E+10 | 0.00 | 0.00 | 0.00 | 0.288481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.447833E+10 | 0.00 | 0.00 | 0.00 | 0.327148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.476169E+10 | 0.00 | 0.00 | 0.00 | 0.330126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.394419E+10 | 0.00 | 0.00 | 0.00 | 0.256696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.417306E+10 | 0.00 | 0.00 | 0.00 | 0.299182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.379817E+10 | 0.00 | 0.00 | 0.00 | 0.272962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371300E+10 | 0.00 | 0.00 | 0.00 | 0.261653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381260E+10 | 0.00 | 0.00 | 0.00 | 0.246109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372629E+10 | 0.00 | 0.00 | 0.00 | 0.227953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488475E+11 | 0.00 | 0.00 | 0.00 | 0.325126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371300E+10 | 0.00 | 0.00 | 0.00 | 0.226613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.476169E+10 | 0.00 | 0.00 | 0.00 | 0.330126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.311279E+10 | 0.00 | 0.00 | 0.00 | 0.201938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298684E+10 | 0.00 | 0.00 | 0.00 | 0.196259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340717E+10 | 0.00 | 0.00 | 0.00 | 0.241206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312736E+10 | 0.00 | 0.00 | 0.00 | 0.251593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.334934E+10 | 0.00 | 0.00 | 0.00 | 0.284342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.352998E+10 | 0.00 | 0.00 | 0.00 | 0.286400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286845E+10 | 0.00 | 0.00 | 0.00 | 0.218996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300562E+10 | 0.00 | 0.00 | 0.00 | 0.255589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.277211E+10 | 0.00 | 0.00 | 0.00 | 0.234285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277140E+10 | 0.00 | 0.00 | 0.00 | 0.224064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.287843E+10 | 0.00 | 0.00 | 0.00 | 0.210093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283961E+10 | 0.00 | 0.00 | 0.00 | 0.195310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366491E+11 | 0.00 | 0.00 | 0.00 | 0.280007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277140E+10 | 0.00 | 0.00 | 0.00 | 0.195310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.352998E+10 | 0.00 | 0.00 | 0.00 | 0.286400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.299676E+10 | 0.00 | 0.00 | 0.00 | 0.212511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291416E+10 | 0.00 | 0.00 | 0.00 | 0.207807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340341E+10 | 0.00 | 0.00 | 0.00 | 0.256682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316593E+10 | 0.00 | 0.00 | 0.00 | 0.268073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.333525E+10 | 0.00 | 0.00 | 0.00 | 0.299555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.351908E+10 | 0.00 | 0.00 | 0.00 | 0.302405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281405E+10 | 0.00 | 0.00 | 0.00 | 0.230458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294499E+10 | 0.00 | 0.00 | 0.00 | 0.266241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274496E+10 | 0.00 | 0.00 | 0.00 | 0.245164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267332E+10 | 0.00 | 0.00 | 0.00 | 0.232558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276689E+10 | 0.00 | 0.00 | 0.00 | 0.219139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272382E+10 | 0.00 | 0.00 | 0.00 | 0.205081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360026E+11 | 0.00 | 0.00 | 0.00 | 0.294567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267332E+10 | 0.00 | 0.00 | 0.00 | 0.205081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.351908E+10 | 0.00 | 0.00 | 0.00 | 0.302405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1058606.34 | 0.121161E+11 | 0.00 | 55379.37 | 0.220569E+10 | 0.00 | 221619.68 | 0.00 | 0.34 |
February | 0.00 | 0.116501E+11 | 0.00 | 0.00 | 0.234282E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.156583E+11 | 0.00 | 0.00 | 0.236913E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.185387E+11 | 0.00 | 0.00 | 0.401954E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
May | 0.00 | 0.227337E+11 | 0.00 | 0.00 | 0.510913E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.228308E+11 | 0.00 | 0.00 | 0.409967E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.160471E+11 | 0.00 | 0.00 | 0.357431E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.228170E+11 | 0.00 | 0.00 | 0.313263E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.198180E+11 | 0.00 | 0.00 | 0.397112E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.191401E+11 | 0.00 | 0.00 | 0.352769E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.159330E+11 | 0.00 | 0.00 | 0.292361E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.126835E+11 | 0.00 | 0.00 | 0.264721E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 1058606.34 | 0.209967E+12 | 0.00 | 55379.37 | 0.399225E+11 | 0.00 | 221619.68 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.116501E+11 | 0.00 | 0.00 | 0.220569E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 1058606.34 | 0.228308E+11 | 0.00 | 55379.37 | 0.510913E+10 | 0.00 | 221619.68 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1636518.50 | 0.111278E+11 | 0.00 | 43153.86 | 0.207241E+10 | 0.00 | 1383163.04 | 0.00 | 0.30 |
February | 0.00 | 0.107474E+11 | 0.00 | 0.00 | 0.235833E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.143350E+11 | 0.00 | 0.00 | 0.269599E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
April | 0.00 | 0.171086E+11 | 0.00 | 0.00 | 0.437105E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.213075E+11 | 0.00 | 0.00 | 0.524367E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.215064E+11 | 0.00 | 0.00 | 0.437458E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.150028E+11 | 0.00 | 0.00 | 0.365679E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.213239E+11 | 0.00 | 0.00 | 0.355784E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.184405E+11 | 0.00 | 0.00 | 0.425449E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.175939E+11 | 0.00 | 0.00 | 0.366268E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.147758E+11 | 0.00 | 0.00 | 0.295060E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.117015E+11 | 0.00 | 0.00 | 0.250537E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 1636518.50 | 0.194971E+12 | 0.00 | 43153.86 | 0.417038E+11 | 0.00 | 1383163.04 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.107474E+11 | 0.00 | 0.00 | 0.207241E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 1636518.50 | 0.215064E+11 | 0.00 | 43153.86 | 0.524367E+10 | 0.00 | 1383163.04 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 383590.02 | 0.107733E+11 | 0.00 | 13455.89 | 0.211650E+10 | 0.00 | 91833.85 | 0.00 | 0.30 |
February | 0.00 | 0.104047E+11 | 0.00 | 0.00 | 0.237652E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.138245E+11 | 0.00 | 0.00 | 0.268836E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.165756E+11 | 0.00 | 0.00 | 0.449652E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.207680E+11 | 0.00 | 0.00 | 0.531216E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.208570E+11 | 0.00 | 0.00 | 0.455478E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.144754E+11 | 0.00 | 0.00 | 0.376675E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.206659E+11 | 0.00 | 0.00 | 0.368157E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.179134E+11 | 0.00 | 0.00 | 0.426218E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.170409E+11 | 0.00 | 0.00 | 0.378075E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.143314E+11 | 0.00 | 0.00 | 0.302769E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.111727E+11 | 0.00 | 0.00 | 0.279529E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 383590.02 | 0.188803E+12 | 0.00 | 13455.89 | 0.428591E+11 | 0.00 | 91833.85 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.104047E+11 | 0.00 | 0.00 | 0.211650E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 383590.02 | 0.208570E+11 | 0.00 | 13455.89 | 0.531216E+10 | 0.00 | 91833.85 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 102242.34 | 0.308196E+10 | 0.00 | 0.00 | 0.447185E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
February | 0.00 | 0.318835E+10 | 0.00 | 0.00 | 0.431521E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
March | 0.00 | 0.439986E+10 | 0.00 | 0.00 | 0.449847E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.572451E+10 | 0.00 | 0.00 | 0.717504E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.791869E+10 | 0.00 | 0.00 | 0.708005E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.867761E+10 | 0.00 | 0.00 | 0.485776E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.535054E+10 | 0.00 | 0.00 | 0.519886E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.688781E+10 | 0.00 | 0.00 | 0.584366E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.578577E+10 | 0.00 | 0.00 | 0.694941E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.513214E+10 | 0.00 | 0.00 | 0.634142E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.417417E+10 | 0.00 | 0.00 | 0.583495E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
December | 0.00 | 0.318142E+10 | 0.00 | 0.00 | 0.568251E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 102242.34 | 0.635028E+11 | 0.00 | 0.00 | 0.682492E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.308196E+10 | 0.00 | 0.00 | 0.431521E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 102242.34 | 0.867761E+10 | 0.00 | 0.00 | 0.717504E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 82422.93 | 0.257291E+10 | 0.00 | 0.00 | 0.297902E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.00 | 0.274362E+10 | 0.00 | 0.00 | 0.237125E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.379460E+10 | 0.00 | 0.00 | 0.300422E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.484388E+10 | 0.00 | 0.00 | 0.495077E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.567234E+10 | 0.00 | 0.00 | 0.594782E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.586406E+10 | 0.00 | 0.00 | 0.464518E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.366260E+10 | 0.00 | 0.00 | 0.467351E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.528702E+10 | 0.00 | 0.00 | 0.456371E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.468272E+10 | 0.00 | 0.00 | 0.477712E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.410816E+10 | 0.00 | 0.00 | 0.463178E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.335901E+10 | 0.00 | 0.00 | 0.382321E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.268696E+10 | 0.00 | 0.00 | 0.329799E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 82422.93 | 0.492779E+11 | 0.00 | 0.00 | 0.496656E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.257291E+10 | 0.00 | 0.00 | 0.237125E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 82422.93 | 0.586406E+10 | 0.00 | 0.00 | 0.594782E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 102237.68 | 0.466292E+10 | 0.00 | 0.00 | 0.246583E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
February | 0.00 | 0.446582E+10 | 0.00 | 0.00 | 0.274802E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.508600E+10 | 0.00 | 0.00 | 0.389601E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
April | 0.00 | 0.560221E+10 | 0.00 | 0.00 | 0.737596E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
May | 0.00 | 0.699607E+10 | 0.00 | 0.00 | 0.845987E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.701261E+10 | 0.00 | 0.00 | 0.675127E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.459443E+10 | 0.00 | 0.00 | 0.654036E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.644202E+10 | 0.00 | 0.00 | 0.631234E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.607373E+10 | 0.00 | 0.00 | 0.672631E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.615026E+10 | 0.00 | 0.00 | 0.514732E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.570967E+10 | 0.00 | 0.00 | 0.359938E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.495060E+10 | 0.00 | 0.00 | 0.297926E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 102237.68 | 0.677463E+11 | 0.00 | 0.00 | 0.630019E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.446582E+10 | 0.00 | 0.00 | 0.246583E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 102237.68 | 0.701261E+10 | 0.00 | 0.00 | 0.845987E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 95063.56 | 0.255229E+10 | 0.00 | 0.00 | 0.410117E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
February | 0.00 | 0.269469E+10 | 0.00 | 0.00 | 0.422746E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.379212E+10 | 0.00 | 0.00 | 0.418771E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.472931E+10 | 0.00 | 0.00 | 0.660597E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.543891E+10 | 0.00 | 0.00 | 0.845737E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.560474E+10 | 0.00 | 0.00 | 0.669275E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.353889E+10 | 0.00 | 0.00 | 0.658846E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.509222E+10 | 0.00 | 0.00 | 0.637977E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.449470E+10 | 0.00 | 0.00 | 0.687644E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.392849E+10 | 0.00 | 0.00 | 0.758637E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.00 | 0.328725E+10 | 0.00 | 0.00 | 0.603982E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.258271E+10 | 0.00 | 0.00 | 0.567961E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 95063.56 | 0.477363E+11 | 0.00 | 0.00 | 0.734229E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.255229E+10 | 0.00 | 0.00 | 0.410117E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 95063.56 | 0.560474E+10 | 0.00 | 0.00 | 0.845737E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 265520.10 | 0.257718E+10 | 0.00 | 0.00 | 0.552769E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.260611E+10 | 0.00 | 0.00 | 0.571835E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.359212E+10 | 0.00 | 0.00 | 0.625789E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.468399E+10 | 0.00 | 0.00 | 0.903218E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
May | 0.00 | 0.666843E+10 | 0.00 | 0.00 | 0.883683E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.746149E+10 | 0.00 | 0.00 | 0.559746E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.462263E+10 | 0.00 | 0.00 | 0.640318E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.586904E+10 | 0.00 | 0.00 | 0.693739E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.484512E+10 | 0.00 | 0.00 | 0.901355E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.417556E+10 | 0.00 | 0.00 | 0.904126E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 0.00 | 0.345929E+10 | 0.00 | 0.00 | 0.732470E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
December | 0.00 | 0.266837E+10 | 0.00 | 0.00 | 0.638607E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 265520.10 | 0.532293E+11 | 0.00 | 0.00 | 0.860766E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.257718E+10 | 0.00 | 0.00 | 0.552769E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 265520.10 | 0.746149E+10 | 0.00 | 0.00 | 0.904126E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 197005.80 | 0.215029E+10 | 0.00 | 0.00 | 0.355395E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
February | 0.00 | 0.231409E+10 | 0.00 | 0.00 | 0.290242E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.324884E+10 | 0.00 | 0.00 | 0.307009E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.414477E+10 | 0.00 | 0.00 | 0.463740E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.481943E+10 | 0.00 | 0.00 | 0.615362E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.500239E+10 | 0.00 | 0.00 | 0.463191E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.313858E+10 | 0.00 | 0.00 | 0.492903E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.451862E+10 | 0.00 | 0.00 | 0.443554E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.402510E+10 | 0.00 | 0.00 | 0.475473E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.343584E+10 | 0.00 | 0.00 | 0.506134E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.279606E+10 | 0.00 | 0.00 | 0.437149E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.224638E+10 | 0.00 | 0.00 | 0.369861E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 197005.80 | 0.418404E+11 | 0.00 | 0.00 | 0.522001E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.215029E+10 | 0.00 | 0.00 | 0.290242E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 197005.80 | 0.500239E+10 | 0.00 | 0.00 | 0.615362E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 266049.26 | 0.439782E+10 | 0.00 | 0.00 | 0.308331E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
February | 0.00 | 0.423042E+10 | 0.00 | 0.00 | 0.309223E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
March | 0.00 | 0.517268E+10 | 0.00 | 0.00 | 0.429055E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.572748E+10 | 0.00 | 0.00 | 0.868101E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.712221E+10 | 0.00 | 0.00 | 0.107539E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.723047E+10 | 0.00 | 0.00 | 0.831061E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.456375E+10 | 0.00 | 0.00 | 0.802953E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.661530E+10 | 0.00 | 0.00 | 0.757555E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.605594E+10 | 0.00 | 0.00 | 0.820816E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.601070E+10 | 0.00 | 0.00 | 0.607048E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.555152E+10 | 0.00 | 0.00 | 0.405270E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.466237E+10 | 0.00 | 0.00 | 0.317828E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 266049.26 | 0.673407E+11 | 0.00 | 0.00 | 0.753263E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.423042E+10 | 0.00 | 0.00 | 0.308331E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 266049.26 | 0.723047E+10 | 0.00 | 0.00 | 0.107539E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 211757.97 | 0.217287E+10 | 0.00 | 0.00 | 0.376131E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
February | 0.00 | 0.230429E+10 | 0.00 | 0.00 | 0.371359E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.327697E+10 | 0.00 | 0.00 | 0.355913E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.408988E+10 | 0.00 | 0.00 | 0.533933E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.467725E+10 | 0.00 | 0.00 | 0.730723E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.489601E+10 | 0.00 | 0.00 | 0.534784E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.308532E+10 | 0.00 | 0.00 | 0.554650E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.440725E+10 | 0.00 | 0.00 | 0.499773E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.387359E+10 | 0.00 | 0.00 | 0.590681E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.336522E+10 | 0.00 | 0.00 | 0.597790E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.277807E+10 | 0.00 | 0.00 | 0.511851E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.223980E+10 | 0.00 | 0.00 | 0.423155E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 211757.97 | 0.411665E+11 | 0.00 | 0.00 | 0.608074E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.217287E+10 | 0.00 | 0.00 | 0.355913E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 211757.97 | 0.489601E+10 | 0.00 | 0.00 | 0.730723E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 583876.31 | 0.321307E+10 | 0.00 | 0.00 | 0.446975E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
February | 0.00 | 0.326932E+10 | 0.00 | 0.00 | 0.482370E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.454820E+10 | 0.00 | 0.00 | 0.506403E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
April | 0.00 | 0.585549E+10 | 0.00 | 0.00 | 0.779590E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.813280E+10 | 0.00 | 0.00 | 0.746992E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.895530E+10 | 0.00 | 0.00 | 0.502250E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.547102E+10 | 0.00 | 0.00 | 0.584352E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.706764E+10 | 0.00 | 0.00 | 0.627821E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.586346E+10 | 0.00 | 0.00 | 0.807638E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.517316E+10 | 0.00 | 0.00 | 0.746631E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.428581E+10 | 0.00 | 0.00 | 0.618352E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
December | 0.00 | 0.330958E+10 | 0.00 | 0.00 | 0.544379E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 583876.31 | 0.651449E+11 | 0.00 | 0.00 | 0.739375E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.321307E+10 | 0.00 | 0.00 | 0.446975E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 583876.31 | 0.895530E+10 | 0.00 | 0.00 | 0.807638E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 402404.76 | 0.258639E+10 | 0.00 | 314.75 | 0.321667E+09 | 0.00 | 68971.21 | 0.00 | 0.50 |
February | 0.00 | 0.273718E+10 | 0.00 | 0.00 | 0.287562E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.387927E+10 | 0.00 | 0.00 | 0.317405E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.493730E+10 | 0.00 | 0.00 | 0.500662E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.575444E+10 | 0.00 | 0.00 | 0.603697E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.593713E+10 | 0.00 | 0.00 | 0.483243E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.367216E+10 | 0.00 | 0.00 | 0.515121E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.533769E+10 | 0.00 | 0.00 | 0.472298E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.471003E+10 | 0.00 | 0.00 | 0.517708E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.411375E+10 | 0.00 | 0.00 | 0.494284E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.338052E+10 | 0.00 | 0.00 | 0.395481E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.268984E+10 | 0.00 | 0.00 | 0.350286E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 402404.76 | 0.497357E+11 | 0.00 | 314.75 | 0.525941E+10 | 0.00 | 68971.21 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.258639E+10 | 0.00 | 0.00 | 0.287562E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 402404.76 | 0.593713E+10 | 0.00 | 314.75 | 0.603697E+09 | 0.00 | 68971.21 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 462469.53 | 0.483327E+10 | 0.00 | 1078.50 | 0.245180E+09 | 0.00 | 118445.33 | 0.00 | 0.54 |
February | 0.00 | 0.463597E+10 | 0.00 | 0.00 | 0.280196E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.531706E+10 | 0.00 | 0.00 | 0.404873E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
April | 0.00 | 0.573248E+10 | 0.00 | 0.00 | 0.798659E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.715576E+10 | 0.00 | 0.00 | 0.899714E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.718622E+10 | 0.00 | 0.00 | 0.727568E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.468425E+10 | 0.00 | 0.00 | 0.721687E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.660305E+10 | 0.00 | 0.00 | 0.679720E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.620695E+10 | 0.00 | 0.00 | 0.741220E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.632532E+10 | 0.00 | 0.00 | 0.520057E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.592774E+10 | 0.00 | 0.00 | 0.335525E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.513297E+10 | 0.00 | 0.00 | 0.268760E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 462469.53 | 0.697410E+11 | 0.00 | 1078.50 | 0.662316E+10 | 0.00 | 118445.33 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.463597E+10 | 0.00 | 0.00 | 0.245180E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 462469.53 | 0.718622E+10 | 0.00 | 1078.50 | 0.899714E+09 | 0.00 | 118445.33 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 512473.42 | 0.267591E+10 | 0.00 | 0.00 | 0.345176E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.00 | 0.281971E+10 | 0.00 | 0.00 | 0.378357E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.400011E+10 | 0.00 | 0.00 | 0.379344E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.492902E+10 | 0.00 | 0.00 | 0.609196E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.567364E+10 | 0.00 | 0.00 | 0.747967E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.583943E+10 | 0.00 | 0.00 | 0.609506E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.366526E+10 | 0.00 | 0.00 | 0.607896E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.531672E+10 | 0.00 | 0.00 | 0.532359E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.462844E+10 | 0.00 | 0.00 | 0.651331E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.412704E+10 | 0.00 | 0.00 | 0.604362E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.343774E+10 | 0.00 | 0.00 | 0.492912E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.274518E+10 | 0.00 | 0.00 | 0.421912E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 512473.42 | 0.498582E+11 | 0.00 | 0.00 | 0.638032E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.267591E+10 | 0.00 | 0.00 | 0.345176E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 512473.42 | 0.583943E+10 | 0.00 | 0.00 | 0.747967E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234541E+12 | -0.723669E+10 | 0.00 | -0.122049E+12 | 0.343508E+12 |
February | 0.228548E+12 | -0.721397E+10 | 0.00 | -0.122360E+12 | 0.328887E+12 |
March | 0.292572E+12 | -0.113728E+11 | 0.00 | -0.153165E+12 | 0.401298E+12 |
April | 0.288340E+12 | -0.124066E+11 | 0.00 | -0.196526E+12 | 0.420821E+12 |
May | 0.289776E+12 | -0.155620E+11 | 0.00 | -0.239830E+12 | 0.477725E+12 |
June | 0.300418E+12 | -0.153579E+11 | 0.00 | -0.232927E+12 | 0.480444E+12 |
July | 0.250265E+12 | -0.941662E+10 | 0.00 | -0.172920E+12 | 0.378727E+12 |
August | 0.310975E+12 | -0.143447E+11 | 0.00 | -0.217292E+12 | 0.441511E+12 |
September | 0.246056E+12 | -0.111130E+11 | 0.00 | -0.204565E+12 | 0.404239E+12 |
October | 0.271815E+12 | -0.107240E+11 | 0.00 | -0.194665E+12 | 0.389878E+12 |
November | 0.225314E+12 | -0.910894E+10 | 0.00 | -0.163856E+12 | 0.363539E+12 |
December | 0.221575E+12 | -0.682720E+10 | 0.00 | -0.135276E+12 | 0.335646E+12 |
Annual Sum or Average | 0.316020E+13 | -0.130684E+12 | 0.00 | -0.215543E+13 | 0.476622E+13 |
Minimum of Months | 0.221575E+12 | -0.155620E+11 | 0.00 | -0.239830E+12 | 0.328887E+12 |
Maximum of Months | 0.310975E+12 | -0.682720E+10 | 0.00 | -0.122049E+12 | 0.480444E+12 |