Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:20:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2405.84 | 482.89 | 482.89 |
Net Site Energy | 2405.84 | 482.89 | 482.89 |
Total Source Energy | 5450.49 | 1094.00 | 1094.00 |
Net Source Energy | 5450.49 | 1094.00 | 1094.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1041.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 313.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 24.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1364.65 | 1041.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1041.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 313.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 101.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 24.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1041.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 313.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 101.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 24.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 68.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.03 | 208.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 273.91 | 208.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 74.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 45.03 | 208.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 273.91 | 208.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1364.650 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1364.650 | 100.00 |
Total On-Site and Utility Electric Sources | 1364.650 | 100.00 |
Total Electricity End Uses | 1364.650 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.20 | 0.04 |
Air to Air Heat Recovery for Heating | 445.83 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 446.03 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1150.67 |
Time Setpoint Not Met During Occupied Cooling | 57.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3416.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-JUL-15:39 | 12-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 397243.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43524.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27678.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5769.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 148464.34 | 397243.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 397243.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 43524.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27678.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 5769.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1128.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 153.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 991.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 177.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 322.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 78.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 215.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4321.85 | 1128.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 198.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 867.46 | 226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 198.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 867.46 | 226.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.82 | 0.265430 | 0.280000 | 0.790593 | 0.707814 | 0.500000 | 0.001435 | 0.000157 | 0.790593 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.33 | 0.321745 | 0.336000 | 0.782660 | 0.857986 | 0.500000 | 0.001184 | 0.000240 | 0.828745 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.27 | 0.330478 | 0.352000 | 0.798261 | 0.881276 | 0.500000 | 0.001153 | 0.000438 | 1.52 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.682344 | 0.231543 | 0.249000 | 0.169904 | 0.617447 | 0.500000 | 0.001645 | 0.000197 | 0.682344 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.925561 | 0.108066 | 0.200000 | 0.185112 | 0.300000 | 0.500000 | 0.003526 | 0.000129 | 0.445950 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.45 | 0.108867 | 0.200000 | 0.290248 | 0.300000 | 0.500000 | 0.003500 | 0.000196 | 0.679027 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.957891 | 0.104412 | 0.200000 | 0.191578 | 0.300000 | 0.500000 | 0.003649 | 0.000128 | 0.444071 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.584158 | 0.270460 | 0.286000 | 0.167069 | 0.721227 | 0.500000 | 0.001409 | 0.000159 | 0.549628 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.754628 | 0.132545 | 0.200000 | 0.150926 | 0.353452 | 0.500000 | 0.002875 | 0.000105 | 0.362236 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.18 | 0.133807 | 0.200000 | 0.236149 | 0.356818 | 0.500000 | 0.002847 | 0.000158 | 0.547294 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.796288 | 0.125602 | 0.200000 | 0.159258 | 0.334938 | 0.500000 | 0.003033 | 0.000104 | 0.360714 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.653719 | 0.241681 | 0.252000 | 0.164737 | 0.644483 | 0.500000 | 0.001576 | 0.000151 | 0.522325 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.922438 | 0.108432 | 0.200000 | 0.184488 | 0.300000 | 0.500000 | 0.003514 | 0.000099 | 0.343714 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.38 | 0.114177 | 0.200000 | 0.276749 | 0.304472 | 0.500000 | 0.003337 | 0.000150 | 0.519276 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.913077 | 0.109537 | 0.200000 | 0.182615 | 0.300000 | 0.500000 | 0.003478 | 0.000099 | 0.342123 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17963.68 | 0.000157 | 415.63 |
CORE_MID VAV BOX REHEAT COIL | 27448.40 | 0.000240 | 725.05 |
CORE_TOP VAV BOX REHEAT COIL | 50115.80 | 0.000438 | 1322.32 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22508.53 | 0.000197 | 593.46 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14709.97 | 0.000129 | 387.84 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22399.27 | 0.000196 | 590.59 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14648.08 | 0.000128 | 386.21 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18135.61 | 0.000159 | 478.23 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11951.63 | 0.000105 | 315.15 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18058.72 | 0.000158 | 476.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11901.50 | 0.000104 | 313.83 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17236.84 | 0.000151 | 454.55 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11341.89 | 0.000099 | 299.09 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17136.43 | 0.000150 | 451.91 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11289.47 | 0.000099 | 297.71 |
PACU_VAV_BOT HEATING COIL | 75288.62 | 0.000659 | 1057.85 |
PACU_VAV_MID HEATING COIL | 76175.54 | 0.000666 | 1051.52 |
PACU_VAV_TOP HEATING COIL | 76425.97 | 0.000669 | 1079.49 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.07 | 1.50 | 6.14 | 2.25 | 5.25 | 5.25 | 0.300000 | 0.428548 | 5.25 |
PACU_VAV_MID | 3.10 | 1.59 | 6.20 | 2.56 | 5.00 | 5.00 | 0.300000 | 0.511256 | 5.00 |
PACU_VAV_TOP | 3.14 | 1.64 | 6.28 | 3.77 | 5.43 | 5.43 | 0.300000 | 0.693627 | 5.43 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.25 |
PACU_VAV_MID_OA_CONTROLLER | 5.00 |
PACU_VAV_TOP_OA_CONTROLLER | 5.43 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.20 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.25 | 86960.60 | 0.800655 | 1.75 | 28983.97 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.00 | 82764.59 | 0.800655 | 1.67 | 27585.44 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.43 | 89930.08 | 0.800655 | 1.81 | 29973.70 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.25 |
PACU_VAV_MID FAN | 5.00 |
PACU_VAV_TOP FAN | 5.43 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000659 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000666 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000669 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004503 | 0.540376 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004503 | 1356.15 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 514735.94 | 514735.94 | 0.004503 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6761 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.6631 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.8981 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.245 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.274 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8794 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.32863397E-12 | 0.12532498E-14 | -0.10432781E-12 | 0.10000009E-15 |
43 | 6 | 0.29860290E-07 | 0.19244976E-09 | 0.68304209E-08 | -0.14159436E-12 |
44 | 5 | -0.19612469E-03 | 0.16345755E-05 | -0.10079517E-03 | 0.67484823E-08 |
45 | 4 | 0.29915968 | 0.79015507E-03 | 0.10220689 | -0.34563380E-04 |
46 | 3 | -7.4051490 | 0.24331082E-01 | -2.3801101 | 0.29689509E-01 |
47 | 2 | 41.328906 | 0.86029560E-01 | 15.433920 | -0.33843907 |
48 | 1 | -80.896497 | 0.38634018E-01 | -29.293000 | 1.0860931 |
49 | 0 | 46.824336 | 0.77350051E-03 | 16.287644 | |
50 | 7 | -0.32990843E-12 | 0.11750686E-14 | -0.10494268E-12 | 0.10070323E-15 |
51 | 6 | 0.30013254E-07 | 0.18902410E-09 | 0.68641830E-08 | -0.14241961E-12 |
52 | 5 | -0.19689619E-03 | 0.16039916E-05 | -0.10118091E-03 | 0.67813509E-08 |
53 | 4 | 0.30005484 | 0.77472963E-03 | 0.10252920 | -0.34690470E-04 |
54 | 3 | -7.4228592 | 0.23838592E-01 | -2.3853666 | 0.29776351E-01 |
55 | 2 | 41.387294 | 0.84233400E-01 | 15.455437 | -0.33908948 |
56 | 1 | -80.941219 | 0.37805857E-01 | -29.312279 | 1.0870462 |
57 | 0 | 46.824336 | 0.75649625E-03 | 16.287191 | |
58 | 7 | -0.28528047E-12 | 0.14314274E-14 | -0.82259378E-13 | 0.81732043E-16 |
59 | 6 | 0.27222731E-07 | 0.24871836E-09 | 0.62482715E-08 | -0.12743522E-12 |
60 | 5 | -0.18272614E-03 | 0.21485338E-05 | -0.94080885E-04 | 0.61809713E-08 |
61 | 4 | 0.28347135 | 0.10543336E-02 | 0.96565215E-01 | -0.32350904E-04 |
62 | 3 | -7.0944292 | 0.32900988E-01 | -2.2879113 | 0.28166852E-01 |
63 | 2 | 40.304118 | 0.11770635 | 15.055686 | -0.32702567 |
64 | 1 | -80.111171 | 0.53403795E-01 | -28.953874 | 1.0693576 |
65 | 0 | 46.824341 | 0.10800274E-02 | 16.295775 | |
66 | 7 | -0.22718025E-08 | -0.85076432E-15 | 0.54602610E-14 | -0.81699313E-16 |
67 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
68 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
69 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
70 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
71 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
72 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
73 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
74 | 7 | -0.21518248E-08 | -0.72352508E-15 | 0.47198691E-14 | -0.69590188E-16 |
75 | 6 | 0.55239907E-05 | 0.37570600E-08 | 0.31901221E-02 | -0.26761418E-04 |
76 | 5 | -0.39518120E-03 | 0.22239456E-05 | -0.22373891 | 0.19562768E-02 |
77 | 4 | 0.90771213E-02 | 0.10121852E-03 | 4.8297846 | -0.45267278E-01 |
78 | 3 | -0.79671013E-01 | 0.80474906E-03 | -38.022767 | 0.39866868 |
79 | 2 | 0.28284274 | 0.13386367E-02 | 116.48658 | -1.4179745 |
80 | 1 | -0.40820825 | 0.40769430E-03 | -143.90886 | 2.0490654 |
81 | 0 | 0.19901349 | 0.99021926E-05 | 60.838472 | |
82 | 7 | -0.22718025E-08 | -0.85076409E-15 | 0.54602611E-14 | -0.81699316E-16 |
83 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
84 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
85 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
86 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
87 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
88 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
89 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
90 | 7 | -0.21516764E-08 | -0.72282083E-15 | 0.50090186E-14 | -0.71315031E-16 |
91 | 6 | 0.55243484E-05 | 0.37573175E-08 | 0.31901211E-02 | -0.26761409E-04 |
92 | 5 | -0.39520780E-03 | 0.22240973E-05 | -0.22373885 | 0.19562763E-02 |
93 | 4 | 0.90777390E-02 | 0.10122544E-03 | 4.8297836 | -0.45267268E-01 |
94 | 3 | -0.79676455E-01 | 0.80480411E-03 | -38.022761 | 0.39866862 |
95 | 2 | 0.28286209 | 0.13387285E-02 | 116.48657 | -1.4179743 |
96 | 1 | -0.40823619 | 0.40772215E-03 | -143.90885 | 2.0490653 |
97 | 0 | 0.19902711 | 0.99029315E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.29_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.29_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6680E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6771E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9693E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9774E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3846E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4385E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2324E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2620E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1832 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1235 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2141 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1496 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1083 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8289E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7709E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1604E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6688E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6824E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9703E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9840E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3892E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4588E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2321E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2617E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1213 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.4519E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1266 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.7772E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.3727E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7812E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7776E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1907E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.0490E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0532E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.0842E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0874E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8080E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.8190E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1064E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1167E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.8446E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.9330E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7971E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8752E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6484E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6997E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.2321E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.2617E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 7.1682E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0431E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7316E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2095E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7225E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9425E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7709E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1604E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.8435E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.9375E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7938E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8707E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6442E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6840E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.2324E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.2620E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 8.7409E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3625E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.8892E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8277E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.6169E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8883E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7777E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1908E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 8.1135E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 8.2333E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.4906E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.6337E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7058E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7381E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1066E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1169E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1998 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1479 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2330 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1780 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1194 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1980E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.5817E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0683E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1167 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 7.1861E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1218 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 7.4987E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.1391E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6422E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6518E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1150E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 8.0328E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 5.1527E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.5014E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.1707E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4567E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7618E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.5817E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0683E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.4273E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.1889E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.6162E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.6795E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4413E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7865E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6519E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1151E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1998 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1479 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2330 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1780 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1194 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1973E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.5811E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0679E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1167 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 7.1857E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1218 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 7.4982E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.1386E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6417E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6512E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1147E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 8.0330E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 5.1525E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.5015E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1705E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4564E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7615E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.5811E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0679E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.4274E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.1886E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.6163E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.6792E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4408E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7861E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6513E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1148E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38580.70810 | 38580.70810 | 2.82355 | 2.82355 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10127.15150 | 10127.15150 | 0.44118 | 0.44118 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31853.19292 | 31853.19292 | 2.32935 | 2.32935 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 19233.70472 | 19233.70472 | 0.82874 | 0.82874 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31013.48313 | 31013.48313 | 2.26779 | 2.26779 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35080.38022 | 35080.38022 | 1.51686 | 1.51686 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9168.30093 | 9168.30093 | 0.67664 | 0.67664 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15745.26413 | 15745.26413 | 0.68234 | 0.68234 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 12541.24777 | 12541.24777 | 0.92556 | 0.92556 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10289.79762 | 10289.79762 | 0.44595 | 0.44595 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 19664.14160 | 19664.14160 | 1.45124 | 1.45124 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15668.88117 | 15668.88117 | 0.67903 | 0.67903 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12979.31334 | 12979.31334 | 0.95789 | 0.95789 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10246.53577 | 10246.53577 | 0.44407 | 0.44407 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7915.13687 | 7915.13687 | 0.58416 | 0.58416 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12687.71948 | 12687.71948 | 0.54963 | 0.54963 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 10225.05973 | 10225.05973 | 0.75463 | 0.75463 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8361.16056 | 8361.16056 | 0.36224 | 0.36224 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 15998.81856 | 15998.81856 | 1.18074 | 1.18074 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12633.97238 | 12633.97238 | 0.54729 | 0.54729 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10789.53983 | 10789.53983 | 0.79629 | 0.79629 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8326.11615 | 8326.11615 | 0.36071 | 0.36071 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8857.70142 | 8857.70142 | 0.65372 | 0.65372 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12059.66393 | 12059.66393 | 0.52232 | 0.52232 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 12498.90967 | 12498.90967 | 0.92244 | 0.92244 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7935.06943 | 7935.06943 | 0.34371 | 0.34371 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 18749.49846 | 18749.49846 | 1.38374 | 1.38374 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11989.46679 | 11989.46679 | 0.51928 | 0.51928 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12372.05700 | 12372.05700 | 0.91308 | 0.91308 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7898.42005 | 7898.42005 | 0.34212 | 0.34212 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74810.49 | 5.25329 | 5.25329 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 77870.75 | 2.25129 | 2.25129 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71397.09 | 4.99981 | 4.99981 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 77735.52 | 2.55618 | 2.55618 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76958.85 | 5.43268 | 5.43268 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 77872.19 | 3.76825 | 3.76825 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.82355 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26543 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79059 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70781 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43541E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57154E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79059 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17963.67857 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57154E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 415.62829 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32935 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32174 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78266 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85799 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18417E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.40131E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82874 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27448.39634 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.40131E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 725.05007 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.26779 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33048 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79826 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88128 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15287E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.38435E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.51686 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 50115.79525 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.38435E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1322.31898 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68234 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23154 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16990 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61745 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64549E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96914E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68234 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22508.53250 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96914E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 593.46498 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92556 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10807 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18511 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.52562E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28689E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44595 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14709.96524 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28689E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 387.83884 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45124 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10887 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29025 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49970E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95959E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67903 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22399.27452 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95959E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 590.58605 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95789 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10441 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19158 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64901E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28148E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44407 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14648.08406 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28148E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.20827 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58416 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27046 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16707 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72123 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40871E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58658E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54963 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18135.60664 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58658E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 478.22753 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75463 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13254 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15093 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35345 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87451E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04558E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36224 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11951.62727 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04558E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 315.14959 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18074 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13381 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23615 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35682 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84739E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57986E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54729 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18058.72460 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57986E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 476.20176 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79629 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12560 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15926 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33494 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03339E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04120E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36071 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11901.49929 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04120E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 313.82874 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65372 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24168 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16474 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64448 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57646E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.50795E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52232 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17236.84016 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50795E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 454.55323 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92244 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10843 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18449 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51372E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.92238E-005 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34371 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11341.89215 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.92238E-005 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 299.08826 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38374 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11418 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27675 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30447 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33692E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49917E-004 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51928 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17136.42846 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49917E-004 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 451.90744 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91308 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10954 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18262 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47829E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.87652E-005 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34212 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11289.46847 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.87652E-005 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.70692 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.06968 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.50399 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.13936 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.25129 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.25329 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.25329 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.42855 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.10116 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.59125 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.20232 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55618 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.99981 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.99981 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.51126 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.14241 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.63510 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.28483 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.76825 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.43268 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.43268 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.69363 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.25329 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.99981 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.43268 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.25329 |
239 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.25329 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 86960.60104 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.75092 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28983.96833 |
245 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 75288.61636 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.58658E-004 |
248 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1057.85274 |
249 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.25329 |
250 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.58658E-004 |
251 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.99981 |
252 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.99981 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 82764.58555 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.66644 |
257 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27585.43636 |
258 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 76175.54118 |
260 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.66417E-004 |
261 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1051.52021 |
262 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.99981 |
263 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.66417E-004 |
264 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.43268 |
265 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.43268 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89930.07900 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
269 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.81071 |
270 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29973.69533 |
271 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
272 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 76425.97159 |
273 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.68608E-004 |
274 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1079.48692 |
275 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.43268 |
276 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.68608E-004 |
277 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.50313E-003 |
278 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.54038 |
279 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.50313E-003 |
280 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1356.14638 |
281 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
282 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 514735.94263 |
283 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 514735.94000 |
284 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.50313E-003 |
285 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
286 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
287 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
288 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
289 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17020.38 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 26013.93 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 47486.75 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21324.87 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13936.36 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21221.37 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13877.74 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17182.31 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11323.33 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17109.48 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11275.84 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16330.96 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10745.76 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16235.84 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10696.10 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 45276.29 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 44779.95 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 46269.50 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85464.23 | 291616.04 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 5.9815 | 4.7312 | 3.1705 | 1.3213 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 81340.41 | 277545.01 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 5.6929 | 4.5029 | 3.0176 | 1.2576 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 88382.61 | 301573.97 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 6.1858 | 4.8928 | 3.2788 | 1.3664 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.196 | 0.187 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.196 | 0.187 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2225320702E-002 | 2.0620529112E-002 | Pass | Pass | 0.4856901904 | 0.4924398045 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2502439422 | 0.1519917356 | Pass | Pass | 0.4855401457 | 0.4938129422 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1180008748 | 7.2521610392E-002 | Pass | Pass | 0.4853547317 | 0.4798535605 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1114036627 | 6.1339400323E-002 | Pass | Pass | 0.4835270949 | 0.4786830477 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9828566948E-002 | 6.2251569072E-002 | Pass | Pass | 0.8283884024 | 0.7693777245 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1996129920 | 0.1867847380 | Pass | Pass | 0.6785055373 | 0.6449975726 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7081274933 | 0.5773970822 | Pass | Pass | 0.6294336143 | 0.5628197487 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7294937885 | 0.6566980641 | Pass | Pass | 0.6076029023 | 0.5947189682 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6884999323 | 0.6221640146 | Pass | Pass | 0.6120370009 | 0.6049272636 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7261234095 | 0.6545579231 | Pass | Pass | 0.6069097049 | 0.6036476662 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5883113808 | 0.4818791593 | Pass | Pass | 0.6331886054 | 0.5902485224 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6128878611 | 0.5547069476 | Pass | Pass | 0.6299424168 | 0.5896143384 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5691454852 | 0.5166486553 | Pass | Pass | 0.6321882459 | 0.6075917357 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6105279886 | 0.5532701814 | Pass | Pass | 0.6222563430 | 0.6049857657 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5352734347 | 0.4627698054 | Pass | Pass | 0.6847594605 | 0.5764762184 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5565007244 | 0.5075900225 | Pass | Pass | 0.6238870209 | 0.6216743111 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5177753640 | 0.4746358771 | Pass | Pass | 0.6333127576 | 0.6338067333 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5539479839 | 0.5050327653 | Pass | Pass | 0.6241650653 | 0.6220813820 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2380.22 | 124.50 | 0.00 | 2763.35 | 543.89 | 5811.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.29_SHGC_NORTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.29_SHGC_EAST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.29_SHGC_WEST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.29_SHGC_EAST_0.45 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.29_SHGC_EAST_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.29_SHGC_WEST_0.45 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.29_SHGC_WEST_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.29_SHGC_NORTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.29_SHGC_EAST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.29_SHGC_WEST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.647 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 195.79 | 1.647 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.647 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.95 | 0.0000 | Y | 10.14 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.43 | 0.0000 | Y | 6.31 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.70 | 0.0000 | Y | 9.72 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.33 | 0.0000 | Y | 6.29 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.85 | 0.0000 | Y | 10.11 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.35 | 0.0000 | Y | 6.29 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.62 | 0.0000 | Y | 9.69 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.24 | 0.0000 | Y | 6.27 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.95 | 0.0000 | Y | 10.14 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.43 | 0.0000 | Y | 6.31 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.70 | 0.0000 | Y | 9.72 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.33 | 0.0000 | Y | 6.29 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 313.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 44.84 | 44.84 | 4.75 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.06 | 63.95 | 4.89 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.06 | 52.41 | 46.38 | |
Exterior Lighting Total | 5686.19 | 56.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 514735.94 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 86960.60 | 69625.46 | 17335.14 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 82764.59 | 66265.90 | 16498.68 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89930.08 | 72002.99 | 17927.09 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85464.2 | 3.01 | 10.26 | N/A | N/A | 11.58 | |
PACU_VAV_MID COOLING COIL | 81340.4 | 3.01 | 10.26 | N/A | N/A | 11.58 | |
PACU_VAV_TOP COOLING COIL | 88382.6 | 3.01 | 10.26 | N/A | N/A | 11.58 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17963.68 | 17020.38 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 27448.40 | 26013.93 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 50115.80 | 47486.75 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22508.53 | 21324.87 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14709.97 | 13936.36 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22399.27 | 21221.37 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14648.08 | 13877.74 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18135.61 | 17182.31 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11951.63 | 11323.33 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18058.72 | 17109.48 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11901.50 | 11275.84 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17236.84 | 16330.96 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11341.89 | 10745.76 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17136.43 | 16235.84 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11289.47 | 10696.10 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 75288.62 | 45276.29 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 76175.54 | 44779.95 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 76425.97 | 46269.50 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.25 | 12074.48 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.00 | 11491.87 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.43 | 12486.80 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004503 | 1356.15 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85464.23 | 3.01 | 10.26 | 11.58 | 5.9815 | 3.31 | 11.30 | 4.7312 | 3.48 | 11.88 | 3.1705 | 3.68 | 12.55 | 1.3213 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 81340.41 | 3.01 | 10.26 | 11.58 | 5.6929 | 3.31 | 11.30 | 4.5029 | 3.48 | 11.88 | 3.0176 | 3.68 | 12.55 | 1.2576 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88382.61 | 3.01 | 10.26 | 11.58 | 6.1858 | 3.31 | 11.30 | 4.8928 | 3.48 | 11.88 | 3.2788 | 3.68 | 12.55 | 1.3664 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38580.71 | 38580.71 | 39.23 | 2.824 | 2.824 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 31853.19 | 31853.19 | 32.39 | 2.329 | 2.329 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 31013.48 | 31013.48 | 31.53 | 2.268 | 2.268 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 19.85 | 0.00700 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9168.30 | 9168.30 | 44.22 | 0.677 | 0.677 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00875 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12541.25 | 12541.25 | 95.54 | 0.926 | 0.926 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00862 | 22.37 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 19664.14 | 19664.14 | 94.84 | 1.451 | 1.451 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12979.31 | 12979.31 | 98.89 | 0.958 | 0.958 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00861 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7915.14 | 7915.14 | 38.18 | 0.584 | 0.584 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00880 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 10225.06 | 10225.06 | 77.90 | 0.755 | 0.755 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00865 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 15998.82 | 15998.82 | 77.16 | 1.181 | 1.181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00865 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10789.54 | 10789.54 | 82.20 | 0.796 | 0.796 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00864 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8857.70 | 8857.70 | 42.72 | 0.654 | 0.654 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00876 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 12498.91 | 12498.91 | 95.22 | 0.922 | 0.922 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 18749.50 | 18749.50 | 90.43 | 1.384 | 1.384 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12372.06 | 12372.06 | 94.26 | 0.913 | 0.913 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00862 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10127.15 | 10127.15 | 10.30 | 0.441 | 0.441 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 19233.70 | 19233.70 | 19.56 | 0.829 | 0.829 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 35080.38 | 35080.38 | 35.67 | 1.517 | 1.517 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15745.26 | 15745.26 | 75.94 | 0.682 | 0.682 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10289.80 | 10289.80 | 78.39 | 0.446 | 0.446 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15668.88 | 15668.88 | 75.57 | 0.679 | 0.679 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10246.54 | 10246.54 | 78.07 | 0.444 | 0.444 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12687.72 | 12687.72 | 61.19 | 0.550 | 0.550 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8361.16 | 8361.16 | 63.70 | 0.362 | 0.362 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12633.97 | 12633.97 | 60.93 | 0.547 | 0.547 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8326.12 | 8326.12 | 63.44 | 0.361 | 0.361 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12059.66 | 12059.66 | 58.16 | 0.522 | 0.522 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7935.07 | 7935.07 | 60.45 | 0.344 | 0.344 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11989.47 | 11989.47 | 57.83 | 0.519 | 0.519 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7898.42 | 7898.42 | 60.18 | 0.342 | 0.342 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.25 | 5.25 | 2.25 | 2.25 | 5.2533 | 2.2513 | 5.2533 | 0.4285 | 0.3000 |
PACU_VAV_MID | 5.00 | 5.00 | 2.56 | 2.56 | 4.9998 | 2.5562 | 4.9998 | 0.5113 | 0.3000 |
PACU_VAV_TOP | 5.43 | 5.43 | 3.77 | 3.77 | 5.4327 | 3.7682 | 5.4327 | 0.6936 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17963.679 | 17963.679 | 0.790593 | 0.00015715 | 415.628 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 17963.68 | 17963.68 | 0.790593 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 10127.15 | 0.00 | 18023.08 | 18023.08 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27448.396 | 27448.396 | 0.828745 | 0.00024013 | 725.050 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27448.40 | 27448.40 | 0.828745 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 19233.70 | 0.00 | 27546.81 | 27546.81 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50115.795 | 50115.795 | 1.516858 | 0.00043843 | 1322.319 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50115.80 | 50115.80 | 1.516858 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 35080.38 | 0.00 | 50284.78 | 50284.78 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22508.532 | 22508.532 | 0.682344 | 0.00019691 | 593.465 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22508.53 | 22435.14 | 0.682344 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798458 | 50.8164 | 15745.26 | 0.00 | 22581.34 | 22581.34 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14709.965 | 14709.965 | 0.445950 | 0.00012869 | 387.839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14709.97 | 14709.97 | 0.445950 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798427 | 50.8145 | 10289.80 | 0.00 | 14757.49 | 14757.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22399.275 | 22399.275 | 0.679027 | 0.00019596 | 590.586 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22399.27 | 22399.27 | 0.679027 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798450 | 50.8159 | 15668.88 | 0.00 | 22471.74 | 22471.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14648.084 | 14648.084 | 0.444071 | 0.00012815 | 386.208 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14648.08 | 14648.08 | 0.444071 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798421 | 50.8141 | 10246.54 | 0.00 | 14695.42 | 14695.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18135.607 | 18135.607 | 0.549628 | 0.00015866 | 478.228 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18135.61 | 18135.61 | 0.549628 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798961 | 50.8479 | 12687.72 | 0.00 | 18194.70 | 18194.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11951.627 | 11951.627 | 0.362236 | 0.00010456 | 315.150 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11951.63 | 11951.63 | 0.362236 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798955 | 50.8476 | 8361.16 | 0.00 | 11990.50 | 11990.50 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18058.725 | 18058.725 | 0.547294 | 0.00015799 | 476.202 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18058.72 | 18058.72 | 0.547294 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798955 | 50.8476 | 12633.97 | 0.00 | 18117.58 | 18117.58 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11901.499 | 11901.499 | 0.360714 | 0.00010412 | 313.829 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11901.50 | 11901.50 | 0.360714 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798950 | 50.8472 | 8326.12 | 0.00 | 11940.22 | 11940.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17236.840 | 17236.840 | 0.522325 | 0.00015080 | 454.553 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17236.84 | 17236.84 | 0.522325 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798288 | 50.8057 | 12059.66 | 0.00 | 17293.19 | 17293.19 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11341.892 | 11341.892 | 0.343714 | 0.00009922 | 299.088 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11341.89 | 11341.89 | 0.343714 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798275 | 50.8049 | 7935.07 | 0.00 | 11378.91 | 11378.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17136.428 | 17136.428 | 0.519276 | 0.00014992 | 451.907 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17136.43 | 17136.43 | 0.519276 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798276 | 50.8050 | 11989.47 | 0.00 | 17192.47 | 17192.47 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11289.468 | 11289.468 | 0.342123 | 0.00009877 | 297.707 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11289.47 | 11289.47 | 0.342123 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798266 | 50.8043 | 7898.42 | 0.00 | 11326.32 | 11326.32 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 86960.601 | 69625.463 | 5.253290 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 88332.83 | 88332.83 | 5.253290 | 24.77 | 16.39 | 0.00837512 | 10.90 | 10.90 | 0.00837512 | 27.40 | 0.00700714 | 16.15 | 22.7509 | 24.00 | 0.00877884 | 46.5049 | 71067.28 | 0.00 | 89668.05 | 70015.16 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 75288.616 | 75288.616 | 1.575987 | 0.00065866 | 1057.853 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 75288.62 | 75288.62 | 1.575987 | -27.30 | -27.30 | 0.00197730 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 75.8363 | 18.15 | 0.00798092 | 60.6341 | 21267.89 | 0.00 | 54744.91 | 54744.91 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 82764.586 | 66265.901 | 4.999809 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 84070.60 | 84070.60 | 4.999809 | 24.81 | 16.40 | 0.00836261 | 10.90 | 10.90 | 0.00836261 | 27.40 | 0.00700714 | 16.15 | 23.9043 | 24.00 | 0.00878961 | 46.5611 | 67600.32 | 0.00 | 85341.40 | 66636.79 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 76175.541 | 76175.541 | 1.499943 | 0.00066642 | 1051.520 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76175.54 | 76175.54 | 1.499943 | -29.83 | -29.83 | 0.00167096 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 79.6810 | 17.60 | 0.00795731 | 62.5902 | 23064.05 | 0.00 | 54134.76 | 54134.76 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 89930.079 | 72002.991 | 5.432676 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 91397.28 | 91397.28 | 5.432676 | 24.73 | 16.38 | 0.00837721 | 10.90 | 10.90 | 0.00837721 | 27.30 | 0.00700699 | 16.11 | 21.9997 | 24.00 | 0.00876513 | 46.4331 | 73396.95 | 0.00 | 92729.98 | 72406.00 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 76425.972 | 76425.972 | 1.629803 | 0.00066861 | 1079.487 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76425.97 | 76425.97 | 1.629803 | -26.57 | -26.57 | 0.00217284 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 73.3322 | 15.60 | 0.00796109 | 71.1138 | 26777.23 | 0.00 | 55950.64 | 55950.64 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17963.679 | 17963.679 | 0.790593 | 0.00015715 | 415.628 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 3.4210 | 3.489882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 17963.68 | 17963.68 | 1.0000 | 0.93720031 | 0.790593 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15713807 | 60.00 | 32.22 | 27.78 | 0.000 | 17963.68 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 10127.15 | 0.00 | 18023.08 | 18023.08 | 0.93720031 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.66 | 18.59 | 0.00800000 | 52290.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 27448.396 | 27448.396 | 0.828745 | 0.00024013 | 725.050 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 5.2273 | 5.332520 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27448.40 | 27448.40 | 1.0000 | 0.98242646 | 0.828745 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.24010605 | 60.00 | 32.22 | 27.78 | 0.000 | 27448.40 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 19233.70 | 0.00 | 27546.81 | 27546.81 | 0.98242646 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61099.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 50115.795 | 50115.795 | 1.516858 | 0.00043843 | 1322.319 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 9.5441 | 9.736214 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50115.80 | 50115.80 | 1.0000 | 1.79814292 | 1.516858 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.43839011 | 60.00 | 32.22 | 27.78 | 0.000 | 50115.80 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 35080.38 | 0.00 | 50284.78 | 50284.78 | 1.79814292 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22508.532 | 22508.532 | 0.682344 | 0.00019691 | 593.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 4.2866 | 4.372831 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22508.53 | 22435.14 | 1.0000 | 0.80887707 | 0.682344 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19689437 | 60.00 | 32.22 | 27.78 | 0.000 | 22508.53 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798458 | 21.00 | 0.00798458 | 50.8164 | 15745.26 | 0.00 | 22581.34 | 22581.34 | 0.80887707 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14709.965 | 14709.965 | 0.445950 | 0.00012869 | 387.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.8014 | 2.857769 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14709.97 | 14709.97 | 1.0000 | 0.52864615 | 0.445950 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12867607 | 60.00 | 32.22 | 27.78 | 0.000 | 14709.97 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798427 | 21.00 | 0.00798427 | 50.8145 | 10289.80 | 0.00 | 14757.49 | 14757.49 | 0.52864615 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22399.275 | 22399.275 | 0.679027 | 0.00019596 | 590.586 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 4.2658 | 4.351605 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22399.27 | 22399.27 | 1.0000 | 0.80494539 | 0.679027 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19593864 | 60.00 | 32.22 | 27.78 | 0.000 | 22399.27 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798450 | 21.00 | 0.00798450 | 50.8159 | 15668.88 | 0.00 | 22471.74 | 22471.74 | 0.80494539 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14648.084 | 14648.084 | 0.444071 | 0.00012815 | 386.208 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.7896 | 2.845747 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14648.08 | 14648.08 | 1.0000 | 0.52641937 | 0.444071 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12813476 | 60.00 | 32.22 | 27.78 | 0.000 | 14648.08 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798421 | 21.00 | 0.00798421 | 50.8141 | 10246.54 | 0.00 | 14695.42 | 14695.42 | 0.52641937 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18135.607 | 18135.607 | 0.549628 | 0.00015866 | 478.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 3.4538 | 3.523284 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18135.61 | 18135.61 | 1.0000 | 0.65155038 | 0.549628 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15864201 | 60.00 | 32.22 | 27.78 | 0.000 | 18135.61 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798961 | 21.00 | 0.00798961 | 50.8479 | 12687.72 | 0.00 | 18194.70 | 18194.70 | 0.65155038 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11951.627 | 11951.627 | 0.362236 | 0.00010456 | 315.150 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.2761 | 2.321895 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11951.63 | 11951.63 | 1.0000 | 0.42940878 | 0.362236 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10454738 | 60.00 | 32.22 | 27.78 | 0.000 | 11951.63 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798955 | 21.00 | 0.00798955 | 50.8476 | 8361.16 | 0.00 | 11990.50 | 11990.50 | 0.42940878 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18058.725 | 18058.725 | 0.547294 | 0.00015799 | 476.202 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 3.4391 | 3.508347 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18058.72 | 18058.72 | 1.0000 | 0.64878358 | 0.547294 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15796948 | 60.00 | 32.22 | 27.78 | 0.000 | 18058.72 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798955 | 21.00 | 0.00798955 | 50.8476 | 12633.97 | 0.00 | 18117.58 | 18117.58 | 0.64878358 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11901.499 | 11901.499 | 0.360714 | 0.00010412 | 313.829 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.2665 | 2.312156 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11901.50 | 11901.50 | 1.0000 | 0.42760488 | 0.360714 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10410889 | 60.00 | 32.22 | 27.78 | 0.000 | 11901.50 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798950 | 21.00 | 0.00798950 | 50.8472 | 8326.12 | 0.00 | 11940.22 | 11940.22 | 0.42760488 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17236.840 | 17236.840 | 0.522325 | 0.00015080 | 454.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 3.2826 | 3.348676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17236.84 | 17236.84 | 1.0000 | 0.61918403 | 0.522325 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15078001 | 60.00 | 32.22 | 27.78 | 0.000 | 17236.84 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798288 | 21.00 | 0.00798288 | 50.8057 | 12059.66 | 0.00 | 17293.19 | 17293.19 | 0.61918403 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11341.892 | 11341.892 | 0.343714 | 0.00009922 | 299.088 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.1600 | 2.203439 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11341.89 | 11341.89 | 1.0000 | 0.40745210 | 0.343714 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09921370 | 60.00 | 32.22 | 27.78 | 0.000 | 11341.89 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798275 | 21.00 | 0.00798275 | 50.8049 | 7935.07 | 0.00 | 11378.91 | 11378.91 | 0.40745210 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17136.428 | 17136.428 | 0.519276 | 0.00014992 | 451.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 3.2635 | 3.329169 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17136.43 | 17136.43 | 1.0000 | 0.61557055 | 0.519276 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14990166 | 60.00 | 32.22 | 27.78 | 0.000 | 17136.43 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798276 | 21.00 | 0.00798276 | 50.8050 | 11989.47 | 0.00 | 17192.47 | 17192.47 | 0.61557055 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11289.468 | 11289.468 | 0.342123 | 0.00009877 | 297.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 2.1500 | 2.193254 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11289.47 | 11289.47 | 1.0000 | 0.40556559 | 0.342123 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09875512 | 60.00 | 32.22 | 27.78 | 0.000 | 11289.47 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798266 | 21.00 | 0.00798266 | 50.8043 | 7898.42 | 0.00 | 11326.32 | 11326.32 | 0.40556559 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 86960.601 | 69625.463 | 5.253290 | -999.0 | -999.000 | -999.0000 | 1.02772 | 1.00000 | 1020.4089 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.253290 | 6.22745628 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 88332.83 | 88332.83 | 1.0158 | 6.22745628 | 5.253290 | 24.77 | 16.39 | 0.00837512 | 46225.2 | 10.90 | 10.90 | 0.00837512 | 32068.0 | -999.0 | -999.00 | -999.00 | -999.00 | 12074.485 | 76258.34 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 22.7509 | 24.00 | 0.00877884 | 24.00 | 0.00877884 | 46.5049 | 71067.28 | 0.00 | 89668.05 | 70015.16 | 5.98151883 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 75288.616 | 75288.616 | 1.575987 | 0.00065866 | 1057.853 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.253290 | 6.22745628 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 14.3381 | 14.626648 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 75288.62 | 75288.62 | 1.0000 | 1.86823688 | 1.575987 | -27.30 | -27.30 | 0.00197730 | -22591.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.65859047 | 60.00 | 32.22 | 27.78 | 0.000 | 75288.62 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 75.8363 | 18.50 | 0.00798051 | 18.15 | 0.00798092 | 60.6341 | 21267.89 | 0.00 | 54744.91 | 54744.91 | 1.86823688 | 2.80 | -1.22 | 0.00197730 | 7769.0 | 31.86 | 13.34 | 0.00197730 | 37071.9 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 82764.586 | 66265.901 | 4.999809 | -999.0 | -999.000 | -999.0000 | 1.02491 | 1.00000 | 1020.3857 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.999809 | 5.92696959 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 84070.60 | 84070.60 | 1.0158 | 5.92696959 | 4.999809 | 24.81 | 16.40 | 0.00836261 | 46233.9 | 10.90 | 10.90 | 0.00836261 | 32036.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11491.868 | 72578.73 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 23.9043 | 24.00 | 0.00878961 | 24.00 | 0.00878961 | 46.5611 | 67600.32 | 0.00 | 85341.40 | 66636.79 | 5.69289910 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 76175.541 | 76175.541 | 1.499943 | 0.00066642 | 1051.520 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.999809 | 5.92696959 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 14.5070 | 14.798955 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76175.54 | 76175.54 | 1.0000 | 1.77809088 | 1.499943 | -29.83 | -29.83 | 0.00167096 | -25892.1 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.66634888 | 60.00 | 32.22 | 27.78 | 0.000 | 76175.54 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 79.6810 | 17.48 | 0.00797072 | 17.60 | 0.00795731 | 62.5902 | 23064.05 | 0.00 | 54134.76 | 54134.76 | 1.77809088 | 2.80 | -1.70 | 0.00167096 | 7001.2 | 33.01 | 13.49 | 0.00167096 | 37446.7 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89930.079 | 72002.991 | 5.432676 | -999.0 | -999.000 | -999.0000 | 1.03161 | 1.00000 | 1020.4128 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.432676 | 6.44010769 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 91397.28 | 91397.28 | 1.0163 | 6.44010769 | 5.432676 | 24.73 | 16.38 | 0.00837721 | 46182.5 | 10.90 | 10.90 | 0.00837721 | 32073.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12486.797 | 78910.49 | 27.30 | 0.00700699 | 16.11 | 1.19517000 | 21.9997 | 24.00 | 0.00876513 | 24.00 | 0.00876513 | 46.4331 | 73396.95 | 0.00 | 92729.98 | 72406.00 | 6.18577212 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 76425.972 | 76425.972 | 1.629803 | 0.00066861 | 1079.487 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.432676 | 6.44010769 | 4197.9300 | 999.8980 | 4.50267521 | 54.44 | 82.22 | 27.78 | 525095.21 | 14.5547 | 14.847607 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76425.97 | 76425.97 | 1.0000 | 1.93203231 | 1.629803 | -26.57 | -26.57 | 0.00217284 | -21367.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.66853953 | 60.00 | 32.22 | 27.78 | 0.000 | 76425.97 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 73.3322 | 15.60 | 0.00797045 | 15.60 | 0.00796109 | 71.1138 | 26777.23 | 0.00 | 55950.64 | 55950.64 | 1.93203231 | 2.80 | -0.91 | 0.00217284 | 8259.0 | 31.50 | 13.39 | 0.00217284 | 37218.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.25 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.00 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.43 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1940.00 | 3534.17 | 859.33 |
CORE_MID | 2623.67 | 4135.50 | 2013.83 |
CORE_TOP | 3143.50 | 4453.00 | 2681.00 |
PERIMETER_TOP_ZN_3 | 3883.67 | 4533.33 | 3220.33 |
PERIMETER_TOP_ZN_2 | 4113.67 | 4220.67 | 3020.67 |
PERIMETER_TOP_ZN_1 | 3931.67 | 4219.17 | 2830.50 |
PERIMETER_TOP_ZN_4 | 3953.17 | 4572.83 | 3146.17 |
PERIMETER_BOT_ZN_3 | 3609.33 | 4642.50 | 3116.33 |
PERIMETER_BOT_ZN_2 | 3991.17 | 4046.67 | 2829.00 |
PERIMETER_BOT_ZN_1 | 3780.67 | 4279.00 | 2770.50 |
PERIMETER_BOT_ZN_4 | 3757.83 | 4412.33 | 2971.50 |
PERIMETER_MID_ZN_3 | 3727.67 | 4331.67 | 2955.00 |
PERIMETER_MID_ZN_2 | 3334.67 | 3512.67 | 2388.00 |
PERIMETER_MID_ZN_1 | 3767.33 | 3952.17 | 2522.33 |
PERIMETER_MID_ZN_4 | 3808.67 | 4309.50 | 2888.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5277.33 | 5038.83 | 3416.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 5.67 | 0.00 | 5.50 | 0.00 |
CORE_MID | 21.33 | 0.00 | 20.33 | 0.00 |
CORE_TOP | 49.67 | 0.00 | 41.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 406.67 | 0.00 | 233.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 255.67 | 9.50 | 88.17 | 9.50 |
PERIMETER_TOP_ZN_1 | 213.67 | 16.17 | 71.50 | 16.00 |
PERIMETER_TOP_ZN_4 | 256.67 | 14.83 | 92.00 | 5.00 |
PERIMETER_BOT_ZN_3 | 266.50 | 0.00 | 209.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 110.50 | 8.67 | 56.83 | 8.17 |
PERIMETER_BOT_ZN_1 | 1111.83 | 10.17 | 1055.67 | 9.67 |
PERIMETER_BOT_ZN_4 | 114.83 | 6.00 | 59.00 | 0.83 |
PERIMETER_MID_ZN_3 | 168.17 | 1.00 | 107.67 | 0.00 |
PERIMETER_MID_ZN_2 | 97.33 | 12.00 | 37.50 | 11.50 |
PERIMETER_MID_ZN_1 | 76.17 | 19.17 | 28.67 | 19.00 |
PERIMETER_MID_ZN_4 | 100.17 | 16.50 | 40.67 | 5.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1378.00 | 77.67 | 1150.67 | 57.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.883 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.675 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.643 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.791 | 0.024 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.410 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.459 | 0.024 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.246 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.698 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.240 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 1.274 | 0.857 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.046 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.795 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.314 | 0.023 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.476 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.244 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14042748.74 | 0.00 | 14042748.74 | 0.00 | 14042748.74 | 13393058.27 | 6396.85 | 21.42 | 2341.73 | 427.88 |
CORE_MID | 10804451.80 | 0.00 | 10804451.80 | 0.00 | 10804451.80 | 13393058.27 | 6762.74 | 20.35 | 1976.90 | 372.97 |
CORE_TOP | 10251931.63 | 0.00 | 10251931.63 | 0.00 | 10251931.63 | 13393058.27 | 6850.17 | 20.74 | 1889.09 | 87.97 |
PERIMETER_TOP_ZN_3 | 2649607.81 | 0.00 | 2649607.81 | 166682.89 | 2816290.70 | 2823374.22 | 5762.90 | 70.29 | 2926.82 | 87.97 |
PERIMETER_TOP_ZN_2 | 2988704.48 | 0.00 | 2988704.48 | 111121.26 | 3099825.74 | 1787429.43 | 4133.57 | 0.28 | 4626.15 | 87.97 |
PERIMETER_TOP_ZN_1 | 4882501.43 | 0.00 | 4882501.43 | 166682.89 | 5049184.32 | 2823374.22 | 4133.59 | 0.46 | 4625.96 | 87.97 |
PERIMETER_TOP_ZN_4 | 2656217.58 | 0.00 | 2656217.58 | 111121.26 | 2767338.84 | 1787312.18 | 4132.97 | 0.56 | 4626.47 | 87.97 |
PERIMETER_BOT_ZN_3 | 2357347.78 | 0.00 | 2357347.78 | 88623.85 | 2445971.63 | 2823374.22 | 5913.10 | 57.75 | 2789.16 | 427.88 |
PERIMETER_BOT_ZN_2 | 2638094.26 | 0.00 | 2638094.26 | 59082.21 | 2697176.47 | 1787429.43 | 4137.59 | 3.47 | 4618.94 | 427.88 |
PERIMETER_BOT_ZN_1 | 4303212.31 | 0.00 | 4303212.31 | 2926570.99 | 7229783.30 | 2823374.22 | 4133.09 | 3.28 | 4623.63 | 427.88 |
PERIMETER_BOT_ZN_4 | 2239347.33 | 0.00 | 2239347.33 | 59082.21 | 2298429.54 | 1787312.18 | 4134.90 | 3.49 | 4621.61 | 427.88 |
PERIMETER_MID_ZN_3 | 2676554.44 | 0.00 | 2676554.44 | 138750.27 | 2815304.70 | 2823374.22 | 6192.47 | 47.84 | 2519.69 | 372.97 |
PERIMETER_MID_ZN_2 | 3076940.24 | 0.00 | 3076940.24 | 92499.62 | 3169439.86 | 1787429.43 | 4083.19 | 0.50 | 4676.31 | 1281.97 |
PERIMETER_MID_ZN_1 | 4957777.86 | 0.00 | 4957777.86 | 138750.27 | 5096528.13 | 2823374.22 | 4085.79 | 1.11 | 4673.10 | 372.97 |
PERIMETER_MID_ZN_4 | 2664661.25 | 0.00 | 2664661.25 | 92499.62 | 2757160.88 | 1787312.18 | 4083.19 | 1.33 | 4675.48 | 372.97 |
Total Facility | 73190098.94 | 0.00 | 73190098.94 | 4151467.34 | 77341566.28 | 67843644.98 | 6960.94 | 216.29 | 4738.90 | 1466.23 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6463 | 0.0000 | 0.6463 | 0.0000 | 0.6463 | 0.4247 | 3628.11 | 21.42 | 2293.46 |
CORE_MID | 0.4950 | 0.0000 | 0.4950 | 0.0000 | 0.4950 | 0.4247 | 4010.85 | 20.08 | 1912.07 |
CORE_TOP | 0.4719 | 0.0000 | 0.4719 | 0.0000 | 0.4719 | 0.4247 | 4087.73 | 20.57 | 1834.70 |
PERIMETER_TOP_ZN_3 | 0.1223 | 0.0000 | 0.1223 | 0.0037 | 0.1260 | 0.0895 | 3000.73 | 70.12 | 2872.15 |
PERIMETER_TOP_ZN_2 | 0.1380 | 0.0000 | 0.1380 | 0.0025 | 0.1405 | 0.0567 | 1372.85 | 0.28 | 4569.87 |
PERIMETER_TOP_ZN_1 | 0.2255 | 0.0000 | 0.2255 | 0.0037 | 0.2293 | 0.0895 | 1372.86 | 0.46 | 4569.68 |
PERIMETER_TOP_ZN_4 | 0.1220 | 0.0000 | 0.1220 | 0.0025 | 0.1245 | 0.0567 | 1372.25 | 0.56 | 4570.19 |
PERIMETER_BOT_ZN_3 | 0.1080 | 0.0000 | 0.1080 | 0.0020 | 0.1100 | 0.0895 | 3144.25 | 57.75 | 2741.00 |
PERIMETER_BOT_ZN_2 | 0.1213 | 0.0000 | 0.1213 | 0.0013 | 0.1227 | 0.0567 | 1370.51 | 3.06 | 4569.43 |
PERIMETER_BOT_ZN_1 | 0.1981 | 0.0000 | 0.1981 | 0.1346 | 0.3327 | 0.0895 | 1365.94 | 2.96 | 4574.10 |
PERIMETER_BOT_ZN_4 | 0.1025 | 0.0000 | 0.1025 | 0.0013 | 0.1038 | 0.0567 | 1368.36 | 3.49 | 4571.15 |
PERIMETER_MID_ZN_3 | 0.1229 | 0.0000 | 0.1229 | 0.0031 | 0.1261 | 0.0895 | 3440.77 | 47.51 | 2454.72 |
PERIMETER_MID_ZN_2 | 0.1287 | 0.0000 | 0.1287 | 0.0022 | 0.1309 | 0.0567 | 1333.74 | 0.50 | 3699.76 |
PERIMETER_MID_ZN_1 | 0.2282 | 0.0000 | 0.2282 | 0.0031 | 0.2313 | 0.0895 | 1336.28 | 1.11 | 4605.61 |
PERIMETER_MID_ZN_4 | 0.1218 | 0.0000 | 0.1218 | 0.0021 | 0.1239 | 0.0567 | 1333.74 | 1.33 | 4607.93 |
Total Facility | 3.3526 | 0.0000 | 3.3526 | 0.1623 | 3.5149 | 2.1513 | 4170.96 | 215.08 | 4651.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 35947756.42 | 0.00 | 35947756.42 | 22614548.33 | 4127.19 | 0.75 | 4632.06 | 427.88 |
PACU_VAV_MID | 33979881.81 | 0.00 | 33979881.81 | 22614548.33 | 4086.65 | 1.60 | 4671.75 | 372.77 |
PACU_VAV_TOP | 32923929.86 | 0.00 | 32923929.86 | 22614548.33 | 4133.91 | 0.30 | 4625.79 | 87.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.6530 | 0.0000 | 1.6530 | 0.7171 | 1360.29 | 0.75 | 4581.96 |
PACU_VAV_MID | 1.5589 | 0.0000 | 1.5589 | 0.7171 | 1337.01 | 1.60 | 4604.39 |
PACU_VAV_TOP | 1.5173 | 0.0000 | 1.5173 | 0.7171 | 1373.19 | 0.30 | 4569.51 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2889.63 | 0.00 | 0.00 | 0.00 | 2412.12 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2757.41 | 0.00 | 0.00 | 0.00 | 2510.71 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2267.04 | 0.00 | 0.00 | 0.00 | 2560.72 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.8575 | 0.0000 | 0.0000 | 0.0000 | 1.1573 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.7024 | 0.0000 | 0.0000 | 0.0000 | 1.1242 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.8177 | 0.0000 | 0.0000 | 0.0000 | 1.1242 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 988 |
Defaulted Fields | 577 |
Fields with Defaults | 2480 |
Autosized Fields | 196 |
Autosizable Fields | 253 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
Electricity:Building | 1032.74 | 13465.67 | 02-APR-17:20 | 74341.76 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1032.74 | 13465.67 | 02-APR-17:20 | 74341.76 | 02-JAN-08:10 |
InteriorLights:Electricity | 313.05 | 987.92 | 02-APR-17:20 | 32642.50 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 313.05 | 987.92 | 02-APR-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 313.05 | 987.92 | 02-APR-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 313.05 | 987.92 | 02-APR-17:20 | 32642.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 34.47 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.14 | 36.00 | 19-FEB-10:30 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.14 | 36.00 | 19-FEB-10:30 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 21.71 | 267.21 | 02-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.31 | 22.79 | 29-JAN-11:20 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.31 | 22.79 | 29-JAN-11:20 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 34.05 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.72 | 36.00 | 15-JAN-12:10 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.72 | 36.00 | 15-JAN-12:10 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 21.69 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.29 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.29 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 34.44 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.11 | 36.00 | 12-FEB-12:10 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.11 | 36.00 | 12-FEB-12:10 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 21.70 | 267.21 | 02-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.29 | 22.79 | 16-JAN-12:20 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.29 | 22.79 | 16-JAN-12:20 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 34.02 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.69 | 36.00 | 15-JAN-12:00 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.69 | 36.00 | 15-JAN-12:00 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 21.67 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.27 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.27 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 34.47 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.14 | 36.00 | 19-FEB-10:30 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 10.14 | 36.00 | 19-FEB-10:30 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 21.71 | 267.21 | 02-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.31 | 22.79 | 29-JAN-11:20 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 6.31 | 22.79 | 29-JAN-11:20 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 34.05 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.72 | 36.00 | 15-JAN-12:10 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 9.72 | 36.00 | 15-JAN-12:10 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 21.69 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.29 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 6.29 | 22.79 | 05-FEB-12:20 | 859.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 201.89 | 368.59 | 02-APR-17:30 | 76397.70 | 30-JUN-14:30 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 19-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 19-JAN-12:20 |
ElectricityPurchased:Facility | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
ElectricityPurchased:Plant | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
Cogeneration:ElectricityPurchased | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
General:Cogeneration:ElectricityPurchased | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
ElectricityNet:Plant | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
Cogeneration:ElectricityNet | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
General:Cogeneration:ElectricityNet | 1364.65 | 13834.26 | 09-APR-17:40 | 148464.34 | 11-JUL-15:40 |
Fans:Electricity | 101.77 | 0.00 | 01-JAN-00:40 | 28854.25 | 12-JUL-15:20 |
General:Fans:Electricity | 101.77 | 0.00 | 01-JAN-00:40 | 28854.25 | 12-JUL-15:20 |
ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
HeatRecovery:Electricity | 24.66 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-07:30 |
General:HeatRecovery:Electricity | 24.66 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-07:30 |
Cooling:Electricity | 48.57 | 0.00 | 01-JAN-00:10 | 46269.46 | 30-JUN-14:30 |
General:Cooling:Electricity | 48.57 | 0.00 | 01-JAN-00:10 | 46269.46 | 30-JUN-14:30 |
Electricity:Plant | 74.00 | 0.00 | 01-JAN-00:40 | 8920.04 | 12-JAN-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 68.07 | 0.00 | 01-JAN-00:10 | 7772.01 | 02-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 68.07 | 0.00 | 01-JAN-00:10 | 7772.01 | 02-JAN-12:30 |
Pumps:Electricity | 5.93 | 0.00 | 01-JAN-00:40 | 1328.23 | 12-JAN-07:30 |
General:Pumps:Electricity | 5.93 | 0.00 | 01-JAN-00:40 | 1328.23 | 12-JAN-07:30 |
WIRED_LTG_ELECTRICITY | 8.80 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1041.19 | 0.00 | 01-JAN-00:40 | 397243.56 | 12-JAN-07:30 |
NaturalGas:Plant | 1041.19 | 0.00 | 01-JAN-00:40 | 397243.56 | 12-JAN-07:30 |
Heating:NaturalGas | 1041.19 | 0.00 | 01-JAN-00:40 | 397243.56 | 12-JAN-07:30 |
Boiler:Heating:NaturalGas | 1041.19 | 0.00 | 01-JAN-00:40 | 397243.56 | 12-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3601.63 | 0.00 | 01-JAN-00:40 | 789293.23 | 27-FEB-07:20 |
EnergyTransfer:Building | 1341.45 | 0.00 | 01-JAN-00:40 | 178237.60 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 197.04 | 0.00 | 01-JAN-00:40 | 25006.51 | 24-JUL-08:00 |
Heating:EnergyTransfer | 527.66 | 0.00 | 01-JAN-00:40 | 178237.60 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.71 | 0.00 | 01-JAN-00:10 | 10105.33 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 527.66 | 0.00 | 01-JAN-00:40 | 178237.60 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.71 | 0.00 | 01-JAN-00:10 | 10105.33 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 813.79 | 0.00 | 01-JAN-00:40 | 164235.66 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 196.34 | 0.00 | 01-JAN-00:40 | 25006.51 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 813.79 | 0.00 | 01-JAN-00:40 | 164235.66 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 196.34 | 0.00 | 01-JAN-00:40 | 25006.51 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 85.22 | 0.00 | 01-JAN-00:40 | 18311.68 | 12-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.17 | 0.00 | 01-JAN-00:40 | 18311.68 | 12-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.17 | 0.00 | 01-JAN-00:40 | 18311.68 | 12-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.06 | 0.00 | 01-JAN-00:10 | 8433.90 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.06 | 0.00 | 01-JAN-00:10 | 8433.90 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 39.62 | 0.00 | 01-JAN-00:40 | 11889.35 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.78 | 0.00 | 01-JAN-00:40 | 11889.35 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.78 | 0.00 | 01-JAN-00:40 | 11889.35 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.85 | 0.00 | 01-JAN-00:10 | 4973.75 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.85 | 0.00 | 01-JAN-00:10 | 4973.75 | 12-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 36.51 | 0.00 | 01-JAN-00:40 | 9088.46 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:40 | 9088.46 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:40 | 9088.46 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.16 | 0.00 | 01-JAN-00:10 | 5377.51 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.16 | 0.00 | 01-JAN-00:10 | 5377.51 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 133.30 | 0.00 | 01-JAN-00:40 | 18900.52 | 24-JUL-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.57 | 0.00 | 01-JAN-00:40 | 18500.44 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.57 | 0.00 | 01-JAN-00:40 | 18500.44 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 124.73 | 0.00 | 01-JAN-00:20 | 18900.52 | 24-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 124.73 | 0.00 | 01-JAN-00:20 | 18900.52 | 24-JUL-07:50 |
EnergyTransfer:Zone:CORE_TOP | 135.74 | 0.00 | 01-JAN-00:40 | 25207.08 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 32.53 | 0.00 | 01-JAN-00:40 | 25207.08 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 32.53 | 0.00 | 01-JAN-00:40 | 25207.08 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 103.21 | 0.00 | 01-JAN-00:20 | 18865.78 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 103.21 | 0.00 | 01-JAN-00:20 | 18865.78 | 12-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 67.91 | 0.00 | 01-JAN-00:40 | 9507.41 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.74 | 0.00 | 01-JAN-00:40 | 9507.41 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.74 | 0.00 | 01-JAN-00:40 | 9507.41 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.17 | 0.00 | 01-JAN-00:10 | 6816.34 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.17 | 0.00 | 01-JAN-00:10 | 6816.34 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 56.41 | 0.00 | 01-JAN-00:40 | 11574.15 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.71 | 0.00 | 01-JAN-00:40 | 8598.30 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.71 | 0.00 | 01-JAN-00:40 | 8598.30 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.70 | 0.00 | 01-JAN-00:10 | 11574.15 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.70 | 0.00 | 01-JAN-00:10 | 11574.15 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 85.69 | 0.00 | 01-JAN-00:40 | 16508.56 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.20 | 0.00 | 01-JAN-00:40 | 12859.54 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.20 | 0.00 | 01-JAN-00:40 | 12859.54 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.49 | 0.00 | 01-JAN-00:10 | 16508.56 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.49 | 0.00 | 01-JAN-00:10 | 16508.56 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.37 | 0.00 | 01-JAN-00:40 | 9249.89 | 11-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.38 | 0.00 | 01-JAN-00:40 | 8687.22 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.38 | 0.00 | 01-JAN-00:40 | 8687.22 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.99 | 0.00 | 01-JAN-00:10 | 9249.89 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 21.99 | 0.00 | 01-JAN-00:10 | 9249.89 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 53.29 | 0.00 | 01-JAN-00:40 | 7778.69 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.96 | 0.00 | 01-JAN-00:40 | 7778.69 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.96 | 0.00 | 01-JAN-00:40 | 7778.69 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.33 | 0.00 | 01-JAN-00:10 | 5764.39 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.33 | 0.00 | 01-JAN-00:10 | 5764.39 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 46.23 | 0.00 | 01-JAN-00:40 | 8820.89 | 07-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.38 | 0.00 | 01-JAN-00:40 | 6493.67 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.38 | 0.00 | 01-JAN-00:40 | 6493.67 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.85 | 0.00 | 01-JAN-00:10 | 8820.89 | 07-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.85 | 0.00 | 01-JAN-00:10 | 8820.89 | 07-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.64 | 0.00 | 01-JAN-00:40 | 19866.38 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.28 | 0.00 | 01-JAN-00:40 | 19866.38 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.28 | 0.00 | 01-JAN-00:40 | 19866.38 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.36 | 0.00 | 01-JAN-00:10 | 12934.52 | 11-AUG-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.36 | 0.00 | 01-JAN-00:10 | 12934.52 | 11-AUG-14:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 41.62 | 0.00 | 01-JAN-00:40 | 7405.93 | 31-JUL-18:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.92 | 0.00 | 01-JAN-00:40 | 6536.89 | 12-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.92 | 0.00 | 01-JAN-00:40 | 6536.89 | 12-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.69 | 0.00 | 01-JAN-00:10 | 7405.93 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 18.69 | 0.00 | 01-JAN-00:10 | 7405.93 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.90 | 0.00 | 01-JAN-00:40 | 8118.08 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.33 | 0.00 | 01-JAN-00:40 | 8118.08 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.33 | 0.00 | 01-JAN-00:40 | 8118.08 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.57 | 0.00 | 01-JAN-00:10 | 7350.69 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.57 | 0.00 | 01-JAN-00:10 | 7350.69 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.55 | 0.00 | 01-JAN-00:40 | 11485.47 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.92 | 0.00 | 01-JAN-00:40 | 6568.32 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.92 | 0.00 | 01-JAN-00:40 | 6568.32 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.63 | 0.00 | 01-JAN-00:10 | 11485.47 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.63 | 0.00 | 01-JAN-00:10 | 11485.47 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 73.35 | 0.00 | 01-JAN-00:40 | 16226.85 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 22.28 | 0.00 | 01-JAN-00:40 | 9830.82 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 22.28 | 0.00 | 01-JAN-00:40 | 9830.82 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.07 | 0.00 | 01-JAN-00:20 | 16226.85 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.07 | 0.00 | 01-JAN-00:20 | 16226.85 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.07 | 0.00 | 01-JAN-00:40 | 8982.99 | 06-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.46 | 0.00 | 01-JAN-00:40 | 6522.47 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.46 | 0.00 | 01-JAN-00:40 | 6522.47 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.60 | 0.00 | 01-JAN-00:10 | 8982.99 | 06-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 23.60 | 0.00 | 01-JAN-00:10 | 8982.99 | 06-JUL-17:50 |
PlantLoopHeatingDemand:Facility | 834.21 | 0.00 | 01-JAN-00:40 | 317550.78 | 12-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:20 |
EnergyTransfer:HVAC | 1432.10 | 0.00 | 01-JAN-00:40 | 314995.36 | 12-JAN-07:30 |
HeatingCoils:EnergyTransfer | 769.03 | 0.00 | 01-JAN-00:40 | 314995.36 | 12-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 769.03 | 0.00 | 01-JAN-00:40 | 314995.36 | 12-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 769.03 | 0.00 | 01-JAN-00:40 | 314995.36 | 12-JAN-07:30 |
HeatRecoveryForHeating:EnergyTransfer | 445.83 | 0.00 | 01-JAN-00:10 | 107678.07 | 25-NOV-07:30 |
HeatRecoveryForCooling:EnergyTransfer | 0.20 | 0.00 | 01-JAN-00:10 | 13540.79 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 217.04 | 0.00 | 01-JAN-00:10 | 204131.99 | 30-JUN-12:10 |
EnergyTransfer:Plant | 828.08 | 0.00 | 01-JAN-00:40 | 316446.20 | 12-JAN-07:30 |
WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 02-JAN-12:20 |
Boilers:EnergyTransfer | 762.90 | 0.00 | 01-JAN-00:40 | 313890.78 | 12-JAN-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.709 | -196.336 | 0.000 | 0.000 | 34.278 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -161.003 |
CORE_MID | 0.000 | 0.000 | 8.572 | -124.726 | 0.000 | 0.000 | 35.657 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -106.857 |
CORE_TOP | 0.000 | 0.000 | 32.528 | -103.209 | 0.000 | 0.000 | 36.251 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -152.923 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 46.737 | -21.170 | 0.000 | 0.000 | 7.753 | 10.141 | 24.333 | 17.056 | 0.000 | 0.002 | 0.001 | 0.000 | -52.729 | 0.000 | -3.826 | -28.297 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 28.713 | -27.696 | 0.000 | 0.000 | 4.859 | 6.308 | 15.404 | 38.364 | 0.000 | 0.001 | 0.000 | 0.000 | -33.594 | 0.000 | -2.574 | -29.784 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 38.196 | -47.490 | 0.000 | 0.000 | 7.649 | 9.719 | 24.332 | 75.444 | 0.000 | 0.002 | 0.001 | 0.000 | -48.238 | 0.000 | -3.924 | -55.690 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 30.382 | -21.990 | 0.000 | 0.000 | 4.933 | 6.286 | 15.403 | 26.824 | 0.000 | 0.001 | 0.000 | 0.000 | -34.474 | 0.000 | -2.586 | -24.779 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 34.963 | -18.325 | 0.000 | 0.000 | 7.753 | 10.106 | 24.333 | 17.345 | 0.000 | 0.001 | 0.001 | 0.000 | -53.362 | 0.000 | -2.067 | -20.746 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 21.381 | -24.847 | 0.000 | 0.000 | 4.831 | 6.292 | 15.404 | 38.443 | 0.000 | 0.001 | 0.000 | 0.000 | -34.278 | 0.000 | -1.414 | -25.812 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 64.281 | -31.359 | 0.000 | 0.000 | 8.010 | 9.690 | 24.332 | 76.053 | 0.000 | 0.081 | 0.001 | 0.000 | -48.440 | 0.000 | -70.776 | -31.872 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 22.923 | -18.694 | 0.000 | 0.000 | 4.896 | 6.267 | 15.403 | 26.957 | 0.000 | 0.001 | 0.000 | 0.000 | -35.100 | 0.000 | -1.411 | -21.242 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 28.333 | -23.570 | 0.000 | 0.000 | 7.683 | 10.141 | 24.333 | 16.777 | 0.000 | 0.002 | 0.001 | 0.000 | -54.295 | 0.000 | -3.293 | -6.111 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 17.915 | -29.634 | 0.000 | 0.000 | 3.573 | 6.308 | 15.404 | 38.154 | 0.000 | 0.001 | 0.000 | 0.000 | -34.529 | 0.000 | -2.211 | -14.981 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 22.277 | -51.074 | 0.000 | 0.000 | 7.576 | 9.718 | 24.332 | 75.105 | 0.000 | 0.002 | 0.001 | 0.000 | -49.737 | 0.000 | -3.378 | -34.821 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 18.462 | -23.604 | 0.000 | 0.000 | 4.886 | 6.286 | 15.403 | 26.651 | 0.000 | 0.001 | 0.000 | 0.000 | -35.484 | 0.000 | -2.224 | -10.378 |
TOPFLOOR_PLENUM | 68.167 | -17.056 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -5.823 | -45.290 |
MIDFLOOR_PLENUM | 25.777 | -13.846 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -5.585 | -6.347 |
FIRSTFLOOR_PLENUM | 17.343 | -19.164 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 6.266 | 0.000 | 0.000 | 0.000 | -4.447 | -0.001 |
Total Facility | 111.287 | -50.066 | 416.373 | -763.725 | 0.000 | 0.000 | 180.588 | 313.046 | 719.689 | 473.173 | 0.000 | 0.101 | 6.273 | 0.000 | -514.259 | 0.000 | -115.541 | -776.933 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 17-JUL-05:12 | 0.00 | 0.00 | 0.00 | -41740.45 | 0.00 | 0.00 | 320.98 | 715.98 | 7410.35 | 0.00 | 0.00 | 0.00 | 33293.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 23-JUN-05:12 | 0.00 | 0.00 | 0.00 | -32259.81 | 0.00 | 0.00 | 337.21 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 28180.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-06:02 | 0.00 | 0.00 | 0.00 | -29619.87 | 0.00 | 0.00 | 714.26 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 23731.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 07-JUL-05:12 | 0.00 | 0.00 | 0.00 | -10703.06 | 0.00 | 0.00 | 63.25 | 72.00 | 637.89 | 8413.42 | 0.00 | 0.00 | 1527.28 | 0.00 | -0.00 | 0.00 | -10.77 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-09:51 | 0.00 | 0.00 | 0.00 | -17091.88 | 0.00 | 0.00 | 13.64 | 22.79 | 302.86 | 11592.65 | 0.00 | 0.00 | 5432.15 | 0.00 | -0.00 | 0.00 | -272.20 | 0.00 |
PERIMETER_TOP_ZN_1 | 21-MAY-13:11 | 0.00 | 0.00 | 0.00 | -26873.44 | 0.00 | 0.00 | 21.30 | 36.00 | 478.41 | 20404.59 | 0.00 | 0.00 | 6248.66 | 0.00 | -0.00 | 0.00 | -315.52 | 0.00 |
PERIMETER_TOP_ZN_4 | 21-MAY-17:52 | 0.00 | 0.00 | 0.00 | -16852.62 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 10631.87 | 0.00 | 0.00 | 6052.84 | 0.00 | -0.00 | 0.00 | -99.30 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -8991.72 | 0.00 | 0.00 | 64.31 | 72.00 | 637.89 | 9073.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.99 | -841.41 |
PERIMETER_BOT_ZN_2 | 23-JUL-10:22 | 0.00 | 0.00 | 0.00 | -12863.12 | 0.00 | 0.00 | 14.53 | 22.79 | 302.86 | 10466.26 | 0.00 | 0.00 | 2064.25 | 0.00 | -0.00 | 0.00 | -7.57 | 0.00 |
PERIMETER_BOT_ZN_1 | 27-AUG-13:31 | 0.00 | 0.00 | 0.00 | -21883.87 | 0.00 | 0.00 | 23.02 | 36.00 | 478.41 | 18803.60 | 0.00 | 0.00 | 2589.00 | 0.00 | -0.00 | 0.00 | -46.16 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-18:12 | 0.00 | 0.00 | 0.00 | -13711.89 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 8861.11 | 0.00 | 0.00 | 4637.41 | 0.00 | -0.00 | 0.00 | -53.84 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -10383.29 | 0.00 | 0.00 | 62.58 | 72.00 | 637.89 | 8991.01 | 0.00 | 0.00 | 643.98 | 0.00 | -0.00 | 0.00 | -24.16 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:42 | 0.00 | 0.00 | 0.00 | -16276.77 | 0.00 | 0.00 | 12.18 | 22.79 | 302.86 | 12575.66 | 0.00 | 0.00 | 3394.42 | 0.00 | -0.00 | 0.00 | -31.13 | 0.00 |
PERIMETER_MID_ZN_1 | 27-AUG-13:31 | 0.00 | 0.00 | 0.00 | -26750.57 | 0.00 | 0.00 | 20.13 | 36.00 | 478.41 | 18696.27 | 0.00 | 0.00 | 7597.51 | 0.00 | -0.00 | 0.00 | -77.76 | 0.00 |
PERIMETER_MID_ZN_4 | 27-AUG-16:52 | 0.00 | 0.00 | 0.00 | -16257.33 | 0.00 | 0.00 | 14.02 | 22.79 | 302.86 | 11755.54 | 0.00 | 0.00 | 4301.02 | 0.00 | -0.00 | 0.00 | -138.89 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -8434.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 8430.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -5672.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5699.66 | 0.00 | -0.00 | 0.00 | -26.79 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -6487.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6507.78 | 0.00 | -0.00 | 0.00 | -20.70 | 0.00 |
Total Facility | 24-JUL-06:02 | 0.00 | -7304.20 | 0.00 | -176078.65 | 0.00 | 0.00 | 3572.41 | 8560.47 | 22496.85 | 32948.41 | 0.00 | 0.00 | 123878.02 | 0.00 | 0.00 | 0.00 | -8073.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 12382.11 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18235.90 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 19956.09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22609.88 |
CORE_TOP | 01-JAN-22:42 | 0.00 | 0.00 | 27580.33 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29623.60 |
PERIMETER_TOP_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 10554.28 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4450.47 | 0.00 | 0.00 | -6663.25 |
PERIMETER_TOP_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 10470.47 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2964.41 | 0.00 | 0.00 | -7860.21 |
PERIMETER_TOP_ZN_1 | 30-JAN-04:22 | 0.00 | 0.00 | 16090.08 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3663.27 | 0.00 | -580.69 | -12405.55 |
PERIMETER_TOP_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 10640.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2966.05 | 0.00 | 0.00 | -8028.67 |
PERIMETER_BOT_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 8574.35 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4526.13 | 0.00 | 0.00 | -4607.66 |
PERIMETER_BOT_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 8199.53 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3017.09 | 0.00 | 0.00 | -5536.60 |
PERIMETER_BOT_ZN_1 | 12-JAN-07:10 | 0.00 | 0.00 | 20193.78 | 0.00 | 0.00 | 0.00 | 221.77 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 24888.30 | 0.00 | -4842.96 | 0.00 | -41551.59 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 8413.21 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3018.81 | 0.00 | 0.00 | -5748.54 |
PERIMETER_MID_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 8982.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4550.70 | 0.00 | 0.00 | -4990.99 |
PERIMETER_MID_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 8867.42 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3030.87 | 0.00 | 0.00 | -6190.70 |
PERIMETER_MID_ZN_1 | 30-JAN-04:22 | 0.00 | 0.00 | 13229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3754.54 | 0.00 | -492.98 | -9541.33 |
PERIMETER_MID_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 8792.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3032.74 | 0.00 | 0.00 | -6114.25 |
TOPFLOOR_PLENUM | 12-JAN-06:10 | 18771.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18771.07 |
MIDFLOOR_PLENUM | 02-JAN-08:45 | 11923.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -175.65 | -11747.61 |
FIRSTFLOOR_PLENUM | 02-JAN-06:10 | 9120.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.47 | -9103.70 |
Total Facility | 02-JAN-05:01 | 20388.96 | 0.00 | 171216.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27985.14 | 0.00 | -2092.55 | -178170.61 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.1394 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2533 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.2023 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9998 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.2848 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4327 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0697 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5040 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.1012 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5912 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.1424 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6351 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8235 | 2.8235 | 0.7906 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3293 | 2.3293 | 0.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2678 | 2.2678 | 0.7983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6823 | 0.6823 | 0.1699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9256 | 0.9256 | 0.1851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4512 | 1.4512 | 0.2902 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9579 | 0.9579 | 0.1916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5842 | 0.5842 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7546 | 0.7546 | 0.1509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1807 | 1.1807 | 0.2361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7963 | 0.7963 | 0.1593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6537 | 0.6537 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9224 | 0.9224 | 0.1845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3837 | 1.3837 | 0.2767 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9131 | 0.9131 | 0.1826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.1394 | 5.2533 | 6.1394 | 1.5040 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.2023 | 4.9998 | 6.2023 | 1.5912 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.2848 | 5.4327 | 6.2848 | 1.6351 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4118 | 1.4118 | 0.7906 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1647 | 1.1647 | 0.7827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1339 | 1.1339 | 0.7983 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3412 | 0.3412 | 0.1699 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4628 | 0.4628 | 0.1851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7256 | 0.7256 | 0.2902 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4789 | 0.4789 | 0.1916 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2921 | 0.2921 | 0.1671 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3773 | 0.3773 | 0.1509 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5904 | 0.5904 | 0.2361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3981 | 0.3981 | 0.1593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3269 | 0.3269 | 0.1647 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4612 | 0.4612 | 0.1845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6919 | 0.6919 | 0.2767 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4565 | 0.4565 | 0.1826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0697 | 1.5040 | 1.5040 | 1.5040 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.1012 | 1.5912 | 1.5912 | 1.5912 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.1424 | 1.6351 | 1.6351 | 1.6351 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1150.67 |
Number of hours cooling loads not met | 57.00 |
Number of hours not met | 1207.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1041.19 | 397243.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 48.57 | 46269.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 313.05 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 56.02 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 101.77 | 28854.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 5.93 | 1328.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 24.66 | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 68.07 | 7772.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1364.65 |
Natural Gas | 0.00 | 1041.19 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2405.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 62.83 |
Space Heating | 0.00 |
Space Cooling | 9.75 |
Fans (All) | 20.43 |
Service Water Heating | 13.66 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 273.91 |
Subtotal | 273.91 |
Natural Gas [MJ/m2] | |
Space Heating | 208.98 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 208.98 |
Subtotal | 208.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.01 |
Space Heating | 43.28 |
Space Cooling | 2.02 |
Fans (All) | 4.23 |
Service Water Heating | 2.83 |
Receptacle Equipment | 29.91 |
Miscellaneous | 4.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8704.17 | 55.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8704.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 55.83 | 0.00 | 0.00 | 0.00 |
Average | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
Sum | 157488.00 | 192.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128275.67 | 28.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 28.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.76 | 1.57 | 0.00 | 0.00 | 0.00 |
Sum | 614551.67 | 28.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8686.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8686.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 74.00 | 0.00 | 0.00 | 0.00 |
Average | 8750.49 | 9.51 | 0.00 | 0.00 | 0.00 |
Sum | 157508.83 | 171.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128260.50 | 43.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.67 | 4.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 43.50 | 0.00 | 0.00 | 0.00 |
Average | 34140.68 | 2.66 | 0.00 | 0.00 | 0.00 |
Sum | 614532.17 | 47.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860461E+10 | 7374.33 | 27-JAN-17:00 | -12.2 | -12.5 | 0.159170E+10 | 2389.22 | 27-JAN-16:00 | -12.2 | -12.5 |
February | 0.912871E+10 | 7923.00 | 16-FEB-17:00 | -5.6 | -7.7 | 0.153340E+10 | 2528.94 | 16-FEB-16:00 | -5.6 | -7.7 |
March | 0.111442E+11 | 11644.20 | 23-MAR-16:00 | -1.7 | -4.1 | 0.200350E+10 | 2608.27 | 31-MAR-13:09 | -11.6 | -13.5 |
April | 0.153711E+11 | 40265.29 | 24-APR-05:02 | -3.4 | -6.0 | 0.189795E+10 | 2606.63 | 14-APR-09:09 | -3.4 | -6.0 |
May | 0.239795E+11 | 39603.58 | 13-MAY-05:12 | 9.07 | 3.34 | 0.207754E+10 | 2606.66 | 19-MAY-13:50 | 13.58 | 8.15 |
June | 0.269893E+11 | 40918.22 | 24-JUN-05:12 | 12.80 | 12.28 | 0.207358E+10 | 2606.68 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.264685E+11 | 41746.12 | 17-JUL-05:12 | 8.30 | 8.19 | 0.192800E+10 | 2607.03 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.267015E+11 | 41667.14 | 01-AUG-05:12 | 10.00 | 9.66 | 0.216270E+10 | 2606.65 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.183092E+11 | 40988.90 | 18-SEP-05:02 | 1.78 | 1.10 | 0.191504E+10 | 2606.69 | 08-SEP-13:09 | 1.78 | 1.10 |
October | 0.116947E+11 | 15878.55 | 05-OCT-16:00 | 11.10 | 5.87 | 0.192699E+10 | 2606.63 | 13-OCT-09:20 | -8.2 | -9.0 |
November | 0.893080E+10 | 7873.97 | 03-NOV-16:00 | -11.1 | -11.5 | 0.167289E+10 | 2514.04 | 03-NOV-15:00 | -11.1 | -11.5 |
December | 0.901379E+10 | 7046.92 | 22-DEC-17:00 | -21.7 | -22.0 | 0.153256E+10 | 2314.41 | 22-DEC-16:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.196336E+12 | 0.223159E+11 | ||||||||
Minimum of Months | 0.860461E+10 | 7046.92 | -21.7 | -22.0 | 0.153256E+10 | 2314.41 | -21.7 | -22.0 | ||
Maximum of Months | 0.269893E+11 | 41746.12 | 12.80 | 12.28 | 0.216270E+10 | 2608.27 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 13977686.00 | 991.89 | 22-MAR-16:10 | 5.60 | 2.47 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.47 |
April | 0.871669E+09 | 4360.38 | 21-APR-15:30 | 14.15 | 5.54 | 0.00 | 0.00 | 01-APR-00:10 | 14.15 | 5.54 |
May | 0.288924E+10 | 7366.88 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.491594E+10 | 8338.50 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.478802E+10 | 8433.90 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.308397E+10 | 7242.55 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.482390E+09 | 3000.68 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 10885958.93 | 897.54 | 03-OCT-16:10 | 11.60 | 6.16 | 0.00 | 0.00 | 01-OCT-00:10 | 11.60 | 6.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.170561E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.491594E+10 | 8433.90 | 26.95 | 16.10 | 0.00 | 0.00 | 26.95 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28900078.82 | 3644.32 | 14-JAN-05:01 | -20.6 | -20.8 | 0.00 | 0.00 | 01-JAN-00:10 | -20.6 | -20.8 |
February | 26839221.67 | 3589.69 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 30357590.45 | 3928.21 | 04-MAR-05:01 | -26.1 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.1 | -26.5 |
April | 0.489364E+09 | 2980.66 | 12-APR-06:01 | -5.8 | -7.6 | 0.00 | 0.00 | 01-APR-00:10 | -5.8 | -7.6 |
May | 0.218845E+10 | 3914.93 | 31-MAY-15:30 | 21.65 | 10.77 | 0.00 | 0.00 | 01-MAY-00:10 | 21.65 | 10.77 |
June | 0.395778E+10 | 4709.44 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.377597E+10 | 5672.73 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.270219E+10 | 4267.43 | 11-AUG-15:50 | 25.40 | 14.66 | 0.00 | 0.00 | 01-AUG-00:10 | 25.40 | 14.66 |
September | 0.526086E+09 | 2184.56 | 23-SEP-06:03 | 1.10 | 0.44 | 0.00 | 0.00 | 01-SEP-00:10 | 1.10 | 0.44 |
October | 72246038.19 | 2708.44 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 15877462.43 | 3410.75 | 09-NOV-05:01 | -25.4 | -25.6 | 0.00 | 0.00 | 01-NOV-00:10 | -25.4 | -25.6 |
December | 32025749.56 | 3966.27 | 09-DEC-05:01 | -24.2 | -24.5 | 0.00 | 0.00 | 01-DEC-00:10 | -24.2 | -24.5 |
Annual Sum or Average | 0.138461E+11 | 0.00 | ||||||||
Minimum of Months | 15877462.43 | 2184.56 | -26.1 | -26.5 | 0.00 | 0.00 | -26.1 | -26.5 | ||
Maximum of Months | 0.395778E+10 | 5672.73 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269171E+09 | 4560.10 | 11-JAN-17:10 | -34.5 | -34.6 | 0.00 | 0.00 | 01-JAN-00:10 | -34.5 | -34.6 |
February | 0.223317E+09 | 4653.74 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 0.337073E+09 | 4942.66 | 31-MAR-06:10 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.987894E+09 | 3858.87 | 13-APR-06:01 | -7.4 | -8.5 | 0.00 | 0.00 | 01-APR-00:10 | -7.4 | -8.5 |
May | 0.290697E+10 | 4508.58 | 11-MAY-06:08 | 6.47 | 2.38 | 0.00 | 0.00 | 01-MAY-00:10 | 6.47 | 2.38 |
June | 0.438784E+10 | 5509.63 | 23-JUN-06:13 | 14.07 | 10.29 | 0.00 | 0.00 | 01-JUN-00:10 | 14.07 | 10.29 |
July | 0.437762E+10 | 6487.03 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.362577E+10 | 5451.68 | 28-AUG-06:05 | 5.87 | 5.03 | 0.00 | 0.00 | 01-AUG-00:10 | 5.87 | 5.03 |
September | 0.116924E+10 | 3303.60 | 11-SEP-06:06 | 5.50 | 4.95 | 0.00 | 0.00 | 01-SEP-00:10 | 5.50 | 4.95 |
October | 0.273396E+09 | 3156.90 | 27-OCT-06:10 | -18.4 | -18.8 | 0.00 | 0.00 | 01-OCT-00:10 | -18.4 | -18.8 |
November | 0.283477E+09 | 3673.92 | 30-NOV-17:10 | -27.0 | -27.2 | 0.00 | 0.00 | 01-NOV-00:10 | -27.0 | -27.2 |
December | 0.322259E+09 | 3770.26 | 15-DEC-17:10 | -29.9 | -30.1 | 0.00 | 0.00 | 01-DEC-00:10 | -29.9 | -30.1 |
Annual Sum or Average | 0.191640E+11 | 0.00 | ||||||||
Minimum of Months | 0.223317E+09 | 3156.90 | -34.5 | -34.6 | 0.00 | 0.00 | -34.5 | -34.6 | ||
Maximum of Months | 0.438784E+10 | 6487.03 | 14.47 | 13.19 | 0.00 | 0.00 | 14.47 | 13.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338074E+10 | 5785.40 | 20-JAN-17:00 | -11.1 | -11.2 | 0.146582E+10 | 2065.32 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.446586E+10 | 6544.83 | 09-FEB-15:10 | 0.10 | -1.0 | 0.137236E+10 | 2264.34 | 09-FEB-14:00 | 0.10 | -1.0 |
March | 0.737482E+10 | 7218.30 | 22-MAR-16:00 | 5.60 | 2.61 | 0.174285E+10 | 2400.55 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.104166E+11 | 13533.08 | 21-APR-16:00 | 14.40 | 5.45 | 0.177501E+10 | 2606.67 | 27-APR-09:09 | 3.40 | -0.8 |
May | 0.167259E+11 | 17577.57 | 15-MAY-06:02 | 8.07 | 2.53 | 0.206335E+10 | 2606.64 | 19-MAY-13:50 | 13.58 | 8.15 |
June | 0.197230E+11 | 32258.14 | 23-JUN-05:12 | 14.63 | 10.49 | 0.206727E+10 | 2606.65 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.189960E+11 | 31852.92 | 24-JUL-06:02 | 14.18 | 13.06 | 0.192128E+10 | 2606.93 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.179890E+11 | 30816.24 | 01-AUG-06:01 | 10.10 | 9.72 | 0.215278E+10 | 2606.64 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.111242E+11 | 13511.69 | 01-SEP-16:00 | 15.60 | 10.82 | 0.183717E+10 | 2606.66 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.736362E+10 | 7789.26 | 05-OCT-16:00 | 11.10 | 5.87 | 0.165584E+10 | 2555.33 | 04-OCT-13:00 | 11.10 | 5.87 |
November | 0.402046E+10 | 6036.09 | 02-NOV-16:00 | -8.9 | -9.4 | 0.147365E+10 | 2128.64 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.314576E+10 | 5567.50 | 21-DEC-17:00 | -16.7 | -17.3 | 0.140978E+10 | 2013.23 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.124726E+12 | 0.209372E+11 | ||||||||
Minimum of Months | 0.314576E+10 | 5567.50 | -16.7 | -17.3 | 0.137236E+10 | 2013.23 | -16.7 | -17.3 | ||
Maximum of Months | 0.197230E+11 | 32258.14 | 15.60 | 13.06 | 0.215278E+10 | 2606.93 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129694E+10 | 5212.66 | 20-JAN-17:00 | -11.1 | -11.2 | 0.144867E+10 | 1929.41 | 09-JAN-10:20 | -11.1 | -11.2 |
February | 0.236825E+10 | 6257.26 | 09-FEB-15:40 | 0.40 | -0.7 | 0.132828E+10 | 2164.14 | 09-FEB-14:00 | 0.40 | -0.7 |
March | 0.506180E+10 | 7157.48 | 22-MAR-16:00 | 5.60 | 2.61 | 0.164508E+10 | 2316.81 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.881569E+10 | 13202.07 | 21-APR-16:00 | 14.40 | 5.45 | 0.167286E+10 | 2606.55 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.152558E+11 | 17526.44 | 31-MAY-16:00 | 22.20 | 10.79 | 0.204085E+10 | 2606.64 | 19-MAY-13:50 | 22.20 | 10.79 |
June | 0.189368E+11 | 20893.42 | 21-JUN-06:02 | 14.18 | 11.34 | 0.206245E+10 | 2606.62 | 27-JUN-09:09 | 13.90 | 13.18 |
July | 0.181458E+11 | 29621.21 | 24-JUL-06:02 | 14.18 | 13.06 | 0.191632E+10 | 2606.88 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.162778E+11 | 17602.06 | 11-AUG-16:00 | 25.60 | 14.77 | 0.213479E+10 | 2606.63 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.927246E+10 | 12382.93 | 01-SEP-16:00 | 15.60 | 10.82 | 0.172260E+10 | 2606.63 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.498289E+10 | 7376.71 | 03-OCT-16:00 | 11.70 | 6.37 | 0.153672E+10 | 2408.30 | 04-OCT-13:00 | 11.10 | 4.80 |
November | 0.165862E+10 | 5395.32 | 08-NOV-15:50 | -15.7 | -16.1 | 0.143687E+10 | 1965.60 | 08-NOV-14:00 | -15.7 | -16.1 |
December | 0.113632E+10 | 4994.80 | 30-DEC-17:02 | -10.0 | -10.4 | 0.139758E+10 | 1929.35 | 04-DEC-10:39 | -10.0 | -10.4 |
Annual Sum or Average | 0.103209E+12 | 0.203431E+11 | ||||||||
Minimum of Months | 0.113632E+10 | 4994.80 | -15.7 | -16.1 | 0.132828E+10 | 1929.35 | -15.7 | -16.1 | ||
Maximum of Months | 0.189368E+11 | 29621.21 | 25.60 | 14.77 | 0.213479E+10 | 2606.88 | 22.20 | 13.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7139783.54 | 1021.80 | 07-JAN-17:02 | -9.0 | -9.0 | 0.301542E+09 | 406.86 | 11-JAN-10:50 | -34.2 | -34.3 |
February | 8675761.13 | 1020.73 | 11-FEB-17:03 | -1.2 | -2.7 | 0.274520E+09 | 406.81 | 13-FEB-10:00 | -14.4 | -14.8 |
March | 0.126434E+09 | 1321.45 | 22-MAR-15:40 | 5.60 | 2.48 | 0.331849E+09 | 446.18 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.127878E+10 | 2534.34 | 28-APR-15:20 | 12.20 | 4.90 | 0.326947E+09 | 549.47 | 21-APR-13:00 | 12.20 | 4.90 |
May | 0.345321E+10 | 9427.08 | 31-MAY-06:02 | 14.08 | 8.75 | 0.426227E+09 | 549.50 | 19-MAY-13:50 | 14.08 | 8.75 |
June | 0.568442E+10 | 10641.71 | 13-JUN-05:12 | 12.40 | 9.24 | 0.435551E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.523990E+10 | 10704.05 | 07-JUL-05:12 | 15.57 | 11.80 | 0.404609E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.370954E+10 | 5074.88 | 02-AUG-15:30 | 22.75 | 14.69 | 0.443106E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.142032E+10 | 2464.32 | 01-SEP-16:00 | 15.60 | 10.82 | 0.333507E+09 | 549.47 | 01-SEP-13:09 | 15.60 | 10.82 |
October | 0.225944E+09 | 1368.78 | 04-OCT-15:30 | 10.55 | 4.70 | 0.308627E+09 | 459.82 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 6475862.04 | 1016.46 | 18-NOV-17:02 | -13.0 | -13.3 | 0.299603E+09 | 406.86 | 27-NOV-14:20 | -23.9 | -24.2 |
December | 9022014.10 | 1017.55 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291157E+09 | 406.89 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.211699E+11 | 0.417724E+10 | ||||||||
Minimum of Months | 6475862.04 | 1016.46 | -13.0 | -13.3 | 0.274520E+09 | 406.81 | -34.2 | -34.3 | ||
Maximum of Months | 0.568442E+10 | 10704.05 | 22.75 | 14.69 | 0.443106E+09 | 549.55 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8286774.15 | 1099.24 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192591E+09 | 257.59 | 11-JAN-14:39 | -34.0 | -34.1 |
February | 32014219.06 | 1122.51 | 09-FEB-11:30 | -2.5 | -2.7 | 0.174986E+09 | 257.56 | 27-FEB-10:00 | -33.3 | -33.4 |
March | 0.631856E+09 | 2454.25 | 31-MAR-09:55 | -16.1 | -17.3 | 0.219366E+09 | 347.88 | 31-MAR-09:00 | -16.1 | -17.3 |
April | 0.212397E+10 | 6607.37 | 22-APR-09:15 | 8.87 | 3.75 | 0.225646E+09 | 348.28 | 26-APR-09:39 | 4.03 | -0.4 |
May | 0.545736E+10 | 17091.58 | 21-MAY-09:51 | 12.80 | 5.95 | 0.273771E+09 | 349.10 | 12-MAY-09:09 | 12.80 | 5.95 |
June | 0.624266E+10 | 13733.77 | 13-JUN-05:12 | 12.40 | 9.24 | 0.275371E+09 | 348.55 | 08-JUN-09:30 | 12.40 | 9.24 |
July | 0.613483E+10 | 16314.59 | 23-JUL-10:02 | 21.38 | 14.90 | 0.255749E+09 | 348.72 | 07-JUL-09:39 | 21.38 | 14.90 |
August | 0.473972E+10 | 11801.95 | 10-AUG-06:02 | 10.78 | 7.96 | 0.284138E+09 | 348.40 | 31-AUG-09:20 | 4.63 | 0.29 |
September | 0.188826E+10 | 9217.03 | 10-SEP-10:13 | 13.33 | 7.36 | 0.217928E+09 | 348.23 | 15-SEP-09:50 | 4.72 | 3.32 |
October | 0.419568E+09 | 2178.96 | 03-OCT-09:55 | 3.90 | 2.68 | 0.198202E+09 | 347.87 | 03-OCT-09:00 | 3.90 | 2.68 |
November | 7692603.14 | 1094.55 | 18-NOV-17:02 | -13.0 | -13.3 | 0.190868E+09 | 257.59 | 28-NOV-14:20 | -25.2 | -25.5 |
December | 10137322.18 | 1093.47 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185748E+09 | 257.62 | 22-DEC-10:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.276964E+11 | 0.269436E+10 | ||||||||
Minimum of Months | 7692603.14 | 1093.47 | -16.1 | -17.3 | 0.174986E+09 | 257.56 | -34.0 | -34.1 | ||
Maximum of Months | 0.624266E+10 | 17091.58 | 21.38 | 14.90 | 0.284138E+09 | 349.10 | 21.38 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63644711.42 | 2053.37 | 25-JAN-13:30 | -19.8 | -20.0 | 0.304427E+09 | 420.24 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.566289E+09 | 4861.05 | 15-FEB-13:50 | -8.5 | -9.4 | 0.285929E+09 | 549.49 | 09-FEB-14:50 | -8.5 | -9.4 |
March | 0.216032E+10 | 9700.13 | 31-MAR-13:30 | -11.4 | -13.3 | 0.370978E+09 | 550.38 | 15-MAR-13:09 | -11.4 | -13.3 |
April | 0.536355E+10 | 19111.02 | 23-APR-12:43 | 10.00 | 3.83 | 0.359868E+09 | 550.15 | 07-APR-13:39 | 10.00 | 3.83 |
May | 0.781474E+10 | 26872.70 | 21-MAY-13:11 | 14.80 | 6.89 | 0.419597E+09 | 549.65 | 09-MAY-13:39 | 14.80 | 6.89 |
June | 0.887448E+10 | 18648.45 | 04-JUN-14:52 | 19.40 | 11.69 | 0.430611E+09 | 549.51 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.878439E+10 | 25954.28 | 23-JUL-13:22 | 25.00 | 15.26 | 0.399552E+09 | 550.06 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.825849E+10 | 24722.25 | 27-AUG-13:42 | 19.13 | 14.11 | 0.439490E+09 | 549.90 | 25-AUG-13:00 | 19.13 | 14.11 |
September | 0.407280E+10 | 24157.95 | 10-SEP-11:32 | 15.20 | 8.17 | 0.348829E+09 | 549.52 | 08-SEP-13:09 | 15.20 | 8.17 |
October | 0.135617E+10 | 10473.47 | 03-OCT-13:30 | 10.85 | 6.24 | 0.325439E+09 | 549.49 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.159477E+09 | 2846.91 | 08-NOV-13:50 | -13.4 | -14.2 | 0.303289E+09 | 537.54 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 16401661.50 | 1719.13 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293469E+09 | 406.93 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.474908E+11 | 0.428148E+10 | ||||||||
Minimum of Months | 16401661.50 | 1719.13 | -19.8 | -20.0 | 0.285929E+09 | 406.93 | -18.9 | -19.2 | ||
Maximum of Months | 0.887448E+10 | 26872.70 | 25.00 | 15.26 | 0.439490E+09 | 550.38 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8587078.01 | 1135.81 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192594E+09 | 257.57 | 03-JAN-10:39 | -9.0 | -9.0 |
February | 25579981.54 | 1140.19 | 18-FEB-17:02 | -14.1 | -15.6 | 0.174959E+09 | 257.55 | 22-FEB-10:50 | -25.5 | -25.7 |
March | 0.322606E+09 | 1796.97 | 31-MAR-17:00 | -9.4 | -11.7 | 0.212363E+09 | 314.79 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.218951E+10 | 10227.44 | 22-APR-19:03 | 11.42 | 4.79 | 0.208364E+09 | 347.56 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.380213E+10 | 16851.97 | 21-MAY-17:52 | 16.10 | 7.32 | 0.258761E+09 | 347.85 | 19-MAY-13:00 | 16.10 | 7.32 |
June | 0.518161E+10 | 15552.75 | 10-JUN-17:04 | 21.20 | 10.81 | 0.272155E+09 | 347.85 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.468152E+10 | 11168.59 | 09-JUL-20:03 | 19.22 | 13.03 | 0.251883E+09 | 347.86 | 21-JUL-13:50 | 25.82 | 14.23 |
August | 0.386945E+10 | 13091.81 | 27-AUG-17:02 | 21.02 | 12.75 | 0.271562E+09 | 347.85 | 01-AUG-09:00 | 21.02 | 12.75 |
September | 0.162393E+10 | 4959.98 | 08-SEP-16:00 | 14.40 | 9.03 | 0.205535E+09 | 344.90 | 01-SEP-13:00 | 14.40 | 9.03 |
October | 0.265307E+09 | 1744.21 | 03-OCT-15:10 | 12.62 | 6.83 | 0.195180E+09 | 312.84 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 9453653.92 | 1135.65 | 18-NOV-17:02 | -13.0 | -13.3 | 0.190874E+09 | 257.57 | 29-NOV-10:09 | -29.7 | -29.9 |
December | 10466928.19 | 1129.93 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185747E+09 | 257.58 | 12-DEC-14:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.219902E+11 | 0.261998E+10 | ||||||||
Minimum of Months | 8587078.01 | 1129.93 | -14.1 | -15.6 | 0.174959E+09 | 257.55 | -29.7 | -29.9 | ||
Maximum of Months | 0.518161E+10 | 16851.97 | 21.20 | 13.03 | 0.272155E+09 | 347.86 | 25.82 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9894303.84 | 1007.49 | 07-JAN-17:02 | -9.0 | -9.0 | 0.297871E+09 | 406.85 | 13-JAN-14:50 | -25.8 | -25.9 |
February | 8408541.01 | 1000.88 | 11-FEB-17:03 | -1.2 | -2.7 | 0.271535E+09 | 406.80 | 28-FEB-14:09 | -21.7 | -22.3 |
March | 48096745.13 | 1089.64 | 22-MAR-14:10 | 5.60 | 1.96 | 0.331304E+09 | 407.55 | 22-MAR-13:00 | 5.60 | 1.96 |
April | 0.101477E+10 | 1536.90 | 28-APR-16:00 | 12.20 | 5.13 | 0.312887E+09 | 507.60 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.255958E+10 | 4004.21 | 31-MAY-06:02 | 14.08 | 8.75 | 0.417983E+09 | 549.49 | 19-MAY-13:00 | 14.08 | 8.75 |
June | 0.433701E+10 | 8602.64 | 07-JUN-05:12 | 7.40 | 5.52 | 0.434998E+09 | 549.50 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.447149E+10 | 8992.31 | 11-JUL-05:12 | 15.37 | 12.05 | 0.404626E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.352790E+10 | 7521.38 | 02-AUG-06:02 | 11.28 | 10.30 | 0.448338E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.179123E+10 | 1999.47 | 01-SEP-16:00 | 15.60 | 10.82 | 0.353025E+09 | 549.47 | 01-SEP-13:20 | 15.60 | 10.82 |
October | 0.530593E+09 | 1394.22 | 04-OCT-15:10 | 10.92 | 4.77 | 0.314011E+09 | 476.41 | 06-OCT-13:00 | 10.60 | 4.48 |
November | 8312978.15 | 1013.99 | 04-NOV-16:02 | -9.6 | -11.3 | 0.300600E+09 | 406.82 | 28-NOV-14:39 | -25.4 | -25.6 |
December | 17915131.59 | 1005.46 | 30-DEC-17:02 | -10.0 | -10.4 | 0.290841E+09 | 406.88 | 27-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.183252E+11 | 0.417802E+10 | ||||||||
Minimum of Months | 8312978.15 | 1000.88 | -10.0 | -11.3 | 0.271535E+09 | 406.80 | -25.8 | -25.9 | ||
Maximum of Months | 0.447149E+10 | 8992.31 | 15.60 | 12.05 | 0.448338E+09 | 549.54 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9193349.86 | 901.91 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192079E+09 | 257.57 | 09-JAN-14:00 | -19.4 | -19.6 |
February | 20964244.35 | 898.76 | 18-FEB-17:02 | -14.1 | -15.6 | 0.174841E+09 | 257.55 | 22-FEB-14:09 | -17.6 | -18.3 |
March | 0.446853E+09 | 1910.44 | 31-MAR-09:20 | -17.2 | -18.4 | 0.217504E+09 | 347.88 | 31-MAR-09:00 | -16.1 | -17.3 |
April | 0.166079E+10 | 4467.45 | 22-APR-08:30 | 6.65 | 2.48 | 0.225536E+09 | 347.88 | 13-APR-09:20 | 6.65 | 2.48 |
May | 0.447585E+10 | 12744.26 | 14-MAY-09:11 | 15.37 | 8.02 | 0.275121E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.527993E+10 | 11055.55 | 07-JUN-05:12 | 7.40 | 5.52 | 0.275697E+09 | 348.20 | 08-JUN-09:09 | 15.78 | 10.18 |
July | 0.555113E+10 | 12863.39 | 23-JUL-10:22 | 21.95 | 15.11 | 0.256827E+09 | 348.40 | 07-JUL-09:50 | 21.95 | 15.11 |
August | 0.462172E+10 | 10184.53 | 11-AUG-06:02 | 10.97 | 7.10 | 0.287152E+09 | 348.26 | 11-AUG-09:20 | 17.23 | 10.78 |
September | 0.208586E+10 | 7041.10 | 10-SEP-10:23 | 13.60 | 7.47 | 0.235496E+09 | 347.88 | 08-SEP-13:09 | 13.60 | 7.47 |
October | 0.674403E+09 | 2577.47 | 03-OCT-09:25 | 2.50 | 1.67 | 0.204655E+09 | 347.87 | 03-OCT-09:00 | 3.90 | 2.68 |
November | 7387561.97 | 907.86 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191191E+09 | 257.57 | 28-NOV-14:30 | -25.3 | -25.6 |
December | 13307038.89 | 899.98 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185829E+09 | 257.62 | 27-DEC-14:20 | -10.0 | -10.4 |
Annual Sum or Average | 0.248474E+11 | 0.272193E+10 | ||||||||
Minimum of Months | 7387561.97 | 898.76 | -17.2 | -18.4 | 0.174841E+09 | 257.55 | -25.3 | -25.6 | ||
Maximum of Months | 0.555113E+10 | 12863.39 | 21.95 | 15.11 | 0.287152E+09 | 348.40 | 21.95 | 15.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13503397.05 | 1410.48 | 28-JAN-17:01 | -21.8 | -22.5 | 0.236178E+09 | 406.68 | 19-JAN-10:20 | -21.8 | -22.5 |
February | 0.135097E+09 | 1860.74 | 18-FEB-13:30 | -14.4 | -15.8 | 0.241709E+09 | 440.08 | 09-FEB-14:09 | -14.4 | -15.8 |
March | 0.431276E+09 | 2198.52 | 11-MAR-13:40 | -3.7 | -5.7 | 0.317524E+09 | 503.19 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.272376E+10 | 14399.44 | 23-APR-14:32 | 9.27 | 3.22 | 0.337947E+09 | 549.50 | 12-APR-13:09 | 9.27 | 3.22 |
May | 0.466666E+10 | 17224.94 | 14-MAY-12:31 | 18.53 | 9.40 | 0.407971E+09 | 549.50 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.609716E+10 | 11588.25 | 04-JUN-14:32 | 19.23 | 11.76 | 0.424042E+09 | 549.54 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.688426E+10 | 20182.94 | 23-JUL-13:42 | 25.00 | 15.26 | 0.396833E+09 | 549.53 | 21-JUL-13:30 | 25.00 | 15.26 |
August | 0.650943E+10 | 21885.80 | 27-AUG-13:31 | 18.87 | 14.02 | 0.437484E+09 | 549.56 | 11-AUG-13:30 | 18.87 | 14.02 |
September | 0.307448E+10 | 10196.07 | 09-SEP-14:00 | 13.90 | 8.84 | 0.345793E+09 | 549.52 | 08-SEP-13:09 | 13.90 | 8.84 |
October | 0.782264E+09 | 6831.91 | 03-OCT-13:40 | 11.13 | 6.36 | 0.306667E+09 | 549.51 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 27414215.41 | 1513.74 | 08-NOV-13:16 | -13.7 | -14.5 | 0.252275E+09 | 406.72 | 01-NOV-09:00 | -13.7 | -14.5 |
December | 13395433.18 | 1403.17 | 30-DEC-17:02 | -10.0 | -10.4 | 0.216230E+09 | 394.08 | 29-DEC-14:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.313587E+11 | 0.392065E+10 | ||||||||
Minimum of Months | 13395433.18 | 1403.17 | -21.8 | -22.5 | 0.216230E+09 | 394.08 | -21.8 | -22.5 | ||
Maximum of Months | 0.688426E+10 | 21885.80 | 25.00 | 15.26 | 0.437484E+09 | 549.56 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9630129.16 | 949.81 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192127E+09 | 257.55 | 31-JAN-14:39 | -20.0 | -20.6 |
February | 10675531.62 | 950.16 | 18-FEB-17:02 | -14.1 | -15.6 | 0.174574E+09 | 257.54 | 21-FEB-14:20 | -18.1 | -18.6 |
March | 0.165050E+09 | 1349.47 | 31-MAR-17:00 | -9.4 | -11.7 | 0.211067E+09 | 281.67 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.168293E+10 | 7513.83 | 22-APR-19:03 | 11.42 | 4.79 | 0.209241E+09 | 340.90 | 21-APR-13:00 | 11.42 | 4.79 |
May | 0.282738E+10 | 7471.70 | 14-MAY-19:22 | 16.15 | 8.31 | 0.261272E+09 | 347.85 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.413909E+10 | 10278.34 | 11-JUN-17:11 | 18.70 | 10.96 | 0.274031E+09 | 347.86 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.397811E+10 | 9245.95 | 09-JUL-19:53 | 19.40 | 13.11 | 0.254909E+09 | 347.85 | 19-JUL-09:39 | 17.93 | 14.35 |
August | 0.357247E+10 | 13710.72 | 27-AUG-18:12 | 20.20 | 12.03 | 0.282546E+09 | 347.85 | 28-AUG-09:00 | 12.20 | 8.79 |
September | 0.181185E+10 | 3800.84 | 08-SEP-16:00 | 14.40 | 9.03 | 0.220911E+09 | 347.84 | 01-SEP-13:00 | 14.40 | 9.03 |
October | 0.473329E+09 | 1473.17 | 03-OCT-15:20 | 12.43 | 6.74 | 0.198304E+09 | 316.36 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 9713315.34 | 957.97 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191205E+09 | 257.56 | 27-NOV-14:39 | -23.9 | -24.2 |
December | 14018516.54 | 948.65 | 30-DEC-17:02 | -10.0 | -10.4 | 0.185854E+09 | 257.60 | 12-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.186942E+11 | 0.265604E+10 | ||||||||
Minimum of Months | 9630129.16 | 948.65 | -14.1 | -15.6 | 0.174574E+09 | 257.54 | -23.9 | -24.2 | ||
Maximum of Months | 0.413909E+10 | 13710.72 | 20.20 | 13.11 | 0.282546E+09 | 347.86 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8952518.51 | 1004.64 | 07-JAN-17:02 | -9.0 | -9.0 | 0.303217E+09 | 406.84 | 12-JAN-14:39 | -36.1 | -36.2 |
February | 24408534.88 | 1008.31 | 11-FEB-17:03 | -1.2 | -2.7 | 0.275875E+09 | 406.80 | 22-FEB-10:39 | -25.9 | -26.1 |
March | 0.272350E+09 | 1329.27 | 22-MAR-15:30 | 5.60 | 2.42 | 0.334708E+09 | 461.86 | 22-MAR-13:00 | 5.60 | 2.42 |
April | 0.160262E+10 | 2789.14 | 28-APR-15:20 | 12.20 | 4.90 | 0.342574E+09 | 549.48 | 24-APR-13:00 | 12.20 | 4.90 |
May | 0.382835E+10 | 9078.17 | 31-MAY-06:02 | 14.08 | 8.75 | 0.433127E+09 | 549.50 | 19-MAY-13:00 | 14.08 | 8.75 |
June | 0.593636E+10 | 10310.38 | 13-JUN-05:12 | 12.40 | 9.24 | 0.436275E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.548143E+10 | 10384.01 | 11-JUL-05:12 | 15.37 | 12.05 | 0.405536E+09 | 549.56 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.407226E+10 | 8804.95 | 10-AUG-06:02 | 10.78 | 7.96 | 0.450222E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.181414E+10 | 2895.38 | 01-SEP-13:40 | 14.63 | 10.60 | 0.357066E+09 | 549.49 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.510895E+09 | 1449.02 | 04-OCT-15:30 | 10.55 | 4.70 | 0.314538E+09 | 490.68 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 7572331.87 | 1001.89 | 18-NOV-17:02 | -13.0 | -13.3 | 0.301157E+09 | 406.81 | 27-NOV-14:39 | -23.9 | -24.2 |
December | 10720703.11 | 1000.73 | 23-DEC-17:02 | -2.6 | -3.4 | 0.292854E+09 | 406.86 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.235701E+11 | 0.424715E+10 | ||||||||
Minimum of Months | 7572331.87 | 1000.73 | -13.0 | -13.3 | 0.275875E+09 | 406.80 | -36.1 | -36.2 | ||
Maximum of Months | 0.593636E+10 | 10384.01 | 15.37 | 12.05 | 0.450222E+09 | 549.56 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10573691.12 | 1110.92 | 07-JAN-17:02 | -9.0 | -9.0 | 0.141739E+09 | 250.79 | 03-JAN-09:39 | -9.0 | -9.0 |
February | 77981697.01 | 1290.50 | 15-FEB-11:20 | -14.3 | -14.6 | 0.128980E+09 | 262.87 | 15-FEB-11:39 | -13.0 | -13.4 |
March | 0.877360E+09 | 3524.99 | 31-MAR-10:05 | -15.9 | -17.2 | 0.163589E+09 | 338.72 | 31-MAR-10:09 | -15.9 | -17.2 |
April | 0.251886E+10 | 9896.27 | 23-APR-10:23 | 9.70 | 3.62 | 0.169298E+09 | 339.16 | 19-APR-08:00 | 9.70 | 3.62 |
May | 0.573815E+10 | 16057.90 | 21-MAY-08:42 | 11.73 | 5.60 | 0.203046E+09 | 339.00 | 09-MAY-08:00 | 11.73 | 5.60 |
June | 0.628589E+10 | 13753.09 | 07-JUN-05:12 | 7.40 | 5.52 | 0.203687E+09 | 339.27 | 07-JUN-08:39 | 13.67 | 9.06 |
July | 0.617225E+10 | 16277.60 | 23-JUL-09:42 | 20.63 | 14.69 | 0.190018E+09 | 339.84 | 31-JUL-10:30 | 18.85 | 11.80 |
August | 0.496464E+10 | 13040.35 | 27-AUG-10:12 | 12.43 | 10.50 | 0.210665E+09 | 339.63 | 10-AUG-10:30 | 12.43 | 10.50 |
September | 0.229798E+10 | 11418.18 | 10-SEP-10:23 | 13.60 | 7.47 | 0.167591E+09 | 339.13 | 15-SEP-08:09 | 2.38 | 1.87 |
October | 0.670033E+09 | 3084.71 | 03-OCT-10:05 | 4.27 | 2.93 | 0.148377E+09 | 338.72 | 03-OCT-10:09 | 4.27 | 2.93 |
November | 8870048.50 | 1109.11 | 18-NOV-17:02 | -13.0 | -13.3 | 0.140516E+09 | 250.78 | 13-NOV-09:00 | -13.0 | -13.3 |
December | 11838185.06 | 1105.71 | 30-DEC-17:02 | -10.0 | -10.4 | 0.136748E+09 | 250.77 | 18-DEC-16:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.296344E+11 | 0.200425E+10 | ||||||||
Minimum of Months | 8870048.50 | 1105.71 | -15.9 | -17.2 | 0.128980E+09 | 250.77 | -15.9 | -17.2 | ||
Maximum of Months | 0.628589E+10 | 16277.60 | 20.63 | 14.69 | 0.210665E+09 | 339.84 | 18.85 | 11.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117240E+09 | 2219.47 | 25-JAN-13:30 | -19.8 | -20.0 | 0.305307E+09 | 455.52 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.756178E+09 | 5804.82 | 15-FEB-13:40 | -8.7 | -9.6 | 0.290569E+09 | 549.49 | 09-FEB-14:00 | -8.7 | -9.6 |
March | 0.270560E+10 | 10775.70 | 31-MAR-13:30 | -11.4 | -13.3 | 0.378322E+09 | 549.49 | 13-MAR-13:00 | -11.4 | -13.3 |
April | 0.605832E+10 | 18313.75 | 09-APR-13:43 | 2.12 | -2.6 | 0.369122E+09 | 549.64 | 21-APR-13:00 | 13.90 | 5.62 |
May | 0.815186E+10 | 23484.79 | 28-MAY-14:12 | 14.27 | 6.97 | 0.427915E+09 | 550.42 | 12-MAY-13:50 | 14.27 | 6.97 |
June | 0.896041E+10 | 19100.96 | 04-JUN-14:32 | 19.23 | 11.76 | 0.433757E+09 | 549.55 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.884174E+10 | 24665.23 | 23-JUL-13:42 | 25.00 | 15.26 | 0.403279E+09 | 550.05 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.856174E+10 | 26753.56 | 27-AUG-13:31 | 18.87 | 14.02 | 0.447855E+09 | 549.89 | 25-AUG-13:00 | 18.87 | 14.02 |
September | 0.481760E+10 | 13715.37 | 10-SEP-11:43 | 15.40 | 8.26 | 0.365474E+09 | 549.52 | 08-SEP-13:09 | 15.40 | 8.26 |
October | 0.183881E+10 | 11224.36 | 03-OCT-13:30 | 10.85 | 6.24 | 0.334320E+09 | 549.49 | 30-OCT-13:00 | -11.1 | -12.2 |
November | 0.246840E+09 | 3602.68 | 08-NOV-13:40 | -13.5 | -14.3 | 0.305199E+09 | 549.49 | 08-NOV-14:50 | -13.8 | -14.5 |
December | 18430491.46 | 1664.70 | 30-DEC-17:02 | -10.0 | -10.4 | 0.293908E+09 | 406.82 | 12-DEC-14:30 | -10.0 | -10.4 |
Annual Sum or Average | 0.510748E+11 | 0.435503E+10 | ||||||||
Minimum of Months | 18430491.46 | 1664.70 | -19.8 | -20.0 | 0.290569E+09 | 406.82 | -18.9 | -19.2 | ||
Maximum of Months | 0.896041E+10 | 26753.56 | 25.00 | 15.26 | 0.447855E+09 | 550.42 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10511478.58 | 1099.10 | 07-JAN-17:02 | -9.0 | -9.0 | 0.192841E+09 | 257.56 | 03-JAN-10:39 | -9.0 | -9.0 |
February | 52272449.55 | 1184.09 | 15-FEB-15:40 | -7.2 | -8.6 | 0.175245E+09 | 257.53 | 22-FEB-10:50 | -25.5 | -25.7 |
March | 0.472286E+09 | 1889.78 | 31-MAR-16:50 | -9.4 | -11.7 | 0.214062E+09 | 330.94 | 31-MAR-15:00 | -9.4 | -11.7 |
April | 0.253464E+10 | 10929.60 | 22-APR-19:03 | 11.42 | 4.79 | 0.215949E+09 | 347.83 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.398211E+10 | 15665.71 | 28-MAY-18:12 | 16.70 | 8.41 | 0.267043E+09 | 347.85 | 19-MAY-13:00 | 16.70 | 8.41 |
June | 0.525010E+10 | 14801.31 | 10-JUN-17:04 | 21.20 | 10.81 | 0.274468E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.473351E+10 | 11135.93 | 30-JUL-19:03 | 17.20 | 11.77 | 0.254762E+09 | 347.88 | 19-JUL-09:09 | 17.20 | 11.77 |
August | 0.402154E+10 | 16256.13 | 27-AUG-16:52 | 21.10 | 12.86 | 0.279589E+09 | 347.85 | 01-AUG-09:00 | 21.10 | 12.86 |
September | 0.202449E+10 | 8561.85 | 02-SEP-17:42 | 16.70 | 10.38 | 0.217066E+09 | 347.84 | 01-SEP-13:00 | 16.70 | 10.38 |
October | 0.497839E+09 | 1767.75 | 03-OCT-15:10 | 12.62 | 6.83 | 0.197944E+09 | 327.36 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 13708571.56 | 1101.12 | 18-NOV-17:02 | -13.0 | -13.3 | 0.191142E+09 | 257.55 | 13-NOV-10:30 | -13.0 | -13.3 |
December | 11721672.94 | 1094.53 | 30-DEC-17:02 | -10.0 | -10.4 | 0.186011E+09 | 257.57 | 12-DEC-14:09 | -10.0 | -10.4 |
Annual Sum or Average | 0.236047E+11 | 0.266612E+10 | ||||||||
Minimum of Months | 10511478.58 | 1094.53 | -13.0 | -13.3 | 0.175245E+09 | 257.53 | -25.5 | -25.7 | ||
Maximum of Months | 0.525010E+10 | 16256.13 | 21.20 | 12.86 | 0.279589E+09 | 347.88 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526507E+09 | 12382.12 | 02-JAN-05:01 | -15.6 |
February | 58424380.41 | 8223.52 | 21-FEB-06:02 | -23.3 |
March | 3419660.49 | 6669.71 | 01-MAR-07:01 | -28.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 32815504.22 | 8212.19 | 27-NOV-06:01 | -26.7 |
December | 87785362.60 | 8086.14 | 04-DEC-06:03 | -19.4 |
Annual Sum or Average | 0.708952E+09 | |||
Minimum of Months | 0.00 | 0.00 | -28.8 | |
Maximum of Months | 0.526507E+09 | 12382.12 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138226E+11 | 18771.05 | 12-JAN-06:10 | -38.3 |
February | 0.103126E+11 | 18654.30 | 27-FEB-05:08 | -36.1 |
March | 0.711180E+10 | 17890.95 | 02-MAR-06:08 | -26.7 |
April | 0.216711E+10 | 16121.34 | 03-APR-05:13 | -21.3 |
May | 0.381403E+09 | 6645.81 | 21-MAY-07:11 | 7.60 |
June | 73351660.32 | 5032.48 | 19-JUN-04:40 | 7.43 |
July | 79844049.23 | 4610.86 | 21-JUL-05:12 | 11.50 |
August | 0.292521E+09 | 4695.07 | 31-AUG-05:03 | -1.2 |
September | 0.134668E+10 | 7837.42 | 25-SEP-06:02 | -1.8 |
October | 0.538361E+10 | 15633.02 | 31-OCT-05:12 | -18.1 |
November | 0.126125E+11 | 18649.11 | 30-NOV-06:08 | -28.0 |
December | 0.145833E+11 | 18211.28 | 15-DEC-06:09 | -32.9 |
Annual Sum or Average | 0.681673E+11 | |||
Minimum of Months | 73351660.32 | 4610.86 | -38.3 | |
Maximum of Months | 0.145833E+11 | 18771.05 | 11.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554275E+10 | 11923.04 | 02-JAN-08:45 | -15.4 |
February | 0.388564E+10 | 11015.10 | 21-FEB-08:06 | -22.8 |
March | 0.280450E+10 | 8816.47 | 06-MAR-07:25 | -20.6 |
April | 0.865308E+09 | 10303.20 | 09-APR-13:43 | 2.12 |
May | 64207533.82 | 8658.18 | 28-MAY-16:12 | 16.30 |
June | 24553910.34 | 4326.45 | 04-JUN-15:12 | 19.60 |
July | 27801504.31 | 5480.68 | 23-JUL-11:02 | 22.98 |
August | 26322758.67 | 5977.16 | 20-AUG-13:23 | 14.75 |
September | 0.388120E+09 | 6152.11 | 10-SEP-10:23 | 13.60 |
October | 0.211259E+10 | 9291.39 | 30-OCT-06:25 | -15.3 |
November | 0.463005E+10 | 11093.96 | 13-NOV-08:04 | -16.6 |
December | 0.540435E+10 | 11289.85 | 04-DEC-08:12 | -20.0 |
Annual Sum or Average | 0.257762E+11 | |||
Minimum of Months | 24553910.34 | 4326.45 | -22.8 | |
Maximum of Months | 0.554275E+10 | 11923.04 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405937E+10 | 9120.20 | 02-JAN-06:10 | -15.4 |
February | 0.280548E+10 | 6131.18 | 21-FEB-07:01 | -23.2 |
March | 0.179008E+10 | 4403.46 | 06-MAR-08:23 | -17.8 |
April | 0.376933E+09 | 5387.19 | 25-APR-05:02 | -5.4 |
May | 27668526.15 | 3101.51 | 28-MAY-14:10 | 14.08 |
June | 19891063.30 | 2107.26 | 11-JUN-16:31 | 18.90 |
July | 28857618.84 | 3038.83 | 23-JUL-11:42 | 23.72 |
August | 29082399.95 | 3509.80 | 27-AUG-16:52 | 21.10 |
September | 0.157745E+09 | 5476.67 | 18-SEP-05:02 | 1.78 |
October | 0.129785E+10 | 4073.11 | 30-OCT-11:01 | -15.6 |
November | 0.308286E+10 | 6446.28 | 13-NOV-07:01 | -17.1 |
December | 0.366721E+10 | 6624.12 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.173430E+11 | |||
Minimum of Months | 19891063.30 | 2107.26 | -23.2 | |
Maximum of Months | 0.405937E+10 | 9120.20 | 23.72 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272141E+10 | 19956.10 | 02-JAN-05:01 | -15.6 |
February | 0.130496E+10 | 18777.05 | 21-FEB-05:11 | -23.0 |
March | 0.275521E+09 | 16677.08 | 06-MAR-06:01 | -21.1 |
April | 13167855.95 | 14206.21 | 03-APR-06:01 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.186610E+09 | 16680.74 | 30-OCT-05:01 | -14.5 |
November | 0.158001E+10 | 18845.55 | 13-NOV-05:11 | -19.8 |
December | 0.249085E+10 | 18853.14 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.857253E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.272141E+10 | 19956.10 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839476E+10 | 27580.26 | 01-JAN-22:42 | -15.0 |
February | 0.496559E+10 | 27464.63 | 27-FEB-04:52 | -36.1 |
March | 0.226186E+10 | 26407.20 | 06-MAR-05:01 | -20.2 |
April | 0.328410E+09 | 24580.11 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 55848614.66 | 20886.25 | 28-SEP-06:01 | -2.8 |
October | 0.165385E+10 | 26486.58 | 30-OCT-04:11 | -14.4 |
November | 0.653072E+10 | 27284.85 | 27-NOV-02:12 | -26.1 |
December | 0.833701E+10 | 27242.90 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.325280E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.839476E+10 | 27580.26 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103084E+11 | 10537.51 | 30-JAN-04:22 | -25.3 |
February | 0.750200E+10 | 10554.28 | 27-FEB-04:52 | -36.1 |
March | 0.475809E+10 | 10013.07 | 06-MAR-04:23 | -20.0 |
April | 0.919254E+09 | 9813.60 | 03-APR-04:11 | -21.1 |
May | 619513.21 | 3874.17 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3587247.60 | 7551.23 | 31-AUG-06:02 | -1.5 |
September | 0.305083E+09 | 8667.69 | 25-SEP-05:01 | -1.2 |
October | 0.337867E+10 | 9968.85 | 30-OCT-03:32 | -14.0 |
November | 0.900580E+10 | 10353.29 | 27-NOV-02:12 | -26.1 |
December | 0.105550E+11 | 10323.37 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.467365E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.105550E+11 | 10554.28 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684904E+10 | 10441.43 | 30-JAN-03:02 | -25.0 |
February | 0.438443E+10 | 10470.47 | 27-FEB-04:52 | -36.1 |
March | 0.206878E+10 | 9656.01 | 06-MAR-04:23 | -20.0 |
April | 0.384948E+09 | 9484.88 | 03-APR-04:11 | -21.1 |
May | 231953.91 | 1546.36 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1963162.97 | 6453.38 | 31-AUG-06:02 | -1.5 |
September | 0.142324E+09 | 7975.77 | 25-SEP-05:01 | -1.2 |
October | 0.183783E+10 | 9610.11 | 30-OCT-03:32 | -14.0 |
November | 0.591592E+10 | 10173.48 | 27-NOV-02:12 | -26.1 |
December | 0.712756E+10 | 10127.81 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.287130E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.712756E+10 | 10470.47 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.938405E+10 | 16090.10 | 30-JAN-04:22 | -25.3 |
February | 0.525365E+10 | 16029.07 | 27-FEB-04:52 | -36.1 |
March | 0.265611E+10 | 14849.95 | 06-MAR-04:23 | -20.0 |
April | 0.544234E+09 | 14397.72 | 03-APR-04:11 | -21.1 |
May | 2455586.54 | 7997.36 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3483270.54 | 9724.78 | 31-AUG-06:02 | -1.5 |
September | 0.197818E+09 | 12179.09 | 25-SEP-05:01 | -1.2 |
October | 0.229072E+10 | 14794.99 | 30-OCT-04:11 | -14.4 |
November | 0.751607E+10 | 15650.86 | 27-NOV-02:12 | -26.1 |
December | 0.103479E+11 | 15608.51 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.381965E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.103479E+11 | 16090.10 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.694347E+10 | 10633.35 | 30-JAN-03:02 | -25.0 |
February | 0.479923E+10 | 10640.57 | 27-FEB-04:52 | -36.1 |
March | 0.277273E+10 | 9819.43 | 06-MAR-04:23 | -20.0 |
April | 0.479045E+09 | 9539.65 | 03-APR-04:11 | -21.1 |
May | 2134913.82 | 5216.24 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3027425.13 | 6344.98 | 31-AUG-06:02 | -1.5 |
September | 0.188740E+09 | 8108.48 | 25-SEP-05:01 | -1.2 |
October | 0.214261E+10 | 9764.69 | 30-OCT-03:32 | -14.0 |
November | 0.590849E+10 | 10341.03 | 27-NOV-02:12 | -26.1 |
December | 0.714212E+10 | 10285.91 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.303816E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.714212E+10 | 10640.57 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.833478E+10 | 8529.56 | 01-JAN-20:02 | -14.5 |
February | 0.652672E+10 | 8574.35 | 27-FEB-04:52 | -36.1 |
March | 0.443247E+10 | 8113.31 | 06-MAR-05:01 | -20.2 |
April | 0.704362E+09 | 7919.72 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 24160926.57 | 6383.62 | 28-SEP-06:01 | -2.8 |
October | 0.138385E+10 | 7813.75 | 30-OCT-04:01 | -14.4 |
November | 0.579443E+10 | 8249.40 | 27-NOV-02:12 | -26.1 |
December | 0.776202E+10 | 8258.39 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.349628E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.833478E+10 | 8574.35 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574048E+10 | 8117.45 | 01-JAN-18:42 | -14.4 |
February | 0.387887E+10 | 8199.55 | 27-FEB-04:52 | -36.1 |
March | 0.159601E+10 | 7600.42 | 06-MAR-05:01 | -20.2 |
April | 0.181317E+09 | 6908.53 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 11665567.88 | 5421.14 | 28-SEP-06:01 | -2.8 |
October | 0.681754E+09 | 7264.77 | 30-OCT-04:01 | -14.4 |
November | 0.387589E+10 | 7785.75 | 27-NOV-02:12 | -26.1 |
December | 0.541535E+10 | 7806.55 | 04-DEC-00:12 | -22.0 |
Annual Sum or Average | 0.213813E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.574048E+10 | 8199.55 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141416E+11 | 20194.19 | 12-JAN-07:10 | -38.3 |
February | 0.955847E+10 | 19728.31 | 27-FEB-07:10 | -34.9 |
March | 0.661651E+10 | 18164.48 | 01-MAR-08:00 | -28.3 |
April | 0.180497E+10 | 15501.37 | 03-APR-06:10 | -21.5 |
May | 0.557191E+09 | 8825.65 | 04-MAY-06:20 | 4.47 |
June | 0.114315E+09 | 7954.01 | 02-JUN-06:10 | 7.15 |
July | 83248954.87 | 7724.63 | 17-JUL-06:05 | 8.48 |
August | 0.254485E+09 | 9432.64 | 30-AUG-06:10 | 0.10 |
September | 0.114863E+10 | 11013.15 | 28-SEP-06:10 | -2.8 |
October | 0.432282E+10 | 15234.31 | 31-OCT-07:00 | -19.4 |
November | 0.113614E+11 | 18073.65 | 29-NOV-08:00 | -28.9 |
December | 0.143173E+11 | 19306.12 | 15-DEC-07:10 | -33.4 |
Annual Sum or Average | 0.642809E+11 | |||
Minimum of Months | 83248954.87 | 7724.63 | -38.3 | |
Maximum of Months | 0.143173E+11 | 20194.19 | 8.48 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583863E+10 | 8339.41 | 01-JAN-20:02 | -14.5 |
February | 0.429725E+10 | 8413.22 | 27-FEB-04:52 | -36.1 |
March | 0.239452E+10 | 7835.65 | 06-MAR-05:01 | -20.2 |
April | 0.203743E+09 | 6509.15 | 04-APR-05:01 | -11.6 |
May | 247716.25 | 1651.44 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 15498046.84 | 5504.69 | 28-SEP-06:01 | -2.8 |
October | 0.867154E+09 | 7497.51 | 30-OCT-04:01 | -14.4 |
November | 0.387283E+10 | 7982.87 | 27-NOV-02:12 | -26.1 |
December | 0.543265E+10 | 8002.53 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.229225E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.583863E+10 | 8413.22 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696783E+10 | 8964.71 | 30-JAN-03:02 | -25.0 |
February | 0.459149E+10 | 8982.25 | 27-FEB-04:52 | -36.1 |
March | 0.245384E+10 | 8463.17 | 06-MAR-05:11 | -20.4 |
April | 0.292931E+09 | 8145.26 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 38741757.98 | 6750.78 | 30-SEP-05:01 | -4.5 |
October | 0.149018E+10 | 8430.77 | 23-OCT-04:01 | -11.1 |
November | 0.552046E+10 | 8655.65 | 13-NOV-05:11 | -19.8 |
December | 0.697775E+10 | 8791.50 | 04-DEC-01:32 | -21.3 |
Annual Sum or Average | 0.283332E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.697775E+10 | 8982.25 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471785E+10 | 8834.68 | 30-JAN-03:02 | -25.0 |
February | 0.266331E+10 | 8867.42 | 27-FEB-04:52 | -36.1 |
March | 0.101302E+10 | 8153.13 | 06-MAR-05:11 | -20.4 |
April | 0.119187E+09 | 7537.80 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 24607410.71 | 5764.73 | 30-SEP-05:01 | -4.5 |
October | 0.836402E+09 | 8107.83 | 30-OCT-04:01 | -14.4 |
November | 0.371376E+10 | 8457.11 | 13-NOV-05:11 | -19.8 |
December | 0.482726E+10 | 8578.95 | 04-DEC-01:32 | -21.3 |
Annual Sum or Average | 0.179154E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.482726E+10 | 8867.42 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609529E+10 | 13229.41 | 30-JAN-04:22 | -25.3 |
February | 0.292652E+10 | 13154.84 | 27-FEB-04:52 | -36.1 |
March | 0.116407E+10 | 12209.78 | 06-MAR-05:11 | -20.4 |
April | 0.144702E+09 | 10158.86 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 29088461.50 | 8427.05 | 28-SEP-06:01 | -2.8 |
October | 0.909267E+09 | 12154.58 | 30-OCT-04:01 | -14.4 |
November | 0.430703E+10 | 12676.11 | 13-NOV-05:11 | -19.8 |
December | 0.670150E+10 | 12861.96 | 04-DEC-01:32 | -21.3 |
Annual Sum or Average | 0.222775E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.670150E+10 | 13229.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470409E+10 | 8784.59 | 30-JAN-03:02 | -25.0 |
February | 0.290456E+10 | 8792.85 | 27-FEB-04:52 | -36.1 |
March | 0.137437E+10 | 8108.11 | 06-MAR-05:11 | -20.4 |
April | 0.141672E+09 | 7105.45 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 28806658.79 | 5805.66 | 30-SEP-05:01 | -4.5 |
October | 0.951504E+09 | 8052.66 | 30-OCT-04:01 | -14.4 |
November | 0.361319E+10 | 8389.56 | 13-NOV-05:11 | -19.8 |
December | 0.474417E+10 | 8509.53 | 04-DEC-01:32 | -21.3 |
Annual Sum or Average | 0.184624E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.474417E+10 | 8792.85 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120484E+10 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.902672E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.828756E+09 | 1358.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.635321E+09 | 774.31 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.666552E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.652429E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.616368E+09 | 711.15 | 17-JUL-12:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.708646E+09 | 711.15 | 15-AUG-14:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.699316E+09 | 1358.45 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.888032E+09 | 1358.45 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.112352E+10 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.121421E+10 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.101407E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.616368E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.121421E+10 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.734172E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.545840E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.514169E+09 | 860.01 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.402835E+09 | 450.21 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.429814E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.419449E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.396026E+09 | 410.22 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.452939E+09 | 450.21 | 18-AUG-14:50 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437171E+09 | 750.07 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.540244E+09 | 860.01 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.675871E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.759690E+09 | 860.01 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.630822E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.396026E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.759690E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111183E+10 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.819717E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.796151E+09 | 1358.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.639029E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.675247E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.660533E+09 | 647.98 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.623273E+09 | 647.98 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.711966E+09 | 711.15 | 18-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682424E+09 | 1358.45 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.825601E+09 | 1358.45 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.100478E+10 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.116799E+10 | 1358.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.971853E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.623273E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.116799E+10 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.742669E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.538337E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.512667E+09 | 859.95 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.405826E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.420853E+09 | 410.20 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.412820E+09 | 450.19 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.389563E+09 | 450.19 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.446609E+09 | 450.19 | 03-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436904E+09 | 859.95 | 28-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.537243E+09 | 859.95 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.677073E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.765141E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.628571E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.389563E+09 | 410.20 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.765141E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120110E+10 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.896321E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.825805E+09 | 1358.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.634333E+09 | 774.31 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.666115E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.652029E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.615866E+09 | 711.15 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.708058E+09 | 711.15 | 15-AUG-14:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.696116E+09 | 1358.45 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.881215E+09 | 1358.45 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.111683E+10 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.121254E+10 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.101063E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.615866E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.121254E+10 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.731430E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.543730E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.512946E+09 | 860.01 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.402220E+09 | 450.21 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.429356E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.418983E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.395616E+09 | 410.22 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.452408E+09 | 450.21 | 18-AUG-14:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436259E+09 | 750.07 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.538226E+09 | 860.01 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.671990E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.758605E+09 | 860.01 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.629177E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.395616E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.758605E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.110774E+10 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.814686E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.794399E+09 | 1358.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.637832E+09 | 774.31 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.674509E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.660080E+09 | 647.98 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.622783E+09 | 647.98 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.710924E+09 | 647.98 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.681103E+09 | 1358.45 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.822890E+09 | 1358.45 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.100030E+10 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.116267E+10 | 1358.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.968992E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.622783E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.116267E+10 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.739627E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.534496E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.510949E+09 | 859.95 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.405028E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.420547E+09 | 410.20 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.412616E+09 | 450.19 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.389131E+09 | 450.19 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.446097E+09 | 450.19 | 03-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.435248E+09 | 859.95 | 28-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.535111E+09 | 859.95 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.674454E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.763503E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.626681E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.389131E+09 | 410.20 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.763503E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120484E+10 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.902672E+09 | 1358.45 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.828718E+09 | 1358.45 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.635321E+09 | 774.31 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.666539E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.652429E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.616368E+09 | 711.15 | 17-JUL-12:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.708622E+09 | 711.15 | 15-AUG-14:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.699316E+09 | 1358.45 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.888032E+09 | 1358.45 | 02-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.112352E+10 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.121421E+10 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.101406E+11 | 0.243325E+11 | ||||
Minimum of Months | 0.616368E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.121421E+10 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.734172E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.545840E+09 | 860.01 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.514169E+09 | 860.01 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.402835E+09 | 450.21 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.429814E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.419449E+09 | 410.22 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.396026E+09 | 410.22 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.452939E+09 | 450.21 | 18-AUG-14:50 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.437171E+09 | 750.07 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.540244E+09 | 860.01 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.675871E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.759690E+09 | 860.01 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.630822E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.396026E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.759690E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.111179E+10 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.819717E+09 | 1358.45 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.796151E+09 | 1358.45 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.639029E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.675243E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.660533E+09 | 647.98 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.623271E+09 | 647.98 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.711966E+09 | 711.15 | 18-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.682424E+09 | 1358.45 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.825601E+09 | 1358.45 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.100478E+10 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.116799E+10 | 1358.45 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.971849E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.623271E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.116799E+10 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.742669E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.538337E+09 | 859.95 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.512667E+09 | 859.95 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.405826E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.420853E+09 | 410.20 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.412820E+09 | 450.19 | 27-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.389563E+09 | 450.19 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.446602E+09 | 450.19 | 03-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.436904E+09 | 859.95 | 28-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.537243E+09 | 859.95 | 02-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.677073E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.765141E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.628570E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.389563E+09 | 410.20 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.765141E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.120484E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424245E+09 |
February | 0.901968E+09 | 0.902672E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340851E+09 |
March | 0.107774E+10 | 0.828756E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501960E+09 |
April | 0.956342E+09 | 0.635321E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564158E+09 |
May | 0.103597E+10 | 0.666552E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348956E+09 |
June | 0.103308E+10 | 0.652429E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453548.90 | 0.211471E+09 |
July | 0.959235E+09 | 0.616368E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1439778.45 | 0.156765E+09 |
August | 0.107774E+10 | 0.708646E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206565.66 | 0.180407E+09 |
September | 0.956342E+09 | 0.699316E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203690E+09 |
October | 0.994195E+09 | 0.888032E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429911E+09 |
November | 0.984487E+09 | 0.112352E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155823E+09 |
December | 0.959235E+09 | 0.121421E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307533E+09 |
Annual Sum or Average | 0.119305E+11 | 0.101407E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2099893.01 | 0.382577E+10 |
Minimum of Months | 0.901968E+09 | 0.616368E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155823E+09 |
Maximum of Months | 0.107774E+10 | 0.121421E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1439778.45 | 0.564158E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.734172E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283009E+09 |
February | 0.571020E+09 | 0.545840E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227426E+09 |
March | 0.682301E+09 | 0.514169E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338119E+09 |
April | 0.605444E+09 | 0.402835E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385963E+09 |
May | 0.655854E+09 | 0.429814E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236931E+09 |
June | 0.654023E+09 | 0.419449E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302401.15 | 0.140244E+09 |
July | 0.607275E+09 | 0.396026E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1032959.67 | 0.104701E+09 |
August | 0.682301E+09 | 0.452939E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139433.77 | 0.121193E+09 |
September | 0.605444E+09 | 0.437171E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139350E+09 |
October | 0.629407E+09 | 0.540244E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288363E+09 |
November | 0.623262E+09 | 0.675871E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103853E+09 |
December | 0.607275E+09 | 0.759690E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205065E+09 |
Annual Sum or Average | 0.755301E+10 | 0.630822E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1474794.60 | 0.257422E+10 |
Minimum of Months | 0.571020E+09 | 0.396026E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103853E+09 |
Maximum of Months | 0.682301E+09 | 0.759690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1032959.67 | 0.385963E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.111183E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425238E+09 |
February | 0.901968E+09 | 0.819717E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343903E+09 |
March | 0.107774E+10 | 0.796151E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519308E+09 |
April | 0.956342E+09 | 0.639029E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603482E+09 |
May | 0.103597E+10 | 0.675247E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358158E+09 |
June | 0.103308E+10 | 0.660533E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453535.20 | 0.210364E+09 |
July | 0.959235E+09 | 0.623273E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401294.50 | 0.157826E+09 |
August | 0.107774E+10 | 0.711966E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206264.53 | 0.186104E+09 |
September | 0.956342E+09 | 0.682424E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214520E+09 |
October | 0.994195E+09 | 0.825601E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440969E+09 |
November | 0.984487E+09 | 0.100478E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156282E+09 |
December | 0.959235E+09 | 0.116799E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307965E+09 |
Annual Sum or Average | 0.119305E+11 | 0.971853E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2061094.23 | 0.392412E+10 |
Minimum of Months | 0.901968E+09 | 0.623273E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156282E+09 |
Maximum of Months | 0.107774E+10 | 0.116799E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401294.50 | 0.603482E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.742669E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283007E+09 |
February | 0.570983E+09 | 0.538337E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227365E+09 |
March | 0.682256E+09 | 0.512667E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337231E+09 |
April | 0.605404E+09 | 0.405826E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395515E+09 |
May | 0.655811E+09 | 0.420853E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239169E+09 |
June | 0.653980E+09 | 0.412820E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302374.71 | 0.141862E+09 |
July | 0.607235E+09 | 0.389563E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 826017.10 | 0.105948E+09 |
August | 0.682256E+09 | 0.446609E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137715.01 | 0.122293E+09 |
September | 0.605404E+09 | 0.436904E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137966E+09 |
October | 0.629366E+09 | 0.537243E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287170E+09 |
November | 0.623221E+09 | 0.677073E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103889E+09 |
December | 0.607235E+09 | 0.765141E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205063E+09 |
Annual Sum or Average | 0.755252E+10 | 0.628571E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1266106.82 | 0.258648E+10 |
Minimum of Months | 0.570983E+09 | 0.389563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103889E+09 |
Maximum of Months | 0.682256E+09 | 0.765141E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 826017.10 | 0.395515E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.120110E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227173E+09 |
February | 0.901968E+09 | 0.896321E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182163E+09 |
March | 0.107774E+10 | 0.825805E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270836E+09 |
April | 0.956342E+09 | 0.634333E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301692E+09 |
May | 0.103597E+10 | 0.666115E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182410E+09 |
June | 0.103308E+10 | 0.652029E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249892.81 | 0.110715E+09 |
July | 0.959235E+09 | 0.615866E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 878200.88 | 82399308.92 |
August | 0.107774E+10 | 0.708058E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117027.25 | 98884401.10 |
September | 0.956342E+09 | 0.696116E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115922E+09 |
October | 0.994195E+09 | 0.881215E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243640E+09 |
November | 0.984487E+09 | 0.111683E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85060739.55 |
December | 0.959235E+09 | 0.121254E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165811E+09 |
Annual Sum or Average | 0.119305E+11 | 0.101063E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1245120.94 | 0.206671E+10 |
Minimum of Months | 0.901968E+09 | 0.615866E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82399308.92 |
Maximum of Months | 0.107774E+10 | 0.121254E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 878200.88 | 0.301692E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.731430E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151473E+09 |
February | 0.571020E+09 | 0.543730E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121658E+09 |
March | 0.682301E+09 | 0.512946E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183577E+09 |
April | 0.605444E+09 | 0.402220E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212089E+09 |
May | 0.655854E+09 | 0.429356E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130457E+09 |
June | 0.654023E+09 | 0.418983E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166596.58 | 76223946.84 |
July | 0.607275E+09 | 0.395616E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519579.27 | 57634151.09 |
August | 0.682301E+09 | 0.452408E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77966.51 | 68481684.21 |
September | 0.605444E+09 | 0.436259E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81073148.89 |
October | 0.629407E+09 | 0.538226E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164834E+09 |
November | 0.623262E+09 | 0.671990E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56570305.22 |
December | 0.607275E+09 | 0.758605E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110342E+09 |
Annual Sum or Average | 0.755301E+10 | 0.629177E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 764142.35 | 0.141441E+10 |
Minimum of Months | 0.571020E+09 | 0.395616E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56570305.22 |
Maximum of Months | 0.682301E+09 | 0.758605E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 519579.27 | 0.212089E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.110774E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100277E+11 |
February | 0.901968E+09 | 0.814686E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793695E+10 |
March | 0.107774E+10 | 0.794399E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884664E+10 |
April | 0.956342E+09 | 0.637832E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506050E+10 |
May | 0.103597E+10 | 0.674509E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305694E+10 |
June | 0.103308E+10 | 0.660080E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28762878.97 | 0.177856E+10 |
July | 0.959235E+09 | 0.622783E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42400581.77 | 0.134871E+10 |
August | 0.107774E+10 | 0.710924E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9956873.10 | 0.248463E+10 |
September | 0.956342E+09 | 0.681103E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379597E+10 |
October | 0.994195E+09 | 0.822890E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638735E+10 |
November | 0.984487E+09 | 0.100030E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988570E+10 |
December | 0.959235E+09 | 0.116267E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101668E+11 |
Annual Sum or Average | 0.119305E+11 | 0.968992E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81120333.84 | 0.707764E+11 |
Minimum of Months | 0.901968E+09 | 0.622783E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134871E+10 |
Maximum of Months | 0.107774E+10 | 0.116267E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42400581.77 | 0.101668E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.739627E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151465E+09 |
February | 0.570983E+09 | 0.534496E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121507E+09 |
March | 0.682256E+09 | 0.510949E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182129E+09 |
April | 0.605404E+09 | 0.405028E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216410E+09 |
May | 0.655811E+09 | 0.420547E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128517E+09 |
June | 0.653980E+09 | 0.412616E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166599.99 | 76397162.39 |
July | 0.607235E+09 | 0.389131E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468930.22 | 57094853.60 |
August | 0.682256E+09 | 0.446097E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77968.80 | 68453279.73 |
September | 0.605404E+09 | 0.435248E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79411465.22 |
October | 0.629366E+09 | 0.535111E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163001E+09 |
November | 0.623221E+09 | 0.674454E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56611877.77 |
December | 0.607235E+09 | 0.763503E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110341E+09 |
Annual Sum or Average | 0.755252E+10 | 0.626681E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 713499.01 | 0.141134E+10 |
Minimum of Months | 0.570983E+09 | 0.389131E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56611877.77 |
Maximum of Months | 0.682256E+09 | 0.763503E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468930.22 | 0.216410E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.120484E+10 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356913E+09 |
February | 0.901968E+09 | 0.902672E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287862E+09 |
March | 0.107774E+10 | 0.828718E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431249E+09 |
April | 0.956342E+09 | 0.635321E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493472E+09 |
May | 0.103597E+10 | 0.666539E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302914E+09 |
June | 0.103308E+10 | 0.652429E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 384376.65 | 0.181219E+09 |
July | 0.959235E+09 | 0.616368E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253461.84 | 0.133672E+09 |
August | 0.107774E+10 | 0.708622E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177485.75 | 0.156724E+09 |
September | 0.956342E+09 | 0.699316E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181550E+09 |
October | 0.994195E+09 | 0.888032E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375836E+09 |
November | 0.984487E+09 | 0.112352E+10 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132028E+09 |
December | 0.959235E+09 | 0.121421E+10 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259393E+09 |
Annual Sum or Average | 0.119305E+11 | 0.101406E+11 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1815324.24 | 0.329283E+10 |
Minimum of Months | 0.901968E+09 | 0.616368E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132028E+09 |
Maximum of Months | 0.107774E+10 | 0.121421E+10 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253461.84 | 0.493472E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.734172E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237788E+09 |
February | 0.421807E+09 | 0.545840E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191994E+09 |
March | 0.502994E+09 | 0.514169E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290862E+09 |
April | 0.447140E+09 | 0.402835E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336447E+09 |
May | 0.484071E+09 | 0.429814E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204415E+09 |
June | 0.482240E+09 | 0.419449E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256287.07 | 0.119948E+09 |
July | 0.448971E+09 | 0.396026E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898697.55 | 89091957.44 |
August | 0.502994E+09 | 0.452939E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119728.09 | 0.104749E+09 |
September | 0.447140E+09 | 0.437171E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123128E+09 |
October | 0.465148E+09 | 0.540244E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252260E+09 |
November | 0.460569E+09 | 0.675871E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87837255.83 |
December | 0.448971E+09 | 0.759690E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172645E+09 |
Annual Sum or Average | 0.557719E+10 | 0.630822E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1274712.70 | 0.221117E+10 |
Minimum of Months | 0.421807E+09 | 0.396026E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87837255.83 |
Maximum of Months | 0.502994E+09 | 0.759690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898697.55 | 0.336447E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.111179E+10 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357726E+09 |
February | 0.901968E+09 | 0.819717E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291653E+09 |
March | 0.107774E+10 | 0.796151E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447728E+09 |
April | 0.956342E+09 | 0.639029E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525230E+09 |
May | 0.103597E+10 | 0.675243E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309885E+09 |
June | 0.103308E+10 | 0.660533E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 384362.91 | 0.180628E+09 |
July | 0.959235E+09 | 0.623271E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204465.77 | 0.134897E+09 |
August | 0.107774E+10 | 0.711966E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177136.21 | 0.161233E+09 |
September | 0.956342E+09 | 0.682424E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189343E+09 |
October | 0.994195E+09 | 0.825601E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387446E+09 |
November | 0.984487E+09 | 0.100478E+10 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132795E+09 |
December | 0.959235E+09 | 0.116799E+10 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259680E+09 |
Annual Sum or Average | 0.119305E+11 | 0.971849E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1765964.89 | 0.337825E+10 |
Minimum of Months | 0.901968E+09 | 0.623271E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132795E+09 |
Maximum of Months | 0.107774E+10 | 0.116799E+10 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204465.77 | 0.525230E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.742669E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237790E+09 |
February | 0.570983E+09 | 0.538337E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191832E+09 |
March | 0.682256E+09 | 0.512667E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289935E+09 |
April | 0.605404E+09 | 0.405826E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344657E+09 |
May | 0.655811E+09 | 0.420853E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207173E+09 |
June | 0.653980E+09 | 0.412820E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256258.71 | 0.121711E+09 |
July | 0.607235E+09 | 0.389563E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 698951.62 | 90514157.21 |
August | 0.682256E+09 | 0.446602E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118327.85 | 0.106301E+09 |
September | 0.605404E+09 | 0.436904E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122226E+09 |
October | 0.629366E+09 | 0.537243E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250990E+09 |
November | 0.623221E+09 | 0.677073E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87921591.61 |
December | 0.607235E+09 | 0.765141E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172654E+09 |
Annual Sum or Average | 0.755252E+10 | 0.628570E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1073538.18 | 0.222370E+10 |
Minimum of Months | 0.570983E+09 | 0.389563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87921591.61 |
Maximum of Months | 0.682256E+09 | 0.765141E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 698951.62 | 0.344657E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468197E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381637E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585405E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681476E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407356E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247662.75 | 0.238661E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969264.99 | 0.176777E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52140.31 | 0.213515E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252678E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521387E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177760E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341969E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269068.05 | 0.444682E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176777E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969264.99 | 0.681476E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593176E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483943E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737756E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853975E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516327E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315307.59 | 0.303221E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347452.20 | 0.224111E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69545.90 | 0.268585E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310619E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638268E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222687E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432638E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1732305.69 | 0.558531E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222687E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347452.20 | 0.853975E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625365E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507983E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763931E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882826E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542785E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218541.73 | 0.325437E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 989237.80 | 0.243043E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19593.46 | 0.281353E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314999E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649315E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231164E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454979E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1227372.98 | 0.582318E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231164E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 989237.80 | 0.882826E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1913.25 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1124.90 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 849.51 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1210.44 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 575.68 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30-JUN-15:00 | 554.01 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 17-JUL-12:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 21-JUL-16:00 | 434.09 | 04-JUL-16:53 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 15-AUG-14:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 11-AUG-16:00 | 443.36 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 344.47 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 702.27 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 604.78 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 652.23 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.47 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 1913.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1275.55 | 28-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 749.68 | 25-FEB-00:53 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 566.63 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 450.21 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 806.46 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 384.52 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 30-JUN-15:00 | 367.18 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 410.22 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 | 29-JUL-19:53 | 291.92 | 04-JUL-16:53 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 18-AUG-14:50 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 11-AUG-16:00 | 293.93 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 233.40 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.00 | 21-OCT-04:05 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.05 | 09-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 437.71 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.40 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 | 1275.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1913.28 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1126.40 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 938.25 | 12-MAR-14:55 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1334.34 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 582.29 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30-JUN-15:00 | 572.29 | 18-JUN-14:10 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 21-JUL-16:00 | 444.56 | 04-JUL-16:53 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 18-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 11-AUG-16:00 | 444.29 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 353.03 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 707.66 | 21-OCT-04:05 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 605.39 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 656.20 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.03 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 1913.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1275.47 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 749.36 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 566.77 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1003.54 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 410.20 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 384.57 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 30-JUN-15:00 | 363.29 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 21-JUL-16:00 | 296.74 | 04-JUL-16:53 |
August | 827.17 | 01-AUG-09:09 | 450.19 | 03-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 11-AUG-16:00 | 293.16 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 229.18 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.04 | 21-OCT-04:05 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.10 | 09-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 437.59 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.18 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 1275.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1015.99 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 602.25 | 25-FEB-00:57 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 451.30 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 648.57 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 312.74 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 30-JUN-15:00 | 311.60 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 21-JUL-16:00 | 215.42 | 04-JUL-16:53 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 15-AUG-14:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 11-AUG-16:00 | 252.39 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 200.57 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 391.71 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 330.56 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 346.36 | 28-DEC-02:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.57 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 1015.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 677.31 | 28-JAN-23:55 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 401.50 | 25-FEB-00:57 |
March | 827.22 | 01-MAR-10:09 | 860.01 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 301.45 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 450.21 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 439.14 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 217.12 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 30-JUN-15:00 | 209.29 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 410.22 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 21-JUL-16:00 | 145.41 | 04-JUL-16:53 |
August | 827.22 | 01-AUG-09:09 | 450.21 | 18-AUG-14:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 11-AUG-16:00 | 170.87 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 750.07 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 140.32 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 261.85 | 21-OCT-04:03 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 219.67 | 10-NOV-01:55 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 230.91 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.32 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 677.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 53459.87 | 12-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 48893.13 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 43765.54 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 37841.90 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15091.39 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.56 | 21-JUN-17:00 | 11923.25 | 01-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.78 | 21-JUL-16:10 | 11394.34 | 17-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 647.98 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.85 | 11-AUG-16:20 | 19501.50 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20789.30 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34697.46 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44381.99 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 49266.96 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11394.34 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.78 | 53459.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 677.32 | 28-JAN-23:55 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 401.50 | 25-FEB-00:57 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 301.27 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 525.62 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 410.20 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 209.32 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 30-JUN-15:00 | 206.53 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 21-JUL-16:00 | 145.85 | 04-JUL-16:53 |
August | 827.17 | 01-AUG-09:09 | 450.19 | 03-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 11-AUG-16:00 | 170.23 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 136.81 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 260.36 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 220.12 | 10-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 230.91 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.81 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 677.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1591.63 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 943.84 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 709.15 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1044.06 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 507.18 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 30-JUN-15:00 | 499.67 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 17-JUL-12:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 21-JUL-16:00 | 372.78 | 04-JUL-16:53 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 15-AUG-14:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 11-AUG-16:00 | 391.66 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 313.92 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 598.97 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 511.31 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 542.61 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.92 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 1591.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1061.12 | 28-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 628.44 | 25-FEB-00:53 |
March | 805.43 | 01-MAR-08:09 | 860.01 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 473.10 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 450.21 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 696.07 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 338.35 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 410.22 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 30-JUN-15:00 | 332.02 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 410.22 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 | 29-JUL-19:53 | 250.69 | 04-JUL-16:53 |
August | 805.43 | 01-AUG-07:10 | 450.21 | 18-AUG-14:50 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 11-AUG-16:00 | 259.52 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 750.07 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 212.24 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.60 | 21-OCT-04:03 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 339.49 | 10-NOV-01:55 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 361.75 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.24 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 46.12 | 1061.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1591.78 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 1358.45 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 950.92 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1358.45 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 806.21 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1144.85 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 512.44 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 30-JUN-15:00 | 492.46 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.28 | 29-JUL-19:53 | 381.83 | 04-JUL-16:53 |
August | 1306.65 | 01-AUG-09:09 | 711.15 | 18-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 11-AUG-16:00 | 392.37 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1358.45 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 320.91 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 618.01 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 516.08 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 542.60 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.91 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 56.28 | 1591.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1061.11 | 28-JAN-23:55 |
February | 827.17 | 01-FEB-10:09 | 859.95 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 627.23 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 859.95 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 473.12 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 858.76 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 410.20 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 338.94 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 27-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 30-JUN-15:00 | 326.44 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 21-JUL-16:00 | 254.94 | 04-JUL-16:53 |
August | 827.17 | 01-AUG-09:09 | 450.19 | 03-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 11-AUG-16:00 | 259.55 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 859.95 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 208.87 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 397.86 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.24 | 10-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 361.74 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.87 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 1061.11 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2150.69 | 28-JAN-23:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1286.69 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 915.58 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1456.97 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 691.67 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 30-JUN-15:00 | 672.14 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 | 21-JUL-16:00 | 465.15 | 04-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 11-AUG-16:00 | 538.72 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 418.83 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 849.85 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 707.20 | 10-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.09 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.83 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 | 2150.69 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2704.08 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1646.27 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1157.73 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1823.96 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 879.47 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 30-JUN-15:00 | 833.31 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.38 | 29-JUL-17:03 | 582.29 | 04-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 | 11-AUG-16:00 | 679.68 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 498.96 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1047.24 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 892.14 | 10-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 935.92 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.38 | 2704.08 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2801.43 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1717.37 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1254.94 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1997.41 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 865.84 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 30-JUN-15:00 | 840.78 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 | 21-JUL-16:00 | 675.61 | 04-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 | 11-AUG-16:00 | 661.95 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 537.73 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1048.06 | 21-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 906.55 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 971.97 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 | 2801.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7374.33 | 27-JAN-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7923.00 | 16-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11644.20 | 23-MAR-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40265.29 | 24-APR-05:02 | 3176.32 | 1058.67 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39603.58 | 13-MAY-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40918.22 | 24-JUN-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41746.12 | 17-JUL-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41667.14 | 01-AUG-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40988.90 | 18-SEP-05:02 | 3176.32 | 1058.67 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15878.55 | 05-OCT-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7873.97 | 03-NOV-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7046.92 | 22-DEC-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7046.92 | 2541.06 | 1058.67 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41746.12 | 6035.01 | 6443.98 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.39 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.30 |
March | 991.89 | 22-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4360.38 | 21-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 |
May | 7366.88 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 |
June | 8338.50 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 0.00 |
July | 8433.90 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 0.00 |
August | 7242.55 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 |
September | 3000.68 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
October | 897.54 | 03-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.68 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8433.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 | 555.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3644.32 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.18 |
February | 3589.69 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.52 |
March | 3928.21 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.51 |
April | 2980.66 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.86 |
May | 3914.93 | 31-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 |
June | 4709.44 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.00 |
July | 5672.73 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 |
August | 4267.43 | 11-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 0.00 |
September | 2184.56 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.02 |
October | 2708.44 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.04 |
November | 3410.75 | 09-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3966.27 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2184.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5672.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 947.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4560.10 | 11-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4653.74 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.61 |
March | 4942.66 | 31-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3858.87 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 |
May | 4508.58 | 11-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5509.63 | 23-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
July | 6487.03 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 |
August | 5451.68 | 28-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 |
September | 3303.60 | 11-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 |
October | 3156.90 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.56 |
November | 3673.92 | 30-NOV-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3770.26 | 15-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3156.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6487.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5785.40 | 20-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6544.83 | 09-FEB-15:10 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7218.30 | 22-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13533.08 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17577.57 | 15-MAY-06:02 | 7623.17 | 12888.13 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32258.14 | 23-JUN-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31852.92 | 24-JUL-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30816.24 | 01-AUG-06:01 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13511.69 | 01-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7789.26 | 05-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6036.09 | 02-NOV-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5567.50 | 21-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5567.50 | 3176.32 | 3579.89 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32258.14 | 8893.70 | 15036.15 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5212.66 | 20-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6257.26 | 09-FEB-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7157.48 | 22-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13202.07 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17526.44 | 31-MAY-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20893.42 | 21-JUN-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29621.21 | 24-JUL-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17602.06 | 11-AUG-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12382.93 | 01-SEP-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7376.71 | 03-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5395.32 | 08-NOV-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4994.80 | 30-DEC-17:02 | 1905.79 | 2147.94 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4994.80 | 1905.79 | 2147.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29621.21 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1021.80 | 07-JAN-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 |
February | 1020.73 | 11-FEB-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 |
March | 1321.45 | 22-MAR-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2534.34 | 28-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 |
May | 9427.08 | 31-MAY-06:02 | 1339.19 | 1079.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.69 |
June | 10641.71 | 13-JUN-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 |
July | 10704.05 | 07-JUL-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 |
August | 5074.88 | 02-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
September | 2464.32 | 01-SEP-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 |
October | 1368.78 | 04-OCT-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 |
November | 1016.46 | 18-NOV-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1017.55 | 23-DEC-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1016.46 | 267.84 | 301.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10704.05 | 1339.19 | 1079.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1099.24 | 07-JAN-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.73 |
February | 1122.51 | 09-FEB-11:30 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 |
March | 2454.25 | 31-MAR-09:55 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 |
April | 6607.37 | 22-APR-09:15 | 522.45 | 273.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 |
May | 17091.58 | 21-MAY-09:51 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.20 |
June | 13733.77 | 13-JUN-05:12 | 423.91 | 227.90 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
July | 16314.59 | 23-JUL-10:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.02 |
August | 11801.95 | 10-AUG-06:02 | 1017.38 | 820.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 |
September | 9217.03 | 10-SEP-10:13 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.03 |
October | 2178.96 | 03-OCT-09:55 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.05 |
November | 1094.55 | 18-NOV-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1093.47 | 23-DEC-17:02 | 211.95 | 238.89 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1093.47 | 169.56 | 91.16 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17091.58 | 1654.44 | 820.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2053.37 | 25-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 |
February | 4861.05 | 15-FEB-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9700.13 | 31-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.99 |
April | 19111.02 | 23-APR-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.00 |
May | 26872.70 | 21-MAY-13:11 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.52 |
June | 18648.45 | 04-JUN-14:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.68 |
July | 25954.28 | 23-JUL-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 |
August | 24722.25 | 27-AUG-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.49 |
September | 24157.95 | 10-SEP-11:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.60 |
October | 10473.47 | 03-OCT-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
November | 2846.91 | 08-NOV-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
December | 1719.13 | 23-DEC-17:02 | 334.80 | 377.34 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1719.13 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26872.70 | 1306.65 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1135.81 | 07-JAN-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 |
February | 1140.19 | 18-FEB-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 |
March | 1796.97 | 31-MAR-17:00 | 254.33 | 227.89 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.09 |
April | 10227.44 | 22-APR-19:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.96 |
May | 16851.97 | 21-MAY-17:52 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.30 |
June | 15552.75 | 10-JUN-17:04 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.95 |
July | 11168.59 | 09-JUL-20:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.59 |
August | 13091.81 | 27-AUG-17:02 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.88 |
September | 4959.98 | 08-SEP-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 |
October | 1744.21 | 03-OCT-15:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 |
November | 1135.65 | 18-NOV-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1129.93 | 23-DEC-17:02 | 211.94 | 238.87 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1129.93 | 0.00 | 91.15 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16851.97 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1007.49 | 07-JAN-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 |
February | 1000.88 | 11-FEB-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 |
March | 1089.64 | 22-MAR-14:10 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1536.90 | 28-APR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 |
May | 4004.21 | 31-MAY-06:02 | 1339.19 | 1079.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
June | 8602.64 | 07-JUN-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 |
July | 8992.31 | 11-JUL-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 |
August | 7521.38 | 02-AUG-06:02 | 1607.03 | 1295.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
September | 1999.47 | 01-SEP-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 |
October | 1394.22 | 04-OCT-15:10 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
November | 1013.99 | 04-NOV-16:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1005.46 | 30-DEC-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1000.88 | 267.84 | 301.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8992.31 | 1607.03 | 1295.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 901.91 | 07-JAN-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 |
February | 898.76 | 18-FEB-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
March | 1910.44 | 31-MAR-09:20 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
April | 4467.45 | 22-APR-08:30 | 254.35 | 136.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
May | 12744.26 | 14-MAY-09:11 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.86 |
June | 11055.55 | 07-JUN-05:12 | 423.91 | 227.90 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
July | 12863.39 | 23-JUL-10:22 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
August | 10184.53 | 11-AUG-06:02 | 1017.38 | 820.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
September | 7041.10 | 10-SEP-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 |
October | 2577.47 | 03-OCT-09:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 |
November | 907.86 | 04-NOV-16:02 | 211.95 | 238.89 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 899.98 | 30-DEC-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 898.76 | 169.56 | 91.16 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12863.39 | 1654.44 | 820.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1410.48 | 28-JAN-17:01 | 468.72 | 528.27 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.74 |
February | 1860.74 | 18-FEB-13:30 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 |
March | 2198.52 | 11-MAR-13:40 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 |
April | 14399.44 | 23-APR-14:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.36 |
May | 17224.94 | 14-MAY-12:31 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 |
June | 11588.25 | 04-JUN-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 |
July | 20182.94 | 23-JUL-13:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
August | 21885.80 | 27-AUG-13:31 | 535.68 | 287.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.16 |
September | 10196.07 | 09-SEP-14:00 | 137.54 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.85 |
October | 6831.91 | 03-OCT-13:40 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.88 |
November | 1513.74 | 08-NOV-13:16 | 6361.16 | 3239.90 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4151.05 |
December | 1403.17 | 30-DEC-17:02 | 401.76 | 452.80 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1403.17 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | |
Maximum of Months | 21885.80 | 6361.16 | 3239.90 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4151.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.81 | 07-JAN-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 |
February | 950.16 | 18-FEB-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.93 |
March | 1349.47 | 31-MAR-17:00 | 254.33 | 227.89 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.46 |
April | 7513.83 | 22-APR-19:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.41 |
May | 7471.70 | 14-MAY-19:22 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.12 |
June | 10278.34 | 11-JUN-17:11 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 |
July | 9245.95 | 09-JUL-19:53 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 |
August | 13710.72 | 27-AUG-18:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.84 |
September | 3800.84 | 08-SEP-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
October | 1473.17 | 03-OCT-15:20 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
November | 957.97 | 18-NOV-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 948.65 | 30-DEC-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 948.65 | 0.00 | 91.15 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13710.72 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1004.64 | 07-JAN-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.64 |
February | 1008.31 | 11-FEB-17:03 | 267.84 | 301.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 |
March | 1329.27 | 22-MAR-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2789.14 | 28-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 |
May | 9078.17 | 31-MAY-06:02 | 1339.19 | 1079.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
June | 10310.38 | 13-JUN-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 |
July | 10384.01 | 11-JUL-05:12 | 669.60 | 359.98 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
August | 8804.95 | 10-AUG-06:02 | 1607.03 | 1295.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 |
September | 2895.38 | 01-SEP-13:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
October | 1449.02 | 04-OCT-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 |
November | 1001.89 | 18-NOV-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1000.73 | 23-DEC-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1000.73 | 267.84 | 301.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10384.01 | 1607.03 | 1295.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1110.92 | 07-JAN-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 |
February | 1290.50 | 15-FEB-11:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 |
March | 3524.99 | 31-MAR-10:05 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 |
April | 9896.27 | 23-APR-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.40 |
May | 16057.90 | 21-MAY-08:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.98 |
June | 13753.09 | 07-JUN-05:12 | 423.91 | 227.90 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 |
July | 16277.60 | 23-JUL-09:42 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.13 |
August | 13040.35 | 27-AUG-10:12 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 |
September | 11418.18 | 10-SEP-10:23 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 |
October | 3084.71 | 03-OCT-10:05 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 |
November | 1109.11 | 18-NOV-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1105.71 | 30-DEC-17:02 | 254.35 | 286.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1105.71 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16277.60 | 1610.86 | 820.45 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2219.47 | 25-JAN-13:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 |
February | 5804.82 | 15-FEB-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10775.70 | 31-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 |
April | 18313.75 | 09-APR-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 |
May | 23484.79 | 28-MAY-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.72 |
June | 19100.96 | 04-JUN-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.23 |
July | 24665.23 | 23-JUL-13:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
August | 26753.56 | 27-AUG-13:31 | 535.68 | 287.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 |
September | 13715.37 | 10-SEP-11:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.85 |
October | 11224.36 | 03-OCT-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.98 |
November | 3602.68 | 08-NOV-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 |
December | 1664.70 | 30-DEC-17:02 | 401.76 | 452.80 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1664.70 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26753.56 | 1306.65 | 647.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1099.10 | 07-JAN-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.96 |
February | 1184.09 | 15-FEB-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
March | 1889.78 | 31-MAR-16:50 | 254.33 | 227.89 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.09 |
April | 10929.60 | 22-APR-19:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.09 |
May | 15665.71 | 28-MAY-18:12 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
June | 14801.31 | 10-JUN-17:04 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 |
July | 11135.93 | 30-JUL-19:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 |
August | 16256.13 | 27-AUG-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.89 |
September | 8561.85 | 02-SEP-17:42 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 |
October | 1767.75 | 03-OCT-15:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 |
November | 1101.12 | 18-NOV-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1094.53 | 30-DEC-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1094.53 | 0.00 | 91.15 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16256.13 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.119164E+12 | 99093.88 | 02-JAN-08:09 | 0.238802E+12 | 397243.56 | 12-JAN-07:30 |
February | 0.103280E+12 | 98454.71 | 27-FEB-08:09 | 0.160932E+12 | 391247.98 | 27-FEB-07:19 |
March | 0.113607E+12 | 94494.68 | 01-MAR-08:09 | 0.944100E+11 | 359358.24 | 01-MAR-07:19 |
April | 0.101165E+12 | 89054.61 | 21-APR-15:39 | 0.188337E+11 | 185545.82 | 03-APR-06:10 |
May | 0.110989E+12 | 121205.01 | 31-MAY-15:30 | 0.148252E+10 | 30839.07 | 30-MAY-06:19 |
June | 0.124767E+12 | 147996.69 | 30-JUN-14:30 | 0.295520E+09 | 18218.54 | 07-JUN-06:19 |
July | 0.127039E+12 | 148464.34 | 11-JUL-15:39 | 0.244044E+09 | 25448.13 | 05-JUL-06:19 |
August | 0.122378E+12 | 143514.24 | 11-AUG-15:50 | 0.735233E+09 | 44674.99 | 31-AUG-06:10 |
September | 0.101274E+12 | 90794.43 | 07-SEP-15:00 | 0.866782E+10 | 114753.70 | 25-SEP-06:10 |
October | 0.108830E+12 | 93514.44 | 30-OCT-07:19 | 0.626150E+11 | 210663.58 | 30-OCT-05:10 |
November | 0.113578E+12 | 98044.22 | 27-NOV-08:09 | 0.197192E+12 | 358788.73 | 27-NOV-07:19 |
December | 0.118578E+12 | 97947.62 | 04-DEC-08:09 | 0.256976E+12 | 377826.30 | 15-DEC-07:19 |
Annual Sum or Average | 0.136465E+13 | 0.104119E+13 | ||||
Minimum of Months | 0.101165E+12 | 89054.61 | 0.244044E+09 | 18218.54 | ||
Maximum of Months | 0.127039E+12 | 148464.34 | 0.256976E+12 | 397243.56 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.293606E+11 | 0.882650E+10 | 0.605851E+11 | 0.225916E+10 | 0.733925E+10 | 0.134123E+10 | 0.00 | 4552796.72 | 0.00 | 0.00 | 0.351878E+10 | 0.592835E+10 | 0.00 |
February | 0.247266E+11 | 0.607552E+10 | 0.548702E+11 | 0.204982E+10 | 0.603039E+10 | 0.915581E+09 | 0.00 | 5541204.80 | 0.00 | 0.00 | 0.322473E+10 | 0.538201E+10 | 0.00 |
March | 0.273900E+11 | 0.473450E+10 | 0.627783E+11 | 0.235669E+10 | 0.563786E+10 | 0.550012E+09 | 0.00 | 17411026.73 | 0.00 | 0.00 | 0.379540E+10 | 0.634701E+10 | 0.00 |
April | 0.235661E+11 | 0.291276E+10 | 0.586172E+11 | 0.219296E+10 | 0.609229E+10 | 0.116489E+09 | 0.00 | 31099622.88 | 0.00 | 0.00 | 0.191801E+10 | 0.571816E+10 | 0.00 |
May | 0.252935E+11 | 0.175545E+10 | 0.616817E+11 | 0.230685E+10 | 0.104933E+11 | 24029746.28 | 0.00 | 0.314605E+10 | 0.00 | 0.00 | 0.210235E+09 | 0.607761E+10 | 0.00 |
June | 0.250784E+11 | 0.925713E+09 | 0.604966E+11 | 0.226899E+10 | 0.151830E+11 | 14399107.22 | 0.00 | 0.147970E+11 | 0.00 | 0.00 | 0.180785E+09 | 0.582228E+10 | 0.00 |
July | 0.234684E+11 | 0.131570E+10 | 0.597911E+11 | 0.222981E+10 | 0.147784E+11 | 13786131.04 | 0.00 | 0.198465E+11 | 0.00 | 0.00 | 0.285880E+09 | 0.530911E+10 | 0.00 |
August | 0.264000E+11 | 0.241310E+10 | 0.627783E+11 | 0.235593E+10 | 0.120772E+11 | 17627841.23 | 0.00 | 0.104986E+11 | 0.00 | 0.00 | 0.123183E+09 | 0.571437E+10 | 0.00 |
September | 0.240811E+11 | 0.381882E+10 | 0.585950E+11 | 0.219222E+10 | 0.576540E+10 | 57968630.05 | 0.00 | 0.196564E+09 | 0.00 | 0.00 | 0.142311E+10 | 0.514424E+10 | 0.00 |
October | 0.263537E+11 | 0.580314E+10 | 0.605962E+11 | 0.225961E+10 | 0.493398E+10 | 0.361840E+09 | 0.00 | 17412247.67 | 0.00 | 0.00 | 0.308533E+10 | 0.541893E+10 | 0.00 |
November | 0.282213E+11 | 0.774574E+10 | 0.591197E+11 | 0.220174E+10 | 0.624153E+10 | 0.111517E+10 | 0.00 | 4672975.65 | 0.00 | 0.00 | 0.341096E+10 | 0.551748E+10 | 0.00 |
December | 0.291062E+11 | 0.969307E+10 | 0.597800E+11 | 0.223053E+10 | 0.719257E+10 | 0.140650E+10 | 0.00 | 3437429.51 | 0.00 | 0.00 | 0.347957E+10 | 0.568630E+10 | 0.00 |
Annual Sum or Average | 0.313046E+12 | 0.560200E+11 | 0.719689E+12 | 0.269043E+11 | 0.101765E+12 | 0.593464E+10 | 0.00 | 0.485688E+11 | 0.00 | 0.00 | 0.246560E+11 | 0.680658E+11 | 0.00 |
Minimum of Months | 0.234684E+11 | 0.925713E+09 | 0.548702E+11 | 0.204982E+10 | 0.493398E+10 | 13786131.04 | 0.00 | 3437429.51 | 0.00 | 0.00 | 0.123183E+09 | 0.514424E+10 | 0.00 |
Maximum of Months | 0.293606E+11 | 0.969307E+10 | 0.627783E+11 | 0.235669E+10 | 0.151830E+11 | 0.140650E+10 | 0.00 | 0.198465E+11 | 0.00 | 0.00 | 0.379540E+10 | 0.634701E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.238802E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.160932E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.944100E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.188337E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.148252E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.295520E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.244044E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.735233E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.866782E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.626150E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.197192E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256976E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104119E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.244044E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256976E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 19-JAN-12:20 | 9569.12 | 02-JAN-06:19 | 1328.23 | 12-JAN-07:30 | 0.00 | 01-JAN-00:10 |
February | 32642.50 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:20 | 9569.12 | 21-FEB-07:10 | 1287.84 | 27-FEB-08:00 | 0.00 | 01-FEB-00:10 |
March | 32642.50 | 01-MAR-08:09 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:20 | 8773.90 | 06-MAR-07:10 | 1196.83 | 01-MAR-07:19 | 0.00 | 01-MAR-00:10 |
April | 27128.78 | 04-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-16:10 | 14087.30 | 21-APR-15:50 | 1022.80 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 25681.07 | 01-MAY-07:10 | 3328.83 | 01-MAY-21:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 22285.61 | 31-MAY-14:50 | 176.33 | 03-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 25801.04 | 27-JUN-07:10 | 3328.83 | 01-JUN-22:49 | 41699.26 | 01-JUN-07:10 | 1410.29 | 15-JUN-11:09 | 26360.12 | 20-JUN-15:30 | 155.06 | 01-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 25870.58 | 26-JUL-14:30 | 3328.83 | 11-JUL-22:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 05-JUL-16:10 | 28854.25 | 12-JUL-15:20 | 154.56 | 05-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 26116.88 | 18-AUG-15:00 | 5686.19 | 24-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 07-AUG-11:09 | 26423.77 | 11-AUG-15:50 | 298.62 | 30-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 32312.69 | 28-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:09 | 10766.65 | 08-SEP-15:30 | 603.75 | 25-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 02-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-12:09 | 8300.91 | 30-OCT-06:10 | 1045.99 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:20 | 9341.91 | 27-NOV-07:10 | 1196.64 | 28-NOV-07:40 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-13:30 | 9569.12 | 04-DEC-07:10 | 1265.12 | 15-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 25681.07 | 3328.83 | 41699.26 | 1410.29 | 8300.91 | 154.56 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 28854.25 | 1328.23 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 595.07 | 07-JAN-07:10 | 0.00 | 0.00 | 2722.67 | 02-JAN-07:30 | 7772.01 | 02-JAN-12:30 | 0.00 |
February | 813.34 | 11-FEB-07:10 | 0.00 | 0.00 | 2722.67 | 01-FEB-08:30 | 7771.45 | 27-FEB-12:20 | 0.00 |
March | 1104.51 | 18-MAR-06:10 | 0.00 | 0.00 | 2722.67 | 01-MAR-17:30 | 7770.72 | 01-MAR-12:00 | 0.00 |
April | 1661.66 | 22-APR-13:00 | 0.00 | 0.00 | 2722.67 | 01-APR-16:10 | 7769.42 | 03-APR-11:00 | 0.00 |
May | 25591.44 | 31-MAY-15:00 | 0.00 | 0.00 | 2722.67 | 26-MAY-17:19 | 7768.89 | 02-MAY-11:30 | 0.00 |
June | 46269.46 | 30-JUN-14:30 | 0.00 | 0.00 | 2722.67 | 20-JUN-15:50 | 7700.62 | 01-JUN-11:50 | 0.00 |
July | 43769.53 | 11-JUL-15:00 | 0.00 | 0.00 | 2722.67 | 11-JUL-12:50 | 7246.83 | 03-JUL-11:00 | 0.00 |
August | 40184.42 | 11-AUG-15:50 | 0.00 | 0.00 | 2722.67 | 30-AUG-06:19 | 7176.81 | 01-AUG-11:39 | 0.00 |
September | 6902.28 | 07-SEP-15:00 | 0.00 | 0.00 | 2722.67 | 15-SEP-07:19 | 7159.15 | 27-SEP-11:20 | 0.00 |
October | 792.45 | 14-OCT-06:10 | 0.00 | 0.00 | 2722.67 | 03-OCT-06:19 | 7229.17 | 31-OCT-11:00 | 0.00 |
November | 714.82 | 04-NOV-06:10 | 0.00 | 0.00 | 2722.67 | 01-NOV-07:30 | 7665.32 | 28-NOV-12:50 | 0.00 |
December | 506.76 | 23-DEC-07:19 | 0.00 | 0.00 | 2722.67 | 01-DEC-13:30 | 7770.05 | 28-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 506.76 | 0.00 | 0.00 | 2722.67 | 7159.15 | 0.00 | |||
Maximum of Months | 46269.46 | 0.00 | 0.00 | 2722.67 | 7772.01 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 99093.88 | 02-JAN-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 9440.13 | 1063.06 | 0.00 | 0.00 | 0.00 |
February | 98454.71 | 27-FEB-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 8433.09 | 1236.15 | 0.00 | 0.00 | 0.00 |
March | 94494.68 | 01-MAR-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 4571.59 | 1133.23 | 0.00 | 0.00 | 0.00 |
April | 89054.61 | 21-APR-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 14080.60 | 6.85 | 0.00 | 0.00 | 0.00 |
May | 121205.01 | 31-MAY-15:30 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 21932.03 | 6.85 | 0.00 | 24516.30 | 0.00 |
June | 147996.69 | 30-JUN-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 25995.29 | 6.90 | 0.00 | 46269.46 | 0.00 |
July | 148464.34 | 11-JUL-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 27678.96 | 6.88 | 0.00 | 43524.37 | 0.00 |
August | 143514.24 | 11-AUG-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 26423.77 | 6.85 | 0.00 | 40184.42 | 0.00 |
September | 90794.43 | 07-SEP-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 9717.45 | 6.85 | 0.00 | 6902.28 | 0.00 |
October | 93514.44 | 30-OCT-07:19 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 3782.89 | 978.45 | 0.00 | 0.00 | 0.00 |
November | 98044.22 | 27-NOV-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 8433.09 | 1163.42 | 0.00 | 0.00 | 0.00 |
December | 97947.62 | 04-DEC-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 8433.09 | 1051.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 89054.61 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 3782.89 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 148464.34 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 27678.96 | 1236.15 | 0.00 | 46269.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 397243.56 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 391247.98 | 27-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 359358.24 | 01-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 185545.82 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 30839.07 | 30-MAY-06:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18218.54 | 07-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 25448.13 | 05-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 44674.99 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 114753.70 | 25-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 210663.58 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 358788.73 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 377826.30 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 18218.54 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 397243.56 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 19.53 | 5.50 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 19.53 | 5.50 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 19.53 | 5.50 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 19.19 | 7.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 3.17 | 19.65 | 3.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
March | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.21 | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
November | 3.83 | 19.57 | 3.67 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
December | 6.00 | 19.78 | 6.00 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Annual Sum or Average | 21.33 | 19.49 | 20.33 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 19.78 | 7.33 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 18.87 | 10.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 8.83 | 18.97 | 7.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 2.50 | 18.85 | 2.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.17 | 19.26 | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.65 | 1.50 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 10.67 | 19.04 | 9.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
December | 12.17 | 19.05 | 10.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 49.67 | 18.96 | 41.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 19.26 | 10.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.00 | 16.69 | 56.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
February | 73.17 | 16.61 | 41.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
March | 33.00 | 17.73 | 19.17 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
April | 4.00 | 17.64 | 2.17 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16.50 | 16.88 | 7.83 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
November | 83.00 | 16.76 | 48.83 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
December | 101.00 | 16.85 | 58.33 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
Annual Sum or Average | 406.67 | 16.83 | 233.83 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.00 | 17.73 | 58.33 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.67 | 15.30 | 24.83 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
February | 45.00 | 15.46 | 14.33 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
March | 14.33 | 15.87 | 2.17 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
April | 1.83 | 15.98 | 0.17 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.41 | 2.83 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.91 | 1.33 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 4.50 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.70 | 0.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.53 | 0.50 | 27.53 |
October | 10.67 | 15.62 | 2.17 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
November | 55.33 | 15.39 | 21.67 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
December | 65.83 | 15.32 | 22.83 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
Annual Sum or Average | 255.67 | 15.40 | 88.17 | 15.65 | 9.50 | 15.99 | 9.50 | 16.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 0.00 | 15.54 |
Maximum of Months | 65.83 | 15.98 | 24.83 | 16.25 | 4.50 | 28.41 | 4.50 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.17 | 15.38 | 22.33 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
February | 35.33 | 15.58 | 9.50 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
March | 9.17 | 16.19 | 1.50 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
April | 0.67 | 17.02 | 0.17 | 17.51 | 1.17 | 23.61 | 1.17 | 25.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.07 | 4.83 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.99 | 3.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.16 | 4.50 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.23 | 2.17 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.99 | 0.17 | 27.99 |
October | 7.50 | 15.78 | 1.67 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
November | 43.33 | 15.51 | 14.33 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
December | 60.50 | 15.36 | 22.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
Annual Sum or Average | 213.67 | 15.49 | 71.50 | 15.75 | 16.17 | 16.41 | 16.00 | 17.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.59 | 0.00 | 15.59 |
Maximum of Months | 60.50 | 17.02 | 22.33 | 17.51 | 4.83 | 28.23 | 4.83 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.50 | 15.27 | 25.00 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
February | 47.50 | 15.33 | 17.00 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
March | 13.67 | 15.87 | 2.50 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
April | 1.00 | 16.60 | 0.17 | 17.00 | 0.50 | 20.31 | 0.17 | 21.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.07 | 1.17 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.10 | 1.33 | 28.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.78 | 1.67 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.08 | 0.67 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11.50 | 15.63 | 3.00 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
November | 54.33 | 15.38 | 21.83 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
December | 65.17 | 15.29 | 22.50 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 256.67 | 15.36 | 92.00 | 15.59 | 14.83 | 16.09 | 5.00 | 16.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.17 | 16.60 | 25.00 | 17.00 | 4.50 | 28.10 | 1.67 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.17 | 18.26 | 78.33 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 72.83 | 18.29 | 57.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
March | 19.83 | 19.05 | 16.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 1.33 | 19.48 | 1.17 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 18.76 | 0.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
November | 26.67 | 18.67 | 19.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 46.67 | 18.76 | 36.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 266.50 | 18.47 | 209.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 98.17 | 19.48 | 78.33 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.00 | 16.70 | 27.83 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 26.33 | 17.06 | 13.17 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 |
March | 4.50 | 18.33 | 2.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
April | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.86 | 2.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.33 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.76 | 4.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.58 | 0.67 | 27.58 |
October | 0.33 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
November | 11.17 | 17.26 | 4.17 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
December | 20.00 | 17.12 | 9.33 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
Annual Sum or Average | 110.50 | 16.99 | 56.83 | 17.50 | 8.67 | 18.00 | 8.17 | 18.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 0.00 | 17.11 |
Maximum of Months | 48.00 | 18.33 | 27.83 | 18.88 | 4.33 | 27.86 | 4.00 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.00 | 16.48 | 251.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
February | 145.50 | 16.34 | 135.83 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
March | 95.67 | 16.37 | 94.00 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
April | 29.83 | 17.72 | 29.83 | 17.72 | 1.00 | 17.88 | 1.00 | 18.04 |
May | 3.67 | 20.04 | 3.67 | 20.04 | 2.00 | 21.67 | 2.00 | 22.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.49 | 1.83 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.93 | 2.83 | 27.95 |
August | 2.00 | 19.14 | 2.00 | 19.14 | 1.83 | 21.96 | 1.50 | 23.25 |
September | 20.50 | 19.23 | 20.50 | 19.23 | 0.50 | 19.34 | 0.50 | 19.43 |
October | 64.17 | 17.22 | 64.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
November | 187.50 | 16.49 | 182.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
December | 288.00 | 16.69 | 272.33 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 1111.83 | 16.65 | 1055.67 | 16.69 | 10.17 | 16.74 | 9.67 | 16.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 0.00 | 16.37 |
Maximum of Months | 288.00 | 20.04 | 272.33 | 20.04 | 3.00 | 27.93 | 2.83 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.50 | 16.57 | 28.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
February | 30.50 | 16.97 | 15.83 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 4.67 | 18.19 | 2.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.52 | 0.17 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.50 | 0.00 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.67 | 0.33 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 0.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 0.33 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
November | 10.50 | 17.17 | 3.67 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
December | 20.33 | 16.98 | 9.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Annual Sum or Average | 114.83 | 16.87 | 59.00 | 17.36 | 6.00 | 17.70 | 0.83 | 17.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.50 | 18.19 | 28.00 | 18.77 | 2.00 | 27.71 | 0.33 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.83 | 16.95 | 35.33 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
February | 32.50 | 17.35 | 20.50 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
March | 8.33 | 18.89 | 6.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
April | 0.50 | 18.57 | 0.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.31 | 0.00 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.67 | 18.91 | 1.83 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 27.83 | 17.98 | 18.33 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 39.50 | 17.81 | 25.33 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
Annual Sum or Average | 168.17 | 17.53 | 107.67 | 17.98 | 1.00 | 18.01 | 0.00 | 18.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.83 | 18.91 | 35.33 | 19.26 | 0.83 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.00 | 15.61 | 16.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 17.17 | 16.33 | 6.17 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
March | 2.17 | 17.13 | 0.33 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
April | 0.17 | 17.09 | 0.00 | 17.09 | 0.67 | 25.43 | 0.67 | 26.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.47 | 3.17 | 28.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.89 | 1.50 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.02 | 4.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.84 | 0.83 | 27.84 |
October | 0.83 | 17.42 | 0.17 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
November | 15.33 | 16.37 | 5.83 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
December | 23.67 | 16.12 | 9.00 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
Annual Sum or Average | 97.33 | 16.03 | 37.50 | 16.35 | 12.00 | 17.31 | 11.50 | 18.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 0.00 | 15.82 |
Maximum of Months | 38.00 | 17.42 | 16.00 | 17.75 | 4.83 | 28.47 | 4.50 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.67 | 15.82 | 12.67 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
February | 11.33 | 16.70 | 5.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 1.17 | 17.01 | 0.17 | 17.30 | 0.17 | 18.41 | 0.17 | 19.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.87 | 2.50 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.08 | 5.33 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.01 | 3.17 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.09 | 4.83 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.13 | 2.67 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.11 | 0.33 | 28.11 |
October | 0.50 | 17.77 | 0.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
November | 11.17 | 16.83 | 3.33 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
December | 20.33 | 16.37 | 7.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 76.17 | 16.28 | 28.67 | 16.66 | 19.17 | 18.42 | 19.00 | 19.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 0.00 | 16.09 |
Maximum of Months | 31.67 | 17.77 | 12.67 | 18.19 | 5.33 | 28.13 | 5.33 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.17 | 15.61 | 17.00 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
February | 18.67 | 16.21 | 7.83 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
March | 2.00 | 17.13 | 0.33 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 0.50 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.09 | 1.50 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 1.17 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.77 | 1.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.88 | 0.83 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
October | 0.83 | 17.41 | 0.17 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
November | 15.50 | 16.36 | 6.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
December | 24.00 | 16.16 | 9.33 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
Annual Sum or Average | 100.17 | 16.01 | 40.67 | 16.31 | 16.50 | 17.53 | 5.83 | 17.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 | 15.81 |
Maximum of Months | 39.17 | 17.41 | 17.00 | 17.74 | 4.67 | 28.09 | 1.67 | 28.10 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.25 | 261.50 | 21.01 | 261.50 | 20.90 |
February | 454.00 | 21.89 | 152.00 | 21.63 | 152.00 | 21.47 |
March | 514.00 | 22.92 | 15.17 | 22.87 | 15.17 | 22.81 |
April | 405.83 | 23.85 | 9.50 | 23.90 | 0.00 | 23.90 |
May | 53.33 | 24.00 | 56.83 | 25.08 | 0.00 | 25.08 |
June | 0.00 | 0.00 | 237.33 | 24.94 | 0.00 | 24.94 |
July | 0.00 | 0.00 | 412.33 | 24.64 | 0.00 | 24.64 |
August | 10.83 | 24.00 | 304.33 | 24.71 | 0.00 | 24.71 |
September | 130.33 | 23.91 | 60.33 | 24.57 | 0.00 | 24.57 |
October | 477.83 | 23.51 | 1.17 | 23.50 | 1.17 | 23.49 |
November | 489.00 | 21.95 | 126.50 | 21.74 | 126.50 | 21.60 |
December | 497.00 | 21.33 | 303.00 | 21.18 | 303.00 | 21.11 |
Annual Sum or Average | 3534.17 | 22.43 | 1940.00 | 22.66 | 859.33 | 22.41 |
Minimum of Months | 0.00 | 0.00 | 1.17 | 21.01 | 0.00 | 20.90 |
Maximum of Months | 514.00 | 24.00 | 412.33 | 25.08 | 303.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 461.33 | 20.38 | 461.33 | 20.37 |
February | 454.00 | 20.77 | 317.83 | 20.63 | 317.83 | 20.57 |
March | 514.00 | 21.46 | 199.50 | 21.28 | 199.50 | 21.17 |
April | 477.67 | 22.94 | 36.00 | 22.81 | 36.00 | 22.70 |
May | 264.17 | 23.79 | 6.33 | 23.83 | 0.00 | 23.83 |
June | 13.17 | 23.90 | 142.00 | 24.69 | 0.00 | 24.69 |
July | 0.00 | 0.00 | 297.50 | 24.50 | 0.00 | 24.50 |
August | 64.00 | 23.70 | 163.83 | 24.35 | 0.00 | 24.35 |
September | 358.50 | 23.14 | 0.17 | 23.14 | 0.00 | 23.14 |
October | 502.00 | 21.77 | 105.17 | 21.58 | 105.17 | 21.45 |
November | 489.00 | 20.68 | 407.83 | 20.61 | 407.83 | 20.58 |
December | 497.00 | 20.48 | 486.17 | 20.47 | 486.17 | 20.47 |
Annual Sum or Average | 4135.50 | 21.60 | 2623.67 | 21.54 | 2013.83 | 21.30 |
Minimum of Months | 0.00 | 0.00 | 0.17 | 20.38 | 0.00 | 20.37 |
Maximum of Months | 514.00 | 23.90 | 486.17 | 24.69 | 486.17 | 24.69 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.07 | 501.17 | 20.07 | 501.17 | 20.07 |
February | 454.00 | 20.26 | 409.50 | 20.20 | 409.50 | 20.18 |
March | 514.00 | 20.84 | 361.33 | 20.70 | 361.33 | 20.64 |
April | 485.00 | 22.24 | 113.67 | 21.91 | 113.67 | 21.68 |
May | 346.00 | 23.53 | 1.17 | 23.54 | 0.00 | 23.54 |
June | 46.67 | 23.74 | 104.17 | 24.34 | 0.00 | 24.34 |
July | 13.00 | 23.46 | 249.83 | 24.40 | 0.00 | 24.40 |
August | 138.50 | 23.37 | 107.33 | 23.87 | 0.00 | 23.87 |
September | 465.83 | 22.56 | 24.17 | 22.47 | 24.17 | 22.39 |
October | 502.00 | 20.90 | 289.33 | 20.70 | 289.33 | 20.61 |
November | 489.00 | 20.13 | 484.83 | 20.13 | 484.83 | 20.13 |
December | 497.00 | 20.07 | 497.00 | 20.07 | 497.00 | 20.07 |
Annual Sum or Average | 4453.00 | 21.19 | 3143.50 | 21.05 | 2681.00 | 20.83 |
Minimum of Months | 13.00 | 20.07 | 1.17 | 20.07 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 23.74 | 501.17 | 24.40 | 501.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.62 | 502.00 | 19.62 | 502.00 | 19.62 |
February | 454.00 | 19.75 | 454.00 | 19.75 | 454.00 | 19.75 |
March | 514.00 | 20.16 | 491.17 | 20.13 | 491.17 | 20.12 |
April | 485.00 | 21.35 | 226.17 | 20.97 | 226.17 | 20.78 |
May | 360.83 | 23.35 | 5.17 | 23.33 | 4.17 | 23.30 |
June | 36.17 | 23.60 | 204.50 | 24.37 | 0.00 | 24.37 |
July | 21.33 | 23.49 | 348.67 | 24.40 | 0.00 | 24.40 |
August | 191.50 | 23.03 | 113.17 | 23.47 | 4.00 | 23.43 |
September | 480.50 | 21.74 | 114.67 | 21.50 | 114.67 | 21.34 |
October | 502.00 | 20.21 | 438.17 | 20.14 | 438.17 | 20.11 |
November | 489.00 | 19.66 | 489.00 | 19.66 | 489.00 | 19.66 |
December | 497.00 | 19.59 | 497.00 | 19.59 | 497.00 | 19.59 |
Annual Sum or Average | 4533.33 | 20.66 | 3883.67 | 20.65 | 3220.33 | 20.43 |
Minimum of Months | 21.33 | 19.59 | 5.17 | 19.59 | 0.00 | 19.59 |
Maximum of Months | 514.00 | 23.60 | 502.00 | 24.40 | 502.00 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 502.00 | 19.71 | 502.00 | 19.71 |
February | 454.00 | 19.85 | 452.00 | 19.84 | 452.00 | 19.84 |
March | 512.33 | 20.54 | 407.17 | 20.39 | 407.17 | 20.33 |
April | 403.33 | 21.64 | 170.33 | 21.37 | 156.00 | 21.15 |
May | 191.67 | 23.20 | 138.17 | 23.77 | 10.00 | 23.85 |
June | 58.67 | 23.64 | 309.33 | 24.26 | 5.17 | 24.30 |
July | 53.83 | 24.46 | 393.50 | 24.50 | 18.83 | 24.60 |
August | 149.83 | 22.97 | 252.67 | 23.77 | 3.50 | 23.76 |
September | 408.50 | 21.68 | 105.00 | 21.64 | 82.50 | 21.47 |
October | 500.50 | 20.36 | 397.50 | 20.24 | 397.50 | 20.19 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4220.67 | 20.67 | 4113.67 | 20.90 | 3020.67 | 20.66 |
Minimum of Months | 53.83 | 19.67 | 105.00 | 19.67 | 3.50 | 19.67 |
Maximum of Months | 512.33 | 24.46 | 502.00 | 24.50 | 502.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 499.33 | 19.74 | 499.33 | 19.73 |
February | 450.33 | 20.16 | 409.50 | 20.06 | 409.50 | 20.02 |
March | 457.33 | 20.77 | 335.67 | 20.55 | 331.33 | 20.44 |
April | 327.67 | 21.66 | 209.67 | 21.77 | 129.67 | 21.50 |
May | 251.00 | 22.85 | 143.00 | 23.42 | 18.50 | 23.48 |
June | 112.50 | 23.49 | 268.67 | 24.11 | 11.83 | 24.20 |
July | 105.17 | 23.67 | 340.00 | 24.30 | 17.50 | 24.40 |
August | 186.50 | 22.90 | 247.33 | 23.73 | 11.83 | 23.76 |
September | 359.33 | 21.69 | 149.50 | 21.92 | 76.50 | 21.74 |
October | 481.33 | 20.58 | 351.33 | 20.41 | 346.83 | 20.33 |
November | 489.00 | 19.81 | 480.67 | 19.79 | 480.67 | 19.78 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4219.17 | 20.83 | 3931.67 | 21.03 | 2830.50 | 20.78 |
Minimum of Months | 105.17 | 19.69 | 143.00 | 19.69 | 11.83 | 19.69 |
Maximum of Months | 502.00 | 23.67 | 499.33 | 24.30 | 499.33 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 502.00 | 19.71 | 502.00 | 19.71 |
February | 454.00 | 19.83 | 451.50 | 19.83 | 451.50 | 19.82 |
March | 514.00 | 20.33 | 456.00 | 20.25 | 456.00 | 20.22 |
April | 409.83 | 21.34 | 210.33 | 21.14 | 183.83 | 20.93 |
May | 310.67 | 22.73 | 68.00 | 23.00 | 11.67 | 22.99 |
June | 110.67 | 23.28 | 235.17 | 24.08 | 5.83 | 24.13 |
July | 98.17 | 23.29 | 318.17 | 24.17 | 7.50 | 24.21 |
August | 235.33 | 22.70 | 178.33 | 23.37 | 7.67 | 23.37 |
September | 450.17 | 21.54 | 122.17 | 21.42 | 108.67 | 21.27 |
October | 502.00 | 20.24 | 425.50 | 20.16 | 425.50 | 20.13 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4572.83 | 20.70 | 3953.17 | 20.77 | 3146.17 | 20.55 |
Minimum of Months | 98.17 | 19.67 | 68.00 | 19.67 | 5.83 | 19.67 |
Maximum of Months | 514.00 | 23.29 | 502.00 | 24.17 | 502.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 502.00 | 19.63 | 502.00 | 19.63 |
February | 454.00 | 19.73 | 454.00 | 19.73 | 454.00 | 19.73 |
March | 514.00 | 20.26 | 510.00 | 20.26 | 510.00 | 20.26 |
April | 485.00 | 21.08 | 270.83 | 20.86 | 270.83 | 20.76 |
May | 499.17 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
June | 62.67 | 23.75 | 102.17 | 24.23 | 0.00 | 24.23 |
July | 7.50 | 23.50 | 296.17 | 24.43 | 0.00 | 24.43 |
August | 148.67 | 23.33 | 94.67 | 23.76 | 0.00 | 23.76 |
September | 481.50 | 22.37 | 38.17 | 22.26 | 38.17 | 22.16 |
October | 502.00 | 20.71 | 355.33 | 20.60 | 355.33 | 20.55 |
November | 489.00 | 19.88 | 489.00 | 19.88 | 489.00 | 19.88 |
December | 497.00 | 19.72 | 497.00 | 19.72 | 497.00 | 19.72 |
Annual Sum or Average | 4642.50 | 20.87 | 3609.33 | 20.75 | 3116.33 | 20.54 |
Minimum of Months | 7.50 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
Maximum of Months | 514.00 | 23.75 | 510.00 | 24.43 | 510.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 502.00 | 19.76 | 502.00 | 19.76 |
February | 454.00 | 19.92 | 454.00 | 19.92 | 454.00 | 19.92 |
March | 514.00 | 20.64 | 434.50 | 20.53 | 434.50 | 20.49 |
April | 440.17 | 21.99 | 139.67 | 21.69 | 135.00 | 21.48 |
May | 178.67 | 23.51 | 119.33 | 23.99 | 5.00 | 24.04 |
June | 32.17 | 23.52 | 291.50 | 24.36 | 0.67 | 24.37 |
July | 23.67 | 25.63 | 427.17 | 24.60 | 14.67 | 24.68 |
August | 67.50 | 23.46 | 306.00 | 24.22 | 0.50 | 24.22 |
September | 348.17 | 22.47 | 48.83 | 22.68 | 14.50 | 22.61 |
October | 500.33 | 20.98 | 282.17 | 20.80 | 282.17 | 20.71 |
November | 489.00 | 19.91 | 489.00 | 19.91 | 489.00 | 19.91 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4046.67 | 20.83 | 3991.17 | 21.10 | 2829.00 | 20.83 |
Minimum of Months | 23.67 | 19.76 | 48.83 | 19.76 | 0.50 | 19.76 |
Maximum of Months | 514.00 | 25.63 | 502.00 | 24.60 | 502.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.71 | 502.00 | 17.71 | 502.00 | 17.71 |
February | 454.00 | 18.82 | 436.00 | 18.77 | 436.00 | 18.75 |
March | 511.50 | 19.93 | 404.17 | 19.72 | 404.17 | 19.63 |
April | 389.00 | 21.62 | 143.33 | 21.46 | 112.83 | 21.18 |
May | 286.00 | 22.59 | 73.00 | 23.07 | 3.83 | 23.07 |
June | 107.83 | 22.82 | 223.00 | 23.95 | 3.17 | 23.98 |
July | 70.17 | 23.11 | 367.00 | 24.29 | 11.83 | 24.36 |
August | 145.67 | 22.74 | 272.17 | 23.88 | 8.00 | 23.91 |
September | 339.67 | 21.89 | 95.67 | 22.25 | 26.67 | 22.10 |
October | 487.17 | 20.56 | 280.67 | 20.26 | 278.33 | 20.11 |
November | 489.00 | 18.30 | 486.67 | 18.30 | 486.67 | 18.30 |
December | 497.00 | 17.45 | 497.00 | 17.45 | 497.00 | 17.45 |
Annual Sum or Average | 4279.00 | 19.86 | 3780.67 | 20.00 | 2770.50 | 19.63 |
Minimum of Months | 70.17 | 17.45 | 73.00 | 17.45 | 3.17 | 17.45 |
Maximum of Months | 511.50 | 23.11 | 502.00 | 24.29 | 502.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 502.00 | 19.76 | 502.00 | 19.76 |
February | 454.00 | 19.86 | 454.00 | 19.86 | 454.00 | 19.86 |
March | 514.00 | 20.39 | 487.67 | 20.36 | 487.67 | 20.34 |
April | 433.83 | 21.69 | 166.83 | 21.41 | 160.33 | 21.23 |
May | 353.67 | 23.03 | 21.00 | 23.14 | 0.50 | 23.13 |
June | 75.83 | 23.40 | 204.83 | 24.22 | 0.67 | 24.23 |
July | 33.17 | 23.27 | 340.83 | 24.33 | 0.17 | 24.33 |
August | 130.00 | 23.19 | 206.83 | 23.95 | 0.67 | 23.95 |
September | 427.83 | 22.27 | 37.17 | 22.23 | 28.83 | 22.14 |
October | 502.00 | 20.73 | 350.67 | 20.62 | 350.67 | 20.57 |
November | 489.00 | 19.91 | 489.00 | 19.91 | 489.00 | 19.91 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4412.33 | 20.86 | 3757.83 | 20.91 | 2971.50 | 20.67 |
Minimum of Months | 33.17 | 19.76 | 21.00 | 19.76 | 0.17 | 19.76 |
Maximum of Months | 514.00 | 23.40 | 502.00 | 24.33 | 502.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.80 | 502.00 | 19.80 | 502.00 | 19.80 |
February | 454.00 | 19.92 | 451.83 | 19.92 | 451.83 | 19.92 |
March | 514.00 | 20.44 | 467.33 | 20.40 | 467.33 | 20.39 |
April | 485.00 | 21.92 | 150.50 | 21.55 | 150.50 | 21.32 |
May | 294.33 | 23.68 | 1.50 | 23.69 | 0.00 | 23.69 |
June | 7.50 | 23.88 | 233.83 | 24.53 | 0.00 | 24.53 |
July | 2.50 | 23.91 | 388.17 | 24.48 | 0.17 | 24.49 |
August | 115.50 | 23.36 | 149.33 | 23.94 | 0.00 | 23.94 |
September | 468.83 | 22.41 | 44.17 | 22.26 | 44.17 | 22.14 |
October | 502.00 | 20.62 | 353.00 | 20.48 | 353.00 | 20.42 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4331.67 | 20.87 | 3727.67 | 20.90 | 2955.00 | 20.66 |
Minimum of Months | 2.50 | 19.78 | 1.50 | 19.78 | 0.00 | 19.78 |
Maximum of Months | 514.00 | 23.91 | 502.00 | 24.53 | 502.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.63 | 427.00 | 19.63 | 427.00 | 19.63 |
February | 385.00 | 19.85 | 379.67 | 19.85 | 379.67 | 19.84 |
March | 430.83 | 20.73 | 312.67 | 20.57 | 312.67 | 20.50 |
April | 338.00 | 21.95 | 104.33 | 21.78 | 87.67 | 21.56 |
May | 165.50 | 23.57 | 125.17 | 24.12 | 10.17 | 24.22 |
June | 32.50 | 24.15 | 252.00 | 24.50 | 6.33 | 24.56 |
July | 29.17 | 25.63 | 341.17 | 24.72 | 18.67 | 24.83 |
August | 100.83 | 23.22 | 217.67 | 24.03 | 2.00 | 24.05 |
September | 339.17 | 22.16 | 59.50 | 22.34 | 28.33 | 22.26 |
October | 425.67 | 20.68 | 276.50 | 20.51 | 276.50 | 20.44 |
November | 417.00 | 19.66 | 417.00 | 19.66 | 417.00 | 19.66 |
December | 422.00 | 19.59 | 422.00 | 19.59 | 422.00 | 19.59 |
Annual Sum or Average | 3512.67 | 20.76 | 3334.67 | 21.01 | 2388.00 | 20.75 |
Minimum of Months | 29.17 | 19.59 | 59.50 | 19.59 | 2.00 | 19.59 |
Maximum of Months | 430.83 | 25.63 | 427.00 | 24.72 | 427.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 495.83 | 19.88 | 495.83 | 19.87 |
February | 448.33 | 20.46 | 376.67 | 20.32 | 376.67 | 20.26 |
March | 442.17 | 21.05 | 290.67 | 20.88 | 277.00 | 20.75 |
April | 303.00 | 22.11 | 169.50 | 22.34 | 81.67 | 22.12 |
May | 217.00 | 23.32 | 147.83 | 23.86 | 12.33 | 23.97 |
June | 71.33 | 23.94 | 296.17 | 24.34 | 11.67 | 24.42 |
July | 52.33 | 24.51 | 375.33 | 24.51 | 17.67 | 24.61 |
August | 132.17 | 23.36 | 276.50 | 24.09 | 10.00 | 24.16 |
September | 326.33 | 22.23 | 113.67 | 22.64 | 22.33 | 22.55 |
October | 471.50 | 21.04 | 259.83 | 20.83 | 251.83 | 20.71 |
November | 489.00 | 20.03 | 468.33 | 19.99 | 468.33 | 19.97 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 3952.17 | 21.03 | 3767.33 | 21.31 | 2522.33 | 21.04 |
Minimum of Months | 52.33 | 19.83 | 113.67 | 19.83 | 10.00 | 19.83 |
Maximum of Months | 502.00 | 24.51 | 497.00 | 24.51 | 497.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 502.00 | 19.83 | 502.00 | 19.83 |
February | 454.00 | 19.97 | 447.00 | 19.96 | 447.00 | 19.96 |
March | 514.00 | 20.61 | 421.83 | 20.50 | 421.83 | 20.46 |
April | 395.83 | 21.82 | 150.17 | 21.67 | 119.67 | 21.45 |
May | 262.50 | 23.15 | 63.33 | 23.47 | 3.83 | 23.51 |
June | 62.50 | 23.68 | 259.33 | 24.34 | 5.83 | 24.39 |
July | 43.67 | 23.78 | 363.50 | 24.37 | 7.00 | 24.41 |
August | 161.50 | 23.05 | 206.67 | 23.80 | 3.33 | 23.83 |
September | 425.50 | 22.04 | 55.33 | 22.02 | 38.50 | 21.93 |
October | 502.00 | 20.62 | 353.67 | 20.49 | 353.67 | 20.43 |
November | 489.00 | 19.85 | 488.83 | 19.85 | 488.83 | 19.85 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4309.50 | 20.85 | 3808.67 | 20.98 | 2888.50 | 20.74 |
Minimum of Months | 43.67 | 19.80 | 55.33 | 19.80 | 3.33 | 19.80 |
Maximum of Months | 514.00 | 23.78 | 502.00 | 24.37 | 502.00 | 24.41 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.24512 | 15.20791 | -0.5838 | 13.64963 |
February | 454.00000 | 21.88873 | 16.22897 | -0.4094 | 9.79903 |
March | 514.00000 | 22.92027 | 16.85596 | -0.1497 | 6.27767 |
April | 485.00000 | 24.03715 | 15.86231 | 0.16211 | 6.02128 |
May | 508.00000 | 24.39090 | 20.73240 | -0.5179 | 11.02332 |
June | 496.00000 | 24.45925 | 32.70233 | -0.3766 | 8.63926 |
July | 497.00000 | 24.53223 | 40.89034 | -0.2961 | 7.62185 |
August | 514.00000 | 24.44479 | 36.07885 | -0.3689 | 8.55454 |
September | 485.00000 | 24.32827 | 26.98169 | -0.5439 | 11.90029 |
October | 502.00000 | 23.56641 | 21.69214 | 0.05209 | 5.77488 |
November | 489.00000 | 21.94560 | 15.52382 | -0.4048 | 9.23870 |
December | 497.00000 | 21.32862 | 12.84751 | -0.5727 | 12.40690 |
Annual Sum or Average | 5943.00000 | 23.26810 | 22.70417 | -0.3339 | 9.23313 |
Minimum of Months | 454.00000 | 21.24512 | 12.84751 | -0.5838 | 5.77488 |
Maximum of Months | 514.00000 | 24.53223 | 40.89034 | 0.16211 | 13.64963 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42369 | 17.57987 | -0.7805 | 19.49295 |
February | 454.00000 | 20.77149 | 18.82415 | -0.6678 | 15.82753 |
March | 514.00000 | 21.46443 | 19.13929 | -0.4705 | 10.48090 |
April | 485.00000 | 22.97736 | 17.48188 | -0.0790 | 6.57970 |
May | 508.00000 | 24.02667 | 21.73233 | -0.6564 | 14.48834 |
June | 496.00000 | 24.25022 | 33.57366 | -0.4660 | 9.85995 |
July | 497.00000 | 24.30048 | 41.83572 | -0.3945 | 8.61786 |
August | 514.00000 | 24.17592 | 37.20710 | -0.4865 | 10.41733 |
September | 485.00000 | 23.43373 | 29.68557 | -0.8550 | 21.90821 |
October | 502.00000 | 21.77408 | 25.14491 | -0.3536 | 8.79333 |
November | 489.00000 | 20.68161 | 18.41513 | -0.7024 | 16.35777 |
December | 497.00000 | 20.47942 | 14.74662 | -0.7857 | 19.02506 |
Annual Sum or Average | 5943.00000 | 22.41034 | 24.67630 | -0.5573 | 13.44975 |
Minimum of Months | 454.00000 | 20.42369 | 14.74662 | -0.8550 | 6.57970 |
Maximum of Months | 514.00000 | 24.30048 | 41.83572 | -0.0790 | 21.90821 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06888 | 18.53443 | -0.9039 | 24.44910 |
February | 454.00000 | 20.25501 | 20.15909 | -0.8237 | 21.58585 |
March | 514.00000 | 20.83620 | 20.02943 | -0.6502 | 15.26795 |
April | 485.00000 | 22.23793 | 18.28270 | -0.2657 | 8.91136 |
May | 508.00000 | 23.73327 | 22.31512 | -0.7645 | 18.24953 |
June | 496.00000 | 24.15316 | 33.63783 | -0.5037 | 10.60028 |
July | 497.00000 | 24.20104 | 41.98048 | -0.4345 | 9.26271 |
August | 514.00000 | 23.95158 | 37.77776 | -0.5755 | 12.78733 |
September | 485.00000 | 22.62125 | 31.44858 | -1.1421 | 34.14262 |
October | 502.00000 | 20.90054 | 26.65200 | -0.5878 | 13.94899 |
November | 489.00000 | 20.13142 | 19.69378 | -0.8722 | 23.05308 |
December | 497.00000 | 20.06944 | 15.58191 | -0.9242 | 24.92598 |
Annual Sum or Average | 5943.00000 | 21.94568 | 25.56412 | -0.7026 | 18.03309 |
Minimum of Months | 454.00000 | 20.06888 | 15.58191 | -1.1421 | 8.91136 |
Maximum of Months | 514.00000 | 24.20104 | 41.98048 | -0.2657 | 34.14262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.61877 | 19.03790 | -1.1287 | 33.71778 |
February | 454.00000 | 19.74651 | 21.06810 | -1.0522 | 30.66681 |
March | 514.00000 | 20.15608 | 21.24321 | -0.8892 | 23.77120 |
April | 485.00000 | 21.35275 | 19.47486 | -0.4931 | 13.73685 |
May | 508.00000 | 23.56695 | 22.85240 | -0.8157 | 20.50213 |
June | 496.00000 | 24.20896 | 33.60727 | -0.4406 | 9.58450 |
July | 497.00000 | 24.29552 | 41.82012 | -0.3695 | 8.46716 |
August | 514.00000 | 23.72671 | 38.82426 | -0.6470 | 15.60484 |
September | 485.00000 | 21.75608 | 33.86017 | -1.4504 | 48.84170 |
October | 502.00000 | 20.21395 | 27.87863 | -0.8150 | 21.21729 |
November | 489.00000 | 19.66093 | 20.45829 | -1.1012 | 32.55943 |
December | 497.00000 | 19.58867 | 15.88586 | -1.1613 | 35.02318 |
Annual Sum or Average | 5943.00000 | 21.50913 | 26.38758 | -0.8612 | 24.36400 |
Minimum of Months | 454.00000 | 19.58867 | 15.88586 | -1.4504 | 8.46716 |
Maximum of Months | 514.00000 | 24.29552 | 41.82012 | -0.3695 | 48.84170 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70741 | 18.71290 | -1.1136 | 32.99164 |
February | 454.00000 | 19.84603 | 20.43548 | -1.0120 | 28.98324 |
March | 514.00000 | 20.55012 | 20.09473 | -0.7400 | 19.23993 |
April | 485.00000 | 22.07290 | 17.78619 | -0.2685 | 11.00633 |
May | 508.00000 | 23.82992 | 21.54157 | -0.5768 | 15.38096 |
June | 496.00000 | 24.18688 | 33.35533 | -0.3301 | 8.73281 |
July | 497.00000 | 24.31536 | 41.32578 | -0.2369 | 8.15743 |
August | 514.00000 | 23.82760 | 37.85942 | -0.5006 | 12.64390 |
September | 485.00000 | 22.12237 | 32.30480 | -1.2690 | 41.77548 |
October | 502.00000 | 20.37437 | 26.91472 | -0.7551 | 19.42595 |
November | 489.00000 | 19.72979 | 19.98353 | -1.0889 | 31.97759 |
December | 497.00000 | 19.67313 | 15.77638 | -1.1497 | 34.44239 |
Annual Sum or Average | 5943.00000 | 21.70426 | 25.56022 | -0.7503 | 21.94407 |
Minimum of Months | 454.00000 | 19.67313 | 15.77638 | -1.2690 | 8.15743 |
Maximum of Months | 514.00000 | 24.31536 | 41.32578 | -0.2369 | 41.77548 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73927 | 18.27434 | -1.0845 | 31.86836 |
February | 454.00000 | 20.18639 | 19.61985 | -0.8879 | 24.91056 |
March | 514.00000 | 21.14423 | 18.88472 | -0.5672 | 17.12353 |
April | 485.00000 | 22.50842 | 16.65076 | -0.1276 | 11.50114 |
May | 508.00000 | 23.54792 | 21.67611 | -0.6906 | 20.11302 |
June | 496.00000 | 24.03822 | 33.50014 | -0.4038 | 10.54056 |
July | 497.00000 | 24.13662 | 41.65815 | -0.3186 | 9.68205 |
August | 514.00000 | 23.74174 | 37.70485 | -0.5097 | 14.48799 |
September | 485.00000 | 22.37085 | 31.20565 | -1.1550 | 38.01353 |
October | 502.00000 | 20.72287 | 25.90093 | -0.6477 | 17.39346 |
November | 489.00000 | 19.81077 | 19.47053 | -1.0351 | 29.99773 |
December | 497.00000 | 19.69098 | 15.35808 | -1.1367 | 33.89778 |
Annual Sum or Average | 5943.00000 | 21.81887 | 25.04905 | -0.7116 | 21.55063 |
Minimum of Months | 454.00000 | 19.69098 | 15.35808 | -1.1550 | 9.68205 |
Maximum of Months | 514.00000 | 24.13662 | 41.65815 | -0.1276 | 38.01353 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70733 | 18.64015 | -1.1170 | 33.11781 |
February | 454.00000 | 19.82918 | 20.37295 | -1.0321 | 29.76320 |
March | 514.00000 | 20.33487 | 20.23002 | -0.8303 | 21.96504 |
April | 485.00000 | 21.78150 | 18.03815 | -0.3411 | 12.80589 |
May | 508.00000 | 23.30784 | 22.70875 | -0.8244 | 23.01713 |
June | 496.00000 | 24.03292 | 34.07175 | -0.4291 | 10.79264 |
July | 497.00000 | 24.05768 | 42.37549 | -0.3866 | 9.94498 |
August | 514.00000 | 23.49098 | 38.97076 | -0.6518 | 17.11990 |
September | 485.00000 | 21.73531 | 32.92595 | -1.4163 | 48.03211 |
October | 502.00000 | 20.24260 | 27.04328 | -0.8049 | 20.85975 |
November | 489.00000 | 19.73331 | 19.90512 | -1.0883 | 31.95192 |
December | 497.00000 | 19.67426 | 15.71249 | -1.1503 | 34.46341 |
Annual Sum or Average | 5943.00000 | 21.51010 | 25.97479 | -0.8372 | 24.38947 |
Minimum of Months | 454.00000 | 19.67426 | 15.71249 | -1.4163 | 9.94498 |
Maximum of Months | 514.00000 | 24.05768 | 42.37549 | -0.3411 | 48.03211 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62537 | 16.65208 | -1.1272 | 33.38159 |
February | 454.00000 | 19.73057 | 18.40706 | -1.0735 | 31.22391 |
March | 514.00000 | 20.26087 | 19.78688 | -0.8919 | 23.18028 |
April | 485.00000 | 21.08079 | 19.73866 | -0.5743 | 13.59411 |
May | 508.00000 | 23.26166 | 24.01195 | -0.9552 | 25.25678 |
June | 496.00000 | 24.14297 | 34.27541 | -0.5101 | 10.77378 |
July | 497.00000 | 24.25798 | 42.35641 | -0.4074 | 8.81088 |
August | 514.00000 | 23.90745 | 38.62472 | -0.5936 | 13.36881 |
September | 485.00000 | 22.38515 | 31.99936 | -1.2185 | 37.51256 |
October | 502.00000 | 20.71226 | 25.90347 | -0.6574 | 15.39462 |
November | 489.00000 | 19.87731 | 17.83546 | -1.0199 | 28.62534 |
December | 497.00000 | 19.71990 | 14.11732 | -1.1114 | 32.47456 |
Annual Sum or Average | 5943.00000 | 21.59844 | 25.37840 | -0.8427 | 22.70321 |
Minimum of Months | 454.00000 | 19.62537 | 14.11732 | -1.2185 | 8.81088 |
Maximum of Months | 514.00000 | 24.25798 | 42.35641 | -0.4074 | 37.51256 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76329 | 16.52227 | -1.1057 | 32.38697 |
February | 454.00000 | 19.91619 | 18.17792 | -1.0183 | 28.77560 |
March | 514.00000 | 20.63765 | 19.18211 | -0.7409 | 18.23072 |
April | 485.00000 | 22.21233 | 18.03797 | -0.2541 | 9.61121 |
May | 508.00000 | 24.01157 | 21.56906 | -0.5618 | 13.69565 |
June | 496.00000 | 24.25577 | 33.51902 | -0.3515 | 8.51013 |
July | 497.00000 | 24.44259 | 41.33298 | -0.2194 | 7.31584 |
August | 514.00000 | 24.15933 | 37.23490 | -0.3973 | 9.46576 |
September | 485.00000 | 23.02511 | 30.26013 | -0.9541 | 27.85082 |
October | 502.00000 | 20.99433 | 25.18915 | -0.5687 | 13.51885 |
November | 489.00000 | 19.91072 | 17.62016 | -1.0172 | 28.49021 |
December | 497.00000 | 19.78016 | 14.19374 | -1.1084 | 32.33997 |
Annual Sum or Average | 5943.00000 | 21.94378 | 24.46751 | -0.6884 | 19.06999 |
Minimum of Months | 454.00000 | 19.76329 | 14.19374 | -1.1084 | 7.31584 |
Maximum of Months | 514.00000 | 24.44259 | 41.33298 | -0.2194 | 32.38697 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.71084 | 15.00264 | -1.4802 | 48.81794 |
February | 454.00000 | 18.81894 | 15.99173 | -1.1747 | 35.63214 |
March | 514.00000 | 19.95903 | 16.30866 | -0.8101 | 22.14661 |
April | 485.00000 | 22.19284 | 16.02053 | -0.1806 | 10.26408 |
May | 508.00000 | 23.38046 | 21.86333 | -0.7660 | 21.03524 |
June | 496.00000 | 23.94341 | 33.92136 | -0.4694 | 11.42655 |
July | 497.00000 | 24.14801 | 41.86202 | -0.3330 | 9.47107 |
August | 514.00000 | 23.86780 | 37.34055 | -0.4529 | 12.28284 |
September | 485.00000 | 22.67640 | 29.10855 | -0.9936 | 30.66193 |
October | 502.00000 | 20.66814 | 22.68609 | -0.5936 | 15.89953 |
November | 489.00000 | 18.30479 | 15.21869 | -1.2961 | 40.79358 |
December | 497.00000 | 17.45444 | 12.65556 | -1.5510 | 51.75240 |
Annual Sum or Average | 5943.00000 | 21.11380 | 23.23945 | -0.8388 | 25.73458 |
Minimum of Months | 454.00000 | 17.45444 | 12.65556 | -1.5510 | 9.47107 |
Maximum of Months | 514.00000 | 24.14801 | 41.86202 | -0.1806 | 51.75240 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76281 | 16.39582 | -1.1096 | 32.54244 |
February | 454.00000 | 19.86457 | 18.04115 | -1.0463 | 29.97203 |
March | 514.00000 | 20.38667 | 19.22789 | -0.8419 | 21.41956 |
April | 485.00000 | 21.94779 | 18.19145 | -0.3163 | 10.32194 |
May | 508.00000 | 23.40636 | 23.08363 | -0.8388 | 21.95282 |
June | 496.00000 | 24.13871 | 34.19721 | -0.4424 | 10.17894 |
July | 497.00000 | 24.21822 | 42.39523 | -0.3652 | 8.65210 |
August | 514.00000 | 23.95822 | 38.19220 | -0.5116 | 11.88554 |
September | 485.00000 | 22.50808 | 31.09616 | -1.1387 | 34.70596 |
October | 502.00000 | 20.73398 | 25.38219 | -0.6474 | 15.12979 |
November | 489.00000 | 19.91349 | 17.47178 | -1.0173 | 28.49093 |
December | 497.00000 | 19.78173 | 14.09534 | -1.1092 | 32.36768 |
Annual Sum or Average | 5943.00000 | 21.73501 | 24.88465 | -0.7798 | 21.37234 |
Minimum of Months | 454.00000 | 19.76281 | 14.09534 | -1.1387 | 8.65210 |
Maximum of Months | 514.00000 | 24.21822 | 42.39523 | -0.3163 | 34.70596 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79634 | 18.62501 | -1.0410 | 29.88178 |
February | 454.00000 | 19.92306 | 20.25963 | -0.9635 | 26.86476 |
March | 514.00000 | 20.44460 | 20.57518 | -0.7782 | 19.20422 |
April | 485.00000 | 21.91956 | 18.87800 | -0.3369 | 10.23147 |
May | 508.00000 | 23.88537 | 22.22580 | -0.6990 | 16.02734 |
June | 496.00000 | 24.28902 | 33.51217 | -0.4075 | 8.90931 |
July | 497.00000 | 24.38298 | 41.68313 | -0.3326 | 7.86625 |
August | 514.00000 | 23.99255 | 38.13288 | -0.5469 | 12.23666 |
September | 485.00000 | 22.45977 | 32.34382 | -1.1893 | 36.55759 |
October | 502.00000 | 20.62077 | 26.85284 | -0.6721 | 16.27895 |
November | 489.00000 | 19.82886 | 19.89213 | -1.0062 | 28.42630 |
December | 497.00000 | 19.77588 | 15.76852 | -1.0668 | 30.76736 |
Annual Sum or Average | 5943.00000 | 21.79430 | 25.78491 | -0.7510 | 20.17245 |
Minimum of Months | 454.00000 | 19.77588 | 15.76852 | -1.1893 | 7.86625 |
Maximum of Months | 514.00000 | 24.38298 | 41.68313 | -0.3326 | 36.55759 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.62869 | 17.61261 | -1.0822 | 31.73534 |
February | 385.00000 | 19.85393 | 18.93791 | -0.9682 | 27.03758 |
March | 433.00000 | 20.75127 | 18.79437 | -0.6676 | 16.44171 |
April | 410.00000 | 22.38673 | 16.79996 | -0.1827 | 9.31664 |
May | 430.00000 | 24.03670 | 20.99397 | -0.5183 | 13.58528 |
June | 418.00000 | 24.31771 | 33.11592 | -0.3089 | 8.38286 |
July | 422.00000 | 24.47172 | 41.06679 | -0.2067 | 7.81299 |
August | 433.00000 | 24.00669 | 37.16620 | -0.4509 | 11.11870 |
September | 410.00000 | 22.59122 | 30.63118 | -1.0935 | 34.12637 |
October | 427.00000 | 20.68736 | 25.32958 | -0.6451 | 15.68157 |
November | 417.00000 | 19.65628 | 18.82032 | -1.0473 | 30.25212 |
December | 422.00000 | 19.58849 | 14.90909 | -1.1128 | 32.88376 |
Annual Sum or Average | 5034.00000 | 21.84556 | 24.56195 | -0.6880 | 19.77288 |
Minimum of Months | 385.00000 | 19.58849 | 14.90909 | -1.1128 | 7.81299 |
Maximum of Months | 433.00000 | 24.47172 | 41.06679 | -0.1827 | 34.12637 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.88574 | 17.51357 | -1.0042 | 28.41637 |
February | 454.00000 | 20.50410 | 18.46703 | -0.7747 | 20.75163 |
March | 514.00000 | 21.50531 | 18.00488 | -0.4441 | 13.79322 |
April | 485.00000 | 22.93817 | 16.10134 | -0.0011 | 9.72771 |
May | 508.00000 | 23.85951 | 21.21882 | -0.5784 | 15.52130 |
June | 496.00000 | 24.18811 | 33.29316 | -0.3536 | 9.09603 |
July | 497.00000 | 24.29553 | 41.39484 | -0.2646 | 8.30927 |
August | 514.00000 | 24.00808 | 37.10856 | -0.4123 | 11.24003 |
September | 485.00000 | 22.91082 | 29.93494 | -0.9424 | 28.62456 |
October | 502.00000 | 21.22465 | 24.68956 | -0.4888 | 13.18389 |
November | 489.00000 | 20.02790 | 18.35837 | -0.9338 | 25.70599 |
December | 497.00000 | 19.82671 | 14.75978 | -1.0548 | 30.23098 |
Annual Sum or Average | 5943.00000 | 22.11295 | 24.29826 | -0.6025 | 17.81822 |
Minimum of Months | 454.00000 | 19.82671 | 14.75978 | -1.0548 | 8.30927 |
Maximum of Months | 514.00000 | 24.29553 | 41.39484 | -0.0011 | 30.23098 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83098 | 17.96238 | -1.0420 | 29.85779 |
February | 454.00000 | 19.96752 | 19.40024 | -0.9522 | 26.36555 |
March | 514.00000 | 20.60828 | 19.48428 | -0.7232 | 17.91081 |
April | 485.00000 | 22.25791 | 17.48746 | -0.2034 | 9.93965 |
May | 508.00000 | 23.68285 | 22.18898 | -0.6931 | 17.58655 |
June | 496.00000 | 24.18793 | 33.83634 | -0.3767 | 9.29994 |
July | 497.00000 | 24.22795 | 42.07141 | -0.3283 | 8.47702 |
August | 514.00000 | 23.82252 | 38.24889 | -0.5350 | 13.00413 |
September | 485.00000 | 22.30669 | 31.61593 | -1.1919 | 37.44866 |
October | 502.00000 | 20.61564 | 26.01106 | -0.6696 | 16.13591 |
November | 489.00000 | 19.85430 | 19.01999 | -1.0052 | 28.35407 |
December | 497.00000 | 19.80140 | 15.18355 | -1.0706 | 30.89919 |
Annual Sum or Average | 5943.00000 | 21.78027 | 25.27069 | -0.7304 | 20.34566 |
Minimum of Months | 454.00000 | 19.80140 | 15.18355 | -1.1919 | 8.47702 |
Maximum of Months | 514.00000 | 24.22795 | 42.07141 | -0.2034 | 37.44866 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.178295E+12 | 0.00 | 619.55 | 320924.52 | 12-JAN-07:07 | 0.00 | 41.07 | 56.73 | 0.91 | 0.00 | 0.13 | 0.62 | 12-JAN-07:07 |
February | 0.117557E+12 | 0.00 | 517.64 | 317254.61 | 27-FEB-07:13 | 0.00 | 39.33 | 54.99 | 0.63 | 0.00 | 0.09 | 0.62 | 27-FEB-07:13 |
March | 0.651797E+11 | 0.00 | 497.67 | 285206.03 | 01-MAR-07:10 | 0.00 | 35.12 | 51.07 | 0.29 | 0.00 | 0.05 | 0.55 | 01-MAR-07:10 |
April | 0.122701E+11 | 0.00 | 250.33 | 254302.43 | 17-APR-05:01 | 0.00 | 33.43 | 42.53 | 0.05 | 0.00 | 0.01 | 0.49 | 17-APR-05:01 |
May | 0.891633E+09 | 0.00 | 44.52 | 37957.60 | 27-MAY-06:03 | 0.00 | 41.47 | 42.68 | 0.00 | 0.00 | 0.00 | 0.07 | 27-MAY-06:03 |
June | 0.177575E+09 | 0.00 | 29.33 | 15039.59 | 15-JUN-06:05 | 0.00 | 37.84 | 38.81 | 0.00 | 0.00 | 0.00 | 0.03 | 15-JUN-06:05 |
July | 0.146619E+09 | 0.00 | 44.36 | 17665.22 | 05-JUL-06:06 | 0.00 | 36.45 | 37.82 | 0.00 | 0.00 | 0.00 | 0.03 | 05-JUL-06:06 |
August | 0.445089E+09 | 0.00 | 34.74 | 74086.38 | 31-AUG-06:02 | 0.00 | 37.42 | 38.44 | 0.00 | 0.00 | 0.00 | 0.14 | 31-AUG-06:02 |
September | 0.541831E+10 | 0.00 | 184.13 | 235093.18 | 26-SEP-06:02 | 0.00 | 35.03 | 41.74 | 0.02 | 0.00 | 0.00 | 0.46 | 26-SEP-06:02 |
October | 0.422164E+11 | 0.00 | 427.04 | 255475.83 | 12-OCT-05:01 | 0.00 | 30.86 | 46.08 | 0.17 | 0.00 | 0.03 | 0.50 | 12-OCT-05:01 |
November | 0.146043E+12 | 0.00 | 578.58 | 286282.33 | 29-NOV-07:12 | 0.00 | 40.63 | 56.06 | 0.75 | 0.00 | 0.11 | 0.56 | 29-NOV-07:12 |
December | 0.194261E+12 | 0.00 | 623.16 | 304384.40 | 15-DEC-07:11 | 0.00 | 41.39 | 56.75 | 1.01 | 0.00 | 0.14 | 0.59 | 15-DEC-07:11 |
Annual Sum or Average | 0.762902E+12 | 0.00 | 3851.05 | 0.00 | 37.50 | 46.93 | 0.32 | 0.00 | 0.05 | ||||
Minimum of Months | 0.146619E+09 | 0.00 | 29.33 | 15039.59 | 0.00 | 30.86 | 37.82 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.194261E+12 | 0.00 | 623.16 | 320924.52 | 0.00 | 41.47 | 56.75 | 1.01 | 0.00 | 0.14 | 0.62 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7710094.33 | 2041020.75 | 2.42 | 7708783.86 | 1310.47 | 0.00 | 0.29 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 7138.76 | 20-JAN-07:01 | 7138.76 | 20-JAN-07:01 | 4.97 | 19-JAN-17:11 | 1815.78 | 20-JAN-07:01 | 0.00 |
February | 10559775.29 | 2830581.40 | 4.24 | 10475696.90 | 84078.39 | 0.00 | 0.26 | 02-FEB-07:01 | 0.00 | 01-FEB-00:10 | 6357.46 | 02-FEB-07:01 | 6357.46 | 02-FEB-07:01 | 53.40 | 09-FEB-13:02 | 1628.85 | 02-FEB-07:01 | 0.00 |
March | 33256014.71 | 8970209.11 | 14.78 | 32981139.50 | 274875.21 | 0.00 | 0.16 | 18-MAR-06:03 | 0.00 | 01-MAR-00:05 | 3926.03 | 18-MAR-06:03 | 3926.03 | 18-MAR-06:03 | 117.44 | 21-MAR-17:13 | 1029.25 | 18-MAR-06:03 | 0.00 |
April | 41751952.17 | 11221478.21 | 14.91 | 41750218.24 | 1733.94 | 0.00 | 0.19 | 08-APR-06:03 | 0.00 | 01-APR-00:10 | 4581.11 | 08-APR-06:03 | 4581.11 | 08-APR-06:03 | 7.32 | 29-APR-06:10 | 1193.52 | 08-APR-06:03 | 0.00 |
May | 0.427543E+10 | 0.101845E+10 | 140.48 | 0.426922E+10 | 6206982.72 | 0.00 | 1.00 | 31-MAY-14:20 | 0.00 | 01-MAY-00:10 | 39928.12 | 31-MAY-16:00 | 39928.12 | 31-MAY-16:00 | 275.28 | 14-MAY-17:33 | 8380.53 | 31-MAY-16:00 | 0.00 |
June | 0.220110E+11 | 0.494006E+10 | 317.11 | 0.211312E+11 | 0.879758E+09 | 0.00 | 1.00 | 12-JUN-13:00 | 0.00 | 01-JUN-00:10 | 65918.36 | 30-JUN-14:30 | 61061.75 | 30-JUN-14:30 | 15642.32 | 30-JUN-06:03 | 15234.44 | 30-JUN-14:30 | 0.00 |
July | 0.311428E+11 | 0.684782E+10 | 338.57 | 0.287281E+11 | 0.241470E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 68249.43 | 11-JUL-15:50 | 65904.58 | 12-JUL-16:00 | 35882.34 | 03-JUL-15:00 | 15122.54 | 11-JUL-16:00 | 0.00 |
August | 0.167525E+11 | 0.373549E+10 | 247.54 | 0.155835E+11 | 0.116903E+10 | 0.00 | 1.00 | 01-AUG-13:30 | 0.00 | 01-AUG-00:10 | 64525.35 | 11-AUG-15:50 | 64525.35 | 11-AUG-15:50 | 8418.79 | 03-AUG-15:00 | 14052.67 | 11-AUG-15:50 | 0.00 |
September | 0.277780E+09 | 72882667.65 | 32.52 | 0.263435E+09 | 14345023.56 | 0.00 | 0.41 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 10512.13 | 07-SEP-16:00 | 10512.13 | 07-SEP-16:00 | 571.76 | 02-SEP-18:00 | 2592.76 | 07-SEP-16:00 | 0.00 |
October | 36689904.61 | 9885733.84 | 16.00 | 35567252.39 | 1122652.22 | 0.00 | 0.18 | 21-OCT-06:03 | 0.00 | 01-OCT-00:10 | 4392.71 | 21-OCT-06:03 | 4392.71 | 21-OCT-06:03 | 110.57 | 02-OCT-07:20 | 1146.49 | 21-OCT-06:03 | 0.00 |
November | 8025067.61 | 2144287.95 | 3.34 | 8025067.61 | -0.0 | 0.00 | 0.23 | 15-NOV-07:01 | 0.00 | 01-NOV-00:10 | 5725.02 | 15-NOV-07:01 | 5725.02 | 15-NOV-07:01 | 0.00 | 06-NOV-13:12 | 1475.52 | 15-NOV-07:01 | 0.00 |
December | 5277832.66 | 1392073.73 | 1.02 | 5277832.66 | 0.00 | 0.00 | 0.26 | 21-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6436.91 | 21-DEC-07:01 | 6436.91 | 21-DEC-07:01 | 0.00 | 27-DEC-07:01 | 1647.98 | 21-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.746028E+11 | 0.166532E+11 | 1132.93 | 0.701173E+11 | 0.448552E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 5277832.66 | 1392073.73 | 1.02 | 5277832.66 | -0.0 | 0.00 | 0.16 | 0.00 | 3926.03 | 3926.03 | 0.00 | 1029.25 | 0.00 | ||||||
Maximum of Months | 0.311428E+11 | 0.684782E+10 | 338.57 | 0.287281E+11 | 0.241470E+10 | 0.00 | 1.00 | 0.00 | 68249.43 | 65904.58 | 35882.34 | 15234.44 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8129165.26 | 2115107.29 | 0.90 | 8129165.26 | -0.0 | 0.00 | 0.28 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6624.18 | 20-JAN-07:01 | 6624.18 | 20-JAN-07:01 | 0.00 | 25-JAN-07:01 | 1687.69 | 20-JAN-07:01 | 0.00 |
February | 7800275.92 | 2009266.14 | 0.90 | 7797071.41 | 3204.51 | 0.00 | 0.34 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 8076.46 | 09-FEB-07:01 | 8076.46 | 09-FEB-07:01 | 18.89 | 09-FEB-12:04 | 2028.96 | 09-FEB-07:01 | 0.00 |
March | 17112777.52 | 4456985.52 | 6.37 | 17068130.90 | 44646.63 | 0.00 | 0.39 | 22-MAR-06:01 | 0.00 | 01-MAR-00:05 | 9292.68 | 22-MAR-06:01 | 9292.68 | 22-MAR-06:01 | 19.88 | 22-MAR-10:30 | 2307.51 | 22-MAR-06:01 | 0.00 |
April | 33477287.97 | 8979112.00 | 18.34 | 33477287.97 | -0.0 | 0.00 | 0.36 | 05-APR-06:01 | 0.00 | 01-APR-00:10 | 8565.65 | 05-APR-06:01 | 8565.65 | 05-APR-06:01 | 0.00 | 08-APR-06:03 | 2141.78 | 05-APR-06:01 | 0.00 |
May | 0.455631E+10 | 0.107829E+10 | 147.45 | 0.455224E+10 | 4069366.73 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 40269.72 | 31-MAY-16:00 | 40269.72 | 31-MAY-16:00 | 348.95 | 31-MAY-20:30 | 8451.17 | 31-MAY-16:00 | 0.00 |
June | 0.218593E+11 | 0.489392E+10 | 324.40 | 0.209847E+11 | 0.874614E+09 | 0.00 | 1.00 | 09-JUN-12:10 | 0.00 | 01-JUN-00:10 | 67664.87 | 30-JUN-12:10 | 60016.06 | 30-JUN-14:30 | 13809.97 | 30-JUN-06:03 | 14904.24 | 30-JUN-14:30 | 0.00 |
July | 0.293331E+11 | 0.645883E+10 | 345.08 | 0.270392E+11 | 0.229391E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 64383.53 | 11-JUL-15:30 | 61191.86 | 21-JUL-14:30 | 33134.54 | 03-JUL-15:00 | 14177.40 | 11-JUL-16:00 | 0.00 |
August | 0.151415E+11 | 0.339352E+10 | 248.42 | 0.139875E+11 | 0.115392E+10 | 0.00 | 1.00 | 01-AUG-13:00 | 0.00 | 01-AUG-00:10 | 59267.91 | 11-AUG-15:20 | 59267.91 | 11-AUG-15:20 | 7536.45 | 04-AUG-10:50 | 12769.21 | 11-AUG-15:30 | 0.00 |
September | 0.243958E+09 | 64040232.58 | 31.58 | 0.231094E+09 | 12864239.64 | 0.00 | 0.38 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 9140.23 | 07-SEP-16:00 | 9140.23 | 07-SEP-16:00 | 510.88 | 02-SEP-17:45 | 2272.95 | 07-SEP-16:00 | 0.00 |
October | 16629265.91 | 4297842.62 | 3.02 | 16554485.97 | 74779.94 | 0.00 | 0.37 | 20-OCT-06:01 | 0.00 | 01-OCT-00:10 | 8933.29 | 20-OCT-06:01 | 8933.29 | 20-OCT-06:01 | 38.90 | 03-OCT-10:30 | 2225.87 | 20-OCT-06:01 | 0.00 |
November | 8572810.07 | 2232807.83 | 0.94 | 8572810.07 | 0.00 | 0.00 | 0.30 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 7122.60 | 02-NOV-06:01 | 7122.60 | 02-NOV-06:01 | 0.00 | 16-NOV-07:01 | 1805.90 | 02-NOV-06:01 | 0.00 |
December | 6155515.24 | 1615057.88 | 0.76 | 6155515.24 | 0.00 | 0.00 | 0.24 | 21-DEC-07:11 | 0.00 | 01-DEC-00:10 | 5642.12 | 21-DEC-07:11 | 5642.12 | 21-DEC-07:11 | 0.00 | 21-DEC-07:11 | 1451.39 | 21-DEC-07:11 | 0.00 |
Annual Sum or Average | 0.712320E+11 | 0.159143E+11 | 1128.15 | 0.668925E+11 | 0.433950E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 6155515.24 | 1615057.88 | 0.76 | 6155515.24 | -0.0 | 0.00 | 0.24 | 0.00 | 5642.12 | 5642.12 | 0.00 | 1451.39 | 0.00 | ||||||
Maximum of Months | 0.293331E+11 | 0.645883E+10 | 345.08 | 0.270392E+11 | 0.229391E+10 | 0.00 | 1.00 | 0.00 | 67664.87 | 61191.86 | 33134.54 | 14904.24 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1471434.30 | 396668.68 | 0.53 | 1471434.30 | -0.0 | 0.00 | 0.09 | 19-JAN-07:11 | 0.00 | 01-JAN-00:02 | 2261.86 | 19-JAN-07:11 | 2261.86 | 19-JAN-07:11 | 0.00 | 24-JAN-06:15 | 602.99 | 19-JAN-07:11 | 0.00 |
February | 2613637.62 | 701357.26 | 1.09 | 2603951.67 | 9685.94 | 0.00 | 0.19 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 4788.13 | 09-FEB-07:01 | 4788.13 | 09-FEB-07:01 | 15.32 | 09-FEB-07:16 | 1246.88 | 09-FEB-07:01 | 0.00 |
March | 14735360.64 | 3983832.10 | 12.08 | 14508595.02 | 226765.62 | 0.00 | 0.22 | 23-MAR-06:01 | 0.00 | 01-MAR-00:05 | 5493.69 | 23-MAR-06:01 | 5493.69 | 23-MAR-06:01 | 38.43 | 22-MAR-11:00 | 1421.41 | 23-MAR-06:01 | 0.00 |
April | 40387051.89 | 10899032.67 | 26.35 | 40352915.72 | 34136.16 | 0.00 | 0.22 | 12-APR-06:01 | 0.00 | 01-APR-00:10 | 5574.91 | 12-APR-06:01 | 5574.91 | 12-APR-06:01 | 19.12 | 18-APR-12:05 | 1441.36 | 12-APR-06:01 | 0.00 |
May | 0.439870E+10 | 0.104932E+10 | 147.26 | 0.439153E+10 | 7173678.92 | 0.00 | 1.00 | 12-MAY-13:10 | 0.00 | 01-MAY-00:10 | 41735.77 | 31-MAY-16:00 | 41735.77 | 31-MAY-16:00 | 516.92 | 31-MAY-06:02 | 8759.74 | 31-MAY-16:00 | 0.00 |
June | 0.220355E+11 | 0.496302E+10 | 320.12 | 0.211305E+11 | 0.904935E+09 | 0.00 | 1.00 | 12-JUN-13:10 | 0.00 | 01-JUN-00:10 | 72349.67 | 30-JUN-12:30 | 65582.65 | 29-JUN-14:30 | 13733.09 | 30-JUN-11:50 | 16130.77 | 30-JUN-14:30 | 0.00 |
July | 0.295393E+11 | 0.653984E+10 | 340.87 | 0.272302E+11 | 0.230907E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 66778.60 | 21-JUL-14:30 | 66778.60 | 21-JUL-14:30 | 32691.53 | 03-JUL-15:00 | 15164.67 | 21-JUL-14:40 | 0.00 |
August | 0.149291E+11 | 0.336955E+10 | 244.24 | 0.136992E+11 | 0.122994E+10 | 0.00 | 1.00 | 02-AUG-12:10 | 0.00 | 01-AUG-00:10 | 61615.94 | 11-AUG-15:40 | 61615.94 | 11-AUG-15:40 | 7433.99 | 03-AUG-14:40 | 13407.71 | 11-AUG-15:50 | 0.00 |
September | 0.226125E+09 | 59640997.51 | 32.35 | 0.210815E+09 | 15309668.25 | 0.00 | 0.37 | 10-SEP-11:32 | 0.00 | 01-SEP-00:10 | 9746.64 | 10-SEP-11:32 | 9746.64 | 10-SEP-11:32 | 590.86 | 02-SEP-14:50 | 2427.68 | 10-SEP-11:32 | 0.00 |
October | 12111665.35 | 3228671.20 | 5.07 | 11803325.97 | 308339.38 | 0.00 | 0.22 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 5507.53 | 02-OCT-06:03 | 5507.53 | 02-OCT-06:03 | 78.28 | 03-OCT-10:40 | 1424.81 | 02-OCT-06:03 | 0.00 |
November | 1093102.80 | 295879.86 | 0.51 | 1093102.80 | -0.0 | 0.00 | 0.04 | 22-NOV-06:17 | 0.00 | 01-NOV-00:10 | 989.10 | 22-NOV-06:17 | 989.10 | 22-NOV-06:17 | 0.00 | 16-NOV-06:04 | 266.87 | 22-NOV-06:17 | 0.00 |
December | 1594285.17 | 430297.90 | 0.58 | 1594285.17 | -0.0 | 0.00 | 0.06 | 23-DEC-07:15 | 0.00 | 01-DEC-00:10 | 1571.83 | 23-DEC-07:15 | 1571.83 | 23-DEC-07:15 | 0.00 | 08-DEC-06:07 | 421.77 | 23-DEC-07:15 | 0.00 |
Annual Sum or Average | 0.712027E+11 | 0.160013E+11 | 1131.04 | 0.667357E+11 | 0.446700E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1093102.80 | 295879.86 | 0.51 | 1093102.80 | -0.0 | 0.00 | 0.04 | 0.00 | 989.10 | 989.10 | 0.00 | 266.87 | 0.00 | ||||||
Maximum of Months | 0.295393E+11 | 0.653984E+10 | 340.87 | 0.272302E+11 | 0.230907E+10 | 0.00 | 1.00 | 0.00 | 72349.67 | 66778.60 | 32691.53 | 16130.77 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.46 | 0.00 | 47.46 | 0.00 | 3224.79 | 0.00 | 0.00 | 0.00 |
February | 209.78 | 0.00 | 209.78 | 0.00 | 2872.49 | 0.00 | 0.00 | 0.00 |
March | 561.07 | 0.00 | 561.07 | 55.84 | 2107.54 | 0.00 | 0.00 | 0.00 |
April | 1015.27 | 22.49 | 992.78 | 428.07 | 1123.14 | 0.00 | 0.00 | 0.00 |
May | 1556.45 | 247.95 | 1308.49 | 1194.88 | 514.04 | 0.00 | 0.00 | 0.00 |
June | 2030.44 | 451.92 | 1578.52 | 1949.63 | 241.21 | 0.00 | 0.00 | 0.00 |
July | 1704.16 | 277.37 | 1426.79 | 1671.58 | 293.88 | 0.00 | 0.00 | 0.00 |
August | 1088.13 | 61.03 | 1027.09 | 880.65 | 484.74 | 0.00 | 0.00 | 0.00 |
September | 606.93 | 0.62 | 606.31 | 245.01 | 948.90 | 0.00 | 0.00 | 0.00 |
October | 295.32 | 0.00 | 295.32 | 26.89 | 1782.93 | 0.00 | 0.00 | 0.00 |
November | 91.65 | 0.00 | 91.65 | 0.00 | 3147.93 | 0.00 | 0.00 | 0.00 |
December | 14.40 | 0.00 | 14.40 | 0.00 | 3399.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.17 | 88.84 | 682.33 | 540.84 | 1672.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.40 | 0.00 | 14.40 | 0.00 | 241.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2030.44 | 451.92 | 1578.52 | 1949.63 | 3399.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.43 | 26.32 | 57.11 | 8.06 | 2084.13 | 0.00 | 0.00 | 0.00 |
February | 460.68 | 219.93 | 240.75 | 247.25 | 1731.62 | 0.00 | 0.00 | 0.00 |
March | 1313.19 | 664.89 | 648.30 | 1102.05 | 1266.85 | 0.00 | 0.00 | 0.00 |
April | 1804.83 | 912.77 | 892.06 | 1649.50 | 697.02 | 0.00 | 0.00 | 0.00 |
May | 2621.49 | 1475.23 | 1146.27 | 2807.87 | 370.48 | 0.00 | 0.00 | 0.00 |
June | 2412.34 | 1123.51 | 1288.83 | 2665.11 | 183.85 | 0.00 | 0.00 | 0.00 |
July | 2291.25 | 1109.16 | 1182.08 | 2593.27 | 210.71 | 0.00 | 0.00 | 0.00 |
August | 1814.69 | 882.15 | 932.54 | 1970.60 | 326.74 | 0.00 | 0.00 | 0.00 |
September | 1122.79 | 491.35 | 631.45 | 1037.35 | 598.00 | 0.00 | 0.00 | 0.00 |
October | 593.28 | 238.10 | 355.18 | 427.77 | 1082.84 | 0.00 | 0.00 | 0.00 |
November | 126.30 | 44.21 | 82.09 | 11.52 | 2017.91 | 0.00 | 0.00 | 0.00 |
December | 18.05 | 4.34 | 13.71 | 0.00 | 2252.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1226.53 | 601.97 | 624.56 | 1216.51 | 1065.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.05 | 4.34 | 13.71 | 0.00 | 183.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2621.49 | 1475.23 | 1288.83 | 2807.87 | 2252.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 568.55 | 374.32 | 194.23 | 336.58 | 2893.46 | 0.00 | 0.00 | 0.00 |
February | 1957.01 | 1360.67 | 596.34 | 1654.22 | 2318.36 | 0.00 | 0.00 | 0.00 |
March | 3362.42 | 2278.53 | 1083.89 | 3250.29 | 1775.65 | 0.00 | 0.00 | 0.00 |
April | 4104.31 | 2553.35 | 1550.96 | 4393.52 | 1168.70 | 0.00 | 0.00 | 0.00 |
May | 3385.82 | 1755.15 | 1630.67 | 3717.82 | 640.87 | 0.00 | 0.00 | 0.00 |
June | 3091.59 | 1268.14 | 1823.45 | 3483.74 | 347.15 | 0.00 | 0.00 | 0.00 |
July | 2978.42 | 1297.88 | 1680.55 | 3437.85 | 369.42 | 0.00 | 0.00 | 0.00 |
August | 3083.54 | 1699.61 | 1383.93 | 3513.07 | 539.56 | 0.00 | 0.00 | 0.00 |
September | 2491.02 | 1499.97 | 991.05 | 2596.63 | 921.19 | 0.00 | 0.00 | 0.00 |
October | 1792.60 | 1136.84 | 655.76 | 1627.13 | 1508.62 | 0.00 | 0.00 | 0.00 |
November | 960.61 | 670.37 | 290.24 | 643.58 | 2689.47 | 0.00 | 0.00 | 0.00 |
December | 170.47 | 120.08 | 50.39 | 31.66 | 3227.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2328.27 | 1332.57 | 995.70 | 2392.30 | 1529.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.47 | 120.08 | 50.39 | 31.66 | 347.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4104.31 | 2553.35 | 1823.45 | 4393.52 | 3227.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 7.86 | 36.02 | 0.00 | 2126.15 | 0.00 | 0.00 | 0.00 |
February | 258.98 | 90.17 | 168.81 | 56.11 | 1797.60 | 0.00 | 0.00 | 0.00 |
March | 776.93 | 334.07 | 442.86 | 449.58 | 1291.67 | 0.00 | 0.00 | 0.00 |
April | 1842.67 | 954.60 | 888.07 | 1744.41 | 750.31 | 0.00 | 0.00 | 0.00 |
May | 1791.75 | 815.68 | 976.07 | 1789.48 | 393.41 | 0.00 | 0.00 | 0.00 |
June | 1963.84 | 837.09 | 1126.74 | 2119.66 | 215.26 | 0.00 | 0.00 | 0.00 |
July | 1643.22 | 621.40 | 1021.81 | 1790.20 | 232.60 | 0.00 | 0.00 | 0.00 |
August | 1350.52 | 571.73 | 778.79 | 1402.63 | 342.91 | 0.00 | 0.00 | 0.00 |
September | 817.46 | 342.30 | 475.16 | 673.96 | 611.13 | 0.00 | 0.00 | 0.00 |
October | 320.29 | 96.39 | 223.91 | 125.95 | 1126.66 | 0.00 | 0.00 | 0.00 |
November | 128.21 | 46.66 | 81.55 | 15.39 | 2012.70 | 0.00 | 0.00 | 0.00 |
December | 11.51 | 1.22 | 10.29 | 0.00 | 2260.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 914.79 | 394.09 | 520.70 | 850.59 | 1093.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.51 | 1.22 | 10.29 | 0.00 | 215.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1963.84 | 954.60 | 1126.74 | 2119.66 | 2260.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.82 | 0.00 | 15.82 | 0.00 | 1077.36 | 0.00 | 0.00 | 0.00 |
February | 69.92 | 0.00 | 69.92 | 0.00 | 955.40 | 0.00 | 0.00 | 0.00 |
March | 187.01 | 0.00 | 187.01 | 19.61 | 701.75 | 0.00 | 0.00 | 0.00 |
April | 338.41 | 7.49 | 330.91 | 152.65 | 371.71 | 0.00 | 0.00 | 0.00 |
May | 518.79 | 82.65 | 436.14 | 412.48 | 167.11 | 0.00 | 0.00 | 0.00 |
June | 676.78 | 150.63 | 526.15 | 661.11 | 78.43 | 0.00 | 0.00 | 0.00 |
July | 568.03 | 92.45 | 475.57 | 563.66 | 97.54 | 0.00 | 0.00 | 0.00 |
August | 362.69 | 20.34 | 342.35 | 293.53 | 166.45 | 0.00 | 0.00 | 0.00 |
September | 202.30 | 0.21 | 202.09 | 76.99 | 338.60 | 0.00 | 0.00 | 0.00 |
October | 98.44 | 0.00 | 98.44 | 7.31 | 625.30 | 0.00 | 0.00 | 0.00 |
November | 30.55 | 0.00 | 30.55 | 0.00 | 1070.33 | 0.00 | 0.00 | 0.00 |
December | 4.80 | 0.00 | 4.80 | 0.00 | 1143.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.05 | 29.61 | 227.43 | 183.33 | 564.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.80 | 0.00 | 4.80 | 0.00 | 78.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 676.78 | 150.63 | 526.15 | 661.11 | 1143.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.82 | 0.00 | 15.82 | 0.00 | 1077.43 | 0.00 | 0.00 | 0.00 |
February | 69.93 | 0.00 | 69.93 | 0.00 | 955.46 | 0.00 | 0.00 | 0.00 |
March | 187.02 | 0.00 | 187.02 | 19.60 | 701.80 | 0.00 | 0.00 | 0.00 |
April | 338.42 | 7.50 | 330.93 | 152.65 | 371.73 | 0.00 | 0.00 | 0.00 |
May | 518.81 | 82.65 | 436.16 | 412.49 | 167.12 | 0.00 | 0.00 | 0.00 |
June | 676.80 | 150.64 | 526.17 | 661.13 | 78.43 | 0.00 | 0.00 | 0.00 |
July | 568.05 | 92.45 | 475.59 | 563.67 | 97.54 | 0.00 | 0.00 | 0.00 |
August | 362.71 | 20.34 | 342.36 | 293.54 | 166.46 | 0.00 | 0.00 | 0.00 |
September | 202.31 | 0.21 | 202.10 | 76.99 | 338.62 | 0.00 | 0.00 | 0.00 |
October | 98.44 | 0.00 | 98.44 | 7.31 | 625.35 | 0.00 | 0.00 | 0.00 |
November | 30.55 | 0.00 | 30.55 | 0.00 | 1070.39 | 0.00 | 0.00 | 0.00 |
December | 4.80 | 0.00 | 4.80 | 0.00 | 1143.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.06 | 29.61 | 227.44 | 183.34 | 564.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.80 | 0.00 | 4.80 | 0.00 | 78.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 676.80 | 150.64 | 526.17 | 661.13 | 1143.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.82 | 0.00 | 15.82 | 0.00 | 1077.43 | 0.00 | 0.00 | 0.00 |
February | 69.93 | 0.00 | 69.93 | 0.00 | 955.46 | 0.00 | 0.00 | 0.00 |
March | 187.02 | 0.00 | 187.02 | 19.60 | 701.80 | 0.00 | 0.00 | 0.00 |
April | 338.42 | 7.50 | 330.93 | 152.65 | 371.73 | 0.00 | 0.00 | 0.00 |
May | 518.81 | 82.65 | 436.16 | 412.49 | 167.12 | 0.00 | 0.00 | 0.00 |
June | 676.80 | 150.64 | 526.17 | 661.13 | 78.43 | 0.00 | 0.00 | 0.00 |
July | 568.05 | 92.45 | 475.59 | 563.67 | 97.54 | 0.00 | 0.00 | 0.00 |
August | 362.71 | 20.34 | 342.36 | 293.54 | 166.46 | 0.00 | 0.00 | 0.00 |
September | 202.31 | 0.21 | 202.10 | 76.99 | 338.62 | 0.00 | 0.00 | 0.00 |
October | 98.44 | 0.00 | 98.44 | 7.31 | 625.35 | 0.00 | 0.00 | 0.00 |
November | 30.55 | 0.00 | 30.55 | 0.00 | 1070.39 | 0.00 | 0.00 | 0.00 |
December | 4.80 | 0.00 | 4.80 | 0.00 | 1143.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.06 | 29.61 | 227.44 | 183.34 | 564.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.80 | 0.00 | 4.80 | 0.00 | 78.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 676.80 | 150.64 | 526.17 | 661.13 | 1143.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.25 | 25.31 | 54.94 | 8.01 | 2010.48 | 0.00 | 0.00 | 0.00 |
February | 443.15 | 211.56 | 231.59 | 239.45 | 1666.59 | 0.00 | 0.00 | 0.00 |
March | 1263.22 | 639.59 | 623.64 | 1068.92 | 1229.17 | 0.00 | 0.00 | 0.00 |
April | 1736.15 | 878.03 | 858.12 | 1598.50 | 687.30 | 0.00 | 0.00 | 0.00 |
May | 2521.74 | 1419.09 | 1102.65 | 2713.56 | 368.13 | 0.00 | 0.00 | 0.00 |
June | 2320.55 | 1080.75 | 1239.79 | 2577.51 | 180.09 | 0.00 | 0.00 | 0.00 |
July | 2204.06 | 1066.96 | 1137.11 | 2500.80 | 210.82 | 0.00 | 0.00 | 0.00 |
August | 1745.64 | 848.58 | 897.06 | 1894.09 | 334.72 | 0.00 | 0.00 | 0.00 |
September | 1080.07 | 472.65 | 607.42 | 982.00 | 628.74 | 0.00 | 0.00 | 0.00 |
October | 570.70 | 229.04 | 341.66 | 403.49 | 1105.62 | 0.00 | 0.00 | 0.00 |
November | 121.49 | 42.53 | 78.97 | 10.81 | 1978.81 | 0.00 | 0.00 | 0.00 |
December | 17.36 | 4.17 | 13.19 | 0.00 | 2184.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1179.86 | 579.06 | 600.80 | 1172.67 | 1045.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.36 | 4.17 | 13.19 | 0.00 | 180.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2521.74 | 1419.09 | 1239.79 | 2713.56 | 2184.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3.17 | 1.00 | 2.17 | 0.32 | 79.49 | 0.00 | 0.00 | 0.00 |
February | 17.52 | 8.36 | 9.16 | 9.47 | 65.90 | 0.00 | 0.00 | 0.00 |
March | 49.95 | 25.29 | 24.66 | 42.26 | 48.60 | 0.00 | 0.00 | 0.00 |
April | 68.65 | 34.72 | 33.93 | 63.20 | 27.18 | 0.00 | 0.00 | 0.00 |
May | 99.71 | 56.11 | 43.60 | 107.29 | 14.56 | 0.00 | 0.00 | 0.00 |
June | 91.75 | 42.73 | 49.02 | 101.91 | 7.12 | 0.00 | 0.00 | 0.00 |
July | 87.15 | 42.19 | 44.96 | 98.88 | 8.34 | 0.00 | 0.00 | 0.00 |
August | 69.02 | 33.55 | 35.47 | 74.89 | 13.23 | 0.00 | 0.00 | 0.00 |
September | 42.71 | 18.69 | 24.02 | 38.83 | 24.86 | 0.00 | 0.00 | 0.00 |
October | 22.56 | 9.06 | 13.51 | 15.95 | 43.72 | 0.00 | 0.00 | 0.00 |
November | 4.80 | 1.68 | 3.12 | 0.43 | 78.24 | 0.00 | 0.00 | 0.00 |
December | 0.69 | 0.17 | 0.52 | 0.00 | 86.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.65 | 22.90 | 23.76 | 46.37 | 41.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.69 | 0.17 | 0.52 | 0.00 | 7.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.71 | 56.11 | 49.02 | 107.29 | 86.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.51 | 124.77 | 64.74 | 116.27 | 935.31 | 0.00 | 0.00 | 0.00 |
February | 652.32 | 453.55 | 198.78 | 561.24 | 760.25 | 0.00 | 0.00 | 0.00 |
March | 1120.79 | 759.49 | 361.29 | 1101.44 | 593.93 | 0.00 | 0.00 | 0.00 |
April | 1368.08 | 851.10 | 516.98 | 1476.67 | 406.88 | 0.00 | 0.00 | 0.00 |
May | 1128.59 | 585.04 | 543.55 | 1250.99 | 220.38 | 0.00 | 0.00 | 0.00 |
June | 1030.51 | 422.71 | 607.81 | 1171.45 | 118.00 | 0.00 | 0.00 | 0.00 |
July | 992.79 | 432.62 | 560.18 | 1151.90 | 128.25 | 0.00 | 0.00 | 0.00 |
August | 1027.83 | 566.53 | 461.30 | 1174.27 | 193.50 | 0.00 | 0.00 | 0.00 |
September | 830.33 | 499.98 | 330.35 | 863.66 | 335.12 | 0.00 | 0.00 | 0.00 |
October | 597.52 | 378.94 | 218.58 | 540.64 | 530.77 | 0.00 | 0.00 | 0.00 |
November | 320.20 | 223.45 | 96.74 | 218.70 | 892.06 | 0.00 | 0.00 | 0.00 |
December | 56.82 | 40.03 | 16.80 | 12.63 | 1044.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 776.08 | 444.18 | 331.90 | 803.89 | 512.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.82 | 40.03 | 16.80 | 12.63 | 118.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1368.08 | 851.10 | 607.81 | 1476.67 | 1044.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.51 | 124.77 | 64.74 | 116.27 | 935.31 | 0.00 | 0.00 | 0.00 |
February | 652.32 | 453.55 | 198.78 | 561.24 | 760.25 | 0.00 | 0.00 | 0.00 |
March | 1120.79 | 759.49 | 361.29 | 1101.44 | 593.93 | 0.00 | 0.00 | 0.00 |
April | 1368.08 | 851.10 | 516.98 | 1476.67 | 406.88 | 0.00 | 0.00 | 0.00 |
May | 1128.59 | 585.04 | 543.55 | 1250.99 | 220.38 | 0.00 | 0.00 | 0.00 |
June | 1030.51 | 422.71 | 607.81 | 1171.45 | 118.00 | 0.00 | 0.00 | 0.00 |
July | 992.79 | 432.62 | 560.18 | 1151.90 | 128.25 | 0.00 | 0.00 | 0.00 |
August | 1027.83 | 566.53 | 461.30 | 1174.27 | 193.50 | 0.00 | 0.00 | 0.00 |
September | 830.33 | 499.98 | 330.35 | 863.66 | 335.12 | 0.00 | 0.00 | 0.00 |
October | 597.52 | 378.94 | 218.58 | 540.64 | 530.77 | 0.00 | 0.00 | 0.00 |
November | 320.20 | 223.45 | 96.74 | 218.70 | 892.06 | 0.00 | 0.00 | 0.00 |
December | 56.82 | 40.03 | 16.80 | 12.63 | 1044.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 776.08 | 444.18 | 331.90 | 803.89 | 512.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.82 | 40.03 | 16.80 | 12.63 | 118.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1368.08 | 851.10 | 607.81 | 1476.67 | 1044.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.50 | 124.76 | 64.74 | 116.26 | 935.25 | 0.00 | 0.00 | 0.00 |
February | 652.28 | 453.52 | 198.76 | 561.20 | 760.20 | 0.00 | 0.00 | 0.00 |
March | 1120.71 | 759.45 | 361.27 | 1101.37 | 593.89 | 0.00 | 0.00 | 0.00 |
April | 1367.99 | 851.05 | 516.95 | 1476.58 | 406.86 | 0.00 | 0.00 | 0.00 |
May | 1128.52 | 585.00 | 543.52 | 1250.91 | 220.36 | 0.00 | 0.00 | 0.00 |
June | 1030.45 | 422.68 | 607.77 | 1171.37 | 117.99 | 0.00 | 0.00 | 0.00 |
July | 992.73 | 432.59 | 560.14 | 1151.82 | 128.24 | 0.00 | 0.00 | 0.00 |
August | 1027.77 | 566.49 | 461.28 | 1174.20 | 193.48 | 0.00 | 0.00 | 0.00 |
September | 830.27 | 499.95 | 330.33 | 863.61 | 335.09 | 0.00 | 0.00 | 0.00 |
October | 597.48 | 378.92 | 218.57 | 540.60 | 530.74 | 0.00 | 0.00 | 0.00 |
November | 320.18 | 223.44 | 96.74 | 218.69 | 892.00 | 0.00 | 0.00 | 0.00 |
December | 56.82 | 40.02 | 16.80 | 12.62 | 1044.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 776.03 | 444.15 | 331.87 | 803.84 | 511.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.82 | 40.02 | 16.80 | 12.62 | 117.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1367.99 | 851.05 | 607.77 | 1476.58 | 1044.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 42.21 | 7.56 | 34.65 | 0.00 | 2051.28 | 0.00 | 0.00 | 0.00 |
February | 249.12 | 86.74 | 162.39 | 55.27 | 1728.92 | 0.00 | 0.00 | 0.00 |
March | 747.37 | 321.36 | 426.01 | 441.65 | 1247.75 | 0.00 | 0.00 | 0.00 |
April | 1772.56 | 918.27 | 854.28 | 1694.22 | 741.88 | 0.00 | 0.00 | 0.00 |
May | 1723.58 | 784.64 | 938.94 | 1739.12 | 383.79 | 0.00 | 0.00 | 0.00 |
June | 1889.12 | 805.24 | 1083.88 | 2054.16 | 209.24 | 0.00 | 0.00 | 0.00 |
July | 1580.70 | 597.76 | 982.94 | 1730.63 | 228.92 | 0.00 | 0.00 | 0.00 |
August | 1299.13 | 549.97 | 749.16 | 1346.60 | 350.02 | 0.00 | 0.00 | 0.00 |
September | 786.35 | 329.27 | 457.08 | 636.57 | 636.85 | 0.00 | 0.00 | 0.00 |
October | 308.11 | 92.72 | 215.39 | 116.43 | 1143.29 | 0.00 | 0.00 | 0.00 |
November | 123.33 | 44.88 | 78.45 | 14.44 | 1974.89 | 0.00 | 0.00 | 0.00 |
December | 11.07 | 1.17 | 9.90 | 0.00 | 2191.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 879.98 | 379.09 | 500.89 | 822.29 | 1070.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.07 | 1.17 | 9.90 | 0.00 | 209.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1889.12 | 918.27 | 1083.88 | 2054.16 | 2191.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.67 | 0.30 | 1.37 | 0.00 | 81.11 | 0.00 | 0.00 | 0.00 |
February | 9.85 | 3.43 | 6.42 | 2.19 | 68.36 | 0.00 | 0.00 | 0.00 |
March | 29.55 | 12.71 | 16.84 | 17.46 | 49.33 | 0.00 | 0.00 | 0.00 |
April | 70.09 | 36.31 | 33.78 | 66.99 | 29.33 | 0.00 | 0.00 | 0.00 |
May | 68.15 | 31.02 | 37.12 | 68.76 | 15.17 | 0.00 | 0.00 | 0.00 |
June | 74.69 | 31.84 | 42.86 | 81.22 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 62.50 | 23.63 | 38.86 | 68.43 | 9.05 | 0.00 | 0.00 | 0.00 |
August | 51.37 | 21.75 | 29.62 | 53.24 | 13.84 | 0.00 | 0.00 | 0.00 |
September | 31.09 | 13.02 | 18.07 | 25.17 | 25.18 | 0.00 | 0.00 | 0.00 |
October | 12.18 | 3.67 | 8.52 | 4.60 | 45.20 | 0.00 | 0.00 | 0.00 |
November | 4.88 | 1.77 | 3.10 | 0.57 | 78.09 | 0.00 | 0.00 | 0.00 |
December | 0.44 | 0.05 | 0.39 | 0.00 | 86.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.79 | 14.99 | 19.80 | 32.51 | 42.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.44 | 0.05 | 0.39 | 0.00 | 8.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.69 | 36.31 | 42.86 | 81.22 | 86.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 47.46 | 0.00 | 47.46 | 0.00 | 3279.55 | 0.00 | 0.00 | 0.00 |
February | 209.78 | 0.00 | 209.78 | 0.00 | 2933.46 | 0.00 | 0.00 | 0.00 |
March | 561.07 | 0.00 | 561.07 | 51.35 | 2178.49 | 0.00 | 0.00 | 0.00 |
April | 1015.27 | 22.49 | 992.78 | 406.84 | 1188.31 | 0.00 | 0.00 | 0.00 |
May | 1556.45 | 247.95 | 1308.49 | 1171.56 | 536.65 | 0.00 | 0.00 | 0.00 |
June | 2030.44 | 451.92 | 1578.52 | 1941.91 | 249.49 | 0.00 | 0.00 | 0.00 |
July | 1704.16 | 277.37 | 1426.79 | 1663.95 | 303.85 | 0.00 | 0.00 | 0.00 |
August | 1088.13 | 61.03 | 1027.09 | 866.20 | 508.19 | 0.00 | 0.00 | 0.00 |
September | 606.93 | 0.62 | 606.31 | 223.73 | 1020.01 | 0.00 | 0.00 | 0.00 |
October | 295.32 | 0.00 | 295.32 | 21.09 | 1869.79 | 0.00 | 0.00 | 0.00 |
November | 91.65 | 0.00 | 91.65 | 0.00 | 3214.33 | 0.00 | 0.00 | 0.00 |
December | 14.40 | 0.00 | 14.40 | 0.00 | 3456.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.17 | 88.84 | 682.33 | 531.98 | 1721.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.40 | 0.00 | 14.40 | 0.00 | 249.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2030.44 | 451.92 | 1578.52 | 1941.91 | 3456.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.43 | 26.32 | 57.11 | 7.86 | 2118.37 | 0.00 | 0.00 | 0.00 |
February | 460.68 | 219.93 | 240.75 | 243.51 | 1769.00 | 0.00 | 0.00 | 0.00 |
March | 1313.19 | 664.89 | 648.30 | 1091.33 | 1309.37 | 0.00 | 0.00 | 0.00 |
April | 1804.83 | 912.77 | 892.06 | 1633.19 | 731.98 | 0.00 | 0.00 | 0.00 |
May | 2621.49 | 1475.23 | 1146.27 | 2798.67 | 384.68 | 0.00 | 0.00 | 0.00 |
June | 2412.34 | 1123.51 | 1288.83 | 2661.73 | 189.48 | 0.00 | 0.00 | 0.00 |
July | 2291.25 | 1109.16 | 1182.08 | 2589.83 | 217.24 | 0.00 | 0.00 | 0.00 |
August | 1814.69 | 882.15 | 932.54 | 1963.98 | 340.43 | 0.00 | 0.00 | 0.00 |
September | 1122.79 | 491.35 | 631.45 | 1021.21 | 636.06 | 0.00 | 0.00 | 0.00 |
October | 593.28 | 238.10 | 355.18 | 418.16 | 1135.42 | 0.00 | 0.00 | 0.00 |
November | 126.30 | 44.21 | 82.09 | 11.01 | 2059.64 | 0.00 | 0.00 | 0.00 |
December | 18.05 | 4.34 | 13.71 | 0.00 | 2287.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1226.53 | 601.97 | 624.56 | 1209.85 | 1094.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.05 | 4.34 | 13.71 | 0.00 | 189.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2621.49 | 1475.23 | 1288.83 | 2798.67 | 2287.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 568.55 | 374.32 | 194.23 | 332.87 | 2944.51 | 0.00 | 0.00 | 0.00 |
February | 1957.01 | 1360.67 | 596.34 | 1640.59 | 2376.61 | 0.00 | 0.00 | 0.00 |
March | 3362.42 | 2278.53 | 1083.89 | 3232.61 | 1840.63 | 0.00 | 0.00 | 0.00 |
April | 4104.31 | 2553.35 | 1550.96 | 4376.58 | 1226.66 | 0.00 | 0.00 | 0.00 |
May | 3385.82 | 1755.15 | 1630.67 | 3708.21 | 672.72 | 0.00 | 0.00 | 0.00 |
June | 3091.59 | 1268.14 | 1823.45 | 3480.15 | 360.81 | 0.00 | 0.00 | 0.00 |
July | 2978.42 | 1297.88 | 1680.55 | 3433.64 | 383.89 | 0.00 | 0.00 | 0.00 |
August | 3083.54 | 1699.61 | 1383.93 | 3504.95 | 565.67 | 0.00 | 0.00 | 0.00 |
September | 2491.02 | 1499.97 | 991.05 | 2575.17 | 979.89 | 0.00 | 0.00 | 0.00 |
October | 1792.60 | 1136.84 | 655.76 | 1605.38 | 1585.58 | 0.00 | 0.00 | 0.00 |
November | 960.61 | 670.37 | 290.24 | 635.49 | 2752.55 | 0.00 | 0.00 | 0.00 |
December | 170.47 | 120.08 | 50.39 | 31.11 | 3281.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2328.27 | 1332.57 | 995.70 | 2381.56 | 1577.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.47 | 120.08 | 50.39 | 31.11 | 360.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4104.31 | 2553.35 | 1823.45 | 4376.58 | 3281.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.88 | 7.86 | 36.02 | 0.00 | 2160.29 | 0.00 | 0.00 | 0.00 |
February | 258.98 | 90.17 | 168.81 | 55.01 | 1835.87 | 0.00 | 0.00 | 0.00 |
March | 776.93 | 334.07 | 442.86 | 444.01 | 1336.17 | 0.00 | 0.00 | 0.00 |
April | 1842.67 | 954.60 | 888.07 | 1731.72 | 790.18 | 0.00 | 0.00 | 0.00 |
May | 1791.75 | 815.68 | 976.07 | 1779.38 | 413.84 | 0.00 | 0.00 | 0.00 |
June | 1963.84 | 837.09 | 1126.74 | 2116.27 | 223.72 | 0.00 | 0.00 | 0.00 |
July | 1643.22 | 621.40 | 1021.81 | 1786.23 | 241.89 | 0.00 | 0.00 | 0.00 |
August | 1350.52 | 571.73 | 778.79 | 1394.30 | 360.40 | 0.00 | 0.00 | 0.00 |
September | 817.46 | 342.30 | 475.16 | 659.79 | 652.89 | 0.00 | 0.00 | 0.00 |
October | 320.29 | 96.39 | 223.91 | 120.04 | 1181.15 | 0.00 | 0.00 | 0.00 |
November | 128.21 | 46.66 | 81.55 | 14.80 | 2054.26 | 0.00 | 0.00 | 0.00 |
December | 11.51 | 1.22 | 10.29 | 0.00 | 2295.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 914.79 | 394.09 | 520.70 | 845.10 | 1125.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.51 | 1.22 | 10.29 | 0.00 | 223.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1963.84 | 954.60 | 1126.74 | 2116.27 | 2295.18 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127107E+09 | 0.00 | 0.127107E+09 | 0.00 | 0.863728E+10 |
February | 0.507498E+09 | 0.00 | 0.507498E+09 | 0.00 | 0.694912E+10 |
March | 0.150277E+10 | 0.00 | 0.150277E+10 | 0.149569E+09 | 0.564483E+10 |
April | 0.263158E+10 | 58283651.85 | 0.257329E+10 | 0.110955E+10 | 0.291117E+10 |
May | 0.416878E+10 | 0.664116E+09 | 0.350467E+10 | 0.320036E+10 | 0.137680E+10 |
June | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.505345E+10 | 0.625229E+09 |
July | 0.456441E+10 | 0.742901E+09 | 0.382151E+10 | 0.447716E+10 | 0.787138E+09 |
August | 0.291444E+10 | 0.163474E+09 | 0.275096E+10 | 0.235874E+10 | 0.129832E+10 |
September | 0.157316E+10 | 1601027.85 | 0.157156E+10 | 0.635069E+09 | 0.245955E+10 |
October | 0.790989E+09 | 0.00 | 0.790989E+09 | 72026982.33 | 0.477539E+10 |
November | 0.237554E+09 | 0.00 | 0.237554E+09 | 0.00 | 0.815944E+10 |
December | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.910431E+10 |
Annual Sum or Average | 0.243197E+11 | 0.280175E+10 | 0.215180E+11 | 0.170559E+11 | 0.527286E+11 |
Minimum of Months | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.625229E+09 |
Maximum of Months | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.505345E+10 | 0.910431E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223457E+09 | 70483684.60 | 0.152974E+09 | 21589275.52 | 0.558214E+10 |
February | 0.111448E+10 | 0.532056E+09 | 0.582424E+09 | 0.598144E+09 | 0.418914E+10 |
March | 0.351725E+10 | 0.178084E+10 | 0.173641E+10 | 0.295174E+10 | 0.339314E+10 |
April | 0.467811E+10 | 0.236590E+10 | 0.231222E+10 | 0.427550E+10 | 0.180667E+10 |
May | 0.702140E+10 | 0.395124E+10 | 0.307016E+10 | 0.752059E+10 | 0.992297E+09 |
June | 0.625278E+10 | 0.291213E+10 | 0.334065E+10 | 0.690797E+10 | 0.476542E+09 |
July | 0.613688E+10 | 0.297078E+10 | 0.316609E+10 | 0.694582E+10 | 0.564368E+09 |
August | 0.486046E+10 | 0.236274E+10 | 0.249772E+10 | 0.527806E+10 | 0.875138E+09 |
September | 0.291028E+10 | 0.127357E+10 | 0.163671E+10 | 0.268881E+10 | 0.155001E+10 |
October | 0.158903E+10 | 0.637719E+09 | 0.951310E+09 | 0.114575E+10 | 0.290029E+10 |
November | 0.327370E+09 | 0.114592E+09 | 0.212778E+09 | 29847996.05 | 0.523042E+10 |
December | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.603360E+10 |
Annual Sum or Average | 0.386799E+11 | 0.189837E+11 | 0.196962E+11 | 0.383638E+11 | 0.335938E+11 |
Minimum of Months | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.476542E+09 |
Maximum of Months | 0.702140E+10 | 0.395124E+10 | 0.334065E+10 | 0.752059E+10 | 0.603360E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152281E+10 | 0.100257E+10 | 0.520235E+09 | 0.901504E+09 | 0.774984E+10 |
February | 0.473440E+10 | 0.329173E+10 | 0.144266E+10 | 0.400189E+10 | 0.560857E+10 |
March | 0.900590E+10 | 0.610281E+10 | 0.290309E+10 | 0.870556E+10 | 0.475589E+10 |
April | 0.106384E+11 | 0.661829E+10 | 0.402008E+10 | 0.113880E+11 | 0.302927E+10 |
May | 0.906857E+10 | 0.470099E+10 | 0.436759E+10 | 0.995781E+10 | 0.171650E+10 |
June | 0.801340E+10 | 0.328703E+10 | 0.472637E+10 | 0.902985E+10 | 0.899812E+09 |
July | 0.797741E+10 | 0.347624E+10 | 0.450117E+10 | 0.920794E+10 | 0.989453E+09 |
August | 0.825896E+10 | 0.455224E+10 | 0.370672E+10 | 0.940941E+10 | 0.144515E+10 |
September | 0.645673E+10 | 0.388792E+10 | 0.256881E+10 | 0.673045E+10 | 0.238773E+10 |
October | 0.480130E+10 | 0.304492E+10 | 0.175638E+10 | 0.435810E+10 | 0.404070E+10 |
November | 0.248989E+10 | 0.173759E+10 | 0.752300E+09 | 0.166817E+10 | 0.697112E+10 |
December | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 84803649.68 | 0.864399E+10 |
Annual Sum or Average | 0.734243E+11 | 0.420240E+11 | 0.314004E+11 | 0.754435E+11 | 0.482380E+11 |
Minimum of Months | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 84803649.68 | 0.899812E+09 |
Maximum of Months | 0.106384E+11 | 0.661829E+10 | 0.472637E+10 | 0.113880E+11 | 0.864399E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117518E+09 | 21048844.41 | 96468734.51 | 0.00 | 0.569469E+10 |
February | 0.626513E+09 | 0.218131E+09 | 0.408383E+09 | 0.135746E+09 | 0.434874E+10 |
March | 0.208093E+10 | 0.894767E+09 | 0.118616E+10 | 0.120416E+10 | 0.345962E+10 |
April | 0.477620E+10 | 0.247432E+10 | 0.230188E+10 | 0.452152E+10 | 0.194480E+10 |
May | 0.479903E+10 | 0.218472E+10 | 0.261431E+10 | 0.479293E+10 | 0.105371E+10 |
June | 0.509027E+10 | 0.216974E+10 | 0.292052E+10 | 0.549415E+10 | 0.557956E+09 |
July | 0.440119E+10 | 0.166437E+10 | 0.273682E+10 | 0.479487E+10 | 0.622991E+09 |
August | 0.361723E+10 | 0.153131E+10 | 0.208592E+10 | 0.375681E+10 | 0.918442E+09 |
September | 0.211885E+10 | 0.887238E+09 | 0.123161E+10 | 0.174690E+10 | 0.158404E+10 |
October | 0.857874E+09 | 0.258166E+09 | 0.599709E+09 | 0.337341E+09 | 0.301765E+10 |
November | 0.332319E+09 | 0.120932E+09 | 0.211387E+09 | 39902076.73 | 0.521691E+10 |
December | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.605405E+10 |
Annual Sum or Average | 0.288487E+11 | 0.124280E+11 | 0.164207E+11 | 0.268243E+11 | 0.344736E+11 |
Minimum of Months | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.557956E+09 |
Maximum of Months | 0.509027E+10 | 0.247432E+10 | 0.292052E+10 | 0.549415E+10 | 0.605405E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42366959.34 | 0.00 | 42366959.34 | 0.00 | 0.288561E+10 |
February | 0.169158E+09 | 0.00 | 0.169158E+09 | 0.00 | 0.231130E+10 |
March | 0.500899E+09 | 0.00 | 0.500899E+09 | 52511360.83 | 0.187958E+10 |
April | 0.877151E+09 | 19426964.78 | 0.857724E+09 | 0.395656E+09 | 0.963472E+09 |
May | 0.138953E+10 | 0.221362E+09 | 0.116817E+10 | 0.110479E+10 | 0.447593E+09 |
June | 0.175421E+10 | 0.390440E+09 | 0.136377E+10 | 0.171359E+10 | 0.203281E+09 |
July | 0.152140E+10 | 0.247622E+09 | 0.127378E+10 | 0.150970E+10 | 0.261248E+09 |
August | 0.971433E+09 | 54488644.33 | 0.916945E+09 | 0.786199E+09 | 0.445822E+09 |
September | 0.524361E+09 | 533650.70 | 0.523828E+09 | 0.199565E+09 | 0.877641E+09 |
October | 0.263651E+09 | 0.00 | 0.263651E+09 | 19590232.52 | 0.167482E+10 |
November | 79180827.52 | 0.00 | 79180827.52 | 0.00 | 0.277429E+10 |
December | 12851923.53 | 0.00 | 12851923.53 | 0.00 | 0.306209E+10 |
Annual Sum or Average | 0.810619E+10 | 0.933872E+09 | 0.717232E+10 | 0.578161E+10 | 0.177867E+11 |
Minimum of Months | 12851923.53 | 0.00 | 12851923.53 | 0.00 | 0.203281E+09 |
Maximum of Months | 0.175421E+10 | 0.390440E+09 | 0.136377E+10 | 0.171359E+10 | 0.306209E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42368450.28 | 0.00 | 42368450.28 | 0.00 | 0.288579E+10 |
February | 0.169164E+09 | 0.00 | 0.169164E+09 | 0.00 | 0.231145E+10 |
March | 0.500919E+09 | 0.00 | 0.500919E+09 | 52509330.08 | 0.187970E+10 |
April | 0.877186E+09 | 19427486.98 | 0.857758E+09 | 0.395663E+09 | 0.963536E+09 |
May | 0.138958E+10 | 0.221368E+09 | 0.116821E+10 | 0.110482E+10 | 0.447621E+09 |
June | 0.175428E+10 | 0.390450E+09 | 0.136383E+10 | 0.171364E+10 | 0.203293E+09 |
July | 0.152145E+10 | 0.247629E+09 | 0.127382E+10 | 0.150975E+10 | 0.261264E+09 |
August | 0.971470E+09 | 54490109.00 | 0.916980E+09 | 0.786220E+09 | 0.445850E+09 |
September | 0.524381E+09 | 533665.05 | 0.523848E+09 | 0.199567E+09 | 0.877697E+09 |
October | 0.263660E+09 | 0.00 | 0.263660E+09 | 19589503.94 | 0.167492E+10 |
November | 79183614.03 | 0.00 | 79183614.03 | 0.00 | 0.277446E+10 |
December | 12852360.03 | 0.00 | 12852360.03 | 0.00 | 0.306228E+10 |
Annual Sum or Average | 0.810649E+10 | 0.933897E+09 | 0.717259E+10 | 0.578175E+10 | 0.177879E+11 |
Minimum of Months | 12852360.03 | 0.00 | 12852360.03 | 0.00 | 0.203293E+09 |
Maximum of Months | 0.175428E+10 | 0.390450E+09 | 0.136383E+10 | 0.171364E+10 | 0.306228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42368450.28 | 0.00 | 42368450.28 | 0.00 | 0.288579E+10 |
February | 0.169164E+09 | 0.00 | 0.169164E+09 | 0.00 | 0.231145E+10 |
March | 0.500919E+09 | 0.00 | 0.500919E+09 | 52509330.08 | 0.187970E+10 |
April | 0.877186E+09 | 19427486.98 | 0.857758E+09 | 0.395663E+09 | 0.963536E+09 |
May | 0.138958E+10 | 0.221368E+09 | 0.116821E+10 | 0.110482E+10 | 0.447621E+09 |
June | 0.175428E+10 | 0.390450E+09 | 0.136383E+10 | 0.171364E+10 | 0.203293E+09 |
July | 0.152145E+10 | 0.247629E+09 | 0.127382E+10 | 0.150975E+10 | 0.261264E+09 |
August | 0.971470E+09 | 54490109.00 | 0.916980E+09 | 0.786220E+09 | 0.445850E+09 |
September | 0.524381E+09 | 533665.05 | 0.523848E+09 | 0.199567E+09 | 0.877697E+09 |
October | 0.263660E+09 | 0.00 | 0.263660E+09 | 19589503.94 | 0.167492E+10 |
November | 79183614.03 | 0.00 | 79183614.03 | 0.00 | 0.277446E+10 |
December | 12852360.03 | 0.00 | 12852360.03 | 0.00 | 0.306228E+10 |
Annual Sum or Average | 0.810649E+10 | 0.933897E+09 | 0.717259E+10 | 0.578175E+10 | 0.177879E+11 |
Minimum of Months | 12852360.03 | 0.00 | 12852360.03 | 0.00 | 0.203293E+09 |
Maximum of Months | 0.175428E+10 | 0.390450E+09 | 0.136383E+10 | 0.171364E+10 | 0.306228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214954E+09 | 67801495.75 | 0.147153E+09 | 21444537.73 | 0.538486E+10 |
February | 0.107207E+10 | 0.511809E+09 | 0.560262E+09 | 0.579284E+09 | 0.403182E+10 |
March | 0.338342E+10 | 0.171307E+10 | 0.167034E+10 | 0.286299E+10 | 0.329221E+10 |
April | 0.450010E+10 | 0.227586E+10 | 0.222424E+10 | 0.414331E+10 | 0.178149E+10 |
May | 0.675423E+10 | 0.380088E+10 | 0.295335E+10 | 0.726800E+10 | 0.986006E+09 |
June | 0.601486E+10 | 0.280131E+10 | 0.321354E+10 | 0.668091E+10 | 0.466787E+09 |
July | 0.590336E+10 | 0.285773E+10 | 0.304563E+10 | 0.669813E+10 | 0.564671E+09 |
August | 0.467551E+10 | 0.227283E+10 | 0.240268E+10 | 0.507313E+10 | 0.896521E+09 |
September | 0.279954E+10 | 0.122511E+10 | 0.157444E+10 | 0.254534E+10 | 0.162970E+10 |
October | 0.152856E+10 | 0.613452E+09 | 0.915112E+09 | 0.108070E+10 | 0.296129E+10 |
November | 0.314913E+09 | 0.110231E+09 | 0.204682E+09 | 28012374.98 | 0.512909E+10 |
December | 46507480.60 | 11178115.58 | 35329365.02 | 0.00 | 0.584974E+10 |
Annual Sum or Average | 0.372080E+11 | 0.182613E+11 | 0.189468E+11 | 0.369812E+11 | 0.329742E+11 |
Minimum of Months | 46507480.60 | 11178115.58 | 35329365.02 | 0.00 | 0.466787E+09 |
Maximum of Months | 0.675423E+10 | 0.380088E+10 | 0.321354E+10 | 0.726800E+10 | 0.584974E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 8499096.08 | 2680810.10 | 5818285.98 | 847897.71 | 0.212913E+09 |
February | 42388738.06 | 20236471.91 | 22152266.15 | 22904367.91 | 0.159415E+09 |
March | 0.133777E+09 | 67733295.94 | 66043905.92 | 0.113200E+09 | 0.130171E+09 |
April | 0.177930E+09 | 89985617.49 | 87944443.31 | 0.163823E+09 | 70438528.68 |
May | 0.267056E+09 | 0.150284E+09 | 0.116773E+09 | 0.287370E+09 | 38985805.84 |
June | 0.237822E+09 | 0.110761E+09 | 0.127061E+09 | 0.264157E+09 | 18456330.93 |
July | 0.233414E+09 | 0.112992E+09 | 0.120421E+09 | 0.264838E+09 | 22326574.98 |
August | 0.184865E+09 | 89865637.23 | 94999824.04 | 0.200587E+09 | 35447629.02 |
September | 0.110691E+09 | 48439594.68 | 62251794.84 | 0.100640E+09 | 64436957.98 |
October | 60438041.62 | 24255324.78 | 36182716.84 | 42729880.94 | 0.117087E+09 |
November | 12451391.56 | 4358439.52 | 8092952.04 | 1107584.09 | 0.202799E+09 |
December | 1838863.91 | 441972.63 | 1396891.28 | 0.00 | 0.231293E+09 |
Annual Sum or Average | 0.147117E+10 | 0.722034E+09 | 0.749138E+09 | 0.146221E+10 | 0.130377E+10 |
Minimum of Months | 1838863.91 | 441972.63 | 1396891.28 | 0.00 | 18456330.93 |
Maximum of Months | 0.267056E+09 | 0.150284E+09 | 0.127061E+09 | 0.287370E+09 | 0.231293E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507593E+09 | 0.334184E+09 | 0.173408E+09 | 0.311421E+09 | 0.250513E+10 |
February | 0.157810E+10 | 0.109722E+10 | 0.480880E+09 | 0.135774E+10 | 0.183919E+10 |
March | 0.300191E+10 | 0.203423E+10 | 0.967684E+09 | 0.295010E+10 | 0.159078E+10 |
April | 0.354606E+10 | 0.220605E+10 | 0.134001E+10 | 0.382753E+10 | 0.105464E+10 |
May | 0.302281E+10 | 0.156696E+10 | 0.145585E+10 | 0.335066E+10 | 0.590257E+09 |
June | 0.267109E+10 | 0.109565E+10 | 0.157544E+10 | 0.303639E+10 | 0.305855E+09 |
July | 0.265910E+10 | 0.115872E+10 | 0.150037E+10 | 0.308524E+10 | 0.343498E+09 |
August | 0.275294E+10 | 0.151738E+10 | 0.123556E+10 | 0.314517E+10 | 0.518258E+09 |
September | 0.215221E+10 | 0.129595E+10 | 0.856258E+09 | 0.223861E+10 | 0.868619E+09 |
October | 0.160040E+10 | 0.101495E+10 | 0.585450E+09 | 0.144804E+10 | 0.142162E+10 |
November | 0.829948E+09 | 0.579185E+09 | 0.250762E+09 | 0.566870E+09 | 0.231222E+10 |
December | 0.152196E+09 | 0.107206E+09 | 44989455.71 | 33816727.25 | 0.279692E+10 |
Annual Sum or Average | 0.244744E+11 | 0.140077E+11 | 0.104667E+11 | 0.253516E+11 | 0.161470E+11 |
Minimum of Months | 0.152196E+09 | 0.107206E+09 | 44989455.71 | 33816727.25 | 0.305855E+09 |
Maximum of Months | 0.354606E+10 | 0.220605E+10 | 0.157544E+10 | 0.382753E+10 | 0.279692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507593E+09 | 0.334184E+09 | 0.173408E+09 | 0.311421E+09 | 0.250513E+10 |
February | 0.157810E+10 | 0.109722E+10 | 0.480880E+09 | 0.135774E+10 | 0.183919E+10 |
March | 0.300191E+10 | 0.203423E+10 | 0.967684E+09 | 0.295010E+10 | 0.159078E+10 |
April | 0.354606E+10 | 0.220605E+10 | 0.134001E+10 | 0.382753E+10 | 0.105464E+10 |
May | 0.302281E+10 | 0.156696E+10 | 0.145585E+10 | 0.335066E+10 | 0.590257E+09 |
June | 0.267109E+10 | 0.109565E+10 | 0.157544E+10 | 0.303639E+10 | 0.305855E+09 |
July | 0.265910E+10 | 0.115872E+10 | 0.150037E+10 | 0.308524E+10 | 0.343498E+09 |
August | 0.275294E+10 | 0.151738E+10 | 0.123556E+10 | 0.314517E+10 | 0.518258E+09 |
September | 0.215221E+10 | 0.129595E+10 | 0.856258E+09 | 0.223861E+10 | 0.868619E+09 |
October | 0.160040E+10 | 0.101495E+10 | 0.585450E+09 | 0.144804E+10 | 0.142162E+10 |
November | 0.829948E+09 | 0.579185E+09 | 0.250762E+09 | 0.566870E+09 | 0.231222E+10 |
December | 0.152196E+09 | 0.107206E+09 | 44989455.71 | 33816727.25 | 0.279692E+10 |
Annual Sum or Average | 0.244744E+11 | 0.140077E+11 | 0.104667E+11 | 0.253516E+11 | 0.161470E+11 |
Minimum of Months | 0.152196E+09 | 0.107206E+09 | 44989455.71 | 33816727.25 | 0.305855E+09 |
Maximum of Months | 0.354606E+10 | 0.220605E+10 | 0.157544E+10 | 0.382753E+10 | 0.279692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507561E+09 | 0.334163E+09 | 0.173397E+09 | 0.311401E+09 | 0.250497E+10 |
February | 0.157800E+10 | 0.109715E+10 | 0.480849E+09 | 0.135766E+10 | 0.183908E+10 |
March | 0.300172E+10 | 0.203410E+10 | 0.967623E+09 | 0.294991E+10 | 0.159068E+10 |
April | 0.354584E+10 | 0.220591E+10 | 0.133992E+10 | 0.382729E+10 | 0.105457E+10 |
May | 0.302262E+10 | 0.156686E+10 | 0.145575E+10 | 0.335045E+10 | 0.590220E+09 |
June | 0.267092E+10 | 0.109558E+10 | 0.157534E+10 | 0.303620E+10 | 0.305836E+09 |
July | 0.265893E+10 | 0.115865E+10 | 0.150028E+10 | 0.308504E+10 | 0.343476E+09 |
August | 0.275277E+10 | 0.151729E+10 | 0.123548E+10 | 0.314497E+10 | 0.518225E+09 |
September | 0.215207E+10 | 0.129587E+10 | 0.856204E+09 | 0.223847E+10 | 0.868565E+09 |
October | 0.160030E+10 | 0.101489E+10 | 0.585413E+09 | 0.144795E+10 | 0.142153E+10 |
November | 0.829895E+09 | 0.579149E+09 | 0.250747E+09 | 0.566834E+09 | 0.231207E+10 |
December | 0.152186E+09 | 0.107200E+09 | 44986612.63 | 33814590.22 | 0.279674E+10 |
Annual Sum or Average | 0.244728E+11 | 0.140068E+11 | 0.104660E+11 | 0.253500E+11 | 0.161460E+11 |
Minimum of Months | 0.152186E+09 | 0.107200E+09 | 44986612.63 | 33814590.22 | 0.305836E+09 |
Maximum of Months | 0.354584E+10 | 0.220591E+10 | 0.157534E+10 | 0.382729E+10 | 0.279674E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113046E+09 | 20247916.54 | 92798400.78 | 0.00 | 0.549414E+10 |
February | 0.602676E+09 | 0.209831E+09 | 0.392845E+09 | 0.133721E+09 | 0.418261E+10 |
March | 0.200175E+10 | 0.860721E+09 | 0.114103E+10 | 0.118290E+10 | 0.334197E+10 |
April | 0.459447E+10 | 0.238017E+10 | 0.221431E+10 | 0.439142E+10 | 0.192296E+10 |
May | 0.461643E+10 | 0.210159E+10 | 0.251485E+10 | 0.465806E+10 | 0.102794E+10 |
June | 0.489659E+10 | 0.208718E+10 | 0.280941E+10 | 0.532438E+10 | 0.542342E+09 |
July | 0.423374E+10 | 0.160104E+10 | 0.263270E+10 | 0.463531E+10 | 0.613129E+09 |
August | 0.347960E+10 | 0.147305E+10 | 0.200656E+10 | 0.360674E+10 | 0.937499E+09 |
September | 0.203823E+10 | 0.853478E+09 | 0.118475E+10 | 0.164999E+10 | 0.165072E+10 |
October | 0.825234E+09 | 0.248342E+09 | 0.576892E+09 | 0.311855E+09 | 0.306219E+10 |
November | 0.319675E+09 | 0.116330E+09 | 0.203344E+09 | 37420781.25 | 0.511892E+10 |
December | 29649683.41 | 3134771.48 | 26514911.93 | 0.00 | 0.587056E+10 |
Annual Sum or Average | 0.277511E+11 | 0.119551E+11 | 0.157960E+11 | 0.259318E+11 | 0.337650E+11 |
Minimum of Months | 29649683.41 | 3134771.48 | 26514911.93 | 0.00 | 0.542342E+09 |
Maximum of Months | 0.489659E+10 | 0.238017E+10 | 0.280941E+10 | 0.532438E+10 | 0.587056E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4469737.50 | 800581.79 | 3669155.71 | 0.00 | 0.217233E+09 |
February | 23829196.79 | 8296489.48 | 15532707.31 | 5287162.17 | 0.165377E+09 |
March | 79147280.53 | 34032012.61 | 45115267.92 | 46770758.35 | 0.132138E+09 |
April | 0.181661E+09 | 94109351.93 | 87551465.46 | 0.173632E+09 | 76031927.88 |
May | 0.182529E+09 | 83094552.65 | 99434569.57 | 0.184175E+09 | 40643741.13 |
June | 0.193606E+09 | 82525068.96 | 0.111081E+09 | 0.210521E+09 | 21443731.94 |
July | 0.167398E+09 | 63303402.61 | 0.104094E+09 | 0.183276E+09 | 24242552.27 |
August | 0.137580E+09 | 58242707.56 | 79337238.09 | 0.142607E+09 | 37067872.84 |
September | 80589570.69 | 33745651.40 | 46843919.29 | 65238975.88 | 65268136.65 |
October | 32628932.32 | 9819198.99 | 22809733.32 | 12330380.93 | 0.121076E+09 |
November | 12639612.39 | 4599583.69 | 8040028.70 | 1479567.48 | 0.202398E+09 |
December | 1172318.60 | 123945.64 | 1048372.96 | 0.00 | 0.232117E+09 |
Annual Sum or Average | 0.109725E+10 | 0.472693E+09 | 0.624558E+09 | 0.102532E+10 | 0.133504E+10 |
Minimum of Months | 1172318.60 | 123945.64 | 1048372.96 | 0.00 | 21443731.94 |
Maximum of Months | 0.193606E+09 | 94109351.93 | 0.111081E+09 | 0.210521E+09 | 0.232117E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127107E+09 | 0.00 | 0.127107E+09 | 0.00 | 0.878396E+10 |
February | 0.507498E+09 | 0.00 | 0.507498E+09 | 0.00 | 0.709663E+10 |
March | 0.150277E+10 | 0.00 | 0.150277E+10 | 0.137527E+09 | 0.583487E+10 |
April | 0.263158E+10 | 58283651.85 | 0.257329E+10 | 0.105453E+10 | 0.308009E+10 |
May | 0.416878E+10 | 0.664116E+09 | 0.350467E+10 | 0.313790E+10 | 0.143737E+10 |
June | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.503344E+10 | 0.646673E+09 |
July | 0.456441E+10 | 0.742901E+09 | 0.382151E+10 | 0.445672E+10 | 0.813842E+09 |
August | 0.291444E+10 | 0.163474E+09 | 0.275096E+10 | 0.232002E+10 | 0.136114E+10 |
September | 0.157316E+10 | 1601027.85 | 0.157156E+10 | 0.579907E+09 | 0.264387E+10 |
October | 0.790989E+09 | 0.00 | 0.790989E+09 | 56490733.33 | 0.500805E+10 |
November | 0.237554E+09 | 0.00 | 0.237554E+09 | 0.00 | 0.833154E+10 |
December | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.925662E+10 |
Annual Sum or Average | 0.243197E+11 | 0.280175E+10 | 0.215180E+11 | 0.167765E+11 | 0.542947E+11 |
Minimum of Months | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.646673E+09 |
Maximum of Months | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.503344E+10 | 0.925662E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223457E+09 | 70483684.60 | 0.152974E+09 | 21051906.15 | 0.567384E+10 |
February | 0.111448E+10 | 0.532056E+09 | 0.582424E+09 | 0.589110E+09 | 0.427957E+10 |
March | 0.351725E+10 | 0.178084E+10 | 0.173641E+10 | 0.292301E+10 | 0.350701E+10 |
April | 0.467811E+10 | 0.236590E+10 | 0.231222E+10 | 0.423322E+10 | 0.189729E+10 |
May | 0.702140E+10 | 0.395124E+10 | 0.307016E+10 | 0.749595E+10 | 0.103034E+10 |
June | 0.625278E+10 | 0.291213E+10 | 0.334065E+10 | 0.689920E+10 | 0.491138E+09 |
July | 0.613688E+10 | 0.297078E+10 | 0.316609E+10 | 0.693660E+10 | 0.581861E+09 |
August | 0.486046E+10 | 0.236274E+10 | 0.249772E+10 | 0.526032E+10 | 0.911796E+09 |
September | 0.291028E+10 | 0.127357E+10 | 0.163671E+10 | 0.264697E+10 | 0.164867E+10 |
October | 0.158903E+10 | 0.637719E+09 | 0.951310E+09 | 0.112000E+10 | 0.304110E+10 |
November | 0.327370E+09 | 0.114592E+09 | 0.212778E+09 | 28544856.23 | 0.533858E+10 |
December | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.612758E+10 |
Annual Sum or Average | 0.386799E+11 | 0.189837E+11 | 0.196962E+11 | 0.381540E+11 | 0.345288E+11 |
Minimum of Months | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.491138E+09 |
Maximum of Months | 0.702140E+10 | 0.395124E+10 | 0.334065E+10 | 0.749595E+10 | 0.612758E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152281E+10 | 0.100257E+10 | 0.520235E+09 | 0.891556E+09 | 0.788658E+10 |
February | 0.473440E+10 | 0.329173E+10 | 0.144266E+10 | 0.396893E+10 | 0.574949E+10 |
March | 0.900590E+10 | 0.610281E+10 | 0.290309E+10 | 0.865821E+10 | 0.492993E+10 |
April | 0.106384E+11 | 0.661829E+10 | 0.402008E+10 | 0.113441E+11 | 0.317951E+10 |
May | 0.906857E+10 | 0.470099E+10 | 0.436759E+10 | 0.993207E+10 | 0.180181E+10 |
June | 0.801340E+10 | 0.328703E+10 | 0.472637E+10 | 0.902055E+10 | 0.935221E+09 |
July | 0.797741E+10 | 0.347624E+10 | 0.450117E+10 | 0.919666E+10 | 0.102821E+10 |
August | 0.825896E+10 | 0.455224E+10 | 0.370672E+10 | 0.938767E+10 | 0.151509E+10 |
September | 0.645673E+10 | 0.388792E+10 | 0.256881E+10 | 0.667484E+10 | 0.253987E+10 |
October | 0.480130E+10 | 0.304492E+10 | 0.175638E+10 | 0.429984E+10 | 0.424681E+10 |
November | 0.248989E+10 | 0.173759E+10 | 0.752300E+09 | 0.164720E+10 | 0.713462E+10 |
December | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 83318090.19 | 0.879025E+10 |
Annual Sum or Average | 0.734243E+11 | 0.420240E+11 | 0.314004E+11 | 0.751049E+11 | 0.497374E+11 |
Minimum of Months | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 83318090.19 | 0.935221E+09 |
Maximum of Months | 0.106384E+11 | 0.661829E+10 | 0.472637E+10 | 0.113441E+11 | 0.879025E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117518E+09 | 21048844.41 | 96468734.51 | 0.00 | 0.578612E+10 |
February | 0.626513E+09 | 0.218131E+09 | 0.408383E+09 | 0.133089E+09 | 0.444133E+10 |
March | 0.208093E+10 | 0.894767E+09 | 0.118616E+10 | 0.118923E+10 | 0.357881E+10 |
April | 0.477620E+10 | 0.247432E+10 | 0.230188E+10 | 0.448861E+10 | 0.204814E+10 |
May | 0.479903E+10 | 0.218472E+10 | 0.261431E+10 | 0.476590E+10 | 0.110844E+10 |
June | 0.509027E+10 | 0.216974E+10 | 0.292052E+10 | 0.548537E+10 | 0.579879E+09 |
July | 0.440119E+10 | 0.166437E+10 | 0.273682E+10 | 0.478423E+10 | 0.647878E+09 |
August | 0.361723E+10 | 0.153131E+10 | 0.208592E+10 | 0.373450E+10 | 0.965308E+09 |
September | 0.211885E+10 | 0.887238E+09 | 0.123161E+10 | 0.171016E+10 | 0.169229E+10 |
October | 0.857874E+09 | 0.258166E+09 | 0.599709E+09 | 0.321525E+09 | 0.316359E+10 |
November | 0.332319E+09 | 0.120932E+09 | 0.211387E+09 | 38368821.57 | 0.532463E+10 |
December | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.614741E+10 |
Annual Sum or Average | 0.288487E+11 | 0.124280E+11 | 0.164207E+11 | 0.266510E+11 | 0.354838E+11 |
Minimum of Months | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.579879E+09 |
Maximum of Months | 0.509027E+10 | 0.247432E+10 | 0.292052E+10 | 0.548537E+10 | 0.614741E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3224.79 | 47.46 | 0.00 | 47.46 | 0.00 | 0.00 |
February | 0.00 | 2872.49 | 209.78 | 0.00 | 209.78 | 0.00 | 0.00 |
March | 55.84 | 2107.54 | 561.07 | 0.00 | 561.07 | 0.00 | 0.00 |
April | 428.07 | 1123.14 | 1015.27 | 22.49 | 992.78 | 0.00 | 0.00 |
May | 1194.88 | 514.04 | 1556.45 | 247.95 | 1308.49 | 0.00 | 0.00 |
June | 1949.63 | 241.21 | 2030.44 | 451.92 | 1578.52 | 0.00 | 0.00 |
July | 1671.58 | 293.88 | 1704.16 | 277.37 | 1426.79 | 0.00 | 0.00 |
August | 880.65 | 484.74 | 1088.13 | 61.03 | 1027.09 | 0.00 | 0.00 |
September | 245.01 | 948.90 | 606.93 | 0.62 | 606.31 | 0.00 | 0.00 |
October | 26.89 | 1782.93 | 295.32 | 0.00 | 295.32 | 0.00 | 0.00 |
November | 0.00 | 3147.93 | 91.65 | 0.00 | 91.65 | 0.00 | 0.00 |
December | 0.00 | 3399.16 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Annual Sum or Average | 540.84 | 1672.01 | 771.17 | 88.84 | 682.33 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 241.21 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Maximum of Months | 1949.63 | 3399.16 | 2030.44 | 451.92 | 1578.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.06 | 2084.13 | 83.43 | 26.32 | 57.11 | 0.00 | 0.00 |
February | 247.25 | 1731.62 | 460.68 | 219.93 | 240.75 | 0.00 | 0.00 |
March | 1102.05 | 1266.85 | 1313.19 | 664.89 | 648.30 | 0.00 | 0.00 |
April | 1649.50 | 697.02 | 1804.83 | 912.77 | 892.06 | 0.00 | 0.00 |
May | 2807.87 | 370.48 | 2621.49 | 1475.23 | 1146.27 | 0.00 | 0.00 |
June | 2665.11 | 183.85 | 2412.34 | 1123.51 | 1288.83 | 0.00 | 0.00 |
July | 2593.27 | 210.71 | 2291.25 | 1109.16 | 1182.08 | 0.00 | 0.00 |
August | 1970.60 | 326.74 | 1814.69 | 882.15 | 932.54 | 0.00 | 0.00 |
September | 1037.35 | 598.00 | 1122.79 | 491.35 | 631.45 | 0.00 | 0.00 |
October | 427.77 | 1082.84 | 593.28 | 238.10 | 355.18 | 0.00 | 0.00 |
November | 11.52 | 2017.91 | 126.30 | 44.21 | 82.09 | 0.00 | 0.00 |
December | 0.00 | 2252.69 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Annual Sum or Average | 1216.51 | 1065.25 | 1226.53 | 601.97 | 624.56 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 183.85 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Maximum of Months | 2807.87 | 2252.69 | 2621.49 | 1475.23 | 1288.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.58 | 2893.46 | 568.55 | 374.32 | 194.23 | 0.00 | 0.00 |
February | 1654.22 | 2318.36 | 1957.01 | 1360.67 | 596.34 | 0.00 | 0.00 |
March | 3250.29 | 1775.65 | 3362.42 | 2278.53 | 1083.89 | 0.00 | 0.00 |
April | 4393.52 | 1168.70 | 4104.31 | 2553.35 | 1550.96 | 0.00 | 0.00 |
May | 3717.82 | 640.87 | 3385.82 | 1755.15 | 1630.67 | 0.00 | 0.00 |
June | 3483.74 | 347.15 | 3091.59 | 1268.14 | 1823.45 | 0.00 | 0.00 |
July | 3437.85 | 369.42 | 2978.42 | 1297.88 | 1680.55 | 0.00 | 0.00 |
August | 3513.07 | 539.56 | 3083.54 | 1699.61 | 1383.93 | 0.00 | 0.00 |
September | 2596.63 | 921.19 | 2491.02 | 1499.97 | 991.05 | 0.00 | 0.00 |
October | 1627.13 | 1508.62 | 1792.60 | 1136.84 | 655.76 | 0.00 | 0.00 |
November | 643.58 | 2689.47 | 960.61 | 670.37 | 290.24 | 0.00 | 0.00 |
December | 31.66 | 3227.30 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Annual Sum or Average | 2392.30 | 1529.62 | 2328.27 | 1332.57 | 995.70 | 0.00 | 0.00 |
Minimum of Months | 31.66 | 347.15 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Maximum of Months | 4393.52 | 3227.30 | 4104.31 | 2553.35 | 1823.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2126.15 | 43.88 | 7.86 | 36.02 | 0.00 | 0.00 |
February | 56.11 | 1797.60 | 258.98 | 90.17 | 168.81 | 0.00 | 0.00 |
March | 449.58 | 1291.67 | 776.93 | 334.07 | 442.86 | 0.00 | 0.00 |
April | 1744.41 | 750.31 | 1842.67 | 954.60 | 888.07 | 0.00 | 0.00 |
May | 1789.48 | 393.41 | 1791.75 | 815.68 | 976.07 | 0.00 | 0.00 |
June | 2119.66 | 215.26 | 1963.84 | 837.09 | 1126.74 | 0.00 | 0.00 |
July | 1790.20 | 232.60 | 1643.22 | 621.40 | 1021.81 | 0.00 | 0.00 |
August | 1402.63 | 342.91 | 1350.52 | 571.73 | 778.79 | 0.00 | 0.00 |
September | 673.96 | 611.13 | 817.46 | 342.30 | 475.16 | 0.00 | 0.00 |
October | 125.95 | 1126.66 | 320.29 | 96.39 | 223.91 | 0.00 | 0.00 |
November | 15.39 | 2012.70 | 128.21 | 46.66 | 81.55 | 0.00 | 0.00 |
December | 0.00 | 2260.32 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Annual Sum or Average | 850.59 | 1093.15 | 914.79 | 394.09 | 520.70 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 215.26 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Maximum of Months | 2119.66 | 2260.32 | 1963.84 | 954.60 | 1126.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3232.23 | 47.46 | 0.00 | 47.46 | 0.00 | 0.00 |
February | 0.00 | 2866.32 | 209.77 | 0.00 | 209.77 | 0.00 | 0.00 |
March | 58.81 | 2105.36 | 561.06 | 0.00 | 561.06 | 0.00 | 0.00 |
April | 457.94 | 1115.18 | 1015.25 | 22.49 | 992.76 | 0.00 | 0.00 |
May | 1237.47 | 501.36 | 1556.41 | 247.95 | 1308.46 | 0.00 | 0.00 |
June | 1983.36 | 235.29 | 2030.39 | 451.91 | 1578.48 | 0.00 | 0.00 |
July | 1691.01 | 292.63 | 1704.12 | 277.36 | 1426.76 | 0.00 | 0.00 |
August | 880.61 | 499.37 | 1088.10 | 61.03 | 1027.07 | 0.00 | 0.00 |
September | 230.98 | 1015.83 | 606.92 | 0.62 | 606.30 | 0.00 | 0.00 |
October | 21.94 | 1876.00 | 295.31 | 0.00 | 295.31 | 0.00 | 0.00 |
November | 0.00 | 3211.11 | 91.65 | 0.00 | 91.65 | 0.00 | 0.00 |
December | 0.00 | 3429.90 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Annual Sum or Average | 550.01 | 1692.11 | 771.16 | 88.84 | 682.32 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 235.29 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Maximum of Months | 1983.36 | 3429.90 | 2030.39 | 451.91 | 1578.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.32 | 2089.97 | 83.43 | 26.32 | 57.11 | 0.00 | 0.00 |
February | 248.92 | 1732.49 | 460.67 | 219.93 | 240.75 | 0.00 | 0.00 |
March | 1111.18 | 1277.77 | 1313.17 | 664.88 | 648.29 | 0.00 | 0.00 |
April | 1661.70 | 714.48 | 1804.80 | 912.75 | 892.05 | 0.00 | 0.00 |
May | 2820.85 | 382.69 | 2621.45 | 1475.20 | 1146.25 | 0.00 | 0.00 |
June | 2679.42 | 187.21 | 2412.30 | 1123.49 | 1288.81 | 0.00 | 0.00 |
July | 2599.68 | 219.16 | 2291.21 | 1109.14 | 1182.07 | 0.00 | 0.00 |
August | 1968.98 | 347.96 | 1814.66 | 882.13 | 932.53 | 0.00 | 0.00 |
September | 1020.82 | 653.60 | 1122.78 | 491.34 | 631.44 | 0.00 | 0.00 |
October | 419.44 | 1149.33 | 593.27 | 238.09 | 355.17 | 0.00 | 0.00 |
November | 11.23 | 2057.05 | 126.30 | 44.21 | 82.09 | 0.00 | 0.00 |
December | 0.00 | 2270.40 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Annual Sum or Average | 1219.03 | 1086.95 | 1226.51 | 601.96 | 624.55 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 187.21 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Maximum of Months | 2820.85 | 2270.40 | 2621.45 | 1475.20 | 1288.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 348.81 | 2805.86 | 568.53 | 374.30 | 194.23 | 0.00 | 0.00 |
February | 1683.68 | 2280.70 | 1956.93 | 1360.61 | 596.32 | 0.00 | 0.00 |
March | 3304.25 | 1781.75 | 3362.29 | 2278.43 | 1083.85 | 0.00 | 0.00 |
April | 4429.92 | 1220.62 | 4104.15 | 2553.25 | 1550.90 | 0.00 | 0.00 |
May | 3752.90 | 661.12 | 3385.69 | 1755.07 | 1630.62 | 0.00 | 0.00 |
June | 3514.27 | 353.99 | 3091.48 | 1268.09 | 1823.39 | 0.00 | 0.00 |
July | 3455.61 | 384.73 | 2978.32 | 1297.83 | 1680.49 | 0.00 | 0.00 |
August | 3522.74 | 580.47 | 3083.43 | 1699.54 | 1383.89 | 0.00 | 0.00 |
September | 2590.93 | 1005.33 | 2490.93 | 1499.91 | 991.02 | 0.00 | 0.00 |
October | 1621.87 | 1592.28 | 1792.53 | 1136.80 | 655.73 | 0.00 | 0.00 |
November | 656.09 | 2676.12 | 960.57 | 670.34 | 290.23 | 0.00 | 0.00 |
December | 37.88 | 3132.68 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Annual Sum or Average | 2411.63 | 1536.02 | 2328.18 | 1332.52 | 995.67 | 0.00 | 0.00 |
Minimum of Months | 37.88 | 353.99 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Maximum of Months | 4429.92 | 3132.68 | 4104.15 | 2553.25 | 1823.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2132.38 | 43.88 | 7.86 | 36.02 | 0.00 | 0.00 |
February | 57.46 | 1797.28 | 258.97 | 90.17 | 168.81 | 0.00 | 0.00 |
March | 459.11 | 1297.08 | 776.92 | 334.06 | 442.86 | 0.00 | 0.00 |
April | 1761.21 | 771.21 | 1842.64 | 954.58 | 888.06 | 0.00 | 0.00 |
May | 1807.89 | 398.96 | 1791.73 | 815.67 | 976.06 | 0.00 | 0.00 |
June | 2135.38 | 217.51 | 1963.81 | 837.08 | 1126.73 | 0.00 | 0.00 |
July | 1799.05 | 237.97 | 1643.19 | 621.39 | 1021.80 | 0.00 | 0.00 |
August | 1399.85 | 363.86 | 1350.50 | 571.72 | 778.78 | 0.00 | 0.00 |
September | 661.74 | 662.03 | 817.45 | 342.29 | 475.15 | 0.00 | 0.00 |
October | 121.04 | 1188.50 | 320.29 | 96.39 | 223.90 | 0.00 | 0.00 |
November | 15.01 | 2052.98 | 128.21 | 46.66 | 81.55 | 0.00 | 0.00 |
December | 0.00 | 2278.48 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Annual Sum or Average | 854.81 | 1113.01 | 914.78 | 394.08 | 520.69 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 217.51 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Maximum of Months | 2135.38 | 2278.48 | 1963.81 | 954.58 | 1126.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3279.55 | 47.46 | 0.00 | 47.46 | 0.00 | 0.00 |
February | 0.00 | 2933.46 | 209.78 | 0.00 | 209.78 | 0.00 | 0.00 |
March | 51.35 | 2178.49 | 561.07 | 0.00 | 561.07 | 0.00 | 0.00 |
April | 406.84 | 1188.31 | 1015.27 | 22.49 | 992.78 | 0.00 | 0.00 |
May | 1171.56 | 536.65 | 1556.45 | 247.95 | 1308.49 | 0.00 | 0.00 |
June | 1941.91 | 249.49 | 2030.44 | 451.92 | 1578.52 | 0.00 | 0.00 |
July | 1663.95 | 303.85 | 1704.16 | 277.37 | 1426.79 | 0.00 | 0.00 |
August | 866.20 | 508.19 | 1088.13 | 61.03 | 1027.09 | 0.00 | 0.00 |
September | 223.73 | 1020.01 | 606.93 | 0.62 | 606.31 | 0.00 | 0.00 |
October | 21.09 | 1869.79 | 295.32 | 0.00 | 295.32 | 0.00 | 0.00 |
November | 0.00 | 3214.33 | 91.65 | 0.00 | 91.65 | 0.00 | 0.00 |
December | 0.00 | 3456.02 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Annual Sum or Average | 531.98 | 1721.67 | 771.17 | 88.84 | 682.33 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 249.49 | 14.40 | 0.00 | 14.40 | 0.00 | 0.00 |
Maximum of Months | 1941.91 | 3456.02 | 2030.44 | 451.92 | 1578.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.86 | 2118.37 | 83.43 | 26.32 | 57.11 | 0.00 | 0.00 |
February | 243.51 | 1769.00 | 460.68 | 219.93 | 240.75 | 0.00 | 0.00 |
March | 1091.33 | 1309.37 | 1313.19 | 664.89 | 648.30 | 0.00 | 0.00 |
April | 1633.19 | 731.98 | 1804.83 | 912.77 | 892.06 | 0.00 | 0.00 |
May | 2798.67 | 384.68 | 2621.49 | 1475.23 | 1146.27 | 0.00 | 0.00 |
June | 2661.73 | 189.48 | 2412.34 | 1123.51 | 1288.83 | 0.00 | 0.00 |
July | 2589.83 | 217.24 | 2291.25 | 1109.16 | 1182.08 | 0.00 | 0.00 |
August | 1963.98 | 340.43 | 1814.69 | 882.15 | 932.54 | 0.00 | 0.00 |
September | 1021.21 | 636.06 | 1122.79 | 491.35 | 631.45 | 0.00 | 0.00 |
October | 418.16 | 1135.42 | 593.28 | 238.10 | 355.18 | 0.00 | 0.00 |
November | 11.01 | 2059.64 | 126.30 | 44.21 | 82.09 | 0.00 | 0.00 |
December | 0.00 | 2287.78 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Annual Sum or Average | 1209.85 | 1094.90 | 1226.53 | 601.97 | 624.56 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 189.48 | 18.05 | 4.34 | 13.71 | 0.00 | 0.00 |
Maximum of Months | 2798.67 | 2287.78 | 2621.49 | 1475.23 | 1288.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.87 | 2944.51 | 568.55 | 374.32 | 194.23 | 0.00 | 0.00 |
February | 1640.59 | 2376.61 | 1957.01 | 1360.67 | 596.34 | 0.00 | 0.00 |
March | 3232.61 | 1840.63 | 3362.42 | 2278.53 | 1083.89 | 0.00 | 0.00 |
April | 4376.58 | 1226.66 | 4104.31 | 2553.35 | 1550.96 | 0.00 | 0.00 |
May | 3708.21 | 672.72 | 3385.82 | 1755.15 | 1630.67 | 0.00 | 0.00 |
June | 3480.15 | 360.81 | 3091.59 | 1268.14 | 1823.45 | 0.00 | 0.00 |
July | 3433.64 | 383.89 | 2978.42 | 1297.88 | 1680.55 | 0.00 | 0.00 |
August | 3504.95 | 565.67 | 3083.54 | 1699.61 | 1383.93 | 0.00 | 0.00 |
September | 2575.17 | 979.89 | 2491.02 | 1499.97 | 991.05 | 0.00 | 0.00 |
October | 1605.38 | 1585.58 | 1792.60 | 1136.84 | 655.76 | 0.00 | 0.00 |
November | 635.49 | 2752.55 | 960.61 | 670.37 | 290.24 | 0.00 | 0.00 |
December | 31.11 | 3281.90 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Annual Sum or Average | 2381.56 | 1577.16 | 2328.27 | 1332.57 | 995.70 | 0.00 | 0.00 |
Minimum of Months | 31.11 | 360.81 | 170.47 | 120.08 | 50.39 | 0.00 | 0.00 |
Maximum of Months | 4376.58 | 3281.90 | 4104.31 | 2553.35 | 1823.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2160.29 | 43.88 | 7.86 | 36.02 | 0.00 | 0.00 |
February | 55.01 | 1835.87 | 258.98 | 90.17 | 168.81 | 0.00 | 0.00 |
March | 444.01 | 1336.17 | 776.93 | 334.07 | 442.86 | 0.00 | 0.00 |
April | 1731.72 | 790.18 | 1842.67 | 954.60 | 888.07 | 0.00 | 0.00 |
May | 1779.38 | 413.84 | 1791.75 | 815.68 | 976.07 | 0.00 | 0.00 |
June | 2116.27 | 223.72 | 1963.84 | 837.09 | 1126.74 | 0.00 | 0.00 |
July | 1786.23 | 241.89 | 1643.22 | 621.40 | 1021.81 | 0.00 | 0.00 |
August | 1394.30 | 360.40 | 1350.52 | 571.73 | 778.79 | 0.00 | 0.00 |
September | 659.79 | 652.89 | 817.46 | 342.30 | 475.16 | 0.00 | 0.00 |
October | 120.04 | 1181.15 | 320.29 | 96.39 | 223.91 | 0.00 | 0.00 |
November | 14.80 | 2054.26 | 128.21 | 46.66 | 81.55 | 0.00 | 0.00 |
December | 0.00 | 2295.18 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Annual Sum or Average | 845.10 | 1125.18 | 914.79 | 394.09 | 520.70 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 223.72 | 11.51 | 1.22 | 10.29 | 0.00 | 0.00 |
Maximum of Months | 2116.27 | 2295.18 | 1963.84 | 954.60 | 1126.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.863728E+10 | 0.127107E+09 | 0.00 | 0.127107E+09 | 0.00 | 0.00 |
February | 0.00 | 0.694912E+10 | 0.507498E+09 | 0.00 | 0.507498E+09 | 0.00 | 0.00 |
March | 0.149569E+09 | 0.564483E+10 | 0.150277E+10 | 0.00 | 0.150277E+10 | 0.00 | 0.00 |
April | 0.110955E+10 | 0.291117E+10 | 0.263158E+10 | 58283651.85 | 0.257329E+10 | 0.00 | 0.00 |
May | 0.320036E+10 | 0.137680E+10 | 0.416878E+10 | 0.664116E+09 | 0.350467E+10 | 0.00 | 0.00 |
June | 0.505345E+10 | 0.625229E+09 | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.00 | 0.00 |
July | 0.447716E+10 | 0.787138E+09 | 0.456441E+10 | 0.742901E+09 | 0.382151E+10 | 0.00 | 0.00 |
August | 0.235874E+10 | 0.129832E+10 | 0.291444E+10 | 0.163474E+09 | 0.275096E+10 | 0.00 | 0.00 |
September | 0.635069E+09 | 0.245955E+10 | 0.157316E+10 | 1601027.85 | 0.157156E+10 | 0.00 | 0.00 |
October | 72026982.33 | 0.477539E+10 | 0.790989E+09 | 0.00 | 0.790989E+09 | 0.00 | 0.00 |
November | 0.00 | 0.815944E+10 | 0.237554E+09 | 0.00 | 0.237554E+09 | 0.00 | 0.00 |
December | 0.00 | 0.910431E+10 | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.170559E+11 | 0.527286E+11 | 0.243197E+11 | 0.280175E+10 | 0.215180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.625229E+09 | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.00 |
Maximum of Months | 0.505345E+10 | 0.910431E+10 | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21589275.52 | 0.558214E+10 | 0.223457E+09 | 70483684.60 | 0.152974E+09 | 0.00 | 0.00 |
February | 0.598144E+09 | 0.418914E+10 | 0.111448E+10 | 0.532056E+09 | 0.582424E+09 | 0.00 | 0.00 |
March | 0.295174E+10 | 0.339314E+10 | 0.351725E+10 | 0.178084E+10 | 0.173641E+10 | 0.00 | 0.00 |
April | 0.427550E+10 | 0.180667E+10 | 0.467811E+10 | 0.236590E+10 | 0.231222E+10 | 0.00 | 0.00 |
May | 0.752059E+10 | 0.992297E+09 | 0.702140E+10 | 0.395124E+10 | 0.307016E+10 | 0.00 | 0.00 |
June | 0.690797E+10 | 0.476542E+09 | 0.625278E+10 | 0.291213E+10 | 0.334065E+10 | 0.00 | 0.00 |
July | 0.694582E+10 | 0.564368E+09 | 0.613688E+10 | 0.297078E+10 | 0.316609E+10 | 0.00 | 0.00 |
August | 0.527806E+10 | 0.875138E+09 | 0.486046E+10 | 0.236274E+10 | 0.249772E+10 | 0.00 | 0.00 |
September | 0.268881E+10 | 0.155001E+10 | 0.291028E+10 | 0.127357E+10 | 0.163671E+10 | 0.00 | 0.00 |
October | 0.114575E+10 | 0.290029E+10 | 0.158903E+10 | 0.637719E+09 | 0.951310E+09 | 0.00 | 0.00 |
November | 29847996.05 | 0.523042E+10 | 0.327370E+09 | 0.114592E+09 | 0.212778E+09 | 0.00 | 0.00 |
December | 0.00 | 0.603360E+10 | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.383638E+11 | 0.335938E+11 | 0.386799E+11 | 0.189837E+11 | 0.196962E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.476542E+09 | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.00 |
Maximum of Months | 0.752059E+10 | 0.603360E+10 | 0.702140E+10 | 0.395124E+10 | 0.334065E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.901504E+09 | 0.774984E+10 | 0.152281E+10 | 0.100257E+10 | 0.520235E+09 | 0.00 | 0.00 |
February | 0.400189E+10 | 0.560857E+10 | 0.473440E+10 | 0.329173E+10 | 0.144266E+10 | 0.00 | 0.00 |
March | 0.870556E+10 | 0.475589E+10 | 0.900590E+10 | 0.610281E+10 | 0.290309E+10 | 0.00 | 0.00 |
April | 0.113880E+11 | 0.302927E+10 | 0.106384E+11 | 0.661829E+10 | 0.402008E+10 | 0.00 | 0.00 |
May | 0.995781E+10 | 0.171650E+10 | 0.906857E+10 | 0.470099E+10 | 0.436759E+10 | 0.00 | 0.00 |
June | 0.902985E+10 | 0.899812E+09 | 0.801340E+10 | 0.328703E+10 | 0.472637E+10 | 0.00 | 0.00 |
July | 0.920794E+10 | 0.989453E+09 | 0.797741E+10 | 0.347624E+10 | 0.450117E+10 | 0.00 | 0.00 |
August | 0.940941E+10 | 0.144515E+10 | 0.825896E+10 | 0.455224E+10 | 0.370672E+10 | 0.00 | 0.00 |
September | 0.673045E+10 | 0.238773E+10 | 0.645673E+10 | 0.388792E+10 | 0.256881E+10 | 0.00 | 0.00 |
October | 0.435810E+10 | 0.404070E+10 | 0.480130E+10 | 0.304492E+10 | 0.175638E+10 | 0.00 | 0.00 |
November | 0.166817E+10 | 0.697112E+10 | 0.248989E+10 | 0.173759E+10 | 0.752300E+09 | 0.00 | 0.00 |
December | 84803649.68 | 0.864399E+10 | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.754435E+11 | 0.482380E+11 | 0.734243E+11 | 0.420240E+11 | 0.314004E+11 | 0.00 | 0.00 |
Minimum of Months | 84803649.68 | 0.899812E+09 | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113880E+11 | 0.864399E+10 | 0.106384E+11 | 0.661829E+10 | 0.472637E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.569469E+10 | 0.117518E+09 | 21048844.41 | 96468734.51 | 0.00 | 0.00 |
February | 0.135746E+09 | 0.434874E+10 | 0.626513E+09 | 0.218131E+09 | 0.408383E+09 | 0.00 | 0.00 |
March | 0.120416E+10 | 0.345962E+10 | 0.208093E+10 | 0.894767E+09 | 0.118616E+10 | 0.00 | 0.00 |
April | 0.452152E+10 | 0.194480E+10 | 0.477620E+10 | 0.247432E+10 | 0.230188E+10 | 0.00 | 0.00 |
May | 0.479293E+10 | 0.105371E+10 | 0.479903E+10 | 0.218472E+10 | 0.261431E+10 | 0.00 | 0.00 |
June | 0.549415E+10 | 0.557956E+09 | 0.509027E+10 | 0.216974E+10 | 0.292052E+10 | 0.00 | 0.00 |
July | 0.479487E+10 | 0.622991E+09 | 0.440119E+10 | 0.166437E+10 | 0.273682E+10 | 0.00 | 0.00 |
August | 0.375681E+10 | 0.918442E+09 | 0.361723E+10 | 0.153131E+10 | 0.208592E+10 | 0.00 | 0.00 |
September | 0.174690E+10 | 0.158404E+10 | 0.211885E+10 | 0.887238E+09 | 0.123161E+10 | 0.00 | 0.00 |
October | 0.337341E+09 | 0.301765E+10 | 0.857874E+09 | 0.258166E+09 | 0.599709E+09 | 0.00 | 0.00 |
November | 39902076.73 | 0.521691E+10 | 0.332319E+09 | 0.120932E+09 | 0.211387E+09 | 0.00 | 0.00 |
December | 0.00 | 0.605405E+10 | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.268243E+11 | 0.344736E+11 | 0.288487E+11 | 0.124280E+11 | 0.164207E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.557956E+09 | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.00 |
Maximum of Months | 0.549415E+10 | 0.605405E+10 | 0.509027E+10 | 0.247432E+10 | 0.292052E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.865720E+10 | 0.127104E+09 | 0.00 | 0.127104E+09 | 0.00 | 0.00 |
February | 0.00 | 0.693420E+10 | 0.507487E+09 | 0.00 | 0.507487E+09 | 0.00 | 0.00 |
March | 0.157530E+09 | 0.563899E+10 | 0.150274E+10 | 0.00 | 0.150274E+10 | 0.00 | 0.00 |
April | 0.118698E+10 | 0.289054E+10 | 0.263152E+10 | 58281938.74 | 0.257324E+10 | 0.00 | 0.00 |
May | 0.331443E+10 | 0.134283E+10 | 0.416869E+10 | 0.664097E+09 | 0.350459E+10 | 0.00 | 0.00 |
June | 0.514087E+10 | 0.609867E+09 | 0.526276E+10 | 0.117134E+10 | 0.409142E+10 | 0.00 | 0.00 |
July | 0.452920E+10 | 0.783776E+09 | 0.456430E+10 | 0.742879E+09 | 0.382142E+10 | 0.00 | 0.00 |
August | 0.235864E+10 | 0.133752E+10 | 0.291437E+10 | 0.163469E+09 | 0.275090E+10 | 0.00 | 0.00 |
September | 0.598699E+09 | 0.263304E+10 | 0.157312E+10 | 1600980.79 | 0.157152E+10 | 0.00 | 0.00 |
October | 58769240.41 | 0.502467E+10 | 0.790971E+09 | 0.00 | 0.790971E+09 | 0.00 | 0.00 |
November | 0.00 | 0.832320E+10 | 0.237548E+09 | 0.00 | 0.237548E+09 | 0.00 | 0.00 |
December | 0.00 | 0.918664E+10 | 38556643.58 | 0.00 | 38556643.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.173451E+11 | 0.533625E+11 | 0.243192E+11 | 0.280167E+10 | 0.215175E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.609867E+09 | 38556643.58 | 0.00 | 38556643.58 | 0.00 | 0.00 |
Maximum of Months | 0.514087E+10 | 0.918664E+10 | 0.526276E+10 | 0.117134E+10 | 0.409142E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 22292435.44 | 0.559778E+10 | 0.223453E+09 | 70482305.85 | 0.152971E+09 | 0.00 | 0.00 |
February | 0.602188E+09 | 0.419124E+10 | 0.111446E+10 | 0.532046E+09 | 0.582415E+09 | 0.00 | 0.00 |
March | 0.297619E+10 | 0.342238E+10 | 0.351719E+10 | 0.178080E+10 | 0.173639E+10 | 0.00 | 0.00 |
April | 0.430714E+10 | 0.185193E+10 | 0.467803E+10 | 0.236585E+10 | 0.231218E+10 | 0.00 | 0.00 |
May | 0.755537E+10 | 0.102499E+10 | 0.702129E+10 | 0.395117E+10 | 0.307012E+10 | 0.00 | 0.00 |
June | 0.694506E+10 | 0.485243E+09 | 0.625268E+10 | 0.291208E+10 | 0.334061E+10 | 0.00 | 0.00 |
July | 0.696297E+10 | 0.586997E+09 | 0.613678E+10 | 0.297073E+10 | 0.316605E+10 | 0.00 | 0.00 |
August | 0.527371E+10 | 0.931969E+09 | 0.486038E+10 | 0.236270E+10 | 0.249768E+10 | 0.00 | 0.00 |
September | 0.264598E+10 | 0.169414E+10 | 0.291023E+10 | 0.127355E+10 | 0.163669E+10 | 0.00 | 0.00 |
October | 0.112343E+10 | 0.307837E+10 | 0.158900E+10 | 0.637707E+09 | 0.951295E+09 | 0.00 | 0.00 |
November | 29119959.07 | 0.533189E+10 | 0.327365E+09 | 0.114590E+09 | 0.212775E+09 | 0.00 | 0.00 |
December | 0.00 | 0.608103E+10 | 48346344.51 | 11620088.20 | 36726256.30 | 0.00 | 0.00 |
Annual Sum or Average | 0.384435E+11 | 0.342780E+11 | 0.386792E+11 | 0.189833E+11 | 0.196959E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.485243E+09 | 48346344.51 | 11620088.20 | 36726256.30 | 0.00 | 0.00 |
Maximum of Months | 0.755537E+10 | 0.608103E+10 | 0.702129E+10 | 0.395117E+10 | 0.334061E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.934243E+09 | 0.751522E+10 | 0.152275E+10 | 0.100253E+10 | 0.520214E+09 | 0.00 | 0.00 |
February | 0.407315E+10 | 0.551747E+10 | 0.473421E+10 | 0.329160E+10 | 0.144261E+10 | 0.00 | 0.00 |
March | 0.885011E+10 | 0.477224E+10 | 0.900555E+10 | 0.610256E+10 | 0.290299E+10 | 0.00 | 0.00 |
April | 0.114824E+11 | 0.316385E+10 | 0.106380E+11 | 0.661801E+10 | 0.401994E+10 | 0.00 | 0.00 |
May | 0.100518E+11 | 0.177073E+10 | 0.906824E+10 | 0.470079E+10 | 0.436745E+10 | 0.00 | 0.00 |
June | 0.910899E+10 | 0.917546E+09 | 0.801311E+10 | 0.328689E+10 | 0.472622E+10 | 0.00 | 0.00 |
July | 0.925552E+10 | 0.103047E+10 | 0.797712E+10 | 0.347609E+10 | 0.450103E+10 | 0.00 | 0.00 |
August | 0.943530E+10 | 0.155474E+10 | 0.825865E+10 | 0.455205E+10 | 0.370660E+10 | 0.00 | 0.00 |
September | 0.671570E+10 | 0.260580E+10 | 0.645648E+10 | 0.388776E+10 | 0.256872E+10 | 0.00 | 0.00 |
October | 0.434402E+10 | 0.426477E+10 | 0.480111E+10 | 0.304479E+10 | 0.175631E+10 | 0.00 | 0.00 |
November | 0.170057E+10 | 0.693650E+10 | 0.248979E+10 | 0.173752E+10 | 0.752271E+09 | 0.00 | 0.00 |
December | 0.101448E+09 | 0.839057E+10 | 0.456578E+09 | 0.321613E+09 | 0.134966E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.760532E+11 | 0.484399E+11 | 0.734215E+11 | 0.420222E+11 | 0.313993E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101448E+09 | 0.917546E+09 | 0.456578E+09 | 0.321613E+09 | 0.134966E+09 | 0.00 | 0.00 |
Maximum of Months | 0.114824E+11 | 0.839057E+10 | 0.106380E+11 | 0.661801E+10 | 0.472622E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.571138E+10 | 0.117516E+09 | 21048498.33 | 96467556.49 | 0.00 | 0.00 |
February | 0.139008E+09 | 0.434799E+10 | 0.626505E+09 | 0.218127E+09 | 0.408378E+09 | 0.00 | 0.00 |
March | 0.122968E+10 | 0.347410E+10 | 0.208090E+10 | 0.894753E+09 | 0.118615E+10 | 0.00 | 0.00 |
April | 0.456506E+10 | 0.199899E+10 | 0.477613E+10 | 0.247428E+10 | 0.230186E+10 | 0.00 | 0.00 |
May | 0.484224E+10 | 0.106858E+10 | 0.479896E+10 | 0.218468E+10 | 0.261428E+10 | 0.00 | 0.00 |
June | 0.553491E+10 | 0.563786E+09 | 0.509020E+10 | 0.216971E+10 | 0.292049E+10 | 0.00 | 0.00 |
July | 0.481859E+10 | 0.637371E+09 | 0.440113E+10 | 0.166434E+10 | 0.273679E+10 | 0.00 | 0.00 |
August | 0.374935E+10 | 0.974567E+09 | 0.361718E+10 | 0.153129E+10 | 0.208589E+10 | 0.00 | 0.00 |
September | 0.171523E+10 | 0.171599E+10 | 0.211882E+10 | 0.887224E+09 | 0.123160E+10 | 0.00 | 0.00 |
October | 0.324185E+09 | 0.318327E+10 | 0.857863E+09 | 0.258161E+09 | 0.599702E+09 | 0.00 | 0.00 |
November | 38900348.73 | 0.532132E+10 | 0.332314E+09 | 0.120930E+09 | 0.211384E+09 | 0.00 | 0.00 |
December | 0.00 | 0.610268E+10 | 30822002.01 | 3258717.12 | 27563284.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.269571E+11 | 0.351000E+11 | 0.288484E+11 | 0.124278E+11 | 0.164206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.563786E+09 | 30822002.01 | 3258717.12 | 27563284.90 | 0.00 | 0.00 |
Maximum of Months | 0.553491E+10 | 0.610268E+10 | 0.509020E+10 | 0.247428E+10 | 0.292049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.878396E+10 | 0.127107E+09 | 0.00 | 0.127107E+09 | 0.00 | 0.00 |
February | 0.00 | 0.709663E+10 | 0.507498E+09 | 0.00 | 0.507498E+09 | 0.00 | 0.00 |
March | 0.137527E+09 | 0.583487E+10 | 0.150277E+10 | 0.00 | 0.150277E+10 | 0.00 | 0.00 |
April | 0.105453E+10 | 0.308009E+10 | 0.263158E+10 | 58283651.85 | 0.257329E+10 | 0.00 | 0.00 |
May | 0.313790E+10 | 0.143737E+10 | 0.416878E+10 | 0.664116E+09 | 0.350467E+10 | 0.00 | 0.00 |
June | 0.503344E+10 | 0.646673E+09 | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.00 | 0.00 |
July | 0.445672E+10 | 0.813842E+09 | 0.456441E+10 | 0.742901E+09 | 0.382151E+10 | 0.00 | 0.00 |
August | 0.232002E+10 | 0.136114E+10 | 0.291444E+10 | 0.163474E+09 | 0.275096E+10 | 0.00 | 0.00 |
September | 0.579907E+09 | 0.264387E+10 | 0.157316E+10 | 1601027.85 | 0.157156E+10 | 0.00 | 0.00 |
October | 56490733.33 | 0.500805E+10 | 0.790989E+09 | 0.00 | 0.790989E+09 | 0.00 | 0.00 |
November | 0.00 | 0.833154E+10 | 0.237554E+09 | 0.00 | 0.237554E+09 | 0.00 | 0.00 |
December | 0.00 | 0.925662E+10 | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.167765E+11 | 0.542947E+11 | 0.243197E+11 | 0.280175E+10 | 0.215180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.646673E+09 | 38557594.82 | 0.00 | 38557594.82 | 0.00 | 0.00 |
Maximum of Months | 0.503344E+10 | 0.925662E+10 | 0.526289E+10 | 0.117137E+10 | 0.409152E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21051906.15 | 0.567384E+10 | 0.223457E+09 | 70483684.60 | 0.152974E+09 | 0.00 | 0.00 |
February | 0.589110E+09 | 0.427957E+10 | 0.111448E+10 | 0.532056E+09 | 0.582424E+09 | 0.00 | 0.00 |
March | 0.292301E+10 | 0.350701E+10 | 0.351725E+10 | 0.178084E+10 | 0.173641E+10 | 0.00 | 0.00 |
April | 0.423322E+10 | 0.189729E+10 | 0.467811E+10 | 0.236590E+10 | 0.231222E+10 | 0.00 | 0.00 |
May | 0.749595E+10 | 0.103034E+10 | 0.702140E+10 | 0.395124E+10 | 0.307016E+10 | 0.00 | 0.00 |
June | 0.689920E+10 | 0.491138E+09 | 0.625278E+10 | 0.291213E+10 | 0.334065E+10 | 0.00 | 0.00 |
July | 0.693660E+10 | 0.581861E+09 | 0.613688E+10 | 0.297078E+10 | 0.316609E+10 | 0.00 | 0.00 |
August | 0.526032E+10 | 0.911796E+09 | 0.486046E+10 | 0.236274E+10 | 0.249772E+10 | 0.00 | 0.00 |
September | 0.264697E+10 | 0.164867E+10 | 0.291028E+10 | 0.127357E+10 | 0.163671E+10 | 0.00 | 0.00 |
October | 0.112000E+10 | 0.304110E+10 | 0.158903E+10 | 0.637719E+09 | 0.951310E+09 | 0.00 | 0.00 |
November | 28544856.23 | 0.533858E+10 | 0.327370E+09 | 0.114592E+09 | 0.212778E+09 | 0.00 | 0.00 |
December | 0.00 | 0.612758E+10 | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.381540E+11 | 0.345288E+11 | 0.386799E+11 | 0.189837E+11 | 0.196962E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.491138E+09 | 48347169.09 | 11620315.51 | 36726853.58 | 0.00 | 0.00 |
Maximum of Months | 0.749595E+10 | 0.612758E+10 | 0.702140E+10 | 0.395124E+10 | 0.334065E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.891556E+09 | 0.788658E+10 | 0.152281E+10 | 0.100257E+10 | 0.520235E+09 | 0.00 | 0.00 |
February | 0.396893E+10 | 0.574949E+10 | 0.473440E+10 | 0.329173E+10 | 0.144266E+10 | 0.00 | 0.00 |
March | 0.865821E+10 | 0.492993E+10 | 0.900590E+10 | 0.610281E+10 | 0.290309E+10 | 0.00 | 0.00 |
April | 0.113441E+11 | 0.317951E+10 | 0.106384E+11 | 0.661829E+10 | 0.402008E+10 | 0.00 | 0.00 |
May | 0.993207E+10 | 0.180181E+10 | 0.906857E+10 | 0.470099E+10 | 0.436759E+10 | 0.00 | 0.00 |
June | 0.902055E+10 | 0.935221E+09 | 0.801340E+10 | 0.328703E+10 | 0.472637E+10 | 0.00 | 0.00 |
July | 0.919666E+10 | 0.102821E+10 | 0.797741E+10 | 0.347624E+10 | 0.450117E+10 | 0.00 | 0.00 |
August | 0.938767E+10 | 0.151509E+10 | 0.825896E+10 | 0.455224E+10 | 0.370672E+10 | 0.00 | 0.00 |
September | 0.667484E+10 | 0.253987E+10 | 0.645673E+10 | 0.388792E+10 | 0.256881E+10 | 0.00 | 0.00 |
October | 0.429984E+10 | 0.424681E+10 | 0.480130E+10 | 0.304492E+10 | 0.175638E+10 | 0.00 | 0.00 |
November | 0.164720E+10 | 0.713462E+10 | 0.248989E+10 | 0.173759E+10 | 0.752300E+09 | 0.00 | 0.00 |
December | 83318090.19 | 0.879025E+10 | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.751049E+11 | 0.497374E+11 | 0.734243E+11 | 0.420240E+11 | 0.314004E+11 | 0.00 | 0.00 |
Minimum of Months | 83318090.19 | 0.935221E+09 | 0.456597E+09 | 0.321626E+09 | 0.134971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113441E+11 | 0.879025E+10 | 0.106384E+11 | 0.661829E+10 | 0.472637E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.578612E+10 | 0.117518E+09 | 21048844.41 | 96468734.51 | 0.00 | 0.00 |
February | 0.133089E+09 | 0.444133E+10 | 0.626513E+09 | 0.218131E+09 | 0.408383E+09 | 0.00 | 0.00 |
March | 0.118923E+10 | 0.357881E+10 | 0.208093E+10 | 0.894767E+09 | 0.118616E+10 | 0.00 | 0.00 |
April | 0.448861E+10 | 0.204814E+10 | 0.477620E+10 | 0.247432E+10 | 0.230188E+10 | 0.00 | 0.00 |
May | 0.476590E+10 | 0.110844E+10 | 0.479903E+10 | 0.218472E+10 | 0.261431E+10 | 0.00 | 0.00 |
June | 0.548537E+10 | 0.579879E+09 | 0.509027E+10 | 0.216974E+10 | 0.292052E+10 | 0.00 | 0.00 |
July | 0.478423E+10 | 0.647878E+09 | 0.440119E+10 | 0.166437E+10 | 0.273682E+10 | 0.00 | 0.00 |
August | 0.373450E+10 | 0.965308E+09 | 0.361723E+10 | 0.153131E+10 | 0.208592E+10 | 0.00 | 0.00 |
September | 0.171016E+10 | 0.169229E+10 | 0.211885E+10 | 0.887238E+09 | 0.123161E+10 | 0.00 | 0.00 |
October | 0.321525E+09 | 0.316359E+10 | 0.857874E+09 | 0.258166E+09 | 0.599709E+09 | 0.00 | 0.00 |
November | 38368821.57 | 0.532463E+10 | 0.332319E+09 | 0.120932E+09 | 0.211387E+09 | 0.00 | 0.00 |
December | 0.00 | 0.614741E+10 | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.266510E+11 | 0.354838E+11 | 0.288487E+11 | 0.124280E+11 | 0.164207E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.579879E+09 | 30822403.27 | 3258770.70 | 27563632.58 | 0.00 | 0.00 |
Maximum of Months | 0.548537E+10 | 0.614741E+10 | 0.509027E+10 | 0.247432E+10 | 0.292052E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592844E+10 | -0.566902E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -259424049.2 | 60.05 | 0.00 | 0.00 |
February | 0.538196E+10 | -0.515214E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -229817821.1 | 60.05 | 0.00 | 0.00 |
March | 0.634697E+10 | -0.610038E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246584332.8 | 60.05 | 0.00 | 0.00 |
April | 0.571815E+10 | -0.548883E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229325167.4 | 60.05 | 0.00 | 0.00 |
May | 0.607774E+10 | -0.584474E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233003769.5 | 60.05 | 0.00 | 0.00 |
June | 0.582224E+10 | -0.559779E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224449185.9 | 60.05 | 0.00 | 0.00 |
July | 0.530903E+10 | -0.507786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231165319.6 | 60.05 | 0.00 | 0.00 |
August | 0.571437E+10 | -0.548231E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232059920.0 | 60.05 | 0.00 | 0.00 |
September | 0.514423E+10 | -0.491783E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226402685.0 | 60.05 | 0.00 | 0.00 |
October | 0.541897E+10 | -0.517772E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241250612.9 | 60.05 | 0.00 | 0.00 |
November | 0.551749E+10 | -0.527198E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -245503719.6 | 60.05 | 0.00 | 0.00 |
December | 0.568629E+10 | -0.542781E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -258479887.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.680659E+11 | -0.652084E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.285747E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.514423E+10 | -0.610038E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -259424049.2 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.634697E+10 | -0.491783E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224449185.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.63 | 0.48 | 10-JAN-10:00 | 713.47 | 12.48 | 5.83 | 72.33 | 611.37 | 23.38 | 47.00 | 48.83 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-11:39 | 2981.23 | 32.97 | 170.33 | 176.00 | 2619.02 | 36.28 | 191.50 | 161.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 6785.08 | 32.86 | 280.50 | 301.67 | 5920.64 | 34.29 | 289.17 | 285.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 9571.07 | 31.47 | 288.83 | 388.33 | 1917.83 | 21.64 | 278.00 | 348.67 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-05:40 | 4661.54 | 21.84 | 151.17 | 463.17 | 1387.47 | 20.39 | 300.17 | 411.00 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:19 | 2265.74 | 17.95 | 50.50 | 487.17 | 1262.55 | 20.16 | 318.33 | 426.83 |
July | 562.83 | 0.55 | 0.48 | 01-JUL-04:00 | 2698.17 | 18.55 | 63.33 | 483.33 | 1290.93 | 20.18 | 301.33 | 415.67 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 6830.84 | 27.01 | 257.50 | 413.83 | 1468.84 | 20.77 | 265.17 | 368.50 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 5540.80 | 30.92 | 278.33 | 321.33 | 1930.41 | 22.31 | 221.17 | 286.83 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 3062.46 | 31.54 | 223.83 | 237.50 | 2555.45 | 33.84 | 239.50 | 217.00 |
November | 135.83 | 0.57 | 0.48 | 01-NOV-09:00 | 1058.12 | 21.97 | 56.00 | 122.50 | 960.78 | 32.20 | 105.17 | 99.50 |
December | 71.17 | 0.82 | 0.48 | 05-DEC-11:30 | 204.51 | 6.79 | 0.00 | 12.33 | 139.89 | 10.79 | 0.00 | 1.83 |
Annual Sum or Average | 4053.17 | 0.55 | 4559.98 | 24.80 | 1826.17 | 3479.50 | 1918.95 | 23.80 | 2556.50 | 3071.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 204.51 | 6.79 | 0.00 | 12.33 | 139.89 | 10.79 | 0.00 | 1.83 | |
Maximum of Months | 583.50 | 0.82 | 0.48 | 9571.07 | 32.97 | 288.83 | 487.17 | 5920.64 | 36.28 | 318.33 | 426.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.48 | 16-JAN-12:20 | 329.59 | 11.26 | 1.67 | 40.83 | 201.92 | 14.02 | 6.83 | 15.00 |
February | 205.83 | 0.61 | 0.48 | 02-FEB-10:09 | 1085.55 | 17.72 | 46.33 | 147.83 | 731.64 | 22.18 | 88.67 | 108.83 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2731.69 | 21.85 | 114.50 | 283.00 | 1768.62 | 24.30 | 168.67 | 251.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 3517.25 | 23.48 | 135.50 | 393.00 | 2159.63 | 24.66 | 208.67 | 355.50 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 4606.85 | 22.83 | 181.33 | 470.50 | 2418.96 | 23.86 | 230.00 | 431.17 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:49 | 3981.76 | 22.32 | 197.50 | 504.50 | 1779.04 | 22.76 | 245.33 | 451.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:49 | 3966.52 | 22.36 | 199.00 | 491.17 | 2072.82 | 23.38 | 248.00 | 437.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:00 | 3269.33 | 21.71 | 147.00 | 413.67 | 1683.95 | 22.91 | 205.50 | 371.17 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2551.48 | 21.71 | 132.33 | 307.17 | 1335.23 | 22.73 | 157.83 | 266.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:49 | 1350.26 | 20.39 | 97.17 | 217.33 | 789.17 | 21.33 | 86.67 | 169.67 |
November | 135.83 | 0.68 | 0.48 | 01-NOV-10:09 | 448.42 | 16.69 | 34.33 | 78.50 | 263.26 | 19.09 | 36.83 | 25.83 |
December | 71.17 | 0.93 | 0.70 | 04-DEC-10:00 | 111.79 | 6.95 | 0.00 | 0.00 | 64.95 | 9.24 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 3102.14 | 21.23 | 1286.67 | 3347.50 | 1653.46 | 22.61 | 1683.00 | 2883.17 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 111.79 | 6.95 | 0.00 | 0.00 | 64.95 | 9.24 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.70 | 4606.85 | 23.48 | 199.00 | 504.50 | 2418.96 | 24.66 | 248.00 | 451.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.85 | 0.52 | 28-JAN-12:09 | 191.21 | 8.68 | 0.00 | 8.83 | 111.02 | 11.08 | 0.00 | 0.00 |
February | 205.83 | 0.65 | 0.48 | 12-FEB-12:09 | 420.56 | 12.98 | 0.00 | 123.83 | 247.42 | 15.37 | 0.00 | 40.33 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:00 | 773.69 | 16.27 | 0.00 | 276.83 | 458.34 | 18.52 | 33.83 | 220.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 1020.67 | 18.53 | 0.00 | 401.00 | 632.15 | 20.75 | 126.17 | 357.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1264.07 | 22.06 | 135.17 | 503.00 | 752.82 | 24.14 | 283.67 | 481.33 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:49 | 1498.57 | 22.45 | 161.17 | 541.17 | 869.40 | 24.74 | 378.67 | 507.83 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:49 | 1360.72 | 22.12 | 149.17 | 522.50 | 770.03 | 23.35 | 329.33 | 475.17 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1052.43 | 20.04 | 66.83 | 430.00 | 600.39 | 20.24 | 120.50 | 379.50 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:49 | 755.95 | 16.38 | 0.00 | 304.50 | 436.42 | 18.49 | 18.33 | 236.83 |
October | 265.50 | 0.59 | 0.48 | 01-OCT-08:20 | 527.01 | 14.40 | 0.00 | 202.00 | 292.64 | 16.57 | 0.00 | 72.00 |
November | 135.83 | 0.78 | 0.52 | 01-NOV-10:20 | 255.36 | 10.55 | 0.00 | 35.00 | 146.31 | 13.15 | 0.00 | 0.00 |
December | 71.17 | 0.98 | 0.83 | 05-DEC-11:30 | 75.54 | 4.04 | 0.00 | 0.00 | 44.26 | 6.18 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 1002.43 | 18.53 | 512.33 | 3348.67 | 584.33 | 20.39 | 1290.50 | 2770.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 75.54 | 4.04 | 0.00 | 0.00 | 44.26 | 6.18 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.98 | 0.83 | 1498.57 | 22.45 | 161.17 | 541.17 | 869.40 | 24.74 | 378.67 | 507.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.77 | 0.48 | 23-JAN-13:20 | 277.81 | 10.88 | 1.67 | 28.17 | 167.06 | 13.59 | 2.17 | 6.50 |
February | 205.83 | 0.58 | 0.48 | 02-FEB-11:30 | 929.02 | 20.26 | 61.83 | 159.83 | 571.18 | 22.43 | 76.33 | 100.33 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 2063.47 | 21.61 | 99.50 | 295.00 | 1243.92 | 23.76 | 135.17 | 265.83 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:30 | 3973.69 | 23.38 | 139.50 | 393.50 | 2011.42 | 23.32 | 175.17 | 357.67 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:49 | 3142.84 | 20.12 | 118.00 | 489.17 | 1570.64 | 20.75 | 118.50 | 447.17 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:40 | 3323.24 | 19.57 | 111.83 | 517.50 | 1683.54 | 20.49 | 123.83 | 468.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2879.42 | 19.49 | 115.17 | 508.67 | 1491.95 | 20.36 | 130.83 | 457.17 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:19 | 2612.76 | 20.73 | 117.83 | 427.83 | 1578.60 | 22.22 | 150.50 | 386.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 2093.61 | 22.55 | 121.17 | 319.67 | 1266.72 | 23.53 | 132.50 | 273.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-08:39 | 1058.35 | 20.20 | 84.17 | 223.67 | 608.72 | 21.50 | 70.67 | 165.67 |
November | 135.83 | 0.68 | 0.48 | 01-NOV-11:09 | 431.09 | 16.26 | 34.00 | 76.00 | 288.29 | 20.76 | 46.00 | 30.50 |
December | 71.17 | 0.96 | 0.70 | 04-DEC-11:30 | 97.18 | 6.34 | 0.00 | 0.00 | 55.95 | 8.61 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2507.48 | 20.09 | 1004.67 | 3439.00 | 1348.51 | 21.31 | 1161.67 | 2959.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 97.18 | 6.34 | 0.00 | 0.00 | 55.95 | 8.61 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.96 | 0.70 | 3973.69 | 23.38 | 139.50 | 517.50 | 2011.42 | 23.76 | 175.17 | 468.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.64 | 0.48 | 10-JAN-10:00 | 648.84 | 8.00 | 5.50 | 69.83 | 493.11 | 12.57 | 6.00 | 43.67 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-11:50 | 2787.03 | 29.85 | 153.50 | 172.00 | 2510.82 | 36.02 | 191.17 | 158.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 6581.84 | 32.18 | 273.83 | 300.00 | 5771.48 | 33.92 | 284.83 | 284.17 |
April | 421.83 | 0.53 | 0.48 | 01-APR-07:40 | 9383.03 | 30.36 | 283.67 | 385.83 | 1774.67 | 19.11 | 66.17 | 344.17 |
May | 545.00 | 0.55 | 0.48 | 01-MAY-05:49 | 4535.68 | 19.18 | 114.67 | 459.67 | 1294.82 | 18.02 | 44.50 | 405.83 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:30 | 2155.70 | 14.30 | 0.00 | 483.83 | 1185.75 | 17.70 | 42.33 | 421.33 |
July | 562.83 | 0.55 | 0.48 | 01-JUL-04:00 | 2584.93 | 14.98 | 15.67 | 480.33 | 1210.55 | 17.68 | 39.33 | 411.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:00 | 6694.37 | 25.32 | 239.83 | 410.67 | 1367.05 | 18.17 | 31.67 | 363.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 5391.59 | 29.95 | 269.17 | 319.67 | 1823.06 | 19.76 | 48.83 | 284.50 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 2891.97 | 29.00 | 205.50 | 235.83 | 2467.87 | 33.10 | 233.00 | 214.50 |
November | 135.83 | 0.57 | 0.48 | 01-NOV-10:09 | 788.76 | 8.71 | 0.00 | 120.83 | 888.33 | 28.87 | 94.17 | 92.33 |
December | 71.17 | 0.84 | 0.48 | 08-DEC-11:30 | 187.06 | 2.85 | 0.00 | 8.33 | 131.29 | 6.69 | 0.00 | 1.17 |
Annual Sum or Average | 4053.17 | 0.55 | 4414.45 | 22.02 | 1561.33 | 3446.83 | 1819.10 | 21.42 | 1082.00 | 3025.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 187.06 | 2.85 | 0.00 | 8.33 | 131.29 | 6.69 | 0.00 | 1.17 | |
Maximum of Months | 583.50 | 0.84 | 0.48 | 9383.03 | 32.18 | 283.67 | 483.83 | 5771.48 | 36.02 | 284.83 | 421.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.75 | 0.48 | 23-JAN-10:00 | 316.88 | 10.62 | 1.67 | 37.17 | 193.17 | 13.68 | 5.50 | 14.33 |
February | 205.83 | 0.61 | 0.48 | 02-FEB-10:20 | 1046.06 | 17.21 | 45.67 | 146.33 | 701.51 | 21.97 | 83.33 | 104.67 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:20 | 2641.93 | 21.42 | 113.17 | 282.17 | 1625.92 | 22.71 | 141.33 | 247.00 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 3313.70 | 21.39 | 109.67 | 389.83 | 2077.74 | 24.47 | 196.50 | 352.50 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 4495.34 | 22.40 | 181.33 | 468.50 | 2329.70 | 23.70 | 217.83 | 427.83 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:00 | 3882.81 | 21.87 | 196.00 | 501.67 | 1703.76 | 22.57 | 225.67 | 446.17 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:00 | 3827.39 | 21.05 | 173.83 | 487.83 | 1988.25 | 22.63 | 219.67 | 432.33 |
August | 467.17 | 0.54 | 0.48 | 01-AUG-04:00 | 3177.55 | 21.27 | 146.67 | 412.17 | 1612.56 | 22.73 | 190.00 | 368.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2448.35 | 21.05 | 128.83 | 304.50 | 1278.20 | 22.53 | 147.67 | 263.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:49 | 1238.99 | 18.32 | 75.00 | 215.00 | 757.46 | 21.11 | 84.67 | 165.17 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-10:09 | 432.61 | 16.16 | 34.33 | 75.67 | 252.19 | 18.83 | 36.50 | 23.33 |
December | 71.17 | 0.94 | 0.70 | 04-DEC-10:00 | 107.17 | 6.39 | 0.00 | 0.00 | 61.88 | 8.91 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 2995.21 | 20.37 | 1206.17 | 3320.83 | 1581.24 | 22.22 | 1548.67 | 2845.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 107.17 | 6.39 | 0.00 | 0.00 | 61.88 | 8.91 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.70 | 4495.34 | 22.40 | 196.00 | 501.67 | 2329.70 | 24.47 | 225.67 | 446.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.86 | 0.52 | 28-JAN-12:30 | 182.44 | 5.01 | 0.00 | 7.00 | 106.05 | 8.39 | 0.00 | 0.00 |
February | 205.83 | 0.66 | 0.48 | 16-FEB-12:20 | 402.72 | 9.33 | 0.00 | 119.00 | 237.45 | 12.88 | 0.00 | 32.00 |
March | 329.50 | 0.56 | 0.48 | 01-MAR-09:00 | 743.74 | 12.97 | 0.00 | 274.50 | 441.83 | 16.40 | 0.00 | 215.50 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:00 | 981.76 | 15.43 | 0.00 | 399.33 | 611.22 | 18.98 | 12.17 | 351.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1218.28 | 19.62 | 129.83 | 502.00 | 726.36 | 22.59 | 152.33 | 477.33 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-03:49 | 1444.03 | 19.96 | 150.83 | 537.67 | 835.83 | 23.07 | 178.00 | 504.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:00 | 1311.57 | 19.66 | 138.83 | 520.17 | 740.06 | 21.09 | 125.83 | 470.83 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1013.95 | 17.21 | 63.83 | 427.33 | 604.03 | 20.29 | 77.17 | 378.17 |
September | 356.33 | 0.56 | 0.48 | 01-SEP-06:49 | 727.54 | 13.01 | 0.00 | 301.67 | 420.55 | 16.37 | 1.00 | 226.83 |
October | 265.50 | 0.60 | 0.48 | 01-OCT-08:30 | 507.01 | 10.65 | 0.00 | 197.67 | 281.17 | 14.07 | 0.00 | 57.33 |
November | 135.83 | 0.79 | 0.52 | 01-NOV-10:20 | 244.17 | 6.65 | 0.00 | 31.67 | 139.95 | 10.36 | 0.00 | 0.00 |
December | 71.17 | 0.98 | 0.87 | 04-DEC-10:50 | 71.85 | 1.37 | 0.00 | 0.00 | 42.17 | 3.80 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 965.29 | 15.58 | 483.33 | 3318.00 | 565.64 | 18.59 | 546.50 | 2713.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 71.85 | 1.37 | 0.00 | 0.00 | 42.17 | 3.80 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.98 | 0.87 | 1444.03 | 19.96 | 150.83 | 537.67 | 835.83 | 23.07 | 178.00 | 504.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.48 | 23-JAN-13:20 | 267.43 | 10.38 | 1.33 | 24.50 | 160.00 | 13.58 | 2.17 | 5.67 |
February | 205.83 | 0.59 | 0.48 | 04-FEB-11:00 | 852.34 | 17.48 | 45.00 | 154.83 | 549.15 | 22.36 | 76.50 | 94.50 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 1996.51 | 21.15 | 98.17 | 293.17 | 1168.66 | 22.53 | 121.00 | 260.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:30 | 3874.28 | 22.97 | 139.50 | 391.50 | 1934.23 | 23.19 | 172.50 | 353.67 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:49 | 3062.58 | 19.67 | 118.00 | 487.00 | 1506.87 | 20.60 | 109.33 | 443.50 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:40 | 3242.07 | 19.10 | 111.67 | 514.33 | 1619.81 | 20.32 | 116.33 | 464.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-05:10 | 2794.19 | 19.03 | 115.00 | 504.33 | 1435.28 | 20.19 | 124.83 | 452.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:30 | 2529.17 | 20.11 | 114.67 | 425.83 | 1524.08 | 22.08 | 147.00 | 382.00 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-07:10 | 2000.09 | 20.70 | 104.50 | 316.17 | 1222.57 | 23.42 | 131.17 | 268.50 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-08:50 | 1027.50 | 19.82 | 84.17 | 221.83 | 585.65 | 21.40 | 70.83 | 160.00 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-11:39 | 414.23 | 15.90 | 34.00 | 72.67 | 276.19 | 20.73 | 46.00 | 28.67 |
December | 71.17 | 0.96 | 0.70 | 04-DEC-11:30 | 93.31 | 6.06 | 0.00 | 0.00 | 53.39 | 8.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2432.70 | 19.39 | 966.00 | 3406.17 | 1295.31 | 21.09 | 1117.67 | 2913.17 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 93.31 | 6.06 | 0.00 | 0.00 | 53.39 | 8.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.96 | 0.70 | 3874.28 | 22.97 | 139.50 | 514.33 | 1934.23 | 23.42 | 172.50 | 464.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.64 | 0.48 | 10-JAN-10:00 | 648.86 | 8.01 | 5.50 | 69.83 | 493.09 | 12.57 | 6.00 | 43.50 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-11:50 | 2787.07 | 29.85 | 153.50 | 172.00 | 2510.77 | 36.02 | 191.17 | 158.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 6581.83 | 32.18 | 273.83 | 300.00 | 5771.37 | 33.92 | 284.83 | 284.17 |
April | 421.83 | 0.53 | 0.48 | 01-APR-07:40 | 9382.96 | 30.36 | 283.67 | 385.83 | 1774.54 | 19.11 | 66.17 | 344.17 |
May | 545.00 | 0.55 | 0.48 | 01-MAY-05:49 | 4535.56 | 19.18 | 114.67 | 459.67 | 1294.73 | 18.02 | 44.67 | 405.67 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:30 | 2155.57 | 14.30 | 0.00 | 483.83 | 1185.66 | 17.70 | 42.50 | 421.33 |
July | 562.83 | 0.55 | 0.48 | 01-JUL-04:00 | 2584.80 | 14.99 | 15.67 | 480.33 | 1210.45 | 17.68 | 39.33 | 411.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:00 | 6694.27 | 25.32 | 239.83 | 410.67 | 1366.94 | 18.17 | 31.67 | 363.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 5391.54 | 29.95 | 269.17 | 319.67 | 1822.96 | 19.76 | 48.83 | 284.50 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 2891.95 | 29.00 | 205.50 | 235.83 | 2467.81 | 33.10 | 233.00 | 214.50 |
November | 135.83 | 0.57 | 0.48 | 01-NOV-10:09 | 788.79 | 8.72 | 0.00 | 120.83 | 888.31 | 28.87 | 94.17 | 92.33 |
December | 71.17 | 0.84 | 0.48 | 08-DEC-11:30 | 187.07 | 2.85 | 0.00 | 8.33 | 131.29 | 6.69 | 0.00 | 1.17 |
Annual Sum or Average | 4053.17 | 0.55 | 4414.38 | 22.02 | 1561.33 | 3446.83 | 1819.00 | 21.42 | 1082.33 | 3024.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 187.07 | 2.85 | 0.00 | 8.33 | 131.29 | 6.69 | 0.00 | 1.17 | |
Maximum of Months | 583.50 | 0.84 | 0.48 | 9382.96 | 32.18 | 283.67 | 483.83 | 5771.37 | 36.02 | 284.83 | 421.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.75 | 0.48 | 23-JAN-10:00 | 316.88 | 10.62 | 1.67 | 37.17 | 193.15 | 13.68 | 5.50 | 14.33 |
February | 205.83 | 0.61 | 0.48 | 02-FEB-10:20 | 1046.05 | 17.21 | 45.67 | 146.33 | 701.48 | 21.97 | 83.33 | 104.67 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:20 | 2641.91 | 21.42 | 113.17 | 282.17 | 1625.86 | 22.71 | 141.33 | 247.00 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 3313.68 | 21.40 | 109.67 | 389.83 | 2077.67 | 24.47 | 196.50 | 352.50 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 4495.31 | 22.40 | 181.33 | 468.50 | 2329.61 | 23.70 | 217.83 | 427.83 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:00 | 3883.59 | 21.90 | 197.00 | 501.67 | 1703.67 | 22.57 | 225.83 | 446.17 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:00 | 3866.70 | 21.95 | 198.83 | 487.83 | 1988.16 | 22.63 | 220.00 | 432.33 |
August | 467.17 | 0.54 | 0.48 | 01-AUG-04:00 | 3177.50 | 21.27 | 146.67 | 412.17 | 1612.48 | 22.73 | 190.17 | 368.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2448.32 | 21.06 | 128.83 | 304.50 | 1278.14 | 22.53 | 147.67 | 263.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:49 | 1238.96 | 18.32 | 75.00 | 215.00 | 757.42 | 21.11 | 84.67 | 165.17 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-10:09 | 432.61 | 16.16 | 34.33 | 75.67 | 252.17 | 18.83 | 36.50 | 23.33 |
December | 71.17 | 0.94 | 0.70 | 04-DEC-10:00 | 107.17 | 6.39 | 0.00 | 0.00 | 61.87 | 8.91 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 3000.76 | 20.50 | 1232.17 | 3320.83 | 1581.17 | 22.22 | 1549.33 | 2845.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 107.17 | 6.39 | 0.00 | 0.00 | 61.87 | 8.91 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.70 | 4495.31 | 22.40 | 198.83 | 501.67 | 2329.61 | 24.47 | 225.83 | 446.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.86 | 0.52 | 28-JAN-12:30 | 182.43 | 5.01 | 0.00 | 7.00 | 106.05 | 8.39 | 0.00 | 0.00 |
February | 205.83 | 0.66 | 0.48 | 16-FEB-12:20 | 402.71 | 9.33 | 0.00 | 119.00 | 237.44 | 12.88 | 0.00 | 32.00 |
March | 329.50 | 0.56 | 0.48 | 01-MAR-09:00 | 743.72 | 12.97 | 0.00 | 274.50 | 441.80 | 16.40 | 0.00 | 215.50 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:00 | 981.74 | 15.43 | 0.00 | 399.33 | 611.18 | 18.98 | 12.17 | 351.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1218.25 | 19.62 | 129.83 | 502.00 | 726.32 | 22.59 | 152.33 | 477.17 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-03:49 | 1444.00 | 19.97 | 150.83 | 537.67 | 835.78 | 23.07 | 178.00 | 504.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:00 | 1311.54 | 19.66 | 138.83 | 520.17 | 740.01 | 21.09 | 125.83 | 470.83 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1013.91 | 17.21 | 63.83 | 427.33 | 603.99 | 20.29 | 77.17 | 378.17 |
September | 356.33 | 0.56 | 0.48 | 01-SEP-06:49 | 727.51 | 13.02 | 0.00 | 301.67 | 420.52 | 16.37 | 1.00 | 226.83 |
October | 265.50 | 0.60 | 0.48 | 01-OCT-08:30 | 506.98 | 10.65 | 0.00 | 197.67 | 281.14 | 14.07 | 0.00 | 57.33 |
November | 135.83 | 0.79 | 0.52 | 01-NOV-10:20 | 244.16 | 6.66 | 0.00 | 31.67 | 139.94 | 10.36 | 0.00 | 0.00 |
December | 71.17 | 0.98 | 0.87 | 04-DEC-10:50 | 71.85 | 1.38 | 0.00 | 0.00 | 42.17 | 3.81 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 965.27 | 15.58 | 483.33 | 3318.00 | 565.60 | 18.59 | 546.50 | 2713.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 71.85 | 1.38 | 0.00 | 0.00 | 42.17 | 3.81 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.98 | 0.87 | 1444.00 | 19.97 | 150.83 | 537.67 | 835.78 | 23.07 | 178.00 | 504.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.48 | 23-JAN-13:20 | 267.43 | 10.38 | 1.33 | 24.50 | 159.99 | 13.58 | 2.17 | 5.67 |
February | 205.83 | 0.59 | 0.48 | 04-FEB-11:00 | 852.33 | 17.48 | 45.00 | 154.83 | 549.13 | 22.36 | 76.50 | 94.50 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 1996.49 | 21.15 | 98.17 | 293.17 | 1168.61 | 22.53 | 121.00 | 260.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:30 | 3874.26 | 22.97 | 139.50 | 391.50 | 1934.16 | 23.19 | 172.50 | 353.67 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:49 | 3062.54 | 19.67 | 118.00 | 487.00 | 1506.80 | 20.60 | 109.33 | 443.50 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:40 | 3242.02 | 19.10 | 111.67 | 514.33 | 1619.73 | 20.32 | 116.33 | 464.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-05:10 | 2794.13 | 19.03 | 115.00 | 504.33 | 1435.20 | 20.19 | 124.83 | 452.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:30 | 2529.13 | 20.11 | 114.67 | 425.67 | 1524.01 | 22.08 | 147.00 | 382.00 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-07:10 | 2000.06 | 20.70 | 104.50 | 316.17 | 1222.52 | 23.42 | 131.17 | 268.50 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-08:50 | 1027.47 | 19.83 | 84.17 | 221.83 | 585.61 | 21.40 | 70.83 | 160.00 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-11:39 | 414.23 | 15.90 | 34.00 | 72.67 | 276.18 | 20.73 | 46.00 | 28.67 |
December | 71.17 | 0.96 | 0.70 | 04-DEC-11:30 | 93.31 | 6.06 | 0.00 | 0.00 | 53.38 | 8.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2432.66 | 19.39 | 966.00 | 3406.00 | 1295.25 | 21.10 | 1117.67 | 2913.17 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 93.31 | 6.06 | 0.00 | 0.00 | 53.38 | 8.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.96 | 0.70 | 3874.26 | 22.97 | 139.50 | 514.33 | 1934.16 | 23.42 | 172.50 | 464.17 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122614E+11 | 52141.05 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.725774E+10 | 51057.85 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200179E+10 | 44754.91 | 01-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51879016.54 | 9082.39 | 25-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4528485.77 | 5589.20 | 27-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 127048.63 | 5.69 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 237258.79 | 5.24 | 24-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3018422.51 | 3987.06 | 31-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22574725.16 | 5490.22 | 16-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88197444.97 | 3602.86 | 21-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107452E+11 | 45206.92 | 29-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177433E+11 | 50629.63 | 15-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 127048.63 | 5.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177433E+11 | 52141.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187649E+10 | 14341.96 | 02-JAN-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464332E+09 | 14289.20 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22781458.05 | 14288.63 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312638E+09 | 14290.80 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.862055E+09 | 14292.02 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187649E+10 | 14341.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160443E+11 | 12143.73 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113867E+11 | 11863.45 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.836118E+10 | 11745.89 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248398E+10 | 11866.96 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.797495E+09 | 11988.72 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193319E+09 | 11847.64 | 02-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143312E+09 | 11841.87 | 17-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387483E+09 | 11861.31 | 30-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172547E+10 | 12330.84 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.583485E+10 | 11744.50 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132562E+11 | 11751.59 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161756E+11 | 11752.64 | 15-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.143312E+09 | 11744.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161756E+11 | 12330.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.747400E+10 | 7888.49 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530245E+10 | 7706.60 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271657E+10 | 7630.37 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.455336E+09 | 7619.31 | 05-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67850848.73 | 7597.58 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143316E+10 | 7610.77 | 19-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.531402E+10 | 7634.16 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.703789E+10 | 7634.78 | 26-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.747400E+10 | 7888.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102957E+11 | 8323.47 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.818528E+10 | 8134.00 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.613967E+10 | 8054.99 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131649E+10 | 8052.28 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145806E+09 | 8050.09 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238484E+10 | 8054.36 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.747751E+10 | 8059.61 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.974907E+10 | 8060.35 | 26-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.102957E+11 | 8323.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.765623E+10 | 8100.34 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.583423E+10 | 7913.26 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385216E+10 | 7834.75 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.545788E+09 | 7818.48 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6419405.01 | 2653.84 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131166E+09 | 7800.58 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184139E+10 | 7814.24 | 19-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537145E+10 | 7838.49 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.710713E+10 | 7839.30 | 15-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.323459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.765623E+10 | 8100.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122770E+11 | 53429.49 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.713476E+10 | 50413.11 | 27-FEB-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203883E+10 | 42971.53 | 01-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44123178.80 | 6808.08 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2085235.34 | 1527.60 | 16-MAY-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 133813.94 | 5.24 | 29-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 223266.46 | 5.10 | 11-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1231268.35 | 975.77 | 31-AUG-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8094098.91 | 4219.31 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205176E+09 | 9213.75 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108271E+11 | 42762.25 | 30-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172442E+11 | 48400.67 | 15-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 133813.94 | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172442E+11 | 53429.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.717272E+10 | 20398.06 | 07-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419040E+10 | 20395.90 | 15-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147954E+10 | 20398.20 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86346854.41 | 20387.76 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.997418E+09 | 20401.64 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.514132E+10 | 20396.54 | 02-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713867E+10 | 20391.31 | 21-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717272E+10 | 20401.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.865944E+10 | 12433.94 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.475801E+10 | 12383.03 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243845E+10 | 12381.71 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.423946E+09 | 12377.99 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173585E+09 | 12297.14 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215705E+10 | 12392.62 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.663346E+10 | 12383.32 | 15-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933017E+10 | 12390.24 | 21-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.933017E+10 | 12433.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650009E+10 | 8291.53 | 12-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418230E+10 | 8227.16 | 21-FEB-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209514E+10 | 8244.36 | 27-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.355338E+09 | 8231.51 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 209549.20 | 947.21 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152484E+09 | 8166.08 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189120E+10 | 8224.52 | 19-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.540530E+10 | 8235.00 | 09-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658713E+10 | 8221.99 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.658713E+10 | 8291.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.874401E+10 | 8525.65 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.607789E+10 | 8477.51 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384790E+10 | 8475.08 | 11-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.591905E+09 | 8462.78 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175337E+09 | 8457.23 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250900E+10 | 8480.73 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.714600E+10 | 8477.37 | 14-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877630E+10 | 8476.41 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877630E+10 | 8525.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.646776E+10 | 8231.66 | 12-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.443578E+10 | 8169.00 | 21-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274731E+10 | 8177.64 | 03-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435340E+09 | 8160.49 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 713511.78 | 809.82 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86671.72 | 322.51 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215004E+09 | 8125.87 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212087E+10 | 8166.88 | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.528230E+10 | 8175.56 | 09-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648625E+10 | 8164.88 | 08-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648625E+10 | 8231.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172126E+11 | 54317.70 | 12-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104813E+11 | 51252.47 | 27-FEB-08:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358086E+10 | 46793.99 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208211E+09 | 7222.92 | 03-APR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2597390.52 | 1576.92 | 19-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113705.27 | 5.38 | 29-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 132460.64 | 5.30 | 07-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1666533.00 | 3242.62 | 31-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16518128.87 | 5814.03 | 26-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.975378E+09 | 8323.35 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153528E+11 | 46364.24 | 30-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225022E+11 | 52652.19 | 15-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.703344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 113705.27 | 5.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225022E+11 | 54317.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148959E+11 | 27162.04 | 21-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.976126E+10 | 27158.38 | 15-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.575623E+10 | 27159.56 | 10-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101219E+10 | 27153.56 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274275E+09 | 27168.83 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.453447E+10 | 27180.21 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124843E+11 | 27161.63 | 03-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150724E+11 | 27157.32 | 30-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150724E+11 | 27180.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122077E+11 | 14792.66 | 12-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738927E+10 | 14490.54 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438927E+10 | 14489.09 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111293E+10 | 14472.15 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29576875.87 | 10561.11 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18116084.94 | 13964.44 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.634957E+09 | 14464.39 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403502E+10 | 14494.35 | 20-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101261E+11 | 14487.46 | 14-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131947E+11 | 14484.67 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131947E+11 | 14792.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.870501E+10 | 9563.57 | 12-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.599545E+10 | 9382.98 | 16-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340774E+10 | 9374.18 | 16-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.774429E+09 | 9373.05 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5906344.93 | 2740.12 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6127497.29 | 9313.23 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.418363E+09 | 9351.87 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314881E+10 | 9379.52 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.767802E+10 | 9368.32 | 10-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.896761E+10 | 9364.84 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896761E+10 | 9563.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123942E+11 | 9854.96 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.920206E+10 | 9656.11 | 04-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645116E+10 | 9651.36 | 25-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146255E+10 | 9651.64 | 17-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8468072.16 | 4970.79 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11858699.17 | 9598.72 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672080E+09 | 9651.83 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.477236E+10 | 9657.43 | 11-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109323E+11 | 9655.69 | 03-NOV-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127493E+11 | 9654.71 | 20-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.127493E+11 | 9854.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885604E+10 | 9721.09 | 12-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.647494E+10 | 9522.40 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442623E+10 | 9528.27 | 16-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101818E+10 | 9510.40 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31788714.62 | 6882.94 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18358740.26 | 9086.83 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.651219E+09 | 9505.20 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363519E+10 | 9533.58 | 27-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772010E+10 | 9520.87 | 07-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.902997E+10 | 9518.57 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.902997E+10 | 9721.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7710094.33 | 7708783.86 | 7138.76 | 20-JAN-07:01 | 7138.76 | 0.00 |
February | 0.00 | 0.00 | 10559775.29 | 10475696.90 | 6357.46 | 02-FEB-07:01 | 6357.46 | 0.00 |
March | 0.00 | 0.00 | 33256014.71 | 32981139.50 | 3926.03 | 18-MAR-06:03 | 3926.03 | 0.00 |
April | 0.00 | 0.00 | 41751952.17 | 41750218.24 | 4581.11 | 08-APR-06:03 | 4581.11 | 0.00 |
May | 0.00 | 0.00 | 0.427543E+10 | 0.426922E+10 | 39928.12 | 31-MAY-16:00 | 39928.12 | 0.00 |
June | 0.00 | 0.00 | 0.220110E+11 | 0.211312E+11 | 65918.36 | 30-JUN-14:30 | 61061.75 | 0.00 |
July | 0.00 | 0.00 | 0.311428E+11 | 0.287281E+11 | 68249.43 | 11-JUL-15:50 | 64556.54 | 0.00 |
August | 0.00 | 0.00 | 0.167525E+11 | 0.155835E+11 | 64525.35 | 11-AUG-15:50 | 64525.35 | 0.00 |
September | 0.00 | 0.00 | 0.277780E+09 | 0.263435E+09 | 10512.13 | 07-SEP-16:00 | 10512.13 | 0.00 |
October | 0.00 | 0.00 | 36689904.61 | 35567252.39 | 4392.71 | 21-OCT-06:03 | 4392.71 | 0.00 |
November | 0.00 | 0.00 | 8025067.61 | 8025067.61 | 5725.02 | 15-NOV-07:01 | 5725.02 | 0.00 |
December | 0.00 | 0.00 | 5277832.66 | 5277832.66 | 6436.91 | 21-DEC-07:01 | 6436.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.746028E+11 | 0.701173E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 5277832.66 | 5277832.66 | 3926.03 | 3926.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.311428E+11 | 0.287281E+11 | 68249.43 | 64556.54 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8129165.26 | 8129165.26 | 6624.18 | 20-JAN-07:01 | 6624.18 | 0.00 |
February | 0.00 | 0.00 | 7800275.92 | 7797071.41 | 8076.46 | 09-FEB-07:01 | 8076.46 | 0.00 |
March | 0.00 | 0.00 | 17112777.52 | 17068130.90 | 9292.68 | 22-MAR-06:01 | 9292.68 | 0.00 |
April | 0.00 | 0.00 | 33477287.97 | 33477287.97 | 8565.65 | 05-APR-06:01 | 8565.65 | 0.00 |
May | 0.00 | 0.00 | 0.455631E+10 | 0.455224E+10 | 40269.72 | 31-MAY-16:00 | 40269.72 | 0.00 |
June | 0.00 | 0.00 | 0.218593E+11 | 0.209847E+11 | 67664.87 | 30-JUN-12:10 | 59775.58 | 0.00 |
July | 0.00 | 0.00 | 0.293331E+11 | 0.270392E+11 | 64383.53 | 11-JUL-15:30 | 60587.21 | 0.00 |
August | 0.00 | 0.00 | 0.151415E+11 | 0.139875E+11 | 59267.91 | 11-AUG-15:20 | 59267.91 | 0.00 |
September | 0.00 | 0.00 | 0.243958E+09 | 0.231094E+09 | 9140.23 | 07-SEP-16:00 | 9140.23 | 0.00 |
October | 0.00 | 0.00 | 16629265.91 | 16554485.97 | 8933.29 | 20-OCT-06:01 | 8933.29 | 0.00 |
November | 0.00 | 0.00 | 8572810.07 | 8572810.07 | 7122.60 | 02-NOV-06:01 | 7122.60 | 0.00 |
December | 0.00 | 0.00 | 6155515.24 | 6155515.24 | 5642.12 | 21-DEC-07:11 | 5642.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.712320E+11 | 0.668925E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6155515.24 | 6155515.24 | 5642.12 | 5642.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.293331E+11 | 0.270392E+11 | 67664.87 | 60587.21 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1471434.30 | 1471434.30 | 2261.86 | 19-JAN-07:11 | 2261.86 | 0.00 |
February | 0.00 | 0.00 | 2613637.62 | 2603951.67 | 4788.13 | 09-FEB-07:01 | 4788.13 | 0.00 |
March | 0.00 | 0.00 | 14735360.64 | 14508595.02 | 5493.69 | 23-MAR-06:01 | 5493.69 | 0.00 |
April | 0.00 | 0.00 | 40387051.89 | 40352915.72 | 5574.91 | 12-APR-06:01 | 5574.91 | 0.00 |
May | 0.00 | 0.00 | 0.439870E+10 | 0.439153E+10 | 41735.77 | 31-MAY-16:00 | 41735.77 | 0.00 |
June | 0.00 | 0.00 | 0.220355E+11 | 0.211305E+11 | 72349.67 | 30-JUN-12:30 | 64603.47 | 0.00 |
July | 0.00 | 0.00 | 0.295393E+11 | 0.272302E+11 | 66778.60 | 21-JUL-14:30 | 66778.60 | 0.00 |
August | 0.00 | 0.00 | 0.149291E+11 | 0.136992E+11 | 61615.94 | 11-AUG-15:40 | 61615.94 | 0.00 |
September | 0.00 | 0.00 | 0.226125E+09 | 0.210815E+09 | 9746.64 | 10-SEP-11:32 | 9746.64 | 0.00 |
October | 0.00 | 0.00 | 12111665.35 | 11803325.97 | 5507.53 | 02-OCT-06:03 | 5507.53 | 0.00 |
November | 0.00 | 0.00 | 1093102.80 | 1093102.80 | 989.10 | 22-NOV-06:17 | 989.10 | 0.00 |
December | 0.00 | 0.00 | 1594285.17 | 1594285.17 | 1571.83 | 23-DEC-07:15 | 1571.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.712027E+11 | 0.667357E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1093102.80 | 1093102.80 | 989.10 | 989.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.295393E+11 | 0.272302E+11 | 72349.67 | 66778.60 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 66567.82 | 320924.52 | 12-JAN-07:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 48593.43 | 317254.61 | 27-FEB-07:13 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 24335.33 | 285206.03 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4733.82 | 254302.43 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 332.90 | 37957.60 | 27-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 68.51 | 15039.59 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.74 | 17665.22 | 05-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 166.18 | 74086.38 | 31-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2090.40 | 235093.18 | 26-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 15761.80 | 255475.83 | 12-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56343.85 | 286282.33 | 29-NOV-07:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 72528.71 | 304384.40 | 15-DEC-07:11 |
Annual Sum or Average | 0.00 | 24191.47 | ||||
Minimum of Months | 0.00 | 0.00 | 54.74 | 15039.59 | ||
Maximum of Months | 0.00 | 0.00 | 72528.71 | 320924.52 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2106.65 | 7651.70 | 05-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2119.74 | 7651.73 | 02-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2267.31 | 7651.66 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2107.71 | 7651.55 | 07-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2172.08 | 7651.62 | 04-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2149.54 | 7461.26 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1886.34 | 7150.85 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2036.90 | 6936.49 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1887.74 | 6889.75 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1923.51 | 7094.18 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2024.11 | 7375.22 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2016.79 | 7651.57 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 2057.87 | ||||
Minimum of Months | 0.00 | 0.00 | 1886.34 | 6889.75 | ||
Maximum of Months | 0.00 | 0.00 | 2267.31 | 7651.73 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255093E+10 | 0.42 | 3086.44 | 02-JAN-05:01 | 0.84 |
February | 0.201868E+10 | 0.40 | 3086.44 | 01-FEB-07:01 | 0.84 |
March | 0.177590E+10 | 0.33 | 3086.44 | 01-MAR-07:01 | 0.84 |
April | 0.200819E+10 | 0.33 | 5882.03 | 24-APR-06:02 | 1.23 |
May | 0.360794E+10 | 0.42 | 7031.63 | 17-MAY-06:03 | 1.36 |
June | 0.522437E+10 | 0.52 | 8601.06 | 30-JUN-14:30 | 1.53 |
July | 0.543843E+10 | 0.51 | 10347.97 | 12-JUL-15:20 | 1.73 |
August | 0.473333E+10 | 0.48 | 9997.93 | 11-AUG-15:50 | 1.69 |
September | 0.227961E+10 | 0.34 | 5427.48 | 05-SEP-06:03 | 1.16 |
October | 0.158581E+10 | 0.29 | 2270.23 | 03-OCT-14:10 | 0.71 |
November | 0.191163E+10 | 0.35 | 3086.44 | 06-NOV-07:01 | 0.84 |
December | 0.241657E+10 | 0.41 | 3086.44 | 01-DEC-07:01 | 0.84 |
Annual Sum or Average | 0.355514E+11 | 0.40 | |||
Minimum of Months | 0.158581E+10 | 0.29 | 2270.23 | 0.71 | |
Maximum of Months | 0.543843E+10 | 0.52 | 10347.97 | 1.73 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220069E+10 | 0.40 | 3361.66 | 02-JAN-05:01 | 0.91 |
February | 0.182882E+10 | 0.37 | 3361.66 | 01-FEB-06:01 | 0.91 |
March | 0.177587E+10 | 0.33 | 3361.66 | 01-MAR-06:01 | 0.91 |
April | 0.210038E+10 | 0.34 | 5335.37 | 21-APR-15:30 | 1.19 |
May | 0.371721E+10 | 0.44 | 7816.83 | 31-MAY-14:50 | 1.50 |
June | 0.526977E+10 | 0.54 | 9297.97 | 30-JUN-12:10 | 1.66 |
July | 0.493758E+10 | 0.50 | 9521.42 | 12-JUL-12:10 | 1.69 |
August | 0.397104E+10 | 0.45 | 8982.25 | 10-AUG-15:30 | 1.64 |
September | 0.181931E+10 | 0.32 | 3731.77 | 08-SEP-15:30 | 0.96 |
October | 0.155046E+10 | 0.29 | 3361.66 | 10-OCT-06:01 | 0.90 |
November | 0.190225E+10 | 0.36 | 3361.66 | 01-NOV-05:01 | 0.91 |
December | 0.212089E+10 | 0.38 | 3361.66 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.331943E+11 | 0.39 | |||
Minimum of Months | 0.155046E+10 | 0.29 | 3361.66 | 0.90 | |
Maximum of Months | 0.526977E+10 | 0.54 | 9521.42 | 1.69 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.258763E+10 | 0.44 | 3121.01 | 01-JAN-00:42 | 0.83 |
February | 0.218288E+10 | 0.43 | 3121.01 | 01-FEB-05:01 | 0.83 |
March | 0.208610E+10 | 0.37 | 3121.01 | 01-MAR-05:11 | 0.83 |
April | 0.198371E+10 | 0.33 | 4525.87 | 21-APR-15:50 | 1.03 |
May | 0.316817E+10 | 0.40 | 7671.57 | 31-MAY-14:50 | 1.41 |
June | 0.468883E+10 | 0.49 | 8871.01 | 20-JUN-15:30 | 1.54 |
July | 0.440238E+10 | 0.45 | 9091.65 | 12-JUL-15:20 | 1.56 |
August | 0.337279E+10 | 0.40 | 8333.80 | 10-AUG-15:20 | 1.48 |
September | 0.166647E+10 | 0.30 | 3121.01 | 25-SEP-06:02 | 0.83 |
October | 0.179771E+10 | 0.33 | 3121.01 | 03-OCT-06:02 | 0.83 |
November | 0.242765E+10 | 0.44 | 3121.01 | 01-NOV-05:01 | 0.83 |
December | 0.265511E+10 | 0.46 | 3121.01 | 01-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.330194E+11 | 0.40 | |||
Minimum of Months | 0.166647E+10 | 0.30 | 3121.01 | 0.83 | |
Maximum of Months | 0.468883E+10 | 0.49 | 9091.65 | 1.56 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.132885E+10 | 0.119597E+10 | 1321.38 | 12-JAN-07:30 | 1189.24 | 1189.24 | 42.31 | 4.25 |
February | 0.904385E+09 | 0.813947E+09 | 1291.41 | 27-FEB-08:45 | 1162.27 | 1162.27 | 42.43 | 4.15 |
March | 0.537337E+09 | 0.483603E+09 | 1192.41 | 01-MAR-07:17 | 1073.17 | 1073.17 | 41.89 | 3.74 |
April | 0.104529E+09 | 94075904.09 | 1042.07 | 03-APR-06:01 | 937.86 | 937.86 | 45.17 | 2.40 |
May | 11502039.22 | 10351835.30 | 401.94 | 27-MAY-06:03 | 361.74 | 361.74 | 41.00 | 0.48 |
June | 2167330.25 | 1950597.22 | 148.21 | 01-JUN-06:20 | 133.39 | 133.39 | 46.02 | 0.16 |
July | 1529693.22 | 1376723.90 | 147.78 | 06-JUL-06:05 | 133.00 | 133.00 | 38.36 | 0.16 |
August | 4952169.12 | 4456952.21 | 609.23 | 31-AUG-06:02 | 548.31 | 548.31 | 38.21 | 0.81 |
September | 46008122.32 | 41407310.09 | 1006.74 | 30-SEP-06:03 | 906.06 | 906.06 | 36.35 | 2.11 |
October | 0.349460E+09 | 0.314514E+09 | 1042.64 | 27-OCT-06:11 | 938.38 | 938.38 | 44.26 | 2.41 |
November | 0.110311E+10 | 0.992802E+09 | 1189.79 | 28-NOV-07:40 | 1070.81 | 1070.81 | 41.80 | 3.73 |
December | 0.139424E+10 | 0.125482E+10 | 1262.52 | 15-DEC-07:11 | 1136.27 | 1136.27 | 42.02 | 4.05 |
Annual Sum or Average | 0.578808E+10 | 0.520927E+10 | ||||||
Minimum of Months | 1529693.22 | 1376723.90 | 147.78 | 133.00 | 133.00 | 36.35 | 0.16 | |
Maximum of Months | 0.139424E+10 | 0.125482E+10 | 1321.38 | 1189.24 | 1189.24 | 46.02 | 4.25 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.66 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.59 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.50 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.49 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.52 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.39 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.53 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:02 | 2.06 | 2.06 | 56.72 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 56.77 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.73 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 56.80 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.63 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.39 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.73 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 39.38 | 39.38 | 66567.82 | 320924.52 | 12-JAN-07:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 43.82 | 43.82 | 48593.43 | 317254.61 | 27-FEB-07:13 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 42.03 | 60.00 | 24335.33 | 285206.03 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 33.19 | 33.19 | 4733.82 | 254302.43 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33.38 | 33.38 | 332.90 | 37957.60 | 27-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 45.30 | 45.30 | 68.51 | 15039.59 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.96 | 32.96 | 54.74 | 17665.22 | 05-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 36.74 | 36.74 | 166.18 | 74086.38 | 31-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 38.44 | 38.44 | 2090.40 | 235093.18 | 26-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.21 | 22.21 | 15761.80 | 255475.83 | 12-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 38.28 | 38.28 | 56343.85 | 286282.33 | 29-NOV-07:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 43.40 | 43.40 | 72528.71 | 304384.40 | 15-DEC-07:11 |
Annual Sum or Average | 0.00 | 24191.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.21 | 22.21 | 54.74 | 15039.59 | ||
Maximum of Months | 0.00 | 0.00 | 45.30 | 60.00 | 72528.71 | 320924.52 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.66 | 57.66 | 2106.65 | 7651.70 | 05-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.06 | 57.06 | 2119.74 | 7651.73 | 02-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.06 | 57.06 | 2267.31 | 7651.66 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.06 | 57.06 | 2107.71 | 7651.55 | 07-APR-11:17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.66 | 57.66 | 2172.08 | 7651.62 | 04-MAY-11:13 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 2149.54 | 7461.26 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.24 | 57.24 | 1886.34 | 7150.85 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.34 | 57.34 | 2036.90 | 6936.49 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.38 | 57.38 | 1887.74 | 6889.75 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.27 | 56.27 | 1923.51 | 7094.18 | 31-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 2024.11 | 7375.22 | 30-NOV-12:17 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.17 | 57.17 | 2016.79 | 7651.57 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 2057.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.27 | 56.27 | 1886.34 | 6889.75 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 2267.31 | 7651.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.556082E+11 | 0.00 | 0.00 | 0.255297E+10 | 0.00 | 0.00 |
February | 0.384308E+11 | 0.00 | 0.00 | 0.202151E+10 | 0.00 | 0.00 |
March | 0.230941E+11 | 0.00 | 0.00 | 0.178487E+10 | 0.00 | 0.00 |
April | 0.485347E+10 | 0.00 | 0.00 | 0.201941E+10 | 0.00 | 0.00 |
May | 0.808443E+09 | 0.00 | 0.00 | 0.462638E+10 | 0.00 | 0.00 |
June | 0.193446E+09 | 0.00 | 0.00 | 0.101644E+11 | 0.00 | 0.00 |
July | 0.143549E+09 | 0.00 | 0.00 | 0.122862E+11 | 0.00 | 0.00 |
August | 0.390502E+09 | 0.00 | 0.00 | 0.846882E+10 | 0.00 | 0.00 |
September | 0.209287E+10 | 0.00 | 0.00 | 0.235250E+10 | 0.00 | 0.00 |
October | 0.115824E+11 | 0.00 | 0.00 | 0.159570E+10 | 0.00 | 0.00 |
November | 0.424769E+11 | 0.00 | 0.00 | 0.191378E+10 | 0.00 | 0.00 |
December | 0.586750E+11 | 0.00 | 0.00 | 0.241797E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.238350E+12 | 0.00 | 0.00 | 0.522046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143549E+09 | 0.00 | 0.00 | 0.159570E+10 | 0.00 | 0.00 |
Maximum of Months | 0.586750E+11 | 0.00 | 0.00 | 0.122862E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.498211E+11 | 0.00 | 0.00 | 0.220281E+10 | 0.00 | 0.00 |
February | 0.307791E+11 | 0.00 | 0.00 | 0.183083E+10 | 0.00 | 0.00 |
March | 0.146472E+11 | 0.00 | 0.00 | 0.178032E+10 | 0.00 | 0.00 |
April | 0.193700E+10 | 0.00 | 0.00 | 0.210936E+10 | 0.00 | 0.00 |
May | 2798747.12 | 0.00 | 0.00 | 0.479550E+10 | 0.00 | 0.00 |
June | 133813.94 | 0.00 | 0.00 | 0.101637E+11 | 0.00 | 0.00 |
July | 223266.46 | 0.00 | 0.00 | 0.113964E+11 | 0.00 | 0.00 |
August | 1527489.27 | 0.00 | 0.00 | 0.736456E+10 | 0.00 | 0.00 |
September | 0.724505E+09 | 0.00 | 0.00 | 0.188335E+10 | 0.00 | 0.00 |
October | 0.988072E+10 | 0.00 | 0.00 | 0.155476E+10 | 0.00 | 0.00 |
November | 0.404355E+11 | 0.00 | 0.00 | 0.190448E+10 | 0.00 | 0.00 |
December | 0.555627E+11 | 0.00 | 0.00 | 0.212250E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.203792E+12 | 0.00 | 0.00 | 0.491086E+11 | 0.00 | 0.00 |
Minimum of Months | 133813.94 | 0.00 | 0.00 | 0.155476E+10 | 0.00 | 0.00 |
Maximum of Months | 0.555627E+11 | 0.00 | 0.00 | 0.113964E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.742714E+11 | 0.00 | 0.00 | 0.258802E+10 | 0.00 | 0.00 |
February | 0.493043E+11 | 0.00 | 0.00 | 0.218358E+10 | 0.00 | 0.00 |
March | 0.280115E+11 | 0.00 | 0.00 | 0.209008E+10 | 0.00 | 0.00 |
April | 0.558849E+10 | 0.00 | 0.00 | 0.199461E+10 | 0.00 | 0.00 |
May | 78337398.10 | 0.00 | 0.00 | 0.421749E+10 | 0.00 | 0.00 |
June | 113705.27 | 0.00 | 0.00 | 0.965185E+10 | 0.00 | 0.00 |
July | 132460.64 | 0.00 | 0.00 | 0.109422E+11 | 0.00 | 0.00 |
August | 56127554.66 | 0.00 | 0.00 | 0.674234E+10 | 0.00 | 0.00 |
September | 0.266741E+10 | 0.00 | 0.00 | 0.172611E+10 | 0.00 | 0.00 |
October | 0.211012E+11 | 0.00 | 0.00 | 0.180094E+10 | 0.00 | 0.00 |
November | 0.642935E+11 | 0.00 | 0.00 | 0.242794E+10 | 0.00 | 0.00 |
December | 0.815162E+11 | 0.00 | 0.00 | 0.265554E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.326889E+12 | 0.00 | 0.00 | 0.490207E+11 | 0.00 | 0.00 |
Minimum of Months | 113705.27 | 0.00 | 0.00 | 0.172611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.815162E+11 | 0.00 | 0.00 | 0.109422E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.255093E+10 | 7710094.33 | 0.556082E+11 | 0.267356E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201868E+10 | 10559775.29 | 0.384308E+11 | 0.220766E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177590E+10 | 33256014.71 | 0.230941E+11 | 0.239542E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200819E+10 | 41751952.17 | 0.485347E+10 | 0.567331E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360794E+10 | 0.427543E+10 | 0.808443E+09 | 0.139244E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522437E+10 | 0.220110E+11 | 0.193446E+09 | 42920713.46 | 5615522.37 | 0.00 | 0.00 | 0.00 |
July | 0.543843E+10 | 0.311428E+11 | 0.143549E+09 | 0.124406E+09 | 59833882.71 | 0.00 | 0.00 | 0.00 |
August | 0.473333E+10 | 0.167525E+11 | 0.390502E+09 | 35675012.08 | 154345.21 | 0.00 | 0.00 | 0.00 |
September | 0.227961E+10 | 0.277780E+09 | 0.209287E+10 | 0.184999E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158581E+10 | 36689904.61 | 0.115824E+11 | 0.150622E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191163E+10 | 8025067.61 | 0.424769E+11 | 0.258832E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241657E+10 | 5277832.66 | 0.586750E+11 | 0.240460E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355514E+11 | 0.746028E+11 | 0.238350E+12 | 0.145623E+12 | 65603750.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158581E+10 | 5277832.66 | 0.143549E+09 | 35675012.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.543843E+10 | 0.311428E+11 | 0.586750E+11 | 0.267356E+11 | 59833882.71 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220069E+10 | 8129165.26 | 0.498211E+11 | 0.261715E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182882E+10 | 7800275.92 | 0.307791E+11 | 0.221551E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177587E+10 | 17112777.52 | 0.146472E+11 | 0.251030E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210038E+10 | 33477287.97 | 0.193700E+10 | 0.664608E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371721E+10 | 0.455631E+10 | 2798747.12 | 0.236333E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.526977E+10 | 0.218593E+11 | 133813.94 | 61497761.64 | 7289717.64 | 0.00 | 0.00 | 0.00 |
July | 0.493758E+10 | 0.293331E+11 | 223266.46 | 0.149519E+09 | 67311154.87 | 0.00 | 0.00 | 0.00 |
August | 0.397104E+10 | 0.151415E+11 | 1527489.27 | 0.110637E+09 | 66492.51 | 0.00 | 0.00 | 0.00 |
September | 0.181931E+10 | 0.243958E+09 | 0.724505E+09 | 0.299302E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155046E+10 | 16629265.91 | 0.988072E+10 | 0.167207E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190225E+10 | 8572810.07 | 0.404355E+11 | 0.257952E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212089E+10 | 6155515.24 | 0.555627E+11 | 0.229021E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331943E+11 | 0.712320E+11 | 0.203792E+12 | 0.149045E+12 | 74667365.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155046E+10 | 6155515.24 | 133813.94 | 61497761.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.526977E+10 | 0.293331E+11 | 0.555627E+11 | 0.261715E+11 | 67311154.87 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.258763E+10 | 1471434.30 | 0.742714E+11 | 0.258987E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218288E+10 | 2613637.62 | 0.493043E+11 | 0.223240E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208610E+10 | 14735360.64 | 0.280115E+11 | 0.253577E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198371E+10 | 40387051.89 | 0.558849E+10 | 0.744687E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316817E+10 | 0.439870E+10 | 78337398.10 | 0.380977E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468883E+10 | 0.220355E+11 | 113705.27 | 30022319.40 | 7384331.70 | 0.00 | 0.00 | 0.00 |
July | 0.440238E+10 | 0.295393E+11 | 132460.64 | 0.106194E+09 | 49698230.12 | 0.00 | 0.00 | 0.00 |
August | 0.337279E+10 | 0.149291E+11 | 56127554.66 | 0.208759E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166647E+10 | 0.226125E+09 | 0.266741E+10 | 0.387354E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179771E+10 | 12111665.35 | 0.211012E+11 | 0.175717E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242765E+10 | 1093102.80 | 0.642935E+11 | 0.255087E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265511E+10 | 1594285.17 | 0.815162E+11 | 0.224586E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330194E+11 | 0.712027E+11 | 0.326889E+12 | 0.151166E+12 | 57082561.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166647E+10 | 1093102.80 | 113705.27 | 30022319.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468883E+10 | 0.295393E+11 | 0.815162E+11 | 0.258987E+11 | 49698230.12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.255093E+10 | 0.556082E+11 | 0.00 | 0.00 | 2041020.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201868E+10 | 0.384308E+11 | 0.00 | 0.00 | 2830581.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177590E+10 | 0.230941E+11 | 0.00 | 0.00 | 8970209.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200819E+10 | 0.485347E+10 | 0.00 | 0.00 | 11221478.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360794E+10 | 0.808443E+09 | 0.00 | 0.00 | 0.101845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522437E+10 | 0.193446E+09 | 0.00 | 0.00 | 0.494006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543843E+10 | 0.143549E+09 | 0.00 | 0.00 | 0.684782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.473333E+10 | 0.390502E+09 | 0.00 | 0.00 | 0.373549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227961E+10 | 0.209287E+10 | 0.00 | 0.00 | 72882667.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158581E+10 | 0.115824E+11 | 0.00 | 0.00 | 9885733.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191163E+10 | 0.424769E+11 | 0.00 | 0.00 | 2144287.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241657E+10 | 0.586750E+11 | 0.00 | 0.00 | 1392073.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355514E+11 | 0.238350E+12 | 0.00 | 0.00 | 0.166532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158581E+10 | 0.143549E+09 | 0.00 | 0.00 | 1392073.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.543843E+10 | 0.586750E+11 | 0.00 | 0.00 | 0.684782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.220069E+10 | 0.498211E+11 | 0.00 | 0.00 | 2115107.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182882E+10 | 0.307791E+11 | 0.00 | 0.00 | 2009266.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177587E+10 | 0.146472E+11 | 0.00 | 0.00 | 4456985.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210038E+10 | 0.193700E+10 | 0.00 | 0.00 | 8979112.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.371721E+10 | 2798747.12 | 0.00 | 0.00 | 0.107829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.526977E+10 | 133813.94 | 0.00 | 0.00 | 0.489392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.493758E+10 | 223266.46 | 0.00 | 0.00 | 0.645883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.397104E+10 | 1527489.27 | 0.00 | 0.00 | 0.339352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181931E+10 | 0.724505E+09 | 0.00 | 0.00 | 64040232.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155046E+10 | 0.988072E+10 | 0.00 | 0.00 | 4297842.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190225E+10 | 0.404355E+11 | 0.00 | 0.00 | 2232807.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212089E+10 | 0.555627E+11 | 0.00 | 0.00 | 1615057.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331943E+11 | 0.203792E+12 | 0.00 | 0.00 | 0.159143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155046E+10 | 133813.94 | 0.00 | 0.00 | 1615057.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.526977E+10 | 0.555627E+11 | 0.00 | 0.00 | 0.645883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.258763E+10 | 0.742714E+11 | 0.00 | 0.00 | 396668.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218288E+10 | 0.493043E+11 | 0.00 | 0.00 | 701357.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208610E+10 | 0.280115E+11 | 0.00 | 0.00 | 3983832.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198371E+10 | 0.558849E+10 | 0.00 | 0.00 | 10899032.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316817E+10 | 78337398.10 | 0.00 | 0.00 | 0.104932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468883E+10 | 113705.27 | 0.00 | 0.00 | 0.496302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.440238E+10 | 132460.64 | 0.00 | 0.00 | 0.653984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.337279E+10 | 56127554.66 | 0.00 | 0.00 | 0.336955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166647E+10 | 0.266741E+10 | 0.00 | 0.00 | 59640997.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179771E+10 | 0.211012E+11 | 0.00 | 0.00 | 3228671.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242765E+10 | 0.642935E+11 | 0.00 | 0.00 | 295879.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265511E+10 | 0.815162E+11 | 0.00 | 0.00 | 430297.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330194E+11 | 0.326889E+12 | 0.00 | 0.00 | 0.160013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166647E+10 | 113705.27 | 0.00 | 0.00 | 295879.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468883E+10 | 0.815162E+11 | 0.00 | 0.00 | 0.653984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915907E+09 | 0.00 | 0.00 | 0.25 |
February | 0.103080E+11 | 0.00 | 0.00 | 461856.40 | 0.00 | 0.165002E+09 | 0.557622E+09 | 0.00 | 0.26 |
March | 0.813612E+10 | 0.00 | 0.00 | 5566703.06 | 0.00 | 9679865.84 | 0.344018E+10 | 0.00 | 0.29 |
April | 0.252567E+10 | 0.00 | 0.00 | 30152754.61 | 0.00 | 0.00 | 0.148397E+11 | 0.00 | 0.44 |
May | 0.146515E+10 | 0.00 | 0.00 | 46056488.28 | 0.00 | 0.00 | 0.259260E+11 | 0.00 | 0.99 |
June | 0.117724E+10 | 6272267.04 | 0.00 | 51099987.06 | 0.00 | 0.00 | 0.216412E+11 | 0.00 | 1.28 |
July | 0.142460E+10 | 63232109.45 | 0.00 | 47612275.91 | 10522143.64 | 0.00 | 0.164970E+11 | 0.00 | 1.18 |
August | 0.973635E+09 | 46359.70 | 0.00 | 54265135.98 | 0.00 | 0.00 | 0.240727E+11 | 0.00 | 1.16 |
September | 0.115918E+10 | 0.00 | 0.00 | 37824890.95 | 0.00 | 0.00 | 0.200897E+11 | 0.00 | 0.60 |
October | 0.446790E+10 | 0.00 | 0.00 | 13534499.77 | 0.00 | 0.00 | 0.739776E+10 | 0.00 | 0.31 |
November | 0.118565E+11 | 0.00 | 0.00 | 204284.07 | 0.00 | 0.104813E+09 | 0.341134E+09 | 0.00 | 0.25 |
December | 0.148439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136693E+09 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.701010E+11 | 69550736.19 | 0.00 | 0.286779E+09 | 10522143.64 | 0.133209E+10 | 0.134803E+12 | 0.00 | 0.61 |
Minimum of Months | 0.973635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.148439E+11 | 63232109.45 | 0.00 | 54265135.98 | 10522143.64 | 0.915907E+09 | 0.259260E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.790330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506255E+10 | 0.00 | 0.00 | 0.26 |
February | 0.738138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328352E+10 | 0.00 | 0.00 | 0.26 |
March | 0.996828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549955E+09 | 0.00 | 0.00 | 0.28 |
April | 0.716930E+10 | 0.00 | 0.00 | 7663972.93 | 0.00 | 23607068.09 | 0.529757E+10 | 0.00 | 0.34 |
May | 0.312693E+10 | 0.00 | 0.00 | 26287403.51 | 0.00 | 0.00 | 0.160793E+11 | 0.00 | 0.70 |
June | 0.200542E+10 | 5955351.73 | 0.00 | 33290190.88 | 0.00 | 0.00 | 0.146365E+11 | 0.00 | 0.93 |
July | 0.198064E+10 | 43360850.20 | 0.00 | 30502814.52 | 10861995.43 | 0.00 | 0.107902E+11 | 0.00 | 0.85 |
August | 0.195121E+10 | 237632.86 | 0.00 | 31187571.52 | 0.00 | 0.00 | 0.147409E+11 | 0.00 | 0.79 |
September | 0.646071E+10 | 0.00 | 0.00 | 10607748.42 | 0.00 | 0.00 | 0.679710E+10 | 0.00 | 0.39 |
October | 0.836723E+10 | 0.00 | 0.00 | 367590.90 | 0.00 | 0.234893E+09 | 0.615057E+09 | 0.00 | 0.27 |
November | 0.866521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390375E+10 | 0.00 | 0.00 | 0.26 |
December | 0.922043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619600E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.742000E+11 | 49553834.79 | 0.00 | 0.139907E+09 | 10861995.43 | 0.192543E+11 | 0.689566E+11 | 0.00 | 0.47 |
Minimum of Months | 0.195121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.996828E+10 | 43360850.20 | 0.00 | 33290190.88 | 10861995.43 | 0.619600E+10 | 0.160793E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895343E+10 | 0.00 | 0.00 | 0.24 |
February | 0.312348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.600751E+10 | 0.00 | 0.00 | 0.25 |
March | 0.676319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242368E+10 | 0.00 | 0.00 | 0.27 |
April | 0.779629E+10 | 0.00 | 0.00 | 3243150.32 | 0.00 | 0.242513E+09 | 0.302685E+10 | 0.00 | 0.32 |
May | 0.432832E+10 | 0.00 | 0.00 | 20384949.21 | 0.00 | 0.00 | 0.132578E+11 | 0.00 | 0.65 |
June | 0.214552E+10 | 13265080.82 | 0.00 | 29999413.91 | 0.00 | 0.00 | 0.137183E+11 | 0.00 | 0.91 |
July | 0.242052E+10 | 40935386.29 | 0.00 | 26722004.07 | 6999460.56 | 0.00 | 0.951185E+10 | 0.00 | 0.83 |
August | 0.284275E+10 | 634212.57 | 0.00 | 23221099.59 | 0.00 | 0.00 | 0.118208E+11 | 0.00 | 0.73 |
September | 0.800813E+10 | 0.00 | 0.00 | 2980017.56 | 0.00 | 59572560.73 | 0.300545E+10 | 0.00 | 0.36 |
October | 0.637086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151294E+10 | 0.00 | 0.00 | 0.26 |
November | 0.302255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794546E+10 | 0.00 | 0.00 | 0.24 |
December | 0.278803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107309E+11 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.519290E+11 | 54834679.69 | 0.00 | 0.106551E+09 | 6999460.56 | 0.378760E+11 | 0.543410E+11 | 0.00 | 0.44 |
Minimum of Months | 0.214552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.800813E+10 | 40935386.29 | 0.00 | 29999413.91 | 6999460.56 | 0.107309E+11 | 0.137183E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 15231687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365363E+10 | 0.00 | 0.00 | 0.34 |
February | 25487954.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262666E+10 | 0.00 | 0.00 | 0.31 |
March | 0.305074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191722E+10 | 0.00 | 0.00 | 0.29 |
April | 0.163816E+10 | 0.00 | 0.00 | 260630.17 | 0.00 | 0.430432E+09 | 0.264270E+09 | 0.00 | 0.32 |
May | 0.107684E+10 | 0.00 | 0.00 | 4636622.71 | 0.00 | 865416.96 | 0.290086E+10 | 0.00 | 0.72 |
June | 0.320176E+09 | 5077149.25 | 0.00 | 10324013.15 | 0.00 | 0.00 | 0.426309E+10 | 0.00 | 1.28 |
July | 0.421325E+09 | 13199632.08 | 0.00 | 8561101.34 | 1489779.46 | 0.00 | 0.278492E+10 | 0.00 | 1.13 |
August | 0.863547E+09 | 160472.86 | 0.00 | 5123974.29 | 0.00 | 4509853.75 | 0.238915E+10 | 0.00 | 0.81 |
September | 0.183578E+10 | 0.00 | 0.00 | 159124.82 | 0.00 | 0.268139E+09 | 0.220305E+09 | 0.00 | 0.35 |
October | 0.466195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128282E+10 | 0.00 | 0.00 | 0.28 |
November | 11843354.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332718E+10 | 0.00 | 0.00 | 0.32 |
December | 18659903.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442525E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.699832E+10 | 18437254.19 | 0.00 | 29065466.48 | 1489779.46 | 0.179367E+11 | 0.128226E+11 | 0.00 | 0.54 |
Minimum of Months | 11843354.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.183578E+10 | 13199632.08 | 0.00 | 10324013.15 | 1489779.46 | 0.442525E+10 | 0.426309E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16616056.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292574E+10 | 0.00 | 0.00 | 0.45 |
February | 85275543.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218935E+10 | 0.00 | 0.00 | 0.45 |
March | 0.903133E+09 | 0.00 | 0.00 | 150644.57 | 0.00 | 0.127974E+10 | 68532244.94 | 0.00 | 0.48 |
April | 0.134209E+10 | 0.00 | 0.00 | 2460617.96 | 0.00 | 0.239801E+09 | 0.134145E+10 | 0.00 | 0.63 |
May | 0.834161E+09 | 0.00 | 0.00 | 10130556.07 | 0.00 | 178067.66 | 0.538318E+10 | 0.00 | 1.68 |
June | 0.409576E+09 | 3842885.67 | 0.00 | 11435735.93 | 0.00 | 0.00 | 0.509191E+10 | 0.00 | 2.22 |
July | 0.434676E+09 | 9842973.02 | 0.00 | 11259028.05 | 1623133.97 | 0.00 | 0.365290E+10 | 0.00 | 2.11 |
August | 0.718841E+09 | 147070.19 | 0.00 | 7659135.07 | 0.00 | 966381.17 | 0.370928E+10 | 0.00 | 1.58 |
September | 0.187445E+10 | 0.00 | 0.00 | 1208514.97 | 0.00 | 0.153314E+09 | 0.655600E+09 | 0.00 | 0.64 |
October | 0.806510E+09 | 0.00 | 0.00 | 37776.21 | 0.00 | 0.102175E+10 | 15063168.43 | 0.00 | 0.46 |
November | 12918421.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273844E+10 | 0.00 | 0.00 | 0.45 |
December | 20330206.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337385E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.745858E+10 | 13832928.88 | 0.00 | 44342008.84 | 1623133.97 | 0.139231E+11 | 0.199179E+11 | 0.00 | 0.97 |
Minimum of Months | 12918421.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.187445E+10 | 9842973.02 | 0.00 | 11435735.93 | 1623133.97 | 0.337385E+10 | 0.538318E+10 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433420E+10 | 0.00 | 0.00 | 0.44 |
February | 0.638987E+09 | 0.00 | 0.00 | 249666.71 | 0.00 | 0.278644E+10 | 0.108269E+09 | 0.00 | 0.45 |
March | 0.117695E+10 | 0.00 | 0.00 | 3560952.40 | 0.00 | 0.154454E+10 | 0.131361E+10 | 0.00 | 0.53 |
April | 0.138631E+10 | 0.00 | 0.00 | 10095234.17 | 0.00 | 0.322180E+09 | 0.531368E+10 | 0.00 | 0.95 |
May | 0.168973E+10 | 0.00 | 0.00 | 13596286.79 | 0.00 | 4215929.53 | 0.739403E+10 | 0.00 | 1.67 |
June | 0.109821E+10 | 7188713.55 | 0.00 | 13836209.08 | 0.00 | 0.00 | 0.594171E+10 | 0.00 | 2.04 |
July | 0.118060E+10 | 24572922.90 | 0.00 | 13810940.24 | 1688611.58 | 0.00 | 0.387251E+10 | 0.00 | 1.90 |
August | 0.144968E+10 | 230600.13 | 0.00 | 12934900.47 | 0.00 | 5942696.23 | 0.566648E+10 | 0.00 | 1.81 |
September | 0.218463E+10 | 0.00 | 0.00 | 5117322.60 | 0.00 | 0.226694E+09 | 0.301351E+10 | 0.00 | 0.84 |
October | 0.129902E+10 | 0.00 | 0.00 | 1281475.32 | 0.00 | 0.126953E+10 | 0.576009E+09 | 0.00 | 0.48 |
November | 0.255556E+09 | 0.00 | 0.00 | 15816.11 | 0.00 | 0.397067E+10 | 14030126.91 | 0.00 | 0.44 |
December | 31876944.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520303E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.125542E+11 | 31992236.57 | 0.00 | 74498803.89 | 1688611.58 | 0.196675E+11 | 0.332138E+11 | 0.00 | 1.00 |
Minimum of Months | 31876944.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.218463E+10 | 24572922.90 | 0.00 | 13836209.08 | 1688611.58 | 0.520303E+10 | 0.739403E+10 | 0.00 | 2.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17196461.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301339E+10 | 0.00 | 0.00 | 0.46 |
February | 73938516.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230299E+10 | 0.00 | 0.00 | 0.47 |
March | 0.645587E+09 | 0.00 | 0.00 | 2405.59 | 0.00 | 0.166492E+10 | 10725087.30 | 0.00 | 0.49 |
April | 0.139022E+10 | 0.00 | 0.00 | 2798186.33 | 0.00 | 0.345666E+09 | 0.161056E+10 | 0.00 | 0.73 |
May | 0.142381E+10 | 0.00 | 0.00 | 5430102.36 | 0.00 | 4834050.90 | 0.298358E+10 | 0.00 | 1.28 |
June | 0.698018E+09 | 5498117.36 | 0.00 | 8142218.32 | 0.00 | 0.00 | 0.313370E+10 | 0.00 | 1.85 |
July | 0.811402E+09 | 16391522.81 | 0.00 | 6264931.02 | 1262119.76 | 0.00 | 0.183551E+10 | 0.00 | 1.59 |
August | 0.127123E+10 | 168870.19 | 0.00 | 4694168.80 | 0.00 | 8383506.98 | 0.203009E+10 | 0.00 | 1.36 |
September | 0.194154E+10 | 0.00 | 0.00 | 724750.23 | 0.00 | 0.253634E+09 | 0.550547E+09 | 0.00 | 0.67 |
October | 0.623056E+09 | 0.00 | 0.00 | 2.60 | 0.00 | 0.128094E+10 | 1489274.54 | 0.00 | 0.47 |
November | 19565513.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280451E+10 | 0.00 | 0.00 | 0.46 |
December | 21040347.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345534E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.893660E+10 | 22058510.36 | 0.00 | 28056765.25 | 1262119.76 | 0.151346E+11 | 0.121562E+11 | 0.00 | 0.86 |
Minimum of Months | 17196461.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.194154E+10 | 16391522.81 | 0.00 | 8142218.32 | 1262119.76 | 0.345534E+10 | 0.313370E+10 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50550012.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375675E+10 | 0.00 | 0.00 | 0.33 |
February | 39150750.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307693E+10 | 0.00 | 0.00 | 0.33 |
March | 0.198192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248691E+10 | 0.00 | 0.00 | 0.31 |
April | 0.189606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700041E+09 | 0.00 | 0.00 | 0.31 |
May | 0.181689E+10 | 0.00 | 0.00 | 1721814.34 | 0.00 | 0.00 | 0.135232E+10 | 0.00 | 0.54 |
June | 0.358518E+09 | 1268978.06 | 0.00 | 7564505.02 | 0.00 | 0.00 | 0.317810E+10 | 0.00 | 0.97 |
July | 0.414107E+09 | 10810227.25 | 0.00 | 7249831.06 | 2223554.57 | 0.00 | 0.240189E+10 | 0.00 | 0.95 |
August | 0.844982E+09 | 6879.12 | 0.00 | 5013998.95 | 0.00 | 0.00 | 0.239794E+10 | 0.00 | 0.76 |
September | 0.230809E+10 | 0.00 | 0.00 | 228184.81 | 0.00 | 61217629.74 | 0.355557E+09 | 0.00 | 0.36 |
October | 0.105219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115795E+10 | 0.00 | 0.00 | 0.27 |
November | 37993218.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321840E+10 | 0.00 | 0.00 | 0.30 |
December | 0.118094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429488E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.913482E+10 | 12086084.43 | 0.00 | 21778334.19 | 2223554.57 | 0.187531E+11 | 0.968582E+10 | 0.00 | 0.48 |
Minimum of Months | 37993218.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.230809E+10 | 10810227.25 | 0.00 | 7564505.02 | 2223554.57 | 0.429488E+10 | 0.317810E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47108646.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318642E+10 | 0.00 | 0.00 | 0.43 |
February | 82310211.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252529E+10 | 0.00 | 0.00 | 0.43 |
March | 0.773333E+09 | 0.00 | 0.00 | 33962.07 | 0.00 | 0.150977E+10 | 25174944.22 | 0.00 | 0.42 |
April | 0.140416E+10 | 0.00 | 0.00 | 1654773.75 | 0.00 | 0.250629E+09 | 0.942259E+09 | 0.00 | 0.49 |
May | 0.603901E+09 | 0.00 | 0.00 | 8335481.19 | 0.00 | 0.00 | 0.458498E+10 | 0.00 | 1.39 |
June | 0.282300E+09 | 1615987.71 | 0.00 | 9755877.07 | 0.00 | 0.00 | 0.431937E+10 | 0.00 | 1.88 |
July | 0.288157E+09 | 11012999.40 | 0.00 | 10428096.54 | 1832881.25 | 0.00 | 0.331861E+10 | 0.00 | 1.87 |
August | 0.406928E+09 | 5741.90 | 0.00 | 8462685.35 | 0.00 | 0.00 | 0.395214E+10 | 0.00 | 1.52 |
September | 0.143847E+10 | 0.00 | 0.00 | 2120737.70 | 0.00 | 28935523.79 | 0.132131E+10 | 0.00 | 0.58 |
October | 0.111987E+10 | 0.00 | 0.00 | 80821.58 | 0.00 | 0.828962E+09 | 44573150.92 | 0.00 | 0.39 |
November | 32485980.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264841E+10 | 0.00 | 0.00 | 0.39 |
December | 94314468.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336152E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.657333E+10 | 12634729.00 | 0.00 | 40872435.26 | 1832881.25 | 0.143399E+11 | 0.185084E+11 | 0.00 | 0.85 |
Minimum of Months | 32485980.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.143847E+10 | 11012999.40 | 0.00 | 10428096.54 | 1832881.25 | 0.336152E+10 | 0.458498E+10 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57029873.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792208E+10 | 0.00 | 0.00 | 0.71 |
February | 0.252060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560376E+10 | 0.00 | 0.00 | 0.62 |
March | 0.722856E+09 | 0.00 | 0.00 | 543.82 | 0.00 | 0.404348E+10 | 4734659.57 | 0.00 | 0.54 |
April | 0.182059E+10 | 0.00 | 0.00 | 2716317.26 | 0.00 | 0.123462E+10 | 0.190956E+10 | 0.00 | 0.62 |
May | 0.209601E+10 | 0.00 | 0.00 | 5600166.87 | 0.00 | 0.434038E+09 | 0.337414E+10 | 0.00 | 1.07 |
June | 0.108492E+10 | 2732319.40 | 0.00 | 8425313.67 | 0.00 | 0.126719E+09 | 0.349639E+10 | 0.00 | 1.40 |
July | 0.100598E+10 | 24021174.64 | 0.00 | 10123943.33 | 1639382.76 | 0.105581E+09 | 0.262716E+10 | 0.00 | 1.45 |
August | 0.134532E+10 | 12129.46 | 0.00 | 9636653.25 | 0.00 | 0.247724E+09 | 0.394588E+10 | 0.00 | 1.46 |
September | 0.219349E+10 | 0.00 | 0.00 | 2746995.31 | 0.00 | 0.970888E+09 | 0.198884E+10 | 0.00 | 0.71 |
October | 0.964064E+09 | 0.00 | 0.00 | 362267.70 | 0.00 | 0.280960E+10 | 0.251966E+09 | 0.00 | 0.50 |
November | 91585249.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737259E+10 | 0.00 | 0.00 | 0.67 |
December | 75506262.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998531E+10 | 0.00 | 0.00 | 0.76 |
Annual Sum or Average | 0.117094E+11 | 26765623.50 | 0.00 | 39612201.20 | 1639382.76 | 0.408564E+11 | 0.175987E+11 | 0.00 | 0.88 |
Minimum of Months | 57029873.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105581E+09 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.219349E+10 | 24021174.64 | 0.00 | 10123943.33 | 1639382.76 | 0.998531E+10 | 0.394588E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49115122.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334581E+10 | 0.00 | 0.00 | 0.46 |
February | 63514232.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279428E+10 | 0.00 | 0.00 | 0.46 |
March | 0.434248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202523E+10 | 0.00 | 0.00 | 0.44 |
April | 0.162365E+10 | 0.00 | 0.00 | 1473415.25 | 0.00 | 0.311923E+09 | 0.866544E+09 | 0.00 | 0.55 |
May | 0.143002E+10 | 0.00 | 0.00 | 2996929.27 | 0.00 | 214977.58 | 0.193573E+10 | 0.00 | 0.95 |
June | 0.504555E+09 | 940994.63 | 0.00 | 6463578.11 | 0.00 | 0.00 | 0.255662E+10 | 0.00 | 1.45 |
July | 0.526227E+09 | 14038516.64 | 0.00 | 5570407.87 | 2119585.93 | 0.00 | 0.172778E+10 | 0.00 | 1.32 |
August | 0.762598E+09 | 7484.92 | 0.00 | 5200314.39 | 0.00 | 0.00 | 0.226471E+10 | 0.00 | 1.21 |
September | 0.203516E+10 | 0.00 | 0.00 | 769224.44 | 0.00 | 46674021.95 | 0.627665E+09 | 0.00 | 0.58 |
October | 0.107127E+10 | 0.00 | 0.00 | 37.82 | 0.00 | 0.102415E+10 | 2437848.25 | 0.00 | 0.41 |
November | 41010318.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274143E+10 | 0.00 | 0.00 | 0.41 |
December | 99468521.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346148E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.864084E+10 | 14986996.19 | 0.00 | 22473907.16 | 2119585.93 | 0.157512E+11 | 0.998148E+10 | 0.00 | 0.72 |
Minimum of Months | 41010318.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.203516E+10 | 14038516.64 | 0.00 | 6463578.11 | 2119585.93 | 0.346148E+10 | 0.255662E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 23349792.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350372E+10 | 0.00 | 0.00 | 0.31 |
February | 91257850.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261172E+10 | 0.00 | 0.00 | 0.29 |
March | 0.600921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178110E+10 | 0.00 | 0.00 | 0.29 |
April | 0.180454E+10 | 0.00 | 0.00 | 561540.96 | 0.00 | 0.253345E+09 | 0.475146E+09 | 0.00 | 0.32 |
May | 0.782084E+09 | 0.00 | 0.00 | 6094248.98 | 0.00 | 0.00 | 0.358057E+10 | 0.00 | 0.78 |
June | 0.298078E+09 | 1984205.53 | 0.00 | 11345695.26 | 0.00 | 0.00 | 0.453524E+10 | 0.00 | 1.32 |
July | 0.357084E+09 | 13674499.52 | 0.00 | 9516911.47 | 2286273.16 | 0.00 | 0.307752E+10 | 0.00 | 1.16 |
August | 0.653753E+09 | 61519.19 | 0.00 | 6522135.18 | 0.00 | 0.00 | 0.297036E+10 | 0.00 | 0.87 |
September | 0.194054E+10 | 0.00 | 0.00 | 609141.35 | 0.00 | 69682134.92 | 0.593495E+09 | 0.00 | 0.37 |
October | 0.914273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105549E+10 | 0.00 | 0.00 | 0.27 |
November | 21851717.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313460E+10 | 0.00 | 0.00 | 0.29 |
December | 29688984.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402481E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.751742E+10 | 15720224.24 | 0.00 | 34649673.21 | 2286273.16 | 0.164345E+11 | 0.152323E+11 | 0.00 | 0.55 |
Minimum of Months | 21851717.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.194054E+10 | 13674499.52 | 0.00 | 11345695.26 | 2286273.16 | 0.402481E+10 | 0.453524E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28824437.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326293E+10 | 0.00 | 0.00 | 0.47 |
February | 0.278472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237719E+10 | 0.00 | 0.00 | 0.48 |
March | 0.125422E+10 | 0.00 | 0.00 | 368314.85 | 0.00 | 0.117883E+10 | 0.141172E+09 | 0.00 | 0.50 |
April | 0.146753E+10 | 0.00 | 0.00 | 3270152.03 | 0.00 | 0.159055E+09 | 0.177090E+10 | 0.00 | 0.67 |
May | 0.780621E+09 | 0.00 | 0.00 | 10959104.16 | 0.00 | 0.00 | 0.583547E+10 | 0.00 | 1.76 |
June | 0.356189E+09 | 2224088.65 | 0.00 | 11774559.45 | 0.00 | 0.00 | 0.521411E+10 | 0.00 | 2.21 |
July | 0.392649E+09 | 10639589.45 | 0.00 | 11605763.80 | 2510057.05 | 0.00 | 0.376536E+10 | 0.00 | 2.09 |
August | 0.663765E+09 | 54317.01 | 0.00 | 8576830.06 | 0.00 | 0.00 | 0.411482E+10 | 0.00 | 1.63 |
September | 0.192656E+10 | 0.00 | 0.00 | 1870535.83 | 0.00 | 58110323.20 | 0.117389E+10 | 0.00 | 0.69 |
October | 0.118069E+10 | 0.00 | 0.00 | 102742.80 | 0.00 | 0.963996E+09 | 48740214.42 | 0.00 | 0.48 |
November | 25393294.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309525E+10 | 0.00 | 0.00 | 0.47 |
December | 34429513.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379509E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.838934E+10 | 12917995.11 | 0.00 | 48528002.98 | 2510057.05 | 0.148905E+11 | 0.220645E+11 | 0.00 | 1.00 |
Minimum of Months | 25393294.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.192656E+10 | 10639589.45 | 0.00 | 11774559.45 | 2510057.05 | 0.379509E+10 | 0.583547E+10 | 0.00 | 2.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.265894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462036E+10 | 0.00 | 0.00 | 0.45 |
February | 0.914322E+09 | 0.00 | 0.00 | 513577.36 | 0.00 | 0.287989E+10 | 0.195653E+09 | 0.00 | 0.46 |
March | 0.157295E+10 | 0.00 | 0.00 | 4852336.18 | 0.00 | 0.140892E+10 | 0.158043E+10 | 0.00 | 0.56 |
April | 0.164444E+10 | 0.00 | 0.00 | 11734862.68 | 0.00 | 0.194450E+09 | 0.574663E+10 | 0.00 | 0.99 |
May | 0.152645E+10 | 0.00 | 0.00 | 14617902.66 | 0.00 | 0.00 | 0.769101E+10 | 0.00 | 1.72 |
June | 0.900427E+09 | 4327121.10 | 0.00 | 14517686.19 | 0.00 | 0.00 | 0.604998E+10 | 0.00 | 2.02 |
July | 0.917889E+09 | 27838793.29 | 0.00 | 14464997.19 | 2804308.66 | 0.00 | 0.401379E+10 | 0.00 | 1.85 |
August | 0.116756E+10 | 81608.68 | 0.00 | 14503732.98 | 0.00 | 0.00 | 0.610684E+10 | 0.00 | 1.83 |
September | 0.234929E+10 | 0.00 | 0.00 | 6684995.70 | 0.00 | 75248833.02 | 0.373307E+10 | 0.00 | 0.90 |
October | 0.168870E+10 | 0.00 | 0.00 | 1851488.21 | 0.00 | 0.112753E+10 | 0.837153E+09 | 0.00 | 0.49 |
November | 0.438584E+09 | 0.00 | 0.00 | 96948.59 | 0.00 | 0.418011E+10 | 28958933.53 | 0.00 | 0.45 |
December | 51869925.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567317E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.134384E+11 | 32247523.07 | 0.00 | 83838527.73 | 2804308.66 | 0.201597E+11 | 0.359835E+11 | 0.00 | 1.02 |
Minimum of Months | 51869925.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.234929E+10 | 27838793.29 | 0.00 | 14617902.66 | 2804308.66 | 0.567317E+10 | 0.769101E+10 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28672509.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322905E+10 | 0.00 | 0.00 | 0.47 |
February | 0.179038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247877E+10 | 0.00 | 0.00 | 0.47 |
March | 0.917077E+09 | 0.00 | 0.00 | 58344.35 | 0.00 | 0.155802E+10 | 50194987.19 | 0.00 | 0.49 |
April | 0.159948E+10 | 0.00 | 0.00 | 3225201.40 | 0.00 | 0.204128E+09 | 0.177981E+10 | 0.00 | 0.74 |
May | 0.113005E+10 | 0.00 | 0.00 | 6228586.89 | 0.00 | 0.00 | 0.336455E+10 | 0.00 | 1.31 |
June | 0.566865E+09 | 1294597.47 | 0.00 | 8693383.59 | 0.00 | 0.00 | 0.326626E+10 | 0.00 | 1.83 |
July | 0.624176E+09 | 16920871.79 | 0.00 | 6754380.32 | 1995818.11 | 0.00 | 0.201455E+10 | 0.00 | 1.56 |
August | 0.962235E+09 | 62919.32 | 0.00 | 5626519.78 | 0.00 | 0.00 | 0.242394E+10 | 0.00 | 1.36 |
September | 0.214805E+10 | 0.00 | 0.00 | 1099560.58 | 0.00 | 80390649.31 | 0.799846E+09 | 0.00 | 0.68 |
October | 0.107423E+10 | 0.00 | 0.00 | 7074.68 | 0.00 | 0.107776E+10 | 13421828.25 | 0.00 | 0.47 |
November | 35565297.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304974E+10 | 0.00 | 0.00 | 0.47 |
December | 34194825.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375890E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.929963E+10 | 18278388.58 | 0.00 | 31693051.59 | 1995818.11 | 0.154368E+11 | 0.137126E+11 | 0.00 | 0.86 |
Minimum of Months | 28672509.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.214805E+10 | 16920871.79 | 0.00 | 8693383.59 | 1995818.11 | 0.375890E+10 | 0.336455E+10 | 0.00 | 1.83 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.576970E+10 | 0.159562E+11 | 0.00 | 0.192559E+12 | 0.605289E+11 |
February | 0.491326E+11 | 0.128405E+11 | 0.00 | 0.172172E+12 | 0.434013E+11 |
March | 0.208725E+12 | 0.161876E+11 | 0.00 | 0.211860E+12 | 0.293128E+11 |
April | 0.354019E+12 | 0.127047E+11 | 0.00 | 0.237729E+12 | 0.671030E+10 |
May | 0.428820E+12 | 0.765854E+10 | 0.00 | 0.302192E+12 | 0.169674E+11 |
June | 0.437588E+12 | 0.428176E+10 | 0.00 | 0.259228E+12 | 0.808207E+11 |
July | 0.397497E+12 | 0.329338E+10 | 0.00 | 0.265551E+12 | 0.109959E+12 |
August | 0.300927E+12 | 0.488395E+10 | 0.00 | 0.271460E+12 | 0.576118E+11 |
September | 0.146902E+12 | 0.680170E+10 | 0.00 | 0.250101E+12 | 0.419394E+10 |
October | 0.679592E+11 | 0.127264E+11 | 0.00 | 0.204664E+12 | 0.204815E+11 |
November | 0.925407E+10 | 0.126447E+11 | 0.00 | 0.198216E+12 | 0.511711E+11 |
December | -0.148296E+11 | 0.145203E+11 | 0.00 | 0.197617E+12 | 0.627320E+11 |
Annual Sum or Average | 0.238022E+13 | 0.124500E+12 | 0.00 | 0.276335E+13 | 0.543891E+12 |
Minimum of Months | -0.148296E+11 | 0.329338E+10 | 0.00 | 0.172172E+12 | 0.419394E+10 |
Maximum of Months | 0.437588E+12 | 0.161876E+11 | 0.00 | 0.302192E+12 | 0.109959E+12 |