Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:20:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2048.33 | 411.13 | 411.13 |
Net Site Energy | 2048.33 | 411.13 | 411.13 |
Total Source Energy | 5140.81 | 1031.84 | 1031.84 |
Net Source Energy | 5140.81 | 1031.84 | 1031.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 646.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 63.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1402.02 | 646.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 646.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 109.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 101.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 63.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 646.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 109.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 101.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 23.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 63.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 55.84 | 129.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 281.41 | 129.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 55.84 | 129.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 281.41 | 129.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1402.022 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1402.022 | 100.00 |
Total On-Site and Utility Electric Sources | 1402.022 | 100.00 |
Total Electricity End Uses | 1402.022 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 12.89 | 3.66 |
Air to Air Heat Recovery for Heating | 339.50 | 96.34 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 352.38 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 707.50 |
Time Setpoint Not Met During Occupied Cooling | 85.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3208.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUL-10:00 | 09-JAN-07:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 371219.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 74810.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41666.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35833.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5389.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 184798.47 | 371219.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 371219.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 74810.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 53.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 35833.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 5389.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 700.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 346.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 955.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 164.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 321.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 75.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4440.20 | 700.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 140.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 40.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 891.22 | 140.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 140.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 40.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 891.22 | 140.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.84 | 0.264058 | 0.278000 | 0.789026 | 0.704154 | 0.500000 | 0.001443 | 0.000154 | 0.789026 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.32 | 0.323454 | 0.336000 | 0.778525 | 0.862543 | 0.500000 | 0.001178 | 0.000239 | 0.846652 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.35 | 0.319177 | 0.341000 | 0.800698 | 0.851138 | 0.500000 | 0.001194 | 0.000417 | 1.48 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.712952 | 0.221602 | 0.237000 | 0.168970 | 0.590939 | 0.500000 | 0.001719 | 0.000194 | 0.691307 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.939826 | 0.106426 | 0.200000 | 0.187965 | 0.300000 | 0.500000 | 0.003580 | 0.000127 | 0.452170 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.21 | 0.130970 | 0.200000 | 0.241265 | 0.349252 | 0.500000 | 0.002909 | 0.000196 | 0.696898 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.02 | 0.098063 | 0.200000 | 0.203982 | 0.300000 | 0.500000 | 0.003885 | 0.000128 | 0.456278 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.566749 | 0.278768 | 0.293000 | 0.166057 | 0.743382 | 0.500000 | 0.001367 | 0.000154 | 0.548661 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.755532 | 0.132386 | 0.200000 | 0.151106 | 0.353029 | 0.500000 | 0.002878 | 0.000102 | 0.361718 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.967969 | 0.163220 | 0.200000 | 0.193594 | 0.435253 | 0.500000 | 0.002334 | 0.000156 | 0.554009 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.812377 | 0.123114 | 0.200000 | 0.162475 | 0.328305 | 0.500000 | 0.003095 | 0.000103 | 0.365248 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.641485 | 0.246290 | 0.256000 | 0.164220 | 0.656774 | 0.500000 | 0.001547 | 0.000152 | 0.541330 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.933817 | 0.107111 | 0.200000 | 0.186763 | 0.300000 | 0.500000 | 0.003557 | 0.000100 | 0.356300 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.13 | 0.140161 | 0.200000 | 0.225443 | 0.373763 | 0.500000 | 0.002718 | 0.000153 | 0.546061 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.960810 | 0.104095 | 0.200000 | 0.192162 | 0.300000 | 0.500000 | 0.003660 | 0.000101 | 0.359913 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17609.98 | 0.000154 | 408.44 |
CORE_MID VAV BOX REHEAT COIL | 27292.25 | 0.000239 | 720.88 |
CORE_TOP VAV BOX REHEAT COIL | 47695.04 | 0.000417 | 1258.49 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22196.25 | 0.000194 | 585.21 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14517.51 | 0.000127 | 382.75 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22375.53 | 0.000196 | 589.93 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14649.22 | 0.000128 | 386.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17621.77 | 0.000154 | 464.67 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11616.80 | 0.000102 | 306.32 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17793.24 | 0.000156 | 469.19 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11730.01 | 0.000103 | 309.30 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17386.93 | 0.000152 | 458.49 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11443.22 | 0.000100 | 301.74 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17538.62 | 0.000153 | 462.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11559.06 | 0.000101 | 304.80 |
PACU_VAV_BOT HEATING COIL | 60688.68 | 0.000531 | 895.12 |
PACU_VAV_MID HEATING COIL | 61535.08 | 0.000538 | 891.81 |
PACU_VAV_TOP HEATING COIL | 61578.07 | 0.000539 | 919.44 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.97 | 1.46 | 5.94 | 2.27 | 5.18 | 5.18 | 0.300000 | 0.437861 | 5.18 |
PACU_VAV_MID | 2.99 | 1.55 | 5.98 | 2.65 | 4.92 | 4.92 | 0.300000 | 0.538692 | 4.92 |
PACU_VAV_TOP | 3.11 | 1.60 | 6.23 | 3.78 | 5.50 | 5.50 | 0.300000 | 0.687040 | 5.50 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.18 |
PACU_VAV_MID_OA_CONTROLLER | 4.92 |
PACU_VAV_TOP_OA_CONTROLLER | 5.50 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.20 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.18 | 102512.00 | 0.780255 | 1.72 | 34167.25 | 0.780255 |
PACU_VAV_MID COOLING COIL | 4.92 | 98629.63 | 0.775579 | 1.64 | 32873.26 | 0.775579 |
PACU_VAV_TOP COOLING COIL | 5.50 | 107829.90 | 0.784494 | 1.83 | 35939.71 | 0.784494 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.18 |
PACU_VAV_MID FAN | 4.92 |
PACU_VAV_TOP FAN | 5.50 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000531 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000538 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000539 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004084 | 0.490081 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.004084 | 1229.92 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 466827.27 | 466827.27 | 0.004084 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.33_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.33_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5418E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5499E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7355E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7425E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.6435E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6993E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1752E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2040E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2050 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1199 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2356 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1393 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1350 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9246E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7226E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1466E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5420E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5515E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7357E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7443E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.6455E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7097E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1749E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2037E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.6238E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6268E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.2919E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3422E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.0183E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5622E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7181E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1654E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.5242E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.5578E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2262E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.2506E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4994E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.5078E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0399E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0498E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7844E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8562E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8259E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8846E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1489E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1923E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1749E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.2037E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6525E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2387E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3679E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4772E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9755E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6699E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7226E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1466E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7841E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8572E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8250E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8830E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1470E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1848E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.1752E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.2040E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 8.1459E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8797E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.3954E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3788E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.9448E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0465E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7182E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1655E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.5906E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.6964E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0233E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1438E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8468E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.8839E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0401E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0500E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2058 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1434 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2329 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1657 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1454 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.4845E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.5235E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0443E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.2983E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.4402E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.9904E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.1691E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.8012E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4331E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5934E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0905E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.4105E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.1914E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0400E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2944E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6463E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4117E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.5235E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0443E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.8707E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.7273E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.1591E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.2500E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.7605E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9395E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5934E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0906E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2058 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1434 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2329 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1656 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1454 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.4836E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.5229E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0440E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.2982E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.4398E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.9903E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1687E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.8007E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4327E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5928E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0902E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.4107E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1912E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0401E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2943E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6460E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4114E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.5229E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0440E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.8707E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.7270E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.1590E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2497E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.7600E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9391E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5928E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0902E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37749.47050 | 37749.47050 | 2.83822 | 2.83822 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9996.89909 | 9996.89909 | 0.44733 | 0.44733 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30842.98174 | 30842.98174 | 2.31704 | 2.31704 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 19123.16205 | 19123.16205 | 0.84665 | 0.84665 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30969.43840 | 30969.43840 | 2.34809 | 2.34809 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 33386.85637 | 33386.85637 | 1.48291 | 1.48291 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9403.11665 | 9403.11665 | 0.71295 | 0.71295 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15527.97989 | 15527.97989 | 0.69131 | 0.69131 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 12395.49572 | 12395.49572 | 0.93983 | 0.93983 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10155.95659 | 10155.95659 | 0.45217 | 0.45217 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15910.32288 | 15910.32288 | 1.20632 | 1.20632 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15653.32035 | 15653.32035 | 0.69690 | 0.69690 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 13451.76311 | 13451.76311 | 1.01991 | 1.01991 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10248.03951 | 10248.03951 | 0.45628 | 0.45628 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7474.92755 | 7474.92755 | 0.56675 | 0.56675 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12328.91774 | 12328.91774 | 0.54866 | 0.54866 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9964.91996 | 9964.91996 | 0.75553 | 0.75553 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.33400 | 1.27158E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8127.37507 | 8127.37507 | 0.36172 | 0.36172 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12766.77393 | 12766.77393 | 0.96797 | 0.96797 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12448.79430 | 12448.79430 | 0.55401 | 0.55401 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10714.67053 | 10714.67053 | 0.81238 | 0.81238 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 26.50400 | 1.27196E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8206.51571 | 8206.51571 | 0.36525 | 0.36525 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8460.55236 | 8460.55236 | 0.64149 | 0.64149 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 25.26400 | 1.27174E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12165.36388 | 12165.36388 | 0.54133 | 0.54133 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 12316.29868 | 12316.29868 | 0.93382 | 0.93382 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 22.88733 | 1.27133E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8006.43097 | 8006.43097 | 0.35630 | 0.35630 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14866.99149 | 14866.99149 | 1.12721 | 1.12721 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12271.41043 | 12271.41043 | 0.54606 | 0.54606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 12672.30621 | 12672.30621 | 0.96081 | 0.96081 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8087.41557 | 8087.41557 | 0.35991 | 0.35991 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 75642.40 | 5.17537 | 5.17537 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 62709.73 | 2.26609 | 2.26609 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 72287.63 | 4.91980 | 4.91980 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 62711.46 | 2.65026 | 2.65026 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 79738.35 | 5.50123 | 5.50123 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 63038.91 | 3.77957 | 3.77957 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83822 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26406 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78903 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70415 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44287E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54060E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78903 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17609.97629 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54060E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 408.43532 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31704 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32345 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77853 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86254 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17791E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.38765E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84665 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27292.25382 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.38765E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 720.87971 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34809 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31918 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80070 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85114 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19370E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.17257E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.48291 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 47695.03507 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.17257E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1258.48586 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71295 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22160 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16897 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59094 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71930E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94182E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69131 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22196.24737 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94182E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 585.21065 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93983 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10643 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18797 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.57996E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27006E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45217 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14517.51168 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27006E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 382.75094 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20632 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13097 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24126 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34925 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90907E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95751E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69690 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22375.53070 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95751E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 589.93469 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01991 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.80627E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20398 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.88527E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28158E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45628 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14649.22405 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28158E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.22151 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56675 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27877 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16606 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74338 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36673E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54163E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54866 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17621.76816 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54163E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 464.66982 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75553 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13239 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15111 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35303 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87795E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01629E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36172 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11616.80357 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01629E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.31528 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96797 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16322 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19359 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43525 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33428E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55663E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55401 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17793.24320 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55663E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 469.18806 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81238 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12311 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16248 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32830 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09468E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02619E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36525 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11730.00888 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02619E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 309.29813 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64149 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24629 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16422 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65677 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54695E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52108E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54133 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17386.93322 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52108E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 458.48502 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93382 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10711 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18676 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.55707E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00110E-004 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35630 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11443.21942 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00110E-004 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 301.74316 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12721 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14016 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22544 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37376 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71830E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53436E-004 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54606 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17538.62397 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53436E-004 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 462.48195 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96081 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10409 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19216 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66013E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01124E-004 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35991 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11559.06063 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01124E-004 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 304.79549 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97043 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46226 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.94085 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.26609 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.17537 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.17537 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43786 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99018 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54711 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.98037 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.65026 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91980 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.91980 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.53869 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.11355 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60288 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.22710 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.77957 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.50123 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.50123 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.68704 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.17537 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.91980 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.50123 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.17537 |
239 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.17537 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 102511.99987 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78025 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.72495 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34167.24956 |
245 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78025 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 60688.67906 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.30931E-004 |
248 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 895.11531 |
249 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.17537 |
250 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.30931E-004 |
251 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91980 |
252 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.91980 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98629.62854 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.77558 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63977 |
257 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32873.25519 |
258 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.77558 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 61535.08429 |
260 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38336E-004 |
261 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 891.81057 |
262 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.91980 |
263 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.38336E-004 |
264 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.50123 |
265 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.50123 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107829.89851 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78449 |
269 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.83356 |
270 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35939.70518 |
271 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78449 |
272 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 61578.06788 |
273 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38712E-004 |
274 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 919.44243 |
275 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.50123 |
276 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.38712E-004 |
277 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.08401E-003 |
278 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.49008 |
279 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.08401E-003 |
280 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1229.92405 |
281 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
282 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 466827.27126 |
283 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 466827.27000 |
284 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.08401E-003 |
285 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
286 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
287 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
288 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
289 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16685.94 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25867.00 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 45195.61 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21029.97 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13754.65 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21199.81 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13879.43 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16696.30 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11006.64 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16858.74 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11113.89 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16473.85 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10842.21 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16617.55 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10951.95 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 38765.75 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 38468.80 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 39924.03 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 101534.77 | 346451.00 | 12.10 | 3.10 | 3.46 | 3.64 | 3.84 | 10.58 | 11.82 | 12.43 | 13.11 | 5.7361 | 4.5864 | 3.0899 | 1.2360 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 97735.47 | 333487.26 | 12.13 | 3.11 | 3.47 | 3.65 | 3.85 | 10.61 | 11.85 | 12.46 | 13.13 | 5.4529 | 4.3587 | 2.9362 | 1.1798 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 106757.59 | 364272.03 | 12.07 | 3.10 | 3.46 | 3.63 | 3.84 | 10.57 | 11.79 | 12.40 | 13.10 | 6.0973 | 4.8768 | 3.2855 | 1.3095 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0332264967E-002 | 3.4020656088E-002 | Pass | Pass | 0.4863894799 | 0.4947152174 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2753953267 | 0.2165587468 | Pass | Pass | 0.4970905947 | 0.5025797477 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1187153667 | 7.5466455207E-002 | Pass | Pass | 0.4895616372 | 0.4893967899 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1052617020 | 6.5563889123E-002 | Pass | Pass | 0.4843049851 | 0.4875610057 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.3438623162E-002 | 2.6642496778E-002 | Pass | Pass | 1.4322036442 | 7.3643822422 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1807883639 | 0.2014703536 | Pass | Pass | 0.6822995328 | 0.6617166620 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.9050439382 | 0.7703656407 | Pass | Pass | 0.5856507407 | 0.5546357644 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7936402429 | 0.8022831339 | Pass | Pass | 0.6163098694 | 0.5939380604 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5879527270 | 0.6735599641 | Pass | Pass | 0.6521224861 | 0.8768921523 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8263537081 | 0.8473922321 | Pass | Pass | 0.6413942854 | 0.6233752126 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7007887106 | 0.6053805897 | Pass | Pass | 0.6093341154 | 0.5736358319 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5677359879 | 0.5910519976 | Pass | Pass | 0.6545280063 | 0.6761870140 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3045382356 | 0.3536245088 | Pass | Pass | 0.6906831794 | 0.9734333054 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5989518398 | 0.6282705672 | Pass | Pass | 0.8652848992 | 2.6214029154 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6872738303 | 0.6022922228 | Pass | Pass | 0.6240787261 | 0.5585923305 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5776241502 | 0.6234915262 | Pass | Pass | 0.8049396424 | 1.7104940074 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4377487479 | 0.4811229335 | Pass | Pass | 1.1408431665 | 6.4296038073 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6094258292 | 0.6542935816 | Pass | Pass | 1.9390705830 | 11.0232264643 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3363.37 | 124.96 | 0.00 | 2287.93 | 776.42 | 6552.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.33_SHGC_NORTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.33_SHGC_EAST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.33_SHGC_WEST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.33_SHGC_EAST_0.45 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.33_SHGC_EAST_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.33_SHGC_WEST_0.45 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.33_SHGC_WEST_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.33_SHGC_NORTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.33_SHGC_EAST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.33_SHGC_WEST_0.45 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 195.79 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.875 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 5.55 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.61 | 0.0000 | Y | 8.67 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.84 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.10 | 0.0000 | Y | 8.84 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 8.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.78 | 0.0000 | Y | 5.53 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.18 | 0.0000 | Y | 8.86 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 5.55 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.61 | 0.0000 | Y | 8.67 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.84 | 0.0000 | Y | 5.54 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.60 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.55 | 42.55 | 4.50 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.52 | 63.04 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.52 | 47.99 | 42.47 | |
Exterior Lighting Total | 5686.19 | 51.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 466827.27 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 102512.00 | 79985.46 | 22526.54 | 0.78 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98629.63 | 76495.06 | 22134.57 | 0.78 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107829.90 | 84591.86 | 23238.04 | 0.78 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 101534.8 | 3.10 | 10.58 | N/A | N/A | 12.10 | |
PACU_VAV_MID COOLING COIL | 97735.5 | 3.11 | 10.61 | N/A | N/A | 12.13 | |
PACU_VAV_TOP COOLING COIL | 106757.6 | 3.10 | 10.57 | N/A | N/A | 12.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17609.98 | 16685.94 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 27292.25 | 25867.00 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 47695.04 | 45195.61 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22196.25 | 21029.97 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14517.51 | 13754.65 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22375.53 | 21199.81 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14649.22 | 13879.43 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17621.77 | 16696.30 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11616.80 | 11006.64 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17793.24 | 16858.74 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11730.01 | 11113.89 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17386.93 | 16473.85 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11443.22 | 10842.21 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17538.62 | 16617.55 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11559.06 | 10951.95 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 60688.68 | 38765.75 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 61535.08 | 38468.80 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 61578.07 | 39924.03 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.18 | 11895.38 | 2298.46 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.92 | 11307.96 | 2298.46 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.50 | 12644.37 | 2298.46 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004084 | 1229.92 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101534.77 | 3.10 | 10.58 | 12.10 | 5.7361 | 3.46 | 11.82 | 4.5864 | 3.64 | 12.43 | 3.0899 | 3.84 | 13.11 | 1.2360 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97735.47 | 3.11 | 10.61 | 12.13 | 5.4529 | 3.47 | 11.85 | 4.3587 | 3.65 | 12.46 | 2.9362 | 3.85 | 13.13 | 1.1798 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106757.59 | 3.10 | 10.57 | 12.07 | 6.0973 | 3.46 | 11.79 | 4.8768 | 3.63 | 12.40 | 3.2855 | 3.84 | 13.10 | 1.3095 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37749.47 | 37749.47 | 38.38 | 2.838 | 2.838 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_MID | 30842.98 | 30842.98 | 31.36 | 2.317 | 2.317 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 20.92 | 0.01271 | 0.425 | 0.00 |
CORE_TOP | 30969.44 | 30969.44 | 31.49 | 2.348 | 2.348 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00889 | 29.85 | 0.01273 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9403.12 | 9403.12 | 45.35 | 0.713 | 0.713 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00885 | 29.98 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 12395.50 | 12395.50 | 94.43 | 0.940 | 0.940 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00867 | 23.28 | 0.01271 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15910.32 | 15910.32 | 76.74 | 1.206 | 1.206 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00871 | 29.79 | 0.01273 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 13451.76 | 13451.76 | 102.49 | 1.020 | 1.020 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00866 | 27.95 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7474.93 | 7474.93 | 36.05 | 0.567 | 0.567 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9964.92 | 9964.92 | 75.92 | 0.756 | 0.756 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00869 | 24.33 | 0.01272 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12766.77 | 12766.77 | 61.57 | 0.968 | 0.968 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00873 | 30.10 | 0.01273 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10714.67 | 10714.67 | 81.63 | 0.812 | 0.812 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00868 | 26.50 | 0.01272 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8460.55 | 8460.55 | 40.81 | 0.641 | 0.641 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00887 | 25.26 | 0.01272 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 12316.30 | 12316.30 | 93.83 | 0.934 | 0.934 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00867 | 22.89 | 0.01271 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14866.99 | 14866.99 | 71.70 | 1.127 | 1.127 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00872 | 29.69 | 0.01273 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 12672.31 | 12672.31 | 96.55 | 0.961 | 0.961 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00866 | 27.95 | 0.01272 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9996.90 | 9996.90 | 10.16 | 0.447 | 0.447 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_MID | 19123.16 | 19123.16 | 19.44 | 0.847 | 0.847 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
CORE_TOP | 33386.86 | 33386.86 | 33.95 | 1.483 | 1.483 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15527.98 | 15527.98 | 74.89 | 0.691 | 0.691 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10155.96 | 10155.96 | 77.37 | 0.452 | 0.452 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15653.32 | 15653.32 | 75.50 | 0.697 | 0.697 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10248.04 | 10248.04 | 78.08 | 0.456 | 0.456 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12328.92 | 12328.92 | 59.46 | 0.549 | 0.549 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8127.38 | 8127.38 | 61.92 | 0.362 | 0.362 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12448.79 | 12448.79 | 60.04 | 0.554 | 0.554 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8206.52 | 8206.52 | 62.52 | 0.365 | 0.365 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12165.36 | 12165.36 | 58.67 | 0.541 | 0.541 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8006.43 | 8006.43 | 61.00 | 0.356 | 0.356 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12271.41 | 12271.41 | 59.19 | 0.546 | 0.546 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8087.42 | 8087.42 | 61.62 | 0.360 | 0.360 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.18 | 5.18 | 2.27 | 2.27 | 5.1754 | 2.2661 | 5.1754 | 0.4379 | 0.3000 |
PACU_VAV_MID | 4.92 | 4.92 | 2.65 | 2.65 | 4.9198 | 2.6503 | 4.9198 | 0.5387 | 0.3000 |
PACU_VAV_TOP | 5.50 | 5.50 | 3.78 | 3.78 | 5.5012 | 3.7796 | 5.5012 | 0.6870 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17609.976 | 17609.976 | 0.789026 | 0.00015406 | 408.435 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 17609.98 | 17609.98 | 0.789026 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 9996.90 | 0.00 | 17668.12 | 17668.12 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27292.254 | 27292.254 | 0.846652 | 0.00023876 | 720.880 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27292.25 | 27292.25 | 0.846652 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 19123.16 | 0.00 | 27389.77 | 27389.77 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 47695.035 | 47695.035 | 1.482913 | 0.00041726 | 1258.486 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47695.04 | 47695.04 | 1.482913 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 33386.86 | 0.00 | 47856.14 | 47856.14 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22196.247 | 22196.247 | 0.691307 | 0.00019418 | 585.211 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22196.25 | 22196.25 | 0.691307 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788614 | 48.8651 | 15527.98 | 0.00 | 22267.90 | 22267.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14517.512 | 14517.512 | 0.452170 | 0.00012701 | 382.751 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14517.51 | 14517.51 | 0.452170 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788402 | 48.8522 | 10155.96 | 0.00 | 14564.32 | 14564.32 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22375.531 | 22375.531 | 0.696898 | 0.00019575 | 589.935 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22375.53 | 22375.53 | 0.696898 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788706 | 48.8707 | 15653.32 | 0.00 | 22447.74 | 22447.74 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14649.224 | 14649.224 | 0.456278 | 0.00012816 | 386.222 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14649.22 | 14649.22 | 0.456278 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788507 | 48.8586 | 10248.04 | 0.00 | 14696.44 | 14696.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17621.768 | 17621.768 | 0.548661 | 0.00015416 | 464.670 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17621.77 | 17621.77 | 0.548661 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00792177 | 49.0822 | 12328.92 | 0.00 | 17679.13 | 17679.13 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11616.804 | 11616.804 | 0.361718 | 0.00010163 | 306.315 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11616.80 | 11616.80 | 0.361718 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00792139 | 49.0799 | 8127.38 | 0.00 | 11654.55 | 11654.55 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17793.243 | 17793.243 | 0.554009 | 0.00015566 | 469.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17793.24 | 17793.24 | 0.554009 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00792265 | 49.0876 | 12448.79 | 0.00 | 17851.14 | 17851.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11730.009 | 11730.009 | 0.365248 | 0.00010262 | 309.298 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11730.01 | 11730.01 | 0.365248 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00792225 | 49.0852 | 8206.52 | 0.00 | 11768.11 | 11768.11 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17386.933 | 17386.933 | 0.541330 | 0.00015211 | 458.485 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17386.93 | 17386.93 | 0.541330 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787724 | 48.8104 | 12165.36 | 0.00 | 17443.59 | 17443.59 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11443.219 | 11443.219 | 0.356300 | 0.00010011 | 301.743 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11443.22 | 11443.22 | 0.356300 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787621 | 48.8041 | 8006.43 | 0.00 | 11480.44 | 11480.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17538.624 | 17538.624 | 0.546061 | 0.00015344 | 462.482 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17538.62 | 17538.62 | 0.546061 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787842 | 48.8176 | 12271.41 | 0.00 | 17595.75 | 17595.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11559.061 | 11559.061 | 0.359913 | 0.00010112 | 304.795 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11559.06 | 11559.06 | 0.359913 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00787755 | 48.8124 | 8087.42 | 0.00 | 11596.64 | 11596.64 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 102512.000 | 79985.456 | 5.175366 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 104142.62 | 86013.76 | 5.175366 | 25.41 | 17.44 | 0.00972006 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 23.0934 | 24.00 | 0.00881719 | 45.4640 | 68242.26 | 0.00 | 105703.63 | 79472.99 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 60688.679 | 60688.679 | 1.552610 | 0.00053093 | 895.115 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60688.68 | 60688.68 | 1.552610 | -20.91 | -20.91 | 0.00194957 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 76.9781 | 18.16 | 0.00785856 | 58.0762 | 20508.36 | 0.00 | 46880.50 | 46880.50 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 98629.629 | 76495.063 | 4.919796 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100352.29 | 82147.62 | 4.919796 | 25.48 | 17.52 | 0.00978932 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 24.2931 | 24.00 | 0.00884601 | 45.6107 | 64834.71 | 0.00 | 101700.39 | 76026.81 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 61535.084 | 61535.084 | 1.475939 | 0.00053834 | 891.811 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61535.08 | 61535.08 | 1.475939 | -23.16 | -23.16 | 0.00163235 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 80.9769 | 17.60 | 0.00771255 | 59.0785 | 23452.33 | 0.00 | 46513.32 | 46513.32 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 107829.899 | 84591.857 | 5.501230 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 109401.60 | 90956.42 | 5.501230 | 25.33 | 17.37 | 0.00966738 | 10.85 | 10.85 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 21.7255 | 24.00 | 0.00881617 | 45.4590 | 72402.43 | 0.00 | 111187.10 | 84024.41 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 61578.068 | 61578.068 | 1.650369 | 0.00053871 | 919.442 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61578.07 | 61578.07 | 1.650369 | -19.38 | -19.38 | 0.00228021 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 72.4184 | 15.60 | 0.00770536 | 67.0303 | 25070.47 | 0.00 | 48288.08 | 48288.08 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17609.976 | 17609.976 | 0.789026 | 0.00015406 | 408.435 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.6978 | 3.772268 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 17609.98 | 17609.98 | 1.0000 | 0.91047709 | 0.789026 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15404404 | 60.00 | 32.22 | 27.78 | 0.000 | 17609.98 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 9996.90 | 0.00 | 17668.12 | 17668.12 | 0.91047709 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.83 | 18.64 | 0.00800000 | 52465.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 27292.254 | 27292.254 | 0.846652 | 0.00023876 | 720.880 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 5.7310 | 5.846328 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27292.25 | 27292.25 | 1.0000 | 0.97697300 | 0.846652 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.23874019 | 60.00 | 32.22 | 27.78 | 0.000 | 27292.25 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 19123.16 | 0.00 | 27389.77 | 27389.77 | 0.97697300 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61095.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 47695.035 | 47695.035 | 1.482913 | 0.00041726 | 1258.486 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 10.0153 | 10.216849 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47695.04 | 47695.04 | 1.0000 | 1.71116994 | 1.482913 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.41721441 | 60.00 | 32.22 | 27.78 | 0.000 | 47695.04 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 33386.86 | 0.00 | 47856.14 | 47856.14 | 1.71116994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61026.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22196.247 | 22196.247 | 0.691307 | 0.00019418 | 585.211 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 4.6609 | 4.754702 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22196.25 | 22196.25 | 1.0000 | 0.79771596 | 0.691307 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.19416265 | 60.00 | 32.22 | 27.78 | 0.000 | 22196.25 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788614 | 21.00 | 0.00788614 | 48.8651 | 15527.98 | 0.00 | 22267.90 | 22267.90 | 0.79771596 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14517.512 | 14517.512 | 0.452170 | 0.00012701 | 382.751 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.0485 | 3.109825 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14517.51 | 14517.51 | 1.0000 | 0.52177071 | 0.452170 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12699257 | 60.00 | 32.22 | 27.78 | 0.000 | 14517.51 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788402 | 21.00 | 0.00788402 | 48.8522 | 10155.96 | 0.00 | 14564.32 | 14564.32 | 0.52177071 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22375.531 | 22375.531 | 0.696898 | 0.00019575 | 589.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 4.6985 | 4.793107 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22375.53 | 22375.53 | 1.0000 | 0.80416767 | 0.696898 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.19573093 | 60.00 | 32.22 | 27.78 | 0.000 | 22375.53 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788706 | 21.00 | 0.00788706 | 48.8707 | 15653.32 | 0.00 | 22447.74 | 22447.74 | 0.80416767 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14649.224 | 14649.224 | 0.456278 | 0.00012816 | 386.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.0761 | 3.138039 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14649.22 | 14649.22 | 1.0000 | 0.52651052 | 0.456278 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12814473 | 60.00 | 32.22 | 27.78 | 0.000 | 14649.22 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788507 | 21.00 | 0.00788507 | 48.8586 | 10248.04 | 0.00 | 14696.44 | 14696.44 | 0.52651052 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17621.768 | 17621.768 | 0.548661 | 0.00015416 | 464.670 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.7003 | 3.774794 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17621.77 | 17621.77 | 1.0000 | 0.63311385 | 0.548661 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15414719 | 60.00 | 32.22 | 27.78 | 0.000 | 17621.77 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00792177 | 21.00 | 0.00792177 | 49.0822 | 12328.92 | 0.00 | 17679.13 | 17679.13 | 0.63311385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11616.804 | 11616.804 | 0.361718 | 0.00010163 | 306.315 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 2.4394 | 2.488459 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11616.80 | 11616.80 | 1.0000 | 0.41739512 | 0.361718 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10161850 | 60.00 | 32.22 | 27.78 | 0.000 | 11616.80 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00792139 | 21.00 | 0.00792139 | 49.0799 | 8127.38 | 0.00 | 11654.55 | 11654.55 | 0.41739512 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17793.243 | 17793.243 | 0.554009 | 0.00015566 | 469.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.7363 | 3.811526 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17793.24 | 17793.24 | 1.0000 | 0.63928474 | 0.554009 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15564717 | 60.00 | 32.22 | 27.78 | 0.000 | 17793.24 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00792265 | 21.00 | 0.00792265 | 49.0876 | 12448.79 | 0.00 | 17851.14 | 17851.14 | 0.63928474 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11730.009 | 11730.009 | 0.365248 | 0.00010262 | 309.298 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 2.4631 | 2.512709 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11730.01 | 11730.01 | 1.0000 | 0.42146910 | 0.365248 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10260877 | 60.00 | 32.22 | 27.78 | 0.000 | 11730.01 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00792225 | 21.00 | 0.00792225 | 49.0852 | 8206.52 | 0.00 | 11768.11 | 11768.11 | 0.42146910 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17386.933 | 17386.933 | 0.541330 | 0.00015211 | 458.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.6510 | 3.724490 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17386.93 | 17386.93 | 1.0000 | 0.62465413 | 0.541330 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15209296 | 60.00 | 32.22 | 27.78 | 0.000 | 17386.93 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787724 | 21.00 | 0.00787724 | 48.8104 | 12165.36 | 0.00 | 17443.59 | 17443.59 | 0.62465413 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11443.219 | 11443.219 | 0.356300 | 0.00010011 | 301.743 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 2.4029 | 2.451275 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11443.22 | 11443.22 | 1.0000 | 0.41114327 | 0.356300 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10010006 | 60.00 | 32.22 | 27.78 | 0.000 | 11443.22 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787621 | 21.00 | 0.00787621 | 48.8041 | 8006.43 | 0.00 | 11480.44 | 11480.44 | 0.41114327 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17538.624 | 17538.624 | 0.546061 | 0.00015344 | 462.482 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 3.6829 | 3.756984 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17538.62 | 17538.62 | 1.0000 | 0.63011306 | 0.546061 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.15341988 | 60.00 | 32.22 | 27.78 | 0.000 | 17538.62 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787842 | 21.00 | 0.00787842 | 48.8176 | 12271.41 | 0.00 | 17595.75 | 17595.75 | 0.63011306 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11559.061 | 11559.061 | 0.359913 | 0.00010112 | 304.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 2.4272 | 2.476089 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11559.06 | 11559.06 | 1.0000 | 0.41531208 | 0.359913 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10111339 | 60.00 | 32.22 | 27.78 | 0.000 | 11559.06 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787755 | 21.00 | 0.00787755 | 48.8124 | 8087.42 | 0.00 | 11596.64 | 11596.64 | 0.41531208 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.5 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 102512.000 | 79985.456 | 5.175366 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9091 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.175366 | 5.97198395 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 104142.62 | 86013.76 | 1.0159 | 5.97198395 | 5.175366 | 25.41 | 17.44 | 0.00972006 | 50299.4 | 10.85 | 10.85 | 0.00850000 | 32334.7 | -999.0 | -999.00 | -999.00 | -999.00 | 11895.381 | 92247.24 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 23.0934 | 24.00 | 0.00881719 | 24.00 | 0.00881719 | 45.4640 | 68242.26 | 0.00 | 105703.63 | 79472.99 | 5.73613573 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.11 | 13.10 | 0.00939174 | 36894.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 60688.679 | 60688.679 | 1.552610 | 0.00053093 | 895.115 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.175366 | 5.97198395 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 12.7438 | 13.000243 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60688.68 | 60688.68 | 1.0000 | 1.79159518 | 1.552610 | -20.91 | -20.91 | 0.00194957 | -16211.6 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 0.53087688 | 60.00 | 32.22 | 27.78 | 0.000 | 60688.68 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 76.9781 | 18.51 | 0.00785517 | 18.16 | 0.00785856 | 58.0762 | 20508.36 | 0.00 | 46880.50 | 46880.50 | 1.79159518 | 2.80 | -1.26 | 0.00194957 | 7699.4 | 28.75 | 12.06 | 0.00194957 | 33866.3 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98629.629 | 76495.063 | 4.919796 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0379 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.919796 | 5.67707478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 100352.29 | 82147.62 | 1.0175 | 5.67707478 | 4.919796 | 25.48 | 17.52 | 0.00978932 | 50551.6 | 10.85 | 10.85 | 0.00850000 | 32335.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11307.962 | 89044.33 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 24.2931 | 24.00 | 0.00884601 | 24.00 | 0.00884601 | 45.6107 | 64834.71 | 0.00 | 101700.39 | 76026.81 | 5.45287324 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.03 | 13.02 | 0.00933866 | 36671.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 61535.084 | 61535.084 | 1.475939 | 0.00053834 | 891.811 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.919796 | 5.67707478 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 12.9215 | 13.181553 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61535.08 | 61535.08 | 1.0000 | 1.70312243 | 1.475939 | -23.16 | -23.16 | 0.00163235 | -19256.0 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 0.53828085 | 60.00 | 32.22 | 27.78 | 0.000 | 61535.08 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 80.9769 | 17.47 | 0.00780034 | 17.60 | 0.00771255 | 59.0785 | 23452.33 | 0.00 | 46513.32 | 46513.32 | 1.70312243 | 2.80 | -1.76 | 0.00163235 | 6904.5 | 29.90 | 12.21 | 0.00163235 | 34215.1 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107829.899 | 84591.857 | 5.501230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8112 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.501230 | 6.34800597 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 109401.60 | 90956.42 | 1.0146 | 6.34800597 | 5.501230 | 25.33 | 17.37 | 0.00966738 | 50082.3 | 10.85 | 10.85 | 0.00850000 | 32334.6 | -999.0 | -999.00 | -999.00 | -999.00 | 12644.365 | 96757.23 | 30.10 | 0.01272586 | 21.13 | 1.19517000 | 21.7255 | 24.00 | 0.00881617 | 24.00 | 0.00881617 | 45.4590 | 72402.43 | 0.00 | 111187.10 | 84024.41 | 6.09730772 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.19 | 13.18 | 0.00943801 | 37086.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 61578.068 | 61578.068 | 1.650369 | 0.00053871 | 919.442 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.501230 | 6.34800597 | 4197.9300 | 999.8980 | 4.08359201 | 54.44 | 82.22 | 27.78 | 476222.36 | 12.9305 | 13.190761 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61578.07 | 61578.07 | 1.0000 | 1.90440179 | 1.650369 | -19.38 | -19.38 | 0.00228021 | -13851.5 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 0.53865685 | 60.00 | 32.22 | 27.78 | 0.000 | 61578.07 | -32.70 | 0.00018338 | -32.70 | 1.19517000 | 72.4184 | 15.60 | 0.00778566 | 15.60 | 0.00770536 | 67.0303 | 25070.47 | 0.00 | 48288.08 | 48288.08 | 1.90440179 | 2.80 | -0.75 | 0.00228021 | 8528.1 | 27.93 | 12.06 | 0.00228021 | 33884.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.18 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.92 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.50 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2160.67 | 3147.83 | 328.50 |
CORE_MID | 2785.50 | 3803.50 | 1362.83 |
CORE_TOP | 3293.83 | 4112.17 | 2060.00 |
PERIMETER_TOP_ZN_3 | 3973.33 | 4296.50 | 2764.83 |
PERIMETER_TOP_ZN_2 | 4007.17 | 4121.33 | 2600.17 |
PERIMETER_TOP_ZN_1 | 3663.17 | 3975.17 | 2214.33 |
PERIMETER_TOP_ZN_4 | 3912.67 | 4326.83 | 2643.50 |
PERIMETER_BOT_ZN_3 | 3855.83 | 4347.33 | 2725.67 |
PERIMETER_BOT_ZN_2 | 3981.17 | 3978.83 | 2461.83 |
PERIMETER_BOT_ZN_1 | 3677.33 | 4198.17 | 2349.00 |
PERIMETER_BOT_ZN_4 | 3925.50 | 4096.33 | 2501.67 |
PERIMETER_MID_ZN_3 | 3835.83 | 4061.83 | 2473.50 |
PERIMETER_MID_ZN_2 | 3298.83 | 3409.83 | 2056.83 |
PERIMETER_MID_ZN_1 | 3498.50 | 3676.33 | 1874.50 |
PERIMETER_MID_ZN_4 | 3784.50 | 4081.00 | 2338.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5221.17 | 4864.67 | 3208.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 3.00 | 1.17 | 3.00 | 1.00 |
CORE_MID | 10.50 | 0.67 | 9.67 | 0.67 |
CORE_TOP | 33.33 | 0.33 | 27.50 | 0.33 |
PERIMETER_TOP_ZN_3 | 313.17 | 1.83 | 173.00 | 1.67 |
PERIMETER_TOP_ZN_2 | 193.83 | 14.83 | 63.67 | 14.83 |
PERIMETER_TOP_ZN_1 | 160.67 | 22.50 | 54.33 | 22.17 |
PERIMETER_TOP_ZN_4 | 186.50 | 22.67 | 61.83 | 12.17 |
PERIMETER_BOT_ZN_3 | 200.17 | 0.50 | 161.50 | 0.50 |
PERIMETER_BOT_ZN_2 | 64.67 | 10.17 | 32.17 | 10.17 |
PERIMETER_BOT_ZN_1 | 638.00 | 16.17 | 615.17 | 16.00 |
PERIMETER_BOT_ZN_4 | 66.83 | 18.00 | 34.67 | 9.17 |
PERIMETER_MID_ZN_3 | 139.83 | 2.83 | 92.50 | 2.83 |
PERIMETER_MID_ZN_2 | 72.67 | 17.83 | 28.00 | 17.83 |
PERIMETER_MID_ZN_1 | 56.50 | 27.17 | 22.83 | 27.00 |
PERIMETER_MID_ZN_4 | 73.17 | 22.50 | 29.50 | 12.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 889.83 | 103.33 | 707.50 | 85.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.912 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.682 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.664 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.789 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.395 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 1.272 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.410 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.682 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.154 | 0.022 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 1.033 | 0.851 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.133 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.783 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.304 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 1.257 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.372 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14465637.42 | 0.00 | 14465637.42 | 0.00 | 14465637.42 | 13393058.27 | 6141.40 | 32.55 | 2586.05 | 248.86 |
CORE_MID | 10870229.06 | 0.00 | 10870229.06 | 0.00 | 10870229.06 | 13393058.27 | 6658.32 | 28.94 | 2072.74 | 271.96 |
CORE_TOP | 10576985.27 | 0.00 | 10576985.27 | 0.00 | 10576985.27 | 13393058.27 | 6695.54 | 21.41 | 2043.05 | 80.62 |
PERIMETER_TOP_ZN_3 | 2645415.82 | 0.00 | 2645415.82 | 249519.24 | 2894935.06 | 2823374.22 | 5791.62 | 48.73 | 2919.64 | 80.62 |
PERIMETER_TOP_ZN_2 | 2958381.18 | 0.00 | 2958381.18 | 166345.16 | 3124726.34 | 1787429.43 | 4080.84 | 1.11 | 4678.05 | 80.62 |
PERIMETER_TOP_ZN_1 | 4254933.38 | 0.00 | 4254933.38 | 249519.24 | 4504452.62 | 2823374.22 | 4098.02 | 3.22 | 4658.75 | 80.62 |
PERIMETER_TOP_ZN_4 | 3006911.54 | 0.00 | 3006911.54 | 166345.16 | 3173256.71 | 1787312.18 | 4077.57 | 2.00 | 4680.43 | 80.62 |
PERIMETER_BOT_ZN_3 | 2300712.18 | 0.00 | 2300712.18 | 132667.22 | 2433379.40 | 2823374.22 | 6076.95 | 52.47 | 2630.58 | 248.86 |
PERIMETER_BOT_ZN_2 | 2454900.85 | 0.00 | 2454900.85 | 88444.28 | 2543345.13 | 1787429.43 | 4122.57 | 7.42 | 4630.01 | 248.86 |
PERIMETER_BOT_ZN_1 | 3482631.35 | 0.00 | 3482631.35 | 2924357.98 | 6406989.34 | 2823374.22 | 4212.88 | 53.44 | 4493.68 | 248.86 |
PERIMETER_BOT_ZN_4 | 2421405.29 | 0.00 | 2421405.29 | 88444.28 | 2509849.58 | 1787312.18 | 4117.42 | 8.79 | 4633.80 | 248.86 |
PERIMETER_MID_ZN_3 | 2628060.09 | 0.00 | 2628060.09 | 207704.95 | 2835765.05 | 2823374.22 | 6056.96 | 51.96 | 2651.08 | 271.96 |
PERIMETER_MID_ZN_2 | 2986214.43 | 0.00 | 2986214.43 | 138469.14 | 3124683.57 | 1787429.43 | 4052.20 | 1.34 | 4706.46 | 1180.96 |
PERIMETER_MID_ZN_1 | 4208227.23 | 0.00 | 4208227.23 | 207704.95 | 4415932.18 | 2823374.22 | 4075.00 | 2.10 | 4682.91 | 271.96 |
PERIMETER_MID_ZN_4 | 2928711.94 | 0.00 | 2928711.94 | 138469.14 | 3067181.08 | 1787312.18 | 4049.34 | 4.66 | 4706.00 | 271.96 |
Total Facility | 72189357.04 | 0.00 | 72189357.04 | 4757990.76 | 76947347.81 | 67843644.98 | 6844.12 | 258.81 | 4789.95 | 1290.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6679 | 0.0000 | 0.6679 | 0.0000 | 0.6679 | 0.4247 | 3369.08 | 32.55 | 2541.37 |
CORE_MID | 0.5007 | 0.0000 | 0.5007 | 0.0000 | 0.5007 | 0.4247 | 3884.66 | 28.11 | 2030.23 |
CORE_TOP | 0.4879 | 0.0000 | 0.4879 | 0.0000 | 0.4879 | 0.4247 | 3926.20 | 21.30 | 1995.51 |
PERIMETER_TOP_ZN_3 | 0.1223 | 0.0000 | 0.1223 | 0.0061 | 0.1283 | 0.0895 | 3022.28 | 48.68 | 2872.04 |
PERIMETER_TOP_ZN_2 | 0.1368 | 0.0000 | 0.1368 | 0.0040 | 0.1408 | 0.0567 | 1311.49 | 1.11 | 4630.40 |
PERIMETER_TOP_ZN_1 | 0.1969 | 0.0000 | 0.1969 | 0.0061 | 0.2030 | 0.0895 | 1328.68 | 3.22 | 4611.10 |
PERIMETER_TOP_ZN_4 | 0.1384 | 0.0000 | 0.1384 | 0.0040 | 0.1424 | 0.0567 | 1308.23 | 2.00 | 4632.77 |
PERIMETER_BOT_ZN_3 | 0.1058 | 0.0000 | 0.1058 | 0.0032 | 0.1090 | 0.0895 | 3304.51 | 52.47 | 2586.03 |
PERIMETER_BOT_ZN_2 | 0.1132 | 0.0000 | 0.1132 | 0.0021 | 0.1153 | 0.0567 | 1351.01 | 7.42 | 4584.57 |
PERIMETER_BOT_ZN_1 | 0.1607 | 0.0000 | 0.1607 | 0.1337 | 0.2944 | 0.0895 | 1440.48 | 53.44 | 4449.09 |
PERIMETER_BOT_ZN_4 | 0.1112 | 0.0000 | 0.1112 | 0.0021 | 0.1133 | 0.0567 | 1345.93 | 8.76 | 4588.31 |
PERIMETER_MID_ZN_3 | 0.1213 | 0.0000 | 0.1213 | 0.0050 | 0.1263 | 0.0895 | 3283.30 | 51.13 | 2608.57 |
PERIMETER_MID_ZN_2 | 0.1279 | 0.0000 | 0.1279 | 0.0035 | 0.1314 | 0.0567 | 1279.37 | 1.18 | 3753.46 |
PERIMETER_MID_ZN_1 | 0.1945 | 0.0000 | 0.1945 | 0.0050 | 0.1996 | 0.0895 | 1302.58 | 2.10 | 4638.32 |
PERIMETER_MID_ZN_4 | 0.1346 | 0.0000 | 0.1346 | 0.0034 | 0.1380 | 0.0567 | 1277.30 | 4.66 | 4661.03 |
Total Facility | 3.3201 | 0.0000 | 3.3201 | 0.1784 | 3.4985 | 2.1513 | 4055.49 | 257.84 | 4724.23 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33455394.04 | 0.00 | 33455394.04 | 22614548.33 | 4094.50 | 2.10 | 4663.40 | 248.75 |
PACU_VAV_MID | 31452947.28 | 0.00 | 31452947.28 | 22614548.33 | 4064.43 | 1.87 | 4693.69 | 271.83 |
PACU_VAV_TOP | 31214856.14 | 0.00 | 31214856.14 | 22614548.33 | 4086.28 | 1.61 | 4672.11 | 80.45 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5430 | 0.0000 | 1.5430 | 0.7171 | 1322.72 | 2.10 | 4618.18 |
PACU_VAV_MID | 1.4499 | 0.0000 | 1.4499 | 0.7171 | 1292.33 | 1.87 | 4648.80 |
PACU_VAV_TOP | 1.4412 | 0.0000 | 1.4412 | 0.7171 | 1316.94 | 1.61 | 4624.45 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 1.75 | 2769.09 | 0.00 | 0.00 | 0.00 | 2299.20 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 1.50 | 2664.34 | 0.00 | 0.00 | 0.00 | 2455.98 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.50 | 2400.43 | 0.00 | 0.00 | 0.00 | 2460.78 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 12.0596 | 2.6657 | 0.0000 | 0.0000 | 0.0000 | 1.0615 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 9.8264 | 2.5048 | 0.0000 | 0.0000 | 0.0000 | 1.0655 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.5655 | 0.0000 | 0.0000 | 0.0000 | 1.0617 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 988 |
Defaulted Fields | 577 |
Fields with Defaults | 2480 |
Autosized Fields | 196 |
Autosizable Fields | 253 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
Electricity:Building | 1021.29 | 13465.67 | 16-APR-17:20 | 74341.76 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1021.29 | 13465.67 | 16-APR-17:20 | 74341.76 | 02-JAN-08:10 |
InteriorLights:Electricity | 301.60 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.60 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 301.60 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.60 | 987.92 | 16-APR-17:20 | 32642.50 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.20 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.86 | 36.00 | 01-JAN-10:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.86 | 36.00 | 01-JAN-10:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.96 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 33.00 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.67 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.67 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.17 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 36.00 | 01-JAN-10:30 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.84 | 36.00 | 01-JAN-10:30 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.95 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.99 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.66 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.93 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.53 | 22.79 | 01-JAN-10:30 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.53 | 22.79 | 01-JAN-10:30 | 859.95 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.20 | 422.10 | 02-APR-17:10 | 2793.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.86 | 36.00 | 01-JAN-10:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.86 | 36.00 | 01-JAN-10:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.96 | 267.21 | 16-APR-17:10 | 1768.58 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-08:40 | 860.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 33.00 | 422.10 | 12-MAR-17:10 | 2793.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.67 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.67 | 36.00 | 01-JAN-08:40 | 1358.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.94 | 267.21 | 12-MAR-17:10 | 1768.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.54 | 22.79 | 01-JAN-10:40 | 859.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 261.75 | 368.59 | 07-MAY-17:30 | 112335.86 | 05-JUL-11:40 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
ElectricityPurchased:Facility | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
ElectricityPurchased:Plant | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
Cogeneration:ElectricityPurchased | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
ElectricityNet:Plant | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
Cogeneration:ElectricityNet | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
General:Cogeneration:ElectricityNet | 1402.02 | 13834.26 | 07-MAY-17:30 | 184798.47 | 05-JUL-11:00 |
Fans:Electricity | 101.67 | 0.00 | 01-JAN-00:40 | 35833.37 | 05-JUL-10:40 |
General:Fans:Electricity | 101.67 | 0.00 | 01-JAN-00:40 | 35833.37 | 05-JUL-10:40 |
ExteriorLights:Electricity | 51.80 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.80 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
HeatRecovery:Electricity | 23.82 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-08:50 |
General:HeatRecovery:Electricity | 23.82 | 0.00 | 01-JAN-00:10 | 2722.67 | 02-JAN-08:50 |
Cooling:Electricity | 109.36 | 0.00 | 01-JAN-00:10 | 75165.20 | 05-JUL-11:50 |
General:Cooling:Electricity | 109.36 | 0.00 | 01-JAN-00:10 | 75165.20 | 05-JUL-11:50 |
Electricity:Plant | 67.19 | 0.00 | 01-JAN-00:40 | 8647.99 | 04-JAN-12:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 63.33 | 0.00 | 01-JAN-00:10 | 7751.02 | 27-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 63.33 | 0.00 | 01-JAN-00:10 | 7751.02 | 27-FEB-13:00 |
Pumps:Electricity | 3.86 | 0.00 | 01-JAN-00:40 | 1223.81 | 09-JAN-07:50 |
General:Pumps:Electricity | 3.86 | 0.00 | 01-JAN-00:40 | 1223.81 | 09-JAN-07:50 |
WIRED_LTG_ELECTRICITY | 8.47 | 0.00 | 01-JAN-00:10 | 917.25 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 646.31 | 0.00 | 01-JAN-00:40 | 371219.92 | 09-JAN-07:50 |
NaturalGas:Plant | 646.31 | 0.00 | 01-JAN-00:40 | 371219.92 | 09-JAN-07:50 |
Heating:NaturalGas | 646.31 | 0.00 | 01-JAN-00:40 | 371219.92 | 09-JAN-07:50 |
Boiler:Heating:NaturalGas | 646.31 | 0.00 | 01-JAN-00:40 | 371219.92 | 09-JAN-07:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3046.82 | 0.00 | 01-JAN-00:40 | 752186.81 | 09-JAN-07:20 |
EnergyTransfer:Building | 1217.99 | 0.00 | 01-JAN-00:40 | 175838.56 | 24-JUL-15:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 203.53 | 0.00 | 01-JAN-00:40 | 25432.46 | 05-JUL-15:10 |
Heating:EnergyTransfer | 342.48 | 0.00 | 01-JAN-00:40 | 173955.04 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 9519.78 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 342.48 | 0.00 | 01-JAN-00:40 | 173955.04 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 9519.78 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 875.51 | 0.00 | 01-JAN-00:40 | 175838.56 | 24-JUL-15:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 203.16 | 0.00 | 01-JAN-00:40 | 25432.46 | 05-JUL-15:10 |
General:Cooling:EnergyTransfer | 875.51 | 0.00 | 01-JAN-00:40 | 175838.56 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 203.16 | 0.00 | 01-JAN-00:40 | 25432.46 | 05-JUL-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 68.39 | 0.00 | 01-JAN-00:40 | 17429.81 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.32 | 0.00 | 01-JAN-00:40 | 17429.81 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.32 | 0.00 | 01-JAN-00:40 | 17429.81 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 22.07 | 0.00 | 01-JAN-00:10 | 10964.40 | 30-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 22.07 | 0.00 | 01-JAN-00:10 | 10964.40 | 30-JUN-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 33.51 | 0.00 | 01-JAN-00:40 | 11194.55 | 26-DEC-08:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 19.04 | 0.00 | 01-JAN-00:40 | 11194.55 | 26-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 19.04 | 0.00 | 01-JAN-00:40 | 11194.55 | 26-DEC-08:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.47 | 0.00 | 01-JAN-00:10 | 5786.25 | 24-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.47 | 0.00 | 01-JAN-00:10 | 5786.25 | 24-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 31.29 | 0.00 | 01-JAN-00:40 | 8897.31 | 02-JAN-08:50 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.65 | 0.00 | 01-JAN-00:40 | 8897.31 | 02-JAN-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 12.65 | 0.00 | 01-JAN-00:40 | 8897.31 | 02-JAN-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.64 | 0.00 | 01-JAN-00:10 | 6049.79 | 24-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.64 | 0.00 | 01-JAN-00:10 | 6049.79 | 24-JUL-15:30 |
EnergyTransfer:Zone:CORE_MID | 137.91 | 0.00 | 01-JAN-00:40 | 19358.13 | 24-JUL-09:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 4.25 | 0.00 | 01-JAN-00:40 | 18055.39 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 4.25 | 0.00 | 01-JAN-00:40 | 18055.39 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 133.66 | 0.00 | 01-JAN-00:20 | 19358.13 | 24-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 133.66 | 0.00 | 01-JAN-00:20 | 19358.13 | 24-JUL-09:20 |
EnergyTransfer:Zone:CORE_TOP | 136.65 | 0.00 | 01-JAN-00:40 | 25102.46 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 19.33 | 0.00 | 01-JAN-00:40 | 25102.46 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 19.33 | 0.00 | 01-JAN-00:40 | 25102.46 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 117.31 | 0.00 | 01-JAN-00:20 | 20768.58 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 117.31 | 0.00 | 01-JAN-00:20 | 20768.58 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 57.99 | 0.00 | 01-JAN-00:40 | 10045.72 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.68 | 0.00 | 01-JAN-00:40 | 10045.72 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.68 | 0.00 | 01-JAN-00:40 | 10045.72 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.31 | 0.00 | 01-JAN-00:10 | 7303.41 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.31 | 0.00 | 01-JAN-00:10 | 7303.41 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.64 | 0.00 | 01-JAN-00:40 | 10536.81 | 24-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.27 | 0.00 | 01-JAN-00:40 | 9071.25 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.27 | 0.00 | 01-JAN-00:40 | 9071.25 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.37 | 0.00 | 01-JAN-00:10 | 10536.81 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.37 | 0.00 | 01-JAN-00:10 | 10536.81 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.94 | 0.00 | 01-JAN-00:40 | 15926.65 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.77 | 0.00 | 01-JAN-00:40 | 12986.01 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.77 | 0.00 | 01-JAN-00:40 | 12986.01 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.17 | 0.00 | 01-JAN-00:10 | 15926.65 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.17 | 0.00 | 01-JAN-00:10 | 15926.65 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.27 | 0.00 | 01-JAN-00:40 | 11123.02 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.44 | 0.00 | 01-JAN-00:40 | 9309.57 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.44 | 0.00 | 01-JAN-00:40 | 9309.57 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.83 | 0.00 | 01-JAN-00:10 | 11123.02 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 28.83 | 0.00 | 01-JAN-00:10 | 11123.02 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 44.32 | 0.00 | 01-JAN-00:40 | 7732.92 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.85 | 0.00 | 01-JAN-00:40 | 7732.92 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.85 | 0.00 | 01-JAN-00:40 | 7732.92 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.47 | 0.00 | 01-JAN-00:10 | 5418.90 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.47 | 0.00 | 01-JAN-00:10 | 5418.90 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.29 | 0.00 | 01-JAN-00:40 | 8260.70 | 24-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.77 | 0.00 | 01-JAN-00:40 | 6889.20 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 12.77 | 0.00 | 01-JAN-00:40 | 6889.20 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.52 | 0.00 | 01-JAN-00:10 | 8260.70 | 24-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.52 | 0.00 | 01-JAN-00:10 | 8260.70 | 24-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 70.82 | 0.00 | 01-JAN-00:40 | 16410.44 | 09-JAN-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.95 | 0.00 | 01-JAN-00:40 | 16410.44 | 09-JAN-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.95 | 0.00 | 01-JAN-00:40 | 16410.44 | 09-JAN-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.87 | 0.00 | 01-JAN-00:20 | 13829.58 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.87 | 0.00 | 01-JAN-00:20 | 13829.58 | 29-JUN-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.59 | 0.00 | 01-JAN-00:40 | 8397.30 | 24-JUL-17:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.45 | 0.00 | 01-JAN-00:40 | 6968.71 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.45 | 0.00 | 01-JAN-00:40 | 6968.71 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.14 | 0.00 | 01-JAN-00:10 | 8397.30 | 24-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 24.14 | 0.00 | 01-JAN-00:10 | 8397.30 | 24-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 46.29 | 0.00 | 01-JAN-00:40 | 8340.71 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.04 | 0.00 | 01-JAN-00:40 | 8340.71 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.04 | 0.00 | 01-JAN-00:40 | 8340.71 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.25 | 0.00 | 01-JAN-00:10 | 6794.67 | 29-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.25 | 0.00 | 01-JAN-00:10 | 6794.67 | 29-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 41.37 | 0.00 | 01-JAN-00:40 | 10548.21 | 24-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.39 | 0.00 | 01-JAN-00:40 | 7516.61 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 11.39 | 0.00 | 01-JAN-00:40 | 7516.61 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.98 | 0.00 | 01-JAN-00:10 | 10548.21 | 24-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.98 | 0.00 | 01-JAN-00:10 | 10548.21 | 24-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.08 | 0.00 | 01-JAN-00:40 | 15102.84 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.02 | 0.00 | 01-JAN-00:40 | 10761.55 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 12.02 | 0.00 | 01-JAN-00:40 | 10761.55 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.06 | 0.00 | 01-JAN-00:10 | 15102.84 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.06 | 0.00 | 01-JAN-00:10 | 15102.84 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 42.09 | 0.00 | 01-JAN-00:40 | 10643.21 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.88 | 0.00 | 01-JAN-00:40 | 7604.89 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 11.88 | 0.00 | 01-JAN-00:40 | 7604.89 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.20 | 0.00 | 01-JAN-00:10 | 10643.21 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.20 | 0.00 | 01-JAN-00:10 | 10643.21 | 30-JUN-17:00 |
PlantLoopHeatingDemand:Facility | 528.15 | 0.00 | 01-JAN-00:40 | 297585.78 | 09-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
EnergyTransfer:HVAC | 1304.59 | 0.00 | 01-JAN-00:40 | 363063.75 | 05-JUL-10:40 |
HeatingCoils:EnergyTransfer | 467.68 | 0.00 | 01-JAN-00:40 | 295130.23 | 09-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 467.68 | 0.00 | 01-JAN-00:40 | 295130.23 | 09-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 467.68 | 0.00 | 01-JAN-00:40 | 295130.23 | 09-JAN-08:00 |
HeatRecoveryForHeating:EnergyTransfer | 339.50 | 0.00 | 01-JAN-00:10 | 99560.46 | 28-JAN-07:50 |
HeatRecoveryForCooling:EnergyTransfer | 12.89 | 0.00 | 01-JAN-00:10 | 56305.78 | 15-JUL-14:00 |
CoolingCoils:EnergyTransfer | 484.53 | 0.00 | 01-JAN-00:10 | 363063.75 | 05-JUL-10:40 |
EnergyTransfer:Plant | 524.25 | 0.00 | 01-JAN-00:40 | 296507.77 | 09-JAN-07:50 |
WaterSystems:EnergyTransfer | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 60.47 | 0.00 | 01-JAN-00:10 | 7612.87 | 24-FEB-12:10 |
Boilers:EnergyTransfer | 463.77 | 0.00 | 01-JAN-00:40 | 294052.23 | 09-JAN-07:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.370 | -203.164 | 0.000 | 0.000 | 33.666 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -153.224 |
CORE_MID | 0.000 | 0.000 | 4.255 | -133.655 | 0.000 | 0.000 | 35.136 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -93.089 |
CORE_TOP | 0.000 | 0.000 | 19.332 | -117.313 | 0.000 | 0.000 | 35.798 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -125.170 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 33.677 | -24.314 | 0.000 | 0.000 | 7.690 | 8.864 | 24.333 | 18.963 | 0.000 | 0.018 | 0.000 | 0.000 | -45.612 | 0.000 | -5.355 | -18.263 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 19.271 | -28.370 | 0.000 | 0.000 | 4.834 | 5.553 | 15.404 | 37.267 | 0.000 | 0.012 | 0.001 | 0.000 | -28.246 | 0.000 | -3.602 | -22.123 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.767 | -47.174 | 0.000 | 0.000 | 7.519 | 8.671 | 24.332 | 79.320 | 0.000 | 0.017 | 0.000 | 0.000 | -40.980 | 0.000 | -5.509 | -48.964 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 20.439 | -28.831 | 0.000 | 0.000 | 4.886 | 5.538 | 15.403 | 37.936 | 0.000 | 0.012 | 0.001 | 0.000 | -29.264 | 0.000 | -3.611 | -22.508 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 23.850 | -20.471 | 0.000 | 0.000 | 7.685 | 8.837 | 24.333 | 19.330 | 0.000 | 0.012 | 0.000 | 0.000 | -46.221 | 0.000 | -2.908 | -14.445 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 12.770 | -24.521 | 0.000 | 0.000 | 4.804 | 5.542 | 15.404 | 37.443 | 0.000 | 0.007 | 0.000 | 0.000 | -29.005 | 0.000 | -1.977 | -20.467 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 38.953 | -31.869 | 0.000 | 0.000 | 7.796 | 8.656 | 24.332 | 80.296 | 0.000 | 0.685 | 0.001 | 0.000 | -41.837 | 0.000 | -55.405 | -31.607 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 13.452 | -24.141 | 0.000 | 0.000 | 4.841 | 5.527 | 15.403 | 38.143 | 0.000 | 0.006 | 0.000 | 0.000 | -30.041 | 0.000 | -1.984 | -21.207 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 20.043 | -26.250 | 0.000 | 0.000 | 7.612 | 8.864 | 24.333 | 18.670 | 0.000 | 0.016 | 0.000 | 0.000 | -47.252 | 0.000 | -4.605 | -1.430 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 11.391 | -29.981 | 0.000 | 0.000 | 3.553 | 5.553 | 15.404 | 37.053 | 0.000 | 0.011 | 0.000 | 0.000 | -29.223 | 0.000 | -3.090 | -10.669 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 12.015 | -50.062 | 0.000 | 0.000 | 7.424 | 8.671 | 24.332 | 78.933 | 0.000 | 0.014 | 0.001 | 0.000 | -42.569 | 0.000 | -4.750 | -34.009 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 11.883 | -30.204 | 0.000 | 0.000 | 4.835 | 5.538 | 15.403 | 37.739 | 0.000 | 0.010 | 0.000 | 0.000 | -30.303 | 0.000 | -3.103 | -11.800 |
TOPFLOOR_PLENUM | 46.324 | -22.071 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.016 | 0.000 | 0.000 | 0.000 | 0.000 | -8.162 | -16.107 |
MIDFLOOR_PLENUM | 19.043 | -14.470 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.021 | 3.229 | 0.000 | 0.000 | 0.000 | -7.823 | -0.001 |
FIRSTFLOOR_PLENUM | 12.649 | -18.645 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.016 | 12.253 | 0.000 | 0.000 | 0.000 | -6.273 | -0.000 |
Total Facility | 78.016 | -55.185 | 264.467 | -820.321 | 0.000 | 0.000 | 178.078 | 301.600 | 719.689 | 521.094 | 0.000 | 0.873 | 15.487 | 0.000 | -440.554 | 0.000 | -118.157 | -645.082 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 30-JUN-04:02 | 0.00 | 0.00 | 0.00 | -42734.97 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 36881.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-JUL-05:12 | 0.00 | 0.00 | 0.00 | -33234.42 | 0.00 | 0.00 | 331.38 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 29161.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 30-JUN-04:02 | 0.00 | 0.00 | 0.00 | -33846.78 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31192.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-16:12 | 0.00 | 0.00 | 0.00 | -10461.55 | 0.00 | 0.00 | 27.24 | 36.00 | 478.42 | 3187.65 | 0.00 | 50.96 | 6681.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:12 | 0.00 | 0.00 | 0.00 | -16177.23 | 0.00 | 0.00 | 12.36 | 22.79 | 302.86 | 13102.73 | 0.00 | 0.00 | 2778.40 | 0.00 | -0.00 | 0.00 | -41.90 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:22 | 0.00 | 0.00 | 0.00 | -20497.04 | 0.00 | 0.00 | 20.58 | 36.00 | 478.41 | 20138.89 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -131.66 | -45.18 |
PERIMETER_TOP_ZN_4 | 14-MAY-17:01 | 0.00 | 0.00 | 0.00 | -18976.29 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 15293.18 | 0.00 | 0.00 | 3555.14 | 0.00 | -0.00 | 0.00 | -139.23 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6631.09 | 0.00 | 0.00 | 147.74 | 216.00 | 637.89 | 2953.14 | 0.00 | 0.00 | 2688.05 | 0.00 | -0.00 | 0.00 | -11.73 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-AUG-09:11 | 0.00 | 0.00 | 0.00 | -13032.38 | 0.00 | 0.00 | 15.90 | 22.79 | 302.86 | 12280.60 | 0.00 | 0.00 | 474.45 | 0.00 | -0.00 | 0.00 | -64.22 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-13:21 | 0.00 | 0.00 | 0.00 | -16992.49 | 0.00 | 0.00 | 24.74 | 36.00 | 478.41 | 15394.72 | 0.00 | 0.00 | 1113.31 | 0.00 | -0.00 | 0.00 | -54.70 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-17:41 | 0.00 | 0.00 | 0.00 | -14663.84 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 8493.03 | 0.00 | 0.00 | 5963.21 | 0.00 | -0.00 | 0.00 | -59.61 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-16:41 | 0.00 | 0.00 | 0.00 | -10123.20 | 0.00 | 0.00 | 28.58 | 36.00 | 478.42 | 2462.10 | 0.00 | 21.91 | 7096.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:61 | 0.00 | 0.00 | 0.00 | -17733.63 | 0.00 | 0.00 | 12.52 | 22.79 | 302.86 | 13344.18 | 0.00 | 0.00 | 4105.65 | 0.00 | -0.00 | 0.00 | -54.36 | 0.00 |
PERIMETER_MID_ZN_1 | 22-OCT-13:51 | 0.00 | 0.00 | 0.00 | -21197.35 | 0.00 | 0.00 | 20.70 | 36.00 | 478.41 | 16864.52 | 0.00 | 0.00 | 3911.84 | 0.00 | -0.00 | 0.00 | -114.12 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-16:41 | 0.00 | 0.00 | 0.00 | -17696.77 | 0.00 | 0.00 | 11.81 | 22.79 | 302.86 | 9685.04 | 0.00 | 0.00 | 7682.39 | 0.00 | -0.00 | 0.00 | -8.11 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:30 | 0.00 | -10964.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 10899.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:15 | 0.00 | -6156.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6191.19 | 0.00 | -0.00 | 0.00 | -35.17 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:15 | 0.00 | -6390.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6417.09 | 0.00 | -0.00 | 0.00 | -27.05 | 0.00 |
Total Facility | 24-JUL-06:03 | 0.00 | -7673.57 | 0.00 | -169518.50 | 0.00 | 0.00 | 3536.12 | 8560.47 | 22496.85 | 37738.81 | 0.00 | 0.00 | 109227.64 | 0.00 | 0.00 | 0.00 | -4367.82 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 11707.62 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17561.41 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 19546.26 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22200.05 |
CORE_TOP | 02-JAN-00:02 | 0.00 | 0.00 | 27190.69 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29844.48 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 10851.98 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4746.48 | 0.00 | -618.32 | -6046.62 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 10686.55 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3161.89 | 0.00 | -414.42 | -7464.40 |
PERIMETER_TOP_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 14863.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4876.53 | 0.00 | -622.01 | -9924.15 |
PERIMETER_TOP_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 11251.05 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3241.87 | 0.00 | -414.54 | -7948.79 |
PERIMETER_BOT_ZN_3 | 01-JAN-22:02 | 0.00 | 0.00 | 8286.01 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3829.01 | 0.00 | -331.56 | -4556.17 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 8104.64 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3227.85 | 0.00 | -225.26 | -5005.67 |
PERIMETER_BOT_ZN_1 | 09-JAN-07:10 | 0.00 | 0.00 | 16895.21 | 0.00 | 0.00 | 0.00 | 222.64 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 21979.82 | 0.00 | -5031.29 | 0.00 | -35157.08 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 8473.71 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3296.43 | 0.00 | -225.34 | -5306.09 |
PERIMETER_MID_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 8983.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4848.84 | 0.00 | -525.02 | -4169.47 |
PERIMETER_MID_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 9188.83 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3229.30 | 0.00 | -351.58 | -5962.10 |
PERIMETER_MID_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 12292.60 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4978.53 | 0.00 | -527.88 | -7345.63 |
PERIMETER_MID_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 9381.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3306.98 | 0.00 | -351.48 | -6076.82 |
TOPFLOOR_PLENUM | 09-JAN-05:19 | 18765.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -956.29 | -17809.09 |
MIDFLOOR_PLENUM | 26-DEC-08:26 | 11388.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -120.73 | -11267.63 |
FIRSTFLOOR_PLENUM | 02-JAN-08:55 | 9067.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9067.25 |
Total Facility | 02-JAN-05:21 | 23777.10 | 0.00 | 172023.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33867.86 | 0.00 | -5465.75 | -173109.72 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9409 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.9804 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9198 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.2271 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5012 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9704 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4623 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.9902 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5471 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.1136 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6029 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8382 | 2.8382 | 0.7890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3170 | 2.3170 | 0.7785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3481 | 2.3481 | 0.8007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7130 | 0.7130 | 0.1690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9398 | 0.9398 | 0.1880 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2063 | 1.2063 | 0.2413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0199 | 1.0199 | 0.2040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5667 | 0.5667 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7555 | 0.7555 | 0.1511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9680 | 0.9680 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8124 | 0.8124 | 0.1625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6415 | 0.6415 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9338 | 0.9338 | 0.1868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1272 | 1.1272 | 0.2254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9608 | 0.9608 | 0.1922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9409 | 5.1754 | 5.9409 | 1.4623 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.9804 | 4.9198 | 5.9804 | 1.5471 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.2271 | 5.5012 | 6.2271 | 1.6029 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4191 | 1.4191 | 0.7890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1585 | 1.1585 | 0.7785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1740 | 1.1740 | 0.8007 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3565 | 0.3565 | 0.1690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4699 | 0.4699 | 0.1880 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6032 | 0.6032 | 0.2413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5100 | 0.5100 | 0.2040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2834 | 0.2834 | 0.1661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3778 | 0.3778 | 0.1511 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4840 | 0.4840 | 0.1936 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4062 | 0.4062 | 0.1625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3207 | 0.3207 | 0.1642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4669 | 0.4669 | 0.1868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5636 | 0.5636 | 0.2254 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4804 | 0.4804 | 0.1922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9704 | 1.4623 | 1.4623 | 1.4623 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.9902 | 1.5471 | 1.5471 | 1.5471 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.1136 | 1.6029 | 1.6029 | 1.6029 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 707.50 |
Number of hours cooling loads not met | 85.67 |
Number of hours not met | 793.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 646.31 | 371219.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 109.36 | 75165.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.60 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.80 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 101.67 | 35833.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 3.86 | 1223.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 23.82 | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 63.33 | 7751.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1402.02 |
Natural Gas | 0.00 | 646.31 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2048.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.54 |
Space Heating | 0.00 |
Space Cooling | 21.95 |
Fans (All) | 20.41 |
Service Water Heating | 12.71 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 281.41 |
Subtotal | 281.41 |
Natural Gas [MJ/m2] | |
Space Heating | 129.72 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 129.72 |
Subtotal | 129.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.72 |
Space Heating | 31.55 |
Space Cooling | 5.34 |
Fans (All) | 4.96 |
Service Water Heating | 3.09 |
Receptacle Equipment | 35.14 |
Miscellaneous | 5.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8595.17 | 164.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8698.17 | 61.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8707.83 | 52.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8715.17 | 44.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8696.17 | 63.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8595.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 164.83 | 0.00 | 0.00 | 0.00 |
Average | 8725.14 | 34.86 | 0.00 | 0.00 | 0.00 |
Sum | 157052.50 | 627.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128228.67 | 75.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 75.33 | 0.00 | 0.00 | 0.00 |
Average | 34139.15 | 4.19 | 0.00 | 0.00 | 0.00 |
Sum | 614504.67 | 75.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8189.00 | 571.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8428.50 | 331.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8522.17 | 237.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8506.50 | 253.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8517.50 | 242.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8494.17 | 265.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8473.00 | 287.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8586.00 | 174.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8478.33 | 281.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8438.33 | 321.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8437.00 | 323.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8465.17 | 294.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8481.67 | 278.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8433.50 | 326.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8419.50 | 340.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8294.17 | 465.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8475.00 | 285.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8446.83 | 313.17 | 0.00 | 0.00 | 0.00 |
Min | 8189.00 | 174.00 | 0.00 | 0.00 | 0.00 |
Max | 8586.00 | 571.00 | 0.00 | 0.00 | 0.00 |
Average | 8449.24 | 310.76 | 0.00 | 0.00 | 0.00 |
Sum | 152086.33 | 5593.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127864.83 | 439.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128079.50 | 224.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128128.50 | 175.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24883.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24900.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24888.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14009.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24723.00 | 186.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14009.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24879.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10131.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24888.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14010.50 | 5.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128128.50 | 439.17 | 0.00 | 0.00 | 0.00 |
Average | 34078.81 | 64.53 | 0.00 | 0.00 | 0.00 |
Sum | 613418.50 | 1161.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870293E+10 | 7962.02 | 06-JAN-08:53 | -35.6 | -35.7 | 0.164752E+10 | 2517.99 | 27-JAN-16:40 | -15.9 | -16.8 |
February | 0.892430E+10 | 9795.74 | 08-FEB-17:00 | 3.30 | -1.3 | 0.162981E+10 | 2595.87 | 09-FEB-14:00 | -8.3 | -9.6 |
March | 0.117016E+11 | 14627.18 | 31-MAR-16:00 | 8.90 | 3.77 | 0.204875E+10 | 2606.64 | 24-MAR-09:20 | 8.90 | 3.77 |
April | 0.145667E+11 | 25003.46 | 19-APR-05:03 | 0.60 | -1.3 | 0.190168E+10 | 2606.65 | 07-APR-09:09 | 0.60 | -1.3 |
May | 0.223615E+11 | 41569.07 | 30-MAY-05:12 | 10.60 | 8.25 | 0.207837E+10 | 2606.73 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.251444E+11 | 42744.78 | 30-JUN-04:02 | 26.10 | 22.87 | 0.207179E+10 | 2606.67 | 06-JUN-09:09 | 26.10 | 22.87 |
July | 0.264152E+11 | 41763.45 | 31-JUL-05:12 | 14.97 | 13.44 | 0.192907E+10 | 2760.67 | 05-JUL-10:00 | 14.97 | 13.44 |
August | 0.274437E+11 | 40103.10 | 26-AUG-05:12 | 16.10 | 14.74 | 0.216154E+10 | 2606.69 | 03-AUG-13:00 | 16.10 | 14.74 |
September | 0.219651E+11 | 40621.72 | 05-SEP-05:12 | 5.60 | 5.31 | 0.191879E+10 | 2606.67 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.159328E+11 | 36591.77 | 23-OCT-06:01 | 5.60 | 4.30 | 0.198412E+10 | 2606.66 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.105866E+11 | 14137.26 | 17-NOV-16:20 | 8.90 | 2.59 | 0.189853E+10 | 2606.84 | 15-NOV-10:09 | 8.90 | 2.59 |
December | 0.941919E+10 | 9284.45 | 01-DEC-15:20 | -18.1 | -18.9 | 0.165779E+10 | 2583.30 | 01-DEC-14:00 | -18.1 | -18.9 |
Annual Sum or Average | 0.203164E+12 | 0.229278E+11 | ||||||||
Minimum of Months | 0.870293E+10 | 7962.02 | -35.6 | -35.7 | 0.162981E+10 | 2517.99 | -18.1 | -18.9 | ||
Maximum of Months | 0.274437E+11 | 42744.78 | 26.10 | 22.87 | 0.216154E+10 | 2760.67 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 1608523.15 | 675.40 | 04-FEB-17:25 | 6.10 | 1.54 | 0.00 | 0.00 | 01-FEB-00:10 | 6.10 | 1.54 |
March | 0.119895E+09 | 1780.28 | 31-MAR-16:10 | 8.90 | 3.69 | 0.00 | 0.00 | 01-MAR-00:10 | 8.90 | 3.69 |
April | 0.103711E+10 | 5043.98 | 13-APR-14:50 | 19.82 | 7.99 | 0.00 | 0.00 | 01-APR-00:10 | 19.82 | 7.99 |
May | 0.345667E+10 | 9653.46 | 18-MAY-14:10 | 28.57 | 16.73 | 0.00 | 0.00 | 01-MAY-00:10 | 28.57 | 16.73 |
June | 0.506124E+10 | 10964.40 | 30-JUN-14:30 | 31.65 | 24.14 | 0.00 | 0.00 | 01-JUN-00:10 | 31.65 | 24.14 |
July | 0.586016E+10 | 10449.22 | 24-JUL-14:30 | 29.40 | 19.57 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.57 |
August | 0.427349E+10 | 9531.51 | 08-AUG-15:00 | 30.60 | 23.36 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.36 |
September | 0.184857E+10 | 8193.56 | 01-SEP-15:40 | 26.10 | 17.70 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.70 |
October | 0.398193E+09 | 3687.53 | 20-OCT-14:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 14331846.88 | 1082.90 | 01-NOV-16:30 | 17.25 | 13.03 | 0.00 | 0.00 | 01-NOV-00:10 | 17.25 | 13.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.220713E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.00 | 0.00 | -21.9 | -22.1 | ||
Maximum of Months | 0.586016E+10 | 10964.40 | 31.65 | 24.14 | 0.00 | 0.00 | 31.65 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40413517.69 | 3918.09 | 26-JAN-05:01 | -31.0 | -31.1 | 0.00 | 0.00 | 01-JAN-00:10 | -31.0 | -31.1 |
February | 20781778.60 | 4296.63 | 25-FEB-05:01 | -29.0 | -29.1 | 0.00 | 0.00 | 01-FEB-00:10 | -29.0 | -29.1 |
March | 69285592.71 | 3578.95 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.466027E+09 | 2968.21 | 26-APR-06:02 | 1.10 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 1.10 | 0.37 |
May | 0.201762E+10 | 4362.27 | 18-MAY-16:00 | 28.50 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.32 |
June | 0.321836E+10 | 5338.31 | 30-JUN-15:50 | 31.78 | 24.63 | 0.00 | 0.00 | 01-JUN-00:10 | 31.78 | 24.63 |
July | 0.388438E+10 | 6156.66 | 24-JUL-06:15 | 19.07 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 19.07 | 17.12 |
August | 0.304247E+10 | 4496.67 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.134472E+10 | 4349.33 | 01-SEP-15:50 | 26.10 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.67 |
October | 0.310604E+09 | 3009.48 | 25-OCT-06:01 | -4.2 | -4.4 | 0.00 | 0.00 | 01-OCT-00:10 | -4.2 | -4.4 |
November | 25836896.65 | 3077.04 | 29-NOV-05:02 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 29186103.31 | 3838.05 | 02-DEC-05:01 | -27.3 | -27.5 | 0.00 | 0.00 | 01-DEC-00:10 | -27.3 | -27.5 |
Annual Sum or Average | 0.144697E+11 | 0.00 | ||||||||
Minimum of Months | 20781778.60 | 2968.21 | -31.0 | -31.1 | 0.00 | 0.00 | -31.0 | -31.1 | ||
Maximum of Months | 0.388438E+10 | 6156.66 | 31.78 | 24.63 | 0.00 | 0.00 | 31.78 | 24.63 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147680E+09 | 3875.46 | 26-JAN-07:10 | -33.1 | -33.2 | 0.00 | 0.00 | 01-JAN-00:10 | -33.1 | -33.2 |
February | 0.149390E+09 | 3893.49 | 25-FEB-05:01 | -29.0 | -29.1 | 0.00 | 0.00 | 01-FEB-00:10 | -29.0 | -29.1 |
March | 0.249157E+09 | 3764.64 | 16-MAR-04:01 | -26.3 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.5 |
April | 0.795840E+09 | 3591.09 | 05-APR-05:01 | -13.4 | -13.9 | 0.00 | 0.00 | 01-APR-00:10 | -13.4 | -13.9 |
May | 0.248512E+10 | 4462.22 | 18-MAY-16:00 | 28.50 | 16.32 | 0.00 | 0.00 | 01-MAY-00:10 | 28.50 | 16.32 |
June | 0.359210E+10 | 5433.00 | 30-JUN-15:10 | 32.12 | 24.53 | 0.00 | 0.00 | 01-JUN-00:10 | 32.12 | 24.53 |
July | 0.443450E+10 | 6390.39 | 24-JUL-06:15 | 19.07 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 19.07 | 17.12 |
August | 0.384534E+10 | 5056.47 | 08-AUG-16:00 | 30.60 | 22.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 22.99 |
September | 0.210330E+10 | 4639.24 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.614050E+09 | 2777.72 | 06-OCT-06:01 | -3.6 | -4.0 | 0.00 | 0.00 | 01-OCT-00:10 | -3.6 | -4.0 |
November | 0.105917E+09 | 2149.69 | 29-NOV-05:02 | -19.6 | -19.9 | 0.00 | 0.00 | 01-NOV-00:10 | -19.6 | -19.9 |
December | 0.122582E+09 | 3654.76 | 01-DEC-17:10 | -19.9 | -20.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.9 | -20.4 |
Annual Sum or Average | 0.186450E+11 | 0.00 | ||||||||
Minimum of Months | 0.105917E+09 | 2149.69 | -33.1 | -33.2 | 0.00 | 0.00 | -33.1 | -33.2 | ||
Maximum of Months | 0.443450E+10 | 6390.39 | 32.12 | 24.53 | 0.00 | 0.00 | 32.12 | 24.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411404E+10 | 6221.03 | 27-JAN-16:30 | -15.6 | -16.5 | 0.148993E+10 | 2195.43 | 27-JAN-14:00 | -15.6 | -16.5 |
February | 0.523584E+10 | 6728.42 | 08-FEB-17:00 | 3.30 | -1.3 | 0.140368E+10 | 2301.29 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.801454E+10 | 7627.11 | 29-MAR-16:00 | 5.00 | 1.34 | 0.179135E+10 | 2551.59 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.997243E+10 | 12526.72 | 14-APR-16:00 | 15.00 | 6.77 | 0.177325E+10 | 2606.62 | 18-APR-09:09 | 17.88 | 10.72 |
May | 0.155845E+11 | 32597.06 | 30-MAY-05:12 | 10.60 | 8.25 | 0.205542E+10 | 2606.71 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.179839E+11 | 30651.52 | 30-JUN-04:02 | 26.10 | 22.87 | 0.206277E+10 | 2606.65 | 06-JUN-09:09 | 26.10 | 22.87 |
July | 0.189458E+11 | 33240.73 | 31-JUL-05:12 | 14.97 | 13.44 | 0.192232E+10 | 2690.50 | 05-JUL-10:00 | 14.97 | 13.44 |
August | 0.188442E+11 | 30180.95 | 28-AUG-06:02 | 14.08 | 13.35 | 0.215327E+10 | 2606.66 | 10-AUG-13:00 | 14.08 | 13.35 |
September | 0.138434E+11 | 29655.53 | 05-SEP-06:01 | 6.05 | 5.72 | 0.189579E+10 | 2606.66 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.979902E+10 | 12798.34 | 20-OCT-16:00 | 18.30 | 9.93 | 0.183570E+10 | 2606.62 | 02-OCT-09:09 | 18.30 | 9.93 |
November | 0.666092E+10 | 7324.24 | 17-NOV-16:20 | 8.90 | 2.59 | 0.162231E+10 | 2485.54 | 17-NOV-14:00 | 8.90 | 2.59 |
December | 0.465637E+10 | 6263.29 | 01-DEC-16:00 | -18.7 | -19.4 | 0.145257E+10 | 2248.47 | 01-DEC-14:00 | -18.7 | -19.4 |
Annual Sum or Average | 0.133655E+12 | 0.214584E+11 | ||||||||
Minimum of Months | 0.411404E+10 | 6221.03 | -18.7 | -19.4 | 0.140368E+10 | 2195.43 | -18.7 | -19.4 | ||
Maximum of Months | 0.189458E+11 | 33240.73 | 26.10 | 22.87 | 0.215327E+10 | 2690.50 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240529E+10 | 5893.69 | 27-JAN-16:20 | -15.2 | -16.2 | 0.145768E+10 | 2076.12 | 27-JAN-14:00 | -15.2 | -16.2 |
February | 0.337500E+10 | 6698.65 | 08-FEB-17:00 | 3.30 | -1.3 | 0.134767E+10 | 2250.47 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.589840E+10 | 7557.59 | 29-MAR-16:00 | 5.00 | 1.34 | 0.168919E+10 | 2468.06 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.883030E+10 | 12304.61 | 13-APR-16:00 | 20.00 | 8.11 | 0.168516E+10 | 2606.60 | 19-APR-13:50 | 6.60 | 0.79 |
May | 0.148861E+11 | 18469.49 | 18-MAY-15:40 | 28.63 | 16.41 | 0.202837E+10 | 2606.72 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.178085E+11 | 33852.44 | 30-JUN-04:02 | 26.10 | 22.87 | 0.205345E+10 | 2606.67 | 26-JUN-13:09 | 26.10 | 22.87 |
July | 0.186699E+11 | 28459.66 | 24-JUL-06:03 | 18.68 | 16.82 | 0.191593E+10 | 2645.81 | 05-JUL-10:00 | 18.68 | 16.82 |
August | 0.178265E+11 | 18557.13 | 08-AUG-15:50 | 30.60 | 23.05 | 0.214255E+10 | 2606.65 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.122343E+11 | 18026.04 | 01-SEP-15:50 | 26.10 | 17.67 | 0.184549E+10 | 2606.62 | 11-SEP-13:20 | 18.90 | 14.42 |
October | 0.808446E+10 | 12052.48 | 20-OCT-16:00 | 18.30 | 9.93 | 0.169878E+10 | 2606.49 | 20-OCT-13:00 | 18.30 | 9.93 |
November | 0.479734E+10 | 7060.12 | 17-NOV-16:20 | 8.90 | 2.59 | 0.152482E+10 | 2366.08 | 17-NOV-14:00 | 8.90 | 2.59 |
December | 0.249741E+10 | 5750.88 | 28-DEC-15:50 | -2.0 | -3.9 | 0.140720E+10 | 2078.07 | 28-DEC-14:00 | -2.0 | -3.9 |
Annual Sum or Average | 0.117314E+12 | 0.207963E+11 | ||||||||
Minimum of Months | 0.240529E+10 | 5750.88 | -15.2 | -16.2 | 0.134767E+10 | 2076.12 | -15.2 | -16.2 | ||
Maximum of Months | 0.186699E+11 | 33852.44 | 30.60 | 23.05 | 0.214255E+10 | 2645.81 | 26.10 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7493342.78 | 983.05 | 28-JAN-17:02 | -7.8 | -9.1 | 0.299527E+09 | 406.82 | 05-JAN-14:09 | -7.8 | -9.1 |
February | 50355460.27 | 1086.56 | 08-FEB-15:00 | 5.00 | -0.5 | 0.275191E+09 | 410.69 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.316213E+09 | 1402.53 | 31-MAR-16:00 | 8.90 | 3.77 | 0.336074E+09 | 472.74 | 28-MAR-13:00 | 8.90 | 3.77 |
April | 0.126958E+10 | 3014.07 | 18-APR-15:20 | 13.90 | 7.83 | 0.329746E+09 | 549.48 | 18-APR-13:00 | 13.90 | 7.83 |
May | 0.371833E+10 | 5936.28 | 18-MAY-14:50 | 28.83 | 16.63 | 0.419636E+09 | 549.51 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.518469E+10 | 8209.61 | 29-JUN-06:03 | 23.17 | 19.92 | 0.432577E+09 | 549.51 | 26-JUN-13:09 | 23.17 | 19.92 |
July | 0.553280E+10 | 10462.95 | 23-JUL-16:12 | 29.43 | 22.47 | 0.404118E+09 | 565.84 | 05-JUL-10:00 | 29.43 | 22.47 |
August | 0.451131E+10 | 6142.34 | 08-AUG-15:30 | 30.60 | 23.17 | 0.448457E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.245626E+10 | 5133.18 | 01-SEP-15:40 | 26.10 | 17.70 | 0.372156E+09 | 549.49 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.104281E+10 | 2004.18 | 20-OCT-15:20 | 18.70 | 10.02 | 0.328599E+09 | 549.07 | 20-OCT-13:00 | 18.70 | 10.02 |
November | 0.215653E+09 | 1382.27 | 01-NOV-15:50 | 17.88 | 13.29 | 0.303849E+09 | 471.30 | 01-NOV-13:00 | 17.88 | 13.29 |
December | 8756953.37 | 989.67 | 30-DEC-17:02 | -3.3 | -3.3 | 0.290826E+09 | 406.83 | 18-DEC-14:30 | -3.3 | -3.3 |
Annual Sum or Average | 0.243143E+11 | 0.424076E+10 | ||||||||
Minimum of Months | 7493342.78 | 983.05 | -7.8 | -9.1 | 0.275191E+09 | 406.82 | -7.8 | -9.1 | ||
Maximum of Months | 0.553280E+10 | 10462.95 | 30.60 | 23.17 | 0.448457E+09 | 565.84 | 29.43 | 22.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9820202.32 | 1080.25 | 21-JAN-17:02 | -5.0 | -7.1 | 0.192325E+09 | 257.56 | 05-JAN-14:09 | -5.0 | -7.1 |
February | 0.171962E+09 | 1501.31 | 28-FEB-10:25 | -4.4 | -6.4 | 0.175892E+09 | 299.56 | 28-FEB-10:30 | -4.4 | -6.4 |
March | 0.696330E+09 | 2967.25 | 31-MAR-09:35 | 1.13 | -1.2 | 0.222631E+09 | 347.88 | 20-MAR-09:00 | 1.13 | -1.2 |
April | 0.216531E+10 | 7115.88 | 18-APR-09:20 | 17.97 | 10.84 | 0.226197E+09 | 347.88 | 18-APR-09:39 | 18.13 | 11.06 |
May | 0.421899E+10 | 15412.51 | 21-MAY-09:52 | 14.10 | 8.39 | 0.269284E+09 | 347.90 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.566817E+10 | 16184.54 | 25-JUN-08:12 | 24.27 | 20.87 | 0.273642E+09 | 348.38 | 27-JUN-09:30 | 25.55 | 19.23 |
July | 0.611214E+10 | 16068.35 | 23-JUL-09:32 | 26.13 | 22.79 | 0.255739E+09 | 348.60 | 24-JUL-09:00 | 26.10 | 19.03 |
August | 0.481182E+10 | 13282.84 | 06-AUG-08:52 | 18.30 | 14.00 | 0.281442E+09 | 347.89 | 04-AUG-09:50 | 18.30 | 14.00 |
September | 0.302264E+10 | 8721.97 | 01-SEP-09:00 | 20.00 | 17.77 | 0.234052E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.116678E+10 | 4229.01 | 19-OCT-09:30 | 12.50 | 9.01 | 0.209215E+09 | 347.88 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.308063E+09 | 1513.44 | 16-NOV-09:55 | 1.70 | -0.5 | 0.193067E+09 | 300.26 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 17861767.93 | 1083.70 | 30-DEC-17:02 | -3.3 | -3.3 | 0.185710E+09 | 257.56 | 11-DEC-14:39 | -3.3 | -3.3 |
Annual Sum or Average | 0.283699E+11 | 0.271920E+10 | ||||||||
Minimum of Months | 9820202.32 | 1080.25 | -5.0 | -7.1 | 0.175892E+09 | 257.56 | -5.0 | -7.1 | ||
Maximum of Months | 0.611214E+10 | 16184.54 | 26.13 | 22.79 | 0.281442E+09 | 348.60 | 26.10 | 19.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816703E+09 | 6902.52 | 27-JAN-13:50 | -14.6 | -15.8 | 0.324080E+09 | 549.49 | 26-JAN-14:00 | -14.6 | -15.8 |
February | 0.150596E+10 | 9964.84 | 28-FEB-13:50 | 3.62 | -0.3 | 0.307942E+09 | 549.50 | 27-FEB-14:00 | 3.62 | -0.3 |
March | 0.206521E+10 | 10560.30 | 31-MAR-13:50 | 8.03 | 2.94 | 0.374158E+09 | 549.50 | 20-MAR-13:00 | 8.03 | 2.94 |
April | 0.378514E+10 | 18223.84 | 23-APR-14:02 | 24.60 | 16.15 | 0.355536E+09 | 550.10 | 04-APR-13:20 | 24.60 | 16.15 |
May | 0.604817E+10 | 18943.19 | 21-MAY-14:32 | 22.23 | 11.38 | 0.419591E+09 | 550.27 | 17-MAY-13:50 | 22.23 | 11.38 |
June | 0.698914E+10 | 16339.73 | 25-JUN-11:32 | 27.07 | 21.57 | 0.428460E+09 | 550.10 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.791545E+10 | 20112.67 | 23-JUL-12:52 | 30.00 | 22.84 | 0.401916E+09 | 567.00 | 05-JUL-13:09 | 30.00 | 22.84 |
August | 0.763911E+10 | 20377.01 | 27-AUG-14:12 | 22.57 | 18.07 | 0.445332E+09 | 549.99 | 25-AUG-13:00 | 22.57 | 18.07 |
September | 0.558574E+10 | 20330.53 | 04-SEP-12:32 | 15.93 | 9.56 | 0.375076E+09 | 550.30 | 07-SEP-13:50 | 23.90 | 14.43 |
October | 0.302694E+10 | 20498.66 | 22-OCT-13:22 | 18.85 | 12.94 | 0.346619E+09 | 549.75 | 20-OCT-13:00 | 18.85 | 12.94 |
November | 0.132145E+10 | 8990.37 | 17-NOV-13:03 | 10.10 | 3.25 | 0.328216E+09 | 549.49 | 07-NOV-14:30 | 10.10 | 3.25 |
December | 0.475234E+09 | 4126.54 | 20-DEC-13:25 | -20.9 | -21.5 | 0.304668E+09 | 549.49 | 20-DEC-14:00 | -18.9 | -19.7 |
Annual Sum or Average | 0.471742E+11 | 0.441159E+10 | ||||||||
Minimum of Months | 0.475234E+09 | 4126.54 | -20.9 | -21.5 | 0.304668E+09 | 549.49 | -18.9 | -19.7 | ||
Maximum of Months | 0.791545E+10 | 20498.66 | 30.00 | 22.84 | 0.445332E+09 | 567.00 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85224873.80 | 1588.88 | 27-JAN-16:00 | -14.4 | -15.6 | 0.192731E+09 | 286.39 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.286170E+09 | 2542.82 | 08-FEB-16:30 | 3.85 | -1.1 | 0.178821E+09 | 338.68 | 08-FEB-16:00 | 3.30 | -1.3 |
March | 0.790274E+09 | 5267.15 | 31-MAR-16:00 | 8.90 | 3.77 | 0.218407E+09 | 339.04 | 10-MAR-15:50 | 8.90 | 3.77 |
April | 0.217240E+10 | 17316.42 | 23-APR-16:42 | 26.20 | 16.72 | 0.208155E+09 | 347.84 | 18-APR-13:00 | 26.20 | 16.72 |
May | 0.458394E+10 | 18976.15 | 14-MAY-17:01 | 20.00 | 8.43 | 0.258742E+09 | 347.86 | 23-MAY-13:50 | 25.63 | 17.00 |
June | 0.534680E+10 | 17156.00 | 17-JUN-17:42 | 23.90 | 13.28 | 0.268447E+09 | 347.86 | 26-JUN-13:09 | 25.78 | 17.07 |
July | 0.583204E+10 | 17587.12 | 16-JUL-16:42 | 21.38 | 15.74 | 0.252997E+09 | 347.86 | 17-JUL-13:00 | 19.40 | 14.70 |
August | 0.498477E+10 | 17529.70 | 27-AUG-15:32 | 23.70 | 18.88 | 0.276626E+09 | 347.86 | 10-AUG-13:00 | 23.70 | 18.88 |
September | 0.309261E+10 | 14571.76 | 03-SEP-17:12 | 21.33 | 15.90 | 0.224985E+09 | 347.85 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.131813E+10 | 5792.68 | 19-OCT-16:00 | 21.70 | 13.55 | 0.207050E+09 | 347.83 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.308966E+09 | 1874.91 | 17-NOV-15:50 | 10.10 | 3.24 | 0.194041E+09 | 322.36 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 30075594.91 | 1183.97 | 02-DEC-17:02 | -20.0 | -20.5 | 0.185706E+09 | 257.57 | 19-DEC-10:39 | -24.5 | -25.0 |
Annual Sum or Average | 0.288314E+11 | 0.266671E+10 | ||||||||
Minimum of Months | 30075594.91 | 1183.97 | -20.0 | -20.5 | 0.178821E+09 | 257.57 | -24.5 | -25.0 | ||
Maximum of Months | 0.583204E+10 | 18976.15 | 26.20 | 18.88 | 0.276626E+09 | 347.86 | 26.20 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7655165.78 | 971.62 | 21-JAN-17:02 | -5.0 | -7.1 | 0.297106E+09 | 406.84 | 03-JAN-14:00 | -5.0 | -7.1 |
February | 14291091.95 | 975.78 | 11-FEB-17:02 | -7.1 | -8.6 | 0.275946E+09 | 406.79 | 01-FEB-14:39 | -7.1 | -8.6 |
March | 0.146893E+09 | 1154.75 | 31-MAR-16:00 | 8.90 | 3.77 | 0.332552E+09 | 426.33 | 28-MAR-13:00 | 8.90 | 3.77 |
April | 0.877722E+09 | 1837.10 | 23-APR-17:42 | 25.68 | 16.51 | 0.310726E+09 | 498.25 | 14-APR-13:09 | 25.68 | 16.51 |
May | 0.250757E+10 | 3809.36 | 26-MAY-13:30 | 22.50 | 17.44 | 0.408218E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.368250E+10 | 5362.49 | 29-JUN-15:00 | 34.40 | 24.01 | 0.431031E+09 | 549.50 | 06-JUN-09:09 | 34.40 | 24.01 |
July | 0.451578E+10 | 6632.66 | 24-JUL-06:03 | 18.68 | 16.82 | 0.404282E+09 | 565.83 | 05-JUL-10:00 | 18.68 | 16.82 |
August | 0.414942E+10 | 5109.66 | 09-AUG-15:30 | 27.25 | 21.19 | 0.451738E+09 | 549.50 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.256945E+10 | 4266.61 | 01-SEP-15:40 | 26.10 | 17.70 | 0.387949E+09 | 549.50 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.156022E+10 | 2009.48 | 22-OCT-16:03 | 18.53 | 12.09 | 0.346987E+09 | 546.07 | 02-OCT-13:50 | 18.53 | 12.09 |
November | 0.429201E+09 | 1374.01 | 01-NOV-15:30 | 18.05 | 13.35 | 0.308244E+09 | 480.30 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 10816498.05 | 981.77 | 30-DEC-17:02 | -3.3 | -3.3 | 0.291198E+09 | 406.82 | 11-DEC-14:30 | -3.3 | -3.3 |
Annual Sum or Average | 0.204715E+11 | 0.424598E+10 | ||||||||
Minimum of Months | 7655165.78 | 971.62 | -7.1 | -8.6 | 0.275946E+09 | 406.79 | -7.1 | -8.6 | ||
Maximum of Months | 0.451578E+10 | 6632.66 | 34.40 | 24.01 | 0.451738E+09 | 565.83 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7612259.13 | 882.35 | 21-JAN-17:02 | -5.0 | -7.1 | 0.192458E+09 | 257.58 | 04-JAN-14:39 | -5.0 | -7.1 |
February | 99187160.64 | 1067.18 | 28-FEB-10:25 | -4.4 | -6.4 | 0.175942E+09 | 276.03 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.437605E+09 | 1415.83 | 31-MAR-09:45 | 1.42 | -1.1 | 0.218737E+09 | 335.71 | 31-MAR-09:00 | 1.70 | -0.9 |
April | 0.154047E+10 | 4236.56 | 18-APR-09:30 | 18.05 | 10.95 | 0.222894E+09 | 347.88 | 11-APR-09:09 | 18.05 | 10.95 |
May | 0.307876E+10 | 6333.15 | 18-MAY-09:30 | 24.55 | 16.00 | 0.269374E+09 | 347.89 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.448476E+10 | 12593.41 | 25-JUN-08:31 | 24.63 | 20.97 | 0.274531E+09 | 347.88 | 13-JUN-09:00 | 24.63 | 20.97 |
July | 0.534140E+10 | 11028.06 | 23-JUL-10:12 | 27.23 | 23.20 | 0.256581E+09 | 349.64 | 05-JUL-13:09 | 27.23 | 23.20 |
August | 0.450566E+10 | 13032.00 | 20-AUG-09:11 | 21.33 | 15.66 | 0.286501E+09 | 347.88 | 04-AUG-09:00 | 21.33 | 15.66 |
September | 0.299666E+10 | 6976.99 | 10-SEP-10:02 | 15.87 | 10.57 | 0.245779E+09 | 347.88 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.152175E+10 | 3209.36 | 19-OCT-08:35 | 10.37 | 7.57 | 0.223503E+09 | 347.88 | 18-OCT-09:20 | 10.37 | 7.57 |
November | 0.484886E+09 | 1263.94 | 17-NOV-10:20 | 4.43 | 0.70 | 0.196742E+09 | 309.70 | 17-NOV-10:30 | 5.00 | 1.00 |
December | 22180249.98 | 914.99 | 01-DEC-09:35 | -21.1 | -21.3 | 0.186150E+09 | 257.57 | 18-DEC-14:30 | -22.8 | -23.5 |
Annual Sum or Average | 0.245209E+11 | 0.274919E+10 | ||||||||
Minimum of Months | 7612259.13 | 882.35 | -21.1 | -21.3 | 0.175942E+09 | 257.57 | -22.8 | -23.5 | ||
Maximum of Months | 0.534140E+10 | 13032.00 | 27.23 | 23.20 | 0.286501E+09 | 349.64 | 27.23 | 23.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82792997.96 | 1454.00 | 21-JAN-12:00 | -10.0 | -10.7 | 0.263434E+09 | 444.36 | 27-JAN-14:50 | -14.4 | -15.6 |
February | 0.344530E+09 | 2678.82 | 28-FEB-14:55 | 6.10 | 1.55 | 0.260908E+09 | 549.51 | 28-FEB-14:20 | 6.10 | 1.55 |
March | 0.481663E+09 | 3301.96 | 31-MAR-14:30 | 8.30 | 2.87 | 0.326136E+09 | 549.50 | 31-MAR-13:50 | 8.30 | 2.87 |
April | 0.169382E+10 | 9816.81 | 23-APR-14:22 | 25.00 | 16.28 | 0.326332E+09 | 549.50 | 19-APR-13:50 | 25.00 | 16.28 |
May | 0.368152E+10 | 10763.30 | 18-MAY-12:00 | 27.80 | 16.87 | 0.401470E+09 | 549.52 | 16-MAY-13:30 | 27.80 | 16.87 |
June | 0.489178E+10 | 13829.58 | 29-JUN-16:10 | 34.90 | 24.48 | 0.420524E+09 | 555.77 | 30-JUN-12:09 | 31.70 | 24.14 |
July | 0.643833E+10 | 14116.29 | 23-JUL-13:32 | 30.00 | 22.59 | 0.400969E+09 | 563.32 | 05-JUL-13:09 | 30.00 | 22.59 |
August | 0.656165E+10 | 16991.05 | 13-AUG-13:21 | 23.05 | 14.31 | 0.444707E+09 | 549.93 | 22-AUG-13:50 | 24.32 | 16.45 |
September | 0.462433E+10 | 16664.29 | 03-SEP-13:42 | 20.92 | 15.82 | 0.375013E+09 | 549.96 | 07-SEP-13:00 | 23.90 | 14.48 |
October | 0.235572E+10 | 16364.27 | 22-OCT-13:22 | 18.85 | 12.94 | 0.346029E+09 | 549.61 | 20-OCT-13:00 | 18.85 | 12.94 |
November | 0.571553E+09 | 6827.95 | 17-NOV-13:07 | 10.10 | 3.25 | 0.309081E+09 | 549.51 | 10-NOV-14:09 | 10.10 | 3.25 |
December | 0.141525E+09 | 2721.96 | 02-DEC-13:40 | -18.4 | -19.2 | 0.260210E+09 | 406.74 | 12-DEC-10:00 | -7.1 | -7.7 |
Annual Sum or Average | 0.318692E+11 | 0.413481E+10 | ||||||||
Minimum of Months | 82792997.96 | 1454.00 | -18.4 | -19.2 | 0.260210E+09 | 406.74 | -14.4 | -15.6 | ||
Maximum of Months | 0.656165E+10 | 16991.05 | 34.90 | 24.48 | 0.444707E+09 | 563.32 | 31.70 | 24.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52084862.00 | 1203.94 | 27-JAN-16:00 | -14.4 | -15.6 | 0.192431E+09 | 277.70 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.165619E+09 | 1524.80 | 08-FEB-16:40 | 3.67 | -1.2 | 0.177643E+09 | 328.61 | 08-FEB-16:49 | 3.48 | -1.2 |
March | 0.468306E+09 | 3230.75 | 28-MAR-17:20 | 7.20 | 3.26 | 0.215354E+09 | 338.67 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.146121E+10 | 13070.12 | 23-APR-17:42 | 25.68 | 16.51 | 0.207073E+09 | 347.82 | 18-APR-13:00 | 25.68 | 16.51 |
May | 0.329419E+10 | 12491.53 | 14-MAY-17:52 | 20.00 | 8.57 | 0.260983E+09 | 347.85 | 25-MAY-09:00 | 21.50 | 16.78 |
June | 0.402778E+10 | 13410.62 | 17-JUN-18:22 | 23.05 | 13.03 | 0.270639E+09 | 347.85 | 07-JUN-13:00 | 23.05 | 13.03 |
July | 0.501434E+10 | 13416.09 | 23-JUL-16:12 | 29.43 | 22.47 | 0.256198E+09 | 349.92 | 05-JUL-13:39 | 29.43 | 22.47 |
August | 0.456389E+10 | 14085.03 | 13-AUG-18:02 | 21.93 | 15.20 | 0.285343E+09 | 347.86 | 10-AUG-13:00 | 21.93 | 15.20 |
September | 0.294359E+10 | 14663.36 | 03-SEP-17:41 | 20.78 | 15.57 | 0.242645E+09 | 347.85 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.165789E+10 | 4835.04 | 19-OCT-16:00 | 21.70 | 13.55 | 0.220564E+09 | 347.83 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.464141E+09 | 1527.52 | 17-NOV-15:50 | 10.10 | 3.24 | 0.196180E+09 | 327.85 | 17-NOV-15:00 | 10.00 | 3.20 |
December | 28070777.77 | 958.62 | 02-DEC-17:02 | -20.0 | -20.5 | 0.186068E+09 | 257.55 | 18-DEC-10:30 | -21.9 | -22.7 |
Annual Sum or Average | 0.241411E+11 | 0.271112E+10 | ||||||||
Minimum of Months | 28070777.77 | 958.62 | -20.0 | -20.5 | 0.177643E+09 | 257.55 | -21.9 | -22.7 | ||
Maximum of Months | 0.501434E+10 | 14663.36 | 29.43 | 22.47 | 0.285343E+09 | 349.92 | 29.43 | 22.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9165721.34 | 970.46 | 28-JAN-17:02 | -7.8 | -9.1 | 0.301861E+09 | 406.82 | 13-JAN-10:39 | -7.8 | -9.1 |
February | 85421634.35 | 1095.39 | 08-FEB-15:00 | 5.00 | -0.5 | 0.277030E+09 | 419.96 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.518222E+09 | 1423.89 | 29-MAR-15:40 | 4.80 | 1.35 | 0.340709E+09 | 492.06 | 28-MAR-13:00 | 4.80 | 1.35 |
April | 0.156860E+10 | 2949.10 | 18-APR-15:20 | 13.90 | 7.83 | 0.342060E+09 | 549.48 | 18-APR-13:00 | 13.90 | 7.83 |
May | 0.386763E+10 | 5591.87 | 26-MAY-13:30 | 22.50 | 17.44 | 0.427303E+09 | 549.51 | 24-MAY-09:09 | 22.50 | 17.44 |
June | 0.522592E+10 | 8493.96 | 28-JUN-06:03 | 19.55 | 18.20 | 0.434769E+09 | 549.78 | 28-JUN-13:39 | 30.00 | 21.52 |
July | 0.558286E+10 | 10123.67 | 23-JUL-16:41 | 28.58 | 21.92 | 0.405518E+09 | 583.28 | 05-JUL-10:00 | 28.58 | 21.92 |
August | 0.471193E+10 | 5763.65 | 09-AUG-15:30 | 27.25 | 21.19 | 0.452340E+09 | 549.51 | 10-AUG-13:00 | 19.40 | 16.96 |
September | 0.274543E+10 | 4837.87 | 01-SEP-15:40 | 26.10 | 17.70 | 0.387933E+09 | 549.50 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.148751E+10 | 2220.51 | 20-OCT-15:20 | 18.70 | 10.02 | 0.347695E+09 | 549.48 | 02-OCT-13:00 | 18.70 | 10.02 |
November | 0.436868E+09 | 1404.78 | 01-NOV-15:30 | 18.05 | 13.35 | 0.308420E+09 | 490.69 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 10871900.49 | 976.21 | 30-DEC-17:02 | -3.3 | -3.3 | 0.292517E+09 | 406.82 | 19-DEC-10:00 | -3.3 | -3.3 |
Annual Sum or Average | 0.262504E+11 | 0.431816E+10 | ||||||||
Minimum of Months | 9165721.34 | 970.46 | -7.8 | -9.1 | 0.277030E+09 | 406.82 | -7.8 | -9.1 | ||
Maximum of Months | 0.558286E+10 | 10123.67 | 28.58 | 21.92 | 0.452340E+09 | 583.28 | 30.00 | 21.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23680826.97 | 1173.17 | 25-JAN-10:00 | -23.3 | -23.6 | 0.141637E+09 | 250.75 | 02-JAN-16:40 | -23.3 | -23.6 |
February | 0.239356E+09 | 1624.85 | 28-FEB-09:55 | -6.1 | -7.7 | 0.130203E+09 | 308.64 | 28-FEB-09:00 | -6.1 | -7.7 |
March | 0.910598E+09 | 3670.70 | 31-MAR-08:55 | 0.00 | -1.8 | 0.165219E+09 | 339.04 | 29-MAR-10:50 | 0.00 | -1.8 |
April | 0.250879E+10 | 7576.12 | 19-APR-08:30 | 3.05 | -2.4 | 0.168905E+09 | 339.24 | 11-APR-08:30 | 3.05 | -2.4 |
May | 0.431034E+10 | 11878.59 | 21-MAY-08:42 | 11.70 | 7.10 | 0.200532E+09 | 339.03 | 17-MAY-08:50 | 11.70 | 7.10 |
June | 0.562144E+10 | 17744.90 | 25-JUN-08:61 | 24.08 | 20.82 | 0.202635E+09 | 339.17 | 28-JUN-08:39 | 26.47 | 21.10 |
July | 0.605999E+10 | 17181.07 | 23-JUL-10:01 | 26.97 | 23.13 | 0.189807E+09 | 344.47 | 05-JUL-10:00 | 26.97 | 23.13 |
August | 0.488709E+10 | 16987.58 | 20-AUG-09:11 | 21.33 | 15.66 | 0.209246E+09 | 338.75 | 21-AUG-07:10 | 15.97 | 15.14 |
September | 0.328662E+10 | 12881.15 | 04-SEP-10:22 | 14.70 | 9.57 | 0.176691E+09 | 338.73 | 05-SEP-07:10 | 8.77 | 7.97 |
October | 0.161283E+10 | 5616.89 | 22-OCT-09:53 | 14.40 | 11.54 | 0.158682E+09 | 338.73 | 19-OCT-10:09 | 14.40 | 11.54 |
November | 0.486165E+09 | 1675.31 | 16-NOV-09:45 | 1.32 | -0.7 | 0.143807E+09 | 316.14 | 16-NOV-09:00 | 1.70 | -0.5 |
December | 34162354.71 | 1210.77 | 01-DEC-10:00 | -20.8 | -21.1 | 0.136861E+09 | 253.48 | 01-DEC-09:00 | -20.8 | -21.1 |
Annual Sum or Average | 0.299811E+11 | 0.202422E+10 | ||||||||
Minimum of Months | 23680826.97 | 1173.17 | -23.3 | -23.6 | 0.130203E+09 | 250.75 | -23.3 | -23.6 | ||
Maximum of Months | 0.605999E+10 | 17744.90 | 26.97 | 23.13 | 0.209246E+09 | 344.47 | 26.97 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.983968E+09 | 7732.84 | 27-JAN-13:40 | -14.8 | -15.9 | 0.329493E+09 | 549.49 | 06-JAN-14:50 | -14.8 | -15.9 |
February | 0.173895E+10 | 10306.98 | 28-FEB-13:35 | 3.33 | -0.5 | 0.314954E+09 | 549.50 | 27-FEB-14:50 | 3.33 | -0.5 |
March | 0.250016E+10 | 16621.64 | 26-MAR-13:43 | 8.80 | 4.51 | 0.382155E+09 | 549.50 | 20-MAR-13:00 | 8.80 | 4.51 |
April | 0.422624E+10 | 18610.85 | 23-APR-13:42 | 24.13 | 15.95 | 0.365166E+09 | 549.95 | 13-APR-13:00 | 24.13 | 15.95 |
May | 0.615480E+10 | 18018.47 | 21-MAY-12:43 | 19.22 | 10.58 | 0.427472E+09 | 550.43 | 17-MAY-13:00 | 19.22 | 10.58 |
June | 0.690886E+10 | 19184.90 | 25-JUN-11:22 | 27.25 | 21.76 | 0.432522E+09 | 550.08 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.784366E+10 | 19911.31 | 23-JUL-13:21 | 30.00 | 22.65 | 0.404598E+09 | 585.19 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.773762E+10 | 20625.85 | 13-AUG-13:21 | 23.05 | 14.31 | 0.451494E+09 | 550.58 | 01-AUG-13:50 | 23.05 | 14.31 |
September | 0.596807E+10 | 20955.84 | 04-SEP-11:41 | 15.50 | 9.24 | 0.388844E+09 | 558.01 | 01-SEP-13:20 | 15.50 | 9.24 |
October | 0.366797E+10 | 21194.02 | 22-OCT-13:51 | 19.40 | 12.77 | 0.363418E+09 | 549.80 | 20-OCT-13:00 | 19.40 | 12.77 |
November | 0.171937E+10 | 9830.16 | 17-NOV-13:03 | 10.10 | 3.25 | 0.337137E+09 | 549.50 | 07-NOV-14:50 | 10.10 | 3.25 |
December | 0.612900E+09 | 5187.33 | 02-DEC-13:20 | -18.8 | -19.5 | 0.309544E+09 | 549.49 | 20-DEC-14:00 | -18.9 | -19.7 |
Annual Sum or Average | 0.500626E+11 | 0.450680E+10 | ||||||||
Minimum of Months | 0.612900E+09 | 5187.33 | -18.8 | -19.5 | 0.309544E+09 | 549.49 | -18.9 | -19.7 | ||
Maximum of Months | 0.784366E+10 | 21194.02 | 30.00 | 22.65 | 0.451494E+09 | 585.19 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108206E+09 | 1594.33 | 27-JAN-16:00 | -14.4 | -15.6 | 0.193666E+09 | 299.04 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.343470E+09 | 2684.17 | 08-FEB-16:30 | 3.85 | -1.1 | 0.180319E+09 | 338.68 | 28-FEB-16:00 | 5.60 | 1.06 |
March | 0.991552E+09 | 5710.99 | 26-MAR-17:03 | 9.82 | 4.83 | 0.220945E+09 | 338.68 | 31-MAR-15:00 | 8.90 | 3.77 |
April | 0.246443E+10 | 16354.76 | 23-APR-16:22 | 26.40 | 16.81 | 0.213989E+09 | 347.84 | 19-APR-13:50 | 26.40 | 16.81 |
May | 0.461449E+10 | 16136.11 | 14-MAY-17:12 | 20.00 | 8.46 | 0.265315E+09 | 347.86 | 24-MAY-09:09 | 22.38 | 16.32 |
June | 0.526927E+10 | 16153.35 | 17-JUN-17:42 | 23.90 | 13.28 | 0.272071E+09 | 347.85 | 07-JUN-13:00 | 23.90 | 13.28 |
July | 0.577909E+10 | 17700.60 | 23-JUL-16:41 | 28.58 | 21.92 | 0.255336E+09 | 351.32 | 05-JUL-13:09 | 28.58 | 21.92 |
August | 0.500551E+10 | 16681.45 | 13-AUG-18:02 | 21.93 | 15.20 | 0.282345E+09 | 347.86 | 10-AUG-13:00 | 21.93 | 15.20 |
September | 0.329433E+10 | 17374.02 | 03-SEP-17:41 | 20.78 | 15.57 | 0.235784E+09 | 347.85 | 11-SEP-13:00 | 18.90 | 14.76 |
October | 0.177307E+10 | 7157.90 | 22-OCT-15:53 | 18.90 | 12.36 | 0.214754E+09 | 347.83 | 20-OCT-13:00 | 18.90 | 12.36 |
November | 0.505044E+09 | 1873.25 | 17-NOV-15:40 | 10.20 | 3.28 | 0.196397E+09 | 337.06 | 17-NOV-15:50 | 10.10 | 3.24 |
December | 55868287.94 | 1286.61 | 20-DEC-15:40 | -19.8 | -20.5 | 0.186123E+09 | 260.09 | 20-DEC-15:50 | -20.0 | -20.7 |
Annual Sum or Average | 0.302043E+11 | 0.271704E+10 | ||||||||
Minimum of Months | 55868287.94 | 1286.61 | -19.8 | -20.5 | 0.180319E+09 | 260.09 | -20.0 | -20.7 | ||
Maximum of Months | 0.577909E+10 | 17700.60 | 28.58 | 21.92 | 0.282345E+09 | 351.32 | 28.58 | 21.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319125E+09 | 11707.62 | 02-JAN-05:01 | -18.2 |
February | 1619152.09 | 5989.42 | 21-FEB-07:02 | 2.70 |
March | 999200.55 | 6028.02 | 06-MAR-07:01 | -19.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 653313.11 | 5709.48 | 27-NOV-07:01 | -6.7 |
December | 47404876.90 | 8582.56 | 26-DEC-06:03 | -26.7 |
Annual Sum or Average | 0.369801E+09 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.319125E+09 | 11707.62 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123357E+11 | 18765.41 | 09-JAN-05:19 | -32.8 |
February | 0.785865E+10 | 17459.38 | 14-FEB-06:09 | -32.0 |
March | 0.529372E+10 | 16193.04 | 07-MAR-06:13 | -21.8 |
April | 0.165243E+10 | 11905.65 | 05-APR-06:02 | -13.5 |
May | 0.404132E+09 | 6483.79 | 01-MAY-06:01 | -3.5 |
June | 0.136261E+09 | 5175.40 | 04-JUN-07:06 | 9.97 |
July | 0.103896E+09 | 4372.67 | 02-JUL-06:20 | 11.70 |
August | 0.137587E+09 | 4958.94 | 06-AUG-08:12 | 16.83 |
September | 0.478885E+09 | 4816.72 | 10-SEP-08:13 | 11.10 |
October | 0.178380E+10 | 14107.79 | 30-OCT-05:12 | -9.8 |
November | 0.494732E+10 | 15900.74 | 25-NOV-06:07 | -19.4 |
December | 0.111913E+11 | 17043.48 | 20-DEC-06:08 | -28.9 |
Annual Sum or Average | 0.463237E+11 | |||
Minimum of Months | 0.103896E+09 | 4372.67 | -32.8 | |
Maximum of Months | 0.123357E+11 | 18765.41 | 16.83 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504359E+10 | 11253.40 | 02-JAN-08:18 | -19.6 |
February | 0.313566E+10 | 8338.85 | 27-FEB-07:14 | -19.0 |
March | 0.229956E+10 | 9246.47 | 26-MAR-13:43 | 8.80 |
April | 0.777020E+09 | 6584.82 | 23-APR-15:42 | 26.52 |
May | 0.110359E+09 | 4716.64 | 14-MAY-16:32 | 20.00 |
June | 23687875.72 | 4426.07 | 25-JUN-10:41 | 27.62 |
July | 29403671.79 | 5058.49 | 23-JUL-15:21 | 30.00 |
August | 32434084.51 | 5881.77 | 20-AUG-14:32 | 25.40 |
September | 0.102949E+09 | 5912.40 | 03-SEP-15:41 | 21.70 |
October | 0.799823E+09 | 8847.98 | 09-OCT-13:23 | 5.85 |
November | 0.224326E+10 | 9138.32 | 27-NOV-07:15 | -6.7 |
December | 0.444454E+10 | 11388.19 | 26-DEC-08:26 | -26.2 |
Annual Sum or Average | 0.190423E+11 | |||
Minimum of Months | 23687875.72 | 4426.07 | -26.2 | |
Maximum of Months | 0.504359E+10 | 11388.19 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359773E+10 | 9067.03 | 02-JAN-08:55 | -20.0 |
February | 0.206085E+10 | 4524.72 | 27-FEB-08:55 | -16.1 |
March | 0.148727E+10 | 4537.95 | 06-MAR-07:01 | -19.3 |
April | 0.382115E+09 | 3278.60 | 20-APR-05:03 | -4.1 |
May | 36985728.74 | 2776.93 | 14-MAY-14:28 | 19.45 |
June | 14677752.86 | 2971.28 | 30-JUN-04:02 | 26.10 |
July | 25737985.82 | 2471.08 | 09-JUL-14:28 | 17.20 |
August | 28168794.05 | 3285.73 | 20-AUG-11:52 | 24.40 |
September | 34083966.61 | 4365.29 | 06-SEP-04:03 | 1.10 |
October | 0.391507E+09 | 4279.46 | 04-OCT-05:03 | -0.5 |
November | 0.145781E+10 | 5223.00 | 27-NOV-07:01 | -6.7 |
December | 0.313203E+10 | 7136.41 | 26-DEC-07:01 | -26.5 |
Annual Sum or Average | 0.126490E+11 | |||
Minimum of Months | 14677752.86 | 2471.08 | -26.5 | |
Maximum of Months | 0.359773E+10 | 9067.03 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200243E+10 | 19546.26 | 02-JAN-05:01 | -18.2 |
February | 0.456727E+09 | 16398.31 | 27-FEB-06:01 | -18.5 |
March | 0.185242E+09 | 16543.35 | 06-MAR-06:02 | -19.0 |
April | 10260054.13 | 13994.90 | 10-APR-06:01 | -1.9 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 8122111.51 | 13973.95 | 30-OCT-06:01 | -9.4 |
November | 0.301388E+09 | 16654.90 | 27-NOV-06:01 | -7.1 |
December | 0.129065E+10 | 19189.01 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.425482E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.200243E+10 | 19546.26 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672911E+10 | 27190.66 | 02-JAN-00:02 | -20.9 |
February | 0.316417E+10 | 25845.12 | 13-FEB-05:01 | -23.4 |
March | 0.151674E+10 | 26014.92 | 06-MAR-05:11 | -18.5 |
April | 0.246398E+09 | 22952.55 | 03-APR-05:01 | -4.3 |
May | 3879861.36 | 20140.11 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.226533E+09 | 23190.38 | 30-OCT-05:01 | -9.9 |
November | 0.188298E+10 | 25921.39 | 27-NOV-05:01 | -7.2 |
December | 0.556265E+10 | 27092.76 | 26-DEC-03:42 | -24.6 |
Annual Sum or Average | 0.193325E+11 | |||
Minimum of Months | 0.00 | 0.00 | -24.6 | |
Maximum of Months | 0.672911E+10 | 27190.66 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100897E+11 | 10852.02 | 09-JAN-05:11 | -32.8 |
February | 0.608991E+10 | 10342.99 | 13-FEB-03:02 | -22.3 |
March | 0.373415E+10 | 10133.38 | 06-MAR-03:13 | -16.5 |
April | 0.676166E+09 | 9620.39 | 03-APR-04:01 | -5.4 |
May | 19158000.06 | 8316.22 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 195113.34 | 1300.76 | 19-AUG-06:03 | 6.23 |
September | 10417432.56 | 7473.23 | 23-SEP-06:03 | 4.32 |
October | 0.625152E+09 | 9477.25 | 30-OCT-04:01 | -10.0 |
November | 0.328218E+10 | 9838.62 | 24-NOV-05:11 | -10.6 |
December | 0.914986E+10 | 10637.59 | 24-DEC-21:42 | -27.9 |
Annual Sum or Average | 0.336769E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.100897E+11 | 10852.02 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601597E+10 | 10686.64 | 09-JAN-05:11 | -32.8 |
February | 0.322338E+10 | 9938.75 | 13-FEB-03:02 | -22.3 |
March | 0.184719E+10 | 9632.80 | 06-MAR-05:11 | -18.5 |
April | 0.280904E+09 | 9025.71 | 03-APR-04:01 | -5.4 |
May | 3956556.70 | 7221.95 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 9854633.17 | 5177.08 | 28-SEP-06:03 | 6.70 |
October | 0.361099E+09 | 8868.18 | 30-OCT-04:01 | -10.0 |
November | 0.194339E+10 | 9381.99 | 24-NOV-05:11 | -10.6 |
December | 0.558494E+10 | 10337.59 | 26-DEC-03:42 | -24.6 |
Annual Sum or Average | 0.192707E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.601597E+10 | 10686.64 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.678855E+10 | 14863.36 | 09-JAN-05:11 | -32.8 |
February | 0.367629E+10 | 13885.19 | 13-FEB-03:02 | -22.3 |
March | 0.240446E+10 | 13526.46 | 05-MAR-06:12 | -27.8 |
April | 0.508241E+09 | 12361.97 | 03-APR-04:01 | -5.4 |
May | 22262408.80 | 10395.30 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 777227.93 | 5180.36 | 19-AUG-06:03 | 6.23 |
September | 12274362.69 | 8115.15 | 23-SEP-06:03 | 4.32 |
October | 0.477055E+09 | 12588.02 | 30-OCT-04:01 | -10.0 |
November | 0.234979E+10 | 13223.53 | 24-NOV-05:11 | -10.6 |
December | 0.652761E+10 | 14432.64 | 26-DEC-03:42 | -24.6 |
Annual Sum or Average | 0.227673E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.678855E+10 | 14863.36 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622860E+10 | 11251.15 | 09-JAN-05:11 | -32.8 |
February | 0.354376E+10 | 10417.18 | 13-FEB-03:02 | -22.3 |
March | 0.209996E+10 | 10111.56 | 06-MAR-05:11 | -18.5 |
April | 0.391775E+09 | 9255.24 | 03-APR-04:01 | -5.4 |
May | 16037296.11 | 7489.19 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 954634.93 | 4832.55 | 19-AUG-06:03 | 6.23 |
September | 11949772.32 | 5169.12 | 23-SEP-06:03 | 4.32 |
October | 0.401583E+09 | 9260.65 | 30-OCT-04:01 | -10.0 |
November | 0.202785E+10 | 9831.39 | 24-NOV-05:11 | -10.6 |
December | 0.571658E+10 | 10874.23 | 26-DEC-03:42 | -24.6 |
Annual Sum or Average | 0.204390E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.622860E+10 | 11251.15 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773469E+10 | 8286.02 | 01-JAN-22:02 | -23.0 |
February | 0.458092E+10 | 7753.70 | 13-FEB-05:11 | -23.5 |
March | 0.347759E+10 | 7797.58 | 06-MAR-05:11 | -18.5 |
April | 0.589669E+09 | 7047.77 | 03-APR-04:01 | -5.4 |
May | 12818003.57 | 6449.15 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 65193147.08 | 6571.01 | 30-OCT-05:01 | -9.9 |
November | 0.136231E+10 | 7456.34 | 27-NOV-05:01 | -7.2 |
December | 0.602675E+10 | 7920.66 | 26-DEC-04:51 | -25.8 |
Annual Sum or Average | 0.238499E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.8 | |
Maximum of Months | 0.773469E+10 | 8286.02 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454994E+10 | 8104.69 | 09-JAN-05:11 | -32.8 |
February | 0.221152E+10 | 7433.21 | 13-FEB-05:11 | -23.5 |
March | 0.144124E+10 | 7474.39 | 06-MAR-05:11 | -18.5 |
April | 0.155371E+09 | 6427.44 | 10-APR-05:01 | -2.7 |
May | 344218.14 | 2829.93 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 38172435.29 | 5941.02 | 30-OCT-05:01 | -9.9 |
November | 0.776596E+09 | 7078.75 | 27-NOV-05:01 | -7.2 |
December | 0.359712E+10 | 7655.62 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.127703E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.454994E+10 | 8104.69 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100888E+11 | 16895.71 | 09-JAN-07:10 | -32.3 |
February | 0.606168E+10 | 16399.85 | 14-FEB-07:10 | -33.0 |
March | 0.547717E+10 | 14267.64 | 16-MAR-06:10 | -22.9 |
April | 0.198312E+10 | 12257.60 | 05-APR-06:10 | -13.5 |
May | 0.575006E+09 | 10238.58 | 01-MAY-06:10 | -3.5 |
June | 0.101902E+09 | 7227.77 | 02-JUN-06:10 | 9.08 |
July | 11101857.69 | 6311.15 | 18-JUL-06:06 | 11.23 |
August | 42319817.01 | 6996.84 | 25-AUG-06:05 | 9.05 |
September | 0.513226E+09 | 8073.76 | 21-SEP-06:10 | 5.10 |
October | 0.157065E+10 | 11511.15 | 30-OCT-06:10 | -9.4 |
November | 0.356074E+10 | 13235.83 | 29-NOV-07:10 | -18.4 |
December | 0.896738E+10 | 15859.25 | 20-DEC-07:10 | -29.1 |
Annual Sum or Average | 0.389531E+11 | |||
Minimum of Months | 11101857.69 | 6311.15 | -33.0 | |
Maximum of Months | 0.100888E+11 | 16895.71 | 11.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470560E+10 | 8473.77 | 09-JAN-05:11 | -32.8 |
February | 0.237849E+10 | 7732.87 | 13-FEB-05:11 | -23.5 |
March | 0.159476E+10 | 7825.25 | 06-MAR-05:11 | -18.5 |
April | 0.220906E+09 | 6635.31 | 10-APR-05:01 | -2.7 |
May | 6662043.89 | 5704.50 | 01-MAY-05:02 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 44778547.88 | 6123.39 | 30-OCT-05:01 | -9.9 |
November | 0.792474E+09 | 7329.18 | 27-NOV-05:01 | -7.2 |
December | 0.370845E+10 | 7982.82 | 26-DEC-04:51 | -25.8 |
Annual Sum or Average | 0.134521E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.470560E+10 | 8473.77 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684746E+10 | 8983.93 | 09-JAN-05:11 | -32.8 |
February | 0.352959E+10 | 8361.36 | 13-FEB-04:12 | -23.0 |
March | 0.189121E+10 | 8327.66 | 06-MAR-05:01 | -18.4 |
April | 0.199486E+09 | 7330.62 | 03-APR-05:01 | -4.3 |
May | 1368395.31 | 6399.33 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.141873E+09 | 7312.87 | 30-OCT-05:01 | -9.9 |
November | 0.152325E+10 | 8118.72 | 25-NOV-05:01 | -19.0 |
December | 0.590888E+10 | 8602.53 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.200431E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.684746E+10 | 8983.93 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399759E+10 | 9188.89 | 09-JAN-05:11 | -32.8 |
February | 0.177730E+10 | 8190.09 | 02-FEB-05:11 | -25.4 |
March | 0.917106E+09 | 8193.35 | 06-MAR-05:01 | -18.4 |
April | 80089920.43 | 6769.91 | 03-APR-05:01 | -4.3 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 612796.15 | 1383.05 | 23-SEP-06:03 | 4.32 |
October | 91750891.88 | 6785.34 | 30-OCT-05:01 | -9.9 |
November | 0.937539E+09 | 7975.02 | 25-NOV-05:01 | -19.0 |
December | 0.358879E+10 | 8629.32 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.113908E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.399759E+10 | 9188.89 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409235E+10 | 12292.68 | 09-JAN-05:11 | -32.8 |
February | 0.182307E+10 | 11005.12 | 13-FEB-04:12 | -23.0 |
March | 0.106021E+10 | 11112.23 | 06-MAR-05:01 | -18.4 |
April | 0.137918E+09 | 9319.15 | 10-APR-05:01 | -2.7 |
May | 2489388.30 | 7982.54 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.105442E+09 | 9450.65 | 30-OCT-05:01 | -9.9 |
November | 0.102377E+10 | 10777.06 | 25-NOV-05:01 | -19.0 |
December | 0.376993E+10 | 11580.86 | 25-DEC-07:31 | -28.2 |
Annual Sum or Average | 0.120152E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.409235E+10 | 12292.68 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.411670E+10 | 9381.20 | 09-JAN-05:11 | -32.8 |
February | 0.196639E+10 | 8257.98 | 02-FEB-05:11 | -25.4 |
March | 0.101412E+10 | 8357.70 | 06-MAR-05:01 | -18.4 |
April | 0.113501E+09 | 6820.46 | 04-APR-05:01 | -9.0 |
May | 2065860.04 | 5650.60 | 01-MAY-06:01 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 486145.56 | 970.42 | 29-SEP-06:03 | 7.30 |
October | 0.102714E+09 | 6893.41 | 30-OCT-05:01 | -9.9 |
November | 0.939200E+09 | 8151.70 | 25-NOV-05:01 | -19.0 |
December | 0.362773E+10 | 8766.82 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.118829E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.8 | |
Maximum of Months | 0.411670E+10 | 9381.20 | 17.07 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869384E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.701167E+09 | 1184.79 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.782415E+09 | 1184.79 | 03-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.656426E+09 | 774.31 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.681033E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.672855E+09 | 774.31 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.631432E+09 | 647.98 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.728476E+09 | 947.97 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.673592E+09 | 947.97 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.759121E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841279E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.867130E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886431E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.631432E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.869384E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.532118E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437551E+09 | 860.01 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490400E+09 | 750.07 | 03-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.415442E+09 | 450.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.435035E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.430056E+09 | 450.21 | 09-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.403324E+09 | 450.21 | 25-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.462223E+09 | 600.14 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.425109E+09 | 600.14 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.471505E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.519600E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.530526E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555289E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.403324E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.532118E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.814817E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.675798E+09 | 1184.79 | 02-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.770710E+09 | 1184.79 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.657694E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.686747E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.678696E+09 | 774.31 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.636635E+09 | 711.15 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.730996E+09 | 947.97 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.670850E+09 | 947.97 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.735471E+09 | 1358.45 | 26-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.798187E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.814752E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.867135E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.636635E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.814817E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531948E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.434154E+09 | 750.02 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491353E+09 | 750.02 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.415471E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.431725E+09 | 450.19 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.425951E+09 | 490.17 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.399619E+09 | 450.19 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461955E+09 | 600.10 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.426428E+09 | 750.02 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.474780E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.515425E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.529388E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553820E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.399619E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.531948E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.865145E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.698428E+09 | 1184.79 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.779736E+09 | 1184.79 | 03-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.655414E+09 | 774.31 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.680697E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.672446E+09 | 774.31 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.631133E+09 | 647.98 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.727444E+09 | 947.97 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.672358E+09 | 947.97 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.756356E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.835987E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.861807E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.883695E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.631133E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.865145E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530619E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.436514E+09 | 860.01 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.489237E+09 | 750.07 | 03-MAR-16:49 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.415009E+09 | 450.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.434596E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.429653E+09 | 450.21 | 09-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.402941E+09 | 450.21 | 25-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461450E+09 | 600.14 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.424445E+09 | 600.14 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.470130E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.518142E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.529186E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.554192E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.402941E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.530619E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.812432E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.675068E+09 | 1184.79 | 02-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.769121E+09 | 1184.79 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.656828E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.686175E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.677828E+09 | 774.31 | 30-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.635736E+09 | 647.98 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.729914E+09 | 947.97 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.669883E+09 | 947.97 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.734312E+09 | 1358.45 | 26-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.796407E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.812722E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.865643E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.635736E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.812722E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530502E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.433064E+09 | 750.02 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490087E+09 | 750.02 | 13-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.414619E+09 | 490.17 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.431434E+09 | 450.19 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.425622E+09 | 490.17 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.399272E+09 | 450.19 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461194E+09 | 600.10 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.425502E+09 | 640.09 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.473621E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.514044E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.527627E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.552659E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.399272E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.530502E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.869384E+09 | 1358.45 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.701167E+09 | 1184.79 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.782402E+09 | 1184.79 | 03-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.656426E+09 | 774.31 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.681033E+09 | 647.98 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.672855E+09 | 774.31 | 30-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.631432E+09 | 647.98 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.728476E+09 | 947.97 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.673592E+09 | 947.97 | 19-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.759121E+09 | 1358.45 | 26-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.841279E+09 | 1358.45 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.867130E+09 | 1358.45 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.886430E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.631432E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.869384E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.532118E+09 | 860.01 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.437551E+09 | 860.01 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490400E+09 | 750.07 | 03-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.415442E+09 | 450.21 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.435035E+09 | 410.22 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.430056E+09 | 450.21 | 09-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.403324E+09 | 450.21 | 25-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.462223E+09 | 600.14 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.425109E+09 | 600.14 | 19-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.471505E+09 | 860.01 | 26-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.519600E+09 | 860.01 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.530526E+09 | 860.01 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555289E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.403324E+09 | 410.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.532118E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.814817E+09 | 1358.45 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.675798E+09 | 1184.79 | 02-FEB-16:49 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.770710E+09 | 1184.79 | 03-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.657694E+09 | 774.31 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.686747E+09 | 647.98 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.678696E+09 | 774.31 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.636635E+09 | 711.15 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.730996E+09 | 947.97 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.670850E+09 | 947.97 | 19-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.735471E+09 | 1358.45 | 26-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.798187E+09 | 1358.45 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.814752E+09 | 1358.45 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.867135E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.636635E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.814817E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.531948E+09 | 859.95 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.434154E+09 | 750.02 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491353E+09 | 750.02 | 03-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.415467E+09 | 600.10 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.431725E+09 | 450.19 | 12-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.425951E+09 | 490.17 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.399619E+09 | 450.19 | 03-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.461955E+09 | 600.10 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.426428E+09 | 750.02 | 19-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.474780E+09 | 859.95 | 26-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.515425E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.529388E+09 | 859.95 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553819E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.399619E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.531948E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.869384E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891055E+09 |
February | 0.901968E+09 | 0.701167E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761139E+09 |
March | 0.107774E+10 | 0.782415E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520996E+09 |
April | 0.956342E+09 | 0.656426E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 933271.97 | 0.480557E+09 |
May | 0.103597E+10 | 0.681033E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1572857.16 | 0.245983E+09 |
June | 0.103308E+10 | 0.672855E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5924609.82 | 0.133857E+09 |
July | 0.959235E+09 | 0.631432E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7244662.62 | 98573988.18 |
August | 0.107774E+10 | 0.728476E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2501808.28 | 0.134086E+09 |
September | 0.956342E+09 | 0.673592E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77760.75 | 0.225261E+09 |
October | 0.994195E+09 | 0.759121E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327479E+09 |
November | 0.984487E+09 | 0.841279E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590214E+09 |
December | 0.959235E+09 | 0.867130E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946095E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886431E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18254970.59 | 0.535530E+10 |
Minimum of Months | 0.901968E+09 | 0.631432E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98573988.18 |
Maximum of Months | 0.107774E+10 | 0.869384E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7244662.62 | 0.946095E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.532118E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594978E+09 |
February | 0.571020E+09 | 0.437551E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510006E+09 |
March | 0.682301E+09 | 0.490400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351760E+09 |
April | 0.605444E+09 | 0.415442E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708929.96 | 0.329525E+09 |
May | 0.655854E+09 | 0.435035E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1049697.64 | 0.167703E+09 |
June | 0.654023E+09 | 0.430056E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4025034.37 | 90473619.72 |
July | 0.607275E+09 | 0.403324E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4883167.64 | 65514146.82 |
August | 0.682301E+09 | 0.462223E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1628571.02 | 92257150.76 |
September | 0.605444E+09 | 0.425109E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51841.05 | 0.152336E+09 |
October | 0.629407E+09 | 0.471505E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221063E+09 |
November | 0.623262E+09 | 0.519600E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394809E+09 |
December | 0.607275E+09 | 0.530526E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631378E+09 |
Annual Sum or Average | 0.755301E+10 | 0.555289E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12347241.68 | 0.360180E+10 |
Minimum of Months | 0.571020E+09 | 0.403324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65514146.82 |
Maximum of Months | 0.682301E+09 | 0.532118E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4883167.64 | 0.631378E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.814817E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900107E+09 |
February | 0.901968E+09 | 0.675798E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787122E+09 |
March | 0.107774E+10 | 0.770710E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543428E+09 |
April | 0.956342E+09 | 0.657694E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21275.51 | 0.506306E+09 |
May | 0.103597E+10 | 0.686747E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1572360.22 | 0.251020E+09 |
June | 0.103308E+10 | 0.678696E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5893187.73 | 0.133381E+09 |
July | 0.959235E+09 | 0.636635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7041641.95 | 98940276.10 |
August | 0.107774E+10 | 0.730996E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401368.75 | 0.140558E+09 |
September | 0.956342E+09 | 0.670850E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77283.82 | 0.238858E+09 |
October | 0.994195E+09 | 0.735471E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345348E+09 |
November | 0.984487E+09 | 0.798187E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606814E+09 |
December | 0.959235E+09 | 0.814752E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957003E+09 |
Annual Sum or Average | 0.119305E+11 | 0.867135E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17007117.98 | 0.550888E+10 |
Minimum of Months | 0.901968E+09 | 0.636635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98940276.10 |
Maximum of Months | 0.107774E+10 | 0.814817E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7041641.95 | 0.957003E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.531948E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595198E+09 |
February | 0.570983E+09 | 0.434154E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512579E+09 |
March | 0.682256E+09 | 0.491353E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354300E+09 |
April | 0.605404E+09 | 0.415471E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329490E+09 |
May | 0.655811E+09 | 0.431725E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1048607.95 | 0.168861E+09 |
June | 0.653980E+09 | 0.425951E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4130870.70 | 89778124.06 |
July | 0.607235E+09 | 0.399619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4854379.11 | 68086133.95 |
August | 0.682256E+09 | 0.461955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1729512.12 | 91900499.93 |
September | 0.605404E+09 | 0.426428E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51841.73 | 0.152596E+09 |
October | 0.629366E+09 | 0.474780E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221703E+09 |
November | 0.623221E+09 | 0.515425E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395042E+09 |
December | 0.607235E+09 | 0.529388E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631508E+09 |
Annual Sum or Average | 0.755252E+10 | 0.553820E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11815211.61 | 0.361104E+10 |
Minimum of Months | 0.570983E+09 | 0.399619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68086133.95 |
Maximum of Months | 0.682256E+09 | 0.531948E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4854379.11 | 0.631508E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.865145E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478049E+09 |
February | 0.901968E+09 | 0.698428E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412031E+09 |
March | 0.107774E+10 | 0.779736E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279607E+09 |
April | 0.956342E+09 | 0.655414E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1295475.82 | 0.255092E+09 |
May | 0.103597E+10 | 0.680697E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 874528.99 | 0.124976E+09 |
June | 0.103308E+10 | 0.672446E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3938715.36 | 68347769.07 |
July | 0.959235E+09 | 0.631133E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4393106.75 | 51074647.55 |
August | 0.107774E+10 | 0.727444E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432277.26 | 72878542.62 |
September | 0.956342E+09 | 0.672358E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43189.89 | 0.128101E+09 |
October | 0.994195E+09 | 0.756356E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190376E+09 |
November | 0.984487E+09 | 0.835987E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335133E+09 |
December | 0.959235E+09 | 0.861807E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512749E+09 |
Annual Sum or Average | 0.119305E+11 | 0.883695E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11977294.06 | 0.290841E+10 |
Minimum of Months | 0.901968E+09 | 0.631133E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51074647.55 |
Maximum of Months | 0.107774E+10 | 0.865145E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4393106.75 | 0.512749E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.530619E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319696E+09 |
February | 0.571020E+09 | 0.436514E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277627E+09 |
March | 0.682301E+09 | 0.489237E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189941E+09 |
April | 0.605444E+09 | 0.415009E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 532875.08 | 0.179246E+09 |
May | 0.655854E+09 | 0.434596E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 580609.30 | 88824343.06 |
June | 0.654023E+09 | 0.429653E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2294670.25 | 48699778.32 |
July | 0.607275E+09 | 0.402941E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2708371.02 | 35598093.35 |
August | 0.682301E+09 | 0.461450E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 878184.86 | 52417129.09 |
September | 0.605444E+09 | 0.424445E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28793.13 | 88520131.60 |
October | 0.629407E+09 | 0.470130E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129602E+09 |
November | 0.623262E+09 | 0.518142E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224825E+09 |
December | 0.607275E+09 | 0.529186E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342259E+09 |
Annual Sum or Average | 0.755301E+10 | 0.554192E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7023503.63 | 0.197725E+10 |
Minimum of Months | 0.571020E+09 | 0.402941E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35598093.35 |
Maximum of Months | 0.682301E+09 | 0.530619E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2708371.02 | 0.342259E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.812432E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100140E+11 |
February | 0.901968E+09 | 0.675068E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772507E+10 |
March | 0.107774E+10 | 0.769121E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737808E+10 |
April | 0.956342E+09 | 0.656828E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42757.42 | 0.423492E+10 |
May | 0.103597E+10 | 0.686175E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103563E+09 | 0.211707E+10 |
June | 0.103308E+10 | 0.677828E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236831E+09 | 0.104054E+10 |
July | 0.959235E+09 | 0.635736E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219242E+09 | 0.723749E+09 |
August | 0.107774E+10 | 0.729914E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120634E+09 | 0.128202E+10 |
September | 0.956342E+09 | 0.669883E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5073403.54 | 0.248853E+10 |
October | 0.994195E+09 | 0.734312E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417262E+10 |
November | 0.984487E+09 | 0.796407E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551087E+10 |
December | 0.959235E+09 | 0.812722E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871741E+10 |
Annual Sum or Average | 0.119305E+11 | 0.865643E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685386E+09 | 0.554049E+11 |
Minimum of Months | 0.901968E+09 | 0.635736E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723749E+09 |
Maximum of Months | 0.107774E+10 | 0.812722E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236831E+09 | 0.100140E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.530502E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319881E+09 |
February | 0.570983E+09 | 0.433064E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278427E+09 |
March | 0.682256E+09 | 0.490087E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191095E+09 |
April | 0.605404E+09 | 0.414619E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5724.03 | 0.178862E+09 |
May | 0.655811E+09 | 0.431434E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 572002.00 | 90092842.66 |
June | 0.653980E+09 | 0.425622E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2302807.55 | 48111234.75 |
July | 0.607235E+09 | 0.399272E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2654876.56 | 37786581.48 |
August | 0.682256E+09 | 0.461194E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 882614.94 | 52945530.64 |
September | 0.605404E+09 | 0.425502E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28793.62 | 89234536.01 |
October | 0.629366E+09 | 0.473621E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129802E+09 |
November | 0.623221E+09 | 0.514044E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224719E+09 |
December | 0.607235E+09 | 0.527627E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342567E+09 |
Annual Sum or Average | 0.755252E+10 | 0.552659E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6446818.70 | 0.198352E+10 |
Minimum of Months | 0.570983E+09 | 0.399272E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37786581.48 |
Maximum of Months | 0.682256E+09 | 0.530502E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2654876.56 | 0.342567E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.869384E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749469E+09 |
February | 0.901968E+09 | 0.701167E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647686E+09 |
March | 0.107774E+10 | 0.782402E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447437E+09 |
April | 0.956342E+09 | 0.656426E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 812871.97 | 0.422734E+09 |
May | 0.103597E+10 | 0.681033E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1325956.28 | 0.212773E+09 |
June | 0.103308E+10 | 0.672855E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5063189.66 | 0.115794E+09 |
July | 0.959235E+09 | 0.631432E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6174715.90 | 84966900.44 |
August | 0.107774E+10 | 0.728476E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084913.08 | 0.116721E+09 |
September | 0.956342E+09 | 0.673592E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66170.76 | 0.199923E+09 |
October | 0.994195E+09 | 0.759121E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293059E+09 |
November | 0.984487E+09 | 0.841279E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515028E+09 |
December | 0.959235E+09 | 0.867130E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799490E+09 |
Annual Sum or Average | 0.119305E+11 | 0.886430E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15527817.64 | 0.460508E+10 |
Minimum of Months | 0.901968E+09 | 0.631432E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84966900.44 |
Maximum of Months | 0.107774E+10 | 0.869384E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6174715.90 | 0.799490E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.532118E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499962E+09 |
February | 0.421807E+09 | 0.437551E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434967E+09 |
March | 0.502994E+09 | 0.490400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302024E+09 |
April | 0.447140E+09 | 0.415442E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 634734.90 | 0.287891E+09 |
May | 0.484071E+09 | 0.435035E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886217.08 | 0.144130E+09 |
June | 0.482240E+09 | 0.430056E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3421190.48 | 77904891.62 |
July | 0.448971E+09 | 0.403324E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4188945.13 | 56282054.27 |
August | 0.502994E+09 | 0.462223E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1375272.93 | 79624574.95 |
September | 0.447140E+09 | 0.425109E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44109.51 | 0.133867E+09 |
October | 0.465148E+09 | 0.471505E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196426E+09 |
November | 0.460569E+09 | 0.519600E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344210E+09 |
December | 0.448971E+09 | 0.530526E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533043E+09 |
Annual Sum or Average | 0.557719E+10 | 0.555289E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10550470.03 | 0.309033E+10 |
Minimum of Months | 0.421807E+09 | 0.403324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56282054.27 |
Maximum of Months | 0.502994E+09 | 0.532118E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4188945.13 | 0.533043E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.814817E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761182E+09 |
February | 0.901968E+09 | 0.675798E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676342E+09 |
March | 0.107774E+10 | 0.770710E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467349E+09 |
April | 0.956342E+09 | 0.657694E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16785.68 | 0.442939E+09 |
May | 0.103597E+10 | 0.686747E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1325349.66 | 0.216804E+09 |
June | 0.103308E+10 | 0.678696E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4967615.25 | 0.115905E+09 |
July | 0.959235E+09 | 0.636635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5938838.03 | 85700690.93 |
August | 0.107774E+10 | 0.730996E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2022542.64 | 0.122481E+09 |
September | 0.956342E+09 | 0.670850E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64007.71 | 0.209997E+09 |
October | 0.994195E+09 | 0.735471E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307086E+09 |
November | 0.984487E+09 | 0.798187E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531219E+09 |
December | 0.959235E+09 | 0.814752E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812770E+09 |
Annual Sum or Average | 0.119305E+11 | 0.867135E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14335138.96 | 0.474978E+10 |
Minimum of Months | 0.901968E+09 | 0.636635E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85700690.93 |
Maximum of Months | 0.107774E+10 | 0.814817E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5938838.03 | 0.812770E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.531948E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500291E+09 |
February | 0.570983E+09 | 0.434154E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436751E+09 |
March | 0.682256E+09 | 0.491353E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304105E+09 |
April | 0.605404E+09 | 0.415467E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288477E+09 |
May | 0.655811E+09 | 0.431725E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 883988.28 | 0.145840E+09 |
June | 0.653980E+09 | 0.425951E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3445574.16 | 78060086.54 |
July | 0.607235E+09 | 0.399619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4056217.95 | 58849728.61 |
August | 0.682256E+09 | 0.461955E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1392977.98 | 80315581.01 |
September | 0.605404E+09 | 0.426428E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44104.00 | 0.135004E+09 |
October | 0.629366E+09 | 0.474780E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197252E+09 |
November | 0.623221E+09 | 0.515425E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344454E+09 |
December | 0.607235E+09 | 0.529388E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533407E+09 |
Annual Sum or Average | 0.755252E+10 | 0.553819E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9822862.37 | 0.310281E+10 |
Minimum of Months | 0.570983E+09 | 0.399619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58849728.61 |
Maximum of Months | 0.682256E+09 | 0.531948E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4056217.95 | 0.533407E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993753E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883597E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608913E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582209.11 | 0.584424E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1142679.59 | 0.285478E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5735525.84 | 0.154994E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6563487.49 | 0.113938E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1753107.18 | 0.161594E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36192.78 | 0.279103E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414257E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718774E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107411E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15813201.99 | 0.627294E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113938E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6563487.49 | 0.107411E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125367E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110132E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763895E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 889060.18 | 0.728848E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1487465.07 | 0.363276E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7357867.32 | 0.196710E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8492199.77 | 0.143908E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2311553.07 | 0.202082E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47854.41 | 0.344731E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500874E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878202E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134515E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20585999.82 | 0.782267E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143908E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8492199.77 | 0.134515E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132823E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115369E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798467E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15397.89 | 0.753081E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044711.05 | 0.384596E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6738249.82 | 0.208857E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6085039.18 | 0.153528E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1763909.04 | 0.213513E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16448.96 | 0.356217E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506996E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894096E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141066E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15663755.94 | 0.816193E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153528E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6738249.82 | 0.141066E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1600.81 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1903.91 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 979.09 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 | 23-APR-15:51 | 774.79 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 24-MAY-15:00 | 430.39 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.05 | 29-JUN-21:03 | 282.92 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.65 | 23-JUL-14:56 | 287.54 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 08-AUG-16:00 | 370.61 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | 01-SEP-15:00 | 477.28 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 652.86 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1046.36 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1572.02 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.92 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.65 | 1903.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1079.46 | 04-JAN-05:58 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1268.83 | 12-FEB-22:52 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 03-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 652.71 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 450.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.92 | 23-APR-16:10 | 534.67 | 16-APR-12:00 |
May | 827.22 | 01-MAY-09:09 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 24-MAY-15:00 | 297.18 | 14-MAY-08:20 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.01 | 24-JUN-17:02 | 186.55 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 25-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 23-JUL-14:58 | 187.72 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 08-AUG-16:00 | 249.65 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 01-SEP-15:00 | 314.13 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 435.07 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 692.54 | 22-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1048.00 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.55 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 1268.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1619.21 | 04-JAN-05:58 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 02-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1906.67 | 12-FEB-22:52 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 979.08 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 23-APR-16:05 | 905.32 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 | 24-MAY-15:00 | 436.52 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.79 | 29-JUN-21:03 | 282.25 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.25 | 23-JUL-14:56 | 288.47 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 08-AUG-16:00 | 377.65 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 01-SEP-15:00 | 477.21 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 653.49 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1045.61 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1572.03 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.25 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 118.25 | 1906.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1079.45 | 04-JAN-05:58 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1269.09 | 12-FEB-22:52 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 652.77 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 519.89 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 24-MAY-15:00 | 293.04 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 29-JUN-16:00 | 188.07 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 | 23-JUL-14:56 | 213.45 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 08-AUG-16:00 | 252.78 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 01-SEP-15:00 | 313.02 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 434.93 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 691.18 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1048.02 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.07 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 | 1269.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 859.96 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1028.87 | 12-FEB-22:58 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 519.91 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 | 23-APR-16:00 | 418.98 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 24-MAY-15:00 | 218.43 | 20-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.15 | 24-JUN-17:02 | 148.43 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.85 | 23-JUL-15:00 | 152.25 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 08-AUG-16:00 | 206.30 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 01-SEP-15:00 | 277.23 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 349.73 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 616.38 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 834.55 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 | 1028.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 573.30 | 04-JAN-05:58 |
February | 827.22 | 01-FEB-10:09 | 860.01 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 685.32 | 12-FEB-22:58 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 03-MAR-16:49 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 346.60 | 15-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 450.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.01 | 23-APR-16:00 | 283.25 | 01-APR-19:00 |
May | 827.22 | 01-MAY-09:09 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 24-MAY-15:00 | 148.99 | 08-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 | 24-JUN-17:02 | 101.41 | 20-JUN-04:00 |
July | 827.22 | 03-JUL-09:09 | 450.21 | 25-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 23-JUL-15:00 | 104.21 | 06-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 600.14 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 08-AUG-16:00 | 144.89 | 27-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 600.14 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 01-SEP-15:00 | 183.29 | 20-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 233.12 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 408.38 | 22-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 556.36 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 50.01 | 685.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 49352.59 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 02-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 47511.09 | 14-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37847.87 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 | 23-APR-17:50 | 29059.22 | 05-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3971.88 | 25-MAY-17:00 | 19830.64 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 30-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8113.68 | 29-JUN-16:10 | 9825.48 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4057.47 | 28-JUL-16:10 | 8711.80 | 18-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4937.81 | 08-AUG-16:10 | 10689.39 | 25-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.10 | 01-SEP-16:10 | 15676.80 | 06-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 25378.39 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 33556.48 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 43693.10 | 20-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8711.80 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8113.68 | 49352.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 573.30 | 04-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 683.73 | 12-FEB-22:58 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 13-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 346.62 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 490.17 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 23-APR-14:02 | 286.40 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 24-MAY-15:00 | 148.08 | 20-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 29-JUN-16:00 | 100.82 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 | 23-JUL-14:56 | 120.41 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 08-AUG-16:00 | 148.48 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 640.09 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 01-SEP-15:00 | 183.98 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 232.99 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 407.97 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 556.36 | 16-DEC-05:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.82 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.16 | 683.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1347.11 | 04-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1606.44 | 12-FEB-22:54 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 814.49 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.54 | 23-APR-15:50 | 681.70 | 01-APR-19:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 24-MAY-15:00 | 359.41 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 30-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 | 24-JUN-17:02 | 246.99 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 647.98 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 | 23-JUL-14:50 | 245.26 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 08-AUG-16:00 | 325.74 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 01-SEP-15:00 | 422.92 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 546.62 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 935.74 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1307.57 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.26 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 | 1606.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 898.07 | 04-JAN-05:58 |
February | 805.43 | 01-FEB-08:09 | 860.01 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1070.91 | 12-FEB-22:54 |
March | 805.43 | 01-MAR-08:09 | 750.07 | 03-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 542.99 | 15-MAR-05:00 |
April | 805.43 | 03-APR-07:10 | 450.21 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 23-APR-15:50 | 469.72 | 16-APR-12:00 |
May | 805.43 | 01-MAY-07:10 | 410.22 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 24-MAY-15:00 | 257.32 | 14-MAY-07:50 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 24-JUN-17:02 | 163.00 | 20-JUN-04:00 |
July | 805.43 | 03-JUL-07:10 | 450.21 | 25-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.00 | 23-JUL-14:46 | 160.61 | 06-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 600.14 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 08-AUG-16:00 | 219.19 | 27-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 600.14 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 01-SEP-15:00 | 278.43 | 20-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 860.01 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 364.24 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 618.54 | 22-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 871.71 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.61 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 1070.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1347.11 | 04-JAN-05:55 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 02-FEB-16:49 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1604.72 | 12-FEB-22:54 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 03-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 814.52 | 15-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 774.31 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 23-APR-15:46 | 794.51 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 647.98 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 24-MAY-15:00 | 363.31 | 29-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 774.31 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 24-JUN-17:02 | 246.69 | 20-JUN-04:00 |
July | 1306.65 | 03-JUL-09:09 | 711.15 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 | 23-JUL-14:44 | 247.09 | 06-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 08-AUG-16:00 | 331.53 | 27-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 19-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 01-SEP-15:00 | 423.19 | 20-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 26-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 547.22 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 934.92 | 22-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1307.59 | 16-DEC-05:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.69 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 | 1604.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 898.08 | 04-JAN-05:58 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1070.65 | 12-FEB-22:54 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 03-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 543.00 | 15-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 456.40 | 01-APR-19:00 |
May | 827.17 | 01-MAY-09:09 | 450.19 | 12-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 24-MAY-15:00 | 243.48 | 29-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 490.17 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.73 | 29-JUN-16:00 | 164.35 | 20-JUN-04:00 |
July | 827.17 | 03-JUL-09:09 | 450.19 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 | 23-JUL-14:44 | 181.49 | 06-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 08-AUG-16:00 | 221.93 | 27-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 750.02 | 19-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 01-SEP-15:00 | 278.21 | 20-SEP-01:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 26-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 364.16 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 617.66 | 22-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 871.71 | 16-DEC-05:54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.35 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 | 1070.65 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1708.13 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2227.92 | 12-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1082.48 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 | 23-APR-16:00 | 955.74 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 24-MAY-15:00 | 488.60 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 | 24-JUN-17:02 | 333.44 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.98 | 23-JUL-15:00 | 323.72 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 | 08-AUG-16:00 | 449.53 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 01-SEP-15:00 | 586.65 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 727.89 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1334.22 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1728.32 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.98 | 2227.92 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2183.38 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2732.09 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1366.10 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.37 | 23-APR-16:00 | 1186.54 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 24-MAY-15:00 | 619.92 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.59 | 24-JUN-17:02 | 424.89 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 23-JUL-15:00 | 412.82 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 08-AUG-16:00 | 565.32 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 01-SEP-15:00 | 733.87 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 899.21 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1637.22 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2162.90 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 | 2732.09 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2313.31 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2828.15 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1408.80 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 23-APR-15:51 | 1202.96 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 24-MAY-15:00 | 679.13 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.59 | 29-JUN-16:00 | 419.57 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.67 | 15-JUL-17:03 | 407.42 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 | 08-AUG-16:00 | 562.62 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 01-SEP-15:50 | 723.46 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 964.61 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1594.82 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2231.26 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.67 | 2828.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7962.02 | 06-JAN-08:53 | 18105.02 | 19331.93 | 42059.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9795.74 | 08-FEB-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14627.18 | 31-MAR-16:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25003.46 | 19-APR-05:03 | 2541.06 | 846.94 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41569.07 | 30-MAY-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42744.78 | 30-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41763.45 | 31-JUL-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40103.10 | 26-AUG-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40621.72 | 05-SEP-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36591.77 | 23-OCT-06:01 | 8893.70 | 15036.15 | 71363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14137.26 | 17-NOV-16:20 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9284.45 | 01-DEC-15:20 | 6035.01 | 6443.98 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7962.02 | 0.00 | 846.94 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42744.78 | 18105.02 | 19331.93 | 71363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.11 |
February | 675.40 | 04-FEB-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.18 |
March | 1780.28 | 31-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.61 |
April | 5043.98 | 13-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 |
May | 9653.46 | 18-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 |
June | 10964.40 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 0.00 |
July | 10449.22 | 24-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
August | 9531.51 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 0.00 |
September | 8193.56 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 0.00 |
October | 3687.53 | 20-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.41 |
November | 1082.90 | 01-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 840.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10964.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 840.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3918.09 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.84 |
February | 4296.63 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3578.95 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 673.16 |
April | 2968.21 | 26-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.00 |
May | 4362.27 | 18-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 0.00 |
June | 5338.31 | 30-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.51 | 0.00 |
July | 6156.66 | 24-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 |
August | 4496.67 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 0.00 |
September | 4349.33 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 | 0.00 |
October | 3009.48 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3077.04 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.02 |
December | 3838.05 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2968.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6156.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 708.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3875.46 | 26-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.73 |
February | 3893.49 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3764.64 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.93 |
April | 3591.09 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4462.22 | 18-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
June | 5433.00 | 30-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 | 0.00 |
July | 6390.39 | 24-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 |
August | 5056.47 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 | 0.00 |
September | 4639.24 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 0.00 |
October | 2777.72 | 06-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 |
November | 2149.69 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.16 |
December | 3654.76 | 01-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2149.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6390.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 | 530.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6221.03 | 27-JAN-16:30 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6728.42 | 08-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7627.11 | 29-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12526.72 | 14-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32597.06 | 30-MAY-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30651.52 | 30-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33240.73 | 31-JUL-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30180.95 | 28-AUG-06:02 | 6352.64 | 10740.11 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29655.53 | 05-SEP-06:01 | 11434.75 | 19332.19 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12798.34 | 20-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7324.24 | 17-NOV-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6263.29 | 01-DEC-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6221.03 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33240.73 | 11434.75 | 19332.19 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5893.69 | 27-JAN-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6698.65 | 08-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7557.59 | 29-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12304.61 | 13-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18469.49 | 18-MAY-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33852.44 | 30-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28459.66 | 24-JUL-06:03 | 3811.58 | 6444.06 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18557.13 | 08-AUG-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18026.04 | 01-SEP-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12052.48 | 20-OCT-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7060.12 | 17-NOV-16:20 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5750.88 | 28-DEC-15:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5750.88 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33852.44 | 6035.01 | 6444.06 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 983.05 | 28-JAN-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.64 |
February | 1086.56 | 08-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.18 |
March | 1402.53 | 31-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 |
April | 3014.07 | 18-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.46 |
May | 5936.28 | 18-MAY-14:50 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 | 0.00 |
June | 8209.61 | 29-JUN-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
July | 10462.95 | 23-JUL-16:12 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 0.00 |
August | 6142.34 | 08-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 | 0.00 |
September | 5133.18 | 01-SEP-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 0.00 |
October | 2004.18 | 20-OCT-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 |
November | 1382.27 | 01-NOV-15:50 | 1272.23 | 774.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 |
December | 989.67 | 30-DEC-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 983.05 | 334.80 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10462.95 | 1306.65 | 774.31 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 189.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1080.25 | 21-JAN-17:02 | 211.95 | 238.89 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.30 |
February | 1501.31 | 28-FEB-10:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.48 |
March | 2967.25 | 31-MAR-09:35 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.07 |
April | 7115.88 | 18-APR-09:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 |
May | 15412.51 | 21-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.05 |
June | 16184.54 | 25-JUN-08:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 |
July | 16068.35 | 23-JUL-09:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
August | 13282.84 | 06-AUG-08:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.28 |
September | 8721.97 | 01-SEP-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 |
October | 4229.01 | 19-OCT-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 |
November | 1513.44 | 16-NOV-09:55 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 |
December | 1083.70 | 30-DEC-17:02 | 211.95 | 238.89 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1080.25 | 211.95 | 113.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | |
Maximum of Months | 16184.54 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6902.52 | 27-JAN-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9964.84 | 28-FEB-13:50 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 |
March | 10560.30 | 31-MAR-13:50 | 2613.31 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 |
April | 18223.84 | 23-APR-14:02 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 |
May | 18943.19 | 21-MAY-14:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.37 |
June | 16339.73 | 25-JUN-11:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
July | 20112.67 | 23-JUL-12:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 | 0.00 |
August | 20377.01 | 27-AUG-14:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.37 |
September | 20330.53 | 04-SEP-12:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.09 |
October | 20498.66 | 22-OCT-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.66 |
November | 8990.37 | 17-NOV-13:03 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.29 |
December | 4126.54 | 20-DEC-13:25 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4126.54 | 334.80 | 179.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20498.66 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 39.77 | 303.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1588.88 | 27-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2542.82 | 08-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.04 |
March | 5267.15 | 31-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 |
April | 17316.42 | 23-APR-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 |
May | 18976.15 | 14-MAY-17:01 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.23 |
June | 17156.00 | 17-JUN-17:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 |
July | 17587.12 | 16-JUL-16:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 |
August | 17529.70 | 27-AUG-15:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 |
September | 14571.76 | 03-SEP-17:12 | 0.00 | 113.94 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 |
October | 5792.68 | 19-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
November | 1874.91 | 17-NOV-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 |
December | 1183.97 | 02-DEC-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1183.97 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18976.15 | 805.38 | 410.20 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 971.62 | 21-JAN-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 |
February | 975.78 | 11-FEB-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
March | 1154.75 | 31-MAR-16:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 |
April | 1837.10 | 23-APR-17:42 | 0.00 | 215.99 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 65.56 | 0.00 |
May | 3809.36 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 |
June | 5362.49 | 29-JUN-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.26 | 0.00 |
July | 6632.66 | 24-JUL-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
August | 5109.66 | 09-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
September | 4266.61 | 01-SEP-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
October | 2009.48 | 22-OCT-16:03 | 267.84 | 172.07 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 |
November | 1374.01 | 01-NOV-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 |
December | 981.77 | 30-DEC-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 971.62 | 0.00 | 172.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6632.66 | 1306.65 | 711.15 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 65.56 | 121.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 882.35 | 21-JAN-17:02 | 211.95 | 238.89 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 |
February | 1067.18 | 28-FEB-10:25 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
March | 1415.83 | 31-MAR-09:45 | 1654.44 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.68 |
April | 4236.56 | 18-APR-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
May | 6333.15 | 18-MAY-09:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 0.00 |
June | 12593.41 | 25-JUN-08:31 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 |
July | 11028.06 | 23-JUL-10:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 0.00 |
August | 13032.00 | 20-AUG-09:11 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.22 |
September | 6976.99 | 10-SEP-10:02 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 |
October | 3209.36 | 19-OCT-08:35 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 |
November | 1263.94 | 17-NOV-10:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 |
December | 914.99 | 01-DEC-09:35 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 882.35 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13032.00 | 1654.44 | 820.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 88.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1454.00 | 21-JAN-12:00 | 401.76 | 216.00 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 |
February | 2678.82 | 28-FEB-14:55 | 2613.31 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.96 |
March | 3301.96 | 31-MAR-14:30 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.41 |
April | 9816.81 | 23-APR-14:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.24 |
May | 10763.30 | 18-MAY-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2941.93 | 0.00 |
June | 13829.58 | 29-JUN-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8113.68 | 0.00 |
July | 14116.29 | 23-JUL-13:32 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 0.00 |
August | 16991.05 | 13-AUG-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.70 |
September | 16664.29 | 03-SEP-13:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.46 |
October | 16364.27 | 22-OCT-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.86 |
November | 6827.95 | 17-NOV-13:07 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1543.92 |
December | 2721.96 | 02-DEC-13:40 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1454.00 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16991.05 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 8113.68 | 2022.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1203.94 | 27-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1524.80 | 08-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 |
March | 3230.75 | 28-MAR-17:20 | 84.78 | 136.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
April | 13070.12 | 23-APR-17:42 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 |
May | 12491.53 | 14-MAY-17:52 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.28 |
June | 13410.62 | 17-JUN-18:22 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
July | 13416.09 | 23-JUL-16:12 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 0.00 |
August | 14085.03 | 13-AUG-18:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 |
September | 14663.36 | 03-SEP-17:41 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 |
October | 4835.04 | 19-OCT-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
November | 1527.52 | 17-NOV-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.05 |
December | 958.62 | 02-DEC-17:02 | 254.33 | 286.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 958.62 | 0.00 | 136.73 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14663.36 | 805.38 | 410.20 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 65.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 970.46 | 28-JAN-17:02 | 401.76 | 452.80 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.16 |
February | 1095.39 | 08-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.37 |
March | 1423.89 | 29-MAR-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.96 |
April | 2949.10 | 18-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.83 |
May | 5591.87 | 26-MAY-13:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 |
June | 8493.96 | 28-JUN-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10123.67 | 23-JUL-16:41 | 602.64 | 323.98 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
August | 5763.65 | 09-AUG-15:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
September | 4837.87 | 01-SEP-15:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.52 | 0.00 |
October | 2220.51 | 20-OCT-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 |
November | 1404.78 | 01-NOV-15:30 | 1272.23 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 |
December | 976.21 | 30-DEC-17:02 | 334.80 | 377.34 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 970.46 | 334.80 | 323.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10123.67 | 1306.65 | 711.15 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 158.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1173.17 | 25-JAN-10:00 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.86 |
February | 1624.85 | 28-FEB-09:55 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.81 |
March | 3670.70 | 31-MAR-08:55 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.39 |
April | 7576.12 | 19-APR-08:30 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.44 |
May | 11878.59 | 21-MAY-08:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 |
June | 17744.90 | 25-JUN-08:61 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.36 |
July | 17181.07 | 23-JUL-10:01 | 339.13 | 182.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
August | 16987.58 | 20-AUG-09:11 | 296.74 | 159.53 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.56 |
September | 12881.15 | 04-SEP-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.16 |
October | 5616.89 | 22-OCT-09:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.48 |
November | 1675.31 | 16-NOV-09:45 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 |
December | 1210.77 | 01-DEC-10:00 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1173.17 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | |
Maximum of Months | 17744.90 | 1610.86 | 820.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7732.84 | 27-JAN-13:40 | 1272.23 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10306.98 | 28-FEB-13:35 | 2544.47 | 1295.96 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.48 |
March | 16621.64 | 26-MAR-13:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.33 |
April | 18610.85 | 23-APR-13:42 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.41 |
May | 18018.47 | 21-MAY-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 |
June | 19184.90 | 25-JUN-11:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
July | 19911.31 | 23-JUL-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 0.00 |
August | 20625.85 | 13-AUG-13:21 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.99 |
September | 20955.84 | 04-SEP-11:41 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.16 |
October | 21194.02 | 22-OCT-13:51 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.12 |
November | 9830.16 | 17-NOV-13:03 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.48 |
December | 5187.33 | 02-DEC-13:20 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5187.33 | 133.92 | 107.99 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21194.02 | 8905.63 | 4535.85 | 10046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 317.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1594.33 | 27-JAN-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2684.17 | 08-FEB-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 |
March | 5710.99 | 26-MAR-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.37 |
April | 16354.76 | 23-APR-16:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 |
May | 16136.11 | 14-MAY-17:12 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.18 |
June | 16153.35 | 17-JUN-17:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 |
July | 17700.60 | 23-JUL-16:41 | 381.49 | 205.09 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
August | 16681.45 | 13-AUG-18:02 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 |
September | 17374.02 | 03-SEP-17:41 | 0.00 | 159.52 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.86 |
October | 7157.90 | 22-OCT-15:53 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 |
November | 1873.25 | 17-NOV-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 |
December | 1286.61 | 20-DEC-15:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1286.61 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17700.60 | 805.38 | 410.20 | 2725.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.37 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.112714E+12 | 98530.73 | 02-JAN-08:09 | 0.202609E+12 | 371219.92 | 09-JAN-07:49 |
February | 0.993263E+11 | 86569.74 | 02-FEB-16:00 | 0.108869E+12 | 351763.63 | 14-FEB-07:19 |
March | 0.112463E+12 | 85840.80 | 03-MAR-16:00 | 0.708306E+11 | 254980.33 | 15-MAR-06:00 |
April | 0.102168E+12 | 99138.70 | 13-APR-15:20 | 0.175764E+11 | 144877.36 | 03-APR-06:10 |
May | 0.120275E+12 | 146670.58 | 18-MAY-15:20 | 0.176729E+10 | 85158.67 | 01-MAY-06:10 |
June | 0.136820E+12 | 171417.30 | 29-JUN-15:39 | 0.260530E+09 | 18152.99 | 02-JUN-06:19 |
July | 0.146054E+12 | 184798.47 | 05-JUL-10:00 | 37330678.04 | 7147.64 | 10-JUL-06:19 |
August | 0.141159E+12 | 160287.45 | 08-AUG-15:50 | 0.150099E+09 | 21754.26 | 18-AUG-06:19 |
September | 0.107843E+12 | 144212.22 | 01-SEP-15:50 | 0.157870E+10 | 38158.54 | 29-SEP-06:10 |
October | 0.106455E+12 | 102394.53 | 19-OCT-15:20 | 0.160704E+11 | 155062.03 | 30-OCT-06:10 |
November | 0.106353E+12 | 92984.65 | 10-NOV-16:49 | 0.593938E+11 | 198148.65 | 27-NOV-07:19 |
December | 0.110392E+12 | 97862.43 | 26-DEC-08:09 | 0.167170E+12 | 344113.37 | 26-DEC-08:09 |
Annual Sum or Average | 0.140202E+13 | 0.646313E+12 | ||||
Minimum of Months | 0.993263E+11 | 85840.80 | 37330678.04 | 7147.64 | ||
Maximum of Months | 0.146054E+12 | 184798.47 | 0.202609E+12 | 371219.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.262290E+11 | 0.637348E+10 | 0.605851E+11 | 0.225895E+10 | 0.685332E+10 | 0.114465E+10 | 0.00 | 3782378.70 | 0.00 | 0.00 | 0.351878E+10 | 0.574686E+10 | 0.00 |
February | 0.230647E+11 | 0.495648E+10 | 0.548702E+11 | 0.204969E+10 | 0.520348E+10 | 0.642957E+09 | 0.00 | 11100323.05 | 0.00 | 0.00 | 0.320068E+10 | 0.532699E+10 | 0.00 |
March | 0.270404E+11 | 0.444818E+10 | 0.627783E+11 | 0.235658E+10 | 0.545611E+10 | 0.433448E+09 | 0.00 | 21773191.96 | 0.00 | 0.00 | 0.366726E+10 | 0.626084E+10 | 0.00 |
April | 0.237526E+11 | 0.339353E+10 | 0.586172E+11 | 0.219321E+10 | 0.561927E+10 | 0.109116E+09 | 0.00 | 0.106840E+10 | 0.00 | 0.00 | 0.193078E+10 | 0.548334E+10 | 0.00 |
May | 0.254201E+11 | 0.285786E+10 | 0.616817E+11 | 0.230701E+10 | 0.991752E+10 | 25560414.88 | 0.00 | 0.118564E+11 | 0.00 | 0.00 | 0.617138E+09 | 0.559190E+10 | 0.00 |
June | 0.252649E+11 | 0.248541E+10 | 0.604966E+11 | 0.226921E+10 | 0.137086E+11 | 14271120.23 | 0.00 | 0.267514E+11 | 0.00 | 0.00 | 0.592997E+09 | 0.523695E+10 | 0.00 |
July | 0.236056E+11 | 0.268901E+10 | 0.597911E+11 | 0.222998E+10 | 0.165681E+11 | 12494607.40 | 0.00 | 0.354068E+11 | 0.00 | 0.00 | 0.104224E+10 | 0.470876E+10 | 0.00 |
August | 0.265895E+11 | 0.318424E+10 | 0.627783E+11 | 0.235614E+10 | 0.136260E+11 | 13602904.38 | 0.00 | 0.270231E+11 | 0.00 | 0.00 | 0.542492E+09 | 0.504550E+10 | 0.00 |
September | 0.239048E+11 | 0.386337E+10 | 0.585950E+11 | 0.219210E+10 | 0.829140E+10 | 24599897.39 | 0.00 | 0.617688E+10 | 0.00 | 0.00 | 0.215182E+09 | 0.457986E+10 | 0.00 |
October | 0.253102E+11 | 0.503950E+10 | 0.605962E+11 | 0.225949E+10 | 0.536721E+10 | 97034784.34 | 0.00 | 0.888156E+09 | 0.00 | 0.00 | 0.199175E+10 | 0.490545E+10 | 0.00 |
November | 0.258088E+11 | 0.586930E+10 | 0.591197E+11 | 0.220159E+10 | 0.474716E+10 | 0.347217E+09 | 0.00 | 0.143695E+09 | 0.00 | 0.00 | 0.302311E+10 | 0.509231E+10 | 0.00 |
December | 0.256097E+11 | 0.663618E+10 | 0.597800E+11 | 0.223025E+10 | 0.630860E+10 | 0.994262E+09 | 0.00 | 6580392.91 | 0.00 | 0.00 | 0.347957E+10 | 0.534709E+10 | 0.00 |
Annual Sum or Average | 0.301600E+12 | 0.517965E+11 | 0.719689E+12 | 0.269042E+11 | 0.101667E+12 | 0.385921E+10 | 0.00 | 0.109358E+12 | 0.00 | 0.00 | 0.238220E+11 | 0.633259E+11 | 0.00 |
Minimum of Months | 0.230647E+11 | 0.248541E+10 | 0.548702E+11 | 0.204969E+10 | 0.474716E+10 | 12494607.40 | 0.00 | 3782378.70 | 0.00 | 0.00 | 0.215182E+09 | 0.457986E+10 | 0.00 |
Maximum of Months | 0.270404E+11 | 0.663618E+10 | 0.627783E+11 | 0.235658E+10 | 0.165681E+11 | 0.114465E+10 | 0.00 | 0.354068E+11 | 0.00 | 0.00 | 0.366726E+10 | 0.626084E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.202609E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108869E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.708306E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.175764E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.176729E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.260530E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 37330678.04 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.150099E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.157870E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.160704E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.593938E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.167170E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.646313E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 37330678.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.202609E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:20 | 9094.22 | 02-JAN-06:19 | 1223.81 | 09-JAN-07:49 | 0.00 | 01-JAN-00:10 |
February | 31270.78 | 02-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-12:20 | 8101.05 | 27-FEB-07:10 | 1184.72 | 14-FEB-07:19 | 0.00 | 01-FEB-00:10 |
March | 30831.04 | 03-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 03-MAR-12:20 | 7990.70 | 06-MAR-06:10 | 1009.52 | 15-MAR-06:00 | 0.00 | 01-MAR-00:10 |
April | 27018.85 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-16:10 | 10566.94 | 13-APR-15:20 | 848.10 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 25801.04 | 12-MAY-07:10 | 3328.83 | 01-MAY-19:30 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 26107.72 | 18-MAY-14:00 | 423.10 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 26798.99 | 30-JUN-07:10 | 3328.83 | 01-JUN-19:00 | 41699.26 | 01-JUN-07:10 | 1410.29 | 02-JUN-16:10 | 31787.31 | 30-JUN-15:09 | 152.23 | 02-JUN-06:40 | 0.00 | 01-JUN-00:10 |
July | 25927.37 | 03-JUL-07:10 | 3328.83 | 01-JUL-20:19 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 35833.37 | 05-JUL-10:39 | 56.28 | 10-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 28620.49 | 31-AUG-07:10 | 5686.19 | 15-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 18-AUG-16:10 | 29543.24 | 08-AUG-15:00 | 132.34 | 18-AUG-06:19 | 0.00 | 01-AUG-00:10 |
September | 28960.32 | 19-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-07:10 | 26006.70 | 01-SEP-15:50 | 286.40 | 21-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32642.50 | 26-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 11552.47 | 20-OCT-14:00 | 897.66 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 02-NOV-07:10 | 8073.13 | 27-NOV-07:10 | 969.69 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-12:20 | 9094.22 | 26-DEC-06:10 | 1174.84 | 20-DEC-07:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 25801.04 | 3328.83 | 41699.26 | 1410.29 | 7990.70 | 56.28 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 35833.37 | 1223.81 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 519.29 | 03-JAN-07:30 | 0.00 | 0.00 | 2722.67 | 02-JAN-08:50 | 7724.75 | 31-JAN-12:39 | 0.00 |
February | 538.97 | 21-FEB-07:19 | 0.00 | 0.00 | 2722.67 | 01-FEB-17:40 | 7751.02 | 27-FEB-12:00 | 0.00 |
March | 802.72 | 25-MAR-06:10 | 0.00 | 0.00 | 2722.67 | 01-MAR-13:20 | 7749.69 | 01-MAR-12:00 | 0.00 |
April | 16668.79 | 23-APR-16:10 | 0.00 | 0.00 | 2722.67 | 01-APR-16:10 | 7694.67 | 03-APR-11:39 | 0.00 |
May | 45945.12 | 25-MAY-15:00 | 0.00 | 0.00 | 2722.67 | 03-MAY-06:10 | 7247.52 | 01-MAY-11:00 | 0.00 |
June | 66232.86 | 29-JUN-15:00 | 0.00 | 0.00 | 2722.67 | 30-JUN-06:10 | 7056.60 | 01-JUN-11:50 | 0.00 |
July | 75165.20 | 05-JUL-11:50 | 0.00 | 0.00 | 2722.67 | 22-JUL-16:10 | 6656.11 | 03-JUL-11:30 | 0.00 |
August | 57367.63 | 08-AUG-10:09 | 0.00 | 0.00 | 2722.67 | 08-AUG-10:30 | 6254.91 | 01-AUG-11:30 | 0.00 |
September | 44654.66 | 01-SEP-13:20 | 0.00 | 0.00 | 2722.67 | 01-SEP-14:20 | 6268.77 | 29-SEP-11:20 | 0.00 |
October | 18461.71 | 19-OCT-14:00 | 0.00 | 0.00 | 2722.67 | 05-OCT-17:10 | 6692.87 | 31-OCT-11:30 | 0.00 |
November | 7030.56 | 01-NOV-14:00 | 0.00 | 0.00 | 2722.67 | 02-NOV-16:19 | 7153.37 | 30-NOV-12:50 | 0.00 |
December | 631.50 | 30-DEC-07:10 | 0.00 | 0.00 | 2722.67 | 01-DEC-17:40 | 7559.52 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 519.29 | 0.00 | 0.00 | 2722.67 | 6254.91 | 0.00 | |||
Maximum of Months | 75165.20 | 0.00 | 0.00 | 2722.67 | 7751.02 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 98530.73 | 02-JAN-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 9094.22 | 994.34 | 0.00 | 0.00 | 0.00 |
February | 86569.74 | 02-FEB-16:00 | 31270.78 | 41670.51 | 0.00 | 1410.29 | 3202.95 | 435.95 | 0.00 | 0.00 | 0.00 |
March | 85840.80 | 03-MAR-16:00 | 30831.04 | 41670.51 | 0.00 | 1410.29 | 3121.95 | 202.96 | 0.00 | 0.00 | 0.00 |
April | 99138.70 | 13-APR-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 10566.94 | 6.85 | 0.00 | 14018.80 | 0.00 |
May | 146670.58 | 18-MAY-15:20 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 26033.40 | 6.85 | 0.00 | 43573.21 | 0.00 |
June | 171417.30 | 29-JUN-15:39 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 29882.84 | 6.92 | 0.00 | 65028.62 | 0.00 |
July | 184798.47 | 05-JUL-10:00 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 35833.37 | 6.85 | 0.00 | 74810.31 | 0.00 |
August | 160287.45 | 08-AUG-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 29234.56 | 6.93 | 0.00 | 54719.09 | 0.00 |
September | 144212.22 | 01-SEP-15:50 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 26006.70 | 6.87 | 0.00 | 42067.49 | 0.00 |
October | 102394.53 | 19-OCT-15:20 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 10215.02 | 6.85 | 0.00 | 18096.43 | 0.00 |
November | 92984.65 | 10-NOV-16:49 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3466.36 | 22.89 | 0.00 | 0.00 | 0.00 |
December | 97862.43 | 26-DEC-08:09 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 8101.05 | 1127.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 85840.80 | 25681.07 | 41666.76 | 0.00 | 1410.29 | 3121.95 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 184798.47 | 32642.50 | 41699.26 | 5686.19 | 1410.29 | 35833.37 | 1127.96 | 0.00 | 74810.31 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 371219.92 | 09-JAN-07:49 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 351763.63 | 14-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 254980.33 | 15-MAR-06:00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 144877.36 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 85158.67 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18152.99 | 02-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 7147.64 | 10-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 21754.26 | 18-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 38158.54 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 155062.03 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 198148.65 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 344113.37 | 26-DEC-08:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 7147.64 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 371219.92 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 19.42 | 2.67 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.81 | 1.00 | 24.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.89 | 0.33 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
Annual Sum or Average | 3.00 | 19.47 | 3.00 | 19.47 | 1.17 | 20.37 | 1.00 | 20.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.89 | 2.67 | 19.89 | 1.00 | 26.16 | 1.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 19.18 | 5.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
February | 0.17 | 19.26 | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.17 | 19.11 | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.78 | 0.33 | 19.78 | 0.00 | 19.78 | 0.00 | 19.78 |
December | 3.33 | 19.27 | 3.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Annual Sum or Average | 10.50 | 19.23 | 9.67 | 19.32 | 0.67 | 19.49 | 0.67 | 19.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 19.78 | 5.83 | 19.78 | 0.67 | 24.65 | 0.67 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.50 | 18.80 | 11.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 5.17 | 19.10 | 4.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 2.00 | 18.93 | 1.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.34 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
November | 2.50 | 18.66 | 1.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
December | 10.00 | 18.94 | 8.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 33.33 | 18.89 | 27.50 | 19.09 | 0.33 | 19.12 | 0.33 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.50 | 19.34 | 11.00 | 19.34 | 0.33 | 24.57 | 0.33 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 115.83 | 16.92 | 67.83 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
February | 59.17 | 17.09 | 31.67 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
March | 24.00 | 17.11 | 12.67 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
April | 1.17 | 18.02 | 0.50 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.45 | 1.67 | 26.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 18.52 | 0.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
November | 20.67 | 16.88 | 9.67 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
December | 91.17 | 16.53 | 49.83 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
Annual Sum or Average | 313.17 | 16.86 | 173.00 | 17.39 | 1.83 | 17.43 | 1.67 | 17.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.83 | 18.52 | 67.83 | 18.89 | 1.83 | 26.45 | 1.67 | 26.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 15.86 | 28.83 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
February | 33.00 | 15.78 | 7.33 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
March | 12.00 | 15.72 | 2.33 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
April | 0.67 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.67 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.21 | 5.00 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.12 | 4.00 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.23 | 3.33 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
October | 0.50 | 17.29 | 0.17 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
November | 13.83 | 15.47 | 2.33 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
December | 61.33 | 15.42 | 22.67 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
Annual Sum or Average | 193.83 | 15.68 | 63.67 | 16.11 | 14.83 | 16.76 | 14.83 | 17.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 | 15.70 |
Maximum of Months | 72.50 | 17.29 | 28.83 | 17.79 | 5.00 | 28.23 | 5.00 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.33 | 16.22 | 23.50 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
February | 26.67 | 16.25 | 8.33 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
March | 9.50 | 16.07 | 2.33 | 16.38 | 0.33 | 16.68 | 0.33 | 16.97 |
April | 0.67 | 17.11 | 0.00 | 17.11 | 1.33 | 24.41 | 1.33 | 25.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.85 | 2.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.94 | 5.00 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.04 | 5.50 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.11 | 3.67 | 28.11 |
October | 0.50 | 17.33 | 0.17 | 17.80 | 2.17 | 25.69 | 2.17 | 26.74 |
November | 10.83 | 15.72 | 2.17 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
December | 52.17 | 15.82 | 17.83 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
Annual Sum or Average | 160.67 | 16.06 | 54.33 | 16.60 | 22.50 | 17.68 | 22.17 | 18.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 0.00 | 16.08 |
Maximum of Months | 60.33 | 17.33 | 23.50 | 17.80 | 5.50 | 28.11 | 5.50 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 15.77 | 26.67 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
February | 32.33 | 15.66 | 8.67 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
March | 11.67 | 15.64 | 3.33 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
April | 0.67 | 17.03 | 0.00 | 17.03 | 1.50 | 24.99 | 0.83 | 25.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.39 | 1.67 | 28.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.13 | 1.17 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.42 | 4.17 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.18 | 3.50 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.36 | 0.83 | 28.40 |
October | 0.50 | 17.32 | 0.17 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
November | 13.50 | 15.47 | 2.67 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
December | 59.17 | 15.33 | 20.33 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
Annual Sum or Average | 186.50 | 15.59 | 61.83 | 15.98 | 22.67 | 17.01 | 12.17 | 17.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 | 15.66 |
Maximum of Months | 68.67 | 17.32 | 26.67 | 17.82 | 7.67 | 28.42 | 4.17 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.00 | 18.56 | 86.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 25.67 | 19.08 | 21.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 14.67 | 19.03 | 12.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.33 | 19.30 | 0.33 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.69 | 0.50 | 24.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.96 | 0.83 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
December | 54.33 | 18.00 | 40.67 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
Annual Sum or Average | 200.17 | 18.51 | 161.50 | 18.83 | 0.50 | 18.84 | 0.50 | 18.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.00 | 19.30 | 86.00 | 19.31 | 0.50 | 24.69 | 0.50 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 17.12 | 19.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
February | 6.33 | 18.01 | 3.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
March | 2.33 | 16.81 | 0.67 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.78 | 3.00 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.83 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 3.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
December | 21.33 | 16.43 | 9.50 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Annual Sum or Average | 64.67 | 16.97 | 32.17 | 17.50 | 10.17 | 18.47 | 10.17 | 19.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.17 | 18.01 | 19.00 | 18.58 | 3.83 | 27.78 | 3.83 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 166.17 | 15.79 | 153.50 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 100.50 | 16.26 | 97.83 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
March | 87.33 | 16.90 | 86.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
April | 37.83 | 18.04 | 37.83 | 18.04 | 0.83 | 18.14 | 0.83 | 18.24 |
May | 9.00 | 19.46 | 9.00 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.68 | 2.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.72 | 5.00 | 27.72 |
September | 4.67 | 20.21 | 4.67 | 20.21 | 4.67 | 22.74 | 4.50 | 23.97 |
October | 30.50 | 18.91 | 30.50 | 18.91 | 2.33 | 19.24 | 2.33 | 19.55 |
November | 61.50 | 17.74 | 61.17 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
December | 140.50 | 16.16 | 134.33 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
Annual Sum or Average | 638.00 | 16.65 | 615.17 | 16.66 | 16.17 | 16.81 | 16.00 | 16.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 | 15.80 |
Maximum of Months | 166.17 | 20.21 | 153.50 | 20.21 | 5.00 | 27.72 | 5.00 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.83 | 17.17 | 20.83 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
February | 5.83 | 17.85 | 2.33 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
March | 3.50 | 17.50 | 1.50 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.00 | 0.50 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 1.17 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.95 | 0.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.90 | 3.50 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 3.00 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.16 | 0.83 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
December | 21.33 | 16.32 | 10.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 66.83 | 16.97 | 34.67 | 17.48 | 18.00 | 19.04 | 9.17 | 19.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.83 | 17.85 | 20.83 | 18.44 | 6.33 | 28.16 | 3.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.67 | 17.57 | 41.50 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
February | 19.50 | 18.43 | 13.67 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
March | 6.00 | 18.46 | 4.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.24 | 2.83 | 25.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 18.71 | 2.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
December | 49.33 | 17.02 | 31.17 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
Annual Sum or Average | 139.83 | 17.56 | 92.50 | 17.99 | 2.83 | 18.07 | 2.83 | 18.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.67 | 18.71 | 41.50 | 19.10 | 2.83 | 25.24 | 2.83 | 25.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 16.34 | 14.17 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
February | 7.67 | 16.73 | 2.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
March | 1.83 | 16.57 | 0.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 3.00 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.25 | 4.83 | 28.25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.99 | 4.33 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.20 | 4.00 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.72 | 1.50 | 27.72 |
October | 0.17 | 17.24 | 0.00 | 17.24 | 0.17 | 22.25 | 0.17 | 23.93 |
November | 1.33 | 17.12 | 0.17 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
December | 28.50 | 15.86 | 11.33 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
Annual Sum or Average | 72.67 | 16.21 | 28.00 | 16.62 | 17.83 | 18.34 | 17.83 | 19.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.17 | 17.24 | 14.17 | 17.36 | 4.83 | 28.25 | 4.83 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.00 | 16.88 | 12.00 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
February | 5.67 | 17.54 | 2.17 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
March | 1.17 | 17.03 | 0.17 | 17.30 | 1.50 | 22.73 | 1.50 | 24.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.12 | 1.33 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.73 | 1.67 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.78 | 2.33 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.25 | 5.83 | 27.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.01 | 5.67 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.98 | 5.33 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.06 | 3.33 | 28.06 |
November | 1.00 | 17.20 | 0.17 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
December | 20.67 | 16.40 | 8.33 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
Annual Sum or Average | 56.50 | 16.78 | 22.83 | 17.34 | 27.17 | 20.00 | 27.00 | 21.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 0.00 | 16.89 |
Maximum of Months | 28.00 | 17.54 | 12.00 | 18.09 | 6.00 | 28.12 | 5.83 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.33 | 16.34 | 14.67 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 6.83 | 16.56 | 2.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 2.17 | 16.77 | 0.33 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.49 | 0.83 | 28.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.39 | 1.67 | 28.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.15 | 1.00 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.31 | 4.00 | 28.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.13 | 3.50 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.33 | 1.17 | 28.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 17.15 | 0.17 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
December | 29.50 | 15.85 | 12.33 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 73.17 | 16.19 | 29.50 | 16.57 | 22.50 | 18.68 | 12.17 | 19.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.33 | 17.15 | 14.67 | 17.39 | 7.67 | 28.49 | 4.00 | 28.58 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.61 | 195.17 | 21.35 | 195.17 | 21.20 |
February | 454.00 | 22.55 | 27.67 | 22.47 | 27.67 | 22.39 |
March | 511.00 | 23.19 | 5.67 | 23.17 | 5.67 | 23.14 |
April | 400.00 | 23.89 | 1.33 | 23.90 | 0.00 | 23.90 |
May | 73.00 | 24.00 | 204.67 | 24.65 | 0.00 | 24.65 |
June | 4.17 | 24.00 | 371.00 | 24.49 | 0.00 | 24.49 |
July | 2.67 | 24.86 | 493.17 | 24.54 | 2.67 | 24.54 |
August | 0.00 | 0.00 | 489.67 | 24.41 | 0.00 | 24.41 |
September | 0.00 | 0.00 | 232.50 | 24.83 | 0.00 | 24.83 |
October | 232.83 | 23.90 | 42.50 | 24.11 | 0.00 | 24.11 |
November | 471.17 | 23.41 | 2.00 | 23.40 | 2.00 | 23.39 |
December | 497.00 | 22.06 | 95.33 | 21.85 | 95.33 | 21.70 |
Annual Sum or Average | 3147.83 | 22.86 | 2160.67 | 23.33 | 328.50 | 23.18 |
Minimum of Months | 0.00 | 0.00 | 1.33 | 21.35 | 0.00 | 21.20 |
Maximum of Months | 511.00 | 24.86 | 493.17 | 24.83 | 195.17 | 24.83 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 420.17 | 20.49 | 420.17 | 20.46 |
February | 454.00 | 21.05 | 273.33 | 20.89 | 273.33 | 20.81 |
March | 514.00 | 21.70 | 156.17 | 21.48 | 156.17 | 21.34 |
April | 466.00 | 22.87 | 7.50 | 22.83 | 7.50 | 22.80 |
May | 188.83 | 23.56 | 141.33 | 23.98 | 0.00 | 23.98 |
June | 41.67 | 23.54 | 295.33 | 24.20 | 0.00 | 24.20 |
July | 3.50 | 24.05 | 468.83 | 24.33 | 2.50 | 24.33 |
August | 20.50 | 23.33 | 424.67 | 24.19 | 0.00 | 24.19 |
September | 161.33 | 23.41 | 98.00 | 23.83 | 3.00 | 23.83 |
October | 465.67 | 22.76 | 2.67 | 22.74 | 2.67 | 22.73 |
November | 489.00 | 21.62 | 132.50 | 21.42 | 132.50 | 21.29 |
December | 497.00 | 20.70 | 365.00 | 20.58 | 365.00 | 20.53 |
Annual Sum or Average | 3803.50 | 21.80 | 2785.50 | 22.09 | 1362.83 | 21.82 |
Minimum of Months | 3.50 | 20.58 | 2.67 | 20.49 | 0.00 | 20.46 |
Maximum of Months | 514.00 | 24.05 | 468.83 | 24.33 | 420.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 477.17 | 20.12 | 477.17 | 20.11 |
February | 454.00 | 20.49 | 384.00 | 20.41 | 384.00 | 20.37 |
March | 514.00 | 21.07 | 288.67 | 20.86 | 288.67 | 20.76 |
April | 476.67 | 22.23 | 85.00 | 21.97 | 85.00 | 21.78 |
May | 235.83 | 23.24 | 130.17 | 23.66 | 2.33 | 23.64 |
June | 82.83 | 23.20 | 268.33 | 23.99 | 0.00 | 23.99 |
July | 26.00 | 23.32 | 425.00 | 24.24 | 2.17 | 24.24 |
August | 58.33 | 23.20 | 362.83 | 24.03 | 0.00 | 24.03 |
September | 284.67 | 23.04 | 57.33 | 23.24 | 5.33 | 23.25 |
October | 491.83 | 21.89 | 77.67 | 21.67 | 77.67 | 21.50 |
November | 489.00 | 20.80 | 278.67 | 20.57 | 278.67 | 20.47 |
December | 497.00 | 20.20 | 459.00 | 20.16 | 459.00 | 20.14 |
Annual Sum or Average | 4112.17 | 21.34 | 3293.83 | 21.52 | 2060.00 | 21.24 |
Minimum of Months | 26.00 | 20.15 | 57.33 | 20.12 | 0.00 | 20.11 |
Maximum of Months | 514.00 | 23.32 | 477.17 | 24.24 | 477.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.54 | 502.00 | 19.54 | 502.00 | 19.54 |
February | 454.00 | 19.81 | 451.17 | 19.81 | 451.17 | 19.81 |
March | 514.00 | 20.34 | 440.33 | 20.25 | 440.33 | 20.22 |
April | 476.50 | 21.36 | 204.33 | 21.03 | 202.67 | 20.84 |
May | 250.33 | 22.78 | 142.50 | 23.26 | 11.50 | 23.19 |
June | 98.67 | 23.27 | 291.33 | 24.02 | 3.67 | 24.04 |
July | 57.67 | 24.28 | 433.33 | 24.36 | 26.67 | 24.43 |
August | 106.33 | 22.98 | 337.17 | 23.89 | 3.83 | 23.89 |
September | 350.00 | 22.48 | 62.50 | 22.66 | 14.33 | 22.64 |
October | 501.00 | 21.00 | 191.50 | 20.72 | 191.50 | 20.56 |
November | 489.00 | 19.98 | 420.17 | 19.89 | 420.17 | 19.86 |
December | 497.00 | 19.62 | 497.00 | 19.62 | 497.00 | 19.62 |
Annual Sum or Average | 4296.50 | 20.76 | 3973.33 | 20.98 | 2764.83 | 20.71 |
Minimum of Months | 57.67 | 19.54 | 62.50 | 19.54 | 3.67 | 19.54 |
Maximum of Months | 514.00 | 24.28 | 502.00 | 24.36 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 19.96 | 424.17 | 19.92 | 424.17 | 19.91 |
March | 509.00 | 20.69 | 372.67 | 20.50 | 372.67 | 20.43 |
April | 405.67 | 21.56 | 158.67 | 21.30 | 139.50 | 21.06 |
May | 199.67 | 22.74 | 210.83 | 23.64 | 6.83 | 23.63 |
June | 103.17 | 23.76 | 355.67 | 24.22 | 22.83 | 24.34 |
July | 65.00 | 24.72 | 432.67 | 24.46 | 36.17 | 24.59 |
August | 125.00 | 23.16 | 348.33 | 24.00 | 14.50 | 24.09 |
September | 300.67 | 22.16 | 127.00 | 22.71 | 17.00 | 22.68 |
October | 471.17 | 20.98 | 180.83 | 20.80 | 170.17 | 20.64 |
November | 489.00 | 20.06 | 397.33 | 19.95 | 397.33 | 19.90 |
December | 497.00 | 19.71 | 497.00 | 19.71 | 497.00 | 19.71 |
Annual Sum or Average | 4121.33 | 20.84 | 4007.17 | 21.19 | 2600.17 | 20.92 |
Minimum of Months | 65.00 | 19.68 | 127.00 | 19.68 | 6.83 | 19.68 |
Maximum of Months | 509.00 | 24.72 | 502.00 | 24.46 | 502.00 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.00 | 20.00 | 422.17 | 19.81 | 422.17 | 19.74 |
February | 422.83 | 20.55 | 317.83 | 20.28 | 312.17 | 20.15 |
March | 450.00 | 20.92 | 318.33 | 20.78 | 297.83 | 20.63 |
April | 376.17 | 21.57 | 192.17 | 21.46 | 152.33 | 21.24 |
May | 204.00 | 22.53 | 202.83 | 23.39 | 14.50 | 23.32 |
June | 134.83 | 23.06 | 306.17 | 23.92 | 10.83 | 23.99 |
July | 93.83 | 24.14 | 405.33 | 24.37 | 37.50 | 24.50 |
August | 136.67 | 23.42 | 350.33 | 24.08 | 22.17 | 24.20 |
September | 282.83 | 22.53 | 173.83 | 23.25 | 27.17 | 23.33 |
October | 425.50 | 21.20 | 205.00 | 21.29 | 151.17 | 21.11 |
November | 460.50 | 20.37 | 323.00 | 20.14 | 320.33 | 20.04 |
December | 497.00 | 20.05 | 446.17 | 19.91 | 446.17 | 19.86 |
Annual Sum or Average | 3975.17 | 21.12 | 3663.17 | 21.45 | 2214.33 | 21.16 |
Minimum of Months | 93.83 | 20.00 | 173.83 | 19.81 | 10.83 | 19.74 |
Maximum of Months | 497.00 | 24.14 | 446.17 | 24.37 | 446.17 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.71 | 490.00 | 19.69 | 490.00 | 19.68 |
February | 452.17 | 20.07 | 402.17 | 19.97 | 402.17 | 19.94 |
March | 492.50 | 20.55 | 379.00 | 20.42 | 373.50 | 20.35 |
April | 418.17 | 21.23 | 214.67 | 21.10 | 185.50 | 20.93 |
May | 245.33 | 22.50 | 204.33 | 23.28 | 24.33 | 23.27 |
June | 145.00 | 22.81 | 306.00 | 23.82 | 13.67 | 23.88 |
July | 102.50 | 23.95 | 402.00 | 24.33 | 39.17 | 24.46 |
August | 173.50 | 23.01 | 308.17 | 23.83 | 19.67 | 23.94 |
September | 343.00 | 22.13 | 114.17 | 22.60 | 18.67 | 22.60 |
October | 466.67 | 20.87 | 194.50 | 20.72 | 179.17 | 20.56 |
November | 489.00 | 20.08 | 402.00 | 19.97 | 402.00 | 19.92 |
December | 497.00 | 19.72 | 495.67 | 19.71 | 495.67 | 19.71 |
Annual Sum or Average | 4326.83 | 20.84 | 3912.67 | 21.13 | 2643.50 | 20.88 |
Minimum of Months | 102.50 | 19.71 | 114.17 | 19.69 | 13.67 | 19.68 |
Maximum of Months | 502.00 | 23.95 | 495.67 | 24.33 | 495.67 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 502.00 | 19.61 | 502.00 | 19.61 |
February | 454.00 | 20.01 | 454.00 | 20.01 | 454.00 | 20.01 |
March | 514.00 | 20.35 | 484.50 | 20.32 | 484.50 | 20.32 |
April | 485.00 | 21.01 | 282.33 | 20.84 | 282.33 | 20.76 |
May | 357.50 | 22.70 | 92.17 | 22.90 | 15.33 | 22.83 |
June | 146.33 | 23.31 | 218.50 | 23.82 | 1.83 | 23.82 |
July | 36.17 | 24.33 | 432.33 | 24.29 | 18.17 | 24.33 |
August | 58.83 | 23.28 | 357.67 | 24.02 | 0.00 | 24.02 |
September | 308.50 | 23.07 | 70.83 | 23.29 | 6.00 | 23.30 |
October | 499.00 | 21.72 | 74.83 | 21.57 | 74.83 | 21.45 |
November | 489.00 | 20.51 | 389.67 | 20.42 | 389.67 | 20.39 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 4347.33 | 20.98 | 3855.83 | 21.14 | 2725.67 | 20.88 |
Minimum of Months | 36.17 | 19.61 | 70.83 | 19.61 | 0.00 | 19.61 |
Maximum of Months | 514.00 | 24.33 | 502.00 | 24.29 | 502.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 502.00 | 19.82 | 502.00 | 19.82 |
February | 454.00 | 20.20 | 449.00 | 20.19 | 449.00 | 20.19 |
March | 514.00 | 20.73 | 399.00 | 20.60 | 399.00 | 20.54 |
April | 442.17 | 21.77 | 146.83 | 21.45 | 144.00 | 21.25 |
May | 231.17 | 22.91 | 163.83 | 23.60 | 1.67 | 23.59 |
June | 76.50 | 23.69 | 351.33 | 24.24 | 12.50 | 24.31 |
July | 44.17 | 25.38 | 468.83 | 24.52 | 31.83 | 24.62 |
August | 48.33 | 24.19 | 433.33 | 24.32 | 14.33 | 24.39 |
September | 226.50 | 22.88 | 155.17 | 23.54 | 7.67 | 23.55 |
October | 454.00 | 21.74 | 70.67 | 21.69 | 58.67 | 21.57 |
November | 489.00 | 20.62 | 344.17 | 20.49 | 344.17 | 20.44 |
December | 497.00 | 19.93 | 497.00 | 19.93 | 497.00 | 19.93 |
Annual Sum or Average | 3978.83 | 21.07 | 3981.17 | 21.46 | 2461.83 | 21.18 |
Minimum of Months | 44.17 | 19.82 | 70.67 | 19.82 | 1.67 | 19.82 |
Maximum of Months | 514.00 | 25.38 | 502.00 | 24.52 | 502.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.49 | 481.67 | 18.44 | 481.67 | 18.42 |
February | 451.67 | 19.67 | 351.17 | 19.41 | 351.17 | 19.30 |
March | 500.00 | 20.19 | 355.00 | 19.95 | 349.17 | 19.82 |
April | 430.50 | 21.23 | 183.83 | 20.96 | 173.00 | 20.74 |
May | 291.00 | 22.33 | 135.83 | 22.87 | 13.67 | 22.78 |
June | 204.17 | 22.83 | 253.17 | 23.61 | 41.00 | 23.62 |
July | 95.00 | 23.97 | 423.33 | 24.32 | 52.83 | 24.39 |
August | 116.33 | 23.40 | 404.67 | 24.15 | 41.33 | 24.23 |
September | 225.33 | 22.57 | 208.17 | 23.58 | 20.67 | 23.69 |
October | 410.00 | 21.57 | 136.50 | 21.76 | 80.50 | 21.61 |
November | 475.17 | 20.48 | 273.00 | 20.19 | 273.00 | 20.06 |
December | 497.00 | 18.94 | 471.00 | 18.86 | 471.00 | 18.83 |
Annual Sum or Average | 4198.17 | 20.64 | 3677.33 | 20.93 | 2349.00 | 20.61 |
Minimum of Months | 95.00 | 18.49 | 135.83 | 18.44 | 13.67 | 18.42 |
Maximum of Months | 502.00 | 23.97 | 481.67 | 24.32 | 481.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 495.33 | 19.82 | 495.33 | 19.81 |
February | 454.00 | 20.25 | 427.17 | 20.20 | 427.17 | 20.18 |
March | 509.17 | 20.67 | 402.83 | 20.54 | 402.67 | 20.48 |
April | 447.17 | 21.45 | 192.50 | 21.20 | 188.00 | 21.05 |
May | 260.33 | 22.77 | 158.17 | 23.34 | 8.67 | 23.30 |
June | 125.67 | 22.98 | 293.67 | 23.89 | 3.33 | 23.91 |
July | 43.33 | 25.52 | 458.00 | 24.55 | 32.67 | 24.65 |
August | 58.83 | 23.80 | 418.50 | 24.26 | 14.33 | 24.34 |
September | 249.17 | 22.90 | 149.33 | 23.50 | 10.00 | 23.54 |
October | 460.67 | 21.73 | 79.83 | 21.64 | 69.33 | 21.52 |
November | 489.00 | 20.60 | 353.17 | 20.49 | 353.17 | 20.44 |
December | 497.00 | 19.94 | 497.00 | 19.94 | 497.00 | 19.94 |
Annual Sum or Average | 4096.33 | 21.06 | 3925.50 | 21.40 | 2501.67 | 21.14 |
Minimum of Months | 43.33 | 19.83 | 79.83 | 19.82 | 3.33 | 19.81 |
Maximum of Months | 509.17 | 25.52 | 497.00 | 24.55 | 497.00 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 20.09 | 442.50 | 20.08 | 442.50 | 20.07 |
March | 514.00 | 20.60 | 391.50 | 20.48 | 391.50 | 20.43 |
April | 474.67 | 21.83 | 134.50 | 21.53 | 134.00 | 21.33 |
May | 218.17 | 23.18 | 149.33 | 23.65 | 4.17 | 23.62 |
June | 56.50 | 23.59 | 309.00 | 24.18 | 1.17 | 24.19 |
July | 32.33 | 25.06 | 464.17 | 24.45 | 22.00 | 24.51 |
August | 46.17 | 23.22 | 392.50 | 24.09 | 0.00 | 24.09 |
September | 281.67 | 22.94 | 80.00 | 23.23 | 5.83 | 23.25 |
October | 496.33 | 21.63 | 103.67 | 21.41 | 103.67 | 21.24 |
November | 489.00 | 20.39 | 369.67 | 20.26 | 369.67 | 20.21 |
December | 497.00 | 19.83 | 497.00 | 19.83 | 497.00 | 19.83 |
Annual Sum or Average | 4061.83 | 20.99 | 3835.83 | 21.28 | 2473.50 | 20.99 |
Minimum of Months | 32.33 | 19.73 | 80.00 | 19.73 | 0.00 | 19.73 |
Maximum of Months | 514.00 | 25.06 | 502.00 | 24.45 | 502.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.61 | 427.00 | 19.61 | 427.00 | 19.61 |
February | 385.00 | 20.12 | 357.33 | 20.07 | 357.33 | 20.06 |
March | 424.33 | 20.81 | 282.00 | 20.62 | 282.00 | 20.54 |
April | 342.50 | 21.79 | 107.33 | 21.65 | 86.17 | 21.44 |
May | 162.17 | 23.04 | 182.00 | 23.92 | 6.17 | 23.96 |
June | 70.50 | 24.18 | 301.17 | 24.41 | 20.83 | 24.54 |
July | 43.67 | 25.56 | 386.33 | 24.62 | 32.33 | 24.76 |
August | 80.00 | 23.66 | 311.83 | 24.23 | 15.00 | 24.33 |
September | 240.67 | 22.55 | 106.00 | 23.17 | 6.17 | 23.22 |
October | 395.00 | 21.33 | 107.33 | 21.26 | 93.33 | 21.11 |
November | 417.00 | 20.32 | 310.17 | 20.18 | 310.17 | 20.13 |
December | 422.00 | 19.69 | 420.33 | 19.68 | 420.33 | 19.68 |
Annual Sum or Average | 3409.83 | 20.97 | 3298.83 | 21.36 | 2056.83 | 21.09 |
Minimum of Months | 43.67 | 19.61 | 106.00 | 19.61 | 6.17 | 19.61 |
Maximum of Months | 427.00 | 25.56 | 427.00 | 24.62 | 427.00 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 20.26 | 404.17 | 20.05 | 404.17 | 19.97 |
February | 411.00 | 20.89 | 288.00 | 20.64 | 278.83 | 20.49 |
March | 438.33 | 21.21 | 270.33 | 21.09 | 244.83 | 20.92 |
April | 361.33 | 22.00 | 133.33 | 21.98 | 91.17 | 21.80 |
May | 173.67 | 22.98 | 208.50 | 23.79 | 6.00 | 23.78 |
June | 92.17 | 23.45 | 326.33 | 24.13 | 8.50 | 24.19 |
July | 59.50 | 24.99 | 437.83 | 24.51 | 33.83 | 24.63 |
August | 75.83 | 24.20 | 403.33 | 24.32 | 22.67 | 24.44 |
September | 225.17 | 23.07 | 197.33 | 23.78 | 23.83 | 23.92 |
October | 407.17 | 21.80 | 142.00 | 22.00 | 81.50 | 21.89 |
November | 451.50 | 20.82 | 265.33 | 20.60 | 257.17 | 20.47 |
December | 493.00 | 20.33 | 422.00 | 20.16 | 422.00 | 20.09 |
Annual Sum or Average | 3676.33 | 21.40 | 3498.50 | 21.81 | 1874.50 | 21.53 |
Minimum of Months | 59.50 | 20.26 | 133.33 | 20.05 | 6.00 | 19.97 |
Maximum of Months | 493.00 | 24.99 | 437.83 | 24.51 | 422.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 484.83 | 19.82 | 484.83 | 19.81 |
February | 451.17 | 20.33 | 387.50 | 20.23 | 387.50 | 20.19 |
March | 490.00 | 20.80 | 332.50 | 20.64 | 326.33 | 20.55 |
April | 411.00 | 21.63 | 147.67 | 21.55 | 118.83 | 21.38 |
May | 211.00 | 22.89 | 211.83 | 23.67 | 13.17 | 23.71 |
June | 106.00 | 23.12 | 329.67 | 24.02 | 8.17 | 24.07 |
July | 64.67 | 24.72 | 439.33 | 24.47 | 33.17 | 24.59 |
August | 106.17 | 23.49 | 361.83 | 24.11 | 18.00 | 24.22 |
September | 292.83 | 22.57 | 131.00 | 23.14 | 10.17 | 23.19 |
October | 460.17 | 21.37 | 121.83 | 21.29 | 101.83 | 21.15 |
November | 489.00 | 20.46 | 344.67 | 20.32 | 344.67 | 20.25 |
December | 497.00 | 19.89 | 491.83 | 19.89 | 491.83 | 19.89 |
Annual Sum or Average | 4081.00 | 21.06 | 3784.50 | 21.42 | 2338.50 | 21.15 |
Minimum of Months | 64.67 | 19.85 | 121.83 | 19.82 | 8.17 | 19.81 |
Maximum of Months | 502.00 | 24.72 | 491.83 | 24.47 | 491.83 | 24.59 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.61286 | 14.93133 | -0.4950 | 11.56667 |
February | 454.00000 | 22.55346 | 16.52620 | -0.2474 | 6.92570 |
March | 514.00000 | 23.20181 | 19.26176 | -0.0604 | 5.85163 |
April | 485.00000 | 24.03247 | 18.92240 | 0.17546 | 5.93614 |
May | 508.00000 | 24.44233 | 31.43819 | -0.4428 | 10.08077 |
June | 496.00000 | 24.38976 | 43.81457 | -0.3361 | 7.95885 |
July | 497.00000 | 24.53203 | 50.12562 | -0.2312 | 6.86116 |
August | 514.00000 | 24.38958 | 49.56842 | -0.2834 | 7.17009 |
September | 485.00000 | 24.42114 | 36.87644 | -0.4010 | 9.06018 |
October | 502.00000 | 24.14408 | 29.29601 | 0.28282 | 6.95091 |
November | 489.00000 | 23.43315 | 22.16839 | 0.01491 | 5.77129 |
December | 497.00000 | 22.05932 | 16.84462 | -0.3654 | 8.81273 |
Annual Sum or Average | 5943.00000 | 23.60760 | 29.27366 | -0.1995 | 7.75487 |
Minimum of Months | 454.00000 | 21.61286 | 14.93133 | -0.4950 | 5.77129 |
Maximum of Months | 514.00000 | 24.53203 | 50.12562 | 0.28282 | 11.56667 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57935 | 16.75942 | -0.7383 | 18.07189 |
February | 454.00000 | 21.04705 | 18.48745 | -0.5897 | 13.29327 |
March | 514.00000 | 21.69729 | 21.84703 | -0.3905 | 9.38955 |
April | 485.00000 | 22.91925 | 21.06632 | -0.0745 | 6.21357 |
May | 508.00000 | 24.03078 | 32.59563 | -0.5894 | 13.55157 |
June | 496.00000 | 24.13333 | 45.02130 | -0.4387 | 9.57789 |
July | 497.00000 | 24.30948 | 51.15300 | -0.3255 | 7.62023 |
August | 514.00000 | 24.16389 | 50.69923 | -0.3872 | 8.52294 |
September | 485.00000 | 23.92803 | 38.87770 | -0.5915 | 13.11497 |
October | 502.00000 | 22.85264 | 32.96360 | -0.0175 | 6.11008 |
November | 489.00000 | 21.62462 | 25.49857 | -0.3942 | 9.44829 |
December | 497.00000 | 20.70470 | 18.94752 | -0.6841 | 16.25851 |
Annual Sum or Average | 5943.00000 | 22.67812 | 31.28282 | -0.4344 | 10.91682 |
Minimum of Months | 454.00000 | 20.57935 | 16.75942 | -0.7383 | 6.11008 |
Maximum of Months | 514.00000 | 24.30948 | 51.15300 | -0.0175 | 18.07189 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14941 | 17.29587 | -0.8747 | 23.38972 |
February | 454.00000 | 20.49467 | 19.07408 | -0.7553 | 18.81648 |
March | 514.00000 | 21.07307 | 22.77125 | -0.5631 | 13.35217 |
April | 485.00000 | 22.25878 | 21.98679 | -0.2382 | 8.12043 |
May | 508.00000 | 23.78845 | 32.78444 | -0.6762 | 16.63070 |
June | 496.00000 | 23.98890 | 45.44898 | -0.4852 | 10.83685 |
July | 497.00000 | 24.20160 | 51.36650 | -0.3621 | 8.30113 |
August | 514.00000 | 24.00290 | 51.16318 | -0.4478 | 9.78292 |
September | 485.00000 | 23.46680 | 40.08567 | -0.7575 | 18.51994 |
October | 502.00000 | 21.92935 | 34.95973 | -0.2468 | 7.97974 |
November | 489.00000 | 20.79734 | 26.40041 | -0.6166 | 15.04903 |
December | 497.00000 | 20.19879 | 19.84571 | -0.8410 | 22.12859 |
Annual Sum or Average | 5943.00000 | 22.20999 | 32.05432 | -0.5708 | 14.37122 |
Minimum of Months | 454.00000 | 20.14941 | 17.29587 | -0.8747 | 7.97974 |
Maximum of Months | 514.00000 | 24.20160 | 51.36650 | -0.2382 | 23.38972 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.54273 | 17.79167 | -1.1336 | 34.14242 |
February | 454.00000 | 19.81409 | 20.12343 | -1.0021 | 28.55232 |
March | 514.00000 | 20.33625 | 24.16558 | -0.8023 | 20.79189 |
April | 485.00000 | 21.41082 | 23.34330 | -0.4535 | 12.30973 |
May | 508.00000 | 23.52886 | 33.45202 | -0.7461 | 20.33937 |
June | 496.00000 | 24.00506 | 45.58993 | -0.4448 | 10.68045 |
July | 497.00000 | 24.25330 | 51.75105 | -0.3032 | 8.21797 |
August | 514.00000 | 23.87959 | 52.03040 | -0.4751 | 11.04743 |
September | 485.00000 | 22.91756 | 42.11290 | -0.9419 | 26.50199 |
October | 502.00000 | 21.01057 | 36.10320 | -0.4872 | 12.34518 |
November | 489.00000 | 19.98211 | 27.66766 | -0.8642 | 23.68783 |
December | 497.00000 | 19.61579 | 20.51185 | -1.0892 | 32.26232 |
Annual Sum or Average | 5943.00000 | 21.70838 | 33.00566 | -0.7262 | 19.99337 |
Minimum of Months | 454.00000 | 19.54273 | 17.79167 | -1.1336 | 8.21797 |
Maximum of Months | 514.00000 | 24.25330 | 52.03040 | -0.3032 | 34.14242 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68107 | 17.43984 | -1.0838 | 32.02975 |
February | 454.00000 | 19.96407 | 19.44337 | -0.9334 | 25.83962 |
March | 514.00000 | 20.72125 | 22.87544 | -0.6749 | 17.47052 |
April | 485.00000 | 21.98498 | 21.66788 | -0.2634 | 10.80726 |
May | 508.00000 | 23.72488 | 32.66312 | -0.5914 | 16.53796 |
June | 496.00000 | 24.05545 | 45.15846 | -0.3174 | 9.95295 |
July | 497.00000 | 24.26570 | 51.24368 | -0.1821 | 8.03029 |
August | 514.00000 | 23.87560 | 51.64493 | -0.3843 | 11.01307 |
September | 485.00000 | 22.92545 | 41.27406 | -0.8618 | 25.12314 |
October | 502.00000 | 21.18602 | 34.80474 | -0.4278 | 11.87319 |
November | 489.00000 | 20.06038 | 26.84060 | -0.8339 | 22.54150 |
December | 497.00000 | 19.70989 | 20.07647 | -1.0565 | 30.86485 |
Annual Sum or Average | 5943.00000 | 21.86311 | 32.21387 | -0.6317 | 18.42990 |
Minimum of Months | 454.00000 | 19.68107 | 17.43984 | -1.0838 | 8.03029 |
Maximum of Months | 514.00000 | 24.26570 | 51.64493 | -0.1821 | 32.02975 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08360 | 17.03737 | -0.9170 | 27.55868 |
February | 454.00000 | 20.79000 | 18.39714 | -0.6779 | 20.55058 |
March | 514.00000 | 21.36874 | 21.90909 | -0.4949 | 15.74292 |
April | 485.00000 | 22.16176 | 21.13024 | -0.2198 | 11.35213 |
May | 508.00000 | 23.59966 | 32.65425 | -0.6520 | 18.80090 |
June | 496.00000 | 23.86333 | 45.61668 | -0.4372 | 12.05915 |
July | 497.00000 | 24.18230 | 51.55154 | -0.2573 | 9.00423 |
August | 514.00000 | 23.91604 | 51.34324 | -0.3710 | 11.18069 |
September | 485.00000 | 23.25389 | 40.23462 | -0.7320 | 22.65249 |
October | 502.00000 | 21.69981 | 33.52383 | -0.2816 | 11.99676 |
November | 489.00000 | 20.58231 | 25.93015 | -0.6752 | 19.45807 |
December | 497.00000 | 20.05499 | 19.73270 | -0.9224 | 26.69097 |
Annual Sum or Average | 5943.00000 | 22.14242 | 31.71294 | -0.5520 | 17.21445 |
Minimum of Months | 454.00000 | 20.05499 | 17.03737 | -0.9224 | 9.00423 |
Maximum of Months | 514.00000 | 24.18230 | 51.55154 | -0.2198 | 27.55868 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70559 | 17.21605 | -1.0817 | 32.02018 |
February | 454.00000 | 20.08566 | 19.11264 | -0.9130 | 25.67126 |
March | 514.00000 | 20.70749 | 22.66803 | -0.6863 | 18.72503 |
April | 485.00000 | 21.63545 | 21.96181 | -0.3532 | 12.42445 |
May | 508.00000 | 23.41720 | 33.04387 | -0.6821 | 20.89316 |
June | 496.00000 | 23.76008 | 46.07162 | -0.4324 | 12.70997 |
July | 497.00000 | 24.13892 | 51.87797 | -0.2401 | 9.46564 |
August | 514.00000 | 23.68996 | 52.21347 | -0.4409 | 12.90105 |
September | 485.00000 | 22.71724 | 41.66714 | -0.9277 | 28.16870 |
October | 502.00000 | 21.10479 | 34.76002 | -0.4435 | 12.39245 |
November | 489.00000 | 20.08484 | 26.64451 | -0.8325 | 22.59323 |
December | 497.00000 | 19.71545 | 19.89807 | -1.0588 | 30.95052 |
Annual Sum or Average | 5943.00000 | 21.74577 | 32.38397 | -0.6721 | 19.84623 |
Minimum of Months | 454.00000 | 19.70559 | 17.21605 | -1.0817 | 9.46564 |
Maximum of Months | 514.00000 | 24.13892 | 52.21347 | -0.2401 | 32.02018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60549 | 16.55870 | -1.1115 | 32.77445 |
February | 454.00000 | 20.01012 | 19.15348 | -0.9610 | 26.13924 |
March | 514.00000 | 20.34882 | 23.04790 | -0.8281 | 20.90886 |
April | 485.00000 | 21.00575 | 23.60147 | -0.5744 | 13.00710 |
May | 508.00000 | 23.12899 | 35.18461 | -0.9284 | 26.06736 |
June | 496.00000 | 23.86378 | 46.45957 | -0.5482 | 12.32519 |
July | 497.00000 | 24.21613 | 52.11430 | -0.3517 | 8.11521 |
August | 514.00000 | 23.99880 | 51.81010 | -0.4481 | 9.73705 |
September | 485.00000 | 23.44456 | 40.77375 | -0.7666 | 18.86007 |
October | 502.00000 | 21.73329 | 34.34844 | -0.2905 | 7.91048 |
November | 489.00000 | 20.51333 | 26.22011 | -0.7035 | 16.85743 |
December | 497.00000 | 19.83307 | 19.08110 | -1.0141 | 28.60202 |
Annual Sum or Average | 5943.00000 | 21.82385 | 32.48755 | -0.7089 | 18.39911 |
Minimum of Months | 454.00000 | 19.60549 | 16.55870 | -1.1115 | 7.91048 |
Maximum of Months | 514.00000 | 24.21613 | 52.11430 | -0.2905 | 32.77445 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81515 | 16.56296 | -1.0480 | 30.03176 |
February | 454.00000 | 20.19918 | 18.83045 | -0.8848 | 22.96472 |
March | 514.00000 | 20.72786 | 22.28388 | -0.6951 | 16.93109 |
April | 485.00000 | 21.97973 | 21.90902 | -0.2919 | 9.74216 |
May | 508.00000 | 23.70979 | 33.56379 | -0.6540 | 17.07650 |
June | 496.00000 | 24.12569 | 45.16156 | -0.3523 | 9.38307 |
July | 497.00000 | 24.38745 | 51.03508 | -0.1783 | 6.84087 |
August | 514.00000 | 24.19121 | 50.84001 | -0.2957 | 8.28629 |
September | 485.00000 | 23.63517 | 39.63917 | -0.6317 | 16.03662 |
October | 502.00000 | 21.99501 | 33.27619 | -0.2092 | 7.97748 |
November | 489.00000 | 20.61713 | 25.78481 | -0.6656 | 15.76904 |
December | 497.00000 | 19.93203 | 18.90967 | -0.9809 | 27.16436 |
Annual Sum or Average | 5943.00000 | 22.12523 | 31.60469 | -0.5719 | 15.63378 |
Minimum of Months | 454.00000 | 19.81515 | 16.56296 | -1.0480 | 6.84087 |
Maximum of Months | 514.00000 | 24.38745 | 51.03508 | -0.1783 | 30.03176 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.49300 | 14.27247 | -1.2185 | 37.44661 |
February | 454.00000 | 19.69307 | 15.95624 | -0.8801 | 25.01497 |
March | 514.00000 | 20.32442 | 19.59114 | -0.7069 | 19.65675 |
April | 485.00000 | 21.59200 | 20.36052 | -0.3502 | 11.53304 |
May | 508.00000 | 23.18455 | 33.56987 | -0.8214 | 23.32985 |
June | 496.00000 | 23.64783 | 46.99941 | -0.5516 | 14.07067 |
July | 497.00000 | 24.20826 | 52.35283 | -0.2754 | 8.26631 |
August | 514.00000 | 24.02375 | 51.78289 | -0.3281 | 9.72803 |
September | 485.00000 | 23.53837 | 39.00602 | -0.6071 | 17.90417 |
October | 502.00000 | 22.11189 | 30.98175 | -0.1341 | 9.53343 |
November | 489.00000 | 20.59181 | 23.16965 | -0.6118 | 16.14264 |
December | 497.00000 | 18.93628 | 16.61614 | -1.1125 | 33.20458 |
Annual Sum or Average | 5943.00000 | 21.71072 | 30.52558 | -0.6318 | 18.78799 |
Minimum of Months | 454.00000 | 18.49300 | 14.27247 | -1.2185 | 8.26631 |
Maximum of Months | 514.00000 | 24.20826 | 52.35283 | -0.1341 | 37.44661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82714 | 16.30362 | -1.0491 | 30.13197 |
February | 454.00000 | 20.24815 | 18.53866 | -0.8768 | 23.06994 |
March | 514.00000 | 20.70290 | 22.04689 | -0.7066 | 17.77210 |
April | 485.00000 | 21.67018 | 22.10432 | -0.3733 | 10.92145 |
May | 508.00000 | 23.51613 | 33.69819 | -0.7111 | 19.49520 |
June | 496.00000 | 23.87894 | 46.04790 | -0.4570 | 11.62053 |
July | 497.00000 | 24.37776 | 51.29388 | -0.1987 | 7.28387 |
August | 514.00000 | 24.13150 | 51.03407 | -0.3151 | 8.83196 |
September | 485.00000 | 23.56638 | 39.81864 | -0.6579 | 17.01046 |
October | 502.00000 | 21.93566 | 33.12450 | -0.2192 | 7.99358 |
November | 489.00000 | 20.60170 | 25.59717 | -0.6722 | 15.96299 |
December | 497.00000 | 19.94112 | 18.69952 | -0.9832 | 27.24009 |
Annual Sum or Average | 5943.00000 | 22.04830 | 31.64864 | -0.5997 | 16.40012 |
Minimum of Months | 454.00000 | 19.82714 | 16.30362 | -1.0491 | 7.28387 |
Maximum of Months | 514.00000 | 24.37776 | 51.29388 | -0.1987 | 30.13197 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73086 | 17.73796 | -1.0451 | 30.17970 |
February | 454.00000 | 20.08838 | 19.86855 | -0.8957 | 23.79844 |
March | 514.00000 | 20.60190 | 23.59806 | -0.6997 | 17.08625 |
April | 485.00000 | 21.87371 | 22.75714 | -0.3242 | 9.37493 |
May | 508.00000 | 23.79809 | 33.18589 | -0.6508 | 16.35822 |
June | 496.00000 | 24.14717 | 45.14835 | -0.3980 | 9.18446 |
July | 497.00000 | 24.36175 | 51.44137 | -0.2667 | 7.32644 |
August | 514.00000 | 24.06103 | 51.40561 | -0.4093 | 9.15879 |
September | 485.00000 | 23.43346 | 40.78412 | -0.7615 | 19.08265 |
October | 502.00000 | 21.65991 | 34.84081 | -0.3076 | 8.72833 |
November | 489.00000 | 20.38773 | 26.90552 | -0.7260 | 18.15409 |
December | 497.00000 | 19.82727 | 20.11768 | -0.9926 | 28.02678 |
Annual Sum or Average | 5943.00000 | 22.01363 | 32.43445 | -0.6211 | 16.31189 |
Minimum of Months | 454.00000 | 19.73086 | 17.73796 | -1.0451 | 7.32644 |
Maximum of Months | 514.00000 | 24.36175 | 51.44137 | -0.2667 | 30.17970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.61303 | 16.76755 | -1.0565 | 30.81575 |
February | 385.00000 | 20.11582 | 18.56322 | -0.8663 | 22.63404 |
March | 433.00000 | 20.87339 | 21.66397 | -0.6116 | 15.22467 |
April | 410.00000 | 22.21226 | 20.81807 | -0.1986 | 9.25669 |
May | 430.00000 | 23.91315 | 32.07102 | -0.5398 | 14.81206 |
June | 418.00000 | 24.20223 | 44.63606 | -0.2897 | 9.26072 |
July | 422.00000 | 24.42008 | 50.76034 | -0.1574 | 7.50457 |
August | 433.00000 | 24.03938 | 50.84066 | -0.3445 | 9.93048 |
September | 410.00000 | 23.25571 | 40.13407 | -0.7516 | 20.73278 |
October | 427.00000 | 21.58357 | 33.30226 | -0.3095 | 9.46024 |
November | 417.00000 | 20.32264 | 25.32920 | -0.7368 | 18.53289 |
December | 422.00000 | 19.68662 | 19.07292 | -1.0148 | 29.01866 |
Annual Sum or Average | 5034.00000 | 22.03246 | 31.26576 | -0.5712 | 16.38478 |
Minimum of Months | 385.00000 | 19.61303 | 16.76755 | -1.0565 | 7.50457 |
Maximum of Months | 433.00000 | 24.42008 | 50.84066 | -0.1574 | 30.81575 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36608 | 16.66086 | -0.8126 | 23.51217 |
February | 454.00000 | 21.20980 | 17.87434 | -0.5457 | 16.39039 |
March | 514.00000 | 21.69438 | 21.21347 | -0.3826 | 12.97848 |
April | 485.00000 | 22.57119 | 20.53734 | -0.1031 | 9.25377 |
May | 508.00000 | 23.86394 | 32.42392 | -0.5597 | 14.98435 |
June | 496.00000 | 24.05465 | 45.06491 | -0.3785 | 9.90681 |
July | 497.00000 | 24.33512 | 51.11708 | -0.2106 | 7.67650 |
August | 514.00000 | 24.13177 | 50.70647 | -0.2978 | 9.05362 |
September | 485.00000 | 23.69819 | 39.13754 | -0.5730 | 16.50444 |
October | 502.00000 | 22.29351 | 32.37596 | -0.1148 | 9.49364 |
November | 489.00000 | 21.08086 | 25.03736 | -0.5211 | 14.71663 |
December | 497.00000 | 20.35968 | 19.09713 | -0.8092 | 22.39760 |
Annual Sum or Average | 5943.00000 | 22.48284 | 31.06241 | -0.4416 | 13.88129 |
Minimum of Months | 454.00000 | 20.35968 | 16.66086 | -0.8126 | 7.67650 |
Maximum of Months | 514.00000 | 24.33512 | 51.11708 | -0.1031 | 23.51217 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85097 | 16.98162 | -1.0031 | 28.61562 |
February | 454.00000 | 20.35648 | 18.72048 | -0.8088 | 21.34246 |
March | 514.00000 | 20.95939 | 22.04744 | -0.5875 | 15.46434 |
April | 485.00000 | 22.01832 | 21.45346 | -0.2401 | 9.86986 |
May | 508.00000 | 23.70780 | 32.78115 | -0.5825 | 16.61987 |
June | 496.00000 | 23.96708 | 45.50710 | -0.3694 | 10.34881 |
July | 497.00000 | 24.29818 | 51.42992 | -0.1913 | 8.01569 |
August | 514.00000 | 23.94560 | 51.49321 | -0.3566 | 10.25721 |
September | 485.00000 | 23.21446 | 40.51088 | -0.7533 | 20.90425 |
October | 502.00000 | 21.60744 | 33.74546 | -0.2922 | 9.22580 |
November | 489.00000 | 20.46431 | 25.91460 | -0.7000 | 17.44742 |
December | 497.00000 | 19.89444 | 19.33617 | -0.9700 | 27.06232 |
Annual Sum or Average | 5943.00000 | 22.03854 | 31.78261 | -0.5692 | 16.21633 |
Minimum of Months | 454.00000 | 19.85097 | 16.98162 | -1.0031 | 8.01569 |
Maximum of Months | 514.00000 | 24.29818 | 51.49321 | -0.1913 | 28.61562 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.150883E+12 | 0.00 | 613.77 | 298304.31 | 09-JAN-07:15 | 0.00 | 40.97 | 56.52 | 0.79 | 0.00 | 0.12 | 0.64 | 09-JAN-07:15 |
February | 0.779640E+11 | 0.00 | 492.30 | 279962.81 | 14-FEB-07:12 | 0.00 | 37.84 | 53.68 | 0.42 | 0.00 | 0.07 | 0.60 | 14-FEB-07:12 |
March | 0.483623E+11 | 0.00 | 466.52 | 241744.14 | 30-MAR-06:01 | 0.00 | 34.35 | 49.47 | 0.21 | 0.00 | 0.04 | 0.52 | 30-MAR-06:01 |
April | 0.113433E+11 | 0.00 | 254.30 | 219091.81 | 06-APR-05:01 | 0.00 | 30.93 | 40.46 | 0.05 | 0.00 | 0.01 | 0.47 | 06-APR-05:01 |
May | 0.108355E+10 | 0.00 | 61.38 | 208096.41 | 01-MAY-06:01 | 0.00 | 41.61 | 43.16 | 0.01 | 0.00 | 0.00 | 0.45 | 01-MAY-06:01 |
June | 0.156547E+09 | 0.00 | 59.85 | 13225.29 | 09-JUN-06:06 | 0.00 | 40.88 | 42.52 | 0.00 | 0.00 | 0.00 | 0.03 | 09-JUN-06:06 |
July | 22441805.98 | 0.00 | 87.96 | 14147.44 | 18-JUL-06:06 | 0.00 | 37.72 | 40.43 | 0.00 | 0.00 | 0.00 | 0.03 | 18-JUL-06:06 |
August | 90304503.44 | 0.00 | 65.70 | 18570.09 | 19-AUG-06:03 | 0.00 | 36.25 | 38.27 | 0.00 | 0.00 | 0.00 | 0.04 | 19-AUG-06:03 |
September | 0.958697E+09 | 0.00 | 71.23 | 63280.24 | 29-SEP-06:03 | 0.00 | 41.22 | 43.00 | 0.01 | 0.00 | 0.00 | 0.14 | 29-SEP-06:03 |
October | 0.102372E+11 | 0.00 | 277.09 | 260061.23 | 16-OCT-05:11 | 0.00 | 30.66 | 40.79 | 0.04 | 0.00 | 0.01 | 0.56 | 16-OCT-05:11 |
November | 0.405227E+11 | 0.00 | 436.20 | 274773.83 | 20-NOV-06:11 | 0.00 | 31.99 | 47.96 | 0.18 | 0.00 | 0.03 | 0.59 | 20-NOV-06:11 |
December | 0.122151E+12 | 0.00 | 594.62 | 280715.29 | 26-DEC-08:02 | 0.00 | 39.95 | 55.64 | 0.62 | 0.00 | 0.10 | 0.60 | 26-DEC-08:02 |
Annual Sum or Average | 0.463774E+12 | 0.00 | 3480.92 | 0.00 | 37.03 | 45.96 | 0.19 | 0.00 | 0.03 | ||||
Minimum of Months | 22441805.98 | 0.00 | 59.85 | 13225.29 | 0.00 | 30.66 | 38.27 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.150883E+12 | 0.00 | 613.77 | 298304.31 | 0.00 | 41.61 | 56.52 | 0.79 | 0.00 | 0.12 | 0.64 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5326878.93 | 1416734.68 | 1.65 | 5263400.39 | 63478.54 | 0.00 | 0.19 | 30-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5332.22 | 30-JAN-07:01 | 5332.22 | 30-JAN-07:01 | 59.08 | 19-JAN-13:12 | 1389.97 | 30-JAN-07:01 | 0.00 |
February | 14507630.43 | 3919442.16 | 7.98 | 14382133.19 | 125497.24 | 0.00 | 0.19 | 21-FEB-07:02 | 0.00 | 01-FEB-00:10 | 5474.64 | 21-FEB-07:02 | 5474.64 | 21-FEB-07:02 | 63.80 | 21-FEB-18:01 | 1425.46 | 21-FEB-07:02 | 0.00 |
March | 33375741.29 | 9018369.63 | 16.12 | 32181059.39 | 1194681.90 | 0.00 | 0.13 | 25-MAR-06:03 | 0.00 | 01-MAR-00:10 | 3777.81 | 25-MAR-06:03 | 3777.81 | 25-MAR-06:03 | 145.62 | 21-MAR-10:10 | 997.27 | 25-MAR-06:03 | 0.00 |
April | 0.130013E+10 | 0.326377E+09 | 62.71 | 0.125811E+10 | 42023080.66 | 0.00 | 0.91 | 23-APR-17:42 | 0.00 | 01-APR-00:10 | 30880.67 | 23-APR-17:42 | 30880.67 | 23-APR-17:42 | 4025.75 | 23-APR-13:44 | 6973.04 | 23-APR-17:42 | 0.00 |
May | 0.165921E+11 | 0.380629E+10 | 211.08 | 0.156052E+11 | 0.986870E+09 | 0.00 | 1.00 | 16-MAY-12:10 | 0.00 | 01-MAY-00:10 | 61849.97 | 26-MAY-11:00 | 58026.27 | 18-MAY-15:20 | 19853.33 | 26-MAY-11:00 | 14320.90 | 25-MAY-15:50 | 0.00 |
June | 0.391819E+11 | 0.890674E+10 | 346.93 | 0.306526E+11 | 0.852937E+10 | 0.00 | 1.00 | 06-JUN-09:50 | 0.00 | 01-JUN-00:10 | 113517.62 | 29-JUN-06:03 | 67299.89 | 30-JUN-15:10 | 58973.41 | 29-JUN-06:03 | 23847.64 | 29-JUN-06:03 | 0.00 |
July | 0.548014E+11 | 0.121749E+11 | 397.87 | 0.411874E+11 | 0.136140E+11 | 0.00 | 1.00 | 03-JUL-05:12 | 0.00 | 01-JUL-00:10 | 120481.45 | 05-JUL-10:20 | 70881.45 | 24-JUL-16:00 | 78742.65 | 05-JUL-11:00 | 24938.66 | 05-JUL-11:50 | 0.00 |
August | 0.434762E+11 | 0.966079E+10 | 388.73 | 0.314249E+11 | 0.120513E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 97238.56 | 08-AUG-10:10 | 67358.04 | 08-AUG-16:00 | 52647.86 | 31-AUG-12:50 | 20558.47 | 08-AUG-10:10 | 0.00 |
September | 0.959320E+10 | 0.221356E+10 | 164.23 | 0.807359E+10 | 0.151961E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 68086.80 | 01-SEP-13:20 | 62045.70 | 01-SEP-16:00 | 25328.62 | 01-SEP-06:03 | 14684.19 | 01-SEP-13:20 | 0.00 |
October | 0.129406E+10 | 0.310996E+09 | 43.36 | 0.123984E+10 | 54216676.74 | 0.00 | 0.91 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 31213.24 | 19-OCT-15:00 | 31213.24 | 19-OCT-15:00 | 4130.44 | 22-OCT-12:02 | 6732.60 | 19-OCT-15:00 | 0.00 |
November | 0.200996E+09 | 51843351.57 | 20.30 | 0.148477E+09 | 52518678.88 | 0.00 | 0.35 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 10238.48 | 01-NOV-15:00 | 7547.49 | 01-NOV-15:00 | 2690.99 | 01-NOV-15:00 | 2567.42 | 01-NOV-15:00 | 0.00 |
December | 11378264.60 | 3064154.43 | 5.27 | 11169598.69 | 208665.92 | 0.00 | 0.23 | 28-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6732.53 | 28-DEC-07:01 | 6732.53 | 28-DEC-07:01 | 154.79 | 05-DEC-18:12 | 1735.42 | 28-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.166505E+12 | 0.374689E+11 | 1666.23 | 0.129653E+12 | 0.368515E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 5326878.93 | 1416734.68 | 1.65 | 5263400.39 | 63478.54 | 0.00 | 0.13 | 0.00 | 3777.81 | 3777.81 | 59.08 | 997.27 | 0.00 | ||||||
Maximum of Months | 0.548014E+11 | 0.121749E+11 | 397.87 | 0.411874E+11 | 0.136140E+11 | 0.00 | 1.00 | 0.00 | 120481.45 | 70881.45 | 78742.65 | 24938.66 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6372378.99 | 1687241.70 | 0.93 | 6371422.50 | 956.49 | 0.00 | 0.23 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6381.05 | 20-JAN-07:01 | 6381.05 | 20-JAN-07:01 | 14.68 | 19-JAN-07:06 | 1646.13 | 20-JAN-07:01 | 0.00 |
February | 14581552.00 | 3869483.48 | 6.32 | 14575582.85 | 5969.16 | 0.00 | 0.29 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 8224.76 | 09-FEB-07:01 | 8224.76 | 09-FEB-07:01 | 7.38 | 22-FEB-10:40 | 2089.83 | 09-FEB-07:01 | 0.00 |
March | 22798940.59 | 6044456.63 | 10.77 | 22670886.45 | 128054.14 | 0.00 | 0.29 | 27-MAR-06:01 | 0.00 | 01-MAR-00:10 | 8173.66 | 27-MAR-06:01 | 8173.66 | 27-MAR-06:01 | 59.18 | 28-MAR-11:07 | 2077.71 | 27-MAR-06:01 | 0.00 |
April | 0.146513E+10 | 0.362697E+09 | 60.16 | 0.143547E+10 | 29660676.11 | 0.00 | 1.00 | 23-APR-13:42 | 0.00 | 01-APR-00:10 | 40695.64 | 23-APR-16:22 | 40695.64 | 23-APR-16:22 | 3522.28 | 23-APR-13:04 | 9100.75 | 23-APR-16:22 | 0.00 |
May | 0.170955E+11 | 0.390858E+10 | 218.44 | 0.161036E+11 | 0.991920E+09 | 0.00 | 1.00 | 10-MAY-15:20 | 0.00 | 01-MAY-00:10 | 63043.42 | 25-MAY-16:00 | 59121.91 | 18-MAY-15:00 | 19741.32 | 26-MAY-11:00 | 14984.96 | 25-MAY-16:00 | 0.00 |
June | 0.384407E+11 | 0.872086E+10 | 353.06 | 0.304736E+11 | 0.796712E+10 | 0.00 | 1.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 | 108422.80 | 30-JUN-04:02 | 68262.77 | 30-JUN-04:02 | 55301.47 | 29-JUN-06:03 | 23678.49 | 30-JUN-04:02 | 0.00 |
July | 0.511447E+11 | 0.113773E+11 | 397.66 | 0.385276E+11 | 0.126171E+11 | 0.00 | 1.00 | 03-JUL-06:03 | 0.00 | 01-JUL-00:10 | 115918.53 | 05-JUL-10:20 | 75390.07 | 23-JUL-16:41 | 75796.22 | 05-JUL-11:00 | 23994.17 | 05-JUL-11:50 | 0.00 |
August | 0.383236E+11 | 0.856434E+10 | 385.01 | 0.279340E+11 | 0.103895E+11 | 0.00 | 1.00 | 04-AUG-12:20 | 0.00 | 01-AUG-00:10 | 90762.08 | 31-AUG-12:50 | 62233.60 | 08-AUG-15:10 | 49525.46 | 31-AUG-12:50 | 18941.14 | 31-AUG-12:50 | 0.00 |
September | 0.865818E+10 | 0.201008E+10 | 163.20 | 0.722570E+10 | 0.143249E+10 | 0.00 | 1.00 | 01-SEP-08:40 | 0.00 | 01-SEP-00:10 | 67327.75 | 01-SEP-13:20 | 60335.61 | 01-SEP-15:40 | 19489.47 | 01-SEP-12:20 | 14519.28 | 01-SEP-13:20 | 0.00 |
October | 0.122270E+10 | 0.296174E+09 | 36.71 | 0.116864E+10 | 54065748.18 | 0.00 | 0.83 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 26819.66 | 19-OCT-15:00 | 26819.66 | 19-OCT-15:00 | 3818.35 | 22-OCT-11:53 | 5916.57 | 19-OCT-15:00 | 0.00 |
November | 0.173136E+09 | 44690896.27 | 16.10 | 0.123402E+09 | 49733483.75 | 0.00 | 0.30 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 8577.38 | 01-NOV-15:00 | 8320.26 | 15-NOV-07:01 | 2641.33 | 01-NOV-15:00 | 2173.17 | 01-NOV-15:00 | 0.00 |
December | 10243201.66 | 2685912.43 | 1.16 | 10242253.31 | 948.35 | 0.00 | 0.25 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 6966.76 | 06-DEC-07:01 | 6966.76 | 06-DEC-07:01 | 14.23 | 05-DEC-07:07 | 1788.55 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.156578E+12 | 0.352990E+11 | 1649.52 | 0.123046E+12 | 0.335318E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 6372378.99 | 1687241.70 | 0.93 | 6371422.50 | 948.35 | 0.00 | 0.23 | 0.00 | 6381.05 | 6381.05 | 7.38 | 1646.13 | 0.00 | ||||||
Maximum of Months | 0.511447E+11 | 0.113773E+11 | 397.66 | 0.385276E+11 | 0.126171E+11 | 0.00 | 1.00 | 0.00 | 115918.53 | 75390.07 | 75796.22 | 23994.17 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2512360.55 | 678402.32 | 1.16 | 2512360.55 | 0.00 | 0.00 | 0.10 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 3078.26 | 19-JAN-07:01 | 3078.26 | 19-JAN-07:01 | 0.00 | 19-JAN-07:01 | 818.28 | 19-JAN-07:01 | 0.00 |
February | 12208496.99 | 3311397.41 | 9.08 | 12087000.81 | 121496.18 | 0.00 | 0.11 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 3345.77 | 09-FEB-07:01 | 3345.77 | 09-FEB-07:01 | 40.24 | 22-FEB-05:30 | 887.54 | 09-FEB-07:01 | 0.00 |
March | 24849357.14 | 6710365.70 | 16.84 | 24284820.54 | 564536.60 | 0.00 | 0.20 | 28-MAR-06:02 | 0.00 | 01-MAR-00:10 | 5968.45 | 28-MAR-06:02 | 5968.45 | 28-MAR-06:02 | 86.32 | 28-MAR-11:30 | 1551.55 | 28-MAR-06:02 | 0.00 |
April | 0.153089E+10 | 0.379328E+09 | 67.55 | 0.147497E+10 | 55916288.72 | 0.00 | 1.00 | 23-APR-15:22 | 0.00 | 01-APR-00:10 | 51110.43 | 23-APR-16:02 | 51110.43 | 23-APR-16:02 | 4086.75 | 23-APR-13:25 | 11490.57 | 23-APR-16:02 | 0.00 |
May | 0.180477E+11 | 0.414152E+10 | 220.19 | 0.169352E+11 | 0.111252E+10 | 0.00 | 1.00 | 10-MAY-15:20 | 0.00 | 01-MAY-00:10 | 70218.73 | 25-MAY-15:00 | 67587.15 | 18-MAY-14:50 | 18847.90 | 26-MAY-11:00 | 16640.52 | 25-MAY-16:00 | 0.00 |
June | 0.399991E+11 | 0.912383E+10 | 351.39 | 0.316867E+11 | 0.831239E+10 | 0.00 | 1.00 | 01-JUN-12:10 | 0.00 | 01-JUN-00:10 | 112938.49 | 30-JUN-04:02 | 76742.38 | 30-JUN-14:30 | 53947.07 | 19-JUN-16:00 | 24652.87 | 30-JUN-04:02 | 0.00 |
July | 0.530277E+11 | 0.118546E+11 | 395.66 | 0.399569E+11 | 0.130708E+11 | 0.00 | 1.00 | 03-JUL-12:05 | 0.00 | 01-JUL-00:10 | 126707.88 | 05-JUL-10:40 | 81484.45 | 23-JUL-15:32 | 82791.18 | 05-JUL-11:00 | 27236.37 | 23-JUL-16:52 | 0.00 |
August | 0.391405E+11 | 0.879797E+10 | 382.44 | 0.282116E+11 | 0.109289E+11 | 0.00 | 1.00 | 04-AUG-12:40 | 0.00 | 01-AUG-00:10 | 102422.18 | 29-AUG-15:20 | 70474.84 | 08-AUG-15:00 | 45012.68 | 31-AUG-12:50 | 22022.93 | 29-AUG-15:20 | 0.00 |
September | 0.832953E+10 | 0.195323E+10 | 161.69 | 0.686152E+10 | 0.146800E+10 | 0.00 | 1.00 | 01-SEP-09:00 | 0.00 | 01-SEP-00:10 | 73530.34 | 01-SEP-14:00 | 66856.31 | 01-SEP-15:40 | 18375.00 | 01-SEP-12:40 | 16122.69 | 01-SEP-14:00 | 0.00 |
October | 0.114326E+10 | 0.280986E+09 | 36.45 | 0.107773E+10 | 65530975.41 | 0.00 | 0.75 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 25735.67 | 19-OCT-15:00 | 25735.67 | 19-OCT-15:00 | 4139.81 | 22-OCT-12:02 | 5812.54 | 19-OCT-15:00 | 0.00 |
November | 0.182010E+09 | 47160419.11 | 18.57 | 0.128139E+09 | 53870841.51 | 0.00 | 0.29 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 9013.93 | 01-NOV-15:00 | 6145.19 | 01-NOV-15:00 | 2868.74 | 01-NOV-15:00 | 2289.97 | 01-NOV-15:00 | 0.00 |
December | 3092659.66 | 830326.05 | 0.99 | 3072280.35 | 20379.30 | 0.00 | 0.14 | 06-DEC-07:01 | 0.00 | 01-DEC-00:10 | 4210.79 | 06-DEC-07:01 | 4210.79 | 06-DEC-07:01 | 56.73 | 06-DEC-07:15 | 1109.52 | 06-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.161443E+12 | 0.365902E+11 | 1662.01 | 0.126375E+12 | 0.350686E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2512360.55 | 678402.32 | 0.99 | 2512360.55 | 0.00 | 0.00 | 0.10 | 0.00 | 3078.26 | 3078.26 | 0.00 | 818.28 | 0.00 | ||||||
Maximum of Months | 0.530277E+11 | 0.118546E+11 | 395.66 | 0.399569E+11 | 0.130708E+11 | 0.00 | 1.00 | 0.00 | 126707.88 | 81484.45 | 82791.18 | 27236.37 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 386.51 | 0.00 | 386.51 | 6.56 | 3152.93 | 0.00 | 0.00 | 0.00 |
February | 593.70 | 0.00 | 593.70 | 60.56 | 2477.77 | 0.00 | 0.00 | 0.00 |
March | 730.45 | 0.00 | 730.45 | 138.80 | 1917.01 | 0.00 | 0.00 | 0.00 |
April | 957.57 | 7.47 | 950.10 | 478.37 | 1148.90 | 0.00 | 0.00 | 0.00 |
May | 1346.79 | 72.52 | 1274.27 | 1196.71 | 630.74 | 0.00 | 0.00 | 0.00 |
June | 1503.04 | 165.22 | 1337.81 | 1620.25 | 439.81 | 0.00 | 0.00 | 0.00 |
July | 1435.64 | 123.20 | 1312.43 | 1618.62 | 414.87 | 0.00 | 0.00 | 0.00 |
August | 1090.41 | 18.73 | 1071.69 | 1115.62 | 484.59 | 0.00 | 0.00 | 0.00 |
September | 849.73 | 0.21 | 849.52 | 653.42 | 775.55 | 0.00 | 0.00 | 0.00 |
October | 590.01 | 0.00 | 590.01 | 245.47 | 1156.05 | 0.00 | 0.00 | 0.00 |
November | 390.66 | 0.00 | 390.66 | 40.32 | 1790.96 | 0.00 | 0.00 | 0.00 |
December | 327.48 | 0.00 | 327.48 | 1.11 | 3014.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 851.45 | 32.43 | 819.02 | 601.30 | 1446.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.48 | 0.00 | 327.48 | 1.11 | 414.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1503.04 | 165.22 | 1337.81 | 1620.25 | 3152.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 564.93 | 235.82 | 329.11 | 223.30 | 1894.37 | 0.00 | 0.00 | 0.00 |
February | 887.73 | 378.67 | 509.06 | 534.78 | 1483.85 | 0.00 | 0.00 | 0.00 |
March | 1209.59 | 606.75 | 602.84 | 918.63 | 1172.99 | 0.00 | 0.00 | 0.00 |
April | 1676.84 | 904.45 | 772.39 | 1600.51 | 727.77 | 0.00 | 0.00 | 0.00 |
May | 1814.83 | 797.82 | 1017.01 | 1960.01 | 426.04 | 0.00 | 0.00 | 0.00 |
June | 2054.52 | 982.79 | 1071.73 | 2416.68 | 299.94 | 0.00 | 0.00 | 0.00 |
July | 2012.67 | 945.02 | 1067.65 | 2429.19 | 280.03 | 0.00 | 0.00 | 0.00 |
August | 1551.77 | 678.23 | 873.54 | 1802.07 | 321.81 | 0.00 | 0.00 | 0.00 |
September | 1242.71 | 556.23 | 686.48 | 1289.97 | 494.95 | 0.00 | 0.00 | 0.00 |
October | 752.48 | 285.34 | 467.14 | 592.68 | 732.07 | 0.00 | 0.00 | 0.00 |
November | 479.04 | 160.15 | 318.88 | 238.47 | 1105.43 | 0.00 | 0.00 | 0.00 |
December | 437.12 | 161.57 | 275.55 | 138.40 | 1834.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1224.92 | 558.19 | 666.73 | 1181.74 | 895.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 437.12 | 160.15 | 275.55 | 138.40 | 280.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2054.52 | 982.79 | 1071.73 | 2429.19 | 1894.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2661.50 | 1851.55 | 809.95 | 2233.04 | 2525.38 | 0.00 | 0.00 | 0.00 |
February | 3370.10 | 2276.28 | 1093.82 | 3176.85 | 2111.87 | 0.00 | 0.00 | 0.00 |
March | 2969.46 | 1879.26 | 1090.21 | 2862.54 | 1757.66 | 0.00 | 0.00 | 0.00 |
April | 2690.24 | 1460.19 | 1230.05 | 2825.23 | 1177.33 | 0.00 | 0.00 | 0.00 |
May | 2261.79 | 773.25 | 1488.53 | 2565.79 | 696.05 | 0.00 | 0.00 | 0.00 |
June | 2029.45 | 540.94 | 1488.52 | 2457.27 | 478.86 | 0.00 | 0.00 | 0.00 |
July | 2218.85 | 702.92 | 1515.93 | 2801.28 | 445.79 | 0.00 | 0.00 | 0.00 |
August | 2369.61 | 991.19 | 1378.42 | 2904.75 | 512.98 | 0.00 | 0.00 | 0.00 |
September | 2538.20 | 1351.78 | 1186.42 | 2886.95 | 789.93 | 0.00 | 0.00 | 0.00 |
October | 2167.45 | 1274.78 | 892.66 | 2197.88 | 1117.75 | 0.00 | 0.00 | 0.00 |
November | 1930.72 | 1211.72 | 719.00 | 1738.00 | 1582.90 | 0.00 | 0.00 | 0.00 |
December | 2055.00 | 1347.49 | 707.51 | 1592.25 | 2438.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2432.42 | 1298.93 | 1133.50 | 2515.23 | 1299.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1930.72 | 540.94 | 707.51 | 1592.25 | 445.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3370.10 | 2276.28 | 1515.93 | 3176.85 | 2525.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 570.97 | 239.09 | 331.88 | 245.98 | 1937.89 | 0.00 | 0.00 | 0.00 |
February | 930.28 | 424.89 | 505.39 | 616.90 | 1543.33 | 0.00 | 0.00 | 0.00 |
March | 1224.18 | 626.40 | 597.77 | 972.70 | 1220.78 | 0.00 | 0.00 | 0.00 |
April | 1563.82 | 792.06 | 771.76 | 1492.63 | 769.50 | 0.00 | 0.00 | 0.00 |
May | 1921.43 | 916.53 | 1004.90 | 2136.39 | 457.62 | 0.00 | 0.00 | 0.00 |
June | 1854.14 | 801.72 | 1052.42 | 2184.17 | 317.46 | 0.00 | 0.00 | 0.00 |
July | 1979.47 | 920.25 | 1059.22 | 2402.39 | 301.93 | 0.00 | 0.00 | 0.00 |
August | 1628.97 | 740.20 | 888.78 | 1922.42 | 340.88 | 0.00 | 0.00 | 0.00 |
September | 1273.11 | 571.99 | 701.12 | 1346.04 | 517.89 | 0.00 | 0.00 | 0.00 |
October | 804.23 | 322.85 | 481.38 | 676.72 | 755.99 | 0.00 | 0.00 | 0.00 |
November | 488.45 | 164.69 | 323.76 | 258.60 | 1133.07 | 0.00 | 0.00 | 0.00 |
December | 435.43 | 152.40 | 283.02 | 138.94 | 1867.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1224.49 | 556.88 | 667.61 | 1202.95 | 927.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.43 | 152.40 | 283.02 | 138.94 | 301.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1979.47 | 920.25 | 1059.22 | 2402.39 | 1937.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.83 | 0.00 | 128.83 | 1.95 | 1051.34 | 0.00 | 0.00 | 0.00 |
February | 197.89 | 0.00 | 197.89 | 20.27 | 830.40 | 0.00 | 0.00 | 0.00 |
March | 243.47 | 0.00 | 243.47 | 50.03 | 634.67 | 0.00 | 0.00 | 0.00 |
April | 319.18 | 2.49 | 316.68 | 173.09 | 375.14 | 0.00 | 0.00 | 0.00 |
May | 448.91 | 24.17 | 424.74 | 416.67 | 200.79 | 0.00 | 0.00 | 0.00 |
June | 500.99 | 55.07 | 445.92 | 552.68 | 141.84 | 0.00 | 0.00 | 0.00 |
July | 478.52 | 41.07 | 437.46 | 546.88 | 136.89 | 0.00 | 0.00 | 0.00 |
August | 363.45 | 6.24 | 357.21 | 374.04 | 165.72 | 0.00 | 0.00 | 0.00 |
September | 283.23 | 0.07 | 283.16 | 214.71 | 275.08 | 0.00 | 0.00 | 0.00 |
October | 196.66 | 0.00 | 196.66 | 75.80 | 417.83 | 0.00 | 0.00 | 0.00 |
November | 130.21 | 0.00 | 130.21 | 12.05 | 631.70 | 0.00 | 0.00 | 0.00 |
December | 109.15 | 0.00 | 109.15 | 0.10 | 1016.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.80 | 10.81 | 273.00 | 204.31 | 488.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.15 | 0.00 | 109.15 | 0.10 | 136.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 500.99 | 55.07 | 445.92 | 552.68 | 1051.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.83 | 0.00 | 128.83 | 1.95 | 1051.40 | 0.00 | 0.00 | 0.00 |
February | 197.90 | 0.00 | 197.90 | 20.27 | 830.45 | 0.00 | 0.00 | 0.00 |
March | 243.48 | 0.00 | 243.48 | 50.03 | 634.71 | 0.00 | 0.00 | 0.00 |
April | 319.19 | 2.49 | 316.70 | 173.09 | 375.16 | 0.00 | 0.00 | 0.00 |
May | 448.93 | 24.17 | 424.75 | 416.68 | 200.81 | 0.00 | 0.00 | 0.00 |
June | 501.01 | 55.07 | 445.93 | 552.70 | 141.85 | 0.00 | 0.00 | 0.00 |
July | 478.54 | 41.07 | 437.47 | 546.90 | 136.90 | 0.00 | 0.00 | 0.00 |
August | 363.47 | 6.24 | 357.23 | 374.06 | 165.73 | 0.00 | 0.00 | 0.00 |
September | 283.24 | 0.07 | 283.17 | 214.71 | 275.09 | 0.00 | 0.00 | 0.00 |
October | 196.67 | 0.00 | 196.67 | 75.80 | 417.85 | 0.00 | 0.00 | 0.00 |
November | 130.22 | 0.00 | 130.22 | 12.05 | 631.74 | 0.00 | 0.00 | 0.00 |
December | 109.16 | 0.00 | 109.16 | 0.10 | 1016.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.81 | 10.81 | 273.01 | 204.32 | 488.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.16 | 0.00 | 109.16 | 0.10 | 136.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 501.01 | 55.07 | 445.93 | 552.70 | 1051.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.83 | 0.00 | 128.83 | 1.95 | 1051.40 | 0.00 | 0.00 | 0.00 |
February | 197.90 | 0.00 | 197.90 | 20.27 | 830.45 | 0.00 | 0.00 | 0.00 |
March | 243.48 | 0.00 | 243.48 | 50.03 | 634.71 | 0.00 | 0.00 | 0.00 |
April | 319.19 | 2.49 | 316.70 | 173.09 | 375.16 | 0.00 | 0.00 | 0.00 |
May | 448.93 | 24.17 | 424.75 | 416.68 | 200.81 | 0.00 | 0.00 | 0.00 |
June | 501.01 | 55.07 | 445.93 | 552.70 | 141.85 | 0.00 | 0.00 | 0.00 |
July | 478.54 | 41.07 | 437.47 | 546.90 | 136.90 | 0.00 | 0.00 | 0.00 |
August | 363.47 | 6.24 | 357.23 | 374.06 | 165.73 | 0.00 | 0.00 | 0.00 |
September | 283.24 | 0.07 | 283.17 | 214.71 | 275.09 | 0.00 | 0.00 | 0.00 |
October | 196.67 | 0.00 | 196.67 | 75.80 | 417.85 | 0.00 | 0.00 | 0.00 |
November | 130.22 | 0.00 | 130.22 | 12.05 | 631.74 | 0.00 | 0.00 | 0.00 |
December | 109.16 | 0.00 | 109.16 | 0.10 | 1016.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 283.81 | 10.81 | 273.01 | 204.32 | 488.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.16 | 0.00 | 109.16 | 0.10 | 136.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 501.01 | 55.07 | 445.93 | 552.70 | 1051.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 543.43 | 226.84 | 316.59 | 217.23 | 1831.08 | 0.00 | 0.00 | 0.00 |
February | 853.95 | 364.26 | 489.70 | 518.51 | 1445.04 | 0.00 | 0.00 | 0.00 |
March | 1163.56 | 583.66 | 579.90 | 897.59 | 1134.10 | 0.00 | 0.00 | 0.00 |
April | 1613.04 | 870.04 | 743.00 | 1560.04 | 709.99 | 0.00 | 0.00 | 0.00 |
May | 1745.78 | 767.46 | 978.32 | 1909.09 | 408.17 | 0.00 | 0.00 | 0.00 |
June | 1976.34 | 945.39 | 1030.95 | 2342.95 | 291.96 | 0.00 | 0.00 | 0.00 |
July | 1936.09 | 909.06 | 1027.03 | 2346.68 | 277.97 | 0.00 | 0.00 | 0.00 |
August | 1492.73 | 652.42 | 840.30 | 1735.42 | 331.27 | 0.00 | 0.00 | 0.00 |
September | 1195.42 | 535.06 | 660.36 | 1231.89 | 518.36 | 0.00 | 0.00 | 0.00 |
October | 723.85 | 274.48 | 449.37 | 554.72 | 771.52 | 0.00 | 0.00 | 0.00 |
November | 460.81 | 154.06 | 306.75 | 224.17 | 1131.80 | 0.00 | 0.00 | 0.00 |
December | 420.48 | 155.42 | 265.07 | 132.81 | 1791.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1178.31 | 536.95 | 641.36 | 1142.16 | 884.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 420.48 | 154.06 | 265.07 | 132.81 | 277.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1976.34 | 945.39 | 1030.95 | 2346.68 | 1831.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.49 | 8.97 | 12.52 | 8.59 | 72.40 | 0.00 | 0.00 | 0.00 |
February | 33.76 | 14.40 | 19.36 | 20.50 | 57.14 | 0.00 | 0.00 | 0.00 |
March | 46.01 | 23.08 | 22.93 | 35.49 | 44.84 | 0.00 | 0.00 | 0.00 |
April | 63.78 | 34.40 | 29.38 | 61.68 | 28.07 | 0.00 | 0.00 | 0.00 |
May | 69.03 | 30.34 | 38.68 | 75.48 | 16.14 | 0.00 | 0.00 | 0.00 |
June | 78.14 | 37.38 | 40.76 | 92.64 | 11.54 | 0.00 | 0.00 | 0.00 |
July | 76.55 | 35.94 | 40.61 | 92.79 | 10.99 | 0.00 | 0.00 | 0.00 |
August | 59.02 | 25.80 | 33.22 | 68.62 | 13.10 | 0.00 | 0.00 | 0.00 |
September | 47.27 | 21.16 | 26.11 | 48.71 | 20.50 | 0.00 | 0.00 | 0.00 |
October | 28.62 | 10.85 | 17.77 | 21.93 | 30.51 | 0.00 | 0.00 | 0.00 |
November | 18.22 | 6.09 | 12.13 | 8.86 | 44.75 | 0.00 | 0.00 | 0.00 |
December | 16.63 | 6.15 | 10.48 | 5.25 | 70.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.59 | 21.23 | 25.36 | 45.16 | 34.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 6.09 | 10.48 | 5.25 | 10.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.14 | 37.38 | 40.76 | 92.79 | 72.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 887.15 | 617.17 | 269.98 | 763.00 | 831.68 | 0.00 | 0.00 | 0.00 |
February | 1123.34 | 758.74 | 364.60 | 1078.26 | 712.72 | 0.00 | 0.00 | 0.00 |
March | 989.80 | 626.41 | 363.40 | 973.83 | 589.68 | 0.00 | 0.00 | 0.00 |
April | 896.73 | 486.72 | 410.01 | 958.27 | 397.36 | 0.00 | 0.00 | 0.00 |
May | 753.92 | 257.74 | 496.17 | 871.72 | 228.45 | 0.00 | 0.00 | 0.00 |
June | 676.48 | 180.31 | 496.17 | 832.38 | 156.57 | 0.00 | 0.00 | 0.00 |
July | 739.61 | 234.30 | 505.31 | 940.78 | 151.91 | 0.00 | 0.00 | 0.00 |
August | 789.86 | 330.39 | 459.47 | 972.52 | 182.35 | 0.00 | 0.00 | 0.00 |
September | 846.05 | 450.59 | 395.47 | 963.84 | 286.69 | 0.00 | 0.00 | 0.00 |
October | 722.47 | 424.92 | 297.55 | 729.41 | 410.74 | 0.00 | 0.00 | 0.00 |
November | 643.56 | 403.90 | 239.66 | 580.43 | 561.09 | 0.00 | 0.00 | 0.00 |
December | 684.99 | 449.15 | 235.83 | 540.68 | 811.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.79 | 432.97 | 377.83 | 848.74 | 442.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 643.56 | 180.31 | 235.83 | 540.68 | 151.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1123.34 | 758.74 | 505.31 | 1078.26 | 831.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 887.15 | 617.17 | 269.98 | 763.00 | 831.68 | 0.00 | 0.00 | 0.00 |
February | 1123.34 | 758.74 | 364.60 | 1078.26 | 712.72 | 0.00 | 0.00 | 0.00 |
March | 989.80 | 626.41 | 363.40 | 973.83 | 589.68 | 0.00 | 0.00 | 0.00 |
April | 896.73 | 486.72 | 410.01 | 958.27 | 397.36 | 0.00 | 0.00 | 0.00 |
May | 753.92 | 257.74 | 496.17 | 871.72 | 228.45 | 0.00 | 0.00 | 0.00 |
June | 676.48 | 180.31 | 496.17 | 832.38 | 156.57 | 0.00 | 0.00 | 0.00 |
July | 739.61 | 234.30 | 505.31 | 940.78 | 151.91 | 0.00 | 0.00 | 0.00 |
August | 789.86 | 330.39 | 459.47 | 972.52 | 182.35 | 0.00 | 0.00 | 0.00 |
September | 846.05 | 450.59 | 395.47 | 963.84 | 286.69 | 0.00 | 0.00 | 0.00 |
October | 722.47 | 424.92 | 297.55 | 729.41 | 410.74 | 0.00 | 0.00 | 0.00 |
November | 643.56 | 403.90 | 239.66 | 580.43 | 561.09 | 0.00 | 0.00 | 0.00 |
December | 684.99 | 449.15 | 235.83 | 540.68 | 811.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.79 | 432.97 | 377.83 | 848.74 | 442.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 643.56 | 180.31 | 235.83 | 540.68 | 151.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1123.34 | 758.74 | 505.31 | 1078.26 | 831.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 887.09 | 617.13 | 269.96 | 762.96 | 831.63 | 0.00 | 0.00 | 0.00 |
February | 1123.27 | 758.70 | 364.58 | 1078.19 | 712.68 | 0.00 | 0.00 | 0.00 |
March | 989.74 | 626.37 | 363.37 | 973.77 | 589.64 | 0.00 | 0.00 | 0.00 |
April | 896.68 | 486.69 | 409.99 | 958.21 | 397.34 | 0.00 | 0.00 | 0.00 |
May | 753.87 | 257.73 | 496.14 | 871.67 | 228.44 | 0.00 | 0.00 | 0.00 |
June | 676.43 | 180.30 | 496.14 | 832.33 | 156.56 | 0.00 | 0.00 | 0.00 |
July | 739.56 | 234.29 | 505.27 | 940.72 | 151.90 | 0.00 | 0.00 | 0.00 |
August | 789.81 | 330.37 | 459.44 | 972.46 | 182.34 | 0.00 | 0.00 | 0.00 |
September | 846.00 | 450.56 | 395.44 | 963.78 | 286.67 | 0.00 | 0.00 | 0.00 |
October | 722.42 | 424.89 | 297.53 | 729.36 | 410.72 | 0.00 | 0.00 | 0.00 |
November | 643.52 | 403.87 | 239.65 | 580.39 | 561.05 | 0.00 | 0.00 | 0.00 |
December | 684.94 | 449.12 | 235.82 | 540.65 | 811.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 810.74 | 432.94 | 377.80 | 848.68 | 442.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 643.52 | 180.30 | 235.82 | 540.65 | 151.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1123.27 | 758.70 | 505.27 | 1078.19 | 831.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 549.25 | 229.99 | 319.26 | 241.29 | 1870.80 | 0.00 | 0.00 | 0.00 |
February | 894.89 | 408.72 | 486.16 | 603.08 | 1502.78 | 0.00 | 0.00 | 0.00 |
March | 1177.60 | 602.57 | 575.03 | 952.51 | 1181.56 | 0.00 | 0.00 | 0.00 |
April | 1504.32 | 761.92 | 742.40 | 1458.33 | 749.58 | 0.00 | 0.00 | 0.00 |
May | 1848.33 | 881.66 | 966.67 | 2076.51 | 442.10 | 0.00 | 0.00 | 0.00 |
June | 1783.59 | 771.21 | 1012.38 | 2119.05 | 307.23 | 0.00 | 0.00 | 0.00 |
July | 1904.16 | 885.23 | 1018.93 | 2319.03 | 302.24 | 0.00 | 0.00 | 0.00 |
August | 1567.00 | 712.03 | 854.96 | 1849.41 | 351.75 | 0.00 | 0.00 | 0.00 |
September | 1224.67 | 550.22 | 674.44 | 1285.27 | 542.93 | 0.00 | 0.00 | 0.00 |
October | 773.63 | 310.57 | 463.06 | 638.14 | 796.96 | 0.00 | 0.00 | 0.00 |
November | 469.87 | 158.42 | 311.45 | 245.22 | 1156.08 | 0.00 | 0.00 | 0.00 |
December | 418.86 | 146.60 | 272.26 | 134.44 | 1819.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1177.90 | 535.69 | 642.21 | 1163.49 | 916.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.86 | 146.60 | 272.26 | 134.44 | 302.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1904.16 | 885.23 | 1018.93 | 2319.03 | 1870.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.72 | 9.09 | 12.62 | 9.54 | 73.97 | 0.00 | 0.00 | 0.00 |
February | 35.38 | 16.16 | 19.22 | 23.84 | 59.42 | 0.00 | 0.00 | 0.00 |
March | 46.56 | 23.82 | 22.74 | 37.66 | 46.72 | 0.00 | 0.00 | 0.00 |
April | 59.48 | 30.13 | 29.35 | 57.66 | 29.64 | 0.00 | 0.00 | 0.00 |
May | 73.08 | 34.86 | 38.22 | 82.10 | 17.48 | 0.00 | 0.00 | 0.00 |
June | 70.52 | 30.49 | 40.03 | 83.79 | 12.15 | 0.00 | 0.00 | 0.00 |
July | 75.29 | 35.00 | 40.29 | 91.69 | 11.95 | 0.00 | 0.00 | 0.00 |
August | 61.96 | 28.15 | 33.80 | 73.12 | 13.91 | 0.00 | 0.00 | 0.00 |
September | 48.42 | 21.76 | 26.67 | 50.82 | 21.47 | 0.00 | 0.00 | 0.00 |
October | 30.59 | 12.28 | 18.31 | 25.23 | 31.51 | 0.00 | 0.00 | 0.00 |
November | 18.58 | 6.26 | 12.31 | 9.70 | 45.71 | 0.00 | 0.00 | 0.00 |
December | 16.56 | 5.80 | 10.76 | 5.32 | 71.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 46.57 | 21.18 | 25.39 | 46.00 | 36.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.56 | 5.80 | 10.76 | 5.32 | 11.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.29 | 35.00 | 40.29 | 91.69 | 73.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 386.51 | 0.00 | 386.51 | 5.35 | 3207.45 | 0.00 | 0.00 | 0.00 |
February | 593.70 | 0.00 | 593.70 | 55.22 | 2545.01 | 0.00 | 0.00 | 0.00 |
March | 730.45 | 0.00 | 730.45 | 130.39 | 1985.80 | 0.00 | 0.00 | 0.00 |
April | 957.57 | 7.47 | 950.10 | 460.33 | 1214.07 | 0.00 | 0.00 | 0.00 |
May | 1346.79 | 72.52 | 1274.27 | 1183.39 | 656.29 | 0.00 | 0.00 | 0.00 |
June | 1503.04 | 165.22 | 1337.81 | 1612.96 | 455.79 | 0.00 | 0.00 | 0.00 |
July | 1435.64 | 123.20 | 1312.43 | 1613.56 | 428.09 | 0.00 | 0.00 | 0.00 |
August | 1090.41 | 18.73 | 1071.69 | 1108.36 | 506.13 | 0.00 | 0.00 | 0.00 |
September | 849.73 | 0.21 | 849.52 | 635.28 | 825.48 | 0.00 | 0.00 | 0.00 |
October | 590.01 | 0.00 | 590.01 | 224.05 | 1242.35 | 0.00 | 0.00 | 0.00 |
November | 390.66 | 0.00 | 390.66 | 35.15 | 1884.60 | 0.00 | 0.00 | 0.00 |
December | 327.48 | 0.00 | 327.48 | 0.34 | 3078.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 851.45 | 32.43 | 819.02 | 592.02 | 1498.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.48 | 0.00 | 327.48 | 0.34 | 428.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1503.04 | 165.22 | 1337.81 | 1613.56 | 3207.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 564.93 | 235.82 | 329.11 | 220.28 | 1926.56 | 0.00 | 0.00 | 0.00 |
February | 887.73 | 378.67 | 509.06 | 526.64 | 1525.13 | 0.00 | 0.00 | 0.00 |
March | 1209.59 | 606.75 | 602.84 | 908.63 | 1215.10 | 0.00 | 0.00 | 0.00 |
April | 1676.84 | 904.45 | 772.39 | 1588.56 | 764.54 | 0.00 | 0.00 | 0.00 |
May | 1814.83 | 797.82 | 1017.01 | 1954.00 | 441.27 | 0.00 | 0.00 | 0.00 |
June | 2054.52 | 982.79 | 1071.73 | 2414.63 | 310.39 | 0.00 | 0.00 | 0.00 |
July | 2012.67 | 945.02 | 1067.65 | 2427.79 | 288.71 | 0.00 | 0.00 | 0.00 |
August | 1551.77 | 678.23 | 873.54 | 1799.18 | 335.27 | 0.00 | 0.00 | 0.00 |
September | 1242.71 | 556.23 | 686.48 | 1279.29 | 522.52 | 0.00 | 0.00 | 0.00 |
October | 752.48 | 285.34 | 467.14 | 577.64 | 781.11 | 0.00 | 0.00 | 0.00 |
November | 479.04 | 160.15 | 318.88 | 230.78 | 1162.58 | 0.00 | 0.00 | 0.00 |
December | 437.12 | 161.57 | 275.55 | 135.60 | 1874.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1224.92 | 558.19 | 666.73 | 1174.96 | 926.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 437.12 | 160.15 | 275.55 | 135.60 | 288.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2054.52 | 982.79 | 1071.73 | 2427.79 | 1926.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2661.50 | 1851.55 | 809.95 | 2221.83 | 2577.41 | 0.00 | 0.00 | 0.00 |
February | 3370.10 | 2276.28 | 1093.82 | 3159.83 | 2180.40 | 0.00 | 0.00 | 0.00 |
March | 2969.46 | 1879.26 | 1090.21 | 2847.87 | 1824.43 | 0.00 | 0.00 | 0.00 |
April | 2690.24 | 1460.19 | 1230.05 | 2810.31 | 1239.09 | 0.00 | 0.00 | 0.00 |
May | 2261.79 | 773.25 | 1488.53 | 2558.54 | 725.47 | 0.00 | 0.00 | 0.00 |
June | 2029.45 | 540.94 | 1488.52 | 2452.36 | 498.77 | 0.00 | 0.00 | 0.00 |
July | 2218.85 | 702.92 | 1515.93 | 2798.44 | 462.16 | 0.00 | 0.00 | 0.00 |
August | 2369.61 | 991.19 | 1378.42 | 2900.44 | 536.64 | 0.00 | 0.00 | 0.00 |
September | 2538.20 | 1351.78 | 1186.42 | 2873.26 | 836.32 | 0.00 | 0.00 | 0.00 |
October | 2167.45 | 1274.78 | 892.66 | 2173.34 | 1194.63 | 0.00 | 0.00 | 0.00 |
November | 1930.72 | 1211.72 | 719.00 | 1718.18 | 1667.66 | 0.00 | 0.00 | 0.00 |
December | 2055.00 | 1347.49 | 707.51 | 1579.50 | 2498.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2432.42 | 1298.93 | 1133.50 | 2502.95 | 1349.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1930.72 | 540.94 | 707.51 | 1579.50 | 462.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3370.10 | 2276.28 | 1515.93 | 3159.83 | 2577.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 570.97 | 239.09 | 331.88 | 244.06 | 1970.26 | 0.00 | 0.00 | 0.00 |
February | 930.28 | 424.89 | 505.39 | 611.45 | 1586.04 | 0.00 | 0.00 | 0.00 |
March | 1224.18 | 626.40 | 597.77 | 966.35 | 1265.05 | 0.00 | 0.00 | 0.00 |
April | 1563.82 | 792.06 | 771.76 | 1482.59 | 809.86 | 0.00 | 0.00 | 0.00 |
May | 1921.43 | 916.53 | 1004.90 | 2130.35 | 476.57 | 0.00 | 0.00 | 0.00 |
June | 1854.14 | 801.72 | 1052.42 | 2180.23 | 330.25 | 0.00 | 0.00 | 0.00 |
July | 1979.47 | 920.25 | 1059.22 | 2400.37 | 312.47 | 0.00 | 0.00 | 0.00 |
August | 1628.97 | 740.20 | 888.78 | 1917.77 | 356.39 | 0.00 | 0.00 | 0.00 |
September | 1273.11 | 571.99 | 701.12 | 1334.46 | 548.94 | 0.00 | 0.00 | 0.00 |
October | 804.23 | 322.85 | 481.38 | 663.02 | 807.69 | 0.00 | 0.00 | 0.00 |
November | 488.45 | 164.69 | 323.76 | 251.53 | 1190.51 | 0.00 | 0.00 | 0.00 |
December | 435.43 | 152.40 | 283.02 | 136.45 | 1906.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1224.49 | 556.88 | 667.61 | 1196.70 | 960.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.43 | 152.40 | 283.02 | 136.45 | 312.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1979.47 | 920.25 | 1059.22 | 2400.37 | 1970.26 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103522E+10 | 0.00 | 0.103522E+10 | 17572768.65 | 0.844481E+10 |
February | 0.143628E+10 | 0.00 | 0.143628E+10 | 0.146496E+09 | 0.599423E+10 |
March | 0.195643E+10 | 0.00 | 0.195643E+10 | 0.371752E+09 | 0.513451E+10 |
April | 0.248202E+10 | 19371904.28 | 0.246265E+10 | 0.123992E+10 | 0.297796E+10 |
May | 0.360724E+10 | 0.194244E+09 | 0.341299E+10 | 0.320528E+10 | 0.168937E+10 |
June | 0.389587E+10 | 0.428260E+09 | 0.346761E+10 | 0.419970E+10 | 0.113999E+10 |
July | 0.384521E+10 | 0.329992E+09 | 0.351522E+10 | 0.433530E+10 | 0.111120E+10 |
August | 0.292056E+10 | 50154901.34 | 0.287040E+10 | 0.298808E+10 | 0.129793E+10 |
September | 0.220249E+10 | 539900.92 | 0.220195E+10 | 0.169367E+10 | 0.201023E+10 |
October | 0.158027E+10 | 0.00 | 0.158027E+10 | 0.657479E+09 | 0.309637E+10 |
November | 0.101259E+10 | 0.00 | 0.101259E+10 | 0.104514E+09 | 0.464217E+10 |
December | 0.877119E+09 | 0.00 | 0.877119E+09 | 2978563.60 | 0.807304E+10 |
Annual Sum or Average | 0.268513E+11 | 0.102256E+10 | 0.258287E+11 | 0.189627E+11 | 0.456118E+11 |
Minimum of Months | 0.877119E+09 | 0.00 | 0.877119E+09 | 2978563.60 | 0.111120E+10 |
Maximum of Months | 0.389587E+10 | 0.428260E+09 | 0.351522E+10 | 0.433530E+10 | 0.844481E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151310E+10 | 0.631613E+09 | 0.881483E+09 | 0.598089E+09 | 0.507388E+10 |
February | 0.214760E+10 | 0.916068E+09 | 0.123153E+10 | 0.129375E+10 | 0.358972E+10 |
March | 0.323976E+10 | 0.162511E+10 | 0.161465E+10 | 0.246046E+10 | 0.314173E+10 |
April | 0.434637E+10 | 0.234435E+10 | 0.200202E+10 | 0.414852E+10 | 0.188638E+10 |
May | 0.486085E+10 | 0.213689E+10 | 0.272397E+10 | 0.524970E+10 | 0.114110E+10 |
June | 0.532531E+10 | 0.254739E+10 | 0.277792E+10 | 0.626403E+10 | 0.777451E+09 |
July | 0.539074E+10 | 0.253115E+10 | 0.285959E+10 | 0.650633E+10 | 0.750035E+09 |
August | 0.415627E+10 | 0.181658E+10 | 0.233969E+10 | 0.482668E+10 | 0.861926E+09 |
September | 0.322110E+10 | 0.144175E+10 | 0.177935E+10 | 0.334361E+10 | 0.128292E+10 |
October | 0.201545E+10 | 0.764255E+09 | 0.125120E+10 | 0.158743E+10 | 0.196079E+10 |
November | 0.124166E+10 | 0.415116E+09 | 0.826546E+09 | 0.618112E+09 | 0.286528E+10 |
December | 0.117077E+10 | 0.432736E+09 | 0.738036E+09 | 0.370691E+09 | 0.491445E+10 |
Annual Sum or Average | 0.386290E+11 | 0.176030E+11 | 0.210260E+11 | 0.372674E+11 | 0.282457E+11 |
Minimum of Months | 0.117077E+10 | 0.415116E+09 | 0.738036E+09 | 0.370691E+09 | 0.750035E+09 |
Maximum of Months | 0.539074E+10 | 0.254739E+10 | 0.285959E+10 | 0.650633E+10 | 0.507388E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.712856E+10 | 0.495918E+10 | 0.216938E+10 | 0.598098E+10 | 0.676399E+10 |
February | 0.815294E+10 | 0.550678E+10 | 0.264616E+10 | 0.768543E+10 | 0.510903E+10 |
March | 0.795341E+10 | 0.503341E+10 | 0.292001E+10 | 0.766702E+10 | 0.470772E+10 |
April | 0.697310E+10 | 0.378480E+10 | 0.318830E+10 | 0.732300E+10 | 0.305164E+10 |
May | 0.605797E+10 | 0.207107E+10 | 0.398689E+10 | 0.687220E+10 | 0.186429E+10 |
June | 0.526035E+10 | 0.140211E+10 | 0.385823E+10 | 0.636924E+10 | 0.124121E+10 |
July | 0.594297E+10 | 0.188271E+10 | 0.406027E+10 | 0.750296E+10 | 0.119399E+10 |
August | 0.634676E+10 | 0.265480E+10 | 0.369196E+10 | 0.778009E+10 | 0.137397E+10 |
September | 0.657902E+10 | 0.350382E+10 | 0.307520E+10 | 0.748299E+10 | 0.204749E+10 |
October | 0.580529E+10 | 0.341438E+10 | 0.239091E+10 | 0.588680E+10 | 0.299378E+10 |
November | 0.500442E+10 | 0.314078E+10 | 0.186364E+10 | 0.450489E+10 | 0.410286E+10 |
December | 0.550410E+10 | 0.360911E+10 | 0.189500E+10 | 0.426469E+10 | 0.653023E+10 |
Annual Sum or Average | 0.767089E+11 | 0.409630E+11 | 0.357459E+11 | 0.793203E+11 | 0.409802E+11 |
Minimum of Months | 0.500442E+10 | 0.140211E+10 | 0.186364E+10 | 0.426469E+10 | 0.119399E+10 |
Maximum of Months | 0.815294E+10 | 0.550678E+10 | 0.406027E+10 | 0.778009E+10 | 0.676399E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152929E+10 | 0.640377E+09 | 0.888915E+09 | 0.658838E+09 | 0.519044E+10 |
February | 0.225054E+10 | 0.102790E+10 | 0.122264E+10 | 0.149241E+10 | 0.373362E+10 |
March | 0.327884E+10 | 0.167776E+10 | 0.160108E+10 | 0.260527E+10 | 0.326973E+10 |
April | 0.405343E+10 | 0.205302E+10 | 0.200040E+10 | 0.386888E+10 | 0.199456E+10 |
May | 0.514637E+10 | 0.245484E+10 | 0.269152E+10 | 0.572210E+10 | 0.122569E+10 |
June | 0.480593E+10 | 0.207805E+10 | 0.272788E+10 | 0.566136E+10 | 0.822863E+09 |
July | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.643455E+10 | 0.808687E+09 |
August | 0.436305E+10 | 0.198254E+10 | 0.238050E+10 | 0.514902E+10 | 0.913008E+09 |
September | 0.329989E+10 | 0.148259E+10 | 0.181730E+10 | 0.348895E+10 | 0.134238E+10 |
October | 0.215405E+10 | 0.864730E+09 | 0.128932E+10 | 0.181253E+10 | 0.202483E+10 |
November | 0.126606E+10 | 0.426868E+09 | 0.839194E+09 | 0.670288E+09 | 0.293692E+10 |
December | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.372134E+09 | 0.500145E+10 |
Annual Sum or Average | 0.386155E+11 | 0.175617E+11 | 0.210538E+11 | 0.379363E+11 | 0.292642E+11 |
Minimum of Months | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.372134E+09 | 0.808687E+09 |
Maximum of Months | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.643455E+10 | 0.519044E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345056E+09 | 0.00 | 0.345056E+09 | 5216082.88 | 0.281590E+10 |
February | 0.478739E+09 | 0.00 | 0.478739E+09 | 49032995.41 | 0.200890E+10 |
March | 0.652113E+09 | 0.00 | 0.652113E+09 | 0.133988E+09 | 0.169989E+10 |
April | 0.827302E+09 | 6456995.92 | 0.820845E+09 | 0.448649E+09 | 0.972362E+09 |
May | 0.120236E+10 | 64745049.35 | 0.113761E+10 | 0.111600E+10 | 0.537807E+09 |
June | 0.129856E+10 | 0.142747E+09 | 0.115582E+10 | 0.143256E+10 | 0.367657E+09 |
July | 0.128168E+10 | 0.109992E+09 | 0.117168E+10 | 0.146477E+10 | 0.366659E+09 |
August | 0.973473E+09 | 16717509.47 | 0.956755E+09 | 0.100184E+10 | 0.443870E+09 |
September | 0.734128E+09 | 179958.46 | 0.733948E+09 | 0.556523E+09 | 0.712998E+09 |
October | 0.526733E+09 | 0.00 | 0.526733E+09 | 0.203028E+09 | 0.111911E+10 |
November | 0.337513E+09 | 0.00 | 0.337513E+09 | 31222953.69 | 0.163737E+10 |
December | 0.292359E+09 | 0.00 | 0.292359E+09 | 259482.78 | 0.272374E+10 |
Annual Sum or Average | 0.895001E+10 | 0.340838E+09 | 0.860917E+10 | 0.644309E+10 | 0.154063E+11 |
Minimum of Months | 0.292359E+09 | 0.00 | 0.292359E+09 | 259482.78 | 0.366659E+09 |
Maximum of Months | 0.129856E+10 | 0.142747E+09 | 0.117168E+10 | 0.146477E+10 | 0.281590E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345069E+09 | 0.00 | 0.345069E+09 | 5215429.37 | 0.281608E+10 |
February | 0.478758E+09 | 0.00 | 0.478758E+09 | 49031804.05 | 0.200904E+10 |
March | 0.652139E+09 | 0.00 | 0.652139E+09 | 0.133987E+09 | 0.170000E+10 |
April | 0.827336E+09 | 6457169.48 | 0.820879E+09 | 0.448660E+09 | 0.972424E+09 |
May | 0.120240E+10 | 64746789.71 | 0.113766E+10 | 0.111603E+10 | 0.537840E+09 |
June | 0.129861E+10 | 0.142751E+09 | 0.115586E+10 | 0.143261E+10 | 0.367678E+09 |
July | 0.128173E+10 | 0.109995E+09 | 0.117173E+10 | 0.146483E+10 | 0.366680E+09 |
August | 0.973511E+09 | 16717958.84 | 0.956793E+09 | 0.100187E+10 | 0.443896E+09 |
September | 0.734157E+09 | 179963.30 | 0.733977E+09 | 0.556538E+09 | 0.713042E+09 |
October | 0.526752E+09 | 0.00 | 0.526752E+09 | 0.203028E+09 | 0.111918E+10 |
November | 0.337526E+09 | 0.00 | 0.337526E+09 | 31221980.11 | 0.163748E+10 |
December | 0.292370E+09 | 0.00 | 0.292370E+09 | 259322.05 | 0.272391E+10 |
Annual Sum or Average | 0.895036E+10 | 0.340847E+09 | 0.860951E+10 | 0.644328E+10 | 0.154072E+11 |
Minimum of Months | 0.292370E+09 | 0.00 | 0.292370E+09 | 259322.05 | 0.366680E+09 |
Maximum of Months | 0.129861E+10 | 0.142751E+09 | 0.117173E+10 | 0.146483E+10 | 0.281608E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345069E+09 | 0.00 | 0.345069E+09 | 5215429.37 | 0.281608E+10 |
February | 0.478758E+09 | 0.00 | 0.478758E+09 | 49031804.05 | 0.200904E+10 |
March | 0.652139E+09 | 0.00 | 0.652139E+09 | 0.133987E+09 | 0.170000E+10 |
April | 0.827336E+09 | 6457169.48 | 0.820879E+09 | 0.448660E+09 | 0.972424E+09 |
May | 0.120240E+10 | 64746789.71 | 0.113766E+10 | 0.111603E+10 | 0.537840E+09 |
June | 0.129861E+10 | 0.142751E+09 | 0.115586E+10 | 0.143261E+10 | 0.367678E+09 |
July | 0.128173E+10 | 0.109995E+09 | 0.117173E+10 | 0.146483E+10 | 0.366680E+09 |
August | 0.973511E+09 | 16717958.84 | 0.956793E+09 | 0.100187E+10 | 0.443896E+09 |
September | 0.734157E+09 | 179963.30 | 0.733977E+09 | 0.556538E+09 | 0.713042E+09 |
October | 0.526752E+09 | 0.00 | 0.526752E+09 | 0.203028E+09 | 0.111918E+10 |
November | 0.337526E+09 | 0.00 | 0.337526E+09 | 31221980.11 | 0.163748E+10 |
December | 0.292370E+09 | 0.00 | 0.292370E+09 | 259322.05 | 0.272391E+10 |
Annual Sum or Average | 0.895036E+10 | 0.340847E+09 | 0.860951E+10 | 0.644328E+10 | 0.154072E+11 |
Minimum of Months | 0.292370E+09 | 0.00 | 0.292370E+09 | 259322.05 | 0.366680E+09 |
Maximum of Months | 0.129861E+10 | 0.142751E+09 | 0.117173E+10 | 0.146483E+10 | 0.281608E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145552E+10 | 0.607578E+09 | 0.847943E+09 | 0.581819E+09 | 0.490437E+10 |
February | 0.206588E+10 | 0.881208E+09 | 0.118467E+10 | 0.125437E+10 | 0.349583E+10 |
March | 0.311649E+10 | 0.156327E+10 | 0.155322E+10 | 0.240411E+10 | 0.303757E+10 |
April | 0.418099E+10 | 0.225513E+10 | 0.192585E+10 | 0.404363E+10 | 0.184030E+10 |
May | 0.467589E+10 | 0.205557E+10 | 0.262033E+10 | 0.511332E+10 | 0.109325E+10 |
June | 0.512268E+10 | 0.245045E+10 | 0.267223E+10 | 0.607294E+10 | 0.756759E+09 |
July | 0.518562E+10 | 0.243483E+10 | 0.275079E+10 | 0.628535E+10 | 0.744527E+09 |
August | 0.399812E+10 | 0.174745E+10 | 0.225067E+10 | 0.464815E+10 | 0.887285E+09 |
September | 0.309854E+10 | 0.138689E+10 | 0.171165E+10 | 0.319305E+10 | 0.134359E+10 |
October | 0.193876E+10 | 0.735172E+09 | 0.120359E+10 | 0.148577E+10 | 0.206645E+10 |
November | 0.119442E+10 | 0.399319E+09 | 0.795097E+09 | 0.581041E+09 | 0.293361E+10 |
December | 0.112622E+10 | 0.416269E+09 | 0.709955E+09 | 0.355724E+09 | 0.479848E+10 |
Annual Sum or Average | 0.371591E+11 | 0.169331E+11 | 0.202260E+11 | 0.360193E+11 | 0.279020E+11 |
Minimum of Months | 0.112622E+10 | 0.399319E+09 | 0.709955E+09 | 0.355724E+09 | 0.744527E+09 |
Maximum of Months | 0.518562E+10 | 0.245045E+10 | 0.275079E+10 | 0.628535E+10 | 0.490437E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57550006.32 | 24023087.61 | 33526918.71 | 23004609.42 | 0.193914E+09 |
February | 81682978.44 | 34842185.26 | 46840793.18 | 49596856.10 | 0.138222E+09 |
March | 0.123223E+09 | 61810336.80 | 61412750.47 | 95056228.41 | 0.120103E+09 |
April | 0.165313E+09 | 89165950.93 | 76146551.59 | 0.159882E+09 | 72763741.42 |
May | 0.184881E+09 | 81275312.86 | 0.103605E+09 | 0.202176E+09 | 43226167.05 |
June | 0.202546E+09 | 96888717.44 | 0.105657E+09 | 0.240119E+09 | 29921574.89 |
July | 0.205035E+09 | 96271004.85 | 0.108764E+09 | 0.248517E+09 | 29437931.94 |
August | 0.158082E+09 | 69092693.72 | 88989413.14 | 0.183784E+09 | 35082437.20 |
September | 0.122513E+09 | 54836195.03 | 67677268.21 | 0.126250E+09 | 53124263.03 |
October | 76656879.45 | 29068036.99 | 47588842.46 | 58745916.86 | 81705540.02 |
November | 47226155.69 | 15788730.54 | 31437425.15 | 22973843.42 | 0.115992E+09 |
December | 44529874.72 | 16458896.41 | 28070978.31 | 14064990.51 | 0.189728E+09 |
Annual Sum or Average | 0.146924E+10 | 0.669521E+09 | 0.799717E+09 | 0.142417E+10 | 0.110322E+10 |
Minimum of Months | 44529874.72 | 15788730.54 | 28070978.31 | 14064990.51 | 29437931.94 |
Maximum of Months | 0.205035E+09 | 96888717.44 | 0.108764E+09 | 0.248517E+09 | 0.193914E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237614E+10 | 0.165303E+10 | 0.723116E+09 | 0.204363E+10 | 0.222757E+10 |
February | 0.271760E+10 | 0.183556E+10 | 0.882041E+09 | 0.260852E+10 | 0.172422E+10 |
March | 0.265109E+10 | 0.167777E+10 | 0.973325E+09 | 0.260831E+10 | 0.157939E+10 |
April | 0.232433E+10 | 0.126158E+10 | 0.106276E+10 | 0.248384E+10 | 0.102997E+10 |
May | 0.201929E+10 | 0.690344E+09 | 0.132895E+10 | 0.233482E+10 | 0.611891E+09 |
June | 0.175343E+10 | 0.467361E+09 | 0.128607E+10 | 0.215753E+10 | 0.405839E+09 |
July | 0.198097E+10 | 0.627556E+09 | 0.135341E+10 | 0.251978E+10 | 0.406874E+09 |
August | 0.211555E+10 | 0.884915E+09 | 0.123064E+10 | 0.260480E+10 | 0.488401E+09 |
September | 0.219297E+10 | 0.116792E+10 | 0.102505E+10 | 0.249828E+10 | 0.743106E+09 |
October | 0.193506E+10 | 0.113810E+10 | 0.796959E+09 | 0.195365E+10 | 0.110013E+10 |
November | 0.166811E+10 | 0.104691E+10 | 0.621204E+09 | 0.150447E+10 | 0.145434E+10 |
December | 0.183467E+10 | 0.120301E+10 | 0.631656E+09 | 0.144816E+10 | 0.217437E+10 |
Annual Sum or Average | 0.255692E+11 | 0.136540E+11 | 0.119152E+11 | 0.267658E+11 | 0.139461E+11 |
Minimum of Months | 0.166811E+10 | 0.467361E+09 | 0.621204E+09 | 0.144816E+10 | 0.405839E+09 |
Maximum of Months | 0.271760E+10 | 0.183556E+10 | 0.135341E+10 | 0.260852E+10 | 0.222757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237614E+10 | 0.165303E+10 | 0.723116E+09 | 0.204363E+10 | 0.222757E+10 |
February | 0.271760E+10 | 0.183556E+10 | 0.882041E+09 | 0.260852E+10 | 0.172422E+10 |
March | 0.265109E+10 | 0.167777E+10 | 0.973325E+09 | 0.260831E+10 | 0.157939E+10 |
April | 0.232433E+10 | 0.126158E+10 | 0.106276E+10 | 0.248384E+10 | 0.102997E+10 |
May | 0.201929E+10 | 0.690344E+09 | 0.132895E+10 | 0.233482E+10 | 0.611891E+09 |
June | 0.175343E+10 | 0.467361E+09 | 0.128607E+10 | 0.215753E+10 | 0.405839E+09 |
July | 0.198097E+10 | 0.627556E+09 | 0.135341E+10 | 0.251978E+10 | 0.406874E+09 |
August | 0.211555E+10 | 0.884915E+09 | 0.123064E+10 | 0.260480E+10 | 0.488401E+09 |
September | 0.219297E+10 | 0.116792E+10 | 0.102505E+10 | 0.249828E+10 | 0.743106E+09 |
October | 0.193506E+10 | 0.113810E+10 | 0.796959E+09 | 0.195365E+10 | 0.110013E+10 |
November | 0.166811E+10 | 0.104691E+10 | 0.621204E+09 | 0.150447E+10 | 0.145434E+10 |
December | 0.183467E+10 | 0.120301E+10 | 0.631656E+09 | 0.144816E+10 | 0.217437E+10 |
Annual Sum or Average | 0.255692E+11 | 0.136540E+11 | 0.119152E+11 | 0.267658E+11 | 0.139461E+11 |
Minimum of Months | 0.166811E+10 | 0.467361E+09 | 0.621204E+09 | 0.144816E+10 | 0.405839E+09 |
Maximum of Months | 0.271760E+10 | 0.183556E+10 | 0.135341E+10 | 0.260852E+10 | 0.222757E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237599E+10 | 0.165292E+10 | 0.723070E+09 | 0.204350E+10 | 0.222743E+10 |
February | 0.271742E+10 | 0.183544E+10 | 0.881985E+09 | 0.260836E+10 | 0.172411E+10 |
March | 0.265092E+10 | 0.167766E+10 | 0.973263E+09 | 0.260814E+10 | 0.157929E+10 |
April | 0.232418E+10 | 0.126150E+10 | 0.106269E+10 | 0.248368E+10 | 0.102990E+10 |
May | 0.201917E+10 | 0.690300E+09 | 0.132887E+10 | 0.233467E+10 | 0.611852E+09 |
June | 0.175332E+10 | 0.467332E+09 | 0.128598E+10 | 0.215739E+10 | 0.405814E+09 |
July | 0.198084E+10 | 0.627516E+09 | 0.135332E+10 | 0.251962E+10 | 0.406848E+09 |
August | 0.211542E+10 | 0.884859E+09 | 0.123056E+10 | 0.260463E+10 | 0.488370E+09 |
September | 0.219283E+10 | 0.116784E+10 | 0.102499E+10 | 0.249812E+10 | 0.743059E+09 |
October | 0.193494E+10 | 0.113803E+10 | 0.796908E+09 | 0.195353E+10 | 0.110007E+10 |
November | 0.166800E+10 | 0.104684E+10 | 0.621164E+09 | 0.150437E+10 | 0.145424E+10 |
December | 0.183455E+10 | 0.120294E+10 | 0.631616E+09 | 0.144806E+10 | 0.217423E+10 |
Annual Sum or Average | 0.255676E+11 | 0.136532E+11 | 0.119144E+11 | 0.267641E+11 | 0.139452E+11 |
Minimum of Months | 0.166800E+10 | 0.467332E+09 | 0.621164E+09 | 0.144806E+10 | 0.405814E+09 |
Maximum of Months | 0.271742E+10 | 0.183544E+10 | 0.135332E+10 | 0.260836E+10 | 0.222743E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147111E+10 | 0.616010E+09 | 0.855095E+09 | 0.646267E+09 | 0.501074E+10 |
February | 0.216491E+10 | 0.988784E+09 | 0.117613E+10 | 0.145896E+10 | 0.363552E+10 |
March | 0.315409E+10 | 0.161392E+10 | 0.154017E+10 | 0.255121E+10 | 0.316470E+10 |
April | 0.389920E+10 | 0.197490E+10 | 0.192430E+10 | 0.378000E+10 | 0.194292E+10 |
May | 0.495056E+10 | 0.236143E+10 | 0.258913E+10 | 0.556171E+10 | 0.118413E+10 |
June | 0.462308E+10 | 0.199898E+10 | 0.262410E+10 | 0.549258E+10 | 0.796332E+09 |
July | 0.510010E+10 | 0.237101E+10 | 0.272909E+10 | 0.621128E+10 | 0.809514E+09 |
August | 0.419704E+10 | 0.190710E+10 | 0.228994E+10 | 0.495345E+10 | 0.942116E+09 |
September | 0.317434E+10 | 0.142618E+10 | 0.174816E+10 | 0.333142E+10 | 0.140726E+10 |
October | 0.207209E+10 | 0.831826E+09 | 0.124027E+10 | 0.170918E+10 | 0.213457E+10 |
November | 0.121789E+10 | 0.410625E+09 | 0.807266E+09 | 0.635609E+09 | 0.299656E+10 |
December | 0.112187E+10 | 0.392662E+09 | 0.729209E+09 | 0.360081E+09 | 0.487424E+10 |
Annual Sum or Average | 0.371463E+11 | 0.168934E+11 | 0.202528E+11 | 0.366918E+11 | 0.288986E+11 |
Minimum of Months | 0.112187E+10 | 0.392662E+09 | 0.729209E+09 | 0.360081E+09 | 0.796332E+09 |
Maximum of Months | 0.510010E+10 | 0.237101E+10 | 0.272909E+10 | 0.621128E+10 | 0.501074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58166010.15 | 24356418.60 | 33809591.55 | 25552666.35 | 0.198120E+09 |
February | 85598305.86 | 39095482.59 | 46502823.27 | 57685791.32 | 0.143745E+09 |
March | 0.124709E+09 | 63812782.64 | 60896652.02 | 0.100872E+09 | 0.125129E+09 |
April | 0.154170E+09 | 78085563.73 | 76084921.57 | 0.149457E+09 | 76821376.33 |
May | 0.195740E+09 | 93368578.93 | 0.102371E+09 | 0.219905E+09 | 46819459.34 |
June | 0.182792E+09 | 79037424.30 | 0.103754E+09 | 0.217171E+09 | 31486243.23 |
July | 0.201653E+09 | 93747321.00 | 0.107906E+09 | 0.245588E+09 | 32007448.95 |
August | 0.165947E+09 | 75404970.01 | 90541849.93 | 0.195854E+09 | 37250401.13 |
September | 0.125510E+09 | 56389626.52 | 69120460.40 | 0.131721E+09 | 55641965.00 |
October | 81928437.35 | 32889558.78 | 49038878.58 | 67579249.29 | 84399135.12 |
November | 48154171.17 | 16235699.88 | 31918471.28 | 25131270.36 | 0.118481E+09 |
December | 44357633.85 | 15525434.24 | 28832199.61 | 14237174.61 | 0.192723E+09 |
Annual Sum or Average | 0.146873E+10 | 0.667949E+09 | 0.800777E+09 | 0.145075E+10 | 0.114263E+10 |
Minimum of Months | 44357633.85 | 15525434.24 | 28832199.61 | 14237174.61 | 31486243.23 |
Maximum of Months | 0.201653E+09 | 93747321.00 | 0.107906E+09 | 0.245588E+09 | 0.198120E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103522E+10 | 0.00 | 0.103522E+10 | 14338674.19 | 0.859083E+10 |
February | 0.143628E+10 | 0.00 | 0.143628E+10 | 0.133586E+09 | 0.615688E+10 |
March | 0.195643E+10 | 0.00 | 0.195643E+10 | 0.349243E+09 | 0.531876E+10 |
April | 0.248202E+10 | 19371904.28 | 0.246265E+10 | 0.119317E+10 | 0.314686E+10 |
May | 0.360724E+10 | 0.194244E+09 | 0.341299E+10 | 0.316959E+10 | 0.175781E+10 |
June | 0.389587E+10 | 0.428260E+09 | 0.346761E+10 | 0.418078E+10 | 0.118141E+10 |
July | 0.384521E+10 | 0.329992E+09 | 0.351522E+10 | 0.432177E+10 | 0.114661E+10 |
August | 0.292056E+10 | 50154901.34 | 0.287040E+10 | 0.296864E+10 | 0.135562E+10 |
September | 0.220249E+10 | 539900.92 | 0.220195E+10 | 0.164664E+10 | 0.213965E+10 |
October | 0.158027E+10 | 0.00 | 0.158027E+10 | 0.600091E+09 | 0.332752E+10 |
November | 0.101259E+10 | 0.00 | 0.101259E+10 | 91115224.02 | 0.488488E+10 |
December | 0.877119E+09 | 0.00 | 0.877119E+09 | 902054.58 | 0.824524E+10 |
Annual Sum or Average | 0.268513E+11 | 0.102256E+10 | 0.258287E+11 | 0.186699E+11 | 0.472521E+11 |
Minimum of Months | 0.877119E+09 | 0.00 | 0.877119E+09 | 902054.58 | 0.114661E+10 |
Maximum of Months | 0.389587E+10 | 0.428260E+09 | 0.351522E+10 | 0.432177E+10 | 0.859083E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151310E+10 | 0.631613E+09 | 0.881483E+09 | 0.589985E+09 | 0.516010E+10 |
February | 0.214760E+10 | 0.916068E+09 | 0.123153E+10 | 0.127406E+10 | 0.368959E+10 |
March | 0.323976E+10 | 0.162511E+10 | 0.161465E+10 | 0.243368E+10 | 0.325454E+10 |
April | 0.434637E+10 | 0.234435E+10 | 0.200202E+10 | 0.411754E+10 | 0.198168E+10 |
May | 0.486085E+10 | 0.213689E+10 | 0.272397E+10 | 0.523359E+10 | 0.118189E+10 |
June | 0.532531E+10 | 0.254739E+10 | 0.277792E+10 | 0.625872E+10 | 0.804530E+09 |
July | 0.539074E+10 | 0.253115E+10 | 0.285959E+10 | 0.650260E+10 | 0.773289E+09 |
August | 0.415627E+10 | 0.181658E+10 | 0.233969E+10 | 0.481892E+10 | 0.898000E+09 |
September | 0.322110E+10 | 0.144175E+10 | 0.177935E+10 | 0.331592E+10 | 0.135438E+10 |
October | 0.201545E+10 | 0.764255E+09 | 0.125120E+10 | 0.154714E+10 | 0.209212E+10 |
November | 0.124166E+10 | 0.415116E+09 | 0.826546E+09 | 0.598171E+09 | 0.301341E+10 |
December | 0.117077E+10 | 0.432736E+09 | 0.738036E+09 | 0.363191E+09 | 0.501996E+10 |
Annual Sum or Average | 0.386290E+11 | 0.176030E+11 | 0.210260E+11 | 0.370535E+11 | 0.292235E+11 |
Minimum of Months | 0.117077E+10 | 0.415116E+09 | 0.738036E+09 | 0.363191E+09 | 0.773289E+09 |
Maximum of Months | 0.539074E+10 | 0.254739E+10 | 0.285959E+10 | 0.650260E+10 | 0.516010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.712856E+10 | 0.495918E+10 | 0.216938E+10 | 0.595095E+10 | 0.690333E+10 |
February | 0.815294E+10 | 0.550678E+10 | 0.264616E+10 | 0.764425E+10 | 0.527483E+10 |
March | 0.795341E+10 | 0.503341E+10 | 0.292001E+10 | 0.762774E+10 | 0.488654E+10 |
April | 0.697310E+10 | 0.378480E+10 | 0.318830E+10 | 0.728432E+10 | 0.321171E+10 |
May | 0.605797E+10 | 0.207107E+10 | 0.398689E+10 | 0.685281E+10 | 0.194310E+10 |
June | 0.526035E+10 | 0.140211E+10 | 0.385823E+10 | 0.635652E+10 | 0.129282E+10 |
July | 0.594297E+10 | 0.188271E+10 | 0.406027E+10 | 0.749534E+10 | 0.123785E+10 |
August | 0.634676E+10 | 0.265480E+10 | 0.369196E+10 | 0.776854E+10 | 0.143733E+10 |
September | 0.657902E+10 | 0.350382E+10 | 0.307520E+10 | 0.744750E+10 | 0.216775E+10 |
October | 0.580529E+10 | 0.341438E+10 | 0.239091E+10 | 0.582108E+10 | 0.319969E+10 |
November | 0.500442E+10 | 0.314078E+10 | 0.186364E+10 | 0.445352E+10 | 0.432259E+10 |
December | 0.550410E+10 | 0.360911E+10 | 0.189500E+10 | 0.423054E+10 | 0.669159E+10 |
Annual Sum or Average | 0.767089E+11 | 0.409630E+11 | 0.357459E+11 | 0.789331E+11 | 0.425691E+11 |
Minimum of Months | 0.500442E+10 | 0.140211E+10 | 0.186364E+10 | 0.423054E+10 | 0.123785E+10 |
Maximum of Months | 0.815294E+10 | 0.550678E+10 | 0.406027E+10 | 0.776854E+10 | 0.690333E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152929E+10 | 0.640377E+09 | 0.888915E+09 | 0.653698E+09 | 0.527715E+10 |
February | 0.225054E+10 | 0.102790E+10 | 0.122264E+10 | 0.147923E+10 | 0.383696E+10 |
March | 0.327884E+10 | 0.167776E+10 | 0.160108E+10 | 0.258826E+10 | 0.338832E+10 |
April | 0.405343E+10 | 0.205302E+10 | 0.200040E+10 | 0.384287E+10 | 0.209917E+10 |
May | 0.514637E+10 | 0.245484E+10 | 0.269152E+10 | 0.570592E+10 | 0.127644E+10 |
June | 0.480593E+10 | 0.207805E+10 | 0.272788E+10 | 0.565115E+10 | 0.855995E+09 |
July | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.642915E+10 | 0.836917E+09 |
August | 0.436305E+10 | 0.198254E+10 | 0.238050E+10 | 0.513656E+10 | 0.954559E+09 |
September | 0.329989E+10 | 0.148259E+10 | 0.181730E+10 | 0.345892E+10 | 0.142285E+10 |
October | 0.215405E+10 | 0.864730E+09 | 0.128932E+10 | 0.177583E+10 | 0.216331E+10 |
November | 0.126606E+10 | 0.426868E+09 | 0.839194E+09 | 0.651977E+09 | 0.308579E+10 |
December | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.365467E+09 | 0.510510E+10 |
Annual Sum or Average | 0.386155E+11 | 0.175617E+11 | 0.210538E+11 | 0.377390E+11 | 0.303026E+11 |
Minimum of Months | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.365467E+09 | 0.836917E+09 |
Maximum of Months | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.642915E+10 | 0.527715E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.56 | 3152.93 | 386.51 | 0.00 | 386.51 | 0.00 | 0.00 |
February | 60.56 | 2477.77 | 593.70 | 0.00 | 593.70 | 0.00 | 0.00 |
March | 138.80 | 1917.01 | 730.45 | 0.00 | 730.45 | 0.00 | 0.00 |
April | 478.37 | 1148.90 | 957.57 | 7.47 | 950.10 | 0.00 | 0.00 |
May | 1196.71 | 630.74 | 1346.79 | 72.52 | 1274.27 | 0.00 | 0.00 |
June | 1620.25 | 439.81 | 1503.04 | 165.22 | 1337.81 | 0.00 | 0.00 |
July | 1618.62 | 414.87 | 1435.64 | 123.20 | 1312.43 | 0.00 | 0.00 |
August | 1115.62 | 484.59 | 1090.41 | 18.73 | 1071.69 | 0.00 | 0.00 |
September | 653.42 | 775.55 | 849.73 | 0.21 | 849.52 | 0.00 | 0.00 |
October | 245.47 | 1156.05 | 590.01 | 0.00 | 590.01 | 0.00 | 0.00 |
November | 40.32 | 1790.96 | 390.66 | 0.00 | 390.66 | 0.00 | 0.00 |
December | 1.11 | 3014.13 | 327.48 | 0.00 | 327.48 | 0.00 | 0.00 |
Annual Sum or Average | 601.30 | 1446.34 | 851.45 | 32.43 | 819.02 | 0.00 | 0.00 |
Minimum of Months | 1.11 | 414.87 | 327.48 | 0.00 | 327.48 | 0.00 | 0.00 |
Maximum of Months | 1620.25 | 3152.93 | 1503.04 | 165.22 | 1337.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.30 | 1894.37 | 564.93 | 235.82 | 329.11 | 0.00 | 0.00 |
February | 534.78 | 1483.85 | 887.73 | 378.67 | 509.06 | 0.00 | 0.00 |
March | 918.63 | 1172.99 | 1209.59 | 606.75 | 602.84 | 0.00 | 0.00 |
April | 1600.51 | 727.77 | 1676.84 | 904.45 | 772.39 | 0.00 | 0.00 |
May | 1960.01 | 426.04 | 1814.83 | 797.82 | 1017.01 | 0.00 | 0.00 |
June | 2416.68 | 299.94 | 2054.52 | 982.79 | 1071.73 | 0.00 | 0.00 |
July | 2429.19 | 280.03 | 2012.67 | 945.02 | 1067.65 | 0.00 | 0.00 |
August | 1802.07 | 321.81 | 1551.77 | 678.23 | 873.54 | 0.00 | 0.00 |
September | 1289.97 | 494.95 | 1242.71 | 556.23 | 686.48 | 0.00 | 0.00 |
October | 592.68 | 732.07 | 752.48 | 285.34 | 467.14 | 0.00 | 0.00 |
November | 238.47 | 1105.43 | 479.04 | 160.15 | 318.88 | 0.00 | 0.00 |
December | 138.40 | 1834.85 | 437.12 | 161.57 | 275.55 | 0.00 | 0.00 |
Annual Sum or Average | 1181.74 | 895.66 | 1224.92 | 558.19 | 666.73 | 0.00 | 0.00 |
Minimum of Months | 138.40 | 280.03 | 437.12 | 160.15 | 275.55 | 0.00 | 0.00 |
Maximum of Months | 2429.19 | 1894.37 | 2054.52 | 982.79 | 1071.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2233.04 | 2525.38 | 2661.50 | 1851.55 | 809.95 | 0.00 | 0.00 |
February | 3176.85 | 2111.87 | 3370.10 | 2276.28 | 1093.82 | 0.00 | 0.00 |
March | 2862.54 | 1757.66 | 2969.46 | 1879.26 | 1090.21 | 0.00 | 0.00 |
April | 2825.23 | 1177.33 | 2690.24 | 1460.19 | 1230.05 | 0.00 | 0.00 |
May | 2565.79 | 696.05 | 2261.79 | 773.25 | 1488.53 | 0.00 | 0.00 |
June | 2457.27 | 478.86 | 2029.45 | 540.94 | 1488.52 | 0.00 | 0.00 |
July | 2801.28 | 445.79 | 2218.85 | 702.92 | 1515.93 | 0.00 | 0.00 |
August | 2904.75 | 512.98 | 2369.61 | 991.19 | 1378.42 | 0.00 | 0.00 |
September | 2886.95 | 789.93 | 2538.20 | 1351.78 | 1186.42 | 0.00 | 0.00 |
October | 2197.88 | 1117.75 | 2167.45 | 1274.78 | 892.66 | 0.00 | 0.00 |
November | 1738.00 | 1582.90 | 1930.72 | 1211.72 | 719.00 | 0.00 | 0.00 |
December | 1592.25 | 2438.11 | 2055.00 | 1347.49 | 707.51 | 0.00 | 0.00 |
Annual Sum or Average | 2515.23 | 1299.47 | 2432.42 | 1298.93 | 1133.50 | 0.00 | 0.00 |
Minimum of Months | 1592.25 | 445.79 | 1930.72 | 540.94 | 707.51 | 0.00 | 0.00 |
Maximum of Months | 3176.85 | 2525.38 | 3370.10 | 2276.28 | 1515.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 245.98 | 1937.89 | 570.97 | 239.09 | 331.88 | 0.00 | 0.00 |
February | 616.90 | 1543.33 | 930.28 | 424.89 | 505.39 | 0.00 | 0.00 |
March | 972.70 | 1220.78 | 1224.18 | 626.40 | 597.77 | 0.00 | 0.00 |
April | 1492.63 | 769.50 | 1563.82 | 792.06 | 771.76 | 0.00 | 0.00 |
May | 2136.39 | 457.62 | 1921.43 | 916.53 | 1004.90 | 0.00 | 0.00 |
June | 2184.17 | 317.46 | 1854.14 | 801.72 | 1052.42 | 0.00 | 0.00 |
July | 2402.39 | 301.93 | 1979.47 | 920.25 | 1059.22 | 0.00 | 0.00 |
August | 1922.42 | 340.88 | 1628.97 | 740.20 | 888.78 | 0.00 | 0.00 |
September | 1346.04 | 517.89 | 1273.11 | 571.99 | 701.12 | 0.00 | 0.00 |
October | 676.72 | 755.99 | 804.23 | 322.85 | 481.38 | 0.00 | 0.00 |
November | 258.60 | 1133.07 | 488.45 | 164.69 | 323.76 | 0.00 | 0.00 |
December | 138.94 | 1867.33 | 435.43 | 152.40 | 283.02 | 0.00 | 0.00 |
Annual Sum or Average | 1202.95 | 927.96 | 1224.49 | 556.88 | 667.61 | 0.00 | 0.00 |
Minimum of Months | 138.94 | 301.93 | 435.43 | 152.40 | 283.02 | 0.00 | 0.00 |
Maximum of Months | 2402.39 | 1937.89 | 1979.47 | 920.25 | 1059.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.84 | 3154.15 | 386.50 | 0.00 | 386.50 | 0.00 | 0.00 |
February | 60.80 | 2491.31 | 593.69 | 0.00 | 593.69 | 0.00 | 0.00 |
March | 150.08 | 1904.08 | 730.43 | 0.00 | 730.43 | 0.00 | 0.00 |
April | 519.28 | 1125.47 | 957.55 | 7.47 | 950.08 | 0.00 | 0.00 |
May | 1250.03 | 602.41 | 1346.76 | 72.52 | 1274.24 | 0.00 | 0.00 |
June | 1658.09 | 425.55 | 1503.00 | 165.22 | 1337.78 | 0.00 | 0.00 |
July | 1640.69 | 410.70 | 1435.61 | 123.20 | 1312.40 | 0.00 | 0.00 |
August | 1122.16 | 497.19 | 1090.39 | 18.73 | 1071.66 | 0.00 | 0.00 |
September | 644.14 | 825.26 | 849.71 | 0.21 | 849.50 | 0.00 | 0.00 |
October | 227.41 | 1253.53 | 589.99 | 0.00 | 589.99 | 0.00 | 0.00 |
November | 36.14 | 1895.19 | 390.65 | 0.00 | 390.65 | 0.00 | 0.00 |
December | 0.29 | 3050.91 | 327.47 | 0.00 | 327.47 | 0.00 | 0.00 |
Annual Sum or Average | 612.94 | 1465.65 | 851.43 | 32.42 | 819.01 | 0.00 | 0.00 |
Minimum of Months | 0.29 | 410.70 | 327.47 | 0.00 | 327.47 | 0.00 | 0.00 |
Maximum of Months | 1658.09 | 3154.15 | 1503.00 | 165.22 | 1337.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.82 | 1903.48 | 564.92 | 235.81 | 329.10 | 0.00 | 0.00 |
February | 539.01 | 1502.17 | 887.72 | 378.66 | 509.06 | 0.00 | 0.00 |
March | 933.08 | 1178.94 | 1209.57 | 606.74 | 602.83 | 0.00 | 0.00 |
April | 1621.73 | 738.06 | 1676.81 | 904.44 | 772.38 | 0.00 | 0.00 |
May | 1984.58 | 424.31 | 1814.81 | 797.81 | 1017.00 | 0.00 | 0.00 |
June | 2435.59 | 303.50 | 2054.49 | 982.77 | 1071.71 | 0.00 | 0.00 |
July | 2439.47 | 288.97 | 2012.64 | 945.01 | 1067.63 | 0.00 | 0.00 |
August | 1804.04 | 344.37 | 1551.75 | 678.22 | 873.53 | 0.00 | 0.00 |
September | 1280.59 | 538.86 | 1242.69 | 556.22 | 686.47 | 0.00 | 0.00 |
October | 576.66 | 802.03 | 752.47 | 285.33 | 467.14 | 0.00 | 0.00 |
November | 233.03 | 1176.55 | 479.03 | 160.15 | 318.88 | 0.00 | 0.00 |
December | 138.06 | 1862.38 | 437.11 | 161.56 | 275.55 | 0.00 | 0.00 |
Annual Sum or Average | 1187.32 | 919.75 | 1224.90 | 558.18 | 666.72 | 0.00 | 0.00 |
Minimum of Months | 138.06 | 288.97 | 437.11 | 160.15 | 275.55 | 0.00 | 0.00 |
Maximum of Months | 2439.47 | 1903.48 | 2054.49 | 982.77 | 1071.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2288.97 | 2494.98 | 2661.39 | 1851.47 | 809.92 | 0.00 | 0.00 |
February | 3234.71 | 2138.12 | 3369.96 | 2276.19 | 1093.78 | 0.00 | 0.00 |
March | 2921.43 | 1769.00 | 2969.35 | 1879.18 | 1090.17 | 0.00 | 0.00 |
April | 2874.75 | 1192.07 | 2690.14 | 1460.13 | 1230.02 | 0.00 | 0.00 |
May | 2615.11 | 685.35 | 2261.71 | 773.22 | 1488.49 | 0.00 | 0.00 |
June | 2497.09 | 469.71 | 2029.39 | 540.92 | 1488.47 | 0.00 | 0.00 |
July | 2822.28 | 455.72 | 2218.78 | 702.89 | 1515.88 | 0.00 | 0.00 |
August | 2917.50 | 547.03 | 2369.52 | 991.15 | 1378.37 | 0.00 | 0.00 |
September | 2891.46 | 860.06 | 2538.11 | 1351.73 | 1186.38 | 0.00 | 0.00 |
October | 2188.18 | 1232.20 | 2167.36 | 1274.73 | 892.63 | 0.00 | 0.00 |
November | 1741.25 | 1683.22 | 1930.64 | 1211.67 | 718.97 | 0.00 | 0.00 |
December | 1622.00 | 2435.40 | 2054.91 | 1347.43 | 707.48 | 0.00 | 0.00 |
Annual Sum or Average | 2546.16 | 1326.66 | 2432.33 | 1298.87 | 1133.46 | 0.00 | 0.00 |
Minimum of Months | 1622.00 | 455.72 | 1930.64 | 540.92 | 707.48 | 0.00 | 0.00 |
Maximum of Months | 3234.71 | 2494.98 | 3369.96 | 2276.19 | 1515.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.83 | 1944.77 | 570.96 | 239.09 | 331.88 | 0.00 | 0.00 |
February | 626.92 | 1562.20 | 930.27 | 424.88 | 505.39 | 0.00 | 0.00 |
March | 990.18 | 1228.28 | 1224.16 | 626.39 | 597.77 | 0.00 | 0.00 |
April | 1515.99 | 779.22 | 1563.80 | 792.05 | 771.75 | 0.00 | 0.00 |
May | 2158.61 | 459.58 | 1921.41 | 916.52 | 1004.89 | 0.00 | 0.00 |
June | 2202.84 | 319.37 | 1854.12 | 801.70 | 1052.41 | 0.00 | 0.00 |
July | 2410.72 | 314.19 | 1979.45 | 920.24 | 1059.21 | 0.00 | 0.00 |
August | 1922.53 | 365.65 | 1628.95 | 740.18 | 888.77 | 0.00 | 0.00 |
September | 1336.09 | 564.39 | 1273.09 | 571.98 | 701.11 | 0.00 | 0.00 |
October | 663.37 | 828.47 | 804.22 | 322.85 | 481.37 | 0.00 | 0.00 |
November | 254.92 | 1201.79 | 488.44 | 164.68 | 323.76 | 0.00 | 0.00 |
December | 139.75 | 1891.79 | 435.42 | 152.40 | 283.02 | 0.00 | 0.00 |
Annual Sum or Average | 1209.49 | 952.60 | 1224.47 | 556.87 | 667.61 | 0.00 | 0.00 |
Minimum of Months | 139.75 | 314.19 | 435.42 | 152.40 | 283.02 | 0.00 | 0.00 |
Maximum of Months | 2410.72 | 1944.77 | 1979.45 | 920.24 | 1059.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.35 | 3207.45 | 386.51 | 0.00 | 386.51 | 0.00 | 0.00 |
February | 55.22 | 2545.01 | 593.70 | 0.00 | 593.70 | 0.00 | 0.00 |
March | 130.39 | 1985.80 | 730.45 | 0.00 | 730.45 | 0.00 | 0.00 |
April | 460.33 | 1214.07 | 957.57 | 7.47 | 950.10 | 0.00 | 0.00 |
May | 1183.39 | 656.29 | 1346.79 | 72.52 | 1274.27 | 0.00 | 0.00 |
June | 1612.96 | 455.79 | 1503.04 | 165.22 | 1337.81 | 0.00 | 0.00 |
July | 1613.56 | 428.09 | 1435.64 | 123.20 | 1312.43 | 0.00 | 0.00 |
August | 1108.36 | 506.13 | 1090.41 | 18.73 | 1071.69 | 0.00 | 0.00 |
September | 635.28 | 825.48 | 849.73 | 0.21 | 849.52 | 0.00 | 0.00 |
October | 224.05 | 1242.35 | 590.01 | 0.00 | 590.01 | 0.00 | 0.00 |
November | 35.15 | 1884.60 | 390.66 | 0.00 | 390.66 | 0.00 | 0.00 |
December | 0.34 | 3078.42 | 327.48 | 0.00 | 327.48 | 0.00 | 0.00 |
Annual Sum or Average | 592.02 | 1498.35 | 851.45 | 32.43 | 819.02 | 0.00 | 0.00 |
Minimum of Months | 0.34 | 428.09 | 327.48 | 0.00 | 327.48 | 0.00 | 0.00 |
Maximum of Months | 1613.56 | 3207.45 | 1503.04 | 165.22 | 1337.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.28 | 1926.56 | 564.93 | 235.82 | 329.11 | 0.00 | 0.00 |
February | 526.64 | 1525.13 | 887.73 | 378.67 | 509.06 | 0.00 | 0.00 |
March | 908.63 | 1215.10 | 1209.59 | 606.75 | 602.84 | 0.00 | 0.00 |
April | 1588.56 | 764.54 | 1676.84 | 904.45 | 772.39 | 0.00 | 0.00 |
May | 1954.00 | 441.27 | 1814.83 | 797.82 | 1017.01 | 0.00 | 0.00 |
June | 2414.63 | 310.39 | 2054.52 | 982.79 | 1071.73 | 0.00 | 0.00 |
July | 2427.79 | 288.71 | 2012.67 | 945.02 | 1067.65 | 0.00 | 0.00 |
August | 1799.18 | 335.27 | 1551.77 | 678.23 | 873.54 | 0.00 | 0.00 |
September | 1279.29 | 522.52 | 1242.71 | 556.23 | 686.48 | 0.00 | 0.00 |
October | 577.64 | 781.11 | 752.48 | 285.34 | 467.14 | 0.00 | 0.00 |
November | 230.78 | 1162.58 | 479.04 | 160.15 | 318.88 | 0.00 | 0.00 |
December | 135.60 | 1874.24 | 437.12 | 161.57 | 275.55 | 0.00 | 0.00 |
Annual Sum or Average | 1174.96 | 926.67 | 1224.92 | 558.19 | 666.73 | 0.00 | 0.00 |
Minimum of Months | 135.60 | 288.71 | 437.12 | 160.15 | 275.55 | 0.00 | 0.00 |
Maximum of Months | 2427.79 | 1926.56 | 2054.52 | 982.79 | 1071.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2221.83 | 2577.41 | 2661.50 | 1851.55 | 809.95 | 0.00 | 0.00 |
February | 3159.83 | 2180.40 | 3370.10 | 2276.28 | 1093.82 | 0.00 | 0.00 |
March | 2847.87 | 1824.43 | 2969.46 | 1879.26 | 1090.21 | 0.00 | 0.00 |
April | 2810.31 | 1239.09 | 2690.24 | 1460.19 | 1230.05 | 0.00 | 0.00 |
May | 2558.54 | 725.47 | 2261.79 | 773.25 | 1488.53 | 0.00 | 0.00 |
June | 2452.36 | 498.77 | 2029.45 | 540.94 | 1488.52 | 0.00 | 0.00 |
July | 2798.44 | 462.16 | 2218.85 | 702.92 | 1515.93 | 0.00 | 0.00 |
August | 2900.44 | 536.64 | 2369.61 | 991.19 | 1378.42 | 0.00 | 0.00 |
September | 2873.26 | 836.32 | 2538.20 | 1351.78 | 1186.42 | 0.00 | 0.00 |
October | 2173.34 | 1194.63 | 2167.45 | 1274.78 | 892.66 | 0.00 | 0.00 |
November | 1718.18 | 1667.66 | 1930.72 | 1211.72 | 719.00 | 0.00 | 0.00 |
December | 1579.50 | 2498.35 | 2055.00 | 1347.49 | 707.51 | 0.00 | 0.00 |
Annual Sum or Average | 2502.95 | 1349.86 | 2432.42 | 1298.93 | 1133.50 | 0.00 | 0.00 |
Minimum of Months | 1579.50 | 462.16 | 1930.72 | 540.94 | 707.51 | 0.00 | 0.00 |
Maximum of Months | 3159.83 | 2577.41 | 3370.10 | 2276.28 | 1515.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 244.06 | 1970.26 | 570.97 | 239.09 | 331.88 | 0.00 | 0.00 |
February | 611.45 | 1586.04 | 930.28 | 424.89 | 505.39 | 0.00 | 0.00 |
March | 966.35 | 1265.05 | 1224.18 | 626.40 | 597.77 | 0.00 | 0.00 |
April | 1482.59 | 809.86 | 1563.82 | 792.06 | 771.76 | 0.00 | 0.00 |
May | 2130.35 | 476.57 | 1921.43 | 916.53 | 1004.90 | 0.00 | 0.00 |
June | 2180.23 | 330.25 | 1854.14 | 801.72 | 1052.42 | 0.00 | 0.00 |
July | 2400.37 | 312.47 | 1979.47 | 920.25 | 1059.22 | 0.00 | 0.00 |
August | 1917.77 | 356.39 | 1628.97 | 740.20 | 888.78 | 0.00 | 0.00 |
September | 1334.46 | 548.94 | 1273.11 | 571.99 | 701.12 | 0.00 | 0.00 |
October | 663.02 | 807.69 | 804.23 | 322.85 | 481.38 | 0.00 | 0.00 |
November | 251.53 | 1190.51 | 488.45 | 164.69 | 323.76 | 0.00 | 0.00 |
December | 136.45 | 1906.03 | 435.43 | 152.40 | 283.02 | 0.00 | 0.00 |
Annual Sum or Average | 1196.70 | 960.89 | 1224.49 | 556.88 | 667.61 | 0.00 | 0.00 |
Minimum of Months | 136.45 | 312.47 | 435.43 | 152.40 | 283.02 | 0.00 | 0.00 |
Maximum of Months | 2400.37 | 1970.26 | 1979.47 | 920.25 | 1059.22 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17572768.65 | 0.844481E+10 | 0.103522E+10 | 0.00 | 0.103522E+10 | 0.00 | 0.00 |
February | 0.146496E+09 | 0.599423E+10 | 0.143628E+10 | 0.00 | 0.143628E+10 | 0.00 | 0.00 |
March | 0.371752E+09 | 0.513451E+10 | 0.195643E+10 | 0.00 | 0.195643E+10 | 0.00 | 0.00 |
April | 0.123992E+10 | 0.297796E+10 | 0.248202E+10 | 19371904.28 | 0.246265E+10 | 0.00 | 0.00 |
May | 0.320528E+10 | 0.168937E+10 | 0.360724E+10 | 0.194244E+09 | 0.341299E+10 | 0.00 | 0.00 |
June | 0.419970E+10 | 0.113999E+10 | 0.389587E+10 | 0.428260E+09 | 0.346761E+10 | 0.00 | 0.00 |
July | 0.433530E+10 | 0.111120E+10 | 0.384521E+10 | 0.329992E+09 | 0.351522E+10 | 0.00 | 0.00 |
August | 0.298808E+10 | 0.129793E+10 | 0.292056E+10 | 50154901.34 | 0.287040E+10 | 0.00 | 0.00 |
September | 0.169367E+10 | 0.201023E+10 | 0.220249E+10 | 539900.92 | 0.220195E+10 | 0.00 | 0.00 |
October | 0.657479E+09 | 0.309637E+10 | 0.158027E+10 | 0.00 | 0.158027E+10 | 0.00 | 0.00 |
November | 0.104514E+09 | 0.464217E+10 | 0.101259E+10 | 0.00 | 0.101259E+10 | 0.00 | 0.00 |
December | 2978563.60 | 0.807304E+10 | 0.877119E+09 | 0.00 | 0.877119E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189627E+11 | 0.456118E+11 | 0.268513E+11 | 0.102256E+10 | 0.258287E+11 | 0.00 | 0.00 |
Minimum of Months | 2978563.60 | 0.111120E+10 | 0.877119E+09 | 0.00 | 0.877119E+09 | 0.00 | 0.00 |
Maximum of Months | 0.433530E+10 | 0.844481E+10 | 0.389587E+10 | 0.428260E+09 | 0.351522E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598089E+09 | 0.507388E+10 | 0.151310E+10 | 0.631613E+09 | 0.881483E+09 | 0.00 | 0.00 |
February | 0.129375E+10 | 0.358972E+10 | 0.214760E+10 | 0.916068E+09 | 0.123153E+10 | 0.00 | 0.00 |
March | 0.246046E+10 | 0.314173E+10 | 0.323976E+10 | 0.162511E+10 | 0.161465E+10 | 0.00 | 0.00 |
April | 0.414852E+10 | 0.188638E+10 | 0.434637E+10 | 0.234435E+10 | 0.200202E+10 | 0.00 | 0.00 |
May | 0.524970E+10 | 0.114110E+10 | 0.486085E+10 | 0.213689E+10 | 0.272397E+10 | 0.00 | 0.00 |
June | 0.626403E+10 | 0.777451E+09 | 0.532531E+10 | 0.254739E+10 | 0.277792E+10 | 0.00 | 0.00 |
July | 0.650633E+10 | 0.750035E+09 | 0.539074E+10 | 0.253115E+10 | 0.285959E+10 | 0.00 | 0.00 |
August | 0.482668E+10 | 0.861926E+09 | 0.415627E+10 | 0.181658E+10 | 0.233969E+10 | 0.00 | 0.00 |
September | 0.334361E+10 | 0.128292E+10 | 0.322110E+10 | 0.144175E+10 | 0.177935E+10 | 0.00 | 0.00 |
October | 0.158743E+10 | 0.196079E+10 | 0.201545E+10 | 0.764255E+09 | 0.125120E+10 | 0.00 | 0.00 |
November | 0.618112E+09 | 0.286528E+10 | 0.124166E+10 | 0.415116E+09 | 0.826546E+09 | 0.00 | 0.00 |
December | 0.370691E+09 | 0.491445E+10 | 0.117077E+10 | 0.432736E+09 | 0.738036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.372674E+11 | 0.282457E+11 | 0.386290E+11 | 0.176030E+11 | 0.210260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.370691E+09 | 0.750035E+09 | 0.117077E+10 | 0.415116E+09 | 0.738036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.650633E+10 | 0.507388E+10 | 0.539074E+10 | 0.254739E+10 | 0.285959E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598098E+10 | 0.676399E+10 | 0.712856E+10 | 0.495918E+10 | 0.216938E+10 | 0.00 | 0.00 |
February | 0.768543E+10 | 0.510903E+10 | 0.815294E+10 | 0.550678E+10 | 0.264616E+10 | 0.00 | 0.00 |
March | 0.766702E+10 | 0.470772E+10 | 0.795341E+10 | 0.503341E+10 | 0.292001E+10 | 0.00 | 0.00 |
April | 0.732300E+10 | 0.305164E+10 | 0.697310E+10 | 0.378480E+10 | 0.318830E+10 | 0.00 | 0.00 |
May | 0.687220E+10 | 0.186429E+10 | 0.605797E+10 | 0.207107E+10 | 0.398689E+10 | 0.00 | 0.00 |
June | 0.636924E+10 | 0.124121E+10 | 0.526035E+10 | 0.140211E+10 | 0.385823E+10 | 0.00 | 0.00 |
July | 0.750296E+10 | 0.119399E+10 | 0.594297E+10 | 0.188271E+10 | 0.406027E+10 | 0.00 | 0.00 |
August | 0.778009E+10 | 0.137397E+10 | 0.634676E+10 | 0.265480E+10 | 0.369196E+10 | 0.00 | 0.00 |
September | 0.748299E+10 | 0.204749E+10 | 0.657902E+10 | 0.350382E+10 | 0.307520E+10 | 0.00 | 0.00 |
October | 0.588680E+10 | 0.299378E+10 | 0.580529E+10 | 0.341438E+10 | 0.239091E+10 | 0.00 | 0.00 |
November | 0.450489E+10 | 0.410286E+10 | 0.500442E+10 | 0.314078E+10 | 0.186364E+10 | 0.00 | 0.00 |
December | 0.426469E+10 | 0.653023E+10 | 0.550410E+10 | 0.360911E+10 | 0.189500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.793203E+11 | 0.409802E+11 | 0.767089E+11 | 0.409630E+11 | 0.357459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426469E+10 | 0.119399E+10 | 0.500442E+10 | 0.140211E+10 | 0.186364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.778009E+10 | 0.676399E+10 | 0.815294E+10 | 0.550678E+10 | 0.406027E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.658838E+09 | 0.519044E+10 | 0.152929E+10 | 0.640377E+09 | 0.888915E+09 | 0.00 | 0.00 |
February | 0.149241E+10 | 0.373362E+10 | 0.225054E+10 | 0.102790E+10 | 0.122264E+10 | 0.00 | 0.00 |
March | 0.260527E+10 | 0.326973E+10 | 0.327884E+10 | 0.167776E+10 | 0.160108E+10 | 0.00 | 0.00 |
April | 0.386888E+10 | 0.199456E+10 | 0.405343E+10 | 0.205302E+10 | 0.200040E+10 | 0.00 | 0.00 |
May | 0.572210E+10 | 0.122569E+10 | 0.514637E+10 | 0.245484E+10 | 0.269152E+10 | 0.00 | 0.00 |
June | 0.566136E+10 | 0.822863E+09 | 0.480593E+10 | 0.207805E+10 | 0.272788E+10 | 0.00 | 0.00 |
July | 0.643455E+10 | 0.808687E+09 | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.00 | 0.00 |
August | 0.514902E+10 | 0.913008E+09 | 0.436305E+10 | 0.198254E+10 | 0.238050E+10 | 0.00 | 0.00 |
September | 0.348895E+10 | 0.134238E+10 | 0.329989E+10 | 0.148259E+10 | 0.181730E+10 | 0.00 | 0.00 |
October | 0.181253E+10 | 0.202483E+10 | 0.215405E+10 | 0.864730E+09 | 0.128932E+10 | 0.00 | 0.00 |
November | 0.670288E+09 | 0.293692E+10 | 0.126606E+10 | 0.426868E+09 | 0.839194E+09 | 0.00 | 0.00 |
December | 0.372134E+09 | 0.500145E+10 | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.379363E+11 | 0.292642E+11 | 0.386155E+11 | 0.175617E+11 | 0.210538E+11 | 0.00 | 0.00 |
Minimum of Months | 0.372134E+09 | 0.808687E+09 | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.00 | 0.00 |
Maximum of Months | 0.643455E+10 | 0.519044E+10 | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15646941.63 | 0.844807E+10 | 0.103519E+10 | 0.00 | 0.103519E+10 | 0.00 | 0.00 |
February | 0.147097E+09 | 0.602697E+10 | 0.143625E+10 | 0.00 | 0.143625E+10 | 0.00 | 0.00 |
March | 0.401962E+09 | 0.509989E+10 | 0.195639E+10 | 0.00 | 0.195639E+10 | 0.00 | 0.00 |
April | 0.134597E+10 | 0.291721E+10 | 0.248197E+10 | 19371334.89 | 0.246260E+10 | 0.00 | 0.00 |
May | 0.334807E+10 | 0.161349E+10 | 0.360716E+10 | 0.194239E+09 | 0.341292E+10 | 0.00 | 0.00 |
June | 0.429777E+10 | 0.110301E+10 | 0.389579E+10 | 0.428248E+09 | 0.346754E+10 | 0.00 | 0.00 |
July | 0.439443E+10 | 0.110002E+10 | 0.384513E+10 | 0.329982E+09 | 0.351514E+10 | 0.00 | 0.00 |
August | 0.300559E+10 | 0.133166E+10 | 0.292050E+10 | 50153427.15 | 0.287034E+10 | 0.00 | 0.00 |
September | 0.166960E+10 | 0.213908E+10 | 0.220244E+10 | 539885.05 | 0.220190E+10 | 0.00 | 0.00 |
October | 0.609085E+09 | 0.335746E+10 | 0.158024E+10 | 0.00 | 0.158024E+10 | 0.00 | 0.00 |
November | 93666913.91 | 0.491232E+10 | 0.101257E+10 | 0.00 | 0.101257E+10 | 0.00 | 0.00 |
December | 778126.89 | 0.817156E+10 | 0.877099E+09 | 0.00 | 0.877099E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193297E+11 | 0.462208E+11 | 0.268507E+11 | 0.102253E+10 | 0.258282E+11 | 0.00 | 0.00 |
Minimum of Months | 778126.89 | 0.110002E+10 | 0.877099E+09 | 0.00 | 0.877099E+09 | 0.00 | 0.00 |
Maximum of Months | 0.439443E+10 | 0.844807E+10 | 0.389579E+10 | 0.428248E+09 | 0.351514E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.604824E+09 | 0.509828E+10 | 0.151307E+10 | 0.631601E+09 | 0.881470E+09 | 0.00 | 0.00 |
February | 0.130397E+10 | 0.363405E+10 | 0.214756E+10 | 0.916051E+09 | 0.123151E+10 | 0.00 | 0.00 |
March | 0.249916E+10 | 0.315767E+10 | 0.323971E+10 | 0.162508E+10 | 0.161463E+10 | 0.00 | 0.00 |
April | 0.420351E+10 | 0.191306E+10 | 0.434630E+10 | 0.234430E+10 | 0.200200E+10 | 0.00 | 0.00 |
May | 0.531549E+10 | 0.113648E+10 | 0.486077E+10 | 0.213684E+10 | 0.272393E+10 | 0.00 | 0.00 |
June | 0.631306E+10 | 0.786681E+09 | 0.532523E+10 | 0.254734E+10 | 0.277788E+10 | 0.00 | 0.00 |
July | 0.653387E+10 | 0.773965E+09 | 0.539065E+10 | 0.253110E+10 | 0.285955E+10 | 0.00 | 0.00 |
August | 0.483193E+10 | 0.922367E+09 | 0.415620E+10 | 0.181655E+10 | 0.233966E+10 | 0.00 | 0.00 |
September | 0.331930E+10 | 0.139671E+10 | 0.322105E+10 | 0.144172E+10 | 0.177933E+10 | 0.00 | 0.00 |
October | 0.154451E+10 | 0.214815E+10 | 0.201542E+10 | 0.764240E+09 | 0.125118E+10 | 0.00 | 0.00 |
November | 0.604015E+09 | 0.304961E+10 | 0.124164E+10 | 0.415108E+09 | 0.826535E+09 | 0.00 | 0.00 |
December | 0.369789E+09 | 0.498821E+10 | 0.117075E+10 | 0.432728E+09 | 0.738026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374434E+11 | 0.290052E+11 | 0.386284E+11 | 0.176027E+11 | 0.210257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.369789E+09 | 0.773965E+09 | 0.117075E+10 | 0.415108E+09 | 0.738026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.653387E+10 | 0.509828E+10 | 0.539065E+10 | 0.254734E+10 | 0.285955E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.613077E+10 | 0.668257E+10 | 0.712828E+10 | 0.495897E+10 | 0.216930E+10 | 0.00 | 0.00 |
February | 0.782541E+10 | 0.517254E+10 | 0.815262E+10 | 0.550655E+10 | 0.264607E+10 | 0.00 | 0.00 |
March | 0.782476E+10 | 0.473808E+10 | 0.795311E+10 | 0.503320E+10 | 0.291991E+10 | 0.00 | 0.00 |
April | 0.745136E+10 | 0.308984E+10 | 0.697285E+10 | 0.378465E+10 | 0.318820E+10 | 0.00 | 0.00 |
May | 0.700430E+10 | 0.183563E+10 | 0.605776E+10 | 0.207099E+10 | 0.398677E+10 | 0.00 | 0.00 |
June | 0.647245E+10 | 0.121749E+10 | 0.526017E+10 | 0.140205E+10 | 0.385812E+10 | 0.00 | 0.00 |
July | 0.755919E+10 | 0.122060E+10 | 0.594277E+10 | 0.188263E+10 | 0.406014E+10 | 0.00 | 0.00 |
August | 0.781423E+10 | 0.146517E+10 | 0.634653E+10 | 0.265469E+10 | 0.369184E+10 | 0.00 | 0.00 |
September | 0.749467E+10 | 0.222927E+10 | 0.657878E+10 | 0.350368E+10 | 0.307510E+10 | 0.00 | 0.00 |
October | 0.586083E+10 | 0.330033E+10 | 0.580506E+10 | 0.341424E+10 | 0.239083E+10 | 0.00 | 0.00 |
November | 0.451331E+10 | 0.436292E+10 | 0.500422E+10 | 0.314065E+10 | 0.186357E+10 | 0.00 | 0.00 |
December | 0.434438E+10 | 0.652298E+10 | 0.550388E+10 | 0.360896E+10 | 0.189493E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.802956E+11 | 0.418374E+11 | 0.767060E+11 | 0.409613E+11 | 0.357448E+11 | 0.00 | 0.00 |
Minimum of Months | 0.434438E+10 | 0.121749E+10 | 0.500422E+10 | 0.140205E+10 | 0.186357E+10 | 0.00 | 0.00 |
Maximum of Months | 0.782541E+10 | 0.668257E+10 | 0.815262E+10 | 0.550655E+10 | 0.406014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.671820E+09 | 0.520886E+10 | 0.152927E+10 | 0.640367E+09 | 0.888904E+09 | 0.00 | 0.00 |
February | 0.151665E+10 | 0.377927E+10 | 0.225051E+10 | 0.102788E+10 | 0.122263E+10 | 0.00 | 0.00 |
March | 0.265209E+10 | 0.328983E+10 | 0.327880E+10 | 0.167773E+10 | 0.160106E+10 | 0.00 | 0.00 |
April | 0.392946E+10 | 0.201974E+10 | 0.405337E+10 | 0.205299E+10 | 0.200038E+10 | 0.00 | 0.00 |
May | 0.578162E+10 | 0.123095E+10 | 0.514630E+10 | 0.245480E+10 | 0.269150E+10 | 0.00 | 0.00 |
June | 0.570975E+10 | 0.827818E+09 | 0.480587E+10 | 0.207801E+10 | 0.272786E+10 | 0.00 | 0.00 |
July | 0.645687E+10 | 0.841522E+09 | 0.530175E+10 | 0.246476E+10 | 0.283700E+10 | 0.00 | 0.00 |
August | 0.514931E+10 | 0.979366E+09 | 0.436299E+10 | 0.198251E+10 | 0.238048E+10 | 0.00 | 0.00 |
September | 0.346314E+10 | 0.146291E+10 | 0.329985E+10 | 0.148257E+10 | 0.181728E+10 | 0.00 | 0.00 |
October | 0.177676E+10 | 0.221897E+10 | 0.215402E+10 | 0.864716E+09 | 0.128930E+10 | 0.00 | 0.00 |
November | 0.660740E+09 | 0.311504E+10 | 0.126604E+10 | 0.426861E+09 | 0.839184E+09 | 0.00 | 0.00 |
December | 0.374318E+09 | 0.506696E+10 | 0.116623E+10 | 0.408187E+09 | 0.758041E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.381425E+11 | 0.300412E+11 | 0.386150E+11 | 0.175614E+11 | 0.210536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.374318E+09 | 0.827818E+09 | 0.116623E+10 | 0.408187E+09 | 0.758041E+09 | 0.00 | 0.00 |
Maximum of Months | 0.645687E+10 | 0.520886E+10 | 0.530175E+10 | 0.246476E+10 | 0.283700E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 14338674.19 | 0.859083E+10 | 0.103522E+10 | 0.00 | 0.103522E+10 | 0.00 | 0.00 |
February | 0.133586E+09 | 0.615688E+10 | 0.143628E+10 | 0.00 | 0.143628E+10 | 0.00 | 0.00 |
March | 0.349243E+09 | 0.531876E+10 | 0.195643E+10 | 0.00 | 0.195643E+10 | 0.00 | 0.00 |
April | 0.119317E+10 | 0.314686E+10 | 0.248202E+10 | 19371904.28 | 0.246265E+10 | 0.00 | 0.00 |
May | 0.316959E+10 | 0.175781E+10 | 0.360724E+10 | 0.194244E+09 | 0.341299E+10 | 0.00 | 0.00 |
June | 0.418078E+10 | 0.118141E+10 | 0.389587E+10 | 0.428260E+09 | 0.346761E+10 | 0.00 | 0.00 |
July | 0.432177E+10 | 0.114661E+10 | 0.384521E+10 | 0.329992E+09 | 0.351522E+10 | 0.00 | 0.00 |
August | 0.296864E+10 | 0.135562E+10 | 0.292056E+10 | 50154901.34 | 0.287040E+10 | 0.00 | 0.00 |
September | 0.164664E+10 | 0.213965E+10 | 0.220249E+10 | 539900.92 | 0.220195E+10 | 0.00 | 0.00 |
October | 0.600091E+09 | 0.332752E+10 | 0.158027E+10 | 0.00 | 0.158027E+10 | 0.00 | 0.00 |
November | 91115224.02 | 0.488488E+10 | 0.101259E+10 | 0.00 | 0.101259E+10 | 0.00 | 0.00 |
December | 902054.58 | 0.824524E+10 | 0.877119E+09 | 0.00 | 0.877119E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.186699E+11 | 0.472521E+11 | 0.268513E+11 | 0.102256E+10 | 0.258287E+11 | 0.00 | 0.00 |
Minimum of Months | 902054.58 | 0.114661E+10 | 0.877119E+09 | 0.00 | 0.877119E+09 | 0.00 | 0.00 |
Maximum of Months | 0.432177E+10 | 0.859083E+10 | 0.389587E+10 | 0.428260E+09 | 0.351522E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589985E+09 | 0.516010E+10 | 0.151310E+10 | 0.631613E+09 | 0.881483E+09 | 0.00 | 0.00 |
February | 0.127406E+10 | 0.368959E+10 | 0.214760E+10 | 0.916068E+09 | 0.123153E+10 | 0.00 | 0.00 |
March | 0.243368E+10 | 0.325454E+10 | 0.323976E+10 | 0.162511E+10 | 0.161465E+10 | 0.00 | 0.00 |
April | 0.411754E+10 | 0.198168E+10 | 0.434637E+10 | 0.234435E+10 | 0.200202E+10 | 0.00 | 0.00 |
May | 0.523359E+10 | 0.118189E+10 | 0.486085E+10 | 0.213689E+10 | 0.272397E+10 | 0.00 | 0.00 |
June | 0.625872E+10 | 0.804530E+09 | 0.532531E+10 | 0.254739E+10 | 0.277792E+10 | 0.00 | 0.00 |
July | 0.650260E+10 | 0.773289E+09 | 0.539074E+10 | 0.253115E+10 | 0.285959E+10 | 0.00 | 0.00 |
August | 0.481892E+10 | 0.898000E+09 | 0.415627E+10 | 0.181658E+10 | 0.233969E+10 | 0.00 | 0.00 |
September | 0.331592E+10 | 0.135438E+10 | 0.322110E+10 | 0.144175E+10 | 0.177935E+10 | 0.00 | 0.00 |
October | 0.154714E+10 | 0.209212E+10 | 0.201545E+10 | 0.764255E+09 | 0.125120E+10 | 0.00 | 0.00 |
November | 0.598171E+09 | 0.301341E+10 | 0.124166E+10 | 0.415116E+09 | 0.826546E+09 | 0.00 | 0.00 |
December | 0.363191E+09 | 0.501996E+10 | 0.117077E+10 | 0.432736E+09 | 0.738036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.370535E+11 | 0.292235E+11 | 0.386290E+11 | 0.176030E+11 | 0.210260E+11 | 0.00 | 0.00 |
Minimum of Months | 0.363191E+09 | 0.773289E+09 | 0.117077E+10 | 0.415116E+09 | 0.738036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.650260E+10 | 0.516010E+10 | 0.539074E+10 | 0.254739E+10 | 0.285959E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595095E+10 | 0.690333E+10 | 0.712856E+10 | 0.495918E+10 | 0.216938E+10 | 0.00 | 0.00 |
February | 0.764425E+10 | 0.527483E+10 | 0.815294E+10 | 0.550678E+10 | 0.264616E+10 | 0.00 | 0.00 |
March | 0.762774E+10 | 0.488654E+10 | 0.795341E+10 | 0.503341E+10 | 0.292001E+10 | 0.00 | 0.00 |
April | 0.728432E+10 | 0.321171E+10 | 0.697310E+10 | 0.378480E+10 | 0.318830E+10 | 0.00 | 0.00 |
May | 0.685281E+10 | 0.194310E+10 | 0.605797E+10 | 0.207107E+10 | 0.398689E+10 | 0.00 | 0.00 |
June | 0.635652E+10 | 0.129282E+10 | 0.526035E+10 | 0.140211E+10 | 0.385823E+10 | 0.00 | 0.00 |
July | 0.749534E+10 | 0.123785E+10 | 0.594297E+10 | 0.188271E+10 | 0.406027E+10 | 0.00 | 0.00 |
August | 0.776854E+10 | 0.143733E+10 | 0.634676E+10 | 0.265480E+10 | 0.369196E+10 | 0.00 | 0.00 |
September | 0.744750E+10 | 0.216775E+10 | 0.657902E+10 | 0.350382E+10 | 0.307520E+10 | 0.00 | 0.00 |
October | 0.582108E+10 | 0.319969E+10 | 0.580529E+10 | 0.341438E+10 | 0.239091E+10 | 0.00 | 0.00 |
November | 0.445352E+10 | 0.432259E+10 | 0.500442E+10 | 0.314078E+10 | 0.186364E+10 | 0.00 | 0.00 |
December | 0.423054E+10 | 0.669159E+10 | 0.550410E+10 | 0.360911E+10 | 0.189500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.789331E+11 | 0.425691E+11 | 0.767089E+11 | 0.409630E+11 | 0.357459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.423054E+10 | 0.123785E+10 | 0.500442E+10 | 0.140211E+10 | 0.186364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.776854E+10 | 0.690333E+10 | 0.815294E+10 | 0.550678E+10 | 0.406027E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.653698E+09 | 0.527715E+10 | 0.152929E+10 | 0.640377E+09 | 0.888915E+09 | 0.00 | 0.00 |
February | 0.147923E+10 | 0.383696E+10 | 0.225054E+10 | 0.102790E+10 | 0.122264E+10 | 0.00 | 0.00 |
March | 0.258826E+10 | 0.338832E+10 | 0.327884E+10 | 0.167776E+10 | 0.160108E+10 | 0.00 | 0.00 |
April | 0.384287E+10 | 0.209917E+10 | 0.405343E+10 | 0.205302E+10 | 0.200040E+10 | 0.00 | 0.00 |
May | 0.570592E+10 | 0.127644E+10 | 0.514637E+10 | 0.245484E+10 | 0.269152E+10 | 0.00 | 0.00 |
June | 0.565115E+10 | 0.855995E+09 | 0.480593E+10 | 0.207805E+10 | 0.272788E+10 | 0.00 | 0.00 |
July | 0.642915E+10 | 0.836917E+09 | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.00 | 0.00 |
August | 0.513656E+10 | 0.954559E+09 | 0.436305E+10 | 0.198254E+10 | 0.238050E+10 | 0.00 | 0.00 |
September | 0.345892E+10 | 0.142285E+10 | 0.329989E+10 | 0.148259E+10 | 0.181730E+10 | 0.00 | 0.00 |
October | 0.177583E+10 | 0.216331E+10 | 0.215405E+10 | 0.864730E+09 | 0.128932E+10 | 0.00 | 0.00 |
November | 0.651977E+09 | 0.308579E+10 | 0.126606E+10 | 0.426868E+09 | 0.839194E+09 | 0.00 | 0.00 |
December | 0.365467E+09 | 0.510510E+10 | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377390E+11 | 0.303026E+11 | 0.386155E+11 | 0.175617E+11 | 0.210538E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365467E+09 | 0.836917E+09 | 0.116624E+10 | 0.408194E+09 | 0.758050E+09 | 0.00 | 0.00 |
Maximum of Months | 0.642915E+10 | 0.527715E+10 | 0.530182E+10 | 0.246480E+10 | 0.283702E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.574696E+10 | -0.549024E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -256722827.4 | 60.05 | 0.00 | 0.00 |
February | 0.532689E+10 | -0.510162E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -225268083.4 | 60.05 | 0.00 | 0.00 |
March | 0.626095E+10 | -0.601659E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -244363869.6 | 60.05 | 0.00 | 0.00 |
April | 0.548333E+10 | -0.525371E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229619812.7 | 60.05 | 0.00 | 0.00 |
May | 0.559182E+10 | -0.535901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232815023.2 | 60.05 | 0.00 | 0.00 |
June | 0.523692E+10 | -0.501176E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225156011.5 | 60.05 | 0.00 | 0.00 |
July | 0.470881E+10 | -0.447756E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231253080.4 | 60.05 | 0.00 | 0.00 |
August | 0.504546E+10 | -0.481309E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232369370.7 | 60.05 | 0.00 | 0.00 |
September | 0.457987E+10 | -0.435482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225046304.3 | 60.05 | 0.00 | 0.00 |
October | 0.490556E+10 | -0.466946E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236101099.1 | 60.05 | 0.00 | 0.00 |
November | 0.509222E+10 | -0.485746E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -234755626.2 | 60.05 | 0.00 | 0.00 |
December | 0.534713E+10 | -0.509420E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -252924420.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.633259E+11 | -0.604995E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.282640E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.457987E+10 | -0.601659E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -256722827.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.626095E+10 | -0.435482E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -225046304.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.50 | 0.48 | 01-JAN-08:39 | 5710.27 | 35.71 | 235.50 | 238.33 | 4785.85 | 36.82 | 241.67 | 228.00 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 8825.49 | 36.23 | 260.83 | 258.33 | 3864.60 | 31.69 | 238.83 | 245.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12429.85 | 35.29 | 216.00 | 323.50 | 2067.29 | 21.92 | 190.33 | 290.67 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:00 | 2599.81 | 18.71 | 23.67 | 350.33 | 1614.07 | 21.00 | 184.33 | 320.00 |
May | 437.50 | 0.51 | 0.48 | 01-MAY-06:30 | 2267.68 | 19.27 | 10.83 | 413.00 | 1275.97 | 21.50 | 260.17 | 372.33 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 2155.11 | 19.37 | 15.17 | 414.83 | 1227.14 | 21.59 | 257.33 | 374.83 |
July | 409.17 | 0.51 | 0.48 | 01-JUL-05:30 | 2337.60 | 19.64 | 33.83 | 420.67 | 1342.29 | 21.88 | 271.33 | 383.83 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2938.43 | 20.19 | 55.83 | 379.17 | 1566.78 | 22.09 | 239.67 | 341.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 4950.68 | 23.29 | 114.50 | 332.67 | 1612.70 | 21.97 | 223.17 | 302.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6225.88 | 31.95 | 270.50 | 298.17 | 1646.10 | 24.15 | 212.33 | 274.33 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4508.98 | 34.27 | 244.67 | 240.83 | 3735.64 | 35.62 | 247.50 | 220.83 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4243.35 | 33.76 | 210.50 | 224.17 | 3532.99 | 35.19 | 217.17 | 205.33 |
Annual Sum or Average | 3785.50 | 0.50 | 4541.03 | 25.93 | 1691.83 | 3894.00 | 2152.53 | 25.32 | 2783.83 | 3559.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2155.11 | 18.71 | 10.83 | 224.17 | 1227.14 | 21.00 | 184.33 | 205.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12429.85 | 36.23 | 270.50 | 420.67 | 4785.85 | 36.82 | 271.33 | 383.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1879.04 | 23.31 | 100.00 | 223.17 | 1106.88 | 24.05 | 110.17 | 192.83 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2425.93 | 21.74 | 74.33 | 247.50 | 1342.49 | 23.90 | 132.67 | 223.83 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 4157.62 | 23.38 | 80.83 | 318.00 | 2576.27 | 25.70 | 117.33 | 283.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4469.73 | 22.31 | 84.33 | 357.17 | 2671.40 | 24.51 | 103.50 | 326.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4082.13 | 22.34 | 135.67 | 422.33 | 1827.17 | 22.63 | 119.50 | 388.17 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-04:49 | 4943.69 | 22.81 | 120.00 | 419.50 | 2337.33 | 23.92 | 108.67 | 388.50 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4736.66 | 23.20 | 126.00 | 426.00 | 2207.54 | 23.91 | 130.17 | 395.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3978.24 | 22.88 | 99.83 | 382.33 | 1785.34 | 23.00 | 109.83 | 349.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3107.84 | 21.70 | 97.83 | 332.00 | 1665.50 | 22.84 | 132.50 | 298.67 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2297.19 | 21.49 | 97.17 | 288.50 | 1032.11 | 22.33 | 96.50 | 250.83 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-07:00 | 1510.20 | 20.53 | 77.50 | 226.50 | 847.96 | 22.87 | 87.67 | 189.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1362.81 | 21.32 | 67.33 | 206.50 | 913.59 | 23.63 | 88.50 | 173.50 |
Annual Sum or Average | 3785.50 | 0.51 | 3446.62 | 22.31 | 1160.83 | 3849.50 | 1756.44 | 23.54 | 1337.00 | 3459.50 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1362.81 | 20.53 | 67.33 | 206.50 | 847.96 | 22.33 | 87.67 | 173.50 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4943.69 | 23.38 | 135.67 | 426.00 | 2671.40 | 25.70 | 132.67 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.55 | 0.48 | 01-JAN-10:30 | 685.84 | 15.94 | 0.00 | 208.83 | 397.86 | 18.41 | 0.33 | 151.00 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 868.03 | 17.20 | 0.00 | 238.50 | 520.51 | 19.61 | 12.83 | 198.50 |
March | 254.17 | 0.52 | 0.48 | 02-MAR-10:39 | 941.13 | 17.82 | 0.00 | 312.00 | 600.69 | 20.20 | 28.50 | 258.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 1070.32 | 18.23 | 0.00 | 354.67 | 678.41 | 20.44 | 69.67 | 321.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1458.67 | 20.51 | 39.83 | 431.33 | 849.60 | 23.45 | 265.00 | 413.67 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1737.03 | 22.71 | 118.17 | 438.67 | 1004.72 | 24.76 | 295.17 | 413.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1660.18 | 22.25 | 111.17 | 439.50 | 983.09 | 24.34 | 297.17 | 417.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1387.12 | 19.48 | 10.00 | 387.83 | 825.90 | 21.64 | 190.67 | 353.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1051.19 | 18.28 | 0.00 | 330.33 | 619.82 | 20.47 | 43.00 | 287.17 |
October | 299.00 | 0.52 | 0.48 | 01-OCT-07:30 | 861.88 | 17.16 | 0.00 | 278.50 | 485.59 | 19.38 | 2.50 | 222.50 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:00 | 666.50 | 15.75 | 0.00 | 212.83 | 373.19 | 18.00 | 0.00 | 144.83 |
December | 226.33 | 0.55 | 0.48 | 01-DEC-09:30 | 635.98 | 15.66 | 0.00 | 192.50 | 356.94 | 18.01 | 0.00 | 124.00 |
Annual Sum or Average | 3785.50 | 0.51 | 1160.26 | 18.87 | 279.17 | 3825.50 | 684.81 | 21.18 | 1204.83 | 3306.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 635.98 | 15.66 | 0.00 | 192.50 | 356.94 | 18.00 | 0.00 | 124.00 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1737.03 | 22.71 | 118.17 | 439.50 | 1004.72 | 24.76 | 297.17 | 417.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:30 | 1755.76 | 21.44 | 76.83 | 224.50 | 1046.44 | 23.70 | 99.83 | 195.00 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 2449.69 | 21.94 | 75.50 | 249.67 | 1360.64 | 23.98 | 126.33 | 225.33 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 3871.58 | 23.36 | 78.83 | 318.33 | 2261.68 | 24.22 | 100.33 | 281.33 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:20 | 4616.42 | 21.85 | 84.50 | 354.00 | 2021.89 | 21.48 | 68.17 | 323.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3716.89 | 19.70 | 81.83 | 420.67 | 2173.53 | 21.39 | 76.33 | 393.67 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:30 | 4020.61 | 18.59 | 47.00 | 431.00 | 1781.82 | 19.78 | 29.83 | 399.00 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:40 | 4334.31 | 19.05 | 53.67 | 434.17 | 1941.36 | 19.99 | 37.50 | 403.50 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:49 | 3913.87 | 21.14 | 79.33 | 384.50 | 2223.46 | 22.42 | 103.83 | 350.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 3300.94 | 21.98 | 100.33 | 333.00 | 1922.14 | 23.25 | 123.17 | 301.67 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2482.45 | 22.03 | 101.50 | 289.33 | 1079.86 | 22.58 | 93.50 | 252.33 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:00 | 1494.84 | 20.41 | 76.17 | 227.33 | 806.98 | 22.39 | 80.00 | 191.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:30 | 1390.61 | 20.78 | 66.00 | 212.17 | 733.45 | 21.61 | 60.00 | 174.50 |
Annual Sum or Average | 3785.50 | 0.51 | 3275.76 | 20.83 | 921.50 | 3878.67 | 1688.55 | 22.03 | 998.83 | 3492.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1390.61 | 18.59 | 47.00 | 212.17 | 733.45 | 19.78 | 29.83 | 174.50 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4616.42 | 23.36 | 101.50 | 434.17 | 2261.68 | 24.22 | 126.33 | 403.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.50 | 0.48 | 01-JAN-08:39 | 5455.04 | 33.88 | 219.33 | 236.00 | 4641.72 | 36.49 | 233.33 | 226.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 8605.49 | 35.95 | 257.00 | 257.67 | 3690.72 | 30.25 | 173.00 | 243.67 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 12216.67 | 34.67 | 215.00 | 322.00 | 1903.28 | 19.20 | 24.00 | 287.67 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:00 | 2450.35 | 14.99 | 0.00 | 349.17 | 1499.36 | 18.61 | 28.50 | 316.83 |
May | 437.50 | 0.51 | 0.48 | 01-MAY-06:30 | 2164.65 | 15.58 | 0.00 | 411.00 | 1205.08 | 19.08 | 20.50 | 369.17 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 2060.94 | 15.83 | 0.00 | 412.83 | 1164.47 | 19.31 | 41.00 | 370.67 |
July | 409.17 | 0.51 | 0.48 | 01-JUL-05:40 | 2231.71 | 16.10 | 0.00 | 417.67 | 1270.37 | 19.61 | 55.67 | 380.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2803.39 | 16.58 | 8.00 | 377.50 | 1471.41 | 19.66 | 55.33 | 339.17 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 4801.45 | 20.48 | 92.00 | 331.00 | 1502.56 | 19.29 | 29.33 | 299.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6081.69 | 31.28 | 263.83 | 296.83 | 1539.96 | 21.71 | 72.00 | 271.67 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4346.61 | 32.85 | 233.17 | 239.50 | 3631.32 | 35.36 | 245.83 | 219.83 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4084.31 | 33.03 | 205.67 | 222.83 | 3417.77 | 34.79 | 211.83 | 204.00 |
Annual Sum or Average | 3785.50 | 0.51 | 4391.83 | 23.49 | 1494.00 | 3874.00 | 2047.25 | 23.35 | 1190.33 | 3528.33 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 2060.94 | 14.99 | 0.00 | 222.83 | 1164.47 | 18.61 | 20.50 | 204.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12216.67 | 35.95 | 263.83 | 417.67 | 4641.72 | 36.49 | 245.83 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1827.10 | 22.88 | 99.33 | 221.00 | 1067.49 | 23.83 | 100.33 | 189.83 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2351.17 | 21.25 | 74.17 | 246.33 | 1283.45 | 23.69 | 122.17 | 220.33 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 4053.38 | 22.91 | 80.83 | 316.50 | 2492.18 | 25.51 | 111.00 | 280.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4350.83 | 21.85 | 84.33 | 355.50 | 2574.52 | 24.33 | 95.00 | 323.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 3983.16 | 21.90 | 135.50 | 420.33 | 1749.18 | 22.46 | 103.17 | 385.67 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-04:49 | 4825.26 | 22.36 | 120.00 | 417.33 | 2245.94 | 23.76 | 96.33 | 386.00 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4612.24 | 22.68 | 125.00 | 424.50 | 2102.30 | 23.14 | 106.33 | 393.17 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3819.98 | 21.47 | 89.17 | 380.50 | 1703.81 | 22.81 | 98.50 | 345.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3023.15 | 21.24 | 97.33 | 330.50 | 1599.20 | 22.61 | 111.33 | 295.50 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2236.62 | 21.03 | 96.50 | 286.00 | 964.89 | 21.50 | 72.00 | 246.17 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-07:00 | 1464.74 | 20.04 | 77.00 | 225.17 | 814.09 | 22.64 | 81.33 | 185.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1314.66 | 20.55 | 64.33 | 205.00 | 881.42 | 23.40 | 82.17 | 171.00 |
Annual Sum or Average | 3785.50 | 0.51 | 3351.09 | 21.74 | 1143.50 | 3828.67 | 1683.30 | 23.23 | 1179.67 | 3422.50 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1314.66 | 20.04 | 64.33 | 205.00 | 814.09 | 21.50 | 72.00 | 171.00 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4825.26 | 22.91 | 135.50 | 424.50 | 2574.52 | 25.51 | 122.17 | 393.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.55 | 0.48 | 01-JAN-10:39 | 659.70 | 12.18 | 0.00 | 204.83 | 383.26 | 15.90 | 0.00 | 145.33 |
February | 265.33 | 0.53 | 0.48 | 01-FEB-09:30 | 835.53 | 13.68 | 0.00 | 236.83 | 502.80 | 17.31 | 0.00 | 193.17 |
March | 254.17 | 0.52 | 0.48 | 02-MAR-10:39 | 907.47 | 14.61 | 0.00 | 309.67 | 583.30 | 18.24 | 0.00 | 253.50 |
April | 296.33 | 0.52 | 0.48 | 01-APR-08:09 | 1034.35 | 15.11 | 0.00 | 354.00 | 660.01 | 18.67 | 5.83 | 317.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:30 | 1408.10 | 17.33 | 30.00 | 429.83 | 820.80 | 21.59 | 83.33 | 411.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1676.86 | 19.95 | 76.83 | 437.67 | 970.03 | 23.03 | 138.33 | 411.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1589.94 | 18.22 | 38.50 | 437.67 | 950.09 | 22.63 | 136.50 | 415.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1337.87 | 16.19 | 0.00 | 386.50 | 798.92 | 19.70 | 44.50 | 350.50 |
September | 344.17 | 0.51 | 0.48 | 01-SEP-06:49 | 1014.13 | 14.90 | 0.00 | 328.33 | 599.55 | 18.37 | 0.17 | 282.50 |
October | 299.00 | 0.52 | 0.48 | 01-OCT-07:30 | 831.23 | 13.47 | 0.00 | 276.33 | 468.28 | 16.98 | 0.00 | 216.17 |
November | 255.50 | 0.56 | 0.48 | 01-NOV-08:00 | 641.94 | 11.86 | 0.00 | 209.67 | 359.22 | 15.40 | 0.00 | 136.67 |
December | 226.33 | 0.56 | 0.48 | 01-DEC-09:39 | 612.04 | 11.75 | 0.00 | 189.83 | 343.30 | 15.39 | 0.00 | 110.50 |
Annual Sum or Average | 3785.50 | 0.51 | 1117.93 | 15.43 | 145.33 | 3801.17 | 661.97 | 19.11 | 408.67 | 3244.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 612.04 | 11.75 | 0.00 | 189.83 | 343.30 | 15.39 | 0.00 | 110.50 | |
Maximum of Months | 437.50 | 0.56 | 0.48 | 1676.86 | 19.95 | 76.83 | 437.67 | 970.03 | 23.03 | 138.33 | 415.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:39 | 1702.54 | 21.05 | 76.33 | 222.17 | 1004.02 | 23.59 | 97.50 | 191.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 2372.97 | 21.55 | 75.50 | 248.33 | 1248.06 | 22.67 | 112.33 | 222.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 3773.91 | 22.95 | 78.83 | 316.83 | 2182.29 | 24.11 | 98.67 | 278.17 |
April | 296.33 | 0.52 | 0.48 | 01-APR-08:20 | 4369.38 | 21.41 | 84.50 | 351.00 | 1937.33 | 21.34 | 64.50 | 321.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:40 | 3613.80 | 19.23 | 81.67 | 419.67 | 2091.80 | 21.24 | 71.33 | 391.17 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:40 | 3913.62 | 18.09 | 47.00 | 429.50 | 1700.41 | 19.60 | 21.17 | 396.17 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:40 | 4218.84 | 18.57 | 53.67 | 431.83 | 1851.92 | 19.83 | 30.00 | 399.50 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:49 | 3800.11 | 20.70 | 79.17 | 383.00 | 2113.29 | 22.28 | 97.67 | 346.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 3212.50 | 21.57 | 100.00 | 331.17 | 1805.25 | 23.02 | 118.17 | 298.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2417.38 | 21.64 | 100.67 | 287.50 | 1006.89 | 21.67 | 83.17 | 248.33 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:00 | 1449.01 | 20.00 | 75.83 | 225.50 | 773.07 | 22.28 | 79.83 | 187.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:30 | 1348.12 | 20.39 | 65.67 | 210.17 | 702.06 | 21.50 | 59.33 | 169.83 |
Annual Sum or Average | 3785.50 | 0.51 | 3175.90 | 20.40 | 918.83 | 3856.67 | 1607.41 | 21.74 | 933.67 | 3449.83 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1348.12 | 18.09 | 47.00 | 210.17 | 702.06 | 19.60 | 21.17 | 169.83 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4369.38 | 22.95 | 100.67 | 431.83 | 2182.29 | 24.11 | 118.17 | 399.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.50 | 0.48 | 01-JAN-08:39 | 5455.03 | 33.88 | 219.33 | 236.00 | 4641.62 | 36.49 | 233.33 | 226.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-08:39 | 8605.45 | 35.95 | 257.17 | 257.67 | 3690.58 | 30.25 | 173.00 | 243.67 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 12216.58 | 34.67 | 215.00 | 322.00 | 1903.16 | 19.20 | 24.00 | 287.67 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:00 | 2450.23 | 14.99 | 0.00 | 349.17 | 1499.26 | 18.61 | 28.50 | 316.83 |
May | 437.50 | 0.51 | 0.48 | 01-MAY-06:30 | 2164.52 | 15.58 | 0.00 | 411.00 | 1204.98 | 19.08 | 20.50 | 369.17 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 2060.82 | 15.83 | 0.00 | 412.83 | 1164.38 | 19.31 | 41.00 | 370.67 |
July | 409.17 | 0.51 | 0.48 | 01-JUL-05:40 | 2231.58 | 16.11 | 0.00 | 417.67 | 1270.28 | 19.61 | 55.67 | 380.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2803.24 | 16.59 | 8.00 | 377.50 | 1471.30 | 19.66 | 55.33 | 339.17 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 4801.31 | 20.48 | 92.00 | 331.00 | 1502.45 | 19.29 | 29.33 | 299.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6081.61 | 31.28 | 263.83 | 296.83 | 1539.84 | 21.71 | 72.00 | 271.67 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4346.58 | 32.85 | 233.17 | 239.50 | 3631.23 | 35.36 | 245.83 | 219.83 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4084.30 | 33.03 | 205.67 | 222.83 | 3417.69 | 34.79 | 211.83 | 204.00 |
Annual Sum or Average | 3785.50 | 0.51 | 4391.73 | 23.49 | 1494.17 | 3874.00 | 2047.14 | 23.35 | 1190.33 | 3528.33 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 2060.82 | 14.99 | 0.00 | 222.83 | 1164.38 | 18.61 | 20.50 | 204.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12216.58 | 35.95 | 263.83 | 417.67 | 4641.62 | 36.49 | 245.83 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1827.07 | 22.88 | 99.33 | 221.00 | 1067.44 | 23.83 | 100.33 | 189.83 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2351.14 | 21.25 | 74.17 | 246.33 | 1283.38 | 23.69 | 122.17 | 220.33 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 4053.35 | 22.91 | 80.83 | 316.50 | 2492.11 | 25.51 | 111.00 | 280.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4350.80 | 21.86 | 84.33 | 355.50 | 2574.45 | 24.33 | 95.00 | 323.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 3983.08 | 21.91 | 135.50 | 420.33 | 1749.09 | 22.46 | 103.17 | 385.67 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-04:49 | 4825.19 | 22.37 | 120.00 | 417.33 | 2245.85 | 23.76 | 96.33 | 386.00 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4612.17 | 22.69 | 125.00 | 424.50 | 2102.20 | 23.14 | 106.33 | 393.17 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3819.92 | 21.48 | 89.17 | 380.50 | 1703.72 | 22.81 | 98.50 | 345.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3023.09 | 21.24 | 97.33 | 330.50 | 1599.12 | 22.61 | 111.33 | 295.50 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2236.56 | 21.03 | 96.50 | 286.00 | 964.82 | 21.50 | 72.00 | 246.17 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-07:00 | 1464.70 | 20.04 | 77.00 | 225.17 | 814.04 | 22.64 | 81.33 | 185.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1314.62 | 20.55 | 64.33 | 205.00 | 881.37 | 23.40 | 82.17 | 171.00 |
Annual Sum or Average | 3785.50 | 0.51 | 3351.04 | 21.74 | 1143.50 | 3828.67 | 1683.23 | 23.24 | 1179.67 | 3422.50 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1314.62 | 20.04 | 64.33 | 205.00 | 814.04 | 21.50 | 72.00 | 171.00 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4825.19 | 22.91 | 135.50 | 424.50 | 2574.45 | 25.51 | 122.17 | 393.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.55 | 0.48 | 01-JAN-10:39 | 659.68 | 12.18 | 0.00 | 204.83 | 383.23 | 15.90 | 0.00 | 145.33 |
February | 265.33 | 0.53 | 0.48 | 01-FEB-09:30 | 835.51 | 13.68 | 0.00 | 236.83 | 502.76 | 17.31 | 0.00 | 193.17 |
March | 254.17 | 0.52 | 0.48 | 02-MAR-10:39 | 907.45 | 14.61 | 0.00 | 309.67 | 583.27 | 18.24 | 0.00 | 253.50 |
April | 296.33 | 0.52 | 0.48 | 01-APR-08:09 | 1034.33 | 15.11 | 0.00 | 354.00 | 659.98 | 18.67 | 5.83 | 317.67 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:30 | 1408.05 | 17.33 | 30.00 | 429.83 | 820.75 | 21.59 | 83.33 | 411.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1676.81 | 19.95 | 76.83 | 437.67 | 969.97 | 23.04 | 138.33 | 411.83 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1589.89 | 18.22 | 38.50 | 437.67 | 950.04 | 22.63 | 136.50 | 415.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1337.83 | 16.19 | 0.00 | 386.50 | 798.87 | 19.70 | 44.50 | 350.50 |
September | 344.17 | 0.51 | 0.48 | 01-SEP-06:49 | 1014.09 | 14.91 | 0.00 | 328.33 | 599.51 | 18.37 | 0.17 | 282.50 |
October | 299.00 | 0.52 | 0.48 | 01-OCT-07:30 | 831.19 | 13.48 | 0.00 | 276.33 | 468.24 | 16.98 | 0.00 | 216.17 |
November | 255.50 | 0.56 | 0.48 | 01-NOV-08:00 | 641.91 | 11.86 | 0.00 | 209.67 | 359.19 | 15.40 | 0.00 | 136.67 |
December | 226.33 | 0.56 | 0.48 | 01-DEC-09:39 | 612.02 | 11.75 | 0.00 | 189.83 | 343.28 | 15.40 | 0.00 | 110.50 |
Annual Sum or Average | 3785.50 | 0.51 | 1117.90 | 15.43 | 145.33 | 3801.17 | 661.92 | 19.12 | 408.67 | 3244.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 612.02 | 11.75 | 0.00 | 189.83 | 343.28 | 15.40 | 0.00 | 110.50 | |
Maximum of Months | 437.50 | 0.56 | 0.48 | 1676.81 | 19.95 | 76.83 | 437.67 | 969.97 | 23.04 | 138.33 | 415.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:39 | 1702.51 | 21.05 | 76.33 | 222.17 | 1003.97 | 23.59 | 97.50 | 191.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 2372.93 | 21.55 | 75.50 | 248.33 | 1248.00 | 22.68 | 112.50 | 222.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 3773.89 | 22.95 | 78.83 | 316.83 | 2182.22 | 24.11 | 98.67 | 278.17 |
April | 296.33 | 0.52 | 0.48 | 01-APR-08:20 | 4369.34 | 21.41 | 84.50 | 350.83 | 1937.26 | 21.34 | 64.50 | 321.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:40 | 3613.73 | 19.24 | 81.67 | 419.67 | 2091.71 | 21.24 | 71.33 | 391.17 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-05:40 | 3913.54 | 18.10 | 47.00 | 429.50 | 1700.32 | 19.60 | 21.17 | 396.17 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:40 | 4218.76 | 18.57 | 53.67 | 431.83 | 1851.83 | 19.83 | 30.00 | 399.50 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:49 | 3800.05 | 20.71 | 79.17 | 383.00 | 2113.19 | 22.28 | 97.67 | 346.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 3212.44 | 21.57 | 100.00 | 331.17 | 1805.17 | 23.02 | 118.33 | 298.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:30 | 2417.32 | 21.64 | 100.67 | 287.50 | 1006.83 | 21.67 | 83.17 | 248.33 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:00 | 1448.97 | 20.00 | 75.83 | 225.50 | 773.02 | 22.28 | 79.83 | 187.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:30 | 1348.09 | 20.39 | 65.67 | 210.17 | 702.01 | 21.50 | 59.33 | 169.83 |
Annual Sum or Average | 3785.50 | 0.51 | 3175.84 | 20.40 | 918.83 | 3856.50 | 1607.33 | 21.74 | 934.00 | 3449.83 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1348.09 | 18.10 | 47.00 | 210.17 | 702.01 | 19.60 | 21.17 | 169.83 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4369.34 | 22.95 | 100.67 | 431.83 | 2182.22 | 24.11 | 118.33 | 399.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106663E+11 | 43826.35 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327693E+10 | 42922.36 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202286E+09 | 34258.69 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31970211.91 | 8422.57 | 21-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3255084.19 | 2211.40 | 13-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 529976.48 | 5.88 | 30-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1033532.33 | 6.06 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 661920.64 | 5.82 | 08-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1432598.09 | 2362.05 | 23-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26022419.91 | 9688.42 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52409474.72 | 6229.03 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559034E+10 | 42191.45 | 20-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 529976.48 | 5.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106663E+11 | 43826.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107261E+10 | 14064.94 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6088424.40 | 14055.34 | 21-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4421972.11 | 14045.48 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1682943.94 | 14047.84 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272389E+09 | 14052.37 | 28-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107261E+10 | 14064.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115785E+11 | 11019.26 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721565E+10 | 10772.17 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691740E+10 | 10429.21 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270105E+10 | 10483.60 | 24-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.787828E+09 | 10788.05 | 31-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162241E+09 | 10485.14 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24165341.67 | 8478.69 | 18-JUL-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75172388.06 | 9922.74 | 25-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.703511E+09 | 10684.83 | 13-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225822E+10 | 10488.85 | 03-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480849E+10 | 10431.86 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105033E+11 | 10584.96 | 20-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.477356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 24165341.67 | 8478.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115785E+11 | 11019.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.610772E+10 | 7849.72 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339466E+10 | 7673.29 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250592E+10 | 7428.44 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464457E+09 | 7412.73 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 718834.61 | 3593.59 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198261E+09 | 7409.00 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159399E+10 | 7430.86 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.500015E+10 | 7527.16 | 20-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610772E+10 | 7849.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959829E+10 | 8120.93 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605850E+10 | 7941.14 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498735E+10 | 7691.35 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124389E+10 | 7684.60 | 10-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37522541.58 | 7673.41 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244297E+09 | 7685.46 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.236274E+10 | 7694.30 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767717E+10 | 7803.76 | 20-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.959829E+10 | 8120.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.637816E+10 | 8194.14 | 06-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361256E+10 | 8009.57 | 14-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276847E+10 | 7753.46 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.666113E+09 | 7737.22 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24231180.52 | 7726.01 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243305E+09 | 7732.74 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172209E+10 | 7755.88 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.521784E+10 | 7869.30 | 20-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.637816E+10 | 8194.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110378E+11 | 45285.43 | 06-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356387E+10 | 44573.23 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325669E+09 | 32228.21 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13937800.58 | 7790.81 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1513810.20 | 2745.60 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 571429.34 | 5.53 | 26-JUN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 949303.12 | 5.71 | 24-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 545401.44 | 5.41 | 08-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 700535.71 | 1079.20 | 06-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8695477.30 | 5472.63 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127197E+09 | 8308.71 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600482E+10 | 43797.42 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 545401.44 | 5.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110378E+11 | 45285.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566374E+10 | 20024.94 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227575E+10 | 20030.55 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.958699E+09 | 20026.27 | 10-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50710266.77 | 19991.04 | 10-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40192256.76 | 19959.14 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123318E+10 | 20031.77 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447241E+10 | 20039.46 | 06-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.566374E+10 | 20039.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.571166E+10 | 11489.61 | 06-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285789E+10 | 11297.77 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201511E+10 | 11144.60 | 06-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376404E+09 | 11145.61 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10707562.30 | 11082.30 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 271416.32 | 255.62 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.375120E+09 | 11135.63 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196075E+10 | 11174.43 | 06-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.547075E+10 | 11178.86 | 28-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571166E+10 | 11489.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575876E+10 | 8495.88 | 06-JAN-08:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310201E+10 | 8320.69 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198751E+10 | 8214.37 | 16-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317058E+09 | 8182.78 | 10-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 104578.69 | 472.32 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4942365.88 | 2557.84 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471391E+09 | 8183.57 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205650E+10 | 8213.00 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.526216E+10 | 8203.46 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.575876E+10 | 8495.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860381E+10 | 8642.03 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487199E+10 | 8366.24 | 14-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302281E+10 | 8281.63 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448912E+09 | 8278.63 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5596402.59 | 8203.91 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.394917E+09 | 8267.17 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252190E+10 | 8286.23 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.752791E+10 | 8283.02 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860381E+10 | 8642.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.587876E+10 | 8752.44 | 06-JAN-08:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327493E+10 | 8483.56 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215995E+10 | 8359.13 | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439004E+09 | 8362.95 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12306506.90 | 8314.33 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7830118.87 | 2184.77 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.491941E+09 | 8338.56 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209255E+10 | 8358.23 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.533981E+10 | 8358.88 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.587876E+10 | 8752.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147822E+11 | 45848.45 | 06-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562985E+10 | 45013.26 | 14-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121965E+10 | 35604.79 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58750103.31 | 6117.28 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2585141.90 | 3061.32 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 571487.25 | 6.27 | 30-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 945311.85 | 6.30 | 24-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 523334.14 | 53.64 | 19-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2058303.85 | 1490.84 | 29-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49911649.22 | 5904.81 | 12-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662108E+09 | 5691.59 | 29-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.952602E+10 | 44354.38 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 523334.14 | 6.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147822E+11 | 45848.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122933E+11 | 26623.37 | 30-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.707212E+10 | 26632.40 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.417594E+10 | 26647.50 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.688204E+09 | 26633.19 | 10-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16813919.56 | 26604.84 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.860083E+09 | 26639.84 | 13-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462956E+10 | 26641.38 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107893E+11 | 26649.40 | 06-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122933E+11 | 26649.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871725E+10 | 13653.22 | 06-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502034E+10 | 13388.65 | 14-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373555E+10 | 13054.59 | 08-MAR-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105544E+10 | 13052.96 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58917532.70 | 12976.64 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3811332.55 | 6687.90 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 57797816.22 | 10751.01 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115304E+10 | 13055.68 | 30-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368202E+10 | 13053.91 | 25-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852128E+10 | 13189.39 | 20-DEC-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.871725E+10 | 13653.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.788065E+10 | 9684.66 | 06-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.467519E+10 | 9496.78 | 14-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310760E+10 | 9260.68 | 08-MAR-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.693605E+09 | 9249.14 | 06-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11827230.03 | 9199.92 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42186.03 | 281.24 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58663536.66 | 6827.00 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107337E+10 | 9268.04 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326978E+10 | 9257.18 | 14-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733793E+10 | 9342.56 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.788065E+10 | 9684.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121399E+11 | 10237.37 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.766384E+10 | 9923.70 | 14-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.517436E+10 | 9705.07 | 23-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118795E+10 | 9699.29 | 04-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38944874.02 | 9684.61 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 482271.45 | 2360.89 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40703423.29 | 9657.27 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123023E+10 | 9701.84 | 16-OCT-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460050E+10 | 9702.98 | 30-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110394E+11 | 9848.80 | 20-DEC-08:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121399E+11 | 10237.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.821279E+10 | 10278.49 | 06-JAN-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506849E+10 | 9958.09 | 14-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353091E+10 | 9700.26 | 01-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101602E+10 | 9698.85 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59720177.16 | 9645.82 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6646002.43 | 6251.27 | 19-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98917179.91 | 6795.60 | 23-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121128E+10 | 9717.12 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349414E+10 | 9703.49 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.761595E+10 | 9843.43 | 20-DEC-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.821279E+10 | 10278.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5326878.93 | 5263400.39 | 5332.22 | 30-JAN-07:01 | 5332.22 | 0.00 |
February | 0.00 | 0.00 | 14507630.43 | 14382133.19 | 5474.64 | 21-FEB-07:02 | 5474.64 | 0.00 |
March | 0.00 | 0.00 | 33375741.29 | 32181059.39 | 3777.81 | 25-MAR-06:03 | 3777.81 | 0.00 |
April | 0.00 | 0.00 | 0.130013E+10 | 0.125811E+10 | 30880.67 | 23-APR-17:42 | 30880.67 | 0.00 |
May | 0.00 | 0.00 | 0.165921E+11 | 0.156052E+11 | 61849.97 | 26-MAY-11:00 | 41996.64 | 0.00 |
June | 0.00 | 0.00 | 0.391819E+11 | 0.306526E+11 | 113517.62 | 29-JUN-06:03 | 54544.21 | 0.00 |
July | 0.00 | 0.00 | 0.548014E+11 | 0.411874E+11 | 120481.45 | 05-JUL-10:20 | 43653.80 | 0.00 |
August | 0.00 | 0.00 | 0.434762E+11 | 0.314249E+11 | 97238.56 | 08-AUG-10:10 | 53330.04 | 0.00 |
September | 0.00 | 0.00 | 0.959320E+10 | 0.807359E+10 | 68086.80 | 01-SEP-13:20 | 52581.99 | 0.00 |
October | 0.00 | 0.00 | 0.129406E+10 | 0.123984E+10 | 31213.24 | 19-OCT-15:00 | 31213.24 | 0.00 |
November | 0.00 | 0.00 | 0.200996E+09 | 0.148477E+09 | 10238.48 | 01-NOV-15:00 | 7547.49 | 0.00 |
December | 0.00 | 0.00 | 11378264.60 | 11169598.69 | 6732.53 | 28-DEC-07:01 | 6732.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166505E+12 | 0.129653E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 5326878.93 | 5263400.39 | 3777.81 | 3777.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548014E+11 | 0.411874E+11 | 120481.45 | 54544.21 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6372378.99 | 6371422.50 | 6381.05 | 20-JAN-07:01 | 6381.05 | 0.00 |
February | 0.00 | 0.00 | 14581552.00 | 14575582.85 | 8224.76 | 09-FEB-07:01 | 8224.76 | 0.00 |
March | 0.00 | 0.00 | 22798940.59 | 22670886.45 | 8173.66 | 27-MAR-06:01 | 8173.66 | 0.00 |
April | 0.00 | 0.00 | 0.146513E+10 | 0.143547E+10 | 40695.64 | 23-APR-16:22 | 40695.64 | 0.00 |
May | 0.00 | 0.00 | 0.170955E+11 | 0.161036E+11 | 63043.42 | 25-MAY-16:00 | 55419.73 | 0.00 |
June | 0.00 | 0.00 | 0.384407E+11 | 0.304736E+11 | 108422.80 | 30-JUN-04:02 | 68262.77 | 0.00 |
July | 0.00 | 0.00 | 0.511447E+11 | 0.385276E+11 | 115918.53 | 05-JUL-10:20 | 42050.33 | 0.00 |
August | 0.00 | 0.00 | 0.383236E+11 | 0.279340E+11 | 90762.08 | 31-AUG-12:50 | 41236.62 | 0.00 |
September | 0.00 | 0.00 | 0.865818E+10 | 0.722570E+10 | 67327.75 | 01-SEP-13:20 | 50799.57 | 0.00 |
October | 0.00 | 0.00 | 0.122270E+10 | 0.116864E+10 | 26819.66 | 19-OCT-15:00 | 26819.66 | 0.00 |
November | 0.00 | 0.00 | 0.173136E+09 | 0.123402E+09 | 8577.38 | 01-NOV-15:00 | 5936.05 | 0.00 |
December | 0.00 | 0.00 | 10243201.66 | 10242253.31 | 6966.76 | 06-DEC-07:01 | 6966.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156578E+12 | 0.123046E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6372378.99 | 6371422.50 | 6381.05 | 5936.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.511447E+11 | 0.385276E+11 | 115918.53 | 68262.77 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2512360.55 | 2512360.55 | 3078.26 | 19-JAN-07:01 | 3078.26 | 0.00 |
February | 0.00 | 0.00 | 12208496.99 | 12087000.81 | 3345.77 | 09-FEB-07:01 | 3345.77 | 0.00 |
March | 0.00 | 0.00 | 24849357.14 | 24284820.54 | 5968.45 | 28-MAR-06:02 | 5968.45 | 0.00 |
April | 0.00 | 0.00 | 0.153089E+10 | 0.147497E+10 | 51110.43 | 23-APR-16:02 | 51110.43 | 0.00 |
May | 0.00 | 0.00 | 0.180477E+11 | 0.169352E+11 | 70218.73 | 25-MAY-15:00 | 64463.50 | 0.00 |
June | 0.00 | 0.00 | 0.399991E+11 | 0.316867E+11 | 112938.49 | 30-JUN-04:02 | 67267.75 | 0.00 |
July | 0.00 | 0.00 | 0.530277E+11 | 0.399569E+11 | 126707.88 | 05-JUL-10:40 | 44921.65 | 0.00 |
August | 0.00 | 0.00 | 0.391405E+11 | 0.282116E+11 | 102422.18 | 29-AUG-15:20 | 62213.70 | 0.00 |
September | 0.00 | 0.00 | 0.832953E+10 | 0.686152E+10 | 73530.34 | 01-SEP-14:00 | 60196.70 | 0.00 |
October | 0.00 | 0.00 | 0.114326E+10 | 0.107773E+10 | 25735.67 | 19-OCT-15:00 | 25735.67 | 0.00 |
November | 0.00 | 0.00 | 0.182010E+09 | 0.128139E+09 | 9013.93 | 01-NOV-15:00 | 6145.19 | 0.00 |
December | 0.00 | 0.00 | 3092659.66 | 3072280.35 | 4210.79 | 06-DEC-07:01 | 4210.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161443E+12 | 0.126375E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2512360.55 | 2512360.55 | 3078.26 | 3078.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.530277E+11 | 0.399569E+11 | 126707.88 | 67267.75 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56333.21 | 298304.31 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 32227.19 | 279962.81 | 14-FEB-07:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18056.42 | 241744.14 | 30-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4376.29 | 219091.81 | 06-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 404.55 | 208096.41 | 01-MAY-06:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 60.40 | 13225.29 | 09-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8.38 | 14147.44 | 18-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.72 | 18570.09 | 19-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 369.87 | 63280.24 | 29-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3822.12 | 260061.23 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15633.76 | 274773.83 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 45605.78 | 280715.29 | 26-DEC-08:02 |
Annual Sum or Average | 0.00 | 14706.19 | ||||
Minimum of Months | 0.00 | 0.00 | 8.38 | 13225.29 | ||
Maximum of Months | 0.00 | 0.00 | 56333.21 | 298304.31 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2040.00 | 7525.81 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2098.89 | 7598.41 | 24-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2236.09 | 8653.34 | 10-MAR-17:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2017.13 | 7443.92 | 03-APR-11:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1991.02 | 7153.39 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1923.77 | 6743.20 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1662.51 | 6338.86 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1787.37 | 6089.27 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1670.81 | 6140.53 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1733.99 | 7224.53 | 05-OCT-12:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1864.42 | 6862.17 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1892.43 | 7233.59 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1908.76 | ||||
Minimum of Months | 0.00 | 0.00 | 1662.51 | 6089.27 | ||
Maximum of Months | 0.00 | 0.00 | 2236.09 | 8653.34 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208964E+10 | 0.39 | 2922.96 | 02-JAN-05:01 | 0.85 |
February | 0.152244E+10 | 0.34 | 2922.96 | 21-FEB-07:02 | 0.84 |
March | 0.171591E+10 | 0.34 | 2922.96 | 06-MAR-07:01 | 0.85 |
April | 0.186716E+10 | 0.33 | 3531.82 | 24-APR-06:03 | 0.93 |
May | 0.335177E+10 | 0.41 | 8104.53 | 18-MAY-15:20 | 1.53 |
June | 0.465207E+10 | 0.50 | 10789.01 | 30-JUN-15:10 | 1.83 |
July | 0.607817E+10 | 0.56 | 11890.62 | 05-JUL-10:30 | 1.94 |
August | 0.535981E+10 | 0.54 | 10982.63 | 08-AUG-16:00 | 1.85 |
September | 0.340090E+10 | 0.42 | 9883.18 | 05-SEP-15:50 | 1.75 |
October | 0.201440E+10 | 0.33 | 4759.18 | 20-OCT-15:00 | 1.11 |
November | 0.145147E+10 | 0.30 | 2922.96 | 27-NOV-07:01 | 0.85 |
December | 0.186729E+10 | 0.36 | 2922.96 | 04-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.353710E+11 | 0.40 | |||
Minimum of Months | 0.145147E+10 | 0.30 | 2922.96 | 0.84 | |
Maximum of Months | 0.607817E+10 | 0.56 | 11890.62 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.212288E+10 | 0.40 | 3157.56 | 02-JAN-05:01 | 0.91 |
February | 0.162102E+10 | 0.35 | 3157.56 | 01-FEB-06:02 | 0.91 |
March | 0.176954E+10 | 0.34 | 3157.56 | 01-MAR-07:01 | 0.91 |
April | 0.191474E+10 | 0.34 | 3873.01 | 13-APR-15:20 | 1.02 |
May | 0.342385E+10 | 0.43 | 9008.40 | 18-MAY-14:20 | 1.68 |
June | 0.470100E+10 | 0.52 | 10594.68 | 30-JUN-14:30 | 1.87 |
July | 0.551896E+10 | 0.54 | 11303.44 | 05-JUL-10:20 | 1.94 |
August | 0.439541E+10 | 0.50 | 9892.87 | 08-AUG-15:10 | 1.79 |
September | 0.261655E+10 | 0.38 | 9234.32 | 01-SEP-15:50 | 1.71 |
October | 0.169181E+10 | 0.31 | 3925.08 | 20-OCT-14:40 | 1.02 |
November | 0.149782E+10 | 0.31 | 3157.56 | 06-NOV-06:01 | 0.91 |
December | 0.200555E+10 | 0.39 | 3157.56 | 01-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.332791E+11 | 0.40 | |||
Minimum of Months | 0.149782E+10 | 0.31 | 3157.56 | 0.91 | |
Maximum of Months | 0.551896E+10 | 0.54 | 11303.44 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264080E+10 | 0.47 | 3013.70 | 01-JAN-00:42 | 0.83 |
February | 0.206002E+10 | 0.42 | 3013.70 | 01-FEB-05:01 | 0.83 |
March | 0.197066E+10 | 0.37 | 3013.70 | 01-MAR-06:01 | 0.83 |
April | 0.183737E+10 | 0.32 | 3640.61 | 13-APR-15:20 | 0.92 |
May | 0.314190E+10 | 0.40 | 9033.53 | 18-MAY-15:00 | 1.57 |
June | 0.435548E+10 | 0.47 | 11389.66 | 30-JUN-14:30 | 1.82 |
July | 0.497093E+10 | 0.49 | 12639.31 | 05-JUL-10:40 | 1.94 |
August | 0.387076E+10 | 0.45 | 9897.65 | 08-AUG-15:00 | 1.66 |
September | 0.227395E+10 | 0.35 | 9303.51 | 01-SEP-15:50 | 1.60 |
October | 0.166100E+10 | 0.31 | 3163.39 | 20-OCT-14:30 | 0.85 |
November | 0.179787E+10 | 0.35 | 3013.70 | 03-NOV-06:01 | 0.83 |
December | 0.243577E+10 | 0.44 | 3013.70 | 01-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.330165E+11 | 0.40 | |||
Minimum of Months | 0.166100E+10 | 0.31 | 3013.70 | 0.83 | |
Maximum of Months | 0.497093E+10 | 0.49 | 12639.31 | 1.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.113227E+10 | 0.101904E+10 | 1226.96 | 09-JAN-07:17 | 1104.26 | 1104.26 | 42.06 | 3.93 |
February | 0.631761E+09 | 0.568584E+09 | 1180.97 | 14-FEB-07:20 | 1062.87 | 1062.87 | 42.49 | 3.80 |
March | 0.420772E+09 | 0.378695E+09 | 1002.67 | 15-MAR-07:00 | 902.40 | 902.40 | 43.13 | 2.81 |
April | 97155416.16 | 87439874.55 | 961.12 | 05-APR-06:01 | 865.00 | 865.00 | 41.98 | 2.35 |
May | 13032707.82 | 11729437.04 | 907.91 | 01-MAY-06:01 | 817.12 | 817.12 | 33.54 | 1.88 |
June | 2039343.26 | 1835408.93 | 145.38 | 02-JUN-06:40 | 130.84 | 130.84 | 46.14 | 0.16 |
July | 238169.59 | 214352.63 | 144.95 | 18-JUL-06:06 | 130.45 | 130.45 | 38.25 | 0.16 |
August | 927232.27 | 834509.05 | 242.37 | 19-AUG-06:03 | 218.14 | 218.14 | 43.61 | 0.27 |
September | 12639389.67 | 11375450.70 | 603.78 | 29-SEP-06:03 | 543.40 | 543.40 | 41.90 | 0.84 |
October | 84655042.33 | 76189538.09 | 959.98 | 30-OCT-06:01 | 863.98 | 863.98 | 44.45 | 2.33 |
November | 0.335158E+09 | 0.301642E+09 | 977.63 | 27-NOV-07:02 | 879.86 | 879.86 | 45.07 | 2.53 |
December | 0.982006E+09 | 0.883805E+09 | 1170.86 | 20-DEC-07:13 | 1053.77 | 1053.77 | 42.41 | 3.76 |
Annual Sum or Average | 0.371265E+10 | 0.334139E+10 | ||||||
Minimum of Months | 238169.59 | 214352.63 | 144.95 | 130.45 | 130.45 | 33.54 | 0.16 | |
Maximum of Months | 0.113227E+10 | 0.101904E+10 | 1226.96 | 1104.26 | 1104.26 | 46.14 | 3.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.78 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 56.50 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.52 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 56.30 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:02 | 2.06 | 2.06 | 56.95 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.66 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 56.85 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.07 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.10 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.98 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 56.71 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 56.94 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.30 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.98 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 42.56 | 42.56 | 56333.21 | 298304.31 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 42.91 | 60.00 | 32227.19 | 279962.81 | 14-FEB-07:12 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 29.81 | 29.81 | 18056.42 | 241744.14 | 30-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.92 | 29.92 | 4376.29 | 219091.81 | 06-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.32 | 21.32 | 404.55 | 208096.41 | 01-MAY-06:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44.72 | 44.72 | 60.40 | 13225.29 | 09-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 39.50 | 39.50 | 8.38 | 14147.44 | 18-JUL-06:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 35.20 | 35.20 | 33.72 | 18570.09 | 19-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 38.48 | 38.48 | 369.87 | 63280.24 | 29-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33.01 | 33.01 | 3822.12 | 260061.23 | 16-OCT-05:11 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.91 | 28.91 | 15633.76 | 274773.83 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 31.16 | 31.16 | 45605.78 | 280715.29 | 26-DEC-08:02 |
Annual Sum or Average | 0.00 | 14706.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.32 | 21.32 | 8.38 | 13225.29 | ||
Maximum of Months | 0.00 | 0.00 | 44.72 | 60.00 | 56333.21 | 298304.31 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.78 | 57.78 | 2040.00 | 7525.81 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.11 | 57.11 | 2098.89 | 7598.41 | 24-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.08 | 57.08 | 2236.09 | 8653.34 | 10-MAR-17:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.13 | 57.13 | 2017.13 | 7443.92 | 03-APR-11:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.81 | 57.81 | 1991.02 | 7153.39 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.41 | 57.41 | 1923.77 | 6743.20 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.56 | 57.56 | 1662.51 | 6338.86 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.67 | 57.67 | 1787.37 | 6089.27 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.70 | 57.70 | 1670.81 | 6140.53 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.69 | 56.69 | 1733.99 | 7224.53 | 05-OCT-12:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.52 | 57.52 | 1864.42 | 6862.17 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.37 | 57.37 | 1892.43 | 7233.59 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1908.76 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.69 | 56.69 | 1662.51 | 6089.27 | ||
Maximum of Months | 0.00 | 0.00 | 57.81 | 57.81 | 2236.09 | 8653.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.454016E+11 | 0.00 | 0.00 | 0.209106E+10 | 0.00 | 0.00 |
February | 0.235644E+11 | 0.00 | 0.00 | 0.152635E+10 | 0.00 | 0.00 |
March | 0.173859E+11 | 0.00 | 0.00 | 0.172493E+10 | 0.00 | 0.00 |
April | 0.510747E+10 | 0.00 | 0.00 | 0.219354E+10 | 0.00 | 0.00 |
May | 0.853555E+09 | 0.00 | 0.00 | 0.715806E+10 | 0.00 | 0.00 |
June | 0.162771E+09 | 0.00 | 0.00 | 0.135588E+11 | 0.00 | 0.00 |
July | 25198874.01 | 0.00 | 0.00 | 0.182531E+11 | 0.00 | 0.00 |
August | 75834308.70 | 0.00 | 0.00 | 0.150206E+11 | 0.00 | 0.00 |
September | 0.704944E+09 | 0.00 | 0.00 | 0.561447E+10 | 0.00 | 0.00 |
October | 0.297010E+10 | 0.00 | 0.00 | 0.232539E+10 | 0.00 | 0.00 |
November | 0.105414E+11 | 0.00 | 0.00 | 0.150331E+10 | 0.00 | 0.00 |
December | 0.342612E+11 | 0.00 | 0.00 | 0.187035E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.141054E+12 | 0.00 | 0.00 | 0.728400E+11 | 0.00 | 0.00 |
Minimum of Months | 25198874.01 | 0.00 | 0.00 | 0.150331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.454016E+11 | 0.00 | 0.00 | 0.182531E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.426546E+11 | 0.00 | 0.00 | 0.212457E+10 | 0.00 | 0.00 |
February | 0.199464E+11 | 0.00 | 0.00 | 0.162489E+10 | 0.00 | 0.00 |
March | 0.104698E+11 | 0.00 | 0.00 | 0.177559E+10 | 0.00 | 0.00 |
April | 0.164603E+10 | 0.00 | 0.00 | 0.227744E+10 | 0.00 | 0.00 |
May | 30228860.67 | 0.00 | 0.00 | 0.733243E+10 | 0.00 | 0.00 |
June | 571429.34 | 0.00 | 0.00 | 0.134219E+11 | 0.00 | 0.00 |
July | 949303.12 | 0.00 | 0.00 | 0.168962E+11 | 0.00 | 0.00 |
August | 545401.44 | 0.00 | 0.00 | 0.129598E+11 | 0.00 | 0.00 |
September | 13744436.77 | 0.00 | 0.00 | 0.462663E+10 | 0.00 | 0.00 |
October | 0.178226E+10 | 0.00 | 0.00 | 0.198799E+10 | 0.00 | 0.00 |
November | 0.999208E+10 | 0.00 | 0.00 | 0.154251E+10 | 0.00 | 0.00 |
December | 0.340779E+11 | 0.00 | 0.00 | 0.200823E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120615E+12 | 0.00 | 0.00 | 0.685781E+11 | 0.00 | 0.00 |
Minimum of Months | 545401.44 | 0.00 | 0.00 | 0.154251E+10 | 0.00 | 0.00 |
Maximum of Months | 0.426546E+11 | 0.00 | 0.00 | 0.168962E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.640261E+11 | 0.00 | 0.00 | 0.264147E+10 | 0.00 | 0.00 |
February | 0.351298E+11 | 0.00 | 0.00 | 0.206334E+10 | 0.00 | 0.00 |
March | 0.209440E+11 | 0.00 | 0.00 | 0.197737E+10 | 0.00 | 0.00 |
April | 0.469996E+10 | 0.00 | 0.00 | 0.221670E+10 | 0.00 | 0.00 |
May | 0.188809E+09 | 0.00 | 0.00 | 0.728342E+10 | 0.00 | 0.00 |
June | 571487.25 | 0.00 | 0.00 | 0.134793E+11 | 0.00 | 0.00 |
July | 945311.85 | 0.00 | 0.00 | 0.168255E+11 | 0.00 | 0.00 |
August | 11505126.60 | 0.00 | 0.00 | 0.126687E+11 | 0.00 | 0.00 |
September | 0.258140E+09 | 0.00 | 0.00 | 0.422718E+10 | 0.00 | 0.00 |
October | 0.557790E+10 | 0.00 | 0.00 | 0.194199E+10 | 0.00 | 0.00 |
November | 0.203381E+11 | 0.00 | 0.00 | 0.184503E+10 | 0.00 | 0.00 |
December | 0.548299E+11 | 0.00 | 0.00 | 0.243660E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.206006E+12 | 0.00 | 0.00 | 0.696067E+11 | 0.00 | 0.00 |
Minimum of Months | 571487.25 | 0.00 | 0.00 | 0.184503E+10 | 0.00 | 0.00 |
Maximum of Months | 0.640261E+11 | 0.00 | 0.00 | 0.168255E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208964E+10 | 5326878.93 | 0.454016E+11 | 0.252027E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152244E+10 | 14507630.43 | 0.235644E+11 | 0.210612E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171591E+10 | 33375741.29 | 0.173859E+11 | 0.185466E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186716E+10 | 0.130013E+10 | 0.510747E+10 | 0.403993E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335177E+10 | 0.165921E+11 | 0.853555E+09 | 0.287531E+09 | 67292073.81 | 0.00 | 0.00 | 0.00 |
June | 0.465207E+10 | 0.391819E+11 | 0.162771E+09 | 16960598.13 | 0.152950E+10 | 0.00 | 0.00 | 0.00 |
July | 0.607817E+10 | 0.548014E+11 | 25198874.01 | 34015597.58 | 0.176356E+10 | 0.00 | 0.00 | 0.00 |
August | 0.535981E+10 | 0.434762E+11 | 75834308.70 | 4451209.15 | 0.882506E+09 | 0.00 | 0.00 | 0.00 |
September | 0.340090E+10 | 0.959320E+10 | 0.704944E+09 | 9318201.89 | 12122305.95 | 0.00 | 0.00 | 0.00 |
October | 0.201440E+10 | 0.129406E+10 | 0.297010E+10 | 0.242007E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145147E+10 | 0.200996E+09 | 0.105414E+11 | 0.114367E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186729E+10 | 11378264.60 | 0.342612E+11 | 0.254562E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353710E+11 | 0.166505E+12 | 0.141054E+12 | 0.108516E+12 | 0.425498E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145147E+10 | 5326878.93 | 25198874.01 | 4451209.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.607817E+10 | 0.548014E+11 | 0.454016E+11 | 0.254562E+11 | 0.176356E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.212288E+10 | 6372378.99 | 0.426546E+11 | 0.252046E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162102E+10 | 14581552.00 | 0.199464E+11 | 0.216206E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176954E+10 | 22798940.59 | 0.104698E+11 | 0.196986E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191474E+10 | 0.146513E+10 | 0.164603E+10 | 0.504789E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342385E+10 | 0.170955E+11 | 30228860.67 | 0.379357E+09 | 76055618.54 | 0.00 | 0.00 | 0.00 |
June | 0.470100E+10 | 0.384407E+11 | 571429.34 | 18687571.03 | 0.165062E+10 | 0.00 | 0.00 | 0.00 |
July | 0.551896E+10 | 0.511447E+11 | 949303.12 | 41082943.76 | 0.198663E+10 | 0.00 | 0.00 | 0.00 |
August | 0.439541E+10 | 0.383236E+11 | 545401.44 | 5820473.89 | 0.941951E+09 | 0.00 | 0.00 | 0.00 |
September | 0.261655E+10 | 0.865818E+10 | 13744436.77 | 94496834.53 | 11943836.81 | 0.00 | 0.00 | 0.00 |
October | 0.169181E+10 | 0.122270E+10 | 0.178226E+10 | 0.400862E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149782E+10 | 0.173136E+09 | 0.999208E+10 | 0.129566E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200555E+10 | 10243201.66 | 0.340779E+11 | 0.257702E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332791E+11 | 0.156578E+12 | 0.120615E+12 | 0.114847E+12 | 0.466721E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149782E+10 | 6372378.99 | 545401.44 | 5820473.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.551896E+10 | 0.511447E+11 | 0.426546E+11 | 0.257702E+11 | 0.198663E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.264080E+10 | 2512360.55 | 0.640261E+11 | 0.248859E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206002E+10 | 12208496.99 | 0.351298E+11 | 0.212040E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197066E+10 | 24849357.14 | 0.209440E+11 | 0.198910E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183737E+10 | 0.153089E+10 | 0.469996E+10 | 0.560003E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314190E+10 | 0.180477E+11 | 0.188809E+09 | 0.484706E+09 | 53673198.64 | 0.00 | 0.00 | 0.00 |
June | 0.435548E+10 | 0.399991E+11 | 571487.25 | 14077833.63 | 0.149078E+10 | 0.00 | 0.00 | 0.00 |
July | 0.497093E+10 | 0.530277E+11 | 945311.85 | 29383339.94 | 0.170616E+10 | 0.00 | 0.00 | 0.00 |
August | 0.387076E+10 | 0.391405E+11 | 11505126.60 | 13997601.66 | 0.710861E+09 | 0.00 | 0.00 | 0.00 |
September | 0.227395E+10 | 0.832953E+10 | 0.258140E+09 | 0.278815E+09 | 2156868.93 | 0.00 | 0.00 | 0.00 |
October | 0.166100E+10 | 0.114326E+10 | 0.557790E+10 | 0.468846E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179787E+10 | 0.182010E+09 | 0.203381E+11 | 0.134347E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243577E+10 | 3092659.66 | 0.548299E+11 | 0.256117E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330165E+11 | 0.161443E+12 | 0.206006E+12 | 0.116137E+12 | 0.396363E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166100E+10 | 2512360.55 | 571487.25 | 13997601.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.497093E+10 | 0.530277E+11 | 0.640261E+11 | 0.256117E+11 | 0.170616E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208964E+10 | 0.454016E+11 | 0.00 | 0.00 | 1416734.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152244E+10 | 0.235644E+11 | 0.00 | 0.00 | 3919442.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171591E+10 | 0.173859E+11 | 0.00 | 0.00 | 9018369.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186716E+10 | 0.510747E+10 | 0.00 | 0.00 | 0.326377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335177E+10 | 0.853555E+09 | 0.00 | 0.00 | 0.380629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465207E+10 | 0.162771E+09 | 0.00 | 0.00 | 0.890674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.607817E+10 | 25198874.01 | 0.00 | 0.00 | 0.121749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.535981E+10 | 75834308.70 | 0.00 | 0.00 | 0.966079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340090E+10 | 0.704944E+09 | 0.00 | 0.00 | 0.221356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201440E+10 | 0.297010E+10 | 0.00 | 0.00 | 0.310996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145147E+10 | 0.105414E+11 | 0.00 | 0.00 | 51843351.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186729E+10 | 0.342612E+11 | 0.00 | 0.00 | 3064154.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353710E+11 | 0.141054E+12 | 0.00 | 0.00 | 0.374689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145147E+10 | 25198874.01 | 0.00 | 0.00 | 1416734.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.607817E+10 | 0.454016E+11 | 0.00 | 0.00 | 0.121749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.212288E+10 | 0.426546E+11 | 0.00 | 0.00 | 1687241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162102E+10 | 0.199464E+11 | 0.00 | 0.00 | 3869483.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176954E+10 | 0.104698E+11 | 0.00 | 0.00 | 6044456.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191474E+10 | 0.164603E+10 | 0.00 | 0.00 | 0.362697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.342385E+10 | 30228860.67 | 0.00 | 0.00 | 0.390858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.470100E+10 | 571429.34 | 0.00 | 0.00 | 0.872086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.551896E+10 | 949303.12 | 0.00 | 0.00 | 0.113773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.439541E+10 | 545401.44 | 0.00 | 0.00 | 0.856434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.261655E+10 | 13744436.77 | 0.00 | 0.00 | 0.201008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169181E+10 | 0.178226E+10 | 0.00 | 0.00 | 0.296174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149782E+10 | 0.999208E+10 | 0.00 | 0.00 | 44690896.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200555E+10 | 0.340779E+11 | 0.00 | 0.00 | 2685912.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332791E+11 | 0.120615E+12 | 0.00 | 0.00 | 0.352990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149782E+10 | 545401.44 | 0.00 | 0.00 | 1687241.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.551896E+10 | 0.426546E+11 | 0.00 | 0.00 | 0.113773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.264080E+10 | 0.640261E+11 | 0.00 | 0.00 | 678402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206002E+10 | 0.351298E+11 | 0.00 | 0.00 | 3311397.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197066E+10 | 0.209440E+11 | 0.00 | 0.00 | 6710365.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183737E+10 | 0.469996E+10 | 0.00 | 0.00 | 0.379328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314190E+10 | 0.188809E+09 | 0.00 | 0.00 | 0.414152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.435548E+10 | 571487.25 | 0.00 | 0.00 | 0.912383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.497093E+10 | 945311.85 | 0.00 | 0.00 | 0.118546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387076E+10 | 11505126.60 | 0.00 | 0.00 | 0.879797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227395E+10 | 0.258140E+09 | 0.00 | 0.00 | 0.195323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166100E+10 | 0.557790E+10 | 0.00 | 0.00 | 0.280986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179787E+10 | 0.203381E+11 | 0.00 | 0.00 | 47160419.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243577E+10 | 0.548299E+11 | 0.00 | 0.00 | 830326.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330165E+11 | 0.206006E+12 | 0.00 | 0.00 | 0.365902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166100E+10 | 571487.25 | 0.00 | 0.00 | 678402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.497093E+10 | 0.640261E+11 | 0.00 | 0.00 | 0.118546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121199E+11 | 0.00 | 0.00 | 128278.41 | 0.00 | 0.389677E+09 | 0.131824E+09 | 0.00 | 0.26 |
February | 0.858254E+10 | 0.00 | 0.00 | 1231645.26 | 0.00 | 1619238.06 | 0.116201E+10 | 0.00 | 0.27 |
March | 0.645816E+10 | 0.00 | 0.00 | 9476583.55 | 0.00 | 1065824.09 | 0.537295E+10 | 0.00 | 0.31 |
April | 0.193730E+10 | 0.00 | 0.00 | 27066592.15 | 57863564.88 | 0.00 | 0.138087E+11 | 0.00 | 0.47 |
May | 0.111453E+10 | 38323302.10 | 0.00 | 40498393.17 | 0.00 | 0.00 | 0.170574E+11 | 0.00 | 0.87 |
June | 0.448267E+09 | 0.180862E+10 | 0.00 | 34898463.15 | 0.231567E+09 | 0.00 | 0.117611E+11 | 0.00 | 1.10 |
July | 0.542180E+09 | 0.296673E+10 | 0.00 | 28487452.39 | 0.421961E+09 | 0.00 | 0.801396E+10 | 0.00 | 1.02 |
August | 0.717856E+09 | 0.159688E+10 | 0.00 | 38889431.10 | 51506815.97 | 0.00 | 0.124578E+11 | 0.00 | 1.20 |
September | 0.116697E+10 | 11780054.80 | 0.00 | 42147670.37 | 0.00 | 0.00 | 0.207941E+11 | 0.00 | 0.94 |
October | 0.193715E+10 | 0.00 | 0.00 | 29853256.70 | 0.00 | 0.00 | 0.154713E+11 | 0.00 | 0.48 |
November | 0.456258E+10 | 0.00 | 0.00 | 10795333.29 | 0.00 | 663443.38 | 0.608651E+10 | 0.00 | 0.31 |
December | 0.102222E+11 | 0.00 | 0.00 | 536992.64 | 0.00 | 0.102045E+09 | 0.472692E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.498096E+11 | 0.642234E+10 | 0.00 | 0.264010E+09 | 0.762899E+09 | 0.495071E+09 | 0.112590E+12 | 0.00 | 0.63 |
Minimum of Months | 0.448267E+09 | 0.00 | 0.00 | 128278.41 | 0.00 | 0.00 | 0.131824E+09 | 0.00 | 0.26 |
Maximum of Months | 0.121199E+11 | 0.296673E+10 | 0.00 | 42147670.37 | 0.421961E+09 | 0.389677E+09 | 0.207941E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.929447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324234E+10 | 0.00 | 0.00 | 0.26 |
February | 0.825451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862277E+09 | 0.00 | 0.00 | 0.26 |
March | 0.960895E+10 | 0.00 | 0.00 | 213733.46 | 0.00 | 0.179214E+09 | 0.395945E+09 | 0.00 | 0.29 |
April | 0.681779E+10 | 0.00 | 0.00 | 6673532.19 | 38998054.01 | 7818334.40 | 0.466394E+10 | 0.00 | 0.36 |
May | 0.314963E+10 | 33581266.73 | 0.00 | 21569440.77 | 0.00 | 0.00 | 0.960638E+10 | 0.00 | 0.62 |
June | 0.117432E+10 | 0.132845E+10 | 0.00 | 21140415.41 | 0.245592E+09 | 0.00 | 0.733298E+10 | 0.00 | 0.79 |
July | 0.911491E+09 | 0.220684E+10 | 0.00 | 17678756.28 | 0.418376E+09 | 0.00 | 0.502314E+10 | 0.00 | 0.73 |
August | 0.143614E+10 | 0.115128E+10 | 0.00 | 22055296.64 | 45538960.71 | 0.00 | 0.734552E+10 | 0.00 | 0.83 |
September | 0.356210E+10 | 22409246.33 | 0.00 | 18305422.81 | 2181235.79 | 0.00 | 0.101193E+11 | 0.00 | 0.61 |
October | 0.751429E+10 | 0.00 | 0.00 | 5109786.81 | 0.00 | 6051800.25 | 0.366607E+10 | 0.00 | 0.34 |
November | 0.790288E+10 | 0.00 | 0.00 | 29489.75 | 0.00 | 0.441382E+09 | 84108482.60 | 0.00 | 0.28 |
December | 0.790670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244373E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.675333E+11 | 0.474256E+10 | 0.00 | 0.112776E+09 | 0.750686E+09 | 0.718282E+10 | 0.482374E+11 | 0.00 | 0.47 |
Minimum of Months | 0.911491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.960895E+10 | 0.220684E+10 | 0.00 | 22055296.64 | 0.418376E+09 | 0.324234E+10 | 0.101193E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716110E+10 | 0.00 | 0.00 | 0.24 |
February | 0.439997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367647E+10 | 0.00 | 0.00 | 0.25 |
March | 0.772658E+10 | 0.00 | 0.00 | 36205.17 | 0.00 | 0.118589E+10 | 0.151319E+09 | 0.00 | 0.28 |
April | 0.723115E+10 | 0.00 | 0.00 | 3951650.85 | 54724791.01 | 0.120970E+09 | 0.318958E+10 | 0.00 | 0.35 |
May | 0.405977E+10 | 34113720.87 | 0.00 | 18235766.85 | 0.00 | 3411585.70 | 0.783279E+10 | 0.00 | 0.61 |
June | 0.171722E+10 | 0.132656E+10 | 0.00 | 18168632.63 | 0.320384E+09 | 0.00 | 0.657508E+10 | 0.00 | 0.79 |
July | 0.129762E+10 | 0.223172E+10 | 0.00 | 14677684.84 | 0.463069E+09 | 0.00 | 0.426203E+10 | 0.00 | 0.74 |
August | 0.208892E+10 | 0.126164E+10 | 0.00 | 16462790.75 | 38574382.80 | 0.00 | 0.567196E+10 | 0.00 | 0.81 |
September | 0.524141E+10 | 13923359.17 | 0.00 | 10710531.25 | 43440.63 | 0.00 | 0.666862E+10 | 0.00 | 0.56 |
October | 0.833192E+10 | 0.00 | 0.00 | 1221863.27 | 0.00 | 0.150105E+09 | 0.124578E+10 | 0.00 | 0.32 |
November | 0.620754E+10 | 0.00 | 0.00 | 0.00 | 311683.40 | 0.123163E+10 | 0.00 | 0.00 | 0.27 |
December | 0.307414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570822E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.552159E+11 | 0.486796E+10 | 0.00 | 83465125.61 | 0.877108E+09 | 0.192378E+11 | 0.355972E+11 | 0.00 | 0.46 |
Minimum of Months | 0.129762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.833192E+10 | 0.223172E+10 | 0.00 | 18235766.85 | 0.463069E+09 | 0.716110E+10 | 0.783279E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13342415.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359999E+10 | 0.00 | 0.00 | 0.34 |
February | 0.151623E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203456E+10 | 0.00 | 0.00 | 0.30 |
March | 0.667292E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135934E+10 | 0.00 | 0.00 | 0.30 |
April | 0.151569E+10 | 0.00 | 0.00 | 391512.97 | 11548453.45 | 0.362586E+09 | 0.323016E+09 | 0.00 | 0.35 |
May | 0.102996E+10 | 11205353.32 | 0.00 | 4697040.43 | 0.00 | 11838189.26 | 0.169888E+10 | 0.00 | 0.72 |
June | 0.360014E+09 | 0.449930E+09 | 0.00 | 5275968.40 | 61710920.03 | 0.00 | 0.179371E+10 | 0.00 | 1.05 |
July | 0.271903E+09 | 0.707845E+09 | 0.00 | 4234994.62 | 95034558.66 | 0.00 | 0.118602E+10 | 0.00 | 0.99 |
August | 0.552464E+09 | 0.369153E+09 | 0.00 | 3603921.71 | 8539437.07 | 213276.97 | 0.117996E+10 | 0.00 | 0.94 |
September | 0.146887E+10 | 3793897.45 | 0.00 | 1771164.66 | 9167.18 | 11567835.08 | 0.100179E+10 | 0.00 | 0.56 |
October | 0.154742E+10 | 0.00 | 0.00 | 61340.72 | 0.00 | 0.443641E+09 | 63112186.61 | 0.00 | 0.32 |
November | 0.485941E+09 | 0.00 | 4952.04 | 0.00 | 49261.03 | 0.115912E+10 | 0.00 | 23818.49 | 0.28 |
December | 19109137.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266123E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.808363E+10 | 0.154193E+10 | 4952.04 | 20035943.50 | 0.176892E+09 | 0.116441E+11 | 0.724649E+10 | 23818.49 | 0.54 |
Minimum of Months | 13342415.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.154742E+10 | 0.707845E+09 | 4952.04 | 5275968.40 | 95034558.66 | 0.359999E+10 | 0.179371E+10 | 23818.49 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25097045.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284826E+10 | 0.00 | 0.00 | 0.46 |
February | 0.363255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163751E+10 | 0.00 | 0.00 | 0.45 |
March | 0.103270E+10 | 0.00 | 0.00 | 259812.37 | 0.00 | 0.102022E+10 | 0.105322E+09 | 0.00 | 0.50 |
April | 0.135258E+10 | 0.00 | 0.00 | 2648766.45 | 12846742.99 | 0.223049E+09 | 0.134953E+10 | 0.00 | 0.74 |
May | 0.991883E+09 | 8635490.20 | 0.00 | 5920294.03 | 0.00 | 3314168.52 | 0.226775E+10 | 0.00 | 1.31 |
June | 0.340370E+09 | 0.424433E+09 | 0.00 | 6955887.65 | 44298746.61 | 0.00 | 0.247539E+10 | 0.00 | 1.87 |
July | 0.246420E+09 | 0.713748E+09 | 0.00 | 5918736.82 | 84286189.47 | 0.00 | 0.166542E+10 | 0.00 | 1.85 |
August | 0.672682E+09 | 0.320556E+09 | 0.00 | 5208476.11 | 19687243.51 | 0.00 | 0.138448E+10 | 0.00 | 1.66 |
September | 0.158596E+10 | 3303748.75 | 0.00 | 2875464.82 | 10197.77 | 14194626.00 | 0.152314E+10 | 0.00 | 1.10 |
October | 0.171444E+10 | 0.00 | 0.00 | 362534.32 | 0.00 | 0.403814E+09 | 0.201623E+09 | 0.00 | 0.57 |
November | 0.761173E+09 | 0.00 | 9385.60 | 0.00 | 51234.96 | 0.100248E+10 | 0.00 | 21879.15 | 0.48 |
December | 54251360.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220062E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.914082E+10 | 0.147068E+10 | 9385.60 | 30149972.56 | 0.161180E+09 | 0.935346E+10 | 0.109727E+11 | 21879.15 | 0.96 |
Minimum of Months | 25097045.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.171444E+10 | 0.713748E+09 | 9385.60 | 6955887.65 | 84286189.47 | 0.284826E+10 | 0.247539E+10 | 21879.15 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.780118E+09 | 0.00 | 0.00 | 1323767.97 | 0.00 | 0.266455E+10 | 0.381534E+09 | 0.00 | 0.39 |
February | 0.715979E+09 | 0.00 | 0.00 | 2425683.27 | 0.00 | 0.150395E+10 | 0.841361E+09 | 0.00 | 0.43 |
March | 0.994959E+09 | 0.00 | 0.00 | 3404663.37 | 0.00 | 0.105962E+10 | 0.146146E+10 | 0.00 | 0.48 |
April | 0.138411E+10 | 24492188.14 | 0.00 | 6153681.93 | 3334435.22 | 0.309006E+09 | 0.330403E+10 | 0.00 | 0.83 |
May | 0.124398E+10 | 13992276.65 | 0.00 | 8615284.79 | 0.00 | 17732143.91 | 0.322229E+10 | 0.00 | 1.17 |
June | 0.723578E+09 | 0.537679E+09 | 0.00 | 6672674.71 | 79499971.33 | 0.00 | 0.223307E+10 | 0.00 | 1.42 |
July | 0.462352E+09 | 0.918921E+09 | 0.00 | 5820094.97 | 0.138624E+09 | 0.00 | 0.161083E+10 | 0.00 | 1.38 |
August | 0.829222E+09 | 0.594228E+09 | 0.00 | 7562772.31 | 10361250.02 | 304529.59 | 0.193514E+10 | 0.00 | 1.56 |
September | 0.164460E+10 | 12213191.76 | 0.00 | 7815383.48 | 13089.45 | 18900928.23 | 0.355353E+10 | 0.00 | 1.27 |
October | 0.179819E+10 | 0.00 | 0.00 | 4088599.49 | 0.00 | 0.420979E+09 | 0.184781E+10 | 0.00 | 0.70 |
November | 0.930201E+09 | 0.00 | 10965.84 | 1916331.17 | 65763.16 | 0.100455E+10 | 0.738099E+09 | 29164.37 | 0.44 |
December | 0.423720E+09 | 0.00 | 0.00 | 379042.57 | 0.00 | 0.240926E+10 | 0.120811E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.119310E+11 | 0.210153E+10 | 10965.84 | 56177980.03 | 0.231899E+09 | 0.940885E+10 | 0.212500E+11 | 29164.37 | 0.87 |
Minimum of Months | 0.423720E+09 | 0.00 | 0.00 | 379042.57 | 0.00 | 0.00 | 0.120811E+09 | 0.00 | 0.37 |
Maximum of Months | 0.179819E+10 | 0.918921E+09 | 10965.84 | 8615284.79 | 0.138624E+09 | 0.266455E+10 | 0.355353E+10 | 29164.37 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307192E+10 | 0.00 | 0.00 | 0.50 |
February | 0.412388E+09 | 0.00 | 0.00 | 79632.96 | 0.00 | 0.177009E+10 | 62915503.63 | 0.00 | 0.50 |
March | 0.915460E+09 | 0.00 | 0.00 | 708632.61 | 0.00 | 0.119573E+10 | 0.353347E+09 | 0.00 | 0.56 |
April | 0.152680E+10 | 7516477.59 | 0.00 | 2777225.63 | 10160877.86 | 0.340818E+09 | 0.147668E+10 | 0.00 | 0.86 |
May | 0.122273E+10 | 9700386.66 | 0.00 | 6730637.16 | 0.00 | 16520804.91 | 0.218820E+10 | 0.00 | 1.39 |
June | 0.626174E+09 | 0.394399E+09 | 0.00 | 5259786.15 | 67336137.57 | 0.00 | 0.161637E+10 | 0.00 | 1.73 |
July | 0.386480E+09 | 0.686377E+09 | 0.00 | 4461897.07 | 0.104212E+09 | 0.00 | 0.111814E+10 | 0.00 | 1.61 |
August | 0.867962E+09 | 0.372021E+09 | 0.00 | 4062742.75 | 13692213.12 | 1557335.23 | 0.108738E+10 | 0.00 | 1.64 |
September | 0.191487E+10 | 4236523.74 | 0.00 | 2868126.90 | 0.00 | 23683312.60 | 0.131611E+10 | 0.00 | 1.17 |
October | 0.175072E+10 | 0.00 | 0.00 | 711788.53 | 0.00 | 0.475080E+09 | 0.382827E+09 | 0.00 | 0.66 |
November | 0.738795E+09 | 0.00 | 11587.20 | 4367.71 | 55600.82 | 0.115756E+10 | 13899520.26 | 22341.71 | 0.52 |
December | 83616445.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240998E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.106125E+11 | 0.147425E+10 | 11587.20 | 27664837.48 | 0.195457E+09 | 0.104629E+11 | 0.961588E+10 | 22341.71 | 0.97 |
Minimum of Months | 83616445.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.191487E+10 | 0.686377E+09 | 11587.20 | 6730637.16 | 0.104212E+09 | 0.307192E+10 | 0.218820E+10 | 22341.71 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31820980.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373961E+10 | 0.00 | 0.00 | 0.34 |
February | 52518382.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239058E+10 | 0.00 | 0.00 | 0.30 |
March | 0.430136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202732E+10 | 0.00 | 0.00 | 0.31 |
April | 0.165290E+10 | 0.00 | 0.00 | 0.00 | 12177891.68 | 0.719749E+09 | 0.00 | 0.00 | 0.33 |
May | 0.158783E+10 | 6226239.52 | 0.00 | 1794462.40 | 0.00 | 22377898.79 | 0.610985E+09 | 0.00 | 0.51 |
June | 0.541674E+09 | 0.295039E+09 | 0.00 | 3254224.01 | 51873086.34 | 0.00 | 0.103702E+10 | 0.00 | 0.74 |
July | 0.301115E+09 | 0.527768E+09 | 0.00 | 3515260.53 | 93727261.56 | 0.00 | 0.982427E+09 | 0.00 | 0.78 |
August | 0.501969E+09 | 0.277129E+09 | 0.00 | 3677359.60 | 11671405.87 | 0.00 | 0.124089E+10 | 0.00 | 0.84 |
September | 0.145547E+10 | 2122471.04 | 0.00 | 2052204.37 | 0.00 | 0.00 | 0.121613E+10 | 0.00 | 0.57 |
October | 0.229957E+10 | 0.00 | 0.00 | 48137.47 | 0.00 | 0.132991E+09 | 70947009.60 | 0.00 | 0.33 |
November | 0.917690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113693E+10 | 0.00 | 0.00 | 0.28 |
December | 32275513.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281404E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.980496E+10 | 0.110828E+10 | 0.00 | 14341648.38 | 0.169450E+09 | 0.129836E+11 | 0.515839E+10 | 0.00 | 0.47 |
Minimum of Months | 31820980.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.229957E+10 | 0.527768E+09 | 0.00 | 3677359.60 | 93727261.56 | 0.373961E+10 | 0.124089E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39410835.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285084E+10 | 0.00 | 0.00 | 0.42 |
February | 0.263986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175106E+10 | 0.00 | 0.00 | 0.40 |
March | 0.822332E+09 | 0.00 | 0.00 | 4756.98 | 0.00 | 0.130600E+10 | 18305082.21 | 0.00 | 0.42 |
April | 0.135634E+10 | 0.00 | 0.00 | 1507378.77 | 11081446.74 | 0.262868E+09 | 0.808055E+09 | 0.00 | 0.54 |
May | 0.973809E+09 | 5535053.20 | 0.00 | 3845966.82 | 0.00 | 434612.81 | 0.149617E+10 | 0.00 | 0.94 |
June | 0.256535E+09 | 0.299637E+09 | 0.00 | 5570124.29 | 33552215.13 | 0.00 | 0.193696E+10 | 0.00 | 1.45 |
July | 0.204983E+09 | 0.581984E+09 | 0.00 | 5337308.50 | 63818000.94 | 0.00 | 0.148359E+10 | 0.00 | 1.52 |
August | 0.351680E+09 | 0.271645E+09 | 0.00 | 5493941.96 | 10539898.73 | 0.00 | 0.159571E+10 | 0.00 | 1.46 |
September | 0.107881E+10 | 2085522.92 | 0.00 | 3589914.97 | 0.00 | 0.00 | 0.198306E+10 | 0.00 | 1.04 |
October | 0.190705E+10 | 0.00 | 0.00 | 458579.22 | 0.00 | 0.101075E+09 | 0.333204E+09 | 0.00 | 0.49 |
November | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857452E+09 | 0.00 | 0.00 | 0.41 |
December | 69805238.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225346E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.832841E+10 | 0.116089E+10 | 0.00 | 25807971.51 | 0.118992E+09 | 0.938319E+10 | 0.965506E+10 | 0.00 | 0.79 |
Minimum of Months | 39410835.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.190705E+10 | 0.581984E+09 | 0.00 | 5570124.29 | 63818000.94 | 0.285084E+10 | 0.198306E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551626E+10 | 0.00 | 0.00 | 0.51 |
February | 0.453997E+09 | 0.00 | 0.00 | 58317.32 | 0.00 | 0.316265E+10 | 52961137.09 | 0.00 | 0.46 |
March | 0.677168E+09 | 0.00 | 0.00 | 134008.22 | 0.00 | 0.289566E+10 | 93002468.64 | 0.00 | 0.45 |
April | 0.147690E+10 | 10499222.14 | 0.00 | 1270626.79 | 5482460.59 | 0.130368E+10 | 0.815757E+09 | 0.00 | 0.53 |
May | 0.156295E+10 | 10154266.55 | 0.00 | 3586095.43 | 0.00 | 0.396569E+09 | 0.100604E+10 | 0.00 | 0.73 |
June | 0.827001E+09 | 0.381138E+09 | 0.00 | 3539258.82 | 67121224.78 | 92372779.34 | 0.986216E+09 | 0.00 | 0.94 |
July | 0.464669E+09 | 0.725369E+09 | 0.00 | 4117043.72 | 0.117388E+09 | 15779055.49 | 0.108171E+10 | 0.00 | 1.02 |
August | 0.769268E+09 | 0.475215E+09 | 0.00 | 5878973.44 | 8351388.38 | 56379444.70 | 0.143257E+10 | 0.00 | 1.25 |
September | 0.144373E+10 | 6165086.86 | 0.00 | 6425097.62 | 0.00 | 0.350804E+09 | 0.279673E+10 | 0.00 | 1.08 |
October | 0.162211E+10 | 0.00 | 0.00 | 2849338.61 | 0.00 | 0.117673E+10 | 0.127497E+10 | 0.00 | 0.60 |
November | 0.832014E+09 | 0.00 | 0.00 | 187127.26 | 0.00 | 0.207635E+10 | 0.150064E+09 | 0.00 | 0.42 |
December | 0.186077E+09 | 0.00 | 0.00 | 49873.44 | 0.00 | 0.434190E+10 | 27093088.21 | 0.00 | 0.50 |
Annual Sum or Average | 0.104669E+11 | 0.160854E+10 | 0.00 | 28095760.66 | 0.198343E+09 | 0.213851E+11 | 0.971712E+10 | 0.00 | 0.71 |
Minimum of Months | 0.150981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15779055.49 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.162211E+10 | 0.725369E+09 | 0.00 | 6425097.62 | 0.117388E+09 | 0.551626E+10 | 0.279673E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311715E+10 | 0.00 | 0.00 | 0.46 |
February | 0.333151E+09 | 0.00 | 0.00 | 4622.05 | 0.00 | 0.186222E+10 | 13831513.17 | 0.00 | 0.44 |
March | 0.814028E+09 | 0.00 | 0.00 | 189681.45 | 0.00 | 0.140841E+10 | 0.112842E+09 | 0.00 | 0.46 |
April | 0.154056E+10 | 1276411.81 | 0.00 | 1207918.86 | 11020834.28 | 0.378448E+09 | 0.668514E+09 | 0.00 | 0.59 |
May | 0.115930E+10 | 7019971.68 | 0.00 | 4007220.86 | 0.00 | 13043420.66 | 0.131400E+10 | 0.00 | 0.98 |
June | 0.527667E+09 | 0.290249E+09 | 0.00 | 3758910.85 | 43881263.32 | 0.00 | 0.111283E+10 | 0.00 | 1.26 |
July | 0.241626E+09 | 0.581454E+09 | 0.00 | 4072587.63 | 74234158.37 | 0.00 | 0.110462E+10 | 0.00 | 1.34 |
August | 0.475946E+09 | 0.296250E+09 | 0.00 | 4547274.30 | 4893255.13 | 0.00 | 0.132327E+10 | 0.00 | 1.41 |
September | 0.127567E+10 | 3082054.16 | 0.00 | 3208474.55 | 0.00 | 0.00 | 0.166139E+10 | 0.00 | 1.02 |
October | 0.203586E+10 | 0.00 | 0.00 | 661033.36 | 0.00 | 0.128260E+09 | 0.394427E+09 | 0.00 | 0.55 |
November | 0.103577E+10 | 0.00 | 0.00 | 4942.06 | 0.00 | 0.951247E+09 | 11616265.92 | 0.00 | 0.44 |
December | 95431586.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243465E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.964955E+10 | 0.117933E+10 | 0.00 | 21662665.98 | 0.134030E+09 | 0.102934E+11 | 0.771735E+10 | 0.00 | 0.78 |
Minimum of Months | 95431586.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.203586E+10 | 0.581454E+09 | 0.00 | 4547274.30 | 74234158.37 | 0.311715E+10 | 0.166139E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33704996.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347845E+10 | 0.00 | 0.00 | 0.31 |
February | 0.221332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199609E+10 | 0.00 | 0.00 | 0.28 |
March | 0.954935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125417E+10 | 0.00 | 0.00 | 0.29 |
April | 0.174553E+10 | 0.00 | 0.00 | 506409.27 | 8226157.60 | 0.205946E+09 | 0.384452E+09 | 0.00 | 0.35 |
May | 0.869917E+09 | 11052824.87 | 0.00 | 5298991.78 | 0.00 | 1932747.55 | 0.201065E+10 | 0.00 | 0.72 |
June | 0.241373E+09 | 0.445932E+09 | 0.00 | 5954705.32 | 50757564.38 | 0.00 | 0.193384E+10 | 0.00 | 1.05 |
July | 0.246071E+09 | 0.686885E+09 | 0.00 | 4776402.01 | 87113809.22 | 0.00 | 0.128589E+10 | 0.00 | 0.97 |
August | 0.437020E+09 | 0.332665E+09 | 0.00 | 4476766.06 | 10180061.38 | 0.00 | 0.145543E+10 | 0.00 | 0.95 |
September | 0.128220E+10 | 6065671.23 | 0.00 | 2639547.40 | 460104.74 | 0.00 | 0.143742E+10 | 0.00 | 0.60 |
October | 0.193425E+10 | 0.00 | 0.00 | 146731.13 | 0.00 | 0.191080E+09 | 0.166213E+09 | 0.00 | 0.33 |
November | 0.810719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100388E+10 | 0.00 | 0.00 | 0.28 |
December | 30084515.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267174E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.880714E+10 | 0.148260E+10 | 0.00 | 23799552.97 | 0.156738E+09 | 0.108033E+11 | 0.867389E+10 | 0.00 | 0.54 |
Minimum of Months | 30084515.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.193425E+10 | 0.686885E+09 | 0.00 | 5954705.32 | 87113809.22 | 0.347845E+10 | 0.201065E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312445E+10 | 0.00 | 0.00 | 0.48 |
February | 0.571606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171938E+10 | 0.00 | 0.00 | 0.48 |
March | 0.129253E+10 | 0.00 | 0.00 | 434316.49 | 0.00 | 0.103572E+10 | 0.177982E+09 | 0.00 | 0.53 |
April | 0.156547E+10 | 0.00 | 0.00 | 3120824.05 | 9355388.23 | 0.151512E+09 | 0.155085E+10 | 0.00 | 0.77 |
May | 0.906559E+09 | 8418042.97 | 0.00 | 6401655.76 | 0.00 | 0.00 | 0.253200E+10 | 0.00 | 1.30 |
June | 0.308916E+09 | 0.403427E+09 | 0.00 | 7358557.86 | 38055116.36 | 0.00 | 0.254180E+10 | 0.00 | 1.84 |
July | 0.241070E+09 | 0.698047E+09 | 0.00 | 6189962.48 | 74674324.08 | 0.00 | 0.174867E+10 | 0.00 | 1.78 |
August | 0.586251E+09 | 0.294072E+09 | 0.00 | 5801435.01 | 15982539.61 | 0.00 | 0.161743E+10 | 0.00 | 1.63 |
September | 0.162090E+10 | 5948225.31 | 0.00 | 3463717.64 | 523264.77 | 1039801.44 | 0.179970E+10 | 0.00 | 1.15 |
October | 0.215762E+10 | 0.00 | 0.00 | 504175.81 | 0.00 | 0.212075E+09 | 0.307255E+09 | 0.00 | 0.61 |
November | 0.103505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100204E+10 | 0.00 | 0.00 | 0.50 |
December | 0.122648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252692E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.105562E+11 | 0.140991E+10 | 0.00 | 33274645.11 | 0.138591E+09 | 0.977315E+10 | 0.122757E+11 | 0.00 | 0.97 |
Minimum of Months | 0.122648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.215762E+10 | 0.698047E+09 | 0.00 | 7358557.86 | 74674324.08 | 0.312445E+10 | 0.254180E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.892715E+09 | 0.00 | 0.00 | 1852023.33 | 0.00 | 0.273921E+10 | 0.567399E+09 | 0.00 | 0.40 |
February | 0.834960E+09 | 0.00 | 0.00 | 3037463.07 | 0.00 | 0.150728E+10 | 0.972253E+09 | 0.00 | 0.44 |
March | 0.129425E+10 | 0.00 | 0.00 | 4450358.91 | 0.00 | 0.944603E+09 | 0.162172E+10 | 0.00 | 0.49 |
April | 0.158205E+10 | 19596893.25 | 0.00 | 6756951.42 | 1422685.99 | 0.175528E+09 | 0.335497E+10 | 0.00 | 0.83 |
May | 0.110927E+10 | 14506891.78 | 0.00 | 9216854.33 | 0.00 | 6002613.41 | 0.334738E+10 | 0.00 | 1.13 |
June | 0.568068E+09 | 0.523032E+09 | 0.00 | 7086730.95 | 64836268.23 | 0.00 | 0.222486E+10 | 0.00 | 1.37 |
July | 0.425100E+09 | 0.907564E+09 | 0.00 | 6011529.68 | 0.116762E+09 | 0.00 | 0.159160E+10 | 0.00 | 1.30 |
August | 0.652186E+09 | 0.528906E+09 | 0.00 | 8227738.49 | 8808780.99 | 0.00 | 0.210392E+10 | 0.00 | 1.50 |
September | 0.140045E+10 | 20565379.08 | 0.00 | 9383122.58 | 631635.38 | 0.00 | 0.401193E+10 | 0.00 | 1.31 |
October | 0.208120E+10 | 0.00 | 0.00 | 5337318.60 | 0.00 | 0.176769E+09 | 0.216645E+10 | 0.00 | 0.72 |
November | 0.125112E+10 | 0.00 | 0.00 | 2379034.15 | 0.00 | 0.852483E+09 | 0.897514E+09 | 0.00 | 0.45 |
December | 0.589222E+09 | 0.00 | 0.00 | 703968.40 | 0.00 | 0.245569E+10 | 0.235864E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.126806E+11 | 0.201417E+10 | 0.00 | 64443093.91 | 0.192461E+09 | 0.885757E+10 | 0.230959E+11 | 0.00 | 0.86 |
Minimum of Months | 0.425100E+09 | 0.00 | 0.00 | 703968.40 | 0.00 | 0.00 | 0.235864E+09 | 0.00 | 0.38 |
Maximum of Months | 0.208120E+10 | 0.907564E+09 | 0.00 | 9383122.58 | 0.116762E+09 | 0.273921E+10 | 0.401193E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322391E+10 | 0.00 | 0.00 | 0.50 |
February | 0.527100E+09 | 0.00 | 0.00 | 98015.96 | 0.00 | 0.180262E+10 | 63735090.90 | 0.00 | 0.50 |
March | 0.116862E+10 | 0.00 | 0.00 | 856613.90 | 0.00 | 0.112807E+10 | 0.388098E+09 | 0.00 | 0.56 |
April | 0.175760E+10 | 607331.49 | 0.00 | 2851161.82 | 9327242.67 | 0.204694E+09 | 0.144602E+10 | 0.00 | 0.84 |
May | 0.109310E+10 | 10573528.90 | 0.00 | 6957520.43 | 0.00 | 6074979.12 | 0.226444E+10 | 0.00 | 1.33 |
June | 0.536815E+09 | 0.391026E+09 | 0.00 | 5500107.84 | 50829570.19 | 0.00 | 0.158579E+10 | 0.00 | 1.66 |
July | 0.372751E+09 | 0.675765E+09 | 0.00 | 4647570.24 | 86251641.46 | 0.00 | 0.111400E+10 | 0.00 | 1.54 |
August | 0.687726E+09 | 0.329395E+09 | 0.00 | 4455416.45 | 4517843.87 | 0.00 | 0.125590E+10 | 0.00 | 1.55 |
September | 0.169044E+10 | 5111214.08 | 0.00 | 3366220.02 | 470774.79 | 1331052.87 | 0.161735E+10 | 0.00 | 1.17 |
October | 0.213629E+10 | 0.00 | 0.00 | 856052.89 | 0.00 | 0.238329E+09 | 0.464306E+09 | 0.00 | 0.66 |
November | 0.103215E+10 | 0.00 | 0.00 | 20992.28 | 0.00 | 0.102293E+10 | 39348044.39 | 0.00 | 0.51 |
December | 0.181541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257982E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.114163E+11 | 0.141248E+10 | 0.00 | 29609671.84 | 0.151397E+09 | 0.102078E+11 | 0.102390E+11 | 0.00 | 0.95 |
Minimum of Months | 0.181541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.213629E+10 | 0.675765E+09 | 0.00 | 6957520.43 | 86251641.46 | 0.322391E+10 | 0.226444E+10 | 0.00 | 1.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.169171E+12 | 0.216498E+11 | 0.00 | 0.186410E+12 | 0.517437E+11 |
February | 0.227065E+12 | 0.180061E+11 | 0.00 | 0.169228E+12 | 0.309576E+11 |
March | 0.307387E+12 | 0.149400E+11 | 0.00 | 0.199610E+12 | 0.225711E+11 |
April | 0.367757E+12 | 0.108565E+11 | 0.00 | 0.210796E+12 | 0.115976E+11 |
May | 0.416891E+12 | 0.541663E+10 | 0.00 | 0.252853E+12 | 0.642755E+11 |
June | 0.422454E+12 | 0.160172E+10 | 0.00 | 0.162229E+12 | 0.144477E+12 |
July | 0.429950E+12 | 0.554753E+09 | 0.00 | 0.111551E+12 | 0.194395E+12 |
August | 0.362525E+12 | 0.215035E+10 | 0.00 | 0.173429E+12 | 0.148023E+12 |
September | 0.273368E+12 | 0.552011E+10 | 0.00 | 0.245682E+12 | 0.333778E+11 |
October | 0.165633E+12 | 0.913458E+10 | 0.00 | 0.225993E+12 | 0.103814E+11 |
November | 0.965144E+11 | 0.138714E+11 | 0.00 | 0.169087E+12 | 0.195710E+11 |
December | 0.124657E+12 | 0.212592E+11 | 0.00 | 0.181064E+12 | 0.450503E+11 |
Annual Sum or Average | 0.336337E+13 | 0.124961E+12 | 0.00 | 0.228793E+13 | 0.776422E+12 |
Minimum of Months | 0.965144E+11 | 0.554753E+09 | 0.00 | 0.111551E+12 | 0.103814E+11 |
Maximum of Months | 0.429950E+12 | 0.216498E+11 | 0.00 | 0.252853E+12 | 0.194395E+12 |