Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2024-07-03 12:20:14


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1650.93 331.37 331.37
Net Site Energy 1650.93 331.37 331.37
Total Source Energy 5228.49 1049.44 1049.44
Net Source Energy 5228.49 1049.44 1049.44


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 124.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 305.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 302.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 71.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 48.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1650.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 124.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 305.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 302.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 71.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 48.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 124.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 305.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 302.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 71.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 48.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 110.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 331.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 110.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 331.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1650.928 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1650.928 100.00
     
Total On-Site and Utility Electric Sources 1650.928 100.00
Total Electricity End Uses 1650.928 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 128.50
Time Setpoint Not Met During Occupied Cooling 115.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 1773.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 8.6994 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 8.6994 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 8.6994 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 8.6994 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 8.6994 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 8.6994 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 8.6994 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 8.6994 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 8.6994 18.58 8.0700  
Total 4982.19             8.6994 9.29 24.1370  
Conditioned Total 4982.19             8.6994 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 8.6994 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 13-FEB-07:10 - - - - - - - - - - - 03-JAN-12:20
Heating 195320.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 10880.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 22496.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 975.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5356.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1951.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 242674.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 195320.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 10880.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 43.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 15327.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 975.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 5356.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 1951.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 395.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 967.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 957.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 162.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 227.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 152.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 5228.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 79.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 194.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 192.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 45.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 30.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1049.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 79.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 194.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 192.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 45.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 30.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1049.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2]
CORE_BOTTOM VAV BOX COMPONENT 2.72 0.275549 0.283000 0.769720 0.734798 0.500000 0.001383
CORE_MID VAV BOX COMPONENT 2.20 0.340370 0.342000 0.753045 0.907652 0.500000 0.001119
CORE_TOP VAV BOX COMPONENT 2.34 0.320154 0.335000 0.784207 0.853745 0.500000 0.001190
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.726007 0.217617 0.228000 0.165530 0.580313 0.500000 0.001751
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.696097 0.143690 0.200000 0.139219 0.383172 0.500000 0.002652
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 0.840533 0.187966 0.200000 0.168107 0.501243 0.500000 0.002027
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.767238 0.130358 0.200000 0.153448 0.347620 0.500000 0.002923
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.588036 0.268677 0.276000 0.162298 0.716471 0.500000 0.001418
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.598696 0.167066 0.200000 0.119739 0.445510 0.500000 0.002281
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.688894 0.229341 0.235000 0.161890 0.611576 0.500000 0.001661
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.619363 0.161481 0.200000 0.123873 0.430615 0.500000 0.002359
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.631133 0.250330 0.251000 0.158414 0.667547 0.500000 0.001522
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.670365 0.149205 0.200000 0.134073 0.397880 0.500000 0.002554
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 0.744990 0.212072 0.213000 0.158683 0.565526 0.500000 0.001797
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.697377 0.143416 0.200000 0.139475 0.382443 0.500000 0.002657
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 24785.76
CORE_MID VAV BOX REHEAT COIL 24248.82
CORE_TOP VAV BOX REHEAT COIL 35333.63
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16288.52
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 10560.27
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 16136.74
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10652.81
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 12467.11
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 8150.01
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12332.36
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8236.54
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 12837.64
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 8364.90
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 12695.32
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8449.74
PACU_VAV_BOT HEATING COIL 24829.27
PACU_VAV_MID HEATING COIL 25569.01
PACU_VAV_TOP HEATING COIL 24852.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.61 1.34 5.21 1.70 4.72 4.72 0.300000 0.360782 4.72
PACU_VAV_MID 2.47 1.34 4.95 1.94 4.35 4.35 0.300000 0.444714 4.35
PACU_VAV_TOP 2.69 1.41 5.37 2.76 5.07 5.07 0.300000 0.544711 5.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.72
PACU_VAV_MID_OA_CONTROLLER 4.35
PACU_VAV_TOP_OA_CONTROLLER 5.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.72 108009.53 0.727087 1.57 35999.58 0.727087
PACU_VAV_MID COOLING COIL 4.35 102699.86 0.717022 1.45 34229.86 0.717022
PACU_VAV_TOP COOLING COIL 5.07 113611.56 0.734723 1.69 37866.73 0.734723
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.72
PACU_VAV_MID FAN 4.35
PACU_VAV_TOP FAN 5.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 8.699 89.459 0.000 0.000 0.000 0.000 98.158 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.9622 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.9482 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.202 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8052
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8206
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5978
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.056
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.890
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.056
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.890
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
39 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
40 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
41 0 21.361010 0.87247630E-01 5.4456762  
42 7 -0.27384127E-12 0.12865281E-14 -0.83346422E-13 0.81323336E-16
43 6 0.26454352E-07 0.26406074E-09 0.60786733E-08 -0.12333448E-12
44 5 -0.17878666E-03 0.22931636E-05 -0.92101048E-04 0.60153540E-08
45 4 0.27880517 0.11305828E-02 0.94889811E-01 -0.31698392E-04
46 3 -7.0018852 0.35426556E-01 -2.2604600 0.27713709E-01
47 2 39.998753 0.12720283 14.942758 -0.32362551
48 1 -79.877006 0.57894353E-01 -28.852534 1.0643678
49 0 46.824343 0.11744712E-02 16.298269  
50 7 -0.27620064E-12 0.12774393E-14 -0.83964131E-13 0.81942822E-16
51 6 0.26622461E-07 0.26074659E-09 0.61157793E-08 -0.12423095E-12
52 5 -0.17965003E-03 0.22617301E-05 -0.92535175E-04 0.60516003E-08
53 4 0.27982997 0.11139309E-02 0.95257664E-01 -0.31841476E-04
54 3 -7.0222151 0.34872839E-01 -2.2664901 0.27813240E-01
55 2 40.065841 0.12511414 14.967577 -0.32437249
56 1 -79.928458 0.56904129E-01 -28.874810 1.0654641
57 0 46.824343 0.11535943E-02 16.297719  
58 7 -0.27931930E-12 0.13886628E-14 -0.87137092E-13 0.18759942E-15
59 6 0.23561308E-07 0.31712788E-09 0.54400317E-08 -0.10799411E-12
60 5 -0.16378969E-03 0.28142694E-05 -0.84539011E-04 0.53904798E-08
61 4 0.26080053 0.14141629E-02 0.88437074E-01 -0.29205444E-04
62 3 -6.6442204 0.45062581E-01 -2.1544048 0.25964059E-01
63 2 38.817908 0.16418932 14.505027 -0.31048073
64 1 -78.970774 0.75677137E-01 -28.459322 1.0450580
65 0 46.824349 0.15543837E-02 16.308247  
66 7 -0.13059908E-08 -0.16504735E-15 0.90649122E-14 -0.12541312E-15
67 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
68 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
69 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
70 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
71 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
72 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
73 0 0.32650513 0.16166393E-04 60.838472  
74 7 -0.12346633E-08 -0.14425327E-15 0.91357699E-14 -0.10087110E-15
75 6 0.94177090E-05 0.64929528E-08 0.31789869E-02 -0.26668006E-04
76 5 -0.68205191E-03 0.38502154E-05 -0.22310594 0.19506899E-02
77 4 0.15716902E-01 0.17535208E-03 4.8192406 -0.45165923E-01
78 3 -0.13809356 0.13952366E-02 -37.963195 0.39801023
79 2 0.49043520 0.23220647E-02 116.37063 -1.4164235
80 1 -0.70792287 0.70803996E-03 -143.84059 2.0479434
81 0 0.34515858 0.17069463E-04 60.838472  
82 7 -0.13059908E-08 -0.16504702E-15 0.90649122E-14 -0.12541312E-15
83 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
84 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
85 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
86 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
87 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
88 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
89 0 0.32650513 0.16166393E-04 60.838472  
90 7 -0.12345751E-08 -0.14398051E-15 0.92894684E-14 -0.10085648E-15
91 6 0.94183649E-05 0.64934092E-08 0.31789851E-02 -0.26667991E-04
92 5 -0.68209995E-03 0.38504865E-05 -0.22310583 0.19506890E-02
93 4 0.15718012E-01 0.17536444E-03 4.8192388 -0.45165906E-01
94 3 -0.13810332 0.13953351E-02 -37.963185 0.39801012
95 2 0.49046985 0.23222288E-02 116.37061 -1.4164232
96 1 -0.70797289 0.70809005E-03 -143.84058 2.0479432
97 0 0.34518296 0.17070678E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.45_SHGC_EAST_0.25 35 1 VerySmooth 2.557 2.557 1.000 0.251    
2 WINDOW_U_0.45_SHGC_SOUTH_0.25 36 1 VerySmooth 2.557 2.557 1.000 0.251    
3 WINDOW_U_0.45_SHGC_WEST_0.25 37 1 VerySmooth 2.557 2.557 1.000 0.251    
4 WINDOW_U_0.45_SHGC_NORTH_0.25 38 1 VerySmooth 2.557 2.557 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.66719E-002 0.16139 0.61727 0.61727 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12129 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.66719E-002 0.16139 0.61727 0.61727 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12129 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.66719E-002 0.16139 0.61727 0.61727 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12129 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.66719E-002 0.16139 0.61727 0.61727 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12129 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0154E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0548E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.5333E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5658E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.3333E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.3590E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9164E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9329E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1011
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6105E-002
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1127
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9971E-002
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6512E-002
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0535E-002
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2073E-002
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2006E-002
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0182E-003
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0717E-003
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.5364E-003
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5846E-003
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.3363E-003
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.3723E-003
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9162E-003
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9327E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4712E-002
26 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0617E-002
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3095E-002
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8955E-002
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.1866E-002
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5629E-002
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7685E-002
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7749E-002
33 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8084E-004
34 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8244E-004
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6586E-004
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.6702E-004
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2994E-004
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.3039E-004
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4038E-004
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.4095E-004
41 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9419E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9799E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4803E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5112E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1854E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2090E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9162E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9327E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7332E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5479E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1205E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1871E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9704E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.3399E-003
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2073E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2006E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9411E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9793E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4790E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5082E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1828E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1998E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9164E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9329E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.9026E-002
66 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3393E-002
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3943E-002
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.0120E-002
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7737E-002
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9199E-002
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7686E-002
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.7749E-002
73 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7990E-004
74 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8327E-004
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4179E-004
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4521E-004
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4291E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4468E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4040E-004
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4097E-004
81 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1093
82 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.7177E-002
83 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1214
84 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.1854E-002
85 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.3417E-002
86 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.9225E-002
87 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.6593E-002
88 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.7065E-002
89 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2977E-002
90 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.9600E-002
91 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1501E-002
92 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.8013E-002
93 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.0648E-002
94 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4890E-002
95 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.6984E-002
96 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.7326E-002
97 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.1345E-002
98 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0406E-002
99 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.4795E-002
100 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6142E-002
101 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3290E-002
102 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2281E-002
103 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.6593E-002
104 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7065E-002
105 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.7764E-002
106 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.2698E-002
107 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.2932E-002
108 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9575E-002
109 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6925E-002
110 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8735E-002
111 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6984E-002
112 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.7326E-002
113 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1093
114 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.7171E-002
115 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1214
116 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.1847E-002
117 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.3412E-002
118 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.9220E-002
119 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.6589E-002
120 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.7063E-002
121 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2976E-002
122 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.9597E-002
123 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1499E-002
124 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.8011E-002
125 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.0645E-002
126 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4887E-002
127 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.6980E-002
128 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.7324E-002
129 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.1346E-002
130 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0405E-002
131 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.4795E-002
132 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6142E-002
133 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3289E-002
134 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2279E-002
135 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.6589E-002
136 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7063E-002
137 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.7763E-002
138 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.2696E-002
139 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.2931E-002
140 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9574E-002
141 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6923E-002
142 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8733E-002
143 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6980E-002
144 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.7324E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 36398.62141 36398.62141 2.71986 2.71986 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 6814.74716 6814.74716 0.29666 0.42469 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 29492.69775 29492.69775 2.20189 2.20189 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 14154.25437 14154.25437 0.62121 0.62121 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 31063.55885 31063.55885 2.34092 2.34092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 34.02000 1.44726E-002 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 24889.41623 24889.41623 1.09728 1.09728 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 9633.75779 9633.75779 0.72601 0.72601 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.11500 1.44727E-002 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 11439.69640 11439.69640 0.50584 0.50584 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 9236.89836 9236.89836 0.69610 0.69610 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 31.26500 1.44675E-002 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 7416.21218 7416.21218 0.32795 0.32795 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 11153.48408 11153.48408 0.84053 0.84053 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 11333.38706 11333.38706 0.50112 0.50112 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 10180.93296 10180.93296 0.76724 0.76724 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.91167 1.44705E-002 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 7481.01810 7481.01810 0.33082 0.33082 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7803.05981 7803.05981 0.58804 0.58804 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 34.30500 1.44731E-002 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 8762.17945 8762.17945 0.38717 0.38717 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 7944.55991 7944.55991 0.59870 0.59870 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.50250 1.44680E-002 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 5727.40071 5727.40071 0.25310 0.25310 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 9141.42949 9141.42949 0.68889 0.68889 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 8667.81022 8667.81022 0.38298 0.38298 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 8218.80881 8218.80881 0.61936 0.61936 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59500 1.44700E-002 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 5787.99762 5787.99762 0.25579 0.25579 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 8374.86117 8374.86117 0.63113 0.63113 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 34.30500 1.44731E-002 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 9022.32748 9022.32748 0.39867 0.39867 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 8895.50644 8895.50644 0.67037 0.67037 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 31.02750 1.44671E-002 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 5878.32338 5878.32338 0.25977 0.25977 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 9885.70508 9885.70508 0.74499 0.74499 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 8922.65812 8922.65812 0.39425 0.39425 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 9253.95628 9253.95628 0.69738 0.69738 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 5937.73585 5937.73585 0.26241 0.26241 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 76065.24 4.72230 4.72230 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 26344.47 1.70372 1.70372 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:50:00
3 PACU_VAV_MID Cooling Sensible 71003.10 4.35406 4.35406 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 PACU_VAV_MID Heating Sensible 26401.97 1.93631 1.93631 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00
5 PACU_VAV_TOP Cooling Sensible 80209.49 5.07245 5.07245 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 26383.62 2.76302 2.76302 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.71986
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27555
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28300
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.76972
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73480
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.38269E-003
8 Coil:Heating:Electric CORE_BOTTOM VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 24785.76009
9 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.20189
10 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34037
11 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34200
12 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75304
13 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90765
14 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11937E-003
16 Coil:Heating:Electric CORE_MID VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 24248.81622
17 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.34092
18 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32015
19 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33500
20 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78421
21 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85374
22 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
23 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19005E-003
24 Coil:Heating:Electric CORE_TOP VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 35333.63410
25 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72601
26 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21762
27 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22800
28 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16553
29 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58031
30 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
31 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.75078E-003
32 Coil:Heating:Electric PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 16288.52467
33 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69610
34 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14369
35 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
36 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13922
37 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38317
38 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.65155E-003
40 Coil:Heating:Electric PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 10560.27406
41 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84053
42 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18797
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16811
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50124
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.02696E-003
48 Coil:Heating:Electric PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 16136.73533
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.76724
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13036
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15345
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34762
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.92273E-003
56 Coil:Heating:Electric PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 10652.80656
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.58804
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26868
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27600
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16230
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71647
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41806E-003
64 Coil:Heating:Electric PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12467.11474
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.59870
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16707
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.11974
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44551
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28053E-003
72 Coil:Heating:Electric PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8150.00601
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.68889
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22934
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23500
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16189
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61158
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66128E-003
80 Coil:Heating:Electric PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12332.35694
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.61936
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16148
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12387
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43062
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35941E-003
88 Coil:Heating:Electric PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8236.53941
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.63113
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25033
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25100
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15841
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66755
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.52199E-003
96 Coil:Heating:Electric PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12837.64424
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.67037
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14920
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13407
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39788
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55353E-003
104 Coil:Heating:Electric PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8364.90156
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.74499
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21207
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21300
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15868
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56553
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.79656E-003
112 Coil:Heating:Electric PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12695.32364
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69738
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14342
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13948
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38244
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.65660E-003
120 Coil:Heating:Electric PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8449.73980
121 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.60742
122 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.33752
123 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 5.21485
124 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.70372
125 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.72230
126 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.72230
127 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
128 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.36078
129 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.47288
130 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.34369
131 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.94575
132 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.93631
133 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.35406
134 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.35406
135 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
136 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.44471
137 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.68540
138 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.41051
139 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.37079
140 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.76302
141 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 5.07245
142 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 5.07245
143 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
144 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.54471
145 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.72230
146 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.35406
147 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 5.07245
148 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.72230
149 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.72230
150 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 108009.53149
151 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.72709
152 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.57394
153 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 35999.57685
154 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.72709
155 Coil:Heating:Electric PACU_VAV_BOT HEATING COIL Design Size Nominal Capacity [W] 24829.26859
156 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.72230
157 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.35406
158 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.35406
159 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 102699.86220
160 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.71702
161 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.45121
162 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 34229.86407
163 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.71702
164 Coil:Heating:Electric PACU_VAV_MID HEATING COIL Design Size Nominal Capacity [W] 25569.00936
165 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.35406
166 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.07245
167 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.07245
168 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 113611.56336
169 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.73472
170 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.69065
171 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 37866.73407
172 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.73472
173 Coil:Heating:Electric PACU_VAV_TOP HEATING COIL Design Size Nominal Capacity [W] 24852.24717
174 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 5.07245
175 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
176 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
177 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
178 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
179 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 107544.88 366958.35 12.42 3.17 3.56 3.75 3.90 10.82 12.14 12.80 13.32 5.2660 4.1880 2.8184 1.1860
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 102363.29 349278.04 12.49 3.18 3.58 3.77 3.92 10.86 12.21 12.88 13.37 4.8553 3.8580 2.5957 1.1033
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 113041.44 385713.40 12.37 3.16 3.55 3.73 3.90 10.79 12.10 12.74 13.29 5.6564 4.5047 3.0327 1.2650


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_NORTH_0.25 N/A 2.557 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_EAST_0.25 N/A 2.557 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_SOUTH_0.25 N/A 2.557 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_WEST_0.25 N/A 2.557 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_NORTH_0.25 N/A 2.557 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_NORTH_0.25 N/A 2.557 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_NORTH_0.25 N/A 2.557 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_EAST_0.25 N/A 2.557 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_EAST_0.25 N/A 2.557 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.337 0.312   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_SOUTH_0.25 N/A 2.557 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_SOUTH_0.25 N/A 2.557 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_SOUTH_0.25 N/A 2.557 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_WEST_0.25 N/A 2.557 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_WEST_0.25 N/A 2.557 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.337 0.312   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_NORTH_0.25 N/A 2.557 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_EAST_0.25 N/A 2.557 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_SOUTH_0.25 N/A 2.557 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.45_SHGC_WEST_0.25 N/A 2.557 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 4.1052747143E-003 5.7285901976E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.3497308466E-002 2.9956915914E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.8798364485E-003 4.2483039661E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.1626142756E-003 3.8537698894E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 5.6796230130E-003 6.7853908694E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 1.5190336722E-002 1.1308805651E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.4142832354E-002 2.4557947322E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 3.5383490184E-002 2.6310441210E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 3.5873223491E-002 2.8126384385E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 3.5608274601E-002 2.4993611368E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.3160099612E-002 2.0809090428E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.4027025014E-002 2.2517489240E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.4516023106E-002 2.3381916286E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.4039964921E-002 2.1252798240E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.6846499876E-002 2.2787402188E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 2.8066550197E-002 2.4733240884E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 2.8505437975E-002 2.6019272308E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 2.8219983674E-002 2.3300354374E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2919.86 24.70 0.00 1149.35 1611.87 5705.78



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.830 0.948 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.830 0.948 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.320 0.337 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.320 0.337 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.830 0.948 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.830 0.948 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.45_SHGC_NORTH_0.25   65.26 0.00 0.00 65.26 65.26 2.557 0.251 0.276             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.45_SHGC_EAST_0.25   43.51 0.00 0.00 43.51 43.51 2.557 0.251 0.276             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.45_SHGC_SOUTH_0.25   65.26 0.00 0.00 65.26 65.26 2.557 0.251 0.276             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.45_SHGC_WEST_0.25   43.51 0.00 0.00 43.51 43.51 2.557 0.251 0.276             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.45_SHGC_NORTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.45_SHGC_NORTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.45_SHGC_NORTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.45_SHGC_EAST_0.25   41.85 0.00 0.00 41.85 41.85 2.557 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.45_SHGC_EAST_0.25   1.65 0.00 0.00 1.65 1.65 2.557 0.251 0.276             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.45_SHGC_SOUTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.45_SHGC_SOUTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.45_SHGC_SOUTH_0.25   21.75 0.00 0.00 21.75 21.75 2.557 0.251 0.276             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.45_SHGC_WEST_0.25   41.85 0.00 0.00 41.85 41.85 2.557 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.45_SHGC_WEST_0.25   1.65 0.00 0.00 1.65 1.65 2.557 0.251 0.276             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.45_SHGC_NORTH_0.25   65.26 0.00 0.00 65.26 65.26 2.557 0.251 0.276             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.45_SHGC_EAST_0.25   43.51 0.00 0.00 43.51 43.51 2.557 0.251 0.276             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.45_SHGC_SOUTH_0.25   65.26 0.00 0.00 65.26 65.26 2.557 0.251 0.276             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.45_SHGC_WEST_0.25   43.51 0.00 0.00 43.51 43.51 2.557 0.251 0.276             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.557 0.251 0.276                      
North Total or Average             195.79 2.557 0.251 0.276                      
Non-North Total or Average             456.84 2.557 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.62 0.0000 Y 9.01
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.98 0.0000 Y 5.57
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.66 0.0000 Y 8.69
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.29 0.0000 Y 5.63
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.50 0.0000 Y 8.97
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.90 0.0000 Y 5.55
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.59 0.0000 Y 8.66
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.19 0.0000 Y 5.61
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.62 0.0000 Y 9.01
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.98 0.0000 Y 5.57
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.65 0.0000 Y 8.69
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.29 0.0000 Y 5.63
Interior Lighting Total       8.6994 4982.19 43341.88               302.40


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   41.77 41.77 4.42
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.77 62.77 4.80
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.77 47.60 42.13
Exterior Lighting Total 5686.19           51.35



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   108009.53 78532.28 29477.25 0.73 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   102699.86 73638.04 29061.82 0.72 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   113611.56 83473.06 30138.50 0.73 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   107544.9 3.17 10.82 N/A N/A 12.42
PACU_VAV_MID COOLING COIL   102363.3 3.18 10.86 N/A N/A 12.49
PACU_VAV_TOP COOLING COIL   113041.4 3.16 10.79 N/A N/A 12.37
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric   24785.76 1.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric   24248.82 1.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric   35333.63 1.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   16288.52 1.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   10560.27 1.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   16136.74 1.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   10652.81 1.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   12467.11 1.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   8150.01 1.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   12332.36 1.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   8236.54 1.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   12837.64 1.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   8364.90 1.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   12695.32 1.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   8449.74 1.00
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric   24829.27 1.00
PACU_VAV_MID HEATING COIL Coil:Heating:Electric   25569.01 1.00
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric   24852.25 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.72 10337.16 2189.01 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1389.42 4.35 10072.62 2313.39 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 5.07 11032.00 2174.89 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 107544.88 3.17 10.82 12.42 5.2660 3.56 12.14 4.1880 3.75 12.80 2.8184 3.90 13.32 1.1860
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 102363.29 3.18 10.86 12.49 4.8553 3.58 12.21 3.8580 3.77 12.88 2.5957 3.92 13.37 1.1033
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 113041.44 3.16 10.79 12.37 5.6564 3.55 12.10 4.5047 3.73 12.74 3.0327 3.90 13.29 1.2650
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 36398.62 36398.62 37.01 2.720 2.720 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00884 27.37 0.01446 0.425 0.00
CORE_MID 29492.70 29492.70 29.99 2.202 2.202 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 27.37 0.01446 0.425 0.00
CORE_TOP 31063.56 31063.56 31.58 2.341 2.341 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 24.00 24.00 0.00889 34.02 0.01447 0.425 0.00
PERIMETER_TOP_ZN_3 9633.76 9633.76 46.46 0.726 0.726 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00886 34.12 0.01447 0.090 0.00
PERIMETER_TOP_ZN_2 9236.90 9236.90 70.37 0.696 0.696 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 24.00 24.00 0.00874 31.26 0.01447 0.057 0.00
PERIMETER_TOP_ZN_1 11153.48 11153.48 53.79 0.841 0.841 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00881 34.40 0.01447 0.090 0.00
PERIMETER_TOP_ZN_4 10180.93 10180.93 77.57 0.767 0.767 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00872 32.91 0.01447 0.057 0.00
PERIMETER_BOT_ZN_3 7803.06 7803.06 37.63 0.588 0.588 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00889 34.30 0.01447 0.090 0.00
PERIMETER_BOT_ZN_2 7944.56 7944.56 60.52 0.599 0.599 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.00 24.00 0.00875 31.50 0.01447 0.057 0.00
PERIMETER_BOT_ZN_1 9141.43 9141.43 44.09 0.689 0.689 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00883 34.40 0.01447 0.090 0.00
PERIMETER_BOT_ZN_4 8218.81 8218.81 62.62 0.619 0.619 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00874 32.59 0.01447 0.057 0.00
PERIMETER_MID_ZN_3 8374.86 8374.86 40.39 0.631 0.631 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00890 34.30 0.01447 0.090 0.00
PERIMETER_MID_ZN_2 8895.51 8895.51 67.77 0.670 0.670 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 24.00 24.00 0.00874 31.03 0.01447 0.057 0.00
PERIMETER_MID_ZN_1 9885.71 9885.71 47.68 0.745 0.745 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00884 34.40 0.01447 0.090 0.00
PERIMETER_MID_ZN_4 9253.96 9253.96 70.50 0.697 0.697 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00873 32.75 0.01447 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 6814.75 6814.75 6.93 0.297 0.425 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
CORE_MID 14154.25 14154.25 14.39 0.621 0.621 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
CORE_TOP 24889.42 24889.42 25.31 1.097 1.097 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
PERIMETER_TOP_ZN_3 11439.70 11439.70 55.17 0.506 0.506 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_TOP_ZN_2 7416.21 7416.21 56.50 0.328 0.328 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.057 0.00
PERIMETER_TOP_ZN_1 11333.39 11333.39 54.66 0.501 0.501 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_TOP_ZN_4 7481.02 7481.02 57.00 0.331 0.331 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.057 0.00
PERIMETER_BOT_ZN_3 8762.18 8762.18 42.26 0.387 0.387 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_BOT_ZN_2 5727.40 5727.40 43.63 0.253 0.253 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00777 -6.30 0.00230 0.057 0.00
PERIMETER_BOT_ZN_1 8667.81 8667.81 41.81 0.383 0.383 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_BOT_ZN_4 5788.00 5788.00 44.10 0.256 0.256 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 -6.30 0.00230 0.057 0.00
PERIMETER_MID_ZN_3 9022.33 9022.33 43.52 0.399 0.399 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00771 -6.30 0.00230 0.090 0.00
PERIMETER_MID_ZN_2 5878.32 5878.32 44.78 0.260 0.260 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00771 -6.30 0.00230 0.057 0.00
PERIMETER_MID_ZN_1 8922.66 8922.66 43.03 0.394 0.394 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -6.30 0.00230 0.090 0.00
PERIMETER_MID_ZN_4 5937.74 5937.74 45.24 0.262 0.262 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00771 -6.30 0.00230 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.72 4.72 1.70 1.70 4.7223 1.7037 4.7223 0.3608 0.3000
PACU_VAV_MID 4.35 4.35 1.94 1.94 4.3541 1.9363 4.3541 0.4447 0.3000
PACU_VAV_TOP 5.07 5.07 2.76 2.76 5.0724 2.7630 5.0724 0.5447 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 24785.760 24785.760 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24785.76 13675.49 0.424691 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 6814.75 0.00 -999.00 -999.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 24248.816 24248.816 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24248.82 20003.59 0.621210 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 14154.25 0.00 -999.00 -999.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 35333.634 35333.634 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 35333.63 35333.63 1.097283 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 24889.42 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 16288.525 16288.525 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16288.52 16288.52 0.505839 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00776362 48.4106 11439.70 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 10560.274 10560.274 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10560.27 10560.27 0.327948 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775851 48.3792 7416.21 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 16136.735 16136.735 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16136.74 16136.74 0.501125 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00776090 48.3938 11333.39 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 10652.807 10652.807 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10652.81 10652.81 0.330822 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00776101 48.3946 7481.02 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 12467.115 12467.115 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12467.11 12467.11 0.387165 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00776451 48.4157 8762.18 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 8150.006 8150.006 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8150.01 8150.01 0.253098 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00777090 48.4550 5727.40 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 12332.357 12332.357 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12332.36 12332.36 0.382980 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775736 48.3718 8667.81 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8236.539 8236.539 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8236.54 8236.54 0.255785 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00777738 48.4949 5788.00 0.00 -999.00 -999.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 12837.644 12837.644 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12837.64 12837.64 0.398672 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00770887 48.0736 9022.33 0.00 -999.00 -999.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 8364.902 8364.902 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8364.90 8364.90 0.259771 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00770951 48.0776 5878.32 0.00 -999.00 -999.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 12695.324 12695.324 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12695.32 12695.32 0.394252 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00770230 48.0332 8922.66 0.00 -999.00 -999.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 8449.740 8449.740 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8449.74 8449.74 0.262406 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00771488 48.1106 5937.74 0.00 -999.00 -999.00
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 108009.531 78532.282 4.722295 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 108719.98 84619.07 4.722295 26.64 18.35 0.01027683 10.96 10.96 0.00850000 34.40 0.01447326 23.54 25.3091 24.00 0.00885078 45.9137 62529.53 0.00 111372.33 78549.81
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_BOT 24829.269 24829.269 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24829.27 24829.27 1.416689 -2.22 -2.42 0.00312912 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 84.3636 19.62 0.00758619 51.5217 19854.36 0.00 -999.00 -999.00
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 102699.862 73638.044 4.354060 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 103876.23 79522.25 4.354060 26.87 18.55 0.01043919 10.85 10.85 0.00850000 34.40 0.01447326 23.54 27.4496 24.00 0.00889860 46.1585 57387.76 0.00 105897.34 73724.21
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_MID 25569.009 25569.009 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25569.01 25569.01 1.306218 -3.98 -4.05 0.00276328 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 91.4985 19.88 0.00775054 51.7888 24933.12 0.00 -999.00 -999.00
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 113611.563 83473.060 5.072446 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 114126.50 89636.21 5.072446 26.42 18.20 0.01018055 10.97 10.97 0.00850000 34.21 0.01447292 23.49 23.5620 24.00 0.00884962 45.9080 67007.81 0.00 117148.77 83456.75
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_TOP 24852.247 24852.247 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24852.25 24852.25 1.521734 -1.20 -1.35 0.00344487 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 78.5400 17.60 0.00759596 58.5527 29414.25 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes No unknown No 24785.760 24785.760 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24785.76 13675.49 1.0000 0.49305639 0.424691 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24785.76 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.59 0.00800000 21.00 0.00800000 49.8624 6814.75 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes No unknown No 24248.816 24248.816 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24248.82 20003.59 1.0000 0.72120975 0.621210 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 24248.82 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.8624 14154.25 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes No unknown No 35333.634 35333.634 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 35333.63 35333.63 1.0000 1.27391967 1.097283 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 35333.63 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 49.8624 24889.42 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes No unknown No 16288.525 16288.525 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16288.52 16288.52 1.0000 0.58726685 0.505839 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 16288.52 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00776362 21.00 0.00776362 48.4106 11439.70 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes No unknown No 10560.274 10560.274 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10560.27 10560.27 1.0000 0.38074037 0.327948 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10560.27 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775851 21.00 0.00775851 48.3792 7416.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes No unknown No 16136.735 16136.735 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16136.74 16136.74 1.0000 0.58179423 0.501125 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 16136.74 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00776090 21.00 0.00776090 48.3938 11333.39 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes No unknown No 10652.807 10652.807 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10652.81 10652.81 1.0000 0.38407654 0.330822 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10652.81 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00776101 21.00 0.00776101 48.3946 7481.02 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes No unknown No 12467.115 12467.115 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12467.11 12467.11 1.0000 0.44948965 0.387165 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12467.11 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00776451 21.00 0.00776451 48.4157 8762.18 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes No unknown No 8150.006 8150.006 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8150.01 8150.01 1.0000 0.29384051 0.253098 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8150.01 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00777090 21.00 0.00777090 48.4550 5727.40 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes No unknown No 12332.357 12332.357 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12332.36 12332.36 1.0000 0.44463109 0.382980 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12332.36 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775736 21.00 0.00775736 48.3718 8667.81 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes No unknown No 8236.539 8236.539 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8236.54 8236.54 1.0000 0.29696038 0.255785 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8236.54 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00777738 21.00 0.00777738 48.4949 5788.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes No unknown No 12837.644 12837.644 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12837.64 12837.64 1.0000 0.46284873 0.398672 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12837.64 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00770887 21.00 0.00770887 48.0736 9022.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes No unknown No 8364.902 8364.902 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8364.90 8364.90 1.0000 0.30158836 0.259771 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8364.90 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00770951 21.00 0.00770951 48.0776 5878.32 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes No unknown No 12695.324 12695.324 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12695.32 12695.32 1.0000 0.45771750 0.394252 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12695.32 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00770230 21.00 0.00770230 48.0332 8922.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes No unknown No 8449.740 8449.740 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8449.74 8449.74 1.0000 0.30464712 0.262406 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8449.74 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00771488 21.00 0.00771488 48.1106 5937.74 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 108009.531 78532.282 4.722295 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.9441 1004.8586 1.1610 PACU_VAV_BOT FAN Fan:VariableVolume 4.722295 5.48247382   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 108719.98 84619.07 1.0066 5.48247382 4.722295 26.64 18.35 0.01027683 52976.3 10.96 10.96 0.00850000 32442.8 -999.0 -999.00 -999.00 -999.00 10337.156 98382.82 34.40 0.01447326 23.54 1.19517000 25.3091 24.00 0.00885078 24.00 0.00885078 45.9137 62529.53 0.00 111372.33 78549.81 5.26595755 26.67 19.44 0.01118466 55322.4 12.06 12.03 0.00874086 34172.9
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 24829.269 24829.269 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_BOT FAN Fan:VariableVolume 4.722295 5.48247382   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:50:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24829.27 24829.27 1.0000 1.64474215 1.416689 -2.22 -2.42 0.00312912 5578.9 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 24829.27 -6.30 0.00229779 -6.30 1.19517000 84.3636 19.77 0.00761443 19.62 0.00758619 51.5217 19854.36 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 102699.862 73638.044 4.354060 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.2459 1004.8586 1.1610 PACU_VAV_MID FAN Fan:VariableVolume 4.354060 5.05496120   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 103876.23 79522.25 1.0115 5.05496120 4.354060 26.87 18.55 0.01043919 53632.5 10.85 10.85 0.00850000 32336.6 -999.0 -999.00 -999.00 -999.00 10072.623 93803.61 34.40 0.01447326 23.54 1.19517000 27.4496 24.00 0.00889860 24.00 0.00889860 46.1585 57387.76 0.00 105897.34 73724.21 4.85532844 26.67 19.44 0.01118466 55322.4 11.79 11.77 0.00858661 33511.8
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 25569.009 25569.009 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_MID FAN Fan:VariableVolume 4.354060 5.05496120   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25569.01 25569.01 1.0000 1.51648836 1.306218 -3.98 -4.05 0.00276328 2892.0 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 25569.01 -6.30 0.00229779 -6.30 1.19517000 91.4985 21.00 0.00777319 19.88 0.00775054 51.7888 24933.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 113611.563 83473.060 5.072446 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7651 1004.8586 1.1610 PACU_VAV_TOP FAN Fan:VariableVolume 5.072446 5.88899071   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 114126.50 89636.21 1.0045 5.88899071 5.072446 26.42 18.20 0.01018055 52504.1 10.97 10.97 0.00850000 32454.6 -999.0 -999.00 -999.00 -999.00 11032.003 103094.50 34.21 0.01447292 23.49 1.19517000 23.5620 24.00 0.00884962 24.00 0.00884962 45.9080 67007.81 0.00 117148.77 83456.75 5.65642009 26.67 19.44 0.01118466 55322.4 12.22 12.21 0.00884928 34611.6
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 24852.247 24852.247 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_TOP FAN Fan:VariableVolume 5.072446 5.88899071   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24852.25 24852.25 1.0000 1.76669721 1.521734 -1.20 -1.35 0.00344487 7402.9 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 24852.25 -6.30 0.00229779 -6.30 1.19517000 78.5400 17.47 0.00764299 17.60 0.00759596 58.5527 29414.25 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialEnthalpy 0.00 4.72 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialEnthalpy 0.00 4.35 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialEnthalpy 0.00 5.07 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 2967.00 1842.17 16.33
CORE_MID 2286.50 3099.83 262.00
CORE_TOP 2546.00 3418.00 697.83
PERIMETER_TOP_ZN_3 3327.83 3542.67 1355.67
PERIMETER_TOP_ZN_2 3323.17 3392.83 1221.33
PERIMETER_TOP_ZN_1 3163.00 3016.00 925.33
PERIMETER_TOP_ZN_4 3201.00 3532.33 1262.67
PERIMETER_BOT_ZN_3 2924.83 3575.17 1005.00
PERIMETER_BOT_ZN_2 3058.33 3190.33 799.83
PERIMETER_BOT_ZN_1 2938.83 3234.67 785.17
PERIMETER_BOT_ZN_4 3024.33 3248.00 829.33
PERIMETER_MID_ZN_3 3135.50 3326.33 1010.83
PERIMETER_MID_ZN_2 2650.33 2794.67 846.50
PERIMETER_MID_ZN_1 3064.33 2686.50 603.50
PERIMETER_MID_ZN_4 3099.67 3268.17 931.83
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4620.33 4259.00 1773.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.17 0.00 0.17 0.00
CORE_TOP 1.83 0.00 1.17 0.00
PERIMETER_TOP_ZN_3 20.83 3.33 9.33 2.17
PERIMETER_TOP_ZN_2 13.67 22.50 2.67 21.67
PERIMETER_TOP_ZN_1 9.67 18.67 2.67 17.50
PERIMETER_TOP_ZN_4 14.33 26.50 3.83 15.00
PERIMETER_BOT_ZN_3 1.17 0.00 0.83 0.00
PERIMETER_BOT_ZN_2 0.33 10.67 0.00 10.67
PERIMETER_BOT_ZN_1 121.33 51.00 121.33 51.00
PERIMETER_BOT_ZN_4 0.33 16.00 0.00 8.33
PERIMETER_MID_ZN_3 2.17 0.00 1.50 0.00
PERIMETER_MID_ZN_2 1.17 17.00 0.50 17.00
PERIMETER_MID_ZN_1 1.17 14.50 0.50 14.50
PERIMETER_MID_ZN_4 1.17 22.17 0.50 12.67
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 141.50 135.83 128.50 115.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.99 52.94 2698.04 0.702 0.000 0.000 0.000
CORE_MID 21.99 52.94 2698.04 0.565 0.000 0.000 0.000
CORE_TOP 21.99 52.94 2698.04 0.566 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.64 11.16 568.77 0.628 0.038 0.000 0.000
PERIMETER_TOP_ZN_2 2.94 7.07 360.08 0.875 0.040 0.000 0.000
PERIMETER_TOP_ZN_1 4.64 11.16 568.77 0.775 0.038 0.000 0.000
PERIMETER_TOP_ZN_4 2.93 7.06 360.05 0.933 0.040 0.000 0.000
PERIMETER_BOT_ZN_3 4.64 11.16 568.77 0.576 0.020 0.000 0.000
PERIMETER_BOT_ZN_2 2.94 7.07 360.08 0.754 0.021 0.000 0.000
PERIMETER_BOT_ZN_1 4.64 11.16 568.77 0.709 0.817 0.000 0.000
PERIMETER_BOT_ZN_4 2.93 7.06 360.05 0.755 0.021 0.000 0.000
PERIMETER_MID_ZN_3 4.64 11.16 568.77 0.618 0.031 0.000 0.000
PERIMETER_MID_ZN_2 2.58 7.07 360.08 0.800 0.035 0.000 0.000
PERIMETER_MID_ZN_1 4.64 11.16 568.77 0.777 0.032 0.000 0.000
PERIMETER_MID_ZN_4 2.93 7.06 360.05 0.890 0.033 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.94 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.94 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.58 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.99 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.99 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.99 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.94 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.93 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.94 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.93 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.58 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.93 7.06 360.05 131.25 0.0000 0.057
Total Facility   111.05 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 11055765.50 0.00 11055765.50 0.00 11055765.50 13393058.27 5099.32 381.34 3279.34 3.72
CORE_MID 8940842.95 0.00 8940842.95 0.00 8940842.95 13393058.27 6310.34 228.84 2220.82 16.76
CORE_TOP 8984186.41 0.00 8984186.41 0.00 8984186.41 13393058.27 6573.26 59.15 2127.59 74.51
PERIMETER_TOP_ZN_3 2099702.62 0.00 2099702.62 253748.86 2353451.48 2823374.22 5237.51 83.31 3439.17 74.51
PERIMETER_TOP_ZN_2 1850983.50 0.00 1850983.50 169164.89 2020148.39 1787429.43 4248.68 4.31 4507.01 74.51
PERIMETER_TOP_ZN_1 2583099.35 0.00 2583099.35 253748.86 2836848.21 2823374.22 4535.07 689.13 3535.80 74.51
PERIMETER_TOP_ZN_4 1974058.58 0.00 1974058.58 169164.89 2143223.47 1787312.18 4273.40 17.47 4469.13 74.51
PERIMETER_BOT_ZN_3 1918452.31 0.00 1918452.31 134917.23 2053369.54 2823374.22 5768.88 398.05 2593.07 3.72
PERIMETER_BOT_ZN_2 1588474.42 0.00 1588474.42 89944.28 1678418.70 1787429.43 4361.55 60.25 4338.20 3.72
PERIMETER_BOT_ZN_1 2357807.09 0.00 2357807.09 2786735.31 5144542.40 2823374.22 4964.00 350.91 3445.09 3.72
PERIMETER_BOT_ZN_4 1590371.93 0.00 1590371.93 89944.28 1680316.20 1787312.18 4575.86 87.83 4096.31 3.72
PERIMETER_MID_ZN_3 2060078.98 0.00 2060078.98 211226.68 2271305.66 2823374.22 5044.36 188.64 3526.99 16.76
PERIMETER_MID_ZN_2 1833014.09 0.00 1833014.09 140816.94 1973831.03 1787429.43 4226.37 10.74 4522.89 925.76
PERIMETER_MID_ZN_1 2585890.67 0.00 2585890.67 211226.68 2797117.35 2823374.22 4877.13 223.04 3659.83 16.76
PERIMETER_MID_ZN_4 1878937.65 0.00 1878937.65 140816.94 2019754.59 1787312.18 4278.22 25.92 4455.87 16.76
Total Facility 53301666.05 0.00 53301666.05 4651455.83 57953121.87 67843644.98 6728.11 1236.33 4567.08 986.40


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.5165 0.0000 0.5165 0.0000 0.5165 0.4247 2283.37 381.34 3278.29
CORE_MID 0.4169 0.0000 0.4169 0.0000 0.4169 0.4247 3497.57 228.84 2216.59
CORE_TOP 0.4181 0.0000 0.4181 0.0000 0.4181 0.4247 3760.94 59.15 2122.91
PERIMETER_TOP_ZN_3 0.0977 0.0000 0.0977 0.0059 0.1036 0.0895 2425.19 83.31 3434.49
PERIMETER_TOP_ZN_2 0.0862 0.0000 0.0862 0.0039 0.0901 0.0567 1436.62 4.31 4502.07
PERIMETER_TOP_ZN_1 0.1203 0.0000 0.1203 0.0059 0.1262 0.0895 1722.78 689.13 3531.09
PERIMETER_TOP_ZN_4 0.0919 0.0000 0.0919 0.0039 0.0958 0.0567 1461.33 17.47 4464.21
PERIMETER_BOT_ZN_3 0.0896 0.0000 0.0896 0.0031 0.0927 0.0895 2952.96 398.05 2592.00
PERIMETER_BOT_ZN_2 0.0742 0.0000 0.0742 0.0021 0.0763 0.0567 1545.82 60.25 4336.94
PERIMETER_BOT_ZN_1 0.1102 0.0000 0.1102 0.1271 0.2372 0.0895 2148.08 350.91 3444.01
PERIMETER_BOT_ZN_4 0.0743 0.0000 0.0743 0.0021 0.0764 0.0567 1760.12 87.81 4095.07
PERIMETER_MID_ZN_3 0.0961 0.0000 0.0961 0.0049 0.1010 0.0895 2231.73 188.62 3522.64
PERIMETER_MID_ZN_2 0.0788 0.0000 0.0788 0.0035 0.0823 0.0567 1406.30 7.41 3620.29
PERIMETER_MID_ZN_1 0.1207 0.0000 0.1207 0.0049 0.1256 0.0895 2064.39 223.04 3655.57
PERIMETER_MID_ZN_4 0.0876 0.0000 0.0876 0.0033 0.0909 0.0567 1465.72 25.92 4451.36
Total Facility 2.4791 0.0000 2.4791 0.1705 2.6496 2.1513 3911.44 1236.29 4560.94


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 24950218.71 0.00 24950218.71 22614548.33 4213.99 2.14 4543.86 3.72
PACU_VAV_MID 23316459.10 0.00 23316459.10 22614548.33 4207.91 0.21 4551.88 16.76
PACU_VAV_TOP 23576919.70 0.00 23576919.70 22614548.33 4239.17 1.11 4519.72 74.51


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.1656 0.0000 1.1656 0.7171 1398.29 1.98 4542.73
PACU_VAV_MID 1.0875 0.0000 1.0875 0.7171 1395.24 0.21 4547.55
PACU_VAV_TOP 1.0975 0.0000 1.0975 0.7171 1426.85 1.11 4515.04


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 0.00 2355.31 0.00 0.00 0.00 2211.55 0.00 0.00 0.00
PACU_VAV_MID 0.00 0.00 2264.52 0.00 0.00 0.00 2326.15 0.00 0.00 0.00
PACU_VAV_TOP 0.00 0.00 2296.65 0.00 0.00 0.00 2355.98 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 0.0000 1.9504 0.0000 0.0000 0.0000 1.0591 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 0.0000 1.7810 0.0000 0.0000 0.0000 1.0580 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 0.0000 1.8218 0.0000 0.0000 0.0000 1.0505 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 920
Defaulted Fields 545
Fields with Defaults 2217
Autosized Fields 149
Autosizable Fields 202
Autocalculated Fields 155
Autocalculatable Fields 276



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
Electricity:Building 1022.09 13465.67 29-MAY-17:20 74341.76 03-JAN-08:10
Electricity:Zone:CORE_BOTTOM 322.35 5243.28 01-JAN-00:10 20463.73 02-JAN-08:10
Electricity:SpaceType:GENERAL 1022.09 13465.67 29-MAY-17:20 74341.76 03-JAN-08:10
InteriorLights:Electricity 302.40 987.92 29-MAY-17:20 32642.50 03-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 302.40 987.92 29-MAY-17:20 32642.50 03-JAN-08:10
LightsWired:InteriorLights:Electricity 302.40 987.92 29-MAY-17:20 32642.50 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 302.40 987.92 29-MAY-17:20 32642.50 03-JAN-08:10
Electricity:Zone:CORE_MID 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:CORE_TOP 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 33.35 422.10 16-APR-17:10 2793.69 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.01 36.00 01-JAN-11:30 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.01 36.00 01-JAN-11:30 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 20.97 267.21 21-MAY-17:10 1768.58 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.57 22.79 01-JAN-09:20 860.01 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.57 22.79 01-JAN-09:20 860.01 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 33.02 422.10 12-MAR-17:10 2793.68 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.69 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.69 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 21.04 267.21 05-MAR-18:10 1768.52 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.63 22.79 01-JAN-11:00 859.95 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.63 22.79 01-JAN-11:00 859.95 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 33.30 422.10 16-APR-17:10 2793.69 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.97 36.00 01-JAN-11:20 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.97 36.00 01-JAN-11:20 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 20.96 267.21 23-APR-17:10 1768.58 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.55 22.79 01-JAN-09:10 860.01 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.55 22.79 01-JAN-09:10 860.01 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 33.00 422.10 12-MAR-17:10 2793.68 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.66 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.66 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 21.02 267.21 05-MAR-18:10 1768.52 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.61 22.79 01-JAN-11:00 859.95 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.61 22.79 01-JAN-11:00 859.95 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 33.35 422.10 16-APR-17:10 2793.69 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 9.01 36.00 01-JAN-11:30 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 9.01 36.00 01-JAN-11:30 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 20.97 267.21 21-MAY-17:10 1768.58 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.57 22.79 01-JAN-09:20 860.01 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.57 22.79 01-JAN-09:20 860.01 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 33.02 422.10 12-MAR-17:10 2793.68 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.69 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.69 36.00 01-JAN-09:20 1358.45 03-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 21.04 267.21 05-MAR-18:10 1768.52 03-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.63 22.79 01-JAN-11:00 859.95 03-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.63 22.79 01-JAN-11:00 859.95 03-JAN-08:10
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 529.19 367.92 01-JAN-00:10 201652.63 13-FEB-07:10
ExteriorEquipment:Electricity 26.91 367.92 01-JAN-00:10 1410.29 05-JAN-17:10
Transformer:ExteriorEquipment:Electricity 26.91 367.92 01-JAN-00:10 1410.29 05-JAN-17:10
ElectricityPurchased:Facility 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
ElectricityPurchased:Plant 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
Cogeneration:ElectricityPurchased 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
General:Cogeneration:ElectricityPurchased 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
ElectricityNet:Plant 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
Cogeneration:ElectricityNet 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
General:Cogeneration:ElectricityNet 1650.93 13840.93 09-JUL-17:40 242674.82 13-FEB-07:10
Heating:Electricity 124.85 0.00 01-JAN-00:10 195320.41 13-FEB-07:10
General:Heating:Electricity 124.85 0.00 01-JAN-00:10 195320.41 13-FEB-07:10
Fans:Electricity 71.99 0.00 01-JAN-00:10 14770.08 02-AUG-16:00
General:Fans:Electricity 71.99 0.00 01-JAN-00:10 14770.08 02-AUG-16:00
ExteriorLights:Electricity 51.35 0.00 01-JAN-07:50 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 51.35 0.00 01-JAN-07:50 5686.19 01-JAN-06:10
Cooling:Electricity 305.46 0.00 01-JAN-00:10 70815.12 07-JUL-16:00
General:Cooling:Electricity 305.46 0.00 01-JAN-00:10 70815.12 07-JUL-16:00
Electricity:Plant 48.30 0.00 01-JAN-00:10 6221.35 30-JAN-13:00
WaterSystems:Electricity 48.15 0.00 01-JAN-00:10 6214.50 30-JAN-13:00
Water Heater:WaterSystems:Electricity 48.15 0.00 01-JAN-00:10 6214.50 30-JAN-13:00
Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 05-JAN-06:10
General:Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 05-JAN-06:10
WIRED_LTG_ELECTRICITY 8.50 0.00 01-JAN-00:10 917.25 03-JAN-08:20
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:20
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2717.34 0.00 01-JAN-00:10 415023.22 07-JUL-16:00
EnergyTransfer:Building 1240.71 0.00 01-JAN-00:10 160455.30 02-AUG-15:50
EnergyTransfer:Zone:CORE_BOTTOM 250.78 0.00 01-JAN-00:10 25116.00 21-AUG-08:00
Heating:EnergyTransfer 61.05 0.00 01-JAN-00:10 145500.95 09-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 2640.22 02-JAN-07:10
General:Heating:EnergyTransfer 61.05 0.00 01-JAN-00:10 145500.95 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 2640.22 02-JAN-07:10
Cooling:EnergyTransfer 1179.66 0.00 01-JAN-00:10 160455.30 02-AUG-15:50
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 250.78 0.00 01-JAN-00:10 25116.00 21-AUG-08:00
General:Cooling:EnergyTransfer 1179.66 0.00 01-JAN-00:10 160455.30 02-AUG-15:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 250.78 0.00 01-JAN-00:10 25116.00 21-AUG-08:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 48.29 0.00 01-JAN-00:10 13160.48 13-FEB-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 11.37 0.00 01-JAN-00:10 13160.48 13-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 11.37 0.00 01-JAN-00:10 13160.48 13-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 36.91 0.00 01-JAN-00:10 10435.40 01-AUG-14:00
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 36.91 0.00 01-JAN-00:10 10435.40 01-AUG-14:00
EnergyTransfer:Zone:MIDFLOOR_PLENUM 24.53 0.00 01-JAN-00:10 7010.52 09-JAN-07:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 3.93 0.00 01-JAN-00:10 7010.52 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 3.93 0.00 01-JAN-00:10 7010.52 09-JAN-07:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 20.60 0.00 01-JAN-00:10 4333.73 10-JUL-15:50
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 20.60 0.00 01-JAN-00:10 4333.73 10-JUL-15:50
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 26.54 0.00 01-JAN-00:10 4688.62 18-AUG-16:00
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 2.48 0.00 01-JAN-00:10 3512.36 09-JAN-09:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 2.48 0.00 01-JAN-00:10 3512.36 09-JAN-09:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 24.06 0.00 01-JAN-00:10 4688.62 18-AUG-16:00
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 24.06 0.00 01-JAN-00:10 4688.62 18-AUG-16:00
EnergyTransfer:Zone:CORE_MID 182.59 0.00 01-JAN-00:10 18770.50 21-AUG-07:50
Heating:EnergyTransfer:Zone:CORE_MID 0.40 0.00 01-JAN-00:10 14271.03 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.40 0.00 01-JAN-00:10 14271.03 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 182.20 0.00 01-JAN-00:10 18770.50 21-AUG-07:50
General:Cooling:EnergyTransfer:Zone:CORE_MID 182.20 0.00 01-JAN-00:10 18770.50 21-AUG-07:50
EnergyTransfer:Zone:CORE_TOP 179.94 0.00 01-JAN-00:10 26823.66 09-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_TOP 3.10 0.00 01-JAN-00:10 26823.66 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 3.10 0.00 01-JAN-00:10 26823.66 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 176.84 0.00 01-JAN-00:10 20701.52 07-JUL-15:50
General:Cooling:EnergyTransfer:Zone:CORE_TOP 176.84 0.00 01-JAN-00:10 20701.52 07-JUL-15:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 46.98 0.00 01-JAN-00:10 9189.41 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.86 0.00 01-JAN-00:10 9189.41 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.86 0.00 01-JAN-00:10 9189.41 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 40.12 0.00 01-JAN-00:10 7285.37 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 40.12 0.00 01-JAN-00:10 7285.37 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 40.21 0.00 01-JAN-00:10 8168.13 07-JUL-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.50 0.00 01-JAN-00:10 7734.20 13-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.50 0.00 01-JAN-00:10 7734.20 13-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 36.71 0.00 01-JAN-00:10 8168.13 07-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 36.71 0.00 01-JAN-00:10 8168.13 07-JUL-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 57.61 0.00 01-JAN-00:10 11008.16 10-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.20 0.00 01-JAN-00:10 10392.15 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.20 0.00 01-JAN-00:10 10392.15 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.42 0.00 01-JAN-00:10 11008.16 10-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 53.42 0.00 01-JAN-00:10 11008.16 10-OCT-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 40.78 0.00 01-JAN-00:10 8266.86 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 4.05 0.00 01-JAN-00:10 7673.26 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 4.05 0.00 01-JAN-00:10 7673.26 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 36.73 0.00 01-JAN-00:10 8266.86 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 36.73 0.00 01-JAN-00:10 8266.86 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 40.23 0.00 01-JAN-00:10 7040.50 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.74 0.00 01-JAN-00:10 7040.50 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.74 0.00 01-JAN-00:10 7040.50 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 37.49 0.00 01-JAN-00:10 5975.69 09-AUG-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 37.49 0.00 01-JAN-00:10 5975.69 09-AUG-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 35.35 0.00 01-JAN-00:10 6811.20 07-JUL-09:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.25 0.00 01-JAN-00:10 4893.80 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.25 0.00 01-JAN-00:10 4893.80 13-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 34.10 0.00 01-JAN-00:10 6811.20 07-JUL-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 34.10 0.00 01-JAN-00:10 6811.20 07-JUL-09:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 57.44 0.00 01-JAN-00:10 10548.87 03-FEB-07:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 8.22 0.00 01-JAN-00:10 10548.87 03-FEB-07:50
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 8.22 0.00 01-JAN-00:10 10548.87 03-FEB-07:50
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 49.22 0.00 01-JAN-00:10 10514.13 18-AUG-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 49.22 0.00 01-JAN-00:10 10514.13 18-AUG-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 34.39 0.00 01-JAN-00:10 6770.56 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.36 0.00 01-JAN-00:10 4888.54 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.36 0.00 01-JAN-00:10 4888.54 09-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 33.03 0.00 01-JAN-00:10 6770.56 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 33.03 0.00 01-JAN-00:10 6770.56 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 43.39 0.00 01-JAN-00:10 7833.97 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.87 0.00 01-JAN-00:10 7833.97 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.87 0.00 01-JAN-00:10 7833.97 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 40.52 0.00 01-JAN-00:10 6508.36 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 40.52 0.00 01-JAN-00:10 6508.36 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 38.04 0.00 01-JAN-00:10 7800.60 07-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.51 0.00 01-JAN-00:10 5559.46 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.51 0.00 01-JAN-00:10 5559.46 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 36.54 0.00 01-JAN-00:10 7800.60 07-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 36.54 0.00 01-JAN-00:10 7800.60 07-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 55.56 0.00 01-JAN-00:10 10112.34 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.56 0.00 01-JAN-00:10 8290.70 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.56 0.00 01-JAN-00:10 8290.70 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 54.00 0.00 01-JAN-00:10 10112.34 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 54.00 0.00 01-JAN-00:10 10112.34 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 38.06 0.00 01-JAN-00:10 7662.17 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.65 0.00 01-JAN-00:10 5586.24 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.65 0.00 01-JAN-00:10 5586.24 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 36.41 0.00 01-JAN-00:10 7662.17 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 36.41 0.00 01-JAN-00:10 7662.17 02-AUG-16:00
PlantLoopHeatingDemand:Facility 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
PlantLoopHeatingDemand:Plant 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
EnergyTransfer:HVAC 1431.26 0.00 01-JAN-00:10 254041.95 07-JUL-16:00
HeatingCoils:EnergyTransfer 124.85 0.00 01-JAN-00:10 195320.41 13-FEB-07:10
CoolingCoils:EnergyTransfer 1306.42 0.00 01-JAN-00:10 254041.95 07-JUL-16:00
EnergyTransfer:Plant 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterSystems:EnergyTransfer 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.004 -250.775 0.000 0.000 33.035 71.928 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -104.615
CORE_MID 0.000 0.000 0.397 -182.195 0.000 0.000 34.299 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -39.854
CORE_TOP 0.000 0.000 3.098 -176.845 0.000 0.000 34.989 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -48.596
PERIMETER_TOP_ZN_3 0.000 0.000 6.865 -40.117 0.000 0.000 7.484 9.014 24.333 18.207 0.000 0.135 2.148 0.000 -25.729 0.000 -2.339 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 3.500 -36.705 0.000 0.000 4.690 5.569 15.404 29.314 0.000 0.086 0.001 0.000 -15.802 0.000 -1.592 -4.465
PERIMETER_TOP_ZN_1 0.000 0.000 4.197 -53.415 0.000 0.000 7.283 8.686 24.332 51.464 0.000 0.125 0.000 0.000 -24.095 0.000 -2.498 -16.080
PERIMETER_TOP_ZN_4 0.000 0.000 4.049 -36.733 0.000 0.000 4.755 5.635 15.403 29.687 0.000 0.086 0.000 0.000 -16.899 0.000 -1.600 -4.382
PERIMETER_BOT_ZN_3 0.000 0.000 2.739 -37.486 0.000 0.000 7.445 8.972 24.333 18.522 0.000 0.078 3.721 0.000 -26.993 0.000 -1.330 -0.001
PERIMETER_BOT_ZN_2 0.000 0.000 1.248 -34.104 0.000 0.000 4.635 5.553 15.404 29.414 0.000 0.047 0.000 0.000 -16.908 0.000 -0.920 -4.367
PERIMETER_BOT_ZN_1 0.000 0.000 8.221 -49.216 0.000 0.000 7.341 8.665 24.332 51.968 0.000 3.949 0.001 0.000 -25.761 0.000 -20.340 -9.158
PERIMETER_BOT_ZN_4 0.000 0.000 1.358 -33.029 0.000 0.000 4.679 5.613 15.403 29.846 0.000 0.045 0.000 0.000 -18.113 0.000 -0.926 -4.878
PERIMETER_MID_ZN_3 0.000 0.000 2.869 -40.517 0.000 0.000 7.399 9.014 24.333 18.048 0.000 0.115 8.200 0.000 -27.375 0.000 -2.084 -0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.506 -36.536 0.000 0.000 3.441 5.569 15.404 29.151 0.000 0.074 0.000 0.000 -16.736 0.000 -1.413 -0.460
PERIMETER_MID_ZN_1 0.000 0.000 1.561 -53.996 0.000 0.000 7.193 8.686 24.332 51.204 0.000 0.106 0.002 0.000 -25.580 0.000 -2.220 -11.287
PERIMETER_MID_ZN_4 0.000 0.000 1.653 -36.408 0.000 0.000 4.694 5.635 15.403 29.563 0.000 0.071 0.000 0.000 -17.959 0.000 -1.423 -1.228
TOPFLOOR_PLENUM 11.372 -36.913 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.132 28.980 0.000 0.000 0.000 -3.571 -0.001
MIDFLOOR_PLENUM 3.927 -20.600 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.164 20.141 0.000 0.000 0.000 -3.633 -0.000
FIRSTFLOOR_PLENUM 2.482 -24.058 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.122 24.462 0.000 0.000 0.000 -3.007 -0.000
Total Facility 17.781 -81.571 43.266 -1098.078 0.000 0.000 173.359 302.396 719.689 386.386 0.000 5.336 87.658 0.000 -257.950 0.000 -48.897 -249.374


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 07-JUL-04:02 0.00 0.00 0.00 -40730.82 0.00 0.00 0.00 211.73 5642.06 0.00 0.00 0.00 34877.03 0.00 -0.00 0.00 0.00 0.00
CORE_MID 03-AUG-04:02 0.00 0.00 0.00 -32003.92 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 29350.13 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 14-AUG-04:02 0.00 0.00 0.00 -33566.09 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 30912.30 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 16-JUL-18:32 0.00 0.00 0.00 -11781.09 0.00 0.00 0.00 36.00 386.10 1803.05 0.00 44.08 9511.86 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 04-JUN-08:23 0.00 0.00 0.00 -11638.15 0.00 0.00 16.07 22.79 302.86 8311.94 0.00 0.00 3012.85 0.00 -0.00 0.00 -28.34 0.00
PERIMETER_TOP_ZN_1 09-OCT-14:23 0.00 0.00 0.00 -14408.66 0.00 0.00 25.35 36.00 478.41 8886.79 0.00 1.47 4980.64 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 11-JUN-16:02 0.00 0.00 0.00 -13305.60 0.00 0.00 14.94 22.79 302.86 7718.48 0.00 70.91 5175.63 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 09-AUG-15:00 0.00 0.00 0.00 -5975.60 0.00 0.00 737.23 647.98 1435.25 3958.96 0.00 6.79 0.00 0.00 -0.00 0.00 0.00 -810.61
PERIMETER_BOT_ZN_2 27-AUG-09:52 0.00 0.00 0.00 -10429.10 0.00 0.00 16.09 22.79 302.86 7172.39 0.00 0.00 2915.70 0.00 -0.00 0.00 -0.73 0.00
PERIMETER_BOT_ZN_1 09-OCT-14:13 0.00 0.00 0.00 -11980.98 0.00 0.00 25.47 36.00 478.41 9070.50 0.00 0.00 2371.88 0.00 -0.00 0.00 -1.28 0.00
PERIMETER_BOT_ZN_4 13-AUG-16:51 0.00 0.00 0.00 -11199.20 0.00 0.00 14.89 22.79 302.86 8059.71 0.00 14.29 2784.66 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 16-JUL-18:32 0.00 0.00 0.00 -8474.21 0.00 0.00 0.00 36.00 386.10 1884.01 0.00 38.88 6129.22 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 27-AUG-09:52 0.00 0.00 0.00 -11960.66 0.00 0.00 15.00 22.79 302.86 7090.83 0.00 0.00 4531.65 0.00 -0.00 0.00 -2.47 0.00
PERIMETER_MID_ZN_1 09-OCT-14:13 0.00 0.00 0.00 -12813.37 0.00 0.00 25.58 36.00 478.41 9058.84 0.00 0.00 3215.13 0.00 -0.00 0.00 -0.59 0.00
PERIMETER_MID_ZN_4 13-AUG-16:51 0.00 0.00 0.00 -12820.96 0.00 0.00 13.71 22.79 302.86 7982.39 0.00 18.95 4480.27 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 01-AUG-14:00 0.00 -10435.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.42 10394.71 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 17-JUL-06:03 0.00 -4500.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4508.81 0.00 -0.00 0.00 -7.99 0.00
FIRSTFLOOR_PLENUM 18-AUG-16:00 0.00 -4688.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.18 4652.44 0.00 -0.00 0.00 0.00 0.00
Total Facility 14-AUG-04:02 0.00 9146.87 0.00 -184171.47 0.00 0.00 0.00 1072.56 15570.33 0.00 0.00 0.00 163853.38 0.00 -5236.90 0.00 -234.76 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-07:02 0.00 0.00 15840.31 0.00 0.00 0.00 896.19 2148.02 10194.85 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -29079.37
CORE_MID 09-JAN-06:01 0.00 0.00 17479.65 0.00 0.00 0.00 500.42 211.73 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -21217.73
CORE_TOP 09-JAN-05:11 0.00 0.00 31039.72 0.00 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -33693.51
PERIMETER_TOP_ZN_3 12-FEB-07:23 0.00 0.00 10762.76 0.00 0.00 0.00 59.31 75.47 478.42 0.00 0.00 0.00 0.00 0.00 -3940.23 0.00 -811.00 -6624.72
PERIMETER_TOP_ZN_2 12-FEB-07:23 0.00 0.00 9680.77 0.00 0.00 0.00 37.59 47.78 302.86 0.00 0.00 0.00 0.00 0.00 -2534.63 0.00 -548.52 -6985.85
PERIMETER_TOP_ZN_1 12-FEB-06:03 0.00 0.00 12315.11 0.00 0.00 0.00 59.14 44.64 478.41 0.00 0.00 0.00 0.00 0.00 -3864.56 0.00 -1011.49 -8021.24
PERIMETER_TOP_ZN_4 12-FEB-07:23 0.00 0.00 9683.08 0.00 0.00 0.00 37.59 47.77 302.86 0.00 0.00 0.00 0.00 0.00 -2627.83 0.00 -548.54 -6894.93
PERIMETER_BOT_ZN_3 13-FEB-05:01 0.00 0.00 8193.74 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3203.39 0.00 -367.10 -5182.69
PERIMETER_BOT_ZN_2 13-FEB-05:01 0.00 0.00 6811.97 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2173.32 0.00 -250.44 -4742.36
PERIMETER_BOT_ZN_1 03-FEB-07:10 0.00 0.00 10726.88 0.00 0.00 0.00 193.30 452.82 637.88 0.00 0.00 0.00 11926.17 0.00 -4063.02 0.00 -19874.04 0.00
PERIMETER_BOT_ZN_4 09-JAN-05:02 0.00 0.00 6811.79 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1802.71 0.00 -165.76 -5197.47
PERIMETER_MID_ZN_3 09-JAN-05:11 0.00 0.00 8968.72 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -2596.59 0.00 -363.11 -6568.46
PERIMETER_MID_ZN_2 09-JAN-05:11 0.00 0.00 7193.84 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1678.18 0.00 -243.32 -5626.49
PERIMETER_MID_ZN_1 09-JAN-05:11 0.00 0.00 10513.64 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -2543.77 0.00 -366.49 -8162.81
PERIMETER_MID_ZN_4 09-JAN-05:11 0.00 0.00 7235.28 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1727.93 0.00 -243.19 -5618.30
TOPFLOOR_PLENUM 13-FEB-06:12 14122.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -264.38 -13857.89
MIDFLOOR_PLENUM 09-JAN-07:06 7676.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -167.05 -7509.47
FIRSTFLOOR_PLENUM 09-JAN-07:01 3814.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -134.90 -3679.41
Total Facility 09-JAN-07:01 21228.04 0.00 139716.78 0.00 0.00 0.00 4626.03 10880.98 22496.85 0.00 0.00 0.00 0.00 0.00 -30574.03 0.00 -21125.47 -147249.18



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 5.2148 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.7223 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 4.9458 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.3541 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.3708 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.0724 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.6074 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3375 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.4729 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.3437 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.6854 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.4105 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7199 2.7199 0.7697 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2019 2.2019 0.7530 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3409 2.3409 0.7842 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7260 0.7260 0.1655 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6961 0.6961 0.1392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8405 0.8405 0.1681 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7672 0.7672 0.1534 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5880 0.5880 0.1623 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5987 0.5987 0.1197 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6889 0.6889 0.1619 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6194 0.6194 0.1239 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6311 0.6311 0.1584 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6704 0.6704 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7450 0.7450 0.1587 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6974 0.6974 0.1395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 5.2148 4.7223 5.2148 1.3375 0.0000 1.0000
PACU_VAV_MID 4.9458 4.3541 4.9458 1.3437 0.0000 1.0000
PACU_VAV_TOP 5.3708 5.0724 5.3708 1.4105 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3599 1.3599 0.7697 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1009 1.1009 0.7530 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1705 1.1705 0.7842 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3630 0.3630 0.1655 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3480 0.3480 0.1392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4203 0.4203 0.1681 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3836 0.3836 0.1534 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2940 0.2940 0.1623 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2993 0.2993 0.1197 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3444 0.3444 0.1619 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3097 0.3097 0.1239 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3156 0.3156 0.1584 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3352 0.3352 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3725 0.3725 0.1587 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3487 0.3487 0.1395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.6074 1.3375 1.3375 1.3375 0.0000 1.0000
PACU_VAV_MID 2.4729 1.3437 1.3437 1.3437 0.0000 1.0000
PACU_VAV_TOP 2.6854 1.4105 1.4105 1.4105 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 4982.19
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 128.50
Number of hours cooling loads not met 115.67
Number of hours not met 244.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 124.85 195320.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 305.46 70815.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 302.40 32642.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 51.35 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.91 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 71.99 14770.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.15 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 48.15 6214.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1650.93
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 719.69 1650.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 60.70
Space Heating 25.06
Space Cooling 61.31
Fans (All) 14.45
Service Water Heating 9.66
Receptacle Equipment 144.45
Miscellaneous (All) 331.37
Subtotal 331.37


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 18.32
Space Heating 7.56
Space Cooling 18.50
Fans (All) 4.36
Service Water Heating 2.92
Receptacle Equipment 43.59
Miscellaneous 4.75


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 1574. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8395.33 364.67 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8745.17 14.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8701.50 58.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8716.67 43.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8684.17 75.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8757.33 2.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8716.83 43.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8737.50 22.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8713.83 46.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8754.83 5.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8714.17 45.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8727.33 32.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8692.67 67.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 8611.00 149.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8395.33 0.00 0.00 0.00 0.00
Max 8760.00 364.67 0.00 0.00 0.00
Average 8706.02 53.98 0.00 0.00 0.00
Sum 156708.33 971.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128177.67 126.33 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 126.33 0.00 0.00 0.00
Average 34136.31 7.02 0.00 0.00 0.00
Sum 614453.67 126.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8240.83 519.17 0.00 0.00 0.00
CORE_MID 8758.50 1.50 0.00 0.00 0.00
CORE_TOP 8758.33 1.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8224.17 535.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8185.17 574.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8199.33 560.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8163.17 596.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8403.67 356.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8256.67 503.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8164.17 595.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8220.33 539.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8210.33 549.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8167.17 592.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8178.67 581.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8117.83 642.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 8519.33 240.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8618.17 141.83 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8645.33 114.67 0.00 0.00 0.00
Min 8117.83 1.50 0.00 0.00 0.00
Max 8758.50 642.17 0.00 0.00 0.00
Average 8335.06 424.94 0.00 0.00 0.00
Sum 150031.17 7648.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128085.67 218.33 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128303.67 0.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24903.67 5.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24903.83 5.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24907.00 2.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 23945.17 963.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24903.00 6.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24903.00 6.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 963.83 0.00 0.00 0.00
Average 34076.28 67.06 0.00 0.00 0.00
Sum 613373.00 1207.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:14

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124119E+11 12522.50 31-JAN-17:00 19.40 13.37 0.180201E+10 2606.39 31-JAN-14:00 19.40 13.37
February 0.128248E+11 17977.16 28-FEB-17:00 23.90 12.94 0.171281E+10 2606.64 22-FEB-14:09 23.90 12.94
March 0.189853E+11 21022.54 31-MAR-06:03 17.30 16.12 0.214912E+10 2606.71 08-MAR-10:09 17.30 16.12
April 0.197647E+11 30348.25 18-APR-06:03 13.30 12.06 0.191598E+10 2606.62 17-APR-09:09 13.30 12.06
May 0.242797E+11 35859.96 30-MAY-06:03 20.78 18.26 0.207879E+10 2606.72 11-MAY-09:00 20.78 18.26
June 0.270917E+11 38483.59 26-JUN-05:12 23.30 21.67 0.207195E+10 2606.67 09-JUN-09:00 23.30 21.67
July 0.273470E+11 40732.33 07-JUL-04:02 25.22 21.53 0.192641E+10 2606.54 03-JUL-09:09 25.22 21.53
August 0.297441E+11 40723.27 03-AUG-04:02 23.90 22.21 0.216165E+10 2606.53 25-AUG-13:09 30.18 18.86
September 0.252770E+11 36090.67 18-SEP-06:02 14.50 13.76 0.192001E+10 2606.65 15-SEP-09:00 14.50 13.76
October 0.216297E+11 35125.05 10-OCT-06:02 15.00 14.30 0.199152E+10 2606.60 04-OCT-13:00 15.00 14.30
November 0.173694E+11 20107.09 06-NOV-17:00 18.90 9.61 0.196401E+10 2606.75 16-NOV-10:09 10.68 10.03
December 0.140501E+11 16630.37 14-DEC-17:00 13.90 10.25 0.186452E+10 2606.56 13-DEC-10:09 13.90 10.25
                     
Annual Sum or Average 0.250775E+12         0.235588E+11        
Minimum of Months 0.124119E+11 12522.50   13.30 9.61 0.171281E+10 2606.39   10.68 10.03
Maximum of Months 0.297441E+11 40732.33   25.22 22.21 0.216165E+10 2606.75   30.18 21.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157433E+09 1586.00 28-JAN-17:25 11.40 4.15 0.00 0.00 01-JAN-00:10 11.40 4.15
February 0.555100E+09 3588.69 26-FEB-14:07 24.50 12.58 0.00 0.00 01-FEB-00:10 24.50 12.58
March 0.166994E+10 6839.98 30-MAR-14:50 27.80 17.21 0.00 0.00 01-MAR-00:10 27.80 17.21
April 0.285854E+10 7782.06 17-APR-15:10 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.449706E+10 8642.68 30-MAY-15:00 30.60 21.44 0.00 0.00 01-MAY-00:10 30.60 21.44
June 0.632473E+10 9260.24 27-JUN-14:40 32.20 23.14 0.00 0.00 01-JUN-00:10 32.20 23.14
July 0.673533E+10 10318.28 07-JUL-15:20 35.20 23.90 0.00 0.00 01-JUL-00:10 35.20 23.90
August 0.700866E+10 10435.40 01-AUG-14:00 33.90 23.66 0.00 0.00 01-AUG-00:10 33.90 23.66
September 0.393205E+10 8963.05 06-SEP-14:20 30.53 23.42 0.00 0.00 01-SEP-00:10 30.53 23.42
October 0.200119E+10 6841.69 10-OCT-14:40 29.07 20.78 0.00 0.00 01-OCT-00:10 29.07 20.78
November 0.853317E+09 3359.21 05-NOV-14:43 23.80 18.47 0.00 0.00 01-NOV-00:10 23.80 18.47
December 0.320352E+09 2489.44 10-DEC-14:40 17.77 8.37 0.00 0.00 01-DEC-00:10 17.77 8.37
                     
Annual Sum or Average 0.369137E+11         0.00        
Minimum of Months 0.157433E+09 1586.00   11.40 4.15 0.00 0.00   11.40 4.15
Maximum of Months 0.700866E+10 10435.40   35.20 23.90 0.00 0.00   35.20 23.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 68376953.79 1927.05 14-JAN-06:01 -6.7 -7.8 0.00 0.00 01-JAN-00:10 -6.7 -7.8
February 0.226511E+09 2142.33 03-FEB-06:01 -8.4 -9.9 0.00 0.00 01-FEB-00:10 -8.4 -9.9
March 0.815164E+09 2225.04 30-MAR-16:00 27.80 17.47 0.00 0.00 01-MAR-00:10 27.80 17.47
April 0.138618E+10 3028.98 06-APR-06:02 1.20 -0.4 0.00 0.00 01-APR-00:10 1.20 -0.4
May 0.233532E+10 3624.57 30-MAY-15:30 29.20 21.54 0.00 0.00 01-MAY-00:10 29.20 21.54
June 0.346679E+10 3981.13 26-JUN-06:03 23.30 21.67 0.00 0.00 01-JUN-00:10 23.30 21.67
July 0.383225E+10 4501.11 17-JUL-06:03 21.70 19.38 0.00 0.00 01-JUL-00:10 21.70 19.38
August 0.414782E+10 4289.30 02-AUG-16:00 35.00 23.13 0.00 0.00 01-AUG-00:10 35.00 23.13
September 0.255057E+10 3935.45 07-SEP-16:00 31.70 23.71 0.00 0.00 01-SEP-00:10 31.70 23.71
October 0.117305E+10 2710.89 11-OCT-16:00 26.10 17.12 0.00 0.00 01-OCT-00:10 26.10 17.12
November 0.425842E+09 1808.33 08-NOV-07:03 4.40 1.76 0.00 0.00 01-NOV-00:10 4.40 1.76
December 0.172344E+09 2067.57 09-DEC-06:11 2.20 -1.0 0.00 0.00 01-DEC-00:10 2.20 -1.0
                     
Annual Sum or Average 0.206002E+11         0.00        
Minimum of Months 68376953.79 1808.33   -8.4 -9.9 0.00 0.00   -8.4 -9.9
Maximum of Months 0.414782E+10 4501.11   35.00 23.71 0.00 0.00   35.00 23.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 75211070.89 1763.09 13-JAN-06:11 3.90 2.25 0.00 0.00 01-JAN-00:10 3.90 2.25
February 0.278948E+09 2471.41 23-FEB-07:03 5.00 3.70 0.00 0.00 01-FEB-00:10 5.00 3.70
March 0.108957E+10 2582.88 06-MAR-07:03 2.80 0.11 0.00 0.00 01-MAR-00:10 2.80 0.11
April 0.168206E+10 3140.24 06-APR-06:02 1.20 -0.4 0.00 0.00 01-APR-00:10 1.20 -0.4
May 0.262879E+10 3959.92 30-MAY-15:20 29.67 21.52 0.00 0.00 01-MAY-00:10 29.67 21.52
June 0.380131E+10 4178.93 26-JUN-15:30 30.00 23.57 0.00 0.00 01-JUN-00:10 30.00 23.57
July 0.419615E+10 4662.67 10-JUL-15:50 32.70 22.31 0.00 0.00 01-JUL-00:10 32.70 22.31
August 0.467106E+10 4688.62 18-AUG-16:00 35.00 23.11 0.00 0.00 01-AUG-00:10 35.00 23.11
September 0.317043E+10 4587.76 11-SEP-16:00 30.00 22.85 0.00 0.00 01-SEP-00:10 30.00 22.85
October 0.164139E+10 3550.87 11-OCT-16:00 26.10 17.12 0.00 0.00 01-OCT-00:10 26.10 17.12
November 0.610153E+09 1933.14 21-NOV-07:01 -2.8 -3.9 0.00 0.00 01-NOV-00:10 -2.8 -3.9
December 0.213097E+09 2238.72 15-DEC-07:03 3.22 0.92 0.00 0.00 01-DEC-00:10 3.22 0.92
                     
Annual Sum or Average 0.240582E+11         0.00        
Minimum of Months 75211070.89 1763.09   -2.8 -3.9 0.00 0.00   -2.8 -3.9
Maximum of Months 0.467106E+10 4688.62   35.00 23.57 0.00 0.00   35.00 23.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.832784E+10 8954.73 31-JAN-17:00 19.40 13.37 0.154467E+10 2296.12 31-JAN-14:00 19.40 13.37
February 0.942843E+10 10784.10 28-FEB-17:00 23.90 12.94 0.149469E+10 2591.45 28-FEB-14:00 23.90 12.94
March 0.139616E+11 14149.26 30-MAR-16:00 27.80 17.47 0.201175E+10 2606.60 13-MAR-13:00 27.80 17.47
April 0.145352E+11 15068.27 18-APR-16:00 25.60 16.92 0.186336E+10 2606.61 17-APR-09:09 25.60 16.92
May 0.179254E+11 17207.12 30-MAY-16:00 27.80 21.50 0.205820E+10 2606.71 24-MAY-09:09 27.80 21.50
June 0.202139E+11 29557.58 26-JUN-05:12 23.30 21.67 0.206203E+10 2606.67 09-JUN-09:50 23.30 21.67
July 0.206021E+11 31415.80 07-JUL-04:02 25.22 21.53 0.191776E+10 2606.56 03-JUL-09:09 25.22 21.53
August 0.221395E+11 32004.97 03-AUG-04:02 23.90 22.21 0.215520E+10 2606.54 25-AUG-09:09 24.97 18.13
September 0.179309E+11 17698.49 11-SEP-06:03 19.50 18.37 0.190392E+10 2606.61 21-SEP-09:09 20.97 17.73
October 0.147431E+11 15679.81 11-OCT-16:00 26.10 17.12 0.191038E+10 2606.58 10-OCT-09:39 26.10 17.12
November 0.120463E+11 11741.33 06-NOV-17:00 18.90 9.61 0.178721E+10 2606.48 07-NOV-14:00 18.90 8.70
December 0.103409E+11 9775.03 13-DEC-17:00 16.70 16.70 0.158615E+10 2516.83 13-DEC-14:00 16.70 16.70
                     
Annual Sum or Average 0.182195E+12         0.222953E+11        
Minimum of Months 0.832784E+10 8954.73   16.70 9.61 0.149469E+10 2296.12   16.70 8.70
Maximum of Months 0.221395E+11 32004.97   27.80 22.21 0.215520E+10 2606.71   27.80 21.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.617929E+10 9120.56 20-JAN-17:00 16.70 11.48 0.148748E+10 2222.44 31-JAN-14:00 21.10 12.97
February 0.785765E+10 10610.98 28-FEB-17:00 23.90 12.94 0.142045E+10 2539.06 28-FEB-14:00 23.90 12.94
March 0.134536E+11 16101.24 30-MAR-16:00 27.80 17.47 0.190356E+10 2606.56 29-MAR-13:00 27.80 17.47
April 0.145290E+11 17150.42 17-APR-16:00 28.90 16.41 0.180573E+10 2606.62 12-APR-13:50 28.90 16.41
May 0.183687E+11 19397.47 30-MAY-15:30 29.20 21.54 0.203692E+10 2606.63 22-MAY-09:39 29.20 21.54
June 0.212679E+11 32434.12 26-JUN-05:12 23.30 21.67 0.205586E+10 2606.65 06-JUN-09:09 23.30 21.67
July 0.218326E+11 33163.23 07-JUL-04:02 25.22 21.53 0.191485E+10 2606.61 03-JUL-09:09 25.22 21.53
August 0.232736E+11 33562.07 14-AUG-04:02 24.22 20.90 0.215245E+10 2606.64 25-AUG-09:50 27.23 18.71
September 0.177465E+11 19449.84 07-SEP-16:00 31.70 23.71 0.188321E+10 2606.67 25-SEP-09:09 24.78 19.25
October 0.137939E+11 16567.35 11-OCT-16:00 26.10 17.12 0.181717E+10 2606.60 11-OCT-09:00 26.10 17.12
November 0.107716E+11 10317.21 06-NOV-17:00 18.90 9.61 0.164271E+10 2542.22 06-NOV-14:00 18.90 9.61
December 0.777041E+10 9805.13 13-DEC-17:00 16.70 16.70 0.148499E+10 2425.50 13-DEC-14:00 16.70 16.70
                     
Annual Sum or Average 0.176845E+12         0.216054E+11        
Minimum of Months 0.617929E+10 9120.56   16.70 9.61 0.142045E+10 2222.44   16.70 9.61
Maximum of Months 0.232736E+11 33562.07   31.70 23.71 0.215245E+10 2606.67   29.20 21.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.357369E+09 1879.57 31-JAN-16:50 19.50 13.40 0.308018E+09 465.52 31-JAN-14:00 19.50 13.40
February 0.865568E+09 2529.64 28-FEB-15:40 23.87 12.92 0.289403E+09 549.47 28-FEB-14:00 23.87 12.92
March 0.239130E+10 4688.03 30-MAR-15:50 27.80 17.41 0.380757E+09 549.48 29-MAR-13:00 27.80 17.41
April 0.311742E+10 5065.85 19-APR-14:30 26.15 17.54 0.367294E+09 549.49 12-APR-13:50 26.15 17.54
May 0.463260E+10 6513.62 30-MAY-15:00 30.60 21.44 0.424976E+09 549.49 19-MAY-09:39 30.60 21.44
June 0.626199E+10 7512.76 25-JUN-18:53 29.40 22.34 0.433617E+09 549.50 02-JUN-09:00 29.40 22.34
July 0.653065E+10 11780.92 16-JUL-18:32 31.67 22.10 0.404446E+09 549.48 03-JUL-09:09 31.67 22.10
August 0.679469E+10 8410.81 20-AUG-16:42 27.88 24.54 0.454295E+09 549.49 25-AUG-09:50 27.23 18.71
September 0.428208E+10 6347.10 06-SEP-14:30 30.25 23.24 0.392534E+09 549.50 25-SEP-09:20 25.17 19.30
October 0.260031E+10 4395.39 02-OCT-14:40 26.70 20.10 0.363774E+09 549.47 19-OCT-13:39 23.33 19.60
November 0.156694E+10 2158.84 02-NOV-15:50 22.30 16.05 0.326181E+09 529.81 03-NOV-13:00 21.70 17.40
December 0.716846E+09 2011.61 13-DEC-15:00 18.30 16.86 0.301250E+09 501.20 13-DEC-14:00 18.30 16.86
                     
Annual Sum or Average 0.401178E+11         0.444655E+10        
Minimum of Months 0.357369E+09 1879.57   18.30 12.92 0.289403E+09 465.52   18.30 12.92
Maximum of Months 0.679469E+10 11780.92   31.67 24.54 0.454295E+09 549.50   31.67 22.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.443221E+09 1547.08 31-JAN-15:10 20.92 13.08 0.195149E+09 291.63 31-JAN-14:00 20.92 13.08
February 0.894653E+09 2184.68 27-FEB-10:40 14.27 6.32 0.189010E+09 347.86 28-FEB-14:09 25.00 13.72
March 0.219434E+10 3653.22 30-MAR-11:00 22.20 17.83 0.253269E+09 347.88 08-MAR-10:09 22.20 17.83
April 0.306888E+10 7866.22 16-APR-10:02 22.85 14.78 0.243184E+09 347.88 12-APR-13:50 22.85 14.78
May 0.435313E+10 11629.01 07-MAY-09:23 24.15 19.65 0.271550E+09 347.89 11-MAY-09:00 17.20 13.27
June 0.549544E+10 11635.36 04-JUN-08:23 23.30 17.57 0.275161E+09 347.88 09-JUN-09:00 24.40 15.46
July 0.575600E+10 11628.06 02-JUL-10:02 26.28 22.27 0.255885E+09 347.86 03-JUL-09:09 25.60 20.69
August 0.585461E+10 10983.14 27-AUG-10:02 27.77 22.01 0.287532E+09 347.88 25-AUG-09:50 27.77 22.01
September 0.400152E+10 9326.65 24-SEP-10:43 27.52 19.23 0.249488E+09 347.88 25-SEP-09:30 25.55 19.33
October 0.240855E+10 4472.78 11-OCT-10:30 24.20 19.54 0.239529E+09 347.87 11-OCT-09:00 24.20 19.54
November 0.145933E+10 1868.30 06-NOV-10:40 16.27 12.91 0.211440E+09 347.84 06-NOV-10:00 17.20 13.02
December 0.776335E+09 1641.63 12-DEC-15:10 22.70 16.14 0.191887E+09 308.05 12-DEC-14:00 22.70 16.14
                     
Annual Sum or Average 0.367060E+11         0.286308E+10        
Minimum of Months 0.443221E+09 1547.08   14.27 6.32 0.189010E+09 291.63   17.20 13.02
Maximum of Months 0.585461E+10 11635.36   27.77 22.27 0.287532E+09 347.89   27.77 22.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135530E+10 4693.13 11-JAN-14:30 6.70 2.05 0.341109E+09 549.47 05-JAN-14:00 6.70 2.05
February 0.192639E+10 13787.20 26-FEB-14:32 24.80 12.68 0.317773E+09 549.49 21-FEB-14:00 24.80 12.68
March 0.370347E+10 9614.19 30-MAR-13:40 27.43 17.97 0.407117E+09 549.50 13-MAR-13:00 27.43 17.97
April 0.421227E+10 13094.67 16-APR-14:02 28.62 16.11 0.376928E+09 549.53 12-APR-13:50 28.62 16.11
May 0.527135E+10 7824.51 29-MAY-13:02 28.80 20.58 0.424826E+09 549.49 15-MAY-13:09 28.80 20.58
June 0.647590E+10 8968.21 25-JUN-16:12 33.13 22.15 0.432520E+09 549.50 02-JUN-13:09 33.13 22.15
July 0.686686E+10 13554.27 16-JUL-13:53 33.90 23.22 0.404272E+09 549.48 03-JUL-09:09 33.90 23.22
August 0.796549E+10 13996.96 20-AUG-14:02 28.77 24.15 0.454531E+09 549.49 25-AUG-09:50 27.23 18.71
September 0.595578E+10 14325.03 24-SEP-14:02 28.40 19.93 0.395129E+09 549.50 22-SEP-13:50 28.40 19.93
October 0.465783E+10 14407.92 09-OCT-14:23 27.50 19.51 0.386342E+09 549.49 04-OCT-13:00 27.50 19.51
November 0.303544E+10 14006.45 11-NOV-14:23 21.10 11.76 0.365173E+09 549.49 14-NOV-14:00 20.00 9.44
December 0.198982E+10 6339.95 08-DEC-14:10 12.80 5.52 0.342115E+09 549.47 07-DEC-14:00 12.80 5.52
                     
Annual Sum or Average 0.534159E+11         0.464784E+10        
Minimum of Months 0.135530E+10 4693.13   6.70 2.05 0.317773E+09 549.47   6.70 2.05
Maximum of Months 0.796549E+10 14407.92   33.90 24.15 0.454531E+09 549.53   33.90 23.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.494610E+09 1807.67 20-JAN-16:40 16.87 11.91 0.196492E+09 302.31 11-JAN-16:49 16.87 11.91
February 0.921603E+09 4229.84 27-FEB-17:00 22.20 11.44 0.184859E+09 347.50 28-FEB-14:00 25.00 13.71
March 0.241750E+10 6374.77 30-MAR-16:00 27.80 17.47 0.239468E+09 347.84 29-MAR-13:00 27.80 17.47
April 0.323048E+10 11819.88 09-APR-17:33 21.30 11.08 0.228056E+09 347.85 12-APR-13:00 28.90 17.10
May 0.433264E+10 11759.97 21-MAY-18:23 24.75 19.04 0.263270E+09 347.84 22-MAY-09:50 22.43 19.37
June 0.530095E+10 13305.25 11-JUN-16:02 32.70 21.37 0.271708E+09 347.85 02-JUN-09:00 32.70 21.37
July 0.549900E+10 13218.32 23-JUL-18:32 28.50 21.82 0.254323E+09 347.84 03-JUL-09:09 28.50 21.82
August 0.576557E+10 13200.41 13-AUG-17:02 31.10 22.35 0.286242E+09 347.84 25-AUG-09:00 27.80 18.82
September 0.395943E+10 8983.04 17-SEP-17:23 24.70 20.50 0.243777E+09 347.84 19-SEP-13:09 24.90 16.60
October 0.254118E+10 6631.95 11-OCT-16:00 26.10 17.12 0.227610E+09 347.83 16-OCT-13:00 25.00 19.11
November 0.150730E+10 3847.37 06-NOV-16:00 20.60 10.48 0.208462E+09 347.80 06-NOV-14:00 20.60 10.48
December 0.764315E+09 1946.68 11-DEC-16:00 21.10 15.91 0.193442E+09 323.54 11-DEC-16:10 21.02 15.88
                     
Annual Sum or Average 0.367346E+11         0.279771E+10        
Minimum of Months 0.494610E+09 1807.67   16.87 10.48 0.184859E+09 302.31   16.87 10.48
Maximum of Months 0.576557E+10 13305.25   32.70 22.35 0.286242E+09 347.85   32.70 21.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.408946E+09 1780.93 31-JAN-16:40 19.60 13.44 0.308925E+09 454.53 31-JAN-14:00 19.60 13.44
February 0.912013E+09 2032.48 28-FEB-15:20 24.43 13.32 0.288164E+09 518.15 28-FEB-14:00 24.43 13.32
March 0.226554E+10 2722.38 30-MAR-16:00 27.80 17.47 0.372879E+09 549.47 30-MAR-13:09 27.80 17.47
April 0.253382E+10 3045.32 19-APR-14:30 26.15 17.54 0.355811E+09 549.47 20-APR-13:00 23.90 16.60
May 0.347695E+10 4627.94 30-MAY-15:00 30.60 21.44 0.421702E+09 549.48 18-MAY-09:20 30.60 21.44
June 0.512220E+10 5399.13 28-JUN-14:30 30.85 23.20 0.434110E+09 549.49 09-JUN-09:00 30.85 23.20
July 0.566254E+10 5936.11 10-JUL-15:30 32.50 22.22 0.404624E+09 549.48 03-JUL-09:09 32.50 22.22
August 0.621877E+10 5975.69 09-AUG-15:00 32.80 23.20 0.454724E+09 549.47 18-AUG-13:00 33.30 22.95
September 0.433889E+10 5675.74 06-SEP-14:30 30.25 23.24 0.400468E+09 549.49 15-SEP-09:00 23.90 16.09
October 0.306510E+10 4078.61 02-OCT-14:30 26.70 20.05 0.386642E+09 549.47 05-OCT-13:09 20.00 14.95
November 0.225629E+10 2247.97 05-NOV-12:53 22.20 18.11 0.349792E+09 543.79 03-NOV-13:00 22.20 18.11
December 0.122546E+10 1996.32 13-DEC-13:30 19.45 17.14 0.307829E+09 505.85 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.374865E+11         0.448567E+10        
Minimum of Months 0.408946E+09 1780.93   19.45 13.32 0.288164E+09 454.53   18.30 13.32
Maximum of Months 0.621877E+10 5975.69   32.80 23.24 0.454724E+09 549.49   33.30 23.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.521503E+09 1350.15 31-JAN-15:00 21.10 12.97 0.197104E+09 296.01 31-JAN-14:00 21.10 12.97
February 0.882389E+09 1947.91 27-FEB-10:40 14.27 6.32 0.190881E+09 347.87 28-FEB-10:00 20.60 11.95
March 0.194473E+10 2651.78 14-MAR-11:00 20.60 15.46 0.254562E+09 347.88 08-MAR-10:20 20.60 15.46
April 0.235101E+10 4358.38 17-APR-10:10 23.27 15.57 0.242402E+09 347.87 17-APR-09:09 23.27 15.57
May 0.337499E+10 7219.48 07-MAY-09:23 24.15 19.65 0.272153E+09 347.89 11-MAY-09:00 17.20 13.27
June 0.467864E+10 8365.43 11-JUN-10:02 25.28 14.81 0.275749E+09 347.88 09-JUN-09:00 25.28 14.81
July 0.512568E+10 10184.10 04-JUL-09:52 27.20 23.54 0.256622E+09 347.86 17-JUL-09:00 27.80 22.02
August 0.547793E+10 10427.76 27-AUG-09:52 27.20 21.81 0.288290E+09 347.86 18-AUG-13:00 27.20 21.81
September 0.400396E+10 6326.20 08-SEP-09:30 26.65 22.11 0.254198E+09 347.88 15-SEP-09:00 23.90 16.09
October 0.273633E+10 4477.17 10-OCT-10:20 24.23 18.95 0.252028E+09 347.87 04-OCT-13:00 24.23 18.95
November 0.183288E+10 2491.47 06-NOV-10:10 14.87 12.62 0.233391E+09 347.87 08-NOV-10:09 12.25 6.43
December 0.117476E+10 1480.98 13-DEC-12:00 20.00 17.41 0.200974E+09 321.05 13-DEC-10:00 20.00 17.41
                     
Annual Sum or Average 0.341048E+11         0.291835E+10        
Minimum of Months 0.521503E+09 1350.15   14.27 6.32 0.190881E+09 296.01   12.25 6.43
Maximum of Months 0.547793E+10 10427.76   27.20 23.54 0.288290E+09 347.89   27.80 22.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.897642E+09 2752.56 28-JAN-14:40 11.67 4.40 0.317249E+09 532.20 31-JAN-14:50 21.02 13.03
February 0.138893E+10 9592.97 26-FEB-14:32 24.80 12.68 0.301969E+09 549.50 28-FEB-10:00 20.60 11.95
March 0.274531E+10 7774.39 30-MAR-16:10 27.62 17.53 0.394131E+09 549.50 13-MAR-13:00 27.62 17.53
April 0.304919E+10 7892.78 17-APR-16:10 28.80 16.45 0.363742E+09 549.51 12-APR-13:39 28.80 16.45
May 0.407314E+10 9042.73 30-MAY-12:00 29.40 21.24 0.415956E+09 549.49 09-MAY-13:09 29.40 21.24
June 0.607471E+10 9864.54 06-JUN-16:20 33.90 21.85 0.431568E+09 567.21 06-JUN-12:09 33.90 21.85
July 0.676155E+10 10295.70 07-JUL-16:10 35.50 23.98 0.404529E+09 591.68 14-JUL-12:09 33.40 24.44
August 0.832811E+10 11343.71 27-AUG-13:53 31.70 22.32 0.456556E+09 617.41 18-AUG-12:09 31.70 22.32
September 0.623766E+10 10184.63 07-SEP-12:00 31.10 23.22 0.399709E+09 595.87 07-SEP-12:09 31.02 23.18
October 0.467581E+10 11980.45 09-OCT-14:13 27.40 19.48 0.394841E+09 585.23 10-OCT-13:00 29.40 21.05
November 0.305605E+10 11569.44 11-NOV-13:53 21.10 11.67 0.374048E+09 549.49 21-NOV-14:20 9.27 3.66
December 0.192902E+10 5911.67 12-DEC-13:50 22.52 17.00 0.335507E+09 549.49 04-DEC-14:09 22.52 17.00
                     
Annual Sum or Average 0.492171E+11         0.458980E+10        
Minimum of Months 0.897642E+09 2752.56   11.67 4.40 0.301969E+09 532.20   9.27 3.66
Maximum of Months 0.832811E+10 11980.45   35.50 23.98 0.456556E+09 617.41   33.90 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500511E+09 1459.65 23-JAN-17:00 10.00 3.54 0.197690E+09 302.58 23-JAN-16:00 10.00 3.54
February 0.864726E+09 3101.61 27-FEB-17:00 22.20 11.44 0.186241E+09 345.74 28-FEB-14:00 25.00 13.71
March 0.204595E+10 4311.14 30-MAR-16:00 27.80 17.47 0.244080E+09 347.83 30-MAR-13:09 27.80 17.47
April 0.237616E+10 4904.03 17-APR-16:00 28.90 16.41 0.230555E+09 347.83 20-APR-13:00 23.90 16.60
May 0.320600E+10 7058.10 29-MAY-16:03 30.00 20.55 0.267410E+09 347.84 22-MAY-09:09 30.00 20.55
June 0.439905E+10 10543.48 04-JUN-16:32 31.50 19.59 0.274782E+09 347.85 09-JUN-09:00 24.40 15.46
July 0.477440E+10 10831.42 04-JUL-17:52 30.60 22.43 0.256266E+09 347.84 03-JUL-09:09 30.60 22.43
August 0.531644E+10 11198.16 13-AUG-16:51 31.10 22.45 0.288210E+09 347.84 21-AUG-09:09 23.40 22.58
September 0.383415E+10 8989.00 04-SEP-16:42 28.22 22.25 0.253690E+09 347.85 15-SEP-09:00 23.90 16.09
October 0.271621E+10 8608.05 09-OCT-16:53 26.70 19.37 0.247506E+09 347.84 10-OCT-09:09 21.05 17.87
November 0.189760E+10 3870.44 06-NOV-16:30 19.75 10.05 0.227291E+09 347.82 15-NOV-14:00 21.70 11.58
December 0.109805E+10 1628.40 11-DEC-16:10 21.02 15.88 0.199850E+09 335.47 12-DEC-14:50 22.80 16.32
                     
Annual Sum or Average 0.330292E+11         0.287357E+10        
Minimum of Months 0.500511E+09 1459.65   10.00 3.54 0.186241E+09 302.58   10.00 3.54
Maximum of Months 0.531644E+10 11198.16   31.50 22.45 0.288210E+09 347.85   30.60 22.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.496577E+09 1837.19 31-JAN-16:50 19.50 13.40 0.310220E+09 477.26 31-JAN-14:00 19.50 13.40
February 0.109530E+10 2570.82 28-FEB-15:30 24.15 13.12 0.294564E+09 549.47 28-FEB-14:30 24.15 13.12
March 0.264179E+10 4181.98 30-MAR-16:00 27.80 17.47 0.395427E+09 549.47 29-MAR-13:00 27.80 17.47
April 0.311720E+10 4616.96 18-APR-14:00 27.20 15.86 0.377957E+09 549.49 12-APR-13:39 27.20 15.86
May 0.444156E+10 5906.83 30-MAY-15:00 30.60 21.44 0.430933E+09 549.50 24-MAY-09:09 30.60 21.44
June 0.592022E+10 7038.03 26-JUN-05:12 23.30 21.67 0.435107E+09 549.50 09-JUN-09:50 23.30 21.67
July 0.614273E+10 8473.77 16-JUL-18:32 31.67 22.10 0.405047E+09 549.48 03-JUL-09:09 31.67 22.10
August 0.644393E+10 7978.78 14-AUG-04:02 24.22 20.90 0.454879E+09 549.47 18-AUG-13:00 33.30 22.95
September 0.425345E+10 5789.69 06-SEP-14:30 30.25 23.24 0.398559E+09 549.49 21-SEP-09:09 20.97 17.73
October 0.290247E+10 4130.94 02-OCT-14:40 26.70 20.10 0.379226E+09 549.48 11-OCT-09:30 21.70 18.27
November 0.199177E+10 2134.59 03-NOV-15:20 21.50 17.22 0.342398E+09 547.96 03-NOV-13:00 21.50 17.22
December 0.107115E+10 1991.65 13-DEC-13:30 19.45 17.14 0.307596E+09 518.14 13-DEC-14:00 18.30 16.86
                     
Annual Sum or Average 0.405182E+11         0.453191E+10        
Minimum of Months 0.496577E+09 1837.19   19.45 13.12 0.294564E+09 477.26   18.30 13.12
Maximum of Months 0.644393E+10 8473.77   31.67 23.24 0.454879E+09 549.50   33.30 22.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.563971E+09 1509.35 31-JAN-12:00 17.20 13.29 0.145006E+09 288.08 31-JAN-15:39 20.37 13.40
February 0.103599E+10 2775.84 27-FEB-10:00 12.80 5.65 0.141074E+09 338.72 28-FEB-11:09 20.87 12.02
March 0.235629E+10 3785.78 13-MAR-10:20 14.23 6.73 0.189813E+09 338.72 08-MAR-09:39 14.23 6.73
April 0.305894E+10 6883.55 16-APR-10:53 26.10 15.47 0.180967E+09 338.74 18-APR-14:30 26.40 16.44
May 0.415955E+10 11216.85 07-MAY-09:02 23.58 19.38 0.201514E+09 338.74 11-MAY-10:09 17.67 13.57
June 0.515468E+10 11182.77 11-JUN-09:43 24.72 14.58 0.203413E+09 338.74 05-JUN-07:40 24.72 14.58
July 0.537530E+10 11641.57 04-JUL-09:52 27.20 23.54 0.189866E+09 338.74 03-JUL-07:40 27.20 23.54
August 0.550625E+10 11959.36 27-AUG-09:52 27.20 21.81 0.212519E+09 338.73 14-AUG-07:19 27.20 21.81
September 0.390707E+10 9841.98 04-SEP-10:02 26.97 22.50 0.185783E+09 338.75 11-SEP-07:30 20.85 19.50
October 0.263330E+10 4676.47 11-OCT-10:20 23.73 19.29 0.179805E+09 338.72 03-OCT-10:39 23.73 19.29
November 0.174897E+10 2668.40 06-NOV-09:50 14.03 12.24 0.162135E+09 338.71 08-NOV-09:00 11.70 6.14
December 0.103564E+10 1624.83 13-DEC-12:00 20.00 17.41 0.144508E+09 308.27 13-DEC-13:39 19.07 17.05
                     
Annual Sum or Average 0.365360E+11         0.213640E+10        
Minimum of Months 0.563971E+09 1509.35   12.80 5.65 0.141074E+09 288.08   11.70 6.14
Maximum of Months 0.550625E+10 11959.36   27.20 23.54 0.212519E+09 338.75   27.20 23.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160409E+10 4931.02 27-JAN-14:30 3.35 -2.1 0.348461E+09 549.48 05-JAN-14:00 3.35 -2.1
February 0.221353E+10 11176.03 26-FEB-14:03 24.50 12.58 0.325041E+09 549.49 21-FEB-14:00 24.50 12.58
March 0.395582E+10 9038.58 30-MAR-13:40 27.43 17.97 0.420524E+09 549.50 13-MAR-13:00 27.43 17.97
April 0.417678E+10 7788.49 17-APR-13:50 28.72 16.68 0.386323E+09 549.51 12-APR-13:39 28.72 16.68
May 0.503685E+10 7220.57 29-MAY-13:32 28.50 20.43 0.430935E+09 549.50 24-MAY-09:09 28.50 20.43
June 0.609388E+10 7091.88 26-JUN-05:12 23.30 21.67 0.434576E+09 549.50 09-JUN-09:50 23.30 21.67
July 0.643275E+10 10474.81 16-JUL-13:53 33.90 23.22 0.405116E+09 549.48 03-JUL-09:09 33.90 23.22
August 0.754648E+10 12376.46 27-AUG-13:53 31.70 22.32 0.455229E+09 549.48 10-AUG-13:00 31.70 22.32
September 0.587125E+10 9821.06 17-SEP-14:43 28.12 22.39 0.400137E+09 549.49 22-SEP-13:39 26.50 17.31
October 0.502931E+10 12812.45 09-OCT-14:13 27.40 19.48 0.397615E+09 562.34 10-OCT-13:50 29.22 21.00
November 0.354955E+10 12744.58 11-NOV-13:53 21.10 11.67 0.380633E+09 549.49 14-NOV-14:00 20.00 9.44
December 0.248660E+10 6846.84 08-DEC-14:00 12.80 5.54 0.353230E+09 549.47 07-DEC-14:00 12.80 5.54
                     
Annual Sum or Average 0.539969E+11         0.473782E+10        
Minimum of Months 0.160409E+10 4931.02   3.35 -2.1 0.325041E+09 549.47   3.35 -2.1
Maximum of Months 0.754648E+10 12812.45   33.90 23.22 0.455229E+09 562.34   33.90 23.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.598406E+09 1683.29 27-JAN-16:40 4.40 -1.7 0.198646E+09 309.85 11-JAN-16:49 4.40 -1.7
February 0.108077E+10 4142.88 27-FEB-17:00 22.20 11.44 0.188029E+09 347.83 28-FEB-14:50 25.00 13.71
March 0.256865E+10 5986.48 30-MAR-16:00 27.80 17.47 0.248211E+09 347.83 29-MAR-13:00 27.80 17.47
April 0.314977E+10 11160.22 09-APR-17:12 21.50 10.93 0.235732E+09 347.84 12-APR-13:39 28.53 16.91
May 0.408521E+10 11931.91 21-MAY-17:32 25.97 19.50 0.269219E+09 347.85 17-MAY-09:50 25.97 19.50
June 0.497170E+10 11898.51 11-JUN-15:52 32.80 21.45 0.274119E+09 347.85 09-JUN-09:00 32.80 21.45
July 0.512584E+10 12405.08 04-JUL-17:52 30.60 22.43 0.255777E+09 347.84 03-JUL-09:09 30.60 22.43
August 0.543115E+10 12819.98 13-AUG-16:51 31.10 22.45 0.287521E+09 347.84 10-AUG-13:00 31.10 22.45
September 0.382059E+10 10801.72 04-SEP-16:12 27.97 22.70 0.249826E+09 347.84 25-SEP-09:09 24.78 19.25
October 0.273556E+10 9027.45 09-OCT-16:12 27.43 19.51 0.237021E+09 347.83 17-OCT-13:00 25.00 20.48
November 0.182475E+10 4017.67 06-NOV-16:00 20.60 10.48 0.216981E+09 347.82 15-NOV-14:00 21.70 11.58
December 0.101653E+10 1835.65 11-DEC-15:50 21.10 15.67 0.197789E+09 335.83 11-DEC-15:00 21.10 15.91
                     
Annual Sum or Average 0.364089E+11         0.285887E+10        
Minimum of Months 0.598406E+09 1683.29   4.40 -1.7 0.188029E+09 309.85   4.40 -1.7
Maximum of Months 0.543115E+10 12819.98   32.80 22.70 0.287521E+09 347.85   32.80 22.45



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3855069.72 15841.33 02-JAN-07:02 3.30
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 3855069.72      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 3855069.72 15841.33   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.368217E+10 12714.17 09-JAN-06:07 -2.4
February 0.233229E+10 14122.28 13-FEB-06:12 -5.6
March 0.756478E+09 4825.35 18-MAR-06:03 2.70
April 0.413378E+09 5655.70 06-APR-05:03 0.18
May 0.126997E+09 3646.73 10-MAY-05:03 8.98
June 57389513.51 3253.43 08-JUN-05:03 11.70
July 17282403.96 3238.01 07-JUL-04:02 25.22
August 16625336.54 4091.16 10-AUG-05:03 24.40
September 0.106245E+09 3117.84 29-SEP-05:03 12.30
October 0.592147E+09 5548.26 26-OCT-06:03 2.20
November 0.112023E+10 9667.82 22-NOV-07:02 -3.2
December 0.215079E+10 12800.04 18-DEC-06:13 -5.0
         
Annual Sum or Average 0.113720E+11      
Minimum of Months 16625336.54 3117.84   -5.6
Maximum of Months 0.368217E+10 14122.28   25.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157442E+10 7676.53 09-JAN-07:06 -3.3
February 0.838409E+09 6886.90 13-FEB-07:11 -5.6
March 0.155393E+09 2776.84 26-MAR-13:13 18.17
April 33558835.32 2167.71 09-APR-17:12 21.50
May 9702396.71 1849.52 14-MAY-16:33 25.60
June 7577312.53 1560.95 11-JUN-09:02 23.58
July 9642247.29 1903.59 30-JUL-10:43 26.73
August 9060939.67 1939.13 14-AUG-04:02 24.22
September 8811047.73 2185.62 17-SEP-11:23 26.40
October 0.110670E+09 2841.70 09-OCT-16:12 27.43
November 0.332216E+09 3398.23 11-NOV-11:13 17.60
December 0.837960E+09 3939.52 04-DEC-07:03 -3.3
         
Annual Sum or Average 0.392742E+10      
Minimum of Months 7577312.53 1560.95   -5.6
Maximum of Months 0.157442E+10 7676.53   27.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108365E+10 3814.31 09-JAN-07:01 -3.3
February 0.574393E+09 3384.76 13-FEB-08:18 -4.8
March 42214565.03 894.84 23-MAR-07:40 6.50
April 8414383.13 1830.62 09-APR-16:23 21.70
May 8954969.16 1767.83 29-MAY-14:10 28.48
June 10974228.68 1574.58 18-JUN-11:23 26.95
July 11724736.61 3036.55 07-JUL-04:02 25.22
August 14134423.63 3209.34 14-AUG-04:02 24.22
September 16819310.12 2259.63 17-SEP-11:23 26.40
October 56634265.22 2465.88 22-OCT-11:13 21.13
November 0.130902E+09 2946.24 26-NOV-13:23 18.30
December 0.522737E+09 2801.29 10-DEC-12:53 15.60
         
Annual Sum or Average 0.248155E+10      
Minimum of Months 8414383.13 894.84   -4.8
Maximum of Months 0.108365E+10 3814.31   28.48



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243261E+09 17479.66 09-JAN-06:01 -2.4
February 0.103683E+09 17060.88 13-FEB-06:01 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 780349.51 7126.55 22-NOV-07:01 -3.2
December 49454344.56 15603.87 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.397179E+09      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 0.243261E+09 17479.66   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.161046E+10 31039.74 09-JAN-05:11 -2.2
February 0.732435E+09 30694.15 13-FEB-05:01 -5.1
March 28707667.49 24738.79 22-MAR-06:03 5.50
April 3862636.37 20618.69 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 15142033.97 24645.70 26-OCT-06:03 2.20
November 99205590.69 26686.47 22-NOV-06:01 -3.3
December 0.608577E+09 29252.06 04-DEC-05:11 -2.8
         
Annual Sum or Average 0.309839E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.161046E+10 31039.74   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.302206E+10 10538.75 09-JAN-05:11 -2.2
February 0.165017E+10 10762.84 12-FEB-07:23 -12.5
March 0.177070E+09 8971.20 23-MAR-05:12 6.10
April 47147542.92 8637.67 06-APR-05:03 0.18
May 301553.93 1507.77 11-MAY-06:03 8.17
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 77287198.38 9073.32 26-OCT-05:11 2.20
November 0.451036E+09 9654.55 22-NOV-05:02 -2.9
December 0.143988E+10 10376.79 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.686496E+10      
Minimum of Months 0.00 0.00   -12.5
Maximum of Months 0.302206E+10 10762.84   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160779E+10 9516.32 09-JAN-05:11 -2.2
February 0.838379E+09 9680.80 12-FEB-07:23 -12.5
March 87232307.06 8009.35 23-MAR-05:12 6.10
April 22811462.74 7378.00 07-APR-06:02 2.80
May 103671.55 518.36 11-MAY-06:03 8.17
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 213283.51 1421.89 29-SEP-06:03 12.88
October 49885697.64 8114.46 26-OCT-05:11 2.20
November 0.207875E+09 8605.63 22-NOV-05:02 -2.9
December 0.686072E+09 9351.79 04-DEC-05:11 -2.8
         
Annual Sum or Average 0.350036E+10      
Minimum of Months 0.00 0.00   -12.5
Maximum of Months 0.160779E+10 9680.80   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190345E+10 12137.18 09-JAN-05:11 -2.2
February 0.103503E+10 12315.25 12-FEB-06:03 -12.3
March 0.121532E+09 10320.37 23-MAR-05:12 6.10
April 40437582.70 9557.16 06-APR-06:02 1.20
May 520281.22 2601.41 11-MAY-06:03 8.17
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 58835437.16 10267.29 26-OCT-05:11 2.20
November 0.247406E+09 10780.53 25-NOV-06:01 0.68
December 0.790157E+09 11820.82 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.419737E+10      
Minimum of Months 0.00 0.00   -12.3
Maximum of Months 0.190345E+10 12315.25   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.177559E+10 9509.45 09-JAN-05:11 -2.2
February 0.960550E+09 9683.10 12-FEB-07:23 -12.5
March 0.106220E+09 7846.98 23-MAR-05:12 6.10
April 28784662.31 7373.92 07-APR-06:02 2.80
May 628546.53 2466.50 11-MAY-06:03 8.17
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 335513.01 2236.75 29-SEP-06:03 12.88
October 51195993.50 7891.97 26-OCT-05:11 2.20
November 0.277348E+09 8662.17 22-NOV-05:02 -2.9
December 0.847958E+09 9314.66 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.404861E+10      
Minimum of Months 0.00 0.00   -12.5
Maximum of Months 0.177559E+10 9683.10   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156167E+10 8049.59 09-JAN-05:02 -2.2
February 0.810211E+09 8193.78 13-FEB-05:01 -5.1
March 44481742.40 6680.75 22-MAR-06:03 5.50
April 13836054.85 6722.52 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 1514015.46 5513.19 26-OCT-06:03 2.20
November 24258250.56 6912.71 22-NOV-06:01 -3.3
December 0.282800E+09 7433.64 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.273877E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.156167E+10 8193.78   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.765519E+09 6766.70 09-JAN-05:02 -2.2
February 0.339879E+09 6812.07 13-FEB-05:01 -5.1
March 19270825.13 5561.22 18-MAR-06:03 2.70
April 4080526.06 5412.55 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 1291069.74 3817.28 26-OCT-06:03 2.20
November 6948242.89 5476.31 22-NOV-07:01 -3.2
December 0.111494E+09 6031.60 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.124848E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.765519E+09 6812.07   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291430E+10 10452.43 27-JAN-07:10 -6.7
February 0.180082E+10 10727.20 03-FEB-07:10 -8.9
March 0.732941E+09 8624.29 06-MAR-07:50 2.80
April 0.409595E+09 9049.22 06-APR-06:10 1.20
May 97289853.89 7871.31 11-MAY-06:03 8.17
June 10956121.48 6061.58 08-JUN-06:07 12.07
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 11112061.80 3364.58 29-SEP-06:08 12.88
October 0.358341E+09 8652.32 26-OCT-07:00 2.20
November 0.722715E+09 9507.00 22-NOV-07:10 -3.2
December 0.116298E+10 9952.11 18-DEC-07:10 -5.1
         
Annual Sum or Average 0.822105E+10      
Minimum of Months 0.00 0.00   -8.9
Maximum of Months 0.291430E+10 10727.20   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.803583E+09 6812.13 09-JAN-05:02 -2.2
February 0.388070E+09 6751.75 13-FEB-05:01 -5.1
March 17458083.11 5447.51 23-MAR-06:03 6.10
April 4515092.27 5545.13 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 974498.26 3205.48 31-OCT-06:03 8.22
November 12008942.73 5473.46 22-NOV-07:01 -3.2
December 0.131650E+09 6031.73 26-DEC-06:11 3.30
         
Annual Sum or Average 0.135826E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.803583E+09 6812.13   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.151576E+10 8968.75 09-JAN-05:11 -2.2
February 0.715598E+09 8823.89 13-FEB-05:01 -5.1
March 26776605.07 7141.72 23-MAR-06:03 6.10
April 6022708.95 7192.85 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 8986819.19 7158.92 30-OCT-06:03 8.90
November 94596193.08 7834.25 22-NOV-06:01 -3.3
December 0.500969E+09 8401.51 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.286871E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.151576E+10 8968.75   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.833373E+09 7193.89 09-JAN-05:11 -2.2
February 0.361759E+09 7058.56 13-FEB-05:01 -5.1
March 18097504.24 5544.77 18-MAR-06:03 2.70
April 3812389.99 5644.95 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 7256844.72 5563.44 26-OCT-06:03 2.20
November 44240806.71 6005.98 22-NOV-06:01 -3.3
December 0.237770E+09 6552.96 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.150631E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.833373E+09 7193.89   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.862169E+09 10513.68 09-JAN-05:11 -2.2
February 0.379439E+09 10351.28 13-FEB-05:01 -5.1
March 17922215.86 8371.66 23-MAR-06:03 6.10
April 5044651.80 8444.86 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 7591129.71 8341.76 26-OCT-06:03 2.20
November 44626718.35 8993.30 22-NOV-06:01 -3.3
December 0.243884E+09 9707.63 26-DEC-06:11 3.30
         
Annual Sum or Average 0.156068E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.862169E+09 10513.68   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.870340E+09 7235.33 09-JAN-05:11 -2.2
February 0.400051E+09 7083.58 13-FEB-05:01 -5.1
March 18238764.21 5462.72 23-MAR-06:03 6.10
April 4162977.99 5769.20 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 7101734.22 5467.53 26-OCT-06:03 2.20
November 61705425.02 6011.19 22-NOV-06:01 -3.3
December 0.291387E+09 6570.28 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.165299E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.870340E+09 7235.33   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.250423E+12    
Minimum of Months 0.544142E+10 6443.98   0.191215E+11 14019.75  
Maximum of Months 0.648083E+10 6443.98   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846055E+09 1358.45 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.762897E+09 1358.45 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.796776E+09 1358.45 16-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.675359E+09 1184.79 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.699833E+09 947.97 24-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.687181E+09 774.31 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.651426E+09 947.97 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.744765E+09 1184.79 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.703252E+09 1358.45 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.808123E+09 1358.45 13-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.811693E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.826313E+09 1358.45 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.901367E+10     0.243325E+11    
Minimum of Months 0.651426E+09 774.31   0.185366E+10 1435.25  
Maximum of Months 0.846055E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.508129E+09 860.01 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.460497E+09 860.01 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.492356E+09 860.01 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.424791E+09 750.07 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.447103E+09 450.21 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.439946E+09 450.21 23-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.415308E+09 600.14 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.471842E+09 750.07 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.436677E+09 750.07 05-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.484045E+09 860.01 19-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.494745E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.493985E+09 860.01 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.556942E+10     0.154036E+11    
Minimum of Months 0.415308E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.508129E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.765762E+09 1358.45 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.705338E+09 1358.45 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.777899E+09 1358.45 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.677143E+09 1184.79 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.712140E+09 947.97 02-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.700772E+09 947.97 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.663635E+09 947.97 19-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.749752E+09 1184.79 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.692213E+09 1358.45 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.750902E+09 1358.45 19-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.748109E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.742755E+09 1358.45 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.868642E+10     0.243324E+11    
Minimum of Months 0.663635E+09 947.97   0.185364E+10 1435.24  
Maximum of Months 0.777899E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.507897E+09 859.95 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.468127E+09 859.95 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.503400E+09 859.95 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.431347E+09 859.95 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.451973E+09 750.02 24-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.442883E+09 600.10 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.420627E+09 750.02 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.477530E+09 750.02 23-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.446712E+09 859.95 27-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.500286E+09 859.95 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.490384E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.493477E+09 859.95 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.563464E+10     0.154035E+11    
Minimum of Months 0.420627E+09 600.10   0.117344E+10 908.57  
Maximum of Months 0.507897E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.839329E+09 1358.45 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.757888E+09 1358.45 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.793132E+09 1358.45 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.673272E+09 1184.79 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.699539E+09 774.31 02-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.686444E+09 774.31 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.651107E+09 947.97 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.743416E+09 1184.79 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.700764E+09 1358.45 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.802629E+09 1358.45 13-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.805079E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.819465E+09 1358.45 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.897207E+10     0.243325E+11    
Minimum of Months 0.651107E+09 774.31   0.185366E+10 1435.25  
Maximum of Months 0.839329E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.505975E+09 860.01 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.458253E+09 860.01 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.491163E+09 860.01 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.423886E+09 750.07 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.446374E+09 450.21 02-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.439292E+09 410.22 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.414667E+09 490.21 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.471104E+09 750.07 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.435545E+09 750.07 05-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.481922E+09 860.01 19-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.492680E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.491780E+09 860.01 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.555264E+10     0.154036E+11    
Minimum of Months 0.414667E+09 410.22   0.117344E+10 908.57  
Maximum of Months 0.505975E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.763932E+09 1358.45 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.704598E+09 1358.45 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.775420E+09 1358.45 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.675198E+09 1184.79 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.710688E+09 947.97 02-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.699319E+09 947.97 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.661869E+09 947.97 19-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.747992E+09 1184.79 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.690150E+09 1358.45 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.748760E+09 1358.45 19-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.746697E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.740187E+09 1358.45 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.866481E+10     0.243324E+11    
Minimum of Months 0.661869E+09 947.97   0.185364E+10 1435.24  
Maximum of Months 0.775420E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.505576E+09 859.95 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.465983E+09 859.95 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.501880E+09 859.95 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.429834E+09 859.95 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.450170E+09 750.02 24-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.441854E+09 600.10 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.419226E+09 750.02 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.476238E+09 750.02 23-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.444656E+09 859.95 29-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.498301E+09 859.95 13-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.487915E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.491638E+09 859.95 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.561327E+10     0.154035E+11    
Minimum of Months 0.419226E+09 600.10   0.117344E+10 908.57  
Maximum of Months 0.505576E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.846055E+09 1358.45 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.762897E+09 1358.45 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.796776E+09 1358.45 16-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.675359E+09 1184.79 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.699833E+09 947.97 24-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.687181E+09 774.31 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.651426E+09 947.97 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.744765E+09 1184.79 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.703252E+09 1358.45 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.808123E+09 1358.45 13-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.811693E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.826313E+09 1358.45 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.901367E+10     0.243325E+11    
Minimum of Months 0.651426E+09 774.31   0.185366E+10 1435.25  
Maximum of Months 0.846055E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.508129E+09 860.01 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.460497E+09 860.01 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.492356E+09 860.01 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.424791E+09 750.07 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.447103E+09 450.21 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.439946E+09 450.21 23-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.415308E+09 600.14 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.471842E+09 750.07 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.436677E+09 750.07 05-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.484045E+09 860.01 19-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.494745E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.493961E+09 860.01 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.556940E+10     0.154036E+11    
Minimum of Months 0.415308E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.508129E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.765727E+09 1358.45 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.705338E+09 1358.45 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.777861E+09 1358.45 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.677143E+09 1184.79 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.712140E+09 947.97 02-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.700772E+09 947.97 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.663635E+09 947.97 19-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.749752E+09 1184.79 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.692213E+09 1358.45 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.750900E+09 1358.45 19-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.748109E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.742755E+09 1358.45 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.868634E+10     0.243324E+11    
Minimum of Months 0.663635E+09 947.97   0.185364E+10 1435.24  
Maximum of Months 0.777861E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.507897E+09 859.95 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.468127E+09 859.95 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.503400E+09 859.95 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.431347E+09 859.95 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.451973E+09 750.02 24-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.442883E+09 600.10 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.420627E+09 750.02 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.477530E+09 750.02 23-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.446712E+09 859.95 27-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.500286E+09 859.95 06-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.490384E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.493477E+09 859.95 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.563464E+10     0.154035E+11    
Minimum of Months 0.420627E+09 600.10   0.117344E+10 908.57  
Maximum of Months 0.507897E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.846055E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.458093E+09
February 0.901968E+09 0.762897E+09 0.185366E+10 0.00 0.00 0.00 0.00 1096236.59 0.390095E+09
March 0.107774E+10 0.796776E+09 0.212947E+10 0.00 0.00 0.00 0.00 1385393.83 0.249948E+09
April 0.956342E+09 0.675359E+09 0.197726E+10 0.00 0.00 0.00 0.00 3374076.72 0.157489E+09
May 0.103597E+10 0.699833E+09 0.208852E+10 0.00 0.00 0.00 0.00 8553241.44 0.104576E+09
June 0.103308E+10 0.687181E+09 0.205071E+10 0.00 0.00 0.00 0.00 33844452.61 52538627.89
July 0.959235E+09 0.651426E+09 0.201461E+10 0.00 0.00 0.00 0.00 36610722.59 34943496.02
August 0.107774E+10 0.744765E+09 0.212947E+10 0.00 0.00 0.00 0.00 35464134.03 22140447.45
September 0.956342E+09 0.703252E+09 0.197634E+10 0.00 0.00 0.00 0.00 10893362.31 51274469.59
October 0.994195E+09 0.808123E+09 0.204804E+10 0.00 0.00 0.00 0.00 3675417.43 0.167465E+09
November 0.984487E+09 0.811693E+09 0.200273E+10 0.00 0.00 0.00 0.00 426747.82 0.238546E+09
December 0.959235E+09 0.826313E+09 0.201415E+10 0.00 0.00 0.00 0.00 662.35 0.412315E+09
                   
Annual Sum or Average 0.119305E+11 0.901367E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.135324E+09 0.233942E+10
Minimum of Months 0.901968E+09 0.651426E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 22140447.45
Maximum of Months 0.107774E+10 0.846055E+09 0.212947E+10 0.00 0.00 0.00 0.00 36610722.59 0.458093E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.508129E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.309153E+09
February 0.571020E+09 0.460497E+09 0.117344E+10 0.00 0.00 0.00 0.00 378644.20 0.265225E+09
March 0.682301E+09 0.492356E+09 0.134804E+10 0.00 0.00 0.00 0.00 956293.62 0.172458E+09
April 0.605444E+09 0.424791E+09 0.125169E+10 0.00 0.00 0.00 0.00 1894532.26 0.108336E+09
May 0.655854E+09 0.447103E+09 0.132213E+10 0.00 0.00 0.00 0.00 5165296.87 72318249.81
June 0.654023E+09 0.439946E+09 0.129819E+10 0.00 0.00 0.00 0.00 22092678.72 35717735.93
July 0.607275E+09 0.415308E+09 0.127534E+10 0.00 0.00 0.00 0.00 23773073.61 23842511.99
August 0.682301E+09 0.471842E+09 0.134804E+10 0.00 0.00 0.00 0.00 23169191.13 15066536.64
September 0.605444E+09 0.436677E+09 0.125111E+10 0.00 0.00 0.00 0.00 6810629.02 34338317.40
October 0.629407E+09 0.484045E+09 0.129650E+10 0.00 0.00 0.00 0.00 1890224.45 0.114852E+09
November 0.623262E+09 0.494745E+09 0.126781E+10 0.00 0.00 0.00 0.00 262434.35 0.162771E+09
December 0.607275E+09 0.493985E+09 0.127504E+10 0.00 0.00 0.00 0.00 684.80 0.277599E+09
                   
Annual Sum or Average 0.755301E+10 0.556942E+10 0.154036E+11 0.00 0.00 0.00 0.00 86393683.04 0.159168E+10
Minimum of Months 0.571020E+09 0.415308E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 15066536.64
Maximum of Months 0.682301E+09 0.508129E+09 0.134804E+10 0.00 0.00 0.00 0.00 23773073.61 0.309153E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.765762E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.486739E+09
February 0.901968E+09 0.705338E+09 0.185364E+10 0.00 0.00 0.00 0.00 51448.64 0.416863E+09
March 0.107774E+10 0.777899E+09 0.212945E+10 0.00 0.00 0.00 0.00 944238.14 0.274260E+09
April 0.956342E+09 0.677143E+09 0.197725E+10 0.00 0.00 0.00 0.00 2415428.36 0.164227E+09
May 0.103597E+10 0.712140E+09 0.208851E+10 0.00 0.00 0.00 0.00 7831160.32 0.105601E+09
June 0.103308E+10 0.700772E+09 0.205070E+10 0.00 0.00 0.00 0.00 33635075.08 51888511.90
July 0.959235E+09 0.663635E+09 0.201460E+10 0.00 0.00 0.00 0.00 36206214.37 34785567.78
August 0.107774E+10 0.749752E+09 0.212945E+10 0.00 0.00 0.00 0.00 34017089.71 22919662.61
September 0.956342E+09 0.692213E+09 0.197632E+10 0.00 0.00 0.00 0.00 8884910.42 53579776.16
October 0.994195E+09 0.750902E+09 0.204803E+10 0.00 0.00 0.00 0.00 1386388.93 0.183711E+09
November 0.984487E+09 0.748109E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.264415E+09
December 0.959235E+09 0.742755E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.439176E+09
                   
Annual Sum or Average 0.119305E+11 0.868642E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.125372E+09 0.249817E+10
Minimum of Months 0.901968E+09 0.663635E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 22919662.61
Maximum of Months 0.107774E+10 0.777899E+09 0.212945E+10 0.00 0.00 0.00 0.00 36206214.37 0.486739E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.507897E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.310017E+09
February 0.570983E+09 0.468127E+09 0.117344E+10 0.00 0.00 0.00 0.00 472399.00 0.265387E+09
March 0.682256E+09 0.503400E+09 0.134804E+10 0.00 0.00 0.00 0.00 735239.84 0.176300E+09
April 0.605404E+09 0.431347E+09 0.125169E+10 0.00 0.00 0.00 0.00 1950053.28 0.108973E+09
May 0.655811E+09 0.451973E+09 0.132212E+10 0.00 0.00 0.00 0.00 5382589.14 71576161.31
June 0.653980E+09 0.442883E+09 0.129818E+10 0.00 0.00 0.00 0.00 22029870.62 35930323.04
July 0.607235E+09 0.420627E+09 0.127533E+10 0.00 0.00 0.00 0.00 24027171.37 23658023.33
August 0.682256E+09 0.477530E+09 0.134804E+10 0.00 0.00 0.00 0.00 22708865.54 15980425.84
September 0.605404E+09 0.446712E+09 0.125110E+10 0.00 0.00 0.00 0.00 6880838.19 34822793.38
October 0.629366E+09 0.500286E+09 0.129649E+10 0.00 0.00 0.00 0.00 1757477.16 0.115351E+09
November 0.623221E+09 0.490384E+09 0.126780E+10 0.00 0.00 0.00 0.00 27167.48 0.163708E+09
December 0.607235E+09 0.493477E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.278081E+09
                   
Annual Sum or Average 0.755252E+10 0.563464E+10 0.154035E+11 0.00 0.00 0.00 0.00 85971671.62 0.159979E+10
Minimum of Months 0.570983E+09 0.420627E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 15980425.84
Maximum of Months 0.682256E+09 0.507897E+09 0.134804E+10 0.00 0.00 0.00 0.00 24027171.37 0.310017E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.839329E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.261853E+09
February 0.901968E+09 0.757888E+09 0.185366E+10 0.00 0.00 0.00 0.00 644081.15 0.218037E+09
March 0.107774E+10 0.793132E+09 0.212947E+10 0.00 0.00 0.00 0.00 1093997.27 0.133784E+09
April 0.956342E+09 0.673272E+09 0.197726E+10 0.00 0.00 0.00 0.00 2522215.59 79662562.37
May 0.103597E+10 0.699539E+09 0.208852E+10 0.00 0.00 0.00 0.00 5222536.42 52930479.72
June 0.103308E+10 0.686444E+09 0.205071E+10 0.00 0.00 0.00 0.00 19151260.58 26940043.09
July 0.959235E+09 0.651107E+09 0.201461E+10 0.00 0.00 0.00 0.00 21278383.08 18110179.30
August 0.107774E+10 0.743416E+09 0.212947E+10 0.00 0.00 0.00 0.00 19976142.45 11516721.68
September 0.956342E+09 0.700764E+09 0.197634E+10 0.00 0.00 0.00 0.00 5903722.85 31066198.88
October 0.994195E+09 0.802629E+09 0.204804E+10 0.00 0.00 0.00 0.00 1786770.94 0.101972E+09
November 0.984487E+09 0.805079E+09 0.200273E+10 0.00 0.00 0.00 0.00 41463.60 0.145604E+09
December 0.959235E+09 0.819465E+09 0.201415E+10 0.00 0.00 0.00 0.00 248.91 0.248169E+09
                   
Annual Sum or Average 0.119305E+11 0.897207E+10 0.243325E+11 0.00 0.00 0.00 0.00 77620822.83 0.132965E+10
Minimum of Months 0.901968E+09 0.651107E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 11516721.68
Maximum of Months 0.107774E+10 0.839329E+09 0.212947E+10 0.00 0.00 0.00 0.00 21278383.08 0.261853E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.505975E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.177545E+09
February 0.571020E+09 0.458253E+09 0.117344E+10 0.00 0.00 0.00 0.00 186289.72 0.149687E+09
March 0.682301E+09 0.491163E+09 0.134804E+10 0.00 0.00 0.00 0.00 616367.68 94968896.09
April 0.605444E+09 0.423886E+09 0.125169E+10 0.00 0.00 0.00 0.00 1159380.81 56887683.43
May 0.655854E+09 0.446374E+09 0.132213E+10 0.00 0.00 0.00 0.00 2860725.98 38413124.06
June 0.654023E+09 0.439292E+09 0.129819E+10 0.00 0.00 0.00 0.00 12013045.46 19186538.19
July 0.607275E+09 0.414667E+09 0.127534E+10 0.00 0.00 0.00 0.00 13028820.66 13045469.87
August 0.682301E+09 0.471104E+09 0.134804E+10 0.00 0.00 0.00 0.00 12442649.70 8522136.85
September 0.605444E+09 0.435545E+09 0.125111E+10 0.00 0.00 0.00 0.00 3544785.46 21482166.69
October 0.629407E+09 0.481922E+09 0.129650E+10 0.00 0.00 0.00 0.00 822404.07 71077809.65
November 0.623262E+09 0.492680E+09 0.126781E+10 0.00 0.00 0.00 0.00 8724.63 0.101041E+09
December 0.607275E+09 0.491780E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.168108E+09
                   
Annual Sum or Average 0.755301E+10 0.555264E+10 0.154036E+11 0.00 0.00 0.00 0.00 46683194.18 0.919966E+09
Minimum of Months 0.571020E+09 0.414667E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 8522136.85
Maximum of Months 0.682301E+09 0.505975E+09 0.134804E+10 0.00 0.00 0.00 0.00 13028820.66 0.177545E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.763932E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.431483E+10
February 0.901968E+09 0.704598E+09 0.185364E+10 0.00 0.00 0.00 0.00 620510.31 0.315259E+10
March 0.107774E+10 0.775420E+09 0.212945E+10 0.00 0.00 0.00 0.00 27230583.43 0.226055E+10
April 0.956342E+09 0.675198E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.141056E+09 0.127743E+10
May 0.103597E+10 0.710688E+09 0.208851E+10 0.00 0.00 0.00 0.00 0.333719E+09 0.673527E+09
June 0.103308E+10 0.699319E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.943175E+09 0.249548E+09
July 0.959235E+09 0.661869E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.977167E+09 0.186271E+09
August 0.107774E+10 0.747992E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.108313E+10 0.114920E+09
September 0.956342E+09 0.690150E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.374366E+09 0.452690E+09
October 0.994195E+09 0.748760E+09 0.204803E+10 0.00 0.00 0.00 0.00 68474415.44 0.175723E+10
November 0.984487E+09 0.746697E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.268247E+10
December 0.959235E+09 0.740187E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.321815E+10
                   
Annual Sum or Average 0.119305E+11 0.866481E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.394894E+10 0.203402E+11
Minimum of Months 0.901968E+09 0.661869E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.114920E+09
Maximum of Months 0.107774E+10 0.775420E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.108313E+10 0.431483E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.505576E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.177925E+09
February 0.570983E+09 0.465983E+09 0.117344E+10 0.00 0.00 0.00 0.00 217525.87 0.149384E+09
March 0.682256E+09 0.501880E+09 0.134804E+10 0.00 0.00 0.00 0.00 433940.83 97365958.43
April 0.605404E+09 0.429834E+09 0.125169E+10 0.00 0.00 0.00 0.00 1091661.31 57780440.86
May 0.655811E+09 0.450170E+09 0.132212E+10 0.00 0.00 0.00 0.00 2761084.87 38326937.18
June 0.653980E+09 0.441854E+09 0.129818E+10 0.00 0.00 0.00 0.00 11787164.65 19513130.88
July 0.607235E+09 0.419226E+09 0.127533E+10 0.00 0.00 0.00 0.00 12953426.16 13031643.76
August 0.682256E+09 0.476238E+09 0.134804E+10 0.00 0.00 0.00 0.00 12004293.49 9167255.35
September 0.605404E+09 0.444656E+09 0.125110E+10 0.00 0.00 0.00 0.00 3477481.27 22027405.75
October 0.629366E+09 0.498301E+09 0.129649E+10 0.00 0.00 0.00 0.00 724086.30 71757309.01
November 0.623221E+09 0.487915E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.101319E+09
December 0.607235E+09 0.491638E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.168050E+09
                   
Annual Sum or Average 0.755252E+10 0.561327E+10 0.154035E+11 0.00 0.00 0.00 0.00 45450664.75 0.925648E+09
Minimum of Months 0.570983E+09 0.419226E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 9167255.35
Maximum of Months 0.682256E+09 0.505576E+09 0.134804E+10 0.00 0.00 0.00 0.00 12953426.16 0.177925E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.846055E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.403983E+09
February 0.901968E+09 0.762897E+09 0.185366E+10 0.00 0.00 0.00 0.00 796101.81 0.342446E+09
March 0.107774E+10 0.796776E+09 0.212947E+10 0.00 0.00 0.00 0.00 1121183.14 0.222940E+09
April 0.956342E+09 0.675359E+09 0.197726E+10 0.00 0.00 0.00 0.00 2909215.66 0.138684E+09
May 0.103597E+10 0.699833E+09 0.208852E+10 0.00 0.00 0.00 0.00 7229994.55 91209784.08
June 0.103308E+10 0.687181E+09 0.205071E+10 0.00 0.00 0.00 0.00 28898984.38 45383268.69
July 0.959235E+09 0.651426E+09 0.201461E+10 0.00 0.00 0.00 0.00 31570788.48 30107935.26
August 0.107774E+10 0.744765E+09 0.212947E+10 0.00 0.00 0.00 0.00 30294735.84 19135567.60
September 0.956342E+09 0.703252E+09 0.197634E+10 0.00 0.00 0.00 0.00 9187014.37 46674798.36
October 0.994195E+09 0.808123E+09 0.204804E+10 0.00 0.00 0.00 0.00 2855645.74 0.152385E+09
November 0.984487E+09 0.811693E+09 0.200273E+10 0.00 0.00 0.00 0.00 143778.90 0.217741E+09
December 0.959235E+09 0.826313E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.373482E+09
                   
Annual Sum or Average 0.119305E+11 0.901367E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.115007E+09 0.208417E+10
Minimum of Months 0.901968E+09 0.651426E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 19135567.60
Maximum of Months 0.107774E+10 0.846055E+09 0.212947E+10 0.00 0.00 0.00 0.00 31570788.48 0.403983E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.508129E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.272694E+09
February 0.421807E+09 0.460497E+09 0.117344E+10 0.00 0.00 0.00 0.00 279529.76 0.232858E+09
March 0.502994E+09 0.492356E+09 0.134804E+10 0.00 0.00 0.00 0.00 795673.72 0.152797E+09
April 0.447140E+09 0.424791E+09 0.125169E+10 0.00 0.00 0.00 0.00 1695343.17 94653017.58
May 0.484071E+09 0.447103E+09 0.132213E+10 0.00 0.00 0.00 0.00 4449017.12 62714101.66
June 0.482240E+09 0.439946E+09 0.129819E+10 0.00 0.00 0.00 0.00 18798282.79 30730887.72
July 0.448971E+09 0.415308E+09 0.127534E+10 0.00 0.00 0.00 0.00 20389495.19 20525011.26
August 0.502994E+09 0.471842E+09 0.134804E+10 0.00 0.00 0.00 0.00 19725666.24 12997033.96
September 0.447140E+09 0.436677E+09 0.125111E+10 0.00 0.00 0.00 0.00 5783307.59 31067225.07
October 0.465148E+09 0.484045E+09 0.129650E+10 0.00 0.00 0.00 0.00 1522181.54 0.103318E+09
November 0.460569E+09 0.494745E+09 0.126781E+10 0.00 0.00 0.00 0.00 81343.25 0.147689E+09
December 0.448971E+09 0.493961E+09 0.127504E+10 0.00 0.00 0.00 0.00 2193.30 0.251160E+09
                   
Annual Sum or Average 0.557719E+10 0.556940E+10 0.154036E+11 0.00 0.00 0.00 0.00 73522033.65 0.141320E+10
Minimum of Months 0.421807E+09 0.415308E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 12997033.96
Maximum of Months 0.502994E+09 0.508129E+09 0.134804E+10 0.00 0.00 0.00 0.00 20389495.19 0.272694E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.765727E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.430167E+09
February 0.901968E+09 0.705338E+09 0.185364E+10 0.00 0.00 0.00 0.00 44399.18 0.366795E+09
March 0.107774E+10 0.777861E+09 0.212945E+10 0.00 0.00 0.00 0.00 789117.35 0.242828E+09
April 0.956342E+09 0.677143E+09 0.197725E+10 0.00 0.00 0.00 0.00 2053196.07 0.144104E+09
May 0.103597E+10 0.712140E+09 0.208851E+10 0.00 0.00 0.00 0.00 6634160.61 92132877.29
June 0.103308E+10 0.700772E+09 0.205070E+10 0.00 0.00 0.00 0.00 28613564.63 44931335.89
July 0.959235E+09 0.663635E+09 0.201460E+10 0.00 0.00 0.00 0.00 30990818.22 30041958.18
August 0.107774E+10 0.749752E+09 0.212945E+10 0.00 0.00 0.00 0.00 28765812.14 19817934.75
September 0.956342E+09 0.692213E+09 0.197632E+10 0.00 0.00 0.00 0.00 7417834.18 48513660.92
October 0.994195E+09 0.750900E+09 0.204803E+10 0.00 0.00 0.00 0.00 1174055.40 0.165080E+09
November 0.984487E+09 0.748109E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.239066E+09
December 0.959235E+09 0.742755E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.397022E+09
                   
Annual Sum or Average 0.119305E+11 0.868634E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.106483E+09 0.222050E+10
Minimum of Months 0.901968E+09 0.663635E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 19817934.75
Maximum of Months 0.107774E+10 0.777861E+09 0.212945E+10 0.00 0.00 0.00 0.00 30990818.22 0.430167E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.507897E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.273263E+09
February 0.570983E+09 0.468127E+09 0.117344E+10 0.00 0.00 0.00 0.00 303589.91 0.232898E+09
March 0.682256E+09 0.503400E+09 0.134804E+10 0.00 0.00 0.00 0.00 581333.93 0.156493E+09
April 0.605404E+09 0.431347E+09 0.125169E+10 0.00 0.00 0.00 0.00 1575131.54 95881380.71
May 0.655811E+09 0.451973E+09 0.132212E+10 0.00 0.00 0.00 0.00 4341695.95 62706979.52
June 0.653980E+09 0.442883E+09 0.129818E+10 0.00 0.00 0.00 0.00 18401735.63 31226666.86
July 0.607235E+09 0.420627E+09 0.127533E+10 0.00 0.00 0.00 0.00 20117875.78 20593584.13
August 0.682256E+09 0.477530E+09 0.134804E+10 0.00 0.00 0.00 0.00 18904659.90 13920716.22
September 0.605404E+09 0.446712E+09 0.125110E+10 0.00 0.00 0.00 0.00 5631586.99 31857235.13
October 0.629366E+09 0.500286E+09 0.129649E+10 0.00 0.00 0.00 0.00 1319362.91 0.104316E+09
November 0.623221E+09 0.490384E+09 0.126780E+10 0.00 0.00 0.00 0.00 216.90 0.148631E+09
December 0.607235E+09 0.493477E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.251527E+09
                   
Annual Sum or Average 0.755252E+10 0.563464E+10 0.154035E+11 0.00 0.00 0.00 0.00 71177189.45 0.142331E+10
Minimum of Months 0.570983E+09 0.420627E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 13920716.22
Maximum of Months 0.682256E+09 0.507897E+09 0.134804E+10 0.00 0.00 0.00 0.00 20117875.78 0.273263E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.576710E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271889.41 0.493213E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 777371.33 0.323486E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2338990.32 0.194625E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6930759.04 0.125895E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31934529.08 60607519.44
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36232795.30 39913155.51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33123794.74 25258908.20
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8425841.13 67880408.20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1693276.96 0.226657E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86041.14 0.325113E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.548064E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121815E+09 0.300742E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25258908.20
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36232795.30 0.576710E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.698656E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 865521.20 0.598406E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1276207.38 0.394700E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3754538.60 0.242218E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9771907.60 0.158250E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42010353.08 76590228.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47301096.43 49924033.21
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43471998.61 31433377.02
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12113182.65 80847615.59
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2919641.21 0.268274E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 701013.60 0.382524E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.651056E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.164185E+09 0.363288E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31433377.02
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47301096.43 0.698656E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.690717E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64025.45 0.593322E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 561052.61 0.394597E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1167632.44 0.246194E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5310964.77 0.161034E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35246312.31 73605677.72
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40434742.59 49346659.08
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38528888.89 29030892.85
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8900164.81 76339005.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1299213.37 0.261478E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 184655.39 0.368956E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.626148E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131698E+09 0.357077E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29030892.85
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40434742.59 0.690717E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 900.40 07-JAN-18:05
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 75.13 26-FEB-13:00 1089.30 12-FEB-01:00
March 1306.65 01-MAR-10:09 1358.45 16-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 37.05 11-MAR-16:00 634.90 22-MAR-03:00
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 63.30 16-APR-11:53 357.11 05-APR-05:00
May 1306.65 01-MAY-09:09 947.97 24-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 73.20 07-MAY-12:10 282.12 10-MAY-04:00
June 1306.65 01-JUN-09:09 774.31 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 187.81 11-JUN-15:00 210.31 07-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 172.28 08-JUL-18:53 149.38 28-JUL-22:00
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 182.42 06-AUG-13:52 98.00 23-AUG-05:00
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 75.57 17-SEP-15:00 186.51 29-SEP-05:00
October 1306.65 02-OCT-09:09 1358.45 13-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 85.92 08-OCT-13:53 371.92 28-OCT-04:00
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 59.79 19-NOV-15:00 624.20 30-NOV-22:03
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.64 12-DEC-14:00 931.77 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   774.31   1435.25   0.00 0.00 0.00 0.00 0.00   98.00  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 187.81   1089.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 595.23 07-JAN-18:05
February 827.22 01-FEB-10:09 860.01 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 29.90 26-FEB-16:00 726.19 12-FEB-01:00
March 827.22 01-MAR-10:09 860.01 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 25.49 11-MAR-18:03 419.16 22-MAR-03:00
April 827.22 03-APR-09:09 750.07 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 29.97 08-APR-17:20 236.91 05-APR-05:00
May 827.22 01-MAY-09:09 450.21 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 37.77 29-MAY-17:50 187.23 10-MAY-04:00
June 827.22 01-JUN-09:09 450.21 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 117.80 11-JUN-15:00 140.65 07-JUN-03:00
July 827.22 03-JUL-09:09 600.14 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 120.08 08-JUL-19:10 100.09 01-JUL-20:00
August 827.22 01-AUG-09:09 750.07 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 117.86 06-AUG-14:10 65.40 23-AUG-05:00
September 827.22 01-SEP-09:09 750.07 05-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 52.80 17-SEP-15:10 123.05 29-SEP-05:00
October 827.22 02-OCT-09:09 860.01 19-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 44.77 09-OCT-15:50 246.44 28-OCT-04:00
November 827.22 01-NOV-09:09 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 36.79 19-NOV-15:00 415.63 30-NOV-22:03
December 827.22 01-DEC-10:09 860.01 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.38 12-DEC-14:00 619.54 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 0.00   65.40  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 120.08   726.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 910.79 07-JAN-18:05
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 10.16 28-FEB-15:00 1107.66 11-FEB-18:05
March 1306.65 01-MAR-10:09 1358.45 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 26.46 30-MAR-16:00 638.14 22-MAR-03:00
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 26.59 16-APR-14:08 358.08 05-APR-05:00
May 1306.65 01-MAY-09:09 947.97 02-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 56.52 07-MAY-12:13 283.53 10-MAY-04:00
June 1306.65 01-JUN-09:09 947.97 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 175.13 11-JUN-15:00 210.75 07-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 19-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 170.23 08-JUL-18:53 149.55 28-JUL-22:00
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 165.85 06-AUG-14:08 98.70 23-AUG-05:00
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 54.13 17-SEP-14:48 187.13 29-SEP-05:00
October 1306.65 02-OCT-09:09 1358.45 19-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 23.83 09-OCT-15:50 385.16 28-OCT-04:00
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 624.40 30-NOV-22:03
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 947.90 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   947.97   1435.24   0.00 0.00 0.00 0.00 0.00   98.70  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 175.13   1107.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 599.76 07-JAN-18:05
February 827.17 01-FEB-10:09 859.95 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 54.06 26-FEB-13:00 754.48 11-FEB-18:05
March 827.17 01-MAR-10:09 859.95 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 17.64 30-MAR-16:00 421.37 22-MAR-03:00
April 827.17 03-APR-09:09 859.95 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 47.99 16-APR-12:10 235.12 05-APR-05:00
May 827.17 01-MAY-09:09 750.02 24-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 60.58 07-MAY-12:10 190.62 10-MAY-04:00
June 827.17 01-JUN-09:09 600.10 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 108.39 11-JUN-14:55 142.27 07-JUN-03:00
July 827.17 03-JUL-09:09 750.02 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 113.40 08-JUL-19:10 98.30 28-JUL-22:00
August 827.17 01-AUG-09:09 750.02 23-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 124.09 06-AUG-13:52 66.23 23-AUG-05:00
September 827.17 01-SEP-09:09 859.95 27-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 58.74 17-SEP-12:10 122.51 29-SEP-05:00
October 827.17 02-OCT-09:09 859.95 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 46.07 08-OCT-13:53 248.72 28-OCT-04:00
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 3.41 27-NOV-13:00 415.93 30-NOV-22:03
December 827.17 01-DEC-10:09 859.95 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 618.00 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   600.10   908.57   0.00 0.00 0.00 0.00 0.00   66.23  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 124.09   754.48  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 499.44 07-JAN-18:10
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 38.39 26-FEB-13:00 608.27 12-FEB-01:00
March 1306.65 01-MAR-10:09 1358.45 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 30.56 11-MAR-18:03 362.82 22-MAR-03:00
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 40.54 08-APR-17:03 188.56 05-APR-05:00
May 1306.65 01-MAY-09:09 774.31 02-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 46.88 07-MAY-11:53 158.12 10-MAY-04:00
June 1306.65 01-JUN-09:09 774.31 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 111.96 11-JUN-15:10 113.10 07-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 105.99 08-JUL-18:53 83.23 28-JUL-22:00
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 112.45 06-AUG-14:00 55.71 25-AUG-05:00
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 45.81 17-SEP-15:00 116.09 29-SEP-05:00
October 1306.65 02-OCT-09:09 1358.45 13-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 41.73 08-OCT-13:53 228.95 28-OCT-04:00
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 11.94 19-NOV-15:00 341.83 21-NOV-04:00
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.20 12-DEC-14:00 583.24 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   774.31   1435.25   0.00 0.00 0.00 0.00 0.00   55.71  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 112.45   608.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 331.86 07-JAN-18:10
February 827.22 01-FEB-10:09 860.01 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 14.94 26-FEB-16:00 404.64 12-FEB-01:00
March 827.22 01-MAR-10:09 860.01 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 16.69 11-MAR-18:03 244.98 22-MAR-03:00
April 827.22 03-APR-09:09 750.07 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 19.58 08-APR-17:03 125.17 05-APR-05:00
May 827.22 01-MAY-09:09 450.21 02-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 23.13 29-MAY-17:50 107.62 10-MAY-04:00
June 827.22 01-JUN-09:09 410.22 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 65.50 11-JUN-15:10 78.00 07-JUN-03:00
July 827.22 03-JUL-09:09 490.21 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 67.89 08-JUL-18:53 54.70 28-JUL-22:00
August 827.22 01-AUG-09:09 750.07 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 67.45 06-AUG-14:00 37.10 25-AUG-05:00
September 827.22 01-SEP-09:09 750.07 05-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.75 17-SEP-15:00 77.01 29-SEP-05:00
October 827.22 02-OCT-09:09 860.01 19-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 19.70 09-OCT-16:00 155.63 28-OCT-04:00
November 827.22 01-NOV-09:09 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 3.58 19-NOV-15:00 232.41 07-NOV-02:00
December 827.22 01-DEC-10:09 860.01 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 389.82 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   410.22   908.57   0.00 0.00 0.00 0.00 0.00   37.10  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 67.89   404.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 23092.21 27-JAN-07:01
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 108.19 28-FEB-15:00 25043.67 03-FEB-07:01
March 1306.65 01-MAR-10:09 1358.45 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 2811.40 30-MAR-16:10 14365.70 06-MAR-07:03
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 3713.92 17-APR-16:10 15683.52 06-APR-06:02
May 1306.65 01-MAY-09:09 947.97 02-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 5093.93 19-MAY-16:10 10409.68 11-MAY-06:10
June 1306.65 01-JUN-09:09 947.97 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 7175.56 06-JUN-16:05 7303.93 08-JUN-06:03
July 1306.65 03-JUL-09:09 947.97 19-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 8302.26 07-JUL-16:03 3486.57 03-JUL-06:03
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 8009.47 01-AUG-16:03 3668.09 25-AUG-06:03
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 5441.32 07-SEP-16:03 7927.76 14-SEP-06:02
October 1306.65 02-OCT-09:09 1358.45 19-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 3980.17 10-OCT-16:05 14851.50 26-OCT-06:03
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 19626.78 22-NOV-07:01
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 21580.35 18-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   947.97   1435.24   0.00 0.00 0.00 0.00 0.00   3486.57  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 8302.26   25043.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 333.95 07-JAN-18:10
February 827.17 01-FEB-10:09 859.95 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 23.97 26-FEB-13:00 413.33 11-FEB-18:15
March 827.17 01-MAR-10:09 859.95 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 9.51 30-MAR-16:00 246.25 22-MAR-03:00
April 827.17 03-APR-09:09 859.95 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 17.08 16-APR-11:53 124.94 05-APR-05:00
May 827.17 01-MAY-09:09 750.02 24-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 29.98 07-MAY-11:53 109.57 10-MAY-04:00
June 827.17 01-JUN-09:09 600.10 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 60.38 11-JUN-15:00 79.00 07-JUN-03:00
July 827.17 03-JUL-09:09 750.02 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 63.27 08-JUL-18:53 55.61 28-JUL-22:00
August 827.17 01-AUG-09:09 750.02 23-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 68.63 06-AUG-14:00 38.79 25-AUG-05:00
September 827.17 01-SEP-09:09 859.95 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 25.66 24-SEP-13:00 77.00 29-SEP-05:00
October 827.17 02-OCT-09:09 859.95 13-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 18.49 08-OCT-13:53 156.80 28-OCT-04:00
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 234.72 07-NOV-02:00
December 827.17 01-DEC-10:09 859.95 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 387.84 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   600.10   908.57   0.00 0.00 0.00 0.00 0.00   38.79  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 68.63   413.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 773.54 07-JAN-18:05
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 51.04 26-FEB-13:10 922.81 12-FEB-01:00
March 1306.65 01-MAR-10:09 1358.45 16-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 30.37 11-MAR-16:00 579.13 22-MAR-03:00
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 52.18 16-APR-12:00 314.89 05-APR-05:00
May 1306.65 01-MAY-09:09 947.97 24-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 59.86 07-MAY-12:10 252.71 10-MAY-04:00
June 1306.65 01-JUN-09:09 774.31 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 169.71 11-JUN-15:00 181.45 07-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 156.23 08-JUL-18:53 130.28 28-JUL-22:00
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 164.53 06-AUG-14:00 87.14 25-AUG-05:00
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 67.29 17-SEP-15:10 172.13 29-SEP-05:00
October 1306.65 02-OCT-09:09 1358.45 13-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 67.49 08-OCT-13:53 342.09 28-OCT-04:00
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 28.03 19-NOV-15:00 523.62 30-NOV-22:03
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 859.03 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   774.31   1435.25   0.00 0.00 0.00 0.00 0.00   87.14  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 169.71   922.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 860.01 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 511.09 07-JAN-18:05
February 805.43 01-FEB-08:09 860.01 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 24.01 26-FEB-15:30 614.39 11-FEB-19:00
March 805.43 01-MAR-08:09 860.01 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 20.93 11-MAR-18:03 381.73 22-MAR-03:00
April 805.43 03-APR-07:10 750.07 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 27.47 08-APR-17:20 208.79 05-APR-05:00
May 805.43 01-MAY-07:10 450.21 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 36.29 21-MAY-17:00 167.58 10-MAY-04:00
June 805.43 01-JUN-07:10 450.21 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 105.16 11-JUN-15:00 121.23 07-JUN-03:00
July 805.43 03-JUL-07:10 600.14 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 107.89 08-JUL-18:53 84.56 28-JUL-22:00
August 805.43 01-AUG-07:10 750.07 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 106.21 06-AUG-14:00 57.44 25-AUG-05:00
September 805.43 01-SEP-07:10 750.07 05-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 47.12 17-SEP-15:10 113.61 29-SEP-05:00
October 805.43 02-OCT-07:10 860.01 19-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 36.54 09-OCT-16:00 226.11 28-OCT-04:00
November 805.43 01-NOV-07:10 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 16.26 19-NOV-15:00 348.70 30-NOV-22:03
December 805.43 01-DEC-08:09 860.01 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.75 12-DEC-15:00 571.01 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   450.21   908.57   0.00 0.00 0.00 0.00 0.00   57.44  
Maximum of Months 805.43   860.01   908.57   0.00 0.00 0.00 0.00 107.89   614.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 782.01 07-JAN-18:05
February 1306.65 01-FEB-10:09 1358.45 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 8.69 28-FEB-15:00 955.95 11-FEB-19:00
March 1306.65 01-MAR-10:09 1358.45 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 22.18 30-MAR-16:00 582.02 22-MAR-03:00
April 1306.65 03-APR-09:09 1184.79 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 24.95 08-APR-17:20 315.79 05-APR-05:00
May 1306.65 01-MAY-09:09 947.97 02-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 47.80 07-MAY-12:10 253.91 10-MAY-04:00
June 1306.65 01-JUN-09:09 947.97 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 158.78 11-JUN-15:00 181.81 07-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 19-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 154.01 08-JUL-18:53 130.53 28-JUL-22:00
August 1306.65 01-AUG-09:09 1184.79 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 150.31 06-AUG-13:56 87.63 25-AUG-05:00
September 1306.65 01-SEP-09:09 1358.45 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 43.24 17-SEP-14:48 172.68 29-SEP-05:00
October 1306.65 02-OCT-09:09 1358.45 19-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 21.50 09-OCT-15:38 352.27 28-OCT-04:00
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 529.50 07-NOV-02:00
December 1306.65 01-DEC-10:09 1358.45 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 873.40 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   947.97   1435.24   0.00 0.00 0.00 0.00 0.00   87.63  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 158.78   955.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 515.32 07-JAN-18:10
February 827.17 01-FEB-10:09 859.95 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 36.28 26-FEB-13:10 646.49 11-FEB-18:15
March 827.17 01-MAR-10:09 859.95 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 14.78 30-MAR-16:00 384.06 22-MAR-03:00
April 827.17 03-APR-09:09 859.95 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 38.32 16-APR-12:00 207.79 05-APR-05:00
May 827.17 01-MAY-09:09 750.02 24-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 45.68 07-MAY-12:10 170.66 10-MAY-04:00
June 827.17 01-JUN-09:09 600.10 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 94.54 11-JUN-15:16 122.77 07-JUN-03:00
July 827.17 03-JUL-09:09 750.02 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 97.75 08-JUL-18:53 86.18 28-JUL-22:00
August 827.17 01-AUG-09:09 750.02 23-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 107.96 06-AUG-14:00 59.05 25-AUG-05:00
September 827.17 01-SEP-09:09 859.95 27-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 47.16 17-SEP-12:10 113.44 29-SEP-05:00
October 827.17 02-OCT-09:09 859.95 06-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 34.94 08-OCT-13:53 228.36 28-OCT-04:00
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.21 27-NOV-13:00 348.93 30-NOV-22:03
December 827.17 01-DEC-10:09 859.95 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 569.56 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   600.10   908.57   0.00 0.00 0.00 0.00 0.00   59.05  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 107.96   646.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1095.50 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.50 26-FEB-15:00 1349.79 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.67 11-MAR-16:00 844.27 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.35 16-APR-11:53 437.66 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.35 07-MAY-11:53 358.18 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.37 11-JUN-15:00 247.15 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 186.94 08-JUL-18:53 175.77 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.61 06-AUG-14:00 119.97 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.92 17-SEP-14:55 248.83 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.72 08-OCT-13:53 504.76 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.98 19-NOV-15:00 747.53 07-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1280.56 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   119.97  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 196.61   1349.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1360.61 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.66 26-FEB-15:13 1673.81 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.14 11-MAR-16:00 1031.62 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.55 16-APR-12:00 553.28 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.69 07-MAY-12:10 453.82 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.10 11-JUN-15:00 315.08 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.32 08-JUL-18:53 220.25 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 259.78 06-AUG-14:00 150.49 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.34 17-SEP-15:00 306.32 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.72 08-OCT-13:53 602.73 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96.30 19-NOV-15:00 912.15 07-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1539.35 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   150.49  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.10   1673.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1452.66 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.12 26-FEB-15:00 1726.25 11-FEB-18:05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.56 11-MAR-16:00 960.81 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.54 16-APR-11:53 531.62 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.74 07-MAY-11:53 409.84 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.73 11-JUN-15:10 310.93 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 208.27 08-JUL-18:53 235.99 01-JUL-20:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.06 06-AUG-13:52 145.49 23-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.41 17-SEP-15:00 265.30 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.46 08-OCT-13:53 560.72 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.95 19-NOV-15:00 915.05 30-NOV-22:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1416.76 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   145.49  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 208.27   1726.25  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12522.50 31-JAN-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
February 17977.16 28-FEB-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
March 21022.54 31-MAR-06:03 3811.58 6444.06 30584.54 0.00 0.00 0.00 0.00 0.00 0.00
April 30348.25 18-APR-06:03 5082.11 8592.08 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
May 35859.96 30-MAY-06:03 3811.58 6444.06 30584.54 0.00 0.00 0.00 0.00 0.00 0.00
June 38483.59 26-JUN-05:12 2541.06 2863.91 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
July 40732.33 07-JUL-04:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
August 40723.27 03-AUG-04:02 0.00 1058.67 28210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 36090.67 18-SEP-06:02 6352.64 10740.11 50974.24 0.00 0.00 0.00 0.00 0.00 0.00
October 35125.05 10-OCT-06:02 6352.64 10740.11 50974.24 0.00 0.00 0.00 0.00 0.00 0.00
November 20107.09 06-NOV-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
December 16630.37 14-DEC-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12522.50   0.00 1058.67 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40732.33   6352.64 10740.11 50974.24 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1586.00 28-JAN-17:25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.80
February 3588.69 26-FEB-14:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.52 0.00
March 6839.98 30-MAR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.36 0.00
April 7782.06 17-APR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.95 0.00
May 8642.68 30-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.09 0.00
June 9260.24 27-JUN-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.47 0.00
July 10318.28 07-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.85 0.00
August 10435.40 01-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.42 0.00
September 8963.05 06-SEP-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.68 0.00
October 6841.69 10-OCT-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.14 0.00
November 3359.21 05-NOV-14:43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.06
December 2489.44 10-DEC-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73.20
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1586.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10435.40   0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.47 73.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1927.05 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199.07
February 2142.33 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 216.80
March 2225.04 30-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.44 0.00
April 3028.98 06-APR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129.09
May 3624.57 30-MAY-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.94 0.00
June 3981.13 26-JUN-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.43
July 4501.11 17-JUL-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.99
August 4289.30 02-AUG-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.83 0.00
September 3935.45 07-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.53 0.00
October 2710.89 11-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.72 0.00
November 1808.33 08-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.65
December 2067.57 09-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.14
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1808.33   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4501.11   0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.83 216.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1763.09 13-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.22
February 2471.41 23-FEB-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.19
March 2582.88 06-MAR-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.62
April 3140.24 06-APR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 103.10
May 3959.92 30-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.22 0.00
June 4178.93 26-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.06 0.00
July 4662.67 10-JUL-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.45 0.00
August 4688.62 18-AUG-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.18 0.00
September 4587.76 11-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.80 0.00
October 3550.87 11-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.34 0.00
November 1933.14 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 144.46
December 2238.72 15-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.85
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1763.09   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4688.62   0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.45 144.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 8954.73 31-JAN-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 10784.10 28-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 14149.26 30-MAR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 15068.27 18-APR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 17207.12 30-MAY-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 29557.58 26-JUN-05:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
July 31415.80 07-JUL-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
August 32004.97 03-AUG-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 17698.49 11-SEP-06:03 3811.58 6444.06 9077.76 0.00 0.00 0.00 0.00 0.00 0.00
October 15679.81 11-OCT-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 11741.33 06-NOV-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 9775.03 13-DEC-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 8954.73   0.00 1058.67 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32004.97   6035.01 6444.06 12210.28 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 9120.56 20-JAN-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 10610.98 28-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 16101.24 30-MAR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 17150.42 17-APR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 19397.47 30-MAY-15:30 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 32434.12 26-JUN-05:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
July 33163.23 07-JUL-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
August 33562.07 14-AUG-04:02 0.00 1058.67 12210.28 0.00 0.00 0.00 0.00 0.00 0.00
September 19449.84 07-SEP-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 16567.35 11-OCT-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 10317.21 06-NOV-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 9805.13 13-DEC-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 9120.56   0.00 1058.67 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 33562.07   6035.01 6443.98 12210.28 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1879.57 31-JAN-16:50 1272.23 947.97 1435.25 0.00 0.00 0.00 0.00 0.00 12.39
February 2529.64 28-FEB-15:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 1.53
March 4688.03 30-MAR-15:50 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 26.15 0.00
April 5065.85 19-APR-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.38 0.00
May 6513.62 30-MAY-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 22.94 0.00
June 7512.76 25-JUN-18:53 0.00 143.99 1544.41 0.00 0.00 0.00 0.00 47.25 0.00
July 11780.92 16-JUL-18:32 0.00 179.99 1930.52 0.00 0.00 0.00 0.00 44.08 0.00
August 8410.81 20-AUG-16:42 334.80 179.99 2392.08 0.00 0.00 0.00 0.00 19.85 0.00
September 6347.10 06-SEP-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 23.19 0.00
October 4395.39 02-OCT-14:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 14.31 0.00
November 2158.84 02-NOV-15:50 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 7.94
December 2011.61 13-DEC-15:00 1306.65 774.31 1435.25 0.00 0.00 0.00 0.00 0.00 15.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1879.57   0.00 143.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11780.92   1306.65 947.97 2392.08 0.00 0.00 0.00 0.00 47.25 15.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1547.08 31-JAN-15:10 805.43 450.21 908.57 0.00 0.00 0.00 0.00 0.00 5.32
February 2184.68 27-FEB-10:40 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 25.43
March 3653.22 30-MAR-11:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 7.04
April 7866.22 16-APR-10:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 27.44
May 11629.01 07-MAY-09:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 35.17
June 11635.36 04-JUN-08:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 28.34
July 11628.06 02-JUL-10:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 3.98
August 10983.14 27-AUG-10:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 3.36 0.00
September 9326.65 24-SEP-10:43 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 5.53 0.00
October 4472.78 11-OCT-10:30 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.53 0.00
November 1868.30 06-NOV-10:40 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 38.98
December 1641.63 12-DEC-15:10 805.43 450.21 908.57 0.00 0.00 0.00 0.00 0.00 0.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1547.08   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11635.36   827.22 450.21 1514.29 0.00 0.00 0.00 0.00 5.53 38.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4693.13 11-JAN-14:30 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 38.81
February 13787.20 26-FEB-14:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 36.52
March 9614.19 30-MAR-13:40 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 18.93 0.00
April 13094.67 16-APR-14:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 17.68 0.00
May 7824.51 29-MAY-13:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 20.02 0.00
June 8968.21 25-JUN-16:12 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 147.37 0.00
July 13554.27 16-JUL-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 56.89 0.00
August 13996.96 20-AUG-14:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 40.34 0.00
September 14325.03 24-SEP-14:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 17.20 0.00
October 14407.92 09-OCT-14:23 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 1.47 0.00
November 14006.45 11-NOV-14:23 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 117.26
December 6339.95 08-DEC-14:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 97.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4693.13   267.84 143.99 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14407.92   1306.65 647.98 2392.06 0.00 0.00 0.00 0.00 147.37 117.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1807.67 20-JAN-16:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 20.61
February 4229.84 27-FEB-17:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 2.60
March 6374.77 30-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 17.64 0.00
April 11819.88 09-APR-17:33 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 28.75
May 11759.97 21-MAY-18:23 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 34.21
June 13305.25 11-JUN-16:02 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 70.91 0.00
July 13218.32 23-JUL-18:32 0.00 113.94 1222.09 0.00 0.00 0.00 0.00 12.01 0.00
August 13200.41 13-AUG-17:02 0.00 136.73 1466.51 0.00 0.00 0.00 0.00 32.89 0.00
September 8983.04 17-SEP-17:23 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 33.54
October 6631.95 11-OCT-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 6.99 0.00
November 3847.37 06-NOV-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 18.87
December 1946.68 11-DEC-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 6.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1807.67   0.00 91.15 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13305.25   805.38 410.20 1514.28 0.00 0.00 0.00 0.00 70.91 34.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1780.93 31-JAN-16:40 1272.23 774.31 1435.25 0.00 0.00 0.00 0.00 0.00 6.22
February 2032.48 28-FEB-15:20 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 5.18 0.00
March 2722.38 30-MAR-16:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 14.26 0.00
April 3045.32 19-APR-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 6.75 0.00
May 4627.94 30-MAY-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.29 0.00
June 5399.13 28-JUN-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 27.34 0.00
July 5936.11 10-JUL-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 26.10 0.00
August 5975.69 09-AUG-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 6.79 0.00
September 5675.74 06-SEP-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.43 0.00
October 4078.61 02-OCT-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 7.26 0.00
November 2247.97 05-NOV-12:53 200.88 107.99 1435.25 0.00 0.00 0.00 0.00 0.00 12.50
December 1996.32 13-DEC-13:30 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 8.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1780.93   200.88 107.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5975.69   1272.23 774.31 1435.25 0.00 0.00 0.00 0.00 27.34 12.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1350.15 31-JAN-15:00 827.22 450.21 908.57 0.00 0.00 0.00 0.00 0.00 2.53
February 1947.91 27-FEB-10:40 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 13.45
March 2651.78 14-MAR-11:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 4.97
April 4358.38 17-APR-10:10 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 1.00
May 7219.48 07-MAY-09:23 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 16.99
June 8365.43 11-JUN-10:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 6.97
July 10184.10 04-JUL-09:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.05 0.00
August 10427.76 27-AUG-09:52 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 0.73
September 6326.20 08-SEP-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 2.87 0.00
October 4477.17 10-OCT-10:20 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.31 0.00
November 2491.47 06-NOV-10:10 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 20.29
December 1480.98 13-DEC-12:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 4.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1350.15   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10427.76   827.22 450.21 1817.15 0.00 0.00 0.00 0.00 2.87 20.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2752.56 28-JAN-14:40 137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 16.83
February 9592.97 26-FEB-14:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 18.15
March 7774.39 30-MAR-16:10 401.76 359.99 797.35 0.00 0.00 0.00 0.00 2811.40 0.00
April 7892.78 17-APR-16:10 401.76 359.99 797.35 0.00 0.00 0.00 0.00 3713.92 0.00
May 9042.73 30-MAY-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 4174.38 0.00
June 9864.54 06-JUN-16:20 401.76 359.99 797.35 0.00 0.00 0.00 0.00 6838.59 0.00
July 10295.70 07-JUL-16:10 1205.27 1079.96 2392.06 0.00 0.00 0.00 0.00 7668.83 0.00
August 11343.71 27-AUG-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 52.25 0.00
September 10184.63 07-SEP-12:00 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 4536.21 0.00
October 11980.45 09-OCT-14:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 1.28
November 11569.44 11-NOV-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 66.64
December 5911.67 12-DEC-13:50 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 158.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2752.56   137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11980.45   1272.23 1079.96 2392.06 0.00 0.00 0.00 0.00 7668.83 158.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1459.65 23-JAN-17:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 24.61
February 3101.61 27-FEB-17:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 1.34
March 4311.14 30-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 9.51 0.00
April 4904.03 17-APR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 3.57 0.00
May 7058.10 29-MAY-16:03 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 9.81 0.00
June 10543.48 04-JUN-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 18.16 0.00
July 10831.42 04-JUL-17:52 0.00 136.73 1466.51 0.00 0.00 0.00 0.00 16.90 0.00
August 11198.16 13-AUG-16:51 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 14.29 0.00
September 8989.00 04-SEP-16:42 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 4.83 0.00
October 8608.05 09-OCT-16:53 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 0.00 0.32
November 3870.44 06-NOV-16:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 12.02
December 1628.40 11-DEC-16:10 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 4.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1459.65   0.00 91.15 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11198.16   805.38 410.20 2119.99 0.00 0.00 0.00 0.00 18.16 24.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1837.19 31-JAN-16:50 1272.23 947.97 1435.25 0.00 0.00 0.00 0.00 0.00 10.93
February 2570.82 28-FEB-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.94 0.00
March 4181.98 30-MAR-16:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 22.18 0.00
April 4616.96 18-APR-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 3.91 0.00
May 5906.83 30-MAY-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 19.17 0.00
June 7038.03 26-JUN-05:12 535.68 603.74 2551.55 0.00 0.00 0.00 0.00 0.00 5.26
July 8473.77 16-JUL-18:32 0.00 179.99 1930.52 0.00 0.00 0.00 0.00 38.88 0.00
August 7978.78 14-AUG-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 15.46
September 5789.69 06-SEP-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 19.39 0.00
October 4130.94 02-OCT-14:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.02 0.00
November 2134.59 03-NOV-15:20 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 9.82
December 1991.65 13-DEC-13:30 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 13.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1837.19   0.00 179.99 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8473.77   1306.65 947.97 2574.02 0.00 0.00 0.00 0.00 38.88 15.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1509.35 31-JAN-12:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 16.74
February 2775.84 27-FEB-10:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 26.57
March 3785.78 13-MAR-10:20 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 18.28
April 6883.55 16-APR-10:53 127.17 68.37 908.57 0.00 0.00 0.00 0.00 0.00 4.01
May 11216.85 07-MAY-09:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 32.59
June 11182.77 11-JUN-09:43 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 19.92
July 11641.57 04-JUL-09:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 1.98
August 11959.36 27-AUG-09:52 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 2.47
September 9841.98 04-SEP-10:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.70 0.00
October 4676.47 11-OCT-10:20 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 0.91
November 2668.40 06-NOV-09:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 30.97
December 1624.83 13-DEC-12:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 7.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1509.35   127.17 68.37 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11959.36   805.43 410.22 1817.15 0.00 0.00 0.00 0.00 0.70 32.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4931.02 27-JAN-14:30 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 57.76
February 11176.03 26-FEB-14:03 200.88 107.99 1435.24 0.00 0.00 0.00 0.00 0.00 38.34
March 9038.58 30-MAR-13:40 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 15.88 0.00
April 7788.49 17-APR-13:50 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 6.45 0.00
May 7220.57 29-MAY-13:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 13.00 0.00
June 7091.88 26-JUN-05:12 535.68 603.74 2551.53 0.00 0.00 0.00 0.00 0.00 5.26
July 10474.81 16-JUL-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 48.31 0.00
August 12376.46 27-AUG-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 78.50 0.00
September 9821.06 17-SEP-14:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 27.04 0.00
October 12812.45 09-OCT-14:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 0.59
November 12744.58 11-NOV-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 109.92
December 6846.84 08-DEC-14:00 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 79.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4931.02   200.88 107.99 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12812.45   1306.65 647.98 2551.53 0.00 0.00 0.00 0.00 78.50 109.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1683.29 27-JAN-16:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 59.58
February 4142.88 27-FEB-17:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 2.13
March 5986.48 30-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 14.78 0.00
April 11160.22 09-APR-17:12 0.00 91.15 977.67 0.00 0.00 0.00 0.00 0.00 20.47
May 11931.91 21-MAY-17:32 0.00 113.94 1222.09 0.00 0.00 0.00 0.00 0.00 20.58
June 11898.51 11-JUN-15:52 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 66.43 0.00
July 12405.08 04-JUL-17:52 0.00 136.73 1466.51 0.00 0.00 0.00 0.00 23.51 0.00
August 12819.98 13-AUG-16:51 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 18.95 0.00
September 10801.72 04-SEP-16:12 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 8.26 0.00
October 9027.45 09-OCT-16:12 169.55 91.15 1211.42 0.00 0.00 0.00 0.00 5.63 0.00
November 4017.67 06-NOV-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 15.59
December 1835.65 11-DEC-15:50 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 6.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1683.29   0.00 91.15 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12819.98   805.38 410.20 2119.99 0.00 0.00 0.00 0.00 66.43 59.58



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.158473E+12 242474.07 09-JAN-07:10 0.00 0.00
February 0.126487E+12 242674.82 13-FEB-07:10 0.00 0.00
March 0.121093E+12 115730.18 30-MAR-15:09 0.00 0.00
April 0.116727E+12 120405.67 17-APR-15:39 0.00 0.00
May 0.136661E+12 135078.04 30-MAY-15:09 0.00 0.00
June 0.154349E+12 144052.45 27-JUN-15:39 0.00 0.00
July 0.160297E+12 156832.63 07-JUL-15:00 0.00 0.00
August 0.174382E+12 155392.88 01-AUG-15:20 0.00 0.00
September 0.138300E+12 148263.80 07-SEP-15:50 0.00 0.00
October 0.121614E+12 128803.71 10-OCT-15:00 0.00 0.00
November 0.115053E+12 155979.72 22-NOV-07:10 0.00 0.00
December 0.127493E+12 204674.89 18-DEC-07:10 0.00 0.00
           
Annual Sum or Average 0.165093E+13     0.00 0.00
Minimum of Months 0.115053E+12 115730.18   0.00 0.00
Maximum of Months 0.174382E+12 242674.82   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.258642E+11 0.544208E+10 0.605851E+11 0.225893E+10 0.391294E+10 12379742.02 0.542898E+11 0.149187E+10 0.00 0.00 0.00 0.461605E+10 0.00
February 0.235047E+11 0.447543E+10 0.548702E+11 0.204972E+10 0.366096E+10 11196021.66 0.300341E+11 0.368308E+10 0.00 0.00 0.00 0.419803E+10 0.00
March 0.271449E+11 0.443078E+10 0.627783E+11 0.235658E+10 0.448288E+10 12675672.10 0.469267E+10 0.104035E+11 0.00 0.00 0.00 0.479055E+10 0.00
April 0.239402E+11 0.378945E+10 0.586172E+11 0.219335E+10 0.477705E+10 11960507.72 0.144371E+10 0.178849E+11 0.00 0.00 0.00 0.406909E+10 0.00
May 0.256470E+11 0.345949E+10 0.616817E+11 0.230726E+10 0.636227E+10 12527707.06 0.184999E+09 0.329725E+11 0.00 0.00 0.00 0.403284E+10 0.00
June 0.254527E+11 0.317507E+10 0.604966E+11 0.226944E+10 0.867685E+10 12231776.97 25625123.02 0.505342E+11 0.00 0.00 0.00 0.370659E+10 0.00
July 0.238434E+11 0.336986E+10 0.597911E+11 0.223024E+10 0.941242E+10 12256437.81 0.00 0.582902E+11 0.00 0.00 0.00 0.334732E+10 0.00
August 0.267688E+11 0.373343E+10 0.627783E+11 0.235633E+10 0.105009E+11 12675672.10 0.00 0.645639E+11 0.00 0.00 0.00 0.366739E+10 0.00
September 0.241495E+11 0.405491E+10 0.585950E+11 0.219223E+10 0.723327E+10 11960507.72 29735518.16 0.385698E+11 0.00 0.00 0.00 0.346322E+10 0.00
October 0.256123E+11 0.470282E+10 0.605962E+11 0.225948E+10 0.515667E+10 12379742.02 0.241262E+10 0.170155E+11 0.00 0.00 0.00 0.384583E+10 0.00
November 0.254175E+11 0.511872E+10 0.591197E+11 0.220156E+10 0.402099E+10 12059151.09 0.776702E+10 0.730791E+10 0.00 0.00 0.00 0.408746E+10 0.00
December 0.250509E+11 0.559902E+10 0.597800E+11 0.223021E+10 0.378800E+10 12256437.81 0.239666E+11 0.273895E+10 0.00 0.00 0.00 0.432677E+10 0.00
                           
Annual Sum or Average 0.302396E+12 0.513511E+11 0.719689E+12 0.269053E+11 0.719852E+11 0.146559E+09 0.124847E+12 0.305456E+12 0.00 0.00 0.00 0.481511E+11 0.00
Minimum of Months 0.235047E+11 0.317507E+10 0.548702E+11 0.204972E+10 0.366096E+10 11196021.66 0.00 0.149187E+10 0.00 0.00 0.00 0.334732E+10 0.00
Maximum of Months 0.271449E+11 0.559902E+10 0.627783E+11 0.235658E+10 0.105009E+11 12675672.10 0.542898E+11 0.645639E+11 0.00 0.00 0.00 0.479055E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 32642.50 03-JAN-08:09 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 05-JAN-17:10 5736.93 09-JAN-07:10 6.85 05-JAN-06:10 194745.30 09-JAN-07:10
February 32642.50 01-FEB-08:09 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 02-FEB-17:10 5356.42 13-FEB-07:10 6.85 02-FEB-06:10 195320.41 13-FEB-07:10
March 32642.50 21-MAR-07:10 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 06-MAR-08:09 7939.89 30-MAR-15:00 6.85 06-MAR-08:09 67621.75 23-MAR-06:10
April 31270.76 03-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 05-APR-16:10 8698.99 17-APR-15:50 6.85 01-APR-05:10 62984.65 06-APR-06:10
May 28326.84 24-MAY-07:10 5686.19 01-MAY-05:10 41699.26 01-MAY-07:10 1410.29 01-MAY-11:09 11470.28 30-MAY-14:00 6.85 01-MAY-05:10 15573.49 11-MAY-06:10
June 27609.75 23-JUN-07:10 5686.19 01-JUN-05:10 41699.26 01-JUN-07:10 1410.29 01-JUN-07:10 12047.04 27-JUN-15:30 6.85 01-JUN-05:10 5038.32 08-JUN-06:19
July 28960.31 27-JUL-07:10 5686.19 01-JUL-05:10 41699.26 03-JUL-07:10 1410.29 03-JUL-07:10 14010.14 07-JUL-15:00 6.85 09-JUL-16:00 0.00 01-JUL-00:10
August 30940.97 24-AUG-07:10 5686.19 01-AUG-05:10 41699.26 01-AUG-07:10 1410.29 03-AUG-12:09 14770.08 02-AUG-15:00 6.85 01-AUG-05:10 0.00 01-AUG-00:10
September 32312.69 29-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 01-SEP-07:10 13892.55 07-SEP-15:30 6.85 01-SEP-05:10 5409.03 29-SEP-06:10
October 32642.50 19-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 24-OCT-11:09 10121.98 11-OCT-15:30 6.85 26-OCT-07:10 67779.74 26-OCT-06:10
November 32642.50 01-NOV-07:10 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 13-NOV-12:09 5352.33 06-NOV-15:30 6.85 13-NOV-12:09 110842.85 22-NOV-07:10
December 32642.50 06-DEC-08:09 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 01-DEC-12:09 4189.95 04-DEC-07:10 6.85 04-DEC-12:09 158531.84 18-DEC-07:10
                             
Annual Sum or Average                            
Minimum of Months 27609.75   5686.19   41699.26   1410.29   4189.95   6.85   0.00  
Maximum of Months 32642.50   5686.19   41699.26   1410.29   14770.08   6.85   195320.41  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 14961.80 19-JAN-15:00 0.00 0.00 0.00 6214.50 30-JAN-12:00 0.00
February 19179.20 28-FEB-15:09 0.00 0.00 0.00 6214.45 01-FEB-12:00 0.00
March 35035.77 30-MAR-15:09 0.00 0.00 0.00 6145.01 02-MAR-12:00 0.00
April 38757.33 17-APR-15:39 0.00 0.00 0.00 5783.54 03-APR-11:20 0.00
May 51668.96 30-MAY-14:00 0.00 0.00 0.00 5375.54 01-MAY-11:20 0.00
June 59817.78 27-JUN-15:00 0.00 0.00 0.00 4970.88 01-JUN-11:50 0.00
July 70815.12 07-JUL-15:00 0.00 0.00 0.00 4599.01 03-JUL-11:30 0.00
August 69014.18 01-AUG-15:20 0.00 0.00 0.00 4595.98 31-AUG-11:20 0.00
September 62238.92 07-SEP-15:00 0.00 0.00 0.00 4957.59 29-SEP-11:39 0.00
October 45932.59 10-OCT-15:00 0.00 0.00 0.00 5361.65 31-OCT-11:39 0.00
November 20319.36 02-NOV-14:09 0.00 0.00 0.00 5776.30 30-NOV-12:20 0.00
December 19910.74 12-DEC-13:00 0.00 0.00 0.00 5939.74 29-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 14961.80   0.00 0.00 0.00 4595.98   0.00
Maximum of Months 70815.12   0.00 0.00 0.00 6214.50   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 242474.07 09-JAN-07:10 10880.98 22496.85 5686.19 975.80 5736.93 6.85 194745.30 0.00 0.00
February 242674.82 13-FEB-07:10 10880.98 22496.85 5686.19 975.80 5356.42 6.85 195320.41 0.00 0.00
March 115730.18 30-MAR-15:09 25681.07 41670.51 0.00 1410.29 7667.44 6.85 0.00 35035.77 0.00
April 120405.67 17-APR-15:39 25681.07 41670.51 0.00 1410.29 8696.75 6.85 0.00 38757.33 0.00
May 135078.04 30-MAY-15:09 25681.07 41670.51 0.00 1410.29 11404.85 6.85 0.00 51046.96 0.00
June 144052.45 27-JUN-15:39 25681.07 41670.51 0.00 1410.29 12025.89 6.85 0.00 59716.93 0.00
July 156832.63 07-JUL-15:00 25681.07 41670.51 0.00 1410.29 14010.14 6.85 0.00 70815.12 0.00
August 155392.88 01-AUG-15:20 25681.07 41670.51 0.00 1410.29 14128.84 6.85 0.00 69014.18 0.00
September 148263.80 07-SEP-15:50 25681.07 41670.51 0.00 1410.29 13802.22 6.85 0.00 62153.05 0.00
October 128803.71 10-OCT-15:00 25990.55 41670.51 0.00 1410.29 9916.01 6.85 0.00 45932.59 0.00
November 155979.72 22-NOV-07:10 10880.98 22496.85 5686.19 975.80 3427.79 6.85 110842.85 0.00 0.00
December 204674.89 18-DEC-07:10 10880.98 22496.85 5686.19 975.80 4157.04 6.85 158531.84 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 115730.18   10880.98 22496.85 0.00 975.80 3427.79 6.85 0.00 0.00 0.00
Maximum of Months 242674.82   25990.55 41670.51 5686.19 1410.29 14128.84 6.85 195320.41 70815.12 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.22 0.17 19.22 0.00 19.22 0.00 19.22
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.22 0.17 19.22 0.00 19.22 0.00 19.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.22 0.17 19.22 0.00 19.22 0.00 19.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 17.94 0.50 18.32 0.00 18.32 0.00 18.32
February 0.50 18.48 0.33 18.80 0.00 18.80 0.00 18.80
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.61 0.33 18.92 0.00 18.92 0.00 18.92
                 
Annual Sum or Average 1.83 18.27 1.17 18.62 0.00 18.62 0.00 18.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 18.61 0.50 18.92 0.00 18.92 0.00 18.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.00 16.76 4.33 17.19 0.00 17.19 0.00 17.19
February 8.33 16.41 3.50 16.84 0.00 16.84 0.00 16.84
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 27.32 0.33 27.32
July 0.00 0.00 0.00 0.00 2.83 27.48 1.83 27.48
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 17.19 0.00 17.19 0.00 17.19 0.00 17.19
December 2.33 18.20 1.50 18.68 0.00 18.68 0.00 18.68
                 
Annual Sum or Average 20.83 16.78 9.33 17.24 3.33 18.26 2.17 18.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.00 18.20 4.33 18.68 2.83 27.48 1.83 27.48



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.17 15.85 1.50 16.02 0.00 16.02 0.00 16.02
February 5.17 15.48 0.83 15.61 0.00 15.61 0.00 15.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.41 0.17 27.41
May 0.00 0.00 0.00 0.00 1.83 27.51 1.83 27.51
June 0.00 0.00 0.00 0.00 4.33 27.80 4.17 27.81
July 0.00 0.00 0.00 0.00 9.17 27.76 8.50 27.78
August 0.00 0.00 0.00 0.00 6.00 27.70 6.00 27.70
September 0.00 0.00 0.00 0.00 1.00 27.51 1.00 27.51
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 17.18 0.00 17.18 0.00 17.18 0.00 17.18
December 1.17 16.95 0.33 17.45 0.00 17.45 0.00 17.45
                 
Annual Sum or Average 13.67 15.82 2.67 16.01 22.50 22.80 21.67 24.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.17 17.18 1.50 17.45 9.17 27.80 8.50 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 16.50 1.17 16.77 0.00 16.77 0.00 16.77
February 4.00 16.05 1.17 16.32 0.67 17.59 0.67 18.61
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.38 0.67 27.38
May 0.00 0.00 0.00 0.00 0.33 27.26 0.33 27.26
June 0.00 0.00 0.00 0.00 1.50 27.43 1.33 27.43
July 0.00 0.00 0.00 0.00 4.17 27.53 3.33 27.55
August 0.00 0.00 0.00 0.00 5.00 27.67 4.83 27.67
September 0.00 0.00 0.00 0.00 2.00 27.56 2.00 27.56
October 0.00 0.00 0.00 0.00 3.33 27.65 3.33 27.65
November 0.00 0.00 0.00 0.00 1.00 27.57 1.00 27.57
December 0.83 17.40 0.33 17.89 0.00 17.89 0.00 17.89
                 
Annual Sum or Average 9.67 16.39 2.67 16.69 18.67 23.24 17.50 24.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.83 17.40 1.17 17.89 5.00 27.67 4.83 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.33 15.94 1.83 16.13 0.00 16.13 0.00 16.13
February 5.67 15.56 1.67 15.66 0.00 15.66 0.00 15.66
March 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
April 0.00 0.00 0.00 0.00 1.33 27.58 1.00 27.56
May 0.00 0.00 0.00 0.00 3.00 27.84 1.83 27.85
June 0.00 0.00 0.00 0.00 5.00 28.01 2.83 28.05
July 0.00 0.00 0.00 0.00 8.67 28.16 4.17 28.17
August 0.00 0.00 0.00 0.00 5.67 28.12 3.00 28.17
September 0.00 0.00 0.00 0.00 2.17 27.57 1.50 27.57
October 0.00 0.00 0.00 0.00 0.50 27.40 0.50 27.40
November 0.17 17.16 0.00 17.16 0.00 17.16 0.00 17.16
December 1.17 17.28 0.33 17.71 0.00 17.71 0.00 17.71
                 
Annual Sum or Average 14.33 15.91 3.83 16.08 26.50 23.15 15.00 24.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.66 0.00 15.66
Maximum of Months 7.33 17.28 1.83 17.71 8.67 28.16 4.17 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.83 0.50 19.07 0.00 19.07 0.00 19.07
February 0.50 18.85 0.33 19.23 0.00 19.23 0.00 19.23
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 18.84 0.83 19.13 0.00 19.13 0.00 19.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 18.85 0.50 19.23 0.00 19.23 0.00 19.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 17.12 0.00 17.12 0.00 17.12 0.00 17.12
February 0.17 17.05 0.00 17.05 0.00 17.05 0.00 17.05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.17 27.52 2.17 27.52
July 0.00 0.00 0.00 0.00 4.00 27.60 4.00 27.60
August 0.00 0.00 0.00 0.00 3.67 27.59 3.67 27.59
September 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
October 0.00 0.00 0.00 0.00 0.17 27.34 0.17 27.34
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.08 0.00 17.08 10.67 27.25 10.67 27.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 17.12 0.00 17.12 4.00 27.60 4.00 27.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 44.17 18.16 44.17 18.16 0.00 18.16 0.00 18.16
February 29.67 18.41 29.67 18.41 0.00 18.41 0.00 18.41
March 11.00 19.54 11.00 19.54 0.00 19.54 0.00 19.54
April 4.50 18.81 4.50 18.81 0.00 18.81 0.00 18.81
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.50 24.71 1.50 24.71
July 0.00 0.00 0.00 0.00 12.83 24.83 12.83 24.83
August 0.00 0.00 0.00 0.00 20.50 25.17 20.50 25.17
September 0.00 0.00 0.00 0.00 6.83 25.17 6.83 25.17
October 2.00 19.48 2.00 19.48 7.17 23.95 7.17 24.92
November 10.00 19.42 10.00 19.42 2.00 20.15 2.00 20.76
December 20.00 18.49 20.00 18.49 0.17 18.52 0.17 18.56
                 
Annual Sum or Average 121.33 18.55 121.33 18.55 51.00 19.73 51.00 20.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 44.17 19.54 44.17 19.54 20.50 25.17 20.50 25.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 17.10 0.00 17.10 0.00 17.10 0.00 17.10
February 0.17 17.14 0.00 17.14 0.00 17.14 0.00 17.14
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.83 27.35 0.17 27.35
June 0.00 0.00 0.00 0.00 2.67 27.69 1.33 27.70
July 0.00 0.00 0.00 0.00 5.83 27.83 2.83 27.83
August 0.00 0.00 0.00 0.00 4.67 27.80 2.50 27.82
September 0.00 0.00 0.00 0.00 1.50 27.40 1.00 27.41
October 0.00 0.00 0.00 0.00 0.50 27.36 0.50 27.36
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.12 0.00 17.12 16.00 27.50 8.33 27.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 17.14 0.00 17.14 5.83 27.83 2.83 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 18.45 0.83 18.85 0.00 18.85 0.00 18.85
February 0.83 18.28 0.50 18.73 0.00 18.73 0.00 18.73
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.41 0.17 19.41 0.00 19.41 0.00 19.41
                 
Annual Sum or Average 2.17 18.46 1.50 18.86 0.00 18.86 0.00 18.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.17 19.41 0.83 19.41 0.00 19.41 0.00 19.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.62 0.33 18.16 0.00 18.16 0.00 18.16
February 0.50 17.36 0.17 17.79 0.00 17.79 0.00 17.79
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.50 0.50 27.50
May 0.00 0.00 0.00 0.00 1.50 27.60 1.50 27.60
June 0.00 0.00 0.00 0.00 3.17 27.87 3.17 27.87
July 0.00 0.00 0.00 0.00 6.00 27.77 6.00 27.77
August 0.00 0.00 0.00 0.00 4.33 27.78 4.33 27.78
September 0.00 0.00 0.00 0.00 1.17 27.58 1.17 27.58
October 0.00 0.00 0.00 0.00 0.33 27.28 0.33 27.28
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 17.51 0.50 18.01 17.00 26.88 17.00 27.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.62 0.33 18.16 6.00 27.87 6.00 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.70 0.33 18.23 0.00 18.23 0.00 18.23
February 0.50 17.58 0.17 17.99 1.17 24.00 1.17 25.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.29 0.33 27.29
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 27.37 1.17 27.37
August 0.00 0.00 0.00 0.00 4.00 27.51 4.00 27.51
September 0.00 0.00 0.00 0.00 1.17 27.59 1.17 27.59
October 0.00 0.00 0.00 0.00 4.17 27.61 4.17 27.61
November 0.00 0.00 0.00 0.00 2.33 27.59 2.33 27.59
December 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
                 
Annual Sum or Average 1.17 17.65 0.50 18.13 14.50 26.56 14.50 27.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.70 0.33 18.23 4.17 27.61 4.17 27.61



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.60 0.33 18.14 0.00 18.14 0.00 18.14
February 0.50 17.44 0.17 17.87 0.00 17.87 0.00 17.87
March 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
April 0.00 0.00 0.00 0.00 0.83 27.63 0.50 27.60
May 0.00 0.00 0.00 0.00 2.50 27.74 1.50 27.73
June 0.00 0.00 0.00 0.00 4.00 27.91 2.17 27.94
July 0.00 0.00 0.00 0.00 7.33 28.03 3.67 28.03
August 0.00 0.00 0.00 0.00 5.00 27.98 2.67 28.01
September 0.00 0.00 0.00 0.00 1.83 27.54 1.50 27.55
October 0.00 0.00 0.00 0.00 0.50 27.44 0.50 27.44
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.17 17.53 0.50 18.03 22.17 27.20 12.67 27.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.60 0.33 18.14 7.33 28.03 3.67 28.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 22.75 15.83 22.72 15.83 22.68
February 399.00 23.21 7.67 23.23 0.50 23.23
March 209.83 23.83 97.17 24.10 0.00 24.10
April 59.17 23.85 210.00 24.57 0.00 24.57
May 1.50 24.00 409.00 24.55 0.00 24.55
June 0.00 0.00 449.00 24.42 0.00 24.42
July 0.00 0.00 497.00 24.47 0.00 24.47
August 0.00 0.00 514.00 24.40 0.00 24.40
September 0.00 0.00 458.83 24.48 0.00 24.48
October 28.33 23.66 229.17 24.63 0.00 24.63
November 212.33 23.84 68.50 24.09 0.00 24.09
December 433.50 23.51 10.83 23.54 0.00 23.54
             
Annual Sum or Average 1842.17 23.33 2967.00 24.06 16.33 24.05
Minimum of Months 0.00 0.00 7.67 22.72 0.00 22.68
Maximum of Months 498.50 24.00 514.00 24.63 15.83 24.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.20 156.83 21.04 156.83 20.94
February 451.33 21.80 75.50 21.64 75.50 21.51
March 436.33 22.90 21.00 22.96 0.00 22.96
April 266.00 23.21 88.33 23.48 0.00 23.48
May 89.00 23.30 244.83 24.03 0.00 24.03
June 33.67 23.46 365.33 24.20 0.00 24.20
July 11.33 23.11 437.50 24.25 0.00 24.25
August 0.00 0.00 470.00 24.25 0.00 24.25
September 59.00 23.15 311.00 24.15 0.00 24.15
October 286.00 22.98 86.50 23.26 0.00 23.26
November 470.50 22.73 0.00 22.73 0.00 22.73
December 494.67 21.76 29.67 21.71 29.67 21.66
             
Annual Sum or Average 3099.83 22.31 2286.50 22.97 262.00 22.86
Minimum of Months 0.00 0.00 0.00 21.04 0.00 20.94
Maximum of Months 502.00 23.46 470.00 24.25 156.83 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.64 307.17 20.49 307.17 20.42
February 452.67 21.23 143.83 21.01 143.83 20.88
March 463.67 22.31 35.33 22.33 15.83 22.28
April 314.67 22.86 63.33 23.07 0.67 23.07
May 138.50 23.15 216.00 23.81 0.00 23.81
June 45.33 23.31 353.83 24.15 0.00 24.15
July 16.17 22.87 429.67 24.24 0.00 24.24
August 3.17 23.38 456.67 24.24 0.00 24.24
September 117.83 22.97 252.67 23.86 0.00 23.86
October 380.50 22.48 58.50 22.68 1.33 22.67
November 486.50 21.87 46.00 21.75 46.00 21.66
December 497.00 21.05 183.00 20.86 183.00 20.76
             
Annual Sum or Average 3418.00 21.82 2546.00 22.40 697.83 22.18
Minimum of Months 3.17 20.64 35.33 20.49 0.00 20.42
Maximum of Months 502.00 23.38 456.67 24.24 307.17 24.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.14 415.33 20.04 415.33 20.00
February 451.17 20.71 252.67 20.49 252.67 20.39
March 465.33 21.68 110.17 21.60 83.00 21.44
April 319.17 22.35 107.17 22.63 22.33 22.53
May 146.83 22.87 261.00 23.76 0.17 23.76
June 45.33 23.60 392.67 24.26 8.83 24.29
July 38.17 24.59 454.33 24.45 23.50 24.51
August 17.67 25.01 488.67 24.36 12.33 24.39
September 166.83 23.10 271.50 23.86 17.00 23.90
October 408.17 21.92 83.17 22.12 29.33 22.09
November 485.00 21.19 157.83 20.98 157.83 20.84
December 497.00 20.42 333.33 20.25 333.33 20.18
             
Annual Sum or Average 3542.67 21.37 3327.83 22.01 1355.67 21.73
Minimum of Months 17.67 20.14 83.17 20.04 0.17 20.00
Maximum of Months 502.00 25.01 488.67 24.45 415.33 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.28 388.67 20.17 388.67 20.13
February 445.67 20.97 217.33 20.70 217.33 20.56
March 428.17 21.95 87.50 21.95 48.67 21.80
April 253.83 22.41 158.33 23.04 13.50 22.97
May 125.50 22.96 313.17 24.00 8.67 24.04
June 53.00 24.48 417.17 24.42 23.00 24.52
July 72.67 25.30 446.50 24.65 50.33 24.81
August 41.67 25.78 475.17 24.53 32.50 24.65
September 157.17 23.01 306.50 23.92 20.50 23.99
October 335.83 21.90 123.17 22.36 28.50 22.31
November 480.33 21.40 110.17 21.20 110.17 21.06
December 497.00 20.54 279.50 20.34 279.50 20.24
             
Annual Sum or Average 3392.83 21.56 3323.17 22.28 1221.33 22.06
Minimum of Months 41.67 20.28 87.50 20.17 8.67 20.13
Maximum of Months 502.00 25.78 475.17 24.65 388.67 24.81



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 482.33 20.92 277.83 20.60 274.50 20.43
February 397.83 21.23 187.00 21.09 168.67 20.89
March 347.33 21.94 128.50 22.19 52.33 22.00
April 248.83 22.39 152.83 23.01 18.33 22.93
May 144.17 22.85 272.67 23.81 1.17 23.82
June 63.33 23.74 383.83 24.26 14.50 24.33
July 49.67 24.88 445.50 24.51 31.50 24.60
August 35.83 25.97 487.00 24.50 30.67 24.60
September 138.17 23.32 309.33 24.09 25.00 24.19
October 282.17 22.16 179.17 22.98 28.17 23.01
November 377.33 21.69 129.00 21.79 81.67 21.59
December 449.00 21.14 210.33 20.85 198.83 20.65
             
Annual Sum or Average 3016.00 21.83 3163.00 22.61 925.33 22.38
Minimum of Months 35.83 20.92 128.50 20.60 1.17 20.43
Maximum of Months 482.33 25.97 487.00 24.51 274.50 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.30 370.50 20.15 370.50 20.08
February 436.00 20.78 237.33 20.60 232.33 20.49
March 413.17 21.58 122.83 21.68 72.50 21.52
April 290.17 22.15 146.83 22.76 20.00 22.70
May 175.17 22.73 265.50 23.69 8.17 23.74
June 87.50 23.56 377.83 24.23 19.33 24.32
July 72.17 24.40 418.33 24.46 35.33 24.57
August 42.17 25.03 452.83 24.44 25.00 24.54
September 184.50 22.86 260.33 23.77 23.50 23.86
October 374.83 21.80 113.33 22.24 28.17 22.22
November 457.67 21.20 142.83 21.04 135.33 20.90
December 497.00 20.57 292.50 20.36 292.50 20.26
             
Annual Sum or Average 3532.33 21.45 3201.00 22.12 1262.67 21.89
Minimum of Months 42.17 20.30 113.33 20.15 8.17 20.08
Maximum of Months 502.00 25.03 452.83 24.46 370.50 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.47 400.83 20.40 400.83 20.37
February 454.00 20.87 224.50 20.70 224.50 20.61
March 500.83 21.69 60.83 21.59 57.00 21.49
April 421.00 22.32 31.33 22.36 12.33 22.31
May 223.33 23.01 179.00 23.56 4.00 23.57
June 38.17 23.56 381.67 24.20 2.67 24.21
July 15.00 24.45 466.50 24.37 8.50 24.38
August 5.67 26.08 503.50 24.33 5.67 24.35
September 74.17 23.71 325.17 24.22 16.83 24.27
October 366.83 22.67 83.83 22.94 6.33 22.97
November 477.17 21.99 36.50 21.91 35.17 21.82
December 497.00 20.96 231.17 20.82 231.17 20.74
             
Annual Sum or Average 3575.17 21.69 2924.83 22.29 1005.00 22.06
Minimum of Months 5.67 20.47 31.33 20.40 2.67 20.37
Maximum of Months 502.00 26.08 503.50 24.37 400.83 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.66 352.17 20.56 352.17 20.51
February 446.83 21.25 178.67 21.01 178.67 20.88
March 459.33 22.20 35.67 22.17 21.50 22.09
April 301.33 22.59 91.50 22.97 4.33 22.94
May 142.50 23.06 284.00 24.00 4.83 24.01
June 23.50 24.63 433.17 24.40 9.17 24.45
July 36.83 25.45 470.83 24.59 25.50 24.68
August 18.33 26.80 508.50 24.51 18.33 24.58
September 60.33 23.91 380.17 24.36 19.17 24.43
October 256.33 22.69 148.33 23.31 7.33 23.33
November 446.00 22.36 31.00 22.37 14.50 22.32
December 497.00 21.20 144.33 21.04 144.33 20.94
             
Annual Sum or Average 3190.33 21.92 3058.33 22.69 799.83 22.51
Minimum of Months 18.33 20.66 31.00 20.56 4.33 20.51
Maximum of Months 502.00 26.80 508.50 24.59 352.17 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 492.83 20.85 250.83 20.59 246.00 20.44
February 410.33 21.17 152.67 21.01 139.00 20.81
March 405.67 22.02 80.00 22.19 29.33 22.07
April 341.33 22.36 88.83 22.68 11.17 22.61
May 217.00 22.77 211.00 23.51 12.00 23.51
June 95.83 23.46 391.33 24.10 46.67 24.08
July 75.33 23.94 470.83 24.33 66.50 24.30
August 83.17 24.37 509.33 24.41 82.17 24.41
September 94.67 23.71 395.17 24.32 43.67 24.37
October 224.67 22.67 219.67 23.59 28.83 23.65
November 346.50 22.34 79.50 22.74 9.83 22.68
December 447.33 21.48 89.67 21.39 70.00 21.20
             
Annual Sum or Average 3234.67 22.02 2938.83 22.81 785.17 22.66
Minimum of Months 75.33 20.85 79.50 20.59 9.83 20.44
Maximum of Months 492.83 24.37 509.33 24.41 246.00 24.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.66 343.17 20.53 343.17 20.48
February 443.50 21.07 187.00 20.89 184.50 20.77
March 441.50 21.98 66.17 22.04 34.00 21.95
April 331.17 22.50 86.00 22.86 5.00 22.83
May 165.33 23.02 251.50 23.85 5.83 23.87
June 39.17 23.92 406.33 24.33 8.00 24.37
July 33.17 25.11 464.67 24.50 21.00 24.57
August 17.17 26.73 506.50 24.49 17.17 24.56
September 65.83 23.82 374.83 24.34 19.17 24.41
October 278.33 22.68 138.67 23.25 7.00 23.28
November 436.17 22.17 35.67 22.19 20.67 22.13
December 494.67 21.17 163.83 21.01 163.83 20.90
             
Annual Sum or Average 3248.00 21.84 3024.33 22.60 829.33 22.41
Minimum of Months 17.17 20.66 35.67 20.53 5.00 20.48
Maximum of Months 502.00 26.73 506.50 24.50 343.17 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.42 388.33 20.32 388.33 20.28
February 450.67 20.99 191.83 20.75 191.83 20.62
March 457.00 22.08 72.00 22.07 41.67 21.96
April 292.67 22.67 92.67 23.01 5.00 22.98
May 109.83 23.17 288.33 23.98 0.00 23.98
June 26.00 23.93 415.33 24.29 6.33 24.31
July 20.33 24.70 475.50 24.43 13.67 24.46
August 8.17 25.73 505.00 24.36 8.17 24.38
September 100.00 23.44 301.83 24.11 17.17 24.16
October 383.00 22.38 77.33 22.65 11.33 22.66
November 479.67 21.71 70.33 21.56 70.33 21.44
December 497.00 20.81 257.00 20.63 257.00 20.55
             
Annual Sum or Average 3326.33 21.64 3135.50 22.34 1010.83 22.10
Minimum of Months 8.17 20.42 70.33 20.32 0.00 20.28
Maximum of Months 502.00 25.73 505.00 24.43 388.33 24.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.49 307.17 20.37 307.17 20.31
February 370.00 21.11 155.67 20.89 151.67 20.75
March 355.83 22.16 53.33 22.24 20.83 22.15
April 213.17 22.62 117.17 23.25 4.50 23.23
May 102.83 23.23 257.67 24.19 7.50 24.24
June 35.50 24.95 356.33 24.52 18.50 24.61
July 48.33 25.61 392.00 24.72 36.67 24.86
August 27.67 26.32 412.17 24.59 25.33 24.70
September 114.00 23.41 258.67 24.17 21.83 24.26
October 282.17 22.25 94.17 22.76 11.83 22.78
November 396.17 21.76 50.00 21.66 44.67 21.54
December 422.00 20.85 196.00 20.67 196.00 20.57
             
Annual Sum or Average 2794.67 21.78 2650.33 22.54 846.50 22.35
Minimum of Months 27.67 20.49 50.00 20.37 4.50 20.31
Maximum of Months 427.00 26.32 412.17 24.72 307.17 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 464.00 21.21 236.00 20.92 231.00 20.74
February 389.50 21.56 131.50 21.46 112.33 21.26
March 325.17 22.37 103.33 22.75 17.67 22.66
April 216.17 22.74 147.00 23.39 5.17 23.37
May 102.50 23.11 300.17 24.03 0.00 24.03
June 36.17 23.80 406.50 24.29 7.00 24.32
July 23.00 24.99 469.00 24.48 16.33 24.52
August 23.67 26.50 506.00 24.49 23.67 24.57
September 86.67 23.83 343.83 24.33 24.00 24.42
October 247.17 22.63 196.83 23.44 18.33 23.51
November 348.83 22.23 90.50 22.53 30.33 22.43
December 423.67 21.51 133.67 21.34 117.67 21.14
             
Annual Sum or Average 2686.50 22.11 3064.33 22.98 603.50 22.81
Minimum of Months 23.00 21.21 90.50 20.92 0.00 20.74
Maximum of Months 464.00 26.50 506.00 24.49 231.00 24.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.60 331.50 20.43 331.50 20.36
February 434.50 21.05 177.33 20.87 172.00 20.73
March 396.17 21.95 93.17 22.16 34.33 22.06
April 259.17 22.52 147.67 23.16 6.67 23.15
May 130.83 23.06 303.17 23.97 6.00 24.01
June 55.67 24.08 402.67 24.34 16.67 24.42
July 44.67 25.14 450.33 24.51 30.33 24.61
August 25.17 26.01 487.33 24.46 21.00 24.54
September 132.17 23.32 303.33 24.08 23.50 24.17
October 346.17 22.23 114.00 22.73 12.50 22.76
November 447.50 21.67 74.67 21.59 62.83 21.47
December 494.17 20.95 214.50 20.75 214.50 20.64
             
Annual Sum or Average 3268.17 21.72 3099.67 22.49 931.83 22.29
Minimum of Months 25.17 20.60 74.67 20.43 6.00 20.36
Maximum of Months 502.00 26.01 487.33 24.51 331.50 24.61



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.76128 26.49904 -0.1023 5.92357
February 454.00000 23.35070 27.57730 0.06430 5.96497
March 514.00000 24.13278 30.71820 0.31000 7.34901
April 485.00000 24.36195 35.58899 0.41598 8.96336
May 508.00000 24.45180 42.11154 -0.3436 8.08666
June 496.00000 24.39741 44.18842 -0.3133 7.59785
July 497.00000 24.46909 46.01325 -0.2740 7.14233
August 514.00000 24.40331 46.41372 -0.2827 7.17874
September 485.00000 24.45864 44.71597 -0.2993 7.50327
October 502.00000 24.34878 37.95864 0.43783 9.32608
November 489.00000 24.15895 28.80161 0.29879 7.19204
December 497.00000 23.59311 28.35409 0.12943 5.80023
           
Annual Sum or Average 5943.00000 24.07863 36.65257 0.00212 7.34358
Minimum of Months 454.00000 22.76128 26.49904 -0.3436 5.80023
Maximum of Months 514.00000 24.46909 46.41372 0.43783 9.32608



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.19826 28.38954 -0.4616 10.24733
February 454.00000 21.81663 29.31060 -0.2854 8.12978
March 514.00000 23.07351 33.00171 0.06941 6.01131
April 485.00000 23.63547 37.53142 0.24946 6.90534
May 508.00000 23.98776 43.41497 -0.5043 10.86304
June 496.00000 24.13103 45.18984 -0.4165 9.11700
July 497.00000 24.20806 47.15190 -0.3731 8.32393
August 514.00000 24.21223 47.52055 -0.3630 8.08726
September 485.00000 24.06793 45.90081 -0.4500 9.84892
October 502.00000 23.45982 40.44346 0.22257 6.79355
November 489.00000 22.77737 31.60356 -0.0214 5.79312
December 497.00000 21.76702 31.31480 -0.2827 7.53796
           
Annual Sum or Average 5943.00000 23.20489 38.47136 -0.2182 8.13976
Minimum of Months 454.00000 21.19826 28.38954 -0.5043 5.79312
Maximum of Months 514.00000 24.21223 47.52055 0.24946 10.86304



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.64460 28.65815 -0.6255 14.93324
February 454.00000 21.24126 29.84923 -0.4424 11.16163
March 514.00000 22.47512 33.54351 -0.0749 6.65757
April 485.00000 23.28444 37.72198 0.16617 6.66261
May 508.00000 23.84045 43.11214 -0.5493 12.19136
June 496.00000 24.08874 45.08945 -0.4195 9.30980
July 497.00000 24.19614 47.14051 -0.3642 8.27268
August 514.00000 24.19193 47.53732 -0.3568 8.00290
September 485.00000 23.86626 45.88100 -0.5205 11.68243
October 502.00000 22.84779 41.44855 0.07232 6.47259
November 489.00000 21.87554 32.78139 -0.2428 7.38729
December 497.00000 21.04825 32.32091 -0.4789 11.05945
           
Annual Sum or Average 5943.00000 22.81242 38.82818 -0.3192 9.46950
Minimum of Months 454.00000 20.64460 28.65815 -0.6255 6.47259
Maximum of Months 514.00000 24.19614 47.53732 0.16617 14.93324



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.13532 29.34022 -0.8139 21.71605
February 454.00000 20.73329 31.48270 -0.6096 15.77431
March 514.00000 21.89855 35.84826 -0.2217 8.64150
April 485.00000 22.95013 40.18476 0.09225 7.49464
May 508.00000 23.80352 44.98508 -0.5428 13.05017
June 496.00000 24.18687 46.34825 -0.3428 8.61554
July 497.00000 24.35592 48.99971 -0.2589 7.48716
August 514.00000 24.30023 49.52561 -0.2723 7.27414
September 485.00000 23.80677 48.57906 -0.5245 12.85690
October 502.00000 22.29891 45.30470 -0.0566 7.40487
November 489.00000 21.21374 35.74938 -0.4197 10.60407
December 497.00000 20.42011 33.12770 -0.6784 17.09555
           
Annual Sum or Average 5943.00000 22.52301 40.86109 -0.3860 11.46511
Minimum of Months 454.00000 20.13532 29.34022 -0.8139 7.27414
Maximum of Months 514.00000 24.35592 49.52561 0.09225 21.71605



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.27882 29.05740 -0.7577 19.46847
February 454.00000 21.03210 30.91381 -0.5150 13.94725
March 514.00000 22.29554 34.95857 -0.1041 7.84799
April 485.00000 23.27100 39.11762 0.20510 8.25851
May 508.00000 23.94540 44.06591 -0.4320 11.68668
June 496.00000 24.25846 45.74926 -0.2525 7.97144
July 497.00000 24.40982 48.34462 -0.1724 7.66514
August 514.00000 24.34146 48.92463 -0.1943 7.15381
September 485.00000 23.82705 47.91538 -0.4562 12.44253
October 502.00000 22.63300 44.09806 0.04679 7.86575
November 489.00000 21.44668 35.10909 -0.3424 9.38005
December 497.00000 20.53894 32.84287 -0.6258 15.34960
           
Annual Sum or Average 5943.00000 22.70363 40.16179 -0.2986 10.72196
Minimum of Months 454.00000 20.27882 29.05740 -0.7577 7.15381
Maximum of Months 514.00000 24.40982 48.92463 0.20510 19.46847



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.06259 28.07880 -0.5450 15.98909
February 454.00000 21.65020 29.99224 -0.3541 12.36549
March 514.00000 22.70948 33.92732 -0.0068 8.55840
April 485.00000 23.28836 38.99465 0.19288 8.41849
May 508.00000 23.83836 44.66315 -0.5135 12.83924
June 496.00000 24.16094 46.35957 -0.3461 9.00156
July 497.00000 24.36297 48.90488 -0.2477 7.64000
August 514.00000 24.34834 49.13608 -0.2242 7.15659
September 485.00000 23.97506 47.54817 -0.4195 11.59169
October 502.00000 23.07386 42.67820 0.16341 9.13704
November 489.00000 22.33089 33.20239 -0.1233 9.32334
December 497.00000 21.43862 31.42566 -0.3925 12.59063
           
Annual Sum or Average 5943.00000 23.03097 39.65132 -0.2342 10.36691
Minimum of Months 454.00000 21.06259 28.07880 -0.5450 7.15659
Maximum of Months 514.00000 24.36297 49.13608 0.19288 15.98909



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.29862 28.76945 -0.7583 19.98196
February 454.00000 20.92404 30.77567 -0.5462 14.70523
March 514.00000 22.09937 34.92119 -0.1460 8.86835
April 485.00000 22.98028 39.62922 0.14159 8.41785
May 508.00000 23.67425 44.74432 -0.5234 13.99712
June 496.00000 24.09452 46.28407 -0.3171 9.40663
July 497.00000 24.26065 48.92078 -0.2365 8.22545
August 514.00000 24.25655 49.24600 -0.2282 7.61342
September 485.00000 23.67490 48.36049 -0.5090 13.92098
October 502.00000 22.39326 44.49682 -0.0062 8.03377
November 489.00000 21.39236 34.91726 -0.3593 10.24787
December 497.00000 20.57338 32.58542 -0.6266 15.77776
           
Annual Sum or Average 5943.00000 22.56543 40.37673 -0.3416 11.57043
Minimum of Months 454.00000 20.29862 28.76945 -0.7583 7.61342
Maximum of Months 514.00000 24.26065 49.24600 0.14159 19.98196



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.47375 29.23458 -0.7088 16.97685
February 454.00000 20.87325 31.85370 -0.5598 13.45139
March 514.00000 21.74448 36.85606 -0.2574 7.84148
April 485.00000 22.54717 41.83927 -0.0171 6.53896
May 508.00000 23.63002 46.72552 -0.6396 14.99273
June 496.00000 24.15141 46.48227 -0.3952 8.87302
July 497.00000 24.31585 48.40014 -0.3075 7.49351
August 514.00000 24.29950 48.57159 -0.3003 7.28106
September 485.00000 24.10634 47.83187 -0.4239 9.60739
October 502.00000 23.02745 43.48602 0.12875 6.64381
November 489.00000 22.04103 34.35768 -0.1912 7.09175
December 497.00000 20.95728 32.64738 -0.5042 11.41907
           
Annual Sum or Average 5943.00000 22.69385 40.76071 -0.3473 9.83564
Minimum of Months 454.00000 20.47375 29.23458 -0.7088 6.53896
Maximum of Months 514.00000 24.31585 48.57159 0.12875 16.97685



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.66279 29.36380 -0.6400 14.85926
February 454.00000 21.29483 31.55775 -0.4375 11.42093
March 514.00000 22.38649 35.93015 -0.0865 6.85522
April 485.00000 23.20272 40.30891 0.16419 7.20547
May 508.00000 23.96966 45.35154 -0.4711 11.72124
June 496.00000 24.30637 45.70645 -0.2787 7.56492
July 497.00000 24.46476 47.67042 -0.1908 7.04823
August 514.00000 24.41394 47.91887 -0.1973 6.72102
September 485.00000 24.22315 47.15368 -0.3259 8.59439
October 502.00000 23.42386 42.31166 0.24689 7.85134
November 489.00000 22.51716 33.75600 -0.0639 6.54548
December 497.00000 21.20146 32.56771 -0.4230 9.85759
           
Annual Sum or Average 5943.00000 23.01798 40.03366 -0.2245 8.84006
Minimum of Months 454.00000 20.66279 29.36380 -0.6400 6.54548
Maximum of Months 514.00000 24.46476 47.91887 0.24689 14.85926



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.94334 26.90076 -0.5172 13.62554
February 454.00000 21.51488 29.31219 -0.3457 11.14472
March 514.00000 22.51875 34.57825 -0.0340 7.48997
April 485.00000 22.92234 40.34047 0.09717 7.27642
May 508.00000 23.58052 48.37260 -0.6179 15.07228
June 496.00000 24.08908 50.23440 -0.3836 9.14003
July 497.00000 24.33564 53.02358 -0.2598 7.15638
August 514.00000 24.41095 53.53590 -0.1928 6.47202
September 485.00000 24.22362 49.66505 -0.3070 8.69628
October 502.00000 23.60126 41.98707 0.32510 9.47534
November 489.00000 22.97958 31.56870 0.08245 7.79267
December 497.00000 21.78072 30.16831 -0.2444 8.94693
           
Annual Sum or Average 5943.00000 23.08611 40.90624 -0.1996 9.35280
Minimum of Months 454.00000 20.94334 26.90076 -0.6179 6.47202
Maximum of Months 514.00000 24.41095 53.53590 0.32510 15.07228



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.66195 29.24418 -0.6430 15.17646
February 454.00000 21.15083 31.59269 -0.4742 12.04297
March 514.00000 22.29482 35.80683 -0.1056 7.33700
April 485.00000 23.05360 40.57546 0.12943 7.13593
May 508.00000 23.83466 45.84662 -0.5243 12.62373
June 496.00000 24.23520 46.11562 -0.3159 8.13933
July 497.00000 24.38582 48.11104 -0.2342 7.24249
August 514.00000 24.39988 48.10663 -0.2098 6.79341
September 485.00000 24.21084 47.33919 -0.3386 8.77382
October 502.00000 23.34376 42.60037 0.22706 7.67024
November 489.00000 22.39631 33.73848 -0.0912 6.85843
December 497.00000 21.18576 32.51189 -0.4327 10.19509
           
Annual Sum or Average 5943.00000 22.94249 40.20029 -0.2502 9.15127
Minimum of Months 454.00000 20.66195 29.24418 -0.6430 6.79341
Maximum of Months 514.00000 24.39988 48.11104 0.22706 15.17646



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.42247 29.11308 -0.7096 17.55248
February 454.00000 21.00882 31.21767 -0.5130 13.10970
March 514.00000 22.29013 35.51752 -0.1160 7.23265
April 485.00000 23.24667 39.92832 0.16499 7.17110
May 508.00000 23.97240 45.01666 -0.4931 11.17076
June 496.00000 24.23947 46.18779 -0.3386 8.07118
July 497.00000 24.37874 48.64345 -0.2672 7.20776
August 514.00000 24.32603 49.19402 -0.2790 7.15813
September 485.00000 24.01418 48.27923 -0.4559 10.56474
October 502.00000 22.75936 44.36719 0.06341 6.79067
November 489.00000 21.75671 34.95086 -0.2670 8.05089
December 497.00000 20.81109 32.65277 -0.5484 12.92441
           
Annual Sum or Average 5943.00000 22.78254 40.49388 -0.3123 9.72429
Minimum of Months 454.00000 20.42247 29.11308 -0.7096 6.79067
Maximum of Months 514.00000 24.37874 49.19402 0.16499 17.55248



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.49275 28.08421 -0.6813 16.47888
February 385.00000 21.23911 30.19484 -0.4450 12.07498
March 433.00000 22.51851 34.11886 -0.0478 7.14954
April 410.00000 23.42296 38.71042 0.23218 7.98300
May 430.00000 24.07846 43.72440 -0.4166 10.98432
June 418.00000 24.35157 45.32669 -0.2628 7.86835
July 422.00000 24.52208 47.75621 -0.1791 7.48134
August 433.00000 24.43287 48.46148 -0.2066 7.22780
September 410.00000 24.02490 47.49815 -0.4125 10.88080
October 427.00000 22.90914 43.07565 0.11588 7.50861
November 417.00000 21.88418 33.74225 -0.2250 7.75918
December 422.00000 20.85171 31.84736 -0.5255 12.16982
           
Annual Sum or Average 5034.00000 22.90413 39.43670 -0.2537 9.61296
Minimum of Months 385.00000 20.49275 28.08421 -0.6813 7.14954
Maximum of Months 433.00000 24.52208 48.46148 0.23218 16.47888



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.46054 27.69859 -0.4223 12.80042
February 454.00000 21.98971 29.59956 -0.2484 10.26488
March 514.00000 23.08665 33.50873 0.09345 7.72856
April 485.00000 23.57519 38.68538 0.26200 8.20226
May 508.00000 24.01236 44.67100 -0.4632 10.88153
June 496.00000 24.22852 46.17567 -0.3382 8.28545
July 497.00000 24.40220 48.52573 -0.2521 7.25521
August 514.00000 24.38417 48.78213 -0.2293 6.97737
September 485.00000 24.17200 47.27654 -0.3560 9.49099
October 502.00000 23.45931 41.79911 0.26599 8.96549
November 489.00000 22.87001 32.26860 0.02408 8.08000
December 497.00000 21.92333 30.70372 -0.2491 9.71380
           
Annual Sum or Average 5943.00000 23.30697 39.21714 -0.1594 9.04407
Minimum of Months 454.00000 21.46054 27.69859 -0.4632 6.97737
Maximum of Months 514.00000 24.40220 48.78213 0.26599 12.80042



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.59991 28.67483 -0.6516 16.07781
February 454.00000 21.19449 30.64010 -0.4512 12.22180
March 514.00000 22.47868 34.68454 -0.0435 7.68176
April 485.00000 23.31551 39.33197 0.22052 8.14254
May 508.00000 23.91262 44.72940 -0.4561 11.42811
June 496.00000 24.20446 46.07950 -0.2980 8.32470
July 497.00000 24.34361 48.51153 -0.2292 7.54124
August 514.00000 24.33043 48.89366 -0.2228 7.15946
September 485.00000 23.95508 48.04905 -0.4220 10.94222
October 502.00000 22.83014 43.71940 0.10875 7.54647
November 489.00000 21.88658 34.29884 -0.2167 8.03505
December 497.00000 20.96757 32.23859 -0.4970 11.92048
           
Annual Sum or Average 5943.00000 22.84798 40.05963 -0.2622 9.73056
Minimum of Months 454.00000 20.59991 28.67483 -0.6516 7.15946
Maximum of Months 514.00000 24.34361 48.89366 0.22052 16.07781



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.199769E+10 0.489820E+09 52.83 0.123622E+10 0.761475E+09 0.00 0.63 19-JAN-20:00 0.00 01-JAN-00:10 21197.72 19-JAN-20:00 14915.02 31-JAN-15:10 10159.57 19-JAN-16:00 4937.47 19-JAN-20:00 0.00
February 0.496106E+10 0.121366E+10 132.54 0.407509E+10 0.885970E+09 0.00 0.89 28-FEB-15:10 0.00 01-FEB-00:10 31798.74 28-FEB-15:10 31798.74 28-FEB-15:10 8759.06 18-FEB-16:30 7053.20 28-FEB-15:10 0.00
March 0.150129E+11 0.351503E+10 267.83 0.117247E+11 0.328813E+10 0.00 1.00 29-MAR-14:50 0.00 01-MAR-00:10 49041.03 30-MAR-15:10 49041.03 30-MAR-15:10 14033.50 31-MAR-11:30 11362.17 30-MAR-15:10 0.00
April 0.256881E+11 0.593094E+10 329.33 0.210057E+11 0.468245E+10 0.00 1.00 04-APR-10:50 0.00 01-APR-00:10 51582.72 17-APR-14:00 51582.72 17-APR-14:00 15991.64 21-APR-10:30 12320.52 17-APR-14:00 0.00
May 0.489629E+11 0.110910E+11 410.14 0.372809E+11 0.116820E+11 0.00 1.00 01-MAY-14:50 0.00 01-MAY-00:10 69929.83 30-MAY-15:00 56371.92 30-MAY-15:00 22646.72 23-MAY-06:03 17250.06 30-MAY-15:00 0.00
June 0.735298E+11 0.173333E+11 433.53 0.555088E+11 0.180210E+11 0.00 1.00 01-JUN-05:13 0.00 01-JUN-00:10 80073.10 28-JUN-12:05 60085.43 19-JUN-16:00 26551.10 27-JUN-12:00 20152.20 19-JUN-16:00 0.00
July 0.845191E+11 0.201468E+11 439.78 0.606759E+11 0.238432E+11 0.00 1.00 01-JUL-05:13 0.00 01-JUL-00:10 89213.71 07-JUL-12:03 66686.32 07-JUL-16:00 32123.20 26-JUL-06:03 23840.92 07-JUL-16:00 0.00
August 0.964149E+11 0.227249E+11 465.70 0.676683E+11 0.287465E+11 0.00 1.00 01-AUG-05:12 0.00 01-AUG-00:10 87345.63 17-AUG-12:03 77631.96 14-AUG-04:02 33775.26 24-AUG-06:03 23274.90 01-AUG-15:00 0.00
September 0.618762E+11 0.139646E+11 411.94 0.458525E+11 0.160237E+11 0.00 1.00 01-SEP-05:13 0.00 01-SEP-00:10 85699.53 07-SEP-16:00 64749.13 07-SEP-15:50 26069.37 06-SEP-12:03 21627.40 07-SEP-16:00 0.00
October 0.275370E+11 0.621706E+10 303.40 0.205354E+11 0.700161E+10 0.00 1.00 02-OCT-05:13 0.00 01-OCT-00:10 68659.64 10-OCT-16:00 56896.60 10-OCT-16:00 33072.64 02-OCT-05:13 16718.89 10-OCT-16:00 0.00
November 0.109438E+11 0.258127E+10 220.36 0.833913E+10 0.260469E+10 0.00 0.94 02-NOV-14:10 0.00 01-NOV-00:10 34671.72 02-NOV-14:10 28473.82 02-NOV-14:10 12135.71 02-NOV-10:50 7435.69 03-NOV-15:00 0.00
December 0.396239E+10 0.940212E+09 113.28 0.267585E+10 0.128654E+10 0.00 0.88 12-DEC-14:00 0.00 01-DEC-00:10 31673.59 12-DEC-14:00 24102.81 12-DEC-14:10 15967.38 13-DEC-16:40 6902.86 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.455406E+12 0.106149E+12 3580.68 0.336579E+12 0.118827E+12 0.00                         0.00
Minimum of Months 0.199769E+10 0.489820E+09 52.83 0.123622E+10 0.761475E+09 0.00 0.63   0.00   21197.72   14915.02   8759.06   4937.47   0.00
Maximum of Months 0.964149E+11 0.227249E+11 465.70 0.676683E+11 0.287465E+11 0.00 1.00   0.00   89213.71   77631.96   33775.26   23840.92   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.200835E+10 0.489702E+09 52.83 0.126820E+10 0.740153E+09 0.00 0.68 19-JAN-16:00 0.00 01-JAN-00:10 21910.88 19-JAN-16:00 14041.83 31-JAN-15:00 9854.74 19-JAN-15:10 5040.02 19-JAN-16:00 0.00
February 0.494226E+10 0.121087E+10 135.47 0.406288E+10 0.879382E+09 0.00 0.79 28-FEB-15:30 0.00 01-FEB-00:10 26376.06 28-FEB-15:30 26376.06 28-FEB-15:30 8501.57 18-FEB-16:00 5983.33 28-FEB-15:10 0.00
March 0.142263E+11 0.334931E+10 274.19 0.111161E+11 0.311023E+10 0.00 1.00 29-MAR-14:50 0.00 01-MAR-00:10 48459.00 30-MAR-15:10 48459.00 30-MAR-15:10 12322.28 31-MAR-11:30 11226.39 30-MAR-15:10 0.00
April 0.248281E+11 0.575164E+10 341.21 0.203465E+11 0.448152E+10 0.00 1.00 04-APR-13:30 0.00 01-APR-00:10 54335.24 17-APR-15:40 54335.24 17-APR-15:40 14010.43 21-APR-10:40 12977.31 17-APR-15:40 0.00
May 0.462255E+11 0.105182E+11 423.48 0.352264E+11 0.109991E+11 0.00 1.00 01-MAY-15:10 0.00 01-MAY-00:10 65988.75 30-MAY-15:10 52651.37 30-MAY-15:00 17253.65 31-MAY-13:00 16250.69 30-MAY-15:00 0.00
June 0.679196E+11 0.160189E+11 439.25 0.505498E+11 0.173698E+11 0.00 1.00 01-JUN-08:70 0.00 01-JUN-00:10 74954.04 26-JUN-15:00 63568.23 26-JUN-05:12 23958.12 23-JUN-10:50 18769.78 27-JUN-16:00 0.00
July 0.774759E+11 0.184349E+11 442.37 0.544152E+11 0.230607E+11 0.00 1.00 01-JUL-07:20 0.00 01-JUL-00:10 79347.88 07-JUL-16:00 64994.43 15-JUL-05:03 27152.80 26-JUL-10:50 22086.94 07-JUL-16:00 0.00
August 0.865473E+11 0.203426E+11 463.85 0.589091E+11 0.276381E+11 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 79254.12 17-AUG-15:30 71305.52 14-AUG-04:02 25710.25 24-AUG-14:00 21508.76 01-AUG-15:20 0.00
September 0.532059E+11 0.120668E+11 411.02 0.381344E+11 0.150715E+11 0.00 1.00 01-SEP-09:20 0.00 01-SEP-00:10 77390.69 07-SEP-16:00 57201.39 07-SEP-15:30 22767.70 11-SEP-11:00 19434.79 07-SEP-16:00 0.00
October 0.234098E+11 0.533468E+10 302.36 0.169656E+11 0.644424E+10 0.00 1.00 02-OCT-09:50 0.00 01-OCT-00:10 59558.80 11-OCT-14:10 47359.94 10-OCT-16:00 22581.27 18-OCT-15:00 14133.95 10-OCT-16:00 0.00
November 0.973853E+10 0.231902E+10 219.43 0.725965E+10 0.247888E+10 0.00 0.86 05-NOV-13:32 0.00 01-NOV-00:10 29002.08 05-NOV-13:32 23082.93 05-NOV-13:32 10639.74 27-NOV-18:00 6351.53 05-NOV-13:32 0.00
December 0.369216E+10 0.883520E+09 112.94 0.248861E+10 0.120356E+10 0.00 0.84 12-DEC-14:00 0.00 01-DEC-00:10 28500.51 12-DEC-14:00 20953.38 12-DEC-14:00 10672.31 13-DEC-17:02 6265.13 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.414220E+12 0.967203E+11 3618.41 0.300742E+12 0.113477E+12 0.00                         0.00
Minimum of Months 0.200835E+10 0.489702E+09 52.83 0.126820E+10 0.740153E+09 0.00 0.68   0.00   21910.88   14041.83   8501.57   5040.02   0.00
Maximum of Months 0.865473E+11 0.203426E+11 463.85 0.589091E+11 0.276381E+11 0.00 1.00   0.00   79347.88   71305.52   27152.80   22086.94   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.208812E+10 0.512351E+09 52.83 0.129695E+10 0.791170E+09 0.00 0.63 19-JAN-17:50 0.00 01-JAN-00:10 22048.37 19-JAN-17:50 14675.56 31-JAN-15:00 10703.56 19-JAN-16:00 5143.92 19-JAN-17:50 0.00
February 0.511044E+10 0.125854E+10 134.49 0.416431E+10 0.946137E+09 0.00 0.82 26-FEB-15:13 0.00 01-FEB-00:10 30266.09 26-FEB-15:13 30266.09 26-FEB-15:13 8907.60 18-FEB-16:00 6858.70 26-FEB-15:13 0.00
March 0.149369E+11 0.353913E+10 274.54 0.116299E+11 0.330704E+10 0.00 1.00 29-MAR-15:10 0.00 01-MAR-00:10 54013.65 30-MAR-15:30 54013.65 30-MAR-15:30 12130.55 31-MAR-11:30 12509.60 30-MAR-15:20 0.00
April 0.266444E+11 0.620232E+10 340.99 0.218575E+11 0.478695E+10 0.00 1.00 04-APR-15:00 0.00 01-APR-00:10 60363.56 17-APR-15:40 60363.56 17-APR-15:40 13566.29 21-APR-10:50 14416.99 17-APR-15:40 0.00
May 0.496304E+11 0.113632E+11 425.34 0.385225E+11 0.111078E+11 0.00 1.00 01-MAY-15:20 0.00 01-MAY-00:10 73968.09 30-MAY-15:10 63213.58 16-MAY-15:40 17261.85 31-MAY-13:00 18168.21 30-MAY-15:00 0.00
June 0.725011E+11 0.171819E+11 440.93 0.549795E+11 0.175216E+11 0.00 1.00 01-JUN-09:30 0.00 01-JUN-00:10 82578.01 26-JUN-15:00 64407.33 27-JUN-15:30 24076.39 23-JUN-10:40 21023.26 27-JUN-15:50 0.00
July 0.823764E+11 0.197085E+11 445.01 0.592145E+11 0.231619E+11 0.00 1.00 01-JUL-08:70 0.00 01-JUL-00:10 89545.63 07-JUL-16:00 71644.85 07-JUL-16:00 27234.75 26-JUL-10:40 24887.26 07-JUL-16:00 0.00
August 0.910052E+11 0.214964E+11 465.14 0.634009E+11 0.276043E+11 0.00 1.00 01-AUG-07:10 0.00 01-AUG-00:10 88719.73 01-AUG-15:00 71779.46 02-AUG-16:00 25831.41 24-AUG-14:00 24257.72 01-AUG-15:00 0.00
September 0.548678E+11 0.125384E+11 411.43 0.394961E+11 0.153717E+11 0.00 1.00 01-SEP-10:30 0.00 01-SEP-00:10 84820.85 06-SEP-14:00 64754.60 07-SEP-15:30 22744.17 11-SEP-11:00 21176.72 07-SEP-16:00 0.00
October 0.237805E+11 0.546374E+10 298.87 0.171467E+11 0.663384E+10 0.00 1.00 02-OCT-11:00 0.00 01-OCT-00:10 64295.94 11-OCT-14:00 51833.83 10-OCT-15:40 22639.89 18-OCT-15:00 15125.15 10-OCT-14:00 0.00
November 0.100445E+11 0.240761E+10 217.94 0.741647E+10 0.262806E+10 0.00 0.81 02-NOV-13:50 0.00 01-NOV-00:10 30240.05 02-NOV-13:40 23619.53 05-NOV-15:05 11031.05 27-NOV-18:00 6726.67 02-NOV-13:00 0.00
December 0.380672E+10 0.915216E+09 111.50 0.254801E+10 0.125871E+10 0.00 0.82 12-DEC-14:00 0.00 01-DEC-00:10 30441.40 12-DEC-14:00 22412.15 12-DEC-14:00 10945.47 13-DEC-16:00 6742.74 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.436793E+12 0.102587E+12 3619.02 0.321673E+12 0.115119E+12 0.00                         0.00
Minimum of Months 0.208812E+10 0.512351E+09 52.83 0.129695E+10 0.791170E+09 0.00 0.63   0.00   22048.37   14675.56   8907.60   5143.92   0.00
Maximum of Months 0.910052E+11 0.214964E+11 465.14 0.634009E+11 0.276043E+11 0.00 1.00   0.00   89545.63   71779.46   27234.75   24887.26   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 278.63 0.00 278.63 47.74 1775.69 0.00 0.00 0.00
February 308.83 0.00 308.83 144.47 1451.86 0.00 0.00 0.00
March 433.58 0.00 433.58 320.87 908.32 0.00 0.00 0.00
April 524.46 2.33 522.13 596.63 730.12 0.00 0.00 0.00
May 627.24 20.02 607.23 890.41 479.27 0.00 0.00 0.00
June 690.31 45.58 644.73 1265.62 305.69 0.00 0.00 0.00
July 651.31 31.66 619.65 1263.06 221.55 0.00 0.00 0.00
August 579.23 6.31 572.92 1152.80 184.04 0.00 0.00 0.00
September 437.84 0.06 437.78 669.24 399.84 0.00 0.00 0.00
October 332.91 0.00 332.91 314.28 828.48 0.00 0.00 0.00
November 297.94 0.00 297.94 181.03 1120.53 0.00 0.00 0.00
December 257.57 0.00 257.57 52.94 1423.76 0.00 0.00 0.00
                 
Annual Sum or Average 452.43 8.87 443.57 577.33 815.87 0.00 0.00 0.00
Minimum of Months 257.57 0.00 257.57 47.74 184.04 0.00 0.00 0.00
Maximum of Months 690.31 45.58 644.73 1265.62 1775.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 407.94 184.00 223.94 298.18 1058.39 0.00 0.00 0.00
February 514.28 276.32 237.96 513.29 872.03 0.00 0.00 0.00
March 647.02 294.54 352.48 752.40 559.75 0.00 0.00 0.00
April 782.42 356.76 425.66 1092.80 460.68 0.00 0.00 0.00
May 859.15 363.32 495.83 1323.98 316.08 0.00 0.00 0.00
June 889.51 372.82 516.70 1560.45 203.96 0.00 0.00 0.00
July 867.31 364.63 502.68 1571.74 148.16 0.00 0.00 0.00
August 793.30 314.73 478.57 1463.24 122.21 0.00 0.00 0.00
September 651.99 288.88 363.11 1049.92 257.36 0.00 0.00 0.00
October 556.20 289.40 266.80 729.46 515.33 0.00 0.00 0.00
November 444.69 201.35 243.33 466.55 673.84 0.00 0.00 0.00
December 385.18 175.58 209.60 306.84 847.82 0.00 0.00 0.00
                 
Annual Sum or Average 650.57 290.15 360.42 929.55 501.07 0.00 0.00 0.00
Minimum of Months 385.18 175.58 209.60 298.18 122.21 0.00 0.00 0.00
Maximum of Months 889.51 372.82 516.70 1571.74 1058.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1490.14 1038.92 451.22 1718.18 1493.18 0.00 0.00 0.00
February 1390.80 932.29 458.51 1742.57 1285.80 0.00 0.00 0.00
March 1250.80 651.84 598.96 1699.81 892.10 0.00 0.00 0.00
April 936.76 304.94 631.83 1412.48 755.88 0.00 0.00 0.00
May 756.87 87.97 668.90 1202.27 508.27 0.00 0.00 0.00
June 699.80 38.94 660.86 1323.25 324.88 0.00 0.00 0.00
July 707.49 52.75 654.73 1404.66 230.47 0.00 0.00 0.00
August 844.69 157.79 686.90 1706.77 192.77 0.00 0.00 0.00
September 928.95 345.52 583.43 1603.01 412.25 0.00 0.00 0.00
October 1346.71 872.40 474.31 2008.62 813.18 0.00 0.00 0.00
November 1448.82 961.41 487.41 1956.02 1040.93 0.00 0.00 0.00
December 1468.86 1033.36 435.51 1808.37 1252.54 0.00 0.00 0.00
                 
Annual Sum or Average 1104.67 538.01 566.66 1631.90 764.05 0.00 0.00 0.00
Minimum of Months 699.80 38.94 435.51 1202.27 192.77 0.00 0.00 0.00
Maximum of Months 1490.14 1038.92 686.90 2008.62 1493.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 419.01 194.36 224.64 342.52 1100.83 0.00 0.00 0.00
February 481.02 224.90 256.11 506.80 923.83 0.00 0.00 0.00
March 708.99 342.60 366.39 898.12 602.76 0.00 0.00 0.00
April 797.60 364.98 432.62 1153.68 499.25 0.00 0.00 0.00
May 801.61 303.70 497.91 1265.47 341.62 0.00 0.00 0.00
June 843.00 324.30 518.70 1499.51 223.31 0.00 0.00 0.00
July 795.14 294.81 500.33 1465.09 158.45 0.00 0.00 0.00
August 779.13 291.36 487.76 1450.31 134.15 0.00 0.00 0.00
September 634.78 264.41 370.36 1036.06 272.25 0.00 0.00 0.00
October 565.51 293.56 271.95 787.33 555.24 0.00 0.00 0.00
November 451.32 202.57 248.74 530.96 734.21 0.00 0.00 0.00
December 372.33 162.86 209.47 333.18 908.68 0.00 0.00 0.00
                 
Annual Sum or Average 638.25 272.24 366.02 941.37 535.87 0.00 0.00 0.00
Minimum of Months 372.33 162.86 209.47 333.18 134.15 0.00 0.00 0.00
Maximum of Months 843.00 364.98 518.70 1499.51 1100.83 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.87 0.00 92.87 15.12 620.47 0.00 0.00 0.00
February 102.94 0.00 102.94 49.65 499.42 0.00 0.00 0.00
March 144.52 0.00 144.52 115.17 302.34 0.00 0.00 0.00
April 174.81 0.78 174.04 214.64 232.46 0.00 0.00 0.00
May 209.07 6.67 202.40 310.34 151.49 0.00 0.00 0.00
June 230.09 15.19 214.90 430.57 98.61 0.00 0.00 0.00
July 217.09 10.55 206.54 428.90 71.39 0.00 0.00 0.00
August 193.07 2.10 190.97 389.03 60.89 0.00 0.00 0.00
September 145.94 0.02 145.92 220.81 146.64 0.00 0.00 0.00
October 110.96 0.00 110.96 98.25 310.54 0.00 0.00 0.00
November 99.31 0.00 99.31 51.44 419.31 0.00 0.00 0.00
December 85.85 0.00 85.85 15.48 522.98 0.00 0.00 0.00
                 
Annual Sum or Average 150.80 2.96 147.85 195.77 285.31 0.00 0.00 0.00
Minimum of Months 85.85 0.00 85.85 15.12 60.89 0.00 0.00 0.00
Maximum of Months 230.09 15.19 214.90 430.57 620.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.88 0.00 92.88 15.12 620.51 0.00 0.00 0.00
February 102.94 0.00 102.94 49.65 499.45 0.00 0.00 0.00
March 144.53 0.00 144.53 115.17 302.36 0.00 0.00 0.00
April 174.82 0.78 174.04 214.65 232.47 0.00 0.00 0.00
May 209.08 6.67 202.41 310.36 151.50 0.00 0.00 0.00
June 230.10 15.19 214.91 430.59 98.62 0.00 0.00 0.00
July 217.10 10.55 206.55 428.92 71.39 0.00 0.00 0.00
August 193.08 2.10 190.97 389.05 60.90 0.00 0.00 0.00
September 145.95 0.02 145.93 220.82 146.65 0.00 0.00 0.00
October 110.97 0.00 110.97 98.26 310.56 0.00 0.00 0.00
November 99.31 0.00 99.31 51.44 419.33 0.00 0.00 0.00
December 85.86 0.00 85.86 15.48 523.01 0.00 0.00 0.00
                 
Annual Sum or Average 150.81 2.96 147.85 195.78 285.32 0.00 0.00 0.00
Minimum of Months 85.86 0.00 85.86 15.12 60.90 0.00 0.00 0.00
Maximum of Months 230.10 15.19 214.91 430.59 620.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.88 0.00 92.88 15.12 620.51 0.00 0.00 0.00
February 102.94 0.00 102.94 49.65 499.45 0.00 0.00 0.00
March 144.53 0.00 144.53 115.17 302.36 0.00 0.00 0.00
April 174.82 0.78 174.04 214.65 232.47 0.00 0.00 0.00
May 209.08 6.67 202.41 310.36 151.50 0.00 0.00 0.00
June 230.10 15.19 214.91 430.59 98.62 0.00 0.00 0.00
July 217.10 10.55 206.55 428.92 71.39 0.00 0.00 0.00
August 193.08 2.10 190.97 389.05 60.90 0.00 0.00 0.00
September 145.95 0.02 145.93 220.82 146.65 0.00 0.00 0.00
October 110.97 0.00 110.97 98.26 310.56 0.00 0.00 0.00
November 99.31 0.00 99.31 51.44 419.33 0.00 0.00 0.00
December 85.86 0.00 85.86 15.48 523.01 0.00 0.00 0.00
                 
Annual Sum or Average 150.81 2.96 147.85 195.78 285.32 0.00 0.00 0.00
Minimum of Months 85.86 0.00 85.86 15.12 60.90 0.00 0.00 0.00
Maximum of Months 230.10 15.19 214.91 430.59 620.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 392.41 177.00 215.42 281.96 1077.08 0.00 0.00 0.00
February 494.71 265.80 228.91 495.68 877.79 0.00 0.00 0.00
March 622.40 283.33 339.07 737.42 553.42 0.00 0.00 0.00
April 752.65 343.19 409.46 1075.89 438.57 0.00 0.00 0.00
May 826.46 349.50 476.96 1297.01 299.67 0.00 0.00 0.00
June 855.67 358.63 497.04 1517.34 197.38 0.00 0.00 0.00
July 834.31 350.75 483.55 1525.91 145.22 0.00 0.00 0.00
August 763.12 302.75 460.36 1416.87 123.97 0.00 0.00 0.00
September 627.18 277.89 349.29 1005.35 280.18 0.00 0.00 0.00
October 535.04 278.39 256.64 686.01 566.68 0.00 0.00 0.00
November 427.77 193.69 234.08 420.09 741.36 0.00 0.00 0.00
December 370.53 168.90 201.63 282.15 909.83 0.00 0.00 0.00
                 
Annual Sum or Average 625.81 279.11 346.71 897.22 515.77 0.00 0.00 0.00
Minimum of Months 370.53 168.90 201.63 281.96 123.97 0.00 0.00 0.00
Maximum of Months 855.67 358.63 497.04 1525.91 1077.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.52 7.00 8.52 11.15 42.59 0.00 0.00 0.00
February 19.56 10.51 9.05 19.60 34.71 0.00 0.00 0.00
March 24.61 11.20 13.41 29.16 21.88 0.00 0.00 0.00
April 29.76 13.57 16.19 42.54 17.34 0.00 0.00 0.00
May 32.68 13.82 18.86 51.28 11.85 0.00 0.00 0.00
June 33.83 14.18 19.65 59.99 7.80 0.00 0.00 0.00
July 32.99 13.87 19.12 60.33 5.74 0.00 0.00 0.00
August 30.17 11.97 18.20 56.02 4.90 0.00 0.00 0.00
September 24.80 10.99 13.81 39.75 11.08 0.00 0.00 0.00
October 21.15 11.01 10.15 27.12 22.41 0.00 0.00 0.00
November 16.91 7.66 9.26 16.61 29.31 0.00 0.00 0.00
December 14.65 6.68 7.97 11.16 35.97 0.00 0.00 0.00
                 
Annual Sum or Average 24.74 11.04 13.71 35.48 20.39 0.00 0.00 0.00
Minimum of Months 14.65 6.68 7.97 11.15 4.90 0.00 0.00 0.00
Maximum of Months 33.83 14.18 19.65 60.33 42.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 496.70 346.30 150.40 577.74 532.12 0.00 0.00 0.00
February 463.59 310.76 152.83 588.53 453.06 0.00 0.00 0.00
March 416.93 217.28 199.65 578.96 307.92 0.00 0.00 0.00
April 312.25 101.64 210.61 487.36 245.94 0.00 0.00 0.00
May 252.29 29.32 222.96 415.26 161.58 0.00 0.00 0.00
June 233.27 12.98 220.29 450.39 104.99 0.00 0.00 0.00
July 235.83 17.58 218.24 475.93 75.00 0.00 0.00 0.00
August 281.56 52.60 228.96 573.16 66.22 0.00 0.00 0.00
September 309.65 115.17 194.47 533.74 153.23 0.00 0.00 0.00
October 448.90 290.79 158.10 667.04 310.06 0.00 0.00 0.00
November 482.93 320.46 162.47 644.30 399.04 0.00 0.00 0.00
December 489.61 344.44 145.17 600.48 469.88 0.00 0.00 0.00
                 
Annual Sum or Average 368.22 179.33 188.88 549.31 272.30 0.00 0.00 0.00
Minimum of Months 233.27 12.98 145.17 415.26 66.22 0.00 0.00 0.00
Maximum of Months 496.70 346.30 228.96 667.04 532.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 496.70 346.30 150.40 577.74 532.12 0.00 0.00 0.00
February 463.59 310.76 152.83 588.53 453.06 0.00 0.00 0.00
March 416.93 217.28 199.65 578.96 307.92 0.00 0.00 0.00
April 312.25 101.64 210.61 487.36 245.94 0.00 0.00 0.00
May 252.29 29.32 222.96 415.26 161.58 0.00 0.00 0.00
June 233.27 12.98 220.29 450.39 104.99 0.00 0.00 0.00
July 235.83 17.58 218.24 475.93 75.00 0.00 0.00 0.00
August 281.56 52.60 228.96 573.16 66.22 0.00 0.00 0.00
September 309.65 115.17 194.47 533.74 153.23 0.00 0.00 0.00
October 448.90 290.79 158.10 667.04 310.06 0.00 0.00 0.00
November 482.93 320.46 162.47 644.30 399.04 0.00 0.00 0.00
December 489.61 344.44 145.17 600.48 469.88 0.00 0.00 0.00
                 
Annual Sum or Average 368.22 179.33 188.88 549.31 272.30 0.00 0.00 0.00
Minimum of Months 233.27 12.98 145.17 415.26 66.22 0.00 0.00 0.00
Maximum of Months 496.70 346.30 228.96 667.04 532.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 496.67 346.28 150.39 577.71 532.09 0.00 0.00 0.00
February 463.56 310.74 152.82 588.49 453.03 0.00 0.00 0.00
March 416.90 217.26 199.64 578.92 307.90 0.00 0.00 0.00
April 312.23 101.64 210.59 487.33 245.93 0.00 0.00 0.00
May 252.27 29.32 222.95 415.23 161.57 0.00 0.00 0.00
June 233.25 12.98 220.27 450.37 104.98 0.00 0.00 0.00
July 235.81 17.58 218.23 475.90 75.00 0.00 0.00 0.00
August 281.54 52.59 228.95 573.13 66.22 0.00 0.00 0.00
September 309.63 115.16 194.46 533.71 153.22 0.00 0.00 0.00
October 448.87 290.78 158.09 667.00 310.04 0.00 0.00 0.00
November 482.90 320.44 162.46 644.26 399.01 0.00 0.00 0.00
December 489.58 344.42 145.16 600.44 469.85 0.00 0.00 0.00
                 
Annual Sum or Average 368.19 179.32 188.87 549.28 272.28 0.00 0.00 0.00
Minimum of Months 233.25 12.98 145.16 415.23 66.22 0.00 0.00 0.00
Maximum of Months 496.67 346.28 228.95 667.00 532.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 403.06 186.97 216.10 330.68 1121.10 0.00 0.00 0.00
February 462.72 216.35 246.37 494.46 929.02 0.00 0.00 0.00
March 682.02 329.56 352.45 879.87 599.64 0.00 0.00 0.00
April 767.26 351.09 416.16 1134.37 479.71 0.00 0.00 0.00
May 771.11 292.14 478.97 1237.20 326.73 0.00 0.00 0.00
June 810.93 311.96 498.97 1458.12 218.04 0.00 0.00 0.00
July 764.89 283.59 481.30 1421.23 155.88 0.00 0.00 0.00
August 749.48 280.28 469.21 1402.60 136.89 0.00 0.00 0.00
September 610.62 254.35 356.27 989.72 297.75 0.00 0.00 0.00
October 543.99 282.39 261.60 744.85 612.99 0.00 0.00 0.00
November 434.15 194.87 239.28 491.51 804.53 0.00 0.00 0.00
December 358.17 156.66 201.51 313.92 970.96 0.00 0.00 0.00
                 
Annual Sum or Average 613.97 261.88 352.09 910.40 552.50 0.00 0.00 0.00
Minimum of Months 358.17 156.66 201.51 313.92 136.89 0.00 0.00 0.00
Maximum of Months 810.93 351.09 498.97 1458.12 1121.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.94 7.39 8.54 13.07 44.33 0.00 0.00 0.00
February 18.30 8.55 9.74 19.55 36.73 0.00 0.00 0.00
March 26.97 13.03 13.94 34.79 23.71 0.00 0.00 0.00
April 30.34 13.88 16.45 44.85 18.97 0.00 0.00 0.00
May 30.49 11.55 18.94 48.92 12.92 0.00 0.00 0.00
June 32.06 12.33 19.73 57.65 8.62 0.00 0.00 0.00
July 30.24 11.21 19.03 56.19 6.16 0.00 0.00 0.00
August 29.63 11.08 18.55 55.46 5.41 0.00 0.00 0.00
September 24.14 10.06 14.09 39.13 11.77 0.00 0.00 0.00
October 21.51 11.17 10.34 29.45 24.24 0.00 0.00 0.00
November 17.17 7.70 9.46 19.43 31.81 0.00 0.00 0.00
December 14.16 6.19 7.97 12.41 38.39 0.00 0.00 0.00
                 
Annual Sum or Average 24.28 10.35 13.92 36.00 21.85 0.00 0.00 0.00
Minimum of Months 14.16 6.19 7.97 12.41 5.41 0.00 0.00 0.00
Maximum of Months 32.06 13.88 19.73 57.65 44.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 278.63 0.00 278.63 42.77 1873.23 0.00 0.00 0.00
February 308.83 0.00 308.83 137.23 1534.14 0.00 0.00 0.00
March 433.58 0.00 433.58 307.34 971.77 0.00 0.00 0.00
April 524.46 2.33 522.13 588.30 769.46 0.00 0.00 0.00
May 627.24 20.02 607.23 888.73 498.75 0.00 0.00 0.00
June 690.31 45.58 644.73 1271.10 313.52 0.00 0.00 0.00
July 651.31 31.66 619.65 1271.97 226.00 0.00 0.00 0.00
August 579.23 6.31 572.92 1160.60 188.67 0.00 0.00 0.00
September 437.84 0.06 437.78 664.24 427.75 0.00 0.00 0.00
October 332.91 0.00 332.91 299.59 898.51 0.00 0.00 0.00
November 297.94 0.00 297.94 160.58 1217.16 0.00 0.00 0.00
December 257.57 0.00 257.57 45.75 1538.25 0.00 0.00 0.00
                 
Annual Sum or Average 452.43 8.87 443.57 572.30 868.06 0.00 0.00 0.00
Minimum of Months 257.57 0.00 257.57 42.77 188.67 0.00 0.00 0.00
Maximum of Months 690.31 45.58 644.73 1271.97 1873.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 407.94 184.00 223.94 287.85 1116.91 0.00 0.00 0.00
February 514.28 276.32 237.96 503.09 920.64 0.00 0.00 0.00
March 647.02 294.54 352.48 741.37 594.29 0.00 0.00 0.00
April 782.42 356.76 425.66 1087.96 481.40 0.00 0.00 0.00
May 859.15 363.32 495.83 1324.68 326.45 0.00 0.00 0.00
June 889.51 372.82 516.70 1565.61 208.39 0.00 0.00 0.00
July 867.31 364.63 502.68 1578.83 151.01 0.00 0.00 0.00
August 793.30 314.73 478.57 1469.78 125.07 0.00 0.00 0.00
September 651.99 288.88 363.11 1047.66 273.16 0.00 0.00 0.00
October 556.20 289.40 266.80 718.63 552.72 0.00 0.00 0.00
November 444.69 201.35 243.33 446.62 727.43 0.00 0.00 0.00
December 385.18 175.58 209.60 293.98 914.48 0.00 0.00 0.00
                 
Annual Sum or Average 650.57 290.15 360.42 924.36 530.68 0.00 0.00 0.00
Minimum of Months 385.18 175.58 209.60 287.85 125.07 0.00 0.00 0.00
Maximum of Months 889.51 372.82 516.70 1578.83 1116.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1490.14 1038.92 451.22 1695.67 1579.49 0.00 0.00 0.00
February 1390.80 932.29 458.51 1726.42 1361.02 0.00 0.00 0.00
March 1250.80 651.84 598.96 1686.44 949.80 0.00 0.00 0.00
April 936.76 304.94 631.83 1406.69 794.47 0.00 0.00 0.00
May 756.87 87.97 668.90 1203.04 529.28 0.00 0.00 0.00
June 699.80 38.94 660.86 1329.98 334.75 0.00 0.00 0.00
July 707.49 52.75 654.73 1414.11 236.25 0.00 0.00 0.00
August 844.69 157.79 686.90 1715.87 198.01 0.00 0.00 0.00
September 928.95 345.52 583.43 1600.50 438.52 0.00 0.00 0.00
October 1346.71 872.40 474.31 1996.18 873.57 0.00 0.00 0.00
November 1448.82 961.41 487.41 1928.96 1124.32 0.00 0.00 0.00
December 1468.86 1033.36 435.51 1782.86 1349.46 0.00 0.00 0.00
                 
Annual Sum or Average 1104.67 538.01 566.66 1623.68 811.13 0.00 0.00 0.00
Minimum of Months 699.80 38.94 435.51 1203.04 198.01 0.00 0.00 0.00
Maximum of Months 1490.14 1038.92 686.90 1996.18 1579.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 419.01 194.36 224.64 336.00 1162.35 0.00 0.00 0.00
February 481.02 224.90 256.11 501.14 976.40 0.00 0.00 0.00
March 708.99 342.60 366.39 890.20 642.88 0.00 0.00 0.00
April 797.60 364.98 432.62 1148.60 525.54 0.00 0.00 0.00
May 801.61 303.70 497.91 1264.47 356.30 0.00 0.00 0.00
June 843.00 324.30 518.70 1503.74 230.65 0.00 0.00 0.00
July 795.14 294.81 500.33 1470.20 163.01 0.00 0.00 0.00
August 779.13 291.36 487.76 1455.19 138.12 0.00 0.00 0.00
September 634.78 264.41 370.36 1031.75 291.19 0.00 0.00 0.00
October 565.51 293.56 271.95 778.76 599.23 0.00 0.00 0.00
November 451.32 202.57 248.74 516.96 793.83 0.00 0.00 0.00
December 372.33 162.86 209.47 324.58 979.60 0.00 0.00 0.00
                 
Annual Sum or Average 638.25 272.24 366.02 937.44 569.48 0.00 0.00 0.00
Minimum of Months 372.33 162.86 209.47 324.58 138.12 0.00 0.00 0.00
Maximum of Months 843.00 364.98 518.70 1503.74 1162.35 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.746277E+09 0.00 0.746277E+09 0.127869E+09 0.475602E+10
February 0.747125E+09 0.00 0.747125E+09 0.349499E+09 0.351234E+10
March 0.116131E+10 0.00 0.116131E+10 0.859428E+09 0.243284E+10
April 0.135940E+10 6029322.01 0.135337E+10 0.154647E+10 0.189246E+10
May 0.168001E+10 53616748.83 0.162639E+10 0.238488E+10 0.128368E+10
June 0.178928E+10 0.118135E+09 0.167115E+10 0.328050E+10 0.792351E+09
July 0.174447E+10 84799715.93 0.165967E+10 0.338298E+10 0.593407E+09
August 0.155141E+10 16900235.20 0.153451E+10 0.308766E+10 0.492921E+09
September 0.113489E+10 159761.37 0.113473E+10 0.173468E+10 0.103639E+10
October 0.891659E+09 0.00 0.891659E+09 0.841765E+09 0.221900E+10
November 0.772262E+09 0.00 0.772262E+09 0.469242E+09 0.290440E+10
December 0.689877E+09 0.00 0.689877E+09 0.141792E+09 0.381339E+10
           
Annual Sum or Average 0.142680E+11 0.279641E+09 0.139883E+11 0.182068E+11 0.257292E+11
Minimum of Months 0.689877E+09 0.00 0.689877E+09 0.127869E+09 0.492921E+09
Maximum of Months 0.178928E+10 0.118135E+09 0.167115E+10 0.338298E+10 0.475602E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109261E+10 0.492825E+09 0.599790E+09 0.798648E+09 0.283480E+10
February 0.124414E+10 0.668469E+09 0.575674E+09 0.124175E+10 0.210962E+10
March 0.173298E+10 0.788905E+09 0.944080E+09 0.201523E+10 0.149924E+10
April 0.202802E+10 0.924727E+09 0.110330E+10 0.283253E+10 0.119409E+10
May 0.230115E+10 0.973125E+09 0.132803E+10 0.354614E+10 0.846588E+09
June 0.230561E+10 0.966340E+09 0.133927E+10 0.404468E+10 0.528673E+09
July 0.232300E+10 0.976623E+09 0.134638E+10 0.420974E+10 0.396840E+09
August 0.212478E+10 0.842976E+09 0.128180E+10 0.391915E+10 0.327314E+09
September 0.168995E+10 0.748772E+09 0.941176E+09 0.272139E+10 0.667067E+09
October 0.148972E+10 0.775140E+09 0.714585E+09 0.195378E+10 0.138026E+10
November 0.115263E+10 0.521905E+09 0.630721E+09 0.120930E+10 0.174659E+10
December 0.103168E+10 0.470278E+09 0.561398E+09 0.821836E+09 0.227079E+10
           
Annual Sum or Average 0.205163E+11 0.915008E+10 0.113662E+11 0.293142E+11 0.158019E+11
Minimum of Months 0.103168E+10 0.470278E+09 0.561398E+09 0.798648E+09 0.327314E+09
Maximum of Months 0.232300E+10 0.976623E+09 0.134638E+10 0.420974E+10 0.283480E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.399118E+10 0.278264E+10 0.120854E+10 0.460197E+10 0.399932E+10
February 0.336461E+10 0.225539E+10 0.110922E+10 0.421562E+10 0.311062E+10
March 0.335013E+10 0.174589E+10 0.160424E+10 0.455276E+10 0.238940E+10
April 0.242809E+10 0.790395E+09 0.163769E+10 0.366115E+10 0.195924E+10
May 0.202719E+10 0.235614E+09 0.179158E+10 0.322016E+10 0.136134E+10
June 0.181389E+10 0.100936E+09 0.171295E+10 0.342986E+10 0.842092E+09
July 0.189493E+10 0.141297E+09 0.175364E+10 0.376224E+10 0.617279E+09
August 0.226241E+10 0.422627E+09 0.183979E+10 0.457140E+10 0.516306E+09
September 0.240784E+10 0.895590E+09 0.151225E+10 0.415500E+10 0.106854E+10
October 0.360703E+10 0.233664E+10 0.127039E+10 0.537990E+10 0.217802E+10
November 0.375534E+10 0.249198E+10 0.126336E+10 0.507002E+10 0.269809E+10
December 0.393420E+10 0.276774E+10 0.116646E+10 0.484353E+10 0.335480E+10
           
Annual Sum or Average 0.348369E+11 0.169667E+11 0.178701E+11 0.514636E+11 0.240951E+11
Minimum of Months 0.181389E+10 0.100936E+09 0.110922E+10 0.322016E+10 0.516306E+09
Maximum of Months 0.399118E+10 0.278264E+10 0.183979E+10 0.537990E+10 0.399932E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.112227E+10 0.520587E+09 0.601681E+09 0.917409E+09 0.294846E+10
February 0.116368E+10 0.544089E+09 0.619587E+09 0.122606E+10 0.223492E+10
March 0.189896E+10 0.917621E+09 0.981340E+09 0.240553E+10 0.161442E+10
April 0.206738E+10 0.946027E+09 0.112136E+10 0.299034E+10 0.129405E+10
May 0.214704E+10 0.813430E+09 0.133361E+10 0.338943E+10 0.914999E+09
June 0.218506E+10 0.840583E+09 0.134448E+10 0.388674E+10 0.578811E+09
July 0.212971E+10 0.789625E+09 0.134009E+10 0.392409E+10 0.424395E+09
August 0.208681E+10 0.780386E+09 0.130643E+10 0.388451E+10 0.359296E+09
September 0.164534E+10 0.685356E+09 0.959983E+09 0.268547E+10 0.705669E+09
October 0.151466E+10 0.786276E+09 0.728386E+09 0.210877E+10 0.148717E+10
November 0.116982E+10 0.525073E+09 0.644742E+09 0.137626E+10 0.190308E+10
December 0.997260E+09 0.436203E+09 0.561057E+09 0.892388E+09 0.243380E+10
           
Annual Sum or Average 0.201280E+11 0.858525E+10 0.115427E+11 0.296870E+11 0.168991E+11
Minimum of Months 0.997260E+09 0.436203E+09 0.561057E+09 0.892388E+09 0.359296E+09
Maximum of Months 0.218506E+10 0.946027E+09 0.134448E+10 0.392409E+10 0.294846E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.248747E+09 0.00 0.248747E+09 40489501.74 0.166187E+10
February 0.249030E+09 0.00 0.249030E+09 0.120112E+09 0.120820E+10
March 0.387084E+09 0.00 0.387084E+09 0.308466E+09 0.809784E+09
April 0.453110E+09 2009678.92 0.451101E+09 0.556353E+09 0.602527E+09
May 0.559977E+09 17871404.04 0.542106E+09 0.831226E+09 0.405757E+09
June 0.596400E+09 39376456.78 0.557023E+09 0.111605E+10 0.255605E+09
July 0.581461E+09 28265234.63 0.553196E+09 0.114876E+10 0.191202E+09
August 0.517114E+09 5633145.20 0.511481E+09 0.104198E+10 0.163100E+09
September 0.378280E+09 53251.27 0.378227E+09 0.572348E+09 0.380084E+09
October 0.297206E+09 0.00 0.297206E+09 0.263160E+09 0.831742E+09
November 0.257408E+09 0.00 0.257408E+09 0.133336E+09 0.108684E+10
December 0.229948E+09 0.00 0.229948E+09 41462073.38 0.140074E+10
           
Annual Sum or Average 0.475577E+10 93209170.84 0.466256E+10 0.617374E+10 0.899746E+10
Minimum of Months 0.229948E+09 0.00 0.229948E+09 40489501.74 0.163100E+09
Maximum of Months 0.596400E+09 39376456.78 0.557023E+09 0.114876E+10 0.166187E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.248757E+09 0.00 0.248757E+09 40489950.29 0.166198E+10
February 0.249040E+09 0.00 0.249040E+09 0.120116E+09 0.120827E+10
March 0.387100E+09 0.00 0.387100E+09 0.308476E+09 0.809832E+09
April 0.453129E+09 2009732.94 0.451119E+09 0.556376E+09 0.602562E+09
May 0.560000E+09 17871884.42 0.542128E+09 0.831261E+09 0.405779E+09
June 0.596423E+09 39377515.23 0.557046E+09 0.111610E+10 0.255618E+09
July 0.581484E+09 28265994.40 0.553218E+09 0.114881E+10 0.191211E+09
August 0.517135E+09 5633296.63 0.511501E+09 0.104203E+10 0.163107E+09
September 0.378295E+09 53252.70 0.378242E+09 0.572373E+09 0.380105E+09
October 0.297218E+09 0.00 0.297218E+09 0.263170E+09 0.831791E+09
November 0.257419E+09 0.00 0.257419E+09 0.133340E+09 0.108691E+10
December 0.229957E+09 0.00 0.229957E+09 41461976.01 0.140083E+10
           
Annual Sum or Average 0.475596E+10 93211676.32 0.466275E+10 0.617400E+10 0.899799E+10
Minimum of Months 0.229957E+09 0.00 0.229957E+09 40489950.29 0.163107E+09
Maximum of Months 0.596423E+09 39377515.23 0.557046E+09 0.114881E+10 0.166198E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.248757E+09 0.00 0.248757E+09 40489950.29 0.166198E+10
February 0.249040E+09 0.00 0.249040E+09 0.120116E+09 0.120827E+10
March 0.387100E+09 0.00 0.387100E+09 0.308476E+09 0.809832E+09
April 0.453129E+09 2009732.94 0.451119E+09 0.556376E+09 0.602562E+09
May 0.560000E+09 17871884.42 0.542128E+09 0.831261E+09 0.405779E+09
June 0.596423E+09 39377515.23 0.557046E+09 0.111610E+10 0.255618E+09
July 0.581484E+09 28265994.40 0.553218E+09 0.114881E+10 0.191211E+09
August 0.517135E+09 5633296.63 0.511501E+09 0.104203E+10 0.163107E+09
September 0.378295E+09 53252.70 0.378242E+09 0.572373E+09 0.380105E+09
October 0.297218E+09 0.00 0.297218E+09 0.263170E+09 0.831791E+09
November 0.257419E+09 0.00 0.257419E+09 0.133340E+09 0.108691E+10
December 0.229957E+09 0.00 0.229957E+09 41461976.01 0.140083E+10
           
Annual Sum or Average 0.475596E+10 93211676.32 0.466275E+10 0.617400E+10 0.899799E+10
Minimum of Months 0.229957E+09 0.00 0.229957E+09 40489950.29 0.163107E+09
Maximum of Months 0.596423E+09 39377515.23 0.557046E+09 0.114881E+10 0.166198E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.105104E+10 0.474071E+09 0.576970E+09 0.755199E+09 0.288486E+10
February 0.119680E+10 0.643031E+09 0.553772E+09 0.119914E+10 0.212354E+10
March 0.166704E+10 0.758884E+09 0.908160E+09 0.197509E+10 0.148228E+10
April 0.195086E+10 0.889537E+09 0.106132E+10 0.278871E+10 0.113678E+10
May 0.221359E+10 0.936093E+09 0.127750E+10 0.347390E+10 0.802631E+09
June 0.221789E+10 0.929567E+09 0.128832E+10 0.393294E+10 0.511620E+09
July 0.223461E+10 0.939459E+09 0.129515E+10 0.408699E+10 0.388964E+09
August 0.204393E+10 0.810897E+09 0.123303E+10 0.379495E+10 0.332031E+09
September 0.162564E+10 0.720278E+09 0.905366E+09 0.260587E+10 0.726225E+09
October 0.143304E+10 0.745643E+09 0.687397E+09 0.183741E+10 0.151779E+10
November 0.110877E+10 0.502044E+09 0.606724E+09 0.108888E+10 0.192160E+10
December 0.992421E+09 0.452382E+09 0.540039E+09 0.755717E+09 0.243688E+10
           
Annual Sum or Average 0.197356E+11 0.880189E+10 0.109338E+11 0.282948E+11 0.162652E+11
Minimum of Months 0.992421E+09 0.452382E+09 0.540039E+09 0.755199E+09 0.332031E+09
Maximum of Months 0.223461E+10 0.939459E+09 0.129515E+10 0.408699E+10 0.288486E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41557201.42 18744328.32 22812873.10 29859897.26 0.114065E+09
February 47320506.07 25424863.36 21895642.72 47413040.73 83962849.99
March 65913438.86 30005591.80 35907847.06 78093445.60 58608116.76
April 77135194.26 35171493.49 41963700.77 0.110263E+09 44947330.82
May 87523548.73 37012286.17 50511262.56 0.137355E+09 31735319.33
June 87693210.88 36754233.49 50938977.38 0.155505E+09 20228980.67
July 88354573.77 37145363.44 51209210.33 0.161596E+09 15379287.65
August 80815226.94 32062140.92 48753086.02 0.150049E+09 13128205.95
September 64276518.48 28479146.03 35797372.45 0.103034E+09 28714280.61
October 56661118.88 29482041.05 27179077.83 72649604.74 60012078.81
November 43839703.36 19850374.49 23989328.87 43053227.36 75978298.51
December 39239425.34 17886781.13 21352644.21 29880365.95 96352050.86
           
Annual Sum or Average 0.780330E+09 0.348019E+09 0.432311E+09 0.111875E+10 0.643112E+09
Minimum of Months 39239425.34 17886781.13 21352644.21 29859897.26 13128205.95
Maximum of Months 88354573.77 37145363.44 51209210.33 0.161596E+09 0.114065E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133037E+10 0.927527E+09 0.402843E+09 0.154742E+10 0.142524E+10
February 0.112152E+10 0.751783E+09 0.369736E+09 0.142377E+10 0.109604E+10
March 0.111669E+10 0.581952E+09 0.534742E+09 0.155068E+10 0.824728E+09
April 0.809353E+09 0.263460E+09 0.545893E+09 0.126324E+10 0.637487E+09
May 0.675724E+09 78536548.52 0.597187E+09 0.111223E+10 0.432779E+09
June 0.604624E+09 33644551.71 0.570980E+09 0.116742E+10 0.272134E+09
July 0.631639E+09 47098022.03 0.584540E+09 0.127473E+10 0.200888E+09
August 0.754129E+09 0.140873E+09 0.613257E+09 0.153516E+10 0.177367E+09
September 0.802601E+09 0.298524E+09 0.504077E+09 0.138345E+10 0.397173E+09
October 0.120232E+10 0.778864E+09 0.423460E+09 0.178660E+10 0.830470E+09
November 0.125176E+10 0.830643E+09 0.421114E+09 0.167003E+10 0.103431E+10
December 0.131138E+10 0.922561E+09 0.388815E+09 0.160833E+10 0.125853E+10
           
Annual Sum or Average 0.116121E+11 0.565547E+10 0.595665E+10 0.173231E+11 0.858715E+10
Minimum of Months 0.604624E+09 33644551.71 0.369736E+09 0.111223E+10 0.177367E+09
Maximum of Months 0.133037E+10 0.927527E+09 0.613257E+09 0.178660E+10 0.142524E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133037E+10 0.927527E+09 0.402843E+09 0.154742E+10 0.142524E+10
February 0.112152E+10 0.751783E+09 0.369736E+09 0.142377E+10 0.109604E+10
March 0.111669E+10 0.581952E+09 0.534742E+09 0.155068E+10 0.824728E+09
April 0.809353E+09 0.263460E+09 0.545893E+09 0.126324E+10 0.637487E+09
May 0.675724E+09 78536548.52 0.597187E+09 0.111223E+10 0.432779E+09
June 0.604624E+09 33644551.71 0.570980E+09 0.116742E+10 0.272134E+09
July 0.631639E+09 47098022.03 0.584540E+09 0.127473E+10 0.200888E+09
August 0.754129E+09 0.140873E+09 0.613257E+09 0.153516E+10 0.177367E+09
September 0.802601E+09 0.298524E+09 0.504077E+09 0.138345E+10 0.397173E+09
October 0.120232E+10 0.778864E+09 0.423460E+09 0.178660E+10 0.830470E+09
November 0.125176E+10 0.830643E+09 0.421114E+09 0.167003E+10 0.103431E+10
December 0.131138E+10 0.922561E+09 0.388815E+09 0.160833E+10 0.125853E+10
           
Annual Sum or Average 0.116121E+11 0.565547E+10 0.595665E+10 0.173231E+11 0.858715E+10
Minimum of Months 0.604624E+09 33644551.71 0.369736E+09 0.111223E+10 0.177367E+09
Maximum of Months 0.133037E+10 0.927527E+09 0.613257E+09 0.178660E+10 0.142524E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133029E+10 0.927469E+09 0.402817E+09 0.154733E+10 0.142515E+10
February 0.112145E+10 0.751735E+09 0.369713E+09 0.142368E+10 0.109597E+10
March 0.111662E+10 0.581915E+09 0.534708E+09 0.155058E+10 0.824675E+09
April 0.809302E+09 0.263443E+09 0.545859E+09 0.126316E+10 0.637447E+09
May 0.675681E+09 78531585.46 0.597149E+09 0.111216E+10 0.432752E+09
June 0.604586E+09 33642425.56 0.570944E+09 0.116735E+10 0.272117E+09
July 0.631599E+09 47095045.70 0.584504E+09 0.127465E+10 0.200875E+09
August 0.754082E+09 0.140864E+09 0.613218E+09 0.153506E+10 0.177355E+09
September 0.802550E+09 0.298505E+09 0.504045E+09 0.138337E+10 0.397148E+09
October 0.120225E+10 0.778815E+09 0.423434E+09 0.178649E+10 0.830417E+09
November 0.125168E+10 0.830591E+09 0.421088E+09 0.166992E+10 0.103424E+10
December 0.131129E+10 0.922503E+09 0.388791E+09 0.160823E+10 0.125845E+10
           
Annual Sum or Average 0.116114E+11 0.565511E+10 0.595627E+10 0.173220E+11 0.858660E+10
Minimum of Months 0.604586E+09 33642425.56 0.369713E+09 0.111216E+10 0.177355E+09
Maximum of Months 0.133029E+10 0.927469E+09 0.613218E+09 0.178649E+10 0.142515E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.107957E+10 0.500778E+09 0.578790E+09 0.885682E+09 0.300276E+10
February 0.111940E+10 0.523386E+09 0.596015E+09 0.119619E+10 0.224749E+10
March 0.182671E+10 0.882705E+09 0.944005E+09 0.235665E+10 0.160609E+10
April 0.198873E+10 0.910029E+09 0.107870E+10 0.294029E+10 0.124342E+10
May 0.206535E+10 0.782478E+09 0.128288E+10 0.331371E+10 0.875104E+09
June 0.210193E+10 0.808598E+09 0.129333E+10 0.377944E+10 0.565170E+09
July 0.204868E+10 0.759579E+09 0.128910E+10 0.380662E+10 0.417511E+09
August 0.200742E+10 0.750692E+09 0.125673E+10 0.375673E+10 0.366643E+09
September 0.158274E+10 0.659277E+09 0.923461E+09 0.256536E+10 0.771768E+09
October 0.145703E+10 0.756357E+09 0.700675E+09 0.199500E+10 0.164183E+10
November 0.112531E+10 0.505094E+09 0.620213E+09 0.127399E+10 0.208533E+10
December 0.959316E+09 0.419605E+09 0.539712E+09 0.840815E+09 0.260062E+10
           
Annual Sum or Average 0.193622E+11 0.825858E+10 0.111036E+11 0.287105E+11 0.174237E+11
Minimum of Months 0.959316E+09 0.419605E+09 0.539712E+09 0.840815E+09 0.366643E+09
Maximum of Months 0.210193E+10 0.910029E+09 0.129333E+10 0.380662E+10 0.300276E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42685035.43 19800245.05 22884790.38 35018931.31 0.118726E+09
February 44259987.63 20694142.70 23565844.93 47296014.71 88863776.82
March 72226267.00 34901238.65 37325028.36 93179695.80 63503160.50
April 78632209.33 35981626.23 42650583.10 0.116256E+09 49163544.40
May 81662019.58 30938378.45 50723641.13 0.131021E+09 34600799.22
June 83108020.92 31971121.65 51136899.27 0.149435E+09 22346294.47
July 81002876.45 30032981.75 50969894.70 0.150510E+09 16507997.59
August 79371262.08 29681575.71 49689686.37 0.148537E+09 14496727.82
September 62579864.35 26067143.10 36512721.25 0.101432E+09 30514990.82
October 57609595.62 29905591.65 27704003.97 78880113.01 64916381.41
November 44493501.38 19970895.60 24522605.78 50372212.67 82452184.00
December 37930402.25 16590743.33 21339658.92 33244921.74 0.102826E+09
           
Annual Sum or Average 0.765561E+09 0.326536E+09 0.439025E+09 0.113518E+10 0.688918E+09
Minimum of Months 37930402.25 16590743.33 21339658.92 33244921.74 14496727.82
Maximum of Months 83108020.92 35981626.23 51136899.27 0.150510E+09 0.118726E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.746277E+09 0.00 0.746277E+09 0.114555E+09 0.501726E+10
February 0.747125E+09 0.00 0.747125E+09 0.331984E+09 0.371139E+10
March 0.116131E+10 0.00 0.116131E+10 0.823184E+09 0.260278E+10
April 0.135940E+10 6029322.01 0.135337E+10 0.152487E+10 0.199445E+10
May 0.168001E+10 53616748.83 0.162639E+10 0.238038E+10 0.133586E+10
June 0.178928E+10 0.118135E+09 0.167115E+10 0.329470E+10 0.812640E+09
July 0.174447E+10 84799715.93 0.165967E+10 0.340685E+10 0.605322E+09
August 0.155141E+10 16900235.20 0.153451E+10 0.310855E+10 0.505333E+09
September 0.113489E+10 159761.37 0.113473E+10 0.172172E+10 0.110872E+10
October 0.891659E+09 0.00 0.891659E+09 0.802413E+09 0.240658E+10
November 0.772262E+09 0.00 0.772262E+09 0.416230E+09 0.315488E+10
December 0.689877E+09 0.00 0.689877E+09 0.122529E+09 0.412004E+10
           
Annual Sum or Average 0.142680E+11 0.279641E+09 0.139883E+11 0.180480E+11 0.273753E+11
Minimum of Months 0.689877E+09 0.00 0.689877E+09 0.114555E+09 0.505333E+09
Maximum of Months 0.178928E+10 0.118135E+09 0.167115E+10 0.340685E+10 0.501726E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109261E+10 0.492825E+09 0.599790E+09 0.770966E+09 0.299152E+10
February 0.124414E+10 0.668469E+09 0.575674E+09 0.121709E+10 0.222722E+10
March 0.173298E+10 0.788905E+09 0.944080E+09 0.198568E+10 0.159174E+10
April 0.202802E+10 0.924727E+09 0.110330E+10 0.281999E+10 0.124778E+10
May 0.230115E+10 0.973125E+09 0.132803E+10 0.354802E+10 0.874360E+09
June 0.230561E+10 0.966340E+09 0.133927E+10 0.405806E+10 0.540145E+09
July 0.232300E+10 0.976623E+09 0.134638E+10 0.422875E+10 0.404469E+09
August 0.212478E+10 0.842976E+09 0.128180E+10 0.393665E+10 0.334989E+09
September 0.168995E+10 0.748772E+09 0.941176E+09 0.271554E+10 0.708018E+09
October 0.148972E+10 0.775140E+09 0.714585E+09 0.192479E+10 0.148041E+10
November 0.115263E+10 0.521905E+09 0.630721E+09 0.115764E+10 0.188550E+10
December 0.103168E+10 0.470278E+09 0.561398E+09 0.787386E+09 0.244935E+10
           
Annual Sum or Average 0.205163E+11 0.915008E+10 0.113662E+11 0.291506E+11 0.167355E+11
Minimum of Months 0.103168E+10 0.470278E+09 0.561398E+09 0.770966E+09 0.334989E+09
Maximum of Months 0.232300E+10 0.976623E+09 0.134638E+10 0.422875E+10 0.299152E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.399118E+10 0.278264E+10 0.120854E+10 0.454168E+10 0.423050E+10
February 0.336461E+10 0.225539E+10 0.110922E+10 0.417655E+10 0.329259E+10
March 0.335013E+10 0.174589E+10 0.160424E+10 0.451697E+10 0.254395E+10
April 0.242809E+10 0.790395E+09 0.163769E+10 0.364613E+10 0.205927E+10
May 0.202719E+10 0.235614E+09 0.179158E+10 0.322222E+10 0.141763E+10
June 0.181389E+10 0.100936E+09 0.171295E+10 0.344732E+10 0.867672E+09
July 0.189493E+10 0.141297E+09 0.175364E+10 0.378755E+10 0.632784E+09
August 0.226241E+10 0.422627E+09 0.183979E+10 0.459579E+10 0.530357E+09
September 0.240784E+10 0.895590E+09 0.151225E+10 0.414851E+10 0.113665E+10
October 0.360703E+10 0.233664E+10 0.127039E+10 0.534658E+10 0.233978E+10
November 0.375534E+10 0.249198E+10 0.126336E+10 0.499986E+10 0.291424E+10
December 0.393420E+10 0.276774E+10 0.116646E+10 0.477521E+10 0.361440E+10
           
Annual Sum or Average 0.348369E+11 0.169667E+11 0.178701E+11 0.512044E+11 0.255798E+11
Minimum of Months 0.181389E+10 0.100936E+09 0.110922E+10 0.322222E+10 0.530357E+09
Maximum of Months 0.399118E+10 0.278264E+10 0.183979E+10 0.534658E+10 0.423050E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.112227E+10 0.520587E+09 0.601681E+09 0.899932E+09 0.311325E+10
February 0.116368E+10 0.544089E+09 0.619587E+09 0.121236E+10 0.236211E+10
March 0.189896E+10 0.917621E+09 0.981340E+09 0.238431E+10 0.172190E+10
April 0.206738E+10 0.946027E+09 0.112136E+10 0.297716E+10 0.136220E+10
May 0.214704E+10 0.813430E+09 0.133361E+10 0.338675E+10 0.954316E+09
June 0.218506E+10 0.840583E+09 0.134448E+10 0.389769E+10 0.597836E+09
July 0.212971E+10 0.789625E+09 0.134009E+10 0.393777E+10 0.436607E+09
August 0.208681E+10 0.780386E+09 0.130643E+10 0.389757E+10 0.369948E+09
September 0.164534E+10 0.685356E+09 0.959983E+09 0.267428E+10 0.754764E+09
October 0.151466E+10 0.786276E+09 0.728386E+09 0.208582E+10 0.160497E+10
November 0.116982E+10 0.525073E+09 0.644742E+09 0.133997E+10 0.205761E+10
December 0.997260E+09 0.436203E+09 0.561057E+09 0.869349E+09 0.262376E+10
           
Annual Sum or Average 0.201280E+11 0.858525E+10 0.115427E+11 0.295630E+11 0.179593E+11
Minimum of Months 0.997260E+09 0.436203E+09 0.561057E+09 0.869349E+09 0.369948E+09
Maximum of Months 0.218506E+10 0.946027E+09 0.134448E+10 0.393777E+10 0.311325E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 47.74 1775.69 278.63 0.00 278.63 0.00 0.00
February 144.47 1451.86 308.83 0.00 308.83 0.00 0.00
March 320.87 908.32 433.58 0.00 433.58 0.00 0.00
April 596.63 730.12 524.46 2.33 522.13 0.00 0.00
May 890.41 479.27 627.24 20.02 607.23 0.00 0.00
June 1265.62 305.69 690.31 45.58 644.73 0.00 0.00
July 1263.06 221.55 651.31 31.66 619.65 0.00 0.00
August 1152.80 184.04 579.23 6.31 572.92 0.00 0.00
September 669.24 399.84 437.84 0.06 437.78 0.00 0.00
October 314.28 828.48 332.91 0.00 332.91 0.00 0.00
November 181.03 1120.53 297.94 0.00 297.94 0.00 0.00
December 52.94 1423.76 257.57 0.00 257.57 0.00 0.00
               
Annual Sum or Average 577.33 815.87 452.43 8.87 443.57 0.00 0.00
Minimum of Months 47.74 184.04 257.57 0.00 257.57 0.00 0.00
Maximum of Months 1265.62 1775.69 690.31 45.58 644.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 298.18 1058.39 407.94 184.00 223.94 0.00 0.00
February 513.29 872.03 514.28 276.32 237.96 0.00 0.00
March 752.40 559.75 647.02 294.54 352.48 0.00 0.00
April 1092.80 460.68 782.42 356.76 425.66 0.00 0.00
May 1323.98 316.08 859.15 363.32 495.83 0.00 0.00
June 1560.45 203.96 889.51 372.82 516.70 0.00 0.00
July 1571.74 148.16 867.31 364.63 502.68 0.00 0.00
August 1463.24 122.21 793.30 314.73 478.57 0.00 0.00
September 1049.92 257.36 651.99 288.88 363.11 0.00 0.00
October 729.46 515.33 556.20 289.40 266.80 0.00 0.00
November 466.55 673.84 444.69 201.35 243.33 0.00 0.00
December 306.84 847.82 385.18 175.58 209.60 0.00 0.00
               
Annual Sum or Average 929.55 501.07 650.57 290.15 360.42 0.00 0.00
Minimum of Months 298.18 122.21 385.18 175.58 209.60 0.00 0.00
Maximum of Months 1571.74 1058.39 889.51 372.82 516.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1718.18 1493.18 1490.14 1038.92 451.22 0.00 0.00
February 1742.57 1285.80 1390.80 932.29 458.51 0.00 0.00
March 1699.81 892.10 1250.80 651.84 598.96 0.00 0.00
April 1412.48 755.88 936.76 304.94 631.83 0.00 0.00
May 1202.27 508.27 756.87 87.97 668.90 0.00 0.00
June 1323.25 324.88 699.80 38.94 660.86 0.00 0.00
July 1404.66 230.47 707.49 52.75 654.73 0.00 0.00
August 1706.77 192.77 844.69 157.79 686.90 0.00 0.00
September 1603.01 412.25 928.95 345.52 583.43 0.00 0.00
October 2008.62 813.18 1346.71 872.40 474.31 0.00 0.00
November 1956.02 1040.93 1448.82 961.41 487.41 0.00 0.00
December 1808.37 1252.54 1468.86 1033.36 435.51 0.00 0.00
               
Annual Sum or Average 1631.90 764.05 1104.67 538.01 566.66 0.00 0.00
Minimum of Months 1202.27 192.77 699.80 38.94 435.51 0.00 0.00
Maximum of Months 2008.62 1493.18 1490.14 1038.92 686.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 342.52 1100.83 419.01 194.36 224.64 0.00 0.00
February 506.80 923.83 481.02 224.90 256.11 0.00 0.00
March 898.12 602.76 708.99 342.60 366.39 0.00 0.00
April 1153.68 499.25 797.60 364.98 432.62 0.00 0.00
May 1265.47 341.62 801.61 303.70 497.91 0.00 0.00
June 1499.51 223.31 843.00 324.30 518.70 0.00 0.00
July 1465.09 158.45 795.14 294.81 500.33 0.00 0.00
August 1450.31 134.15 779.13 291.36 487.76 0.00 0.00
September 1036.06 272.25 634.78 264.41 370.36 0.00 0.00
October 787.33 555.24 565.51 293.56 271.95 0.00 0.00
November 530.96 734.21 451.32 202.57 248.74 0.00 0.00
December 333.18 908.68 372.33 162.86 209.47 0.00 0.00
               
Annual Sum or Average 941.37 535.87 638.25 272.24 366.02 0.00 0.00
Minimum of Months 333.18 134.15 372.33 162.86 209.47 0.00 0.00
Maximum of Months 1499.51 1100.83 843.00 364.98 518.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 45.35 1861.49 278.62 0.00 278.62 0.00 0.00
February 148.95 1498.32 308.83 0.00 308.83 0.00 0.00
March 345.51 907.05 433.57 0.00 433.57 0.00 0.00
April 643.95 697.40 524.45 2.33 522.12 0.00 0.00
May 931.06 454.49 627.23 20.02 607.21 0.00 0.00
June 1291.76 295.85 690.30 45.58 644.72 0.00 0.00
July 1286.73 214.17 651.30 31.66 619.64 0.00 0.00
August 1167.13 182.69 579.22 6.31 572.91 0.00 0.00
September 662.46 439.93 437.84 0.06 437.77 0.00 0.00
October 294.77 931.65 332.90 0.00 332.90 0.00 0.00
November 154.33 1257.97 297.93 0.00 297.93 0.00 0.00
December 46.44 1569.00 257.57 0.00 257.57 0.00 0.00
               
Annual Sum or Average 587.32 855.96 452.43 8.87 443.56 0.00 0.00
Minimum of Months 45.35 182.69 257.57 0.00 257.57 0.00 0.00
Maximum of Months 1291.76 1861.49 690.30 45.58 644.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 293.11 1119.67 407.93 184.00 223.93 0.00 0.00
February 515.28 912.49 514.27 276.31 237.96 0.00 0.00
March 766.57 575.30 647.01 294.54 352.47 0.00 0.00
April 1118.43 455.91 782.41 356.75 425.65 0.00 0.00
May 1348.29 311.52 859.14 363.32 495.82 0.00 0.00
June 1577.33 205.19 889.50 372.81 516.69 0.00 0.00
July 1586.24 150.96 867.30 364.62 502.67 0.00 0.00
August 1472.89 128.87 793.29 314.72 478.56 0.00 0.00
September 1045.10 291.26 651.98 288.87 363.10 0.00 0.00
October 713.14 589.08 556.19 289.40 266.79 0.00 0.00
November 436.70 770.67 444.68 201.35 243.33 0.00 0.00
December 293.31 945.80 385.18 175.58 209.60 0.00 0.00
               
Annual Sum or Average 932.70 536.16 650.56 290.14 360.42 0.00 0.00
Minimum of Months 293.11 128.87 385.18 175.58 209.60 0.00 0.00
Maximum of Months 1586.24 1119.67 889.50 372.81 516.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1733.19 1596.34 1490.08 1038.88 451.20 0.00 0.00
February 1765.56 1359.15 1390.74 932.25 458.49 0.00 0.00
March 1736.83 923.73 1250.75 651.81 598.94 0.00 0.00
April 1462.05 737.82 936.73 304.92 631.81 0.00 0.00
May 1245.75 484.73 756.84 87.96 668.88 0.00 0.00
June 1351.16 314.96 699.78 38.94 660.84 0.00 0.00
July 1427.75 225.00 707.47 52.75 654.71 0.00 0.00
August 1719.45 198.66 844.66 157.78 686.88 0.00 0.00
September 1601.19 459.68 928.92 345.51 583.41 0.00 0.00
October 2001.08 930.17 1346.66 872.37 474.30 0.00 0.00
November 1932.86 1197.09 1448.76 961.37 487.39 0.00 0.00
December 1801.41 1409.62 1468.80 1033.31 435.49 0.00 0.00
               
Annual Sum or Average 1647.90 816.87 1104.63 537.99 566.64 0.00 0.00
Minimum of Months 1245.75 198.66 699.78 38.94 435.49 0.00 0.00
Maximum of Months 2001.08 1596.34 1490.08 1038.88 686.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 343.75 1165.43 419.00 194.36 224.64 0.00 0.00
February 514.01 965.76 481.01 224.90 256.11 0.00 0.00
March 914.66 623.35 708.98 342.59 366.39 0.00 0.00
April 1179.22 498.68 797.59 364.97 432.62 0.00 0.00
May 1286.11 339.64 801.60 303.69 497.91 0.00 0.00
June 1515.77 226.67 842.99 324.29 518.70 0.00 0.00
July 1477.42 162.04 795.13 294.81 500.33 0.00 0.00
August 1458.06 142.30 779.12 291.36 487.76 0.00 0.00
September 1028.85 309.52 634.77 264.41 370.36 0.00 0.00
October 774.30 637.23 565.50 293.56 271.95 0.00 0.00
November 510.94 836.34 451.31 202.57 248.74 0.00 0.00
December 326.34 1009.35 372.33 162.86 209.47 0.00 0.00
               
Annual Sum or Average 946.40 574.35 638.25 272.23 366.01 0.00 0.00
Minimum of Months 326.34 142.30 372.33 162.86 209.47 0.00 0.00
Maximum of Months 1515.77 1165.43 842.99 364.97 518.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 42.77 1873.23 278.63 0.00 278.63 0.00 0.00
February 137.23 1534.14 308.83 0.00 308.83 0.00 0.00
March 307.34 971.77 433.58 0.00 433.58 0.00 0.00
April 588.30 769.46 524.46 2.33 522.13 0.00 0.00
May 888.73 498.75 627.24 20.02 607.23 0.00 0.00
June 1271.10 313.52 690.31 45.58 644.73 0.00 0.00
July 1271.97 226.00 651.31 31.66 619.65 0.00 0.00
August 1160.60 188.67 579.23 6.31 572.92 0.00 0.00
September 664.24 427.75 437.84 0.06 437.78 0.00 0.00
October 299.59 898.51 332.91 0.00 332.91 0.00 0.00
November 160.58 1217.16 297.94 0.00 297.94 0.00 0.00
December 45.75 1538.25 257.57 0.00 257.57 0.00 0.00
               
Annual Sum or Average 572.30 868.06 452.43 8.87 443.57 0.00 0.00
Minimum of Months 42.77 188.67 257.57 0.00 257.57 0.00 0.00
Maximum of Months 1271.97 1873.23 690.31 45.58 644.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 287.85 1116.91 407.94 184.00 223.94 0.00 0.00
February 503.09 920.64 514.28 276.32 237.96 0.00 0.00
March 741.37 594.29 647.02 294.54 352.48 0.00 0.00
April 1087.96 481.40 782.42 356.76 425.66 0.00 0.00
May 1324.68 326.45 859.15 363.32 495.83 0.00 0.00
June 1565.61 208.39 889.51 372.82 516.70 0.00 0.00
July 1578.83 151.01 867.31 364.63 502.68 0.00 0.00
August 1469.78 125.07 793.30 314.73 478.57 0.00 0.00
September 1047.66 273.16 651.99 288.88 363.11 0.00 0.00
October 718.63 552.72 556.20 289.40 266.80 0.00 0.00
November 446.62 727.43 444.69 201.35 243.33 0.00 0.00
December 293.98 914.48 385.18 175.58 209.60 0.00 0.00
               
Annual Sum or Average 924.36 530.68 650.57 290.15 360.42 0.00 0.00
Minimum of Months 287.85 125.07 385.18 175.58 209.60 0.00 0.00
Maximum of Months 1578.83 1116.91 889.51 372.82 516.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1695.67 1579.49 1490.14 1038.92 451.22 0.00 0.00
February 1726.42 1361.02 1390.80 932.29 458.51 0.00 0.00
March 1686.44 949.80 1250.80 651.84 598.96 0.00 0.00
April 1406.69 794.47 936.76 304.94 631.83 0.00 0.00
May 1203.04 529.28 756.87 87.97 668.90 0.00 0.00
June 1329.98 334.75 699.80 38.94 660.86 0.00 0.00
July 1414.11 236.25 707.49 52.75 654.73 0.00 0.00
August 1715.87 198.01 844.69 157.79 686.90 0.00 0.00
September 1600.50 438.52 928.95 345.52 583.43 0.00 0.00
October 1996.18 873.57 1346.71 872.40 474.31 0.00 0.00
November 1928.96 1124.32 1448.82 961.41 487.41 0.00 0.00
December 1782.86 1349.46 1468.86 1033.36 435.51 0.00 0.00
               
Annual Sum or Average 1623.68 811.13 1104.67 538.01 566.66 0.00 0.00
Minimum of Months 1203.04 198.01 699.80 38.94 435.51 0.00 0.00
Maximum of Months 1996.18 1579.49 1490.14 1038.92 686.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 336.00 1162.35 419.01 194.36 224.64 0.00 0.00
February 501.14 976.40 481.02 224.90 256.11 0.00 0.00
March 890.20 642.88 708.99 342.60 366.39 0.00 0.00
April 1148.60 525.54 797.60 364.98 432.62 0.00 0.00
May 1264.47 356.30 801.61 303.70 497.91 0.00 0.00
June 1503.74 230.65 843.00 324.30 518.70 0.00 0.00
July 1470.20 163.01 795.14 294.81 500.33 0.00 0.00
August 1455.19 138.12 779.13 291.36 487.76 0.00 0.00
September 1031.75 291.19 634.78 264.41 370.36 0.00 0.00
October 778.76 599.23 565.51 293.56 271.95 0.00 0.00
November 516.96 793.83 451.32 202.57 248.74 0.00 0.00
December 324.58 979.60 372.33 162.86 209.47 0.00 0.00
               
Annual Sum or Average 937.44 569.48 638.25 272.24 366.02 0.00 0.00
Minimum of Months 324.58 138.12 372.33 162.86 209.47 0.00 0.00
Maximum of Months 1503.74 1162.35 843.00 364.98 518.70 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.127869E+09 0.475602E+10 0.746277E+09 0.00 0.746277E+09 0.00 0.00
February 0.349499E+09 0.351234E+10 0.747125E+09 0.00 0.747125E+09 0.00 0.00
March 0.859428E+09 0.243284E+10 0.116131E+10 0.00 0.116131E+10 0.00 0.00
April 0.154647E+10 0.189246E+10 0.135940E+10 6029322.01 0.135337E+10 0.00 0.00
May 0.238488E+10 0.128368E+10 0.168001E+10 53616748.83 0.162639E+10 0.00 0.00
June 0.328050E+10 0.792351E+09 0.178928E+10 0.118135E+09 0.167115E+10 0.00 0.00
July 0.338298E+10 0.593407E+09 0.174447E+10 84799715.93 0.165967E+10 0.00 0.00
August 0.308766E+10 0.492921E+09 0.155141E+10 16900235.20 0.153451E+10 0.00 0.00
September 0.173468E+10 0.103639E+10 0.113489E+10 159761.37 0.113473E+10 0.00 0.00
October 0.841765E+09 0.221900E+10 0.891659E+09 0.00 0.891659E+09 0.00 0.00
November 0.469242E+09 0.290440E+10 0.772262E+09 0.00 0.772262E+09 0.00 0.00
December 0.141792E+09 0.381339E+10 0.689877E+09 0.00 0.689877E+09 0.00 0.00
               
Annual Sum or Average 0.182068E+11 0.257292E+11 0.142680E+11 0.279641E+09 0.139883E+11 0.00 0.00
Minimum of Months 0.127869E+09 0.492921E+09 0.689877E+09 0.00 0.689877E+09 0.00 0.00
Maximum of Months 0.338298E+10 0.475602E+10 0.178928E+10 0.118135E+09 0.167115E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.798648E+09 0.283480E+10 0.109261E+10 0.492825E+09 0.599790E+09 0.00 0.00
February 0.124175E+10 0.210962E+10 0.124414E+10 0.668469E+09 0.575674E+09 0.00 0.00
March 0.201523E+10 0.149924E+10 0.173298E+10 0.788905E+09 0.944080E+09 0.00 0.00
April 0.283253E+10 0.119409E+10 0.202802E+10 0.924727E+09 0.110330E+10 0.00 0.00
May 0.354614E+10 0.846588E+09 0.230115E+10 0.973125E+09 0.132803E+10 0.00 0.00
June 0.404468E+10 0.528673E+09 0.230561E+10 0.966340E+09 0.133927E+10 0.00 0.00
July 0.420974E+10 0.396840E+09 0.232300E+10 0.976623E+09 0.134638E+10 0.00 0.00
August 0.391915E+10 0.327314E+09 0.212478E+10 0.842976E+09 0.128180E+10 0.00 0.00
September 0.272139E+10 0.667067E+09 0.168995E+10 0.748772E+09 0.941176E+09 0.00 0.00
October 0.195378E+10 0.138026E+10 0.148972E+10 0.775140E+09 0.714585E+09 0.00 0.00
November 0.120930E+10 0.174659E+10 0.115263E+10 0.521905E+09 0.630721E+09 0.00 0.00
December 0.821836E+09 0.227079E+10 0.103168E+10 0.470278E+09 0.561398E+09 0.00 0.00
               
Annual Sum or Average 0.293142E+11 0.158019E+11 0.205163E+11 0.915008E+10 0.113662E+11 0.00 0.00
Minimum of Months 0.798648E+09 0.327314E+09 0.103168E+10 0.470278E+09 0.561398E+09 0.00 0.00
Maximum of Months 0.420974E+10 0.283480E+10 0.232300E+10 0.976623E+09 0.134638E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.460197E+10 0.399932E+10 0.399118E+10 0.278264E+10 0.120854E+10 0.00 0.00
February 0.421562E+10 0.311062E+10 0.336461E+10 0.225539E+10 0.110922E+10 0.00 0.00
March 0.455276E+10 0.238940E+10 0.335013E+10 0.174589E+10 0.160424E+10 0.00 0.00
April 0.366115E+10 0.195924E+10 0.242809E+10 0.790395E+09 0.163769E+10 0.00 0.00
May 0.322016E+10 0.136134E+10 0.202719E+10 0.235614E+09 0.179158E+10 0.00 0.00
June 0.342986E+10 0.842092E+09 0.181389E+10 0.100936E+09 0.171295E+10 0.00 0.00
July 0.376224E+10 0.617279E+09 0.189493E+10 0.141297E+09 0.175364E+10 0.00 0.00
August 0.457140E+10 0.516306E+09 0.226241E+10 0.422627E+09 0.183979E+10 0.00 0.00
September 0.415500E+10 0.106854E+10 0.240784E+10 0.895590E+09 0.151225E+10 0.00 0.00
October 0.537990E+10 0.217802E+10 0.360703E+10 0.233664E+10 0.127039E+10 0.00 0.00
November 0.507002E+10 0.269809E+10 0.375534E+10 0.249198E+10 0.126336E+10 0.00 0.00
December 0.484353E+10 0.335480E+10 0.393420E+10 0.276774E+10 0.116646E+10 0.00 0.00
               
Annual Sum or Average 0.514636E+11 0.240951E+11 0.348369E+11 0.169667E+11 0.178701E+11 0.00 0.00
Minimum of Months 0.322016E+10 0.516306E+09 0.181389E+10 0.100936E+09 0.110922E+10 0.00 0.00
Maximum of Months 0.537990E+10 0.399932E+10 0.399118E+10 0.278264E+10 0.183979E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.917409E+09 0.294846E+10 0.112227E+10 0.520587E+09 0.601681E+09 0.00 0.00
February 0.122606E+10 0.223492E+10 0.116368E+10 0.544089E+09 0.619587E+09 0.00 0.00
March 0.240553E+10 0.161442E+10 0.189896E+10 0.917621E+09 0.981340E+09 0.00 0.00
April 0.299034E+10 0.129405E+10 0.206738E+10 0.946027E+09 0.112136E+10 0.00 0.00
May 0.338943E+10 0.914999E+09 0.214704E+10 0.813430E+09 0.133361E+10 0.00 0.00
June 0.388674E+10 0.578811E+09 0.218506E+10 0.840583E+09 0.134448E+10 0.00 0.00
July 0.392409E+10 0.424395E+09 0.212971E+10 0.789625E+09 0.134009E+10 0.00 0.00
August 0.388451E+10 0.359296E+09 0.208681E+10 0.780386E+09 0.130643E+10 0.00 0.00
September 0.268547E+10 0.705669E+09 0.164534E+10 0.685356E+09 0.959983E+09 0.00 0.00
October 0.210877E+10 0.148717E+10 0.151466E+10 0.786276E+09 0.728386E+09 0.00 0.00
November 0.137626E+10 0.190308E+10 0.116982E+10 0.525073E+09 0.644742E+09 0.00 0.00
December 0.892388E+09 0.243380E+10 0.997260E+09 0.436203E+09 0.561057E+09 0.00 0.00
               
Annual Sum or Average 0.296870E+11 0.168991E+11 0.201280E+11 0.858525E+10 0.115427E+11 0.00 0.00
Minimum of Months 0.892388E+09 0.359296E+09 0.997260E+09 0.436203E+09 0.561057E+09 0.00 0.00
Maximum of Months 0.392409E+10 0.294846E+10 0.218506E+10 0.946027E+09 0.134448E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121469E+09 0.498583E+10 0.746261E+09 0.00 0.746261E+09 0.00 0.00
February 0.360344E+09 0.362473E+10 0.747110E+09 0.00 0.747110E+09 0.00 0.00
March 0.925419E+09 0.242945E+10 0.116128E+10 0.00 0.116128E+10 0.00 0.00
April 0.166911E+10 0.180765E+10 0.135937E+10 6029144.79 0.135334E+10 0.00 0.00
May 0.249375E+10 0.121732E+10 0.167998E+10 53615172.89 0.162636E+10 0.00 0.00
June 0.334824E+10 0.766840E+09 0.178925E+10 0.118131E+09 0.167111E+10 0.00 0.00
July 0.344638E+10 0.573624E+09 0.174443E+10 84797223.43 0.165963E+10 0.00 0.00
August 0.312605E+10 0.489313E+09 0.155138E+10 16899738.46 0.153448E+10 0.00 0.00
September 0.171709E+10 0.114029E+10 0.113487E+10 159756.68 0.113471E+10 0.00 0.00
October 0.789500E+09 0.249533E+10 0.891642E+09 0.00 0.891642E+09 0.00 0.00
November 0.400016E+09 0.326067E+10 0.772246E+09 0.00 0.772246E+09 0.00 0.00
December 0.124386E+09 0.420240E+10 0.689863E+09 0.00 0.689863E+09 0.00 0.00
               
Annual Sum or Average 0.185217E+11 0.269934E+11 0.142677E+11 0.279633E+09 0.139880E+11 0.00 0.00
Minimum of Months 0.121469E+09 0.489313E+09 0.689863E+09 0.00 0.689863E+09 0.00 0.00
Maximum of Months 0.344638E+10 0.498583E+10 0.178925E+10 0.118131E+09 0.167111E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.785059E+09 0.299893E+10 0.109260E+10 0.492815E+09 0.599783E+09 0.00 0.00
February 0.124656E+10 0.220750E+10 0.124412E+10 0.668456E+09 0.575668E+09 0.00 0.00
March 0.205319E+10 0.154089E+10 0.173296E+10 0.788890E+09 0.944068E+09 0.00 0.00
April 0.289897E+10 0.118173E+10 0.202799E+10 0.924709E+09 0.110329E+10 0.00 0.00
May 0.361126E+10 0.834367E+09 0.230112E+10 0.973106E+09 0.132801E+10 0.00 0.00
June 0.408844E+10 0.531849E+09 0.230558E+10 0.966321E+09 0.133926E+10 0.00 0.00
July 0.424859E+10 0.404343E+09 0.232297E+10 0.976604E+09 0.134636E+10 0.00 0.00
August 0.394499E+10 0.345159E+09 0.212475E+10 0.842959E+09 0.128179E+10 0.00 0.00
September 0.270890E+10 0.754939E+09 0.168992E+10 0.748757E+09 0.941164E+09 0.00 0.00
October 0.191006E+10 0.157780E+10 0.148970E+10 0.775125E+09 0.714577E+09 0.00 0.00
November 0.113193E+10 0.199758E+10 0.115261E+10 0.521895E+09 0.630714E+09 0.00 0.00
December 0.785597E+09 0.253323E+10 0.103166E+10 0.470269E+09 0.561391E+09 0.00 0.00
               
Annual Sum or Average 0.294135E+11 0.169083E+11 0.205160E+11 0.914990E+10 0.113661E+11 0.00 0.00
Minimum of Months 0.785059E+09 0.345159E+09 0.103166E+10 0.470269E+09 0.561391E+09 0.00 0.00
Maximum of Months 0.424859E+10 0.299893E+10 0.232297E+10 0.976604E+09 0.134636E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.464217E+10 0.427564E+10 0.399103E+10 0.278252E+10 0.120850E+10 0.00 0.00
February 0.427123E+10 0.328806E+10 0.336449E+10 0.225530E+10 0.110919E+10 0.00 0.00
March 0.465193E+10 0.247413E+10 0.335001E+10 0.174582E+10 0.160419E+10 0.00 0.00
April 0.378963E+10 0.191242E+10 0.242801E+10 0.790362E+09 0.163765E+10 0.00 0.00
May 0.333662E+10 0.129831E+10 0.202713E+10 0.235605E+09 0.179152E+10 0.00 0.00
June 0.350220E+10 0.816384E+09 0.181384E+10 0.100932E+09 0.171290E+10 0.00 0.00
July 0.382410E+10 0.602651E+09 0.189488E+10 0.141291E+09 0.175358E+10 0.00 0.00
August 0.460537E+10 0.532088E+09 0.226234E+10 0.422609E+09 0.183973E+10 0.00 0.00
September 0.415027E+10 0.119149E+10 0.240775E+10 0.895553E+09 0.151220E+10 0.00 0.00
October 0.535969E+10 0.249136E+10 0.360690E+10 0.233654E+10 0.127035E+10 0.00 0.00
November 0.500998E+10 0.310285E+10 0.375519E+10 0.249188E+10 0.126332E+10 0.00 0.00
December 0.482489E+10 0.377552E+10 0.393405E+10 0.276763E+10 0.116642E+10 0.00 0.00
               
Annual Sum or Average 0.519681E+11 0.257609E+11 0.348356E+11 0.169660E+11 0.178696E+11 0.00 0.00
Minimum of Months 0.333662E+10 0.532088E+09 0.181384E+10 0.100932E+09 0.110919E+10 0.00 0.00
Maximum of Months 0.535969E+10 0.427564E+10 0.399103E+10 0.278252E+10 0.183973E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.920701E+09 0.312148E+10 0.112225E+10 0.520578E+09 0.601675E+09 0.00 0.00
February 0.124348E+10 0.233636E+10 0.116366E+10 0.544080E+09 0.619581E+09 0.00 0.00
March 0.244983E+10 0.166959E+10 0.189894E+10 0.917606E+09 0.981330E+09 0.00 0.00
April 0.305655E+10 0.129258E+10 0.206736E+10 0.946011E+09 0.112135E+10 0.00 0.00
May 0.344473E+10 0.909705E+09 0.214702E+10 0.813416E+09 0.133360E+10 0.00 0.00
June 0.392887E+10 0.587516E+09 0.218503E+10 0.840569E+09 0.134446E+10 0.00 0.00
July 0.395713E+10 0.434019E+09 0.212969E+10 0.789612E+09 0.134007E+10 0.00 0.00
August 0.390526E+10 0.381140E+09 0.208679E+10 0.780373E+09 0.130642E+10 0.00 0.00
September 0.266679E+10 0.802283E+09 0.164532E+10 0.685344E+09 0.959973E+09 0.00 0.00
October 0.207388E+10 0.170674E+10 0.151464E+10 0.786263E+09 0.728379E+09 0.00 0.00
November 0.132436E+10 0.216779E+10 0.116980E+10 0.525065E+09 0.644736E+09 0.00 0.00
December 0.874060E+09 0.270345E+10 0.997247E+09 0.436196E+09 0.561051E+09 0.00 0.00
               
Annual Sum or Average 0.298457E+11 0.181126E+11 0.201277E+11 0.858511E+10 0.115426E+11 0.00 0.00
Minimum of Months 0.874060E+09 0.381140E+09 0.997247E+09 0.436196E+09 0.561051E+09 0.00 0.00
Maximum of Months 0.395713E+10 0.312148E+10 0.218503E+10 0.946011E+09 0.134446E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.114555E+09 0.501726E+10 0.746277E+09 0.00 0.746277E+09 0.00 0.00
February 0.331984E+09 0.371139E+10 0.747125E+09 0.00 0.747125E+09 0.00 0.00
March 0.823184E+09 0.260278E+10 0.116131E+10 0.00 0.116131E+10 0.00 0.00
April 0.152487E+10 0.199445E+10 0.135940E+10 6029322.01 0.135337E+10 0.00 0.00
May 0.238038E+10 0.133586E+10 0.168001E+10 53616748.83 0.162639E+10 0.00 0.00
June 0.329470E+10 0.812640E+09 0.178928E+10 0.118135E+09 0.167115E+10 0.00 0.00
July 0.340685E+10 0.605322E+09 0.174447E+10 84799715.93 0.165967E+10 0.00 0.00
August 0.310855E+10 0.505333E+09 0.155141E+10 16900235.20 0.153451E+10 0.00 0.00
September 0.172172E+10 0.110872E+10 0.113489E+10 159761.37 0.113473E+10 0.00 0.00
October 0.802413E+09 0.240658E+10 0.891659E+09 0.00 0.891659E+09 0.00 0.00
November 0.416230E+09 0.315488E+10 0.772262E+09 0.00 0.772262E+09 0.00 0.00
December 0.122529E+09 0.412004E+10 0.689877E+09 0.00 0.689877E+09 0.00 0.00
               
Annual Sum or Average 0.180480E+11 0.273753E+11 0.142680E+11 0.279641E+09 0.139883E+11 0.00 0.00
Minimum of Months 0.114555E+09 0.505333E+09 0.689877E+09 0.00 0.689877E+09 0.00 0.00
Maximum of Months 0.340685E+10 0.501726E+10 0.178928E+10 0.118135E+09 0.167115E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.770966E+09 0.299152E+10 0.109261E+10 0.492825E+09 0.599790E+09 0.00 0.00
February 0.121709E+10 0.222722E+10 0.124414E+10 0.668469E+09 0.575674E+09 0.00 0.00
March 0.198568E+10 0.159174E+10 0.173298E+10 0.788905E+09 0.944080E+09 0.00 0.00
April 0.281999E+10 0.124778E+10 0.202802E+10 0.924727E+09 0.110330E+10 0.00 0.00
May 0.354802E+10 0.874360E+09 0.230115E+10 0.973125E+09 0.132803E+10 0.00 0.00
June 0.405806E+10 0.540145E+09 0.230561E+10 0.966340E+09 0.133927E+10 0.00 0.00
July 0.422875E+10 0.404469E+09 0.232300E+10 0.976623E+09 0.134638E+10 0.00 0.00
August 0.393665E+10 0.334989E+09 0.212478E+10 0.842976E+09 0.128180E+10 0.00 0.00
September 0.271554E+10 0.708018E+09 0.168995E+10 0.748772E+09 0.941176E+09 0.00 0.00
October 0.192479E+10 0.148041E+10 0.148972E+10 0.775140E+09 0.714585E+09 0.00 0.00
November 0.115764E+10 0.188550E+10 0.115263E+10 0.521905E+09 0.630721E+09 0.00 0.00
December 0.787386E+09 0.244935E+10 0.103168E+10 0.470278E+09 0.561398E+09 0.00 0.00
               
Annual Sum or Average 0.291506E+11 0.167355E+11 0.205163E+11 0.915008E+10 0.113662E+11 0.00 0.00
Minimum of Months 0.770966E+09 0.334989E+09 0.103168E+10 0.470278E+09 0.561398E+09 0.00 0.00
Maximum of Months 0.422875E+10 0.299152E+10 0.232300E+10 0.976623E+09 0.134638E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.454168E+10 0.423050E+10 0.399118E+10 0.278264E+10 0.120854E+10 0.00 0.00
February 0.417655E+10 0.329259E+10 0.336461E+10 0.225539E+10 0.110922E+10 0.00 0.00
March 0.451697E+10 0.254395E+10 0.335013E+10 0.174589E+10 0.160424E+10 0.00 0.00
April 0.364613E+10 0.205927E+10 0.242809E+10 0.790395E+09 0.163769E+10 0.00 0.00
May 0.322222E+10 0.141763E+10 0.202719E+10 0.235614E+09 0.179158E+10 0.00 0.00
June 0.344732E+10 0.867672E+09 0.181389E+10 0.100936E+09 0.171295E+10 0.00 0.00
July 0.378755E+10 0.632784E+09 0.189493E+10 0.141297E+09 0.175364E+10 0.00 0.00
August 0.459579E+10 0.530357E+09 0.226241E+10 0.422627E+09 0.183979E+10 0.00 0.00
September 0.414851E+10 0.113665E+10 0.240784E+10 0.895590E+09 0.151225E+10 0.00 0.00
October 0.534658E+10 0.233978E+10 0.360703E+10 0.233664E+10 0.127039E+10 0.00 0.00
November 0.499986E+10 0.291424E+10 0.375534E+10 0.249198E+10 0.126336E+10 0.00 0.00
December 0.477521E+10 0.361440E+10 0.393420E+10 0.276774E+10 0.116646E+10 0.00 0.00
               
Annual Sum or Average 0.512044E+11 0.255798E+11 0.348369E+11 0.169667E+11 0.178701E+11 0.00 0.00
Minimum of Months 0.322222E+10 0.530357E+09 0.181389E+10 0.100936E+09 0.110922E+10 0.00 0.00
Maximum of Months 0.534658E+10 0.423050E+10 0.399118E+10 0.278264E+10 0.183979E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.899932E+09 0.311325E+10 0.112227E+10 0.520587E+09 0.601681E+09 0.00 0.00
February 0.121236E+10 0.236211E+10 0.116368E+10 0.544089E+09 0.619587E+09 0.00 0.00
March 0.238431E+10 0.172190E+10 0.189896E+10 0.917621E+09 0.981340E+09 0.00 0.00
April 0.297716E+10 0.136220E+10 0.206738E+10 0.946027E+09 0.112136E+10 0.00 0.00
May 0.338675E+10 0.954316E+09 0.214704E+10 0.813430E+09 0.133361E+10 0.00 0.00
June 0.389769E+10 0.597836E+09 0.218506E+10 0.840583E+09 0.134448E+10 0.00 0.00
July 0.393777E+10 0.436607E+09 0.212971E+10 0.789625E+09 0.134009E+10 0.00 0.00
August 0.389757E+10 0.369948E+09 0.208681E+10 0.780386E+09 0.130643E+10 0.00 0.00
September 0.267428E+10 0.754764E+09 0.164534E+10 0.685356E+09 0.959983E+09 0.00 0.00
October 0.208582E+10 0.160497E+10 0.151466E+10 0.786276E+09 0.728386E+09 0.00 0.00
November 0.133997E+10 0.205761E+10 0.116982E+10 0.525073E+09 0.644742E+09 0.00 0.00
December 0.869349E+09 0.262376E+10 0.997260E+09 0.436203E+09 0.561057E+09 0.00 0.00
               
Annual Sum or Average 0.295630E+11 0.179593E+11 0.201280E+11 0.858525E+10 0.115427E+11 0.00 0.00
Minimum of Months 0.869349E+09 0.369948E+09 0.997260E+09 0.436203E+09 0.561057E+09 0.00 0.00
Maximum of Months 0.393777E+10 0.311325E+10 0.218506E+10 0.946027E+09 0.134448E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.461605E+10 -0.436950E+10 0.00 0.00 744.00 0.00 -246552352.4 60.05 0.00 0.00
February 0.419810E+10 -0.397953E+10 0.00 0.00 672.00 0.00 -218567806.6 60.05 0.00 0.00
March 0.479049E+10 -0.455481E+10 0.00 0.00 744.00 0.00 -235686662.0 60.05 0.00 0.00
April 0.406922E+10 -0.384332E+10 0.00 0.00 720.00 0.00 -225901687.6 60.05 0.00 0.00
May 0.403275E+10 -0.380052E+10 0.00 0.00 744.00 0.00 -232232637.2 60.05 0.00 0.00
June 0.370662E+10 -0.348189E+10 0.00 0.00 720.00 0.00 -224724851.1 60.05 0.00 0.00
July 0.334723E+10 -0.311564E+10 0.00 0.00 744.00 0.00 -231598649.6 60.05 0.00 0.00
August 0.366740E+10 -0.343530E+10 0.00 0.00 744.00 0.00 -232102115.3 60.05 0.00 0.00
September 0.346332E+10 -0.323908E+10 0.00 0.00 720.00 0.00 -224231818.3 60.05 0.00 0.00
October 0.384573E+10 -0.361240E+10 0.00 0.00 744.00 0.00 -233329910.8 60.05 0.00 0.00
November 0.408750E+10 -0.385962E+10 0.00 0.00 720.00 0.00 -227884794.4 60.05 0.00 0.00
December 0.432682E+10 -0.408649E+10 0.00 0.00 744.00 0.00 -240325207.7 60.05 0.00 0.00
                     
Annual Sum or Average 0.481512E+11 -0.453781E+11 0.00 0.00 8760.00 0.00 -0.277314E+10 60.05 0.00 0.00
Minimum of Months 0.334723E+10 -0.455481E+10 0.00 0.00 672.00 0.00 -246552352.4 60.05 0.00 0.00
Maximum of Months 0.479049E+10 -0.311564E+10 0.00 0.00 744.00 0.00 -218567806.6 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5944.13 33.56 265.83 271.50 1657.27 25.59 178.50 250.33
February 263.00 0.52 0.48 01-FEB-13:39 6962.61 33.59 230.83 246.83 1109.82 19.25 74.67 210.83
March 351.67 0.52 0.48 01-MAR-08:50 1639.75 18.12 6.83 317.83 961.50 20.22 124.00 283.00
April 369.33 0.53 0.48 01-APR-09:39 1350.13 17.76 0.00 324.17 773.30 19.91 104.50 280.33
May 407.00 0.53 0.48 01-MAY-07:49 1220.07 17.94 0.00 358.50 683.84 20.09 89.67 310.67
June 411.67 0.53 0.48 01-JUN-07:19 1133.53 17.68 0.00 358.67 641.54 19.85 91.67 311.00
July 411.00 0.53 0.48 01-JUL-07:49 1195.26 17.85 0.00 362.50 668.51 19.99 118.50 312.83
August 390.50 0.52 0.48 01-AUG-07:30 1461.06 18.48 0.00 349.33 801.51 20.60 174.83 311.50
September 298.50 0.53 0.48 01-SEP-07:40 1564.17 18.59 6.50 307.83 880.51 20.47 122.67 268.33
October 293.50 0.51 0.48 01-OCT-10:39 2832.02 23.85 119.33 291.83 1070.85 19.63 83.17 255.17
November 299.00 0.52 0.48 01-NOV-08:30 5850.38 34.50 285.50 272.83 1203.10 24.25 167.17 252.83
December 285.17 0.50 0.48 01-DEC-07:00 5602.08 34.35 269.83 267.67 1598.52 26.54 179.50 245.17
                         
Annual Sum or Average 4071.00 0.52     2776.74 22.92 1184.67 3729.50 962.96 21.19 1508.83 3292.00
Minimum of Months 263.00 0.50 0.48   1133.53 17.68 0.00 246.83 641.54 19.25 74.67 210.83
Maximum of Months 411.67 0.53 0.48   6962.61 34.50 285.50 362.50 1657.27 26.54 179.50 312.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-09:09 1403.14 19.13 71.83 240.83 715.25 19.99 55.33 179.00
February 263.00 0.55 0.48 01-FEB-13:39 1863.36 18.94 60.17 222.67 1030.30 21.08 50.00 177.17
March 351.67 0.53 0.48 01-MAR-08:39 2242.56 20.56 105.50 309.83 881.09 20.10 47.50 267.33
April 369.33 0.52 0.48 01-APR-08:09 2159.60 19.96 93.33 325.00 1163.95 21.19 67.17 287.67
May 407.00 0.52 0.48 01-MAY-07:10 2462.38 20.32 108.50 366.67 1018.16 20.21 50.17 327.67
June 411.67 0.52 0.48 01-JUN-06:30 2486.06 20.25 110.67 368.50 1042.13 20.91 64.00 332.50
July 411.00 0.52 0.48 01-JUL-05:00 2460.73 20.28 105.50 371.83 1042.79 20.29 51.83 330.50
August 390.50 0.52 0.48 01-AUG-06:40 2255.62 20.63 102.17 350.83 1190.30 21.92 73.50 313.33
September 298.50 0.53 0.48 01-SEP-07:10 2082.99 19.39 67.33 303.17 1122.96 21.64 55.33 259.33
October 293.50 0.54 0.48 01-OCT-08:20 2490.79 20.88 90.83 267.17 929.04 19.93 43.83 214.83
November 299.00 0.55 0.48 01-NOV-08:20 1701.57 21.17 97.00 246.83 918.85 22.00 75.50 200.83
December 285.17 0.54 0.48 01-DEC-07:49 1440.43 19.73 73.33 236.67 771.34 21.42 60.17 177.50
                         
Annual Sum or Average 4071.00 0.53     2130.75 20.15 1086.17 3610.00 996.80 20.87 694.33 3067.67
Minimum of Months 263.00 0.52 0.48   1403.14 18.94 60.17 222.67 715.25 19.93 43.83 177.17
Maximum of Months 411.67 0.55 0.48   2490.79 21.17 110.67 371.83 1190.30 22.00 75.50 332.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.59 0.48 01-JAN-11:20 500.43 14.35 0.00 211.33 302.57 16.75 0.00 89.17
February 263.00 0.59 0.48 01-FEB-13:50 531.48 14.55 0.00 190.50 330.34 16.90 0.00 111.67
March 351.67 0.54 0.48 01-MAR-09:30 678.09 16.37 0.00 299.67 413.74 18.58 0.00 226.17
April 369.33 0.52 0.48 01-APR-10:30 809.95 17.28 0.00 328.17 485.58 19.39 0.67 271.17
May 407.00 0.51 0.48 01-MAY-07:40 1012.67 20.33 51.83 382.67 584.27 20.48 66.67 342.50
June 411.67 0.50 0.48 01-JUN-06:49 1101.66 21.05 66.83 385.83 648.41 23.06 178.00 363.83
July 411.00 0.51 0.48 01-JUL-06:10 1110.01 20.48 53.33 384.83 617.52 21.45 145.83 348.83
August 390.50 0.51 0.48 01-AUG-07:10 990.02 18.23 0.00 359.33 578.27 20.31 54.67 324.83
September 298.50 0.53 0.48 01-SEP-07:49 752.92 17.08 0.00 302.50 456.60 19.19 0.00 219.83
October 293.50 0.58 0.48 01-OCT-10:50 556.20 15.08 0.00 237.00 355.94 17.47 0.00 143.83
November 299.00 0.58 0.48 01-NOV-09:00 517.80 14.66 0.00 224.67 315.06 17.00 0.00 121.50
December 285.17 0.59 0.48 01-DEC-10:20 483.52 14.43 0.00 203.50 293.36 16.87 0.00 82.83
                         
Annual Sum or Average 4071.00 0.54     789.00 17.35 172.00 3510.00 467.36 19.24 445.83 2646.17
Minimum of Months 263.00 0.50 0.48   483.52 14.35 0.00 190.50 293.36 16.75 0.00 82.83
Maximum of Months 411.67 0.59 0.48   1110.01 21.05 66.83 385.83 648.41 23.06 178.00 363.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.54 0.48 01-JAN-10:00 1724.54 21.14 89.83 243.83 955.65 21.84 68.00 191.33
February 263.00 0.56 0.48 01-FEB-13:39 1648.22 18.89 64.00 214.33 856.95 19.72 40.33 165.33
March 351.67 0.53 0.48 01-MAR-11:50 2222.20 20.89 98.17 309.33 1182.08 21.80 72.00 266.50
April 369.33 0.52 0.48 01-APR-10:39 2368.78 18.68 78.67 330.67 1304.67 20.04 51.83 288.67
May 407.00 0.52 0.48 01-MAY-08:30 2368.37 17.04 50.83 364.67 1008.52 18.03 0.00 325.83
June 411.67 0.52 0.48 01-JUN-07:49 2490.05 14.72 1.67 367.50 1066.09 17.98 0.00 330.83
July 411.00 0.52 0.48 01-JUL-08:09 2471.35 17.03 52.17 367.50 1043.28 18.02 0.00 328.00
August 390.50 0.52 0.48 01-AUG-07:00 2423.28 19.52 89.00 352.67 1057.45 18.72 7.67 319.17
September 298.50 0.53 0.48 01-SEP-08:00 2175.17 21.47 90.83 305.00 1149.50 22.24 62.67 256.67
October 293.50 0.54 0.48 01-OCT-10:50 2351.32 20.91 92.67 262.50 902.70 19.99 42.83 210.33
November 299.00 0.55 0.48 01-NOV-09:00 1596.56 19.48 80.83 248.50 857.86 21.75 68.67 200.00
December 285.17 0.54 0.48 01-DEC-10:09 1393.57 19.37 74.17 236.50 757.14 21.35 63.33 177.83
                         
Annual Sum or Average 4071.00 0.53     2150.89 18.88 862.83 3603.00 1024.87 19.93 477.33 3060.50
Minimum of Months 263.00 0.52 0.48   1393.57 14.72 1.67 214.33 757.14 17.98 0.00 165.33
Maximum of Months 411.67 0.56 0.48   2490.05 21.47 98.17 367.50 1304.67 22.24 72.00 330.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5823.08 33.12 258.17 269.83 1561.52 23.29 103.33 249.00
February 263.00 0.52 0.48 01-FEB-13:39 6853.73 33.22 229.67 245.83 1060.06 18.04 25.83 214.17
March 351.67 0.52 0.48 01-MAR-08:00 1553.16 14.23 6.67 314.67 896.80 17.63 0.50 278.83
April 369.33 0.53 0.48 01-APR-09:50 1289.89 14.01 0.00 321.83 731.87 17.52 0.00 277.33
May 407.00 0.53 0.48 01-MAY-07:49 1172.51 14.26 0.00 355.83 654.37 17.73 0.00 307.83
June 411.67 0.53 0.48 01-JUN-07:19 1091.09 14.07 0.00 356.33 616.22 17.53 0.00 306.83
July 411.00 0.53 0.48 01-JUL-07:49 1149.36 14.24 0.00 359.33 640.70 17.67 0.00 308.33
August 390.50 0.52 0.48 01-AUG-07:40 1400.63 14.86 0.00 347.33 762.74 18.28 0.00 307.17
September 298.50 0.53 0.48 01-SEP-07:49 1490.14 14.98 6.50 305.00 828.73 18.12 0.00 265.50
October 293.50 0.52 0.48 01-OCT-10:39 2727.91 21.24 117.33 290.33 988.09 16.85 2.17 251.33
November 299.00 0.52 0.48 01-NOV-08:30 5736.91 34.09 281.17 271.67 1115.61 21.76 82.17 249.67
December 285.17 0.51 0.48 01-DEC-07:00 5429.53 32.30 249.50 263.83 1501.05 24.34 116.17 243.00
                         
Annual Sum or Average 4071.00 0.52     2695.29 20.12 1149.00 3701.83 908.51 18.87 330.17 3259.00
Minimum of Months 263.00 0.51 0.48   1091.09 14.01 0.00 245.83 616.22 16.85 0.00 214.17
Maximum of Months 411.67 0.53 0.48   6853.73 34.09 281.17 359.33 1561.52 24.34 116.17 308.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-09:20 1363.77 18.62 71.50 239.00 684.67 19.74 48.67 172.50
February 263.00 0.55 0.48 01-FEB-13:39 1813.50 18.44 60.17 219.33 989.09 20.87 48.50 174.00
March 351.67 0.53 0.48 01-MAR-08:39 2191.30 20.09 105.33 308.00 839.46 19.89 47.33 262.83
April 369.33 0.53 0.48 01-APR-08:09 2098.61 19.49 93.00 322.67 1115.83 21.00 67.17 283.50
May 407.00 0.52 0.48 01-MAY-07:19 2391.36 19.87 108.33 364.00 967.49 20.04 50.17 323.50
June 411.67 0.52 0.48 01-JUN-06:30 2421.72 19.80 110.33 366.00 992.13 20.75 64.00 329.00
July 411.00 0.52 0.48 01-JUL-05:00 2392.59 19.83 105.33 369.00 991.41 20.11 51.83 328.17
August 390.50 0.52 0.48 01-AUG-06:40 2184.22 20.17 102.17 349.17 1140.60 21.75 73.50 309.67
September 298.50 0.53 0.48 01-SEP-07:10 2023.73 18.89 67.33 301.33 1074.78 21.45 55.33 253.33
October 293.50 0.54 0.48 01-OCT-10:39 2436.85 20.40 90.50 265.00 884.47 19.72 42.67 210.00
November 299.00 0.55 0.48 01-NOV-08:20 1659.27 20.71 97.00 244.33 885.48 21.78 72.83 195.83
December 285.17 0.55 0.48 01-DEC-07:49 1400.26 19.22 73.00 234.17 739.07 21.18 57.50 173.33
                         
Annual Sum or Average 4071.00 0.53     2073.27 19.67 1084.00 3582.00 952.46 20.68 679.50 3015.67
Minimum of Months 263.00 0.52 0.48   1363.77 18.44 60.17 219.33 684.67 19.72 42.67 172.50
Maximum of Months 411.67 0.55 0.48   2436.85 20.71 110.33 369.00 1140.60 21.78 73.50 329.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.60 0.48 01-JAN-11:30 482.96 10.47 0.00 206.50 293.15 14.20 0.00 79.67
February 263.00 0.60 0.48 01-FEB-13:00 513.49 10.78 0.00 185.33 320.90 14.47 0.00 106.83
March 351.67 0.54 0.48 01-MAR-12:20 654.86 12.86 0.00 296.67 401.31 16.43 0.00 220.17
April 369.33 0.53 0.48 01-APR-10:39 782.39 13.81 0.00 325.67 470.58 17.33 0.00 266.50
May 407.00 0.51 0.48 01-MAY-07:49 976.23 17.28 51.83 380.33 573.88 20.45 52.50 348.50
June 411.67 0.50 0.48 01-JUN-06:49 1061.26 18.08 65.67 384.67 624.76 21.23 68.17 361.00
July 411.00 0.51 0.48 01-JUL-06:19 1065.85 16.16 27.33 383.17 604.40 20.59 54.00 350.83
August 390.50 0.51 0.48 01-AUG-07:10 953.90 14.80 0.00 357.83 557.88 18.26 0.00 320.67
September 298.50 0.54 0.48 01-SEP-07:00 725.98 13.77 0.00 299.67 441.99 17.24 0.00 210.33
October 293.50 0.58 0.48 01-OCT-10:50 537.67 11.52 0.00 231.00 346.46 15.26 0.00 136.67
November 299.00 0.59 0.48 01-NOV-10:09 499.26 10.90 0.00 219.33 305.08 14.56 0.00 110.00
December 285.17 0.60 0.48 01-DEC-10:20 465.99 10.51 0.00 198.00 283.90 14.30 0.00 70.17
                         
Annual Sum or Average 4071.00 0.54     760.54 13.79 144.83 3468.17 453.78 17.40 174.67 2581.33
Minimum of Months 263.00 0.50 0.48   465.99 10.47 0.00 185.33 283.90 14.20 0.00 70.17
Maximum of Months 411.67 0.60 0.48   1065.85 18.08 65.67 384.67 624.76 21.23 68.17 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-10:00 1682.62 20.74 89.33 240.83 922.67 21.73 68.00 186.83
February 263.00 0.56 0.48 01-FEB-13:39 1597.52 18.47 64.00 211.67 817.05 19.59 40.00 162.83
March 351.67 0.53 0.48 01-MAR-11:50 2096.20 18.82 77.50 306.83 1133.94 21.68 72.17 263.17
April 369.33 0.52 0.48 01-APR-10:39 2307.77 18.21 78.50 327.83 1256.61 19.87 51.83 285.83
May 407.00 0.52 0.48 01-MAY-08:39 2300.27 16.53 50.83 361.83 961.70 17.84 0.00 322.83
June 411.67 0.52 0.48 01-JUN-07:00 2402.94 14.17 1.67 364.17 1018.49 17.79 0.00 328.17
July 411.00 0.53 0.48 01-JUL-08:20 2386.26 16.52 52.00 365.33 995.72 17.82 0.00 324.50
August 390.50 0.52 0.48 01-AUG-08:09 2349.84 18.89 86.50 351.17 1000.66 18.55 7.83 314.00
September 298.50 0.53 0.48 01-SEP-08:00 2071.15 19.40 75.50 301.17 1102.03 22.11 62.67 252.50
October 293.50 0.54 0.48 01-OCT-10:50 2298.89 20.49 92.50 260.67 859.80 19.86 42.83 206.50
November 299.00 0.55 0.48 01-NOV-09:00 1552.04 19.05 80.83 245.83 823.42 21.64 68.17 196.50
December 285.17 0.55 0.48 01-DEC-10:09 1354.65 18.95 73.83 233.83 726.36 21.24 63.17 173.83
                         
Annual Sum or Average 4071.00 0.53     2079.55 18.14 823.00 3571.17 980.42 19.78 476.67 3017.50
Minimum of Months 263.00 0.52 0.48   1354.65 14.17 1.67 211.67 726.36 17.79 0.00 162.83
Maximum of Months 411.67 0.56 0.48   2402.94 20.74 92.50 365.33 1256.61 22.11 72.17 328.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.51 0.48 01-JAN-09:20 5823.03 33.12 258.17 269.83 1561.45 23.29 103.33 249.00
February 263.00 0.52 0.48 01-FEB-13:39 6853.66 33.22 229.67 245.83 1059.99 18.05 25.83 214.17
March 351.67 0.52 0.48 01-MAR-08:00 1553.07 14.23 6.67 314.67 896.74 17.63 0.50 278.67
April 369.33 0.53 0.48 01-APR-09:50 1289.81 14.01 0.00 321.83 731.82 17.52 0.00 277.33
May 407.00 0.53 0.48 01-MAY-07:49 1172.44 14.26 0.00 355.83 654.32 17.73 0.00 307.83
June 411.67 0.53 0.48 01-JUN-07:19 1091.03 14.07 0.00 356.33 616.17 17.53 0.00 306.83
July 411.00 0.53 0.48 01-JUL-07:49 1149.30 14.24 0.00 359.33 640.65 17.68 0.00 308.33
August 390.50 0.52 0.48 01-AUG-07:40 1400.54 14.86 0.00 347.33 762.68 18.28 0.00 307.17
September 298.50 0.53 0.48 01-SEP-07:49 1490.05 14.99 6.50 305.00 828.67 18.12 0.00 265.50
October 293.50 0.52 0.48 01-OCT-10:39 2727.84 21.24 117.33 290.33 988.03 16.85 2.17 251.33
November 299.00 0.52 0.48 01-NOV-08:30 5736.86 34.09 281.17 271.67 1115.53 21.76 82.17 249.67
December 285.17 0.51 0.48 01-DEC-07:00 5429.50 32.30 249.50 263.83 1500.98 24.34 116.17 243.00
                         
Annual Sum or Average 4071.00 0.52     2695.22 20.12 1149.00 3701.83 908.45 18.87 330.17 3258.83
Minimum of Months 263.00 0.51 0.48   1091.03 14.01 0.00 245.83 616.17 16.85 0.00 214.17
Maximum of Months 411.67 0.53 0.48   6853.66 34.09 281.17 359.33 1561.45 24.34 116.17 308.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-09:20 1363.74 18.63 71.50 239.00 684.64 19.74 48.67 172.50
February 263.00 0.55 0.48 01-FEB-13:39 1813.48 18.44 60.17 219.33 989.06 20.87 48.50 174.00
March 351.67 0.53 0.48 01-MAR-08:39 2191.27 20.09 105.33 308.00 839.42 19.89 47.33 262.83
April 369.33 0.53 0.48 01-APR-08:09 2098.57 19.50 93.00 322.67 1115.78 21.00 67.17 283.50
May 407.00 0.52 0.48 01-MAY-07:19 2391.30 19.87 108.33 364.00 967.43 20.04 50.17 323.50
June 411.67 0.52 0.48 01-JUN-06:30 2421.66 19.80 110.33 366.00 992.07 20.75 64.00 329.00
July 411.00 0.52 0.48 01-JUL-05:00 2392.53 19.84 105.33 369.00 991.34 20.12 51.83 328.17
August 390.50 0.52 0.48 01-AUG-06:40 2184.16 20.18 102.17 349.17 1140.53 21.75 73.50 309.67
September 298.50 0.53 0.48 01-SEP-07:10 2023.69 18.90 67.33 301.33 1074.73 21.45 55.33 253.33
October 293.50 0.54 0.48 01-OCT-10:39 2436.83 20.40 90.50 265.00 884.43 19.72 42.67 210.00
November 299.00 0.55 0.48 01-NOV-08:20 1659.24 20.71 97.00 244.33 885.44 21.78 72.83 195.83
December 285.17 0.55 0.48 01-DEC-07:49 1400.23 19.22 73.00 234.17 739.04 21.18 57.50 173.17
                         
Annual Sum or Average 4071.00 0.53     2073.23 19.67 1084.00 3582.00 952.41 20.68 679.50 3015.50
Minimum of Months 263.00 0.52 0.48   1363.74 18.44 60.17 219.33 684.64 19.72 42.67 172.50
Maximum of Months 411.67 0.55 0.48   2436.83 20.71 110.33 369.00 1140.53 21.78 73.50 329.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.60 0.48 01-JAN-11:30 482.94 10.47 0.00 206.50 293.13 14.20 0.00 79.67
February 263.00 0.60 0.48 01-FEB-13:00 513.48 10.78 0.00 185.33 320.88 14.48 0.00 106.83
March 351.67 0.54 0.48 01-MAR-12:20 654.84 12.86 0.00 296.67 401.28 16.43 0.00 220.17
April 369.33 0.53 0.48 01-APR-10:39 782.36 13.81 0.00 325.67 470.55 17.33 0.00 266.50
May 407.00 0.51 0.48 01-MAY-07:49 976.19 17.28 51.83 380.33 573.84 20.45 52.50 348.50
June 411.67 0.50 0.48 01-JUN-06:49 1061.22 18.08 65.67 384.67 624.72 21.23 68.17 361.00
July 411.00 0.51 0.48 01-JUL-06:19 1065.80 16.16 27.33 383.17 604.36 20.59 54.00 350.83
August 390.50 0.51 0.48 01-AUG-07:10 953.87 14.80 0.00 357.83 557.84 18.26 0.00 320.67
September 298.50 0.54 0.48 01-SEP-07:00 725.96 13.78 0.00 299.67 441.96 17.24 0.00 210.33
October 293.50 0.58 0.48 01-OCT-10:50 537.66 11.52 0.00 231.00 346.44 15.26 0.00 136.67
November 299.00 0.59 0.48 01-NOV-10:09 499.24 10.90 0.00 219.33 305.06 14.56 0.00 110.00
December 285.17 0.60 0.48 01-DEC-10:20 465.98 10.51 0.00 198.00 283.88 14.30 0.00 70.17
                         
Annual Sum or Average 4071.00 0.54     760.51 13.79 144.83 3468.17 453.75 17.40 174.67 2581.33
Minimum of Months 263.00 0.50 0.48   465.98 10.47 0.00 185.33 283.88 14.20 0.00 70.17
Maximum of Months 411.67 0.60 0.48   1065.80 18.08 65.67 384.67 624.72 21.23 68.17 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-10:00 1682.59 20.74 89.33 240.83 922.63 21.73 68.00 186.83
February 263.00 0.56 0.48 01-FEB-13:39 1597.50 18.47 64.00 211.67 817.01 19.59 40.00 162.83
March 351.67 0.53 0.48 01-MAR-11:50 2096.16 18.82 77.50 306.83 1133.89 21.68 72.17 263.17
April 369.33 0.52 0.48 01-APR-10:39 2307.72 18.21 78.50 327.83 1256.56 19.87 51.83 285.83
May 407.00 0.52 0.48 01-MAY-08:39 2300.21 16.54 50.83 361.83 961.64 17.84 0.00 322.83
June 411.67 0.52 0.48 01-JUN-07:00 2402.88 14.17 1.67 364.17 1018.43 17.79 0.00 328.17
July 411.00 0.53 0.48 01-JUL-08:20 2386.20 16.52 52.00 365.33 995.66 17.82 0.00 324.50
August 390.50 0.52 0.48 01-AUG-08:09 2349.78 18.89 86.50 351.17 1000.60 18.55 7.83 314.00
September 298.50 0.53 0.48 01-SEP-08:00 2071.10 19.40 75.50 301.17 1101.97 22.11 62.67 252.50
October 293.50 0.54 0.48 01-OCT-10:50 2298.87 20.49 92.50 260.67 859.76 19.86 42.83 206.50
November 299.00 0.55 0.48 01-NOV-09:00 1552.01 19.05 80.83 245.83 823.38 21.64 68.17 196.50
December 285.17 0.55 0.48 01-DEC-10:09 1354.63 18.95 73.83 233.83 726.32 21.24 63.17 173.83
                         
Annual Sum or Average 4071.00 0.53     2079.50 18.14 823.00 3571.17 980.37 19.78 476.67 3017.50
Minimum of Months 263.00 0.52 0.48   1354.63 14.17 1.67 211.67 726.32 17.79 0.00 162.83
Maximum of Months 411.67 0.56 0.48   2402.88 20.74 92.50 365.33 1256.56 22.11 72.17 328.17



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.267378E+10 10513.89 14-JAN-07:08 0.00 0.00 0.00 0.00 0.00
February 0.119636E+10 12434.58 03-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 9388735.56 1404.24 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 4130950.64 1395.05 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1692628.51 540.77 26-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.106870E+09 6217.33 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.401187E+09 9441.07 18-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.439341E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.267378E+10 12434.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 18296197.28 24785.76 02-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 18296197.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18296197.28 24785.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.447064E+10 11132.34 19-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.292560E+10 11110.51 17-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.117007E+10 11089.38 24-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.644478E+09 11065.90 05-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.170531E+09 11056.38 11-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 25625123.02 8735.16 08-JUN-06:07 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 23737487.74 4934.17 29-SEP-06:08 0.00 0.00 0.00 0.00 0.00
October 0.540364E+09 11144.66 04-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.107007E+10 11084.07 06-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.188494E+10 11083.40 07-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129261E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.447064E+10 11144.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185737E+10 8150.01 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.102834E+10 8150.01 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.123223E+09 7927.55 18-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 19246109.00 8150.01 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 11414007.98 5452.90 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 67861852.56 8150.01 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.594573E+09 8150.01 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.370202E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185737E+10 8150.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.333704E+10 9474.90 19-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.195641E+10 9479.42 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.346892E+09 9441.58 24-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 78224836.24 9440.25 08-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 11473899.21 7877.57 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.200631E+09 9428.12 24-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.125607E+10 9440.30 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.718674E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.333704E+10 9479.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.197876E+10 8236.54 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.114564E+10 8236.54 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.161777E+09 7764.59 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 28135993.77 8236.54 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 10827612.36 4578.40 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.108830E+09 8236.54 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.747320E+09 8236.54 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.418130E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.197876E+10 8236.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.318480E+10 11508.07 14-JAN-07:08 0.00 0.00 0.00 0.00 0.00
February 0.149789E+10 13359.15 03-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 27673371.89 2266.78 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 19744842.96 2928.09 06-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 12537534.70 2411.37 26-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.192773E+09 7847.12 22-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.618842E+09 10562.22 18-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.555426E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.318480E+10 13359.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.243530E+10 24248.82 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.110239E+10 24248.82 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 23871861.42 14238.79 22-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.635726E+09 24248.82 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.419729E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.243530E+10 24248.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.184665E+10 12021.48 02-JAN-06:23 0.00 0.00 0.00 0.00 0.00
February 0.100062E+10 11957.66 08-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 98173930.55 11902.99 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 21649917.09 11853.49 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 44669752.34 11871.08 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.169701E+09 11867.29 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.733398E+09 11936.43 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.391486E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.184665E+10 12021.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.208874E+10 8364.90 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.113336E+10 8364.90 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.126130E+09 7891.98 18-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 16891260.11 8364.90 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 95177370.30 7916.19 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.275884E+09 8364.90 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.103102E+10 8364.90 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.476720E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.208874E+10 8364.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.319077E+10 10187.05 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.170938E+10 10165.48 07-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.175931E+09 10095.95 22-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 27823117.20 10041.90 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 66732171.45 10133.09 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.420062E+09 10120.94 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.158894E+10 10152.07 26-DEC-06:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.717964E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.319077E+10 10187.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218140E+10 8449.74 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.122262E+10 8449.74 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.175814E+09 7773.84 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 29319327.04 8449.74 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 91821814.59 7780.27 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.367331E+09 8449.74 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.119242E+10 8449.74 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.526072E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.218140E+10 8449.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.327926E+10 13608.13 27-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.158542E+10 15981.62 03-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 86129513.47 3734.80 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 49591011.19 4989.06 06-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 24354287.62 4208.21 26-OCT-06:20 0.00 0.00 0.00 0.00 0.00
November 0.298214E+09 9547.57 22-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.768820E+09 11272.87 18-DEC-07:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.609180E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.327926E+10 15981.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.664423E+10 35333.63 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.351062E+10 35333.63 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.278172E+09 35333.63 20-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 23639670.48 29380.39 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.176241E+09 35333.63 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.872097E+09 35333.63 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.376596E+10 35333.63 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152710E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.664423E+10 35333.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.332239E+10 13528.40 02-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.200477E+10 13538.22 08-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.400616E+09 13443.59 22-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.121686E+09 13373.65 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 4075307.11 4221.03 11-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 385997.02 667.35 29-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.264909E+09 13489.21 30-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.661830E+09 13461.21 21-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.171249E+10 13535.85 07-DEC-06:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.849315E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.332239E+10 13538.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.316465E+10 10560.27 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.183897E+10 10560.27 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.364472E+09 10560.27 06-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 75029373.90 10560.27 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 1010033.63 1859.13 11-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1940894.76 2770.62 29-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.293825E+09 10560.27 26-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.725171E+09 10560.27 08-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.181632E+10 10560.27 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.828139E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.316465E+10 10560.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.513511E+10 11711.43 02-JAN-06:37 0.00 0.00 0.00 0.00 0.00
February 0.303367E+10 11693.62 08-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.603245E+09 11656.60 24-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.145184E+09 11626.43 26-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 2018781.80 3102.98 11-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 453198.46 800.04 29-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.383405E+09 11668.33 25-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.121142E+10 11683.55 24-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.302504E+10 11696.67 12-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.135395E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.513511E+10 11711.43   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.348059E+10 10652.81 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.214208E+10 10652.81 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.544964E+09 10652.81 18-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.138934E+09 10652.81 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 7363497.29 3942.04 11-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 3217940.17 3722.05 29-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.383174E+09 10652.81 26-OCT-05:11 0.00 0.00 0.00 0.00 0.00
November 0.994404E+09 10652.81 08-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.219352E+10 10652.81 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.988824E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.348059E+10 10652.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.199769E+10 0.123622E+10 21197.72 19-JAN-20:00 11767.82 0.00
February 0.00 0.00 0.496106E+10 0.407509E+10 31798.74 28-FEB-15:10 31798.74 0.00
March 0.00 0.00 0.150129E+11 0.117247E+11 49041.03 30-MAR-15:10 49041.03 0.00
April 0.00 0.00 0.256881E+11 0.210057E+11 51582.72 17-APR-14:00 51582.72 0.00
May 0.00 0.00 0.489629E+11 0.372809E+11 69929.83 30-MAY-15:00 56371.92 0.00
June 0.00 0.00 0.735298E+11 0.555088E+11 80073.10 28-JUN-12:05 55192.61 0.00
July 0.00 0.00 0.845191E+11 0.606759E+11 89213.71 07-JUL-12:03 61213.50 0.00
August 0.00 0.00 0.964149E+11 0.676683E+11 87345.63 17-AUG-12:03 59799.51 0.00
September 0.00 0.00 0.618762E+11 0.458525E+11 85699.53 07-SEP-16:00 64537.23 0.00
October 0.00 0.00 0.275370E+11 0.205354E+11 68659.64 10-OCT-16:00 56896.60 0.00
November 0.00 0.00 0.109438E+11 0.833913E+10 34671.72 02-NOV-14:10 28473.82 0.00
December 0.00 0.00 0.396239E+10 0.267585E+10 31673.59 12-DEC-14:00 24015.86 0.00
                 
Annual Sum or Average 0.00 0.00 0.455406E+12 0.336579E+12       0.00
Minimum of Months 0.00 0.00 0.199769E+10 0.123622E+10 21197.72   11767.82 0.00
Maximum of Months 0.00 0.00 0.964149E+11 0.676683E+11 89213.71   64537.23 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.200835E+10 0.126820E+10 21910.88 19-JAN-16:00 12529.84 0.00
February 0.00 0.00 0.494226E+10 0.406288E+10 26376.06 28-FEB-15:30 26376.06 0.00
March 0.00 0.00 0.142263E+11 0.111161E+11 48459.00 30-MAR-15:10 48459.00 0.00
April 0.00 0.00 0.248281E+11 0.203465E+11 54335.24 17-APR-15:40 54335.24 0.00
May 0.00 0.00 0.462255E+11 0.352264E+11 65988.75 30-MAY-15:10 52104.38 0.00
June 0.00 0.00 0.679196E+11 0.505498E+11 74954.04 26-JUN-15:00 53650.99 0.00
July 0.00 0.00 0.774759E+11 0.544152E+11 79347.88 07-JUL-16:00 61163.05 0.00
August 0.00 0.00 0.865473E+11 0.589091E+11 79254.12 17-AUG-15:30 58986.44 0.00
September 0.00 0.00 0.532059E+11 0.381344E+11 77390.69 07-SEP-16:00 56680.79 0.00
October 0.00 0.00 0.234098E+11 0.169656E+11 59558.80 11-OCT-14:10 44813.39 0.00
November 0.00 0.00 0.973853E+10 0.725965E+10 29002.08 05-NOV-13:32 23082.93 0.00
December 0.00 0.00 0.369216E+10 0.248861E+10 28500.51 12-DEC-14:00 20953.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.414220E+12 0.300742E+12       0.00
Minimum of Months 0.00 0.00 0.200835E+10 0.126820E+10 21910.88   12529.84 0.00
Maximum of Months 0.00 0.00 0.865473E+11 0.589091E+11 79347.88   61163.05 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.208812E+10 0.129695E+10 22048.37 19-JAN-17:50 12103.09 0.00
February 0.00 0.00 0.511044E+10 0.416431E+10 30266.09 26-FEB-15:13 30266.09 0.00
March 0.00 0.00 0.149369E+11 0.116299E+11 54013.65 30-MAR-15:30 54013.65 0.00
April 0.00 0.00 0.266444E+11 0.218575E+11 60363.56 17-APR-15:40 60363.56 0.00
May 0.00 0.00 0.496304E+11 0.385225E+11 73968.09 30-MAY-15:10 60259.30 0.00
June 0.00 0.00 0.725011E+11 0.549795E+11 82578.01 26-JUN-15:00 61436.61 0.00
July 0.00 0.00 0.823764E+11 0.592145E+11 89545.63 07-JUL-16:00 71644.85 0.00
August 0.00 0.00 0.910052E+11 0.634009E+11 88719.73 01-AUG-15:00 71041.17 0.00
September 0.00 0.00 0.548678E+11 0.394961E+11 84820.85 06-SEP-14:00 63108.59 0.00
October 0.00 0.00 0.237805E+11 0.171467E+11 64295.94 11-OCT-14:00 49051.90 0.00
November 0.00 0.00 0.100445E+11 0.741647E+10 30240.05 02-NOV-13:40 21849.79 0.00
December 0.00 0.00 0.380672E+10 0.254801E+10 30441.40 12-DEC-14:00 22412.15 0.00
                 
Annual Sum or Average 0.00 0.00 0.436793E+12 0.321673E+12       0.00
Minimum of Months 0.00 0.00 0.208812E+10 0.129695E+10 22048.37   12103.09 0.00
Maximum of Months 0.00 0.00 0.910052E+11 0.634009E+11 89545.63   71644.85 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 1622.14 5938.05 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 1635.70 5938.22 01-FEB-12:13
March 0.00 0.00 01-MAR-00:10 1691.06 5844.24 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 1473.72 5521.84 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 1409.90 5140.54 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 1334.31 4713.01 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 1154.70 4387.43 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 1273.65 4371.12 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 1240.92 4647.28 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 1339.84 5078.24 31-OCT-11:10
November 0.00 0.00 01-NOV-00:10 1479.94 5492.35 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 1516.69 5797.92 29-DEC-13:00
             
Annual Sum or Average 0.00     1429.90    
Minimum of Months 0.00 0.00   1154.70 4371.12  
Maximum of Months 0.00 0.00   1691.06 5938.22  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.120402E+10 0.28 2336.43 09-JAN-07:01 0.76
February 0.115856E+10 0.29 1715.18 28-FEB-16:20 0.65
March 0.154119E+10 0.31 2462.13 30-MAR-16:00 0.78
April 0.164219E+10 0.31 2988.37 18-APR-06:03 0.87
May 0.220712E+10 0.35 3981.63 22-MAY-06:03 1.02
June 0.315088E+10 0.43 5589.71 26-JUN-06:03 1.25
July 0.349443E+10 0.43 6722.23 17-JUL-06:03 1.41
August 0.402600E+10 0.48 10333.02 14-AUG-04:02 1.85
September 0.290786E+10 0.40 5915.22 05-SEP-06:03 1.30
October 0.200328E+10 0.33 4113.25 10-OCT-16:00 1.04
November 0.143870E+10 0.29 2382.46 06-NOV-15:30 0.77
December 0.122277E+10 0.28 1433.21 01-DEC-07:01 0.60
           
Annual Sum or Average 0.259970E+11 0.35      
Minimum of Months 0.115856E+10 0.28 1433.21   0.60
Maximum of Months 0.402600E+10 0.48 10333.02   1.85



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.128752E+10 0.30 2418.94 02-JAN-06:11 0.83
February 0.122640E+10 0.31 2418.94 13-FEB-06:06 0.84
March 0.149993E+10 0.33 2758.71 30-MAR-16:00 0.89
April 0.160818E+10 0.33 2952.17 17-APR-16:00 0.92
May 0.214141E+10 0.37 3812.99 30-MAY-15:00 1.07
June 0.285815E+10 0.44 7237.35 26-JUN-05:12 1.58
July 0.305989E+10 0.44 8225.17 15-JUL-05:03 1.71
August 0.337344E+10 0.47 10068.59 14-AUG-04:02 1.95
September 0.229826E+10 0.38 4439.77 07-SEP-15:30 1.17
October 0.166024E+10 0.33 3263.84 11-OCT-15:30 0.98
November 0.131425E+10 0.30 1773.65 21-NOV-06:01 0.71
December 0.127550E+10 0.29 2418.94 04-DEC-06:01 0.84
           
Annual Sum or Average 0.236032E+11 0.36      
Minimum of Months 0.122640E+10 0.29 1773.65   0.71
Maximum of Months 0.337344E+10 0.47 10068.59   1.95



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.142140E+10 0.31 2283.42 02-JAN-06:12 0.72
February 0.127601E+10 0.31 2283.42 06-FEB-06:01 0.73
March 0.144176E+10 0.30 2719.06 30-MAR-16:00 0.79
April 0.152668E+10 0.30 2938.56 17-APR-15:40 0.82
May 0.201374E+10 0.34 3708.04 30-MAY-15:00 0.94
June 0.266783E+10 0.39 4971.99 26-JUN-05:12 1.11
July 0.285810E+10 0.39 5248.38 15-JUL-05:03 1.15
August 0.310145E+10 0.41 5967.66 14-AUG-04:02 1.25
September 0.202715E+10 0.34 4178.55 07-SEP-15:30 1.00
October 0.149315E+10 0.29 2842.58 11-OCT-15:30 0.81
November 0.126804E+10 0.28 2283.42 21-NOV-06:01 0.72
December 0.128973E+10 0.28 2283.42 26-DEC-06:14 0.72
           
Annual Sum or Average 0.223850E+11 0.33      
Minimum of Months 0.126804E+10 0.28 2283.42   0.72
Maximum of Months 0.310145E+10 0.41 5967.66   1.25



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:10 2.06 2.06 58.23 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:02 2.06 2.06 57.25 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:03 2.06 2.06 57.18 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:03 2.06 2.06 57.27 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.59 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.75 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 57.89 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.95 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.91 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.48 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.49 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:01 2.06 2.06 57.49 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 57.18 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.48 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 58.23 58.23 1622.14 5938.05 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 57.73 57.73 1635.70 5938.22 01-FEB-12:13
March 0.00 0.00 01-MAR-00:10 57.77 57.77 1691.06 5844.24 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 57.88 57.88 1473.72 5521.84 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 58.44 58.44 1409.90 5140.54 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 58.21 58.21 1334.31 4713.01 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 58.33 58.33 1154.70 4387.43 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 58.38 58.38 1273.65 4371.12 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 58.34 58.34 1240.92 4647.28 29-SEP-12:00
October 0.00 0.00 01-OCT-00:10 57.50 57.50 1339.84 5078.24 31-OCT-11:10
November 0.00 0.00 01-NOV-00:10 58.07 58.07 1479.94 5492.35 30-NOV-12:40
December 0.00 0.00 01-DEC-00:10 57.90 57.90 1516.69 5797.92 29-DEC-13:00
                 
Annual Sum or Average 0.00         1429.90    
Minimum of Months 0.00 0.00   57.50 57.50 1154.70 4371.12  
Maximum of Months 0.00 0.00   58.44 58.44 1691.06 5938.22  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.160297E+11 0.00 0.00
February 0.00 0.00 0.00 0.106246E+11 0.00 0.00
March 0.00 0.00 0.00 0.686757E+10 0.00 0.00
April 0.00 0.00 0.00 0.834734E+10 0.00 0.00
May 0.00 0.00 0.00 0.134687E+11 0.00 0.00
June 0.00 0.00 0.00 0.205098E+11 0.00 0.00
July 0.00 0.00 0.00 0.236412E+11 0.00 0.00
August 0.00 0.00 0.00 0.267509E+11 0.00 0.00
September 0.00 0.00 0.00 0.168962E+11 0.00 0.00
October 0.00 0.00 0.00 0.879612E+10 0.00 0.00
November 0.00 0.00 0.00 0.557424E+10 0.00 0.00
December 0.00 0.00 0.00 0.704708E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.164554E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.557424E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.267509E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.167049E+11 0.00 0.00
February 0.00 0.00 0.00 0.101035E+11 0.00 0.00
March 0.00 0.00 0.00 0.545296E+10 0.00 0.00
April 0.00 0.00 0.00 0.747525E+10 0.00 0.00
May 0.00 0.00 0.00 0.126597E+11 0.00 0.00
June 0.00 0.00 0.00 0.188771E+11 0.00 0.00
July 0.00 0.00 0.00 0.214948E+11 0.00 0.00
August 0.00 0.00 0.00 0.237161E+11 0.00 0.00
September 0.00 0.00 0.00 0.143651E+11 0.00 0.00
October 0.00 0.00 0.00 0.730586E+10 0.00 0.00
November 0.00 0.00 0.00 0.508289E+10 0.00 0.00
December 0.00 0.00 0.00 0.795936E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.151197E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.508289E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.237161E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.269600E+11 0.00 0.00
February 0.00 0.00 0.00 0.166501E+11 0.00 0.00
March 0.00 0.00 0.00 0.725848E+10 0.00 0.00
April 0.00 0.00 0.00 0.828306E+10 0.00 0.00
May 0.00 0.00 0.00 0.133914E+11 0.00 0.00
June 0.00 0.00 0.00 0.198497E+11 0.00 0.00
July 0.00 0.00 0.00 0.225666E+11 0.00 0.00
August 0.00 0.00 0.00 0.245978E+11 0.00 0.00
September 0.00 0.00 0.00 0.145716E+11 0.00 0.00
October 0.00 0.00 0.00 0.848279E+10 0.00 0.00
November 0.00 0.00 0.00 0.843878E+10 0.00 0.00
December 0.00 0.00 0.00 0.154871E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.186537E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.725848E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.269600E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.120402E+10 0.199769E+10 0.143359E+11 0.00 0.00 0.00 0.00 0.00
February 0.115856E+10 0.496106E+10 0.825235E+10 0.00 0.00 0.00 0.00 0.00
March 0.154119E+10 0.150129E+11 0.181135E+10 0.00 0.00 0.00 0.00 0.00
April 0.164219E+10 0.256881E+11 0.774216E+09 0.00 0.00 0.00 0.00 0.00
May 0.220712E+10 0.489629E+11 0.170531E+09 0.00 0.00 0.00 0.00 0.00
June 0.315088E+10 0.735298E+11 25625123.02 0.00 0.00 0.00 0.00 0.00
July 0.349443E+10 0.845191E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.402600E+10 0.964149E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.290786E+10 0.618762E+11 23737487.74 0.00 0.00 0.00 0.00 0.00
October 0.200328E+10 0.275370E+11 0.575772E+09 0.00 0.00 0.00 0.00 0.00
November 0.143870E+10 0.109438E+11 0.155426E+10 0.00 0.00 0.00 0.00 0.00
December 0.122277E+10 0.396239E+10 0.488409E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.259970E+11 0.455406E+12 0.324078E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115856E+10 0.199769E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402600E+10 0.964149E+11 0.143359E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.128752E+10 0.200835E+10 0.149277E+11 0.00 0.00 0.00 0.00 0.00
February 0.122640E+10 0.494226E+10 0.766625E+10 0.00 0.00 0.00 0.00 0.00
March 0.149993E+10 0.142263E+11 0.603722E+09 0.00 0.00 0.00 0.00 0.00
April 0.160818E+10 0.248281E+11 0.115428E+09 0.00 0.00 0.00 0.00 0.00
May 0.214141E+10 0.462255E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.285815E+10 0.679196E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.305989E+10 0.774759E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.337344E+10 0.865473E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.229826E+10 0.532059E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166024E+10 0.234098E+11 0.310939E+09 0.00 0.00 0.00 0.00 0.00
November 0.131425E+10 0.973853E+10 0.144962E+10 0.00 0.00 0.00 0.00 0.00
December 0.127550E+10 0.369216E+10 0.580035E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.236032E+11 0.414220E+12 0.308740E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122640E+10 0.200835E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337344E+10 0.865473E+11 0.149277E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.142140E+10 0.208812E+10 0.250262E+11 0.00 0.00 0.00 0.00 0.00
February 0.127601E+10 0.511044E+10 0.141155E+11 0.00 0.00 0.00 0.00 0.00
March 0.144176E+10 0.149369E+11 0.227760E+10 0.00 0.00 0.00 0.00 0.00
April 0.152668E+10 0.266444E+11 0.554064E+09 0.00 0.00 0.00 0.00 0.00
May 0.201374E+10 0.496304E+11 14467619.83 0.00 0.00 0.00 0.00 0.00
June 0.266783E+10 0.725011E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.285810E+10 0.823764E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.310145E+10 0.910052E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.202715E+10 0.548678E+11 5998030.42 0.00 0.00 0.00 0.00 0.00
October 0.149315E+10 0.237805E+11 0.152591E+10 0.00 0.00 0.00 0.00 0.00
November 0.126804E+10 0.100445E+11 0.476313E+10 0.00 0.00 0.00 0.00 0.00
December 0.128973E+10 0.380672E+10 0.132821E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.223850E+11 0.436793E+12 0.615651E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126804E+10 0.208812E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310145E+10 0.910052E+11 0.250262E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.120402E+10 0.00 0.00 0.00 0.489820E+09 0.143359E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.115856E+10 0.00 0.00 0.00 0.121366E+10 0.825235E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.154119E+10 0.00 0.00 0.00 0.351503E+10 0.181135E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.164219E+10 0.00 0.00 0.00 0.593094E+10 0.774216E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.220712E+10 0.00 0.00 0.00 0.110910E+11 0.170531E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.315088E+10 0.00 0.00 0.00 0.173333E+11 25625123.02 0.00 0.00 0.00 0.00 0.00 0.00
July 0.349443E+10 0.00 0.00 0.00 0.201468E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.402600E+10 0.00 0.00 0.00 0.227249E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.290786E+10 0.00 0.00 0.00 0.139646E+11 23737487.74 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200328E+10 0.00 0.00 0.00 0.621706E+10 0.575772E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143870E+10 0.00 0.00 0.00 0.258127E+10 0.155426E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.122277E+10 0.00 0.00 0.00 0.940212E+09 0.488409E+10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.259970E+11 0.00 0.00 0.00 0.106149E+12 0.324078E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115856E+10 0.00 0.00 0.00 0.489820E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.402600E+10 0.00 0.00 0.00 0.227249E+11 0.143359E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.128752E+10 0.00 0.00 0.00 0.489702E+09 0.149277E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122640E+10 0.00 0.00 0.00 0.121087E+10 0.766625E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149993E+10 0.00 0.00 0.00 0.334931E+10 0.603722E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.160818E+10 0.00 0.00 0.00 0.575164E+10 0.115428E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.214141E+10 0.00 0.00 0.00 0.105182E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.285815E+10 0.00 0.00 0.00 0.160189E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.305989E+10 0.00 0.00 0.00 0.184349E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.337344E+10 0.00 0.00 0.00 0.203426E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.229826E+10 0.00 0.00 0.00 0.120668E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.166024E+10 0.00 0.00 0.00 0.533468E+10 0.310939E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131425E+10 0.00 0.00 0.00 0.231902E+10 0.144962E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.127550E+10 0.00 0.00 0.00 0.883520E+09 0.580035E+10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.236032E+11 0.00 0.00 0.00 0.967203E+11 0.308740E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122640E+10 0.00 0.00 0.00 0.489702E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337344E+10 0.00 0.00 0.00 0.203426E+11 0.149277E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.142140E+10 0.00 0.00 0.00 0.512351E+09 0.250262E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127601E+10 0.00 0.00 0.00 0.125854E+10 0.141155E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144176E+10 0.00 0.00 0.00 0.353913E+10 0.227760E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.152668E+10 0.00 0.00 0.00 0.620232E+10 0.554064E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.201374E+10 0.00 0.00 0.00 0.113632E+11 14467619.83 0.00 0.00 0.00 0.00 0.00 0.00
June 0.266783E+10 0.00 0.00 0.00 0.171819E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.285810E+10 0.00 0.00 0.00 0.197085E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.310145E+10 0.00 0.00 0.00 0.214964E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.202715E+10 0.00 0.00 0.00 0.125384E+11 5998030.42 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149315E+10 0.00 0.00 0.00 0.546374E+10 0.152591E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.126804E+10 0.00 0.00 0.00 0.240761E+10 0.476313E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.128973E+10 0.00 0.00 0.00 0.915216E+09 0.132821E+11 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.223850E+11 0.00 0.00 0.00 0.102587E+12 0.615651E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126804E+10 0.00 0.00 0.00 0.512351E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310145E+10 0.00 0.00 0.00 0.214964E+11 0.250262E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107938E+11 0.00 0.00 2811407.42 12196086.94 3211521.18 0.304176E+10 0.00 0.35
February 0.630152E+10 0.00 0.00 9398497.38 0.00 0.00 0.561958E+10 0.00 0.45
March 0.156444E+10 0.278919E+09 0.00 25877121.49 20599372.47 0.00 0.115804E+11 0.00 0.62
April 0.618951E+09 0.511114E+09 0.00 26462290.17 37531644.99 0.00 0.761531E+10 0.00 0.65
May 0.153691E+09 0.285992E+10 0.00 13178424.07 48928329.67 0.00 0.269655E+10 0.00 0.52
June 54930091.65 0.813858E+10 0.00 6344883.50 73888838.62 0.00 0.128857E+10 0.00 0.41
July 0.00 0.106465E+11 0.00 0.00 0.195448E+09 0.00 0.00 0.00 0.28
August 0.00 0.127602E+11 0.00 227309.88 0.147522E+09 0.00 1765519.26 0.00 0.30
September 64325288.98 0.517321E+10 0.00 13467476.53 0.100799E+09 0.00 0.186821E+10 0.00 0.49
October 0.598638E+09 0.155501E+10 0.00 27940341.97 6522624.80 0.00 0.110149E+11 0.00 0.62
November 0.168531E+10 0.162181E+09 0.00 26078030.45 40226014.24 0.00 0.120753E+11 0.00 0.59
December 0.588241E+10 35724195.88 0.00 11296080.18 280913.61 0.00 0.745345E+10 0.00 0.43
                   
Annual Sum or Average 0.277180E+11 0.421214E+11 0.00 0.163082E+09 0.683943E+09 3211521.18 0.642558E+11 0.00 0.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.107938E+11 0.127602E+11 0.00 27940341.97 0.195448E+09 3211521.18 0.120753E+11 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.123375E+11 0.00 0.00 0.00 30465428.19 0.554017E+09 0.00 0.00 0.34
February 0.100978E+11 0.00 0.00 521021.43 4929884.32 0.137426E+09 0.352395E+09 0.00 0.41
March 0.759308E+10 0.112425E+09 0.00 3857895.03 0.172307E+09 0.00 0.262211E+10 0.00 0.49
April 0.316461E+10 0.235004E+09 0.00 8619912.49 0.246180E+09 0.00 0.293523E+10 0.00 0.49
May 0.740773E+09 0.198605E+10 0.00 5628800.44 0.348712E+09 0.00 0.127877E+10 0.00 0.39
June 0.286235E+09 0.705555E+10 0.00 3138689.69 0.125536E+09 0.00 0.684400E+09 0.00 0.33
July 0.00 0.926307E+10 0.00 0.00 0.382048E+09 0.00 0.00 0.00 0.24
August 1622979.08 0.115987E+11 0.00 72011.19 0.146207E+09 0.00 1470764.82 0.00 0.27
September 0.369610E+09 0.427287E+10 0.00 5599502.19 0.522121E+09 0.00 0.830043E+09 0.00 0.37
October 0.464524E+10 0.122835E+10 0.00 6569837.54 0.146241E+09 0.00 0.327464E+10 0.00 0.46
November 0.842493E+10 29443114.59 0.00 1700350.39 0.253404E+09 1329154.34 0.151501E+10 0.00 0.44
December 0.111079E+11 17525215.21 0.00 55310.92 42808772.48 0.109029E+09 0.108333E+09 0.00 0.39
                   
Annual Sum or Average 0.587694E+11 0.357990E+11 0.00 35763331.29 0.242096E+10 0.801801E+09 0.136024E+11 0.00 0.38
Minimum of Months 0.00 0.00 0.00 0.00 4929884.32 0.00 0.00 0.00 0.24
Maximum of Months 0.123375E+11 0.115987E+11 0.00 8619912.49 0.522121E+09 0.554017E+09 0.327464E+10 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.991030E+10 0.00 0.00 0.00 25261788.51 0.260091E+10 0.00 0.00 0.34
February 0.905356E+10 0.00 0.00 207597.74 8486101.42 0.101896E+10 81864316.67 0.00 0.42
March 0.880263E+10 0.112093E+09 0.00 2070870.71 0.187690E+09 20985917.90 0.958938E+09 0.00 0.50
April 0.368064E+10 0.176453E+09 0.00 7119513.60 0.268707E+09 1429835.16 0.206983E+10 0.00 0.51
May 0.789356E+09 0.179450E+10 0.00 3649328.21 0.426347E+09 0.00 0.100745E+10 0.00 0.38
June 0.372909E+09 0.670770E+10 0.00 2639494.36 0.160067E+09 0.00 0.517482E+09 0.00 0.33
July 0.00 0.885325E+10 0.00 0.00 0.454165E+09 0.00 0.00 0.00 0.24
August 0.00 0.112030E+11 0.00 0.00 0.164449E+09 0.00 0.00 0.00 0.26
September 0.449449E+09 0.374227E+10 0.00 4361759.79 0.107316E+10 0.00 0.519612E+09 0.00 0.36
October 0.570231E+10 0.106209E+10 0.00 2771504.59 0.334819E+09 13060172.75 0.148263E+10 0.00 0.44
November 0.874972E+10 17648403.24 3338853.96 310975.10 0.301651E+09 0.153079E+09 0.294561E+09 40307.84 0.45
December 0.997790E+10 1434671.72 0.00 0.00 73956751.66 0.786610E+09 0.00 0.00 0.39
                   
Annual Sum or Average 0.574888E+11 0.336704E+11 3338853.96 23131044.09 0.347876E+10 0.459503E+10 0.693237E+10 40307.84 0.39
Minimum of Months 0.00 0.00 0.00 0.00 8486101.42 0.00 0.00 0.00 0.24
Maximum of Months 0.997790E+10 0.112030E+11 3338853.96 7119513.60 0.107316E+10 0.260091E+10 0.206983E+10 40307.84 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.551068E+09 0.00 0.00 0.00 5332229.98 0.225820E+10 0.00 0.00 0.36
February 0.935801E+09 0.00 296001.33 60175.02 1494767.84 0.127602E+10 18353606.05 467.60 0.43
March 0.171818E+10 27301065.44 0.00 344805.60 38380656.88 0.228663E+09 0.123514E+09 0.00 0.51
April 0.917436E+09 63357123.02 0.00 1511659.72 37657073.77 55414935.33 0.260326E+09 0.00 0.54
May 0.214639E+09 0.522105E+09 0.00 801758.15 62216357.31 284381.19 0.176316E+09 0.00 0.43
June 81870034.61 0.210988E+10 0.00 703073.57 33425671.93 0.00 0.119737E+09 0.00 0.45
July 0.00 0.284893E+10 0.00 0.00 82027730.10 0.00 0.00 0.00 0.35
August 0.00 0.337600E+10 0.00 0.00 41035298.21 0.00 0.00 0.00 0.37
September 0.114135E+09 0.995677E+09 0.00 941169.31 0.207179E+09 0.00 0.100558E+09 0.00 0.40
October 0.124232E+10 0.256063E+09 0.00 305011.40 70789443.25 0.127363E+09 0.142346E+09 0.00 0.45
November 0.147286E+10 3748431.90 3672476.16 13520.43 60750515.99 0.473921E+09 10472444.33 12365.51 0.45
December 0.101155E+10 0.00 91130.96 0.00 15822040.44 0.133424E+10 0.00 365.68 0.40
                   
Annual Sum or Average 0.825986E+10 0.102031E+11 4059608.45 4681173.20 0.656111E+09 0.575410E+10 0.951623E+09 13198.80 0.43
Minimum of Months 0.00 0.00 0.00 0.00 1494767.84 0.00 0.00 0.00 0.35
Maximum of Months 0.171818E+10 0.337600E+10 3672476.16 1511659.72 0.207179E+09 0.225820E+10 0.260326E+09 12365.51 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.846586E+09 0.00 0.00 0.00 4484692.00 0.142587E+10 0.00 0.00 0.46
February 0.913900E+09 0.00 248724.72 208180.51 1257180.09 0.798571E+09 0.116602E+09 621.59 0.56
March 0.127490E+10 22389448.49 0.00 834367.80 32879307.08 0.123721E+09 0.357109E+09 0.00 0.69
April 0.520920E+09 50331088.48 0.00 2457199.09 33973687.26 25112614.85 0.593249E+09 0.00 0.82
May 0.130313E+09 0.498504E+09 0.00 1204193.98 56565860.45 659768.24 0.267609E+09 0.00 0.65
June 52088447.72 0.177526E+10 0.00 915378.06 37096476.51 0.00 0.173916E+09 0.00 0.64
July 0.00 0.248185E+10 0.00 0.00 94666548.05 0.00 0.00 0.00 0.48
August 0.00 0.284333E+10 0.00 0.00 59615294.10 0.00 0.00 0.00 0.50
September 86779830.66 0.944570E+09 0.00 1128066.20 0.178305E+09 215472.43 0.121938E+09 0.00 0.61
October 0.839273E+09 0.222316E+09 0.00 931397.32 62906720.34 96279034.69 0.406718E+09 0.00 0.63
November 0.130964E+10 4440742.05 3041936.00 64510.42 49806339.65 0.263883E+09 64675298.27 7910.17 0.59
December 0.118445E+10 0.00 75422.30 0.00 13307186.37 0.749590E+09 0.00 1531.29 0.53
                   
Annual Sum or Average 0.715886E+10 0.884300E+10 3366083.03 7743293.37 0.624865E+09 0.348390E+10 0.210182E+10 10063.05 0.60
Minimum of Months 0.00 0.00 0.00 0.00 1257180.09 0.00 0.00 0.00 0.46
Maximum of Months 0.130964E+10 0.284333E+10 3041936.00 2457199.09 0.178305E+09 0.142587E+10 0.593249E+09 7910.17 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100110E+10 0.00 0.00 971887.02 5415244.02 0.136001E+10 0.578887E+09 0.00 0.38
February 0.977907E+09 0.00 0.00 1868478.31 1819123.37 0.806226E+09 0.725728E+09 0.00 0.52
March 0.125760E+10 61410997.80 0.00 3329048.67 21887433.04 0.166024E+09 0.108183E+10 0.00 0.66
April 0.706465E+09 88335045.36 0.00 3544698.36 24661265.20 43963634.92 0.727914E+09 0.00 0.70
May 0.205654E+09 0.592869E+09 0.00 1138821.90 64986792.79 288808.54 0.237848E+09 0.00 0.49
June 90808129.85 0.214459E+10 0.00 719596.45 52205434.71 0.00 0.120102E+09 0.00 0.46
July 0.00 0.296566E+10 0.00 0.00 98188586.27 0.00 0.00 0.00 0.36
August 0.00 0.391346E+10 0.00 0.00 42611512.98 0.00 0.00 0.00 0.43
September 0.106338E+09 0.141907E+10 0.00 1851279.98 0.165857E+09 0.00 0.190333E+09 0.00 0.56
October 0.847216E+09 0.443958E+09 0.00 3661708.51 39617564.73 89656222.47 0.125215E+10 0.00 0.70
November 0.113928E+10 8461826.42 1524932.89 3019807.79 61162066.46 0.254939E+09 0.109756E+10 9541.41 0.61
December 0.118617E+10 6088918.90 0.00 1898934.81 12652318.88 0.617479E+09 0.846136E+09 0.00 0.47
                   
Annual Sum or Average 0.751854E+10 0.116439E+11 1524932.89 22004261.80 0.591064E+09 0.333859E+10 0.685848E+10 9541.41 0.53
Minimum of Months 0.00 0.00 0.00 0.00 1819123.37 0.00 0.00 0.00 0.36
Maximum of Months 0.125760E+10 0.391346E+10 1524932.89 3661708.51 0.165857E+09 0.136001E+10 0.125215E+10 9541.41 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.821402E+09 0.00 0.00 0.00 4943029.16 0.166901E+10 0.00 0.00 0.51
February 0.943893E+09 0.00 0.00 302150.05 1660493.94 0.978961E+09 0.112232E+09 0.00 0.63
March 0.141337E+10 33000170.91 0.00 1183678.45 30875675.14 0.192949E+09 0.393599E+09 0.00 0.80
April 0.724003E+09 46642248.63 0.00 2404872.69 43937551.52 42130305.18 0.483956E+09 0.00 0.90
May 0.202170E+09 0.422014E+09 0.00 941127.40 87803967.47 727196.80 0.214857E+09 0.00 0.67
June 91447070.26 0.165304E+10 0.00 645495.22 85291475.04 0.00 0.104057E+09 0.00 0.61
July 0.00 0.225210E+10 0.00 0.00 0.146011E+09 0.00 0.00 0.00 0.45
August 0.00 0.279750E+10 0.00 0.00 78727405.86 0.00 0.00 0.00 0.49
September 0.111247E+09 0.844146E+09 0.00 972751.56 0.242910E+09 237493.79 97747483.05 0.00 0.61
October 0.103838E+10 0.193756E+09 0.00 949297.92 97059372.64 0.111625E+09 0.347268E+09 0.00 0.71
November 0.129491E+10 584183.28 3338142.83 367368.25 59206969.97 0.384529E+09 0.156805E+09 7812.36 0.67
December 0.110499E+10 391096.37 82884.64 9420.01 14276089.31 0.994477E+09 27511497.50 1933.65 0.58
                   
Annual Sum or Average 0.774582E+10 0.824318E+10 3421027.47 7776161.56 0.892703E+09 0.437465E+10 0.193803E+10 9746.00 0.64
Minimum of Months 0.00 0.00 0.00 0.00 1660493.94 0.00 0.00 0.00 0.45
Maximum of Months 0.141337E+10 0.279750E+10 3338142.83 2404872.69 0.242910E+09 0.166901E+10 0.483956E+09 7812.36 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.805126E+09 0.00 0.00 0.00 2571587.23 0.215163E+10 0.00 0.00 0.35
February 0.124229E+10 0.00 0.00 1261.41 0.00 0.119356E+10 2854878.72 0.00 0.42
March 0.209380E+10 8988736.64 0.00 34819.04 44148835.74 0.125171E+09 35836284.58 0.00 0.49
April 0.120018E+10 21110806.18 0.00 290557.98 70767652.05 22023771.72 58969424.59 0.00 0.47
May 0.326495E+09 0.363490E+09 0.00 293200.64 92767226.82 0.00 82243808.97 0.00 0.36
June 99566027.49 0.160691E+10 0.00 542417.68 23437227.17 0.00 98625977.96 0.00 0.35
July 0.00 0.224348E+10 0.00 0.00 52926012.48 0.00 0.00 0.00 0.27
August 261562.64 0.270833E+10 0.00 2547.72 31292293.19 0.00 40108.52 0.00 0.29
September 0.140622E+09 0.943568E+09 0.00 1088010.73 31765373.50 0.00 0.142359E+09 0.00 0.38
October 0.151090E+10 0.245043E+09 0.00 521128.32 10756879.74 3407725.99 0.259747E+09 0.00 0.45
November 0.221387E+10 2388841.19 0.00 53298.31 35966492.67 70470362.75 48101030.50 0.00 0.46
December 0.204283E+10 0.00 0.00 0.00 5742888.11 0.654348E+09 0.00 0.00 0.41
                   
Annual Sum or Average 0.116759E+11 0.814330E+10 0.00 2827241.83 0.402142E+09 0.422061E+10 0.728778E+09 0.00 0.39
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.221387E+10 0.270833E+10 0.00 1088010.73 92767226.82 0.215163E+10 0.259747E+09 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.982555E+09 0.00 0.00 0.00 1897249.09 0.118983E+10 0.00 0.00 0.40
February 0.106361E+10 0.00 0.00 181957.54 0.00 0.618816E+09 0.109075E+09 0.00 0.49
March 0.136527E+10 10900304.81 0.00 483232.97 29149200.29 46198511.38 0.265540E+09 0.00 0.58
April 0.652689E+09 27931491.93 0.00 1472185.80 42453196.18 5862576.21 0.361069E+09 0.00 0.63
May 0.151374E+09 0.386601E+09 0.00 1021980.39 51964784.61 0.00 0.225624E+09 0.00 0.53
June 46810179.10 0.142463E+10 0.00 885387.52 16281209.38 0.00 0.173630E+09 0.00 0.52
July 0.00 0.204196E+10 0.00 0.00 47888125.07 0.00 0.00 0.00 0.39
August 192974.00 0.236726E+10 0.00 2062.88 23082409.35 0.00 29407.77 0.00 0.41
September 93203644.08 0.868320E+09 0.00 1341039.90 19045709.07 0.00 0.175260E+09 0.00 0.56
October 0.831313E+09 0.212541E+09 0.00 1583497.06 3448525.48 2521462.08 0.669939E+09 0.00 0.61
November 0.149041E+10 1941215.21 0.00 418431.62 26369318.69 15792226.83 0.231463E+09 0.00 0.55
December 0.173296E+10 0.00 0.00 0.00 4236951.07 0.257057E+09 0.00 0.00 0.48
                   
Annual Sum or Average 0.841040E+10 0.734208E+10 0.00 7389775.69 0.265817E+09 0.213607E+10 0.221163E+10 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.173296E+10 0.236726E+10 0.00 1583497.06 51964784.61 0.118983E+10 0.669939E+09 0.00 0.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.119424E+10 0.00 0.00 76377.59 2565124.50 0.223220E+10 64281222.07 0.00 0.40
February 0.112918E+10 0.00 0.00 828847.51 0.00 0.145670E+10 0.266944E+09 0.00 0.50
March 0.162201E+10 45754733.16 0.00 975753.87 20190342.71 0.546546E+09 0.332100E+09 0.00 0.56
April 0.975105E+09 43477408.72 0.00 1214331.31 60165489.78 0.287112E+09 0.130502E+09 0.00 0.55
May 0.298319E+09 0.474583E+09 0.00 368947.90 93219032.71 64521157.81 75538216.84 0.00 0.41
June 0.113362E+09 0.190874E+10 0.00 419986.68 74062980.98 16268375.81 66899729.24 0.00 0.39
July 0.00 0.264749E+10 0.00 0.00 0.107770E+09 0.00 0.00 0.00 0.32
August 303454.34 0.361148E+10 0.00 0.00 48395920.16 0.00 0.00 0.00 0.39
September 0.146103E+09 0.137340E+10 0.00 1736376.31 46273088.12 14856122.53 0.179107E+09 0.00 0.53
October 0.982694E+09 0.404757E+09 0.00 3065738.33 8758294.42 0.252958E+09 0.106493E+10 0.00 0.66
November 0.143442E+10 11423159.96 0.00 2496544.19 28707228.29 0.471534E+09 0.979191E+09 0.00 0.61
December 0.174787E+10 3954181.10 0.00 803791.23 2760006.29 0.861966E+09 0.426349E+09 0.00 0.46
                   
Annual Sum or Average 0.964360E+10 0.105251E+11 0.00 11986694.91 0.492867E+09 0.620466E+10 0.358584E+10 0.00 0.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
Maximum of Months 0.174787E+10 0.361148E+10 0.00 3065738.33 0.107770E+09 0.223220E+10 0.106493E+10 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.894289E+09 0.00 0.00 0.00 1962741.96 0.135064E+10 0.00 0.00 0.42
February 0.108288E+10 0.00 0.00 186022.49 0.00 0.720337E+09 55066866.71 0.00 0.51
March 0.147657E+10 24830057.64 0.00 591123.92 21258914.69 55682363.29 0.219927E+09 0.00 0.62
April 0.789447E+09 31615079.56 0.00 1079380.50 44068693.81 11320725.71 0.217855E+09 0.00 0.64
May 0.216329E+09 0.355633E+09 0.00 572933.67 53314441.42 0.00 0.138185E+09 0.00 0.51
June 78325808.37 0.136317E+10 0.00 551754.34 19743443.18 0.00 87258303.46 0.00 0.48
July 0.00 0.189402E+10 0.00 0.00 46515016.88 0.00 0.00 0.00 0.36
August 175091.49 0.235494E+10 0.00 2521.41 14691123.44 0.00 54579.56 0.00 0.40
September 0.105202E+09 0.838240E+09 0.00 1117404.56 22379161.76 0.00 0.123393E+09 0.00 0.53
October 0.979995E+09 0.210290E+09 0.00 1251166.43 5307176.43 838808.70 0.483436E+09 0.00 0.62
November 0.155691E+10 1870295.47 0.00 544771.44 27406782.75 32816381.24 0.234319E+09 0.00 0.58
December 0.169384E+10 211287.74 0.00 27742.28 4171922.50 0.332433E+09 31829067.66 0.00 0.49
                   
Annual Sum or Average 0.887396E+10 0.707482E+10 0.00 5924821.05 0.260819E+09 0.250407E+10 0.159132E+10 0.00 0.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.169384E+10 0.235494E+10 0.00 1251166.43 53314441.42 0.135064E+10 0.483436E+09 0.00 0.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.855232E+09 0.00 0.00 0.00 6408868.40 0.191510E+10 0.00 0.00 0.34
February 0.127520E+10 0.00 0.00 73787.26 1037076.51 0.970326E+09 15858958.71 0.00 0.41
March 0.195611E+10 32196153.16 0.00 343126.15 30967423.32 67358177.61 0.124986E+09 0.00 0.50
April 0.967378E+09 81118024.75 0.00 1330873.86 29611691.49 14949408.87 0.290097E+09 0.00 0.51
May 0.229673E+09 0.596910E+09 0.00 953843.94 32722445.41 0.00 0.190569E+09 0.00 0.43
June 82177520.06 0.226349E+10 0.00 734512.42 16688607.21 0.00 0.126649E+09 0.00 0.44
July 0.00 0.303205E+10 0.00 0.00 53803008.55 0.00 0.00 0.00 0.35
August 484289.12 0.355392E+10 0.00 686.41 30999094.49 0.00 180989.44 0.00 0.38
September 0.141040E+09 0.116407E+10 0.00 907451.22 55851684.06 0.00 0.104506E+09 0.00 0.40
October 0.140216E+10 0.297317E+09 0.00 451309.26 25520735.74 19156329.37 0.202063E+09 0.00 0.45
November 0.182865E+10 5712044.37 184101.44 32054.76 53601910.88 0.226015E+09 38639087.69 4275.99 0.44
December 0.159428E+10 812447.25 0.00 0.00 11879729.10 0.809633E+09 0.00 0.00 0.39
                   
Annual Sum or Average 0.103324E+11 0.110276E+11 184101.44 4827645.28 0.349092E+09 0.402254E+10 0.109355E+10 4275.99 0.42
Minimum of Months 0.00 0.00 0.00 0.00 1037076.51 0.00 0.00 0.00 0.34
Maximum of Months 0.195611E+10 0.355392E+10 184101.44 1330873.86 55851684.06 0.191510E+10 0.290097E+09 4275.99 0.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.105640E+10 0.00 0.00 0.00 5424101.81 0.126131E+10 0.00 0.00 0.45
February 0.110361E+10 0.00 0.00 291955.98 877722.59 0.662101E+09 0.146618E+09 0.00 0.55
March 0.135341E+10 23418393.86 0.00 991237.40 28672518.54 39971457.92 0.474555E+09 0.00 0.68
April 0.577913E+09 68828240.41 0.00 2401406.04 22694264.80 7033572.87 0.650658E+09 0.00 0.78
May 0.154738E+09 0.527508E+09 0.00 1403784.07 40282811.66 0.00 0.292099E+09 0.00 0.66
June 57763794.43 0.185499E+10 0.00 960724.74 18958394.18 0.00 0.186258E+09 0.00 0.63
July 0.00 0.257874E+10 0.00 0.00 69573958.63 0.00 0.00 0.00 0.48
August 539851.49 0.293952E+10 0.00 143.17 32740838.30 0.00 23640.22 0.00 0.50
September 0.117190E+09 0.976902E+09 0.00 1078434.69 0.118346E+09 0.00 0.131903E+09 0.00 0.60
October 0.977285E+09 0.223794E+09 0.00 1202254.16 42088367.80 18523488.62 0.513188E+09 0.00 0.65
November 0.150311E+10 5207161.61 151041.76 207007.82 44981746.85 0.124762E+09 0.148495E+09 3539.39 0.59
December 0.157984E+10 0.00 0.00 0.00 10741936.39 0.447865E+09 0.00 0.00 0.52
                   
Annual Sum or Average 0.848180E+10 0.919890E+10 151041.76 8536948.07 0.435382E+09 0.256157E+10 0.254380E+10 3539.39 0.59
Minimum of Months 0.00 0.00 0.00 0.00 877722.59 0.00 0.00 0.00 0.45
Maximum of Months 0.157984E+10 0.293952E+10 151041.76 2401406.04 0.118346E+09 0.126131E+10 0.650658E+09 3539.39 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122605E+10 0.00 0.00 1407788.14 6419724.90 0.102733E+10 0.742707E+09 0.00 0.37
February 0.123943E+10 0.00 0.00 2243410.21 1038833.29 0.516929E+09 0.844852E+09 0.00 0.52
March 0.139832E+10 77629038.96 0.00 3492957.57 11577361.89 36065323.93 0.116915E+10 0.00 0.66
April 0.749991E+09 0.116950E+09 0.00 3209587.96 14847055.27 14254750.53 0.719960E+09 0.00 0.65
May 0.230990E+09 0.687958E+09 0.00 1203495.60 33373537.65 0.00 0.227713E+09 0.00 0.48
June 97892573.84 0.232600E+10 0.00 693038.85 17991854.95 0.00 0.111922E+09 0.00 0.46
July 0.00 0.318821E+10 0.00 0.00 52737950.23 0.00 0.00 0.00 0.37
August 485109.49 0.415166E+10 0.00 622.94 31051606.34 0.00 181360.66 0.00 0.44
September 0.133580E+09 0.159693E+10 0.00 1689884.71 42144370.02 0.00 0.173909E+09 0.00 0.55
October 0.940345E+09 0.474790E+09 0.00 4235705.40 12678602.95 16230034.45 0.141010E+10 0.00 0.73
November 0.131710E+10 20629064.78 0.00 3987531.21 42754029.93 70746455.92 0.137832E+10 0.00 0.64
December 0.143163E+10 14315542.01 0.00 2571263.87 3162342.48 0.337588E+09 0.108199E+10 0.00 0.48
                   
Annual Sum or Average 0.876582E+10 0.126551E+11 0.00 24735286.46 0.269777E+09 0.201915E+10 0.786080E+10 0.00 0.53
Minimum of Months 0.00 0.00 0.00 0.00 1038833.29 0.00 0.00 0.00 0.37
Maximum of Months 0.143163E+10 0.415166E+10 0.00 4235705.40 52737950.23 0.102733E+10 0.141010E+10 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.969645E+09 0.00 0.00 0.00 5642664.66 0.143886E+10 0.00 0.00 0.47
February 0.118535E+10 0.00 0.00 339018.31 913090.20 0.710429E+09 0.102660E+09 0.00 0.59
March 0.155511E+10 45892325.87 0.00 1149778.70 17490373.46 54637538.51 0.369345E+09 0.00 0.75
April 0.769299E+09 71893835.41 0.00 2043650.82 28011127.56 13289197.22 0.435968E+09 0.00 0.80
May 0.218202E+09 0.514183E+09 0.00 882582.13 40609265.63 0.00 0.197506E+09 0.00 0.65
June 92759174.02 0.184742E+10 0.00 598519.76 27625801.67 0.00 93280729.50 0.00 0.61
July 0.00 0.248557E+10 0.00 0.00 66986327.93 0.00 0.00 0.00 0.46
August 586346.41 0.301697E+10 0.00 0.00 24278889.56 0.00 0.00 0.00 0.50
September 0.133687E+09 0.957398E+09 0.00 849005.21 0.128855E+09 0.00 83462479.55 0.00 0.58
October 0.114664E+10 0.236254E+09 0.00 1080904.84 39177265.21 18532888.93 0.366557E+09 0.00 0.68
November 0.150564E+10 3958639.15 162569.20 494289.30 48279504.09 0.167864E+09 0.211594E+09 3819.52 0.64
December 0.148668E+10 1024365.47 0.00 36584.15 10150414.62 0.578887E+09 42330957.22 0.00 0.54
                   
Annual Sum or Average 0.906361E+10 0.918057E+10 162569.20 7474333.23 0.438019E+09 0.298250E+10 0.190270E+10 3819.52 0.61
Minimum of Months 0.00 0.00 0.00 0.00 913090.20 0.00 0.00 0.00 0.46
Maximum of Months 0.155511E+10 0.301697E+10 162569.20 2043650.82 0.128855E+09 0.143886E+10 0.435968E+09 3819.52 0.80



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:14

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.188488E+12 0.105682E+11 0.00 0.197666E+12 0.758604E+10
February 0.186118E+12 0.861413E+10 0.00 0.190471E+12 0.186968E+11
March 0.267020E+12 0.551382E+10 0.00 0.204633E+12 0.545796E+11
April 0.296197E+12 0.246177E+10 0.00 0.129664E+12 0.950455E+11
May 0.324943E+12 -419558405.2 0.00 0.364272E+11 0.177791E+12
June 0.315034E+12 -0.413490E+10 0.00 -0.176182E+11 0.264485E+12
July 0.305345E+12 -0.587463E+10 0.00 -0.613737E+11 0.302662E+12
August 0.284910E+12 -0.720119E+10 0.00 -0.741042E+11 0.338531E+12
September 0.223406E+12 -0.210898E+10 0.00 -0.421923E+10 0.208520E+12
October 0.215474E+12 0.261435E+10 0.00 0.144319E+12 0.917429E+11
November 0.159275E+12 0.556751E+10 0.00 0.183317E+12 0.380348E+11
December 0.153647E+12 0.909936E+10 0.00 0.220108E+12 0.142002E+11
           
Annual Sum or Average 0.291986E+13 0.246999E+11 0.00 0.114929E+13 0.161187E+13
Minimum of Months 0.153647E+12 -0.720119E+10 0.00 -0.741042E+11 0.758604E+10
Maximum of Months 0.324943E+12 0.105682E+11 0.00 0.220108E+12 0.338531E+12