Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:20:09


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1534.55 308.01 308.01
Net Site Energy 1534.55 308.01 308.01
Total Source Energy 4387.25 880.59 880.59
Net Source Energy 4387.25 880.59 880.59


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 226.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 70.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 303.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 79.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1307.63 226.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 226.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 70.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 303.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 79.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 226.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 70.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 303.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 79.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 41.23 45.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 262.46 45.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 41.23 45.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 262.46 45.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1307.629 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1307.629 100.00
     
Total On-Site and Utility Electric Sources 1307.629 100.00
Total Electricity End Uses 1307.629 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 306.50
Time Setpoint Not Met During Occupied Cooling 45.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 1700.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 8.6994 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 8.6994 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 8.6994 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 8.6994 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 8.6994 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 8.6994 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 8.6994 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 8.6994 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 8.6994 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 8.6994 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 8.6994 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 8.6994 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 8.6994 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 8.6994 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 8.6994 18.58 8.0700  
Total 4982.19             8.6994 9.29 24.1370  
Conditioned Total 4982.19             8.6994 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 8.6994 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-AUG-15:20 26-DEC-07:19 - - - - - - - - - - 03-JAN-12:09
Heating 0.00 185997.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 53036.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41670.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27002.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4248.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 153056.31 185997.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 185997.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 53036.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 25681.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 57.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 27002.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4248.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 245.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 222.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 962.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 163.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 252.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 171.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4141.26 245.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 49.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 44.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 193.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 50.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 831.21 49.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 49.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 44.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 193.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 50.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 831.21 49.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 2.73 0.274048 0.285000 0.779406 0.730794 0.500000 0.001390 0.000116 0.779406 12.80 0.008000
CORE_MID VAV BOX COMPONENT 2.21 0.339235 0.346000 0.764400 0.904627 0.500000 0.001123 0.000174 0.764400 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 2.25 0.332505 0.350000 0.788887 0.886681 0.500000 0.001146 0.000272 0.938507 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.628908 0.251216 0.264000 0.166032 0.669909 0.500000 0.001517 0.000123 0.426413 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.803839 0.124430 0.200000 0.160768 0.331814 0.500000 0.003062 0.000081 0.278819 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.20 0.131296 0.200000 0.240665 0.350122 0.500000 0.002902 0.000123 0.423699 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.877907 0.113925 0.200000 0.175581 0.303799 0.500000 0.003344 0.000080 0.277248 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.507654 0.311219 0.323000 0.163972 0.829918 0.500000 0.001224 0.000092 0.318765 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.667855 0.149766 0.200000 0.133571 0.399375 0.500000 0.002544 0.000061 0.211298 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.992249 0.159226 0.200000 0.198450 0.424602 0.500000 0.002393 0.000091 0.316196 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.737320 0.135647 0.200000 0.147464 0.361726 0.500000 0.002809 0.000061 0.209618 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.557174 0.283559 0.289000 0.161023 0.756157 0.500000 0.001344 0.000096 0.332205 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.804107 0.124389 0.200000 0.160821 0.331703 0.500000 0.003063 0.000063 0.218926 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 1.12 0.141127 0.200000 0.223900 0.376339 0.500000 0.002700 0.000095 0.329484 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.820951 0.121829 0.200000 0.164190 0.324876 0.500000 0.003127 0.000063 0.217419 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 13240.10 0.000116 287.10
CORE_MID VAV BOX REHEAT COIL 19904.87 0.000174 479.13
CORE_TOP VAV BOX REHEAT COIL 31102.57 0.000272 821.31
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 14094.43 0.000123 371.74
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 9215.29 0.000081 243.04
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 14004.90 0.000123 369.38
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 9163.45 0.000080 241.68
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 10543.08 0.000092 278.15
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6987.79 0.000061 184.34
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 10458.32 0.000091 275.92
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 6932.38 0.000061 182.88
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 10986.49 0.000096 289.84
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 7239.44 0.000063 190.98
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 10896.75 0.000095 287.47
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 7189.74 0.000063 189.67
PACU_VAV_BOT HEATING COIL 21468.83 0.000188 361.65
PACU_VAV_MID HEATING COIL 22456.55 0.000196 374.86
PACU_VAV_TOP HEATING COIL 21967.65 0.000192 370.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.82 1.42 5.64 1.48 4.93 4.93 0.300000 0.300535 4.93
PACU_VAV_MID 2.76 1.47 5.51 1.63 4.59 4.59 0.300000 0.354217 4.59
PACU_VAV_TOP 2.88 1.53 5.77 2.34 5.17 5.17 0.300000 0.453897 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.93
PACU_VAV_MID_OA_CONTROLLER 4.59
PACU_VAV_TOP_OA_CONTROLLER 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.93 86560.51 0.800374 1.64 28850.62 0.800374
PACU_VAV_MID COOLING COIL 4.59 81291.90 0.800621 1.53 27094.59 0.800621
PACU_VAV_TOP COOLING COIL 5.17 90239.51 0.800388 1.72 30076.83 0.800388
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.93
PACU_VAV_MID FAN 4.59
PACU_VAV_TOP FAN 5.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000188
PACU_VAV_MID_HEATC_CONTROLLER 0.000196
PACU_VAV_TOP_HEATC_CONTROLLER 0.000192
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002168 0.260199
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.002168 653.00 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 247852.63 247852.63 0.002168
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 8.699 89.459 0.000 0.000 0.000 0.000 98.158 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 8.699 8.069 0.000 0.000 0.000 0.000 16.769 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 8.699 8.070 0.000 0.000 0.000 0.000 16.769 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 8556.149 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8556.149
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 1141.898 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.898
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1803.711 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1803.711
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 1141.823 8.699 161.624 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1141.823


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.8668 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.8532 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.101 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.2365 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.2366 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9196
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9381
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6745
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.383
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.151
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.383
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 4.150
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
39 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
40 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
41 0 21.357363 0.71091016E-01 5.4032014  
42 7 -0.29350128E-12 0.14024199E-14 -0.85558835E-13 0.14795563E-15
43 6 0.27596652E-07 0.24107488E-09 0.63308017E-08 -0.12943591E-12
44 5 -0.18463709E-03 0.20772830E-05 -0.95040309E-04 0.62615177E-08
45 4 0.28572581 0.10171039E-02 0.97375121E-01 -0.32667087E-04
46 3 -7.1391205 0.31676816E-01 -2.3011695 0.28385744E-01
47 2 40.451560 0.11313072 15.110175 -0.32866754
48 1 -80.224209 0.51250674E-01 -29.002757 1.0717664
49 0 46.824341 0.10349526E-02 16.294583  
50 7 -0.29575366E-12 0.13916748E-14 -0.86470795E-13 0.14800413E-15
51 6 0.27759747E-07 0.23770535E-09 0.63667993E-08 -0.13030888E-12
52 5 -0.18546937E-03 0.20460315E-05 -0.95457978E-04 0.62966404E-08
53 4 0.28670590 0.10008406E-02 0.97727300E-01 -0.32804728E-04
54 3 -7.1585449 0.31143840E-01 -2.3069324 0.28480895E-01
55 2 40.515639 0.11114407 15.133849 -0.32938113
56 1 -80.273331 0.50317938E-01 -29.023991 1.0728132
57 0 46.824340 0.10154678E-02 16.294067  
58 7 -0.28281898E-12 0.14025464E-14 -0.82622143E-13 0.19904483E-15
59 6 0.24787521E-07 0.29557932E-09 0.57107416E-08 -0.11447606E-12
60 5 -0.17017937E-03 0.25981591E-05 -0.87765911E-04 0.56555961E-08
61 4 0.26851995 0.12946983E-02 0.91201294E-01 -0.30269387E-04
62 3 -6.7976835 0.40953066E-01 -2.1999024 0.26714449E-01
63 2 39.324706 0.14826279 14.693101 -0.31612152
64 1 -79.359856 0.67961194E-01 -28.628348 1.0533482
65 0 46.824347 0.13883650E-02 16.303898  
66 7 -0.18778705E-08 -0.48456698E-15 0.68415356E-14 -0.90766841E-16
67 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
68 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
69 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
70 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
71 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
72 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
73 0 0.22781756 0.11275910E-04 60.838472  
74 7 -0.17777358E-08 -0.41207670E-15 0.60771148E-14 -0.79247013E-16
75 6 0.66205355E-05 0.45347915E-08 0.31869553E-02 -0.26734852E-04
76 5 -0.47643654E-03 0.26865296E-05 -0.22355891 0.19546881E-02
77 4 0.10961386E-01 0.12229770E-03 4.8267865 -0.45238458E-01
78 3 -0.96263561E-01 0.97262436E-03 -38.005829 0.39848146
79 2 0.34182167 0.16181264E-02 116.45361 -1.4175335
80 1 -0.49337445 0.49308431E-03 -143.88945 2.0487464
81 0 0.24054552 0.11921404E-04 60.838472  
82 7 -0.18778705E-08 -0.48456747E-15 0.68415356E-14 -0.90766840E-16
83 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
84 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
85 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
86 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
87 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
88 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
89 0 0.22781756 0.11275910E-04 60.838472  
90 7 -0.17776120E-08 -0.41258204E-15 0.60425363E-14 -0.82023253E-16
91 6 0.66209765E-05 0.45351028E-08 0.31869540E-02 -0.26734841E-04
92 5 -0.47646911E-03 0.26867147E-05 -0.22355884 0.19546874E-02
93 4 0.10962140E-01 0.12230614E-03 4.8267853 -0.45238446E-01
94 3 -0.96270204E-01 0.97269154E-03 -38.005822 0.39848139
95 2 0.34184528 0.16182383E-02 116.45360 -1.4175333
96 1 -0.49340854 0.49311848E-03 -143.88944 2.0487463
97 0 0.24056214 0.11922214E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.38_SHGC_EAST_0.36 35 1 VerySmooth 2.159 2.159 1.000 0.361    
2 WINDOW_U_0.38_SHGC_SOUTH_0.36 36 1 VerySmooth 2.159 2.159 1.000 0.361    
3 WINDOW_U_0.38_SHGC_WEST_0.36 37 1 VerySmooth 2.159 2.159 1.000 0.361    
4 WINDOW_U_0.38_SHGC_NORTH_0.36 38 1 VerySmooth 2.159 2.159 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.45900E-002 0.27318 0.51781 0.51781 0.39600 0.13802 0.18068 0.00000 0.84000 0.84000 0.11893 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2607E-002
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2676E-002
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.4263E-002
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4324E-002
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6683E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7157E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1452E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1682E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1627
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.9501E-002
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1872
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1164
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1063
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7176E-002
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5786E-002
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7177E-002
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2607E-002
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2679E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.4263E-002
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4327E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6683E-003
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.7175E-003
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1449E-003
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1679E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.2506E-002
26 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2965E-002
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8499E-002
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0038E-002
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.9161E-002
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5140E-002
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3760E-002
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5338E-002
33 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5435E-004
34 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.5712E-004
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.2168E-004
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.2369E-004
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8248E-004
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8314E-004
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8379E-004
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8458E-004
41 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6999E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.7581E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.9147E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9618E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3567E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3902E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1449E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1679E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6186E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6474E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.5656E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0238E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2371E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3569E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5786E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7177E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.7000E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.7586E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.9147E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9617E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3564E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3888E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1452E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1682E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.9356E-002
66 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1328E-002
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.4429E-002
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7911E-002
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.6933E-002
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4057E-002
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3760E-002
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5339E-002
73 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.3663E-004
74 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.4684E-004
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9878E-004
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.1074E-004
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6955E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7264E-004
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.8380E-004
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.8460E-004
81 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1617
82 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1157
83 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1826
84 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1340
85 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1145
86 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.9330E-002
87 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.2201E-002
88 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.4367E-002
89 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.0031E-002
90 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.1558E-002
91 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.6259E-002
92 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.8767E-002
93 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.7507E-002
94 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4162E-002
95 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2761E-002
96 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4738E-002
97 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2316E-002
98 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.4198E-002
99 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.1082E-002
100 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.6853E-002
101 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.7791E-002
102 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9563E-002
103 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2201E-002
104 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4367E-002
105 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.6996E-002
106 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.0015E-002
107 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2340E-002
108 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6764E-002
109 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.5350E-002
110 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3131E-002
111 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.2761E-002
112 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4738E-002
113 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1617
114 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1157
115 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1826
116 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1340
117 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1145
118 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.9324E-002
119 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.2196E-002
120 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.4365E-002
121 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.0031E-002
122 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.1555E-002
123 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.6258E-002
124 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.8764E-002
125 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.7503E-002
126 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4158E-002
127 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2756E-002
128 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4735E-002
129 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2317E-002
130 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.4196E-002
131 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.1083E-002
132 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.6852E-002
133 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.7789E-002
134 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9561E-002
135 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2196E-002
136 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4365E-002
137 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.6996E-002
138 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.0013E-002
139 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2339E-002
140 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6761E-002
141 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.5346E-002
142 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3127E-002
143 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.2756E-002
144 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4736E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 37419.39673 37419.39673 2.73476 2.73476 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 5504.34546 5504.34546 0.23505 0.42469 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 30255.87052 30255.87052 2.20925 2.20925 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 12318.06057 12318.06057 0.52776 0.52776 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 30579.90380 30579.90380 2.25396 2.25396 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 29.29600 8.82133E-003 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 21787.71652 21787.71652 0.93851 0.93851 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 8532.61647 8532.61647 0.62891 0.62891 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 29.29600 8.82133E-003 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 9864.44467 9864.44467 0.42641 0.42641 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 10906.05351 10906.05351 0.80384 0.80384 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 6449.43382 6449.43382 0.27882 0.27882 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 16326.06163 16326.06163 1.20333 1.20333 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 9801.86564 9801.86564 0.42370 0.42370 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 11910.96917 11910.96917 0.87791 0.87791 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 6413.19609 6413.19609 0.27725 0.27725 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 6887.49633 6887.49633 0.50765 0.50765 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 7381.29781 7381.29781 0.31876 0.31876 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 9061.13496 9061.13496 0.66786 0.66786 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 22.36267 8.81033E-003 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 4891.90111 4891.90111 0.21130 0.21130 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 13462.25273 13462.25273 0.99225 0.99225 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 29.31333 8.82136E-003 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 7322.06177 7322.06177 0.31620 0.31620 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 10003.54038 10003.54038 0.73732 0.73732 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 26.90400 8.81750E-003 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 4853.16753 4853.16753 0.20962 0.20962 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 7559.36433 7559.36433 0.55717 0.55717 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 7691.85711 7691.85711 0.33220 0.33220 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 10909.68718 10909.68718 0.80411 0.80411 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 23.35067 8.81188E-003 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 5068.18791 5068.18791 0.21893 0.21893 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 15188.74090 15188.74090 1.11950 1.11950 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 7629.14038 7629.14038 0.32948 0.32948 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 11138.21405 11138.21405 0.82095 0.82095 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 5033.45476 5033.45476 0.21742 0.21742 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 73504.50 4.92644 4.92644 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 24013.17 1.48057 1.48057 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00
3 PACU_VAV_MID Cooling Sensible 69008.08 4.58982 4.58982 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 PACU_VAV_MID Heating Sensible 24229.77 1.62579 1.62579 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00
5 PACU_VAV_TOP Cooling Sensible 76659.96 5.16568 5.16568 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 24066.21 2.34469 2.34469 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.73476
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27405
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28500
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.77941
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.73079
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.39027E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.15830E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.77941
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13240.09501
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.15830E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 287.10066
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.20925
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33924
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34600
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.76440
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90463
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12311E-003
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74136E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.76440
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19904.87001
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74136E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 479.12793
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.25396
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33251
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35000
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.78889
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88668
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14585E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.72099E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93851
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 31102.56697
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.72099E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 821.30966
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.62891
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25122
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26400
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16603
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66991
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.51662E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.23304E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42641
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14094.42576
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.23304E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 371.73587
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80384
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12443
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16077
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33181
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06196E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.06194E-005
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27882
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9215.29028
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.06194E-005
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 243.04247
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20333
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13130
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24067
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35012
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90184E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22521E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42370
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14004.90203
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22521E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 369.37697
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.87791
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11392
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17558
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30380
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.34431E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.01659E-005
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27725
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9163.45099
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.01659E-005
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 241.67652
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50765
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31122
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32300
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16397
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82992
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22422E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.22354E-005
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31876
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10543.07661
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.22354E-005
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 278.15246
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.66786
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14977
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13357
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39938
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.54397E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.11323E-005
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21130
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6987.79282
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.11323E-005
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 184.34493
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.99225
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15923
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19845
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42460
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.39283E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.14940E-005
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31620
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10458.32452
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.14940E-005
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 275.91917
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.73732
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13565
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.14746
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36173
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.80876E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.06474E-005
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20962
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6932.37578
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.06474E-005
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 182.88463
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.55717
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28356
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28900
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16102
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75616
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34364E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.61146E-005
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33220
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10986.49035
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.61146E-005
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 289.83742
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80411
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12439
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16082
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33170
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06298E-003
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.33338E-005
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21893
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
180 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7239.44298
181 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.33338E-005
182 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 190.97662
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11950
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14113
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22390
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37634
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.69970E-003
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.53295E-005
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32948
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
194 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10896.75111
195 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.53295E-005
196 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 287.47265
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.82095
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12183
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.16419
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32488
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.12735E-003
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.28990E-005
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21742
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
208 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7189.74320
209 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.28990E-005
210 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 189.66694
211 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.81992
212 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.42286
213 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 5.63984
214 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.48057
215 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.92644
216 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.92644
217 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
218 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.30053
219 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.75549
220 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.47433
221 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.51098
222 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.62579
223 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.58982
224 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.58982
225 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
226 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.35422
227 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.88397
228 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.53193
229 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.76794
230 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.34469
231 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 5.16568
232 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 5.16568
233 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
234 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.45390
235 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.92644
236 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.58982
237 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 5.16568
238 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.92644
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.92644
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 86560.51092
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80037
242 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.64198
243 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 28850.61829
244 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80037
245 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 21468.83329
246 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.87819E-004
247 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 361.65095
248 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.92644
249 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.87819E-004
250 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.58982
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.58982
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 81291.89586
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80062
254 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.52979
255 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 27094.58889
256 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80062
257 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 22456.55131
258 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.96460E-004
259 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 374.86087
260 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.58982
261 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.96460E-004
262 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.16568
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.16568
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 90239.51013
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80039
266 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.72172
267 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 30076.82873
268 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80039
269 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 21967.64751
270 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.92183E-004
271 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 370.72332
272 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 5.16568
273 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.92183E-004
274 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.16832E-003
275 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.26020
276 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.16832E-003
277 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 653.00365
278 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
279 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 247852.63057
280 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 247852.63000
281 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.16832E-003
282 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
283 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
284 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
285 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
286 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 12549.21
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 18856.36
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 29475.28
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 13354.01
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 8731.13
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 13269.20
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 8682.03
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 9989.77
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6621.00
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9909.48
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 6568.50
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 10409.82
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 6859.39
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 10324.81
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 6812.31
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 17317.12
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 17788.11
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 17783.34


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 85305.08 291073.02 11.74 3.04 3.36 3.53 3.74 10.37 11.45 12.05 12.75 5.6167 4.4544 2.9895 1.2186
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 80141.31 273453.51 11.76 3.04 3.36 3.54 3.74 10.39 11.47 12.07 12.77 5.2329 4.1530 2.7879 1.1317
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 88907.63 303365.44 11.72 3.04 3.35 3.53 3.73 10.36 11.44 12.03 12.73 5.8895 4.6693 3.1331 1.2802


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.237 0.224   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.237 0.224   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_NORTH_0.36 N/A 2.159 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_EAST_0.36 N/A 2.159 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_SOUTH_0.36 N/A 2.159 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.38_SHGC_WEST_0.36 N/A 2.159 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 7.7860076767E-002 6.6843252900E-002 Pass Pass 0.2078971329 0.3914165945 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1187497699 6.3865940195E-002 Pass Pass 0.4225415435 0.4715287279 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.7667125793E-002 3.8239238714E-002 Pass Pass 0.3256653029 0.4555641849 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.0828430617E-002 4.4678894264E-002 Pass Pass 0.2144649598 0.3893901997 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 2.7793796566E-002 1.9274542454E-002 Pass Pass 0.6531351820 1.3783849185 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 1.5548043727E-002 1.6254582965E-002 Pass Pass 10.7161802484 24.7701901086 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2253997918 0.2092203525 Pass Pass 14.0060236464 31.2545716827 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2280936681 0.2171476077 Pass Pass 10.8385632121 23.9428024429 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2128195498 0.2033933794 Pass Pass 10.8680768027 23.9563553206 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2313879202 0.2199392856 Pass Pass 10.2439062831 22.5577761151 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.1009977966 0.1307005496 Pass Pass 1.6474778138 3.7690987398 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1130672631 0.1487364099 Pass Pass 1.3680999350 3.0635003123 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 9.7460966980E-002 0.1237239597 Pass Pass 1.6748432056 3.8625495568 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1154570790 0.1518894596 Pass Pass 1.2990985839 2.8893780810 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1279426646 0.1495914996 Pass Pass 2.2781843925 4.5079158881 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1355934113 0.1603968395 Pass Pass 1.8021794351 3.4569631712 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1260789142 0.1460870999 Pass Pass 2.1056594028 4.2089866633 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1379599705 0.1631006032 Pass Pass 1.7586876073 3.2639353078 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3038.44 75.87 0.00 2463.44 453.10 6030.86



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.228 0.237 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.228 0.237 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_NORTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_EAST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_SOUTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_WEST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.38_SHGC_NORTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.38_SHGC_EAST_0.36   41.85 0.00 0.00 41.85 41.85 2.159 0.361 0.397             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.38_SHGC_EAST_0.36   1.65 0.00 0.00 1.65 1.65 2.159 0.361 0.397             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.38_SHGC_SOUTH_0.36   21.75 0.00 0.00 21.75 21.75 2.159 0.361 0.397             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.38_SHGC_WEST_0.36   41.85 0.00 0.00 41.85 41.85 2.159 0.361 0.397             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.38_SHGC_WEST_0.36   1.65 0.00 0.00 1.65 1.65 2.159 0.361 0.397             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.38_SHGC_NORTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.38_SHGC_EAST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.38_SHGC_SOUTH_0.36   65.26 0.00 0.00 65.26 65.26 2.159 0.361 0.397             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.38_SHGC_WEST_0.36   43.51 0.00 0.00 43.51 43.51 2.159 0.361 0.397             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.159 0.361 0.397                      
North Total or Average             195.79 2.159 0.361 0.397                      
Non-North Total or Average             456.84 2.159 0.361 0.397                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 8.6994 983.54 8556.15 LightsWired LTG_SCH_OFFICE 47.17 168.00 44.78 0.0000 Y 71.93
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 27.09 0.0000 Y 9.17
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.60 0.0000 Y 5.70
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.18 0.0000 Y 8.86
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.58 0.0000 Y 5.70
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.96 0.0000 Y 9.13
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.52 0.0000 Y 5.68
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.11 0.0000 Y 8.84
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.49 0.0000 Y 5.68
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 27.09 0.0000 Y 9.17
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 8.6994 131.26 1141.90 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.60 0.0000 Y 5.70
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 8.6994 207.34 1803.71 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.18 0.0000 Y 8.86
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 8.6994 131.25 1141.82 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.58 0.0000 Y 5.70
Interior Lighting Total       8.6994 4982.19 43341.88               303.98


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.38 1141.90 437.92
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Stepped 0.14 1141.90 159.29
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.38 1803.71 691.72
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Stepped 0.14 1803.71 251.62
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.38 1141.82 437.89
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Stepped 0.14 1141.82 159.28


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   42.59 42.59 4.51
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.55 63.07 4.83
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.55 47.80 42.30
Exterior Lighting Total 5686.19           51.64



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 247852.63 0.80        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   86560.51 69280.80 17279.71 0.80 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   81291.90 65084.03 16207.87 0.80 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   90239.51 72226.61 18012.90 0.80 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   85305.1 3.04 10.37 N/A N/A 11.74
PACU_VAV_MID COOLING COIL   80141.3 3.04 10.39 N/A N/A 11.76
PACU_VAV_TOP COOLING COIL   88907.6 3.04 10.36 N/A N/A 11.72
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 13240.10 12549.21 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 19904.87 18856.36 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 31102.57 29475.28 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 14094.43 13354.01 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9215.29 8731.13 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 14004.90 13269.20 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9163.45 8682.03 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 10543.08 9989.77 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 6987.79 6621.00 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 10458.32 9909.48 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 6932.38 6568.50 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 10986.49 10409.82 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 7239.44 6859.39 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 10896.75 10324.81 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 7189.74 6812.31 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 21468.83 17317.12 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 22456.55 17788.11 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 21967.65 17783.34 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.93 10784.04 2189.01 1.00 1.13 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 4.59 10047.16 2189.01 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 5.17 11234.78 2174.89 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002168 653.00 301156.09 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 85305.08 3.04 10.37 11.74 5.6167 3.36 11.45 4.4544 3.53 12.05 2.9895 3.74 12.75 1.2186
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 80141.31 3.04 10.39 11.76 5.2329 3.36 11.47 4.1530 3.54 12.07 2.7879 3.74 12.77 1.1317
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 88907.63 3.04 10.36 11.72 5.8895 3.35 11.44 4.6693 3.53 12.03 3.1331 3.73 12.73 1.2802
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 37419.40 37419.40 38.05 2.735 2.735 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00883 21.70 0.00881 0.425 0.00
CORE_MID 30255.87 30255.87 30.76 2.209 2.209 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00890 21.70 0.00881 0.425 0.00
CORE_TOP 30579.90 30579.90 31.09 2.254 2.254 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00889 29.30 0.00882 0.425 0.00
PERIMETER_TOP_ZN_3 8532.62 8532.62 41.15 0.629 0.629 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00880 29.30 0.00882 0.090 0.00
PERIMETER_TOP_ZN_2 10906.05 10906.05 83.09 0.804 0.804 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 24.00 24.00 0.00865 23.68 0.00881 0.057 0.00
PERIMETER_TOP_ZN_1 16326.06 16326.06 78.74 1.203 1.203 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00866 29.14 0.00882 0.090 0.00
PERIMETER_TOP_ZN_4 11910.97 11910.97 90.75 0.878 0.878 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00864 27.94 0.00882 0.057 0.00
PERIMETER_BOT_ZN_3 6887.50 6887.50 33.22 0.508 0.508 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00887 29.40 0.00882 0.090 0.00
PERIMETER_BOT_ZN_2 9061.13 9061.13 69.03 0.668 0.668 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 24.00 24.00 0.00868 22.36 0.00881 0.057 0.00
PERIMETER_BOT_ZN_1 13462.25 13462.25 64.93 0.992 0.992 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00869 29.31 0.00882 0.090 0.00
PERIMETER_BOT_ZN_4 10003.54 10003.54 76.22 0.737 0.737 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.00 24.00 0.00866 26.90 0.00882 0.057 0.00
PERIMETER_MID_ZN_3 7559.36 7559.36 36.46 0.557 0.557 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00883 29.40 0.00882 0.090 0.00
PERIMETER_MID_ZN_2 10909.69 10909.69 83.11 0.804 0.804 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00865 23.35 0.00881 0.057 0.00
PERIMETER_MID_ZN_1 15188.74 15188.74 73.26 1.120 1.120 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00867 29.05 0.00882 0.090 0.00
PERIMETER_MID_ZN_4 11138.21 11138.21 84.86 0.821 0.821 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00864 27.94 0.00882 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 5504.35 5504.35 5.60 0.235 0.425 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_MID 12318.06 12318.06 12.52 0.528 0.528 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_TOP 21787.72 21787.72 22.15 0.939 0.939 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
PERIMETER_TOP_ZN_3 9864.44 9864.44 47.58 0.426 0.426 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_2 6449.43 6449.43 49.13 0.279 0.279 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
PERIMETER_TOP_ZN_1 9801.87 9801.87 47.27 0.424 0.424 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_4 6413.20 6413.20 48.86 0.277 0.277 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_3 7381.30 7381.30 35.60 0.319 0.319 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_2 4891.90 4891.90 37.27 0.211 0.211 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00773 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_1 7322.06 7322.06 35.31 0.316 0.316 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00771 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_4 4853.17 4853.17 36.98 0.210 0.210 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00773 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_3 7691.86 7691.86 37.10 0.332 0.332 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00766 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_2 5068.19 5068.19 38.61 0.219 0.219 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00767 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_1 7629.14 7629.14 36.80 0.329 0.329 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00765 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_4 5033.45 5033.45 38.35 0.217 0.217 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00767 -4.20 0.00269 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.93 4.93 1.48 1.48 4.9264 1.4806 4.9264 0.3005 0.3000
PACU_VAV_MID 4.59 4.59 1.63 1.63 4.5898 1.6258 4.5898 0.3542 0.3000
PACU_VAV_TOP 5.17 5.17 2.34 2.34 5.1657 2.3447 5.1657 0.4539 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 13240.095 13240.095 0.779406 0.00011583 287.101 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13240.10 13240.10 0.779406 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 5504.35 0.00 13286.20 13286.20
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 19904.870 19904.870 0.764400 0.00017414 479.128 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 19904.87 19904.87 0.764400 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 12318.06 0.00 19969.34 19969.34
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 31102.567 31102.567 0.938507 0.00027210 821.310 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 31102.57 31102.57 0.938507 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 21787.72 0.00 31212.18 31212.18
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 14094.426 14094.426 0.426413 0.00012330 371.736 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14094.43 14094.43 0.426413 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777221 49.5489 9864.44 0.00 14140.87 14140.87
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 9215.290 9215.290 0.278819 0.00008062 243.042 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9215.29 9215.29 0.278819 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777208 49.5482 6449.43 0.00 9245.60 9245.60
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 14004.902 14004.902 0.423699 0.00012252 369.377 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14004.90 14004.90 0.423699 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00776985 49.5341 9801.87 0.00 14051.07 14051.07
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 9163.451 9163.451 0.277248 0.00008017 241.677 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9163.45 9163.45 0.277248 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00777009 49.5357 6413.20 0.00 9193.60 9193.60
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 10543.077 10543.077 0.318765 0.00009224 278.152 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10543.08 10543.08 0.318765 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00771905 49.2144 7381.30 0.00 10578.41 10578.41
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 6987.793 6987.793 0.211298 0.00006113 184.345 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6987.79 6987.79 0.211298 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00773231 49.2978 4891.90 0.00 7011.14 7011.14
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 10458.325 10458.325 0.316196 0.00009149 275.919 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10458.32 10458.32 0.316196 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00771400 49.1826 7322.06 0.00 10493.40 10493.40
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 6932.376 6932.376 0.209618 0.00006065 182.885 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6932.38 6932.38 0.209618 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00772759 49.2682 4853.17 0.00 6955.55 6955.55
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 10986.490 10986.490 0.332205 0.00009611 289.837 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10986.49 10986.49 0.332205 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00765803 48.8307 7691.86 0.00 11023.22 11023.22
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 7239.443 7239.443 0.218926 0.00006333 190.977 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7239.44 7239.44 0.218926 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00767256 48.9222 5068.19 0.00 7263.58 7263.58
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 10896.751 10896.751 0.329484 0.00009533 287.473 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10896.75 10896.75 0.329484 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00765148 48.7895 7629.14 0.00 10933.20 10933.20
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 7189.743 7189.743 0.217419 0.00006290 189.667 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7189.74 7189.74 0.217419 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00766696 48.8870 5033.45 0.00 7213.72 7213.72
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 86560.511 69280.801 4.926443 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 87530.99 82957.15 4.926443 25.31 16.96 0.00880760 10.99 10.99 0.00850000 29.40 0.00882150 18.34 24.2603 24.00 0.00880314 46.6930 66838.40 0.00 89255.51 69716.73
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 21468.833 21468.833 1.477933 0.00018782 361.651 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21468.83 21468.83 1.477933 0.62 0.15 0.00368333 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 80.8677 21.00 0.00784263 49.9905 21257.37 0.00 20957.20 20957.20
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 81291.896 65084.026 4.589817 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 82270.28 77776.74 4.589817 25.41 17.01 0.00882453 10.99 10.99 0.00850000 29.40 0.00882150 18.34 26.0396 24.00 0.00882559 46.8104 62271.37 0.00 83822.86 65513.69
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 22456.551 22456.551 1.376945 0.00019646 374.861 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 22456.55 22456.55 1.376945 -0.87 -1.17 0.00336664 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 86.7987 21.00 0.00779566 49.6952 25098.99 0.00 21524.92 21524.92
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 90239.510 72226.606 5.165683 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 91205.38 86573.69 5.165683 25.25 16.93 0.00879720 11.01 11.01 0.00850000 29.40 0.00882150 18.34 23.1367 24.00 0.00878988 46.6236 70043.45 0.00 93049.05 72684.59
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 21967.648 21967.648 1.549705 0.00019218 370.723 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:20:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21967.65 21967.65 1.549705 0.92 0.54 0.00383446 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 77.1224 19.60 0.00764728 53.1670 28223.09 0.00 21522.16 21522.16



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 13240.095 13240.095 0.779406 0.00011583 287.101 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 5.2365 5.341922 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13240.10 13240.10 1.0000 0.92514795 0.779406 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.11581831 60.00 32.22 27.78 0.000 13240.10 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.67 0.00800000 21.00 0.00800000 50.9797 5504.35 0.00 13286.20 13286.20 0.92514795 12.80 11.60 0.00800000 33059.8 26.88 16.98 0.00800000 47421.0
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 19904.870 19904.870 0.764400 0.00017414 479.128 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 7.8725 8.030929 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 19904.87 19904.87 1.0000 0.90733563 0.764400 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.17411872 60.00 32.22 27.78 0.000 19904.87 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 50.9797 12318.06 0.00 19969.34 19969.34 0.90733563 12.80 11.60 0.00800000 33059.8 34.38 19.46 0.00800000 55068.6
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 31102.567 31102.567 0.938507 0.00027210 821.310 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 12.3012 12.548815 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 31102.57 31102.57 1.0000 1.11399868 0.938507 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.27207107 60.00 32.22 27.78 0.000 31102.57 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.9797 21787.72 0.00 31212.18 31212.18 1.11399868 12.80 11.60 0.00800000 33059.8 40.28 21.26 0.00800000 61078.0
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 14094.426 14094.426 0.426413 0.00012330 371.736 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 5.5744 5.686615 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14094.43 14094.43 1.0000 0.50614887 0.426413 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.12329161 60.00 32.22 27.78 0.000 14094.43 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777221 21.00 0.00777221 49.5489 9864.44 0.00 14140.87 14140.87 0.50614887 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 9215.290 9215.290 0.278819 0.00008062 243.042 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 3.6447 3.718052 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9215.29 9215.29 1.0000 0.33095609 0.278819 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.08061116 60.00 32.22 27.78 0.000 9215.29 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777208 21.00 0.00777208 49.5482 6449.43 0.00 9245.60 9245.60 0.33095609 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60995.9
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 14004.902 14004.902 0.423699 0.00012252 369.377 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 5.5390 5.650496 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14004.90 14004.90 1.0000 0.50292723 0.423699 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.12250849 60.00 32.22 27.78 0.000 14004.90 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00776985 21.00 0.00776985 49.5341 9801.87 0.00 14051.07 14051.07 0.50292723 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 9163.451 9163.451 0.277248 0.00008017 241.677 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 3.6242 3.697137 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9163.45 9163.45 1.0000 0.32909061 0.277248 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.08015769 60.00 32.22 27.78 0.000 9163.45 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00777009 21.00 0.00777009 49.5357 6413.20 0.00 9193.60 9193.60 0.32909061 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.2
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 10543.077 10543.077 0.318765 0.00009224 278.152 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 4.1698 4.253768 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10543.08 10543.08 1.0000 0.37837074 0.318765 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09222602 60.00 32.22 27.78 0.000 10543.08 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00771905 21.00 0.00771905 49.2144 7381.30 0.00 10578.41 10578.41 0.37837074 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61017.6
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 6987.793 6987.793 0.211298 0.00006113 184.345 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 2.7637 2.819334 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6987.79 6987.79 1.0000 0.25080918 0.211298 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06112602 60.00 32.22 27.78 0.000 6987.79 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00773231 21.00 0.00773231 49.2978 4891.90 0.00 7011.14 7011.14 0.25080918 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.9
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 10458.325 10458.325 0.316196 0.00009149 275.919 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 4.1363 4.219574 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10458.32 10458.32 1.0000 0.37532119 0.316196 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09148465 60.00 32.22 27.78 0.000 10458.32 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00771400 21.00 0.00771400 49.1826 7322.06 0.00 10493.40 10493.40 0.37532119 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61018.3
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 6932.376 6932.376 0.209618 0.00006065 182.885 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 2.7418 2.796975 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6932.38 6932.38 1.0000 0.24881519 0.209618 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06064126 60.00 32.22 27.78 0.000 6932.38 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00772759 21.00 0.00772759 49.2682 4853.17 0.00 6955.55 6955.55 0.24881519 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.5
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 10986.490 10986.490 0.332205 0.00009611 289.837 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 4.3452 4.432670 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10986.49 10986.49 1.0000 0.39432379 0.332205 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09610481 60.00 32.22 27.78 0.000 10986.49 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00765803 21.00 0.00765803 48.8307 7691.86 0.00 11023.22 11023.22 0.39432379 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.6
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 7239.443 7239.443 0.218926 0.00006333 190.977 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 2.8632 2.920866 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7239.44 7239.44 1.0000 0.25986259 0.218926 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06332734 60.00 32.22 27.78 0.000 7239.44 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00767256 21.00 0.00767256 48.9222 5068.19 0.00 7263.58 7263.58 0.25986259 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.4
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 10896.751 10896.751 0.329484 0.00009533 287.473 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 4.3097 4.396464 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10896.75 10896.75 1.0000 0.39109498 0.329484 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09531981 60.00 32.22 27.78 0.000 10896.75 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00765148 21.00 0.00765148 48.7895 7629.14 0.00 10933.20 10933.20 0.39109498 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61015.2
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 7189.743 7189.743 0.217419 0.00006290 189.667 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 2.8436 2.900814 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7189.74 7189.74 1.0000 0.25807444 0.217419 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06289259 60.00 32.22 27.78 0.000 7189.74 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00766696 21.00 0.00766696 48.8870 5033.45 0.00 7213.72 7213.72 0.25807444 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.9
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 86560.511 69280.801 4.926443 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2129 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 4.926443 5.84764188   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 87530.99 82957.15 1.0112 5.84764188 4.926443 25.31 16.96 0.00880760 47873.3 10.99 10.99 0.00850000 32479.1 -999.0 -999.00 -999.00 -999.00 10784.037 76746.95 29.40 0.00882150 18.34 1.19517000 24.2603 24.00 0.00880314 24.00 0.00880314 46.6930 66838.40 0.00 89255.51 69716.73 5.61670423 26.67 19.44 0.01118466 55322.4 14.53 14.07 0.00982074 39431.3
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 21468.833 21468.833 1.477933 0.00018782 361.651 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 4.926443 5.84764188   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 8.4910 8.661935 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 21468.83 21468.83 1.0000 1.75429256 1.477933 0.62 0.15 0.00368333 9840.3 12.80 11.47 0.00800000 33059.8 0.18779956 60.00 32.22 27.78 0.000 21468.83 -4.20 0.00269032 -4.20 1.19517000 80.8677 21.00 0.00788055 21.00 0.00784263 49.9905 21257.37 0.00 20957.20 20957.20 1.75429256 2.80 1.50 0.00368333 12044.5 14.61 7.68 0.00368333 23990.8
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 81291.896 65084.026 4.589817 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2444 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 4.589817 5.44807105   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 82270.28 77776.74 1.0120 5.44807105 4.589817 25.41 17.01 0.00882453 48014.6 10.99 10.99 0.00850000 32479.1 -999.0 -999.00 -999.00 -999.00 10047.161 72223.12 29.40 0.00882150 18.34 1.19517000 26.0396 24.00 0.00882559 24.00 0.00882559 46.8104 62271.37 0.00 83822.86 65513.69 5.23291343 26.67 19.44 0.01118466 55322.4 14.43 14.02 0.00981284 39304.0
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 22456.551 22456.551 1.376945 0.00019646 374.861 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 4.589817 5.44807105   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 8.8817 9.060445 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 22:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 22456.55 22456.55 1.0000 1.63442132 1.376945 -0.87 -1.17 0.00336664 7536.8 12.80 11.47 0.00800000 33059.8 0.19643967 60.00 32.22 27.78 0.000 22456.55 -4.20 0.00269032 -4.20 1.19517000 86.7987 21.00 0.00781348 21.00 0.00779566 49.6952 25098.99 0.00 21524.92 21524.92 1.63442132 2.80 1.05 0.00336664 11250.9 15.83 7.89 0.00336664 24420.6
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 90239.510 72226.606 5.165683 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1936 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 5.165683 6.13161833   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 91205.38 86573.69 1.0107 6.13161833 5.165683 25.25 16.93 0.00879720 47785.6 11.01 11.01 0.00850000 32490.9 -999.0 -999.00 -999.00 -999.00 11234.784 79970.60 29.40 0.00882150 18.34 1.19517000 23.1367 24.00 0.00878988 24.00 0.00878988 46.6236 70043.45 0.00 93049.05 72684.59 5.88946576 26.67 19.44 0.01118466 55322.4 14.60 14.10 0.00982894 39523.2
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 21967.648 21967.648 1.549705 0.00019218 370.723 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 5.165683 6.13161833   4197.9300 999.8980 2.16810174 54.44 82.22 27.78 252840.76 8.6883 8.863189 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:20:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 21967.65 21967.65 1.0000 1.83948550 1.549705 0.92 0.54 0.00383446 10516.2 12.80 11.47 0.00800000 33059.8 0.19216296 60.00 32.22 27.78 0.000 21967.65 -4.20 0.00269032 -4.20 1.19517000 77.1224 18.16 0.00769149 19.60 0.00764728 53.1670 28223.09 0.00 21522.16 21522.16 1.83948550 2.80 1.71 0.00383446 12423.3 14.36 7.74 0.00383446 24123.4



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialDryBulb 0.00 4.93 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialDryBulb 0.00 4.59 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialDryBulb 0.00 5.17 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 1978.17 2105.67 32.00
CORE_MID 1203.67 3499.67 168.83
CORE_TOP 1416.33 4098.50 634.50
PERIMETER_TOP_ZN_3 2214.17 4430.00 1472.00
PERIMETER_TOP_ZN_2 2550.50 4162.50 1394.83
PERIMETER_TOP_ZN_1 2457.17 4006.50 1179.33
PERIMETER_TOP_ZN_4 2504.00 4419.67 1472.83
PERIMETER_BOT_ZN_3 1642.00 4481.50 1026.17
PERIMETER_BOT_ZN_2 2155.50 3926.83 925.50
PERIMETER_BOT_ZN_1 2056.33 4089.50 878.50
PERIMETER_BOT_ZN_4 2179.50 4048.17 961.00
PERIMETER_MID_ZN_3 1813.67 4102.33 955.17
PERIMETER_MID_ZN_2 1853.17 3477.67 884.67
PERIMETER_MID_ZN_1 2165.67 3638.67 723.50
PERIMETER_MID_ZN_4 2154.33 4116.83 965.33
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4150.00 4930.50 1700.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 2.17 0.00 2.17 0.00
CORE_MID 3.17 0.00 3.17 0.00
CORE_TOP 5.50 0.00 5.33 0.00
PERIMETER_TOP_ZN_3 19.17 0.00 17.17 0.00
PERIMETER_TOP_ZN_2 7.50 8.17 6.50 8.17
PERIMETER_TOP_ZN_1 6.17 10.00 5.50 10.00
PERIMETER_TOP_ZN_4 7.00 16.00 6.17 9.00
PERIMETER_BOT_ZN_3 4.67 0.00 4.67 0.00
PERIMETER_BOT_ZN_2 3.17 6.00 3.00 6.00
PERIMETER_BOT_ZN_1 297.00 6.17 297.00 6.17
PERIMETER_BOT_ZN_4 3.33 10.83 2.83 4.50
PERIMETER_MID_ZN_3 4.83 0.00 4.67 0.00
PERIMETER_MID_ZN_2 2.50 9.17 2.33 9.17
PERIMETER_MID_ZN_1 2.17 11.17 2.17 11.17
PERIMETER_MID_ZN_4 2.50 16.00 2.33 8.83
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 309.33 59.00 306.50 45.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.49 52.94 2698.04 1.044 0.000 0.000 0.000
CORE_MID 21.49 52.94 2698.04 0.731 0.000 0.000 0.000
CORE_TOP 21.49 52.94 2698.04 0.712 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.53 11.16 568.77 0.753 0.035 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 1.256 0.037 0.000 0.000
PERIMETER_TOP_ZN_1 4.53 11.16 568.77 1.308 0.035 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 1.329 0.037 0.000 0.000
PERIMETER_BOT_ZN_3 4.53 11.16 568.77 0.690 0.019 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 1.085 0.020 0.000 0.000
PERIMETER_BOT_ZN_1 4.53 11.16 568.77 1.051 0.829 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 1.123 0.020 0.000 0.000
PERIMETER_MID_ZN_3 4.53 11.16 568.77 0.758 0.030 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 1.169 0.033 0.000 0.000
PERIMETER_MID_ZN_1 4.53 11.16 568.77 1.291 0.030 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 1.287 0.031 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.49 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.87 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.51 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.53 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.87 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.49 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.49 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.49 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.87 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.87 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.51 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.53 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.87 7.06 360.05 131.25 0.0000 0.057
Total Facility   108.48 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 16458540.79 0.00 16458540.79 0.00 16458540.79 13393058.27 5062.81 51.61 3645.58 40.46
CORE_MID 11570592.32 0.00 11570592.32 0.00 11570592.32 13393058.27 5670.34 53.59 3036.06 44.72
CORE_TOP 11309089.87 0.00 11309089.87 0.00 11309089.87 13393058.27 5730.11 42.53 2987.36 45.17
PERIMETER_TOP_ZN_3 2519989.07 0.00 2519989.07 242662.85 2762651.92 2823374.22 5623.15 55.89 3080.96 45.17
PERIMETER_TOP_ZN_2 2660137.39 0.00 2660137.39 161774.26 2821911.65 1787429.43 4075.95 3.37 4680.68 45.17
PERIMETER_TOP_ZN_1 4369965.89 0.00 4369965.89 242662.85 4612628.75 2823374.22 4083.79 2.63 4673.57 45.17
PERIMETER_TOP_ZN_4 2824836.27 0.00 2824836.27 161774.26 2986610.53 1787312.18 4068.99 5.79 4685.22 45.17
PERIMETER_BOT_ZN_3 2306299.91 0.00 2306299.91 129022.55 2435322.46 2823374.22 5499.81 60.84 3199.36 40.46
PERIMETER_BOT_ZN_2 2291840.65 0.00 2291840.65 86014.52 2377855.16 1787429.43 4084.34 6.12 4669.54 40.46
PERIMETER_BOT_ZN_1 3514702.71 0.00 3514702.71 2835943.55 6350646.26 2823374.22 4097.06 18.69 4644.26 40.46
PERIMETER_BOT_ZN_4 2378846.11 0.00 2378846.11 86014.52 2464860.62 1787312.18 4064.21 5.10 4690.69 40.46
PERIMETER_MID_ZN_3 2531944.02 0.00 2531944.02 201998.19 2733942.21 2823374.22 5566.03 63.63 3130.34 44.72
PERIMETER_MID_ZN_2 2690634.66 0.00 2690634.66 134664.65 2825299.31 1787429.43 4022.26 3.66 4734.08 953.72
PERIMETER_MID_ZN_1 4305107.14 0.00 4305107.14 201998.19 4507105.32 2823374.22 4053.55 4.17 4702.28 44.72
PERIMETER_MID_ZN_4 2729401.73 0.00 2729401.73 134664.65 2864066.38 1787312.18 4022.30 6.15 4731.55 44.72
Total Facility 74461928.54 0.00 74461928.54 4619195.04 79081123.58 67843644.98 5856.31 252.74 4795.21 978.42


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.7652 0.0000 0.7652 0.0000 0.7652 0.4247 2275.43 51.61 3615.96
CORE_MID 0.5365 0.0000 0.5365 0.0000 0.5365 0.4247 2886.44 53.59 3002.97
CORE_TOP 0.5237 0.0000 0.5237 0.0000 0.5237 0.4247 2949.56 42.53 2950.91
PERIMETER_TOP_ZN_3 0.1168 0.0000 0.1168 0.0055 0.1223 0.0895 2842.59 55.89 3044.52
PERIMETER_TOP_ZN_2 0.1233 0.0000 0.1233 0.0037 0.1270 0.0567 1295.39 3.37 4644.24
PERIMETER_TOP_ZN_1 0.2028 0.0000 0.2028 0.0055 0.2083 0.0895 1303.24 2.63 4637.13
PERIMETER_TOP_ZN_4 0.1305 0.0000 0.1305 0.0037 0.1342 0.0567 1288.44 5.79 4648.78
PERIMETER_BOT_ZN_3 0.1069 0.0000 0.1069 0.0029 0.1099 0.0895 2712.43 60.84 3169.73
PERIMETER_BOT_ZN_2 0.1064 0.0000 0.1064 0.0020 0.1084 0.0567 1296.98 6.12 4639.90
PERIMETER_BOT_ZN_1 0.1632 0.0000 0.1632 0.1295 0.2927 0.0895 1309.68 18.69 4614.63
PERIMETER_BOT_ZN_4 0.1102 0.0000 0.1102 0.0020 0.1122 0.0567 1276.86 5.10 4661.04
PERIMETER_MID_ZN_3 0.1174 0.0000 0.1174 0.0046 0.1220 0.0895 2782.12 63.63 3097.24
PERIMETER_MID_ZN_2 0.1147 0.0000 0.1147 0.0033 0.1180 0.0567 1238.40 3.66 3791.94
PERIMETER_MID_ZN_1 0.2000 0.0000 0.2000 0.0046 0.2045 0.0895 1269.65 4.17 4669.18
PERIMETER_MID_ZN_4 0.1263 0.0000 0.1263 0.0031 0.1294 0.0567 1238.44 6.15 4698.41
Total Facility 3.4441 0.0000 3.4441 0.1702 3.6142 2.1513 3059.51 252.74 4748.85


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 37971449.18 0.00 37971449.18 22614548.33 4039.72 4.44 4715.83 40.46
PACU_VAV_MID 33571940.93 0.00 33571940.93 22614548.33 4019.22 4.03 4736.75 44.72
PACU_VAV_TOP 33369529.64 0.00 33369529.64 22614548.33 4073.74 1.70 4684.56 45.05


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.7641 0.0000 1.7641 0.7171 1252.35 4.44 4686.21
PACU_VAV_MID 1.5570 0.0000 1.5570 0.7171 1235.31 4.03 4703.66
PACU_VAV_TOP 1.5457 0.0000 1.5457 0.7171 1293.19 1.70 4648.12


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 0.00 3692.42 0.00 0.00 0.00 1076.70 0.00 0.00 0.00
PACU_VAV_MID 0.00 0.00 3393.67 0.00 0.00 0.00 1413.22 0.00 0.00 0.00
PACU_VAV_TOP 0.00 0.00 3344.61 0.00 0.00 0.00 1454.74 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 0.0000 2.5469 0.0000 0.0000 0.0000 1.1017 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 0.0000 2.2997 0.0000 0.0000 0.0000 1.0996 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 0.0000 2.3021 0.0000 0.0000 0.0000 1.0945 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 982
Defaulted Fields 577
Fields with Defaults 2420
Autosized Fields 193
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
Electricity:Building 1023.67 13465.67 07-MAY-17:20 74341.76 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 322.35 5243.28 01-JAN-00:10 20463.73 02-JAN-08:10
Electricity:SpaceType:GENERAL 1023.67 13465.67 07-MAY-17:20 74341.76 02-JAN-08:10
InteriorLights:Electricity 303.98 987.92 07-MAY-17:20 32642.50 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 303.98 987.92 07-MAY-17:20 32642.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity 303.98 987.92 07-MAY-17:20 32642.50 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 303.98 987.92 07-MAY-17:20 32642.50 02-JAN-08:10
Electricity:Zone:CORE_MID 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:CORE_TOP 187.35 2043.28 01-JAN-00:10 13252.30 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 71.93 211.73 01-JAN-00:10 6443.98 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 33.51 422.10 09-APR-17:10 2793.69 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.17 36.00 15-JAN-11:40 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.17 36.00 15-JAN-11:40 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 21.10 267.21 23-APR-17:10 1768.58 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.70 22.79 01-JAN-10:20 860.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.70 22.79 01-JAN-10:20 860.01 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 33.20 422.10 19-MAR-17:10 2793.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.86 36.00 01-JAN-10:10 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.86 36.00 01-JAN-10:10 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 21.10 267.21 19-MAR-17:10 1768.52 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.70 22.79 01-JAN-13:30 859.95 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.70 22.79 01-JAN-13:30 859.95 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 33.46 422.10 09-APR-17:10 2793.69 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 9.13 36.00 08-JAN-11:30 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 9.13 36.00 08-JAN-11:30 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 21.09 267.21 23-APR-17:10 1768.58 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.68 22.79 01-JAN-10:10 860.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.68 22.79 01-JAN-10:10 860.01 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 33.17 422.10 19-MAR-17:10 2793.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.84 36.00 01-JAN-10:00 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.84 36.00 01-JAN-10:00 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 21.08 267.21 19-MAR-17:10 1768.52 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.68 22.79 01-JAN-13:20 859.95 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.68 22.79 01-JAN-13:20 859.95 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 33.51 422.10 09-APR-17:10 2793.69 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 9.17 36.00 15-JAN-11:40 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 9.17 36.00 15-JAN-11:40 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 21.10 267.21 23-APR-17:10 1768.58 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.70 22.79 01-JAN-10:20 860.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 5.70 22.79 01-JAN-10:20 860.01 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 33.20 422.10 19-MAR-17:10 2793.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.86 36.00 01-JAN-10:10 1358.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 8.86 36.00 01-JAN-10:10 1358.45 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 21.10 267.21 19-MAR-17:10 1768.52 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.70 22.79 01-JAN-13:30 859.95 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 5.70 22.79 01-JAN-13:30 859.95 02-JAN-08:10
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 176.90 368.59 02-JUL-17:50 81449.51 10-AUG-15:20
ExteriorEquipment:Electricity 26.90 367.92 01-JAN-00:10 1410.29 02-JAN-08:10
Transformer:ExteriorEquipment:Electricity 26.90 367.92 01-JAN-00:10 1410.29 02-JAN-08:10
ElectricityPurchased:Facility 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
ElectricityPurchased:Plant 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
Cogeneration:ElectricityPurchased 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
General:Cogeneration:ElectricityPurchased 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
ElectricityNet:Plant 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
Cogeneration:ElectricityNet 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
General:Cogeneration:ElectricityNet 1307.63 13840.93 02-JUL-17:50 153056.31 10-AUG-15:20
Fans:Electricity 79.67 0.00 01-JAN-00:50 27002.48 10-AUG-15:20
General:Fans:Electricity 79.67 0.00 01-JAN-00:50 27002.48 10-AUG-15:20
ExteriorLights:Electricity 51.64 0.00 01-JAN-08:10 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 51.64 0.00 01-JAN-08:10 5686.19 01-JAN-06:10
Cooling:Electricity 70.33 0.00 01-JAN-00:10 53443.20 29-AUG-15:30
General:Cooling:Electricity 70.33 0.00 01-JAN-00:10 53443.20 29-AUG-15:30
Electricity:Plant 55.42 0.00 01-JAN-01:30 6743.46 02-JAN-12:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 54.28 0.00 01-JAN-00:10 6514.45 09-FEB-12:20
Water Heater:WaterSystems:Electricity 54.28 0.00 01-JAN-00:10 6514.45 09-FEB-12:20
Pumps:Electricity 1.13 0.00 01-JAN-00:50 568.43 26-DEC-07:40
General:Pumps:Electricity 1.13 0.00 01-JAN-00:50 568.43 26-DEC-07:40
WIRED_LTG_ELECTRICITY 8.54 0.00 01-JAN-00:10 917.25 02-JAN-08:20
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 226.92 0.00 01-JAN-00:50 185997.07 26-DEC-07:20
NaturalGas:Plant 226.92 0.00 01-JAN-00:50 185997.07 26-DEC-07:20
Heating:NaturalGas 226.92 0.00 01-JAN-00:50 185997.07 26-DEC-07:20
Boiler:Heating:NaturalGas 226.92 0.00 01-JAN-00:50 185997.07 26-DEC-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 03-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1635.28 0.00 01-JAN-00:50 400039.08 26-DEC-07:20
EnergyTransfer:Building 966.25 0.00 01-JAN-00:50 159952.39 10-AUG-15:20
EnergyTransfer:Zone:CORE_BOTTOM 215.75 0.00 01-JAN-00:40 23887.96 14-AUG-16:00
Heating:EnergyTransfer 70.08 0.00 01-JAN-00:50 125352.98 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.09 0.00 01-JAN-00:10 5573.59 02-JAN-06:20
General:Heating:EnergyTransfer 70.08 0.00 01-JAN-00:50 125352.98 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.09 0.00 01-JAN-00:10 5573.59 02-JAN-06:20
Cooling:EnergyTransfer 896.18 0.00 01-JAN-00:50 159952.39 10-AUG-15:20
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 215.66 0.00 01-JAN-00:40 23887.96 14-AUG-16:00
General:Cooling:EnergyTransfer 896.18 0.00 01-JAN-00:50 159952.39 10-AUG-15:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 215.66 0.00 01-JAN-00:40 23887.96 14-AUG-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 36.63 0.00 01-JAN-00:10 10245.83 09-JAN-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 14.65 0.00 01-JAN-00:10 10245.83 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 14.65 0.00 01-JAN-00:10 10245.83 09-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 21.98 0.00 01-JAN-00:10 10160.22 10-AUG-14:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 21.98 0.00 01-JAN-00:10 10160.22 10-AUG-14:50
EnergyTransfer:Zone:MIDFLOOR_PLENUM 19.11 0.00 01-JAN-00:10 8689.37 02-JAN-08:30
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 6.72 0.00 01-JAN-00:10 8689.37 02-JAN-08:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 6.72 0.00 01-JAN-00:10 8689.37 02-JAN-08:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 12.38 0.00 01-JAN-00:10 4531.76 14-AUG-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 12.38 0.00 01-JAN-00:10 4531.76 14-AUG-15:30
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 21.59 0.00 01-JAN-00:40 7366.27 02-JAN-09:10
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.23 0.00 01-JAN-00:40 7366.27 02-JAN-09:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.23 0.00 01-JAN-00:40 7366.27 02-JAN-09:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 17.36 0.00 01-JAN-00:10 5070.97 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 17.36 0.00 01-JAN-00:10 5070.97 14-AUG-16:00
EnergyTransfer:Zone:CORE_MID 142.45 0.00 01-JAN-00:10 17627.39 14-AUG-16:00
Heating:EnergyTransfer:Zone:CORE_MID 0.52 0.00 01-JAN-00:10 12338.77 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_MID 0.52 0.00 01-JAN-00:10 12338.77 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_MID 141.93 0.00 01-JAN-00:10 17627.39 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 141.93 0.00 01-JAN-00:10 17627.39 14-AUG-16:00
EnergyTransfer:Zone:CORE_TOP 131.20 0.00 01-JAN-00:10 19263.10 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_TOP 2.55 0.00 01-JAN-00:10 19263.10 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 2.55 0.00 01-JAN-00:10 19263.10 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 128.65 0.00 01-JAN-00:10 19115.00 24-JUL-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 128.65 0.00 01-JAN-00:10 19115.00 24-JUL-15:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 29.99 0.00 01-JAN-00:10 6871.67 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.03 0.00 01-JAN-00:10 6871.67 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.03 0.00 01-JAN-00:10 6871.67 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 23.96 0.00 01-JAN-00:10 6284.14 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 23.96 0.00 01-JAN-00:10 6284.14 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 29.33 0.00 01-JAN-00:10 8862.70 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.63 0.00 01-JAN-00:10 5698.55 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.63 0.00 01-JAN-00:10 5698.55 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 25.70 0.00 01-JAN-00:10 8862.70 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 25.70 0.00 01-JAN-00:10 8862.70 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 50.15 0.00 01-JAN-00:10 13767.91 04-OCT-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.56 0.00 01-JAN-00:10 8662.21 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.56 0.00 01-JAN-00:10 8662.21 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 45.59 0.00 01-JAN-00:10 13767.91 04-OCT-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 45.59 0.00 01-JAN-00:10 13767.91 04-OCT-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 30.65 0.00 01-JAN-00:10 9822.17 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.84 0.00 01-JAN-00:10 5802.18 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.84 0.00 01-JAN-00:10 5802.18 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 26.81 0.00 01-JAN-00:10 9822.17 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 26.81 0.00 01-JAN-00:10 9822.17 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 25.33 0.00 01-JAN-00:40 5360.47 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.30 0.00 01-JAN-00:40 5360.47 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.30 0.00 01-JAN-00:40 5360.47 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 23.03 0.00 01-JAN-00:20 4883.65 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 23.03 0.00 01-JAN-00:20 4883.65 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 25.43 0.00 01-JAN-00:40 7282.13 24-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.38 0.00 01-JAN-00:40 4518.88 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.38 0.00 01-JAN-00:40 4518.88 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 24.05 0.00 01-JAN-00:20 7282.13 24-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 24.05 0.00 01-JAN-00:20 7282.13 24-JUL-09:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 44.46 0.00 01-JAN-00:40 13002.33 10-AUG-16:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.69 0.00 01-JAN-00:40 8621.22 26-DEC-07:50
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.69 0.00 01-JAN-00:40 8621.22 26-DEC-07:50
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 32.77 0.00 01-JAN-00:20 13002.33 10-AUG-16:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 32.77 0.00 01-JAN-00:20 13002.33 10-AUG-16:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 26.14 0.00 01-JAN-00:40 7943.06 10-AUG-17:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.40 0.00 01-JAN-00:40 4599.71 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.40 0.00 01-JAN-00:40 4599.71 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 24.74 0.00 01-JAN-00:20 7943.06 10-AUG-17:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 24.74 0.00 01-JAN-00:20 7943.06 10-AUG-17:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 28.76 0.00 01-JAN-00:10 5787.20 24-JUL-15:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.12 0.00 01-JAN-00:10 5696.57 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.12 0.00 01-JAN-00:10 5696.57 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 26.64 0.00 01-JAN-00:10 5787.20 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 26.64 0.00 01-JAN-00:10 5787.20 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 29.06 0.00 01-JAN-00:10 8951.57 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.41 0.00 01-JAN-00:10 4812.33 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.41 0.00 01-JAN-00:10 4812.33 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 27.65 0.00 01-JAN-00:10 8951.57 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 27.65 0.00 01-JAN-00:10 8951.57 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 50.26 0.00 01-JAN-00:10 13619.48 04-OCT-13:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.58 0.00 01-JAN-00:10 7168.30 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.58 0.00 01-JAN-00:10 7168.30 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 48.67 0.00 01-JAN-00:10 13619.48 04-OCT-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 48.67 0.00 01-JAN-00:10 13619.48 04-OCT-13:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 29.98 0.00 01-JAN-00:10 9376.00 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.38 0.00 01-JAN-00:10 4807.70 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.38 0.00 01-JAN-00:10 4807.70 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 28.60 0.00 01-JAN-00:10 9376.00 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 28.60 0.00 01-JAN-00:10 9376.00 10-AUG-16:00
PlantLoopHeatingDemand:Facility 206.10 0.00 01-JAN-00:50 150545.10 26-DEC-07:10
PlantLoopHeatingDemand:Plant 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
EnergyTransfer:HVAC 464.00 0.00 01-JAN-00:50 214480.23 10-AUG-15:20
HeatingCoils:EnergyTransfer 154.62 0.00 01-JAN-00:50 148507.92 26-DEC-07:10
PlantLoopHeatingDemand:HVAC 154.62 0.00 01-JAN-00:50 148507.92 26-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 154.62 0.00 01-JAN-00:50 148507.92 26-DEC-07:10
CoolingCoils:EnergyTransfer 309.39 0.00 01-JAN-00:10 214468.46 10-AUG-15:20
EnergyTransfer:Plant 205.02 0.00 01-JAN-00:50 148894.19 26-DEC-07:20
WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
Boilers:EnergyTransfer 153.53 0.00 01-JAN-00:50 146857.01 26-DEC-07:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.089 -215.661 0.000 0.000 32.909 71.928 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -139.688
CORE_MID 0.000 0.000 0.518 -141.927 0.000 0.000 34.197 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -80.142
CORE_TOP 0.000 0.000 2.553 -128.647 0.000 0.000 35.053 71.928 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -96.313
PERIMETER_TOP_ZN_3 0.000 0.000 6.028 -23.960 0.000 0.000 7.601 9.173 24.333 13.742 0.000 0.009 0.001 0.000 -29.286 0.000 -3.141 -4.499
PERIMETER_TOP_ZN_2 0.000 0.000 3.626 -25.701 0.000 0.000 4.788 5.701 15.404 26.276 0.000 0.005 0.000 0.000 -18.845 0.000 -2.109 -9.145
PERIMETER_TOP_ZN_1 0.000 0.000 4.558 -45.593 0.000 0.000 7.497 8.864 24.332 56.853 0.000 0.007 0.001 0.000 -28.918 0.000 -3.253 -24.348
PERIMETER_TOP_ZN_4 0.000 0.000 3.839 -26.807 0.000 0.000 4.852 5.697 15.403 28.464 0.000 0.005 0.000 0.000 -19.458 0.000 -2.130 -9.866
PERIMETER_BOT_ZN_3 0.000 0.000 2.301 -23.030 0.000 0.000 7.544 9.127 24.333 13.902 0.000 0.006 0.001 0.000 -30.739 0.000 -1.764 -1.679
PERIMETER_BOT_ZN_2 0.000 0.000 1.383 -24.049 0.000 0.000 4.727 5.685 15.404 26.292 0.000 0.003 0.001 0.000 -20.037 0.000 -1.203 -8.205
PERIMETER_BOT_ZN_1 0.000 0.000 11.688 -32.768 0.000 0.000 7.606 8.839 24.332 57.343 0.000 0.383 0.000 0.000 -30.645 0.000 -32.432 -14.348
PERIMETER_BOT_ZN_4 0.000 0.000 1.398 -24.741 0.000 0.000 4.775 5.677 15.403 28.563 0.000 0.003 0.001 0.000 -20.728 0.000 -1.214 -9.136
PERIMETER_MID_ZN_3 0.000 0.000 2.120 -26.644 0.000 0.000 7.479 9.173 24.333 13.409 0.000 0.008 4.189 0.000 -31.281 0.000 -2.786 -0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.406 -27.654 0.000 0.000 3.509 5.701 15.404 26.036 0.000 0.005 0.001 0.000 -20.010 0.000 -1.862 -2.535
PERIMETER_MID_ZN_1 0.000 0.000 1.581 -48.674 0.000 0.000 7.373 8.864 24.332 56.462 0.000 0.006 0.001 0.000 -30.771 0.000 -2.879 -16.294
PERIMETER_MID_ZN_4 0.000 0.000 1.381 -28.598 0.000 0.000 4.776 5.697 15.403 28.252 0.000 0.004 0.001 0.000 -20.723 0.000 -1.885 -4.307
TOPFLOOR_PLENUM 14.647 -21.980 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.005 12.174 0.000 0.000 0.000 -4.846 -0.000
MIDFLOOR_PLENUM 6.725 -12.382 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 10.446 0.000 0.000 0.000 -4.798 -0.000
FIRSTFLOOR_PLENUM 4.232 -17.357 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.007 17.041 0.000 0.000 0.000 -3.924 -0.000
Total Facility 25.604 -51.719 44.471 -844.454 0.000 0.000 174.687 303.983 719.689 375.594 0.000 0.467 43.858 0.000 -301.442 0.000 -70.225 -420.506


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 17-JUL-05:12 0.00 0.00 0.00 -40600.61 0.00 0.00 319.60 715.98 7410.35 0.00 0.00 0.00 32154.68 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-06:02 0.00 0.00 0.00 -29267.47 0.00 0.00 710.51 2148.02 3025.92 0.00 0.00 0.00 23383.02 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUL-15:20 0.00 0.00 0.00 -19115.13 0.00 0.00 3497.10 6443.98 6808.32 0.00 0.00 0.00 2365.73 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -6284.18 0.00 0.00 737.22 647.98 1435.25 3606.66 0.00 20.14 0.00 0.00 -0.00 0.00 0.00 -163.06
PERIMETER_TOP_ZN_2 25-JUN-08:52 0.00 0.00 0.00 -13853.52 0.00 0.00 15.73 22.79 302.86 9398.97 0.00 0.00 4174.30 0.00 -0.00 0.00 -61.13 0.00
PERIMETER_TOP_ZN_1 10-SEP-13:32 0.00 0.00 0.00 -22231.94 0.00 0.00 22.29 36.00 478.41 13911.04 0.00 0.00 7858.53 0.00 -0.00 0.00 -74.33 0.00
PERIMETER_TOP_ZN_4 10-SEP-16:12 0.00 0.00 0.00 -15818.73 0.00 0.00 14.06 22.79 302.86 11438.41 0.00 0.00 4082.07 0.00 -0.00 0.00 -41.45 0.00
PERIMETER_BOT_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -4883.61 0.00 0.00 737.22 647.98 1435.25 3653.33 0.00 10.79 0.00 0.00 -0.00 0.00 0.00 -1600.96
PERIMETER_BOT_ZN_2 23-JUL-08:42 0.00 0.00 0.00 -11665.64 0.00 0.00 16.35 22.79 302.86 10474.52 0.00 0.00 906.12 0.00 -0.00 0.00 -57.00 0.00
PERIMETER_BOT_ZN_1 30-JUL-14:12 0.00 0.00 0.00 -16908.40 0.00 0.00 26.50 36.00 478.41 9579.89 0.00 0.00 6788.62 0.00 -0.00 0.00 -1.02 0.00
PERIMETER_BOT_ZN_4 30-JUL-17:31 0.00 0.00 0.00 -13955.48 0.00 0.00 0.00 22.79 244.42 11487.64 0.00 0.00 2213.96 0.00 -0.00 0.00 -13.32 0.00
PERIMETER_MID_ZN_3 24-JUL-15:00 0.00 0.00 0.00 -5787.19 0.00 0.00 737.22 647.98 1435.25 3625.50 0.00 16.83 0.00 0.00 -0.00 0.00 0.00 -675.59
PERIMETER_MID_ZN_2 30-JUL-08:52 0.00 0.00 0.00 -14830.36 0.00 0.00 14.15 22.79 302.86 10346.31 0.00 0.00 4189.15 0.00 -0.00 0.00 -44.89 0.00
PERIMETER_MID_ZN_1 30-JUL-12:12 0.00 0.00 0.00 -19556.94 0.00 0.00 24.66 36.00 478.41 13046.33 0.00 0.00 5989.28 0.00 -0.00 0.00 -17.75 0.00
PERIMETER_MID_ZN_4 23-JUL-16:41 0.00 0.00 0.00 -16063.62 0.00 0.00 12.63 22.79 302.86 12228.57 0.00 0.00 3531.16 0.00 -0.00 0.00 -34.39 0.00
TOPFLOOR_PLENUM 10-AUG-14:50 0.00 -10159.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.69 10141.25 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 14-AUG-15:30 0.00 -4531.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00 4521.71 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 14-AUG-16:00 0.00 -5070.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.20 5063.67 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-15:20 0.00 -19442.92 0.00 -140507.98 0.00 0.00 17714.89 25681.07 41670.51 69321.20 0.00 850.87 4712.36 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-06:11 0.00 0.00 6509.58 0.00 0.00 0.00 500.32 715.98 7410.35 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -15136.22
CORE_MID 02-JAN-06:11 0.00 0.00 13492.94 0.00 0.00 0.00 525.36 715.98 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17760.20
CORE_TOP 02-JAN-06:11 0.00 0.00 20946.39 0.00 0.00 0.00 536.35 715.98 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25224.64
PERIMETER_TOP_ZN_3 21-FEB-05:51 0.00 0.00 7625.18 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -1668.47 0.00 -128.18 -6387.97
PERIMETER_TOP_ZN_2 21-FEB-05:51 0.00 0.00 6921.01 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1112.27 0.00 -86.41 -6076.48
PERIMETER_TOP_ZN_1 21-FEB-05:51 0.00 0.00 10229.50 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -1671.91 0.00 -132.39 -8984.64
PERIMETER_TOP_ZN_4 21-FEB-05:51 0.00 0.00 7116.45 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1095.74 0.00 -87.08 -6287.78
PERIMETER_BOT_ZN_3 02-JAN-06:11 0.00 0.00 5789.35 0.00 0.00 0.00 113.18 150.93 637.89 0.00 0.00 0.00 0.00 0.00 -1129.29 0.00 -34.89 -5527.16
PERIMETER_BOT_ZN_2 02-JAN-06:11 0.00 0.00 5262.86 0.00 0.00 0.00 71.65 95.55 403.81 0.00 0.00 0.00 0.00 0.00 -767.90 0.00 -23.57 -5042.40
PERIMETER_BOT_ZN_1 26-DEC-07:50 0.00 0.00 8620.09 0.00 0.00 0.00 231.29 452.82 637.88 0.00 0.00 0.00 6353.44 0.00 -2166.57 0.00 -14128.94 0.00
PERIMETER_BOT_ZN_4 02-JAN-06:11 0.00 0.00 5437.84 0.00 0.00 0.00 71.65 95.55 403.81 0.00 0.00 0.00 0.00 0.00 -750.55 0.00 -23.61 -5234.69
PERIMETER_MID_ZN_3 02-JAN-06:11 0.00 0.00 6187.17 0.00 0.00 0.00 113.18 150.93 637.89 0.00 0.00 0.00 0.00 0.00 -1134.50 0.00 -54.84 -5899.82
PERIMETER_MID_ZN_2 02-JAN-06:11 0.00 0.00 5759.25 0.00 0.00 0.00 71.65 95.55 403.81 0.00 0.00 0.00 0.00 0.00 -774.41 0.00 -37.14 -5518.71
PERIMETER_MID_ZN_1 02-JAN-06:11 0.00 0.00 8440.78 0.00 0.00 0.00 113.18 150.93 637.88 0.00 0.00 0.00 0.00 0.00 -1163.51 0.00 -55.54 -8123.72
PERIMETER_MID_ZN_4 02-JAN-06:11 0.00 0.00 5776.38 0.00 0.00 0.00 71.65 95.55 403.81 0.00 0.00 0.00 0.00 0.00 -755.05 0.00 -37.15 -5555.19
TOPFLOOR_PLENUM 26-DEC-06:09 11296.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -10.42 -11286.37
MIDFLOOR_PLENUM 02-JAN-08:20 8843.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -67.00 -8776.56
FIRSTFLOOR_PLENUM 02-JAN-08:10 7515.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -49.21 -7466.47
Total Facility 02-JAN-06:11 6530.26 0.00 122474.29 0.00 0.00 0.00 2670.98 3626.85 19712.35 0.00 0.00 0.00 0.00 0.00 -11362.79 0.00 -1872.71 -141779.25



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 5.6398 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.9264 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 5.5110 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.5898 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.7679 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.1657 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.8199 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.4229 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.7555 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.4743 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.8840 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.5319 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7348 2.7348 0.7794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2092 2.2092 0.7644 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2540 2.2540 0.7889 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6289 0.6289 0.1660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8038 0.8038 0.1608 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2033 1.2033 0.2407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8779 0.8779 0.1756 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5077 0.5077 0.1640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6679 0.6679 0.1336 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9922 0.9922 0.1984 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7373 0.7373 0.1475 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5572 0.5572 0.1610 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8041 0.8041 0.1608 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1195 1.1195 0.2239 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8210 0.8210 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 5.6398 4.9264 5.6398 1.4229 0.0000 1.0000
PACU_VAV_MID 5.5110 4.5898 5.5110 1.4743 0.0000 1.0000
PACU_VAV_TOP 5.7679 5.1657 5.7679 1.5319 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3674 1.3674 0.7794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1046 1.1046 0.7644 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1270 1.1270 0.7889 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3145 0.3145 0.1660 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4019 0.4019 0.1608 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6017 0.6017 0.2407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4390 0.4390 0.1756 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2538 0.2538 0.1640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3339 0.3339 0.1336 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4961 0.4961 0.1984 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3687 0.3687 0.1475 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2786 0.2786 0.1610 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4021 0.4021 0.1608 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5598 0.5598 0.2239 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4105 0.4105 0.1642 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.8199 1.4229 1.4229 1.4229 0.0000 1.0000
PACU_VAV_MID 2.7555 1.4743 1.4743 1.4743 0.0000 1.0000
PACU_VAV_TOP 2.8840 1.5319 1.5319 1.5319 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 306.50
Number of hours cooling loads not met 45.67
Number of hours not met 352.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 226.92 185997.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 70.33 53443.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 303.98 32642.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 51.64 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.90 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 79.67 27002.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.13 568.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 54.28 6514.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1307.63
Natural Gas 0.00 226.92
Additional 0.00 0.00
Total 719.69 1534.55


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 61.01
Space Heating 0.00
Space Cooling 14.12
Fans (All) 15.99
Service Water Heating 10.90
Receptacle Equipment 144.45
Miscellaneous (All) 262.46
Subtotal 262.46


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 45.55
Service Water Heating 0.00
Miscellaneous (All) 45.55
Subtotal 45.55


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 19.81
Space Heating 14.79
Space Cooling 4.58
Fans (All) 5.19
Service Water Heating 3.54
Receptacle Equipment 46.90
Miscellaneous 5.19


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 1574. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8698.83 61.17 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8749.00 11.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8742.17 17.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8734.50 25.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8750.67 9.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8742.50 17.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8739.00 21.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8748.17 11.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8743.67 16.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8736.33 23.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 8738.33 21.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8698.83 0.00 0.00 0.00 0.00
Max 8760.00 61.17 0.00 0.00 0.00
Average 8746.84 13.16 0.00 0.00 0.00
Sum 157443.17 236.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128275.33 28.67 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 28.67 0.00 0.00 0.00
Average 34141.74 1.59 0.00 0.00 0.00
Sum 614551.33 28.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8581.67 178.33 0.00 0.00 0.00
CORE_MID 8744.17 15.83 0.00 0.00 0.00
CORE_TOP 8756.50 3.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8755.17 4.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8744.00 16.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8733.00 27.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8726.00 34.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8753.83 6.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8740.17 19.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8730.67 29.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8709.17 50.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8753.83 6.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8740.50 19.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8731.67 28.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8728.50 31.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8744.67 15.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8581.67 0.00 0.00 0.00 0.00
Max 8760.00 178.33 0.00 0.00 0.00
Average 8732.97 27.03 0.00 0.00 0.00
Sum 157193.50 486.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128203.67 100.33 0.00 0.00 0.00
CORE_MID 128296.33 7.67 0.00 0.00 0.00
CORE_TOP 128299.33 4.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128299.33 100.33 0.00 0.00 0.00
Average 34137.07 6.26 0.00 0.00 0.00
Sum 614467.33 112.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:09

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.985543E+10 11809.99 13-JAN-17:00 2.20 1.77 0.186054E+10 2606.60 27-JAN-14:09 9.72 8.09
February 0.108597E+11 14969.83 28-FEB-17:00 14.40 10.82 0.177426E+10 2606.64 09-FEB-10:09 14.40 10.82
March 0.158684E+11 17025.71 02-MAR-17:00 12.80 8.57 0.215031E+10 2606.66 09-MAR-14:09 14.90 12.35
April 0.172335E+11 36721.64 28-APR-06:02 11.10 10.22 0.191592E+10 2606.65 27-APR-13:20 11.10 10.22
May 0.221474E+11 37258.86 08-MAY-06:03 9.90 9.62 0.207741E+10 2606.68 05-MAY-09:09 9.90 9.62
June 0.238654E+11 39552.48 29-JUN-05:12 12.80 11.40 0.207217E+10 2606.71 05-JUN-13:00 12.80 11.40
July 0.245775E+11 40612.30 17-JUL-05:12 14.07 12.34 0.192780E+10 2606.64 28-JUL-13:39 21.10 15.48
August 0.266453E+11 40236.62 11-AUG-05:12 13.40 12.29 0.216246E+10 2606.90 09-AUG-09:00 13.40 12.29
September 0.220846E+11 38666.19 05-SEP-06:02 11.02 9.56 0.192026E+10 2606.66 22-SEP-09:09 14.37 14.11
October 0.180313E+11 37535.15 10-OCT-06:02 12.12 10.88 0.199234E+10 2606.65 05-OCT-09:00 12.12 10.88
November 0.132184E+11 17269.00 06-NOV-17:00 11.70 10.80 0.195724E+10 2606.63 10-NOV-10:20 7.07 5.84
December 0.112750E+11 14062.18 06-DEC-15:50 3.58 3.15 0.187465E+10 2606.64 12-DEC-10:20 3.87 3.71
                     
Annual Sum or Average 0.215662E+12         0.236854E+11        
Minimum of Months 0.985543E+10 11809.99   2.20 1.77 0.177426E+10 2606.60   3.87 3.71
Maximum of Months 0.266453E+11 40612.30   14.40 12.34 0.216246E+10 2606.90   21.10 15.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 462652.30 246.89 11-JAN-17:20 12.40 9.38 0.00 0.00 01-JAN-00:10 12.40 9.38
February 0.101068E+09 2085.25 27-FEB-15:30 19.70 12.30 0.00 0.00 01-FEB-00:10 19.70 12.30
March 0.579680E+09 3045.56 14-MAR-15:00 16.10 10.31 0.00 0.00 01-MAR-00:10 16.10 10.31
April 0.161491E+10 8553.18 27-APR-14:30 26.65 17.06 0.00 0.00 01-APR-00:10 26.65 17.06
May 0.289917E+10 8815.11 15-MAY-14:30 23.30 13.06 0.00 0.00 01-MAY-00:10 23.30 13.06
June 0.372030E+10 8826.98 28-JUN-14:30 25.55 15.61 0.00 0.00 01-JUN-00:10 25.55 15.61
July 0.489417E+10 9964.81 24-JUL-14:00 29.40 18.12 0.00 0.00 01-JUL-00:10 29.40 18.12
August 0.477860E+10 10160.22 10-AUG-14:50 30.07 18.95 0.00 0.00 01-AUG-00:10 30.07 18.95
September 0.255567E+10 7899.03 14-SEP-14:30 23.90 17.04 0.00 0.00 01-SEP-00:10 23.90 17.04
October 0.758269E+09 5553.08 04-OCT-14:40 21.50 11.47 0.00 0.00 01-OCT-00:10 21.50 11.47
November 73972753.74 2502.75 04-NOV-14:10 21.10 15.94 0.00 0.00 01-NOV-00:10 21.10 15.94
December 4137111.78 439.53 02-DEC-14:50 11.78 5.57 0.00 0.00 01-DEC-00:10 11.78 5.57
                     
Annual Sum or Average 0.219804E+11         0.00        
Minimum of Months 462652.30 246.89   11.78 5.57 0.00 0.00   11.78 5.57
Maximum of Months 0.489417E+10 10160.22   30.07 18.95 0.00 0.00   30.07 18.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 14428524.43 1844.32 14-JAN-06:11 2.20 1.14 0.00 0.00 01-JAN-00:10 2.20 1.14
February 0.113226E+09 2035.28 04-FEB-07:03 7.30 6.18 0.00 0.00 01-FEB-00:10 7.30 6.18
March 0.350085E+09 2651.61 02-MAR-07:02 0.78 -0.1 0.00 0.00 01-MAR-00:10 0.78 -0.1
April 0.700576E+09 2941.17 27-APR-16:00 27.20 16.90 0.00 0.00 01-APR-00:10 27.20 16.90
May 0.131319E+10 3065.21 15-MAY-15:30 23.60 12.74 0.00 0.00 01-MAY-00:10 23.60 12.74
June 0.197681E+10 3463.81 28-JUN-16:00 26.10 16.29 0.00 0.00 01-JUN-00:10 26.10 16.29
July 0.263568E+10 4447.06 31-JUL-15:20 28.50 19.00 0.00 0.00 01-JUL-00:10 28.50 19.00
August 0.295417E+10 4531.76 14-AUG-15:30 27.25 17.25 0.00 0.00 01-AUG-00:10 27.25 17.25
September 0.159241E+10 3547.58 14-SEP-15:50 24.32 17.03 0.00 0.00 01-SEP-00:10 24.32 17.03
October 0.573988E+09 2361.92 28-OCT-06:03 7.80 6.34 0.00 0.00 01-OCT-00:10 7.80 6.34
November 0.135351E+09 1809.12 09-NOV-07:03 6.70 5.68 0.00 0.00 01-NOV-00:10 6.70 5.68
December 21990206.76 1647.71 02-DEC-06:11 4.97 2.41 0.00 0.00 01-DEC-00:10 4.97 2.41
                     
Annual Sum or Average 0.123819E+11         0.00        
Minimum of Months 14428524.43 1647.71   0.78 -0.1 0.00 0.00   0.78 -0.1
Maximum of Months 0.295417E+10 4531.76   28.50 19.00 0.00 0.00   28.50 19.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 81905788.26 2308.47 13-JAN-06:11 3.13 2.22 0.00 0.00 01-JAN-00:10 3.13 2.22
February 0.201717E+09 2472.43 10-FEB-07:01 0.60 -0.1 0.00 0.00 01-FEB-00:10 0.60 -0.1
March 0.575024E+09 3216.89 02-MAR-07:02 0.78 -0.1 0.00 0.00 01-MAR-00:10 0.78 -0.1
April 0.111375E+10 3442.70 28-APR-06:06 11.10 10.22 0.00 0.00 01-APR-00:10 11.10 10.22
May 0.197430E+10 3651.13 08-MAY-06:08 9.90 9.62 0.00 0.00 01-MAY-00:10 9.90 9.62
June 0.264075E+10 3884.09 28-JUN-16:00 26.10 16.29 0.00 0.00 01-JUN-00:10 26.10 16.29
July 0.331007E+10 4973.89 31-JUL-16:00 28.90 19.18 0.00 0.00 01-JUL-00:10 28.90 19.18
August 0.372477E+10 5070.97 14-AUG-16:00 27.50 16.95 0.00 0.00 01-AUG-00:10 27.50 16.95
September 0.231985E+10 4373.81 11-SEP-16:00 23.30 16.14 0.00 0.00 01-SEP-00:10 23.30 16.14
October 0.101267E+10 3208.54 05-OCT-06:06 8.48 5.36 0.00 0.00 01-OCT-00:10 8.48 5.36
November 0.280689E+09 2660.26 10-NOV-07:02 4.08 3.61 0.00 0.00 01-NOV-00:10 4.08 3.61
December 0.121765E+09 2151.95 07-DEC-07:03 6.10 3.18 0.00 0.00 01-DEC-00:10 6.10 3.18
                     
Annual Sum or Average 0.173573E+11         0.00        
Minimum of Months 81905788.26 2151.95   0.60 -0.1 0.00 0.00   0.60 -0.1
Maximum of Months 0.372477E+10 5070.97   28.90 19.18 0.00 0.00   28.90 19.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.677852E+10 6959.14 12-JAN-17:00 7.20 5.41 0.161207E+10 2374.76 12-JAN-14:00 7.20 5.41
February 0.746272E+10 7910.31 28-FEB-17:00 14.40 10.82 0.155279E+10 2573.09 28-FEB-14:00 14.40 10.82
March 0.101205E+11 9568.31 02-MAR-17:00 12.80 8.57 0.200651E+10 2606.57 02-MAR-14:00 12.80 8.57
April 0.109972E+11 14910.01 27-APR-16:00 27.20 16.90 0.185874E+10 2606.64 14-APR-09:09 27.20 16.90
May 0.144327E+11 15366.77 15-MAY-16:00 23.90 12.85 0.205533E+10 2606.66 05-MAY-09:09 23.90 12.85
June 0.160366E+11 21474.95 12-JUN-06:02 14.60 13.50 0.205972E+10 2606.68 09-JUN-13:09 14.60 13.50
July 0.168147E+11 22945.59 25-JUL-05:12 13.90 13.23 0.191848E+10 2606.64 11-JUL-09:09 13.90 13.23
August 0.182297E+11 29269.19 14-AUG-06:02 15.47 13.75 0.215339E+10 2606.83 09-AUG-09:00 15.47 13.75
September 0.141019E+11 16243.73 11-SEP-16:00 23.30 16.14 0.190200E+10 2606.65 22-SEP-09:09 14.37 14.11
October 0.109589E+11 14427.44 04-OCT-16:00 21.10 11.40 0.191420E+10 2606.65 12-OCT-09:09 9.18 7.86
November 0.843071E+10 8469.41 06-NOV-17:00 11.70 10.80 0.175226E+10 2606.60 06-NOV-14:39 11.70 10.80
December 0.756337E+10 7325.39 06-DEC-16:20 2.57 2.27 0.161173E+10 2478.74 06-DEC-14:00 2.57 2.27
                     
Annual Sum or Average 0.141927E+12         0.223972E+11        
Minimum of Months 0.677852E+10 6959.14   2.57 2.27 0.155279E+10 2374.76   2.57 2.27
Maximum of Months 0.182297E+11 29269.19   27.20 16.90 0.215339E+10 2606.83   27.20 16.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.487835E+10 6696.18 11-JAN-17:00 12.20 9.27 0.152907E+10 2261.05 11-JAN-14:00 12.20 9.27
February 0.602625E+10 7737.72 28-FEB-17:00 14.40 10.82 0.145395E+10 2492.25 28-FEB-14:00 14.40 10.82
March 0.920414E+10 8572.44 02-MAR-17:00 12.80 8.57 0.187335E+10 2570.46 02-MAR-14:00 12.80 8.57
April 0.103364E+11 16284.96 27-APR-15:50 27.20 16.97 0.178107E+10 2606.64 27-APR-13:50 27.20 16.97
May 0.136214E+11 16945.92 15-MAY-16:00 23.90 12.85 0.201923E+10 2606.66 05-MAY-09:09 23.90 12.85
June 0.154989E+11 17799.86 28-JUN-16:00 26.10 16.29 0.204388E+10 2606.68 09-JUN-13:09 26.10 16.29
July 0.165306E+11 19115.00 24-JUL-15:20 30.03 18.73 0.190806E+10 2606.64 20-JUL-13:09 30.03 18.73
August 0.176812E+11 19102.45 14-AUG-15:30 27.25 17.25 0.214254E+10 2606.82 09-AUG-09:00 27.25 17.25
September 0.129491E+11 17069.28 14-SEP-15:50 24.32 17.03 0.186405E+10 2606.61 07-SEP-13:09 24.32 17.03
October 0.968017E+10 14239.63 04-OCT-16:00 21.10 11.40 0.180567E+10 2606.60 05-OCT-09:00 13.90 9.28
November 0.686534E+10 7579.10 02-NOV-16:00 13.30 10.88 0.161938E+10 2448.85 02-NOV-13:00 13.30 10.88
December 0.537578E+10 7012.47 05-DEC-16:00 6.10 4.53 0.150067E+10 2330.90 05-DEC-14:00 6.10 4.53
                     
Annual Sum or Average 0.128648E+12         0.215409E+11        
Minimum of Months 0.487835E+10 6696.18   6.10 4.53 0.145395E+10 2261.05   6.10 4.53
Maximum of Months 0.176812E+11 19115.00   30.03 18.73 0.214254E+10 2606.82   30.03 18.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.205247E+09 1226.26 11-JAN-16:20 13.67 10.10 0.305879E+09 433.61 11-JAN-14:00 13.67 10.10
February 0.516367E+09 1507.11 27-FEB-16:20 19.23 12.34 0.284821E+09 501.24 28-FEB-14:00 13.90 10.81
March 0.130330E+10 1593.79 10-MAR-14:50 16.20 11.59 0.361624E+09 525.61 10-MAR-14:00 16.10 11.51
April 0.189433E+10 4520.89 27-APR-15:20 27.20 17.16 0.353711E+09 549.50 27-APR-13:00 27.20 17.16
May 0.295633E+10 4739.53 15-MAY-14:30 23.30 13.06 0.413056E+09 549.50 15-MAY-13:09 23.30 13.06
June 0.361157E+10 5214.89 21-JUN-15:30 24.70 15.68 0.425515E+09 549.50 09-JUN-13:09 24.70 15.68
July 0.413958E+10 6284.14 24-JUL-15:00 30.60 18.78 0.399458E+09 549.50 20-JUL-13:09 30.60 18.78
August 0.424211E+10 5725.22 09-AUG-15:20 28.47 18.71 0.447345E+09 549.54 09-AUG-09:00 28.47 18.71
September 0.260346E+10 4295.41 12-SEP-15:00 24.40 16.71 0.378389E+09 549.49 12-SEP-13:00 24.40 16.71
October 0.154762E+10 2684.03 04-OCT-15:30 21.40 11.45 0.350441E+09 549.48 05-OCT-13:00 16.10 10.65
November 0.692072E+09 1439.31 02-NOV-14:40 13.67 11.26 0.313438E+09 484.05 02-NOV-13:00 13.67 11.26
December 0.247779E+09 1145.75 29-DEC-16:00 10.60 8.76 0.295539E+09 419.49 05-DEC-14:00 10.60 8.76
                     
Annual Sum or Average 0.239598E+11         0.432921E+10        
Minimum of Months 0.205247E+09 1145.75   10.60 8.76 0.284821E+09 419.49   10.60 8.76
Maximum of Months 0.424211E+10 6284.14   30.60 18.78 0.447345E+09 549.54   30.60 18.78



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.200984E+09 1099.56 20-JAN-10:45 5.32 3.17 0.193593E+09 265.33 20-JAN-10:50 5.32 3.17
February 0.555390E+09 1415.66 27-FEB-15:50 19.50 12.39 0.181740E+09 309.18 27-FEB-14:00 19.50 12.39
March 0.135961E+10 2716.03 14-MAR-09:45 9.63 7.44 0.235525E+09 347.88 02-MAR-10:09 9.63 7.44
April 0.221920E+10 6710.31 27-APR-09:20 18.17 12.47 0.234134E+09 347.88 20-APR-09:00 18.17 12.47
May 0.310735E+10 6926.99 15-MAY-09:10 17.48 11.96 0.262953E+09 347.89 15-MAY-09:00 18.90 13.25
June 0.397774E+10 13854.65 25-JUN-08:52 16.70 12.03 0.270238E+09 347.88 09-JUN-13:09 16.70 12.03
July 0.426289E+10 12667.41 30-JUL-09:02 20.87 15.88 0.252713E+09 348.34 31-JUL-09:39 22.93 17.42
August 0.457266E+10 12890.34 13-AUG-09:12 21.50 16.14 0.283760E+09 348.42 10-AUG-09:00 21.50 16.14
September 0.293467E+10 10433.76 10-SEP-10:13 17.77 13.72 0.240230E+09 347.88 11-SEP-09:00 18.90 14.30
October 0.160261E+10 4749.71 04-OCT-09:20 16.13 10.66 0.226064E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.630492E+09 1411.51 02-NOV-10:40 12.43 10.47 0.197137E+09 304.32 02-NOV-13:00 14.40 11.37
December 0.277270E+09 1193.60 05-DEC-10:25 7.50 5.28 0.187326E+09 278.99 05-DEC-10:39 7.77 5.32
                     
Annual Sum or Average 0.257009E+11         0.276541E+10        
Minimum of Months 0.200984E+09 1099.56   5.32 3.17 0.181740E+09 265.33   5.32 3.17
Maximum of Months 0.457266E+10 13854.65   21.50 16.14 0.283760E+09 348.42   22.93 17.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.801879E+09 6922.77 20-JAN-13:25 6.70 4.72 0.317691E+09 549.49 20-JAN-14:50 7.12 4.90
February 0.155812E+10 8862.26 27-FEB-14:30 19.15 11.80 0.308573E+09 549.49 27-FEB-14:50 19.72 12.05
March 0.310739E+10 10004.74 14-MAR-13:40 15.20 10.17 0.386420E+09 549.50 02-MAR-14:00 15.20 10.17
April 0.397804E+10 12108.75 27-APR-13:10 26.10 16.37 0.364824E+09 549.51 27-APR-13:50 26.10 16.74
May 0.493215E+10 18064.91 14-MAY-13:43 22.70 12.26 0.409893E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.530830E+10 9443.97 28-JUN-13:10 24.50 15.71 0.419538E+09 549.51 09-JUN-13:09 24.50 15.71
July 0.638254E+10 18067.63 23-JUL-13:32 27.23 16.89 0.395171E+09 549.52 20-JUL-13:09 27.23 16.89
August 0.724261E+10 18511.76 13-AUG-13:12 26.73 18.53 0.444196E+09 550.34 29-AUG-13:20 29.17 20.09
September 0.597100E+10 22231.54 10-SEP-13:32 21.67 14.47 0.379257E+09 549.97 15-SEP-13:39 21.70 16.54
October 0.380779E+10 17143.91 08-OCT-13:02 18.17 13.70 0.367326E+09 549.83 04-OCT-13:00 18.17 13.70
November 0.146761E+10 8976.40 04-NOV-13:30 20.85 16.00 0.326611E+09 549.49 15-NOV-14:00 8.90 6.49
December 0.103621E+10 6983.43 05-DEC-12:30 10.30 6.13 0.314058E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.455936E+11         0.443356E+10        
Minimum of Months 0.801879E+09 6922.77   6.70 4.72 0.308573E+09 549.49   7.12 4.90
Maximum of Months 0.724261E+10 22231.54   27.23 18.53 0.444196E+09 550.34   29.17 20.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222388E+09 1441.25 05-JAN-15:50 6.20 4.71 0.194293E+09 290.17 05-JAN-15:00 6.10 4.61
February 0.542891E+09 3502.44 27-FEB-15:30 19.70 12.30 0.182959E+09 347.83 27-FEB-14:00 19.70 12.30
March 0.138563E+10 5201.56 14-MAR-16:00 17.20 10.94 0.227569E+09 347.84 02-MAR-14:00 17.20 10.94
April 0.226649E+10 8217.78 26-APR-16:00 24.40 14.49 0.218654E+09 347.85 27-APR-13:00 26.10 16.83
May 0.339671E+10 14878.63 14-MAY-16:22 23.05 11.91 0.253680E+09 347.85 15-MAY-13:09 22.88 13.76
June 0.379439E+10 12018.50 18-JUN-16:52 17.20 12.22 0.262135E+09 347.85 09-JUN-13:09 17.20 12.22
July 0.480108E+10 15671.72 23-JUL-16:52 26.70 15.58 0.248720E+09 347.85 28-JUL-13:39 21.10 15.48
August 0.464877E+10 15054.84 06-AUG-16:52 23.40 15.11 0.278214E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.318936E+10 15818.29 10-SEP-16:12 22.20 14.38 0.232511E+09 347.85 12-SEP-13:00 24.40 16.54
October 0.167311E+10 6653.72 04-OCT-16:00 21.10 11.40 0.216769E+09 347.83 03-OCT-13:00 21.10 11.40
November 0.612529E+09 2497.36 04-NOV-15:30 20.55 15.94 0.196605E+09 319.66 15-NOV-14:00 8.90 6.49
December 0.274089E+09 1560.15 05-DEC-15:40 7.40 5.40 0.188547E+09 306.82 05-DEC-15:50 6.75 4.97
                     
Annual Sum or Average 0.268074E+11         0.270066E+10        
Minimum of Months 0.222388E+09 1441.25   6.20 4.71 0.182959E+09 290.17   6.10 4.61
Maximum of Months 0.480108E+10 15818.29   26.70 15.94 0.278214E+09 347.88   26.10 16.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.328235E+09 1191.75 11-JAN-16:20 13.67 10.10 0.307271E+09 431.27 11-JAN-14:00 13.67 10.10
February 0.645163E+09 1398.39 28-FEB-15:00 13.90 10.81 0.285336E+09 481.92 28-FEB-14:00 13.90 10.81
March 0.146938E+10 1452.77 10-MAR-14:40 16.30 11.68 0.361777E+09 495.53 10-MAR-14:50 16.20 11.59
April 0.178686E+10 2696.07 27-APR-16:00 27.20 16.90 0.350236E+09 549.49 27-APR-13:00 27.20 16.90
May 0.248672E+10 3213.76 05-MAY-15:30 24.70 17.20 0.416374E+09 549.49 15-MAY-09:00 18.90 13.25
June 0.299874E+10 3970.09 21-JUN-15:40 24.80 15.84 0.428551E+09 549.50 09-JUN-13:09 24.80 15.84
July 0.350114E+10 4883.65 24-JUL-15:00 30.60 18.78 0.401946E+09 549.50 21-JUL-13:00 30.60 18.78
August 0.372142E+10 4550.20 09-AUG-15:30 28.70 18.83 0.450719E+09 549.53 09-AUG-09:00 28.70 18.83
September 0.249529E+10 3383.15 14-SEP-15:50 24.32 17.03 0.388774E+09 549.49 14-SEP-09:09 24.32 17.03
October 0.186664E+10 2104.91 04-OCT-15:30 21.40 11.45 0.368978E+09 549.48 05-OCT-13:00 16.10 10.65
November 0.118812E+10 1471.97 06-NOV-12:00 13.90 10.05 0.327454E+09 496.77 06-NOV-14:09 11.60 10.16
December 0.542760E+09 1169.26 29-DEC-16:10 10.40 8.63 0.298957E+09 427.58 29-DEC-14:20 10.40 8.63
                     
Annual Sum or Average 0.230305E+11         0.438637E+10        
Minimum of Months 0.328235E+09 1169.26   10.40 8.63 0.285336E+09 427.58   10.40 8.63
Maximum of Months 0.372142E+10 4883.65   30.60 18.83 0.450719E+09 549.53   30.60 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288421E+09 949.20 20-JAN-10:45 5.32 3.17 0.194540E+09 271.57 20-JAN-10:50 5.32 3.17
February 0.598040E+09 1147.32 27-FEB-15:40 19.60 12.34 0.184422E+09 306.44 27-FEB-10:00 19.60 12.34
March 0.134203E+10 1587.83 14-MAR-10:00 10.00 7.75 0.240240E+09 347.88 02-MAR-10:09 10.00 7.75
April 0.189373E+10 5049.15 27-APR-09:30 18.35 12.60 0.237620E+09 347.88 27-APR-13:00 26.10 16.83
May 0.257156E+10 7828.79 15-MAY-06:02 11.97 9.44 0.267806E+09 347.89 15-MAY-09:00 18.90 13.25
June 0.343945E+10 9839.85 25-JUN-08:52 16.70 12.03 0.273683E+09 347.88 28-JUN-13:50 24.90 15.66
July 0.377219E+10 11665.81 23-JUL-08:42 18.72 13.76 0.255212E+09 348.14 31-JUL-09:39 22.93 17.42
August 0.424926E+10 8990.13 14-AUG-06:02 15.47 13.75 0.286560E+09 348.20 14-AUG-09:00 21.10 15.94
September 0.274181E+10 5781.35 11-SEP-09:30 17.80 13.71 0.248156E+09 347.88 11-SEP-09:00 18.90 14.30
October 0.173520E+10 4022.48 04-OCT-08:30 14.75 10.13 0.239958E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.939046E+09 1248.65 02-NOV-10:40 12.43 10.47 0.207040E+09 317.56 02-NOV-10:50 12.62 10.55
December 0.478281E+09 1092.12 05-DEC-10:25 7.50 5.28 0.190338E+09 297.35 05-DEC-10:30 7.50 5.28
                     
Annual Sum or Average 0.240490E+11         0.282558E+10        
Minimum of Months 0.288421E+09 949.20   5.32 3.17 0.184422E+09 271.57   5.32 3.17
Maximum of Months 0.424926E+10 11665.81   19.60 13.76 0.286560E+09 348.20   26.10 17.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.318714E+09 1978.53 20-JAN-13:50 6.70 4.72 0.300662E+09 537.98 20-JAN-14:09 6.78 4.76
February 0.865427E+09 5967.19 27-FEB-13:08 17.88 11.31 0.293366E+09 549.51 07-FEB-14:09 17.88 11.31
March 0.183199E+10 6133.38 02-MAR-13:20 12.57 7.60 0.367376E+09 549.50 28-MAR-13:09 11.20 4.56
April 0.246133E+10 9339.53 27-APR-13:40 26.10 16.65 0.349332E+09 549.51 27-APR-13:00 26.10 16.83
May 0.311675E+10 10645.61 14-MAY-13:53 22.80 12.27 0.396964E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.355477E+10 7215.18 28-JUN-13:30 24.70 15.69 0.410567E+09 549.52 28-JUN-13:50 24.90 15.66
July 0.487753E+10 16907.99 30-JUL-14:12 26.87 17.81 0.393576E+09 549.60 31-JUL-13:00 28.30 18.92
August 0.626648E+10 13820.39 06-AUG-13:53 22.60 15.75 0.443563E+09 549.91 29-AUG-13:30 29.30 20.07
September 0.472767E+10 15578.35 10-SEP-13:42 21.93 14.56 0.380281E+09 549.95 15-SEP-13:50 21.70 16.50
October 0.301018E+10 14856.50 08-OCT-13:43 19.63 14.09 0.369154E+09 549.68 03-OCT-13:00 19.63 14.09
November 0.112274E+10 6661.19 04-NOV-13:40 20.93 15.98 0.318525E+09 549.50 15-NOV-14:00 8.90 6.49
December 0.614727E+09 4160.37 05-DEC-12:00 10.00 6.07 0.301010E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.327683E+11         0.432438E+10        
Minimum of Months 0.318714E+09 1978.53   6.70 4.72 0.293366E+09 537.98   6.78 4.56
Maximum of Months 0.626648E+10 16907.99   26.87 17.81 0.443563E+09 549.95   29.30 20.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.289025E+09 1172.37 20-JAN-15:50 5.87 4.23 0.194949E+09 284.06 20-JAN-15:00 5.60 4.08
February 0.611800E+09 2199.45 27-FEB-15:40 19.60 12.34 0.183678E+09 343.94 27-FEB-14:00 19.60 12.34
March 0.139235E+10 2973.14 02-MAR-16:30 13.05 8.47 0.230682E+09 345.03 02-MAR-14:00 13.05 8.47
April 0.190919E+10 5793.49 26-APR-17:30 23.60 13.73 0.223964E+09 347.85 27-APR-13:00 26.10 16.83
May 0.277486E+10 12394.27 14-MAY-17:11 22.60 11.84 0.262732E+09 347.85 15-MAY-09:00 18.90 13.25
June 0.318769E+10 6885.09 18-JUN-18:33 16.30 12.47 0.269369E+09 347.86 28-JUN-13:50 24.90 15.66
July 0.421567E+10 13955.86 30-JUL-17:31 26.70 17.74 0.255099E+09 347.85 28-JUL-13:39 26.70 17.74
August 0.419596E+10 11552.13 06-AUG-17:52 23.80 15.26 0.285104E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.289573E+10 10099.70 10-SEP-17:02 21.93 14.12 0.245746E+09 347.85 05-SEP-09:09 21.93 14.12
October 0.182973E+10 5861.35 04-OCT-16:00 21.10 11.40 0.232062E+09 347.84 05-OCT-13:00 16.10 10.65
November 0.972150E+09 2079.63 04-NOV-15:40 20.37 15.93 0.203907E+09 323.26 10-NOV-14:00 10.00 6.84
December 0.467301E+09 1339.46 05-DEC-15:30 8.05 5.82 0.190476E+09 311.73 05-DEC-15:39 7.40 5.40
                     
Annual Sum or Average 0.247415E+11         0.277777E+10        
Minimum of Months 0.289025E+09 1172.37   5.87 4.23 0.183678E+09 284.06   5.60 4.08
Maximum of Months 0.421567E+10 13955.86   26.70 17.74 0.285104E+09 347.88   26.70 17.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.441195E+09 1260.92 11-JAN-16:20 13.67 10.10 0.308871E+09 451.20 11-JAN-14:00 13.67 10.10
February 0.821854E+09 1515.43 28-FEB-15:00 13.90 10.81 0.291776E+09 517.03 28-FEB-14:00 13.90 10.81
March 0.169792E+10 1576.50 10-MAR-14:50 16.20 11.59 0.379982E+09 533.41 10-MAR-14:00 16.10 11.51
April 0.207869E+10 4173.43 27-APR-15:40 27.20 17.03 0.368933E+09 549.50 27-APR-13:00 27.20 17.03
May 0.308161E+10 4393.10 05-MAY-13:30 23.85 16.52 0.424749E+09 549.50 05-MAY-09:09 23.85 16.52
June 0.369959E+10 4876.19 21-JUN-15:30 24.70 15.68 0.431525E+09 549.50 09-JUN-13:09 24.70 15.68
July 0.417614E+10 5787.20 24-JUL-15:00 30.60 18.78 0.403006E+09 549.50 28-JUL-13:39 21.10 15.48
August 0.431847E+10 5321.88 25-AUG-14:00 27.40 18.74 0.451764E+09 549.54 09-AUG-09:00 27.40 18.74
September 0.276831E+10 4151.43 12-SEP-14:40 24.40 16.65 0.391256E+09 549.49 07-SEP-13:09 24.40 16.65
October 0.188546E+10 2778.76 04-OCT-15:30 21.40 11.45 0.371955E+09 549.48 05-OCT-13:00 16.10 10.65
November 0.110695E+10 1468.71 02-NOV-14:40 13.67 11.26 0.326909E+09 504.20 02-NOV-13:00 13.67 11.26
December 0.567573E+09 1198.17 05-DEC-15:00 10.00 7.01 0.300425E+09 440.52 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.266438E+11         0.445115E+10        
Minimum of Months 0.441195E+09 1198.17   10.00 7.01 0.291776E+09 440.52   10.00 7.01
Maximum of Months 0.431847E+10 5787.20   30.60 18.78 0.451764E+09 549.54   27.40 18.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342950E+09 1186.09 05-JAN-09:40 1.67 1.50 0.143333E+09 270.70 05-JAN-09:50 2.23 2.03
February 0.755033E+09 1492.43 08-FEB-10:00 2.20 1.26 0.136365E+09 316.59 08-FEB-09:00 2.20 1.26
March 0.170456E+10 3211.41 14-MAR-09:00 7.80 5.89 0.177463E+09 338.72 14-MAR-10:09 10.28 7.92
April 0.241625E+10 6993.12 27-APR-09:00 17.80 12.21 0.175150E+09 338.73 20-APR-10:09 17.80 12.21
May 0.320140E+10 12638.42 14-MAY-08:43 16.32 11.34 0.196316E+09 338.74 15-MAY-10:09 19.18 13.24
June 0.398746E+10 12156.92 25-JUN-07:42 15.32 11.39 0.200556E+09 338.73 07-JUN-10:09 15.32 11.39
July 0.424684E+10 14832.07 30-JUL-08:52 20.60 15.79 0.188048E+09 339.01 31-JUL-08:00 22.20 16.89
August 0.455934E+10 13407.33 13-AUG-08:52 20.90 15.90 0.210296E+09 338.94 10-AUG-08:00 20.90 15.90
September 0.306542E+10 8510.41 10-SEP-09:02 16.28 13.48 0.180468E+09 338.73 14-SEP-07:10 14.18 13.39
October 0.194144E+10 5444.11 04-OCT-09:00 15.60 10.49 0.171602E+09 338.73 05-OCT-10:09 14.08 9.36
November 0.941431E+09 1516.91 02-NOV-10:40 12.43 10.47 0.149067E+09 319.90 02-NOV-10:50 12.62 10.55
December 0.491553E+09 1339.66 05-DEC-10:00 6.70 5.10 0.139526E+09 291.39 05-DEC-09:00 6.70 5.10
                     
Annual Sum or Average 0.276537E+11         0.206819E+10        
Minimum of Months 0.342950E+09 1186.09   1.67 1.26 0.136365E+09 270.70   2.20 1.26
Maximum of Months 0.455934E+10 14832.07   20.90 15.90 0.210296E+09 339.01   22.20 16.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109996E+10 7396.09 20-JAN-13:20 6.70 4.72 0.324604E+09 549.49 20-JAN-14:50 7.12 4.90
February 0.202045E+10 9012.49 27-FEB-14:10 18.58 11.55 0.316748E+09 549.49 09-FEB-10:39 18.58 11.55
March 0.364077E+10 10325.66 01-MAR-13:30 11.15 5.98 0.400938E+09 549.50 14-MAR-13:00 15.60 10.50
April 0.421969E+10 11609.07 27-APR-13:10 26.10 16.37 0.376761E+09 549.95 27-APR-13:50 26.10 16.74
May 0.501802E+10 14451.44 07-MAY-13:32 20.93 15.98 0.421467E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.528971E+10 8930.60 28-JUN-13:10 24.50 15.71 0.427640E+09 549.52 28-JUN-13:39 24.80 15.68
July 0.630131E+10 19558.06 30-JUL-12:12 26.10 17.39 0.400966E+09 549.98 31-JUL-13:50 28.12 18.80
August 0.719322E+10 19029.85 06-AUG-13:13 22.00 15.46 0.450118E+09 550.48 29-AUG-13:30 29.30 20.07
September 0.609505E+10 19092.58 10-SEP-13:02 20.87 14.20 0.390960E+09 550.32 15-SEP-13:50 21.70 16.50
October 0.432503E+10 18999.02 08-OCT-13:02 18.17 13.70 0.383194E+09 549.83 04-OCT-13:00 18.17 13.70
November 0.199278E+10 9123.85 04-NOV-13:30 20.85 16.00 0.341928E+09 549.49 15-NOV-14:00 8.90 6.49
December 0.147874E+10 7886.74 05-DEC-12:30 10.30 6.13 0.322260E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.486747E+11         0.455758E+10        
Minimum of Months 0.109996E+10 7396.09   6.70 4.72 0.316748E+09 549.49   7.12 4.90
Maximum of Months 0.719322E+10 19558.06   26.10 17.39 0.450118E+09 550.48   29.30 20.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.396792E+09 1415.56 05-JAN-15:50 6.20 4.71 0.195735E+09 300.25 05-JAN-15:00 6.10 4.61
February 0.800456E+09 3601.02 27-FEB-15:30 19.70 12.30 0.186306E+09 347.83 27-FEB-14:00 19.70 12.30
March 0.174290E+10 5080.86 14-MAR-16:00 17.20 10.94 0.236047E+09 347.84 02-MAR-14:00 17.20 10.94
April 0.241722E+10 7959.95 26-APR-16:00 24.40 14.49 0.227292E+09 347.85 27-APR-13:00 26.10 16.83
May 0.342485E+10 15471.15 07-MAY-16:51 21.70 16.17 0.262556E+09 347.85 15-MAY-09:00 18.90 13.25
June 0.375899E+10 11759.40 18-JUN-16:52 17.20 12.22 0.268604E+09 347.86 28-JUN-13:39 24.80 15.68
July 0.473091E+10 16063.55 23-JUL-16:41 26.88 15.68 0.253091E+09 347.85 28-JUL-13:39 21.10 15.48
August 0.459447E+10 14089.00 06-AUG-16:32 23.53 15.27 0.283311E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.324627E+10 12684.94 10-SEP-16:22 22.20 14.33 0.241946E+09 347.85 12-SEP-13:00 24.40 16.54
October 0.199247E+10 6635.15 04-OCT-16:00 21.10 11.40 0.228083E+09 347.83 12-OCT-13:00 15.00 11.02
November 0.975139E+09 2619.95 04-NOV-15:30 20.55 15.94 0.202402E+09 335.32 10-NOV-14:00 10.00 6.84
December 0.518282E+09 1552.15 05-DEC-15:40 7.40 5.40 0.190860E+09 320.97 05-DEC-15:50 6.75 4.97
                     
Annual Sum or Average 0.285987E+11         0.277623E+10        
Minimum of Months 0.396792E+09 1415.56   6.20 4.71 0.186306E+09 300.25   6.10 4.61
Maximum of Months 0.473091E+10 16063.55   26.88 16.17 0.283311E+09 347.88   26.10 16.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 88949258.67 6509.58 02-JAN-06:11 6.10
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 88949258.67      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 88949258.67 6509.58   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.358396E+10 10944.54 09-JAN-06:07 -1.5
February 0.212911E+10 10715.65 21-FEB-06:10 1.70
March 0.129137E+10 6731.36 06-MAR-07:04 6.70
April 0.668279E+09 4946.05 19-APR-05:03 1.78
May 0.363563E+09 4169.73 11-MAY-05:03 5.10
June 0.195961E+09 4127.74 25-JUN-06:57 13.90
July 0.130174E+09 3946.54 23-JUL-06:20 14.63
August 0.162544E+09 3843.44 06-AUG-06:53 12.00
September 0.351429E+09 4900.30 10-SEP-07:32 13.67
October 0.861743E+09 3979.36 16-OCT-06:03 6.60
November 0.184940E+10 9582.80 24-NOV-07:06 1.20
December 0.305924E+10 11296.80 26-DEC-06:09 -0.8
         
Annual Sum or Average 0.146468E+11      
Minimum of Months 0.130174E+09 3843.44   -1.5
Maximum of Months 0.358396E+10 11296.80   14.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188291E+10 8843.35 02-JAN-08:20 6.70
February 0.107905E+10 6075.58 21-FEB-07:12 1.50
March 0.687205E+09 2118.06 06-MAR-10:50 9.13
April 0.286381E+09 3749.27 02-APR-11:23 16.40
May 56869601.67 4030.24 29-MAY-17:12 16.50
June 18277024.36 2789.61 18-JUN-16:52 17.20
July 28013014.34 4223.38 30-JUL-14:52 27.20
August 18581104.71 3814.77 06-AUG-14:32 23.33
September 56359350.44 4074.44 10-SEP-15:02 22.70
October 0.345423E+09 4974.33 08-OCT-13:02 18.17
November 0.878425E+09 3028.67 11-NOV-11:53 5.00
December 0.138685E+10 6670.16 26-DEC-07:20 -1.5
         
Annual Sum or Average 0.672435E+10      
Minimum of Months 18277024.36 2118.06   -1.5
Maximum of Months 0.188291E+10 8843.35   27.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149429E+10 7515.60 02-JAN-08:10 6.70
February 0.705710E+09 2977.64 21-FEB-08:20 1.47
March 0.254319E+09 2285.12 14-MAR-07:08 5.10
April 49749890.61 2791.90 02-APR-12:32 18.33
May 19444935.69 2795.16 29-MAY-16:00 16.10
June 21723517.80 2111.76 18-JUN-15:17 18.70
July 27582578.34 2682.43 30-JUL-15:31 27.60
August 18197829.84 2134.97 06-AUG-14:32 23.33
September 22737241.35 2870.12 10-SEP-16:22 22.20
October 0.102086E+09 3204.11 08-OCT-13:02 18.17
November 0.521945E+09 2818.86 13-NOV-08:09 0.78
December 0.994308E+09 3260.06 26-DEC-09:10 -0.9
         
Annual Sum or Average 0.423210E+10      
Minimum of Months 18197829.84 2111.76   -0.9
Maximum of Months 0.149429E+10 7515.60   27.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.408196E+09 13492.94 02-JAN-06:11 6.10
February 36757987.51 9684.08 21-FEB-06:01 1.70
March 1533869.93 8223.28 06-MAR-07:02 6.70
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 6186705.68 8689.57 27-NOV-07:03 11.70
December 65539719.98 10338.69 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.518214E+09      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.408196E+09 13492.94   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117864E+10 20946.38 02-JAN-06:11 6.10
February 0.410137E+09 19005.76 21-FEB-05:51 1.70
March 74945327.11 16582.26 06-MAR-06:11 6.70
April 5436401.99 14428.44 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 15048381.13 14891.52 23-OCT-06:03 10.40
November 0.231714E+09 17038.47 13-NOV-06:01 1.70
December 0.637467E+09 19851.79 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.255338E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.117864E+10 20946.38   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215275E+10 7587.70 09-JAN-05:01 0.22
February 0.107118E+10 7625.24 21-FEB-05:51 1.70
March 0.301239E+09 6868.66 06-MAR-06:11 6.70
April 72367621.60 6146.38 18-APR-05:12 3.30
May 3040801.58 5658.54 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2366428.98 5591.90 28-SEP-06:03 8.40
October 93734992.77 6188.22 30-OCT-05:12 7.20
November 0.701724E+09 7047.77 24-NOV-06:11 1.83
December 0.162992E+10 7444.53 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.602832E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.215275E+10 7625.24   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131637E+10 6866.02 09-JAN-05:01 0.22
February 0.611017E+09 6921.08 21-FEB-05:51 1.70
March 0.157365E+09 6022.52 06-MAR-06:11 6.70
April 34149814.28 5109.65 18-APR-05:12 3.30
May 3647312.86 4420.01 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2095768.06 4405.37 28-SEP-06:03 8.40
October 63079470.53 5138.01 16-OCT-05:12 7.03
November 0.433930E+09 6248.44 24-NOV-06:11 1.83
December 0.100486E+10 6673.93 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.362651E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.131637E+10 6921.08   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.163888E+10 10084.02 17-JAN-05:01 1.60
February 0.722254E+09 10229.59 21-FEB-05:51 1.70
March 0.231598E+09 9037.79 06-MAR-06:11 6.70
April 70980853.15 7682.46 18-APR-05:12 3.30
May 6278657.23 6717.44 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 3098740.73 6686.46 27-SEP-06:03 8.40
October 77479694.04 7649.36 16-OCT-05:12 7.03
November 0.537965E+09 9334.48 24-NOV-06:11 1.83
December 0.126963E+10 10085.38 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.455816E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.163888E+10 10229.59   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136412E+10 7046.04 09-JAN-05:01 0.22
February 0.647254E+09 7116.52 21-FEB-05:51 1.70
March 0.198879E+09 6195.98 06-MAR-06:11 6.70
April 53922362.31 5210.10 18-APR-05:12 3.30
May 5260081.01 4441.59 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 2661766.60 4418.39 28-SEP-06:03 8.40
October 67649705.41 5180.09 16-OCT-05:12 7.03
November 0.458891E+09 6416.99 24-NOV-06:11 1.83
December 0.104046E+10 6892.89 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.383910E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.136412E+10 7116.52   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122708E+10 5789.34 02-JAN-06:11 6.10
February 0.425968E+09 5210.67 21-FEB-06:01 1.70
March 62714623.28 4722.84 06-MAR-06:11 6.70
April 9285802.86 4417.17 19-APR-06:02 2.48
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 2659223.34 4270.15 30-OCT-06:03 7.20
November 85645385.67 4679.94 24-NOV-06:11 1.83
December 0.487597E+09 5208.68 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.230095E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.122708E+10 5789.34   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.756731E+09 5262.85 02-JAN-06:11 6.10
February 0.207948E+09 4421.28 21-FEB-06:01 1.70
March 26254775.35 3904.84 06-MAR-06:11 6.70
April 3577814.12 3505.31 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 2089806.98 3103.87 31-OCT-06:03 10.18
November 57082741.64 3896.21 24-NOV-06:11 1.83
December 0.329747E+09 4538.63 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.138343E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.756731E+09 5262.85   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.300030E+10 8548.25 06-JAN-08:00 -2.8
February 0.165248E+10 7929.31 14-FEB-07:10 0.68
March 0.116235E+10 7403.79 01-MAR-07:10 -0.1
April 0.661998E+09 7036.87 19-APR-06:10 2.48
May 0.428631E+09 6229.68 18-MAY-06:10 5.68
June 0.208377E+09 5244.39 15-JUN-06:20 9.80
July 33784648.31 4840.98 03-JUL-06:06 11.88
August 52099796.08 4933.01 18-AUG-06:10 11.63
September 0.191113E+09 5633.00 28-SEP-06:10 8.40
October 0.605948E+09 6093.60 24-OCT-06:10 6.28
November 0.145443E+10 7867.46 24-NOV-07:10 1.20
December 0.223732E+10 8621.22 26-DEC-07:50 -1.2
         
Annual Sum or Average 0.116888E+11      
Minimum of Months 33784648.31 4840.98   -2.8
Maximum of Months 0.300030E+10 8621.22   11.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.762715E+09 5437.83 02-JAN-06:11 6.10
February 0.213645E+09 4468.05 21-FEB-06:01 1.70
March 36344278.15 3999.72 06-MAR-06:11 6.70
April 6593332.92 3505.89 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 2426078.05 2933.91 28-OCT-06:03 7.80
November 58836402.95 3939.79 24-NOV-06:11 1.83
December 0.317178E+09 4644.03 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.139774E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.762715E+09 5437.83   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101557E+10 6187.15 02-JAN-06:11 6.10
February 0.329761E+09 5713.14 21-FEB-05:51 1.70
March 47061720.32 5114.61 06-MAR-06:11 6.70
April 5885950.01 4693.37 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 7706308.19 4651.84 30-OCT-06:03 7.20
November 0.160063E+09 5245.13 24-NOV-06:11 1.83
December 0.554304E+09 5921.63 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.212035E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.101557E+10 6187.15   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.659468E+09 5759.24 02-JAN-06:11 6.10
February 0.200245E+09 5110.16 21-FEB-05:51 1.70
March 27804830.89 4350.05 06-MAR-06:11 6.70
April 4340893.10 3691.42 18-APR-06:02 3.40
May 126307.89 842.05 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 8409603.36 3596.38 16-OCT-06:03 6.60
November 0.111782E+09 4541.15 24-NOV-06:11 1.83
December 0.394303E+09 5430.94 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.140648E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.659468E+09 5759.24   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.743467E+09 8440.76 02-JAN-06:11 6.10
February 0.222755E+09 7075.62 21-FEB-06:01 1.70
March 38214713.96 6376.00 06-MAR-06:11 6.70
April 7271676.30 5546.68 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 7578547.89 5405.69 16-OCT-06:03 6.60
November 0.115934E+09 6602.75 24-NOV-06:11 1.83
December 0.445450E+09 7798.95 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.158067E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.743467E+09 8440.76   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.644213E+09 5776.37 02-JAN-06:11 6.10
February 0.203641E+09 5060.03 21-FEB-05:51 1.70
March 35660890.69 4349.61 06-MAR-06:11 6.70
April 6743659.48 3668.19 18-APR-06:02 3.40
May 153639.62 1024.26 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 7975810.21 3566.20 16-OCT-06:03 6.60
November 0.112339E+09 4519.23 24-NOV-06:11 1.83
December 0.370316E+09 5432.81 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.138104E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.644213E+09 5776.37   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.250423E+12    
Minimum of Months 0.544142E+10 6443.98   0.191215E+11 14019.75  
Maximum of Months 0.648083E+10 6443.98   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.599791E+10 6443.98 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.544142E+10 6443.98 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.648083E+10 6443.98 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.577357E+10 6443.98 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.623937E+10 6443.98 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.621476E+10 6443.98 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.579818E+10 6443.98 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.648074E+10 6443.98 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.577357E+10 6443.98 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.599800E+10 6443.98 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.593174E+10 6443.98 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.579827E+10 6443.98 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.719283E+11     0.115425E+12    
Minimum of Months 0.544142E+10 6443.98   0.879311E+10 6808.32  
Maximum of Months 0.648083E+10 6443.98   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.922641E+09 1358.45 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.742986E+09 1358.45 01-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.800974E+09 1184.79 07-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.665752E+09 947.97 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.697171E+09 711.15 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.680233E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.638723E+09 947.97 12-JUL-07:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.725166E+09 947.97 02-AUG-07:30 0.212947E+10 1435.25 01-AUG-07:10
September 0.692141E+09 1184.79 21-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.792086E+09 1358.45 20-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.887470E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.927199E+09 1358.45 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.917254E+10     0.243325E+11    
Minimum of Months 0.638723E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.927199E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.556721E+09 860.01 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.458134E+09 860.01 01-FEB-16:49 0.117344E+10 908.57 01-FEB-08:09
March 0.500609E+09 750.07 03-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.420759E+09 490.21 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.444411E+09 450.21 01-MAY-14:30 0.132213E+10 908.57 01-MAY-07:10
June 0.434545E+09 450.21 08-JUN-15:30 0.129819E+10 908.57 01-JUN-07:10
July 0.407200E+09 450.21 12-JUL-07:49 0.127534E+10 908.57 03-JUL-07:10
August 0.462328E+09 490.21 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.432375E+09 750.07 21-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.487622E+09 860.01 26-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.540082E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.556228E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.570101E+10     0.154036E+11    
Minimum of Months 0.407200E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.556721E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.848693E+09 1358.45 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.698668E+09 1358.45 02-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.781477E+09 1184.79 13-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.664770E+09 947.97 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.701333E+09 711.15 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.686095E+09 711.15 13-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.647689E+09 947.97 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.731330E+09 947.97 02-AUG-07:30 0.212945E+10 1435.24 01-AUG-07:10
September 0.683670E+09 1184.79 21-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.755110E+09 1358.45 20-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.825102E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.840332E+09 1358.45 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.886427E+10     0.243324E+11    
Minimum of Months 0.647689E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.848693E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.556192E+09 859.95 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.453142E+09 859.95 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.500676E+09 750.02 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.421571E+09 600.10 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.442567E+09 490.17 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.431976E+09 490.17 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.408495E+09 750.02 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.461348E+09 710.03 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.437676E+09 750.02 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.489002E+09 859.95 18-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.538288E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.556241E+09 859.95 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.569717E+10     0.154035E+11    
Minimum of Months 0.408495E+09 490.17   0.117344E+10 908.57  
Maximum of Months 0.556241E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.915174E+09 1358.45 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.738120E+09 1358.45 01-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.796724E+09 1184.79 07-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.664256E+09 947.97 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.696174E+09 711.15 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.679488E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.638121E+09 947.97 12-JUL-07:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.723805E+09 774.31 02-AUG-07:19 0.212947E+10 1435.25 01-AUG-07:10
September 0.689780E+09 1184.79 21-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.787549E+09 1358.45 20-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.879426E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.917989E+09 1358.45 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.912661E+10     0.243325E+11    
Minimum of Months 0.638121E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.917989E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.554404E+09 860.01 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.456080E+09 860.01 01-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.498976E+09 750.07 03-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.420180E+09 490.21 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.443724E+09 450.21 05-MAY-14:20 0.132213E+10 908.57 01-MAY-07:10
June 0.434070E+09 450.21 08-JUN-15:30 0.129819E+10 908.57 01-JUN-07:10
July 0.406752E+09 450.21 12-JUL-07:49 0.127534E+10 908.57 03-JUL-07:10
August 0.461454E+09 490.21 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.431569E+09 750.07 21-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.486136E+09 860.01 26-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.537560E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.553628E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.568453E+10     0.154036E+11    
Minimum of Months 0.406752E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.554404E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.844351E+09 1358.45 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.696512E+09 1358.45 02-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.779594E+09 1184.79 13-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.663764E+09 947.97 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.700397E+09 711.15 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.685074E+09 711.15 16-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.646057E+09 947.97 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.730015E+09 774.31 02-AUG-07:19 0.212945E+10 1435.24 01-AUG-07:10
September 0.681877E+09 1184.79 21-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.752661E+09 1358.45 26-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.822189E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.836981E+09 1358.45 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.883947E+10     0.243324E+11    
Minimum of Months 0.646057E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.844351E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.553885E+09 859.95 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.450859E+09 859.95 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.498864E+09 750.02 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.420815E+09 600.10 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.441925E+09 490.17 02-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.431302E+09 450.19 05-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.407403E+09 710.03 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.460327E+09 710.03 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.436481E+09 750.02 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.486994E+09 859.95 20-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.535471E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.553114E+09 859.95 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.567744E+10     0.154035E+11    
Minimum of Months 0.407403E+09 450.19   0.117344E+10 908.57  
Maximum of Months 0.553885E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.922641E+09 1358.45 02-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.742986E+09 1358.45 01-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.800974E+09 1184.79 07-MAR-16:00 0.212947E+10 1435.25 01-MAR-08:09
April 0.665752E+09 947.97 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.697171E+09 711.15 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.680233E+09 711.15 16-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.638723E+09 947.97 12-JUL-07:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.725166E+09 947.97 02-AUG-07:30 0.212947E+10 1435.25 01-AUG-07:10
September 0.692141E+09 1184.79 21-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.792086E+09 1358.45 20-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.887470E+09 1358.45 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.927199E+09 1358.45 01-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.917254E+10     0.243325E+11    
Minimum of Months 0.638723E+09 711.15   0.185366E+10 1435.25  
Maximum of Months 0.927199E+09 1358.45   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.556721E+09 860.01 02-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.458134E+09 860.01 01-FEB-16:49 0.117344E+10 908.57 01-FEB-08:09
March 0.500609E+09 750.07 03-MAR-16:00 0.134804E+10 908.57 01-MAR-08:09
April 0.420759E+09 490.21 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.444411E+09 450.21 01-MAY-14:30 0.132213E+10 908.57 01-MAY-07:10
June 0.434545E+09 450.21 08-JUN-15:30 0.129819E+10 908.57 01-JUN-07:10
July 0.407200E+09 450.21 12-JUL-07:49 0.127534E+10 908.57 03-JUL-07:10
August 0.462328E+09 490.21 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.432375E+09 750.07 21-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.487622E+09 860.01 26-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.540082E+09 860.01 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.556228E+09 860.01 01-DEC-16:10 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.570101E+10     0.154036E+11    
Minimum of Months 0.407200E+09 450.21   0.117344E+10 908.57  
Maximum of Months 0.556721E+09 860.01   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.848693E+09 1358.45 02-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.698668E+09 1358.45 02-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.781477E+09 1184.79 13-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.664770E+09 947.97 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.701333E+09 711.15 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.686060E+09 711.15 13-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.647689E+09 947.97 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.731330E+09 947.97 02-AUG-07:30 0.212945E+10 1435.24 01-AUG-07:10
September 0.683670E+09 1184.79 21-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.755104E+09 1358.45 20-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.825064E+09 1358.45 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.840332E+09 1358.45 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.886419E+10     0.243324E+11    
Minimum of Months 0.647689E+09 711.15   0.185364E+10 1435.24  
Maximum of Months 0.848693E+09 1358.45   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.556192E+09 859.95 02-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.453076E+09 859.95 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.500676E+09 750.02 13-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.421571E+09 600.10 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.442567E+09 490.17 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.431976E+09 490.17 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.408495E+09 750.02 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.461348E+09 710.03 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.437652E+09 750.02 21-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.489002E+09 859.95 18-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.538288E+09 859.95 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.556241E+09 859.95 01-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.569708E+10     0.154035E+11    
Minimum of Months 0.408495E+09 490.17   0.117344E+10 908.57  
Maximum of Months 0.556241E+09 859.95   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.599791E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.577357E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.623937E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.621476E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.579818E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.648074E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.577357E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.599800E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.593174E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.579827E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.719283E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.544142E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.648083E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.922641E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.367911E+09
February 0.901968E+09 0.742986E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.330829E+09
March 0.107774E+10 0.800974E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.326227E+09
April 0.956342E+09 0.665752E+09 0.197726E+10 0.00 0.00 0.00 0.00 817363.76 0.319840E+09
May 0.103597E+10 0.697171E+09 0.208852E+10 0.00 0.00 0.00 0.00 19006.21 0.260677E+09
June 0.103308E+10 0.680233E+09 0.205071E+10 0.00 0.00 0.00 0.00 210034.35 0.219688E+09
July 0.959235E+09 0.638723E+09 0.201461E+10 0.00 0.00 0.00 0.00 3263980.01 0.185292E+09
August 0.107774E+10 0.725166E+09 0.212947E+10 0.00 0.00 0.00 0.00 4896275.03 0.149835E+09
September 0.956342E+09 0.692141E+09 0.197634E+10 0.00 0.00 0.00 0.00 19426.45 0.119022E+09
October 0.994195E+09 0.792086E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.260107E+09
November 0.984487E+09 0.887470E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.288087E+09
December 0.959235E+09 0.927199E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.313210E+09
                   
Annual Sum or Average 0.119305E+11 0.917254E+10 0.243325E+11 0.00 0.00 0.00 0.00 9226085.82 0.314072E+10
Minimum of Months 0.901968E+09 0.638723E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.119022E+09
Maximum of Months 0.107774E+10 0.927199E+09 0.212947E+10 0.00 0.00 0.00 0.00 4896275.03 0.367911E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.556721E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.245063E+09
February 0.571020E+09 0.458134E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.223420E+09
March 0.682301E+09 0.500609E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.219170E+09
April 0.605444E+09 0.420759E+09 0.125169E+10 0.00 0.00 0.00 0.00 509945.46 0.216486E+09
May 0.655854E+09 0.444411E+09 0.132213E+10 0.00 0.00 0.00 0.00 12672.48 0.175154E+09
June 0.654023E+09 0.434545E+09 0.129819E+10 0.00 0.00 0.00 0.00 140027.61 0.148396E+09
July 0.607275E+09 0.407200E+09 0.127534E+10 0.00 0.00 0.00 0.00 1705115.58 0.124555E+09
August 0.682301E+09 0.462328E+09 0.134804E+10 0.00 0.00 0.00 0.00 3078718.22 0.101424E+09
September 0.605444E+09 0.432375E+09 0.125111E+10 0.00 0.00 0.00 0.00 12952.00 80011696.97
October 0.629407E+09 0.487622E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.174966E+09
November 0.623262E+09 0.540082E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.191696E+09
December 0.607275E+09 0.556228E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.208803E+09
                   
Annual Sum or Average 0.755301E+10 0.570101E+10 0.154036E+11 0.00 0.00 0.00 0.00 5459431.36 0.210914E+10
Minimum of Months 0.571020E+09 0.407200E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 80011696.97
Maximum of Months 0.682301E+09 0.556721E+09 0.134804E+10 0.00 0.00 0.00 0.00 3078718.22 0.245063E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.848693E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.377285E+09
February 0.901968E+09 0.698668E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.353463E+09
March 0.107774E+10 0.781477E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.340705E+09
April 0.956342E+09 0.664770E+09 0.197725E+10 0.00 0.00 0.00 0.00 524462.22 0.331260E+09
May 0.103597E+10 0.701333E+09 0.208851E+10 0.00 0.00 0.00 0.00 19002.60 0.265582E+09
June 0.103308E+10 0.686095E+09 0.205070E+10 0.00 0.00 0.00 0.00 210021.02 0.221544E+09
July 0.959235E+09 0.647689E+09 0.201460E+10 0.00 0.00 0.00 0.00 2065271.83 0.188159E+09
August 0.107774E+10 0.731330E+09 0.212945E+10 0.00 0.00 0.00 0.00 4488443.99 0.153894E+09
September 0.956342E+09 0.683670E+09 0.197632E+10 0.00 0.00 0.00 0.00 19419.55 0.124778E+09
October 0.994195E+09 0.755110E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.276312E+09
November 0.984487E+09 0.825102E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.296628E+09
December 0.959235E+09 0.840332E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.323795E+09
                   
Annual Sum or Average 0.119305E+11 0.886427E+10 0.243324E+11 0.00 0.00 0.00 0.00 7326621.22 0.325340E+10
Minimum of Months 0.901968E+09 0.647689E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.124778E+09
Maximum of Months 0.107774E+10 0.848693E+09 0.212945E+10 0.00 0.00 0.00 0.00 4488443.99 0.377285E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.556192E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.245727E+09
February 0.570983E+09 0.453142E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.224782E+09
March 0.682256E+09 0.500676E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.220884E+09
April 0.605404E+09 0.421571E+09 0.125169E+10 0.00 0.00 0.00 0.00 229527.95 0.217182E+09
May 0.655811E+09 0.442567E+09 0.132212E+10 0.00 0.00 0.00 0.00 12672.77 0.179028E+09
June 0.653980E+09 0.431976E+09 0.129818E+10 0.00 0.00 0.00 0.00 140022.35 0.148956E+09
July 0.607235E+09 0.408495E+09 0.127533E+10 0.00 0.00 0.00 0.00 1557493.54 0.129146E+09
August 0.682256E+09 0.461348E+09 0.134804E+10 0.00 0.00 0.00 0.00 3138035.41 0.103870E+09
September 0.605404E+09 0.437676E+09 0.125110E+10 0.00 0.00 0.00 0.00 12951.76 82462414.99
October 0.629366E+09 0.489002E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.176249E+09
November 0.623221E+09 0.538288E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.192380E+09
December 0.607235E+09 0.556241E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.209478E+09
                   
Annual Sum or Average 0.755252E+10 0.569717E+10 0.154035E+11 0.00 0.00 0.00 0.00 5090703.79 0.213014E+10
Minimum of Months 0.570983E+09 0.408495E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 82462414.99
Maximum of Months 0.682256E+09 0.556241E+09 0.134804E+10 0.00 0.00 0.00 0.00 3138035.41 0.245727E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.915174E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.208720E+09
February 0.901968E+09 0.738120E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.188485E+09
March 0.107774E+10 0.796724E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.181152E+09
April 0.956342E+09 0.664256E+09 0.197726E+10 0.00 0.00 0.00 0.00 499131.53 0.173867E+09
May 0.103597E+10 0.696174E+09 0.208852E+10 0.00 0.00 0.00 0.00 11815.91 0.140811E+09
June 0.103308E+10 0.679488E+09 0.205071E+10 0.00 0.00 0.00 0.00 118678.55 0.118716E+09
July 0.959235E+09 0.638121E+09 0.201461E+10 0.00 0.00 0.00 0.00 2207571.72 0.100255E+09
August 0.107774E+10 0.723805E+09 0.212947E+10 0.00 0.00 0.00 0.00 2877157.14 81571105.90
September 0.956342E+09 0.689780E+09 0.197634E+10 0.00 0.00 0.00 0.00 11771.80 66599777.40
October 0.994195E+09 0.787549E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.151603E+09
November 0.984487E+09 0.879426E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.169771E+09
December 0.959235E+09 0.917989E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.182266E+09
                   
Annual Sum or Average 0.119305E+11 0.912661E+10 0.243325E+11 0.00 0.00 0.00 0.00 5726126.65 0.176382E+10
Minimum of Months 0.901968E+09 0.638121E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 66599777.40
Maximum of Months 0.107774E+10 0.917989E+09 0.212947E+10 0.00 0.00 0.00 0.00 2877157.14 0.208720E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.554404E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.139019E+09
February 0.571020E+09 0.456080E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.127770E+09
March 0.682301E+09 0.498976E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.123638E+09
April 0.605444E+09 0.420180E+09 0.125169E+10 0.00 0.00 0.00 0.00 262719.44 0.121159E+09
May 0.655854E+09 0.443724E+09 0.132213E+10 0.00 0.00 0.00 0.00 7877.02 97213623.21
June 0.654023E+09 0.434070E+09 0.129819E+10 0.00 0.00 0.00 0.00 79119.01 83061695.59
July 0.607275E+09 0.406752E+09 0.127534E+10 0.00 0.00 0.00 0.00 937912.96 69266383.00
August 0.682301E+09 0.461454E+09 0.134804E+10 0.00 0.00 0.00 0.00 1663630.17 57367434.49
September 0.605444E+09 0.431569E+09 0.125111E+10 0.00 0.00 0.00 0.00 7847.88 45965552.35
October 0.629407E+09 0.486136E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.103376E+09
November 0.623262E+09 0.537560E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.113179E+09
December 0.607275E+09 0.553628E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.121582E+09
                   
Annual Sum or Average 0.755301E+10 0.568453E+10 0.154036E+11 0.00 0.00 0.00 0.00 2959106.49 0.120260E+10
Minimum of Months 0.571020E+09 0.406752E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 45965552.35
Maximum of Months 0.682301E+09 0.554404E+09 0.134804E+10 0.00 0.00 0.00 0.00 1663630.17 0.139019E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.844351E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.398738E+10
February 0.901968E+09 0.696512E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.348542E+10
March 0.107774E+10 0.779594E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.367711E+10
April 0.956342E+09 0.663764E+09 0.197725E+10 0.00 0.00 0.00 0.00 14218576.93 0.275586E+10
May 0.103597E+10 0.700397E+09 0.208851E+10 0.00 0.00 0.00 0.00 1604612.63 0.242744E+10
June 0.103308E+10 0.685074E+09 0.205070E+10 0.00 0.00 0.00 0.00 15759020.08 0.185973E+10
July 0.959235E+09 0.646057E+09 0.201460E+10 0.00 0.00 0.00 0.00 93402775.55 0.120108E+10
August 0.107774E+10 0.730015E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.254795E+09 0.114947E+10
September 0.956342E+09 0.681877E+09 0.197632E+10 0.00 0.00 0.00 0.00 3498790.92 0.174945E+10
October 0.994195E+09 0.752661E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.278678E+10
November 0.984487E+09 0.822189E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.349655E+10
December 0.959235E+09 0.836981E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.385555E+10
                   
Annual Sum or Average 0.119305E+11 0.883947E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.383279E+09 0.324318E+11
Minimum of Months 0.901968E+09 0.646057E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.114947E+10
Maximum of Months 0.107774E+10 0.844351E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.254795E+09 0.398738E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.553885E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.139384E+09
February 0.570983E+09 0.450859E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.128042E+09
March 0.682256E+09 0.498864E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.123965E+09
April 0.605404E+09 0.420815E+09 0.125169E+10 0.00 0.00 0.00 0.00 143190.19 0.120519E+09
May 0.655811E+09 0.441925E+09 0.132212E+10 0.00 0.00 0.00 0.00 7877.30 99945814.80
June 0.653980E+09 0.431302E+09 0.129818E+10 0.00 0.00 0.00 0.00 79119.24 82949766.20
July 0.607235E+09 0.407403E+09 0.127533E+10 0.00 0.00 0.00 0.00 840503.48 73214135.28
August 0.682256E+09 0.460327E+09 0.134804E+10 0.00 0.00 0.00 0.00 1688384.63 59133583.10
September 0.605404E+09 0.436481E+09 0.125110E+10 0.00 0.00 0.00 0.00 7847.91 47725567.42
October 0.629366E+09 0.486994E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.103735E+09
November 0.623221E+09 0.535471E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.113255E+09
December 0.607235E+09 0.553114E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.121880E+09
                   
Annual Sum or Average 0.755252E+10 0.567744E+10 0.154035E+11 0.00 0.00 0.00 0.00 2766922.76 0.121375E+10
Minimum of Months 0.570983E+09 0.407403E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 47725567.42
Maximum of Months 0.682256E+09 0.553885E+09 0.134804E+10 0.00 0.00 0.00 0.00 1688384.63 0.139384E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.922641E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.324857E+09
February 0.901968E+09 0.742986E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.295546E+09
March 0.107774E+10 0.800974E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.291352E+09
April 0.956342E+09 0.665752E+09 0.197726E+10 0.00 0.00 0.00 0.00 667909.42 0.282975E+09
May 0.103597E+10 0.697171E+09 0.208852E+10 0.00 0.00 0.00 0.00 17144.22 0.227567E+09
June 0.103308E+10 0.680233E+09 0.205071E+10 0.00 0.00 0.00 0.00 180273.02 0.190163E+09
July 0.959235E+09 0.638723E+09 0.201461E+10 0.00 0.00 0.00 0.00 2914086.93 0.160289E+09
August 0.107774E+10 0.725166E+09 0.212947E+10 0.00 0.00 0.00 0.00 4230078.62 0.130544E+09
September 0.956342E+09 0.692141E+09 0.197634E+10 0.00 0.00 0.00 0.00 17285.12 0.105496E+09
October 0.994195E+09 0.792086E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.235669E+09
November 0.984487E+09 0.887470E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.260387E+09
December 0.959235E+09 0.927199E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.281103E+09
                   
Annual Sum or Average 0.119305E+11 0.917254E+10 0.243325E+11 0.00 0.00 0.00 0.00 8026777.33 0.278595E+10
Minimum of Months 0.901968E+09 0.638723E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.105496E+09
Maximum of Months 0.107774E+10 0.927199E+09 0.212947E+10 0.00 0.00 0.00 0.00 4230078.62 0.324857E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.556721E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.216099E+09
February 0.421807E+09 0.458134E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.199132E+09
March 0.502994E+09 0.500609E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.194647E+09
April 0.447140E+09 0.420759E+09 0.125169E+10 0.00 0.00 0.00 0.00 417695.31 0.190286E+09
May 0.484071E+09 0.444411E+09 0.132213E+10 0.00 0.00 0.00 0.00 11427.47 0.152006E+09
June 0.482240E+09 0.434545E+09 0.129819E+10 0.00 0.00 0.00 0.00 120180.98 0.127853E+09
July 0.448971E+09 0.407200E+09 0.127534E+10 0.00 0.00 0.00 0.00 1591210.18 0.107266E+09
August 0.502994E+09 0.462328E+09 0.134804E+10 0.00 0.00 0.00 0.00 2646487.96 87849782.82
September 0.447140E+09 0.432375E+09 0.125111E+10 0.00 0.00 0.00 0.00 11522.24 70357782.49
October 0.465148E+09 0.487622E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.156957E+09
November 0.460569E+09 0.540082E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.172376E+09
December 0.448971E+09 0.556228E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.187058E+09
                   
Annual Sum or Average 0.557719E+10 0.570101E+10 0.154036E+11 0.00 0.00 0.00 0.00 4798524.14 0.186189E+10
Minimum of Months 0.421807E+09 0.407200E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 70357782.49
Maximum of Months 0.502994E+09 0.556721E+09 0.134804E+10 0.00 0.00 0.00 0.00 2646487.96 0.216099E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.848693E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.333588E+09
February 0.901968E+09 0.698668E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.314626E+09
March 0.107774E+10 0.781477E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.302819E+09
April 0.956342E+09 0.664770E+09 0.197725E+10 0.00 0.00 0.00 0.00 428922.66 0.291885E+09
May 0.103597E+10 0.701333E+09 0.208851E+10 0.00 0.00 0.00 0.00 17140.85 0.231685E+09
June 0.103308E+10 0.686060E+09 0.205070E+10 0.00 0.00 0.00 0.00 180260.02 0.192213E+09
July 0.959235E+09 0.647689E+09 0.201460E+10 0.00 0.00 0.00 0.00 1802752.09 0.163009E+09
August 0.107774E+10 0.731330E+09 0.212945E+10 0.00 0.00 0.00 0.00 3780775.38 0.134135E+09
September 0.956342E+09 0.683670E+09 0.197632E+10 0.00 0.00 0.00 0.00 17211.65 0.110057E+09
October 0.994195E+09 0.755104E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.247758E+09
November 0.984487E+09 0.825064E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.267170E+09
December 0.959235E+09 0.840332E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.290208E+09
                   
Annual Sum or Average 0.119305E+11 0.886419E+10 0.243324E+11 0.00 0.00 0.00 0.00 6227062.65 0.287915E+10
Minimum of Months 0.901968E+09 0.647689E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.110057E+09
Maximum of Months 0.107774E+10 0.848693E+09 0.212945E+10 0.00 0.00 0.00 0.00 3780775.38 0.333588E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.556192E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.216720E+09
February 0.570983E+09 0.453076E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.200182E+09
March 0.682256E+09 0.500676E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.196363E+09
April 0.605404E+09 0.421571E+09 0.125169E+10 0.00 0.00 0.00 0.00 193098.75 0.191555E+09
May 0.655811E+09 0.442567E+09 0.132212E+10 0.00 0.00 0.00 0.00 11431.14 0.156235E+09
June 0.653980E+09 0.431976E+09 0.129818E+10 0.00 0.00 0.00 0.00 120183.32 0.129303E+09
July 0.607235E+09 0.408495E+09 0.127533E+10 0.00 0.00 0.00 0.00 1292979.79 0.111801E+09
August 0.682256E+09 0.461348E+09 0.134804E+10 0.00 0.00 0.00 0.00 2641020.79 90651441.91
September 0.605404E+09 0.437652E+09 0.125110E+10 0.00 0.00 0.00 0.00 11523.48 72876194.13
October 0.629366E+09 0.489002E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.158536E+09
November 0.623221E+09 0.538288E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.173100E+09
December 0.607235E+09 0.556241E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.187688E+09
                   
Annual Sum or Average 0.755252E+10 0.569708E+10 0.154035E+11 0.00 0.00 0.00 0.00 4270237.27 0.188501E+10
Minimum of Months 0.570983E+09 0.408495E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 72876194.13
Maximum of Months 0.682256E+09 0.556241E+09 0.134804E+10 0.00 0.00 0.00 0.00 2641020.79 0.216720E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.456600E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.422127E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.412568E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 587147.36 0.393344E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1265.50 0.313411E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82723.67 0.260505E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2387365.61 0.219891E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3895759.36 0.181516E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 342.80 0.148758E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.338356E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.373886E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.402632E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6954604.29 0.392359E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148758E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3895759.36 0.456600E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.552730E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.509106E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.505119E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 961360.99 0.487128E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1810.09 0.392773E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107570.39 0.327905E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3356613.06 0.275886E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5161296.20 0.227474E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 424.54 0.183906E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.407766E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.446138E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.482337E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9589075.27 0.479827E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.183906E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5161296.20 0.552730E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.551813E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.509565E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.503708E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 485196.05 0.498461E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.410961E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33220.60 0.345681E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1116742.79 0.292135E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3581808.49 0.233921E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.186639E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.403956E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.436719E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.472578E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5216967.93 0.484614E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.186639E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3581808.49 0.551813E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 6443.98 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 6443.98 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 6443.98 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 6443.98 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 6443.98 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 6443.98 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 6443.98 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 6443.98 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 6443.98 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 6443.98 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 6443.98 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 6443.98 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   6443.98   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 625.25 12-JAN-24:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 572.88 16-FEB-22:03
March 1306.65 01-MAR-10:09 1184.79 07-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 551.39 28-MAR-24:00
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 98.43 01-APR-17:03 594.59 07-APR-24:00
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 2.50 05-MAY-16:00 440.38 22-MAY-24:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 9.53 28-JUN-16:00 587.59 13-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 81.28 23-JUL-14:00 291.94 02-JUL-04:00
August 1306.65 01-AUG-09:09 947.97 02-AUG-07:30 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 43.21 13-AUG-14:53 420.37 11-AUG-04:00
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 2.99 14-SEP-17:00 272.76 18-SEP-23:00
October 1306.65 02-OCT-09:09 1358.45 20-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 528.80 31-OCT-21:05
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 594.90 29-NOV-23:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 480.34 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   272.76  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 98.43   625.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 414.08 12-JAN-24:00
February 827.22 01-FEB-10:09 860.01 01-FEB-16:49 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 381.57 16-FEB-22:03
March 827.22 01-MAR-10:09 750.07 03-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 371.96 28-MAR-24:00
April 827.22 03-APR-09:09 490.21 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 62.67 01-APR-17:03 400.31 07-APR-24:00
May 827.22 01-MAY-09:09 450.21 01-MAY-14:30 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.67 05-MAY-16:00 291.71 22-MAY-24:00
June 827.22 01-JUN-09:09 450.21 08-JUN-15:30 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 6.35 28-JUN-16:00 388.67 13-JUN-03:00
July 827.22 03-JUL-09:09 450.21 12-JUL-07:49 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 43.98 23-JUL-16:00 197.40 02-JUL-10:00
August 827.22 01-AUG-09:09 490.21 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 25.66 08-AUG-17:00 280.90 11-AUG-04:00
September 827.22 01-SEP-09:09 750.07 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.99 14-SEP-17:00 178.77 18-SEP-23:00
October 827.22 02-OCT-09:09 860.01 26-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 351.88 31-OCT-21:05
November 827.22 01-NOV-09:09 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 394.25 29-NOV-23:00
December 827.22 01-DEC-10:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 318.72 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 0.00   178.77  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 62.67   414.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 626.10 12-JAN-24:00
February 1306.65 01-FEB-10:09 1358.45 02-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 613.80 19-FEB-12:00
March 1306.65 01-MAR-10:09 1184.79 13-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 574.20 28-MAR-24:00
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 56.90 01-APR-17:20 603.64 07-APR-24:00
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 2.50 05-MAY-16:00 440.38 22-MAY-24:00
June 1306.65 01-JUN-09:09 711.15 13-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 9.53 28-JUN-16:00 584.22 13-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 53.06 23-JUL-15:40 294.20 02-JUL-04:00
August 1306.65 01-AUG-09:09 947.97 02-AUG-07:30 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 38.50 08-AUG-17:00 426.75 11-AUG-04:00
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 2.99 14-SEP-17:00 271.66 18-SEP-23:00
October 1306.65 02-OCT-09:09 1358.45 20-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 528.46 31-OCT-21:05
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 594.51 29-NOV-23:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 482.93 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   271.66  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 56.90   626.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 413.72 12-JAN-24:00
February 827.17 01-FEB-10:09 859.95 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 381.44 16-FEB-22:03
March 827.17 01-MAR-10:09 750.02 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 370.34 28-MAR-24:00
April 827.17 03-APR-09:09 600.10 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 15.13 01-APR-16:00 393.35 07-APR-24:00
May 827.17 01-MAY-09:09 490.17 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.67 05-MAY-16:00 293.15 22-MAY-24:00
June 827.17 01-JUN-09:09 490.17 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 6.35 28-JUN-16:00 386.37 13-JUN-03:00
July 827.17 03-JUL-09:09 750.02 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 39.41 23-JUL-13:13 196.94 02-JUL-04:00
August 827.17 01-AUG-09:09 710.03 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 26.18 13-AUG-12:00 288.41 11-AUG-04:00
September 827.17 01-SEP-09:09 750.02 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.99 14-SEP-17:00 178.35 18-SEP-23:00
October 827.17 02-OCT-09:09 859.95 18-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 351.62 31-OCT-21:05
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 393.43 29-NOV-23:00
December 827.17 01-DEC-10:09 859.95 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 319.25 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   490.17   908.57   0.00 0.00 0.00 0.00 0.00   178.35  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 39.41   413.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 356.19 12-JAN-24:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 326.73 16-FEB-04:00
March 1306.65 01-MAR-10:09 1184.79 07-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 306.29 28-MAR-24:00
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 64.28 01-APR-17:03 323.87 07-APR-24:00
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 1.40 05-MAY-16:00 248.67 18-MAY-05:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 5.19 28-JUN-16:00 335.69 13-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 55.14 23-JUL-14:10 166.95 02-JUL-04:00
August 1306.65 01-AUG-09:09 774.31 02-AUG-07:19 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 33.19 13-AUG-15:00 232.45 11-AUG-04:00
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 1.67 14-SEP-17:00 158.02 18-SEP-23:00
October 1306.65 02-OCT-09:09 1358.45 20-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 287.11 31-OCT-21:10
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 341.07 29-NOV-23:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 269.02 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   158.02  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 64.28   356.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 860.01 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 235.86 12-JAN-24:00
February 827.22 01-FEB-10:09 860.01 01-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 216.57 16-FEB-04:00
March 827.22 01-MAR-10:09 750.07 03-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 213.67 28-MAR-24:00
April 827.22 03-APR-09:09 490.21 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 37.45 01-APR-17:03 227.39 07-APR-24:00
May 827.22 01-MAY-09:09 450.21 05-MAY-14:20 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 0.93 05-MAY-16:00 164.87 18-MAY-05:00
June 827.22 01-JUN-09:09 450.21 08-JUN-15:30 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 3.46 28-JUN-16:00 228.53 13-JUN-03:00
July 827.22 03-JUL-09:09 450.21 12-JUL-07:49 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 23.82 23-JUL-16:10 111.57 02-JUL-04:00
August 827.22 01-AUG-09:09 490.21 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 13.77 08-AUG-17:00 161.49 11-AUG-04:00
September 827.22 01-SEP-09:09 750.07 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.12 14-SEP-17:00 104.63 18-SEP-23:00
October 827.22 02-OCT-09:09 860.01 26-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 190.94 31-OCT-21:10
November 827.22 01-NOV-09:09 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 225.94 29-NOV-23:00
December 827.22 01-DEC-10:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 178.68 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   450.21   908.57   0.00 0.00 0.00 0.00 0.00   104.63  
Maximum of Months 827.22   860.01   908.57   0.00 0.00 0.00 0.00 37.45   235.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 19123.84 06-JAN-07:01
February 1306.65 01-FEB-10:09 1358.45 02-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 17629.33 09-FEB-07:01
March 1306.65 01-MAR-10:09 1184.79 13-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17235.46 01-MAR-07:01
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 2392.12 27-APR-16:10 14856.99 19-APR-06:02
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 508.35 05-MAY-16:10 12085.43 11-MAY-06:03
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 2152.84 28-JUN-17:00 9391.05 15-JUN-06:05
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 3809.60 31-JUL-16:10 8306.48 03-JUL-06:02
August 1306.65 01-AUG-09:09 774.31 02-AUG-07:19 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 6055.23 10-AUG-17:00 9385.85 01-AUG-06:02
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 802.39 14-SEP-17:00 10200.12 27-SEP-06:03
October 1306.65 02-OCT-09:09 1358.45 26-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 12269.66 13-OCT-06:03
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 16150.03 24-NOV-07:01
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 18605.40 26-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   8306.48  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 6055.23   19123.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 235.75 12-JAN-24:00
February 827.17 01-FEB-10:09 859.95 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 215.79 16-FEB-04:00
March 827.17 01-MAR-10:09 750.02 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 208.72 28-MAR-24:00
April 827.17 03-APR-09:09 600.10 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 12.56 01-APR-17:03 215.67 07-APR-24:00
May 827.17 01-MAY-09:09 490.17 02-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 0.93 05-MAY-16:00 166.55 22-MAY-24:00
June 827.17 01-JUN-09:09 450.19 05-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 3.46 28-JUN-16:00 222.63 13-JUN-03:00
July 827.17 03-JUL-09:09 710.03 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 22.62 23-JUL-13:45 115.64 02-JUL-04:00
August 827.17 01-AUG-09:09 710.03 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 13.77 08-AUG-17:00 167.15 11-AUG-04:00
September 827.17 01-SEP-09:09 750.02 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.12 14-SEP-17:00 104.34 18-SEP-23:00
October 827.17 02-OCT-09:09 859.95 20-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 191.03 31-OCT-21:10
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 225.51 29-NOV-23:00
December 827.17 01-DEC-10:09 859.95 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 178.90 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   450.19   908.57   0.00 0.00 0.00 0.00 0.00   104.34  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 22.62   235.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 556.41 12-JAN-24:00
February 1306.65 01-FEB-10:09 1358.45 01-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 510.46 16-FEB-04:00
March 1306.65 01-MAR-10:09 1184.79 07-MAR-16:00 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 495.19 28-MAR-24:00
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 84.51 01-APR-17:03 523.72 07-APR-24:00
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 2.14 05-MAY-16:00 387.32 18-MAY-05:00
June 1306.65 01-JUN-09:09 711.15 16-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 8.03 28-JUN-16:00 524.90 13-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 75.98 23-JUL-14:10 261.50 02-JUL-04:00
August 1306.65 01-AUG-09:09 947.97 02-AUG-07:30 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 43.75 13-AUG-15:00 366.15 11-AUG-04:00
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 2.55 14-SEP-17:00 245.51 18-SEP-23:00
October 1306.65 02-OCT-09:09 1358.45 20-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 446.27 31-OCT-21:10
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 524.43 29-NOV-23:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 418.64 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.25   0.00 0.00 0.00 0.00 0.00   245.51  
Maximum of Months 1306.65   1358.45   1435.25   0.00 0.00 0.00 0.00 84.51   556.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 860.01 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 367.63 12-JAN-24:00
February 805.43 01-FEB-08:09 860.01 01-FEB-16:49 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 337.62 16-FEB-04:00
March 805.43 01-MAR-08:09 750.07 03-MAR-16:00 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 332.57 28-MAR-24:00
April 805.43 03-APR-07:10 490.21 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 54.76 01-APR-17:03 351.40 07-APR-24:00
May 805.43 01-MAY-07:10 450.21 01-MAY-14:30 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.43 05-MAY-16:00 255.17 22-MAY-24:00
June 805.43 01-JUN-07:10 450.21 08-JUN-15:30 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 5.35 28-JUN-16:00 347.15 13-JUN-03:00
July 805.43 03-JUL-07:10 450.21 12-JUL-07:49 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 44.25 23-JUL-16:10 172.69 02-JUL-04:00
August 805.43 01-AUG-07:10 490.21 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 23.68 13-AUG-15:00 244.54 11-AUG-04:00
September 805.43 01-SEP-07:10 750.07 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.70 14-SEP-17:00 160.55 18-SEP-23:00
October 805.43 02-OCT-07:10 860.01 26-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 296.45 31-OCT-21:05
November 805.43 01-NOV-07:10 860.01 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 347.29 29-NOV-23:00
December 805.43 01-DEC-08:09 860.01 01-DEC-16:10 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 277.68 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   450.21   908.57   0.00 0.00 0.00 0.00 0.00   160.55  
Maximum of Months 805.43   860.01   908.57   0.00 0.00 0.00 0.00 54.76   367.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1358.45 02-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 556.85 12-JAN-24:00
February 1306.65 01-FEB-10:09 1358.45 02-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 550.78 19-FEB-12:00
March 1306.65 01-MAR-10:09 1184.79 13-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 513.34 28-MAR-24:00
April 1306.65 03-APR-09:09 947.97 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 49.51 01-APR-17:03 530.90 07-APR-24:00
May 1306.65 01-MAY-09:09 711.15 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 2.14 05-MAY-16:00 385.78 22-MAY-24:00
June 1306.65 01-JUN-09:09 711.15 13-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 8.03 28-JUN-16:00 522.51 13-JUN-03:00
July 1306.65 03-JUL-09:09 947.97 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 48.31 23-JUL-15:27 263.29 02-JUL-04:00
August 1306.65 01-AUG-09:09 947.97 02-AUG-07:30 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 32.19 08-AUG-17:00 371.39 11-AUG-04:00
September 1306.65 01-SEP-09:09 1184.79 21-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 2.55 14-SEP-17:00 245.09 18-SEP-23:00
October 1306.65 02-OCT-09:09 1358.45 20-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 445.58 31-OCT-21:05
November 1306.65 01-NOV-09:09 1358.45 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 524.04 29-NOV-23:00
December 1306.65 01-DEC-10:09 1358.45 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 421.44 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   711.15   1435.24   0.00 0.00 0.00 0.00 0.00   245.09  
Maximum of Months 1306.65   1358.45   1435.24   0.00 0.00 0.00 0.00 49.51   556.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 859.95 02-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 367.61 12-JAN-24:00
February 827.17 01-FEB-10:09 859.95 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 336.47 16-FEB-04:00
March 827.17 01-MAR-10:09 750.02 13-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 332.01 28-MAR-24:00
April 827.17 03-APR-09:09 600.10 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 12.70 01-APR-16:00 346.75 07-APR-24:00
May 827.17 01-MAY-09:09 490.17 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.43 05-MAY-16:00 256.85 22-MAY-24:00
June 827.17 01-JUN-09:09 490.17 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 5.35 28-JUN-16:00 345.82 13-JUN-03:00
July 827.17 03-JUL-09:09 750.02 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 34.45 23-JUL-13:45 176.20 02-JUL-04:00
August 827.17 01-AUG-09:09 710.03 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 21.55 13-AUG-12:20 250.79 11-AUG-04:00
September 827.17 01-SEP-09:09 750.02 21-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.70 14-SEP-17:00 160.95 18-SEP-23:00
October 827.17 02-OCT-09:09 859.95 18-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 296.36 31-OCT-21:05
November 827.17 01-NOV-09:09 859.95 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 346.67 29-NOV-23:00
December 827.17 01-DEC-10:09 859.95 01-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 278.25 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   490.17   908.57   0.00 0.00 0.00 0.00 0.00   160.95  
Maximum of Months 827.17   859.95   908.57   0.00 0.00 0.00 0.00 34.45   367.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 791.44 28-JAN-04:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 734.20 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 706.16 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.98 01-APR-17:03 732.55 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.92 05-MAY-16:00 548.62 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.55 28-JUN-15:00 737.64 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69.74 23-JUL-13:53 368.28 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.77 13-AUG-15:10 504.38 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42 14-SEP-17:00 339.57 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 634.07 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 743.38 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 593.28 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   339.57  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.98   791.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 971.87 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 892.58 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 873.57 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.20 01-APR-17:03 922.06 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.25 05-MAY-16:00 681.71 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.55 28-JUN-15:00 925.39 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 100.43 23-JUL-13:53 457.53 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.79 13-AUG-15:10 641.27 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48 14-SEP-17:00 417.01 30-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 770.29 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 904.07 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 729.24 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   417.01  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.20   971.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 945.33 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 856.64 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 829.06 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.99 01-APR-17:03 909.85 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 658.84 22-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.89 28-JUN-17:00 874.91 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.54 24-JUL-14:00 433.15 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.44 08-AUG-17:00 630.78 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 405.17 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 793.69 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 903.47 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 750.94 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   405.17  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.99   945.33  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11809.99 13-JAN-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
February 14969.83 28-FEB-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
March 17025.71 02-MAR-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
April 36721.64 28-APR-06:02 6352.64 10740.11 50974.24 0.00 0.00 0.00 0.00 0.00 0.00
May 37258.86 08-MAY-06:03 5082.11 8592.08 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
June 39552.48 29-JUN-05:12 2541.06 2863.91 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
July 40612.30 17-JUL-05:12 2541.06 2863.91 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
August 40236.62 11-AUG-05:12 2541.06 2863.91 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
September 38666.19 05-SEP-06:02 7623.17 12888.13 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
October 37535.15 10-OCT-06:02 7623.17 12888.13 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
November 17269.00 06-NOV-17:00 6035.01 6443.98 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
December 14062.18 06-DEC-15:50 6035.01 6443.98 13979.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11809.99   2541.06 2863.91 13979.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40612.30   7623.17 12888.13 61169.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 246.89 11-JAN-17:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.39
February 2085.25 27-FEB-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.01
March 3045.56 14-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37.89
April 8553.18 27-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.64 0.00
May 8815.11 15-MAY-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.56
June 8826.98 28-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.82
July 9964.81 24-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.54 0.00
August 10160.22 10-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.69 0.00
September 7899.03 14-SEP-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.84
October 5553.08 04-OCT-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.90
November 2502.75 04-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.60
December 439.53 02-DEC-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.68
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 246.89   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10160.22   0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.54 116.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1844.32 14-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.41
February 2035.28 04-FEB-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.63
March 2651.61 02-MAR-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95.64
April 2941.17 27-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.06 0.00
May 3065.21 15-MAY-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.99
June 3463.81 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.37 0.00
July 4447.06 31-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.59 0.00
August 4531.76 14-AUG-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00 0.00
September 3547.58 14-SEP-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.69
October 2361.92 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.56
November 1809.12 09-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.01
December 1647.71 02-DEC-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.45
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1647.71   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4531.76   0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.59 142.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2308.47 13-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.89
February 2472.43 10-FEB-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.24
March 3216.89 02-MAR-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.83
April 3442.70 28-APR-06:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.39
May 3651.13 08-MAY-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.46
June 3884.09 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.45 0.00
July 4973.89 31-JUL-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.44 0.00
August 5070.97 14-AUG-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.20 0.00
September 4373.81 11-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.24
October 3208.54 05-OCT-06:06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.03
November 2660.26 10-NOV-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.68
December 2151.95 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.20
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2151.95   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5070.97   0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.44 126.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6959.14 12-JAN-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 7910.31 28-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 9568.31 02-MAR-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14910.01 27-APR-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 15366.77 15-MAY-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 21474.95 12-JUN-06:02 6352.64 10740.11 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 22945.59 25-JUL-05:12 2541.06 2863.91 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
August 29269.19 14-AUG-06:02 6352.64 10740.11 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 16243.73 11-SEP-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 14427.44 04-OCT-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 8469.41 06-NOV-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7325.39 06-DEC-16:20 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6959.14   2541.06 2863.91 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29269.19   6352.64 10740.11 15129.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6696.18 11-JAN-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 7737.72 28-FEB-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 8572.44 02-MAR-17:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 16284.96 27-APR-15:50 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 16945.92 15-MAY-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 17799.86 28-JUN-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
July 19115.00 24-JUL-15:20 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
August 19102.45 14-AUG-15:30 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
September 17069.28 14-SEP-15:50 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 14239.63 04-OCT-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 7579.10 02-NOV-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7012.47 05-DEC-16:00 6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6696.18   6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19115.00   6035.01 6443.98 6808.32 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1226.26 11-JAN-16:20 1272.23 1358.45 1435.25 0.00 0.00 0.00 0.00 0.00 49.83
February 1507.11 27-FEB-16:20 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 10.52
March 1593.79 10-MAR-14:50 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 32.89
April 4520.89 27-APR-15:20 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.94 0.00
May 4739.53 15-MAY-14:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 2.55
June 5214.89 21-JUN-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 2.21 0.00
July 6284.14 24-JUL-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 20.14 0.00
August 5725.22 09-AUG-15:20 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 23.60 0.00
September 4295.41 12-SEP-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 1.10 0.00
October 2684.03 04-OCT-15:30 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 14.03
November 1439.31 02-NOV-14:40 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 26.78
December 1145.75 29-DEC-16:00 1272.23 1358.45 1435.25 0.00 0.00 0.00 0.00 0.00 41.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1145.75   1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6284.14   1306.65 1358.45 1435.25 0.00 0.00 0.00 0.00 23.60 49.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1099.56 20-JAN-10:45 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 17.57
February 1415.66 27-FEB-15:50 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 6.13
March 2716.03 14-MAR-09:45 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 22.54
April 6710.31 27-APR-09:20 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 10.57
May 6926.99 15-MAY-09:10 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 12.21
June 13854.65 25-JUN-08:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 61.13
July 12667.41 30-JUL-09:02 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 43.72
August 12890.34 13-AUG-09:12 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 69.92
September 10433.76 10-SEP-10:13 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 47.15
October 4749.71 04-OCT-09:20 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 19.81
November 1411.51 02-NOV-10:40 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 25.49
December 1193.60 05-DEC-10:25 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 34.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1099.56   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 6.13
Maximum of Months 13854.65   1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 69.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6922.77 20-JAN-13:25 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 14.18
February 8862.26 27-FEB-14:30 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 13.16
March 10004.74 14-MAR-13:40 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 19.24
April 12108.75 27-APR-13:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 7.08 0.00
May 18064.91 14-MAY-13:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 134.11
June 9443.97 28-JUN-13:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 2.03 0.00
July 18067.63 23-JUL-13:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 9.00 0.00
August 18511.76 13-AUG-13:12 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 4.10
September 22231.54 10-SEP-13:32 401.76 215.99 2870.47 0.00 0.00 0.00 0.00 0.00 74.33
October 17143.91 08-OCT-13:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 115.50
November 8976.40 04-NOV-13:30 137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
December 6983.43 05-DEC-12:30 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 0.00 37.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6922.77   137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22231.54   2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 9.00 134.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1441.25 05-JAN-15:50 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 35.25
February 3502.44 27-FEB-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 7.78
March 5201.56 14-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 9.99
April 8217.78 26-APR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.73 0.00
May 14878.63 14-MAY-16:22 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 72.25
June 12018.50 18-JUN-16:52 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 141.65
July 15671.72 23-JUL-16:52 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 17.46
August 15054.84 06-AUG-16:52 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 46.12
September 15818.29 10-SEP-16:12 254.33 136.73 1817.13 0.00 0.00 0.00 0.00 0.00 41.45
October 6653.72 04-OCT-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 10.42
November 2497.36 04-NOV-15:30 84.78 68.36 353.33 0.00 0.00 0.00 0.00 0.00 2.52
December 1560.15 05-DEC-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 30.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1441.25   84.78 68.36 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15818.29   805.38 410.20 1817.13 0.00 0.00 0.00 0.00 0.73 141.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1191.75 11-JAN-16:20 1272.23 1358.45 1435.25 0.00 0.00 0.00 0.00 0.00 26.01
February 1398.39 28-FEB-15:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 1452.77 10-MAR-14:40 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 16.35
April 2696.07 27-APR-16:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 6.99 0.00
May 3213.76 05-MAY-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 1.08 0.00
June 3970.09 21-JUN-15:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 1.56 0.00
July 4883.65 24-JUL-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 10.79 0.00
August 4550.20 09-AUG-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 12.88 0.00
September 3383.15 14-SEP-15:50 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.45 0.00
October 2104.91 04-OCT-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 7.31
November 1471.97 06-NOV-12:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 26.33
December 1169.26 29-DEC-16:10 1272.23 1358.45 1435.25 0.00 0.00 0.00 0.00 0.00 22.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1169.26   1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4883.65   1306.65 1358.45 1435.25 0.00 0.00 0.00 0.00 12.88 26.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 949.20 20-JAN-10:45 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 9.44
February 1147.32 27-FEB-15:40 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 2.95
March 1587.83 14-MAR-10:00 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 11.18
April 5049.15 27-APR-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 5.39
May 7828.79 15-MAY-06:02 847.82 683.72 2019.05 0.00 0.00 0.00 0.00 0.00 7.95
June 9839.85 25-JUN-08:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 31.28
July 11665.81 23-JUL-08:42 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 57.00
August 8990.13 14-AUG-06:02 847.82 683.72 2019.05 0.00 0.00 0.00 0.00 0.00 8.36
September 5781.35 11-SEP-09:30 827.22 410.22 908.57 0.00 0.00 0.00 0.00 0.00 6.51
October 4022.48 04-OCT-08:30 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 11.51
November 1248.65 02-NOV-10:40 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 14.09
December 1092.12 05-DEC-10:25 1654.44 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 18.90
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 949.20   211.95 113.95 908.57 0.00 0.00 0.00 0.00 0.00 2.95
Maximum of Months 11665.81   1654.44 820.45 2019.05 0.00 0.00 0.00 0.00 0.00 57.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1978.53 20-JAN-13:50 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 1946.63
February 5967.19 27-FEB-13:08 5088.93 2591.92 5740.95 0.00 0.00 0.00 0.00 0.00 665.40
March 6133.38 02-MAR-13:20 2544.47 1295.96 2870.47 0.00 0.00 0.00 0.00 0.00 1263.08
April 9339.53 27-APR-13:40 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 221.82 0.00
May 10645.61 14-MAY-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 65.76
June 7215.18 28-JUN-13:30 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 75.22 0.00
July 16907.99 30-JUL-14:12 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 1.02
August 13820.39 06-AUG-13:53 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 33.04
September 15578.35 10-SEP-13:42 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 28.71
October 14856.50 08-OCT-13:43 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 55.48
November 6661.19 04-NOV-13:40 137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
December 4160.37 05-DEC-12:00 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 1557.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1978.53   137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16907.99   5088.93 2591.92 5740.95 0.00 0.00 0.00 0.00 221.82 1946.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1172.37 20-JAN-15:50 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 16.44
February 2199.45 27-FEB-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 4.18
March 2973.14 02-MAR-16:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 6.14
April 5793.49 26-APR-17:30 84.78 136.73 403.81 0.00 0.00 0.00 0.00 0.00 0.52
May 12394.27 14-MAY-17:11 0.00 159.52 1710.93 0.00 0.00 0.00 0.00 0.00 37.56
June 6885.09 18-JUN-18:33 0.00 68.36 733.26 0.00 0.00 0.00 0.00 0.00 75.42
July 13955.86 30-JUL-17:31 0.00 182.31 1955.35 0.00 0.00 0.00 0.00 0.00 13.32
August 11552.13 06-AUG-17:52 0.00 113.94 1222.09 0.00 0.00 0.00 0.00 0.00 20.52
September 10099.70 10-SEP-17:02 0.00 113.94 1222.09 0.00 0.00 0.00 0.00 0.00 18.04
October 5861.35 04-OCT-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 5.44
November 2079.63 04-NOV-15:40 84.78 68.36 353.33 0.00 0.00 0.00 0.00 0.00 0.93
December 1339.46 05-DEC-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 16.24
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1172.37   0.00 68.36 353.33 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 13955.86   805.38 410.20 1955.35 0.00 0.00 0.00 0.00 0.00 75.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1260.92 11-JAN-16:20 1272.23 1358.45 1435.25 0.00 0.00 0.00 0.00 0.00 43.23
February 1515.43 28-FEB-15:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 1576.50 10-MAR-14:50 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 27.86
April 4173.43 27-APR-15:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 10.86 0.00
May 4393.10 05-MAY-13:30 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.46
June 4876.19 21-JUN-15:30 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 1.91 0.00
July 5787.20 24-JUL-15:00 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 16.83 0.00
August 5321.88 25-AUG-14:00 1306.65 647.98 1435.25 0.00 0.00 0.00 0.00 7.30 0.00
September 4151.43 12-SEP-14:40 1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.98 0.00
October 2778.76 04-OCT-15:30 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 11.57
November 1468.71 02-NOV-14:40 1272.23 711.15 1435.25 0.00 0.00 0.00 0.00 0.00 23.13
December 1198.17 05-DEC-15:00 1306.65 947.97 1435.25 0.00 0.00 0.00 0.00 0.00 32.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1198.17   1272.23 647.98 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5787.20   1306.65 1358.45 1435.25 0.00 0.00 0.00 0.00 16.83 43.23



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1186.09 05-JAN-09:40 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 29.72
February 1492.43 08-FEB-10:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 27.17
March 3211.41 14-MAR-09:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 25.33
April 6993.12 27-APR-09:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 9.32
May 12638.42 14-MAY-08:43 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 98.49
June 12156.92 25-JUN-07:42 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 72.36
July 14832.07 30-JUL-08:52 254.35 136.74 1817.15 0.00 0.00 0.00 0.00 0.00 44.89
August 13407.33 13-AUG-08:52 211.95 113.95 1514.29 0.00 0.00 0.00 0.00 0.00 71.95
September 8510.41 10-SEP-09:02 169.56 91.16 1211.43 0.00 0.00 0.00 0.00 0.00 49.12
October 5444.11 04-OCT-09:00 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 17.58
November 1516.91 02-NOV-10:40 805.43 410.22 908.57 0.00 0.00 0.00 0.00 0.00 22.27
December 1339.66 05-DEC-10:00 1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 43.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1186.09   169.56 91.16 908.57 0.00 0.00 0.00 0.00 0.00 9.32
Maximum of Months 14832.07   1610.86 820.45 1817.15 0.00 0.00 0.00 0.00 0.00 98.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7396.09 20-JAN-13:20 5088.93 2591.92 5740.95 0.00 0.00 0.00 0.00 0.00 7.86
February 9012.49 27-FEB-14:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 12.19
March 10325.66 01-MAR-13:30 1272.23 647.98 1435.24 0.00 0.00 0.00 0.00 0.00 27.03
April 11609.07 27-APR-13:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 5.97 0.00
May 14451.44 07-MAY-13:32 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 100.71
June 8930.60 28-JUN-13:10 1306.65 647.98 1435.24 0.00 0.00 0.00 0.00 1.79 0.00
July 19558.06 30-JUL-12:12 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 17.75
August 19029.85 06-AUG-13:13 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 61.65
September 19092.58 10-SEP-13:02 334.80 179.99 2392.06 0.00 0.00 0.00 0.00 0.00 63.60
October 18999.02 08-OCT-13:02 267.84 143.99 1913.65 0.00 0.00 0.00 0.00 0.00 97.00
November 9123.85 04-NOV-13:30 137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
December 7886.74 05-DEC-12:30 687.71 647.98 1275.77 0.00 0.00 0.00 0.00 0.00 31.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7396.09   137.54 107.99 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19558.06   5088.93 2591.92 5740.95 0.00 0.00 0.00 0.00 5.97 100.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1415.56 05-JAN-15:50 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 29.92
February 3601.02 27-FEB-15:30 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 6.43
March 5080.86 14-MAR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 8.29
April 7959.95 26-APR-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.66 0.00
May 15471.15 07-MAY-16:51 296.72 159.52 2119.99 0.00 0.00 0.00 0.00 0.00 63.01
June 11759.40 18-JUN-16:52 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 117.35
July 16063.55 23-JUL-16:41 339.11 182.31 2422.85 0.00 0.00 0.00 0.00 0.00 34.39
August 14089.00 06-AUG-16:32 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 38.49
September 12684.94 10-SEP-16:22 211.94 113.94 1514.28 0.00 0.00 0.00 0.00 0.00 28.14
October 6635.15 04-OCT-16:00 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 8.60
November 2619.95 04-NOV-15:30 84.78 68.36 353.33 0.00 0.00 0.00 0.00 0.00 2.09
December 1552.15 05-DEC-15:40 805.38 410.20 908.57 0.00 0.00 0.00 0.00 0.00 26.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1415.56   84.78 68.36 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16063.55   805.38 410.20 2422.85 0.00 0.00 0.00 0.00 0.66 117.35



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.105259E+12 89656.10 13-JAN-16:00 0.737719E+11 176288.92 02-JAN-06:19
February 0.937959E+11 87194.73 27-FEB-15:09 0.405490E+11 167465.41 21-FEB-07:10
March 0.107007E+12 84290.88 14-MAR-15:00 0.148220E+11 111612.20 06-MAR-07:10
April 0.100528E+12 127074.12 27-APR-15:09 0.499324E+10 88072.26 18-APR-06:10
May 0.109605E+12 120144.66 15-MAY-15:30 0.146421E+10 45140.29 18-MAY-06:10
June 0.113604E+12 128412.38 28-JUN-15:30 0.567481E+09 16918.70 15-JUN-06:10
July 0.121667E+12 147725.11 31-JUL-15:20 0.141737E+09 8908.58 03-JUL-06:19
August 0.136232E+12 153056.31 10-AUG-15:20 0.158510E+09 15843.61 03-AUG-06:19
September 0.109829E+12 128225.24 14-SEP-15:20 0.626433E+09 33051.28 28-SEP-06:10
October 0.104389E+12 108690.14 04-OCT-15:09 0.487242E+10 76888.53 16-OCT-06:10
November 0.102234E+12 89684.52 07-NOV-16:00 0.289281E+11 138717.42 24-NOV-07:10
December 0.103479E+12 89715.04 06-DEC-16:30 0.560296E+11 185997.07 26-DEC-07:19
             
Annual Sum or Average 0.130763E+13     0.226925E+12    
Minimum of Months 0.937959E+11 84290.88   0.141737E+09 8908.58  
Maximum of Months 0.136232E+12 153056.31   0.737719E+11 185997.07  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.266300E+11 0.628818E+10 0.605851E+11 0.225896E+10 0.433443E+10 0.331264E+09 0.00 835790.50 0.00 0.00 0.00 0.482995E+10 0.00
February 0.233716E+11 0.491554E+10 0.548702E+11 0.204972E+10 0.383191E+10 0.185756E+09 0.00 0.159379E+09 0.00 0.00 0.00 0.441175E+10 0.00
March 0.271841E+11 0.442863E+10 0.627783E+11 0.235662E+10 0.478553E+10 78354267.96 0.00 0.248815E+09 0.00 0.00 0.00 0.514712E+10 0.00
April 0.238354E+11 0.340219E+10 0.586172E+11 0.219329E+10 0.542213E+10 35625990.84 0.00 0.249558E+10 0.00 0.00 0.00 0.452637E+10 0.00
May 0.255713E+11 0.290318E+10 0.616817E+11 0.230719E+10 0.723976E+10 21193658.31 0.00 0.520298E+10 0.00 0.00 0.00 0.467754E+10 0.00
June 0.253399E+11 0.254241E+10 0.604966E+11 0.226931E+10 0.879261E+10 16044964.93 0.00 0.966970E+10 0.00 0.00 0.00 0.447775E+10 0.00
July 0.236971E+11 0.273940E+10 0.597911E+11 0.223007E+10 0.109559E+11 12975675.43 0.00 0.181118E+11 0.00 0.00 0.00 0.412887E+10 0.00
August 0.265782E+11 0.320959E+10 0.627783E+11 0.235614E+10 0.125899E+11 13633839.51 0.00 0.241991E+11 0.00 0.00 0.00 0.450678E+10 0.00
September 0.240521E+11 0.386004E+10 0.585950E+11 0.219219E+10 0.819364E+10 15819591.30 0.00 0.879591E+10 0.00 0.00 0.00 0.412397E+10 0.00
October 0.255550E+11 0.500879E+10 0.605962E+11 0.225951E+10 0.537511E+10 35674106.70 0.00 0.117239E+10 0.00 0.00 0.00 0.438631E+10 0.00
November 0.261517E+11 0.580107E+10 0.591197E+11 0.220160E+10 0.408270E+10 0.135233E+09 0.00 0.268617E+09 0.00 0.00 0.00 0.447352E+10 0.00
December 0.260165E+11 0.653724E+10 0.597800E+11 0.223029E+10 0.407096E+10 0.251783E+09 0.00 21297.05 0.00 0.00 0.00 0.459198E+10 0.00
                           
Annual Sum or Average 0.303983E+12 0.516363E+11 0.719689E+12 0.269049E+11 0.796746E+11 0.113336E+10 0.00 0.703252E+11 0.00 0.00 0.00 0.542819E+11 0.00
Minimum of Months 0.233716E+11 0.254241E+10 0.548702E+11 0.204972E+10 0.383191E+10 12975675.43 0.00 21297.05 0.00 0.00 0.00 0.412397E+10 0.00
Maximum of Months 0.271841E+11 0.653724E+10 0.627783E+11 0.235662E+10 0.125899E+11 0.331264E+09 0.00 0.241991E+11 0.00 0.00 0.00 0.514712E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.737719E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.405490E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.148220E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.499324E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 0.146421E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.567481E+09 0.00 0.00 0.00 0.00
July 0.00 0.00 0.141737E+09 0.00 0.00 0.00 0.00
August 0.00 0.00 0.158510E+09 0.00 0.00 0.00 0.00
September 0.00 0.00 0.626433E+09 0.00 0.00 0.00 0.00
October 0.00 0.00 0.487242E+10 0.00 0.00 0.00 0.00
November 0.00 0.00 0.289281E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.560296E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.226925E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.141737E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.737719E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 32642.50 02-JAN-08:09 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 02-JAN-08:09 7962.60 02-JAN-07:10 556.02 02-JAN-07:10 0.00 01-JAN-00:10
February 32642.50 02-FEB-16:00 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 02-FEB-08:09 6354.14 21-FEB-07:10 551.01 21-FEB-07:10 0.00 01-FEB-00:10
March 30940.97 22-MAR-07:10 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 01-MAR-12:09 5660.25 02-MAR-15:30 471.37 06-MAR-07:10 0.00 01-MAR-00:10
April 28290.68 03-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 04-APR-11:09 18184.16 27-APR-14:30 365.85 18-APR-06:10 0.00 01-APR-00:10
May 26379.99 17-MAY-07:10 3328.83 01-MAY-19:19 41699.26 01-MAY-07:10 1410.29 01-MAY-11:09 18850.36 15-MAY-14:50 214.16 18-MAY-06:10 0.00 01-MAY-00:10
June 26260.02 16-JUN-07:10 3328.83 01-JUN-19:00 41699.26 01-JUN-07:10 1410.29 05-JUN-16:10 19299.69 28-JUN-15:20 98.45 14-JUN-06:10 0.00 01-JUN-00:10
July 28580.47 12-JUL-07:49 3328.83 01-JUL-20:10 41699.26 03-JUL-07:10 1410.29 12-JUL-11:09 25815.42 31-JUL-14:50 55.76 03-JUL-06:19 0.00 01-JUL-00:10
August 27943.37 02-AUG-07:30 5686.19 16-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-11:09 27002.48 10-AUG-15:20 91.52 18-AUG-06:19 0.00 01-AUG-00:10
September 30940.97 21-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 05-SEP-11:09 22141.97 11-SEP-15:30 178.31 28-SEP-06:10 0.00 01-SEP-00:10
October 32642.50 26-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 10-OCT-11:09 15595.02 04-OCT-15:20 326.47 16-OCT-06:10 0.00 01-OCT-00:10
November 32642.50 01-NOV-07:10 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 02-NOV-16:10 4812.29 24-NOV-07:10 516.61 24-NOV-07:10 0.00 01-NOV-00:10
December 32642.50 01-DEC-16:19 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 04-DEC-12:09 6983.29 26-DEC-07:10 568.43 26-DEC-07:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 26260.02   3328.83   41699.26   1410.29   4812.29   55.76   0.00  
Maximum of Months 32642.50   5686.19   41699.26   1410.29   27002.48   568.43   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 456.46 03-JAN-07:30 0.00 0.00 0.00 6463.99 27-JAN-12:30 0.00
February 9577.45 27-FEB-15:09 0.00 0.00 0.00 6514.45 09-FEB-12:20 0.00
March 8521.98 18-MAR-15:00 0.00 0.00 0.00 6420.25 03-MAR-12:20 0.00
April 36271.22 27-APR-14:00 0.00 0.00 0.00 6250.80 03-APR-11:39 0.00
May 29379.32 04-MAY-14:00 0.00 0.00 0.00 6199.99 01-MAY-11:20 0.00
June 35870.81 28-JUN-15:30 0.00 0.00 0.00 5815.84 01-JUN-11:20 0.00
July 50708.33 24-JUL-14:00 0.00 0.00 0.00 5767.43 03-JUL-11:30 0.00
August 53443.20 29-AUG-15:30 0.00 0.00 0.00 5699.25 29-AUG-11:20 0.00
September 34079.06 14-SEP-15:30 0.00 0.00 0.00 5776.64 29-SEP-11:30 0.00
October 20617.14 04-OCT-14:00 0.00 0.00 0.00 5828.89 31-OCT-11:20 0.00
November 13450.73 04-NOV-14:20 0.00 0.00 0.00 6210.38 29-NOV-12:00 0.00
December 19.43 27-DEC-07:10 0.00 0.00 0.00 6261.88 29-DEC-12:39 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 19.43   0.00 0.00 0.00 5699.25   0.00
Maximum of Months 53443.20   0.00 0.00 0.00 6514.45   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 89656.10 13-JAN-16:00 32642.50 41670.51 5686.19 1410.29 3075.57 188.88 0.00 0.00 0.00
February 87194.73 27-FEB-15:09 25681.07 41659.26 0.00 1410.29 5046.99 6.85 0.00 9577.45 0.00
March 84290.88 14-MAR-15:00 25681.07 41670.51 0.00 1410.29 5493.47 6.85 0.00 5047.89 0.00
April 127074.12 27-APR-15:09 25681.07 41670.51 0.00 1410.29 17590.82 6.85 0.00 36104.28 0.00
May 120144.66 15-MAY-15:30 25681.07 41670.51 0.00 1410.29 18594.86 6.85 0.00 28168.94 0.00
June 128412.38 28-JUN-15:30 25681.07 41670.51 0.00 1410.29 19280.60 6.85 0.00 35870.81 0.00
July 147725.11 31-JUL-15:20 25681.07 41670.51 0.00 1410.29 25722.61 6.89 0.00 48984.22 0.00
August 153056.31 10-AUG-15:20 25681.07 41670.51 0.00 1410.29 27002.48 6.91 0.00 53036.74 0.00
September 128225.24 14-SEP-15:20 25681.07 41670.51 0.00 1410.29 21210.51 6.90 0.00 33988.99 0.00
October 108690.14 04-OCT-15:09 25681.07 41670.51 0.00 1410.29 15357.52 6.85 0.00 20311.82 0.00
November 89684.52 07-NOV-16:00 32642.50 41670.51 5686.19 1410.29 3659.00 6.85 0.00 0.00 0.00
December 89715.04 06-DEC-16:30 32642.50 41670.51 5686.19 1410.29 3291.52 107.53 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 84290.88   25681.07 41659.26 0.00 1410.29 3075.57 6.85 0.00 0.00 0.00
Maximum of Months 153056.31   32642.50 41670.51 5686.19 1410.29 27002.48 188.88 0.00 53036.74 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 176288.92 02-JAN-06:19 0.00 0.00 0.00
February 0.00 0.00 167465.41 21-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 111612.20 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 88072.26 18-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 45140.29 18-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 16918.70 15-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 8908.58 03-JUL-06:19 0.00 0.00 0.00
August 0.00 0.00 15843.61 03-AUG-06:19 0.00 0.00 0.00
September 0.00 0.00 33051.28 28-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 76888.53 16-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 138717.42 24-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 185997.07 26-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 8908.58   0.00 0.00 0.00
Maximum of Months 0.00 0.00 185997.07   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.46 2.17 19.46 0.00 19.46 0.00 19.46
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.17 19.46 2.17 19.46 0.00 19.46 0.00 19.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.46 2.17 19.46 0.00 19.46 0.00 19.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 19.16 3.17 19.16 0.00 19.16 0.00 19.16
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.17 19.16 3.17 19.16 0.00 19.16 0.00 19.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.16 3.17 19.16 0.00 19.16 0.00 19.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 19.25 3.67 19.25 0.00 19.25 0.00 19.25
February 0.50 19.48 0.50 19.48 0.00 19.48 0.00 19.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.33 19.28 1.17 19.42 0.00 19.42 0.00 19.42
                 
Annual Sum or Average 5.50 19.28 5.33 19.31 0.00 19.31 0.00 19.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.67 19.48 3.67 19.48 0.00 19.48 0.00 19.48



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.33 18.87 8.50 18.98 0.00 18.98 0.00 18.98
February 3.50 18.48 2.83 18.78 0.00 18.78 0.00 18.78
March 0.17 19.15 0.17 19.15 0.00 19.15 0.00 19.15
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 19.18 0.67 19.18 0.00 19.18 0.00 19.18
December 5.50 19.13 5.00 19.25 0.00 19.25 0.00 19.25
                 
Annual Sum or Average 19.17 18.88 17.17 19.03 0.00 19.03 0.00 19.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9.33 19.18 8.50 19.25 0.00 19.25 0.00 19.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 18.57 3.33 18.78 0.00 18.78 0.00 18.78
February 0.83 19.31 0.83 19.31 0.00 19.31 0.00 19.31
March 0.17 19.35 0.17 19.35 0.00 19.35 0.00 19.35
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 27.63 1.00 27.63
June 0.00 0.00 0.00 0.00 1.00 27.82 1.00 27.82
July 0.00 0.00 0.00 0.00 2.67 28.06 2.67 28.06
August 0.00 0.00 0.00 0.00 2.67 27.97 2.67 27.97
September 0.00 0.00 0.00 0.00 0.83 27.75 0.83 27.75
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.03 0.17 19.03 0.00 19.03 0.00 19.03
December 2.33 19.02 2.00 19.22 0.00 19.22 0.00 19.22
                 
Annual Sum or Average 7.50 18.82 6.50 19.00 8.17 22.28 8.17 23.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 19.35 3.33 19.35 2.67 28.06 2.67 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 19.20 3.00 19.33 0.00 19.33 0.00 19.33
February 0.67 19.24 0.67 19.24 0.00 19.24 0.00 19.24
March 0.17 19.37 0.17 19.37 0.00 19.37 0.00 19.37
April 0.00 0.00 0.00 0.00 0.33 27.47 0.33 27.47
May 0.00 0.00 0.00 0.00 1.50 27.67 1.50 27.67
June 0.00 0.00 0.00 0.00 1.00 27.45 1.00 27.45
July 0.00 0.00 0.00 0.00 2.50 27.92 2.50 27.92
August 0.00 0.00 0.00 0.00 2.67 28.04 2.67 28.04
September 0.00 0.00 0.00 0.00 1.67 28.20 1.67 28.20
October 0.00 0.00 0.00 0.00 0.33 27.79 0.33 27.79
November 0.17 19.08 0.17 19.08 0.00 19.08 0.00 19.08
December 1.83 18.95 1.50 19.20 0.00 19.20 0.00 19.20
                 
Annual Sum or Average 6.17 19.13 5.50 19.28 10.00 23.25 10.00 24.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.08 0.00 19.08
Maximum of Months 3.33 19.37 3.00 19.37 2.67 28.20 2.67 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.83 18.67 3.33 18.85 0.00 18.85 0.00 18.85
February 0.83 19.40 0.83 19.40 0.00 19.40 0.00 19.40
March 0.17 19.36 0.17 19.36 0.00 19.36 0.00 19.36
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.33 28.07 2.67 28.08
June 0.00 0.00 0.00 0.00 2.00 27.96 1.00 27.98
July 0.00 0.00 0.00 0.00 4.83 28.36 2.50 28.36
August 0.00 0.00 0.00 0.00 3.33 28.23 1.67 28.27
September 0.00 0.00 0.00 0.00 1.50 27.95 1.17 27.95
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.07 0.17 19.07 0.00 19.07 0.00 19.07
December 2.00 18.99 1.67 19.22 0.00 19.22 0.00 19.22
                 
Annual Sum or Average 7.00 18.87 6.17 19.04 16.00 24.05 9.00 25.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.83 19.40 3.33 19.40 4.83 28.36 2.67 28.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.17 19.29 4.17 19.29 0.00 19.29 0.00 19.29
February 0.17 19.13 0.17 19.13 0.00 19.13 0.00 19.13
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.76 0.33 19.76 0.00 19.76 0.00 19.76
                 
Annual Sum or Average 4.67 19.32 4.67 19.32 0.00 19.32 0.00 19.32
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.17 19.76 4.17 19.76 0.00 19.76 0.00 19.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 19.15 2.83 19.26 0.00 19.26 0.00 19.26
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
July 0.00 0.00 0.00 0.00 2.33 27.69 2.33 27.69
August 0.00 0.00 0.00 0.00 2.17 27.72 2.17 27.72
September 0.00 0.00 0.00 0.00 0.83 27.47 0.83 27.47
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.32 0.17 19.32 0.00 19.32 0.00 19.32
                 
Annual Sum or Average 3.17 19.15 3.00 19.27 6.00 23.40 6.00 24.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 19.32 2.83 19.32 2.33 27.72 2.33 27.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 71.50 18.41 71.50 18.41 0.00 18.41 0.00 18.41
February 43.00 18.63 43.00 18.63 0.00 18.63 0.00 18.63
March 35.33 19.15 35.33 19.15 0.00 19.15 0.00 19.15
April 17.83 19.22 17.83 19.22 0.17 19.26 0.17 19.29
May 8.50 19.90 8.50 19.90 0.00 19.90 0.00 19.90
June 0.17 20.43 0.17 20.43 0.00 20.43 0.00 20.43
July 0.00 0.00 0.00 0.00 1.50 27.52 1.50 27.52
August 0.00 0.00 0.00 0.00 2.17 27.65 2.17 27.65
September 2.00 19.90 2.00 19.90 1.67 22.25 1.67 23.54
October 14.50 19.91 14.50 19.91 0.67 20.08 0.67 20.24
November 43.83 19.14 43.83 19.14 0.00 19.14 0.00 19.14
December 60.33 18.59 60.33 18.59 0.00 18.59 0.00 18.59
                 
Annual Sum or Average 297.00 18.85 297.00 18.85 6.17 18.94 6.17 19.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.41 0.00 18.41
Maximum of Months 71.50 20.43 71.50 20.43 2.17 27.65 2.17 27.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 18.71 2.67 19.03 0.00 19.03 0.00 19.03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 2.17 27.75 1.00 27.72
June 0.00 0.00 0.00 0.00 1.17 27.52 0.33 27.49
July 0.00 0.00 0.00 0.00 3.83 28.06 1.33 28.06
August 0.00 0.00 0.00 0.00 3.00 27.85 1.33 27.84
September 0.00 0.00 0.00 0.00 0.67 27.96 0.50 27.97
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.33 0.17 19.33 0.00 19.33 0.00 19.33
                 
Annual Sum or Average 3.33 18.74 2.83 19.04 10.83 24.67 4.50 25.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.33 2.67 19.33 3.83 28.06 1.33 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.67 19.19 3.50 19.24 0.00 19.24 0.00 19.24
February 0.17 19.18 0.17 19.18 0.00 19.18 0.00 19.18
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 19.78 1.00 19.78 0.00 19.78 0.00 19.78
                 
Annual Sum or Average 4.83 19.31 4.67 19.35 0.00 19.35 0.00 19.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.67 19.78 3.50 19.78 0.00 19.78 0.00 19.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.34 2.00 19.43 0.00 19.43 0.00 19.43
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.33 27.65 1.33 27.65
June 0.00 0.00 0.00 0.00 1.17 27.83 1.17 27.83
July 0.00 0.00 0.00 0.00 2.83 28.11 2.83 28.11
August 0.00 0.00 0.00 0.00 2.67 28.06 2.67 28.06
September 0.00 0.00 0.00 0.00 1.17 27.77 1.17 27.77
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.90 0.33 19.90 0.00 19.90 0.00 19.90
                 
Annual Sum or Average 2.50 19.41 2.33 19.49 9.17 25.03 9.17 26.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.90 2.00 19.90 2.83 28.11 2.83 28.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 19.46 2.00 19.46 0.00 19.46 0.00 19.46
February 0.00 0.00 0.00 0.00 0.17 27.30 0.17 27.30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
May 0.00 0.00 0.00 0.00 1.67 27.58 1.67 27.58
June 0.00 0.00 0.00 0.00 0.67 27.41 0.67 27.41
July 0.00 0.00 0.00 0.00 2.67 27.77 2.67 27.77
August 0.00 0.00 0.00 0.00 2.83 27.90 2.83 27.90
September 0.00 0.00 0.00 0.00 1.67 28.17 1.67 28.17
October 0.00 0.00 0.00 0.00 0.67 27.74 0.67 27.74
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.36 0.17 19.36 0.17 22.00 0.17 23.32
                 
Annual Sum or Average 2.17 19.45 2.17 19.45 11.17 25.45 11.17 26.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 19.46 2.00 19.46 2.83 28.17 2.83 28.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.33 2.00 19.41 0.00 19.41 0.00 19.41
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.00 28.08 2.33 28.07
June 0.00 0.00 0.00 0.00 2.00 27.88 1.00 27.87
July 0.00 0.00 0.00 0.00 4.83 28.25 2.17 28.27
August 0.00 0.00 0.00 0.00 3.33 28.11 1.67 28.12
September 0.00 0.00 0.00 0.00 1.67 27.86 1.50 27.85
October 0.00 0.00 0.00 0.00 0.17 27.33 0.17 27.33
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.90 0.33 19.90 0.00 19.90 0.00 19.90
                 
Annual Sum or Average 2.50 19.40 2.33 19.48 16.00 26.09 8.83 26.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.90 2.00 19.90 4.83 28.25 2.33 28.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.50 22.99 32.00 22.79 32.00 22.62
February 409.50 23.64 0.00 23.64 0.00 23.64
March 290.83 23.93 7.33 23.96 0.00 23.96
April 88.33 23.96 94.83 24.61 0.00 24.61
May 1.17 24.00 210.00 24.87 0.00 24.87
June 0.00 0.00 272.50 24.74 0.00 24.74
July 0.00 0.00 409.33 24.64 0.00 24.64
August 0.00 0.00 469.83 24.47 0.00 24.47
September 0.00 0.00 349.00 24.66 0.00 24.66
October 43.67 23.86 102.33 25.01 0.00 25.01
November 282.00 23.78 31.00 23.91 0.00 23.91
December 488.67 23.59 0.00 23.59 0.00 23.59
             
Annual Sum or Average 2105.67 23.55 1978.17 24.08 32.00 24.05
Minimum of Months 0.00 0.00 0.00 22.79 0.00 22.62
Maximum of Months 501.50 24.00 469.83 25.01 32.00 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.37 109.50 21.15 109.50 20.99
February 452.00 22.04 34.33 21.93 34.33 21.84
March 511.00 22.96 0.17 22.96 0.17 22.96
April 357.50 23.33 29.17 23.44 0.00 23.44
May 186.17 23.55 60.83 23.78 0.00 23.78
June 72.17 23.59 129.33 24.18 0.00 24.18
July 8.50 23.55 279.50 24.39 0.00 24.39
August 22.50 23.52 359.33 24.26 0.00 24.26
September 74.33 23.33 168.17 24.11 0.00 24.11
October 345.33 23.09 8.50 23.14 0.00 23.14
November 471.17 22.41 1.00 22.40 1.00 22.40
December 497.00 21.79 23.83 21.73 23.83 21.67
             
Annual Sum or Average 3499.67 22.48 1203.67 22.83 168.83 22.74
Minimum of Months 8.50 21.37 0.17 21.15 0.00 20.99
Maximum of Months 511.00 23.59 359.33 24.39 109.50 24.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.73 225.83 20.47 225.83 20.33
February 454.00 21.27 128.33 21.03 128.33 20.87
March 514.00 22.17 29.67 22.08 29.67 22.00
April 404.00 22.78 17.33 22.85 0.17 22.85
May 270.17 23.19 44.00 23.34 0.00 23.34
June 149.17 23.40 89.83 23.74 0.00 23.74
July 78.00 23.47 238.00 24.09 0.00 24.09
August 74.33 23.36 289.83 24.05 0.00 24.05
September 217.50 23.15 103.00 23.50 0.00 23.50
October 449.33 22.51 3.50 22.50 3.50 22.48
November 489.00 21.58 75.50 21.41 75.50 21.27
December 497.00 21.00 171.50 20.78 171.50 20.65
             
Annual Sum or Average 4098.50 21.99 1416.33 22.09 634.50 21.89
Minimum of Months 74.33 20.73 3.50 20.47 0.00 20.33
Maximum of Months 514.00 23.47 289.83 24.09 225.83 24.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.08 388.67 19.96 388.67 19.91
February 454.00 20.48 258.50 20.27 258.50 20.17
March 514.00 21.24 139.50 21.03 139.50 20.89
April 432.67 22.10 57.67 22.00 44.33 21.86
May 313.83 22.64 52.00 22.85 1.17 22.84
June 185.50 23.08 91.67 23.47 0.00 23.47
July 121.17 23.23 240.33 23.89 0.00 23.89
August 139.50 23.13 271.50 23.82 0.00 23.82
September 296.83 22.61 75.33 22.92 0.83 22.91
October 484.50 21.69 52.33 21.53 52.33 21.40
November 489.00 20.71 219.50 20.49 219.50 20.37
December 497.00 20.26 367.17 20.14 367.17 20.10
             
Annual Sum or Average 4430.00 21.38 2214.17 21.38 1472.00 21.12
Minimum of Months 121.17 20.08 52.00 19.96 0.00 19.91
Maximum of Months 514.00 23.23 388.67 23.89 388.67 23.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.11 377.50 19.98 377.50 19.93
February 454.00 20.62 239.67 20.42 239.67 20.32
March 508.67 21.40 110.00 21.16 110.00 21.00
April 339.67 22.00 85.00 22.11 34.67 21.97
May 266.33 22.45 127.83 23.06 4.83 23.07
June 158.00 22.96 212.17 23.77 3.50 23.80
July 120.17 23.37 308.50 24.09 10.17 24.15
August 124.67 23.37 329.67 24.03 13.17 24.11
September 262.67 22.40 152.17 23.09 4.83 23.10
October 440.33 21.62 58.00 21.53 46.50 21.40
November 489.00 20.72 202.67 20.51 202.67 20.39
December 497.00 20.29 347.33 20.16 347.33 20.10
             
Annual Sum or Average 4162.50 21.32 2550.50 21.58 1394.83 21.33
Minimum of Months 120.17 20.11 58.00 19.98 3.50 19.93
Maximum of Months 508.67 23.37 377.50 24.09 377.50 24.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.67 20.42 314.50 20.19 313.67 20.08
February 410.00 20.92 201.50 20.77 186.67 20.62
March 422.33 21.34 131.00 21.27 102.33 21.10
April 327.33 21.93 118.83 22.24 39.17 22.09
May 282.00 22.43 134.17 23.04 8.83 23.08
June 206.50 22.80 168.83 23.51 3.00 23.53
July 154.67 23.19 279.33 23.96 10.17 24.03
August 159.17 23.19 309.33 23.93 12.00 24.01
September 248.17 22.54 193.33 23.32 7.67 23.36
October 371.50 21.68 125.33 22.07 40.00 21.94
November 456.33 20.92 190.67 20.82 168.67 20.66
December 471.83 20.56 290.33 20.36 287.17 20.25
             
Annual Sum or Average 4006.50 21.50 2457.17 21.82 1179.33 21.57
Minimum of Months 154.67 20.42 118.83 20.19 3.00 20.08
Maximum of Months 496.67 23.19 314.50 23.96 313.67 24.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.12 383.00 20.00 383.00 19.95
February 450.00 20.62 246.67 20.41 246.00 20.30
March 488.33 21.18 142.67 21.02 134.50 20.88
April 379.00 21.74 97.17 21.90 45.33 21.77
May 314.33 22.44 119.50 22.96 15.17 23.04
June 225.33 22.77 167.33 23.44 4.33 23.48
July 157.83 23.18 284.17 23.97 12.83 24.05
August 173.17 22.99 280.17 23.81 9.50 23.88
September 296.33 22.42 143.17 23.05 7.67 23.09
October 451.50 21.48 73.50 21.48 49.83 21.35
November 484.83 20.71 212.50 20.51 210.50 20.40
December 497.00 20.33 354.17 20.19 354.17 20.13
             
Annual Sum or Average 4419.67 21.33 2504.00 21.53 1472.83 21.30
Minimum of Months 157.83 20.12 73.50 20.00 4.33 19.95
Maximum of Months 502.00 23.18 383.00 23.97 383.00 24.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.41 358.00 20.30 358.00 20.26
February 454.00 20.76 222.17 20.61 222.17 20.54
March 514.00 21.36 75.67 21.25 75.67 21.16
April 463.33 22.19 9.17 22.17 6.50 22.15
May 383.50 23.01 21.17 23.07 0.00 23.07
June 215.50 23.38 51.67 23.55 0.00 23.55
July 86.00 23.49 209.50 24.02 0.00 24.02
August 104.33 23.41 262.33 23.96 0.00 23.96
September 288.17 23.12 68.50 23.33 0.00 23.33
October 484.67 22.34 0.50 22.34 0.50 22.33
November 489.00 21.33 87.83 21.19 87.83 21.08
December 497.00 20.69 275.50 20.58 275.50 20.53
             
Annual Sum or Average 4481.50 21.75 1642.00 21.75 1026.17 21.54
Minimum of Months 86.00 20.41 0.50 20.30 0.00 20.26
Maximum of Months 514.00 23.49 358.00 24.02 358.00 24.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.43 344.67 20.32 344.67 20.27
February 454.00 20.96 192.50 20.81 192.50 20.72
March 513.33 21.72 44.67 21.61 44.67 21.51
April 360.50 22.50 40.50 22.63 4.67 22.60
May 258.00 22.88 100.33 23.34 0.00 23.34
June 107.00 23.26 210.83 24.06 0.67 24.07
July 68.67 23.84 330.33 24.33 8.33 24.38
August 62.83 23.84 370.50 24.26 9.33 24.32
September 204.00 23.04 183.17 23.68 2.67 23.70
October 410.50 22.35 20.00 22.46 0.00 22.46
November 489.00 21.35 75.67 21.22 75.67 21.11
December 497.00 20.73 242.33 20.60 242.33 20.54
             
Annual Sum or Average 3926.83 21.69 2155.50 22.04 925.50 21.83
Minimum of Months 62.83 20.43 20.00 20.32 0.00 20.27
Maximum of Months 513.33 23.84 370.50 24.33 344.67 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.50 20.31 316.33 20.09 316.33 20.00
February 435.33 20.99 143.17 20.75 139.17 20.57
March 467.17 21.40 62.17 21.25 56.33 21.10
April 379.00 21.95 72.33 22.15 20.17 22.03
May 338.33 22.37 81.00 22.79 2.50 22.76
June 242.33 22.67 114.83 23.29 0.00 23.29
July 119.50 22.93 284.50 24.00 4.00 24.03
August 113.67 23.00 325.17 24.01 7.33 24.06
September 200.33 22.68 222.00 23.64 6.33 23.69
October 353.67 22.09 90.00 22.62 4.17 22.61
November 459.50 21.10 100.00 21.05 80.83 20.88
December 481.17 20.65 244.83 20.44 241.33 20.32
             
Annual Sum or Average 4089.50 21.52 2056.33 21.87 878.50 21.63
Minimum of Months 113.67 20.31 62.17 20.09 0.00 20.00
Maximum of Months 499.50 23.00 325.17 24.01 316.33 24.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.44 345.50 20.33 345.50 20.28
February 452.67 20.93 191.17 20.76 191.17 20.66
March 499.83 21.49 62.00 21.38 61.83 21.28
April 393.67 22.18 45.67 22.38 5.50 22.35
May 290.17 22.93 108.00 23.37 2.33 23.39
June 173.33 23.18 164.00 23.77 0.33 23.77
July 57.00 23.85 349.50 24.38 7.50 24.43
August 71.33 23.51 355.50 24.19 6.50 24.23
September 195.67 23.02 194.50 23.73 2.17 23.74
October 431.67 22.22 23.17 22.35 0.00 22.35
November 483.83 21.26 85.00 21.15 82.67 21.05
December 497.00 20.74 255.50 20.61 255.50 20.55
             
Annual Sum or Average 4048.17 21.64 2179.50 21.99 961.00 21.78
Minimum of Months 57.00 20.44 23.17 20.33 0.00 20.28
Maximum of Months 502.00 23.85 355.50 24.38 345.50 24.43



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.39 316.50 20.23 316.50 20.16
February 454.00 20.87 187.33 20.65 187.33 20.53
March 514.00 21.77 54.17 21.64 54.17 21.53
April 420.33 22.59 22.00 22.64 4.00 22.62
May 273.17 23.10 57.00 23.29 0.00 23.29
June 127.17 23.41 104.17 23.79 0.00 23.79
July 55.00 23.50 268.17 24.13 0.00 24.13
August 70.00 23.38 309.50 24.05 0.00 24.05
September 234.50 23.08 99.67 23.42 0.00 23.42
October 466.17 22.29 9.17 22.27 7.17 22.24
November 489.00 21.23 120.67 21.04 120.67 20.91
December 497.00 20.63 265.33 20.49 265.33 20.42
             
Annual Sum or Average 4102.33 21.71 1813.67 21.82 955.17 21.59
Minimum of Months 55.00 20.39 9.17 20.23 0.00 20.16
Maximum of Months 514.00 23.50 316.50 24.13 316.50 24.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.28 285.50 20.13 285.50 20.07
February 385.00 20.90 162.50 20.71 162.50 20.60
March 422.17 21.64 44.50 21.50 44.50 21.39
April 292.50 22.34 49.33 22.58 5.67 22.54
May 234.67 22.85 99.50 23.35 3.83 23.39
June 125.00 23.24 165.67 23.95 4.83 24.00
July 85.33 23.71 256.83 24.30 9.83 24.38
August 85.50 23.60 284.83 24.20 10.00 24.28
September 213.83 22.84 129.67 23.45 4.00 23.49
October 367.67 21.99 29.17 22.09 8.33 22.05
November 417.00 21.08 110.17 20.89 110.17 20.77
December 422.00 20.56 235.50 20.41 235.50 20.34
             
Annual Sum or Average 3477.67 21.60 1853.17 21.90 884.67 21.68
Minimum of Months 85.33 20.28 29.17 20.13 3.83 20.07
Maximum of Months 427.00 23.71 285.50 24.30 285.50 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 490.17 20.75 243.33 20.53 239.67 20.40
February 394.33 21.26 135.83 21.19 114.83 21.03
March 405.33 21.81 73.17 21.86 40.17 21.74
April 298.33 22.38 93.50 22.84 5.00 22.82
May 249.67 22.92 142.17 23.47 5.17 23.51
June 160.83 23.15 189.67 23.81 2.00 23.83
July 99.17 23.57 306.00 24.21 9.17 24.27
August 101.00 23.60 341.17 24.16 11.83 24.23
September 190.00 23.03 220.33 23.76 6.50 23.81
October 343.83 22.25 102.17 22.77 5.33 22.77
November 445.17 21.40 113.67 21.40 86.33 21.25
December 460.83 20.94 204.67 20.77 197.50 20.65
             
Annual Sum or Average 3638.67 21.83 2165.67 22.30 723.50 22.10
Minimum of Months 99.17 20.75 73.17 20.53 2.00 20.40
Maximum of Months 490.17 23.60 341.17 24.21 239.67 24.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.42 310.83 20.26 310.83 20.19
February 445.67 20.94 171.17 20.74 170.67 20.63
March 481.33 21.59 66.00 21.50 57.17 21.39
April 364.17 22.21 65.17 22.50 7.00 22.46
May 280.83 22.93 131.33 23.42 10.17 23.51
June 173.33 23.11 185.83 23.75 3.67 23.78
July 102.33 23.62 314.83 24.24 12.83 24.32
August 113.33 23.36 327.00 24.07 9.33 24.13
September 240.83 22.91 170.50 23.54 6.83 23.59
October 433.67 22.00 39.83 22.13 9.00 22.10
November 482.33 21.11 119.50 20.97 115.50 20.85
December 497.00 20.68 252.33 20.52 252.33 20.44
             
Annual Sum or Average 4116.83 21.64 2154.33 21.96 965.33 21.76
Minimum of Months 102.33 20.42 39.83 20.26 3.67 20.19
Maximum of Months 502.00 23.62 327.00 24.24 310.83 24.32



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.98847 31.35816 -0.0434 6.63173
February 454.00000 23.70706 31.18595 0.15414 5.85900
March 514.00000 24.11702 29.84220 0.27449 6.69998
April 485.00000 24.34480 32.55679 0.37061 8.14933
May 508.00000 24.39505 36.25002 -0.4260 9.24724
June 496.00000 24.41117 38.20328 -0.3822 8.56025
July 497.00000 24.52654 42.33540 -0.3076 7.65396
August 514.00000 24.42955 45.55966 -0.3067 7.52912
September 485.00000 24.47746 43.11202 -0.3374 8.06137
October 502.00000 24.37063 35.86059 0.40050 8.63655
November 489.00000 24.01995 35.90165 0.27665 6.94828
December 497.00000 23.59932 31.41149 0.12367 5.58547
           
Annual Sum or Average 5943.00000 24.11811 36.16525 -0.0191 7.47464
Minimum of Months 454.00000 22.98847 29.84220 -0.4260 5.58547
Maximum of Months 514.00000 24.52654 45.55966 0.40050 9.24724



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.37193 34.19431 -0.4029 9.89857
February 454.00000 22.04845 34.43878 -0.2186 7.05319
March 514.00000 22.96875 33.03034 0.00976 5.57133
April 485.00000 23.56255 35.07480 0.18501 6.26941
May 508.00000 23.91876 38.03238 -0.6032 13.11705
June 496.00000 24.08251 39.55881 -0.5137 10.82278
July 497.00000 24.22615 43.53060 -0.4298 9.19414
August 514.00000 24.17968 46.74298 -0.4161 8.94039
September 485.00000 24.04243 44.91120 -0.5081 10.86246
October 502.00000 23.43660 38.99909 0.17510 6.23773
November 489.00000 22.46621 39.87926 -0.0794 6.10344
December 497.00000 21.79191 34.97230 -0.2843 7.34611
           
Annual Sum or Average 5943.00000 23.18344 38.63932 -0.2581 8.46495
Minimum of Months 454.00000 21.37193 33.03034 -0.6032 5.57133
Maximum of Months 514.00000 24.22615 46.74298 0.18501 13.11705



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.73132 35.14616 -0.5771 14.05593
February 454.00000 21.27389 35.53041 -0.4189 10.47014
March 514.00000 22.17078 34.33164 -0.1839 6.73554
April 485.00000 23.00753 36.10963 0.05178 6.14899
May 508.00000 23.59576 38.76612 -0.7150 16.86466
June 496.00000 23.90187 39.90618 -0.5768 12.49229
July 497.00000 24.06720 43.70186 -0.4825 10.31523
August 514.00000 24.02491 46.90066 -0.4719 10.15394
September 485.00000 23.67046 45.93362 -0.6417 14.60815
October 502.00000 22.67688 40.86734 -0.0105 6.11626
November 489.00000 21.58498 41.87432 -0.3014 8.17953
December 497.00000 21.00178 36.35059 -0.4951 11.21399
           
Annual Sum or Average 5943.00000 22.65337 39.64046 -0.4023 10.61611
Minimum of Months 454.00000 20.73132 34.33164 -0.7150 6.11626
Maximum of Months 514.00000 24.06720 46.90066 0.05178 16.86466



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.07707 36.84456 -0.7790 20.33735
February 454.00000 20.47594 37.31273 -0.6418 16.10024
March 514.00000 21.24243 36.96356 -0.4134 9.99103
April 485.00000 22.30786 38.12369 -0.1147 7.30024
May 508.00000 23.18214 40.39173 -0.8473 22.63555
June 496.00000 23.71379 40.96116 -0.6328 14.70184
July 497.00000 23.93932 44.29361 -0.5123 11.51688
August 514.00000 23.85425 47.99465 -0.5215 11.86345
September 485.00000 23.16801 48.22862 -0.8138 21.14151
October 502.00000 21.76809 43.97925 -0.2292 7.67209
November 489.00000 20.71225 44.22970 -0.5337 12.70228
December 497.00000 20.25698 38.38885 -0.7171 17.44909
           
Annual Sum or Average 5943.00000 22.07139 41.49759 -0.5628 14.43651
Minimum of Months 454.00000 20.07707 36.84456 -0.8473 7.30024
Maximum of Months 514.00000 23.93932 48.22862 -0.1147 22.63555



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.10685 36.26750 -0.7685 19.85309
February 454.00000 20.61950 36.57503 -0.5955 14.48426
March 514.00000 21.42748 36.08710 -0.3477 9.38820
April 485.00000 22.62317 36.77313 -0.0021 7.54594
May 508.00000 23.25981 39.69032 -0.7601 20.96472
June 496.00000 23.79884 40.19000 -0.5216 13.22446
July 497.00000 24.01087 43.79141 -0.4097 10.79684
August 514.00000 23.93846 47.35406 -0.4052 10.70302
September 485.00000 23.20589 47.48075 -0.7331 20.18543
October 502.00000 21.92028 42.97944 -0.1704 7.76218
November 489.00000 20.72371 43.68397 -0.5234 12.41437
December 497.00000 20.28872 37.83064 -0.7038 17.01789
           
Annual Sum or Average 5943.00000 22.17316 40.74768 -0.4946 13.68320
Minimum of Months 454.00000 20.10685 36.08710 -0.7685 7.54594
Maximum of Months 514.00000 24.01087 47.48075 -0.0021 20.96472



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46078 35.17821 -0.6632 17.43117
February 454.00000 21.24719 34.87528 -0.4277 12.72637
March 514.00000 21.83400 34.57308 -0.2353 9.48829
April 485.00000 22.68248 36.04489 0.01805 8.24795
May 508.00000 23.20017 39.39023 -0.7800 22.27751
June 496.00000 23.60804 40.53459 -0.6128 15.77969
July 497.00000 23.90719 43.83345 -0.4539 12.08072
August 514.00000 23.85368 47.30916 -0.4336 11.81473
September 485.00000 23.34755 46.46971 -0.6487 18.68558
October 502.00000 22.38122 41.15687 -0.0391 8.53517
November 489.00000 21.16373 42.13078 -0.4069 11.49195
December 497.00000 20.74912 36.40865 -0.5741 15.13207
           
Annual Sum or Average 5943.00000 22.37918 39.85501 -0.4386 13.64856
Minimum of Months 454.00000 20.46078 34.57308 -0.7800 8.24795
Maximum of Months 514.00000 23.90719 47.30916 0.01805 22.27751



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.12437 36.00742 -0.7658 19.86646
February 454.00000 20.65142 36.26302 -0.5923 15.03316
March 514.00000 21.32688 35.95447 -0.3746 10.08158
April 485.00000 22.28940 37.34138 -0.0808 8.11399
May 508.00000 23.07245 40.09903 -0.8109 23.75216
June 496.00000 23.50984 41.11479 -0.6261 16.35242
July 497.00000 23.88637 44.11961 -0.4312 12.18941
August 514.00000 23.74864 48.01083 -0.4682 12.70900
September 485.00000 23.10226 47.67296 -0.7566 21.55850
October 502.00000 21.75946 43.14074 -0.2071 8.07756
November 489.00000 20.73570 43.44196 -0.5242 12.54205
December 497.00000 20.32567 37.53253 -0.6981 17.03799
           
Annual Sum or Average 5943.00000 22.05620 40.91762 -0.5278 14.77275
Minimum of Months 454.00000 20.12437 35.95447 -0.8109 8.07756
Maximum of Months 514.00000 23.88637 48.01083 -0.0808 23.75216



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.40948 36.57401 -0.6809 16.13617
February 454.00000 20.76098 37.12555 -0.5572 12.64083
March 514.00000 21.36228 36.58652 -0.3786 8.58199
April 485.00000 22.27277 38.38108 -0.1281 6.41647
May 508.00000 23.25424 40.72310 -0.8460 21.37021
June 496.00000 23.77840 41.36675 -0.6358 14.07770
July 497.00000 24.02776 44.62915 -0.5067 10.77528
August 514.00000 23.95759 48.20838 -0.5043 10.82134
September 485.00000 23.49795 47.58864 -0.7089 16.54912
October 502.00000 22.40174 42.30487 -0.0711 5.92856
November 489.00000 21.32881 42.84663 -0.3541 8.61148
December 497.00000 20.68717 37.67629 -0.5781 12.46040
           
Annual Sum or Average 5943.00000 22.32379 41.19050 -0.4960 12.03514
Minimum of Months 454.00000 20.40948 36.57401 -0.8460 5.92856
Maximum of Months 514.00000 24.02776 48.20838 -0.0711 21.37021



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.43093 36.53326 -0.6708 15.76064
February 454.00000 20.96204 36.77841 -0.4967 11.16776
March 514.00000 21.72234 35.92469 -0.2750 7.56353
April 485.00000 22.92162 36.65182 0.05486 6.64131
May 508.00000 23.53670 39.56859 -0.6987 17.49282
June 496.00000 24.04587 40.01578 -0.4687 11.00001
July 497.00000 24.21300 43.76698 -0.3694 9.10608
August 514.00000 24.15906 47.12391 -0.3477 8.78165
September 485.00000 23.71105 46.45912 -0.5763 14.00595
October 502.00000 22.68201 41.34356 0.01608 6.33700
November 489.00000 21.35026 42.77022 -0.3398 8.45142
December 497.00000 20.73188 37.59046 -0.5610 12.11062
           
Annual Sum or Average 5943.00000 22.55100 40.39800 -0.3943 10.70138
Minimum of Months 454.00000 20.43093 35.92469 -0.6987 6.33700
Maximum of Months 514.00000 24.21300 47.12391 0.05486 17.49282



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.33200 34.38945 -0.6513 15.91597
February 454.00000 21.13525 34.23888 -0.4076 10.85756
March 514.00000 21.66863 33.85226 -0.2428 8.17193
April 485.00000 22.48763 35.94983 -0.0163 7.36626
May 508.00000 23.01576 39.66772 -0.8398 22.99215
June 496.00000 23.47223 40.91409 -0.6666 16.66491
July 497.00000 23.96898 44.06038 -0.4505 11.20848
August 514.00000 23.93895 47.42598 -0.4086 10.48805
September 485.00000 23.62537 45.67249 -0.5439 14.65077
October 502.00000 22.79811 39.36173 0.08945 7.64256
November 489.00000 21.33138 40.47303 -0.3105 9.24650
December 497.00000 20.77676 35.17738 -0.5109 12.50338
           
Annual Sum or Average 5943.00000 22.38898 39.29807 -0.4140 12.33003
Minimum of Months 454.00000 20.33200 33.85226 -0.8398 7.36626
Maximum of Months 514.00000 23.96898 47.42598 0.08945 22.99215



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.44449 36.18941 -0.6691 15.76027
February 454.00000 20.93753 36.46801 -0.5034 11.64140
March 514.00000 21.56479 35.77991 -0.3119 8.13097
April 485.00000 22.57547 37.16525 -0.0264 6.87024
May 508.00000 23.48845 39.55514 -0.7065 17.99813
June 496.00000 23.83831 40.75663 -0.5497 12.77169
July 497.00000 24.25900 43.54696 -0.3368 8.75523
August 514.00000 24.10340 47.38651 -0.3714 9.24006
September 485.00000 23.75218 46.21838 -0.5569 13.62532
October 502.00000 22.51601 41.48777 -0.0197 6.41619
November 489.00000 21.29079 42.59418 -0.3540 8.68111
December 497.00000 20.74096 37.25215 -0.5606 12.20029
           
Annual Sum or Average 5943.00000 22.47119 40.38937 -0.4138 11.00868
Minimum of Months 454.00000 20.44449 35.77991 -0.7065 6.41619
Maximum of Months 514.00000 24.25900 47.38651 -0.0197 17.99813



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.38870 36.39726 -0.6697 16.19688
February 454.00000 20.86737 36.68543 -0.5150 12.24810
March 514.00000 21.76730 36.09725 -0.2692 7.51252
April 485.00000 22.79369 37.23248 0.00688 6.34760
May 508.00000 23.54791 39.55279 -0.7235 17.36237
June 496.00000 23.92373 40.47718 -0.5612 12.15605
July 497.00000 24.11039 44.02610 -0.4556 9.78326
August 514.00000 24.03132 47.66812 -0.4602 9.97341
September 485.00000 23.59251 47.06755 -0.6671 15.50659
October 502.00000 22.41827 42.40065 -0.0638 6.23766
November 489.00000 21.23207 43.08906 -0.3792 9.29722
December 497.00000 20.63339 37.65560 -0.5868 13.00315
           
Annual Sum or Average 5943.00000 22.45488 40.71824 -0.4453 11.29573
Minimum of Months 454.00000 20.38870 36.09725 -0.7235 6.23766
Maximum of Months 514.00000 24.11039 47.66812 0.00688 17.36237



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.28098 35.26913 -0.6963 16.92241
February 385.00000 20.89946 35.26928 -0.5039 11.71754
March 433.00000 21.69856 34.90314 -0.2677 7.74923
April 410.00000 22.87526 35.67524 0.05722 6.97240
May 430.00000 23.46967 38.72449 -0.7000 18.13272
June 418.00000 23.93573 39.73933 -0.4904 12.03685
July 422.00000 24.16646 43.27800 -0.3785 9.85829
August 433.00000 24.07837 46.81909 -0.3771 9.83002
September 410.00000 23.49192 46.29500 -0.6442 16.51603
October 427.00000 22.30290 41.41964 -0.0698 6.75919
November 417.00000 21.07737 42.12829 -0.4118 9.72695
December 422.00000 20.55576 36.57646 -0.6054 13.47398
           
Annual Sum or Average 5034.00000 22.41174 39.69944 -0.4239 11.64009
Minimum of Months 385.00000 20.28098 34.90314 -0.7000 6.75919
Maximum of Months 433.00000 24.16646 46.81909 0.05722 18.13272



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.83908 34.69118 -0.5418 13.82574
February 454.00000 21.66521 34.22997 -0.2977 10.09376
March 514.00000 22.30293 33.74770 -0.1043 7.66532
April 485.00000 23.10988 35.22801 0.12664 7.61706
May 508.00000 23.56481 38.59612 -0.6579 16.98994
June 496.00000 23.85969 40.02823 -0.5312 12.63171
July 497.00000 24.11896 43.50663 -0.3880 9.83761
August 514.00000 24.05840 46.94673 -0.3672 9.62714
September 485.00000 23.74171 45.46994 -0.5132 13.56915
October 502.00000 22.91722 39.80698 0.10222 7.79433
November 489.00000 21.68101 41.06105 -0.2540 8.89710
December 497.00000 21.18398 35.59062 -0.4345 11.40321
           
Annual Sum or Average 5943.00000 22.76246 39.10566 -0.3225 10.83679
Minimum of Months 454.00000 20.83908 33.74770 -0.6579 7.61706
Maximum of Months 514.00000 24.11896 46.94673 0.12664 16.98994



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.41600 35.67527 -0.6602 15.90783
February 454.00000 20.99946 35.78265 -0.4738 11.64779
March 514.00000 21.75160 35.29541 -0.2496 7.90434
April 485.00000 22.73027 36.54262 0.03166 7.19694
May 508.00000 23.46685 39.28385 -0.6801 18.07515
June 496.00000 23.78590 40.59376 -0.5373 12.94228
July 497.00000 24.11310 43.75895 -0.3611 9.83204
August 514.00000 23.98342 47.59249 -0.3927 10.21234
September 485.00000 23.54287 46.57227 -0.6072 15.70594
October 502.00000 22.30547 41.82652 -0.0616 6.76238
November 489.00000 21.15622 42.56461 -0.3881 9.45557
December 497.00000 20.67650 36.89295 -0.5730 12.85113
           
Annual Sum or Average 5943.00000 22.42218 40.22465 -0.4127 11.54085
Minimum of Months 454.00000 20.41600 35.29541 -0.6801 6.76238
Maximum of Months 514.00000 24.11310 47.59249 0.03166 18.07515



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.515070E+11 0.00 426.03 174234.70 02-JAN-06:11 0.00 31.12 47.70 0.18 0.00 0.08 0.70 02-JAN-06:11
February 0.272530E+11 0.00 323.79 166854.19 06-FEB-06:11 0.00 29.21 43.69 0.10 0.00 0.05 0.67 06-FEB-06:11
March 0.959428E+10 0.00 275.49 170694.10 01-MAR-07:01 0.00 27.22 38.68 0.03 0.00 0.01 0.69 01-MAR-07:01
April 0.317106E+10 0.00 121.57 155430.89 18-APR-06:02 0.00 31.15 35.99 0.01 0.00 0.00 0.63 18-APR-06:02
May 0.892016E+09 0.00 52.03 67450.33 18-MAY-06:03 0.00 35.92 37.58 0.00 0.00 0.00 0.27 18-MAY-06:03
June 0.340977E+09 0.00 24.00 10926.40 15-JUN-06:05 0.00 38.99 39.70 0.00 0.00 0.00 0.04 15-JUN-06:05
July 85232022.84 0.00 58.85 11311.26 12-JUL-06:06 0.00 31.00 33.40 0.00 0.00 0.00 0.05 12-JUL-06:06
August 95249394.95 0.00 108.23 11789.65 01-AUG-06:07 0.00 36.80 40.24 0.00 0.00 0.00 0.05 01-AUG-06:07
September 0.380873E+09 0.00 56.24 54334.95 28-SEP-06:03 0.00 37.68 39.48 0.00 0.00 0.00 0.22 28-SEP-06:03
October 0.308693E+10 0.00 164.84 140686.83 31-OCT-06:03 0.00 30.95 37.59 0.01 0.00 0.00 0.57 31-OCT-06:03
November 0.188973E+11 0.00 318.68 161606.26 28-NOV-07:01 0.00 27.76 41.48 0.06 0.00 0.03 0.65 28-NOV-07:01
December 0.382295E+11 0.00 384.56 162807.09 21-DEC-07:01 0.00 28.78 44.64 0.12 0.00 0.06 0.66 21-DEC-07:01
                           
Annual Sum or Average 0.153533E+12 0.00 2314.29     0.00 32.22 39.99 0.04 0.00 0.02    
Minimum of Months 85232022.84 0.00 24.00 10926.40   0.00 27.22 33.40 0.00 0.00 0.00 0.04  
Maximum of Months 0.515070E+11 0.00 426.03 174234.70   0.00 38.99 47.70 0.18 0.00 0.08 0.70  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 2824018.97 752627.61 0.42 2590215.13 233803.83 0.00 0.15 03-JAN-07:25 0.00 01-JAN-00:05 3467.54 03-JAN-07:25 3292.02 03-JAN-07:25 175.51 03-JAN-07:25 912.91 03-JAN-07:25 0.00
February 0.211916E+09 52919225.27 8.00 0.195303E+09 16612783.14 0.00 0.51 27-FEB-15:10 0.00 01-FEB-00:10 13330.76 27-FEB-15:10 13330.76 27-FEB-15:10 1272.44 27-FEB-17:30 3205.00 27-FEB-15:10 0.00
March 0.321181E+09 82529779.92 22.33 0.283806E+09 37375076.92 0.00 0.43 18-MAR-16:00 0.00 01-MAR-00:10 10815.83 18-MAR-16:00 10815.83 18-MAR-16:00 1448.77 09-MAR-12:00 2659.21 18-MAR-16:00 0.00
April 0.353408E+10 0.816437E+09 67.71 0.340468E+10 0.129399E+09 0.00 1.00 26-APR-13:20 0.00 01-APR-00:10 51950.68 27-APR-15:00 51950.68 27-APR-15:00 4139.30 28-APR-13:00 11850.26 27-APR-15:00 0.00
May 0.770096E+10 0.176350E+10 159.03 0.690822E+10 0.792738E+09 0.00 1.00 04-MAY-12:50 0.00 01-MAY-00:10 46599.70 15-MAY-16:00 46599.70 15-MAY-16:00 5595.23 05-MAY-18:00 9804.45 15-MAY-16:00 0.00
June 0.146596E+11 0.334714E+10 264.77 0.137081E+11 0.951441E+09 0.00 1.00 09-JUN-13:50 0.00 01-JUN-00:10 53880.48 28-JUN-15:30 53880.48 28-JUN-15:30 10107.71 12-JUN-06:02 11946.50 28-JUN-15:30 0.00
July 0.281712E+11 0.632488E+10 350.18 0.251131E+11 0.305805E+10 0.00 1.00 06-JUL-14:30 0.00 01-JUL-00:10 71647.56 31-JUL-16:00 66799.33 24-JUL-15:00 15689.34 31-JUL-06:03 17476.16 24-JUL-15:00 0.00
August 0.380933E+11 0.860712E+10 375.40 0.335915E+11 0.450170E+10 0.00 1.00 07-AUG-09:00 0.00 01-AUG-00:10 72382.29 10-AUG-15:30 68771.18 10-AUG-16:00 19006.87 30-AUG-06:03 18190.51 10-AUG-16:00 0.00
September 0.139892E+11 0.314005E+10 229.85 0.117607E+11 0.222848E+10 0.00 1.00 08-SEP-14:00 0.00 01-SEP-00:10 57860.73 12-SEP-16:00 55154.30 12-SEP-15:20 14598.88 14-SEP-11:00 12343.15 12-SEP-16:00 0.00
October 0.180820E+10 0.430126E+09 59.60 0.171346E+10 94737123.60 0.00 1.00 04-OCT-13:50 0.00 01-OCT-00:10 35441.99 04-OCT-15:00 35441.99 04-OCT-15:00 3580.24 08-OCT-13:02 7440.64 04-OCT-15:00 0.00
November 0.366284E+09 86568535.76 7.67 0.252063E+09 0.114221E+09 0.00 0.71 04-NOV-14:20 0.00 01-NOV-00:10 19368.19 04-NOV-14:20 14748.52 04-NOV-14:20 5485.21 04-NOV-16:00 4421.61 04-NOV-14:20 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.108859E+12 0.246520E+11 1544.95 0.969337E+11 0.119250E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.380933E+11 0.860712E+10 375.40 0.335915E+11 0.450170E+10 0.00 1.00   0.00   72382.29   68771.18   19006.87   18190.51   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.210345E+09 52355320.72 8.00 0.196605E+09 13739820.74 0.00 0.55 27-FEB-15:00 0.00 01-FEB-00:10 13578.77 27-FEB-15:00 13578.77 27-FEB-15:00 1177.37 27-FEB-17:25 3232.54 27-FEB-15:00 0.00
March 0.322623E+09 82059170.64 22.17 0.290740E+09 31882962.75 0.00 0.49 18-MAR-16:00 0.00 01-MAR-00:10 12030.88 18-MAR-16:00 12030.88 18-MAR-16:00 1341.87 09-MAR-12:00 2905.79 18-MAR-16:00 0.00
April 0.350365E+10 0.809283E+09 70.94 0.338393E+10 0.119722E+09 0.00 1.00 26-APR-13:10 0.00 01-APR-00:10 49846.92 27-APR-14:50 49846.92 27-APR-14:50 4218.73 28-APR-13:00 11343.15 27-APR-15:00 0.00
May 0.734009E+10 0.168028E+10 162.21 0.660658E+10 0.733511E+09 0.00 1.00 04-MAY-12:40 0.00 01-MAY-00:10 44298.93 04-MAY-15:00 44298.93 04-MAY-15:00 6390.95 07-MAY-16:11 9428.27 04-MAY-15:00 0.00
June 0.134516E+11 0.308035E+10 269.49 0.125718E+11 0.879858E+09 0.00 1.00 09-JUN-13:30 0.00 01-JUN-00:10 49984.85 28-JUN-15:30 49984.85 28-JUN-15:30 5518.56 12-JUN-12:50 11083.14 28-JUN-15:30 0.00
July 0.253931E+11 0.571642E+10 352.61 0.227128E+11 0.268031E+10 0.00 1.00 06-JUL-14:40 0.00 01-JUL-00:10 65671.85 31-JUL-14:40 59623.45 31-JUL-15:20 11876.10 31-JUL-10:30 15559.60 24-JUL-15:00 0.00
August 0.334197E+11 0.758227E+10 375.41 0.295095E+11 0.391020E+10 0.00 1.00 06-AUG-13:13 0.00 01-AUG-00:10 67191.91 29-AUG-14:40 62533.77 10-AUG-15:20 15747.17 30-AUG-13:00 16762.13 29-AUG-15:20 0.00
September 0.124764E+11 0.281100E+10 230.54 0.104646E+11 0.201179E+10 0.00 1.00 08-SEP-13:50 0.00 01-SEP-00:10 52578.57 14-SEP-13:00 49300.69 12-SEP-15:20 14294.56 14-SEP-13:00 11102.16 14-SEP-13:00 0.00
October 0.161693E+10 0.385239E+09 58.25 0.151808E+10 98858850.86 0.00 1.00 04-OCT-13:50 0.00 01-OCT-00:10 31746.37 04-OCT-15:00 31746.37 04-OCT-15:00 4348.63 08-OCT-13:02 6665.36 04-OCT-15:00 0.00
November 0.383128E+09 89209910.56 7.67 0.275257E+09 0.107871E+09 0.00 0.76 04-NOV-13:40 0.00 01-NOV-00:10 19812.91 04-NOV-13:40 15622.06 04-NOV-14:00 5127.92 04-NOV-16:00 4458.72 04-NOV-13:40 0.00
December 43020.58 11655.65 0.02 42697.15 323.44 0.00 0.02 27-DEC-07:04 0.00 01-DEC-00:10 501.91 27-DEC-07:04 498.13 27-DEC-07:04 3.77 27-DEC-07:04 135.98 27-DEC-07:04 0.00
                                       
Annual Sum or Average 0.981177E+11 0.222885E+11 1557.32 0.875299E+11 0.105877E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.334197E+11 0.758227E+10 375.41 0.295095E+11 0.391020E+10 0.00 1.00   0.00   67191.91   62533.77   15747.17   16762.13   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 306623.24 83162.89 0.25 290659.09 15964.15 0.00 0.03 03-JAN-07:12 0.00 01-JAN-00:05 666.90 03-JAN-07:12 600.08 03-JAN-07:12 66.82 03-JAN-07:12 180.50 03-JAN-07:12 0.00
February 0.215832E+09 54103964.99 8.08 0.196455E+09 19376818.41 0.00 0.50 27-FEB-15:00 0.00 01-FEB-00:10 13470.71 27-FEB-15:00 13470.71 27-FEB-15:00 1382.55 27-FEB-17:13 3250.36 27-FEB-15:00 0.00
March 0.329246E+09 84226408.69 22.00 0.292254E+09 36992542.66 0.00 0.45 18-MAR-16:00 0.00 01-MAR-00:10 12113.99 18-MAR-16:00 12113.99 18-MAR-16:00 1493.17 09-MAR-12:00 2956.98 18-MAR-16:00 0.00
April 0.375525E+10 0.869864E+09 71.09 0.359781E+10 0.157438E+09 0.00 1.00 26-APR-13:30 0.00 01-APR-00:10 57561.79 27-APR-14:40 57561.79 27-APR-14:40 4016.27 28-APR-13:00 13077.81 27-APR-15:00 0.00
May 0.765878E+10 0.175919E+10 160.17 0.679918E+10 0.859603E+09 0.00 1.00 04-MAY-12:50 0.00 01-MAY-00:10 48074.45 04-MAY-15:00 48074.45 04-MAY-15:00 6251.80 05-MAY-18:00 10232.40 04-MAY-15:00 0.00
June 0.140954E+11 0.324221E+10 268.14 0.130322E+11 0.106320E+10 0.00 1.00 09-JUN-13:40 0.00 01-JUN-00:10 57977.23 28-JUN-15:20 57977.23 28-JUN-15:20 5345.03 12-JUN-12:30 12853.64 28-JUN-15:20 0.00
July 0.268474E+11 0.607053E+10 351.25 0.237152E+11 0.313222E+10 0.00 1.00 06-JUL-15:00 0.00 01-JUL-00:10 73743.41 31-JUL-14:40 68316.84 24-JUL-15:00 11848.15 31-JUL-10:30 17672.57 24-JUL-15:00 0.00
August 0.350887E+11 0.800970E+10 374.03 0.307456E+11 0.434313E+10 0.00 1.00 06-AUG-16:12 0.00 01-AUG-00:10 75608.63 10-AUG-14:50 71386.08 10-AUG-15:20 15967.21 30-AUG-13:00 18661.88 10-AUG-15:20 0.00
September 0.125461E+11 0.284486E+10 227.40 0.103414E+11 0.220470E+10 0.00 1.00 08-SEP-14:10 0.00 01-SEP-00:10 53504.18 14-SEP-13:30 50353.76 12-SEP-15:20 13853.91 14-SEP-13:00 11288.14 14-SEP-13:30 0.00
October 0.147745E+10 0.357023E+09 54.67 0.136982E+10 0.107629E+09 0.00 1.00 04-OCT-15:00 0.00 01-OCT-00:10 30989.70 04-OCT-15:00 30989.70 04-OCT-15:00 3226.22 08-OCT-13:02 6511.13 04-OCT-15:00 0.00
November 0.394950E+09 92838638.30 7.67 0.274748E+09 0.120202E+09 0.00 0.72 04-NOV-13:40 0.00 01-NOV-00:10 20659.46 04-NOV-13:40 15757.49 04-NOV-14:00 5678.81 04-NOV-13:00 4698.77 04-NOV-13:40 0.00
December 35537.80 9641.40 0.02 33890.41 1647.39 0.00 0.02 26-DEC-06:01 0.00 01-DEC-00:10 414.61 26-DEC-06:01 395.39 26-DEC-06:01 19.22 26-DEC-06:01 112.48 26-DEC-06:01 0.00
                                       
Annual Sum or Average 0.102409E+12 0.233847E+11 1544.77 0.903650E+11 0.120445E+11 0.00                         0.00
Minimum of Months 35537.80 9641.40 0.02 33890.41 1647.39 0.00 0.02   0.00   414.61   395.39   19.22   112.48   0.00
Maximum of Months 0.350887E+11 0.800970E+10 374.03 0.307456E+11 0.434313E+10 0.00 1.00   0.00   75608.63   71386.08   15967.21   18661.88   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.13 0.00 241.13 10.11 1446.73 0.00 0.00 0.00
February 375.20 0.00 375.20 79.81 1283.75 0.00 0.00 0.00
March 552.80 0.00 552.80 240.88 1060.63 0.00 0.00 0.00
April 782.27 2.77 779.49 513.30 862.74 0.00 0.00 0.00
May 1006.58 29.90 976.68 816.36 709.10 0.00 0.00 0.00
June 1058.39 69.89 988.50 943.04 553.53 0.00 0.00 0.00
July 1005.94 78.87 927.07 1017.09 500.78 0.00 0.00 0.00
August 814.32 22.01 792.31 840.80 488.59 0.00 0.00 0.00
September 632.53 0.19 632.35 487.62 712.84 0.00 0.00 0.00
October 433.39 0.00 433.39 204.73 934.05 0.00 0.00 0.00
November 272.99 0.00 272.99 43.22 1159.95 0.00 0.00 0.00
December 204.90 0.00 204.90 5.46 1451.90 0.00 0.00 0.00
                 
Annual Sum or Average 616.22 17.10 599.13 435.75 928.66 0.00 0.00 0.00
Minimum of Months 204.90 0.00 204.90 5.46 488.59 0.00 0.00 0.00
Maximum of Months 1058.39 78.87 988.50 1017.09 1451.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 258.31 65.49 192.82 93.85 915.06 0.00 0.00 0.00
February 473.97 168.22 305.75 314.65 807.01 0.00 0.00 0.00
March 707.67 256.18 451.49 594.42 674.75 0.00 0.00 0.00
April 1097.01 455.82 641.18 1111.62 553.03 0.00 0.00 0.00
May 1167.31 405.85 761.46 1238.71 473.62 0.00 0.00 0.00
June 1397.99 608.28 789.71 1591.82 375.67 0.00 0.00 0.00
July 1301.85 584.35 717.51 1551.10 333.64 0.00 0.00 0.00
August 1279.54 640.10 639.44 1578.71 324.53 0.00 0.00 0.00
September 946.03 436.32 509.71 1041.23 455.62 0.00 0.00 0.00
October 616.62 262.01 354.62 566.76 598.46 0.00 0.00 0.00
November 302.23 85.32 216.91 165.50 743.56 0.00 0.00 0.00
December 247.90 79.81 168.09 118.55 927.80 0.00 0.00 0.00
                 
Annual Sum or Average 817.87 338.05 479.82 833.21 597.58 0.00 0.00 0.00
Minimum of Months 247.90 65.49 168.09 93.85 324.53 0.00 0.00 0.00
Maximum of Months 1397.99 640.10 789.71 1591.82 927.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1065.37 632.62 432.75 949.35 1309.61 0.00 0.00 0.00
February 1638.38 1014.18 624.20 1666.92 1192.76 0.00 0.00 0.00
March 1762.43 939.88 822.54 1873.10 1048.92 0.00 0.00 0.00
April 1860.79 807.94 1052.84 2090.29 903.77 0.00 0.00 0.00
May 1701.45 506.88 1194.57 1925.98 763.07 0.00 0.00 0.00
June 1556.66 417.94 1138.72 1796.72 609.48 0.00 0.00 0.00
July 1697.61 621.75 1075.85 2168.23 555.23 0.00 0.00 0.00
August 1823.86 850.50 973.37 2412.45 534.48 0.00 0.00 0.00
September 2020.77 1115.93 904.83 2511.93 727.12 0.00 0.00 0.00
October 1830.47 1130.18 700.29 2081.25 926.60 0.00 0.00 0.00
November 1082.24 620.21 462.02 1039.15 1097.91 0.00 0.00 0.00
December 1132.33 732.78 399.55 1112.47 1350.92 0.00 0.00 0.00
                 
Annual Sum or Average 1597.01 781.12 815.88 1802.80 916.99 0.00 0.00 0.00
Minimum of Months 1065.37 417.94 399.55 949.35 534.48 0.00 0.00 0.00
Maximum of Months 2020.77 1130.18 1194.57 2511.93 1350.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 272.45 80.34 192.11 118.04 922.14 0.00 0.00 0.00
February 488.48 183.59 304.90 348.39 819.47 0.00 0.00 0.00
March 684.49 231.03 453.46 580.55 691.20 0.00 0.00 0.00
April 1041.38 398.16 643.22 1055.29 582.12 0.00 0.00 0.00
May 1340.01 544.37 795.64 1478.93 498.04 0.00 0.00 0.00
June 1288.72 500.37 788.35 1452.30 396.43 0.00 0.00 0.00
July 1592.04 836.86 755.18 1968.54 367.16 0.00 0.00 0.00
August 1317.00 672.50 644.50 1655.17 354.94 0.00 0.00 0.00
September 1072.50 514.61 557.89 1243.48 482.58 0.00 0.00 0.00
October 610.58 248.78 361.79 572.40 616.08 0.00 0.00 0.00
November 304.06 85.76 218.30 173.76 747.70 0.00 0.00 0.00
December 255.62 87.60 168.03 140.85 937.44 0.00 0.00 0.00
                 
Annual Sum or Average 857.85 366.72 491.13 902.60 617.01 0.00 0.00 0.00
Minimum of Months 255.62 80.34 168.03 118.04 354.94 0.00 0.00 0.00
Maximum of Months 1592.04 836.86 795.64 1968.54 937.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.37 0.00 80.37 2.91 505.87 0.00 0.00 0.00
February 125.06 0.00 125.06 25.94 448.72 0.00 0.00 0.00
March 184.26 0.00 184.26 82.15 364.77 0.00 0.00 0.00
April 260.74 0.92 259.82 177.27 291.03 0.00 0.00 0.00
May 335.51 9.97 325.54 278.83 239.75 0.00 0.00 0.00
June 352.78 23.30 329.48 320.73 186.81 0.00 0.00 0.00
July 335.30 26.29 309.01 344.07 169.44 0.00 0.00 0.00
August 271.43 7.34 264.09 283.47 166.65 0.00 0.00 0.00
September 210.83 0.06 210.77 162.23 250.35 0.00 0.00 0.00
October 144.46 0.00 144.46 63.78 338.84 0.00 0.00 0.00
November 90.99 0.00 90.99 11.83 424.28 0.00 0.00 0.00
December 68.30 0.00 68.30 1.13 519.46 0.00 0.00 0.00
                 
Annual Sum or Average 205.40 5.70 199.70 146.94 324.89 0.00 0.00 0.00
Minimum of Months 68.30 0.00 68.30 1.13 166.65 0.00 0.00 0.00
Maximum of Months 352.78 26.29 329.48 344.07 519.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.37 0.00 80.37 2.91 505.90 0.00 0.00 0.00
February 125.07 0.00 125.07 25.94 448.75 0.00 0.00 0.00
March 184.26 0.00 184.26 82.15 364.79 0.00 0.00 0.00
April 260.75 0.92 259.83 177.28 291.05 0.00 0.00 0.00
May 335.52 9.97 325.56 278.84 239.77 0.00 0.00 0.00
June 352.79 23.30 329.50 320.74 186.82 0.00 0.00 0.00
July 335.31 26.29 309.02 344.08 169.45 0.00 0.00 0.00
August 271.44 7.34 264.10 283.48 166.66 0.00 0.00 0.00
September 210.84 0.06 210.78 162.23 250.36 0.00 0.00 0.00
October 144.46 0.00 144.46 63.78 338.86 0.00 0.00 0.00
November 91.00 0.00 91.00 11.83 424.31 0.00 0.00 0.00
December 68.30 0.00 68.30 1.13 519.49 0.00 0.00 0.00
                 
Annual Sum or Average 205.41 5.70 199.71 146.95 324.91 0.00 0.00 0.00
Minimum of Months 68.30 0.00 68.30 1.13 166.66 0.00 0.00 0.00
Maximum of Months 352.79 26.29 329.50 344.08 519.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.37 0.00 80.37 2.91 505.90 0.00 0.00 0.00
February 125.07 0.00 125.07 25.94 448.75 0.00 0.00 0.00
March 184.26 0.00 184.26 82.15 364.79 0.00 0.00 0.00
April 260.75 0.92 259.83 177.28 291.05 0.00 0.00 0.00
May 335.52 9.97 325.56 278.84 239.77 0.00 0.00 0.00
June 352.79 23.30 329.50 320.74 186.82 0.00 0.00 0.00
July 335.31 26.29 309.02 344.08 169.45 0.00 0.00 0.00
August 271.44 7.34 264.10 283.48 166.66 0.00 0.00 0.00
September 210.84 0.06 210.78 162.23 250.36 0.00 0.00 0.00
October 144.46 0.00 144.46 63.78 338.86 0.00 0.00 0.00
November 91.00 0.00 91.00 11.83 424.31 0.00 0.00 0.00
December 68.30 0.00 68.30 1.13 519.49 0.00 0.00 0.00
                 
Annual Sum or Average 205.41 5.70 199.71 146.95 324.91 0.00 0.00 0.00
Minimum of Months 68.30 0.00 68.30 1.13 166.66 0.00 0.00 0.00
Maximum of Months 352.79 26.29 329.50 344.08 519.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 248.48 63.00 185.48 87.93 922.88 0.00 0.00 0.00
February 455.93 161.82 294.11 299.27 817.90 0.00 0.00 0.00
March 680.74 246.43 434.31 574.09 680.09 0.00 0.00 0.00
April 1055.27 438.48 616.79 1075.59 555.68 0.00 0.00 0.00
May 1122.90 390.40 732.49 1199.89 474.06 0.00 0.00 0.00
June 1344.80 585.13 759.67 1540.29 379.03 0.00 0.00 0.00
July 1252.32 562.11 690.21 1499.69 334.83 0.00 0.00 0.00
August 1230.85 615.74 615.11 1523.46 330.61 0.00 0.00 0.00
September 910.03 419.71 490.32 998.31 473.51 0.00 0.00 0.00
October 593.16 252.04 341.12 534.40 635.75 0.00 0.00 0.00
November 290.73 82.08 208.66 151.01 784.89 0.00 0.00 0.00
December 238.47 76.77 161.70 109.41 957.09 0.00 0.00 0.00
                 
Annual Sum or Average 786.75 325.19 461.57 802.00 611.20 0.00 0.00 0.00
Minimum of Months 238.47 63.00 161.70 87.93 330.61 0.00 0.00 0.00
Maximum of Months 1344.80 615.74 759.67 1540.29 957.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.82 2.49 7.33 3.48 36.49 0.00 0.00 0.00
February 18.03 6.40 11.63 11.83 32.34 0.00 0.00 0.00
March 26.92 9.74 17.17 22.70 26.89 0.00 0.00 0.00
April 41.72 17.34 24.39 42.53 21.97 0.00 0.00 0.00
May 44.40 15.44 28.96 47.44 18.74 0.00 0.00 0.00
June 53.17 23.14 30.04 60.90 14.99 0.00 0.00 0.00
July 49.52 22.23 27.29 59.30 13.24 0.00 0.00 0.00
August 48.67 24.35 24.32 60.24 13.07 0.00 0.00 0.00
September 35.98 16.60 19.39 39.47 18.72 0.00 0.00 0.00
October 23.45 9.97 13.49 21.13 25.14 0.00 0.00 0.00
November 11.50 3.25 8.25 5.97 31.03 0.00 0.00 0.00
December 9.43 3.04 6.39 4.33 37.84 0.00 0.00 0.00
                 
Annual Sum or Average 31.11 12.86 18.25 31.71 24.17 0.00 0.00 0.00
Minimum of Months 9.43 2.49 6.39 3.48 13.07 0.00 0.00 0.00
Maximum of Months 53.17 24.35 30.04 60.90 37.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 355.12 210.87 144.25 318.76 456.27 0.00 0.00 0.00
February 546.12 338.05 208.06 559.54 421.87 0.00 0.00 0.00
March 587.47 313.29 274.18 632.60 368.64 0.00 0.00 0.00
April 620.25 269.31 350.94 707.69 311.23 0.00 0.00 0.00
May 567.14 168.96 398.19 653.92 260.57 0.00 0.00 0.00
June 518.88 139.31 379.57 610.19 207.47 0.00 0.00 0.00
July 565.86 207.25 358.61 730.44 192.06 0.00 0.00 0.00
August 607.95 283.49 324.45 809.99 188.29 0.00 0.00 0.00
September 673.58 371.97 301.61 839.27 263.51 0.00 0.00 0.00
October 610.15 376.72 233.43 693.34 343.30 0.00 0.00 0.00
November 360.74 206.73 154.01 344.96 399.19 0.00 0.00 0.00
December 377.44 244.25 133.18 370.74 480.39 0.00 0.00 0.00
                 
Annual Sum or Average 532.33 260.37 271.96 606.12 323.92 0.00 0.00 0.00
Minimum of Months 355.12 139.31 133.18 318.76 188.29 0.00 0.00 0.00
Maximum of Months 673.58 376.72 398.19 839.27 480.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 355.12 210.87 144.25 318.76 456.27 0.00 0.00 0.00
February 546.12 338.05 208.06 559.54 421.87 0.00 0.00 0.00
March 587.47 313.29 274.18 632.60 368.64 0.00 0.00 0.00
April 620.25 269.31 350.94 707.69 311.23 0.00 0.00 0.00
May 567.14 168.96 398.19 653.92 260.57 0.00 0.00 0.00
June 518.88 139.31 379.57 610.19 207.47 0.00 0.00 0.00
July 565.86 207.25 358.61 730.44 192.06 0.00 0.00 0.00
August 607.95 283.49 324.45 809.99 188.29 0.00 0.00 0.00
September 673.58 371.97 301.61 839.27 263.51 0.00 0.00 0.00
October 610.15 376.72 233.43 693.34 343.30 0.00 0.00 0.00
November 360.74 206.73 154.01 344.96 399.19 0.00 0.00 0.00
December 377.44 244.25 133.18 370.74 480.39 0.00 0.00 0.00
                 
Annual Sum or Average 532.33 260.37 271.96 606.12 323.92 0.00 0.00 0.00
Minimum of Months 355.12 139.31 133.18 318.76 188.29 0.00 0.00 0.00
Maximum of Months 673.58 376.72 398.19 839.27 480.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 355.10 210.86 144.24 318.74 456.24 0.00 0.00 0.00
February 546.08 338.03 208.05 559.51 421.85 0.00 0.00 0.00
March 587.43 313.27 274.16 632.56 368.62 0.00 0.00 0.00
April 620.21 269.29 350.92 707.65 311.21 0.00 0.00 0.00
May 567.11 168.95 398.16 653.88 260.55 0.00 0.00 0.00
June 518.85 139.30 379.55 610.15 207.46 0.00 0.00 0.00
July 565.83 207.23 358.59 730.40 192.04 0.00 0.00 0.00
August 607.91 283.48 324.43 809.94 188.27 0.00 0.00 0.00
September 673.54 371.95 301.59 839.22 263.50 0.00 0.00 0.00
October 610.11 376.70 233.41 693.30 343.28 0.00 0.00 0.00
November 360.72 206.72 154.00 344.93 399.17 0.00 0.00 0.00
December 377.41 244.24 133.17 370.71 480.36 0.00 0.00 0.00
                 
Annual Sum or Average 532.29 260.35 271.94 606.08 323.90 0.00 0.00 0.00
Minimum of Months 355.10 139.30 133.17 318.74 188.27 0.00 0.00 0.00
Maximum of Months 673.54 376.70 398.16 839.22 480.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 262.08 77.28 184.80 113.57 931.42 0.00 0.00 0.00
February 469.90 176.60 293.30 336.46 832.02 0.00 0.00 0.00
March 658.45 222.24 436.20 564.66 696.44 0.00 0.00 0.00
April 1001.76 383.01 618.75 1026.73 581.44 0.00 0.00 0.00
May 1289.03 523.66 765.37 1433.63 503.33 0.00 0.00 0.00
June 1239.69 481.33 758.36 1408.26 399.01 0.00 0.00 0.00
July 1531.47 805.02 726.45 1902.19 375.47 0.00 0.00 0.00
August 1266.89 646.91 619.98 1597.81 364.26 0.00 0.00 0.00
September 1031.69 495.03 536.66 1192.81 505.20 0.00 0.00 0.00
October 587.34 239.31 348.03 542.31 653.24 0.00 0.00 0.00
November 292.49 82.50 210.00 161.32 788.48 0.00 0.00 0.00
December 245.90 84.26 161.63 133.67 968.33 0.00 0.00 0.00
                 
Annual Sum or Average 825.21 352.77 472.44 871.28 632.30 0.00 0.00 0.00
Minimum of Months 245.90 77.28 161.63 113.57 364.26 0.00 0.00 0.00
Maximum of Months 1531.47 805.02 765.37 1902.19 968.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.36 3.06 7.31 4.49 36.83 0.00 0.00 0.00
February 18.58 6.98 11.60 13.30 32.90 0.00 0.00 0.00
March 26.03 8.79 17.25 22.33 27.54 0.00 0.00 0.00
April 39.61 15.14 24.46 40.60 22.99 0.00 0.00 0.00
May 50.97 20.70 30.26 56.68 19.90 0.00 0.00 0.00
June 49.02 19.03 29.98 55.68 15.78 0.00 0.00 0.00
July 60.55 31.83 28.72 75.21 14.85 0.00 0.00 0.00
August 50.09 25.58 24.51 63.18 14.40 0.00 0.00 0.00
September 40.79 19.57 21.22 47.16 19.98 0.00 0.00 0.00
October 23.22 9.46 13.76 21.44 25.83 0.00 0.00 0.00
November 11.56 3.26 8.30 6.38 31.18 0.00 0.00 0.00
December 9.72 3.33 6.39 5.29 38.29 0.00 0.00 0.00
                 
Annual Sum or Average 32.63 13.95 18.68 34.45 25.00 0.00 0.00 0.00
Minimum of Months 9.72 3.06 6.39 4.49 14.40 0.00 0.00 0.00
Maximum of Months 60.55 31.83 30.26 75.21 38.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.13 0.00 241.13 7.56 1533.63 0.00 0.00 0.00
February 375.20 0.00 375.20 70.34 1374.65 0.00 0.00 0.00
March 552.80 0.00 552.80 223.26 1140.03 0.00 0.00 0.00
April 782.27 2.77 779.49 495.13 919.66 0.00 0.00 0.00
May 1006.58 29.90 976.68 801.62 748.53 0.00 0.00 0.00
June 1058.39 69.89 988.50 934.38 578.88 0.00 0.00 0.00
July 1005.94 78.87 927.07 1011.84 522.18 0.00 0.00 0.00
August 814.32 22.01 792.31 834.50 512.01 0.00 0.00 0.00
September 632.53 0.19 632.35 473.81 761.93 0.00 0.00 0.00
October 433.39 0.00 433.39 185.33 1017.52 0.00 0.00 0.00
November 272.99 0.00 272.99 34.63 1260.20 0.00 0.00 0.00
December 204.90 0.00 204.90 3.15 1556.26 0.00 0.00 0.00
                 
Annual Sum or Average 616.22 17.10 599.13 425.19 991.91 0.00 0.00 0.00
Minimum of Months 204.90 0.00 204.90 3.15 512.01 0.00 0.00 0.00
Maximum of Months 1058.39 78.87 988.50 1011.84 1556.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 258.31 65.49 192.82 88.80 968.75 0.00 0.00 0.00
February 473.97 168.22 305.75 302.85 860.23 0.00 0.00 0.00
March 707.67 256.18 451.49 581.86 720.03 0.00 0.00 0.00
April 1097.01 455.82 641.18 1100.46 584.35 0.00 0.00 0.00
May 1167.31 405.85 761.46 1231.28 496.79 0.00 0.00 0.00
June 1397.99 608.28 789.71 1589.00 391.02 0.00 0.00 0.00
July 1301.85 584.35 717.51 1548.92 345.94 0.00 0.00 0.00
August 1279.54 640.10 639.44 1576.38 337.79 0.00 0.00 0.00
September 946.03 436.32 509.71 1033.00 483.08 0.00 0.00 0.00
October 616.62 262.01 354.62 553.49 644.89 0.00 0.00 0.00
November 302.23 85.32 216.91 156.50 802.55 0.00 0.00 0.00
December 247.90 79.81 168.09 112.46 991.57 0.00 0.00 0.00
                 
Annual Sum or Average 817.87 338.05 479.82 825.58 634.51 0.00 0.00 0.00
Minimum of Months 247.90 65.49 168.09 88.80 337.79 0.00 0.00 0.00
Maximum of Months 1397.99 640.10 789.71 1589.00 991.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1065.37 632.62 432.75 934.10 1387.93 0.00 0.00 0.00
February 1638.38 1014.18 624.20 1646.21 1271.53 0.00 0.00 0.00
March 1762.43 939.88 822.54 1856.76 1122.45 0.00 0.00 0.00
April 1860.79 807.94 1052.84 2076.40 958.09 0.00 0.00 0.00
May 1701.45 506.88 1194.57 1916.65 805.12 0.00 0.00 0.00
June 1556.66 417.94 1138.72 1792.35 639.34 0.00 0.00 0.00
July 1697.61 621.75 1075.85 2166.39 579.74 0.00 0.00 0.00
August 1823.86 850.50 973.37 2410.21 560.04 0.00 0.00 0.00
September 2020.77 1115.93 904.83 2500.45 772.85 0.00 0.00 0.00
October 1830.47 1130.18 700.29 2062.64 999.96 0.00 0.00 0.00
November 1082.24 620.21 462.02 1019.41 1185.48 0.00 0.00 0.00
December 1132.33 732.78 399.55 1096.71 1443.94 0.00 0.00 0.00
                 
Annual Sum or Average 1597.01 781.12 815.88 1790.41 975.75 0.00 0.00 0.00
Minimum of Months 1065.37 417.94 399.55 934.10 560.04 0.00 0.00 0.00
Maximum of Months 2020.77 1130.18 1194.57 2500.45 1443.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 272.45 80.34 192.11 114.26 976.69 0.00 0.00 0.00
February 488.48 183.59 304.90 339.84 875.00 0.00 0.00 0.00
March 684.49 231.03 453.46 569.95 739.75 0.00 0.00 0.00
April 1041.38 398.16 643.22 1044.90 618.11 0.00 0.00 0.00
May 1340.01 544.37 795.64 1471.56 525.69 0.00 0.00 0.00
June 1288.72 500.37 788.35 1448.56 416.02 0.00 0.00 0.00
July 1592.04 836.86 755.18 1967.26 383.12 0.00 0.00 0.00
August 1317.00 672.50 644.50 1652.50 371.96 0.00 0.00 0.00
September 1072.50 514.61 557.89 1234.71 513.95 0.00 0.00 0.00
October 610.58 248.78 361.79 560.23 666.81 0.00 0.00 0.00
November 304.06 85.76 218.30 166.07 808.11 0.00 0.00 0.00
December 255.62 87.60 168.03 136.78 1002.73 0.00 0.00 0.00
                 
Annual Sum or Average 857.85 366.72 491.13 895.87 657.14 0.00 0.00 0.00
Minimum of Months 255.62 80.34 168.03 114.26 371.96 0.00 0.00 0.00
Maximum of Months 1592.04 836.86 795.64 1967.26 1002.73 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645835E+09 0.00 0.645835E+09 27070362.68 0.387492E+10
February 0.907684E+09 0.00 0.907684E+09 0.193077E+09 0.310566E+10
March 0.148061E+10 0.00 0.148061E+10 0.645165E+09 0.284080E+10
April 0.202763E+10 7192628.59 0.202044E+10 0.133047E+10 0.223623E+10
May 0.269602E+10 80094863.53 0.261593E+10 0.218654E+10 0.189925E+10
June 0.274335E+10 0.181160E+09 0.256219E+10 0.244436E+10 0.143475E+10
July 0.269432E+10 0.211248E+09 0.248307E+10 0.272418E+10 0.134128E+10
August 0.218107E+10 58960942.61 0.212211E+10 0.225200E+10 0.130864E+10
September 0.163953E+10 483472.07 0.163904E+10 0.126392E+10 0.184768E+10
October 0.116079E+10 0.00 0.116079E+10 0.548340E+09 0.250177E+10
November 0.707600E+09 0.00 0.707600E+09 0.112020E+09 0.300659E+10
December 0.548793E+09 0.00 0.548793E+09 14636872.07 0.388876E+10
           
Annual Sum or Average 0.194333E+11 0.539139E+09 0.188941E+11 0.137418E+11 0.292863E+11
Minimum of Months 0.548793E+09 0.00 0.548793E+09 14636872.07 0.130864E+10
Maximum of Months 0.274335E+10 0.211248E+09 0.261593E+10 0.272418E+10 0.388876E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.691850E+09 0.175407E+09 0.516443E+09 0.251376E+09 0.245090E+10
February 0.114662E+10 0.406961E+09 0.739663E+09 0.761209E+09 0.195232E+10
March 0.189542E+10 0.686158E+09 0.120926E+10 0.159209E+10 0.180725E+10
April 0.284344E+10 0.118149E+10 0.166195E+10 0.288131E+10 0.143346E+10
May 0.312653E+10 0.108702E+10 0.203951E+10 0.331777E+10 0.126855E+10
June 0.362359E+10 0.157665E+10 0.204694E+10 0.412600E+10 0.973736E+09
July 0.348688E+10 0.156511E+10 0.192177E+10 0.415446E+10 0.893635E+09
August 0.342712E+10 0.171444E+10 0.171268E+10 0.422841E+10 0.869212E+09
September 0.245211E+10 0.113094E+10 0.132118E+10 0.269886E+10 0.118097E+10
October 0.165156E+10 0.701758E+09 0.949803E+09 0.151802E+10 0.160293E+10
November 0.783391E+09 0.221159E+09 0.562232E+09 0.428976E+09 0.192731E+10
December 0.663975E+09 0.213753E+09 0.450222E+09 0.317530E+09 0.248501E+10
           
Annual Sum or Average 0.257925E+11 0.106609E+11 0.151316E+11 0.262760E+11 0.188453E+11
Minimum of Months 0.663975E+09 0.175407E+09 0.450222E+09 0.251376E+09 0.869212E+09
Maximum of Months 0.362359E+10 0.171444E+10 0.204694E+10 0.422841E+10 0.248501E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.285350E+10 0.169442E+10 0.115908E+10 0.254274E+10 0.350767E+10
February 0.396357E+10 0.245351E+10 0.151007E+10 0.403261E+10 0.288553E+10
March 0.472048E+10 0.251738E+10 0.220310E+10 0.501692E+10 0.280942E+10
April 0.482316E+10 0.209419E+10 0.272897E+10 0.541803E+10 0.234256E+10
May 0.455717E+10 0.135763E+10 0.319954E+10 0.515855E+10 0.204381E+10
June 0.403487E+10 0.108331E+10 0.295156E+10 0.465709E+10 0.157978E+10
July 0.454687E+10 0.166531E+10 0.288156E+10 0.580738E+10 0.148712E+10
August 0.488504E+10 0.227798E+10 0.260706E+10 0.646150E+10 0.143155E+10
September 0.523783E+10 0.289250E+10 0.234533E+10 0.651092E+10 0.188470E+10
October 0.490274E+10 0.302708E+10 0.187566E+10 0.557442E+10 0.248181E+10
November 0.280516E+10 0.160759E+10 0.119757E+10 0.269347E+10 0.284580E+10
December 0.303283E+10 0.196266E+10 0.107017E+10 0.297963E+10 0.361831E+10
           
Annual Sum or Average 0.503632E+11 0.246336E+11 0.257297E+11 0.568532E+11 0.289181E+11
Minimum of Months 0.280516E+10 0.108331E+10 0.107017E+10 0.254274E+10 0.143155E+10
Maximum of Months 0.523783E+10 0.302708E+10 0.319954E+10 0.651092E+10 0.361831E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.729733E+09 0.215185E+09 0.514548E+09 0.316152E+09 0.246986E+10
February 0.118174E+10 0.444131E+09 0.737608E+09 0.842820E+09 0.198247E+10
March 0.183334E+10 0.618801E+09 0.121454E+10 0.155496E+10 0.185131E+10
April 0.269925E+10 0.103203E+10 0.166722E+10 0.273530E+10 0.150887E+10
May 0.358909E+10 0.145805E+10 0.213103E+10 0.396116E+10 0.133394E+10
June 0.334037E+10 0.129696E+10 0.204342E+10 0.376435E+10 0.102754E+10
July 0.426413E+10 0.224144E+10 0.202268E+10 0.527253E+10 0.983390E+09
August 0.352745E+10 0.180122E+10 0.172623E+10 0.443322E+10 0.950678E+09
September 0.277991E+10 0.133386E+10 0.144605E+10 0.322311E+10 0.125085E+10
October 0.163536E+10 0.666333E+09 0.969031E+09 0.153312E+10 0.165011E+10
November 0.788130E+09 0.222286E+09 0.565845E+09 0.450397E+09 0.193804E+10
December 0.684662E+09 0.234616E+09 0.450046E+09 0.377258E+09 0.251085E+10
           
Annual Sum or Average 0.270532E+11 0.115649E+11 0.154883E+11 0.284644E+11 0.194579E+11
Minimum of Months 0.684662E+09 0.215185E+09 0.450046E+09 0.316152E+09 0.950678E+09
Maximum of Months 0.426413E+10 0.224144E+10 0.213103E+10 0.527253E+10 0.251085E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215268E+09 0.00 0.215268E+09 7783626.78 0.135492E+10
February 0.302547E+09 0.00 0.302547E+09 62744963.38 0.108554E+10
March 0.493515E+09 0.00 0.493515E+09 0.220030E+09 0.977003E+09
April 0.675845E+09 2397429.43 0.673448E+09 0.459496E+09 0.754357E+09
May 0.898631E+09 26697024.69 0.871934E+09 0.746814E+09 0.642159E+09
June 0.914408E+09 60383693.28 0.854025E+09 0.831331E+09 0.484204E+09
July 0.898065E+09 70412523.88 0.827652E+09 0.921557E+09 0.453825E+09
August 0.726990E+09 19652717.68 0.707337E+09 0.759238E+09 0.446356E+09
September 0.546484E+09 161149.73 0.546322E+09 0.420490E+09 0.648897E+09
October 0.386913E+09 0.00 0.386913E+09 0.170833E+09 0.907545E+09
November 0.235856E+09 0.00 0.235856E+09 30661636.03 0.109973E+10
December 0.182922E+09 0.00 0.182922E+09 3026622.52 0.139132E+10
           
Annual Sum or Average 0.647744E+10 0.179705E+09 0.629774E+10 0.463401E+10 0.102459E+11
Minimum of Months 0.182922E+09 0.00 0.182922E+09 3026622.52 0.446356E+09
Maximum of Months 0.914408E+09 70412523.88 0.871934E+09 0.921557E+09 0.139132E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215276E+09 0.00 0.215276E+09 7782774.49 0.135501E+10
February 0.302558E+09 0.00 0.302558E+09 62743794.45 0.108561E+10
March 0.493534E+09 0.00 0.493534E+09 0.220032E+09 0.977065E+09
April 0.675872E+09 2397493.88 0.673474E+09 0.459507E+09 0.754404E+09
May 0.898666E+09 26697742.32 0.871968E+09 0.746834E+09 0.642198E+09
June 0.914444E+09 60385316.41 0.854059E+09 0.831356E+09 0.484233E+09
July 0.898101E+09 70414416.59 0.827687E+09 0.921590E+09 0.453852E+09
August 0.727019E+09 19653245.95 0.707366E+09 0.759267E+09 0.446382E+09
September 0.546505E+09 161154.06 0.546344E+09 0.420502E+09 0.648935E+09
October 0.386928E+09 0.00 0.386928E+09 0.170835E+09 0.907601E+09
November 0.235864E+09 0.00 0.235864E+09 30660546.47 0.109980E+10
December 0.182929E+09 0.00 0.182929E+09 3026244.37 0.139141E+10
           
Annual Sum or Average 0.647770E+10 0.179709E+09 0.629799E+10 0.463414E+10 0.102465E+11
Minimum of Months 0.182929E+09 0.00 0.182929E+09 3026244.37 0.446382E+09
Maximum of Months 0.914444E+09 70414416.59 0.871968E+09 0.921590E+09 0.139141E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.215276E+09 0.00 0.215276E+09 7782774.49 0.135501E+10
February 0.302558E+09 0.00 0.302558E+09 62743794.45 0.108561E+10
March 0.493534E+09 0.00 0.493534E+09 0.220032E+09 0.977065E+09
April 0.675872E+09 2397493.88 0.673474E+09 0.459507E+09 0.754404E+09
May 0.898666E+09 26697742.32 0.871968E+09 0.746834E+09 0.642198E+09
June 0.914444E+09 60385316.41 0.854059E+09 0.831356E+09 0.484233E+09
July 0.898101E+09 70414416.59 0.827687E+09 0.921590E+09 0.453852E+09
August 0.727019E+09 19653245.95 0.707366E+09 0.759267E+09 0.446382E+09
September 0.546505E+09 161154.06 0.546344E+09 0.420502E+09 0.648935E+09
October 0.386928E+09 0.00 0.386928E+09 0.170835E+09 0.907601E+09
November 0.235864E+09 0.00 0.235864E+09 30660546.47 0.109980E+10
December 0.182929E+09 0.00 0.182929E+09 3026244.37 0.139141E+10
           
Annual Sum or Average 0.647770E+10 0.179709E+09 0.629799E+10 0.463414E+10 0.102465E+11
Minimum of Months 0.182929E+09 0.00 0.182929E+09 3026244.37 0.446382E+09
Maximum of Months 0.914444E+09 70414416.59 0.871968E+09 0.921590E+09 0.139141E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.665525E+09 0.168732E+09 0.496793E+09 0.235499E+09 0.247184E+10
February 0.110299E+10 0.391475E+09 0.711520E+09 0.724001E+09 0.197867E+10
March 0.182330E+10 0.660047E+09 0.116325E+10 0.153766E+10 0.182154E+10
April 0.273525E+10 0.113653E+10 0.159872E+10 0.278793E+10 0.144033E+10
May 0.300757E+10 0.104566E+10 0.196191E+10 0.321377E+10 0.126971E+10
June 0.348571E+10 0.151665E+10 0.196906E+10 0.399244E+10 0.982457E+09
July 0.335421E+10 0.150555E+10 0.184865E+10 0.401676E+10 0.896805E+09
August 0.329671E+10 0.164920E+10 0.164752E+10 0.408043E+10 0.885506E+09
September 0.235881E+10 0.108790E+10 0.127091E+10 0.258763E+10 0.122733E+10
October 0.158872E+10 0.675053E+09 0.913664E+09 0.143133E+10 0.170280E+10
November 0.753582E+09 0.212743E+09 0.540839E+09 0.391413E+09 0.203445E+10
December 0.638710E+09 0.205619E+09 0.433091E+09 0.293053E+09 0.256347E+10
           
Annual Sum or Average 0.248111E+11 0.102552E+11 0.145559E+11 0.252919E+11 0.192749E+11
Minimum of Months 0.638710E+09 0.168732E+09 0.433091E+09 0.235499E+09 0.885506E+09
Maximum of Months 0.348571E+10 0.164920E+10 0.196906E+10 0.408043E+10 0.256347E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 26314251.24 6671511.59 19642739.65 9311405.44 97734475.80
February 43611429.05 15478560.31 28132868.74 28626346.90 78234724.96
March 72091522.60 26097647.10 45993875.50 60797525.43 72022182.83
April 0.108149E+09 44937423.00 63211821.09 0.110232E+09 56949447.92
May 0.118917E+09 41344367.65 77572145.90 0.127070E+09 50203166.19
June 0.137822E+09 59967020.72 77854822.95 0.157857E+09 38845472.67
July 0.132622E+09 59528271.20 73094072.13 0.158819E+09 35458876.64
August 0.130349E+09 65207857.07 65141280.00 0.161337E+09 35012110.13
September 93265234.25 43014572.25 50250661.99 0.102313E+09 48527395.11
October 62816474.46 26691003.25 36125471.21 56593592.61 67327317.05
November 29795965.36 8411666.13 21384299.23 15476101.18 80440148.47
December 25254026.77 8129989.92 17124036.85 11587045.71 0.101357E+09
           
Annual Sum or Average 0.981008E+09 0.405480E+09 0.575528E+09 0.100002E+10 0.762113E+09
Minimum of Months 25254026.77 6671511.59 17124036.85 9311405.44 35012110.13
Maximum of Months 0.137822E+09 65207857.07 77854822.95 0.161337E+09 0.101357E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.951149E+09 0.564795E+09 0.386353E+09 0.853758E+09 0.122208E+10
February 0.132117E+10 0.817818E+09 0.503349E+09 0.135365E+10 0.102060E+10
March 0.157347E+10 0.839110E+09 0.734357E+09 0.169435E+10 0.987373E+09
April 0.160770E+10 0.698049E+09 0.909646E+09 0.183433E+10 0.806716E+09
May 0.151903E+10 0.452533E+09 0.106650E+10 0.175146E+10 0.697901E+09
June 0.134494E+10 0.361096E+09 0.983843E+09 0.158162E+10 0.537763E+09
July 0.151560E+10 0.555091E+09 0.960514E+09 0.195641E+10 0.514405E+09
August 0.162832E+10 0.759310E+09 0.869014E+09 0.216947E+10 0.504305E+09
September 0.174591E+10 0.964148E+09 0.781767E+09 0.217540E+10 0.683029E+09
October 0.163422E+10 0.100901E+10 0.625212E+09 0.185705E+10 0.919493E+09
November 0.935036E+09 0.535853E+09 0.399183E+09 0.894125E+09 0.103470E+10
December 0.101092E+10 0.654208E+09 0.356716E+09 0.992977E+09 0.128669E+10
           
Annual Sum or Average 0.167875E+11 0.821102E+10 0.857646E+10 0.191146E+11 0.102151E+11
Minimum of Months 0.935036E+09 0.361096E+09 0.356716E+09 0.853758E+09 0.504305E+09
Maximum of Months 0.174591E+10 0.100901E+10 0.106650E+10 0.217540E+10 0.128669E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.951149E+09 0.564795E+09 0.386353E+09 0.853758E+09 0.122208E+10
February 0.132117E+10 0.817818E+09 0.503349E+09 0.135365E+10 0.102060E+10
March 0.157347E+10 0.839110E+09 0.734357E+09 0.169435E+10 0.987373E+09
April 0.160770E+10 0.698049E+09 0.909646E+09 0.183433E+10 0.806716E+09
May 0.151903E+10 0.452533E+09 0.106650E+10 0.175146E+10 0.697901E+09
June 0.134494E+10 0.361096E+09 0.983843E+09 0.158162E+10 0.537763E+09
July 0.151560E+10 0.555091E+09 0.960514E+09 0.195641E+10 0.514405E+09
August 0.162832E+10 0.759310E+09 0.869014E+09 0.216947E+10 0.504305E+09
September 0.174591E+10 0.964148E+09 0.781767E+09 0.217540E+10 0.683029E+09
October 0.163422E+10 0.100901E+10 0.625212E+09 0.185705E+10 0.919493E+09
November 0.935036E+09 0.535853E+09 0.399183E+09 0.894125E+09 0.103470E+10
December 0.101092E+10 0.654208E+09 0.356716E+09 0.992977E+09 0.128669E+10
           
Annual Sum or Average 0.167875E+11 0.821102E+10 0.857646E+10 0.191146E+11 0.102151E+11
Minimum of Months 0.935036E+09 0.361096E+09 0.356716E+09 0.853758E+09 0.504305E+09
Maximum of Months 0.174591E+10 0.100901E+10 0.106650E+10 0.217540E+10 0.128669E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.951088E+09 0.564759E+09 0.386329E+09 0.853704E+09 0.122200E+10
February 0.132108E+10 0.817767E+09 0.503317E+09 0.135357E+10 0.102053E+10
March 0.157337E+10 0.839057E+09 0.734311E+09 0.169424E+10 0.987311E+09
April 0.160759E+10 0.698005E+09 0.909589E+09 0.183422E+10 0.806665E+09
May 0.151894E+10 0.452504E+09 0.106643E+10 0.175135E+10 0.697857E+09
June 0.134485E+10 0.361073E+09 0.983781E+09 0.158152E+10 0.537729E+09
July 0.151551E+10 0.555056E+09 0.960453E+09 0.195629E+10 0.514372E+09
August 0.162822E+10 0.759262E+09 0.868959E+09 0.216934E+10 0.504273E+09
September 0.174580E+10 0.964087E+09 0.781717E+09 0.217526E+10 0.682986E+09
October 0.163411E+10 0.100894E+10 0.625172E+09 0.185693E+10 0.919435E+09
November 0.934976E+09 0.535819E+09 0.399157E+09 0.894068E+09 0.103464E+10
December 0.101086E+10 0.654167E+09 0.356694E+09 0.992914E+09 0.128661E+10
           
Annual Sum or Average 0.167864E+11 0.821050E+10 0.857591E+10 0.191134E+11 0.102144E+11
Minimum of Months 0.934976E+09 0.361073E+09 0.356694E+09 0.853704E+09 0.504273E+09
Maximum of Months 0.174580E+10 0.100894E+10 0.106643E+10 0.217526E+10 0.128661E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.701968E+09 0.206997E+09 0.494971E+09 0.304178E+09 0.249472E+10
February 0.113678E+10 0.427231E+09 0.709545E+09 0.813968E+09 0.201282E+10
March 0.176358E+10 0.595255E+09 0.116833E+10 0.151238E+10 0.186534E+10
April 0.259655E+10 0.992758E+09 0.160379E+10 0.266129E+10 0.150709E+10
May 0.345253E+10 0.140257E+10 0.204996E+10 0.383982E+10 0.134813E+10
June 0.321328E+10 0.124761E+10 0.196567E+10 0.365022E+10 0.103424E+10
July 0.410189E+10 0.215615E+10 0.194573E+10 0.509482E+10 0.100567E+10
August 0.339324E+10 0.173268E+10 0.166056E+10 0.427957E+10 0.975632E+09
September 0.267414E+10 0.128311E+10 0.139103E+10 0.309176E+10 0.130949E+10
October 0.157314E+10 0.640978E+09 0.932164E+09 0.145252E+10 0.174964E+10
November 0.758144E+09 0.213827E+09 0.544316E+09 0.418138E+09 0.204374E+10
December 0.658612E+09 0.225689E+09 0.432923E+09 0.358019E+09 0.259358E+10
           
Annual Sum or Average 0.260239E+11 0.111249E+11 0.148990E+11 0.274767E+11 0.199401E+11
Minimum of Months 0.658612E+09 0.206997E+09 0.432923E+09 0.304178E+09 0.975632E+09
Maximum of Months 0.410189E+10 0.215615E+10 0.204996E+10 0.509482E+10 0.259358E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27755118.08 8184449.75 19570668.33 12026839.60 98638815.59
February 44946994.89 16892286.15 28054708.74 32183411.58 79585062.26
March 69730341.87 23535763.83 46194578.04 59798064.31 73753953.40
April 0.102665E+09 39252638.59 63412414.49 0.105225E+09 59589110.20
May 0.136510E+09 55456227.52 81053341.15 0.151823E+09 53303742.54
June 0.127050E+09 49329020.13 77720816.20 0.144326E+09 40892730.98
July 0.162184E+09 85252100.53 76932317.02 0.201444E+09 39763311.79
August 0.134165E+09 68508435.27 65656896.20 0.169210E+09 38575602.47
September 0.105733E+09 50732702.02 55000037.08 0.122245E+09 51776053.19
October 62200459.73 25343627.85 36856831.89 57431087.04 69179204.10
November 29976239.05 8454514.73 21521724.32 16532721.11 80807753.29
December 26040846.00 8923505.54 17117340.45 14155676.11 0.102548E+09
           
Annual Sum or Average 0.102896E+10 0.439865E+09 0.589092E+09 0.108640E+10 0.788413E+09
Minimum of Months 26040846.00 8184449.75 17117340.45 12026839.60 38575602.47
Maximum of Months 0.162184E+09 85252100.53 81053341.15 0.201444E+09 0.102548E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645835E+09 0.00 0.645835E+09 20237598.13 0.410768E+10
February 0.907684E+09 0.00 0.907684E+09 0.170174E+09 0.332555E+10
March 0.148061E+10 0.00 0.148061E+10 0.597982E+09 0.305347E+10
April 0.202763E+10 7192628.59 0.202044E+10 0.128338E+10 0.238376E+10
May 0.269602E+10 80094863.53 0.261593E+10 0.214705E+10 0.200487E+10
June 0.274335E+10 0.181160E+09 0.256219E+10 0.242191E+10 0.150046E+10
July 0.269432E+10 0.211248E+09 0.248307E+10 0.271011E+10 0.139860E+10
August 0.218107E+10 58960942.61 0.212211E+10 0.223513E+10 0.137136E+10
September 0.163953E+10 483472.07 0.163904E+10 0.122811E+10 0.197492E+10
October 0.116079E+10 0.00 0.116079E+10 0.496378E+09 0.272533E+10
November 0.707600E+09 0.00 0.707600E+09 89757712.95 0.326644E+10
December 0.548793E+09 0.00 0.548793E+09 8435233.18 0.416829E+10
           
Annual Sum or Average 0.194333E+11 0.539139E+09 0.188941E+11 0.134087E+11 0.312808E+11
Minimum of Months 0.548793E+09 0.00 0.548793E+09 8435233.18 0.137136E+10
Maximum of Months 0.274335E+10 0.211248E+09 0.261593E+10 0.271011E+10 0.416829E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.691850E+09 0.175407E+09 0.516443E+09 0.237847E+09 0.259470E+10
February 0.114662E+10 0.406961E+09 0.739663E+09 0.732652E+09 0.208107E+10
March 0.189542E+10 0.686158E+09 0.120926E+10 0.155845E+10 0.192852E+10
April 0.284344E+10 0.118149E+10 0.166195E+10 0.285240E+10 0.151463E+10
May 0.312653E+10 0.108702E+10 0.203951E+10 0.329786E+10 0.133061E+10
June 0.362359E+10 0.157665E+10 0.204694E+10 0.411868E+10 0.101354E+10
July 0.348688E+10 0.156511E+10 0.192177E+10 0.414863E+10 0.926563E+09
August 0.342712E+10 0.171444E+10 0.171268E+10 0.422219E+10 0.904724E+09
September 0.245211E+10 0.113094E+10 0.132118E+10 0.267754E+10 0.125214E+10
October 0.165156E+10 0.701758E+09 0.949803E+09 0.148247E+10 0.172729E+10
November 0.783391E+09 0.221159E+09 0.562232E+09 0.405646E+09 0.208020E+10
December 0.663975E+09 0.213753E+09 0.450222E+09 0.301211E+09 0.265582E+10
           
Annual Sum or Average 0.257925E+11 0.106609E+11 0.151316E+11 0.260356E+11 0.200098E+11
Minimum of Months 0.663975E+09 0.175407E+09 0.450222E+09 0.237847E+09 0.904724E+09
Maximum of Months 0.362359E+10 0.171444E+10 0.204694E+10 0.422219E+10 0.265582E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.285350E+10 0.169442E+10 0.115908E+10 0.250189E+10 0.371742E+10
February 0.396357E+10 0.245351E+10 0.151007E+10 0.398251E+10 0.307609E+10
March 0.472048E+10 0.251738E+10 0.220310E+10 0.497315E+10 0.300637E+10
April 0.482316E+10 0.209419E+10 0.272897E+10 0.538204E+10 0.248336E+10
May 0.455717E+10 0.135763E+10 0.319954E+10 0.513357E+10 0.215643E+10
June 0.403487E+10 0.108331E+10 0.295156E+10 0.464578E+10 0.165716E+10
July 0.454687E+10 0.166531E+10 0.288156E+10 0.580245E+10 0.155278E+10
August 0.488504E+10 0.227798E+10 0.260706E+10 0.645550E+10 0.150002E+10
September 0.523783E+10 0.289250E+10 0.234533E+10 0.648116E+10 0.200324E+10
October 0.490274E+10 0.302708E+10 0.187566E+10 0.552457E+10 0.267830E+10
November 0.280516E+10 0.160759E+10 0.119757E+10 0.264232E+10 0.307277E+10
December 0.303283E+10 0.196266E+10 0.107017E+10 0.293744E+10 0.386745E+10
           
Annual Sum or Average 0.503632E+11 0.246336E+11 0.257297E+11 0.564624E+11 0.307714E+11
Minimum of Months 0.280516E+10 0.108331E+10 0.107017E+10 0.250189E+10 0.150002E+10
Maximum of Months 0.523783E+10 0.302708E+10 0.319954E+10 0.648116E+10 0.386745E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.729733E+09 0.215185E+09 0.514548E+09 0.306036E+09 0.261597E+10
February 0.118174E+10 0.444131E+09 0.737608E+09 0.822129E+09 0.211680E+10
March 0.183334E+10 0.618801E+09 0.121454E+10 0.152657E+10 0.198135E+10
April 0.269925E+10 0.103203E+10 0.166722E+10 0.270837E+10 0.160215E+10
May 0.358909E+10 0.145805E+10 0.213103E+10 0.394143E+10 0.140800E+10
June 0.334037E+10 0.129696E+10 0.204342E+10 0.375467E+10 0.107833E+10
July 0.426413E+10 0.224144E+10 0.202268E+10 0.526911E+10 0.102614E+10
August 0.352745E+10 0.180122E+10 0.172623E+10 0.442606E+10 0.996268E+09
September 0.277991E+10 0.133386E+10 0.144605E+10 0.320036E+10 0.133216E+10
October 0.163536E+10 0.666333E+09 0.969031E+09 0.150052E+10 0.178599E+10
November 0.788130E+09 0.222286E+09 0.565845E+09 0.430461E+09 0.209463E+10
December 0.684662E+09 0.234616E+09 0.450046E+09 0.366356E+09 0.268570E+10
           
Annual Sum or Average 0.270532E+11 0.115649E+11 0.154883E+11 0.282521E+11 0.207235E+11
Minimum of Months 0.684662E+09 0.215185E+09 0.450046E+09 0.306036E+09 0.996268E+09
Maximum of Months 0.426413E+10 0.224144E+10 0.213103E+10 0.526911E+10 0.268570E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 10.11 1446.73 241.13 0.00 241.13 0.00 0.00
February 79.81 1283.75 375.20 0.00 375.20 0.00 0.00
March 240.88 1060.63 552.80 0.00 552.80 0.00 0.00
April 513.30 862.74 782.27 2.77 779.49 0.00 0.00
May 816.36 709.10 1006.58 29.90 976.68 0.00 0.00
June 943.04 553.53 1058.39 69.89 988.50 0.00 0.00
July 1017.09 500.78 1005.94 78.87 927.07 0.00 0.00
August 840.80 488.59 814.32 22.01 792.31 0.00 0.00
September 487.62 712.84 632.53 0.19 632.35 0.00 0.00
October 204.73 934.05 433.39 0.00 433.39 0.00 0.00
November 43.22 1159.95 272.99 0.00 272.99 0.00 0.00
December 5.46 1451.90 204.90 0.00 204.90 0.00 0.00
               
Annual Sum or Average 435.75 928.66 616.22 17.10 599.13 0.00 0.00
Minimum of Months 5.46 488.59 204.90 0.00 204.90 0.00 0.00
Maximum of Months 1017.09 1451.90 1058.39 78.87 988.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 93.85 915.06 258.31 65.49 192.82 0.00 0.00
February 314.65 807.01 473.97 168.22 305.75 0.00 0.00
March 594.42 674.75 707.67 256.18 451.49 0.00 0.00
April 1111.62 553.03 1097.01 455.82 641.18 0.00 0.00
May 1238.71 473.62 1167.31 405.85 761.46 0.00 0.00
June 1591.82 375.67 1397.99 608.28 789.71 0.00 0.00
July 1551.10 333.64 1301.85 584.35 717.51 0.00 0.00
August 1578.71 324.53 1279.54 640.10 639.44 0.00 0.00
September 1041.23 455.62 946.03 436.32 509.71 0.00 0.00
October 566.76 598.46 616.62 262.01 354.62 0.00 0.00
November 165.50 743.56 302.23 85.32 216.91 0.00 0.00
December 118.55 927.80 247.90 79.81 168.09 0.00 0.00
               
Annual Sum or Average 833.21 597.58 817.87 338.05 479.82 0.00 0.00
Minimum of Months 93.85 324.53 247.90 65.49 168.09 0.00 0.00
Maximum of Months 1591.82 927.80 1397.99 640.10 789.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 949.35 1309.61 1065.37 632.62 432.75 0.00 0.00
February 1666.92 1192.76 1638.38 1014.18 624.20 0.00 0.00
March 1873.10 1048.92 1762.43 939.88 822.54 0.00 0.00
April 2090.29 903.77 1860.79 807.94 1052.84 0.00 0.00
May 1925.98 763.07 1701.45 506.88 1194.57 0.00 0.00
June 1796.72 609.48 1556.66 417.94 1138.72 0.00 0.00
July 2168.23 555.23 1697.61 621.75 1075.85 0.00 0.00
August 2412.45 534.48 1823.86 850.50 973.37 0.00 0.00
September 2511.93 727.12 2020.77 1115.93 904.83 0.00 0.00
October 2081.25 926.60 1830.47 1130.18 700.29 0.00 0.00
November 1039.15 1097.91 1082.24 620.21 462.02 0.00 0.00
December 1112.47 1350.92 1132.33 732.78 399.55 0.00 0.00
               
Annual Sum or Average 1802.80 916.99 1597.01 781.12 815.88 0.00 0.00
Minimum of Months 949.35 534.48 1065.37 417.94 399.55 0.00 0.00
Maximum of Months 2511.93 1350.92 2020.77 1130.18 1194.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 118.04 922.14 272.45 80.34 192.11 0.00 0.00
February 348.39 819.47 488.48 183.59 304.90 0.00 0.00
March 580.55 691.20 684.49 231.03 453.46 0.00 0.00
April 1055.29 582.12 1041.38 398.16 643.22 0.00 0.00
May 1478.93 498.04 1340.01 544.37 795.64 0.00 0.00
June 1452.30 396.43 1288.72 500.37 788.35 0.00 0.00
July 1968.54 367.16 1592.04 836.86 755.18 0.00 0.00
August 1655.17 354.94 1317.00 672.50 644.50 0.00 0.00
September 1243.48 482.58 1072.50 514.61 557.89 0.00 0.00
October 572.40 616.08 610.58 248.78 361.79 0.00 0.00
November 173.76 747.70 304.06 85.76 218.30 0.00 0.00
December 140.85 937.44 255.62 87.60 168.03 0.00 0.00
               
Annual Sum or Average 902.60 617.01 857.85 366.72 491.13 0.00 0.00
Minimum of Months 118.04 354.94 255.62 80.34 168.03 0.00 0.00
Maximum of Months 1968.54 937.44 1592.04 836.86 795.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.72 1517.67 241.12 0.00 241.12 0.00 0.00
February 77.81 1346.21 375.19 0.00 375.19 0.00 0.00
March 246.45 1094.36 552.79 0.00 552.79 0.00 0.00
April 531.83 873.13 782.25 2.77 779.47 0.00 0.00
May 836.50 719.29 1006.56 29.90 976.65 0.00 0.00
June 962.21 560.44 1058.37 69.89 988.48 0.00 0.00
July 1032.23 508.34 1005.92 78.87 927.06 0.00 0.00
August 850.42 499.97 814.30 22.01 792.29 0.00 0.00
September 486.69 751.07 632.52 0.19 632.33 0.00 0.00
October 191.35 1016.56 433.38 0.00 433.38 0.00 0.00
November 35.49 1272.89 272.99 0.00 272.99 0.00 0.00
December 3.39 1558.45 204.89 0.00 204.89 0.00 0.00
               
Annual Sum or Average 440.84 974.72 616.21 17.10 599.12 0.00 0.00
Minimum of Months 3.39 499.97 204.89 0.00 204.89 0.00 0.00
Maximum of Months 1032.23 1558.45 1058.37 78.87 988.48 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 91.40 959.37 258.30 65.49 192.81 0.00 0.00
February 311.11 850.24 473.96 168.22 305.74 0.00 0.00
March 596.79 706.98 707.66 256.18 451.48 0.00 0.00
April 1118.12 577.66 1096.99 455.81 641.18 0.00 0.00
May 1247.33 492.80 1167.30 405.84 761.46 0.00 0.00
June 1601.19 394.02 1397.97 608.26 789.70 0.00 0.00
July 1558.98 348.07 1301.83 584.33 717.50 0.00 0.00
August 1583.70 343.68 1279.52 640.09 639.43 0.00 0.00
September 1037.79 492.23 946.02 436.31 509.71 0.00 0.00
October 555.53 660.89 616.61 262.00 354.61 0.00 0.00
November 156.98 815.93 302.23 85.32 216.91 0.00 0.00
December 113.74 994.93 247.90 79.80 168.09 0.00 0.00
               
Annual Sum or Average 833.71 635.37 817.86 338.05 479.82 0.00 0.00
Minimum of Months 91.40 343.68 247.90 65.49 168.09 0.00 0.00
Maximum of Months 1601.19 994.93 1397.97 640.09 789.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 956.25 1368.79 1065.33 632.60 432.73 0.00 0.00
February 1678.60 1265.60 1638.32 1014.14 624.18 0.00 0.00
March 1897.75 1105.91 1762.36 939.84 822.52 0.00 0.00
April 2123.03 933.68 1860.72 807.91 1052.81 0.00 0.00
May 1961.71 781.68 1701.39 506.86 1194.53 0.00 0.00
June 1830.54 622.40 1556.61 417.93 1138.68 0.00 0.00
July 2191.28 576.16 1697.55 621.73 1075.82 0.00 0.00
August 2429.92 564.85 1823.80 850.46 973.34 0.00 0.00
September 2517.77 790.53 2020.69 1115.89 904.80 0.00 0.00
October 2079.99 1029.88 1830.40 1130.14 700.27 0.00 0.00
November 1034.84 1197.55 1082.19 620.19 462.01 0.00 0.00
December 1112.18 1441.15 1132.28 732.74 399.54 0.00 0.00
               
Annual Sum or Average 1818.32 971.73 1596.95 781.09 815.86 0.00 0.00
Minimum of Months 956.25 564.85 1065.33 417.93 399.54 0.00 0.00
Maximum of Months 2517.77 1441.15 2020.69 1130.14 1194.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 118.06 968.25 272.45 80.34 192.11 0.00 0.00
February 349.76 864.92 488.48 183.58 304.89 0.00 0.00
March 586.99 723.98 684.48 231.03 453.45 0.00 0.00
April 1067.33 604.43 1041.36 398.15 643.21 0.00 0.00
May 1490.31 523.23 1339.99 544.37 795.63 0.00 0.00
June 1463.94 414.79 1288.71 500.36 788.35 0.00 0.00
July 1977.40 390.32 1592.02 836.85 755.18 0.00 0.00
August 1660.98 378.66 1316.98 672.49 644.50 0.00 0.00
September 1239.97 525.18 1072.48 514.60 557.88 0.00 0.00
October 563.75 679.07 610.57 248.78 361.79 0.00 0.00
November 167.70 819.66 304.06 85.76 218.30 0.00 0.00
December 138.95 1006.62 255.62 87.59 168.03 0.00 0.00
               
Annual Sum or Average 905.73 657.30 857.84 366.71 491.12 0.00 0.00
Minimum of Months 118.06 378.66 255.62 80.34 168.03 0.00 0.00
Maximum of Months 1977.40 1006.62 1592.02 836.85 795.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.56 1533.63 241.13 0.00 241.13 0.00 0.00
February 70.34 1374.65 375.20 0.00 375.20 0.00 0.00
March 223.26 1140.03 552.80 0.00 552.80 0.00 0.00
April 495.13 919.66 782.27 2.77 779.49 0.00 0.00
May 801.62 748.53 1006.58 29.90 976.68 0.00 0.00
June 934.38 578.88 1058.39 69.89 988.50 0.00 0.00
July 1011.84 522.18 1005.94 78.87 927.07 0.00 0.00
August 834.50 512.01 814.32 22.01 792.31 0.00 0.00
September 473.81 761.93 632.53 0.19 632.35 0.00 0.00
October 185.33 1017.52 433.39 0.00 433.39 0.00 0.00
November 34.63 1260.20 272.99 0.00 272.99 0.00 0.00
December 3.15 1556.26 204.90 0.00 204.90 0.00 0.00
               
Annual Sum or Average 425.19 991.91 616.22 17.10 599.13 0.00 0.00
Minimum of Months 3.15 512.01 204.90 0.00 204.90 0.00 0.00
Maximum of Months 1011.84 1556.26 1058.39 78.87 988.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 88.80 968.75 258.31 65.49 192.82 0.00 0.00
February 302.85 860.23 473.97 168.22 305.75 0.00 0.00
March 581.86 720.03 707.67 256.18 451.49 0.00 0.00
April 1100.46 584.35 1097.01 455.82 641.18 0.00 0.00
May 1231.28 496.79 1167.31 405.85 761.46 0.00 0.00
June 1589.00 391.02 1397.99 608.28 789.71 0.00 0.00
July 1548.92 345.94 1301.85 584.35 717.51 0.00 0.00
August 1576.38 337.79 1279.54 640.10 639.44 0.00 0.00
September 1033.00 483.08 946.03 436.32 509.71 0.00 0.00
October 553.49 644.89 616.62 262.01 354.62 0.00 0.00
November 156.50 802.55 302.23 85.32 216.91 0.00 0.00
December 112.46 991.57 247.90 79.81 168.09 0.00 0.00
               
Annual Sum or Average 825.58 634.51 817.87 338.05 479.82 0.00 0.00
Minimum of Months 88.80 337.79 247.90 65.49 168.09 0.00 0.00
Maximum of Months 1589.00 991.57 1397.99 640.10 789.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 934.10 1387.93 1065.37 632.62 432.75 0.00 0.00
February 1646.21 1271.53 1638.38 1014.18 624.20 0.00 0.00
March 1856.76 1122.45 1762.43 939.88 822.54 0.00 0.00
April 2076.40 958.09 1860.79 807.94 1052.84 0.00 0.00
May 1916.65 805.12 1701.45 506.88 1194.57 0.00 0.00
June 1792.35 639.34 1556.66 417.94 1138.72 0.00 0.00
July 2166.39 579.74 1697.61 621.75 1075.85 0.00 0.00
August 2410.21 560.04 1823.86 850.50 973.37 0.00 0.00
September 2500.45 772.85 2020.77 1115.93 904.83 0.00 0.00
October 2062.64 999.96 1830.47 1130.18 700.29 0.00 0.00
November 1019.41 1185.48 1082.24 620.21 462.02 0.00 0.00
December 1096.71 1443.94 1132.33 732.78 399.55 0.00 0.00
               
Annual Sum or Average 1790.41 975.75 1597.01 781.12 815.88 0.00 0.00
Minimum of Months 934.10 560.04 1065.37 417.94 399.55 0.00 0.00
Maximum of Months 2500.45 1443.94 2020.77 1130.18 1194.57 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 114.26 976.69 272.45 80.34 192.11 0.00 0.00
February 339.84 875.00 488.48 183.59 304.90 0.00 0.00
March 569.95 739.75 684.49 231.03 453.46 0.00 0.00
April 1044.90 618.11 1041.38 398.16 643.22 0.00 0.00
May 1471.56 525.69 1340.01 544.37 795.64 0.00 0.00
June 1448.56 416.02 1288.72 500.37 788.35 0.00 0.00
July 1967.26 383.12 1592.04 836.86 755.18 0.00 0.00
August 1652.50 371.96 1317.00 672.50 644.50 0.00 0.00
September 1234.71 513.95 1072.50 514.61 557.89 0.00 0.00
October 560.23 666.81 610.58 248.78 361.79 0.00 0.00
November 166.07 808.11 304.06 85.76 218.30 0.00 0.00
December 136.78 1002.73 255.62 87.60 168.03 0.00 0.00
               
Annual Sum or Average 895.87 657.14 857.85 366.72 491.13 0.00 0.00
Minimum of Months 114.26 371.96 255.62 80.34 168.03 0.00 0.00
Maximum of Months 1967.26 1002.73 1592.04 836.86 795.64 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 27070362.68 0.387492E+10 0.645835E+09 0.00 0.645835E+09 0.00 0.00
February 0.193077E+09 0.310566E+10 0.907684E+09 0.00 0.907684E+09 0.00 0.00
March 0.645165E+09 0.284080E+10 0.148061E+10 0.00 0.148061E+10 0.00 0.00
April 0.133047E+10 0.223623E+10 0.202763E+10 7192628.59 0.202044E+10 0.00 0.00
May 0.218654E+10 0.189925E+10 0.269602E+10 80094863.53 0.261593E+10 0.00 0.00
June 0.244436E+10 0.143475E+10 0.274335E+10 0.181160E+09 0.256219E+10 0.00 0.00
July 0.272418E+10 0.134128E+10 0.269432E+10 0.211248E+09 0.248307E+10 0.00 0.00
August 0.225200E+10 0.130864E+10 0.218107E+10 58960942.61 0.212211E+10 0.00 0.00
September 0.126392E+10 0.184768E+10 0.163953E+10 483472.07 0.163904E+10 0.00 0.00
October 0.548340E+09 0.250177E+10 0.116079E+10 0.00 0.116079E+10 0.00 0.00
November 0.112020E+09 0.300659E+10 0.707600E+09 0.00 0.707600E+09 0.00 0.00
December 14636872.07 0.388876E+10 0.548793E+09 0.00 0.548793E+09 0.00 0.00
               
Annual Sum or Average 0.137418E+11 0.292863E+11 0.194333E+11 0.539139E+09 0.188941E+11 0.00 0.00
Minimum of Months 14636872.07 0.130864E+10 0.548793E+09 0.00 0.548793E+09 0.00 0.00
Maximum of Months 0.272418E+10 0.388876E+10 0.274335E+10 0.211248E+09 0.261593E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.251376E+09 0.245090E+10 0.691850E+09 0.175407E+09 0.516443E+09 0.00 0.00
February 0.761209E+09 0.195232E+10 0.114662E+10 0.406961E+09 0.739663E+09 0.00 0.00
March 0.159209E+10 0.180725E+10 0.189542E+10 0.686158E+09 0.120926E+10 0.00 0.00
April 0.288131E+10 0.143346E+10 0.284344E+10 0.118149E+10 0.166195E+10 0.00 0.00
May 0.331777E+10 0.126855E+10 0.312653E+10 0.108702E+10 0.203951E+10 0.00 0.00
June 0.412600E+10 0.973736E+09 0.362359E+10 0.157665E+10 0.204694E+10 0.00 0.00
July 0.415446E+10 0.893635E+09 0.348688E+10 0.156511E+10 0.192177E+10 0.00 0.00
August 0.422841E+10 0.869212E+09 0.342712E+10 0.171444E+10 0.171268E+10 0.00 0.00
September 0.269886E+10 0.118097E+10 0.245211E+10 0.113094E+10 0.132118E+10 0.00 0.00
October 0.151802E+10 0.160293E+10 0.165156E+10 0.701758E+09 0.949803E+09 0.00 0.00
November 0.428976E+09 0.192731E+10 0.783391E+09 0.221159E+09 0.562232E+09 0.00 0.00
December 0.317530E+09 0.248501E+10 0.663975E+09 0.213753E+09 0.450222E+09 0.00 0.00
               
Annual Sum or Average 0.262760E+11 0.188453E+11 0.257925E+11 0.106609E+11 0.151316E+11 0.00 0.00
Minimum of Months 0.251376E+09 0.869212E+09 0.663975E+09 0.175407E+09 0.450222E+09 0.00 0.00
Maximum of Months 0.422841E+10 0.248501E+10 0.362359E+10 0.171444E+10 0.204694E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.254274E+10 0.350767E+10 0.285350E+10 0.169442E+10 0.115908E+10 0.00 0.00
February 0.403261E+10 0.288553E+10 0.396357E+10 0.245351E+10 0.151007E+10 0.00 0.00
March 0.501692E+10 0.280942E+10 0.472048E+10 0.251738E+10 0.220310E+10 0.00 0.00
April 0.541803E+10 0.234256E+10 0.482316E+10 0.209419E+10 0.272897E+10 0.00 0.00
May 0.515855E+10 0.204381E+10 0.455717E+10 0.135763E+10 0.319954E+10 0.00 0.00
June 0.465709E+10 0.157978E+10 0.403487E+10 0.108331E+10 0.295156E+10 0.00 0.00
July 0.580738E+10 0.148712E+10 0.454687E+10 0.166531E+10 0.288156E+10 0.00 0.00
August 0.646150E+10 0.143155E+10 0.488504E+10 0.227798E+10 0.260706E+10 0.00 0.00
September 0.651092E+10 0.188470E+10 0.523783E+10 0.289250E+10 0.234533E+10 0.00 0.00
October 0.557442E+10 0.248181E+10 0.490274E+10 0.302708E+10 0.187566E+10 0.00 0.00
November 0.269347E+10 0.284580E+10 0.280516E+10 0.160759E+10 0.119757E+10 0.00 0.00
December 0.297963E+10 0.361831E+10 0.303283E+10 0.196266E+10 0.107017E+10 0.00 0.00
               
Annual Sum or Average 0.568532E+11 0.289181E+11 0.503632E+11 0.246336E+11 0.257297E+11 0.00 0.00
Minimum of Months 0.254274E+10 0.143155E+10 0.280516E+10 0.108331E+10 0.107017E+10 0.00 0.00
Maximum of Months 0.651092E+10 0.361831E+10 0.523783E+10 0.302708E+10 0.319954E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.316152E+09 0.246986E+10 0.729733E+09 0.215185E+09 0.514548E+09 0.00 0.00
February 0.842820E+09 0.198247E+10 0.118174E+10 0.444131E+09 0.737608E+09 0.00 0.00
March 0.155496E+10 0.185131E+10 0.183334E+10 0.618801E+09 0.121454E+10 0.00 0.00
April 0.273530E+10 0.150887E+10 0.269925E+10 0.103203E+10 0.166722E+10 0.00 0.00
May 0.396116E+10 0.133394E+10 0.358909E+10 0.145805E+10 0.213103E+10 0.00 0.00
June 0.376435E+10 0.102754E+10 0.334037E+10 0.129696E+10 0.204342E+10 0.00 0.00
July 0.527253E+10 0.983390E+09 0.426413E+10 0.224144E+10 0.202268E+10 0.00 0.00
August 0.443322E+10 0.950678E+09 0.352745E+10 0.180122E+10 0.172623E+10 0.00 0.00
September 0.322311E+10 0.125085E+10 0.277991E+10 0.133386E+10 0.144605E+10 0.00 0.00
October 0.153312E+10 0.165011E+10 0.163536E+10 0.666333E+09 0.969031E+09 0.00 0.00
November 0.450397E+09 0.193804E+10 0.788130E+09 0.222286E+09 0.565845E+09 0.00 0.00
December 0.377258E+09 0.251085E+10 0.684662E+09 0.234616E+09 0.450046E+09 0.00 0.00
               
Annual Sum or Average 0.284644E+11 0.194579E+11 0.270532E+11 0.115649E+11 0.154883E+11 0.00 0.00
Minimum of Months 0.316152E+09 0.950678E+09 0.684662E+09 0.215185E+09 0.450046E+09 0.00 0.00
Maximum of Months 0.527253E+10 0.251085E+10 0.426413E+10 0.224144E+10 0.213103E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23349175.76 0.406493E+10 0.645820E+09 0.00 0.645820E+09 0.00 0.00
February 0.188233E+09 0.325675E+10 0.907663E+09 0.00 0.907663E+09 0.00 0.00
March 0.660094E+09 0.293113E+10 0.148058E+10 0.00 0.148058E+10 0.00 0.00
April 0.137851E+10 0.226317E+10 0.202759E+10 7192417.18 0.202040E+10 0.00 0.00
May 0.224048E+10 0.192656E+10 0.269596E+10 80092509.32 0.261587E+10 0.00 0.00
June 0.249404E+10 0.145267E+10 0.274330E+10 0.181154E+09 0.256214E+10 0.00 0.00
July 0.276474E+10 0.136153E+10 0.269427E+10 0.211241E+09 0.248303E+10 0.00 0.00
August 0.227777E+10 0.133912E+10 0.218103E+10 58959209.59 0.212207E+10 0.00 0.00
September 0.126149E+10 0.194677E+10 0.163949E+10 483457.86 0.163901E+10 0.00 0.00
October 0.512504E+09 0.272275E+10 0.116077E+10 0.00 0.116077E+10 0.00 0.00
November 91982728.98 0.329934E+10 0.707584E+09 0.00 0.707584E+09 0.00 0.00
December 9079111.25 0.417415E+10 0.548780E+09 0.00 0.548780E+09 0.00 0.00
               
Annual Sum or Average 0.139023E+11 0.307389E+11 0.194328E+11 0.539123E+09 0.188937E+11 0.00 0.00
Minimum of Months 9079111.25 0.133912E+10 0.548780E+09 0.00 0.548780E+09 0.00 0.00
Maximum of Months 0.276474E+10 0.417415E+10 0.274330E+10 0.211241E+09 0.261587E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.244810E+09 0.256958E+10 0.691839E+09 0.175404E+09 0.516436E+09 0.00 0.00
February 0.752627E+09 0.205690E+10 0.114661E+10 0.406953E+09 0.739653E+09 0.00 0.00
March 0.159845E+10 0.189357E+10 0.189539E+10 0.686144E+09 0.120924E+10 0.00 0.00
April 0.289817E+10 0.149728E+10 0.284340E+10 0.118147E+10 0.166193E+10 0.00 0.00
May 0.334084E+10 0.131991E+10 0.312648E+10 0.108700E+10 0.203948E+10 0.00 0.00
June 0.415029E+10 0.102130E+10 0.362353E+10 0.157662E+10 0.204691E+10 0.00 0.00
July 0.417558E+10 0.932264E+09 0.348683E+10 0.156508E+10 0.192175E+10 0.00 0.00
August 0.424177E+10 0.920518E+09 0.342706E+10 0.171441E+10 0.171266E+10 0.00 0.00
September 0.268994E+10 0.127585E+10 0.245208E+10 0.113091E+10 0.132116E+10 0.00 0.00
October 0.148793E+10 0.177013E+10 0.165153E+10 0.701744E+09 0.949790E+09 0.00 0.00
November 0.406889E+09 0.211489E+10 0.783378E+09 0.221155E+09 0.562224E+09 0.00 0.00
December 0.304640E+09 0.266482E+10 0.663964E+09 0.213749E+09 0.450215E+09 0.00 0.00
               
Annual Sum or Average 0.262919E+11 0.200370E+11 0.257921E+11 0.106606E+11 0.151315E+11 0.00 0.00
Minimum of Months 0.244810E+09 0.920518E+09 0.663964E+09 0.175404E+09 0.450215E+09 0.00 0.00
Maximum of Months 0.424177E+10 0.266482E+10 0.362353E+10 0.171441E+10 0.204691E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.256122E+10 0.366617E+10 0.285339E+10 0.169435E+10 0.115904E+10 0.00 0.00
February 0.406087E+10 0.306173E+10 0.396342E+10 0.245340E+10 0.151001E+10 0.00 0.00
March 0.508294E+10 0.296206E+10 0.472030E+10 0.251728E+10 0.220302E+10 0.00 0.00
April 0.550289E+10 0.242010E+10 0.482298E+10 0.209410E+10 0.272888E+10 0.00 0.00
May 0.525426E+10 0.209366E+10 0.455701E+10 0.135757E+10 0.319944E+10 0.00 0.00
June 0.474476E+10 0.161326E+10 0.403473E+10 0.108327E+10 0.295147E+10 0.00 0.00
July 0.586912E+10 0.154318E+10 0.454672E+10 0.166524E+10 0.288148E+10 0.00 0.00
August 0.650829E+10 0.151288E+10 0.488487E+10 0.227788E+10 0.260699E+10 0.00 0.00
September 0.652605E+10 0.204904E+10 0.523763E+10 0.289238E+10 0.234525E+10 0.00 0.00
October 0.557104E+10 0.275842E+10 0.490255E+10 0.302695E+10 0.187560E+10 0.00 0.00
November 0.268232E+10 0.310404E+10 0.280505E+10 0.160752E+10 0.119752E+10 0.00 0.00
December 0.297887E+10 0.385998E+10 0.303271E+10 0.196258E+10 0.107013E+10 0.00 0.00
               
Annual Sum or Average 0.573426E+11 0.306445E+11 0.503614E+11 0.246325E+11 0.257288E+11 0.00 0.00
Minimum of Months 0.256122E+10 0.151288E+10 0.280505E+10 0.108327E+10 0.107013E+10 0.00 0.00
Maximum of Months 0.652605E+10 0.385998E+10 0.523763E+10 0.302695E+10 0.319944E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.316204E+09 0.259335E+10 0.729723E+09 0.215181E+09 0.514542E+09 0.00 0.00
February 0.846151E+09 0.209240E+10 0.118172E+10 0.444124E+09 0.737600E+09 0.00 0.00
March 0.157218E+10 0.193910E+10 0.183331E+10 0.618791E+09 0.121452E+10 0.00 0.00
April 0.276651E+10 0.156668E+10 0.269922E+10 0.103201E+10 0.166721E+10 0.00 0.00
May 0.399165E+10 0.140143E+10 0.358904E+10 0.145803E+10 0.213101E+10 0.00 0.00
June 0.379454E+10 0.107513E+10 0.334033E+10 0.129693E+10 0.204340E+10 0.00 0.00
July 0.529627E+10 0.104543E+10 0.426407E+10 0.224141E+10 0.202266E+10 0.00 0.00
August 0.444878E+10 0.101421E+10 0.352741E+10 0.180119E+10 0.172622E+10 0.00 0.00
September 0.321400E+10 0.136127E+10 0.277987E+10 0.133384E+10 0.144603E+10 0.00 0.00
October 0.150995E+10 0.181882E+10 0.163534E+10 0.666322E+09 0.969021E+09 0.00 0.00
November 0.434671E+09 0.212455E+10 0.788120E+09 0.222282E+09 0.565838E+09 0.00 0.00
December 0.372175E+09 0.269612E+10 0.684653E+09 0.234612E+09 0.450040E+09 0.00 0.00
               
Annual Sum or Average 0.285631E+11 0.207285E+11 0.270528E+11 0.115647E+11 0.154881E+11 0.00 0.00
Minimum of Months 0.316204E+09 0.101421E+10 0.684653E+09 0.215181E+09 0.450040E+09 0.00 0.00
Maximum of Months 0.529627E+10 0.269612E+10 0.426407E+10 0.224141E+10 0.213101E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20237598.13 0.410768E+10 0.645835E+09 0.00 0.645835E+09 0.00 0.00
February 0.170174E+09 0.332555E+10 0.907684E+09 0.00 0.907684E+09 0.00 0.00
March 0.597982E+09 0.305347E+10 0.148061E+10 0.00 0.148061E+10 0.00 0.00
April 0.128338E+10 0.238376E+10 0.202763E+10 7192628.59 0.202044E+10 0.00 0.00
May 0.214705E+10 0.200487E+10 0.269602E+10 80094863.53 0.261593E+10 0.00 0.00
June 0.242191E+10 0.150046E+10 0.274335E+10 0.181160E+09 0.256219E+10 0.00 0.00
July 0.271011E+10 0.139860E+10 0.269432E+10 0.211248E+09 0.248307E+10 0.00 0.00
August 0.223513E+10 0.137136E+10 0.218107E+10 58960942.61 0.212211E+10 0.00 0.00
September 0.122811E+10 0.197492E+10 0.163953E+10 483472.07 0.163904E+10 0.00 0.00
October 0.496378E+09 0.272533E+10 0.116079E+10 0.00 0.116079E+10 0.00 0.00
November 89757712.95 0.326644E+10 0.707600E+09 0.00 0.707600E+09 0.00 0.00
December 8435233.18 0.416829E+10 0.548793E+09 0.00 0.548793E+09 0.00 0.00
               
Annual Sum or Average 0.134087E+11 0.312808E+11 0.194333E+11 0.539139E+09 0.188941E+11 0.00 0.00
Minimum of Months 8435233.18 0.137136E+10 0.548793E+09 0.00 0.548793E+09 0.00 0.00
Maximum of Months 0.271011E+10 0.416829E+10 0.274335E+10 0.211248E+09 0.261593E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.237847E+09 0.259470E+10 0.691850E+09 0.175407E+09 0.516443E+09 0.00 0.00
February 0.732652E+09 0.208107E+10 0.114662E+10 0.406961E+09 0.739663E+09 0.00 0.00
March 0.155845E+10 0.192852E+10 0.189542E+10 0.686158E+09 0.120926E+10 0.00 0.00
April 0.285240E+10 0.151463E+10 0.284344E+10 0.118149E+10 0.166195E+10 0.00 0.00
May 0.329786E+10 0.133061E+10 0.312653E+10 0.108702E+10 0.203951E+10 0.00 0.00
June 0.411868E+10 0.101354E+10 0.362359E+10 0.157665E+10 0.204694E+10 0.00 0.00
July 0.414863E+10 0.926563E+09 0.348688E+10 0.156511E+10 0.192177E+10 0.00 0.00
August 0.422219E+10 0.904724E+09 0.342712E+10 0.171444E+10 0.171268E+10 0.00 0.00
September 0.267754E+10 0.125214E+10 0.245211E+10 0.113094E+10 0.132118E+10 0.00 0.00
October 0.148247E+10 0.172729E+10 0.165156E+10 0.701758E+09 0.949803E+09 0.00 0.00
November 0.405646E+09 0.208020E+10 0.783391E+09 0.221159E+09 0.562232E+09 0.00 0.00
December 0.301211E+09 0.265582E+10 0.663975E+09 0.213753E+09 0.450222E+09 0.00 0.00
               
Annual Sum or Average 0.260356E+11 0.200098E+11 0.257925E+11 0.106609E+11 0.151316E+11 0.00 0.00
Minimum of Months 0.237847E+09 0.904724E+09 0.663975E+09 0.175407E+09 0.450222E+09 0.00 0.00
Maximum of Months 0.422219E+10 0.265582E+10 0.362359E+10 0.171444E+10 0.204694E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.250189E+10 0.371742E+10 0.285350E+10 0.169442E+10 0.115908E+10 0.00 0.00
February 0.398251E+10 0.307609E+10 0.396357E+10 0.245351E+10 0.151007E+10 0.00 0.00
March 0.497315E+10 0.300637E+10 0.472048E+10 0.251738E+10 0.220310E+10 0.00 0.00
April 0.538204E+10 0.248336E+10 0.482316E+10 0.209419E+10 0.272897E+10 0.00 0.00
May 0.513357E+10 0.215643E+10 0.455717E+10 0.135763E+10 0.319954E+10 0.00 0.00
June 0.464578E+10 0.165716E+10 0.403487E+10 0.108331E+10 0.295156E+10 0.00 0.00
July 0.580245E+10 0.155278E+10 0.454687E+10 0.166531E+10 0.288156E+10 0.00 0.00
August 0.645550E+10 0.150002E+10 0.488504E+10 0.227798E+10 0.260706E+10 0.00 0.00
September 0.648116E+10 0.200324E+10 0.523783E+10 0.289250E+10 0.234533E+10 0.00 0.00
October 0.552457E+10 0.267830E+10 0.490274E+10 0.302708E+10 0.187566E+10 0.00 0.00
November 0.264232E+10 0.307277E+10 0.280516E+10 0.160759E+10 0.119757E+10 0.00 0.00
December 0.293744E+10 0.386745E+10 0.303283E+10 0.196266E+10 0.107017E+10 0.00 0.00
               
Annual Sum or Average 0.564624E+11 0.307714E+11 0.503632E+11 0.246336E+11 0.257297E+11 0.00 0.00
Minimum of Months 0.250189E+10 0.150002E+10 0.280516E+10 0.108331E+10 0.107017E+10 0.00 0.00
Maximum of Months 0.648116E+10 0.386745E+10 0.523783E+10 0.302708E+10 0.319954E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.306036E+09 0.261597E+10 0.729733E+09 0.215185E+09 0.514548E+09 0.00 0.00
February 0.822129E+09 0.211680E+10 0.118174E+10 0.444131E+09 0.737608E+09 0.00 0.00
March 0.152657E+10 0.198135E+10 0.183334E+10 0.618801E+09 0.121454E+10 0.00 0.00
April 0.270837E+10 0.160215E+10 0.269925E+10 0.103203E+10 0.166722E+10 0.00 0.00
May 0.394143E+10 0.140800E+10 0.358909E+10 0.145805E+10 0.213103E+10 0.00 0.00
June 0.375467E+10 0.107833E+10 0.334037E+10 0.129696E+10 0.204342E+10 0.00 0.00
July 0.526911E+10 0.102614E+10 0.426413E+10 0.224144E+10 0.202268E+10 0.00 0.00
August 0.442606E+10 0.996268E+09 0.352745E+10 0.180122E+10 0.172623E+10 0.00 0.00
September 0.320036E+10 0.133216E+10 0.277991E+10 0.133386E+10 0.144605E+10 0.00 0.00
October 0.150052E+10 0.178599E+10 0.163536E+10 0.666333E+09 0.969031E+09 0.00 0.00
November 0.430461E+09 0.209463E+10 0.788130E+09 0.222286E+09 0.565845E+09 0.00 0.00
December 0.366356E+09 0.268570E+10 0.684662E+09 0.234616E+09 0.450046E+09 0.00 0.00
               
Annual Sum or Average 0.282521E+11 0.207235E+11 0.270532E+11 0.115649E+11 0.154883E+11 0.00 0.00
Minimum of Months 0.306036E+09 0.996268E+09 0.684662E+09 0.215185E+09 0.450046E+09 0.00 0.00
Maximum of Months 0.526911E+10 0.268570E+10 0.426413E+10 0.224144E+10 0.213103E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.483010E+10 -0.458408E+10 0.00 0.00 744.00 0.00 -246019356.5 60.05 0.00 0.00
February 0.441160E+10 -0.419457E+10 0.00 0.00 672.00 0.00 -217031703.3 60.05 0.00 0.00
March 0.514719E+10 -0.491064E+10 0.00 0.00 744.00 0.00 -236547115.8 60.05 0.00 0.00
April 0.452642E+10 -0.429981E+10 0.00 0.00 720.00 0.00 -226608719.5 60.05 0.00 0.00
May 0.467757E+10 -0.444432E+10 0.00 0.00 744.00 0.00 -233253641.6 60.05 0.00 0.00
June 0.447764E+10 -0.425257E+10 0.00 0.00 720.00 0.00 -225072685.1 60.05 0.00 0.00
July 0.412894E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -231500699.8 60.05 0.00 0.00
August 0.450680E+10 -0.427461E+10 0.00 0.00 744.00 0.00 -232192447.6 60.05 0.00 0.00
September 0.412382E+10 -0.389919E+10 0.00 0.00 720.00 0.00 -224629708.9 60.05 0.00 0.00
October 0.438634E+10 -0.415238E+10 0.00 0.00 744.00 0.00 -233959100.2 60.05 0.00 0.00
November 0.447354E+10 -0.424363E+10 0.00 0.00 720.00 0.00 -229904253.9 60.05 0.00 0.00
December 0.459194E+10 -0.435083E+10 0.00 0.00 744.00 0.00 -241109650.8 60.05 0.00 0.00
                     
Annual Sum or Average 0.542819E+11 -0.515041E+11 0.00 0.00 8760.00 0.00 -0.277783E+10 60.05 0.00 0.00
Minimum of Months 0.412382E+10 -0.491064E+10 0.00 0.00 672.00 0.00 -246019356.5 60.05 0.00 0.00
Maximum of Months 0.514719E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -217031703.3 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-09:00 2752.09 32.29 222.33 219.00 2197.51 33.54 226.00 187.50
February 259.50 0.51 0.48 01-FEB-08:39 4689.04 33.25 243.17 243.67 2070.44 29.39 222.17 221.17
March 247.00 0.51 0.48 01-MAR-07:40 7764.82 33.06 208.83 312.00 1690.81 21.84 156.00 267.33
April 379.50 0.52 0.48 01-APR-07:10 2189.81 18.65 2.83 344.33 1220.11 20.88 213.33 307.33
May 427.83 0.52 0.48 01-MAY-07:19 2000.57 18.54 4.83 384.83 1096.11 20.72 210.50 343.33
June 375.17 0.53 0.48 01-JUN-06:19 1747.28 18.11 0.00 394.17 1006.76 20.33 191.00 343.83
July 471.00 0.55 0.48 01-JUL-05:00 1556.83 16.90 0.00 393.00 915.75 19.12 151.50 337.50
August 366.67 0.53 0.48 01-AUG-06:10 1851.87 17.95 2.67 372.83 1114.36 20.19 160.50 326.50
September 301.17 0.51 0.48 01-SEP-07:40 2991.98 20.79 42.17 319.17 1482.59 21.67 187.00 288.00
October 245.33 0.52 0.48 01-OCT-07:00 7215.50 34.59 220.50 284.67 1974.15 23.03 157.67 256.33
November 242.67 0.52 0.48 01-NOV-08:20 3067.16 31.82 224.67 224.17 2463.70 33.16 229.67 193.83
December 160.33 0.51 0.48 01-DEC-09:39 3696.50 35.43 149.50 207.33 3150.63 36.90 149.67 167.17
                         
Annual Sum or Average 3714.00 0.52     3110.46 23.95 1321.50 3699.17 1524.23 23.68 2255.00 3239.83
Minimum of Months 160.33 0.51 0.48   1556.83 16.90 0.00 207.33 915.75 19.12 149.67 167.17
Maximum of Months 471.00 0.55 0.48   7764.82 35.43 243.17 394.17 3150.63 36.90 229.67 343.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.55 0.48 01-JAN-10:09 913.62 18.96 61.50 198.83 569.48 21.22 76.00 129.33
February 259.50 0.53 0.48 01-FEB-08:39 1473.30 19.70 68.33 226.83 790.18 21.91 79.83 179.50
March 247.00 0.52 0.48 01-MAR-07:30 2666.91 22.09 79.00 302.00 1194.76 23.03 91.33 253.00
April 379.50 0.52 0.48 01-APR-06:19 2804.50 21.12 105.50 346.67 1588.83 23.21 104.67 306.33
May 427.83 0.52 0.48 01-MAY-06:00 2895.55 21.04 132.67 390.83 1267.46 21.36 92.00 349.50
June 375.17 0.52 0.48 01-JUN-05:10 3039.46 20.27 89.00 402.67 1687.16 22.32 77.67 356.33
July 471.00 0.53 0.48 01-JUL-04:00 2867.10 20.73 148.50 406.33 1305.67 21.67 102.00 370.50
August 366.67 0.52 0.48 01-AUG-05:30 3352.76 22.21 116.33 377.67 1468.20 21.99 74.33 337.67
September 301.17 0.51 0.48 01-SEP-07:40 2737.77 21.79 82.67 322.83 1536.03 23.02 78.00 284.50
October 245.33 0.54 0.48 01-OCT-07:49 2450.96 21.99 83.00 270.50 1099.11 22.65 89.33 225.17
November 242.67 0.54 0.48 01-NOV-08:09 1138.50 20.35 79.17 207.50 597.99 21.17 72.00 144.00
December 160.33 0.55 0.48 01-DEC-09:39 1072.55 21.50 56.33 182.00 583.92 22.15 57.17 104.33
                         
Annual Sum or Average 3714.00 0.53     2465.15 20.99 1102.00 3634.67 1221.89 22.13 994.33 3040.17
Minimum of Months 160.33 0.51 0.48   913.62 18.96 56.33 182.00 569.48 21.17 57.17 104.33
Maximum of Months 471.00 0.55 0.48   3352.76 22.21 148.50 406.33 1687.16 23.21 104.67 370.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.60 0.48 03-JAN-10:30 491.44 14.25 0.00 177.17 269.77 16.44 0.00 46.33
February 259.50 0.56 0.48 01-FEB-11:09 622.46 15.49 0.00 214.00 354.25 17.74 0.00 127.33
March 247.00 0.53 0.48 01-MAR-08:39 836.80 17.02 0.00 297.50 498.62 19.28 4.17 215.00
April 379.50 0.52 0.48 01-APR-07:19 982.93 17.77 0.00 348.17 572.37 19.90 33.17 300.67
May 427.83 0.51 0.48 01-MAY-07:19 1225.96 20.02 40.00 399.33 702.73 22.07 163.83 366.83
June 375.17 0.51 0.48 01-JUN-05:40 1284.66 21.21 60.83 413.17 759.18 23.28 194.67 384.17
July 471.00 0.52 0.48 01-JUL-05:10 1086.93 20.33 79.33 423.50 653.58 22.40 182.00 382.17
August 366.67 0.51 0.48 01-AUG-05:00 954.47 17.85 0.00 390.67 586.05 20.04 54.67 345.17
September 301.17 0.52 0.48 01-SEP-07:49 908.91 17.90 0.00 313.33 555.12 20.11 17.33 255.17
October 245.33 0.55 0.48 01-OCT-08:50 677.62 16.04 0.00 258.83 413.24 18.38 0.33 165.33
November 242.67 0.58 0.48 01-NOV-11:39 529.45 14.58 0.00 190.33 290.42 16.72 0.00 64.83
December 160.33 0.61 0.48 01-DEC-10:20 457.77 14.23 0.00 151.33 270.01 16.70 0.00 36.17
                         
Annual Sum or Average 3714.00 0.53     906.93 17.81 180.17 3577.33 535.00 19.98 650.17 2689.17
Minimum of Months 160.33 0.51 0.48   457.77 14.23 0.00 151.33 269.77 16.44 0.00 36.17
Maximum of Months 471.00 0.61 0.48   1284.66 21.21 79.33 423.50 759.18 23.28 194.67 384.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.55 0.48 01-JAN-13:20 1023.10 18.87 65.17 199.67 562.37 21.17 68.67 136.67
February 259.50 0.53 0.48 01-FEB-10:00 1471.75 19.88 66.67 229.00 770.96 21.68 71.83 181.67
March 247.00 0.52 0.48 01-MAR-08:39 2357.65 22.15 78.17 304.67 1273.91 23.11 94.17 251.17
April 379.50 0.52 0.48 01-APR-07:00 2828.67 20.84 105.50 344.33 1243.19 20.76 60.00 306.00
May 427.83 0.51 0.48 01-MAY-08:09 2920.92 17.72 52.50 390.33 1583.55 18.63 12.33 354.67
June 375.17 0.52 0.48 01-JUN-06:30 2989.78 17.34 42.83 402.00 1356.40 18.43 1.17 361.33
July 471.00 0.54 0.48 01-JUL-09:00 3291.18 16.48 58.83 402.83 1449.01 17.25 4.67 360.50
August 366.67 0.52 0.48 01-AUG-07:10 3117.65 19.28 75.83 380.17 1803.21 20.74 54.50 341.67
September 301.17 0.51 0.48 01-SEP-08:09 3442.11 22.98 100.50 314.83 1950.03 23.92 95.67 271.67
October 245.33 0.53 0.48 01-OCT-08:00 2354.95 22.33 87.33 272.17 1073.45 23.23 85.17 225.17
November 242.67 0.55 0.48 01-NOV-10:20 1093.63 18.83 63.50 208.50 585.44 20.52 60.17 140.67
December 160.33 0.56 0.48 01-DEC-10:09 1093.79 20.33 48.67 182.50 587.30 21.08 50.00 101.00
                         
Annual Sum or Average 3714.00 0.53     2531.19 19.43 845.50 3631.00 1275.49 20.50 658.33 3032.17
Minimum of Months 160.33 0.51 0.48   1023.10 16.48 42.83 182.50 562.37 17.25 1.17 101.00
Maximum of Months 471.00 0.56 0.48   3442.11 22.98 105.50 402.83 1950.03 23.92 95.67 361.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-10:09 2635.62 30.49 207.17 216.33 2129.75 33.21 222.50 182.67
February 259.50 0.51 0.48 01-FEB-08:39 4558.93 32.09 231.50 240.83 1978.88 27.94 157.17 219.00
March 247.00 0.52 0.48 01-MAR-07:40 7608.54 32.26 207.67 309.83 1578.63 18.98 12.33 263.33
April 379.50 0.52 0.48 01-APR-07:19 2082.19 14.69 0.00 342.83 1143.61 18.20 10.83 302.83
May 427.83 0.52 0.48 01-MAY-07:19 1912.10 14.65 0.00 382.67 1036.32 18.10 3.50 340.00
June 375.17 0.53 0.48 01-JUN-06:19 1670.36 14.47 0.00 392.50 954.91 17.93 0.00 340.33
July 471.00 0.55 0.48 01-JUL-05:00 1485.50 13.11 0.00 389.67 865.65 16.61 1.00 332.50
August 366.67 0.53 0.48 01-AUG-06:10 1756.04 14.24 0.00 369.33 1043.42 17.81 5.83 322.67
September 301.17 0.51 0.48 01-SEP-07:40 2854.67 17.25 27.00 317.83 1378.94 19.09 29.83 282.83
October 245.33 0.52 0.48 01-OCT-07:00 7052.25 33.75 218.00 282.67 1855.32 20.33 28.33 254.50
November 242.67 0.52 0.48 01-NOV-08:20 2957.20 30.64 215.33 222.50 2395.69 32.84 227.00 190.00
December 160.33 0.51 0.48 01-DEC-09:39 3561.77 34.94 149.17 204.83 3049.98 36.51 149.67 161.50
                         
Annual Sum or Average 3714.00 0.52     3001.14 21.20 1255.83 3671.83 1447.69 21.57 848.00 3192.17
Minimum of Months 160.33 0.51 0.48   1485.50 13.11 0.00 204.83 865.65 16.61 0.00 161.50
Maximum of Months 471.00 0.55 0.48   7608.54 34.94 231.50 392.50 3049.98 36.51 227.00 340.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 01-JAN-10:20 884.08 18.46 61.33 197.00 548.16 20.99 72.50 124.50
February 259.50 0.54 0.48 01-FEB-08:39 1429.93 19.20 68.00 225.67 756.80 21.68 74.33 175.50
March 247.00 0.52 0.48 01-MAR-07:30 2597.20 21.62 79.00 300.00 1141.09 22.83 80.67 249.17
April 379.50 0.52 0.48 01-APR-06:19 2729.27 20.66 105.33 345.17 1529.69 23.03 95.50 303.67
May 427.83 0.52 0.48 01-MAY-07:10 2824.44 20.61 132.33 388.50 1212.69 21.18 85.17 344.50
June 375.17 0.52 0.48 01-JUN-05:19 2949.87 19.81 89.00 400.83 1619.06 22.12 75.83 352.00
July 471.00 0.54 0.48 01-JUL-05:10 2786.44 20.14 146.50 404.17 1246.46 20.68 87.17 365.67
August 366.67 0.52 0.48 01-AUG-05:30 3204.92 20.23 98.50 373.67 1402.06 21.81 71.33 332.83
September 301.17 0.51 0.48 01-SEP-07:40 2663.70 21.31 82.67 320.33 1478.31 22.81 68.50 280.83
October 245.33 0.54 0.48 01-OCT-07:49 2380.91 21.30 81.00 268.17 1050.31 22.43 77.50 221.17
November 242.67 0.55 0.48 01-NOV-08:20 1084.38 18.46 65.67 204.00 573.71 20.93 67.83 137.83
December 160.33 0.56 0.48 01-DEC-09:39 1037.26 21.02 56.33 179.00 558.26 21.90 54.83 98.67
                         
Annual Sum or Average 3714.00 0.53     2390.15 20.25 1065.67 3606.50 1170.75 21.82 911.17 2986.33
Minimum of Months 160.33 0.51 0.48   884.08 18.46 56.33 179.00 548.16 20.68 54.83 98.67
Maximum of Months 471.00 0.56 0.48   3204.92 21.62 146.50 404.17 1619.06 23.03 95.50 365.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.61 0.48 06-JAN-10:00 473.17 10.06 0.00 172.50 259.26 13.62 0.00 34.17
February 259.50 0.56 0.48 01-FEB-11:09 599.68 11.56 0.00 210.67 341.43 15.13 0.00 120.67
March 247.00 0.53 0.48 01-MAR-08:50 806.78 13.49 0.00 293.17 482.20 17.03 0.00 206.67
April 379.50 0.52 0.48 01-APR-07:30 948.35 14.27 0.00 346.00 553.25 17.71 0.17 294.83
May 427.83 0.51 0.48 01-MAY-07:19 1179.55 16.07 26.67 397.83 678.31 19.99 51.67 362.17
June 375.17 0.51 0.48 01-JUN-05:40 1240.40 18.32 59.00 411.00 734.14 21.52 73.67 380.83
July 471.00 0.52 0.48 01-JUL-05:10 1046.18 15.67 44.67 420.83 633.38 20.53 86.83 378.83
August 366.67 0.51 0.48 01-AUG-05:00 922.28 14.49 0.00 389.17 568.81 18.10 1.67 340.00
September 301.17 0.52 0.48 01-SEP-07:00 875.95 14.67 0.00 311.33 537.47 18.17 0.00 247.67
October 245.33 0.56 0.48 01-OCT-09:20 652.48 12.51 0.00 256.00 399.69 16.13 0.00 156.17
November 242.67 0.59 0.48 01-NOV-11:50 510.08 10.43 0.00 184.00 279.28 13.92 0.00 53.67
December 160.33 0.62 0.48 01-DEC-10:20 439.29 10.26 0.00 145.67 259.75 14.06 0.00 29.33
                         
Annual Sum or Average 3714.00 0.54     874.08 14.07 130.33 3538.17 517.28 17.79 214.00 2605.00
Minimum of Months 160.33 0.51 0.48   439.29 10.06 0.00 145.67 259.26 13.62 0.00 29.33
Maximum of Months 471.00 0.62 0.48   1240.40 18.32 59.00 420.83 734.14 21.52 86.83 380.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 01-JAN-13:30 992.40 18.47 64.83 198.00 539.60 21.07 67.67 130.33
February 259.50 0.54 0.48 01-FEB-10:00 1426.36 19.46 66.50 227.17 723.52 20.58 61.00 176.00
March 247.00 0.52 0.48 01-MAR-08:50 2292.69 21.75 78.17 302.50 1218.45 22.91 91.67 245.67
April 379.50 0.52 0.48 01-APR-07:00 2717.24 20.41 105.50 342.33 1188.49 20.62 55.33 303.50
May 427.83 0.52 0.48 01-MAY-08:20 2834.89 17.23 52.33 389.67 1518.62 18.46 8.83 351.50
June 375.17 0.52 0.48 01-JUN-06:30 2870.79 16.85 42.83 398.50 1294.17 18.25 0.83 358.83
July 471.00 0.54 0.48 01-JUL-09:00 3160.43 15.99 58.83 399.33 1381.24 17.09 4.00 357.83
August 366.67 0.52 0.48 01-AUG-07:30 3030.61 18.83 75.83 377.00 1727.31 20.59 54.17 337.50
September 301.17 0.51 0.48 01-SEP-08:20 3351.01 22.58 100.50 312.67 1845.77 23.52 91.50 266.33
October 245.33 0.53 0.48 01-OCT-09:20 2291.54 21.94 87.33 269.17 994.72 21.86 73.50 218.83
November 242.67 0.55 0.48 01-NOV-10:30 1060.51 18.42 63.00 206.83 561.00 20.40 58.50 133.17
December 160.33 0.56 0.48 01-DEC-10:09 1059.05 19.92 48.67 180.50 561.88 20.97 49.67 94.33
                         
Annual Sum or Average 3714.00 0.53     2448.00 18.99 844.33 3603.67 1215.23 20.18 616.67 2973.83
Minimum of Months 160.33 0.51 0.48   992.40 15.99 42.83 180.50 539.60 17.09 0.83 94.33
Maximum of Months 471.00 0.56 0.48   3351.01 22.58 105.50 399.33 1845.77 23.52 91.67 358.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.52 0.48 01-JAN-10:09 2635.60 30.49 207.17 216.33 2129.69 33.21 222.50 182.67
February 259.50 0.51 0.48 01-FEB-08:39 4558.88 32.09 231.50 240.83 1978.79 27.95 157.17 219.00
March 247.00 0.52 0.48 01-MAR-07:40 7608.44 32.26 207.67 309.83 1578.51 18.98 12.33 263.33
April 379.50 0.52 0.48 01-APR-07:19 2082.06 14.69 0.00 342.83 1143.52 18.20 10.83 302.83
May 427.83 0.52 0.48 01-MAY-07:19 1911.97 14.65 0.00 382.67 1036.24 18.10 3.50 340.00
June 375.17 0.53 0.48 01-JUN-06:19 1670.27 14.47 0.00 392.33 954.84 17.93 0.00 340.33
July 471.00 0.55 0.48 01-JUL-05:00 1485.42 13.11 0.00 389.67 865.58 16.61 1.00 332.50
August 366.67 0.53 0.48 01-AUG-06:10 1755.95 14.24 0.00 369.33 1043.35 17.81 5.83 322.67
September 301.17 0.51 0.48 01-SEP-07:40 2854.56 17.26 27.00 317.83 1378.84 19.09 30.00 282.83
October 245.33 0.52 0.48 01-OCT-07:00 7052.20 33.75 218.00 282.50 1855.21 20.33 28.33 254.50
November 242.67 0.52 0.48 01-NOV-08:20 2957.17 30.64 215.33 222.50 2395.61 32.84 227.00 189.83
December 160.33 0.51 0.48 01-DEC-09:39 3561.79 34.94 149.17 204.83 3049.91 36.51 149.67 161.50
                         
Annual Sum or Average 3714.00 0.52     3001.06 21.20 1255.83 3671.50 1447.61 21.57 848.17 3192.00
Minimum of Months 160.33 0.51 0.48   1485.42 13.11 0.00 204.83 865.58 16.61 0.00 161.50
Maximum of Months 471.00 0.55 0.48   7608.44 34.94 231.50 392.33 3049.91 36.51 227.00 340.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 01-JAN-10:20 884.05 18.46 61.33 197.00 548.12 20.99 72.50 124.50
February 259.50 0.54 0.48 01-FEB-08:39 1429.89 19.20 68.00 225.67 756.76 21.68 74.33 175.50
March 247.00 0.52 0.48 01-MAR-07:30 2597.15 21.62 79.00 300.00 1141.02 22.83 80.67 249.17
April 379.50 0.52 0.48 01-APR-06:19 2729.20 20.66 105.33 345.17 1529.62 23.03 95.50 303.67
May 427.83 0.52 0.48 01-MAY-07:10 2824.36 20.61 132.33 388.50 1212.62 21.18 85.17 344.50
June 375.17 0.52 0.48 01-JUN-05:19 2949.81 19.81 89.00 400.83 1618.98 22.12 75.83 352.00
July 471.00 0.54 0.48 01-JUL-05:10 2786.39 20.14 146.50 404.17 1246.40 20.68 87.17 365.67
August 366.67 0.52 0.48 01-AUG-05:30 3204.88 20.24 98.50 373.67 1402.00 21.81 71.33 332.83
September 301.17 0.51 0.48 01-SEP-07:40 2663.66 21.31 82.67 320.33 1478.25 22.81 68.50 280.83
October 245.33 0.54 0.48 01-OCT-07:49 2380.88 21.30 81.00 268.17 1050.26 22.43 77.50 221.17
November 242.67 0.55 0.48 01-NOV-08:20 1084.34 18.46 65.67 204.00 573.67 20.93 67.83 137.83
December 160.33 0.56 0.48 01-DEC-09:39 1037.24 21.02 56.33 179.00 558.22 21.90 54.83 98.67
                         
Annual Sum or Average 3714.00 0.53     2390.10 20.25 1065.67 3606.50 1170.69 21.82 911.17 2986.33
Minimum of Months 160.33 0.51 0.48   884.05 18.46 56.33 179.00 548.12 20.68 54.83 98.67
Maximum of Months 471.00 0.56 0.48   3204.88 21.62 146.50 404.17 1618.98 23.03 95.50 365.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.61 0.48 06-JAN-10:00 473.14 10.07 0.00 172.50 259.23 13.62 0.00 34.17
February 259.50 0.56 0.48 01-FEB-11:09 599.65 11.56 0.00 210.67 341.41 15.13 0.00 120.67
March 247.00 0.53 0.48 01-MAR-08:50 806.75 13.50 0.00 293.17 482.17 17.03 0.00 206.67
April 379.50 0.52 0.48 01-APR-07:30 948.32 14.27 0.00 346.00 553.21 17.71 0.17 294.83
May 427.83 0.51 0.48 01-MAY-07:19 1179.50 16.07 26.67 397.83 678.27 19.99 51.67 362.17
June 375.17 0.51 0.48 01-JUN-05:40 1240.36 18.32 59.00 411.00 734.09 21.52 73.67 380.83
July 471.00 0.52 0.48 01-JUL-05:10 1046.15 15.67 44.67 420.83 633.34 20.53 86.83 378.83
August 366.67 0.51 0.48 01-AUG-05:00 922.26 14.49 0.00 389.17 568.78 18.10 1.67 340.00
September 301.17 0.52 0.48 01-SEP-07:00 875.93 14.67 0.00 311.33 537.44 18.17 0.00 247.67
October 245.33 0.56 0.48 01-OCT-09:20 652.46 12.52 0.00 256.00 399.67 16.13 0.00 156.17
November 242.67 0.59 0.48 01-NOV-11:50 510.06 10.43 0.00 184.00 279.26 13.93 0.00 53.67
December 160.33 0.62 0.48 01-DEC-10:20 439.28 10.26 0.00 145.67 259.73 14.06 0.00 29.33
                         
Annual Sum or Average 3714.00 0.54     874.05 14.07 130.33 3538.17 517.25 17.79 214.00 2605.00
Minimum of Months 160.33 0.51 0.48   439.28 10.07 0.00 145.67 259.23 13.62 0.00 29.33
Maximum of Months 471.00 0.62 0.48   1240.36 18.32 59.00 420.83 734.09 21.52 86.83 380.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 01-JAN-13:30 992.37 18.47 64.83 198.00 539.57 21.07 67.67 130.33
February 259.50 0.54 0.48 01-FEB-10:00 1426.32 19.46 66.50 227.17 723.47 20.58 61.00 176.00
March 247.00 0.52 0.48 01-MAR-08:50 2292.64 21.76 78.17 302.50 1218.39 22.91 91.67 245.67
April 379.50 0.52 0.48 01-APR-07:00 2717.18 20.42 105.50 342.33 1188.42 20.62 55.33 303.50
May 427.83 0.52 0.48 01-MAY-08:20 2834.81 17.23 52.33 389.67 1518.54 18.46 8.83 351.50
June 375.17 0.52 0.48 01-JUN-06:30 2870.72 16.85 42.83 398.50 1294.09 18.25 0.83 358.83
July 471.00 0.54 0.48 01-JUL-09:00 3160.37 15.99 58.83 399.33 1381.18 17.09 4.00 357.83
August 366.67 0.52 0.48 01-AUG-07:30 3030.58 18.83 75.83 377.00 1727.25 20.59 54.17 337.50
September 301.17 0.51 0.48 01-SEP-08:20 3350.97 22.58 100.50 312.67 1845.69 23.52 91.50 266.33
October 245.33 0.53 0.48 01-OCT-09:20 2291.52 21.94 87.33 269.17 994.67 21.86 73.67 218.83
November 242.67 0.55 0.48 01-NOV-10:30 1060.48 18.42 63.00 206.83 560.96 20.40 58.50 133.17
December 160.33 0.56 0.48 01-DEC-10:09 1059.03 19.92 48.67 180.50 561.84 20.97 49.67 94.33
                         
Annual Sum or Average 3714.00 0.53     2447.95 18.99 844.33 3603.67 1215.17 20.18 616.83 2973.83
Minimum of Months 160.33 0.51 0.48   992.37 15.99 42.83 180.50 539.57 17.09 0.83 94.33
Maximum of Months 471.00 0.56 0.48   3350.97 22.58 105.50 399.33 1845.69 23.52 91.67 358.83



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.461564E+10 12316.25 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.265306E+10 10350.96 18-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.412107E+09 7588.48 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.112200E+09 4895.59 19-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 68275.19 76.86 17-MAY-21:00 0.00 0.00 0.00 0.00 0.00
June 1564.77 2.61 28-JUN-16:50 0.00 0.00 0.00 0.00 0.00
July 377359.92 5.18 31-JUL-14:20 0.00 0.00 0.00 0.00 0.00
August 951267.94 5.34 14-AUG-16:00 0.00 0.00 0.00 0.00 0.00
September 206711.79 5.16 12-SEP-15:00 0.00 0.00 0.00 0.00 0.00
October 8014880.89 884.68 31-OCT-21:00 0.00 0.00 0.00 0.00 0.00
November 0.124135E+10 7707.42 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.316796E+10 11539.66 26-DEC-07:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122119E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1564.77 2.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.461564E+10 12316.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.400752E+09 10346.90 03-JAN-07:17 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.400752E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400752E+09 10346.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.467187E+10 8154.46 03-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.271217E+10 8138.54 24-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.188169E+10 8134.09 09-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.103692E+10 8161.15 26-APR-06:07 0.00 0.00 0.00 0.00 0.00
May 0.674798E+09 8207.11 23-MAY-06:07 0.00 0.00 0.00 0.00 0.00
June 0.347787E+09 8218.72 09-JUN-06:07 0.00 0.00 0.00 0.00 0.00
July 88043771.70 8153.15 03-JUL-06:06 0.00 0.00 0.00 0.00 0.00
August 90332867.50 8201.55 03-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.309887E+09 8202.86 26-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.933685E+09 8217.99 11-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.244453E+10 8136.88 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.364837E+10 8134.62 29-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.188401E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 88043771.70 8134.09   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.467187E+10 8218.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.168232E+10 5458.67 04-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.748495E+09 5446.28 21-FEB-06:06 0.00 0.00 0.00 0.00 0.00
March 0.181529E+09 5440.12 06-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 22766989.06 5432.36 11-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 18714760.22 4645.43 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.372898E+09 5440.01 13-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.104553E+10 5448.72 11-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.407226E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168232E+10 5458.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.237311E+10 5910.01 03-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.115044E+10 5894.89 22-FEB-06:14 0.00 0.00 0.00 0.00 0.00
March 0.320654E+09 5892.55 06-MAR-07:04 0.00 0.00 0.00 0.00 0.00
April 46715812.45 5885.50 19-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 17484887.44 5883.89 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.442658E+09 5890.30 24-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.139676E+10 5892.27 11-DEC-06:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.574783E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.237311E+10 5910.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.181594E+10 5659.51 04-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.857744E+09 5640.67 22-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.270078E+09 5640.83 10-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 46784542.29 5633.81 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 74092.82 287.19 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 28730206.71 4224.41 28-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.449384E+09 5640.13 13-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.116830E+10 5640.33 18-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.463703E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181594E+10 5659.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.569122E+10 13238.81 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.352593E+10 11528.18 18-FEB-07:08 0.00 0.00 0.00 0.00 0.00
March 0.107616E+10 8862.42 01-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 0.349744E+09 6447.89 19-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 27030036.08 2488.85 18-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 301945.07 4.83 31-JUL-12:10 0.00 0.00 0.00 0.00 0.00
August 767349.76 4.83 14-AUG-15:20 0.00 0.00 0.00 0.00 0.00
September 143095.01 4.85 13-SEP-15:20 0.00 0.00 0.00 0.00 0.00
October 0.112668E+09 3162.90 16-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.217497E+10 9307.47 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.447304E+10 12199.90 26-DEC-08:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174320E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.569122E+10 13238.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.133083E+10 14777.45 04-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.215157E+09 14759.20 22-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 10391111.62 14607.42 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 74896015.35 14784.05 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.408451E+09 14770.90 18-DEC-07:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.203973E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133083E+10 14784.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.186013E+10 8765.77 03-JAN-06:14 0.00 0.00 0.00 0.00 0.00
February 0.780974E+09 8762.30 15-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.195322E+09 8742.60 06-MAR-06:12 0.00 0.00 0.00 0.00 0.00
April 40225613.14 8719.58 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 623407.87 1347.57 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 60154581.14 8713.79 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.620870E+09 8763.78 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.137575E+10 8764.23 20-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.493405E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.186013E+10 8765.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.177082E+10 6013.44 09-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.831395E+09 6008.29 06-FEB-06:13 0.00 0.00 0.00 0.00 0.00
March 0.196828E+09 5992.66 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 28345570.42 5979.66 17-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 1170388.48 1886.73 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 255963.89 967.70 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 75741931.12 5976.33 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.646573E+09 6005.93 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.133946E+10 6011.80 26-DEC-06:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.489059E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.177082E+10 6013.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.203007E+10 6331.25 05-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.897084E+09 6331.71 06-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 0.169718E+09 6333.33 06-MAR-07:04 0.00 0.00 0.00 0.00 0.00
April 24263401.25 6278.52 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 38255766.12 6280.10 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.575283E+09 6316.62 13-NOV-07:04 0.00 0.00 0.00 0.00 0.00
December 0.142754E+10 6332.24 18-DEC-07:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.516222E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.203007E+10 6333.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.174127E+10 6036.14 09-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.842700E+09 6027.26 15-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.241056E+09 6015.20 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 46922001.97 6002.09 17-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 1348239.68 2090.61 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 247659.09 534.78 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 84201880.96 5998.76 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.652603E+09 6028.19 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.133097E+10 6034.42 26-DEC-06:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.494131E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.174127E+10 6036.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.605958E+10 14465.73 07-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.387409E+10 13604.30 18-FEB-07:15 0.00 0.00 0.00 0.00 0.00
March 0.154310E+10 10952.39 01-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 0.561851E+09 8356.17 19-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 86953701.72 4226.87 18-MAY-06:08 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 310478.86 4.97 31-JUL-12:20 0.00 0.00 0.00 0.00 0.00
August 788566.15 5.34 09-AUG-14:10 0.00 0.00 0.00 0.00 0.00
September 11731525.06 1630.40 27-SEP-06:08 0.00 0.00 0.00 0.00 0.00
October 0.265449E+09 4455.86 16-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.248993E+10 10222.94 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.496182E+10 12200.40 26-DEC-08:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198556E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.605958E+10 14465.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.384026E+10 21427.47 27-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.164266E+10 21418.77 16-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 0.291670E+09 21404.95 06-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 30491673.80 21228.40 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 70019819.85 21244.79 23-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.117231E+10 21431.85 20-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.272759E+10 21430.22 28-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.977500E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.384026E+10 21431.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.317230E+10 10429.78 03-JAN-06:15 0.00 0.00 0.00 0.00 0.00
February 0.170781E+10 10422.61 22-FEB-06:14 0.00 0.00 0.00 0.00 0.00
March 0.765169E+09 10421.46 06-MAR-06:14 0.00 0.00 0.00 0.00 0.00
April 0.260290E+09 10385.98 07-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 36690136.07 10373.33 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 812881.48 1044.15 15-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 17343967.42 10378.82 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.368175E+09 10379.60 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.152571E+10 10422.55 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.265379E+10 10422.77 18-DEC-06:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105081E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.317230E+10 10429.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.258685E+10 6914.99 06-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.142485E+10 6909.15 13-FEB-06:17 0.00 0.00 0.00 0.00 0.00
March 0.573746E+09 6903.95 06-MAR-06:14 0.00 0.00 0.00 0.00 0.00
April 0.134361E+09 6886.85 12-APR-05:12 0.00 0.00 0.00 0.00 0.00
May 21063209.90 6872.03 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 642213.23 944.29 14-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 13173598.61 6875.63 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.312329E+09 6879.74 31-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.123582E+10 6909.75 13-NOV-07:06 0.00 0.00 0.00 0.00 0.00
December 0.216387E+10 6919.37 11-DEC-06:25 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.846670E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.258685E+10 6919.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.346664E+10 7587.88 04-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.196359E+10 7584.10 06-FEB-07:17 0.00 0.00 0.00 0.00 0.00
March 0.758896E+09 7587.08 14-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.200121E+09 7585.85 18-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 11812826.20 7532.07 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 9037538.48 7536.60 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.323049E+09 7540.64 31-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.150182E+10 7587.76 13-NOV-06:17 0.00 0.00 0.00 0.00 0.00
December 0.286241E+10 7587.55 20-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.110974E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.346664E+10 7587.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.275139E+10 7155.09 09-JAN-07:40 0.00 0.00 0.00 0.00 0.00
February 0.161634E+10 7158.39 13-FEB-06:17 0.00 0.00 0.00 0.00 0.00
March 0.779915E+09 7152.54 06-MAR-06:14 0.00 0.00 0.00 0.00 0.00
April 0.244487E+09 7127.91 07-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 36920453.77 7119.27 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 1117405.49 897.70 14-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 20535074.67 7122.73 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.403005E+09 7127.17 31-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.140780E+10 7153.23 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.234191E+10 7153.37 18-DEC-06:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.960343E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.275139E+10 7158.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 2824018.97 2590215.13 3467.54 03-JAN-07:25 3292.02 0.00
February 0.00 0.00 0.211916E+09 0.195303E+09 13330.76 27-FEB-15:10 13330.76 0.00
March 0.00 0.00 0.321181E+09 0.283806E+09 10815.83 18-MAR-16:00 10815.83 0.00
April 0.00 0.00 0.353408E+10 0.340468E+10 51950.68 27-APR-15:00 51950.68 0.00
May 0.00 0.00 0.770096E+10 0.690822E+10 46599.70 15-MAY-16:00 46599.70 0.00
June 0.00 0.00 0.146596E+11 0.137081E+11 53880.48 28-JUN-15:30 53880.48 0.00
July 0.00 0.00 0.281712E+11 0.251131E+11 71647.56 31-JUL-16:00 65481.60 0.00
August 0.00 0.00 0.380933E+11 0.335915E+11 72382.29 10-AUG-15:30 68296.21 0.00
September 0.00 0.00 0.139892E+11 0.117607E+11 57860.73 12-SEP-16:00 54733.37 0.00
October 0.00 0.00 0.180820E+10 0.171346E+10 35441.99 04-OCT-15:00 35441.99 0.00
November 0.00 0.00 0.366284E+09 0.252063E+09 19368.19 04-NOV-14:20 14748.52 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.108859E+12 0.969337E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.380933E+11 0.335915E+11 72382.29   68296.21 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.210345E+09 0.196605E+09 13578.77 27-FEB-15:00 13578.77 0.00
March 0.00 0.00 0.322623E+09 0.290740E+09 12030.88 18-MAR-16:00 12030.88 0.00
April 0.00 0.00 0.350365E+10 0.338393E+10 49846.92 27-APR-14:50 49846.92 0.00
May 0.00 0.00 0.734009E+10 0.660658E+10 44298.93 04-MAY-15:00 44298.93 0.00
June 0.00 0.00 0.134516E+11 0.125718E+11 49984.85 28-JUN-15:30 49984.85 0.00
July 0.00 0.00 0.253931E+11 0.227128E+11 65671.85 31-JUL-14:40 59417.92 0.00
August 0.00 0.00 0.334197E+11 0.295095E+11 67191.91 29-AUG-14:40 60187.97 0.00
September 0.00 0.00 0.124764E+11 0.104646E+11 52578.57 14-SEP-13:00 38284.01 0.00
October 0.00 0.00 0.161693E+10 0.151808E+10 31746.37 04-OCT-15:00 31746.37 0.00
November 0.00 0.00 0.383128E+09 0.275257E+09 19812.91 04-NOV-13:40 15439.56 0.00
December 0.00 0.00 43020.58 42697.15 501.91 27-DEC-07:04 498.13 0.00
                 
Annual Sum or Average 0.00 0.00 0.981177E+11 0.875299E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.334197E+11 0.295095E+11 67191.91   60187.97 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 306623.24 290659.09 666.90 03-JAN-07:12 600.08 0.00
February 0.00 0.00 0.215832E+09 0.196455E+09 13470.71 27-FEB-15:00 13470.71 0.00
March 0.00 0.00 0.329246E+09 0.292254E+09 12113.99 18-MAR-16:00 12113.99 0.00
April 0.00 0.00 0.375525E+10 0.359781E+10 57561.79 27-APR-14:40 57561.79 0.00
May 0.00 0.00 0.765878E+10 0.679918E+10 48074.45 04-MAY-15:00 48074.45 0.00
June 0.00 0.00 0.140954E+11 0.130322E+11 57977.23 28-JUN-15:20 57977.23 0.00
July 0.00 0.00 0.268474E+11 0.237152E+11 73743.41 31-JUL-14:40 67194.86 0.00
August 0.00 0.00 0.350887E+11 0.307456E+11 75608.63 10-AUG-14:50 70565.84 0.00
September 0.00 0.00 0.125461E+11 0.103414E+11 53504.18 14-SEP-13:30 43201.95 0.00
October 0.00 0.00 0.147745E+10 0.136982E+10 30989.70 04-OCT-15:00 30989.70 0.00
November 0.00 0.00 0.394950E+09 0.274748E+09 20659.46 04-NOV-13:40 15517.95 0.00
December 0.00 0.00 35537.80 33890.41 414.61 26-DEC-06:01 395.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.102409E+12 0.903650E+11       0.00
Minimum of Months 0.00 0.00 35537.80 33890.41 414.61   395.39 0.00
Maximum of Months 0.00 0.00 0.350887E+11 0.307456E+11 75608.63   70565.84 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 19230.51 174234.70 02-JAN-06:11
February 0.00 0.00 01-FEB-00:10 11265.29 166854.19 06-FEB-06:11
March 0.00 0.00 01-MAR-00:10 3582.10 170694.10 01-MAR-07:01
April 0.00 0.00 01-APR-00:10 1223.40 155430.89 18-APR-06:02
May 0.00 0.00 01-MAY-00:10 333.04 67450.33 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 131.55 10926.40 15-JUN-06:05
July 0.00 0.00 01-JUL-00:10 31.82 11311.26 12-JUL-06:06
August 0.00 0.00 01-AUG-00:10 35.56 11789.65 01-AUG-06:07
September 0.00 0.00 01-SEP-00:10 146.94 54334.95 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 1152.53 140686.83 31-OCT-06:03
November 0.00 0.00 01-NOV-00:10 7290.64 161606.26 28-NOV-07:01
December 0.00 0.00 01-DEC-00:10 14273.25 162807.09 21-DEC-07:01
             
Annual Sum or Average 0.00     4868.51    
Minimum of Months 0.00 0.00   31.82 10926.40  
Maximum of Months 0.00 0.00   19230.51 174234.70  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 1702.15 6226.75 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 1724.48 6234.19 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 1823.75 6212.85 01-MAR-12:17
April 0.00 0.00 01-APR-00:10 1649.61 6074.20 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 1649.95 5884.98 01-MAY-11:15
June 0.00 0.00 01-JUN-00:10 1631.24 5653.23 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 1446.19 5455.86 03-JUL-11:17
August 0.00 0.00 01-AUG-00:10 1586.59 5376.19 31-AUG-11:40
September 0.00 0.00 01-SEP-00:10 1495.25 5493.56 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 1541.18 5706.33 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 1627.90 5930.86 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 1615.25 6114.32 29-DEC-12:20
             
Annual Sum or Average 0.00     1623.90    
Minimum of Months 0.00 0.00   1446.19 5376.19  
Maximum of Months 0.00 0.00   1823.75 6234.19  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.140188E+10 0.28 2634.26 02-JAN-06:11 0.78
February 0.128243E+10 0.28 1751.02 27-FEB-15:30 0.63
March 0.175009E+10 0.31 2172.09 02-MAR-16:20 0.70
April 0.202618E+10 0.32 5941.82 27-APR-14:50 1.24
May 0.274398E+10 0.37 6437.90 15-MAY-15:20 1.31
June 0.335534E+10 0.41 6719.94 28-JUN-15:20 1.34
July 0.419019E+10 0.44 9442.83 24-JUL-14:10 1.66
August 0.491926E+10 0.49 9723.56 10-AUG-15:40 1.69
September 0.327534E+10 0.39 8550.33 11-SEP-15:30 1.56
October 0.215670E+10 0.32 6284.42 04-OCT-15:30 1.29
November 0.148443E+10 0.28 1805.48 06-NOV-17:00 0.64
December 0.136608E+10 0.27 1654.95 01-DEC-06:11 0.62
           
Annual Sum or Average 0.299519E+11 0.35      
Minimum of Months 0.128243E+10 0.27 1654.95   0.62
Maximum of Months 0.491926E+10 0.49 9723.56   1.69



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138850E+10 0.28 2728.31 02-JAN-07:08 0.82
February 0.124087E+10 0.28 2728.31 21-FEB-06:01 0.82
March 0.151928E+10 0.30 2728.31 06-MAR-07:02 0.82
April 0.173607E+10 0.31 6134.37 27-APR-14:30 1.32
May 0.233819E+10 0.35 6175.00 15-MAY-14:50 1.34
June 0.284381E+10 0.40 6206.81 28-JUN-15:20 1.33
July 0.353208E+10 0.42 8271.99 31-JUL-14:50 1.59
August 0.403351E+10 0.46 8532.40 10-AUG-15:20 1.63
September 0.261438E+10 0.37 7296.09 11-SEP-14:50 1.48
October 0.167497E+10 0.30 5302.94 04-OCT-15:00 1.22
November 0.128630E+10 0.27 2728.31 13-NOV-07:01 0.82
December 0.131602E+10 0.27 2728.31 11-DEC-07:03 0.82
           
Annual Sum or Average 0.255240E+11 0.33      
Minimum of Months 0.124087E+10 0.27 2728.31   0.82
Maximum of Months 0.403351E+10 0.46 8532.40   1.63



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.154405E+10 0.30 2600.03 02-JAN-06:11 0.75
February 0.130861E+10 0.28 2600.03 01-FEB-07:03 0.75
March 0.151616E+10 0.29 2600.03 01-MAR-07:01 0.75
April 0.165988E+10 0.29 6110.32 27-APR-14:30 1.22
May 0.215759E+10 0.33 6248.68 15-MAY-14:50 1.25
June 0.259346E+10 0.36 6372.94 28-JUN-15:20 1.26
July 0.323365E+10 0.38 8221.61 31-JUL-14:50 1.47
August 0.363708E+10 0.41 8751.21 10-AUG-15:20 1.53
September 0.230392E+10 0.33 6489.18 14-SEP-14:30 1.27
October 0.154344E+10 0.28 4449.95 04-OCT-14:50 1.02
November 0.131197E+10 0.27 2600.03 10-NOV-07:02 0.75
December 0.138885E+10 0.27 2600.03 01-DEC-07:01 0.75
           
Annual Sum or Average 0.241987E+11 0.32      
Minimum of Months 0.130861E+10 0.27 2600.03   0.75
Maximum of Months 0.363708E+10 0.41 8751.21   1.53



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.318884E+09 0.286996E+09 558.22 07-JAN-07:15 502.40 502.40 42.00 1.71
February 0.174560E+09 0.157104E+09 557.86 18-FEB-07:03 502.07 502.07 38.30 1.71
March 65678595.85 59110736.27 530.62 06-MAR-07:02 477.56 477.56 36.97 1.48
April 23665483.11 21298934.80 518.30 18-APR-06:02 466.47 466.47 32.28 1.34
May 8665951.25 7799356.13 373.75 18-MAY-06:03 336.37 336.37 31.58 0.57
June 3813187.96 3431869.16 98.54 14-JUN-06:05 88.69 88.69 37.90 0.11
July 719237.62 647313.86 84.56 03-JUL-06:06 76.11 76.11 34.11 0.09
August 958167.40 862350.66 84.79 21-AUG-06:08 76.31 76.31 41.99 0.09
September 3859083.58 3473175.22 349.24 28-SEP-06:03 314.31 314.31 34.39 0.51
October 23294364.69 20964928.22 514.97 31-OCT-06:03 463.47 463.47 34.14 1.30
November 0.123173E+09 0.110856E+09 542.74 24-NOV-07:01 488.47 488.47 39.58 1.59
December 0.239526E+09 0.215574E+09 563.08 26-DEC-07:01 506.77 506.77 41.81 1.74
                 
Annual Sum or Average 0.986798E+09 0.888118E+09            
Minimum of Months 719237.62 647313.86 84.56   76.11 76.11 31.58 0.09
Maximum of Months 0.318884E+09 0.286996E+09 563.08   506.77 506.77 42.00 1.74



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:05 2.06 2.06 58.14 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:05 2.06 2.06 56.83 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:03 2.06 2.06 57.01 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.90 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.23 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.21 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 57.31 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.42 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.35 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.20 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.18 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:03 2.06 2.06 57.07 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.83 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.20 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 34.32 60.00 19230.51 174234.70 02-JAN-06:11
February 0.00 0.00 01-FEB-00:10 27.99 27.99 11265.29 166854.19 06-FEB-06:11
March 0.00 0.00 01-MAR-00:10 26.66 26.66 3582.10 170694.10 01-MAR-07:01
April 0.00 0.00 01-APR-00:10 21.74 21.74 1223.40 155430.89 18-APR-06:02
May 0.00 0.00 01-MAY-00:10 39.77 39.77 333.04 67450.33 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 44.08 44.08 131.55 10926.40 15-JUN-06:05
July 0.00 0.00 01-JUL-00:10 33.90 33.90 31.82 11311.26 12-JUL-06:06
August 0.00 0.00 01-AUG-00:10 28.30 28.30 35.56 11789.65 01-AUG-06:07
September 0.00 0.00 01-SEP-00:10 34.52 34.52 146.94 54334.95 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 38.64 38.64 1152.53 140686.83 31-OCT-06:03
November 0.00 0.00 01-NOV-00:10 24.04 24.04 7290.64 161606.26 28-NOV-07:01
December 0.00 0.00 01-DEC-00:10 29.28 29.28 14273.25 162807.09 21-DEC-07:01
                 
Annual Sum or Average 0.00         4868.51    
Minimum of Months 0.00 0.00   21.74 21.74 31.82 10926.40  
Maximum of Months 0.00 0.00   44.08 60.00 19230.51 174234.70  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 58.14 58.14 1702.15 6226.75 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 57.61 57.61 1724.48 6234.19 10-FEB-12:40
March 0.00 0.00 01-MAR-00:10 57.62 57.62 1823.75 6212.85 01-MAR-12:17
April 0.00 0.00 01-APR-00:10 57.67 57.67 1649.61 6074.20 03-APR-12:00
May 0.00 0.00 01-MAY-00:10 58.21 58.21 1649.95 5884.98 01-MAY-11:15
June 0.00 0.00 01-JUN-00:10 57.84 57.84 1631.24 5653.23 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 57.91 57.91 1446.19 5455.86 03-JUL-11:17
August 0.00 0.00 01-AUG-00:10 57.95 57.95 1586.59 5376.19 31-AUG-11:40
September 0.00 0.00 01-SEP-00:10 57.95 57.95 1495.25 5493.56 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 57.04 57.04 1541.18 5706.33 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 57.82 57.82 1627.90 5930.86 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 57.74 57.74 1615.25 6114.32 29-DEC-12:20
                 
Annual Sum or Average 0.00         1623.90    
Minimum of Months 0.00 0.00   57.04 57.04 1446.19 5376.19  
Maximum of Months 0.00 0.00   58.21 58.21 1823.75 6234.19  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.155596E+11 0.00 0.00 0.140263E+10 0.00 0.00
February 0.812192E+10 0.00 0.00 0.133535E+10 0.00 0.00
March 0.306606E+10 0.00 0.00 0.183262E+10 0.00 0.00
April 0.126538E+10 0.00 0.00 0.284262E+10 0.00 0.00
May 0.674940E+09 0.00 0.00 0.450748E+10 0.00 0.00
June 0.347789E+09 0.00 0.00 0.670249E+10 0.00 0.00
July 88421131.61 0.00 0.00 0.105151E+11 0.00 0.00
August 91284135.44 0.00 0.00 0.135264E+11 0.00 0.00
September 0.310094E+09 0.00 0.00 0.641538E+10 0.00 0.00
October 0.100663E+10 0.00 0.00 0.258683E+10 0.00 0.00
November 0.495082E+10 0.00 0.00 0.157100E+10 0.00 0.00
December 0.104269E+11 0.00 0.00 0.136608E+10 0.00 0.00
             
Annual Sum or Average 0.459099E+11 0.00 0.00 0.546039E+11 0.00 0.00
Minimum of Months 88421131.61 0.00 0.00 0.133535E+10 0.00 0.00
Maximum of Months 0.155596E+11 0.00 0.00 0.135264E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.144243E+11 0.00 0.00 0.138850E+10 0.00 0.00
February 0.709324E+10 0.00 0.00 0.129322E+10 0.00 0.00
March 0.188948E+10 0.00 0.00 0.160134E+10 0.00 0.00
April 0.489501E+09 0.00 0.00 0.254535E+10 0.00 0.00
May 30172072.11 0.00 0.00 0.401847E+10 0.00 0.00
June 0.00 0.00 0.00 0.592415E+10 0.00 0.00
July 301945.07 0.00 0.00 0.924850E+10 0.00 0.00
August 767349.76 0.00 0.00 0.116158E+11 0.00 0.00
September 646717.99 0.00 0.00 0.542539E+10 0.00 0.00
October 0.371022E+09 0.00 0.00 0.206021E+10 0.00 0.00
November 0.474519E+10 0.00 0.00 0.137551E+10 0.00 0.00
December 0.103552E+11 0.00 0.00 0.131604E+10 0.00 0.00
             
Annual Sum or Average 0.393999E+11 0.00 0.00 0.478125E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.129322E+10 0.00 0.00
Maximum of Months 0.144243E+11 0.00 0.00 0.116158E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.218770E+11 0.00 0.00 0.154413E+10 0.00 0.00
February 0.122293E+11 0.00 0.00 0.136272E+10 0.00 0.00
March 0.471250E+10 0.00 0.00 0.160039E+10 0.00 0.00
April 0.143160E+10 0.00 0.00 0.252975E+10 0.00 0.00
May 0.193440E+09 0.00 0.00 0.391678E+10 0.00 0.00
June 2572500.20 0.00 0.00 0.583567E+10 0.00 0.00
July 310478.86 0.00 0.00 0.930419E+10 0.00 0.00
August 788566.15 0.00 0.00 0.116468E+11 0.00 0.00
September 71821704.24 0.00 0.00 0.514878E+10 0.00 0.00
October 0.174203E+10 0.00 0.00 0.190046E+10 0.00 0.00
November 0.933338E+10 0.00 0.00 0.140481E+10 0.00 0.00
December 0.177114E+11 0.00 0.00 0.138886E+10 0.00 0.00
             
Annual Sum or Average 0.693062E+11 0.00 0.00 0.475833E+11 0.00 0.00
Minimum of Months 310478.86 0.00 0.00 0.136272E+10 0.00 0.00
Maximum of Months 0.218770E+11 0.00 0.00 0.116468E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.140188E+10 2824018.97 0.155596E+11 0.00 0.00 0.00 0.00 0.00
February 0.128243E+10 0.211916E+09 0.812192E+10 0.00 0.00 0.00 0.00 0.00
March 0.175009E+10 0.321181E+09 0.306606E+10 0.00 0.00 0.00 0.00 0.00
April 0.202618E+10 0.353408E+10 0.126538E+10 0.00 0.00 0.00 0.00 0.00
May 0.274398E+10 0.770096E+10 0.674940E+09 0.00 0.00 0.00 0.00 0.00
June 0.335534E+10 0.146596E+11 0.347789E+09 0.00 0.00 0.00 0.00 0.00
July 0.419019E+10 0.281712E+11 88421131.61 0.00 0.00 0.00 0.00 0.00
August 0.491926E+10 0.380933E+11 91284135.44 0.00 0.00 0.00 0.00 0.00
September 0.327534E+10 0.139892E+11 0.310094E+09 0.00 0.00 0.00 0.00 0.00
October 0.215670E+10 0.180820E+10 0.100663E+10 0.00 0.00 0.00 0.00 0.00
November 0.148443E+10 0.366284E+09 0.495082E+10 0.00 0.00 0.00 0.00 0.00
December 0.136608E+10 0.00 0.104269E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.299519E+11 0.108859E+12 0.459099E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128243E+10 0.00 88421131.61 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.491926E+10 0.380933E+11 0.155596E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138850E+10 0.00 0.144243E+11 0.00 0.00 0.00 0.00 0.00
February 0.124087E+10 0.210345E+09 0.709324E+10 0.00 0.00 0.00 0.00 0.00
March 0.151928E+10 0.322623E+09 0.188948E+10 0.00 0.00 0.00 0.00 0.00
April 0.173607E+10 0.350365E+10 0.489501E+09 0.00 0.00 0.00 0.00 0.00
May 0.233819E+10 0.734009E+10 30172072.11 0.00 0.00 0.00 0.00 0.00
June 0.284381E+10 0.134516E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.353208E+10 0.253931E+11 301945.07 0.00 0.00 0.00 0.00 0.00
August 0.403351E+10 0.334197E+11 767349.76 0.00 0.00 0.00 0.00 0.00
September 0.261438E+10 0.124764E+11 646717.99 0.00 0.00 0.00 0.00 0.00
October 0.167497E+10 0.161693E+10 0.371022E+09 0.00 0.00 0.00 0.00 0.00
November 0.128630E+10 0.383128E+09 0.474519E+10 0.00 0.00 0.00 0.00 0.00
December 0.131602E+10 43020.58 0.103552E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.255240E+11 0.981177E+11 0.393999E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124087E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.403351E+10 0.334197E+11 0.144243E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.154405E+10 306623.24 0.218770E+11 0.00 0.00 0.00 0.00 0.00
February 0.130861E+10 0.215832E+09 0.122293E+11 0.00 0.00 0.00 0.00 0.00
March 0.151616E+10 0.329246E+09 0.471250E+10 0.00 0.00 0.00 0.00 0.00
April 0.165988E+10 0.375525E+10 0.143160E+10 0.00 0.00 0.00 0.00 0.00
May 0.215759E+10 0.765878E+10 0.193440E+09 0.00 0.00 0.00 0.00 0.00
June 0.259346E+10 0.140954E+11 2572500.20 0.00 0.00 0.00 0.00 0.00
July 0.323365E+10 0.268474E+11 310478.86 0.00 0.00 0.00 0.00 0.00
August 0.363708E+10 0.350887E+11 788566.15 0.00 0.00 0.00 0.00 0.00
September 0.230392E+10 0.125461E+11 71821704.24 0.00 0.00 0.00 0.00 0.00
October 0.154344E+10 0.147745E+10 0.174203E+10 0.00 0.00 0.00 0.00 0.00
November 0.131197E+10 0.394950E+09 0.933338E+10 0.00 0.00 0.00 0.00 0.00
December 0.138885E+10 35537.80 0.177114E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.241987E+11 0.102409E+12 0.693062E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130861E+10 35537.80 310478.86 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.363708E+10 0.350887E+11 0.218770E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.140188E+10 0.155596E+11 0.00 0.00 752627.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128243E+10 0.812192E+10 0.00 0.00 52919225.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.175009E+10 0.306606E+10 0.00 0.00 82529779.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.202618E+10 0.126538E+10 0.00 0.00 0.816437E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.274398E+10 0.674940E+09 0.00 0.00 0.176350E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.335534E+10 0.347789E+09 0.00 0.00 0.334714E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.419019E+10 88421131.61 0.00 0.00 0.632488E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.491926E+10 91284135.44 0.00 0.00 0.860712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.327534E+10 0.310094E+09 0.00 0.00 0.314005E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.215670E+10 0.100663E+10 0.00 0.00 0.430126E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148443E+10 0.495082E+10 0.00 0.00 86568535.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.136608E+10 0.104269E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.299519E+11 0.459099E+11 0.00 0.00 0.246520E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128243E+10 88421131.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.491926E+10 0.155596E+11 0.00 0.00 0.860712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138850E+10 0.144243E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124087E+10 0.709324E+10 0.00 0.00 52355320.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151928E+10 0.188948E+10 0.00 0.00 82059170.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.173607E+10 0.489501E+09 0.00 0.00 0.809283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.233819E+10 30172072.11 0.00 0.00 0.168028E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.284381E+10 0.00 0.00 0.00 0.308035E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.353208E+10 301945.07 0.00 0.00 0.571642E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.403351E+10 767349.76 0.00 0.00 0.758227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.261438E+10 646717.99 0.00 0.00 0.281100E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167497E+10 0.371022E+09 0.00 0.00 0.385239E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.128630E+10 0.474519E+10 0.00 0.00 89209910.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131602E+10 0.103552E+11 0.00 0.00 11655.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.255240E+11 0.393999E+11 0.00 0.00 0.222885E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124087E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.403351E+10 0.144243E+11 0.00 0.00 0.758227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.154405E+10 0.218770E+11 0.00 0.00 83162.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130861E+10 0.122293E+11 0.00 0.00 54103964.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151616E+10 0.471250E+10 0.00 0.00 84226408.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.165988E+10 0.143160E+10 0.00 0.00 0.869864E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.215759E+10 0.193440E+09 0.00 0.00 0.175919E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.259346E+10 2572500.20 0.00 0.00 0.324221E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.323365E+10 310478.86 0.00 0.00 0.607053E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.363708E+10 788566.15 0.00 0.00 0.800970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.230392E+10 71821704.24 0.00 0.00 0.284486E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.154344E+10 0.174203E+10 0.00 0.00 0.357023E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131197E+10 0.933338E+10 0.00 0.00 92838638.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138885E+10 0.177114E+11 0.00 0.00 9641.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.241987E+11 0.693062E+11 0.00 0.00 0.233847E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130861E+10 310478.86 0.00 0.00 9641.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.363708E+10 0.218770E+11 0.00 0.00 0.800970E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.783238E+10 0.00 0.00 6136908.48 0.00 0.216497E+09 0.476535E+10 0.00 0.29
February 0.431826E+10 0.00 0.00 13811012.79 0.00 0.00 0.852667E+10 0.00 0.36
March 0.138664E+10 0.00 0.00 30350895.51 0.00 0.00 0.164354E+11 0.00 0.50
April 0.786118E+09 10026514.59 0.00 35067573.36 0.00 0.00 0.176646E+11 0.00 0.64
May 0.930341E+09 7959366.88 0.00 43656496.81 0.00 0.00 0.217186E+11 0.00 0.95
June 0.652225E+09 9691042.89 0.00 45965460.58 1717434.68 0.00 0.207027E+11 0.00 1.14
July 0.614669E+09 0.135134E+09 0.00 42129447.86 12295558.73 0.00 0.150062E+11 0.00 1.09
August 0.445846E+09 0.390215E+09 0.00 41673229.60 14930256.71 0.00 0.131454E+11 0.00 1.07
September 0.757857E+09 7679496.62 0.00 43285947.41 0.00 0.00 0.189699E+11 0.00 1.05
October 0.759733E+09 0.00 0.00 35675171.67 0.00 0.00 0.195577E+11 0.00 0.70
November 0.278769E+10 0.00 0.00 20676865.88 0.00 0.00 0.120863E+11 0.00 0.42
December 0.581612E+10 0.00 0.00 12194316.14 0.00 0.00 0.751163E+10 0.00 0.31
                   
Annual Sum or Average 0.270879E+11 0.560705E+09 0.00 0.370623E+09 28943250.11 0.216497E+09 0.176090E+12 0.00 0.71
Minimum of Months 0.445846E+09 0.00 0.00 6136908.48 0.00 0.00 0.476535E+10 0.00 0.29
Maximum of Months 0.783238E+10 0.390215E+09 0.00 45965460.58 14930256.71 0.216497E+09 0.217186E+11 0.00 1.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112428E+11 0.00 0.00 0.00 0.00 0.512330E+09 0.00 0.00 0.28
February 0.100646E+11 0.00 0.00 249875.58 0.00 57011616.27 0.585083E+09 0.00 0.31
March 0.892568E+10 0.00 0.00 3030680.43 0.00 3205007.19 0.361100E+10 0.00 0.36
April 0.545944E+10 4813818.14 0.00 10073628.23 5489656.79 0.00 0.676329E+10 0.00 0.43
May 0.342435E+10 5915853.49 0.00 20491021.28 0.00 0.00 0.114817E+11 0.00 0.63
June 0.184224E+10 5584015.70 0.00 25228057.86 1860008.12 0.00 0.125201E+11 0.00 0.78
July 0.138630E+10 93299430.48 0.00 24412579.11 10096857.32 0.00 0.914075E+10 0.00 0.75
August 0.109399E+10 0.284057E+09 0.00 23980490.99 11767126.80 0.00 0.800430E+10 0.00 0.73
September 0.271895E+10 149757.52 0.00 20399936.99 5494109.56 0.00 0.968944E+10 0.00 0.68
October 0.590679E+10 0.00 0.00 9197057.45 0.00 0.00 0.678806E+10 0.00 0.45
November 0.945847E+10 0.00 0.00 1198179.95 0.00 7131877.95 0.151608E+10 0.00 0.32
December 0.111736E+11 0.00 0.00 21274.97 0.00 0.112862E+09 0.153525E+09 0.00 0.27
                   
Annual Sum or Average 0.726973E+11 0.393819E+09 0.00 0.138283E+09 34707758.59 0.692540E+09 0.702534E+11 0.00 0.50
Minimum of Months 0.109399E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.112428E+11 0.284057E+09 0.00 25228057.86 11767126.80 0.512330E+09 0.125201E+11 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.945332E+10 0.00 0.00 0.00 0.00 0.159052E+10 0.00 0.00 0.27
February 0.931075E+10 0.00 0.00 47679.65 0.00 0.628307E+09 0.144068E+09 0.00 0.30
March 0.105219E+11 0.00 0.00 797922.39 0.00 74263281.21 0.138311E+10 0.00 0.36
April 0.701664E+10 891622.67 0.00 5987295.71 262772.28 5501645.60 0.470250E+10 0.00 0.42
May 0.466089E+10 2158128.96 0.00 16151319.30 0.00 0.00 0.964164E+10 0.00 0.61
June 0.303869E+10 1812764.12 0.00 21233087.59 1235365.57 0.00 0.109586E+11 0.00 0.76
July 0.223058E+10 76659942.58 0.00 20622244.14 14087425.87 0.00 0.806275E+10 0.00 0.76
August 0.184524E+10 0.217537E+09 0.00 19841290.32 26093016.45 0.00 0.642057E+10 0.00 0.72
September 0.432947E+10 0.00 0.00 13651410.77 2029895.89 0.00 0.687234E+10 0.00 0.64
October 0.797210E+10 0.00 0.00 3766236.95 0.00 11176185.33 0.334571E+10 0.00 0.42
November 0.971856E+10 0.00 0.00 10337.27 0.00 0.281641E+09 67495796.14 0.00 0.31
December 0.949580E+10 0.00 0.00 0.00 0.00 0.108334E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.795940E+11 0.299060E+09 0.00 0.102109E+09 43708476.05 0.367475E+10 0.515988E+11 0.00 0.49
Minimum of Months 0.184524E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.105219E+11 0.217537E+09 0.00 21233087.59 26093016.45 0.159052E+10 0.109586E+11 0.00 0.76



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.613854E+09 0.00 0.00 0.00 0.00 0.175876E+10 0.00 0.00 0.27
February 0.101965E+10 0.00 0.00 0.00 0.00 0.112799E+10 0.00 0.00 0.31
March 0.216263E+10 0.00 0.00 1030.12 0.00 0.356050E+09 9307991.31 0.00 0.35
April 0.174998E+10 242758.65 0.00 873557.10 55303.95 97146439.70 0.586898E+09 0.00 0.42
May 0.129104E+10 784406.52 0.00 3323394.27 0.00 6409447.19 0.183075E+10 0.00 0.65
June 0.786760E+09 537227.04 0.00 4972668.60 259999.25 0.00 0.234369E+10 0.00 0.85
July 0.547103E+09 23222937.25 0.00 5157859.57 2964887.69 0.00 0.186434E+10 0.00 0.89
August 0.532437E+09 64023874.49 0.00 4350363.40 5491625.23 0.00 0.127128E+10 0.00 0.79
September 0.127766E+10 427218.81 0.00 2267555.60 0.00 2911650.36 0.103491E+10 0.00 0.64
October 0.194495E+10 0.00 0.00 268653.55 0.00 0.131668E+09 0.246441E+09 0.00 0.40
November 0.126819E+10 0.00 0.00 0.00 0.00 0.865409E+09 0.00 0.00 0.31
December 0.707620E+09 0.00 0.00 0.00 0.00 0.155141E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.139019E+11 89238422.76 0.00 21215082.20 8771816.13 0.589776E+10 0.918761E+10 0.00 0.52
Minimum of Months 0.532437E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.216263E+10 64023874.49 0.00 5157859.57 5491625.23 0.175876E+10 0.234369E+10 0.00 0.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.766436E+09 0.00 0.00 0.00 0.00 0.151470E+10 0.00 0.00 0.42
February 0.113470E+10 0.00 0.00 0.00 0.00 0.935029E+09 0.00 0.00 0.47
March 0.199274E+10 0.00 0.00 268402.60 0.00 0.259385E+09 0.213310E+09 0.00 0.55
April 0.126379E+10 212492.18 0.00 2224641.27 53550.54 53917090.89 0.133589E+10 0.00 0.73
May 0.114639E+10 714910.67 0.00 3992239.65 0.00 7777213.30 0.214448E+10 0.00 1.08
June 0.684525E+09 374159.94 0.00 6024810.53 251755.99 0.00 0.293231E+10 0.00 1.48
July 0.515059E+09 18784980.50 0.00 6154386.82 2828472.62 0.00 0.209414E+10 0.00 1.47
August 0.423410E+09 56912017.12 0.00 6008906.69 3599177.77 0.00 0.160556E+10 0.00 1.43
September 0.114871E+10 485604.14 0.00 3445296.49 0.00 2164091.67 0.146471E+10 0.00 1.14
October 0.163072E+10 0.00 0.00 795589.88 0.00 0.114921E+09 0.617600E+09 0.00 0.65
November 0.131475E+10 0.00 0.00 0.00 0.00 0.746788E+09 0.00 0.00 0.47
December 0.846713E+09 0.00 0.00 0.00 0.00 0.133354E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.128679E+11 77484164.54 0.00 28914273.93 6732956.92 0.496822E+10 0.124080E+11 0.00 0.86
Minimum of Months 0.423410E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.199274E+10 56912017.12 0.00 6154386.82 3599177.77 0.151470E+10 0.293231E+10 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150241E+10 0.00 0.00 287581.84 0.00 0.179349E+10 0.153450E+09 0.00 0.40
February 0.162588E+10 0.00 0.00 1706151.44 0.00 0.991164E+09 0.835761E+09 0.00 0.50
March 0.219145E+10 0.00 0.00 3847862.87 0.00 0.369963E+09 0.213885E+10 0.00 0.67
April 0.176686E+10 829417.84 0.00 5139224.06 0.00 0.133667E+09 0.278809E+10 0.00 0.85
May 0.175688E+10 1478291.25 0.00 6747665.84 0.00 12120911.55 0.348732E+10 0.00 1.10
June 0.134424E+10 679621.88 0.00 7148141.31 376872.25 0.00 0.332382E+10 0.00 1.27
July 0.928770E+09 42364020.48 0.00 7693626.37 1190894.92 0.00 0.269690E+10 0.00 1.37
August 0.829829E+09 0.130534E+09 0.00 7423798.01 2101688.16 0.00 0.197451E+10 0.00 1.31
September 0.154191E+10 2432663.00 0.00 8414346.99 0.00 5150331.74 0.323279E+10 0.00 1.46
October 0.196561E+10 0.00 0.00 4553000.22 0.00 0.144261E+09 0.275477E+10 0.00 0.88
November 0.193437E+10 0.00 0.00 871828.27 0.00 0.929150E+09 0.354635E+09 0.00 0.49
December 0.138875E+10 0.00 0.00 889632.35 0.00 0.157454E+10 0.431801E+09 0.00 0.41
                   
Annual Sum or Average 0.187770E+11 0.178318E+09 0.00 54722859.57 3669455.34 0.595351E+10 0.241727E+11 0.00 0.89
Minimum of Months 0.829829E+09 0.00 0.00 287581.84 0.00 0.00 0.153450E+09 0.00 0.40
Maximum of Months 0.219145E+10 0.130534E+09 0.00 8414346.99 2101688.16 0.179349E+10 0.348732E+10 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.752713E+09 0.00 0.00 0.00 0.00 0.173480E+10 0.00 0.00 0.45
February 0.113130E+10 0.00 0.00 84094.65 0.00 0.106535E+10 67871661.85 0.00 0.51
March 0.198763E+10 0.00 0.00 600834.54 0.00 0.376851E+09 0.425969E+09 0.00 0.62
April 0.169639E+10 433290.82 0.00 1977718.52 0.00 0.111668E+09 0.107895E+10 0.00 0.81
May 0.146002E+10 623216.45 0.00 4732518.37 0.00 9496543.16 0.204628E+10 0.00 1.21
June 0.108256E+10 1316098.75 0.00 4942950.56 274953.38 0.00 0.206847E+10 0.00 1.43
July 0.686963E+09 40957209.94 0.00 6490999.45 1486802.40 0.00 0.186824E+10 0.00 1.62
August 0.669858E+09 84345343.80 0.00 4709249.78 4533836.93 0.00 0.115138E+10 0.00 1.30
September 0.141343E+10 766475.77 0.00 3511721.74 0.00 5466965.48 0.129218E+10 0.00 1.26
October 0.192587E+10 0.00 0.00 817785.46 0.00 0.151281E+09 0.546296E+09 0.00 0.73
November 0.136277E+10 0.00 0.00 24113.46 0.00 0.885402E+09 2476314.13 0.00 0.52
December 0.848292E+09 0.00 0.00 0.00 0.00 0.152976E+10 0.00 0.00 0.45
                   
Annual Sum or Average 0.150178E+11 0.128442E+09 0.00 27891986.54 6295592.71 0.587007E+10 0.105481E+11 0.00 0.91
Minimum of Months 0.669858E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.198763E+10 84345343.80 0.00 6490999.45 4533836.93 0.173480E+10 0.206847E+10 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.925782E+09 0.00 0.00 0.00 0.00 0.170687E+10 0.00 0.00 0.28
February 0.144624E+10 0.00 0.00 0.00 0.00 0.942306E+09 0.00 0.00 0.31
March 0.258012E+10 0.00 0.00 0.00 0.00 0.157408E+09 0.00 0.00 0.36
April 0.229307E+10 850294.03 0.00 161907.30 659968.44 26207401.49 0.124142E+09 0.00 0.40
May 0.159397E+10 1245882.91 0.00 1815109.47 0.00 0.00 0.111822E+10 0.00 0.55
June 0.842323E+09 1458247.48 0.00 3655674.18 361315.66 0.00 0.177864E+10 0.00 0.70
July 0.500584E+09 23577035.07 0.00 4266531.00 2586752.22 0.00 0.155650E+10 0.00 0.73
August 0.526984E+09 69503521.84 0.00 3681374.86 3141042.67 0.00 0.119042E+10 0.00 0.68
September 0.131829E+10 598286.11 0.00 2029956.14 520224.41 0.00 0.100139E+10 0.00 0.60
October 0.231351E+10 0.00 0.00 283421.08 0.00 3300364.69 0.285245E+09 0.00 0.42
November 0.209282E+10 0.00 0.00 0.00 0.00 0.346232E+09 0.00 0.00 0.32
December 0.134324E+10 0.00 0.00 0.00 0.00 0.120910E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.177769E+11 97233267.44 0.00 15893974.04 7269303.41 0.439143E+10 0.705455E+10 0.00 0.47
Minimum of Months 0.500584E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.258012E+10 69503521.84 0.00 4266531.00 3141042.67 0.170687E+10 0.177864E+10 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.883981E+09 0.00 0.00 0.00 0.00 0.127230E+10 0.00 0.00 0.36
February 0.136990E+10 0.00 0.00 0.00 0.00 0.578491E+09 0.00 0.00 0.40
March 0.203047E+10 0.00 0.00 155612.54 0.00 68178223.65 0.137602E+09 0.00 0.47
April 0.123659E+10 1120125.43 0.00 1714162.27 537607.15 9860464.31 0.100815E+10 0.00 0.60
May 0.980684E+09 1426998.06 0.00 3224445.22 0.00 0.00 0.169073E+10 0.00 0.88
June 0.469206E+09 1289649.40 0.00 5517175.22 294326.02 0.00 0.253453E+10 0.00 1.26
July 0.333927E+09 25491559.54 0.00 5536289.93 2071998.37 0.00 0.186740E+10 0.00 1.24
August 0.283932E+09 74435176.65 0.00 5650438.31 1568025.29 0.00 0.162080E+10 0.00 1.25
September 0.867882E+09 1156036.47 0.00 3632510.86 0.00 0.00 0.154943E+10 0.00 1.03
October 0.154475E+10 0.00 0.00 1096352.35 0.00 2041756.18 0.759860E+09 0.00 0.60
November 0.172344E+10 0.00 0.00 0.00 0.00 0.266377E+09 0.00 0.00 0.42
December 0.117535E+10 0.00 0.00 0.00 0.00 0.912201E+09 0.00 0.00 0.36
                   
Annual Sum or Average 0.129001E+11 0.104920E+09 0.00 26526986.70 4471956.83 0.310945E+10 0.111685E+11 0.00 0.74
Minimum of Months 0.283932E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.203047E+10 74435176.65 0.00 5650438.31 2071998.37 0.127230E+10 0.253453E+10 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.789032E+09 0.00 0.00 4953.98 0.00 0.331744E+10 12560784.49 0.00 0.44
February 0.141567E+10 0.00 0.00 239794.16 0.00 0.199464E+10 0.173986E+09 0.00 0.47
March 0.223202E+10 0.00 0.00 844011.77 0.00 0.122139E+10 0.610098E+09 0.00 0.54
April 0.205190E+10 4567710.68 0.00 1529403.46 0.00 0.675907E+09 0.798796E+09 0.00 0.61
May 0.205258E+10 2760501.53 0.00 2440688.63 0.00 0.438609E+09 0.120742E+10 0.00 0.79
June 0.156063E+10 2232918.33 0.00 3440642.42 437287.45 0.238425E+09 0.141858E+10 0.00 0.90
July 0.862194E+09 49888841.74 0.00 5061859.23 2902836.08 70042862.50 0.160675E+10 0.00 1.00
August 0.827022E+09 0.164820E+09 0.00 5259295.33 2163918.70 61379661.25 0.133010E+10 0.00 1.03
September 0.140345E+10 5049867.81 0.00 6152421.95 0.00 0.202474E+09 0.214482E+10 0.00 1.18
October 0.196940E+10 0.00 0.00 2809807.77 0.00 0.585383E+09 0.176131E+10 0.00 0.74
November 0.182239E+10 0.00 0.00 262748.77 0.00 0.170988E+10 98814102.15 0.00 0.48
December 0.107117E+10 0.00 0.00 193888.09 0.00 0.274845E+10 0.140125E+09 0.00 0.42
                   
Annual Sum or Average 0.180575E+11 0.229320E+09 0.00 28239515.56 5504042.23 0.132640E+11 0.113034E+11 0.00 0.72
Minimum of Months 0.789032E+09 0.00 0.00 4953.98 0.00 61379661.25 12560784.49 0.00 0.42
Maximum of Months 0.223202E+10 0.164820E+09 0.00 6152421.95 2902836.08 0.331744E+10 0.214482E+10 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.906718E+09 0.00 0.00 0.00 0.00 0.147168E+10 0.00 0.00 0.40
February 0.146646E+10 0.00 0.00 35478.27 0.00 0.650599E+09 34280645.76 0.00 0.45
March 0.218045E+10 0.00 0.00 283391.97 0.00 0.129632E+09 0.191363E+09 0.00 0.53
April 0.169005E+10 1677010.85 0.00 1232977.29 240603.84 23047080.98 0.646735E+09 0.00 0.64
May 0.122134E+10 1210750.59 0.00 3486895.84 0.00 0.00 0.154857E+10 0.00 0.96
June 0.747942E+09 3588460.04 0.00 4237855.00 324939.21 0.00 0.178662E+10 0.00 1.17
July 0.372482E+09 42683522.40 0.00 5660920.77 627416.33 0.00 0.176409E+10 0.00 1.34
August 0.392816E+09 95352626.21 0.00 4614682.10 1972936.08 0.00 0.126670E+10 0.00 1.12
September 0.995811E+09 1575915.84 0.00 3511443.46 0.00 0.00 0.138800E+10 0.00 1.09
October 0.189625E+10 0.00 0.00 862950.18 0.00 3610918.27 0.590315E+09 0.00 0.66
November 0.188235E+10 0.00 0.00 17347.51 0.00 0.306237E+09 8337218.34 0.00 0.46
December 0.129772E+10 0.00 0.00 0.00 0.00 0.100598E+10 0.00 0.00 0.39
                   
Annual Sum or Average 0.150504E+11 0.146088E+09 0.00 23943942.40 3165895.46 0.359079E+10 0.922501E+10 0.00 0.77
Minimum of Months 0.372482E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.218045E+10 95352626.21 0.00 5660920.77 1972936.08 0.147168E+10 0.178662E+10 0.00 1.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.105789E+10 0.00 0.00 0.00 0.00 0.143545E+10 0.00 0.00 0.28
February 0.162969E+10 0.00 0.00 0.00 0.00 0.635474E+09 0.00 0.00 0.31
March 0.249871E+10 0.00 0.00 10881.13 0.00 97562565.96 38737065.75 0.00 0.35
April 0.175064E+10 1320131.78 0.00 1105579.59 1156414.42 12841048.22 0.723262E+09 0.00 0.42
May 0.111206E+10 2101362.25 0.00 3945638.22 0.00 0.00 0.203354E+10 0.00 0.66
June 0.602950E+09 1719383.61 0.00 5636322.58 391816.88 0.00 0.252868E+10 0.00 0.86
July 0.436875E+09 28600204.52 0.00 5565678.30 2126936.50 0.00 0.195706E+10 0.00 0.87
August 0.418845E+09 84285051.80 0.00 4826486.50 2478784.30 0.00 0.149349E+10 0.00 0.79
September 0.110261E+10 1194875.55 0.00 2967045.92 0.00 0.00 0.132291E+10 0.00 0.66
October 0.204945E+10 0.00 0.00 531961.81 0.00 17941106.14 0.429370E+09 0.00 0.41
November 0.189652E+10 0.00 0.00 0.00 0.00 0.419573E+09 0.00 0.00 0.32
December 0.130916E+10 0.00 0.00 0.00 0.00 0.111457E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.158654E+11 0.119221E+09 0.00 24589594.05 6153952.10 0.373341E+10 0.105270E+11 0.00 0.52
Minimum of Months 0.418845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.249871E+10 84285051.80 0.00 5636322.58 2478784.30 0.143545E+10 0.252868E+10 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112475E+10 0.00 0.00 0.00 0.00 0.137024E+10 0.00 0.00 0.44
February 0.168201E+10 0.00 0.00 175.02 0.00 0.580220E+09 1261452.70 0.00 0.49
March 0.230774E+10 0.00 0.00 452856.55 0.00 64325603.17 0.318635E+09 0.00 0.57
April 0.137825E+10 1133825.64 0.00 2554737.92 1154963.24 13952509.51 0.143741E+10 0.00 0.75
May 0.112542E+10 1861601.86 0.00 4263980.37 0.00 283551.80 0.219773E+10 0.00 1.09
June 0.613356E+09 1174361.53 0.00 6261792.71 391325.19 0.00 0.297135E+10 0.00 1.46
July 0.491710E+09 23803670.08 0.00 6362722.19 2101321.98 0.00 0.209457E+10 0.00 1.43
August 0.406719E+09 73384316.28 0.00 6169173.29 1275361.09 0.00 0.174894E+10 0.00 1.39
September 0.113139E+10 1286212.32 0.00 3771883.44 0.00 0.00 0.164496E+10 0.00 1.17
October 0.185812E+10 0.00 0.00 1108551.99 0.00 21479200.38 0.769806E+09 0.00 0.69
November 0.188283E+10 0.00 0.00 723.81 0.00 0.429114E+09 4604770.01 0.00 0.50
December 0.131643E+10 0.00 0.00 0.00 0.00 0.111163E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.153187E+11 0.102644E+09 0.00 30946597.28 4922971.51 0.359125E+10 0.131893E+11 0.00 0.87
Minimum of Months 0.406719E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.230774E+10 73384316.28 0.00 6362722.19 2101321.98 0.137024E+10 0.297135E+10 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.193161E+10 0.00 0.00 437191.11 0.00 0.134159E+10 0.260492E+09 0.00 0.39
February 0.205700E+10 0.00 0.00 2206979.91 0.00 0.546577E+09 0.101872E+10 0.00 0.50
March 0.245743E+10 0.00 0.00 4595773.23 0.00 97811886.66 0.233239E+10 0.00 0.68
April 0.177427E+10 7639710.43 0.00 5577200.99 736.32 22184472.70 0.286007E+10 0.00 0.83
May 0.151040E+10 3925467.39 0.00 7353956.50 0.00 0.00 0.353896E+10 0.00 1.10
June 0.107170E+10 2146453.53 0.00 7642420.14 544814.08 0.00 0.335305E+10 0.00 1.24
July 0.777071E+09 49448321.02 0.00 7725206.14 2645226.27 0.00 0.259416E+10 0.00 1.30
August 0.686203E+09 0.164407E+09 0.00 7501289.45 1404497.95 0.00 0.208705E+10 0.00 1.24
September 0.133059E+10 6626661.94 0.00 8972545.42 0.00 0.00 0.334782E+10 0.00 1.45
October 0.205970E+10 0.00 0.00 5499224.47 0.00 15877711.82 0.307690E+10 0.00 0.92
November 0.251829E+10 0.00 0.00 1212069.06 0.00 0.378806E+09 0.520617E+09 0.00 0.49
December 0.196334E+10 0.00 0.00 1275256.76 0.00 0.105595E+10 0.596077E+09 0.00 0.41
                   
Annual Sum or Average 0.201376E+11 0.234194E+09 0.00 59999113.18 4595274.61 0.345879E+10 0.255863E+11 0.00 0.88
Minimum of Months 0.686203E+09 0.00 0.00 437191.11 0.00 0.00 0.260492E+09 0.00 0.39
Maximum of Months 0.251829E+10 0.164407E+09 0.00 8972545.42 2645226.27 0.134159E+10 0.353896E+10 0.00 1.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117324E+10 0.00 0.00 0.00 0.00 0.137331E+10 0.00 0.00 0.45
February 0.165066E+10 0.00 0.00 120434.76 0.00 0.564772E+09 0.104410E+09 0.00 0.50
March 0.223025E+10 0.00 0.00 720024.36 0.00 0.113068E+09 0.479585E+09 0.00 0.61
April 0.170684E+10 3288080.46 0.00 2064384.26 302065.84 25140281.07 0.109532E+10 0.00 0.78
May 0.119392E+10 1782949.19 0.00 5147749.01 0.00 289491.61 0.213192E+10 0.00 1.18
June 0.826448E+09 4223192.00 0.00 5333823.20 399522.63 0.00 0.213246E+10 0.00 1.37
July 0.558129E+09 48552926.87 0.00 6016563.46 422173.69 0.00 0.181259E+10 0.00 1.51
August 0.564095E+09 0.110338E+09 0.00 4843384.68 2062825.82 0.00 0.123494E+10 0.00 1.23
September 0.117253E+10 2149018.94 0.00 3870905.92 0.00 0.00 0.147682E+10 0.00 1.24
October 0.205041E+10 0.00 0.00 1014326.55 0.00 23036030.71 0.641988E+09 0.00 0.73
November 0.190654E+10 0.00 0.00 39297.44 0.00 0.432735E+09 26039912.87 0.00 0.51
December 0.139996E+10 0.00 0.00 1460.38 0.00 0.107345E+10 5194136.42 0.00 0.44
                   
Annual Sum or Average 0.164330E+11 0.170334E+09 0.00 29172354.03 3186587.98 0.360581E+10 0.111412E+11 0.00 0.88
Minimum of Months 0.558129E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.223025E+10 0.110338E+09 0.00 6016563.46 2062825.82 0.137331E+10 0.213246E+10 0.00 1.51



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:09

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.654232E+11 0.928144E+10 0.00 0.150198E+12 0.222671E+11
February 0.126943E+12 0.830500E+10 0.00 0.161759E+12 0.140935E+11
March 0.220763E+12 0.828253E+10 0.00 0.202700E+12 0.644953E+10
April 0.339593E+12 0.717295E+10 0.00 0.228909E+12 0.151107E+11
May 0.442085E+12 0.592469E+10 0.00 0.247055E+12 0.284750E+11
June 0.443787E+12 0.469113E+10 0.00 0.232417E+12 0.521028E+11
July 0.469922E+12 0.340219E+10 0.00 0.230910E+12 0.985801E+11
August 0.370128E+12 0.260712E+10 0.00 0.180465E+12 0.130864E+12
September 0.264891E+12 0.335671E+10 0.00 0.238132E+12 0.480531E+11
October 0.170416E+12 0.653182E+10 0.00 0.234489E+12 0.786047E+10
November 0.731494E+11 0.785003E+10 0.00 0.189893E+12 0.114437E+11
December 0.513424E+11 0.846483E+10 0.00 0.166513E+12 0.178002E+11
           
Annual Sum or Average 0.303844E+13 0.758704E+11 0.00 0.246344E+13 0.453100E+12
Minimum of Months 0.513424E+11 0.260712E+10 0.00 0.150198E+12 0.644953E+10
Maximum of Months 0.469922E+12 0.928144E+10 0.00 0.247055E+12 0.130864E+12