Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:20:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1627.27 | 326.62 | 326.62 |
Net Site Energy | 1627.27 | 326.62 | 326.62 |
Total Source Energy | 5029.04 | 1009.40 | 1009.40 |
Net Source Energy | 5029.04 | 1009.40 | 1009.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 290.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 301.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 132.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 46.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1567.49 | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 290.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 301.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 132.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 46.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 59.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 290.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 301.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 132.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 46.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.23 | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 314.62 | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 70.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.23 | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 314.62 | 12.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1567.487 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1567.487 | 100.00 |
Total On-Site and Utility Electric Sources | 1567.487 | 100.00 |
Total Electricity End Uses | 1567.487 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 95.50 |
Time Setpoint Not Met During Occupied Cooling | 228.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1499.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 8.6994 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 8.6994 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 8.6994 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6994 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 8.6994 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6994 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6994 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6994 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6994 | 18.58 | 8.0700 | |
Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 8.6994 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 8.6994 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-15:09 | 27-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 09-JAN-12:09 |
Heating | 0.00 | 148342.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71789.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35827.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3207.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 179593.23 | 148342.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 148342.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 71789.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 25681.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 35827.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3207.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 64.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 918.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 953.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 159.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 419.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 147.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4964.23 | 64.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 996.40 | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 191.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 996.40 | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.04 | 0.246594 | 0.263000 | 0.799316 | 0.657584 | 0.500000 | 0.001545 | 0.000111 | 0.799316 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.47 | 0.303601 | 0.318000 | 0.784999 | 0.809603 | 0.500000 | 0.001255 | 0.000178 | 0.784999 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.68 | 0.279657 | 0.304000 | 0.814693 | 0.745751 | 0.500000 | 0.001362 | 0.000301 | 1.18 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.878603 | 0.179821 | 0.200000 | 0.175721 | 0.479524 | 0.500000 | 0.002119 | 0.000132 | 0.519723 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.777300 | 0.128678 | 0.200000 | 0.155460 | 0.343143 | 0.500000 | 0.002961 | 0.000086 | 0.339626 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.968702 | 0.163096 | 0.200000 | 0.193740 | 0.434923 | 0.500000 | 0.002336 | 0.000131 | 0.516044 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.887473 | 0.112697 | 0.200000 | 0.177495 | 0.300524 | 0.500000 | 0.003381 | 0.000086 | 0.337442 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.717983 | 0.220049 | 0.235000 | 0.168726 | 0.586798 | 0.500000 | 0.001731 | 0.000094 | 0.371096 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.678365 | 0.147445 | 0.200000 | 0.135673 | 0.393188 | 0.500000 | 0.002584 | 0.000063 | 0.245786 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.800300 | 0.197416 | 0.211000 | 0.168863 | 0.526442 | 0.500000 | 0.001930 | 0.000094 | 0.367688 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.720887 | 0.138739 | 0.200000 | 0.144177 | 0.369971 | 0.500000 | 0.002746 | 0.000062 | 0.243537 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.760079 | 0.207862 | 0.217000 | 0.164937 | 0.554299 | 0.500000 | 0.001833 | 0.000103 | 0.404749 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.746094 | 0.134061 | 0.200000 | 0.149219 | 0.357495 | 0.500000 | 0.002842 | 0.000068 | 0.266447 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.851423 | 0.185562 | 0.200000 | 0.170285 | 0.494832 | 0.500000 | 0.002053 | 0.000102 | 0.401226 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.800797 | 0.124895 | 0.200000 | 0.160159 | 0.333052 | 0.500000 | 0.003051 | 0.000067 | 0.264431 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 12641.41 | 0.000111 | 277.09 |
CORE_MID VAV BOX REHEAT COIL | 20359.90 | 0.000178 | 511.87 |
CORE_TOP VAV BOX REHEAT COIL | 34394.54 | 0.000301 | 907.81 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15109.18 | 0.000132 | 398.44 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9872.91 | 0.000086 | 260.35 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15002.43 | 0.000131 | 395.63 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9809.53 | 0.000086 | 258.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10795.31 | 0.000094 | 284.77 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7149.24 | 0.000063 | 188.58 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10696.42 | 0.000094 | 282.16 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7083.97 | 0.000062 | 186.86 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11772.36 | 0.000103 | 310.52 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7749.08 | 0.000068 | 204.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11670.11 | 0.000102 | 307.82 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7690.58 | 0.000067 | 202.84 |
PACU_VAV_BOT HEATING COIL | 18714.38 | 0.000164 | 317.88 |
PACU_VAV_MID HEATING COIL | 19796.73 | 0.000173 | 332.95 |
PACU_VAV_TOP HEATING COIL | 19700.15 | 0.000172 | 335.29 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.98 | 1.42 | 5.96 | 1.65 | 5.48 | 5.48 | 0.300000 | 0.301619 | 5.48 |
PACU_VAV_MID | 2.81 | 1.43 | 5.63 | 2.00 | 5.06 | 5.06 | 0.300000 | 0.394468 | 5.06 |
PACU_VAV_TOP | 3.10 | 1.52 | 6.19 | 2.89 | 5.94 | 5.94 | 0.300000 | 0.487192 | 5.94 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.48 |
PACU_VAV_MID_OA_CONTROLLER | 5.06 |
PACU_VAV_TOP_OA_CONTROLLER | 5.94 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.48 | 98337.58 | 0.800136 | 1.83 | 32775.91 | 0.800136 |
PACU_VAV_MID COOLING COIL | 5.06 | 92196.78 | 0.800048 | 1.69 | 30729.19 | 0.800048 |
PACU_VAV_TOP COOLING COIL | 5.94 | 105177.70 | 0.800682 | 1.98 | 35055.73 | 0.800682 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.48 |
PACU_VAV_MID FAN | 5.06 |
PACU_VAV_TOP FAN | 5.94 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000164 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000173 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000172 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002187 | 0.262462 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002187 | 658.68 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 250008.24 | 250008.24 | 0.002187 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 98.158 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 8.699 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.769 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8556.149 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8556.149 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1141.898 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.898 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1803.711 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1803.711 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1141.823 | 8.699 | 161.624 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1141.823 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1810E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2249E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7335E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7711E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4183E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4485E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9164E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9329E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1037 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7896E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1159 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2172E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8088E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1296E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2073E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2006E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1807E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2256E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7333E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7719E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4182E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4491E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9162E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9327E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5510E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6366E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1831E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3780E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4682E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2402E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7685E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7749E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2153E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2318E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9310E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9428E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8583E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8624E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4038E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4095E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9414E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9785E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4731E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5024E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1616E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1819E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9162E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9327E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7294E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5521E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1093E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1858E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9345E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1896E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2073E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2006E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9415E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9786E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4732E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5024E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1615E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1814E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9164E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9329E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4424E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5856E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0508E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3158E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3683E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1943E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7686E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7749E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1534E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1948E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8554E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8990E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8016E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8210E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4040E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4097E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1034 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.8936E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1135 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3994E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3138E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0067E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6593E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7065E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4054E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5535E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0577E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3066E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3665E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1799E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6984E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7326E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1296E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0442E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4669E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6115E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2905E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2096E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6593E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7065E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3003E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5056E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9297E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2481E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2697E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1363E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6984E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7326E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1034 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.8929E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1135 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3987E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3132E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0062E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6589E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7063E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4053E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5533E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0576E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3064E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3662E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1796E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6980E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7324E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1296E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0441E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4669E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6114E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2903E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2095E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6589E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7063E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3003E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5054E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9296E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2480E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2694E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1361E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6980E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7324E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 36574.37416 | 36574.37416 | 3.03922 | 3.03922 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5661.52473 | 5661.52473 | 0.27534 | 0.42469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29729.92827 | 29729.92827 | 2.46855 | 2.46855 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 13505.04001 | 13505.04001 | 0.65935 | 0.65935 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31988.79130 | 31988.79130 | 2.67991 | 2.67991 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24083.16917 | 24083.16917 | 1.18083 | 1.18083 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10487.74130 | 10487.74130 | 0.87860 | 0.87860 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10571.70489 | 10571.70489 | 0.51972 | 0.51972 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9278.55668 | 9278.55668 | 0.77730 | 0.77730 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6907.79624 | 6907.79624 | 0.33963 | 0.33963 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11563.25126 | 11563.25126 | 0.96870 | 0.96870 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10497.07918 | 10497.07918 | 0.51604 | 0.51604 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10593.69845 | 10593.69845 | 0.88747 | 0.88747 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6863.48984 | 6863.48984 | 0.33744 | 0.33744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8570.37671 | 8570.37671 | 0.71798 | 0.71798 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7555.48045 | 7555.48045 | 0.37110 | 0.37110 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8097.51803 | 8097.51803 | 0.67837 | 0.67837 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5003.40657 | 5003.40657 | 0.24579 | 0.24579 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9552.97728 | 9552.97728 | 0.80030 | 0.80030 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7486.35234 | 7486.35234 | 0.36769 | 0.36769 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8605.09821 | 8605.09821 | 0.72089 | 0.72089 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 36.45333 | 6.86884E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4957.77993 | 4957.77993 | 0.24354 | 0.24354 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9072.90314 | 9072.90314 | 0.76008 | 0.76008 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8238.84468 | 8238.84468 | 0.40475 | 0.40475 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8906.02576 | 8906.02576 | 0.74609 | 0.74609 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5422.95004 | 5422.95004 | 0.26645 | 0.26645 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 10163.26866 | 10163.26866 | 0.85142 | 0.85142 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8167.37225 | 8167.37225 | 0.40123 | 0.40123 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9559.01034 | 9559.01034 | 0.80080 | 0.80080 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5382.05840 | 5382.05840 | 0.26443 | 0.26443 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 82014.69 | 5.47976 | 5.47976 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 22486.74 | 1.65280 | 1.65280 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 76961.88 | 5.06050 | 5.06050 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 22444.37 | 1.99621 | 1.99621 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 87149.75 | 5.93947 | 5.93947 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 22449.23 | 2.89366 | 2.89366 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.03922 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24659 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79932 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65758 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54505E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10593E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.79932 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12641.40971 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10593E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.08597 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.46855 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30360 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78500 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80960 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25494E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78117E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78500 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20359.90479 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78117E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 511.86929 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.67991 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27966 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81469 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74575 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36239E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.00898E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18083 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34394.54444 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00898E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 907.80998 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87860 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17982 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17572 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47952 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11877E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32182E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51972 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15109.17624 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32182E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 398.44144 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77730 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12868 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15546 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34314 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96087E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.63725E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33963 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9872.90855 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.63725E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.35004 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96870 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16310 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19374 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43492 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33604E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31248E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51604 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15002.42801 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31248E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 395.62873 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88747 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11270 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17749 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30052 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38076E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.58181E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33744 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9809.53107 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.58181E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.68010 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71798 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22005 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16873 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58680 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73143E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.44421E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37110 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10795.30840 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.44421E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.76517 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67837 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14745 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13567 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39319 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58401E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.25447E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24579 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7149.24331 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.25447E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 188.57789 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80030 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19742 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16886 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52644 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92994E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.35769E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36769 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10696.41673 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.35769E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.15942 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72089 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13874 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14418 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36997 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74616E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.19737E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24354 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7083.97295 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.19737E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 186.85804 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76008 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20786 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16494 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55430 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83294E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02990E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40475 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11772.36099 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02990E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 310.51501 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74609 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13406 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14922 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35749 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84200E-003 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.77923E-005 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26645 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
180 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7749.07956 |
181 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.77923E-005 |
182 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 204.38639 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85142 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18556 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17028 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49483 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05322E-003 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02095E-004 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40123 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
194 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11670.11256 |
195 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02095E-004 |
196 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 307.82082 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80080 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12489 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16016 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33305 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05057E-003 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.72806E-005 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26443 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
208 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7690.58116 |
209 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.72806E-005 |
210 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 202.84499 |
211 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97838 |
212 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41676 |
213 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.95676 |
214 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65280 |
215 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.47976 |
216 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.47976 |
217 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
218 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30162 |
219 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81347 |
220 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42960 |
221 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62694 |
222 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99621 |
223 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06050 |
224 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.06050 |
225 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.39447 |
227 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.09599 |
228 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51711 |
229 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.19199 |
230 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.89366 |
231 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.93947 |
232 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.93947 |
233 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.48719 |
235 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.47976 |
236 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.06050 |
237 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.93947 |
238 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.47976 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.47976 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98337.57649 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80014 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.82640 |
243 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32775.91424 |
244 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80014 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 18714.37990 |
246 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63722E-004 |
247 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 317.88379 |
248 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.47976 |
249 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.63722E-004 |
250 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06050 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.06050 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92196.77828 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80005 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68666 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30729.18620 |
256 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80005 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 19796.73228 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73190E-004 |
259 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 332.95358 |
260 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.06050 |
261 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73190E-004 |
262 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.93947 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.93947 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105177.70216 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80068 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.97963 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35055.72813 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80068 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 19700.15155 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72346E-004 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 335.28623 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.93947 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72346E-004 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.18718E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.26246 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.18718E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 658.68292 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 250008.24220 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 250008.24000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.18718E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 11983.55 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 19289.35 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 32600.68 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14318.79 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9356.39 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14217.64 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9296.34 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10231.15 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6775.57 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10137.45 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6713.72 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11156.99 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7343.96 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11060.10 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7288.53 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 15347.09 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 15921.64 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 16218.19 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 97001.78 | 330983.81 | 12.10 | 3.05 | 3.46 | 3.65 | 3.83 | 10.41 | 11.82 | 12.45 | 13.08 | 5.4967 | 4.3635 | 2.9302 | 1.2004 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 91004.00 | 310518.53 | 12.13 | 3.06 | 3.47 | 3.66 | 3.85 | 10.44 | 11.86 | 12.48 | 13.12 | 5.0761 | 4.0355 | 2.7111 | 1.1031 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 103688.24 | 353798.97 | 12.07 | 3.04 | 3.45 | 3.64 | 3.82 | 10.38 | 11.79 | 12.41 | 13.04 | 5.9578 | 4.7255 | 3.1719 | 1.3055 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.4432231122E-002 | 0.1579803038 | Pass | Pass | 9.9505406067E-002 | 0.2976053762 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1202815386E-002 | 7.8144245775E-002 | Pass | Pass | 6.5089209394E-002 | 0.3375230469 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3124631928E-002 | 3.4016132329E-002 | Pass | Pass | 9.8325336511E-002 | 0.3210476737 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.3457389543E-002 | 3.4128354702E-002 | Pass | Pass | 0.9873120260 | 6.0070349714 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.0161537234E-002 | 0.1075203450 | Pass | Pass | 7.7253003700E-002 | 0.2658136572 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.3065351521E-002 | 7.9674789304E-002 | Pass | Pass | 4.8679547434E-002 | 0.2131747672 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6531333805E-002 | 6.0232163068E-002 | Pass | Pass | 4.8639778979E-002 | 0.2121059212 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.4306163155E-002 | 0.1134678282 | Pass | Pass | 4.8714189309E-002 | 0.2146051160 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1568946533 | 0.1644016017 | Pass | Pass | 5.5820886767E-002 | 0.2399024263 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1104508509 | 0.1562337396 | Pass | Pass | 4.6471673896E-002 | 0.2043443141 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.1148378403E-002 | 8.9942872510E-002 | Pass | Pass | 9.9190515474E-002 | 0.2969180801 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.5752971081E-002 | 0.1372821759 | Pass | Pass | 9.9636676120E-002 | 0.2988089881 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1489527971 | 0.2231823315 | Pass | Pass | 0.1044444925 | 0.3073416352 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1023524082 | 0.1623447136 | Pass | Pass | 9.6979049602E-002 | 0.2917297435 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.3871296071E-002 | 7.6908298040E-002 | Pass | Pass | 7.6523977094E-002 | 0.2646946331 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.5853069930E-002 | 0.1431367279 | Pass | Pass | 7.7477477785E-002 | 0.2672118831 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1517037314 | 0.1929836951 | Pass | Pass | 7.9089503447E-002 | 0.2635261473 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1048648818 | 0.1627313075 | Pass | Pass | 7.4712862508E-002 | 0.2572370312 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3272.46 | 29.76 | 0.00 | 1338.13 | 1495.97 | 6136.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_EAST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_WEST_0.25 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_WEST_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 195.79 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.557 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6994 | 983.54 | 8556.15 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 44.78 | 0.0000 | Y | 71.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.11 | 0.0000 | Y | 8.84 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 8.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.01 | 0.0000 | Y | 8.81 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.83 | 0.0000 | Y | 5.54 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.30 | 0.0000 | Y | 8.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.46 | 0.0000 | Y | 5.46 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.11 | 0.0000 | Y | 8.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6994 | 131.26 | 1141.90 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.90 | 0.0000 | Y | 5.55 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6994 | 207.34 | 1803.71 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 8.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6994 | 131.25 | 1141.82 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 5.47 |
Interior Lighting Total | 8.6994 | 4982.19 | 43341.88 | 301.05 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.90 | 437.92 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.90 | 159.29 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1803.71 | 691.72 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1803.71 | 251.62 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.38 | 1141.82 | 437.89 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1141.82 | 159.28 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 46.49 | 41.14 | |
Exterior Lighting Total | 5686.19 | 50.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 250008.24 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98337.58 | 78683.44 | 19654.14 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92196.78 | 73761.88 | 18434.90 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105177.70 | 84213.85 | 20963.86 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 97001.8 | 3.05 | 10.41 | N/A | N/A | 12.10 | |
PACU_VAV_MID COOLING COIL | 91004.0 | 3.06 | 10.44 | N/A | N/A | 12.13 | |
PACU_VAV_TOP COOLING COIL | 103688.2 | 3.04 | 10.38 | N/A | N/A | 12.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 12641.41 | 11983.55 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 20359.90 | 19289.35 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 34394.54 | 32600.68 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15109.18 | 14318.79 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9872.91 | 9356.39 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15002.43 | 14217.64 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9809.53 | 9296.34 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10795.31 | 10231.15 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7149.24 | 6775.57 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10696.42 | 10137.45 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7083.97 | 6713.72 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11772.36 | 11156.99 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7749.08 | 7343.96 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11670.11 | 11060.10 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7690.58 | 7288.53 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 18714.38 | 15347.09 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 19796.73 | 15921.64 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 19700.15 | 16218.19 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.48 | 11917.86 | 2174.89 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.06 | 11006.01 | 2174.89 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.94 | 12917.69 | 2174.89 | 1.00 | 1.13 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002187 | 658.68 | 301156.09 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97001.78 | 3.05 | 10.41 | 12.10 | 5.4967 | 3.46 | 11.82 | 4.3635 | 3.65 | 12.45 | 2.9302 | 3.83 | 13.08 | 1.2004 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91004.00 | 3.06 | 10.44 | 12.13 | 5.0761 | 3.47 | 11.86 | 4.0355 | 3.66 | 12.48 | 2.7111 | 3.85 | 13.12 | 1.1031 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 103688.24 | 3.04 | 10.38 | 12.07 | 5.9578 | 3.45 | 11.79 | 4.7255 | 3.64 | 12.41 | 3.1719 | 3.82 | 13.04 | 1.3055 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 36574.37 | 36574.37 | 37.19 | 3.039 | 3.039 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_MID | 29729.93 | 29729.93 | 30.23 | 2.469 | 2.469 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_TOP | 31988.79 | 31988.79 | 32.52 | 2.680 | 2.680 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00887 | 37.84 | 0.00687 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10487.74 | 10487.74 | 50.58 | 0.879 | 0.879 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00871 | 37.84 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9278.56 | 9278.56 | 70.69 | 0.777 | 0.777 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00865 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11563.25 | 11563.25 | 55.77 | 0.969 | 0.969 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00869 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10593.70 | 10593.70 | 80.71 | 0.887 | 0.887 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00863 | 36.63 | 0.00687 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8570.38 | 8570.38 | 41.34 | 0.718 | 0.718 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8097.52 | 8097.52 | 61.69 | 0.678 | 0.678 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00869 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9552.98 | 9552.98 | 46.07 | 0.800 | 0.800 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00875 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8605.10 | 8605.10 | 65.56 | 0.721 | 0.721 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00867 | 36.45 | 0.00687 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9072.90 | 9072.90 | 43.76 | 0.760 | 0.760 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00875 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8906.03 | 8906.03 | 67.85 | 0.746 | 0.746 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00866 | 32.79 | 0.00686 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10163.27 | 10163.27 | 49.02 | 0.851 | 0.851 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00873 | 37.88 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9559.01 | 9559.01 | 72.83 | 0.801 | 0.801 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00865 | 36.63 | 0.00687 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5661.52 | 5661.52 | 5.76 | 0.275 | 0.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_MID | 13505.04 | 13505.04 | 13.73 | 0.659 | 0.659 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_TOP | 24083.17 | 24083.17 | 24.49 | 1.181 | 1.181 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10571.70 | 10571.70 | 50.99 | 0.520 | 0.520 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6907.80 | 6907.80 | 52.63 | 0.340 | 0.340 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10497.08 | 10497.08 | 50.63 | 0.516 | 0.516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6863.49 | 6863.49 | 52.29 | 0.337 | 0.337 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7555.48 | 7555.48 | 36.44 | 0.371 | 0.371 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5003.41 | 5003.41 | 38.12 | 0.246 | 0.246 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7486.35 | 7486.35 | 36.11 | 0.368 | 0.368 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4957.78 | 4957.78 | 37.77 | 0.244 | 0.244 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8238.84 | 8238.84 | 39.74 | 0.405 | 0.405 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5422.95 | 5422.95 | 41.31 | 0.266 | 0.266 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8167.37 | 8167.37 | 39.39 | 0.401 | 0.401 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5382.06 | 5382.06 | 41.01 | 0.264 | 0.264 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.48 | 5.48 | 1.65 | 1.65 | 5.4798 | 1.6528 | 5.4798 | 0.3016 | 0.3000 |
PACU_VAV_MID | 5.06 | 5.06 | 2.00 | 2.00 | 5.0605 | 1.9962 | 5.0605 | 0.3945 | 0.3000 |
PACU_VAV_TOP | 5.94 | 5.94 | 2.89 | 2.89 | 5.9395 | 2.8937 | 5.9395 | 0.4872 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 12641.410 | 12641.410 | 0.799316 | 0.00011059 | 277.086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12641.41 | 12641.41 | 0.799316 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 5661.52 | 0.00 | 12685.17 | 12685.17 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20359.905 | 20359.905 | 0.784999 | 0.00017812 | 511.869 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20359.90 | 20359.90 | 0.784999 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 13505.04 | 0.00 | 20423.18 | 20423.18 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 34394.544 | 34394.544 | 1.180829 | 0.00030090 | 907.810 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34394.54 | 34394.54 | 1.180829 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 24083.17 | 0.00 | 34512.68 | 34512.68 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15109.176 | 15109.176 | 0.519723 | 0.00013218 | 398.441 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15109.18 | 15109.18 | 0.519723 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791542 | 44.3855 | 10571.70 | 0.00 | 15158.55 | 15158.55 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9872.909 | 9872.909 | 0.339626 | 0.00008637 | 260.350 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9872.91 | 9872.91 | 0.339626 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791423 | 44.3789 | 6907.80 | 0.00 | 9905.12 | 9905.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15002.428 | 15002.428 | 0.516044 | 0.00013125 | 395.629 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15002.43 | 15002.43 | 0.516044 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791469 | 44.3815 | 10497.08 | 0.00 | 15051.47 | 15051.47 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9809.531 | 9809.531 | 0.337442 | 0.00008582 | 258.680 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9809.53 | 9809.53 | 0.337442 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791359 | 44.3754 | 6863.49 | 0.00 | 9841.55 | 9841.55 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10795.308 | 10795.308 | 0.371096 | 0.00009444 | 284.765 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10795.31 | 10795.31 | 0.371096 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790729 | 44.3405 | 7555.48 | 0.00 | 10831.19 | 10831.19 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7149.243 | 7149.243 | 0.245786 | 0.00006254 | 188.578 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7149.24 | 7149.24 | 0.245786 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00791126 | 44.3624 | 5003.41 | 0.00 | 7172.94 | 7172.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10696.417 | 10696.417 | 0.367688 | 0.00009358 | 282.159 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10696.42 | 10696.42 | 0.367688 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790539 | 44.3299 | 7486.35 | 0.00 | 10731.99 | 10731.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7083.973 | 7083.973 | 0.243537 | 0.00006197 | 186.858 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7083.97 | 7083.97 | 0.243537 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790952 | 44.3528 | 4957.78 | 0.00 | 7107.47 | 7107.47 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11772.361 | 11772.361 | 0.404749 | 0.00010299 | 310.515 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11772.36 | 11772.36 | 0.404749 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789225 | 44.2573 | 8238.84 | 0.00 | 11811.32 | 11811.32 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7749.080 | 7749.080 | 0.266447 | 0.00006779 | 204.386 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7749.08 | 7749.08 | 0.266447 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789518 | 44.2736 | 5422.95 | 0.00 | 7774.67 | 7774.67 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11670.113 | 11670.113 | 0.401226 | 0.00010210 | 307.821 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11670.11 | 11670.11 | 0.401226 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789010 | 44.2455 | 8167.37 | 0.00 | 11708.75 | 11708.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7690.581 | 7690.581 | 0.264431 | 0.00006728 | 202.845 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7690.58 | 7690.58 | 0.264431 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789351 | 44.2643 | 5382.06 | 0.00 | 7715.99 | 7715.99 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 98337.576 | 78683.436 | 5.479759 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 92246.29 | 92246.29 | 5.479759 | 27.08 | 15.87 | 0.00838060 | 10.76 | 9.88 | 0.00838060 | 38.10 | 0.00687148 | 18.17 | 21.8106 | 24.00 | 0.00880215 | 41.0767 | 65339.02 | 0.00 | 101399.24 | 74387.33 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 18714.380 | 18714.380 | 1.643928 | 0.00016372 | 317.884 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18714.38 | 18714.38 | 1.643928 | 1.95 | 0.88 | 0.00420978 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 72.7021 | 19.87 | 0.00792353 | 47.6505 | 18245.73 | 0.00 | 18572.99 | 18572.99 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 92196.778 | 73761.876 | 5.060496 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 86485.87 | 86485.87 | 5.060496 | 27.34 | 15.94 | 0.00836078 | 10.76 | 9.86 | 0.00836078 | 38.10 | 0.00687148 | 18.17 | 23.6176 | 24.00 | 0.00882327 | 41.1738 | 60206.89 | 0.00 | 95067.25 | 69743.65 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 19796.732 | 19796.732 | 1.518149 | 0.00017319 | 332.954 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19796.73 | 19796.73 | 1.518149 | 0.37 | -0.46 | 0.00389402 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 78.7255 | 19.93 | 0.00790332 | 47.3436 | 22468.38 | 0.00 | 19266.21 | 19266.21 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 105177.702 | 84213.846 | 5.939474 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 98662.72 | 98662.72 | 5.939474 | 26.85 | 15.80 | 0.00838923 | 10.76 | 9.89 | 0.00838923 | 38.10 | 0.00687148 | 18.17 | 20.1225 | 24.00 | 0.00877390 | 40.9466 | 70554.82 | 0.00 | 108452.33 | 79621.44 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 19700.152 | 19700.152 | 1.781842 | 0.00017235 | 335.286 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19700.15 | 19700.15 | 1.781842 | 2.26 | 1.39 | 0.00446468 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 67.0750 | 17.60 | 0.00781528 | 54.1692 | 25691.58 | 0.00 | 19628.15 | 19628.15 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 12641.410 | 12641.410 | 0.799316 | 0.00011059 | 277.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 4.9566 | 5.056397 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12641.41 | 12641.41 | 1.0000 | 0.83475099 | 0.799316 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11058129 | 60.00 | 32.22 | 27.78 | 0.000 | 12641.41 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.65 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 5661.52 | 0.00 | 12685.17 | 12685.17 | 0.83475099 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.70 | 17.26 | 0.00800000 | 48256.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 20359.905 | 20359.905 | 0.784999 | 0.00017812 | 511.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 7.9830 | 8.143693 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20359.90 | 20359.90 | 1.0000 | 0.81979956 | 0.784999 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.17809916 | 60.00 | 32.22 | 27.78 | 0.000 | 20359.90 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 13505.04 | 0.00 | 20423.18 | 20423.18 | 0.81979956 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.23 | 20.35 | 0.00800000 | 57972.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 34394.544 | 34394.544 | 1.180829 | 0.00030090 | 907.810 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 13.4860 | 13.757364 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34394.54 | 34394.54 | 1.0000 | 1.23317690 | 1.180829 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.30086778 | 60.00 | 32.22 | 27.78 | 0.000 | 34394.54 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 24083.17 | 0.00 | 34512.68 | 34512.68 | 1.23317690 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.25 | 0.00800000 | 61046.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15109.176 | 15109.176 | 0.519723 | 0.00013218 | 398.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 5.9242 | 6.043471 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15109.18 | 15109.18 | 1.0000 | 0.54276305 | 0.519723 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.13216818 | 60.00 | 32.22 | 27.78 | 0.000 | 15109.18 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00791542 | 21.00 | 0.00791542 | 44.3855 | 10571.70 | 0.00 | 15158.55 | 15158.55 | 0.54276305 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9872.909 | 9872.909 | 0.339626 | 0.00008637 | 260.350 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 3.8711 | 3.949033 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9872.91 | 9872.91 | 1.0000 | 0.35468193 | 0.339626 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08636370 | 60.00 | 32.22 | 27.78 | 0.000 | 9872.91 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00791423 | 21.00 | 0.00791423 | 44.3789 | 6907.80 | 0.00 | 9905.12 | 9905.12 | 0.35468193 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15002.428 | 15002.428 | 0.516044 | 0.00013125 | 395.629 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 5.8824 | 6.000773 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15002.43 | 15002.43 | 1.0000 | 0.53892141 | 0.516044 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.13123440 | 60.00 | 32.22 | 27.78 | 0.000 | 15002.43 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00791469 | 21.00 | 0.00791469 | 44.3815 | 10497.08 | 0.00 | 15051.47 | 15051.47 | 0.53892141 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9809.531 | 9809.531 | 0.337442 | 0.00008582 | 258.680 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 3.8463 | 3.923683 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9809.53 | 9809.53 | 1.0000 | 0.35240113 | 0.337442 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08580930 | 60.00 | 32.22 | 27.78 | 0.000 | 9809.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00791359 | 21.00 | 0.00791359 | 44.3754 | 6863.49 | 0.00 | 9841.55 | 9841.55 | 0.35240113 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10795.308 | 10795.308 | 0.371096 | 0.00009444 | 284.765 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 4.2328 | 4.317981 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10795.31 | 10795.31 | 1.0000 | 0.38754707 | 0.371096 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09443243 | 60.00 | 32.22 | 27.78 | 0.000 | 10795.31 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00790729 | 21.00 | 0.00790729 | 44.3405 | 7555.48 | 0.00 | 10831.19 | 10831.19 | 0.38754707 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7149.243 | 7149.243 | 0.245786 | 0.00006254 | 188.578 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 2.8032 | 2.859603 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7149.24 | 7149.24 | 1.0000 | 0.25668214 | 0.245786 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06253832 | 60.00 | 32.22 | 27.78 | 0.000 | 7149.24 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00791126 | 21.00 | 0.00791126 | 44.3624 | 5003.41 | 0.00 | 7172.94 | 7172.94 | 0.25668214 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10696.417 | 10696.417 | 0.367688 | 0.00009358 | 282.159 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 4.1940 | 4.278426 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10696.42 | 10696.42 | 1.0000 | 0.38398834 | 0.367688 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09356737 | 60.00 | 32.22 | 27.78 | 0.000 | 10696.42 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00790539 | 21.00 | 0.00790539 | 44.3299 | 7486.35 | 0.00 | 10731.99 | 10731.99 | 0.38398834 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7083.973 | 7083.973 | 0.243537 | 0.00006197 | 186.858 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 2.7776 | 2.833496 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7083.97 | 7083.97 | 1.0000 | 0.25433334 | 0.243537 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06196736 | 60.00 | 32.22 | 27.78 | 0.000 | 7083.97 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00790952 | 21.00 | 0.00790952 | 44.3528 | 4957.78 | 0.00 | 7107.47 | 7107.47 | 0.25433334 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11772.361 | 11772.361 | 0.404749 | 0.00010299 | 310.515 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 4.6159 | 4.708789 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11772.36 | 11772.36 | 1.0000 | 0.42269260 | 0.404749 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10297924 | 60.00 | 32.22 | 27.78 | 0.000 | 11772.36 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00789225 | 21.00 | 0.00789225 | 44.2573 | 8238.84 | 0.00 | 11811.32 | 11811.32 | 0.42269260 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7749.080 | 7749.080 | 0.266447 | 0.00006779 | 204.386 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 3.0384 | 3.099530 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7749.08 | 7749.08 | 1.0000 | 0.27825868 | 0.266447 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06778541 | 60.00 | 32.22 | 27.78 | 0.000 | 7749.08 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00789518 | 21.00 | 0.00789518 | 44.2736 | 5422.95 | 0.00 | 7774.67 | 7774.67 | 0.27825868 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11670.113 | 11670.113 | 0.401226 | 0.00010210 | 307.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 4.5758 | 4.667891 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11670.11 | 11670.11 | 1.0000 | 0.41901305 | 0.401226 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.10208482 | 60.00 | 32.22 | 27.78 | 0.000 | 11670.11 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00789010 | 21.00 | 0.00789010 | 44.2455 | 8167.37 | 0.00 | 11708.75 | 11708.75 | 0.41901305 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7690.581 | 7690.581 | 0.264431 | 0.00006728 | 202.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 3.0154 | 3.076131 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7690.58 | 7690.58 | 1.0000 | 0.27615353 | 0.264431 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.06727370 | 60.00 | 32.22 | 27.78 | 0.000 | 7690.58 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00789351 | 21.00 | 0.00789351 | 44.2643 | 5382.06 | 0.00 | 7715.99 | 7715.99 | 0.27615353 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.8 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98337.576 | 78683.436 | 5.479759 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4191 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.479759 | 5.72268612 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 92246.29 | 92246.29 | 0.9381 | 5.72268612 | 5.479759 | 27.08 | 15.87 | 0.00838060 | 48590.0 | 10.76 | 9.88 | 0.00838060 | 31938.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11917.864 | 80328.43 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 21.8106 | 24.00 | 0.00880215 | 24.00 | 0.00880215 | 41.0767 | 65339.02 | 0.00 | 101399.24 | 74387.33 | 5.49668328 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.43 | 13.10 | 0.00925791 | 36875.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18714.380 | 18714.380 | 1.643928 | 0.00016372 | 317.884 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.479759 | 5.72268612 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 7.3378 | 7.485505 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18714.38 | 18714.38 | 1.0000 | 1.71680584 | 1.643928 | 1.95 | 0.88 | 0.00420978 | 12505.1 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.16370486 | 60.00 | 32.22 | 27.78 | 0.000 | 18714.38 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 72.7021 | 21.00 | 0.00794207 | 19.87 | 0.00792353 | 47.6505 | 18245.73 | 0.00 | 18572.99 | 18572.99 | 1.71680584 | 2.80 | 2.24 | 0.00420978 | 13363.9 | 13.48 | 7.76 | 0.00420978 | 24182.2 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92196.778 | 73761.876 | 5.060496 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3823 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.060496 | 5.28483626 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 86485.87 | 86485.87 | 0.9381 | 5.28483626 | 5.060496 | 27.34 | 15.94 | 0.00836078 | 48807.2 | 10.76 | 9.86 | 0.00836078 | 31888.1 | -999.0 | -999.00 | -999.00 | -999.00 | 11006.013 | 75479.86 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 23.6176 | 24.00 | 0.00882327 | 24.00 | 0.00882327 | 41.1738 | 60206.89 | 0.00 | 95067.25 | 69743.65 | 5.07612517 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.22 | 12.99 | 0.00922868 | 36594.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 19796.732 | 19796.732 | 1.518149 | 0.00017319 | 332.954 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.060496 | 5.28483626 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 7.7622 | 7.918432 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19796.73 | 19796.73 | 1.0000 | 1.58545088 | 1.518149 | 0.37 | -0.46 | 0.00389402 | 10117.1 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.17317278 | 60.00 | 32.22 | 27.78 | 0.000 | 19796.73 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 78.7255 | 21.00 | 0.00791130 | 19.93 | 0.00790332 | 47.3436 | 22468.38 | 0.00 | 19266.21 | 19266.21 | 1.58545088 | 2.80 | 1.80 | 0.00389402 | 12572.5 | 14.81 | 8.02 | 0.00389402 | 24724.4 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105177.702 | 84213.846 | 5.939474 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4352 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.939474 | 6.20278078 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 98662.72 | 98662.72 | 0.9381 | 6.20278078 | 5.939474 | 26.85 | 15.80 | 0.00838923 | 48379.8 | 10.76 | 9.89 | 0.00838923 | 31960.0 | -999.0 | -999.00 | -999.00 | -999.00 | 12917.692 | 85745.03 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 20.1225 | 24.00 | 0.00877390 | 24.00 | 0.00877390 | 40.9466 | 70554.82 | 0.00 | 108452.33 | 79621.44 | 5.95781782 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.59 | 13.19 | 0.00928733 | 37119.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 19700.152 | 19700.152 | 1.781842 | 0.00017235 | 335.286 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.939474 | 6.20278078 | 4197.9300 | 999.8980 | 2.18695805 | 54.44 | 82.22 | 27.78 | 255039.76 | 7.7243 | 7.879801 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19700.15 | 19700.15 | 1.0000 | 1.86083423 | 1.781842 | 2.26 | 1.39 | 0.00446468 | 13460.1 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 0.17232794 | 60.00 | 32.22 | 27.78 | 0.000 | 19700.15 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 67.0750 | 17.47 | 0.00783887 | 17.60 | 0.00781528 | 54.1692 | 25691.58 | 0.00 | 19628.15 | 19628.15 | 1.86083423 | 2.80 | 2.59 | 0.00446468 | 14002.7 | 13.21 | 7.93 | 0.00446468 | 24550.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.48 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.06 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2578.00 | 1676.00 | 31.33 |
CORE_MID | 2129.33 | 2755.00 | 60.00 |
CORE_TOP | 2292.00 | 3051.67 | 303.50 |
PERIMETER_TOP_ZN_3 | 3115.33 | 3335.83 | 1135.83 |
PERIMETER_TOP_ZN_2 | 3131.17 | 3021.00 | 919.17 |
PERIMETER_TOP_ZN_1 | 3024.50 | 2491.17 | 699.83 |
PERIMETER_TOP_ZN_4 | 3194.00 | 3153.50 | 1082.00 |
PERIMETER_BOT_ZN_3 | 2545.00 | 3252.67 | 564.00 |
PERIMETER_BOT_ZN_2 | 2756.83 | 2815.67 | 387.50 |
PERIMETER_BOT_ZN_1 | 2672.83 | 2461.00 | 353.50 |
PERIMETER_BOT_ZN_4 | 2742.00 | 2869.33 | 423.50 |
PERIMETER_MID_ZN_3 | 2635.33 | 3150.83 | 574.17 |
PERIMETER_MID_ZN_2 | 2435.00 | 2514.00 | 530.00 |
PERIMETER_MID_ZN_1 | 2844.83 | 2170.50 | 369.83 |
PERIMETER_MID_ZN_4 | 2848.00 | 2921.67 | 616.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4312.50 | 3868.33 | 1499.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.17 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.17 |
CORE_TOP | 0.00 | 0.67 | 0.00 | 0.67 |
PERIMETER_TOP_ZN_3 | 2.33 | 18.00 | 1.67 | 12.00 |
PERIMETER_TOP_ZN_2 | 1.33 | 61.00 | 0.50 | 57.00 |
PERIMETER_TOP_ZN_1 | 0.83 | 48.17 | 0.50 | 44.33 |
PERIMETER_TOP_ZN_4 | 0.83 | 50.83 | 0.33 | 31.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 37.50 | 0.00 | 37.17 |
PERIMETER_BOT_ZN_1 | 93.83 | 87.17 | 93.83 | 86.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 40.17 | 0.00 | 25.83 |
PERIMETER_MID_ZN_3 | 0.00 | 2.83 | 0.00 | 2.17 |
PERIMETER_MID_ZN_2 | 0.00 | 47.67 | 0.00 | 47.17 |
PERIMETER_MID_ZN_1 | 0.00 | 40.33 | 0.00 | 39.33 |
PERIMETER_MID_ZN_4 | 0.00 | 45.33 | 0.00 | 29.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 96.33 | 262.67 | 95.50 | 228.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 1.095 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.746 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.723 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.790 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 1.311 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 1.253 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 1.272 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.714 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 1.167 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 1.057 | 0.814 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 1.077 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.781 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 1.233 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 1.256 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 1.223 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.10 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.66 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.95 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.10 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.59 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.66 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.95 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.62 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 17364353.96 | 0.00 | 17364353.96 | 0.00 | 17364353.96 | 13393058.27 | 5271.56 | 97.87 | 3390.57 | 41.78 |
CORE_MID | 11805597.00 | 0.00 | 11805597.00 | 0.00 | 11805597.00 | 13393058.27 | 6072.19 | 27.52 | 2660.29 | 20.42 |
CORE_TOP | 11474049.71 | 0.00 | 11474049.71 | 0.00 | 11474049.71 | 13393058.27 | 6088.16 | 22.61 | 2649.23 | 35.26 |
PERIMETER_TOP_ZN_3 | 2641282.86 | 0.00 | 2641282.86 | 230064.88 | 2871347.74 | 2823374.22 | 4652.32 | 61.57 | 4046.11 | 35.26 |
PERIMETER_TOP_ZN_2 | 2770322.53 | 0.00 | 2770322.53 | 153375.66 | 2923698.19 | 1787429.43 | 4030.71 | 1.39 | 4727.90 | 35.26 |
PERIMETER_TOP_ZN_1 | 4181195.41 | 0.00 | 4181195.41 | 230064.88 | 4411260.29 | 2823374.22 | 4088.20 | 16.60 | 4655.19 | 35.26 |
PERIMETER_TOP_ZN_4 | 2695946.12 | 0.00 | 2695946.12 | 153375.66 | 2849321.78 | 1787312.18 | 4073.73 | 18.40 | 4667.87 | 35.26 |
PERIMETER_BOT_ZN_3 | 2397936.77 | 0.00 | 2397936.77 | 122324.81 | 2520261.57 | 2823374.22 | 5622.59 | 131.20 | 3006.21 | 41.78 |
PERIMETER_BOT_ZN_2 | 2473102.87 | 0.00 | 2473102.87 | 81549.38 | 2554652.25 | 1787429.43 | 4096.68 | 50.50 | 4612.82 | 41.78 |
PERIMETER_BOT_ZN_1 | 3538577.37 | 0.00 | 3538577.37 | 2770602.97 | 6309180.34 | 2823374.22 | 4613.19 | 79.88 | 4066.94 | 41.78 |
PERIMETER_BOT_ZN_4 | 2286725.20 | 0.00 | 2286725.20 | 81549.38 | 2368274.59 | 1787312.18 | 4227.00 | 53.70 | 4479.29 | 41.78 |
PERIMETER_MID_ZN_3 | 2604488.23 | 0.00 | 2604488.23 | 191511.76 | 2795999.99 | 2823374.22 | 4676.70 | 58.61 | 4024.69 | 20.42 |
PERIMETER_MID_ZN_2 | 2755562.32 | 0.00 | 2755562.32 | 127673.74 | 2883236.06 | 1787429.43 | 3997.00 | 6.15 | 4756.85 | 929.42 |
PERIMETER_MID_ZN_1 | 4185326.61 | 0.00 | 4185326.61 | 191511.76 | 4376838.37 | 2823374.22 | 4092.81 | 402.54 | 4264.65 | 20.42 |
PERIMETER_MID_ZN_4 | 2583773.12 | 0.00 | 2583773.12 | 127673.74 | 2711446.86 | 1787312.18 | 4024.36 | 20.16 | 4715.49 | 20.42 |
Total Facility | 75758240.07 | 0.00 | 75758240.07 | 4461278.61 | 80219518.68 | 67843644.98 | 6273.24 | 833.69 | 4883.22 | 971.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.8054 | 0.0000 | 0.8054 | 0.0000 | 0.8054 | 0.4247 | 2496.34 | 97.87 | 3348.79 |
CORE_MID | 0.5489 | 0.0000 | 0.5489 | 0.0000 | 0.5489 | 0.4247 | 3275.61 | 27.52 | 2639.87 |
CORE_TOP | 0.5324 | 0.0000 | 0.5324 | 0.0000 | 0.5324 | 0.4247 | 3297.92 | 22.61 | 2622.46 |
PERIMETER_TOP_ZN_3 | 0.1226 | 0.0000 | 0.1226 | 0.0054 | 0.1281 | 0.0895 | 1862.09 | 61.57 | 4019.35 |
PERIMETER_TOP_ZN_2 | 0.1288 | 0.0000 | 0.1288 | 0.0036 | 0.1324 | 0.0567 | 1240.48 | 1.39 | 4701.13 |
PERIMETER_TOP_ZN_1 | 0.1945 | 0.0000 | 0.1945 | 0.0054 | 0.1999 | 0.0895 | 1297.97 | 16.60 | 4628.43 |
PERIMETER_TOP_ZN_4 | 0.1251 | 0.0000 | 0.1251 | 0.0036 | 0.1287 | 0.0567 | 1283.50 | 18.40 | 4641.10 |
PERIMETER_BOT_ZN_3 | 0.1109 | 0.0000 | 0.1109 | 0.0029 | 0.1138 | 0.0895 | 2847.37 | 131.20 | 2964.43 |
PERIMETER_BOT_ZN_2 | 0.1146 | 0.0000 | 0.1146 | 0.0019 | 0.1166 | 0.0567 | 1321.46 | 50.50 | 4571.04 |
PERIMETER_BOT_ZN_1 | 0.1642 | 0.0000 | 0.1642 | 0.1267 | 0.2908 | 0.0895 | 1837.96 | 79.88 | 4025.16 |
PERIMETER_BOT_ZN_4 | 0.1058 | 0.0000 | 0.1058 | 0.0019 | 0.1077 | 0.0567 | 1451.78 | 53.70 | 4437.52 |
PERIMETER_MID_ZN_3 | 0.1211 | 0.0000 | 0.1211 | 0.0045 | 0.1257 | 0.0895 | 1880.12 | 58.61 | 4004.28 |
PERIMETER_MID_ZN_2 | 0.1211 | 0.0000 | 0.1211 | 0.0032 | 0.1243 | 0.0567 | 1199.75 | 5.98 | 3828.26 |
PERIMETER_MID_ZN_1 | 0.1950 | 0.0000 | 0.1950 | 0.0045 | 0.1995 | 0.0895 | 1296.23 | 402.54 | 4244.24 |
PERIMETER_MID_ZN_4 | 0.1202 | 0.0000 | 0.1202 | 0.0030 | 0.1232 | 0.0567 | 1227.77 | 20.16 | 4695.07 |
Total Facility | 3.5108 | 0.0000 | 3.5108 | 0.1667 | 3.6774 | 2.1513 | 3469.26 | 833.69 | 4828.95 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30603802.43 | 0.00 | 30603802.43 | 22614548.33 | 4014.32 | 3.39 | 4742.29 | 41.78 |
PACU_VAV_MID | 26103923.88 | 0.00 | 26103923.88 | 22614548.33 | 4025.80 | 1.88 | 4732.32 | 20.42 |
PACU_VAV_TOP | 25916389.56 | 0.00 | 25916389.56 | 22614548.33 | 4044.67 | 2.06 | 4713.27 | 35.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4188 | 0.0000 | 1.4188 | 0.7171 | 1239.10 | 3.39 | 4700.51 |
PACU_VAV_MID | 1.2144 | 0.0000 | 1.2144 | 0.7171 | 1229.21 | 1.88 | 4711.91 |
PACU_VAV_TOP | 1.2035 | 0.0000 | 1.2035 | 0.7171 | 1254.44 | 2.06 | 4686.50 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3094.01 | 0.00 | 0.00 | 0.00 | 1730.02 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.08 | 2857.51 | 0.00 | 0.00 | 0.00 | 1964.63 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.50 | 2846.18 | 0.00 | 0.00 | 0.00 | 1984.90 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.2882 | 0.0000 | 0.0000 | 0.0000 | 0.8373 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.9532 | 0.0000 | 0.0000 | 0.0000 | 0.8531 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.9477 | 0.0000 | 0.0000 | 0.0000 | 0.8448 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 982 |
Defaulted Fields | 577 |
Fields with Defaults | 2420 |
Autosized Fields | 193 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
Electricity:Building | 1020.74 | 13472.34 | 02-JUL-17:20 | 74313.01 | 17-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 322.35 | 5243.28 | 01-JAN-00:10 | 20463.73 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1020.74 | 13472.34 | 02-JUL-17:20 | 74313.01 | 17-JAN-16:40 |
InteriorLights:Electricity | 301.05 | 994.59 | 02-JUL-17:20 | 32642.50 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 301.05 | 994.59 | 02-JUL-17:20 | 32642.50 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 301.05 | 994.59 | 02-JUL-17:20 | 32642.50 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 301.05 | 994.59 | 02-JUL-17:20 | 32642.50 | 17-JAN-16:40 |
Electricity:Zone:CORE_MID | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 187.35 | 2043.28 | 01-JAN-00:10 | 13252.30 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 71.93 | 211.73 | 01-JAN-00:10 | 6443.98 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 33.17 | 422.10 | 30-APR-17:10 | 2793.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.84 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.95 | 269.43 | 30-APR-17:10 | 1768.58 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.55 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 32.92 | 422.10 | 21-MAY-17:10 | 2793.68 | 17-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.58 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.58 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.88 | 267.21 | 12-MAR-17:10 | 1768.52 | 17-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.47 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 33.14 | 422.10 | 30-APR-17:10 | 2793.69 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.81 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.94 | 269.43 | 23-APR-17:10 | 1768.58 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.54 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 32.90 | 422.10 | 19-MAR-17:10 | 2793.68 | 17-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.57 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.57 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.86 | 267.21 | 12-MAR-17:10 | 1768.52 | 17-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.46 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 33.17 | 422.10 | 30-APR-17:10 | 2793.69 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 8.84 | 36.00 | 01-JAN-09:20 | 1358.45 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.95 | 269.43 | 30-APR-17:10 | 1768.58 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 5.55 | 22.79 | 01-JAN-08:10 | 860.01 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 32.92 | 422.10 | 21-MAY-17:10 | 2793.68 | 17-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.58 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 8.58 | 36.00 | 01-JAN-08:20 | 1358.45 | 17-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.88 | 267.21 | 12-MAR-17:10 | 1768.52 | 17-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 5.47 | 22.79 | 01-JAN-09:20 | 859.95 | 17-JAN-16:30 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 449.35 | 367.92 | 01-JAN-00:10 | 109026.87 | 20-JUL-15:10 |
ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 03-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.90 | 367.92 | 01-JAN-00:10 | 1410.29 | 03-JAN-08:10 |
ElectricityPurchased:Facility | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
ElectricityPurchased:Plant | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
ElectricityNet:Plant | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
Cogeneration:ElectricityNet | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1567.49 | 13847.95 | 16-JUL-17:30 | 179593.23 | 20-JUL-15:10 |
Fans:Electricity | 132.33 | 0.00 | 01-JAN-00:10 | 35827.23 | 20-JUL-15:00 |
General:Fans:Electricity | 132.33 | 0.00 | 01-JAN-00:10 | 35827.23 | 20-JUL-15:00 |
ExteriorLights:Electricity | 50.37 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.37 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 290.12 | 0.00 | 01-JAN-00:10 | 71789.35 | 20-JUL-15:10 |
General:Cooling:Electricity | 290.12 | 0.00 | 01-JAN-00:10 | 71789.35 | 20-JUL-15:10 |
Electricity:Plant | 47.03 | 0.00 | 01-JAN-00:10 | 6060.97 | 26-DEC-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 46.60 | 0.00 | 01-JAN-00:10 | 5914.70 | 01-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 46.60 | 0.00 | 01-JAN-00:10 | 5914.70 | 01-FEB-13:00 |
Pumps:Electricity | 0.43 | 0.00 | 01-JAN-00:10 | 548.18 | 27-DEC-07:10 |
General:Pumps:Electricity | 0.43 | 0.00 | 01-JAN-00:10 | 548.18 | 27-DEC-07:10 |
WIRED_LTG_ELECTRICITY | 8.46 | 0.00 | 01-JAN-00:10 | 917.25 | 17-JAN-16:50 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 59.78 | 0.00 | 01-JAN-00:10 | 148342.61 | 27-DEC-07:10 |
NaturalGas:Plant | 59.78 | 0.00 | 01-JAN-00:10 | 148342.61 | 27-DEC-07:10 |
Heating:NaturalGas | 59.78 | 0.00 | 01-JAN-00:10 | 148342.61 | 27-DEC-07:10 |
Boiler:Heating:NaturalGas | 59.78 | 0.00 | 01-JAN-00:10 | 148342.61 | 27-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2643.22 | 0.00 | 01-JAN-00:10 | 447791.45 | 20-JUL-15:00 |
EnergyTransfer:Building | 1335.26 | 0.00 | 01-JAN-00:10 | 171002.87 | 03-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 269.75 | 0.00 | 01-JAN-00:10 | 26238.12 | 05-SEP-07:50 |
Heating:EnergyTransfer | 25.03 | 0.00 | 01-JAN-00:10 | 70451.46 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 25.03 | 0.00 | 01-JAN-00:10 | 70451.46 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1310.23 | 0.00 | 01-JAN-00:10 | 171002.87 | 03-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 269.75 | 0.00 | 01-JAN-00:10 | 26238.12 | 05-SEP-07:50 |
General:Cooling:EnergyTransfer | 1310.23 | 0.00 | 01-JAN-00:10 | 171002.87 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 269.75 | 0.00 | 01-JAN-00:10 | 26238.12 | 05-SEP-07:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.45 | 0.00 | 01-JAN-00:10 | 12067.95 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.29 | 0.00 | 01-JAN-00:10 | 9644.40 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.29 | 0.00 | 01-JAN-00:10 | 9644.40 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.16 | 0.00 | 01-JAN-00:10 | 12067.95 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.16 | 0.00 | 01-JAN-00:10 | 12067.95 | 03-JUL-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 30.35 | 0.00 | 01-JAN-00:10 | 5798.32 | 03-JUL-14:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.43 | 0.00 | 01-JAN-00:10 | 2827.88 | 04-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.43 | 0.00 | 01-JAN-00:10 | 2827.88 | 04-DEC-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.93 | 0.00 | 01-JAN-00:10 | 5798.32 | 03-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.93 | 0.00 | 01-JAN-00:10 | 5798.32 | 03-JUL-14:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.42 | 0.00 | 01-JAN-00:10 | 5879.66 | 03-JUL-12:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.36 | 0.00 | 01-JAN-00:10 | 2199.23 | 04-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.36 | 0.00 | 01-JAN-00:10 | 2199.23 | 04-DEC-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.06 | 0.00 | 01-JAN-00:10 | 5879.66 | 03-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.06 | 0.00 | 01-JAN-00:10 | 5879.66 | 03-JUL-12:20 |
EnergyTransfer:Zone:CORE_MID | 181.57 | 0.00 | 01-JAN-00:10 | 19774.85 | 19-JUN-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1292.60 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1292.60 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 181.57 | 0.00 | 01-JAN-00:10 | 19774.85 | 19-JUN-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 181.57 | 0.00 | 01-JAN-00:10 | 19774.85 | 19-JUN-08:00 |
EnergyTransfer:Zone:CORE_TOP | 177.95 | 0.00 | 01-JAN-00:10 | 21769.03 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.48 | 0.00 | 01-JAN-00:10 | 12956.91 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.48 | 0.00 | 01-JAN-00:10 | 12956.91 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 177.47 | 0.00 | 01-JAN-00:10 | 21769.03 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 177.47 | 0.00 | 01-JAN-00:10 | 21769.03 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.51 | 0.00 | 01-JAN-00:10 | 7893.93 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.66 | 0.00 | 01-JAN-00:10 | 6989.55 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.66 | 0.00 | 01-JAN-00:10 | 6989.55 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.85 | 0.00 | 01-JAN-00:10 | 7893.93 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.85 | 0.00 | 01-JAN-00:10 | 7893.93 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.51 | 0.00 | 01-JAN-00:10 | 8349.25 | 03-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.15 | 0.00 | 01-JAN-00:10 | 4713.00 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.15 | 0.00 | 01-JAN-00:10 | 4713.00 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.36 | 0.00 | 01-JAN-00:10 | 8349.25 | 03-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.36 | 0.00 | 01-JAN-00:10 | 8349.25 | 03-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 66.72 | 0.00 | 01-JAN-00:10 | 11725.68 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.36 | 0.00 | 01-JAN-00:10 | 6481.71 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.36 | 0.00 | 01-JAN-00:10 | 6481.71 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.36 | 0.00 | 01-JAN-00:10 | 11725.68 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 65.36 | 0.00 | 01-JAN-00:10 | 11725.68 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.12 | 0.00 | 01-JAN-00:10 | 9364.15 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.53 | 0.00 | 01-JAN-00:10 | 4532.50 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.53 | 0.00 | 01-JAN-00:10 | 4532.50 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.59 | 0.00 | 01-JAN-00:10 | 9364.15 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.59 | 0.00 | 01-JAN-00:10 | 9364.15 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.02 | 0.00 | 01-JAN-00:10 | 6876.51 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.37 | 0.00 | 01-JAN-00:10 | 2867.14 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.37 | 0.00 | 01-JAN-00:10 | 2867.14 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.66 | 0.00 | 01-JAN-00:10 | 6876.51 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.66 | 0.00 | 01-JAN-00:10 | 6876.51 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.15 | 0.00 | 01-JAN-00:10 | 7423.56 | 03-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 1891.93 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 1891.93 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.05 | 0.00 | 01-JAN-00:10 | 7423.56 | 03-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.05 | 0.00 | 01-JAN-00:10 | 7423.56 | 03-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 63.09 | 0.00 | 01-JAN-00:10 | 10996.78 | 03-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.94 | 0.00 | 01-JAN-00:10 | 7049.66 | 27-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.94 | 0.00 | 01-JAN-00:10 | 7049.66 | 27-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 60.15 | 0.00 | 01-JAN-00:10 | 10996.78 | 03-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 60.15 | 0.00 | 01-JAN-00:10 | 10996.78 | 03-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.29 | 0.00 | 01-JAN-00:10 | 7787.08 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.13 | 0.00 | 01-JAN-00:10 | 1879.74 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.13 | 0.00 | 01-JAN-00:10 | 1879.74 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.16 | 0.00 | 01-JAN-00:10 | 7787.08 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 40.16 | 0.00 | 01-JAN-00:10 | 7787.08 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.44 | 0.00 | 01-JAN-00:10 | 7176.97 | 03-JUL-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.50 | 0.00 | 01-JAN-00:10 | 4013.69 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.50 | 0.00 | 01-JAN-00:10 | 4013.69 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.94 | 0.00 | 01-JAN-00:10 | 7176.97 | 03-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.94 | 0.00 | 01-JAN-00:10 | 7176.97 | 03-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.28 | 0.00 | 01-JAN-00:10 | 8065.97 | 30-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.24 | 0.00 | 01-JAN-00:10 | 2763.86 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.24 | 0.00 | 01-JAN-00:10 | 2763.86 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.04 | 0.00 | 01-JAN-00:10 | 8065.97 | 30-MAY-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.04 | 0.00 | 01-JAN-00:10 | 8065.97 | 30-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 66.13 | 0.00 | 01-JAN-00:10 | 10563.93 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.21 | 0.00 | 01-JAN-00:10 | 3835.74 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.21 | 0.00 | 01-JAN-00:10 | 3835.74 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.91 | 0.00 | 01-JAN-00:10 | 10563.93 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.91 | 0.00 | 01-JAN-00:10 | 10563.93 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.51 | 0.00 | 01-JAN-00:10 | 8731.61 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.29 | 0.00 | 01-JAN-00:10 | 2704.22 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.29 | 0.00 | 01-JAN-00:10 | 2704.22 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.22 | 0.00 | 01-JAN-00:10 | 8731.61 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.22 | 0.00 | 01-JAN-00:10 | 8731.61 | 15-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 83.41 | 0.00 | 01-JAN-00:10 | 120251.25 | 27-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 43.85 | 0.00 | 01-JAN-00:10 | 5760.69 | 30-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 43.85 | 0.00 | 01-JAN-00:10 | 5760.69 | 30-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 43.85 | 0.00 | 01-JAN-00:10 | 5760.69 | 30-JAN-12:10 |
EnergyTransfer:HVAC | 1224.87 | 0.00 | 01-JAN-00:10 | 347075.31 | 20-JUL-15:00 |
HeatingCoils:EnergyTransfer | 39.57 | 0.00 | 01-JAN-00:10 | 118375.62 | 27-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 39.57 | 0.00 | 01-JAN-00:10 | 118375.62 | 27-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 39.57 | 0.00 | 01-JAN-00:10 | 118375.62 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 1185.31 | 0.00 | 01-JAN-00:10 | 347075.31 | 20-JUL-15:00 |
EnergyTransfer:Plant | 83.08 | 0.00 | 01-JAN-00:10 | 117960.20 | 27-DEC-07:10 |
WaterSystems:EnergyTransfer | 43.85 | 0.00 | 01-JAN-00:10 | 5760.69 | 30-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 43.85 | 0.00 | 01-JAN-00:10 | 5760.69 | 30-JAN-12:10 |
Boilers:EnergyTransfer | 39.24 | 0.00 | 01-JAN-00:10 | 116084.56 | 27-DEC-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -269.754 | 0.000 | 0.000 | 32.675 | 71.928 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -85.272 |
CORE_MID | 0.000 | 0.000 | 0.002 | -181.569 | 0.000 | 0.000 | 33.131 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -38.918 |
CORE_TOP | 0.000 | 0.000 | 0.477 | -177.470 | 0.000 | 0.000 | 33.757 | 71.928 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -44.118 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.658 | -42.852 | 0.000 | 0.000 | 7.307 | 8.841 | 24.333 | 19.109 | 0.000 | 0.222 | 7.011 | 0.000 | -25.120 | 0.000 | -1.510 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.147 | -43.360 | 0.000 | 0.000 | 4.542 | 5.551 | 15.404 | 38.237 | 0.000 | 0.146 | 0.001 | 0.000 | -15.668 | 0.000 | -1.042 | -4.957 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.365 | -65.357 | 0.000 | 0.000 | 7.075 | 8.585 | 24.332 | 65.313 | 0.000 | 0.218 | 0.000 | 0.000 | -24.114 | 0.000 | -1.645 | -15.771 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.526 | -43.591 | 0.000 | 0.000 | 4.619 | 5.472 | 15.403 | 38.637 | 0.000 | 0.142 | 0.000 | 0.000 | -16.780 | 0.000 | -1.050 | -4.379 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.367 | -39.657 | 0.000 | 0.000 | 7.257 | 8.806 | 24.333 | 19.383 | 0.000 | 0.129 | 6.640 | 0.000 | -26.408 | 0.000 | -0.851 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.103 | -41.049 | 0.000 | 0.000 | 4.484 | 5.536 | 15.404 | 38.327 | 0.000 | 0.080 | 0.000 | 0.000 | -16.900 | 0.000 | -0.604 | -5.381 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.935 | -60.151 | 0.000 | 0.000 | 7.092 | 8.568 | 24.332 | 65.736 | 0.000 | 5.180 | 0.001 | 0.000 | -26.107 | 0.000 | -16.740 | -10.846 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.129 | -40.156 | 0.000 | 0.000 | 4.545 | 5.458 | 15.403 | 38.807 | 0.000 | 0.077 | 0.000 | 0.000 | -18.139 | 0.000 | -0.609 | -5.515 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.502 | -42.937 | 0.000 | 0.000 | 7.206 | 8.841 | 24.333 | 18.955 | 0.000 | 0.190 | 11.173 | 0.000 | -26.904 | 0.000 | -1.358 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.239 | -43.038 | 0.000 | 0.000 | 3.324 | 5.551 | 15.404 | 38.071 | 0.000 | 0.124 | 0.001 | 0.000 | -16.648 | 0.000 | -0.930 | -2.096 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.214 | -65.912 | 0.000 | 0.000 | 6.997 | 8.585 | 24.332 | 65.082 | 0.000 | 0.184 | 0.001 | 0.000 | -25.643 | 0.000 | -1.466 | -12.372 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.293 | -43.220 | 0.000 | 0.000 | 4.557 | 5.472 | 15.403 | 38.544 | 0.000 | 0.119 | 0.000 | 0.000 | -17.899 | 0.000 | -0.940 | -2.330 |
TOPFLOOR_PLENUM | 8.288 | -50.159 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.268 | 43.937 | 0.000 | 0.000 | 0.000 | -2.333 | -0.002 |
MIDFLOOR_PLENUM | 3.425 | -26.929 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.289 | 25.619 | 0.000 | 0.000 | 0.000 | -2.405 | -0.001 |
FIRSTFLOOR_PLENUM | 1.361 | -33.056 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.222 | 33.439 | 0.000 | 0.000 | 0.000 | -1.966 | -0.000 |
Total Facility | 13.075 | -110.144 | 11.958 | -1200.074 | 0.000 | 0.000 | 168.569 | 301.049 | 719.689 | 484.201 | 0.000 | 7.588 | 127.824 | 0.000 | -256.330 | 0.000 | -35.449 | -231.956 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 | -41507.18 | 0.00 | 0.00 | 292.99 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 33592.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -32625.90 | 0.00 | 0.00 | 321.94 | 715.98 | 3025.92 | 0.00 | 0.00 | 0.00 | 28562.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-JUL-04:02 | 0.00 | 0.00 | 0.00 | -34970.98 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 32317.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-16:22 | 0.00 | 0.00 | 0.00 | -12730.47 | 0.00 | 0.00 | 25.76 | 36.00 | 478.42 | 3311.92 | 0.00 | 87.72 | 8790.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 17-SEP-09:42 | 0.00 | 0.00 | 0.00 | -12133.77 | 0.00 | 0.00 | 15.11 | 22.79 | 302.86 | 6338.64 | 0.00 | 0.00 | 5459.65 | 0.00 | -0.00 | 0.00 | -5.28 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:12 | 0.00 | 0.00 | 0.00 | -15933.87 | 0.00 | 0.00 | 22.75 | 36.00 | 478.41 | 11989.03 | 0.00 | 15.40 | 3392.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-APR-16:21 | 0.00 | 0.00 | 0.00 | -14636.58 | 0.00 | 0.00 | 13.30 | 22.79 | 302.86 | 9231.33 | 0.00 | 7.84 | 5058.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 03-JUL-06:03 | 0.00 | 0.00 | 0.00 | -8438.28 | 0.00 | 0.00 | 144.48 | 216.00 | 637.89 | 2162.89 | 0.00 | 5.82 | 5271.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-09:12 | 0.00 | 0.00 | 0.00 | -10775.90 | 0.00 | 0.00 | 15.45 | 22.79 | 302.86 | 6794.37 | 0.00 | 0.00 | 3652.62 | 0.00 | -0.00 | 0.00 | -12.19 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-12:22 | 0.00 | 0.00 | 0.00 | -12683.08 | 0.00 | 0.00 | 24.98 | 36.00 | 478.41 | 11139.87 | 0.00 | 0.00 | 1009.77 | 0.00 | -0.00 | 0.00 | -5.95 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:42 | 0.00 | 0.00 | 0.00 | -11566.86 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 4798.49 | 0.00 | 25.66 | 6475.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:21 | 0.00 | 0.00 | 0.00 | -11183.98 | 0.00 | 0.00 | 0.00 | 39.51 | 386.10 | 3119.34 | 0.00 | 24.76 | 7614.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18-JUN-08:52 | 0.00 | 0.00 | 0.00 | -12137.78 | 0.00 | 0.00 | 14.30 | 22.79 | 302.86 | 7502.66 | 0.00 | 1.62 | 4293.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:22 | 0.00 | 0.00 | 0.00 | -14052.54 | 0.00 | 0.00 | 23.00 | 36.00 | 478.41 | 11849.47 | 0.00 | 0.00 | 1749.68 | 0.00 | -0.00 | 0.00 | -84.01 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 | -13251.97 | 0.00 | 0.00 | 0.00 | 22.79 | 244.42 | 8023.83 | 0.00 | 41.10 | 4919.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:10 | 0.00 | -12068.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.26 | 12038.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-14:50 | 0.00 | -5798.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 | 5776.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-12:08 | 0.00 | -6974.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 6971.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -11442.53 | 0.00 | -188318.00 | 0.00 | 0.00 | 3482.78 | 9050.38 | 22496.85 | 22948.77 | 0.00 | 1985.01 | 139796.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 04-DEC-07:01 | 0.00 | 0.00 | 9048.22 | 0.00 | 0.00 | 0.00 | 889.77 | 2148.02 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15111.92 |
CORE_TOP | 04-DEC-06:02 | 0.00 | 0.00 | 18689.88 | 0.00 | 0.00 | 0.00 | 493.19 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22420.72 |
PERIMETER_TOP_ZN_3 | 04-DEC-05:01 | 0.00 | 0.00 | 8330.51 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2458.16 | 0.00 | -16.90 | -6414.88 |
PERIMETER_TOP_ZN_2 | 04-DEC-05:01 | 0.00 | 0.00 | 6281.96 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1633.06 | 0.00 | -11.28 | -4991.77 |
PERIMETER_TOP_ZN_1 | 04-DEC-05:01 | 0.00 | 0.00 | 8441.10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2505.81 | 0.00 | -17.37 | -6477.36 |
PERIMETER_TOP_ZN_4 | 04-DEC-05:01 | 0.00 | 0.00 | 6499.60 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1662.86 | 0.00 | -11.50 | -5179.38 |
PERIMETER_BOT_ZN_3 | 02-MAR-06:01 | 0.00 | 0.00 | 5169.24 | 0.00 | 0.00 | 0.00 | 100.47 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3305.77 | 0.00 | -26.59 | -2619.88 |
PERIMETER_BOT_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 3830.43 | 0.00 | 0.00 | 0.00 | 63.47 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2228.40 | 0.00 | -20.35 | -2077.22 |
PERIMETER_BOT_ZN_1 | 27-DEC-07:10 | 0.00 | 0.00 | 7524.32 | 0.00 | 0.00 | 0.00 | 193.29 | 452.82 | 637.88 | 0.00 | 0.00 | 0.00 | 9169.43 | 0.00 | -3395.30 | 0.00 | -14582.46 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 3848.30 | 0.00 | 0.00 | 0.00 | 63.39 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2188.47 | 0.00 | -20.38 | -2134.91 |
PERIMETER_MID_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 5959.04 | 0.00 | 0.00 | 0.00 | 104.21 | 44.64 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3156.77 | 0.00 | -45.76 | -3543.24 |
PERIMETER_MID_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 4604.87 | 0.00 | 0.00 | 0.00 | 66.40 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2137.42 | 0.00 | -30.39 | -2935.52 |
PERIMETER_MID_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 6147.30 | 0.00 | 0.00 | 0.00 | 103.82 | 44.64 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3242.32 | 0.00 | -46.00 | -3645.33 |
PERIMETER_MID_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 4655.16 | 0.00 | 0.00 | 0.00 | 66.25 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2096.31 | 0.00 | -30.48 | -3026.68 |
TOPFLOOR_PLENUM | 04-DEC-06:13 | 10992.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -53.89 | -10938.71 |
MIDFLOOR_PLENUM | 08-OCT-15:52 | 4606.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4639.04 |
FIRSTFLOOR_PLENUM | 16-NOV-06:03 | 5271.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -49.81 | -5221.72 |
Total Facility | 27-DEC-07:01 | 4364.64 | 6436.25 | 84965.66 | -6436.25 | 0.00 | 0.00 | 4467.69 | 10880.98 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33514.15 | 0.00 | -19112.30 | -74549.39 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9568 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4798 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6269 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0605 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.1920 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9395 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9784 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4168 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8135 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4296 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0960 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5171 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0392 | 3.0392 | 0.7993 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4686 | 2.4686 | 0.7850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6799 | 2.6799 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8786 | 0.8786 | 0.1757 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7773 | 0.7773 | 0.1555 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9687 | 0.9687 | 0.1937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8875 | 0.8875 | 0.1775 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7180 | 0.7180 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6784 | 0.6784 | 0.1357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8003 | 0.8003 | 0.1689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7209 | 0.7209 | 0.1442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7601 | 0.7601 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7461 | 0.7461 | 0.1492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8514 | 0.8514 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8008 | 0.8008 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9568 | 5.4798 | 5.9568 | 1.4168 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6269 | 5.0605 | 5.6269 | 1.4296 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.1920 | 5.9395 | 6.1920 | 1.5171 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5196 | 1.5196 | 0.7993 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2343 | 1.2343 | 0.7850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3400 | 1.3400 | 0.8147 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4393 | 0.4393 | 0.1757 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3887 | 0.3887 | 0.1555 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4844 | 0.4844 | 0.1937 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4437 | 0.4437 | 0.1775 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3590 | 0.3590 | 0.1687 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3392 | 0.3392 | 0.1357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4001 | 0.4001 | 0.1689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3604 | 0.3604 | 0.1442 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3800 | 0.3800 | 0.1649 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3730 | 0.3730 | 0.1492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4257 | 0.4257 | 0.1703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4004 | 0.4004 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9784 | 1.4168 | 1.4168 | 1.4168 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8135 | 1.4296 | 1.4296 | 1.4296 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0960 | 1.5171 | 1.5171 | 1.5171 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 95.50 |
Number of hours cooling loads not met | 228.33 |
Number of hours not met | 323.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 59.78 | 148342.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 290.12 | 71789.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 301.05 | 32642.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.37 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.90 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 132.33 | 35827.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.43 | 548.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 46.60 | 5914.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1567.49 |
Natural Gas | 0.00 | 59.78 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1627.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 60.43 |
Space Heating | 0.00 |
Space Cooling | 58.23 |
Fans (All) | 26.56 |
Service Water Heating | 9.35 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 314.62 |
Subtotal | 314.62 |
Natural Gas [MJ/m2] | |
Space Heating | 12.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 12.00 |
Subtotal | 12.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.50 |
Space Heating | 3.67 |
Space Cooling | 17.83 |
Fans (All) | 8.13 |
Service Water Heating | 2.86 |
Receptacle Equipment | 44.23 |
Miscellaneous | 4.78 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8517.00 | 243.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8690.33 | 69.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8685.67 | 74.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8695.67 | 64.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8699.00 | 61.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8693.00 | 67.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8557.33 | 202.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8517.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 243.00 | 0.00 | 0.00 | 0.00 |
Average | 8706.13 | 53.87 | 0.00 | 0.00 | 0.00 |
Sum | 156710.33 | 969.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128240.67 | 63.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 63.33 | 0.00 | 0.00 | 0.00 |
Average | 34139.81 | 3.52 | 0.00 | 0.00 | 0.00 |
Sum | 614516.67 | 63.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8359.83 | 400.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8577.33 | 182.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8682.50 | 77.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8611.83 | 148.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8536.33 | 223.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8579.50 | 180.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8543.83 | 216.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8606.33 | 153.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8486.67 | 273.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8515.17 | 244.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8474.00 | 286.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8579.00 | 181.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8495.67 | 264.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8535.00 | 225.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8497.67 | 262.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8499.17 | 260.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8673.33 | 86.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8643.33 | 116.67 | 0.00 | 0.00 | 0.00 |
Min | 8359.83 | 77.50 | 0.00 | 0.00 | 0.00 |
Max | 8682.50 | 400.17 | 0.00 | 0.00 | 0.00 |
Average | 8549.81 | 210.19 | 0.00 | 0.00 | 0.00 |
Sum | 153896.50 | 3783.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128116.33 | 187.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128225.17 | 78.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128237.67 | 66.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24898.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24906.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14013.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24790.17 | 118.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24903.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24904.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128237.67 | 187.67 | 0.00 | 0.00 | 0.00 |
Average | 34115.31 | 28.03 | 0.00 | 0.00 | 0.00 |
Sum | 614075.50 | 504.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150815E+11 | 22953.41 | 05-JAN-06:01 | -1.6 | -5.8 | 0.198722E+10 | 2606.64 | 02-JAN-10:09 | -1.6 | -5.8 |
February | 0.151182E+11 | 25103.29 | 22-FEB-07:02 | 1.93 | -2.5 | 0.180519E+10 | 2606.78 | 13-FEB-10:09 | 1.93 | -2.5 |
March | 0.194214E+11 | 30587.80 | 17-MAR-06:02 | 2.88 | -2.5 | 0.215841E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.221180E+11 | 38215.05 | 10-APR-05:12 | 14.63 | 6.49 | 0.191925E+10 | 2606.68 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.267659E+11 | 40847.72 | 31-MAY-04:03 | 26.32 | 12.48 | 0.207907E+10 | 2606.70 | 08-MAY-09:09 | 26.32 | 12.48 |
June | 0.282252E+11 | 41507.92 | 09-JUN-05:02 | 23.80 | 14.62 | 0.207271E+10 | 2606.66 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.279405E+11 | 41263.39 | 25-JUL-04:02 | 24.40 | 17.41 | 0.192710E+10 | 2770.26 | 20-JUL-15:20 | 24.40 | 17.41 |
August | 0.295520E+11 | 40608.79 | 11-AUG-04:03 | 24.22 | 15.27 | 0.216248E+10 | 2606.66 | 30-AUG-09:00 | 25.00 | 16.34 |
September | 0.266721E+11 | 40323.11 | 06-SEP-05:12 | 15.93 | 14.42 | 0.192112E+10 | 2606.66 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.247650E+11 | 39338.46 | 02-OCT-04:02 | 24.82 | 15.04 | 0.199612E+10 | 2606.73 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.194607E+11 | 36507.34 | 01-NOV-06:02 | 11.10 | 10.08 | 0.197343E+10 | 2606.61 | 09-NOV-10:00 | 20.00 | 9.96 |
December | 0.146344E+11 | 17495.38 | 15-DEC-17:00 | 15.00 | 5.87 | 0.191718E+10 | 2606.62 | 04-DEC-10:09 | 15.00 | 5.87 |
Annual Sum or Average | 0.269755E+12 | 0.239193E+11 | ||||||||
Minimum of Months | 0.146344E+11 | 17495.38 | -1.6 | -5.8 | 0.180519E+10 | 2606.61 | -1.6 | -5.8 | ||
Maximum of Months | 0.295520E+11 | 41507.92 | 26.32 | 17.41 | 0.216248E+10 | 2770.26 | 30.00 | 17.41 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.477606E+09 | 3069.52 | 12-JAN-15:20 | 18.90 | 10.07 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.07 |
February | 0.893463E+09 | 4597.54 | 22-FEB-14:10 | 21.78 | 7.94 | 0.00 | 0.00 | 01-FEB-00:10 | 21.78 | 7.94 |
March | 0.192797E+10 | 5875.03 | 16-MAR-14:20 | 22.80 | 9.14 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.14 |
April | 0.409291E+10 | 9204.72 | 28-APR-14:40 | 28.90 | 14.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 14.03 |
May | 0.657517E+10 | 11105.14 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.890518E+10 | 11715.37 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.830836E+10 | 12067.95 | 03-JUL-13:10 | 36.88 | 18.64 | 0.00 | 0.00 | 01-JUL-00:10 | 36.88 | 18.64 |
August | 0.772495E+10 | 11660.88 | 07-AUG-14:50 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.620370E+10 | 10307.04 | 19-SEP-15:10 | 33.40 | 16.39 | 0.00 | 0.00 | 01-SEP-00:10 | 33.40 | 16.39 |
October | 0.346207E+10 | 9401.86 | 03-OCT-14:30 | 32.25 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 | 32.25 | 19.38 |
November | 0.127081E+10 | 5216.57 | 03-NOV-15:20 | 23.50 | 13.53 | 0.00 | 0.00 | 01-NOV-00:10 | 23.50 | 13.53 |
December | 0.317848E+09 | 1734.43 | 09-DEC-13:30 | 17.50 | 7.28 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 7.28 |
Annual Sum or Average | 0.501600E+11 | 0.00 | ||||||||
Minimum of Months | 0.317848E+09 | 1734.43 | 17.50 | 7.28 | 0.00 | 0.00 | 17.50 | 7.28 | ||
Maximum of Months | 0.890518E+10 | 12067.95 | 38.13 | 19.38 | 0.00 | 0.00 | 38.13 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183117E+09 | 2157.13 | 05-JAN-07:02 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.279190E+09 | 2514.15 | 09-FEB-07:02 | 0.78 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.78 | -2.4 |
March | 0.608474E+09 | 2584.02 | 30-MAR-06:02 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.188414E+10 | 3518.45 | 21-APR-15:50 | 31.28 | 14.93 | 0.00 | 0.00 | 01-APR-00:10 | 31.28 | 14.93 |
May | 0.357936E+10 | 5215.60 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.491239E+10 | 5530.54 | 19-JUN-14:30 | 34.70 | 18.56 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 18.56 |
July | 0.472532E+10 | 5798.32 | 03-JUL-14:50 | 37.30 | 18.89 | 0.00 | 0.00 | 01-JUL-00:10 | 37.30 | 18.89 |
August | 0.455134E+10 | 5567.64 | 07-AUG-14:50 | 35.00 | 18.73 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.73 |
September | 0.354629E+10 | 4945.72 | 05-SEP-15:20 | 31.10 | 19.29 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 19.29 |
October | 0.201577E+10 | 4244.71 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.510968E+09 | 2286.03 | 10-NOV-15:50 | 15.10 | 9.99 | 0.00 | 0.00 | 01-NOV-00:10 | 15.10 | 9.99 |
December | 0.132462E+09 | 1991.05 | 14-DEC-07:02 | 2.30 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 2.30 | 1.51 |
Annual Sum or Average | 0.269288E+11 | 0.00 | ||||||||
Minimum of Months | 0.132462E+09 | 1991.05 | -0.9 | -5.5 | 0.00 | 0.00 | -0.9 | -5.5 | ||
Maximum of Months | 0.491239E+10 | 5798.32 | 37.30 | 19.29 | 0.00 | 0.00 | 37.30 | 19.29 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362667E+09 | 2609.42 | 06-JAN-07:02 | 0.32 | -3.5 | 0.00 | 0.00 | 01-JAN-00:10 | 0.32 | -3.5 |
February | 0.595529E+09 | 2764.90 | 16-FEB-07:01 | -1.5 | -2.6 | 0.00 | 0.00 | 01-FEB-00:10 | -1.5 | -2.6 |
March | 0.116499E+10 | 2681.96 | 17-MAR-06:06 | 2.88 | -2.5 | 0.00 | 0.00 | 01-MAR-00:10 | 2.88 | -2.5 |
April | 0.241705E+10 | 3739.85 | 21-APR-15:50 | 31.28 | 14.93 | 0.00 | 0.00 | 01-APR-00:10 | 31.28 | 14.93 |
May | 0.402872E+10 | 5384.42 | 30-MAY-15:40 | 34.07 | 17.56 | 0.00 | 0.00 | 01-MAY-00:10 | 34.07 | 17.56 |
June | 0.522315E+10 | 5887.54 | 05-JUN-12:10 | 34.68 | 16.27 | 0.00 | 0.00 | 01-JUN-00:10 | 34.68 | 16.27 |
July | 0.514483E+10 | 6974.88 | 03-JUL-12:08 | 35.78 | 18.54 | 0.00 | 0.00 | 01-JUL-00:10 | 35.78 | 18.54 |
August | 0.521474E+10 | 6150.62 | 21-AUG-12:10 | 30.78 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 30.78 | 18.88 |
September | 0.442669E+10 | 5643.73 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.300624E+10 | 4511.43 | 03-OCT-16:00 | 29.40 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 29.40 | 17.21 |
November | 0.121322E+10 | 3161.93 | 10-NOV-16:00 | 15.00 | 9.95 | 0.00 | 0.00 | 01-NOV-00:10 | 15.00 | 9.95 |
December | 0.258055E+09 | 2456.44 | 21-DEC-07:02 | 0.60 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | 0.60 | -2.5 |
Annual Sum or Average | 0.330559E+11 | 0.00 | ||||||||
Minimum of Months | 0.258055E+09 | 2456.44 | -1.5 | -3.5 | 0.00 | 0.00 | -1.5 | -3.5 | ||
Maximum of Months | 0.522315E+10 | 6974.88 | 35.78 | 18.88 | 0.00 | 0.00 | 35.78 | 18.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.886122E+10 | 10245.86 | 13-JAN-17:00 | 17.20 | 8.47 | 0.187047E+10 | 2606.60 | 13-JAN-10:20 | 17.20 | 8.47 |
February | 0.911849E+10 | 12017.57 | 22-FEB-17:00 | 21.70 | 8.09 | 0.174204E+10 | 2606.60 | 23-FEB-10:09 | 13.48 | 7.26 |
March | 0.121846E+11 | 13663.73 | 16-MAR-16:00 | 22.20 | 8.37 | 0.211850E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.150317E+11 | 15942.34 | 21-APR-16:00 | 31.10 | 14.82 | 0.190728E+10 | 2606.67 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.191824E+11 | 32181.00 | 30-MAY-04:03 | 25.00 | 11.58 | 0.207351E+10 | 2606.68 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.210111E+11 | 31972.25 | 07-JUN-04:02 | 24.32 | 12.65 | 0.206922E+10 | 2606.65 | 12-JUN-09:30 | 28.05 | 12.77 |
July | 0.207196E+11 | 32540.48 | 25-JUL-04:02 | 24.40 | 17.41 | 0.192284E+10 | 2689.01 | 20-JUL-15:20 | 24.40 | 17.41 |
August | 0.213622E+11 | 32473.96 | 08-AUG-04:02 | 25.00 | 18.13 | 0.215838E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.184579E+11 | 32627.23 | 05-SEP-05:12 | 16.30 | 15.51 | 0.191579E+10 | 2606.65 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.160125E+11 | 30663.22 | 02-OCT-04:02 | 24.82 | 15.04 | 0.198414E+10 | 2606.69 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.111927E+11 | 15112.49 | 10-NOV-16:50 | 14.50 | 9.32 | 0.191941E+10 | 2606.61 | 01-NOV-09:09 | 14.50 | 9.32 |
December | 0.843436E+10 | 9024.23 | 15-DEC-17:00 | 15.00 | 5.87 | 0.178161E+10 | 2606.57 | 01-DEC-14:09 | 15.00 | 5.87 |
Annual Sum or Average | 0.181569E+12 | 0.234632E+11 | ||||||||
Minimum of Months | 0.843436E+10 | 9024.23 | 14.50 | 5.87 | 0.174204E+10 | 2606.57 | 13.48 | 5.68 | ||
Maximum of Months | 0.213622E+11 | 32627.23 | 31.10 | 18.13 | 0.215838E+10 | 2689.01 | 28.05 | 17.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.757847E+10 | 9335.34 | 12-JAN-16:50 | 17.98 | 9.87 | 0.172675E+10 | 2606.51 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.808708E+10 | 11407.07 | 22-FEB-15:40 | 22.60 | 8.36 | 0.163829E+10 | 2606.53 | 07-FEB-14:09 | 22.60 | 8.36 |
March | 0.111170E+11 | 14699.02 | 16-MAR-16:00 | 22.20 | 8.37 | 0.203963E+10 | 2606.58 | 09-MAR-14:09 | 22.20 | 8.37 |
April | 0.146907E+11 | 17814.47 | 28-APR-15:40 | 28.50 | 13.78 | 0.188948E+10 | 2606.67 | 27-APR-09:09 | 28.50 | 13.78 |
May | 0.196725E+11 | 28377.39 | 30-MAY-04:03 | 25.00 | 11.58 | 0.206906E+10 | 2606.67 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.225438E+11 | 34637.46 | 09-JUN-05:02 | 23.80 | 14.62 | 0.206879E+10 | 2606.65 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.220924E+11 | 34965.00 | 10-JUL-04:02 | 24.32 | 16.38 | 0.192327E+10 | 2693.56 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.221290E+11 | 34273.28 | 14-AUG-05:12 | 17.40 | 16.29 | 0.215713E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.182846E+11 | 23396.39 | 05-SEP-06:03 | 17.07 | 15.07 | 0.191080E+10 | 2606.64 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.147161E+11 | 31412.89 | 02-OCT-04:02 | 24.82 | 15.04 | 0.196178E+10 | 2606.66 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.954718E+10 | 14740.46 | 10-NOV-15:00 | 15.60 | 10.20 | 0.182423E+10 | 2606.58 | 01-NOV-09:00 | 15.60 | 10.20 |
December | 0.701158E+10 | 7214.00 | 15-DEC-17:00 | 15.00 | 5.87 | 0.162811E+10 | 2565.85 | 01-DEC-14:00 | 15.00 | 5.87 |
Annual Sum or Average | 0.177470E+12 | 0.228373E+11 | ||||||||
Minimum of Months | 0.701158E+10 | 7214.00 | 15.00 | 5.87 | 0.162811E+10 | 2565.85 | 15.00 | 5.87 | ||
Maximum of Months | 0.225438E+11 | 34965.00 | 28.50 | 16.38 | 0.215713E+10 | 2693.56 | 30.00 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853587E+09 | 1537.39 | 12-JAN-14:30 | 18.60 | 9.87 | 0.326658E+09 | 518.01 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.115674E+10 | 2112.29 | 22-FEB-15:00 | 22.20 | 8.00 | 0.312821E+09 | 549.47 | 07-FEB-14:00 | 22.20 | 8.00 |
March | 0.193125E+10 | 3387.78 | 22-MAR-14:30 | 24.15 | 9.01 | 0.399762E+09 | 549.48 | 16-MAR-13:00 | 24.15 | 9.01 |
April | 0.332698E+10 | 5723.53 | 21-APR-15:00 | 32.20 | 15.49 | 0.388362E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.543453E+10 | 12719.21 | 21-MAY-15:11 | 34.40 | 17.95 | 0.435065E+09 | 549.50 | 16-MAY-09:00 | 34.40 | 17.95 |
June | 0.719321E+10 | 12655.40 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436533E+09 | 549.50 | 27-JUN-09:50 | 25.50 | 15.70 |
July | 0.684582E+10 | 12730.50 | 02-JUL-16:22 | 38.05 | 18.71 | 0.406150E+09 | 560.56 | 20-JUL-14:00 | 24.40 | 22.82 |
August | 0.623489E+10 | 10928.87 | 07-AUG-04:02 | 26.10 | 16.24 | 0.454573E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.467298E+10 | 6124.81 | 20-SEP-14:30 | 33.30 | 17.76 | 0.400246E+09 | 549.50 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.303560E+10 | 6556.40 | 02-OCT-04:02 | 24.82 | 15.04 | 0.400719E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.148645E+10 | 2818.31 | 09-NOV-15:40 | 23.30 | 12.89 | 0.353562E+09 | 549.47 | 09-NOV-14:00 | 23.30 | 12.89 |
December | 0.680329E+09 | 1355.24 | 08-DEC-16:30 | 16.65 | 7.38 | 0.308661E+09 | 491.89 | 08-DEC-14:00 | 16.65 | 7.38 |
Annual Sum or Average | 0.428524E+11 | 0.462311E+10 | ||||||||
Minimum of Months | 0.680329E+09 | 1355.24 | 16.65 | 7.38 | 0.308661E+09 | 491.89 | 16.65 | 7.38 | ||
Maximum of Months | 0.719321E+10 | 12730.50 | 38.05 | 18.71 | 0.454573E+09 | 560.56 | 34.40 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102267E+10 | 1485.97 | 04-JAN-10:10 | 9.60 | 3.11 | 0.219488E+09 | 347.86 | 04-JAN-10:09 | 9.60 | 3.11 |
February | 0.132833E+10 | 2908.73 | 21-FEB-10:30 | 18.35 | 7.04 | 0.214310E+09 | 347.87 | 24-FEB-10:09 | 7.48 | 2.32 |
March | 0.227663E+10 | 4193.66 | 16-MAR-10:10 | 19.18 | 7.83 | 0.270101E+09 | 347.87 | 06-MAR-10:09 | 19.18 | 7.83 |
April | 0.385324E+10 | 10384.40 | 30-APR-10:53 | 25.00 | 12.86 | 0.252835E+09 | 347.90 | 19-APR-09:09 | 25.00 | 12.86 |
May | 0.552049E+10 | 12021.86 | 21-MAY-09:52 | 27.20 | 13.44 | 0.276583E+09 | 348.28 | 15-MAY-09:00 | 27.20 | 13.44 |
June | 0.667120E+10 | 11724.41 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276587E+09 | 348.25 | 27-JUN-09:00 | 25.60 | 15.68 |
July | 0.622904E+10 | 11807.64 | 02-JUL-09:42 | 30.73 | 19.96 | 0.257392E+09 | 348.37 | 28-JUL-09:00 | 30.60 | 19.45 |
August | 0.597367E+10 | 11769.78 | 06-AUG-09:32 | 29.83 | 17.77 | 0.287910E+09 | 348.24 | 09-AUG-09:39 | 29.43 | 19.02 |
September | 0.485733E+10 | 12133.04 | 17-SEP-09:42 | 26.65 | 16.10 | 0.254951E+09 | 348.33 | 05-SEP-09:00 | 26.65 | 16.10 |
October | 0.313866E+10 | 8611.50 | 01-OCT-09:32 | 23.67 | 13.35 | 0.258696E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.161313E+10 | 4630.47 | 10-NOV-09:20 | 18.67 | 11.91 | 0.237695E+09 | 347.87 | 09-NOV-10:00 | 18.67 | 11.91 |
December | 0.875114E+09 | 1272.26 | 01-DEC-10:20 | 12.77 | 4.87 | 0.204275E+09 | 326.50 | 01-DEC-10:30 | 13.05 | 5.08 |
Annual Sum or Average | 0.433595E+11 | 0.301082E+10 | ||||||||
Minimum of Months | 0.875114E+09 | 1272.26 | 9.60 | 3.11 | 0.204275E+09 | 326.50 | 7.48 | 2.32 | ||
Maximum of Months | 0.667120E+10 | 12133.04 | 31.13 | 19.96 | 0.287910E+09 | 348.37 | 30.60 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322276E+10 | 9366.83 | 12-JAN-14:30 | 18.60 | 9.87 | 0.384874E+09 | 549.60 | 12-JAN-14:00 | 18.90 | 10.02 |
February | 0.329358E+10 | 14519.71 | 20-FEB-14:13 | 22.57 | 8.60 | 0.352769E+09 | 549.79 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.412214E+10 | 8726.31 | 16-MAR-13:30 | 22.50 | 9.16 | 0.424759E+09 | 549.71 | 16-MAR-13:00 | 22.80 | 9.34 |
April | 0.495713E+10 | 14390.86 | 30-APR-12:53 | 29.40 | 12.28 | 0.391593E+09 | 549.51 | 26-APR-13:50 | 29.40 | 12.28 |
May | 0.600063E+10 | 14277.80 | 21-MAY-15:11 | 34.40 | 17.95 | 0.434045E+09 | 549.51 | 05-MAY-13:00 | 34.40 | 17.95 |
June | 0.715254E+10 | 12937.84 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436175E+09 | 549.50 | 12-JUN-09:00 | 37.12 | 16.83 |
July | 0.707877E+10 | 14399.04 | 30-JUL-13:32 | 31.33 | 19.86 | 0.405916E+09 | 557.42 | 20-JUL-14:00 | 31.33 | 19.86 |
August | 0.761910E+10 | 14452.45 | 27-AUG-12:43 | 34.22 | 16.72 | 0.454553E+09 | 550.30 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.758686E+10 | 14725.91 | 04-SEP-12:02 | 28.68 | 18.59 | 0.401760E+09 | 549.94 | 15-SEP-13:00 | 32.20 | 17.96 |
October | 0.674427E+10 | 15933.62 | 01-OCT-12:12 | 30.37 | 14.43 | 0.410373E+09 | 557.13 | 03-OCT-13:39 | 32.07 | 19.44 |
November | 0.469162E+10 | 11700.04 | 11-NOV-13:02 | 18.30 | 8.11 | 0.389845E+09 | 549.92 | 08-NOV-14:50 | 18.30 | 8.11 |
December | 0.288904E+10 | 7475.52 | 07-DEC-14:10 | 15.68 | 6.76 | 0.368680E+09 | 549.49 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.653585E+11 | 0.485534E+10 | ||||||||
Minimum of Months | 0.288904E+10 | 7475.52 | 15.68 | 6.76 | 0.352769E+09 | 549.49 | 15.68 | 6.76 | ||
Maximum of Months | 0.761910E+10 | 15933.62 | 37.12 | 19.86 | 0.454553E+09 | 557.42 | 37.12 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108167E+10 | 3600.75 | 12-JAN-15:30 | 18.90 | 10.10 | 0.215156E+09 | 347.83 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.136378E+10 | 4997.85 | 19-FEB-16:23 | 22.50 | 8.40 | 0.200712E+09 | 347.84 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.245411E+10 | 6198.27 | 21-MAR-16:00 | 25.00 | 9.53 | 0.250756E+09 | 347.84 | 09-MAR-14:09 | 25.00 | 9.53 |
April | 0.383178E+10 | 14636.43 | 16-APR-16:21 | 30.00 | 11.59 | 0.242057E+09 | 347.86 | 26-APR-13:50 | 26.32 | 13.73 |
May | 0.543716E+10 | 14333.35 | 21-MAY-15:11 | 34.40 | 17.95 | 0.273316E+09 | 347.86 | 05-MAY-13:00 | 34.40 | 17.95 |
June | 0.644462E+10 | 13917.03 | 25-JUN-16:32 | 31.50 | 16.81 | 0.275896E+09 | 347.85 | 12-JUN-09:00 | 31.50 | 16.81 |
July | 0.603023E+10 | 13866.48 | 09-JUL-16:32 | 32.97 | 19.28 | 0.256692E+09 | 347.86 | 03-JUL-09:09 | 32.97 | 19.28 |
August | 0.580008E+10 | 13892.15 | 06-AUG-16:52 | 36.10 | 18.82 | 0.286829E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.488543E+10 | 13639.27 | 17-SEP-15:42 | 32.80 | 15.93 | 0.251792E+09 | 347.85 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.347579E+10 | 13806.74 | 01-OCT-14:52 | 32.80 | 15.90 | 0.249781E+09 | 347.85 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.190719E+10 | 5639.37 | 09-NOV-15:30 | 23.30 | 12.82 | 0.225189E+09 | 347.84 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.880187E+09 | 2683.83 | 15-DEC-15:50 | 15.60 | 6.12 | 0.204957E+09 | 347.83 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.435920E+11 | 0.293313E+10 | ||||||||
Minimum of Months | 0.880187E+09 | 2683.83 | 15.60 | 6.12 | 0.200712E+09 | 347.83 | 15.60 | 6.12 | ||
Maximum of Months | 0.644462E+10 | 14636.43 | 36.10 | 19.28 | 0.286829E+09 | 347.86 | 34.40 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119306E+10 | 1363.35 | 13-JAN-15:00 | 18.30 | 8.81 | 0.334714E+09 | 509.88 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.120800E+10 | 1453.01 | 23-FEB-14:40 | 21.47 | 7.31 | 0.311694E+09 | 536.42 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.165014E+10 | 1585.54 | 22-MAR-14:40 | 24.07 | 8.96 | 0.390886E+09 | 549.46 | 15-MAR-13:00 | 24.07 | 8.96 |
April | 0.239946E+10 | 3870.43 | 21-APR-15:20 | 31.83 | 15.27 | 0.387146E+09 | 549.50 | 27-APR-09:39 | 21.67 | 12.66 |
May | 0.410631E+10 | 5133.38 | 30-MAY-15:20 | 34.23 | 17.67 | 0.434928E+09 | 549.50 | 08-MAY-09:09 | 34.23 | 17.67 |
June | 0.576113E+10 | 6243.17 | 19-JUN-06:03 | 23.07 | 16.06 | 0.435986E+09 | 549.50 | 12-JUN-09:00 | 23.07 | 16.06 |
July | 0.608099E+10 | 8437.79 | 03-JUL-06:03 | 26.88 | 16.13 | 0.405777E+09 | 558.85 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.600245E+10 | 8199.69 | 07-AUG-06:03 | 25.18 | 16.26 | 0.455133E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.489622E+10 | 5565.84 | 20-SEP-14:30 | 33.30 | 17.76 | 0.403432E+09 | 549.49 | 12-SEP-09:20 | 33.30 | 17.76 |
October | 0.331555E+10 | 5339.43 | 03-OCT-14:30 | 32.25 | 19.38 | 0.414220E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.186880E+10 | 2534.60 | 09-NOV-16:20 | 23.13 | 12.95 | 0.376364E+09 | 549.48 | 09-NOV-10:50 | 23.13 | 12.95 |
December | 0.117497E+10 | 1338.12 | 01-DEC-14:30 | 13.85 | 6.23 | 0.322797E+09 | 503.71 | 01-DEC-14:39 | 13.67 | 6.12 |
Annual Sum or Average | 0.396571E+11 | 0.467308E+10 | ||||||||
Minimum of Months | 0.117497E+10 | 1338.12 | 13.85 | 6.23 | 0.311694E+09 | 503.71 | 13.67 | 6.12 | ||
Maximum of Months | 0.608099E+10 | 8437.79 | 34.23 | 19.38 | 0.455133E+09 | 558.85 | 34.23 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120717E+10 | 1527.75 | 04-JAN-10:10 | 9.60 | 3.11 | 0.231279E+09 | 347.86 | 31-JAN-10:09 | 11.88 | 4.56 |
February | 0.130302E+10 | 2573.89 | 21-FEB-10:30 | 18.35 | 7.04 | 0.218777E+09 | 347.87 | 17-FEB-10:09 | 18.35 | 7.04 |
March | 0.185925E+10 | 3041.67 | 31-MAR-09:50 | 18.25 | 6.32 | 0.272067E+09 | 347.87 | 06-MAR-10:09 | 18.25 | 6.32 |
April | 0.304002E+10 | 7498.83 | 30-APR-10:43 | 24.53 | 12.98 | 0.253823E+09 | 347.88 | 27-APR-09:09 | 24.53 | 12.98 |
May | 0.460401E+10 | 10188.72 | 21-MAY-09:52 | 27.20 | 13.44 | 0.276832E+09 | 348.15 | 30-MAY-09:00 | 28.90 | 14.30 |
June | 0.570265E+10 | 8721.66 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276563E+09 | 348.12 | 07-JUN-09:00 | 31.13 | 16.72 |
July | 0.571874E+10 | 10614.82 | 09-JUL-09:02 | 26.38 | 19.19 | 0.257497E+09 | 348.25 | 28-JUL-09:00 | 30.60 | 19.45 |
August | 0.586741E+10 | 10482.30 | 27-AUG-10:22 | 31.95 | 14.97 | 0.288608E+09 | 348.14 | 04-AUG-09:00 | 31.95 | 14.97 |
September | 0.514806E+10 | 10776.87 | 04-SEP-09:12 | 24.23 | 18.30 | 0.256125E+09 | 348.22 | 11-SEP-09:00 | 25.60 | 12.20 |
October | 0.346184E+10 | 5863.07 | 05-OCT-09:10 | 25.37 | 18.00 | 0.264159E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.195694E+10 | 4417.88 | 10-NOV-09:10 | 18.48 | 11.84 | 0.251355E+09 | 347.87 | 09-NOV-10:50 | 18.48 | 11.84 |
December | 0.117991E+10 | 1311.45 | 01-DEC-10:10 | 12.48 | 4.67 | 0.221626E+09 | 347.86 | 01-DEC-10:00 | 13.90 | 5.69 |
Annual Sum or Average | 0.410490E+11 | 0.306871E+10 | ||||||||
Minimum of Months | 0.117991E+10 | 1311.45 | 9.60 | 3.11 | 0.218777E+09 | 347.86 | 11.88 | 4.56 | ||
Maximum of Months | 0.586741E+10 | 10776.87 | 31.95 | 19.19 | 0.288608E+09 | 348.25 | 31.95 | 19.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249284E+10 | 8721.41 | 01-JAN-14:13 | 15.77 | 9.37 | 0.379791E+09 | 549.50 | 26-JAN-14:09 | 6.20 | -1.5 |
February | 0.224269E+10 | 10427.57 | 20-FEB-14:33 | 22.93 | 8.74 | 0.345039E+09 | 549.65 | 21-FEB-14:09 | 21.88 | 8.00 |
March | 0.255860E+10 | 5975.11 | 22-MAR-13:10 | 24.90 | 9.24 | 0.414002E+09 | 549.50 | 01-MAR-14:09 | 24.90 | 9.24 |
April | 0.357508E+10 | 9532.21 | 19-APR-12:00 | 30.60 | 14.04 | 0.386596E+09 | 549.51 | 24-APR-13:30 | 24.70 | 9.91 |
May | 0.507442E+10 | 10462.08 | 30-MAY-16:10 | 33.62 | 17.22 | 0.431581E+09 | 561.62 | 19-MAY-12:09 | 33.62 | 17.22 |
June | 0.680837E+10 | 10906.82 | 02-JUN-16:50 | 38.90 | 16.18 | 0.436682E+09 | 605.63 | 15-JUN-12:09 | 36.10 | 14.46 |
July | 0.717649E+10 | 10996.78 | 03-JUL-16:50 | 38.30 | 18.84 | 0.406775E+09 | 614.98 | 03-JUL-12:09 | 38.30 | 18.84 |
August | 0.806822E+10 | 11915.61 | 27-AUG-13:02 | 34.40 | 16.78 | 0.455979E+09 | 610.87 | 07-AUG-12:09 | 34.40 | 16.78 |
September | 0.832774E+10 | 12550.20 | 04-SEP-13:12 | 30.60 | 18.77 | 0.405218E+09 | 601.50 | 19-SEP-12:09 | 31.88 | 16.39 |
October | 0.692788E+10 | 12684.42 | 22-OCT-12:22 | 24.75 | 14.17 | 0.416748E+09 | 589.05 | 03-OCT-12:09 | 24.75 | 14.17 |
November | 0.454217E+10 | 12556.72 | 11-NOV-13:22 | 18.30 | 8.05 | 0.394913E+09 | 558.66 | 09-NOV-14:09 | 18.30 | 8.05 |
December | 0.235809E+10 | 8242.72 | 17-DEC-13:33 | 14.27 | 4.03 | 0.364748E+09 | 549.50 | 27-DEC-14:20 | 6.87 | 2.11 |
Annual Sum or Average | 0.601526E+11 | 0.483807E+10 | ||||||||
Minimum of Months | 0.224269E+10 | 5975.11 | 14.27 | 4.03 | 0.345039E+09 | 549.50 | 6.20 | -1.5 | ||
Maximum of Months | 0.832774E+10 | 12684.42 | 38.90 | 18.84 | 0.455979E+09 | 614.98 | 38.30 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129312E+10 | 2707.35 | 30-JAN-16:30 | 15.60 | 6.05 | 0.223059E+09 | 347.83 | 13-JAN-14:00 | 15.60 | 6.05 |
February | 0.127445E+10 | 3854.69 | 21-FEB-16:50 | 22.30 | 7.87 | 0.205191E+09 | 347.83 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.188483E+10 | 3941.72 | 21-MAR-16:00 | 25.00 | 9.53 | 0.255968E+09 | 347.84 | 09-MAR-14:09 | 25.00 | 9.53 |
April | 0.285852E+10 | 11300.22 | 16-APR-16:21 | 30.00 | 11.59 | 0.247351E+09 | 347.85 | 27-APR-09:00 | 22.20 | 13.12 |
May | 0.440055E+10 | 11415.26 | 21-MAY-15:11 | 34.40 | 17.95 | 0.275708E+09 | 347.86 | 08-MAY-09:09 | 34.40 | 17.95 |
June | 0.539546E+10 | 10961.90 | 04-JUN-16:22 | 35.30 | 17.10 | 0.276306E+09 | 347.85 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.543879E+10 | 11155.55 | 09-JUL-17:01 | 32.80 | 19.12 | 0.257151E+09 | 347.86 | 03-JUL-09:09 | 32.80 | 19.12 |
August | 0.560717E+10 | 11566.86 | 27-AUG-17:42 | 33.58 | 16.47 | 0.288461E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.503331E+10 | 11286.38 | 04-SEP-16:32 | 29.80 | 17.87 | 0.255922E+09 | 347.85 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.361095E+10 | 10991.91 | 22-OCT-16:22 | 26.95 | 14.59 | 0.263616E+09 | 347.86 | 17-OCT-09:00 | 26.95 | 14.59 |
November | 0.212281E+10 | 5096.77 | 09-NOV-16:10 | 23.22 | 12.98 | 0.243829E+09 | 347.84 | 10-NOV-10:09 | 19.60 | 12.16 |
December | 0.123704E+10 | 2452.59 | 15-DEC-16:10 | 15.50 | 6.10 | 0.214839E+09 | 347.84 | 01-DEC-14:00 | 15.50 | 6.10 |
Annual Sum or Average | 0.401570E+11 | 0.300740E+10 | ||||||||
Minimum of Months | 0.123704E+10 | 2452.59 | 15.50 | 6.05 | 0.205191E+09 | 347.83 | 15.50 | 6.05 | ||
Maximum of Months | 0.560717E+10 | 11566.86 | 35.30 | 19.12 | 0.288461E+09 | 347.86 | 34.40 | 19.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124185E+10 | 1656.55 | 12-JAN-14:30 | 18.60 | 9.87 | 0.341644E+09 | 537.28 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.142951E+10 | 2299.21 | 23-FEB-14:30 | 21.65 | 7.41 | 0.327822E+09 | 549.47 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.210442E+10 | 3240.64 | 22-MAR-14:30 | 24.15 | 9.01 | 0.416664E+09 | 549.48 | 22-MAR-13:00 | 24.15 | 9.01 |
April | 0.329023E+10 | 5180.78 | 21-APR-15:20 | 31.83 | 15.27 | 0.395774E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.521942E+10 | 8056.37 | 30-MAY-06:03 | 25.10 | 11.90 | 0.436667E+09 | 549.50 | 08-MAY-09:09 | 25.10 | 11.90 |
June | 0.670608E+10 | 11183.97 | 25-JUN-18:21 | 30.85 | 16.43 | 0.436707E+09 | 549.50 | 12-JUN-09:39 | 30.85 | 16.43 |
July | 0.640151E+10 | 10932.58 | 02-JUL-16:11 | 38.13 | 18.77 | 0.406180E+09 | 560.64 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.595335E+10 | 9104.43 | 07-AUG-04:02 | 26.10 | 16.24 | 0.455148E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.459832E+10 | 5575.05 | 20-SEP-14:30 | 33.30 | 17.76 | 0.402744E+09 | 549.50 | 11-SEP-09:50 | 33.30 | 17.76 |
October | 0.315463E+10 | 6687.06 | 02-OCT-04:02 | 24.82 | 15.04 | 0.411154E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.176776E+10 | 2844.37 | 09-NOV-16:20 | 23.13 | 12.95 | 0.371998E+09 | 549.48 | 09-NOV-10:20 | 23.13 | 12.95 |
December | 0.107059E+10 | 1354.59 | 08-DEC-15:00 | 17.20 | 7.54 | 0.322409E+09 | 516.67 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.429377E+11 | 0.472491E+10 | ||||||||
Minimum of Months | 0.107059E+10 | 1354.59 | 17.20 | 7.41 | 0.322409E+09 | 516.67 | 17.20 | 7.10 | ||
Maximum of Months | 0.670608E+10 | 11183.97 | 38.13 | 18.77 | 0.455148E+09 | 560.64 | 33.30 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125965E+10 | 2228.37 | 04-JAN-09:50 | 9.32 | 3.11 | 0.168654E+09 | 338.71 | 03-JAN-09:50 | 9.32 | 3.11 |
February | 0.154862E+10 | 3448.48 | 21-FEB-10:00 | 16.70 | 6.62 | 0.162553E+09 | 338.72 | 24-FEB-08:20 | 4.80 | 0.90 |
March | 0.246312E+10 | 4596.51 | 31-MAR-09:00 | 15.00 | 4.82 | 0.201596E+09 | 338.72 | 07-MAR-08:09 | 15.00 | 4.82 |
April | 0.382096E+10 | 10959.37 | 16-APR-08:32 | 19.67 | 9.35 | 0.187513E+09 | 338.85 | 28-APR-08:00 | 21.10 | 12.61 |
May | 0.527756E+10 | 12048.19 | 29-MAY-09:02 | 22.67 | 15.59 | 0.204725E+09 | 342.94 | 30-MAY-07:19 | 25.97 | 12.58 |
June | 0.623441E+10 | 12136.93 | 18-JUN-08:52 | 28.30 | 16.88 | 0.204437E+09 | 343.61 | 05-JUN-07:19 | 28.30 | 16.88 |
July | 0.582378E+10 | 12019.08 | 09-JUL-09:02 | 26.38 | 19.19 | 0.190864E+09 | 345.65 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.565056E+10 | 11923.97 | 20-AUG-09:12 | 26.83 | 16.55 | 0.212860E+09 | 339.62 | 07-AUG-10:30 | 26.83 | 16.55 |
September | 0.473367E+10 | 12080.73 | 04-SEP-08:32 | 22.57 | 17.97 | 0.188978E+09 | 338.91 | 15-SEP-08:00 | 25.60 | 19.42 |
October | 0.322091E+10 | 6691.44 | 05-OCT-08:40 | 24.27 | 17.57 | 0.193034E+09 | 338.83 | 05-OCT-08:50 | 24.63 | 17.73 |
November | 0.187982E+10 | 5076.47 | 10-NOV-08:50 | 18.22 | 11.69 | 0.180001E+09 | 338.72 | 09-NOV-11:20 | 18.22 | 11.69 |
December | 0.112498E+10 | 1499.58 | 07-DEC-09:25 | 5.30 | 0.63 | 0.158415E+09 | 338.71 | 07-DEC-09:39 | 5.77 | 0.97 |
Annual Sum or Average | 0.430380E+11 | 0.225363E+10 | ||||||||
Minimum of Months | 0.112498E+10 | 1499.58 | 5.30 | 0.63 | 0.158415E+09 | 338.71 | 4.80 | 0.90 | ||
Maximum of Months | 0.623441E+10 | 12136.93 | 28.30 | 19.19 | 0.212860E+09 | 345.65 | 28.30 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380544E+10 | 9325.09 | 12-JAN-14:10 | 18.40 | 9.78 | 0.396870E+09 | 549.61 | 04-JAN-14:00 | 18.40 | 9.78 |
February | 0.370878E+10 | 12978.82 | 20-FEB-13:32 | 21.83 | 8.44 | 0.363540E+09 | 549.97 | 22-FEB-14:30 | 21.95 | 7.96 |
March | 0.437355E+10 | 8360.01 | 16-MAR-13:10 | 22.30 | 9.05 | 0.437197E+09 | 549.78 | 22-MAR-13:39 | 24.60 | 9.18 |
April | 0.485433E+10 | 12087.24 | 30-APR-14:32 | 29.80 | 12.58 | 0.398218E+09 | 549.79 | 21-APR-13:50 | 29.80 | 12.58 |
May | 0.570616E+10 | 9139.78 | 28-MAY-15:52 | 32.20 | 17.70 | 0.436464E+09 | 549.51 | 05-MAY-13:00 | 32.20 | 17.70 |
June | 0.663370E+10 | 12109.83 | 18-JUN-15:31 | 37.03 | 16.78 | 0.436563E+09 | 549.50 | 12-JUN-09:00 | 37.03 | 16.78 |
July | 0.657983E+10 | 12566.15 | 30-JUL-13:32 | 31.33 | 19.86 | 0.406133E+09 | 555.59 | 20-JUL-15:20 | 31.33 | 19.86 |
August | 0.723233E+10 | 12639.23 | 27-AUG-12:32 | 34.03 | 16.56 | 0.455401E+09 | 550.25 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.741073E+10 | 13396.88 | 17-SEP-12:12 | 31.30 | 15.71 | 0.403937E+09 | 556.53 | 29-SEP-13:39 | 28.13 | 14.71 |
October | 0.684848E+10 | 14049.85 | 29-OCT-13:22 | 23.90 | 11.32 | 0.417065E+09 | 573.38 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.522411E+10 | 13551.38 | 11-NOV-12:52 | 18.30 | 8.13 | 0.401212E+09 | 561.93 | 09-NOV-14:09 | 18.30 | 8.13 |
December | 0.353590E+10 | 8673.69 | 17-DEC-13:33 | 14.27 | 4.03 | 0.381208E+09 | 549.58 | 07-DEC-14:50 | 14.27 | 4.03 |
Annual Sum or Average | 0.659133E+11 | 0.493381E+10 | ||||||||
Minimum of Months | 0.353590E+10 | 8360.01 | 14.27 | 4.03 | 0.363540E+09 | 549.50 | 14.27 | 4.03 | ||
Maximum of Months | 0.741073E+10 | 14049.85 | 37.03 | 19.86 | 0.455401E+09 | 573.38 | 37.03 | 19.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139955E+10 | 3648.28 | 12-JAN-15:30 | 18.90 | 10.10 | 0.222112E+09 | 347.83 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.159990E+10 | 4870.12 | 21-FEB-16:40 | 22.40 | 7.93 | 0.208151E+09 | 347.84 | 10-FEB-14:50 | 22.40 | 7.93 |
March | 0.258253E+10 | 8768.56 | 26-MAR-17:03 | 22.52 | 9.15 | 0.260841E+09 | 347.84 | 22-MAR-13:00 | 22.52 | 9.15 |
April | 0.371059E+10 | 12109.59 | 30-APR-16:32 | 30.20 | 12.69 | 0.248196E+09 | 347.85 | 27-APR-09:30 | 30.20 | 12.69 |
May | 0.517380E+10 | 12838.80 | 29-MAY-17:01 | 32.52 | 16.27 | 0.275665E+09 | 347.86 | 05-MAY-13:00 | 32.52 | 16.27 |
June | 0.603374E+10 | 13251.57 | 11-JUN-17:01 | 32.12 | 14.88 | 0.276336E+09 | 347.85 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.564245E+10 | 12682.44 | 09-JUL-16:21 | 33.05 | 19.34 | 0.256992E+09 | 347.85 | 03-JUL-09:09 | 33.05 | 19.34 |
August | 0.550529E+10 | 12923.24 | 20-AUG-16:31 | 32.40 | 15.84 | 0.287883E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.473356E+10 | 12540.94 | 04-SEP-16:32 | 29.80 | 17.87 | 0.254504E+09 | 347.85 | 25-SEP-13:50 | 24.90 | 13.77 |
October | 0.348032E+10 | 12172.41 | 08-OCT-16:32 | 24.97 | 17.46 | 0.257944E+09 | 347.85 | 02-OCT-09:09 | 24.97 | 17.46 |
November | 0.215172E+10 | 5571.84 | 09-NOV-15:30 | 23.30 | 12.82 | 0.234753E+09 | 347.84 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.120730E+10 | 2961.33 | 15-DEC-15:50 | 15.60 | 6.12 | 0.211733E+09 | 347.84 | 01-DEC-14:00 | 15.60 | 6.12 |
Annual Sum or Average | 0.432207E+11 | 0.299511E+10 | ||||||||
Minimum of Months | 0.120730E+10 | 2961.33 | 15.60 | 6.12 | 0.208151E+09 | 347.83 | 15.60 | 6.12 | ||
Maximum of Months | 0.603374E+10 | 13251.57 | 33.05 | 19.34 | 0.287883E+09 | 347.86 | 33.05 | 19.34 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168823E+10 | 9527.25 | 27-JAN-07:03 | -4.3 |
February | 0.121092E+10 | 10219.28 | 03-FEB-07:03 | -5.1 |
March | 0.102798E+10 | 9243.42 | 02-MAR-07:02 | -1.6 |
April | 0.414439E+09 | 4444.13 | 16-APR-07:42 | 16.97 |
May | 0.168488E+09 | 4706.30 | 30-MAY-04:03 | 25.00 |
June | 40987179.13 | 5410.81 | 14-JUN-05:02 | 23.90 |
July | 24836223.50 | 4436.83 | 10-JUL-04:02 | 24.32 |
August | 42596029.87 | 4349.89 | 07-AUG-04:02 | 26.10 |
September | 0.177266E+09 | 3642.40 | 17-SEP-07:10 | 19.27 |
October | 0.427157E+09 | 3731.14 | 01-OCT-08:18 | 19.60 |
November | 0.104512E+10 | 8330.87 | 28-NOV-07:03 | 0.87 |
December | 0.201962E+10 | 10992.57 | 04-DEC-06:13 | -0.9 |
Annual Sum or Average | 0.828765E+10 | |||
Minimum of Months | 24836223.50 | 3642.40 | -5.1 | |
Maximum of Months | 0.201962E+10 | 10992.57 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949352E+09 | 3786.56 | 01-JAN-13:53 | 15.60 |
February | 0.530458E+09 | 3754.66 | 12-FEB-14:53 | 21.10 |
March | 0.288647E+09 | 2771.04 | 26-MAR-16:23 | 22.50 |
April | 27889444.29 | 2581.17 | 02-APR-15:02 | 26.60 |
May | 17024249.55 | 2070.99 | 07-MAY-16:02 | 29.32 |
June | 13755743.11 | 2656.01 | 18-JUN-15:31 | 37.03 |
July | 16377791.03 | 2657.48 | 02-JUL-14:51 | 37.80 |
August | 15296683.11 | 2462.08 | 27-AUG-15:11 | 35.00 |
September | 16008750.53 | 2674.04 | 17-SEP-14:51 | 32.80 |
October | 38556308.62 | 4606.61 | 08-OCT-15:52 | 26.10 |
November | 0.428245E+09 | 4062.03 | 19-NOV-12:23 | 15.55 |
December | 0.108374E+10 | 3929.60 | 17-DEC-13:33 | 14.27 |
Annual Sum or Average | 0.342535E+10 | |||
Minimum of Months | 13755743.11 | 2070.99 | 14.27 | |
Maximum of Months | 0.108374E+10 | 4606.61 | 37.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379809E+09 | 4372.51 | 05-JAN-06:01 | -1.6 |
February | 0.149930E+09 | 3325.29 | 09-FEB-06:02 | 0.60 |
March | 49378733.35 | 2765.98 | 24-MAR-05:03 | 1.52 |
April | 17562708.18 | 1878.98 | 23-APR-14:50 | 22.20 |
May | 16810637.30 | 2872.77 | 31-MAY-04:03 | 26.32 |
June | 15696356.00 | 3113.51 | 09-JUN-05:02 | 23.80 |
July | 22546009.35 | 3223.90 | 26-JUL-04:02 | 25.82 |
August | 24393407.16 | 3345.81 | 08-AUG-04:02 | 25.00 |
September | 30032402.47 | 1970.10 | 10-SEP-15:42 | 31.10 |
October | 44291822.55 | 3470.07 | 02-OCT-04:02 | 24.82 |
November | 0.151629E+09 | 5271.31 | 16-NOV-06:03 | 1.70 |
December | 0.459248E+09 | 3020.01 | 08-DEC-06:02 | 1.28 |
Annual Sum or Average | 0.136133E+10 | |||
Minimum of Months | 15696356.00 | 1878.98 | -1.6 | |
Maximum of Months | 0.459248E+09 | 5271.31 | 31.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 688772.25 | 4591.81 | 17-JAN-07:03 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 1738114.36 | 9048.17 | 04-DEC-07:01 | -0.5 |
Annual Sum or Average | 2426886.60 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 1738114.36 | 9048.17 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130136E+09 | 17567.54 | 17-JAN-06:11 | 4.60 |
February | 28678933.06 | 16522.02 | 03-FEB-07:01 | -5.1 |
March | 6975374.73 | 16375.92 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 45928311.72 | 17377.51 | 28-NOV-06:01 | 1.02 |
December | 0.265431E+09 | 18689.72 | 04-DEC-06:02 | -1.0 |
Annual Sum or Average | 0.477150E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.265431E+09 | 18689.72 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.752470E+09 | 7877.52 | 09-JAN-06:11 | 3.17 |
February | 0.382336E+09 | 7651.73 | 03-FEB-06:01 | -3.7 |
March | 0.170913E+09 | 7484.15 | 02-MAR-06:01 | -3.5 |
April | 5393553.36 | 6272.07 | 12-APR-06:03 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 972860.36 | 4996.45 | 25-OCT-06:03 | 6.88 |
November | 0.272898E+09 | 7851.72 | 27-NOV-06:11 | 3.30 |
December | 0.107344E+10 | 8331.14 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.265842E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.107344E+10 | 8331.14 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349864E+09 | 5865.87 | 09-JAN-06:11 | 3.17 |
February | 0.136647E+09 | 5667.73 | 03-FEB-06:01 | -3.7 |
March | 68997925.80 | 5511.93 | 02-MAR-06:01 | -3.5 |
April | 1186226.23 | 2705.55 | 12-APR-06:03 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 1306070.58 | 4414.40 | 25-OCT-06:03 | 6.88 |
November | 0.106497E+09 | 5863.29 | 27-NOV-06:11 | 3.30 |
December | 0.482433E+09 | 6282.77 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.114693E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.482433E+09 | 6282.77 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396942E+09 | 7928.39 | 09-JAN-06:11 | 3.17 |
February | 0.189471E+09 | 7728.96 | 03-FEB-06:01 | -3.7 |
March | 0.106571E+09 | 7701.95 | 02-MAR-06:01 | -3.5 |
April | 5390773.54 | 6410.64 | 12-APR-06:03 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 495159.74 | 3301.06 | 25-OCT-06:03 | 6.88 |
November | 0.129761E+09 | 8026.80 | 27-NOV-06:11 | 3.30 |
December | 0.536177E+09 | 8441.85 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.136481E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.536177E+09 | 8441.85 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431651E+09 | 6122.64 | 09-JAN-06:11 | 3.17 |
February | 0.227543E+09 | 5872.52 | 03-FEB-06:01 | -3.7 |
March | 96639544.30 | 5750.68 | 02-MAR-06:01 | -3.5 |
April | 4346742.86 | 4528.25 | 11-APR-06:03 | 4.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 987355.49 | 3784.00 | 25-OCT-06:03 | 6.88 |
November | 0.159361E+09 | 6135.29 | 27-NOV-06:11 | 3.30 |
December | 0.605503E+09 | 6500.56 | 04-DEC-05:01 | -0.7 |
Annual Sum or Average | 0.152603E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.605503E+09 | 6500.56 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109771E+09 | 5139.58 | 28-JAN-06:01 | -3.3 |
February | 78861886.69 | 5160.98 | 03-FEB-06:01 | -3.7 |
March | 41437772.38 | 5169.30 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 6028319.84 | 4811.36 | 28-NOV-07:02 | 0.87 |
December | 0.130733E+09 | 5156.80 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.366832E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.130733E+09 | 5169.30 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35030922.94 | 3699.32 | 28-JAN-06:01 | -3.3 |
February | 16252141.13 | 3704.83 | 03-FEB-06:01 | -3.7 |
March | 9584507.63 | 3726.92 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1040392.83 | 3433.02 | 28-NOV-07:02 | 0.87 |
December | 41463337.12 | 3830.51 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.103371E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 41463337.12 | 3830.51 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614484E+09 | 6891.27 | 27-JAN-07:10 | -4.3 |
February | 0.515405E+09 | 7098.24 | 03-FEB-07:10 | -5.1 |
March | 0.535286E+09 | 6720.71 | 02-MAR-07:10 | -1.6 |
April | 0.149804E+09 | 5708.57 | 12-APR-06:10 | 3.87 |
May | 13057522.48 | 4799.36 | 02-MAY-06:10 | 9.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 1095895.32 | 2023.89 | 25-SEP-06:07 | 10.55 |
October | 64012323.15 | 5018.19 | 25-OCT-06:10 | 6.88 |
November | 0.362804E+09 | 6176.07 | 28-NOV-07:10 | 0.87 |
December | 0.679088E+09 | 7524.67 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 0.293504E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.679088E+09 | 7524.67 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38443086.37 | 3594.52 | 27-JAN-07:01 | -4.3 |
February | 28540706.90 | 3598.83 | 03-FEB-07:01 | -5.1 |
March | 11155399.40 | 3715.51 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 2462375.69 | 3499.06 | 28-NOV-07:02 | 0.87 |
December | 48317941.45 | 3848.38 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.128920E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 48317941.45 | 3848.38 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142898E+09 | 5705.76 | 28-JAN-06:01 | -3.3 |
February | 58883154.39 | 5546.88 | 02-FEB-06:01 | -3.5 |
March | 18567706.65 | 5521.14 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 32288084.72 | 5656.77 | 28-NOV-06:01 | 1.02 |
December | 0.249200E+09 | 5959.08 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.501837E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.249200E+09 | 5959.08 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73779146.67 | 4310.51 | 28-JAN-06:01 | -3.3 |
February | 23211350.06 | 4157.43 | 02-FEB-06:01 | -3.5 |
March | 10602105.06 | 4132.06 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 12160383.20 | 4306.26 | 28-NOV-06:01 | 1.02 |
December | 0.119398E+09 | 4604.91 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.239151E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.119398E+09 | 4604.91 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61596931.82 | 5658.60 | 17-JAN-06:11 | 4.60 |
February | 23660487.54 | 5448.34 | 03-FEB-07:01 | -5.1 |
March | 8273690.38 | 5426.71 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 10861059.11 | 5737.41 | 28-NOV-06:01 | 1.02 |
December | 0.109962E+09 | 6147.35 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.214354E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.109962E+09 | 6147.35 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83901778.72 | 4269.85 | 28-JAN-06:01 | -3.3 |
February | 37312520.82 | 4123.24 | 02-FEB-06:01 | -3.5 |
March | 11701752.75 | 4085.06 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 19612928.94 | 4270.66 | 28-NOV-06:01 | 1.02 |
December | 0.140522E+09 | 4655.20 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.293051E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.140522E+09 | 4655.20 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599791E+10 | 6443.98 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.544142E+10 | 6443.98 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.648083E+10 | 6443.98 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.577357E+10 | 6443.98 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.623937E+10 | 6443.98 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.621476E+10 | 6443.98 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.579818E+10 | 6443.98 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.648074E+10 | 6443.98 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.577357E+10 | 6443.98 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.599800E+10 | 6443.98 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.593174E+10 | 6443.98 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.579827E+10 | 6443.98 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.719283E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.544142E+10 | 6443.98 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.648083E+10 | 6443.98 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826419E+09 | 1358.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.712558E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.787597E+09 | 1184.79 | 10-MAR-16:40 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.663389E+09 | 947.97 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.703123E+09 | 711.15 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.691477E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.653630E+09 | 947.97 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745427E+09 | 947.97 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687145E+09 | 947.97 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.754067E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.807904E+09 | 1358.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.808517E+09 | 1358.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.884126E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.653630E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.826419E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505103E+09 | 860.01 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.442335E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.493341E+09 | 750.07 | 10-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.422984E+09 | 490.21 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451243E+09 | 450.21 | 02-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.444979E+09 | 450.21 | 02-JUN-14:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420573E+09 | 490.21 | 03-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.475141E+09 | 490.21 | 16-AUG-15:20 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.429360E+09 | 450.21 | 01-SEP-15:39 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468855E+09 | 750.07 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.499316E+09 | 860.01 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.497535E+09 | 860.01 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555077E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.420573E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505103E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.754699E+09 | 1358.45 | 17-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.672204E+09 | 1184.79 | 13-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.768324E+09 | 1184.79 | 10-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.668115E+09 | 947.97 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.713054E+09 | 711.15 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.703739E+09 | 711.15 | 19-JUN-15:00 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.666090E+09 | 947.97 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751460E+09 | 947.97 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676525E+09 | 774.31 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.722623E+09 | 1358.45 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.743649E+09 | 1358.45 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.744148E+09 | 1358.45 | 01-DEC-16:49 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.858463E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.666090E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.768324E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.491623E+09 | 859.95 | 17-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.432605E+09 | 750.02 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490339E+09 | 750.02 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.421608E+09 | 600.10 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446327E+09 | 490.17 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439636E+09 | 450.19 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.416423E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474407E+09 | 600.10 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.432166E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465478E+09 | 859.95 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479023E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.481974E+09 | 859.95 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547161E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.416423E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.491623E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.820269E+09 | 1358.45 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.708477E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.784194E+09 | 1184.79 | 10-MAR-16:49 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.662435E+09 | 947.97 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.702757E+09 | 711.15 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.690911E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.652831E+09 | 947.97 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.743807E+09 | 774.31 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.684535E+09 | 947.97 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.750421E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.802182E+09 | 1358.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.803131E+09 | 1358.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.880595E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.652831E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.820269E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503177E+09 | 860.01 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.440975E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.491766E+09 | 750.07 | 10-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.422234E+09 | 490.21 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.450460E+09 | 450.21 | 02-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.444581E+09 | 450.21 | 02-JUN-14:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.419672E+09 | 490.21 | 03-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474349E+09 | 490.21 | 16-AUG-15:20 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.428378E+09 | 450.21 | 01-SEP-15:50 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.467705E+09 | 750.07 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.497232E+09 | 860.01 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.495783E+09 | 860.01 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.553631E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.419672E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.503177E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.751908E+09 | 1358.45 | 17-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.670909E+09 | 1184.79 | 13-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.766750E+09 | 1184.79 | 10-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.666738E+09 | 947.97 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.711948E+09 | 711.15 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.702618E+09 | 647.98 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.664652E+09 | 947.97 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.749398E+09 | 947.97 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.675325E+09 | 711.15 | 01-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.721677E+09 | 1184.79 | 02-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.742145E+09 | 1358.45 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.743554E+09 | 1358.45 | 01-DEC-16:49 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.856762E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.664652E+09 | 647.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.766750E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489743E+09 | 859.95 | 17-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.431455E+09 | 750.02 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.488992E+09 | 750.02 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.420760E+09 | 600.10 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.445709E+09 | 490.17 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439032E+09 | 450.19 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.415608E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.473124E+09 | 600.10 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.430582E+09 | 600.10 | 05-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.464533E+09 | 859.95 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.477328E+09 | 859.95 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.480733E+09 | 859.95 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.545760E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.415608E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.489743E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826419E+09 | 1358.45 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.712558E+09 | 1184.79 | 01-FEB-16:49 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.787595E+09 | 1184.79 | 10-MAR-16:40 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.663389E+09 | 947.97 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.703123E+09 | 711.15 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.691477E+09 | 647.98 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.653630E+09 | 947.97 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.745427E+09 | 947.97 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.687145E+09 | 947.97 | 05-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.754067E+09 | 1358.45 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.807866E+09 | 1358.45 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.808517E+09 | 1358.45 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.884122E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.653630E+09 | 647.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.826419E+09 | 1358.45 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505103E+09 | 860.01 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.442335E+09 | 750.07 | 01-FEB-16:49 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.493341E+09 | 750.07 | 10-MAR-16:40 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.422984E+09 | 490.21 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.451247E+09 | 450.21 | 02-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.444979E+09 | 450.21 | 02-JUN-14:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.420573E+09 | 490.21 | 03-JUL-15:20 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.475141E+09 | 490.21 | 16-AUG-15:20 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.429360E+09 | 450.21 | 01-SEP-15:39 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.468855E+09 | 750.07 | 02-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.499316E+09 | 860.01 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.497511E+09 | 860.01 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.555075E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.420573E+09 | 450.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505103E+09 | 860.01 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.754661E+09 | 1358.45 | 17-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.672204E+09 | 1184.79 | 13-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.768324E+09 | 1184.79 | 10-MAR-16:49 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.668115E+09 | 947.97 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.713054E+09 | 711.15 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.703739E+09 | 711.15 | 19-JUN-15:00 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.666090E+09 | 947.97 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.751460E+09 | 947.97 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.676525E+09 | 774.31 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.722623E+09 | 1358.45 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.743649E+09 | 1358.45 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.744148E+09 | 1358.45 | 01-DEC-16:49 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.858459E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.666090E+09 | 711.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.768324E+09 | 1358.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.491623E+09 | 859.95 | 17-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.432601E+09 | 750.02 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.490339E+09 | 750.02 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.421608E+09 | 600.10 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.446327E+09 | 490.17 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.439636E+09 | 450.19 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.416423E+09 | 600.10 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.474407E+09 | 600.10 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.432166E+09 | 600.10 | 01-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.465478E+09 | 859.95 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.479023E+09 | 859.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.481974E+09 | 859.95 | 01-DEC-16:49 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.547161E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.416423E+09 | 450.19 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.491623E+09 | 859.95 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.599791E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.577357E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.623937E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.621476E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.579818E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.648074E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.577357E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.599800E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.593174E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.579827E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.719283E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.544142E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.648083E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.826419E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244652E+09 |
February | 0.901968E+09 | 0.712558E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86345.53 | 0.211137E+09 |
March | 0.107774E+10 | 0.787597E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138736.37 | 0.224185E+09 |
April | 0.956342E+09 | 0.663389E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14236011.45 | 0.125115E+09 |
May | 0.103597E+10 | 0.703123E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39132344.55 | 71667919.43 |
June | 0.103308E+10 | 0.691477E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60220159.05 | 27497156.47 |
July | 0.959235E+09 | 0.653630E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49858607.50 | 21021425.13 |
August | 0.107774E+10 | 0.745427E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40419103.26 | 27080854.67 |
September | 0.956342E+09 | 0.687145E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13290721.77 | 35269594.69 |
October | 0.994195E+09 | 0.754067E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5034315.64 | 0.108772E+09 |
November | 0.984487E+09 | 0.807904E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202108E+09 |
December | 0.959235E+09 | 0.808517E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211782E+09 |
Annual Sum or Average | 0.119305E+11 | 0.884126E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222416E+09 | 0.151029E+10 |
Minimum of Months | 0.901968E+09 | 0.653630E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21021425.13 |
Maximum of Months | 0.107774E+10 | 0.826419E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60220159.05 | 0.244652E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.505103E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166864E+09 |
February | 0.571020E+09 | 0.442335E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939.16 | 0.144881E+09 |
March | 0.682301E+09 | 0.493341E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49337.49 | 0.157181E+09 |
April | 0.605444E+09 | 0.422984E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8752371.22 | 87114391.42 |
May | 0.655854E+09 | 0.451243E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25902695.95 | 49586482.62 |
June | 0.654023E+09 | 0.444979E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40059773.87 | 18711277.08 |
July | 0.607275E+09 | 0.420573E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33272877.87 | 14442471.40 |
August | 0.682301E+09 | 0.475141E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26563762.19 | 18720498.91 |
September | 0.605444E+09 | 0.429360E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8392533.50 | 24989485.77 |
October | 0.629407E+09 | 0.468855E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2992577.26 | 75372399.40 |
November | 0.623262E+09 | 0.499316E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139864E+09 |
December | 0.607275E+09 | 0.497535E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144383E+09 |
Annual Sum or Average | 0.755301E+10 | 0.555077E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145987E+09 | 0.104211E+10 |
Minimum of Months | 0.571020E+09 | 0.420573E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14442471.40 |
Maximum of Months | 0.682301E+09 | 0.505103E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40059773.87 | 0.166864E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.754699E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271293E+09 |
February | 0.901968E+09 | 0.672204E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231658E+09 |
March | 0.107774E+10 | 0.768324E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72999.22 | 0.246679E+09 |
April | 0.956342E+09 | 0.668115E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11851467.58 | 0.130337E+09 |
May | 0.103597E+10 | 0.713054E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38969586.54 | 71278564.85 |
June | 0.103308E+10 | 0.703739E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61139312.02 | 26944300.35 |
July | 0.959235E+09 | 0.666090E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50626485.15 | 20508751.60 |
August | 0.107774E+10 | 0.751460E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39663486.83 | 27584146.41 |
September | 0.956342E+09 | 0.676525E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11885313.85 | 38261852.36 |
October | 0.994195E+09 | 0.722623E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3693920.38 | 0.121301E+09 |
November | 0.984487E+09 | 0.743649E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225412E+09 |
December | 0.959235E+09 | 0.744148E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233974E+09 |
Annual Sum or Average | 0.119305E+11 | 0.858463E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217903E+09 | 0.164523E+10 |
Minimum of Months | 0.901968E+09 | 0.666090E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20508751.60 |
Maximum of Months | 0.107774E+10 | 0.768324E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61139312.02 | 0.271293E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.491623E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168389E+09 |
February | 0.570983E+09 | 0.432605E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145679E+09 |
March | 0.682256E+09 | 0.490339E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57421.88 | 0.157830E+09 |
April | 0.605404E+09 | 0.421608E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7882591.90 | 87739769.67 |
May | 0.655811E+09 | 0.446327E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24623265.05 | 49933327.41 |
June | 0.653980E+09 | 0.439636E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39363080.38 | 19484529.63 |
July | 0.607235E+09 | 0.416423E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32864488.20 | 15081993.00 |
August | 0.682256E+09 | 0.474407E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26012739.89 | 18940255.34 |
September | 0.605404E+09 | 0.432166E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8473990.78 | 25251362.61 |
October | 0.629366E+09 | 0.465478E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2723001.69 | 76533094.43 |
November | 0.623221E+09 | 0.479023E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139889E+09 |
December | 0.607235E+09 | 0.481974E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145613E+09 |
Annual Sum or Average | 0.755252E+10 | 0.547161E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142001E+09 | 0.105036E+10 |
Minimum of Months | 0.570983E+09 | 0.416423E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15081993.00 |
Maximum of Months | 0.682256E+09 | 0.491623E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39363080.38 | 0.168389E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.820269E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141991E+09 |
February | 0.901968E+09 | 0.708477E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140790.34 | 0.116832E+09 |
March | 0.107774E+10 | 0.784194E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120335.70 | 0.119216E+09 |
April | 0.956342E+09 | 0.662435E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8980723.72 | 64640859.12 |
May | 0.103597E+10 | 0.702757E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23675687.14 | 36279029.48 |
June | 0.103308E+10 | 0.690911E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34739753.06 | 13114897.67 |
July | 0.959235E+09 | 0.652831E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28546237.08 | 10506577.25 |
August | 0.107774E+10 | 0.743807E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22629027.78 | 14855609.89 |
September | 0.956342E+09 | 0.684535E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7371140.97 | 20361218.30 |
October | 0.994195E+09 | 0.750421E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3032320.39 | 64483413.10 |
November | 0.984487E+09 | 0.802182E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122231E+09 |
December | 0.959235E+09 | 0.803131E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126221E+09 |
Annual Sum or Average | 0.119305E+11 | 0.880595E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129236E+09 | 0.850732E+09 |
Minimum of Months | 0.901968E+09 | 0.652831E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10506577.25 |
Maximum of Months | 0.107774E+10 | 0.820269E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34739753.06 | 0.141991E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.503177E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98376028.41 |
February | 0.571020E+09 | 0.440975E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.77 | 82414146.08 |
March | 0.682301E+09 | 0.491766E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33682.01 | 86630316.22 |
April | 0.605444E+09 | 0.422234E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4774814.85 | 47715887.68 |
May | 0.655854E+09 | 0.450460E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14445264.03 | 26734113.59 |
June | 0.654023E+09 | 0.444581E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22001705.80 | 9691777.65 |
July | 0.607275E+09 | 0.419672E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18009176.75 | 7856213.56 |
August | 0.682301E+09 | 0.474349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14191592.14 | 10891020.92 |
September | 0.605444E+09 | 0.428378E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4480332.41 | 14936239.16 |
October | 0.629407E+09 | 0.467705E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1732024.15 | 45503560.15 |
November | 0.623262E+09 | 0.497232E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86000576.88 |
December | 0.607275E+09 | 0.495783E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87455920.40 |
Annual Sum or Average | 0.755301E+10 | 0.553631E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79668671.92 | 0.604206E+09 |
Minimum of Months | 0.571020E+09 | 0.419672E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7856213.56 |
Maximum of Months | 0.682301E+09 | 0.503177E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22001705.80 | 98376028.41 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.751908E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306989E+10 |
February | 0.901968E+09 | 0.670909E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246386E+10 |
March | 0.107774E+10 | 0.766750E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3873202.80 | 0.228259E+10 |
April | 0.956342E+09 | 0.666738E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248934E+09 | 0.984247E+09 |
May | 0.103597E+10 | 0.711948E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693671E+09 | 0.398215E+09 |
June | 0.103308E+10 | 0.702618E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136007E+10 | 0.143983E+09 |
July | 0.959235E+09 | 0.664652E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111499E+10 | 98110156.64 |
August | 0.107774E+10 | 0.749398E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951255E+09 | 0.243978E+09 |
September | 0.956342E+09 | 0.675325E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664412E+09 | 0.380743E+09 |
October | 0.994195E+09 | 0.721677E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142659E+09 | 0.109613E+10 |
November | 0.984487E+09 | 0.742145E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233484E+10 |
December | 0.959235E+09 | 0.743554E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324321E+10 |
Annual Sum or Average | 0.119305E+11 | 0.856762E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517987E+10 | 0.167398E+11 |
Minimum of Months | 0.901968E+09 | 0.664652E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98110156.64 |
Maximum of Months | 0.107774E+10 | 0.766750E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136007E+10 | 0.324321E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.489743E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98944762.76 |
February | 0.570983E+09 | 0.431455E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82320479.31 |
March | 0.682256E+09 | 0.488992E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34823.17 | 87138280.85 |
April | 0.605404E+09 | 0.420760E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4193656.93 | 48129376.05 |
May | 0.655811E+09 | 0.445709E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13541625.51 | 27329383.41 |
June | 0.653980E+09 | 0.439032E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21434526.62 | 10200664.83 |
July | 0.607235E+09 | 0.415608E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17614018.15 | 8283134.80 |
August | 0.682256E+09 | 0.473124E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13774194.78 | 11213500.00 |
September | 0.605404E+09 | 0.430582E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4420147.35 | 15213879.92 |
October | 0.629366E+09 | 0.464533E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591210.74 | 46783880.25 |
November | 0.623221E+09 | 0.477328E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86253209.01 |
December | 0.607235E+09 | 0.480733E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87471628.91 |
Annual Sum or Average | 0.755252E+10 | 0.545760E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76604203.24 | 0.609282E+09 |
Minimum of Months | 0.570983E+09 | 0.415608E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8283134.80 |
Maximum of Months | 0.682256E+09 | 0.489743E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21434526.62 | 98944762.76 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.826419E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221992E+09 |
February | 0.901968E+09 | 0.712558E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42181.28 | 0.189915E+09 |
March | 0.107774E+10 | 0.787595E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94474.82 | 0.199895E+09 |
April | 0.956342E+09 | 0.663389E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12287020.53 | 0.110288E+09 |
May | 0.103597E+10 | 0.703123E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33519283.37 | 62980773.56 |
June | 0.103308E+10 | 0.691477E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51037836.25 | 23542894.75 |
July | 0.959235E+09 | 0.653630E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42544710.33 | 17821497.55 |
August | 0.107774E+10 | 0.745427E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34333851.62 | 23572526.84 |
September | 0.956342E+09 | 0.687145E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11380352.34 | 31099136.02 |
October | 0.994195E+09 | 0.754067E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4289935.98 | 97866143.82 |
November | 0.984487E+09 | 0.807866E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185483E+09 |
December | 0.959235E+09 | 0.808517E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193051E+09 |
Annual Sum or Average | 0.119305E+11 | 0.884122E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189530E+09 | 0.135751E+10 |
Minimum of Months | 0.901968E+09 | 0.653630E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17821497.55 |
Maximum of Months | 0.107774E+10 | 0.826419E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51037836.25 | 0.221992E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.505103E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150771E+09 |
February | 0.421807E+09 | 0.442335E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129426E+09 |
March | 0.502994E+09 | 0.493341E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43862.53 | 0.138684E+09 |
April | 0.447140E+09 | 0.422984E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7571061.38 | 75942016.02 |
May | 0.484071E+09 | 0.451247E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22106382.06 | 43262618.80 |
June | 0.482240E+09 | 0.444979E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33968234.63 | 15985675.97 |
July | 0.448971E+09 | 0.420573E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28285017.61 | 12212304.32 |
August | 0.502994E+09 | 0.475141E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22530103.98 | 16213063.82 |
September | 0.447140E+09 | 0.429360E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7206792.05 | 21794109.46 |
October | 0.465148E+09 | 0.468855E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2586285.30 | 67043094.68 |
November | 0.460569E+09 | 0.499316E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127161E+09 |
December | 0.448971E+09 | 0.497511E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131132E+09 |
Annual Sum or Average | 0.557719E+10 | 0.555075E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124298E+09 | 0.929627E+09 |
Minimum of Months | 0.421807E+09 | 0.420573E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12212304.32 |
Maximum of Months | 0.502994E+09 | 0.505103E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33968234.63 | 0.150771E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.754661E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243618E+09 |
February | 0.901968E+09 | 0.672204E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206336E+09 |
March | 0.107774E+10 | 0.768324E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63968.40 | 0.217653E+09 |
April | 0.956342E+09 | 0.668115E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10042464.77 | 0.114643E+09 |
May | 0.103597E+10 | 0.713054E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32892853.69 | 62964652.23 |
June | 0.103308E+10 | 0.703739E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51577921.41 | 23158061.71 |
July | 0.959235E+09 | 0.666090E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42769532.18 | 17486380.90 |
August | 0.107774E+10 | 0.751460E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33365280.60 | 24081866.73 |
September | 0.956342E+09 | 0.676525E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10001636.57 | 33640303.22 |
October | 0.994195E+09 | 0.722623E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3089755.69 | 0.107617E+09 |
November | 0.984487E+09 | 0.743649E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203357E+09 |
December | 0.959235E+09 | 0.744148E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211065E+09 |
Annual Sum or Average | 0.119305E+11 | 0.858459E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183803E+09 | 0.146562E+10 |
Minimum of Months | 0.901968E+09 | 0.666090E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17486380.90 |
Maximum of Months | 0.107774E+10 | 0.768324E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51577921.41 | 0.243618E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.491623E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151845E+09 |
February | 0.570983E+09 | 0.432601E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130255E+09 |
March | 0.682256E+09 | 0.490339E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44060.74 | 0.139895E+09 |
April | 0.605404E+09 | 0.421608E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6609490.15 | 77314341.66 |
May | 0.655811E+09 | 0.446327E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20568243.19 | 44098851.96 |
June | 0.653980E+09 | 0.439636E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32942392.62 | 16742788.93 |
July | 0.607235E+09 | 0.416423E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27563456.49 | 12861336.06 |
August | 0.682256E+09 | 0.474407E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21762078.08 | 16536420.20 |
September | 0.605404E+09 | 0.432166E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7044166.03 | 22225928.74 |
October | 0.629366E+09 | 0.465478E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2268557.65 | 68574539.89 |
November | 0.623221E+09 | 0.479023E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127477E+09 |
December | 0.607235E+09 | 0.481974E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131916E+09 |
Annual Sum or Average | 0.755252E+10 | 0.547161E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118802E+09 | 0.939743E+09 |
Minimum of Months | 0.570983E+09 | 0.416423E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12861336.06 |
Maximum of Months | 0.682256E+09 | 0.491623E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32942392.62 | 0.151845E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325904E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276380E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28167.03 | 0.288677E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12547767.53 | 0.155795E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38848983.00 | 86625605.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62352764.03 | 30330794.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51484729.31 | 22598817.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40395740.77 | 31910600.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11675034.52 | 44492591.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4272943.66 | 0.143490E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274821E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285298E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221606E+09 | 0.196632E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22598817.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62352764.03 | 0.325904E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391564E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338457E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53015.88 | 0.357104E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17304698.48 | 0.196420E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50351721.55 | 0.110062E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80016714.03 | 39123864.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66388203.78 | 28673261.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52657228.11 | 40071003.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15800117.38 | 54936311.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6052115.70 | 0.175149E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331934E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341163E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288624E+09 | 0.240466E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28673261.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80016714.03 | 0.391564E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380411E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330606E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358985E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11635976.92 | 0.193047E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43680985.08 | 0.102257E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79965975.42 | 36401146.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63880419.80 | 27584674.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51182017.07 | 37250948.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12561143.13 | 53201666.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4718038.94 | 0.171846E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315811E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325836E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267625E+09 | 0.233324E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27584674.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79965975.42 | 0.380411E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 6443.98 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 6443.98 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 6443.98 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 6443.98 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 6443.98 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 6443.98 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 6443.98 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 6443.98 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 6443.98 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 6443.98 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 6443.98 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 6443.98 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 689.41 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 20-FEB-15:43 | 878.00 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:40 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 19-MAR-14:15 | 649.24 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.39 | 01-APR-17:20 | 716.29 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.91 | 14-MAY-15:57 | 330.27 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.87 | 10-JUN-17:02 | 263.91 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.31 | 02-JUL-21:10 | 131.31 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.22 | 26-AUG-18:00 | 228.64 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 10-SEP-14:53 | 127.73 | 23-SEP-17:10 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.81 | 01-OCT-15:00 | 326.57 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.90 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 515.90 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.73 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 272.31 | 878.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 458.20 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 | 20-FEB-15:43 | 585.89 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 10-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 | 22-MAR-13:00 | 448.72 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.37 | 01-APR-17:20 | 477.12 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 02-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.53 | 14-MAY-16:00 | 217.54 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 02-JUN-14:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.24 | 10-JUN-17:02 | 175.47 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 03-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.59 | 02-JUL-21:15 | 87.10 | 18-JUL-21:10 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 16-AUG-15:20 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.21 | 26-AUG-17:50 | 153.83 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 01-SEP-15:39 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.01 | 10-SEP-14:53 | 104.28 | 24-SEP-10:30 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.37 | 01-OCT-15:00 | 217.52 | 23-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 304.72 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 346.39 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.10 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 189.59 | 585.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 17-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 700.25 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 13-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 897.99 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 22-MAR-13:00 | 696.78 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.68 | 01-APR-17:20 | 722.79 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.36 | 14-MAY-15:55 | 331.82 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-15:00 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.03 | 10-JUN-17:02 | 262.37 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.51 | 02-JUL-21:15 | 131.57 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.78 | 26-AUG-18:00 | 232.24 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.98 | 10-SEP-15:26 | 146.49 | 24-SEP-10:47 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.85 | 01-OCT-14:55 | 344.12 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 457.15 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:49 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 547.87 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.57 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 276.51 | 897.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 17-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 457.54 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 587.70 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 22-MAR-13:00 | 449.86 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.06 | 21-APR-15:00 | 478.73 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.00 | 14-MAY-16:00 | 223.49 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.24 | 04-JUN-19:10 | 181.76 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.90 | 02-JUL-21:15 | 107.73 | 04-JUL-18:53 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.62 | 27-AUG-12:53 | 157.70 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 | 10-SEP-14:45 | 91.62 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.65 | 01-OCT-14:55 | 223.83 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 275.77 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 349.99 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 185.90 | 587.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 396.35 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 20-FEB-16:00 | 495.60 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:49 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 26-MAR-17:00 | 362.53 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 | 01-APR-17:03 | 400.26 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.46 | 14-MAY-15:50 | 177.01 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.27 | 04-JUN-18:53 | 137.71 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.13 | 02-JUL-21:20 | 69.92 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 774.31 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.47 | 26-AUG-18:00 | 119.66 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 | 10-SEP-15:10 | 72.86 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 | 01-OCT-14:52 | 191.97 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 250.54 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 324.95 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.92 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 159.13 | 495.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 860.01 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 266.44 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 20-FEB-15:40 | 338.54 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 750.07 | 10-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 22-MAR-13:00 | 261.62 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 490.21 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.31 | 01-APR-17:03 | 274.59 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 450.21 | 02-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.16 | 14-MAY-15:50 | 120.03 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 450.21 | 02-JUN-14:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.64 | 04-JUN-18:53 | 94.70 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 490.21 | 03-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.87 | 02-JUL-21:15 | 48.61 | 04-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 490.21 | 16-AUG-15:20 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.65 | 26-AUG-17:50 | 84.91 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 450.21 | 01-SEP-15:50 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 10-SEP-15:10 | 56.19 | 24-SEP-10:00 |
October | 827.22 | 02-OCT-09:09 | 750.07 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.92 | 01-OCT-14:52 | 131.81 | 24-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 860.01 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 189.74 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 860.01 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 223.34 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.61 | |||||
Maximum of Months | 827.22 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 103.87 | 338.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 17-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 18541.97 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 13-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 19147.46 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 632.09 | 21-MAR-16:10 | 16430.52 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4908.96 | 19-APR-16:10 | 11977.80 | 12-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7239.16 | 19-MAY-16:10 | 8233.94 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9621.92 | 02-JUN-16:03 | 4154.43 | 13-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9276.06 | 03-JUL-16:03 | 3911.91 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8523.17 | 07-AUG-16:03 | 4645.48 | 31-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 711.15 | 01-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6356.40 | 19-SEP-16:03 | 8948.61 | 25-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1184.79 | 02-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4284.14 | 04-OCT-16:05 | 10942.20 | 11-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15311.83 | 17-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:49 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18518.09 | 27-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3911.91 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9621.92 | 19147.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 17-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 264.97 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 338.49 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 22-MAR-12:00 | 261.19 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 | 29-APR-17:03 | 274.83 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 | 14-MAY-15:25 | 124.38 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 | 04-JUN-18:53 | 98.76 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.46 | 02-JUL-21:15 | 56.69 | 04-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 | 27-AUG-12:53 | 87.81 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 05-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 10-SEP-15:04 | 49.28 | 24-SEP-07:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.25 | 01-OCT-15:05 | 134.27 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.74 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 225.54 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 101.46 | 338.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 614.68 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 01-FEB-16:49 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 20-FEB-15:43 | 784.10 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:40 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 19-MAR-14:00 | 590.47 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.67 | 01-APR-17:03 | 636.44 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.13 | 14-MAY-16:00 | 295.52 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 647.98 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.09 | 04-JUN-18:53 | 222.98 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.78 | 02-JUL-21:00 | 109.05 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.26 | 26-AUG-18:00 | 189.30 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 947.97 | 05-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.59 | 10-SEP-15:00 | 107.69 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.06 | 01-OCT-14:52 | 289.45 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 371.72 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 487.91 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.69 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 242.78 | 784.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 860.01 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 407.70 | 25-JAN-23:00 |
February | 805.43 | 01-FEB-08:09 | 750.07 | 01-FEB-16:49 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 521.67 | 09-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 750.07 | 10-MAR-16:40 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 22-MAR-13:00 | 405.92 | 19-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 490.21 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.78 | 01-APR-17:20 | 423.54 | 10-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 450.21 | 02-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.38 | 14-MAY-15:50 | 194.70 | 04-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 450.21 | 02-JUN-14:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.02 | 10-JUN-17:02 | 148.26 | 28-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 490.21 | 03-JUL-15:20 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.06 | 02-JUL-21:00 | 72.46 | 18-JUL-21:10 |
August | 805.43 | 01-AUG-07:10 | 490.21 | 16-AUG-15:20 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 | 26-AUG-17:50 | 127.49 | 14-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 450.21 | 01-SEP-15:39 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 10-SEP-15:20 | 88.69 | 24-SEP-10:07 |
October | 805.43 | 02-OCT-07:10 | 750.07 | 02-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.61 | 01-OCT-14:52 | 192.81 | 24-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 860.01 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 286.11 | 26-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 860.01 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 326.84 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 450.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.46 | |||||
Maximum of Months | 805.43 | 860.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 168.06 | 521.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1358.45 | 17-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 624.86 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 1184.79 | 13-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 800.44 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1184.79 | 10-MAR-16:49 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 22-MAR-13:00 | 628.69 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 947.97 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.97 | 01-APR-17:20 | 641.88 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 711.15 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.64 | 14-MAY-15:50 | 297.02 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 711.15 | 19-JUN-15:00 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.02 | 04-JUN-18:53 | 221.74 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 947.97 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.14 | 02-JUL-21:00 | 109.30 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 947.97 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 | 26-AUG-18:00 | 193.02 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 774.31 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.07 | 10-SEP-15:15 | 124.52 | 24-SEP-10:47 |
October | 1306.65 | 02-OCT-09:09 | 1358.45 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 01-OCT-15:05 | 300.35 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1358.45 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 429.03 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 1358.45 | 01-DEC-16:49 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.52 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 711.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.30 | |||||
Maximum of Months | 1306.65 | 1358.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 243.14 | 800.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 859.95 | 17-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 407.40 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 750.02 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 524.04 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 750.02 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 22-MAR-13:00 | 407.32 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 600.10 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 21-APR-15:00 | 425.34 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 490.17 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 14-MAY-15:44 | 199.94 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 450.19 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.14 | 04-JUN-18:53 | 153.45 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 600.10 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 02-JUL-21:00 | 89.07 | 04-JUL-18:57 |
August | 827.17 | 01-AUG-09:09 | 600.10 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 | 27-AUG-12:53 | 131.19 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 600.10 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 10-SEP-15:13 | 74.15 | 24-SEP-16:00 |
October | 827.17 | 02-OCT-09:09 | 859.95 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 01-OCT-15:05 | 196.34 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 859.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 255.39 | 26-NOV-16:55 |
December | 827.17 | 01-DEC-10:09 | 859.95 | 01-DEC-16:49 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 329.59 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 450.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.15 | |||||
Maximum of Months | 827.17 | 859.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 168.96 | 524.04 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 884.27 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1125.01 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 22-MAR-13:00 | 872.45 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.86 | 01-APR-17:03 | 902.55 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.98 | 14-MAY-15:52 | 413.19 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.00 | 04-JUN-18:53 | 303.66 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.14 | 02-JUL-21:20 | 148.79 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.98 | 27-AUG-12:53 | 254.20 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.02 | 10-SEP-14:53 | 152.26 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.40 | 01-OCT-14:52 | 414.79 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 548.19 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 734.15 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.14 | 1125.01 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1078.00 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1418.31 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.82 | 22-MAR-13:00 | 1067.95 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.21 | 01-APR-17:03 | 1144.45 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.30 | 14-MAY-16:00 | 517.24 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.48 | 04-JUN-18:53 | 390.43 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 02-JUL-21:20 | 192.58 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.50 | 26-AUG-17:02 | 327.05 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 | 10-SEP-15:00 | 187.26 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.75 | 01-OCT-14:52 | 517.73 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 649.85 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 871.59 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.27 | 1418.31 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1044.51 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1324.36 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.99 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.83 | 01-APR-17:03 | 1054.03 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.10 | 14-MAY-16:00 | 466.16 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.16 | 10-JUN-17:02 | 406.49 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.64 | 02-JUL-21:20 | 207.96 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.58 | 26-AUG-18:00 | 354.35 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 | 10-SEP-15:00 | 212.01 | 23-SEP-17:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.09 | 01-OCT-15:00 | 509.29 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 625.65 | 26-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 775.60 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.64 | 1324.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22953.41 | 05-JAN-06:01 | 4446.85 | 1482.14 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25103.29 | 22-FEB-07:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30587.80 | 17-MAR-06:02 | 6352.64 | 10740.11 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38215.05 | 10-APR-05:12 | 2541.06 | 2863.91 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40847.72 | 31-MAY-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41507.92 | 09-JUN-05:02 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41263.39 | 25-JUL-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40608.79 | 11-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40323.11 | 06-SEP-05:12 | 3176.32 | 3579.89 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39338.46 | 02-OCT-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36507.34 | 01-NOV-06:02 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17495.38 | 15-DEC-17:00 | 6035.01 | 6443.98 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17495.38 | 0.00 | 846.94 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41507.92 | 7623.17 | 12888.13 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3069.52 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
February | 4597.54 | 22-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5875.03 | 16-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 |
April | 9204.72 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 |
May | 11105.14 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 0.00 |
June | 11715.37 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.21 | 0.00 |
July | 12067.95 | 03-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.26 | 0.00 |
August | 11660.88 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 0.00 |
September | 10307.04 | 19-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 | 0.00 |
October | 9401.86 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | 0.00 |
November | 5216.57 | 03-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 |
December | 1734.43 | 09-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1734.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12067.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.21 | 55.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2157.13 | 05-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.74 |
February | 2514.15 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.66 |
March | 2584.02 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.80 |
April | 3518.45 | 21-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.65 | 0.00 |
May | 5215.60 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.38 | 0.00 |
June | 5530.54 | 19-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 0.00 |
July | 5798.32 | 03-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.38 | 0.00 |
August | 5567.64 | 07-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 0.00 |
September | 4945.72 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 0.00 |
October | 4244.71 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.99 | 0.00 |
November | 2286.03 | 10-NOV-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.38 |
December | 1991.05 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1991.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5798.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.65 | 133.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2609.42 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 |
February | 2764.90 | 16-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2681.96 | 17-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.02 |
April | 3739.85 | 21-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 | 0.00 |
May | 5384.42 | 30-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 0.00 |
June | 5887.54 | 05-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 0.00 |
July | 6974.88 | 03-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
August | 6150.62 | 21-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 0.00 |
September | 5643.73 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 |
October | 4511.43 | 03-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 0.00 |
November | 3161.93 | 10-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.78 |
December | 2456.44 | 21-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2456.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6974.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.15 | 105.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10245.86 | 13-JAN-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12017.57 | 22-FEB-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13663.73 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15942.34 | 21-APR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32181.00 | 30-MAY-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31972.25 | 07-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32540.48 | 25-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32473.96 | 08-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32627.23 | 05-SEP-05:12 | 2541.06 | 2863.91 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30663.22 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15112.49 | 10-NOV-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9024.23 | 15-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9024.23 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32627.23 | 6035.01 | 6443.98 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9335.34 | 12-JAN-16:50 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11407.07 | 22-FEB-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14699.02 | 16-MAR-16:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17814.47 | 28-APR-15:40 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28377.39 | 30-MAY-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34637.46 | 09-JUN-05:02 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34965.00 | 10-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34273.28 | 14-AUG-05:12 | 3176.32 | 3579.89 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23396.39 | 05-SEP-06:03 | 5082.11 | 8592.08 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31412.89 | 02-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14740.46 | 10-NOV-15:00 | 6198.29 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7214.00 | 15-DEC-17:00 | 6035.01 | 6443.98 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7214.00 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34965.00 | 6198.29 | 8592.08 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1537.39 | 12-JAN-14:30 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
February | 2112.29 | 22-FEB-15:00 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3387.78 | 22-MAR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
April | 5723.53 | 21-APR-15:00 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 105.09 | 0.00 |
May | 12719.21 | 21-MAY-15:11 | 468.72 | 251.99 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 | 0.00 |
June | 12655.40 | 18-JUN-15:42 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 85.72 | 0.00 |
July | 12730.50 | 02-JUL-16:22 | 401.76 | 215.99 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 87.72 | 0.00 |
August | 10928.87 | 07-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
September | 6124.81 | 20-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 0.00 |
October | 6556.40 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
November | 2818.31 | 09-NOV-15:40 | 1272.23 | 947.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
December | 1355.24 | 08-DEC-16:30 | 1272.23 | 1358.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1355.24 | 0.00 | 215.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12730.50 | 1306.65 | 1358.45 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 | 17.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1485.97 | 04-JAN-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 |
February | 2908.73 | 21-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
March | 4193.66 | 16-MAR-10:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 |
April | 10384.40 | 30-APR-10:53 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12021.86 | 21-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11724.41 | 18-JUN-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 0.00 |
July | 11807.64 | 02-JUL-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11769.78 | 06-AUG-09:32 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 0.00 |
September | 12133.04 | 17-SEP-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
October | 8611.50 | 01-OCT-09:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4630.47 | 10-NOV-09:20 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 |
December | 1272.26 | 01-DEC-10:20 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1272.26 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12133.04 | 827.22 | 410.22 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 59.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9366.83 | 12-JAN-14:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 |
February | 14519.71 | 20-FEB-14:13 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
March | 8726.31 | 16-MAR-13:30 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
April | 14390.86 | 30-APR-12:53 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 | 0.00 |
May | 14277.80 | 21-MAY-15:11 | 468.72 | 251.99 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 129.64 | 0.00 |
June | 12937.84 | 18-JUN-15:42 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 | 0.00 |
July | 14399.04 | 30-JUL-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 38.84 | 0.00 |
August | 14452.45 | 27-AUG-12:43 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 | 0.00 |
September | 14725.91 | 04-SEP-12:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
October | 15933.62 | 01-OCT-12:12 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
November | 11700.04 | 11-NOV-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.50 |
December | 7475.52 | 07-DEC-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7475.52 | 267.84 | 143.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15933.62 | 1306.65 | 647.98 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 | 134.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3600.75 | 12-JAN-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
February | 4997.85 | 19-FEB-16:23 | 169.55 | 91.15 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 |
March | 6198.27 | 21-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
April | 14636.43 | 16-APR-16:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
May | 14333.35 | 21-MAY-15:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 70.12 | 0.00 |
June | 13917.03 | 25-JUN-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 0.00 |
July | 13866.48 | 09-JUL-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | 0.00 |
August | 13892.15 | 06-AUG-16:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 77.11 | 0.00 |
September | 13639.27 | 17-SEP-15:42 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 0.00 |
October | 13806.74 | 01-OCT-14:52 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 67.58 | 0.00 |
November | 5639.37 | 09-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
December | 2683.83 | 15-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2683.83 | 169.55 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14636.43 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 77.11 | 44.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1363.35 | 13-JAN-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
February | 1453.01 | 23-FEB-14:40 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 |
March | 1585.54 | 22-MAR-14:40 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.00 |
April | 3870.43 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 0.00 |
May | 5133.38 | 30-MAY-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 0.00 |
June | 6243.17 | 19-JUN-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 8437.79 | 03-JUL-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
August | 8199.69 | 07-AUG-06:03 | 803.52 | 774.33 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 0.00 |
September | 5565.84 | 20-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
October | 5339.43 | 03-OCT-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 | 0.00 |
November | 2534.60 | 09-NOV-16:20 | 1272.23 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
December | 1338.12 | 01-DEC-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1338.12 | 803.52 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8437.79 | 1306.65 | 1184.79 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 | 28.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1527.75 | 04-JAN-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 |
February | 2573.89 | 21-FEB-10:30 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.07 |
March | 3041.67 | 31-MAR-09:50 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 |
April | 7498.83 | 30-APR-10:43 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
May | 10188.72 | 21-MAY-09:52 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8721.66 | 18-JUN-09:42 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 0.00 |
July | 10614.82 | 09-JUL-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
August | 10482.30 | 27-AUG-10:22 | 211.95 | 113.95 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 0.00 |
September | 10776.87 | 04-SEP-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
October | 5863.07 | 05-OCT-09:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
November | 4417.88 | 10-NOV-09:10 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
December | 1311.45 | 01-DEC-10:10 | 827.22 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1311.45 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10776.87 | 827.22 | 410.22 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 31.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8721.41 | 01-JAN-14:13 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.76 |
February | 10427.57 | 20-FEB-14:33 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 |
March | 5975.11 | 22-MAR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 85.41 | 0.00 |
April | 9532.21 | 19-APR-12:00 | 687.71 | 647.98 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4581.93 | 0.00 |
May | 10462.08 | 30-MAY-16:10 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6471.38 | 0.00 |
June | 10906.82 | 02-JUN-16:50 | 401.76 | 359.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8874.10 | 0.00 |
July | 10996.78 | 03-JUL-16:50 | 401.76 | 526.65 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8492.99 | 0.00 |
August | 11915.61 | 27-AUG-13:02 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 0.00 |
September | 12550.20 | 04-SEP-13:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | 0.00 |
October | 12684.42 | 22-OCT-12:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
November | 12556.72 | 11-NOV-13:22 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.59 |
December | 8242.72 | 17-DEC-13:33 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5975.11 | 200.88 | 107.99 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12684.42 | 1306.65 | 647.98 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8874.10 | 114.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2707.35 | 30-JAN-16:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 |
February | 3854.69 | 21-FEB-16:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 |
March | 3941.72 | 21-MAR-16:00 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 0.00 |
April | 11300.22 | 16-APR-16:21 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 0.00 |
May | 11415.26 | 21-MAY-15:11 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 42.57 | 0.00 |
June | 10961.90 | 04-JUN-16:22 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 |
July | 11155.55 | 09-JUL-17:01 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 |
August | 11566.86 | 27-AUG-17:42 | 0.00 | 136.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 0.00 |
September | 11286.38 | 04-SEP-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
October | 10991.91 | 22-OCT-16:22 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 5096.77 | 09-NOV-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
December | 2452.59 | 15-DEC-16:10 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2452.59 | 0.00 | 113.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11566.86 | 805.38 | 410.20 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 42.57 | 16.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1656.55 | 12-JAN-14:30 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.65 |
February | 2299.21 | 23-FEB-14:30 | 1306.65 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
March | 3240.64 | 22-MAR-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
April | 5180.78 | 21-APR-15:20 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 0.00 |
May | 8056.37 | 30-MAY-06:03 | 803.52 | 647.99 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
June | 11183.97 | 25-JUN-18:21 | 0.00 | 276.55 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 0.00 |
July | 10932.58 | 02-JUL-16:11 | 535.68 | 287.98 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 0.00 |
August | 9104.43 | 07-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 0.00 |
September | 5575.05 | 20-SEP-14:30 | 1272.23 | 647.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 0.00 |
October | 6687.06 | 02-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 |
November | 2844.37 | 09-NOV-16:20 | 1272.23 | 1184.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 |
December | 1354.59 | 08-DEC-15:00 | 1306.65 | 711.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1354.59 | 0.00 | 223.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11183.97 | 1306.65 | 1184.79 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 16.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2228.37 | 04-JAN-09:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.49 |
February | 3448.48 | 21-FEB-10:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.64 |
March | 4596.51 | 31-MAR-09:00 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.88 |
April | 10959.37 | 16-APR-08:32 | 169.56 | 91.16 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 |
May | 12048.19 | 29-MAY-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
June | 12136.93 | 18-JUN-08:52 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
July | 12019.08 | 09-JUL-09:02 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 |
August | 11923.97 | 20-AUG-09:12 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
September | 12080.73 | 04-SEP-08:32 | 254.35 | 136.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 |
October | 6691.44 | 05-OCT-08:40 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
November | 5076.47 | 10-NOV-08:50 | 805.43 | 410.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 |
December | 1499.58 | 07-DEC-09:25 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1499.58 | 169.56 | 91.16 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12136.93 | 1610.86 | 820.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 49.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9325.09 | 12-JAN-14:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 |
February | 12978.82 | 20-FEB-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.95 |
March | 8360.01 | 16-MAR-13:10 | 1306.65 | 647.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
April | 12087.24 | 30-APR-14:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
May | 9139.78 | 28-MAY-15:52 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 0.00 |
June | 12109.83 | 18-JUN-15:31 | 535.68 | 287.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 | 0.00 |
July | 12566.15 | 30-JUL-13:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 0.00 |
August | 12639.23 | 27-AUG-12:32 | 267.84 | 143.99 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 | 0.00 |
September | 13396.88 | 17-SEP-12:12 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 0.00 |
October | 14049.85 | 29-OCT-13:22 | 401.76 | 215.99 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.01 |
November | 13551.38 | 11-NOV-12:52 | 334.80 | 179.99 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.77 |
December | 8673.69 | 17-DEC-13:33 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8360.01 | 200.88 | 107.99 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14049.85 | 1306.65 | 647.98 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 115.46 | 132.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3648.28 | 12-JAN-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
February | 4870.12 | 21-FEB-16:40 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 |
March | 8768.56 | 26-MAR-17:03 | 0.00 | 91.15 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 |
April | 12109.59 | 30-APR-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 0.00 |
May | 12838.80 | 29-MAY-17:01 | 0.00 | 205.09 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 0.00 |
June | 13251.57 | 11-JUN-17:01 | 0.00 | 182.31 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 0.00 |
July | 12682.44 | 09-JUL-16:21 | 339.11 | 182.31 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 | 0.00 |
August | 12923.24 | 20-AUG-16:31 | 296.72 | 159.52 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 | 0.00 |
September | 12540.94 | 04-SEP-16:32 | 254.33 | 136.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
October | 12172.41 | 08-OCT-16:32 | 211.94 | 113.94 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 |
November | 5571.84 | 09-NOV-15:30 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
December | 2961.33 | 15-DEC-15:50 | 805.38 | 410.20 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2961.33 | 0.00 | 91.15 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13251.57 | 805.38 | 410.20 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 | 42.78 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.103892E+12 | 92299.95 | 03-JAN-16:00 | 0.159170E+11 | 128981.08 | 27-JAN-07:10 |
February | 0.956894E+11 | 100291.47 | 21-FEB-16:49 | 0.932336E+10 | 133258.10 | 03-FEB-07:10 |
March | 0.113353E+12 | 105894.18 | 21-MAR-15:00 | 0.556583E+10 | 116263.98 | 02-MAR-07:10 |
April | 0.120058E+12 | 138735.50 | 21-APR-15:09 | 0.592038E+09 | 41818.95 | 12-APR-06:10 |
May | 0.147652E+12 | 160696.36 | 30-MAY-14:50 | 41528559.55 | 13076.17 | 02-MAY-06:19 |
June | 0.167751E+12 | 170241.50 | 15-JUN-14:30 | 1863748.10 | 12.53 | 29-JUN-16:00 |
July | 0.168461E+12 | 179593.23 | 20-JUL-15:09 | 7092754.50 | 14.76 | 26-JUL-19:30 |
August | 0.168680E+12 | 162638.42 | 07-AUG-15:00 | 6917989.88 | 15.59 | 10-AUG-06:00 |
September | 0.147127E+12 | 149908.05 | 05-SEP-15:30 | 9731791.37 | 2280.14 | 25-SEP-06:10 |
October | 0.126578E+12 | 140051.56 | 05-OCT-15:00 | 0.228506E+09 | 21854.05 | 25-OCT-06:10 |
November | 0.106559E+12 | 111839.37 | 09-NOV-16:49 | 0.568744E+10 | 104986.74 | 28-NOV-07:10 |
December | 0.101688E+12 | 91461.62 | 08-DEC-16:00 | 0.224009E+11 | 148342.61 | 27-DEC-07:10 |
Annual Sum or Average | 0.156749E+13 | 0.597822E+11 | ||||
Minimum of Months | 0.956894E+11 | 91461.62 | 1863748.10 | 12.53 | ||
Maximum of Months | 0.168680E+12 | 179593.23 | 0.224009E+11 | 148342.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.257145E+11 | 0.537384E+10 | 0.605851E+11 | 0.225891E+10 | 0.477904E+10 | 87567774.58 | 0.00 | 0.621838E+09 | 0.00 | 0.00 | 0.00 | 0.447136E+10 | 0.00 |
February | 0.230955E+11 | 0.443448E+10 | 0.548702E+11 | 0.204960E+10 | 0.473398E+10 | 55787395.15 | 0.00 | 0.239127E+10 | 0.00 | 0.00 | 0.00 | 0.405856E+10 | 0.00 |
March | 0.270534E+11 | 0.433543E+10 | 0.627783E+11 | 0.235658E+10 | 0.634315E+10 | 40370661.17 | 0.00 | 0.582296E+10 | 0.00 | 0.00 | 0.00 | 0.462321E+10 | 0.00 |
April | 0.238451E+11 | 0.368213E+10 | 0.586172E+11 | 0.219330E+10 | 0.937064E+10 | 15459813.05 | 0.00 | 0.184153E+11 | 0.00 | 0.00 | 0.00 | 0.391841E+10 | 0.00 |
May | 0.256565E+11 | 0.337896E+10 | 0.616817E+11 | 0.230729E+10 | 0.147477E+11 | 12837911.22 | 0.00 | 0.359880E+11 | 0.00 | 0.00 | 0.00 | 0.387877E+10 | 0.00 |
June | 0.254811E+11 | 0.308173E+10 | 0.604966E+11 | 0.226949E+10 | 0.194717E+11 | 12243636.44 | 0.00 | 0.533717E+11 | 0.00 | 0.00 | 0.00 | 0.356680E+10 | 0.00 |
July | 0.238607E+11 | 0.329899E+10 | 0.597911E+11 | 0.223026E+10 | 0.186075E+11 | 12299387.05 | 0.00 | 0.574295E+11 | 0.00 | 0.00 | 0.00 | 0.323036E+10 | 0.00 |
August | 0.267758E+11 | 0.363867E+10 | 0.627783E+11 | 0.235635E+10 | 0.184859E+11 | 12714637.45 | 0.00 | 0.510805E+11 | 0.00 | 0.00 | 0.00 | 0.355219E+10 | 0.00 |
September | 0.239899E+11 | 0.393727E+10 | 0.585950E+11 | 0.219216E+10 | 0.146542E+11 | 12013203.65 | 0.00 | 0.403795E+11 | 0.00 | 0.00 | 0.00 | 0.336674E+10 | 0.00 |
October | 0.252204E+11 | 0.466421E+10 | 0.605962E+11 | 0.225948E+10 | 0.101746E+11 | 13900060.50 | 0.00 | 0.199034E+11 | 0.00 | 0.00 | 0.00 | 0.374532E+10 | 0.00 |
November | 0.253739E+11 | 0.503684E+10 | 0.591197E+11 | 0.220143E+10 | 0.632527E+10 | 39832450.10 | 0.00 | 0.448067E+10 | 0.00 | 0.00 | 0.00 | 0.398127E+10 | 0.00 |
December | 0.249823E+11 | 0.550349E+10 | 0.597800E+11 | 0.223015E+10 | 0.463336E+10 | 0.117588E+09 | 0.00 | 0.233713E+09 | 0.00 | 0.00 | 0.00 | 0.420699E+10 | 0.00 |
Annual Sum or Average | 0.301049E+12 | 0.503660E+11 | 0.719689E+12 | 0.269050E+11 | 0.132327E+12 | 0.432615E+09 | 0.00 | 0.290118E+12 | 0.00 | 0.00 | 0.00 | 0.466000E+11 | 0.00 |
Minimum of Months | 0.230955E+11 | 0.308173E+10 | 0.548702E+11 | 0.204960E+10 | 0.463336E+10 | 12013203.65 | 0.00 | 0.233713E+09 | 0.00 | 0.00 | 0.00 | 0.323036E+10 | 0.00 |
Maximum of Months | 0.270534E+11 | 0.550349E+10 | 0.627783E+11 | 0.235658E+10 | 0.194717E+11 | 0.117588E+09 | 0.00 | 0.574295E+11 | 0.00 | 0.00 | 0.00 | 0.462321E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.159170E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.932336E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.556583E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.592038E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 41528559.55 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1863748.10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 7092754.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 6917989.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 9731791.37 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.228506E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.568744E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224009E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597822E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1863748.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.224009E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 32642.50 | 17-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 03-JAN-08:09 | 7207.14 | 12-JAN-15:39 | 522.03 | 27-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 30940.97 | 13-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-13:09 | 9217.89 | 21-FEB-16:30 | 529.56 | 03-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 30940.97 | 10-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 12645.62 | 16-MAR-15:30 | 493.21 | 02-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 28290.68 | 20-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 11-APR-07:10 | 20865.27 | 21-APR-14:00 | 219.78 | 12-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 26300.02 | 23-MAY-12:20 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-07:19 | 29857.57 | 30-MAY-14:50 | 93.43 | 02-MAY-06:19 | 0.00 | 01-MAY-00:10 |
June | 25927.38 | 19-JUN-15:00 | 3328.83 | 01-JUN-19:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 32064.48 | 19-JUN-14:30 | 6.93 | 20-JUN-09:50 | 0.00 | 01-JUN-00:10 |
July | 28290.68 | 07-JUL-07:30 | 5686.19 | 06-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-11:09 | 35827.23 | 20-JUL-14:00 | 6.94 | 26-JUL-19:30 | 0.00 | 01-JUL-00:10 |
August | 27997.05 | 17-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 04-AUG-12:09 | 27741.88 | 07-AUG-14:50 | 6.94 | 10-AUG-06:00 | 0.00 | 01-AUG-00:10 |
September | 27466.60 | 18-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 25-SEP-07:10 | 23117.22 | 13-SEP-15:39 | 19.07 | 25-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 32139.03 | 13-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 06-OCT-07:10 | 19310.13 | 03-OCT-15:39 | 166.54 | 25-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 32642.50 | 22-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 13435.91 | 10-NOV-15:00 | 471.63 | 28-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 32642.50 | 01-DEC-16:49 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-17:10 | 5675.65 | 07-DEC-15:09 | 548.18 | 27-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 25927.38 | 3328.83 | 41699.26 | 1410.29 | 5675.65 | 6.93 | 0.00 | |||||||
Maximum of Months | 32642.50 | 5686.19 | 41699.26 | 1410.29 | 35827.23 | 548.18 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 10316.29 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 5911.19 | 26-JAN-12:20 | 0.00 |
February | 17440.06 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 5914.70 | 01-FEB-12:00 | 0.00 |
March | 22686.80 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 5812.43 | 01-MAR-12:39 | 0.00 |
April | 45759.56 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 5413.87 | 03-APR-11:00 | 0.00 |
May | 59218.75 | 30-MAY-14:50 | 0.00 | 0.00 | 0.00 | 5016.27 | 01-MAY-11:00 | 0.00 |
June | 69363.00 | 15-JUN-14:50 | 0.00 | 0.00 | 0.00 | 4644.59 | 01-JUN-11:00 | 0.00 |
July | 71789.35 | 20-JUL-15:09 | 0.00 | 0.00 | 0.00 | 4528.01 | 05-JUL-11:39 | 0.00 |
August | 67138.07 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 4510.44 | 30-AUG-11:00 | 0.00 |
September | 54730.78 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 4622.82 | 29-SEP-11:00 | 0.00 |
October | 54135.78 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 5017.66 | 31-OCT-11:00 | 0.00 |
November | 23475.57 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 5568.95 | 30-NOV-12:30 | 0.00 |
December | 5088.20 | 20-DEC-14:00 | 0.00 | 0.00 | 0.00 | 5809.75 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5088.20 | 0.00 | 0.00 | 0.00 | 4510.44 | 0.00 | ||
Maximum of Months | 71789.35 | 0.00 | 0.00 | 0.00 | 5914.70 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 92299.95 | 03-JAN-16:00 | 31112.50 | 41670.51 | 0.00 | 1410.29 | 4542.55 | 6.85 | 0.00 | 9268.25 | 0.00 |
February | 100291.47 | 21-FEB-16:49 | 27150.80 | 41670.51 | 0.00 | 1410.29 | 8961.09 | 6.85 | 0.00 | 16799.50 | 0.00 |
March | 105894.18 | 21-MAR-15:00 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 9866.79 | 6.85 | 0.00 | 22686.80 | 0.00 |
April | 138735.50 | 21-APR-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 20755.99 | 6.85 | 0.00 | 45315.02 | 0.00 |
May | 160696.36 | 30-MAY-14:50 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 29857.57 | 6.85 | 0.00 | 59218.75 | 0.00 |
June | 170241.50 | 15-JUN-14:30 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 29842.08 | 6.85 | 0.00 | 69075.74 | 0.00 |
July | 179593.23 | 20-JUL-15:09 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 35827.23 | 6.85 | 0.00 | 71789.35 | 0.00 |
August | 162638.42 | 07-AUG-15:00 | 25681.07 | 41670.51 | 0.00 | 1410.29 | 23515.35 | 6.89 | 0.00 | 67138.07 | 0.00 |
September | 149908.05 | 05-SEP-15:30 | 25927.38 | 41670.51 | 0.00 | 1410.29 | 22667.98 | 6.90 | 0.00 | 54701.28 | 0.00 |
October | 140051.56 | 05-OCT-15:00 | 25990.55 | 41670.51 | 0.00 | 1410.29 | 18964.81 | 6.86 | 0.00 | 48451.15 | 0.00 |
November | 111839.37 | 09-NOV-16:49 | 31152.49 | 41670.51 | 0.00 | 1410.29 | 12779.41 | 6.85 | 0.00 | 20878.79 | 0.00 |
December | 91461.62 | 08-DEC-16:00 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 3893.12 | 6.85 | 0.00 | 1893.41 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 91461.62 | 25681.07 | 41659.26 | 0.00 | 1410.29 | 3893.12 | 6.85 | 0.00 | 1893.41 | 0.00 | |
Maximum of Months | 179593.23 | 32642.50 | 41670.51 | 5686.19 | 1410.29 | 35827.23 | 6.90 | 0.00 | 71789.35 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 128981.08 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 133258.10 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 116263.98 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 41818.95 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 13076.17 | 02-MAY-06:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 12.53 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 14.76 | 26-JUL-19:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 15.59 | 10-AUG-06:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2280.14 | 25-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 21854.05 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 104986.74 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 148342.61 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 12.53 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 148342.61 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.30 | 0.00 | 26.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.94 | 0.17 | 24.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.00 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 26.67 | 0.17 | 26.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.17 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.17 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.67 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 24.61 | 0.67 | 24.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.61 | 0.67 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.36 | 0.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.36 | 1.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.50 | 3.17 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.46 | 4.67 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.47 | 2.67 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 1.33 | 18.22 | 0.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 2.33 | 18.71 | 1.67 | 18.98 | 18.00 | 25.92 | 12.00 | 26.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.40 | 0.67 | 19.40 | 6.67 | 27.50 | 4.67 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.74 | 2.67 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.80 | 10.33 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.89 | 10.50 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.88 | 15.50 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.89 | 9.67 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.67 | 7.83 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.56 | 0.50 | 27.56 |
November | 0.17 | 19.37 | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
December | 1.00 | 17.48 | 0.17 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
Annual Sum or Average | 1.33 | 17.95 | 0.50 | 18.34 | 61.00 | 27.56 | 57.00 | 27.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.37 | 0.17 | 19.37 | 16.67 | 27.89 | 15.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.63 | 1.67 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.57 | 2.50 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.51 | 4.50 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.54 | 3.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.60 | 7.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.74 | 6.17 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.86 | 7.33 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.99 | 7.17 | 27.99 |
November | 0.17 | 19.43 | 0.17 | 19.43 | 4.17 | 27.03 | 4.17 | 27.33 |
December | 0.67 | 18.28 | 0.33 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
Annual Sum or Average | 0.83 | 18.51 | 0.50 | 18.85 | 48.17 | 27.47 | 44.33 | 27.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.43 | 0.33 | 19.43 | 8.00 | 27.99 | 7.33 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.53 | 0.17 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.18 | 3.67 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.38 | 4.83 | 28.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.39 | 4.33 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.23 | 6.50 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.41 | 4.17 | 28.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.11 | 4.67 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.90 | 3.00 | 27.90 |
November | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 0.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
Annual Sum or Average | 0.83 | 18.01 | 0.33 | 18.42 | 50.83 | 28.04 | 31.33 | 28.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.17 | 19.44 | 12.00 | 28.41 | 6.50 | 28.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.66 | 4.00 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.68 | 5.83 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.68 | 9.83 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.66 | 8.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.63 | 7.17 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 37.50 | 27.66 | 37.17 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.68 | 9.83 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.83 | 18.60 | 20.83 | 18.60 | 0.67 | 18.74 | 0.67 | 18.87 |
February | 16.33 | 18.66 | 16.33 | 18.66 | 1.00 | 18.93 | 1.00 | 19.17 |
March | 20.17 | 19.18 | 20.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 4.17 | 19.47 | 4.17 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 24.99 | 18.33 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 25.04 | 12.83 | 25.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 25.71 | 14.83 | 25.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 26.06 | 17.50 | 26.04 |
October | 0.17 | 20.30 | 0.17 | 20.30 | 13.50 | 26.50 | 12.83 | 26.56 |
November | 9.83 | 19.55 | 9.83 | 19.55 | 7.00 | 21.67 | 7.00 | 22.90 |
December | 22.33 | 18.42 | 22.33 | 18.42 | 0.83 | 18.58 | 0.83 | 18.74 |
Annual Sum or Average | 93.83 | 18.83 | 93.83 | 18.83 | 87.17 | 21.07 | 86.00 | 22.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 0.00 | 18.74 |
Maximum of Months | 22.33 | 20.30 | 22.33 | 20.30 | 18.33 | 26.50 | 18.33 | 26.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.80 | 1.83 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.87 | 3.83 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.99 | 3.50 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.89 | 5.50 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.98 | 4.17 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.83 | 4.33 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.79 | 2.67 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 27.90 | 25.83 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.99 | 5.50 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.39 | 1.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.00 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.83 | 27.42 | 2.17 | 27.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.17 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.79 | 3.17 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.80 | 7.67 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.88 | 8.50 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.79 | 13.00 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.85 | 8.00 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.79 | 5.33 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 47.67 | 27.81 | 47.17 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.88 | 13.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.34 | 1.17 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.55 | 3.17 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.50 | 1.67 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 1.17 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.33 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.46 | 3.83 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.57 | 5.67 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.76 | 7.00 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.97 | 7.33 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.71 | 6.17 | 27.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
Annual Sum or Average | 0.00 | 0.00 | 40.33 | 27.66 | 39.33 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.97 | 7.33 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.33 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.05 | 3.17 | 28.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.16 | 5.00 | 28.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.24 | 4.33 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.11 | 5.50 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.25 | 4.00 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.01 | 4.17 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.85 | 2.83 | 27.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 45.33 | 28.12 | 29.33 | 28.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.25 | 5.50 | 28.31 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.83 | 23.99 | 1.17 | 24.00 | 0.00 | 24.00 |
February | 304.67 | 24.05 | 9.50 | 24.07 | 0.00 | 24.07 |
March | 308.33 | 24.01 | 19.17 | 24.11 | 0.00 | 24.11 |
April | 101.83 | 24.01 | 106.17 | 24.74 | 0.00 | 24.74 |
May | 7.67 | 24.00 | 244.50 | 24.81 | 0.00 | 24.81 |
June | 0.00 | 0.00 | 358.67 | 24.56 | 0.00 | 24.56 |
July | 23.67 | 24.64 | 497.00 | 24.49 | 23.67 | 24.49 |
August | 0.00 | 0.00 | 506.50 | 24.43 | 0.00 | 24.43 |
September | 7.67 | 26.38 | 445.83 | 24.56 | 7.67 | 24.59 |
October | 3.83 | 24.00 | 303.83 | 24.74 | 0.00 | 24.74 |
November | 163.00 | 24.01 | 84.83 | 24.37 | 0.00 | 24.37 |
December | 399.50 | 24.05 | 0.83 | 24.05 | 0.00 | 24.05 |
Annual Sum or Average | 1676.00 | 24.04 | 2578.00 | 24.40 | 31.33 | 24.40 |
Minimum of Months | 0.00 | 0.00 | 0.83 | 24.00 | 0.00 | 24.00 |
Maximum of Months | 399.50 | 26.38 | 506.50 | 24.81 | 23.67 | 24.81 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
February | 447.00 | 23.34 | 0.00 | 23.34 | 0.00 | 23.34 |
March | 501.00 | 23.64 | 0.33 | 23.64 | 0.00 | 23.64 |
April | 224.67 | 23.86 | 25.33 | 23.97 | 0.00 | 23.97 |
May | 41.50 | 23.95 | 177.67 | 24.43 | 0.00 | 24.43 |
June | 0.83 | 24.00 | 320.83 | 24.41 | 0.00 | 24.41 |
July | 38.67 | 24.28 | 494.00 | 24.33 | 38.67 | 24.32 |
August | 5.33 | 24.00 | 489.00 | 24.30 | 5.33 | 24.30 |
September | 18.67 | 24.51 | 408.50 | 24.36 | 13.17 | 24.37 |
October | 90.67 | 23.70 | 200.00 | 24.15 | 2.00 | 24.15 |
November | 389.17 | 23.48 | 12.83 | 23.51 | 0.00 | 23.51 |
December | 497.00 | 22.87 | 0.83 | 22.86 | 0.83 | 22.86 |
Annual Sum or Average | 2755.00 | 23.35 | 2129.33 | 23.79 | 60.00 | 23.80 |
Minimum of Months | 0.83 | 22.87 | 0.00 | 22.86 | 0.00 | 22.86 |
Maximum of Months | 501.00 | 24.51 | 494.00 | 24.43 | 38.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 22.02 | 76.00 | 21.83 | 76.00 | 21.68 |
February | 454.00 | 22.54 | 36.83 | 22.42 | 36.83 | 22.31 |
March | 512.00 | 23.14 | 4.83 | 23.12 | 4.83 | 23.10 |
April | 273.83 | 23.65 | 24.00 | 23.72 | 0.00 | 23.72 |
May | 76.67 | 23.79 | 181.83 | 24.27 | 0.00 | 24.27 |
June | 4.83 | 24.00 | 338.50 | 24.40 | 0.00 | 24.40 |
July | 34.83 | 24.13 | 495.17 | 24.34 | 34.83 | 24.33 |
August | 4.33 | 24.00 | 481.83 | 24.29 | 4.33 | 24.29 |
September | 37.33 | 23.87 | 385.67 | 24.25 | 14.00 | 24.26 |
October | 212.33 | 23.41 | 136.33 | 23.70 | 1.67 | 23.71 |
November | 443.00 | 22.72 | 15.83 | 22.65 | 15.83 | 22.59 |
December | 497.00 | 21.77 | 115.17 | 21.54 | 115.17 | 21.38 |
Annual Sum or Average | 3051.67 | 22.69 | 2292.00 | 23.22 | 303.50 | 23.12 |
Minimum of Months | 4.33 | 21.77 | 4.83 | 21.54 | 0.00 | 21.38 |
Maximum of Months | 512.00 | 24.13 | 495.17 | 24.40 | 115.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 272.17 | 20.72 | 272.17 | 20.62 |
February | 454.00 | 21.50 | 167.33 | 21.24 | 167.33 | 21.08 |
March | 511.83 | 22.28 | 98.50 | 22.01 | 98.50 | 21.81 |
April | 296.50 | 23.13 | 53.83 | 23.23 | 10.33 | 23.15 |
May | 103.00 | 23.64 | 225.67 | 24.26 | 2.17 | 24.28 |
June | 16.17 | 25.71 | 404.67 | 24.53 | 9.33 | 24.58 |
July | 74.50 | 25.11 | 496.50 | 24.59 | 74.50 | 24.65 |
August | 31.00 | 24.53 | 475.50 | 24.39 | 20.33 | 24.42 |
September | 80.67 | 23.48 | 350.33 | 24.15 | 21.83 | 24.16 |
October | 302.00 | 22.84 | 119.17 | 23.21 | 7.67 | 23.22 |
November | 467.17 | 21.67 | 123.33 | 21.40 | 123.33 | 21.22 |
December | 497.00 | 20.70 | 328.33 | 20.53 | 328.33 | 20.46 |
Annual Sum or Average | 3335.83 | 21.95 | 3115.33 | 22.52 | 1135.83 | 22.28 |
Minimum of Months | 16.17 | 20.70 | 53.83 | 20.53 | 2.17 | 20.46 |
Maximum of Months | 511.83 | 25.71 | 496.50 | 24.59 | 328.33 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.32 | 177.00 | 21.03 | 177.00 | 20.86 |
February | 432.33 | 21.99 | 95.17 | 21.72 | 93.50 | 21.52 |
March | 398.50 | 22.44 | 64.83 | 22.27 | 56.67 | 22.07 |
April | 169.50 | 23.22 | 135.50 | 23.87 | 10.00 | 23.86 |
May | 82.67 | 24.70 | 327.33 | 24.62 | 29.17 | 24.78 |
June | 40.50 | 26.50 | 442.67 | 24.70 | 34.17 | 24.85 |
July | 110.17 | 25.77 | 495.67 | 24.81 | 110.17 | 24.96 |
August | 58.50 | 25.71 | 487.17 | 24.57 | 47.50 | 24.71 |
September | 84.33 | 24.84 | 400.83 | 24.50 | 47.83 | 24.65 |
October | 206.83 | 22.62 | 182.67 | 23.47 | 4.17 | 23.48 |
November | 438.67 | 22.09 | 89.00 | 21.89 | 75.67 | 21.69 |
December | 497.00 | 21.07 | 233.33 | 20.82 | 233.33 | 20.69 |
Annual Sum or Average | 3021.00 | 22.34 | 3131.17 | 23.01 | 919.17 | 22.89 |
Minimum of Months | 40.50 | 21.07 | 64.83 | 20.82 | 4.17 | 20.69 |
Maximum of Months | 502.00 | 26.50 | 495.67 | 24.81 | 233.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 374.67 | 21.73 | 154.67 | 21.58 | 123.00 | 21.32 |
February | 315.17 | 22.01 | 111.33 | 22.02 | 79.67 | 21.78 |
March | 342.83 | 22.42 | 91.50 | 22.35 | 67.17 | 22.11 |
April | 222.67 | 23.09 | 112.67 | 23.55 | 13.50 | 23.51 |
May | 115.00 | 23.73 | 238.50 | 24.28 | 10.33 | 24.36 |
June | 26.17 | 25.18 | 386.50 | 24.52 | 11.00 | 24.58 |
July | 81.33 | 25.23 | 495.17 | 24.59 | 81.33 | 24.67 |
August | 49.17 | 25.21 | 473.50 | 24.48 | 34.67 | 24.58 |
September | 87.50 | 24.60 | 392.00 | 24.47 | 47.33 | 24.61 |
October | 197.50 | 23.37 | 261.67 | 24.04 | 28.00 | 24.20 |
November | 298.17 | 22.12 | 150.17 | 22.48 | 61.50 | 22.27 |
December | 381.00 | 21.65 | 156.83 | 21.38 | 142.33 | 21.14 |
Annual Sum or Average | 2491.17 | 22.56 | 3024.50 | 23.29 | 699.83 | 23.15 |
Minimum of Months | 26.17 | 21.65 | 91.50 | 21.38 | 10.33 | 21.14 |
Maximum of Months | 381.00 | 25.23 | 495.17 | 24.59 | 142.33 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.17 | 21.19 | 221.50 | 20.91 | 221.17 | 20.77 |
February | 414.17 | 21.55 | 153.67 | 21.34 | 146.33 | 21.17 |
March | 409.17 | 22.00 | 114.50 | 21.87 | 95.33 | 21.68 |
April | 252.33 | 22.90 | 120.50 | 23.37 | 19.83 | 23.38 |
May | 130.33 | 23.86 | 277.17 | 24.33 | 23.17 | 24.48 |
June | 39.67 | 25.42 | 396.50 | 24.58 | 20.83 | 24.70 |
July | 84.17 | 25.26 | 491.83 | 24.59 | 84.17 | 24.68 |
August | 63.17 | 24.68 | 464.33 | 24.43 | 37.33 | 24.52 |
September | 106.00 | 23.89 | 369.83 | 24.26 | 43.50 | 24.36 |
October | 269.83 | 22.74 | 183.00 | 23.41 | 13.50 | 23.49 |
November | 410.17 | 21.63 | 133.17 | 21.51 | 108.83 | 21.32 |
December | 493.33 | 21.09 | 268.00 | 20.80 | 268.00 | 20.67 |
Annual Sum or Average | 3153.50 | 22.09 | 3194.00 | 22.74 | 1082.00 | 22.57 |
Minimum of Months | 39.67 | 21.09 | 114.50 | 20.80 | 13.50 | 20.67 |
Maximum of Months | 493.33 | 25.42 | 491.83 | 24.59 | 268.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.35 | 133.50 | 21.21 | 133.50 | 21.13 |
February | 454.00 | 21.58 | 123.33 | 21.40 | 123.33 | 21.29 |
March | 514.00 | 22.08 | 64.67 | 21.93 | 64.67 | 21.81 |
April | 396.50 | 23.26 | 5.00 | 23.24 | 3.50 | 23.22 |
May | 140.00 | 23.71 | 149.83 | 24.06 | 0.00 | 24.06 |
June | 6.17 | 24.01 | 346.83 | 24.40 | 0.00 | 24.40 |
July | 39.83 | 24.39 | 495.17 | 24.44 | 39.83 | 24.44 |
August | 8.17 | 24.16 | 501.67 | 24.35 | 8.17 | 24.35 |
September | 30.17 | 24.04 | 398.50 | 24.33 | 14.33 | 24.34 |
October | 208.17 | 23.55 | 153.17 | 23.82 | 3.33 | 23.83 |
November | 456.67 | 22.52 | 12.67 | 22.48 | 12.67 | 22.43 |
December | 497.00 | 21.36 | 160.67 | 21.20 | 160.67 | 21.10 |
Annual Sum or Average | 3252.67 | 22.21 | 2545.00 | 22.85 | 564.00 | 22.70 |
Minimum of Months | 6.17 | 21.35 | 5.00 | 21.20 | 0.00 | 21.10 |
Maximum of Months | 514.00 | 24.39 | 501.67 | 24.44 | 160.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.97 | 60.50 | 21.82 | 60.50 | 21.71 |
February | 440.00 | 22.38 | 45.33 | 22.24 | 43.67 | 22.11 |
March | 463.17 | 22.80 | 33.00 | 22.71 | 28.17 | 22.60 |
April | 200.00 | 23.52 | 100.17 | 24.05 | 0.83 | 24.06 |
May | 52.33 | 24.32 | 288.50 | 24.58 | 9.67 | 24.65 |
June | 16.67 | 26.82 | 435.50 | 24.59 | 15.50 | 24.67 |
July | 79.33 | 25.76 | 496.33 | 24.76 | 79.33 | 24.88 |
August | 30.33 | 26.59 | 510.33 | 24.59 | 30.33 | 24.69 |
September | 45.50 | 26.12 | 444.00 | 24.66 | 40.50 | 24.80 |
October | 114.67 | 23.48 | 244.50 | 24.16 | 3.00 | 24.18 |
November | 374.67 | 22.97 | 26.50 | 23.05 | 3.83 | 23.03 |
December | 497.00 | 22.00 | 72.17 | 21.83 | 72.17 | 21.69 |
Annual Sum or Average | 2815.67 | 22.78 | 2756.83 | 23.51 | 387.50 | 23.49 |
Minimum of Months | 16.67 | 21.97 | 26.50 | 21.82 | 0.83 | 21.69 |
Maximum of Months | 502.00 | 26.82 | 510.33 | 24.76 | 79.33 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 373.50 | 22.12 | 69.17 | 22.18 | 35.67 | 21.97 |
February | 352.00 | 22.29 | 53.17 | 22.40 | 24.50 | 22.22 |
March | 418.83 | 22.51 | 52.33 | 22.51 | 30.67 | 22.33 |
April | 285.17 | 23.11 | 66.33 | 23.41 | 5.67 | 23.35 |
May | 135.33 | 23.37 | 161.00 | 23.99 | 0.00 | 23.99 |
June | 21.00 | 23.42 | 330.33 | 24.41 | 0.67 | 24.41 |
July | 76.33 | 24.22 | 494.33 | 24.44 | 76.33 | 24.42 |
August | 40.17 | 24.57 | 500.83 | 24.45 | 37.50 | 24.46 |
September | 68.17 | 25.11 | 437.83 | 24.65 | 53.67 | 24.76 |
October | 92.17 | 24.09 | 322.50 | 24.53 | 33.83 | 24.68 |
November | 231.50 | 22.72 | 119.83 | 23.43 | 12.17 | 23.38 |
December | 366.83 | 22.11 | 65.17 | 22.07 | 42.83 | 21.83 |
Annual Sum or Average | 2461.00 | 22.72 | 2672.83 | 23.57 | 353.50 | 23.52 |
Minimum of Months | 21.00 | 22.11 | 52.33 | 22.07 | 0.00 | 21.83 |
Maximum of Months | 418.83 | 25.11 | 500.83 | 24.65 | 76.33 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.50 | 21.83 | 70.67 | 21.69 | 70.33 | 21.58 |
February | 441.00 | 22.02 | 67.50 | 21.90 | 63.33 | 21.77 |
March | 455.67 | 22.45 | 38.17 | 22.43 | 27.83 | 22.35 |
April | 262.33 | 23.32 | 82.83 | 23.70 | 2.33 | 23.72 |
May | 99.33 | 24.01 | 260.33 | 24.41 | 10.67 | 24.49 |
June | 17.67 | 26.29 | 405.33 | 24.54 | 13.33 | 24.62 |
July | 64.50 | 25.38 | 495.67 | 24.62 | 64.50 | 24.70 |
August | 29.50 | 26.06 | 507.33 | 24.54 | 29.50 | 24.62 |
September | 41.33 | 25.34 | 436.83 | 24.56 | 31.83 | 24.65 |
October | 101.83 | 23.74 | 247.00 | 24.24 | 11.67 | 24.31 |
November | 369.50 | 22.74 | 36.17 | 22.86 | 4.00 | 22.84 |
December | 495.17 | 21.85 | 94.17 | 21.67 | 94.17 | 21.53 |
Annual Sum or Average | 2869.33 | 22.56 | 2742.00 | 23.34 | 423.50 | 23.30 |
Minimum of Months | 17.67 | 21.83 | 36.17 | 21.67 | 2.33 | 21.53 |
Maximum of Months | 495.17 | 26.29 | 507.33 | 24.62 | 94.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.46 | 133.67 | 21.29 | 133.67 | 21.17 |
February | 454.00 | 22.03 | 75.00 | 21.84 | 75.00 | 21.70 |
March | 513.83 | 22.74 | 30.50 | 22.63 | 30.50 | 22.53 |
April | 279.00 | 23.49 | 33.00 | 23.59 | 0.00 | 23.59 |
May | 73.17 | 23.83 | 220.67 | 24.38 | 0.00 | 24.38 |
June | 2.33 | 26.37 | 395.33 | 24.52 | 1.67 | 24.53 |
July | 60.00 | 24.68 | 497.00 | 24.53 | 60.00 | 24.54 |
August | 13.67 | 24.30 | 493.17 | 24.37 | 13.67 | 24.37 |
September | 46.67 | 23.83 | 384.17 | 24.27 | 20.83 | 24.28 |
October | 252.67 | 23.33 | 138.33 | 23.63 | 4.33 | 23.63 |
November | 456.50 | 22.31 | 38.50 | 22.18 | 38.50 | 22.07 |
December | 497.00 | 21.26 | 196.00 | 21.06 | 196.00 | 20.95 |
Annual Sum or Average | 3150.83 | 22.34 | 2635.33 | 22.98 | 574.17 | 22.83 |
Minimum of Months | 2.33 | 21.26 | 30.50 | 21.06 | 0.00 | 20.95 |
Maximum of Months | 513.83 | 26.37 | 497.00 | 24.53 | 196.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 425.17 | 21.73 | 87.17 | 21.52 | 87.17 | 21.37 |
February | 355.17 | 22.28 | 50.67 | 22.16 | 44.67 | 22.00 |
March | 354.83 | 22.75 | 38.17 | 22.77 | 22.50 | 22.66 |
April | 152.67 | 23.52 | 108.83 | 24.15 | 5.67 | 24.21 |
May | 56.67 | 24.87 | 262.67 | 24.78 | 20.00 | 24.91 |
June | 29.33 | 26.85 | 367.00 | 24.80 | 27.67 | 24.95 |
July | 95.67 | 25.76 | 422.00 | 24.90 | 95.67 | 25.03 |
August | 41.17 | 26.04 | 416.50 | 24.66 | 37.83 | 24.78 |
September | 54.17 | 25.32 | 346.50 | 24.64 | 37.00 | 24.77 |
October | 171.00 | 23.15 | 170.83 | 23.84 | 4.67 | 23.87 |
November | 356.17 | 22.47 | 41.00 | 22.47 | 23.50 | 22.36 |
December | 422.00 | 21.57 | 123.67 | 21.32 | 123.67 | 21.17 |
Annual Sum or Average | 2514.00 | 22.67 | 2435.00 | 23.39 | 530.00 | 23.35 |
Minimum of Months | 29.33 | 21.57 | 38.17 | 21.32 | 4.67 | 21.17 |
Maximum of Months | 425.17 | 26.85 | 422.00 | 24.90 | 123.67 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.33 | 22.22 | 91.17 | 22.31 | 49.67 | 22.11 |
February | 293.00 | 22.56 | 63.17 | 22.77 | 27.83 | 22.63 |
March | 327.00 | 22.94 | 37.50 | 23.10 | 12.50 | 23.02 |
April | 194.17 | 23.48 | 99.67 | 23.95 | 1.50 | 23.97 |
May | 78.00 | 23.82 | 240.17 | 24.40 | 1.83 | 24.42 |
June | 8.00 | 25.11 | 388.67 | 24.50 | 2.67 | 24.51 |
July | 71.67 | 25.00 | 496.17 | 24.57 | 71.67 | 24.61 |
August | 31.33 | 25.83 | 495.33 | 24.50 | 31.33 | 24.57 |
September | 61.50 | 25.40 | 421.83 | 24.59 | 46.33 | 24.72 |
October | 149.83 | 24.03 | 293.33 | 24.38 | 31.33 | 24.54 |
November | 268.33 | 22.81 | 121.67 | 23.36 | 21.33 | 23.32 |
December | 347.33 | 22.19 | 96.17 | 22.11 | 71.83 | 21.88 |
Annual Sum or Average | 2170.50 | 22.98 | 2844.83 | 23.75 | 369.83 | 23.72 |
Minimum of Months | 8.00 | 22.19 | 37.50 | 22.11 | 1.50 | 21.88 |
Maximum of Months | 347.33 | 25.83 | 496.17 | 24.59 | 71.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.17 | 21.64 | 114.67 | 21.45 | 112.50 | 21.31 |
February | 406.50 | 22.00 | 72.67 | 21.90 | 64.83 | 21.75 |
March | 406.33 | 22.52 | 43.83 | 22.55 | 24.67 | 22.46 |
April | 230.17 | 23.34 | 107.50 | 23.79 | 6.83 | 23.86 |
May | 98.17 | 24.26 | 284.83 | 24.49 | 20.83 | 24.63 |
June | 24.50 | 26.34 | 408.00 | 24.60 | 18.67 | 24.70 |
July | 85.83 | 25.23 | 496.17 | 24.61 | 85.83 | 24.69 |
August | 39.33 | 25.53 | 489.83 | 24.49 | 35.67 | 24.57 |
September | 68.00 | 24.54 | 399.83 | 24.42 | 41.33 | 24.50 |
October | 217.50 | 23.28 | 208.00 | 23.83 | 13.33 | 23.90 |
November | 389.50 | 22.20 | 67.17 | 22.24 | 36.50 | 22.12 |
December | 483.67 | 21.55 | 155.50 | 21.30 | 155.50 | 21.14 |
Annual Sum or Average | 2921.67 | 22.48 | 2848.00 | 23.21 | 616.50 | 23.14 |
Minimum of Months | 24.50 | 21.55 | 43.83 | 21.30 | 6.83 | 21.14 |
Maximum of Months | 483.67 | 26.34 | 496.17 | 24.61 | 155.50 | 24.70 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.19886 | 19.97077 | 0.22439 | 6.18134 |
February | 454.00000 | 24.26803 | 16.76104 | 0.23175 | 6.25101 |
March | 514.00000 | 24.31939 | 16.30834 | 0.25707 | 6.56311 |
April | 485.00000 | 24.43427 | 20.35546 | 0.34444 | 7.77523 |
May | 508.00000 | 24.43362 | 29.40756 | -0.4128 | 9.17262 |
June | 496.00000 | 24.41620 | 35.70801 | -0.3549 | 8.19388 |
July | 497.00000 | 24.47866 | 47.56589 | -0.2533 | 6.87289 |
August | 514.00000 | 24.42436 | 45.47757 | -0.2833 | 7.17462 |
September | 485.00000 | 24.49098 | 42.66881 | -0.2884 | 7.46673 |
October | 502.00000 | 24.46439 | 34.41337 | 0.46477 | 9.91152 |
November | 489.00000 | 24.37584 | 21.49808 | 0.31699 | 7.36878 |
December | 497.00000 | 24.20121 | 17.34392 | 0.20441 | 5.98829 |
Annual Sum or Average | 5943.00000 | 24.37592 | 29.05234 | 0.03531 | 7.41870 |
Minimum of Months | 454.00000 | 24.19886 | 16.30834 | -0.4128 | 5.98829 |
Maximum of Months | 514.00000 | 24.49098 | 47.56589 | 0.46477 | 9.91152 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.00326 | 22.75085 | -0.0572 | 5.58473 |
February | 454.00000 | 23.34822 | 18.73895 | 0.01201 | 5.49285 |
March | 514.00000 | 23.67475 | 17.66667 | 0.09707 | 5.50623 |
April | 485.00000 | 24.08382 | 21.30250 | 0.25185 | 6.57574 |
May | 508.00000 | 24.25034 | 30.40506 | -0.4935 | 10.51527 |
June | 496.00000 | 24.29519 | 36.67924 | -0.4128 | 8.93831 |
July | 497.00000 | 24.32700 | 49.65071 | -0.3133 | 7.35158 |
August | 514.00000 | 24.28809 | 47.12008 | -0.3470 | 7.79692 |
September | 485.00000 | 24.30321 | 44.25232 | -0.3743 | 8.33765 |
October | 502.00000 | 24.11905 | 35.75961 | 0.36346 | 8.01158 |
November | 489.00000 | 23.63548 | 23.46327 | 0.12429 | 5.89444 |
December | 497.00000 | 22.86745 | 19.89809 | -0.1100 | 5.87202 |
Annual Sum or Average | 5943.00000 | 23.85312 | 30.73400 | -0.1066 | 7.17139 |
Minimum of Months | 454.00000 | 22.86745 | 17.66667 | -0.4935 | 5.49285 |
Maximum of Months | 514.00000 | 24.32700 | 49.65071 | 0.36346 | 10.51527 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.02303 | 23.92964 | -0.2972 | 8.01357 |
February | 454.00000 | 22.54328 | 19.56947 | -0.1837 | 6.88430 |
March | 514.00000 | 23.14340 | 18.28793 | -0.0330 | 5.90897 |
April | 485.00000 | 23.88543 | 21.29328 | 0.20303 | 6.36794 |
May | 508.00000 | 24.19366 | 30.22068 | -0.5073 | 10.95442 |
June | 496.00000 | 24.29682 | 36.31600 | -0.3974 | 8.70288 |
July | 497.00000 | 24.35161 | 48.76540 | -0.2956 | 7.16442 |
August | 514.00000 | 24.27567 | 46.32272 | -0.3476 | 7.82990 |
September | 485.00000 | 24.21946 | 43.82727 | -0.4052 | 8.91265 |
October | 502.00000 | 23.81900 | 36.12016 | 0.28301 | 7.17952 |
November | 489.00000 | 22.84082 | 24.55598 | -0.0727 | 6.56335 |
December | 497.00000 | 21.77393 | 20.90200 | -0.3794 | 9.33045 |
Annual Sum or Average | 5943.00000 | 23.45394 | 30.93055 | -0.2036 | 7.82672 |
Minimum of Months | 454.00000 | 21.77393 | 18.28793 | -0.5073 | 5.90897 |
Maximum of Months | 514.00000 | 24.35161 | 48.76540 | 0.28301 | 10.95442 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.93014 | 25.90095 | -0.5805 | 13.43462 |
February | 454.00000 | 21.50265 | 21.70241 | -0.4440 | 10.91733 |
March | 514.00000 | 22.28558 | 19.84795 | -0.2441 | 8.17689 |
April | 485.00000 | 23.55612 | 22.05235 | 0.12468 | 6.80196 |
May | 508.00000 | 24.18974 | 30.09166 | -0.4882 | 11.49567 |
June | 496.00000 | 24.40579 | 36.05609 | -0.3094 | 7.88901 |
July | 497.00000 | 24.51081 | 49.00747 | -0.1932 | 6.73144 |
August | 514.00000 | 24.32548 | 46.54759 | -0.3038 | 7.77960 |
September | 485.00000 | 24.12658 | 44.63041 | -0.4249 | 10.17619 |
October | 502.00000 | 23.33871 | 38.17955 | 0.16728 | 6.97687 |
November | 489.00000 | 21.77588 | 26.71076 | -0.3369 | 9.72740 |
December | 497.00000 | 20.70362 | 23.03439 | -0.6630 | 15.82874 |
Annual Sum or Average | 5943.00000 | 22.98216 | 32.05898 | -0.3076 | 9.65185 |
Minimum of Months | 454.00000 | 20.70362 | 19.84795 | -0.6630 | 6.73144 |
Maximum of Months | 514.00000 | 24.51081 | 49.00747 | 0.16728 | 15.82874 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32074 | 25.08674 | -0.4621 | 11.31201 |
February | 454.00000 | 22.11117 | 20.61757 | -0.2707 | 9.00535 |
March | 514.00000 | 22.84787 | 18.45764 | -0.0735 | 7.56394 |
April | 485.00000 | 23.95958 | 20.95904 | 0.28061 | 8.36251 |
May | 508.00000 | 24.35079 | 29.55975 | -0.3389 | 9.64845 |
June | 496.00000 | 24.47115 | 35.76427 | -0.1938 | 7.33908 |
July | 497.00000 | 24.59536 | 48.54647 | -0.0812 | 6.92578 |
August | 514.00000 | 24.38430 | 46.21150 | -0.1941 | 7.37839 |
September | 485.00000 | 24.28986 | 43.78750 | -0.2772 | 8.78603 |
October | 502.00000 | 23.58492 | 37.04600 | 0.26679 | 8.41725 |
November | 489.00000 | 22.29665 | 25.59971 | -0.1859 | 8.40844 |
December | 497.00000 | 21.07172 | 22.35219 | -0.5481 | 13.12278 |
Annual Sum or Average | 5943.00000 | 23.28233 | 31.24741 | -0.1731 | 8.85199 |
Minimum of Months | 454.00000 | 21.07172 | 18.45764 | -0.5481 | 6.92578 |
Maximum of Months | 514.00000 | 24.59536 | 48.54647 | 0.28061 | 13.12278 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.39686 | 22.84199 | -0.1768 | 10.19452 |
February | 454.00000 | 22.76992 | 19.10459 | -0.0933 | 9.31131 |
March | 514.00000 | 23.05949 | 17.80599 | -0.0169 | 8.12272 |
April | 485.00000 | 23.77306 | 21.23617 | 0.21144 | 7.93857 |
May | 508.00000 | 24.16844 | 30.02383 | -0.4783 | 11.76844 |
June | 496.00000 | 24.36750 | 36.12816 | -0.3247 | 8.21299 |
July | 497.00000 | 24.48197 | 49.02698 | -0.1969 | 6.90410 |
August | 514.00000 | 24.34440 | 46.28588 | -0.2576 | 7.62551 |
September | 485.00000 | 24.28589 | 43.66189 | -0.2818 | 9.01885 |
October | 502.00000 | 23.88299 | 35.86096 | 0.37000 | 10.29812 |
November | 489.00000 | 23.03966 | 23.67117 | 0.02995 | 9.42846 |
December | 497.00000 | 22.26318 | 20.22409 | -0.2355 | 10.86577 |
Annual Sum or Average | 5943.00000 | 23.57510 | 30.57813 | -0.1220 | 9.14146 |
Minimum of Months | 454.00000 | 22.26318 | 17.80599 | -0.4783 | 6.90410 |
Maximum of Months | 514.00000 | 24.48197 | 49.02698 | 0.37000 | 11.76844 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.31528 | 24.70374 | -0.4679 | 12.28646 |
February | 454.00000 | 21.80753 | 20.61723 | -0.3470 | 10.47606 |
March | 514.00000 | 22.46812 | 18.73203 | -0.1584 | 8.57424 |
April | 485.00000 | 23.56945 | 21.56462 | 0.18692 | 8.35315 |
May | 508.00000 | 24.14080 | 30.00791 | -0.4176 | 11.81292 |
June | 496.00000 | 24.37395 | 36.04698 | -0.2429 | 8.08052 |
July | 497.00000 | 24.46735 | 49.01739 | -0.1389 | 7.13236 |
August | 514.00000 | 24.29578 | 46.52477 | -0.2364 | 8.06169 |
September | 485.00000 | 24.11785 | 44.41147 | -0.3370 | 10.07149 |
October | 502.00000 | 23.40255 | 37.43193 | 0.23470 | 8.50562 |
November | 489.00000 | 22.04768 | 25.40433 | -0.2377 | 9.58649 |
December | 497.00000 | 21.10662 | 21.98045 | -0.5483 | 14.11371 |
Annual Sum or Average | 5943.00000 | 23.10256 | 31.45292 | -0.2256 | 9.74871 |
Minimum of Months | 454.00000 | 21.10662 | 18.73203 | -0.5483 | 7.13236 |
Maximum of Months | 514.00000 | 24.46735 | 49.01739 | 0.23470 | 14.11371 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34672 | 25.25524 | -0.4562 | 9.93141 |
February | 454.00000 | 21.57873 | 21.62122 | -0.4193 | 9.52134 |
March | 514.00000 | 22.08304 | 20.63427 | -0.2991 | 7.80003 |
April | 485.00000 | 23.41084 | 23.14306 | 0.06472 | 5.98176 |
May | 508.00000 | 24.09392 | 30.77574 | -0.5657 | 12.46087 |
June | 496.00000 | 24.30553 | 36.36984 | -0.3911 | 8.60158 |
July | 497.00000 | 24.44081 | 48.37804 | -0.2496 | 6.77321 |
August | 514.00000 | 24.34598 | 46.22151 | -0.3084 | 7.41450 |
September | 485.00000 | 24.29483 | 43.82537 | -0.3663 | 8.42217 |
October | 502.00000 | 23.86874 | 37.06269 | 0.29815 | 7.31296 |
November | 489.00000 | 22.61924 | 25.64325 | -0.1196 | 6.44706 |
December | 497.00000 | 21.36466 | 22.16765 | -0.4678 | 10.25531 |
Annual Sum or Average | 5943.00000 | 23.15633 | 31.83871 | -0.2734 | 8.41289 |
Minimum of Months | 454.00000 | 21.34672 | 20.63427 | -0.5657 | 5.98176 |
Maximum of Months | 514.00000 | 24.44081 | 48.37804 | 0.29815 | 12.46087 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.96695 | 24.45327 | -0.2895 | 7.85647 |
February | 454.00000 | 22.45666 | 20.53889 | -0.1876 | 7.23611 |
March | 514.00000 | 22.97172 | 19.11160 | -0.0595 | 6.62342 |
April | 485.00000 | 24.05783 | 21.49007 | 0.27353 | 7.60645 |
May | 508.00000 | 24.36288 | 29.81553 | -0.3797 | 9.42056 |
June | 496.00000 | 24.45208 | 35.81579 | -0.2477 | 7.32238 |
July | 497.00000 | 24.60374 | 47.70112 | -0.1123 | 6.54573 |
August | 514.00000 | 24.46505 | 45.69621 | -0.1773 | 6.72253 |
September | 485.00000 | 24.47278 | 42.94754 | -0.2090 | 7.29069 |
October | 502.00000 | 24.12573 | 35.94216 | 0.40320 | 9.17345 |
November | 489.00000 | 23.26641 | 24.34956 | 0.06002 | 6.40660 |
December | 497.00000 | 22.00195 | 21.45455 | -0.2982 | 8.02576 |
Annual Sum or Average | 5943.00000 | 23.60737 | 30.85897 | -0.1025 | 7.52340 |
Minimum of Months | 454.00000 | 21.96695 | 19.11160 | -0.3797 | 6.40660 |
Maximum of Months | 514.00000 | 24.60374 | 47.70112 | 0.40320 | 9.42056 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.74222 | 21.29890 | -0.0478 | 7.91703 |
February | 454.00000 | 22.85120 | 18.47956 | -0.0480 | 7.80323 |
March | 514.00000 | 22.90354 | 17.79645 | -0.0500 | 7.30638 |
April | 485.00000 | 23.66203 | 21.37158 | 0.16109 | 7.02393 |
May | 508.00000 | 24.04585 | 30.01469 | -0.5652 | 13.00899 |
June | 496.00000 | 24.30299 | 35.68271 | -0.4030 | 8.99859 |
July | 497.00000 | 24.47263 | 49.18300 | -0.2315 | 6.74103 |
August | 514.00000 | 24.41443 | 46.14262 | -0.2435 | 7.06635 |
September | 485.00000 | 24.47744 | 42.88989 | -0.2080 | 7.50968 |
October | 502.00000 | 24.28756 | 35.02128 | 0.48869 | 11.35867 |
November | 489.00000 | 23.65453 | 22.26564 | 0.21857 | 8.56912 |
December | 497.00000 | 22.73947 | 18.59056 | -0.0648 | 7.94205 |
Annual Sum or Average | 5943.00000 | 23.71757 | 29.98677 | -0.0844 | 8.44945 |
Minimum of Months | 454.00000 | 22.73947 | 17.79645 | -0.5652 | 6.74103 |
Maximum of Months | 514.00000 | 24.47744 | 49.18300 | 0.48869 | 13.00899 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88344 | 24.23639 | -0.3072 | 8.35918 |
February | 454.00000 | 22.11341 | 20.70488 | -0.2706 | 8.13359 |
March | 514.00000 | 22.68449 | 19.34904 | -0.1264 | 7.05451 |
April | 485.00000 | 23.81307 | 21.99332 | 0.20803 | 7.26241 |
May | 508.00000 | 24.25570 | 30.11767 | -0.4283 | 10.46588 |
June | 496.00000 | 24.39499 | 36.03034 | -0.2845 | 7.75085 |
July | 497.00000 | 24.52468 | 48.05025 | -0.1543 | 6.56888 |
August | 514.00000 | 24.44463 | 45.85284 | -0.1993 | 6.90020 |
September | 485.00000 | 24.43525 | 43.20777 | -0.2305 | 7.30639 |
October | 502.00000 | 24.15243 | 35.98912 | 0.41342 | 9.36011 |
November | 489.00000 | 23.10314 | 24.27180 | 0.02677 | 6.58235 |
December | 497.00000 | 21.86131 | 21.35045 | -0.3306 | 8.65031 |
Annual Sum or Average | 5943.00000 | 23.48097 | 31.01151 | -0.1404 | 7.86978 |
Minimum of Months | 454.00000 | 21.86131 | 19.34904 | -0.4283 | 6.56888 |
Maximum of Months | 514.00000 | 24.52468 | 48.05025 | 0.41342 | 10.46588 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.46358 | 25.36598 | -0.4239 | 9.67503 |
February | 454.00000 | 22.02922 | 21.29856 | -0.2995 | 8.13926 |
March | 514.00000 | 22.74039 | 19.55133 | -0.1272 | 6.53901 |
April | 485.00000 | 23.79710 | 22.05480 | 0.18158 | 6.43842 |
May | 508.00000 | 24.26633 | 30.24860 | -0.4696 | 10.50471 |
June | 496.00000 | 24.41751 | 36.32592 | -0.3218 | 7.85421 |
July | 497.00000 | 24.50770 | 49.67576 | -0.2066 | 6.61885 |
August | 514.00000 | 24.35755 | 47.18083 | -0.2992 | 7.44749 |
September | 485.00000 | 24.24381 | 44.84593 | -0.3869 | 8.90784 |
October | 502.00000 | 23.70804 | 37.62609 | 0.25892 | 7.06549 |
November | 489.00000 | 22.42500 | 26.01566 | -0.1676 | 7.11958 |
December | 497.00000 | 21.26436 | 22.61170 | -0.4949 | 11.12632 |
Annual Sum or Average | 5943.00000 | 23.27756 | 31.98237 | -0.2299 | 8.12113 |
Minimum of Months | 454.00000 | 21.26436 | 19.55133 | -0.4949 | 6.43842 |
Maximum of Months | 514.00000 | 24.50770 | 49.67576 | 0.25892 | 11.12632 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.74371 | 24.08630 | -0.3427 | 8.85364 |
February | 385.00000 | 22.46705 | 19.46830 | -0.1764 | 7.63214 |
March | 433.00000 | 23.07598 | 17.78969 | -0.0180 | 6.87909 |
April | 410.00000 | 24.10499 | 20.77398 | 0.30149 | 8.26300 |
May | 430.00000 | 24.46674 | 29.37883 | -0.3330 | 9.37856 |
June | 418.00000 | 24.56720 | 35.40895 | -0.2090 | 7.51709 |
July | 422.00000 | 24.70125 | 48.60216 | -0.0864 | 6.98267 |
August | 433.00000 | 24.48860 | 46.16826 | -0.1960 | 7.31290 |
September | 410.00000 | 24.42927 | 43.57499 | -0.2604 | 8.37211 |
October | 427.00000 | 23.84411 | 36.47708 | 0.32202 | 8.51742 |
November | 417.00000 | 22.75005 | 24.35393 | -0.0685 | 7.09939 |
December | 422.00000 | 21.57097 | 21.26659 | -0.4084 | 9.91418 |
Annual Sum or Average | 5034.00000 | 23.52280 | 30.69264 | -0.1233 | 8.06261 |
Minimum of Months | 385.00000 | 21.57097 | 17.78969 | -0.4084 | 6.87909 |
Maximum of Months | 433.00000 | 24.70125 | 48.60216 | 0.32202 | 9.91418 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.92001 | 22.11005 | -0.0283 | 8.25782 |
February | 454.00000 | 23.25138 | 18.52801 | 0.03743 | 7.80816 |
March | 514.00000 | 23.45384 | 17.42888 | 0.08517 | 7.09747 |
April | 485.00000 | 24.01615 | 21.20877 | 0.26671 | 7.64063 |
May | 508.00000 | 24.27816 | 30.13517 | -0.4515 | 10.49217 |
June | 496.00000 | 24.39629 | 36.37225 | -0.3323 | 8.06562 |
July | 497.00000 | 24.50201 | 49.65337 | -0.2041 | 6.73876 |
August | 514.00000 | 24.39640 | 46.86701 | -0.2491 | 7.19902 |
September | 485.00000 | 24.40517 | 43.82979 | -0.2469 | 7.88862 |
October | 502.00000 | 24.17848 | 35.43083 | 0.44411 | 10.64904 |
November | 489.00000 | 23.55430 | 23.00183 | 0.16861 | 8.54182 |
December | 497.00000 | 22.84099 | 19.55607 | -0.0706 | 8.44678 |
Annual Sum or Average | 5943.00000 | 23.85333 | 30.43637 | -0.0500 | 8.24011 |
Minimum of Months | 454.00000 | 22.84099 | 17.42888 | -0.4515 | 6.73876 |
Maximum of Months | 514.00000 | 24.50201 | 49.65337 | 0.44411 | 10.64904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79227 | 24.16950 | -0.3242 | 9.13278 |
February | 454.00000 | 22.26414 | 20.25588 | -0.2173 | 8.12383 |
March | 514.00000 | 22.89569 | 18.45771 | -0.0484 | 7.10372 |
April | 485.00000 | 23.84996 | 21.55231 | 0.24980 | 7.95402 |
May | 508.00000 | 24.27129 | 30.07497 | -0.3862 | 10.28502 |
June | 496.00000 | 24.41739 | 36.24479 | -0.2479 | 7.72978 |
July | 497.00000 | 24.49708 | 49.59863 | -0.1445 | 6.80783 |
August | 514.00000 | 24.36657 | 47.06969 | -0.2231 | 7.41410 |
September | 485.00000 | 24.27702 | 44.52793 | -0.2905 | 8.48296 |
October | 502.00000 | 23.79201 | 36.95270 | 0.32859 | 8.63485 |
November | 489.00000 | 22.62065 | 24.77370 | -0.0850 | 7.51727 |
December | 497.00000 | 21.61689 | 21.54243 | -0.3920 | 10.19919 |
Annual Sum or Average | 5943.00000 | 23.39670 | 31.35394 | -0.1486 | 8.28350 |
Minimum of Months | 454.00000 | 21.61689 | 18.45771 | -0.3920 | 6.80783 |
Maximum of Months | 514.00000 | 24.49708 | 49.59863 | 0.32859 | 10.28502 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.105116E+11 | 0.00 | 242.12 | 168608.75 | 09-JAN-06:11 | 0.00 | 27.65 | 37.66 | 0.04 | 0.00 | 0.02 | 0.67 | 09-JAN-06:11 |
February | 0.606141E+10 | 0.00 | 170.30 | 165206.03 | 16-FEB-07:01 | 0.00 | 28.42 | 35.84 | 0.02 | 0.00 | 0.01 | 0.66 | 16-FEB-07:01 |
March | 0.356679E+10 | 0.00 | 103.53 | 157600.44 | 01-MAR-07:02 | 0.00 | 32.72 | 36.50 | 0.01 | 0.00 | 0.01 | 0.63 | 01-MAR-07:02 |
April | 0.363297E+09 | 0.00 | 23.54 | 59602.86 | 12-APR-06:03 | 0.00 | 37.61 | 38.36 | 0.00 | 0.00 | 0.00 | 0.24 | 12-APR-06:03 |
May | 24961452.26 | 0.00 | 39.41 | 8916.41 | 02-MAY-06:07 | 0.00 | 39.12 | 40.26 | 0.00 | 0.00 | 0.00 | 0.04 | 02-MAY-06:07 |
June | 1119822.28 | 0.00 | 66.34 | 7.53 | 29-JUN-17:00 | 0.00 | 37.91 | 39.96 | 0.00 | 0.00 | 0.00 | 0.00 | 29-JUN-17:00 |
July | 4268459.48 | 0.00 | 236.95 | 8.87 | 26-JUL-19:30 | 0.00 | 36.74 | 44.20 | 0.00 | 0.00 | 0.00 | 0.00 | 26-JUL-19:30 |
August | 4158394.86 | 0.00 | 212.48 | 9.37 | 10-AUG-07:00 | 0.00 | 34.80 | 41.98 | 0.00 | 0.00 | 0.00 | 0.00 | 10-AUG-07:00 |
September | 5875316.58 | 0.00 | 158.41 | 3568.02 | 27-SEP-06:07 | 0.00 | 33.92 | 39.63 | 0.00 | 0.00 | 0.00 | 0.01 | 27-SEP-06:07 |
October | 0.138386E+09 | 0.00 | 69.38 | 27984.60 | 25-OCT-06:03 | 0.00 | 37.11 | 39.38 | 0.00 | 0.00 | 0.00 | 0.11 | 25-OCT-06:03 |
November | 0.366839E+10 | 0.00 | 121.73 | 142612.10 | 27-NOV-06:11 | 0.00 | 30.15 | 35.03 | 0.01 | 0.00 | 0.01 | 0.57 | 27-NOV-06:11 |
December | 0.148878E+11 | 0.00 | 270.50 | 150258.43 | 14-DEC-07:02 | 0.00 | 27.13 | 37.99 | 0.06 | 0.00 | 0.02 | 0.60 | 14-DEC-07:02 |
Annual Sum or Average | 0.392381E+11 | 0.00 | 1714.68 | 0.00 | 33.64 | 38.93 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 1119822.28 | 0.00 | 23.54 | 7.53 | 0.00 | 27.13 | 35.03 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148878E+11 | 0.00 | 270.50 | 168608.75 | 0.00 | 39.12 | 44.20 | 0.06 | 0.00 | 0.02 | 0.67 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.964790E+09 | 0.242986E+09 | 49.17 | 0.957952E+09 | 6837932.24 | 0.00 | 0.59 | 03-JAN-15:10 | 0.00 | 01-JAN-00:10 | 17709.26 | 03-JAN-15:10 | 17709.26 | 03-JAN-15:10 | 497.07 | 02-JAN-13:00 | 4174.75 | 03-JAN-15:10 | 0.00 |
February | 0.353587E+10 | 0.852663E+09 | 105.17 | 0.352208E+10 | 13785586.81 | 0.00 | 0.91 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 30060.37 | 21-FEB-16:00 | 30060.37 | 21-FEB-16:00 | 704.42 | 27-FEB-16:20 | 6478.60 | 21-FEB-16:00 | 0.00 |
March | 0.852778E+10 | 0.201327E+10 | 198.54 | 0.851777E+10 | 10013771.91 | 0.00 | 1.00 | 14-MAR-15:30 | 0.00 | 01-MAR-00:10 | 36439.61 | 21-MAR-16:00 | 36439.61 | 21-MAR-16:00 | 365.15 | 03-MAR-19:20 | 7872.96 | 21-MAR-16:00 | 0.00 |
April | 0.262664E+11 | 0.618967E+10 | 328.27 | 0.261364E+11 | 0.129929E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 56629.44 | 21-APR-15:00 | 56629.44 | 21-APR-15:00 | 3012.34 | 18-APR-21:00 | 14860.87 | 21-APR-15:00 | 0.00 |
May | 0.511563E+11 | 0.122946E+11 | 441.37 | 0.500298E+11 | 0.112648E+10 | 0.00 | 1.00 | 01-MAY-14:10 | 0.00 | 01-MAY-00:10 | 70374.17 | 30-MAY-15:10 | 70374.17 | 30-MAY-15:10 | 12490.77 | 25-MAY-06:03 | 19669.53 | 30-MAY-15:00 | 0.00 |
June | 0.697805E+11 | 0.181415E+11 | 456.14 | 0.676408E+11 | 0.213971E+10 | 0.00 | 1.00 | 01-JUN-07:20 | 0.00 | 01-JUN-00:10 | 75183.86 | 19-JUN-06:03 | 73518.88 | 05-JUN-15:00 | 21589.86 | 19-JUN-18:00 | 23129.13 | 15-JUN-15:00 | 0.00 |
July | 0.821514E+11 | 0.202860E+11 | 469.60 | 0.673349E+11 | 0.148166E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 115418.17 | 20-JUL-14:55 | 88706.55 | 03-JUL-06:03 | 76484.02 | 21-JUL-06:03 | 23873.19 | 20-JUL-15:05 | 0.00 |
August | 0.759126E+11 | 0.184251E+11 | 480.12 | 0.664215E+11 | 0.949114E+10 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 108972.72 | 03-AUG-06:03 | 83797.77 | 07-AUG-06:03 | 62568.59 | 03-AUG-06:03 | 23056.52 | 07-AUG-16:00 | 0.00 |
September | 0.635476E+11 | 0.149603E+11 | 425.00 | 0.558565E+11 | 0.769110E+10 | 0.00 | 1.00 | 01-SEP-05:12 | 0.00 | 01-SEP-00:10 | 103645.62 | 23-SEP-06:03 | 69906.60 | 18-SEP-16:00 | 62487.52 | 22-SEP-06:03 | 21872.10 | 23-SEP-06:03 | 0.00 |
October | 0.329739E+11 | 0.749930E+10 | 345.69 | 0.297826E+11 | 0.319134E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 77173.05 | 04-OCT-10:40 | 67129.79 | 02-OCT-04:02 | 28049.45 | 04-OCT-10:40 | 18743.09 | 03-OCT-14:10 | 0.00 |
November | 0.748216E+10 | 0.174407E+10 | 161.06 | 0.735757E+10 | 0.124583E+09 | 0.00 | 1.00 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 42274.82 | 03-NOV-16:00 | 42274.82 | 03-NOV-16:00 | 3040.12 | 03-NOV-11:10 | 8898.95 | 03-NOV-16:00 | 0.00 |
December | 0.358440E+09 | 93938624.06 | 29.50 | 0.356800E+09 | 1640709.84 | 0.00 | 0.29 | 20-DEC-15:10 | 0.00 | 01-DEC-00:10 | 8054.96 | 20-DEC-15:10 | 8054.96 | 20-DEC-15:10 | 363.01 | 10-DEC-12:50 | 2049.12 | 20-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.422658E+12 | 0.102743E+12 | 3489.63 | 0.383915E+12 | 0.387431E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.358440E+09 | 93938624.06 | 29.50 | 0.356800E+09 | 1640709.84 | 0.00 | 0.29 | 0.00 | 8054.96 | 8054.96 | 363.01 | 2049.12 | 0.00 | ||||||
Maximum of Months | 0.821514E+11 | 0.202860E+11 | 480.12 | 0.676408E+11 | 0.148166E+11 | 0.00 | 1.00 | 0.00 | 115418.17 | 88706.55 | 76484.02 | 23873.19 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.765057E+09 | 0.194665E+09 | 48.00 | 0.756460E+09 | 8596091.51 | 0.00 | 0.49 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 13583.29 | 12-JAN-15:00 | 13583.29 | 12-JAN-15:00 | 508.72 | 12-JAN-17:15 | 3282.41 | 12-JAN-15:00 | 0.00 |
February | 0.319757E+10 | 0.779691E+09 | 108.83 | 0.318154E+10 | 16027069.71 | 0.00 | 0.83 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 24947.95 | 21-FEB-16:00 | 24947.95 | 21-FEB-16:00 | 813.51 | 27-FEB-16:00 | 5508.78 | 21-FEB-16:00 | 0.00 |
March | 0.796811E+10 | 0.189475E+10 | 212.72 | 0.795862E+10 | 9496307.06 | 0.00 | 1.00 | 14-MAR-15:40 | 0.00 | 01-MAR-00:10 | 32786.96 | 21-MAR-16:00 | 32786.96 | 21-MAR-16:00 | 325.85 | 11-MAR-16:00 | 7084.28 | 21-MAR-16:00 | 0.00 |
April | 0.246549E+11 | 0.583785E+10 | 342.68 | 0.245231E+11 | 0.131779E+09 | 0.00 | 1.00 | 03-APR-11:40 | 0.00 | 01-APR-00:10 | 54629.80 | 21-APR-15:00 | 54629.80 | 21-APR-15:00 | 3170.28 | 18-APR-21:00 | 14334.97 | 21-APR-15:00 | 0.00 |
May | 0.466860E+11 | 0.112553E+11 | 444.80 | 0.457535E+11 | 0.932532E+09 | 0.00 | 1.00 | 01-MAY-14:40 | 0.00 | 01-MAY-00:10 | 67374.06 | 30-MAY-06:03 | 67374.06 | 30-MAY-06:03 | 9094.10 | 28-MAY-07:52 | 18351.68 | 30-MAY-14:40 | 0.00 |
June | 0.636910E+11 | 0.165973E+11 | 455.92 | 0.619894E+11 | 0.170166E+10 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 76491.70 | 19-JUN-06:03 | 68114.71 | 15-JUN-14:30 | 18756.97 | 19-JUN-18:00 | 21374.66 | 15-JUN-14:40 | 0.00 |
July | 0.713571E+11 | 0.176413E+11 | 466.11 | 0.593655E+11 | 0.119916E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 108210.76 | 20-JUL-15:00 | 80899.18 | 03-JUL-06:03 | 70870.91 | 17-JUL-06:03 | 22382.40 | 20-JUL-15:05 | 0.00 |
August | 0.637291E+11 | 0.155616E+11 | 474.37 | 0.565664E+11 | 0.716269E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 88410.77 | 05-AUG-05:03 | 75514.54 | 07-AUG-04:02 | 46637.15 | 03-AUG-06:03 | 20551.79 | 07-AUG-16:00 | 0.00 |
September | 0.515145E+11 | 0.122225E+11 | 416.54 | 0.458371E+11 | 0.567741E+10 | 0.00 | 1.00 | 01-SEP-07:05 | 0.00 | 01-SEP-00:10 | 80732.38 | 14-SEP-09:50 | 62658.04 | 18-SEP-15:20 | 38805.76 | 14-SEP-09:50 | 17144.56 | 14-SEP-09:50 | 0.00 |
October | 0.264679E+11 | 0.608336E+10 | 335.33 | 0.238833E+11 | 0.258461E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 63849.38 | 02-OCT-04:02 | 63849.38 | 02-OCT-04:02 | 20503.63 | 04-OCT-10:30 | 16752.98 | 03-OCT-14:00 | 0.00 |
November | 0.598837E+10 | 0.141987E+10 | 159.25 | 0.583502E+10 | 0.153348E+09 | 0.00 | 1.00 | 03-NOV-14:50 | 0.00 | 01-NOV-00:10 | 34512.37 | 09-NOV-15:20 | 34512.37 | 09-NOV-15:20 | 3646.40 | 03-NOV-11:00 | 7246.64 | 09-NOV-15:20 | 0.00 |
December | 0.277516E+09 | 73121743.33 | 27.89 | 0.276606E+09 | 910430.47 | 0.00 | 0.23 | 20-DEC-15:00 | 0.00 | 01-DEC-00:10 | 6024.18 | 20-DEC-15:00 | 6024.18 | 20-DEC-15:00 | 270.89 | 10-DEC-12:50 | 1553.25 | 20-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.366297E+12 | 0.895614E+11 | 3492.45 | 0.335926E+12 | 0.303707E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.277516E+09 | 73121743.33 | 27.89 | 0.276606E+09 | 910430.47 | 0.00 | 0.23 | 0.00 | 6024.18 | 6024.18 | 270.89 | 1553.25 | 0.00 | ||||||
Maximum of Months | 0.713571E+11 | 0.176413E+11 | 474.37 | 0.619894E+11 | 0.119916E+11 | 0.00 | 1.00 | 0.00 | 108210.76 | 80899.18 | 70870.91 | 22382.40 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.714516E+09 | 0.184187E+09 | 47.10 | 0.695983E+09 | 18532844.12 | 0.00 | 0.40 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 12434.84 | 03-JAN-15:00 | 12434.84 | 03-JAN-15:00 | 731.07 | 12-JAN-17:03 | 3073.37 | 03-JAN-15:00 | 0.00 |
February | 0.306347E+10 | 0.758917E+09 | 105.68 | 0.303659E+10 | 26875896.14 | 0.00 | 0.79 | 20-FEB-14:53 | 0.00 | 01-FEB-00:10 | 26793.01 | 20-FEB-14:53 | 26793.01 | 20-FEB-14:53 | 982.95 | 27-FEB-15:00 | 5982.55 | 20-FEB-14:53 | 0.00 |
March | 0.794904E+10 | 0.191494E+10 | 209.74 | 0.792476E+10 | 24272128.82 | 0.00 | 0.99 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 35697.67 | 21-MAR-16:00 | 35697.67 | 21-MAR-16:00 | 510.81 | 15-MAR-09:40 | 7729.56 | 21-MAR-16:00 | 0.00 |
April | 0.267805E+11 | 0.638778E+10 | 342.32 | 0.265753E+11 | 0.205180E+09 | 0.00 | 1.00 | 03-APR-12:00 | 0.00 | 01-APR-00:10 | 63205.54 | 21-APR-14:40 | 63205.54 | 21-APR-14:40 | 3831.55 | 18-APR-21:00 | 16584.59 | 21-APR-14:40 | 0.00 |
May | 0.511824E+11 | 0.124381E+11 | 445.90 | 0.499452E+11 | 0.123715E+10 | 0.00 | 1.00 | 02-MAY-14:40 | 0.00 | 01-MAY-00:10 | 78205.62 | 21-MAY-15:11 | 78205.62 | 21-MAY-15:11 | 12436.60 | 24-MAY-11:00 | 21962.48 | 21-MAY-14:32 | 0.00 |
June | 0.709625E+11 | 0.186329E+11 | 458.16 | 0.688332E+11 | 0.212934E+10 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 80293.61 | 15-JUN-14:40 | 80293.61 | 15-JUN-14:40 | 20690.36 | 19-JUN-18:00 | 25242.18 | 15-JUN-14:40 | 0.00 |
July | 0.783100E+11 | 0.195022E+11 | 468.66 | 0.655285E+11 | 0.127815E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 123446.38 | 20-JUL-14:55 | 83043.89 | 03-JUL-14:30 | 80227.07 | 20-JUL-14:55 | 25694.36 | 21-JUL-10:50 | 0.00 |
August | 0.693731E+11 | 0.170938E+11 | 475.66 | 0.613897E+11 | 0.798349E+10 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 84112.43 | 07-AUG-04:02 | 84112.43 | 07-AUG-04:02 | 40229.74 | 02-AUG-08:30 | 23529.76 | 07-AUG-16:00 | 0.00 |
September | 0.551374E+11 | 0.131967E+11 | 416.45 | 0.488823E+11 | 0.625511E+10 | 0.00 | 1.00 | 01-SEP-07:30 | 0.00 | 01-SEP-00:10 | 84928.72 | 14-SEP-10:00 | 71581.43 | 18-SEP-15:20 | 41793.57 | 14-SEP-10:00 | 19268.19 | 19-SEP-15:20 | 0.00 |
October | 0.271807E+11 | 0.632077E+10 | 330.44 | 0.242468E+11 | 0.293393E+10 | 0.00 | 1.00 | 01-OCT-11:32 | 0.00 | 01-OCT-00:10 | 72878.74 | 03-OCT-13:50 | 65761.88 | 05-OCT-16:00 | 19474.21 | 04-OCT-10:40 | 19098.15 | 03-OCT-14:00 | 0.00 |
November | 0.544780E+10 | 0.131674E+10 | 153.47 | 0.524305E+10 | 0.204750E+09 | 0.00 | 0.97 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 34971.61 | 09-NOV-15:00 | 34971.61 | 09-NOV-15:00 | 3313.30 | 03-NOV-11:50 | 7401.55 | 09-NOV-15:00 | 0.00 |
December | 0.251911E+09 | 66652727.70 | 25.83 | 0.249285E+09 | 2626664.86 | 0.00 | 0.21 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 6005.81 | 23-DEC-15:00 | 6005.81 | 23-DEC-15:00 | 213.31 | 08-DEC-16:20 | 1559.01 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.396353E+12 | 0.978138E+11 | 3479.41 | 0.362551E+12 | 0.338027E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.251911E+09 | 66652727.70 | 25.83 | 0.249285E+09 | 2626664.86 | 0.00 | 0.21 | 0.00 | 6005.81 | 6005.81 | 213.31 | 1559.01 | 0.00 | ||||||
Maximum of Months | 0.783100E+11 | 0.195022E+11 | 475.66 | 0.688332E+11 | 0.127815E+11 | 0.00 | 1.00 | 0.00 | 123446.38 | 84112.43 | 80227.07 | 25694.36 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 289.47 | 0.00 | 289.47 | 69.24 | 1441.73 | 0.00 | 0.00 | 0.00 |
February | 353.47 | 0.00 | 353.47 | 165.72 | 1306.84 | 0.00 | 0.00 | 0.00 |
March | 462.58 | 0.00 | 462.58 | 323.01 | 1117.05 | 0.00 | 0.00 | 0.00 |
April | 534.10 | 4.21 | 529.90 | 609.65 | 665.46 | 0.00 | 0.00 | 0.00 |
May | 633.47 | 45.81 | 587.66 | 1016.55 | 395.22 | 0.00 | 0.00 | 0.00 |
June | 673.58 | 82.93 | 590.66 | 1416.17 | 216.59 | 0.00 | 0.00 | 0.00 |
July | 622.52 | 60.60 | 561.92 | 1300.06 | 173.92 | 0.00 | 0.00 | 0.00 |
August | 524.92 | 10.73 | 514.19 | 1011.58 | 232.97 | 0.00 | 0.00 | 0.00 |
September | 458.04 | 0.18 | 457.86 | 768.17 | 464.61 | 0.00 | 0.00 | 0.00 |
October | 380.30 | 0.00 | 380.30 | 402.13 | 738.37 | 0.00 | 0.00 | 0.00 |
November | 307.02 | 0.00 | 307.02 | 112.73 | 1246.21 | 0.00 | 0.00 | 0.00 |
December | 287.23 | 0.00 | 287.23 | 49.29 | 1589.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.08 | 17.13 | 443.96 | 605.94 | 796.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 287.23 | 0.00 | 287.23 | 49.29 | 173.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 673.58 | 82.93 | 590.66 | 1416.17 | 1589.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.16 | 280.00 | 236.16 | 508.87 | 886.77 | 0.00 | 0.00 | 0.00 |
February | 690.57 | 393.62 | 296.95 | 782.99 | 802.59 | 0.00 | 0.00 | 0.00 |
March | 852.63 | 469.77 | 382.86 | 1047.54 | 690.61 | 0.00 | 0.00 | 0.00 |
April | 1027.37 | 569.96 | 457.41 | 1491.36 | 422.88 | 0.00 | 0.00 | 0.00 |
May | 1060.19 | 576.18 | 484.02 | 1731.57 | 263.55 | 0.00 | 0.00 | 0.00 |
June | 1060.79 | 590.14 | 470.65 | 1956.61 | 141.83 | 0.00 | 0.00 | 0.00 |
July | 951.30 | 497.32 | 453.98 | 1760.20 | 115.69 | 0.00 | 0.00 | 0.00 |
August | 905.21 | 463.28 | 441.93 | 1615.18 | 154.21 | 0.00 | 0.00 | 0.00 |
September | 896.82 | 511.70 | 385.12 | 1495.11 | 292.93 | 0.00 | 0.00 | 0.00 |
October | 689.71 | 372.23 | 317.48 | 971.59 | 470.53 | 0.00 | 0.00 | 0.00 |
November | 618.26 | 359.93 | 258.33 | 688.90 | 767.12 | 0.00 | 0.00 | 0.00 |
December | 515.71 | 273.24 | 242.48 | 483.55 | 971.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 815.48 | 446.21 | 369.28 | 1212.48 | 496.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.71 | 273.24 | 236.16 | 483.55 | 115.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1060.79 | 590.14 | 484.02 | 1956.61 | 971.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1980.26 | 1500.25 | 480.01 | 2645.96 | 1330.45 | 0.00 | 0.00 | 0.00 |
February | 1836.91 | 1294.99 | 541.92 | 2493.60 | 1217.07 | 0.00 | 0.00 | 0.00 |
March | 1492.87 | 860.78 | 632.08 | 2084.09 | 1091.12 | 0.00 | 0.00 | 0.00 |
April | 1012.16 | 377.66 | 634.50 | 1594.48 | 693.44 | 0.00 | 0.00 | 0.00 |
May | 715.28 | 100.12 | 615.17 | 1254.07 | 420.89 | 0.00 | 0.00 | 0.00 |
June | 617.11 | 39.16 | 577.95 | 1340.61 | 220.67 | 0.00 | 0.00 | 0.00 |
July | 629.07 | 58.32 | 570.76 | 1353.68 | 179.54 | 0.00 | 0.00 | 0.00 |
August | 801.90 | 212.27 | 589.63 | 1621.78 | 245.45 | 0.00 | 0.00 | 0.00 |
September | 1251.67 | 650.28 | 601.38 | 2298.20 | 475.72 | 0.00 | 0.00 | 0.00 |
October | 1700.65 | 1149.75 | 550.90 | 2671.09 | 737.61 | 0.00 | 0.00 | 0.00 |
November | 2046.57 | 1560.26 | 486.31 | 2865.17 | 1159.43 | 0.00 | 0.00 | 0.00 |
December | 2028.23 | 1522.48 | 505.75 | 2664.78 | 1431.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1339.88 | 774.26 | 565.62 | 2071.05 | 764.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 617.11 | 39.16 | 480.01 | 1254.07 | 179.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2046.57 | 1560.26 | 634.50 | 2865.17 | 1431.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 543.71 | 306.20 | 237.51 | 597.85 | 934.74 | 0.00 | 0.00 | 0.00 |
February | 613.52 | 326.10 | 287.42 | 719.03 | 856.67 | 0.00 | 0.00 | 0.00 |
March | 836.06 | 448.10 | 387.96 | 1075.63 | 740.50 | 0.00 | 0.00 | 0.00 |
April | 960.98 | 519.04 | 441.94 | 1436.25 | 463.62 | 0.00 | 0.00 | 0.00 |
May | 1035.07 | 553.81 | 481.26 | 1721.96 | 292.30 | 0.00 | 0.00 | 0.00 |
June | 1007.56 | 541.17 | 466.39 | 1888.65 | 159.27 | 0.00 | 0.00 | 0.00 |
July | 894.14 | 444.31 | 449.82 | 1680.48 | 128.15 | 0.00 | 0.00 | 0.00 |
August | 865.92 | 441.31 | 424.62 | 1565.69 | 169.01 | 0.00 | 0.00 | 0.00 |
September | 885.54 | 493.34 | 392.21 | 1519.13 | 324.93 | 0.00 | 0.00 | 0.00 |
October | 762.31 | 444.91 | 317.40 | 1139.29 | 500.66 | 0.00 | 0.00 | 0.00 |
November | 639.84 | 389.60 | 250.25 | 792.80 | 814.00 | 0.00 | 0.00 | 0.00 |
December | 515.62 | 280.10 | 235.52 | 540.08 | 1020.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 797.35 | 432.62 | 364.73 | 1225.17 | 532.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.62 | 280.10 | 235.52 | 540.08 | 128.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1035.07 | 553.81 | 481.26 | 1888.65 | 1020.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.49 | 0.00 | 96.49 | 20.34 | 513.52 | 0.00 | 0.00 | 0.00 |
February | 117.82 | 0.00 | 117.82 | 56.94 | 446.91 | 0.00 | 0.00 | 0.00 |
March | 154.19 | 0.00 | 154.19 | 116.37 | 370.33 | 0.00 | 0.00 | 0.00 |
April | 178.03 | 1.40 | 176.62 | 214.56 | 215.73 | 0.00 | 0.00 | 0.00 |
May | 211.15 | 15.27 | 195.88 | 349.63 | 127.09 | 0.00 | 0.00 | 0.00 |
June | 224.52 | 27.64 | 196.88 | 482.70 | 67.34 | 0.00 | 0.00 | 0.00 |
July | 207.50 | 20.20 | 187.30 | 440.99 | 56.12 | 0.00 | 0.00 | 0.00 |
August | 174.97 | 3.58 | 171.39 | 339.70 | 80.47 | 0.00 | 0.00 | 0.00 |
September | 152.67 | 0.06 | 152.61 | 254.93 | 166.02 | 0.00 | 0.00 | 0.00 |
October | 126.76 | 0.00 | 126.76 | 129.48 | 271.23 | 0.00 | 0.00 | 0.00 |
November | 102.33 | 0.00 | 102.33 | 31.84 | 463.52 | 0.00 | 0.00 | 0.00 |
December | 95.74 | 0.00 | 95.74 | 12.02 | 580.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.69 | 5.71 | 147.98 | 204.88 | 279.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.74 | 0.00 | 95.74 | 12.02 | 56.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.52 | 27.64 | 196.88 | 482.70 | 580.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.49 | 0.00 | 96.49 | 20.34 | 513.55 | 0.00 | 0.00 | 0.00 |
February | 117.82 | 0.00 | 117.82 | 56.94 | 446.94 | 0.00 | 0.00 | 0.00 |
March | 154.19 | 0.00 | 154.19 | 116.38 | 370.35 | 0.00 | 0.00 | 0.00 |
April | 178.03 | 1.40 | 176.63 | 214.57 | 215.74 | 0.00 | 0.00 | 0.00 |
May | 211.15 | 15.27 | 195.89 | 349.64 | 127.10 | 0.00 | 0.00 | 0.00 |
June | 224.53 | 27.64 | 196.89 | 482.72 | 67.34 | 0.00 | 0.00 | 0.00 |
July | 207.51 | 20.20 | 187.31 | 441.01 | 56.12 | 0.00 | 0.00 | 0.00 |
August | 174.97 | 3.58 | 171.40 | 339.72 | 80.48 | 0.00 | 0.00 | 0.00 |
September | 152.68 | 0.06 | 152.62 | 254.94 | 166.03 | 0.00 | 0.00 | 0.00 |
October | 126.77 | 0.00 | 126.77 | 129.49 | 271.25 | 0.00 | 0.00 | 0.00 |
November | 102.34 | 0.00 | 102.34 | 31.84 | 463.55 | 0.00 | 0.00 | 0.00 |
December | 95.74 | 0.00 | 95.74 | 12.02 | 580.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.69 | 5.71 | 147.99 | 204.89 | 279.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.74 | 0.00 | 95.74 | 12.02 | 56.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.53 | 27.64 | 196.89 | 482.72 | 580.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.49 | 0.00 | 96.49 | 20.34 | 513.55 | 0.00 | 0.00 | 0.00 |
February | 117.82 | 0.00 | 117.82 | 56.94 | 446.94 | 0.00 | 0.00 | 0.00 |
March | 154.19 | 0.00 | 154.19 | 116.38 | 370.35 | 0.00 | 0.00 | 0.00 |
April | 178.03 | 1.40 | 176.63 | 214.57 | 215.74 | 0.00 | 0.00 | 0.00 |
May | 211.15 | 15.27 | 195.89 | 349.64 | 127.10 | 0.00 | 0.00 | 0.00 |
June | 224.53 | 27.64 | 196.89 | 482.72 | 67.34 | 0.00 | 0.00 | 0.00 |
July | 207.51 | 20.20 | 187.31 | 441.01 | 56.12 | 0.00 | 0.00 | 0.00 |
August | 174.97 | 3.58 | 171.40 | 339.72 | 80.48 | 0.00 | 0.00 | 0.00 |
September | 152.68 | 0.06 | 152.62 | 254.94 | 166.03 | 0.00 | 0.00 | 0.00 |
October | 126.77 | 0.00 | 126.77 | 129.49 | 271.25 | 0.00 | 0.00 | 0.00 |
November | 102.34 | 0.00 | 102.34 | 31.84 | 463.55 | 0.00 | 0.00 | 0.00 |
December | 95.74 | 0.00 | 95.74 | 12.02 | 580.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.69 | 5.71 | 147.99 | 204.89 | 279.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.74 | 0.00 | 95.74 | 12.02 | 56.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.53 | 27.64 | 196.89 | 482.72 | 580.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 496.52 | 269.34 | 227.18 | 479.35 | 928.93 | 0.00 | 0.00 | 0.00 |
February | 664.29 | 378.64 | 285.65 | 753.28 | 813.87 | 0.00 | 0.00 | 0.00 |
March | 820.18 | 451.89 | 368.29 | 1021.98 | 681.79 | 0.00 | 0.00 | 0.00 |
April | 988.28 | 548.27 | 440.01 | 1453.87 | 415.07 | 0.00 | 0.00 | 0.00 |
May | 1019.85 | 554.25 | 465.60 | 1686.03 | 257.34 | 0.00 | 0.00 | 0.00 |
June | 1020.43 | 567.68 | 452.75 | 1901.77 | 135.50 | 0.00 | 0.00 | 0.00 |
July | 915.10 | 478.40 | 436.70 | 1706.38 | 115.11 | 0.00 | 0.00 | 0.00 |
August | 870.77 | 445.65 | 425.12 | 1558.93 | 161.63 | 0.00 | 0.00 | 0.00 |
September | 862.69 | 492.23 | 370.47 | 1437.35 | 310.97 | 0.00 | 0.00 | 0.00 |
October | 663.47 | 358.06 | 305.40 | 927.10 | 507.41 | 0.00 | 0.00 | 0.00 |
November | 594.74 | 346.24 | 248.50 | 642.84 | 836.47 | 0.00 | 0.00 | 0.00 |
December | 496.09 | 262.84 | 233.25 | 444.71 | 1039.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 784.45 | 429.23 | 355.23 | 1169.11 | 515.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.09 | 262.84 | 227.18 | 444.71 | 115.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1020.43 | 567.68 | 465.60 | 1901.77 | 1039.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.63 | 10.65 | 8.98 | 18.95 | 36.73 | 0.00 | 0.00 | 0.00 |
February | 26.27 | 14.97 | 11.29 | 29.78 | 32.18 | 0.00 | 0.00 | 0.00 |
March | 32.43 | 17.87 | 14.56 | 40.41 | 26.96 | 0.00 | 0.00 | 0.00 |
April | 39.08 | 21.68 | 17.40 | 57.48 | 16.41 | 0.00 | 0.00 | 0.00 |
May | 40.32 | 21.91 | 18.41 | 66.66 | 10.18 | 0.00 | 0.00 | 0.00 |
June | 40.35 | 22.45 | 17.90 | 75.19 | 5.36 | 0.00 | 0.00 | 0.00 |
July | 36.18 | 18.92 | 17.27 | 67.47 | 4.55 | 0.00 | 0.00 | 0.00 |
August | 34.43 | 17.62 | 16.81 | 61.64 | 6.39 | 0.00 | 0.00 | 0.00 |
September | 34.11 | 19.46 | 14.65 | 56.83 | 12.30 | 0.00 | 0.00 | 0.00 |
October | 26.23 | 14.16 | 12.08 | 36.66 | 20.06 | 0.00 | 0.00 | 0.00 |
November | 23.52 | 13.69 | 9.83 | 25.42 | 33.07 | 0.00 | 0.00 | 0.00 |
December | 19.61 | 10.39 | 9.22 | 17.58 | 41.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.02 | 16.97 | 14.05 | 46.23 | 20.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.61 | 10.39 | 8.98 | 17.58 | 4.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.35 | 22.45 | 18.41 | 75.19 | 41.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 660.07 | 500.07 | 160.00 | 883.59 | 494.14 | 0.00 | 0.00 | 0.00 |
February | 612.29 | 431.65 | 180.64 | 838.41 | 436.50 | 0.00 | 0.00 | 0.00 |
March | 497.62 | 286.92 | 210.69 | 708.38 | 375.24 | 0.00 | 0.00 | 0.00 |
April | 337.38 | 125.88 | 211.50 | 544.17 | 231.47 | 0.00 | 0.00 | 0.00 |
May | 238.43 | 33.37 | 205.05 | 429.54 | 136.97 | 0.00 | 0.00 | 0.00 |
June | 205.70 | 13.05 | 192.65 | 455.93 | 68.94 | 0.00 | 0.00 | 0.00 |
July | 209.69 | 19.44 | 190.25 | 457.60 | 58.77 | 0.00 | 0.00 | 0.00 |
August | 267.30 | 70.75 | 196.54 | 542.92 | 87.06 | 0.00 | 0.00 | 0.00 |
September | 417.22 | 216.76 | 200.46 | 766.85 | 175.40 | 0.00 | 0.00 | 0.00 |
October | 566.87 | 383.24 | 183.63 | 889.23 | 277.57 | 0.00 | 0.00 | 0.00 |
November | 682.18 | 520.08 | 162.10 | 949.69 | 441.99 | 0.00 | 0.00 | 0.00 |
December | 676.07 | 507.48 | 168.58 | 883.70 | 536.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.62 | 258.08 | 188.54 | 694.84 | 275.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.70 | 13.05 | 160.00 | 429.54 | 58.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 682.18 | 520.08 | 211.50 | 949.69 | 536.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 660.07 | 500.07 | 160.00 | 883.59 | 494.14 | 0.00 | 0.00 | 0.00 |
February | 612.29 | 431.65 | 180.64 | 838.41 | 436.50 | 0.00 | 0.00 | 0.00 |
March | 497.62 | 286.92 | 210.69 | 708.38 | 375.24 | 0.00 | 0.00 | 0.00 |
April | 337.38 | 125.88 | 211.50 | 544.17 | 231.47 | 0.00 | 0.00 | 0.00 |
May | 238.43 | 33.37 | 205.05 | 429.54 | 136.97 | 0.00 | 0.00 | 0.00 |
June | 205.70 | 13.05 | 192.65 | 455.93 | 68.94 | 0.00 | 0.00 | 0.00 |
July | 209.69 | 19.44 | 190.25 | 457.60 | 58.77 | 0.00 | 0.00 | 0.00 |
August | 267.30 | 70.75 | 196.54 | 542.92 | 87.06 | 0.00 | 0.00 | 0.00 |
September | 417.22 | 216.76 | 200.46 | 766.85 | 175.40 | 0.00 | 0.00 | 0.00 |
October | 566.87 | 383.24 | 183.63 | 889.23 | 277.57 | 0.00 | 0.00 | 0.00 |
November | 682.18 | 520.08 | 162.10 | 949.69 | 441.99 | 0.00 | 0.00 | 0.00 |
December | 676.07 | 507.48 | 168.58 | 883.70 | 536.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.62 | 258.08 | 188.54 | 694.84 | 275.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.70 | 13.05 | 160.00 | 429.54 | 58.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 682.18 | 520.08 | 211.50 | 949.69 | 536.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 660.03 | 500.04 | 159.99 | 883.53 | 494.11 | 0.00 | 0.00 | 0.00 |
February | 612.25 | 431.63 | 180.63 | 838.36 | 436.48 | 0.00 | 0.00 | 0.00 |
March | 497.58 | 286.90 | 210.68 | 708.33 | 375.21 | 0.00 | 0.00 | 0.00 |
April | 337.36 | 125.88 | 211.48 | 544.14 | 231.46 | 0.00 | 0.00 | 0.00 |
May | 238.41 | 33.37 | 205.04 | 429.51 | 136.96 | 0.00 | 0.00 | 0.00 |
June | 205.69 | 13.05 | 192.64 | 455.90 | 68.94 | 0.00 | 0.00 | 0.00 |
July | 209.68 | 19.44 | 190.24 | 457.57 | 58.76 | 0.00 | 0.00 | 0.00 |
August | 267.28 | 70.75 | 196.53 | 542.88 | 87.06 | 0.00 | 0.00 | 0.00 |
September | 417.19 | 216.74 | 200.45 | 766.81 | 175.39 | 0.00 | 0.00 | 0.00 |
October | 566.84 | 383.22 | 183.62 | 889.17 | 277.55 | 0.00 | 0.00 | 0.00 |
November | 682.14 | 520.04 | 162.09 | 949.63 | 441.96 | 0.00 | 0.00 | 0.00 |
December | 676.02 | 507.45 | 168.57 | 883.65 | 536.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 446.59 | 258.06 | 188.53 | 694.80 | 275.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.69 | 13.05 | 159.99 | 429.51 | 58.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 682.14 | 520.04 | 211.48 | 949.63 | 536.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 523.03 | 294.55 | 228.47 | 572.91 | 979.66 | 0.00 | 0.00 | 0.00 |
February | 590.18 | 313.69 | 276.49 | 699.34 | 867.22 | 0.00 | 0.00 | 0.00 |
March | 804.25 | 431.05 | 373.20 | 1053.56 | 734.58 | 0.00 | 0.00 | 0.00 |
April | 924.42 | 499.29 | 425.12 | 1400.37 | 457.23 | 0.00 | 0.00 | 0.00 |
May | 995.69 | 532.73 | 462.95 | 1676.29 | 287.90 | 0.00 | 0.00 | 0.00 |
June | 969.22 | 520.58 | 448.65 | 1834.04 | 152.71 | 0.00 | 0.00 | 0.00 |
July | 860.12 | 427.41 | 432.71 | 1627.53 | 127.86 | 0.00 | 0.00 | 0.00 |
August | 832.98 | 424.52 | 408.46 | 1510.45 | 178.44 | 0.00 | 0.00 | 0.00 |
September | 851.85 | 474.56 | 377.29 | 1460.26 | 346.45 | 0.00 | 0.00 | 0.00 |
October | 733.30 | 427.98 | 305.32 | 1086.58 | 544.78 | 0.00 | 0.00 | 0.00 |
November | 615.50 | 374.77 | 240.73 | 749.86 | 891.85 | 0.00 | 0.00 | 0.00 |
December | 496.00 | 269.44 | 226.56 | 509.93 | 1089.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 767.02 | 416.16 | 350.86 | 1183.76 | 553.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.00 | 269.44 | 226.56 | 509.93 | 127.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 995.69 | 532.73 | 462.95 | 1834.04 | 1089.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.68 | 11.65 | 9.03 | 22.65 | 38.74 | 0.00 | 0.00 | 0.00 |
February | 23.34 | 12.40 | 10.93 | 27.65 | 34.29 | 0.00 | 0.00 | 0.00 |
March | 31.80 | 17.04 | 14.76 | 41.66 | 29.04 | 0.00 | 0.00 | 0.00 |
April | 36.55 | 19.74 | 16.81 | 55.37 | 18.08 | 0.00 | 0.00 | 0.00 |
May | 39.37 | 21.06 | 18.30 | 66.28 | 11.38 | 0.00 | 0.00 | 0.00 |
June | 38.32 | 20.58 | 17.74 | 72.52 | 6.04 | 0.00 | 0.00 | 0.00 |
July | 34.01 | 16.90 | 17.11 | 64.35 | 5.06 | 0.00 | 0.00 | 0.00 |
August | 32.94 | 16.78 | 16.15 | 59.72 | 7.06 | 0.00 | 0.00 | 0.00 |
September | 33.68 | 18.76 | 14.92 | 57.74 | 13.70 | 0.00 | 0.00 | 0.00 |
October | 28.99 | 16.92 | 12.07 | 42.96 | 21.54 | 0.00 | 0.00 | 0.00 |
November | 24.34 | 14.82 | 9.52 | 29.65 | 35.26 | 0.00 | 0.00 | 0.00 |
December | 19.61 | 10.65 | 8.96 | 20.16 | 43.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.33 | 16.45 | 13.87 | 46.80 | 21.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.61 | 10.65 | 8.96 | 20.16 | 5.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.37 | 21.06 | 18.30 | 72.52 | 43.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 289.47 | 0.00 | 289.47 | 55.48 | 1560.32 | 0.00 | 0.00 | 0.00 |
February | 353.47 | 0.00 | 353.47 | 149.73 | 1404.65 | 0.00 | 0.00 | 0.00 |
March | 462.58 | 0.00 | 462.58 | 308.03 | 1191.11 | 0.00 | 0.00 | 0.00 |
April | 534.10 | 4.21 | 529.90 | 605.33 | 702.66 | 0.00 | 0.00 | 0.00 |
May | 633.47 | 45.81 | 587.66 | 1018.20 | 409.95 | 0.00 | 0.00 | 0.00 |
June | 673.58 | 82.93 | 590.66 | 1425.22 | 220.39 | 0.00 | 0.00 | 0.00 |
July | 622.52 | 60.60 | 561.92 | 1311.10 | 176.40 | 0.00 | 0.00 | 0.00 |
August | 524.92 | 10.73 | 514.19 | 1018.16 | 241.07 | 0.00 | 0.00 | 0.00 |
September | 458.04 | 0.18 | 457.86 | 768.83 | 486.71 | 0.00 | 0.00 | 0.00 |
October | 380.30 | 0.00 | 380.30 | 391.48 | 792.66 | 0.00 | 0.00 | 0.00 |
November | 307.02 | 0.00 | 307.02 | 96.98 | 1361.62 | 0.00 | 0.00 | 0.00 |
December | 287.23 | 0.00 | 287.23 | 36.54 | 1722.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.08 | 17.13 | 443.96 | 601.07 | 853.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 287.23 | 0.00 | 287.23 | 36.54 | 176.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 673.58 | 82.93 | 590.66 | 1425.22 | 1722.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.16 | 280.00 | 236.16 | 490.88 | 955.19 | 0.00 | 0.00 | 0.00 |
February | 690.57 | 393.62 | 296.95 | 765.81 | 856.56 | 0.00 | 0.00 | 0.00 |
March | 852.63 | 469.77 | 382.86 | 1035.91 | 728.85 | 0.00 | 0.00 | 0.00 |
April | 1027.37 | 569.96 | 457.41 | 1490.13 | 440.93 | 0.00 | 0.00 | 0.00 |
May | 1060.19 | 576.18 | 484.02 | 1735.85 | 272.42 | 0.00 | 0.00 | 0.00 |
June | 1060.79 | 590.14 | 470.65 | 1964.92 | 144.41 | 0.00 | 0.00 | 0.00 |
July | 951.30 | 497.32 | 453.98 | 1769.25 | 117.46 | 0.00 | 0.00 | 0.00 |
August | 905.21 | 463.28 | 441.93 | 1621.40 | 159.18 | 0.00 | 0.00 | 0.00 |
September | 896.82 | 511.70 | 385.12 | 1496.79 | 304.44 | 0.00 | 0.00 | 0.00 |
October | 689.71 | 372.23 | 317.48 | 965.34 | 499.93 | 0.00 | 0.00 | 0.00 |
November | 618.26 | 359.93 | 258.33 | 670.78 | 828.11 | 0.00 | 0.00 | 0.00 |
December | 515.71 | 273.24 | 242.48 | 462.35 | 1046.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 815.48 | 446.21 | 369.28 | 1207.21 | 527.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.71 | 273.24 | 236.16 | 462.35 | 117.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1060.79 | 590.14 | 484.02 | 1964.92 | 1046.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1980.26 | 1500.25 | 480.01 | 2623.02 | 1430.96 | 0.00 | 0.00 | 0.00 |
February | 1836.91 | 1294.99 | 541.92 | 2473.59 | 1300.76 | 0.00 | 0.00 | 0.00 |
March | 1492.87 | 860.78 | 632.08 | 2070.62 | 1155.54 | 0.00 | 0.00 | 0.00 |
April | 1012.16 | 377.66 | 634.50 | 1593.00 | 729.91 | 0.00 | 0.00 | 0.00 |
May | 715.28 | 100.12 | 615.17 | 1257.51 | 439.21 | 0.00 | 0.00 | 0.00 |
June | 617.11 | 39.16 | 577.95 | 1348.86 | 225.95 | 0.00 | 0.00 | 0.00 |
July | 629.07 | 58.32 | 570.76 | 1363.97 | 183.34 | 0.00 | 0.00 | 0.00 |
August | 801.90 | 212.27 | 589.63 | 1629.37 | 254.73 | 0.00 | 0.00 | 0.00 |
September | 1251.67 | 650.28 | 601.38 | 2301.70 | 496.86 | 0.00 | 0.00 | 0.00 |
October | 1700.65 | 1149.75 | 550.90 | 2663.75 | 782.81 | 0.00 | 0.00 | 0.00 |
November | 2046.57 | 1560.26 | 486.31 | 2840.74 | 1247.36 | 0.00 | 0.00 | 0.00 |
December | 2028.23 | 1522.48 | 505.75 | 2632.83 | 1539.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1339.88 | 774.26 | 565.62 | 2063.73 | 813.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 617.11 | 39.16 | 480.01 | 1257.51 | 183.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2046.57 | 1560.26 | 634.50 | 2840.74 | 1539.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 543.71 | 306.20 | 237.51 | 587.54 | 1007.41 | 0.00 | 0.00 | 0.00 |
February | 613.52 | 326.10 | 287.42 | 709.47 | 917.11 | 0.00 | 0.00 | 0.00 |
March | 836.06 | 448.10 | 387.96 | 1067.99 | 787.15 | 0.00 | 0.00 | 0.00 |
April | 960.98 | 519.04 | 441.94 | 1434.50 | 488.28 | 0.00 | 0.00 | 0.00 |
May | 1035.07 | 553.81 | 481.26 | 1725.35 | 304.72 | 0.00 | 0.00 | 0.00 |
June | 1007.56 | 541.17 | 466.39 | 1895.26 | 162.69 | 0.00 | 0.00 | 0.00 |
July | 894.14 | 444.31 | 449.82 | 1687.82 | 130.74 | 0.00 | 0.00 | 0.00 |
August | 865.92 | 441.31 | 424.62 | 1570.66 | 175.25 | 0.00 | 0.00 | 0.00 |
September | 885.54 | 493.34 | 392.21 | 1520.11 | 339.63 | 0.00 | 0.00 | 0.00 |
October | 762.31 | 444.91 | 317.40 | 1132.88 | 535.05 | 0.00 | 0.00 | 0.00 |
November | 639.84 | 389.60 | 250.25 | 781.44 | 883.00 | 0.00 | 0.00 | 0.00 |
December | 515.62 | 280.10 | 235.52 | 527.99 | 1100.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 797.35 | 432.62 | 364.73 | 1222.22 | 567.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.62 | 280.10 | 235.52 | 527.99 | 130.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1035.07 | 553.81 | 481.26 | 1895.26 | 1100.92 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.775318E+09 | 0.00 | 0.775318E+09 | 0.185443E+09 | 0.386154E+10 |
February | 0.855125E+09 | 0.00 | 0.855125E+09 | 0.400913E+09 | 0.316150E+10 |
March | 0.123898E+10 | 0.00 | 0.123898E+10 | 0.865144E+09 | 0.299191E+10 |
April | 0.138440E+10 | 10907061.00 | 0.137349E+10 | 0.158020E+10 | 0.172487E+10 |
May | 0.169668E+10 | 0.122694E+09 | 0.157399E+10 | 0.272272E+10 | 0.105855E+10 |
June | 0.174593E+10 | 0.214944E+09 | 0.153099E+10 | 0.367071E+10 | 0.561410E+09 |
July | 0.166736E+10 | 0.162305E+09 | 0.150506E+10 | 0.348207E+10 | 0.465822E+09 |
August | 0.140595E+10 | 28748062.13 | 0.137720E+10 | 0.270942E+10 | 0.623980E+09 |
September | 0.118724E+10 | 473753.19 | 0.118677E+10 | 0.199109E+10 | 0.120426E+10 |
October | 0.101860E+10 | 0.00 | 0.101860E+10 | 0.107705E+10 | 0.197764E+10 |
November | 0.795784E+09 | 0.00 | 0.795784E+09 | 0.292205E+09 | 0.323017E+10 |
December | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.132017E+09 | 0.425852E+10 |
Annual Sum or Average | 0.145407E+11 | 0.540072E+09 | 0.140006E+11 | 0.191090E+11 | 0.251202E+11 |
Minimum of Months | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.132017E+09 | 0.465822E+09 |
Maximum of Months | 0.174593E+10 | 0.214944E+09 | 0.157399E+10 | 0.367071E+10 | 0.425852E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138248E+10 | 0.749943E+09 | 0.632532E+09 | 0.136295E+10 | 0.237512E+10 |
February | 0.167062E+10 | 0.952246E+09 | 0.718379E+09 | 0.189421E+10 | 0.194163E+10 |
March | 0.228367E+10 | 0.125823E+10 | 0.102544E+10 | 0.280573E+10 | 0.184973E+10 |
April | 0.266295E+10 | 0.147734E+10 | 0.118561E+10 | 0.386560E+10 | 0.109609E+10 |
May | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.463784E+10 | 0.705904E+09 |
June | 0.274957E+10 | 0.152964E+10 | 0.121993E+10 | 0.507154E+10 | 0.367613E+09 |
July | 0.254795E+10 | 0.133203E+10 | 0.121593E+10 | 0.471452E+10 | 0.309866E+09 |
August | 0.242452E+10 | 0.124084E+10 | 0.118367E+10 | 0.432610E+10 | 0.413028E+09 |
September | 0.232455E+10 | 0.132633E+10 | 0.998225E+09 | 0.387534E+10 | 0.759279E+09 |
October | 0.184732E+10 | 0.996980E+09 | 0.850338E+09 | 0.260231E+10 | 0.126026E+10 |
November | 0.160254E+10 | 0.932947E+09 | 0.669592E+09 | 0.178563E+10 | 0.198838E+10 |
December | 0.138129E+10 | 0.731838E+09 | 0.649451E+09 | 0.129515E+10 | 0.260074E+10 |
Annual Sum or Average | 0.257171E+11 | 0.140716E+11 | 0.116455E+11 | 0.382369E+11 | 0.156676E+11 |
Minimum of Months | 0.138129E+10 | 0.731838E+09 | 0.632532E+09 | 0.129515E+10 | 0.309866E+09 |
Maximum of Months | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.507154E+10 | 0.260074E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530392E+10 | 0.401827E+10 | 0.128565E+10 | 0.708695E+10 | 0.356347E+10 |
February | 0.444385E+10 | 0.313284E+10 | 0.131100E+10 | 0.603251E+10 | 0.294433E+10 |
March | 0.399850E+10 | 0.230552E+10 | 0.169298E+10 | 0.558202E+10 | 0.292246E+10 |
April | 0.262352E+10 | 0.978900E+09 | 0.164462E+10 | 0.413288E+10 | 0.179740E+10 |
May | 0.191581E+10 | 0.268151E+09 | 0.164766E+10 | 0.335890E+10 | 0.112731E+10 |
June | 0.159954E+10 | 0.101492E+09 | 0.149805E+10 | 0.347486E+10 | 0.571981E+09 |
July | 0.168491E+10 | 0.156194E+09 | 0.152872E+10 | 0.362569E+10 | 0.480869E+09 |
August | 0.214780E+10 | 0.568535E+09 | 0.157926E+10 | 0.434377E+10 | 0.657422E+09 |
September | 0.324432E+10 | 0.168554E+10 | 0.155878E+10 | 0.595694E+10 | 0.123306E+10 |
October | 0.455502E+10 | 0.307950E+10 | 0.147552E+10 | 0.715424E+10 | 0.197562E+10 |
November | 0.530472E+10 | 0.404420E+10 | 0.126052E+10 | 0.742653E+10 | 0.300523E+10 |
December | 0.543242E+10 | 0.407782E+10 | 0.135460E+10 | 0.713734E+10 | 0.383497E+10 |
Annual Sum or Average | 0.422543E+11 | 0.244170E+11 | 0.178374E+11 | 0.653126E+11 | 0.241141E+11 |
Minimum of Months | 0.159954E+10 | 0.101492E+09 | 0.126052E+10 | 0.335890E+10 | 0.480869E+09 |
Maximum of Months | 0.543242E+10 | 0.407782E+10 | 0.169298E+10 | 0.742653E+10 | 0.383497E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145628E+10 | 0.820137E+09 | 0.636146E+09 | 0.160128E+10 | 0.250362E+10 |
February | 0.148424E+10 | 0.788905E+09 | 0.695334E+09 | 0.173947E+10 | 0.207246E+10 |
March | 0.223930E+10 | 0.120019E+10 | 0.103911E+10 | 0.288096E+10 | 0.198336E+10 |
April | 0.249086E+10 | 0.134536E+10 | 0.114550E+10 | 0.372277E+10 | 0.120169E+10 |
May | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.461211E+10 | 0.782890E+09 |
June | 0.261159E+10 | 0.140271E+10 | 0.120888E+10 | 0.489537E+10 | 0.412818E+09 |
July | 0.239485E+10 | 0.119005E+10 | 0.120480E+10 | 0.450099E+10 | 0.343244E+09 |
August | 0.231929E+10 | 0.118200E+10 | 0.113729E+10 | 0.419354E+10 | 0.452675E+09 |
September | 0.229533E+10 | 0.127873E+10 | 0.101660E+10 | 0.393760E+10 | 0.842224E+09 |
October | 0.204176E+10 | 0.119164E+10 | 0.850124E+09 | 0.305148E+10 | 0.134098E+10 |
November | 0.165848E+10 | 0.100984E+10 | 0.648641E+09 | 0.205494E+10 | 0.210989E+10 |
December | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.144654E+10 | 0.273379E+10 |
Annual Sum or Average | 0.251453E+11 | 0.136431E+11 | 0.115022E+11 | 0.386370E+11 | 0.167796E+11 |
Minimum of Months | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.144654E+10 | 0.343244E+09 |
Maximum of Months | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.489537E+10 | 0.273379E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258427E+09 | 0.00 | 0.258427E+09 | 54480826.83 | 0.137542E+10 |
February | 0.285028E+09 | 0.00 | 0.285028E+09 | 0.137745E+09 | 0.108117E+10 |
March | 0.412975E+09 | 0.00 | 0.412975E+09 | 0.311690E+09 | 0.991901E+09 |
April | 0.461445E+09 | 3635514.99 | 0.457809E+09 | 0.556144E+09 | 0.559160E+09 |
May | 0.565533E+09 | 40895929.42 | 0.524637E+09 | 0.936439E+09 | 0.340403E+09 |
June | 0.581949E+09 | 71644763.78 | 0.510305E+09 | 0.125115E+10 | 0.174545E+09 |
July | 0.555762E+09 | 54099169.65 | 0.501663E+09 | 0.118114E+10 | 0.150313E+09 |
August | 0.468628E+09 | 9582234.00 | 0.459046E+09 | 0.909852E+09 | 0.215535E+09 |
September | 0.395729E+09 | 157910.26 | 0.395571E+09 | 0.660768E+09 | 0.430324E+09 |
October | 0.339517E+09 | 0.00 | 0.339517E+09 | 0.346807E+09 | 0.726466E+09 |
November | 0.265249E+09 | 0.00 | 0.265249E+09 | 82536531.26 | 0.120144E+10 |
December | 0.256426E+09 | 0.00 | 0.256426E+09 | 32201654.66 | 0.155564E+10 |
Annual Sum or Average | 0.484667E+10 | 0.180016E+09 | 0.466665E+10 | 0.646096E+10 | 0.880232E+10 |
Minimum of Months | 0.256426E+09 | 0.00 | 0.256426E+09 | 32201654.66 | 0.150313E+09 |
Maximum of Months | 0.581949E+09 | 71644763.78 | 0.524637E+09 | 0.125115E+10 | 0.155564E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258438E+09 | 0.00 | 0.258438E+09 | 54481054.53 | 0.137550E+10 |
February | 0.285040E+09 | 0.00 | 0.285040E+09 | 0.137750E+09 | 0.108124E+10 |
March | 0.412993E+09 | 0.00 | 0.412993E+09 | 0.311702E+09 | 0.991958E+09 |
April | 0.461465E+09 | 3635612.71 | 0.457829E+09 | 0.556171E+09 | 0.559191E+09 |
May | 0.565557E+09 | 40897028.72 | 0.524660E+09 | 0.936484E+09 | 0.340419E+09 |
June | 0.581974E+09 | 71646689.61 | 0.510327E+09 | 0.125122E+10 | 0.174553E+09 |
July | 0.555785E+09 | 54100623.85 | 0.501685E+09 | 0.118120E+10 | 0.150320E+09 |
August | 0.468649E+09 | 9582491.57 | 0.459066E+09 | 0.909899E+09 | 0.215546E+09 |
September | 0.395747E+09 | 157914.50 | 0.395589E+09 | 0.660803E+09 | 0.430346E+09 |
October | 0.339532E+09 | 0.00 | 0.339532E+09 | 0.346822E+09 | 0.726507E+09 |
November | 0.265260E+09 | 0.00 | 0.265260E+09 | 82539143.27 | 0.120152E+10 |
December | 0.256437E+09 | 0.00 | 0.256437E+09 | 32201558.84 | 0.155573E+10 |
Annual Sum or Average | 0.484688E+10 | 0.180020E+09 | 0.466686E+10 | 0.646127E+10 | 0.880283E+10 |
Minimum of Months | 0.256437E+09 | 0.00 | 0.256437E+09 | 32201558.84 | 0.150320E+09 |
Maximum of Months | 0.581974E+09 | 71646689.61 | 0.524660E+09 | 0.125122E+10 | 0.155573E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.258438E+09 | 0.00 | 0.258438E+09 | 54481054.53 | 0.137550E+10 |
February | 0.285040E+09 | 0.00 | 0.285040E+09 | 0.137750E+09 | 0.108124E+10 |
March | 0.412993E+09 | 0.00 | 0.412993E+09 | 0.311702E+09 | 0.991958E+09 |
April | 0.461465E+09 | 3635612.71 | 0.457829E+09 | 0.556171E+09 | 0.559191E+09 |
May | 0.565557E+09 | 40897028.72 | 0.524660E+09 | 0.936484E+09 | 0.340419E+09 |
June | 0.581974E+09 | 71646689.61 | 0.510327E+09 | 0.125122E+10 | 0.174553E+09 |
July | 0.555785E+09 | 54100623.85 | 0.501685E+09 | 0.118120E+10 | 0.150320E+09 |
August | 0.468649E+09 | 9582491.57 | 0.459066E+09 | 0.909899E+09 | 0.215546E+09 |
September | 0.395747E+09 | 157914.50 | 0.395589E+09 | 0.660803E+09 | 0.430346E+09 |
October | 0.339532E+09 | 0.00 | 0.339532E+09 | 0.346822E+09 | 0.726507E+09 |
November | 0.265260E+09 | 0.00 | 0.265260E+09 | 82539143.27 | 0.120152E+10 |
December | 0.256437E+09 | 0.00 | 0.256437E+09 | 32201558.84 | 0.155573E+10 |
Annual Sum or Average | 0.484688E+10 | 0.180020E+09 | 0.466686E+10 | 0.646127E+10 | 0.880283E+10 |
Minimum of Months | 0.256437E+09 | 0.00 | 0.256437E+09 | 32201558.84 | 0.150320E+09 |
Maximum of Months | 0.581974E+09 | 71646689.61 | 0.524660E+09 | 0.125122E+10 | 0.155573E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132987E+10 | 0.721405E+09 | 0.608467E+09 | 0.128390E+10 | 0.248805E+10 |
February | 0.160706E+10 | 0.916009E+09 | 0.691047E+09 | 0.182235E+10 | 0.196891E+10 |
March | 0.219678E+10 | 0.121035E+10 | 0.986429E+09 | 0.273728E+10 | 0.182612E+10 |
April | 0.256162E+10 | 0.142112E+10 | 0.114050E+10 | 0.376843E+10 | 0.107587E+10 |
May | 0.273157E+10 | 0.148450E+10 | 0.124707E+10 | 0.451587E+10 | 0.689267E+09 |
June | 0.264494E+10 | 0.147143E+10 | 0.117352E+10 | 0.492939E+10 | 0.351211E+09 |
July | 0.245100E+10 | 0.128134E+10 | 0.116967E+10 | 0.457036E+10 | 0.308322E+09 |
August | 0.233226E+10 | 0.119363E+10 | 0.113864E+10 | 0.417544E+10 | 0.432917E+09 |
September | 0.223610E+10 | 0.127585E+10 | 0.960247E+09 | 0.372561E+10 | 0.806036E+09 |
October | 0.177703E+10 | 0.959041E+09 | 0.817987E+09 | 0.248314E+10 | 0.135905E+10 |
November | 0.154156E+10 | 0.897445E+09 | 0.644117E+09 | 0.166625E+10 | 0.216813E+10 |
December | 0.132873E+10 | 0.703988E+09 | 0.624742E+09 | 0.119112E+10 | 0.278363E+10 |
Annual Sum or Average | 0.247385E+11 | 0.135361E+11 | 0.112024E+11 | 0.368691E+11 | 0.162575E+11 |
Minimum of Months | 0.132873E+10 | 0.703988E+09 | 0.608467E+09 | 0.119112E+10 | 0.308322E+09 |
Maximum of Months | 0.273157E+10 | 0.148450E+10 | 0.124707E+10 | 0.492939E+10 | 0.278363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52581944.28 | 28523704.99 | 24058239.29 | 50764104.51 | 98375426.33 |
February | 63541558.72 | 36218162.94 | 27323395.78 | 72053913.99 | 77848887.98 |
March | 86858705.00 | 47856182.44 | 39002522.56 | 0.108230E+09 | 72203020.88 |
April | 0.101284E+09 | 56189925.25 | 45094365.84 | 0.149000E+09 | 42538788.60 |
May | 0.108004E+09 | 58695847.52 | 49308016.15 | 0.178553E+09 | 27252987.71 |
June | 0.104579E+09 | 58178917.64 | 46399826.11 | 0.194904E+09 | 13886561.23 |
July | 96910484.51 | 50662919.39 | 46247565.12 | 0.180708E+09 | 12190782.78 |
August | 92215566.60 | 47194882.78 | 45020683.82 | 0.165093E+09 | 17117141.59 |
September | 88413450.76 | 50446137.29 | 37967313.47 | 0.147307E+09 | 31869945.01 |
October | 70262059.20 | 37919600.19 | 32342459.02 | 98181222.40 | 53735601.14 |
November | 60951973.59 | 35484158.54 | 25467815.05 | 65882086.93 | 85725904.74 |
December | 52536782.79 | 27835062.02 | 24701720.76 | 47095772.18 | 0.110062E+09 |
Annual Sum or Average | 0.978139E+09 | 0.535206E+09 | 0.442934E+09 | 0.145777E+10 | 0.642807E+09 |
Minimum of Months | 52536782.79 | 27835062.02 | 24058239.29 | 47095772.18 | 12190782.78 |
Maximum of Months | 0.108004E+09 | 58695847.52 | 49308016.15 | 0.194904E+09 | 0.110062E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176794E+10 | 0.133940E+10 | 0.428544E+09 | 0.236661E+10 | 0.132350E+10 |
February | 0.148126E+10 | 0.104426E+10 | 0.436997E+09 | 0.202828E+10 | 0.105599E+10 |
March | 0.133281E+10 | 0.768492E+09 | 0.564320E+09 | 0.189731E+10 | 0.100503E+10 |
April | 0.874496E+09 | 0.326293E+09 | 0.548202E+09 | 0.141050E+10 | 0.599983E+09 |
May | 0.638599E+09 | 89381728.24 | 0.549218E+09 | 0.115047E+10 | 0.366863E+09 |
June | 0.533179E+09 | 33829815.37 | 0.499350E+09 | 0.118177E+10 | 0.178700E+09 |
July | 0.561634E+09 | 52063639.22 | 0.509570E+09 | 0.122562E+10 | 0.157397E+09 |
August | 0.715925E+09 | 0.189508E+09 | 0.526418E+09 | 0.145415E+10 | 0.233189E+09 |
September | 0.108143E+10 | 0.561835E+09 | 0.519591E+09 | 0.198769E+10 | 0.454641E+09 |
October | 0.151831E+10 | 0.102648E+10 | 0.491836E+09 | 0.238171E+10 | 0.743431E+09 |
November | 0.176821E+10 | 0.134804E+10 | 0.420170E+09 | 0.246161E+10 | 0.114564E+10 |
December | 0.181077E+10 | 0.135925E+10 | 0.451528E+09 | 0.236691E+10 | 0.143816E+10 |
Annual Sum or Average | 0.140846E+11 | 0.813882E+10 | 0.594574E+10 | 0.219126E+11 | 0.870252E+10 |
Minimum of Months | 0.533179E+09 | 33829815.37 | 0.420170E+09 | 0.115047E+10 | 0.157397E+09 |
Maximum of Months | 0.181077E+10 | 0.135925E+10 | 0.564320E+09 | 0.246161E+10 | 0.143816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176794E+10 | 0.133940E+10 | 0.428544E+09 | 0.236661E+10 | 0.132350E+10 |
February | 0.148126E+10 | 0.104426E+10 | 0.436997E+09 | 0.202828E+10 | 0.105599E+10 |
March | 0.133281E+10 | 0.768492E+09 | 0.564320E+09 | 0.189731E+10 | 0.100503E+10 |
April | 0.874496E+09 | 0.326293E+09 | 0.548202E+09 | 0.141050E+10 | 0.599983E+09 |
May | 0.638599E+09 | 89381728.24 | 0.549218E+09 | 0.115047E+10 | 0.366863E+09 |
June | 0.533179E+09 | 33829815.37 | 0.499350E+09 | 0.118177E+10 | 0.178700E+09 |
July | 0.561634E+09 | 52063639.22 | 0.509570E+09 | 0.122562E+10 | 0.157397E+09 |
August | 0.715925E+09 | 0.189508E+09 | 0.526418E+09 | 0.145415E+10 | 0.233189E+09 |
September | 0.108143E+10 | 0.561835E+09 | 0.519591E+09 | 0.198769E+10 | 0.454641E+09 |
October | 0.151831E+10 | 0.102648E+10 | 0.491836E+09 | 0.238171E+10 | 0.743431E+09 |
November | 0.176821E+10 | 0.134804E+10 | 0.420170E+09 | 0.246161E+10 | 0.114564E+10 |
December | 0.181077E+10 | 0.135925E+10 | 0.451528E+09 | 0.236691E+10 | 0.143816E+10 |
Annual Sum or Average | 0.140846E+11 | 0.813882E+10 | 0.594574E+10 | 0.219126E+11 | 0.870252E+10 |
Minimum of Months | 0.533179E+09 | 33829815.37 | 0.420170E+09 | 0.115047E+10 | 0.157397E+09 |
Maximum of Months | 0.181077E+10 | 0.135925E+10 | 0.564320E+09 | 0.246161E+10 | 0.143816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.176783E+10 | 0.133931E+10 | 0.428517E+09 | 0.236646E+10 | 0.132342E+10 |
February | 0.148116E+10 | 0.104419E+10 | 0.436969E+09 | 0.202815E+10 | 0.105592E+10 |
March | 0.133273E+10 | 0.768443E+09 | 0.564285E+09 | 0.189719E+10 | 0.100497E+10 |
April | 0.874440E+09 | 0.326273E+09 | 0.548168E+09 | 0.141041E+10 | 0.599945E+09 |
May | 0.638559E+09 | 89376079.82 | 0.549183E+09 | 0.115040E+10 | 0.366840E+09 |
June | 0.533146E+09 | 33827677.51 | 0.499318E+09 | 0.118169E+10 | 0.178688E+09 |
July | 0.561598E+09 | 52060349.09 | 0.509538E+09 | 0.122555E+10 | 0.157387E+09 |
August | 0.715880E+09 | 0.189496E+09 | 0.526384E+09 | 0.145406E+10 | 0.233174E+09 |
September | 0.108136E+10 | 0.561799E+09 | 0.519558E+09 | 0.198756E+10 | 0.454613E+09 |
October | 0.151822E+10 | 0.102641E+10 | 0.491805E+09 | 0.238156E+10 | 0.743384E+09 |
November | 0.176810E+10 | 0.134795E+10 | 0.420143E+09 | 0.246145E+10 | 0.114557E+10 |
December | 0.181066E+10 | 0.135916E+10 | 0.451499E+09 | 0.236676E+10 | 0.143807E+10 |
Annual Sum or Average | 0.140837E+11 | 0.813831E+10 | 0.594537E+10 | 0.219112E+11 | 0.870197E+10 |
Minimum of Months | 0.533146E+09 | 33827677.51 | 0.420143E+09 | 0.115040E+10 | 0.157387E+09 |
Maximum of Months | 0.181066E+10 | 0.135916E+10 | 0.564285E+09 | 0.246145E+10 | 0.143807E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140087E+10 | 0.788931E+09 | 0.611944E+09 | 0.153447E+10 | 0.262393E+10 |
February | 0.142777E+10 | 0.758886E+09 | 0.668881E+09 | 0.169185E+10 | 0.209797E+10 |
March | 0.215410E+10 | 0.115452E+10 | 0.999579E+09 | 0.282184E+10 | 0.196750E+10 |
April | 0.239609E+10 | 0.129417E+10 | 0.110192E+10 | 0.362976E+10 | 0.118514E+10 |
May | 0.266684E+10 | 0.142688E+10 | 0.123997E+10 | 0.448978E+10 | 0.771123E+09 |
June | 0.251223E+10 | 0.134934E+10 | 0.116289E+10 | 0.475382E+10 | 0.395823E+09 |
July | 0.230374E+10 | 0.114477E+10 | 0.115897E+10 | 0.435918E+10 | 0.342462E+09 |
August | 0.223105E+10 | 0.113702E+10 | 0.109403E+10 | 0.404559E+10 | 0.477945E+09 |
September | 0.220800E+10 | 0.123007E+10 | 0.977923E+09 | 0.378499E+10 | 0.898008E+09 |
October | 0.196408E+10 | 0.114630E+10 | 0.817782E+09 | 0.291029E+10 | 0.145914E+10 |
November | 0.159538E+10 | 0.971411E+09 | 0.623965E+09 | 0.194363E+10 | 0.231166E+10 |
December | 0.132849E+10 | 0.721679E+09 | 0.606816E+09 | 0.136578E+10 | 0.291793E+10 |
Annual Sum or Average | 0.241886E+11 | 0.131240E+11 | 0.110647E+11 | 0.373310E+11 | 0.174486E+11 |
Minimum of Months | 0.132849E+10 | 0.721679E+09 | 0.606816E+09 | 0.136578E+10 | 0.342462E+09 |
Maximum of Months | 0.266684E+10 | 0.142688E+10 | 0.123997E+10 | 0.475382E+10 | 0.291793E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55389168.40 | 31193500.79 | 24195667.61 | 60671357.46 | 0.103748E+09 |
February | 56452480.86 | 30005586.87 | 26446893.98 | 66893921.19 | 82951809.32 |
March | 85170831.06 | 45648445.41 | 39522385.65 | 0.111573E+09 | 77793214.37 |
April | 94738942.45 | 51169990.13 | 43568952.32 | 0.143517E+09 | 46859248.97 |
May | 0.105444E+09 | 56417244.49 | 49027066.66 | 0.177521E+09 | 30489463.33 |
June | 99330854.99 | 53351356.51 | 45979498.48 | 0.187961E+09 | 15650478.21 |
July | 91087428.42 | 45262943.57 | 45824484.85 | 0.172358E+09 | 13540615.77 |
August | 88213505.29 | 44956793.89 | 43256711.40 | 0.159958E+09 | 18897482.79 |
September | 87301918.45 | 48635799.14 | 38666119.31 | 0.149655E+09 | 35506392.85 |
October | 77657722.05 | 45323431.39 | 32334290.66 | 0.115070E+09 | 57692949.13 |
November | 63079569.73 | 38408610.79 | 24670958.94 | 76849225.01 | 91401096.59 |
December | 52527332.60 | 28534433.65 | 23992898.95 | 54001695.40 | 0.115372E+09 |
Annual Sum or Average | 0.956394E+09 | 0.518908E+09 | 0.437486E+09 | 0.147603E+10 | 0.689903E+09 |
Minimum of Months | 52527332.60 | 28534433.65 | 23992898.95 | 54001695.40 | 13540615.77 |
Maximum of Months | 0.105444E+09 | 56417244.49 | 49027066.66 | 0.187961E+09 | 0.115372E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.775318E+09 | 0.00 | 0.775318E+09 | 0.148595E+09 | 0.417915E+10 |
February | 0.855125E+09 | 0.00 | 0.855125E+09 | 0.362225E+09 | 0.339813E+10 |
March | 0.123898E+10 | 0.00 | 0.123898E+10 | 0.825022E+09 | 0.319026E+10 |
April | 0.138440E+10 | 10907061.00 | 0.137349E+10 | 0.156901E+10 | 0.182129E+10 |
May | 0.169668E+10 | 0.122694E+09 | 0.157399E+10 | 0.272714E+10 | 0.109800E+10 |
June | 0.174593E+10 | 0.214944E+09 | 0.153099E+10 | 0.369418E+10 | 0.571250E+09 |
July | 0.166736E+10 | 0.162305E+09 | 0.150506E+10 | 0.351166E+10 | 0.472474E+09 |
August | 0.140595E+10 | 28748062.13 | 0.137720E+10 | 0.272703E+10 | 0.645677E+09 |
September | 0.118724E+10 | 473753.19 | 0.118677E+10 | 0.199281E+10 | 0.126155E+10 |
October | 0.101860E+10 | 0.00 | 0.101860E+10 | 0.104854E+10 | 0.212306E+10 |
November | 0.795784E+09 | 0.00 | 0.795784E+09 | 0.251383E+09 | 0.352932E+10 |
December | 0.769314E+09 | 0.00 | 0.769314E+09 | 97863424.07 | 0.461375E+10 |
Annual Sum or Average | 0.145407E+11 | 0.540072E+09 | 0.140006E+11 | 0.189555E+11 | 0.269039E+11 |
Minimum of Months | 0.769314E+09 | 0.00 | 0.769314E+09 | 97863424.07 | 0.472474E+09 |
Maximum of Months | 0.174593E+10 | 0.214944E+09 | 0.157399E+10 | 0.369418E+10 | 0.461375E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138248E+10 | 0.749943E+09 | 0.632532E+09 | 0.131478E+10 | 0.255837E+10 |
February | 0.167062E+10 | 0.952246E+09 | 0.718379E+09 | 0.185265E+10 | 0.207220E+10 |
March | 0.228367E+10 | 0.125823E+10 | 0.102544E+10 | 0.277458E+10 | 0.195216E+10 |
April | 0.266295E+10 | 0.147734E+10 | 0.118561E+10 | 0.386240E+10 | 0.114290E+10 |
May | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.464930E+10 | 0.729656E+09 |
June | 0.274957E+10 | 0.152964E+10 | 0.121993E+10 | 0.509307E+10 | 0.374315E+09 |
July | 0.254795E+10 | 0.133203E+10 | 0.121593E+10 | 0.473875E+10 | 0.314601E+09 |
August | 0.242452E+10 | 0.124084E+10 | 0.118367E+10 | 0.434277E+10 | 0.426340E+09 |
September | 0.232455E+10 | 0.132633E+10 | 0.998225E+09 | 0.387968E+10 | 0.789114E+09 |
October | 0.184732E+10 | 0.996980E+09 | 0.850338E+09 | 0.258558E+10 | 0.133900E+10 |
November | 0.160254E+10 | 0.932947E+09 | 0.669592E+09 | 0.173865E+10 | 0.214646E+10 |
December | 0.138129E+10 | 0.731838E+09 | 0.649451E+09 | 0.123835E+10 | 0.280328E+10 |
Annual Sum or Average | 0.257171E+11 | 0.140716E+11 | 0.116455E+11 | 0.380706E+11 | 0.166484E+11 |
Minimum of Months | 0.138129E+10 | 0.731838E+09 | 0.632532E+09 | 0.123835E+10 | 0.314601E+09 |
Maximum of Months | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.509307E+10 | 0.280328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.530392E+10 | 0.401827E+10 | 0.128565E+10 | 0.702549E+10 | 0.383268E+10 |
February | 0.444385E+10 | 0.313284E+10 | 0.131100E+10 | 0.598411E+10 | 0.314680E+10 |
March | 0.399850E+10 | 0.230552E+10 | 0.169298E+10 | 0.554594E+10 | 0.309501E+10 |
April | 0.262352E+10 | 0.978900E+09 | 0.164462E+10 | 0.412906E+10 | 0.189192E+10 |
May | 0.191581E+10 | 0.268151E+09 | 0.164766E+10 | 0.336813E+10 | 0.117639E+10 |
June | 0.159954E+10 | 0.101492E+09 | 0.149805E+10 | 0.349625E+10 | 0.585659E+09 |
July | 0.168491E+10 | 0.156194E+09 | 0.152872E+10 | 0.365326E+10 | 0.491049E+09 |
August | 0.214780E+10 | 0.568535E+09 | 0.157926E+10 | 0.436410E+10 | 0.682257E+09 |
September | 0.324432E+10 | 0.168554E+10 | 0.155878E+10 | 0.596600E+10 | 0.128787E+10 |
October | 0.455502E+10 | 0.307950E+10 | 0.147552E+10 | 0.713459E+10 | 0.209667E+10 |
November | 0.530472E+10 | 0.404420E+10 | 0.126052E+10 | 0.736319E+10 | 0.323316E+10 |
December | 0.543242E+10 | 0.407782E+10 | 0.135460E+10 | 0.705178E+10 | 0.412382E+10 |
Annual Sum or Average | 0.422543E+11 | 0.244170E+11 | 0.178374E+11 | 0.650819E+11 | 0.256433E+11 |
Minimum of Months | 0.159954E+10 | 0.101492E+09 | 0.126052E+10 | 0.336813E+10 | 0.491049E+09 |
Maximum of Months | 0.543242E+10 | 0.407782E+10 | 0.169298E+10 | 0.736319E+10 | 0.412382E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.145628E+10 | 0.820137E+09 | 0.636146E+09 | 0.157366E+10 | 0.269825E+10 |
February | 0.148424E+10 | 0.788905E+09 | 0.695334E+09 | 0.171636E+10 | 0.221867E+10 |
March | 0.223930E+10 | 0.120019E+10 | 0.103911E+10 | 0.286051E+10 | 0.210831E+10 |
April | 0.249086E+10 | 0.134536E+10 | 0.114550E+10 | 0.371822E+10 | 0.126562E+10 |
May | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.462118E+10 | 0.816169E+09 |
June | 0.261159E+10 | 0.140271E+10 | 0.120888E+10 | 0.491250E+10 | 0.421696E+09 |
July | 0.239485E+10 | 0.119005E+10 | 0.120480E+10 | 0.452066E+10 | 0.350178E+09 |
August | 0.231929E+10 | 0.118200E+10 | 0.113729E+10 | 0.420685E+10 | 0.469389E+09 |
September | 0.229533E+10 | 0.127873E+10 | 0.101660E+10 | 0.394013E+10 | 0.880319E+09 |
October | 0.204176E+10 | 0.119164E+10 | 0.850124E+09 | 0.303431E+10 | 0.143309E+10 |
November | 0.165848E+10 | 0.100984E+10 | 0.648641E+09 | 0.202549E+10 | 0.228872E+10 |
December | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.141416E+10 | 0.294871E+10 |
Annual Sum or Average | 0.251453E+11 | 0.136431E+11 | 0.115022E+11 | 0.385440E+11 | 0.178991E+11 |
Minimum of Months | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.141416E+10 | 0.350178E+09 |
Maximum of Months | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.491250E+10 | 0.294871E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 69.24 | 1441.73 | 289.47 | 0.00 | 289.47 | 0.00 | 0.00 |
February | 165.72 | 1306.84 | 353.47 | 0.00 | 353.47 | 0.00 | 0.00 |
March | 323.01 | 1117.05 | 462.58 | 0.00 | 462.58 | 0.00 | 0.00 |
April | 609.65 | 665.46 | 534.10 | 4.21 | 529.90 | 0.00 | 0.00 |
May | 1016.55 | 395.22 | 633.47 | 45.81 | 587.66 | 0.00 | 0.00 |
June | 1416.17 | 216.59 | 673.58 | 82.93 | 590.66 | 0.00 | 0.00 |
July | 1300.06 | 173.92 | 622.52 | 60.60 | 561.92 | 0.00 | 0.00 |
August | 1011.58 | 232.97 | 524.92 | 10.73 | 514.19 | 0.00 | 0.00 |
September | 768.17 | 464.61 | 458.04 | 0.18 | 457.86 | 0.00 | 0.00 |
October | 402.13 | 738.37 | 380.30 | 0.00 | 380.30 | 0.00 | 0.00 |
November | 112.73 | 1246.21 | 307.02 | 0.00 | 307.02 | 0.00 | 0.00 |
December | 49.29 | 1589.95 | 287.23 | 0.00 | 287.23 | 0.00 | 0.00 |
Annual Sum or Average | 605.94 | 796.56 | 461.08 | 17.13 | 443.96 | 0.00 | 0.00 |
Minimum of Months | 49.29 | 173.92 | 287.23 | 0.00 | 287.23 | 0.00 | 0.00 |
Maximum of Months | 1416.17 | 1589.95 | 673.58 | 82.93 | 590.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 508.87 | 886.77 | 516.16 | 280.00 | 236.16 | 0.00 | 0.00 |
February | 782.99 | 802.59 | 690.57 | 393.62 | 296.95 | 0.00 | 0.00 |
March | 1047.54 | 690.61 | 852.63 | 469.77 | 382.86 | 0.00 | 0.00 |
April | 1491.36 | 422.88 | 1027.37 | 569.96 | 457.41 | 0.00 | 0.00 |
May | 1731.57 | 263.55 | 1060.19 | 576.18 | 484.02 | 0.00 | 0.00 |
June | 1956.61 | 141.83 | 1060.79 | 590.14 | 470.65 | 0.00 | 0.00 |
July | 1760.20 | 115.69 | 951.30 | 497.32 | 453.98 | 0.00 | 0.00 |
August | 1615.18 | 154.21 | 905.21 | 463.28 | 441.93 | 0.00 | 0.00 |
September | 1495.11 | 292.93 | 896.82 | 511.70 | 385.12 | 0.00 | 0.00 |
October | 971.59 | 470.53 | 689.71 | 372.23 | 317.48 | 0.00 | 0.00 |
November | 688.90 | 767.12 | 618.26 | 359.93 | 258.33 | 0.00 | 0.00 |
December | 483.55 | 971.01 | 515.71 | 273.24 | 242.48 | 0.00 | 0.00 |
Annual Sum or Average | 1212.48 | 496.82 | 815.48 | 446.21 | 369.28 | 0.00 | 0.00 |
Minimum of Months | 483.55 | 115.69 | 515.71 | 273.24 | 236.16 | 0.00 | 0.00 |
Maximum of Months | 1956.61 | 971.01 | 1060.79 | 590.14 | 484.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2645.96 | 1330.45 | 1980.26 | 1500.25 | 480.01 | 0.00 | 0.00 |
February | 2493.60 | 1217.07 | 1836.91 | 1294.99 | 541.92 | 0.00 | 0.00 |
March | 2084.09 | 1091.12 | 1492.87 | 860.78 | 632.08 | 0.00 | 0.00 |
April | 1594.48 | 693.44 | 1012.16 | 377.66 | 634.50 | 0.00 | 0.00 |
May | 1254.07 | 420.89 | 715.28 | 100.12 | 615.17 | 0.00 | 0.00 |
June | 1340.61 | 220.67 | 617.11 | 39.16 | 577.95 | 0.00 | 0.00 |
July | 1353.68 | 179.54 | 629.07 | 58.32 | 570.76 | 0.00 | 0.00 |
August | 1621.78 | 245.45 | 801.90 | 212.27 | 589.63 | 0.00 | 0.00 |
September | 2298.20 | 475.72 | 1251.67 | 650.28 | 601.38 | 0.00 | 0.00 |
October | 2671.09 | 737.61 | 1700.65 | 1149.75 | 550.90 | 0.00 | 0.00 |
November | 2865.17 | 1159.43 | 2046.57 | 1560.26 | 486.31 | 0.00 | 0.00 |
December | 2664.78 | 1431.81 | 2028.23 | 1522.48 | 505.75 | 0.00 | 0.00 |
Annual Sum or Average | 2071.05 | 764.65 | 1339.88 | 774.26 | 565.62 | 0.00 | 0.00 |
Minimum of Months | 1254.07 | 179.54 | 617.11 | 39.16 | 480.01 | 0.00 | 0.00 |
Maximum of Months | 2865.17 | 1431.81 | 2046.57 | 1560.26 | 634.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 597.85 | 934.74 | 543.71 | 306.20 | 237.51 | 0.00 | 0.00 |
February | 719.03 | 856.67 | 613.52 | 326.10 | 287.42 | 0.00 | 0.00 |
March | 1075.63 | 740.50 | 836.06 | 448.10 | 387.96 | 0.00 | 0.00 |
April | 1436.25 | 463.62 | 960.98 | 519.04 | 441.94 | 0.00 | 0.00 |
May | 1721.96 | 292.30 | 1035.07 | 553.81 | 481.26 | 0.00 | 0.00 |
June | 1888.65 | 159.27 | 1007.56 | 541.17 | 466.39 | 0.00 | 0.00 |
July | 1680.48 | 128.15 | 894.14 | 444.31 | 449.82 | 0.00 | 0.00 |
August | 1565.69 | 169.01 | 865.92 | 441.31 | 424.62 | 0.00 | 0.00 |
September | 1519.13 | 324.93 | 885.54 | 493.34 | 392.21 | 0.00 | 0.00 |
October | 1139.29 | 500.66 | 762.31 | 444.91 | 317.40 | 0.00 | 0.00 |
November | 792.80 | 814.00 | 639.84 | 389.60 | 250.25 | 0.00 | 0.00 |
December | 540.08 | 1020.68 | 515.62 | 280.10 | 235.52 | 0.00 | 0.00 |
Annual Sum or Average | 1225.17 | 532.08 | 797.35 | 432.62 | 364.73 | 0.00 | 0.00 |
Minimum of Months | 540.08 | 128.15 | 515.62 | 280.10 | 235.52 | 0.00 | 0.00 |
Maximum of Months | 1888.65 | 1020.68 | 1035.07 | 553.81 | 481.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 61.02 | 1540.63 | 289.47 | 0.00 | 289.47 | 0.00 | 0.00 |
February | 170.82 | 1340.79 | 353.47 | 0.00 | 353.47 | 0.00 | 0.00 |
March | 349.12 | 1111.04 | 462.58 | 0.00 | 462.58 | 0.00 | 0.00 |
April | 643.71 | 647.20 | 534.10 | 4.21 | 529.89 | 0.00 | 0.00 |
May | 1048.91 | 381.29 | 633.46 | 45.81 | 587.65 | 0.00 | 0.00 |
June | 1448.14 | 202.03 | 673.57 | 82.92 | 590.65 | 0.00 | 0.00 |
July | 1323.01 | 168.37 | 622.51 | 60.60 | 561.91 | 0.00 | 0.00 |
August | 1019.13 | 241.42 | 524.91 | 10.73 | 514.18 | 0.00 | 0.00 |
September | 764.80 | 498.08 | 458.03 | 0.18 | 457.85 | 0.00 | 0.00 |
October | 388.46 | 813.72 | 380.29 | 0.00 | 380.29 | 0.00 | 0.00 |
November | 95.53 | 1390.62 | 307.01 | 0.00 | 307.01 | 0.00 | 0.00 |
December | 36.07 | 1742.50 | 287.22 | 0.00 | 287.22 | 0.00 | 0.00 |
Annual Sum or Average | 614.65 | 837.39 | 461.07 | 17.13 | 443.95 | 0.00 | 0.00 |
Minimum of Months | 36.07 | 168.37 | 287.22 | 0.00 | 287.22 | 0.00 | 0.00 |
Maximum of Months | 1448.14 | 1742.50 | 673.57 | 82.92 | 590.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 498.31 | 965.66 | 516.15 | 279.99 | 236.16 | 0.00 | 0.00 |
February | 783.07 | 846.05 | 690.56 | 393.61 | 296.95 | 0.00 | 0.00 |
March | 1062.39 | 708.75 | 852.61 | 469.76 | 382.85 | 0.00 | 0.00 |
April | 1511.35 | 431.48 | 1027.36 | 569.95 | 457.41 | 0.00 | 0.00 |
May | 1752.70 | 267.52 | 1060.18 | 576.16 | 484.01 | 0.00 | 0.00 |
June | 1976.96 | 140.86 | 1060.77 | 590.13 | 470.65 | 0.00 | 0.00 |
July | 1773.85 | 119.67 | 951.28 | 497.31 | 453.97 | 0.00 | 0.00 |
August | 1620.57 | 168.02 | 905.20 | 463.27 | 441.93 | 0.00 | 0.00 |
September | 1494.18 | 323.27 | 896.80 | 511.69 | 385.11 | 0.00 | 0.00 |
October | 963.76 | 527.47 | 689.70 | 372.22 | 317.48 | 0.00 | 0.00 |
November | 668.26 | 869.54 | 618.25 | 359.93 | 258.33 | 0.00 | 0.00 |
December | 462.30 | 1080.38 | 515.71 | 273.23 | 242.47 | 0.00 | 0.00 |
Annual Sum or Average | 1215.34 | 535.91 | 815.47 | 446.20 | 369.27 | 0.00 | 0.00 |
Minimum of Months | 462.30 | 119.67 | 515.71 | 273.23 | 236.16 | 0.00 | 0.00 |
Maximum of Months | 1976.96 | 1080.38 | 1060.77 | 590.13 | 484.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2650.71 | 1482.39 | 1980.18 | 1500.19 | 479.99 | 0.00 | 0.00 |
February | 2515.18 | 1309.48 | 1836.84 | 1294.94 | 541.90 | 0.00 | 0.00 |
March | 2125.08 | 1125.69 | 1492.81 | 860.75 | 632.07 | 0.00 | 0.00 |
April | 1632.49 | 694.41 | 1012.13 | 377.65 | 634.48 | 0.00 | 0.00 |
May | 1288.58 | 410.90 | 715.26 | 100.11 | 615.15 | 0.00 | 0.00 |
June | 1367.76 | 206.82 | 617.09 | 39.15 | 577.94 | 0.00 | 0.00 |
July | 1372.76 | 176.29 | 629.06 | 58.31 | 570.74 | 0.00 | 0.00 |
August | 1628.72 | 261.18 | 801.87 | 212.26 | 589.61 | 0.00 | 0.00 |
September | 2300.51 | 526.19 | 1251.62 | 650.26 | 601.37 | 0.00 | 0.00 |
October | 2667.64 | 832.68 | 1700.58 | 1149.70 | 550.88 | 0.00 | 0.00 |
November | 2849.02 | 1325.94 | 2046.49 | 1560.20 | 486.30 | 0.00 | 0.00 |
December | 2651.05 | 1610.80 | 2028.15 | 1522.42 | 505.73 | 0.00 | 0.00 |
Annual Sum or Average | 2084.49 | 827.85 | 1339.83 | 774.22 | 565.60 | 0.00 | 0.00 |
Minimum of Months | 1288.58 | 176.29 | 617.09 | 39.15 | 479.99 | 0.00 | 0.00 |
Maximum of Months | 2849.02 | 1610.80 | 2046.49 | 1560.20 | 634.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 595.56 | 1018.40 | 543.71 | 306.20 | 237.51 | 0.00 | 0.00 |
February | 726.99 | 901.51 | 613.52 | 326.10 | 287.42 | 0.00 | 0.00 |
March | 1095.21 | 763.63 | 836.05 | 448.09 | 387.96 | 0.00 | 0.00 |
April | 1455.74 | 475.31 | 960.97 | 519.03 | 441.93 | 0.00 | 0.00 |
May | 1742.57 | 299.29 | 1035.05 | 553.80 | 481.26 | 0.00 | 0.00 |
June | 1906.55 | 158.75 | 1007.54 | 541.16 | 466.38 | 0.00 | 0.00 |
July | 1691.88 | 132.92 | 894.12 | 444.31 | 449.82 | 0.00 | 0.00 |
August | 1570.17 | 185.50 | 865.91 | 441.30 | 424.61 | 0.00 | 0.00 |
September | 1517.99 | 360.15 | 885.53 | 493.33 | 392.20 | 0.00 | 0.00 |
October | 1129.54 | 566.32 | 762.30 | 444.90 | 317.40 | 0.00 | 0.00 |
November | 779.51 | 927.11 | 639.84 | 389.59 | 250.25 | 0.00 | 0.00 |
December | 530.09 | 1132.51 | 515.61 | 280.10 | 235.52 | 0.00 | 0.00 |
Annual Sum or Average | 1230.56 | 575.17 | 797.34 | 432.61 | 364.73 | 0.00 | 0.00 |
Minimum of Months | 530.09 | 132.92 | 515.61 | 280.10 | 235.52 | 0.00 | 0.00 |
Maximum of Months | 1906.55 | 1132.51 | 1035.05 | 553.80 | 481.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 55.48 | 1560.32 | 289.47 | 0.00 | 289.47 | 0.00 | 0.00 |
February | 149.73 | 1404.65 | 353.47 | 0.00 | 353.47 | 0.00 | 0.00 |
March | 308.03 | 1191.11 | 462.58 | 0.00 | 462.58 | 0.00 | 0.00 |
April | 605.33 | 702.66 | 534.10 | 4.21 | 529.90 | 0.00 | 0.00 |
May | 1018.20 | 409.95 | 633.47 | 45.81 | 587.66 | 0.00 | 0.00 |
June | 1425.22 | 220.39 | 673.58 | 82.93 | 590.66 | 0.00 | 0.00 |
July | 1311.10 | 176.40 | 622.52 | 60.60 | 561.92 | 0.00 | 0.00 |
August | 1018.16 | 241.07 | 524.92 | 10.73 | 514.19 | 0.00 | 0.00 |
September | 768.83 | 486.71 | 458.04 | 0.18 | 457.86 | 0.00 | 0.00 |
October | 391.48 | 792.66 | 380.30 | 0.00 | 380.30 | 0.00 | 0.00 |
November | 96.98 | 1361.62 | 307.02 | 0.00 | 307.02 | 0.00 | 0.00 |
December | 36.54 | 1722.58 | 287.23 | 0.00 | 287.23 | 0.00 | 0.00 |
Annual Sum or Average | 601.07 | 853.12 | 461.08 | 17.13 | 443.96 | 0.00 | 0.00 |
Minimum of Months | 36.54 | 176.40 | 287.23 | 0.00 | 287.23 | 0.00 | 0.00 |
Maximum of Months | 1425.22 | 1722.58 | 673.58 | 82.93 | 590.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 490.88 | 955.19 | 516.16 | 280.00 | 236.16 | 0.00 | 0.00 |
February | 765.81 | 856.56 | 690.57 | 393.62 | 296.95 | 0.00 | 0.00 |
March | 1035.91 | 728.85 | 852.63 | 469.77 | 382.86 | 0.00 | 0.00 |
April | 1490.13 | 440.93 | 1027.37 | 569.96 | 457.41 | 0.00 | 0.00 |
May | 1735.85 | 272.42 | 1060.19 | 576.18 | 484.02 | 0.00 | 0.00 |
June | 1964.92 | 144.41 | 1060.79 | 590.14 | 470.65 | 0.00 | 0.00 |
July | 1769.25 | 117.46 | 951.30 | 497.32 | 453.98 | 0.00 | 0.00 |
August | 1621.40 | 159.18 | 905.21 | 463.28 | 441.93 | 0.00 | 0.00 |
September | 1496.79 | 304.44 | 896.82 | 511.70 | 385.12 | 0.00 | 0.00 |
October | 965.34 | 499.93 | 689.71 | 372.23 | 317.48 | 0.00 | 0.00 |
November | 670.78 | 828.11 | 618.26 | 359.93 | 258.33 | 0.00 | 0.00 |
December | 462.35 | 1046.62 | 515.71 | 273.24 | 242.48 | 0.00 | 0.00 |
Annual Sum or Average | 1207.21 | 527.92 | 815.48 | 446.21 | 369.28 | 0.00 | 0.00 |
Minimum of Months | 462.35 | 117.46 | 515.71 | 273.24 | 236.16 | 0.00 | 0.00 |
Maximum of Months | 1964.92 | 1046.62 | 1060.79 | 590.14 | 484.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2623.02 | 1430.96 | 1980.26 | 1500.25 | 480.01 | 0.00 | 0.00 |
February | 2473.59 | 1300.76 | 1836.91 | 1294.99 | 541.92 | 0.00 | 0.00 |
March | 2070.62 | 1155.54 | 1492.87 | 860.78 | 632.08 | 0.00 | 0.00 |
April | 1593.00 | 729.91 | 1012.16 | 377.66 | 634.50 | 0.00 | 0.00 |
May | 1257.51 | 439.21 | 715.28 | 100.12 | 615.17 | 0.00 | 0.00 |
June | 1348.86 | 225.95 | 617.11 | 39.16 | 577.95 | 0.00 | 0.00 |
July | 1363.97 | 183.34 | 629.07 | 58.32 | 570.76 | 0.00 | 0.00 |
August | 1629.37 | 254.73 | 801.90 | 212.27 | 589.63 | 0.00 | 0.00 |
September | 2301.70 | 496.86 | 1251.67 | 650.28 | 601.38 | 0.00 | 0.00 |
October | 2663.75 | 782.81 | 1700.65 | 1149.75 | 550.90 | 0.00 | 0.00 |
November | 2840.74 | 1247.36 | 2046.57 | 1560.26 | 486.31 | 0.00 | 0.00 |
December | 2632.83 | 1539.66 | 2028.23 | 1522.48 | 505.75 | 0.00 | 0.00 |
Annual Sum or Average | 2063.73 | 813.14 | 1339.88 | 774.26 | 565.62 | 0.00 | 0.00 |
Minimum of Months | 1257.51 | 183.34 | 617.11 | 39.16 | 480.01 | 0.00 | 0.00 |
Maximum of Months | 2840.74 | 1539.66 | 2046.57 | 1560.26 | 634.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 587.54 | 1007.41 | 543.71 | 306.20 | 237.51 | 0.00 | 0.00 |
February | 709.47 | 917.11 | 613.52 | 326.10 | 287.42 | 0.00 | 0.00 |
March | 1067.99 | 787.15 | 836.06 | 448.10 | 387.96 | 0.00 | 0.00 |
April | 1434.50 | 488.28 | 960.98 | 519.04 | 441.94 | 0.00 | 0.00 |
May | 1725.35 | 304.72 | 1035.07 | 553.81 | 481.26 | 0.00 | 0.00 |
June | 1895.26 | 162.69 | 1007.56 | 541.17 | 466.39 | 0.00 | 0.00 |
July | 1687.82 | 130.74 | 894.14 | 444.31 | 449.82 | 0.00 | 0.00 |
August | 1570.66 | 175.25 | 865.92 | 441.31 | 424.62 | 0.00 | 0.00 |
September | 1520.11 | 339.63 | 885.54 | 493.34 | 392.21 | 0.00 | 0.00 |
October | 1132.88 | 535.05 | 762.31 | 444.91 | 317.40 | 0.00 | 0.00 |
November | 781.44 | 883.00 | 639.84 | 389.60 | 250.25 | 0.00 | 0.00 |
December | 527.99 | 1100.92 | 515.62 | 280.10 | 235.52 | 0.00 | 0.00 |
Annual Sum or Average | 1222.22 | 567.58 | 797.35 | 432.62 | 364.73 | 0.00 | 0.00 |
Minimum of Months | 527.99 | 130.74 | 515.62 | 280.10 | 235.52 | 0.00 | 0.00 |
Maximum of Months | 1895.26 | 1100.92 | 1035.07 | 553.81 | 481.26 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185443E+09 | 0.386154E+10 | 0.775318E+09 | 0.00 | 0.775318E+09 | 0.00 | 0.00 |
February | 0.400913E+09 | 0.316150E+10 | 0.855125E+09 | 0.00 | 0.855125E+09 | 0.00 | 0.00 |
March | 0.865144E+09 | 0.299191E+10 | 0.123898E+10 | 0.00 | 0.123898E+10 | 0.00 | 0.00 |
April | 0.158020E+10 | 0.172487E+10 | 0.138440E+10 | 10907061.00 | 0.137349E+10 | 0.00 | 0.00 |
May | 0.272272E+10 | 0.105855E+10 | 0.169668E+10 | 0.122694E+09 | 0.157399E+10 | 0.00 | 0.00 |
June | 0.367071E+10 | 0.561410E+09 | 0.174593E+10 | 0.214944E+09 | 0.153099E+10 | 0.00 | 0.00 |
July | 0.348207E+10 | 0.465822E+09 | 0.166736E+10 | 0.162305E+09 | 0.150506E+10 | 0.00 | 0.00 |
August | 0.270942E+10 | 0.623980E+09 | 0.140595E+10 | 28748062.13 | 0.137720E+10 | 0.00 | 0.00 |
September | 0.199109E+10 | 0.120426E+10 | 0.118724E+10 | 473753.19 | 0.118677E+10 | 0.00 | 0.00 |
October | 0.107705E+10 | 0.197764E+10 | 0.101860E+10 | 0.00 | 0.101860E+10 | 0.00 | 0.00 |
November | 0.292205E+09 | 0.323017E+10 | 0.795784E+09 | 0.00 | 0.795784E+09 | 0.00 | 0.00 |
December | 0.132017E+09 | 0.425852E+10 | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191090E+11 | 0.251202E+11 | 0.145407E+11 | 0.540072E+09 | 0.140006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.132017E+09 | 0.465822E+09 | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367071E+10 | 0.425852E+10 | 0.174593E+10 | 0.214944E+09 | 0.157399E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136295E+10 | 0.237512E+10 | 0.138248E+10 | 0.749943E+09 | 0.632532E+09 | 0.00 | 0.00 |
February | 0.189421E+10 | 0.194163E+10 | 0.167062E+10 | 0.952246E+09 | 0.718379E+09 | 0.00 | 0.00 |
March | 0.280573E+10 | 0.184973E+10 | 0.228367E+10 | 0.125823E+10 | 0.102544E+10 | 0.00 | 0.00 |
April | 0.386560E+10 | 0.109609E+10 | 0.266295E+10 | 0.147734E+10 | 0.118561E+10 | 0.00 | 0.00 |
May | 0.463784E+10 | 0.705904E+09 | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.00 | 0.00 |
June | 0.507154E+10 | 0.367613E+09 | 0.274957E+10 | 0.152964E+10 | 0.121993E+10 | 0.00 | 0.00 |
July | 0.471452E+10 | 0.309866E+09 | 0.254795E+10 | 0.133203E+10 | 0.121593E+10 | 0.00 | 0.00 |
August | 0.432610E+10 | 0.413028E+09 | 0.242452E+10 | 0.124084E+10 | 0.118367E+10 | 0.00 | 0.00 |
September | 0.387534E+10 | 0.759279E+09 | 0.232455E+10 | 0.132633E+10 | 0.998225E+09 | 0.00 | 0.00 |
October | 0.260231E+10 | 0.126026E+10 | 0.184732E+10 | 0.996980E+09 | 0.850338E+09 | 0.00 | 0.00 |
November | 0.178563E+10 | 0.198838E+10 | 0.160254E+10 | 0.932947E+09 | 0.669592E+09 | 0.00 | 0.00 |
December | 0.129515E+10 | 0.260074E+10 | 0.138129E+10 | 0.731838E+09 | 0.649451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.382369E+11 | 0.156676E+11 | 0.257171E+11 | 0.140716E+11 | 0.116455E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129515E+10 | 0.309866E+09 | 0.138129E+10 | 0.731838E+09 | 0.632532E+09 | 0.00 | 0.00 |
Maximum of Months | 0.507154E+10 | 0.260074E+10 | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.708695E+10 | 0.356347E+10 | 0.530392E+10 | 0.401827E+10 | 0.128565E+10 | 0.00 | 0.00 |
February | 0.603251E+10 | 0.294433E+10 | 0.444385E+10 | 0.313284E+10 | 0.131100E+10 | 0.00 | 0.00 |
March | 0.558202E+10 | 0.292246E+10 | 0.399850E+10 | 0.230552E+10 | 0.169298E+10 | 0.00 | 0.00 |
April | 0.413288E+10 | 0.179740E+10 | 0.262352E+10 | 0.978900E+09 | 0.164462E+10 | 0.00 | 0.00 |
May | 0.335890E+10 | 0.112731E+10 | 0.191581E+10 | 0.268151E+09 | 0.164766E+10 | 0.00 | 0.00 |
June | 0.347486E+10 | 0.571981E+09 | 0.159954E+10 | 0.101492E+09 | 0.149805E+10 | 0.00 | 0.00 |
July | 0.362569E+10 | 0.480869E+09 | 0.168491E+10 | 0.156194E+09 | 0.152872E+10 | 0.00 | 0.00 |
August | 0.434377E+10 | 0.657422E+09 | 0.214780E+10 | 0.568535E+09 | 0.157926E+10 | 0.00 | 0.00 |
September | 0.595694E+10 | 0.123306E+10 | 0.324432E+10 | 0.168554E+10 | 0.155878E+10 | 0.00 | 0.00 |
October | 0.715424E+10 | 0.197562E+10 | 0.455502E+10 | 0.307950E+10 | 0.147552E+10 | 0.00 | 0.00 |
November | 0.742653E+10 | 0.300523E+10 | 0.530472E+10 | 0.404420E+10 | 0.126052E+10 | 0.00 | 0.00 |
December | 0.713734E+10 | 0.383497E+10 | 0.543242E+10 | 0.407782E+10 | 0.135460E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.653126E+11 | 0.241141E+11 | 0.422543E+11 | 0.244170E+11 | 0.178374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335890E+10 | 0.480869E+09 | 0.159954E+10 | 0.101492E+09 | 0.126052E+10 | 0.00 | 0.00 |
Maximum of Months | 0.742653E+10 | 0.383497E+10 | 0.543242E+10 | 0.407782E+10 | 0.169298E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160128E+10 | 0.250362E+10 | 0.145628E+10 | 0.820137E+09 | 0.636146E+09 | 0.00 | 0.00 |
February | 0.173947E+10 | 0.207246E+10 | 0.148424E+10 | 0.788905E+09 | 0.695334E+09 | 0.00 | 0.00 |
March | 0.288096E+10 | 0.198336E+10 | 0.223930E+10 | 0.120019E+10 | 0.103911E+10 | 0.00 | 0.00 |
April | 0.372277E+10 | 0.120169E+10 | 0.249086E+10 | 0.134536E+10 | 0.114550E+10 | 0.00 | 0.00 |
May | 0.461211E+10 | 0.782890E+09 | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.00 | 0.00 |
June | 0.489537E+10 | 0.412818E+09 | 0.261159E+10 | 0.140271E+10 | 0.120888E+10 | 0.00 | 0.00 |
July | 0.450099E+10 | 0.343244E+09 | 0.239485E+10 | 0.119005E+10 | 0.120480E+10 | 0.00 | 0.00 |
August | 0.419354E+10 | 0.452675E+09 | 0.231929E+10 | 0.118200E+10 | 0.113729E+10 | 0.00 | 0.00 |
September | 0.393760E+10 | 0.842224E+09 | 0.229533E+10 | 0.127873E+10 | 0.101660E+10 | 0.00 | 0.00 |
October | 0.305148E+10 | 0.134098E+10 | 0.204176E+10 | 0.119164E+10 | 0.850124E+09 | 0.00 | 0.00 |
November | 0.205494E+10 | 0.210989E+10 | 0.165848E+10 | 0.100984E+10 | 0.648641E+09 | 0.00 | 0.00 |
December | 0.144654E+10 | 0.273379E+10 | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.386370E+11 | 0.167796E+11 | 0.251453E+11 | 0.136431E+11 | 0.115022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144654E+10 | 0.343244E+09 | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489537E+10 | 0.273379E+10 | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163443E+09 | 0.412642E+10 | 0.775303E+09 | 0.00 | 0.775303E+09 | 0.00 | 0.00 |
February | 0.413245E+09 | 0.324365E+10 | 0.855109E+09 | 0.00 | 0.855109E+09 | 0.00 | 0.00 |
March | 0.935094E+09 | 0.297582E+10 | 0.123896E+10 | 0.00 | 0.123896E+10 | 0.00 | 0.00 |
April | 0.166849E+10 | 0.167754E+10 | 0.138437E+10 | 10906740.41 | 0.137347E+10 | 0.00 | 0.00 |
May | 0.280941E+10 | 0.102124E+10 | 0.169665E+10 | 0.122690E+09 | 0.157396E+10 | 0.00 | 0.00 |
June | 0.375359E+10 | 0.523651E+09 | 0.174590E+10 | 0.214938E+09 | 0.153096E+10 | 0.00 | 0.00 |
July | 0.354354E+10 | 0.450953E+09 | 0.166733E+10 | 0.162300E+09 | 0.150503E+10 | 0.00 | 0.00 |
August | 0.272965E+10 | 0.646627E+09 | 0.140593E+10 | 28747217.14 | 0.137718E+10 | 0.00 | 0.00 |
September | 0.198237E+10 | 0.129102E+10 | 0.118722E+10 | 473739.26 | 0.118675E+10 | 0.00 | 0.00 |
October | 0.104045E+10 | 0.217948E+10 | 0.101858E+10 | 0.00 | 0.101858E+10 | 0.00 | 0.00 |
November | 0.247615E+09 | 0.360448E+10 | 0.795769E+09 | 0.00 | 0.795769E+09 | 0.00 | 0.00 |
December | 96604772.34 | 0.466710E+10 | 0.769299E+09 | 0.00 | 0.769299E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193835E+11 | 0.264080E+11 | 0.145404E+11 | 0.540056E+09 | 0.140004E+11 | 0.00 | 0.00 |
Minimum of Months | 96604772.34 | 0.450953E+09 | 0.769299E+09 | 0.00 | 0.769299E+09 | 0.00 | 0.00 |
Maximum of Months | 0.375359E+10 | 0.466710E+10 | 0.174590E+10 | 0.214938E+09 | 0.157396E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133466E+10 | 0.258643E+10 | 0.138245E+10 | 0.749929E+09 | 0.632525E+09 | 0.00 | 0.00 |
February | 0.189440E+10 | 0.204676E+10 | 0.167060E+10 | 0.952227E+09 | 0.718371E+09 | 0.00 | 0.00 |
March | 0.284551E+10 | 0.189832E+10 | 0.228364E+10 | 0.125821E+10 | 0.102543E+10 | 0.00 | 0.00 |
April | 0.391743E+10 | 0.111841E+10 | 0.266291E+10 | 0.147731E+10 | 0.118559E+10 | 0.00 | 0.00 |
May | 0.469442E+10 | 0.716520E+09 | 0.283958E+10 | 0.154320E+10 | 0.129638E+10 | 0.00 | 0.00 |
June | 0.512429E+10 | 0.365097E+09 | 0.274952E+10 | 0.152961E+10 | 0.121992E+10 | 0.00 | 0.00 |
July | 0.475107E+10 | 0.320513E+09 | 0.254791E+10 | 0.133200E+10 | 0.121591E+10 | 0.00 | 0.00 |
August | 0.434053E+10 | 0.450034E+09 | 0.242448E+10 | 0.124082E+10 | 0.118366E+10 | 0.00 | 0.00 |
September | 0.387291E+10 | 0.837906E+09 | 0.232452E+10 | 0.132630E+10 | 0.998215E+09 | 0.00 | 0.00 |
October | 0.258132E+10 | 0.141279E+10 | 0.184729E+10 | 0.996960E+09 | 0.850329E+09 | 0.00 | 0.00 |
November | 0.173213E+10 | 0.225386E+10 | 0.160251E+10 | 0.932929E+09 | 0.669585E+09 | 0.00 | 0.00 |
December | 0.123821E+10 | 0.289369E+10 | 0.138127E+10 | 0.731823E+09 | 0.649443E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.383269E+11 | 0.169003E+11 | 0.257167E+11 | 0.140713E+11 | 0.116454E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123821E+10 | 0.320513E+09 | 0.138127E+10 | 0.731823E+09 | 0.632525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.512429E+10 | 0.289369E+10 | 0.283958E+10 | 0.154320E+10 | 0.129638E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.709967E+10 | 0.397042E+10 | 0.530371E+10 | 0.401810E+10 | 0.128560E+10 | 0.00 | 0.00 |
February | 0.608472E+10 | 0.316790E+10 | 0.444368E+10 | 0.313271E+10 | 0.131096E+10 | 0.00 | 0.00 |
March | 0.569182E+10 | 0.301504E+10 | 0.399835E+10 | 0.230543E+10 | 0.169293E+10 | 0.00 | 0.00 |
April | 0.423141E+10 | 0.179991E+10 | 0.262343E+10 | 0.978859E+09 | 0.164457E+10 | 0.00 | 0.00 |
May | 0.345133E+10 | 0.110056E+10 | 0.191576E+10 | 0.268140E+09 | 0.164762E+10 | 0.00 | 0.00 |
June | 0.354522E+10 | 0.536087E+09 | 0.159950E+10 | 0.101487E+09 | 0.149802E+10 | 0.00 | 0.00 |
July | 0.367679E+10 | 0.472181E+09 | 0.168487E+10 | 0.156188E+09 | 0.152868E+10 | 0.00 | 0.00 |
August | 0.436236E+10 | 0.699553E+09 | 0.214773E+10 | 0.568511E+09 | 0.157922E+10 | 0.00 | 0.00 |
September | 0.596293E+10 | 0.136390E+10 | 0.324421E+10 | 0.168547E+10 | 0.155874E+10 | 0.00 | 0.00 |
October | 0.714499E+10 | 0.223025E+10 | 0.455484E+10 | 0.307937E+10 | 0.147548E+10 | 0.00 | 0.00 |
November | 0.738466E+10 | 0.343684E+10 | 0.530451E+10 | 0.404403E+10 | 0.126048E+10 | 0.00 | 0.00 |
December | 0.710058E+10 | 0.431438E+10 | 0.543221E+10 | 0.407765E+10 | 0.135455E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.657365E+11 | 0.261070E+11 | 0.422528E+11 | 0.244159E+11 | 0.178369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.345133E+10 | 0.472181E+09 | 0.159950E+10 | 0.101487E+09 | 0.126048E+10 | 0.00 | 0.00 |
Maximum of Months | 0.738466E+10 | 0.431438E+10 | 0.543221E+10 | 0.407765E+10 | 0.169293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159514E+10 | 0.272768E+10 | 0.145626E+10 | 0.820124E+09 | 0.636140E+09 | 0.00 | 0.00 |
February | 0.175874E+10 | 0.218092E+10 | 0.148422E+10 | 0.788892E+09 | 0.695328E+09 | 0.00 | 0.00 |
March | 0.293342E+10 | 0.204530E+10 | 0.223927E+10 | 0.120017E+10 | 0.103910E+10 | 0.00 | 0.00 |
April | 0.377328E+10 | 0.123200E+10 | 0.249083E+10 | 0.134534E+10 | 0.114549E+10 | 0.00 | 0.00 |
May | 0.466730E+10 | 0.801612E+09 | 0.277229E+10 | 0.148329E+10 | 0.128899E+10 | 0.00 | 0.00 |
June | 0.494178E+10 | 0.411474E+09 | 0.261156E+10 | 0.140269E+10 | 0.120887E+10 | 0.00 | 0.00 |
July | 0.453154E+10 | 0.356003E+09 | 0.239482E+10 | 0.119003E+10 | 0.120479E+10 | 0.00 | 0.00 |
August | 0.420554E+10 | 0.496842E+09 | 0.231926E+10 | 0.118198E+10 | 0.113728E+10 | 0.00 | 0.00 |
September | 0.393464E+10 | 0.933514E+09 | 0.229530E+10 | 0.127871E+10 | 0.101659E+10 | 0.00 | 0.00 |
October | 0.302536E+10 | 0.151683E+10 | 0.204174E+10 | 0.119162E+10 | 0.850116E+09 | 0.00 | 0.00 |
November | 0.202048E+10 | 0.240307E+10 | 0.165846E+10 | 0.100982E+10 | 0.648636E+09 | 0.00 | 0.00 |
December | 0.141979E+10 | 0.303330E+10 | 0.138102E+10 | 0.750213E+09 | 0.630809E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.388070E+11 | 0.181385E+11 | 0.251450E+11 | 0.136429E+11 | 0.115021E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141979E+10 | 0.356003E+09 | 0.138102E+10 | 0.750213E+09 | 0.630809E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494178E+10 | 0.303330E+10 | 0.277229E+10 | 0.148329E+10 | 0.128899E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148595E+09 | 0.417915E+10 | 0.775318E+09 | 0.00 | 0.775318E+09 | 0.00 | 0.00 |
February | 0.362225E+09 | 0.339813E+10 | 0.855125E+09 | 0.00 | 0.855125E+09 | 0.00 | 0.00 |
March | 0.825022E+09 | 0.319026E+10 | 0.123898E+10 | 0.00 | 0.123898E+10 | 0.00 | 0.00 |
April | 0.156901E+10 | 0.182129E+10 | 0.138440E+10 | 10907061.00 | 0.137349E+10 | 0.00 | 0.00 |
May | 0.272714E+10 | 0.109800E+10 | 0.169668E+10 | 0.122694E+09 | 0.157399E+10 | 0.00 | 0.00 |
June | 0.369418E+10 | 0.571250E+09 | 0.174593E+10 | 0.214944E+09 | 0.153099E+10 | 0.00 | 0.00 |
July | 0.351166E+10 | 0.472474E+09 | 0.166736E+10 | 0.162305E+09 | 0.150506E+10 | 0.00 | 0.00 |
August | 0.272703E+10 | 0.645677E+09 | 0.140595E+10 | 28748062.13 | 0.137720E+10 | 0.00 | 0.00 |
September | 0.199281E+10 | 0.126155E+10 | 0.118724E+10 | 473753.19 | 0.118677E+10 | 0.00 | 0.00 |
October | 0.104854E+10 | 0.212306E+10 | 0.101860E+10 | 0.00 | 0.101860E+10 | 0.00 | 0.00 |
November | 0.251383E+09 | 0.352932E+10 | 0.795784E+09 | 0.00 | 0.795784E+09 | 0.00 | 0.00 |
December | 97863424.07 | 0.461375E+10 | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189555E+11 | 0.269039E+11 | 0.145407E+11 | 0.540072E+09 | 0.140006E+11 | 0.00 | 0.00 |
Minimum of Months | 97863424.07 | 0.472474E+09 | 0.769314E+09 | 0.00 | 0.769314E+09 | 0.00 | 0.00 |
Maximum of Months | 0.369418E+10 | 0.461375E+10 | 0.174593E+10 | 0.214944E+09 | 0.157399E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131478E+10 | 0.255837E+10 | 0.138248E+10 | 0.749943E+09 | 0.632532E+09 | 0.00 | 0.00 |
February | 0.185265E+10 | 0.207220E+10 | 0.167062E+10 | 0.952246E+09 | 0.718379E+09 | 0.00 | 0.00 |
March | 0.277458E+10 | 0.195216E+10 | 0.228367E+10 | 0.125823E+10 | 0.102544E+10 | 0.00 | 0.00 |
April | 0.386240E+10 | 0.114290E+10 | 0.266295E+10 | 0.147734E+10 | 0.118561E+10 | 0.00 | 0.00 |
May | 0.464930E+10 | 0.729656E+09 | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.00 | 0.00 |
June | 0.509307E+10 | 0.374315E+09 | 0.274957E+10 | 0.152964E+10 | 0.121993E+10 | 0.00 | 0.00 |
July | 0.473875E+10 | 0.314601E+09 | 0.254795E+10 | 0.133203E+10 | 0.121593E+10 | 0.00 | 0.00 |
August | 0.434277E+10 | 0.426340E+09 | 0.242452E+10 | 0.124084E+10 | 0.118367E+10 | 0.00 | 0.00 |
September | 0.387968E+10 | 0.789114E+09 | 0.232455E+10 | 0.132633E+10 | 0.998225E+09 | 0.00 | 0.00 |
October | 0.258558E+10 | 0.133900E+10 | 0.184732E+10 | 0.996980E+09 | 0.850338E+09 | 0.00 | 0.00 |
November | 0.173865E+10 | 0.214646E+10 | 0.160254E+10 | 0.932947E+09 | 0.669592E+09 | 0.00 | 0.00 |
December | 0.123835E+10 | 0.280328E+10 | 0.138129E+10 | 0.731838E+09 | 0.649451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.380706E+11 | 0.166484E+11 | 0.257171E+11 | 0.140716E+11 | 0.116455E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123835E+10 | 0.314601E+09 | 0.138129E+10 | 0.731838E+09 | 0.632532E+09 | 0.00 | 0.00 |
Maximum of Months | 0.509307E+10 | 0.280328E+10 | 0.283962E+10 | 0.154323E+10 | 0.129639E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.702549E+10 | 0.383268E+10 | 0.530392E+10 | 0.401827E+10 | 0.128565E+10 | 0.00 | 0.00 |
February | 0.598411E+10 | 0.314680E+10 | 0.444385E+10 | 0.313284E+10 | 0.131100E+10 | 0.00 | 0.00 |
March | 0.554594E+10 | 0.309501E+10 | 0.399850E+10 | 0.230552E+10 | 0.169298E+10 | 0.00 | 0.00 |
April | 0.412906E+10 | 0.189192E+10 | 0.262352E+10 | 0.978900E+09 | 0.164462E+10 | 0.00 | 0.00 |
May | 0.336813E+10 | 0.117639E+10 | 0.191581E+10 | 0.268151E+09 | 0.164766E+10 | 0.00 | 0.00 |
June | 0.349625E+10 | 0.585659E+09 | 0.159954E+10 | 0.101492E+09 | 0.149805E+10 | 0.00 | 0.00 |
July | 0.365326E+10 | 0.491049E+09 | 0.168491E+10 | 0.156194E+09 | 0.152872E+10 | 0.00 | 0.00 |
August | 0.436410E+10 | 0.682257E+09 | 0.214780E+10 | 0.568535E+09 | 0.157926E+10 | 0.00 | 0.00 |
September | 0.596600E+10 | 0.128787E+10 | 0.324432E+10 | 0.168554E+10 | 0.155878E+10 | 0.00 | 0.00 |
October | 0.713459E+10 | 0.209667E+10 | 0.455502E+10 | 0.307950E+10 | 0.147552E+10 | 0.00 | 0.00 |
November | 0.736319E+10 | 0.323316E+10 | 0.530472E+10 | 0.404420E+10 | 0.126052E+10 | 0.00 | 0.00 |
December | 0.705178E+10 | 0.412382E+10 | 0.543242E+10 | 0.407782E+10 | 0.135460E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650819E+11 | 0.256433E+11 | 0.422543E+11 | 0.244170E+11 | 0.178374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.336813E+10 | 0.491049E+09 | 0.159954E+10 | 0.101492E+09 | 0.126052E+10 | 0.00 | 0.00 |
Maximum of Months | 0.736319E+10 | 0.412382E+10 | 0.543242E+10 | 0.407782E+10 | 0.169298E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157366E+10 | 0.269825E+10 | 0.145628E+10 | 0.820137E+09 | 0.636146E+09 | 0.00 | 0.00 |
February | 0.171636E+10 | 0.221867E+10 | 0.148424E+10 | 0.788905E+09 | 0.695334E+09 | 0.00 | 0.00 |
March | 0.286051E+10 | 0.210831E+10 | 0.223930E+10 | 0.120019E+10 | 0.103911E+10 | 0.00 | 0.00 |
April | 0.371822E+10 | 0.126562E+10 | 0.249086E+10 | 0.134536E+10 | 0.114550E+10 | 0.00 | 0.00 |
May | 0.462118E+10 | 0.816169E+09 | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.00 | 0.00 |
June | 0.491250E+10 | 0.421696E+09 | 0.261159E+10 | 0.140271E+10 | 0.120888E+10 | 0.00 | 0.00 |
July | 0.452066E+10 | 0.350178E+09 | 0.239485E+10 | 0.119005E+10 | 0.120480E+10 | 0.00 | 0.00 |
August | 0.420685E+10 | 0.469389E+09 | 0.231929E+10 | 0.118200E+10 | 0.113729E+10 | 0.00 | 0.00 |
September | 0.394013E+10 | 0.880319E+09 | 0.229533E+10 | 0.127873E+10 | 0.101660E+10 | 0.00 | 0.00 |
October | 0.303431E+10 | 0.143309E+10 | 0.204176E+10 | 0.119164E+10 | 0.850124E+09 | 0.00 | 0.00 |
November | 0.202549E+10 | 0.228872E+10 | 0.165848E+10 | 0.100984E+10 | 0.648641E+09 | 0.00 | 0.00 |
December | 0.141416E+10 | 0.294871E+10 | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.385440E+11 | 0.178991E+11 | 0.251453E+11 | 0.136431E+11 | 0.115022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141416E+10 | 0.350178E+09 | 0.138104E+10 | 0.750225E+09 | 0.630815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491250E+10 | 0.294871E+10 | 0.277232E+10 | 0.148332E+10 | 0.128900E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.447139E+10 | -0.423539E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -236000456.3 | 60.05 | 0.00 | 0.00 |
February | 0.405863E+10 | -0.384633E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -212295704.1 | 60.05 | 0.00 | 0.00 |
March | 0.462320E+10 | -0.438882E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234379905.0 | 60.05 | 0.00 | 0.00 |
April | 0.391832E+10 | -0.369339E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224932769.7 | 60.05 | 0.00 | 0.00 |
May | 0.387879E+10 | -0.364681E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231972761.1 | 60.05 | 0.00 | 0.00 |
June | 0.356682E+10 | -0.334238E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224437377.3 | 60.05 | 0.00 | 0.00 |
July | 0.323036E+10 | -0.299880E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231563228.5 | 60.05 | 0.00 | 0.00 |
August | 0.355212E+10 | -0.332008E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232036677.9 | 60.05 | 0.00 | 0.00 |
September | 0.336685E+10 | -0.314304E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223812531.6 | 60.05 | 0.00 | 0.00 |
October | 0.374533E+10 | -0.351336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231975138.6 | 60.05 | 0.00 | 0.00 |
November | 0.398118E+10 | -0.375521E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225973128.4 | 60.05 | 0.00 | 0.00 |
December | 0.420693E+10 | -0.397101E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235926643.0 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.465999E+11 | -0.438546E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.274531E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.323036E+10 | -0.438882E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -236000456.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.462320E+10 | -0.299880E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -212295704.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 8821.95 | 38.52 | 276.00 | 279.17 | 1909.70 | 26.36 | 156.83 | 262.83 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 9484.62 | 36.88 | 261.67 | 269.17 | 1397.59 | 22.44 | 122.17 | 246.67 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:19 | 1987.39 | 18.31 | 10.67 | 322.17 | 1045.64 | 20.02 | 106.17 | 292.00 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:10 | 1244.32 | 17.75 | 0.00 | 336.33 | 772.46 | 19.93 | 71.17 | 295.83 |
May | 408.83 | 0.53 | 0.48 | 01-MAY-06:49 | 1014.23 | 17.47 | 0.00 | 360.67 | 624.32 | 19.65 | 36.67 | 322.17 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:49 | 906.65 | 17.37 | 0.00 | 351.67 | 571.70 | 19.65 | 12.33 | 312.67 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-06:00 | 967.75 | 17.40 | 0.00 | 359.17 | 588.10 | 19.61 | 29.83 | 302.50 |
August | 377.83 | 0.53 | 0.48 | 01-AUG-06:49 | 1148.70 | 17.73 | 0.00 | 346.67 | 698.14 | 19.90 | 59.00 | 298.67 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1478.63 | 18.10 | 11.00 | 318.33 | 880.21 | 19.83 | 82.50 | 281.67 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:10 | 3608.43 | 24.79 | 131.00 | 311.50 | 1243.20 | 20.87 | 98.83 | 286.50 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8989.23 | 37.40 | 288.50 | 287.67 | 1562.25 | 24.74 | 129.17 | 274.00 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 7983.29 | 37.78 | 284.17 | 276.33 | 1880.50 | 26.40 | 166.83 | 269.67 |
Annual Sum or Average | 4125.67 | 0.52 | 3492.85 | 23.72 | 1263.00 | 3818.83 | 1034.31 | 21.31 | 1071.50 | 3445.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 906.65 | 17.37 | 0.00 | 269.17 | 571.70 | 19.61 | 12.33 | 246.67 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9484.62 | 38.52 | 288.50 | 360.67 | 1909.70 | 26.40 | 166.83 | 322.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:09 | 2407.51 | 22.30 | 92.50 | 247.00 | 1323.25 | 22.75 | 68.17 | 198.00 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-07:40 | 2893.74 | 22.19 | 89.67 | 249.83 | 1080.44 | 20.93 | 41.00 | 209.33 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-06:00 | 2631.53 | 21.07 | 101.33 | 309.67 | 1415.57 | 21.85 | 71.17 | 274.50 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 3335.15 | 20.95 | 109.83 | 336.83 | 1284.39 | 20.22 | 50.83 | 307.50 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2666.43 | 20.13 | 103.67 | 366.50 | 1471.41 | 21.29 | 72.67 | 335.00 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2716.73 | 20.16 | 100.00 | 357.67 | 1507.27 | 21.35 | 70.00 | 326.50 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 2404.28 | 20.01 | 99.33 | 366.00 | 1308.65 | 21.31 | 70.33 | 320.33 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 3011.64 | 20.65 | 109.67 | 348.33 | 1209.50 | 21.16 | 63.33 | 314.50 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2901.11 | 21.40 | 114.50 | 319.17 | 1133.42 | 20.63 | 57.67 | 283.50 |
October | 318.83 | 0.53 | 0.48 | 01-OCT-06:40 | 2512.01 | 20.91 | 89.83 | 288.50 | 1381.74 | 22.01 | 63.67 | 250.17 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:50 | 2011.91 | 19.95 | 77.50 | 256.00 | 1108.57 | 21.91 | 61.83 | 210.33 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-07:10 | 1820.17 | 21.11 | 81.33 | 249.33 | 943.21 | 21.53 | 60.50 | 211.00 |
Annual Sum or Average | 4125.67 | 0.53 | 2635.06 | 20.83 | 1169.17 | 3694.83 | 1278.03 | 21.37 | 751.17 | 3240.67 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1820.17 | 19.95 | 77.50 | 247.00 | 943.21 | 20.22 | 41.00 | 198.00 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 3335.15 | 22.30 | 114.50 | 366.50 | 1507.27 | 22.75 | 72.67 | 335.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.57 | 0.48 | 01-JAN-09:20 | 505.83 | 14.67 | 0.00 | 225.00 | 337.63 | 17.35 | 0.00 | 132.17 |
February | 268.33 | 0.55 | 0.48 | 01-FEB-09:50 | 575.94 | 15.45 | 0.00 | 231.83 | 383.79 | 17.98 | 0.00 | 160.67 |
March | 351.83 | 0.54 | 0.48 | 01-MAR-08:20 | 678.59 | 16.32 | 0.00 | 302.00 | 436.71 | 18.62 | 0.00 | 237.00 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 804.96 | 17.56 | 0.00 | 349.50 | 515.71 | 19.72 | 4.83 | 309.00 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:10 | 992.60 | 18.31 | 3.00 | 385.00 | 577.50 | 20.36 | 77.00 | 359.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:10 | 1065.92 | 21.41 | 84.33 | 381.50 | 606.23 | 20.70 | 86.00 | 358.33 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:10 | 1010.57 | 19.70 | 37.50 | 390.33 | 580.10 | 20.55 | 77.83 | 347.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 862.18 | 17.84 | 0.00 | 361.00 | 537.48 | 19.98 | 26.00 | 322.50 |
September | 365.83 | 0.54 | 0.48 | 01-SEP-08:20 | 675.20 | 16.73 | 0.00 | 308.83 | 442.66 | 18.98 | 0.17 | 242.00 |
October | 318.83 | 0.55 | 0.48 | 01-OCT-08:09 | 605.55 | 15.80 | 0.00 | 278.17 | 400.14 | 18.22 | 0.00 | 207.17 |
November | 295.83 | 0.58 | 0.48 | 01-NOV-13:20 | 490.49 | 14.69 | 0.00 | 234.83 | 331.01 | 17.32 | 0.00 | 132.83 |
December | 289.50 | 0.57 | 0.48 | 01-DEC-09:09 | 506.21 | 14.65 | 0.00 | 227.83 | 332.05 | 17.29 | 0.00 | 136.33 |
Annual Sum or Average | 4125.67 | 0.53 | 757.74 | 17.18 | 124.83 | 3675.83 | 470.00 | 19.09 | 271.83 | 2945.00 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 490.49 | 14.65 | 0.00 | 225.00 | 331.01 | 17.29 | 0.00 | 132.17 | |
Maximum of Months | 408.83 | 0.58 | 0.48 | 1065.92 | 21.41 | 84.33 | 390.33 | 606.23 | 20.70 | 86.00 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:20 | 1969.96 | 21.19 | 81.83 | 258.67 | 1102.20 | 23.03 | 66.00 | 209.83 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:50 | 2322.25 | 22.29 | 88.33 | 251.83 | 1260.46 | 22.84 | 61.33 | 210.33 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:20 | 2933.18 | 21.52 | 111.33 | 320.67 | 1122.71 | 20.51 | 52.67 | 281.83 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 3259.85 | 20.95 | 111.83 | 342.50 | 1304.28 | 20.36 | 51.83 | 309.83 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:19 | 2561.46 | 13.79 | 0.00 | 374.50 | 1430.70 | 17.47 | 0.00 | 345.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-07:19 | 2656.84 | 13.91 | 0.00 | 371.67 | 1466.70 | 17.60 | 0.00 | 337.83 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:19 | 2376.54 | 14.24 | 3.67 | 379.17 | 1311.30 | 17.64 | 0.00 | 332.33 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-07:30 | 2429.53 | 17.38 | 57.17 | 351.17 | 1268.98 | 17.73 | 3.67 | 311.17 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-08:30 | 2872.19 | 20.96 | 110.33 | 318.33 | 1141.42 | 20.51 | 56.17 | 281.00 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-08:20 | 2427.41 | 20.61 | 86.17 | 299.00 | 1336.57 | 22.63 | 69.00 | 259.67 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 1865.38 | 20.98 | 86.33 | 265.50 | 938.56 | 21.27 | 54.50 | 217.33 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-09:09 | 2046.82 | 23.01 | 105.67 | 255.83 | 839.13 | 21.90 | 53.33 | 214.67 |
Annual Sum or Average | 4125.67 | 0.52 | 2511.55 | 18.86 | 842.67 | 3788.83 | 1227.22 | 20.02 | 468.50 | 3311.33 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1865.38 | 13.79 | 0.00 | 251.83 | 839.13 | 17.47 | 0.00 | 209.83 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 3259.85 | 23.01 | 111.83 | 379.17 | 1466.70 | 23.03 | 69.00 | 345.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 8621.43 | 37.07 | 265.17 | 276.33 | 1777.26 | 23.90 | 97.17 | 261.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:09 | 9347.82 | 36.62 | 261.50 | 268.17 | 1287.05 | 19.73 | 35.33 | 244.00 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:19 | 1892.34 | 14.52 | 10.67 | 319.17 | 971.61 | 17.55 | 2.17 | 288.83 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:19 | 1186.55 | 14.23 | 0.00 | 333.17 | 732.04 | 17.81 | 0.00 | 292.00 |
May | 408.83 | 0.53 | 0.48 | 01-MAY-06:00 | 975.81 | 14.12 | 0.00 | 358.00 | 601.24 | 17.65 | 0.00 | 316.67 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:00 | 875.16 | 13.93 | 0.00 | 349.33 | 554.21 | 17.57 | 0.00 | 307.33 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-07:10 | 931.90 | 13.98 | 0.00 | 355.50 | 567.12 | 17.54 | 0.00 | 296.83 |
August | 377.83 | 0.53 | 0.48 | 01-AUG-06:00 | 1099.64 | 14.27 | 0.00 | 343.50 | 665.89 | 17.80 | 0.00 | 293.67 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1403.72 | 14.49 | 11.00 | 316.50 | 823.62 | 17.57 | 0.00 | 278.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:10 | 3490.79 | 22.14 | 131.00 | 310.83 | 1147.28 | 18.25 | 14.50 | 283.83 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 8847.78 | 37.11 | 288.33 | 287.00 | 1443.94 | 22.24 | 90.17 | 273.50 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 7823.20 | 37.53 | 284.00 | 275.17 | 1751.57 | 23.93 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.52 | 3405.23 | 21.09 | 1251.67 | 3792.67 | 969.33 | 19.01 | 340.83 | 3405.00 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 875.16 | 13.93 | 0.00 | 268.17 | 554.21 | 17.54 | 0.00 | 244.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9347.82 | 37.53 | 288.33 | 358.00 | 1777.26 | 23.93 | 101.50 | 316.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:09 | 2354.99 | 21.83 | 92.50 | 243.83 | 1279.95 | 22.53 | 63.50 | 195.00 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-07:40 | 2829.33 | 21.73 | 89.67 | 248.00 | 1030.36 | 20.72 | 41.00 | 207.17 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-06:00 | 2461.41 | 18.84 | 82.50 | 306.17 | 1358.67 | 21.66 | 71.17 | 272.33 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 3252.43 | 20.48 | 109.83 | 334.83 | 1219.70 | 20.03 | 50.83 | 305.00 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2508.33 | 18.39 | 87.50 | 363.33 | 1410.76 | 21.12 | 72.67 | 331.83 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-05:49 | 2644.34 | 19.65 | 99.50 | 356.67 | 1445.78 | 21.19 | 70.00 | 324.33 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-05:49 | 2279.17 | 18.31 | 84.17 | 362.67 | 1251.40 | 21.14 | 70.33 | 318.00 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 2931.97 | 20.19 | 109.67 | 346.67 | 1152.87 | 20.99 | 63.33 | 312.17 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-06:10 | 2835.97 | 20.93 | 114.50 | 315.50 | 1079.57 | 20.45 | 57.67 | 281.67 |
October | 318.83 | 0.53 | 0.48 | 01-OCT-06:40 | 2449.98 | 20.43 | 89.83 | 286.67 | 1330.54 | 21.81 | 63.67 | 247.17 |
November | 295.83 | 0.55 | 0.48 | 01-NOV-12:00 | 1954.42 | 19.43 | 77.50 | 253.00 | 1062.74 | 21.70 | 61.00 | 205.83 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-07:10 | 1767.43 | 20.62 | 81.33 | 246.83 | 902.16 | 21.31 | 51.50 | 206.67 |
Annual Sum or Average | 4125.67 | 0.53 | 2544.87 | 19.96 | 1118.50 | 3664.17 | 1223.58 | 21.18 | 736.67 | 3207.17 | ||
Minimum of Months | 268.33 | 0.52 | 0.48 | 1767.43 | 18.31 | 77.50 | 243.83 | 902.16 | 20.03 | 41.00 | 195.00 | |
Maximum of Months | 408.83 | 0.55 | 0.48 | 3252.43 | 21.83 | 114.50 | 363.33 | 1445.78 | 22.53 | 72.67 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.58 | 0.48 | 01-JAN-09:20 | 487.60 | 11.07 | 0.00 | 220.33 | 328.51 | 15.01 | 0.00 | 123.50 |
February | 268.33 | 0.56 | 0.48 | 01-FEB-09:00 | 555.90 | 12.04 | 0.00 | 227.00 | 373.83 | 15.84 | 0.00 | 154.33 |
March | 351.83 | 0.54 | 0.48 | 01-MAR-08:20 | 656.56 | 12.98 | 0.00 | 298.33 | 425.54 | 16.62 | 0.00 | 231.00 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 778.60 | 14.36 | 0.00 | 348.83 | 502.21 | 17.96 | 0.00 | 304.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:19 | 959.98 | 14.92 | 3.00 | 384.17 | 559.69 | 18.44 | 1.83 | 357.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:10 | 1031.08 | 18.59 | 83.33 | 380.50 | 588.40 | 18.62 | 2.00 | 354.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 976.26 | 16.48 | 37.50 | 388.50 | 592.12 | 19.95 | 37.50 | 349.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:10 | 832.85 | 14.52 | 0.00 | 359.17 | 521.96 | 18.12 | 0.00 | 317.50 |
September | 365.83 | 0.54 | 0.48 | 01-SEP-08:30 | 652.66 | 13.51 | 0.00 | 306.00 | 431.38 | 17.15 | 0.00 | 236.00 |
October | 318.83 | 0.55 | 0.48 | 01-OCT-08:20 | 584.95 | 12.46 | 0.00 | 275.33 | 389.87 | 16.19 | 0.00 | 199.00 |
November | 295.83 | 0.58 | 0.48 | 01-NOV-13:30 | 473.33 | 11.12 | 0.00 | 227.33 | 322.58 | 15.05 | 0.00 | 126.50 |
December | 289.50 | 0.58 | 0.48 | 01-DEC-09:20 | 487.30 | 11.08 | 0.00 | 224.00 | 322.38 | 14.94 | 0.00 | 123.00 |
Annual Sum or Average | 4125.67 | 0.53 | 732.19 | 13.87 | 123.83 | 3639.50 | 459.75 | 17.20 | 41.33 | 2876.33 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 473.33 | 11.07 | 0.00 | 220.33 | 322.38 | 14.94 | 0.00 | 123.00 | |
Maximum of Months | 408.83 | 0.58 | 0.48 | 1031.08 | 18.59 | 83.33 | 388.50 | 592.12 | 19.95 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-09:20 | 1913.08 | 20.78 | 81.83 | 256.83 | 999.41 | 21.57 | 54.50 | 204.00 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:50 | 2264.77 | 21.88 | 88.33 | 250.17 | 1215.60 | 22.73 | 61.33 | 208.50 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:30 | 2871.49 | 21.10 | 111.33 | 317.83 | 1070.74 | 20.37 | 52.67 | 280.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 3188.07 | 20.50 | 111.83 | 340.50 | 1245.92 | 20.20 | 51.83 | 306.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:30 | 2482.29 | 13.26 | 0.00 | 373.00 | 1373.69 | 17.28 | 0.00 | 342.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2588.95 | 13.36 | 0.00 | 369.50 | 1411.62 | 17.41 | 0.00 | 335.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:30 | 2310.40 | 13.69 | 3.67 | 377.00 | 1261.01 | 17.45 | 0.00 | 328.83 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-07:30 | 2355.80 | 16.89 | 57.17 | 349.00 | 1215.16 | 17.55 | 3.67 | 307.83 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:30 | 2807.68 | 20.52 | 110.17 | 314.83 | 1088.00 | 20.37 | 56.17 | 277.67 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-08:20 | 2360.58 | 20.18 | 86.17 | 297.50 | 1282.14 | 22.52 | 69.00 | 256.50 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 1812.35 | 20.57 | 86.33 | 261.67 | 894.99 | 21.17 | 54.33 | 212.67 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-09:09 | 1998.32 | 22.62 | 105.67 | 254.17 | 800.90 | 21.80 | 53.00 | 211.67 |
Annual Sum or Average | 4125.67 | 0.52 | 2446.57 | 18.39 | 842.50 | 3762.00 | 1172.17 | 19.78 | 456.50 | 3271.67 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1812.35 | 13.26 | 0.00 | 250.17 | 800.90 | 17.28 | 0.00 | 204.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 3188.07 | 22.62 | 111.83 | 377.00 | 1411.62 | 22.73 | 69.00 | 342.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 8621.39 | 37.07 | 265.17 | 276.33 | 1777.19 | 23.90 | 97.17 | 261.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:09 | 9347.76 | 36.62 | 261.50 | 268.17 | 1286.98 | 19.73 | 35.33 | 244.00 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-07:19 | 1892.26 | 14.52 | 10.67 | 319.17 | 971.55 | 17.55 | 2.17 | 288.83 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:19 | 1186.49 | 14.24 | 0.00 | 333.17 | 732.00 | 17.81 | 0.00 | 292.00 |
May | 408.83 | 0.53 | 0.48 | 01-MAY-06:00 | 975.77 | 14.13 | 0.00 | 358.00 | 601.20 | 17.65 | 0.00 | 316.67 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:00 | 875.13 | 13.93 | 0.00 | 349.33 | 554.18 | 17.57 | 0.00 | 307.33 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-07:10 | 931.87 | 13.98 | 0.00 | 355.50 | 567.09 | 17.54 | 0.00 | 296.83 |
August | 377.83 | 0.53 | 0.48 | 01-AUG-06:00 | 1099.59 | 14.27 | 0.00 | 343.50 | 665.85 | 17.80 | 0.00 | 293.67 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1403.66 | 14.49 | 11.00 | 316.50 | 823.57 | 17.57 | 0.00 | 278.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-07:10 | 3490.72 | 22.14 | 131.00 | 310.83 | 1147.22 | 18.25 | 14.50 | 283.83 |
November | 295.83 | 0.51 | 0.48 | 01-NOV-12:39 | 8847.75 | 37.11 | 288.33 | 287.00 | 1443.88 | 22.24 | 90.17 | 273.50 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 7823.18 | 37.53 | 284.00 | 275.17 | 1751.49 | 23.94 | 101.50 | 268.33 |
Annual Sum or Average | 4125.67 | 0.52 | 3405.18 | 21.10 | 1251.67 | 3792.67 | 969.28 | 19.02 | 340.83 | 3405.00 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 875.13 | 13.93 | 0.00 | 268.17 | 554.18 | 17.54 | 0.00 | 244.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 9347.76 | 37.53 | 288.33 | 358.00 | 1777.19 | 23.94 | 101.50 | 316.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:09 | 2354.98 | 21.83 | 92.50 | 243.83 | 1279.91 | 22.54 | 63.50 | 195.00 |
February | 268.33 | 0.53 | 0.48 | 01-FEB-07:40 | 2829.32 | 21.73 | 89.67 | 248.00 | 1030.32 | 20.72 | 41.00 | 207.17 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-06:00 | 2461.38 | 18.85 | 82.50 | 306.17 | 1358.63 | 21.66 | 71.17 | 272.33 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 3252.41 | 20.48 | 109.83 | 334.83 | 1219.65 | 20.04 | 50.83 | 305.00 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2508.31 | 18.39 | 87.50 | 363.33 | 1410.71 | 21.12 | 72.67 | 331.83 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-05:49 | 2644.33 | 19.65 | 99.50 | 356.67 | 1445.73 | 21.19 | 70.00 | 324.33 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-05:49 | 2279.15 | 18.31 | 84.17 | 362.67 | 1251.35 | 21.14 | 70.33 | 318.00 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 2931.94 | 20.19 | 109.67 | 346.67 | 1152.82 | 20.99 | 63.33 | 312.17 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-06:10 | 2835.95 | 20.93 | 114.50 | 315.50 | 1079.52 | 20.45 | 57.67 | 281.67 |
October | 318.83 | 0.53 | 0.48 | 01-OCT-06:40 | 2449.97 | 20.43 | 89.83 | 286.67 | 1330.50 | 21.81 | 63.67 | 247.17 |
November | 295.83 | 0.55 | 0.48 | 01-NOV-12:00 | 1954.42 | 19.43 | 77.50 | 253.00 | 1062.71 | 21.71 | 61.00 | 205.83 |
December | 289.50 | 0.54 | 0.48 | 01-DEC-07:10 | 1767.42 | 20.62 | 81.33 | 246.83 | 902.13 | 21.31 | 51.50 | 206.50 |
Annual Sum or Average | 4125.67 | 0.53 | 2544.85 | 19.96 | 1118.50 | 3664.17 | 1223.53 | 21.18 | 736.67 | 3207.00 | ||
Minimum of Months | 268.33 | 0.52 | 0.48 | 1767.42 | 18.31 | 77.50 | 243.83 | 902.13 | 20.04 | 41.00 | 195.00 | |
Maximum of Months | 408.83 | 0.55 | 0.48 | 3252.41 | 21.83 | 114.50 | 363.33 | 1445.73 | 22.54 | 72.67 | 331.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.58 | 0.48 | 01-JAN-09:20 | 487.60 | 11.07 | 0.00 | 220.33 | 328.50 | 15.01 | 0.00 | 123.50 |
February | 268.33 | 0.56 | 0.48 | 01-FEB-09:00 | 555.89 | 12.04 | 0.00 | 227.00 | 373.81 | 15.84 | 0.00 | 154.33 |
March | 351.83 | 0.54 | 0.48 | 01-MAR-08:20 | 656.54 | 12.98 | 0.00 | 298.33 | 425.52 | 16.62 | 0.00 | 231.00 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 778.59 | 14.36 | 0.00 | 348.83 | 502.19 | 17.96 | 0.00 | 304.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-06:19 | 959.96 | 14.92 | 3.00 | 384.17 | 559.66 | 18.44 | 1.83 | 357.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-06:10 | 1031.06 | 18.59 | 83.33 | 380.50 | 588.37 | 18.62 | 2.00 | 354.17 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 976.24 | 16.49 | 37.50 | 388.50 | 592.09 | 19.95 | 37.50 | 349.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-06:10 | 832.83 | 14.52 | 0.00 | 359.17 | 521.94 | 18.12 | 0.00 | 317.50 |
September | 365.83 | 0.54 | 0.48 | 01-SEP-08:30 | 652.65 | 13.51 | 0.00 | 306.00 | 431.36 | 17.15 | 0.00 | 236.00 |
October | 318.83 | 0.55 | 0.48 | 01-OCT-08:20 | 584.94 | 12.46 | 0.00 | 275.33 | 389.85 | 16.19 | 0.00 | 199.00 |
November | 295.83 | 0.58 | 0.48 | 01-NOV-13:30 | 473.33 | 11.12 | 0.00 | 227.33 | 322.56 | 15.05 | 0.00 | 126.33 |
December | 289.50 | 0.58 | 0.48 | 01-DEC-09:20 | 487.30 | 11.08 | 0.00 | 224.00 | 322.37 | 14.94 | 0.00 | 123.00 |
Annual Sum or Average | 4125.67 | 0.53 | 732.18 | 13.87 | 123.83 | 3639.50 | 459.72 | 17.20 | 41.33 | 2876.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 473.33 | 11.07 | 0.00 | 220.33 | 322.37 | 14.94 | 0.00 | 123.00 | |
Maximum of Months | 408.83 | 0.58 | 0.48 | 1031.06 | 18.59 | 83.33 | 388.50 | 592.09 | 19.95 | 37.50 | 357.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-09:20 | 1913.07 | 20.78 | 81.83 | 256.83 | 999.38 | 21.57 | 54.50 | 204.00 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:50 | 2264.75 | 21.88 | 88.33 | 250.17 | 1215.57 | 22.73 | 61.33 | 208.50 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:30 | 2871.46 | 21.10 | 111.33 | 317.83 | 1070.69 | 20.38 | 52.67 | 280.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 3188.05 | 20.50 | 111.83 | 340.50 | 1245.87 | 20.20 | 51.83 | 306.33 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:30 | 2482.26 | 13.26 | 0.00 | 373.00 | 1373.65 | 17.28 | 0.00 | 342.33 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2588.92 | 13.36 | 0.00 | 369.50 | 1411.57 | 17.41 | 0.00 | 335.17 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:30 | 2310.37 | 13.70 | 3.67 | 377.00 | 1260.96 | 17.45 | 0.00 | 328.83 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-07:30 | 2355.77 | 16.89 | 57.17 | 349.00 | 1215.11 | 17.55 | 3.67 | 307.83 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:30 | 2807.66 | 20.52 | 110.17 | 314.83 | 1087.96 | 20.37 | 56.17 | 277.67 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-08:20 | 2360.57 | 20.19 | 86.17 | 297.50 | 1282.10 | 22.52 | 69.00 | 256.50 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 1812.34 | 20.57 | 86.33 | 261.67 | 894.96 | 21.17 | 54.33 | 212.67 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-09:09 | 1998.31 | 22.63 | 105.67 | 254.17 | 800.87 | 21.80 | 53.00 | 211.67 |
Annual Sum or Average | 4125.67 | 0.52 | 2446.55 | 18.39 | 842.50 | 3762.00 | 1172.12 | 19.78 | 456.50 | 3271.67 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1812.34 | 13.26 | 0.00 | 250.17 | 800.87 | 17.28 | 0.00 | 204.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 3188.05 | 22.63 | 111.83 | 377.00 | 1411.57 | 22.73 | 69.00 | 342.33 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.620952E+09 | 10038.79 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394235E+09 | 10736.07 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190307E+09 | 7811.02 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 387728.11 | 972.72 | 12-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 305931.94 | 4.75 | 22-MAY-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 531298.99 | 5.10 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1979412.77 | 5.61 | 13-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1882697.82 | 5.39 | 21-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1349486.40 | 5.10 | 01-SEP-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 455081.30 | 5.16 | 02-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94838538.72 | 5779.54 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123325E+10 | 10759.74 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 305931.94 | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123325E+10 | 10759.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.821283E+09 | 7003.28 | 13-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.688731E+09 | 7064.16 | 22-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725952E+09 | 7124.99 | 17-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216562E+09 | 7142.46 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23935388.07 | 7042.01 | 02-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3366999.11 | 2948.40 | 25-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99056072.92 | 7048.48 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511757E+09 | 7178.96 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.909349E+09 | 6983.02 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.909349E+09 | 7178.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139636E+09 | 5237.15 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60461962.61 | 5238.05 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37390740.64 | 5234.82 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10188181.99 | 5232.09 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150010E+09 | 5238.32 | 29-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150010E+09 | 5238.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392253E+09 | 6636.70 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283916E+09 | 6634.19 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140262E+09 | 6630.82 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 546886.07 | 678.26 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28438607.66 | 6623.60 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413615E+09 | 6636.55 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413615E+09 | 6636.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171278E+09 | 5355.80 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126699E+09 | 5359.86 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54147997.64 | 5353.92 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13917495.11 | 5350.89 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193929E+09 | 5361.06 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.559972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193929E+09 | 5361.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124911E+10 | 11030.40 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797046E+09 | 11633.37 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458383E+09 | 8848.72 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21767988.77 | 3165.02 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 234551.92 | 4.55 | 23-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421655.83 | 4.79 | 19-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1669031.96 | 4.89 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1501324.64 | 4.70 | 31-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 950990.45 | 4.74 | 06-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1476715.51 | 618.66 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416850E+09 | 7367.64 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204231E+10 | 12033.68 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 234551.92 | 4.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204231E+10 | 12033.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3774078.98 | 8978.61 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10169847.16 | 15599.00 | 27-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13943926.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10169847.16 | 15599.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156495E+09 | 7513.38 | 26-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56414403.77 | 7507.98 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25792300.55 | 7500.20 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37409186.87 | 7491.98 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226544E+09 | 7532.04 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226544E+09 | 7532.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.255293E+09 | 5723.00 | 28-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75846994.10 | 5711.97 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35451418.24 | 5711.87 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61293421.88 | 5728.12 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353901E+09 | 5730.58 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.781786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353901E+09 | 5730.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.391364E+09 | 7141.15 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164469E+09 | 7142.18 | 16-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59857475.34 | 7121.91 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101618E+09 | 7144.13 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.600578E+09 | 7150.44 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.600578E+09 | 7150.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323259E+09 | 5870.10 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149462E+09 | 5880.04 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53266821.02 | 5871.08 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15996.21 | 106.64 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95336729.67 | 5870.33 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454169E+09 | 5895.01 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454169E+09 | 5895.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175542E+10 | 13944.01 | 27-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114982E+10 | 14094.04 | 03-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.732567E+09 | 11759.81 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61536529.73 | 5131.60 | 12-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 220969.13 | 4.91 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 507322.19 | 5.02 | 19-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1726625.28 | 5.39 | 31-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1504842.16 | 5.44 | 04-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 934363.04 | 5.15 | 14-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13927685.94 | 2377.14 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.655657E+09 | 9097.52 | 28-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257816E+10 | 14180.29 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.695198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 220969.13 | 4.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.257816E+10 | 14180.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.498598E+09 | 22938.62 | 17-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143198E+09 | 22896.50 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30996179.42 | 22896.02 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168106E+09 | 22934.86 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.835372E+09 | 22957.57 | 05-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.835372E+09 | 22957.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698651E+09 | 9109.40 | 17-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362699E+09 | 9223.95 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234929E+09 | 9100.60 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19909315.59 | 9069.14 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2014689.59 | 4408.12 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280760E+09 | 9103.09 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.896174E+09 | 9131.01 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896174E+09 | 9223.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.724277E+09 | 6675.15 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.322619E+09 | 6709.58 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167214E+09 | 6619.51 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2838049.48 | 3579.97 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6819104.34 | 6611.90 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265802E+09 | 6622.76 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.945134E+09 | 6642.53 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.945134E+09 | 6709.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140007E+10 | 8795.54 | 27-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744903E+09 | 8871.82 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352914E+09 | 8706.71 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18891809.79 | 8676.90 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4550442.58 | 6491.70 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533667E+09 | 8720.21 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186184E+10 | 8736.14 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186184E+10 | 8871.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100899E+10 | 7051.55 | 17-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.588422E+09 | 7041.07 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291752E+09 | 7022.65 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23467214.53 | 6955.78 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10689300.88 | 5142.84 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428832E+09 | 7045.86 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129727E+10 | 7067.30 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129727E+10 | 7067.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.964790E+09 | 0.957952E+09 | 17709.26 | 03-JAN-15:10 | 17709.26 | 0.00 |
February | 0.00 | 0.00 | 0.353587E+10 | 0.352208E+10 | 30060.37 | 21-FEB-16:00 | 30060.37 | 0.00 |
March | 0.00 | 0.00 | 0.852778E+10 | 0.851777E+10 | 36439.61 | 21-MAR-16:00 | 36439.61 | 0.00 |
April | 0.00 | 0.00 | 0.262664E+11 | 0.261364E+11 | 56629.44 | 21-APR-15:00 | 56629.44 | 0.00 |
May | 0.00 | 0.00 | 0.511563E+11 | 0.500298E+11 | 70374.17 | 30-MAY-15:10 | 70374.17 | 0.00 |
June | 0.00 | 0.00 | 0.697805E+11 | 0.676408E+11 | 75183.86 | 19-JUN-06:03 | 59970.96 | 0.00 |
July | 0.00 | 0.00 | 0.821514E+11 | 0.673349E+11 | 115418.17 | 20-JUL-14:55 | 40405.30 | 0.00 |
August | 0.00 | 0.00 | 0.759126E+11 | 0.664215E+11 | 108972.72 | 03-AUG-06:03 | 46404.12 | 0.00 |
September | 0.00 | 0.00 | 0.635476E+11 | 0.558565E+11 | 103645.62 | 23-SEP-06:03 | 45583.80 | 0.00 |
October | 0.00 | 0.00 | 0.329739E+11 | 0.297826E+11 | 77173.05 | 04-OCT-10:40 | 49123.60 | 0.00 |
November | 0.00 | 0.00 | 0.748216E+10 | 0.735757E+10 | 42274.82 | 03-NOV-16:00 | 42274.82 | 0.00 |
December | 0.00 | 0.00 | 0.358440E+09 | 0.356800E+09 | 8054.96 | 20-DEC-15:10 | 8054.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.422658E+12 | 0.383915E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.358440E+09 | 0.356800E+09 | 8054.96 | 8054.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.821514E+11 | 0.676408E+11 | 115418.17 | 70374.17 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.765057E+09 | 0.756460E+09 | 13583.29 | 12-JAN-15:00 | 13583.29 | 0.00 |
February | 0.00 | 0.00 | 0.319757E+10 | 0.318154E+10 | 24947.95 | 21-FEB-16:00 | 24947.95 | 0.00 |
March | 0.00 | 0.00 | 0.796811E+10 | 0.795862E+10 | 32786.96 | 21-MAR-16:00 | 32786.96 | 0.00 |
April | 0.00 | 0.00 | 0.246549E+11 | 0.245231E+11 | 54629.80 | 21-APR-15:00 | 54629.80 | 0.00 |
May | 0.00 | 0.00 | 0.466860E+11 | 0.457535E+11 | 67374.06 | 30-MAY-06:03 | 67374.06 | 0.00 |
June | 0.00 | 0.00 | 0.636910E+11 | 0.619894E+11 | 76491.70 | 19-JUN-06:03 | 61320.82 | 0.00 |
July | 0.00 | 0.00 | 0.713571E+11 | 0.593655E+11 | 108210.76 | 20-JUL-15:00 | 37889.38 | 0.00 |
August | 0.00 | 0.00 | 0.637291E+11 | 0.565664E+11 | 88410.77 | 05-AUG-05:03 | 52503.17 | 0.00 |
September | 0.00 | 0.00 | 0.515145E+11 | 0.458371E+11 | 80732.38 | 14-SEP-09:50 | 41926.62 | 0.00 |
October | 0.00 | 0.00 | 0.264679E+11 | 0.238833E+11 | 63849.38 | 02-OCT-04:02 | 63849.38 | 0.00 |
November | 0.00 | 0.00 | 0.598837E+10 | 0.583502E+10 | 34512.37 | 09-NOV-15:20 | 34512.37 | 0.00 |
December | 0.00 | 0.00 | 0.277516E+09 | 0.276606E+09 | 6024.18 | 20-DEC-15:00 | 6024.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366297E+12 | 0.335926E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.277516E+09 | 0.276606E+09 | 6024.18 | 6024.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.713571E+11 | 0.619894E+11 | 108210.76 | 67374.06 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.714516E+09 | 0.695983E+09 | 12434.84 | 03-JAN-15:00 | 12434.84 | 0.00 |
February | 0.00 | 0.00 | 0.306347E+10 | 0.303659E+10 | 26793.01 | 20-FEB-14:53 | 26793.01 | 0.00 |
March | 0.00 | 0.00 | 0.794904E+10 | 0.792476E+10 | 35697.67 | 21-MAR-16:00 | 35697.67 | 0.00 |
April | 0.00 | 0.00 | 0.267805E+11 | 0.265753E+11 | 63205.54 | 21-APR-14:40 | 63205.54 | 0.00 |
May | 0.00 | 0.00 | 0.511824E+11 | 0.499452E+11 | 78205.62 | 21-MAY-15:11 | 78205.62 | 0.00 |
June | 0.00 | 0.00 | 0.709625E+11 | 0.688332E+11 | 80293.61 | 15-JUN-14:40 | 80293.61 | 0.00 |
July | 0.00 | 0.00 | 0.783100E+11 | 0.655285E+11 | 123446.38 | 20-JUL-14:55 | 43219.31 | 0.00 |
August | 0.00 | 0.00 | 0.693731E+11 | 0.613897E+11 | 84112.43 | 07-AUG-04:02 | 84112.43 | 0.00 |
September | 0.00 | 0.00 | 0.551374E+11 | 0.488823E+11 | 84928.72 | 14-SEP-10:00 | 43135.15 | 0.00 |
October | 0.00 | 0.00 | 0.271807E+11 | 0.242468E+11 | 72878.74 | 03-OCT-13:50 | 64336.33 | 0.00 |
November | 0.00 | 0.00 | 0.544780E+10 | 0.524305E+10 | 34971.61 | 09-NOV-15:00 | 34971.61 | 0.00 |
December | 0.00 | 0.00 | 0.251911E+09 | 0.249285E+09 | 6005.81 | 23-DEC-15:00 | 6005.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.396353E+12 | 0.362551E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.251911E+09 | 0.249285E+09 | 6005.81 | 6005.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783100E+11 | 0.688332E+11 | 123446.38 | 84112.43 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3924.58 | 168608.75 | 09-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2505.54 | 165206.03 | 16-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1331.69 | 157600.44 | 01-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 140.16 | 59602.86 | 12-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 8916.41 | 02-MAY-06:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.43 | 7.53 | 29-JUN-17:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.60 | 8.87 | 26-JUL-19:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1.55 | 9.37 | 10-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2.27 | 3568.02 | 27-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.67 | 27984.60 | 25-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1415.27 | 142612.10 | 27-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5558.48 | 150258.43 | 14-DEC-07:02 |
Annual Sum or Average | 0.00 | 1244.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.43 | 7.53 | ||
Maximum of Months | 0.00 | 0.00 | 5558.48 | 168608.75 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1572.13 | 5747.43 | 30-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1580.72 | 5746.90 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1629.17 | 5639.55 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1415.96 | 5311.12 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1352.59 | 4934.44 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1280.57 | 4521.17 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1111.13 | 4216.23 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1230.69 | 4233.10 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1203.92 | 4514.90 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1302.91 | 4941.13 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1439.71 | 5341.54 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1473.62 | 5628.74 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1381.66 | ||||
Minimum of Months | 0.00 | 0.00 | 1111.13 | 4216.23 | ||
Maximum of Months | 0.00 | 0.00 | 1629.17 | 5747.43 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184059E+10 | 0.33 | 3204.08 | 12-JAN-15:30 | 0.92 |
February | 0.183665E+10 | 0.35 | 5421.72 | 22-FEB-07:02 | 1.26 |
March | 0.242675E+10 | 0.38 | 4810.08 | 17-MAR-06:02 | 1.17 |
April | 0.345182E+10 | 0.45 | 6972.28 | 21-APR-14:10 | 1.46 |
May | 0.542252E+10 | 0.57 | 10681.39 | 30-MAY-15:10 | 1.90 |
June | 0.704665E+10 | 0.68 | 11513.42 | 19-JUN-12:10 | 1.99 |
July | 0.697720E+10 | 0.66 | 11913.10 | 21-JUL-10:20 | 2.02 |
August | 0.703999E+10 | 0.67 | 11913.10 | 07-AUG-06:03 | 2.04 |
September | 0.582175E+10 | 0.60 | 9700.72 | 13-SEP-15:50 | 1.78 |
October | 0.433876E+10 | 0.50 | 9112.10 | 02-OCT-04:02 | 1.72 |
November | 0.275731E+10 | 0.40 | 5999.99 | 10-NOV-16:00 | 1.33 |
December | 0.177123E+10 | 0.33 | 2652.77 | 07-DEC-15:30 | 0.84 |
Annual Sum or Average | 0.507312E+11 | 0.49 | |||
Minimum of Months | 0.177123E+10 | 0.33 | 2652.77 | 0.84 | |
Maximum of Months | 0.704665E+10 | 0.68 | 11913.10 | 2.04 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146860E+10 | 0.32 | 2178.79 | 12-JAN-15:40 | 0.78 |
February | 0.146904E+10 | 0.34 | 2947.71 | 21-FEB-16:30 | 0.93 |
March | 0.202215E+10 | 0.38 | 4437.14 | 16-MAR-15:30 | 1.17 |
April | 0.307939E+10 | 0.45 | 6959.36 | 21-APR-15:00 | 1.53 |
May | 0.482099E+10 | 0.56 | 9649.48 | 30-MAY-14:40 | 1.88 |
June | 0.629089E+10 | 0.66 | 10243.03 | 19-JUN-14:30 | 1.94 |
July | 0.591442E+10 | 0.62 | 11001.61 | 20-JUL-14:55 | 2.02 |
August | 0.589538E+10 | 0.62 | 11001.61 | 07-AUG-04:02 | 2.04 |
September | 0.457209E+10 | 0.54 | 8194.84 | 21-SEP-15:40 | 1.69 |
October | 0.308100E+10 | 0.43 | 9255.20 | 02-OCT-04:02 | 1.83 |
November | 0.185391E+10 | 0.35 | 4504.63 | 09-NOV-16:10 | 1.17 |
December | 0.141345E+10 | 0.31 | 2524.41 | 04-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.418813E+11 | 0.47 | |||
Minimum of Months | 0.141345E+10 | 0.31 | 2178.79 | 0.78 | |
Maximum of Months | 0.629089E+10 | 0.66 | 11001.61 | 2.04 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146984E+10 | 0.31 | 2590.25 | 02-JAN-07:02 | 0.79 |
February | 0.142830E+10 | 0.33 | 2590.25 | 01-FEB-07:01 | 0.79 |
March | 0.189425E+10 | 0.36 | 4128.16 | 16-MAR-15:30 | 1.02 |
April | 0.283943E+10 | 0.41 | 6942.98 | 21-APR-14:40 | 1.39 |
May | 0.450416E+10 | 0.50 | 9912.49 | 30-MAY-15:00 | 1.72 |
June | 0.613418E+10 | 0.60 | 10376.21 | 19-JUN-14:30 | 1.77 |
July | 0.571587E+10 | 0.56 | 12912.52 | 20-JUL-14:35 | 2.02 |
August | 0.555050E+10 | 0.56 | 11591.78 | 07-AUG-04:02 | 1.91 |
September | 0.426034E+10 | 0.48 | 8561.91 | 20-SEP-15:30 | 1.57 |
October | 0.275481E+10 | 0.39 | 8313.08 | 02-OCT-04:02 | 1.54 |
November | 0.171405E+10 | 0.34 | 3910.48 | 09-NOV-15:50 | 0.98 |
December | 0.144869E+10 | 0.31 | 2590.25 | 04-DEC-06:02 | 0.79 |
Annual Sum or Average | 0.397144E+11 | 0.43 | |||
Minimum of Months | 0.142830E+10 | 0.31 | 2590.25 | 0.79 | |
Maximum of Months | 0.613418E+10 | 0.60 | 12912.52 | 2.02 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 75188032.56 | 67669229.31 | 554.35 | 27-JAN-07:01 | 498.92 | 498.92 | 39.17 | 1.66 |
February | 44591373.49 | 40132236.14 | 559.76 | 03-FEB-07:01 | 503.78 | 503.78 | 39.93 | 1.70 |
March | 27694989.07 | 24925490.16 | 543.40 | 02-MAR-07:01 | 489.06 | 489.06 | 37.86 | 1.57 |
April | 3499305.33 | 3149374.79 | 371.73 | 12-APR-06:03 | 334.55 | 334.55 | 34.48 | 0.56 |
May | 310204.16 | 279183.75 | 86.68 | 02-MAY-06:30 | 78.02 | 78.02 | 43.14 | 0.09 |
June | 11859.47 | 10673.52 | 0.08 | 20-JUN-09:50 | 0.07 | 0.07 | 37.86 | 0.00 |
July | 42949.24 | 38654.32 | 0.09 | 26-JUL-19:30 | 0.08 | 0.08 | 35.98 | 0.00 |
August | 38965.35 | 35068.81 | 0.09 | 10-AUG-07:00 | 0.08 | 0.08 | 34.78 | 0.00 |
September | 52695.92 | 47426.33 | 31.31 | 25-SEP-06:07 | 28.18 | 28.18 | 34.05 | 0.03 |
October | 1520318.48 | 1368286.64 | 290.95 | 25-OCT-06:03 | 261.86 | 261.86 | 42.63 | 0.39 |
November | 27773299.01 | 24995969.11 | 537.21 | 28-NOV-07:02 | 483.49 | 483.49 | 39.10 | 1.51 |
December | 0.105331E+09 | 94798047.01 | 578.15 | 27-DEC-07:01 | 520.33 | 520.33 | 42.83 | 1.81 |
Annual Sum or Average | 0.286055E+09 | 0.257450E+09 | ||||||
Minimum of Months | 11859.47 | 10673.52 | 0.08 | 0.07 | 0.07 | 34.05 | 0.00 | |
Maximum of Months | 0.105331E+09 | 94798047.01 | 578.15 | 520.33 | 520.33 | 43.14 | 1.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.29 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.35 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:02 | 2.06 | 2.06 | 57.39 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.29 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.69 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.78 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.98 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.04 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.92 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.52 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.56 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.36 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.29 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.52 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 3924.58 | 168608.75 | 09-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.31 | 26.31 | 2505.54 | 165206.03 | 16-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.42 | 26.42 | 1331.69 | 157600.44 | 01-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 35.28 | 35.28 | 140.16 | 59602.86 | 12-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 37.03 | 37.03 | 9.32 | 8916.41 | 02-MAY-06:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 38.08 | 38.08 | 0.43 | 7.53 | 29-JUN-17:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.48 | 37.48 | 1.60 | 8.87 | 26-JUL-19:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 35.55 | 35.55 | 1.55 | 9.37 | 10-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 34.29 | 34.29 | 2.27 | 3568.02 | 27-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33.07 | 33.07 | 51.67 | 27984.60 | 25-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 34.75 | 34.75 | 1415.27 | 142612.10 | 27-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22.82 | 22.82 | 5558.48 | 150258.43 | 14-DEC-07:02 |
Annual Sum or Average | 0.00 | 1244.23 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.82 | 22.82 | 0.43 | 7.53 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 5558.48 | 168608.75 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.29 | 58.29 | 1572.13 | 5747.43 | 30-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.81 | 57.81 | 1580.72 | 5746.90 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.84 | 57.84 | 1629.17 | 5639.55 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.96 | 57.96 | 1415.96 | 5311.12 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.51 | 58.51 | 1352.59 | 4934.44 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.28 | 58.28 | 1280.57 | 4521.17 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.40 | 58.40 | 1111.13 | 4216.23 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.44 | 58.44 | 1230.69 | 4233.10 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.39 | 58.39 | 1203.92 | 4514.90 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.57 | 57.57 | 1302.91 | 4941.13 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.12 | 58.12 | 1439.71 | 5341.54 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.96 | 57.96 | 1473.62 | 5628.74 | 29-DEC-12:13 |
Annual Sum or Average | 0.00 | 1381.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.57 | 57.57 | 1111.13 | 4216.23 | ||
Maximum of Months | 0.00 | 0.00 | 58.51 | 58.51 | 1629.17 | 5747.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.214540E+10 | 0.00 | 0.00 | 0.208358E+10 | 0.00 | 0.00 |
February | 0.155404E+10 | 0.00 | 0.00 | 0.268931E+10 | 0.00 | 0.00 |
March | 0.114806E+10 | 0.00 | 0.00 | 0.444002E+10 | 0.00 | 0.00 |
April | 0.217497E+09 | 0.00 | 0.00 | 0.964150E+10 | 0.00 | 0.00 |
May | 24241320.01 | 0.00 | 0.00 | 0.177171E+11 | 0.00 | 0.00 |
June | 531298.99 | 0.00 | 0.00 | 0.251881E+11 | 0.00 | 0.00 |
July | 1979412.77 | 0.00 | 0.00 | 0.272632E+11 | 0.00 | 0.00 |
August | 1882697.82 | 0.00 | 0.00 | 0.254650E+11 | 0.00 | 0.00 |
September | 4716485.50 | 0.00 | 0.00 | 0.207820E+11 | 0.00 | 0.00 |
October | 99511154.22 | 0.00 | 0.00 | 0.118381E+11 | 0.00 | 0.00 |
November | 0.659140E+09 | 0.00 | 0.00 | 0.450137E+10 | 0.00 | 0.00 |
December | 0.290015E+10 | 0.00 | 0.00 | 0.186516E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.875715E+10 | 0.00 | 0.00 | 0.153475E+12 | 0.00 | 0.00 |
Minimum of Months | 531298.99 | 0.00 | 0.00 | 0.186516E+10 | 0.00 | 0.00 |
Maximum of Months | 0.290015E+10 | 0.00 | 0.00 | 0.272632E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.237930E+10 | 0.00 | 0.00 | 0.166326E+10 | 0.00 | 0.00 |
February | 0.124324E+10 | 0.00 | 0.00 | 0.224873E+10 | 0.00 | 0.00 |
March | 0.632751E+09 | 0.00 | 0.00 | 0.391690E+10 | 0.00 | 0.00 |
April | 21783984.99 | 0.00 | 0.00 | 0.891724E+10 | 0.00 | 0.00 |
May | 234551.92 | 0.00 | 0.00 | 0.160763E+11 | 0.00 | 0.00 |
June | 421655.83 | 0.00 | 0.00 | 0.228882E+11 | 0.00 | 0.00 |
July | 1669031.96 | 0.00 | 0.00 | 0.235558E+11 | 0.00 | 0.00 |
August | 1501324.64 | 0.00 | 0.00 | 0.214570E+11 | 0.00 | 0.00 |
September | 950990.45 | 0.00 | 0.00 | 0.167946E+11 | 0.00 | 0.00 |
October | 1476715.51 | 0.00 | 0.00 | 0.916436E+10 | 0.00 | 0.00 |
November | 0.712508E+09 | 0.00 | 0.00 | 0.327378E+10 | 0.00 | 0.00 |
December | 0.368768E+10 | 0.00 | 0.00 | 0.148657E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.868351E+10 | 0.00 | 0.00 | 0.131443E+12 | 0.00 | 0.00 |
Minimum of Months | 234551.92 | 0.00 | 0.00 | 0.148657E+10 | 0.00 | 0.00 |
Maximum of Months | 0.368768E+10 | 0.00 | 0.00 | 0.235558E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.608601E+10 | 0.00 | 0.00 | 0.165403E+10 | 0.00 | 0.00 |
February | 0.331166E+10 | 0.00 | 0.00 | 0.218721E+10 | 0.00 | 0.00 |
March | 0.181037E+10 | 0.00 | 0.00 | 0.380919E+10 | 0.00 | 0.00 |
April | 0.126643E+09 | 0.00 | 0.00 | 0.922722E+10 | 0.00 | 0.00 |
May | 220969.13 | 0.00 | 0.00 | 0.169423E+11 | 0.00 | 0.00 |
June | 507322.19 | 0.00 | 0.00 | 0.247671E+11 | 0.00 | 0.00 |
July | 1726625.28 | 0.00 | 0.00 | 0.252180E+11 | 0.00 | 0.00 |
August | 1504842.16 | 0.00 | 0.00 | 0.226443E+11 | 0.00 | 0.00 |
September | 934363.04 | 0.00 | 0.00 | 0.174571E+11 | 0.00 | 0.00 |
October | 38001223.33 | 0.00 | 0.00 | 0.907558E+10 | 0.00 | 0.00 |
November | 0.233282E+10 | 0.00 | 0.00 | 0.303079E+10 | 0.00 | 0.00 |
December | 0.841394E+10 | 0.00 | 0.00 | 0.151534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.221243E+11 | 0.00 | 0.00 | 0.137528E+12 | 0.00 | 0.00 |
Minimum of Months | 220969.13 | 0.00 | 0.00 | 0.151534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841394E+10 | 0.00 | 0.00 | 0.252180E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.184059E+10 | 0.964790E+09 | 0.214540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183665E+10 | 0.353587E+10 | 0.155404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242675E+10 | 0.852778E+10 | 0.114806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.345182E+10 | 0.262664E+11 | 0.217497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.542252E+10 | 0.511563E+11 | 24241320.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704665E+10 | 0.697805E+11 | 531298.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.697720E+10 | 0.821514E+11 | 1979412.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.703999E+10 | 0.759126E+11 | 1882697.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582175E+10 | 0.635476E+11 | 4716485.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433876E+10 | 0.329739E+11 | 99511154.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275731E+10 | 0.748216E+10 | 0.659140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177123E+10 | 0.358440E+09 | 0.290015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507312E+11 | 0.422658E+12 | 0.875715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177123E+10 | 0.358440E+09 | 531298.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.704665E+10 | 0.821514E+11 | 0.290015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146860E+10 | 0.765057E+09 | 0.237930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146904E+10 | 0.319757E+10 | 0.124324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202215E+10 | 0.796811E+10 | 0.632751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307939E+10 | 0.246549E+11 | 21783984.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482099E+10 | 0.466860E+11 | 234551.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.629089E+10 | 0.636910E+11 | 421655.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591442E+10 | 0.713571E+11 | 1669031.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.589538E+10 | 0.637291E+11 | 1501324.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457209E+10 | 0.515145E+11 | 950990.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308100E+10 | 0.264679E+11 | 1476715.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185391E+10 | 0.598837E+10 | 0.712508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141345E+10 | 0.277516E+09 | 0.368768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418813E+11 | 0.366297E+12 | 0.868351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141345E+10 | 0.277516E+09 | 234551.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.629089E+10 | 0.713571E+11 | 0.368768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146984E+10 | 0.714516E+09 | 0.608601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142830E+10 | 0.306347E+10 | 0.331166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189425E+10 | 0.794904E+10 | 0.181037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283943E+10 | 0.267805E+11 | 0.126643E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450416E+10 | 0.511824E+11 | 220969.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.613418E+10 | 0.709625E+11 | 507322.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.571587E+10 | 0.783100E+11 | 1726625.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.555050E+10 | 0.693731E+11 | 1504842.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426034E+10 | 0.551374E+11 | 934363.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275481E+10 | 0.271807E+11 | 38001223.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171405E+10 | 0.544780E+10 | 0.233282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144869E+10 | 0.251911E+09 | 0.841394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397144E+11 | 0.396353E+12 | 0.221243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142830E+10 | 0.251911E+09 | 220969.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.613418E+10 | 0.783100E+11 | 0.841394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.184059E+10 | 0.214540E+10 | 0.00 | 0.00 | 0.242986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183665E+10 | 0.155404E+10 | 0.00 | 0.00 | 0.852663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242675E+10 | 0.114806E+10 | 0.00 | 0.00 | 0.201327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.345182E+10 | 0.217497E+09 | 0.00 | 0.00 | 0.618967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.542252E+10 | 24241320.01 | 0.00 | 0.00 | 0.122946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.704665E+10 | 531298.99 | 0.00 | 0.00 | 0.181415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.697720E+10 | 1979412.77 | 0.00 | 0.00 | 0.202860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.703999E+10 | 1882697.82 | 0.00 | 0.00 | 0.184251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582175E+10 | 4716485.50 | 0.00 | 0.00 | 0.149603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433876E+10 | 99511154.22 | 0.00 | 0.00 | 0.749930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275731E+10 | 0.659140E+09 | 0.00 | 0.00 | 0.174407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177123E+10 | 0.290015E+10 | 0.00 | 0.00 | 93938624.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.507312E+11 | 0.875715E+10 | 0.00 | 0.00 | 0.102743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177123E+10 | 531298.99 | 0.00 | 0.00 | 93938624.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.704665E+10 | 0.290015E+10 | 0.00 | 0.00 | 0.202860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146860E+10 | 0.237930E+10 | 0.00 | 0.00 | 0.194665E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146904E+10 | 0.124324E+10 | 0.00 | 0.00 | 0.779691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202215E+10 | 0.632751E+09 | 0.00 | 0.00 | 0.189475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307939E+10 | 21783984.99 | 0.00 | 0.00 | 0.583785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482099E+10 | 234551.92 | 0.00 | 0.00 | 0.112553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.629089E+10 | 421655.83 | 0.00 | 0.00 | 0.165973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.591442E+10 | 1669031.96 | 0.00 | 0.00 | 0.176413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.589538E+10 | 1501324.64 | 0.00 | 0.00 | 0.155616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.457209E+10 | 950990.45 | 0.00 | 0.00 | 0.122225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308100E+10 | 1476715.51 | 0.00 | 0.00 | 0.608336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185391E+10 | 0.712508E+09 | 0.00 | 0.00 | 0.141987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141345E+10 | 0.368768E+10 | 0.00 | 0.00 | 73121743.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418813E+11 | 0.868351E+10 | 0.00 | 0.00 | 0.895614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141345E+10 | 234551.92 | 0.00 | 0.00 | 73121743.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.629089E+10 | 0.368768E+10 | 0.00 | 0.00 | 0.176413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146984E+10 | 0.608601E+10 | 0.00 | 0.00 | 0.184187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142830E+10 | 0.331166E+10 | 0.00 | 0.00 | 0.758917E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189425E+10 | 0.181037E+10 | 0.00 | 0.00 | 0.191494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283943E+10 | 0.126643E+09 | 0.00 | 0.00 | 0.638778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450416E+10 | 220969.13 | 0.00 | 0.00 | 0.124381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.613418E+10 | 507322.19 | 0.00 | 0.00 | 0.186329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.571587E+10 | 1726625.28 | 0.00 | 0.00 | 0.195022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.555050E+10 | 1504842.16 | 0.00 | 0.00 | 0.170938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426034E+10 | 934363.04 | 0.00 | 0.00 | 0.131967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275481E+10 | 38001223.33 | 0.00 | 0.00 | 0.632077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171405E+10 | 0.233282E+10 | 0.00 | 0.00 | 0.131674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144869E+10 | 0.841394E+10 | 0.00 | 0.00 | 66652727.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397144E+11 | 0.221243E+11 | 0.00 | 0.00 | 0.978138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142830E+10 | 220969.13 | 0.00 | 0.00 | 66652727.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.613418E+10 | 0.841394E+10 | 0.00 | 0.00 | 0.195022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105629E+10 | 0.00 | 0.00 | 32095823.32 | 0.00 | 0.00 | 0.162086E+11 | 0.00 | 0.59 |
February | 0.737248E+09 | 0.00 | 0.00 | 32586152.96 | 0.00 | 0.00 | 0.151950E+11 | 0.00 | 0.72 |
March | 0.591394E+09 | 0.00 | 0.00 | 39746784.71 | 0.00 | 0.00 | 0.175407E+11 | 0.00 | 0.93 |
April | 0.404259E+09 | 0.161197E+09 | 0.00 | 36715905.44 | 13767392.29 | 0.00 | 0.114717E+11 | 0.00 | 0.92 |
May | 0.313672E+09 | 0.593081E+09 | 0.00 | 27486287.75 | 69159159.89 | 0.00 | 0.522495E+10 | 0.00 | 0.76 |
June | 0.114830E+09 | 0.186114E+10 | 0.00 | 15415570.10 | 89129979.86 | 0.00 | 0.127409E+10 | 0.00 | 0.55 |
July | 8473229.00 | 0.678466E+10 | 0.00 | 927538.91 | 0.363087E+09 | 0.00 | 58969863.61 | 0.00 | 0.51 |
August | 57606665.96 | 0.296138E+10 | 0.00 | 13262210.30 | 0.132692E+09 | 0.00 | 0.137567E+10 | 0.00 | 0.71 |
September | 0.321360E+09 | 0.199751E+10 | 0.00 | 20833024.42 | 0.169641E+09 | 0.00 | 0.299454E+10 | 0.00 | 0.73 |
October | 0.553079E+09 | 0.457976E+09 | 0.00 | 39773554.52 | 37597777.04 | 0.00 | 0.133540E+11 | 0.00 | 1.10 |
November | 0.116412E+10 | 0.00 | 0.00 | 38351778.03 | 0.00 | 0.00 | 0.181813E+11 | 0.00 | 0.93 |
December | 0.110967E+10 | 0.00 | 0.00 | 31920417.98 | 0.00 | 0.00 | 0.161802E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.643201E+10 | 0.148169E+11 | 0.00 | 0.329115E+09 | 0.875074E+09 | 0.00 | 0.119060E+12 | 0.00 | 0.75 |
Minimum of Months | 8473229.00 | 0.00 | 0.00 | 927538.91 | 0.00 | 0.00 | 58969863.61 | 0.00 | 0.51 |
Maximum of Months | 0.116412E+10 | 0.678466E+10 | 0.00 | 39773554.52 | 0.363087E+09 | 0.00 | 0.181813E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.722147E+10 | 0.00 | 0.00 | 4027290.95 | 0.00 | 947604.81 | 0.382961E+10 | 0.00 | 0.38 |
February | 0.499863E+10 | 0.00 | 0.00 | 7302819.82 | 0.00 | 0.00 | 0.511580E+10 | 0.00 | 0.47 |
March | 0.401437E+10 | 0.00 | 0.00 | 14411191.15 | 0.00 | 0.00 | 0.774378E+10 | 0.00 | 0.61 |
April | 0.123403E+10 | 77975400.34 | 0.00 | 20816842.85 | 47808070.87 | 0.00 | 0.664115E+10 | 0.00 | 0.61 |
May | 0.685099E+09 | 0.399529E+09 | 0.00 | 18739812.17 | 65867635.55 | 0.00 | 0.325494E+10 | 0.00 | 0.54 |
June | 0.215182E+09 | 0.144230E+10 | 0.00 | 11309690.63 | 74248015.69 | 0.00 | 0.879819E+09 | 0.00 | 0.43 |
July | 6281785.02 | 0.485869E+10 | 0.00 | 928021.65 | 0.356254E+09 | 0.00 | 45377257.77 | 0.00 | 0.40 |
August | 0.131408E+09 | 0.206677E+10 | 0.00 | 10255236.83 | 0.118147E+09 | 0.00 | 0.939301E+09 | 0.00 | 0.53 |
September | 0.361753E+09 | 0.132381E+10 | 0.00 | 13792769.15 | 0.144657E+09 | 0.00 | 0.179929E+10 | 0.00 | 0.52 |
October | 0.126560E+10 | 0.315608E+09 | 0.00 | 20931292.69 | 37038034.63 | 0.00 | 0.733307E+10 | 0.00 | 0.71 |
November | 0.466519E+10 | 0.00 | 0.00 | 12059655.36 | 0.00 | 0.00 | 0.662955E+10 | 0.00 | 0.55 |
December | 0.810254E+10 | 0.00 | 0.00 | 2801865.60 | 0.00 | 1874492.13 | 0.300762E+10 | 0.00 | 0.35 |
Annual Sum or Average | 0.329015E+11 | 0.104847E+11 | 0.00 | 0.137376E+09 | 0.844019E+09 | 2822096.95 | 0.472193E+11 | 0.00 | 0.51 |
Minimum of Months | 6281785.02 | 0.00 | 0.00 | 928021.65 | 0.00 | 0.00 | 45377257.77 | 0.00 | 0.35 |
Maximum of Months | 0.810254E+10 | 0.485869E+10 | 0.00 | 20931292.69 | 0.356254E+09 | 1874492.13 | 0.774378E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.851796E+10 | 0.00 | 0.00 | 1123387.62 | 0.00 | 0.271480E+09 | 0.147531E+10 | 0.00 | 0.36 |
February | 0.647756E+10 | 0.00 | 0.00 | 3362151.33 | 0.00 | 61230103.51 | 0.284026E+10 | 0.00 | 0.45 |
March | 0.539599E+10 | 0.00 | 0.00 | 9064360.97 | 0.00 | 13357994.12 | 0.555509E+10 | 0.00 | 0.58 |
April | 0.180548E+10 | 52324129.52 | 0.00 | 18013493.53 | 19167491.02 | 0.00 | 0.542847E+10 | 0.00 | 0.62 |
May | 0.862487E+09 | 0.322679E+09 | 0.00 | 18341441.06 | 93503907.39 | 0.00 | 0.260236E+10 | 0.00 | 0.56 |
June | 0.228133E+09 | 0.129834E+10 | 0.00 | 11386128.24 | 84362570.56 | 0.00 | 0.615401E+09 | 0.00 | 0.42 |
July | 11853060.19 | 0.484554E+10 | 0.00 | 1091450.85 | 0.508946E+09 | 0.00 | 22061530.68 | 0.00 | 0.39 |
August | 0.117435E+09 | 0.208958E+10 | 0.00 | 9187784.77 | 0.195163E+09 | 0.00 | 0.628410E+09 | 0.00 | 0.51 |
September | 0.509533E+09 | 0.134373E+10 | 0.00 | 11033354.33 | 0.297398E+09 | 0.00 | 0.113573E+10 | 0.00 | 0.51 |
October | 0.199719E+10 | 0.338938E+09 | 0.00 | 14265899.57 | 56351800.39 | 0.00 | 0.531570E+10 | 0.00 | 0.68 |
November | 0.591243E+10 | 0.00 | 0.00 | 6347352.92 | 659432.85 | 67472467.98 | 0.406577E+10 | 0.00 | 0.51 |
December | 0.897343E+10 | 0.00 | 0.00 | 534783.89 | 0.00 | 0.342174E+09 | 0.955821E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.408095E+11 | 0.102911E+11 | 0.00 | 0.103752E+09 | 0.125555E+10 | 0.755714E+09 | 0.306404E+11 | 0.00 | 0.49 |
Minimum of Months | 11853060.19 | 0.00 | 0.00 | 534783.89 | 0.00 | 0.00 | 22061530.68 | 0.00 | 0.34 |
Maximum of Months | 0.897343E+10 | 0.484554E+10 | 0.00 | 18341441.06 | 0.508946E+09 | 0.342174E+09 | 0.555509E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154754E+10 | 0.00 | 0.00 | 3168.80 | 0.00 | 0.676981E+09 | 11023176.77 | 0.00 | 0.37 |
February | 0.154305E+10 | 0.00 | 0.00 | 185622.35 | 0.00 | 0.335546E+09 | 0.113157E+09 | 0.00 | 0.44 |
March | 0.152586E+10 | 0.00 | 0.00 | 1032586.37 | 0.00 | 0.186418E+09 | 0.553104E+09 | 0.00 | 0.57 |
April | 0.668182E+09 | 17959332.12 | 0.00 | 3514449.11 | 2465567.31 | 8968293.56 | 0.794542E+09 | 0.00 | 0.64 |
May | 0.233278E+09 | 0.104117E+09 | 0.00 | 4655372.73 | 21115847.69 | 0.00 | 0.523040E+09 | 0.00 | 0.65 |
June | 53686534.69 | 0.461914E+09 | 0.00 | 3213542.92 | 16838054.80 | 0.00 | 0.154714E+09 | 0.00 | 0.58 |
July | 3325853.54 | 0.145956E+10 | 0.00 | 317297.89 | 0.110428E+09 | 0.00 | 4660869.73 | 0.00 | 0.54 |
August | 35777573.14 | 0.576825E+09 | 0.00 | 2215756.92 | 46986441.03 | 0.00 | 0.133304E+09 | 0.00 | 0.62 |
September | 0.140577E+09 | 0.328927E+09 | 0.00 | 2434380.71 | 74607977.83 | 0.00 | 0.201972E+09 | 0.00 | 0.55 |
October | 0.768344E+09 | 83099059.92 | 0.00 | 2126856.05 | 13325028.64 | 1463470.96 | 0.651979E+09 | 0.00 | 0.66 |
November | 0.158261E+10 | 0.00 | 0.00 | 436721.24 | 142232.60 | 0.241733E+09 | 0.240892E+09 | 0.00 | 0.49 |
December | 0.131538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953698E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.941762E+10 | 0.303240E+10 | 0.00 | 20135755.09 | 0.285909E+09 | 0.240481E+10 | 0.338239E+10 | 0.00 | 0.54 |
Minimum of Months | 3325853.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.158261E+10 | 0.145956E+10 | 0.00 | 4655372.73 | 0.110428E+09 | 0.953698E+09 | 0.794542E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153216E+10 | 0.00 | 0.00 | 55803.68 | 0.00 | 0.344717E+09 | 86121604.23 | 0.00 | 0.52 |
February | 0.122049E+10 | 0.00 | 0.00 | 643757.01 | 0.00 | 0.123961E+09 | 0.468656E+09 | 0.00 | 0.65 |
March | 0.979506E+09 | 0.00 | 0.00 | 2520872.81 | 0.00 | 90536568.69 | 0.133225E+10 | 0.00 | 0.95 |
April | 0.337097E+09 | 16456876.10 | 0.00 | 5663876.17 | 1652245.10 | 900172.13 | 0.156690E+10 | 0.00 | 1.25 |
May | 0.128281E+09 | 0.101333E+09 | 0.00 | 6068998.23 | 12132042.59 | 0.00 | 0.925546E+09 | 0.00 | 1.25 |
June | 43996173.60 | 0.384108E+09 | 0.00 | 3431547.08 | 12039122.57 | 0.00 | 0.182647E+09 | 0.00 | 0.93 |
July | 2764091.96 | 0.137579E+10 | 0.00 | 273838.74 | 81738482.65 | 0.00 | 5118664.75 | 0.00 | 0.81 |
August | 29353739.89 | 0.602316E+09 | 0.00 | 2167321.06 | 32588955.16 | 0.00 | 0.138772E+09 | 0.00 | 0.99 |
September | 91844200.92 | 0.434306E+09 | 0.00 | 2993322.95 | 42360557.75 | 0.00 | 0.343012E+09 | 0.00 | 1.05 |
October | 0.515248E+09 | 70900147.43 | 0.00 | 3015951.82 | 10983281.89 | 1095250.37 | 0.108389E+10 | 0.00 | 1.10 |
November | 0.115305E+10 | 0.00 | 0.00 | 1130927.81 | 125833.24 | 0.127191E+09 | 0.652879E+09 | 0.00 | 0.74 |
December | 0.147138E+10 | 0.00 | 0.00 | 312.38 | 0.00 | 0.502048E+09 | 4282004.59 | 0.00 | 0.49 |
Annual Sum or Average | 0.750517E+10 | 0.298521E+10 | 0.00 | 27966529.76 | 0.193621E+09 | 0.119045E+10 | 0.679007E+10 | 0.00 | 0.89 |
Minimum of Months | 2764091.96 | 0.00 | 0.00 | 312.38 | 0.00 | 0.00 | 4282004.59 | 0.00 | 0.49 |
Maximum of Months | 0.153216E+10 | 0.137579E+10 | 0.00 | 6068998.23 | 81738482.65 | 0.502048E+09 | 0.156690E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.984052E+09 | 0.00 | 0.00 | 5232174.51 | 0.00 | 0.287962E+09 | 0.295054E+10 | 0.00 | 0.74 |
February | 0.894873E+09 | 0.00 | 0.00 | 5504931.86 | 0.00 | 0.141098E+09 | 0.274287E+10 | 0.00 | 0.88 |
March | 0.977213E+09 | 0.00 | 0.00 | 6124209.35 | 0.00 | 0.120934E+09 | 0.297293E+10 | 0.00 | 1.08 |
April | 0.579633E+09 | 32541678.05 | 0.00 | 6260263.81 | 1902324.97 | 10115591.43 | 0.153922E+10 | 0.00 | 0.94 |
May | 0.280545E+09 | 0.118913E+09 | 0.00 | 4961307.16 | 23203276.01 | 0.00 | 0.565633E+09 | 0.00 | 0.71 |
June | 68647061.59 | 0.450237E+09 | 0.00 | 3034897.56 | 21829383.20 | 0.00 | 0.137269E+09 | 0.00 | 0.56 |
July | 3666914.12 | 0.144198E+10 | 0.00 | 328256.90 | 0.130959E+09 | 0.00 | 4571618.75 | 0.00 | 0.53 |
August | 42494386.87 | 0.668029E+09 | 0.00 | 2678577.66 | 53051169.77 | 0.00 | 0.155490E+09 | 0.00 | 0.71 |
September | 0.107263E+09 | 0.516810E+09 | 0.00 | 4604756.55 | 70340765.90 | 0.00 | 0.409988E+09 | 0.00 | 0.83 |
October | 0.512734E+09 | 0.153250E+09 | 0.00 | 8571193.70 | 6464741.63 | 210453.21 | 0.244529E+10 | 0.00 | 1.41 |
November | 0.888733E+09 | 0.00 | 0.00 | 7483735.85 | 156818.31 | 0.141183E+09 | 0.362826E+10 | 0.00 | 1.21 |
December | 0.971285E+09 | 0.00 | 0.00 | 4785376.20 | 0.00 | 0.380430E+09 | 0.264725E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.631114E+10 | 0.338176E+10 | 0.00 | 59569681.12 | 0.307908E+09 | 0.108193E+10 | 0.201993E+11 | 0.00 | 0.85 |
Minimum of Months | 3666914.12 | 0.00 | 0.00 | 328256.90 | 0.00 | 0.00 | 4571618.75 | 0.00 | 0.53 |
Maximum of Months | 0.984052E+09 | 0.144198E+10 | 0.00 | 8571193.70 | 0.130959E+09 | 0.380430E+09 | 0.362826E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134307E+10 | 0.00 | 0.00 | 542518.84 | 0.00 | 0.538277E+09 | 0.445403E+09 | 0.00 | 0.62 |
February | 0.133895E+10 | 0.00 | 0.00 | 924729.15 | 0.00 | 0.272500E+09 | 0.534978E+09 | 0.00 | 0.77 |
March | 0.134753E+10 | 0.00 | 0.00 | 2494914.75 | 0.00 | 0.158647E+09 | 0.119720E+10 | 0.00 | 1.11 |
April | 0.659436E+09 | 22577827.25 | 0.00 | 4486923.83 | 1004134.66 | 10396418.84 | 0.100711E+10 | 0.00 | 1.13 |
May | 0.277102E+09 | 0.105374E+09 | 0.00 | 4242785.13 | 16563226.90 | 0.00 | 0.414111E+09 | 0.00 | 0.97 |
June | 67267587.75 | 0.423188E+09 | 0.00 | 2495022.47 | 15862358.16 | 0.00 | 0.102867E+09 | 0.00 | 0.76 |
July | 3870303.46 | 0.114727E+10 | 0.00 | 257729.83 | 0.134798E+09 | 0.00 | 3017203.66 | 0.00 | 0.69 |
August | 44532101.56 | 0.477513E+09 | 0.00 | 1855143.57 | 57679232.66 | 0.00 | 96861890.63 | 0.00 | 0.84 |
September | 0.142329E+09 | 0.288095E+09 | 0.00 | 2823428.18 | 81115034.69 | 0.00 | 0.217085E+09 | 0.00 | 0.84 |
October | 0.750703E+09 | 84496776.85 | 0.00 | 3114425.95 | 10928170.12 | 1346466.04 | 0.872360E+09 | 0.00 | 1.20 |
November | 0.136190E+10 | 0.00 | 0.00 | 1482575.69 | 143668.63 | 0.218439E+09 | 0.819190E+09 | 0.00 | 0.93 |
December | 0.122970E+10 | 0.00 | 0.00 | 333832.46 | 0.00 | 0.719977E+09 | 0.341007E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.856639E+10 | 0.254852E+10 | 0.00 | 25054029.86 | 0.318094E+09 | 0.191958E+10 | 0.605120E+10 | 0.00 | 0.87 |
Minimum of Months | 3870303.46 | 0.00 | 0.00 | 257729.83 | 0.00 | 0.00 | 3017203.66 | 0.00 | 0.57 |
Maximum of Months | 0.136190E+10 | 0.114727E+10 | 0.00 | 4486923.83 | 0.134798E+09 | 0.719977E+09 | 0.119720E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252004E+09 | 0.00 | 0.00 | 0.38 |
February | 0.185716E+10 | 0.00 | 0.00 | 15439.84 | 0.00 | 0.172665E+09 | 20822415.02 | 0.00 | 0.43 |
March | 0.193883E+10 | 0.00 | 0.00 | 155431.20 | 0.00 | 0.103755E+09 | 96886352.93 | 0.00 | 0.50 |
April | 0.868856E+09 | 16840863.42 | 0.00 | 1601306.97 | 10574858.14 | 0.00 | 0.386661E+09 | 0.00 | 0.48 |
May | 0.286196E+09 | 0.105894E+09 | 0.00 | 2583113.50 | 16541803.97 | 0.00 | 0.368047E+09 | 0.00 | 0.48 |
June | 76280858.52 | 0.415940E+09 | 0.00 | 2082322.54 | 24350420.96 | 0.00 | 0.134438E+09 | 0.00 | 0.47 |
July | 4871458.49 | 0.132430E+10 | 0.00 | 75333.52 | 0.111428E+09 | 0.00 | 5533759.03 | 0.00 | 0.47 |
August | 42803014.44 | 0.594544E+09 | 0.00 | 1850084.99 | 36827698.43 | 0.00 | 0.168792E+09 | 0.00 | 0.60 |
September | 0.155416E+09 | 0.375659E+09 | 0.00 | 2397780.67 | 42854673.07 | 0.00 | 0.285161E+09 | 0.00 | 0.56 |
October | 0.624045E+09 | 83896441.49 | 0.00 | 2939249.90 | 10797012.43 | 0.00 | 0.986638E+09 | 0.00 | 0.67 |
November | 0.182780E+10 | 0.00 | 0.00 | 623569.02 | 0.00 | 12680838.81 | 0.406563E+09 | 0.00 | 0.49 |
December | 0.209817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342893E+09 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.119259E+11 | 0.291708E+10 | 0.00 | 14323632.15 | 0.253374E+09 | 0.883997E+09 | 0.285954E+10 | 0.00 | 0.49 |
Minimum of Months | 4871458.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.214546E+10 | 0.132430E+10 | 0.00 | 2939249.90 | 0.111428E+09 | 0.342893E+09 | 0.986638E+09 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167953E+10 | 0.00 | 0.00 | 122889.67 | 0.00 | 82469739.97 | 0.168491E+09 | 0.00 | 0.48 |
February | 0.125461E+10 | 0.00 | 0.00 | 594905.82 | 0.00 | 32397672.24 | 0.418096E+09 | 0.00 | 0.57 |
March | 0.103098E+10 | 0.00 | 0.00 | 1871702.18 | 0.00 | 22801037.10 | 0.959903E+09 | 0.00 | 0.75 |
April | 0.338021E+09 | 23618909.04 | 0.00 | 4180619.35 | 2336828.21 | 0.00 | 0.125605E+10 | 0.00 | 0.96 |
May | 0.135207E+09 | 0.110582E+09 | 0.00 | 4360741.43 | 8693250.89 | 0.00 | 0.796677E+09 | 0.00 | 0.98 |
June | 51284074.06 | 0.374745E+09 | 0.00 | 2579765.40 | 14446576.81 | 0.00 | 0.178982E+09 | 0.00 | 0.78 |
July | 2372524.36 | 0.126986E+10 | 0.00 | 109530.70 | 61260042.86 | 0.00 | 8669152.99 | 0.00 | 0.72 |
August | 29205090.88 | 0.600757E+09 | 0.00 | 1985526.70 | 21161918.30 | 0.00 | 0.188701E+09 | 0.00 | 0.95 |
September | 91436616.24 | 0.417652E+09 | 0.00 | 3401607.69 | 24076473.33 | 0.00 | 0.475720E+09 | 0.00 | 1.04 |
October | 0.354992E+09 | 73275642.32 | 0.00 | 4238031.67 | 6594071.49 | 0.00 | 0.146690E+10 | 0.00 | 1.13 |
November | 0.101577E+10 | 0.00 | 0.00 | 2179725.22 | 0.00 | 1244041.67 | 0.109563E+10 | 0.00 | 0.76 |
December | 0.169982E+10 | 0.00 | 0.00 | 89600.05 | 0.00 | 0.123304E+09 | 0.139745E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.768323E+10 | 0.287049E+10 | 0.00 | 25714645.86 | 0.138569E+09 | 0.262217E+09 | 0.715357E+10 | 0.00 | 0.80 |
Minimum of Months | 2372524.36 | 0.00 | 0.00 | 89600.05 | 0.00 | 0.00 | 8669152.99 | 0.00 | 0.45 |
Maximum of Months | 0.169982E+10 | 0.126986E+10 | 0.00 | 4360741.43 | 61260042.86 | 0.123304E+09 | 0.146690E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131692E+10 | 0.00 | 0.00 | 2755012.69 | 0.00 | 0.492026E+09 | 0.176946E+10 | 0.00 | 0.60 |
February | 0.114320E+10 | 0.00 | 0.00 | 2516116.32 | 0.00 | 0.383439E+09 | 0.125377E+10 | 0.00 | 0.66 |
March | 0.133927E+10 | 0.00 | 0.00 | 2501159.93 | 0.00 | 0.401154E+09 | 0.105504E+10 | 0.00 | 0.72 |
April | 0.719570E+09 | 49301738.97 | 0.00 | 3331752.61 | 2908494.48 | 0.124385E+09 | 0.640864E+09 | 0.00 | 0.63 |
May | 0.344473E+09 | 0.148820E+09 | 0.00 | 2697385.18 | 16610157.59 | 10475130.42 | 0.303802E+09 | 0.00 | 0.53 |
June | 0.104501E+09 | 0.504714E+09 | 0.00 | 1847020.78 | 25979170.69 | 0.00 | 84392537.73 | 0.00 | 0.49 |
July | 7406588.62 | 0.141147E+10 | 0.00 | 26304.99 | 0.147621E+09 | 0.00 | 1036830.02 | 0.00 | 0.50 |
August | 65976343.28 | 0.787287E+09 | 0.00 | 1934132.64 | 41151259.42 | 0.00 | 0.146654E+09 | 0.00 | 0.69 |
September | 0.154865E+09 | 0.618667E+09 | 0.00 | 4106841.70 | 40769497.65 | 1452745.90 | 0.424593E+09 | 0.00 | 0.82 |
October | 0.420304E+09 | 0.172518E+09 | 0.00 | 8818042.01 | 3375294.44 | 55991223.25 | 0.238620E+10 | 0.00 | 1.34 |
November | 0.801285E+09 | 0.00 | 0.00 | 7629008.93 | 0.00 | 0.286793E+09 | 0.339815E+10 | 0.00 | 1.14 |
December | 0.129600E+10 | 0.00 | 0.00 | 2670654.38 | 0.00 | 0.579382E+09 | 0.175003E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.771377E+10 | 0.369278E+10 | 0.00 | 40833432.17 | 0.278414E+09 | 0.233510E+10 | 0.132140E+11 | 0.00 | 0.72 |
Minimum of Months | 7406588.62 | 0.00 | 0.00 | 26304.99 | 0.00 | 0.00 | 1036830.02 | 0.00 | 0.49 |
Maximum of Months | 0.133927E+10 | 0.141147E+10 | 0.00 | 8818042.01 | 0.147621E+09 | 0.579382E+09 | 0.339815E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163140E+10 | 0.00 | 0.00 | 460100.18 | 0.00 | 0.127923E+09 | 0.357855E+09 | 0.00 | 0.53 |
February | 0.143533E+10 | 0.00 | 0.00 | 556194.00 | 0.00 | 78841027.84 | 0.301819E+09 | 0.00 | 0.62 |
March | 0.140466E+10 | 0.00 | 0.00 | 1457558.12 | 0.00 | 26871303.55 | 0.611676E+09 | 0.00 | 0.80 |
April | 0.570259E+09 | 29185648.80 | 0.00 | 2981506.29 | 3175390.23 | 0.00 | 0.709705E+09 | 0.00 | 0.81 |
May | 0.219977E+09 | 0.122630E+09 | 0.00 | 2688325.49 | 10650770.83 | 0.00 | 0.369123E+09 | 0.00 | 0.74 |
June | 60588934.29 | 0.419832E+09 | 0.00 | 1674328.85 | 14569202.45 | 0.00 | 0.105435E+09 | 0.00 | 0.64 |
July | 2814082.85 | 0.113358E+10 | 0.00 | 52177.39 | 81962085.04 | 0.00 | 5047761.15 | 0.00 | 0.61 |
August | 32979766.93 | 0.542962E+09 | 0.00 | 1498281.01 | 23967261.09 | 0.00 | 0.132165E+09 | 0.00 | 0.81 |
September | 96467176.30 | 0.363844E+09 | 0.00 | 2658047.31 | 27591685.99 | 0.00 | 0.315678E+09 | 0.00 | 0.83 |
October | 0.383264E+09 | 87977586.63 | 0.00 | 4027611.58 | 5139495.28 | 0.00 | 0.123174E+10 | 0.00 | 1.13 |
November | 0.122301E+10 | 0.00 | 0.00 | 1915123.07 | 0.00 | 7763411.12 | 0.101764E+10 | 0.00 | 0.84 |
December | 0.163482E+10 | 0.00 | 0.00 | 390384.47 | 0.00 | 0.155757E+09 | 0.349204E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.869557E+10 | 0.270001E+10 | 0.00 | 20359637.76 | 0.167056E+09 | 0.397156E+09 | 0.550709E+10 | 0.00 | 0.74 |
Minimum of Months | 2814082.85 | 0.00 | 0.00 | 52177.39 | 0.00 | 0.00 | 5047761.15 | 0.00 | 0.50 |
Maximum of Months | 0.163482E+10 | 0.113358E+10 | 0.00 | 4027611.58 | 81962085.04 | 0.155757E+09 | 0.123174E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199096E+10 | 0.00 | 0.00 | 21003.56 | 0.00 | 0.269412E+09 | 31117241.63 | 0.00 | 0.37 |
February | 0.170137E+10 | 0.00 | 0.00 | 270286.28 | 0.00 | 0.116303E+09 | 0.189000E+09 | 0.00 | 0.44 |
March | 0.161086E+10 | 0.00 | 0.00 | 1264515.57 | 0.00 | 40137394.81 | 0.589075E+09 | 0.00 | 0.56 |
April | 0.595896E+09 | 31394701.99 | 0.00 | 3501578.65 | 4085494.90 | 0.00 | 0.883457E+09 | 0.00 | 0.60 |
May | 0.200990E+09 | 0.139201E+09 | 0.00 | 4293346.28 | 14084888.86 | 0.00 | 0.613090E+09 | 0.00 | 0.63 |
June | 62041938.82 | 0.532106E+09 | 0.00 | 3003429.42 | 15880539.14 | 0.00 | 0.197666E+09 | 0.00 | 0.60 |
July | 2394685.12 | 0.146861E+10 | 0.00 | 204441.04 | 82199955.02 | 0.00 | 9063885.03 | 0.00 | 0.55 |
August | 41138418.56 | 0.588274E+09 | 0.00 | 2327131.94 | 30403953.27 | 0.00 | 0.182432E+09 | 0.00 | 0.63 |
September | 0.144028E+09 | 0.340650E+09 | 0.00 | 2470590.74 | 37520380.88 | 0.00 | 0.257901E+09 | 0.00 | 0.55 |
October | 0.671753E+09 | 82114167.88 | 0.00 | 2742644.78 | 7218191.66 | 0.00 | 0.841683E+09 | 0.00 | 0.64 |
November | 0.165768E+10 | 0.00 | 0.00 | 677341.59 | 0.00 | 67677952.31 | 0.393565E+09 | 0.00 | 0.48 |
December | 0.187315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452970E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.105523E+11 | 0.318235E+10 | 0.00 | 20776309.84 | 0.191393E+09 | 0.946500E+09 | 0.418805E+10 | 0.00 | 0.53 |
Minimum of Months | 2394685.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.199096E+10 | 0.146861E+10 | 0.00 | 4293346.28 | 82199955.02 | 0.452970E+09 | 0.883457E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168811E+10 | 0.00 | 0.00 | 206881.96 | 0.00 | 0.168021E+09 | 0.229117E+09 | 0.00 | 0.53 |
February | 0.124176E+10 | 0.00 | 0.00 | 1029362.99 | 0.00 | 41059046.40 | 0.656664E+09 | 0.00 | 0.66 |
March | 0.105622E+10 | 0.00 | 0.00 | 2926736.75 | 0.00 | 19821343.43 | 0.146428E+10 | 0.00 | 0.96 |
April | 0.322009E+09 | 28622898.24 | 0.00 | 5703330.84 | 2819306.68 | 0.00 | 0.170033E+10 | 0.00 | 1.20 |
May | 0.132003E+09 | 0.124910E+09 | 0.00 | 5725459.58 | 9335460.54 | 0.00 | 0.101304E+10 | 0.00 | 1.19 |
June | 50218077.31 | 0.427443E+09 | 0.00 | 3426499.64 | 11131547.76 | 0.00 | 0.234381E+09 | 0.00 | 0.94 |
July | 3172095.44 | 0.133565E+10 | 0.00 | 204390.97 | 61387854.67 | 0.00 | 8729825.66 | 0.00 | 0.82 |
August | 39130662.91 | 0.576071E+09 | 0.00 | 2223383.11 | 22555174.16 | 0.00 | 0.188698E+09 | 0.00 | 1.00 |
September | 0.100667E+09 | 0.388834E+09 | 0.00 | 3190216.26 | 26528364.64 | 0.00 | 0.434401E+09 | 0.00 | 1.03 |
October | 0.526203E+09 | 65274846.95 | 0.00 | 3533713.58 | 6407294.59 | 0.00 | 0.122945E+10 | 0.00 | 1.09 |
November | 0.119446E+10 | 0.00 | 0.00 | 1678750.38 | 0.00 | 39674343.29 | 0.883584E+09 | 0.00 | 0.76 |
December | 0.173437E+10 | 0.00 | 0.00 | 81715.43 | 0.00 | 0.281264E+09 | 88503788.70 | 0.00 | 0.49 |
Annual Sum or Average | 0.808833E+10 | 0.294680E+10 | 0.00 | 29930441.50 | 0.140165E+09 | 0.549840E+09 | 0.813118E+10 | 0.00 | 0.89 |
Minimum of Months | 3172095.44 | 0.00 | 0.00 | 81715.43 | 0.00 | 0.00 | 8729825.66 | 0.00 | 0.49 |
Maximum of Months | 0.173437E+10 | 0.133565E+10 | 0.00 | 5725459.58 | 61387854.67 | 0.281264E+09 | 0.170033E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102105E+10 | 0.00 | 0.00 | 6571440.03 | 0.00 | 0.122219E+09 | 0.347297E+10 | 0.00 | 0.80 |
February | 0.916407E+09 | 0.00 | 0.00 | 6602461.45 | 0.00 | 45211385.40 | 0.300101E+10 | 0.00 | 0.93 |
March | 0.951182E+09 | 0.00 | 0.00 | 6846807.07 | 0.00 | 16393439.67 | 0.300883E+10 | 0.00 | 1.07 |
April | 0.507374E+09 | 59775856.69 | 0.00 | 5950569.52 | 3217319.16 | 0.00 | 0.154057E+10 | 0.00 | 0.86 |
May | 0.238723E+09 | 0.163014E+09 | 0.00 | 4453599.98 | 14872904.00 | 0.00 | 0.616119E+09 | 0.00 | 0.67 |
June | 67577516.69 | 0.529884E+09 | 0.00 | 2795368.22 | 17336934.63 | 0.00 | 0.173579E+09 | 0.00 | 0.57 |
July | 4006550.80 | 0.146329E+10 | 0.00 | 195780.79 | 89429377.90 | 0.00 | 6677368.64 | 0.00 | 0.54 |
August | 42159006.15 | 0.695530E+09 | 0.00 | 2721658.67 | 33741798.86 | 0.00 | 0.203597E+09 | 0.00 | 0.72 |
September | 0.107691E+09 | 0.542244E+09 | 0.00 | 4322560.59 | 36249336.70 | 0.00 | 0.452085E+09 | 0.00 | 0.80 |
October | 0.441707E+09 | 0.153810E+09 | 0.00 | 9218685.18 | 4197645.43 | 0.00 | 0.250185E+10 | 0.00 | 1.35 |
November | 0.839653E+09 | 0.00 | 0.00 | 9195086.53 | 0.00 | 24897841.01 | 0.391181E+10 | 0.00 | 1.24 |
December | 0.108997E+10 | 0.00 | 0.00 | 6166183.85 | 0.00 | 0.177768E+09 | 0.321772E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.622750E+10 | 0.360755E+10 | 0.00 | 65040201.88 | 0.199045E+09 | 0.386490E+09 | 0.221068E+11 | 0.00 | 0.86 |
Minimum of Months | 4006550.80 | 0.00 | 0.00 | 195780.79 | 0.00 | 0.00 | 6677368.64 | 0.00 | 0.54 |
Maximum of Months | 0.108997E+10 | 0.146329E+10 | 0.00 | 9218685.18 | 89429377.90 | 0.177768E+09 | 0.391181E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163559E+10 | 0.00 | 0.00 | 746588.49 | 0.00 | 0.218313E+09 | 0.514210E+09 | 0.00 | 0.61 |
February | 0.146274E+10 | 0.00 | 0.00 | 1082569.88 | 0.00 | 0.105962E+09 | 0.559821E+09 | 0.00 | 0.74 |
March | 0.137051E+10 | 0.00 | 0.00 | 2693627.38 | 0.00 | 31648011.83 | 0.116543E+10 | 0.00 | 1.05 |
April | 0.590077E+09 | 42690405.89 | 0.00 | 4151555.71 | 1994752.36 | 0.00 | 0.999802E+09 | 0.00 | 1.02 |
May | 0.250935E+09 | 0.149445E+09 | 0.00 | 3547750.72 | 8930330.55 | 0.00 | 0.441366E+09 | 0.00 | 0.89 |
June | 67412341.12 | 0.512411E+09 | 0.00 | 2179243.67 | 11207146.52 | 0.00 | 0.127475E+09 | 0.00 | 0.77 |
July | 4793826.41 | 0.119104E+10 | 0.00 | 128329.55 | 81278294.03 | 0.00 | 3641349.12 | 0.00 | 0.69 |
August | 48980649.91 | 0.506584E+09 | 0.00 | 1834554.97 | 30568938.36 | 0.00 | 0.126558E+09 | 0.00 | 0.84 |
September | 0.141973E+09 | 0.307643E+09 | 0.00 | 2599805.53 | 35237739.19 | 0.00 | 0.244485E+09 | 0.00 | 0.80 |
October | 0.617583E+09 | 84162159.76 | 0.00 | 3349962.30 | 5037295.71 | 0.00 | 0.974174E+09 | 0.00 | 1.12 |
November | 0.145912E+10 | 0.00 | 0.00 | 1745693.50 | 0.00 | 47294312.30 | 0.872847E+09 | 0.00 | 0.91 |
December | 0.158685E+10 | 0.00 | 0.00 | 509975.49 | 0.00 | 0.337292E+09 | 0.418409E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.923657E+10 | 0.279397E+10 | 0.00 | 24569657.19 | 0.174254E+09 | 0.740509E+09 | 0.644822E+10 | 0.00 | 0.83 |
Minimum of Months | 4793826.41 | 0.00 | 0.00 | 128329.55 | 0.00 | 0.00 | 3641349.12 | 0.00 | 0.56 |
Maximum of Months | 0.163559E+10 | 0.119104E+10 | 0.00 | 4151555.71 | 81278294.03 | 0.337292E+09 | 0.116543E+10 | 0.00 | 1.12 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.216036E+12 | 0.677435E+10 | 0.00 | 0.198047E+12 | 0.847160E+10 |
February | 0.218512E+12 | 0.540777E+10 | 0.00 | 0.171755E+12 | 0.154501E+11 |
March | 0.311921E+12 | 0.558710E+10 | 0.00 | 0.210430E+12 | 0.322669E+11 |
April | 0.318792E+12 | 0.269302E+10 | 0.00 | 0.161288E+12 | 0.963458E+11 |
May | 0.330109E+12 | 0.903294E+09 | 0.00 | 0.112832E+12 | 0.185029E+12 |
June | 0.318463E+12 | -0.109085E+10 | 0.00 | 0.199960E+11 | 0.257807E+12 |
July | 0.316808E+12 | -0.287177E+10 | 0.00 | -0.916510E+11 | 0.289251E+12 |
August | 0.295962E+12 | -0.133480E+10 | 0.00 | -0.184632E+11 | 0.260098E+12 |
September | 0.280115E+12 | -307715226.3 | 0.00 | 0.140087E+11 | 0.210583E+12 |
October | 0.261403E+12 | 0.222389E+10 | 0.00 | 0.158675E+12 | 0.106616E+12 |
November | 0.217273E+12 | 0.536167E+10 | 0.00 | 0.215884E+12 | 0.254180E+11 |
December | 0.187064E+12 | 0.641098E+10 | 0.00 | 0.185265E+12 | 0.863465E+10 |
Annual Sum or Average | 0.327246E+13 | 0.297569E+11 | 0.00 | 0.133806E+13 | 0.149597E+13 |
Minimum of Months | 0.187064E+12 | -0.287177E+10 | 0.00 | -0.916510E+11 | 0.847160E+10 |